Program Version:EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:21
Tabular Output Report in Format: HTML
Building: RetailStripmall
Environment: RUNPERIOD 1 ** New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820
Simulation Timestamp: 2020-06-03 19:21:12
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2020-06-03 19:21:12
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1396.40 | 668.03 | 668.03 |
Net Site Energy | 1396.40 | 668.03 | 668.03 |
Total Source Energy | 4418.01 | 2113.56 | 2113.56 |
Net Source Energy | 4418.01 | 2113.56 | 2113.56 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 2090.32 |
Net Conditioned Building Area | 2090.32 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 2.11 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 480.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 502.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 91.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 128.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 133.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 58.82 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1394.29 | 2.11 | 0.00 | 0.00 | 0.00 | 87.30 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 2.11 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 480.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 502.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 91.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 128.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 133.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 58.82 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 283.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 321.73 | 1.01 | 0.00 | 0.00 | 0.00 | 0.04 |
Other | 61.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 667.02 | 1.01 | 0.00 | 0.00 | 0.00 | 0.04 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 283.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 321.73 | 1.01 | 0.00 | 0.00 | 0.00 | 0.04 |
Other | 61.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 667.02 | 1.01 | 0.00 | 0.00 | 0.00 | 0.04 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1394.291 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1394.291 | 100.00 |
Total On-Site and Utility Electric Sources | 1394.291 | 100.00 |
Total Electricity End Uses | 1394.291 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 87.30 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 87.30 | 100.00 |
Total Water End Uses | 87.30 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 37.67 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 1311.33 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Meter |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2015
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Meter |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTRIPMALL
| Meter |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 1B
| Meter |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY IND_DELHI_NEWDELHI
| Meter |ZoneCoolingSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ZoneHeatingSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ZoneElectricSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |SpaceGainsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |PeakSpaceGainsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |SpaceGainComponentsAtCoolingPeakMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ComfortReportSimple55Monthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |OccupantComfortDataSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |DXReportMonthly
| PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL |WindowReportMonthly
| LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR |WindowEnergyReportMonthly
| LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR |WindowZoneSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |WindowEnergyZoneSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| GAS TANK1 | GAS TANK2 | GAS TANK3 | GAS TANK4 | GAS TANK5 | GAS TANK6 | GAS TANK7 |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC_1:1_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_2:2_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_3:3_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_4:4_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_5:5_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_6:6_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_7:7_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_8:8_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_9:9_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_10:10_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL |FanReportMonthly
| PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN |ZoneTemperatureOscillationReportMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |MechanicalVentilationLoadsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2020-06-03 19:21:12
GeneralValue | |
Program Version and Build | EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:21 |
RunPeriod | RUNPERIOD 1 |
Weather File | New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820 |
Latitude [deg] | 28.58 |
Longitude [deg] | 77.20 |
Elevation [m] | 216.00 |
Time Zone | 5.50 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Above Ground Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Window Opening Area [m2] | 124.29 | 0.00 | 0.00 | 124.29 | 0.00 |
Gross Window-Wall Ratio [%] | 10.50 | 0.00 | 0.00 | 26.24 | 0.00 |
Above Ground Window-Wall Ratio [%] | 10.50 | 0.00 | 0.00 | 26.24 | 0.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Above Ground Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Window Opening Area [m2] | 124.29 | 0.00 | 0.00 | 124.29 | 0.00 |
Gross Window-Wall Ratio [%] | 10.50 | 0.00 | 0.00 | 26.24 | 0.00 |
Above Ground Window-Wall Ratio [%] | 10.50 | 0.00 | 0.00 | 26.24 | 0.00 |
Total | |
Gross Roof Area [m2] | 2090.32 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
LGSTORE1 | 348.39 | Yes | Yes | 1805.20 | 1.00 | 276.30 | 0.00 | 20.75 | 20.75 | 18.3665 | 11.61 | 4.3000 |
SMSTORE1 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.37 | 10.37 | 19.8089 | 11.61 | 4.3000 |
SMSTORE2 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.35 | 10.35 | 17.6561 | 11.61 | 4.3000 |
SMSTORE3 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.35 | 10.35 | 17.6561 | 11.61 | 4.3000 |
SMSTORE4 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.35 | 10.35 | 17.6561 | 11.61 | 4.3000 |
LGSTORE2 | 348.39 | Yes | Yes | 1805.20 | 1.00 | 157.89 | 0.00 | 20.70 | 20.70 | 13.1675 | 11.61 | 4.3000 |
SMSTORE5 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.35 | 10.35 | 13.1675 | 11.61 | 4.3000 |
SMSTORE6 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.35 | 10.35 | 13.1675 | 11.61 | 4.3000 |
SMSTORE7 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.35 | 10.35 | 13.1675 | 11.61 | 4.3000 |
SMSTORE8 | 174.19 | Yes | Yes | 902.60 | 1.00 | 197.36 | 0.00 | 10.35 | 10.35 | 13.1675 | 11.61 | 4.3000 |
Total | 2090.32 | 10831.20 | 1184.15 | 0.00 | 124.29 | 124.29 | 15.7096 | 11.61 | 4.3000 | |||
Conditioned Total | 2090.32 | 10831.20 | 1184.15 | 0.00 | 124.29 | 124.29 | 15.7096 | 11.61 | 4.3000 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:21:12
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 22-JUN-15:09 | 02-JAN-09:09 | - | - | - | 06-JAN-13:09 |
Heating | 0.00 | 102906.53 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 83701.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 31196.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 8089.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 15573.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 5420.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 143981.46 | 102906.53 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 102906.53 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 83701.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 31196.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 8089.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 15573.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 5420.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:21:12
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 2.28 | 0.00 | 0.00 | 0.00 |
Cooling | 1520.58 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1589.92 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 288.26 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 407.66 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 423.02 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 186.28 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 4415.72 | 2.28 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 1.09 | 0.00 | 0.00 | 0.00 |
Cooling | 727.44 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 760.61 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 137.90 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 195.02 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 202.37 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 89.11 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2112.46 | 1.09 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 1.09 | 0.00 | 0.00 | 0.00 |
Cooling | 727.44 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 760.61 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 137.90 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 195.02 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 202.37 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 89.11 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2112.46 | 1.09 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:21:12
AirTerminal:SingleDuct:UncontrolledDesign Size Maximum Air Flow Rate [m3/s] | |
LGSTORE1 DIRECT AIR | 2.51 |
SMSTORE1 DIRECT AIR | 1.32 |
SMSTORE2 DIRECT AIR | 1.31 |
SMSTORE3 DIRECT AIR | 1.32 |
SMSTORE4 DIRECT AIR | 1.31 |
LGSTORE2 DIRECT AIR | 2.38 |
SMSTORE5 DIRECT AIR | 1.26 |
SMSTORE6 DIRECT AIR | 1.26 |
SMSTORE7 DIRECT AIR | 1.26 |
SMSTORE8 DIRECT AIR | 1.36 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC_1:1 | 2.51 | 2.51 | 2.51 | 2.51 | 2.51 | 2.51 | 1.00 | 1.00 | 2.51 |
PSZ-AC_2:2 | 1.32 | 1.32 | 1.32 | 1.32 | 1.32 | 1.32 | 1.00 | 1.00 | 1.32 |
PSZ-AC_3:3 | 1.31 | 1.31 | 1.31 | 1.31 | 1.31 | 1.31 | 1.00 | 1.00 | 1.31 |
PSZ-AC_4:4 | 1.32 | 1.32 | 1.32 | 1.32 | 1.32 | 1.32 | 1.00 | 1.00 | 1.32 |
PSZ-AC_5:5 | 1.31 | 1.31 | 1.31 | 1.31 | 1.31 | 1.31 | 1.00 | 1.00 | 1.31 |
PSZ-AC_6:6 | 2.38 | 2.38 | 2.38 | 2.38 | 2.38 | 2.38 | 1.00 | 1.00 | 2.38 |
PSZ-AC_7:7 | 1.26 | 1.26 | 1.26 | 1.26 | 1.26 | 1.26 | 1.00 | 1.00 | 1.26 |
PSZ-AC_8:8 | 1.26 | 1.26 | 1.26 | 1.26 | 1.26 | 1.26 | 1.00 | 1.00 | 1.26 |
PSZ-AC_9:9 | 1.26 | 1.26 | 1.26 | 1.26 | 1.26 | 1.26 | 1.00 | 1.00 | 1.26 |
PSZ-AC_10:10 | 1.36 | 1.36 | 1.36 | 1.36 | 1.36 | 1.36 | 1.00 | 1.00 | 1.36 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC_1:1_OA_CONTROLLER | 2.51 | 0.411453 |
PSZ-AC_2:2_OA_CONTROLLER | 1.32 | 0.205727 |
PSZ-AC_3:3_OA_CONTROLLER | 1.31 | 0.205727 |
PSZ-AC_4:4_OA_CONTROLLER | 1.32 | 0.205727 |
PSZ-AC_5:5_OA_CONTROLLER | 1.31 | 0.205727 |
PSZ-AC_6:6_OA_CONTROLLER | 2.38 | 0.411453 |
PSZ-AC_7:7_OA_CONTROLLER | 1.26 | 0.205727 |
PSZ-AC_8:8_OA_CONTROLLER | 1.26 | 0.205727 |
PSZ-AC_9:9_OA_CONTROLLER | 1.26 | 0.205727 |
PSZ-AC_10:10_OA_CONTROLLER | 1.36 | 0.205727 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC_1:1_UNITARY_PACKAGE_DX | 2.51 | 2.51 | 2.51 | 1.66 | 51734.55 | 63210.34 | 40.00 | 1.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_DX | 1.32 | 1.32 | 1.32 | 0.872302 | 26997.92 | 33042.67 | 40.00 | 1.00 |
PSZ-AC_3:3_UNITARY_PACKAGE_DX | 1.31 | 1.31 | 1.31 | 0.867651 | 26873.08 | 32885.67 | 40.00 | 1.00 |
PSZ-AC_4:4_UNITARY_PACKAGE_DX | 1.32 | 1.32 | 1.32 | 0.869585 | 26925.41 | 32950.97 | 40.00 | 1.00 |
PSZ-AC_5:5_UNITARY_PACKAGE_DX | 1.31 | 1.31 | 1.31 | 0.866535 | 26843.13 | 32847.98 | 40.00 | 1.00 |
PSZ-AC_6:6_UNITARY_PACKAGE_DX | 2.38 | 2.38 | 2.38 | 1.57 | 49294.01 | 60153.02 | 40.00 | 1.00 |
PSZ-AC_7:7_UNITARY_PACKAGE_DX | 1.26 | 1.26 | 1.26 | 0.832774 | 25933.27 | 31708.20 | 40.00 | 1.00 |
PSZ-AC_8:8_UNITARY_PACKAGE_DX | 1.26 | 1.26 | 1.26 | 0.829299 | 25839.50 | 31590.89 | 40.00 | 1.00 |
PSZ-AC_9:9_UNITARY_PACKAGE_DX | 1.26 | 1.26 | 1.26 | 0.829855 | 25854.61 | 31609.66 | 40.00 | 1.00 |
PSZ-AC_10:10_UNITARY_PACKAGE_DX | 1.36 | 1.36 | 1.36 | 0.896316 | 27549.62 | 33853.41 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | Speed 2 Design Size Rated Total Cooling Capacity [W] | Speed 2 User-Specified Rated Total Cooling Capacity [W] | Speed 1 Design Size Rated Total Cooling Capacity [W] | Speed 1 User-Specified Rated Total Cooling Capacity [W] | Speed 2 Design Size Rated Sensible Heat Ratio | Speed 2 User-Specified Rated Sensible Heat Ratio | Speed 1 Design Size Rated Sensible Heat Ratio | Speed 1 User-Specified Rated Sensible Heat Ratio | |
PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | 2.51 | 1.26 | 1.68 | 42063.50 | 51734.55 | 25867.28 | 25867.28 | 0.726782 | 0.726780 | 0.726780 | 0.726780 |
PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | 1.32 | 0.660835 | 0.881113 | 21878.33 | 26997.92 | 13498.96 | 13498.96 | 0.728937 | 0.728940 | 0.728940 | 0.728940 |
PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | 1.31 | 0.657310 | 0.876413 | 21794.83 | 26873.08 | 13436.54 | 13436.54 | 0.728725 | 0.728730 | 0.728730 | 0.728730 |
PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | 1.32 | 0.658775 | 0.878367 | 21829.11 | 26925.41 | 13462.70 | 13462.70 | 0.728808 | 0.728810 | 0.728810 | 0.728810 |
PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | 1.31 | 0.656465 | 0.875287 | 21775.59 | 26843.13 | 13421.57 | 13421.57 | 0.728674 | 0.728670 | 0.728670 | 0.728670 |
PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | 2.38 | 1.19 | 1.58 | 40461.83 | 49294.01 | 24647.01 | 24647.01 | 0.724486 | 0.724490 | 0.724490 | 0.724490 |
PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | 1.26 | 0.630890 | 0.841187 | 21183.34 | 25933.27 | 12966.64 | 12966.64 | 0.727114 | 0.727110 | 0.727110 | 0.727110 |
PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | 1.26 | 0.628255 | 0.837673 | 21121.92 | 25839.50 | 12919.75 | 12919.75 | 0.726947 | 0.726950 | 0.726950 | 0.726950 |
PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | 1.26 | 0.628680 | 0.838240 | 21132.07 | 25854.61 | 12927.31 | 12927.31 | 0.726974 | 0.726970 | 0.726970 | 0.726970 |
PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | 1.36 | 0.679025 | 0.905367 | 22480.55 | 27549.62 | 13774.81 | 13774.81 | 0.731007 | 0.731010 | 0.731010 | 0.731010 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | 2.51 | 2690.45 |
PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | 1.32 | 1463.30 |
PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | 1.31 | 1455.50 |
PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | 1.32 | 1458.74 |
PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | 1.31 | 1453.62 |
PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | 2.38 | 2543.62 |
PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | 1.26 | 1396.99 |
PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | 1.26 | 1391.16 |
PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | 1.26 | 1392.09 |
PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | 1.36 | 1503.58 |
Design Size Nominal Capacity [W] | |
PSZ-AC_1:1_UNITARY_PACKAGE_HEATCOIL | 63210.34 |
PSZ-AC_2:2_UNITARY_PACKAGE_HEATCOIL | 33042.67 |
PSZ-AC_3:3_UNITARY_PACKAGE_HEATCOIL | 32885.67 |
PSZ-AC_4:4_UNITARY_PACKAGE_HEATCOIL | 32950.97 |
PSZ-AC_5:5_UNITARY_PACKAGE_HEATCOIL | 32847.98 |
PSZ-AC_6:6_UNITARY_PACKAGE_HEATCOIL | 60153.02 |
PSZ-AC_7:7_UNITARY_PACKAGE_HEATCOIL | 31708.20 |
PSZ-AC_8:8_UNITARY_PACKAGE_HEATCOIL | 31590.89 |
PSZ-AC_9:9_UNITARY_PACKAGE_HEATCOIL | 31609.66 |
PSZ-AC_10:10_UNITARY_PACKAGE_HEATCOIL | 33853.41 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:21:12
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
LGSTORE1_WALL_3 | LGSTORE1_WALL_3_DOOR_1 | LGSTORE1_WALL_3_DOOR_2 | |
LGSTORE1_WALL_1 | LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | |
SMSTORE1_WALL_1 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | |
SMSTORE1_WALL_3 | SMSTORE1_WALL_3_DOOR | |
SMSTORE2_WALL_1 | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | |
SMSTORE2_WALL_3 | SMSTORE2_WALL_3_DOOR | |
SMSTORE3_WALL_1 | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | |
SMSTORE3_WALL_3 | SMSTORE3_WALL_3_DOOR | |
SMSTORE4_WALL_1 | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | |
SMSTORE4_WALL_3 | SMSTORE4_WALL_3_DOOR | |
LGSTORE2_WALL_3 | LGSTORE2_WALL_3_DOOR_1 | LGSTORE2_WALL_3_DOOR_2 | |
LGSTORE2_WALL_1 | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | |
SMSTORE5_WALL_1 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | |
SMSTORE5_WALL_3 | SMSTORE5_WALL_3_DOOR | |
SMSTORE6_WALL_1 | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | |
SMSTORE6_WALL_3 | SMSTORE6_WALL_3_DOOR | |
SMSTORE7_WALL_1 | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | |
SMSTORE7_WALL_3 | SMSTORE7_WALL_3_DOOR | |
SMSTORE8_WALL_1 | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR | |
SMSTORE8_WALL_3 | SMSTORE8_WALL_3_DOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2020-06-03 19:21:12
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2020-06-03 19:21:12
VersionVersion ID | |
1 | 9.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 25.10 | 19.60 | 14.50 | 13.40 | 17.00 | 22.40 | 29.10 | 33.00 | 33.60 | 31.70 | 30.00 | 28.70 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820 | 28.58 | 77.20 | 5.50 | 216.00 | 98757 | 1.1738 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 24.84 | 20.20 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RetailStripmall | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 10 | 118 | 48 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | LGSTORE1 | 0.0 | 0.00 | 0.00 | 0.00 | 7.62 | 11.43 | 2.59 | 1 | 1 | 1 | 0.00 | 15.24 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 1805.20 | TARP | TARP | 348.39 | 276.30 | 247.76 | 20.75 | 6 | 8 | 0 | Yes |
2 | SMSTORE1 | 0.0 | 0.00 | 0.00 | 0.00 | 19.05 | 11.43 | 2.59 | 1 | 1 | 1 | 15.24 | 22.86 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.67 | 10.37 | 6 | 4 | 0 | Yes |
3 | SMSTORE2 | 0.0 | 0.00 | 0.00 | 0.00 | 26.67 | 11.43 | 2.59 | 1 | 1 | 1 | 22.86 | 30.48 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.35 | 6 | 4 | 0 | Yes |
4 | SMSTORE3 | 0.0 | 0.00 | 0.00 | 0.00 | 34.29 | 11.43 | 2.59 | 1 | 1 | 1 | 30.48 | 38.10 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.35 | 6 | 4 | 0 | Yes |
5 | SMSTORE4 | 0.0 | 0.00 | 0.00 | 0.00 | 41.91 | 11.43 | 2.59 | 1 | 1 | 1 | 38.10 | 45.72 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.35 | 6 | 4 | 0 | Yes |
6 | LGSTORE2 | 0.0 | 0.00 | 0.00 | 0.00 | 53.34 | 11.43 | 2.59 | 1 | 1 | 1 | 45.72 | 60.96 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 1805.20 | TARP | TARP | 348.39 | 157.89 | 129.43 | 20.70 | 6 | 8 | 0 | Yes |
7 | SMSTORE5 | 0.0 | 0.00 | 0.00 | 0.00 | 64.77 | 11.43 | 2.59 | 1 | 1 | 1 | 60.96 | 68.58 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.35 | 6 | 4 | 0 | Yes |
8 | SMSTORE6 | 0.0 | 0.00 | 0.00 | 0.00 | 72.39 | 11.43 | 2.59 | 1 | 1 | 1 | 68.58 | 76.20 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.35 | 6 | 4 | 0 | Yes |
9 | SMSTORE7 | 0.0 | 0.00 | 0.00 | 0.00 | 80.01 | 11.43 | 2.59 | 1 | 1 | 1 | 76.20 | 83.82 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.35 | 6 | 4 | 0 | Yes |
10 | SMSTORE8 | 0.0 | 0.00 | 0.00 | 0.00 | 87.63 | 11.43 | 2.59 | 1 | 1 | 1 | 83.82 | 91.44 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 197.36 | 183.13 | 10.35 | 6 | 4 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | LGSTORE1 | 348.39 | 30.0 | 11.614 | 8.610E-002 | 18.366 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 22.666 | No |
2 | SMSTORE1 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 19.809 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 24.109 | No |
3 | SMSTORE2 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 17.656 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 21.956 | No |
4 | SMSTORE3 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 17.656 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 21.956 | No |
5 | SMSTORE4 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 17.656 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 21.956 | No |
6 | LGSTORE2 | 348.39 | 30.0 | 11.614 | 8.610E-002 | 13.168 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 17.468 | No |
7 | SMSTORE5 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 13.168 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 17.468 | No |
8 | SMSTORE6 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 13.168 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 17.468 | No |
9 | SMSTORE7 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 13.168 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 17.468 | No |
10 | SMSTORE8 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 13.168 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 17.468 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | |
1 | LGSTORE1 | TYPE1_OCC_SCH | LGSTORE1 | 348.39 | 30.0 | 30.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 30 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
2 | SMSTORE1 | TYPE1_OCC_SCH | SMSTORE1 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
3 | SMSTORE2 | TYPE2_OCC_SCH | SMSTORE2 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
4 | SMSTORE3 | TYPE2_OCC_SCH | SMSTORE3 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
5 | SMSTORE4 | TYPE2_OCC_SCH | SMSTORE4 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
6 | LGSTORE2 | TYPE3_OCC_SCH | LGSTORE2 | 348.39 | 30.0 | 30.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 30 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
7 | SMSTORE5 | TYPE3_OCC_SCH | SMSTORE5 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
8 | SMSTORE6 | TYPE3_OCC_SCH | SMSTORE6 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
9 | SMSTORE7 | TYPE3_OCC_SCH | SMSTORE7 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
10 | SMSTORE8 | TYPE3_OCC_SCH | SMSTORE8 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | LGSTORE1_LIGHTS | TYPE1_LIGHT_SCH | LGSTORE1 | 348.39 | 30.0 | 4587.386 | 13.168 | 152.933 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 4587.386 |
2 | LGSTORE1_LIGHTS_ALLOWANCE | TYPE1_LIGHT_SCH | LGSTORE1 | 348.39 | 30.0 | 1811.251 | 5.199 | 60.383 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1811.251 |
3 | SMSTORE1_LIGHTS | TYPE1_LIGHT_SCH | SMSTORE1 | 174.19 | 15.0 | 2293.693 | 13.168 | 152.933 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2293.693 |
4 | SMSTORE1_LIGHTS_ALLOWANCE | TYPE1_LIGHT_SCH | SMSTORE1 | 174.19 | 15.0 | 1156.875 | 6.641 | 77.135 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1156.875 |
5 | SMSTORE2_LIGHTS | TYPE2_LIGHT_SCH | SMSTORE2 | 174.19 | 15.0 | 2293.693 | 13.168 | 152.933 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2293.693 |
6 | SMSTORE2_LIGHTS_ALLOWANCE | TYPE2_LIGHT_SCH | SMSTORE2 | 174.19 | 15.0 | 781.875 | 4.489 | 52.132 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 781.875 |
7 | SMSTORE3_LIGHTS | TYPE2_LIGHT_SCH | SMSTORE3 | 174.19 | 15.0 | 2293.693 | 13.168 | 152.933 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2293.693 |
8 | SMSTORE3_LIGHTS_ALLOWANCE | TYPE2_LIGHT_SCH | SMSTORE3 | 174.19 | 15.0 | 781.875 | 4.489 | 52.132 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 781.875 |
9 | SMSTORE4_LIGHTS | TYPE2_LIGHT_SCH | SMSTORE4 | 174.19 | 15.0 | 2293.693 | 13.168 | 152.933 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2293.693 |
10 | SMSTORE4_LIGHTS_ALLOWANCE | TYPE2_LIGHT_SCH | SMSTORE4 | 174.19 | 15.0 | 781.875 | 4.489 | 52.132 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 781.875 |
11 | LGSTORE2_LIGHTS | TYPE3_LIGHT_SCH | LGSTORE2 | 348.39 | 30.0 | 4587.386 | 13.168 | 152.933 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 4587.386 |
12 | LGSTORE2_LIGHTS_ALLOWANCE | TYPE3_LIGHT_SCH | LGSTORE2 | 348.39 | 30.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
13 | SMSTORE5_LIGHTS | TYPE3_LIGHT_SCH | SMSTORE5 | 174.19 | 15.0 | 2293.693 | 13.168 | 152.933 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2293.693 |
14 | SMSTORE5_LIGHTS_ALLOWANCE | TYPE3_LIGHT_SCH | SMSTORE5 | 174.19 | 15.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
15 | SMSTORE6_LIGHTS | TYPE3_LIGHT_SCH | SMSTORE6 | 174.19 | 15.0 | 2293.693 | 13.168 | 152.933 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2293.693 |
16 | SMSTORE6_LIGHTS_ALLOWANCE | TYPE3_LIGHT_SCH | SMSTORE6 | 174.19 | 15.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
17 | SMSTORE7_LIGHTS | TYPE3_LIGHT_SCH | SMSTORE7 | 174.19 | 15.0 | 2293.693 | 13.168 | 152.933 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2293.693 |
18 | SMSTORE7_LIGHTS_ALLOWANCE | TYPE3_LIGHT_SCH | SMSTORE7 | 174.19 | 15.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
19 | SMSTORE8_LIGHTS | TYPE3_LIGHT_SCH | SMSTORE8 | 174.19 | 15.0 | 2293.693 | 13.168 | 152.933 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2293.693 |
20 | SMSTORE8_LIGHTS_ALLOWANCE | TYPE3_LIGHT_SCH | SMSTORE8 | 174.19 | 15.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | LGSTORE1_MISCPLUG_EQUIP | TYPE1_EQUIP_SCH | LGSTORE1 | 348.39 | 30.0 | 1498.062 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1498.062 |
2 | SMSTORE1_MISCPLUG_EQUIP | TYPE1_EQUIP_SCH | SMSTORE1 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
3 | SMSTORE2_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE2 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
4 | SMSTORE3_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE3 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
5 | SMSTORE4_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE4 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
6 | LGSTORE2_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | LGSTORE2 | 348.39 | 30.0 | 1498.062 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1498.062 |
7 | SMSTORE5_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE5 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
8 | SMSTORE6_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE6 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
9 | SMSTORE7_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE7 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
10 | SMSTORE8_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE8 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.464 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.2832 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
5 | NONRES_EXT_WALL | 20 | 4 | 7 | 0.167 | 0.4678 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
6 | LGSTORE1_FLOOR_FFACTOR | 30 | 2 | 7 | 0.167 | 0.1995 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
7 | SMSTORE1_FLOOR_FFACTOR | 31 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
8 | SMSTORE2_FLOOR_FFACTOR | 32 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | SMSTORE3_FLOOR_FFACTOR | 33 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
10 | SMSTORE4_FLOOR_FFACTOR | 34 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
11 | LGSTORE2_FLOOR_FFACTOR | 35 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | SMSTORE5_FLOOR_FFACTOR | 36 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | SMSTORE6_FLOOR_FFACTOR | 37 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | SMSTORE7_FLOOR_FFACTOR | 38 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | SMSTORE8_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.2888 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2887 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
6 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 3.472 |
7 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
8 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
9 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
10 | NONRES_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.903 |
11 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
12 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.937 |
13 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
14 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
15 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
16 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
17 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
18 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
19 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
20 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
21 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
22 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
23 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
24 | ~FC_Insulation_7 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_8 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_9 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
30 | ~FC_Insulation_10 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.386 |
31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.4637443 | 3.4637443 | 3.4637443 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
14 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
15 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
16 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
17 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
18 | 3 | -0.61927053E-06 | 0.12767249E-08 | -0.37968499E-05 | 0.16832131E-17 |
19 | 2 | 0.77611055 | 0.17315568E-02 | 1.0534842 | -0.72792597E-06 |
20 | 1 | -21.915918 | 0.11588205 | -6.3286394 | 0.20197014 |
21 | 0 | 21.365777 | 0.10835518 | 5.5011278 | |
22 | 7 | -0.37383775E-12 | 0.81582362E-15 | -0.12542534E-12 | 0.11541335E-15 |
23 | 6 | 0.32294454E-07 | 0.13597119E-09 | 0.73677206E-08 | -0.15476624E-12 |
24 | 5 | -0.20833553E-03 | 0.11386595E-05 | -0.10688959E-03 | 0.72710034E-08 |
25 | 4 | 0.31322919 | 0.54351077E-03 | 0.10727732 | -0.36571185E-04 |
26 | 3 | -7.6832781 | 0.16549290E-01 | -2.4626776 | 0.31053958E-01 |
27 | 2 | 42.245606 | 0.57933024E-01 | 15.771342 | -0.34865193 |
28 | 1 | -81.598353 | 0.25789083E-01 | -29.595166 | 1.1010509 |
29 | 0 | 46.824332 | 0.51189598E-03 | 16.280659 | |
30 | 7 | -0.21163652E-08 | -0.68723841E-15 | 0.43910983E-14 | -0.57684426E-16 |
31 | 6 | 0.56109385E-05 | 0.38186281E-08 | 0.31898696E-02 | -0.26759299E-04 |
32 | 5 | -0.40164657E-03 | 0.22608617E-05 | -0.22372456 | 0.19561502E-02 |
33 | 4 | 0.92272104E-02 | 0.10289840E-03 | 4.8295456 | -0.45264980E-01 |
34 | 3 | -0.80993241E-01 | 0.81813938E-03 | -38.021416 | 0.39865375 |
35 | 2 | 0.28754352 | 0.13608947E-02 | 116.48395 | -1.4179393 |
36 | 1 | -0.41499682 | 0.41453381E-03 | -143.90731 | 2.0490399 |
37 | 0 | 0.20232414 | 0.10048102E-04 | 60.838472 | |
38 | 7 | -0.37862368E-08 | -0.38757603E-14 | 0.11479940E-14 | -0.41635801E-16 |
39 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
40 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
41 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
42 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
43 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
44 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
45 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
46 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479937E-14 | -0.41635796E-16 |
47 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
48 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
49 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
50 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
51 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
52 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
53 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
54 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479940E-14 | -0.41635801E-16 |
55 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
56 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
57 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
58 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
59 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
60 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
61 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
62 | 7 | -0.37862368E-08 | -0.38757603E-14 | 0.11479940E-14 | -0.41635801E-16 |
63 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
64 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
65 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
66 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
67 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
68 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
69 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
70 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479937E-14 | -0.41635796E-16 |
71 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
72 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
73 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
74 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
75 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
76 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
77 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
78 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479937E-14 | -0.41635796E-16 |
79 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
80 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
81 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
82 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
83 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
84 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
85 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
86 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479940E-14 | -0.41635801E-16 |
87 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
88 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
89 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
90 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
91 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
92 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
93 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
94 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479936E-14 | -0.41635794E-16 |
95 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
96 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
97 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
98 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
99 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
100 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
101 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
102 | 7 | -0.14484255E-08 | -0.22640907E-15 | 0.11860658E-13 | -0.17473455E-15 |
103 | 6 | 0.80640390E-05 | 0.55493782E-08 | 0.31828288E-02 | -0.26700235E-04 |
104 | 5 | -0.58275339E-03 | 0.32892043E-05 | -0.22332434 | 0.19526176E-02 |
105 | 4 | 0.13421983E-01 | 0.14977251E-03 | 4.8228790 | -0.45200897E-01 |
106 | 3 | -0.11791368 | 0.11914425E-02 | -37.983753 | 0.39823745 |
107 | 2 | 0.41875064 | 0.19825898E-02 | 116.41064 | -1.4169588 |
108 | 1 | -0.60444169 | 0.60433957E-03 | -143.86415 | 2.0483306 |
109 | 0 | 0.29470347 | 0.14596444E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.5_SHGC_0.25 | 29 | 1 | VerySmooth | 2.843 | 0.252 | 0.162 | 0.251 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 1.97990E-002 | 0.16139 | 0.61114 | 0.61114 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.10909 | 1.00000 | No |
Calculation Method | Value {days} | Allowable Number Figures in Shadow Overlap {} | Polygon Clipping Algorithm | Sky Diffuse Modeling Algorithm | External Shading Calculation Method | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | AverageOverDaysInFrequency | 30 | 15000 | SutherlandHodgman | SimpleSkyDiffuseModeling | InternalCalculation | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | GAS TANK1 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
2 | WaterHeater:Mixed | GAS TANK2 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
3 | WaterHeater:Mixed | GAS TANK3 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
4 | WaterHeater:Mixed | GAS TANK4 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
5 | WaterHeater:Mixed | GAS TANK5 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
6 | WaterHeater:Mixed | GAS TANK6 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
7 | WaterHeater:Mixed | GAS TANK7 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | LGSTORE1_WALL_2 | 0 | 118.41 | 56.08 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 4 | No | No |
2 | LGSTORE1_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 4 | No | No |
3 | LGSTORE1_WALL_3_DOOR_1 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 0 | No | No |
4 | LGSTORE1_WALL_3_DOOR_2 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 0 | No | No |
5 | LGSTORE1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 0 | No | No |
6 | LGSTORE1_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 4 | No | No |
7 | LGSTORE1_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 1 | No | No |
8 | LGSTORE1_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 1 | No | No |
9 | LGSTORE1_WALL_1_WINDOW_3 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 1 | No | No |
10 | LGSTORE1_WALL_1_WINDOW_4 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 1 | No | No |
11 | LGSTORE1_WALL_1_DOOR_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 1 | No | No |
12 | LGSTORE1_WALL_1_DOOR_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 1 | No | No |
13 | LGSTORE1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 0 | No | No |
14 | LGSTORE1_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 0 | No | No |
15 | LGSTORE1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 0 | No | No |
16 | SMSTORE1_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
17 | SMSTORE1_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
18 | SMSTORE1_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
19 | SMSTORE1_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
20 | SMSTORE1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
21 | SMSTORE1_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
22 | SMSTORE1_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
23 | SMSTORE1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
24 | SMSTORE1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
25 | SMSTORE1_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
26 | SMSTORE1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
27 | SMSTORE2_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
28 | SMSTORE2_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
29 | SMSTORE2_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
30 | SMSTORE2_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
31 | SMSTORE2_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
32 | SMSTORE2_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
33 | SMSTORE2_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
34 | SMSTORE2_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
35 | SMSTORE2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
36 | SMSTORE2_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
37 | SMSTORE2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
38 | SMSTORE3_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
39 | SMSTORE3_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
40 | SMSTORE3_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
41 | SMSTORE3_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
42 | SMSTORE3_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
43 | SMSTORE3_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
44 | SMSTORE3_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
45 | SMSTORE3_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
46 | SMSTORE3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
47 | SMSTORE3_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
48 | SMSTORE3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
49 | SMSTORE4_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
50 | SMSTORE4_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
51 | SMSTORE4_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
52 | SMSTORE4_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
53 | SMSTORE4_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
54 | SMSTORE4_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 3 | No | No |
55 | SMSTORE4_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
56 | SMSTORE4_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
57 | SMSTORE4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
58 | SMSTORE4_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
59 | SMSTORE4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
60 | LGSTORE2_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
61 | LGSTORE2_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 4 | No | No |
62 | LGSTORE2_WALL_3_DOOR_1 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
63 | LGSTORE2_WALL_3_DOOR_2 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
64 | LGSTORE2_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
65 | LGSTORE2_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 4 | No | No |
66 | LGSTORE2_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
67 | LGSTORE2_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
68 | LGSTORE2_WALL_1_WINDOW_3 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
69 | LGSTORE2_WALL_1_WINDOW_4 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
70 | LGSTORE2_WALL_1_DOOR_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
71 | LGSTORE2_WALL_1_DOOR_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
72 | LGSTORE2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
73 | LGSTORE2_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
74 | LGSTORE2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
75 | SMSTORE5_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
76 | SMSTORE5_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
77 | SMSTORE5_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
78 | SMSTORE5_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
79 | SMSTORE5_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
80 | SMSTORE5_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
81 | SMSTORE5_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
82 | SMSTORE5_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
83 | SMSTORE5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
84 | SMSTORE5_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
85 | SMSTORE5_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
86 | SMSTORE6_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
87 | SMSTORE6_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
88 | SMSTORE6_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
89 | SMSTORE6_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
90 | SMSTORE6_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
91 | SMSTORE6_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
92 | SMSTORE6_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
93 | SMSTORE6_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
94 | SMSTORE6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
95 | SMSTORE6_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
96 | SMSTORE6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
97 | SMSTORE7_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
98 | SMSTORE7_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
99 | SMSTORE7_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
100 | SMSTORE7_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
101 | SMSTORE7_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
102 | SMSTORE7_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 3 | No | No |
103 | SMSTORE7_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
104 | SMSTORE7_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
105 | SMSTORE7_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
106 | SMSTORE7_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
107 | SMSTORE7_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
108 | SMSTORE8_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 4 | No | No |
109 | SMSTORE8_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 1 | No | No |
110 | SMSTORE8_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 1 | No | No |
111 | SMSTORE8_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 1 | No | No |
112 | SMSTORE8_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
113 | SMSTORE8_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 3 | No | No |
114 | SMSTORE8_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
115 | SMSTORE8_WALL_4 | 0 | 118.41 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 3 | No | No |
116 | SMSTORE8_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
117 | SMSTORE8_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
118 | SMSTORE8_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | LGSTORE1_INFILTRATION | TYPE1_INFIL_SCH | LGSTORE1 | 348.39 | 30.0 | 0.159 | 4.569E-004 | 2.517E-004 | 0.317 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | LGSTORE1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | LGSTORE1 | 348.39 | 30.0 | 0.389 | 1.116E-003 | 6.149E-004 | 0.776 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | SMSTORE1_INFILTRATION | TYPE1_INFIL_SCH | SMSTORE1 | 174.19 | 15.0 | 4.561E-002 | 2.619E-004 | 1.775E-004 | 0.182 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | SMSTORE1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE1 | 174.19 | 15.0 | 0.222 | 1.276E-003 | 8.648E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
5 | SMSTORE2_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE2 | 174.19 | 15.0 | 4.561E-002 | 2.618E-004 | 1.775E-004 | 0.182 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | SMSTORE2_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE2 | 174.19 | 15.0 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
7 | SMSTORE3_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE3 | 174.19 | 15.0 | 4.561E-002 | 2.618E-004 | 1.775E-004 | 0.182 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | SMSTORE3_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE3 | 174.19 | 15.0 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | SMSTORE4_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE4 | 174.19 | 15.0 | 4.561E-002 | 2.618E-004 | 1.775E-004 | 0.182 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | SMSTORE4_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE4 | 174.19 | 15.0 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
11 | LGSTORE2_INFILTRATION | TYPE3_INFIL_SCH | LGSTORE2 | 348.39 | 30.0 | 9.122E-002 | 2.618E-004 | 1.775E-004 | 0.182 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | LGSTORE2_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | LGSTORE2 | 348.39 | 30.0 | 0.389 | 1.116E-003 | 7.565E-004 | 0.776 | 1.000 | 0.000 | 0.000 | 0.000 |
13 | SMSTORE5_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE5 | 174.19 | 15.0 | 4.561E-002 | 2.618E-004 | 1.775E-004 | 0.182 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | SMSTORE5_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE5 | 174.19 | 15.0 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
15 | SMSTORE6_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE6 | 174.19 | 15.0 | 4.561E-002 | 2.618E-004 | 1.775E-004 | 0.182 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | SMSTORE6_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE6 | 174.19 | 15.0 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
17 | SMSTORE7_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE7 | 174.19 | 15.0 | 4.561E-002 | 2.618E-004 | 1.775E-004 | 0.182 | 0.000 | 0.000 | 0.224 | 0.000 |
18 | SMSTORE7_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE7 | 174.19 | 15.0 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
19 | SMSTORE8_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE8 | 174.19 | 15.0 | 0.113 | 6.514E-004 | 3.022E-004 | 0.453 | 0.000 | 0.000 | 0.224 | 0.000 |
20 | SMSTORE8_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE8 | 174.19 | 15.0 | 0.222 | 1.276E-003 | 5.921E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | LGSTORE1 | Mixing/Well-Stirred |
2 | SMSTORE1 | Mixing/Well-Stirred |
3 | SMSTORE2 | Mixing/Well-Stirred |
4 | SMSTORE3 | Mixing/Well-Stirred |
5 | SMSTORE4 | Mixing/Well-Stirred |
6 | LGSTORE2 | Mixing/Well-Stirred |
7 | SMSTORE5 | Mixing/Well-Stirred |
8 | SMSTORE6 | Mixing/Well-Stirred |
9 | SMSTORE7 | Mixing/Well-Stirred |
10 | SMSTORE8 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone LGSTORE1 | 1.2000 |
3 | Zone SMSTORE1 | 1.2000 |
4 | Zone SMSTORE2 | 1.2000 |
5 | Zone SMSTORE3 | 1.2000 |
6 | Zone SMSTORE4 | 1.2000 |
7 | Zone LGSTORE2 | 1.2000 |
8 | Zone SMSTORE5 | 1.2000 |
9 | Zone SMSTORE6 | 1.2000 |
10 | Zone SMSTORE7 | 1.2000 |
11 | Zone SMSTORE8 | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone LGSTORE1 | 1.2000 |
3 | Zone SMSTORE1 | 1.2000 |
4 | Zone SMSTORE2 | 1.2000 |
5 | Zone SMSTORE3 | 1.2000 |
6 | Zone SMSTORE4 | 1.2000 |
7 | Zone LGSTORE2 | 1.2000 |
8 | Zone SMSTORE5 | 1.2000 |
9 | Zone SMSTORE6 | 1.2000 |
10 | Zone SMSTORE7 | 1.2000 |
11 | Zone SMSTORE8 | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | LGSTORE1 | Cooling | 27755.42914 | 33306.51497 | 2.09527 | 2.51432 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:30:00 | 42.00000 | 9.11023E-003 | 348.38640 | 29.99610 | 0.41145 | 0.00000 |
2 | LGSTORE1 | Heating | 13243.63398 | 15892.36077 | 0.58571 | 0.70286 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 6.30000 | 6.07234E-003 | 348.38640 | 29.99610 | 0.41145 | 0.00000 |
3 | SMSTORE1 | Cooling | 14589.74371 | 17507.69245 | 1.10139 | 1.32167 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | 42.00000 | 9.11023E-003 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
4 | SMSTORE1 | Heating | 6867.46268 | 8240.95521 | 0.30372 | 0.36446 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 6.30000 | 6.07234E-003 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
5 | SMSTORE2 | Cooling | 14511.96017 | 17414.35220 | 1.09552 | 1.31462 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:50:00 | 41.91917 | 9.11022E-003 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
6 | SMSTORE2 | Heating | 6959.31081 | 8351.17298 | 0.30778 | 0.36934 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 6.30000 | 6.07234E-003 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
7 | SMSTORE3 | Cooling | 14544.31138 | 17453.17366 | 1.09796 | 1.31755 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:50:00 | 41.91917 | 9.11022E-003 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
8 | SMSTORE3 | Heating | 7024.97130 | 8429.96556 | 0.31069 | 0.37282 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 6.30000 | 6.07234E-003 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
9 | SMSTORE4 | Cooling | 14493.29259 | 17391.95111 | 1.09411 | 1.31293 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:50:00 | 41.91917 | 9.11022E-003 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
10 | SMSTORE4 | Heating | 7161.26776 | 8593.52131 | 0.31671 | 0.38006 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 6.30000 | 6.07234E-003 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
11 | LGSTORE2 | Cooling | 26240.84847 | 31489.01816 | 1.98093 | 2.37711 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:40:00 | 41.83833 | 9.11022E-003 | 348.38640 | 29.99610 | 0.41145 | 0.00000 |
12 | LGSTORE2 | Heating | 13459.80420 | 16151.76504 | 0.59527 | 0.71433 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 6.30000 | 6.07234E-003 | 348.38640 | 29.99610 | 0.41145 | 0.00000 |
13 | SMSTORE5 | Cooling | 13928.64933 | 16714.37919 | 1.05148 | 1.26178 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:40:00 | 41.83833 | 9.11022E-003 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
