Program Version:EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:21
Tabular Output Report in Format: HTML
Building: RetailStripmall
Environment: RUNPERIOD 1 ** Great Falls Intl Arpt MT USA TMY3 WMO#=727750
Simulation Timestamp: 2020-06-03 19:21:42
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2020-06-03 19:21:42
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 2064.38 | 987.59 | 987.59 |
Net Site Energy | 2064.38 | 987.59 | 987.59 |
Total Source Energy | 5144.93 | 2461.31 | 2461.31 |
Net Source Energy | 5144.93 | 2461.31 | 2461.31 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 2090.32 |
Net Conditioned Building Area | 2090.32 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 668.73 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 84.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 704.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 110.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 128.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 301.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 66.02 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1395.65 | 668.73 | 0.00 | 0.00 | 0.00 | 87.30 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 668.73 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 84.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 704.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 110.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 128.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 301.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 66.02 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 389.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 216.32 | 319.92 | 0.00 | 0.00 | 0.00 | 0.04 |
Other | 61.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 667.67 | 319.92 | 0.00 | 0.00 | 0.00 | 0.04 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 389.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 216.32 | 319.92 | 0.00 | 0.00 | 0.00 | 0.04 |
Other | 61.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 667.67 | 319.92 | 0.00 | 0.00 | 0.00 | 0.04 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1395.649 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1395.649 | 100.00 |
Total On-Site and Utility Electric Sources | 1395.649 | 100.00 |
Total Electricity End Uses | 1395.649 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 87.30 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 87.30 | 100.00 |
Total Water End Uses | 87.30 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 3.00 |
Time Setpoint Not Met During Occupied Cooling | 0.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 2233.00 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Meter |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2009
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Meter |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTRIPMALL
| Meter |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 6B
| Meter |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MT_GREATFALLS
| Meter |ZoneCoolingSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ZoneHeatingSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ZoneElectricSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |SpaceGainsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |PeakSpaceGainsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |SpaceGainComponentsAtCoolingPeakMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ComfortReportSimple55Monthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |OccupantComfortDataSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |DXReportMonthly
| PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL |WindowReportMonthly
| LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR |WindowEnergyReportMonthly
| LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR |WindowZoneSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |WindowEnergyZoneSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| GAS TANK1 | GAS TANK2 | GAS TANK3 | GAS TANK4 | GAS TANK5 | GAS TANK6 | GAS TANK7 |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC_1:1_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_2:2_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_3:3_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_4:4_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_5:5_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_6:6_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_7:7_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_8:8_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_9:9_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_10:10_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL |FanReportMonthly
| PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN |ZoneTemperatureOscillationReportMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |MechanicalVentilationLoadsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2020-06-03 19:21:42
GeneralValue | |
Program Version and Build | EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:21 |
RunPeriod | RUNPERIOD 1 |
Weather File | Great Falls Intl Arpt MT USA TMY3 WMO#=727750 |
Latitude [deg] | 47.47 |
Longitude [deg] | -111.4 |
Elevation [m] | 1117.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Above Ground Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Window Opening Area [m2] | 124.29 | 0.00 | 0.00 | 124.29 | 0.00 |
Gross Window-Wall Ratio [%] | 10.50 | 0.00 | 0.00 | 26.24 | 0.00 |
Above Ground Window-Wall Ratio [%] | 10.50 | 0.00 | 0.00 | 26.24 | 0.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Above Ground Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Window Opening Area [m2] | 124.29 | 0.00 | 0.00 | 124.29 | 0.00 |
Gross Window-Wall Ratio [%] | 10.50 | 0.00 | 0.00 | 26.24 | 0.00 |
Above Ground Window-Wall Ratio [%] | 10.50 | 0.00 | 0.00 | 26.24 | 0.00 |
Total | |
Gross Roof Area [m2] | 2090.32 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
LGSTORE1 | 348.39 | Yes | Yes | 1805.20 | 1.00 | 276.30 | 0.00 | 20.75 | 20.75 | 24.9638 | 11.61 | 4.3000 |
SMSTORE1 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.37 | 10.37 | 27.8378 | 11.61 | 4.3000 |
SMSTORE2 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.35 | 10.35 | 25.6850 | 11.61 | 4.3000 |
SMSTORE3 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.35 | 10.35 | 25.6850 | 11.61 | 4.3000 |
SMSTORE4 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.35 | 10.35 | 25.6850 | 11.61 | 4.3000 |
LGSTORE2 | 348.39 | Yes | Yes | 1805.20 | 1.00 | 157.89 | 0.00 | 20.70 | 20.70 | 18.3225 | 11.61 | 4.3000 |
SMSTORE5 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.35 | 10.35 | 18.3225 | 11.61 | 4.3000 |
SMSTORE6 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.35 | 10.35 | 18.3225 | 11.61 | 4.3000 |
SMSTORE7 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.35 | 10.35 | 18.3225 | 11.61 | 4.3000 |
SMSTORE8 | 174.19 | Yes | Yes | 902.60 | 1.00 | 197.36 | 0.00 | 10.35 | 10.35 | 18.3225 | 11.61 | 4.3000 |
Total | 2090.32 | 10831.20 | 1184.15 | 0.00 | 124.29 | 124.29 | 22.0629 | 11.61 | 4.3000 | |||
Conditioned Total | 2090.32 | 10831.20 | 1184.15 | 0.00 | 124.29 | 124.29 | 22.0629 | 11.61 | 4.3000 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:21:42
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 17-JUL-15:00 | 08-JAN-17:00 | - | - | - | 06-JAN-13:09 |
Heating | 0.00 | 385434.51 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 60739.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 43812.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 8089.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 17525.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 5445.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 135613.27 | 385434.51 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 385434.51 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 60739.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 43812.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 8089.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 17525.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 5445.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:21:42
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 724.91 | 0.00 | 0.00 | 0.00 |
Cooling | 268.05 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 2230.12 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 350.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 407.66 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 954.94 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 209.09 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 4420.02 | 724.91 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 346.79 | 0.00 | 0.00 | 0.00 |
Cooling | 128.23 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1066.88 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 167.52 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 195.02 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 456.84 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 100.03 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2114.52 | 346.79 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 346.79 | 0.00 | 0.00 | 0.00 |
Cooling | 128.23 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1066.88 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 167.52 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 195.02 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 456.84 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 100.03 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2114.52 | 346.79 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:21:42
AirTerminal:SingleDuct:UncontrolledDesign Size Maximum Air Flow Rate [m3/s] | |
LGSTORE1 DIRECT AIR | 2.47 |
SMSTORE1 DIRECT AIR | 1.35 |
SMSTORE2 DIRECT AIR | 1.35 |
SMSTORE3 DIRECT AIR | 1.35 |
SMSTORE4 DIRECT AIR | 1.34 |
LGSTORE2 DIRECT AIR | 2.38 |
SMSTORE5 DIRECT AIR | 1.31 |
SMSTORE6 DIRECT AIR | 1.30 |
SMSTORE7 DIRECT AIR | 1.31 |
SMSTORE8 DIRECT AIR | 1.45 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC_1:1 | 2.47 | 2.47 | 2.47 | 2.47 | 2.47 | 2.47 | 1.00 | 1.00 | 2.47 |
PSZ-AC_2:2 | 1.35 | 1.35 | 1.35 | 1.35 | 1.35 | 1.35 | 1.00 | 1.00 | 1.35 |
PSZ-AC_3:3 | 1.35 | 1.35 | 1.35 | 1.35 | 1.35 | 1.35 | 1.00 | 1.00 | 1.35 |
PSZ-AC_4:4 | 1.35 | 1.35 | 1.35 | 1.35 | 1.35 | 1.35 | 1.00 | 1.00 | 1.35 |
PSZ-AC_5:5 | 1.34 | 1.34 | 1.34 | 1.34 | 1.34 | 1.34 | 1.00 | 1.00 | 1.34 |
PSZ-AC_6:6 | 2.38 | 2.38 | 2.38 | 2.38 | 2.38 | 2.38 | 1.00 | 1.00 | 2.38 |
PSZ-AC_7:7 | 1.31 | 1.31 | 1.31 | 1.31 | 1.31 | 1.31 | 1.00 | 1.00 | 1.31 |
PSZ-AC_8:8 | 1.30 | 1.30 | 1.30 | 1.30 | 1.30 | 1.30 | 1.00 | 1.00 | 1.30 |
PSZ-AC_9:9 | 1.31 | 1.31 | 1.31 | 1.31 | 1.31 | 1.31 | 1.00 | 1.00 | 1.31 |
PSZ-AC_10:10 | 1.45 | 1.45 | 1.45 | 1.45 | 1.45 | 1.45 | 1.00 | 1.00 | 1.45 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC_1:1_OA_CONTROLLER | 2.47 | 0.411453 |
PSZ-AC_2:2_OA_CONTROLLER | 1.35 | 0.205727 |
PSZ-AC_3:3_OA_CONTROLLER | 1.35 | 0.205727 |
PSZ-AC_4:4_OA_CONTROLLER | 1.35 | 0.205727 |
PSZ-AC_5:5_OA_CONTROLLER | 1.34 | 0.205727 |
PSZ-AC_6:6_OA_CONTROLLER | 2.38 | 0.411453 |
PSZ-AC_7:7_OA_CONTROLLER | 1.31 | 0.205727 |
PSZ-AC_8:8_OA_CONTROLLER | 1.30 | 0.205727 |
PSZ-AC_9:9_OA_CONTROLLER | 1.31 | 0.205727 |
PSZ-AC_10:10_OA_CONTROLLER | 1.45 | 0.205727 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC_1:1_UNITARY_PACKAGE_DX | 2.47 | 2.47 | 2.47 | 2.47 | 40831.86 | 70533.79 | 40.00 | 1.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_DX | 1.35 | 1.35 | 1.35 | 1.35 | 22370.89 | 37629.29 | 40.00 | 1.00 |
PSZ-AC_3:3_UNITARY_PACKAGE_DX | 1.35 | 1.35 | 1.35 | 1.35 | 22355.27 | 37610.41 | 40.00 | 1.00 |
PSZ-AC_4:4_UNITARY_PACKAGE_DX | 1.35 | 1.35 | 1.35 | 1.35 | 22416.84 | 37684.79 | 40.00 | 1.00 |
PSZ-AC_5:5_UNITARY_PACKAGE_DX | 1.34 | 1.34 | 1.34 | 1.34 | 22255.74 | 37490.15 | 40.00 | 1.00 |
PSZ-AC_6:6_UNITARY_PACKAGE_DX | 2.38 | 2.38 | 2.38 | 2.38 | 39404.20 | 68808.71 | 40.00 | 1.00 |
PSZ-AC_7:7_UNITARY_PACKAGE_DX | 1.31 | 1.31 | 1.31 | 1.31 | 21611.22 | 36711.46 | 40.00 | 1.00 |
PSZ-AC_8:8_UNITARY_PACKAGE_DX | 1.30 | 1.30 | 1.30 | 1.30 | 21590.18 | 36686.04 | 40.00 | 1.00 |
PSZ-AC_9:9_UNITARY_PACKAGE_DX | 1.31 | 1.31 | 1.31 | 1.31 | 21764.17 | 36896.23 | 40.00 | 1.00 |
PSZ-AC_10:10_UNITARY_PACKAGE_DX | 1.45 | 1.45 | 1.45 | 1.45 | 24027.89 | 39631.34 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | Speed 2 Design Size Rated Total Cooling Capacity [W] | Speed 2 User-Specified Rated Total Cooling Capacity [W] | Speed 1 Design Size Rated Total Cooling Capacity [W] | Speed 1 User-Specified Rated Total Cooling Capacity [W] | Speed 2 Design Size Rated Sensible Heat Ratio | Speed 2 User-Specified Rated Sensible Heat Ratio | Speed 1 Design Size Rated Sensible Heat Ratio | Speed 1 User-Specified Rated Sensible Heat Ratio | |
PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | 2.47 | 1.23 | 2.47 | 40831.82 | 40831.86 | 20415.93 | 40831.86 | 0.798655 | 0.798660 | 0.798660 | 0.798660 |
PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | 1.35 | 0.675715 | 1.35 | 22370.97 | 22370.89 | 11185.44 | 22370.89 | 0.798655 | 0.798660 | 0.798660 | 0.798660 |
PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | 1.35 | 0.675240 | 1.35 | 22355.24 | 22355.27 | 11177.64 | 22355.27 | 0.798655 | 0.798660 | 0.798660 | 0.798660 |
PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | 1.35 | 0.677100 | 1.35 | 22416.82 | 22416.84 | 11208.42 | 22416.84 | 0.798655 | 0.798660 | 0.798660 | 0.798660 |
PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | 1.34 | 0.672235 | 1.34 | 22255.75 | 22255.74 | 11127.87 | 22255.74 | 0.798655 | 0.798660 | 0.798660 | 0.798660 |
PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | 2.38 | 1.19 | 2.38 | 39404.24 | 39404.20 | 19702.10 | 39404.20 | 0.798655 | 0.798660 | 0.798660 | 0.798660 |
PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | 1.31 | 0.652765 | 1.31 | 21611.16 | 21611.22 | 10805.61 | 21611.22 | 0.798654 | 0.798660 | 0.798660 | 0.798660 |
PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | 1.30 | 0.652130 | 1.30 | 21590.13 | 21590.18 | 10795.09 | 21590.18 | 0.798654 | 0.798660 | 0.798660 | 0.798660 |
PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | 1.31 | 0.657385 | 1.31 | 21764.11 | 21764.17 | 10882.08 | 21764.17 | 0.798654 | 0.798660 | 0.798660 | 0.798660 |
PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | 1.45 | 0.725760 | 1.45 | 24027.81 | 24027.89 | 12013.94 | 24027.89 | 0.798654 | 0.798660 | 0.798660 | 0.798660 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | 2.47 | 2699.77 |
PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | 1.35 | 1540.77 |
PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | 1.35 | 1539.70 |
PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | 1.35 | 1543.94 |
PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | 1.34 | 1532.84 |
PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | 2.38 | 2605.37 |
PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | 1.31 | 1488.45 |
PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | 1.30 | 1487.00 |
PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | 1.31 | 1498.99 |
PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | 1.45 | 1588.70 |
Design Size Nominal Capacity [W] | |
PSZ-AC_1:1_UNITARY_PACKAGE_HEATCOIL | 70533.79 |
PSZ-AC_2:2_UNITARY_PACKAGE_HEATCOIL | 37629.29 |
PSZ-AC_3:3_UNITARY_PACKAGE_HEATCOIL | 37610.41 |
PSZ-AC_4:4_UNITARY_PACKAGE_HEATCOIL | 37684.79 |
PSZ-AC_5:5_UNITARY_PACKAGE_HEATCOIL | 37490.15 |
PSZ-AC_6:6_UNITARY_PACKAGE_HEATCOIL | 68808.71 |
PSZ-AC_7:7_UNITARY_PACKAGE_HEATCOIL | 36711.46 |
PSZ-AC_8:8_UNITARY_PACKAGE_HEATCOIL | 36686.04 |
PSZ-AC_9:9_UNITARY_PACKAGE_HEATCOIL | 36896.23 |
PSZ-AC_10:10_UNITARY_PACKAGE_HEATCOIL | 39631.34 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:21:42
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
LGSTORE1_WALL_3 | LGSTORE1_WALL_3_DOOR_1 | LGSTORE1_WALL_3_DOOR_2 | |
LGSTORE1_WALL_1 | LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | |
SMSTORE1_WALL_1 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | |
SMSTORE1_WALL_3 | SMSTORE1_WALL_3_DOOR | |
SMSTORE2_WALL_1 | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | |
SMSTORE2_WALL_3 | SMSTORE2_WALL_3_DOOR | |
SMSTORE3_WALL_1 | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | |
SMSTORE3_WALL_3 | SMSTORE3_WALL_3_DOOR | |
SMSTORE4_WALL_1 | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | |
SMSTORE4_WALL_3 | SMSTORE4_WALL_3_DOOR | |
LGSTORE2_WALL_3 | LGSTORE2_WALL_3_DOOR_1 | LGSTORE2_WALL_3_DOOR_2 | |
LGSTORE2_WALL_1 | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | |
SMSTORE5_WALL_1 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | |
SMSTORE5_WALL_3 | SMSTORE5_WALL_3_DOOR | |
SMSTORE6_WALL_1 | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | |
SMSTORE6_WALL_3 | SMSTORE6_WALL_3_DOOR | |
SMSTORE7_WALL_1 | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | |
SMSTORE7_WALL_3 | SMSTORE7_WALL_3_DOOR | |
SMSTORE8_WALL_1 | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR | |
SMSTORE8_WALL_3 | SMSTORE8_WALL_3_DOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2020-06-03 19:21:42
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2020-06-03 19:21:42
VersionVersion ID | |
1 | 9.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 8.60 | 2.80 | -4.10 | -8.80 | -2.20 | 0.30 | 6.70 | 10.10 | 16.50 | 20.60 | 19.20 | 14.70 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Great Falls Intl Arpt MT USA TMY3 WMO#=727750 | 47.47 | -111.38 | -7.00 | 1117.00 | 88606 | 1.0531 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 7.03 | 29.40 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RetailStripmall | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 10 | 118 | 48 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | LGSTORE1 | 0.0 | 0.00 | 0.00 | 0.00 | 7.62 | 11.43 | 2.59 | 1 | 1 | 1 | 0.00 | 15.24 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 1805.20 | TARP | TARP | 348.39 | 276.30 | 247.76 | 20.75 | 6 | 8 | 0 | Yes |
2 | SMSTORE1 | 0.0 | 0.00 | 0.00 | 0.00 | 19.05 | 11.43 | 2.59 | 1 | 1 | 1 | 15.24 | 22.86 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.67 | 10.37 | 6 | 4 | 0 | Yes |
3 | SMSTORE2 | 0.0 | 0.00 | 0.00 | 0.00 | 26.67 | 11.43 | 2.59 | 1 | 1 | 1 | 22.86 | 30.48 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.35 | 6 | 4 | 0 | Yes |
4 | SMSTORE3 | 0.0 | 0.00 | 0.00 | 0.00 | 34.29 | 11.43 | 2.59 | 1 | 1 | 1 | 30.48 | 38.10 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.35 | 6 | 4 | 0 | Yes |
5 | SMSTORE4 | 0.0 | 0.00 | 0.00 | 0.00 | 41.91 | 11.43 | 2.59 | 1 | 1 | 1 | 38.10 | 45.72 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.35 | 6 | 4 | 0 | Yes |
6 | LGSTORE2 | 0.0 | 0.00 | 0.00 | 0.00 | 53.34 | 11.43 | 2.59 | 1 | 1 | 1 | 45.72 | 60.96 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 1805.20 | TARP | TARP | 348.39 | 157.89 | 129.43 | 20.70 | 6 | 8 | 0 | Yes |
7 | SMSTORE5 | 0.0 | 0.00 | 0.00 | 0.00 | 64.77 | 11.43 | 2.59 | 1 | 1 | 1 | 60.96 | 68.58 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.35 | 6 | 4 | 0 | Yes |
8 | SMSTORE6 | 0.0 | 0.00 | 0.00 | 0.00 | 72.39 | 11.43 | 2.59 | 1 | 1 | 1 | 68.58 | 76.20 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.35 | 6 | 4 | 0 | Yes |
9 | SMSTORE7 | 0.0 | 0.00 | 0.00 | 0.00 | 80.01 | 11.43 | 2.59 | 1 | 1 | 1 | 76.20 | 83.82 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.35 | 6 | 4 | 0 | Yes |
10 | SMSTORE8 | 0.0 | 0.00 | 0.00 | 0.00 | 87.63 | 11.43 | 2.59 | 1 | 1 | 1 | 83.82 | 91.44 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 197.36 | 183.13 | 10.35 | 6 | 4 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | LGSTORE1 | 348.39 | 30.0 | 11.614 | 8.610E-002 | 24.964 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 29.264 | No |
2 | SMSTORE1 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 27.838 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 32.138 | No |
3 | SMSTORE2 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 25.685 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 29.985 | No |
4 | SMSTORE3 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 25.685 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 29.985 | No |
5 | SMSTORE4 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 25.685 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 29.985 | No |
6 | LGSTORE2 | 348.39 | 30.0 | 11.614 | 8.610E-002 | 18.322 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 22.622 | No |
7 | SMSTORE5 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 18.322 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 22.622 | No |
8 | SMSTORE6 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 18.322 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 22.622 | No |
9 | SMSTORE7 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 18.322 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 22.622 | No |
10 | SMSTORE8 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 18.322 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 22.622 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | |
1 | LGSTORE1 | TYPE1_OCC_SCH | LGSTORE1 | 348.39 | 30.0 | 30.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 30 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
2 | SMSTORE1 | TYPE1_OCC_SCH | SMSTORE1 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
3 | SMSTORE2 | TYPE2_OCC_SCH | SMSTORE2 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
4 | SMSTORE3 | TYPE2_OCC_SCH | SMSTORE3 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
5 | SMSTORE4 | TYPE2_OCC_SCH | SMSTORE4 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
6 | LGSTORE2 | TYPE3_OCC_SCH | LGSTORE2 | 348.39 | 30.0 | 30.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 30 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
7 | SMSTORE5 | TYPE3_OCC_SCH | SMSTORE5 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
8 | SMSTORE6 | TYPE3_OCC_SCH | SMSTORE6 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
9 | SMSTORE7 | TYPE3_OCC_SCH | SMSTORE7 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
10 | SMSTORE8 | TYPE3_OCC_SCH | SMSTORE8 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | LGSTORE1_LIGHTS | TYPE1_LIGHT_SCH | LGSTORE1 | 348.39 | 30.0 | 6383.296 | 18.322 | 212.804 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 6383.296 |
2 | LGSTORE1_LIGHTS_ALLOWANCE | TYPE1_LIGHT_SCH | LGSTORE1 | 348.39 | 30.0 | 2313.751 | 6.641 | 77.135 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2313.751 |
3 | SMSTORE1_LIGHTS | TYPE1_LIGHT_SCH | SMSTORE1 | 174.19 | 15.0 | 3191.648 | 18.322 | 212.805 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3191.648 |
4 | SMSTORE1_LIGHTS_ALLOWANCE | TYPE1_LIGHT_SCH | SMSTORE1 | 174.19 | 15.0 | 1657.501 | 9.515 | 110.515 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1657.501 |
5 | SMSTORE2_LIGHTS | TYPE2_LIGHT_SCH | SMSTORE2 | 174.19 | 15.0 | 3191.648 | 18.322 | 212.805 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3191.648 |
6 | SMSTORE2_LIGHTS_ALLOWANCE | TYPE2_LIGHT_SCH | SMSTORE2 | 174.19 | 15.0 | 1282.501 | 7.363 | 85.511 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1282.501 |
7 | SMSTORE3_LIGHTS | TYPE2_LIGHT_SCH | SMSTORE3 | 174.19 | 15.0 | 3191.648 | 18.322 | 212.805 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3191.648 |
8 | SMSTORE3_LIGHTS_ALLOWANCE | TYPE2_LIGHT_SCH | SMSTORE3 | 174.19 | 15.0 | 1282.501 | 7.363 | 85.511 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1282.501 |
9 | SMSTORE4_LIGHTS | TYPE2_LIGHT_SCH | SMSTORE4 | 174.19 | 15.0 | 3191.648 | 18.322 | 212.805 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3191.648 |
10 | SMSTORE4_LIGHTS_ALLOWANCE | TYPE2_LIGHT_SCH | SMSTORE4 | 174.19 | 15.0 | 1282.501 | 7.363 | 85.511 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1282.501 |
11 | LGSTORE2_LIGHTS | TYPE3_LIGHT_SCH | LGSTORE2 | 348.39 | 30.0 | 6383.296 | 18.322 | 212.804 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 6383.296 |
12 | LGSTORE2_LIGHTS_ALLOWANCE | TYPE3_LIGHT_SCH | LGSTORE2 | 348.39 | 30.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
13 | SMSTORE5_LIGHTS | TYPE3_LIGHT_SCH | SMSTORE5 | 174.19 | 15.0 | 3191.648 | 18.322 | 212.805 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3191.648 |
14 | SMSTORE5_LIGHTS_ALLOWANCE | TYPE3_LIGHT_SCH | SMSTORE5 | 174.19 | 15.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
15 | SMSTORE6_LIGHTS | TYPE3_LIGHT_SCH | SMSTORE6 | 174.19 | 15.0 | 3191.648 | 18.322 | 212.805 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3191.648 |
16 | SMSTORE6_LIGHTS_ALLOWANCE | TYPE3_LIGHT_SCH | SMSTORE6 | 174.19 | 15.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
17 | SMSTORE7_LIGHTS | TYPE3_LIGHT_SCH | SMSTORE7 | 174.19 | 15.0 | 3191.648 | 18.322 | 212.805 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3191.648 |
18 | SMSTORE7_LIGHTS_ALLOWANCE | TYPE3_LIGHT_SCH | SMSTORE7 | 174.19 | 15.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
19 | SMSTORE8_LIGHTS | TYPE3_LIGHT_SCH | SMSTORE8 | 174.19 | 15.0 | 3191.648 | 18.322 | 212.805 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3191.648 |
20 | SMSTORE8_LIGHTS_ALLOWANCE | TYPE3_LIGHT_SCH | SMSTORE8 | 174.19 | 15.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | LGSTORE1_MISCPLUG_EQUIP | TYPE1_EQUIP_SCH | LGSTORE1 | 348.39 | 30.0 | 1498.062 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1498.062 |
2 | SMSTORE1_MISCPLUG_EQUIP | TYPE1_EQUIP_SCH | SMSTORE1 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
3 | SMSTORE2_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE2 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
4 | SMSTORE3_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE3 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
5 | SMSTORE4_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE4 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
6 | LGSTORE2_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | LGSTORE2 | 348.39 | 30.0 | 1498.062 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1498.062 |
7 | SMSTORE5_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE5 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
8 | SMSTORE6_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE6 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
9 | SMSTORE7_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE7 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
10 | SMSTORE8_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE8 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.975 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.2832 | 0.900 | 0.900 | 0.770 | 0.700 | Rough |
5 | NONRES_EXT_WALL | 20 | 4 | 7 | 0.167 | 0.3843 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
6 | LGSTORE1_FLOOR_FFACTOR | 30 | 2 | 7 | 0.167 | 0.1464 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
7 | SMSTORE1_FLOOR_FFACTOR | 31 | 2 | 7 | 0.167 | 0.8283E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
8 | SMSTORE2_FLOOR_FFACTOR | 32 | 2 | 7 | 0.167 | 0.8283E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | SMSTORE3_FLOOR_FFACTOR | 33 | 2 | 7 | 0.167 | 0.8283E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
10 | SMSTORE4_FLOOR_FFACTOR | 34 | 2 | 7 | 0.167 | 0.8283E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
11 | LGSTORE2_FLOOR_FFACTOR | 35 | 2 | 7 | 0.167 | 0.8283E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | SMSTORE5_FLOOR_FFACTOR | 36 | 2 | 7 | 0.167 | 0.8283E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | SMSTORE6_FLOOR_FFACTOR | 37 | 2 | 7 | 0.167 | 0.8283E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | SMSTORE7_FLOOR_FFACTOR | 38 | 2 | 7 | 0.167 | 0.8283E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | SMSTORE8_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.2111 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2516 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
6 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 3.472 |
7 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
8 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
9 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
10 | NONRES_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.368 |
11 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
12 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 6.756 |
13 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
14 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.00 |
15 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
16 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.00 |
17 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
18 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.00 |
19 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
20 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.00 |
21 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
22 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.00 |
23 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
24 | ~FC_Insulation_7 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.00 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_8 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.00 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_9 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.00 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
30 | ~FC_Insulation_10 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.659 |
31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.9747885 | 3.9747885 | 3.9747885 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
14 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
15 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
16 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
17 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
18 | 3 | -0.61927053E-06 | 0.12767249E-08 | -0.37968499E-05 | 0.16832131E-17 |
19 | 2 | 0.77611055 | 0.17315568E-02 | 1.0534842 | -0.72792597E-06 |
20 | 1 | -21.915918 | 0.11588205 | -6.3286394 | 0.20197014 |
21 | 0 | 21.365777 | 0.10835518 | 5.5011278 | |
22 | 7 | -0.35963630E-12 | 0.61482467E-15 | -0.13288964E-12 | 0.15093609E-15 |
23 | 6 | 0.33258387E-07 | 0.11249777E-09 | 0.75805110E-08 | -0.16019892E-12 |
24 | 5 | -0.21313350E-03 | 0.93714421E-06 | -0.10927814E-03 | 0.74776115E-08 |
25 | 4 | 0.31870195 | 0.44521373E-03 | 0.10925225 | -0.37358013E-04 |
26 | 3 | -7.7913368 | 0.13499397E-01 | -2.4947666 | 0.31584435E-01 |
27 | 2 | 42.601618 | 0.47079245E-01 | 15.902165 | -0.35261900 |
28 | 1 | -81.870774 | 0.20888078E-01 | -29.712230 | 1.1068570 |
29 | 0 | 46.824331 | 0.41326549E-03 | 16.278015 | |
30 | 7 | -0.28997596E-08 | -0.17578320E-14 | 0.22751757E-14 | -0.53829073E-16 |
31 | 6 | 0.41991781E-05 | 0.27986603E-08 | 0.31940183E-02 | -0.26794102E-04 |
32 | 5 | -0.29588474E-03 | 0.16552611E-05 | -0.22396035 | 0.19582313E-02 |
33 | 4 | 0.67666006E-02 | 0.75295852E-04 | 4.8334724 | -0.45302727E-01 |
34 | 3 | -0.59297736E-01 | 0.59838054E-03 | -38.043598 | 0.39889893 |
35 | 2 | 0.21038411 | 0.99492606E-03 | 116.52712 | -1.4185167 |
36 | 1 | -0.30354941 | 0.30287292E-03 | -143.93272 | 2.0494576 |
37 | 0 | 0.14796861 | 0.73483799E-05 | 60.838472 | |
38 | 7 | -0.51571905E-08 | -0.97500959E-14 | 0.15789915E-14 | -0.32998988E-16 |
39 | 6 | 0.26247599E-05 | 0.15902949E-08 | 0.31989528E-02 | -0.26835497E-04 |
40 | 5 | -0.17282397E-03 | 0.93714128E-06 | -0.22424071 | 0.19607060E-02 |
41 | 4 | 0.38696203E-02 | 0.42548205E-04 | 4.8381400 | -0.45347597E-01 |
42 | 3 | -0.33643188E-01 | 0.33758390E-03 | -38.069955 | 0.39919029 |
43 | 2 | 0.11898200 | 0.56044665E-03 | 116.57840 | -1.4192028 |
44 | 1 | -0.17142224 | 0.17027190E-03 | -143.96290 | 2.0499538 |
45 | 0 | 0.83499932E-01 | 0.41268798E-05 | 60.838472 | |
46 | 7 | -0.51571905E-08 | -0.97500958E-14 | 0.15789913E-14 | -0.32998984E-16 |
47 | 6 | 0.26247599E-05 | 0.15902949E-08 | 0.31989528E-02 | -0.26835497E-04 |
48 | 5 | -0.17282397E-03 | 0.93714128E-06 | -0.22424071 | 0.19607060E-02 |
49 | 4 | 0.38696203E-02 | 0.42548205E-04 | 4.8381400 | -0.45347597E-01 |
50 | 3 | -0.33643188E-01 | 0.33758390E-03 | -38.069955 | 0.39919029 |
51 | 2 | 0.11898200 | 0.56044665E-03 | 116.57840 | -1.4192028 |
52 | 1 | -0.17142224 | 0.17027190E-03 | -143.96290 | 2.0499538 |
53 | 0 | 0.83499932E-01 | 0.41268798E-05 | 60.838472 | |
54 | 7 | -0.51571905E-08 | -0.97500959E-14 | 0.15789911E-14 | -0.32998980E-16 |
55 | 6 | 0.26247599E-05 | 0.15902949E-08 | 0.31989528E-02 | -0.26835497E-04 |
56 | 5 | -0.17282397E-03 | 0.93714128E-06 | -0.22424071 | 0.19607060E-02 |
57 | 4 | 0.38696203E-02 | 0.42548205E-04 | 4.8381400 | -0.45347597E-01 |
58 | 3 | -0.33643188E-01 | 0.33758390E-03 | -38.069955 | 0.39919029 |
59 | 2 | 0.11898200 | 0.56044665E-03 | 116.57840 | -1.4192028 |
60 | 1 | -0.17142224 | 0.17027190E-03 | -143.96290 | 2.0499538 |
61 | 0 | 0.83499932E-01 | 0.41268798E-05 | 60.838472 | |
62 | 7 | -0.51571905E-08 | -0.97500959E-14 | 0.15789915E-14 | -0.32998988E-16 |
63 | 6 | 0.26247599E-05 | 0.15902949E-08 | 0.31989528E-02 | -0.26835497E-04 |
64 | 5 | -0.17282397E-03 | 0.93714128E-06 | -0.22424071 | 0.19607060E-02 |
65 | 4 | 0.38696203E-02 | 0.42548205E-04 | 4.8381400 | -0.45347597E-01 |
66 | 3 | -0.33643188E-01 | 0.33758390E-03 | -38.069955 | 0.39919029 |
67 | 2 | 0.11898200 | 0.56044665E-03 | 116.57840 | -1.4192028 |
68 | 1 | -0.17142224 | 0.17027190E-03 | -143.96290 | 2.0499538 |
69 | 0 | 0.83499932E-01 | 0.41268798E-05 | 60.838472 | |
70 | 7 | -0.51571905E-08 | -0.97500958E-14 | 0.15789913E-14 | -0.32998984E-16 |
71 | 6 | 0.26247599E-05 | 0.15902949E-08 | 0.31989528E-02 | -0.26835497E-04 |
72 | 5 | -0.17282397E-03 | 0.93714128E-06 | -0.22424071 | 0.19607060E-02 |
73 | 4 | 0.38696203E-02 | 0.42548205E-04 | 4.8381400 | -0.45347597E-01 |
74 | 3 | -0.33643188E-01 | 0.33758390E-03 | -38.069955 | 0.39919029 |
75 | 2 | 0.11898200 | 0.56044665E-03 | 116.57840 | -1.4192028 |
76 | 1 | -0.17142224 | 0.17027190E-03 | -143.96290 | 2.0499538 |
77 | 0 | 0.83499932E-01 | 0.41268798E-05 | 60.838472 | |
78 | 7 | -0.51571905E-08 | -0.97500957E-14 | 0.15789917E-14 | -0.32998991E-16 |
79 | 6 | 0.26247599E-05 | 0.15902949E-08 | 0.31989528E-02 | -0.26835497E-04 |
80 | 5 | -0.17282397E-03 | 0.93714128E-06 | -0.22424071 | 0.19607060E-02 |
81 | 4 | 0.38696203E-02 | 0.42548205E-04 | 4.8381400 | -0.45347597E-01 |
82 | 3 | -0.33643188E-01 | 0.33758390E-03 | -38.069955 | 0.39919029 |
83 | 2 | 0.11898200 | 0.56044665E-03 | 116.57840 | -1.4192028 |
84 | 1 | -0.17142224 | 0.17027190E-03 | -143.96290 | 2.0499538 |
85 | 0 | 0.83499932E-01 | 0.41268798E-05 | 60.838472 | |
86 | 7 | -0.51571905E-08 | -0.97500959E-14 | 0.15789915E-14 | -0.32998988E-16 |
87 | 6 | 0.26247599E-05 | 0.15902949E-08 | 0.31989528E-02 | -0.26835497E-04 |
88 | 5 | -0.17282397E-03 | 0.93714128E-06 | -0.22424071 | 0.19607060E-02 |
89 | 4 | 0.38696203E-02 | 0.42548205E-04 | 4.8381400 | -0.45347597E-01 |
90 | 3 | -0.33643188E-01 | 0.33758390E-03 | -38.069955 | 0.39919029 |
91 | 2 | 0.11898200 | 0.56044665E-03 | 116.57840 | -1.4192028 |
92 | 1 | -0.17142224 | 0.17027190E-03 | -143.96290 | 2.0499538 |
93 | 0 | 0.83499932E-01 | 0.41268798E-05 | 60.838472 | |
94 | 7 | -0.51571905E-08 | -0.97500958E-14 | 0.15789913E-14 | -0.32998984E-16 |
95 | 6 | 0.26247599E-05 | 0.15902949E-08 | 0.31989528E-02 | -0.26835497E-04 |
96 | 5 | -0.17282397E-03 | 0.93714128E-06 | -0.22424071 | 0.19607060E-02 |
97 | 4 | 0.38696203E-02 | 0.42548205E-04 | 4.8381400 | -0.45347597E-01 |
98 | 3 | -0.33643188E-01 | 0.33758390E-03 | -38.069955 | 0.39919029 |
99 | 2 | 0.11898200 | 0.56044665E-03 | 116.57840 | -1.4192028 |
100 | 1 | -0.17142224 | 0.17027190E-03 | -143.96290 | 2.0499538 |
101 | 0 | 0.83499932E-01 | 0.41268798E-05 | 60.838472 | |
102 | 7 | -0.19967951E-08 | -0.58252365E-15 | 0.72897552E-14 | -0.10630581E-15 |
103 | 6 | 0.59274927E-05 | 0.40433693E-08 | 0.31889525E-02 | -0.26751606E-04 |
104 | 5 | -0.42514865E-03 | 0.23948505E-05 | -0.22367243 | 0.19556901E-02 |
105 | 4 | 0.97725356E-02 | 0.10900143E-03 | 4.8286774 | -0.45256634E-01 |
106 | 3 | -0.85796444E-01 | 0.86675557E-03 | -38.016512 | 0.39859954 |
107 | 2 | 0.30461848 | 0.14417950E-02 | 116.47440 | -1.4178116 |
108 | 1 | -0.43965446 | 0.43929230E-03 | -143.90169 | 2.0489476 |
109 | 0 | 0.21434897 | 0.10616597E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.47_SHGC_0.4 | 29 | 1 | VerySmooth | 2.672 | 0.394 | 0.315 | 0.401 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 2.40629E-002 | 0.31435 | 0.46917 | 0.46917 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11822 | 1.00000 | No |
Calculation Method | Value {days} | Allowable Number Figures in Shadow Overlap {} | Polygon Clipping Algorithm | Sky Diffuse Modeling Algorithm | External Shading Calculation Method | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | AverageOverDaysInFrequency | 30 | 15000 | SutherlandHodgman | SimpleSkyDiffuseModeling | InternalCalculation | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | GAS TANK1 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
2 | WaterHeater:Mixed | GAS TANK2 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
3 | WaterHeater:Mixed | GAS TANK3 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
4 | WaterHeater:Mixed | GAS TANK4 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
5 | WaterHeater:Mixed | GAS TANK5 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
6 | WaterHeater:Mixed | GAS TANK6 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
7 | WaterHeater:Mixed | GAS TANK7 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | LGSTORE1_WALL_2 | 0 | 118.41 | 56.08 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 4 | No | No |
2 | LGSTORE1_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 4 | No | No |
3 | LGSTORE1_WALL_3_DOOR_1 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 0 | No | No |
4 | LGSTORE1_WALL_3_DOOR_2 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 0 | No | No |
5 | LGSTORE1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 0 | No | No |
6 | LGSTORE1_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 4 | No | No |
7 | LGSTORE1_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 1 | No | No |
8 | LGSTORE1_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 1 | No | No |
9 | LGSTORE1_WALL_1_WINDOW_3 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 1 | No | No |
10 | LGSTORE1_WALL_1_WINDOW_4 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 1 | No | No |
11 | LGSTORE1_WALL_1_DOOR_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 1 | No | No |
12 | LGSTORE1_WALL_1_DOOR_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 1 | No | No |
13 | LGSTORE1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 0 | No | No |
14 | LGSTORE1_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 0 | No | No |
15 | LGSTORE1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 0 | No | No |
16 | SMSTORE1_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
17 | SMSTORE1_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
18 | SMSTORE1_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
19 | SMSTORE1_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
20 | SMSTORE1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
21 | SMSTORE1_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
22 | SMSTORE1_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
23 | SMSTORE1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
24 | SMSTORE1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
25 | SMSTORE1_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
26 | SMSTORE1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
27 | SMSTORE2_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
28 | SMSTORE2_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
29 | SMSTORE2_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
30 | SMSTORE2_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
31 | SMSTORE2_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
32 | SMSTORE2_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
33 | SMSTORE2_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
34 | SMSTORE2_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
35 | SMSTORE2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
36 | SMSTORE2_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
37 | SMSTORE2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
38 | SMSTORE3_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
39 | SMSTORE3_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
40 | SMSTORE3_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
41 | SMSTORE3_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
42 | SMSTORE3_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
43 | SMSTORE3_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
44 | SMSTORE3_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
45 | SMSTORE3_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
46 | SMSTORE3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
47 | SMSTORE3_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
48 | SMSTORE3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
49 | SMSTORE4_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
50 | SMSTORE4_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
51 | SMSTORE4_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
52 | SMSTORE4_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
53 | SMSTORE4_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
54 | SMSTORE4_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 3 | No | No |
55 | SMSTORE4_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
56 | SMSTORE4_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
57 | SMSTORE4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
58 | SMSTORE4_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
59 | SMSTORE4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
60 | LGSTORE2_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
61 | LGSTORE2_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 4 | No | No |
62 | LGSTORE2_WALL_3_DOOR_1 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
63 | LGSTORE2_WALL_3_DOOR_2 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
64 | LGSTORE2_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
65 | LGSTORE2_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 4 | No | No |
66 | LGSTORE2_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
67 | LGSTORE2_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
68 | LGSTORE2_WALL_1_WINDOW_3 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
69 | LGSTORE2_WALL_1_WINDOW_4 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
70 | LGSTORE2_WALL_1_DOOR_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
71 | LGSTORE2_WALL_1_DOOR_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
72 | LGSTORE2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
73 | LGSTORE2_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
74 | LGSTORE2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
75 | SMSTORE5_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
76 | SMSTORE5_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
77 | SMSTORE5_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
78 | SMSTORE5_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
79 | SMSTORE5_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
80 | SMSTORE5_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
81 | SMSTORE5_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
82 | SMSTORE5_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
83 | SMSTORE5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
84 | SMSTORE5_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
85 | SMSTORE5_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
86 | SMSTORE6_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
87 | SMSTORE6_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
88 | SMSTORE6_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
89 | SMSTORE6_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
90 | SMSTORE6_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
91 | SMSTORE6_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
92 | SMSTORE6_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
93 | SMSTORE6_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
94 | SMSTORE6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
95 | SMSTORE6_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
96 | SMSTORE6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
97 | SMSTORE7_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
98 | SMSTORE7_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
99 | SMSTORE7_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
100 | SMSTORE7_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
101 | SMSTORE7_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
102 | SMSTORE7_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 3 | No | No |
103 | SMSTORE7_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
104 | SMSTORE7_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
105 | SMSTORE7_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
106 | SMSTORE7_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
107 | SMSTORE7_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
108 | SMSTORE8_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 4 | No | No |
109 | SMSTORE8_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 1 | No | No |
110 | SMSTORE8_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 1 | No | No |
111 | SMSTORE8_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 1 | No | No |
112 | SMSTORE8_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
113 | SMSTORE8_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 3 | No | No |
114 | SMSTORE8_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
115 | SMSTORE8_WALL_4 | 0 | 118.41 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 3 | No | No |
116 | SMSTORE8_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
117 | SMSTORE8_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
118 | SMSTORE8_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | LGSTORE1_INFILTRATION | TYPE1_INFIL_SCH | LGSTORE1 | 348.39 | 30.0 | 0.286 | 8.224E-004 | 4.530E-004 | 0.571 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | LGSTORE1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | LGSTORE1 | 348.39 | 30.0 | 0.389 | 1.116E-003 | 6.149E-004 | 0.776 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | SMSTORE1_INFILTRATION | TYPE1_INFIL_SCH | SMSTORE1 | 174.19 | 15.0 | 8.210E-002 | 4.713E-004 | 3.194E-004 | 0.327 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | SMSTORE1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE1 | 174.19 | 15.0 | 0.222 | 1.276E-003 | 8.648E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
5 | SMSTORE2_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE2 | 174.19 | 15.0 | 8.210E-002 | 4.713E-004 | 3.194E-004 | 0.327 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | SMSTORE2_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE2 | 174.19 | 15.0 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
7 | SMSTORE3_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE3 | 174.19 | 15.0 | 8.210E-002 | 4.713E-004 | 3.194E-004 | 0.327 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | SMSTORE3_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE3 | 174.19 | 15.0 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | SMSTORE4_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE4 | 174.19 | 15.0 | 8.210E-002 | 4.713E-004 | 3.194E-004 | 0.327 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | SMSTORE4_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE4 | 174.19 | 15.0 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
11 | LGSTORE2_INFILTRATION | TYPE3_INFIL_SCH | LGSTORE2 | 348.39 | 30.0 | 0.164 | 4.713E-004 | 3.194E-004 | 0.327 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | LGSTORE2_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | LGSTORE2 | 348.39 | 30.0 | 0.389 | 1.116E-003 | 7.565E-004 | 0.776 | 1.000 | 0.000 | 0.000 | 0.000 |
13 | SMSTORE5_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE5 | 174.19 | 15.0 | 8.210E-002 | 4.713E-004 | 3.194E-004 | 0.327 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | SMSTORE5_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE5 | 174.19 | 15.0 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
15 | SMSTORE6_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE6 | 174.19 | 15.0 | 8.210E-002 | 4.713E-004 | 3.194E-004 | 0.327 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | SMSTORE6_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE6 | 174.19 | 15.0 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
17 | SMSTORE7_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE7 | 174.19 | 15.0 | 8.210E-002 | 4.713E-004 | 3.194E-004 | 0.327 | 0.000 | 0.000 | 0.224 | 0.000 |
18 | SMSTORE7_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE7 | 174.19 | 15.0 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
19 | SMSTORE8_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE8 | 174.19 | 15.0 | 0.204 | 1.172E-003 | 5.440E-004 | 0.815 | 0.000 | 0.000 | 0.224 | 0.000 |
20 | SMSTORE8_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE8 | 174.19 | 15.0 | 0.222 | 1.276E-003 | 5.921E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | LGSTORE1 | Mixing/Well-Stirred |
2 | SMSTORE1 | Mixing/Well-Stirred |
3 | SMSTORE2 | Mixing/Well-Stirred |
4 | SMSTORE3 | Mixing/Well-Stirred |
5 | SMSTORE4 | Mixing/Well-Stirred |
6 | LGSTORE2 | Mixing/Well-Stirred |
7 | SMSTORE5 | Mixing/Well-Stirred |
8 | SMSTORE6 | Mixing/Well-Stirred |
9 | SMSTORE7 | Mixing/Well-Stirred |
10 | SMSTORE8 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone LGSTORE1 | 1.2000 |
3 | Zone SMSTORE1 | 1.2000 |
4 | Zone SMSTORE2 | 1.2000 |
5 | Zone SMSTORE3 | 1.2000 |
6 | Zone SMSTORE4 | 1.2000 |
7 | Zone LGSTORE2 | 1.2000 |
8 | Zone SMSTORE5 | 1.2000 |
9 | Zone SMSTORE6 | 1.2000 |
10 | Zone SMSTORE7 | 1.2000 |
11 | Zone SMSTORE8 | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone LGSTORE1 | 1.2000 |
3 | Zone SMSTORE1 | 1.2000 |
4 | Zone SMSTORE2 | 1.2000 |
5 | Zone SMSTORE3 | 1.2000 |
6 | Zone SMSTORE4 | 1.2000 |
7 | Zone LGSTORE2 | 1.2000 |
8 | Zone SMSTORE5 | 1.2000 |
9 | Zone SMSTORE6 | 1.2000 |
10 | Zone SMSTORE7 | 1.2000 |
11 | Zone SMSTORE8 | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | LGSTORE1 | Cooling | 24434.84035 | 29321.80841 | 2.05554 | 2.46665 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 33.40000 | 6.26594E-003 | 348.38640 | 29.99610 | 0.41145 | 0.00000 |
2 | LGSTORE1 | Heating | 41290.93052 | 49549.11663 | 2.03471 | 2.44166 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -27.60000 | 3.41898E-004 | 348.38640 | 29.99610 | 0.41145 | 0.00000 |
3 | SMSTORE1 | Cooling | 13387.41563 | 16064.89876 | 1.12619 | 1.35143 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 33.40000 | 6.26594E-003 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
4 | SMSTORE1 | Heating | 21382.10268 | 25658.52322 | 1.05362 | 1.26435 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -27.60000 | 3.41898E-004 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
5 | SMSTORE2 | Cooling | 13378.06668 | 16053.68001 | 1.12540 | 1.35048 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 33.40000 | 6.26594E-003 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
6 | SMSTORE2 | Heating | 21549.44462 | 25859.33354 | 1.06187 | 1.27425 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -27.60000 | 3.41898E-004 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
7 | SMSTORE3 | Cooling | 13414.91313 | 16097.89576 | 1.12850 | 1.35420 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 33.40000 | 6.26594E-003 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
8 | SMSTORE3 | Heating | 21606.02003 | 25927.22404 | 1.06466 | 1.27759 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -27.60000 | 3.41898E-004 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
9 | SMSTORE4 | Cooling | 13318.50607 | 15982.20728 | 1.12039 | 1.34447 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 33.40000 | 6.26594E-003 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
10 | SMSTORE4 | Heating | 21739.94393 | 26087.93271 | 1.07126 | 1.28551 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -27.60000 | 3.41898E-004 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
11 | LGSTORE2 | Cooling | 23407.42984 | 28088.91581 | 1.96912 | 2.36294 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 33.40000 | 6.26594E-003 | 348.38640 | 29.99610 | 0.41145 | 0.00000 |
12 | LGSTORE2 | Heating | 40254.75732 | 48305.70878 | 1.98367 | 2.38041 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -27.60000 | 3.41898E-004 | 348.38640 | 29.99610 | 0.41145 | 0.00000 |
13 | SMSTORE5 | Cooling | 12194.81621 | 14633.77945 | 1.02586 | 1.23104 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 33.40000 | 6.26594E-003 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
14 | SMSTORE5 | Heating | 22078.50814 | 26494.20977 | 1.08794 | 1.30553 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -27.60000 | 3.41898E-004 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
15 | SMSTORE6 | Cooling | 12109.46538 | 14531.35846 | 1.01868 | 1.22242 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 33.40000 | 6.26594E-003 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
16 | SMSTORE6 | Heating | 22057.01458 | 26468.41750 | 1.08689 | 1.30426 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -27.60000 | 3.41898E-004 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
17 | SMSTORE7 | Cooling | 12017.35747 | 14420.82897 | 1.01093 | 1.21312 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 33.40000 | 6.26594E-003 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
18 | SMSTORE7 | Heating | 22234.75655 | 26681.70786 | 1.09564 | 1.31477 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -27.60000 | 3.41898E-004 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
19 | SMSTORE8 | Cooling | 12147.80471 | 14577.36565 | 1.02191 | 1.22629 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 33.13333 | 6.26594E-003 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
20 | SMSTORE8 | Heating | 24547.74696 | 29457.29635 | 1.20960 | 1.45152 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -27.60000 | 3.41898E-004 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC_1:1 | Cooling | Sensible | 33088.58 | 2.46665 | 2.46665 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-AC_1:1 | Heating | Sensible | 70033.92 | 2.44166 | 2.44166 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
3 | PSZ-AC_2:2 | Cooling | Sensible | 17930.34 | 1.35143 | 1.35143 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-AC_2:2 | Heating | Sensible | 35887.93 | 1.26435 | 1.26435 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
5 | PSZ-AC_3:3 | Cooling | Sensible | 17919.27 | 1.35048 | 1.35048 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
6 | PSZ-AC_3:3 | Heating | Sensible | 36085.81 | 1.27425 | 1.27425 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
7 | PSZ-AC_4:4 | Cooling | Sensible | 17962.92 | 1.35420 | 1.35420 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
8 | PSZ-AC_4:4 | Heating | Sensible | 36152.72 | 1.27759 | 1.27759 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
9 | PSZ-AC_5:5 | Cooling | Sensible | 17848.71 | 1.34447 | 1.34447 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
10 | PSZ-AC_5:5 | Heating | Sensible | 36311.09 | 1.28551 | 1.28551 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
11 | PSZ-AC_6:6 | Cooling | Sensible | 31871.43 | 2.36294 | 2.36294 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
12 | PSZ-AC_6:6 | Heating | Sensible | 68808.71 | 2.38041 | 2.38041 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
13 | PSZ-AC_7:7 | Cooling | Sensible | 16517.49 | 1.23104 | 1.23104 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
14 | PSZ-AC_7:7 | Heating | Sensible | 36711.46 | 1.30553 | 1.30553 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
15 | PSZ-AC_8:8 | Cooling | Sensible | 16416.38 | 1.22242 | 1.22242 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
16 | PSZ-AC_8:8 | Heating | Sensible | 36686.04 | 1.30426 | 1.30426 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
17 | PSZ-AC_9:9 | Cooling | Sensible | 16307.26 | 1.21312 | 1.21312 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
18 | PSZ-AC_9:9 | Heating | Sensible | 36896.23 | 1.31477 | 1.31477 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
19 | PSZ-AC_10:10 | Cooling | Sensible | 16448.84 | 1.22629 | 1.22629 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
20 | PSZ-AC_10:10 | Heating | Sensible | 39631.34 | 1.45152 | 1.45152 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:Uncontrolled | LGSTORE1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.46665 |
2 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.35143 |
3 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE2 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.35048 |
4 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.35420 |
5 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE4 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.34447 |
6 | AirTerminal:SingleDuct:Uncontrolled | LGSTORE2 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.38041 |
7 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE5 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.30553 |
8 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.30426 |
9 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE7 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.31477 |
10 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE8 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.45152 |
11 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.46665 |
12 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.46665 |
13 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.46665 |
14 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 2.46665 |
15 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.46665 |
16 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Main Design Air Flow Rate [m3/s] | 2.46665 |
17 | AirLoopHVAC | PSZ-AC_1:1 | User Heating Air Flow Ratio [] | 1.00000 |
18 | AirLoopHVAC | PSZ-AC_1:1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
19 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.35143 |
20 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.35143 |
21 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.35143 |
22 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.35143 |
23 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.35143 |
24 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Main Design Air Flow Rate [m3/s] | 1.35143 |
25 | AirLoopHVAC | PSZ-AC_2:2 | User Heating Air Flow Ratio [] | 1.00000 |
26 | AirLoopHVAC | PSZ-AC_2:2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
27 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.35048 |
28 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.35048 |
29 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.35048 |
30 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.35048 |
31 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.35048 |
32 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Main Design Air Flow Rate [m3/s] | 1.35048 |
33 | AirLoopHVAC | PSZ-AC_3:3 | User Heating Air Flow Ratio [] | 1.00000 |
34 | AirLoopHVAC | PSZ-AC_3:3 | Calculated Heating Air Flow Ratio [] | 1.00000 |
35 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.35420 |
36 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.35420 |
37 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.35420 |
38 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.35420 |
39 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.35420 |
40 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Main Design Air Flow Rate [m3/s] | 1.35420 |
41 | AirLoopHVAC | PSZ-AC_4:4 | User Heating Air Flow Ratio [] | 1.00000 |
42 | AirLoopHVAC | PSZ-AC_4:4 | Calculated Heating Air Flow Ratio [] | 1.00000 |
43 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.34447 |
44 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.34447 |
45 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.34447 |
46 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.34447 |
47 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.34447 |
48 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Main Design Air Flow Rate [m3/s] | 1.34447 |
49 | AirLoopHVAC | PSZ-AC_5:5 | User Heating Air Flow Ratio [] | 1.00000 |
50 | AirLoopHVAC | PSZ-AC_5:5 | Calculated Heating Air Flow Ratio [] | 1.00000 |
51 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.38041 |
52 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.38041 |
53 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.38041 |
54 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Heating Design Air Flow Rate [m3/s] | 2.38041 |
55 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.38041 |
56 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Main Design Air Flow Rate [m3/s] | 2.38041 |
57 | AirLoopHVAC | PSZ-AC_6:6 | User Heating Air Flow Ratio [] | 1.00000 |
58 | AirLoopHVAC | PSZ-AC_6:6 | Calculated Heating Air Flow Ratio [] | 1.00000 |
59 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.30553 |
60 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.30553 |
61 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.30553 |
62 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.30553 |
63 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.30553 |
64 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Main Design Air Flow Rate [m3/s] | 1.30553 |
65 | AirLoopHVAC | PSZ-AC_7:7 | User Heating Air Flow Ratio [] | 1.00000 |
66 | AirLoopHVAC | PSZ-AC_7:7 | Calculated Heating Air Flow Ratio [] | 1.00000 |
67 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.30426 |
68 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.30426 |
69 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.30426 |
70 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.30426 |
71 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.30426 |
72 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Main Design Air Flow Rate [m3/s] | 1.30426 |
73 | AirLoopHVAC | PSZ-AC_8:8 | User Heating Air Flow Ratio [] | 1.00000 |
74 | AirLoopHVAC | PSZ-AC_8:8 | Calculated Heating Air Flow Ratio [] | 1.00000 |
75 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.31477 |
76 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.31477 |
77 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.31477 |
78 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.31477 |
79 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.31477 |
80 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Main Design Air Flow Rate [m3/s] | 1.31477 |
81 | AirLoopHVAC | PSZ-AC_9:9 | User Heating Air Flow Ratio [] | 1.00000 |
82 | AirLoopHVAC | PSZ-AC_9:9 | Calculated Heating Air Flow Ratio [] | 1.00000 |
83 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.45152 |
84 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.45152 |
85 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.45152 |
86 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.45152 |
87 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.45152 |
88 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Main Design Air Flow Rate [m3/s] | 1.45152 |
89 | AirLoopHVAC | PSZ-AC_10:10 | User Heating Air Flow Ratio [] | 1.00000 |
90 | AirLoopHVAC | PSZ-AC_10:10 | Calculated Heating Air Flow Ratio [] | 1.00000 |
91 | AirLoopHVAC | PSZ-AC_1:1 | Design Supply Air Flow Rate [m3/s] | 2.46665 |
92 | AirLoopHVAC | PSZ-AC_2:2 | Design Supply Air Flow Rate [m3/s] | 1.35143 |
93 | AirLoopHVAC | PSZ-AC_3:3 | Design Supply Air Flow Rate [m3/s] | 1.35048 |
94 | AirLoopHVAC | PSZ-AC_4:4 | Design Supply Air Flow Rate [m3/s] | 1.35420 |
95 | AirLoopHVAC | PSZ-AC_5:5 | Design Supply Air Flow Rate [m3/s] | 1.34447 |
96 | AirLoopHVAC | PSZ-AC_6:6 | Design Supply Air Flow Rate [m3/s] | 2.38041 |
97 | AirLoopHVAC | PSZ-AC_7:7 | Design Supply Air Flow Rate [m3/s] | 1.30553 |
98 | AirLoopHVAC | PSZ-AC_8:8 | Design Supply Air Flow Rate [m3/s] | 1.30426 |
99 | AirLoopHVAC | PSZ-AC_9:9 | Design Supply Air Flow Rate [m3/s] | 1.31477 |
100 | AirLoopHVAC | PSZ-AC_10:10 | Design Supply Air Flow Rate [m3/s] | 1.45152 |
101 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.46665 |
102 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41145 |
103 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.46665 |
104 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.46665 |
105 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.46665 |
106 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 2.46665 |
107 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.46665 |
108 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.23333 |
109 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 2.46665 |
110 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 40831.81592 |
111 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 40831.86000 |
112 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 20415.93000 |
113 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 40831.86000 |
114 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.79865 |
115 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.79866 |
116 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.79866 |
117 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.79866 |
118 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 40831.86000 |
119 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 70533.79421 |
120 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
121 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
122 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.46665 |
123 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 2699.76512 |
124 | Coil:Heating:Fuel | PSZ-AC_1:1_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 70533.79421 |
125 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.35143 |
126 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20573 |
127 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.35143 |
128 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.35143 |
129 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.35143 |
130 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.35143 |
131 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.35143 |
132 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.67572 |
133 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.35143 |
134 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 22370.96507 |
135 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 22370.89000 |
136 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 11185.44500 |
137 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 22370.89000 |
138 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.79866 |
139 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.79866 |
140 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.79866 |
141 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.79866 |
142 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 22370.89000 |
143 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 37629.28960 |
144 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
145 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
146 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.35143 |
147 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1540.77339 |
148 | Coil:Heating:Fuel | PSZ-AC_2:2_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 37629.28960 |
149 | Controller:OutdoorAir | PSZ-AC_3:3_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.35048 |
150 | Controller:OutdoorAir | PSZ-AC_3:3_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20573 |
151 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.35048 |
152 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.35048 |
153 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.35048 |
154 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.35048 |
155 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.35048 |
156 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.67524 |
157 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.35048 |
158 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 22355.23920 |
159 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 22355.27000 |
160 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 11177.63500 |
161 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 22355.27000 |
162 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.79865 |
163 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.79866 |
164 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.79866 |
165 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.79866 |
166 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 22355.27000 |
167 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 37610.40833 |
168 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
169 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
170 | Fan:SystemModel | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.35048 |
171 | Fan:SystemModel | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1539.69751 |
172 | Coil:Heating:Fuel | PSZ-AC_3:3_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 37610.40833 |
173 | Controller:OutdoorAir | PSZ-AC_4:4_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.35420 |
174 | Controller:OutdoorAir | PSZ-AC_4:4_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20573 |
175 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.35420 |
176 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.35420 |
177 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.35420 |
178 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.35420 |
179 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.35420 |
180 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.67710 |
181 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.35420 |
182 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 22416.81841 |
183 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 22416.84000 |
184 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 11208.42000 |
185 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 22416.84000 |
186 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.79865 |
187 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.79866 |
188 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.79866 |
189 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.79866 |