14 | SMSTORE5 | Heating | 7327.07403 | 8792.48884 | 0.32405 | 0.38886 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 6.30000 | 6.07234E-003 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
15 | SMSTORE6 | Cooling | 13870.53081 | 16644.63697 | 1.04709 | 1.25651 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:40:00 | 41.83833 | 9.11022E-003 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
16 | SMSTORE6 | Heating | 7321.47105 | 8785.76526 | 0.32380 | 0.38856 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 6.30000 | 6.07234E-003 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
17 | SMSTORE7 | Cooling | 13879.83038 | 16655.79646 | 1.04780 | 1.25736 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:40:00 | 41.83833 | 9.11022E-003 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
18 | SMSTORE7 | Heating | 7483.96441 | 8980.75729 | 0.33098 | 0.39718 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 6.30000 | 6.07234E-003 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
19 | SMSTORE8 | Cooling | 14992.03899 | 17990.44678 | 1.13171 | 1.35805 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:00:00 | 41.51500 | 9.11022E-003 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
20 | SMSTORE8 | Heating | 8205.62858 | 9846.75429 | 0.36290 | 0.43548 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 6.30000 | 6.07234E-003 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC_1:1 | Cooling | Sensible | 41671.39 | 2.51432 | 2.51432 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
2 | PSZ-AC_1:1 | Heating | Sensible | 22847.75 | 0.70286 | 0.70286 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
3 | PSZ-AC_2:2 | Cooling | Sensible | 21679.23 | 1.32167 | 1.32167 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
4 | PSZ-AC_2:2 | Heating | Sensible | 11714.33 | 0.36446 | 0.36446 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
5 | PSZ-AC_3:3 | Cooling | Sensible | 21583.73 | 1.31462 | 1.31462 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
6 | PSZ-AC_3:3 | Heating | Sensible | 11822.94 | 0.36934 | 0.36934 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
7 | PSZ-AC_4:4 | Cooling | Sensible | 21621.32 | 1.31755 | 1.31755 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
8 | PSZ-AC_4:4 | Heating | Sensible | 11900.58 | 0.37282 | 0.37282 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
9 | PSZ-AC_5:5 | Cooling | Sensible | 21560.76 | 1.31293 | 1.31293 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
10 | PSZ-AC_5:5 | Heating | Sensible | 12061.76 | 0.38006 | 0.38006 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
11 | PSZ-AC_6:6 | Cooling | Sensible | 39861.36 | 2.37711 | 2.37711 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
12 | PSZ-AC_6:6 | Heating | Sensible | 23103.37 | 0.71433 | 0.71433 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
13 | PSZ-AC_7:7 | Cooling | Sensible | 20886.01 | 1.26178 | 1.26178 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
14 | PSZ-AC_7:7 | Heating | Sensible | 12257.82 | 0.38886 | 0.38886 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
15 | PSZ-AC_8:8 | Cooling | Sensible | 20817.11 | 1.25651 | 1.25651 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
16 | PSZ-AC_8:8 | Heating | Sensible | 12251.20 | 0.38856 | 0.38856 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
17 | PSZ-AC_9:9 | Cooling | Sensible | 20827.63 | 1.25736 | 1.25736 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
18 | PSZ-AC_9:9 | Heating | Sensible | 12443.35 | 0.39718 | 0.39718 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
19 | PSZ-AC_10:10 | Cooling | Sensible | 22072.56 | 1.35805 | 1.35805 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
20 | PSZ-AC_10:10 | Heating | Sensible | 13296.73 | 0.43548 | 0.43548 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:Uncontrolled | LGSTORE1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.51432 |
2 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.32167 |
3 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE2 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.31462 |
4 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.31755 |
5 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE4 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.31293 |
6 | AirTerminal:SingleDuct:Uncontrolled | LGSTORE2 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.37711 |
7 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE5 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.26178 |
8 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.25651 |
9 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE7 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.25736 |
10 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE8 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.35805 |
11 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.51432 |
12 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.51432 |
13 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.51432 |
14 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 2.51432 |
15 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.51432 |
16 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Main Design Air Flow Rate [m3/s] | 2.51432 |
17 | AirLoopHVAC | PSZ-AC_1:1 | User Heating Air Flow Ratio [] | 1.00000 |
18 | AirLoopHVAC | PSZ-AC_1:1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
19 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.32167 |
20 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.32167 |
21 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.32167 |
22 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.32167 |
23 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.32167 |
24 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Main Design Air Flow Rate [m3/s] | 1.32167 |
25 | AirLoopHVAC | PSZ-AC_2:2 | User Heating Air Flow Ratio [] | 1.00000 |
26 | AirLoopHVAC | PSZ-AC_2:2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
27 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.31462 |
28 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.31462 |
29 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.31462 |
30 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.31462 |
31 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.31462 |
32 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Main Design Air Flow Rate [m3/s] | 1.31462 |
33 | AirLoopHVAC | PSZ-AC_3:3 | User Heating Air Flow Ratio [] | 1.00000 |
34 | AirLoopHVAC | PSZ-AC_3:3 | Calculated Heating Air Flow Ratio [] | 1.00000 |
35 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.31755 |
36 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.31755 |
37 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.31755 |
38 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.31755 |
39 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.31755 |
40 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Main Design Air Flow Rate [m3/s] | 1.31755 |
41 | AirLoopHVAC | PSZ-AC_4:4 | User Heating Air Flow Ratio [] | 1.00000 |
42 | AirLoopHVAC | PSZ-AC_4:4 | Calculated Heating Air Flow Ratio [] | 1.00000 |
43 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.31293 |
44 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.31293 |
45 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.31293 |
46 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.31293 |
47 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.31293 |
48 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Main Design Air Flow Rate [m3/s] | 1.31293 |
49 | AirLoopHVAC | PSZ-AC_5:5 | User Heating Air Flow Ratio [] | 1.00000 |
50 | AirLoopHVAC | PSZ-AC_5:5 | Calculated Heating Air Flow Ratio [] | 1.00000 |
51 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.37711 |
52 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.37711 |
53 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.37711 |
54 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Heating Design Air Flow Rate [m3/s] | 2.37711 |
55 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.37711 |
56 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Main Design Air Flow Rate [m3/s] | 2.37711 |
57 | AirLoopHVAC | PSZ-AC_6:6 | User Heating Air Flow Ratio [] | 1.00000 |
58 | AirLoopHVAC | PSZ-AC_6:6 | Calculated Heating Air Flow Ratio [] | 1.00000 |
59 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.26178 |
60 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.26178 |
61 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.26178 |
62 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.26178 |
63 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.26178 |
64 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Main Design Air Flow Rate [m3/s] | 1.26178 |
65 | AirLoopHVAC | PSZ-AC_7:7 | User Heating Air Flow Ratio [] | 1.00000 |
66 | AirLoopHVAC | PSZ-AC_7:7 | Calculated Heating Air Flow Ratio [] | 1.00000 |
67 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.25651 |
68 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.25651 |
69 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.25651 |
70 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.25651 |
71 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.25651 |
72 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Main Design Air Flow Rate [m3/s] | 1.25651 |
73 | AirLoopHVAC | PSZ-AC_8:8 | User Heating Air Flow Ratio [] | 1.00000 |
74 | AirLoopHVAC | PSZ-AC_8:8 | Calculated Heating Air Flow Ratio [] | 1.00000 |
75 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.25736 |
76 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.25736 |
77 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.25736 |
78 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.25736 |
79 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.25736 |
80 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Main Design Air Flow Rate [m3/s] | 1.25736 |
81 | AirLoopHVAC | PSZ-AC_9:9 | User Heating Air Flow Ratio [] | 1.00000 |
82 | AirLoopHVAC | PSZ-AC_9:9 | Calculated Heating Air Flow Ratio [] | 1.00000 |
83 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.35805 |
84 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.35805 |
85 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.35805 |
86 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.35805 |
87 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.35805 |
88 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Main Design Air Flow Rate [m3/s] | 1.35805 |
89 | AirLoopHVAC | PSZ-AC_10:10 | User Heating Air Flow Ratio [] | 1.00000 |
90 | AirLoopHVAC | PSZ-AC_10:10 | Calculated Heating Air Flow Ratio [] | 1.00000 |
91 | AirLoopHVAC | PSZ-AC_1:1 | Design Supply Air Flow Rate [m3/s] | 2.51432 |
92 | AirLoopHVAC | PSZ-AC_2:2 | Design Supply Air Flow Rate [m3/s] | 1.32167 |
93 | AirLoopHVAC | PSZ-AC_3:3 | Design Supply Air Flow Rate [m3/s] | 1.31462 |
94 | AirLoopHVAC | PSZ-AC_4:4 | Design Supply Air Flow Rate [m3/s] | 1.31755 |
95 | AirLoopHVAC | PSZ-AC_5:5 | Design Supply Air Flow Rate [m3/s] | 1.31293 |
96 | AirLoopHVAC | PSZ-AC_6:6 | Design Supply Air Flow Rate [m3/s] | 2.37711 |
97 | AirLoopHVAC | PSZ-AC_7:7 | Design Supply Air Flow Rate [m3/s] | 1.26178 |
98 | AirLoopHVAC | PSZ-AC_8:8 | Design Supply Air Flow Rate [m3/s] | 1.25651 |
99 | AirLoopHVAC | PSZ-AC_9:9 | Design Supply Air Flow Rate [m3/s] | 1.25736 |
100 | AirLoopHVAC | PSZ-AC_10:10 | Design Supply Air Flow Rate [m3/s] | 1.35805 |
101 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.51432 |
102 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41145 |
103 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.51432 |
104 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.51432 |
105 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.51432 |
106 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.65945 |
107 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.51432 |
108 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.25716 |
109 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.67621 |
110 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 42063.50076 |
111 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 51734.55000 |
112 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 25867.27500 |
113 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 25867.27500 |
114 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.72678 |
115 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.72678 |
116 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.72678 |
117 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.72678 |
118 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 51734.55000 |
119 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 63210.34271 |
120 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
121 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
122 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.51432 |
123 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 2690.44576 |
124 | Coil:Heating:Fuel | PSZ-AC_1:1_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 63210.34271 |
125 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.32167 |
126 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20573 |
127 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.32167 |
128 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.32167 |
129 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.32167 |
130 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.87230 |
131 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.32167 |
132 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.66084 |
133 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.88111 |
134 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 21878.33140 |
135 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 26997.92000 |
136 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 13498.96000 |
137 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 13498.96000 |
138 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.72894 |
139 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.72894 |
140 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.72894 |
141 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.72894 |
142 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 26997.92000 |
143 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 33042.66992 |
144 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
145 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
146 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.32167 |
147 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1463.29872 |
148 | Coil:Heating:Fuel | PSZ-AC_2:2_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 33042.66992 |
149 | Controller:OutdoorAir | PSZ-AC_3:3_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.31462 |
150 | Controller:OutdoorAir | PSZ-AC_3:3_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20573 |
151 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.31462 |
152 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.31462 |
153 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.31462 |
154 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.86765 |
155 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.31462 |
156 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.65731 |
157 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.87641 |
158 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 21794.83484 |
159 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 26873.08000 |
160 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 13436.54000 |
161 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 13436.54000 |
162 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.72872 |
163 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.72873 |
164 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.72873 |
165 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.72873 |
166 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 26873.08000 |
167 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 32885.66900 |
168 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
169 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
170 | Fan:SystemModel | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.31462 |
171 | Fan:SystemModel | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1455.49645 |
172 | Coil:Heating:Fuel | PSZ-AC_3:3_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 32885.66900 |
173 | Controller:OutdoorAir | PSZ-AC_4:4_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.31755 |
174 | Controller:OutdoorAir | PSZ-AC_4:4_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20573 |
175 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.31755 |
176 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.31755 |
177 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.31755 |
178 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.86959 |
179 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.31755 |
180 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.65878 |
181 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.87837 |
182 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 21829.10731 |
183 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 26925.41000 |
184 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 13462.70500 |
185 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 13462.70500 |
186 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.72881 |
187 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.72881 |
188 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.72881 |
189 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.72881 |
190 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 26925.41000 |
191 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 32950.96940 |
192 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
193 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
194 | Fan:SystemModel | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.31755 |
195 | Fan:SystemModel | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1458.74115 |
196 | Coil:Heating:Fuel | PSZ-AC_4:4_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 32950.96940 |
197 | Controller:OutdoorAir | PSZ-AC_5:5_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.31293 |
198 | Controller:OutdoorAir | PSZ-AC_5:5_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20573 |
199 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.31293 |
200 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.31293 |
201 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.31293 |
202 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.86654 |
203 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.31293 |
204 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.65647 |
205 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.87529 |
206 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 21775.59320 |
207 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 26843.13000 |
208 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 13421.56500 |
209 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 13421.56500 |
210 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.72867 |
211 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.72867 |
212 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.72867 |
213 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.72867 |
214 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 26843.13000 |
215 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 32847.98162 |
216 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
217 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
218 | Fan:SystemModel | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.31293 |
219 | Fan:SystemModel | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1453.62398 |
220 | Coil:Heating:Fuel | PSZ-AC_5:5_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 32847.98162 |
221 | Controller:OutdoorAir | PSZ-AC_6:6_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.37711 |
222 | Controller:OutdoorAir | PSZ-AC_6:6_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41145 |
223 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.37711 |
224 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.37711 |
225 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.37711 |
226 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.56889 |
227 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.37711 |
228 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.18856 |
229 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.58474 |
230 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 40461.83399 |
231 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 49294.01000 |
232 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 24647.00500 |
233 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 24647.00500 |
234 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.72449 |
235 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.72449 |
236 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.72449 |
237 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.72449 |
238 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 49294.01000 |
239 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 60153.02434 |
240 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
241 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
242 | Fan:SystemModel | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.37711 |
243 | Fan:SystemModel | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 2543.62074 |
244 | Coil:Heating:Fuel | PSZ-AC_6:6_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 60153.02434 |
245 | Controller:OutdoorAir | PSZ-AC_7:7_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.26178 |
246 | Controller:OutdoorAir | PSZ-AC_7:7_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20573 |
247 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.26178 |
248 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.26178 |
249 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.26178 |
250 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.83277 |
251 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.26178 |
252 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.63089 |
253 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.84119 |
254 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 21183.34489 |
255 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 25933.27000 |
256 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 12966.63500 |
257 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 12966.63500 |
258 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.72711 |
259 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.72711 |
260 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.72711 |
261 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.72711 |
262 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 25933.27000 |
263 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 31708.20445 |
264 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
265 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
266 | Fan:SystemModel | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.26178 |
267 | Fan:SystemModel | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1396.98951 |
268 | Coil:Heating:Fuel | PSZ-AC_7:7_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 31708.20445 |
269 | Controller:OutdoorAir | PSZ-AC_8:8_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.25651 |
270 | Controller:OutdoorAir | PSZ-AC_8:8_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20573 |
271 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.25651 |
272 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.25651 |
273 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.25651 |
274 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.82930 |
275 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.25651 |
276 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.62826 |
277 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.83767 |
278 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 21121.91818 |
279 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 25839.50000 |
280 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 12919.75000 |
281 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 12919.75000 |
282 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.72695 |
283 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.72695 |
284 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.72695 |
285 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.72695 |
286 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 25839.50000 |
287 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 31590.89217 |
288 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
289 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
290 | Fan:SystemModel | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.25651 |
291 | Fan:SystemModel | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1391.16044 |
292 | Coil:Heating:Fuel | PSZ-AC_8:8_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 31590.89217 |
293 | Controller:OutdoorAir | PSZ-AC_9:9_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.25736 |
294 | Controller:OutdoorAir | PSZ-AC_9:9_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20573 |
295 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.25736 |
296 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.25736 |
297 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.25736 |
298 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.82986 |
299 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.25736 |
300 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.62868 |
301 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.83824 |
302 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 21132.07342 |
303 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 25854.61000 |
304 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 12927.30500 |
305 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 12927.30500 |
306 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.72697 |
307 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.72697 |
308 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.72697 |
309 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.72697 |
310 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 25854.61000 |
311 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 31609.65886 |
312 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
313 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
314 | Fan:SystemModel | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.25736 |
315 | Fan:SystemModel | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1392.09299 |
316 | Coil:Heating:Fuel | PSZ-AC_9:9_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 31609.65886 |
317 | Controller:OutdoorAir | PSZ-AC_10:10_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.35805 |
318 | Controller:OutdoorAir | PSZ-AC_10:10_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20573 |
319 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.35805 |
320 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.35805 |
321 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.35805 |
322 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.89632 |
323 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.35805 |
324 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.67903 |
325 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.90537 |
326 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 22480.54958 |
327 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 27549.62000 |
328 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 13774.81000 |
329 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 13774.81000 |
330 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.73101 |
331 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.73101 |
332 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.73101 |
333 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.73101 |
334 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 27549.62000 |
335 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 33853.41457 |
336 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
337 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
338 | Fan:SystemModel | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.35805 |
339 | Fan:SystemModel | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1503.58141 |
340 | Coil:Heating:Fuel | PSZ-AC_10:10_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 33853.41457 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | 49757.7 | 11.42 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | 25958.9 | 33.76 | |||
3 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | 25839.6 | 45.49 | |||
4 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | 25889.6 | 56.98 | |||
5 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | 25811.0 | 68.73 | |||
6 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | 47424.8 | 48.39 | |||
7 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | 24941.2 | 104.81 | |||
8 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | 24851.6 | 116.79 | |||
9 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | 24866.0 | 128.31 | |||
10 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | 26482.1 | 131.75 |
Zone Name | # Surfaces | |
1 | LGSTORE1 | 15 |
2 | SMSTORE1 | 11 |
3 | SMSTORE2 | 11 |
4 | SMSTORE3 | 11 |
5 | SMSTORE4 | 11 |
6 | LGSTORE2 | 15 |
7 | SMSTORE5 | 11 |
8 | SMSTORE6 | 11 |
9 | SMSTORE7 | 11 |
10 | SMSTORE8 | 11 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | LGSTORE1_WALL_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.468 | 0.437 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | LGSTORE1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.468 | 0.437 | 71.15 | 78.94 | 71.15 | 0.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | LGSTORE1_WALL_3_DOOR_1 | Door | LGSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
4 | LGSTORE1_WALL_3_DOOR_2 | Door | LGSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
5 | LGSTORE1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
6 | LGSTORE1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.468 | 0.437 | 58.20 | 78.94 | 58.20 | 180.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
7 | LGSTORE1_WALL_1_WINDOW_1 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
8 | LGSTORE1_WALL_1_WINDOW_2 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
9 | LGSTORE1_WALL_1_WINDOW_3 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
10 | LGSTORE1_WALL_1_WINDOW_4 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
11 | LGSTORE1_WALL_1_DOOR_1 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
12 | LGSTORE1_WALL_1_DOOR_2 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
13 | LGSTORE1_FLOOR | Floor | CTF - ConductionTransferFunction | LGSTORE1_FLOOR_FFACTOR | 0.199 | 0.190 | 348.39 | 348.39 | 348.39 | 270.00 | 180.00 | 22.86 | 15.24 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | LGSTORE1_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 348.39 | 348.39 | 348.39 | 270.00 | 0.00 | 22.86 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
15 | LGSTORE1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 696.77 | 696.77 | 696.77 | 0.00 | 90.00 | 696.77 | 1.00 | 0.00 | LGSTORE1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
16 | SMSTORE1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.468 | 0.437 | 29.10 | 39.47 | 29.10 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
17 | SMSTORE1_WALL_1_WINDOW_1 | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
18 | SMSTORE1_WALL_1_WINDOW_2 | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
19 | SMSTORE1_WALL_1_DOOR | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
20 | SMSTORE1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | SMSTORE1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.468 | 0.437 | 35.57 | 39.47 | 35.57 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | SMSTORE1_WALL_3_DOOR | Door | SMSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
23 | SMSTORE1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE2_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
24 | SMSTORE1_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE1_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | SMSTORE1_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
26 | SMSTORE1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
27 | SMSTORE2_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.468 | 0.437 | 29.12 | 39.47 | 29.12 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | SMSTORE2_WALL_1_WINDOW_1 | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
29 | SMSTORE2_WALL_1_WINDOW_2 | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
30 | SMSTORE2_WALL_1_DOOR | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
31 | SMSTORE2_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
32 | SMSTORE2_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.468 | 0.437 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | SMSTORE2_WALL_3_DOOR | Door | SMSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
34 | SMSTORE2_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE3_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | SMSTORE2_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE2_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
36 | SMSTORE2_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
37 | SMSTORE2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
38 | SMSTORE3_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.468 | 0.437 | 29.12 | 39.47 | 29.12 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
39 | SMSTORE3_WALL_1_WINDOW_1 | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
40 | SMSTORE3_WALL_1_WINDOW_2 | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
41 | SMSTORE3_WALL_1_DOOR | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
42 | SMSTORE3_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE2_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | SMSTORE3_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.468 | 0.437 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | SMSTORE3_WALL_3_DOOR | Door | SMSTORE3_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
45 | SMSTORE3_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE4_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | SMSTORE3_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE3_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
47 | SMSTORE3_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
48 | SMSTORE3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
49 | SMSTORE4_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.468 | 0.437 | 29.12 | 39.47 | 29.12 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | SMSTORE4_WALL_1_WINDOW_1 | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
51 | SMSTORE4_WALL_1_WINDOW_2 | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
52 | SMSTORE4_WALL_1_DOOR | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | SMSTORE4_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE3_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | SMSTORE4_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.468 | 0.437 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | SMSTORE4_WALL_3_DOOR | Door | SMSTORE4_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | SMSTORE4_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE2_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | SMSTORE4_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE4_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | SMSTORE4_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | SMSTORE4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | LGSTORE2_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE4_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | LGSTORE2_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.468 | 0.437 | 71.19 | 78.94 | 71.19 | 0.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
62 | LGSTORE2_WALL_3_DOOR_1 | Door | LGSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
63 | LGSTORE2_WALL_3_DOOR_2 | Door | LGSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
64 | LGSTORE2_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE5_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | LGSTORE2_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.468 | 0.437 | 58.24 | 78.94 | 58.24 | 180.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
66 | LGSTORE2_WALL_1_WINDOW_1 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | LGSTORE2_WALL_1_WINDOW_2 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | LGSTORE2_WALL_1_WINDOW_3 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | LGSTORE2_WALL_1_WINDOW_4 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | LGSTORE2_WALL_1_DOOR_1 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
71 | LGSTORE2_WALL_1_DOOR_2 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
72 | LGSTORE2_FLOOR | Floor | CTF - ConductionTransferFunction | LGSTORE2_FLOOR_FFACTOR | 0.112 | 0.109 | 348.39 | 348.39 | 348.39 | 270.00 | 180.00 | 22.86 | 15.24 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
73 | LGSTORE2_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 348.39 | 348.39 | 348.39 | 270.00 | 0.00 | 22.86 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
74 | LGSTORE2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 696.77 | 696.77 | 696.77 | 0.00 | 90.00 | 696.77 | 1.00 | 0.00 | LGSTORE2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
75 | SMSTORE5_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.468 | 0.437 | 29.12 | 39.47 | 29.12 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | SMSTORE5_WALL_1_WINDOW_1 | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
77 | SMSTORE5_WALL_1_WINDOW_2 | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | SMSTORE5_WALL_1_DOOR | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
79 | SMSTORE5_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE2_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | SMSTORE5_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.468 | 0.437 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | SMSTORE5_WALL_3_DOOR | Door | SMSTORE5_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
82 | SMSTORE5_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE6_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
83 | SMSTORE5_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE5_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
84 | SMSTORE5_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
85 | SMSTORE5_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE5_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
86 | SMSTORE6_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.468 | 0.437 | 29.12 | 39.47 | 29.12 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | SMSTORE6_WALL_1_WINDOW_1 | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
88 | SMSTORE6_WALL_1_WINDOW_2 | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
89 | SMSTORE6_WALL_1_DOOR | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
90 | SMSTORE6_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE5_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
91 | SMSTORE6_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.468 | 0.437 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
92 | SMSTORE6_WALL_3_DOOR | Door | SMSTORE6_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
93 | SMSTORE6_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE7_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | SMSTORE6_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE6_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
95 | SMSTORE6_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
96 | SMSTORE6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
97 | SMSTORE7_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.468 | 0.437 | 29.12 | 39.47 | 29.12 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | SMSTORE7_WALL_1_WINDOW_1 | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
99 | SMSTORE7_WALL_1_WINDOW_2 | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
100 | SMSTORE7_WALL_1_DOOR | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
101 | SMSTORE7_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE6_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
102 | SMSTORE7_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.468 | 0.437 | 35.59 | 39.47 | 35.59 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | SMSTORE7_WALL_3_DOOR | Door | SMSTORE7_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
104 | SMSTORE7_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE8_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | SMSTORE7_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE7_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
106 | SMSTORE7_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
107 | SMSTORE7_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE7_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
108 | SMSTORE8_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.468 | 0.437 | 29.12 | 39.47 | 29.12 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | SMSTORE8_WALL_1_WINDOW_1 | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
110 | SMSTORE8_WALL_1_WINDOW_2 | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
111 | SMSTORE8_WALL_1_DOOR | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
112 | SMSTORE8_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE7_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
113 | SMSTORE8_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.468 | 0.437 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | SMSTORE8_WALL_3_DOOR | Door | SMSTORE8_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
115 | SMSTORE8_WALL_4 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.468 | 0.437 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | SMSTORE8_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE8_FLOOR_FFACTOR | 0.289 | 0.270 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | SMSTORE8_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | SMSTORE8_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE8_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1 |
2 | VETERANS DAY | Holiday | InputFile | 11/11 | 1 |
3 | CHRISTMAS | Holiday | InputFile | 12/25 | 1 |
4 | INDEPENDENCE DAY | Holiday | InputFile | 07/04 | 1 |
5 | MLK DAY | Holiday | InputFile | 01/16 | 1 |
6 | PRESIDENTS DAY | Holiday | InputFile | 02/20 | 1 |
7 | MEMORIAL DAY | Holiday | InputFile | 05/29 | 1 |
8 | LABOR DAY | Holiday | InputFile | 09/04 | 1 |
9 | COLUMBUS DAY | Holiday | InputFile | 10/09 | 1 |
10 | THANKSGIVING | Holiday | InputFile | 11/23 | 1 |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
NumberofWarmupDays | |
1 | 9 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | LGSTORE1 | RunPeriod: RUNPERIOD 1 | 6.5755581896E-002 | 0.1600218268 | Pass | Pass | 0.1259186515 | 0.7239537637 | Pass | Pass |
2 | SMSTORE1 | RunPeriod: RUNPERIOD 1 | 7.6968783621E-002 | 0.1595980580 | Pass | Pass | 0.1069319158 | 0.4180802380 | Pass | Pass |
3 | SMSTORE2 | RunPeriod: RUNPERIOD 1 | 5.7910136839E-002 | 0.1728310458 | Pass | Pass | 0.3999735308 | 3.3384208870 | Pass | Pass |
4 | SMSTORE3 | RunPeriod: RUNPERIOD 1 | 4.9598321848E-002 | 0.2020849826 | Pass | Pass | 0.5505959933 | 5.1389832531 | Pass | Pass |
5 | SMSTORE4 | RunPeriod: RUNPERIOD 1 | 4.7226502895E-002 | 0.2237898802 | Pass | Pass | 0.2980218187 | 1.9761965964 | Pass | Pass |
6 | LGSTORE2 | RunPeriod: RUNPERIOD 1 | 4.3300511809E-002 | 0.2280952685 | Pass | Pass | 0.1634190485 | 0.4667040257 | Pass | Pass |
7 | SMSTORE5 | RunPeriod: RUNPERIOD 1 | 4.2203234463E-002 | 0.2258517514 | Pass | Pass | 0.2723359152 | 1.0235086068 | Pass | Pass |
8 | SMSTORE6 | RunPeriod: RUNPERIOD 1 | 4.1735610781E-002 | 0.2259018294 | Pass | Pass | 0.7193173065 | 5.9993181379 | Pass | Pass |
9 | SMSTORE7 | RunPeriod: RUNPERIOD 1 | 4.3174200413E-002 | 0.2257517089 | Pass | Pass | 0.3166885952 | 1.3519937816 | Pass | Pass |
10 | SMSTORE8 | RunPeriod: RUNPERIOD 1 | 4.0761319528E-002 | 0.2229501181 | Pass | Pass | 0.2905174200 | 0.8778256355 | Pass | Pass |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2020-06-03 19:21:12
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 6.30 | 0.00 | 6.30 | Wetbulb [C] | 0.50 | 270.00 |
NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 42.00 | 9.70 | 22.20 | Wetbulb [C] | 3.20 | 320.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2020-06-03 19:21:12
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_2 | NONRES_EXT_WALL | 0.30 | 0.437 | 0.468 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE1_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.437 | 0.468 | 78.94 | 71.15 | 0.00 | 90.00 | N |
LGSTORE1_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.437 | 0.468 | 78.94 | 58.20 | 180.00 | 90.00 | S |
LGSTORE1_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 348.39 | 348.39 | 270.00 | 0.00 | |
SMSTORE1_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.437 | 0.468 | 39.47 | 29.10 | 180.00 | 90.00 | S |
SMSTORE1_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.437 | 0.468 | 39.47 | 35.57 | 0.00 | 90.00 | N |
SMSTORE1_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE2_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.437 | 0.468 | 39.47 | 29.12 | 180.00 | 90.00 | S |
SMSTORE2_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.437 | 0.468 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE2_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE3_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.437 | 0.468 | 39.47 | 29.12 | 180.00 | 90.00 | S |
SMSTORE3_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.437 | 0.468 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE3_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE4_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.437 | 0.468 | 39.47 | 29.12 | 180.00 | 90.00 | S |
SMSTORE4_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.437 | 0.468 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE4_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
LGSTORE2_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.437 | 0.468 | 78.94 | 71.19 | 0.00 | 90.00 | N |
LGSTORE2_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.437 | 0.468 | 78.94 | 58.24 | 180.00 | 90.00 | S |
LGSTORE2_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 348.39 | 348.39 | 270.00 | 0.00 | |
SMSTORE5_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.437 | 0.468 | 39.47 | 29.12 | 180.00 | 90.00 | S |
SMSTORE5_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.437 | 0.468 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE5_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE6_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.437 | 0.468 | 39.47 | 29.12 | 180.00 | 90.00 | S |
SMSTORE6_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.437 | 0.468 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE6_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE7_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.437 | 0.468 | 39.47 | 29.12 | 180.00 | 90.00 | S |
SMSTORE7_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.437 | 0.468 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE7_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE8_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.437 | 0.468 | 39.47 | 29.12 | 180.00 | 90.00 | S |
SMSTORE8_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.437 | 0.468 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE8_WALL_4 | NONRES_EXT_WALL | 0.30 | 0.437 | 0.468 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE8_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
LGSTORE1_FLOOR | LGSTORE1_FLOOR_FFACTOR | 1.00 | 0.199 | 348.39 | 348.39 | 270.00 | 180.00 | ||
SMSTORE1_FLOOR | SMSTORE1_FLOOR_FFACTOR | 1.00 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | ||
SMSTORE2_FLOOR | SMSTORE2_FLOOR_FFACTOR | 1.00 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | ||
SMSTORE3_FLOOR | SMSTORE3_FLOOR_FFACTOR | 1.00 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | ||
SMSTORE4_FLOOR | SMSTORE4_FLOOR_FFACTOR | 1.00 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | ||
LGSTORE2_FLOOR | LGSTORE2_FLOOR_FFACTOR | 1.00 | 0.112 | 348.39 | 348.39 | 270.00 | 180.00 | ||
SMSTORE5_FLOOR | SMSTORE5_FLOOR_FFACTOR | 1.00 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | ||
SMSTORE6_FLOOR | SMSTORE6_FLOOR_FFACTOR | 1.00 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | ||
SMSTORE7_FLOOR | SMSTORE7_FLOOR_FFACTOR | 1.00 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | ||
SMSTORE8_FLOOR | SMSTORE8_FLOOR_FFACTOR | 1.00 | 0.289 | 174.19 | 174.19 | 270.00 | 180.00 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.843 | 0.252 | 0.251 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE1_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.843 | 0.252 | 0.251 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE1_WALL_1_WINDOW_3 | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.843 | 0.252 | 0.251 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE1_WALL_1_WINDOW_4 | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.843 | 0.252 | 0.251 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE1_WALL_1_DOOR_1 | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.843 | 0.252 | 0.251 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE1_WALL_1_DOOR_2 | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.843 | 0.252 | 0.251 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE1_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.843 | 0.252 | 0.251 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE1_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.843 | 0.252 | 0.251 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE1_WALL_1_DOOR | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.843 | 0.252 | 0.251 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE2_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.843 | 0.252 | 0.251 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE2_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.843 | 0.252 | 0.251 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE2_WALL_1_DOOR | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.843 | 0.252 | 0.251 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE3_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.843 | 0.252 | 0.251 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE3_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.843 | 0.252 | 0.251 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE3_WALL_1_DOOR | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.843 | 0.252 | 0.251 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE4_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.843 | 0.252 | 0.251 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE4_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.843 | 0.252 | 0.251 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE4_WALL_1_DOOR | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.843 | 0.252 | 0.251 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE2_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.843 | 0.252 | 0.251 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE2_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.843 | 0.252 | 0.251 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE2_WALL_1_WINDOW_3 | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.843 | 0.252 | 0.251 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE2_WALL_1_WINDOW_4 | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.843 | 0.252 | 0.251 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE2_WALL_1_DOOR_1 | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.843 | 0.252 | 0.251 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE2_WALL_1_DOOR_2 | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.843 | 0.252 | 0.251 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE5_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.843 | 0.252 | 0.251 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE5_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.843 | 0.252 | 0.251 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE5_WALL_1_DOOR | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.843 | 0.252 | 0.251 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE6_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.843 | 0.252 | 0.251 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE6_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.843 | 0.252 | 0.251 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE6_WALL_1_DOOR | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.843 | 0.252 | 0.251 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE7_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.843 | 0.252 | 0.251 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE7_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.843 | 0.252 | 0.251 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE7_WALL_1_DOOR | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.843 | 0.252 | 0.251 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE8_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.843 | 0.252 | 0.251 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE8_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.843 | 0.252 | 0.251 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE8_WALL_1_DOOR | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.843 | 0.252 | 0.251 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | ||