190 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 22416.84000 |
191 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 37684.78885 |
192 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
193 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
194 | Fan:SystemModel | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.35420 |
195 | Fan:SystemModel | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1543.93820 |
196 | Coil:Heating:Fuel | PSZ-AC_4:4_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 37684.78885 |
197 | Controller:OutdoorAir | PSZ-AC_5:5_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.34447 |
198 | Controller:OutdoorAir | PSZ-AC_5:5_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20573 |
199 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.34447 |
200 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.34447 |
201 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.34447 |
202 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.34447 |
203 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.34447 |
204 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.67224 |
205 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.34447 |
206 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 22255.75236 |
207 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 22255.74000 |
208 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 11127.87000 |
209 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 22255.74000 |
210 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.79866 |
211 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.79866 |
212 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.79866 |
213 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.79866 |
214 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 22255.74000 |
215 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 37490.15291 |
216 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
217 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
218 | Fan:SystemModel | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.34447 |
219 | Fan:SystemModel | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1532.84258 |
220 | Coil:Heating:Fuel | PSZ-AC_5:5_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 37490.15291 |
221 | Controller:OutdoorAir | PSZ-AC_6:6_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.38041 |
222 | Controller:OutdoorAir | PSZ-AC_6:6_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41145 |
223 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.38041 |
224 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.38041 |
225 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.38041 |
226 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 2.38041 |
227 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.38041 |
228 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.19021 |
229 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 2.38041 |
230 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 39404.23771 |
231 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 39404.20000 |
232 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 19702.10000 |
233 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 39404.20000 |
234 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.79866 |
235 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.79866 |
236 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.79866 |
237 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.79866 |
238 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 39404.20000 |
239 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 68808.70801 |
240 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
241 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
242 | Fan:SystemModel | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.38041 |
243 | Fan:SystemModel | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 2605.36937 |
244 | Coil:Heating:Fuel | PSZ-AC_6:6_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 68808.70801 |
245 | Controller:OutdoorAir | PSZ-AC_7:7_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.30553 |
246 | Controller:OutdoorAir | PSZ-AC_7:7_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20573 |
247 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.30553 |
248 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.30553 |
249 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.30553 |
250 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.30553 |
251 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.30553 |
252 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.65277 |
253 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.30553 |
254 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 21611.15709 |
255 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 21611.22000 |
256 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 10805.61000 |
257 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 21611.22000 |
258 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.79865 |
259 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.79866 |
260 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.79866 |
261 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.79866 |
262 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 21611.22000 |
263 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 36711.45918 |
264 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
265 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
266 | Fan:SystemModel | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.30553 |
267 | Fan:SystemModel | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1488.45195 |
268 | Coil:Heating:Fuel | PSZ-AC_7:7_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 36711.45918 |
269 | Controller:OutdoorAir | PSZ-AC_8:8_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.30426 |
270 | Controller:OutdoorAir | PSZ-AC_8:8_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20573 |
271 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.30426 |
272 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.30426 |
273 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.30426 |
274 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.30426 |
275 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.30426 |
276 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.65213 |
277 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.30426 |
278 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 21590.13408 |
279 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 21590.18000 |
280 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 10795.09000 |
281 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 21590.18000 |
282 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.79865 |
283 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.79866 |
284 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.79866 |
285 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.79866 |
286 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 21590.18000 |
287 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 36686.04241 |
288 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
289 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
290 | Fan:SystemModel | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.30426 |
291 | Fan:SystemModel | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1487.00285 |
292 | Coil:Heating:Fuel | PSZ-AC_8:8_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 36686.04241 |
293 | Controller:OutdoorAir | PSZ-AC_9:9_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.31477 |
294 | Controller:OutdoorAir | PSZ-AC_9:9_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20573 |
295 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.31477 |
296 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.31477 |
297 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.31477 |
298 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.31477 |
299 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.31477 |
300 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.65739 |
301 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.31477 |
302 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 21764.11190 |
303 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 21764.17000 |
304 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 10882.08500 |
305 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 21764.17000 |
306 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.79865 |
307 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.79866 |
308 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.79866 |
309 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.79866 |
310 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 21764.17000 |
311 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 36896.22817 |
312 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
313 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
314 | Fan:SystemModel | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.31477 |
315 | Fan:SystemModel | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1498.98628 |
316 | Coil:Heating:Fuel | PSZ-AC_9:9_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 36896.22817 |
317 | Controller:OutdoorAir | PSZ-AC_10:10_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.45152 |
318 | Controller:OutdoorAir | PSZ-AC_10:10_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20573 |
319 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.45152 |
320 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.45152 |
321 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.45152 |
322 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.45152 |
323 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.45152 |
324 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.72576 |
325 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.45152 |
326 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 24027.80997 |
327 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 24027.89000 |
328 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 12013.94500 |
329 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 24027.89000 |
330 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.79865 |
331 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.79866 |
332 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.79866 |
333 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.79866 |
334 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 24027.89000 |
335 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 39631.33538 |
336 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
337 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
338 | Fan:SystemModel | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.45152 |
339 | Fan:SystemModel | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1588.70208 |
340 | Coil:Heating:Fuel | PSZ-AC_10:10_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 39631.33538 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | 38898.7 | 9.54 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | 21311.8 | 28.32 | |||
3 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | 21296.9 | 38.37 | |||
4 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | 21355.5 | 48.29 | |||
5 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | 21202.1 | 58.66 | |||
6 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | 37538.7 | 43.16 | |||
7 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | 20588.1 | 88.72 | |||
8 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | 20568.0 | 98.83 | |||
9 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | 20733.8 | 108.06 | |||
10 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | 22890.3 | 107.91 |
Zone Name | # Surfaces | |
1 | LGSTORE1 | 15 |
2 | SMSTORE1 | 11 |
3 | SMSTORE2 | 11 |
4 | SMSTORE3 | 11 |
5 | SMSTORE4 | 11 |
6 | LGSTORE2 | 15 |
7 | SMSTORE5 | 11 |
8 | SMSTORE6 | 11 |
9 | SMSTORE7 | 11 |
10 | SMSTORE8 | 11 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | LGSTORE1_WALL_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | LGSTORE1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 71.15 | 78.94 | 71.15 | 0.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | LGSTORE1_WALL_3_DOOR_1 | Door | LGSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
4 | LGSTORE1_WALL_3_DOOR_2 | Door | LGSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
5 | LGSTORE1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
6 | LGSTORE1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 58.20 | 78.94 | 58.20 | 180.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
7 | LGSTORE1_WALL_1_WINDOW_1 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.47_SHGC_0.4 | N/A | 2.672 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
8 | LGSTORE1_WALL_1_WINDOW_2 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.47_SHGC_0.4 | N/A | 2.672 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
9 | LGSTORE1_WALL_1_WINDOW_3 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.47_SHGC_0.4 | N/A | 2.672 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
10 | LGSTORE1_WALL_1_WINDOW_4 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.47_SHGC_0.4 | N/A | 2.672 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
11 | LGSTORE1_WALL_1_DOOR_1 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.47_SHGC_0.4 | N/A | 2.672 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
12 | LGSTORE1_WALL_1_DOOR_2 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.47_SHGC_0.4 | N/A | 2.672 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
13 | LGSTORE1_FLOOR | Floor | CTF - ConductionTransferFunction | LGSTORE1_FLOOR_FFACTOR | 0.146 | 0.141 | 348.39 | 348.39 | 348.39 | 270.00 | 180.00 | 22.86 | 15.24 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | LGSTORE1_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 348.39 | 348.39 | 348.39 | 270.00 | 0.00 | 22.86 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
15 | LGSTORE1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 696.77 | 696.77 | 696.77 | 0.00 | 90.00 | 696.77 | 1.00 | 0.00 | LGSTORE1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
16 | SMSTORE1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 29.10 | 39.47 | 29.10 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
17 | SMSTORE1_WALL_1_WINDOW_1 | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.47_SHGC_0.4 | N/A | 2.672 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
18 | SMSTORE1_WALL_1_WINDOW_2 | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.47_SHGC_0.4 | N/A | 2.672 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
19 | SMSTORE1_WALL_1_DOOR | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.47_SHGC_0.4 | N/A | 2.672 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
20 | SMSTORE1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | SMSTORE1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 35.57 | 39.47 | 35.57 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | SMSTORE1_WALL_3_DOOR | Door | SMSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
23 | SMSTORE1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE2_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
24 | SMSTORE1_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE1_FLOOR_FFACTOR | 8.283E-002 | 8.119E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | SMSTORE1_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
26 | SMSTORE1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
27 | SMSTORE2_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 29.12 | 39.47 | 29.12 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | SMSTORE2_WALL_1_WINDOW_1 | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.47_SHGC_0.4 | N/A | 2.672 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
29 | SMSTORE2_WALL_1_WINDOW_2 | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.47_SHGC_0.4 | N/A | 2.672 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
30 | SMSTORE2_WALL_1_DOOR | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.47_SHGC_0.4 | N/A | 2.672 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
31 | SMSTORE2_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
32 | SMSTORE2_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | SMSTORE2_WALL_3_DOOR | Door | SMSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
34 | SMSTORE2_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE3_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | SMSTORE2_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE2_FLOOR_FFACTOR | 8.283E-002 | 8.119E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
36 | SMSTORE2_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
37 | SMSTORE2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
38 | SMSTORE3_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 29.12 | 39.47 | 29.12 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
39 | SMSTORE3_WALL_1_WINDOW_1 | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.47_SHGC_0.4 | N/A | 2.672 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
40 | SMSTORE3_WALL_1_WINDOW_2 | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.47_SHGC_0.4 | N/A | 2.672 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
41 | SMSTORE3_WALL_1_DOOR | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.47_SHGC_0.4 | N/A | 2.672 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
42 | SMSTORE3_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE2_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | SMSTORE3_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | SMSTORE3_WALL_3_DOOR | Door | SMSTORE3_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
45 | SMSTORE3_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE4_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | SMSTORE3_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE3_FLOOR_FFACTOR | 8.283E-002 | 8.119E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
47 | SMSTORE3_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
48 | SMSTORE3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
49 | SMSTORE4_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 29.12 | 39.47 | 29.12 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | SMSTORE4_WALL_1_WINDOW_1 | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.47_SHGC_0.4 | N/A | 2.672 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
51 | SMSTORE4_WALL_1_WINDOW_2 | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.47_SHGC_0.4 | N/A | 2.672 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
52 | SMSTORE4_WALL_1_DOOR | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.47_SHGC_0.4 | N/A | 2.672 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | SMSTORE4_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE3_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | SMSTORE4_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | SMSTORE4_WALL_3_DOOR | Door | SMSTORE4_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | SMSTORE4_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE2_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | SMSTORE4_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE4_FLOOR_FFACTOR | 8.283E-002 | 8.119E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | SMSTORE4_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | SMSTORE4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | LGSTORE2_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE4_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | LGSTORE2_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 71.19 | 78.94 | 71.19 | 0.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
62 | LGSTORE2_WALL_3_DOOR_1 | Door | LGSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
63 | LGSTORE2_WALL_3_DOOR_2 | Door | LGSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
64 | LGSTORE2_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE5_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | LGSTORE2_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 58.24 | 78.94 | 58.24 | 180.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
66 | LGSTORE2_WALL_1_WINDOW_1 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.47_SHGC_0.4 | N/A | 2.672 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | LGSTORE2_WALL_1_WINDOW_2 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.47_SHGC_0.4 | N/A | 2.672 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | LGSTORE2_WALL_1_WINDOW_3 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.47_SHGC_0.4 | N/A | 2.672 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | LGSTORE2_WALL_1_WINDOW_4 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.47_SHGC_0.4 | N/A | 2.672 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | LGSTORE2_WALL_1_DOOR_1 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.47_SHGC_0.4 | N/A | 2.672 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
71 | LGSTORE2_WALL_1_DOOR_2 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.47_SHGC_0.4 | N/A | 2.672 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
72 | LGSTORE2_FLOOR | Floor | CTF - ConductionTransferFunction | LGSTORE2_FLOOR_FFACTOR | 8.283E-002 | 8.119E-002 | 348.39 | 348.39 | 348.39 | 270.00 | 180.00 | 22.86 | 15.24 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
73 | LGSTORE2_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 348.39 | 348.39 | 348.39 | 270.00 | 0.00 | 22.86 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
74 | LGSTORE2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 696.77 | 696.77 | 696.77 | 0.00 | 90.00 | 696.77 | 1.00 | 0.00 | LGSTORE2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
75 | SMSTORE5_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 29.12 | 39.47 | 29.12 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | SMSTORE5_WALL_1_WINDOW_1 | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.47_SHGC_0.4 | N/A | 2.672 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
77 | SMSTORE5_WALL_1_WINDOW_2 | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.47_SHGC_0.4 | N/A | 2.672 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | SMSTORE5_WALL_1_DOOR | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.47_SHGC_0.4 | N/A | 2.672 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
79 | SMSTORE5_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE2_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | SMSTORE5_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | SMSTORE5_WALL_3_DOOR | Door | SMSTORE5_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
82 | SMSTORE5_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE6_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
83 | SMSTORE5_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE5_FLOOR_FFACTOR | 8.283E-002 | 8.119E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
84 | SMSTORE5_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
85 | SMSTORE5_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE5_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
86 | SMSTORE6_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 29.12 | 39.47 | 29.12 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | SMSTORE6_WALL_1_WINDOW_1 | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.47_SHGC_0.4 | N/A | 2.672 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
88 | SMSTORE6_WALL_1_WINDOW_2 | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.47_SHGC_0.4 | N/A | 2.672 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
89 | SMSTORE6_WALL_1_DOOR | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.47_SHGC_0.4 | N/A | 2.672 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
90 | SMSTORE6_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE5_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
91 | SMSTORE6_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
92 | SMSTORE6_WALL_3_DOOR | Door | SMSTORE6_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
93 | SMSTORE6_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE7_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | SMSTORE6_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE6_FLOOR_FFACTOR | 8.283E-002 | 8.119E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
95 | SMSTORE6_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
96 | SMSTORE6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
97 | SMSTORE7_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 29.12 | 39.47 | 29.12 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | SMSTORE7_WALL_1_WINDOW_1 | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.47_SHGC_0.4 | N/A | 2.672 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
99 | SMSTORE7_WALL_1_WINDOW_2 | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.47_SHGC_0.4 | N/A | 2.672 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
100 | SMSTORE7_WALL_1_DOOR | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.47_SHGC_0.4 | N/A | 2.672 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
101 | SMSTORE7_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE6_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
102 | SMSTORE7_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 35.59 | 39.47 | 35.59 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | SMSTORE7_WALL_3_DOOR | Door | SMSTORE7_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
104 | SMSTORE7_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE8_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | SMSTORE7_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE7_FLOOR_FFACTOR | 8.283E-002 | 8.119E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
106 | SMSTORE7_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
107 | SMSTORE7_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE7_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
108 | SMSTORE8_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 29.12 | 39.47 | 29.12 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | SMSTORE8_WALL_1_WINDOW_1 | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.47_SHGC_0.4 | N/A | 2.672 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
110 | SMSTORE8_WALL_1_WINDOW_2 | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.47_SHGC_0.4 | N/A | 2.672 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
111 | SMSTORE8_WALL_1_DOOR | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.47_SHGC_0.4 | N/A | 2.672 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
112 | SMSTORE8_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE7_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
113 | SMSTORE8_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | SMSTORE8_WALL_3_DOOR | Door | SMSTORE8_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
115 | SMSTORE8_WALL_4 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | SMSTORE8_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE8_FLOOR_FFACTOR | 0.211 | 0.201 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | SMSTORE8_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | SMSTORE8_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE8_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1 |
2 | VETERANS DAY | Holiday | InputFile | 11/11 | 1 |
3 | CHRISTMAS | Holiday | InputFile | 12/25 | 1 |
4 | INDEPENDENCE DAY | Holiday | InputFile | 07/04 | 1 |
5 | MLK DAY | Holiday | InputFile | 01/16 | 1 |
6 | PRESIDENTS DAY | Holiday | InputFile | 02/20 | 1 |
7 | MEMORIAL DAY | Holiday | InputFile | 05/29 | 1 |
8 | LABOR DAY | Holiday | InputFile | 09/04 | 1 |
9 | COLUMBUS DAY | Holiday | InputFile | 10/09 | 1 |
10 | THANKSGIVING | Holiday | InputFile | 11/23 | 1 |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
NumberofWarmupDays | |
1 | 14 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | LGSTORE1 | RunPeriod: RUNPERIOD 1 | 3.8028092937E-002 | 0.2170689475 | Pass | Pass | 0.3642220151 | 1.9949345789 | Pass | Pass |
2 | SMSTORE1 | RunPeriod: RUNPERIOD 1 | 7.4192212524E-002 | 0.1764145616 | Pass | Pass | 0.2098982588 | 0.6183282369 | Pass | Pass |
3 | SMSTORE2 | RunPeriod: RUNPERIOD 1 | 3.9078034294E-002 | 0.1833955738 | Pass | Pass | 0.3754209704 | 1.7600809571 | Pass | Pass |
4 | SMSTORE3 | RunPeriod: RUNPERIOD 1 | 4.3060643803E-002 | 0.2207116160 | Pass | Pass | 0.1728785048 | 0.6499041673 | Pass | Pass |
5 | SMSTORE4 | RunPeriod: RUNPERIOD 1 | 4.7528876910E-002 | 0.2518473133 | Pass | Pass | 0.1380592324 | 0.4510062150 | Pass | Pass |
6 | LGSTORE2 | RunPeriod: RUNPERIOD 1 | 6.0577920406E-002 | 0.3083200947 | Pass | Pass | 9.4181552134E-002 | 0.3232417220 | Pass | Pass |
7 | SMSTORE5 | RunPeriod: RUNPERIOD 1 | 6.1261872576E-002 | 0.3138628399 | Pass | Pass | 6.2359668082E-002 | 0.1712805527 | Pass | Pass |
8 | SMSTORE6 | RunPeriod: RUNPERIOD 1 | 6.2839193463E-002 | 0.3229286800 | Pass | Pass | 5.6347786651E-002 | 0.1499412037 | Pass | Pass |
9 | SMSTORE7 | RunPeriod: RUNPERIOD 1 | 6.8272716974E-002 | 0.3561518944 | Pass | Pass | 4.6582707013E-002 | 0.1205125134 | Pass | Pass |
10 | SMSTORE8 | RunPeriod: RUNPERIOD 1 | 0.1016289128 | 0.4232988589 | Pass | Pass | 4.1705953695E-002 | 0.1138808201 | Pass | Pass |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2020-06-03 19:21:42
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | -27.60 | 0.00 | -27.60 | Wetbulb [C] | 2.70 | 230.00 |
GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 33.40 | 16.00 | 16.30 | Wetbulb [C] | 4.90 | 240.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2020-06-03 19:21:42
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_2 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE1_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 78.94 | 71.15 | 0.00 | 90.00 | N |
LGSTORE1_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 78.94 | 58.20 | 180.00 | 90.00 | S |
LGSTORE1_ROOF | NONRES_ROOF | 0.23 | 0.273 | 0.283 | 348.39 | 348.39 | 270.00 | 0.00 | |
SMSTORE1_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 29.10 | 180.00 | 90.00 | S |
SMSTORE1_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 35.57 | 0.00 | 90.00 | N |
SMSTORE1_ROOF | NONRES_ROOF | 0.23 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE2_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 29.12 | 180.00 | 90.00 | S |
SMSTORE2_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE2_ROOF | NONRES_ROOF | 0.23 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE3_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 29.12 | 180.00 | 90.00 | S |
SMSTORE3_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE3_ROOF | NONRES_ROOF | 0.23 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE4_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 29.12 | 180.00 | 90.00 | S |
SMSTORE4_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE4_ROOF | NONRES_ROOF | 0.23 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
LGSTORE2_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 78.94 | 71.19 | 0.00 | 90.00 | N |
LGSTORE2_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 78.94 | 58.24 | 180.00 | 90.00 | S |
LGSTORE2_ROOF | NONRES_ROOF | 0.23 | 0.273 | 0.283 | 348.39 | 348.39 | 270.00 | 0.00 | |
SMSTORE5_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 29.12 | 180.00 | 90.00 | S |
SMSTORE5_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE5_ROOF | NONRES_ROOF | 0.23 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE6_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 29.12 | 180.00 | 90.00 | S |
SMSTORE6_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE6_ROOF | NONRES_ROOF | 0.23 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE7_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 29.12 | 180.00 | 90.00 | S |
SMSTORE7_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE7_ROOF | NONRES_ROOF | 0.23 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE8_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 29.12 | 180.00 | 90.00 | S |
SMSTORE8_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE8_WALL_4 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE8_ROOF | NONRES_ROOF | 0.23 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
LGSTORE1_FLOOR | LGSTORE1_FLOOR_FFACTOR | 1.00 | 0.146 | 348.39 | 348.39 | 270.00 | 180.00 | ||
SMSTORE1_FLOOR | SMSTORE1_FLOOR_FFACTOR | 1.00 | 0.083 | 174.19 | 174.19 | 270.00 | 180.00 | ||
SMSTORE2_FLOOR | SMSTORE2_FLOOR_FFACTOR | 1.00 | 0.083 | 174.19 | 174.19 | 270.00 | 180.00 | ||
SMSTORE3_FLOOR | SMSTORE3_FLOOR_FFACTOR | 1.00 | 0.083 | 174.19 | 174.19 | 270.00 | 180.00 | ||
SMSTORE4_FLOOR | SMSTORE4_FLOOR_FFACTOR | 1.00 | 0.083 | 174.19 | 174.19 | 270.00 | 180.00 | ||
LGSTORE2_FLOOR | LGSTORE2_FLOOR_FFACTOR | 1.00 | 0.083 | 348.39 | 348.39 | 270.00 | 180.00 | ||
SMSTORE5_FLOOR | SMSTORE5_FLOOR_FFACTOR | 1.00 | 0.083 | 174.19 | 174.19 | 270.00 | 180.00 | ||
SMSTORE6_FLOOR | SMSTORE6_FLOOR_FFACTOR | 1.00 | 0.083 | 174.19 | 174.19 | 270.00 | 180.00 | ||
SMSTORE7_FLOOR | SMSTORE7_FLOOR_FFACTOR | 1.00 | 0.083 | 174.19 | 174.19 | 270.00 | 180.00 | ||
SMSTORE8_FLOOR | SMSTORE8_FLOOR_FFACTOR | 1.00 | 0.211 | 174.19 | 174.19 | 270.00 | 180.00 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.47_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.672 | 0.394 | 0.401 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE1_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.47_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.672 | 0.394 | 0.401 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE1_WALL_1_WINDOW_3 | NONRESWINDOW_U_0.47_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.672 | 0.394 | 0.401 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE1_WALL_1_WINDOW_4 | NONRESWINDOW_U_0.47_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.672 | 0.394 | 0.401 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE1_WALL_1_DOOR_1 | NONRESWINDOW_U_0.47_SHGC_0.4 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.672 | 0.394 | 0.401 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE1_WALL_1_DOOR_2 | NONRESWINDOW_U_0.47_SHGC_0.4 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.672 | 0.394 | 0.401 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE1_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.47_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.672 | 0.394 | 0.401 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE1_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.47_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.672 | 0.394 | 0.401 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE1_WALL_1_DOOR | NONRESWINDOW_U_0.47_SHGC_0.4 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.672 | 0.394 | 0.401 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE2_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.47_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.672 | 0.394 | 0.401 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE2_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.47_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.672 | 0.394 | 0.401 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE2_WALL_1_DOOR | NONRESWINDOW_U_0.47_SHGC_0.4 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.672 | 0.394 | 0.401 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE3_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.47_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.672 | 0.394 | 0.401 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE3_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.47_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.672 | 0.394 | 0.401 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE3_WALL_1_DOOR | NONRESWINDOW_U_0.47_SHGC_0.4 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.672 | 0.394 | 0.401 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE4_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.47_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.672 | 0.394 | 0.401 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE4_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.47_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.672 | 0.394 | 0.401 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE4_WALL_1_DOOR | NONRESWINDOW_U_0.47_SHGC_0.4 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.672 | 0.394 | 0.401 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE2_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.47_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.672 | 0.394 | 0.401 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE2_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.47_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.672 | 0.394 | 0.401 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE2_WALL_1_WINDOW_3 | NONRESWINDOW_U_0.47_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.672 | 0.394 | 0.401 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE2_WALL_1_WINDOW_4 | NONRESWINDOW_U_0.47_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.672 | 0.394 | 0.401 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE2_WALL_1_DOOR_1 | NONRESWINDOW_U_0.47_SHGC_0.4 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.672 | 0.394 | 0.401 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE2_WALL_1_DOOR_2 | NONRESWINDOW_U_0.47_SHGC_0.4 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.672 | 0.394 | 0.401 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE5_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.47_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.672 | 0.394 | 0.401 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE5_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.47_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.672 | 0.394 | 0.401 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE5_WALL_1_DOOR | NONRESWINDOW_U_0.47_SHGC_0.4 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.672 | 0.394 | 0.401 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE6_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.47_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.672 | 0.394 | 0.401 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE6_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.47_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.672 | 0.394 | 0.401 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE6_WALL_1_DOOR | NONRESWINDOW_U_0.47_SHGC_0.4 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.672 | 0.394 | 0.401 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE7_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.47_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.672 | 0.394 | 0.401 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE7_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.47_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.672 | 0.394 | 0.401 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE7_WALL_1_DOOR | NONRESWINDOW_U_0.47_SHGC_0.4 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.672 | 0.394 | 0.401 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE8_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.47_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.672 | 0.394 | 0.401 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE8_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.47_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.672 | 0.394 | 0.401 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE8_WALL_1_DOOR | NONRESWINDOW_U_0.47_SHGC_0.4 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.672 | 0.394 | 0.401 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | ||
Total or Average | 124.29 | 2.672 | 0.394 | 0.401 | ||||||||||||
North Total or Average | 0.00 | - | - | - | ||||||||||||
Non-North Total or Average | 124.29 | 2.672 | 0.394 | 0.401 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
LGSTORE1_WALL_3_DOOR_1 | SWINGING DOOR_CON | 2.492 | 3.975 | 3.90 | LGSTORE1_WALL_3 |
LGSTORE1_WALL_3_DOOR_2 | SWINGING DOOR_CON | 2.492 | 3.975 | 3.90 | LGSTORE1_WALL_3 |
SMSTORE1_WALL_3_DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 3.90 | SMSTORE1_WALL_3 |
SMSTORE2_WALL_3_DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 3.88 | SMSTORE2_WALL_3 |
SMSTORE3_WALL_3_DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 3.88 | SMSTORE3_WALL_3 |
SMSTORE4_WALL_3_DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 3.88 | SMSTORE4_WALL_3 |
LGSTORE2_WALL_3_DOOR_1 | SWINGING DOOR_CON | 2.492 | 3.975 | 3.88 | LGSTORE2_WALL_3 |
LGSTORE2_WALL_3_DOOR_2 | SWINGING DOOR_CON | 2.492 | 3.975 | 3.88 | LGSTORE2_WALL_3 |
SMSTORE5_WALL_3_DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 3.88 | SMSTORE5_WALL_3 |
SMSTORE6_WALL_3_DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 3.88 | SMSTORE6_WALL_3 |
SMSTORE7_WALL_3_DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 3.88 | SMSTORE7_WALL_3 |
SMSTORE8_WALL_3_DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 3.88 | SMSTORE8_WALL_3 |
Report: Shading Summary
For: Entire Facility
Timestamp: 2020-06-03 19:21:42
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
LGSTORE1_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_DOOR_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_DOOR_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_DOOR_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_DOOR_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2020-06-03 19:21:42
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
LGSTORE1_LIGHTS | LGSTORE1 | 18.3225 | 348.39 | 6383.30 | LightsWired | TYPE1_LIGHT_SCH | 98.40 | 168.00 | 98.38 | 0.0000 | Y | 117.88 |
LGSTORE1_LIGHTS_ALLOWANCE | LGSTORE1 | 6.6413 | 348.39 | 2313.75 | LightsWired | TYPE1_LIGHT_SCH | 98.40 | 168.00 | 98.38 | 0.0000 | Y | 42.73 |
SMSTORE1_LIGHTS | SMSTORE1 | 18.3225 | 174.19 | 3191.65 | LightsWired | TYPE1_LIGHT_SCH | 98.40 | 168.00 | 98.38 | 0.0000 | Y | 58.94 |
SMSTORE1_LIGHTS_ALLOWANCE | SMSTORE1 | 9.5153 | 174.19 | 1657.50 | LightsWired | TYPE1_LIGHT_SCH | 98.40 | 168.00 | 98.38 | 0.0000 | Y | 30.61 |
SMSTORE2_LIGHTS | SMSTORE2 | 18.3225 | 174.19 | 3191.65 | LightsWired | TYPE2_LIGHT_SCH | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 46.71 |
SMSTORE2_LIGHTS_ALLOWANCE | SMSTORE2 | 7.3625 | 174.19 | 1282.50 | LightsWired | TYPE2_LIGHT_SCH | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 18.77 |
SMSTORE3_LIGHTS | SMSTORE3 | 18.3225 | 174.19 | 3191.65 | LightsWired | TYPE2_LIGHT_SCH | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 46.71 |
SMSTORE3_LIGHTS_ALLOWANCE | SMSTORE3 | 7.3625 | 174.19 | 1282.50 | LightsWired | TYPE2_LIGHT_SCH | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 18.77 |
SMSTORE4_LIGHTS | SMSTORE4 | 18.3225 | 174.19 | 3191.65 | LightsWired | TYPE2_LIGHT_SCH | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 46.71 |
SMSTORE4_LIGHTS_ALLOWANCE | SMSTORE4 | 7.3625 | 174.19 | 1282.50 | LightsWired | TYPE2_LIGHT_SCH | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 18.77 |
LGSTORE2_LIGHTS | LGSTORE2 | 18.3225 | 348.39 | 6383.30 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 168.00 | 71.66 | 0.0000 | Y | 85.86 |
LGSTORE2_LIGHTS_ALLOWANCE | LGSTORE2 | 0.0000 | 348.39 | 0.00 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE5_LIGHTS | SMSTORE5 | 18.3225 | 174.19 | 3191.65 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 168.00 | 71.66 | 0.0000 | Y | 42.93 |
SMSTORE5_LIGHTS_ALLOWANCE | SMSTORE5 | 0.0000 | 174.19 | 0.00 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE6_LIGHTS | SMSTORE6 | 18.3225 | 174.19 | 3191.65 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 168.00 | 71.66 | 0.0000 | Y | 42.93 |
SMSTORE6_LIGHTS_ALLOWANCE | SMSTORE6 | 0.0000 | 174.19 | 0.00 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE7_LIGHTS | SMSTORE7 | 18.3225 | 174.19 | 3191.65 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 168.00 | 71.66 | 0.0000 | Y | 42.93 |
SMSTORE7_LIGHTS_ALLOWANCE | SMSTORE7 | 0.0000 | 174.19 | 0.00 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE8_LIGHTS | SMSTORE8 | 18.3225 | 174.19 | 3191.65 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 168.00 | 71.66 | 0.0000 | Y | 42.93 |
SMSTORE8_LIGHTS_ALLOWANCE | SMSTORE8 | 0.0000 | 174.19 | 0.00 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
Interior Lighting Total | 11.0315 | 4180.64 | 46118.53 | 704.17 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS | 7048.38 | AstronomicalClock | - | 83.57 | 83.57 | 110.57 | |
Exterior Lighting Total | 7048.38 | 110.57 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2020-06-03 19:21:42
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 40831.86 | 32610.77 | 8221.09 | 0.80 | 3.30 | |||
PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 22370.89 | 17866.74 | 4504.15 | 0.80 | 3.50 | |||
PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 22355.27 | 17854.26 | 4501.01 | 0.80 | 3.50 | |||
PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 22416.84 | 17903.43 | 4513.41 | 0.80 | 3.50 | |||
PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 22255.74 | 17774.77 | 4480.97 | 0.80 | 3.50 | |||
PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 39404.20 | 31470.56 | 7933.64 | 0.80 | 3.50 | |||
PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 21611.22 | 17260.02 | 4351.20 | 0.80 | 3.50 | |||
PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 21590.18 | 17243.21 | 4346.97 | 0.80 | 3.50 | |||
PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 21764.17 | 17382.17 | 4382.00 | 0.80 | 3.50 | |||
PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 24027.89 | 19190.11 | 4837.78 | 0.80 | 3.50 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | 38898.7 | 9.54 | ||||
PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | 21311.8 | 28.32 | ||||
PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | 21296.9 | 38.37 | ||||
PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | 21355.5 | 48.29 | ||||
PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | 21202.1 | 58.66 | ||||
PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | 37538.7 | 43.16 | ||||
PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | 20588.1 | 88.72 | ||||
PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | 20568.0 | 98.83 | ||||
PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | 20733.8 | 108.06 | ||||
PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | 22890.3 | 107.91 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
PSZ-AC_1:1_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 70533.79 | 0.80 | |
PSZ-AC_2:2_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 37629.29 | 0.80 | |
PSZ-AC_3:3_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 37610.41 | 0.80 | |
PSZ-AC_4:4_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 37684.79 | 0.80 | |
PSZ-AC_5:5_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 37490.15 | 0.80 | |
PSZ-AC_6:6_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 68808.71 | 0.80 | |
PSZ-AC_7:7_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 36711.46 | 0.80 | |
PSZ-AC_8:8_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 36686.04 | 0.80 | |
PSZ-AC_9:9_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 36896.23 | 0.80 | |
PSZ-AC_10:10_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 39631.34 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.57 | 622.50 | 2.47 | 2699.77 | 1094.51 | 1.00 | 1.26 | General | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 |
PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.55 | 622.50 | 1.35 | 1540.77 | 1140.11 | 1.00 | 1.30 | General | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 |
PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.55 | 622.50 | 1.35 | 1539.70 | 1140.11 | 1.00 | 1.30 | General | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 |
PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.55 | 622.50 | 1.35 | 1543.94 | 1140.11 | 1.00 | 1.30 | General | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 |
PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.55 | 622.50 | 1.34 | 1532.84 | 1140.11 | 1.00 | 1.30 | General | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 |
PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.57 | 622.50 | 2.38 | 2605.37 | 1094.51 | 1.00 | 1.26 | General | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 |
PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.55 | 622.50 | 1.31 | 1488.45 | 1140.11 | 1.00 | 1.30 | General | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 |
PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.55 | 622.50 | 1.30 | 1487.00 | 1140.11 | 1.00 | 1.30 | General | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 |
PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.55 | 622.50 | 1.31 | 1498.99 | 1140.11 | 1.00 | 1.30 | General | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 |
PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.57 | 622.50 | 1.45 | 1588.70 | 1094.51 | 1.00 | 1.34 | General | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
GAS TANK1 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK2 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK3 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK4 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK5 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK6 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK7 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:21:42
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
LGSTORE1 | 24434.84 | 29321.81 | 84.16 | 2.056 | 2.467 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 23.89 | 23.89 | 0.00711 | 33.40 | 0.00627 | 0.411 | 0.00 |
SMSTORE1 | 13387.42 | 16064.90 | 92.22 | 1.126 | 1.351 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 23.89 | 23.89 | 0.00709 | 33.40 | 0.00627 | 0.206 | 0.00 |
SMSTORE2 | 13378.07 | 16053.68 | 92.16 | 1.125 | 1.350 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 23.89 | 23.89 | 0.00709 | 33.40 | 0.00627 | 0.206 | 0.00 |
SMSTORE3 | 13414.91 | 16097.90 | 92.41 | 1.129 | 1.354 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 23.89 | 23.89 | 0.00709 | 33.40 | 0.00627 | 0.206 | 0.00 |
SMSTORE4 | 13318.51 | 15982.21 | 91.75 | 1.120 | 1.344 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 23.89 | 23.89 | 0.00709 | 33.40 | 0.00627 | 0.206 | 0.00 |
LGSTORE2 | 23407.43 | 28088.92 | 80.63 | 1.969 | 2.363 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 23.89 | 23.89 | 0.00712 | 33.40 | 0.00627 | 0.411 | 0.00 |
SMSTORE5 | 12194.82 | 14633.78 | 84.01 | 1.026 | 1.231 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 23.89 | 23.89 | 0.00710 | 33.40 | 0.00627 | 0.206 | 0.00 |
SMSTORE6 | 12109.47 | 14531.36 | 83.42 | 1.019 | 1.222 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 23.89 | 23.89 | 0.00710 | 33.40 | 0.00627 | 0.206 | 0.00 |
SMSTORE7 | 12017.36 | 14420.83 | 82.79 | 1.011 | 1.213 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 23.89 | 23.89 | 0.00710 | 33.40 | 0.00627 | 0.206 | 0.00 |
SMSTORE8 | 12147.80 | 14577.37 | 83.69 | 1.022 | 1.226 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 23.89 | 23.89 | 0.00709 | 33.13 | 0.00627 | 0.206 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
LGSTORE1 | 41290.93 | 49549.12 | 142.22 | 2.035 | 2.442 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00655 | -27.60 | 0.00034 | 0.411 | 0.00 |
SMSTORE1 | 21382.10 | 25658.52 | 147.30 | 1.054 | 1.264 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00644 | -27.60 | 0.00034 | 0.206 | 0.00 |
SMSTORE2 | 21549.44 | 25859.33 | 148.45 | 1.062 | 1.274 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00645 | -27.60 | 0.00034 | 0.206 | 0.00 |
SMSTORE3 | 21606.02 | 25927.22 | 148.84 | 1.065 | 1.278 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00645 | -27.60 | 0.00034 | 0.206 | 0.00 |
SMSTORE4 | 21739.94 | 26087.93 | 149.76 | 1.071 | 1.286 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00646 | -27.60 | 0.00034 | 0.206 | 0.00 |
LGSTORE2 | 40254.76 | 48305.71 | 138.66 | 1.984 | 2.380 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00653 | -27.60 | 0.00034 | 0.411 | 0.00 |
SMSTORE5 | 22078.51 | 26494.21 | 152.10 | 1.088 | 1.306 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00648 | -27.60 | 0.00034 | 0.206 | 0.00 |
SMSTORE6 | 22057.01 | 26468.42 | 151.95 | 1.087 | 1.304 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00648 | -27.60 | 0.00034 | 0.206 | 0.00 |
SMSTORE7 | 22234.76 | 26681.71 | 153.17 | 1.096 | 1.315 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00649 | -27.60 | 0.00034 | 0.206 | 0.00 |
SMSTORE8 | 24547.75 | 29457.30 | 169.11 | 1.210 | 1.452 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00657 | -27.60 | 0.00034 | 0.206 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC_1:1 | 2.47 | 2.47 | 2.44 | 2.44 | 2.4667 | 2.4667 | 2.4667 | 1.0000 | 1.0000 |
PSZ-AC_2:2 | 1.35 | 1.35 | 1.26 | 1.26 | 1.3514 | 1.3514 | 1.3514 | 1.0000 | 1.0000 |
PSZ-AC_3:3 | 1.35 | 1.35 | 1.27 | 1.27 | 1.3505 | 1.3505 | 1.3505 | 1.0000 | 1.0000 |
PSZ-AC_4:4 | 1.35 | 1.35 | 1.28 | 1.28 | 1.3542 | 1.3542 | 1.3542 | 1.0000 | 1.0000 |
PSZ-AC_5:5 | 1.34 | 1.34 | 1.29 | 1.29 | 1.3445 | 1.3445 | 1.3445 | 1.0000 | 1.0000 |
PSZ-AC_6:6 | 2.36 | 2.36 | 2.38 | 2.38 | 2.3804 | 2.3804 | 2.3804 | 1.0000 | 1.0000 |
PSZ-AC_7:7 | 1.23 | 1.23 | 1.31 | 1.31 | 1.3055 | 1.3055 | 1.3055 | 1.0000 | 1.0000 |
PSZ-AC_8:8 | 1.22 | 1.22 | 1.30 | 1.30 | 1.3043 | 1.3043 | 1.3043 | 1.0000 | 1.0000 |
PSZ-AC_9:9 | 1.21 | 1.21 | 1.31 | 1.31 | 1.3148 | 1.3148 | 1.3148 | 1.0000 | 1.0000 |
PSZ-AC_10:10 | 1.23 | 1.23 | 1.45 | 1.45 | 1.4515 | 1.4515 | 1.4515 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_1:1 | 40831.860 | 0.000 | 2.466650 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 40831.86 | 40831.86 | 2.466650 | 25.48 | 14.22 | 0.00697052 | 12.80 | 10.89 | 0.00850000 | 33.40 | 0.00626594 | 16.30 | 16.6807 | 23.89 | 0.00711158 | 33.7784 | 24434.84 | 0.00 | -999.00 | -999.00 |
PSZ-AC_1:1_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_1:1 | 70533.794 | 70533.794 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 70533.79 | 70533.79 | 2.466653 | 12.90 | 7.86 | 0.00550065 | 40.00 | 19.60 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 16.6806 | 21.10 | 0.00654616 | 36.8710 | 41290.93 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_2:2 | 22370.890 | 0.000 | 1.351430 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 22370.89 | 22370.89 | 1.351430 | 25.34 | 14.16 | 0.00696422 | 12.80 | 10.89 | 0.00850000 | 33.40 | 0.00626594 | 16.30 | 15.2229 | 23.89 | 0.00708960 | 33.6750 | 13387.42 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_2:2 | 37629.290 | 37629.290 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 37629.29 | 37629.29 | 1.351425 | 13.18 | 7.93 | 0.00544956 | 40.00 | 19.60 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 15.2229 | 21.10 | 0.00644216 | 36.2931 | 21382.10 | 0.00 | -999.00 | -999.00 |
PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_3:3 | 22355.270 | 0.000 | 1.350480 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 22355.27 | 22355.27 | 1.350480 | 25.34 | 14.16 | 0.00696415 | 12.80 | 10.89 | 0.00850000 | 33.40 | 0.00626594 | 16.30 | 15.2336 | 23.89 | 0.00708962 | 33.6751 | 13378.07 | 0.00 | -999.00 | -999.00 |
PSZ-AC_3:3_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_3:3 | 37610.408 | 37610.408 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 37610.41 | 37610.41 | 1.350482 | 13.24 | 7.97 | 0.00546508 | 40.00 | 19.60 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 15.2336 | 21.10 | 0.00645147 | 36.3451 | 21549.44 | 0.00 | -999.00 | -999.00 |
PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_4:4 | 22416.840 | 0.000 | 1.354200 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 22416.84 | 22416.84 | 1.354200 | 25.33 | 14.16 | 0.00696432 | 12.80 | 10.89 | 0.00850000 | 33.40 | 0.00626594 | 16.30 | 15.1918 | 23.89 | 0.00708942 | 33.6741 | 13414.91 | 0.00 | -999.00 | -999.00 |
PSZ-AC_4:4_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_4:4 | 37684.789 | 37684.789 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 37684.79 | 37684.79 | 1.354201 | 13.26 | 7.99 | 0.00547028 | 40.00 | 19.60 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 15.1917 | 21.10 | 0.00645459 | 36.3625 | 21606.02 | 0.00 | -999.00 | -999.00 |
PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_5:5 | 22255.740 | 0.000 | 1.344470 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 22255.74 | 22255.74 | 1.344470 | 25.34 | 14.16 | 0.00696387 | 12.80 | 10.89 | 0.00850000 | 33.40 | 0.00626594 | 16.30 | 15.3017 | 23.89 | 0.00708996 | 33.6766 | 13318.51 | 0.00 | -999.00 | -999.00 |
PSZ-AC_5:5_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_5:5 | 37490.153 | 37490.153 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 37490.15 | 37490.15 | 1.344469 | 13.31 | 8.02 | 0.00548249 | 40.00 | 19.60 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 15.3017 | 21.10 | 0.00646190 | 36.4032 | 21739.94 | 0.00 | -999.00 | -999.00 |
PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_6:6 | 39404.200 | 0.000 | 2.380410 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 39404.20 | 39404.20 | 2.380410 | 25.55 | 14.24 | 0.00697040 | 12.80 | 10.89 | 0.00850000 | 33.40 | 0.00626594 | 16.30 | 17.2850 | 23.89 | 0.00711892 | 33.8129 | 23407.43 | 0.00 | -999.00 | -999.00 |
PSZ-AC_6:6_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_6:6 | 68808.708 | 68808.708 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 68808.71 | 68808.71 | 2.380408 | 12.69 | 7.73 | 0.00546335 | 40.00 | 19.60 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 17.2850 | 21.10 | 0.00653358 | 36.8006 | 40254.76 | 0.00 | -999.00 | -999.00 |
PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_7:7 | 21611.220 | 0.000 | 1.305530 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 21611.22 | 21611.22 | 1.305530 | 25.48 | 14.21 | 0.00695798 | 12.80 | 10.89 | 0.00850000 | 33.40 | 0.00626594 | 16.30 | 15.7581 | 23.89 | 0.00709684 | 33.7089 | 12194.82 | 0.00 | -999.00 | -999.00 |
PSZ-AC_7:7_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_7:7 | 36711.459 | 36711.459 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 36711.46 | 36711.46 | 1.305534 | 13.43 | 8.11 | 0.00551267 | 40.00 | 19.60 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 15.7581 | 21.10 | 0.00647990 | 36.5036 | 22078.51 | 0.00 | -999.00 | -999.00 |
PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_8:8 | 21590.180 | 0.000 | 1.304260 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 21590.18 | 21590.18 | 1.304260 | 25.49 | 14.21 | 0.00695747 | 12.80 | 10.89 | 0.00850000 | 33.40 | 0.00626594 | 16.30 | 15.7734 | 23.89 | 0.00709740 | 33.7116 | 12109.47 | 0.00 | -999.00 | -999.00 |
PSZ-AC_8:8_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_8:8 | 36686.042 | 36686.042 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 36686.04 | 36686.04 | 1.304263 | 13.42 | 8.10 | 0.00551076 | 40.00 | 19.60 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 15.7734 | 21.10 | 0.00647875 | 36.4971 | 22057.01 | 0.00 | -999.00 | -999.00 |
PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_9:9 | 21764.170 | 0.000 | 1.314770 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 21764.17 | 21764.17 | 1.314770 | 25.50 | 14.21 | 0.00695691 | 12.80 | 10.89 | 0.00850000 | 33.40 | 0.00626594 | 16.30 | 15.6474 | 23.89 | 0.00709802 | 33.7145 | 12017.36 | 0.00 | -999.00 | -999.00 |
PSZ-AC_9:9_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_9:9 | 36896.228 | 36896.228 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 36896.23 | 36896.23 | 1.314774 | 13.48 | 8.14 | 0.00552645 | 40.00 | 19.60 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 15.6473 | 21.10 | 0.00648817 | 36.5497 | 22234.76 | 0.00 | -999.00 | -999.00 |
PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_10:10 | 24027.890 | 0.000 | 1.451520 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 24027.89 | 24027.89 | 1.451520 | 25.49 | 14.20 | 0.00695261 | 12.80 | 10.89 | 0.00850000 | 33.40 | 0.00626594 | 16.30 | 14.1732 | 23.89 | 0.00709134 | 33.6831 | 12136.87 | 0.00 | -999.00 | -999.00 |
PSZ-AC_10:10_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_10:10 | 39631.335 | 39631.335 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 39631.34 | 39631.34 | 1.451525 | 14.20 | 8.63 | 0.00569133 | 40.00 | 19.60 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 14.1731 | 21.10 | 0.00657471 | 37.0327 | 24547.75 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2020-06-03 19:21:42
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | LGSTORE1 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 40831.860 | 0.000 | 2.466650 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.7979 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 40831.86 | 40831.86 | 1.0000 | 2.59772749 | 2.466650 | 25.48 | 14.22 | 0.00697052 | 43362.2 | 12.80 | 10.89 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 40831.86 | 33.40 | 0.00626594 | 16.30 | 0.41145340 | 16.6807 | 23.89 | 0.00711158 | 23.89 | 0.00711158 | 33.7784 | 24434.84 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_1:1_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | LGSTORE1 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 70533.794 | 70533.794 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.466653 | 2.59773050 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 70533.79 | 70533.79 | 1.0000 | 2.59773050 | 2.466653 | 12.90 | 7.86 | 0.00550065 | 26847.1 | 40.00 | 19.60 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 70533.79 | -27.60 | 0.00034190 | -27.60 | 0.41145340 | 16.6806 | 21.10 | 0.00654616 | 21.10 | 0.00654616 | 36.8710 | 41290.93 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | SMSTORE1 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 22370.890 | 0.000 | 1.351430 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.7861 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 22370.89 | 22370.89 | 1.0000 | 1.42324483 | 1.351430 | 25.34 | 14.16 | 0.00696422 | 43205.1 | 12.80 | 10.89 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 22370.89 | 33.40 | 0.00626594 | 16.30 | 0.20572670 | 15.2229 | 23.89 | 0.00708960 | 23.89 | 0.00708960 | 33.6750 | 13387.42 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | SMSTORE1 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 37629.290 | 37629.290 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.351425 | 1.42323991 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 37629.29 | 37629.29 | 1.0000 | 1.42323991 | 1.351425 | 13.18 | 7.93 | 0.00544956 | 27004.4 | 40.00 | 19.60 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 37629.29 | -27.60 | 0.00034190 | -27.60 | 0.20572670 | 15.2229 | 21.10 | 0.00644216 | 21.10 | 0.00644216 | 36.2931 | 21382.10 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_3:3 | SMSTORE2 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 22355.270 | 0.000 | 1.350480 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.7860 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 22355.27 | 22355.27 | 1.0000 | 1.42224435 | 1.350480 | 25.34 | 14.16 | 0.00696415 | 43205.9 | 12.80 | 10.89 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 22355.27 | 33.40 | 0.00626594 | 16.30 | 0.20572670 | 15.2336 | 23.89 | 0.00708962 | 23.89 | 0.00708962 | 33.6751 | 13378.07 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_3:3_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_3:3 | SMSTORE2 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 37610.408 | 37610.408 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.350482 | 1.42224610 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 37610.41 | 37610.41 | 1.0000 | 1.42224610 | 1.350482 | 13.24 | 7.97 | 0.00546508 | 27106.0 | 40.00 | 19.60 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 37610.41 | -27.60 | 0.00034190 | -27.60 | 0.20572670 | 15.2336 | 21.10 | 0.00645147 | 21.10 | 0.00645147 | 36.3451 | 21549.44 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_4:4 | SMSTORE3 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 22416.840 | 0.000 | 1.354200 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.7863 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 22416.84 | 22416.84 | 1.0000 | 1.42616203 | 1.354200 | 25.33 | 14.16 | 0.00696432 | 43202.3 | 12.80 | 10.89 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 22416.84 | 33.40 | 0.00626594 | 16.30 | 0.20572670 | 15.1918 | 23.89 | 0.00708942 | 23.89 | 0.00708942 | 33.6741 | 13414.91 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_4:4_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_4:4 | SMSTORE3 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 37684.789 | 37684.789 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.354201 | 1.42616331 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 37684.79 | 37684.79 | 1.0000 | 1.42616331 | 1.354201 | 13.26 | 7.99 | 0.00547028 | 27140.1 | 40.00 | 19.60 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 37684.79 | -27.60 | 0.00034190 | -27.60 | 0.20572670 | 15.1917 | 21.10 | 0.00645459 | 21.10 | 0.00645459 | 36.3625 | 21606.02 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_5:5 | SMSTORE4 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 22255.740 | 0.000 | 1.344470 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.7855 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 22255.74 | 22255.74 | 1.0000 | 1.41591497 | 1.344470 | 25.34 | 14.16 | 0.00696387 | 43211.8 | 12.80 | 10.89 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 22255.74 | 33.40 | 0.00626594 | 16.30 | 0.20572670 | 15.3017 | 23.89 | 0.00708996 | 23.89 | 0.00708996 | 33.6766 | 13318.51 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_5:5_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_5:5 | SMSTORE4 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 37490.153 | 37490.153 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.344469 | 1.41591409 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 37490.15 | 37490.15 | 1.0000 | 1.41591409 | 1.344469 | 13.31 | 8.02 | 0.00548249 | 27219.9 | 40.00 | 19.60 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 37490.15 | -27.60 | 0.00034190 | -27.60 | 0.20572670 | 15.3017 | 21.10 | 0.00646190 | 21.10 | 0.00646190 | 36.4032 | 21739.94 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_6:6 | LGSTORE2 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 39404.200 | 0.000 | 2.380410 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.7976 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 39404.20 | 39404.20 | 1.0000 | 2.50690470 | 2.380410 | 25.55 | 14.24 | 0.00697040 | 43432.7 | 12.80 | 10.89 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 39404.20 | 33.40 | 0.00626594 | 16.30 | 0.41145340 | 17.2850 | 23.89 | 0.00711892 | 23.89 | 0.00711892 | 33.8129 | 23407.43 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_6:6_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_6:6 | LGSTORE2 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 68808.708 | 68808.708 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.380408 | 2.50690234 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 68808.71 | 68808.71 | 1.0000 | 2.50690234 | 2.380408 | 12.69 | 7.73 | 0.00546335 | 26538.7 | 40.00 | 19.60 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 68808.71 | -27.60 | 0.00034190 | -27.60 | 0.41145340 | 17.2850 | 21.10 | 0.00653358 | 21.10 | 0.00653358 | 36.8006 | 40254.76 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_7:7 | SMSTORE5 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 21611.220 | 0.000 | 1.305530 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.7745 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 21611.22 | 21611.22 | 1.0000 | 1.37490571 | 1.305530 | 25.48 | 14.21 | 0.00695798 | 43333.3 | 12.80 | 10.89 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 21611.22 | 33.40 | 0.00626594 | 16.30 | 0.20572670 | 15.7581 | 23.89 | 0.00709684 | 23.89 | 0.00709684 | 33.7089 | 12194.82 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_7:7_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_7:7 | SMSTORE5 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 36711.459 | 36711.459 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.305534 | 1.37490967 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 36711.46 | 36711.46 | 1.0000 | 1.37490967 | 1.305534 | 13.43 | 8.11 | 0.00551267 | 27417.6 | 40.00 | 19.60 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 36711.46 | -27.60 | 0.00034190 | -27.60 | 0.20572670 | 15.7581 | 21.10 | 0.00647990 | 21.10 | 0.00647990 | 36.5036 | 22078.51 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_8:8 | SMSTORE6 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 21590.180 | 0.000 | 1.304260 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.7736 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 21590.18 | 21590.18 | 1.0000 | 1.37356822 | 1.304260 | 25.49 | 14.21 | 0.00695747 | 43343.4 | 12.80 | 10.89 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 21590.18 | 33.40 | 0.00626594 | 16.30 | 0.20572670 | 15.7734 | 23.89 | 0.00709740 | 23.89 | 0.00709740 | 33.7116 | 12109.47 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_8:8_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_8:8 | SMSTORE6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 36686.042 | 36686.042 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.304263 | 1.37357110 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 36686.04 | 36686.04 | 1.0000 | 1.37357110 | 1.304263 | 13.42 | 8.10 | 0.00551076 | 27405.1 | 40.00 | 19.60 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 36686.04 | -27.60 | 0.00034190 | -27.60 | 0.20572670 | 15.7734 | 21.10 | 0.00647875 | 21.10 | 0.00647875 | 36.4971 | 22057.01 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_9:9 | SMSTORE7 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 21764.170 | 0.000 | 1.314770 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.7726 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 21764.17 | 21764.17 | 1.0000 | 1.38463672 | 1.314770 | 25.50 | 14.21 | 0.00695691 | 43354.5 | 12.80 | 10.89 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 21764.17 | 33.40 | 0.00626594 | 16.30 | 0.20572670 | 15.6474 | 23.89 | 0.00709802 | 23.89 | 0.00709802 | 33.7145 | 12017.36 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_9:9_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_9:9 | SMSTORE7 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 36896.228 | 36896.228 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.314774 | 1.38464042 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 36896.23 | 36896.23 | 1.0000 | 1.38464042 | 1.314774 | 13.48 | 8.14 | 0.00552645 | 27507.1 | 40.00 | 19.60 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 36896.23 | -27.60 | 0.00034190 | -27.60 | 0.20572670 | 15.6473 | 21.10 | 0.00648817 | 21.10 | 0.00648817 | 36.5497 | 22234.76 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_10:10 | SMSTORE8 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 24027.890 | 0.000 | 1.451520 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.7645 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 24027.89 | 24027.89 | 1.0000 | 1.52865360 | 1.451520 | 25.49 | 14.20 | 0.00695261 | 43327.3 | 12.80 | 10.89 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 24027.89 | 33.40 | 0.00626594 | 16.30 | 0.20572670 | 14.1732 | 23.89 | 0.00709118 | 23.89 | 0.00709134 | 33.6831 | 12136.87 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_10:10_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_10:10 | SMSTORE8 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 39631.335 | 39631.335 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.451525 | 1.52865885 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 39631.34 | 39631.34 | 1.0000 | 1.52865885 | 1.451525 | 14.20 | 8.63 | 0.00569133 | 28652.4 | 40.00 | 19.60 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 39631.34 | -27.60 | 0.00034190 | -27.60 | 0.20572670 | 14.1731 | 21.10 | 0.00657471 | 21.10 | 0.00657471 | 37.0327 | 24547.75 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2020-06-03 19:21:42