Total or Average | 124.29 | 2.843 | 0.252 | 0.251 | ||||||||||||
North Total or Average | 0.00 | - | - | - | ||||||||||||
Non-North Total or Average | 124.29 | 2.843 | 0.252 | 0.251 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
LGSTORE1_WALL_3_DOOR_1 | SWINGING DOOR_CON | 2.281 | 3.464 | 3.90 | LGSTORE1_WALL_3 |
LGSTORE1_WALL_3_DOOR_2 | SWINGING DOOR_CON | 2.281 | 3.464 | 3.90 | LGSTORE1_WALL_3 |
SMSTORE1_WALL_3_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 3.90 | SMSTORE1_WALL_3 |
SMSTORE2_WALL_3_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 3.88 | SMSTORE2_WALL_3 |
SMSTORE3_WALL_3_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 3.88 | SMSTORE3_WALL_3 |
SMSTORE4_WALL_3_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 3.88 | SMSTORE4_WALL_3 |
LGSTORE2_WALL_3_DOOR_1 | SWINGING DOOR_CON | 2.281 | 3.464 | 3.88 | LGSTORE2_WALL_3 |
LGSTORE2_WALL_3_DOOR_2 | SWINGING DOOR_CON | 2.281 | 3.464 | 3.88 | LGSTORE2_WALL_3 |
SMSTORE5_WALL_3_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 3.88 | SMSTORE5_WALL_3 |
SMSTORE6_WALL_3_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 3.88 | SMSTORE6_WALL_3 |
SMSTORE7_WALL_3_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 3.88 | SMSTORE7_WALL_3 |
SMSTORE8_WALL_3_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 3.88 | SMSTORE8_WALL_3 |
Report: Shading Summary
For: Entire Facility
Timestamp: 2020-06-03 19:21:12
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
LGSTORE1_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_4 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_DOOR_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_DOOR_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_4 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_DOOR_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_DOOR_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2020-06-03 19:21:12
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
LGSTORE1_LIGHTS | LGSTORE1 | 13.1675 | 348.39 | 4587.39 | LightsWired | TYPE1_LIGHT_SCH | 98.40 | 168.00 | 98.38 | 0.0000 | Y | 84.71 |
LGSTORE1_LIGHTS_ALLOWANCE | LGSTORE1 | 5.1990 | 348.39 | 1811.25 | LightsWired | TYPE1_LIGHT_SCH | 98.40 | 168.00 | 98.38 | 0.0000 | Y | 33.45 |
SMSTORE1_LIGHTS | SMSTORE1 | 13.1675 | 174.19 | 2293.69 | LightsWired | TYPE1_LIGHT_SCH | 98.40 | 168.00 | 98.38 | 0.0000 | Y | 42.36 |
SMSTORE1_LIGHTS_ALLOWANCE | SMSTORE1 | 6.6413 | 174.19 | 1156.88 | LightsWired | TYPE1_LIGHT_SCH | 98.40 | 168.00 | 98.38 | 0.0000 | Y | 21.36 |
SMSTORE2_LIGHTS | SMSTORE2 | 13.1675 | 174.19 | 2293.69 | LightsWired | TYPE2_LIGHT_SCH | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 33.57 |
SMSTORE2_LIGHTS_ALLOWANCE | SMSTORE2 | 4.4886 | 174.19 | 781.88 | LightsWired | TYPE2_LIGHT_SCH | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 11.44 |
SMSTORE3_LIGHTS | SMSTORE3 | 13.1675 | 174.19 | 2293.69 | LightsWired | TYPE2_LIGHT_SCH | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 33.57 |
SMSTORE3_LIGHTS_ALLOWANCE | SMSTORE3 | 4.4886 | 174.19 | 781.88 | LightsWired | TYPE2_LIGHT_SCH | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 11.44 |
SMSTORE4_LIGHTS | SMSTORE4 | 13.1675 | 174.19 | 2293.69 | LightsWired | TYPE2_LIGHT_SCH | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 33.57 |
SMSTORE4_LIGHTS_ALLOWANCE | SMSTORE4 | 4.4886 | 174.19 | 781.88 | LightsWired | TYPE2_LIGHT_SCH | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 11.44 |
LGSTORE2_LIGHTS | LGSTORE2 | 13.1675 | 348.39 | 4587.39 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 168.00 | 71.66 | 0.0000 | Y | 61.71 |
LGSTORE2_LIGHTS_ALLOWANCE | LGSTORE2 | 0.0000 | 348.39 | 0.00 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE5_LIGHTS | SMSTORE5 | 13.1675 | 174.19 | 2293.69 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 168.00 | 71.66 | 0.0000 | Y | 30.85 |
SMSTORE5_LIGHTS_ALLOWANCE | SMSTORE5 | 0.0000 | 174.19 | 0.00 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE6_LIGHTS | SMSTORE6 | 13.1675 | 174.19 | 2293.69 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 168.00 | 71.66 | 0.0000 | Y | 30.85 |
SMSTORE6_LIGHTS_ALLOWANCE | SMSTORE6 | 0.0000 | 174.19 | 0.00 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE7_LIGHTS | SMSTORE7 | 13.1675 | 174.19 | 2293.69 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 168.00 | 71.66 | 0.0000 | Y | 30.85 |
SMSTORE7_LIGHTS_ALLOWANCE | SMSTORE7 | 0.0000 | 174.19 | 0.00 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE8_LIGHTS | SMSTORE8 | 13.1675 | 174.19 | 2293.69 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 168.00 | 71.66 | 0.0000 | Y | 30.85 |
SMSTORE8_LIGHTS_ALLOWANCE | SMSTORE8 | 0.0000 | 174.19 | 0.00 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
Interior Lighting Total | 7.8548 | 4180.64 | 32838.07 | 502.03 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 314.61 | AstronomicalClock | - | 41.75 | 41.75 | 2.47 | |
EXTERIOR_LIGHTS_B | 6630.02 | AstronomicalClock | - | 83.75 | 71.15 | 88.55 | |
Exterior Lighting Total | 6944.63 | 91.02 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2020-06-03 19:21:12
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 51734.55 | 37599.64 | 14134.91 | 0.73 | 3.73 | |||
PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 26997.92 | 19679.86 | 7318.06 | 0.73 | 3.80 | |||
PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 26873.08 | 19583.22 | 7289.86 | 0.73 | 3.80 | |||
PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 26925.41 | 19623.51 | 7301.90 | 0.73 | 3.80 | |||
PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 26843.13 | 19559.78 | 7283.35 | 0.73 | 3.80 | |||
PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 49294.01 | 35713.02 | 13580.99 | 0.72 | 3.73 | |||
PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 25933.27 | 18856.34 | 7076.93 | 0.73 | 3.80 | |||
PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 25839.50 | 18784.02 | 7055.48 | 0.73 | 3.80 | |||
PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 25854.61 | 18795.53 | 7059.08 | 0.73 | 3.80 | |||
PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 27549.62 | 20139.05 | 7410.57 | 0.73 | 3.80 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | 49757.7 | 11.42 | ||||
PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | 25958.9 | 33.76 | ||||
PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | 25839.6 | 45.49 | ||||
PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | 25889.6 | 56.98 | ||||
PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | 25811.0 | 68.73 | ||||
PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | 47424.8 | 48.39 | ||||
PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | 24941.2 | 104.81 | ||||
PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | 24851.6 | 116.79 | ||||
PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | 24866.0 | 128.31 | ||||
PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | 26482.1 | 131.75 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
PSZ-AC_1:1_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 63210.34 | 0.80 | |
PSZ-AC_2:2_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 33042.67 | 0.80 | |
PSZ-AC_3:3_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 32885.67 | 0.80 | |
PSZ-AC_4:4_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 32950.97 | 0.80 | |
PSZ-AC_5:5_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 32847.98 | 0.80 | |
PSZ-AC_6:6_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 60153.02 | 0.80 | |
PSZ-AC_7:7_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 31708.20 | 0.80 | |
PSZ-AC_8:8_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 31590.89 | 0.80 | |
PSZ-AC_9:9_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 31609.66 | 0.80 | |
PSZ-AC_10:10_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 33853.41 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 2.51 | 2690.45 | 1070.05 | 1.00 | 1.28 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:30:00 |
PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.32 | 1463.30 | 1107.16 | 1.00 | 1.34 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 |
PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.31 | 1455.50 | 1107.16 | 1.00 | 1.34 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:50:00 |
PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.32 | 1458.74 | 1107.16 | 1.00 | 1.34 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:50:00 |
PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.31 | 1453.62 | 1107.16 | 1.00 | 1.34 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:50:00 |
PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 2.38 | 2543.62 | 1070.05 | 1.00 | 1.29 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:40:00 |
PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.26 | 1396.99 | 1107.16 | 1.00 | 1.35 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:40:00 |
PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.26 | 1391.16 | 1107.16 | 1.00 | 1.35 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:40:00 |
PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.26 | 1392.09 | 1107.16 | 1.00 | 1.35 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:40:00 |
PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.36 | 1503.58 | 1107.16 | 1.00 | 1.33 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
GAS TANK1 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK2 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK3 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK4 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK5 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK6 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK7 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:21:12
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
LGSTORE1 | 27755.43 | 33306.51 | 95.60 | 2.095 | 2.514 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:30:00 | 23.89 | 23.89 | 0.00752 | 42.00 | 0.00911 | 0.411 | 0.00 |
SMSTORE1 | 14589.74 | 17507.69 | 100.51 | 1.101 | 1.322 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | 23.89 | 23.89 | 0.00752 | 42.00 | 0.00911 | 0.206 | 0.00 |
SMSTORE2 | 14511.96 | 17414.35 | 99.97 | 1.096 | 1.315 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:50:00 | 23.89 | 23.89 | 0.00753 | 41.92 | 0.00911 | 0.206 | 0.00 |
SMSTORE3 | 14544.31 | 17453.17 | 100.19 | 1.098 | 1.318 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:50:00 | 23.89 | 23.89 | 0.00753 | 41.92 | 0.00911 | 0.206 | 0.00 |
SMSTORE4 | 14493.29 | 17391.95 | 99.84 | 1.094 | 1.313 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:50:00 | 23.89 | 23.89 | 0.00753 | 41.92 | 0.00911 | 0.206 | 0.00 |
LGSTORE2 | 26240.85 | 31489.02 | 90.39 | 1.981 | 2.377 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:40:00 | 23.89 | 23.89 | 0.00754 | 41.84 | 0.00911 | 0.411 | 0.00 |
SMSTORE5 | 13928.65 | 16714.38 | 95.95 | 1.051 | 1.262 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:40:00 | 23.89 | 23.89 | 0.00754 | 41.84 | 0.00911 | 0.206 | 0.00 |
SMSTORE6 | 13870.53 | 16644.64 | 95.55 | 1.047 | 1.257 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:40:00 | 23.89 | 23.89 | 0.00755 | 41.84 | 0.00911 | 0.206 | 0.00 |
SMSTORE7 | 13879.83 | 16655.80 | 95.62 | 1.048 | 1.257 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:40:00 | 23.89 | 23.89 | 0.00755 | 41.84 | 0.00911 | 0.206 | 0.00 |
SMSTORE8 | 14992.04 | 17990.45 | 103.28 | 1.132 | 1.358 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:00:00 | 23.89 | 23.89 | 0.00752 | 41.52 | 0.00911 | 0.206 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
LGSTORE1 | 13243.63 | 15892.36 | 45.62 | 0.586 | 0.703 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00732 | 6.30 | 0.00607 | 0.411 | 0.00 |
SMSTORE1 | 6867.46 | 8240.96 | 47.31 | 0.304 | 0.364 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00726 | 6.30 | 0.00607 | 0.206 | 0.00 |
SMSTORE2 | 6959.31 | 8351.17 | 47.94 | 0.308 | 0.369 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00727 | 6.30 | 0.00607 | 0.206 | 0.00 |
SMSTORE3 | 7024.97 | 8429.97 | 48.39 | 0.311 | 0.373 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00727 | 6.30 | 0.00607 | 0.206 | 0.00 |
SMSTORE4 | 7161.27 | 8593.52 | 49.33 | 0.317 | 0.380 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00728 | 6.30 | 0.00607 | 0.206 | 0.00 |
LGSTORE2 | 13459.80 | 16151.77 | 46.36 | 0.595 | 0.714 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00732 | 6.30 | 0.00607 | 0.411 | 0.00 |
SMSTORE5 | 7327.07 | 8792.49 | 50.48 | 0.324 | 0.389 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00728 | 6.30 | 0.00607 | 0.206 | 0.00 |
SMSTORE6 | 7321.47 | 8785.77 | 50.44 | 0.324 | 0.389 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00728 | 6.30 | 0.00607 | 0.206 | 0.00 |
SMSTORE7 | 7483.96 | 8980.76 | 51.56 | 0.331 | 0.397 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00729 | 6.30 | 0.00607 | 0.206 | 0.00 |
SMSTORE8 | 8205.63 | 9846.75 | 56.53 | 0.363 | 0.435 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00732 | 6.30 | 0.00607 | 0.206 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC_1:1 | 2.51 | 2.51 | 0.70 | 0.70 | 2.5143 | 2.5143 | 2.5143 | 1.0000 | 1.0000 |
PSZ-AC_2:2 | 1.32 | 1.32 | 0.36 | 0.36 | 1.3217 | 1.3217 | 1.3217 | 1.0000 | 1.0000 |
PSZ-AC_3:3 | 1.31 | 1.31 | 0.37 | 0.37 | 1.3146 | 1.3146 | 1.3146 | 1.0000 | 1.0000 |
PSZ-AC_4:4 | 1.32 | 1.32 | 0.37 | 0.37 | 1.3176 | 1.3176 | 1.3176 | 1.0000 | 1.0000 |
PSZ-AC_5:5 | 1.31 | 1.31 | 0.38 | 0.38 | 1.3129 | 1.3129 | 1.3129 | 1.0000 | 1.0000 |
PSZ-AC_6:6 | 2.38 | 2.38 | 0.71 | 0.71 | 2.3771 | 2.3771 | 2.3771 | 1.0000 | 1.0000 |
PSZ-AC_7:7 | 1.26 | 1.26 | 0.39 | 0.39 | 1.2618 | 1.2618 | 1.2618 | 1.0000 | 1.0000 |
PSZ-AC_8:8 | 1.26 | 1.26 | 0.39 | 0.39 | 1.2565 | 1.2565 | 1.2565 | 1.0000 | 1.0000 |
PSZ-AC_9:9 | 1.26 | 1.26 | 0.40 | 0.40 | 1.2574 | 1.2574 | 1.2574 | 1.0000 | 1.0000 |
PSZ-AC_10:10 | 1.36 | 1.36 | 0.44 | 0.44 | 1.3581 | 1.3581 | 1.3581 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_1:1 | 25867.275 | 0.000 | 2.514320 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:30:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:30:00 | 25867.28 | 25867.28 | 2.514320 | 26.85 | 16.49 | 0.00777698 | 12.80 | 11.87 | 0.00850000 | 42.00 | 0.00911023 | 22.20 | 16.3644 | 23.89 | 0.00751611 | 39.7686 | 27755.43 | 0.00 | -999.00 | -999.00 |
PSZ-AC_1:1_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_1:1 | 63210.343 | 63210.343 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 63210.34 | 63210.34 | 2.514324 | 12.44 | 9.74 | 0.00658917 | 40.00 | 20.85 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 16.3644 | 21.11 | 0.00731892 | 45.8639 | 13243.63 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_2:2 | 13498.960 | 0.000 | 1.321670 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | 13498.96 | 13498.96 | 1.321670 | 26.71 | 16.43 | 0.00777115 | 12.80 | 11.87 | 0.00850000 | 42.00 | 0.00911023 | 22.20 | 15.5657 | 23.89 | 0.00752428 | 39.8115 | 14589.74 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_2:2 | 33042.670 | 33042.670 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 33042.67 | 33042.67 | 1.321670 | 12.75 | 9.87 | 0.00659046 | 40.00 | 20.85 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 15.5657 | 21.11 | 0.00726196 | 45.5115 | 6867.46 | 0.00 | -999.00 | -999.00 |
PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_3:3 | 13436.540 | 0.000 | 1.314620 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:50:00 | 13436.54 | 13436.54 | 1.314620 | 26.72 | 16.44 | 0.00777461 | 12.80 | 11.87 | 0.00850000 | 42.00 | 0.00911023 | 22.20 | 15.6491 | 23.89 | 0.00752664 | 39.8238 | 14509.12 | 0.00 | -999.00 | -999.00 |
PSZ-AC_3:3_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_3:3 | 32885.669 | 32885.669 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 32885.67 | 32885.67 | 1.314623 | 12.86 | 9.93 | 0.00660071 | 40.00 | 20.85 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 15.6491 | 21.11 | 0.00726509 | 45.5309 | 6959.31 | 0.00 | -999.00 | -999.00 |
PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_4:4 | 13462.705 | 0.000 | 1.317550 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:50:00 | 13462.70 | 13462.70 | 1.317550 | 26.72 | 16.44 | 0.00777326 | 12.80 | 11.87 | 0.00850000 | 42.00 | 0.00911023 | 22.20 | 15.6143 | 23.89 | 0.00752566 | 39.8187 | 14540.86 | 0.00 | -999.00 | -999.00 |
PSZ-AC_4:4_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_4:4 | 32950.969 | 32950.969 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 32950.97 | 32950.97 | 1.317554 | 12.94 | 9.98 | 0.00660853 | 40.00 | 20.85 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 15.6143 | 21.11 | 0.00726867 | 45.5532 | 7024.97 | 0.00 | -999.00 | -999.00 |
PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_5:5 | 13421.565 | 0.000 | 1.312930 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:50:00 | 13421.57 | 13421.57 | 1.312930 | 26.73 | 16.45 | 0.00777545 | 12.80 | 11.87 | 0.00850000 | 42.00 | 0.00911023 | 22.20 | 15.6693 | 23.89 | 0.00752722 | 39.8268 | 14489.74 | 0.00 | -999.00 | -999.00 |
PSZ-AC_5:5_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_5:5 | 32847.982 | 32847.982 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 32847.98 | 32847.98 | 1.312932 | 13.09 | 10.06 | 0.00662462 | 40.00 | 20.85 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 15.6693 | 21.11 | 0.00727637 | 45.6009 | 7161.27 | 0.00 | -999.00 | -999.00 |
PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_6:6 | 24647.005 | 0.000 | 2.377110 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:40:00 | 24647.01 | 24647.01 | 2.377110 | 27.02 | 16.58 | 0.00781159 | 12.80 | 11.87 | 0.00850000 | 42.00 | 0.00911023 | 22.20 | 17.3090 | 23.89 | 0.00753904 | 39.8885 | 26227.58 | 0.00 | -999.00 | -999.00 |
PSZ-AC_6:6_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_6:6 | 60153.024 | 60153.024 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 60153.02 | 60153.02 | 2.377111 | 12.58 | 9.81 | 0.00660273 | 40.00 | 20.85 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 17.3090 | 21.11 | 0.00732326 | 45.8908 | 13459.80 | 0.00 | -999.00 | -999.00 |
PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_7:7 | 12966.635 | 0.000 | 1.261780 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:40:00 | 12966.64 | 12966.64 | 1.261780 | 26.84 | 16.51 | 0.00780071 | 12.80 | 11.87 | 0.00850000 | 42.00 | 0.00911023 | 22.20 | 16.3045 | 23.89 | 0.00754484 | 39.9189 | 13920.18 | 0.00 | -999.00 | -999.00 |
PSZ-AC_7:7_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_7:7 | 31708.204 | 31708.204 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 31708.20 | 31708.20 | 1.261779 | 13.27 | 10.16 | 0.00664307 | 40.00 | 20.85 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 16.3045 | 21.11 | 0.00728423 | 45.6496 | 7327.07 | 0.00 | -999.00 | -999.00 |
PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_8:8 | 12919.750 | 0.000 | 1.256510 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:40:00 | 12919.75 | 12919.75 | 1.256510 | 26.85 | 16.51 | 0.00780338 | 12.80 | 11.87 | 0.00850000 | 42.00 | 0.00911023 | 22.20 | 16.3729 | 23.89 | 0.00754675 | 39.9289 | 13862.02 | 0.00 | -999.00 | -999.00 |
PSZ-AC_8:8_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_8:8 | 31590.892 | 31590.892 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 31590.89 | 31590.89 | 1.256514 | 13.27 | 10.16 | 0.00664247 | 40.00 | 20.85 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 16.3728 | 21.11 | 0.00728399 | 45.6481 | 7321.47 | 0.00 | -999.00 | -999.00 |
PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_9:9 | 12927.305 | 0.000 | 1.257360 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:40:00 | 12927.31 | 12927.31 | 1.257360 | 26.85 | 16.51 | 0.00780297 | 12.80 | 11.87 | 0.00850000 | 42.00 | 0.00911023 | 22.20 | 16.3618 | 23.89 | 0.00754644 | 39.9273 | 13870.90 | 0.00 | -999.00 | -999.00 |
PSZ-AC_9:9_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_9:9 | 31609.659 | 31609.659 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 31609.66 | 31609.66 | 1.257356 | 13.44 | 10.25 | 0.00666045 | 40.00 | 20.85 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 16.3618 | 21.11 | 0.00729239 | 45.7002 | 7483.96 | 0.00 | -999.00 | -999.00 |
PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_10:10 | 13774.810 | 0.000 | 1.358050 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:40:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:00:00 | 13774.81 | 13774.81 | 1.358050 | 26.61 | 16.39 | 0.00775919 | 12.80 | 11.87 | 0.00850000 | 41.84 | 0.00911022 | 22.15 | 15.1487 | 23.89 | 0.00751641 | 39.7703 | 14915.87 | 0.00 | -999.00 | -999.00 |
PSZ-AC_10:10_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_10:10 | 33853.415 | 33853.415 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 33853.41 | 33853.41 | 1.358054 | 14.11 | 10.61 | 0.00673249 | 40.00 | 20.85 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 15.1486 | 21.11 | 0.00732360 | 45.8936 | 8205.63 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2020-06-03 19:21:12
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | LGSTORE1 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 25867.275 | 0.000 | 2.514320 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.2970 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:30:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:30:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:30:00 | 25867.28 | 25867.28 | 1.0000 | 2.95127226 | 2.514320 | 26.85 | 16.49 | 0.00777698 | 46819.4 | 12.80 | 11.87 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 25867.28 | 42.00 | 0.00911023 | 22.20 | 0.41145340 | 16.3644 | 23.89 | 0.00751611 | 23.89 | 0.00751611 | 39.7686 | 27755.43 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_1:1_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | LGSTORE1 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 63210.343 | 63210.343 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.514324 | 2.95127720 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 63210.34 | 63210.34 | 1.0000 | 2.95127720 | 2.514324 | 12.44 | 9.74 | 0.00658917 | 29131.5 | 40.00 | 20.85 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 63210.34 | 6.30 | 0.00607234 | 6.30 | 0.41145340 | 16.3644 | 21.11 | 0.00731892 | 21.11 | 0.00731892 | 45.8639 | 13243.63 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | SMSTORE1 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 13498.960 | 0.000 | 1.321670 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.2862 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | 13498.96 | 13498.96 | 1.0000 | 1.55135703 | 1.321670 | 26.71 | 16.43 | 0.00777115 | 46657.0 | 12.80 | 11.87 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 13498.96 | 42.00 | 0.00911023 | 22.20 | 0.20572670 | 15.5657 | 23.89 | 0.00752428 | 23.89 | 0.00752428 | 39.8115 | 14589.74 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | SMSTORE1 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 33042.670 | 33042.670 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.321670 | 1.55135728 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 33042.67 | 33042.67 | 1.0000 | 1.55135728 | 1.321670 | 12.75 | 9.87 | 0.00659046 | 29450.1 | 40.00 | 20.85 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 33042.67 | 6.30 | 0.00607234 | 6.30 | 0.20572670 | 15.5657 | 21.11 | 0.00726196 | 21.11 | 0.00726196 | 45.5115 | 6867.46 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_3:3 | SMSTORE2 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 13436.540 | 0.000 | 1.314620 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.2926 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:50:00 | 13436.54 | 13436.54 | 1.0000 | 1.54308184 | 1.314620 | 26.72 | 16.44 | 0.00777461 | 46681.9 | 12.80 | 11.87 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 13436.54 | 42.00 | 0.00911023 | 22.20 | 0.20572670 | 15.6491 | 23.89 | 0.00752677 | 23.89 | 0.00752664 | 39.8238 | 14509.12 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_3:3_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_3:3 | SMSTORE2 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 32885.669 | 32885.669 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.314623 | 1.54308548 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 32885.67 | 32885.67 | 1.0000 | 1.54308548 | 1.314623 | 12.86 | 9.93 | 0.00660071 | 29588.1 | 40.00 | 20.85 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 32885.67 | 6.30 | 0.00607234 | 6.30 | 0.20572670 | 15.6491 | 21.11 | 0.00726509 | 21.11 | 0.00726509 | 45.5309 | 6959.31 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_4:4 | SMSTORE3 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 13462.705 | 0.000 | 1.317550 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.2901 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:50:00 | 13462.70 | 13462.70 | 1.0000 | 1.54652103 | 1.317550 | 26.72 | 16.44 | 0.00777326 | 46672.1 | 12.80 | 11.87 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 13462.70 | 42.00 | 0.00911023 | 22.20 | 0.20572670 | 15.6143 | 23.89 | 0.00752581 | 23.89 | 0.00752566 | 39.8187 | 14540.86 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_4:4_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_4:4 | SMSTORE3 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 32950.969 | 32950.969 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.317554 | 1.54652544 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 32950.97 | 32950.97 | 1.0000 | 1.54652544 | 1.317554 | 12.94 | 9.98 | 0.00660853 | 29686.3 | 40.00 | 20.85 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 32950.97 | 6.30 | 0.00607234 | 6.30 | 0.20572670 | 15.6143 | 21.11 | 0.00726867 | 21.11 | 0.00726867 | 45.5532 | 7024.97 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_5:5 | SMSTORE4 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 13421.565 | 0.000 | 1.312930 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.2942 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:50:00 | 13421.57 | 13421.57 | 1.0000 | 1.54109814 | 1.312930 | 26.73 | 16.45 | 0.00777545 | 46687.9 | 12.80 | 11.87 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 13421.57 | 42.00 | 0.00911023 | 22.20 | 0.20572670 | 15.6693 | 23.89 | 0.00752737 | 23.89 | 0.00752722 | 39.8268 | 14489.74 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_5:5_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_5:5 | SMSTORE4 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 32847.982 | 32847.982 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.312932 | 1.54110032 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 32847.98 | 32847.98 | 1.0000 | 1.54110032 | 1.312932 | 13.09 | 10.06 | 0.00662462 | 29885.1 | 40.00 | 20.85 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 32847.98 | 6.30 | 0.00607234 | 6.30 | 0.20572670 | 15.6693 | 21.11 | 0.00727637 | 21.11 | 0.00727637 | 45.6009 | 7161.27 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_6:6 | LGSTORE2 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 24647.005 | 0.000 | 2.377110 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.3614 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:40:00 | 24647.01 | 24647.01 | 1.0000 | 2.79021716 | 2.377110 | 27.02 | 16.58 | 0.00781159 | 47083.8 | 12.80 | 11.87 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 24647.01 | 42.00 | 0.00911023 | 22.20 | 0.41145340 | 17.3090 | 23.89 | 0.00753960 | 23.89 | 0.00753904 | 39.8885 | 26227.58 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_6:6_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_6:6 | LGSTORE2 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 60153.024 | 60153.024 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.377111 | 2.79021789 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 60153.02 | 60153.02 | 1.0000 | 2.79021789 | 2.377111 | 12.58 | 9.81 | 0.00660273 | 29307.3 | 40.00 | 20.85 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 60153.02 | 6.30 | 0.00607234 | 6.30 | 0.41145340 | 17.3090 | 21.11 | 0.00732326 | 21.11 | 0.00732326 | 45.8908 | 13459.80 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_7:7 | SMSTORE5 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 12966.635 | 0.000 | 1.261780 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.3411 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:40:00 | 12966.64 | 12966.64 | 1.0000 | 1.48105902 | 1.261780 | 26.84 | 16.51 | 0.00780071 | 46870.7 | 12.80 | 11.87 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 12966.64 | 42.00 | 0.00911023 | 22.20 | 0.20572670 | 16.3045 | 23.89 | 0.00754542 | 23.89 | 0.00754484 | 39.9189 | 13920.18 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_7:7_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_7:7 | SMSTORE5 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 31708.204 | 31708.204 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.261779 | 1.48105771 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 31708.20 | 31708.20 | 1.0000 | 1.48105771 | 1.261779 | 13.27 | 10.16 | 0.00664307 | 30116.2 | 40.00 | 20.85 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 31708.20 | 6.30 | 0.00607234 | 6.30 | 0.20572670 | 16.3045 | 21.11 | 0.00728423 | 21.11 | 0.00728423 | 45.6496 | 7327.07 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_8:8 | SMSTORE6 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 12919.750 | 0.000 | 1.256510 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.3461 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:40:00 | 12919.75 | 12919.75 | 1.0000 | 1.47487317 | 1.256510 | 26.85 | 16.51 | 0.00780338 | 46890.1 | 12.80 | 11.87 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 12919.75 | 42.00 | 0.00911023 | 22.20 | 0.20572670 | 16.3729 | 23.89 | 0.00754733 | 23.89 | 0.00754675 | 39.9289 | 13862.02 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_8:8_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_8:8 | SMSTORE6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 31590.892 | 31590.892 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.256514 | 1.47487785 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 31590.89 | 31590.89 | 1.0000 | 1.47487785 | 1.256514 | 13.27 | 10.16 | 0.00664247 | 30108.6 | 40.00 | 20.85 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 31590.89 | 6.30 | 0.00607234 | 6.30 | 0.20572670 | 16.3728 | 21.11 | 0.00728399 | 21.11 | 0.00728399 | 45.6481 | 7321.47 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_9:9 | SMSTORE7 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 12927.305 | 0.000 | 1.257360 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.3453 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:40:00 | 12927.31 | 12927.31 | 1.0000 | 1.47587089 | 1.257360 | 26.85 | 16.51 | 0.00780297 | 46887.2 | 12.80 | 11.87 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 12927.31 | 42.00 | 0.00911023 | 22.20 | 0.20572670 | 16.3618 | 23.89 | 0.00754704 | 23.89 | 0.00754644 | 39.9273 | 13870.90 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_9:9_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_9:9 | SMSTORE7 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 31609.659 | 31609.659 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.257356 | 1.47586652 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 31609.66 | 31609.66 | 1.0000 | 1.47586652 | 1.257356 | 13.44 | 10.25 | 0.00666045 | 30327.2 | 40.00 | 20.85 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 31609.66 | 6.30 | 0.00607234 | 6.30 | 0.20572670 | 16.3618 | 21.11 | 0.00729239 | 21.11 | 0.00729239 | 45.7002 | 7483.96 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_10:10 | SMSTORE8 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 13774.810 | 0.000 | 1.358050 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.2639 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:40:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:00:00 | 13774.81 | 13774.81 | 1.0000 | 1.59405934 | 1.358050 | 26.61 | 16.39 | 0.00775919 | 46531.4 | 12.80 | 11.87 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 13774.81 | 41.84 | 0.00911022 | 22.15 | 0.20572670 | 15.1487 | 23.89 | 0.00751729 | 23.89 | 0.00751641 | 39.7703 | 14915.87 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_10:10_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_10:10 | SMSTORE8 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 33853.415 | 33853.415 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.358054 | 1.59406410 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 33853.41 | 33853.41 | 1.0000 | 1.59406410 | 1.358054 | 14.11 | 10.61 | 0.00673249 | 31195.4 | 40.00 | 20.85 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 33853.41 | 6.30 | 0.00607234 | 6.30 | 0.20572670 | 15.1486 | 21.11 | 0.00732360 | 21.11 | 0.00732360 | 45.8936 | 8205.63 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2020-06-03 19:21:12
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
LGSTORE1 | 4385.00 | 1572.00 | 1102.00 |
SMSTORE1 | 4260.67 | 1258.17 | 924.33 |
SMSTORE2 | 3233.33 | 1336.17 | 977.17 |
SMSTORE3 | 3208.67 | 1360.67 | 963.83 |
SMSTORE4 | 3167.67 | 1423.00 | 977.00 |
LGSTORE2 | 2833.67 | 1398.17 | 917.33 |
SMSTORE5 | 2742.67 | 1438.00 | 925.50 |
SMSTORE6 | 2722.83 | 1456.50 | 927.83 |
SMSTORE7 | 2709.17 | 1486.50 | 927.17 |
SMSTORE8 | 2738.00 | 1460.00 | 865.17 |
Facility | 4504.67 | 2168.50 | 1311.33 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
LGSTORE1 | 0.00 | 15.17 | 0.00 | 15.17 |
SMSTORE1 | 0.00 | 10.33 | 0.00 | 10.33 |
SMSTORE2 | 0.00 | 17.33 | 0.00 | 17.33 |
SMSTORE3 | 0.00 | 17.50 | 0.00 | 17.50 |
SMSTORE4 | 0.00 | 17.67 | 0.00 | 17.67 |
LGSTORE2 | 0.00 | 17.50 | 0.00 | 17.50 |
SMSTORE5 | 0.00 | 16.17 | 0.00 | 16.17 |
SMSTORE6 | 0.00 | 16.33 | 0.00 | 16.33 |
SMSTORE7 | 0.00 | 16.33 | 0.00 | 16.33 |
SMSTORE8 | 0.00 | 16.17 | 0.00 | 16.17 |
Facility | 0.00 | 37.67 | 0.00 | 37.67 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2020-06-03 19:21:12
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
LGSTORE1 | 9.03 | 30.00 | 1805.20 | 0.848 | 0.333 | 0.000 | 0.000 |
SMSTORE1 | 4.51 | 15.00 | 902.60 | 0.702 | 0.375 | 0.000 | 0.000 |
SMSTORE2 | 3.78 | 15.00 | 902.60 | 0.848 | 0.494 | 0.000 | 0.000 |
SMSTORE3 | 3.78 | 15.00 | 902.60 | 0.848 | 0.494 | 0.000 | 0.000 |
SMSTORE4 | 3.78 | 15.00 | 902.60 | 0.848 | 0.494 | 0.000 | 0.000 |
LGSTORE2 | 13.22 | 30.00 | 1805.20 | 0.848 | 0.462 | 0.000 | 0.000 |
SMSTORE5 | 6.61 | 15.00 | 902.60 | 0.848 | 0.527 | 0.000 | 0.000 |
SMSTORE6 | 6.61 | 15.00 | 902.60 | 0.848 | 0.527 | 0.000 | 0.000 |
SMSTORE7 | 6.61 | 15.00 | 902.60 | 0.848 | 0.527 | 0.000 | 0.000 |
SMSTORE8 | 6.61 | 15.00 | 902.60 | 0.848 | 0.536 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
LGSTORE1 | 9.03 | 30.00 | 1805.20 | 0.780 | 0.000 | 0.000 | 0.000 |
SMSTORE1 | 4.51 | 15.00 | 902.60 | 0.000 | 0.000 | 0.000 | 0.000 |
SMSTORE2 | 3.78 | 15.00 | 902.60 | 0.779 | 0.000 | 0.000 | 0.000 |
SMSTORE3 | 3.78 | 15.00 | 902.60 | 0.778 | 0.000 | 0.000 | 0.000 |
SMSTORE4 | 3.78 | 15.00 | 902.60 | 0.778 | 0.000 | 0.000 | 0.000 |
LGSTORE2 | 13.22 | 30.00 | 1805.20 | 0.779 | 0.000 | 0.000 | 0.000 |
SMSTORE5 | 6.61 | 15.00 | 902.60 | 0.779 | 0.000 | 0.000 | 0.000 |
SMSTORE6 | 6.61 | 15.00 | 902.60 | 0.779 | 0.000 | 0.000 | 0.000 |
SMSTORE7 | 6.61 | 15.00 | 902.60 | 0.778 | 0.000 | 0.000 | 0.000 |
SMSTORE8 | 6.61 | 15.00 | 902.60 | 0.777 | 0.000 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2020-06-03 19:21:12
Surfaces by ClassTotal | Outdoors | |
Wall | 40 | 22 |
Floor | 10 | 10 |
Roof | 10 | 10 |
Internal Mass | 10 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 36 | 36 |
Door | 12 | 12 |
Glass Door | 12 | 12 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 10 |
Conditioned Zones | 10 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 0 |
Defaulted Fields | 0 |
Fields with Defaults | 0 |
Autosized Fields | 0 |
Autosizable Fields | 0 |
Autocalculated Fields | 0 |
Autocalculatable Fields | 0 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2020-06-03 19:21:12
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1394.29 | 3309.32 | 01-JAN-08:00 | 143981.46 | 22-JUN-15:10 |
Electricity:Building | 630.75 | 2091.32 | 01-JAN-00:10 | 39285.70 | 01-JAN-11:10 |
Electricity:Zone:LGSTORE1 | 144.52 | 394.83 | 01-JAN-00:10 | 7426.96 | 01-JAN-10:10 |
InteriorLights:Electricity | 502.03 | 1641.90 | 01-JAN-00:10 | 31196.17 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:LGSTORE1 | 118.16 | 319.93 | 01-JAN-00:10 | 6078.71 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity | 502.03 | 1641.90 | 01-JAN-00:10 | 31196.17 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE1 | 76.90 | 209.98 | 01-JAN-00:10 | 3952.17 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE1 | 63.72 | 172.53 | 01-JAN-00:10 | 3278.04 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE2 | 55.48 | 191.23 | 01-JAN-00:10 | 3595.92 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE2 | 45.01 | 153.78 | 01-JAN-00:10 | 2921.79 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE3 | 55.48 | 191.23 | 01-JAN-00:10 | 3595.92 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE3 | 45.01 | 153.78 | 01-JAN-00:10 | 2921.79 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE4 | 55.48 | 191.23 | 01-JAN-00:10 | 3595.92 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE4 | 45.01 | 153.78 | 01-JAN-00:10 | 2921.79 | 01-JAN-10:10 |
Electricity:Zone:LGSTORE2 | 80.97 | 304.27 | 01-JAN-00:10 | 5706.27 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:LGSTORE2 | 61.71 | 229.37 | 01-JAN-00:10 | 4358.02 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE5 | 40.48 | 152.14 | 01-JAN-00:10 | 2853.14 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE5 | 30.85 | 114.68 | 01-JAN-00:10 | 2179.01 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE6 | 40.48 | 152.14 | 01-JAN-00:10 | 2853.14 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE6 | 30.85 | 114.68 | 01-JAN-00:10 | 2179.01 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE7 | 40.48 | 152.14 | 01-JAN-00:10 | 2853.14 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE7 | 30.85 | 114.68 | 01-JAN-00:10 | 2179.01 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE8 | 40.48 | 152.14 | 01-JAN-00:10 | 2853.14 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE8 | 30.85 | 114.68 | 01-JAN-00:10 | 2179.01 | 01-JAN-11:10 |
InteriorEquipment:Electricity | 128.72 | 449.42 | 01-JAN-00:10 | 8089.53 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:LGSTORE1 | 26.36 | 74.90 | 01-JAN-00:10 | 1348.26 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity | 128.72 | 449.42 | 01-JAN-00:10 | 8089.53 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE1 | 13.18 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE2 | 10.47 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE3 | 10.47 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE4 | 10.47 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:LGSTORE2 | 19.26 | 74.90 | 01-JAN-00:10 | 1348.26 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE5 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE6 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE7 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE8 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
Electricity:Plant | 58.82 | 1218.00 | 03-JAN-08:10 | 11784.25 | 21-DEC-15:20 |
WaterSystems:Electricity | 58.82 | 1218.00 | 03-JAN-08:10 | 11784.25 | 21-DEC-15:20 |
Water Heater:WaterSystems:Electricity | 58.82 | 1218.00 | 03-JAN-08:10 | 11784.25 | 21-DEC-15:20 |
ElectricityPurchased:Facility | 1394.29 | 3309.32 | 01-JAN-08:00 | 143981.46 | 22-JUN-15:10 |
ElectricityPurchased:Plant | 1394.29 | 3309.32 | 01-JAN-08:00 | 143981.46 | 22-JUN-15:10 |
Cogeneration:ElectricityPurchased | 1394.29 | 3309.32 | 01-JAN-08:00 | 143981.46 | 22-JUN-15:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1394.29 | 3309.32 | 01-JAN-08:00 | 143981.46 | 22-JUN-15:10 |
ElectricityNet:Plant | 1394.29 | 3309.32 | 01-JAN-08:00 | 143981.46 | 22-JUN-15:10 |
Cogeneration:ElectricityNet | 1394.29 | 3309.32 | 01-JAN-08:00 | 143981.46 | 22-JUN-15:10 |
Electricity:HVAC | 613.70 | 0.00 | 01-JAN-00:10 | 100408.36 | 22-JUN-16:10 |
Fans:Electricity | 133.57 | 0.00 | 01-JAN-00:10 | 16042.25 | 01-JUL-15:00 |
General:Fans:Electricity | 133.57 | 0.00 | 01-JAN-00:10 | 16042.25 | 01-JUL-15:00 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 480.13 | 0.00 | 01-JAN-00:10 | 84630.47 | 22-JUN-16:10 |
ExteriorLights:Electricity | 91.02 | 0.00 | 01-JAN-07:20 | 6944.63 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 91.02 | 0.00 | 01-JAN-07:20 | 6944.63 | 01-JAN-06:10 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Gas:Facility | 2.11 | 0.00 | 01-JAN-00:10 | 102906.53 | 02-JAN-09:10 |
Gas:HVAC | 2.11 | 0.00 | 01-JAN-00:10 | 102906.53 | 02-JAN-09:10 |
Heating:Gas | 2.11 | 0.00 | 01-JAN-00:10 | 102906.53 | 02-JAN-09:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water:Plant | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
WaterSystems:Water | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water Heater:WaterSystems:Water | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
MainsWater:Facility | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
MainsWater:Plant | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
WaterSystems:MainsWater | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water Heater:WaterSystems:MainsWater | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:Facility | 2851.31 | 0.00 | 01-JAN-00:10 | 436868.92 | 01-JUL-15:00 |
EnergyTransfer:Building | 1004.64 | 0.00 | 01-JAN-00:10 | 149820.63 | 12-JUN-14:20 |
EnergyTransfer:Zone:LGSTORE1 | 206.22 | 0.00 | 01-JAN-00:10 | 24412.10 | 08-JUN-16:10 |
Heating:EnergyTransfer | 8.32 | 0.00 | 01-JAN-00:10 | 60792.01 | 02-JAN-09:10 |
Heating:EnergyTransfer:Zone:LGSTORE1 | 0.32 | 0.00 | 01-JAN-00:10 | 9376.60 | 02-JAN-09:10 |
Cooling:EnergyTransfer | 996.32 | 0.00 | 01-JAN-00:10 | 149820.63 | 12-JUN-14:20 |
Cooling:EnergyTransfer:Zone:LGSTORE1 | 205.90 | 0.00 | 01-JAN-00:10 | 24412.10 | 08-JUN-16:10 |
EnergyTransfer:Zone:SMSTORE1 | 107.95 | 0.00 | 01-JAN-00:10 | 12498.11 | 08-JUN-16:10 |
Heating:EnergyTransfer:Zone:SMSTORE1 | 0.15 | 0.00 | 01-JAN-00:10 | 3764.91 | 02-JAN-09:10 |
Cooling:EnergyTransfer:Zone:SMSTORE1 | 107.80 | 0.00 | 01-JAN-00:10 | 12498.11 | 08-JUN-16:10 |
EnergyTransfer:Zone:SMSTORE2 | 84.10 | 0.00 | 01-JAN-00:10 | 12654.88 | 12-JUN-14:00 |
Heating:EnergyTransfer:Zone:SMSTORE2 | 1.32 | 0.00 | 01-JAN-00:10 | 5409.35 | 02-JAN-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE2 | 82.78 | 0.00 | 01-JAN-00:10 | 12654.88 | 12-JUN-14:00 |
EnergyTransfer:Zone:SMSTORE3 | 84.17 | 0.00 | 01-JAN-00:10 | 12803.84 | 12-JUN-14:00 |
Heating:EnergyTransfer:Zone:SMSTORE3 | 1.32 | 0.00 | 01-JAN-00:10 | 7009.81 | 02-JAN-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE3 | 82.85 | 0.00 | 01-JAN-00:10 | 12803.84 | 12-JUN-14:00 |
EnergyTransfer:Zone:SMSTORE4 | 82.56 | 0.00 | 01-JAN-00:10 | 12788.31 | 12-JUN-14:00 |
Heating:EnergyTransfer:Zone:SMSTORE4 | 1.36 | 0.00 | 01-JAN-00:10 | 7849.43 | 02-JAN-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE4 | 81.20 | 0.00 | 01-JAN-00:10 | 12788.31 | 12-JUN-14:00 |
EnergyTransfer:Zone:LGSTORE2 | 141.55 | 0.00 | 01-JAN-00:10 | 23814.61 | 12-JUN-14:20 |
Heating:EnergyTransfer:Zone:LGSTORE2 | 1.18 | 0.00 | 01-JAN-00:10 | 15099.65 | 02-JAN-09:10 |
Cooling:EnergyTransfer:Zone:LGSTORE2 | 140.37 | 0.00 | 01-JAN-00:10 | 23814.61 | 12-JUN-14:20 |
EnergyTransfer:Zone:SMSTORE5 | 73.77 | 0.00 | 01-JAN-00:10 | 12742.01 | 12-JUN-14:20 |
Heating:EnergyTransfer:Zone:SMSTORE5 | 0.64 | 0.00 | 01-JAN-00:10 | 7912.67 | 02-JAN-09:10 |
Cooling:EnergyTransfer:Zone:SMSTORE5 | 73.13 | 0.00 | 01-JAN-00:10 | 12742.01 | 12-JUN-14:20 |
EnergyTransfer:Zone:SMSTORE6 | 73.10 | 0.00 | 01-JAN-00:10 | 12696.71 | 12-JUN-14:20 |
Heating:EnergyTransfer:Zone:SMSTORE6 | 0.65 | 0.00 | 01-JAN-00:10 | 7940.96 | 02-JAN-09:10 |
Cooling:EnergyTransfer:Zone:SMSTORE6 | 72.45 | 0.00 | 01-JAN-00:10 | 12696.71 | 12-JUN-14:20 |
EnergyTransfer:Zone:SMSTORE7 | 72.52 | 0.00 | 01-JAN-00:10 | 12754.89 | 12-JUN-14:20 |
Heating:EnergyTransfer:Zone:SMSTORE7 | 0.69 | 0.00 | 01-JAN-00:10 | 8026.86 | 02-JAN-09:10 |
Cooling:EnergyTransfer:Zone:SMSTORE7 | 71.83 | 0.00 | 01-JAN-00:10 | 12754.89 | 12-JUN-14:20 |
EnergyTransfer:Zone:SMSTORE8 | 78.70 | 0.00 | 01-JAN-00:10 | 14129.13 | 12-JUN-12:50 |
Heating:EnergyTransfer:Zone:SMSTORE8 | 0.69 | 0.00 | 01-JAN-00:10 | 8108.42 | 02-JAN-09:10 |
Cooling:EnergyTransfer:Zone:SMSTORE8 | 78.01 | 0.00 | 01-JAN-00:10 | 14129.13 | 12-JUN-12:50 |
EnergyTransfer:HVAC | 1846.67 | 0.00 | 01-JAN-00:10 | 318281.01 | 01-JUL-16:00 |
HeatingCoils:EnergyTransfer | 1.69 | 0.00 | 01-JAN-00:10 | 82325.23 | 02-JAN-09:10 |
CoolingCoils:EnergyTransfer | 1844.98 | 0.00 | 01-JAN-00:10 | 318281.01 | 01-JUL-16:00 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2020-06-03 19:21:12
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
LGSTORE1 | 0.000 | 0.000 | 0.320 | -205.892 | 0.000 | 0.000 | 12.412 | 118.163 | 26.357 | 19.935 | 0.000 | 25.203 | 13.228 | 0.000 | -4.609 | 0.000 | -5.117 | -0.001 |
SMSTORE1 | 0.000 | 0.000 | 0.148 | -107.799 | 0.000 | 0.000 | 6.197 | 63.721 | 13.179 | 9.985 | 0.000 | 14.182 | 5.534 | 0.000 | -2.335 | 0.000 | -2.810 | -0.001 |
SMSTORE2 | 0.000 | 0.000 | 1.318 | -82.780 | 0.000 | 0.000 | 3.729 | 45.008 | 10.467 | 9.824 | 0.000 | 14.024 | 3.626 | 0.000 | -2.400 | 0.000 | -2.815 | -0.001 |
SMSTORE3 | 0.000 | 0.000 | 1.318 | -82.851 | 0.000 | 0.000 | 3.730 | 45.008 | 10.467 | 9.816 | 0.000 | 14.020 | 3.679 | 0.000 | -2.391 | 0.000 | -2.795 | -0.000 |
SMSTORE4 | 0.000 | 0.000 | 1.360 | -81.193 | 0.000 | 0.000 | 3.733 | 45.008 | 10.467 | 9.833 | 0.000 | 14.023 | 1.897 | 0.000 | -2.361 | 0.000 | -2.767 | -0.000 |
LGSTORE2 | 0.000 | 0.000 | 1.182 | -140.365 | 0.000 | 0.000 | 12.821 | 61.707 | 19.261 | 19.711 | 0.000 | 24.515 | 10.579 | 0.000 | -4.586 | 0.000 | -4.825 | -0.001 |
SMSTORE5 | 0.000 | 0.000 | 0.644 | -73.129 | 0.000 | 0.000 | 6.412 | 30.853 | 9.631 | 9.886 | 0.000 | 13.983 | 6.709 | 0.000 | -2.272 | 0.000 | -2.718 | -0.001 |
SMSTORE6 | 0.000 | 0.000 | 0.655 | -72.445 | 0.000 | 0.000 | 6.414 | 30.853 | 9.631 | 9.897 | 0.000 | 13.985 | 5.976 | 0.000 | -2.261 | 0.000 | -2.705 | -0.002 |
SMSTORE7 | 0.000 | 0.000 | 0.688 | -71.831 | 0.000 | 0.000 | 6.418 | 30.853 | 9.631 | 9.901 | 0.000 | 13.986 | 5.269 | 0.000 | -2.242 | 0.000 | -2.674 | -0.001 |
SMSTORE8 | 0.000 | 0.000 | 0.690 | -78.011 | 0.000 | 0.000 | 6.422 | 30.853 | 9.631 | 9.847 | 0.000 | 14.335 | 11.333 | 0.000 | -2.205 | 0.000 | -2.896 | -0.002 |
Total Facility | 0.000 | 0.000 | 8.323 | -996.296 | 0.000 | 0.000 | 68.288 | 502.028 | 128.721 | 118.634 | 0.000 | 162.257 | 67.831 | 0.000 | -27.663 | 0.000 | -32.123 | -0.008 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
LGSTORE1 | 08-APR-08:62 | 0.00 | 0.00 | 0.00 | -44270.28 | 0.00 | 0.00 | 89.84 | 3199.32 | 749.03 | 401.41 | 0.00 | 78.64 | 39752.04 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 08-APR-08:62 | 0.00 | 0.00 | 0.00 | -23094.10 | 0.00 | 0.00 | 44.36 | 1725.28 | 374.52 | 197.44 | 0.00 | 39.86 | 20712.64 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 30-APR-08:61 | 0.00 | 0.00 | 0.00 | -23609.59 | 0.00 | 0.00 | 42.92 | 1537.78 | 374.52 | 168.47 | 0.00 | 21.08 | 21464.83 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 30-APR-08:61 | 0.00 | 0.00 | 0.00 | -23694.74 | 0.00 | 0.00 | 42.54 | 1537.78 | 374.52 | 165.81 | 0.00 | 17.59 | 21556.50 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 30-APR-08:61 | 0.00 | 0.00 | 0.00 | -23591.39 | 0.00 | 0.00 | 42.83 | 1537.78 | 374.52 | 166.88 | 0.00 | 20.32 | 21449.06 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 09-APR-09:01 | 0.00 | 0.00 | 0.00 | -42460.44 | 0.00 | 0.00 | 185.55 | 2293.69 | 749.03 | 788.24 | 0.00 | 118.42 | 38325.51 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 20-APR-08:61 | 0.00 | 0.00 | 0.00 | -22314.01 | 0.00 | 0.00 | 92.88 | 1146.85 | 374.52 | 243.73 | 0.00 | 68.90 | 20387.14 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 20-APR-08:61 | 0.00 | 0.00 | 0.00 | -22221.36 | 0.00 | 0.00 | 92.94 | 1146.85 | 374.52 | 244.45 | 0.00 | 69.13 | 20293.48 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 20-APR-08:61 | 0.00 | 0.00 | 0.00 | -22175.61 | 0.00 | 0.00 | 93.49 | 1146.85 | 374.52 | 245.52 | 0.00 | 71.64 | 20243.60 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 09-APR-09:01 | 0.00 | 0.00 | 0.00 | -23536.18 | 0.00 | 0.00 | 93.47 | 1146.85 | 374.52 | 398.68 | 0.00 | 84.19 | 21438.47 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 12-JUN-07:01 | 0.00 | 0.00 | 0.00 | -232209.08 | 0.00 | 0.00 | 242.95 | 5793.92 | 1460.61 | 3680.35 | 0.00 | 4013.08 | 217018.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
LGSTORE1 | 01-JAN-09:01 | 0.00 | 0.00 | 57555.75 | 0.00 | 0.00 | 0.00 | 133.95 | 3199.32 | 749.03 | 571.52 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -786.77 | -61422.80 |
SMSTORE1 | 02-JAN-09:01 | 0.00 | 0.00 | 29904.97 | 0.00 | 0.00 | 0.00 | 65.54 | 1725.28 | 374.52 | 360.64 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -493.32 | -31937.62 |
SMSTORE2 | 01-JAN-09:01 | 0.00 | 0.00 | 30086.86 | 0.00 | 0.00 | 0.00 | 67.54 | 1537.78 | 374.52 | 289.96 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -440.48 | -31916.17 |
SMSTORE3 | 01-JAN-09:01 | 0.00 | 0.00 | 30253.18 | 0.00 | 0.00 | 0.00 | 68.68 | 1537.78 | 374.52 | 300.38 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -423.63 | -32110.91 |
SMSTORE4 | 01-JAN-09:01 | 0.00 | 0.00 | 30226.35 | 0.00 | 0.00 | 0.00 | 69.42 | 1537.78 | 374.52 | 306.78 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -412.34 | -32102.50 |
LGSTORE2 | 01-JAN-10:01 | 0.00 | 0.00 | 55765.11 | 0.00 | 0.00 | 0.00 | 305.91 | 2293.69 | 749.03 | 1342.79 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -629.02 | -59827.51 |
SMSTORE5 | 01-JAN-10:01 | 0.00 | 0.00 | 29467.73 | 0.00 | 0.00 | 0.00 | 152.95 | 1146.85 | 374.52 | 670.96 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -360.96 | -31452.05 |
SMSTORE6 | 01-JAN-10:01 | 0.00 | 0.00 | 29361.28 | 0.00 | 0.00 | 0.00 | 152.96 | 1146.85 | 374.52 | 671.81 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -360.69 | -31346.72 |
SMSTORE7 | 01-JAN-10:01 | 0.00 | 0.00 | 29389.03 | 0.00 | 0.00 | 0.00 | 152.96 | 1146.85 | 374.52 | 673.62 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -360.44 | -31376.53 |
SMSTORE8 | 01-JAN-10:01 | 0.00 | 0.00 | 31501.75 | 0.00 | 0.00 | 0.00 | 152.96 | 1146.85 | 374.52 | 677.98 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -369.82 | -33484.22 |
Total Facility | 02-JAN-09:01 | -229.98 | 229.98 | 260779.18 | -229.98 | 0.00 | 0.00 | 1487.90 | 20571.05 | 5393.02 | 4641.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -5288.70 | -287354.38 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2020-06-03 19:21:12
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 2.5143 | 0.0000 | 29.9961 | 1.0000 | 0.4115 | 2.5143 | 0.1636 | 1.0000 | 0.4115 | 0.1636 | ||
PSZ-AC_2:2 | 1.3217 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.3217 | 0.1557 | 1.0000 | 0.2057 | 0.1557 | ||
PSZ-AC_3:3 | 1.3146 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.3146 | 0.1565 | 1.0000 | 0.2057 | 0.1565 | ||
PSZ-AC_4:4 | 1.3176 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.3176 | 0.1561 | 1.0000 | 0.2057 | 0.1561 | ||
PSZ-AC_5:5 | 1.3129 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.3129 | 0.1567 | 1.0000 | 0.2057 | 0.1567 | ||
PSZ-AC_6:6 | 2.3771 | 0.0000 | 29.9961 | 1.0000 | 0.4115 | 2.3771 | 0.1731 | 1.0000 | 0.4115 | 0.1731 | ||
PSZ-AC_7:7 | 1.2618 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.2618 | 0.1630 | 1.0000 | 0.2057 | 0.1630 | ||
PSZ-AC_8:8 | 1.2565 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.2565 | 0.1637 | 1.0000 | 0.2057 | 0.1637 | ||
PSZ-AC_9:9 | 1.2574 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.2574 | 0.1636 | 1.0000 | 0.2057 | 0.1636 | ||
PSZ-AC_10:10 | 1.3581 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.3581 | 0.1515 | 1.0000 | 0.2057 | 0.1515 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 2.5143 | 0.0000 | 29.9961 | 1.0000 | 0.4115 | 2.5143 | 1.0000 | 1.0000 | 0.4115 | 0.1636 | ||
PSZ-AC_2:2 | 1.3217 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.3217 | 1.0000 | 1.0000 | 0.2057 | 0.1557 | ||
PSZ-AC_3:3 | 1.3146 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.3146 | 1.0000 | 1.0000 | 0.2057 | 0.1565 | ||
PSZ-AC_4:4 | 1.3176 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.3176 | 1.0000 | 1.0000 | 0.2057 | 0.1561 | ||
PSZ-AC_5:5 | 1.3129 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.3129 | 1.0000 | 1.0000 | 0.2057 | 0.1567 | ||
PSZ-AC_6:6 | 2.3771 | 0.0000 | 29.9961 | 1.0000 | 0.4115 | 2.3771 | 1.0000 | 1.0000 | 0.4115 | 0.1731 | ||
PSZ-AC_7:7 | 1.2618 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.2618 | 1.0000 | 1.0000 | 0.2057 | 0.1630 | ||
PSZ-AC_8:8 | 1.2565 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.2565 | 1.0000 | 1.0000 | 0.2057 | 0.1637 | ||
PSZ-AC_9:9 | 1.2574 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.2574 | 1.0000 | 1.0000 | 0.2057 | 0.1636 | ||
PSZ-AC_10:10 | 1.3581 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.3581 | 1.0000 | 1.0000 | 0.2057 | 0.1515 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
LGSTORE1 | PSZ-AC_1:1 | 0.000000 | 29.9961 | 0.001181 | 348.39 | 0.4115 | 1.0000 | 0.4115 | 1.000 | 0.4115 |
SMSTORE1 | PSZ-AC_2:2 | 0.000000 | 14.9980 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE2 | PSZ-AC_3:3 | 0.000000 | 14.9980 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE3 | PSZ-AC_4:4 | 0.000000 | 14.9980 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE4 | PSZ-AC_5:5 | 0.000000 | 14.9980 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
LGSTORE2 | PSZ-AC_6:6 | 0.000000 | 29.9961 | 0.001181 | 348.39 | 0.4115 | 1.0000 | 0.4115 | 1.000 | 0.4115 |
SMSTORE5 | PSZ-AC_7:7 | 0.000000 | 14.9980 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE6 | PSZ-AC_8:8 | 0.000000 | 14.9980 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE7 | PSZ-AC_9:9 | 0.000000 | 14.9980 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE8 | PSZ-AC_10:10 | 0.000000 | 14.9980 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC_1:1 | 0.000000 | 30.00 | 0.001181 | 348.3864 | 0.4115 | 0.4115 | 0.4115 |
PSZ-AC_2:2 | 0.000000 | 15.00 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_3:3 | 0.000000 | 15.00 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_4:4 | 0.000000 | 15.00 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_5:5 | 0.000000 | 15.00 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_6:6 | 0.000000 | 30.00 | 0.001181 | 348.3864 | 0.4115 | 0.4115 | 0.4115 |
PSZ-AC_7:7 | 0.000000 | 15.00 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_8:8 | 0.000000 | 15.00 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_9:9 | 0.000000 | 15.00 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_10:10 | 0.000000 | 15.00 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LGSTORE1 | PSZ-AC_1:1 | 2.5143 | 2.5143 | 2.5143 | 0.4115 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE1 | PSZ-AC_2:2 | 1.3217 | 1.3217 | 1.3217 | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE2 | PSZ-AC_3:3 | 1.3146 | 1.3146 | 1.3146 | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE3 | PSZ-AC_4:4 | 1.3176 | 1.3176 | 1.3176 | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE4 | PSZ-AC_5:5 | 1.3129 | 1.3129 | 1.3129 | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
LGSTORE2 | PSZ-AC_6:6 | 2.3771 | 2.3771 | 2.3771 | 0.4115 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE5 | PSZ-AC_7:7 | 1.2618 | 1.2618 | 1.2618 | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE6 | PSZ-AC_8:8 | 1.2565 | 1.2565 | 1.2565 | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE7 | PSZ-AC_9:9 | 1.2574 | 1.2574 | 1.2574 | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE8 | PSZ-AC_10:10 | 1.3581 | 1.3581 | 1.3581 | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 2.5143 | 2.5143 | 2.5143 | 2.5143 | 0.4115 | 1.0000 |
PSZ-AC_2:2 | 1.3217 | 1.3217 | 1.3217 | 1.3217 | 0.2057 | 1.0000 |
PSZ-AC_3:3 | 1.3146 | 1.3146 | 1.3146 | 1.3146 | 0.2057 | 1.0000 |
PSZ-AC_4:4 | 1.3176 | 1.3176 | 1.3176 | 1.3176 | 0.2057 | 1.0000 |
PSZ-AC_5:5 | 1.3129 | 1.3129 | 1.3129 | 1.3129 | 0.2057 | 1.0000 |
PSZ-AC_6:6 | 2.3771 | 2.3771 | 2.3771 | 2.3771 | 0.4115 | 1.0000 |
PSZ-AC_7:7 | 1.2618 | 1.2618 | 1.2618 | 1.2618 | 0.2057 | 1.0000 |
PSZ-AC_8:8 | 1.2565 | 1.2565 | 1.2565 | 1.2565 | 0.2057 | 1.0000 |
PSZ-AC_9:9 | 1.2574 | 1.2574 | 1.2574 | 1.2574 | 0.2057 | 1.0000 |
PSZ-AC_10:10 | 1.3581 | 1.3581 | 1.3581 | 1.3581 | 0.2057 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LGSTORE1 | PSZ-AC_1:1 | 2.5143 | 2.5143 | 2.5143 | 0.4115 | 0.5854 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE1 | PSZ-AC_2:2 | 1.3217 | 1.3217 | 1.3217 | 0.2057 | 0.5645 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE2 | PSZ-AC_3:3 | 1.3146 | 1.3146 | 1.3146 | 0.2057 | 0.5570 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE3 | PSZ-AC_4:4 | 1.3176 | 1.3176 | 1.3176 | 0.2057 | 0.5518 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE4 | PSZ-AC_5:5 | 1.3129 | 1.3129 | 1.3129 | 0.2057 | 0.5413 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
LGSTORE2 | PSZ-AC_6:6 | 2.3771 | 2.3771 | 2.3771 | 0.4115 | 0.5760 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE5 | PSZ-AC_7:7 | 1.2618 | 1.2618 | 1.2618 | 0.2057 | 0.5291 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE6 | PSZ-AC_8:8 | 1.2565 | 1.2565 | 1.2565 | 0.2057 | 0.5295 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE7 | PSZ-AC_9:9 | 1.2574 | 1.2574 | 1.2574 | 0.2057 | 0.5180 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE8 | PSZ-AC_10:10 | 1.3581 | 1.3581 | 1.3581 | 0.2057 | 0.4724 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 2.5143 | 2.5143 | 2.5143 | 2.5143 | 0.4115 | 1.0000 |
PSZ-AC_2:2 | 1.3217 | 1.3217 | 1.3217 | 1.3217 | 0.2057 | 1.0000 |
PSZ-AC_3:3 | 1.3146 | 1.3146 | 1.3146 | 1.3146 | 0.2057 | 1.0000 |
PSZ-AC_4:4 | 1.3176 | 1.3176 | 1.3176 | 1.3176 | 0.2057 | 1.0000 |
PSZ-AC_5:5 | 1.3129 | 1.3129 | 1.3129 | 1.3129 | 0.2057 | 1.0000 |
PSZ-AC_6:6 | 2.3771 | 2.3771 | 2.3771 | 2.3771 | 0.4115 | 1.0000 |
PSZ-AC_7:7 | 1.2618 | 1.2618 | 1.2618 | 1.2618 | 0.2057 | 1.0000 |
PSZ-AC_8:8 | 1.2565 | 1.2565 | 1.2565 | 1.2565 | 0.2057 | 1.0000 |
PSZ-AC_9:9 | 1.2574 | 1.2574 | 1.2574 | 1.2574 | 0.2057 | 1.0000 |
PSZ-AC_10:10 | 1.3581 | 1.3581 | 1.3581 | 1.3581 | 0.2057 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2020-06-03 19:21:12
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820 |
Total gross floor area [m2] | 2090.32 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
LGSTORE1 | 348.39 | 348.39 | 0.00 | 112.00 |
SMSTORE1 | 174.19 | 174.19 | 0.00 | 112.00 |
SMSTORE2 | 174.19 | 174.19 | 0.00 | 84.29 |
SMSTORE3 | 174.19 | 174.19 | 0.00 | 84.29 |
SMSTORE4 | 174.19 | 174.19 | 0.00 | 84.29 |
LGSTORE2 | 348.39 | 348.39 | 0.00 | 77.29 |
SMSTORE5 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE6 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE7 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE8 | 174.19 | 174.19 | 0.00 | 77.29 |
Totals | 2090.32 | 2090.32 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 37.67 |
Number of hours not met | 37.67 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Fuel Use [GJ] | Additional Fuel Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- Not Subdivided | 0.00 | 0.00 | 2.11 | 102906.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- Not Subdivided | 480.13 | 84630.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 502.03 | 31196.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 91.02 | 6944.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 128.72 | 8089.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 133.57 | 16042.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 58.82 | 11784.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 128.72 | 1394.29 |
Natural Gas | 0.00 | 2.11 |
Additional | 0.00 | 0.00 |
Total | 128.72 | 1396.40 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 240.17 |
Space Heating | 0.00 |
Space Cooling | 229.69 |
Fans (All) | 63.90 |
Service Water Heating | 28.14 |
Receptacle Equipment | 61.58 |
Miscellaneous (All) | 667.02 |
Subtotal | 667.02 |
Natural Gas [MJ/m2] | |
Space Heating | 1.01 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 1.01 |
Subtotal | 1.01 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 35.95 |
Space Heating | 0.15 |
Space Cooling | 34.38 |
Fans (All) | 9.57 |
Service Water Heating | 4.21 |
Receptacle Equipment | 9.22 |
Miscellaneous | 6.52 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
TYPE1_OCC_SCH | 1630. | 5840. |
TYPE2_OCC_SCH | 995. | 4429. |
TYPE3_OCC_SCH | 1709. | 4064. |
TYPE1_LIGHT_SCH | 5131. | 8760. |
TYPE2_LIGHT_SCH | 4096. | 8760. |
TYPE3_LIGHT_SCH | 3767. | 8760. |
TYPE1_EQUIP_SCH | 4888. | 8760. |
TYPE2_EQUIP_SCH | 3911. | 8760. |
TYPE3_EQUIP_SCH | 3600. | 8760. |
TYPE1_INFIL_SCH | 4302. | 8760. |
TYPE2_INFIL_SCH | 5164. | 8760. |
TYPE3_INFIL_SCH | 5438. | 8760. |
INFIL_DOOR_OPENING_SCH | 2505. | 4380. |
TYPE1_MINOA_MOTORIZEDDAMPER_SCH | 5579. | 5579. |
TYPE2_MINOA_MOTORIZEDDAMPER_SCH | 4429. | 4429. |
TYPE3_MINOA_MOTORIZEDDAMPER_SCH | 4064. | 4064. |
TYPE1_SWH_SCH | 2063. | 6048. |
TYPE2_SWH_SCH | 1831. | 4429. |
TYPE3_SWH_SCH | 1733. | 4064. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 7118. | 8760. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 5839. | 5839. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 7300. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
TYPE1_HTGSETP_SCH_YES_OPTIMUM | LGSTORE1 DUALSPSCHED | January | 21.11 | 365 | 21.11 | 365 |
TYPE1_CLGSETP_SCH_YES_OPTIMUM | LGSTORE1 DUALSPSCHED | July | 23.89 | 365 | 23.89 | 365 |
TYPE2_HTGSETP_SCH_YES_OPTIMUM | SMSTORE2 DUALSPSCHED | January | 21.11 | 365 | 15.56 | 365 |
TYPE2_CLGSETP_SCH_YES_OPTIMUM | SMSTORE2 DUALSPSCHED | July | 23.89 | 365 | 29.44 | 365 |
TYPE3_HTGSETP_SCH_YES_OPTIMUM | LGSTORE2 DUALSPSCHED | January | 21.11 | 365 | 15.56 | 365 |
TYPE3_CLGSETP_SCH_YES_OPTIMUM | LGSTORE2 DUALSPSCHED | July | 23.89 | 365 | 29.44 | 365 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Meter
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.193787E+10 |
February | 0.000 | 0.568847E+08 |
March | 0.000 | 0.000 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.000 |
December | 0.000 | 0.113002E+09 |
Annual Sum or Average | 0.210776E+10 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.193787E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Meter
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.193787E+10 |
February | 0.000 | 0.568847E+08 |
March | 0.000 | 0.000 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.000 |
December | 0.000 | 0.113002E+09 |
Annual Sum or Average | 0.210776E+10 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.193787E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2015
For: Meter
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.193787E+10 |
February | 0.000 | 0.568847E+08 |
March | 0.000 | 0.000 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.000 |
December | 0.000 | 0.113002E+09 |
Annual Sum or Average | 0.210776E+10 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.193787E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Meter
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.193787E+10 |
February | 0.000 | 0.568847E+08 |
March | 0.000 | 0.000 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.000 |
December | 0.000 | 0.113002E+09 |
Annual Sum or Average | 0.210776E+10 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.193787E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTRIPMALL
For: Meter
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.193787E+10 |
February | 0.000 | 0.568847E+08 |
March | 0.000 | 0.000 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.000 |
December | 0.000 | 0.113002E+09 |
Annual Sum or Average | 0.210776E+10 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.193787E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.193787E+10 |
February | 0.000 | 0.568847E+08 |
March | 0.000 | 0.000 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.000 |
December | 0.000 | 0.113002E+09 |
Annual Sum or Average | 0.210776E+10 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.193787E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.193787E+10 |
February | 0.000 | 0.568847E+08 |
March | 0.000 | 0.000 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.000 |
December | 0.000 | 0.113002E+09 |
Annual Sum or Average | 0.210776E+10 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.193787E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 1B
For: Meter
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.193787E+10 |
February | 0.000 | 0.568847E+08 |
March | 0.000 | 0.000 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.000 |
December | 0.000 | 0.113002E+09 |
Annual Sum or Average | 0.210776E+10 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.193787E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY IND_DELHI_NEWDELHI
For: Meter
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.193787E+10 |
February | 0.000 | 0.568847E+08 |
March | 0.000 | 0.000 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.000 |
December | 0.000 | 0.113002E+09 |
Annual Sum or Average | 0.210776E+10 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.193787E+10 |
Report: ZoneCoolingSummaryMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.718035E+10 | 7752.07 | 12-JAN-15:00 | 23.60 | 14.18 | 0.727732E+09 | 899.03 | 08-JAN-18:00 | 15.90 | 12.25 |
February | 0.876602E+10 | 11172.40 | 22-FEB-15:00 | 27.10 | 16.17 | 0.673594E+09 | 899.05 | 20-FEB-18:00 | 20.60 | 13.90 |
March | 0.139613E+11 | 37379.25 | 11-MAR-09:02 | 25.87 | 17.86 | 0.744822E+09 | 899.04 | 19-MAR-17:00 | 23.40 | 15.03 |
April | 0.192548E+11 | 44270.08 | 08-APR-08:62 | 26.02 | 15.25 | 0.727233E+09 | 899.13 | 28-APR-12:39 | 37.20 | 20.33 |
May | 0.237324E+11 | 42777.98 | 06-MAY-08:61 | 31.42 | 18.14 | 0.748949E+09 | 899.10 | 28-MAY-17:10 | 41.37 | 19.60 |
June | 0.238343E+11 | 38629.81 | 07-JUN-08:61 | 36.23 | 19.94 | 0.723542E+09 | 898.99 | 04-JUN-16:19 | 42.13 | 22.31 |
July | 0.235735E+11 | 33407.41 | 07-JUL-07:01 | 33.33 | 24.38 | 0.754993E+09 | 898.97 | 02-JUL-16:19 | 40.37 | 26.41 |
August | 0.226295E+11 | 30075.58 | 06-AUG-07:01 | 29.23 | 23.53 | 0.744670E+09 | 898.94 | 06-AUG-16:30 | 36.15 | 26.33 |
September | 0.207975E+11 | 34898.53 | 26-SEP-08:61 | 26.97 | 20.02 | 0.729499E+09 | 898.94 | 24-SEP-16:30 | 34.45 | 25.39 |
October | 0.193823E+11 | 39361.15 | 16-OCT-08:62 | 24.53 | 16.47 | 0.752485E+09 | 899.10 | 01-OCT-16:10 | 35.32 | 20.14 |
November | 0.139523E+11 | 28982.61 | 09-NOV-09:02 | 22.33 | 17.30 | 0.726718E+09 | 899.05 | 26-NOV-17:10 | 22.25 | 14.81 |
December | 0.883125E+10 | 9512.70 | 03-DEC-14:00 | 24.50 | 14.15 | 0.744903E+09 | 899.03 | 25-DEC-17:19 | 19.13 | 13.32 |
Annual Sum or Average | 0.205896E+12 | 0.879914E+10 | ||||||||
Minimum of Months | 0.718035E+10 | 7752.07 | 22.33 | 14.15 | 0.673594E+09 | 898.94 | 15.90 | 12.25 | ||
Maximum of Months | 0.238343E+11 | 44270.08 | 36.23 | 24.38 | 0.754993E+09 | 899.13 | 42.13 | 26.41 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.363489E+10 | 4261.20 | 12-JAN-15:00 | 23.60 | 14.18 | 0.369612E+09 | 449.51 | 22-JAN-18:00 | 14.90 | 9.51 |
February | 0.483315E+10 | 6011.69 | 22-FEB-14:50 | 27.08 | 16.20 | 0.337981E+09 | 449.53 | 05-FEB-18:30 | 20.00 | 12.63 |
March | 0.769214E+10 | 20115.01 | 11-MAR-09:02 | 25.87 | 17.86 | 0.372539E+09 | 449.51 | 05-MAR-17:10 | 27.70 | 17.83 |
April | 0.102970E+11 | 23094.02 | 08-APR-08:62 | 26.02 | 15.25 | 0.363665E+09 | 449.57 | 28-APR-12:30 | 37.00 | 20.20 |
May | 0.124940E+11 | 22300.94 | 06-MAY-08:61 | 31.42 | 18.14 | 0.374478E+09 | 449.55 | 28-MAY-17:00 | 39.70 | 19.89 |
June | 0.123819E+11 | 20341.51 | 07-JUN-08:61 | 36.23 | 19.94 | 0.361764E+09 | 449.49 | 04-JUN-16:19 | 42.13 | 22.31 |
July | 0.121571E+11 | 17440.53 | 05-JUL-07:01 | 33.75 | 24.50 | 0.377485E+09 | 449.48 | 04-JUL-16:30 | 39.80 | 24.46 |
August | 0.115746E+11 | 17213.55 | 06-AUG-07:01 | 29.23 | 23.53 | 0.372322E+09 | 449.47 | 06-AUG-16:30 | 36.15 | 26.33 |
September | 0.106841E+11 | 18931.54 | 26-SEP-08:61 | 26.97 | 20.02 | 0.364738E+09 | 449.47 | 24-SEP-17:40 | 33.50 | 25.69 |
October | 0.100722E+11 | 21387.97 | 15-OCT-07:02 | 21.47 | 14.97 | 0.376256E+09 | 449.54 | 01-OCT-16:10 | 35.32 | 20.14 |
November | 0.737139E+10 | 15589.65 | 09-NOV-09:02 | 22.33 | 17.30 | 0.363432E+09 | 449.52 | 26-NOV-17:10 | 22.25 | 14.81 |
December | 0.460869E+10 | 5172.37 | 02-DEC-14:00 | 24.10 | 13.12 | 0.374923E+09 | 449.51 | 25-DEC-17:19 | 19.13 | 13.32 |
Annual Sum or Average | 0.107801E+12 | 0.440920E+10 | ||||||||
Minimum of Months | 0.363489E+10 | 4261.20 | 21.47 | 13.12 | 0.337981E+09 | 449.47 | 14.90 | 9.51 | ||
Maximum of Months | 0.124940E+11 | 23094.02 | 36.23 | 24.50 | 0.377485E+09 | 449.57 | 42.13 | 26.33 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.248924E+10 | 3800.18 | 12-JAN-15:00 | 23.60 | 14.18 | 0.216044E+09 | 449.51 | 07-JAN-13:50 | 20.82 | 13.26 |
February | 0.337758E+10 | 5698.41 | 22-FEB-14:00 | 27.00 | 16.30 | 0.201521E+09 | 449.49 | 11-FEB-13:09 | 20.65 | 13.77 |
March | 0.574203E+10 | 18515.38 | 11-MAR-08:62 | 24.43 | 17.40 | 0.230056E+09 | 449.51 | 04-MAR-13:09 | 26.57 | 15.78 |
April | 0.797322E+10 | 23609.80 | 30-APR-08:61 | 26.15 | 14.11 | 0.219676E+09 | 449.53 | 15-APR-12:00 | 39.40 | 19.77 |
May | 0.100297E+11 | 22620.37 | 06-MAY-07:01 | 30.00 | 17.73 | 0.228090E+09 | 449.53 | 06-MAY-12:50 | 40.93 | 19.96 |
June | 0.997508E+10 | 20143.51 | 07-JUN-07:01 | 34.92 | 19.60 | 0.223212E+09 | 449.42 | 24-JUN-12:20 | 24.83 | 24.20 |
July | 0.944407E+10 | 15598.58 | 05-JUL-06:02 | 33.02 | 24.49 | 0.224732E+09 | 449.36 | 01-JUL-12:30 | 37.90 | 28.21 |
August | 0.914965E+10 | 13980.93 | 03-AUG-07:01 | 28.70 | 23.40 | 0.230790E+09 | 449.33 | 05-AUG-12:09 | 35.03 | 26.47 |
September | 0.822101E+10 | 16976.69 | 26-SEP-07:01 | 25.87 | 19.86 | 0.219625E+09 | 449.40 | 09-SEP-12:00 | 27.10 | 25.75 |
October | 0.770549E+10 | 20406.74 | 16-OCT-07:02 | 22.70 | 15.65 | 0.224546E+09 | 449.49 | 21-OCT-12:09 | 29.33 | 18.35 |
November | 0.549666E+10 | 7539.20 | 04-NOV-14:00 | 30.30 | 17.14 | 0.216298E+09 | 449.51 | 18-NOV-13:09 | 26.42 | 17.17 |
December | 0.317902E+10 | 4862.24 | 02-DEC-14:00 | 24.10 | 13.12 | 0.220018E+09 | 449.51 | 09-DEC-13:50 | 19.47 | 12.75 |
Annual Sum or Average | 0.827828E+11 | 0.265461E+10 | ||||||||
Minimum of Months | 0.248924E+10 | 3800.18 | 22.70 | 13.12 | 0.201521E+09 | 449.33 | 19.47 | 12.75 | ||
Maximum of Months | 0.100297E+11 | 23609.80 | 34.92 | 24.49 | 0.230790E+09 | 449.53 | 40.93 | 28.21 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.232652E+10 | 3709.48 | 04-JAN-08:03 | 6.42 | 5.61 | 0.214741E+09 | 449.51 | 07-JAN-13:00 | 20.90 | 13.27 |
February | 0.327785E+10 | 5630.54 | 22-FEB-14:00 | 27.00 | 16.30 | 0.201337E+09 | 449.49 | 11-FEB-13:09 | 20.65 | 13.77 |
March | 0.571075E+10 | 18544.64 | 11-MAR-08:62 | 24.43 | 17.40 | 0.230043E+09 | 449.51 | 04-MAR-13:09 | 26.57 | 15.78 |
April | 0.801283E+10 | 23694.95 | 30-APR-08:61 | 26.15 | 14.11 | 0.219679E+09 | 449.53 | 15-APR-12:00 | 39.40 | 19.77 |
May | 0.101338E+11 | 22672.01 | 06-MAY-07:01 | 30.00 | 17.73 | 0.228095E+09 | 449.53 | 06-MAY-12:50 | 40.93 | 19.96 |
June | 0.100757E+11 | 20198.92 | 07-JUN-07:01 | 34.92 | 19.60 | 0.223217E+09 | 449.42 | 24-JUN-12:20 | 24.83 | 24.20 |
July | 0.955503E+10 | 15877.94 | 05-JUL-06:02 | 33.02 | 24.49 | 0.224736E+09 | 449.36 | 01-JUL-12:30 | 37.90 | 28.21 |
August | 0.922932E+10 | 14062.09 | 03-AUG-07:01 | 28.70 | 23.40 | 0.230794E+09 | 449.33 | 05-AUG-12:09 | 35.03 | 26.47 |
September | 0.828410E+10 | 17048.06 | 26-SEP-07:01 | 25.87 | 19.86 | 0.219629E+09 | 449.40 | 09-SEP-12:50 | 27.13 | 25.74 |
October | 0.774462E+10 | 20508.86 | 16-OCT-07:02 | 22.70 | 15.65 | 0.224549E+09 | 449.49 | 21-OCT-12:09 | 29.33 | 18.35 |
November | 0.544936E+10 | 7512.00 | 04-NOV-14:00 | 30.30 | 17.14 | 0.216277E+09 | 449.51 | 18-NOV-13:09 | 26.42 | 17.17 |
December | 0.305413E+10 | 4784.77 | 02-DEC-14:00 | 24.10 | 13.12 | 0.219661E+09 | 449.51 | 09-DEC-13:00 | 19.70 | 12.77 |
Annual Sum or Average | 0.828540E+11 | 0.265276E+10 | ||||||||
Minimum of Months | 0.232652E+10 | 3709.48 | 6.42 | 5.61 | 0.201337E+09 | 449.33 | 19.70 | 12.77 | ||
Maximum of Months | 0.101338E+11 | 23694.95 | 34.92 | 24.49 | 0.230794E+09 | 449.53 | 40.93 | 28.21 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.213959E+10 | 3707.24 | 05-JAN-08:04 | 6.10 | 5.58 | 0.213136E+09 | 449.51 | 07-JAN-13:00 | 20.90 | 13.27 |
February | 0.310831E+10 | 5487.70 | 22-FEB-14:00 | 27.00 | 16.30 | 0.201008E+09 | 449.49 | 11-FEB-13:09 | 20.65 | 13.77 |
March | 0.553524E+10 | 18369.47 | 11-MAR-08:62 | 24.43 | 17.40 | 0.229997E+09 | 449.51 | 04-MAR-13:09 | 26.57 | 15.78 |
April | 0.787806E+10 | 23591.60 | 30-APR-08:61 | 26.15 | 14.11 | 0.219660E+09 | 449.54 | 29-APR-12:09 | 37.25 | 19.97 |
May | 0.100247E+11 | 22595.21 | 06-MAY-07:01 | 30.00 | 17.73 | 0.228083E+09 | 449.53 | 06-MAY-12:50 | 40.93 | 19.96 |
June | 0.996677E+10 | 20120.57 | 07-JUN-07:01 | 34.92 | 19.60 | 0.223204E+09 | 449.42 | 24-JUN-12:20 | 24.83 | 24.20 |
July | 0.946323E+10 | 15787.94 | 05-JUL-06:02 | 33.02 | 24.49 | 0.224725E+09 | 449.36 | 01-JUL-12:30 | 37.90 | 28.21 |
August | 0.912011E+10 | 13930.77 | 03-AUG-07:01 | 28.70 | 23.40 | 0.230781E+09 | 449.33 | 05-AUG-12:09 | 35.03 | 26.47 |
September | 0.817468E+10 | 16957.71 | 26-SEP-07:01 | 25.87 | 19.86 | 0.219615E+09 | 449.40 | 09-SEP-12:00 | 27.10 | 25.75 |
October | 0.761636E+10 | 20395.64 | 16-OCT-07:02 | 22.70 | 15.65 | 0.224531E+09 | 449.50 | 21-OCT-12:09 | 29.33 | 18.35 |
November | 0.529267E+10 | 7387.02 | 04-NOV-14:00 | 30.30 | 17.14 | 0.216233E+09 | 449.51 | 18-NOV-13:09 | 26.42 | 17.17 |
December | 0.287638E+10 | 4647.38 | 02-DEC-14:00 | 24.10 | 13.12 | 0.219142E+09 | 449.51 | 09-DEC-13:00 | 19.70 | 12.77 |
Annual Sum or Average | 0.811961E+11 | 0.265011E+10 | ||||||||
Minimum of Months | 0.213959E+10 | 3707.24 | 6.10 | 5.58 | 0.201008E+09 | 449.33 | 19.70 | 12.77 | ||
Maximum of Months | 0.100247E+11 | 23591.60 | 34.92 | 24.49 | 0.230781E+09 | 449.54 | 40.93 | 28.21 |
Report: ZoneCoolingSummaryMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.343648E+10 | 6276.36 | 02-JAN-09:04 | 8.57 | 8.29 | 0.722533E+09 | 1198.69 | 07-JAN-15:30 | 20.40 | 13.32 |
February | 0.504240E+10 | 9773.60 | 22-FEB-14:00 | 27.00 | 16.30 | 0.687945E+09 | 1198.65 | 11-FEB-15:00 | 21.20 | 14.71 |
March | 0.945517E+10 | 34668.60 | 11-MAR-09:02 | 25.87 | 17.86 | 0.788838E+09 | 1198.67 | 04-MAR-15:00 | 26.70 | 15.70 |
April | 0.136966E+11 | 42460.14 | 09-APR-09:01 | 27.52 | 15.31 | 0.753271E+09 | 1198.77 | 29-APR-14:09 | 36.00 | 19.42 |
May | 0.175570E+11 | 41023.43 | 29-MAY-08:61 | 32.12 | 19.76 | 0.779298E+09 | 1198.73 | 06-MAY-14:00 | 41.70 | 19.93 |
June | 0.175065E+11 | 37293.11 | 12-JUN-07:01 | 35.90 | 20.10 | 0.764037E+09 | 1198.56 | 10-JUN-14:50 | 42.48 | 25.52 |
July | 0.165633E+11 | 31924.63 | 07-JUL-07:01 | 33.33 | 24.38 | 0.768716E+09 | 1198.22 | 22-JUL-14:09 | 29.58 | 26.97 |
August | 0.160000E+11 | 29212.76 | 08-AUG-07:01 | 30.50 | 24.41 | 0.790473E+09 | 1198.23 | 19-AUG-14:00 | 27.10 | 25.89 |
September | 0.142534E+11 | 33253.13 | 26-SEP-08:61 | 26.97 | 20.02 | 0.753160E+09 | 1198.38 | 09-SEP-14:20 | 26.77 | 25.70 |
October | 0.132917E+11 | 38402.01 | 15-OCT-09:01 | 26.53 | 16.17 | 0.766428E+09 | 1198.63 | 28-OCT-14:00 | 29.30 | 18.42 |
November | 0.896630E+10 | 29359.55 | 11-NOV-10:02 | 23.18 | 16.66 | 0.736613E+09 | 1198.70 | 18-NOV-15:09 | 26.30 | 17.20 |
December | 0.459999E+10 | 8106.41 | 02-DEC-14:10 | 24.07 | 13.13 | 0.750104E+09 | 1198.69 | 09-DEC-15:39 | 19.17 | 13.13 |
Annual Sum or Average | 0.140369E+12 | 0.906142E+10 | ||||||||
Minimum of Months | 0.343648E+10 | 6276.36 | 8.57 | 8.29 | 0.687945E+09 | 1198.22 | 19.17 | 13.13 | ||
Maximum of Months | 0.175570E+11 | 42460.14 | 35.90 | 24.41 | 0.790473E+09 | 1198.77 | 42.48 | 26.97 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.162352E+10 | 3096.11 | 02-JAN-09:04 | 8.57 | 8.29 | 0.359968E+09 | 599.34 | 07-JAN-15:09 | 20.73 | 13.39 |
February | 0.252065E+10 | 5101.71 | 22-FEB-14:00 | 27.00 | 16.30 | 0.343771E+09 | 599.32 | 11-FEB-15:00 | 21.20 | 14.71 |
March | 0.489437E+10 | 18167.34 | 11-MAR-09:02 | 25.87 | 17.86 | 0.394419E+09 | 599.33 | 04-MAR-15:00 | 26.70 | 15.70 |
April | 0.720408E+10 | 22314.16 | 20-APR-08:61 | 27.53 | 16.76 | 0.376618E+09 | 599.38 | 15-APR-14:30 | 40.25 | 20.61 |
May | 0.927652E+10 | 21503.90 | 29-MAY-08:61 | 32.12 | 19.76 | 0.389634E+09 | 599.37 | 06-MAY-14:00 | 41.70 | 19.93 |
June | 0.922378E+10 | 19558.02 | 12-JUN-07:01 | 35.90 | 20.10 | 0.382001E+09 | 599.27 | 10-JUN-14:00 | 42.70 | 25.56 |
July | 0.870470E+10 | 15477.57 | 05-JUL-07:01 | 33.75 | 24.50 | 0.384335E+09 | 599.09 | 22-JUL-14:09 | 29.58 | 26.97 |
August | 0.838461E+10 | 14273.27 | 03-AUG-08:61 | 29.35 | 23.63 | 0.395218E+09 | 599.10 | 19-AUG-14:00 | 27.10 | 25.89 |
September | 0.747649E+10 | 17494.84 | 26-SEP-08:61 | 26.97 | 20.02 | 0.376563E+09 | 599.17 | 09-SEP-14:20 | 26.77 | 25.70 |
October | 0.694960E+10 | 20155.29 | 15-OCT-09:01 | 26.53 | 16.17 | 0.383207E+09 | 599.31 | 28-OCT-14:00 | 29.30 | 18.42 |
November | 0.462382E+10 | 14290.38 | 11-NOV-10:02 | 23.18 | 16.66 | 0.368312E+09 | 599.35 | 18-NOV-15:09 | 26.30 | 17.20 |
December | 0.224863E+10 | 4181.50 | 02-DEC-14:20 | 24.03 | 13.14 | 0.374722E+09 | 599.34 | 09-DEC-15:39 | 19.17 | 13.13 |
Annual Sum or Average | 0.731307E+11 | 0.452877E+10 | ||||||||
Minimum of Months | 0.162352E+10 | 3096.11 | 8.57 | 8.29 | 0.343771E+09 | 599.09 | 19.17 | 13.13 | ||
Maximum of Months | 0.927652E+10 | 22314.16 | 35.90 | 24.50 | 0.395218E+09 | 599.38 | 42.70 | 26.97 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.157841E+10 | 3099.60 | 02-JAN-09:04 | 8.57 | 8.29 | 0.358860E+09 | 599.34 | 07-JAN-15:09 | 20.73 | 13.39 |
February | 0.245946E+10 | 5036.89 | 22-FEB-14:00 | 27.00 | 16.30 | 0.343491E+09 | 599.32 | 11-FEB-15:00 | 21.20 | 14.71 |
March | 0.482231E+10 | 18064.35 | 11-MAR-09:02 | 25.87 | 17.86 | 0.394395E+09 | 599.33 | 04-MAR-15:00 | 26.70 | 15.70 |
April | 0.713972E+10 | 22221.52 | 20-APR-08:61 | 27.53 | 16.76 | 0.376610E+09 | 599.38 | 15-APR-14:30 | 40.25 | 20.61 |
May | 0.921512E+10 | 21418.26 | 29-MAY-08:61 | 32.12 | 19.76 | 0.389631E+09 | 599.37 | 06-MAY-14:00 | 41.70 | 19.93 |
June | 0.916165E+10 | 19470.59 | 12-JUN-07:01 | 35.90 | 20.10 | 0.381998E+09 | 599.27 | 10-JUN-14:00 | 42.70 | 25.56 |
July | 0.865013E+10 | 15406.99 | 05-JUL-07:01 | 33.75 | 24.50 | 0.384332E+09 | 599.09 | 22-JUL-14:09 | 29.58 | 26.97 |
August | 0.833053E+10 | 14205.57 | 03-AUG-08:61 | 29.35 | 23.63 | 0.395215E+09 | 599.10 | 19-AUG-14:00 | 27.10 | 25.89 |
September | 0.742806E+10 | 17419.42 | 26-SEP-08:61 | 26.97 | 20.02 | 0.376558E+09 | 599.17 | 09-SEP-14:20 | 26.77 | 25.70 |
October | 0.689557E+10 | 20063.17 | 15-OCT-09:01 | 26.53 | 16.17 | 0.383198E+09 | 599.31 | 28-OCT-14:00 | 29.30 | 18.42 |
November | 0.456823E+10 | 13922.61 | 11-NOV-10:02 | 23.18 | 16.66 | 0.368296E+09 | 599.35 | 18-NOV-15:09 | 26.30 | 17.20 |
December | 0.219809E+10 | 4127.90 | 02-DEC-14:20 | 24.03 | 13.14 | 0.374312E+09 | 599.34 | 09-DEC-15:39 | 19.17 | 13.13 |
Annual Sum or Average | 0.724473E+11 | 0.452690E+10 | ||||||||
Minimum of Months | 0.157841E+10 | 3099.60 | 8.57 | 8.29 | 0.343491E+09 | 599.09 | 19.17 | 13.13 | ||
Maximum of Months | 0.921512E+10 | 22221.52 | 35.90 | 24.50 | 0.395215E+09 | 599.38 | 42.70 | 26.97 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.148554E+10 | 3101.13 | 02-JAN-09:04 | 8.57 | 8.29 | 0.356582E+09 | 599.34 | 07-JAN-15:09 | 20.73 | 13.39 |
February | 0.231763E+10 | 4913.05 | 22-FEB-15:10 | 27.00 | 16.13 | 0.342706E+09 | 599.33 | 11-FEB-15:00 | 21.20 | 14.71 |
March | 0.466696E+10 | 17967.12 | 11-MAR-09:02 | 25.87 | 17.86 | 0.394313E+09 | 599.33 | 04-MAR-15:00 | 26.70 | 15.70 |
April | 0.706015E+10 | 22175.79 | 20-APR-08:61 | 27.53 | 16.76 | 0.376595E+09 | 599.38 | 15-APR-14:30 | 40.25 | 20.61 |
May | 0.919088E+10 | 21381.48 | 29-MAY-08:61 | 32.12 | 19.76 | 0.389628E+09 | 599.37 | 06-MAY-14:00 | 41.70 | 19.93 |
June | 0.916460E+10 | 19495.21 | 12-JUN-07:01 | 35.90 | 20.10 | 0.381999E+09 | 599.27 | 10-JUN-14:00 | 42.70 | 25.56 |
July | 0.868029E+10 | 15458.80 | 05-JUL-07:01 | 33.75 | 24.50 | 0.384333E+09 | 599.10 | 22-JUL-14:09 | 29.58 | 26.97 |
August | 0.836805E+10 | 14220.13 | 03-AUG-08:61 | 29.35 | 23.63 | 0.395217E+09 | 599.10 | 19-AUG-14:00 | 27.10 | 25.89 |
September | 0.744876E+10 | 17431.49 | 26-SEP-08:61 | 26.97 | 20.02 | 0.376556E+09 | 599.17 | 09-SEP-14:20 | 26.77 | 25.70 |
October | 0.687849E+10 | 20028.63 | 15-OCT-09:01 | 26.53 | 16.17 | 0.383192E+09 | 599.31 | 28-OCT-14:00 | 29.30 | 18.42 |
November | 0.448363E+10 | 13103.08 | 11-NOV-10:02 | 23.18 | 16.66 | 0.368254E+09 | 599.32 | 25-NOV-15:00 | 23.30 | 13.25 |
December | 0.208785E+10 | 4021.77 | 02-DEC-14:20 | 24.03 | 13.14 | 0.373330E+09 | 599.34 | 09-DEC-15:30 | 19.35 | 13.12 |
Annual Sum or Average | 0.718328E+11 | 0.452271E+10 | ||||||||
Minimum of Months | 0.148554E+10 | 3101.13 | 8.57 | 8.29 | 0.342706E+09 | 599.10 | 19.35 | 13.12 | ||
Maximum of Months | 0.919088E+10 | 22175.79 | 35.90 | 24.50 | 0.395217E+09 | 599.38 | 42.70 | 26.97 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.138006E+10 | 3044.44 | 02-JAN-09:04 | 8.57 | 8.29 | 0.355286E+09 | 599.34 | 07-JAN-15:09 | 20.73 | 13.39 |
February | 0.221134E+10 | 5116.43 | 22-FEB-14:00 | 27.00 | 16.30 | 0.341320E+09 | 599.33 | 11-FEB-15:00 | 21.20 | 14.71 |
March | 0.465829E+10 | 18957.09 | 11-MAR-09:02 | 25.87 | 17.86 | 0.394091E+09 | 599.34 | 04-MAR-15:00 | 26.70 | 15.70 |
April | 0.750778E+10 | 23536.03 | 09-APR-09:01 | 27.52 | 15.31 | 0.376599E+09 | 599.39 | 15-APR-14:30 | 40.25 | 20.61 |
May | 0.100246E+11 | 23111.69 | 29-MAY-08:61 | 32.12 | 19.76 | 0.389659E+09 | 599.37 | 06-MAY-14:00 | 41.70 | 19.93 |
June | 0.101090E+11 | 21364.03 | 12-JUN-07:01 | 35.90 | 20.10 | 0.382027E+09 | 599.28 | 10-JUN-14:00 | 42.70 | 25.56 |
July | 0.973584E+10 | 17955.77 | 07-JUL-07:01 | 33.33 | 24.38 | 0.384387E+09 | 599.13 | 08-JUL-14:30 | 35.35 | 27.80 |
August | 0.949311E+10 | 15963.57 | 09-AUG-07:01 | 30.30 | 25.36 | 0.395261E+09 | 599.09 | 19-AUG-14:00 | 27.10 | 25.89 |
September | 0.840165E+10 | 18594.34 | 26-SEP-08:61 | 26.97 | 20.02 | 0.376614E+09 | 599.16 | 09-SEP-14:09 | 26.78 | 25.72 |
October | 0.765131E+10 | 21483.69 | 15-OCT-09:01 | 26.53 | 16.17 | 0.383252E+09 | 599.31 | 28-OCT-14:00 | 29.30 | 18.42 |
November | 0.478610E+10 | 13569.56 | 11-NOV-10:02 | 23.18 | 16.66 | 0.368220E+09 | 599.35 | 18-NOV-15:20 | 26.20 | 17.22 |
December | 0.205443E+10 | 4176.50 | 01-DEC-14:00 | 23.50 | 13.04 | 0.372588E+09 | 599.34 | 09-DEC-15:30 | 19.35 | 13.12 |
Annual Sum or Average | 0.780135E+11 | 0.451930E+10 | ||||||||
Minimum of Months | 0.138006E+10 | 3044.44 | 8.57 | 8.29 | 0.341320E+09 | 599.09 | 19.35 | 13.12 | ||
Maximum of Months | 0.101090E+11 | 23536.03 | 35.90 | 25.36 | 0.395261E+09 | 599.39 | 42.70 | 27.80 |
Report: ZoneHeatingSummaryMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 36753742.09 | 57555.72 | 01-JAN-09:01 | 9.20 |
February | 509633.30 | 3397.56 | 02-FEB-09:02 | 10.37 |
March | 6095412.94 | 2735.26 | 11-MAR-09:05 | 25.87 |
April | 94667227.86 | 4856.10 | 27-APR-08:05 | 30.47 |
May | 46859399.29 | 7611.05 | 04-MAY-08:05 | 36.48 |
June | 31317210.73 | 7424.81 | 07-JUN-08:05 | 36.23 |
July | 18496936.60 | 6008.27 | 02-JUL-07:07 | 33.57 |
August | 24156099.13 | 3922.75 | 06-AUG-07:06 | 29.23 |
September | 40078504.04 | 3919.34 | 22-SEP-08:06 | 29.38 |
October | 17620198.86 | 3235.11 | 02-OCT-08:05 | 27.45 |
November | 394370.64 | 1077.59 | 09-NOV-09:05 | 22.33 |
December | 2521840.54 | 12025.59 | 23-DEC-09:02 | 10.55 |
Annual Sum or Average | 0.319471E+09 | |||
Minimum of Months | 394370.64 | 1077.59 | 9.20 | |
Maximum of Months | 94667227.86 | 57555.72 | 36.48 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 9094107.78 | 29905.13 | 02-JAN-09:01 | 8.57 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 9.73 |
March | 3215268.18 | 1428.98 | 11-MAR-09:05 | 25.87 |
April | 42006622.72 | 2430.28 | 27-APR-08:05 | 30.47 |
May | 19715522.34 | 3809.25 | 04-MAY-08:05 | 36.48 |
June | 15390211.21 | 3979.49 | 12-JUN-08:05 | 37.17 |
July | 11279295.37 | 3136.55 | 02-JUL-07:06 | 33.57 |
August | 12659216.23 | 2271.70 | 25-AUG-08:07 | 30.23 |
September | 24298166.34 | 1974.79 | 18-SEP-08:06 | 28.37 |
October | 9682046.09 | 1724.09 | 04-OCT-08:05 | 27.45 |
November | 155687.13 | 629.44 | 09-NOV-09:05 | 22.33 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 12.50 |
Annual Sum or Average | 0.147496E+09 | |||
Minimum of Months | 0.00 | 0.00 | 8.57 | |
Maximum of Months | 42006622.72 | 29905.13 | 37.17 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 22206568.79 | 30086.94 | 01-JAN-09:01 | 9.20 |
February | 416085.54 | 333.04 | 20-FEB-17:03 | 24.33 |
March | 35293424.31 | 1890.74 | 12-MAR-16:02 | 31.18 |
April | 0.195330E+09 | 3846.81 | 16-APR-16:01 | 39.13 |
May | 0.239143E+09 | 4568.52 | 07-MAY-16:01 | 42.17 |
June | 0.257858E+09 | 4890.16 | 11-JUN-16:01 | 43.35 |
July | 0.192141E+09 | 4196.25 | 02-JUL-16:01 | 40.38 |
August | 0.158824E+09 | 3201.48 | 06-AUG-16:01 | 36.25 |
September | 0.140078E+09 | 2791.57 | 24-SEP-16:01 | 34.68 |
October | 69987769.34 | 2902.83 | 01-OCT-16:01 | 35.32 |
November | 6232982.58 | 1136.71 | 04-NOV-17:03 | 27.72 |
December | 398995.34 | 1994.98 | 23-DEC-08:63 | 7.55 |
Annual Sum or Average | 0.131791E+10 | |||
Minimum of Months | 398995.34 | 333.04 | 7.55 | |
Maximum of Months | 0.257858E+09 | 30086.94 | 43.35 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 34546030.42 | 30253.26 | 01-JAN-09:01 | 9.20 |
February | 448460.27 | 340.25 | 20-FEB-17:03 | 24.33 |
March | 35428914.75 | 1891.75 | 12-MAR-16:02 | 31.18 |
April | 0.191686E+09 | 3845.26 | 16-APR-16:01 | 39.13 |
May | 0.236026E+09 | 4566.11 | 07-MAY-16:01 | 42.17 |
June | 0.256017E+09 | 4887.41 | 11-JUN-16:01 | 43.35 |
July | 0.191106E+09 | 4193.80 | 02-JUL-16:01 | 40.38 |
August | 0.158252E+09 | 3199.18 | 06-AUG-16:01 | 36.25 |
September | 0.138301E+09 | 2789.60 | 24-SEP-16:01 | 34.68 |
October | 69273841.33 | 2901.06 | 01-OCT-16:01 | 35.32 |
November | 6275480.49 | 1139.12 | 04-NOV-17:03 | 27.72 |
December | 797428.26 | 3987.14 | 23-DEC-08:63 | 7.55 |
Annual Sum or Average | 0.131816E+10 | |||
Minimum of Months | 448460.27 | 340.25 | 7.55 | |
Maximum of Months | 0.256017E+09 | 30253.26 | 43.35 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 49970995.46 | 30226.42 | 01-JAN-09:01 | 9.20 |
February | 775769.99 | 1404.09 | 02-FEB-08:63 | 8.07 |
March | 36178544.85 | 1896.69 | 12-MAR-16:02 | 31.18 |
April | 0.197171E+09 | 3847.70 | 16-APR-16:01 | 39.13 |
May | 0.242229E+09 | 4567.78 | 07-MAY-16:01 | 42.17 |
June | 0.258632E+09 | 4888.58 | 11-JUN-16:01 | 43.35 |
July | 0.192388E+09 | 4195.25 | 02-JUL-16:01 | 40.38 |
August | 0.161077E+09 | 3200.80 | 06-AUG-16:01 | 36.25 |
September | 0.142499E+09 | 2791.93 | 24-SEP-16:01 | 34.68 |
October | 70868602.12 | 2903.62 | 01-OCT-16:01 | 35.32 |
November | 6462956.11 | 1145.52 | 04-NOV-17:03 | 27.72 |
December | 1247152.50 | 5871.76 | 23-DEC-08:63 | 7.55 |
Annual Sum or Average | 0.135950E+10 | |||
Minimum of Months | 775769.99 | 1145.52 | 7.55 | |
Maximum of Months | 0.258632E+09 | 30226.42 | 43.35 |
Report: ZoneHeatingSummaryMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.114575E+09 | 55765.14 | 01-JAN-10:01 | 10.43 |
February | 4457658.20 | 13482.07 | 02-FEB-09:02 | 10.37 |
March | 38125153.12 | 3815.50 | 12-MAR-16:02 | 31.18 |
April | 0.210657E+09 | 7710.00 | 16-APR-16:01 | 39.13 |
May | 0.158169E+09 | 9149.34 | 07-MAY-16:01 | 42.17 |
June | 0.137088E+09 | 9784.21 | 11-JUN-16:01 | 43.35 |
July | 0.147452E+09 | 8395.99 | 02-JUL-16:01 | 40.38 |
August | 0.108663E+09 | 6399.93 | 06-AUG-16:01 | 36.25 |
September | 0.145078E+09 | 5589.94 | 24-SEP-16:01 | 34.68 |
October | 97984202.22 | 5819.13 | 01-OCT-16:01 | 35.32 |
November | 13264717.41 | 2291.41 | 04-NOV-17:03 | 27.72 |
December | 6514577.93 | 28373.48 | 23-DEC-09:02 | 10.55 |
Annual Sum or Average | 0.118203E+10 | |||
Minimum of Months | 4457658.20 | 2291.41 | 10.37 | |
Maximum of Months | 0.210657E+09 | 55765.14 | 43.35 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 62297026.85 | 29467.76 | 01-JAN-10:01 | 10.43 |
February | 1855564.33 | 5684.71 | 02-FEB-09:02 | 10.37 |
March | 20470016.69 | 1915.55 | 12-MAR-16:02 | 31.18 |
April | 0.111103E+09 | 3858.65 | 16-APR-16:01 | 39.13 |
May | 88148743.54 | 4576.79 | 07-MAY-16:01 | 42.17 |
June | 74700858.14 | 4895.25 | 11-JUN-16:01 | 43.35 |
July | 79191502.25 | 4202.56 | 02-JUL-16:01 | 40.38 |
August | 60085506.85 | 3208.34 | 06-AUG-16:01 | 36.25 |
September | 82255745.11 | 2802.44 | 24-SEP-16:01 | 34.68 |
October | 53663490.04 | 2915.12 | 01-OCT-16:01 | 35.32 |
November | 7359894.04 | 1168.38 | 04-NOV-17:03 | 27.72 |
December | 2704994.33 | 13318.73 | 23-DEC-09:02 | 10.55 |
Annual Sum or Average | 0.643836E+09 | |||
Minimum of Months | 1855564.33 | 1168.38 | 10.37 | |
Maximum of Months | 0.111103E+09 | 29467.76 | 43.35 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 66791148.46 | 29361.30 | 01-JAN-10:01 | 10.43 |
February | 2466335.53 | 6586.27 | 02-FEB-09:02 | 10.37 |
March | 20537828.10 | 1917.80 | 12-MAR-16:02 | 31.18 |
April | 0.113023E+09 | 3860.11 | 16-APR-16:01 | 39.13 |
May | 90623855.92 | 4578.00 | 07-MAY-16:01 | 42.17 |
June | 74696761.30 | 4896.24 | 11-JUN-16:01 | 43.35 |
July | 79241801.82 | 4203.61 | 02-JUL-16:01 | 40.38 |
August | 60012794.91 | 3209.24 | 06-AUG-16:01 | 36.25 |
September | 83556117.38 | 2803.65 | 24-SEP-16:01 | 34.68 |
October | 53356259.02 | 2916.38 | 01-OCT-16:01 | 35.32 |
November | 7388632.65 | 1170.37 | 04-NOV-17:03 | 27.72 |
December | 3058657.39 | 14511.86 | 23-DEC-09:02 | 10.55 |
Annual Sum or Average | 0.654754E+09 | |||
Minimum of Months | 2466335.53 | 1170.37 | 10.37 | |
Maximum of Months | 0.113023E+09 | 29361.30 | 43.35 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 80739460.15 | 29389.05 | 01-JAN-10:01 | 10.43 |
February | 4742877.59 | 9239.86 | 02-FEB-09:02 | 10.37 |
March | 20803762.25 | 1921.98 | 12-MAR-16:02 | 31.18 |
April | 0.117068E+09 | 3861.04 | 16-APR-16:01 | 39.13 |
May | 94282286.32 | 4577.85 | 07-MAY-16:01 | 42.17 |
June | 78202133.40 | 4895.37 | 11-JUN-16:01 | 43.35 |
July | 79955635.56 | 4202.28 | 02-JUL-16:01 | 40.38 |
August | 61701182.09 | 3207.57 | 06-AUG-16:01 | 36.25 |
September | 83928993.39 | 2802.31 | 24-SEP-16:01 | 34.68 |
October | 54714319.77 | 2915.35 | 01-OCT-16:01 | 35.32 |
November | 7437082.56 | 1173.20 | 04-NOV-17:03 | 27.72 |
December | 4197601.75 | 17606.26 | 23-DEC-09:02 | 10.55 |
Annual Sum or Average | 0.687773E+09 | |||
Minimum of Months | 4197601.75 | 1173.20 | 10.37 | |
Maximum of Months | 0.117068E+09 | 29389.05 | 43.35 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.108147E+09 | 31501.78 | 01-JAN-10:01 | 10.43 |
February | 12745818.40 | 16057.59 | 02-FEB-09:02 | 10.37 |
March | 21973979.47 | 1919.47 | 12-MAR-16:02 | 31.18 |
April | 0.122177E+09 | 3846.58 | 16-APR-16:01 | 39.13 |
May | 89610067.36 | 4557.23 | 07-MAY-16:01 | 42.17 |
June | 75030228.28 | 4872.06 | 11-JUN-16:01 | 43.35 |
July | 72601160.67 | 4171.67 | 02-JUL-16:01 | 40.38 |
August | 50896903.90 | 3174.80 | 06-AUG-16:01 | 36.25 |
September | 69497692.10 | 2769.49 | 24-SEP-16:01 | 34.68 |
October | 52351088.09 | 2883.78 | 01-OCT-16:01 | 35.32 |
November | 7335749.34 | 1164.42 | 04-NOV-17:03 | 27.72 |
December | 7777483.08 | 24011.80 | 23-DEC-09:02 | 10.55 |
Annual Sum or Average | 0.690144E+09 | |||
Minimum of Months | 7335749.34 | 1164.42 | 10.37 | |
Maximum of Months | 0.122177E+09 | 31501.78 | 43.35 |
Report: ZoneElectricSummaryMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.100203E+11 | 6078.71 | 01-JAN-10:09 | 0.223514E+10 | 1348.26 | 01-JAN-10:09 |
February | 0.906661E+10 | 6078.71 | 01-FEB-10:09 | 0.202238E+10 | 1348.26 | 01-FEB-10:09 |
March | 0.100410E+11 | 6078.71 | 01-MAR-10:09 | 0.223972E+10 | 1348.26 | 01-MAR-10:09 |
April | 0.972311E+10 | 6078.71 | 01-APR-09:09 | 0.216880E+10 | 1348.26 | 01-APR-09:09 |
May | 0.100203E+11 | 6078.71 | 01-MAY-09:09 | 0.223514E+10 | 1348.26 | 01-MAY-09:09 |
June | 0.972311E+10 | 6078.71 | 01-JUN-09:09 | 0.216880E+10 | 1348.26 | 01-JUN-09:09 |
July | 0.100410E+11 | 6078.71 | 01-JUL-09:09 | 0.223972E+10 | 1348.26 | 01-JUL-09:09 |
August | 0.100203E+11 | 6078.71 | 01-AUG-09:09 | 0.223514E+10 | 1348.26 | 01-AUG-09:09 |
September | 0.974384E+10 | 6078.71 | 01-SEP-09:09 | 0.217339E+10 | 1348.26 | 01-SEP-09:09 |
October | 0.100203E+11 | 6078.71 | 01-OCT-09:09 | 0.223514E+10 | 1348.26 | 01-OCT-09:09 |
November | 0.968165E+10 | 6078.71 | 01-NOV-09:09 | 0.215964E+10 | 1348.26 | 01-NOV-09:09 |
December | 0.100617E+11 | 6078.71 | 01-DEC-10:09 | 0.224431E+10 | 1348.26 | 01-DEC-10:09 |
Annual Sum or Average | 0.118163E+12 | 0.263573E+11 | ||||
Minimum of Months | 0.906661E+10 | 6078.71 | 0.202238E+10 | 1348.26 | ||
Maximum of Months | 0.100617E+11 | 6078.71 | 0.224431E+10 | 1348.26 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.540359E+10 | 3278.04 | 01-JAN-10:09 | 0.111757E+10 | 674.13 | 01-JAN-10:09 |
February | 0.488932E+10 | 3278.04 | 01-FEB-10:09 | 0.101119E+10 | 674.13 | 01-FEB-10:09 |
March | 0.541477E+10 | 3278.04 | 01-MAR-10:09 | 0.111986E+10 | 674.13 | 01-MAR-10:09 |
April | 0.524335E+10 | 3278.04 | 01-APR-09:09 | 0.108440E+10 | 674.13 | 01-APR-09:09 |
May | 0.540359E+10 | 3278.04 | 01-MAY-09:09 | 0.111757E+10 | 674.13 | 01-MAY-09:09 |
June | 0.524335E+10 | 3278.04 | 01-JUN-09:09 | 0.108440E+10 | 674.13 | 01-JUN-09:09 |
July | 0.541477E+10 | 3278.04 | 01-JUL-09:09 | 0.111986E+10 | 674.13 | 01-JUL-09:09 |
August | 0.540359E+10 | 3278.04 | 01-AUG-09:09 | 0.111757E+10 | 674.13 | 01-AUG-09:09 |
September | 0.525453E+10 | 3278.04 | 01-SEP-09:09 | 0.108669E+10 | 674.13 | 01-SEP-09:09 |
October | 0.540359E+10 | 3278.04 | 01-OCT-09:09 | 0.111757E+10 | 674.13 | 01-OCT-09:09 |
November | 0.522099E+10 | 3278.04 | 01-NOV-09:09 | 0.107982E+10 | 674.13 | 01-NOV-09:09 |
December | 0.542595E+10 | 3278.04 | 01-DEC-10:09 | 0.112215E+10 | 674.13 | 01-DEC-10:09 |
Annual Sum or Average | 0.637214E+11 | 0.131787E+11 | ||||
Minimum of Months | 0.488932E+10 | 3278.04 | 0.101119E+10 | 674.13 | ||
Maximum of Months | 0.542595E+10 | 3278.04 | 0.112215E+10 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.379993E+10 | 2921.79 | 01-JAN-10:09 | 0.883781E+09 | 674.13 | 01-JAN-10:09 |
February | 0.344119E+10 | 2921.79 | 01-FEB-09:09 | 0.800324E+09 | 674.13 | 01-FEB-09:09 |
March | 0.387965E+10 | 2921.79 | 01-MAR-09:09 | 0.902118E+09 | 674.13 | 01-MAR-09:09 |
April | 0.368699E+10 | 2921.79 | 01-APR-08:09 | 0.857490E+09 | 674.13 | 01-APR-08:09 |
May | 0.383979E+10 | 2921.79 | 01-MAY-08:09 | 0.892950E+09 | 674.13 | 01-MAY-08:09 |
June | 0.374678E+10 | 2921.79 | 01-JUN-08:09 | 0.871243E+09 | 674.13 | 01-JUN-08:09 |
July | 0.378000E+10 | 2921.79 | 01-JUL-08:09 | 0.879197E+09 | 674.13 | 01-JUL-08:09 |
August | 0.387965E+10 | 2921.79 | 01-AUG-08:09 | 0.902118E+09 | 674.13 | 01-AUG-08:09 |
September | 0.368699E+10 | 2921.79 | 01-SEP-08:09 | 0.857490E+09 | 674.13 | 01-SEP-08:09 |
October | 0.379993E+10 | 2921.79 | 01-OCT-09:09 | 0.883781E+09 | 674.13 | 01-OCT-09:09 |
November | 0.368699E+10 | 2921.79 | 01-NOV-08:09 | 0.857490E+09 | 674.13 | 01-NOV-08:09 |
December | 0.378000E+10 | 2921.79 | 01-DEC-09:09 | 0.879197E+09 | 674.13 | 01-DEC-09:09 |
Annual Sum or Average | 0.450079E+11 | 0.104672E+11 | ||||
Minimum of Months | 0.344119E+10 | 2921.79 | 0.800324E+09 | 674.13 | ||
Maximum of Months | 0.387965E+10 | 2921.79 | 0.902118E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.379993E+10 | 2921.79 | 01-JAN-10:09 | 0.883781E+09 | 674.13 | 01-JAN-10:09 |
February | 0.344119E+10 | 2921.79 | 01-FEB-09:09 | 0.800324E+09 | 674.13 | 01-FEB-09:09 |
March | 0.387965E+10 | 2921.79 | 01-MAR-09:09 | 0.902118E+09 | 674.13 | 01-MAR-09:09 |
April | 0.368699E+10 | 2921.79 | 01-APR-08:09 | 0.857490E+09 | 674.13 | 01-APR-08:09 |
May | 0.383979E+10 | 2921.79 | 01-MAY-08:09 | 0.892950E+09 | 674.13 | 01-MAY-08:09 |
June | 0.374678E+10 | 2921.79 | 01-JUN-08:09 | 0.871243E+09 | 674.13 | 01-JUN-08:09 |
July | 0.378000E+10 | 2921.79 | 01-JUL-08:09 | 0.879197E+09 | 674.13 | 01-JUL-08:09 |
August | 0.387965E+10 | 2921.79 | 01-AUG-08:09 | 0.902118E+09 | 674.13 | 01-AUG-08:09 |
September | 0.368699E+10 | 2921.79 | 01-SEP-08:09 | 0.857490E+09 | 674.13 | 01-SEP-08:09 |
October | 0.379993E+10 | 2921.79 | 01-OCT-09:09 | 0.883781E+09 | 674.13 | 01-OCT-09:09 |
November | 0.368699E+10 | 2921.79 | 01-NOV-08:09 | 0.857490E+09 | 674.13 | 01-NOV-08:09 |
December | 0.378000E+10 | 2921.79 | 01-DEC-09:09 | 0.879197E+09 | 674.13 | 01-DEC-09:09 |
Annual Sum or Average | 0.450079E+11 | 0.104672E+11 | ||||
Minimum of Months | 0.344119E+10 | 2921.79 | 0.800324E+09 | 674.13 | ||
Maximum of Months | 0.387965E+10 | 2921.79 | 0.902118E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.379993E+10 | 2921.79 | 01-JAN-10:09 | 0.883781E+09 | 674.13 | 01-JAN-10:09 |
February | 0.344119E+10 | 2921.79 | 01-FEB-09:09 | 0.800324E+09 | 674.13 | 01-FEB-09:09 |
March | 0.387965E+10 | 2921.79 | 01-MAR-09:09 | 0.902118E+09 | 674.13 | 01-MAR-09:09 |
April | 0.368699E+10 | 2921.79 | 01-APR-08:09 | 0.857490E+09 | 674.13 | 01-APR-08:09 |
May | 0.383979E+10 | 2921.79 | 01-MAY-08:09 | 0.892950E+09 | 674.13 | 01-MAY-08:09 |
June | 0.374678E+10 | 2921.79 | 01-JUN-08:09 | 0.871243E+09 | 674.13 | 01-JUN-08:09 |
July | 0.378000E+10 | 2921.79 | 01-JUL-08:09 | 0.879197E+09 | 674.13 | 01-JUL-08:09 |
August | 0.387965E+10 | 2921.79 | 01-AUG-08:09 | 0.902118E+09 | 674.13 | 01-AUG-08:09 |
September | 0.368699E+10 | 2921.79 | 01-SEP-08:09 | 0.857490E+09 | 674.13 | 01-SEP-08:09 |
October | 0.379993E+10 | 2921.79 | 01-OCT-09:09 | 0.883781E+09 | 674.13 | 01-OCT-09:09 |
November | 0.368699E+10 | 2921.79 | 01-NOV-08:09 | 0.857490E+09 | 674.13 | 01-NOV-08:09 |
December | 0.378000E+10 | 2921.79 | 01-DEC-09:09 | 0.879197E+09 | 674.13 | 01-DEC-09:09 |
Annual Sum or Average | 0.450079E+11 | 0.104672E+11 | ||||
Minimum of Months | 0.344119E+10 | 2921.79 | 0.800324E+09 | 674.13 | ||
Maximum of Months | 0.387965E+10 | 2921.79 | 0.902118E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.520705E+10 | 4358.02 | 01-JAN-11:09 | 0.162546E+10 | 1348.26 | 01-JAN-11:09 |
February | 0.471657E+10 | 4358.02 | 01-FEB-10:09 | 0.147229E+10 | 1348.26 | 01-FEB-10:09 |
March | 0.532596E+10 | 4358.02 | 01-MAR-10:09 | 0.166213E+10 | 1348.26 | 01-MAR-10:09 |
April | 0.505346E+10 | 4358.02 | 01-APR-09:09 | 0.157746E+10 | 1348.26 | 01-APR-09:09 |
May | 0.526650E+10 | 4358.02 | 01-MAY-09:09 | 0.164379E+10 | 1348.26 | 01-MAY-09:09 |
June | 0.514264E+10 | 4358.02 | 01-JUN-09:09 | 0.160496E+10 | 1348.26 | 01-JUN-09:09 |
July | 0.517732E+10 | 4358.02 | 01-JUL-09:09 | 0.161629E+10 | 1348.26 | 01-JUL-09:09 |
August | 0.532596E+10 | 4358.02 | 01-AUG-09:09 | 0.166213E+10 | 1348.26 | 01-AUG-09:09 |
September | 0.505346E+10 | 4358.02 | 01-SEP-09:09 | 0.157746E+10 | 1348.26 | 01-SEP-09:09 |
October | 0.520705E+10 | 4358.02 | 01-OCT-10:09 | 0.162546E+10 | 1348.26 | 01-OCT-10:09 |
November | 0.505346E+10 | 4358.02 | 01-NOV-09:09 | 0.157746E+10 | 1348.26 | 01-NOV-09:09 |
December | 0.517732E+10 | 4358.02 | 01-DEC-10:09 | 0.161629E+10 | 1348.26 | 01-DEC-10:09 |
Annual Sum or Average | 0.617068E+11 | 0.192612E+11 | ||||
Minimum of Months | 0.471657E+10 | 4358.02 | 0.147229E+10 | 1348.26 | ||
Maximum of Months | 0.532596E+10 | 4358.02 | 0.166213E+10 | 1348.26 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.260353E+10 | 2179.01 | 01-JAN-11:09 | 0.812728E+09 | 674.13 | 01-JAN-11:09 |
February | 0.235828E+10 | 2179.01 | 01-FEB-10:09 | 0.736147E+09 | 674.13 | 01-FEB-10:09 |
March | 0.266298E+10 | 2179.01 | 01-MAR-10:09 | 0.831065E+09 | 674.13 | 01-MAR-10:09 |
April | 0.252673E+10 | 2179.01 | 01-APR-09:09 | 0.788729E+09 | 674.13 | 01-APR-09:09 |
May | 0.263325E+10 | 2179.01 | 01-MAY-09:09 | 0.821897E+09 | 674.13 | 01-MAY-09:09 |
June | 0.257132E+10 | 2179.01 | 01-JUN-09:09 | 0.802482E+09 | 674.13 | 01-JUN-09:09 |
July | 0.258866E+10 | 2179.01 | 01-JUL-09:09 | 0.808144E+09 | 674.13 | 01-JUL-09:09 |
August | 0.266298E+10 | 2179.01 | 01-AUG-09:09 | 0.831065E+09 | 674.13 | 01-AUG-09:09 |
September | 0.252673E+10 | 2179.01 | 01-SEP-09:09 | 0.788729E+09 | 674.13 | 01-SEP-09:09 |
October | 0.260353E+10 | 2179.01 | 01-OCT-10:09 | 0.812728E+09 | 674.13 | 01-OCT-10:09 |
November | 0.252673E+10 | 2179.01 | 01-NOV-09:09 | 0.788729E+09 | 674.13 | 01-NOV-09:09 |
December | 0.258866E+10 | 2179.01 | 01-DEC-10:09 | 0.808144E+09 | 674.13 | 01-DEC-10:09 |
Annual Sum or Average | 0.308534E+11 | 0.963059E+10 | ||||
Minimum of Months | 0.235828E+10 | 2179.01 | 0.736147E+09 | 674.13 | ||
Maximum of Months | 0.266298E+10 | 2179.01 | 0.831065E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.260353E+10 | 2179.01 | 01-JAN-11:09 | 0.812728E+09 | 674.13 | 01-JAN-11:09 |
February | 0.235828E+10 | 2179.01 | 01-FEB-10:09 | 0.736147E+09 | 674.13 | 01-FEB-10:09 |
March | 0.266298E+10 | 2179.01 | 01-MAR-10:09 | 0.831065E+09 | 674.13 | 01-MAR-10:09 |
April | 0.252673E+10 | 2179.01 | 01-APR-09:09 | 0.788729E+09 | 674.13 | 01-APR-09:09 |
May | 0.263325E+10 | 2179.01 | 01-MAY-09:09 | 0.821897E+09 | 674.13 | 01-MAY-09:09 |
June | 0.257132E+10 | 2179.01 | 01-JUN-09:09 | 0.802482E+09 | 674.13 | 01-JUN-09:09 |
July | 0.258866E+10 | 2179.01 | 01-JUL-09:09 | 0.808144E+09 | 674.13 | 01-JUL-09:09 |
August | 0.266298E+10 | 2179.01 | 01-AUG-09:09 | 0.831065E+09 | 674.13 | 01-AUG-09:09 |
September | 0.252673E+10 | 2179.01 | 01-SEP-09:09 | 0.788729E+09 | 674.13 | 01-SEP-09:09 |
October | 0.260353E+10 | 2179.01 | 01-OCT-10:09 | 0.812728E+09 | 674.13 | 01-OCT-10:09 |
November | 0.252673E+10 | 2179.01 | 01-NOV-09:09 | 0.788729E+09 | 674.13 | 01-NOV-09:09 |
December | 0.258866E+10 | 2179.01 | 01-DEC-10:09 | 0.808144E+09 | 674.13 | 01-DEC-10:09 |
Annual Sum or Average | 0.308534E+11 | 0.963059E+10 | ||||
Minimum of Months | 0.235828E+10 | 2179.01 | 0.736147E+09 | 674.13 | ||
Maximum of Months | 0.266298E+10 | 2179.01 | 0.831065E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.260353E+10 | 2179.01 | 01-JAN-11:09 | 0.812728E+09 | 674.13 | 01-JAN-11:09 |
February | 0.235828E+10 | 2179.01 | 01-FEB-10:09 | 0.736147E+09 | 674.13 | 01-FEB-10:09 |