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-AC_1:1_OA_CONTROLLER | DifferentialDryBulb | 0.41 | 2.47 | - | |||
PSZ-AC_2:2_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.35 | - | |||
PSZ-AC_3:3_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.35 | - | |||
PSZ-AC_4:4_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.35 | - | |||
PSZ-AC_5:5_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.34 | - | |||
PSZ-AC_6:6_OA_CONTROLLER | DifferentialDryBulb | 0.41 | 2.38 | - | |||
PSZ-AC_7:7_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.31 | - | |||
PSZ-AC_8:8_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.30 | - | |||
PSZ-AC_9:9_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.31 | - | |||
PSZ-AC_10:10_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.45 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
LGSTORE1 | 2303.67 | 3771.50 | 1250.50 |
SMSTORE1 | 1750.17 | 3571.83 | 722.17 |
SMSTORE2 | 1663.33 | 2737.00 | 765.17 |
SMSTORE3 | 1730.67 | 2772.50 | 837.83 |
SMSTORE4 | 1796.50 | 2833.67 | 942.17 |
LGSTORE2 | 1806.67 | 2737.83 | 1149.83 |
SMSTORE5 | 1753.00 | 2794.83 | 1186.67 |
SMSTORE6 | 1769.83 | 2823.83 | 1226.00 |
SMSTORE7 | 1850.83 | 2884.17 | 1347.17 |
SMSTORE8 | 2157.50 | 3014.00 | 1719.67 |
Facility | 3410.00 | 4347.50 | 2233.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
LGSTORE1 | 13.33 | 0.00 | 3.00 | 0.00 |
SMSTORE1 | 4.00 | 0.00 | 1.17 | 0.00 |
SMSTORE2 | 2.17 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 3.33 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 3.83 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 12.00 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 11.00 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 11.17 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 13.50 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 88.50 | 0.00 | 0.00 | 0.00 |
Facility | 107.83 | 0.00 | 3.00 | 0.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2020-06-03 19:21:42
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
LGSTORE1 | 9.03 | 30.00 | 1805.20 | 1.257 | 0.398 | 0.000 | 0.000 |
SMSTORE1 | 4.52 | 15.00 | 902.60 | 1.168 | 0.425 | 0.000 | 0.000 |
SMSTORE2 | 3.77 | 15.00 | 902.60 | 1.318 | 0.552 | 0.000 | 0.000 |
SMSTORE3 | 3.77 | 15.00 | 902.60 | 1.312 | 0.552 | 0.000 | 0.000 |
SMSTORE4 | 3.77 | 15.00 | 902.60 | 1.287 | 0.552 | 0.000 | 0.000 |
LGSTORE2 | 13.19 | 30.00 | 1805.20 | 1.198 | 0.517 | 0.000 | 0.000 |
SMSTORE5 | 6.60 | 15.00 | 902.60 | 1.233 | 0.587 | 0.000 | 0.000 |
SMSTORE6 | 6.60 | 15.00 | 902.60 | 1.224 | 0.587 | 0.000 | 0.000 |
SMSTORE7 | 6.60 | 15.00 | 902.60 | 1.207 | 0.587 | 0.000 | 0.000 |
SMSTORE8 | 6.60 | 15.00 | 902.60 | 1.198 | 0.635 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
LGSTORE1 | 9.03 | 30.00 | 1805.20 | 0.000 | 0.000 | 0.000 | 0.000 |
SMSTORE1 | 4.52 | 15.00 | 902.60 | 0.000 | 0.000 | 0.000 | 0.000 |
SMSTORE2 | 3.77 | 15.00 | 902.60 | 0.804 | 0.000 | 0.000 | 0.000 |
SMSTORE3 | 3.77 | 15.00 | 902.60 | 0.804 | 0.000 | 0.000 | 0.000 |
SMSTORE4 | 3.77 | 15.00 | 902.60 | 0.804 | 0.000 | 0.000 | 0.000 |
LGSTORE2 | 13.19 | 30.00 | 1805.20 | 0.806 | 0.000 | 0.000 | 0.000 |
SMSTORE5 | 6.60 | 15.00 | 902.60 | 0.806 | 0.000 | 0.000 | 0.000 |
SMSTORE6 | 6.60 | 15.00 | 902.60 | 0.806 | 0.000 | 0.000 | 0.000 |
SMSTORE7 | 6.60 | 15.00 | 902.60 | 0.806 | 0.000 | 0.000 | 0.000 |
SMSTORE8 | 6.60 | 15.00 | 902.60 | 0.805 | 0.000 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2020-06-03 19:21:42
Surfaces by ClassTotal | Outdoors | |
Wall | 40 | 22 |
Floor | 10 | 10 |
Roof | 10 | 10 |
Internal Mass | 10 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 36 | 36 |
Door | 12 | 12 |
Glass Door | 12 | 12 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 10 |
Conditioned Zones | 10 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 0 |
Defaulted Fields | 0 |
Fields with Defaults | 0 |
Autosized Fields | 0 |
Autosizable Fields | 0 |
Autocalculated Fields | 0 |
Autocalculatable Fields | 0 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2020-06-03 19:21:42
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1395.65 | 3973.34 | 05-FEB-08:00 | 135613.27 | 17-JUL-16:00 |
Electricity:Building | 832.89 | 2755.34 | 01-JAN-00:10 | 51902.14 | 01-JAN-11:10 |
Electricity:Zone:LGSTORE1 | 186.96 | 509.76 | 01-JAN-00:10 | 9610.45 | 01-JAN-10:10 |
InteriorLights:Electricity | 704.17 | 2305.93 | 01-JAN-00:10 | 43812.60 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:LGSTORE1 | 160.61 | 434.85 | 01-JAN-00:10 | 8262.19 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity | 704.17 | 2305.93 | 01-JAN-00:10 | 43812.60 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE1 | 102.73 | 279.91 | 01-JAN-00:10 | 5280.82 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE1 | 89.55 | 242.46 | 01-JAN-00:10 | 4606.69 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE2 | 75.94 | 261.16 | 01-JAN-00:10 | 4924.57 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE2 | 65.47 | 223.71 | 01-JAN-00:10 | 4250.44 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE3 | 75.94 | 261.16 | 01-JAN-00:10 | 4924.57 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE3 | 65.47 | 223.71 | 01-JAN-00:10 | 4250.44 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE4 | 75.94 | 261.16 | 01-JAN-00:10 | 4924.57 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE4 | 65.47 | 223.71 | 01-JAN-00:10 | 4250.44 | 01-JAN-10:10 |
Electricity:Zone:LGSTORE2 | 105.13 | 394.07 | 01-JAN-00:10 | 7412.39 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:LGSTORE2 | 85.86 | 319.16 | 01-JAN-00:10 | 6064.13 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE5 | 52.56 | 197.03 | 01-JAN-00:10 | 3706.19 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE5 | 42.93 | 159.58 | 01-JAN-00:10 | 3032.07 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE6 | 52.56 | 197.03 | 01-JAN-00:10 | 3706.19 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE6 | 42.93 | 159.58 | 01-JAN-00:10 | 3032.07 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE7 | 52.56 | 197.03 | 01-JAN-00:10 | 3706.19 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE7 | 42.93 | 159.58 | 01-JAN-00:10 | 3032.07 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE8 | 52.56 | 197.03 | 01-JAN-00:10 | 3706.19 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE8 | 42.93 | 159.58 | 01-JAN-00:10 | 3032.07 | 01-JAN-11:10 |
InteriorEquipment:Electricity | 128.72 | 449.42 | 01-JAN-00:10 | 8089.53 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:LGSTORE1 | 26.36 | 74.90 | 01-JAN-00:10 | 1348.26 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity | 128.72 | 449.42 | 01-JAN-00:10 | 8089.53 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE1 | 13.18 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE2 | 10.47 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE3 | 10.47 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE4 | 10.47 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:LGSTORE2 | 19.26 | 74.90 | 01-JAN-00:10 | 1348.26 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE5 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE6 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE7 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE8 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
Electricity:Plant | 66.02 | 1218.00 | 03-JAN-07:10 | 14011.43 | 07-JAN-14:10 |
WaterSystems:Electricity | 66.02 | 1218.00 | 03-JAN-07:10 | 14011.43 | 07-JAN-14:10 |
Water Heater:WaterSystems:Electricity | 66.02 | 1218.00 | 03-JAN-07:10 | 14011.43 | 07-JAN-14:10 |
ElectricityPurchased:Facility | 1395.65 | 3973.34 | 05-FEB-08:00 | 135613.27 | 17-JUL-16:00 |
ElectricityPurchased:Plant | 1395.65 | 3973.34 | 05-FEB-08:00 | 135613.27 | 17-JUL-16:00 |
Cogeneration:ElectricityPurchased | 1395.65 | 3973.34 | 05-FEB-08:00 | 135613.27 | 17-JUL-16:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1395.65 | 3973.34 | 05-FEB-08:00 | 135613.27 | 17-JUL-16:00 |
ElectricityNet:Plant | 1395.65 | 3973.34 | 05-FEB-08:00 | 135613.27 | 17-JUL-16:00 |
Cogeneration:ElectricityNet | 1395.65 | 3973.34 | 05-FEB-08:00 | 135613.27 | 17-JUL-16:00 |
Electricity:HVAC | 386.17 | 0.00 | 01-JAN-00:10 | 78265.42 | 17-JUL-16:00 |
Fans:Electricity | 301.53 | 0.00 | 01-JAN-00:10 | 17525.53 | 12-JAN-14:50 |
General:Fans:Electricity | 301.53 | 0.00 | 01-JAN-00:10 | 17525.53 | 12-JAN-14:50 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 84.64 | 0.00 | 01-JAN-00:10 | 60739.89 | 17-JUL-16:00 |
ExteriorLights:Electricity | 110.57 | 0.00 | 01-JAN-08:20 | 7048.38 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 110.57 | 0.00 | 01-JAN-08:20 | 7048.38 | 01-JAN-00:10 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Gas:Facility | 668.73 | 0.00 | 01-JAN-00:10 | 385434.51 | 08-JAN-18:00 |
Gas:HVAC | 668.73 | 0.00 | 01-JAN-00:10 | 385434.51 | 08-JAN-18:00 |
Heating:Gas | 668.73 | 0.00 | 01-JAN-00:10 | 385434.51 | 08-JAN-18:00 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water:Plant | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
WaterSystems:Water | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water Heater:WaterSystems:Water | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
MainsWater:Facility | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
MainsWater:Plant | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
WaterSystems:MainsWater | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water Heater:WaterSystems:MainsWater | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:Facility | 1445.76 | 0.00 | 01-JAN-00:10 | 507967.08 | 08-JAN-18:00 |
EnergyTransfer:Building | 635.78 | 0.00 | 01-JAN-00:10 | 204186.12 | 09-JAN-08:10 |
EnergyTransfer:Zone:LGSTORE1 | 122.93 | 0.00 | 01-JAN-00:10 | 38519.48 | 28-JAN-08:10 |
Heating:EnergyTransfer | 287.63 | 0.00 | 01-JAN-00:10 | 204186.12 | 09-JAN-08:10 |
Heating:EnergyTransfer:Zone:LGSTORE1 | 40.49 | 0.00 | 01-JAN-00:10 | 38519.48 | 28-JAN-08:10 |
Cooling:EnergyTransfer | 348.15 | 0.00 | 01-JAN-00:10 | 122930.69 | 17-JUL-16:10 |
Cooling:EnergyTransfer:Zone:LGSTORE1 | 82.43 | 0.00 | 01-JAN-00:10 | 20169.71 | 17-JUL-16:10 |
EnergyTransfer:Zone:SMSTORE1 | 62.97 | 0.00 | 01-JAN-00:10 | 18478.79 | 29-JAN-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE1 | 15.53 | 0.00 | 01-JAN-00:10 | 18478.79 | 29-JAN-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE1 | 47.43 | 0.00 | 01-JAN-00:10 | 13107.17 | 27-JUL-20:20 |
EnergyTransfer:Zone:SMSTORE2 | 51.07 | 0.00 | 01-JAN-00:10 | 18539.77 | 08-JAN-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE2 | 18.47 | 0.00 | 01-JAN-00:10 | 18539.77 | 08-JAN-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE2 | 32.60 | 0.00 | 01-JAN-00:10 | 10898.13 | 17-JUL-16:10 |
EnergyTransfer:Zone:SMSTORE3 | 51.46 | 0.00 | 01-JAN-00:10 | 19569.16 | 29-JAN-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE3 | 19.74 | 0.00 | 01-JAN-00:10 | 19569.16 | 29-JAN-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE3 | 31.72 | 0.00 | 01-JAN-00:10 | 10957.72 | 17-JUL-16:10 |
EnergyTransfer:Zone:SMSTORE4 | 51.22 | 0.00 | 01-JAN-00:10 | 19707.87 | 29-JAN-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE4 | 21.60 | 0.00 | 01-JAN-00:10 | 19707.87 | 29-JAN-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE4 | 29.62 | 0.00 | 01-JAN-00:10 | 10854.82 | 17-JUL-16:10 |
EnergyTransfer:Zone:LGSTORE2 | 89.98 | 0.00 | 01-JAN-00:10 | 37364.51 | 09-JAN-08:10 |
Heating:EnergyTransfer:Zone:LGSTORE2 | 45.22 | 0.00 | 01-JAN-00:10 | 37364.51 | 09-JAN-08:10 |
Cooling:EnergyTransfer:Zone:LGSTORE2 | 44.76 | 0.00 | 01-JAN-00:10 | 19060.04 | 17-JUL-16:10 |
EnergyTransfer:Zone:SMSTORE5 | 48.06 | 0.00 | 01-JAN-00:10 | 20186.94 | 09-JAN-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE5 | 26.19 | 0.00 | 01-JAN-00:10 | 20186.94 | 09-JAN-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE5 | 21.86 | 0.00 | 01-JAN-00:10 | 10084.65 | 17-JUL-16:10 |
EnergyTransfer:Zone:SMSTORE6 | 47.97 | 0.00 | 01-JAN-00:10 | 20212.00 | 09-JAN-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE6 | 26.78 | 0.00 | 01-JAN-00:10 | 20212.00 | 09-JAN-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE6 | 21.19 | 0.00 | 01-JAN-00:10 | 10012.40 | 17-JUL-16:10 |
EnergyTransfer:Zone:SMSTORE7 | 48.83 | 0.00 | 01-JAN-00:10 | 20281.04 | 09-JAN-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE7 | 29.20 | 0.00 | 01-JAN-00:10 | 20281.04 | 09-JAN-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE7 | 19.63 | 0.00 | 01-JAN-00:10 | 9920.43 | 17-JUL-16:10 |
EnergyTransfer:Zone:SMSTORE8 | 61.29 | 0.00 | 01-JAN-00:10 | 23432.64 | 27-JAN-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE8 | 44.39 | 0.00 | 01-JAN-00:10 | 23432.64 | 27-JAN-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE8 | 16.90 | 0.00 | 01-JAN-00:10 | 10157.84 | 17-JUL-16:10 |
EnergyTransfer:HVAC | 809.98 | 0.00 | 01-JAN-00:10 | 308347.61 | 08-JAN-18:00 |
HeatingCoils:EnergyTransfer | 534.99 | 0.00 | 01-JAN-00:10 | 308347.61 | 08-JAN-18:00 |
CoolingCoils:EnergyTransfer | 275.00 | 0.00 | 01-JAN-00:10 | 175108.14 | 17-JUL-16:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2020-06-03 19:21:42
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
LGSTORE1 | 0.000 | 0.000 | 40.495 | -82.431 | 0.000 | 0.000 | 13.469 | 160.608 | 26.357 | 22.214 | 0.000 | 2.819 | 0.003 | 0.000 | -16.020 | 0.000 | -73.781 | -93.730 |
SMSTORE1 | 0.000 | 0.000 | 15.534 | -47.434 | 0.000 | 0.000 | 6.634 | 89.549 | 13.179 | 10.993 | 0.000 | 1.551 | 0.002 | 0.000 | -8.372 | 0.000 | -35.805 | -45.828 |
SMSTORE2 | 0.000 | 0.000 | 18.472 | -32.596 | 0.000 | 0.000 | 4.040 | 65.475 | 10.467 | 10.985 | 0.000 | 1.513 | 0.001 | 0.000 | -8.211 | 0.000 | -36.917 | -33.228 |
SMSTORE3 | 0.000 | 0.000 | 19.740 | -31.721 | 0.000 | 0.000 | 4.047 | 65.475 | 10.467 | 11.004 | 0.000 | 1.513 | 0.001 | 0.000 | -8.124 | 0.000 | -36.759 | -35.641 |
SMSTORE4 | 0.000 | 0.000 | 21.596 | -29.620 | 0.000 | 0.000 | 4.057 | 65.475 | 10.467 | 11.034 | 0.000 | 1.514 | 0.001 | 0.000 | -8.033 | 0.000 | -36.569 | -39.921 |
LGSTORE2 | 0.000 | 0.000 | 45.222 | -44.761 | 0.000 | 0.000 | 13.997 | 85.864 | 19.261 | 22.261 | 0.000 | 2.669 | 0.006 | 0.000 | -15.495 | 0.000 | -66.008 | -63.010 |
SMSTORE5 | 0.000 | 0.000 | 26.194 | -21.864 | 0.000 | 0.000 | 7.002 | 42.932 | 9.631 | 11.119 | 0.000 | 1.517 | 0.001 | 0.000 | -7.759 | 0.000 | -36.466 | -32.306 |
SMSTORE6 | 0.000 | 0.000 | 26.781 | -21.191 | 0.000 | 0.000 | 7.007 | 42.932 | 9.631 | 11.132 | 0.000 | 1.518 | 0.003 | 0.000 | -7.726 | 0.000 | -36.400 | -33.683 |
SMSTORE7 | 0.000 | 0.000 | 29.205 | -19.627 | 0.000 | 0.000 | 7.020 | 42.932 | 9.631 | 11.165 | 0.000 | 1.518 | 0.003 | 0.000 | -7.619 | 0.000 | -36.200 | -38.024 |
SMSTORE8 | 0.000 | 0.000 | 44.390 | -16.902 | 0.000 | 0.000 | 7.049 | 42.932 | 9.631 | 11.269 | 0.000 | 1.608 | 0.001 | 0.000 | -7.190 | 0.000 | -47.164 | -45.623 |
Total Facility | 0.000 | 0.000 | 287.628 | -348.148 | 0.000 | 0.000 | 74.322 | 704.173 | 128.721 | 133.175 | 0.000 | 17.741 | 0.019 | 0.000 | -94.550 | 0.000 | -442.069 | -460.993 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
LGSTORE1 | 04-SEP-07:02 | 0.00 | 0.00 | 0.00 | -41784.64 | 0.00 | 0.00 | 94.35 | 434.85 | 74.90 | 74.97 | 0.00 | 0.00 | 41420.80 | 0.00 | -0.00 | 0.00 | -315.24 | 0.00 |
SMSTORE1 | 14-AUG-20:24 | 0.00 | 0.00 | 0.00 | -25721.73 | 0.00 | 0.00 | 342.88 | 4606.69 | 674.13 | 0.00 | 0.00 | 0.00 | 20359.33 | 0.00 | -210.49 | 0.00 | -50.81 | 0.00 |
SMSTORE2 | 12-AUG-06:02 | 0.00 | 0.00 | 0.00 | -26310.89 | 0.00 | 0.00 | 0.00 | 223.71 | 37.45 | 0.00 | 0.00 | 0.00 | 26283.31 | 0.00 | -197.64 | 0.00 | -35.93 | 0.00 |
SMSTORE3 | 12-AUG-06:02 | 0.00 | 0.00 | 0.00 | -27159.09 | 0.00 | 0.00 | 0.00 | 223.71 | 37.45 | 0.00 | 0.00 | 0.00 | 27132.71 | 0.00 | -198.83 | 0.00 | -35.95 | 0.00 |
SMSTORE4 | 27-JUL-06:01 | 0.00 | 0.00 | 0.00 | -25805.88 | 0.00 | 0.00 | 0.00 | 223.71 | 37.45 | 0.00 | 0.00 | 0.00 | 25777.26 | 0.00 | -180.02 | 0.00 | -52.52 | 0.00 |
LGSTORE2 | 05-SEP-07:02 | 0.00 | 0.00 | 0.00 | -41013.81 | 0.00 | 0.00 | 0.00 | 319.16 | 74.90 | 0.00 | 0.00 | 0.00 | 41131.70 | 0.00 | -95.64 | 0.00 | -416.31 | 0.00 |
SMSTORE5 | 05-SEP-07:02 | 0.00 | 0.00 | 0.00 | -22282.06 | 0.00 | 0.00 | 0.00 | 159.58 | 37.45 | 0.00 | 0.00 | 0.00 | 22359.94 | 0.00 | -47.15 | 0.00 | -227.77 | 0.00 |
SMSTORE6 | 05-SEP-07:02 | 0.00 | 0.00 | 0.00 | -22206.81 | 0.00 | 0.00 | 0.00 | 159.58 | 37.45 | 0.00 | 0.00 | 0.00 | 22281.75 | 0.00 | -46.00 | 0.00 | -225.98 | 0.00 |
SMSTORE7 | 05-SEP-07:02 | 0.00 | 0.00 | 0.00 | -22220.54 | 0.00 | 0.00 | 0.00 | 159.58 | 37.45 | 0.00 | 0.00 | 0.00 | 22287.48 | 0.00 | -43.38 | 0.00 | -220.59 | 0.00 |
SMSTORE8 | 05-SEP-07:02 | 0.00 | 0.00 | 0.00 | -22370.68 | 0.00 | 0.00 | 0.00 | 159.58 | 37.45 | 0.00 | 0.00 | 0.00 | 22446.79 | 0.00 | -33.29 | 0.00 | -239.85 | 0.00 |
Total Facility | 05-SEP-07:02 | 0.00 | 0.00 | 0.00 | -203807.21 | 0.00 | 0.00 | 298.01 | 8346.03 | 1460.61 | 0.00 | 0.00 | 0.00 | 196682.94 | 0.00 | -436.48 | 0.00 | -2543.89 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
LGSTORE1 | 09-JAN-00:42 | 0.00 | 0.00 | 70695.76 | 0.00 | 0.00 | 0.00 | 0.00 | 434.85 | 74.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1989.42 | 0.00 | -4000.61 | -65215.48 |
SMSTORE1 | 08-JAN-08:61 | 0.00 | 0.00 | 37529.47 | 0.00 | 0.00 | 0.00 | 75.56 | 242.46 | 37.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -902.60 | 0.00 | -1798.59 | -35183.75 |
SMSTORE2 | 29-JAN-08:61 | 0.00 | 0.00 | 37573.91 | 0.00 | 0.00 | 0.00 | 0.00 | 223.71 | 37.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -966.48 | 0.00 | -2069.61 | -34798.98 |
SMSTORE3 | 31-DEC-08:61 | 0.00 | 0.00 | 37651.47 | 0.00 | 0.00 | 0.00 | 0.00 | 223.71 | 37.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -965.56 | 0.00 | -2090.00 | -34857.07 |
SMSTORE4 | 08-JAN-08:61 | 0.00 | 0.00 | 37444.00 | 0.00 | 0.00 | 0.00 | 0.00 | 223.71 | 37.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -884.79 | 0.00 | -1787.50 | -35032.87 |
LGSTORE2 | 31-DEC-09:01 | 0.00 | 0.00 | 69000.29 | 0.00 | 0.00 | 0.00 | 0.00 | 319.16 | 74.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -960.95 | 0.00 | -3513.72 | -64919.69 |
SMSTORE5 | 08-JAN-09:01 | 0.00 | 0.00 | 36791.72 | 0.00 | 0.00 | 0.00 | 0.00 | 159.58 | 37.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -620.75 | 0.00 | -1818.74 | -34549.26 |
SMSTORE6 | 08-JAN-09:01 | 0.00 | 0.00 | 36769.64 | 0.00 | 0.00 | 0.00 | 0.00 | 159.58 | 37.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -620.46 | 0.00 | -1818.64 | -34527.57 |
SMSTORE7 | 31-DEC-09:01 | 0.00 | 0.00 | 36995.84 | 0.00 | 0.00 | 0.00 | 0.00 | 159.58 | 37.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -483.63 | 0.00 | -1974.78 | -34734.46 |
SMSTORE8 | 27-JAN-08:12 | 0.00 | 0.00 | 39873.19 | 0.00 | 0.00 | 0.00 | 0.00 | 159.58 | 37.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -574.02 | 0.00 | -2771.94 | -36724.26 |
Total Facility | 09-JAN-08:61 | 0.00 | 0.00 | 358295.50 | 0.00 | 0.00 | 0.00 | 413.75 | 8346.03 | 1460.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -11118.37 | 0.00 | -22045.75 | -335351.76 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2020-06-03 19:21:42
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 2.4667 | 0.0000 | 29.9961 | 1.0000 | 0.4115 | 2.4667 | 0.1668 | 1.0000 | 0.4115 | 0.1668 | ||
PSZ-AC_2:2 | 1.3514 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.3514 | 0.1522 | 1.0000 | 0.2057 | 0.1522 | ||
PSZ-AC_3:3 | 1.3505 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.3505 | 0.1523 | 1.0000 | 0.2057 | 0.1523 | ||
PSZ-AC_4:4 | 1.3542 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.3542 | 0.1519 | 1.0000 | 0.2057 | 0.1519 | ||
PSZ-AC_5:5 | 1.3445 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.3445 | 0.1530 | 1.0000 | 0.2057 | 0.1530 | ||
PSZ-AC_6:6 | 2.3804 | 0.0000 | 29.9961 | 1.0000 | 0.4115 | 2.3804 | 0.1741 | 1.0000 | 0.4115 | 0.1728 | ||
PSZ-AC_7:7 | 1.3055 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.3055 | 0.1671 | 1.0000 | 0.2057 | 0.1576 | ||
PSZ-AC_8:8 | 1.3043 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.3043 | 0.1683 | 1.0000 | 0.2057 | 0.1577 | ||
PSZ-AC_9:9 | 1.3148 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.3148 | 0.1696 | 1.0000 | 0.2057 | 0.1565 | ||
PSZ-AC_10:10 | 1.4515 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.4515 | 0.1678 | 1.0000 | 0.2057 | 0.1417 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 2.4667 | 0.0000 | 29.9961 | 1.0000 | 0.4115 | 2.4667 | 1.0000 | 1.0000 | 0.4115 | 0.1668 | ||
PSZ-AC_2:2 | 1.3514 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.3514 | 1.0000 | 1.0000 | 0.2057 | 0.1522 | ||
PSZ-AC_3:3 | 1.3505 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.3505 | 1.0000 | 1.0000 | 0.2057 | 0.1523 | ||
PSZ-AC_4:4 | 1.3542 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.3542 | 1.0000 | 1.0000 | 0.2057 | 0.1519 | ||
PSZ-AC_5:5 | 1.3445 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.3445 | 1.0000 | 1.0000 | 0.2057 | 0.1530 | ||
PSZ-AC_6:6 | 2.3804 | 0.0000 | 29.9961 | 1.0000 | 0.4115 | 2.3804 | 1.0000 | 1.0000 | 0.4115 | 0.1728 | ||
PSZ-AC_7:7 | 1.3055 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.3055 | 1.0000 | 1.0000 | 0.2057 | 0.1576 | ||
PSZ-AC_8:8 | 1.3043 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.3043 | 1.0000 | 1.0000 | 0.2057 | 0.1577 | ||
PSZ-AC_9:9 | 1.3148 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.3148 | 1.0000 | 1.0000 | 0.2057 | 0.1565 | ||
PSZ-AC_10:10 | 1.4515 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.4515 | 1.0000 | 1.0000 | 0.2057 | 0.1417 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
LGSTORE1 | PSZ-AC_1:1 | 0.000000 | 29.9961 | 0.001181 | 348.39 | 0.4115 | 1.0000 | 0.4115 | 1.000 | 0.4115 |
SMSTORE1 | PSZ-AC_2:2 | 0.000000 | 14.9980 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE2 | PSZ-AC_3:3 | 0.000000 | 14.9980 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE3 | PSZ-AC_4:4 | 0.000000 | 14.9980 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE4 | PSZ-AC_5:5 | 0.000000 | 14.9980 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
LGSTORE2 | PSZ-AC_6:6 | 0.000000 | 29.9961 | 0.001181 | 348.39 | 0.4115 | 1.0000 | 0.4115 | 1.000 | 0.4115 |
SMSTORE5 | PSZ-AC_7:7 | 0.000000 | 14.9980 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE6 | PSZ-AC_8:8 | 0.000000 | 14.9980 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE7 | PSZ-AC_9:9 | 0.000000 | 14.9980 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE8 | PSZ-AC_10:10 | 0.000000 | 14.9980 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC_1:1 | 0.000000 | 30.00 | 0.001181 | 348.3864 | 0.4115 | 0.4115 | 0.4115 |
PSZ-AC_2:2 | 0.000000 | 15.00 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_3:3 | 0.000000 | 15.00 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_4:4 | 0.000000 | 15.00 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_5:5 | 0.000000 | 15.00 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_6:6 | 0.000000 | 30.00 | 0.001181 | 348.3864 | 0.4115 | 0.4115 | 0.4115 |
PSZ-AC_7:7 | 0.000000 | 15.00 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_8:8 | 0.000000 | 15.00 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_9:9 | 0.000000 | 15.00 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_10:10 | 0.000000 | 15.00 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LGSTORE1 | PSZ-AC_1:1 | 2.4667 | 2.4667 | 2.4667 | 0.4115 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE1 | PSZ-AC_2:2 | 1.3514 | 1.3514 | 1.3514 | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE2 | PSZ-AC_3:3 | 1.3505 | 1.3505 | 1.3505 | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE3 | PSZ-AC_4:4 | 1.3542 | 1.3542 | 1.3542 | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE4 | PSZ-AC_5:5 | 1.3445 | 1.3445 | 1.3445 | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
LGSTORE2 | PSZ-AC_6:6 | 2.3804 | 2.3804 | 2.3804 | 0.4115 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE5 | PSZ-AC_7:7 | 1.3055 | 1.3055 | 1.3055 | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE6 | PSZ-AC_8:8 | 1.3043 | 1.3043 | 1.3043 | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE7 | PSZ-AC_9:9 | 1.3148 | 1.3148 | 1.3148 | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE8 | PSZ-AC_10:10 | 1.4515 | 1.4515 | 1.4515 | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 2.4667 | 2.4667 | 2.4667 | 2.4667 | 0.4115 | 1.0000 |
PSZ-AC_2:2 | 1.3514 | 1.3514 | 1.3514 | 1.3514 | 0.2057 | 1.0000 |
PSZ-AC_3:3 | 1.3505 | 1.3505 | 1.3505 | 1.3505 | 0.2057 | 1.0000 |
PSZ-AC_4:4 | 1.3542 | 1.3542 | 1.3542 | 1.3542 | 0.2057 | 1.0000 |
PSZ-AC_5:5 | 1.3445 | 1.3445 | 1.3445 | 1.3445 | 0.2057 | 1.0000 |
PSZ-AC_6:6 | 2.3804 | 2.3804 | 2.3804 | 2.3804 | 0.4115 | 1.0000 |
PSZ-AC_7:7 | 1.3055 | 1.3055 | 1.3055 | 1.3055 | 0.2057 | 1.0000 |
PSZ-AC_8:8 | 1.3043 | 1.3043 | 1.3043 | 1.3043 | 0.2057 | 1.0000 |
PSZ-AC_9:9 | 1.3148 | 1.3148 | 1.3148 | 1.3148 | 0.2057 | 1.0000 |
PSZ-AC_10:10 | 1.4515 | 1.4515 | 1.4515 | 1.4515 | 0.2057 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LGSTORE1 | PSZ-AC_1:1 | 2.4667 | 2.4667 | 2.4667 | 0.4115 | 0.1685 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE1 | PSZ-AC_2:2 | 1.3514 | 1.3514 | 1.3514 | 0.2057 | 0.1627 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE2 | PSZ-AC_3:3 | 1.3505 | 1.3505 | 1.3505 | 0.2057 | 0.1614 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE3 | PSZ-AC_4:4 | 1.3542 | 1.3542 | 1.3542 | 0.2057 | 0.1610 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE4 | PSZ-AC_5:5 | 1.3445 | 1.3445 | 1.3445 | 0.2057 | 0.1600 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
LGSTORE2 | PSZ-AC_6:6 | 2.3804 | 2.3804 | 2.3804 | 0.4115 | 0.1728 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE5 | PSZ-AC_7:7 | 1.3055 | 1.3055 | 1.3055 | 0.2057 | 0.1576 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE6 | PSZ-AC_8:8 | 1.3043 | 1.3043 | 1.3043 | 0.2057 | 0.1577 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE7 | PSZ-AC_9:9 | 1.3148 | 1.3148 | 1.3148 | 0.2057 | 0.1565 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE8 | PSZ-AC_10:10 | 1.4515 | 1.4515 | 1.4515 | 0.2057 | 0.1417 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 2.4667 | 2.4667 | 2.4667 | 2.4667 | 0.4115 | 1.0000 |
PSZ-AC_2:2 | 1.3514 | 1.3514 | 1.3514 | 1.3514 | 0.2057 | 1.0000 |
PSZ-AC_3:3 | 1.3505 | 1.3505 | 1.3505 | 1.3505 | 0.2057 | 1.0000 |
PSZ-AC_4:4 | 1.3542 | 1.3542 | 1.3542 | 1.3542 | 0.2057 | 1.0000 |
PSZ-AC_5:5 | 1.3445 | 1.3445 | 1.3445 | 1.3445 | 0.2057 | 1.0000 |
PSZ-AC_6:6 | 2.3804 | 2.3804 | 2.3804 | 2.3804 | 0.4115 | 1.0000 |
PSZ-AC_7:7 | 1.3055 | 1.3055 | 1.3055 | 1.3055 | 0.2057 | 1.0000 |
PSZ-AC_8:8 | 1.3043 | 1.3043 | 1.3043 | 1.3043 | 0.2057 | 1.0000 |
PSZ-AC_9:9 | 1.3148 | 1.3148 | 1.3148 | 1.3148 | 0.2057 | 1.0000 |
PSZ-AC_10:10 | 1.4515 | 1.4515 | 1.4515 | 1.4515 | 0.2057 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2020-06-03 19:21:42
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Great Falls Intl Arpt MT USA TMY3 WMO#=727750 |
Total gross floor area [m2] | 2090.32 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
LGSTORE1 | 348.39 | 348.39 | 0.00 | 112.00 |
SMSTORE1 | 174.19 | 174.19 | 0.00 | 112.00 |
SMSTORE2 | 174.19 | 174.19 | 0.00 | 84.29 |
SMSTORE3 | 174.19 | 174.19 | 0.00 | 84.29 |
SMSTORE4 | 174.19 | 174.19 | 0.00 | 84.29 |
LGSTORE2 | 348.39 | 348.39 | 0.00 | 77.29 |
SMSTORE5 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE6 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE7 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE8 | 174.19 | 174.19 | 0.00 | 77.29 |
Totals | 2090.32 | 2090.32 | 0.00 |
Data | |
Number of hours heating loads not met | 3.00 |
Number of hours cooling loads not met | 0.00 |
Number of hours not met | 3.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Fuel Use [GJ] | Additional Fuel Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- Not Subdivided | 0.00 | 0.00 | 668.73 | 385434.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- Not Subdivided | 84.64 | 60739.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 704.17 | 43812.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 110.57 | 7048.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 128.72 | 8089.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 301.53 | 17525.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 66.02 | 14011.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 128.72 | 1395.65 |
Natural Gas | 0.00 | 668.73 |
Additional | 0.00 | 0.00 |
Total | 128.72 | 2064.38 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 336.87 |
Space Heating | 0.00 |
Space Cooling | 40.49 |
Fans (All) | 144.25 |
Service Water Heating | 31.58 |
Receptacle Equipment | 61.58 |
Miscellaneous (All) | 667.67 |
Subtotal | 667.67 |
Natural Gas [MJ/m2] | |
Space Heating | 319.92 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 319.92 |
Subtotal | 319.92 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 34.11 |
Space Heating | 32.39 |
Space Cooling | 4.10 |
Fans (All) | 14.61 |
Service Water Heating | 3.20 |
Receptacle Equipment | 6.24 |
Miscellaneous | 5.36 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
TYPE1_OCC_SCH | 1630. | 5840. |
TYPE2_OCC_SCH | 995. | 4429. |
TYPE3_OCC_SCH | 1709. | 4064. |
TYPE1_LIGHT_SCH | 5131. | 8760. |
TYPE2_LIGHT_SCH | 4096. | 8760. |
TYPE3_LIGHT_SCH | 3767. | 8760. |
TYPE1_EQUIP_SCH | 4888. | 8760. |
TYPE2_EQUIP_SCH | 3911. | 8760. |
TYPE3_EQUIP_SCH | 3600. | 8760. |
TYPE1_INFIL_SCH | 4302. | 8760. |
TYPE2_INFIL_SCH | 5164. | 8760. |
TYPE3_INFIL_SCH | 5438. | 8760. |
INFIL_DOOR_OPENING_SCH | 2505. | 4380. |
TYPE1_MINOA_MOTORIZEDDAMPER_SCH | 5579. | 5579. |
TYPE2_MINOA_MOTORIZEDDAMPER_SCH | 4429. | 4429. |
TYPE3_MINOA_MOTORIZEDDAMPER_SCH | 4064. | 4064. |
TYPE1_SWH_SCH | 2063. | 6048. |
TYPE2_SWH_SCH | 1831. | 4429. |
TYPE3_SWH_SCH | 1733. | 4064. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 7118. | 8760. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 5839. | 5839. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 7300. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
TYPE1_HTGSETP_SCH_NO_OPTIMUM | LGSTORE1 DUALSPSCHED | January | 21.11 | 365 | 21.11 | 365 |
TYPE1_CLGSETP_SCH_NO_OPTIMUM | LGSTORE1 DUALSPSCHED | July | 23.89 | 365 | 23.89 | 365 |
TYPE2_HTGSETP_SCH_NO_OPTIMUM | SMSTORE2 DUALSPSCHED | January | 21.11 | 365 | 15.56 | 365 |
TYPE2_CLGSETP_SCH_NO_OPTIMUM | SMSTORE2 DUALSPSCHED | July | 23.89 | 365 | 29.44 | 365 |
TYPE3_HTGSETP_SCH_NO_OPTIMUM | LGSTORE2 DUALSPSCHED | January | 21.11 | 365 | 15.56 | 365 |
TYPE3_CLGSETP_SCH_NO_OPTIMUM | LGSTORE2 DUALSPSCHED | July | 23.89 | 365 | 29.44 | 365 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Meter
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.206986E+12 |
February | 0.000 | 0.111848E+12 |
March | 0.000 | 0.838611E+11 |
April | 0.000 | 0.278453E+11 |
May | 0.000 | 0.180694E+11 |
June | 0.000 | 0.392106E+09 |
July | 0.000 | 0.000 |
August | 0.000 | 0.294517E+08 |
September | 0.000 | 0.252647E+10 |
October | 0.000 | 0.112186E+11 |
November | 0.000 | 0.604592E+11 |
December | 0.000 | 0.145497E+12 |
Annual Sum or Average | 0.668733E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.206986E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Meter
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.206986E+12 |
February | 0.000 | 0.111848E+12 |
March | 0.000 | 0.838611E+11 |
April | 0.000 | 0.278453E+11 |
May | 0.000 | 0.180694E+11 |
June | 0.000 | 0.392106E+09 |
July | 0.000 | 0.000 |
August | 0.000 | 0.294517E+08 |
September | 0.000 | 0.252647E+10 |
October | 0.000 | 0.112186E+11 |
November | 0.000 | 0.604592E+11 |
December | 0.000 | 0.145497E+12 |
Annual Sum or Average | 0.668733E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.206986E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2009
For: Meter
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.206986E+12 |
February | 0.000 | 0.111848E+12 |
March | 0.000 | 0.838611E+11 |
April | 0.000 | 0.278453E+11 |
May | 0.000 | 0.180694E+11 |
June | 0.000 | 0.392106E+09 |
July | 0.000 | 0.000 |
August | 0.000 | 0.294517E+08 |
September | 0.000 | 0.252647E+10 |
October | 0.000 | 0.112186E+11 |
November | 0.000 | 0.604592E+11 |
December | 0.000 | 0.145497E+12 |
Annual Sum or Average | 0.668733E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.206986E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Meter
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.206986E+12 |
February | 0.000 | 0.111848E+12 |
March | 0.000 | 0.838611E+11 |
April | 0.000 | 0.278453E+11 |
May | 0.000 | 0.180694E+11 |
June | 0.000 | 0.392106E+09 |
July | 0.000 | 0.000 |
August | 0.000 | 0.294517E+08 |
September | 0.000 | 0.252647E+10 |
October | 0.000 | 0.112186E+11 |
November | 0.000 | 0.604592E+11 |
December | 0.000 | 0.145497E+12 |
Annual Sum or Average | 0.668733E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.206986E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTRIPMALL
For: Meter
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.206986E+12 |
February | 0.000 | 0.111848E+12 |
March | 0.000 | 0.838611E+11 |
April | 0.000 | 0.278453E+11 |
May | 0.000 | 0.180694E+11 |
June | 0.000 | 0.392106E+09 |
July | 0.000 | 0.000 |
August | 0.000 | 0.294517E+08 |
September | 0.000 | 0.252647E+10 |
October | 0.000 | 0.112186E+11 |
November | 0.000 | 0.604592E+11 |
December | 0.000 | 0.145497E+12 |
Annual Sum or Average | 0.668733E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.206986E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.206986E+12 |
February | 0.000 | 0.111848E+12 |
March | 0.000 | 0.838611E+11 |
April | 0.000 | 0.278453E+11 |
May | 0.000 | 0.180694E+11 |
June | 0.000 | 0.392106E+09 |
July | 0.000 | 0.000 |
August | 0.000 | 0.294517E+08 |
September | 0.000 | 0.252647E+10 |
October | 0.000 | 0.112186E+11 |
November | 0.000 | 0.604592E+11 |
December | 0.000 | 0.145497E+12 |
Annual Sum or Average | 0.668733E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.206986E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.206986E+12 |
February | 0.000 | 0.111848E+12 |
March | 0.000 | 0.838611E+11 |
April | 0.000 | 0.278453E+11 |
May | 0.000 | 0.180694E+11 |
June | 0.000 | 0.392106E+09 |
July | 0.000 | 0.000 |
August | 0.000 | 0.294517E+08 |
September | 0.000 | 0.252647E+10 |
October | 0.000 | 0.112186E+11 |
November | 0.000 | 0.604592E+11 |
December | 0.000 | 0.145497E+12 |
Annual Sum or Average | 0.668733E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.206986E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 6B
For: Meter
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.206986E+12 |
February | 0.000 | 0.111848E+12 |
March | 0.000 | 0.838611E+11 |
April | 0.000 | 0.278453E+11 |
May | 0.000 | 0.180694E+11 |
June | 0.000 | 0.392106E+09 |
July | 0.000 | 0.000 |
August | 0.000 | 0.294517E+08 |
September | 0.000 | 0.252647E+10 |
October | 0.000 | 0.112186E+11 |
November | 0.000 | 0.604592E+11 |
December | 0.000 | 0.145497E+12 |
Annual Sum or Average | 0.668733E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.206986E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MT_GREATFALLS
For: Meter
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.206986E+12 |
February | 0.000 | 0.111848E+12 |
March | 0.000 | 0.838611E+11 |
April | 0.000 | 0.278453E+11 |
May | 0.000 | 0.180694E+11 |
June | 0.000 | 0.392106E+09 |
July | 0.000 | 0.000 |
August | 0.000 | 0.294517E+08 |
September | 0.000 | 0.252647E+10 |
October | 0.000 | 0.112186E+11 |
November | 0.000 | 0.604592E+11 |
December | 0.000 | 0.145497E+12 |
Annual Sum or Average | 0.668733E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.206986E+12 |
Report: ZoneCoolingSummaryMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.846975E+09 | 17946.63 | 28-JAN-00:01 | -29.2 | -29.5 | 0.568204E+09 | 680.12 | 13-JAN-13:39 | 6.50 | 2.60 |
February | 0.163964E+10 | 14530.09 | 04-FEB-00:01 | -21.0 | -21.3 | 0.526526E+09 | 894.89 | 26-FEB-17:10 | 14.85 | 5.61 |
March | 0.240622E+10 | 12902.12 | 04-MAR-00:02 | -17.2 | -17.7 | 0.570235E+09 | 738.79 | 26-MAR-17:00 | 8.90 | 1.04 |
April | 0.377661E+10 | 7916.12 | 28-APR-23:25 | -5.0 | -6.5 | 0.623535E+09 | 898.99 | 16-APR-17:19 | 19.80 | 8.87 |
May | 0.649404E+10 | 12949.78 | 20-MAY-16:10 | 29.82 | 15.08 | 0.683106E+09 | 899.01 | 13-MAY-12:09 | 23.40 | 10.96 |
June | 0.119646E+11 | 22125.22 | 22-JUN-07:03 | 19.37 | 14.44 | 0.716621E+09 | 899.05 | 04-JUN-12:09 | 23.12 | 14.05 |
July | 0.170277E+11 | 36167.25 | 26-JUL-07:02 | 23.68 | 12.68 | 0.753538E+09 | 899.06 | 16-JUL-12:50 | 29.13 | 18.05 |
August | 0.157939E+11 | 36936.59 | 07-AUG-07:02 | 22.77 | 12.36 | 0.740239E+09 | 899.02 | 20-AUG-17:10 | 23.22 | 14.10 |
September | 0.114748E+11 | 41784.11 | 04-SEP-07:02 | 20.02 | 12.32 | 0.708276E+09 | 899.07 | 10-SEP-12:39 | 19.23 | 13.23 |
October | 0.678917E+10 | 11641.86 | 18-OCT-14:00 | 25.00 | 11.37 | 0.690435E+09 | 898.99 | 29-OCT-17:19 | 10.20 | 4.47 |
November | 0.300301E+10 | 11497.10 | 26-NOV-21:03 | -14.1 | -15.1 | 0.590110E+09 | 898.99 | 05-NOV-17:19 | 12.73 | 5.65 |
December | 0.121440E+10 | 15516.72 | 29-DEC-00:11 | -23.9 | -24.2 | 0.571917E+09 | 680.12 | 09-DEC-13:09 | 3.95 | 0.92 |
Annual Sum or Average | 0.824311E+11 | 0.774274E+10 | ||||||||
Minimum of Months | 0.846975E+09 | 7916.12 | -29.2 | -29.5 | 0.526526E+09 | 680.12 | 3.95 | 0.92 | ||
Maximum of Months | 0.170277E+11 | 41784.11 | 29.82 | 15.08 | 0.753538E+09 | 899.07 | 29.13 | 18.05 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.322416E+09 | 2549.45 | 02-JAN-18:10 | 2.38 | -1.3 | 0.291283E+09 | 417.72 | 01-JAN-18:00 | 2.80 | -0.1 |
February | 0.714341E+09 | 3543.52 | 22-FEB-10:03 | -4.5 | -5.5 | 0.276037E+09 | 449.50 | 26-FEB-17:30 | 13.35 | 5.02 |
March | 0.110925E+10 | 3306.02 | 15-MAR-19:30 | -1.1 | -3.3 | 0.303550E+09 | 436.25 | 26-MAR-17:00 | 8.90 | 1.04 |
April | 0.212890E+10 | 23609.12 | 25-APR-20:01 | 12.12 | 5.44 | 0.329980E+09 | 449.50 | 16-APR-16:19 | 20.00 | 8.83 |
May | 0.397343E+10 | 24530.15 | 14-MAY-17:11 | 13.87 | 4.87 | 0.350714E+09 | 449.51 | 13-MAY-12:09 | 23.40 | 10.96 |
June | 0.733338E+10 | 25543.10 | 19-JUN-20:57 | 16.10 | 8.37 | 0.356937E+09 | 449.53 | 04-JUN-12:09 | 23.12 | 14.05 |
July | 0.992293E+10 | 25246.71 | 27-JUL-20:06 | 17.43 | 9.86 | 0.374385E+09 | 449.53 | 09-JUL-17:00 | 27.80 | 13.12 |
August | 0.922910E+10 | 25721.74 | 14-AUG-20:24 | 16.70 | 9.51 | 0.368621E+09 | 449.51 | 20-AUG-17:10 | 23.22 | 14.10 |
September | 0.676243E+10 | 24689.49 | 23-SEP-18:47 | 16.05 | 9.58 | 0.356344E+09 | 449.55 | 03-SEP-17:00 | 30.00 | 14.97 |
October | 0.387850E+10 | 24552.74 | 15-OCT-17:57 | 17.20 | 8.46 | 0.356537E+09 | 449.50 | 08-OCT-17:30 | 10.85 | 5.14 |
November | 0.151766E+10 | 23138.28 | 05-NOV-17:01 | 13.02 | 5.76 | 0.311713E+09 | 449.50 | 05-NOV-16:10 | 13.47 | 5.99 |
December | 0.542154E+09 | 4156.89 | 13-DEC-11:23 | -7.8 | -8.3 | 0.295366E+09 | 401.06 | 10-DEC-18:00 | 0.00 | -3.2 |
Annual Sum or Average | 0.474345E+11 | 0.397146E+10 | ||||||||
Minimum of Months | 0.322416E+09 | 2549.45 | -7.8 | -8.3 | 0.276037E+09 | 401.06 | 0.00 | -3.2 | ||
Maximum of Months | 0.992293E+10 | 25721.74 | 17.43 | 9.86 | 0.374385E+09 | 449.55 | 30.00 | 14.97 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.143678E+09 | 4509.52 | 19-JAN-18:33 | -8.9 | -10.1 | 0.169189E+09 | 343.62 | 14-JAN-13:20 | 10.20 | 4.86 |
February | 0.423714E+09 | 4057.93 | 28-FEB-08:61 | -4.5 | -4.7 | 0.158900E+09 | 422.72 | 25-FEB-13:00 | 15.00 | 5.03 |
March | 0.826723E+09 | 5834.52 | 03-MAR-20:03 | -15.7 | -16.3 | 0.178217E+09 | 366.48 | 18-MAR-12:00 | 11.70 | 3.92 |
April | 0.136537E+10 | 3956.75 | 25-APR-17:10 | 17.70 | 7.67 | 0.189644E+09 | 446.22 | 08-APR-12:30 | 12.80 | 6.12 |
May | 0.249016E+10 | 8753.59 | 20-MAY-06:02 | 14.13 | 10.25 | 0.207481E+09 | 449.50 | 13-MAY-12:09 | 23.40 | 10.96 |
June | 0.508919E+10 | 20386.47 | 22-JUN-06:02 | 16.57 | 13.82 | 0.220680E+09 | 449.52 | 24-JUN-12:09 | 27.07 | 16.02 |
July | 0.708782E+10 | 26026.18 | 27-JUL-06:01 | 13.40 | 10.16 | 0.224274E+09 | 449.53 | 01-JUL-12:00 | 26.70 | 16.71 |
August | 0.672677E+10 | 26310.39 | 12-AUG-06:02 | 14.87 | 7.98 | 0.229587E+09 | 449.49 | 12-AUG-12:00 | 30.00 | 14.95 |
September | 0.460990E+10 | 23728.60 | 03-SEP-07:02 | 18.27 | 10.73 | 0.212559E+09 | 449.50 | 23-SEP-12:09 | 21.28 | 11.86 |
October | 0.253213E+10 | 6362.17 | 18-OCT-14:00 | 25.00 | 11.37 | 0.206419E+09 | 449.49 | 28-OCT-12:09 | 18.12 | 9.55 |
November | 0.100441E+10 | 4027.51 | 10-NOV-08:61 | -4.6 | -5.5 | 0.176594E+09 | 449.50 | 04-NOV-12:09 | 16.20 | 7.85 |
December | 0.296543E+09 | 3890.67 | 26-DEC-18:23 | -6.4 | -7.9 | 0.169262E+09 | 340.06 | 02-DEC-13:09 | 9.40 | 4.43 |
Annual Sum or Average | 0.325964E+11 | 0.234281E+10 | ||||||||
Minimum of Months | 0.143678E+09 | 3890.67 | -15.7 | -16.3 | 0.158900E+09 | 340.06 | 9.40 | 3.92 | ||
Maximum of Months | 0.708782E+10 | 26310.39 | 25.00 | 13.82 | 0.229587E+09 | 449.53 | 30.00 | 16.71 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.104105E+09 | 2035.17 | 02-JAN-10:15 | 2.77 | -0.0 | 0.169167E+09 | 340.06 | 14-JAN-13:09 | 10.40 | 5.00 |
February | 0.354077E+09 | 3982.22 | 28-FEB-08:61 | -4.5 | -4.7 | 0.158263E+09 | 417.32 | 25-FEB-13:00 | 15.00 | 5.03 |
March | 0.721826E+09 | 4843.61 | 01-MAR-08:61 | -9.3 | -10.0 | 0.177404E+09 | 362.45 | 18-MAR-12:00 | 11.70 | 3.92 |
April | 0.122276E+10 | 3740.25 | 25-APR-17:10 | 17.70 | 7.67 | 0.188178E+09 | 442.49 | 08-APR-12:30 | 12.80 | 6.12 |
May | 0.236490E+10 | 8077.62 | 20-MAY-06:02 | 14.13 | 10.25 | 0.206656E+09 | 449.50 | 13-MAY-12:09 | 23.40 | 10.96 |
June | 0.505230E+10 | 20450.71 | 22-JUN-06:02 | 16.57 | 13.82 | 0.220633E+09 | 449.52 | 24-JUN-12:09 | 27.07 | 16.02 |
July | 0.711185E+10 | 26145.56 | 27-JUL-06:01 | 13.40 | 10.16 | 0.224272E+09 | 449.53 | 01-JUL-12:00 | 26.70 | 16.71 |
August | 0.673413E+10 | 27158.57 | 12-AUG-06:02 | 14.87 | 7.98 | 0.229570E+09 | 449.49 | 12-AUG-12:00 | 30.00 | 14.95 |
September | 0.455188E+10 | 24705.21 | 03-SEP-07:02 | 18.27 | 10.73 | 0.212291E+09 | 449.50 | 23-SEP-12:09 | 21.28 | 11.86 |
October | 0.238626E+10 | 6258.12 | 18-OCT-14:00 | 25.00 | 11.37 | 0.205450E+09 | 449.49 | 28-OCT-12:09 | 18.12 | 9.55 |
November | 0.883742E+09 | 3964.18 | 10-NOV-08:61 | -4.6 | -5.5 | 0.175204E+09 | 449.49 | 04-NOV-12:39 | 16.50 | 8.00 |
December | 0.233925E+09 | 2325.73 | 18-DEC-20:25 | 1.15 | -1.8 | 0.169172E+09 | 340.06 | 09-DEC-13:09 | 3.95 | 0.92 |
Annual Sum or Average | 0.317218E+11 | 0.233626E+10 | ||||||||
Minimum of Months | 0.104105E+09 | 2035.17 | -9.3 | -10.0 | 0.158263E+09 | 340.06 | 3.95 | 0.92 | ||
Maximum of Months | 0.711185E+10 | 27158.57 | 25.00 | 13.82 | 0.229570E+09 | 449.53 | 30.00 | 16.71 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 64949294.95 | 2236.78 | 20-JAN-20:15 | 1.70 | -2.7 | 0.169157E+09 | 340.06 | 14-JAN-13:09 | 10.40 | 5.00 |
February | 0.274907E+09 | 3912.49 | 28-FEB-08:61 | -4.5 | -4.7 | 0.157516E+09 | 408.96 | 25-FEB-13:00 | 15.00 | 5.03 |
March | 0.588497E+09 | 2794.13 | 24-MAR-08:53 | -0.6 | -2.5 | 0.176435E+09 | 356.75 | 18-MAR-12:00 | 11.70 | 3.92 |
April | 0.102430E+10 | 3428.64 | 27-APR-07:01 | -1.6 | -3.1 | 0.186031E+09 | 433.26 | 08-APR-12:30 | 12.80 | 6.12 |
May | 0.211937E+10 | 6860.95 | 20-MAY-16:00 | 30.00 | 15.19 | 0.205317E+09 | 449.50 | 13-MAY-12:09 | 23.40 | 10.96 |
June | 0.480518E+10 | 18375.01 | 22-JUN-06:02 | 16.57 | 13.82 | 0.220481E+09 | 449.52 | 24-JUN-12:09 | 27.07 | 16.02 |
July | 0.688511E+10 | 25806.07 | 27-JUL-06:01 | 13.40 | 10.16 | 0.224244E+09 | 449.53 | 01-JUL-12:00 | 26.70 | 16.71 |
August | 0.649551E+10 | 24729.06 | 12-AUG-06:02 | 14.87 | 7.98 | 0.229431E+09 | 449.49 | 12-AUG-12:00 | 30.00 | 14.95 |
September | 0.431642E+10 | 23517.30 | 04-SEP-07:02 | 20.02 | 12.32 | 0.211722E+09 | 449.50 | 23-SEP-12:09 | 21.28 | 11.86 |
October | 0.214613E+10 | 6026.92 | 18-OCT-14:00 | 25.00 | 11.37 | 0.203734E+09 | 449.49 | 28-OCT-12:09 | 18.12 | 9.55 |
November | 0.732143E+09 | 3917.21 | 11-NOV-10:13 | -6.5 | -7.6 | 0.173244E+09 | 449.49 | 04-NOV-12:00 | 16.70 | 8.09 |
December | 0.168240E+09 | 4518.56 | 12-DEC-20:53 | -8.9 | -9.3 | 0.169067E+09 | 340.06 | 09-DEC-13:09 | 3.95 | 0.92 |
Annual Sum or Average | 0.296208E+11 | 0.232638E+10 | ||||||||
Minimum of Months | 64949294.95 | 2236.78 | -8.9 | -9.3 | 0.157516E+09 | 340.06 | 3.95 | 0.92 | ||
Maximum of Months | 0.688511E+10 | 25806.07 | 30.00 | 15.19 | 0.229431E+09 | 449.53 | 30.00 | 16.71 |
Report: ZoneCoolingSummaryMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 14823046.07 | 2311.46 | 14-JAN-12:00 | 10.00 | 4.77 | 0.578273E+09 | 906.82 | 14-JAN-15:00 | 10.00 | 4.55 |
February | 0.276847E+09 | 7589.50 | 23-FEB-11:43 | -4.5 | -6.1 | 0.535338E+09 | 1067.58 | 25-FEB-15:00 | 15.00 | 5.18 |
March | 0.601472E+09 | 6094.21 | 31-MAR-19:13 | -0.6 | -1.8 | 0.598967E+09 | 954.92 | 18-MAR-14:00 | 12.20 | 4.15 |
April | 0.128080E+10 | 4200.21 | 07-APR-14:10 | 23.03 | 9.52 | 0.621646E+09 | 1123.09 | 22-APR-14:00 | 16.70 | 9.27 |
May | 0.291694E+10 | 11531.39 | 20-MAY-16:00 | 30.00 | 15.19 | 0.689502E+09 | 1198.64 | 27-MAY-14:00 | 23.30 | 12.28 |
June | 0.744912E+10 | 23494.95 | 22-JUN-07:03 | 19.37 | 14.44 | 0.754515E+09 | 1198.67 | 03-JUN-14:09 | 24.18 | 14.31 |
July | 0.111691E+11 | 38759.37 | 27-JUL-07:01 | 13.98 | 10.40 | 0.767048E+09 | 1198.75 | 01-JUL-14:09 | 26.32 | 16.65 |
August | 0.104905E+11 | 37146.46 | 07-AUG-07:02 | 22.77 | 12.36 | 0.784656E+09 | 1198.65 | 19-AUG-14:09 | 21.28 | 11.33 |
September | 0.664772E+10 | 41015.42 | 05-SEP-07:02 | 18.98 | 12.61 | 0.720756E+09 | 1198.66 | 09-SEP-14:09 | 27.70 | 13.65 |
October | 0.298210E+10 | 10045.73 | 18-OCT-14:30 | 25.00 | 11.48 | 0.679784E+09 | 1198.65 | 21-OCT-14:00 | 16.10 | 8.09 |
November | 0.861686E+09 | 4620.58 | 06-NOV-11:10 | 4.62 | 1.12 | 0.575429E+09 | 1198.66 | 04-NOV-14:00 | 16.70 | 7.95 |
December | 70235750.91 | 2913.39 | 19-DEC-20:15 | 7.23 | 4.67 | 0.579257E+09 | 906.82 | 09-DEC-15:09 | 8.27 | 3.16 |
Annual Sum or Average | 0.447614E+11 | 0.788517E+10 | ||||||||
Minimum of Months | 14823046.07 | 2311.46 | -4.5 | -6.1 | 0.535338E+09 | 906.82 | 8.27 | 3.16 | ||
Maximum of Months | 0.111691E+11 | 41015.42 | 30.00 | 15.19 | 0.784656E+09 | 1198.75 | 27.70 | 16.65 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 5984348.76 | 1926.18 | 02-JAN-19:35 | 3.70 | -0.6 | 0.289136E+09 | 453.41 | 14-JAN-15:09 | 10.50 | 5.05 |
February | 0.100147E+09 | 2077.38 | 27-FEB-20:20 | 4.43 | 1.14 | 0.267500E+09 | 531.15 | 25-FEB-15:00 | 15.00 | 5.18 |
March | 0.239300E+09 | 2857.35 | 31-MAR-17:33 | -0.6 | -1.8 | 0.299412E+09 | 474.17 | 18-MAR-14:00 | 12.20 | 4.15 |
April | 0.511877E+09 | 2038.90 | 25-APR-17:10 | 17.70 | 7.67 | 0.309897E+09 | 556.11 | 22-APR-14:00 | 16.70 | 9.27 |
May | 0.132119E+10 | 6011.76 | 20-MAY-16:00 | 30.00 | 15.19 | 0.344149E+09 | 599.32 | 27-MAY-14:00 | 23.30 | 12.28 |
June | 0.369460E+10 | 10442.34 | 22-JUN-07:03 | 19.37 | 14.44 | 0.377198E+09 | 599.34 | 03-JUN-14:09 | 24.18 | 14.31 |
July | 0.569772E+10 | 19516.09 | 17-JUL-07:02 | 23.17 | 14.92 | 0.383522E+09 | 599.34 | 15-JUL-14:09 | 32.20 | 18.27 |
August | 0.531564E+10 | 20139.86 | 07-AUG-07:02 | 22.77 | 12.36 | 0.392292E+09 | 599.32 | 19-AUG-14:09 | 21.28 | 11.33 |
September | 0.328511E+10 | 22282.97 | 05-SEP-07:02 | 18.98 | 12.61 | 0.360103E+09 | 599.33 | 09-SEP-14:09 | 27.70 | 13.65 |
October | 0.132720E+10 | 5174.03 | 18-OCT-14:40 | 25.00 | 11.51 | 0.339172E+09 | 599.32 | 21-OCT-14:00 | 16.10 | 8.09 |
November | 0.336861E+09 | 2960.05 | 25-NOV-11:23 | -1.2 | -2.4 | 0.287357E+09 | 599.33 | 04-NOV-14:00 | 16.70 | 7.95 |
December | 28354697.94 | 2093.33 | 08-DEC-11:35 | 2.77 | -0.8 | 0.289636E+09 | 453.41 | 09-DEC-15:09 | 8.27 | 3.16 |
Annual Sum or Average | 0.218640E+11 | 0.393937E+10 | ||||||||
Minimum of Months | 5984348.76 | 1926.18 | -1.2 | -2.4 | 0.267500E+09 | 453.41 | 8.27 | 3.16 | ||
Maximum of Months | 0.569772E+10 | 22282.97 | 30.00 | 15.19 | 0.392292E+09 | 599.34 | 32.20 | 18.27 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 4857888.03 | 1695.59 | 02-JAN-11:25 | 5.00 | 1.16 | 0.289135E+09 | 453.41 | 14-JAN-15:09 | 10.50 | 5.05 |
February | 91883572.33 | 2466.51 | 16-FEB-18:05 | 0.73 | -2.8 | 0.267213E+09 | 527.26 | 25-FEB-15:00 | 15.00 | 5.18 |
March | 0.214269E+09 | 2658.59 | 24-MAR-10:33 | 0.40 | -1.8 | 0.299211E+09 | 471.09 | 18-MAR-14:00 | 12.20 | 4.15 |
April | 0.465321E+09 | 2222.19 | 29-APR-10:45 | 2.02 | -2.5 | 0.308700E+09 | 552.24 | 22-APR-14:00 | 16.70 | 9.27 |
May | 0.124128E+10 | 5902.33 | 20-MAY-16:00 | 30.00 | 15.19 | 0.343236E+09 | 599.32 | 27-MAY-14:00 | 23.30 | 12.28 |
June | 0.358157E+10 | 9672.93 | 22-JUN-07:03 | 19.37 | 14.44 | 0.377013E+09 | 599.34 | 03-JUN-14:09 | 24.18 | 14.31 |
July | 0.559555E+10 | 19441.39 | 17-JUL-07:02 | 23.17 | 14.92 | 0.383501E+09 | 599.34 | 15-JUL-14:09 | 32.20 | 18.27 |
August | 0.521375E+10 | 20072.22 | 07-AUG-07:02 | 22.77 | 12.36 | 0.392201E+09 | 599.32 | 19-AUG-14:09 | 21.28 | 11.33 |
September | 0.319893E+10 | 22207.72 | 05-SEP-07:02 | 18.98 | 12.61 | 0.359629E+09 | 599.33 | 09-SEP-14:09 | 27.70 | 13.65 |
October | 0.125820E+10 | 5055.94 | 18-OCT-14:40 | 25.00 | 11.51 | 0.337853E+09 | 599.32 | 21-OCT-14:00 | 16.10 | 8.09 |
November | 0.301880E+09 | 2606.85 | 20-NOV-18:15 | -0.0 | -4.0 | 0.286698E+09 | 599.33 | 04-NOV-14:00 | 16.70 | 7.95 |
December | 23978698.64 | 2775.57 | 20-DEC-18:43 | -0.2 | -3.0 | 0.289634E+09 | 453.41 | 09-DEC-15:09 | 8.27 | 3.16 |
Annual Sum or Average | 0.211915E+11 | 0.393402E+10 | ||||||||
Minimum of Months | 4857888.03 | 1695.59 | -0.2 | -4.0 | 0.267213E+09 | 453.41 | 8.27 | 3.16 | ||
Maximum of Months | 0.559555E+10 | 22207.72 | 30.00 | 15.19 | 0.392201E+09 | 599.34 | 32.20 | 18.27 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 2345929.29 | 889.61 | 14-JAN-12:00 | 10.00 | 4.77 | 0.289135E+09 | 453.41 | 14-JAN-15:09 | 10.50 | 5.05 |
February | 64019002.09 | 1741.43 | 27-FEB-19:40 | 5.73 | 1.95 | 0.266521E+09 | 516.91 | 27-FEB-15:00 | 18.90 | 7.03 |
March | 0.140977E+09 | 2190.50 | 21-MAR-17:20 | 2.20 | 0.71 | 0.298812E+09 | 463.03 | 18-MAR-14:00 | 12.20 | 4.15 |
April | 0.342702E+09 | 2192.26 | 14-APR-10:45 | 2.12 | 0.87 | 0.305814E+09 | 542.41 | 22-APR-14:00 | 16.70 | 9.27 |
May | 0.104499E+10 | 5658.01 | 20-MAY-16:00 | 30.00 | 15.19 | 0.341025E+09 | 599.32 | 27-MAY-14:00 | 23.30 | 12.28 |
June | 0.330341E+10 | 7484.64 | 22-JUN-07:03 | 19.37 | 14.44 | 0.376296E+09 | 599.34 | 03-JUN-14:09 | 24.18 | 14.31 |
July | 0.538644E+10 | 19408.40 | 17-JUL-07:02 | 23.17 | 14.92 | 0.383428E+09 | 599.34 | 15-JUL-14:09 | 32.20 | 18.27 |
August | 0.500699E+10 | 20074.24 | 07-AUG-07:02 | 22.77 | 12.36 | 0.391942E+09 | 599.32 | 19-AUG-14:09 | 21.28 | 11.33 |
September | 0.300786E+10 | 22221.49 | 05-SEP-07:02 | 18.98 | 12.61 | 0.358370E+09 | 599.33 | 09-SEP-14:09 | 27.70 | 13.65 |
October | 0.108684E+10 | 4784.22 | 18-OCT-14:40 | 25.00 | 11.51 | 0.334749E+09 | 599.32 | 28-OCT-14:09 | 19.08 | 9.41 |
November | 0.229893E+09 | 2171.90 | 22-NOV-20:15 | 2.27 | -1.2 | 0.285215E+09 | 598.90 | 04-NOV-14:00 | 16.70 | 7.95 |
December | 10579006.69 | 1681.33 | 20-DEC-11:15 | 4.97 | 0.43 | 0.289629E+09 | 453.41 | 09-DEC-15:09 | 8.27 | 3.16 |
Annual Sum or Average | 0.196271E+11 | 0.392094E+10 | ||||||||
Minimum of Months | 2345929.29 | 889.61 | 2.12 | -1.2 | 0.266521E+09 | 453.41 | 8.27 | 3.16 | ||
Maximum of Months | 0.538644E+10 | 22221.49 | 30.00 | 15.19 | 0.391942E+09 | 599.34 | 32.20 | 18.27 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 51233.16 | 85.39 | 14-JAN-12:00 | 10.00 | 4.77 | 0.289136E+09 | 453.41 | 14-JAN-15:09 | 10.50 | 5.05 |
February | 10903942.82 | 1783.39 | 27-FEB-20:35 | 3.87 | 0.78 | 0.265171E+09 | 495.81 | 27-FEB-15:00 | 18.90 | 7.03 |
March | 11085442.64 | 722.43 | 28-MAR-17:10 | 10.32 | 2.83 | 0.298275E+09 | 453.41 | 18-MAR-14:00 | 12.20 | 4.15 |
April | 92998385.22 | 1123.62 | 26-APR-18:20 | 8.53 | 4.05 | 0.300186E+09 | 531.90 | 06-APR-16:10 | 22.02 | 10.90 |
May | 0.662178E+09 | 5244.54 | 20-MAY-16:00 | 30.00 | 15.19 | 0.335923E+09 | 599.32 | 27-MAY-14:00 | 23.30 | 12.28 |
June | 0.280280E+10 | 7248.23 | 23-JUN-14:00 | 31.70 | 15.22 | 0.373390E+09 | 599.34 | 03-JUN-14:09 | 24.18 | 14.31 |
July | 0.517293E+10 | 20714.07 | 17-JUL-07:02 | 23.17 | 14.92 | 0.383072E+09 | 599.35 | 15-JUL-14:09 | 32.20 | 18.27 |
August | 0.473061E+10 | 15723.02 | 07-AUG-07:02 | 22.77 | 12.36 | 0.391276E+09 | 599.32 | 19-AUG-14:09 | 21.28 | 11.33 |
September | 0.264772E+10 | 22372.29 | 05-SEP-07:02 | 18.98 | 12.61 | 0.355186E+09 | 599.33 | 09-SEP-14:09 | 27.70 | 13.65 |
October | 0.697001E+09 | 4372.84 | 18-OCT-14:40 | 25.00 | 11.51 | 0.328289E+09 | 599.33 | 28-OCT-14:09 | 19.08 | 9.41 |
November | 74483787.00 | 2166.98 | 10-NOV-18:45 | 1.73 | -1.5 | 0.282486E+09 | 575.70 | 04-NOV-14:00 | 16.70 | 7.95 |
December | 0.00 | 0.00 | 01-DEC-00:03 | -2.1 | -4.1 | 0.289625E+09 | 453.41 | 09-DEC-15:09 | 8.27 | 3.16 |
Annual Sum or Average | 0.169028E+11 | 0.389202E+10 | ||||||||
Minimum of Months | 0.00 | 0.00 | -2.1 | -4.1 | 0.265171E+09 | 453.41 | 8.27 | 3.16 | ||
Maximum of Months | 0.517293E+10 | 22372.29 | 31.70 | 15.22 | 0.391276E+09 | 599.35 | 32.20 | 18.27 |
Report: ZoneHeatingSummaryMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.140116E+11 | 70695.66 | 09-JAN-00:42 | -27.2 |
February | 0.684726E+10 | 70527.35 | 04-FEB-08:61 | -20.0 |
March | 0.474849E+10 | 70447.61 | 06-MAR-08:61 | -16.9 |
April | 0.143524E+10 | 70280.87 | 22-APR-07:01 | 2.85 |
May | 0.955286E+09 | 70251.07 | 01-MAY-07:01 | 0.78 |
June | 0.102359E+09 | 3569.89 | 22-JUN-07:05 | 19.37 |
July | 42887396.35 | 4060.80 | 18-JUL-07:04 | 24.27 |
August | 56783645.86 | 4067.72 | 07-AUG-07:04 | 22.77 |
September | 0.160536E+09 | 70186.13 | 20-SEP-07:01 | 4.78 |
October | 0.462190E+09 | 70260.06 | 10-OCT-07:01 | -5.7 |
November | 0.303286E+10 | 70330.35 | 21-NOV-08:61 | -8.0 |
December | 0.863922E+10 | 70493.62 | 31-DEC-08:61 | -27.6 |
Annual Sum or Average | 0.404947E+11 | |||
Minimum of Months | 42887396.35 | 3569.89 | -27.6 | |
Maximum of Months | 0.140116E+11 | 70695.66 | 24.27 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.573390E+10 | 37529.53 | 08-JAN-08:61 | -27.2 |
February | 0.264417E+10 | 37523.58 | 05-FEB-08:61 | -20.1 |
March | 0.159149E+10 | 37506.92 | 04-MAR-08:61 | -19.9 |
April | 0.406079E+09 | 37437.06 | 29-APR-07:01 | -4.5 |
May | 0.281859E+09 | 37424.75 | 08-MAY-07:01 | -2.1 |
June | 33699537.38 | 2285.99 | 22-JUN-07:05 | 19.37 |
July | 22122569.52 | 2385.31 | 26-JUL-07:04 | 23.68 |
August | 26186531.37 | 2398.14 | 07-AUG-07:04 | 22.77 |
September | 65045771.71 | 3458.94 | 20-SEP-07:01 | 4.78 |
October | 0.156756E+09 | 30363.79 | 10-OCT-07:01 | -5.7 |
November | 0.111764E+10 | 37472.61 | 21-NOV-08:61 | -8.0 |
December | 0.345484E+10 | 37522.78 | 29-DEC-08:61 | -27.9 |
Annual Sum or Average | 0.155338E+11 | |||
Minimum of Months | 22122569.52 | 2285.99 | -27.9 | |
Maximum of Months | 0.573390E+10 | 37529.53 | 23.68 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.644062E+10 | 37573.92 | 29-JAN-08:61 | -29.8 |
February | 0.307918E+10 | 37515.30 | 05-FEB-08:61 | -20.1 |
March | 0.196781E+10 | 37474.84 | 05-MAR-08:61 | -18.1 |
April | 0.512950E+09 | 37048.79 | 30-APR-07:01 | -3.2 |
May | 0.395314E+09 | 37195.17 | 08-MAY-06:01 | -2.7 |
June | 67573834.69 | 2356.42 | 22-JUN-06:04 | 16.57 |
July | 0.107787E+09 | 2978.68 | 17-JUL-19:02 | 33.48 |
August | 86564472.92 | 3345.92 | 06-AUG-16:11 | 35.40 |
September | 92114874.70 | 3974.17 | 20-SEP-06:03 | 3.48 |
October | 0.209844E+09 | 36730.04 | 10-OCT-06:01 | -6.1 |
November | 0.144221E+10 | 37461.94 | 26-NOV-08:61 | -16.6 |
December | 0.407011E+10 | 37565.90 | 31-DEC-08:61 | -27.6 |
Annual Sum or Average | 0.184721E+11 | |||
Minimum of Months | 67573834.69 | 2356.42 | -29.8 | |
Maximum of Months | 0.644062E+10 | 37573.92 | 35.40 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.676771E+10 | 37597.91 | 11-JAN-07:01 | -27.2 |
February | 0.327314E+10 | 37591.41 | 05-FEB-08:61 | -20.1 |
March | 0.215487E+10 | 37546.44 | 05-MAR-08:61 | -18.1 |
April | 0.581521E+09 | 37118.63 | 30-APR-07:01 | -3.2 |
May | 0.448229E+09 | 37267.60 | 08-MAY-06:01 | -2.7 |
June | 69662134.38 | 2365.11 | 22-JUN-06:04 | 16.57 |
July | 0.107598E+09 | 2978.50 | 17-JUL-19:02 | 33.48 |
August | 86422807.39 | 3348.54 | 06-AUG-16:11 | 35.40 |
September | 96294659.49 | 6254.74 | 20-SEP-06:03 | 3.48 |
October | 0.246688E+09 | 36800.73 | 10-OCT-06:01 | -6.1 |
November | 0.158221E+10 | 37534.13 | 26-NOV-08:61 | -16.6 |
December | 0.432532E+10 | 37651.49 | 31-DEC-08:61 | -27.6 |
Annual Sum or Average | 0.197397E+11 | |||
Minimum of Months | 69662134.38 | 2365.11 | -27.6 | |
Maximum of Months | 0.676771E+10 | 37651.49 | 35.40 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.720218E+10 | 37444.01 | 08-JAN-08:61 | -27.2 |
February | 0.357198E+10 | 37405.09 | 05-FEB-08:61 | -20.1 |
March | 0.243283E+10 | 37371.37 | 06-MAR-07:01 | -19.7 |
April | 0.704835E+09 | 36939.76 | 30-APR-07:01 | -3.2 |
May | 0.524948E+09 | 37087.63 | 08-MAY-06:01 | -2.7 |
June | 75147392.42 | 2251.15 | 22-JUN-06:04 | 16.57 |
July | 0.109218E+09 | 2979.67 | 17-JUL-19:02 | 33.48 |
August | 88571477.00 | 3344.54 | 06-AUG-16:11 | 35.40 |
September | 0.104795E+09 | 8837.25 | 20-SEP-06:03 | 3.48 |
October | 0.297567E+09 | 36626.59 | 10-OCT-06:01 | -6.1 |
November | 0.177659E+10 | 37350.39 | 26-NOV-08:61 | -16.6 |
December | 0.470772E+10 | 37378.25 | 31-DEC-08:61 | -27.6 |
Annual Sum or Average | 0.215964E+11 | |||
Minimum of Months | 75147392.42 | 2251.15 | -27.6 | |
Maximum of Months | 0.720218E+10 | 37444.01 | 35.40 |
Report: ZoneHeatingSummaryMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.146348E+11 | 68952.20 | 30-JAN-08:61 | -14.1 |
February | 0.742544E+10 | 68823.43 | 05-FEB-09:01 | -20.4 |
March | 0.526731E+10 | 68869.19 | 06-MAR-08:61 | -16.9 |
April | 0.171215E+10 | 68624.71 | 28-APR-07:01 | -3.2 |
May | 0.118707E+10 | 68608.55 | 08-MAY-07:01 | -2.1 |
June | 0.127277E+09 | 3581.32 | 22-JUN-07:05 | 19.37 |
July | 0.119516E+09 | 5449.26 | 16-JUL-16:01 | 32.88 |
August | 0.110202E+09 | 6450.03 | 06-AUG-16:01 | 35.50 |
September | 0.250083E+09 | 68572.88 | 20-SEP-07:01 | 4.78 |
October | 0.728145E+09 | 68642.28 | 10-OCT-07:01 | -5.7 |
November | 0.387591E+10 | 68680.93 | 21-NOV-08:61 | -8.0 |
December | 0.978375E+10 | 69000.32 | 31-DEC-09:01 | -26.2 |
Annual Sum or Average | 0.452216E+11 | |||
Minimum of Months | 0.110202E+09 | 3581.32 | -26.2 | |
Maximum of Months | 0.146348E+11 | 69000.32 | 35.50 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.820574E+10 | 36791.73 | 08-JAN-09:01 | -27.1 |
February | 0.426614E+10 | 36692.71 | 05-FEB-09:01 | -20.4 |
March | 0.313145E+10 | 36666.19 | 06-MAR-08:61 | -16.9 |
April | 0.109011E+10 | 36575.24 | 29-APR-07:01 | -4.5 |
May | 0.747420E+09 | 36569.66 | 08-MAY-07:01 | -2.1 |
June | 79160749.54 | 2669.58 | 17-JUN-07:02 | 8.77 |
July | 66438467.02 | 2870.00 | 16-JUL-16:11 | 32.97 |
August | 62901986.48 | 3337.46 | 06-AUG-16:11 | 35.40 |
September | 0.166980E+09 | 36548.26 | 20-SEP-07:01 | 4.78 |
October | 0.464615E+09 | 36589.41 | 10-OCT-07:01 | -5.7 |
November | 0.230914E+10 | 36609.04 | 21-NOV-08:61 | -8.0 |
December | 0.560378E+10 | 36714.77 | 31-DEC-09:01 | -26.2 |
Annual Sum or Average | 0.261939E+11 | |||
Minimum of Months | 62901986.48 | 2669.58 | -27.1 | |
Maximum of Months | 0.820574E+10 | 36791.73 | 35.40 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.829504E+10 | 36769.65 | 08-JAN-09:01 | -27.1 |
February | 0.434787E+10 | 36669.61 | 05-FEB-09:01 | -20.4 |
March | 0.322528E+10 | 36643.64 | 06-MAR-08:61 | -16.9 |
April | 0.116458E+10 | 36551.84 | 28-APR-07:01 | -3.2 |
May | 0.790718E+09 | 36545.56 | 08-MAY-07:01 | -2.1 |
June | 85406130.39 | 4559.21 | 17-JUN-07:02 | 8.77 |
July | 67975950.40 | 2871.26 | 16-JUL-16:11 | 32.97 |
August | 65671623.71 | 3338.96 | 06-AUG-16:11 | 35.40 |
September | 0.179222E+09 | 36524.26 | 20-SEP-07:01 | 4.78 |
October | 0.493069E+09 | 36565.34 | 10-OCT-07:01 | -5.7 |
November | 0.237507E+10 | 36591.69 | 27-NOV-08:61 | -12.7 |
December | 0.569141E+10 | 36691.70 | 31-DEC-09:01 | -26.2 |
Annual Sum or Average | 0.267813E+11 | |||
Minimum of Months | 65671623.71 | 2871.26 | -27.1 | |
Maximum of Months | 0.829504E+10 | 36769.65 | 35.40 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.872397E+10 | 36989.19 | 08-JAN-09:01 | -27.1 |
February | 0.469668E+10 | 36898.46 | 04-FEB-08:61 | -20.0 |
March | 0.361344E+10 | 36859.17 | 06-MAR-08:61 | -16.9 |
April | 0.142562E+10 | 36758.46 | 28-APR-07:01 | -3.2 |
May | 0.955880E+09 | 36747.11 | 01-MAY-07:01 | 0.78 |
June | 0.107087E+09 | 11582.49 | 17-JUN-07:02 | 8.77 |
July | 74070440.23 | 2886.05 | 16-JUL-16:11 | 32.97 |
August | 78791227.50 | 3353.57 | 06-AUG-16:11 | 35.40 |
September | 0.220883E+09 | 36723.09 | 20-SEP-07:01 | 4.78 |
October | 0.581757E+09 | 36764.48 | 10-OCT-07:01 | -5.7 |
November | 0.263838E+10 | 36793.22 | 27-NOV-08:61 | -12.7 |
December | 0.608820E+10 | 36995.85 | 31-DEC-09:01 | -26.2 |
Annual Sum or Average | 0.292048E+11 | |||
Minimum of Months | 74070440.23 | 2886.05 | -27.1 | |
Maximum of Months | 0.872397E+10 | 36995.85 | 35.40 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.124897E+11 | 39873.20 | 27-JAN-08:12 | -27.2 |
February | 0.706374E+10 | 39521.78 | 05-FEB-09:01 | -20.4 |
March | 0.588775E+10 | 39628.69 | 06-MAR-08:61 | -16.9 |
April | 0.265923E+10 | 39301.95 | 29-APR-07:01 | -4.5 |
May | 0.173012E+10 | 39326.52 | 08-MAY-07:01 | -2.1 |
June | 0.192270E+09 | 38073.61 | 17-JUN-07:02 | 8.77 |
July | 99510713.84 | 2956.17 | 16-JUL-16:11 | 32.97 |
August | 0.120278E+09 | 17872.05 | 18-AUG-07:03 | 10.37 |
September | 0.406449E+09 | 39229.10 | 20-SEP-07:01 | 4.78 |
October | 0.994866E+09 | 39286.34 | 10-OCT-07:01 | -5.7 |
November | 0.403520E+10 | 39477.95 | 26-NOV-09:01 | -15.8 |
December | 0.871030E+10 | 39717.91 | 31-DEC-09:01 | -26.2 |
Annual Sum or Average | 0.443894E+11 | |||
Minimum of Months | 99510713.84 | 2956.17 | -27.2 | |
Maximum of Months | 0.124897E+11 | 39873.20 | 32.97 |
Report: ZoneElectricSummaryMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.136196E+11 | 8262.19 | 01-JAN-10:09 | 0.223514E+10 | 1348.26 | 01-JAN-10:09 |
February | 0.123234E+11 | 8262.19 | 01-FEB-10:09 | 0.202238E+10 | 1348.26 | 01-FEB-10:09 |
March | 0.136478E+11 | 8262.19 | 01-MAR-10:09 | 0.223972E+10 | 1348.26 | 01-MAR-10:09 |
April | 0.132157E+11 | 8262.19 | 01-APR-09:09 | 0.216880E+10 | 1348.26 | 01-APR-09:09 |
May | 0.136196E+11 | 8262.19 | 01-MAY-09:09 | 0.223514E+10 | 1348.26 | 01-MAY-09:09 |
June | 0.132157E+11 | 8262.19 | 01-JUN-09:09 | 0.216880E+10 | 1348.26 | 01-JUN-09:09 |
July | 0.136478E+11 | 8262.19 | 01-JUL-09:09 | 0.223972E+10 | 1348.26 | 01-JUL-09:09 |
August | 0.136196E+11 | 8262.19 | 01-AUG-09:09 | 0.223514E+10 | 1348.26 | 01-AUG-09:09 |
September | 0.132439E+11 | 8262.19 | 01-SEP-09:09 | 0.217339E+10 | 1348.26 | 01-SEP-09:09 |
October | 0.136196E+11 | 8262.19 | 01-OCT-09:09 | 0.223514E+10 | 1348.26 | 01-OCT-09:09 |
November | 0.131593E+11 | 8262.19 | 01-NOV-09:09 | 0.215964E+10 | 1348.26 | 01-NOV-09:09 |
December | 0.136759E+11 | 8262.19 | 01-DEC-10:09 | 0.224431E+10 | 1348.26 | 01-DEC-10:09 |
Annual Sum or Average | 0.160608E+12 | 0.263573E+11 | ||||
Minimum of Months | 0.123234E+11 | 8262.19 | 0.202238E+10 | 1348.26 | ||
Maximum of Months | 0.136759E+11 | 8262.19 | 0.224431E+10 | 1348.26 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.759377E+10 | 4606.69 | 01-JAN-10:09 | 0.111757E+10 | 674.13 | 01-JAN-10:09 |
February | 0.687105E+10 | 4606.69 | 01-FEB-10:09 | 0.101119E+10 | 674.13 | 01-FEB-10:09 |
March | 0.760948E+10 | 4606.69 | 01-MAR-10:09 | 0.111986E+10 | 674.13 | 01-MAR-10:09 |
April | 0.736857E+10 | 4606.69 | 01-APR-09:09 | 0.108440E+10 | 674.13 | 01-APR-09:09 |
May | 0.759377E+10 | 4606.69 | 01-MAY-09:09 | 0.111757E+10 | 674.13 | 01-MAY-09:09 |
June | 0.736857E+10 | 4606.69 | 01-JUN-09:09 | 0.108440E+10 | 674.13 | 01-JUN-09:09 |
July | 0.760948E+10 | 4606.69 | 01-JUL-09:09 | 0.111986E+10 | 674.13 | 01-JUL-09:09 |
August | 0.759377E+10 | 4606.69 | 01-AUG-09:09 | 0.111757E+10 | 674.13 | 01-AUG-09:09 |
September | 0.738428E+10 | 4606.69 | 01-SEP-09:09 | 0.108669E+10 | 674.13 | 01-SEP-09:09 |
October | 0.759377E+10 | 4606.69 | 01-OCT-09:09 | 0.111757E+10 | 674.13 | 01-OCT-09:09 |
November | 0.733715E+10 | 4606.69 | 01-NOV-09:09 | 0.107982E+10 | 674.13 | 01-NOV-09:09 |
December | 0.762519E+10 | 4606.69 | 01-DEC-10:09 | 0.112215E+10 | 674.13 | 01-DEC-10:09 |
Annual Sum or Average | 0.895488E+11 | 0.131787E+11 | ||||
Minimum of Months | 0.687105E+10 | 4606.69 | 0.101119E+10 | 674.13 | ||
Maximum of Months | 0.762519E+10 | 4606.69 | 0.112215E+10 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.552790E+10 | 4250.44 | 01-JAN-10:09 | 0.883781E+09 | 674.13 | 01-JAN-10:09 |
February | 0.500604E+10 | 4250.44 | 01-FEB-09:09 | 0.800324E+09 | 674.13 | 01-FEB-09:09 |
March | 0.564387E+10 | 4250.44 | 01-MAR-09:09 | 0.902118E+09 | 674.13 | 01-MAR-09:09 |
April | 0.536361E+10 | 4250.44 | 01-APR-08:09 | 0.857490E+09 | 674.13 | 01-APR-08:09 |
May | 0.558588E+10 | 4250.44 | 01-MAY-08:09 | 0.892950E+09 | 674.13 | 01-MAY-08:09 |
June | 0.545059E+10 | 4250.44 | 01-JUN-08:09 | 0.871243E+09 | 674.13 | 01-JUN-08:09 |
July | 0.549891E+10 | 4250.44 | 01-JUL-08:09 | 0.879197E+09 | 674.13 | 01-JUL-08:09 |
August | 0.564387E+10 | 4250.44 | 01-AUG-08:09 | 0.902118E+09 | 674.13 | 01-AUG-08:09 |
September | 0.536361E+10 | 4250.44 | 01-SEP-08:09 | 0.857490E+09 | 674.13 | 01-SEP-08:09 |
October | 0.552790E+10 | 4250.44 | 01-OCT-09:09 | 0.883781E+09 | 674.13 | 01-OCT-09:09 |
November | 0.536361E+10 | 4250.44 | 01-NOV-08:09 | 0.857490E+09 | 674.13 | 01-NOV-08:09 |
December | 0.549891E+10 | 4250.44 | 01-DEC-09:09 | 0.879197E+09 | 674.13 | 01-DEC-09:09 |
Annual Sum or Average | 0.654747E+11 | 0.104672E+11 | ||||
Minimum of Months | 0.500604E+10 | 4250.44 | 0.800324E+09 | 674.13 | ||
Maximum of Months | 0.564387E+10 | 4250.44 | 0.902118E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.552790E+10 | 4250.44 | 01-JAN-10:09 | 0.883781E+09 | 674.13 | 01-JAN-10:09 |
February | 0.500604E+10 | 4250.44 | 01-FEB-09:09 | 0.800324E+09 | 674.13 | 01-FEB-09:09 |
March | 0.564387E+10 | 4250.44 | 01-MAR-09:09 | 0.902118E+09 | 674.13 | 01-MAR-09:09 |
April | 0.536361E+10 | 4250.44 | 01-APR-08:09 | 0.857490E+09 | 674.13 | 01-APR-08:09 |
May | 0.558588E+10 | 4250.44 | 01-MAY-08:09 | 0.892950E+09 | 674.13 | 01-MAY-08:09 |
June | 0.545059E+10 | 4250.44 | 01-JUN-08:09 | 0.871243E+09 | 674.13 | 01-JUN-08:09 |
July | 0.549891E+10 | 4250.44 | 01-JUL-08:09 | 0.879197E+09 | 674.13 | 01-JUL-08:09 |
August | 0.564387E+10 | 4250.44 | 01-AUG-08:09 | 0.902118E+09 | 674.13 | 01-AUG-08:09 |
September | 0.536361E+10 | 4250.44 | 01-SEP-08:09 | 0.857490E+09 | 674.13 | 01-SEP-08:09 |
October | 0.552790E+10 | 4250.44 | 01-OCT-09:09 | 0.883781E+09 | 674.13 | 01-OCT-09:09 |
November | 0.536361E+10 | 4250.44 | 01-NOV-08:09 | 0.857490E+09 | 674.13 | 01-NOV-08:09 |
December | 0.549891E+10 | 4250.44 | 01-DEC-09:09 | 0.879197E+09 | 674.13 | 01-DEC-09:09 |
Annual Sum or Average | 0.654747E+11 | 0.104672E+11 | ||||
Minimum of Months | 0.500604E+10 | 4250.44 | 0.800324E+09 | 674.13 | ||
Maximum of Months | 0.564387E+10 | 4250.44 | 0.902118E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.552790E+10 | 4250.44 | 01-JAN-10:09 | 0.883781E+09 | 674.13 | 01-JAN-10:09 |
February | 0.500604E+10 | 4250.44 | 01-FEB-09:09 | 0.800324E+09 | 674.13 | 01-FEB-09:09 |
March | 0.564387E+10 | 4250.44 | 01-MAR-09:09 | 0.902118E+09 | 674.13 | 01-MAR-09:09 |
April | 0.536361E+10 | 4250.44 | 01-APR-08:09 | 0.857490E+09 | 674.13 | 01-APR-08:09 |
May | 0.558588E+10 | 4250.44 | 01-MAY-08:09 | 0.892950E+09 | 674.13 | 01-MAY-08:09 |
June | 0.545059E+10 | 4250.44 | 01-JUN-08:09 | 0.871243E+09 | 674.13 | 01-JUN-08:09 |
July | 0.549891E+10 | 4250.44 | 01-JUL-08:09 | 0.879197E+09 | 674.13 | 01-JUL-08:09 |
August | 0.564387E+10 | 4250.44 | 01-AUG-08:09 | 0.902118E+09 | 674.13 | 01-AUG-08:09 |
September | 0.536361E+10 | 4250.44 | 01-SEP-08:09 | 0.857490E+09 | 674.13 | 01-SEP-08:09 |
October | 0.552790E+10 | 4250.44 | 01-OCT-09:09 | 0.883781E+09 | 674.13 | 01-OCT-09:09 |
November | 0.536361E+10 | 4250.44 | 01-NOV-08:09 | 0.857490E+09 | 674.13 | 01-NOV-08:09 |
December | 0.549891E+10 | 4250.44 | 01-DEC-09:09 | 0.879197E+09 | 674.13 | 01-DEC-09:09 |
Annual Sum or Average | 0.654747E+11 | 0.104672E+11 | ||||
Minimum of Months | 0.500604E+10 | 4250.44 | 0.800324E+09 | 674.13 | ||
Maximum of Months | 0.564387E+10 | 4250.44 | 0.902118E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.724555E+10 | 6064.13 | 01-JAN-11:09 | 0.162546E+10 | 1348.26 | 01-JAN-11:09 |
February | 0.656305E+10 | 6064.13 | 01-FEB-10:09 | 0.147229E+10 | 1348.26 | 01-FEB-10:09 |
March | 0.741101E+10 | 6064.13 | 01-MAR-10:09 | 0.166213E+10 | 1348.26 | 01-MAR-10:09 |
April | 0.703184E+10 | 6064.13 | 01-APR-09:09 | 0.157746E+10 | 1348.26 | 01-APR-09:09 |
May | 0.732828E+10 | 6064.13 | 01-MAY-09:09 | 0.164379E+10 | 1348.26 | 01-MAY-09:09 |
June | 0.715593E+10 | 6064.13 | 01-JUN-09:09 | 0.160496E+10 | 1348.26 | 01-JUN-09:09 |
July | 0.720419E+10 | 6064.13 | 01-JUL-09:09 | 0.161629E+10 | 1348.26 | 01-JUL-09:09 |
August | 0.741101E+10 | 6064.13 | 01-AUG-09:09 | 0.166213E+10 | 1348.26 | 01-AUG-09:09 |
September | 0.703184E+10 | 6064.13 | 01-SEP-09:09 | 0.157746E+10 | 1348.26 | 01-SEP-09:09 |
October | 0.724555E+10 | 6064.13 | 01-OCT-10:09 | 0.162546E+10 | 1348.26 | 01-OCT-10:09 |