March | 0.266298E+10 | 2179.01 | 01-MAR-10:09 | 0.831065E+09 | 674.13 | 01-MAR-10:09 |
April | 0.252673E+10 | 2179.01 | 01-APR-09:09 | 0.788729E+09 | 674.13 | 01-APR-09:09 |
May | 0.263325E+10 | 2179.01 | 01-MAY-09:09 | 0.821897E+09 | 674.13 | 01-MAY-09:09 |
June | 0.257132E+10 | 2179.01 | 01-JUN-09:09 | 0.802482E+09 | 674.13 | 01-JUN-09:09 |
July | 0.258866E+10 | 2179.01 | 01-JUL-09:09 | 0.808144E+09 | 674.13 | 01-JUL-09:09 |
August | 0.266298E+10 | 2179.01 | 01-AUG-09:09 | 0.831065E+09 | 674.13 | 01-AUG-09:09 |
September | 0.252673E+10 | 2179.01 | 01-SEP-09:09 | 0.788729E+09 | 674.13 | 01-SEP-09:09 |
October | 0.260353E+10 | 2179.01 | 01-OCT-10:09 | 0.812728E+09 | 674.13 | 01-OCT-10:09 |
November | 0.252673E+10 | 2179.01 | 01-NOV-09:09 | 0.788729E+09 | 674.13 | 01-NOV-09:09 |
December | 0.258866E+10 | 2179.01 | 01-DEC-10:09 | 0.808144E+09 | 674.13 | 01-DEC-10:09 |
Annual Sum or Average | 0.308534E+11 | 0.963059E+10 | ||||
Minimum of Months | 0.235828E+10 | 2179.01 | 0.736147E+09 | 674.13 | ||
Maximum of Months | 0.266298E+10 | 2179.01 | 0.831065E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.260353E+10 | 2179.01 | 01-JAN-11:09 | 0.812728E+09 | 674.13 | 01-JAN-11:09 |
February | 0.235828E+10 | 2179.01 | 01-FEB-10:09 | 0.736147E+09 | 674.13 | 01-FEB-10:09 |
March | 0.266298E+10 | 2179.01 | 01-MAR-10:09 | 0.831065E+09 | 674.13 | 01-MAR-10:09 |
April | 0.252673E+10 | 2179.01 | 01-APR-09:09 | 0.788729E+09 | 674.13 | 01-APR-09:09 |
May | 0.263325E+10 | 2179.01 | 01-MAY-09:09 | 0.821897E+09 | 674.13 | 01-MAY-09:09 |
June | 0.257132E+10 | 2179.01 | 01-JUN-09:09 | 0.802482E+09 | 674.13 | 01-JUN-09:09 |
July | 0.258866E+10 | 2179.01 | 01-JUL-09:09 | 0.808144E+09 | 674.13 | 01-JUL-09:09 |
August | 0.266298E+10 | 2179.01 | 01-AUG-09:09 | 0.831065E+09 | 674.13 | 01-AUG-09:09 |
September | 0.252673E+10 | 2179.01 | 01-SEP-09:09 | 0.788729E+09 | 674.13 | 01-SEP-09:09 |
October | 0.260353E+10 | 2179.01 | 01-OCT-10:09 | 0.812728E+09 | 674.13 | 01-OCT-10:09 |
November | 0.252673E+10 | 2179.01 | 01-NOV-09:09 | 0.788729E+09 | 674.13 | 01-NOV-09:09 |
December | 0.258866E+10 | 2179.01 | 01-DEC-10:09 | 0.808144E+09 | 674.13 | 01-DEC-10:09 |
Annual Sum or Average | 0.308534E+11 | 0.963059E+10 | ||||
Minimum of Months | 0.235828E+10 | 2179.01 | 0.736147E+09 | 674.13 | ||
Maximum of Months | 0.266298E+10 | 2179.01 | 0.831065E+09 | 674.13 |
Report: SpaceGainsMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.180574E+10 | 0.100203E+11 | 0.223514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.200616E+10 |
February | 0.163016E+10 | 0.906661E+10 | 0.202238E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120695E+09 | 0.848385E+09 |
March | 0.178954E+10 | 0.100410E+11 | 0.223972E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122873E+10 | 0.209738E+09 |
April | 0.174484E+10 | 0.972311E+10 | 0.216880E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.328739E+10 | 14456638.32 |
May | 0.179537E+10 | 0.100203E+11 | 0.223514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.464691E+10 | 4395734.37 |
June | 0.173447E+10 | 0.972311E+10 | 0.216880E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.421385E+10 | 1916091.39 |
July | 0.181028E+10 | 0.100410E+11 | 0.223972E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.339296E+10 | 1132947.71 |
August | 0.178501E+10 | 0.100203E+11 | 0.223514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.287235E+10 | 2134047.24 |
September | 0.174937E+10 | 0.974384E+10 | 0.217339E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.251077E+10 | 5839935.29 |
October | 0.180574E+10 | 0.100203E+11 | 0.223514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.218084E+10 | 45707369.59 |
November | 0.174613E+10 | 0.968165E+10 | 0.215964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.743607E+09 | 0.259539E+09 |
December | 0.181481E+10 | 0.100617E+11 | 0.224431E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5217178.07 | 0.171767E+10 |
Annual Sum or Average | 0.212115E+11 | 0.118163E+12 | 0.263573E+11 | 0.252033E+11 | 0.511707E+10 | ||||
Minimum of Months | 0.163016E+10 | 0.906661E+10 | 0.202238E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1132947.71 |
Maximum of Months | 0.181481E+10 | 0.100617E+11 | 0.224431E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.464691E+10 | 0.200616E+10 |
Report: SpaceGainsMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.902868E+09 | 0.540359E+10 | 0.111757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112840E+10 |
February | 0.815075E+09 | 0.488932E+10 | 0.101119E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 68426298.34 | 0.453752E+09 |
March | 0.894769E+09 | 0.541477E+10 | 0.111986E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.695301E+09 | 97348200.93 |
April | 0.872416E+09 | 0.524335E+10 | 0.108440E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185244E+10 | 6476423.96 |
May | 0.897684E+09 | 0.540359E+10 | 0.111757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.260235E+10 | 1671717.45 |
June | 0.867232E+09 | 0.524335E+10 | 0.108440E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.237005E+10 | 637214.34 |
July | 0.905135E+09 | 0.541477E+10 | 0.111986E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189474E+10 | 339834.30 |
August | 0.892501E+09 | 0.540359E+10 | 0.111757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161500E+10 | 745924.66 |
September | 0.874683E+09 | 0.525453E+10 | 0.108669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141908E+10 | 2189466.25 |
October | 0.902868E+09 | 0.540359E+10 | 0.111757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123842E+10 | 23424318.56 |
November | 0.873064E+09 | 0.522099E+10 | 0.107982E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.423063E+09 | 0.138896E+09 |
December | 0.907403E+09 | 0.542595E+10 | 0.112215E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2963255.92 | 0.956442E+09 |
Annual Sum or Average | 0.106057E+11 | 0.637214E+11 | 0.131787E+11 | 0.141818E+11 | 0.281032E+10 | ||||
Minimum of Months | 0.815075E+09 | 0.488932E+10 | 0.101119E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 339834.30 |
Maximum of Months | 0.907403E+09 | 0.542595E+10 | 0.112215E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.260235E+10 | 0.112840E+10 |
Report: SpaceGainsMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.537120E+09 | 0.379993E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110723E+10 |
February | 0.487879E+09 | 0.344119E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 68337624.55 | 0.466128E+09 |
March | 0.551374E+09 | 0.387965E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.683892E+09 | 0.106139E+09 |
April | 0.524810E+09 | 0.368699E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183165E+10 | 6322204.06 |
May | 0.544247E+09 | 0.383979E+10 | 0.892950E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.258057E+10 | 1423696.48 |
June | 0.532585E+09 | 0.374678E+10 | 0.871243E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.235645E+10 | 817086.26 |
July | 0.536472E+09 | 0.378000E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.186872E+10 | 376923.64 |
August | 0.551374E+09 | 0.387965E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160081E+10 | 1184403.15 |
September | 0.524810E+09 | 0.368699E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140062E+10 | 2196820.55 |
October | 0.537120E+09 | 0.379993E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121175E+10 | 21315122.64 |
November | 0.518979E+09 | 0.368699E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.418360E+09 | 0.147074E+09 |
December | 0.536472E+09 | 0.378000E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2963061.69 | 0.955239E+09 |
Annual Sum or Average | 0.638324E+10 | 0.450079E+11 | 0.104672E+11 | 0.140241E+11 | 0.281545E+10 | ||||
Minimum of Months | 0.487879E+09 | 0.344119E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 376923.64 |
Maximum of Months | 0.551374E+09 | 0.387965E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.258057E+10 | 0.110723E+10 |
Report: SpaceGainsMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.537120E+09 | 0.379993E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109362E+10 |
February | 0.487879E+09 | 0.344119E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 68337977.09 | 0.463847E+09 |
March | 0.551374E+09 | 0.387965E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.683872E+09 | 0.105948E+09 |
April | 0.524810E+09 | 0.368699E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183132E+10 | 6421652.72 |
May | 0.544247E+09 | 0.383979E+10 | 0.892950E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.257954E+10 | 1523871.24 |
June | 0.532585E+09 | 0.374678E+10 | 0.871243E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.235573E+10 | 876633.63 |
July | 0.536472E+09 | 0.378000E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.186748E+10 | 423766.60 |
August | 0.551374E+09 | 0.387965E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160021E+10 | 1269768.24 |
September | 0.524810E+09 | 0.368699E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140028E+10 | 2360523.04 |
October | 0.537120E+09 | 0.379993E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121152E+10 | 21403779.61 |
November | 0.518979E+09 | 0.368699E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.418368E+09 | 0.146758E+09 |
December | 0.536472E+09 | 0.378000E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2963027.91 | 0.950986E+09 |
Annual Sum or Average | 0.638324E+10 | 0.450079E+11 | 0.104672E+11 | 0.140196E+11 | 0.279544E+10 | ||||
Minimum of Months | 0.487879E+09 | 0.344119E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 423766.60 |
Maximum of Months | 0.551374E+09 | 0.387965E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.257954E+10 | 0.109362E+10 |
Report: SpaceGainsMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.537120E+09 | 0.379993E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107771E+10 |
February | 0.487879E+09 | 0.344119E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 68338328.33 | 0.460005E+09 |
March | 0.551374E+09 | 0.387965E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.684047E+09 | 0.104804E+09 |
April | 0.524810E+09 | 0.368699E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183173E+10 | 6182825.21 |
May | 0.544247E+09 | 0.383979E+10 | 0.892950E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.258025E+10 | 1408398.46 |
June | 0.532585E+09 | 0.374678E+10 | 0.871243E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.235628E+10 | 838870.40 |
July | 0.536472E+09 | 0.378000E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.186832E+10 | 374081.53 |
August | 0.551374E+09 | 0.387965E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160075E+10 | 1142561.46 |
September | 0.524810E+09 | 0.368699E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140060E+10 | 2139396.51 |
October | 0.537120E+09 | 0.379993E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121180E+10 | 21218710.61 |
November | 0.518979E+09 | 0.368699E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.418401E+09 | 0.145966E+09 |
December | 0.536472E+09 | 0.378000E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2962990.80 | 0.945313E+09 |
Annual Sum or Average | 0.638324E+10 | 0.450079E+11 | 0.104672E+11 | 0.140235E+11 | 0.276711E+10 | ||||
Minimum of Months | 0.487879E+09 | 0.344119E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 374081.53 |
Maximum of Months | 0.551374E+09 | 0.387965E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.258025E+10 | 0.107771E+10 |
Report: SpaceGainsMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.183632E+10 | 0.520705E+10 | 0.162546E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.184548E+10 |
February | 0.167188E+10 | 0.471657E+10 | 0.147229E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119707E+09 | 0.807221E+09 |
March | 0.189386E+10 | 0.532596E+10 | 0.166213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119931E+10 | 0.192138E+09 |
April | 0.180380E+10 | 0.505346E+10 | 0.157746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.320304E+10 | 14205282.44 |
May | 0.186509E+10 | 0.526650E+10 | 0.164379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.451639E+10 | 3761556.98 |
June | 0.182945E+10 | 0.514264E+10 | 0.160496E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.411943E+10 | 1932909.23 |
July | 0.183943E+10 | 0.517732E+10 | 0.161629E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.326682E+10 | 713694.66 |
August | 0.189386E+10 | 0.532596E+10 | 0.166213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.279212E+10 | 2510796.18 |
September | 0.180380E+10 | 0.505346E+10 | 0.157746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.243949E+10 | 6106235.42 |
October | 0.183632E+10 | 0.520705E+10 | 0.162546E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.212066E+10 | 46692735.22 |
November | 0.176881E+10 | 0.505346E+10 | 0.157746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.732733E+09 | 0.259061E+09 |
December | 0.183943E+10 | 0.517732E+10 | 0.161629E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5188844.74 | 0.164564E+10 |
Annual Sum or Average | 0.218821E+11 | 0.617068E+11 | 0.192612E+11 | 0.245149E+11 | 0.482546E+10 | ||||
Minimum of Months | 0.167188E+10 | 0.471657E+10 | 0.147229E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 713694.66 |
Maximum of Months | 0.189386E+10 | 0.532596E+10 | 0.166213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.451639E+10 | 0.184548E+10 |
Report: SpaceGainsMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.918158E+09 | 0.260353E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104057E+10 |
February | 0.835938E+09 | 0.235828E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 68343266.59 | 0.453025E+09 |
March | 0.946926E+09 | 0.266298E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.684688E+09 | 0.104726E+09 |
April | 0.901896E+09 | 0.252673E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182743E+10 | 7455675.21 |
May | 0.932542E+09 | 0.263325E+10 | 0.821897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.257413E+10 | 1854261.84 |
June | 0.914724E+09 | 0.257132E+10 | 0.802482E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.234921E+10 | 955142.28 |
July | 0.919713E+09 | 0.258866E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.186143E+10 | 320173.28 |
August | 0.946926E+09 | 0.266298E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159269E+10 | 1213656.13 |
September | 0.901896E+09 | 0.252673E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139264E+10 | 2969844.27 |
October | 0.918158E+09 | 0.260353E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121134E+10 | 25904339.63 |
November | 0.884402E+09 | 0.252673E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.418536E+09 | 0.146114E+09 |
December | 0.919713E+09 | 0.258866E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2963141.61 | 0.932437E+09 |
Annual Sum or Average | 0.109410E+11 | 0.308534E+11 | 0.963059E+10 | 0.139834E+11 | 0.271754E+10 | ||||
Minimum of Months | 0.835938E+09 | 0.235828E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 320173.28 |
Maximum of Months | 0.946926E+09 | 0.266298E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.257413E+10 | 0.104057E+10 |
Report: SpaceGainsMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.918158E+09 | 0.260353E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103377E+10 |
February | 0.835938E+09 | 0.235828E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 68343485.73 | 0.451018E+09 |
March | 0.946926E+09 | 0.266298E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.684771E+09 | 0.104148E+09 |
April | 0.901896E+09 | 0.252673E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182768E+10 | 7312083.65 |
May | 0.932542E+09 | 0.263325E+10 | 0.821897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.257441E+10 | 1807569.11 |
June | 0.914724E+09 | 0.257132E+10 | 0.802482E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.234944E+10 | 938485.15 |
July | 0.919713E+09 | 0.258866E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.186174E+10 | 309175.61 |
August | 0.946926E+09 | 0.266298E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159291E+10 | 1183198.02 |
September | 0.901896E+09 | 0.252673E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139280E+10 | 2886479.94 |
October | 0.918158E+09 | 0.260353E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121147E+10 | 25752823.40 |
November | 0.884402E+09 | 0.252673E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.418549E+09 | 0.145745E+09 |
December | 0.919713E+09 | 0.258866E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2963236.95 | 0.929664E+09 |
Annual Sum or Average | 0.109410E+11 | 0.308534E+11 | 0.963059E+10 | 0.139851E+11 | 0.270454E+10 | ||||
Minimum of Months | 0.835938E+09 | 0.235828E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 309175.61 |
Maximum of Months | 0.946926E+09 | 0.266298E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.257441E+10 | 0.103377E+10 |
Report: SpaceGainsMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.918158E+09 | 0.260353E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101945E+10 |
February | 0.835938E+09 | 0.235828E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 68343831.14 | 0.445303E+09 |
March | 0.946926E+09 | 0.266298E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.684938E+09 | 0.102266E+09 |
April | 0.901896E+09 | 0.252673E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182816E+10 | 6913804.08 |
May | 0.932542E+09 | 0.263325E+10 | 0.821897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.257476E+10 | 1691148.55 |
June | 0.914724E+09 | 0.257132E+10 | 0.802482E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.234959E+10 | 913494.52 |
July | 0.919713E+09 | 0.258866E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.186176E+10 | 293636.53 |
August | 0.946926E+09 | 0.266298E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159290E+10 | 1168058.35 |
September | 0.901896E+09 | 0.252673E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139282E+10 | 2796354.52 |
October | 0.918158E+09 | 0.260353E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121152E+10 | 25514639.51 |
November | 0.884402E+09 | 0.252673E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.418565E+09 | 0.144841E+09 |
December | 0.919713E+09 | 0.258866E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2963205.62 | 0.923034E+09 |
Annual Sum or Average | 0.109410E+11 | 0.308534E+11 | 0.963059E+10 | 0.139863E+11 | 0.267419E+10 | ||||
Minimum of Months | 0.835938E+09 | 0.235828E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 293636.53 |
Maximum of Months | 0.946926E+09 | 0.266298E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.257476E+10 | 0.101945E+10 |
Report: SpaceGainsMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.918158E+09 | 0.260353E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106512E+10 |
February | 0.835938E+09 | 0.235828E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 69182382.00 | 0.500695E+09 |
March | 0.946926E+09 | 0.266298E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.695302E+09 | 0.139735E+09 |
April | 0.901896E+09 | 0.252673E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.187059E+10 | 9725130.19 |
May | 0.932542E+09 | 0.263325E+10 | 0.821897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.266124E+10 | 3217206.94 |
June | 0.914724E+09 | 0.257132E+10 | 0.802482E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.241369E+10 | 1900214.25 |
July | 0.919713E+09 | 0.258866E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.193147E+10 | 832820.31 |
August | 0.946926E+09 | 0.266298E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163219E+10 | 2450465.06 |
September | 0.901896E+09 | 0.252673E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141518E+10 | 6122410.75 |
October | 0.918158E+09 | 0.260353E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122188E+10 | 31065579.86 |
November | 0.884402E+09 | 0.252673E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.421407E+09 | 0.161035E+09 |
December | 0.919713E+09 | 0.258866E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2991607.23 | 0.973919E+09 |
Annual Sum or Average | 0.109410E+11 | 0.308534E+11 | 0.963059E+10 | 0.143351E+11 | 0.289582E+10 | ||||
Minimum of Months | 0.835938E+09 | 0.235828E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 832820.31 |
Maximum of Months | 0.946926E+09 | 0.266298E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.266124E+10 | 0.106512E+10 |
Report: PeakSpaceGainsMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2159.72 | 01-JAN-13:09 | 6078.71 | 01-JAN-10:09 | 1348.26 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 4265.72 | 15-JAN-18:00 |
February | 2159.72 | 03-FEB-13:09 | 6078.71 | 01-FEB-10:09 | 1348.26 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1447.29 | 22-FEB-15:00 | 3836.92 | 10-FEB-18:00 |
March | 2159.72 | 03-MAR-13:09 | 6078.71 | 01-MAR-10:09 | 1348.26 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5081.45 | 28-MAR-15:00 | 1577.60 | 18-MAR-17:00 |
April | 2159.72 | 01-APR-12:09 | 6078.71 | 01-APR-09:09 | 1348.26 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 7288.71 | 15-APR-15:00 | 332.51 | 10-APR-07:05 |
May | 2159.72 | 05-MAY-12:09 | 6078.71 | 01-MAY-09:09 | 1348.26 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8781.45 | 03-MAY-15:00 | 135.22 | 13-MAY-07:10 |
June | 2159.72 | 02-JUN-12:09 | 6078.71 | 01-JUN-09:09 | 1348.26 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8808.85 | 06-JUN-15:00 | 95.87 | 24-JUN-08:00 |
July | 2159.72 | 01-JUL-12:09 | 6078.71 | 01-JUL-09:09 | 1348.26 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 7083.41 | 07-JUL-15:00 | 77.93 | 19-JUL-03:00 |
August | 2159.72 | 04-AUG-12:09 | 6078.71 | 01-AUG-09:09 | 1348.26 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5871.54 | 07-AUG-15:00 | 147.37 | 16-AUG-07:01 |
September | 2159.72 | 01-SEP-12:09 | 6078.71 | 01-SEP-09:09 | 1348.26 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5407.49 | 29-SEP-13:00 | 139.54 | 07-SEP-07:01 |
October | 2159.72 | 01-OCT-12:09 | 6078.71 | 01-OCT-09:09 | 1348.26 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5500.05 | 02-OCT-14:00 | 522.24 | 31-OCT-07:05 |
November | 2159.72 | 03-NOV-12:09 | 6078.71 | 01-NOV-09:09 | 1348.26 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2858.31 | 04-NOV-14:00 | 2233.41 | 30-NOV-18:00 |
December | 2159.72 | 01-DEC-13:09 | 6078.71 | 01-DEC-10:09 | 1348.26 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 323.81 | 28-DEC-14:00 | 4988.74 | 31-DEC-18:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2159.72 | 6078.71 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.93 | |||||
Maximum of Months | 2159.72 | 6078.71 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 8808.85 | 4988.74 |
Report: PeakSpaceGainsMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1079.86 | 01-JAN-13:09 | 3278.04 | 01-JAN-10:09 | 674.13 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 2453.08 | 15-JAN-18:00 |
February | 1079.86 | 03-FEB-13:09 | 3278.04 | 01-FEB-10:09 | 674.13 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 823.25 | 22-FEB-15:00 | 2258.56 | 10-FEB-12:10 |
March | 1079.86 | 03-MAR-13:09 | 3278.04 | 01-MAR-10:09 | 674.13 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2904.55 | 28-MAR-15:00 | 894.18 | 18-MAR-17:00 |
April | 1079.86 | 01-APR-12:09 | 3278.04 | 01-APR-09:09 | 674.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4078.50 | 15-APR-15:00 | 194.83 | 10-APR-07:05 |
May | 1079.86 | 05-MAY-12:09 | 3278.04 | 01-MAY-09:09 | 674.13 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4974.19 | 03-MAY-15:00 | 80.42 | 13-MAY-07:10 |
June | 1079.86 | 02-JUN-12:09 | 3278.04 | 01-JUN-09:09 | 674.13 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4982.70 | 07-JUN-16:00 | 49.08 | 24-JUN-08:00 |
July | 1079.86 | 01-JUL-12:09 | 3278.04 | 01-JUL-09:09 | 674.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4020.10 | 07-JUL-15:00 | 22.47 | 19-JUL-03:00 |
August | 1079.86 | 04-AUG-12:09 | 3278.04 | 01-AUG-09:09 | 674.13 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3323.82 | 07-AUG-15:00 | 80.70 | 16-AUG-07:10 |
September | 1079.86 | 01-SEP-12:09 | 3278.04 | 01-SEP-09:09 | 674.13 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3058.19 | 29-SEP-13:00 | 77.87 | 07-SEP-08:00 |
October | 1079.86 | 01-OCT-12:09 | 3278.04 | 01-OCT-09:09 | 674.13 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3125.49 | 02-OCT-14:00 | 301.88 | 31-OCT-07:05 |
November | 1079.86 | 03-NOV-12:09 | 3278.04 | 01-NOV-09:09 | 674.13 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1627.96 | 04-NOV-14:00 | 1272.87 | 30-NOV-18:00 |
December | 1079.86 | 01-DEC-13:09 | 3278.04 | 01-DEC-10:09 | 674.13 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 183.43 | 28-DEC-14:00 | 2900.22 | 21-DEC-12:05 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1079.86 | 3278.04 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.47 | |||||
Maximum of Months | 1079.86 | 3278.04 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 4982.70 | 2900.22 |
Report: PeakSpaceGainsMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1079.86 | 07-JAN-13:09 | 2921.79 | 01-JAN-10:09 | 674.13 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 2346.68 | 15-JAN-17:00 |
February | 1079.86 | 04-FEB-13:09 | 2921.79 | 01-FEB-09:09 | 674.13 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 823.23 | 22-FEB-15:00 | 2226.07 | 10-FEB-12:10 |
March | 1079.86 | 04-MAR-13:09 | 2921.79 | 01-MAR-09:09 | 674.13 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2904.56 | 28-MAR-15:00 | 894.21 | 18-MAR-17:00 |
April | 1079.86 | 01-APR-12:09 | 2921.79 | 01-APR-08:09 | 674.13 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4078.50 | 15-APR-15:00 | 181.99 | 22-APR-19:00 |
May | 1079.86 | 06-MAY-12:09 | 2921.79 | 01-MAY-08:09 | 674.13 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4974.18 | 03-MAY-15:00 | 54.42 | 13-MAY-07:02 |
June | 1079.86 | 03-JUN-12:09 | 2921.79 | 01-JUN-08:09 | 674.13 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4982.69 | 07-JUN-16:00 | 65.26 | 18-JUN-07:10 |
July | 1079.86 | 01-JUL-12:09 | 2921.79 | 01-JUL-08:09 | 674.13 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4020.09 | 07-JUL-15:00 | 24.34 | 19-JUL-03:00 |
August | 1079.86 | 05-AUG-12:09 | 2921.79 | 01-AUG-08:09 | 674.13 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3323.82 | 07-AUG-15:00 | 181.25 | 20-AUG-17:00 |
September | 1079.86 | 02-SEP-12:09 | 2921.79 | 01-SEP-08:09 | 674.13 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3058.15 | 29-SEP-13:00 | 77.57 | 03-SEP-17:00 |
October | 1079.86 | 07-OCT-12:09 | 2921.79 | 01-OCT-09:09 | 674.13 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3125.48 | 02-OCT-14:00 | 291.79 | 29-OCT-07:03 |
November | 1079.86 | 04-NOV-12:09 | 2921.79 | 01-NOV-08:09 | 674.13 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1627.96 | 04-NOV-14:00 | 1272.87 | 30-NOV-18:00 |
December | 1079.86 | 02-DEC-13:09 | 2921.79 | 01-DEC-09:09 | 674.13 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 183.42 | 28-DEC-14:00 | 2850.16 | 21-DEC-12:05 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1079.86 | 2921.79 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.34 | |||||
Maximum of Months | 1079.86 | 2921.79 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 4982.69 | 2850.16 |
Report: PeakSpaceGainsMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1079.86 | 07-JAN-13:09 | 2921.79 | 01-JAN-10:09 | 674.13 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 2323.45 | 15-JAN-17:00 |
February | 1079.86 | 04-FEB-13:09 | 2921.79 | 01-FEB-09:09 | 674.13 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 823.23 | 22-FEB-15:00 | 2208.19 | 10-FEB-12:10 |
March | 1079.86 | 04-MAR-13:09 | 2921.79 | 01-MAR-09:09 | 674.13 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2904.56 | 28-MAR-15:00 | 894.21 | 18-MAR-17:00 |
April | 1079.86 | 01-APR-12:09 | 2921.79 | 01-APR-08:09 | 674.13 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4078.50 | 15-APR-15:00 | 182.46 | 22-APR-19:00 |
May | 1079.86 | 06-MAY-12:09 | 2921.79 | 01-MAY-08:09 | 674.13 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4974.18 | 03-MAY-15:00 | 55.46 | 13-MAY-07:02 |
June | 1079.86 | 03-JUN-12:09 | 2921.79 | 01-JUN-08:09 | 674.13 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4982.69 | 07-JUN-16:00 | 65.46 | 18-JUN-07:02 |
July | 1079.86 | 01-JUL-12:09 | 2921.79 | 01-JUL-08:09 | 674.13 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4020.09 | 07-JUL-15:00 | 24.89 | 19-JUL-03:00 |
August | 1079.86 | 05-AUG-12:09 | 2921.79 | 01-AUG-08:09 | 674.13 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3323.83 | 07-AUG-15:00 | 187.55 | 20-AUG-17:00 |
September | 1079.86 | 02-SEP-12:09 | 2921.79 | 01-SEP-08:09 | 674.13 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3058.15 | 29-SEP-13:00 | 85.46 | 03-SEP-17:00 |
October | 1079.86 | 07-OCT-12:09 | 2921.79 | 01-OCT-09:09 | 674.13 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3125.48 | 02-OCT-14:00 | 292.16 | 29-OCT-07:03 |
November | 1079.86 | 04-NOV-12:09 | 2921.79 | 01-NOV-08:09 | 674.13 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1627.96 | 04-NOV-14:00 | 1272.87 | 30-NOV-18:00 |
December | 1079.86 | 02-DEC-13:09 | 2921.79 | 01-DEC-09:09 | 674.13 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 183.42 | 28-DEC-14:00 | 2829.35 | 21-DEC-12:05 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1079.86 | 2921.79 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.89 | |||||
Maximum of Months | 1079.86 | 2921.79 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 4982.69 | 2829.35 |
Report: PeakSpaceGainsMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1079.86 | 07-JAN-13:09 | 2921.79 | 01-JAN-10:09 | 674.13 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 2289.86 | 15-JAN-17:00 |
February | 1079.86 | 04-FEB-13:09 | 2921.79 | 01-FEB-09:09 | 674.13 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 823.23 | 22-FEB-15:00 | 2166.08 | 10-FEB-12:10 |
March | 1079.86 | 04-MAR-13:09 | 2921.79 | 01-MAR-09:09 | 674.13 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2904.56 | 28-MAR-15:00 | 894.22 | 18-MAR-17:00 |
April | 1079.86 | 01-APR-12:09 | 2921.79 | 01-APR-08:09 | 674.13 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4078.50 | 15-APR-15:00 | 178.15 | 22-APR-19:00 |
May | 1079.86 | 06-MAY-12:09 | 2921.79 | 01-MAY-08:09 | 674.13 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4974.18 | 03-MAY-15:00 | 51.89 | 13-MAY-07:02 |
June | 1079.86 | 03-JUN-12:09 | 2921.79 | 01-JUN-08:09 | 674.13 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4982.69 | 07-JUN-16:00 | 65.31 | 18-JUN-07:02 |
July | 1079.86 | 01-JUL-12:09 | 2921.79 | 01-JUL-08:09 | 674.13 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4020.09 | 07-JUL-15:00 | 24.06 | 19-JUL-03:00 |
August | 1079.86 | 05-AUG-12:09 | 2921.79 | 01-AUG-08:09 | 674.13 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3323.83 | 07-AUG-15:00 | 178.32 | 20-AUG-17:00 |
September | 1079.86 | 02-SEP-12:09 | 2921.79 | 01-SEP-08:09 | 674.13 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3058.15 | 29-SEP-13:00 | 76.88 | 03-SEP-17:00 |
October | 1079.86 | 07-OCT-12:09 | 2921.79 | 01-OCT-09:09 | 674.13 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3125.48 | 02-OCT-14:00 | 288.34 | 29-OCT-07:03 |
November | 1079.86 | 04-NOV-12:09 | 2921.79 | 01-NOV-08:09 | 674.13 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1627.95 | 04-NOV-14:00 | 1272.86 | 30-NOV-18:00 |
December | 1079.86 | 02-DEC-13:09 | 2921.79 | 01-DEC-09:09 | 674.13 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 183.42 | 28-DEC-14:00 | 2793.30 | 21-DEC-12:05 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1079.86 | 2921.79 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.06 | |||||
Maximum of Months | 1079.86 | 2921.79 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 4982.69 | 2793.30 |
Report: PeakSpaceGainsMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2879.63 | 07-JAN-15:09 | 4358.02 | 01-JAN-11:09 | 1348.26 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 3884.00 | 15-JAN-17:00 |
February | 2879.63 | 04-FEB-15:09 | 4358.02 | 01-FEB-10:09 | 1348.26 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1441.23 | 22-FEB-15:00 | 3642.36 | 10-FEB-12:10 |
March | 2879.63 | 04-MAR-15:09 | 4358.02 | 01-MAR-10:09 | 1348.26 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5081.51 | 28-MAR-15:00 | 1566.32 | 18-MAR-17:00 |
April | 2879.63 | 01-APR-14:09 | 4358.02 | 01-APR-09:09 | 1348.26 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 7157.76 | 15-APR-15:00 | 347.63 | 10-APR-07:05 |
May | 2879.63 | 06-MAY-14:09 | 4358.02 | 01-MAY-09:09 | 1348.26 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8713.71 | 03-MAY-15:00 | 130.88 | 13-MAY-07:10 |
June | 2879.63 | 03-JUN-14:09 | 4358.02 | 01-JUN-09:09 | 1348.26 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8729.84 | 07-JUN-16:00 | 131.39 | 18-JUN-07:02 |
July | 2879.63 | 01-JUL-14:09 | 4358.02 | 01-JUL-09:09 | 1348.26 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 7040.35 | 07-JUL-15:00 | 45.12 | 19-JUL-03:00 |
August | 2879.63 | 05-AUG-14:09 | 4358.02 | 01-AUG-09:09 | 1348.26 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5823.13 | 07-AUG-15:00 | 295.04 | 20-AUG-17:00 |
September | 2879.63 | 02-SEP-14:09 | 4358.02 | 01-SEP-09:09 | 1348.26 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5358.41 | 29-SEP-13:00 | 134.88 | 19-SEP-07:01 |
October | 2879.63 | 07-OCT-14:09 | 4358.02 | 01-OCT-10:09 | 1348.26 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5472.60 | 02-OCT-14:00 | 524.30 | 29-OCT-07:03 |
November | 2879.63 | 04-NOV-14:09 | 4358.02 | 01-NOV-09:09 | 1348.26 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2849.60 | 04-NOV-14:00 | 2227.78 | 30-NOV-18:00 |
December | 2879.63 | 02-DEC-15:09 | 4358.02 | 01-DEC-10:09 | 1348.26 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 321.30 | 28-DEC-14:00 | 4775.43 | 21-DEC-12:05 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2879.63 | 4358.02 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.12 | |||||
Maximum of Months | 2879.63 | 4358.02 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 8729.84 | 4775.43 |
Report: PeakSpaceGainsMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1439.81 | 07-JAN-15:09 | 2179.01 | 01-JAN-11:09 | 674.13 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 2204.09 | 15-JAN-17:00 |
February | 1439.81 | 04-FEB-15:09 | 2179.01 | 01-FEB-10:09 | 674.13 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 823.23 | 22-FEB-15:00 | 2067.03 | 10-FEB-12:10 |
March | 1439.81 | 04-MAR-15:09 | 2179.01 | 01-MAR-10:09 | 674.13 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2904.60 | 28-MAR-15:00 | 894.23 | 18-MAR-17:00 |
April | 1439.81 | 01-APR-14:09 | 2179.01 | 01-APR-09:09 | 674.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4078.75 | 15-APR-15:00 | 196.36 | 10-APR-07:05 |
May | 1439.81 | 06-MAY-14:09 | 2179.01 | 01-MAY-09:09 | 674.13 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4974.23 | 03-MAY-15:00 | 72.24 | 13-MAY-07:10 |
June | 1439.81 | 03-JUN-14:09 | 2179.01 | 01-JUN-09:09 | 674.13 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4982.75 | 07-JUN-16:00 | 69.78 | 18-JUN-07:02 |
July | 1439.81 | 01-JUL-14:09 | 2179.01 | 01-JUL-09:09 | 674.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4020.16 | 07-JUL-15:00 | 21.88 | 19-JUL-03:00 |
August | 1439.81 | 05-AUG-14:09 | 2179.01 | 01-AUG-09:09 | 674.13 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3323.92 | 07-AUG-15:00 | 146.89 | 20-AUG-17:00 |
September | 1439.81 | 02-SEP-14:09 | 2179.01 | 01-SEP-09:09 | 674.13 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3058.19 | 29-SEP-13:00 | 74.40 | 19-SEP-07:10 |
October | 1439.81 | 07-OCT-14:09 | 2179.01 | 01-OCT-10:09 | 674.13 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3125.52 | 02-OCT-14:00 | 296.32 | 30-OCT-07:05 |
November | 1439.81 | 04-NOV-14:09 | 2179.01 | 01-NOV-09:09 | 674.13 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1627.98 | 04-NOV-14:00 | 1272.86 | 30-NOV-18:00 |
December | 1439.81 | 02-DEC-15:09 | 2179.01 | 01-DEC-10:09 | 674.13 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 183.42 | 28-DEC-14:00 | 2717.99 | 21-DEC-12:05 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1439.81 | 2179.01 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.88 | |||||
Maximum of Months | 1439.81 | 2179.01 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 4982.75 | 2717.99 |
Report: PeakSpaceGainsMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1439.81 | 07-JAN-15:09 | 2179.01 | 01-JAN-11:09 | 674.13 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 2190.69 | 15-JAN-17:00 |
February | 1439.81 | 04-FEB-15:09 | 2179.01 | 01-FEB-10:09 | 674.13 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 823.23 | 22-FEB-15:00 | 2048.78 | 10-FEB-12:10 |
March | 1439.81 | 04-MAR-15:09 | 2179.01 | 01-MAR-10:09 | 674.13 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2904.60 | 28-MAR-15:00 | 894.23 | 18-MAR-17:00 |
April | 1439.81 | 01-APR-14:09 | 2179.01 | 01-APR-09:09 | 674.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4078.75 | 15-APR-15:00 | 194.82 | 10-APR-07:05 |
May | 1439.81 | 06-MAY-14:09 | 2179.01 | 01-MAY-09:09 | 674.13 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4974.23 | 03-MAY-15:00 | 70.97 | 13-MAY-07:10 |
June | 1439.81 | 03-JUN-14:09 | 2179.01 | 01-JUN-09:09 | 674.13 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4982.75 | 07-JUN-16:00 | 68.56 | 18-JUN-07:02 |
July | 1439.81 | 01-JUL-14:09 | 2179.01 | 01-JUL-09:09 | 674.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4020.16 | 07-JUL-15:00 | 21.67 | 19-JUL-03:00 |
August | 1439.81 | 05-AUG-14:09 | 2179.01 | 01-AUG-09:09 | 674.13 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3323.92 | 07-AUG-15:00 | 142.58 | 20-AUG-17:00 |
September | 1439.81 | 02-SEP-14:09 | 2179.01 | 01-SEP-09:09 | 674.13 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3058.19 | 29-SEP-13:00 | 73.75 | 19-SEP-07:10 |
October | 1439.81 | 07-OCT-14:09 | 2179.01 | 01-OCT-10:09 | 674.13 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3125.52 | 02-OCT-14:00 | 295.30 | 30-OCT-07:05 |
November | 1439.81 | 04-NOV-14:09 | 2179.01 | 01-NOV-09:09 | 674.13 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1627.98 | 04-NOV-14:00 | 1272.86 | 30-NOV-18:00 |
December | 1439.81 | 02-DEC-15:09 | 2179.01 | 01-DEC-10:09 | 674.13 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 183.42 | 28-DEC-14:00 | 2705.25 | 21-DEC-12:05 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1439.81 | 2179.01 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.67 | |||||
Maximum of Months | 1439.81 | 2179.01 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 4982.75 | 2705.25 |
Report: PeakSpaceGainsMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1439.81 | 07-JAN-15:09 | 2179.01 | 01-JAN-11:09 | 674.13 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 2178.07 | 01-JAN-18:00 |
February | 1439.81 | 04-FEB-15:09 | 2179.01 | 01-FEB-10:09 | 674.13 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 823.23 | 22-FEB-15:00 | 1997.15 | 10-FEB-12:10 |
March | 1439.81 | 04-MAR-15:09 | 2179.01 | 01-MAR-10:09 | 674.13 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2904.60 | 28-MAR-15:00 | 894.23 | 18-MAR-17:00 |
April | 1439.81 | 01-APR-14:09 | 2179.01 | 01-APR-09:09 | 674.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4078.75 | 15-APR-15:00 | 189.49 | 10-APR-07:05 |
May | 1439.81 | 06-MAY-14:09 | 2179.01 | 01-MAY-09:09 | 674.13 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4974.23 | 03-MAY-15:00 | 66.97 | 13-MAY-07:10 |
June | 1439.81 | 03-JUN-14:09 | 2179.01 | 01-JUN-09:09 | 674.13 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4982.75 | 07-JUN-16:00 | 66.31 | 18-JUN-07:02 |
July | 1439.81 | 01-JUL-14:09 | 2179.01 | 01-JUL-09:09 | 674.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4020.17 | 07-JUL-15:00 | 21.32 | 19-JUL-03:00 |
August | 1439.81 | 05-AUG-14:09 | 2179.01 | 01-AUG-09:09 | 674.13 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3323.92 | 07-AUG-15:00 | 142.03 | 20-AUG-17:00 |
September | 1439.81 | 02-SEP-14:09 | 2179.01 | 01-SEP-09:09 | 674.13 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3058.19 | 29-SEP-13:00 | 73.14 | 19-SEP-07:10 |
October | 1439.81 | 07-OCT-14:09 | 2179.01 | 01-OCT-10:09 | 674.13 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3125.52 | 02-OCT-14:00 | 293.10 | 30-OCT-07:05 |
November | 1439.81 | 04-NOV-14:09 | 2179.01 | 01-NOV-09:09 | 674.13 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1627.98 | 04-NOV-14:00 | 1272.86 | 30-NOV-18:00 |
December | 1439.81 | 02-DEC-15:09 | 2179.01 | 01-DEC-10:09 | 674.13 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 183.42 | 28-DEC-14:00 | 2673.39 | 21-DEC-12:05 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1439.81 | 2179.01 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.32 | |||||
Maximum of Months | 1439.81 | 2179.01 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 4982.75 | 2673.39 |
Report: PeakSpaceGainsMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1439.81 | 07-JAN-15:09 | 2179.01 | 01-JAN-11:09 | 674.13 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 2182.34 | 01-JAN-18:00 |
February | 1439.81 | 04-FEB-15:09 | 2179.01 | 01-FEB-10:09 | 674.13 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 829.25 | 22-FEB-15:00 | 1916.97 | 10-FEB-18:00 |
March | 1439.81 | 04-MAR-15:09 | 2179.01 | 01-MAR-10:09 | 674.13 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2904.59 | 28-MAR-15:00 | 905.56 | 18-MAR-17:00 |
April | 1439.81 | 01-APR-14:09 | 2179.01 | 01-APR-09:09 | 674.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4209.98 | 15-APR-15:00 | 215.21 | 22-APR-18:10 |
May | 1439.81 | 06-MAY-14:09 | 2179.01 | 01-MAY-09:09 | 674.13 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5041.95 | 03-MAY-15:00 | 63.48 | 13-MAY-07:10 |
June | 1439.81 | 03-JUN-14:09 | 2179.01 | 01-JUN-09:09 | 674.13 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5082.26 | 06-JUN-15:00 | 81.52 | 18-JUN-07:02 |
July | 1439.81 | 01-JUL-14:09 | 2179.01 | 01-JUL-09:09 | 674.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4063.29 | 07-JUL-15:00 | 54.30 | 19-JUL-03:00 |
August | 1439.81 | 05-AUG-14:09 | 2179.01 | 01-AUG-09:09 | 674.13 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3371.91 | 07-AUG-15:00 | 207.78 | 20-AUG-17:00 |
September | 1439.81 | 02-SEP-14:09 | 2179.01 | 01-SEP-09:09 | 674.13 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3107.22 | 29-SEP-13:00 | 102.62 | 03-SEP-17:00 |
October | 1439.81 | 07-OCT-14:09 | 2179.01 | 01-OCT-10:09 | 674.13 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3152.98 | 02-OCT-14:00 | 307.85 | 29-OCT-07:03 |
November | 1439.81 | 04-NOV-14:09 | 2179.01 | 01-NOV-09:09 | 674.13 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1636.74 | 04-NOV-14:00 | 1278.46 | 30-NOV-18:00 |
December | 1439.81 | 02-DEC-15:09 | 2179.01 | 01-DEC-10:09 | 674.13 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 185.91 | 28-DEC-14:00 | 2656.05 | 21-DEC-12:05 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1439.81 | 2179.01 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.30 | |||||
Maximum of Months | 1439.81 | 2179.01 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 5082.26 | 2656.05 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7752.07 | 12-JAN-15:00 | 1439.81 | 6078.71 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 138.35 |
February | 11172.40 | 22-FEB-15:00 | 1439.81 | 6078.71 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 1447.29 | 0.00 |
March | 37379.25 | 11-MAR-09:02 | 1079.86 | 19195.91 | 4494.18 | 0.00 | 0.00 | 0.00 | 0.00 | 54.75 | 0.00 |
April | 44270.08 | 08-APR-08:62 | 1079.86 | 19195.91 | 4494.18 | 0.00 | 0.00 | 0.00 | 0.00 | 78.64 | 0.00 |
May | 42777.98 | 06-MAY-08:61 | 1439.81 | 25594.55 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 374.20 | 0.00 |
June | 38629.81 | 07-JUN-08:61 | 1439.81 | 25594.55 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 792.98 | 0.00 |
July | 33407.41 | 07-JUL-07:01 | 0.00 | 2239.52 | 524.32 | 0.00 | 0.00 | 0.00 | 0.00 | 472.70 | 0.00 |
August | 30075.58 | 06-AUG-07:01 | 1439.81 | 2559.45 | 599.22 | 0.00 | 0.00 | 0.00 | 0.00 | 216.38 | 0.00 |
September | 34898.53 | 26-SEP-08:61 | 1439.81 | 25594.55 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 64.70 | 0.00 |
October | 39361.15 | 16-OCT-08:62 | 1079.86 | 19195.91 | 4494.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.14 |
November | 28982.61 | 09-NOV-09:02 | 719.91 | 12797.27 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111.40 |
December | 9512.70 | 03-DEC-14:00 | 2159.72 | 6078.71 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 275.30 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 7752.07 | 0.00 | 2239.52 | 524.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 44270.08 | 2159.72 | 25594.55 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 1447.29 | 138.35 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4261.20 | 12-JAN-15:00 | 719.90 | 3278.04 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.12 |
February | 6011.69 | 22-FEB-14:50 | 719.90 | 3278.04 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 818.97 | 0.00 |
March | 20115.01 | 11-MAR-09:02 | 539.93 | 10351.71 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 28.04 | 0.00 |
April | 23094.02 | 08-APR-08:62 | 539.93 | 10351.71 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 39.86 | 0.00 |
May | 22300.94 | 06-MAY-08:61 | 719.90 | 13802.27 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 208.24 | 0.00 |
June | 20341.51 | 07-JUN-08:61 | 719.90 | 13802.27 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 409.30 | 0.00 |
July | 17440.53 | 05-JUL-07:01 | 629.92 | 1207.70 | 262.16 | 0.00 | 0.00 | 0.00 | 0.00 | 263.18 | 0.00 |
August | 17213.55 | 06-AUG-07:01 | 719.90 | 1380.23 | 299.61 | 0.00 | 0.00 | 0.00 | 0.00 | 121.38 | 0.00 |
September | 18931.54 | 26-SEP-08:61 | 719.90 | 13802.27 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 37.89 | 0.00 |
October | 21387.97 | 15-OCT-07:02 | 449.94 | 862.64 | 187.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 102.75 |
November | 15589.65 | 09-NOV-09:02 | 359.95 | 6901.14 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.41 |
December | 5172.37 | 02-DEC-14:00 | 1079.86 | 3278.04 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 52.96 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 4261.20 | 359.95 | 862.64 | 187.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 23094.02 | 1079.86 | 13802.27 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 818.97 | 102.75 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3800.18 | 12-JAN-15:00 | 539.93 | 2921.79 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.12 |
February | 5698.41 | 22-FEB-14:00 | 719.90 | 2921.79 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 797.56 | 0.00 |
March | 18515.38 | 11-MAR-08:62 | 539.93 | 9226.71 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.94 |
April | 23609.80 | 30-APR-08:61 | 719.90 | 12302.27 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 21.08 | 0.00 |
May | 22620.37 | 06-MAY-07:01 | 719.90 | 12302.27 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 155.91 | 0.00 |
June | 20143.51 | 07-JUN-07:01 | 719.90 | 12302.27 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 349.60 | 0.00 |
July | 15598.58 | 05-JUL-06:02 | 0.00 | 768.89 | 187.26 | 0.00 | 0.00 | 0.00 | 0.00 | 12.51 | 0.00 |
August | 13980.93 | 03-AUG-07:01 | 629.92 | 10764.49 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 100.60 | 0.00 |
September | 16976.69 | 26-SEP-07:01 | 719.90 | 12302.27 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.57 |
October | 20406.74 | 16-OCT-07:02 | 449.94 | 7688.92 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.25 |
November | 7539.20 | 04-NOV-14:00 | 719.90 | 2921.79 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1627.96 | 0.00 |
December | 4862.24 | 02-DEC-14:00 | 1079.86 | 2921.79 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 52.96 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 3800.18 | 0.00 | 768.89 | 187.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 23609.80 | 1079.86 | 12302.27 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 1627.96 | 78.12 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3709.48 | 04-JAN-08:03 | 539.93 | 9226.71 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 609.82 |
February | 5630.54 | 22-FEB-14:00 | 719.90 | 2921.79 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 797.56 | 0.00 |
March | 18544.64 | 11-MAR-08:62 | 539.93 | 9226.71 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.80 |
April | 23694.95 | 30-APR-08:61 | 719.90 | 12302.27 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 17.59 | 0.00 |
May | 22672.01 | 06-MAY-07:01 | 719.90 | 12302.27 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 155.74 | 0.00 |
June | 20198.92 | 07-JUN-07:01 | 719.90 | 12302.27 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 349.47 | 0.00 |
July | 15877.94 | 05-JUL-06:02 | 0.00 | 768.89 | 187.26 | 0.00 | 0.00 | 0.00 | 0.00 | 12.03 | 0.00 |
August | 14062.09 | 03-AUG-07:01 | 629.92 | 10764.49 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 100.58 | 0.00 |
September | 17048.06 | 26-SEP-07:01 | 719.90 | 12302.27 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.38 |
October | 20508.86 | 16-OCT-07:02 | 449.94 | 7688.92 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.75 |
November | 7512.00 | 04-NOV-14:00 | 719.90 | 2921.79 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1627.96 | 0.00 |
December | 4784.77 | 02-DEC-14:00 | 1079.86 | 2921.79 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 52.96 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 3709.48 | 0.00 | 768.89 | 187.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 23694.95 | 1079.86 | 12302.27 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 1627.96 | 609.82 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3707.24 | 05-JAN-08:04 | 449.94 | 7688.92 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 620.54 |
February | 5487.70 | 22-FEB-14:00 | 719.90 | 2921.79 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 797.55 | 0.00 |
March | 18369.47 | 11-MAR-08:62 | 539.93 | 9226.71 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.68 |
April | 23591.60 | 30-APR-08:61 | 719.90 | 12302.27 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 20.32 | 0.00 |
May | 22595.21 | 06-MAY-07:01 | 719.90 | 12302.27 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 155.91 | 0.00 |
June | 20120.57 | 07-JUN-07:01 | 719.90 | 12302.27 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 349.53 | 0.00 |
July | 15787.94 | 05-JUL-06:02 | 0.00 | 768.89 | 187.26 | 0.00 | 0.00 | 0.00 | 0.00 | 12.09 | 0.00 |
August | 13930.77 | 03-AUG-07:01 | 629.92 | 10764.49 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 100.58 | 0.00 |
September | 16957.71 | 26-SEP-07:01 | 719.90 | 12302.27 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.55 |
October | 20395.64 | 16-OCT-07:02 | 449.94 | 7688.92 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.70 |
November | 7387.02 | 04-NOV-14:00 | 719.90 | 2921.79 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1627.95 | 0.00 |
December | 4647.38 | 02-DEC-14:00 | 1079.86 | 2921.79 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 52.96 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 3707.24 | 0.00 | 768.89 | 187.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 23591.60 | 1079.86 | 12302.27 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 1627.95 | 620.54 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6276.36 | 02-JAN-09:04 | 3167.59 | 18349.55 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 908.92 |
February | 9773.60 | 22-FEB-14:00 | 2555.67 | 4358.02 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 1396.03 | 0.00 |
March | 34668.60 | 11-MAR-09:02 | 2375.69 | 13762.16 | 4494.18 | 0.00 | 0.00 | 0.00 | 0.00 | 57.10 | 0.00 |
April | 42460.14 | 09-APR-09:01 | 3167.59 | 18349.55 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 118.42 | 0.00 |
May | 41023.43 | 29-MAY-08:61 | 0.00 | 1834.95 | 599.22 | 0.00 | 0.00 | 0.00 | 0.00 | 409.87 | 0.00 |
June | 37293.11 | 12-JUN-07:01 | 0.00 | 1834.95 | 599.22 | 0.00 | 0.00 | 0.00 | 0.00 | 560.86 | 0.00 |
July | 31924.63 | 07-JUL-07:01 | 0.00 | 1605.59 | 524.32 | 0.00 | 0.00 | 0.00 | 0.00 | 446.45 | 0.00 |
August | 29212.76 | 08-AUG-07:01 | 0.00 | 1605.59 | 524.32 | 0.00 | 0.00 | 0.00 | 0.00 | 254.85 | 0.00 |
September | 33253.13 | 26-SEP-08:61 | 3167.59 | 18349.55 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 61.00 | 0.00 |
October | 38402.01 | 15-OCT-09:01 | 2771.64 | 16055.85 | 5243.22 | 0.00 | 0.00 | 0.00 | 0.00 | 78.33 | 0.00 |
November | 29359.55 | 11-NOV-10:02 | 1583.79 | 9174.77 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.92 |
December | 8106.41 | 02-DEC-14:10 | 2771.64 | 4358.02 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 77.51 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 6276.36 | 0.00 | 1605.59 | 524.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 42460.14 | 3167.59 | 18349.55 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 1396.03 | 908.92 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3096.11 | 02-JAN-09:04 | 1583.79 | 9174.77 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 519.41 |
February | 5101.71 | 22-FEB-14:00 | 1277.83 | 2179.01 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 797.56 | 0.00 |
March | 18167.34 | 11-MAR-09:02 | 1187.84 | 6881.08 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 36.19 | 0.00 |
April | 22314.16 | 20-APR-08:61 | 1583.79 | 9174.77 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 68.90 | 0.00 |
May | 21503.90 | 29-MAY-08:61 | 0.00 | 917.48 | 299.61 | 0.00 | 0.00 | 0.00 | 0.00 | 232.67 | 0.00 |
June | 19558.02 | 12-JUN-07:01 | 0.00 | 917.48 | 299.61 | 0.00 | 0.00 | 0.00 | 0.00 | 321.06 | 0.00 |
July | 15477.57 | 05-JUL-07:01 | 0.00 | 802.79 | 262.16 | 0.00 | 0.00 | 0.00 | 0.00 | 230.31 | 0.00 |
August | 14273.27 | 03-AUG-08:61 | 1583.79 | 9174.77 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 126.10 | 0.00 |
September | 17494.84 | 26-SEP-08:61 | 1583.79 | 9174.77 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 35.86 | 0.00 |
October | 20155.29 | 15-OCT-09:01 | 1385.82 | 8027.93 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 46.97 | 0.00 |
November | 14290.38 | 11-NOV-10:02 | 791.89 | 4587.39 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.16 |
December | 4181.50 | 02-DEC-14:20 | 1385.82 | 2179.01 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 35.59 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 3096.11 | 0.00 | 802.79 | 262.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 22314.16 | 1583.79 | 9174.77 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 797.56 | 519.41 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3099.60 | 02-JAN-09:04 | 1583.79 | 9174.77 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 519.55 |
February | 5036.89 | 22-FEB-14:00 | 1277.83 | 2179.01 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 797.56 | 0.00 |
March | 18064.35 | 11-MAR-09:02 | 1187.84 | 6881.08 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 37.37 | 0.00 |
April | 22221.52 | 20-APR-08:61 | 1583.79 | 9174.77 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 69.13 | 0.00 |
May | 21418.26 | 29-MAY-08:61 | 0.00 | 917.48 | 299.61 | 0.00 | 0.00 | 0.00 | 0.00 | 233.52 | 0.00 |
June | 19470.59 | 12-JUN-07:01 | 0.00 | 917.48 | 299.61 | 0.00 | 0.00 | 0.00 | 0.00 | 321.50 | 0.00 |
July | 15406.99 | 05-JUL-07:01 | 0.00 | 802.79 | 262.16 | 0.00 | 0.00 | 0.00 | 0.00 | 230.56 | 0.00 |
August | 14205.57 | 03-AUG-08:61 | 1583.79 | 9174.77 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 126.06 | 0.00 |
September | 17419.42 | 26-SEP-08:61 | 1583.79 | 9174.77 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 35.76 | 0.00 |
October | 20063.17 | 15-OCT-09:01 | 1385.82 | 8027.93 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 47.70 | 0.00 |
November | 13922.61 | 11-NOV-10:02 | 791.89 | 4587.39 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.01 |
December | 4127.90 | 02-DEC-14:20 | 1385.82 | 2179.01 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 35.59 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 3099.60 | 0.00 | 802.79 | 262.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 22221.52 | 1583.79 | 9174.77 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 797.56 | 519.55 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3101.13 | 02-JAN-09:04 | 1583.79 | 9174.77 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 519.58 |
February | 4913.05 | 22-FEB-15:10 | 1241.83 | 2179.01 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 798.23 | 0.00 |
March | 17967.12 | 11-MAR-09:02 | 1187.84 | 6881.08 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 41.10 | 0.00 |
April | 22175.79 | 20-APR-08:61 | 1583.79 | 9174.77 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 71.64 | 0.00 |
May | 21381.48 | 29-MAY-08:61 | 0.00 | 917.48 | 299.61 | 0.00 | 0.00 | 0.00 | 0.00 | 235.00 | 0.00 |
June | 19495.21 | 12-JUN-07:01 | 0.00 | 917.48 | 299.61 | 0.00 | 0.00 | 0.00 | 0.00 | 321.03 | 0.00 |
July | 15458.80 | 05-JUL-07:01 | 0.00 | 802.79 | 262.16 | 0.00 | 0.00 | 0.00 | 0.00 | 229.10 | 0.00 |
August | 14220.13 | 03-AUG-08:61 | 1583.79 | 9174.77 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 126.03 | 0.00 |
September | 17431.49 | 26-SEP-08:61 | 1583.79 | 9174.77 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 35.84 | 0.00 |
October | 20028.63 | 15-OCT-09:01 | 1385.82 | 8027.93 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 49.47 | 0.00 |
November | 13103.08 | 11-NOV-10:02 | 791.89 | 4587.39 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.70 |
December | 4021.77 | 02-DEC-14:20 | 1385.82 | 2179.01 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 35.58 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 3101.13 | 0.00 | 802.79 | 262.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 22175.79 | 1583.79 | 9174.77 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 798.23 | 519.58 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3044.44 | 02-JAN-09:04 | 1583.79 | 9174.77 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 517.39 |
February | 5116.43 | 22-FEB-14:00 | 1277.83 | 2179.01 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 801.85 | 0.00 |
March | 18957.09 | 11-MAR-09:02 | 1187.84 | 6881.08 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 49.15 | 0.00 |
April | 23536.03 | 09-APR-09:01 | 1583.79 | 9174.77 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 84.19 | 0.00 |
May | 23111.69 | 29-MAY-08:61 | 0.00 | 917.48 | 299.61 | 0.00 | 0.00 | 0.00 | 0.00 | 285.20 | 0.00 |
June | 21364.03 | 12-JUN-07:01 | 0.00 | 917.48 | 299.61 | 0.00 | 0.00 | 0.00 | 0.00 | 344.30 | 0.00 |
July | 17955.77 | 07-JUL-07:01 | 0.00 | 802.79 | 262.16 | 0.00 | 0.00 | 0.00 | 0.00 | 270.26 | 0.00 |
August | 15963.57 | 09-AUG-07:01 | 0.00 | 802.79 | 262.16 | 0.00 | 0.00 | 0.00 | 0.00 | 139.34 | 0.00 |
September | 18594.34 | 26-SEP-08:61 | 1583.79 | 9174.77 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 39.29 | 0.00 |
October | 21483.69 | 15-OCT-09:01 | 1385.82 | 8027.93 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 51.96 | 0.00 |
November | 13569.56 | 11-NOV-10:02 | 791.89 | 4587.39 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.98 |
December | 4176.50 | 01-DEC-14:00 | 1277.83 | 2179.01 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.76 |
Annual Sum or Average | |||||||||||
Minimum of Months | 3044.44 | 0.00 | 802.79 | 262.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 23536.03 | 1583.79 | 9174.77 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 801.85 | 517.39 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | |
January | 0.798985E+11 | 65525.94 | 13-JAN-18:19 | 0.193787E+10 | 102906.53 | 02-JAN-09:09 |
February | 0.792158E+11 | 76355.22 | 22-FEB-13:00 | 56884677.44 | 23133.60 | 02-FEB-09:09 |
March | 0.101967E+12 | 91864.86 | 28-MAR-14:00 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 0.116028E+12 | 113756.49 | 16-APR-14:20 | 0.00 | 0.00 | 01-APR-00:10 |
May | 0.141959E+12 | 131285.07 | 03-MAY-14:39 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 0.146679E+12 | 143981.46 | 22-JUN-15:09 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 0.150864E+12 | 142509.37 | 01-JUL-12:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.150285E+12 | 141593.76 | 27-AUG-13:00 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 0.132767E+12 | 125874.91 | 14-SEP-15:09 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 0.115542E+12 | 109531.91 | 03-OCT-14:50 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 0.958139E+11 | 82888.19 | 09-NOV-13:30 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 0.832717E+11 | 68291.03 | 16-DEC-13:20 | 0.113002E+09 | 32545.36 | 23-DEC-09:09 |
Annual Sum or Average | 0.139429E+13 | 0.210776E+10 | ||||
Minimum of Months | 0.792158E+11 | 65525.94 | 0.00 | 0.00 | ||
Maximum of Months | 0.150864E+12 | 143981.46 | 0.193787E+10 | 102906.53 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.424448E+11 | 0.894945E+10 | 0.108804E+11 | 0.00 | 0.976611E+10 | 0.00 | 0.00 | 0.261540E+10 | 0.00 | 0.00 | 0.00 | 0.524233E+10 | 0.00 |
February | 0.384292E+11 | 0.768618E+10 | 0.985143E+10 | 0.00 | 0.882836E+10 | 0.00 | 0.00 | 0.971513E+10 | 0.00 | 0.00 | 0.00 | 0.470546E+10 | 0.00 |
March | 0.430726E+11 | 0.786608E+10 | 0.110523E+11 | 0.00 | 0.994136E+10 | 0.00 | 0.00 | 0.248862E+11 | 0.00 | 0.00 | 0.00 | 0.514886E+10 | 0.00 |
April | 0.411878E+11 | 0.698248E+10 | 0.105581E+11 | 0.00 | 0.100668E+11 | 0.00 | 0.00 | 0.423943E+11 | 0.00 | 0.00 | 0.00 | 0.483862E+10 | 0.00 |
May | 0.427427E+11 | 0.666189E+10 | 0.109629E+11 | 0.00 | 0.124658E+11 | 0.00 | 0.00 | 0.642426E+11 | 0.00 | 0.00 | 0.00 | 0.488310E+10 | 0.00 |
June | 0.416347E+11 | 0.614913E+10 | 0.106818E+11 | 0.00 | 0.133353E+11 | 0.00 | 0.00 | 0.702263E+11 | 0.00 | 0.00 | 0.00 | 0.465206E+10 | 0.00 |
July | 0.423277E+11 | 0.651605E+10 | 0.108460E+11 | 0.00 | 0.141200E+11 | 0.00 | 0.00 | 0.723127E+11 | 0.00 | 0.00 | 0.00 | 0.474162E+10 | 0.00 |
August | 0.430407E+11 | 0.696189E+10 | 0.110454E+11 | 0.00 | 0.140577E+11 | 0.00 | 0.00 | 0.703816E+11 | 0.00 | 0.00 | 0.00 | 0.479747E+10 | 0.00 |
September | 0.412197E+11 | 0.734083E+10 | 0.105649E+11 | 0.00 | 0.117499E+11 | 0.00 | 0.00 | 0.571831E+11 | 0.00 | 0.00 | 0.00 | 0.470827E+10 | 0.00 |
October | 0.424448E+11 | 0.824109E+10 | 0.108804E+11 | 0.00 | 0.100540E+11 | 0.00 | 0.00 | 0.389502E+11 | 0.00 | 0.00 | 0.00 | 0.497126E+10 | 0.00 |
November | 0.411240E+11 | 0.852003E+10 | 0.105443E+11 | 0.00 | 0.947425E+10 | 0.00 | 0.00 | 0.212169E+11 | 0.00 | 0.00 | 0.00 | 0.493445E+10 | 0.00 |
December | 0.423596E+11 | 0.914529E+10 | 0.108529E+11 | 0.00 | 0.971088E+10 | 0.00 | 0.00 | 0.600780E+10 | 0.00 | 0.00 | 0.00 | 0.519516E+10 | 0.00 |
Annual Sum or Average | 0.502028E+12 | 0.910204E+11 | 0.128721E+12 | 0.133570E+12 | 0.00 | 0.480132E+12 | 0.588187E+11 | ||||||
Minimum of Months | 0.384292E+11 | 0.614913E+10 | 0.985143E+10 | 0.00 | 0.882836E+10 | 0.00 | 0.00 | 0.261540E+10 | 0.00 | 0.00 | 0.00 | 0.465206E+10 | 0.00 |
Maximum of Months | 0.430726E+11 | 0.914529E+10 | 0.110523E+11 | 0.00 | 0.141200E+11 | 0.00 | 0.00 | 0.723127E+11 | 0.00 | 0.00 | 0.00 | 0.524233E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS [J] | COOLING:GAS [] | WATERSYSTEMS:GAS [] | COGENERATION:GAS [] | HUMIDIFIER:GAS [] | |
January | 0.00 | 0.00 | 0.193787E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 56884677.44 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.113002E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.210776E+10 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.193787E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum}[W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum}[W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum}[W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum}[W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 31196.17 | 01-JAN-11:09 | 6944.63 | 01-JAN-06:10 | 8089.53 | 01-JAN-11:09 | 0.00 | 8848.27 | 02-JAN-09:09 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 31196.17 | 01-FEB-10:09 | 6944.63 | 01-FEB-06:10 | 8089.53 | 01-FEB-10:09 | 0.00 | 7183.16 | 02-FEB-09:09 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 31196.17 | 01-MAR-10:09 | 6944.63 | 01-MAR-06:10 | 8089.53 | 01-MAR-10:09 | 0.00 | 8246.77 | 11-MAR-09:09 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 31196.17 | 01-APR-09:09 | 6944.63 | 01-APR-05:10 | 8089.53 | 01-APR-09:09 | 0.00 | 10384.78 | 16-APR-14:00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 31196.17 | 01-MAY-09:09 | 6944.63 | 01-MAY-05:10 | 8089.53 | 01-MAY-09:09 | 0.00 | 13100.01 | 17-MAY-16:10 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 31196.17 | 01-JUN-09:09 | 6944.63 | 01-JUN-05:10 | 8089.53 | 01-JUN-09:09 | 0.00 | 15777.89 | 22-JUN-16:10 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 31196.17 | 01-JUL-09:09 | 6944.63 | 01-JUL-05:10 | 8089.53 | 01-JUL-09:09 | 0.00 | 16042.25 | 01-JUL-14:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 31196.17 | 01-AUG-09:09 | 6944.63 | 01-AUG-05:10 | 8089.53 | 01-AUG-09:09 | 0.00 | 15564.91 | 27-AUG-14:09 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 31196.17 | 01-SEP-09:09 | 6944.63 | 01-SEP-05:10 | 8089.53 | 01-SEP-09:09 | 0.00 | 13189.82 | 14-SEP-16:10 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 31196.17 | 01-OCT-10:09 | 6944.63 | 01-OCT-05:10 | 8089.53 | 01-OCT-10:09 | 0.00 | 9710.48 | 04-OCT-12:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 31196.17 | 01-NOV-09:09 | 6944.63 | 01-NOV-05:10 | 8089.53 | 01-NOV-09:09 | 0.00 | 7446.72 | 09-NOV-09:09 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 31196.17 | 01-DEC-10:09 | 6944.63 | 01-DEC-06:10 | 8089.53 | 01-DEC-10:09 | 0.00 | 7378.88 | 23-DEC-09:09 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 31196.17 | 6944.63 | 8089.53 | 0.00 | 7183.16 | 0.00 | 0.00 | |||||
Maximum of Months | 31196.17 | 6944.63 | 8089.53 | 0.00 | 16042.25 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum}[W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum}[W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 12886.87 | 12-JAN-15:09 | 0.00 | 0.00 | 0.00 | 9864.08 | 02-JAN-14:09 | 0.00 |
February | 22796.61 | 22-FEB-13:00 | 0.00 | 0.00 | 0.00 | 8113.07 | 11-FEB-13:00 | 0.00 |
March | 40433.28 | 28-MAR-14:00 | 0.00 | 0.00 | 0.00 | 7546.33 | 14-MAR-16:49 | 0.00 |
April | 59713.71 | 16-APR-14:00 | 0.00 | 0.00 | 0.00 | 7555.58 | 18-APR-13:09 | 0.00 |
May | 74962.89 | 03-MAY-14:00 | 0.00 | 0.00 | 0.00 | 7530.41 | 18-MAY-16:49 | 0.00 |
June | 84630.47 | 22-JUN-16:10 | 0.00 | 0.00 | 0.00 | 9615.92 | 12-JUN-10:30 | 0.00 |
July | 83657.32 | 01-JUL-14:00 | 0.00 | 0.00 | 0.00 | 7527.08 | 17-JUL-11:50 | 0.00 |
August | 79515.91 | 27-AUG-14:09 | 0.00 | 0.00 | 0.00 | 9627.69 | 19-AUG-16:19 | 0.00 |
September | 67986.80 | 14-SEP-16:10 | 0.00 | 0.00 | 0.00 | 7546.45 | 20-SEP-13:20 | 0.00 |
October | 53865.31 | 04-OCT-12:00 | 0.00 | 0.00 | 0.00 | 7561.60 | 27-OCT-12:30 | 0.00 |
November | 31453.86 | 09-NOV-13:30 | 0.00 | 0.00 | 0.00 | 7567.69 | 20-NOV-13:09 | 0.00 |
December | 16834.96 | 28-DEC-13:00 | 0.00 | 0.00 | 0.00 | 11784.25 | 21-DEC-15:20 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 12886.87 | 0.00 | 0.00 | 0.00 | 7527.08 | 0.00 | ||
Maximum of Months | 84630.47 | 0.00 | 0.00 | 0.00 | 11784.25 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 65525.94 | 13-JAN-18:19 | 31196.17 | 8089.53 | 6944.63 | 0.00 | 6699.62 | 0.00 | 0.00 | 7155.24 | 0.00 |
February | 76355.22 | 22-FEB-13:00 | 31196.17 | 8089.53 | 0.00 | 0.00 | 6699.62 | 0.00 | 0.00 | 22796.61 | 0.00 |
March | 91864.86 | 28-MAR-14:00 | 31196.17 | 8089.53 | 0.00 | 0.00 | 6706.20 | 0.00 | 0.00 | 40433.28 | 0.00 |
April | 113756.49 | 16-APR-14:20 | 31196.17 | 8089.53 | 0.00 | 0.00 | 10222.21 | 0.00 | 0.00 | 58828.49 | 0.00 |
May | 131285.07 | 03-MAY-14:39 | 31196.17 | 8089.53 | 0.00 | 0.00 | 12868.39 | 0.00 | 0.00 | 73698.04 | 0.00 |
June | 143981.46 | 22-JUN-15:09 | 31196.17 | 8089.53 | 0.00 | 0.00 | 15573.55 | 0.00 | 0.00 | 83701.66 | 0.00 |
July | 142509.37 | 01-JUL-12:00 | 31196.17 | 8089.53 | 0.00 | 0.00 | 15670.69 | 0.00 | 0.00 | 82478.16 | 0.00 |
August | 141593.76 | 27-AUG-13:00 | 31196.17 | 8089.53 | 0.00 | 0.00 | 15507.62 | 0.00 | 0.00 | 79286.67 | 0.00 |
September | 125874.91 | 14-SEP-15:09 | 31196.17 | 8089.53 | 0.00 | 0.00 | 12978.09 | 0.00 | 0.00 | 67147.58 | 0.00 |
October | 109531.91 | 03-OCT-14:50 | 31196.17 | 8089.53 | 0.00 | 0.00 | 9492.72 | 0.00 | 0.00 | 53214.29 | 0.00 |
November | 82888.19 | 09-NOV-13:30 | 31196.17 | 8089.53 | 0.00 | 0.00 | 6699.62 | 0.00 | 0.00 | 31453.86 | 0.00 |
December | 68291.03 | 16-DEC-13:20 | 31196.17 | 8089.53 | 0.00 | 0.00 | 6699.62 | 0.00 | 0.00 | 13122.21 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 65525.94 | 31196.17 | 8089.53 | 0.00 | 0.00 | 6699.62 | 0.00 | 0.00 | 7155.24 | 0.00 | |
Maximum of Months | 143981.46 | 31196.17 | 8089.53 | 6944.63 | 0.00 | 15670.69 | 0.00 | 0.00 | 83701.66 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS {Maximum}[W] | HEATING:GAS {TIMESTAMP} | COOLING:GAS [] | WATERSYSTEMS:GAS [] | COGENERATION:GAS [] | |
January | 0.00 | 0.00 | 102906.53 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 23133.60 | 02-FEB-09:09 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 32545.36 | 23-DEC-09:09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 102906.53 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.47 | 0.67 | 24.47 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 24.52 | 2.67 | 24.52 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 24.60 | 4.67 | 24.60 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 24.56 | 4.67 | 24.56 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 24.52 | 2.50 | 24.52 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 15.17 | 24.55 | 15.17 | 24.55 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 24.60 | 4.67 | 24.60 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 24.49 | 1.33 | 24.49 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 24.51 | 4.50 | 24.51 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 24.52 | 2.83 | 24.52 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 24.48 | 1.67 | 24.48 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 10.33 | 24.50 | 10.33 | 24.50 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 24.52 | 4.50 | 24.52 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.48 | 0.50 | 24.48 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 24.54 | 2.83 | 24.54 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 24.65 | 5.00 | 24.65 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 24.63 | 5.17 | 24.63 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 24.57 | 3.83 | 24.57 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 17.33 | 24.60 | 17.33 | 24.60 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 24.65 | 5.17 | 24.65 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.47 | 0.67 | 24.47 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 24.54 | 2.83 | 24.54 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 24.64 | 5.17 | 24.64 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 24.63 | 5.17 | 24.63 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 24.58 | 3.67 | 24.58 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 17.50 | 24.60 | 17.50 | 24.60 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 24.64 | 5.17 | 24.64 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 24.48 | 0.83 | 24.48 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 24.54 | 2.83 | 24.54 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 24.65 | 5.00 | 24.65 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 24.63 | 5.17 | 24.63 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 24.57 | 3.83 | 24.57 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 17.67 | 24.60 | 17.67 | 24.60 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 24.65 | 5.17 | 24.65 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 24.50 | 0.83 | 24.50 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 24.55 | 3.67 | 24.55 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 24.69 | 5.17 | 24.69 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 24.66 | 5.00 | 24.66 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 24.61 | 2.83 | 24.61 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 17.50 | 24.63 | 17.50 | 24.63 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 24.69 | 5.17 | 24.69 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.50 | 0.50 | 24.50 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 24.55 | 2.67 | 24.55 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 24.66 | 5.00 | 24.66 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 24.63 | 4.67 | 24.63 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 24.60 | 3.33 | 24.60 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 16.17 | 24.61 | 16.17 | 24.61 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 24.66 | 5.00 | 24.66 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.49 | 0.67 | 24.49 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 24.54 | 2.83 | 24.54 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 24.66 | 5.00 | 24.66 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 24.64 | 4.67 | 24.64 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 24.60 | 3.17 | 24.60 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 16.33 | 24.62 | 16.33 | 24.62 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 24.66 | 5.00 | 24.66 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.48 | 0.67 | 24.48 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 24.55 | 2.83 | 24.55 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 24.66 | 5.00 | 24.66 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 24.64 | 4.67 | 24.64 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 24.60 | 3.17 | 24.60 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 16.33 | 24.62 | 16.33 | 24.62 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 24.66 | 5.00 | 24.66 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.48 | 0.33 | 24.48 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 24.53 | 2.67 | 24.53 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 24.66 | 5.00 | 24.66 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 24.63 | 5.00 | 24.63 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 24.57 | 3.17 | 24.57 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 16.17 | 24.61 | 16.17 | 24.61 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 24.66 | 5.00 | 24.66 |
Report: ComfortReportSimple55Monthly
For: LGSTORE1
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 222.00 | 22.53 | 45.17 | 23.65 | 2.50 | 19.78 |
February | 86.00 | 22.81 | 144.17 | 23.89 | 0.00 | 0.00 |
March | 18.17 | 23.35 | 338.33 | 23.90 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 431.00 | 23.95 | 0.00 | 0.00 |
May | 27.33 | 24.54 | 496.00 | 23.99 | 27.33 | 24.54 |
June | 130.83 | 24.15 | 480.00 | 23.99 | 130.83 | 24.15 |
July | 329.67 | 24.04 | 496.00 | 23.99 | 329.67 | 24.04 |
August | 376.33 | 24.04 | 496.00 | 24.00 | 376.33 | 24.04 |
September | 229.67 | 24.05 | 480.00 | 23.98 | 229.67 | 24.05 |
October | 5.67 | 24.44 | 493.67 | 23.94 | 5.67 | 24.44 |
November | 12.00 | 23.28 | 373.17 | 23.89 | 0.00 | 0.00 |
December | 134.33 | 22.82 | 111.50 | 23.89 | 0.00 | 0.00 |
Annual Sum or Average | 1572.00 | 23.66 | 4385.00 | 23.96 | 1102.00 | 24.06 |
Minimum of Months | 0.00 | 0.00 | 45.17 | 23.65 | 0.00 | 0.00 |
Maximum of Months | 376.33 | 24.54 | 496.00 | 24.00 | 376.33 | 24.54 |
Report: ComfortReportSimple55Monthly
For: SMSTORE1
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 153.00 | 22.78 | 40.17 | 23.86 | 0.00 | 0.00 |
February | 55.50 | 22.95 | 130.33 | 23.89 | 0.00 | 0.00 |
March | 12.17 | 23.52 | 320.83 | 23.91 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 421.00 | 23.96 | 0.00 | 0.00 |
May | 19.00 | 24.38 | 496.00 | 23.99 | 19.00 | 24.38 |
June | 106.83 | 24.10 | 480.00 | 23.99 | 106.83 | 24.10 |
July | 284.83 | 24.04 | 496.00 | 23.99 | 284.83 | 24.04 |
August | 321.00 | 24.03 | 496.00 | 24.00 | 321.00 | 24.03 |
September | 190.17 | 23.99 | 480.00 | 23.98 | 190.17 | 23.99 |
October | 2.50 | 24.12 | 485.00 | 23.94 | 2.50 | 24.12 |
November | 9.33 | 23.40 | 331.67 | 23.90 | 0.00 | 0.00 |
December | 103.83 | 23.09 | 83.67 | 23.89 | 0.00 | 0.00 |
Annual Sum or Average | 1258.17 | 23.75 | 4260.67 | 23.96 | 924.33 | 24.04 |
Minimum of Months | 0.00 | 0.00 | 40.17 | 23.86 | 0.00 | 0.00 |
Maximum of Months | 321.00 | 24.38 | 496.00 | 24.00 | 321.00 | 24.38 |
Report: ComfortReportSimple55Monthly
For: SMSTORE2
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 176.33 | 22.60 | 17.17 | 23.87 | 0.50 | 21.02 |
February | 62.17 | 22.82 | 98.67 | 24.03 | 0.00 | 0.00 |
March | 10.83 | 23.63 | 267.50 | 24.08 | 0.33 | 28.11 |
April | 5.17 | 28.53 | 324.33 | 24.16 | 5.17 | 28.53 |
May | 36.00 | 25.86 | 375.00 | 24.19 | 36.00 | 25.86 |
June | 125.83 | 24.61 | 366.00 | 24.20 | 125.83 | 24.61 |
July | 279.00 | 24.26 | 369.00 | 24.18 | 279.00 | 24.26 |
August | 318.00 | 24.19 | 379.00 | 24.15 | 318.00 | 24.19 |
September | 203.50 | 24.26 | 360.00 | 24.14 | 203.50 | 24.26 |
October | 8.83 | 25.60 | 368.83 | 24.09 | 8.83 | 25.60 |
November | 9.83 | 23.26 | 259.50 | 24.02 | 0.00 | 0.00 |
December | 100.67 | 22.85 | 48.33 | 23.94 | 0.00 | 0.00 |
Annual Sum or Average | 1336.17 | 23.94 | 3233.33 | 24.13 | 977.17 | 24.38 |
Minimum of Months | 5.17 | 22.60 | 17.17 | 23.87 | 0.00 | 0.00 |
Maximum of Months | 318.00 | 28.53 | 379.00 | 24.20 | 318.00 | 28.53 |
Report: ComfortReportSimple55Monthly
For: SMSTORE3
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 203.17 | 22.63 | 12.50 | 23.82 | 0.67 | 21.07 |
February | 66.33 | 22.78 | 91.67 | 24.02 | 0.00 | 0.00 |
March | 11.33 | 23.60 | 264.17 | 24.08 | 0.33 | 28.12 |
April | 5.17 | 28.54 | 325.33 | 24.16 | 5.17 | 28.54 |
May | 35.33 | 25.95 | 375.00 | 24.19 | 35.33 | 25.95 |
June | 125.00 | 24.62 | 366.00 | 24.20 | 125.00 | 24.62 |
July | 272.33 | 24.27 | 369.00 | 24.19 | 272.33 | 24.27 |
August | 314.00 | 24.20 | 379.00 | 24.15 | 314.00 | 24.20 |
September | 202.00 | 24.26 | 360.00 | 24.14 | 202.00 | 24.26 |
October | 9.00 | 25.71 | 369.17 | 24.09 | 9.00 | 25.71 |
November | 10.83 | 23.24 | 255.17 | 24.02 | 0.00 | 0.00 |
December | 106.17 | 22.80 | 41.67 | 23.94 | 0.00 | 0.00 |
Annual Sum or Average | 1360.67 | 23.91 | 3208.67 | 24.13 | 963.83 | 24.39 |
Minimum of Months | 5.17 | 22.63 | 12.50 | 23.82 | 0.00 | 0.00 |
Maximum of Months | 314.00 | 28.54 | 379.00 | 24.20 | 314.00 | 28.54 |
Report: ComfortReportSimple55Monthly
For: SMSTORE4
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 233.00 | 22.64 | 10.67 | 23.75 | 0.83 | 21.08 |
February | 71.67 | 22.73 | 79.67 | 24.03 | 0.00 | 0.00 |
March | 14.00 | 23.55 | 255.50 | 24.08 | 0.33 | 28.08 |
April | 4.67 | 28.58 | 322.50 | 24.16 | 4.67 | 28.58 |
May | 36.00 | 25.84 | 375.00 | 24.19 | 36.00 | 25.84 |
June | 127.00 | 24.60 | 366.00 | 24.20 | 127.00 | 24.60 |
July | 276.67 | 24.26 | 369.00 | 24.18 | 276.67 | 24.26 |
August | 317.67 | 24.19 | 379.00 | 24.15 | 317.67 | 24.19 |
September | 204.33 | 24.26 | 360.00 | 24.13 | 204.33 | 24.26 |
October | 9.50 | 25.50 | 368.50 | 24.09 | 9.50 | 25.50 |
November | 12.83 | 23.23 | 247.17 | 24.01 | 0.00 | 0.00 |
December | 115.67 | 22.77 | 34.67 | 23.94 | 0.00 | 0.00 |
Annual Sum or Average | 1423.00 | 23.86 | 3167.67 | 24.13 | 977.00 | 24.37 |
Minimum of Months | 4.67 | 22.64 | 10.67 | 23.75 | 0.00 | 0.00 |
Maximum of Months | 317.67 | 28.58 | 379.00 | 24.20 | 317.67 | 28.58 |
Report: ComfortReportSimple55Monthly
For: LGSTORE2
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 273.00 | 22.78 | 7.50 | 23.62 | 0.83 | 21.03 |
February | 69.83 | 22.88 | 54.50 | 23.96 | 0.00 | 0.00 |
March | 11.33 | 23.56 | 211.83 | 23.96 | 0.33 | 27.99 |
April | 3.17 | 28.81 | 288.17 | 24.01 | 3.17 | 28.81 |
May | 25.83 | 25.05 | 344.00 | 24.01 | 25.83 | 25.05 |
June | 116.33 | 24.16 | 336.00 | 24.00 | 116.33 | 24.16 |
July | 268.00 | 24.07 | 338.00 | 24.03 | 268.00 | 24.07 |
August | 306.33 | 23.99 | 348.00 | 23.98 | 306.33 | 23.99 |
September | 189.33 | 24.06 | 330.00 | 23.99 | 189.33 | 24.06 |
October | 7.17 | 25.38 | 337.00 | 23.98 | 7.17 | 25.38 |
November | 7.00 | 23.31 | 216.67 | 23.94 | 0.00 | 0.00 |
December | 120.83 | 22.88 | 22.00 | 23.90 | 0.00 | 0.00 |
Annual Sum or Average | 1398.17 | 23.67 | 2833.67 | 23.99 | 917.33 | 24.11 |
Minimum of Months | 3.17 | 22.78 | 7.50 | 23.62 | 0.00 | 0.00 |
Maximum of Months | 306.33 | 28.81 | 348.00 | 24.03 | 306.33 | 28.81 |
Report: ComfortReportSimple55Monthly
For: SMSTORE5
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 285.17 | 22.79 | 1.83 | 22.54 | 1.00 | 21.05 |
February | 78.17 | 22.96 | 43.50 | 23.97 | 0.00 | 0.00 |
March | 13.17 | 23.61 | 193.00 | 23.97 | 0.33 | 27.93 |
April | 2.83 | 28.76 | 269.83 | 24.01 | 2.83 | 28.76 |
May | 26.00 | 25.00 | 344.00 | 24.01 | 26.00 | 25.00 |
June | 117.50 | 24.14 | 336.00 | 24.00 | 117.50 | 24.14 |
July | 269.83 | 24.06 | 338.00 | 24.03 | 269.83 | 24.06 |
August | 310.67 | 23.99 | 348.00 | 23.98 | 310.67 | 23.99 |
September | 190.50 | 24.06 | 330.00 | 23.99 | 190.50 | 24.06 |
October | 6.83 | 25.15 | 334.17 | 23.98 | 6.83 | 25.15 |
November | 8.00 | 23.39 | 191.83 | 23.95 | 0.00 | 0.00 |
December | 129.33 | 22.94 | 12.50 | 23.91 | 0.00 | 0.00 |
Annual Sum or Average | 1438.00 | 23.66 | 2742.67 | 23.99 | 925.50 | 24.09 |
Minimum of Months | 2.83 | 22.79 | 1.83 | 22.54 | 0.00 | 0.00 |
Maximum of Months | 310.67 | 28.76 | 348.00 | 24.03 | 310.67 | 28.76 |
Report: ComfortReportSimple55Monthly
For: SMSTORE6
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 288.33 | 22.76 | 1.67 | 22.09 | 1.17 | 21.09 |
February | 84.00 | 22.97 | 38.83 | 23.97 | 0.00 | 0.00 |
March | 14.17 | 23.54 | 188.83 | 23.97 | 0.17 | 28.13 |
April | 2.50 | 28.86 | 267.50 | 24.01 | 2.50 | 28.86 |
May | 26.00 | 24.99 | 344.00 | 24.01 | 26.00 | 24.99 |
June | 117.83 | 24.14 | 336.00 | 23.99 | 117.83 | 24.14 |
July | 270.33 | 24.06 | 338.00 | 24.03 | 270.33 | 24.06 |
August | 311.00 | 23.99 | 348.00 | 23.98 | 311.00 | 23.99 |
September | 191.67 | 24.06 | 330.00 | 23.99 | 191.67 | 24.06 |
October | 7.17 | 25.08 | 333.50 | 23.98 | 7.17 | 25.08 |
November | 8.67 | 23.39 | 186.00 | 23.95 | 0.00 | 0.00 |
December | 134.83 | 22.94 | 10.50 | 23.90 | 0.00 | 0.00 |
Annual Sum or Average | 1456.50 | 23.65 | 2722.83 | 23.99 | 927.83 | 24.09 |
Minimum of Months | 2.50 | 22.76 | 1.67 | 22.09 | 0.00 | 0.00 |
Maximum of Months | 311.00 | 28.86 | 348.00 | 24.03 | 311.00 | 28.86 |
Report: ComfortReportSimple55Monthly
For: SMSTORE7
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 295.00 | 22.70 | 1.50 | 21.11 | 1.50 | 21.11 |
February | 97.83 | 22.97 | 36.17 | 23.95 | 0.00 | 0.00 |
March | 16.50 | 23.47 | 184.17 | 23.97 | 0.17 | 28.09 |
April | 2.50 | 28.85 | 266.50 | 24.01 | 2.50 | 28.85 |
May | 26.83 | 24.96 | 344.00 | 24.01 | 26.83 | 24.96 |
June | 118.00 | 24.14 | 336.00 | 23.99 | 118.00 | 24.14 |
July | 269.50 | 24.06 | 338.00 | 24.03 | 269.50 | 24.06 |
August | 310.33 | 23.99 | 348.00 | 23.98 | 310.33 | 23.99 |
September | 191.00 | 24.06 | 330.00 | 23.99 | 191.00 | 24.06 |
October | 7.33 | 25.05 | 333.50 | 23.98 | 7.33 | 25.05 |
November | 10.17 | 23.38 | 184.67 | 23.95 | 0.00 | 0.00 |
December | 141.50 | 22.89 | 6.67 | 23.90 | 0.00 | 0.00 |
Annual Sum or Average | 1486.50 | 23.62 | 2709.17 | 23.99 | 927.17 | 24.09 |
Minimum of Months | 2.50 | 22.70 | 1.50 | 21.11 | 0.00 | 0.00 |
Maximum of Months | 310.33 | 28.85 | 348.00 | 24.03 | 310.33 | 28.85 |
Report: ComfortReportSimple55Monthly
For: SMSTORE8
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 298.83 | 22.65 | 3.00 | 21.20 | 3.00 | 21.20 |
February | 114.83 | 22.91 | 35.00 | 23.94 | 0.17 | 21.33 |
March | 26.50 | 23.40 | 180.00 | 23.97 | 0.33 | 27.95 |
April | 3.33 | 28.57 | 275.83 | 24.01 | 3.17 | 28.81 |
May | 29.33 | 24.98 | 344.00 | 24.01 | 29.33 | 24.98 |
June | 111.33 | 24.18 | 336.00 | 24.00 | 111.33 | 24.18 |
July | 251.67 | 24.08 | 338.00 | 24.03 | 251.67 | 24.08 |
August | 281.00 | 24.01 | 348.00 | 23.98 | 281.00 | 24.01 |
September | 176.67 | 24.08 | 330.00 | 24.00 | 176.67 | 24.08 |
October | 8.17 | 25.55 | 335.83 | 23.99 | 8.17 | 25.55 |
November | 12.33 | 23.35 | 205.00 | 23.95 | 0.00 | 0.00 |
December | 146.00 | 22.82 | 7.33 | 23.79 | 0.33 | 21.34 |
Annual Sum or Average | 1460.00 | 23.58 | 2738.00 | 23.99 | 865.17 | 24.12 |
Minimum of Months | 3.33 | 22.65 | 3.00 | 21.20 | 0.00 | 0.00 |
Maximum of Months | 298.83 | 28.57 | 348.00 | 24.03 | 281.00 | 28.81 |
Report: OccupantComfortDataSummaryMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 496.00000 | 23.25307 | 39.43095 | 0.21693 | 6.94644 |
February | 448.00000 | 23.66981 | 40.88403 | 0.35340 | 8.00603 |
March | 496.00000 | 23.88398 | 41.54788 | 0.45053 | 9.36737 |
April | 480.00000 | 23.96578 | 41.68321 | 0.52344 | 10.87612 |
May | 496.00000 | 24.01830 | 50.83817 | -0.1872 | 6.04373 |
June | 480.00000 | 24.02253 | 57.19943 | -0.1208 | 5.66208 |
July | 496.00000 | 24.01751 | 63.80686 | -0.0801 | 5.52474 |
August | 496.00000 | 24.03209 | 65.23040 | -0.0741 | 5.51263 |
September | 480.00000 | 24.00602 | 62.01588 | -0.1228 | 5.60731 |
October | 496.00000 | 23.95729 | 47.77683 | 0.57174 | 11.95340 |
November | 480.00000 | 23.88127 | 41.20779 | 0.45920 | 9.49811 |
December | 496.00000 | 23.58677 | 38.17552 | 0.31317 | 7.58421 |
Annual Sum or Average | 5840.00000 | 23.85820 | 49.20260 | 0.19070 | 7.71064 |
Minimum of Months | 448.00000 | 23.25307 | 38.17552 | -0.1872 | 5.51263 |
Maximum of Months | 496.00000 | 24.03209 | 65.23040 | 0.57174 | 11.95340 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 496.00000 | 23.51346 | 38.81031 | 0.26873 | 7.12641 |
February | 448.00000 | 23.76227 | 39.79416 | 0.36742 | 8.06719 |
March | 496.00000 | 23.90418 | 40.69135 | 0.44577 | 9.24324 |
April | 480.00000 | 23.97365 | 41.21672 | 0.50857 | 10.54517 |
May | 496.00000 | 24.01940 | 49.95673 | -0.2220 | 6.34433 |
June | 480.00000 | 24.02163 | 56.14568 | -0.1641 | 5.91267 |
July | 496.00000 | 24.01543 | 62.61313 | -0.1258 | 5.69880 |
August | 496.00000 | 24.02991 | 64.09484 | -0.1214 | 5.68705 |
September | 480.00000 | 24.00427 | 60.57797 | -0.1688 | 5.88138 |
October | 496.00000 | 23.95966 | 46.60138 | 0.54405 | 11.30085 |
November | 480.00000 | 23.89364 | 40.20947 | 0.44362 | 9.18166 |
December | 496.00000 | 23.71594 | 37.37642 | 0.33217 | 7.63159 |
Annual Sum or Average | 5840.00000 | 23.90147 | 48.22795 | 0.17434 | 7.71372 |
Minimum of Months | 448.00000 | 23.51346 | 37.37642 | -0.2220 | 5.68705 |
Maximum of Months | 496.00000 | 24.02991 | 64.09484 | 0.54405 | 11.30085 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 23.22725 | 38.63502 | 0.19652 | 6.78372 |
February | 336.00000 | 23.71110 | 39.97811 | 0.35121 | 8.02018 |
March | 379.00000 | 23.98876 | 40.73165 | 0.46260 | 9.66830 |
April | 360.00000 | 24.11263 | 40.98041 | 0.54070 | 11.47029 |
May | 375.00000 | 24.16303 | 50.67280 | -0.1626 | 6.37027 |
June | 366.00000 | 24.16848 | 57.30573 | -0.1012 | 6.11198 |
July | 369.00000 | 24.16041 | 64.73012 | -0.0577 | 5.98050 |
August | 379.00000 | 24.13338 | 66.70187 | -0.0631 | 5.83383 |
September | 360.00000 | 24.12164 | 63.14400 | -0.1075 | 5.89340 |
October | 371.00000 | 24.06759 | 47.58129 | 0.58085 | 12.30450 |
November | 360.00000 | 23.94416 | 40.29780 | 0.45675 | 9.49309 |
December | 369.00000 | 23.59018 | 37.04009 | 0.29873 | 7.40494 |
Annual Sum or Average | 4395.00000 | 23.95054 | 49.06885 | 0.19776 | 7.93750 |
Minimum of Months | 336.00000 | 23.22725 | 37.04009 | -0.1626 | 5.83383 |
Maximum of Months | 379.00000 | 24.16848 | 66.70187 | 0.58085 | 12.30450 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 23.14870 | 38.87006 | 0.17116 | 6.67790 |
February | 336.00000 | 23.68853 | 40.08472 | 0.34223 | 7.93398 |
March | 379.00000 | 23.98642 | 40.74856 | 0.46106 | 9.64219 |
April | 360.00000 | 24.11325 | 40.95841 | 0.54211 | 11.50588 |
May | 375.00000 | 24.16382 | 50.60651 | -0.1586 | 6.35442 |
June | 366.00000 | 24.16929 | 57.21089 | -0.0976 | 6.10982 |
July | 369.00000 | 24.16107 | 64.58396 | -0.0542 | 5.98657 |
August | 379.00000 | 24.13399 | 66.58279 | -0.0607 | 5.83811 |
September | 360.00000 | 24.12237 | 63.04035 | -0.1053 | 5.89286 |
October | 371.00000 | 24.06833 | 47.54720 | 0.58203 | 12.33628 |
November | 360.00000 | 23.94013 | 40.32893 | 0.45429 | 9.45216 |
December | 369.00000 | 23.55897 | 37.16014 | 0.28715 | 7.31834 |
Annual Sum or Average | 4395.00000 | 23.93944 | 49.06167 | 0.19516 | 7.91400 |
Minimum of Months | 336.00000 | 23.14870 | 37.16014 | -0.1586 | 5.83811 |
Maximum of Months | 379.00000 | 24.16929 | 66.58279 | 0.58203 | 12.33628 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 23.05409 | 39.14604 | 0.14308 | 6.55475 |
February | 336.00000 | 23.65289 | 40.26942 | 0.32963 | 7.80876 |
March | 379.00000 | 23.97836 | 40.85771 | 0.45570 | 9.54419 |
April | 360.00000 | 24.10970 | 41.01283 | 0.53879 | 11.42354 |
May | 375.00000 | 24.16189 | 50.68640 | -0.1610 | 6.35369 |
June | 366.00000 | 24.16722 | 57.32778 | -0.0996 | 6.09775 |
July | 369.00000 | 24.15927 | 64.71990 | -0.0553 | 5.97357 |
August | 379.00000 | 24.13187 | 66.75680 | -0.0623 | 5.82523 |
September | 360.00000 | 24.11976 | 63.21844 | -0.1074 | 5.88566 |
October | 371.00000 | 24.06474 | 47.65844 | 0.57953 | 12.26962 |
November | 360.00000 | 23.93170 | 40.43251 | 0.44932 | 9.36403 |
December | 369.00000 | 23.51633 | 37.33054 | 0.27308 | 7.21893 |
Annual Sum or Average | 4395.00000 | 23.92229 | 49.20269 | 0.18852 | 7.85379 |
Minimum of Months | 336.00000 | 23.05409 | 37.33054 | -0.1610 | 5.82523 |
Maximum of Months | 379.00000 | 24.16722 | 66.75680 | 0.57953 | 12.26962 |
Report: OccupantComfortDataSummaryMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 22.96666 | 40.17827 | 0.11330 | 6.29212 |
February | 308.00000 | 23.63993 | 40.87614 | 0.31960 | 7.58940 |
March | 348.00000 | 23.90994 | 41.35581 | 0.44099 | 9.22481 |
April | 330.00000 | 24.00408 | 41.59099 | 0.52369 | 11.00346 |
May | 344.00000 | 24.02827 | 51.51498 | -0.1845 | 6.22708 |
June | 336.00000 | 24.01776 | 58.20879 | -0.1263 | 5.83377 |
July | 338.00000 | 24.04671 | 65.57998 | -0.0734 | 5.78506 |
August | 348.00000 | 24.00555 | 67.63809 | -0.0856 | 5.61424 |
September | 330.00000 | 24.01405 | 63.94856 | -0.1278 | 5.78418 |
October | 340.00000 | 23.98404 | 48.14970 | 0.57012 | 11.98722 |
November | 330.00000 | 23.90364 | 40.76776 | 0.44310 | 9.20398 |
December | 338.00000 | 23.50131 | 38.27917 | 0.26443 | 7.09225 |
Annual Sum or Average | 4030.00000 | 23.83624 | 49.92962 | 0.17122 | 7.62991 |
Minimum of Months | 308.00000 | 22.96666 | 38.27917 | -0.1845 | 5.61424 |
Maximum of Months | 348.00000 | 24.04671 | 67.63809 | 0.57012 | 11.98722 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 22.93869 | 40.18579 | 0.09641 | 6.21918 |
February | 308.00000 | 23.63587 | 40.88218 | 0.30652 | 7.41998 |
March | 348.00000 | 23.91028 | 41.37344 | 0.42599 | 8.94503 |
April | 330.00000 | 24.00278 | 41.56206 | 0.50371 | 10.56583 |
May | 344.00000 | 24.02726 | 51.53012 | -0.2153 | 6.48265 |
June | 336.00000 | 24.01641 | 58.30842 | -0.1578 | 6.02094 |
July | 338.00000 | 24.04516 | 65.81485 | -0.1026 | 5.89321 |
August | 348.00000 | 24.00423 | 67.93746 | -0.1136 | 5.73424 |
September | 330.00000 | 24.01280 | 64.18072 | -0.1548 | 5.94647 |
October | 340.00000 | 23.98365 | 48.22259 | 0.55135 | 11.54008 |
November | 330.00000 | 23.90443 | 40.79621 | 0.42827 | 8.92662 |
December | 338.00000 | 23.49844 | 38.26499 | 0.25273 | 6.97525 |
Annual Sum or Average | 4030.00000 | 23.83273 | 50.01131 | 0.14975 | 7.55071 |
Minimum of Months | 308.00000 | 22.93869 | 38.26499 | -0.2153 | 5.73424 |
Maximum of Months | 348.00000 | 24.04516 | 67.93746 | 0.55135 | 11.54008 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 22.90261 | 40.28277 | 0.08529 | 6.18589 |
February | 308.00000 | 23.62137 | 40.95654 | 0.30023 | 7.36237 |
March | 348.00000 | 23.90775 | 41.41624 | 0.42286 | 8.89203 |
April | 330.00000 | 24.00204 | 41.58627 | 0.50119 | 10.51119 |
May | 344.00000 | 24.02702 | 51.57366 | -0.2181 | 6.50591 |
June | 336.00000 | 24.01625 | 58.36901 | -0.1603 | 6.03600 |
July | 338.00000 | 24.04495 | 65.89022 | -0.1048 | 5.90001 |
August | 348.00000 | 24.00406 | 68.01841 | -0.1156 | 5.74200 |
September | 330.00000 | 24.01231 | 64.25778 | -0.1569 | 5.95757 |
October | 340.00000 | 23.98280 | 48.26622 | 0.54948 | 11.49554 |
November | 330.00000 | 23.90272 | 40.83104 | 0.42585 | 8.88457 |
December | 338.00000 | 23.48162 | 38.32716 | 0.24659 | 6.93512 |
Annual Sum or Average | 4030.00000 | 23.82658 | 50.07099 | 0.14600 | 7.52926 |
Minimum of Months | 308.00000 | 22.90261 | 38.32716 | -0.2181 | 5.74200 |
Maximum of Months | 348.00000 | 24.04495 | 68.01841 | 0.54948 | 11.49554 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 22.82714 | 40.48492 | 0.06475 | 6.15131 |
February | 308.00000 | 23.57976 | 41.14848 | 0.28616 | 7.25954 |
March | 348.00000 | 23.89920 | 41.52392 | 0.41755 | 8.81305 |
April | 330.00000 | 24.00042 | 41.62365 | 0.49997 | 10.48476 |
May | 344.00000 | 24.02675 | 51.60477 | -0.2164 | 6.48956 |
June | 336.00000 | 24.01647 | 58.38497 | -0.1575 | 6.01862 |
July | 338.00000 | 24.04503 | 65.86050 | -0.1010 | 5.88738 |
August | 348.00000 | 24.00439 | 67.96836 | -0.1116 | 5.72675 |
September | 330.00000 | 24.01214 | 64.23644 | -0.1534 | 5.93584 |
October | 340.00000 | 23.98207 | 48.29104 | 0.55081 | 11.52697 |
November | 330.00000 | 23.89811 | 40.89503 | 0.42393 | 8.85740 |
December | 338.00000 | 23.43852 | 38.47560 | 0.23420 | 6.87444 |
Annual Sum or Average | 4030.00000 | 23.81212 | 50.13029 | 0.14289 | 7.49784 |
Minimum of Months | 308.00000 | 22.82714 | 38.47560 | -0.2164 | 5.72675 |
Maximum of Months | 348.00000 | 24.04503 | 67.96836 | 0.55081 | 11.52697 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 22.76745 | 40.64940 | 0.04496 | 6.19390 |
February | 308.00000 | 23.50280 | 41.43912 | 0.26242 | 7.17125 |
March | 348.00000 | 23.87547 | 41.74481 | 0.41173 | 8.78254 |
April | 330.00000 | 24.00009 | 41.62844 | 0.51489 | 10.82211 |
May | 344.00000 | 24.02890 | 51.46734 | -0.1798 | 6.21062 |
June | 336.00000 | 24.01828 | 57.96498 | -0.1172 | 5.81218 |
July | 338.00000 | 24.04949 | 65.02597 | -0.0586 | 5.81163 |
August | 348.00000 | 24.00795 | 66.80998 | -0.0686 | 5.61401 |
September | 330.00000 | 24.01694 | 63.25149 | -0.1124 | 5.75297 |
October | 340.00000 | 23.98710 | 47.94455 | 0.57656 | 12.16405 |
November | 330.00000 | 23.89384 | 40.85949 | 0.43485 | 9.08689 |
December | 338.00000 | 23.39332 | 38.55056 | 0.22266 | 6.88941 |
Annual Sum or Average | 4030.00000 | 23.79682 | 49.86256 | 0.15933 | 7.52139 |
Minimum of Months | 308.00000 | 22.76745 | 38.55056 | -0.1798 | 5.61401 |
Maximum of Months | 348.00000 | 24.04949 | 66.80998 | 0.57656 | 12.16405 |
Report: DXReportMonthly
For: PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.238603E+10 | 0.654028E+09 | 218.75 | 0.214545E+10 | 0.240576E+09 | 0.00 | 0.44 | 12-JAN-15:00 | 0.00 | 01-JAN-00:10 | 9135.55 | 12-JAN-15:00 | 8700.57 | 12-JAN-15:00 | 1475.36 | 13-JAN-14:00 | 2452.92 | 12-JAN-15:00 | 0.00 | 01-JAN-00:10 |
February | 0.782202E+10 | 0.210306E+10 | 339.83 | 0.684924E+10 | 0.972781E+09 | 0.00 | 0.66 | 22-FEB-15:00 | 0.00 | 01-FEB-00:05 | 14898.07 | 22-FEB-15:00 | 13860.46 | 22-FEB-15:00 | 3824.99 | 25-FEB-18:05 | 3979.39 | 22-FEB-15:00 | 0.00 | 01-FEB-00:05 |
March | 0.188898E+11 | 0.508395E+10 | 463.18 | 0.164662E+11 | 0.242358E+10 | 0.00 | 1.00 | 11-MAR-09:02 | 0.00 | 01-MAR-00:05 | 53466.74 | 11-MAR-09:02 | 43046.38 | 11-MAR-09:02 | 12275.07 | 29-MAR-08:62 | 12258.32 | 11-MAR-09:02 | 0.00 | 01-MAR-00:05 |
April | 0.304616E+11 | 0.863161E+10 | 464.78 | 0.275799E+11 | 0.288173E+10 | 0.00 | 1.00 | 01-APR-08:62 | 0.00 | 01-APR-00:05 | 55178.20 | 26-APR-08:61 | 50319.08 | 08-APR-08:62 | 17204.16 | 26-APR-08:04 | 13123.28 | 27-APR-08:61 | 0.00 | 01-APR-00:05 |
May | 0.447322E+11 | 0.127651E+11 | 497.86 | 0.361638E+11 | 0.856837E+10 | 0.00 | 1.00 | 01-MAY-08:61 | 0.00 | 01-MAY-00:10 | 58181.91 | 24-MAY-08:61 | 50219.16 | 06-MAY-08:61 | 28180.57 | 24-MAY-08:04 | 14063.46 | 04-MAY-08:61 | 0.00 | 01-MAY-00:10 |
June | 0.512291E+11 | 0.140667E+11 | 487.11 | 0.365685E+11 | 0.146605E+11 | 0.00 | 1.00 | 01-JUN-08:61 | 0.00 | 01-JUN-00:10 | 59292.83 | 26-JUN-08:61 | 48111.84 | 07-JUN-08:61 | 31944.04 | 26-JUN-08:06 | 14267.29 | 22-JUN-16:10 | 0.00 | 01-JUN-00:10 |
July | 0.588917E+11 | 0.148283E+11 | 503.60 | 0.349235E+11 | 0.239682E+11 | 0.00 | 1.00 | 01-JUL-08:61 | 0.00 | 01-JUL-00:03 | 59368.59 | 18-JUL-08:61 | 41645.29 | 07-JUL-07:01 | 33201.03 | 25-JUL-08:04 | 14082.62 | 01-JUL-16:10 | 0.00 | 01-JUL-00:03 |
August | 0.584694E+11 | 0.141874E+11 | 500.15 | 0.324751E+11 | 0.259943E+11 | 0.00 | 1.00 | 01-AUG-08:61 | 0.00 | 01-AUG-00:10 | 59428.66 | 26-AUG-08:61 | 36251.95 | 06-AUG-07:01 | 35862.29 | 12-AUG-08:07 | 13333.78 | 07-AUG-08:13 | 0.00 | 01-AUG-00:10 |
September | 0.483573E+11 | 0.118259E+11 | 479.82 | 0.289190E+11 | 0.194384E+11 | 0.00 | 1.00 | 01-SEP-08:61 | 0.00 | 01-SEP-00:10 | 59205.20 | 06-SEP-08:61 | 40093.67 | 26-SEP-08:61 | 31591.19 | 09-SEP-08:04 | 13037.59 | 22-SEP-08:13 | 0.00 | 01-SEP-00:10 |
October | 0.306741E+11 | 0.798259E+10 | 476.11 | 0.244362E+11 | 0.623786E+10 | 0.00 | 1.00 | 01-OCT-07:02 | 0.00 | 01-OCT-00:03 | 56837.13 | 12-OCT-08:62 | 44619.64 | 16-OCT-08:62 | 25190.73 | 12-OCT-08:62 | 12704.49 | 04-OCT-08:61 | 0.00 | 01-OCT-00:03 |
November | 0.164150E+11 | 0.433871E+10 | 446.83 | 0.142386E+11 | 0.217646E+10 | 0.00 | 0.94 | 11-NOV-08:63 | 0.00 | 01-NOV-00:10 | 44845.29 | 09-NOV-09:02 | 32773.66 | 09-NOV-09:02 | 12071.63 | 09-NOV-09:02 | 9794.53 | 09-NOV-09:02 | 0.00 | 01-NOV-00:10 |
December | 0.503114E+10 | 0.136327E+10 | 327.50 | 0.440301E+10 | 0.628128E+09 | 0.00 | 0.53 | 28-DEC-15:00 | 0.00 | 01-DEC-00:10 | 11633.87 | 28-DEC-15:00 | 10898.46 | 03-DEC-14:00 | 1661.95 | 16-DEC-14:00 | 3080.90 | 28-DEC-15:00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.373359E+12 | 0.978306E+11 | 5205.53 | 0.265169E+12 | 0.108191E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.238603E+10 | 0.654028E+09 | 218.75 | 0.214545E+10 | 0.240576E+09 | 0.00 | 0.44 | 0.00 | 9135.55 | 8700.57 | 1475.36 | 2452.92 | 0.00 | |||||||
Maximum of Months | 0.588917E+11 | 0.148283E+11 | 503.60 | 0.365685E+11 | 0.259943E+11 | 0.00 | 1.00 | 0.00 | 59428.66 | 50319.08 | 35862.29 | 14267.29 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.225393E+10 | 0.621023E+09 | 335.03 | 0.203701E+10 | 0.216915E+09 | 0.00 | 0.45 | 12-JAN-15:00 | 0.00 | 01-JAN-00:10 | 4999.67 | 12-JAN-15:00 | 4782.62 | 12-JAN-15:00 | 1216.90 | 16-JAN-18:20 | 1311.93 | 12-JAN-15:00 | 0.00 | 01-JAN-00:10 |
February | 0.499073E+10 | 0.133251E+10 | 384.50 | 0.443556E+10 | 0.555170E+09 | 0.00 | 0.68 | 22-FEB-14:50 | 0.00 | 01-FEB-00:05 | 7937.62 | 22-FEB-14:40 | 7399.44 | 22-FEB-14:50 | 2036.30 | 25-FEB-18:05 | 2075.05 | 22-FEB-14:50 | 0.00 | 01-FEB-00:05 |
March | 0.102104E+11 | 0.272330E+10 | 468.46 | 0.907068E+10 | 0.113977E+10 | 0.00 | 1.00 | 11-MAR-09:02 | 0.00 | 01-MAR-00:05 | 27735.34 | 11-MAR-09:02 | 23195.90 | 11-MAR-09:02 | 5968.79 | 29-MAR-08:62 | 6265.72 | 11-MAR-09:02 | 0.00 | 01-MAR-00:05 |
April | 0.153616E+11 | 0.434145E+10 | 465.89 | 0.140848E+11 | 0.127681E+10 | 0.00 | 1.00 | 01-APR-08:62 | 0.00 | 01-APR-00:05 | 28548.64 | 26-APR-08:61 | 26351.46 | 08-APR-08:62 | 7939.99 | 26-APR-08:04 | 6714.37 | 27-APR-08:61 | 0.00 | 01-APR-00:05 |
May | 0.221700E+11 | 0.632654E+10 | 498.53 | 0.181828E+11 | 0.398728E+10 | 0.00 | 1.00 | 01-MAY-08:61 | 0.00 | 01-MAY-00:10 | 30016.34 | 24-MAY-08:61 | 26259.93 | 06-MAY-08:61 | 13325.67 | 24-MAY-08:04 | 7208.58 | 04-MAY-08:61 | 0.00 | 01-MAY-00:10 |
June | 0.251273E+11 | 0.689521E+10 | 487.11 | 0.182143E+11 | 0.691302E+10 | 0.00 | 1.00 | 01-JUN-08:61 | 0.00 | 01-JUN-00:10 | 30584.52 | 26-JUN-08:61 | 25318.12 | 07-JUN-08:61 | 15318.85 | 24-JUN-08:13 | 7285.91 | 12-JUN-08:61 | 0.00 | 01-JUN-00:10 |
July | 0.286626E+11 | 0.720867E+10 | 503.29 | 0.173437E+11 | 0.113189E+11 | 0.00 | 1.00 | 01-JUL-08:61 | 0.00 | 01-JUL-00:03 | 30865.49 | 18-JUL-08:61 | 21865.21 | 05-JUL-07:01 | 16354.47 | 18-JUL-08:06 | 7139.71 | 05-JUL-08:13 | 0.00 | 01-JUL-00:03 |
August | 0.284333E+11 | 0.689083E+10 | 500.04 | 0.161360E+11 | 0.122973E+11 | 0.00 | 1.00 | 01-AUG-08:61 | 0.00 | 01-AUG-00:10 | 30934.14 | 12-AUG-08:61 | 20565.53 | 06-AUG-07:01 | 17609.15 | 12-AUG-08:06 | 6831.04 | 07-AUG-08:13 | 0.00 | 01-AUG-00:10 |
September | 0.234699E+11 | 0.574885E+10 | 478.60 | 0.144093E+11 | 0.906063E+10 | 0.00 | 1.00 | 01-SEP-08:61 | 0.00 | 01-SEP-00:10 | 30522.19 | 12-SEP-08:61 | 21762.63 | 26-SEP-08:61 | 15101.41 | 12-SEP-08:13 | 6674.64 | 22-SEP-08:61 | 0.00 | 01-SEP-00:10 |
October | 0.153945E+11 | 0.399999E+10 | 476.56 | 0.125498E+11 | 0.284471E+10 | 0.00 | 1.00 | 01-OCT-07:02 | 0.00 | 01-OCT-00:03 | 29345.71 | 12-OCT-08:62 | 24114.71 | 16-OCT-08:62 | 11667.79 | 12-OCT-08:62 | 6500.38 | 04-OCT-08:61 | 0.00 | 01-OCT-00:03 |
November | 0.903123E+10 | 0.237038E+10 | 455.58 | 0.798473E+10 | 0.104650E+10 | 0.00 | 0.96 | 10-NOV-09:03 | 0.00 | 01-NOV-00:10 | 22817.04 | 09-NOV-09:02 | 17673.11 | 09-NOV-09:02 | 5143.92 | 09-NOV-09:02 | 4911.02 | 09-NOV-09:02 | 0.00 | 01-NOV-00:10 |
December | 0.378685E+10 | 0.102538E+10 | 405.33 | 0.335726E+10 | 0.429589E+09 | 0.00 | 0.54 | 03-DEC-14:00 | 0.00 | 01-DEC-01:05 | 6157.41 | 28-DEC-14:50 | 5901.42 | 03-DEC-14:00 | 1044.01 | 29-DEC-21:10 | 1599.72 | 28-DEC-14:40 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.188892E+12 | 0.494841E+11 | 5458.93 | 0.137806E+12 | 0.510866E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.225393E+10 | 0.621023E+09 | 335.03 | 0.203701E+10 | 0.216915E+09 | 0.00 | 0.45 | 0.00 | 4999.67 | 4782.62 | 1044.01 | 1311.93 | 0.00 | |||||||
Maximum of Months | 0.286626E+11 | 0.720867E+10 | 503.29 | 0.182143E+11 | 0.122973E+11 | 0.00 | 1.00 | 0.00 | 30934.14 | 26351.46 | 17609.15 | 7285.91 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.926817E+09 | 0.249815E+09 | 157.83 | 0.851340E+09 | 75476525.70 | 0.00 | 0.42 | 12-JAN-15:00 | 0.00 | 01-JAN-00:10 | 4509.41 | 12-JAN-15:00 | 4317.78 | 12-JAN-15:00 | 732.36 | 14-JAN-14:00 | 1196.03 | 12-JAN-15:00 | 0.00 | 01-JAN-00:10 |
February | 0.318573E+10 | 0.842628E+09 | 240.58 | 0.284708E+10 | 0.338651E+09 | 0.00 | 0.65 | 22-FEB-14:00 | 0.00 | 01-FEB-00:05 | 7563.37 | 22-FEB-14:40 | 7062.37 | 22-FEB-14:00 | 1706.18 | 25-FEB-16:40 | 1991.09 | 22-FEB-14:40 | 0.00 | 01-FEB-00:05 |
March | 0.774887E+10 | 0.205213E+10 | 334.67 | 0.687404E+10 | 0.874834E+09 | 0.00 | 1.00 | 11-MAR-08:62 | 0.00 | 01-MAR-00:05 | 28153.16 | 11-MAR-08:62 | 21231.98 | 11-MAR-08:62 | 6921.19 | 11-MAR-08:62 | 6180.34 | 11-MAR-08:62 | 0.00 | 01-MAR-00:05 |
April | 0.122788E+11 | 0.341832E+10 | 334.03 | 0.112121E+11 | 0.106664E+10 | 0.00 | 1.00 | 01-APR-07:02 | 0.00 | 01-APR-00:05 | 28756.41 | 26-APR-07:01 | 26384.47 | 30-APR-08:61 | 8979.90 | 26-APR-07:03 | 6680.05 | 16-APR-08:61 | 0.00 | 01-APR-00:05 |
May | 0.183513E+11 | 0.517011E+10 | 372.79 | 0.149362E+11 | 0.341510E+10 | 0.00 | 1.00 | 01-MAY-07:01 | 0.00 | 01-MAY-00:10 | 30204.76 | 24-MAY-07:01 | 26223.63 | 06-MAY-07:01 | 14363.82 | 24-MAY-07:04 | 7029.48 | 04-MAY-07:01 | 0.00 | 01-MAY-00:10 |
June | 0.208484E+11 | 0.563079E+10 | 367.38 | 0.149050E+11 | 0.594340E+10 | 0.00 | 1.00 | 01-JUN-07:01 | 0.00 | 01-JUN-00:10 | 30888.93 | 25-JUN-08:61 | 24780.05 | 07-JUN-07:01 | 18048.27 | 26-JUN-07:04 | 7168.77 | 22-JUN-16:10 | 0.00 | 01-JUN-00:10 |
July | 0.233137E+11 | 0.576025E+10 | 369.93 | 0.137337E+11 | 0.957996E+10 | 0.00 | 1.00 | 01-JUL-07:01 | 0.00 | 01-JUL-00:03 | 30925.30 | 28-JUL-07:01 | 20083.38 | 05-JUL-06:02 | 17985.68 | 23-JUL-08:04 | 7055.22 | 02-JUL-08:13 | 0.00 | 01-JUL-00:03 |