November | 0.703184E+10 | 6064.13 | 01-NOV-09:09 | 0.157746E+10 | 1348.26 | 01-NOV-09:09 |
December | 0.720419E+10 | 6064.13 | 01-DEC-10:09 | 0.161629E+10 | 1348.26 | 01-DEC-10:09 |
Annual Sum or Average | 0.858643E+11 | 0.192612E+11 | ||||
Minimum of Months | 0.656305E+10 | 6064.13 | 0.147229E+10 | 1348.26 | ||
Maximum of Months | 0.741101E+10 | 6064.13 | 0.166213E+10 | 1348.26 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.362278E+10 | 3032.07 | 01-JAN-11:09 | 0.812728E+09 | 674.13 | 01-JAN-11:09 |
February | 0.328152E+10 | 3032.07 | 01-FEB-10:09 | 0.736147E+09 | 674.13 | 01-FEB-10:09 |
March | 0.370550E+10 | 3032.07 | 01-MAR-10:09 | 0.831065E+09 | 674.13 | 01-MAR-10:09 |
April | 0.351592E+10 | 3032.07 | 01-APR-09:09 | 0.788729E+09 | 674.13 | 01-APR-09:09 |
May | 0.366414E+10 | 3032.07 | 01-MAY-09:09 | 0.821897E+09 | 674.13 | 01-MAY-09:09 |
June | 0.357797E+10 | 3032.07 | 01-JUN-09:09 | 0.802482E+09 | 674.13 | 01-JUN-09:09 |
July | 0.360209E+10 | 3032.07 | 01-JUL-09:09 | 0.808144E+09 | 674.13 | 01-JUL-09:09 |
August | 0.370550E+10 | 3032.07 | 01-AUG-09:09 | 0.831065E+09 | 674.13 | 01-AUG-09:09 |
September | 0.351592E+10 | 3032.07 | 01-SEP-09:09 | 0.788729E+09 | 674.13 | 01-SEP-09:09 |
October | 0.362278E+10 | 3032.07 | 01-OCT-10:09 | 0.812728E+09 | 674.13 | 01-OCT-10:09 |
November | 0.351592E+10 | 3032.07 | 01-NOV-09:09 | 0.788729E+09 | 674.13 | 01-NOV-09:09 |
December | 0.360209E+10 | 3032.07 | 01-DEC-10:09 | 0.808144E+09 | 674.13 | 01-DEC-10:09 |
Annual Sum or Average | 0.429321E+11 | 0.963059E+10 | ||||
Minimum of Months | 0.328152E+10 | 3032.07 | 0.736147E+09 | 674.13 | ||
Maximum of Months | 0.370550E+10 | 3032.07 | 0.831065E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.362278E+10 | 3032.07 | 01-JAN-11:09 | 0.812728E+09 | 674.13 | 01-JAN-11:09 |
February | 0.328152E+10 | 3032.07 | 01-FEB-10:09 | 0.736147E+09 | 674.13 | 01-FEB-10:09 |
March | 0.370550E+10 | 3032.07 | 01-MAR-10:09 | 0.831065E+09 | 674.13 | 01-MAR-10:09 |
April | 0.351592E+10 | 3032.07 | 01-APR-09:09 | 0.788729E+09 | 674.13 | 01-APR-09:09 |
May | 0.366414E+10 | 3032.07 | 01-MAY-09:09 | 0.821897E+09 | 674.13 | 01-MAY-09:09 |
June | 0.357797E+10 | 3032.07 | 01-JUN-09:09 | 0.802482E+09 | 674.13 | 01-JUN-09:09 |
July | 0.360209E+10 | 3032.07 | 01-JUL-09:09 | 0.808144E+09 | 674.13 | 01-JUL-09:09 |
August | 0.370550E+10 | 3032.07 | 01-AUG-09:09 | 0.831065E+09 | 674.13 | 01-AUG-09:09 |
September | 0.351592E+10 | 3032.07 | 01-SEP-09:09 | 0.788729E+09 | 674.13 | 01-SEP-09:09 |
October | 0.362278E+10 | 3032.07 | 01-OCT-10:09 | 0.812728E+09 | 674.13 | 01-OCT-10:09 |
November | 0.351592E+10 | 3032.07 | 01-NOV-09:09 | 0.788729E+09 | 674.13 | 01-NOV-09:09 |
December | 0.360209E+10 | 3032.07 | 01-DEC-10:09 | 0.808144E+09 | 674.13 | 01-DEC-10:09 |
Annual Sum or Average | 0.429321E+11 | 0.963059E+10 | ||||
Minimum of Months | 0.328152E+10 | 3032.07 | 0.736147E+09 | 674.13 | ||
Maximum of Months | 0.370550E+10 | 3032.07 | 0.831065E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.362278E+10 | 3032.07 | 01-JAN-11:09 | 0.812728E+09 | 674.13 | 01-JAN-11:09 |
February | 0.328152E+10 | 3032.07 | 01-FEB-10:09 | 0.736147E+09 | 674.13 | 01-FEB-10:09 |
March | 0.370550E+10 | 3032.07 | 01-MAR-10:09 | 0.831065E+09 | 674.13 | 01-MAR-10:09 |
April | 0.351592E+10 | 3032.07 | 01-APR-09:09 | 0.788729E+09 | 674.13 | 01-APR-09:09 |
May | 0.366414E+10 | 3032.07 | 01-MAY-09:09 | 0.821897E+09 | 674.13 | 01-MAY-09:09 |
June | 0.357797E+10 | 3032.07 | 01-JUN-09:09 | 0.802482E+09 | 674.13 | 01-JUN-09:09 |
July | 0.360209E+10 | 3032.07 | 01-JUL-09:09 | 0.808144E+09 | 674.13 | 01-JUL-09:09 |
August | 0.370550E+10 | 3032.07 | 01-AUG-09:09 | 0.831065E+09 | 674.13 | 01-AUG-09:09 |
September | 0.351592E+10 | 3032.07 | 01-SEP-09:09 | 0.788729E+09 | 674.13 | 01-SEP-09:09 |
October | 0.362278E+10 | 3032.07 | 01-OCT-10:09 | 0.812728E+09 | 674.13 | 01-OCT-10:09 |
November | 0.351592E+10 | 3032.07 | 01-NOV-09:09 | 0.788729E+09 | 674.13 | 01-NOV-09:09 |
December | 0.360209E+10 | 3032.07 | 01-DEC-10:09 | 0.808144E+09 | 674.13 | 01-DEC-10:09 |
Annual Sum or Average | 0.429321E+11 | 0.963059E+10 | ||||
Minimum of Months | 0.328152E+10 | 3032.07 | 0.736147E+09 | 674.13 | ||
Maximum of Months | 0.370550E+10 | 3032.07 | 0.831065E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.362278E+10 | 3032.07 | 01-JAN-11:09 | 0.812728E+09 | 674.13 | 01-JAN-11:09 |
February | 0.328152E+10 | 3032.07 | 01-FEB-10:09 | 0.736147E+09 | 674.13 | 01-FEB-10:09 |
March | 0.370550E+10 | 3032.07 | 01-MAR-10:09 | 0.831065E+09 | 674.13 | 01-MAR-10:09 |
April | 0.351592E+10 | 3032.07 | 01-APR-09:09 | 0.788729E+09 | 674.13 | 01-APR-09:09 |
May | 0.366414E+10 | 3032.07 | 01-MAY-09:09 | 0.821897E+09 | 674.13 | 01-MAY-09:09 |
June | 0.357797E+10 | 3032.07 | 01-JUN-09:09 | 0.802482E+09 | 674.13 | 01-JUN-09:09 |
July | 0.360209E+10 | 3032.07 | 01-JUL-09:09 | 0.808144E+09 | 674.13 | 01-JUL-09:09 |
August | 0.370550E+10 | 3032.07 | 01-AUG-09:09 | 0.831065E+09 | 674.13 | 01-AUG-09:09 |
September | 0.351592E+10 | 3032.07 | 01-SEP-09:09 | 0.788729E+09 | 674.13 | 01-SEP-09:09 |
October | 0.362278E+10 | 3032.07 | 01-OCT-10:09 | 0.812728E+09 | 674.13 | 01-OCT-10:09 |
November | 0.351592E+10 | 3032.07 | 01-NOV-09:09 | 0.788729E+09 | 674.13 | 01-NOV-09:09 |
December | 0.360209E+10 | 3032.07 | 01-DEC-10:09 | 0.808144E+09 | 674.13 | 01-DEC-10:09 |
Annual Sum or Average | 0.429321E+11 | 0.963059E+10 | ||||
Minimum of Months | 0.328152E+10 | 3032.07 | 0.736147E+09 | 674.13 | ||
Maximum of Months | 0.370550E+10 | 3032.07 | 0.831065E+09 | 674.13 |
Report: SpaceGainsMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.180574E+10 | 0.136196E+11 | 0.223514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137064E+11 |
February | 0.163016E+10 | 0.123234E+11 | 0.202238E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.920529E+10 |
March | 0.178954E+10 | 0.136478E+11 | 0.223972E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.846183E+10 |
April | 0.174484E+10 | 0.132157E+11 | 0.216880E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.549514E+10 |
May | 0.179537E+10 | 0.136196E+11 | 0.223514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 65345354.51 | 0.479676E+10 |
June | 0.173447E+10 | 0.132157E+11 | 0.216880E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.407429E+09 | 0.219766E+10 |
July | 0.181028E+10 | 0.136478E+11 | 0.223972E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110644E+10 | 0.106695E+10 |
August | 0.178501E+10 | 0.136196E+11 | 0.223514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.846567E+09 | 0.152733E+10 |
September | 0.174937E+10 | 0.132439E+11 | 0.217339E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.388162E+09 | 0.318372E+10 |
October | 0.180574E+10 | 0.136196E+11 | 0.223514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4588984.02 | 0.530531E+10 |
November | 0.174613E+10 | 0.131593E+11 | 0.215964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.786136E+10 |
December | 0.181481E+10 | 0.136759E+11 | 0.224431E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109732E+11 |
Annual Sum or Average | 0.212115E+11 | 0.160608E+12 | 0.263573E+11 | 0.281853E+10 | 0.737809E+11 | ||||
Minimum of Months | 0.163016E+10 | 0.123234E+11 | 0.202238E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106695E+10 |
Maximum of Months | 0.181481E+10 | 0.136759E+11 | 0.224431E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110644E+10 | 0.137064E+11 |
Report: SpaceGainsMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.902868E+09 | 0.759377E+10 | 0.111757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.678214E+10 |
February | 0.815075E+09 | 0.687105E+10 | 0.101119E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.451823E+10 |
March | 0.894769E+09 | 0.760948E+10 | 0.111986E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.417668E+10 |
April | 0.872416E+09 | 0.736857E+10 | 0.108440E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.272780E+10 |
May | 0.897684E+09 | 0.759377E+10 | 0.111757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35656397.65 | 0.228384E+10 |
June | 0.867232E+09 | 0.736857E+10 | 0.108440E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.224392E+09 | 0.966226E+09 |
July | 0.905135E+09 | 0.760948E+10 | 0.111986E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.609938E+09 | 0.422159E+09 |
August | 0.892501E+09 | 0.759377E+10 | 0.111757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.465426E+09 | 0.653992E+09 |
September | 0.874683E+09 | 0.738428E+10 | 0.108669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.213439E+09 | 0.144404E+10 |
October | 0.902868E+09 | 0.759377E+10 | 0.111757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2513657.19 | 0.254922E+10 |
November | 0.873064E+09 | 0.733715E+10 | 0.107982E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.384157E+10 |
December | 0.907403E+09 | 0.762519E+10 | 0.112215E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.543960E+10 |
Annual Sum or Average | 0.106057E+11 | 0.895488E+11 | 0.131787E+11 | 0.155137E+10 | 0.358055E+11 | ||||
Minimum of Months | 0.815075E+09 | 0.687105E+10 | 0.101119E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.422159E+09 |
Maximum of Months | 0.907403E+09 | 0.762519E+10 | 0.112215E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.609938E+09 | 0.678214E+10 |
Report: SpaceGainsMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.537120E+09 | 0.552790E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.695240E+10 |
February | 0.487879E+09 | 0.500604E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.464428E+10 |
March | 0.551374E+09 | 0.564387E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.428210E+10 |
April | 0.524810E+09 | 0.536361E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.279872E+10 |
May | 0.544247E+09 | 0.558588E+10 | 0.892950E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 35382354.00 | 0.235728E+10 |
June | 0.532585E+09 | 0.545059E+10 | 0.871243E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.221854E+09 | 0.103463E+10 |
July | 0.536472E+09 | 0.549891E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.593115E+09 | 0.482001E+09 |
August | 0.551374E+09 | 0.564387E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.458604E+09 | 0.707686E+09 |
September | 0.524810E+09 | 0.536361E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.202011E+09 | 0.151483E+10 |
October | 0.537120E+09 | 0.552790E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2513613.99 | 0.262086E+10 |
November | 0.518979E+09 | 0.536361E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.392945E+10 |
December | 0.536472E+09 | 0.549891E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.559316E+10 |
Annual Sum or Average | 0.638324E+10 | 0.654747E+11 | 0.104672E+11 | 0.151348E+10 | 0.369174E+11 | ||||
Minimum of Months | 0.487879E+09 | 0.500604E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.482001E+09 |
Maximum of Months | 0.551374E+09 | 0.564387E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.593115E+09 | 0.695240E+10 |
Report: SpaceGainsMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.537120E+09 | 0.552790E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.693892E+10 |
February | 0.487879E+09 | 0.500604E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.462386E+10 |
March | 0.551374E+09 | 0.564387E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.426396E+10 |
April | 0.524810E+09 | 0.536361E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.277498E+10 |
May | 0.544247E+09 | 0.558588E+10 | 0.892950E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 35382868.85 | 0.234211E+10 |
June | 0.532585E+09 | 0.545059E+10 | 0.871243E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.221855E+09 | 0.103320E+10 |
July | 0.536472E+09 | 0.549891E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.592984E+09 | 0.482699E+09 |
August | 0.551374E+09 | 0.564387E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.458498E+09 | 0.707524E+09 |
September | 0.524810E+09 | 0.536361E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.201892E+09 | 0.150926E+10 |
October | 0.537120E+09 | 0.552790E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2513614.05 | 0.260233E+10 |
November | 0.518979E+09 | 0.536361E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.390152E+10 |
December | 0.536472E+09 | 0.549891E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.557842E+10 |
Annual Sum or Average | 0.638324E+10 | 0.654747E+11 | 0.104672E+11 | 0.151313E+10 | 0.367588E+11 | ||||
Minimum of Months | 0.487879E+09 | 0.500604E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.482699E+09 |
Maximum of Months | 0.551374E+09 | 0.564387E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.592984E+09 | 0.693892E+10 |
Report: SpaceGainsMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.537120E+09 | 0.552790E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.692968E+10 |
February | 0.487879E+09 | 0.500604E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.460588E+10 |
March | 0.551374E+09 | 0.564387E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.424693E+10 |
April | 0.524810E+09 | 0.536361E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.274511E+10 |
May | 0.544247E+09 | 0.558588E+10 | 0.892950E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 35385850.19 | 0.232087E+10 |
June | 0.532585E+09 | 0.545059E+10 | 0.871243E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.221861E+09 | 0.102753E+10 |
July | 0.536472E+09 | 0.549891E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.593251E+09 | 0.478776E+09 |
August | 0.551374E+09 | 0.564387E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.458602E+09 | 0.702502E+09 |
September | 0.524810E+09 | 0.536361E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.202018E+09 | 0.149798E+10 |
October | 0.537120E+09 | 0.552790E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2513615.43 | 0.257637E+10 |
November | 0.518979E+09 | 0.536361E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.386964E+10 |
December | 0.536472E+09 | 0.549891E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.556731E+10 |
Annual Sum or Average | 0.638324E+10 | 0.654747E+11 | 0.104672E+11 | 0.151363E+10 | 0.365686E+11 | ||||
Minimum of Months | 0.487879E+09 | 0.500604E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.478776E+09 |
Maximum of Months | 0.551374E+09 | 0.564387E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.593251E+09 | 0.692968E+10 |
Report: SpaceGainsMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.183632E+10 | 0.724555E+10 | 0.162546E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125109E+11 |
February | 0.167188E+10 | 0.656305E+10 | 0.147229E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.830672E+10 |
March | 0.189386E+10 | 0.741101E+10 | 0.166213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.766355E+10 |
April | 0.180380E+10 | 0.703184E+10 | 0.157746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.488612E+10 |
May | 0.186509E+10 | 0.732828E+10 | 0.164379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 62353699.05 | 0.418872E+10 |
June | 0.182945E+10 | 0.715593E+10 | 0.160496E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.390533E+09 | 0.189895E+10 |
July | 0.183943E+10 | 0.720419E+10 | 0.161629E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104659E+10 | 0.902479E+09 |
August | 0.189386E+10 | 0.741101E+10 | 0.166213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.808485E+09 | 0.130419E+10 |
September | 0.180380E+10 | 0.703184E+10 | 0.157746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.356260E+09 | 0.273903E+10 |
October | 0.183632E+10 | 0.724555E+10 | 0.162546E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4425475.60 | 0.461816E+10 |
November | 0.176881E+10 | 0.703184E+10 | 0.157746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.694639E+10 |
December | 0.183943E+10 | 0.720419E+10 | 0.161629E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100428E+11 |
Annual Sum or Average | 0.218821E+11 | 0.858643E+11 | 0.192612E+11 | 0.266865E+10 | 0.660080E+11 | ||||
Minimum of Months | 0.167188E+10 | 0.656305E+10 | 0.147229E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.902479E+09 |
Maximum of Months | 0.189386E+10 | 0.741101E+10 | 0.166213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104659E+10 | 0.125109E+11 |
Report: SpaceGainsMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.918158E+09 | 0.362278E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.696304E+10 |
February | 0.835938E+09 | 0.328152E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.460474E+10 |
March | 0.946926E+09 | 0.370550E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.424922E+10 |
April | 0.901896E+09 | 0.351592E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.269463E+10 |
May | 0.932542E+09 | 0.366414E+10 | 0.821897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 35401647.71 | 0.229625E+10 |
June | 0.914724E+09 | 0.357797E+10 | 0.802482E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.222027E+09 | 0.102807E+10 |
July | 0.919713E+09 | 0.360209E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.595305E+09 | 0.477058E+09 |
August | 0.946926E+09 | 0.370550E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.459583E+09 | 0.701531E+09 |
September | 0.901896E+09 | 0.351592E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.202628E+09 | 0.148935E+10 |
October | 0.918158E+09 | 0.362278E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2513820.12 | 0.253636E+10 |
November | 0.884402E+09 | 0.351592E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.383847E+10 |
December | 0.919713E+09 | 0.360209E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.558687E+10 |
Annual Sum or Average | 0.109410E+11 | 0.429321E+11 | 0.963059E+10 | 0.151746E+10 | 0.364656E+11 | ||||
Minimum of Months | 0.835938E+09 | 0.328152E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.477058E+09 |
Maximum of Months | 0.946926E+09 | 0.370550E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.595305E+09 | 0.696304E+10 |
Report: SpaceGainsMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.918158E+09 | 0.362278E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.696090E+10 |
February | 0.835938E+09 | 0.328152E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.459995E+10 |
March | 0.946926E+09 | 0.370550E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.424532E+10 |
April | 0.901896E+09 | 0.351592E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.268382E+10 |
May | 0.932542E+09 | 0.366414E+10 | 0.821897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 35403368.91 | 0.228699E+10 |
June | 0.914724E+09 | 0.357797E+10 | 0.802482E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.222033E+09 | 0.102476E+10 |
July | 0.919713E+09 | 0.360209E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.595453E+09 | 0.475291E+09 |
August | 0.946926E+09 | 0.370550E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.459642E+09 | 0.699352E+09 |
September | 0.901896E+09 | 0.351592E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.202700E+09 | 0.148387E+10 |
October | 0.918158E+09 | 0.362278E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2513817.77 | 0.252464E+10 |
November | 0.884402E+09 | 0.351592E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.383086E+10 |
December | 0.919713E+09 | 0.360209E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.558412E+10 |
Annual Sum or Average | 0.109410E+11 | 0.429321E+11 | 0.963059E+10 | 0.151774E+10 | 0.363999E+11 | ||||
Minimum of Months | 0.835938E+09 | 0.328152E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.475291E+09 |
Maximum of Months | 0.946926E+09 | 0.370550E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.595453E+09 | 0.696090E+10 |
Report: SpaceGainsMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.918158E+09 | 0.362278E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.695042E+10 |
February | 0.835938E+09 | 0.328152E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.458262E+10 |
March | 0.946926E+09 | 0.370550E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.423151E+10 |
April | 0.901896E+09 | 0.351592E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.265439E+10 |
May | 0.932542E+09 | 0.366414E+10 | 0.821897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 35407019.26 | 0.226088E+10 |
June | 0.914724E+09 | 0.357797E+10 | 0.802482E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.222053E+09 | 0.101326E+10 |
July | 0.919713E+09 | 0.360209E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.595754E+09 | 0.470161E+09 |
August | 0.946926E+09 | 0.370550E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.459732E+09 | 0.693064E+09 |
September | 0.901896E+09 | 0.351592E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.202799E+09 | 0.146829E+10 |
October | 0.918158E+09 | 0.362278E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2513809.51 | 0.249488E+10 |
November | 0.884402E+09 | 0.351592E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.380911E+10 |
December | 0.919713E+09 | 0.360209E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.557173E+10 |
Annual Sum or Average | 0.109410E+11 | 0.429321E+11 | 0.963059E+10 | 0.151826E+10 | 0.362003E+11 | ||||
Minimum of Months | 0.835938E+09 | 0.328152E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.470161E+09 |
Maximum of Months | 0.946926E+09 | 0.370550E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.595754E+09 | 0.695042E+10 |
Report: SpaceGainsMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.918158E+09 | 0.362278E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.879494E+10 |
February | 0.835938E+09 | 0.328152E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.588482E+10 |
March | 0.946926E+09 | 0.370550E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.542277E+10 |
April | 0.901896E+09 | 0.351592E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.339373E+10 |
May | 0.932542E+09 | 0.366414E+10 | 0.821897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 37886278.13 | 0.300748E+10 |
June | 0.914724E+09 | 0.357797E+10 | 0.802482E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.234795E+09 | 0.146089E+10 |
July | 0.919713E+09 | 0.360209E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.630299E+09 | 0.779766E+09 |
August | 0.946926E+09 | 0.370550E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.488049E+09 | 0.105245E+10 |
September | 0.901896E+09 | 0.351592E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.214755E+09 | 0.208574E+10 |
October | 0.918158E+09 | 0.362278E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2677420.82 | 0.330166E+10 |
November | 0.884402E+09 | 0.351592E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.495459E+10 |
December | 0.919713E+09 | 0.360209E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.702502E+10 |
Annual Sum or Average | 0.109410E+11 | 0.429321E+11 | 0.963059E+10 | 0.160846E+10 | 0.471639E+11 | ||||
Minimum of Months | 0.835938E+09 | 0.328152E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.779766E+09 |
Maximum of Months | 0.946926E+09 | 0.370550E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.630299E+09 | 0.879494E+10 |
Report: PeakSpaceGainsMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2159.72 | 01-JAN-13:09 | 8262.19 | 01-JAN-10:09 | 1348.26 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 24880.95 | 10-JAN-18:00 |
February | 2159.72 | 03-FEB-13:09 | 8262.19 | 01-FEB-10:09 | 1348.26 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 20115.01 | 09-FEB-18:00 |
March | 2159.72 | 03-MAR-13:09 | 8262.19 | 01-MAR-10:09 | 1348.26 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 19196.47 | 04-MAR-14:00 |
April | 2159.72 | 01-APR-12:09 | 8262.19 | 01-APR-09:09 | 1348.26 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 11638.40 | 27-APR-11:10 |
May | 2159.72 | 05-MAY-12:09 | 8262.19 | 01-MAY-09:09 | 1348.26 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2610.65 | 20-MAY-16:00 | 10718.03 | 22-MAY-16:00 |
June | 2159.72 | 02-JUN-12:09 | 8262.19 | 01-JUN-09:09 | 1348.26 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3676.49 | 29-JUN-15:00 | 7115.37 | 16-JUN-11:05 |
July | 2159.72 | 01-JUL-12:09 | 8262.19 | 01-JUL-09:09 | 1348.26 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5515.87 | 17-JUL-16:00 | 4370.26 | 05-JUL-11:10 |
August | 2159.72 | 04-AUG-12:09 | 8262.19 | 01-AUG-09:09 | 1348.26 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4889.86 | 05-AUG-16:00 | 7112.48 | 17-AUG-11:05 |
September | 2159.72 | 01-SEP-12:09 | 8262.19 | 01-SEP-09:09 | 1348.26 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4506.96 | 02-SEP-15:00 | 8254.11 | 12-SEP-11:03 |
October | 2159.72 | 01-OCT-12:09 | 8262.19 | 01-OCT-09:09 | 1348.26 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 488.52 | 18-OCT-14:00 | 10018.21 | 10-OCT-11:10 |
November | 2159.72 | 03-NOV-12:09 | 8262.19 | 01-NOV-09:09 | 1348.26 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 17574.45 | 26-NOV-18:00 |
December | 2159.72 | 01-DEC-13:09 | 8262.19 | 01-DEC-10:09 | 1348.26 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 21491.18 | 28-DEC-18:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2159.72 | 8262.19 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4370.26 | |||||
Maximum of Months | 2159.72 | 8262.19 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 5515.87 | 24880.95 |
Report: PeakSpaceGainsMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1079.86 | 01-JAN-13:09 | 4606.69 | 01-JAN-10:09 | 674.13 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 13931.95 | 10-JAN-18:00 |
February | 1079.86 | 03-FEB-13:09 | 4606.69 | 01-FEB-10:09 | 674.13 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 11232.23 | 09-FEB-18:00 |
March | 1079.86 | 03-MAR-13:09 | 4606.69 | 01-MAR-10:09 | 674.13 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 10846.73 | 04-MAR-18:00 |
April | 1079.86 | 01-APR-12:09 | 4606.69 | 01-APR-09:09 | 674.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 6367.03 | 27-APR-11:10 |
May | 1079.86 | 05-MAY-12:09 | 4606.69 | 01-MAY-09:09 | 674.13 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1437.54 | 20-MAY-16:00 | 5735.19 | 22-MAY-16:00 |
June | 1079.86 | 02-JUN-12:09 | 4606.69 | 01-JUN-09:09 | 674.13 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1987.54 | 29-JUN-15:00 | 4221.33 | 16-JUN-11:05 |
July | 1079.86 | 01-JUL-12:09 | 4606.69 | 01-JUL-09:09 | 674.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3071.64 | 17-JUL-16:00 | 2457.60 | 05-JUL-11:10 |
August | 1079.86 | 04-AUG-12:09 | 4606.69 | 01-AUG-09:09 | 674.13 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2714.18 | 05-AUG-16:00 | 4005.80 | 17-AUG-11:05 |
September | 1079.86 | 01-SEP-12:09 | 4606.69 | 01-SEP-09:09 | 674.13 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2468.81 | 02-SEP-15:00 | 4711.05 | 12-SEP-11:03 |
October | 1079.86 | 01-OCT-12:09 | 4606.69 | 01-OCT-09:09 | 674.13 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 267.60 | 18-OCT-14:00 | 5531.06 | 10-OCT-11:10 |
November | 1079.86 | 03-NOV-12:09 | 4606.69 | 01-NOV-09:09 | 674.13 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 9760.22 | 26-NOV-18:00 |
December | 1079.86 | 01-DEC-13:09 | 4606.69 | 01-DEC-10:09 | 674.13 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 12156.59 | 31-DEC-12:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1079.86 | 4606.69 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2457.60 | |||||
Maximum of Months | 1079.86 | 4606.69 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 3071.64 | 13931.95 |
Report: PeakSpaceGainsMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1079.86 | 07-JAN-13:09 | 4250.44 | 01-JAN-10:09 | 674.13 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 13931.93 | 10-JAN-18:00 |
February | 1079.86 | 04-FEB-13:09 | 4250.44 | 01-FEB-09:09 | 674.13 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 11232.21 | 09-FEB-18:00 |
March | 1079.86 | 04-MAR-13:09 | 4250.44 | 01-MAR-09:09 | 674.13 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 10846.73 | 04-MAR-18:00 |
April | 1079.86 | 01-APR-12:09 | 4250.44 | 01-APR-08:09 | 674.13 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 6367.01 | 27-APR-11:10 |
May | 1079.86 | 06-MAY-12:09 | 4250.44 | 01-MAY-08:09 | 674.13 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1437.54 | 20-MAY-16:00 | 5735.16 | 22-MAY-16:00 |
June | 1079.86 | 03-JUN-12:09 | 4250.44 | 01-JUN-08:09 | 674.13 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1987.52 | 29-JUN-15:00 | 4207.47 | 16-JUN-11:05 |
July | 1079.86 | 01-JUL-12:09 | 4250.44 | 01-JUL-08:09 | 674.13 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3071.63 | 17-JUL-16:00 | 2457.60 | 05-JUL-11:10 |
August | 1079.86 | 05-AUG-12:09 | 4250.44 | 01-AUG-08:09 | 674.13 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2714.18 | 05-AUG-16:00 | 4015.70 | 17-AUG-11:05 |
September | 1079.86 | 02-SEP-12:09 | 4250.44 | 01-SEP-08:09 | 674.13 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2468.80 | 02-SEP-15:00 | 4690.64 | 12-SEP-11:03 |
October | 1079.86 | 07-OCT-12:09 | 4250.44 | 01-OCT-09:09 | 674.13 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 267.59 | 18-OCT-14:00 | 5531.05 | 10-OCT-11:10 |
November | 1079.86 | 04-NOV-12:09 | 4250.44 | 01-NOV-08:09 | 674.13 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 9760.20 | 26-NOV-18:00 |
December | 1079.86 | 02-DEC-13:09 | 4250.44 | 01-DEC-09:09 | 674.13 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 12156.59 | 31-DEC-12:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1079.86 | 4250.44 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2457.60 | |||||
Maximum of Months | 1079.86 | 4250.44 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 3071.63 | 13931.93 |
Report: PeakSpaceGainsMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1079.86 | 07-JAN-13:09 | 4250.44 | 01-JAN-10:09 | 674.13 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 13931.93 | 10-JAN-18:00 |
February | 1079.86 | 04-FEB-13:09 | 4250.44 | 01-FEB-09:09 | 674.13 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 11232.21 | 09-FEB-18:00 |
March | 1079.86 | 04-MAR-13:09 | 4250.44 | 01-MAR-09:09 | 674.13 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 10846.73 | 04-MAR-18:00 |
April | 1079.86 | 01-APR-12:09 | 4250.44 | 01-APR-08:09 | 674.13 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 6367.01 | 27-APR-11:10 |
May | 1079.86 | 06-MAY-12:09 | 4250.44 | 01-MAY-08:09 | 674.13 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1437.54 | 20-MAY-16:00 | 5735.16 | 22-MAY-16:00 |
June | 1079.86 | 03-JUN-12:09 | 4250.44 | 01-JUN-08:09 | 674.13 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1987.52 | 29-JUN-15:00 | 4194.67 | 16-JUN-11:05 |
July | 1079.86 | 01-JUL-12:09 | 4250.44 | 01-JUL-08:09 | 674.13 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3071.63 | 17-JUL-16:00 | 2457.60 | 05-JUL-11:10 |
August | 1079.86 | 05-AUG-12:09 | 4250.44 | 01-AUG-08:09 | 674.13 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2714.18 | 05-AUG-16:00 | 4012.75 | 17-AUG-11:05 |
September | 1079.86 | 02-SEP-12:09 | 4250.44 | 01-SEP-08:09 | 674.13 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2468.80 | 02-SEP-15:00 | 4672.14 | 12-SEP-11:03 |
October | 1079.86 | 07-OCT-12:09 | 4250.44 | 01-OCT-09:09 | 674.13 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 267.59 | 18-OCT-14:00 | 5531.05 | 10-OCT-11:10 |
November | 1079.86 | 04-NOV-12:09 | 4250.44 | 01-NOV-08:09 | 674.13 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 9760.20 | 26-NOV-18:00 |
December | 1079.86 | 02-DEC-13:09 | 4250.44 | 01-DEC-09:09 | 674.13 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 12156.59 | 31-DEC-12:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1079.86 | 4250.44 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2457.60 | |||||
Maximum of Months | 1079.86 | 4250.44 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 3071.63 | 13931.93 |
Report: PeakSpaceGainsMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1079.86 | 07-JAN-13:09 | 4250.44 | 01-JAN-10:09 | 674.13 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 13931.93 | 10-JAN-18:00 |
February | 1079.86 | 04-FEB-13:09 | 4250.44 | 01-FEB-09:09 | 674.13 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 11232.21 | 09-FEB-18:00 |
March | 1079.86 | 04-MAR-13:09 | 4250.44 | 01-MAR-09:09 | 674.13 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 10846.73 | 04-MAR-18:00 |
April | 1079.86 | 01-APR-12:09 | 4250.44 | 01-APR-08:09 | 674.13 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 6367.01 | 27-APR-11:10 |
May | 1079.86 | 06-MAY-12:09 | 4250.44 | 01-MAY-08:09 | 674.13 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1437.54 | 20-MAY-16:00 | 5735.16 | 22-MAY-16:00 |
June | 1079.86 | 03-JUN-12:09 | 4250.44 | 01-JUN-08:09 | 674.13 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1987.52 | 29-JUN-15:00 | 4148.51 | 16-JUN-11:05 |
July | 1079.86 | 01-JUL-12:09 | 4250.44 | 01-JUL-08:09 | 674.13 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3071.63 | 17-JUL-16:00 | 2457.60 | 05-JUL-11:10 |
August | 1079.86 | 05-AUG-12:09 | 4250.44 | 01-AUG-08:09 | 674.13 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2714.18 | 05-AUG-16:00 | 3968.46 | 17-AUG-11:05 |
September | 1079.86 | 02-SEP-12:09 | 4250.44 | 01-SEP-08:09 | 674.13 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2468.80 | 02-SEP-15:00 | 4614.27 | 12-SEP-11:03 |
October | 1079.86 | 07-OCT-12:09 | 4250.44 | 01-OCT-09:09 | 674.13 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 267.59 | 18-OCT-14:00 | 5531.05 | 10-OCT-11:10 |
November | 1079.86 | 04-NOV-12:09 | 4250.44 | 01-NOV-08:09 | 674.13 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 9760.20 | 26-NOV-18:00 |
December | 1079.86 | 02-DEC-13:09 | 4250.44 | 01-DEC-09:09 | 674.13 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 12156.60 | 31-DEC-12:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1079.86 | 4250.44 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2457.60 | |||||
Maximum of Months | 1079.86 | 4250.44 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 3071.63 | 13931.93 |
Report: PeakSpaceGainsMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2879.63 | 07-JAN-15:09 | 6064.13 | 01-JAN-11:09 | 1348.26 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 24446.52 | 10-JAN-18:00 |
February | 2879.63 | 04-FEB-15:09 | 6064.13 | 01-FEB-10:09 | 1348.26 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 19717.27 | 09-FEB-18:00 |
March | 2879.63 | 04-MAR-15:09 | 6064.13 | 01-MAR-10:09 | 1348.26 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 18999.99 | 04-MAR-18:00 |
April | 2879.63 | 01-APR-14:09 | 6064.13 | 01-APR-09:09 | 1348.26 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 11210.78 | 27-APR-11:10 |
May | 2879.63 | 06-MAY-14:09 | 6064.13 | 01-MAY-09:09 | 1348.26 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2528.77 | 20-MAY-16:00 | 10132.02 | 22-MAY-16:00 |
June | 2879.63 | 03-JUN-14:09 | 6064.13 | 01-JUN-09:09 | 1348.26 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3505.88 | 29-JUN-15:00 | 7039.41 | 16-JUN-11:05 |
July | 2879.63 | 01-JUL-14:09 | 6064.13 | 01-JUL-09:09 | 1348.26 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5394.25 | 17-JUL-16:00 | 4290.96 | 05-JUL-11:10 |
August | 2879.63 | 05-AUG-14:09 | 6064.13 | 01-AUG-09:09 | 1348.26 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4768.83 | 05-AUG-16:00 | 6708.65 | 17-AUG-11:05 |
September | 2879.63 | 02-SEP-14:09 | 6064.13 | 01-SEP-09:09 | 1348.26 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4346.22 | 02-SEP-15:00 | 7899.89 | 12-SEP-11:03 |
October | 2879.63 | 07-OCT-14:09 | 6064.13 | 01-OCT-10:09 | 1348.26 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 471.10 | 18-OCT-14:00 | 9725.59 | 10-OCT-11:10 |
November | 2879.63 | 04-NOV-14:09 | 6064.13 | 01-NOV-09:09 | 1348.26 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 17147.04 | 26-NOV-18:00 |
December | 2879.63 | 02-DEC-15:09 | 6064.13 | 01-DEC-10:09 | 1348.26 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 21294.48 | 31-DEC-12:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2879.63 | 6064.13 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4290.96 | |||||
Maximum of Months | 2879.63 | 6064.13 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 5394.25 | 24446.52 |
Report: PeakSpaceGainsMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1439.81 | 07-JAN-15:09 | 3032.07 | 01-JAN-11:09 | 674.13 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 13931.92 | 10-JAN-18:00 |
February | 1439.81 | 04-FEB-15:09 | 3032.07 | 01-FEB-10:09 | 674.13 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 11232.20 | 09-FEB-18:00 |
March | 1439.81 | 04-MAR-15:09 | 3032.07 | 01-MAR-10:09 | 674.13 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 10846.72 | 04-MAR-18:00 |
April | 1439.81 | 01-APR-14:09 | 3032.07 | 01-APR-09:09 | 674.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 6367.00 | 27-APR-11:10 |
May | 1439.81 | 06-MAY-14:09 | 3032.07 | 01-MAY-09:09 | 674.13 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1437.56 | 20-MAY-16:00 | 5735.15 | 22-MAY-16:00 |
June | 1439.81 | 03-JUN-14:09 | 3032.07 | 01-JUN-09:09 | 674.13 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1987.55 | 29-JUN-15:00 | 4019.90 | 16-JUN-11:05 |
July | 1439.81 | 01-JUL-14:09 | 3032.07 | 01-JUL-09:09 | 674.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3071.66 | 17-JUL-16:00 | 2441.14 | 05-JUL-11:10 |
August | 1439.81 | 05-AUG-14:09 | 3032.07 | 01-AUG-09:09 | 674.13 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2714.22 | 05-AUG-16:00 | 3802.21 | 17-AUG-11:05 |
September | 1439.81 | 02-SEP-14:09 | 3032.07 | 01-SEP-09:09 | 674.13 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2468.84 | 02-SEP-15:00 | 4484.22 | 12-SEP-11:03 |
October | 1439.81 | 07-OCT-14:09 | 3032.07 | 01-OCT-10:09 | 674.13 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 267.61 | 18-OCT-14:00 | 5531.04 | 10-OCT-11:10 |
November | 1439.81 | 04-NOV-14:09 | 3032.07 | 01-NOV-09:09 | 674.13 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 9760.20 | 26-NOV-18:00 |
December | 1439.81 | 02-DEC-15:09 | 3032.07 | 01-DEC-10:09 | 674.13 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 12156.60 | 31-DEC-12:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1439.81 | 3032.07 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2441.14 | |||||
Maximum of Months | 1439.81 | 3032.07 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 3071.66 | 13931.92 |
Report: PeakSpaceGainsMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1439.81 | 07-JAN-15:09 | 3032.07 | 01-JAN-11:09 | 674.13 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 13931.92 | 10-JAN-18:00 |
February | 1439.81 | 04-FEB-15:09 | 3032.07 | 01-FEB-10:09 | 674.13 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 11232.20 | 09-FEB-18:00 |
March | 1439.81 | 04-MAR-15:09 | 3032.07 | 01-MAR-10:09 | 674.13 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 10846.72 | 04-MAR-18:00 |
April | 1439.81 | 01-APR-14:09 | 3032.07 | 01-APR-09:09 | 674.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 6367.00 | 27-APR-11:10 |
May | 1439.81 | 06-MAY-14:09 | 3032.07 | 01-MAY-09:09 | 674.13 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1437.56 | 20-MAY-16:00 | 5735.15 | 22-MAY-16:00 |
June | 1439.81 | 03-JUN-14:09 | 3032.07 | 01-JUN-09:09 | 674.13 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1987.55 | 29-JUN-15:00 | 4016.85 | 16-JUN-11:05 |
July | 1439.81 | 01-JUL-14:09 | 3032.07 | 01-JUL-09:09 | 674.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3071.66 | 17-JUL-16:00 | 2435.56 | 05-JUL-11:10 |
August | 1439.81 | 05-AUG-14:09 | 3032.07 | 01-AUG-09:09 | 674.13 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2714.22 | 05-AUG-16:00 | 3785.39 | 17-AUG-11:05 |
September | 1439.81 | 02-SEP-14:09 | 3032.07 | 01-SEP-09:09 | 674.13 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2468.84 | 02-SEP-15:00 | 4481.93 | 12-SEP-11:03 |
October | 1439.81 | 07-OCT-14:09 | 3032.07 | 01-OCT-10:09 | 674.13 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 267.61 | 18-OCT-14:00 | 5531.03 | 10-OCT-11:10 |
November | 1439.81 | 04-NOV-14:09 | 3032.07 | 01-NOV-09:09 | 674.13 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 9760.20 | 26-NOV-18:00 |
December | 1439.81 | 02-DEC-15:09 | 3032.07 | 01-DEC-10:09 | 674.13 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 12156.60 | 31-DEC-12:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1439.81 | 3032.07 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2435.56 | |||||
Maximum of Months | 1439.81 | 3032.07 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 3071.66 | 13931.92 |
Report: PeakSpaceGainsMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1439.81 | 07-JAN-15:09 | 3032.07 | 01-JAN-11:09 | 674.13 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 13931.92 | 10-JAN-18:00 |
February | 1439.81 | 04-FEB-15:09 | 3032.07 | 01-FEB-10:09 | 674.13 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 11232.20 | 09-FEB-18:00 |
March | 1439.81 | 04-MAR-15:09 | 3032.07 | 01-MAR-10:09 | 674.13 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 10846.72 | 04-MAR-18:00 |
April | 1439.81 | 01-APR-14:09 | 3032.07 | 01-APR-09:09 | 674.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 6367.00 | 27-APR-11:10 |
May | 1439.81 | 06-MAY-14:09 | 3032.07 | 01-MAY-09:09 | 674.13 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1437.56 | 20-MAY-16:00 | 5735.15 | 22-MAY-16:00 |
June | 1439.81 | 03-JUN-14:09 | 3032.07 | 01-JUN-09:09 | 674.13 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1987.55 | 29-JUN-15:00 | 4008.17 | 16-JUN-11:05 |
July | 1439.81 | 01-JUL-14:09 | 3032.07 | 01-JUL-09:09 | 674.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3071.66 | 17-JUL-16:00 | 2418.50 | 05-JUL-11:10 |
August | 1439.81 | 05-AUG-14:09 | 3032.07 | 01-AUG-09:09 | 674.13 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2714.22 | 05-AUG-16:00 | 3730.21 | 17-AUG-11:05 |
September | 1439.81 | 02-SEP-14:09 | 3032.07 | 01-SEP-09:09 | 674.13 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2468.83 | 02-SEP-15:00 | 4480.79 | 12-SEP-11:10 |
October | 1439.81 | 07-OCT-14:09 | 3032.07 | 01-OCT-10:09 | 674.13 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 267.61 | 18-OCT-14:00 | 5531.04 | 10-OCT-11:10 |
November | 1439.81 | 04-NOV-14:09 | 3032.07 | 01-NOV-09:09 | 674.13 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 9760.20 | 26-NOV-18:00 |
December | 1439.81 | 02-DEC-15:09 | 3032.07 | 01-DEC-10:09 | 674.13 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 12156.60 | 31-DEC-12:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1439.81 | 3032.07 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2418.50 | |||||
Maximum of Months | 1439.81 | 3032.07 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 3071.66 | 13931.92 |
Report: PeakSpaceGainsMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1439.81 | 07-JAN-15:09 | 3032.07 | 01-JAN-11:09 | 674.13 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 14365.77 | 10-JAN-18:00 |
February | 1439.81 | 04-FEB-15:09 | 3032.07 | 01-FEB-10:09 | 674.13 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 11629.41 | 09-FEB-18:00 |
March | 1439.81 | 04-MAR-15:09 | 3032.07 | 01-MAR-10:09 | 674.13 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 11112.88 | 04-MAR-14:00 |
April | 1439.81 | 01-APR-14:09 | 3032.07 | 01-APR-09:09 | 674.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 6794.06 | 27-APR-11:10 |
May | 1439.81 | 06-MAY-14:09 | 3032.07 | 01-MAY-09:09 | 674.13 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1519.39 | 20-MAY-16:00 | 6320.38 | 22-MAY-16:00 |
June | 1439.81 | 03-JUN-14:09 | 3032.07 | 01-JUN-09:09 | 674.13 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2157.99 | 29-JUN-15:00 | 4080.33 | 16-JUN-11:05 |
July | 1439.81 | 01-JUL-14:09 | 3032.07 | 01-JUL-09:09 | 674.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3193.17 | 17-JUL-16:00 | 2392.88 | 05-JUL-11:10 |
August | 1439.81 | 05-AUG-14:09 | 3032.07 | 01-AUG-09:09 | 674.13 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2835.18 | 05-AUG-16:00 | 3863.87 | 17-AUG-11:05 |
September | 1439.81 | 02-SEP-14:09 | 3032.07 | 01-SEP-09:09 | 674.13 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2629.44 | 02-SEP-15:00 | 4826.73 | 12-SEP-11:10 |
October | 1439.81 | 07-OCT-14:09 | 3032.07 | 01-OCT-10:09 | 674.13 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 285.01 | 18-OCT-14:00 | 5823.26 | 10-OCT-11:10 |
November | 1439.81 | 04-NOV-14:09 | 3032.07 | 01-NOV-09:09 | 674.13 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 10187.06 | 26-NOV-18:00 |
December | 1439.81 | 02-DEC-15:09 | 3032.07 | 01-DEC-10:09 | 674.13 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 12382.24 | 31-DEC-15:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1439.81 | 3032.07 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2392.88 | |||||
Maximum of Months | 1439.81 | 3032.07 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 3193.17 | 14365.77 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 17946.63 | 28-JAN-00:01 | 1439.81 | 34788.19 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 642.17 |
February | 14530.09 | 04-FEB-00:01 | 1259.84 | 30439.66 | 5243.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 726.75 |
March | 12902.12 | 04-MAR-00:02 | 1079.86 | 26091.14 | 4494.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 835.33 |
April | 7916.12 | 28-APR-23:25 | 359.95 | 8697.05 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 436.59 |
May | 12949.78 | 20-MAY-16:10 | 1799.77 | 8262.19 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 2523.52 | 0.00 |
June | 22125.22 | 22-JUN-07:03 | 719.91 | 1739.41 | 299.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 328.13 |
July | 36167.25 | 26-JUL-07:02 | 899.88 | 2174.26 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.80 |
August | 36936.59 | 07-AUG-07:02 | 899.88 | 2174.26 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.02 |
September | 41784.11 | 04-SEP-07:02 | 1079.86 | 2609.11 | 449.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 315.24 |
October | 11641.86 | 18-OCT-14:00 | 1439.81 | 8262.19 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 488.52 | 0.00 |
November | 11497.10 | 26-NOV-21:03 | 4319.44 | 33048.78 | 5393.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1093.15 |
December | 15516.72 | 29-DEC-00:11 | 1619.79 | 39136.71 | 6741.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 122.08 |
Annual Sum or Average | |||||||||||
Minimum of Months | 7916.12 | 359.95 | 1739.41 | 299.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 41784.11 | 4319.44 | 39136.71 | 6741.28 | 0.00 | 0.00 | 0.00 | 0.00 | 2523.52 | 1093.15 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2549.45 | 02-JAN-18:10 | 899.88 | 4606.69 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 864.13 |
February | 3543.52 | 22-FEB-10:03 | 539.93 | 13820.07 | 2022.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1165.64 |
March | 3306.02 | 15-MAR-19:30 | 539.93 | 4606.69 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.39 |
April | 23609.12 | 25-APR-20:01 | 5399.28 | 46066.91 | 6741.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 24530.15 | 14-MAY-17:11 | 10798.56 | 46066.91 | 6741.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 478.57 |
June | 25543.10 | 19-JUN-20:57 | 2159.71 | 18426.77 | 2696.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.77 |
July | 25246.71 | 27-JUL-20:06 | 5399.28 | 46066.91 | 6741.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.85 |
August | 25721.74 | 14-AUG-20:24 | 4859.35 | 41460.22 | 6067.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.81 |
September | 24689.49 | 23-SEP-18:47 | 3599.52 | 18426.77 | 2696.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 261.16 |
October | 24552.74 | 15-OCT-17:57 | 4319.42 | 18426.77 | 2696.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 245.17 |
November | 23138.28 | 05-NOV-17:01 | 10798.56 | 46066.91 | 6741.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 407.62 |
December | 4156.89 | 13-DEC-11:23 | 539.93 | 13820.07 | 2022.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1177.76 |
Annual Sum or Average | |||||||||||
Minimum of Months | 2549.45 | 539.93 | 4606.69 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 25721.74 | 10798.56 | 46066.91 | 6741.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1177.76 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4509.52 | 19-JAN-18:33 | 3599.52 | 17001.76 | 2696.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1324.34 |
February | 4057.93 | 28-FEB-08:61 | 899.88 | 22370.74 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1108.00 |
March | 5834.52 | 03-MAR-20:03 | 359.95 | 8948.30 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 248.22 |
April | 3956.75 | 25-APR-17:10 | 899.88 | 4250.44 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 259.17 |
May | 8753.59 | 20-MAY-06:02 | 0.00 | 1342.24 | 224.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.16 |
June | 20386.47 | 22-JUN-06:02 | 0.00 | 1118.54 | 187.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.28 |
July | 26026.18 | 27-JUL-06:01 | 0.00 | 1565.95 | 262.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.96 |
August | 26310.39 | 12-AUG-06:02 | 0.00 | 1342.24 | 224.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.93 |
September | 23728.60 | 03-SEP-07:02 | 0.00 | 1118.54 | 187.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 235.28 |
October | 6362.17 | 18-OCT-14:00 | 539.93 | 4250.44 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 267.59 | 0.00 |
November | 4027.51 | 10-NOV-08:61 | 899.88 | 22370.74 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1158.75 |
December | 3890.67 | 26-DEC-18:23 | 2699.64 | 12751.32 | 2022.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1102.86 |
Annual Sum or Average | |||||||||||
Minimum of Months | 3890.67 | 0.00 | 1118.54 | 187.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 26310.39 | 3599.52 | 22370.74 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 267.59 | 1324.34 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2035.17 | 02-JAN-10:15 | 359.95 | 8500.88 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 781.14 |
February | 3982.22 | 28-FEB-08:61 | 899.88 | 22370.74 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1093.77 |
March | 4843.61 | 01-MAR-08:61 | 899.88 | 22370.74 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1185.91 |
April | 3740.25 | 25-APR-17:10 | 899.88 | 4250.44 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 259.17 |
May | 8077.62 | 20-MAY-06:02 | 0.00 | 1342.24 | 224.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.14 |
June | 20450.71 | 22-JUN-06:02 | 0.00 | 1118.54 | 187.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.30 |
July | 26145.56 | 27-JUL-06:01 | 0.00 | 1565.95 | 262.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.16 |
August | 27158.57 | 12-AUG-06:02 | 0.00 | 1342.24 | 224.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.95 |
September | 24705.21 | 03-SEP-07:02 | 0.00 | 1118.54 | 187.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 235.56 |
October | 6258.12 | 18-OCT-14:00 | 539.93 | 4250.44 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 267.59 | 0.00 |
November | 3964.18 | 10-NOV-08:61 | 899.88 | 22370.74 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1146.53 |
December | 2325.73 | 18-DEC-20:25 | 179.98 | 4474.15 | 749.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 212.27 |
Annual Sum or Average | |||||||||||
Minimum of Months | 2035.17 | 0.00 | 1118.54 | 187.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 27158.57 | 899.88 | 22370.74 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 267.59 | 1185.91 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2236.78 | 20-JAN-20:15 | 179.98 | 4474.15 | 749.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 236.52 |
February | 3912.49 | 28-FEB-08:61 | 899.88 | 22370.74 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1077.47 |
March | 2794.13 | 24-MAR-08:53 | 539.93 | 12751.32 | 2022.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 785.35 |
April | 3428.64 | 27-APR-07:01 | 899.88 | 22370.74 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1052.72 |
May | 6860.95 | 20-MAY-16:00 | 539.93 | 4250.44 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1437.54 | 0.00 |
June | 18375.01 | 22-JUN-06:02 | 0.00 | 1118.54 | 187.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.24 |
July | 25806.07 | 27-JUL-06:01 | 0.00 | 1565.95 | 262.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.52 |
August | 24729.06 | 12-AUG-06:02 | 0.00 | 1342.24 | 224.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.90 |
September | 23517.30 | 04-SEP-07:02 | 0.00 | 1342.24 | 224.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 183.21 |
October | 6026.92 | 18-OCT-14:00 | 539.93 | 4250.44 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 267.59 | 0.00 |
November | 3917.21 | 11-NOV-10:13 | 539.93 | 12751.32 | 2022.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1096.59 |
December | 4518.56 | 12-DEC-20:53 | 359.95 | 8948.30 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.01 |
Annual Sum or Average | |||||||||||
Minimum of Months | 2236.78 | 0.00 | 1118.54 | 187.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 25806.07 | 899.88 | 22370.74 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 1437.54 | 1096.59 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2311.46 | 14-JAN-12:00 | 2087.73 | 6064.13 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 938.45 |
February | 7589.50 | 23-FEB-11:43 | 4643.40 | 18192.39 | 4044.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1869.58 |
March | 6094.21 | 31-MAR-19:13 | 1187.85 | 9574.94 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 210.91 |
April | 4200.21 | 07-APR-14:10 | 2483.68 | 6064.13 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 372.43 |
May | 11531.39 | 20-MAY-16:00 | 2663.65 | 6064.13 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 2528.77 | 0.00 |
June | 23494.95 | 22-JUN-07:03 | 0.00 | 1276.66 | 299.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 306.48 |
July | 38759.37 | 27-JUL-07:01 | 0.00 | 2234.15 | 524.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 679.92 |
August | 37146.46 | 07-AUG-07:02 | 0.00 | 1595.82 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 135.82 |
September | 41015.42 | 05-SEP-07:02 | 0.00 | 1914.99 | 449.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 416.31 |
October | 10045.73 | 18-OCT-14:30 | 2483.68 | 6064.13 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 470.86 | 0.00 |
November | 4620.58 | 06-NOV-11:10 | 1547.80 | 6064.13 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1159.45 |
December | 2913.39 | 19-DEC-20:15 | 791.90 | 6383.30 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 325.66 |
Annual Sum or Average | |||||||||||
Minimum of Months | 2311.46 | 0.00 | 1276.66 | 299.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 41015.42 | 4643.40 | 18192.39 | 4044.77 | 0.00 | 0.00 | 0.00 | 0.00 | 2528.77 | 1869.58 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1926.18 | 02-JAN-19:35 | 935.88 | 6064.13 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 794.45 |
February | 2077.38 | 27-FEB-20:20 | 197.97 | 1595.82 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 158.72 |
March | 2857.35 | 31-MAR-17:33 | 1835.76 | 9096.20 | 2022.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 916.26 |
April | 2038.90 | 25-APR-17:10 | 611.92 | 3032.07 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 259.17 |
May | 6011.76 | 20-MAY-16:00 | 1331.82 | 3032.07 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1437.56 | 0.00 |
June | 10442.34 | 22-JUN-07:03 | 0.00 | 638.33 | 149.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 172.95 |
July | 19516.09 | 17-JUL-07:02 | 0.00 | 957.49 | 224.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.85 |
August | 20139.86 | 07-AUG-07:02 | 0.00 | 797.91 | 187.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.87 |
September | 22282.97 | 05-SEP-07:02 | 0.00 | 957.49 | 224.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 227.77 |
October | 5174.03 | 18-OCT-14:40 | 1241.83 | 3032.07 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 267.42 | 0.00 |
November | 2960.05 | 25-NOV-11:23 | 3131.58 | 9096.20 | 2022.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1012.68 |
December | 2093.33 | 08-DEC-11:35 | 1547.79 | 6064.13 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 740.12 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1926.18 | 0.00 | 638.33 | 149.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 22282.97 | 3131.58 | 9096.20 | 2022.38 | 0.00 | 0.00 | 0.00 | 0.00 | 1437.56 | 1012.68 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1695.59 | 02-JAN-11:25 | 1547.79 | 6064.13 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 712.00 |
February | 2466.51 | 16-FEB-18:05 | 1223.84 | 6064.13 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 954.27 |
March | 2658.59 | 24-MAR-10:33 | 2321.69 | 9096.20 | 2022.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 826.65 |
April | 2222.19 | 29-APR-10:45 | 2087.72 | 6064.13 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 816.31 |
May | 5902.33 | 20-MAY-16:00 | 1331.82 | 3032.07 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1437.56 | 0.00 |
June | 9672.93 | 22-JUN-07:03 | 0.00 | 638.33 | 149.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 172.69 |
July | 19441.39 | 17-JUL-07:02 | 0.00 | 957.49 | 224.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.09 |
August | 20072.22 | 07-AUG-07:02 | 0.00 | 797.91 | 187.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.92 |
September | 22207.72 | 05-SEP-07:02 | 0.00 | 957.49 | 224.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 225.98 |
October | 5055.94 | 18-OCT-14:40 | 1241.83 | 3032.07 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 267.42 | 0.00 |
November | 2606.85 | 20-NOV-18:15 | 1223.84 | 6064.13 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 797.01 |
December | 2775.57 | 20-DEC-18:43 | 1835.76 | 9096.20 | 2022.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 861.08 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1695.59 | 0.00 | 638.33 | 149.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 22207.72 | 2321.69 | 9096.20 | 2022.38 | 0.00 | 0.00 | 0.00 | 0.00 | 1437.56 | 954.27 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 889.61 | 14-JAN-12:00 | 1043.86 | 3032.07 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 516.90 |
February | 1741.43 | 27-FEB-19:40 | 467.94 | 3032.07 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 724.61 |
March | 2190.50 | 21-MAR-17:20 | 1223.84 | 6064.13 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 816.18 |
April | 2192.26 | 14-APR-10:45 | 1547.79 | 6064.13 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 791.83 |
May | 5658.01 | 20-MAY-16:00 | 1331.82 | 3032.07 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1437.56 | 0.00 |
June | 7484.64 | 22-JUN-07:03 | 0.00 | 638.33 | 149.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 171.92 |
July | 19408.40 | 17-JUL-07:02 | 0.00 | 957.49 | 224.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.21 |
August | 20074.24 | 07-AUG-07:02 | 0.00 | 797.91 | 187.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.69 |
September | 22221.49 | 05-SEP-07:02 | 0.00 | 957.49 | 224.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 220.59 |
October | 4784.22 | 18-OCT-14:40 | 1241.83 | 3032.07 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 267.42 | 0.00 |
November | 2171.90 | 22-NOV-20:15 | 395.95 | 3191.65 | 749.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.31 |
December | 1681.33 | 20-DEC-11:15 | 1547.79 | 6064.13 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 759.71 |
Annual Sum or Average | |||||||||||
Minimum of Months | 889.61 | 0.00 | 638.33 | 149.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 22221.49 | 1547.79 | 6064.13 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 1437.56 | 816.18 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 85.39 | 14-JAN-12:00 | 1043.86 | 3032.07 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 711.24 |
February | 1783.39 | 27-FEB-20:35 | 395.95 | 3191.65 | 749.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 314.63 |
March | 722.43 | 28-MAR-17:10 | 1223.84 | 6064.13 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 769.27 |
April | 1123.62 | 26-APR-18:20 | 467.94 | 3032.07 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 670.15 |
May | 5244.54 | 20-MAY-16:00 | 1331.82 | 3032.07 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1519.39 | 0.00 |
June | 7248.23 | 23-JUN-14:00 | 899.88 | 3032.07 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1848.42 | 0.00 |
July | 20714.07 | 17-JUL-07:02 | 0.00 | 957.49 | 224.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.96 |
August | 15723.02 | 07-AUG-07:02 | 0.00 | 797.91 | 187.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.68 |
September | 22372.29 | 05-SEP-07:02 | 0.00 | 957.49 | 224.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 239.85 |
October | 4372.84 | 18-OCT-14:40 | 1241.83 | 3032.07 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 284.82 | 0.00 |
November | 2166.98 | 10-NOV-18:45 | 1223.84 | 6064.13 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 919.51 |
December | 0.00 | 01-DEC-00:03 | 0.00 | 478.75 | 112.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2429.45 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 478.75 | 112.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 22372.29 | 1331.82 | 6064.13 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 1848.42 | 2429.45 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | |
January | 0.113675E+12 | 90429.24 | 07-JAN-16:49 | 0.206986E+12 | 385434.51 | 08-JAN-17:00 |
February | 0.101847E+12 | 87718.48 | 13-FEB-17:49 | 0.111848E+12 | 295661.88 | 05-FEB-17:00 |
March | 0.112713E+12 | 84463.56 | 09-MAR-18:49 | 0.838611E+11 | 270302.54 | 04-MAR-17:00 |
April | 0.106756E+12 | 85910.89 | 07-APR-13:00 | 0.278453E+11 | 135399.62 | 29-APR-07:10 |
May | 0.112904E+12 | 109534.73 | 20-MAY-16:19 | 0.180694E+11 | 136495.92 | 08-MAY-07:10 |
June | 0.120830E+12 | 118945.21 | 23-JUN-13:00 | 0.392106E+09 | 24978.70 | 16-JUN-11:20 |
July | 0.137608E+12 | 135613.27 | 17-JUL-15:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.134485E+12 | 127474.84 | 05-AUG-15:39 | 29451678.11 | 5770.91 | 18-AUG-07:10 |
September | 0.118869E+12 | 129576.15 | 03-SEP-14:09 | 0.252647E+10 | 49554.37 | 20-SEP-07:10 |
October | 0.112949E+12 | 104831.75 | 18-OCT-14:20 | 0.112186E+11 | 123974.57 | 10-OCT-07:10 |
November | 0.109493E+12 | 86173.64 | 30-NOV-17:00 | 0.604592E+11 | 242849.65 | 26-NOV-17:00 |
December | 0.113521E+12 | 86174.83 | 05-DEC-17:00 | 0.145497E+12 | 335564.22 | 31-DEC-17:00 |
Annual Sum or Average | 0.139565E+13 | 0.668733E+12 | ||||
Minimum of Months | 0.101847E+12 | 84463.56 | 0.00 | 0.00 | ||
Maximum of Months | 0.137608E+12 | 135613.27 | 0.206986E+12 | 385434.51 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.595337E+11 | 0.119935E+11 | 0.108804E+11 | 0.00 | 0.254754E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.579166E+10 | 0.00 |
February | 0.539017E+11 | 0.990862E+10 | 0.985143E+10 | 0.00 | 0.229196E+11 | 0.00 | 0.00 | 1354686.84 | 0.00 | 0.00 | 0.00 | 0.526476E+10 | 0.00 |
March | 0.604219E+11 | 0.967602E+10 | 0.110523E+11 | 0.00 | 0.257178E+11 | 0.00 | 0.00 | 184147.46 | 0.00 | 0.00 | 0.00 | 0.584466E+10 | 0.00 |
April | 0.577706E+11 | 0.805630E+10 | 0.105581E+11 | 0.00 | 0.246603E+11 | 0.00 | 0.00 | 0.173783E+09 | 0.00 | 0.00 | 0.00 | 0.553674E+10 | 0.00 |
May | 0.599558E+11 | 0.716398E+10 | 0.109629E+11 | 0.00 | 0.257669E+11 | 0.00 | 0.00 | 0.343315E+10 | 0.00 | 0.00 | 0.00 | 0.562158E+10 | 0.00 |
June | 0.584038E+11 | 0.632663E+10 | 0.106818E+11 | 0.00 | 0.252193E+11 | 0.00 | 0.00 | 0.148651E+11 | 0.00 | 0.00 | 0.00 | 0.533329E+10 | 0.00 |
July | 0.593665E+11 | 0.681720E+10 | 0.108460E+11 | 0.00 | 0.255231E+11 | 0.00 | 0.00 | 0.296716E+11 | 0.00 | 0.00 | 0.00 | 0.538332E+10 | 0.00 |
August | 0.603780E+11 | 0.780256E+10 | 0.110454E+11 | 0.00 | 0.260436E+11 | 0.00 | 0.00 | 0.238157E+11 | 0.00 | 0.00 | 0.00 | 0.539965E+10 | 0.00 |
September | 0.578145E+11 | 0.879215E+10 | 0.105649E+11 | 0.00 | 0.249163E+11 | 0.00 | 0.00 | 0.115511E+11 | 0.00 | 0.00 | 0.00 | 0.523004E+10 | 0.00 |
October | 0.595337E+11 | 0.104288E+11 | 0.108804E+11 | 0.00 | 0.255062E+11 | 0.00 | 0.00 | 0.112004E+10 | 0.00 | 0.00 | 0.00 | 0.547934E+10 | 0.00 |
November | 0.576828E+11 | 0.112746E+11 | 0.105443E+11 | 0.00 | 0.245609E+11 | 0.00 | 0.00 | 6402121.08 | 0.00 | 0.00 | 0.00 | 0.542404E+10 | 0.00 |
December | 0.594104E+11 | 0.123276E+11 | 0.108529E+11 | 0.00 | 0.252188E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.571129E+10 | 0.00 |
Annual Sum or Average | 0.704173E+12 | 0.110568E+12 | 0.128721E+12 | 0.301528E+12 | 0.00 | 0.846383E+11 | 0.660204E+11 | ||||||
Minimum of Months | 0.539017E+11 | 0.632663E+10 | 0.985143E+10 | 0.00 | 0.229196E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.523004E+10 | 0.00 |
Maximum of Months | 0.604219E+11 | 0.123276E+11 | 0.110523E+11 | 0.00 | 0.260436E+11 | 0.00 | 0.00 | 0.296716E+11 | 0.00 | 0.00 | 0.00 | 0.584466E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS [J] | COOLING:GAS [] | WATERSYSTEMS:GAS [] | COGENERATION:GAS [] | HUMIDIFIER:GAS [] | |
January | 0.00 | 0.00 | 0.206986E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.111848E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.838611E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.278453E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.180694E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.392106E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 29451678.11 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.252647E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.112186E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.604592E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.145497E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.668733E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.206986E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum}[W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum}[W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum}[W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum}[W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 43812.60 | 01-JAN-11:09 | 7048.38 | 01-JAN-00:10 | 8089.53 | 01-JAN-11:09 | 0.00 | 17525.53 | 12-JAN-14:50 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 43812.60 | 01-FEB-10:09 | 7048.38 | 01-FEB-00:10 | 8089.53 | 01-FEB-10:09 | 0.00 | 17525.53 | 03-FEB-09:30 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 43812.60 | 01-MAR-10:09 | 7048.38 | 01-MAR-00:10 | 8089.53 | 01-MAR-10:09 | 0.00 | 17525.53 | 07-MAR-09:50 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 43812.60 | 01-APR-09:09 | 7048.38 | 01-APR-00:10 | 8089.53 | 01-APR-09:09 | 0.00 | 17525.53 | 18-APR-10:50 | 0.00 | 0.00 | 01-APR-00:10 |
May | 43812.60 | 01-MAY-09:09 | 7048.38 | 01-MAY-00:10 | 8089.53 | 01-MAY-09:09 | 0.00 | 17525.53 | 02-MAY-18:49 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 43812.60 | 01-JUN-09:09 | 7048.38 | 01-JUN-00:10 | 8089.53 | 01-JUN-09:09 | 0.00 | 17525.53 | 01-JUN-15:09 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 43812.60 | 01-JUL-09:09 | 7048.38 | 01-JUL-00:10 | 8089.53 | 01-JUL-09:09 | 0.00 | 17525.53 | 06-JUL-12:30 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 43812.60 | 01-AUG-09:09 | 7048.38 | 01-AUG-00:10 | 8089.53 | 01-AUG-09:09 | 0.00 | 17525.53 | 02-AUG-12:30 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 43812.60 | 01-SEP-09:09 | 7048.38 | 01-SEP-00:10 | 8089.53 | 01-SEP-09:09 | 0.00 | 17525.53 | 08-SEP-17:00 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 43812.60 | 01-OCT-10:09 | 7048.38 | 01-OCT-00:10 | 8089.53 | 01-OCT-10:09 | 0.00 | 17525.53 | 04-OCT-11:39 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 43812.60 | 01-NOV-09:09 | 7048.38 | 01-NOV-00:10 | 8089.53 | 01-NOV-09:09 | 0.00 | 17525.53 | 16-NOV-09:30 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 43812.60 | 01-DEC-10:09 | 7048.38 | 01-DEC-00:10 | 8089.53 | 01-DEC-10:09 | 0.00 | 17525.53 | 01-DEC-09:50 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 43812.60 | 7048.38 | 8089.53 | 0.00 | 17525.53 | 0.00 | 0.00 | |||||
Maximum of Months | 43812.60 | 7048.38 | 8089.53 | 0.00 | 17525.53 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum}[W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum}[W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 14011.43 | 07-JAN-14:09 | 0.00 |
February | 310.45 | 28-FEB-22:30 | 0.00 | 0.00 | 0.00 | 11242.43 | 13-FEB-17:49 | 0.00 |
March | 74.10 | 23-MAR-21:19 | 0.00 | 0.00 | 0.00 | 11839.07 | 28-MAR-12:00 | 0.00 |
April | 12219.48 | 07-APR-13:00 | 0.00 | 0.00 | 0.00 | 9722.08 | 13-APR-11:30 | 0.00 |
May | 34897.72 | 20-MAY-15:00 | 0.00 | 0.00 | 0.00 | 11809.30 | 30-MAY-16:10 | 0.00 |
June | 43331.58 | 29-JUN-14:00 | 0.00 | 0.00 | 0.00 | 9722.43 | 14-JUN-13:09 | 0.00 |
July | 60739.89 | 17-JUL-15:00 | 0.00 | 0.00 | 0.00 | 11370.78 | 01-JUL-11:20 | 0.00 |
August | 54857.25 | 06-AUG-15:00 | 0.00 | 0.00 | 0.00 | 9675.82 | 23-AUG-16:10 | 0.00 |
September | 52690.52 | 02-SEP-14:00 | 0.00 | 0.00 | 0.00 | 10228.07 | 19-SEP-11:20 | 0.00 |
October | 25757.52 | 18-OCT-14:39 | 0.00 | 0.00 | 0.00 | 11796.49 | 31-OCT-18:30 | 0.00 |
November | 2419.45 | 04-NOV-18:10 | 0.00 | 0.00 | 0.00 | 11179.24 | 30-NOV-14:00 | 0.00 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 10215.55 | 08-DEC-14:39 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 9675.82 | 0.00 | ||
Maximum of Months | 60739.89 | 0.00 | 0.00 | 0.00 | 14011.43 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 90429.24 | 07-JAN-16:49 | 43812.60 | 8089.53 | 7048.38 | 0.00 | 17525.53 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 87718.48 | 13-FEB-17:49 | 43812.60 | 8089.53 | 7048.38 | 0.00 | 17525.53 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 84463.56 | 09-MAR-18:49 | 43812.60 | 8089.53 | 7048.38 | 0.00 | 17525.53 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 85910.89 | 07-APR-13:00 | 43812.60 | 8089.53 | 0.00 | 0.00 | 17525.53 | 0.00 | 0.00 | 12219.48 | 0.00 |