August | 0.236661E+11 | 0.564143E+10 | 377.52 | 0.130588E+11 | 0.106073E+11 | 0.00 | 1.00 | 01-AUG-07:01 | 0.00 | 01-AUG-00:10 | 30979.83 | 21-AUG-07:02 | 17223.41 | 03-AUG-07:01 | 19350.11 | 21-AUG-07:05 | 6744.81 | 08-AUG-07:13 | 0.00 | 01-AUG-00:10 |
September | 0.190343E+11 | 0.456576E+10 | 349.00 | 0.113702E+11 | 0.766416E+10 | 0.00 | 1.00 | 01-SEP-07:01 | 0.00 | 01-SEP-00:10 | 31007.88 | 09-SEP-07:01 | 19490.12 | 26-SEP-07:01 | 19181.50 | 11-SEP-07:05 | 6589.82 | 24-SEP-08:13 | 0.00 | 01-SEP-00:10 |
October | 0.121790E+11 | 0.312392E+10 | 337.81 | 0.984685E+10 | 0.233218E+10 | 0.00 | 1.00 | 01-OCT-08:61 | 0.00 | 01-OCT-00:03 | 29571.33 | 12-OCT-07:02 | 23089.06 | 16-OCT-07:02 | 13422.20 | 13-OCT-07:03 | 6403.47 | 04-OCT-07:01 | 0.00 | 01-OCT-00:03 |
November | 0.670678E+10 | 0.174966E+10 | 315.50 | 0.596714E+10 | 0.739640E+09 | 0.00 | 0.84 | 09-NOV-13:30 | 0.00 | 01-NOV-00:10 | 10460.11 | 09-NOV-13:20 | 9707.91 | 04-NOV-14:00 | 2738.43 | 09-NOV-08:65 | 2692.21 | 09-NOV-13:30 | 0.00 | 01-NOV-00:10 |
December | 0.206979E+10 | 0.552271E+09 | 242.83 | 0.185348E+10 | 0.216309E+09 | 0.00 | 0.51 | 28-DEC-14:00 | 0.00 | 01-DEC-00:10 | 5713.00 | 28-DEC-14:00 | 5494.92 | 02-DEC-14:00 | 819.68 | 16-DEC-14:00 | 1500.02 | 28-DEC-14:00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.150310E+12 | 0.387571E+11 | 3799.88 | 0.107456E+12 | 0.428537E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.926817E+09 | 0.249815E+09 | 157.83 | 0.851340E+09 | 75476525.70 | 0.00 | 0.42 | 0.00 | 4509.41 | 4317.78 | 732.36 | 1196.03 | 0.00 | |||||||
Maximum of Months | 0.236661E+11 | 0.576025E+10 | 377.52 | 0.149362E+11 | 0.106073E+11 | 0.00 | 1.00 | 0.00 | 31007.88 | 26384.47 | 19350.11 | 7168.77 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.814832E+09 | 0.220129E+09 | 144.00 | 0.747920E+09 | 66912421.04 | 0.00 | 0.40 | 12-JAN-15:00 | 0.00 | 01-JAN-00:10 | 4367.45 | 12-JAN-15:00 | 4181.01 | 12-JAN-15:00 | 713.55 | 14-JAN-14:00 | 1162.43 | 12-JAN-15:00 | 0.00 | 01-JAN-00:10 |
February | 0.308540E+10 | 0.817844E+09 | 238.17 | 0.275769E+10 | 0.327708E+09 | 0.00 | 0.65 | 22-FEB-14:00 | 0.00 | 01-FEB-00:05 | 7503.58 | 24-FEB-15:00 | 6995.73 | 22-FEB-14:00 | 1688.03 | 25-FEB-16:40 | 1975.80 | 22-FEB-14:40 | 0.00 | 01-FEB-00:05 |
March | 0.771740E+10 | 0.204540E+10 | 334.50 | 0.684546E+10 | 0.871942E+09 | 0.00 | 1.00 | 11-MAR-08:62 | 0.00 | 01-MAR-00:05 | 28208.87 | 11-MAR-08:62 | 21270.82 | 11-MAR-08:62 | 6938.05 | 11-MAR-08:62 | 6192.47 | 11-MAR-08:62 | 0.00 | 01-MAR-00:05 |
April | 0.123276E+11 | 0.343116E+10 | 334.76 | 0.112568E+11 | 0.107077E+10 | 0.00 | 1.00 | 01-APR-07:02 | 0.00 | 01-APR-00:05 | 28816.40 | 26-APR-07:01 | 26457.97 | 30-APR-08:61 | 8973.15 | 26-APR-07:03 | 6692.26 | 16-APR-08:61 | 0.00 | 01-APR-00:05 |
May | 0.184790E+11 | 0.520392E+10 | 373.91 | 0.150488E+11 | 0.343020E+10 | 0.00 | 1.00 | 01-MAY-07:01 | 0.00 | 01-MAY-00:10 | 30259.36 | 24-MAY-07:01 | 26274.16 | 06-MAY-07:01 | 14356.53 | 24-MAY-07:04 | 7042.81 | 04-MAY-07:01 | 0.00 | 01-MAY-00:10 |
June | 0.209796E+11 | 0.566586E+10 | 367.64 | 0.150143E+11 | 0.596530E+10 | 0.00 | 1.00 | 01-JUN-07:01 | 0.00 | 01-JUN-00:10 | 30949.08 | 25-JUN-08:61 | 24925.84 | 12-JUN-06:02 | 17957.58 | 26-JUN-07:04 | 7178.39 | 22-JUN-16:10 | 0.00 | 01-JUN-00:10 |
July | 0.234699E+11 | 0.580068E+10 | 370.23 | 0.138550E+11 | 0.961497E+10 | 0.00 | 1.00 | 01-JUL-07:01 | 0.00 | 01-JUL-00:03 | 30985.52 | 28-JUL-07:01 | 20333.09 | 05-JUL-06:02 | 17910.53 | 23-JUL-08:04 | 7069.26 | 02-JUL-08:13 | 0.00 | 01-JUL-00:03 |
August | 0.237825E+11 | 0.567064E+10 | 378.05 | 0.131458E+11 | 0.106367E+11 | 0.00 | 1.00 | 01-AUG-07:01 | 0.00 | 01-AUG-00:10 | 31040.16 | 21-AUG-07:02 | 17307.08 | 03-AUG-07:01 | 19356.38 | 28-AUG-06:03 | 6757.67 | 08-AUG-07:13 | 0.00 | 01-AUG-00:10 |
September | 0.191263E+11 | 0.458764E+10 | 349.01 | 0.114390E+11 | 0.768734E+10 | 0.00 | 1.00 | 01-SEP-07:01 | 0.00 | 01-SEP-00:10 | 31068.26 | 09-SEP-07:01 | 19574.00 | 26-SEP-07:01 | 19145.00 | 11-SEP-07:05 | 6602.81 | 24-SEP-08:13 | 0.00 | 01-SEP-00:10 |
October | 0.122267E+11 | 0.313569E+10 | 338.01 | 0.988810E+10 | 0.233863E+10 | 0.00 | 1.00 | 01-OCT-08:61 | 0.00 | 01-OCT-00:03 | 29630.83 | 12-OCT-07:02 | 23188.65 | 16-OCT-07:02 | 13438.12 | 13-OCT-07:03 | 6415.62 | 04-OCT-07:01 | 0.00 | 01-OCT-00:03 |
November | 0.665835E+10 | 0.173887E+10 | 314.42 | 0.592330E+10 | 0.735053E+09 | 0.00 | 0.84 | 09-NOV-13:30 | 0.00 | 01-NOV-00:10 | 10431.61 | 09-NOV-13:20 | 9682.03 | 04-NOV-14:00 | 2682.60 | 09-NOV-08:65 | 2687.47 | 09-NOV-13:30 | 0.00 | 01-NOV-00:10 |
December | 0.194795E+10 | 0.521061E+09 | 238.67 | 0.174469E+10 | 0.203264E+09 | 0.00 | 0.50 | 28-DEC-14:00 | 0.00 | 01-DEC-00:10 | 5583.35 | 28-DEC-14:00 | 5418.76 | 02-DEC-14:00 | 802.38 | 16-DEC-14:00 | 1470.58 | 28-DEC-14:00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.150616E+12 | 0.388389E+11 | 3781.36 | 0.107667E+12 | 0.429488E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.814832E+09 | 0.220129E+09 | 144.00 | 0.747920E+09 | 66912421.04 | 0.00 | 0.40 | 0.00 | 4367.45 | 4181.01 | 713.55 | 1162.43 | 0.00 | |||||||
Maximum of Months | 0.237825E+11 | 0.580068E+10 | 378.05 | 0.150488E+11 | 0.106367E+11 | 0.00 | 1.00 | 0.00 | 31068.26 | 26457.97 | 19356.38 | 7178.39 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.679161E+09 | 0.184040E+09 | 127.50 | 0.622263E+09 | 56898257.66 | 0.00 | 0.39 | 12-JAN-15:00 | 0.00 | 01-JAN-00:10 | 4150.36 | 12-JAN-15:00 | 3970.98 | 12-JAN-15:00 | 681.90 | 14-JAN-14:00 | 1109.90 | 12-JAN-15:00 | 0.00 | 01-JAN-00:10 |
February | 0.290675E+10 | 0.773055E+09 | 232.00 | 0.259927E+10 | 0.307483E+09 | 0.00 | 0.64 | 22-FEB-14:40 | 0.00 | 01-FEB-00:05 | 7353.74 | 24-FEB-15:00 | 6850.68 | 22-FEB-14:00 | 1635.87 | 25-FEB-16:30 | 1942.14 | 22-FEB-14:40 | 0.00 | 01-FEB-00:05 |
March | 0.752198E+10 | 0.199877E+10 | 331.92 | 0.667020E+10 | 0.851780E+09 | 0.00 | 1.00 | 11-MAR-08:62 | 0.00 | 01-MAR-00:05 | 28108.35 | 11-MAR-08:62 | 21104.26 | 11-MAR-08:62 | 7004.10 | 11-MAR-08:62 | 6171.97 | 11-MAR-08:62 | 0.00 | 01-MAR-00:05 |
April | 0.121753E+11 | 0.339289E+10 | 333.43 | 0.111145E+11 | 0.106075E+10 | 0.00 | 1.00 | 01-APR-07:02 | 0.00 | 01-APR-00:05 | 28715.68 | 26-APR-07:01 | 26359.64 | 30-APR-08:61 | 9021.84 | 26-APR-07:03 | 6672.33 | 16-APR-08:61 | 0.00 | 01-APR-00:05 |
May | 0.183393E+11 | 0.516573E+10 | 372.12 | 0.149272E+11 | 0.341203E+10 | 0.00 | 1.00 | 01-MAY-07:01 | 0.00 | 01-MAY-00:10 | 30166.97 | 24-MAY-07:01 | 26194.71 | 06-MAY-07:01 | 14379.19 | 24-MAY-07:04 | 7021.87 | 04-MAY-07:01 | 0.00 | 01-MAY-00:10 |
June | 0.208338E+11 | 0.562640E+10 | 367.22 | 0.148950E+11 | 0.593876E+10 | 0.00 | 1.00 | 01-JUN-07:01 | 0.00 | 01-JUN-00:10 | 30854.50 | 25-JUN-08:61 | 24829.63 | 12-JUN-06:02 | 17978.14 | 26-JUN-07:04 | 7140.83 | 22-JUN-16:10 | 0.00 | 01-JUN-00:10 |
July | 0.233378E+11 | 0.576711E+10 | 370.02 | 0.137549E+11 | 0.958293E+10 | 0.00 | 1.00 | 01-JUL-07:01 | 0.00 | 01-JUL-00:03 | 30890.82 | 28-JUL-07:01 | 20237.40 | 05-JUL-06:02 | 17945.93 | 23-JUL-08:04 | 7047.55 | 02-JUL-08:13 | 0.00 | 01-JUL-00:03 |
August | 0.236193E+11 | 0.563000E+10 | 377.02 | 0.130252E+11 | 0.105941E+11 | 0.00 | 1.00 | 01-AUG-07:01 | 0.00 | 01-AUG-00:10 | 30945.29 | 21-AUG-07:02 | 17178.21 | 08-AUG-07:01 | 19306.83 | 21-AUG-07:05 | 6737.20 | 08-AUG-07:13 | 0.00 | 01-AUG-00:10 |
September | 0.189666E+11 | 0.454914E+10 | 348.06 | 0.113189E+11 | 0.764775E+10 | 0.00 | 1.00 | 01-SEP-07:01 | 0.00 | 01-SEP-00:10 | 30973.31 | 09-SEP-07:01 | 19468.86 | 26-SEP-07:01 | 19178.90 | 11-SEP-07:05 | 6582.50 | 24-SEP-08:13 | 0.00 | 01-SEP-00:10 |
October | 0.120734E+11 | 0.310052E+10 | 337.55 | 0.975699E+10 | 0.231641E+10 | 0.00 | 1.00 | 01-OCT-08:61 | 0.00 | 01-OCT-00:03 | 29534.05 | 12-OCT-07:02 | 23067.41 | 16-OCT-07:02 | 13481.84 | 13-OCT-07:03 | 6396.58 | 04-OCT-07:01 | 0.00 | 01-OCT-00:03 |
November | 0.648537E+10 | 0.169786E+10 | 312.67 | 0.576749E+10 | 0.717873E+09 | 0.00 | 0.83 | 09-NOV-13:30 | 0.00 | 01-NOV-00:10 | 10301.21 | 09-NOV-13:30 | 9554.97 | 04-NOV-14:00 | 2382.66 | 09-NOV-08:65 | 2659.28 | 09-NOV-13:30 | 0.00 | 01-NOV-00:10 |
December | 0.176600E+10 | 0.473876E+09 | 230.33 | 0.158226E+10 | 0.183748E+09 | 0.00 | 0.49 | 02-DEC-14:00 | 0.00 | 01-DEC-00:10 | 5387.50 | 28-DEC-14:00 | 5279.34 | 02-DEC-14:00 | 775.83 | 16-DEC-14:00 | 1424.70 | 28-DEC-14:00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.148705E+12 | 0.383594E+11 | 3739.85 | 0.106034E+12 | 0.426705E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.679161E+09 | 0.184040E+09 | 127.50 | 0.622263E+09 | 56898257.66 | 0.00 | 0.39 | 0.00 | 4150.36 | 3970.98 | 681.90 | 1109.90 | 0.00 | |||||||
Maximum of Months | 0.236193E+11 | 0.576711E+10 | 377.02 | 0.149272E+11 | 0.105941E+11 | 0.00 | 1.00 | 0.00 | 30973.31 | 26359.64 | 19306.83 | 7140.83 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.931405E+09 | 0.257953E+09 | 102.33 | 0.841062E+09 | 90342909.37 | 0.00 | 0.37 | 12-JAN-15:10 | 0.00 | 01-JAN-00:10 | 7207.16 | 12-JAN-15:10 | 6781.18 | 12-JAN-15:10 | 1263.45 | 14-JAN-15:10 | 1970.54 | 12-JAN-15:10 | 0.00 | 01-JAN-00:10 |
February | 0.485014E+10 | 0.132000E+10 | 225.50 | 0.429856E+10 | 0.551579E+09 | 0.00 | 0.63 | 22-FEB-14:00 | 0.00 | 01-FEB-00:05 | 13459.94 | 24-FEB-15:20 | 12356.20 | 22-FEB-14:00 | 3174.08 | 25-FEB-16:00 | 3609.52 | 22-FEB-14:00 | 0.00 | 01-FEB-00:05 |
March | 0.134538E+11 | 0.365093E+10 | 326.93 | 0.118294E+11 | 0.162438E+10 | 0.00 | 1.00 | 11-MAR-09:02 | 0.00 | 01-MAR-00:05 | 51187.71 | 11-MAR-09:02 | 39920.52 | 11-MAR-09:02 | 11267.19 | 11-MAR-09:02 | 11707.05 | 11-MAR-09:02 | 0.00 | 01-MAR-00:05 |
April | 0.220338E+11 | 0.627007E+10 | 324.76 | 0.201164E+11 | 0.191736E+10 | 0.00 | 1.00 | 01-APR-08:62 | 0.00 | 01-APR-00:05 | 52281.86 | 26-APR-08:61 | 47905.95 | 08-APR-08:62 | 15458.47 | 26-APR-08:04 | 12885.87 | 16-APR-09:01 | 0.00 | 01-APR-00:05 |
May | 0.335219E+11 | 0.963085E+10 | 363.03 | 0.271900E+11 | 0.633193E+10 | 0.00 | 1.00 | 01-MAY-08:61 | 0.00 | 01-MAY-00:10 | 55176.05 | 24-MAY-08:61 | 48073.93 | 29-MAY-08:61 | 25980.12 | 24-MAY-08:04 | 13416.14 | 04-MAY-08:61 | 0.00 | 01-MAY-00:10 |
June | 0.381515E+11 | 0.105164E+11 | 358.03 | 0.271796E+11 | 0.109719E+11 | 0.00 | 1.00 | 01-JUN-08:61 | 0.00 | 01-JUN-00:10 | 56519.76 | 25-JUN-09:01 | 45983.07 | 07-JUN-08:61 | 32895.21 | 26-JUN-08:06 | 13549.88 | 12-JUN-08:61 | 0.00 | 01-JUN-00:10 |
July | 0.424957E+11 | 0.106890E+11 | 358.20 | 0.247757E+11 | 0.177200E+11 | 0.00 | 1.00 | 01-JUL-08:61 | 0.00 | 01-JUL-00:03 | 56576.37 | 28-JUL-08:61 | 39788.94 | 07-JUL-07:01 | 32546.27 | 23-JUL-09:05 | 13474.92 | 01-JUL-15:00 | 0.00 | 01-JUL-00:03 |
August | 0.432967E+11 | 0.104980E+11 | 367.37 | 0.235252E+11 | 0.197715E+11 | 0.00 | 1.00 | 01-AUG-08:61 | 0.00 | 01-AUG-00:10 | 56765.28 | 21-AUG-08:61 | 35701.33 | 08-AUG-07:01 | 35320.18 | 21-AUG-08:06 | 12836.71 | 27-AUG-14:10 | 0.00 | 01-AUG-00:10 |
September | 0.344025E+11 | 0.840152E+10 | 336.47 | 0.203151E+11 | 0.140873E+11 | 0.00 | 1.00 | 01-SEP-08:61 | 0.00 | 01-SEP-00:10 | 56822.70 | 04-SEP-09:01 | 38091.68 | 26-SEP-08:61 | 34794.15 | 11-SEP-08:04 | 12513.53 | 24-SEP-09:13 | 0.00 | 01-SEP-00:10 |
October | 0.218775E+11 | 0.572004E+10 | 329.93 | 0.175353E+11 | 0.434214E+10 | 0.00 | 1.00 | 01-OCT-09:01 | 0.00 | 01-OCT-00:03 | 54112.97 | 12-OCT-08:62 | 43590.54 | 15-OCT-09:01 | 24474.39 | 13-OCT-08:62 | 12099.47 | 04-OCT-08:61 | 0.00 | 01-OCT-00:03 |
November | 0.114612E+11 | 0.306245E+10 | 312.17 | 0.100771E+11 | 0.138408E+10 | 0.00 | 0.83 | 09-NOV-13:30 | 0.00 | 01-NOV-00:10 | 41737.23 | 11-NOV-10:02 | 33237.36 | 11-NOV-10:02 | 10207.51 | 09-NOV-09:02 | 9266.45 | 11-NOV-10:02 | 0.00 | 01-NOV-00:10 |
December | 0.264032E+10 | 0.723661E+09 | 201.00 | 0.234492E+10 | 0.295401E+09 | 0.00 | 0.47 | 28-DEC-14:00 | 0.00 | 01-DEC-00:10 | 9630.69 | 28-DEC-14:00 | 9208.24 | 02-DEC-14:10 | 1444.81 | 16-DEC-14:30 | 2600.29 | 28-DEC-14:00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.269116E+12 | 0.707409E+11 | 3605.71 | 0.190028E+12 | 0.790879E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.931405E+09 | 0.257953E+09 | 102.33 | 0.841062E+09 | 90342909.37 | 0.00 | 0.37 | 0.00 | 7207.16 | 6781.18 | 1263.45 | 1970.54 | 0.00 | |||||||
Maximum of Months | 0.432967E+11 | 0.106890E+11 | 367.37 | 0.271900E+11 | 0.197715E+11 | 0.00 | 1.00 | 0.00 | 56822.70 | 48073.93 | 35320.18 | 13549.88 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.443073E+09 | 0.120752E+09 | 97.50 | 0.400672E+09 | 42401457.15 | 0.00 | 0.36 | 12-JAN-15:10 | 0.00 | 01-JAN-00:10 | 3694.92 | 12-JAN-15:10 | 3492.50 | 12-JAN-15:10 | 628.88 | 14-JAN-15:00 | 994.87 | 12-JAN-15:10 | 0.00 | 01-JAN-00:10 |
February | 0.248132E+10 | 0.664698E+09 | 223.92 | 0.220795E+10 | 0.273375E+09 | 0.00 | 0.63 | 22-FEB-14:00 | 0.00 | 01-FEB-00:05 | 6993.77 | 24-FEB-15:20 | 6443.18 | 22-FEB-14:00 | 1601.88 | 25-FEB-16:00 | 1847.02 | 22-FEB-14:00 | 0.00 | 01-FEB-00:05 |
March | 0.697175E+10 | 0.186261E+10 | 326.60 | 0.614828E+10 | 0.823467E+09 | 0.00 | 1.00 | 11-MAR-09:02 | 0.00 | 01-MAR-00:05 | 26926.79 | 11-MAR-09:02 | 21069.61 | 11-MAR-09:02 | 5857.18 | 11-MAR-09:02 | 6050.75 | 11-MAR-09:02 | 0.00 | 01-MAR-00:05 |
April | 0.114641E+11 | 0.321286E+10 | 324.35 | 0.104785E+11 | 0.985652E+09 | 0.00 | 1.00 | 01-APR-08:62 | 0.00 | 01-APR-00:05 | 27477.53 | 26-APR-08:61 | 25221.22 | 20-APR-08:61 | 7954.61 | 26-APR-08:04 | 6660.12 | 16-APR-09:01 | 0.00 | 01-APR-00:05 |
May | 0.174494E+11 | 0.493939E+10 | 362.29 | 0.141727E+11 | 0.327668E+10 | 0.00 | 1.00 | 01-MAY-08:61 | 0.00 | 01-MAY-00:10 | 29015.83 | 24-MAY-08:61 | 25291.15 | 29-MAY-08:61 | 13599.87 | 24-MAY-08:04 | 6933.19 | 04-MAY-08:61 | 0.00 | 01-MAY-00:10 |
June | 0.198251E+11 | 0.538279E+10 | 357.09 | 0.141470E+11 | 0.567808E+10 | 0.00 | 1.00 | 01-JUN-08:61 | 0.00 | 01-JUN-00:10 | 29734.69 | 25-JUN-09:01 | 24253.49 | 07-JUN-08:61 | 17285.98 | 26-JUN-08:06 | 7002.46 | 12-JUN-08:61 | 0.00 | 01-JUN-00:10 |
July | 0.220831E+11 | 0.546897E+10 | 357.55 | 0.129057E+11 | 0.917742E+10 | 0.00 | 1.00 | 01-JUL-08:61 | 0.00 | 01-JUL-00:03 | 29776.38 | 28-JUL-08:61 | 19827.35 | 07-JUL-08:61 | 17133.93 | 23-JUL-09:05 | 6957.37 | 01-JUL-15:00 | 0.00 | 01-JUL-00:03 |
August | 0.224771E+11 | 0.536497E+10 | 366.37 | 0.122414E+11 | 0.102357E+11 | 0.00 | 1.00 | 01-AUG-08:61 | 0.00 | 01-AUG-00:10 | 29863.85 | 21-AUG-08:61 | 17715.68 | 08-AUG-08:61 | 18786.23 | 28-AUG-07:02 | 6640.88 | 27-AUG-14:10 | 0.00 | 01-AUG-00:10 |
September | 0.178757E+11 | 0.429867E+10 | 334.75 | 0.105827E+11 | 0.729304E+10 | 0.00 | 1.00 | 01-SEP-08:61 | 0.00 | 01-SEP-00:10 | 29894.06 | 04-SEP-09:01 | 20147.54 | 26-SEP-08:61 | 18370.36 | 11-SEP-08:04 | 6467.94 | 24-SEP-09:13 | 0.00 | 01-SEP-00:10 |
October | 0.113678E+11 | 0.292688E+10 | 329.57 | 0.913702E+10 | 0.223081E+10 | 0.00 | 1.00 | 01-OCT-09:01 | 0.00 | 01-OCT-00:03 | 28466.24 | 12-OCT-08:62 | 23012.50 | 15-OCT-09:01 | 12745.75 | 13-OCT-08:62 | 6253.93 | 04-OCT-08:61 | 0.00 | 01-OCT-00:03 |
November | 0.594249E+10 | 0.156303E+10 | 312.00 | 0.524292E+10 | 0.699564E+09 | 0.00 | 0.83 | 09-NOV-13:30 | 0.00 | 01-NOV-00:10 | 20313.50 | 11-NOV-10:02 | 16212.90 | 11-NOV-10:02 | 4970.38 | 09-NOV-09:02 | 4431.78 | 11-NOV-10:02 | 0.00 | 01-NOV-00:10 |
December | 0.132881E+10 | 0.358390E+09 | 198.50 | 0.118560E+10 | 0.143211E+09 | 0.00 | 0.46 | 28-DEC-14:00 | 0.00 | 01-DEC-00:10 | 4968.13 | 28-DEC-14:00 | 4780.29 | 02-DEC-14:10 | 727.45 | 16-DEC-14:40 | 1320.91 | 28-DEC-14:00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.139710E+12 | 0.361640E+11 | 3590.48 | 0.988504E+11 | 0.408594E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.443073E+09 | 0.120752E+09 | 97.50 | 0.400672E+09 | 42401457.15 | 0.00 | 0.36 | 0.00 | 3694.92 | 3492.50 | 628.88 | 994.87 | 0.00 | |||||||
Maximum of Months | 0.224771E+11 | 0.546897E+10 | 366.37 | 0.141727E+11 | 0.102357E+11 | 0.00 | 1.00 | 0.00 | 29894.06 | 25291.15 | 18786.23 | 7002.46 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.411191E+09 | 0.112176E+09 | 91.50 | 0.371258E+09 | 39932443.47 | 0.00 | 0.35 | 12-JAN-15:10 | 0.00 | 01-JAN-00:10 | 3612.19 | 12-JAN-15:10 | 3413.14 | 12-JAN-15:10 | 615.94 | 14-JAN-15:00 | 974.24 | 12-JAN-15:10 | 0.00 | 01-JAN-00:10 |
February | 0.241467E+10 | 0.647646E+09 | 222.42 | 0.214900E+10 | 0.265672E+09 | 0.00 | 0.62 | 22-FEB-14:00 | 0.00 | 01-FEB-00:05 | 6927.87 | 24-FEB-15:20 | 6375.93 | 22-FEB-14:00 | 1578.91 | 25-FEB-16:00 | 1830.12 | 22-FEB-14:00 | 0.00 | 01-FEB-00:05 |
March | 0.688928E+10 | 0.184222E+10 | 325.82 | 0.607406E+10 | 0.815225E+09 | 0.00 | 1.00 | 11-MAR-09:02 | 0.00 | 01-MAR-00:05 | 26826.43 | 11-MAR-09:02 | 20956.28 | 11-MAR-09:02 | 5870.15 | 11-MAR-09:02 | 6028.55 | 11-MAR-09:02 | 0.00 | 01-MAR-00:05 |
April | 0.113901E+11 | 0.319321E+10 | 324.06 | 0.104093E+11 | 0.980815E+09 | 0.00 | 1.00 | 01-APR-08:62 | 0.00 | 01-APR-00:05 | 27376.18 | 26-APR-08:61 | 25117.88 | 20-APR-08:61 | 7737.31 | 24-APR-08:62 | 6636.30 | 16-APR-09:01 | 0.00 | 01-APR-00:05 |
May | 0.173712E+11 | 0.491711E+10 | 361.91 | 0.141043E+11 | 0.326683E+10 | 0.00 | 1.00 | 01-MAY-08:61 | 0.00 | 01-MAY-00:10 | 28909.65 | 24-MAY-08:61 | 25195.00 | 29-MAY-08:61 | 13578.30 | 24-MAY-08:04 | 6908.41 | 04-MAY-08:61 | 0.00 | 01-MAY-00:10 |
June | 0.197438E+11 | 0.535999E+10 | 357.13 | 0.140800E+11 | 0.566378E+10 | 0.00 | 1.00 | 01-JUN-08:61 | 0.00 | 01-JUN-00:10 | 29627.19 | 25-JUN-09:01 | 24162.81 | 07-JUN-08:61 | 17255.60 | 26-JUN-08:06 | 6977.35 | 12-JUN-08:61 | 0.00 | 01-JUN-00:10 |
July | 0.220049E+11 | 0.544835E+10 | 357.69 | 0.128462E+11 | 0.915867E+10 | 0.00 | 1.00 | 01-JUL-08:61 | 0.00 | 01-JUL-00:03 | 29681.12 | 28-JUL-08:61 | 19742.31 | 07-JUL-08:61 | 17093.44 | 23-JUL-09:05 | 6935.81 | 01-JUL-15:00 | 0.00 | 01-JUL-00:03 |
August | 0.223983E+11 | 0.534475E+10 | 366.49 | 0.121826E+11 | 0.102157E+11 | 0.00 | 1.00 | 01-AUG-08:61 | 0.00 | 01-AUG-00:10 | 29755.90 | 21-AUG-08:61 | 17633.88 | 08-AUG-08:61 | 18739.79 | 28-AUG-07:02 | 6624.20 | 27-AUG-14:10 | 0.00 | 01-AUG-00:10 |
September | 0.178050E+11 | 0.428086E+10 | 334.52 | 0.105290E+11 | 0.727602E+10 | 0.00 | 1.00 | 01-SEP-08:61 | 0.00 | 01-SEP-00:10 | 29785.99 | 04-SEP-09:01 | 20057.89 | 26-SEP-08:61 | 18331.54 | 11-SEP-08:04 | 6444.45 | 24-SEP-09:13 | 0.00 | 01-SEP-00:10 |
October | 0.113021E+11 | 0.291078E+10 | 329.77 | 0.908048E+10 | 0.222161E+10 | 0.00 | 1.00 | 01-OCT-09:01 | 0.00 | 01-OCT-00:03 | 28363.76 | 12-OCT-08:62 | 22908.34 | 15-OCT-09:01 | 12737.09 | 13-OCT-08:62 | 6231.54 | 04-OCT-08:61 | 0.00 | 01-OCT-00:03 |
November | 0.587816E+10 | 0.154718E+10 | 311.50 | 0.518497E+10 | 0.693194E+09 | 0.00 | 0.83 | 09-NOV-13:40 | 0.00 | 01-NOV-00:10 | 19795.15 | 11-NOV-10:02 | 15764.78 | 11-NOV-10:02 | 4853.55 | 09-NOV-09:02 | 4319.10 | 11-NOV-10:02 | 0.00 | 01-NOV-00:10 |
December | 0.127580E+10 | 0.344390E+09 | 194.00 | 0.113893E+10 | 0.136870E+09 | 0.00 | 0.46 | 28-DEC-14:00 | 0.00 | 01-DEC-00:10 | 4895.90 | 28-DEC-14:00 | 4725.42 | 02-DEC-14:10 | 716.36 | 16-DEC-14:40 | 1303.35 | 28-DEC-14:00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.138884E+12 | 0.359487E+11 | 3576.80 | 0.981501E+11 | 0.407343E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.411191E+09 | 0.112176E+09 | 91.50 | 0.371258E+09 | 39932443.47 | 0.00 | 0.35 | 0.00 | 3612.19 | 3413.14 | 615.94 | 974.24 | 0.00 | |||||||
Maximum of Months | 0.223983E+11 | 0.544835E+10 | 366.49 | 0.141043E+11 | 0.102157E+11 | 0.00 | 1.00 | 0.00 | 29785.99 | 25195.00 | 18739.79 | 6977.35 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.356615E+09 | 97527115.77 | 83.50 | 0.321259E+09 | 35355631.74 | 0.00 | 0.34 | 12-JAN-15:10 | 0.00 | 01-JAN-00:10 | 3453.01 | 12-JAN-15:10 | 3261.53 | 12-JAN-15:10 | 588.23 | 14-JAN-15:10 | 934.98 | 12-JAN-15:10 | 0.00 | 01-JAN-00:10 |
February | 0.227077E+10 | 0.611105E+09 | 216.08 | 0.202248E+10 | 0.248291E+09 | 0.00 | 0.61 | 22-FEB-14:00 | 0.00 | 01-FEB-00:05 | 6808.25 | 24-FEB-15:20 | 6251.12 | 22-FEB-15:10 | 1528.21 | 25-FEB-16:00 | 1800.29 | 22-FEB-14:00 | 0.00 | 01-FEB-00:05 |
March | 0.671901E+10 | 0.180181E+10 | 324.31 | 0.592256E+10 | 0.796443E+09 | 0.00 | 1.00 | 11-MAR-09:02 | 0.00 | 01-MAR-00:05 | 26831.76 | 11-MAR-09:02 | 20882.49 | 11-MAR-09:02 | 5949.26 | 11-MAR-09:02 | 6030.97 | 11-MAR-09:02 | 0.00 | 01-MAR-00:05 |
April | 0.113007E+11 | 0.317205E+10 | 323.46 | 0.103265E+11 | 0.974197E+09 | 0.00 | 1.00 | 01-APR-08:62 | 0.00 | 01-APR-00:05 | 27381.73 | 26-APR-08:61 | 25104.70 | 08-APR-08:62 | 7812.37 | 24-APR-08:62 | 6640.45 | 16-APR-09:01 | 0.00 | 01-APR-00:05 |
May | 0.173354E+11 | 0.490873E+10 | 361.31 | 0.140759E+11 | 0.325950E+10 | 0.00 | 1.00 | 01-MAY-08:61 | 0.00 | 01-MAY-00:10 | 28919.76 | 24-MAY-08:61 | 25164.15 | 29-MAY-08:61 | 13624.77 | 24-MAY-08:04 | 6912.48 | 04-MAY-08:61 | 0.00 | 01-MAY-00:10 |
June | 0.197397E+11 | 0.536002E+10 | 356.30 | 0.140800E+11 | 0.565963E+10 | 0.00 | 1.00 | 01-JUN-08:61 | 0.00 | 01-JUN-00:10 | 29644.48 | 25-JUN-09:01 | 24177.41 | 07-JUN-08:61 | 17327.10 | 26-JUN-08:06 | 6987.42 | 10-JUN-16:00 | 0.00 | 01-JUN-00:10 |
July | 0.220445E+11 | 0.545929E+10 | 357.29 | 0.128785E+11 | 0.916602E+10 | 0.00 | 1.00 | 01-JUL-08:61 | 0.00 | 01-JUL-00:03 | 29704.91 | 28-JUL-08:61 | 19764.85 | 07-JUL-08:61 | 17126.31 | 23-JUL-09:05 | 6947.44 | 01-JUL-15:00 | 0.00 | 01-JUL-00:03 |
August | 0.224492E+11 | 0.535743E+10 | 365.77 | 0.122216E+11 | 0.102276E+11 | 0.00 | 1.00 | 01-AUG-08:61 | 0.00 | 01-AUG-00:10 | 29773.26 | 21-AUG-08:61 | 17666.69 | 08-AUG-08:61 | 18726.14 | 28-AUG-07:02 | 6641.21 | 27-AUG-14:10 | 0.00 | 01-AUG-00:10 |
September | 0.178321E+11 | 0.428778E+10 | 333.96 | 0.105511E+11 | 0.728095E+10 | 0.00 | 1.00 | 01-SEP-08:61 | 0.00 | 01-SEP-00:10 | 29803.37 | 04-SEP-09:01 | 20074.34 | 26-SEP-08:61 | 18365.36 | 11-SEP-08:04 | 6448.26 | 24-SEP-09:13 | 0.00 | 01-SEP-00:10 |
October | 0.112806E+11 | 0.290630E+10 | 329.61 | 0.906333E+10 | 0.221728E+10 | 0.00 | 1.00 | 01-OCT-09:01 | 0.00 | 01-OCT-00:03 | 28376.57 | 12-OCT-08:62 | 22890.77 | 15-OCT-09:01 | 12780.32 | 13-OCT-08:62 | 6235.17 | 04-OCT-08:61 | 0.00 | 01-OCT-00:03 |
November | 0.578542E+10 | 0.152513E+10 | 310.33 | 0.510267E+10 | 0.682759E+09 | 0.00 | 0.82 | 09-NOV-13:30 | 0.00 | 01-NOV-00:10 | 18628.14 | 11-NOV-10:02 | 14771.01 | 11-NOV-10:02 | 4566.81 | 09-NOV-09:02 | 4065.60 | 11-NOV-10:02 | 0.00 | 01-NOV-00:10 |
December | 0.117097E+10 | 0.316758E+09 | 181.83 | 0.104711E+10 | 0.123860E+09 | 0.00 | 0.45 | 28-DEC-14:00 | 0.00 | 01-DEC-00:10 | 4770.46 | 28-DEC-14:00 | 4618.62 | 02-DEC-14:10 | 694.27 | 16-DEC-14:40 | 1273.78 | 28-DEC-14:00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.138285E+12 | 0.358039E+11 | 3543.75 | 0.976130E+11 | 0.406719E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.356615E+09 | 97527115.77 | 83.50 | 0.321259E+09 | 35355631.74 | 0.00 | 0.34 | 0.00 | 3453.01 | 3261.53 | 588.23 | 934.98 | 0.00 | |||||||
Maximum of Months | 0.224492E+11 | 0.545929E+10 | 365.77 | 0.140800E+11 | 0.102276E+11 | 0.00 | 1.00 | 0.00 | 29803.37 | 25164.15 | 18726.14 | 6987.42 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.357385E+09 | 97956359.76 | 81.50 | 0.324209E+09 | 33175139.82 | 0.00 | 0.32 | 12-JAN-15:10 | 0.00 | 01-JAN-00:10 | 3502.36 | 12-JAN-15:10 | 3326.38 | 12-JAN-15:10 | 571.64 | 14-JAN-15:00 | 952.22 | 12-JAN-15:10 | 0.00 | 01-JAN-00:10 |
February | 0.222788E+10 | 0.602581E+09 | 210.17 | 0.199783E+10 | 0.230056E+09 | 0.00 | 0.60 | 22-FEB-14:00 | 0.00 | 01-FEB-00:05 | 7010.18 | 22-FEB-14:00 | 6500.04 | 22-FEB-14:00 | 1461.54 | 25-FEB-16:00 | 1871.99 | 22-FEB-14:00 | 0.00 | 01-FEB-00:05 |
March | 0.675765E+10 | 0.182510E+10 | 319.31 | 0.598226E+10 | 0.775395E+09 | 0.00 | 1.00 | 11-MAR-09:02 | 0.00 | 01-MAR-00:05 | 28598.31 | 11-MAR-09:02 | 22211.57 | 11-MAR-09:02 | 6386.74 | 11-MAR-09:02 | 6427.16 | 11-MAR-09:02 | 0.00 | 01-MAR-00:05 |
April | 0.118232E+11 | 0.333069E+10 | 323.26 | 0.108289E+11 | 0.994310E+09 | 0.00 | 1.00 | 02-APR-09:01 | 0.00 | 01-APR-00:05 | 29172.16 | 17-APR-08:61 | 26747.04 | 30-APR-09:01 | 8359.99 | 24-APR-08:62 | 7074.27 | 16-APR-09:01 | 0.00 | 01-APR-00:05 |
May | 0.183631E+11 | 0.521516E+10 | 361.81 | 0.149907E+11 | 0.337247E+10 | 0.00 | 1.00 | 01-MAY-08:61 | 0.00 | 01-MAY-00:10 | 31158.98 | 24-MAY-08:61 | 27146.06 | 29-MAY-08:61 | 15738.43 | 24-MAY-08:04 | 7364.70 | 04-MAY-08:61 | 0.00 | 01-MAY-00:10 |
June | 0.209753E+11 | 0.572219E+10 | 357.11 | 0.151187E+11 | 0.585655E+10 | 0.00 | 1.00 | 01-JUN-08:61 | 0.00 | 01-JUN-00:10 | 31761.53 | 24-JUN-08:61 | 26023.40 | 12-JUN-07:01 | 18686.50 | 26-JUN-08:06 | 7433.73 | 12-JUN-08:61 | 0.00 | 01-JUN-00:10 |
July | 0.236369E+11 | 0.588202E+10 | 358.62 | 0.140512E+11 | 0.958567E+10 | 0.00 | 1.00 | 01-JUL-08:61 | 0.00 | 01-JUL-00:03 | 31729.96 | 26-JUL-08:61 | 22355.47 | 07-JUL-07:01 | 18281.58 | 23-JUL-09:05 | 7426.30 | 10-JUL-13:00 | 0.00 | 01-JUL-00:03 |
August | 0.241653E+11 | 0.579611E+10 | 368.64 | 0.134713E+11 | 0.106939E+11 | 0.00 | 1.00 | 01-AUG-08:61 | 0.00 | 01-AUG-00:10 | 31725.21 | 21-AUG-08:61 | 19664.05 | 09-AUG-07:01 | 19624.26 | 28-AUG-07:02 | 7100.41 | 27-AUG-14:10 | 0.00 | 01-AUG-00:10 |
September | 0.192076E+11 | 0.463698E+10 | 339.48 | 0.116067E+11 | 0.760094E+10 | 0.00 | 1.00 | 01-SEP-08:61 | 0.00 | 01-SEP-00:10 | 31781.67 | 09-SEP-08:61 | 21511.89 | 26-SEP-08:61 | 19389.47 | 10-SEP-09:05 | 6872.19 | 24-SEP-09:13 | 0.00 | 01-SEP-00:10 |
October | 0.122161E+11 | 0.314353E+10 | 330.08 | 0.990189E+10 | 0.231422E+10 | 0.00 | 1.00 | 01-OCT-09:01 | 0.00 | 01-OCT-00:03 | 30379.46 | 12-OCT-08:62 | 24641.32 | 15-OCT-09:01 | 13916.60 | 12-OCT-08:62 | 6642.44 | 04-OCT-08:61 | 0.00 | 01-OCT-00:03 |
November | 0.615920E+10 | 0.162359E+10 | 308.64 | 0.546413E+10 | 0.695068E+09 | 0.00 | 0.83 | 09-NOV-13:30 | 0.00 | 01-NOV-00:10 | 19283.46 | 11-NOV-10:02 | 15372.71 | 11-NOV-10:02 | 4411.85 | 09-NOV-09:02 | 4208.35 | 11-NOV-10:02 | 0.00 | 01-NOV-00:10 |
December | 0.121443E+10 | 0.328744E+09 | 179.17 | 0.109425E+10 | 0.120181E+09 | 0.00 | 0.44 | 28-DEC-14:00 | 0.00 | 01-DEC-00:10 | 4967.38 | 28-DEC-14:00 | 4793.96 | 02-DEC-14:10 | 707.48 | 16-DEC-14:30 | 1329.77 | 28-DEC-14:00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.147104E+12 | 0.382046E+11 | 3537.79 | 0.104832E+12 | 0.422720E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.357385E+09 | 97956359.76 | 81.50 | 0.324209E+09 | 33175139.82 | 0.00 | 0.32 | 0.00 | 3502.36 | 3326.38 | 571.64 | 952.22 | 0.00 | |||||||
Maximum of Months | 0.241653E+11 | 0.588202E+10 | 368.64 | 0.151187E+11 | 0.106939E+11 | 0.00 | 1.00 | 0.00 | 31781.67 | 27146.06 | 19624.26 | 7433.73 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.96 | 46.77 | 30.19 | 103.79 | 59.22 | 0.00 | 0.00 | 744.00 |
February | 73.17 | 40.64 | 32.53 | 104.10 | 47.10 | 0.00 | 0.00 | 672.00 |
March | 62.54 | 27.62 | 34.93 | 96.95 | 27.82 | 0.00 | 0.00 | 744.00 |
April | 43.92 | 12.38 | 31.54 | 84.65 | 9.32 | 0.00 | 0.00 | 720.00 |
May | 31.58 | 2.32 | 29.26 | 84.73 | 1.52 | 0.00 | 0.00 | 744.00 |
June | 28.89 | 0.48 | 28.41 | 86.62 | 1.18 | 0.00 | 0.00 | 720.00 |
July | 30.14 | 0.41 | 29.74 | 81.21 | 0.40 | 0.00 | 0.00 | 744.00 |
August | 31.98 | 1.70 | 30.27 | 74.20 | 1.21 | 0.00 | 0.00 | 744.00 |
September | 42.87 | 11.12 | 31.75 | 82.44 | 4.60 | 0.00 | 0.00 | 720.00 |
October | 73.76 | 41.19 | 32.57 | 127.20 | 22.12 | 0.00 | 0.00 | 744.00 |
November | 92.16 | 60.92 | 31.23 | 145.13 | 42.42 | 0.00 | 0.00 | 720.00 |
December | 82.25 | 51.55 | 30.70 | 115.37 | 58.62 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 55.75 | 24.67 | 31.09 | 98.81 | 22.86 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 28.89 | 0.41 | 28.41 | 74.20 | 0.40 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 92.16 | 60.92 | 34.93 | 145.13 | 59.22 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.96 | 46.77 | 30.19 | 103.79 | 59.22 | 0.00 | 0.00 | 744.00 |
February | 73.17 | 40.64 | 32.53 | 104.10 | 47.10 | 0.00 | 0.00 | 672.00 |
March | 62.54 | 27.62 | 34.93 | 96.95 | 27.82 | 0.00 | 0.00 | 744.00 |
April | 43.92 | 12.38 | 31.54 | 84.65 | 9.32 | 0.00 | 0.00 | 720.00 |
May | 31.58 | 2.32 | 29.26 | 84.73 | 1.52 | 0.00 | 0.00 | 744.00 |
June | 28.89 | 0.48 | 28.41 | 86.62 | 1.18 | 0.00 | 0.00 | 720.00 |
July | 30.14 | 0.41 | 29.74 | 81.21 | 0.40 | 0.00 | 0.00 | 744.00 |
August | 31.98 | 1.70 | 30.27 | 74.20 | 1.21 | 0.00 | 0.00 | 744.00 |
September | 42.87 | 11.12 | 31.75 | 82.44 | 4.60 | 0.00 | 0.00 | 720.00 |
October | 73.76 | 41.19 | 32.57 | 127.20 | 22.12 | 0.00 | 0.00 | 744.00 |
November | 92.16 | 60.92 | 31.23 | 145.13 | 42.42 | 0.00 | 0.00 | 720.00 |
December | 82.25 | 51.55 | 30.70 | 115.37 | 58.62 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 55.75 | 24.67 | 31.09 | 98.81 | 22.86 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 28.89 | 0.41 | 28.41 | 74.20 | 0.40 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 92.16 | 60.92 | 34.93 | 145.13 | 59.22 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_3
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.96 | 46.77 | 30.19 | 103.79 | 59.22 | 0.00 | 0.00 | 744.00 |
February | 73.17 | 40.64 | 32.53 | 104.10 | 47.10 | 0.00 | 0.00 | 672.00 |
March | 62.54 | 27.62 | 34.93 | 96.95 | 27.82 | 0.00 | 0.00 | 744.00 |
April | 43.92 | 12.38 | 31.54 | 84.65 | 9.32 | 0.00 | 0.00 | 720.00 |
May | 31.58 | 2.32 | 29.26 | 84.73 | 1.52 | 0.00 | 0.00 | 744.00 |
June | 28.89 | 0.48 | 28.41 | 86.62 | 1.18 | 0.00 | 0.00 | 720.00 |
July | 30.14 | 0.41 | 29.74 | 81.21 | 0.40 | 0.00 | 0.00 | 744.00 |
August | 31.98 | 1.70 | 30.27 | 74.20 | 1.21 | 0.00 | 0.00 | 744.00 |
September | 42.87 | 11.12 | 31.75 | 82.44 | 4.60 | 0.00 | 0.00 | 720.00 |
October | 73.76 | 41.19 | 32.57 | 127.20 | 22.12 | 0.00 | 0.00 | 744.00 |
November | 92.16 | 60.92 | 31.23 | 145.13 | 42.42 | 0.00 | 0.00 | 720.00 |
December | 82.25 | 51.55 | 30.70 | 115.37 | 58.62 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 55.75 | 24.67 | 31.09 | 98.81 | 22.86 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 28.89 | 0.41 | 28.41 | 74.20 | 0.40 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 92.16 | 60.92 | 34.93 | 145.13 | 59.22 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_4
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.96 | 46.77 | 30.19 | 103.79 | 59.22 | 0.00 | 0.00 | 744.00 |
February | 73.17 | 40.64 | 32.53 | 104.10 | 47.10 | 0.00 | 0.00 | 672.00 |
March | 62.54 | 27.62 | 34.93 | 96.95 | 27.82 | 0.00 | 0.00 | 744.00 |
April | 43.92 | 12.38 | 31.54 | 84.65 | 9.32 | 0.00 | 0.00 | 720.00 |
May | 31.58 | 2.32 | 29.26 | 84.73 | 1.52 | 0.00 | 0.00 | 744.00 |
June | 28.89 | 0.48 | 28.41 | 86.62 | 1.18 | 0.00 | 0.00 | 720.00 |
July | 30.14 | 0.41 | 29.74 | 81.21 | 0.40 | 0.00 | 0.00 | 744.00 |
August | 31.98 | 1.70 | 30.27 | 74.20 | 1.21 | 0.00 | 0.00 | 744.00 |
September | 42.87 | 11.12 | 31.75 | 82.44 | 4.60 | 0.00 | 0.00 | 720.00 |
October | 73.76 | 41.19 | 32.57 | 127.20 | 22.12 | 0.00 | 0.00 | 744.00 |
November | 92.16 | 60.92 | 31.23 | 145.13 | 42.42 | 0.00 | 0.00 | 720.00 |
December | 82.25 | 51.55 | 30.70 | 115.37 | 58.62 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 55.75 | 24.67 | 31.09 | 98.81 | 22.86 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 28.89 | 0.41 | 28.41 | 74.20 | 0.40 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 92.16 | 60.92 | 34.93 | 145.13 | 59.22 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_DOOR_1
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 92.66 | 56.31 | 36.35 | 124.77 | 70.80 | 0.00 | 0.00 | 744.00 |
February | 88.09 | 48.93 | 39.16 | 125.10 | 56.33 | 0.00 | 0.00 | 672.00 |
March | 75.30 | 33.25 | 42.05 | 116.36 | 33.32 | 0.00 | 0.00 | 744.00 |
April | 52.88 | 14.91 | 37.97 | 101.34 | 11.17 | 0.00 | 0.00 | 720.00 |
May | 38.02 | 2.79 | 35.23 | 101.15 | 1.84 | 0.00 | 0.00 | 744.00 |
June | 34.79 | 0.58 | 34.21 | 103.42 | 1.42 | 0.00 | 0.00 | 720.00 |
July | 36.29 | 0.49 | 35.80 | 96.98 | 0.48 | 0.00 | 0.00 | 744.00 |
August | 38.50 | 2.05 | 36.45 | 88.71 | 1.46 | 0.00 | 0.00 | 744.00 |
September | 51.61 | 13.39 | 38.22 | 98.70 | 5.53 | 0.00 | 0.00 | 720.00 |
October | 88.80 | 49.59 | 39.22 | 152.57 | 26.53 | 0.00 | 0.00 | 744.00 |
November | 110.95 | 73.35 | 37.61 | 174.26 | 50.79 | 0.00 | 0.00 | 720.00 |
December | 99.02 | 62.06 | 36.96 | 138.65 | 70.10 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 67.12 | 29.70 | 37.42 | 118.44 | 27.36 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 34.79 | 0.49 | 34.21 | 88.71 | 0.48 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 110.95 | 73.35 | 42.05 | 174.26 | 70.80 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_DOOR_2
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 92.66 | 56.31 | 36.35 | 124.77 | 70.80 | 0.00 | 0.00 | 744.00 |
February | 88.09 | 48.93 | 39.16 | 125.10 | 56.33 | 0.00 | 0.00 | 672.00 |
March | 75.30 | 33.25 | 42.05 | 116.36 | 33.32 | 0.00 | 0.00 | 744.00 |
April | 52.88 | 14.91 | 37.97 | 101.34 | 11.17 | 0.00 | 0.00 | 720.00 |
May | 38.02 | 2.79 | 35.23 | 101.15 | 1.84 | 0.00 | 0.00 | 744.00 |
June | 34.79 | 0.58 | 34.21 | 103.42 | 1.42 | 0.00 | 0.00 | 720.00 |
July | 36.29 | 0.49 | 35.80 | 96.98 | 0.48 | 0.00 | 0.00 | 744.00 |
August | 38.50 | 2.05 | 36.45 | 88.71 | 1.46 | 0.00 | 0.00 | 744.00 |
September | 51.61 | 13.39 | 38.22 | 98.70 | 5.53 | 0.00 | 0.00 | 720.00 |
October | 88.80 | 49.59 | 39.22 | 152.57 | 26.53 | 0.00 | 0.00 | 744.00 |
November | 110.95 | 73.35 | 37.61 | 174.26 | 50.79 | 0.00 | 0.00 | 720.00 |
December | 99.02 | 62.06 | 36.96 | 138.65 | 70.10 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 67.12 | 29.70 | 37.42 | 118.44 | 27.36 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 34.79 | 0.49 | 34.21 | 88.71 | 0.48 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 110.95 | 73.35 | 42.05 | 174.26 | 70.80 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.96 | 46.77 | 30.19 | 102.99 | 60.84 | 0.00 | 0.00 | 744.00 |
February | 73.17 | 40.64 | 32.53 | 103.51 | 48.06 | 0.00 | 0.00 | 672.00 |
March | 62.54 | 27.62 | 34.93 | 96.69 | 28.30 | 0.00 | 0.00 | 744.00 |
April | 43.92 | 12.38 | 31.54 | 84.86 | 9.51 | 0.00 | 0.00 | 720.00 |
May | 31.58 | 2.32 | 29.26 | 85.36 | 1.54 | 0.00 | 0.00 | 744.00 |
June | 28.89 | 0.48 | 28.41 | 87.50 | 1.18 | 0.00 | 0.00 | 720.00 |
July | 30.14 | 0.41 | 29.74 | 82.17 | 0.37 | 0.00 | 0.00 | 744.00 |
August | 31.98 | 1.70 | 30.27 | 75.06 | 1.10 | 0.00 | 0.00 | 744.00 |
September | 42.87 | 11.12 | 31.75 | 83.01 | 4.35 | 0.00 | 0.00 | 720.00 |
October | 73.76 | 41.19 | 32.57 | 127.40 | 21.97 | 0.00 | 0.00 | 744.00 |
November | 92.16 | 60.92 | 31.23 | 144.98 | 42.53 | 0.00 | 0.00 | 720.00 |
December | 82.25 | 51.55 | 30.70 | 114.84 | 59.50 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 55.75 | 24.67 | 31.09 | 98.98 | 23.16 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 28.89 | 0.41 | 28.41 | 75.06 | 0.37 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 92.16 | 60.92 | 34.93 | 144.98 | 60.84 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.96 | 46.77 | 30.19 | 102.99 | 60.84 | 0.00 | 0.00 | 744.00 |
February | 73.17 | 40.64 | 32.53 | 103.51 | 48.06 | 0.00 | 0.00 | 672.00 |
March | 62.54 | 27.62 | 34.93 | 96.69 | 28.30 | 0.00 | 0.00 | 744.00 |
April | 43.92 | 12.38 | 31.54 | 84.86 | 9.51 | 0.00 | 0.00 | 720.00 |
May | 31.58 | 2.32 | 29.26 | 85.36 | 1.54 | 0.00 | 0.00 | 744.00 |
June | 28.89 | 0.48 | 28.41 | 87.50 | 1.18 | 0.00 | 0.00 | 720.00 |
July | 30.14 | 0.41 | 29.74 | 82.17 | 0.37 | 0.00 | 0.00 | 744.00 |
August | 31.98 | 1.70 | 30.27 | 75.06 | 1.10 | 0.00 | 0.00 | 744.00 |
September | 42.87 | 11.12 | 31.75 | 83.01 | 4.35 | 0.00 | 0.00 | 720.00 |
October | 73.76 | 41.19 | 32.57 | 127.40 | 21.97 | 0.00 | 0.00 | 744.00 |
November | 92.16 | 60.92 | 31.23 | 144.98 | 42.53 | 0.00 | 0.00 | 720.00 |
December | 82.25 | 51.55 | 30.70 | 114.84 | 59.50 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 55.75 | 24.67 | 31.09 | 98.98 | 23.16 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 28.89 | 0.41 | 28.41 | 75.06 | 0.37 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 92.16 | 60.92 | 34.93 | 144.98 | 60.84 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_DOOR
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 92.66 | 56.31 | 36.35 | 123.82 | 72.71 | 0.00 | 0.00 | 744.00 |
February | 88.09 | 48.93 | 39.16 | 124.40 | 57.46 | 0.00 | 0.00 | 672.00 |
March | 75.30 | 33.25 | 42.05 | 116.06 | 33.89 | 0.00 | 0.00 | 744.00 |
April | 52.88 | 14.91 | 37.97 | 101.58 | 11.40 | 0.00 | 0.00 | 720.00 |
May | 38.02 | 2.79 | 35.23 | 101.90 | 1.86 | 0.00 | 0.00 | 744.00 |
June | 34.79 | 0.58 | 34.21 | 104.47 | 1.42 | 0.00 | 0.00 | 720.00 |
July | 36.29 | 0.49 | 35.80 | 98.14 | 0.44 | 0.00 | 0.00 | 744.00 |
August | 38.50 | 2.05 | 36.45 | 89.75 | 1.33 | 0.00 | 0.00 | 744.00 |
September | 51.61 | 13.39 | 38.22 | 99.40 | 5.23 | 0.00 | 0.00 | 720.00 |
October | 88.80 | 49.59 | 39.22 | 152.82 | 26.34 | 0.00 | 0.00 | 744.00 |
November | 110.95 | 73.35 | 37.61 | 174.09 | 50.92 | 0.00 | 0.00 | 720.00 |
December | 99.02 | 62.06 | 36.96 | 138.01 | 71.15 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 67.12 | 29.70 | 37.42 | 118.64 | 27.72 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 34.79 | 0.49 | 34.21 | 89.75 | 0.44 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 110.95 | 73.35 | 42.05 | 174.09 | 72.71 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.96 | 46.77 | 30.19 | 103.66 | 59.46 | 0.00 | 0.00 | 744.00 |
February | 73.17 | 40.64 | 32.53 | 103.77 | 48.19 | 0.00 | 0.00 | 672.00 |
March | 62.54 | 27.62 | 34.93 | 96.55 | 29.60 | 0.00 | 0.00 | 744.00 |
April | 43.92 | 12.38 | 31.54 | 83.11 | 10.90 | 0.00 | 0.00 | 720.00 |
May | 31.58 | 2.32 | 29.26 | 81.80 | 2.16 | 0.00 | 0.00 | 744.00 |
June | 28.89 | 0.48 | 28.41 | 83.79 | 1.74 | 0.00 | 0.00 | 720.00 |
July | 30.14 | 0.41 | 29.74 | 77.96 | 0.59 | 0.00 | 0.00 | 744.00 |
August | 31.98 | 1.70 | 30.27 | 72.27 | 1.82 | 0.00 | 0.00 | 744.00 |
September | 42.87 | 11.12 | 31.75 | 81.36 | 6.06 | 0.00 | 0.00 | 720.00 |
October | 73.76 | 41.19 | 32.57 | 126.97 | 24.25 | 0.00 | 0.00 | 744.00 |
November | 92.16 | 60.92 | 31.23 | 145.07 | 43.71 | 0.00 | 0.00 | 720.00 |
December | 82.25 | 51.55 | 30.70 | 115.27 | 59.16 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 55.75 | 24.67 | 31.09 | 97.57 | 23.86 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 28.89 | 0.41 | 28.41 | 72.27 | 0.59 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 92.16 | 60.92 | 34.93 | 145.07 | 59.46 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.96 | 46.77 | 30.19 | 103.66 | 59.46 | 0.00 | 0.00 | 744.00 |
February | 73.17 | 40.64 | 32.53 | 103.77 | 48.19 | 0.00 | 0.00 | 672.00 |
March | 62.54 | 27.62 | 34.93 | 96.55 | 29.60 | 0.00 | 0.00 | 744.00 |
April | 43.92 | 12.38 | 31.54 | 83.11 | 10.90 | 0.00 | 0.00 | 720.00 |
May | 31.58 | 2.32 | 29.26 | 81.80 | 2.16 | 0.00 | 0.00 | 744.00 |
June | 28.89 | 0.48 | 28.41 | 83.79 | 1.74 | 0.00 | 0.00 | 720.00 |
July | 30.14 | 0.41 | 29.74 | 77.96 | 0.59 | 0.00 | 0.00 | 744.00 |
August | 31.98 | 1.70 | 30.27 | 72.27 | 1.82 | 0.00 | 0.00 | 744.00 |
September | 42.87 | 11.12 | 31.75 | 81.36 | 6.06 | 0.00 | 0.00 | 720.00 |
October | 73.76 | 41.19 | 32.57 | 126.97 | 24.25 | 0.00 | 0.00 | 744.00 |
November | 92.16 | 60.92 | 31.23 | 145.07 | 43.71 | 0.00 | 0.00 | 720.00 |
December | 82.25 | 51.55 | 30.70 | 115.27 | 59.16 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 55.75 | 24.67 | 31.09 | 97.57 | 23.86 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 28.89 | 0.41 | 28.41 | 72.27 | 0.59 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 92.16 | 60.92 | 34.93 | 145.07 | 59.46 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_DOOR
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 92.15 | 56.00 | 36.15 | 123.95 | 70.66 | 0.00 | 0.00 | 744.00 |
February | 87.61 | 48.67 | 38.95 | 124.03 | 57.27 | 0.00 | 0.00 | 672.00 |
March | 74.88 | 33.07 | 41.82 | 115.26 | 35.22 | 0.00 | 0.00 | 744.00 |
April | 52.59 | 14.82 | 37.76 | 98.99 | 12.98 | 0.00 | 0.00 | 720.00 |
May | 37.81 | 2.78 | 35.03 | 97.19 | 2.59 | 0.00 | 0.00 | 744.00 |
June | 34.60 | 0.58 | 34.02 | 99.56 | 2.07 | 0.00 | 0.00 | 720.00 |
July | 36.09 | 0.49 | 35.60 | 92.69 | 0.71 | 0.00 | 0.00 | 744.00 |
August | 38.29 | 2.04 | 36.25 | 86.00 | 2.18 | 0.00 | 0.00 | 744.00 |
September | 51.33 | 13.32 | 38.01 | 96.94 | 7.22 | 0.00 | 0.00 | 720.00 |
October | 88.32 | 49.31 | 39.00 | 151.48 | 28.87 | 0.00 | 0.00 | 744.00 |
November | 110.35 | 72.95 | 37.40 | 173.25 | 52.00 | 0.00 | 0.00 | 720.00 |
December | 98.48 | 61.72 | 36.76 | 137.78 | 70.33 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 66.76 | 29.54 | 37.22 | 116.36 | 28.38 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 34.60 | 0.49 | 34.02 | 86.00 | 0.71 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 110.35 | 72.95 | 41.82 | 173.25 | 70.66 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.96 | 46.77 | 30.19 | 104.03 | 58.48 | 0.00 | 0.00 | 744.00 |
February | 73.17 | 40.64 | 32.53 | 103.92 | 47.75 | 0.00 | 0.00 | 672.00 |
March | 62.54 | 27.62 | 34.93 | 96.57 | 29.53 | 0.00 | 0.00 | 744.00 |
April | 43.92 | 12.38 | 31.54 | 83.01 | 11.07 | 0.00 | 0.00 | 720.00 |
May | 31.58 | 2.32 | 29.26 | 81.45 | 2.32 | 0.00 | 0.00 | 744.00 |
June | 28.89 | 0.48 | 28.41 | 83.37 | 1.85 | 0.00 | 0.00 | 720.00 |
July | 30.14 | 0.41 | 29.74 | 77.49 | 0.65 | 0.00 | 0.00 | 744.00 |
August | 31.98 | 1.70 | 30.27 | 72.00 | 1.94 | 0.00 | 0.00 | 744.00 |
September | 42.87 | 11.12 | 31.75 | 81.26 | 6.33 | 0.00 | 0.00 | 720.00 |
October | 73.76 | 41.19 | 32.57 | 126.93 | 24.44 | 0.00 | 0.00 | 744.00 |
November | 92.16 | 60.92 | 31.23 | 145.12 | 43.58 | 0.00 | 0.00 | 720.00 |
December | 82.25 | 51.55 | 30.70 | 115.48 | 58.62 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 55.75 | 24.67 | 31.09 | 97.49 | 23.77 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 28.89 | 0.41 | 28.41 | 72.00 | 0.65 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 92.16 | 60.92 | 34.93 | 145.12 | 58.62 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.96 | 46.77 | 30.19 | 104.03 | 58.48 | 0.00 | 0.00 | 744.00 |
February | 73.17 | 40.64 | 32.53 | 103.92 | 47.75 | 0.00 | 0.00 | 672.00 |
March | 62.54 | 27.62 | 34.93 | 96.57 | 29.53 | 0.00 | 0.00 | 744.00 |
April | 43.92 | 12.38 | 31.54 | 83.01 | 11.07 | 0.00 | 0.00 | 720.00 |
May | 31.58 | 2.32 | 29.26 | 81.45 | 2.32 | 0.00 | 0.00 | 744.00 |
June | 28.89 | 0.48 | 28.41 | 83.37 | 1.85 | 0.00 | 0.00 | 720.00 |
July | 30.14 | 0.41 | 29.74 | 77.49 | 0.65 | 0.00 | 0.00 | 744.00 |
August | 31.98 | 1.70 | 30.27 | 72.00 | 1.94 | 0.00 | 0.00 | 744.00 |
September | 42.87 | 11.12 | 31.75 | 81.26 | 6.33 | 0.00 | 0.00 | 720.00 |
October | 73.76 | 41.19 | 32.57 | 126.93 | 24.44 | 0.00 | 0.00 | 744.00 |
November | 92.16 | 60.92 | 31.23 | 145.12 | 43.58 | 0.00 | 0.00 | 720.00 |
December | 82.25 | 51.55 | 30.70 | 115.48 | 58.62 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 55.75 | 24.67 | 31.09 | 97.49 | 23.77 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 28.89 | 0.41 | 28.41 | 72.00 | 0.65 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 92.16 | 60.92 | 34.93 | 145.12 | 58.62 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_DOOR
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 92.15 | 56.00 | 36.15 | 124.40 | 69.50 | 0.00 | 0.00 | 744.00 |
February | 87.61 | 48.67 | 38.95 | 124.22 | 56.75 | 0.00 | 0.00 | 672.00 |
March | 74.88 | 33.07 | 41.82 | 115.30 | 35.14 | 0.00 | 0.00 | 744.00 |
April | 52.59 | 14.82 | 37.76 | 98.87 | 13.18 | 0.00 | 0.00 | 720.00 |
May | 37.81 | 2.78 | 35.03 | 96.78 | 2.78 | 0.00 | 0.00 | 744.00 |
June | 34.60 | 0.58 | 34.02 | 99.07 | 2.20 | 0.00 | 0.00 | 720.00 |
July | 36.09 | 0.49 | 35.60 | 92.12 | 0.78 | 0.00 | 0.00 | 744.00 |
August | 38.29 | 2.04 | 36.25 | 85.68 | 2.32 | 0.00 | 0.00 | 744.00 |
September | 51.33 | 13.32 | 38.01 | 96.82 | 7.54 | 0.00 | 0.00 | 720.00 |
October | 88.32 | 49.31 | 39.00 | 151.43 | 29.09 | 0.00 | 0.00 | 744.00 |
November | 110.35 | 72.95 | 37.40 | 173.31 | 51.85 | 0.00 | 0.00 | 720.00 |
December | 98.48 | 61.72 | 36.76 | 138.03 | 69.69 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 66.76 | 29.54 | 37.22 | 116.26 | 28.27 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 34.60 | 0.49 | 34.02 | 85.68 | 0.78 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 110.35 | 72.95 | 41.82 | 173.31 | 69.69 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.96 | 46.77 | 30.19 | 104.42 | 57.60 | 0.00 | 0.00 | 744.00 |
February | 73.17 | 40.64 | 32.53 | 104.14 | 47.24 | 0.00 | 0.00 | 672.00 |
March | 62.54 | 27.62 | 34.93 | 96.69 | 29.18 | 0.00 | 0.00 | 744.00 |
April | 43.92 | 12.38 | 31.54 | 83.15 | 10.83 | 0.00 | 0.00 | 720.00 |
May | 31.58 | 2.32 | 29.26 | 81.64 | 2.22 | 0.00 | 0.00 | 744.00 |
June | 28.89 | 0.48 | 28.41 | 83.62 | 1.79 | 0.00 | 0.00 | 720.00 |
July | 30.14 | 0.41 | 29.74 | 77.67 | 0.60 | 0.00 | 0.00 | 744.00 |
August | 31.98 | 1.70 | 30.27 | 72.16 | 1.84 | 0.00 | 0.00 | 744.00 |
September | 42.87 | 11.12 | 31.75 | 81.34 | 6.11 | 0.00 | 0.00 | 720.00 |
October | 73.76 | 41.19 | 32.57 | 126.99 | 24.19 | 0.00 | 0.00 | 744.00 |
November | 92.16 | 60.92 | 31.23 | 145.23 | 43.27 | 0.00 | 0.00 | 720.00 |
December | 82.25 | 51.55 | 30.70 | 115.72 | 58.11 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 55.75 | 24.67 | 31.09 | 97.67 | 23.48 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 28.89 | 0.41 | 28.41 | 72.16 | 0.60 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 92.16 | 60.92 | 34.93 | 145.23 | 58.11 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.96 | 46.77 | 30.19 | 104.42 | 57.60 | 0.00 | 0.00 | 744.00 |
February | 73.17 | 40.64 | 32.53 | 104.14 | 47.24 | 0.00 | 0.00 | 672.00 |
March | 62.54 | 27.62 | 34.93 | 96.69 | 29.18 | 0.00 | 0.00 | 744.00 |
April | 43.92 | 12.38 | 31.54 | 83.15 | 10.83 | 0.00 | 0.00 | 720.00 |
May | 31.58 | 2.32 | 29.26 | 81.64 | 2.22 | 0.00 | 0.00 | 744.00 |
June | 28.89 | 0.48 | 28.41 | 83.62 | 1.79 | 0.00 | 0.00 | 720.00 |
July | 30.14 | 0.41 | 29.74 | 77.67 | 0.60 | 0.00 | 0.00 | 744.00 |
August | 31.98 | 1.70 | 30.27 | 72.16 | 1.84 | 0.00 | 0.00 | 744.00 |
September | 42.87 | 11.12 | 31.75 | 81.34 | 6.11 | 0.00 | 0.00 | 720.00 |
October | 73.76 | 41.19 | 32.57 | 126.99 | 24.19 | 0.00 | 0.00 | 744.00 |
November | 92.16 | 60.92 | 31.23 | 145.23 | 43.27 | 0.00 | 0.00 | 720.00 |
December | 82.25 | 51.55 | 30.70 | 115.72 | 58.11 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 55.75 | 24.67 | 31.09 | 97.67 | 23.48 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 28.89 | 0.41 | 28.41 | 72.16 | 0.60 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 92.16 | 60.92 | 34.93 | 145.23 | 58.11 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_DOOR
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 92.15 | 56.00 | 36.15 | 124.87 | 68.46 | 0.00 | 0.00 | 744.00 |
February | 87.61 | 48.67 | 38.95 | 124.48 | 56.15 | 0.00 | 0.00 | 672.00 |
March | 74.88 | 33.07 | 41.82 | 115.44 | 34.73 | 0.00 | 0.00 | 744.00 |
April | 52.59 | 14.82 | 37.76 | 99.04 | 12.90 | 0.00 | 0.00 | 720.00 |
May | 37.81 | 2.78 | 35.03 | 97.01 | 2.67 | 0.00 | 0.00 | 744.00 |
June | 34.60 | 0.58 | 34.02 | 99.36 | 2.13 | 0.00 | 0.00 | 720.00 |
July | 36.09 | 0.49 | 35.60 | 92.33 | 0.72 | 0.00 | 0.00 | 744.00 |
August | 38.29 | 2.04 | 36.25 | 85.87 | 2.20 | 0.00 | 0.00 | 744.00 |
September | 51.33 | 13.32 | 38.01 | 96.92 | 7.28 | 0.00 | 0.00 | 720.00 |
October | 88.32 | 49.31 | 39.00 | 151.51 | 28.79 | 0.00 | 0.00 | 744.00 |
November | 110.35 | 72.95 | 37.40 | 173.43 | 51.48 | 0.00 | 0.00 | 720.00 |
December | 98.48 | 61.72 | 36.76 | 138.32 | 69.07 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 66.76 | 29.54 | 37.22 | 116.48 | 27.92 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 34.60 | 0.49 | 34.02 | 85.87 | 0.72 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 110.35 | 72.95 | 41.82 | 173.43 | 69.07 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.96 | 46.77 | 30.19 | 105.22 | 56.06 | 0.00 | 0.00 | 744.00 |
February | 73.17 | 40.64 | 32.53 | 104.62 | 46.19 | 0.00 | 0.00 | 672.00 |
March | 62.54 | 27.62 | 34.93 | 96.91 | 28.27 | 0.00 | 0.00 | 744.00 |
April | 43.92 | 12.38 | 31.54 | 83.27 | 10.15 | 0.00 | 0.00 | 720.00 |
May | 31.58 | 2.32 | 29.26 | 81.82 | 1.97 | 0.00 | 0.00 | 744.00 |
June | 28.89 | 0.48 | 28.41 | 84.00 | 1.65 | 0.00 | 0.00 | 720.00 |
July | 30.14 | 0.41 | 29.74 | 77.69 | 0.48 | 0.00 | 0.00 | 744.00 |
August | 31.98 | 1.70 | 30.27 | 72.25 | 1.54 | 0.00 | 0.00 | 744.00 |
September | 42.87 | 11.12 | 31.75 | 81.19 | 5.46 | 0.00 | 0.00 | 720.00 |
October | 73.76 | 41.19 | 32.57 | 126.84 | 23.41 | 0.00 | 0.00 | 744.00 |
November | 92.16 | 60.92 | 31.23 | 145.36 | 42.54 | 0.00 | 0.00 | 720.00 |
December | 82.25 | 51.55 | 30.70 | 116.21 | 57.10 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 55.75 | 24.67 | 31.09 | 97.89 | 22.80 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 28.89 | 0.41 | 28.41 | 72.25 | 0.48 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 92.16 | 60.92 | 34.93 | 145.36 | 57.10 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.96 | 46.77 | 30.19 | 105.22 | 56.06 | 0.00 | 0.00 | 744.00 |
February | 73.17 | 40.64 | 32.53 | 104.62 | 46.19 | 0.00 | 0.00 | 672.00 |
March | 62.54 | 27.62 | 34.93 | 96.91 | 28.27 | 0.00 | 0.00 | 744.00 |
April | 43.92 | 12.38 | 31.54 | 83.27 | 10.15 | 0.00 | 0.00 | 720.00 |
May | 31.58 | 2.32 | 29.26 | 81.82 | 1.97 | 0.00 | 0.00 | 744.00 |
June | 28.89 | 0.48 | 28.41 | 84.00 | 1.65 | 0.00 | 0.00 | 720.00 |
July | 30.14 | 0.41 | 29.74 | 77.69 | 0.48 | 0.00 | 0.00 | 744.00 |
August | 31.98 | 1.70 | 30.27 | 72.25 | 1.54 | 0.00 | 0.00 | 744.00 |
September | 42.87 | 11.12 | 31.75 | 81.19 | 5.46 | 0.00 | 0.00 | 720.00 |
October | 73.76 | 41.19 | 32.57 | 126.84 | 23.41 | 0.00 | 0.00 | 744.00 |
November | 92.16 | 60.92 | 31.23 | 145.36 | 42.54 | 0.00 | 0.00 | 720.00 |
December | 82.25 | 51.55 | 30.70 | 116.21 | 57.10 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 55.75 | 24.67 | 31.09 | 97.89 | 22.80 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 28.89 | 0.41 | 28.41 | 72.25 | 0.48 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 92.16 | 60.92 | 34.93 | 145.36 | 57.10 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_3
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.96 | 46.77 | 30.19 | 105.22 | 56.06 | 0.00 | 0.00 | 744.00 |
February | 73.17 | 40.64 | 32.53 | 104.62 | 46.19 | 0.00 | 0.00 | 672.00 |
March | 62.54 | 27.62 | 34.93 | 96.91 | 28.27 | 0.00 | 0.00 | 744.00 |
April | 43.92 | 12.38 | 31.54 | 83.27 | 10.15 | 0.00 | 0.00 | 720.00 |
May | 31.58 | 2.32 | 29.26 | 81.82 | 1.97 | 0.00 | 0.00 | 744.00 |
June | 28.89 | 0.48 | 28.41 | 84.00 | 1.65 | 0.00 | 0.00 | 720.00 |
July | 30.14 | 0.41 | 29.74 | 77.69 | 0.48 | 0.00 | 0.00 | 744.00 |
August | 31.98 | 1.70 | 30.27 | 72.25 | 1.54 | 0.00 | 0.00 | 744.00 |
September | 42.87 | 11.12 | 31.75 | 81.19 | 5.46 | 0.00 | 0.00 | 720.00 |
October | 73.76 | 41.19 | 32.57 | 126.84 | 23.41 | 0.00 | 0.00 | 744.00 |
November | 92.16 | 60.92 | 31.23 | 145.36 | 42.54 | 0.00 | 0.00 | 720.00 |
December | 82.25 | 51.55 | 30.70 | 116.21 | 57.10 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 55.75 | 24.67 | 31.09 | 97.89 | 22.80 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 28.89 | 0.41 | 28.41 | 72.25 | 0.48 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 92.16 | 60.92 | 34.93 | 145.36 | 57.10 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_4
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.96 | 46.77 | 30.19 | 105.22 | 56.06 | 0.00 | 0.00 | 744.00 |
February | 73.17 | 40.64 | 32.53 | 104.62 | 46.19 | 0.00 | 0.00 | 672.00 |
March | 62.54 | 27.62 | 34.93 | 96.91 | 28.27 | 0.00 | 0.00 | 744.00 |
April | 43.92 | 12.38 | 31.54 | 83.27 | 10.15 | 0.00 | 0.00 | 720.00 |
May | 31.58 | 2.32 | 29.26 | 81.82 | 1.97 | 0.00 | 0.00 | 744.00 |
June | 28.89 | 0.48 | 28.41 | 84.00 | 1.65 | 0.00 | 0.00 | 720.00 |
July | 30.14 | 0.41 | 29.74 | 77.69 | 0.48 | 0.00 | 0.00 | 744.00 |
August | 31.98 | 1.70 | 30.27 | 72.25 | 1.54 | 0.00 | 0.00 | 744.00 |
September | 42.87 | 11.12 | 31.75 | 81.19 | 5.46 | 0.00 | 0.00 | 720.00 |
October | 73.76 | 41.19 | 32.57 | 126.84 | 23.41 | 0.00 | 0.00 | 744.00 |
November | 92.16 | 60.92 | 31.23 | 145.36 | 42.54 | 0.00 | 0.00 | 720.00 |