May | 109534.73 | 20-MAY-16:19 | 43812.60 | 8089.53 | 0.00 | 0.00 | 17525.53 | 0.00 | 0.00 | 33667.06 | 0.00 |
June | 118945.21 | 23-JUN-13:00 | 43812.60 | 8089.53 | 0.00 | 0.00 | 17525.53 | 0.00 | 0.00 | 42685.97 | 0.00 |
July | 135613.27 | 17-JUL-15:00 | 43812.60 | 8089.53 | 0.00 | 0.00 | 17525.53 | 0.00 | 0.00 | 60739.89 | 0.00 |
August | 127474.84 | 05-AUG-15:39 | 43812.60 | 8089.53 | 0.00 | 0.00 | 17525.53 | 0.00 | 0.00 | 52600.75 | 0.00 |
September | 129576.15 | 03-SEP-14:09 | 43812.60 | 8089.53 | 0.00 | 0.00 | 17525.53 | 0.00 | 0.00 | 51101.60 | 0.00 |
October | 104831.75 | 18-OCT-14:20 | 43812.60 | 8089.53 | 0.00 | 0.00 | 17525.53 | 0.00 | 0.00 | 25709.36 | 0.00 |
November | 86173.64 | 30-NOV-17:00 | 43812.60 | 8089.53 | 7048.38 | 0.00 | 17525.53 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 86174.83 | 05-DEC-17:00 | 43812.60 | 8089.53 | 7048.38 | 0.00 | 17525.53 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 84463.56 | 43812.60 | 8089.53 | 0.00 | 0.00 | 17525.53 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 135613.27 | 43812.60 | 8089.53 | 7048.38 | 0.00 | 17525.53 | 0.00 | 0.00 | 60739.89 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS {Maximum}[W] | HEATING:GAS {TIMESTAMP} | COOLING:GAS [] | WATERSYSTEMS:GAS [] | COGENERATION:GAS [] | |
January | 0.00 | 0.00 | 385434.51 | 08-JAN-17:00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 295661.88 | 05-FEB-17:00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 270302.54 | 04-MAR-17:00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 135399.62 | 29-APR-07:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 136495.92 | 08-MAY-07:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 24978.70 | 16-JUN-11:20 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 5770.91 | 18-AUG-07:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 49554.37 | 20-SEP-07:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 123974.57 | 10-OCT-07:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 242849.65 | 26-NOV-17:00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 335564.22 | 31-DEC-17:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 385434.51 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 6.00 | 19.01 | 1.67 | 20.28 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 2.50 | 20.35 | 0.67 | 20.36 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 1.33 | 20.31 | 0.33 | 20.25 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.33 | 20.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.17 | 20.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.83 | 20.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 2.17 | 19.52 | 0.33 | 20.27 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 13.33 | 19.62 | 3.00 | 20.29 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 6.00 | 20.55 | 1.67 | 20.36 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.00 | 20.29 | 1.00 | 20.35 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.50 | 20.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.17 | 20.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.33 | 20.35 | 0.17 | 20.28 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4.00 | 20.32 | 1.17 | 20.34 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3.00 | 20.47 | 1.00 | 20.35 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.50 | 20.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.17 | 20.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.33 | 20.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.17 | 20.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2.17 | 20.33 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.50 | 20.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.00 | 19.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.50 | 20.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.33 | 20.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.50 | 20.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3.33 | 20.09 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.00 | 20.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.33 | 19.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.50 | 20.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.33 | 20.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.17 | 20.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.50 | 20.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3.83 | 19.84 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.33 | 20.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 6.83 | 17.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 1.67 | 19.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.67 | 19.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.50 | 20.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 2.33 | 18.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 12.00 | 17.89 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 6.83 | 20.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 6.00 | 17.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 1.50 | 19.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 1.00 | 17.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.50 | 20.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 2.00 | 18.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 11.00 | 18.11 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 6.00 | 20.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 6.50 | 17.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 1.50 | 19.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.67 | 19.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.50 | 20.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 2.00 | 18.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 11.17 | 18.04 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 6.50 | 20.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 8.00 | 16.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 1.50 | 19.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 1.00 | 17.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.50 | 20.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 2.50 | 18.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 13.50 | 17.61 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 8.00 | 20.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 38.33 | 15.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 14.83 | 16.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 11.50 | 16.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.50 | 20.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.67 | 19.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.17 | 20.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5.17 | 16.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 17.33 | 15.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 88.50 | 15.80 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 38.33 | 20.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: LGSTORE1
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 496.00 | 21.06 | 373.50 | 21.04 | 373.50 | 21.04 |
February | 448.00 | 21.25 | 208.50 | 21.00 | 208.50 | 21.00 |
March | 496.00 | 21.16 | 159.50 | 21.02 | 159.50 | 21.02 |
April | 459.67 | 22.02 | 45.67 | 21.01 | 45.67 | 21.01 |
May | 317.50 | 22.16 | 54.17 | 22.71 | 22.83 | 21.09 |
June | 68.67 | 23.14 | 208.83 | 23.89 | 0.00 | 0.00 |
July | 14.00 | 23.80 | 354.83 | 23.89 | 1.83 | 23.89 |
August | 39.33 | 23.33 | 285.00 | 23.89 | 0.00 | 0.00 |
September | 136.33 | 22.53 | 181.00 | 23.88 | 6.00 | 23.68 |
October | 324.67 | 22.32 | 7.17 | 21.18 | 7.17 | 21.18 |
November | 475.33 | 21.67 | 114.83 | 21.11 | 114.83 | 21.11 |
December | 496.00 | 21.07 | 310.67 | 21.03 | 310.67 | 21.03 |
Annual Sum or Average | 3771.50 | 21.62 | 2303.67 | 22.35 | 1250.50 | 21.05 |
Minimum of Months | 14.00 | 21.06 | 7.17 | 21.00 | 0.00 | 0.00 |
Maximum of Months | 496.00 | 23.80 | 373.50 | 23.89 | 373.50 | 23.89 |
Report: ComfortReportSimple55Monthly
For: SMSTORE1
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 496.00 | 21.34 | 274.50 | 21.10 | 274.50 | 21.10 |
February | 445.00 | 21.73 | 139.67 | 21.11 | 139.67 | 21.11 |
March | 496.00 | 21.80 | 80.67 | 21.13 | 80.67 | 21.13 |
April | 413.83 | 22.61 | 6.50 | 21.16 | 6.50 | 21.16 |
May | 285.33 | 22.62 | 44.67 | 23.54 | 5.67 | 21.20 |
June | 52.83 | 23.29 | 197.00 | 23.86 | 0.00 | 0.00 |
July | 13.00 | 23.46 | 336.83 | 23.86 | 0.00 | 0.00 |
August | 29.33 | 23.33 | 276.17 | 23.88 | 0.00 | 0.00 |
September | 111.83 | 22.91 | 184.50 | 23.87 | 5.50 | 23.89 |
October | 275.00 | 22.80 | 1.83 | 21.25 | 1.83 | 21.25 |
November | 457.67 | 22.19 | 50.00 | 21.14 | 50.00 | 21.14 |
December | 496.00 | 21.45 | 157.83 | 21.10 | 157.83 | 21.10 |
Annual Sum or Average | 3571.83 | 22.04 | 1750.17 | 22.74 | 722.17 | 21.13 |
Minimum of Months | 13.00 | 21.34 | 1.83 | 21.10 | 0.00 | 0.00 |
Maximum of Months | 496.00 | 23.46 | 336.83 | 23.88 | 274.50 | 23.89 |
Report: ComfortReportSimple55Monthly
For: SMSTORE2
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 371.00 | 21.11 | 247.00 | 21.11 | 247.00 | 21.11 |
February | 336.00 | 21.37 | 132.83 | 21.11 | 132.83 | 21.11 |
March | 379.00 | 21.30 | 93.83 | 21.11 | 93.83 | 21.11 |
April | 321.33 | 22.09 | 12.50 | 21.11 | 12.50 | 21.11 |
May | 228.17 | 22.19 | 41.83 | 23.72 | 8.83 | 21.11 |
June | 36.67 | 22.96 | 178.50 | 24.16 | 0.33 | 27.46 |
July | 7.00 | 25.46 | 293.33 | 24.16 | 2.50 | 28.63 |
August | 20.67 | 23.77 | 253.33 | 24.16 | 2.00 | 28.84 |
September | 98.17 | 22.66 | 151.17 | 24.14 | 7.50 | 25.13 |
October | 218.50 | 22.27 | 3.83 | 22.49 | 2.67 | 21.11 |
November | 351.50 | 21.71 | 63.17 | 21.11 | 63.17 | 21.11 |
December | 369.00 | 21.13 | 192.00 | 21.11 | 192.00 | 21.11 |
Annual Sum or Average | 2737.00 | 21.66 | 1663.33 | 22.78 | 765.17 | 21.20 |
Minimum of Months | 7.00 | 21.11 | 3.83 | 21.11 | 0.33 | 21.11 |
Maximum of Months | 379.00 | 25.46 | 293.33 | 24.16 | 247.00 | 28.84 |
Report: ComfortReportSimple55Monthly
For: SMSTORE3
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 371.00 | 21.11 | 265.33 | 21.11 | 265.33 | 21.11 |
February | 336.00 | 21.34 | 144.33 | 21.11 | 144.33 | 21.11 |
March | 379.00 | 21.26 | 105.33 | 21.11 | 105.33 | 21.11 |
April | 332.00 | 22.06 | 18.00 | 21.11 | 18.00 | 21.11 |
May | 233.17 | 22.15 | 42.67 | 23.53 | 11.83 | 21.11 |
June | 37.00 | 22.92 | 177.00 | 24.16 | 0.17 | 27.55 |
July | 7.33 | 25.38 | 294.17 | 24.16 | 2.50 | 28.64 |
August | 21.67 | 23.80 | 253.17 | 24.16 | 2.17 | 28.78 |
September | 103.83 | 22.65 | 149.00 | 24.14 | 7.50 | 25.13 |
October | 228.17 | 22.25 | 4.67 | 22.07 | 3.67 | 21.11 |
November | 354.33 | 21.65 | 71.67 | 21.11 | 71.67 | 21.11 |
December | 369.00 | 21.12 | 205.33 | 21.11 | 205.33 | 21.11 |
Annual Sum or Average | 2772.50 | 21.64 | 1730.67 | 22.71 | 837.83 | 21.19 |
Minimum of Months | 7.33 | 21.11 | 4.67 | 21.11 | 0.17 | 21.11 |
Maximum of Months | 379.00 | 25.38 | 294.17 | 24.16 | 265.33 | 28.78 |
Report: ComfortReportSimple55Monthly
For: SMSTORE4
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 371.00 | 21.11 | 289.67 | 21.11 | 289.67 | 21.11 |
February | 336.00 | 21.30 | 161.17 | 21.11 | 161.17 | 21.11 |
March | 379.00 | 21.22 | 120.00 | 21.11 | 120.00 | 21.11 |
April | 343.17 | 22.01 | 26.83 | 21.11 | 26.83 | 21.11 |
May | 245.50 | 22.13 | 40.17 | 23.20 | 15.67 | 21.11 |
June | 42.17 | 22.94 | 170.17 | 24.16 | 0.17 | 27.44 |
July | 7.50 | 25.11 | 287.33 | 24.16 | 2.17 | 28.69 |
August | 26.33 | 23.68 | 238.67 | 24.17 | 2.00 | 28.81 |
September | 111.50 | 22.61 | 144.50 | 24.14 | 7.33 | 25.15 |
October | 246.50 | 22.22 | 7.00 | 21.64 | 6.17 | 21.11 |
November | 356.00 | 21.56 | 89.33 | 21.11 | 89.33 | 21.11 |
December | 369.00 | 21.12 | 221.67 | 21.11 | 221.67 | 21.11 |
Annual Sum or Average | 2833.67 | 21.62 | 1796.50 | 22.58 | 942.17 | 21.18 |
Minimum of Months | 7.50 | 21.11 | 7.00 | 21.11 | 0.17 | 21.11 |
Maximum of Months | 379.00 | 25.11 | 289.67 | 24.17 | 289.67 | 28.81 |
Report: ComfortReportSimple55Monthly
For: LGSTORE2
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.11 | 309.83 | 21.11 | 309.83 | 21.11 |
February | 308.00 | 21.22 | 211.83 | 21.11 | 211.83 | 21.11 |
March | 348.00 | 21.14 | 153.17 | 21.11 | 153.17 | 21.11 |
April | 330.00 | 21.86 | 42.17 | 21.11 | 42.17 | 21.11 |
May | 250.00 | 22.06 | 45.83 | 22.26 | 28.83 | 21.11 |
June | 52.50 | 23.03 | 128.33 | 23.99 | 0.00 | 0.00 |
July | 7.33 | 24.67 | 235.50 | 24.01 | 1.50 | 28.77 |
August | 26.50 | 23.31 | 170.67 | 24.00 | 1.33 | 29.01 |
September | 127.00 | 22.59 | 115.83 | 24.05 | 7.67 | 24.81 |
October | 280.50 | 22.26 | 8.00 | 21.11 | 8.00 | 21.11 |
November | 330.00 | 21.36 | 121.17 | 21.11 | 121.17 | 21.11 |
December | 338.00 | 21.11 | 264.33 | 21.11 | 264.33 | 21.11 |
Annual Sum or Average | 2737.83 | 21.59 | 1806.67 | 22.18 | 1149.83 | 21.15 |
Minimum of Months | 7.33 | 21.11 | 8.00 | 21.11 | 0.00 | 0.00 |
Maximum of Months | 348.00 | 24.67 | 309.83 | 24.05 | 309.83 | 29.01 |
Report: ComfortReportSimple55Monthly
For: SMSTORE5
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.11 | 310.83 | 21.11 | 310.83 | 21.11 |
February | 308.00 | 21.22 | 218.83 | 21.11 | 218.83 | 21.11 |
March | 348.00 | 21.14 | 161.33 | 21.11 | 161.33 | 21.11 |
April | 330.00 | 21.84 | 47.50 | 21.11 | 47.50 | 21.11 |
May | 263.17 | 22.14 | 45.17 | 22.06 | 31.67 | 21.11 |
June | 65.83 | 23.21 | 107.00 | 24.01 | 0.00 | 0.00 |
July | 9.00 | 24.44 | 212.83 | 24.02 | 1.33 | 28.72 |
August | 30.33 | 23.32 | 140.33 | 24.02 | 1.00 | 29.04 |
September | 138.00 | 22.68 | 102.83 | 24.06 | 7.83 | 24.57 |
October | 294.50 | 22.33 | 10.33 | 21.11 | 10.33 | 21.11 |
November | 330.00 | 21.36 | 128.33 | 21.11 | 128.33 | 21.11 |
December | 338.00 | 21.11 | 267.67 | 21.11 | 267.67 | 21.11 |
Annual Sum or Average | 2794.83 | 21.63 | 1753.00 | 22.07 | 1186.67 | 21.15 |
Minimum of Months | 9.00 | 21.11 | 10.33 | 21.11 | 0.00 | 0.00 |
Maximum of Months | 348.00 | 24.44 | 310.83 | 24.06 | 310.83 | 29.04 |
Report: ComfortReportSimple55Monthly
For: SMSTORE6
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.11 | 313.67 | 21.11 | 313.67 | 21.11 |
February | 308.00 | 21.21 | 226.67 | 21.11 | 226.67 | 21.11 |
March | 348.00 | 21.14 | 169.00 | 21.11 | 169.00 | 21.11 |
April | 330.00 | 21.81 | 53.33 | 21.11 | 53.33 | 21.11 |
May | 266.83 | 22.13 | 47.17 | 21.89 | 35.67 | 21.11 |
June | 75.67 | 23.27 | 103.00 | 24.01 | 0.00 | 0.00 |
July | 9.83 | 24.37 | 207.00 | 24.02 | 1.33 | 28.69 |
August | 32.50 | 23.33 | 132.83 | 24.03 | 1.00 | 29.02 |
September | 144.17 | 22.69 | 99.67 | 24.07 | 7.83 | 24.56 |
October | 300.83 | 22.32 | 11.33 | 21.11 | 11.33 | 21.11 |
November | 330.00 | 21.34 | 134.00 | 21.11 | 134.00 | 21.11 |
December | 338.00 | 21.11 | 272.17 | 21.11 | 272.17 | 21.11 |
Annual Sum or Average | 2823.83 | 21.63 | 1769.83 | 22.02 | 1226.00 | 21.15 |
Minimum of Months | 9.83 | 21.11 | 11.33 | 21.11 | 0.00 | 0.00 |
Maximum of Months | 348.00 | 24.37 | 313.67 | 24.07 | 313.67 | 29.02 |
Report: ComfortReportSimple55Monthly
For: SMSTORE7
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.11 | 317.50 | 21.11 | 317.50 | 21.11 |
February | 308.00 | 21.19 | 245.67 | 21.11 | 245.67 | 21.11 |
March | 348.00 | 21.13 | 197.50 | 21.11 | 197.50 | 21.11 |
April | 330.00 | 21.72 | 75.17 | 21.11 | 75.17 | 21.11 |
May | 280.50 | 22.12 | 51.33 | 21.63 | 43.00 | 21.11 |
June | 93.00 | 23.29 | 89.83 | 24.02 | 0.00 | 0.00 |
July | 13.00 | 24.20 | 196.83 | 24.02 | 1.33 | 28.66 |
August | 37.83 | 23.31 | 125.00 | 24.03 | 1.00 | 29.00 |
September | 151.17 | 22.65 | 94.67 | 24.05 | 8.67 | 24.28 |
October | 314.67 | 22.28 | 15.00 | 21.11 | 15.00 | 21.11 |
November | 330.00 | 21.29 | 154.33 | 21.11 | 154.33 | 21.11 |
December | 338.00 | 21.11 | 288.00 | 21.11 | 288.00 | 21.11 |
Annual Sum or Average | 2884.17 | 21.63 | 1850.83 | 21.92 | 1347.17 | 21.14 |
Minimum of Months | 13.00 | 21.11 | 15.00 | 21.11 | 0.00 | 0.00 |
Maximum of Months | 348.00 | 24.20 | 317.50 | 24.05 | 317.50 | 29.00 |
Report: ComfortReportSimple55Monthly
For: SMSTORE8
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.11 | 334.17 | 21.11 | 334.17 | 21.11 |
February | 308.00 | 21.16 | 278.50 | 21.11 | 278.50 | 21.11 |
March | 348.00 | 21.11 | 288.00 | 21.11 | 288.00 | 21.11 |
April | 330.00 | 21.56 | 160.17 | 21.11 | 160.17 | 21.11 |
May | 313.83 | 22.12 | 88.67 | 21.17 | 87.67 | 21.11 |
June | 130.33 | 23.19 | 68.17 | 24.03 | 0.00 | 0.00 |
July | 25.33 | 23.83 | 176.67 | 24.03 | 1.33 | 28.69 |
August | 52.67 | 23.26 | 116.67 | 24.03 | 1.00 | 29.04 |
September | 168.00 | 22.54 | 90.00 | 23.93 | 12.33 | 23.35 |
October | 329.83 | 22.14 | 34.17 | 21.11 | 34.17 | 21.11 |
November | 330.00 | 21.22 | 198.00 | 21.11 | 198.00 | 21.11 |
December | 338.00 | 21.11 | 324.33 | 21.11 | 324.33 | 21.11 |
Annual Sum or Average | 3014.00 | 21.62 | 2157.50 | 21.72 | 1719.67 | 21.14 |
Minimum of Months | 25.33 | 21.11 | 34.17 | 21.11 | 0.00 | 0.00 |
Maximum of Months | 348.00 | 23.83 | 334.17 | 24.03 | 334.17 | 29.04 |
Report: OccupantComfortDataSummaryMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 496.00000 | 21.03612 | 10.45369 | -0.6778 | 15.33295 |
February | 448.00000 | 21.23176 | 13.60268 | -0.5474 | 12.36225 |
March | 496.00000 | 21.14468 | 15.35869 | -0.5198 | 11.19564 |
April | 480.00000 | 22.08651 | 19.93693 | -0.2289 | 7.79828 |
May | 496.00000 | 22.76724 | 23.55400 | -1.0118 | 30.26191 |
June | 480.00000 | 23.78044 | 30.78884 | -0.5252 | 11.67485 |
July | 496.00000 | 23.89103 | 33.64502 | -0.4034 | 8.65022 |
August | 496.00000 | 23.84762 | 30.10576 | -0.4563 | 9.83122 |
September | 480.00000 | 23.49900 | 30.96794 | -0.6185 | 15.48548 |
October | 496.00000 | 22.84980 | 22.18627 | 0.02356 | 6.66498 |
November | 480.00000 | 21.66716 | 16.57374 | -0.3585 | 9.19177 |
December | 496.00000 | 21.06040 | 12.73571 | -0.6075 | 13.25777 |
Annual Sum or Average | 5840.00000 | 22.41092 | 21.69346 | -0.4945 | 12.66216 |
Minimum of Months | 448.00000 | 21.03612 | 10.45369 | -1.0118 | 6.66498 |
Maximum of Months | 496.00000 | 23.89103 | 33.64502 | 0.02356 | 30.26191 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 496.00000 | 21.30800 | 11.24242 | -0.5636 | 12.57649 |
February | 448.00000 | 21.71751 | 14.01040 | -0.4015 | 9.86258 |
March | 496.00000 | 21.77280 | 15.88637 | -0.3485 | 8.51847 |
April | 480.00000 | 22.76625 | 19.74374 | -0.0572 | 6.55020 |
May | 496.00000 | 23.12780 | 23.38591 | -0.8732 | 24.00355 |
June | 480.00000 | 23.78112 | 30.66515 | -0.5066 | 10.94655 |
July | 496.00000 | 23.82604 | 33.62103 | -0.4186 | 8.93212 |
August | 496.00000 | 23.81624 | 30.20780 | -0.4579 | 9.72265 |
September | 480.00000 | 23.62921 | 30.76185 | -0.5686 | 13.31356 |
October | 496.00000 | 23.26713 | 21.91773 | 0.12268 | 6.44516 |
November | 480.00000 | 22.24806 | 16.76985 | -0.2119 | 7.65907 |
December | 496.00000 | 21.42647 | 13.48034 | -0.4848 | 10.62873 |
Annual Sum or Average | 5840.00000 | 22.72797 | 21.84246 | -0.3981 | 10.78322 |
Minimum of Months | 448.00000 | 21.30800 | 11.24242 | -0.8732 | 6.44516 |
Maximum of Months | 496.00000 | 23.82604 | 33.62103 | 0.12268 | 24.00355 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 21.11174 | 10.13347 | -0.6323 | 13.78279 |
February | 336.00000 | 21.36882 | 12.99558 | -0.4923 | 11.05588 |
March | 379.00000 | 21.29660 | 15.10144 | -0.4525 | 9.79066 |
April | 360.00000 | 22.28299 | 19.37152 | -0.1616 | 7.23203 |
May | 375.00000 | 22.89565 | 22.88142 | -0.9554 | 28.07473 |
June | 366.00000 | 23.91163 | 30.32251 | -0.4740 | 10.71861 |
July | 369.00000 | 24.06069 | 33.09371 | -0.3527 | 8.19404 |
August | 379.00000 | 24.00310 | 29.75305 | -0.4061 | 9.12365 |
September | 360.00000 | 23.62025 | 30.71364 | -0.5763 | 14.54715 |
October | 371.00000 | 22.95380 | 21.85001 | 0.05496 | 6.67554 |
November | 360.00000 | 21.76470 | 16.38732 | -0.3204 | 8.58981 |
December | 369.00000 | 21.12703 | 12.60528 | -0.5659 | 12.03529 |
Annual Sum or Average | 4395.00000 | 22.54131 | 21.32055 | -0.4452 | 11.67732 |
Minimum of Months | 336.00000 | 21.11174 | 10.13347 | -0.9554 | 6.67554 |
Maximum of Months | 379.00000 | 24.06069 | 33.09371 | 0.05496 | 28.07473 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 21.11096 | 10.13442 | -0.6448 | 14.10388 |
February | 336.00000 | 21.33689 | 13.02247 | -0.5115 | 11.37524 |
March | 379.00000 | 21.26078 | 15.13459 | -0.4716 | 10.11507 |
April | 360.00000 | 22.20360 | 19.46732 | -0.1888 | 7.39829 |
May | 375.00000 | 22.85002 | 22.93573 | -0.9802 | 29.13700 |
June | 366.00000 | 23.90739 | 30.32982 | -0.4773 | 10.81110 |
July | 369.00000 | 24.06040 | 33.09284 | -0.3518 | 8.18562 |
August | 379.00000 | 24.00200 | 29.75558 | -0.4063 | 9.13562 |
September | 360.00000 | 23.60035 | 30.74680 | -0.5862 | 14.94069 |
October | 371.00000 | 22.89762 | 21.92455 | 0.03536 | 6.71328 |
November | 360.00000 | 21.69062 | 16.47352 | -0.3481 | 8.87009 |
December | 369.00000 | 21.12214 | 12.61157 | -0.5798 | 12.36270 |
Annual Sum or Average | 4395.00000 | 22.51200 | 21.35538 | -0.4598 | 11.95497 |
Minimum of Months | 336.00000 | 21.11096 | 10.13442 | -0.9802 | 6.71328 |
Maximum of Months | 379.00000 | 24.06040 | 33.09284 | 0.03536 | 29.13700 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 21.11050 | 10.13539 | -0.6597 | 14.50931 |
February | 336.00000 | 21.29907 | 13.05559 | -0.5346 | 11.79505 |
March | 379.00000 | 21.21838 | 15.17537 | -0.4948 | 10.53716 |
April | 360.00000 | 22.08870 | 19.60738 | -0.2268 | 7.65569 |
May | 375.00000 | 22.77094 | 23.03744 | -1.0207 | 30.82080 |
June | 366.00000 | 23.89144 | 30.35943 | -0.4919 | 11.17019 |
July | 369.00000 | 24.05583 | 33.10861 | -0.3608 | 8.31386 |
August | 379.00000 | 23.99124 | 29.77650 | -0.4178 | 9.36688 |
September | 360.00000 | 23.55600 | 30.83392 | -0.6100 | 15.76026 |
October | 371.00000 | 22.79766 | 22.05928 | 0.00360 | 6.75799 |
November | 360.00000 | 21.58451 | 16.60260 | -0.3847 | 9.25507 |
December | 369.00000 | 21.11614 | 12.61958 | -0.5965 | 12.77560 |
Annual Sum or Average | 4395.00000 | 22.46535 | 21.41701 | -0.4834 | 12.42016 |
Minimum of Months | 336.00000 | 21.11050 | 10.13539 | -1.0207 | 6.75799 |
Maximum of Months | 379.00000 | 24.05583 | 33.10861 | 0.00360 | 30.82080 |
Report: OccupantComfortDataSummaryMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.10996 | 10.77123 | -0.7120 | 15.98983 |
February | 308.00000 | 21.22137 | 13.73248 | -0.5977 | 13.11224 |
March | 348.00000 | 21.14052 | 15.94031 | -0.5507 | 11.64777 |
April | 330.00000 | 21.85295 | 20.48662 | -0.3093 | 8.32568 |
May | 344.00000 | 22.57319 | 23.77098 | -1.1213 | 34.97394 |
June | 336.00000 | 23.78802 | 30.89872 | -0.5450 | 12.27086 |
July | 338.00000 | 23.94872 | 33.58960 | -0.4039 | 8.80828 |
August | 348.00000 | 23.86879 | 30.41854 | -0.4665 | 10.21997 |
September | 330.00000 | 23.41274 | 31.68854 | -0.6748 | 17.83039 |
October | 340.00000 | 22.54729 | 22.98827 | -0.0723 | 6.87560 |
November | 330.00000 | 21.36035 | 17.54525 | -0.4696 | 10.41269 |
December | 338.00000 | 21.11003 | 13.28966 | -0.6495 | 14.14382 |
Annual Sum or Average | 4030.00000 | 22.33680 | 22.14710 | -0.5482 | 13.74748 |
Minimum of Months | 308.00000 | 21.10996 | 10.77123 | -1.1213 | 6.87560 |
Maximum of Months | 348.00000 | 23.94872 | 33.58960 | -0.0723 | 34.97394 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.10990 | 10.70089 | -0.7078 | 15.83737 |
February | 308.00000 | 21.21832 | 13.66830 | -0.6006 | 13.13105 |
March | 348.00000 | 21.14010 | 15.86944 | -0.5582 | 11.79742 |
April | 330.00000 | 21.83414 | 20.43952 | -0.3263 | 8.51313 |
May | 344.00000 | 22.56150 | 23.72788 | -1.1460 | 35.95199 |
June | 336.00000 | 23.78793 | 30.84950 | -0.5717 | 12.87080 |
July | 338.00000 | 23.94915 | 33.53006 | -0.4342 | 9.32571 |
August | 348.00000 | 23.86843 | 30.35857 | -0.4960 | 10.79743 |
September | 330.00000 | 23.40901 | 31.64736 | -0.7016 | 18.54291 |
October | 340.00000 | 22.53657 | 22.93449 | -0.0895 | 6.91017 |
November | 330.00000 | 21.35447 | 17.48141 | -0.4793 | 10.55514 |
December | 338.00000 | 21.11000 | 13.21765 | -0.6488 | 14.10340 |
Annual Sum or Average | 4030.00000 | 22.33229 | 22.08916 | -0.5639 | 14.06063 |
Minimum of Months | 308.00000 | 21.10990 | 10.70089 | -1.1460 | 6.91017 |
Maximum of Months | 348.00000 | 23.94915 | 33.53006 | -0.0895 | 35.95199 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.10990 | 10.70094 | -0.7110 | 15.92744 |
February | 308.00000 | 21.20999 | 13.67617 | -0.6068 | 13.25863 |
March | 348.00000 | 21.13519 | 15.87424 | -0.5646 | 11.94031 |
April | 330.00000 | 21.79923 | 20.48578 | -0.3406 | 8.67887 |
May | 344.00000 | 22.53137 | 23.77514 | -1.1641 | 36.73187 |
June | 336.00000 | 23.78023 | 30.86765 | -0.5810 | 13.12650 |
July | 338.00000 | 23.94774 | 33.53770 | -0.4398 | 9.43162 |
August | 348.00000 | 23.86480 | 30.36558 | -0.5025 | 10.95524 |
September | 330.00000 | 23.39148 | 31.68443 | -0.7131 | 18.95013 |
October | 340.00000 | 22.49515 | 22.99432 | -0.1036 | 6.95576 |
November | 330.00000 | 21.33447 | 17.50791 | -0.4888 | 10.70686 |
December | 338.00000 | 21.11002 | 13.21771 | -0.6531 | 14.21598 |
Annual Sum or Average | 4030.00000 | 22.31816 | 22.11102 | -0.5730 | 14.27335 |
Minimum of Months | 308.00000 | 21.10990 | 10.70094 | -1.1641 | 6.95576 |
Maximum of Months | 348.00000 | 23.94774 | 33.53770 | -0.1036 | 36.73187 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.10996 | 10.70064 | -0.7230 | 16.27849 |
February | 308.00000 | 21.19116 | 13.69280 | -0.6256 | 13.68809 |
March | 348.00000 | 21.12538 | 15.88328 | -0.5834 | 12.38431 |
April | 330.00000 | 21.71538 | 20.59579 | -0.3762 | 9.14509 |
May | 344.00000 | 22.45729 | 23.89211 | -1.2085 | 38.69675 |
June | 336.00000 | 23.75016 | 30.92454 | -0.6052 | 13.86539 |
July | 338.00000 | 23.94340 | 33.55505 | -0.4491 | 9.62630 |
August | 348.00000 | 23.85379 | 30.38503 | -0.5144 | 11.29193 |
September | 330.00000 | 23.34466 | 31.77753 | -0.7390 | 19.94066 |
October | 340.00000 | 22.39577 | 23.13719 | -0.1360 | 7.09922 |
November | 330.00000 | 21.29071 | 17.56487 | -0.5114 | 11.11304 |
December | 338.00000 | 21.11003 | 13.21739 | -0.6672 | 14.60343 |
Annual Sum or Average | 4030.00000 | 22.28306 | 22.16423 | -0.5955 | 14.84600 |
Minimum of Months | 308.00000 | 21.10996 | 10.70064 | -1.2085 | 7.09922 |
Maximum of Months | 348.00000 | 23.94340 | 33.55505 | -0.1360 | 38.69675 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.10997 | 10.59341 | -0.7867 | 18.34437 |
February | 308.00000 | 21.15705 | 13.61587 | -0.6983 | 15.66899 |
March | 348.00000 | 21.11178 | 15.74826 | -0.6572 | 14.33948 |
April | 330.00000 | 21.55217 | 20.67291 | -0.4766 | 10.85985 |
May | 344.00000 | 22.27743 | 24.19920 | -1.3334 | 44.38347 |
June | 336.00000 | 23.63443 | 31.14580 | -0.6823 | 16.50385 |
July | 338.00000 | 23.92434 | 33.59055 | -0.4695 | 10.16191 |
August | 348.00000 | 23.81806 | 30.39981 | -0.5429 | 12.25811 |
September | 330.00000 | 23.22253 | 31.91390 | -0.8072 | 22.75711 |
October | 340.00000 | 22.18083 | 23.32775 | -0.2152 | 7.73692 |
November | 330.00000 | 21.21363 | 17.56459 | -0.5780 | 12.56339 |
December | 338.00000 | 21.10997 | 13.13300 | -0.7292 | 16.45485 |
Annual Sum or Average | 4030.00000 | 22.20178 | 22.21301 | -0.6652 | 16.87316 |
Minimum of Months | 308.00000 | 21.10997 | 10.59341 | -1.3334 | 7.73692 |
Maximum of Months | 348.00000 | 23.92434 | 33.59055 | -0.2152 | 44.38347 |
Report: DXReportMonthly
For: PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 2556.64 | 830.95 | 5.33 | 2556.64 | 0.00 | 0.00 | 0.00 | 27-FEB-15:30 | 0.00 | 01-FEB-00:03 | 0.32 | 27-FEB-15:30 | 0.32 | 27-FEB-15:30 | 0.00 | 27-FEB-15:30 | 0.10 | 27-FEB-15:30 | 0.00 | 01-FEB-00:03 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 0.106951E+09 | 34106016.92 | 46.05 | 0.106951E+09 | 0.00 | 0.00 | 0.24 | 07-APR-14:00 | 0.00 | 01-APR-00:05 | 7266.16 | 07-APR-14:00 | 7266.16 | 07-APR-14:00 | 0.00 | 07-APR-15:10 | 2311.37 | 07-APR-14:00 | 0.00 | 01-APR-00:05 |
May | 0.233953E+10 | 0.737022E+09 | 152.99 | 0.233243E+10 | 7096390.23 | 0.00 | 0.55 | 20-MAY-16:10 | 0.00 | 01-MAY-00:10 | 18258.28 | 20-MAY-16:10 | 18258.28 | 20-MAY-16:10 | 335.56 | 19-MAY-11:20 | 6078.47 | 20-MAY-16:10 | 0.00 | 01-MAY-00:10 |
June | 0.931663E+10 | 0.295325E+10 | 332.76 | 0.893910E+10 | 0.377527E+09 | 0.00 | 0.66 | 29-JUN-15:00 | 0.00 | 01-JUN-00:10 | 22698.12 | 22-JUN-07:03 | 21661.68 | 23-JUN-14:00 | 5606.15 | 22-JUN-07:03 | 7448.29 | 29-JUN-15:00 | 0.00 | 01-JUN-00:10 |
July | 0.185204E+11 | 0.599220E+10 | 435.37 | 0.180643E+11 | 0.456058E+09 | 0.00 | 1.00 | 17-JUL-07:02 | 0.00 | 01-JUL-00:03 | 42131.55 | 19-JUL-07:02 | 39599.28 | 18-JUL-07:02 | 13575.21 | 19-JUL-07:02 | 10364.25 | 17-JUL-16:10 | 0.00 | 01-JUL-00:03 |
August | 0.146969E+11 | 0.475605E+10 | 397.92 | 0.146320E+11 | 64950668.83 | 0.00 | 0.99 | 07-AUG-07:02 | 0.00 | 01-AUG-00:10 | 38344.48 | 07-AUG-07:02 | 38344.48 | 07-AUG-07:02 | 2109.40 | 09-AUG-07:03 | 9658.84 | 07-AUG-07:02 | 0.00 | 01-AUG-00:10 |
September | 0.767095E+10 | 0.243701E+10 | 268.52 | 0.730703E+10 | 0.363922E+09 | 0.00 | 1.00 | 04-SEP-07:02 | 0.00 | 01-SEP-00:10 | 39134.63 | 05-SEP-07:02 | 37663.87 | 04-SEP-07:02 | 13971.72 | 07-SEP-07:02 | 9572.06 | 05-SEP-07:02 | 0.00 | 01-SEP-00:10 |
October | 0.759333E+09 | 0.235842E+09 | 113.34 | 0.759333E+09 | 10.94 | 0.00 | 0.46 | 18-OCT-14:00 | 0.00 | 01-OCT-00:10 | 14828.85 | 18-OCT-14:00 | 14828.85 | 18-OCT-14:00 | 0.01 | 01-OCT-18:00 | 4590.62 | 18-OCT-14:00 | 0.00 | 01-OCT-00:10 |
November | 5285.94 | 1718.01 | 14.24 | 5285.94 | 0.00 | 0.00 | 0.00 | 04-NOV-14:00 | 0.00 | 01-NOV-00:10 | 0.34 | 04-NOV-14:00 | 0.34 | 04-NOV-14:00 | 0.00 | 01-NOV-00:10 | 0.11 | 04-NOV-14:00 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.534107E+11 | 0.171455E+11 | 1766.52 | 0.521412E+11 | 0.126955E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.185204E+11 | 0.599220E+10 | 435.37 | 0.180643E+11 | 0.456058E+09 | 0.00 | 1.00 | 0.00 | 42131.55 | 39599.28 | 13971.72 | 10364.25 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 4144203.72 | 1351974.21 | 10.42 | 4144203.72 | 0.00 | 0.00 | 0.07 | 28-FEB-22:30 | 0.00 | 01-FEB-00:03 | 956.25 | 28-FEB-22:30 | 956.25 | 28-FEB-22:30 | 0.00 | 28-FEB-22:50 | 310.45 | 28-FEB-22:30 | 0.00 | 01-FEB-00:03 |
March | 559030.95 | 184147.46 | 1.83 | 559030.95 | 0.00 | 0.00 | 0.02 | 23-MAR-21:20 | 0.00 | 01-MAR-00:10 | 225.33 | 23-MAR-21:20 | 225.33 | 23-MAR-21:20 | 0.00 | 26-MAR-18:20 | 74.10 | 23-MAR-21:20 | 0.00 | 01-MAR-00:10 |
April | 0.141233E+09 | 39621163.54 | 58.49 | 0.141233E+09 | 0.00 | 0.00 | 1.00 | 06-APR-20:02 | 0.00 | 01-APR-00:05 | 21052.85 | 06-APR-20:02 | 21052.85 | 06-APR-20:02 | 0.00 | 06-APR-16:50 | 4838.89 | 06-APR-20:02 | 0.00 | 01-APR-00:05 |
May | 0.166545E+10 | 0.467474E+09 | 144.28 | 0.165152E+10 | 13931174.54 | 0.00 | 1.00 | 02-MAY-20:05 | 0.00 | 01-MAY-00:10 | 21463.34 | 20-MAY-18:27 | 21463.34 | 20-MAY-18:27 | 3887.95 | 20-MAY-21:40 | 5193.18 | 20-MAY-18:16 | 0.00 | 01-MAY-00:10 |
June | 0.588150E+10 | 0.169496E+10 | 295.85 | 0.563081E+10 | 0.250690E+09 | 0.00 | 1.00 | 03-JUN-18:01 | 0.00 | 01-JUN-00:10 | 22460.23 | 21-JUN-20:01 | 21467.87 | 25-JUN-17:50 | 6229.39 | 21-JUN-22:24 | 5335.67 | 18-JUN-19:11 | 0.00 | 01-JUN-00:10 |
July | 0.109047E+11 | 0.324719E+10 | 378.90 | 0.105867E+11 | 0.317966E+09 | 0.00 | 1.00 | 01-JUL-18:01 | 0.00 | 01-JUL-00:03 | 23129.78 | 18-JUL-21:57 | 21730.60 | 18-JUL-07:02 | 9843.06 | 18-JUL-21:52 | 5326.09 | 18-JUL-20:02 | 0.00 | 01-JUL-00:03 |
August | 0.867691E+10 | 0.258607E+10 | 350.36 | 0.862187E+10 | 55041873.46 | 0.00 | 1.00 | 02-AUG-21:02 | 0.00 | 01-AUG-00:10 | 21754.27 | 08-AUG-22:43 | 21364.64 | 07-AUG-22:01 | 4538.30 | 15-AUG-20:40 | 5228.65 | 08-AUG-22:01 | 0.00 | 01-AUG-00:10 |
September | 0.457470E+10 | 0.134015E+10 | 233.22 | 0.434576E+10 | 0.228945E+09 | 0.00 | 1.00 | 01-SEP-20:01 | 0.00 | 01-SEP-00:10 | 22823.80 | 06-SEP-20:01 | 21433.02 | 24-SEP-17:16 | 8010.25 | 06-SEP-23:00 | 5284.59 | 06-SEP-20:01 | 0.00 | 01-SEP-00:10 |
October | 0.539154E+09 | 0.154163E+09 | 107.17 | 0.539154E+09 | 0.00 | 0.00 | 1.00 | 02-OCT-20:02 | 0.00 | 01-OCT-00:10 | 21052.85 | 02-OCT-20:02 | 21052.85 | 02-OCT-20:02 | 0.00 | 13-OCT-20:02 | 4838.89 | 02-OCT-20:02 | 0.00 | 01-OCT-00:10 |
November | 24823481.98 | 6397125.78 | 25.07 | 24823481.98 | 0.00 | 0.00 | 1.00 | 03-NOV-20:02 | 0.00 | 01-NOV-00:10 | 21052.85 | 03-NOV-20:02 | 21052.85 | 03-NOV-20:02 | 0.00 | 19-NOV-20:30 | 4838.89 | 03-NOV-20:02 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.324132E+11 | 0.953757E+10 | 1605.58 | 0.315466E+11 | 0.866574E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.109047E+11 | 0.324719E+10 | 378.90 | 0.105867E+11 | 0.317966E+09 | 0.00 | 1.00 | 0.00 | 23129.78 | 21730.60 | 9843.06 | 5335.67 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 2315.41 | 709.58 | 7.67 | 2315.41 | 0.00 | 0.00 | 0.00 | 27-FEB-15:30 | 0.00 | 01-FEB-00:03 | 0.17 | 27-FEB-15:30 | 0.17 | 27-FEB-15:30 | 0.00 | 27-FEB-13:00 | 0.05 | 27-FEB-15:30 | 0.00 | 01-FEB-00:03 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 79706723.03 | 23781186.56 | 43.67 | 79706723.03 | 0.00 | 0.00 | 0.27 | 07-APR-14:00 | 0.00 | 01-APR-00:05 | 4571.71 | 07-APR-14:00 | 4571.71 | 07-APR-14:00 | 0.00 | 06-APR-16:20 | 1359.10 | 07-APR-14:00 | 0.00 | 01-APR-00:05 |
May | 0.106814E+10 | 0.317356E+09 | 122.93 | 0.106433E+10 | 3807857.18 | 0.00 | 0.55 | 20-MAY-16:00 | 0.00 | 01-MAY-00:10 | 9982.18 | 20-MAY-16:00 | 9982.18 | 20-MAY-16:00 | 213.28 | 19-MAY-11:00 | 3145.34 | 20-MAY-16:00 | 0.00 | 01-MAY-00:10 |
June | 0.430561E+10 | 0.129075E+10 | 257.84 | 0.414909E+10 | 0.156516E+09 | 0.00 | 1.00 | 22-JUN-06:02 | 0.00 | 01-JUN-00:10 | 22005.10 | 22-JUN-06:02 | 15042.44 | 22-JUN-06:02 | 6962.66 | 22-JUN-06:02 | 5086.99 | 22-JUN-06:02 | 0.00 | 01-JUN-00:10 |
July | 0.815671E+10 | 0.249496E+10 | 316.12 | 0.797222E+10 | 0.184496E+09 | 0.00 | 1.00 | 01-JUL-06:02 | 0.00 | 01-JUL-00:03 | 22888.20 | 19-JUL-06:02 | 21038.17 | 26-JUL-06:02 | 7401.44 | 19-JUL-06:02 | 5276.45 | 19-JUL-06:02 | 0.00 | 01-JUL-00:03 |
August | 0.664649E+10 | 0.203001E+10 | 298.84 | 0.661222E+10 | 34266816.94 | 0.00 | 1.00 | 01-AUG-06:01 | 0.00 | 01-AUG-00:10 | 21267.30 | 06-AUG-07:02 | 21267.30 | 06-AUG-07:02 | 3766.03 | 01-AUG-06:01 | 4925.96 | 06-AUG-07:02 | 0.00 | 01-AUG-00:10 |
September | 0.331776E+10 | 0.991872E+09 | 205.77 | 0.315333E+10 | 0.164423E+09 | 0.00 | 1.00 | 04-SEP-07:02 | 0.00 | 01-SEP-00:10 | 21886.36 | 07-SEP-06:02 | 20923.00 | 04-SEP-07:02 | 7865.24 | 07-SEP-06:02 | 5058.45 | 07-SEP-06:02 | 0.00 | 01-SEP-00:10 |
October | 0.410653E+09 | 0.120319E+09 | 95.00 | 0.410653E+09 | 0.00 | 0.00 | 0.46 | 18-OCT-14:00 | 0.00 | 01-OCT-00:10 | 8145.55 | 18-OCT-14:00 | 8145.55 | 18-OCT-14:00 | 0.00 | 18-OCT-13:50 | 2376.75 | 18-OCT-14:00 | 0.00 | 01-OCT-00:10 |
November | 3655.42 | 1120.24 | 11.83 | 3655.42 | 0.00 | 0.00 | 0.00 | 04-NOV-14:00 | 0.00 | 01-NOV-00:10 | 0.22 | 04-NOV-14:00 | 0.22 | 04-NOV-14:00 | 0.00 | 01-NOV-00:10 | 0.07 | 04-NOV-14:00 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.239851E+11 | 0.726905E+10 | 1359.66 | 0.234416E+11 | 0.543510E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.815671E+10 | 0.249496E+10 | 316.12 | 0.797222E+10 | 0.184496E+09 | 0.00 | 1.00 | 0.00 | 22888.20 | 21267.30 | 7865.24 | 5276.45 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 1513.54 | 463.84 | 6.00 | 1513.54 | 0.00 | 0.00 | 0.00 | 27-FEB-12:50 | 0.00 | 01-FEB-00:03 | 0.20 | 27-FEB-12:50 | 0.20 | 27-FEB-12:50 | 0.00 | 27-FEB-14:40 | 0.06 | 27-FEB-12:50 | 0.00 | 01-FEB-00:03 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 71668079.46 | 21445197.32 | 40.25 | 71668079.46 | 0.00 | 0.00 | 0.26 | 07-APR-14:00 | 0.00 | 01-APR-00:05 | 4377.79 | 07-APR-14:00 | 4377.79 | 07-APR-14:00 | 0.00 | 06-APR-16:30 | 1305.46 | 07-APR-14:00 | 0.00 | 01-APR-00:05 |
May | 0.104307E+10 | 0.310365E+09 | 120.39 | 0.103942E+10 | 3650862.75 | 0.00 | 0.55 | 20-MAY-16:00 | 0.00 | 01-MAY-00:10 | 9947.33 | 20-MAY-16:00 | 9947.33 | 20-MAY-16:00 | 208.68 | 19-MAY-11:00 | 3137.05 | 20-MAY-16:00 | 0.00 | 01-MAY-00:10 |
June | 0.429003E+10 | 0.128684E+10 | 257.14 | 0.413415E+10 | 0.155878E+09 | 0.00 | 1.00 | 22-JUN-06:02 | 0.00 | 01-JUN-00:10 | 22066.33 | 22-JUN-06:02 | 15086.21 | 22-JUN-06:02 | 6980.12 | 22-JUN-06:02 | 5101.15 | 22-JUN-06:02 | 0.00 | 01-JUN-00:10 |
July | 0.818352E+10 | 0.250309E+10 | 315.97 | 0.799762E+10 | 0.185901E+09 | 0.00 | 1.00 | 01-JUL-06:02 | 0.00 | 01-JUL-00:03 | 22952.93 | 19-JUL-06:02 | 21096.11 | 26-JUL-06:02 | 7412.73 | 19-JUL-06:02 | 5291.31 | 19-JUL-06:02 | 0.00 | 01-JUL-00:03 |
August | 0.665624E+10 | 0.203334E+10 | 298.95 | 0.662190E+10 | 34333829.52 | 0.00 | 1.00 | 01-AUG-06:01 | 0.00 | 01-AUG-00:10 | 21330.83 | 06-AUG-07:02 | 21330.83 | 06-AUG-07:02 | 3765.76 | 01-AUG-06:01 | 4940.82 | 06-AUG-07:02 | 0.00 | 01-AUG-00:10 |
September | 0.331094E+10 | 0.990158E+09 | 202.04 | 0.314601E+10 | 0.164935E+09 | 0.00 | 1.00 | 03-SEP-07:02 | 0.00 | 01-SEP-00:10 | 21948.21 | 07-SEP-06:02 | 21096.11 | 03-SEP-07:02 | 7880.28 | 07-SEP-06:02 | 5072.76 | 07-SEP-06:02 | 0.00 | 01-SEP-00:10 |
October | 0.387821E+09 | 0.113827E+09 | 91.68 | 0.387821E+09 | 0.00 | 0.00 | 0.46 | 18-OCT-14:00 | 0.00 | 01-OCT-00:10 | 8045.74 | 18-OCT-14:00 | 8045.74 | 18-OCT-14:00 | 0.00 | 15-OCT-13:40 | 2351.71 | 18-OCT-14:00 | 0.00 | 01-OCT-00:10 |
November | 2739.58 | 839.57 | 10.33 | 2739.58 | 0.00 | 0.00 | 0.00 | 04-NOV-14:00 | 0.00 | 01-NOV-00:10 | 0.21 | 04-NOV-14:00 | 0.21 | 04-NOV-14:00 | 0.00 | 04-NOV-11:40 | 0.06 | 04-NOV-14:00 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.239433E+11 | 0.725906E+10 | 1342.75 | 0.233986E+11 | 0.544698E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.818352E+10 | 0.250309E+10 | 315.97 | 0.799762E+10 | 0.185901E+09 | 0.00 | 1.00 | 0.00 | 22952.93 | 21330.83 | 7880.28 | 5291.31 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 904.56 | 277.21 | 3.17 | 904.56 | 0.00 | 0.00 | 0.00 | 27-FEB-12:00 | 0.00 | 01-FEB-00:03 | 0.18 | 27-FEB-12:00 | 0.18 | 27-FEB-12:00 | 0.00 | 01-FEB-00:03 | 0.05 | 27-FEB-12:00 | 0.00 | 01-FEB-00:03 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 58494168.91 | 17585232.73 | 34.92 | 58494168.91 | 0.00 | 0.00 | 0.24 | 07-APR-14:00 | 0.00 | 01-APR-00:05 | 4004.75 | 07-APR-14:00 | 4004.75 | 07-APR-14:00 | 0.00 | 07-APR-15:20 | 1200.38 | 07-APR-14:00 | 0.00 | 01-APR-00:05 |
May | 0.982026E+09 | 0.293089E+09 | 114.38 | 0.978846E+09 | 3180155.62 | 0.00 | 0.54 | 20-MAY-16:00 | 0.00 | 01-MAY-00:10 | 9738.73 | 20-MAY-16:00 | 9738.73 | 20-MAY-16:00 | 193.32 | 19-MAY-11:00 | 3077.12 | 20-MAY-16:00 | 0.00 | 01-MAY-00:10 |
June | 0.415294E+10 | 0.124849E+10 | 253.92 | 0.400281E+10 | 0.150127E+09 | 0.00 | 0.90 | 22-JUN-06:02 | 0.00 | 01-JUN-00:10 | 19072.41 | 22-JUN-06:02 | 13009.93 | 22-JUN-06:02 | 6062.47 | 22-JUN-06:02 | 4556.11 | 22-JUN-06:02 | 0.00 | 01-JUN-00:10 |
July | 0.799728E+10 | 0.245062E+10 | 313.48 | 0.781757E+10 | 0.179710E+09 | 0.00 | 1.00 | 01-JUL-06:02 | 0.00 | 01-JUL-00:03 | 22782.83 | 19-JUL-06:02 | 20944.50 | 26-JUL-06:02 | 7387.39 | 19-JUL-06:02 | 5252.30 | 19-JUL-06:02 | 0.00 | 01-JUL-00:03 |
August | 0.648712E+10 | 0.198557E+10 | 294.35 | 0.645497E+10 | 32151917.82 | 0.00 | 1.00 | 06-AUG-07:02 | 0.00 | 01-AUG-00:10 | 21169.54 | 06-AUG-07:02 | 21169.54 | 06-AUG-07:02 | 3454.72 | 01-AUG-06:01 | 4903.22 | 06-AUG-07:02 | 0.00 | 01-AUG-00:10 |
September | 0.321244E+10 | 0.962405E+09 | 193.66 | 0.305177E+10 | 0.160664E+09 | 0.00 | 1.00 | 04-SEP-07:02 | 0.00 | 01-SEP-00:10 | 21785.39 | 07-SEP-06:02 | 20831.69 | 04-SEP-07:02 | 7850.56 | 07-SEP-06:02 | 5035.07 | 07-SEP-06:02 | 0.00 | 01-SEP-00:10 |
October | 0.351829E+09 | 0.103535E+09 | 86.12 | 0.351829E+09 | 0.00 | 0.00 | 0.45 | 18-OCT-14:00 | 0.00 | 01-OCT-00:10 | 7803.44 | 18-OCT-14:00 | 7803.44 | 18-OCT-14:00 | 0.00 | 16-OCT-14:30 | 2286.93 | 18-OCT-14:00 | 0.00 | 01-OCT-00:10 |
November | 1863.92 | 571.22 | 6.33 | 1863.92 | 0.00 | 0.00 | 0.00 | 04-NOV-14:00 | 0.00 | 01-NOV-00:10 | 0.18 | 04-NOV-14:00 | 0.18 | 04-NOV-14:00 | 0.00 | 04-NOV-13:20 | 0.06 | 04-NOV-14:00 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.232421E+11 | 0.706130E+10 | 1300.33 | 0.227163E+11 | 0.525834E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.799728E+10 | 0.245062E+10 | 313.48 | 0.781757E+10 | 0.179710E+09 | 0.00 | 1.00 | 0.00 | 22782.83 | 21169.54 | 7850.56 | 5252.30 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 916.48 | 280.86 | 2.17 | 916.48 | 0.00 | 0.00 | 0.00 | 27-FEB-15:10 | 0.00 | 01-FEB-00:03 | 0.21 | 27-FEB-15:10 | 0.21 | 27-FEB-15:10 | 0.00 | 27-FEB-14:10 | 0.06 | 27-FEB-15:10 | 0.00 | 01-FEB-00:03 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 55778588.43 | 16952012.79 | 24.50 | 55778588.43 | 0.00 | 0.00 | 0.19 | 07-APR-14:00 | 0.00 | 01-APR-00:05 | 5549.97 | 07-APR-14:00 | 5549.97 | 07-APR-14:00 | 0.00 | 07-APR-14:30 | 1685.70 | 07-APR-14:00 | 0.00 | 01-APR-00:05 |
May | 0.150853E+10 | 0.454204E+09 | 98.69 | 0.150436E+10 | 4169408.66 | 0.00 | 0.53 | 20-MAY-16:00 | 0.00 | 01-MAY-00:10 | 16825.65 | 20-MAY-16:00 | 16825.65 | 20-MAY-16:00 | 300.68 | 20-MAY-11:00 | 5326.82 | 20-MAY-16:00 | 0.00 | 01-MAY-00:10 |
June | 0.703320E+10 | 0.212764E+10 | 245.74 | 0.675372E+10 | 0.279480E+09 | 0.00 | 0.69 | 22-JUN-07:03 | 0.00 | 01-JUN-00:10 | 24636.34 | 22-JUN-07:03 | 20479.41 | 29-JUN-15:00 | 5943.12 | 22-JUN-07:03 | 6664.54 | 29-JUN-15:00 | 0.00 | 01-JUN-00:10 |
July | 0.137555E+11 | 0.424050E+10 | 308.62 | 0.134437E+11 | 0.311810E+09 | 0.00 | 1.00 | 16-JUL-08:62 | 0.00 | 01-JUL-00:03 | 40583.36 | 19-JUL-07:02 | 38216.41 | 18-JUL-07:02 | 12632.52 | 19-JUL-07:02 | 9382.33 | 17-JUL-16:00 | 0.00 | 01-JUL-00:03 |
August | 0.111036E+11 | 0.342014E+10 | 295.85 | 0.110527E+11 | 50958379.48 | 0.00 | 1.00 | 06-AUG-08:62 | 0.00 | 01-AUG-00:10 | 37987.70 | 06-AUG-08:62 | 37987.70 | 06-AUG-08:62 | 3770.29 | 01-AUG-07:02 | 9204.83 | 06-AUG-08:62 | 0.00 | 01-AUG-00:10 |
September | 0.532229E+10 | 0.160120E+10 | 172.62 | 0.503102E+10 | 0.291268E+09 | 0.00 | 1.00 | 04-SEP-08:62 | 0.00 | 01-SEP-00:10 | 38535.82 | 07-SEP-07:02 | 38193.73 | 04-SEP-08:62 | 14048.58 | 07-SEP-07:02 | 9566.54 | 04-SEP-08:62 | 0.00 | 01-SEP-00:10 |
October | 0.487474E+09 | 0.144448E+09 | 63.03 | 0.487474E+09 | 0.00 | 0.00 | 0.43 | 18-OCT-14:30 | 0.00 | 01-OCT-00:10 | 13137.95 | 18-OCT-14:30 | 13137.95 | 18-OCT-14:30 | 0.00 | 15-OCT-15:10 | 3872.65 | 18-OCT-14:30 | 0.00 | 01-OCT-00:10 |
November | 825.94 | 253.12 | 2.50 | 825.94 | 0.00 | 0.00 | 0.00 | 04-NOV-14:00 | 0.00 | 01-NOV-00:10 | 0.20 | 04-NOV-14:00 | 0.20 | 04-NOV-14:00 | 0.00 | 01-NOV-00:10 | 0.06 | 04-NOV-14:00 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.392664E+11 | 0.120051E+11 | 1213.71 | 0.383288E+11 | 0.937685E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.137555E+11 | 0.424050E+10 | 308.62 | 0.134437E+11 | 0.311810E+09 | 0.00 | 1.00 | 0.00 | 40583.36 | 38216.41 | 14048.58 | 9566.54 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 293.20 | 89.85 | 1.33 | 293.20 | 0.00 | 0.00 | 0.00 | 27-FEB-15:10 | 0.00 | 01-FEB-00:03 | 0.09 | 27-FEB-15:10 | 0.09 | 27-FEB-15:10 | 0.00 | 27-FEB-15:10 | 0.03 | 27-FEB-15:10 | 0.00 | 01-FEB-00:03 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 24559797.86 | 7488621.06 | 21.17 | 24559797.86 | 0.00 | 0.00 | 0.18 | 07-APR-14:00 | 0.00 | 01-APR-00:05 | 2837.04 | 07-APR-14:00 | 2837.04 | 07-APR-14:00 | 0.00 | 06-APR-16:00 | 864.52 | 07-APR-14:00 | 0.00 | 01-APR-00:05 |
May | 0.769250E+09 | 0.232711E+09 | 96.28 | 0.767346E+09 | 1904364.64 | 0.00 | 0.51 | 20-MAY-16:00 | 0.00 | 01-MAY-00:10 | 8844.78 | 20-MAY-16:00 | 8844.78 | 20-MAY-16:00 | 146.84 | 20-MAY-11:00 | 2816.02 | 20-MAY-16:00 | 0.00 | 01-MAY-00:10 |
June | 0.363969E+10 | 0.110720E+10 | 242.47 | 0.349741E+10 | 0.142278E+09 | 0.00 | 0.62 | 29-JUN-15:00 | 0.00 | 01-JUN-00:10 | 10786.23 | 20-JUN-16:10 | 10749.96 | 29-JUN-15:00 | 2483.90 | 22-JUN-07:03 | 3523.00 | 29-JUN-15:00 | 0.00 | 01-JUN-00:10 |
July | 0.716072E+10 | 0.222136E+10 | 306.58 | 0.700094E+10 | 0.159786E+09 | 0.00 | 1.00 | 16-JUL-08:62 | 0.00 | 01-JUL-00:03 | 22263.13 | 19-JUL-07:02 | 20961.52 | 18-JUL-07:02 | 6934.78 | 19-JUL-07:02 | 5142.72 | 19-JUL-07:02 | 0.00 | 01-JUL-00:03 |
August | 0.575971E+10 | 0.178540E+10 | 293.21 | 0.573494E+10 | 24772421.24 | 0.00 | 1.00 | 06-AUG-08:62 | 0.00 | 01-AUG-00:10 | 20836.82 | 06-AUG-08:62 | 20836.82 | 06-AUG-08:62 | 1389.84 | 01-AUG-07:02 | 5048.96 | 06-AUG-08:62 | 0.00 | 01-AUG-00:10 |
September | 0.274490E+10 | 0.830920E+09 | 169.98 | 0.259790E+10 | 0.147002E+09 | 0.00 | 1.00 | 04-SEP-08:62 | 0.00 | 01-SEP-00:10 | 20952.92 | 04-SEP-08:62 | 20952.92 | 04-SEP-08:62 | 6637.04 | 06-SEP-07:01 | 5247.96 | 04-SEP-08:62 | 0.00 | 01-SEP-00:10 |
October | 0.240372E+09 | 71485473.78 | 62.69 | 0.240372E+09 | 0.00 | 0.00 | 0.41 | 18-OCT-14:40 | 0.00 | 01-OCT-00:10 | 6905.93 | 18-OCT-14:40 | 6905.93 | 18-OCT-14:40 | 0.00 | 15-OCT-14:50 | 2044.88 | 18-OCT-14:40 | 0.00 | 01-OCT-00:10 |
November | 466.03 | 142.82 | 2.33 | 466.03 | 0.00 | 0.00 | 0.00 | 04-NOV-15:40 | 0.00 | 01-NOV-00:10 | 0.14 | 04-NOV-15:40 | 0.14 | 04-NOV-15:40 | 0.00 | 01-NOV-00:10 | 0.04 | 04-NOV-15:40 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.203392E+11 | 0.625656E+10 | 1196.05 | 0.198635E+11 | 0.475743E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.716072E+10 | 0.222136E+10 | 306.58 | 0.700094E+10 | 0.159786E+09 | 0.00 | 1.00 | 0.00 | 22263.13 | 20961.52 | 6934.78 | 5247.96 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 196.88 | 60.34 | 1.00 | 196.88 | 0.00 | 0.00 | 0.00 | 27-FEB-15:10 | 0.00 | 01-FEB-00:03 | 0.08 | 27-FEB-15:10 | 0.08 | 27-FEB-15:10 | 0.00 | 01-FEB-00:03 | 0.03 | 27-FEB-15:10 | 0.00 | 01-FEB-00:03 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 21432283.01 | 6547665.78 | 20.33 | 21432283.01 | 0.00 | 0.00 | 0.17 | 07-APR-14:00 | 0.00 | 01-APR-00:05 | 2700.48 | 07-APR-14:00 | 2700.48 | 07-APR-14:00 | 0.00 | 24-APR-17:10 | 824.65 | 07-APR-14:00 | 0.00 | 01-APR-00:05 |
May | 0.743995E+09 | 0.225505E+09 | 93.53 | 0.742218E+09 | 1776515.28 | 0.00 | 0.50 | 20-MAY-16:00 | 0.00 | 01-MAY-00:10 | 8733.93 | 20-MAY-16:00 | 8733.93 | 20-MAY-16:00 | 141.08 | 20-MAY-11:00 | 2784.84 | 20-MAY-16:00 | 0.00 | 01-MAY-00:10 |
June | 0.357636E+10 | 0.108950E+10 | 238.72 | 0.343643E+10 | 0.139927E+09 | 0.00 | 0.62 | 29-JUN-15:00 | 0.00 | 01-JUN-00:10 | 10674.91 | 20-JUN-16:10 | 10666.27 | 29-JUN-15:00 | 2240.97 | 22-JUN-07:03 | 3499.27 | 29-JUN-15:00 | 0.00 | 01-JUN-00:10 |
July | 0.707448E+10 | 0.219731E+10 | 306.57 | 0.691718E+10 | 0.157294E+09 | 0.00 | 1.00 | 16-JUL-08:62 | 0.00 | 01-JUL-00:03 | 22239.54 | 19-JUL-07:02 | 20937.93 | 18-JUL-07:02 | 6940.24 | 19-JUL-07:02 | 5137.37 | 19-JUL-07:02 | 0.00 | 01-JUL-00:03 |
August | 0.568518E+10 | 0.176454E+10 | 292.50 | 0.566109E+10 | 24085687.34 | 0.00 | 1.00 | 06-AUG-08:62 | 0.00 | 01-AUG-00:10 | 20812.88 | 06-AUG-08:62 | 20812.88 | 06-AUG-08:62 | 1158.50 | 01-AUG-07:02 | 5043.20 | 06-AUG-08:62 | 0.00 | 01-AUG-00:10 |
September | 0.270232E+10 | 0.819062E+09 | 167.82 | 0.255745E+10 | 0.144861E+09 | 0.00 | 1.00 | 04-SEP-08:62 | 0.00 | 01-SEP-00:10 | 20929.09 | 04-SEP-08:62 | 20929.09 | 04-SEP-08:62 | 6132.15 | 06-SEP-07:01 | 5242.10 | 04-SEP-08:62 | 0.00 | 01-SEP-00:10 |
October | 0.228214E+09 | 67975708.65 | 58.86 | 0.228214E+09 | 0.00 | 0.00 | 0.41 | 18-OCT-14:40 | 0.00 | 01-OCT-00:10 | 6786.38 | 18-OCT-14:40 | 6786.38 | 18-OCT-14:40 | 0.00 | 18-OCT-14:10 | 2012.86 | 18-OCT-14:40 | 0.00 | 01-OCT-00:10 |
November | 1143.19 | 350.34 | 2.00 | 1143.19 | 0.00 | 0.00 | 0.00 | 04-NOV-15:40 | 0.00 | 01-NOV-00:10 | 1.36 | 04-NOV-15:40 | 1.36 | 04-NOV-15:40 | 0.00 | 04-NOV-15:40 | 0.42 | 04-NOV-15:40 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.200320E+11 | 0.617043E+10 | 1181.32 | 0.195640E+11 | 0.467945E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.707448E+10 | 0.219731E+10 | 306.57 | 0.691718E+10 | 0.157294E+09 | 0.00 | 1.00 | 0.00 | 22239.54 | 20937.93 | 6940.24 | 5242.10 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 15057447.90 | 4624641.42 | 15.42 | 15057447.90 | 0.00 | 0.00 | 0.15 | 07-APR-14:00 | 0.00 | 01-APR-00:05 | 2357.79 | 07-APR-14:00 | 2357.79 | 07-APR-14:00 | 0.00 | 06-APR-16:30 | 724.16 | 07-APR-14:00 | 0.00 | 01-APR-00:05 |
May | 0.688737E+09 | 0.209843E+09 | 82.64 | 0.687232E+09 | 1504865.65 | 0.00 | 0.49 | 20-MAY-16:00 | 0.00 | 01-MAY-00:10 | 8501.65 | 20-MAY-16:00 | 8501.65 | 20-MAY-16:00 | 128.20 | 19-MAY-11:30 | 2722.59 | 20-MAY-16:00 | 0.00 | 01-MAY-00:10 |
June | 0.344087E+10 | 0.105240E+10 | 232.06 | 0.330590E+10 | 0.134975E+09 | 0.00 | 0.61 | 29-JUN-15:00 | 0.00 | 01-JUN-00:10 | 10519.33 | 29-JUN-15:00 | 10519.33 | 29-JUN-15:00 | 1700.59 | 20-JUN-15:20 | 3462.66 | 29-JUN-15:00 | 0.00 | 01-JUN-00:10 |
July | 0.692212E+10 | 0.215706E+10 | 303.57 | 0.676965E+10 | 0.152466E+09 | 0.00 | 1.00 | 16-JUL-08:62 | 0.00 | 01-JUL-00:03 | 22413.50 | 19-JUL-07:02 | 21097.51 | 18-JUL-07:02 | 7030.74 | 19-JUL-07:02 | 5177.83 | 19-JUL-07:02 | 0.00 | 01-JUL-00:03 |
August | 0.555140E+10 | 0.172876E+10 | 288.46 | 0.552875E+10 | 22647473.23 | 0.00 | 1.00 | 06-AUG-08:62 | 0.00 | 01-AUG-00:10 | 20970.22 | 06-AUG-08:62 | 20970.22 | 06-AUG-08:62 | 865.62 | 09-AUG-07:03 | 5081.44 | 06-AUG-08:62 | 0.00 | 01-AUG-00:10 |
September | 0.262175E+10 | 0.797316E+09 | 159.34 | 0.248103E+10 | 0.140718E+09 | 0.00 | 1.00 | 04-SEP-08:62 | 0.00 | 01-SEP-00:10 | 21014.44 | 04-SEP-08:62 | 21014.44 | 04-SEP-08:62 | 4977.56 | 07-SEP-14:50 | 5269.24 | 04-SEP-08:62 | 0.00 | 01-SEP-00:10 |
October | 0.201625E+09 | 60297144.95 | 54.28 | 0.201625E+09 | 0.00 | 0.00 | 0.39 | 18-OCT-14:40 | 0.00 | 01-OCT-00:10 | 6526.66 | 18-OCT-14:40 | 6526.66 | 18-OCT-14:40 | 0.00 | 18-OCT-16:10 | 1944.87 | 18-OCT-14:40 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.194416E+11 | 0.601030E+10 | 1135.77 | 0.189892E+11 | 0.452311E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.692212E+10 | 0.215706E+10 | 303.57 | 0.676965E+10 | 0.152466E+09 | 0.00 | 1.00 | 0.00 | 22413.50 | 21097.51 | 7030.74 | 5269.24 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 5234517.39 | 1631551.07 | 6.67 | 5234517.39 | 0.00 | 0.00 | 0.09 | 07-APR-14:00 | 0.00 | 01-APR-00:05 | 1547.69 | 07-APR-14:00 | 1547.69 | 07-APR-14:00 | 0.00 | 07-APR-14:00 | 482.65 | 07-APR-14:00 | 0.00 | 01-APR-00:05 |
May | 0.600193E+09 | 0.185577E+09 | 64.11 | 0.598970E+09 | 1222566.28 | 0.00 | 0.43 | 20-MAY-16:00 | 0.00 | 01-MAY-00:10 | 8178.10 | 20-MAY-16:00 | 8178.10 | 20-MAY-16:00 | 121.06 | 19-MAY-11:30 | 2661.19 | 20-MAY-16:00 | 0.00 | 01-MAY-00:10 |
June | 0.327299E+10 | 0.101408E+10 | 211.76 | 0.314226E+10 | 0.130735E+09 | 0.00 | 0.56 | 29-JUN-15:00 | 0.00 | 01-JUN-00:10 | 10561.53 | 29-JUN-15:00 | 10561.53 | 29-JUN-15:00 | 1689.80 | 20-JUN-15:20 | 3525.42 | 29-JUN-15:00 | 0.00 | 01-JUN-00:10 |
July | 0.687372E+10 | 0.216727E+10 | 295.70 | 0.672438E+10 | 0.149339E+09 | 0.00 | 1.00 | 17-JUL-07:02 | 0.00 | 01-JUL-00:03 | 23652.90 | 17-JUL-07:02 | 21833.87 | 17-JUL-07:02 | 3446.84 | 16-JUL-08:62 | 5643.08 | 17-JUL-07:02 | 0.00 | 01-JUL-00:03 |
August | 0.547546E+10 | 0.172581E+10 | 279.77 | 0.545473E+10 | 20731369.61 | 0.00 | 0.79 | 06-AUG-08:62 | 0.00 | 01-AUG-00:10 | 16945.96 | 06-AUG-08:62 | 16945.96 | 06-AUG-08:62 | 677.43 | 22-AUG-14:20 | 4590.46 | 06-AUG-16:00 | 0.00 | 01-AUG-00:10 |
September | 0.253605E+10 | 0.780999E+09 | 144.17 | 0.240356E+10 | 0.132490E+09 | 0.00 | 1.00 | 04-SEP-08:62 | 0.00 | 01-SEP-00:10 | 23146.16 | 04-SEP-08:62 | 23146.16 | 04-SEP-08:62 | 4883.01 | 07-SEP-14:50 | 5803.29 | 04-SEP-08:62 | 0.00 | 01-SEP-00:10 |
October | 0.159315E+09 | 48150197.75 | 43.53 | 0.159315E+09 | 0.00 | 0.00 | 0.34 | 18-OCT-14:40 | 0.00 | 01-OCT-00:10 | 6205.03 | 18-OCT-14:40 | 6205.03 | 18-OCT-14:40 | 0.00 | 15-OCT-14:20 | 1874.16 | 18-OCT-14:40 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.189230E+11 | 0.592352E+10 | 1045.71 | 0.184885E+11 | 0.434519E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.687372E+10 | 0.216727E+10 | 295.70 | 0.672438E+10 | 0.149339E+09 | 0.00 | 1.00 | 0.00 | 23652.90 | 23146.16 | 4883.01 | 5803.29 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.98 | 84.25 | 33.73 | 102.05 | 148.82 | 0.00 | 0.00 | 744.00 |
February | 150.30 | 108.10 | 42.20 | 141.09 | 110.94 | 0.00 | 0.00 | 672.00 |
March | 134.40 | 75.50 | 58.90 | 118.06 | 98.51 | 0.00 | 0.00 | 744.00 |
April | 108.00 | 51.66 | 56.34 | 86.65 | 74.40 | 0.00 | 0.00 | 720.00 |
May | 95.93 | 31.85 | 64.08 | 68.80 | 59.95 | 0.00 | 0.00 | 744.00 |
June | 95.32 | 27.79 | 67.53 | 75.98 | 42.15 | 0.00 | 0.00 | 720.00 |
July | 102.76 | 37.95 | 64.81 | 95.78 | 32.64 | 0.00 | 0.00 | 744.00 |
August | 122.14 | 61.58 | 60.56 | 122.89 | 37.23 | 0.00 | 0.00 | 744.00 |
September | 135.53 | 83.06 | 52.47 | 141.16 | 53.38 | 0.00 | 0.00 | 720.00 |
October | 141.68 | 97.98 | 43.70 | 143.63 | 76.15 | 0.00 | 0.00 | 744.00 |
November | 129.10 | 93.51 | 35.59 | 124.56 | 94.78 | 0.00 | 0.00 | 720.00 |
December | 112.19 | 81.00 | 31.19 | 100.68 | 127.34 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 120.24 | 69.26 | 50.97 | 109.89 | 79.58 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 95.32 | 27.79 | 31.19 | 68.80 | 32.64 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 150.30 | 108.10 | 67.53 | 143.63 | 148.82 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.98 | 84.25 | 33.73 | 102.05 | 148.82 | 0.00 | 0.00 | 744.00 |
February | 150.30 | 108.10 | 42.20 | 141.09 | 110.94 | 0.00 | 0.00 | 672.00 |
March | 134.40 | 75.50 | 58.90 | 118.06 | 98.51 | 0.00 | 0.00 | 744.00 |
April | 108.00 | 51.66 | 56.34 | 86.65 | 74.40 | 0.00 | 0.00 | 720.00 |
May | 95.93 | 31.85 | 64.08 | 68.80 | 59.95 | 0.00 | 0.00 | 744.00 |
June | 95.32 | 27.79 | 67.53 | 75.98 | 42.15 | 0.00 | 0.00 | 720.00 |
July | 102.76 | 37.95 | 64.81 | 95.78 | 32.64 | 0.00 | 0.00 | 744.00 |
August | 122.14 | 61.58 | 60.56 | 122.89 | 37.23 | 0.00 | 0.00 | 744.00 |
September | 135.53 | 83.06 | 52.47 | 141.16 | 53.38 | 0.00 | 0.00 | 720.00 |
October | 141.68 | 97.98 | 43.70 | 143.63 | 76.15 | 0.00 | 0.00 | 744.00 |
November | 129.10 | 93.51 | 35.59 | 124.56 | 94.78 | 0.00 | 0.00 | 720.00 |
December | 112.19 | 81.00 | 31.19 | 100.68 | 127.34 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 120.24 | 69.26 | 50.97 | 109.89 | 79.58 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 95.32 | 27.79 | 31.19 | 68.80 | 32.64 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 150.30 | 108.10 | 67.53 | 143.63 | 148.82 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_3
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.98 | 84.25 | 33.73 | 102.05 | 148.82 | 0.00 | 0.00 | 744.00 |
February | 150.30 | 108.10 | 42.20 | 141.09 | 110.94 | 0.00 | 0.00 | 672.00 |
March | 134.40 | 75.50 | 58.90 | 118.06 | 98.51 | 0.00 | 0.00 | 744.00 |
April | 108.00 | 51.66 | 56.34 | 86.65 | 74.40 | 0.00 | 0.00 | 720.00 |
May | 95.93 | 31.85 | 64.08 | 68.80 | 59.95 | 0.00 | 0.00 | 744.00 |
June | 95.32 | 27.79 | 67.53 | 75.98 | 42.15 | 0.00 | 0.00 | 720.00 |
July | 102.76 | 37.95 | 64.81 | 95.78 | 32.64 | 0.00 | 0.00 | 744.00 |
August | 122.14 | 61.58 | 60.56 | 122.89 | 37.23 | 0.00 | 0.00 | 744.00 |
September | 135.53 | 83.06 | 52.47 | 141.16 | 53.38 | 0.00 | 0.00 | 720.00 |
October | 141.68 | 97.98 | 43.70 | 143.63 | 76.15 | 0.00 | 0.00 | 744.00 |
November | 129.10 | 93.51 | 35.59 | 124.56 | 94.78 | 0.00 | 0.00 | 720.00 |
December | 112.19 | 81.00 | 31.19 | 100.68 | 127.34 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 120.24 | 69.26 | 50.97 | 109.89 | 79.58 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 95.32 | 27.79 | 31.19 | 68.80 | 32.64 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 150.30 | 108.10 | 67.53 | 143.63 | 148.82 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_4
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.98 | 84.25 | 33.73 | 102.05 | 148.82 | 0.00 | 0.00 | 744.00 |
February | 150.30 | 108.10 | 42.20 | 141.09 | 110.94 | 0.00 | 0.00 | 672.00 |
March | 134.40 | 75.50 | 58.90 | 118.06 | 98.51 | 0.00 | 0.00 | 744.00 |
April | 108.00 | 51.66 | 56.34 | 86.65 | 74.40 | 0.00 | 0.00 | 720.00 |
May | 95.93 | 31.85 | 64.08 | 68.80 | 59.95 | 0.00 | 0.00 | 744.00 |
June | 95.32 | 27.79 | 67.53 | 75.98 | 42.15 | 0.00 | 0.00 | 720.00 |
July | 102.76 | 37.95 | 64.81 | 95.78 | 32.64 | 0.00 | 0.00 | 744.00 |
August | 122.14 | 61.58 | 60.56 | 122.89 | 37.23 | 0.00 | 0.00 | 744.00 |
September | 135.53 | 83.06 | 52.47 | 141.16 | 53.38 | 0.00 | 0.00 | 720.00 |
October | 141.68 | 97.98 | 43.70 | 143.63 | 76.15 | 0.00 | 0.00 | 744.00 |
November | 129.10 | 93.51 | 35.59 | 124.56 | 94.78 | 0.00 | 0.00 | 720.00 |
December | 112.19 | 81.00 | 31.19 | 100.68 | 127.34 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 120.24 | 69.26 | 50.97 | 109.89 | 79.58 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 95.32 | 27.79 | 31.19 | 68.80 | 32.64 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 150.30 | 108.10 | 67.53 | 143.63 | 148.82 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_DOOR_1
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 142.04 | 101.44 | 40.61 | 123.22 | 177.06 | 0.00 | 0.00 | 744.00 |
February | 180.96 | 130.15 | 50.80 | 170.21 | 132.09 | 0.00 | 0.00 | 672.00 |
March | 161.82 | 90.90 | 70.92 | 142.41 | 117.30 | 0.00 | 0.00 | 744.00 |
April | 130.03 | 62.20 | 67.83 | 104.49 | 88.69 | 0.00 | 0.00 | 720.00 |
May | 115.50 | 38.35 | 77.15 | 82.98 | 71.46 | 0.00 | 0.00 | 744.00 |
June | 114.76 | 33.45 | 81.30 | 91.48 | 50.31 | 0.00 | 0.00 | 720.00 |
July | 123.72 | 45.68 | 78.03 | 115.15 | 39.05 | 0.00 | 0.00 | 744.00 |
August | 147.05 | 74.14 | 72.92 | 147.79 | 44.52 | 0.00 | 0.00 | 744.00 |
September | 163.17 | 100.00 | 63.17 | 169.90 | 63.74 | 0.00 | 0.00 | 720.00 |
October | 170.57 | 117.96 | 52.61 | 173.02 | 90.85 | 0.00 | 0.00 | 744.00 |
November | 155.43 | 112.58 | 42.85 | 150.18 | 112.94 | 0.00 | 0.00 | 720.00 |
December | 135.07 | 97.52 | 37.55 | 121.52 | 151.61 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 144.76 | 83.39 | 61.37 | 132.43 | 94.84 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 114.76 | 33.45 | 37.55 | 82.98 | 39.05 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 180.96 | 130.15 | 81.30 | 173.02 | 177.06 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_DOOR_2
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 142.04 | 101.44 | 40.61 | 123.22 | 177.06 | 0.00 | 0.00 | 744.00 |
February | 180.96 | 130.15 | 50.80 | 170.21 | 132.09 | 0.00 | 0.00 | 672.00 |
March | 161.82 | 90.90 | 70.92 | 142.41 | 117.30 | 0.00 | 0.00 | 744.00 |
April | 130.03 | 62.20 | 67.83 | 104.49 | 88.69 | 0.00 | 0.00 | 720.00 |
May | 115.50 | 38.35 | 77.15 | 82.98 | 71.46 | 0.00 | 0.00 | 744.00 |
June | 114.76 | 33.45 | 81.30 | 91.48 | 50.31 | 0.00 | 0.00 | 720.00 |
July | 123.72 | 45.68 | 78.03 | 115.15 | 39.05 | 0.00 | 0.00 | 744.00 |
August | 147.05 | 74.14 | 72.92 | 147.79 | 44.52 | 0.00 | 0.00 | 744.00 |
September | 163.17 | 100.00 | 63.17 | 169.90 | 63.74 | 0.00 | 0.00 | 720.00 |
October | 170.57 | 117.96 | 52.61 | 173.02 | 90.85 | 0.00 | 0.00 | 744.00 |
November | 155.43 | 112.58 | 42.85 | 150.18 | 112.94 | 0.00 | 0.00 | 720.00 |
December | 135.07 | 97.52 | 37.55 | 121.52 | 151.61 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 144.76 | 83.39 | 61.37 | 132.43 | 94.84 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 114.76 | 33.45 | 37.55 | 82.98 | 39.05 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 180.96 | 130.15 | 81.30 | 173.02 | 177.06 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.98 | 84.25 | 33.73 | 100.83 | 154.16 | 0.00 | 0.00 | 744.00 |
February | 150.30 | 108.10 | 42.20 | 139.30 | 116.40 | 0.00 | 0.00 | 672.00 |
March | 134.40 | 75.50 | 58.90 | 116.40 | 104.59 | 0.00 | 0.00 | 744.00 |
April | 108.00 | 51.66 | 56.34 | 84.92 | 79.83 | 0.00 | 0.00 | 720.00 |
May | 95.93 | 31.85 | 64.08 | 67.50 | 63.50 | 0.00 | 0.00 | 744.00 |
June | 95.32 | 27.79 | 67.53 | 75.38 | 43.46 | 0.00 | 0.00 | 720.00 |
July | 102.76 | 37.95 | 64.81 | 95.65 | 33.14 | 0.00 | 0.00 | 744.00 |
August | 122.14 | 61.58 | 60.56 | 122.64 | 38.00 | 0.00 | 0.00 | 744.00 |
September | 135.53 | 83.06 | 52.47 | 140.45 | 55.16 | 0.00 | 0.00 | 720.00 |
October | 141.68 | 97.98 | 43.70 | 142.31 | 79.41 | 0.00 | 0.00 | 744.00 |
November | 129.10 | 93.51 | 35.59 | 122.89 | 99.54 | 0.00 | 0.00 | 720.00 |
December | 112.19 | 81.00 | 31.19 | 99.41 | 132.53 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 120.24 | 69.26 | 50.97 | 108.76 | 83.19 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 95.32 | 27.79 | 31.19 | 67.50 | 33.14 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 150.30 | 108.10 | 67.53 | 142.31 | 154.16 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.98 | 84.25 | 33.73 | 100.83 | 154.16 | 0.00 | 0.00 | 744.00 |
February | 150.30 | 108.10 | 42.20 | 139.30 | 116.40 | 0.00 | 0.00 | 672.00 |
March | 134.40 | 75.50 | 58.90 | 116.40 | 104.59 | 0.00 | 0.00 | 744.00 |
April | 108.00 | 51.66 | 56.34 | 84.92 | 79.83 | 0.00 | 0.00 | 720.00 |
May | 95.93 | 31.85 | 64.08 | 67.50 | 63.50 | 0.00 | 0.00 | 744.00 |
June | 95.32 | 27.79 | 67.53 | 75.38 | 43.46 | 0.00 | 0.00 | 720.00 |
July | 102.76 | 37.95 | 64.81 | 95.65 | 33.14 | 0.00 | 0.00 | 744.00 |
August | 122.14 | 61.58 | 60.56 | 122.64 | 38.00 | 0.00 | 0.00 | 744.00 |
September | 135.53 | 83.06 | 52.47 | 140.45 | 55.16 | 0.00 | 0.00 | 720.00 |
October | 141.68 | 97.98 | 43.70 | 142.31 | 79.41 | 0.00 | 0.00 | 744.00 |
November | 129.10 | 93.51 | 35.59 | 122.89 | 99.54 | 0.00 | 0.00 | 720.00 |
December | 112.19 | 81.00 | 31.19 | 99.41 | 132.53 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 120.24 | 69.26 | 50.97 | 108.76 | 83.19 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 95.32 | 27.79 | 31.19 | 67.50 | 33.14 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 150.30 | 108.10 | 67.53 | 142.31 | 154.16 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_DOOR
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 142.04 | 101.44 | 40.61 | 121.76 | 183.38 | 0.00 | 0.00 | 744.00 |
February | 180.96 | 130.15 | 50.80 | 168.06 | 138.55 | 0.00 | 0.00 | 672.00 |
March | 161.82 | 90.90 | 70.92 | 140.43 | 124.49 | 0.00 | 0.00 | 744.00 |
April | 130.03 | 62.20 | 67.83 | 102.41 | 95.11 | 0.00 | 0.00 | 720.00 |
May | 115.50 | 38.35 | 77.15 | 81.41 | 75.66 | 0.00 | 0.00 | 744.00 |
June | 114.76 | 33.45 | 81.30 | 90.76 | 51.86 | 0.00 | 0.00 | 720.00 |
July | 123.72 | 45.68 | 78.03 | 114.99 | 39.64 | 0.00 | 0.00 | 744.00 |
August | 147.05 | 74.14 | 72.92 | 147.49 | 45.42 | 0.00 | 0.00 | 744.00 |
September | 163.17 | 100.00 | 63.17 | 169.06 | 65.83 | 0.00 | 0.00 | 720.00 |
October | 170.57 | 117.96 | 52.61 | 171.46 | 94.70 | 0.00 | 0.00 | 744.00 |
November | 155.43 | 112.58 | 42.85 | 148.19 | 118.56 | 0.00 | 0.00 | 720.00 |
December | 135.07 | 97.52 | 37.55 | 120.00 | 157.75 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 144.76 | 83.39 | 61.37 | 131.07 | 99.10 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 114.76 | 33.45 | 37.55 | 81.41 | 39.64 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 180.96 | 130.15 | 81.30 | 171.46 | 183.38 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.98 | 84.25 | 33.73 | 101.17 | 149.90 | 0.00 | 0.00 | 744.00 |
February | 150.30 | 108.10 | 42.20 | 139.86 | 112.72 | 0.00 | 0.00 | 672.00 |
March | 134.40 | 75.50 | 58.90 | 116.83 | 101.09 | 0.00 | 0.00 | 744.00 |
April | 108.00 | 51.66 | 56.34 | 85.36 | 77.30 | 0.00 | 0.00 | 720.00 |
May | 95.93 | 31.85 | 64.08 | 67.66 | 62.45 | 0.00 | 0.00 | 744.00 |
June | 95.32 | 27.79 | 67.53 | 75.10 | 44.77 | 0.00 | 0.00 | 720.00 |
July | 102.76 | 37.95 | 64.81 | 95.02 | 35.37 | 0.00 | 0.00 | 744.00 |
August | 122.14 | 61.58 | 60.56 | 122.21 | 39.95 | 0.00 | 0.00 | 744.00 |
September | 135.53 | 83.06 | 52.47 | 140.26 | 55.96 | 0.00 | 0.00 | 720.00 |
October | 141.68 | 97.98 | 43.70 | 142.67 | 77.98 | 0.00 | 0.00 | 744.00 |
November | 129.10 | 93.51 | 35.59 | 123.48 | 96.31 | 0.00 | 0.00 | 720.00 |
December | 112.19 | 81.00 | 31.19 | 99.80 | 128.62 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 120.24 | 69.26 | 50.97 | 108.90 | 81.76 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 95.32 | 27.79 | 31.19 | 67.66 | 35.37 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 150.30 | 108.10 | 67.53 | 142.67 | 149.90 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.98 | 84.25 | 33.73 | 101.17 | 149.90 | 0.00 | 0.00 | 744.00 |
February | 150.30 | 108.10 | 42.20 | 139.86 | 112.72 | 0.00 | 0.00 | 672.00 |
March | 134.40 | 75.50 | 58.90 | 116.83 | 101.09 | 0.00 | 0.00 | 744.00 |
April | 108.00 | 51.66 | 56.34 | 85.36 | 77.30 | 0.00 | 0.00 | 720.00 |
May | 95.93 | 31.85 | 64.08 | 67.66 | 62.45 | 0.00 | 0.00 | 744.00 |
June | 95.32 | 27.79 | 67.53 | 75.10 | 44.77 | 0.00 | 0.00 | 720.00 |
July | 102.76 | 37.95 | 64.81 | 95.02 | 35.37 | 0.00 | 0.00 | 744.00 |
August | 122.14 | 61.58 | 60.56 | 122.21 | 39.95 | 0.00 | 0.00 | 744.00 |
September | 135.53 | 83.06 | 52.47 | 140.26 | 55.96 | 0.00 | 0.00 | 720.00 |
October | 141.68 | 97.98 | 43.70 | 142.67 | 77.98 | 0.00 | 0.00 | 744.00 |
November | 129.10 | 93.51 | 35.59 | 123.48 | 96.31 | 0.00 | 0.00 | 720.00 |
December | 112.19 | 81.00 | 31.19 | 99.80 | 128.62 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 120.24 | 69.26 | 50.97 | 108.90 | 81.76 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 95.32 | 27.79 | 31.19 | 67.66 | 35.37 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 150.30 | 108.10 | 67.53 | 142.67 | 149.90 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_DOOR
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 141.27 | 100.88 | 40.39 | 121.50 | 177.33 | 0.00 | 0.00 | 744.00 |
February | 179.97 | 129.44 | 50.53 | 167.82 | 133.44 | 0.00 | 0.00 | 672.00 |
March | 160.93 | 90.40 | 70.53 | 140.18 | 119.68 | 0.00 | 0.00 | 744.00 |
April | 129.32 | 61.86 | 67.46 | 102.38 | 91.60 | 0.00 | 0.00 | 720.00 |
May | 114.87 | 38.14 | 76.73 | 81.16 | 73.98 | 0.00 | 0.00 | 744.00 |
June | 114.13 | 33.27 | 80.86 | 89.93 | 53.09 | 0.00 | 0.00 | 720.00 |
July | 123.04 | 45.43 | 77.61 | 113.61 | 42.02 | 0.00 | 0.00 | 744.00 |
August | 146.25 | 73.73 | 72.52 | 146.18 | 47.44 | 0.00 | 0.00 | 744.00 |
September | 162.28 | 99.46 | 62.82 | 167.91 | 66.39 | 0.00 | 0.00 | 720.00 |
October | 169.64 | 117.32 | 52.32 | 170.95 | 92.47 | 0.00 | 0.00 | 744.00 |
November | 154.58 | 111.96 | 42.62 | 148.09 | 114.08 | 0.00 | 0.00 | 720.00 |
December | 134.33 | 96.99 | 37.35 | 119.82 | 152.26 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 143.97 | 82.93 | 61.04 | 130.53 | 96.85 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 114.13 | 33.27 | 37.35 | 81.16 | 42.02 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 179.97 | 129.44 | 80.86 | 170.95 | 177.33 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.98 | 84.25 | 33.73 | 101.33 | 148.53 | 0.00 | 0.00 | 744.00 |
February | 150.30 | 108.10 | 42.20 | 140.16 | 111.33 | 0.00 | 0.00 | 672.00 |
March | 134.40 | 75.50 | 58.90 | 117.09 | 99.75 | 0.00 | 0.00 | 744.00 |
April | 108.00 | 51.66 | 56.34 | 85.71 | 75.99 | 0.00 | 0.00 | 720.00 |
May | 95.93 | 31.85 | 64.08 | 67.91 | 61.58 | 0.00 | 0.00 | 744.00 |
June | 95.32 | 27.79 | 67.53 | 75.15 | 44.62 | 0.00 | 0.00 | 720.00 |
July | 102.76 | 37.95 | 64.81 | 94.99 | 35.46 | 0.00 | 0.00 | 744.00 |
August | 122.14 | 61.58 | 60.56 | 122.20 | 39.97 | 0.00 | 0.00 | 744.00 |
September | 135.53 | 83.06 | 52.47 | 140.34 | 55.64 | 0.00 | 0.00 | 720.00 |
October | 141.68 | 97.98 | 43.70 | 142.93 | 77.00 | 0.00 | 0.00 | 744.00 |
November | 129.10 | 93.51 | 35.59 | 123.84 | 94.85 | 0.00 | 0.00 | 720.00 |
December | 112.19 | 81.00 | 31.19 | 100.00 | 127.24 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 120.24 | 69.26 | 50.97 | 109.08 | 80.89 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 95.32 | 27.79 | 31.19 | 67.91 | 35.46 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 150.30 | 108.10 | 67.53 | 142.93 | 148.53 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.98 | 84.25 | 33.73 | 101.33 | 148.53 | 0.00 | 0.00 | 744.00 |
February | 150.30 | 108.10 | 42.20 | 140.16 | 111.33 | 0.00 | 0.00 | 672.00 |
March | 134.40 | 75.50 | 58.90 | 117.09 | 99.75 | 0.00 | 0.00 | 744.00 |
April | 108.00 | 51.66 | 56.34 | 85.71 | 75.99 | 0.00 | 0.00 | 720.00 |
May | 95.93 | 31.85 | 64.08 | 67.91 | 61.58 | 0.00 | 0.00 | 744.00 |
June | 95.32 | 27.79 | 67.53 | 75.15 | 44.62 | 0.00 | 0.00 | 720.00 |
July | 102.76 | 37.95 | 64.81 | 94.99 | 35.46 | 0.00 | 0.00 | 744.00 |
August | 122.14 | 61.58 | 60.56 | 122.20 | 39.97 | 0.00 | 0.00 | 744.00 |
September | 135.53 | 83.06 | 52.47 | 140.34 | 55.64 | 0.00 | 0.00 | 720.00 |
October | 141.68 | 97.98 | 43.70 | 142.93 | 77.00 | 0.00 | 0.00 | 744.00 |
November | 129.10 | 93.51 | 35.59 | 123.84 | 94.85 | 0.00 | 0.00 | 720.00 |
December | 112.19 | 81.00 | 31.19 | 100.00 | 127.24 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 120.24 | 69.26 | 50.97 | 109.08 | 80.89 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 95.32 | 27.79 | 31.19 | 67.91 | 35.46 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 150.30 | 108.10 | 67.53 | 142.93 | 148.53 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_DOOR
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 141.27 | 100.88 | 40.39 | 121.71 | 175.70 | 0.00 | 0.00 | 744.00 |
February | 179.97 | 129.44 | 50.53 | 168.18 | 131.78 | 0.00 | 0.00 | 672.00 |
March | 160.93 | 90.40 | 70.53 | 140.50 | 118.09 | 0.00 | 0.00 | 744.00 |
April | 129.32 | 61.86 | 67.46 | 102.80 | 90.05 | 0.00 | 0.00 | 720.00 |
May | 114.87 | 38.14 | 76.73 | 81.46 | 72.94 | 0.00 | 0.00 | 744.00 |
June | 114.13 | 33.27 | 80.86 | 89.98 | 52.92 | 0.00 | 0.00 | 720.00 |
July | 123.04 | 45.43 | 77.61 | 113.58 | 42.12 | 0.00 | 0.00 | 744.00 |
August | 146.25 | 73.73 | 72.52 | 146.17 | 47.46 | 0.00 | 0.00 | 744.00 |
September | 162.28 | 99.46 | 62.82 | 168.01 | 66.00 | 0.00 | 0.00 | 720.00 |
October | 169.64 | 117.32 | 52.32 | 171.26 | 91.31 | 0.00 | 0.00 | 744.00 |
November | 154.58 | 111.96 | 42.62 | 148.53 | 112.35 | 0.00 | 0.00 | 720.00 |
December | 134.33 | 96.99 | 37.35 | 120.07 | 150.62 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 143.97 | 82.93 | 61.04 | 130.75 | 95.82 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 114.13 | 33.27 | 37.35 | 81.46 | 42.12 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 179.97 | 129.44 | 80.86 | 171.26 | 175.70 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.98 | 84.25 | 33.73 | 101.52 | 147.56 | 0.00 | 0.00 | 744.00 |
February | 150.30 | 108.10 | 42.20 | 140.51 | 110.24 | 0.00 | 0.00 | 672.00 |
March | 134.40 | 75.50 | 58.90 | 117.40 | 98.67 | 0.00 | 0.00 | 744.00 |
April | 108.00 | 51.66 | 56.34 | 86.18 | 74.70 | 0.00 | 0.00 | 720.00 |
May | 95.93 | 31.85 | 64.08 | 68.33 | 60.57 | 0.00 | 0.00 | 744.00 |
June | 95.32 | 27.79 | 67.53 | 75.36 | 44.11 | 0.00 | 0.00 | 720.00 |
July | 102.76 | 37.95 | 64.81 | 95.14 | 35.07 | 0.00 | 0.00 | 744.00 |
August | 122.14 | 61.58 | 60.56 | 122.35 | 39.52 | 0.00 | 0.00 | 744.00 |
September | 135.53 | 83.06 | 52.47 | 140.57 | 54.98 | 0.00 | 0.00 | 720.00 |
October | 141.68 | 97.98 | 43.70 | 143.34 | 75.94 | 0.00 | 0.00 | 744.00 |
November | 129.10 | 93.51 | 35.59 | 124.30 | 93.54 | 0.00 | 0.00 | 720.00 |
December | 112.19 | 81.00 | 31.19 | 100.24 | 126.19 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 120.24 | 69.26 | 50.97 | 109.38 | 79.99 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 95.32 | 27.79 | 31.19 | 68.33 | 35.07 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 150.30 | 108.10 | 67.53 | 143.34 | 147.56 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.98 | 84.25 | 33.73 | 101.52 | 147.56 | 0.00 | 0.00 | 744.00 |
February | 150.30 | 108.10 | 42.20 | 140.51 | 110.24 | 0.00 | 0.00 | 672.00 |
March | 134.40 | 75.50 | 58.90 | 117.40 | 98.67 | 0.00 | 0.00 | 744.00 |
April | 108.00 | 51.66 | 56.34 | 86.18 | 74.70 | 0.00 | 0.00 | 720.00 |
May | 95.93 | 31.85 | 64.08 | 68.33 | 60.57 | 0.00 | 0.00 | 744.00 |
June | 95.32 | 27.79 | 67.53 | 75.36 | 44.11 | 0.00 | 0.00 | 720.00 |
July | 102.76 | 37.95 | 64.81 | 95.14 | 35.07 | 0.00 | 0.00 | 744.00 |
August | 122.14 | 61.58 | 60.56 | 122.35 | 39.52 | 0.00 | 0.00 | 744.00 |
September | 135.53 | 83.06 | 52.47 | 140.57 | 54.98 | 0.00 | 0.00 | 720.00 |
October | 141.68 | 97.98 | 43.70 | 143.34 | 75.94 | 0.00 | 0.00 | 744.00 |
November | 129.10 | 93.51 | 35.59 | 124.30 | 93.54 | 0.00 | 0.00 | 720.00 |
December | 112.19 | 81.00 | 31.19 | 100.24 | 126.19 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 120.24 | 69.26 | 50.97 | 109.38 | 79.99 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 95.32 | 27.79 | 31.19 | 68.33 | 35.07 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 150.30 | 108.10 | 67.53 | 143.34 | 147.56 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_DOOR
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 141.27 | 100.88 | 40.39 | 121.94 | 174.55 | 0.00 | 0.00 | 744.00 |
February | 179.97 | 129.44 | 50.53 | 168.60 | 130.49 | 0.00 | 0.00 | 672.00 |
March | 160.93 | 90.40 | 70.53 | 140.86 | 116.80 | 0.00 | 0.00 | 744.00 |
April | 129.32 | 61.86 | 67.46 | 103.36 | 88.51 | 0.00 | 0.00 | 720.00 |
May | 114.87 | 38.14 | 76.73 | 81.97 | 71.75 | 0.00 | 0.00 | 744.00 |
June | 114.13 | 33.27 | 80.86 | 90.25 | 52.32 | 0.00 | 0.00 | 720.00 |
July | 123.04 | 45.43 | 77.61 | 113.76 | 41.66 | 0.00 | 0.00 | 744.00 |
August | 146.25 | 73.73 | 72.52 | 146.35 | 46.93 | 0.00 | 0.00 | 744.00 |
September | 162.28 | 99.46 | 62.82 | 168.29 | 65.22 | 0.00 | 0.00 | 720.00 |
October | 169.64 | 117.32 | 52.32 | 171.75 | 90.05 | 0.00 | 0.00 | 744.00 |
November | 154.58 | 111.96 | 42.62 | 149.08 | 110.79 | 0.00 | 0.00 | 720.00 |
December | 134.33 | 96.99 | 37.35 | 120.36 | 149.37 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 143.97 | 82.93 | 61.04 | 131.11 | 94.75 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 114.13 | 33.27 | 37.35 | 81.97 | 41.66 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 179.97 | 129.44 | 80.86 | 171.75 | 174.55 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.98 | 84.25 | 33.73 | 102.57 | 143.60 | 0.00 | 0.00 | 744.00 |
February | 150.30 | 108.10 | 42.20 | 142.00 | 106.56 | 0.00 | 0.00 | 672.00 |
March | 134.40 | 75.50 | 58.90 | 118.54 | 95.25 | 0.00 | 0.00 | 744.00 |
April | 108.00 | 51.66 | 56.34 | 87.44 | 71.39 | 0.00 | 0.00 | 720.00 |
May | 95.93 | 31.85 | 64.08 | 69.42 | 57.76 | 0.00 | 0.00 | 744.00 |
June | 95.32 | 27.79 | 67.53 | 75.87 | 42.35 | 0.00 | 0.00 | 720.00 |
July | 102.76 | 37.95 | 64.81 | 95.30 | 33.59 | 0.00 | 0.00 | 744.00 |
August | 122.14 | 61.58 | 60.56 | 122.63 | 37.88 | 0.00 | 0.00 | 744.00 |
September | 135.53 | 83.06 | 52.47 | 141.25 | 52.99 | 0.00 | 0.00 | 720.00 |
October | 141.68 | 97.98 | 43.70 | 144.63 | 73.13 | 0.00 | 0.00 | 744.00 |
November | 129.10 | 93.51 | 35.59 | 125.74 | 89.97 | 0.00 | 0.00 | 720.00 |
December | 112.19 | 81.00 | 31.19 | 101.40 | 122.37 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 120.24 | 69.26 | 50.97 | 110.34 | 77.14 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 95.32 | 27.79 | 31.19 | 69.42 | 33.59 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 150.30 | 108.10 | 67.53 | 144.63 | 143.60 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.98 | 84.25 | 33.73 | 102.57 | 143.60 | 0.00 | 0.00 | 744.00 |
February | 150.30 | 108.10 | 42.20 | 142.00 | 106.56 | 0.00 | 0.00 | 672.00 |
March | 134.40 | 75.50 | 58.90 | 118.54 | 95.25 | 0.00 | 0.00 | 744.00 |
April | 108.00 | 51.66 | 56.34 | 87.44 | 71.39 | 0.00 | 0.00 | 720.00 |
May | 95.93 | 31.85 | 64.08 | 69.42 | 57.76 | 0.00 | 0.00 | 744.00 |
June | 95.32 | 27.79 | 67.53 | 75.87 | 42.35 | 0.00 | 0.00 | 720.00 |
July | 102.76 | 37.95 | 64.81 | 95.30 | 33.59 | 0.00 | 0.00 | 744.00 |
August | 122.14 | 61.58 | 60.56 | 122.63 | 37.88 | 0.00 | 0.00 | 744.00 |
September | 135.53 | 83.06 | 52.47 | 141.25 | 52.99 | 0.00 | 0.00 | 720.00 |
October | 141.68 | 97.98 | 43.70 | 144.63 | 73.13 | 0.00 | 0.00 | 744.00 |
November | 129.10 | 93.51 | 35.59 | 125.74 | 89.97 | 0.00 | 0.00 | 720.00 |
December | 112.19 | 81.00 | 31.19 | 101.40 | 122.37 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 120.24 | 69.26 | 50.97 | 110.34 | 77.14 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 95.32 | 27.79 | 31.19 | 69.42 | 33.59 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 150.30 | 108.10 | 67.53 | 144.63 | 143.60 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_3
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.98 | 84.25 | 33.73 | 102.57 | 143.60 | 0.00 | 0.00 | 744.00 |
February | 150.30 | 108.10 | 42.20 | 142.00 | 106.56 | 0.00 | 0.00 | 672.00 |
March | 134.40 | 75.50 | 58.90 | 118.54 | 95.25 | 0.00 | 0.00 | 744.00 |
April | 108.00 | 51.66 | 56.34 | 87.44 | 71.39 | 0.00 | 0.00 | 720.00 |
May | 95.93 | 31.85 | 64.08 | 69.42 | 57.76 | 0.00 | 0.00 | 744.00 |
June | 95.32 | 27.79 | 67.53 | 75.87 | 42.35 | 0.00 | 0.00 | 720.00 |
July | 102.76 | 37.95 | 64.81 | 95.30 | 33.59 | 0.00 | 0.00 | 744.00 |
August | 122.14 | 61.58 | 60.56 | 122.63 | 37.88 | 0.00 | 0.00 | 744.00 |
September | 135.53 | 83.06 | 52.47 | 141.25 | 52.99 | 0.00 | 0.00 | 720.00 |
October | 141.68 | 97.98 | 43.70 | 144.63 | 73.13 | 0.00 | 0.00 | 744.00 |
November | 129.10 | 93.51 | 35.59 | 125.74 | 89.97 | 0.00 | 0.00 | 720.00 |
December | 112.19 | 81.00 | 31.19 | 101.40 | 122.37 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 120.24 | 69.26 | 50.97 | 110.34 | 77.14 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 95.32 | 27.79 | 31.19 | 69.42 | 33.59 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 150.30 | 108.10 | 67.53 | 144.63 | 143.60 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_4
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.98 | 84.25 | 33.73 | 102.57 | 143.60 | 0.00 | 0.00 | 744.00 |
February | 150.30 | 108.10 | 42.20 | 142.00 | 106.56 | 0.00 | 0.00 | 672.00 |
March | 134.40 | 75.50 | 58.90 | 118.54 | 95.25 | 0.00 | 0.00 | 744.00 |
April | 108.00 | 51.66 | 56.34 | 87.44 | 71.39 | 0.00 | 0.00 | 720.00 |
May | 95.93 | 31.85 | 64.08 | 69.42 | 57.76 | 0.00 | 0.00 | 744.00 |
June | 95.32 | 27.79 | 67.53 | 75.87 | 42.35 | 0.00 | 0.00 | 720.00 |
July | 102.76 | 37.95 | 64.81 | 95.30 | 33.59 | 0.00 | 0.00 | 744.00 |
August | 122.14 | 61.58 | 60.56 | 122.63 | 37.88 | 0.00 | 0.00 | 744.00 |
September | 135.53 | 83.06 | 52.47 | 141.25 | 52.99 | 0.00 | 0.00 | 720.00 |
October | 141.68 | 97.98 | 43.70 | 144.63 | 73.13 | 0.00 | 0.00 | 744.00 |
November | 129.10 | 93.51 | 35.59 | 125.74 | 89.97 | 0.00 | 0.00 | 720.00 |
December | 112.19 | 81.00 | 31.19 | 101.40 | 122.37 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 120.24 | 69.26 | 50.97 | 110.34 | 77.14 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 95.32 | 27.79 | 31.19 | 69.42 | 33.59 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 150.30 | 108.10 | 67.53 | 144.63 | 143.60 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_DOOR_1
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 141.27 | 100.88 | 40.39 | 123.19 | 169.89 | 0.00 | 0.00 | 744.00 |
February | 179.97 | 129.44 | 50.53 | 170.38 | 126.16 | 0.00 | 0.00 | 672.00 |
March | 160.93 | 90.40 | 70.53 | 142.22 | 112.77 | 0.00 | 0.00 | 744.00 |
April | 129.32 | 61.86 | 67.46 | 104.87 | 84.61 | 0.00 | 0.00 | 720.00 |
May | 114.87 | 38.14 | 76.73 | 83.28 | 68.45 | 0.00 | 0.00 | 744.00 |
June | 114.13 | 33.27 | 80.86 | 90.86 | 50.23 | 0.00 | 0.00 | 720.00 |
July | 123.04 | 45.43 | 77.61 | 113.97 | 39.92 | 0.00 | 0.00 | 744.00 |
August | 146.25 | 73.73 | 72.52 | 146.70 | 45.00 | 0.00 | 0.00 | 744.00 |
September | 162.28 | 99.46 | 62.82 | 169.10 | 62.87 | 0.00 | 0.00 | 720.00 |
October | 169.64 | 117.32 | 52.32 | 173.28 | 86.74 | 0.00 | 0.00 | 744.00 |
November | 154.58 | 111.96 | 42.62 | 150.79 | 106.59 | 0.00 | 0.00 | 720.00 |
December | 134.33 | 96.99 | 37.35 | 121.73 | 144.88 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 143.97 | 82.93 | 61.04 | 132.26 | 91.39 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 114.13 | 33.27 | 37.35 | 83.28 | 39.92 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 179.97 | 129.44 | 80.86 | 173.28 | 169.89 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_DOOR_2
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 141.27 | 100.88 | 40.39 | 123.19 | 169.89 | 0.00 | 0.00 | 744.00 |
February | 179.97 | 129.44 | 50.53 | 170.38 | 126.16 | 0.00 | 0.00 | 672.00 |
March | 160.93 | 90.40 | 70.53 | 142.22 | 112.77 | 0.00 | 0.00 | 744.00 |
April | 129.32 | 61.86 | 67.46 | 104.87 | 84.61 | 0.00 | 0.00 | 720.00 |
May | 114.87 | 38.14 | 76.73 | 83.28 | 68.45 | 0.00 | 0.00 | 744.00 |
June | 114.13 | 33.27 | 80.86 | 90.86 | 50.23 | 0.00 | 0.00 | 720.00 |
July | 123.04 | 45.43 | 77.61 | 113.97 | 39.92 | 0.00 | 0.00 | 744.00 |
August | 146.25 | 73.73 | 72.52 | 146.70 | 45.00 | 0.00 | 0.00 | 744.00 |
September | 162.28 | 99.46 | 62.82 | 169.10 | 62.87 | 0.00 | 0.00 | 720.00 |
October | 169.64 | 117.32 | 52.32 | 173.28 | 86.74 | 0.00 | 0.00 | 744.00 |
November | 154.58 | 111.96 | 42.62 | 150.79 | 106.59 | 0.00 | 0.00 | 720.00 |
December | 134.33 | 96.99 | 37.35 | 121.73 | 144.88 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 143.97 | 82.93 | 61.04 | 132.26 | 91.39 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 114.13 | 33.27 | 37.35 | 83.28 | 39.92 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 179.97 | 129.44 | 80.86 | 173.28 | 169.89 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.98 | 84.25 | 33.73 | 102.09 | 144.56 | 0.00 | 0.00 | 744.00 |
February | 150.30 | 108.10 | 42.20 | 141.52 | 107.12 | 0.00 | 0.00 | 672.00 |
March | 134.40 | 75.50 | 58.90 | 118.19 | 95.59 | 0.00 | 0.00 | 744.00 |
April | 108.00 | 51.66 | 56.34 | 87.40 | 71.33 | 0.00 | 0.00 | 720.00 |
May | 95.93 | 31.85 | 64.08 | 69.49 | 57.67 | 0.00 | 0.00 | 744.00 |
June | 95.32 | 27.79 | 67.53 | 76.07 | 42.13 | 0.00 | 0.00 | 720.00 |
July | 102.76 | 37.95 | 64.81 | 95.63 | 33.26 | 0.00 | 0.00 | 744.00 |
August | 122.14 | 61.58 | 60.56 | 122.83 | 37.56 | 0.00 | 0.00 | 744.00 |
September | 135.53 | 83.06 | 52.47 | 141.22 | 52.80 | 0.00 | 0.00 | 720.00 |
October | 141.68 | 97.98 | 43.70 | 144.44 | 73.04 | 0.00 | 0.00 | 744.00 |
November | 129.10 | 93.51 | 35.59 | 125.45 | 90.20 | 0.00 | 0.00 | 720.00 |
December | 112.19 | 81.00 | 31.19 | 100.94 | 123.09 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 120.24 | 69.26 | 50.97 | 110.22 | 77.26 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 95.32 | 27.79 | 31.19 | 69.49 | 33.26 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 150.30 | 108.10 | 67.53 | 144.44 | 144.56 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.98 | 84.25 | 33.73 | 102.09 | 144.56 | 0.00 | 0.00 | 744.00 |
February | 150.30 | 108.10 | 42.20 | 141.52 | 107.12 | 0.00 | 0.00 | 672.00 |
March | 134.40 | 75.50 | 58.90 | 118.19 | 95.59 | 0.00 | 0.00 | 744.00 |
April | 108.00 | 51.66 | 56.34 | 87.40 | 71.33 | 0.00 | 0.00 | 720.00 |
May | 95.93 | 31.85 | 64.08 | 69.49 | 57.67 | 0.00 | 0.00 | 744.00 |
June | 95.32 | 27.79 | 67.53 | 76.07 | 42.13 | 0.00 | 0.00 | 720.00 |
July | 102.76 | 37.95 | 64.81 | 95.63 | 33.26 | 0.00 | 0.00 | 744.00 |
August | 122.14 | 61.58 | 60.56 | 122.83 | 37.56 | 0.00 | 0.00 | 744.00 |
September | 135.53 | 83.06 | 52.47 | 141.22 | 52.80 | 0.00 | 0.00 | 720.00 |
October | 141.68 | 97.98 | 43.70 | 144.44 | 73.04 | 0.00 | 0.00 | 744.00 |
November | 129.10 | 93.51 | 35.59 | 125.45 | 90.20 | 0.00 | 0.00 | 720.00 |
December | 112.19 | 81.00 | 31.19 | 100.94 | 123.09 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 120.24 | 69.26 | 50.97 | 110.22 | 77.26 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 95.32 | 27.79 | 31.19 | 69.49 | 33.26 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 150.30 | 108.10 | 67.53 | 144.44 | 144.56 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_DOOR
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 141.27 | 100.88 | 40.39 | 122.63 | 170.97 | 0.00 | 0.00 | 744.00 |
February | 179.97 | 129.44 | 50.53 | 169.83 | 126.79 | 0.00 | 0.00 | 672.00 |
March | 160.93 | 90.40 | 70.53 | 141.83 | 113.15 | 0.00 | 0.00 | 744.00 |
April | 129.32 | 61.86 | 67.46 | 104.84 | 84.51 | 0.00 | 0.00 | 720.00 |
May | 114.87 | 38.14 | 76.73 | 83.38 | 68.32 | 0.00 | 0.00 | 744.00 |
June | 114.13 | 33.27 | 80.86 | 91.11 | 49.97 | 0.00 | 0.00 | 720.00 |
July | 123.04 | 45.43 | 77.61 | 114.37 | 39.52 | 0.00 | 0.00 | 744.00 |
August | 146.25 | 73.73 | 72.52 | 146.95 | 44.62 | 0.00 | 0.00 | 744.00 |
September | 162.28 | 99.46 | 62.82 | 169.09 | 62.63 | 0.00 | 0.00 | 720.00 |
October | 169.64 | 117.32 | 52.32 | 173.08 | 86.60 | 0.00 | 0.00 | 744.00 |
November | 154.58 | 111.96 | 42.62 | 150.47 | 106.83 | 0.00 | 0.00 | 720.00 |
December | 134.33 | 96.99 | 37.35 | 121.22 | 145.69 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 143.97 | 82.93 | 61.04 | 132.13 | 91.52 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 114.13 | 33.27 | 37.35 | 83.38 | 39.52 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 179.97 | 129.44 | 80.86 | 173.08 | 170.97 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.98 | 84.25 | 33.73 | 102.13 | 144.35 | 0.00 | 0.00 | 744.00 |
February | 150.30 | 108.10 | 42.20 | 141.62 | 106.82 | 0.00 | 0.00 | 672.00 |
March | 134.40 | 75.50 | 58.90 | 118.28 | 95.24 | 0.00 | 0.00 | 744.00 |
April | 108.00 | 51.66 | 56.34 | 87.60 | 70.79 | 0.00 | 0.00 | 720.00 |
May | 95.93 | 31.85 | 64.08 | 69.71 | 57.22 | 0.00 | 0.00 | 744.00 |
June | 95.32 | 27.79 | 67.53 | 76.24 | 41.86 | 0.00 | 0.00 | 720.00 |
July | 102.76 | 37.95 | 64.81 | 95.74 | 33.07 | 0.00 | 0.00 | 744.00 |
August | 122.14 | 61.58 | 60.56 | 122.94 | 37.36 | 0.00 | 0.00 | 744.00 |
September | 135.53 | 83.06 | 52.47 | 141.36 | 52.49 | 0.00 | 0.00 | 720.00 |
October | 141.68 | 97.98 | 43.70 | 144.64 | 72.58 | 0.00 | 0.00 | 744.00 |
November | 129.10 | 93.51 | 35.59 | 125.59 | 89.81 | 0.00 | 0.00 | 720.00 |
December | 112.19 | 81.00 | 31.19 | 101.01 | 122.81 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 120.24 | 69.26 | 50.97 | 110.35 | 76.93 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 95.32 | 27.79 | 31.19 | 69.71 | 33.07 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 150.30 | 108.10 | 67.53 | 144.64 | 144.35 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.98 | 84.25 | 33.73 | 102.13 | 144.35 | 0.00 | 0.00 | 744.00 |
February | 150.30 | 108.10 | 42.20 | 141.62 | 106.82 | 0.00 | 0.00 | 672.00 |
March | 134.40 | 75.50 | 58.90 | 118.28 | 95.24 | 0.00 | 0.00 | 744.00 |
April | 108.00 | 51.66 | 56.34 | 87.60 | 70.79 | 0.00 | 0.00 | 720.00 |
May | 95.93 | 31.85 | 64.08 | 69.71 | 57.22 | 0.00 | 0.00 | 744.00 |
June | 95.32 | 27.79 | 67.53 | 76.24 | 41.86 | 0.00 | 0.00 | 720.00 |
July | 102.76 | 37.95 | 64.81 | 95.74 | 33.07 | 0.00 | 0.00 | 744.00 |
August | 122.14 | 61.58 | 60.56 | 122.94 | 37.36 | 0.00 | 0.00 | 744.00 |
September | 135.53 | 83.06 | 52.47 | 141.36 | 52.49 | 0.00 | 0.00 | 720.00 |
October | 141.68 | 97.98 | 43.70 | 144.64 | 72.58 | 0.00 | 0.00 | 744.00 |
November | 129.10 | 93.51 | 35.59 | 125.59 | 89.81 | 0.00 | 0.00 | 720.00 |
December | 112.19 | 81.00 | 31.19 | 101.01 | 122.81 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 120.24 | 69.26 | 50.97 | 110.35 | 76.93 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 95.32 | 27.79 | 31.19 | 69.71 | 33.07 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 150.30 | 108.10 | 67.53 | 144.64 | 144.35 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_DOOR
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 141.27 | 100.88 | 40.39 | 122.69 | 170.72 | 0.00 | 0.00 | 744.00 |
February | 179.97 | 129.44 | 50.53 | 169.95 | 126.43 | 0.00 | 0.00 | 672.00 |
March | 160.93 | 90.40 | 70.53 | 141.95 | 112.72 | 0.00 | 0.00 | 744.00 |
April | 129.32 | 61.86 | 67.46 | 105.08 | 83.87 | 0.00 | 0.00 | 720.00 |
May | 114.87 | 38.14 | 76.73 | 83.64 | 67.78 | 0.00 | 0.00 | 744.00 |
June | 114.13 | 33.27 | 80.86 | 91.31 | 49.65 | 0.00 | 0.00 | 720.00 |
July | 123.04 | 45.43 | 77.61 | 114.50 | 39.30 | 0.00 | 0.00 | 744.00 |
August | 146.25 | 73.73 | 72.52 | 147.07 | 44.37 | 0.00 | 0.00 | 744.00 |
September | 162.28 | 99.46 | 62.82 | 169.24 | 62.27 | 0.00 | 0.00 | 720.00 |
October | 169.64 | 117.32 | 52.32 | 173.32 | 86.06 | 0.00 | 0.00 | 744.00 |
November | 154.58 | 111.96 | 42.62 | 150.63 | 106.37 | 0.00 | 0.00 | 720.00 |
December | 134.33 | 96.99 | 37.35 | 121.30 | 145.36 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 143.97 | 82.93 | 61.04 | 132.29 | 91.12 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 114.13 | 33.27 | 37.35 | 83.64 | 39.30 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 179.97 | 129.44 | 80.86 | 173.32 | 170.72 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.98 | 84.25 | 33.73 | 102.30 | 143.35 | 0.00 | 0.00 | 744.00 |
February | 150.30 | 108.10 | 42.20 | 141.96 | 105.59 | 0.00 | 0.00 | 672.00 |
March | 134.40 | 75.50 | 58.90 | 118.58 | 93.89 | 0.00 | 0.00 | 744.00 |
April | 108.00 | 51.66 | 56.34 | 88.10 | 69.15 | 0.00 | 0.00 | 720.00 |
May | 95.93 | 31.85 | 64.08 | 70.24 | 55.86 | 0.00 | 0.00 | 744.00 |
June | 95.32 | 27.79 | 67.53 | 76.65 | 41.05 | 0.00 | 0.00 | 720.00 |
July | 102.76 | 37.95 | 64.81 | 95.95 | 32.61 | 0.00 | 0.00 | 744.00 |
August | 122.14 | 61.58 | 60.56 | 123.12 | 36.84 | 0.00 | 0.00 | 744.00 |
September | 135.53 | 83.06 | 52.47 | 141.64 | 51.68 | 0.00 | 0.00 | 720.00 |
October | 141.68 | 97.98 | 43.70 | 145.09 | 71.36 | 0.00 | 0.00 | 744.00 |
November | 129.10 | 93.51 | 35.59 | 125.95 | 88.59 | 0.00 | 0.00 | 720.00 |
December | 112.19 | 81.00 | 31.19 | 101.24 | 121.65 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 120.24 | 69.26 | 50.97 | 110.68 | 75.87 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 95.32 | 27.79 | 31.19 | 70.24 | 32.61 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 150.30 | 108.10 | 67.53 | 145.09 | 143.35 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.98 | 84.25 | 33.73 | 102.30 | 143.35 | 0.00 | 0.00 | 744.00 |
February | 150.30 | 108.10 | 42.20 | 141.96 | 105.59 | 0.00 | 0.00 | 672.00 |
March | 134.40 | 75.50 | 58.90 | 118.58 | 93.89 | 0.00 | 0.00 | 744.00 |
April | 108.00 | 51.66 | 56.34 | 88.10 | 69.15 | 0.00 | 0.00 | 720.00 |
May | 95.93 | 31.85 | 64.08 | 70.24 | 55.86 | 0.00 | 0.00 | 744.00 |
June | 95.32 | 27.79 | 67.53 | 76.65 | 41.05 | 0.00 | 0.00 | 720.00 |
July | 102.76 | 37.95 | 64.81 | 95.95 | 32.61 | 0.00 | 0.00 | 744.00 |
August | 122.14 | 61.58 | 60.56 | 123.12 | 36.84 | 0.00 | 0.00 | 744.00 |
September | 135.53 | 83.06 | 52.47 | 141.64 | 51.68 | 0.00 | 0.00 | 720.00 |
October | 141.68 | 97.98 | 43.70 | 145.09 | 71.36 | 0.00 | 0.00 | 744.00 |
November | 129.10 | 93.51 | 35.59 | 125.95 | 88.59 | 0.00 | 0.00 | 720.00 |
December | 112.19 | 81.00 | 31.19 | 101.24 | 121.65 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 120.24 | 69.26 | 50.97 | 110.68 | 75.87 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 95.32 | 27.79 | 31.19 | 70.24 | 32.61 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 150.30 | 108.10 | 67.53 | 145.09 | 143.35 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_DOOR
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 141.27 | 100.88 | 40.39 | 122.89 | 169.53 | 0.00 | 0.00 | 744.00 |
February | 179.97 | 129.44 | 50.53 | 170.36 | 124.98 | 0.00 | 0.00 | 672.00 |
March | 160.93 | 90.40 | 70.53 | 142.31 | 111.13 | 0.00 | 0.00 | 744.00 |
April | 129.32 | 61.86 | 67.46 | 105.68 | 81.92 | 0.00 | 0.00 | 720.00 |
May | 114.87 | 38.14 | 76.73 | 84.28 | 66.17 | 0.00 | 0.00 | 744.00 |
June | 114.13 | 33.27 | 80.86 | 91.81 | 48.69 | 0.00 | 0.00 | 720.00 |
July | 123.04 | 45.43 | 77.61 | 114.75 | 38.76 | 0.00 | 0.00 | 744.00 |
August | 146.25 | 73.73 | 72.52 | 147.30 | 43.76 | 0.00 | 0.00 | 744.00 |
September | 162.28 | 99.46 | 62.82 | 169.59 | 61.31 | 0.00 | 0.00 | 720.00 |
October | 169.64 | 117.32 | 52.32 | 173.86 | 84.63 | 0.00 | 0.00 | 744.00 |
November | 154.58 | 111.96 | 42.62 | 151.07 | 104.93 | 0.00 | 0.00 | 720.00 |
December | 134.33 | 96.99 | 37.35 | 121.57 | 143.97 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 143.97 | 82.93 | 61.04 | 132.69 | 89.87 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 114.13 | 33.27 | 37.35 | 84.28 | 38.76 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 179.97 | 129.44 | 80.86 | 173.86 | 169.53 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.98 | 84.25 | 33.73 | 103.09 | 138.49 | 0.00 | 0.00 | 744.00 |
February | 150.30 | 108.10 | 42.20 | 143.22 | 100.23 | 0.00 | 0.00 | 672.00 |
March | 134.40 | 75.50 | 58.90 | 119.72 | 88.01 | 0.00 | 0.00 | 744.00 |
April | 108.00 | 51.66 | 56.34 | 89.56 | 63.03 | 0.00 | 0.00 | 720.00 |
May | 95.93 | 31.85 | 64.08 | 71.79 | 50.86 | 0.00 | 0.00 | 744.00 |
June | 95.32 | 27.79 | 67.53 | 77.97 | 37.74 | 0.00 | 0.00 | 720.00 |
July | 102.76 | 37.95 | 64.81 | 96.47 | 30.68 | 0.00 | 0.00 | 744.00 |
August | 122.14 | 61.58 | 60.56 | 123.59 | 34.73 | 0.00 | 0.00 | 744.00 |
September | 135.53 | 83.06 | 52.47 | 142.38 | 48.60 | 0.00 | 0.00 | 720.00 |
October | 141.68 | 97.98 | 43.70 | 146.23 | 67.24 | 0.00 | 0.00 | 744.00 |
November | 129.10 | 93.51 | 35.59 | 127.08 | 83.96 | 0.00 | 0.00 | 720.00 |
December | 112.19 | 81.00 | 31.19 | 102.12 | 116.60 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 120.24 | 69.26 | 50.97 | 111.71 | 71.59 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 95.32 | 27.79 | 31.19 | 71.79 | 30.68 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 150.30 | 108.10 | 67.53 | 146.23 | 138.49 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.98 | 84.25 | 33.73 | 103.09 | 138.49 | 0.00 | 0.00 | 744.00 |
February | 150.30 | 108.10 | 42.20 | 143.22 | 100.23 | 0.00 | 0.00 | 672.00 |
March | 134.40 | 75.50 | 58.90 | 119.72 | 88.01 | 0.00 | 0.00 | 744.00 |
April | 108.00 | 51.66 | 56.34 | 89.56 | 63.03 | 0.00 | 0.00 | 720.00 |
May | 95.93 | 31.85 | 64.08 | 71.79 | 50.86 | 0.00 | 0.00 | 744.00 |
June | 95.32 | 27.79 | 67.53 | 77.97 | 37.74 | 0.00 | 0.00 | 720.00 |
July | 102.76 | 37.95 | 64.81 | 96.47 | 30.68 | 0.00 | 0.00 | 744.00 |
August | 122.14 | 61.58 | 60.56 | 123.59 | 34.73 | 0.00 | 0.00 | 744.00 |
September | 135.53 | 83.06 | 52.47 | 142.38 | 48.60 | 0.00 | 0.00 | 720.00 |
October | 141.68 | 97.98 | 43.70 | 146.23 | 67.24 | 0.00 | 0.00 | 744.00 |
November | 129.10 | 93.51 | 35.59 | 127.08 | 83.96 | 0.00 | 0.00 | 720.00 |
December | 112.19 | 81.00 | 31.19 | 102.12 | 116.60 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 120.24 | 69.26 | 50.97 | 111.71 | 71.59 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 95.32 | 27.79 | 31.19 | 71.79 | 30.68 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 150.30 | 108.10 | 67.53 | 146.23 | 138.49 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_DOOR
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 141.27 | 100.88 | 40.39 | 123.85 | 163.74 | 0.00 | 0.00 | 744.00 |
February | 179.97 | 129.44 | 50.53 | 171.88 | 118.62 | 0.00 | 0.00 | 672.00 |
March | 160.93 | 90.40 | 70.53 | 143.70 | 104.16 | 0.00 | 0.00 | 744.00 |
April | 129.32 | 61.86 | 67.46 | 107.44 | 74.67 | 0.00 | 0.00 | 720.00 |
May | 114.87 | 38.14 | 76.73 | 86.15 | 60.26 | 0.00 | 0.00 | 744.00 |
June | 114.13 | 33.27 | 80.86 | 93.39 | 44.78 | 0.00 | 0.00 | 720.00 |
July | 123.04 | 45.43 | 77.61 | 115.38 | 36.48 | 0.00 | 0.00 | 744.00 |
August | 146.25 | 73.73 | 72.52 | 147.86 | 41.27 | 0.00 | 0.00 | 744.00 |
September | 162.28 | 99.46 | 62.82 | 170.47 | 57.68 | 0.00 | 0.00 | 720.00 |
October | 169.64 | 117.32 | 52.32 | 175.23 | 79.76 | 0.00 | 0.00 | 744.00 |
November | 154.58 | 111.96 | 42.62 | 152.43 | 99.45 | 0.00 | 0.00 | 720.00 |
December | 134.33 | 96.99 | 37.35 | 122.65 | 137.98 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 143.97 | 82.93 | 61.04 | 133.93 | 84.80 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 114.13 | 33.27 | 37.35 | 86.15 | 36.48 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 179.97 | 129.44 | 80.86 | 175.23 | 163.74 | 0.00 | 0.00 | 744.00 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.316004E+09 | 0.225666E+09 | 90338001.12 | 0.273332E+09 | 0.398605E+09 |
February | 0.363612E+09 | 0.261526E+09 | 0.102086E+09 | 0.341332E+09 | 0.268382E+09 |
March | 0.359988E+09 | 0.202219E+09 | 0.157769E+09 | 0.316202E+09 | 0.263853E+09 |
April | 0.279938E+09 | 0.133906E+09 | 0.146032E+09 | 0.224594E+09 | 0.192846E+09 |
May | 0.256951E+09 | 85313868.24 | 0.171637E+09 | 0.184278E+09 | 0.160557E+09 |
June | 0.247064E+09 | 72023907.49 | 0.175040E+09 | 0.196935E+09 | 0.109250E+09 |
July | 0.275231E+09 | 0.101633E+09 | 0.173598E+09 | 0.256545E+09 | 87420919.12 |
August | 0.327145E+09 | 0.164932E+09 | 0.162213E+09 | 0.329145E+09 | 99727615.47 |
September | 0.351293E+09 | 0.215301E+09 | 0.135992E+09 | 0.365892E+09 | 0.138367E+09 |
October | 0.379464E+09 | 0.262428E+09 | 0.117035E+09 | 0.384690E+09 | 0.203948E+09 |
November | 0.334629E+09 | 0.242372E+09 | 92257076.27 | 0.322859E+09 | 0.245658E+09 |
December | 0.300488E+09 | 0.216951E+09 | 83537300.00 | 0.269661E+09 | 0.341072E+09 |
Annual Sum or Average | 0.379181E+10 | 0.218427E+10 | 0.160754E+10 | 0.346547E+10 | 0.250969E+10 |
Minimum of Months | 0.247064E+09 | 72023907.49 | 83537300.00 | 0.184278E+09 | 87420919.12 |
Maximum of Months | 0.379464E+09 | 0.262428E+09 | 0.175040E+09 | 0.384690E+09 | 0.398605E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.316004E+09 | 0.225666E+09 | 90338001.12 | 0.273332E+09 | 0.398605E+09 |
February | 0.363612E+09 | 0.261526E+09 | 0.102086E+09 | 0.341332E+09 | 0.268382E+09 |
March | 0.359988E+09 | 0.202219E+09 | 0.157769E+09 | 0.316202E+09 | 0.263853E+09 |
April | 0.279938E+09 | 0.133906E+09 | 0.146032E+09 | 0.224594E+09 | 0.192846E+09 |
May | 0.256951E+09 | 85313868.24 | 0.171637E+09 | 0.184278E+09 | 0.160557E+09 |
June | 0.247064E+09 | 72023907.49 | 0.175040E+09 | 0.196935E+09 | 0.109250E+09 |
July | 0.275231E+09 | 0.101633E+09 | 0.173598E+09 | 0.256545E+09 | 87420919.12 |
August | 0.327145E+09 | 0.164932E+09 | 0.162213E+09 | 0.329145E+09 | 99727615.47 |
September | 0.351293E+09 | 0.215301E+09 | 0.135992E+09 | 0.365892E+09 | 0.138367E+09 |
October | 0.379464E+09 | 0.262428E+09 | 0.117035E+09 | 0.384690E+09 | 0.203948E+09 |
November | 0.334629E+09 | 0.242372E+09 | 92257076.27 | 0.322859E+09 | 0.245658E+09 |
December | 0.300488E+09 | 0.216951E+09 | 83537300.00 | 0.269661E+09 | 0.341072E+09 |
Annual Sum or Average | 0.379181E+10 | 0.218427E+10 | 0.160754E+10 | 0.346547E+10 | 0.250969E+10 |
Minimum of Months | 0.247064E+09 | 72023907.49 | 83537300.00 | 0.184278E+09 | 87420919.12 |
Maximum of Months | 0.379464E+09 | 0.262428E+09 | 0.175040E+09 | 0.384690E+09 | 0.398605E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_3
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.316004E+09 | 0.225666E+09 | 90338001.12 | 0.273332E+09 | 0.398605E+09 |
February | 0.363612E+09 | 0.261526E+09 | 0.102086E+09 | 0.341332E+09 | 0.268382E+09 |
March | 0.359988E+09 | 0.202219E+09 | 0.157769E+09 | 0.316202E+09 | 0.263853E+09 |
April | 0.279938E+09 | 0.133906E+09 | 0.146032E+09 | 0.224594E+09 | 0.192846E+09 |
May | 0.256951E+09 | 85313868.24 | 0.171637E+09 | 0.184278E+09 | 0.160557E+09 |
June | 0.247064E+09 | 72023907.49 | 0.175040E+09 | 0.196935E+09 | 0.109250E+09 |
July | 0.275231E+09 | 0.101633E+09 | 0.173598E+09 | 0.256545E+09 | 87420919.12 |
August | 0.327145E+09 | 0.164932E+09 | 0.162213E+09 | 0.329145E+09 | 99727615.47 |
September | 0.351293E+09 | 0.215301E+09 | 0.135992E+09 | 0.365892E+09 | 0.138367E+09 |
October | 0.379464E+09 | 0.262428E+09 | 0.117035E+09 | 0.384690E+09 | 0.203948E+09 |
November | 0.334629E+09 | 0.242372E+09 | 92257076.27 | 0.322859E+09 | 0.245658E+09 |
December | 0.300488E+09 | 0.216951E+09 | 83537300.00 | 0.269661E+09 | 0.341072E+09 |
Annual Sum or Average | 0.379181E+10 | 0.218427E+10 | 0.160754E+10 | 0.346547E+10 | 0.250969E+10 |
Minimum of Months | 0.247064E+09 | 72023907.49 | 83537300.00 | 0.184278E+09 | 87420919.12 |
Maximum of Months | 0.379464E+09 | 0.262428E+09 | 0.175040E+09 | 0.384690E+09 | 0.398605E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_4
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.316004E+09 | 0.225666E+09 | 90338001.12 | 0.273332E+09 | 0.398605E+09 |
February | 0.363612E+09 | 0.261526E+09 | 0.102086E+09 | 0.341332E+09 | 0.268382E+09 |
March | 0.359988E+09 | 0.202219E+09 | 0.157769E+09 | 0.316202E+09 | 0.263853E+09 |
April | 0.279938E+09 | 0.133906E+09 | 0.146032E+09 | 0.224594E+09 | 0.192846E+09 |
May | 0.256951E+09 | 85313868.24 | 0.171637E+09 | 0.184278E+09 | 0.160557E+09 |
June | 0.247064E+09 | 72023907.49 | 0.175040E+09 | 0.196935E+09 | 0.109250E+09 |
July | 0.275231E+09 | 0.101633E+09 | 0.173598E+09 | 0.256545E+09 | 87420919.12 |
August | 0.327145E+09 | 0.164932E+09 | 0.162213E+09 | 0.329145E+09 | 99727615.47 |
September | 0.351293E+09 | 0.215301E+09 | 0.135992E+09 | 0.365892E+09 | 0.138367E+09 |
October | 0.379464E+09 | 0.262428E+09 | 0.117035E+09 | 0.384690E+09 | 0.203948E+09 |
November | 0.334629E+09 | 0.242372E+09 | 92257076.27 | 0.322859E+09 | 0.245658E+09 |
December | 0.300488E+09 | 0.216951E+09 | 83537300.00 | 0.269661E+09 | 0.341072E+09 |
Annual Sum or Average | 0.379181E+10 | 0.218427E+10 | 0.160754E+10 | 0.346547E+10 | 0.250969E+10 |
Minimum of Months | 0.247064E+09 | 72023907.49 | 83537300.00 | 0.184278E+09 | 87420919.12 |
Maximum of Months | 0.379464E+09 | 0.262428E+09 | 0.175040E+09 | 0.384690E+09 | 0.398605E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_DOOR_1
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.380453E+09 | 0.271690E+09 | 0.108762E+09 | 0.330036E+09 | 0.474227E+09 |
February | 0.437770E+09 | 0.314863E+09 | 0.122907E+09 | 0.411767E+09 | 0.319549E+09 |
March | 0.433407E+09 | 0.243461E+09 | 0.189946E+09 | 0.381438E+09 | 0.314183E+09 |
April | 0.337031E+09 | 0.161216E+09 | 0.175815E+09 | 0.270826E+09 | 0.229881E+09 |
May | 0.309355E+09 | 0.102713E+09 | 0.206642E+09 | 0.222250E+09 | 0.191389E+09 |
June | 0.297452E+09 | 86712993.89 | 0.210739E+09 | 0.237105E+09 | 0.130410E+09 |
July | 0.331364E+09 | 0.122361E+09 | 0.209003E+09 | 0.308415E+09 | 0.104579E+09 |
August | 0.393866E+09 | 0.198570E+09 | 0.195296E+09 | 0.395846E+09 | 0.119232E+09 |
September | 0.422938E+09 | 0.259211E+09 | 0.163727E+09 | 0.440391E+09 | 0.165203E+09 |
October | 0.456854E+09 | 0.315950E+09 | 0.140904E+09 | 0.463416E+09 | 0.243331E+09 |
November | 0.402876E+09 | 0.291803E+09 | 0.111073E+09 | 0.389268E+09 | 0.292732E+09 |
December | 0.361772E+09 | 0.261197E+09 | 0.100575E+09 | 0.325491E+09 | 0.406081E+09 |
Annual Sum or Average | 0.456514E+10 | 0.262975E+10 | 0.193539E+10 | 0.417625E+10 | 0.299080E+10 |
Minimum of Months | 0.297452E+09 | 86712993.89 | 0.100575E+09 | 0.222250E+09 | 0.104579E+09 |
Maximum of Months | 0.456854E+09 | 0.315950E+09 | 0.210739E+09 | 0.463416E+09 | 0.474227E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_DOOR_2
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.380453E+09 | 0.271690E+09 | 0.108762E+09 | 0.330036E+09 | 0.474227E+09 |
February | 0.437770E+09 | 0.314863E+09 | 0.122907E+09 | 0.411767E+09 | 0.319549E+09 |
March | 0.433407E+09 | 0.243461E+09 | 0.189946E+09 | 0.381438E+09 | 0.314183E+09 |
April | 0.337031E+09 | 0.161216E+09 | 0.175815E+09 | 0.270826E+09 | 0.229881E+09 |
May | 0.309355E+09 | 0.102713E+09 | 0.206642E+09 | 0.222250E+09 | 0.191389E+09 |
June | 0.297452E+09 | 86712993.89 | 0.210739E+09 | 0.237105E+09 | 0.130410E+09 |
July | 0.331364E+09 | 0.122361E+09 | 0.209003E+09 | 0.308415E+09 | 0.104579E+09 |
August | 0.393866E+09 | 0.198570E+09 | 0.195296E+09 | 0.395846E+09 | 0.119232E+09 |
September | 0.422938E+09 | 0.259211E+09 | 0.163727E+09 | 0.440391E+09 | 0.165203E+09 |
October | 0.456854E+09 | 0.315950E+09 | 0.140904E+09 | 0.463416E+09 | 0.243331E+09 |
November | 0.402876E+09 | 0.291803E+09 | 0.111073E+09 | 0.389268E+09 | 0.292732E+09 |
December | 0.361772E+09 | 0.261197E+09 | 0.100575E+09 | 0.325491E+09 | 0.406081E+09 |
Annual Sum or Average | 0.456514E+10 | 0.262975E+10 | 0.193539E+10 | 0.417625E+10 | 0.299080E+10 |
Minimum of Months | 0.297452E+09 | 86712993.89 | 0.100575E+09 | 0.222250E+09 | 0.104579E+09 |
Maximum of Months | 0.456854E+09 | 0.315950E+09 | 0.210739E+09 | 0.463416E+09 | 0.474227E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.316004E+09 | 0.225666E+09 | 90338001.12 | 0.270063E+09 | 0.412912E+09 |
February | 0.363612E+09 | 0.261526E+09 | 0.102086E+09 | 0.336989E+09 | 0.281605E+09 |
March | 0.359988E+09 | 0.202219E+09 | 0.157769E+09 | 0.311768E+09 | 0.280141E+09 |
April | 0.279938E+09 | 0.133906E+09 | 0.146032E+09 | 0.220116E+09 | 0.206915E+09 |
May | 0.256951E+09 | 85313868.24 | 0.171637E+09 | 0.180787E+09 | 0.170084E+09 |
June | 0.247064E+09 | 72023907.49 | 0.175040E+09 | 0.195397E+09 | 0.112661E+09 |
July | 0.275231E+09 | 0.101633E+09 | 0.173598E+09 | 0.256196E+09 | 88764776.48 |
August | 0.327145E+09 | 0.164932E+09 | 0.162213E+09 | 0.328478E+09 | 0.101791E+09 |
September | 0.351293E+09 | 0.215301E+09 | 0.135992E+09 | 0.364039E+09 | 0.142979E+09 |
October | 0.379464E+09 | 0.262428E+09 | 0.117035E+09 | 0.381160E+09 | 0.212688E+09 |
November | 0.334629E+09 | 0.242372E+09 | 92257076.27 | 0.318521E+09 | 0.258009E+09 |
December | 0.300488E+09 | 0.216951E+09 | 83537300.00 | 0.266247E+09 | 0.354972E+09 |
Annual Sum or Average | 0.379181E+10 | 0.218427E+10 | 0.160754E+10 | 0.342976E+10 | 0.262352E+10 |
Minimum of Months | 0.247064E+09 | 72023907.49 | 83537300.00 | 0.180787E+09 | 88764776.48 |
Maximum of Months | 0.379464E+09 | 0.262428E+09 | 0.175040E+09 | 0.381160E+09 | 0.412912E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.316004E+09 | 0.225666E+09 | 90338001.12 | 0.270063E+09 | 0.412912E+09 |
February | 0.363612E+09 | 0.261526E+09 | 0.102086E+09 | 0.336989E+09 | 0.281605E+09 |
March | 0.359988E+09 | 0.202219E+09 | 0.157769E+09 | 0.311768E+09 | 0.280141E+09 |
April | 0.279938E+09 | 0.133906E+09 | 0.146032E+09 | 0.220116E+09 | 0.206915E+09 |
May | 0.256951E+09 | 85313868.24 | 0.171637E+09 | 0.180787E+09 | 0.170084E+09 |
June | 0.247064E+09 | 72023907.49 | 0.175040E+09 | 0.195397E+09 | 0.112661E+09 |
July | 0.275231E+09 | 0.101633E+09 | 0.173598E+09 | 0.256196E+09 | 88764776.48 |
August | 0.327145E+09 | 0.164932E+09 | 0.162213E+09 | 0.328478E+09 | 0.101791E+09 |
September | 0.351293E+09 | 0.215301E+09 | 0.135992E+09 | 0.364039E+09 | 0.142979E+09 |
October | 0.379464E+09 | 0.262428E+09 | 0.117035E+09 | 0.381160E+09 | 0.212688E+09 |
November | 0.334629E+09 | 0.242372E+09 | 92257076.27 | 0.318521E+09 | 0.258009E+09 |
December | 0.300488E+09 | 0.216951E+09 | 83537300.00 | 0.266247E+09 | 0.354972E+09 |
Annual Sum or Average | 0.379181E+10 | 0.218427E+10 | 0.160754E+10 | 0.342976E+10 | 0.262352E+10 |
Minimum of Months | 0.247064E+09 | 72023907.49 | 83537300.00 | 0.180787E+09 | 88764776.48 |
Maximum of Months | 0.379464E+09 | 0.262428E+09 | 0.175040E+09 | 0.381160E+09 | 0.412912E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_DOOR
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.380453E+09 | 0.271690E+09 | 0.108762E+09 | 0.326113E+09 | 0.491159E+09 |
February | 0.437770E+09 | 0.314863E+09 | 0.122907E+09 | 0.406575E+09 | 0.335175E+09 |
March | 0.433407E+09 | 0.243461E+09 | 0.189946E+09 | 0.376123E+09 | 0.333446E+09 |
April | 0.337031E+09 | 0.161216E+09 | 0.175815E+09 | 0.265455E+09 | 0.246531E+09 |
May | 0.309355E+09 | 0.102713E+09 | 0.206642E+09 | 0.218052E+09 | 0.202644E+09 |
June | 0.297452E+09 | 86712993.89 | 0.210739E+09 | 0.235240E+09 | 0.134429E+09 |
July | 0.331364E+09 | 0.122361E+09 | 0.209003E+09 | 0.307976E+09 | 0.106161E+09 |
August | 0.393866E+09 | 0.198570E+09 | 0.195296E+09 | 0.395040E+09 | 0.121663E+09 |
September | 0.422938E+09 | 0.259211E+09 | 0.163727E+09 | 0.438192E+09 | 0.170637E+09 |
October | 0.456854E+09 | 0.315950E+09 | 0.140904E+09 | 0.459228E+09 | 0.253632E+09 |
November | 0.402876E+09 | 0.291803E+09 | 0.111073E+09 | 0.384103E+09 | 0.307303E+09 |
December | 0.361772E+09 | 0.261197E+09 | 0.100575E+09 | 0.321400E+09 | 0.422509E+09 |
Annual Sum or Average | 0.456514E+10 | 0.262975E+10 | 0.193539E+10 | 0.413350E+10 | 0.312529E+10 |
Minimum of Months | 0.297452E+09 | 86712993.89 | 0.100575E+09 | 0.218052E+09 | 0.106161E+09 |
Maximum of Months | 0.456854E+09 | 0.315950E+09 | 0.210739E+09 | 0.459228E+09 | 0.491159E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.316004E+09 | 0.225666E+09 | 90338001.12 | 0.270960E+09 | 0.401483E+09 |
February | 0.363612E+09 | 0.261526E+09 | 0.102086E+09 | 0.338339E+09 | 0.272701E+09 |
March | 0.359988E+09 | 0.202219E+09 | 0.157769E+09 | 0.312922E+09 | 0.270770E+09 |
April | 0.279938E+09 | 0.133906E+09 | 0.146032E+09 | 0.221241E+09 | 0.200367E+09 |
May | 0.256951E+09 | 85313868.24 | 0.171637E+09 | 0.181217E+09 | 0.167264E+09 |
June | 0.247064E+09 | 72023907.49 | 0.175040E+09 | 0.194668E+09 | 0.116046E+09 |
July | 0.275231E+09 | 0.101633E+09 | 0.173598E+09 | 0.254490E+09 | 94728409.29 |
August | 0.327145E+09 | 0.164932E+09 | 0.162213E+09 | 0.327323E+09 | 0.106994E+09 |
September | 0.351293E+09 | 0.215301E+09 | 0.135992E+09 | 0.363551E+09 | 0.145049E+09 |
October | 0.379464E+09 | 0.262428E+09 | 0.117035E+09 | 0.382123E+09 | 0.208873E+09 |
November | 0.334629E+09 | 0.242372E+09 | 92257076.27 | 0.320069E+09 | 0.249628E+09 |
December | 0.300488E+09 | 0.216951E+09 | 83537300.00 | 0.267303E+09 | 0.344500E+09 |
Annual Sum or Average | 0.379181E+10 | 0.218427E+10 | 0.160754E+10 | 0.343421E+10 | 0.257840E+10 |
Minimum of Months | 0.247064E+09 | 72023907.49 | 83537300.00 | 0.181217E+09 | 94728409.29 |
Maximum of Months | 0.379464E+09 | 0.262428E+09 | 0.175040E+09 | 0.382123E+09 | 0.401483E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.316004E+09 | 0.225666E+09 | 90338001.12 | 0.270960E+09 | 0.401483E+09 |
February | 0.363612E+09 | 0.261526E+09 | 0.102086E+09 | 0.338339E+09 | 0.272701E+09 |
March | 0.359988E+09 | 0.202219E+09 | 0.157769E+09 | 0.312922E+09 | 0.270770E+09 |
April | 0.279938E+09 | 0.133906E+09 | 0.146032E+09 | 0.221241E+09 | 0.200367E+09 |
May | 0.256951E+09 | 85313868.24 | 0.171637E+09 | 0.181217E+09 | 0.167264E+09 |
June | 0.247064E+09 | 72023907.49 | 0.175040E+09 | 0.194668E+09 | 0.116046E+09 |
July | 0.275231E+09 | 0.101633E+09 | 0.173598E+09 | 0.254490E+09 | 94728409.29 |
August | 0.327145E+09 | 0.164932E+09 | 0.162213E+09 | 0.327323E+09 | 0.106994E+09 |
September | 0.351293E+09 | 0.215301E+09 | 0.135992E+09 | 0.363551E+09 | 0.145049E+09 |
October | 0.379464E+09 | 0.262428E+09 | 0.117035E+09 | 0.382123E+09 | 0.208873E+09 |
November | 0.334629E+09 | 0.242372E+09 | 92257076.27 | 0.320069E+09 | 0.249628E+09 |
December | 0.300488E+09 | 0.216951E+09 | 83537300.00 | 0.267303E+09 | 0.344500E+09 |
Annual Sum or Average | 0.379181E+10 | 0.218427E+10 | 0.160754E+10 | 0.343421E+10 | 0.257840E+10 |
Minimum of Months | 0.247064E+09 | 72023907.49 | 83537300.00 | 0.181217E+09 | 94728409.29 |
Maximum of Months | 0.379464E+09 | 0.262428E+09 | 0.175040E+09 | 0.382123E+09 | 0.401483E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_DOOR
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.378374E+09 | 0.270206E+09 | 0.108168E+09 | 0.325426E+09 | 0.474953E+09 |
February | 0.435378E+09 | 0.313143E+09 | 0.122235E+09 | 0.405979E+09 | 0.322819E+09 |
March | 0.431038E+09 | 0.242130E+09 | 0.188908E+09 | 0.375461E+09 | 0.320552E+09 |
April | 0.335189E+09 | 0.160335E+09 | 0.174854E+09 | 0.265359E+09 | 0.237428E+09 |
May | 0.307665E+09 | 0.102152E+09 | 0.205513E+09 | 0.217389E+09 | 0.198144E+09 |
June | 0.295827E+09 | 86239152.39 | 0.209588E+09 | 0.233103E+09 | 0.137613E+09 |
July | 0.329553E+09 | 0.121693E+09 | 0.207861E+09 | 0.304295E+09 | 0.112538E+09 |
August | 0.391714E+09 | 0.197485E+09 | 0.194229E+09 | 0.391525E+09 | 0.127060E+09 |
September | 0.420627E+09 | 0.257795E+09 | 0.162832E+09 | 0.435234E+09 | 0.172074E+09 |
October | 0.454358E+09 | 0.314223E+09 | 0.140134E+09 | 0.457873E+09 | 0.247681E+09 |
November | 0.400674E+09 | 0.290209E+09 | 0.110466E+09 | 0.383860E+09 | 0.295702E+09 |
December | 0.359795E+09 | 0.259770E+09 | 0.100025E+09 | 0.320931E+09 | 0.407821E+09 |
Annual Sum or Average | 0.454019E+10 | 0.261538E+10 | 0.192481E+10 | 0.411643E+10 | 0.305438E+10 |
Minimum of Months | 0.295827E+09 | 86239152.39 | 0.100025E+09 | 0.217389E+09 | 0.112538E+09 |
Maximum of Months | 0.454358E+09 | 0.314223E+09 | 0.209588E+09 | 0.457873E+09 | 0.474953E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.316004E+09 | 0.225666E+09 | 90338001.12 | 0.271410E+09 | 0.397826E+09 |
February | 0.363612E+09 | 0.261526E+09 | 0.102086E+09 | 0.339073E+09 | 0.269329E+09 |
March | 0.359988E+09 | 0.202219E+09 | 0.157769E+09 | 0.313619E+09 | 0.267181E+09 |
April | 0.279938E+09 | 0.133906E+09 | 0.146032E+09 | 0.222147E+09 | 0.196971E+09 |
May | 0.256951E+09 | 85313868.24 | 0.171637E+09 | 0.181881E+09 | 0.164926E+09 |
June | 0.247064E+09 | 72023907.49 | 0.175040E+09 | 0.194782E+09 | 0.115666E+09 |
July | 0.275231E+09 | 0.101633E+09 | 0.173598E+09 | 0.254417E+09 | 94971778.90 |
August | 0.327145E+09 | 0.164932E+09 | 0.162213E+09 | 0.327294E+09 | 0.107045E+09 |
September | 0.351293E+09 | 0.215301E+09 | 0.135992E+09 | 0.363758E+09 | 0.144208E+09 |
October | 0.379464E+09 | 0.262428E+09 | 0.117035E+09 | 0.382817E+09 | 0.206245E+09 |
November | 0.334629E+09 | 0.242372E+09 | 92257076.27 | 0.321002E+09 | 0.245850E+09 |
December | 0.300488E+09 | 0.216951E+09 | 83537300.00 | 0.267848E+09 | 0.340797E+09 |
Annual Sum or Average | 0.379181E+10 | 0.218427E+10 | 0.160754E+10 | 0.344005E+10 | 0.255101E+10 |
Minimum of Months | 0.247064E+09 | 72023907.49 | 83537300.00 | 0.181881E+09 | 94971778.90 |
Maximum of Months | 0.379464E+09 | 0.262428E+09 | 0.175040E+09 | 0.382817E+09 | 0.397826E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.316004E+09 | 0.225666E+09 | 90338001.12 | 0.271410E+09 | 0.397826E+09 |
February | 0.363612E+09 | 0.261526E+09 | 0.102086E+09 | 0.339073E+09 | 0.269329E+09 |
March | 0.359988E+09 | 0.202219E+09 | 0.157769E+09 | 0.313619E+09 | 0.267181E+09 |
April | 0.279938E+09 | 0.133906E+09 | 0.146032E+09 | 0.222147E+09 | 0.196971E+09 |
May | 0.256951E+09 | 85313868.24 | 0.171637E+09 | 0.181881E+09 | 0.164926E+09 |
June | 0.247064E+09 | 72023907.49 | 0.175040E+09 | 0.194782E+09 | 0.115666E+09 |
July | 0.275231E+09 | 0.101633E+09 | 0.173598E+09 | 0.254417E+09 | 94971778.90 |
August | 0.327145E+09 | 0.164932E+09 | 0.162213E+09 | 0.327294E+09 | 0.107045E+09 |
September | 0.351293E+09 | 0.215301E+09 | 0.135992E+09 | 0.363758E+09 | 0.144208E+09 |
October | 0.379464E+09 | 0.262428E+09 | 0.117035E+09 | 0.382817E+09 | 0.206245E+09 |
November | 0.334629E+09 | 0.242372E+09 | 92257076.27 | 0.321002E+09 | 0.245850E+09 |
December | 0.300488E+09 | 0.216951E+09 | 83537300.00 | 0.267848E+09 | 0.340797E+09 |
Annual Sum or Average | 0.379181E+10 | 0.218427E+10 | 0.160754E+10 | 0.344005E+10 | 0.255101E+10 |
Minimum of Months | 0.247064E+09 | 72023907.49 | 83537300.00 | 0.181881E+09 | 94971778.90 |
Maximum of Months | 0.379464E+09 | 0.262428E+09 | 0.175040E+09 | 0.382817E+09 | 0.397826E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_DOOR
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.378374E+09 | 0.270206E+09 | 0.108168E+09 | 0.325975E+09 | 0.470598E+09 |
February | 0.435378E+09 | 0.313143E+09 | 0.122235E+09 | 0.406865E+09 | 0.318814E+09 |
March | 0.431038E+09 | 0.242130E+09 | 0.188908E+09 | 0.376302E+09 | 0.316288E+09 |
April | 0.335189E+09 | 0.160335E+09 | 0.174854E+09 | 0.266449E+09 | 0.233398E+09 |
May | 0.307665E+09 | 0.102152E+09 | 0.205513E+09 | 0.218188E+09 | 0.195369E+09 |
June | 0.295827E+09 | 86239152.39 | 0.209588E+09 | 0.233240E+09 | 0.137161E+09 |
July | 0.329553E+09 | 0.121693E+09 | 0.207861E+09 | 0.304208E+09 | 0.112827E+09 |
August | 0.391714E+09 | 0.197485E+09 | 0.194229E+09 | 0.391489E+09 | 0.127120E+09 |
September | 0.420627E+09 | 0.257795E+09 | 0.162832E+09 | 0.435482E+09 | 0.171076E+09 |
October | 0.454358E+09 | 0.314223E+09 | 0.140134E+09 | 0.458707E+09 | 0.244564E+09 |
November | 0.400674E+09 | 0.290209E+09 | 0.110466E+09 | 0.384979E+09 | 0.291217E+09 |
December | 0.359795E+09 | 0.259770E+09 | 0.100025E+09 | 0.321593E+09 | 0.403420E+09 |
Annual Sum or Average | 0.454019E+10 | 0.261538E+10 | 0.192481E+10 | 0.412348E+10 | 0.302185E+10 |
Minimum of Months | 0.295827E+09 | 86239152.39 | 0.100025E+09 | 0.218188E+09 | 0.112827E+09 |
Maximum of Months | 0.454358E+09 | 0.314223E+09 | 0.209588E+09 | 0.458707E+09 | 0.470598E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.316004E+09 | 0.225666E+09 | 90338001.12 | 0.271916E+09 | 0.395230E+09 |
February | 0.363612E+09 | 0.261526E+09 | 0.102086E+09 | 0.339916E+09 | 0.266691E+09 |
March | 0.359988E+09 | 0.202219E+09 | 0.157769E+09 | 0.314438E+09 | 0.264267E+09 |
April | 0.279938E+09 | 0.133906E+09 | 0.146032E+09 | 0.223375E+09 | 0.193612E+09 |
May | 0.256951E+09 | 85313868.24 | 0.171637E+09 | 0.183002E+09 | 0.162238E+09 |
June | 0.247064E+09 | 72023907.49 | 0.175040E+09 | 0.195342E+09 | 0.114345E+09 |
July | 0.275231E+09 | 0.101633E+09 | 0.173598E+09 | 0.254831E+09 | 93921633.60 |
August | 0.327145E+09 | 0.164932E+09 | 0.162213E+09 | 0.327705E+09 | 0.105839E+09 |
September | 0.351293E+09 | 0.215301E+09 | 0.135992E+09 | 0.364363E+09 | 0.142506E+09 |
October | 0.379464E+09 | 0.262428E+09 | 0.117035E+09 | 0.383909E+09 | 0.203400E+09 |
November | 0.334629E+09 | 0.242372E+09 | 92257076.27 | 0.322191E+09 | 0.242445E+09 |
December | 0.300488E+09 | 0.216951E+09 | 83537300.00 | 0.268486E+09 | 0.337986E+09 |
Annual Sum or Average | 0.379181E+10 | 0.218427E+10 | 0.160754E+10 | 0.344947E+10 | 0.252248E+10 |
Minimum of Months | 0.247064E+09 | 72023907.49 | 83537300.00 | 0.183002E+09 | 93921633.60 |
Maximum of Months | 0.379464E+09 | 0.262428E+09 | 0.175040E+09 | 0.383909E+09 | 0.395230E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.316004E+09 | 0.225666E+09 | 90338001.12 | 0.271916E+09 | 0.395230E+09 |
February | 0.363612E+09 | 0.261526E+09 | 0.102086E+09 | 0.339916E+09 | 0.266691E+09 |
March | 0.359988E+09 | 0.202219E+09 | 0.157769E+09 | 0.314438E+09 | 0.264267E+09 |
April | 0.279938E+09 | 0.133906E+09 | 0.146032E+09 | 0.223375E+09 | 0.193612E+09 |
May | 0.256951E+09 | 85313868.24 | 0.171637E+09 | 0.183002E+09 | 0.162238E+09 |
June | 0.247064E+09 | 72023907.49 | 0.175040E+09 | 0.195342E+09 | 0.114345E+09 |
July | 0.275231E+09 | 0.101633E+09 | 0.173598E+09 | 0.254831E+09 | 93921633.60 |
August | 0.327145E+09 | 0.164932E+09 | 0.162213E+09 | 0.327705E+09 | 0.105839E+09 |
September | 0.351293E+09 | 0.215301E+09 | 0.135992E+09 | 0.364363E+09 | 0.142506E+09 |
October | 0.379464E+09 | 0.262428E+09 | 0.117035E+09 | 0.383909E+09 | 0.203400E+09 |
November | 0.334629E+09 | 0.242372E+09 | 92257076.27 | 0.322191E+09 | 0.242445E+09 |
December | 0.300488E+09 | 0.216951E+09 | 83537300.00 | 0.268486E+09 | 0.337986E+09 |
Annual Sum or Average | 0.379181E+10 | 0.218427E+10 | 0.160754E+10 | 0.344947E+10 | 0.252248E+10 |
Minimum of Months | 0.247064E+09 | 72023907.49 | 83537300.00 | 0.183002E+09 | 93921633.60 |
Maximum of Months | 0.379464E+09 | 0.262428E+09 | 0.175040E+09 | 0.383909E+09 | 0.395230E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_DOOR
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.378374E+09 | 0.270206E+09 | 0.108168E+09 | 0.326593E+09 | 0.467505E+09 |
February | 0.435378E+09 | 0.313143E+09 | 0.122235E+09 | 0.407882E+09 | 0.315682E+09 |
March | 0.431038E+09 | 0.242130E+09 | 0.188908E+09 | 0.377291E+09 | 0.312825E+09 |
April | 0.335189E+09 | 0.160335E+09 | 0.174854E+09 | 0.267920E+09 | 0.229413E+09 |
May | 0.307665E+09 | 0.102152E+09 | 0.205513E+09 | 0.219536E+09 | 0.192184E+09 |
June | 0.295827E+09 | 86239152.39 | 0.209588E+09 | 0.233917E+09 | 0.135601E+09 |
July | 0.329553E+09 | 0.121693E+09 | 0.207861E+09 | 0.304707E+09 | 0.111586E+09 |
August | 0.391714E+09 | 0.197485E+09 | 0.194229E+09 | 0.391987E+09 | 0.125693E+09 |
September | 0.420627E+09 | 0.257795E+09 | 0.162832E+09 | 0.436209E+09 | 0.169061E+09 |
October | 0.454358E+09 | 0.314223E+09 | 0.140134E+09 | 0.460018E+09 | 0.241196E+09 |
November | 0.400674E+09 | 0.290209E+09 | 0.110466E+09 | 0.386406E+09 | 0.287179E+09 |
December | 0.359795E+09 | 0.259770E+09 | 0.100025E+09 | 0.322366E+09 | 0.400075E+09 |
Annual Sum or Average | 0.454019E+10 | 0.261538E+10 | 0.192481E+10 | 0.413483E+10 | 0.298800E+10 |
Minimum of Months | 0.295827E+09 | 86239152.39 | 0.100025E+09 | 0.219536E+09 | 0.111586E+09 |
Maximum of Months | 0.454358E+09 | 0.314223E+09 | 0.209588E+09 | 0.460018E+09 | 0.467505E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.316004E+09 | 0.225666E+09 | 90338001.12 | 0.274733E+09 | 0.384622E+09 |
February | 0.363612E+09 | 0.261526E+09 | 0.102086E+09 | 0.343530E+09 | 0.257779E+09 |
March | 0.359988E+09 | 0.202219E+09 | 0.157769E+09 | 0.317485E+09 | 0.255106E+09 |
April | 0.279938E+09 | 0.133906E+09 | 0.146032E+09 | 0.226644E+09 | 0.185051E+09 |
May | 0.256951E+09 | 85313868.24 | 0.171637E+09 | 0.185938E+09 | 0.154717E+09 |
June | 0.247064E+09 | 72023907.49 | 0.175040E+09 | 0.196649E+09 | 0.109759E+09 |
July | 0.275231E+09 | 0.101633E+09 | 0.173598E+09 | 0.255247E+09 | 89962593.23 |
August | 0.327145E+09 | 0.164932E+09 | 0.162213E+09 | 0.328465E+09 | 0.101454E+09 |
September | 0.351293E+09 | 0.215301E+09 | 0.135992E+09 | 0.366127E+09 | 0.137338E+09 |
October | 0.379464E+09 | 0.262428E+09 | 0.117035E+09 | 0.387376E+09 | 0.195868E+09 |
November | 0.334629E+09 | 0.242372E+09 | 92257076.27 | 0.325926E+09 | 0.233195E+09 |
December | 0.300488E+09 | 0.216951E+09 | 83537300.00 | 0.271577E+09 | 0.327768E+09 |
Annual Sum or Average | 0.379181E+10 | 0.218427E+10 | 0.160754E+10 | 0.347970E+10 | 0.243262E+10 |
Minimum of Months | 0.247064E+09 | 72023907.49 | 83537300.00 | 0.185938E+09 | 89962593.23 |
Maximum of Months | 0.379464E+09 | 0.262428E+09 | 0.175040E+09 | 0.387376E+09 | 0.384622E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.316004E+09 | 0.225666E+09 | 90338001.12 | 0.274733E+09 | 0.384622E+09 |
February | 0.363612E+09 | 0.261526E+09 | 0.102086E+09 | 0.343530E+09 | 0.257779E+09 |
March | 0.359988E+09 | 0.202219E+09 | 0.157769E+09 | 0.317485E+09 | 0.255106E+09 |
April | 0.279938E+09 | 0.133906E+09 | 0.146032E+09 | 0.226644E+09 | 0.185051E+09 |
May | 0.256951E+09 | 85313868.24 | 0.171637E+09 | 0.185938E+09 | 0.154717E+09 |
June | 0.247064E+09 | 72023907.49 | 0.175040E+09 | 0.196649E+09 | 0.109759E+09 |
July | 0.275231E+09 | 0.101633E+09 | 0.173598E+09 | 0.255247E+09 | 89962593.23 |
August | 0.327145E+09 | 0.164932E+09 | 0.162213E+09 | 0.328465E+09 | 0.101454E+09 |
September | 0.351293E+09 | 0.215301E+09 | 0.135992E+09 | 0.366127E+09 | 0.137338E+09 |
October | 0.379464E+09 | 0.262428E+09 | 0.117035E+09 | 0.387376E+09 | 0.195868E+09 |
November | 0.334629E+09 | 0.242372E+09 | 92257076.27 | 0.325926E+09 | 0.233195E+09 |
December | 0.300488E+09 | 0.216951E+09 | 83537300.00 | 0.271577E+09 | 0.327768E+09 |
Annual Sum or Average | 0.379181E+10 | 0.218427E+10 | 0.160754E+10 | 0.347970E+10 | 0.243262E+10 |
Minimum of Months | 0.247064E+09 | 72023907.49 | 83537300.00 | 0.185938E+09 | 89962593.23 |
Maximum of Months | 0.379464E+09 | 0.262428E+09 | 0.175040E+09 | 0.387376E+09 | 0.384622E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_3
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.316004E+09 | 0.225666E+09 | 90338001.12 | 0.274733E+09 | 0.384622E+09 |
February | 0.363612E+09 | 0.261526E+09 | 0.102086E+09 | 0.343530E+09 | 0.257779E+09 |
March | 0.359988E+09 | 0.202219E+09 | 0.157769E+09 | 0.317485E+09 | 0.255106E+09 |
April | 0.279938E+09 | 0.133906E+09 | 0.146032E+09 | 0.226644E+09 | 0.185051E+09 |
May | 0.256951E+09 | 85313868.24 | 0.171637E+09 | 0.185938E+09 | 0.154717E+09 |
June | 0.247064E+09 | 72023907.49 | 0.175040E+09 | 0.196649E+09 | 0.109759E+09 |
July | 0.275231E+09 | 0.101633E+09 | 0.173598E+09 | 0.255247E+09 | 89962593.23 |
August | 0.327145E+09 | 0.164932E+09 | 0.162213E+09 | 0.328465E+09 | 0.101454E+09 |
September | 0.351293E+09 | 0.215301E+09 | 0.135992E+09 | 0.366127E+09 | 0.137338E+09 |
October | 0.379464E+09 | 0.262428E+09 | 0.117035E+09 | 0.387376E+09 | 0.195868E+09 |
November | 0.334629E+09 | 0.242372E+09 | 92257076.27 | 0.325926E+09 | 0.233195E+09 |
December | 0.300488E+09 | 0.216951E+09 | 83537300.00 | 0.271577E+09 | 0.327768E+09 |
Annual Sum or Average | 0.379181E+10 | 0.218427E+10 | 0.160754E+10 | 0.347970E+10 | 0.243262E+10 |
Minimum of Months | 0.247064E+09 | 72023907.49 | 83537300.00 | 0.185938E+09 | 89962593.23 |
Maximum of Months | 0.379464E+09 | 0.262428E+09 | 0.175040E+09 | 0.387376E+09 | 0.384622E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_4
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.316004E+09 | 0.225666E+09 | 90338001.12 | 0.274733E+09 | 0.384622E+09 |
February | 0.363612E+09 | 0.261526E+09 | 0.102086E+09 | 0.343530E+09 | 0.257779E+09 |
March | 0.359988E+09 | 0.202219E+09 | 0.157769E+09 | 0.317485E+09 | 0.255106E+09 |
April | 0.279938E+09 | 0.133906E+09 | 0.146032E+09 | 0.226644E+09 | 0.185051E+09 |
May | 0.256951E+09 | 85313868.24 | 0.171637E+09 | 0.185938E+09 | 0.154717E+09 |
June | 0.247064E+09 | 72023907.49 | 0.175040E+09 | 0.196649E+09 | 0.109759E+09 |
July | 0.275231E+09 | 0.101633E+09 | 0.173598E+09 | 0.255247E+09 | 89962593.23 |
August | 0.327145E+09 | 0.164932E+09 | 0.162213E+09 | 0.328465E+09 | 0.101454E+09 |
September | 0.351293E+09 | 0.215301E+09 | 0.135992E+09 | 0.366127E+09 | 0.137338E+09 |
October | 0.379464E+09 | 0.262428E+09 | 0.117035E+09 | 0.387376E+09 | 0.195868E+09 |
November | 0.334629E+09 | 0.242372E+09 | 92257076.27 | 0.325926E+09 | 0.233195E+09 |
December | 0.300488E+09 | 0.216951E+09 | 83537300.00 | 0.271577E+09 | 0.327768E+09 |
Annual Sum or Average | 0.379181E+10 | 0.218427E+10 | 0.160754E+10 | 0.347970E+10 | 0.243262E+10 |
Minimum of Months | 0.247064E+09 | 72023907.49 | 83537300.00 | 0.185938E+09 | 89962593.23 |
Maximum of Months | 0.379464E+09 | 0.262428E+09 | 0.175040E+09 | 0.387376E+09 | 0.384622E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_DOOR_1
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.378374E+09 | 0.270206E+09 | 0.108168E+09 | 0.329948E+09 | 0.455029E+09 |
February | 0.435378E+09 | 0.313143E+09 | 0.122235E+09 | 0.412180E+09 | 0.305201E+09 |
March | 0.431038E+09 | 0.242130E+09 | 0.188908E+09 | 0.380932E+09 | 0.302045E+09 |
April | 0.335189E+09 | 0.160335E+09 | 0.174854E+09 | 0.271827E+09 | 0.219311E+09 |
May | 0.307665E+09 | 0.102152E+09 | 0.205513E+09 | 0.223064E+09 | 0.183328E+09 |
June | 0.295827E+09 | 86239152.39 | 0.209588E+09 | 0.235513E+09 | 0.130204E+09 |
July | 0.329553E+09 | 0.121693E+09 | 0.207861E+09 | 0.305254E+09 | 0.106915E+09 |
August | 0.391714E+09 | 0.197485E+09 | 0.194229E+09 | 0.392927E+09 | 0.120520E+09 |
September | 0.420627E+09 | 0.257795E+09 | 0.162832E+09 | 0.438315E+09 | 0.162971E+09 |
October | 0.454358E+09 | 0.314223E+09 | 0.140134E+09 | 0.464125E+09 | 0.232320E+09 |
November | 0.400674E+09 | 0.290209E+09 | 0.110466E+09 | 0.390838E+09 | 0.276284E+09 |
December | 0.359795E+09 | 0.259770E+09 | 0.100025E+09 | 0.326052E+09 | 0.388047E+09 |
Annual Sum or Average | 0.454019E+10 | 0.261538E+10 | 0.192481E+10 | 0.417098E+10 | 0.288218E+10 |
Minimum of Months | 0.295827E+09 | 86239152.39 | 0.100025E+09 | 0.223064E+09 | 0.106915E+09 |
Maximum of Months | 0.454358E+09 | 0.314223E+09 | 0.209588E+09 | 0.464125E+09 | 0.455029E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_DOOR_2
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.378374E+09 | 0.270206E+09 | 0.108168E+09 | 0.329948E+09 | 0.455029E+09 |
February | 0.435378E+09 | 0.313143E+09 | 0.122235E+09 | 0.412180E+09 | 0.305201E+09 |
March | 0.431038E+09 | 0.242130E+09 | 0.188908E+09 | 0.380932E+09 | 0.302045E+09 |
April | 0.335189E+09 | 0.160335E+09 | 0.174854E+09 | 0.271827E+09 | 0.219311E+09 |
May | 0.307665E+09 | 0.102152E+09 | 0.205513E+09 | 0.223064E+09 | 0.183328E+09 |
June | 0.295827E+09 | 86239152.39 | 0.209588E+09 | 0.235513E+09 | 0.130204E+09 |
July | 0.329553E+09 | 0.121693E+09 | 0.207861E+09 | 0.305254E+09 | 0.106915E+09 |
August | 0.391714E+09 | 0.197485E+09 | 0.194229E+09 | 0.392927E+09 | 0.120520E+09 |
September | 0.420627E+09 | 0.257795E+09 | 0.162832E+09 | 0.438315E+09 | 0.162971E+09 |
October | 0.454358E+09 | 0.314223E+09 | 0.140134E+09 | 0.464125E+09 | 0.232320E+09 |
November | 0.400674E+09 | 0.290209E+09 | 0.110466E+09 | 0.390838E+09 | 0.276284E+09 |
December | 0.359795E+09 | 0.259770E+09 | 0.100025E+09 | 0.326052E+09 | 0.388047E+09 |
Annual Sum or Average | 0.454019E+10 | 0.261538E+10 | 0.192481E+10 | 0.417098E+10 | 0.288218E+10 |
Minimum of Months | 0.295827E+09 | 86239152.39 | 0.100025E+09 | 0.223064E+09 | 0.106915E+09 |
Maximum of Months | 0.454358E+09 | 0.314223E+09 | 0.209588E+09 | 0.464125E+09 | 0.455029E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.316004E+09 | 0.225666E+09 | 90338001.12 | 0.273440E+09 | 0.387184E+09 |
February | 0.363612E+09 | 0.261526E+09 | 0.102086E+09 | 0.342358E+09 | 0.259138E+09 |
March | 0.359988E+09 | 0.202219E+09 | 0.157769E+09 | 0.316550E+09 | 0.256036E+09 |
April | 0.279938E+09 | 0.133906E+09 | 0.146032E+09 | 0.226549E+09 | 0.184883E+09 |
May | 0.256951E+09 | 85313868.24 | 0.171637E+09 | 0.186134E+09 | 0.154470E+09 |
June | 0.247064E+09 | 72023907.49 | 0.175040E+09 | 0.197184E+09 | 0.109207E+09 |
July | 0.275231E+09 | 0.101633E+09 | 0.173598E+09 | 0.256137E+09 | 89082919.21 |
August | 0.327145E+09 | 0.164932E+09 | 0.162213E+09 | 0.328995E+09 | 0.100613E+09 |
September | 0.351293E+09 | 0.215301E+09 | 0.135992E+09 | 0.366055E+09 | 0.136851E+09 |
October | 0.379464E+09 | 0.262428E+09 | 0.117035E+09 | 0.386874E+09 | 0.195620E+09 |
November | 0.334629E+09 | 0.242372E+09 | 92257076.27 | 0.325177E+09 | 0.233798E+09 |
December | 0.300488E+09 | 0.216951E+09 | 83537300.00 | 0.270368E+09 | 0.329683E+09 |
Annual Sum or Average | 0.379181E+10 | 0.218427E+10 | 0.160754E+10 | 0.347582E+10 | 0.243657E+10 |
Minimum of Months | 0.247064E+09 | 72023907.49 | 83537300.00 | 0.186134E+09 | 89082919.21 |
Maximum of Months | 0.379464E+09 | 0.262428E+09 | 0.175040E+09 | 0.386874E+09 | 0.387184E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.316004E+09 | 0.225666E+09 | 90338001.12 | 0.273440E+09 | 0.387184E+09 |
February | 0.363612E+09 | 0.261526E+09 | 0.102086E+09 | 0.342358E+09 | 0.259138E+09 |
March | 0.359988E+09 | 0.202219E+09 | 0.157769E+09 | 0.316550E+09 | 0.256036E+09 |
April | 0.279938E+09 | 0.133906E+09 | 0.146032E+09 | 0.226549E+09 | 0.184883E+09 |
May | 0.256951E+09 | 85313868.24 | 0.171637E+09 | 0.186134E+09 | 0.154470E+09 |
June | 0.247064E+09 | 72023907.49 | 0.175040E+09 | 0.197184E+09 | 0.109207E+09 |
July | 0.275231E+09 | 0.101633E+09 | 0.173598E+09 | 0.256137E+09 | 89082919.21 |
August | 0.327145E+09 | 0.164932E+09 | 0.162213E+09 | 0.328995E+09 | 0.100613E+09 |
September | 0.351293E+09 | 0.215301E+09 | 0.135992E+09 | 0.366055E+09 | 0.136851E+09 |
October | 0.379464E+09 | 0.262428E+09 | 0.117035E+09 | 0.386874E+09 | 0.195620E+09 |
November | 0.334629E+09 | 0.242372E+09 | 92257076.27 | 0.325177E+09 | 0.233798E+09 |
December | 0.300488E+09 | 0.216951E+09 | 83537300.00 | 0.270368E+09 | 0.329683E+09 |
Annual Sum or Average | 0.379181E+10 | 0.218427E+10 | 0.160754E+10 | 0.347582E+10 | 0.243657E+10 |
Minimum of Months | 0.247064E+09 | 72023907.49 | 83537300.00 | 0.186134E+09 | 89082919.21 |
Maximum of Months | 0.379464E+09 | 0.262428E+09 | 0.175040E+09 | 0.386874E+09 | 0.387184E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_DOOR
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.378374E+09 | 0.270206E+09 | 0.108168E+09 | 0.328464E+09 | 0.457934E+09 |
February | 0.435378E+09 | 0.313143E+09 | 0.122235E+09 | 0.410847E+09 | 0.306719E+09 |
March | 0.431038E+09 | 0.242130E+09 | 0.188908E+09 | 0.379877E+09 | 0.303051E+09 |
April | 0.335189E+09 | 0.160335E+09 | 0.174854E+09 | 0.271750E+09 | 0.219044E+09 |
May | 0.307665E+09 | 0.102152E+09 | 0.205513E+09 | 0.223326E+09 | 0.182976E+09 |
June | 0.295827E+09 | 86239152.39 | 0.209588E+09 | 0.236168E+09 | 0.129516E+09 |
July | 0.329553E+09 | 0.121693E+09 | 0.207861E+09 | 0.306321E+09 | 0.105853E+09 |
August | 0.391714E+09 | 0.197485E+09 | 0.194229E+09 | 0.393582E+09 | 0.119497E+09 |
September | 0.420627E+09 | 0.257795E+09 | 0.162832E+09 | 0.438272E+09 | 0.162348E+09 |
October | 0.454358E+09 | 0.314223E+09 | 0.140134E+09 | 0.463591E+09 | 0.231962E+09 |
November | 0.400674E+09 | 0.290209E+09 | 0.110466E+09 | 0.390006E+09 | 0.276916E+09 |
December | 0.359795E+09 | 0.259770E+09 | 0.100025E+09 | 0.324670E+09 | 0.390209E+09 |
Annual Sum or Average | 0.454019E+10 | 0.261538E+10 | 0.192481E+10 | 0.416687E+10 | 0.288603E+10 |
Minimum of Months | 0.295827E+09 | 86239152.39 | 0.100025E+09 | 0.223326E+09 | 0.105853E+09 |
Maximum of Months | 0.454358E+09 | 0.314223E+09 | 0.209588E+09 | 0.463591E+09 | 0.457934E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.316004E+09 | 0.225666E+09 | 90338001.12 | 0.273555E+09 | 0.386625E+09 |
February | 0.363612E+09 | 0.261526E+09 | 0.102086E+09 | 0.342610E+09 | 0.258421E+09 |
March | 0.359988E+09 | 0.202219E+09 | 0.157769E+09 | 0.316810E+09 | 0.255086E+09 |
April | 0.279938E+09 | 0.133906E+09 | 0.146032E+09 | 0.227059E+09 | 0.183483E+09 |
May | 0.256951E+09 | 85313868.24 | 0.171637E+09 | 0.186708E+09 | 0.153252E+09 |
June | 0.247064E+09 | 72023907.49 | 0.175040E+09 | 0.197601E+09 | 0.108503E+09 |
July | 0.275231E+09 | 0.101633E+09 | 0.173598E+09 | 0.256437E+09 | 88580358.49 |
August | 0.327145E+09 | 0.164932E+09 | 0.162213E+09 | 0.329270E+09 | 0.100053E+09 |
September | 0.351293E+09 | 0.215301E+09 | 0.135992E+09 | 0.366393E+09 | 0.136052E+09 |
October | 0.379464E+09 | 0.262428E+09 | 0.117035E+09 | 0.387393E+09 | 0.194395E+09 |
November | 0.334629E+09 | 0.242372E+09 | 92257076.27 | 0.325538E+09 | 0.232776E+09 |
December | 0.300488E+09 | 0.216951E+09 | 83537300.00 | 0.270547E+09 | 0.328948E+09 |
Annual Sum or Average | 0.379181E+10 | 0.218427E+10 | 0.160754E+10 | 0.347992E+10 | 0.242617E+10 |
Minimum of Months | 0.247064E+09 | 72023907.49 | 83537300.00 | 0.186708E+09 | 88580358.49 |
Maximum of Months | 0.379464E+09 | 0.262428E+09 | 0.175040E+09 | 0.387393E+09 | 0.386625E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.316004E+09 | 0.225666E+09 | 90338001.12 | 0.273555E+09 | 0.386625E+09 |
February | 0.363612E+09 | 0.261526E+09 | 0.102086E+09 | 0.342610E+09 | 0.258421E+09 |
March | 0.359988E+09 | 0.202219E+09 | 0.157769E+09 | 0.316810E+09 | 0.255086E+09 |
April | 0.279938E+09 | 0.133906E+09 | 0.146032E+09 | 0.227059E+09 | 0.183483E+09 |
May | 0.256951E+09 | 85313868.24 | 0.171637E+09 | 0.186708E+09 | 0.153252E+09 |
June | 0.247064E+09 | 72023907.49 | 0.175040E+09 | 0.197601E+09 | 0.108503E+09 |
July | 0.275231E+09 | 0.101633E+09 | 0.173598E+09 | 0.256437E+09 | 88580358.49 |
August | 0.327145E+09 | 0.164932E+09 | 0.162213E+09 | 0.329270E+09 | 0.100053E+09 |
September | 0.351293E+09 | 0.215301E+09 | 0.135992E+09 | 0.366393E+09 | 0.136052E+09 |
October | 0.379464E+09 | 0.262428E+09 | 0.117035E+09 | 0.387393E+09 | 0.194395E+09 |
November | 0.334629E+09 | 0.242372E+09 | 92257076.27 | 0.325538E+09 | 0.232776E+09 |
December | 0.300488E+09 | 0.216951E+09 | 83537300.00 | 0.270547E+09 | 0.328948E+09 |
Annual Sum or Average | 0.379181E+10 | 0.218427E+10 | 0.160754E+10 | 0.347992E+10 | 0.242617E+10 |
Minimum of Months | 0.247064E+09 | 72023907.49 | 83537300.00 | 0.186708E+09 | 88580358.49 |
Maximum of Months | 0.379464E+09 | 0.262428E+09 | 0.175040E+09 | 0.387393E+09 | 0.386625E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_DOOR
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.378374E+09 | 0.270206E+09 | 0.108168E+09 | 0.328603E+09 | 0.457266E+09 |
February | 0.435378E+09 | 0.313143E+09 | 0.122235E+09 | 0.411152E+09 | 0.305867E+09 |
March | 0.431038E+09 | 0.242130E+09 | 0.188908E+09 | 0.380191E+09 | 0.301920E+09 |
April | 0.335189E+09 | 0.160335E+09 | 0.174854E+09 | 0.272362E+09 | 0.217380E+09 |
May | 0.307665E+09 | 0.102152E+09 | 0.205513E+09 | 0.224018E+09 | 0.181531E+09 |
June | 0.295827E+09 | 86239152.39 | 0.209588E+09 | 0.236672E+09 | 0.128681E+09 |
July | 0.329553E+09 | 0.121693E+09 | 0.207861E+09 | 0.306682E+09 | 0.105257E+09 |
August | 0.391714E+09 | 0.197485E+09 | 0.194229E+09 | 0.393914E+09 | 0.118832E+09 |
September | 0.420627E+09 | 0.257795E+09 | 0.162832E+09 | 0.438679E+09 | 0.161400E+09 |
October | 0.454358E+09 | 0.314223E+09 | 0.140134E+09 | 0.464211E+09 | 0.230510E+09 |
November | 0.400674E+09 | 0.290209E+09 | 0.110466E+09 | 0.390440E+09 | 0.275702E+09 |
December | 0.359795E+09 | 0.259770E+09 | 0.100025E+09 | 0.324888E+09 | 0.389334E+09 |
Annual Sum or Average | 0.454019E+10 | 0.261538E+10 | 0.192481E+10 | 0.417181E+10 | 0.287368E+10 |
Minimum of Months | 0.295827E+09 | 86239152.39 | 0.100025E+09 | 0.224018E+09 | 0.105257E+09 |
Maximum of Months | 0.454358E+09 | 0.314223E+09 | 0.209588E+09 | 0.464211E+09 | 0.457266E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.316004E+09 | 0.225666E+09 | 90338001.12 | 0.274000E+09 | 0.383950E+09 |
February | 0.363612E+09 | 0.261526E+09 | 0.102086E+09 | 0.343430E+09 | 0.255454E+09 |
March | 0.359988E+09 | 0.202219E+09 | 0.157769E+09 | 0.317606E+09 | 0.251483E+09 |
April | 0.279938E+09 | 0.133906E+09 | 0.146032E+09 | 0.228361E+09 | 0.179228E+09 |
May | 0.256951E+09 | 85313868.24 | 0.171637E+09 | 0.188141E+09 | 0.149621E+09 |
June | 0.247064E+09 | 72023907.49 | 0.175040E+09 | 0.198679E+09 | 0.106403E+09 |
July | 0.275231E+09 | 0.101633E+09 | 0.173598E+09 | 0.256988E+09 | 87352016.31 |
August | 0.327145E+09 | 0.164932E+09 | 0.162213E+09 | 0.329777E+09 | 98679124.33 |
September | 0.351293E+09 | 0.215301E+09 | 0.135992E+09 | 0.367142E+09 | 0.133944E+09 |
October | 0.379464E+09 | 0.262428E+09 | 0.117035E+09 | 0.388605E+09 | 0.191143E+09 |
November | 0.334629E+09 | 0.242372E+09 | 92257076.27 | 0.326472E+09 | 0.229638E+09 |
December | 0.300488E+09 | 0.216951E+09 | 83537300.00 | 0.271153E+09 | 0.325820E+09 |
Annual Sum or Average | 0.379181E+10 | 0.218427E+10 | 0.160754E+10 | 0.349035E+10 | 0.239271E+10 |
Minimum of Months | 0.247064E+09 | 72023907.49 | 83537300.00 | 0.188141E+09 | 87352016.31 |
Maximum of Months | 0.379464E+09 | 0.262428E+09 | 0.175040E+09 | 0.388605E+09 | 0.383950E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.316004E+09 | 0.225666E+09 | 90338001.12 | 0.274000E+09 | 0.383950E+09 |
February | 0.363612E+09 | 0.261526E+09 | 0.102086E+09 | 0.343430E+09 | 0.255454E+09 |
March | 0.359988E+09 | 0.202219E+09 | 0.157769E+09 | 0.317606E+09 | 0.251483E+09 |
April | 0.279938E+09 | 0.133906E+09 | 0.146032E+09 | 0.228361E+09 | 0.179228E+09 |
May | 0.256951E+09 | 85313868.24 | 0.171637E+09 | 0.188141E+09 | 0.149621E+09 |
June | 0.247064E+09 | 72023907.49 | 0.175040E+09 | 0.198679E+09 | 0.106403E+09 |
July | 0.275231E+09 | 0.101633E+09 | 0.173598E+09 | 0.256988E+09 | 87352016.31 |
August | 0.327145E+09 | 0.164932E+09 | 0.162213E+09 | 0.329777E+09 | 98679124.33 |
September | 0.351293E+09 | 0.215301E+09 | 0.135992E+09 | 0.367142E+09 | 0.133944E+09 |
October | 0.379464E+09 | 0.262428E+09 | 0.117035E+09 | 0.388605E+09 | 0.191143E+09 |
November | 0.334629E+09 | 0.242372E+09 | 92257076.27 | 0.326472E+09 | 0.229638E+09 |
December | 0.300488E+09 | 0.216951E+09 | 83537300.00 | 0.271153E+09 | 0.325820E+09 |
Annual Sum or Average | 0.379181E+10 | 0.218427E+10 | 0.160754E+10 | 0.349035E+10 | 0.239271E+10 |
Minimum of Months | 0.247064E+09 | 72023907.49 | 83537300.00 | 0.188141E+09 | 87352016.31 |
Maximum of Months | 0.379464E+09 | 0.262428E+09 | 0.175040E+09 | 0.388605E+09 | 0.383950E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_DOOR
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.378374E+09 | 0.270206E+09 | 0.108168E+09 | 0.329143E+09 | 0.454078E+09 |
February | 0.435378E+09 | 0.313143E+09 | 0.122235E+09 | 0.412142E+09 | 0.302345E+09 |
March | 0.431038E+09 | 0.242130E+09 | 0.188908E+09 | 0.381162E+09 | 0.297641E+09 |
April | 0.335189E+09 | 0.160335E+09 | 0.174854E+09 | 0.273927E+09 | 0.212328E+09 |
May | 0.307665E+09 | 0.102152E+09 | 0.205513E+09 | 0.225744E+09 | 0.177231E+09 |
June | 0.295827E+09 | 86239152.39 | 0.209588E+09 | 0.237968E+09 | 0.126197E+09 |
July | 0.329553E+09 | 0.121693E+09 | 0.207861E+09 | 0.307347E+09 | 0.103806E+09 |
August | 0.391714E+09 | 0.197485E+09 | 0.194229E+09 | 0.394525E+09 | 0.117208E+09 |
September | 0.420627E+09 | 0.257795E+09 | 0.162832E+09 | 0.439579E+09 | 0.158904E+09 |
October | 0.454358E+09 | 0.314223E+09 | 0.140134E+09 | 0.465668E+09 | 0.226660E+09 |
November | 0.400674E+09 | 0.290209E+09 | 0.110466E+09 | 0.391567E+09 | 0.271982E+09 |
December | 0.359795E+09 | 0.259770E+09 | 0.100025E+09 | 0.325625E+09 | 0.385617E+09 |
Annual Sum or Average | 0.454019E+10 | 0.261538E+10 | 0.192481E+10 | 0.418440E+10 | 0.283400E+10 |
Minimum of Months | 0.295827E+09 | 86239152.39 | 0.100025E+09 | 0.225744E+09 | 0.103806E+09 |
Maximum of Months | 0.454358E+09 | 0.314223E+09 | 0.209588E+09 | 0.465668E+09 | 0.454078E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.316004E+09 | 0.225666E+09 | 90338001.12 | 0.276112E+09 | 0.370927E+09 |
February | 0.363612E+09 | 0.261526E+09 | 0.102086E+09 | 0.346468E+09 | 0.242484E+09 |
March | 0.359988E+09 | 0.202219E+09 | 0.157769E+09 | 0.320657E+09 | 0.235733E+09 |
April | 0.279938E+09 | 0.133906E+09 | 0.146032E+09 | 0.232138E+09 | 0.163373E+09 |
May | 0.256951E+09 | 85313868.24 | 0.171637E+09 | 0.192286E+09 | 0.136219E+09 |
June | 0.247064E+09 | 72023907.49 | 0.175040E+09 | 0.202096E+09 | 97830807.03 |
July | 0.275231E+09 | 0.101633E+09 | 0.173598E+09 | 0.258384E+09 | 82177503.18 |
August | 0.327145E+09 | 0.164932E+09 | 0.162213E+09 | 0.331020E+09 | 93027398.78 |
September | 0.351293E+09 | 0.215301E+09 | 0.135992E+09 | 0.369037E+09 | 0.125976E+09 |
October | 0.379464E+09 | 0.262428E+09 | 0.117035E+09 | 0.391664E+09 | 0.180097E+09 |
November | 0.334629E+09 | 0.242372E+09 | 92257076.27 | 0.329401E+09 | 0.217631E+09 |
December | 0.300488E+09 | 0.216951E+09 | 83537300.00 | 0.273531E+09 | 0.312290E+09 |
Annual Sum or Average | 0.379181E+10 | 0.218427E+10 | 0.160754E+10 | 0.352279E+10 | 0.225777E+10 |
Minimum of Months | 0.247064E+09 | 72023907.49 | 83537300.00 | 0.192286E+09 | 82177503.18 |
Maximum of Months | 0.379464E+09 | 0.262428E+09 | 0.175040E+09 | 0.391664E+09 | 0.370927E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.316004E+09 | 0.225666E+09 | 90338001.12 | 0.276112E+09 | 0.370927E+09 |
February | 0.363612E+09 | 0.261526E+09 | 0.102086E+09 | 0.346468E+09 | 0.242484E+09 |
March | 0.359988E+09 | 0.202219E+09 | 0.157769E+09 | 0.320657E+09 | 0.235733E+09 |
April | 0.279938E+09 | 0.133906E+09 | 0.146032E+09 | 0.232138E+09 | 0.163373E+09 |
May | 0.256951E+09 | 85313868.24 | 0.171637E+09 | 0.192286E+09 | 0.136219E+09 |
June | 0.247064E+09 | 72023907.49 | 0.175040E+09 | 0.202096E+09 | 97830807.03 |
July | 0.275231E+09 | 0.101633E+09 | 0.173598E+09 | 0.258384E+09 | 82177503.18 |
August | 0.327145E+09 | 0.164932E+09 | 0.162213E+09 | 0.331020E+09 | 93027398.78 |
September | 0.351293E+09 | 0.215301E+09 | 0.135992E+09 | 0.369037E+09 | 0.125976E+09 |
October | 0.379464E+09 | 0.262428E+09 | 0.117035E+09 | 0.391664E+09 | 0.180097E+09 |
November | 0.334629E+09 | 0.242372E+09 | 92257076.27 | 0.329401E+09 | 0.217631E+09 |
December | 0.300488E+09 | 0.216951E+09 | 83537300.00 | 0.273531E+09 | 0.312290E+09 |
Annual Sum or Average | 0.379181E+10 | 0.218427E+10 | 0.160754E+10 | 0.352279E+10 | 0.225777E+10 |
Minimum of Months | 0.247064E+09 | 72023907.49 | 83537300.00 | 0.192286E+09 | 82177503.18 |
Maximum of Months | 0.379464E+09 | 0.262428E+09 | 0.175040E+09 | 0.391664E+09 | 0.370927E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_DOOR
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.378374E+09 | 0.270206E+09 | 0.108168E+09 | 0.331718E+09 | 0.438563E+09 |
February | 0.435378E+09 | 0.313143E+09 | 0.122235E+09 | 0.415820E+09 | 0.286962E+09 |
March | 0.431038E+09 | 0.242130E+09 | 0.188908E+09 | 0.384884E+09 | 0.278973E+09 |
April | 0.335189E+09 | 0.160335E+09 | 0.174854E+09 | 0.278493E+09 | 0.193550E+09 |
May | 0.307665E+09 | 0.102152E+09 | 0.205513E+09 | 0.230745E+09 | 0.161397E+09 |
June | 0.295827E+09 | 86239152.39 | 0.209588E+09 | 0.242071E+09 | 0.116082E+09 |
July | 0.329553E+09 | 0.121693E+09 | 0.207861E+09 | 0.309025E+09 | 97702563.81 |
August | 0.391714E+09 | 0.197485E+09 | 0.194229E+09 | 0.396024E+09 | 0.110542E+09 |
September | 0.420627E+09 | 0.257795E+09 | 0.162832E+09 | 0.441855E+09 | 0.149503E+09 |
October | 0.454358E+09 | 0.314223E+09 | 0.140134E+09 | 0.469338E+09 | 0.213621E+09 |
November | 0.400674E+09 | 0.290209E+09 | 0.110466E+09 | 0.395105E+09 | 0.257785E+09 |
December | 0.359795E+09 | 0.259770E+09 | 0.100025E+09 | 0.328514E+09 | 0.369553E+09 |
Annual Sum or Average | 0.454019E+10 | 0.261538E+10 | 0.192481E+10 | 0.422359E+10 | 0.267423E+10 |
Minimum of Months | 0.295827E+09 | 86239152.39 | 0.100025E+09 | 0.230745E+09 | 97702563.81 |
Maximum of Months | 0.454358E+09 | 0.314223E+09 | 0.209588E+09 | 0.469338E+09 | 0.438563E+09 |
Report: WindowZoneSummaryMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 654.64 | 949.40 | 756.02 | 539.89 | 216.13 | 0.00 | 0.00 |
February | 904.79 | 707.93 | 963.12 | 692.72 | 270.40 | 0.00 | 0.00 |
March | 757.05 | 628.65 | 861.25 | 483.79 | 377.45 | 0.00 | 0.00 |
April | 555.57 | 474.98 | 692.06 | 331.04 | 361.02 | 0.00 | 0.00 |
May | 441.16 | 382.69 | 614.74 | 204.11 | 410.63 | 0.00 | 0.00 |
June | 486.86 | 269.22 | 610.79 | 178.06 | 432.73 | 0.00 | 0.00 |
July | 613.43 | 208.65 | 658.47 | 243.15 | 415.32 | 0.00 | 0.00 |
August | 787.14 | 237.97 | 782.67 | 394.59 | 388.08 | 0.00 | 0.00 |
September | 904.46 | 341.00 | 868.46 | 532.26 | 336.20 | 0.00 | 0.00 |
October | 920.55 | 486.28 | 907.84 | 627.84 | 280.00 | 0.00 | 0.00 |
November | 798.60 | 604.97 | 827.26 | 599.19 | 228.08 | 0.00 | 0.00 |
December | 645.77 | 812.59 | 718.90 | 519.04 | 199.86 | 0.00 | 0.00 |
Annual Sum or Average | 704.41 | 508.00 | 770.47 | 443.83 | 326.64 | 0.00 | 0.00 |
Minimum of Months | 441.16 | 208.65 | 610.79 | 178.06 | 199.86 | 0.00 | 0.00 |
Maximum of Months | 920.55 | 949.40 | 963.12 | 692.72 | 432.73 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 323.41 | 491.70 | 378.01 | 269.95 | 108.06 | 0.00 | 0.00 |
February | 446.66 | 371.36 | 481.56 | 346.36 | 135.20 | 0.00 | 0.00 |
March | 373.23 | 333.68 | 430.62 | 241.90 | 188.73 | 0.00 | 0.00 |
April | 272.26 | 254.77 | 346.03 | 165.52 | 180.51 | 0.00 | 0.00 |
May | 216.41 | 202.66 | 307.37 | 102.05 | 205.32 | 0.00 | 0.00 |
June | 241.53 | 138.79 | 305.39 | 89.03 | 216.37 | 0.00 | 0.00 |
July | 306.29 | 105.92 | 329.24 | 121.58 | 207.66 | 0.00 | 0.00 |
August | 392.77 | 121.43 | 391.34 | 197.29 | 194.04 | 0.00 | 0.00 |
September | 449.95 | 176.15 | 434.23 | 266.13 | 168.10 | 0.00 | 0.00 |
October | 456.07 | 253.51 | 453.92 | 313.92 | 140.00 | 0.00 | 0.00 |
November | 393.96 | 317.64 | 413.63 | 299.59 | 114.04 | 0.00 | 0.00 |
December | 318.81 | 422.81 | 359.45 | 259.52 | 99.93 | 0.00 | 0.00 |
Annual Sum or Average | 348.59 | 265.48 | 385.23 | 221.91 | 163.32 | 0.00 | 0.00 |
Minimum of Months | 216.41 | 105.92 | 305.39 | 89.03 | 99.93 | 0.00 | 0.00 |
Maximum of Months | 456.07 | 491.70 | 481.56 | 346.36 | 216.37 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 323.83 | 477.12 | 377.23 | 269.39 | 107.84 | 0.00 | 0.00 |
February | 447.53 | 358.89 | 480.57 | 345.65 | 134.92 | 0.00 | 0.00 |
March | 373.84 | 321.87 | 429.74 | 241.40 | 188.34 | 0.00 | 0.00 |
April | 273.09 | 246.20 | 345.32 | 165.18 | 180.14 | 0.00 | 0.00 |
May | 216.48 | 198.88 | 306.74 | 101.84 | 204.89 | 0.00 | 0.00 |
June | 240.14 | 142.63 | 304.77 | 88.85 | 215.92 | 0.00 | 0.00 |
July | 303.64 | 112.75 | 328.56 | 121.33 | 207.23 | 0.00 | 0.00 |
August | 390.60 | 127.33 | 390.53 | 196.89 | 193.64 | 0.00 | 0.00 |
September | 448.43 | 178.31 | 433.34 | 265.59 | 167.75 | 0.00 | 0.00 |
October | 456.29 | 248.44 | 452.99 | 313.28 | 139.71 | 0.00 | 0.00 |
November | 395.06 | 306.70 | 412.78 | 298.98 | 113.80 | 0.00 | 0.00 |
December | 319.42 | 409.51 | 358.71 | 258.99 | 99.72 | 0.00 | 0.00 |
Annual Sum or Average | 348.33 | 260.37 | 384.44 | 221.46 | 162.98 | 0.00 | 0.00 |
Minimum of Months | 216.48 | 112.75 | 304.77 | 88.85 | 99.72 | 0.00 | 0.00 |
Maximum of Months | 456.29 | 477.12 | 480.57 | 345.65 | 215.92 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 324.37 | 472.76 | 377.23 | 269.39 | 107.84 | 0.00 | 0.00 |
February | 448.50 | 354.44 | 480.57 | 345.65 | 134.92 | 0.00 | 0.00 |
March | 374.68 | 317.60 | 429.74 | 241.40 | 188.34 | 0.00 | 0.00 |
April | 274.21 | 242.03 | 345.32 | 165.18 | 180.14 | 0.00 | 0.00 |
May | 217.27 | 196.09 | 306.74 | 101.84 | 204.89 | 0.00 | 0.00 |
June | 240.28 | 142.17 | 304.77 | 88.85 | 215.92 | 0.00 | 0.00 |
July | 303.55 | 113.04 | 328.56 | 121.33 | 207.23 | 0.00 | 0.00 |
August | 390.56 | 127.39 | 390.53 | 196.89 | 193.64 | 0.00 | 0.00 |
September | 448.69 | 177.27 | 433.34 | 265.59 | 167.75 | 0.00 | 0.00 |
October | 457.12 | 245.31 | 452.99 | 313.28 | 139.71 | 0.00 | 0.00 |
November | 396.21 | 302.05 | 412.78 | 298.98 | 113.80 | 0.00 | 0.00 |
December | 320.07 | 405.10 | 358.71 | 258.99 | 99.72 | 0.00 | 0.00 |
Annual Sum or Average | 348.92 | 257.61 | 384.44 | 221.46 | 162.98 | 0.00 | 0.00 |
Minimum of Months | 217.27 | 113.04 | 304.77 | 88.85 | 99.72 | 0.00 | 0.00 |
Maximum of Months | 457.12 | 472.76 | 480.57 | 345.65 | 215.92 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 324.98 | 469.67 | 377.23 | 269.39 | 107.84 | 0.00 | 0.00 |
February | 449.62 | 350.97 | 480.57 | 345.65 | 134.92 | 0.00 | 0.00 |
March | 375.66 | 314.13 | 429.74 | 241.40 | 188.34 | 0.00 | 0.00 |
April | 275.72 | 237.90 | 345.32 | 165.18 | 180.14 | 0.00 | 0.00 |
May | 218.62 | 192.90 | 306.74 | 101.84 | 204.89 | 0.00 | 0.00 |
June | 240.97 | 140.54 | 304.77 | 88.85 | 215.92 | 0.00 | 0.00 |
July | 304.05 | 111.79 | 328.56 | 121.33 | 207.23 | 0.00 | 0.00 |
August | 391.05 | 125.96 | 390.53 | 196.89 | 193.64 | 0.00 | 0.00 |
September | 449.43 | 175.18 | 433.34 | 265.59 | 167.75 | 0.00 | 0.00 |
October | 458.42 | 241.93 | 452.99 | 313.28 | 139.71 | 0.00 | 0.00 |
November | 397.68 | 297.87 | 412.78 | 298.98 | 113.80 | 0.00 | 0.00 |
December | 320.84 | 401.75 | 358.71 | 258.99 | 99.72 | 0.00 | 0.00 |
Annual Sum or Average | 349.88 | 254.72 | 384.44 | 221.46 | 162.98 | 0.00 | 0.00 |
Minimum of Months | 218.62 | 111.79 | 304.77 | 88.85 | 99.72 | 0.00 | 0.00 |
Maximum of Months | 458.42 | 469.67 | 480.57 | 345.65 | 215.92 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 656.67 | 914.18 | 754.47 | 538.78 | 215.68 | 0.00 | 0.00 |
February | 908.76 | 678.54 | 961.15 | 691.30 | 269.85 | 0.00 | 0.00 |
March | 758.59 | 606.52 | 859.48 | 482.80 | 376.68 | 0.00 | 0.00 |
April | 559.50 | 454.79 | 690.64 | 330.36 | 360.28 | 0.00 | 0.00 |
May | 444.25 | 367.95 | 613.48 | 203.69 | 409.79 | 0.00 | 0.00 |
June | 485.19 | 269.85 | 609.53 | 177.69 | 431.84 | 0.00 | 0.00 |
July | 609.13 | 214.19 | 657.12 | 242.65 | 414.47 | 0.00 | 0.00 |
August | 783.94 | 241.51 | 781.07 | 393.78 | 387.29 | 0.00 | 0.00 |
September | 903.22 | 337.69 | 866.68 | 531.17 | 335.51 | 0.00 | 0.00 |
October | 925.09 | 465.99 | 905.98 | 626.55 | 279.42 | 0.00 | 0.00 |
November | 804.54 | 573.05 | 825.57 | 597.96 | 227.61 | 0.00 | 0.00 |
December | 649.05 | 779.26 | 717.42 | 517.97 | 199.45 | 0.00 | 0.00 |
Annual Sum or Average | 705.88 | 491.34 | 768.89 | 442.92 | 325.97 | 0.00 | 0.00 |
Minimum of Months | 444.25 | 214.19 | 609.53 | 177.69 | 199.45 | 0.00 | 0.00 |
Maximum of Months | 925.09 | 914.18 | 961.15 | 691.30 | 431.84 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 326.82 | 460.09 | 377.23 | 269.39 | 107.84 | 0.00 | 0.00 |
February | 452.86 | 341.02 | 480.57 | 345.65 | 134.92 | 0.00 | 0.00 |
March | 378.20 | 304.33 | 429.74 | 241.40 | 188.34 | 0.00 | 0.00 |
April | 279.65 | 227.16 | 345.32 | 165.18 | 180.14 | 0.00 | 0.00 |
May | 222.37 | 183.66 | 306.74 | 101.84 | 204.89 | 0.00 | 0.00 |
June | 243.26 | 134.23 | 304.77 | 88.85 | 215.92 | 0.00 | 0.00 |
July | 305.63 | 106.04 | 328.56 | 121.33 | 207.23 | 0.00 | 0.00 |
August | 392.61 | 119.74 | 390.53 | 196.89 | 193.64 | 0.00 | 0.00 |
September | 451.54 | 168.23 | 433.34 | 265.59 | 167.75 | 0.00 | 0.00 |
October | 461.97 | 232.68 | 452.99 | 313.28 | 139.71 | 0.00 | 0.00 |
November | 401.37 | 287.23 | 412.78 | 298.98 | 113.80 | 0.00 | 0.00 |
December | 323.10 | 391.87 | 358.71 | 258.99 | 99.72 | 0.00 | 0.00 |
Annual Sum or Average | 352.57 | 246.04 | 384.44 | 221.46 | 162.98 | 0.00 | 0.00 |
Minimum of Months | 222.37 | 106.04 | 304.77 | 88.85 | 99.72 | 0.00 | 0.00 |
Maximum of Months | 461.97 | 460.09 | 480.57 | 345.65 | 215.92 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 326.95 | 459.42 | 377.23 | 269.39 | 107.84 | 0.00 | 0.00 |
February | 453.20 | 340.07 | 480.57 | 345.65 | 134.92 | 0.00 | 0.00 |
March | 378.51 | 303.20 | 429.74 | 241.40 | 188.34 | 0.00 | 0.00 |
April | 280.28 | 225.44 | 345.32 | 165.18 | 180.14 | 0.00 | 0.00 |
May | 223.06 | 182.21 | 306.74 | 101.84 | 204.89 | 0.00 | 0.00 |
June | 243.78 | 133.37 | 304.77 | 88.85 | 215.92 | 0.00 | 0.00 |
July | 305.99 | 105.44 | 328.56 | 121.33 | 207.23 | 0.00 | 0.00 |
August | 392.94 | 119.08 | 390.53 | 196.89 | 193.64 | 0.00 | 0.00 |
September | 451.95 | 167.25 | 433.34 | 265.59 | 167.75 | 0.00 | 0.00 |
October | 462.59 | 231.22 | 452.99 | 313.28 | 139.71 | 0.00 | 0.00 |
November | 401.82 | 285.98 | 412.78 | 298.98 | 113.80 | 0.00 | 0.00 |
December | 323.32 | 390.99 | 358.71 | 258.99 | 99.72 | 0.00 | 0.00 |
Annual Sum or Average | 352.98 | 244.99 | 384.44 | 221.46 | 162.98 | 0.00 | 0.00 |
Minimum of Months | 223.06 | 105.44 | 304.77 | 88.85 | 99.72 | 0.00 | 0.00 |
Maximum of Months | 462.59 | 459.42 | 480.57 | 345.65 | 215.92 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 327.49 | 456.23 | 377.23 | 269.39 | 107.84 | 0.00 | 0.00 |
February | 454.28 | 336.17 | 480.57 | 345.65 | 134.92 | 0.00 | 0.00 |
March | 379.47 | 298.91 | 429.74 | 241.40 | 188.34 | 0.00 | 0.00 |
April | 281.89 | 220.21 | 345.32 | 165.18 | 180.14 | 0.00 | 0.00 |
May | 224.77 | 177.89 | 306.74 | 101.84 | 204.89 | 0.00 | 0.00 |
June | 245.11 | 130.79 | 304.77 | 88.85 | 215.92 | 0.00 | 0.00 |
July | 306.65 | 103.98 | 328.56 | 121.33 | 207.23 | 0.00 | 0.00 |
August | 393.55 | 117.45 | 390.53 | 196.89 | 193.64 | 0.00 | 0.00 |
September | 452.88 | 164.66 | 433.34 | 265.59 | 167.75 | 0.00 | 0.00 |
October | 464.04 | 227.35 | 452.99 | 313.28 | 139.71 | 0.00 | 0.00 |
November | 402.97 | 282.12 | 412.78 | 298.98 | 113.80 | 0.00 | 0.00 |
December | 324.05 | 387.27 | 358.71 | 258.99 | 99.72 | 0.00 | 0.00 |
Annual Sum or Average | 354.04 | 241.61 | 384.44 | 221.46 | 162.98 | 0.00 | 0.00 |
Minimum of Months | 224.77 | 103.98 | 304.77 | 88.85 | 99.72 | 0.00 | 0.00 |
Maximum of Months | 464.04 | 456.23 | 480.57 | 345.65 | 215.92 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 330.03 | 440.72 | 377.23 | 269.39 | 107.84 | 0.00 | 0.00 |
February | 458.32 | 319.08 | 480.57 | 345.65 | 134.92 | 0.00 | 0.00 |
March | 383.14 | 280.18 | 429.74 | 241.40 | 188.34 | 0.00 | 0.00 |
April | 286.56 | 200.73 | 345.32 | 165.18 | 180.14 | 0.00 | 0.00 |
May | 229.73 | 161.97 | 306.74 | 101.84 | 204.89 | 0.00 | 0.00 |
June | 249.33 | 120.27 | 304.77 | 88.85 | 215.92 | 0.00 | 0.00 |
July | 308.32 | 97.84 | 328.56 | 121.33 | 207.23 | 0.00 | 0.00 |
August | 395.04 | 110.74 | 390.53 | 196.89 | 193.64 | 0.00 | 0.00 |
September | 455.22 | 154.88 | 433.34 | 265.59 | 167.75 | 0.00 | 0.00 |
October | 467.69 | 214.24 | 452.99 | 313.28 | 139.71 | 0.00 | 0.00 |
November | 406.60 | 267.38 | 412.78 | 298.98 | 113.80 | 0.00 | 0.00 |
December | 326.90 | 371.17 | 358.71 | 258.99 | 99.72 | 0.00 | 0.00 |
Annual Sum or Average | 357.34 | 227.99 | 384.44 | 221.46 | 162.98 | 0.00 | 0.00 |
Minimum of Months | 229.73 | 97.84 | 304.77 | 88.85 | 99.72 | 0.00 | 0.00 |
Maximum of Months | 467.69 | 440.72 | 480.57 | 345.65 | 215.92 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.175340E+10 | 0.254287E+10 | 0.202492E+10 | 0.144605E+10 | 0.578876E+09 | 0.00 | 0.00 |
February | 0.218886E+10 | 0.171262E+10 | 0.232999E+10 | 0.167583E+10 | 0.654159E+09 | 0.00 | 0.00 |
March | 0.202768E+10 | 0.168377E+10 | 0.230677E+10 | 0.129580E+10 | 0.101097E+10 | 0.00 | 0.00 |
April | 0.144003E+10 | 0.123115E+10 | 0.179381E+10 | 0.858059E+09 | 0.935756E+09 | 0.00 | 0.00 |
May | 0.118161E+10 | 0.102500E+10 | 0.164651E+10 | 0.546682E+09 | 0.109983E+10 | 0.00 | 0.00 |
June | 0.126195E+10 | 0.697822E+09 | 0.158316E+10 | 0.461522E+09 | 0.112164E+10 | 0.00 | 0.00 |
July | 0.164301E+10 | 0.558841E+09 | 0.176365E+10 | 0.651256E+09 | 0.111240E+10 | 0.00 | 0.00 |
August | 0.210827E+10 | 0.637374E+09 | 0.209631E+10 | 0.105687E+10 | 0.103944E+10 | 0.00 | 0.00 |
September | 0.234435E+10 | 0.883874E+09 | 0.225105E+10 | 0.137963E+10 | 0.871421E+09 | 0.00 | 0.00 |
October | 0.246559E+10 | 0.130245E+10 | 0.243156E+10 | 0.168161E+10 | 0.749950E+09 | 0.00 | 0.00 |
November | 0.206997E+10 | 0.156809E+10 | 0.214427E+10 | 0.155309E+10 | 0.591174E+09 | 0.00 | 0.00 |
December | 0.172962E+10 | 0.217645E+10 | 0.192550E+10 | 0.139020E+10 | 0.535298E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.222143E+11 | 0.160203E+11 | 0.242975E+11 | 0.139966E+11 | 0.103009E+11 | 0.00 | 0.00 |
Minimum of Months | 0.118161E+10 | 0.558841E+09 | 0.158316E+10 | 0.461522E+09 | 0.535298E+09 | 0.00 | 0.00 |
Maximum of Months | 0.246559E+10 | 0.254287E+10 | 0.243156E+10 | 0.168161E+10 | 0.112164E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.866234E+09 | 0.131698E+10 | 0.101246E+10 | 0.723023E+09 | 0.289438E+09 | 0.00 | 0.00 |
February | 0.108055E+10 | 0.898383E+09 | 0.116499E+10 | 0.837915E+09 | 0.327080E+09 | 0.00 | 0.00 |
March | 0.999657E+09 | 0.893725E+09 | 0.115338E+10 | 0.647898E+09 | 0.505485E+09 | 0.00 | 0.00 |
April | 0.705685E+09 | 0.660358E+09 | 0.896907E+09 | 0.429029E+09 | 0.467878E+09 | 0.00 | 0.00 |
May | 0.579625E+09 | 0.542811E+09 | 0.823257E+09 | 0.273341E+09 | 0.549916E+09 | 0.00 | 0.00 |
June | 0.626035E+09 | 0.359750E+09 | 0.791580E+09 | 0.230761E+09 | 0.560820E+09 | 0.00 | 0.00 |
July | 0.820369E+09 | 0.283691E+09 | 0.881826E+09 | 0.325628E+09 | 0.556198E+09 | 0.00 | 0.00 |
August | 0.105199E+10 | 0.325244E+09 | 0.104816E+10 | 0.528435E+09 | 0.519722E+09 | 0.00 | 0.00 |
September | 0.116627E+10 | 0.456593E+09 | 0.112552E+10 | 0.689814E+09 | 0.435711E+09 | 0.00 | 0.00 |
October | 0.122155E+10 | 0.679009E+09 | 0.121578E+10 | 0.840807E+09 | 0.374975E+09 | 0.00 | 0.00 |
November | 0.102114E+10 | 0.823320E+09 | 0.107213E+10 | 0.776547E+09 | 0.295587E+09 | 0.00 | 0.00 |
December | 0.853894E+09 | 0.113245E+10 | 0.962748E+09 | 0.695099E+09 | 0.267649E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.109930E+11 | 0.837232E+10 | 0.121488E+11 | 0.699830E+10 | 0.515046E+10 | 0.00 | 0.00 |
Minimum of Months | 0.579625E+09 | 0.283691E+09 | 0.791580E+09 | 0.230761E+09 | 0.267649E+09 | 0.00 | 0.00 |
Maximum of Months | 0.122155E+10 | 0.131698E+10 | 0.121578E+10 | 0.840807E+09 | 0.560820E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.867341E+09 | 0.127791E+10 | 0.101038E+10 | 0.721538E+09 | 0.288844E+09 | 0.00 | 0.00 |
February | 0.108265E+10 | 0.868220E+09 | 0.116260E+10 | 0.836194E+09 | 0.326408E+09 | 0.00 | 0.00 |
March | 0.100130E+10 | 0.862089E+09 | 0.115101E+10 | 0.646568E+09 | 0.504447E+09 | 0.00 | 0.00 |
April | 0.707841E+09 | 0.638161E+09 | 0.895066E+09 | 0.428148E+09 | 0.466917E+09 | 0.00 | 0.00 |
May | 0.579822E+09 | 0.532670E+09 | 0.821566E+09 | 0.272780E+09 | 0.548787E+09 | 0.00 | 0.00 |
June | 0.622437E+09 | 0.369704E+09 | 0.789955E+09 | 0.230287E+09 | 0.559668E+09 | 0.00 | 0.00 |
July | 0.813275E+09 | 0.301995E+09 | 0.880015E+09 | 0.324959E+09 | 0.555056E+09 | 0.00 | 0.00 |
August | 0.104617E+10 | 0.341048E+09 | 0.104600E+10 | 0.527350E+09 | 0.518655E+09 | 0.00 | 0.00 |
September | 0.116233E+10 | 0.462171E+09 | 0.112321E+10 | 0.688398E+09 | 0.434816E+09 | 0.00 | 0.00 |
October | 0.122212E+10 | 0.665427E+09 | 0.121329E+10 | 0.839080E+09 | 0.374205E+09 | 0.00 | 0.00 |
November | 0.102400E+10 | 0.794955E+09 | 0.106993E+10 | 0.774952E+09 | 0.294980E+09 | 0.00 | 0.00 |
December | 0.855534E+09 | 0.109682E+10 | 0.960771E+09 | 0.693672E+09 | 0.267100E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.109848E+11 | 0.821117E+10 | 0.121238E+11 | 0.698393E+10 | 0.513988E+10 | 0.00 | 0.00 |
Minimum of Months | 0.579822E+09 | 0.301995E+09 | 0.789955E+09 | 0.230287E+09 | 0.267100E+09 | 0.00 | 0.00 |
Maximum of Months | 0.122212E+10 | 0.127791E+10 | 0.121329E+10 | 0.839080E+09 | 0.559668E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.868788E+09 | 0.126624E+10 | 0.101038E+10 | 0.721538E+09 | 0.288844E+09 | 0.00 | 0.00 |
February | 0.108501E+10 | 0.857469E+09 | 0.116260E+10 | 0.836194E+09 | 0.326408E+09 | 0.00 | 0.00 |
March | 0.100354E+10 | 0.850650E+09 | 0.115101E+10 | 0.646568E+09 | 0.504447E+09 | 0.00 | 0.00 |
April | 0.710743E+09 | 0.627338E+09 | 0.895066E+09 | 0.428148E+09 | 0.466917E+09 | 0.00 | 0.00 |
May | 0.581949E+09 | 0.525220E+09 | 0.821566E+09 | 0.272780E+09 | 0.548787E+09 | 0.00 | 0.00 |
June | 0.622804E+09 | 0.368492E+09 | 0.789955E+09 | 0.230287E+09 | 0.559668E+09 | 0.00 | 0.00 |
July | 0.813040E+09 | 0.302770E+09 | 0.880015E+09 | 0.324959E+09 | 0.555056E+09 | 0.00 | 0.00 |
August | 0.104608E+10 | 0.341210E+09 | 0.104600E+10 | 0.527350E+09 | 0.518655E+09 | 0.00 | 0.00 |
September | 0.116300E+10 | 0.459492E+09 | 0.112321E+10 | 0.688398E+09 | 0.434816E+09 | 0.00 | 0.00 |
October | 0.122434E+10 | 0.657051E+09 | 0.121329E+10 | 0.839080E+09 | 0.374205E+09 | 0.00 | 0.00 |
November | 0.102698E+10 | 0.782916E+09 | 0.106993E+10 | 0.774952E+09 | 0.294980E+09 | 0.00 | 0.00 |
December | 0.857288E+09 | 0.108501E+10 | 0.960771E+09 | 0.693672E+09 | 0.267100E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.110036E+11 | 0.812386E+10 | 0.121238E+11 | 0.698393E+10 | 0.513988E+10 | 0.00 | 0.00 |
Minimum of Months | 0.581949E+09 | 0.302770E+09 | 0.789955E+09 | 0.230287E+09 | 0.267100E+09 | 0.00 | 0.00 |
Maximum of Months | 0.122434E+10 | 0.126624E+10 | 0.121329E+10 | 0.839080E+09 | 0.559668E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.870423E+09 | 0.125796E+10 | 0.101038E+10 | 0.721538E+09 | 0.288844E+09 | 0.00 | 0.00 |
February | 0.108771E+10 | 0.849064E+09 | 0.116260E+10 | 0.836194E+09 | 0.326408E+09 | 0.00 | 0.00 |
March | 0.100617E+10 | 0.841356E+09 | 0.115101E+10 | 0.646568E+09 | 0.504447E+09 | 0.00 | 0.00 |
April | 0.714668E+09 | 0.616637E+09 | 0.895066E+09 | 0.428148E+09 | 0.466917E+09 | 0.00 | 0.00 |
May | 0.585540E+09 | 0.516660E+09 | 0.821566E+09 | 0.272780E+09 | 0.548787E+09 | 0.00 | 0.00 |
June | 0.624601E+09 | 0.364291E+09 | 0.789955E+09 | 0.230287E+09 | 0.559668E+09 | 0.00 | 0.00 |
July | 0.814369E+09 | 0.299429E+09 | 0.880015E+09 | 0.324959E+09 | 0.555056E+09 | 0.00 | 0.00 |
August | 0.104740E+10 | 0.337372E+09 | 0.104600E+10 | 0.527350E+09 | 0.518655E+09 | 0.00 | 0.00 |
September | 0.116493E+10 | 0.454074E+09 | 0.112321E+10 | 0.688398E+09 | 0.434816E+09 | 0.00 | 0.00 |
October | 0.122783E+10 | 0.647994E+09 | 0.121329E+10 | 0.839080E+09 | 0.374205E+09 | 0.00 | 0.00 |
November | 0.103079E+10 | 0.772070E+09 | 0.106993E+10 | 0.774952E+09 | 0.294980E+09 | 0.00 | 0.00 |
December | 0.859336E+09 | 0.107605E+10 | 0.960771E+09 | 0.693672E+09 | 0.267100E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.110338E+11 | 0.803295E+10 | 0.121238E+11 | 0.698393E+10 | 0.513988E+10 | 0.00 | 0.00 |
Minimum of Months | 0.585540E+09 | 0.299429E+09 | 0.789955E+09 | 0.230287E+09 | 0.267100E+09 | 0.00 | 0.00 |
Maximum of Months | 0.122783E+10 | 0.125796E+10 | 0.121329E+10 | 0.839080E+09 | 0.559668E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.175882E+10 | 0.244854E+10 | 0.202076E+10 | 0.144308E+10 | 0.577688E+09 | 0.00 | 0.00 |
February | 0.219848E+10 | 0.164152E+10 | 0.232520E+10 | 0.167239E+10 | 0.652816E+09 | 0.00 | 0.00 |
March | 0.203180E+10 | 0.162451E+10 | 0.230203E+10 | 0.129314E+10 | 0.100889E+10 | 0.00 | 0.00 |
April | 0.145023E+10 | 0.117883E+10 | 0.179013E+10 | 0.856297E+09 | 0.933834E+09 | 0.00 | 0.00 |
May | 0.118988E+10 | 0.985522E+09 | 0.164313E+10 | 0.545560E+09 | 0.109757E+10 | 0.00 | 0.00 |
June | 0.125762E+10 | 0.699443E+09 | 0.157991E+10 | 0.460574E+09 | 0.111934E+10 | 0.00 | 0.00 |
July | 0.163150E+10 | 0.573680E+09 | 0.176003E+10 | 0.649918E+09 | 0.111011E+10 | 0.00 | 0.00 |
August | 0.209971E+10 | 0.646856E+09 | 0.209201E+10 | 0.105470E+10 | 0.103731E+10 | 0.00 | 0.00 |
September | 0.234114E+10 | 0.875296E+09 | 0.224643E+10 | 0.137680E+10 | 0.869632E+09 | 0.00 | 0.00 |
October | 0.247775E+10 | 0.124811E+10 | 0.242657E+10 | 0.167816E+10 | 0.748410E+09 | 0.00 | 0.00 |
November | 0.208538E+10 | 0.148535E+10 | 0.213986E+10 | 0.154990E+10 | 0.589960E+09 | 0.00 | 0.00 |
December | 0.173841E+10 | 0.208716E+10 | 0.192154E+10 | 0.138734E+10 | 0.534199E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.222607E+11 | 0.154948E+11 | 0.242476E+11 | 0.139679E+11 | 0.102798E+11 | 0.00 | 0.00 |
Minimum of Months | 0.118988E+10 | 0.573680E+09 | 0.157991E+10 | 0.460574E+09 | 0.534199E+09 | 0.00 | 0.00 |
Maximum of Months | 0.247775E+10 | 0.244854E+10 | 0.242657E+10 | 0.167816E+10 | 0.111934E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.875343E+09 | 0.123230E+10 | 0.101038E+10 | 0.721538E+09 | 0.288844E+09 | 0.00 | 0.00 |
February | 0.109556E+10 | 0.824992E+09 | 0.116260E+10 | 0.836194E+09 | 0.326408E+09 | 0.00 | 0.00 |
March | 0.101298E+10 | 0.815123E+09 | 0.115101E+10 | 0.646568E+09 | 0.504447E+09 | 0.00 | 0.00 |
April | 0.724849E+09 | 0.588811E+09 | 0.895066E+09 | 0.428148E+09 | 0.466917E+09 | 0.00 | 0.00 |
May | 0.595593E+09 | 0.491915E+09 | 0.821566E+09 | 0.272780E+09 | 0.548787E+09 | 0.00 | 0.00 |
June | 0.630535E+09 | 0.347930E+09 | 0.789955E+09 | 0.230287E+09 | 0.559668E+09 | 0.00 | 0.00 |
July | 0.818595E+09 | 0.284019E+09 | 0.880015E+09 | 0.324959E+09 | 0.555056E+09 | 0.00 | 0.00 |
August | 0.105157E+10 | 0.320723E+09 | 0.104600E+10 | 0.527350E+09 | 0.518655E+09 | 0.00 | 0.00 |
September | 0.117038E+10 | 0.436049E+09 | 0.112321E+10 | 0.688398E+09 | 0.434816E+09 | 0.00 | 0.00 |
October | 0.123734E+10 | 0.623201E+09 | 0.121329E+10 | 0.839080E+09 | 0.374205E+09 | 0.00 | 0.00 |
November | 0.104036E+10 | 0.744510E+09 | 0.106993E+10 | 0.774952E+09 | 0.294980E+09 | 0.00 | 0.00 |
December | 0.865404E+09 | 0.104957E+10 | 0.960771E+09 | 0.693672E+09 | 0.267100E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.111185E+11 | 0.775915E+10 | 0.121238E+11 | 0.698393E+10 | 0.513988E+10 | 0.00 | 0.00 |
Minimum of Months | 0.595593E+09 | 0.284019E+09 | 0.789955E+09 | 0.230287E+09 | 0.267100E+09 | 0.00 | 0.00 |
Maximum of Months | 0.123734E+10 | 0.123230E+10 | 0.121329E+10 | 0.839080E+09 | 0.559668E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.875712E+09 | 0.123052E+10 | 0.101038E+10 | 0.721538E+09 | 0.288844E+09 | 0.00 | 0.00 |
February | 0.109637E+10 | 0.822707E+09 | 0.116260E+10 | 0.836194E+09 | 0.326408E+09 | 0.00 | 0.00 |
March | 0.101381E+10 | 0.812091E+09 | 0.115101E+10 | 0.646568E+09 | 0.504447E+09 | 0.00 | 0.00 |
April | 0.726480E+09 | 0.584346E+09 | 0.895066E+09 | 0.428148E+09 | 0.466917E+09 | 0.00 | 0.00 |
May | 0.597433E+09 | 0.488033E+09 | 0.821566E+09 | 0.272780E+09 | 0.548787E+09 | 0.00 | 0.00 |
June | 0.631874E+09 | 0.345686E+09 | 0.789955E+09 | 0.230287E+09 | 0.559668E+09 | 0.00 | 0.00 |
July | 0.819555E+09 | 0.282417E+09 | 0.880015E+09 | 0.324959E+09 | 0.555056E+09 | 0.00 | 0.00 |
August | 0.105245E+10 | 0.318937E+09 | 0.104600E+10 | 0.527350E+09 | 0.518655E+09 | 0.00 | 0.00 |
September | 0.117147E+10 | 0.433504E+09 | 0.112321E+10 | 0.688398E+09 | 0.434816E+09 | 0.00 | 0.00 |
October | 0.123900E+10 | 0.619300E+09 | 0.121329E+10 | 0.839080E+09 | 0.374205E+09 | 0.00 | 0.00 |
November | 0.104152E+10 | 0.741255E+09 | 0.106993E+10 | 0.774952E+09 | 0.294980E+09 | 0.00 | 0.00 |
December | 0.865981E+09 | 0.104723E+10 | 0.960771E+09 | 0.693672E+09 | 0.267100E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.111316E+11 | 0.772602E+10 | 0.121238E+11 | 0.698393E+10 | 0.513988E+10 | 0.00 | 0.00 |
Minimum of Months | 0.597433E+09 | 0.282417E+09 | 0.789955E+09 | 0.230287E+09 | 0.267100E+09 | 0.00 | 0.00 |
Maximum of Months | 0.123900E+10 | 0.123052E+10 | 0.121329E+10 | 0.839080E+09 | 0.559668E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.877143E+09 | 0.122198E+10 | 0.101038E+10 | 0.721538E+09 | 0.288844E+09 | 0.00 | 0.00 |
February | 0.109900E+10 | 0.813252E+09 | 0.116260E+10 | 0.836194E+09 | 0.326408E+09 | 0.00 | 0.00 |
March | 0.101637E+10 | 0.800604E+09 | 0.115101E+10 | 0.646568E+09 | 0.504447E+09 | 0.00 | 0.00 |
April | 0.730648E+09 | 0.570783E+09 | 0.895066E+09 | 0.428148E+09 | 0.466917E+09 | 0.00 | 0.00 |
May | 0.602024E+09 | 0.476471E+09 | 0.821566E+09 | 0.272780E+09 | 0.548787E+09 | 0.00 | 0.00 |
June | 0.635324E+09 | 0.339001E+09 | 0.789955E+09 | 0.230287E+09 | 0.559668E+09 | 0.00 | 0.00 |
July | 0.821322E+09 | 0.278510E+09 | 0.880015E+09 | 0.324959E+09 | 0.555056E+09 | 0.00 | 0.00 |
August | 0.105408E+10 | 0.314566E+09 | 0.104600E+10 | 0.527350E+09 | 0.518655E+09 | 0.00 | 0.00 |
September | 0.117386E+10 | 0.426791E+09 | 0.112321E+10 | 0.688398E+09 | 0.434816E+09 | 0.00 | 0.00 |
October | 0.124288E+10 | 0.608945E+09 | 0.121329E+10 | 0.839080E+09 | 0.374205E+09 | 0.00 | 0.00 |
November | 0.104451E+10 | 0.731257E+09 | 0.106993E+10 | 0.774952E+09 | 0.294980E+09 | 0.00 | 0.00 |
December | 0.867929E+09 | 0.103725E+10 | 0.960771E+09 | 0.693672E+09 | 0.267100E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.111651E+11 | 0.761941E+10 | 0.121238E+11 | 0.698393E+10 | 0.513988E+10 | 0.00 | 0.00 |
Minimum of Months | 0.602024E+09 | 0.278510E+09 | 0.789955E+09 | 0.230287E+09 | 0.267100E+09 | 0.00 | 0.00 |
Maximum of Months | 0.124288E+10 | 0.122198E+10 | 0.121329E+10 | 0.839080E+09 | 0.559668E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.883941E+09 | 0.118042E+10 | 0.101038E+10 | 0.721538E+09 | 0.288844E+09 | 0.00 | 0.00 |
February | 0.110876E+10 | 0.771930E+09 | 0.116260E+10 | 0.836194E+09 | 0.326408E+09 | 0.00 | 0.00 |
March | 0.102620E+10 | 0.750437E+09 | 0.115101E+10 | 0.646568E+09 | 0.504447E+09 | 0.00 | 0.00 |
April | 0.742768E+09 | 0.520294E+09 | 0.895066E+09 | 0.428148E+09 | 0.466917E+09 | 0.00 | 0.00 |
May | 0.615315E+09 | 0.433833E+09 | 0.821566E+09 | 0.272780E+09 | 0.548787E+09 | 0.00 | 0.00 |
June | 0.646262E+09 | 0.311744E+09 | 0.789955E+09 | 0.230287E+09 | 0.559668E+09 | 0.00 | 0.00 |
July | 0.825792E+09 | 0.262057E+09 | 0.880015E+09 | 0.324959E+09 | 0.555056E+09 | 0.00 | 0.00 |
August | 0.105806E+10 | 0.296596E+09 | 0.104600E+10 | 0.527350E+09 | 0.518655E+09 | 0.00 | 0.00 |
September | 0.117993E+10 | 0.401453E+09 | 0.112321E+10 | 0.688398E+09 | 0.434816E+09 | 0.00 | 0.00 |
October | 0.125267E+10 | 0.573815E+09 | 0.121329E+10 | 0.839080E+09 | 0.374205E+09 | 0.00 | 0.00 |
November | 0.105391E+10 | 0.693046E+09 | 0.106993E+10 | 0.774952E+09 | 0.294980E+09 | 0.00 | 0.00 |
December | 0.875576E+09 | 0.994132E+09 | 0.960771E+09 | 0.693672E+09 | 0.267100E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.112692E+11 | 0.718975E+10 | 0.121238E+11 | 0.698393E+10 | 0.513988E+10 | 0.00 | 0.00 |
Minimum of Months | 0.615315E+09 | 0.262057E+09 | 0.789955E+09 | 0.230287E+09 | 0.267100E+09 | 0.00 | 0.00 |
Maximum of Months | 0.125267E+10 | 0.118042E+10 | 0.121329E+10 | 0.839080E+09 | 0.559668E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -8.8 | -10.8 | -16.1 | 5.70 | -23.3 | 32.48 | 106.19 | 0.00 |
February | -2.2 | -4.9 | -9.9 | 6.21 | -16.1 | 41.31 | 158.25 | 0.00 |
March | 0.30 | -2.8 | -8.4 | 5.38 | -12.8 | 78.62 | 145.02 | 0.00 |
April | 6.67 | 2.37 | -2.9 | 4.89 | -6.2 | 82.10 | 182.32 | 0.01 |
May | 10.10 | 5.18 | 0.22 | 5.28 | -1.1 | 102.67 | 205.47 | 0.01 |
June | 16.46 | 10.04 | 4.91 | 4.56 | 5.04 | 103.05 | 264.47 | 0.02 |
July | 20.57 | 12.44 | 6.56 | 4.24 | 8.00 | 89.47 | 301.47 | 0.00 |
August | 19.17 | 11.02 | 4.61 | 4.29 | 7.18 | 78.96 | 261.05 | 0.00 |
September | 14.69 | 9.07 | 4.37 | 5.43 | 3.41 | 63.03 | 204.21 | 0.00 |
October | 8.64 | 4.13 | -1.0 | 5.38 | -4.2 | 47.64 | 162.42 | 0.00 |
November | 2.84 | -0.8 | -6.9 | 5.91 | -11.0 | 33.00 | 125.52 | 0.00 |
December | -4.1 | -6.4 | -11.1 | 5.64 | -18.2 | 26.54 | 97.81 | 0.00 |
Annual Sum or Average | 7.07 | 2.40 | -2.9 | 5.23 | -5.7 | 65.04 | 184.63 | 0.00 |
Minimum of Months | -8.8 | -10.8 | -16.1 | 4.24 | -23.3 | 26.54 | 97.81 | 0.00 |
Maximum of Months | 20.57 | 12.44 | 6.56 | 6.21 | 8.00 | 103.05 | 301.47 | 0.02 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.60 | 14-JAN-12:00 | 5.15 | -1.1 | 8.20 | -2.3 | 105.00 | 464.50 |
February | 18.90 | 27-FEB-14:00 | 7.20 | -7.8 | 5.20 | 1.37 | 76.00 | 634.50 |
March | 15.00 | 14-MAR-13:20 | 6.65 | -2.4 | 9.30 | 1.23 | 201.67 | 711.67 |
April | 23.30 | 07-APR-13:00 | 9.64 | -4.4 | 9.30 | 4.92 | 314.50 | 110.00 |
May | 30.00 | 20-MAY-15:00 | 15.19 | 5.60 | 6.70 | 20.57 | 215.50 | 18.50 |
June | 32.20 | 29-JUN-12:00 | 14.36 | 0.60 | 9.30 | 17.03 | 187.00 | 729.00 |
July | 37.20 | 17-JUL-15:00 | 17.25 | 4.40 | 4.60 | 20.22 | 119.50 | 797.00 |
August | 35.60 | 05-AUG-15:00 | 17.61 | 6.70 | 5.20 | 22.47 | 136.50 | 625.50 |
September | 34.40 | 02-SEP-14:00 | 16.25 | 4.40 | 7.70 | 20.75 | 95.50 | 789.50 |
October | 25.00 | 18-OCT-13:00 | 11.37 | -1.1 | 7.70 | 7.35 | 48.00 | 913.00 |
November | 17.20 | 04-NOV-13:00 | 8.15 | -1.1 | 11.30 | 2.22 | 81.00 | 689.50 |
December | 13.90 | 10-DEC-01:00 | 5.47 | -5.0 | 13.90 | 5.74 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 10.60 | 5.15 | -7.8 | 4.60 | -2.3 | 0.00 | 0.00 | |
Maximum of Months | 37.20 | 17.61 | 6.70 | 13.90 | 22.47 | 314.50 | 913.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -33.9 | 10-JAN-21:00 | -34.0 | -37.8 | 3.10 | -54.3 | 0.00 | 0.00 |
February | -25.0 | 01-FEB-03:00 | -25.2 | -27.8 | 2.10 | -45.6 | 0.00 | 0.00 |
March | -23.3 | 04-MAR-23:00 | -23.8 | -28.9 | 3.60 | -44.5 | 0.00 | 0.00 |
April | -7.8 | 29-APR-03:00 | -8.6 | -10.6 | 4.10 | -25.6 | 0.00 | 0.00 |
May | -2.8 | 08-MAY-00:10 | -3.3 | -3.9 | 6.18 | -10.2 | 0.00 | 0.00 |
June | 0.60 | 15-JUN-03:00 | -0.4 | -1.7 | 2.60 | -15.7 | 0.00 | 0.00 |
July | 5.60 | 08-JUL-03:00 | 2.98 | 0.00 | 4.10 | -9.2 | 0.00 | 0.00 |
August | 6.70 | 17-AUG-00:00 | 4.32 | 1.70 | 2.60 | -7.1 | 0.00 | 0.00 |
September | 0.00 | 17-SEP-02:00 | -1.5 | -3.9 | 4.10 | -16.8 | 0.00 | 0.00 |
October | -6.1 | 10-OCT-05:19 | -6.6 | -7.8 | 3.77 | -20.6 | 0.00 | 0.00 |
November | -16.7 | 26-NOV-07:00 | -17.3 | -20.6 | 4.60 | -33.8 | 19.50 | 94.00 |
December | -28.3 | 29-DEC-08:00 | -28.5 | -32.2 | 2.10 | -48.7 | 69.50 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -33.9 | -34.0 | -37.8 | 2.10 | -54.3 | 0.00 | 0.00 | |
Maximum of Months | 6.70 | 4.32 | 1.70 | 6.18 | -7.1 | 69.50 | 94.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 5.17 | 13-JAN-14:00 | 10.00 | 0.00 | 8.80 | -3.0 | 40.00 | 694.00 |
February | 7.20 | 27-FEB-14:00 | 18.90 | -7.8 | 5.20 | 1.37 | 76.00 | 634.50 |
March | 6.92 | 14-MAR-13:00 | 15.00 | -1.7 | 10.30 | 1.80 | 241.00 | 538.00 |
April | 11.00 | 06-APR-15:00 | 22.20 | 1.10 | 3.60 | 5.33 | 110.00 | 779.00 |
May | 15.19 | 20-MAY-15:00 | 30.00 | 5.60 | 6.70 | 20.57 | 215.50 | 18.50 |
June | 19.18 | 20-JUN-14:00 | 29.40 | 14.40 | 2.60 | 18.28 | 204.00 | 614.00 |
July | 19.19 | 19-JUL-11:00 | 29.40 | 14.40 | 8.80 | 19.52 | 306.50 | 563.50 |
August | 17.61 | 05-AUG-15:00 | 35.60 | 6.70 | 5.20 | 22.47 | 136.50 | 625.50 |
September | 20.11 | 07-SEP-15:20 | 25.17 | 17.93 | 4.10 | 15.88 | 127.67 | 652.00 |
October | 11.58 | 18-OCT-14:00 | 25.00 | -0.6 | 7.70 | 7.55 | 40.50 | 852.00 |
November | 8.87 | 17-NOV-16:00 | 17.20 | 1.10 | 11.30 | 4.10 | 0.00 | 0.00 |
December | 7.61 | 19-DEC-14:00 | 12.80 | 2.80 | 8.20 | 1.37 | 74.00 | 138.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 5.17 | 10.00 | -7.8 | 2.60 | -3.0 | 0.00 | 0.00 | |
Maximum of Months | 20.11 | 35.60 | 17.93 | 11.30 | 22.47 | 306.50 | 852.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 1.70 | 12-JAN-14:00 | 7.20 | 4.47 | 5.20 | -1.0 | 107.00 | 61.00 |
February | -0.6 | 11-FEB-08:00 | 4.40 | 2.15 | 10.80 | -5.7 | 69.50 | 50.50 |
March | -0.6 | 10-MAR-12:00 | 8.90 | 4.49 | 10.30 | -2.3 | 253.00 | 140.50 |
April | 6.10 | 17-APR-16:19 | 7.97 | 6.96 | 4.50 | 0.84 | 201.50 | 117.50 |
May | 12.20 | 02-MAY-12:00 | 18.90 | 14.60 | 12.90 | 14.84 | 108.50 | 934.50 |
June | 15.60 | 20-JUN-19:00 | 25.60 | 18.75 | 3.60 | 20.22 | 17.50 | 17.00 |
July | 16.70 | 18-JUL-21:00 | 19.40 | 17.51 | 4.10 | 16.49 | 0.00 | 0.00 |
August | 11.10 | 08-AUG-11:00 | 26.70 | 16.73 | 2.60 | 12.03 | 134.50 | 869.00 |
September | 18.30 | 07-SEP-14:00 | 24.40 | 20.09 | 4.10 | 15.57 | 111.00 | 720.00 |
October | 6.70 | 01-OCT-14:09 | 9.08 | 7.77 | 2.10 | 4.06 | 260.33 | 0.33 |
November | 3.30 | 16-NOV-19:00 | 10.60 | 6.87 | 9.80 | -1.7 | 0.00 | 0.00 |
December | 2.80 | 19-DEC-14:09 | 10.97 | 6.80 | 10.78 | -1.0 | 95.00 | 292.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -0.6 | 4.40 | 2.15 | 2.10 | -5.7 | 0.00 | 0.00 | |
Maximum of Months | 18.30 | 26.70 | 20.09 | 12.90 | 20.22 | 260.33 | 934.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 5.41 | 12.59 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 4.46 | 20.37 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 5.03 | 30.19 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 7.01 | 37.07 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 9.90 | 46.35 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 12.91 | 55.45 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 15.24 | 57.38 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 16.26 | 48.01 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 15.67 | 34.51 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 13.64 | 22.84 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 10.74 | 14.52 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 7.74 | 10.24 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 10.37 | 32.53 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 4.46 | 10.24 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 16.26 | 57.38 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK1
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.389135E+09 | -263102653.8 | 0.00 | 0.00 | 744.00 | 0.00 | -126031925.1 | 58.99 | 0.00 | 0.00 |
February | 0.355869E+09 | -243118253.5 | 0.00 | 0.00 | 672.00 | 0.00 | -112750524.5 | 58.99 | 0.00 | 0.00 |
March | 0.394992E+09 | -270541031.7 | 0.00 | 0.00 | 744.00 | 0.00 | -124451307.9 | 58.99 | 0.00 | 0.00 |
April | 0.366213E+09 | -249331724.7 | 0.00 | 0.00 | 720.00 | 0.00 | -116881233.3 | 59.00 | 0.00 | 0.00 |
May | 0.361817E+09 | -243593462.4 | 0.00 | 0.00 | 744.00 | 0.00 | -118223681.0 | 58.99 | 0.00 | 0.00 |
June | 0.333433E+09 | -223302973.9 | 0.00 | 0.00 | 720.00 | 0.00 | -110129766.9 | 58.99 | 0.00 | 0.00 |
July | 0.327605E+09 | -214925846.9 | 0.00 | 0.00 | 744.00 | 0.00 | -112679562.2 | 58.99 | 0.00 | 0.00 |
August | 0.326962E+09 | -214080762.4 | 0.00 | 0.00 | 744.00 | 0.00 | -112880911.8 | 58.99 | 0.00 | 0.00 |
September | 0.318897E+09 | -207990817.7 | 0.00 | 0.00 | 720.00 | 0.00 | -110905718.3 | 58.99 | 0.00 | 0.00 |
October | 0.340042E+09 | -222696189.8 | 0.00 | 0.00 | 744.00 | 0.00 | -117345619.6 | 58.99 | 0.00 | 0.00 |
November | 0.346807E+09 | -228637345.3 | 0.00 | 0.00 | 720.00 | 0.00 | -118169518.3 | 58.99 | 0.00 | 0.00 |
December | 0.377130E+09 | -251971861.0 | 0.00 | 0.00 | 744.00 | 0.00 | -125158400.5 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.423890E+10 | -.283329E+10 | 8760.00 | -.140561E+10 | 58.99 | |||||
Minimum of Months | 0.318897E+09 | -270541031.7 | 0.00 | 0.00 | 672.00 | 0.00 | -126031925.1 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.394992E+09 | -207990817.7 | 0.00 | 0.00 | 744.00 | 0.00 | -110129766.9 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK2
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.387367E+09 | -263100565.6 | 0.00 | 0.00 | 744.00 | 0.00 | -124266204.0 | 59.00 | 0.00 | 0.00 |
February | 0.353662E+09 | -243113494.3 | 0.00 | 0.00 | 672.00 | 0.00 | -110548013.0 | 58.99 | 0.00 | 0.00 |
March | 0.392153E+09 | -270543566.5 | 0.00 | 0.00 | 744.00 | 0.00 | -121608968.0 | 58.99 | 0.00 | 0.00 |
April | 0.363393E+09 | -249345386.8 | 0.00 | 0.00 | 720.00 | 0.00 | -114047759.2 | 58.99 | 0.00 | 0.00 |
May | 0.359939E+09 | -243587705.9 | 0.00 | 0.00 | 744.00 | 0.00 | -116351781.1 | 58.99 | 0.00 | 0.00 |
June | 0.332860E+09 | -223303760.2 | 0.00 | 0.00 | 720.00 | 0.00 | -109555803.7 | 58.99 | 0.00 | 0.00 |
July | 0.327412E+09 | -214924522.4 | 0.00 | 0.00 | 744.00 | 0.00 | -112487294.0 | 58.99 | 0.00 | 0.00 |
August | 0.326664E+09 | -214074953.1 | 0.00 | 0.00 | 744.00 | 0.00 | -112588709.7 | 58.99 | 0.00 | 0.00 |
September | 0.318015E+09 | -207986801.4 | 0.00 | 0.00 | 720.00 | 0.00 | -110028097.9 | 58.99 | 0.00 | 0.00 |
October | 0.338191E+09 | -222693996.7 | 0.00 | 0.00 | 744.00 | 0.00 | -115496678.7 | 58.99 | 0.00 | 0.00 |
November | 0.344412E+09 | -228631773.6 | 0.00 | 0.00 | 720.00 | 0.00 | -115779730.9 | 58.99 | 0.00 | 0.00 |
December | 0.375091E+09 | -251964943.8 | 0.00 | 0.00 | 744.00 | 0.00 | -123126285.8 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.421916E+10 | -.283327E+10 | 8760.00 | -.138589E+10 | 58.99 | |||||
Minimum of Months | 0.318015E+09 | -270543566.5 | 0.00 | 0.00 | 672.00 | 0.00 | -124266204.0 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.392153E+09 | -207986801.4 | 0.00 | 0.00 | 744.00 | 0.00 | -109555803.7 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK3
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.357977E+09 | -231354003.9 | 0.00 | 0.00 | 744.00 | 0.00 | -126623440.9 | 59.00 | 0.00 | 0.00 |
February | 0.326483E+09 | -213984281.0 | 0.00 | 0.00 | 672.00 | 0.00 | -112498879.9 | 58.98 | 0.00 | 0.00 |
March | 0.365391E+09 | -241632320.1 | 0.00 | 0.00 | 744.00 | 0.00 | -123758430.6 | 58.99 | 0.00 | 0.00 |
April | 0.334751E+09 | -219125517.3 | 0.00 | 0.00 | 720.00 | 0.00 | -115625450.7 | 58.99 | 0.00 | 0.00 |
May | 0.332861E+09 | -216028334.5 | 0.00 | 0.00 | 744.00 | 0.00 | -116832549.7 | 59.01 | 0.00 | 0.00 |
June | 0.307423E+09 | -199011539.4 | 0.00 | 0.00 | 720.00 | 0.00 | -108411174.4 | 58.99 | 0.00 | 0.00 |
July | 0.298195E+09 | -187735546.3 | 0.00 | 0.00 | 744.00 | 0.00 | -110459362.0 | 58.99 | 0.00 | 0.00 |
August | 0.302252E+09 | -191359653.4 | 0.00 | 0.00 | 744.00 | 0.00 | -110892652.6 | 58.99 | 0.00 | 0.00 |
September | 0.291888E+09 | -182658297.0 | 0.00 | 0.00 | 720.00 | 0.00 | -109229341.5 | 58.99 | 0.00 | 0.00 |
October | 0.312201E+09 | -195867625.5 | 0.00 | 0.00 | 744.00 | 0.00 | -116333538.5 | 58.99 | 0.00 | 0.00 |
November | 0.319557E+09 | -201875135.1 | 0.00 | 0.00 | 720.00 | 0.00 | -117681790.2 | 58.99 | 0.00 | 0.00 |
December | 0.345293E+09 | -219928989.8 | 0.00 | 0.00 | 744.00 | 0.00 | -125363657.6 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.389427E+10 | -.250056E+10 | 8760.00 | -.139371E+10 | 58.99 | |||||
Minimum of Months | 0.291888E+09 | -241632320.1 | 0.00 | 0.00 | 672.00 | 0.00 | -126623440.9 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.365391E+09 | -182658297.0 | 0.00 | 0.00 | 744.00 | 0.00 | -108411174.4 | 59.01 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK4
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.358436E+09 | -231385389.6 | 0.00 | 0.00 | 744.00 | 0.00 | -127050415.4 | 58.99 | 0.00 | 0.00 |
February | 0.327013E+09 | -213934994.7 | 0.00 | 0.00 | 672.00 | 0.00 | -113077528.0 | 59.00 | 0.00 | 0.00 |
March | 0.365926E+09 | -241637976.0 | 0.00 | 0.00 | 744.00 | 0.00 | -124287950.5 | 58.99 | 0.00 | 0.00 |
April | 0.335351E+09 | -219127637.3 | 0.00 | 0.00 | 720.00 | 0.00 | -116222862.9 | 58.99 | 0.00 | 0.00 |
May | 0.333248E+09 | -216052772.8 | 0.00 | 0.00 | 744.00 | 0.00 | -117195385.0 | 59.00 | 0.00 | 0.00 |
June | 0.307485E+09 | -199012363.1 | 0.00 | 0.00 | 720.00 | 0.00 | -108472333.9 | 58.99 | 0.00 | 0.00 |
July | 0.298150E+09 | -187737655.6 | 0.00 | 0.00 | 744.00 | 0.00 | -110412228.5 | 58.99 | 0.00 | 0.00 |
August | 0.302240E+09 | -191362468.3 | 0.00 | 0.00 | 744.00 | 0.00 | -110877250.1 | 58.99 | 0.00 | 0.00 |
September | 0.292030E+09 | -182662672.1 | 0.00 | 0.00 | 720.00 | 0.00 | -109367668.6 | 58.99 | 0.00 | 0.00 |
October | 0.312664E+09 | -195846454.0 | 0.00 | 0.00 | 744.00 | 0.00 | -116817078.8 | 58.99 | 0.00 | 0.00 |
November | 0.320178E+09 | -201867186.1 | 0.00 | 0.00 | 720.00 | 0.00 | -118310961.0 | 58.99 | 0.00 | 0.00 |
December | 0.345800E+09 | -219927670.8 | 0.00 | 0.00 | 744.00 | 0.00 | -125872617.4 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.389852E+10 | -.250056E+10 | 8760.00 | -.139796E+10 | 58.99 | |||||
Minimum of Months | 0.292030E+09 | -241637976.0 | 0.00 | 0.00 | 672.00 | 0.00 | -127050415.4 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.365926E+09 | -182662672.1 | 0.00 | 0.00 | 744.00 | 0.00 | -108472333.9 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK5
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.347420E+09 | -218678139.7 | 0.00 | 0.00 | 744.00 | 0.00 | -128742118.2 | 58.99 | 0.00 | 0.00 |
February | 0.317238E+09 | -202327163.1 | 0.00 | 0.00 | 672.00 | 0.00 | -114910551.1 | 58.99 | 0.00 | 0.00 |
March | 0.354804E+09 | -228635803.5 | 0.00 | 0.00 | 744.00 | 0.00 | -126168202.1 | 59.00 | 0.00 | 0.00 |
April | 0.325870E+09 | -207371795.5 | 0.00 | 0.00 | 720.00 | 0.00 | -118498294.6 | 58.99 | 0.00 | 0.00 |
May | 0.323521E+09 | -204345495.4 | 0.00 | 0.00 | 744.00 | 0.00 | -119175253.6 | 58.99 | 0.00 | 0.00 |
June | 0.297939E+09 | -188308837.4 | 0.00 | 0.00 | 720.00 | 0.00 | -109629845.5 | 58.99 | 0.00 | 0.00 |
July | 0.288963E+09 | -177563743.7 | 0.00 | 0.00 | 744.00 | 0.00 | -111399141.1 | 58.98 | 0.00 | 0.00 |
August | 0.293028E+09 | -181118668.2 | 0.00 | 0.00 | 744.00 | 0.00 | -111908936.9 | 58.97 | 0.00 | 0.00 |
September | 0.283505E+09 | -172864405.2 | 0.00 | 0.00 | 720.00 | 0.00 | -110640312.7 | 58.99 | 0.00 | 0.00 |
October | 0.303984E+09 | -185118044.8 | 0.00 | 0.00 | 744.00 | 0.00 | -118866026.9 | 58.99 | 0.00 | 0.00 |
November | 0.311229E+09 | -190662111.4 | 0.00 | 0.00 | 720.00 | 0.00 | -120566503.7 | 58.99 | 0.00 | 0.00 |
December | 0.335701E+09 | -207975531.3 | 0.00 | 0.00 | 744.00 | 0.00 | -127725837.9 | 59.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.378320E+10 | -.236497E+10 | 8760.00 | -.141823E+10 | 58.99 | |||||
Minimum of Months | 0.283505E+09 | -228635803.5 | 0.00 | 0.00 | 672.00 | 0.00 | -128742118.2 | 58.97 | 0.00 | 0.00 |
Maximum of Months | 0.354804E+09 | -172864405.2 | 0.00 | 0.00 | 744.00 | 0.00 | -109629845.5 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK6
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.347348E+09 | -218677300.1 | 0.00 | 0.00 | 744.00 | 0.00 | -128670410.8 | 58.99 | 0.00 | 0.00 |
February | 0.317199E+09 | -202324213.4 | 0.00 | 0.00 | 672.00 | 0.00 | -114875071.7 | 59.00 | 0.00 | 0.00 |
March | 0.354807E+09 | -228641122.3 | 0.00 | 0.00 | 744.00 | 0.00 | -126165906.1 | 58.99 | 0.00 | 0.00 |
April | 0.325980E+09 | -207367911.9 | 0.00 | 0.00 | 720.00 | 0.00 | -118612445.4 | 58.99 | 0.00 | 0.00 |
May | 0.323633E+09 | -204345563.0 | 0.00 | 0.00 | 744.00 | 0.00 | -119287634.6 | 58.99 | 0.00 | 0.00 |
June | 0.298044E+09 | -188308986.2 | 0.00 | 0.00 | 720.00 | 0.00 | -109734643.2 | 58.99 | 0.00 | 0.00 |
July | 0.289122E+09 | -177540399.3 | 0.00 | 0.00 | 744.00 | 0.00 | -111581810.9 | 59.00 | 0.00 | 0.00 |
August | 0.293193E+09 | -181013044.8 | 0.00 | 0.00 | 744.00 | 0.00 | -112180115.7 | 59.01 | 0.00 | 0.00 |
September | 0.283629E+09 | -172836363.8 | 0.00 | 0.00 | 720.00 | 0.00 | -110792372.3 | 59.00 | 0.00 | 0.00 |
October | 0.304098E+09 | -185109834.6 | 0.00 | 0.00 | 744.00 | 0.00 | -118988347.7 | 58.99 | 0.00 | 0.00 |
November | 0.311280E+09 | -190664319.9 | 0.00 | 0.00 | 720.00 | 0.00 | -120615240.0 | 58.99 | 0.00 | 0.00 |
December | 0.335637E+09 | -207999298.5 | 0.00 | 0.00 | 744.00 | 0.00 | -127637909.4 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.378397E+10 | -.236483E+10 | 8760.00 | -.141914E+10 | 58.99 | |||||
Minimum of Months | 0.283629E+09 | -228641122.3 | 0.00 | 0.00 | 672.00 | 0.00 | -128670410.8 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.354807E+09 | -172836363.8 | 0.00 | 0.00 | 744.00 | 0.00 | -109734643.2 | 59.01 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK7
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.347414E+09 | -218678843.2 | 0.00 | 0.00 | 744.00 | 0.00 | -128735254.3 | 58.99 | 0.00 | 0.00 |
February | 0.317311E+09 | -202327784.1 | 0.00 | 0.00 | 672.00 | 0.00 | -114983619.1 | 58.99 | 0.00 | 0.00 |
March | 0.354931E+09 | -228633692.3 | 0.00 | 0.00 | 744.00 | 0.00 | -126297734.7 | 59.00 | 0.00 | 0.00 |
April | 0.326226E+09 | -207369253.1 | 0.00 | 0.00 | 720.00 | 0.00 | -118857021.2 | 58.99 | 0.00 | 0.00 |
May | 0.323858E+09 | -204312726.8 | 0.00 | 0.00 | 744.00 | 0.00 | -119545627.0 | 59.00 | 0.00 | 0.00 |
June | 0.298181E+09 | -188308157.2 | 0.00 | 0.00 | 720.00 | 0.00 | -109873045.8 | 58.99 | 0.00 | 0.00 |
July | 0.289198E+09 | -177568681.8 | 0.00 | 0.00 | 744.00 | 0.00 | -111629066.8 | 58.98 | 0.00 | 0.00 |
August | 0.293272E+09 | -181069888.0 | 0.00 | 0.00 | 744.00 | 0.00 | -112201972.9 | 58.99 | 0.00 | 0.00 |
September | 0.283770E+09 | -172834646.2 | 0.00 | 0.00 | 720.00 | 0.00 | -110935049.9 | 59.00 | 0.00 | 0.00 |
October | 0.304331E+09 | -185114865.4 | 0.00 | 0.00 | 744.00 | 0.00 | -119216181.4 | 58.99 | 0.00 | 0.00 |
November | 0.311449E+09 | -190658202.2 | 0.00 | 0.00 | 720.00 | 0.00 | -120791025.8 | 58.99 | 0.00 | 0.00 |
December | 0.335737E+09 | -207970982.3 | 0.00 | 0.00 | 744.00 | 0.00 | -127766375.6 | 59.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.378568E+10 | -.236485E+10 | 8760.00 | -.142083E+10 | 58.99 | |||||
Minimum of Months | 0.283770E+09 | -228633692.3 | 0.00 | 0.00 | 672.00 | 0.00 | -128735254.3 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.354931E+09 | -172834646.2 | 0.00 | 0.00 | 744.00 | 0.00 | -109873045.8 | 59.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 226.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 275.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 304.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 325.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 385.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 434.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 417.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 421.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 352.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 317.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 269.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 236.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3965.83 | ||||||||||
Minimum of Months | 226.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 434.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.298555E+11 | 70533.79 | 01-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.157644E+11 | 70533.79 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.117297E+11 | 70533.79 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.350385E+10 | 70533.79 | 01-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.222484E+10 | 70533.79 | 01-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 38555905.58 | 5434.49 | 16-JUN-11:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.219172E+09 | 70533.79 | 20-SEP-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.111997E+10 | 70533.79 | 06-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.801610E+10 | 70533.79 | 10-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.206942E+11 | 70533.79 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.931664E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.298555E+11 | 70533.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.111119E+11 | 37629.29 | 03-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.552711E+10 | 37629.29 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.348862E+10 | 37629.29 | 03-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.862439E+09 | 37629.29 | 01-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.570661E+09 | 37629.29 | 08-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 123036.29 | 205.06 | 16-JUN-11:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 24047903.40 | 2081.77 | 20-SEP-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.255471E+09 | 30216.19 | 10-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.249707E+10 | 37629.29 | 13-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.726483E+10 | 37629.29 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.316023E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.111119E+11 | 37629.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_3:3_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.124050E+11 | 37610.41 | 01-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.645892E+10 | 37610.41 | 01-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.440643E+10 | 37610.41 | 03-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.119204E+10 | 37610.41 | 29-APR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.811564E+09 | 37610.41 | 01-MAY-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 331595.49 | 501.73 | 16-JUN-11:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 54981708.33 | 3077.70 | 20-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.447187E+09 | 37610.41 | 10-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.317549E+10 | 37610.41 | 12-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.849243E+10 | 37610.41 | 01-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.374444E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.124050E+11 | 37610.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_4:4_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.127648E+11 | 37684.79 | 01-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.669977E+10 | 37684.79 | 01-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.468070E+10 | 37684.79 | 03-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.131632E+10 | 37684.79 | 29-APR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.894348E+09 | 37684.79 | 01-MAY-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 861960.19 | 691.68 | 16-JUN-11:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 70491059.48 | 5680.75 | 20-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.515157E+09 | 37684.79 | 10-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.339583E+10 | 37684.79 | 12-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.880396E+10 | 37684.79 | 01-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.391422E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.127648E+11 | 37684.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_5:5_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.132541E+11 | 37490.15 | 01-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.707304E+10 | 37490.15 | 01-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.509508E+10 | 37490.15 | 03-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.153685E+10 | 37490.15 | 01-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.102291E+10 | 37490.15 | 01-MAY-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 3973123.50 | 1273.20 | 16-JUN-11:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 99906506.05 | 8631.86 | 20-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.617118E+09 | 37490.15 | 10-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.370928E+10 | 37490.15 | 12-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.926767E+10 | 37490.15 | 01-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.416799E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.132541E+11 | 37490.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_6:6_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.263024E+11 | 68808.71 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.144061E+11 | 68808.71 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.109789E+11 | 68808.71 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.373439E+10 | 68808.71 | 01-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.242741E+10 | 68808.71 | 01-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 50937535.28 | 5572.96 | 16-JUN-11:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.369145E+09 | 68808.71 | 20-SEP-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.163550E+10 | 68808.71 | 05-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.811951E+10 | 68808.71 | 02-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.188025E+11 | 68808.71 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.868268E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.263024E+11 | 68808.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_7:7_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.137943E+11 | 36711.46 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.756946E+10 | 36711.46 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.579622E+10 | 36711.46 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.198675E+10 | 36711.46 | 01-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.129657E+10 | 36711.46 | 01-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 28022028.50 | 3190.87 | 16-JUN-11:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.198391E+09 | 36711.46 | 20-SEP-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.863868E+09 | 36711.46 | 05-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.428362E+10 | 36711.46 | 02-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.987451E+10 | 36711.46 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.456917E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.137943E+11 | 36711.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_8:8_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.138867E+11 | 36686.04 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.765845E+10 | 36686.04 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.591594E+10 | 36686.04 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.208299E+10 | 36686.04 | 01-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.135119E+10 | 36686.04 | 01-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 32529408.61 | 3401.99 | 17-JUN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.217329E+09 | 36686.04 | 20-SEP-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.910065E+09 | 36686.04 | 05-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.437979E+10 | 36686.04 | 02-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.996883E+10 | 36686.04 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.464038E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.138867E+11 | 36686.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_9:9_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.143005E+11 | 36896.23 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.801474E+10 | 36896.23 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.636009E+10 | 36896.23 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.239362E+10 | 36896.23 | 01-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.153797E+10 | 36896.23 | 01-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 47169604.53 | 10944.41 | 17-JUN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.272886E+09 | 36896.23 | 19-SEP-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.104483E+10 | 36896.23 | 04-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.468732E+10 | 36896.23 | 02-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.103639E+11 | 36896.23 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.490230E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.143005E+11 | 36896.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_10:10_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.179134E+11 | 39631.34 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.103065E+11 | 39631.34 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.863727E+10 | 39631.34 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.366701E+10 | 39631.34 | 01-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.231804E+10 | 39631.34 | 01-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.111181E+09 | 39631.34 | 17-JUN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 23561342.49 | 18466.90 | 18-AUG-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.494821E+09 | 39631.34 | 13-SEP-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.156574E+10 | 39631.34 | 02-OCT-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.610334E+10 | 39631.34 | 01-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.128652E+11 | 39631.34 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.640061E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.179134E+11 | 39631.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 2556.64 | 2556.64 | 0.32 | 27-FEB-15:30 | 0.32 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.106951E+09 | 0.106951E+09 | 7266.16 | 07-APR-14:00 | 7266.16 | 0.00 |
May | 0.00 | 0.00 | 0.233953E+10 | 0.233243E+10 | 18258.28 | 20-MAY-16:10 | 18258.28 | 0.00 |
June | 0.00 | 0.00 | 0.931663E+10 | 0.893910E+10 | 22698.12 | 22-JUN-07:03 | 17091.96 | 0.00 |
July | 0.00 | 0.00 | 0.185204E+11 | 0.180643E+11 | 42131.55 | 19-JUL-07:02 | 28556.34 | 0.00 |
August | 0.00 | 0.00 | 0.146969E+11 | 0.146320E+11 | 38344.48 | 07-AUG-07:02 | 38344.48 | 0.00 |
September | 0.00 | 0.00 | 0.767095E+10 | 0.730703E+10 | 39134.63 | 05-SEP-07:02 | 34756.96 | 0.00 |
October | 0.00 | 0.00 | 0.759333E+09 | 0.759333E+09 | 14828.85 | 18-OCT-14:00 | 14828.85 | 0.00 |
November | 0.00 | 0.00 | 5285.94 | 5285.94 | 0.34 | 04-NOV-14:00 | 0.34 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.534107E+11 | 0.521412E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.185204E+11 | 0.180643E+11 | 42131.55 | 38344.48 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 4144203.72 | 4144203.72 | 956.25 | 28-FEB-22:30 | 956.25 | 0.00 |
March | 0.00 | 0.00 | 559030.95 | 559030.95 | 225.33 | 23-MAR-21:20 | 225.33 | 0.00 |
April | 0.00 | 0.00 | 0.141233E+09 | 0.141233E+09 | 21052.85 | 06-APR-20:02 | 21052.85 | 0.00 |
May | 0.00 | 0.00 | 0.166545E+10 | 0.165152E+10 | 21463.34 | 20-MAY-18:27 | 21463.34 | 0.00 |
June | 0.00 | 0.00 | 0.588150E+10 | 0.563081E+10 | 22460.23 | 21-JUN-20:01 | 18225.33 | 0.00 |
July | 0.00 | 0.00 | 0.109047E+11 | 0.105867E+11 | 23129.78 | 18-JUL-21:57 | 13306.16 | 0.00 |
August | 0.00 | 0.00 | 0.867691E+10 | 0.862187E+10 | 21754.27 | 08-AUG-22:43 | 20271.29 | 0.00 |
September | 0.00 | 0.00 | 0.457470E+10 | 0.434576E+10 | 22823.80 | 06-SEP-20:01 | 16051.17 | 0.00 |
October | 0.00 | 0.00 | 0.539154E+09 | 0.539154E+09 | 21052.85 | 02-OCT-20:02 | 21052.85 | 0.00 |
November | 0.00 | 0.00 | 24823481.98 | 24823481.98 | 21052.85 | 03-NOV-20:02 | 21052.85 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.324132E+11 | 0.315466E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.109047E+11 | 0.105867E+11 | 23129.78 | 21463.34 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 2315.41 | 2315.41 | 0.17 | 27-FEB-15:30 | 0.17 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 79706723.03 | 79706723.03 | 4571.71 | 07-APR-14:00 | 4571.71 | 0.00 |
May | 0.00 | 0.00 | 0.106814E+10 | 0.106433E+10 | 9982.18 | 20-MAY-16:00 | 9982.18 | 0.00 |
June | 0.00 | 0.00 | 0.430561E+10 | 0.414909E+10 | 22005.10 | 22-JUN-06:02 | 15042.44 | 0.00 |
July | 0.00 | 0.00 | 0.815671E+10 | 0.797222E+10 | 22888.20 | 19-JUL-06:02 | 15486.76 | 0.00 |
August | 0.00 | 0.00 | 0.664649E+10 | 0.661222E+10 | 21267.30 | 06-AUG-07:02 | 21267.30 | 0.00 |
September | 0.00 | 0.00 | 0.331776E+10 | 0.315333E+10 | 21886.36 | 07-SEP-06:02 | 14021.12 | 0.00 |
October | 0.00 | 0.00 | 0.410653E+09 | 0.410653E+09 | 8145.55 | 18-OCT-14:00 | 8145.55 | 0.00 |
November | 0.00 | 0.00 | 3655.42 | 3655.42 | 0.22 | 04-NOV-14:00 | 0.22 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.239851E+11 | 0.234416E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.815671E+10 | 0.797222E+10 | 22888.20 | 21267.30 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 1513.54 | 1513.54 | 0.20 | 27-FEB-12:50 | 0.20 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 71668079.46 | 71668079.46 | 4377.79 | 07-APR-14:00 | 4377.79 | 0.00 |
May | 0.00 | 0.00 | 0.104307E+10 | 0.103942E+10 | 9947.33 | 20-MAY-16:00 | 9947.33 | 0.00 |
June | 0.00 | 0.00 | 0.429003E+10 | 0.413415E+10 | 22066.33 | 22-JUN-06:02 | 15086.21 | 0.00 |
July | 0.00 | 0.00 | 0.818352E+10 | 0.799762E+10 | 22952.93 | 19-JUL-06:02 | 15540.19 | 0.00 |
August | 0.00 | 0.00 | 0.665624E+10 | 0.662190E+10 | 21330.83 | 06-AUG-07:02 | 21330.83 | 0.00 |
September | 0.00 | 0.00 | 0.331094E+10 | 0.314601E+10 | 21948.21 | 07-SEP-06:02 | 14067.94 | 0.00 |
October | 0.00 | 0.00 | 0.387821E+09 | 0.387821E+09 | 8045.74 | 18-OCT-14:00 | 8045.74 | 0.00 |
November | 0.00 | 0.00 | 2739.58 | 2739.58 | 0.21 | 04-NOV-14:00 | 0.21 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.239433E+11 | 0.233986E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.818352E+10 | 0.799762E+10 | 22952.93 | 21330.83 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 904.56 | 904.56 | 0.18 | 27-FEB-12:00 | 0.18 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 58494168.91 | 58494168.91 | 4004.75 | 07-APR-14:00 | 4004.75 | 0.00 |
May | 0.00 | 0.00 | 0.982026E+09 | 0.978846E+09 | 9738.73 | 20-MAY-16:00 | 9738.73 | 0.00 |
June | 0.00 | 0.00 | 0.415294E+10 | 0.400281E+10 | 19072.41 | 22-JUN-06:02 | 13009.93 | 0.00 |
July | 0.00 | 0.00 | 0.799728E+10 | 0.781757E+10 | 22782.83 | 19-JUL-06:02 | 15395.44 | 0.00 |
August | 0.00 | 0.00 | 0.648712E+10 | 0.645497E+10 | 21169.54 | 06-AUG-07:02 | 21169.54 | 0.00 |
September | 0.00 | 0.00 | 0.321244E+10 | 0.305177E+10 | 21785.39 | 07-SEP-06:02 | 13934.82 | 0.00 |
October | 0.00 | 0.00 | 0.351829E+09 | 0.351829E+09 | 7803.44 | 18-OCT-14:00 | 7803.44 | 0.00 |
November | 0.00 | 0.00 | 1863.92 | 1863.92 | 0.18 | 04-NOV-14:00 | 0.18 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.232421E+11 | 0.227163E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.799728E+10 | 0.781757E+10 | 22782.83 | 21169.54 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 916.48 | 916.48 | 0.21 | 27-FEB-15:10 | 0.21 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 55778588.43 | 55778588.43 | 5549.97 | 07-APR-14:00 | 5549.97 | 0.00 |
May | 0.00 | 0.00 | 0.150853E+10 | 0.150436E+10 | 16825.65 | 20-MAY-16:00 | 16825.65 | 0.00 |
June | 0.00 | 0.00 | 0.703320E+10 | 0.675372E+10 | 24636.34 | 22-JUN-07:03 | 18693.22 | 0.00 |
July | 0.00 | 0.00 | 0.137555E+11 | 0.134437E+11 | 40583.36 | 19-JUL-07:02 | 27950.84 | 0.00 |
August | 0.00 | 0.00 | 0.111036E+11 | 0.110527E+11 | 37987.70 | 06-AUG-08:62 | 37987.70 | 0.00 |
September | 0.00 | 0.00 | 0.532229E+10 | 0.503102E+10 | 38535.82 | 07-SEP-07:02 | 24487.24 | 0.00 |
October | 0.00 | 0.00 | 0.487474E+09 | 0.487474E+09 | 13137.95 | 18-OCT-14:30 | 13137.95 | 0.00 |
November | 0.00 | 0.00 | 825.94 | 825.94 | 0.20 | 04-NOV-14:00 | 0.20 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.392664E+11 | 0.383288E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.137555E+11 | 0.134437E+11 | 40583.36 | 37987.70 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 293.20 | 293.20 | 0.09 | 27-FEB-15:10 | 0.09 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 24559797.86 | 24559797.86 | 2837.04 | 07-APR-14:00 | 2837.04 | 0.00 |
May | 0.00 | 0.00 | 0.769250E+09 | 0.767346E+09 | 8844.78 | 20-MAY-16:00 | 8844.78 | 0.00 |
June | 0.00 | 0.00 | 0.363969E+10 | 0.349741E+10 | 10786.23 | 20-JUN-16:10 | 9079.26 | 0.00 |
July | 0.00 | 0.00 | 0.716072E+10 | 0.700094E+10 | 22263.13 | 19-JUL-07:02 | 15328.35 | 0.00 |
August | 0.00 | 0.00 | 0.575971E+10 | 0.573494E+10 | 20836.82 | 06-AUG-08:62 | 20836.82 | 0.00 |
September | 0.00 | 0.00 | 0.274490E+10 | 0.259790E+10 | 20952.92 | 04-SEP-08:62 | 20952.92 | 0.00 |
October | 0.00 | 0.00 | 0.240372E+09 | 0.240372E+09 | 6905.93 | 18-OCT-14:40 | 6905.93 | 0.00 |
November | 0.00 | 0.00 | 466.03 | 466.03 | 0.14 | 04-NOV-15:40 | 0.14 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.203392E+11 | 0.198635E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.716072E+10 | 0.700094E+10 | 22263.13 | 20952.92 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 196.88 | 196.88 | 0.08 | 27-FEB-15:10 | 0.08 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 21432283.01 | 21432283.01 | 2700.48 | 07-APR-14:00 | 2700.48 | 0.00 |
May | 0.00 | 0.00 | 0.743995E+09 | 0.742218E+09 | 8733.93 | 20-MAY-16:00 | 8733.93 | 0.00 |
June | 0.00 | 0.00 | 0.357636E+10 | 0.343643E+10 | 10674.91 | 20-JUN-16:10 | 8979.42 | 0.00 |
July | 0.00 | 0.00 | 0.707448E+10 | 0.691718E+10 | 22239.54 | 19-JUL-07:02 | 15299.31 | 0.00 |
August | 0.00 | 0.00 | 0.568518E+10 | 0.566109E+10 | 20812.88 | 06-AUG-08:62 | 20812.88 | 0.00 |
September | 0.00 | 0.00 | 0.270232E+10 | 0.255745E+10 | 20929.09 | 04-SEP-08:62 | 20929.09 | 0.00 |
October | 0.00 | 0.00 | 0.228214E+09 | 0.228214E+09 | 6786.38 | 18-OCT-14:40 | 6786.38 | 0.00 |
November | 0.00 | 0.00 | 1143.19 | 1143.19 | 1.36 | 04-NOV-15:40 | 1.36 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.200320E+11 | 0.195640E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.707448E+10 | 0.691718E+10 | 22239.54 | 20929.09 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 15057447.90 | 15057447.90 | 2357.79 | 07-APR-14:00 | 2357.79 | 0.00 |
May | 0.00 | 0.00 | 0.688737E+09 | 0.687232E+09 | 8501.65 | 20-MAY-16:00 | 8501.65 | 0.00 |
June | 0.00 | 0.00 | 0.344087E+10 | 0.330590E+10 | 10519.33 | 29-JUN-15:00 | 10519.33 | 0.00 |
July | 0.00 | 0.00 | 0.692212E+10 | 0.676965E+10 | 22413.50 | 19-JUL-07:02 | 15382.76 | 0.00 |
August | 0.00 | 0.00 | 0.555140E+10 | 0.552875E+10 | 20970.22 | 06-AUG-08:62 | 20970.22 | 0.00 |
September | 0.00 | 0.00 | 0.262175E+10 | 0.248103E+10 | 21014.44 | 04-SEP-08:62 | 21014.44 | 0.00 |
October | 0.00 | 0.00 | 0.201625E+09 | 0.201625E+09 | 6526.66 | 18-OCT-14:40 | 6526.66 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.194416E+11 | 0.189892E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.692212E+10 | 0.676965E+10 | 22413.50 | 21014.44 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 5234517.39 | 5234517.39 | 1547.69 | 07-APR-14:00 | 1547.69 | 0.00 |
May | 0.00 | 0.00 | 0.600193E+09 | 0.598970E+09 | 8178.10 | 20-MAY-16:00 | 8178.10 | 0.00 |
June | 0.00 | 0.00 | 0.327299E+10 | 0.314226E+10 | 10561.53 | 29-JUN-15:00 | 10561.53 | 0.00 |
July | 0.00 | 0.00 | 0.687372E+10 | 0.672438E+10 | 23652.90 | 17-JUL-07:02 | 21833.87 | 0.00 |
August | 0.00 | 0.00 | 0.547546E+10 | 0.545473E+10 | 16945.96 | 06-AUG-08:62 | 16945.96 | 0.00 |
September | 0.00 | 0.00 | 0.253605E+10 | 0.240356E+10 | 23146.16 | 04-SEP-08:62 | 23146.16 | 0.00 |
October | 0.00 | 0.00 | 0.159315E+09 | 0.159315E+09 | 6205.03 | 18-OCT-14:40 | 6205.03 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.189230E+11 | 0.184885E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.687372E+10 | 0.672438E+10 | 23652.90 | 23146.16 | 0.00 |
Report: FanReportMonthly
For: PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.492948E+10 | 0.75 | 2699.77 | 01-JAN-09:03 | 1.03 |
February | 0.444004E+10 | 0.71 | 2699.77 | 02-FEB-21:15 | 1.03 |
March | 0.491424E+10 | 0.71 | 2699.77 | 02-MAR-09:40 | 1.03 |
April | 0.475285E+10 | 0.70 | 2699.77 | 04-APR-08:20 | 1.03 |
May | 0.489928E+10 | 0.70 | 2699.77 | 01-MAY-07:08 | 1.03 |
June | 0.475267E+10 | 0.69 | 2699.77 | 03-JUN-11:30 | 1.02 |
July | 0.490817E+10 | 0.69 | 2699.77 | 01-JUL-09:10 | 1.02 |
August | 0.489845E+10 | 0.69 | 2699.77 | 01-AUG-12:10 | 1.02 |
September | 0.476239E+10 | 0.70 | 2699.77 | 01-SEP-09:40 | 1.02 |
October | 0.489845E+10 | 0.70 | 2699.77 | 04-OCT-08:63 | 1.03 |
November | 0.473800E+10 | 0.70 | 2699.77 | 04-NOV-22:00 | 1.03 |
December | 0.492543E+10 | 0.71 | 2699.77 | 01-DEC-21:05 | 1.03 |
Annual Sum or Average | 0.578195E+11 | 0.70 | |||
Minimum of Months | 0.444004E+10 | 0.69 | 2699.77 | 1.02 | |
Maximum of Months | 0.492948E+10 | 0.75 | 2699.77 | 1.03 |
Report: FanReportMonthly
For: PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.210899E+10 | 0.63 | 1540.77 | 02-JAN-17:20 | 1.07 |
February | 0.190919E+10 | 0.61 | 1540.77 | 01-FEB-09:40 | 1.07 |
March | 0.213049E+10 | 0.60 | 1540.77 | 02-MAR-08:61 | 1.07 |
April | 0.219086E+10 | 0.67 | 1540.77 | 01-APR-08:40 | 1.07 |
May | 0.241604E+10 | 0.67 | 1540.77 | 03-MAY-10:50 | 1.07 |
June | 0.246374E+10 | 0.68 | 1540.77 | 01-JUN-18:40 | 1.06 |
July | 0.245191E+10 | 0.67 | 1540.77 | 01-JUL-10:40 | 1.06 |
August | 0.250395E+10 | 0.68 | 1540.77 | 01-AUG-11:20 | 1.06 |
September | 0.243803E+10 | 0.70 | 1540.77 | 01-SEP-08:40 | 1.06 |
October | 0.234913E+10 | 0.71 | 1540.77 | 03-OCT-15:10 | 1.07 |
November | 0.209795E+10 | 0.64 | 1540.77 | 04-NOV-15:20 | 1.07 |
December | 0.208498E+10 | 0.58 | 1540.77 | 01-DEC-08:30 | 1.07 |
Annual Sum or Average | 0.271453E+11 | 0.65 | |||
Minimum of Months | 0.190919E+10 | 0.58 | 1540.77 | 1.06 | |
Maximum of Months | 0.250395E+10 | 0.71 | 1540.77 | 1.07 |
Report: FanReportMonthly
For: PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.223194E+10 | 0.60 | 1539.70 | 01-JAN-09:20 | 1.07 |
February | 0.201762E+10 | 0.58 | 1539.70 | 01-FEB-20:30 | 1.08 |
March | 0.227264E+10 | 0.59 | 1539.70 | 01-MAR-12:20 | 1.07 |
April | 0.216174E+10 | 0.58 | 1539.70 | 01-APR-07:05 | 1.07 |
May | 0.225042E+10 | 0.58 | 1539.70 | 03-MAY-07:07 | 1.07 |
June | 0.219499E+10 | 0.59 | 1539.70 | 01-JUN-13:40 | 1.06 |
July | 0.221716E+10 | 0.57 | 1539.70 | 01-JUL-08:40 | 1.06 |
August | 0.227259E+10 | 0.59 | 1539.70 | 01-AUG-10:50 | 1.06 |
September | 0.216174E+10 | 0.58 | 1539.70 | 04-SEP-07:03 | 1.06 |
October | 0.222825E+10 | 0.58 | 1539.70 | 02-OCT-13:00 | 1.07 |
November | 0.216174E+10 | 0.58 | 1539.70 | 04-NOV-11:40 | 1.07 |
December | 0.221751E+10 | 0.58 | 1539.70 | 01-DEC-10:40 | 1.07 |
Annual Sum or Average | 0.263883E+11 | 0.58 | |||
Minimum of Months | 0.201762E+10 | 0.57 | 1539.70 | 1.06 | |
Maximum of Months | 0.227264E+10 | 0.60 | 1539.70 | 1.08 |
Report: FanReportMonthly
For: PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.224063E+10 | 0.61 | 1543.94 | 03-JAN-10:40 | 1.07 |
February | 0.202328E+10 | 0.58 | 1543.94 | 01-FEB-19:10 | 1.08 |
March | 0.227937E+10 | 0.59 | 1543.94 | 02-MAR-10:10 | 1.07 |
April | 0.216769E+10 | 0.58 | 1543.94 | 02-APR-08:05 | 1.07 |
May | 0.225662E+10 | 0.58 | 1543.94 | 01-MAY-13:40 | 1.07 |
June | 0.220104E+10 | 0.59 | 1543.94 | 01-JUN-15:10 | 1.06 |
July | 0.222327E+10 | 0.57 | 1543.94 | 08-JUL-11:40 | 1.07 |
August | 0.227885E+10 | 0.59 | 1543.94 | 01-AUG-15:40 | 1.06 |
September | 0.216769E+10 | 0.58 | 1543.94 | 01-SEP-10:20 | 1.06 |
October | 0.223439E+10 | 0.58 | 1543.94 | 03-OCT-15:00 | 1.07 |
November | 0.216769E+10 | 0.58 | 1543.94 | 03-NOV-08:00 | 1.07 |
December | 0.222381E+10 | 0.58 | 1543.94 | 01-DEC-08:00 | 1.07 |
Annual Sum or Average | 0.264643E+11 | 0.58 | |||
Minimum of Months | 0.202328E+10 | 0.57 | 1543.94 | 1.06 | |
Maximum of Months | 0.227937E+10 | 0.61 | 1543.94 | 1.08 |
Report: FanReportMonthly
For: PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.222624E+10 | 0.62 | 1532.84 | 02-JAN-08:05 | 1.07 |
February | 0.200889E+10 | 0.58 | 1532.84 | 06-FEB-07:06 | 1.07 |
March | 0.226336E+10 | 0.59 | 1532.84 | 01-MAR-08:05 | 1.07 |
April | 0.215211E+10 | 0.58 | 1532.84 | 07-APR-13:00 | 1.07 |
May | 0.224040E+10 | 0.58 | 1532.84 | 08-MAY-08:50 | 1.07 |
June | 0.218522E+10 | 0.59 | 1532.84 | 10-JUN-13:30 | 1.07 |
July | 0.220729E+10 | 0.57 | 1532.84 | 06-JUL-10:50 | 1.06 |
August | 0.226248E+10 | 0.59 | 1532.84 | 14-AUG-13:10 | 1.07 |
September | 0.215211E+10 | 0.58 | 1532.84 | 14-SEP-16:00 | 1.06 |
October | 0.221833E+10 | 0.58 | 1532.84 | 16-OCT-14:40 | 1.07 |
November | 0.215211E+10 | 0.58 | 1532.84 | 10-NOV-14:00 | 1.07 |
December | 0.220793E+10 | 0.58 | 1532.84 | 11-DEC-11:20 | 1.07 |
Annual Sum or Average | 0.262765E+11 | 0.58 | |||
Minimum of Months | 0.200889E+10 | 0.57 | 1532.84 | 1.06 | |
Maximum of Months | 0.226336E+10 | 0.62 | 1532.84 | 1.07 |
Report: FanReportMonthly
For: PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.351151E+10 | 0.58 | 2605.37 | 01-JAN-09:10 | 1.03 |
February | 0.315462E+10 | 0.52 | 2605.37 | 03-FEB-09:30 | 1.03 |
March | 0.355906E+10 | 0.53 | 2605.37 | 01-MAR-14:00 | 1.03 |
April | 0.337656E+10 | 0.51 | 2605.37 | 02-APR-10:40 | 1.03 |
May | 0.351725E+10 | 0.52 | 2605.37 | 01-MAY-09:00 | 1.03 |
June | 0.343283E+10 | 0.52 | 2605.37 | 01-JUN-15:10 | 1.02 |
July | 0.346097E+10 | 0.51 | 2605.37 | 01-JUL-12:50 | 1.02 |
August | 0.355477E+10 | 0.52 | 2605.37 | 02-AUG-09:40 | 1.02 |
September | 0.337656E+10 | 0.51 | 2605.37 | 01-SEP-19:17 | 1.02 |
October | 0.347973E+10 | 0.51 | 2605.37 | 03-OCT-12:40 | 1.03 |
November | 0.337667E+10 | 0.51 | 2605.37 | 02-NOV-08:63 | 1.03 |
December | 0.346612E+10 | 0.52 | 2605.37 | 01-DEC-08:50 | 1.03 |
Annual Sum or Average | 0.412666E+11 | 0.52 | |||
Minimum of Months | 0.315462E+10 | 0.51 | 2605.37 | 1.02 | |
Maximum of Months | 0.355906E+10 | 0.58 | 2605.37 | 1.03 |
Report: FanReportMonthly
For: PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.200369E+10 | 0.60 | 1488.45 | 03-JAN-15:00 | 1.07 |
February | 0.180196E+10 | 0.55 | 1488.45 | 07-FEB-16:00 | 1.07 |
March | 0.203312E+10 | 0.56 | 1488.45 | 01-MAR-20:00 | 1.07 |
April | 0.192903E+10 | 0.54 | 1488.45 | 18-APR-16:00 | 1.07 |
May | 0.200941E+10 | 0.54 | 1488.45 | 01-MAY-15:10 | 1.07 |
June | 0.196118E+10 | 0.54 | 1488.45 | 16-JUN-16:30 | 1.07 |
July | 0.197726E+10 | 0.53 | 1488.45 | 14-JUL-08:70 | 1.06 |
August | 0.203084E+10 | 0.54 | 1488.45 | 20-AUG-12:40 | 1.06 |
September | 0.192903E+10 | 0.53 | 1488.45 | 09-SEP-08:00 | 1.07 |
October | 0.198798E+10 | 0.53 | 1488.45 | 21-OCT-14:10 | 1.07 |
November | 0.192912E+10 | 0.54 | 1488.45 | 02-NOV-16:50 | 1.07 |
December | 0.197988E+10 | 0.54 | 1488.45 | 03-DEC-17:00 | 1.07 |
Annual Sum or Average | 0.235725E+11 | 0.54 | |||
Minimum of Months | 0.180196E+10 | 0.53 | 1488.45 | 1.06 | |
Maximum of Months | 0.203312E+10 | 0.60 | 1488.45 | 1.07 |
Report: FanReportMonthly
For: PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.200244E+10 | 0.60 | 1487.00 | 02-JAN-15:20 | 1.07 |
February | 0.180037E+10 | 0.55 | 1487.00 | 01-FEB-08:40 | 1.08 |
March | 0.203128E+10 | 0.56 | 1487.00 | 01-MAR-13:20 | 1.07 |
April | 0.192716E+10 | 0.54 | 1487.00 | 01-APR-09:20 | 1.07 |
May | 0.200745E+10 | 0.54 | 1487.00 | 01-MAY-09:50 | 1.07 |
June | 0.195927E+10 | 0.54 | 1487.00 | 02-JUN-15:10 | 1.07 |
July | 0.197533E+10 | 0.53 | 1487.00 | 01-JUL-14:30 | 1.06 |
August | 0.202887E+10 | 0.54 | 1487.00 | 02-AUG-09:30 | 1.07 |
September | 0.192716E+10 | 0.53 | 1487.00 | 01-SEP-11:20 | 1.06 |
October | 0.198604E+10 | 0.53 | 1487.00 | 03-OCT-10:00 | 1.07 |
November | 0.192730E+10 | 0.54 | 1487.00 | 01-NOV-07:30 | 1.07 |
December | 0.197802E+10 | 0.54 | 1487.00 | 01-DEC-10:10 | 1.07 |
Annual Sum or Average | 0.235507E+11 | 0.54 | |||
Minimum of Months | 0.180037E+10 | 0.53 | 1487.00 | 1.06 | |
Maximum of Months | 0.203128E+10 | 0.60 | 1487.00 | 1.08 |
Report: FanReportMonthly
For: PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.202130E+10 | 0.61 | 1498.99 | 01-JAN-09:09 | 1.07 |
February | 0.181582E+10 | 0.55 | 1498.99 | 08-FEB-14:40 | 1.07 |
March | 0.204831E+10 | 0.56 | 1498.99 | 06-MAR-13:00 | 1.07 |
April | 0.194269E+10 | 0.53 | 1498.99 | 30-APR-16:20 | 1.07 |
May | 0.202363E+10 | 0.54 | 1498.99 | 01-MAY-07:20 | 1.07 |
June | 0.197506E+10 | 0.54 | 1498.99 | 01-JUN-14:30 | 1.06 |
July | 0.199125E+10 | 0.53 | 1498.99 | 01-JUL-11:00 | 1.06 |
August | 0.204522E+10 | 0.54 | 1498.99 | 01-AUG-07:10 | 1.06 |
September | 0.194269E+10 | 0.53 | 1498.99 | 01-SEP-09:40 | 1.06 |
October | 0.200205E+10 | 0.53 | 1498.99 | 02-OCT-08:10 | 1.07 |
November | 0.194315E+10 | 0.54 | 1498.99 | 01-NOV-08:70 | 1.07 |
December | 0.199486E+10 | 0.55 | 1498.99 | 21-DEC-13:00 | 1.07 |
Annual Sum or Average | 0.237460E+11 | 0.55 | |||
Minimum of Months | 0.181582E+10 | 0.53 | 1498.99 | 1.06 | |
Maximum of Months | 0.204831E+10 | 0.61 | 1498.99 | 1.07 |
Report: FanReportMonthly
For: PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.219922E+10 | 0.68 | 1588.70 | 01-JAN-09:07 | 1.03 |
February | 0.194785E+10 | 0.61 | 1588.70 | 04-FEB-08:10 | 1.03 |
March | 0.218592E+10 | 0.57 | 1588.70 | 12-MAR-14:00 | 1.03 |
April | 0.205960E+10 | 0.52 | 1588.70 | 01-APR-07:15 | 1.03 |
May | 0.214637E+10 | 0.52 | 1588.70 | 01-MAY-07:13 | 1.03 |
June | 0.209327E+10 | 0.52 | 1588.70 | 17-JUN-16:40 | 1.02 |
July | 0.211043E+10 | 0.51 | 1588.70 | 01-JUL-09:10 | 1.02 |
August | 0.216763E+10 | 0.52 | 1588.70 | 01-AUG-11:50 | 1.02 |
September | 0.205896E+10 | 0.51 | 1588.70 | 21-SEP-07:20 | 1.03 |
October | 0.212187E+10 | 0.51 | 1588.70 | 01-OCT-09:30 | 1.02 |
November | 0.206719E+10 | 0.54 | 1588.70 | 01-NOV-07:15 | 1.03 |
December | 0.214022E+10 | 0.60 | 1588.70 | 01-DEC-08:07 | 1.03 |
Annual Sum or Average | 0.252985E+11 | 0.55 | |||
Minimum of Months | 0.194785E+10 | 0.51 | 1588.70 | 1.02 | |
Maximum of Months | 0.219922E+10 | 0.68 | 1588.70 | 1.03 |
Report: ZoneTemperatureOscillationReportMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 2.66 | 0.41 |
February | 2.38 | 0.74 |
March | 1.17 | 0.58 |
April | 0.08 | 1.50 |
May | 0.22 | 7.12 |
June | 0.22 | 0.56 |
July | 0.51 | 0.00 |
August | 0.22 | 0.00 |
September | 0.35 | 0.24 |
October | 0.42 | 1.50 |
November | 0.36 | 0.35 |
December | 2.13 | 0.65 |
Annual Sum or Average | 10.72 | 0.71 |
Minimum of Months | 0.08 | 0.00 |
Maximum of Months | 2.66 | 7.12 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.86 | 0.95 |
February | 0.46 | 2.16 |
March | 0.71 | 6.13 |
April | 0.92 | 5.20 |
May | 2.17 | 4.06 |
June | 4.46 | 3.85 |
July | 5.60 | 2.69 |
August | 3.96 | 2.98 |
September | 2.56 | 3.10 |
October | 0.58 | 4.43 |
November | 0.89 | 4.71 |
December | 0.41 | 1.51 |
Annual Sum or Average | 23.59 | 3.35 |
Minimum of Months | 0.41 | 0.95 |
Maximum of Months | 5.60 | 6.13 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.57 | 0.00 |
February | 0.32 | 0.00 |
March | 0.44 | 0.00 |
April | 0.39 | 0.59 |
May | 1.78 | 0.50 |
June | 1.85 | 0.75 |
July | 3.41 | 0.73 |
August | 2.20 | 0.75 |
September | 2.10 | 0.78 |
October | 1.19 | 0.91 |
November | 0.44 | 0.14 |
December | 0.39 | 0.00 |
Annual Sum or Average | 15.10 | 0.63 |
Minimum of Months | 0.32 | 0.00 |
Maximum of Months | 3.41 | 0.91 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.57 | 0.00 |
February | 0.41 | 0.00 |
March | 0.44 | 0.00 |
April | 0.81 | 0.21 |
May | 1.48 | 0.54 |
June | 1.85 | 0.75 |
July | 3.36 | 0.73 |
August | 2.20 | 0.75 |
September | 2.18 | 0.78 |
October | 1.11 | 0.75 |
November | 0.50 | 0.13 |
December | 0.51 | 0.00 |
Annual Sum or Average | 15.41 | 0.59 |
Minimum of Months | 0.41 | 0.00 |
Maximum of Months | 3.36 | 0.78 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.95 | 0.00 |
February | 0.57 | 0.00 |
March | 0.19 | 0.00 |
April | 0.64 | 0.26 |
May | 1.14 | 0.64 |
June | 1.85 | 0.75 |
July | 3.41 | 0.73 |
August | 2.12 | 0.75 |
September | 1.68 | 0.71 |
October | 0.93 | 0.75 |
November | 0.41 | 0.15 |
December | 0.59 | 0.00 |
Annual Sum or Average | 14.49 | 0.57 |
Minimum of Months | 0.19 | 0.00 |
Maximum of Months | 3.41 | 0.75 |
Report: ZoneTemperatureOscillationReportMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 2.21 | 0.00 |
February | 1.11 | 0.00 |
March | 0.39 | 0.00 |
April | 0.00 | 0.00 |
May | 0.51 | 2.76 |
June | 0.61 | 3.30 |
July | 1.76 | 2.62 |
August | 0.56 | 3.30 |
September | 0.78 | 2.95 |
October | 0.22 | 3.30 |
November | 0.15 | 0.00 |
December | 1.34 | 0.00 |
Annual Sum or Average | 9.64 | 1.34 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 2.21 | 3.30 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 1.59 | 0.00 |
February | 0.80 | 0.00 |
March | 0.31 | 0.00 |
April | 0.00 | 0.00 |
May | 0.54 | 1.29 |
June | 0.61 | 1.65 |
July | 1.67 | 1.29 |
August | 0.48 | 1.65 |
September | 0.61 | 1.65 |
October | 0.22 | 1.65 |
November | 0.11 | 0.00 |
December | 1.13 | 0.00 |
Annual Sum or Average | 8.09 | 0.75 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 1.67 | 1.65 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 1.59 | 0.00 |
February | 0.94 | 0.00 |
March | 0.31 | 0.00 |
April | 0.04 | 0.00 |
May | 0.54 | 1.29 |
June | 0.61 | 1.65 |
July | 1.67 | 1.29 |
August | 0.48 | 1.65 |
September | 0.61 | 1.65 |
October | 0.22 | 1.65 |
November | 0.11 | 0.00 |
December | 1.22 | 0.00 |
Annual Sum or Average | 8.35 | 0.72 |
Minimum of Months | 0.04 | 0.00 |
Maximum of Months | 1.67 | 1.65 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 1.82 | 0.00 |
February | 0.99 | 0.00 |
March | 0.43 | 0.00 |
April | 0.10 | 0.00 |
May | 0.58 | 1.20 |
June | 0.56 | 1.65 |
July | 1.42 | 1.42 |
August | 0.48 | 1.65 |
September | 0.61 | 1.65 |
October | 0.17 | 1.65 |
November | 0.24 | 0.00 |
December | 1.31 | 0.00 |
Annual Sum or Average | 8.70 | 0.66 |
Minimum of Months | 0.10 | 0.00 |
Maximum of Months | 1.82 | 1.65 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 4.34 | 0.00 |
February | 3.08 | 0.00 |
March | 2.40 | 0.00 |
April | 0.64 | 0.00 |
May | 0.90 | 0.77 |
June | 0.50 | 1.37 |
July | 1.42 | 1.42 |
August | 0.65 | 1.22 |
September | 0.61 | 1.65 |
October | 0.47 | 0.00 |
November | 1.52 | 0.00 |
December | 3.69 | 0.00 |
Annual Sum or Average | 20.23 | 0.26 |
Minimum of Months | 0.47 | 0.00 |
Maximum of Months | 4.34 | 1.65 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_1:1
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.492948E+10 | 0.373194E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.444004E+10 | 0.197056E+11 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.491424E+10 | 0.146621E+11 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.478696E+10 | 0.437982E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.563630E+10 | 0.278105E+10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.770591E+10 | 48194881.97 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.109004E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.965450E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.719939E+10 | 0.273966E+09 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.513430E+10 | 0.139996E+10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.473801E+10 | 0.100201E+11 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.492543E+10 | 0.258678E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.749649E+11 | 0.116458E+12 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.444004E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.109004E+11 | 0.373194E+11 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_2:2
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.210899E+10 | 0.138899E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.191054E+10 | 0.690888E+10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.213067E+10 | 0.436077E+10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.223048E+10 | 0.107805E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.288351E+10 | 0.713327E+09 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.415870E+10 | 153795.36 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.569911E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.509001E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.377819E+10 | 30059879.25 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.250330E+10 | 0.319339E+09 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.210435E+10 | 0.312134E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.208498E+10 | 0.908103E+10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.366828E+11 | 0.395029E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.191054E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.569911E+10 | 0.138899E+11 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_3:3
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.223194E+10 | 0.155062E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.201762E+10 | 0.807365E+10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.227264E+10 | 0.550803E+10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.218552E+10 | 0.149005E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.256778E+10 | 0.101446E+10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.348574E+10 | 414494.36 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.471213E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.430260E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.315361E+10 | 68727135.41 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.234857E+10 | 0.558984E+09 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.216174E+10 | 0.396937E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.221751E+10 | 0.106155E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.336574E+11 | 0.468054E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.201762E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.471213E+10 | 0.155062E+11 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_4:4
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.224063E+10 | 0.159560E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.202328E+10 | 0.837472E+10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.227937E+10 | 0.585088E+10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.218913E+10 | 0.164540E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.256698E+10 | 0.111793E+10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.348788E+10 | 1077450.23 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.472636E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.431219E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.315785E+10 | 88113824.35 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.234821E+10 | 0.643947E+09 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.216769E+10 | 0.424479E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.222381E+10 | 0.110050E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.337234E+11 | 0.489278E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.202328E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.472636E+10 | 0.159560E+11 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_5:5
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.222624E+10 | 0.165676E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.200889E+10 | 0.884130E+10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.226336E+10 | 0.636885E+10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.216970E+10 | 0.192106E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.253349E+10 | 0.127864E+10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.343371E+10 | 4966404.38 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.465791E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.424805E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.311452E+10 | 0.124883E+09 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.232186E+10 | 0.771398E+09 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.215211E+10 | 0.463660E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.220793E+10 | 0.115846E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.333378E+11 | 0.520999E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.200889E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.465791E+10 | 0.165676E+11 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_6:6
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.351151E+10 | 0.328780E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.315462E+10 | 0.180076E+11 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.355906E+10 | 0.137236E+11 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.339351E+10 | 0.466799E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.397145E+10 | 0.303426E+10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.556047E+10 | 63671919.10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.770147E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.697490E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.497776E+10 | 0.461431E+09 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.362418E+10 | 0.204438E+10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.337667E+10 | 0.101494E+11 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.346612E+10 | 0.235031E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.532717E+11 | 0.108533E+12 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.315462E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.770147E+10 | 0.328780E+11 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_7:7
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.200369E+10 | 0.172428E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.180196E+10 | 0.946182E+10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.203312E+10 | 0.724528E+10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.193652E+10 | 0.248343E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.224212E+10 | 0.162071E+10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.306838E+10 | 35027535.63 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.419862E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.381624E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.275995E+10 | 0.247989E+09 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.205946E+10 | 0.107984E+10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.192912E+10 | 0.535452E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.197988E+10 | 0.123431E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.298291E+11 | 0.571146E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.180196E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.419862E+10 | 0.172428E+11 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_8:8
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.200244E+10 | 0.173584E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.180037E+10 | 0.957306E+10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.203128E+10 | 0.739493E+10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.193370E+10 | 0.260373E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.223296E+10 | 0.168899E+10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.304877E+10 | 40661760.76 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.417265E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.379340E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.274622E+10 | 0.271661E+09 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.205402E+10 | 0.113758E+10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.192730E+10 | 0.547473E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.197802E+10 | 0.124610E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.297211E+11 | 0.580047E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.180037E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.417265E+10 | 0.173584E+11 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_9:9
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.202130E+10 | 0.178757E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.181582E+10 | 0.100184E+11 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.204831E+10 | 0.795011E+10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.194731E+10 | 0.299202E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.223347E+10 | 0.192247E+10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.302746E+10 | 58962005.67 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.414832E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.377398E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.274000E+10 | 0.341108E+09 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.206234E+10 | 0.130603E+10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.194315E+10 | 0.585915E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.199486E+10 | 0.129549E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.297563E+11 | 0.612788E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.181582E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.414832E+10 | 0.178757E+11 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_10:10
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.219922E+10 | 0.223918E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.194785E+10 | 0.128831E+11 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.218592E+10 | 0.107966E+11 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.206124E+10 | 0.458376E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.233195E+10 | 0.289755E+10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.310736E+10 | 0.138976E+09 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.427770E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.389344E+10 | 29451678.11 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.283996E+10 | 0.618526E+09 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.217002E+10 | 0.195718E+10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.206719E+10 | 0.762918E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.214022E+10 | 0.160815E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.312221E+11 | 0.800076E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.194785E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.427770E+10 | 0.223918E+11 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_1:1
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.492948E+10 | 0.00 | 0.298555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.444004E+10 | 2556.64 | 0.157644E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.491424E+10 | 0.00 | 0.117297E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.475285E+10 | 0.106951E+09 | 0.350385E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.489928E+10 | 0.233953E+10 | 0.222484E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.475267E+10 | 0.931663E+10 | 38555905.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.490817E+10 | 0.185204E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.489845E+10 | 0.146969E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.476239E+10 | 0.767095E+10 | 0.219172E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.489845E+10 | 0.759333E+09 | 0.111997E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.473800E+10 | 5285.94 | 0.801610E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.492543E+10 | 0.00 | 0.206942E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.578195E+11 | 0.534107E+11 | 0.931664E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.444004E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.492948E+10 | 0.185204E+11 | 0.298555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_2:2
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.210899E+10 | 0.00 | 0.111119E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.190919E+10 | 4144203.72 | 0.552711E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.213049E+10 | 559030.95 | 0.348862E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.219086E+10 | 0.141233E+09 | 0.862439E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.241604E+10 | 0.166545E+10 | 0.570661E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.246374E+10 | 0.588150E+10 | 123036.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.245191E+10 | 0.109047E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.250395E+10 | 0.867691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.243803E+10 | 0.457470E+10 | 24047903.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.234913E+10 | 0.539154E+09 | 0.255471E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.209795E+10 | 24823481.98 | 0.249707E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.208498E+10 | 0.00 | 0.726483E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.271453E+11 | 0.324132E+11 | 0.316023E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.190919E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.250395E+10 | 0.109047E+11 | 0.111119E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_3:3
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.223194E+10 | 0.00 | 0.124050E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.201762E+10 | 2315.41 | 0.645892E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.227264E+10 | 0.00 | 0.440643E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.216174E+10 | 79706723.03 | 0.119204E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.225042E+10 | 0.106814E+10 | 0.811564E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.219499E+10 | 0.430561E+10 | 331595.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.221716E+10 | 0.815671E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.227259E+10 | 0.664649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.216174E+10 | 0.331776E+10 | 54981708.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.222825E+10 | 0.410653E+09 | 0.447187E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.216174E+10 | 3655.42 | 0.317549E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.221751E+10 | 0.00 | 0.849243E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.263883E+11 | 0.239851E+11 | 0.374444E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.201762E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.227264E+10 | 0.815671E+10 | 0.124050E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_4:4
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.224063E+10 | 0.00 | 0.127648E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.202328E+10 | 1513.54 | 0.669977E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.227937E+10 | 0.00 | 0.468070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.216769E+10 | 71668079.46 | 0.131632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.225662E+10 | 0.104307E+10 | 0.894348E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.220104E+10 | 0.429003E+10 | 861960.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.222327E+10 | 0.818352E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.227885E+10 | 0.665624E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.216769E+10 | 0.331094E+10 | 70491059.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.223439E+10 | 0.387821E+09 | 0.515157E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.216769E+10 | 2739.58 | 0.339583E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.222381E+10 | 0.00 | 0.880396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.264643E+11 | 0.239433E+11 | 0.391422E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.202328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.227937E+10 | 0.818352E+10 | 0.127648E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_5:5
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.222624E+10 | 0.00 | 0.132541E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.200889E+10 | 904.56 | 0.707304E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.226336E+10 | 0.00 | 0.509508E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.215211E+10 | 58494168.91 | 0.153685E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.224040E+10 | 0.982026E+09 | 0.102291E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.218522E+10 | 0.415294E+10 | 3973123.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.220729E+10 | 0.799728E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.226248E+10 | 0.648712E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.215211E+10 | 0.321244E+10 | 99906506.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.221833E+10 | 0.351829E+09 | 0.617118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.215211E+10 | 1863.92 | 0.370928E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.220793E+10 | 0.00 | 0.926767E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.262765E+11 | 0.232421E+11 | 0.416799E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.200889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.226336E+10 | 0.799728E+10 | 0.132541E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_6:6
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.351151E+10 | 0.00 | 0.263024E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.315462E+10 | 916.48 | 0.144061E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.355906E+10 | 0.00 | 0.109789E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.337656E+10 | 55778588.43 | 0.373439E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.351725E+10 | 0.150853E+10 | 0.242741E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.343283E+10 | 0.703320E+10 | 50937535.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.346097E+10 | 0.137555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.355477E+10 | 0.111036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.337656E+10 | 0.532229E+10 | 0.369145E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.347973E+10 | 0.487474E+09 | 0.163550E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.337667E+10 | 825.94 | 0.811951E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.346612E+10 | 0.00 | 0.188025E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.412666E+11 | 0.392664E+11 | 0.868268E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.315462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.355906E+10 | 0.137555E+11 | 0.263024E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_7:7
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.200369E+10 | 0.00 | 0.137943E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.180196E+10 | 293.20 | 0.756946E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.203312E+10 | 0.00 | 0.579622E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.192903E+10 | 24559797.86 | 0.198675E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.200941E+10 | 0.769250E+09 | 0.129657E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.196118E+10 | 0.363969E+10 | 28022028.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.197726E+10 | 0.716072E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.203084E+10 | 0.575971E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.192903E+10 | 0.274490E+10 | 0.198391E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.198798E+10 | 0.240372E+09 | 0.863868E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.192912E+10 | 466.03 | 0.428362E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.197988E+10 | 0.00 | 0.987451E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.235725E+11 | 0.203392E+11 | 0.456917E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.180196E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.203312E+10 | 0.716072E+10 | 0.137943E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_8:8
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.200244E+10 | 0.00 | 0.138867E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.180037E+10 | 196.88 | 0.765845E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.203128E+10 | 0.00 | 0.591594E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.192716E+10 | 21432283.01 | 0.208299E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.200745E+10 | 0.743995E+09 | 0.135119E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.195927E+10 | 0.357636E+10 | 32529408.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.197533E+10 | 0.707448E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.202887E+10 | 0.568518E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.192716E+10 | 0.270232E+10 | 0.217329E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.198604E+10 | 0.228214E+09 | 0.910065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.192730E+10 | 1143.19 | 0.437979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.197802E+10 | 0.00 | 0.996883E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.235507E+11 | 0.200320E+11 | 0.464038E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.180037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.203128E+10 | 0.707448E+10 | 0.138867E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_9:9
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.202130E+10 | 0.00 | 0.143005E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.181582E+10 | 0.00 | 0.801474E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.204831E+10 | 0.00 | 0.636009E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.194269E+10 | 15057447.90 | 0.239362E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.202363E+10 | 0.688737E+09 | 0.153797E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.197506E+10 | 0.344087E+10 | 47169604.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.199125E+10 | 0.692212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.204522E+10 | 0.555140E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.194269E+10 | 0.262175E+10 | 0.272886E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.200205E+10 | 0.201625E+09 | 0.104483E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.194315E+10 | 0.00 | 0.468732E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.199486E+10 | 0.00 | 0.103639E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.237460E+11 | 0.194416E+11 | 0.490230E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.181582E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.204831E+10 | 0.692212E+10 | 0.143005E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_10:10
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.219922E+10 | 0.00 | 0.179134E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.194785E+10 | 0.00 | 0.103065E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.218592E+10 | 0.00 | 0.863727E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.205960E+10 | 5234517.39 | 0.366701E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.214637E+10 | 0.600193E+09 | 0.231804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.209327E+10 | 0.327299E+10 | 0.111181E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.211043E+10 | 0.687372E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.216763E+10 | 0.547546E+10 | 23561342.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.205896E+10 | 0.253605E+10 | 0.494821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.212187E+10 | 0.159315E+09 | 0.156574E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.206719E+10 | 0.00 | 0.610334E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.214022E+10 | 0.00 | 0.128652E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.252985E+11 | 0.189230E+11 | 0.640061E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.194785E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.219922E+10 | 0.687372E+10 | 0.179134E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_1:1
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.492948E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.373194E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.444004E+10 | 0.00 | 0.00 | 0.00 | 830.95 | 0.00 | 0.197056E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.491424E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146621E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.475285E+10 | 0.00 | 0.00 | 0.00 | 34106016.92 | 0.00 | 0.437982E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.489928E+10 | 0.00 | 0.00 | 0.00 | 0.737022E+09 | 0.00 | 0.278105E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.475267E+10 | 0.00 | 0.00 | 0.00 | 0.295325E+10 | 0.00 | 48194881.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.490817E+10 | 0.00 | 0.00 | 0.00 | 0.599220E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.489845E+10 | 0.00 | 0.00 | 0.00 | 0.475605E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.476239E+10 | 0.00 | 0.00 | 0.00 | 0.243701E+10 | 0.00 | 0.273966E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.489845E+10 | 0.00 | 0.00 | 0.00 | 0.235842E+09 | 0.00 | 0.139996E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.473800E+10 | 0.00 | 0.00 | 0.00 | 1718.01 | 0.00 | 0.100201E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.492543E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.258678E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.578195E+11 | 0.00 | 0.00 | 0.00 | 0.171455E+11 | 0.00 | 0.116458E+12 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.444004E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.492948E+10 | 0.00 | 0.00 | 0.00 | 0.599220E+10 | 0.00 | 0.373194E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_2:2
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.210899E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138899E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.190919E+10 | 0.00 | 0.00 | 0.00 | 1351974.21 | 0.00 | 0.690888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.213049E+10 | 0.00 | 0.00 | 0.00 | 184147.46 | 0.00 | 0.436077E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.219086E+10 | 0.00 | 0.00 | 0.00 | 39621163.54 | 0.00 | 0.107805E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.241604E+10 | 0.00 | 0.00 | 0.00 | 0.467474E+09 | 0.00 | 0.713327E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.246374E+10 | 0.00 | 0.00 | 0.00 | 0.169496E+10 | 0.00 | 153795.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.245191E+10 | 0.00 | 0.00 | 0.00 | 0.324719E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.250395E+10 | 0.00 | 0.00 | 0.00 | 0.258607E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.243803E+10 | 0.00 | 0.00 | 0.00 | 0.134015E+10 | 0.00 | 30059879.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.234913E+10 | 0.00 | 0.00 | 0.00 | 0.154163E+09 | 0.00 | 0.319339E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.209795E+10 | 0.00 | 0.00 | 0.00 | 6397125.78 | 0.00 | 0.312134E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.208498E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.908103E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.271453E+11 | 0.00 | 0.00 | 0.00 | 0.953757E+10 | 0.00 | 0.395029E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.190919E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.250395E+10 | 0.00 | 0.00 | 0.00 | 0.324719E+10 | 0.00 | 0.138899E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_3:3
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.223194E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155062E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.201762E+10 | 0.00 | 0.00 | 0.00 | 709.58 | 0.00 | 0.807365E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.227264E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.550803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.216174E+10 | 0.00 | 0.00 | 0.00 | 23781186.56 | 0.00 | 0.149005E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.225042E+10 | 0.00 | 0.00 | 0.00 | 0.317356E+09 | 0.00 | 0.101446E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.219499E+10 | 0.00 | 0.00 | 0.00 | 0.129075E+10 | 0.00 | 414494.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.221716E+10 | 0.00 | 0.00 | 0.00 | 0.249496E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.227259E+10 | 0.00 | 0.00 | 0.00 | 0.203001E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.216174E+10 | 0.00 | 0.00 | 0.00 | 0.991872E+09 | 0.00 | 68727135.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.222825E+10 | 0.00 | 0.00 | 0.00 | 0.120319E+09 | 0.00 | 0.558984E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.216174E+10 | 0.00 | 0.00 | 0.00 | 1120.24 | 0.00 | 0.396937E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.221751E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106155E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.263883E+11 | 0.00 | 0.00 | 0.00 | 0.726905E+10 | 0.00 | 0.468054E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.201762E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.227264E+10 | 0.00 | 0.00 | 0.00 | 0.249496E+10 | 0.00 | 0.155062E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_4:4
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.224063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159560E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.202328E+10 | 0.00 | 0.00 | 0.00 | 463.84 | 0.00 | 0.837472E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.227937E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.585088E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.216769E+10 | 0.00 | 0.00 | 0.00 | 21445197.32 | 0.00 | 0.164540E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.225662E+10 | 0.00 | 0.00 | 0.00 | 0.310365E+09 | 0.00 | 0.111793E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.220104E+10 | 0.00 | 0.00 | 0.00 | 0.128684E+10 | 0.00 | 1077450.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.222327E+10 | 0.00 | 0.00 | 0.00 | 0.250309E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.227885E+10 | 0.00 | 0.00 | 0.00 | 0.203334E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.216769E+10 | 0.00 | 0.00 | 0.00 | 0.990158E+09 | 0.00 | 88113824.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.223439E+10 | 0.00 | 0.00 | 0.00 | 0.113827E+09 | 0.00 | 0.643947E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.216769E+10 | 0.00 | 0.00 | 0.00 | 839.57 | 0.00 | 0.424479E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.222381E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110050E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.264643E+11 | 0.00 | 0.00 | 0.00 | 0.725906E+10 | 0.00 | 0.489278E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.202328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.227937E+10 | 0.00 | 0.00 | 0.00 | 0.250309E+10 | 0.00 | 0.159560E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_5:5
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.222624E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165676E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.200889E+10 | 0.00 | 0.00 | 0.00 | 277.21 | 0.00 | 0.884130E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.226336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.636885E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.215211E+10 | 0.00 | 0.00 | 0.00 | 17585232.73 | 0.00 | 0.192106E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.224040E+10 | 0.00 | 0.00 | 0.00 | 0.293089E+09 | 0.00 | 0.127864E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.218522E+10 | 0.00 | 0.00 | 0.00 | 0.124849E+10 | 0.00 | 4966404.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.220729E+10 | 0.00 | 0.00 | 0.00 | 0.245062E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.226248E+10 | 0.00 | 0.00 | 0.00 | 0.198557E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.215211E+10 | 0.00 | 0.00 | 0.00 | 0.962405E+09 | 0.00 | 0.124883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.221833E+10 | 0.00 | 0.00 | 0.00 | 0.103535E+09 | 0.00 | 0.771398E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.215211E+10 | 0.00 | 0.00 | 0.00 | 571.22 | 0.00 | 0.463660E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.220793E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115846E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.262765E+11 | 0.00 | 0.00 | 0.00 | 0.706130E+10 | 0.00 | 0.520999E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.200889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.226336E+10 | 0.00 | 0.00 | 0.00 | 0.245062E+10 | 0.00 | 0.165676E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_6:6
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.351151E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.328780E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.315462E+10 | 0.00 | 0.00 | 0.00 | 280.86 | 0.00 | 0.180076E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.355906E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137236E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.337656E+10 | 0.00 | 0.00 | 0.00 | 16952012.79 | 0.00 | 0.466799E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.351725E+10 | 0.00 | 0.00 | 0.00 | 0.454204E+09 | 0.00 | 0.303426E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.343283E+10 | 0.00 | 0.00 | 0.00 | 0.212764E+10 | 0.00 | 63671919.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.346097E+10 | 0.00 | 0.00 | 0.00 | 0.424050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.355477E+10 | 0.00 | 0.00 | 0.00 | 0.342014E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.337656E+10 | 0.00 | 0.00 | 0.00 | 0.160120E+10 | 0.00 | 0.461431E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.347973E+10 | 0.00 | 0.00 | 0.00 | 0.144448E+09 | 0.00 | 0.204438E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.337667E+10 | 0.00 | 0.00 | 0.00 | 253.12 | 0.00 | 0.101494E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.346612E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.235031E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.412666E+11 | 0.00 | 0.00 | 0.00 | 0.120051E+11 | 0.00 | 0.108533E+12 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.315462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.355906E+10 | 0.00 | 0.00 | 0.00 | 0.424050E+10 | 0.00 | 0.328780E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_7:7
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.200369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172428E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.180196E+10 | 0.00 | 0.00 | 0.00 | 89.85 | 0.00 | 0.946182E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.203312E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.724528E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.192903E+10 | 0.00 | 0.00 | 0.00 | 7488621.06 | 0.00 | 0.248343E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.200941E+10 | 0.00 | 0.00 | 0.00 | 0.232711E+09 | 0.00 | 0.162071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.196118E+10 | 0.00 | 0.00 | 0.00 | 0.110720E+10 | 0.00 | 35027535.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.222136E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.203084E+10 | 0.00 | 0.00 | 0.00 | 0.178540E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.192903E+10 | 0.00 | 0.00 | 0.00 | 0.830920E+09 | 0.00 | 0.247989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.198798E+10 | 0.00 | 0.00 | 0.00 | 71485473.78 | 0.00 | 0.107984E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.192912E+10 | 0.00 | 0.00 | 0.00 | 142.82 | 0.00 | 0.535452E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.197988E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123431E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.235725E+11 | 0.00 | 0.00 | 0.00 | 0.625656E+10 | 0.00 | 0.571146E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.180196E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.203312E+10 | 0.00 | 0.00 | 0.00 | 0.222136E+10 | 0.00 | 0.172428E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_8:8
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.200244E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.173584E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.180037E+10 | 0.00 | 0.00 | 0.00 | 60.34 | 0.00 | 0.957306E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.203128E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.739493E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.192716E+10 | 0.00 | 0.00 | 0.00 | 6547665.78 | 0.00 | 0.260373E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.200745E+10 | 0.00 | 0.00 | 0.00 | 0.225505E+09 | 0.00 | 0.168899E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.195927E+10 | 0.00 | 0.00 | 0.00 | 0.108950E+10 | 0.00 | 40661760.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.197533E+10 | 0.00 | 0.00 | 0.00 | 0.219731E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.202887E+10 | 0.00 | 0.00 | 0.00 | 0.176454E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.192716E+10 | 0.00 | 0.00 | 0.00 | 0.819062E+09 | 0.00 | 0.271661E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.198604E+10 | 0.00 | 0.00 | 0.00 | 67975708.65 | 0.00 | 0.113758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.192730E+10 | 0.00 | 0.00 | 0.00 | 350.34 | 0.00 | 0.547473E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.197802E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124610E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.235507E+11 | 0.00 | 0.00 | 0.00 | 0.617043E+10 | 0.00 | 0.580047E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.180037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.203128E+10 | 0.00 | 0.00 | 0.00 | 0.219731E+10 | 0.00 | 0.173584E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_9:9
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.202130E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.178757E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.181582E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100184E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.204831E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.795011E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.194269E+10 | 0.00 | 0.00 | 0.00 | 4624641.42 | 0.00 | 0.299202E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.202363E+10 | 0.00 | 0.00 | 0.00 | 0.209843E+09 | 0.00 | 0.192247E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.197506E+10 | 0.00 | 0.00 | 0.00 | 0.105240E+10 | 0.00 | 58962005.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.199125E+10 | 0.00 | 0.00 | 0.00 | 0.215706E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.204522E+10 | 0.00 | 0.00 | 0.00 | 0.172876E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.194269E+10 | 0.00 | 0.00 | 0.00 | 0.797316E+09 | 0.00 | 0.341108E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.200205E+10 | 0.00 | 0.00 | 0.00 | 60297144.95 | 0.00 | 0.130603E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.194315E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.585915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.199486E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.237460E+11 | 0.00 | 0.00 | 0.00 | 0.601030E+10 | 0.00 | 0.612788E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.181582E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.204831E+10 | 0.00 | 0.00 | 0.00 | 0.215706E+10 | 0.00 | 0.178757E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_10:10
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.219922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.223918E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.194785E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128831E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.218592E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107966E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.205960E+10 | 0.00 | 0.00 | 0.00 | 1631551.07 | 0.00 | 0.458376E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.214637E+10 | 0.00 | 0.00 | 0.00 | 0.185577E+09 | 0.00 | 0.289755E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.209327E+10 | 0.00 | 0.00 | 0.00 | 0.101408E+10 | 0.00 | 0.138976E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.211043E+10 | 0.00 | 0.00 | 0.00 | 0.216727E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.216763E+10 | 0.00 | 0.00 | 0.00 | 0.172581E+10 | 0.00 | 29451678.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.205896E+10 | 0.00 | 0.00 | 0.00 | 0.780999E+09 | 0.00 | 0.618526E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.212187E+10 | 0.00 | 0.00 | 0.00 | 48150197.75 | 0.00 | 0.195718E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.206719E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.762918E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.214022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160815E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.252985E+11 | 0.00 | 0.00 | 0.00 | 0.592352E+10 | 0.00 | 0.800076E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.194785E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.219922E+10 | 0.00 | 0.00 | 0.00 | 0.216727E+10 | 0.00 | 0.223918E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.356969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.184162E+11 | 0.00 | 0.00 | 0.52 |
February | 0.527911E+10 | 0.00 | 0.00 | 77304.14 | 0.00 | 0.992908E+10 | 0.122123E+09 | 0.00 | 0.53 |
March | 0.737460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.729147E+10 | 0.00 | 0.00 | 0.53 |
April | 0.647299E+10 | 0.00 | 0.00 | 2104835.48 | 0.00 | 0.239261E+10 | 0.201190E+10 | 0.00 | 0.64 |
May | 0.439210E+10 | 49115968.81 | 0.00 | 13628562.51 | 1731754.76 | 0.138530E+10 | 0.502385E+10 | 0.00 | 0.95 |
June | 0.808546E+09 | 0.598159E+09 | 0.00 | 26560057.01 | 0.00 | 2020513.34 | 0.767560E+10 | 0.00 | 1.29 |
July | 67912687.30 | 0.151421E+10 | 0.00 | 33525923.09 | 1719894.69 | 0.00 | 0.540193E+10 | 0.00 | 1.24 |
August | 0.348082E+09 | 0.105658E+10 | 0.00 | 33465829.52 | 266124.49 | 0.00 | 0.717270E+10 | 0.00 | 1.36 |
September | 0.209745E+10 | 0.549898E+09 | 0.00 | 21074321.85 | 0.00 | 36326807.71 | 0.757888E+10 | 0.00 | 1.16 |
October | 0.559061E+10 | 4569142.34 | 0.00 | 7460193.43 | 0.00 | 0.638231E+09 | 0.582130E+10 | 0.00 | 0.80 |
November | 0.760660E+10 | 0.00 | 0.00 | 607044.27 | 0.00 | 0.476783E+10 | 0.728131E+09 | 0.00 | 0.53 |
December | 0.558409E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129905E+11 | 0.00 | 0.00 | 0.53 |
Annual Sum or Average | 0.491918E+11 | 0.377253E+10 | 0.00 | 0.138504E+09 | 3717773.94 | 0.578496E+11 | 0.415364E+11 | 0.00 | 0.84 |
Minimum of Months | 67912687.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.52 |
Maximum of Months | 0.760660E+10 | 0.151421E+10 | 0.00 | 33525923.09 | 1731754.76 | 0.184162E+11 | 0.767560E+10 | 0.00 | 1.36 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.132292E+10 | 0.00 | 0.00 | 5970.79 | 0.00 | 0.662197E+10 | 4692602.47 | 0.00 | 0.39 |
February | 0.180474E+10 | 0.00 | 0.00 | 275170.16 | 0.00 | 0.356166E+10 | 0.266636E+09 | 0.00 | 0.41 |
March | 0.283084E+10 | 0.00 | 0.00 | 60271.94 | 0.00 | 0.240329E+10 | 43850932.99 | 0.00 | 0.40 |
April | 0.212705E+10 | 0.00 | 0.00 | 2238616.09 | 0.00 | 0.657701E+09 | 0.201775E+10 | 0.00 | 0.63 |
May | 0.151336E+10 | 25087541.04 | 0.00 | 6133268.02 | 0.00 | 0.459010E+09 | 0.328850E+10 | 0.00 | 0.97 |
June | 0.217453E+09 | 0.300156E+09 | 0.00 | 10087488.91 | 0.00 | 0.00 | 0.430376E+10 | 0.00 | 1.31 |
July | 22442758.52 | 0.740717E+09 | 0.00 | 9878819.54 | 77658.75 | 0.00 | 0.253517E+10 | 0.00 | 1.12 |
August | 0.103863E+09 | 0.510483E+09 | 0.00 | 11842320.59 | 310606.38 | 0.00 | 0.375076E+10 | 0.00 | 1.32 |
September | 0.758153E+09 | 0.270468E+09 | 0.00 | 8858757.55 | 0.00 | 0.00 | 0.440103E+10 | 0.00 | 1.19 |
October | 0.179737E+10 | 2339231.33 | 0.00 | 5360516.97 | 0.00 | 0.182590E+09 | 0.403179E+10 | 0.00 | 0.85 |
November | 0.255800E+10 | 0.00 | 0.00 | 885738.25 | 0.00 | 0.172034E+10 | 0.850376E+09 | 0.00 | 0.44 |
December | 0.201423E+10 | 0.00 | 0.00 | 8242.86 | 0.00 | 0.455935E+10 | 6907042.02 | 0.00 | 0.38 |
Annual Sum or Average | 0.170704E+11 | 0.184925E+10 | 0.00 | 55635181.67 | 388265.13 | 0.201659E+11 | 0.255012E+11 | 0.00 | 0.78 |
Minimum of Months | 22442758.52 | 0.00 | 0.00 | 5970.79 | 0.00 | 0.00 | 4692602.47 | 0.00 | 0.38 |
Maximum of Months | 0.283084E+10 | 0.740717E+09 | 0.00 | 11842320.59 | 310606.38 | 0.662197E+10 | 0.440103E+10 | 0.00 | 1.32 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.804049E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.761476E+10 | 0.00 | 0.00 | 0.41 |
February | 0.150385E+10 | 0.00 | 0.00 | 58333.04 | 0.00 | 0.429971E+10 | 94458452.26 | 0.00 | 0.42 |
March | 0.256416E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.305118E+10 | 0.00 | 0.00 | 0.42 |
April | 0.244489E+10 | 0.00 | 0.00 | 775526.00 | 0.00 | 0.884660E+09 | 0.862926E+09 | 0.00 | 0.54 |
May | 0.180280E+10 | 23526549.55 | 0.00 | 2447065.20 | 903111.37 | 0.584809E+09 | 0.181456E+10 | 0.00 | 0.77 |
June | 0.438135E+09 | 0.275683E+09 | 0.00 | 5004181.96 | 5708299.73 | 0.00 | 0.290005E+10 | 0.00 | 1.06 |
July | 0.101277E+09 | 0.644456E+09 | 0.00 | 4855013.80 | 26502524.03 | 0.00 | 0.175807E+10 | 0.00 | 0.93 |
August | 0.248742E+09 | 0.469486E+09 | 0.00 | 5924052.92 | 14882385.35 | 0.00 | 0.260477E+10 | 0.00 | 1.08 |
September | 0.109583E+10 | 0.231546E+09 | 0.00 | 4411031.71 | 12043019.39 | 1586013.40 | 0.269657E+10 | 0.00 | 0.95 |
October | 0.233190E+10 | 2494716.73 | 0.00 | 2378552.92 | 0.00 | 0.293688E+09 | 0.205725E+10 | 0.00 | 0.70 |
November | 0.262108E+10 | 0.00 | 0.00 | 137348.67 | 0.00 | 0.214446E+10 | 0.210867E+09 | 0.00 | 0.42 |
December | 0.151831E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.550023E+10 | 0.00 | 0.00 | 0.41 |
Annual Sum or Average | 0.174750E+11 | 0.164719E+10 | 0.00 | 25991106.23 | 60039339.87 | 0.243751E+11 | 0.149995E+11 | 0.00 | 0.68 |
Minimum of Months | 0.101277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.262108E+10 | 0.644456E+09 | 0.00 | 5924052.92 | 26502524.03 | 0.761476E+10 | 0.290005E+10 | 0.00 | 1.08 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.671382E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.774719E+10 | 0.00 | 0.00 | 0.41 |
February | 0.140950E+10 | 0.00 | 0.00 | 38400.17 | 0.00 | 0.440441E+10 | 65610787.82 | 0.00 | 0.42 |
March | 0.241472E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.318969E+10 | 0.00 | 0.00 | 0.42 |
April | 0.237313E+10 | 0.00 | 0.00 | 647213.89 | 0.00 | 0.101914E+10 | 0.727067E+09 | 0.00 | 0.53 |
May | 0.175209E+10 | 23364996.64 | 0.00 | 2300572.89 | 1174661.20 | 0.638449E+09 | 0.174667E+10 | 0.00 | 0.76 |
June | 0.442428E+09 | 0.275587E+09 | 0.00 | 4941444.33 | 5709053.89 | 0.00 | 0.287782E+10 | 0.00 | 1.05 |
July | 0.104627E+09 | 0.644774E+09 | 0.00 | 4892074.48 | 26481050.32 | 0.00 | 0.175842E+10 | 0.00 | 0.93 |
August | 0.251979E+09 | 0.470152E+09 | 0.00 | 5923247.48 | 14175076.75 | 0.00 | 0.260532E+10 | 0.00 | 1.09 |
September | 0.110163E+10 | 0.231625E+09 | 0.00 | 4340717.54 | 12021581.01 | 3765141.44 | 0.265355E+10 | 0.00 | 0.95 |
October | 0.231936E+10 | 2496352.20 | 0.00 | 2196760.20 | 0.00 | 0.356966E+09 | 0.191834E+10 | 0.00 | 0.69 |
November | 0.252129E+10 | 0.00 | 0.00 | 99945.83 | 0.00 | 0.226693E+10 | 0.152926E+09 | 0.00 | 0.42 |
December | 0.135117E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.566596E+10 | 0.00 | 0.00 | 0.41 |
Annual Sum or Average | 0.167133E+11 | 0.164800E+10 | 0.00 | 25380376.82 | 59561423.17 | 0.252925E+11 | 0.145057E+11 | 0.00 | 0.67 |
Minimum of Months | 0.104627E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.252129E+10 | 0.644774E+09 | 0.00 | 5923247.48 | 26481050.32 | 0.774719E+10 | 0.287782E+10 | 0.00 | 1.09 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.507546E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.791094E+10 | 0.00 | 0.00 | 0.41 |
February | 0.121321E+10 | 0.00 | 0.00 | 20342.98 | 0.00 | 0.460784E+10 | 38465917.41 | 0.00 | 0.42 |
March | 0.208424E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.350728E+10 | 0.00 | 0.00 | 0.42 |
April | 0.223296E+10 | 0.00 | 0.00 | 487572.84 | 0.00 | 0.122556E+10 | 0.558021E+09 | 0.00 | 0.51 |
May | 0.171854E+10 | 22939010.70 | 0.00 | 1979736.61 | 1791787.94 | 0.749776E+09 | 0.151936E+10 | 0.00 | 0.74 |
June | 0.463613E+09 | 0.274403E+09 | 0.00 | 4545168.02 | 5736129.58 | 0.00 | 0.272548E+10 | 0.00 | 1.03 |
July | 0.114909E+09 | 0.643645E+09 | 0.00 | 4594482.13 | 26866227.90 | 0.00 | 0.169003E+10 | 0.00 | 0.92 |
August | 0.273501E+09 | 0.469275E+09 | 0.00 | 5540772.61 | 15175687.75 | 0.00 | 0.249700E+10 | 0.00 | 1.07 |
September | 0.111107E+10 | 0.230715E+09 | 0.00 | 3995471.68 | 12139793.72 | 25993936.32 | 0.248755E+10 | 0.00 | 0.93 |
October | 0.229761E+10 | 2492079.47 | 0.00 | 1868526.57 | 0.00 | 0.451438E+09 | 0.167351E+10 | 0.00 | 0.66 |
November | 0.232164E+10 | 0.00 | 0.00 | 57470.46 | 0.00 | 0.247450E+10 | 96305720.22 | 0.00 | 0.42 |
December | 0.104367E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.597172E+10 | 0.00 | 0.00 | 0.41 |
Annual Sum or Average | 0.153825E+11 | 0.164347E+10 | 0.00 | 23089543.90 | 61709626.90 | 0.269251E+11 | 0.132857E+11 | 0.00 | 0.66 |
Minimum of Months | 0.114909E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.232164E+10 | 0.643645E+09 | 0.00 | 5540772.61 | 26866227.90 | 0.791094E+10 | 0.272548E+10 | 0.00 | 1.07 |
Report: MechanicalVentilationLoadsMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.205695E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.152604E+11 | 0.00 | 0.00 | 0.38 |
February | 0.115463E+10 | 0.00 | 0.00 | 9750.50 | 0.00 | 0.949012E+10 | 33044416.58 | 0.00 | 0.38 |
March | 0.283764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.731852E+10 | 0.00 | 0.00 | 0.39 |
April | 0.358331E+10 | 0.00 | 0.00 | 482347.95 | 0.00 | 0.266873E+10 | 0.679758E+09 | 0.00 | 0.44 |
May | 0.278437E+10 | 33077073.66 | 0.00 | 2767953.85 | 3727792.93 | 0.171208E+10 | 0.209286E+10 | 0.00 | 0.61 |
June | 0.711356E+09 | 0.514146E+09 | 0.00 | 6921064.26 | 210921.50 | 2060018.42 | 0.411064E+10 | 0.00 | 0.85 |
July | 0.108932E+09 | 0.125869E+10 | 0.00 | 6982170.91 | 20492050.69 | 0.00 | 0.247598E+10 | 0.00 | 0.76 |
August | 0.368769E+09 | 0.884730E+09 | 0.00 | 8460794.45 | 22048587.50 | 0.00 | 0.386709E+10 | 0.00 | 0.90 |
September | 0.167257E+10 | 0.415594E+09 | 0.00 | 5771094.74 | 22512644.73 | 0.362405E+09 | 0.369708E+10 | 0.00 | 0.76 |
October | 0.391091E+10 | 2881761.62 | 0.00 | 2239994.68 | 0.00 | 0.113699E+10 | 0.220118E+10 | 0.00 | 0.54 |
November | 0.316320E+10 | 0.00 | 0.00 | 21283.22 | 0.00 | 0.556340E+10 | 49016898.25 | 0.00 | 0.38 |
December | 0.757660E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120799E+11 | 0.00 | 0.00 | 0.38 |
Annual Sum or Average | 0.212590E+11 | 0.310912E+10 | 0.00 | 33656454.57 | 68991997.35 | 0.555947E+11 | 0.192067E+11 | 0.00 | 0.56 |
Minimum of Months | 0.108932E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.391091E+10 | 0.125869E+10 | 0.00 | 8460794.45 | 22512644.73 | 0.152604E+11 | 0.411064E+10 | 0.00 | 0.90 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 81251953.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.764342E+10 | 0.00 | 0.00 | 0.38 |
February | 0.490045E+09 | 0.00 | 0.00 | 1920.77 | 0.00 | 0.482983E+10 | 9989420.96 | 0.00 | 0.38 |
March | 0.121146E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.385772E+10 | 0.00 | 0.00 | 0.39 |
April | 0.166942E+10 | 0.00 | 0.00 | 204716.79 | 0.00 | 0.147898E+10 | 0.306175E+09 | 0.00 | 0.44 |
May | 0.132263E+10 | 17228968.37 | 0.00 | 1295753.11 | 2044248.95 | 0.956786E+09 | 0.103102E+10 | 0.00 | 0.62 |
June | 0.378905E+09 | 0.260158E+09 | 0.00 | 3354487.33 | 113755.52 | 6987409.90 | 0.210162E+10 | 0.00 | 0.89 |
July | 66303172.85 | 0.636681E+09 | 0.00 | 3418443.93 | 10311852.83 | 0.00 | 0.129685E+10 | 0.00 | 0.80 |
August | 0.194598E+09 | 0.446820E+09 | 0.00 | 4168043.01 | 11698463.98 | 0.00 | 0.202699E+10 | 0.00 | 0.95 |
September | 0.824452E+09 | 0.209682E+09 | 0.00 | 2822435.62 | 11448628.74 | 0.210473E+09 | 0.191578E+10 | 0.00 | 0.80 |
October | 0.184696E+10 | 1532145.34 | 0.00 | 1047425.17 | 0.00 | 0.722313E+09 | 0.107597E+10 | 0.00 | 0.55 |
November | 0.141482E+10 | 0.00 | 0.00 | 5746.84 | 0.00 | 0.294202E+10 | 19925720.32 | 0.00 | 0.38 |
December | 0.292645E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.611758E+10 | 0.00 | 0.00 | 0.38 |
Annual Sum or Average | 0.979348E+10 | 0.157210E+10 | 0.00 | 16318972.57 | 35616950.01 | 0.287661E+11 | 0.978432E+10 | 0.00 | 0.58 |
Minimum of Months | 66303172.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.184696E+10 | 0.636681E+09 | 0.00 | 4168043.01 | 11698463.98 | 0.764342E+10 | 0.210162E+10 | 0.00 | 0.95 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 54393780.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.767028E+10 | 0.00 | 0.00 | 0.38 |
February | 0.446387E+09 | 0.00 | 0.00 | 1000.15 | 0.00 | 0.487294E+10 | 7242156.35 | 0.00 | 0.38 |
March | 0.109946E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.396828E+10 | 0.00 | 0.00 | 0.39 |
April | 0.161550E+10 | 0.00 | 0.00 | 178056.16 | 0.00 | 0.153290E+10 | 0.281291E+09 | 0.00 | 0.43 |
May | 0.129904E+10 | 17221554.81 | 0.00 | 1202284.85 | 2157035.30 | 0.100423E+10 | 0.959839E+09 | 0.00 | 0.61 |
June | 0.393723E+09 | 0.259515E+09 | 0.00 | 3206639.58 | 115308.45 | 8905523.45 | 0.202846E+10 | 0.00 | 0.88 |
July | 73811801.27 | 0.636076E+09 | 0.00 | 3305322.47 | 10305953.40 | 0.00 | 0.126862E+10 | 0.00 | 0.80 |
August | 0.202913E+09 | 0.446471E+09 | 0.00 | 4041225.99 | 12185577.53 | 0.00 | 0.198596E+10 | 0.00 | 0.94 |
September | 0.844316E+09 | 0.209128E+09 | 0.00 | 2709095.43 | 11511552.55 | 0.214548E+09 | 0.185088E+10 | 0.00 | 0.79 |
October | 0.184863E+10 | 1531485.15 | 0.00 | 959535.68 | 0.00 | 0.751071E+09 | 0.100279E+10 | 0.00 | 0.55 |
November | 0.135171E+10 | 0.00 | 0.00 | 3495.82 | 0.00 | 0.300197E+10 | 16284035.86 | 0.00 | 0.38 |
December | 0.255064E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.615517E+10 | 0.00 | 0.00 | 0.38 |
Annual Sum or Average | 0.948495E+10 | 0.156994E+10 | 0.00 | 15606656.13 | 36275427.23 | 0.291803E+11 | 0.940137E+10 | 0.00 | 0.58 |
Minimum of Months | 54393780.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.184863E+10 | 0.636076E+09 | 0.00 | 4041225.99 | 12185577.53 | 0.767028E+10 | 0.202846E+10 | 0.00 | 0.94 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 17433352.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.770723E+10 | 0.00 | 0.00 | 0.38 |
February | 0.359950E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.495969E+10 | 0.00 | 0.00 | 0.38 |
March | 0.878154E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.418657E+10 | 0.00 | 0.00 | 0.39 |
April | 0.142720E+10 | 0.00 | 0.00 | 118617.74 | 0.00 | 0.172671E+10 | 0.221071E+09 | 0.00 | 0.42 |
May | 0.118712E+10 | 17203261.18 | 0.00 | 988567.47 | 2483206.47 | 0.117279E+10 | 0.793595E+09 | 0.00 | 0.59 |
June | 0.427072E+09 | 0.258338E+09 | 0.00 | 2803675.14 | 116874.05 | 35119273.82 | 0.182633E+10 | 0.00 | 0.85 |
July | 96445941.63 | 0.634882E+09 | 0.00 | 3035373.20 | 10415762.93 | 0.00 | 0.119583E+10 | 0.00 | 0.79 |
August | 0.231896E+09 | 0.446460E+09 | 0.00 | 3753083.21 | 12257510.34 | 0.00 | 0.188498E+10 | 0.00 | 0.93 |
September | 0.858251E+09 | 0.208242E+09 | 0.00 | 2457084.51 | 11599055.39 | 0.259886E+09 | 0.170499E+10 | 0.00 | 0.78 |
October | 0.185529E+10 | 1536930.40 | 0.00 | 781857.48 | 0.00 | 0.813074E+09 | 0.846359E+09 | 0.00 | 0.53 |
November | 0.117689E+10 | 0.00 | 0.00 | 62.66 | 0.00 | 0.317592E+10 | 3309445.44 | 0.00 | 0.38 |
December | 0.143043E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.626716E+10 | 0.00 | 0.00 | 0.38 |
Annual Sum or Average | 0.865875E+10 | 0.156666E+10 | 0.00 | 13938321.41 | 36872409.18 | 0.303042E+11 | 0.847647E+10 | 0.00 | 0.57 |
Minimum of Months | 17433352.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.185529E+10 | 0.634882E+09 | 0.00 | 3753083.21 | 12257510.34 | 0.770723E+10 | 0.188498E+10 | 0.00 | 0.93 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:21:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 1561267.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.771042E+10 | 0.00 | 0.00 | 0.38 |
February | 0.164665E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.513432E+10 | 0.00 | 0.00 | 0.38 |
March | 0.115045E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.492741E+10 | 0.00 | 0.00 | 0.39 |
April | 0.720357E+09 | 0.00 | 0.00 | 22273.49 | 0.00 | 0.245078E+10 | 91594318.16 | 0.00 | 0.41 |
May | 0.960857E+09 | 17542056.95 | 0.00 | 605354.63 | 3046682.93 | 0.148287E+10 | 0.522610E+09 | 0.00 | 0.56 |
June | 0.530696E+09 | 0.259029E+09 | 0.00 | 2016889.96 | 124556.50 | 0.102798E+09 | 0.139780E+10 | 0.00 | 0.82 |
July | 0.147705E+09 | 0.635038E+09 | 0.00 | 2544834.05 | 10549650.95 | 0.00 | 0.108206E+10 | 0.00 | 0.80 |
August | 0.237062E+09 | 0.448734E+09 | 0.00 | 3171327.22 | 11762489.76 | 13202814.94 | 0.175542E+10 | 0.00 | 0.94 |
September | 0.824052E+09 | 0.206239E+09 | 0.00 | 1950518.39 | 11497783.71 | 0.358211E+09 | 0.148076E+10 | 0.00 | 0.77 |
October | 0.156683E+10 | 1619730.03 | 0.00 | 516265.61 | 0.00 | 0.115343E+10 | 0.641789E+09 | 0.00 | 0.52 |
November | 0.619158E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.370403E+10 | 0.00 | 0.00 | 0.38 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.640016E+10 | 0.00 | 0.00 | 0.38 |
Annual Sum or Average | 0.588799E+10 | 0.156820E+10 | 0.00 | 10827463.35 | 36981163.85 | 0.334376E+11 | 0.697204E+10 | 0.00 | 0.56 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.156683E+10 | 0.635038E+09 | 0.00 | 3171327.22 | 11762489.76 | 0.771042E+10 | 0.175542E+10 | 0.00 | 0.94 |