December | 82.25 | 51.55 | 30.70 | 116.21 | 57.10 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 55.75 | 24.67 | 31.09 | 97.89 | 22.80 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 28.89 | 0.41 | 28.41 | 72.25 | 0.48 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 92.16 | 60.92 | 34.93 | 145.36 | 57.10 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_DOOR_1
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 92.15 | 56.00 | 36.15 | 125.81 | 66.62 | 0.00 | 0.00 | 744.00 |
February | 87.61 | 48.67 | 38.95 | 125.04 | 54.90 | 0.00 | 0.00 | 672.00 |
March | 74.88 | 33.07 | 41.82 | 115.71 | 33.65 | 0.00 | 0.00 | 744.00 |
April | 52.59 | 14.82 | 37.76 | 99.19 | 12.09 | 0.00 | 0.00 | 720.00 |
May | 37.81 | 2.78 | 35.03 | 97.23 | 2.36 | 0.00 | 0.00 | 744.00 |
June | 34.60 | 0.58 | 34.02 | 99.83 | 1.96 | 0.00 | 0.00 | 720.00 |
July | 36.09 | 0.49 | 35.60 | 92.38 | 0.57 | 0.00 | 0.00 | 744.00 |
August | 38.29 | 2.04 | 36.25 | 85.99 | 1.84 | 0.00 | 0.00 | 744.00 |
September | 51.33 | 13.32 | 38.01 | 96.75 | 6.51 | 0.00 | 0.00 | 720.00 |
October | 88.32 | 49.31 | 39.00 | 151.33 | 27.87 | 0.00 | 0.00 | 744.00 |
November | 110.35 | 72.95 | 37.40 | 173.60 | 50.61 | 0.00 | 0.00 | 720.00 |
December | 98.48 | 61.72 | 36.76 | 138.90 | 67.87 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 66.76 | 29.54 | 37.22 | 116.74 | 27.11 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 34.60 | 0.49 | 34.02 | 85.99 | 0.57 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 110.35 | 72.95 | 41.82 | 173.60 | 67.87 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_DOOR_2
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 92.15 | 56.00 | 36.15 | 125.81 | 66.62 | 0.00 | 0.00 | 744.00 |
February | 87.61 | 48.67 | 38.95 | 125.04 | 54.90 | 0.00 | 0.00 | 672.00 |
March | 74.88 | 33.07 | 41.82 | 115.71 | 33.65 | 0.00 | 0.00 | 744.00 |
April | 52.59 | 14.82 | 37.76 | 99.19 | 12.09 | 0.00 | 0.00 | 720.00 |
May | 37.81 | 2.78 | 35.03 | 97.23 | 2.36 | 0.00 | 0.00 | 744.00 |
June | 34.60 | 0.58 | 34.02 | 99.83 | 1.96 | 0.00 | 0.00 | 720.00 |
July | 36.09 | 0.49 | 35.60 | 92.38 | 0.57 | 0.00 | 0.00 | 744.00 |
August | 38.29 | 2.04 | 36.25 | 85.99 | 1.84 | 0.00 | 0.00 | 744.00 |
September | 51.33 | 13.32 | 38.01 | 96.75 | 6.51 | 0.00 | 0.00 | 720.00 |
October | 88.32 | 49.31 | 39.00 | 151.33 | 27.87 | 0.00 | 0.00 | 744.00 |
November | 110.35 | 72.95 | 37.40 | 173.60 | 50.61 | 0.00 | 0.00 | 720.00 |
December | 98.48 | 61.72 | 36.76 | 138.90 | 67.87 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 66.76 | 29.54 | 37.22 | 116.74 | 27.11 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 34.60 | 0.49 | 34.02 | 85.99 | 0.57 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 110.35 | 72.95 | 41.82 | 173.60 | 67.87 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.96 | 46.77 | 30.19 | 105.17 | 55.87 | 0.00 | 0.00 | 744.00 |
February | 73.17 | 40.64 | 32.53 | 104.52 | 46.04 | 0.00 | 0.00 | 672.00 |
March | 62.54 | 27.62 | 34.93 | 96.94 | 28.01 | 0.00 | 0.00 | 744.00 |
April | 43.92 | 12.38 | 31.54 | 83.66 | 9.87 | 0.00 | 0.00 | 720.00 |
May | 31.58 | 2.32 | 29.26 | 82.61 | 1.81 | 0.00 | 0.00 | 744.00 |
June | 28.89 | 0.48 | 28.41 | 84.88 | 1.55 | 0.00 | 0.00 | 720.00 |
July | 30.14 | 0.41 | 29.74 | 78.51 | 0.40 | 0.00 | 0.00 | 744.00 |
August | 31.98 | 1.70 | 30.27 | 72.85 | 1.37 | 0.00 | 0.00 | 744.00 |
September | 42.87 | 11.12 | 31.75 | 81.51 | 5.11 | 0.00 | 0.00 | 720.00 |
October | 73.76 | 41.19 | 32.57 | 126.94 | 23.05 | 0.00 | 0.00 | 744.00 |
November | 92.16 | 60.92 | 31.23 | 145.31 | 42.31 | 0.00 | 0.00 | 720.00 |
December | 82.25 | 51.55 | 30.70 | 116.10 | 56.99 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 55.75 | 24.67 | 31.09 | 98.19 | 22.59 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 28.89 | 0.41 | 28.41 | 72.85 | 0.40 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 92.16 | 60.92 | 34.93 | 145.31 | 56.99 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.96 | 46.77 | 30.19 | 105.17 | 55.87 | 0.00 | 0.00 | 744.00 |
February | 73.17 | 40.64 | 32.53 | 104.52 | 46.04 | 0.00 | 0.00 | 672.00 |
March | 62.54 | 27.62 | 34.93 | 96.94 | 28.01 | 0.00 | 0.00 | 744.00 |
April | 43.92 | 12.38 | 31.54 | 83.66 | 9.87 | 0.00 | 0.00 | 720.00 |
May | 31.58 | 2.32 | 29.26 | 82.61 | 1.81 | 0.00 | 0.00 | 744.00 |
June | 28.89 | 0.48 | 28.41 | 84.88 | 1.55 | 0.00 | 0.00 | 720.00 |
July | 30.14 | 0.41 | 29.74 | 78.51 | 0.40 | 0.00 | 0.00 | 744.00 |
August | 31.98 | 1.70 | 30.27 | 72.85 | 1.37 | 0.00 | 0.00 | 744.00 |
September | 42.87 | 11.12 | 31.75 | 81.51 | 5.11 | 0.00 | 0.00 | 720.00 |
October | 73.76 | 41.19 | 32.57 | 126.94 | 23.05 | 0.00 | 0.00 | 744.00 |
November | 92.16 | 60.92 | 31.23 | 145.31 | 42.31 | 0.00 | 0.00 | 720.00 |
December | 82.25 | 51.55 | 30.70 | 116.10 | 56.99 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 55.75 | 24.67 | 31.09 | 98.19 | 22.59 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 28.89 | 0.41 | 28.41 | 72.85 | 0.40 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 92.16 | 60.92 | 34.93 | 145.31 | 56.99 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_DOOR
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 92.15 | 56.00 | 36.15 | 125.77 | 66.39 | 0.00 | 0.00 | 744.00 |
February | 87.61 | 48.67 | 38.95 | 124.94 | 54.72 | 0.00 | 0.00 | 672.00 |
March | 74.88 | 33.07 | 41.82 | 115.76 | 33.33 | 0.00 | 0.00 | 744.00 |
April | 52.59 | 14.82 | 37.76 | 99.66 | 11.75 | 0.00 | 0.00 | 720.00 |
May | 37.81 | 2.78 | 35.03 | 98.16 | 2.18 | 0.00 | 0.00 | 744.00 |
June | 34.60 | 0.58 | 34.02 | 100.87 | 1.84 | 0.00 | 0.00 | 720.00 |
July | 36.09 | 0.49 | 35.60 | 93.35 | 0.49 | 0.00 | 0.00 | 744.00 |
August | 38.29 | 2.04 | 36.25 | 86.71 | 1.64 | 0.00 | 0.00 | 744.00 |
September | 51.33 | 13.32 | 38.01 | 97.13 | 6.09 | 0.00 | 0.00 | 720.00 |
October | 88.32 | 49.31 | 39.00 | 151.47 | 27.43 | 0.00 | 0.00 | 744.00 |
November | 110.35 | 72.95 | 37.40 | 173.55 | 50.33 | 0.00 | 0.00 | 720.00 |
December | 98.48 | 61.72 | 36.76 | 138.79 | 67.74 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 66.76 | 29.54 | 37.22 | 117.11 | 26.87 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 34.60 | 0.49 | 34.02 | 86.71 | 0.49 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 110.35 | 72.95 | 41.82 | 173.55 | 67.74 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.96 | 46.77 | 30.19 | 105.33 | 55.56 | 0.00 | 0.00 | 744.00 |
February | 73.17 | 40.64 | 32.53 | 104.63 | 45.82 | 0.00 | 0.00 | 672.00 |
March | 62.54 | 27.62 | 34.93 | 97.02 | 27.86 | 0.00 | 0.00 | 744.00 |
April | 43.92 | 12.38 | 31.54 | 83.76 | 9.77 | 0.00 | 0.00 | 720.00 |
May | 31.58 | 2.32 | 29.26 | 82.73 | 1.78 | 0.00 | 0.00 | 744.00 |
June | 28.89 | 0.48 | 28.41 | 85.02 | 1.53 | 0.00 | 0.00 | 720.00 |
July | 30.14 | 0.41 | 29.74 | 78.64 | 0.39 | 0.00 | 0.00 | 744.00 |
August | 31.98 | 1.70 | 30.27 | 72.95 | 1.34 | 0.00 | 0.00 | 744.00 |
September | 42.87 | 11.12 | 31.75 | 81.57 | 5.04 | 0.00 | 0.00 | 720.00 |
October | 73.76 | 41.19 | 32.57 | 126.99 | 22.95 | 0.00 | 0.00 | 744.00 |
November | 92.16 | 60.92 | 31.23 | 145.37 | 42.19 | 0.00 | 0.00 | 720.00 |
December | 82.25 | 51.55 | 30.70 | 116.21 | 56.80 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 55.75 | 24.67 | 31.09 | 98.29 | 22.48 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 28.89 | 0.41 | 28.41 | 72.95 | 0.39 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 92.16 | 60.92 | 34.93 | 145.37 | 56.80 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.96 | 46.77 | 30.19 | 105.33 | 55.56 | 0.00 | 0.00 | 744.00 |
February | 73.17 | 40.64 | 32.53 | 104.63 | 45.82 | 0.00 | 0.00 | 672.00 |
March | 62.54 | 27.62 | 34.93 | 97.02 | 27.86 | 0.00 | 0.00 | 744.00 |
April | 43.92 | 12.38 | 31.54 | 83.76 | 9.77 | 0.00 | 0.00 | 720.00 |
May | 31.58 | 2.32 | 29.26 | 82.73 | 1.78 | 0.00 | 0.00 | 744.00 |
June | 28.89 | 0.48 | 28.41 | 85.02 | 1.53 | 0.00 | 0.00 | 720.00 |
July | 30.14 | 0.41 | 29.74 | 78.64 | 0.39 | 0.00 | 0.00 | 744.00 |
August | 31.98 | 1.70 | 30.27 | 72.95 | 1.34 | 0.00 | 0.00 | 744.00 |
September | 42.87 | 11.12 | 31.75 | 81.57 | 5.04 | 0.00 | 0.00 | 720.00 |
October | 73.76 | 41.19 | 32.57 | 126.99 | 22.95 | 0.00 | 0.00 | 744.00 |
November | 92.16 | 60.92 | 31.23 | 145.37 | 42.19 | 0.00 | 0.00 | 720.00 |
December | 82.25 | 51.55 | 30.70 | 116.21 | 56.80 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 55.75 | 24.67 | 31.09 | 98.29 | 22.48 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 28.89 | 0.41 | 28.41 | 72.95 | 0.39 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 92.16 | 60.92 | 34.93 | 145.37 | 56.80 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_DOOR
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 92.15 | 56.00 | 36.15 | 125.96 | 66.02 | 0.00 | 0.00 | 744.00 |
February | 87.61 | 48.67 | 38.95 | 125.08 | 54.45 | 0.00 | 0.00 | 672.00 |
March | 74.88 | 33.07 | 41.82 | 115.85 | 33.16 | 0.00 | 0.00 | 744.00 |
April | 52.59 | 14.82 | 37.76 | 99.78 | 11.64 | 0.00 | 0.00 | 720.00 |
May | 37.81 | 2.78 | 35.03 | 98.31 | 2.13 | 0.00 | 0.00 | 744.00 |
June | 34.60 | 0.58 | 34.02 | 101.04 | 1.81 | 0.00 | 0.00 | 720.00 |
July | 36.09 | 0.49 | 35.60 | 93.50 | 0.47 | 0.00 | 0.00 | 744.00 |
August | 38.29 | 2.04 | 36.25 | 86.83 | 1.60 | 0.00 | 0.00 | 744.00 |
September | 51.33 | 13.32 | 38.01 | 97.21 | 6.01 | 0.00 | 0.00 | 720.00 |
October | 88.32 | 49.31 | 39.00 | 151.53 | 27.32 | 0.00 | 0.00 | 744.00 |
November | 110.35 | 72.95 | 37.40 | 173.62 | 50.19 | 0.00 | 0.00 | 720.00 |
December | 98.48 | 61.72 | 36.76 | 138.92 | 67.51 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 66.76 | 29.54 | 37.22 | 117.23 | 26.74 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 34.60 | 0.49 | 34.02 | 86.83 | 0.47 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 110.35 | 72.95 | 41.82 | 173.62 | 67.51 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.96 | 46.77 | 30.19 | 105.63 | 54.91 | 0.00 | 0.00 | 744.00 |
February | 73.17 | 40.64 | 32.53 | 104.90 | 45.24 | 0.00 | 0.00 | 672.00 |
March | 62.54 | 27.62 | 34.93 | 97.18 | 27.51 | 0.00 | 0.00 | 744.00 |
April | 43.92 | 12.38 | 31.54 | 83.83 | 9.62 | 0.00 | 0.00 | 720.00 |
May | 31.58 | 2.32 | 29.26 | 82.72 | 1.75 | 0.00 | 0.00 | 744.00 |
June | 28.89 | 0.48 | 28.41 | 84.93 | 1.52 | 0.00 | 0.00 | 720.00 |
July | 30.14 | 0.41 | 29.74 | 78.45 | 0.40 | 0.00 | 0.00 | 744.00 |
August | 31.98 | 1.70 | 30.27 | 72.79 | 1.37 | 0.00 | 0.00 | 744.00 |
September | 42.87 | 11.12 | 31.75 | 81.48 | 5.10 | 0.00 | 0.00 | 720.00 |
October | 73.76 | 41.19 | 32.57 | 126.97 | 22.94 | 0.00 | 0.00 | 744.00 |
November | 92.16 | 60.92 | 31.23 | 145.44 | 42.02 | 0.00 | 0.00 | 720.00 |
December | 82.25 | 51.55 | 30.70 | 116.44 | 56.35 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 55.75 | 24.67 | 31.09 | 98.34 | 22.29 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 28.89 | 0.41 | 28.41 | 72.79 | 0.40 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 92.16 | 60.92 | 34.93 | 145.44 | 56.35 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.96 | 46.77 | 30.19 | 105.63 | 54.91 | 0.00 | 0.00 | 744.00 |
February | 73.17 | 40.64 | 32.53 | 104.90 | 45.24 | 0.00 | 0.00 | 672.00 |
March | 62.54 | 27.62 | 34.93 | 97.18 | 27.51 | 0.00 | 0.00 | 744.00 |
April | 43.92 | 12.38 | 31.54 | 83.83 | 9.62 | 0.00 | 0.00 | 720.00 |
May | 31.58 | 2.32 | 29.26 | 82.72 | 1.75 | 0.00 | 0.00 | 744.00 |
June | 28.89 | 0.48 | 28.41 | 84.93 | 1.52 | 0.00 | 0.00 | 720.00 |
July | 30.14 | 0.41 | 29.74 | 78.45 | 0.40 | 0.00 | 0.00 | 744.00 |
August | 31.98 | 1.70 | 30.27 | 72.79 | 1.37 | 0.00 | 0.00 | 744.00 |
September | 42.87 | 11.12 | 31.75 | 81.48 | 5.10 | 0.00 | 0.00 | 720.00 |
October | 73.76 | 41.19 | 32.57 | 126.97 | 22.94 | 0.00 | 0.00 | 744.00 |
November | 92.16 | 60.92 | 31.23 | 145.44 | 42.02 | 0.00 | 0.00 | 720.00 |
December | 82.25 | 51.55 | 30.70 | 116.44 | 56.35 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 55.75 | 24.67 | 31.09 | 98.34 | 22.29 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 28.89 | 0.41 | 28.41 | 72.79 | 0.40 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 92.16 | 60.92 | 34.93 | 145.44 | 56.35 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_DOOR
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 92.15 | 56.00 | 36.15 | 126.32 | 65.25 | 0.00 | 0.00 | 744.00 |
February | 87.61 | 48.67 | 38.95 | 125.40 | 53.77 | 0.00 | 0.00 | 672.00 |
March | 74.88 | 33.07 | 41.82 | 116.03 | 32.74 | 0.00 | 0.00 | 744.00 |
April | 52.59 | 14.82 | 37.76 | 99.87 | 11.46 | 0.00 | 0.00 | 720.00 |
May | 37.81 | 2.78 | 35.03 | 98.29 | 2.10 | 0.00 | 0.00 | 744.00 |
June | 34.60 | 0.58 | 34.02 | 100.93 | 1.80 | 0.00 | 0.00 | 720.00 |
July | 36.09 | 0.49 | 35.60 | 93.28 | 0.48 | 0.00 | 0.00 | 744.00 |
August | 38.29 | 2.04 | 36.25 | 86.63 | 1.64 | 0.00 | 0.00 | 744.00 |
September | 51.33 | 13.32 | 38.01 | 97.10 | 6.08 | 0.00 | 0.00 | 720.00 |
October | 88.32 | 49.31 | 39.00 | 151.50 | 27.32 | 0.00 | 0.00 | 744.00 |
November | 110.35 | 72.95 | 37.40 | 173.71 | 49.99 | 0.00 | 0.00 | 720.00 |
December | 98.48 | 61.72 | 36.76 | 139.20 | 66.98 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 66.76 | 29.54 | 37.22 | 117.28 | 26.51 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 34.60 | 0.49 | 34.02 | 86.63 | 0.48 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 110.35 | 72.95 | 41.82 | 173.71 | 66.98 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.96 | 46.77 | 30.19 | 106.05 | 53.35 | 0.00 | 0.00 | 744.00 |
February | 73.17 | 40.64 | 32.53 | 105.41 | 43.50 | 0.00 | 0.00 | 672.00 |
March | 62.54 | 27.62 | 34.93 | 97.42 | 26.30 | 0.00 | 0.00 | 744.00 |
April | 43.92 | 12.38 | 31.54 | 83.55 | 9.23 | 0.00 | 0.00 | 720.00 |
May | 31.58 | 2.32 | 29.26 | 81.78 | 1.78 | 0.00 | 0.00 | 744.00 |
June | 28.89 | 0.48 | 28.41 | 83.53 | 1.58 | 0.00 | 0.00 | 720.00 |
July | 30.14 | 0.41 | 29.74 | 76.58 | 0.50 | 0.00 | 0.00 | 744.00 |
August | 31.98 | 1.70 | 30.27 | 71.15 | 1.74 | 0.00 | 0.00 | 744.00 |
September | 42.87 | 11.12 | 31.75 | 80.48 | 5.90 | 0.00 | 0.00 | 720.00 |
October | 73.76 | 41.19 | 32.57 | 126.41 | 23.43 | 0.00 | 0.00 | 744.00 |
November | 92.16 | 60.92 | 31.23 | 145.35 | 41.68 | 0.00 | 0.00 | 720.00 |
December | 82.25 | 51.55 | 30.70 | 116.78 | 55.18 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 55.75 | 24.67 | 31.09 | 97.81 | 21.92 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 28.89 | 0.41 | 28.41 | 71.15 | 0.50 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 92.16 | 60.92 | 34.93 | 145.35 | 55.18 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.96 | 46.77 | 30.19 | 106.05 | 53.35 | 0.00 | 0.00 | 744.00 |
February | 73.17 | 40.64 | 32.53 | 105.41 | 43.50 | 0.00 | 0.00 | 672.00 |
March | 62.54 | 27.62 | 34.93 | 97.42 | 26.30 | 0.00 | 0.00 | 744.00 |
April | 43.92 | 12.38 | 31.54 | 83.55 | 9.23 | 0.00 | 0.00 | 720.00 |
May | 31.58 | 2.32 | 29.26 | 81.78 | 1.78 | 0.00 | 0.00 | 744.00 |
June | 28.89 | 0.48 | 28.41 | 83.53 | 1.58 | 0.00 | 0.00 | 720.00 |
July | 30.14 | 0.41 | 29.74 | 76.58 | 0.50 | 0.00 | 0.00 | 744.00 |
August | 31.98 | 1.70 | 30.27 | 71.15 | 1.74 | 0.00 | 0.00 | 744.00 |
September | 42.87 | 11.12 | 31.75 | 80.48 | 5.90 | 0.00 | 0.00 | 720.00 |
October | 73.76 | 41.19 | 32.57 | 126.41 | 23.43 | 0.00 | 0.00 | 744.00 |
November | 92.16 | 60.92 | 31.23 | 145.35 | 41.68 | 0.00 | 0.00 | 720.00 |
December | 82.25 | 51.55 | 30.70 | 116.78 | 55.18 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 55.75 | 24.67 | 31.09 | 97.81 | 21.92 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 28.89 | 0.41 | 28.41 | 71.15 | 0.50 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 92.16 | 60.92 | 34.93 | 145.35 | 55.18 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_DOOR
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 92.15 | 56.00 | 36.15 | 126.82 | 63.41 | 0.00 | 0.00 | 744.00 |
February | 87.61 | 48.67 | 38.95 | 126.01 | 51.70 | 0.00 | 0.00 | 672.00 |
March | 74.88 | 33.07 | 41.82 | 116.32 | 31.30 | 0.00 | 0.00 | 744.00 |
April | 52.59 | 14.82 | 37.76 | 99.53 | 10.99 | 0.00 | 0.00 | 720.00 |
May | 37.81 | 2.78 | 35.03 | 97.16 | 2.14 | 0.00 | 0.00 | 744.00 |
June | 34.60 | 0.58 | 34.02 | 99.24 | 1.88 | 0.00 | 0.00 | 720.00 |
July | 36.09 | 0.49 | 35.60 | 91.04 | 0.61 | 0.00 | 0.00 | 744.00 |
August | 38.29 | 2.04 | 36.25 | 84.66 | 2.08 | 0.00 | 0.00 | 744.00 |
September | 51.33 | 13.32 | 38.01 | 95.89 | 7.03 | 0.00 | 0.00 | 720.00 |
October | 88.32 | 49.31 | 39.00 | 150.82 | 27.89 | 0.00 | 0.00 | 744.00 |
November | 110.35 | 72.95 | 37.40 | 173.59 | 49.59 | 0.00 | 0.00 | 720.00 |
December | 98.48 | 61.72 | 36.76 | 139.59 | 65.59 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 66.76 | 29.54 | 37.22 | 116.64 | 26.07 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 34.60 | 0.49 | 34.02 | 84.66 | 0.61 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 110.35 | 72.95 | 41.82 | 173.59 | 65.59 | 0.00 | 0.00 | 744.00 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.206140E+09 | 0.125277E+09 | 80862769.86 | 0.277994E+09 | 0.158608E+09 |
February | 0.177011E+09 | 98324877.05 | 78686512.39 | 0.251846E+09 | 0.113956E+09 |
March | 0.167509E+09 | 73965634.87 | 93543734.09 | 0.259664E+09 | 74501491.11 |
April | 0.113838E+09 | 32090702.63 | 81746939.17 | 0.219419E+09 | 24148145.84 |
May | 84580621.94 | 6213479.77 | 78367142.18 | 0.226928E+09 | 4083812.93 |
June | 74895808.02 | 1254904.26 | 73640903.76 | 0.224528E+09 | 3063959.89 |
July | 80739855.26 | 1097554.60 | 79642300.66 | 0.217512E+09 | 1064531.95 |
August | 85648160.46 | 4561320.68 | 81086839.78 | 0.198732E+09 | 3241726.28 |
September | 0.111112E+09 | 28824581.51 | 82287586.02 | 0.213681E+09 | 11932809.26 |
October | 0.197557E+09 | 0.110312E+09 | 87245272.99 | 0.340693E+09 | 59259428.12 |
November | 0.238875E+09 | 0.157914E+09 | 80961026.03 | 0.376182E+09 | 0.109952E+09 |
December | 0.220296E+09 | 0.138066E+09 | 82229496.04 | 0.309016E+09 | 0.157005E+09 |
Annual Sum or Average | 0.175820E+10 | 0.777902E+09 | 0.980301E+09 | 0.311620E+10 | 0.720817E+09 |
Minimum of Months | 74895808.02 | 1097554.60 | 73640903.76 | 0.198732E+09 | 1064531.95 |
Maximum of Months | 0.238875E+09 | 0.157914E+09 | 93543734.09 | 0.376182E+09 | 0.158608E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.206140E+09 | 0.125277E+09 | 80862769.86 | 0.277994E+09 | 0.158608E+09 |
February | 0.177011E+09 | 98324877.05 | 78686512.39 | 0.251846E+09 | 0.113956E+09 |
March | 0.167509E+09 | 73965634.87 | 93543734.09 | 0.259664E+09 | 74501491.11 |
April | 0.113838E+09 | 32090702.63 | 81746939.17 | 0.219419E+09 | 24148145.84 |
May | 84580621.94 | 6213479.77 | 78367142.18 | 0.226928E+09 | 4083812.93 |
June | 74895808.02 | 1254904.26 | 73640903.76 | 0.224528E+09 | 3063959.89 |
July | 80739855.26 | 1097554.60 | 79642300.66 | 0.217512E+09 | 1064531.95 |
August | 85648160.46 | 4561320.68 | 81086839.78 | 0.198732E+09 | 3241726.28 |
September | 0.111112E+09 | 28824581.51 | 82287586.02 | 0.213681E+09 | 11932809.26 |
October | 0.197557E+09 | 0.110312E+09 | 87245272.99 | 0.340693E+09 | 59259428.12 |
November | 0.238875E+09 | 0.157914E+09 | 80961026.03 | 0.376182E+09 | 0.109952E+09 |
December | 0.220296E+09 | 0.138066E+09 | 82229496.04 | 0.309016E+09 | 0.157005E+09 |
Annual Sum or Average | 0.175820E+10 | 0.777902E+09 | 0.980301E+09 | 0.311620E+10 | 0.720817E+09 |
Minimum of Months | 74895808.02 | 1097554.60 | 73640903.76 | 0.198732E+09 | 1064531.95 |
Maximum of Months | 0.238875E+09 | 0.157914E+09 | 93543734.09 | 0.376182E+09 | 0.158608E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_3
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.206140E+09 | 0.125277E+09 | 80862769.86 | 0.277994E+09 | 0.158608E+09 |
February | 0.177011E+09 | 98324877.05 | 78686512.39 | 0.251846E+09 | 0.113956E+09 |
March | 0.167509E+09 | 73965634.87 | 93543734.09 | 0.259664E+09 | 74501491.11 |
April | 0.113838E+09 | 32090702.63 | 81746939.17 | 0.219419E+09 | 24148145.84 |
May | 84580621.94 | 6213479.77 | 78367142.18 | 0.226928E+09 | 4083812.93 |
June | 74895808.02 | 1254904.26 | 73640903.76 | 0.224528E+09 | 3063959.89 |
July | 80739855.26 | 1097554.60 | 79642300.66 | 0.217512E+09 | 1064531.95 |
August | 85648160.46 | 4561320.68 | 81086839.78 | 0.198732E+09 | 3241726.28 |
September | 0.111112E+09 | 28824581.51 | 82287586.02 | 0.213681E+09 | 11932809.26 |
October | 0.197557E+09 | 0.110312E+09 | 87245272.99 | 0.340693E+09 | 59259428.12 |
November | 0.238875E+09 | 0.157914E+09 | 80961026.03 | 0.376182E+09 | 0.109952E+09 |
December | 0.220296E+09 | 0.138066E+09 | 82229496.04 | 0.309016E+09 | 0.157005E+09 |
Annual Sum or Average | 0.175820E+10 | 0.777902E+09 | 0.980301E+09 | 0.311620E+10 | 0.720817E+09 |
Minimum of Months | 74895808.02 | 1097554.60 | 73640903.76 | 0.198732E+09 | 1064531.95 |
Maximum of Months | 0.238875E+09 | 0.157914E+09 | 93543734.09 | 0.376182E+09 | 0.158608E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_4
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.206140E+09 | 0.125277E+09 | 80862769.86 | 0.277994E+09 | 0.158608E+09 |
February | 0.177011E+09 | 98324877.05 | 78686512.39 | 0.251846E+09 | 0.113956E+09 |
March | 0.167509E+09 | 73965634.87 | 93543734.09 | 0.259664E+09 | 74501491.11 |
April | 0.113838E+09 | 32090702.63 | 81746939.17 | 0.219419E+09 | 24148145.84 |
May | 84580621.94 | 6213479.77 | 78367142.18 | 0.226928E+09 | 4083812.93 |
June | 74895808.02 | 1254904.26 | 73640903.76 | 0.224528E+09 | 3063959.89 |
July | 80739855.26 | 1097554.60 | 79642300.66 | 0.217512E+09 | 1064531.95 |
August | 85648160.46 | 4561320.68 | 81086839.78 | 0.198732E+09 | 3241726.28 |
September | 0.111112E+09 | 28824581.51 | 82287586.02 | 0.213681E+09 | 11932809.26 |
October | 0.197557E+09 | 0.110312E+09 | 87245272.99 | 0.340693E+09 | 59259428.12 |
November | 0.238875E+09 | 0.157914E+09 | 80961026.03 | 0.376182E+09 | 0.109952E+09 |
December | 0.220296E+09 | 0.138066E+09 | 82229496.04 | 0.309016E+09 | 0.157005E+09 |
Annual Sum or Average | 0.175820E+10 | 0.777902E+09 | 0.980301E+09 | 0.311620E+10 | 0.720817E+09 |
Minimum of Months | 74895808.02 | 1097554.60 | 73640903.76 | 0.198732E+09 | 1064531.95 |
Maximum of Months | 0.238875E+09 | 0.157914E+09 | 93543734.09 | 0.376182E+09 | 0.158608E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_DOOR_1
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.248181E+09 | 0.150827E+09 | 97354518.97 | 0.334194E+09 | 0.189619E+09 |
February | 0.213112E+09 | 0.118378E+09 | 94734419.52 | 0.302643E+09 | 0.136280E+09 |
March | 0.201672E+09 | 89050731.45 | 0.112622E+09 | 0.311668E+09 | 89254116.01 |
April | 0.137055E+09 | 38635516.98 | 98419012.29 | 0.262662E+09 | 28964191.32 |
May | 0.101831E+09 | 7480702.62 | 94349914.59 | 0.270922E+09 | 4929061.21 |
June | 90170610.98 | 1510838.69 | 88659772.29 | 0.268071E+09 | 3680344.82 |
July | 97206536.27 | 1321397.98 | 95885138.30 | 0.259762E+09 | 1287891.29 |
August | 0.103116E+09 | 5491590.03 | 97624287.37 | 0.237596E+09 | 3910330.79 |
September | 0.133773E+09 | 34703279.05 | 99069922.65 | 0.255830E+09 | 14340587.39 |
October | 0.237848E+09 | 0.132810E+09 | 0.105039E+09 | 0.408637E+09 | 71055547.83 |
November | 0.287593E+09 | 0.190121E+09 | 97472814.23 | 0.451673E+09 | 0.131647E+09 |
December | 0.265225E+09 | 0.166225E+09 | 98999985.37 | 0.371349E+09 | 0.187766E+09 |
Annual Sum or Average | 0.211678E+10 | 0.936554E+09 | 0.118023E+10 | 0.373501E+10 | 0.862733E+09 |
Minimum of Months | 90170610.98 | 1321397.98 | 88659772.29 | 0.237596E+09 | 1287891.29 |
Maximum of Months | 0.287593E+09 | 0.190121E+09 | 0.112622E+09 | 0.451673E+09 | 0.189619E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_DOOR_2
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.248181E+09 | 0.150827E+09 | 97354518.97 | 0.334194E+09 | 0.189619E+09 |
February | 0.213112E+09 | 0.118378E+09 | 94734419.52 | 0.302643E+09 | 0.136280E+09 |
March | 0.201672E+09 | 89050731.45 | 0.112622E+09 | 0.311668E+09 | 89254116.01 |
April | 0.137055E+09 | 38635516.98 | 98419012.29 | 0.262662E+09 | 28964191.32 |
May | 0.101831E+09 | 7480702.62 | 94349914.59 | 0.270922E+09 | 4929061.21 |
June | 90170610.98 | 1510838.69 | 88659772.29 | 0.268071E+09 | 3680344.82 |
July | 97206536.27 | 1321397.98 | 95885138.30 | 0.259762E+09 | 1287891.29 |
August | 0.103116E+09 | 5491590.03 | 97624287.37 | 0.237596E+09 | 3910330.79 |
September | 0.133773E+09 | 34703279.05 | 99069922.65 | 0.255830E+09 | 14340587.39 |
October | 0.237848E+09 | 0.132810E+09 | 0.105039E+09 | 0.408637E+09 | 71055547.83 |
November | 0.287593E+09 | 0.190121E+09 | 97472814.23 | 0.451673E+09 | 0.131647E+09 |
December | 0.265225E+09 | 0.166225E+09 | 98999985.37 | 0.371349E+09 | 0.187766E+09 |
Annual Sum or Average | 0.211678E+10 | 0.936554E+09 | 0.118023E+10 | 0.373501E+10 | 0.862733E+09 |
Minimum of Months | 90170610.98 | 1321397.98 | 88659772.29 | 0.237596E+09 | 1287891.29 |
Maximum of Months | 0.287593E+09 | 0.190121E+09 | 0.112622E+09 | 0.451673E+09 | 0.189619E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.206140E+09 | 0.125277E+09 | 80862769.86 | 0.275843E+09 | 0.162946E+09 |
February | 0.177011E+09 | 98324877.05 | 78686512.39 | 0.250413E+09 | 0.116262E+09 |
March | 0.167509E+09 | 73965634.87 | 93543734.09 | 0.258971E+09 | 75789752.55 |
April | 0.113838E+09 | 32090702.63 | 81746939.17 | 0.219945E+09 | 24648318.84 |
May | 84580621.94 | 6213479.77 | 78367142.18 | 0.228617E+09 | 4116392.88 |
June | 74895808.02 | 1254904.26 | 73640903.76 | 0.226798E+09 | 3063060.66 |
July | 80739855.26 | 1097554.60 | 79642300.66 | 0.220088E+09 | 978803.16 |
August | 85648160.46 | 4561320.68 | 81086839.78 | 0.201051E+09 | 2953202.04 |
September | 0.111112E+09 | 28824581.51 | 82287586.02 | 0.215162E+09 | 11283903.70 |
October | 0.197557E+09 | 0.110312E+09 | 87245272.99 | 0.341233E+09 | 58854416.37 |
November | 0.238875E+09 | 0.157914E+09 | 80961026.03 | 0.375785E+09 | 0.110249E+09 |
December | 0.220296E+09 | 0.138066E+09 | 82229496.04 | 0.307574E+09 | 0.159374E+09 |
Annual Sum or Average | 0.175820E+10 | 0.777902E+09 | 0.980301E+09 | 0.312148E+10 | 0.730520E+09 |
Minimum of Months | 74895808.02 | 1097554.60 | 73640903.76 | 0.201051E+09 | 978803.16 |
Maximum of Months | 0.238875E+09 | 0.157914E+09 | 93543734.09 | 0.375785E+09 | 0.162946E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.206140E+09 | 0.125277E+09 | 80862769.86 | 0.275843E+09 | 0.162946E+09 |
February | 0.177011E+09 | 98324877.05 | 78686512.39 | 0.250413E+09 | 0.116262E+09 |
March | 0.167509E+09 | 73965634.87 | 93543734.09 | 0.258971E+09 | 75789752.55 |
April | 0.113838E+09 | 32090702.63 | 81746939.17 | 0.219945E+09 | 24648318.84 |
May | 84580621.94 | 6213479.77 | 78367142.18 | 0.228617E+09 | 4116392.88 |
June | 74895808.02 | 1254904.26 | 73640903.76 | 0.226798E+09 | 3063060.66 |
July | 80739855.26 | 1097554.60 | 79642300.66 | 0.220088E+09 | 978803.16 |
August | 85648160.46 | 4561320.68 | 81086839.78 | 0.201051E+09 | 2953202.04 |
September | 0.111112E+09 | 28824581.51 | 82287586.02 | 0.215162E+09 | 11283903.70 |
October | 0.197557E+09 | 0.110312E+09 | 87245272.99 | 0.341233E+09 | 58854416.37 |
November | 0.238875E+09 | 0.157914E+09 | 80961026.03 | 0.375785E+09 | 0.110249E+09 |
December | 0.220296E+09 | 0.138066E+09 | 82229496.04 | 0.307574E+09 | 0.159374E+09 |
Annual Sum or Average | 0.175820E+10 | 0.777902E+09 | 0.980301E+09 | 0.312148E+10 | 0.730520E+09 |
Minimum of Months | 74895808.02 | 1097554.60 | 73640903.76 | 0.201051E+09 | 978803.16 |
Maximum of Months | 0.238875E+09 | 0.157914E+09 | 93543734.09 | 0.375785E+09 | 0.162946E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_DOOR
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.248181E+09 | 0.150827E+09 | 97354518.97 | 0.331650E+09 | 0.194749E+09 |
February | 0.213112E+09 | 0.118378E+09 | 94734419.52 | 0.300954E+09 | 0.139012E+09 |
March | 0.201672E+09 | 89050731.45 | 0.112622E+09 | 0.310854E+09 | 90782824.74 |
April | 0.137055E+09 | 38635516.98 | 98419012.29 | 0.263291E+09 | 29560895.78 |
May | 0.101831E+09 | 7480702.62 | 94349914.59 | 0.272932E+09 | 4970431.50 |
June | 90170610.98 | 1510838.69 | 88659772.29 | 0.270796E+09 | 3678408.89 |
July | 97206536.27 | 1321397.98 | 95885138.30 | 0.262852E+09 | 1183780.79 |
August | 0.103116E+09 | 5491590.03 | 97624287.37 | 0.240397E+09 | 3562285.74 |
September | 0.133773E+09 | 34703279.05 | 99069922.65 | 0.257640E+09 | 13560590.40 |
October | 0.237848E+09 | 0.132810E+09 | 0.105039E+09 | 0.409318E+09 | 70559327.67 |
November | 0.287593E+09 | 0.190121E+09 | 97472814.23 | 0.451235E+09 | 0.131986E+09 |
December | 0.265225E+09 | 0.166225E+09 | 98999985.37 | 0.369658E+09 | 0.190561E+09 |
Annual Sum or Average | 0.211678E+10 | 0.936554E+09 | 0.118023E+10 | 0.374158E+10 | 0.874167E+09 |
Minimum of Months | 90170610.98 | 1321397.98 | 88659772.29 | 0.240397E+09 | 1183780.79 |
Maximum of Months | 0.287593E+09 | 0.190121E+09 | 0.112622E+09 | 0.451235E+09 | 0.194749E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.206140E+09 | 0.125277E+09 | 80862769.86 | 0.277644E+09 | 0.159263E+09 |
February | 0.177011E+09 | 98324877.05 | 78686512.39 | 0.251035E+09 | 0.116570E+09 |
March | 0.167509E+09 | 73965634.87 | 93543734.09 | 0.258589E+09 | 79278970.14 |
April | 0.113838E+09 | 32090702.63 | 81746939.17 | 0.215430E+09 | 28257385.41 |
May | 84580621.94 | 6213479.77 | 78367142.18 | 0.219087E+09 | 5791250.95 |
June | 74895808.02 | 1254904.26 | 73640903.76 | 0.217173E+09 | 4519855.62 |
July | 80739855.26 | 1097554.60 | 79642300.66 | 0.208815E+09 | 1579212.33 |
August | 85648160.46 | 4561320.68 | 81086839.78 | 0.193569E+09 | 4877422.06 |
September | 0.111112E+09 | 28824581.51 | 82287586.02 | 0.210888E+09 | 15713360.57 |
October | 0.197557E+09 | 0.110312E+09 | 87245272.99 | 0.340077E+09 | 64962171.02 |
November | 0.238875E+09 | 0.157914E+09 | 80961026.03 | 0.376027E+09 | 0.113309E+09 |
December | 0.220296E+09 | 0.138066E+09 | 82229496.04 | 0.308731E+09 | 0.158467E+09 |
Annual Sum or Average | 0.175820E+10 | 0.777902E+09 | 0.980301E+09 | 0.307707E+10 | 0.752589E+09 |
Minimum of Months | 74895808.02 | 1097554.60 | 73640903.76 | 0.193569E+09 | 1579212.33 |
Maximum of Months | 0.238875E+09 | 0.157914E+09 | 93543734.09 | 0.376027E+09 | 0.159263E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.206140E+09 | 0.125277E+09 | 80862769.86 | 0.277644E+09 | 0.159263E+09 |
February | 0.177011E+09 | 98324877.05 | 78686512.39 | 0.251035E+09 | 0.116570E+09 |
March | 0.167509E+09 | 73965634.87 | 93543734.09 | 0.258589E+09 | 79278970.14 |
April | 0.113838E+09 | 32090702.63 | 81746939.17 | 0.215430E+09 | 28257385.41 |
May | 84580621.94 | 6213479.77 | 78367142.18 | 0.219087E+09 | 5791250.95 |
June | 74895808.02 | 1254904.26 | 73640903.76 | 0.217173E+09 | 4519855.62 |
July | 80739855.26 | 1097554.60 | 79642300.66 | 0.208815E+09 | 1579212.33 |
August | 85648160.46 | 4561320.68 | 81086839.78 | 0.193569E+09 | 4877422.06 |
September | 0.111112E+09 | 28824581.51 | 82287586.02 | 0.210888E+09 | 15713360.57 |
October | 0.197557E+09 | 0.110312E+09 | 87245272.99 | 0.340077E+09 | 64962171.02 |
November | 0.238875E+09 | 0.157914E+09 | 80961026.03 | 0.376027E+09 | 0.113309E+09 |
December | 0.220296E+09 | 0.138066E+09 | 82229496.04 | 0.308731E+09 | 0.158467E+09 |
Annual Sum or Average | 0.175820E+10 | 0.777902E+09 | 0.980301E+09 | 0.307707E+10 | 0.752589E+09 |
Minimum of Months | 74895808.02 | 1097554.60 | 73640903.76 | 0.193569E+09 | 1579212.33 |
Maximum of Months | 0.238875E+09 | 0.157914E+09 | 93543734.09 | 0.376027E+09 | 0.159263E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_DOOR
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.246825E+09 | 0.150002E+09 | 96822527.06 | 0.331997E+09 | 0.189269E+09 |
February | 0.211948E+09 | 0.117731E+09 | 94216745.09 | 0.300061E+09 | 0.138547E+09 |
March | 0.200570E+09 | 88564115.43 | 0.112006E+09 | 0.308715E+09 | 94336189.47 |
April | 0.136306E+09 | 38424393.94 | 97881203.48 | 0.256593E+09 | 33648450.27 |
May | 0.101274E+09 | 7439824.46 | 93834341.29 | 0.260321E+09 | 6944568.67 |
June | 89677875.40 | 1502582.74 | 88175292.66 | 0.258058E+09 | 5374793.25 |
July | 96675353.01 | 1314177.22 | 95361175.79 | 0.248249E+09 | 1901108.13 |
August | 0.102552E+09 | 5461581.34 | 97090821.32 | 0.230353E+09 | 5825753.92 |
September | 0.133042E+09 | 34513643.65 | 98528556.95 | 0.251270E+09 | 18717744.16 |
October | 0.236549E+09 | 0.132084E+09 | 0.104465E+09 | 0.405729E+09 | 77324832.70 |
November | 0.286022E+09 | 0.189082E+09 | 96940175.90 | 0.449058E+09 | 0.134795E+09 |
December | 0.263775E+09 | 0.165316E+09 | 98459001.84 | 0.369026E+09 | 0.188371E+09 |
Annual Sum or Average | 0.210522E+10 | 0.931436E+09 | 0.117378E+10 | 0.366943E+10 | 0.895055E+09 |
Minimum of Months | 89677875.40 | 1314177.22 | 88175292.66 | 0.230353E+09 | 1901108.13 |
Maximum of Months | 0.286022E+09 | 0.189082E+09 | 0.112006E+09 | 0.449058E+09 | 0.189269E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.206140E+09 | 0.125277E+09 | 80862769.86 | 0.278645E+09 | 0.156639E+09 |
February | 0.177011E+09 | 98324877.05 | 78686512.39 | 0.251415E+09 | 0.115522E+09 |
March | 0.167509E+09 | 73965634.87 | 93543734.09 | 0.258665E+09 | 79095982.26 |
April | 0.113838E+09 | 32090702.63 | 81746939.17 | 0.215171E+09 | 28687932.88 |
May | 84580621.94 | 6213479.77 | 78367142.18 | 0.218160E+09 | 6218366.95 |
June | 74895808.02 | 1254904.26 | 73640903.76 | 0.216107E+09 | 4789260.09 |
July | 80739855.26 | 1097554.60 | 79642300.66 | 0.207536E+09 | 1737415.26 |
August | 85648160.46 | 4561320.68 | 81086839.78 | 0.192838E+09 | 5204964.34 |
September | 0.111112E+09 | 28824581.51 | 82287586.02 | 0.210634E+09 | 16395899.62 |
October | 0.197557E+09 | 0.110312E+09 | 87245272.99 | 0.339970E+09 | 65452863.45 |
November | 0.238875E+09 | 0.157914E+09 | 80961026.03 | 0.376151E+09 | 0.112968E+09 |
December | 0.220296E+09 | 0.138066E+09 | 82229496.04 | 0.309291E+09 | 0.157019E+09 |
Annual Sum or Average | 0.175820E+10 | 0.777902E+09 | 0.980301E+09 | 0.307458E+10 | 0.749730E+09 |
Minimum of Months | 74895808.02 | 1097554.60 | 73640903.76 | 0.192838E+09 | 1737415.26 |
Maximum of Months | 0.238875E+09 | 0.157914E+09 | 93543734.09 | 0.376151E+09 | 0.157019E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.206140E+09 | 0.125277E+09 | 80862769.86 | 0.278645E+09 | 0.156639E+09 |
February | 0.177011E+09 | 98324877.05 | 78686512.39 | 0.251415E+09 | 0.115522E+09 |
March | 0.167509E+09 | 73965634.87 | 93543734.09 | 0.258665E+09 | 79095982.26 |
April | 0.113838E+09 | 32090702.63 | 81746939.17 | 0.215171E+09 | 28687932.88 |
May | 84580621.94 | 6213479.77 | 78367142.18 | 0.218160E+09 | 6218366.95 |
June | 74895808.02 | 1254904.26 | 73640903.76 | 0.216107E+09 | 4789260.09 |
July | 80739855.26 | 1097554.60 | 79642300.66 | 0.207536E+09 | 1737415.26 |
August | 85648160.46 | 4561320.68 | 81086839.78 | 0.192838E+09 | 5204964.34 |
September | 0.111112E+09 | 28824581.51 | 82287586.02 | 0.210634E+09 | 16395899.62 |
October | 0.197557E+09 | 0.110312E+09 | 87245272.99 | 0.339970E+09 | 65452863.45 |
November | 0.238875E+09 | 0.157914E+09 | 80961026.03 | 0.376151E+09 | 0.112968E+09 |
December | 0.220296E+09 | 0.138066E+09 | 82229496.04 | 0.309291E+09 | 0.157019E+09 |
Annual Sum or Average | 0.175820E+10 | 0.777902E+09 | 0.980301E+09 | 0.307458E+10 | 0.749730E+09 |
Minimum of Months | 74895808.02 | 1097554.60 | 73640903.76 | 0.192838E+09 | 1737415.26 |
Maximum of Months | 0.238875E+09 | 0.157914E+09 | 93543734.09 | 0.376151E+09 | 0.157019E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_DOOR
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.246825E+09 | 0.150002E+09 | 96822527.06 | 0.333197E+09 | 0.186150E+09 |
February | 0.211948E+09 | 0.117731E+09 | 94216745.09 | 0.300517E+09 | 0.137301E+09 |
March | 0.200570E+09 | 88564115.43 | 0.112006E+09 | 0.308808E+09 | 94118731.38 |
April | 0.136306E+09 | 38424393.94 | 97881203.48 | 0.256282E+09 | 34160228.89 |
May | 0.101274E+09 | 7439824.46 | 93834341.29 | 0.259219E+09 | 7455883.28 |
June | 89677875.40 | 1502582.74 | 88175292.66 | 0.256786E+09 | 5695751.52 |
July | 96675353.01 | 1314177.22 | 95361175.79 | 0.246727E+09 | 2092281.00 |
August | 0.102552E+09 | 5461581.34 | 97090821.32 | 0.229481E+09 | 6214961.76 |
September | 0.133042E+09 | 34513643.65 | 98528556.95 | 0.250965E+09 | 19530940.27 |
October | 0.236549E+09 | 0.132084E+09 | 0.104465E+09 | 0.405600E+09 | 77908886.27 |
November | 0.286022E+09 | 0.189082E+09 | 96940175.90 | 0.449208E+09 | 0.134389E+09 |
December | 0.263775E+09 | 0.165316E+09 | 98459001.84 | 0.369697E+09 | 0.186649E+09 |
Annual Sum or Average | 0.210522E+10 | 0.931436E+09 | 0.117378E+10 | 0.366649E+10 | 0.891667E+09 |
Minimum of Months | 89677875.40 | 1314177.22 | 88175292.66 | 0.229481E+09 | 2092281.00 |
Maximum of Months | 0.286022E+09 | 0.189082E+09 | 0.112006E+09 | 0.449208E+09 | 0.186649E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.206140E+09 | 0.125277E+09 | 80862769.86 | 0.279691E+09 | 0.154285E+09 |
February | 0.177011E+09 | 98324877.05 | 78686512.39 | 0.251925E+09 | 0.114285E+09 |
March | 0.167509E+09 | 73965634.87 | 93543734.09 | 0.258982E+09 | 78167529.66 |
April | 0.113838E+09 | 32090702.63 | 81746939.17 | 0.215532E+09 | 28074837.71 |
May | 84580621.94 | 6213479.77 | 78367142.18 | 0.218669E+09 | 5954040.36 |
June | 74895808.02 | 1254904.26 | 73640903.76 | 0.216736E+09 | 4641884.36 |
July | 80739855.26 | 1097554.60 | 79642300.66 | 0.208023E+09 | 1607085.27 |
August | 85648160.46 | 4561320.68 | 81086839.78 | 0.193271E+09 | 4922127.79 |
September | 0.111112E+09 | 28824581.51 | 82287586.02 | 0.210835E+09 | 15827002.41 |
October | 0.197557E+09 | 0.110312E+09 | 87245272.99 | 0.340137E+09 | 64777274.05 |
November | 0.238875E+09 | 0.157914E+09 | 80961026.03 | 0.376428E+09 | 0.112164E+09 |
December | 0.220296E+09 | 0.138066E+09 | 82229496.04 | 0.309938E+09 | 0.155633E+09 |
Annual Sum or Average | 0.175820E+10 | 0.777902E+09 | 0.980301E+09 | 0.308017E+10 | 0.740339E+09 |
Minimum of Months | 74895808.02 | 1097554.60 | 73640903.76 | 0.193271E+09 | 1607085.27 |
Maximum of Months | 0.238875E+09 | 0.157914E+09 | 93543734.09 | 0.376428E+09 | 0.155633E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.206140E+09 | 0.125277E+09 | 80862769.86 | 0.279691E+09 | 0.154285E+09 |
February | 0.177011E+09 | 98324877.05 | 78686512.39 | 0.251925E+09 | 0.114285E+09 |
March | 0.167509E+09 | 73965634.87 | 93543734.09 | 0.258982E+09 | 78167529.66 |
April | 0.113838E+09 | 32090702.63 | 81746939.17 | 0.215532E+09 | 28074837.71 |
May | 84580621.94 | 6213479.77 | 78367142.18 | 0.218669E+09 | 5954040.36 |
June | 74895808.02 | 1254904.26 | 73640903.76 | 0.216736E+09 | 4641884.36 |
July | 80739855.26 | 1097554.60 | 79642300.66 | 0.208023E+09 | 1607085.27 |
August | 85648160.46 | 4561320.68 | 81086839.78 | 0.193271E+09 | 4922127.79 |
September | 0.111112E+09 | 28824581.51 | 82287586.02 | 0.210835E+09 | 15827002.41 |
October | 0.197557E+09 | 0.110312E+09 | 87245272.99 | 0.340137E+09 | 64777274.05 |
November | 0.238875E+09 | 0.157914E+09 | 80961026.03 | 0.376428E+09 | 0.112164E+09 |
December | 0.220296E+09 | 0.138066E+09 | 82229496.04 | 0.309938E+09 | 0.155633E+09 |
Annual Sum or Average | 0.175820E+10 | 0.777902E+09 | 0.980301E+09 | 0.308017E+10 | 0.740339E+09 |
Minimum of Months | 74895808.02 | 1097554.60 | 73640903.76 | 0.193271E+09 | 1607085.27 |
Maximum of Months | 0.238875E+09 | 0.157914E+09 | 93543734.09 | 0.376428E+09 | 0.155633E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_DOOR
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.246825E+09 | 0.150002E+09 | 96822527.06 | 0.334451E+09 | 0.183359E+09 |
February | 0.211948E+09 | 0.117731E+09 | 94216745.09 | 0.301130E+09 | 0.135838E+09 |
March | 0.200570E+09 | 88564115.43 | 0.112006E+09 | 0.309192E+09 | 93022087.54 |
April | 0.136306E+09 | 38424393.94 | 97881203.48 | 0.256715E+09 | 33436889.28 |
May | 0.101274E+09 | 7439824.46 | 93834341.29 | 0.259820E+09 | 7141228.84 |
June | 89677875.40 | 1502582.74 | 88175292.66 | 0.257531E+09 | 5521873.87 |
July | 96675353.01 | 1314177.22 | 95361175.79 | 0.247300E+09 | 1936582.97 |
August | 0.102552E+09 | 5461581.34 | 97090821.32 | 0.229995E+09 | 5880147.86 |
September | 0.133042E+09 | 34513643.65 | 98528556.95 | 0.251206E+09 | 18862049.56 |
October | 0.236549E+09 | 0.132084E+09 | 0.104465E+09 | 0.405804E+09 | 77111133.23 |
November | 0.286022E+09 | 0.189082E+09 | 96940175.90 | 0.449542E+09 | 0.133439E+09 |
December | 0.263775E+09 | 0.165316E+09 | 98459001.84 | 0.370474E+09 | 0.185007E+09 |
Annual Sum or Average | 0.210522E+10 | 0.931436E+09 | 0.117378E+10 | 0.367316E+10 | 0.880555E+09 |
Minimum of Months | 89677875.40 | 1314177.22 | 88175292.66 | 0.229995E+09 | 1936582.97 |
Maximum of Months | 0.286022E+09 | 0.189082E+09 | 0.112006E+09 | 0.449542E+09 | 0.185007E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.206140E+09 | 0.125277E+09 | 80862769.86 | 0.281827E+09 | 0.150150E+09 |
February | 0.177011E+09 | 98324877.05 | 78686512.39 | 0.253088E+09 | 0.111738E+09 |
March | 0.167509E+09 | 73965634.87 | 93543734.09 | 0.259569E+09 | 75721569.28 |
April | 0.113838E+09 | 32090702.63 | 81746939.17 | 0.215823E+09 | 26305149.90 |
May | 84580621.94 | 6213479.77 | 78367142.18 | 0.219137E+09 | 5280579.60 |
June | 74895808.02 | 1254904.26 | 73640903.76 | 0.217733E+09 | 4265226.33 |
July | 80739855.26 | 1097554.60 | 79642300.66 | 0.208093E+09 | 1275887.44 |
August | 85648160.46 | 4561320.68 | 81086839.78 | 0.193519E+09 | 4114050.89 |
September | 0.111112E+09 | 28824581.51 | 82287586.02 | 0.210446E+09 | 14161989.33 |
October | 0.197557E+09 | 0.110312E+09 | 87245272.99 | 0.339720E+09 | 62700053.06 |
November | 0.238875E+09 | 0.157914E+09 | 80961026.03 | 0.376781E+09 | 0.110273E+09 |
December | 0.220296E+09 | 0.138066E+09 | 82229496.04 | 0.311245E+09 | 0.152931E+09 |
Annual Sum or Average | 0.175820E+10 | 0.777902E+09 | 0.980301E+09 | 0.308698E+10 | 0.718916E+09 |
Minimum of Months | 74895808.02 | 1097554.60 | 73640903.76 | 0.193519E+09 | 1275887.44 |
Maximum of Months | 0.238875E+09 | 0.157914E+09 | 93543734.09 | 0.376781E+09 | 0.152931E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.206140E+09 | 0.125277E+09 | 80862769.86 | 0.281827E+09 | 0.150150E+09 |
February | 0.177011E+09 | 98324877.05 | 78686512.39 | 0.253088E+09 | 0.111738E+09 |
March | 0.167509E+09 | 73965634.87 | 93543734.09 | 0.259569E+09 | 75721569.28 |
April | 0.113838E+09 | 32090702.63 | 81746939.17 | 0.215823E+09 | 26305149.90 |
May | 84580621.94 | 6213479.77 | 78367142.18 | 0.219137E+09 | 5280579.60 |
June | 74895808.02 | 1254904.26 | 73640903.76 | 0.217733E+09 | 4265226.33 |
July | 80739855.26 | 1097554.60 | 79642300.66 | 0.208093E+09 | 1275887.44 |
August | 85648160.46 | 4561320.68 | 81086839.78 | 0.193519E+09 | 4114050.89 |
September | 0.111112E+09 | 28824581.51 | 82287586.02 | 0.210446E+09 | 14161989.33 |
October | 0.197557E+09 | 0.110312E+09 | 87245272.99 | 0.339720E+09 | 62700053.06 |
November | 0.238875E+09 | 0.157914E+09 | 80961026.03 | 0.376781E+09 | 0.110273E+09 |
December | 0.220296E+09 | 0.138066E+09 | 82229496.04 | 0.311245E+09 | 0.152931E+09 |
Annual Sum or Average | 0.175820E+10 | 0.777902E+09 | 0.980301E+09 | 0.308698E+10 | 0.718916E+09 |
Minimum of Months | 74895808.02 | 1097554.60 | 73640903.76 | 0.193519E+09 | 1275887.44 |
Maximum of Months | 0.238875E+09 | 0.157914E+09 | 93543734.09 | 0.376781E+09 | 0.152931E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_3
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.206140E+09 | 0.125277E+09 | 80862769.86 | 0.281827E+09 | 0.150150E+09 |
February | 0.177011E+09 | 98324877.05 | 78686512.39 | 0.253088E+09 | 0.111738E+09 |
March | 0.167509E+09 | 73965634.87 | 93543734.09 | 0.259569E+09 | 75721569.28 |
April | 0.113838E+09 | 32090702.63 | 81746939.17 | 0.215823E+09 | 26305149.90 |
May | 84580621.94 | 6213479.77 | 78367142.18 | 0.219137E+09 | 5280579.60 |
June | 74895808.02 | 1254904.26 | 73640903.76 | 0.217733E+09 | 4265226.33 |
July | 80739855.26 | 1097554.60 | 79642300.66 | 0.208093E+09 | 1275887.44 |
August | 85648160.46 | 4561320.68 | 81086839.78 | 0.193519E+09 | 4114050.89 |
September | 0.111112E+09 | 28824581.51 | 82287586.02 | 0.210446E+09 | 14161989.33 |
October | 0.197557E+09 | 0.110312E+09 | 87245272.99 | 0.339720E+09 | 62700053.06 |
November | 0.238875E+09 | 0.157914E+09 | 80961026.03 | 0.376781E+09 | 0.110273E+09 |
December | 0.220296E+09 | 0.138066E+09 | 82229496.04 | 0.311245E+09 | 0.152931E+09 |
Annual Sum or Average | 0.175820E+10 | 0.777902E+09 | 0.980301E+09 | 0.308698E+10 | 0.718916E+09 |
Minimum of Months | 74895808.02 | 1097554.60 | 73640903.76 | 0.193519E+09 | 1275887.44 |
Maximum of Months | 0.238875E+09 | 0.157914E+09 | 93543734.09 | 0.376781E+09 | 0.152931E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_4
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.206140E+09 | 0.125277E+09 | 80862769.86 | 0.281827E+09 | 0.150150E+09 |
February | 0.177011E+09 | 98324877.05 | 78686512.39 | 0.253088E+09 | 0.111738E+09 |
March | 0.167509E+09 | 73965634.87 | 93543734.09 | 0.259569E+09 | 75721569.28 |
April | 0.113838E+09 | 32090702.63 | 81746939.17 | 0.215823E+09 | 26305149.90 |
May | 84580621.94 | 6213479.77 | 78367142.18 | 0.219137E+09 | 5280579.60 |
June | 74895808.02 | 1254904.26 | 73640903.76 | 0.217733E+09 | 4265226.33 |
July | 80739855.26 | 1097554.60 | 79642300.66 | 0.208093E+09 | 1275887.44 |
August | 85648160.46 | 4561320.68 | 81086839.78 | 0.193519E+09 | 4114050.89 |
September | 0.111112E+09 | 28824581.51 | 82287586.02 | 0.210446E+09 | 14161989.33 |
October | 0.197557E+09 | 0.110312E+09 | 87245272.99 | 0.339720E+09 | 62700053.06 |
November | 0.238875E+09 | 0.157914E+09 | 80961026.03 | 0.376781E+09 | 0.110273E+09 |
December | 0.220296E+09 | 0.138066E+09 | 82229496.04 | 0.311245E+09 | 0.152931E+09 |
Annual Sum or Average | 0.175820E+10 | 0.777902E+09 | 0.980301E+09 | 0.308698E+10 | 0.718916E+09 |
Minimum of Months | 74895808.02 | 1097554.60 | 73640903.76 | 0.193519E+09 | 1275887.44 |
Maximum of Months | 0.238875E+09 | 0.157914E+09 | 93543734.09 | 0.376781E+09 | 0.152931E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_DOOR_1
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.246825E+09 | 0.150002E+09 | 96822527.06 | 0.336981E+09 | 0.178443E+09 |
February | 0.211948E+09 | 0.117731E+09 | 94216745.09 | 0.302507E+09 | 0.132813E+09 |
March | 0.200570E+09 | 88564115.43 | 0.112006E+09 | 0.309904E+09 | 90119018.07 |
April | 0.136306E+09 | 38424393.94 | 97881203.48 | 0.257100E+09 | 31328369.84 |
May | 0.101274E+09 | 7439824.46 | 93834341.29 | 0.260422E+09 | 6329464.42 |
June | 89677875.40 | 1502582.74 | 88175292.66 | 0.258757E+09 | 5069075.55 |
July | 96675353.01 | 1314177.22 | 95361175.79 | 0.247431E+09 | 1535933.12 |
August | 0.102552E+09 | 5461581.34 | 97090821.32 | 0.230321E+09 | 4914938.05 |
September | 0.133042E+09 | 34513643.65 | 98528556.95 | 0.250768E+09 | 16874585.86 |
October | 0.236549E+09 | 0.132084E+09 | 0.104465E+09 | 0.405327E+09 | 74643715.25 |
November | 0.286022E+09 | 0.189082E+09 | 96940175.90 | 0.449964E+09 | 0.131189E+09 |
December | 0.263775E+09 | 0.165316E+09 | 98459001.84 | 0.372023E+09 | 0.181793E+09 |
Annual Sum or Average | 0.210522E+10 | 0.931436E+09 | 0.117378E+10 | 0.368151E+10 | 0.855053E+09 |
Minimum of Months | 89677875.40 | 1314177.22 | 88175292.66 | 0.230321E+09 | 1535933.12 |
Maximum of Months | 0.286022E+09 | 0.189082E+09 | 0.112006E+09 | 0.449964E+09 | 0.181793E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_DOOR_2
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.246825E+09 | 0.150002E+09 | 96822527.06 | 0.336981E+09 | 0.178443E+09 |
February | 0.211948E+09 | 0.117731E+09 | 94216745.09 | 0.302507E+09 | 0.132813E+09 |
March | 0.200570E+09 | 88564115.43 | 0.112006E+09 | 0.309904E+09 | 90119018.07 |
April | 0.136306E+09 | 38424393.94 | 97881203.48 | 0.257100E+09 | 31328369.84 |
May | 0.101274E+09 | 7439824.46 | 93834341.29 | 0.260422E+09 | 6329464.42 |
June | 89677875.40 | 1502582.74 | 88175292.66 | 0.258757E+09 | 5069075.55 |
July | 96675353.01 | 1314177.22 | 95361175.79 | 0.247431E+09 | 1535933.12 |
August | 0.102552E+09 | 5461581.34 | 97090821.32 | 0.230321E+09 | 4914938.05 |
September | 0.133042E+09 | 34513643.65 | 98528556.95 | 0.250768E+09 | 16874585.86 |
October | 0.236549E+09 | 0.132084E+09 | 0.104465E+09 | 0.405327E+09 | 74643715.25 |
November | 0.286022E+09 | 0.189082E+09 | 96940175.90 | 0.449964E+09 | 0.131189E+09 |
December | 0.263775E+09 | 0.165316E+09 | 98459001.84 | 0.372023E+09 | 0.181793E+09 |
Annual Sum or Average | 0.210522E+10 | 0.931436E+09 | 0.117378E+10 | 0.368151E+10 | 0.855053E+09 |
Minimum of Months | 89677875.40 | 1314177.22 | 88175292.66 | 0.230321E+09 | 1535933.12 |
Maximum of Months | 0.286022E+09 | 0.189082E+09 | 0.112006E+09 | 0.449964E+09 | 0.181793E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.206140E+09 | 0.125277E+09 | 80862769.86 | 0.281682E+09 | 0.149643E+09 |
February | 0.177011E+09 | 98324877.05 | 78686512.39 | 0.252844E+09 | 0.111386E+09 |
March | 0.167509E+09 | 73965634.87 | 93543734.09 | 0.259657E+09 | 75009958.78 |
April | 0.113838E+09 | 32090702.63 | 81746939.17 | 0.216845E+09 | 25580371.55 |
May | 84580621.94 | 6213479.77 | 78367142.18 | 0.221252E+09 | 4858867.71 |
June | 74895808.02 | 1254904.26 | 73640903.76 | 0.220010E+09 | 4016515.54 |
July | 80739855.26 | 1097554.60 | 79642300.66 | 0.210285E+09 | 1083554.71 |
August | 85648160.46 | 4561320.68 | 81086839.78 | 0.195127E+09 | 3671674.47 |
September | 0.111112E+09 | 28824581.51 | 82287586.02 | 0.211268E+09 | 13243093.81 |
October | 0.197557E+09 | 0.110312E+09 | 87245272.99 | 0.339998E+09 | 61723969.17 |
November | 0.238875E+09 | 0.157914E+09 | 80961026.03 | 0.376644E+09 | 0.109663E+09 |
December | 0.220296E+09 | 0.138066E+09 | 82229496.04 | 0.310967E+09 | 0.152642E+09 |
Annual Sum or Average | 0.175820E+10 | 0.777902E+09 | 0.980301E+09 | 0.309658E+10 | 0.712523E+09 |
Minimum of Months | 74895808.02 | 1097554.60 | 73640903.76 | 0.195127E+09 | 1083554.71 |
Maximum of Months | 0.238875E+09 | 0.157914E+09 | 93543734.09 | 0.376644E+09 | 0.152642E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.206140E+09 | 0.125277E+09 | 80862769.86 | 0.281682E+09 | 0.149643E+09 |
February | 0.177011E+09 | 98324877.05 | 78686512.39 | 0.252844E+09 | 0.111386E+09 |
March | 0.167509E+09 | 73965634.87 | 93543734.09 | 0.259657E+09 | 75009958.78 |
April | 0.113838E+09 | 32090702.63 | 81746939.17 | 0.216845E+09 | 25580371.55 |
May | 84580621.94 | 6213479.77 | 78367142.18 | 0.221252E+09 | 4858867.71 |
June | 74895808.02 | 1254904.26 | 73640903.76 | 0.220010E+09 | 4016515.54 |
July | 80739855.26 | 1097554.60 | 79642300.66 | 0.210285E+09 | 1083554.71 |
August | 85648160.46 | 4561320.68 | 81086839.78 | 0.195127E+09 | 3671674.47 |
September | 0.111112E+09 | 28824581.51 | 82287586.02 | 0.211268E+09 | 13243093.81 |
October | 0.197557E+09 | 0.110312E+09 | 87245272.99 | 0.339998E+09 | 61723969.17 |
November | 0.238875E+09 | 0.157914E+09 | 80961026.03 | 0.376644E+09 | 0.109663E+09 |
December | 0.220296E+09 | 0.138066E+09 | 82229496.04 | 0.310967E+09 | 0.152642E+09 |
Annual Sum or Average | 0.175820E+10 | 0.777902E+09 | 0.980301E+09 | 0.309658E+10 | 0.712523E+09 |
Minimum of Months | 74895808.02 | 1097554.60 | 73640903.76 | 0.195127E+09 | 1083554.71 |
Maximum of Months | 0.238875E+09 | 0.157914E+09 | 93543734.09 | 0.376644E+09 | 0.152642E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_DOOR
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.246825E+09 | 0.150002E+09 | 96822527.06 | 0.336850E+09 | 0.177822E+09 |
February | 0.211948E+09 | 0.117731E+09 | 94216745.09 | 0.302258E+09 | 0.132381E+09 |
March | 0.200570E+09 | 88564115.43 | 0.112006E+09 | 0.310040E+09 | 89267367.70 |
April | 0.136306E+09 | 38424393.94 | 97881203.48 | 0.258319E+09 | 30466371.26 |
May | 0.101274E+09 | 7439824.46 | 93834341.29 | 0.262919E+09 | 5828687.82 |
June | 89677875.40 | 1502582.74 | 88175292.66 | 0.261457E+09 | 4772083.31 |
July | 96675353.01 | 1314177.22 | 95361175.79 | 0.250028E+09 | 1305728.52 |
August | 0.102552E+09 | 5461581.34 | 97090821.32 | 0.232240E+09 | 4388084.65 |
September | 0.133042E+09 | 34513643.65 | 98528556.95 | 0.251767E+09 | 15781063.66 |
October | 0.236549E+09 | 0.132084E+09 | 0.104465E+09 | 0.405690E+09 | 73477882.54 |
November | 0.286022E+09 | 0.189082E+09 | 96940175.90 | 0.449843E+09 | 0.130454E+09 |
December | 0.263775E+09 | 0.165316E+09 | 98459001.84 | 0.371734E+09 | 0.181433E+09 |
Annual Sum or Average | 0.210522E+10 | 0.931436E+09 | 0.117378E+10 | 0.369314E+10 | 0.847377E+09 |
Minimum of Months | 89677875.40 | 1314177.22 | 88175292.66 | 0.232240E+09 | 1305728.52 |
Maximum of Months | 0.286022E+09 | 0.189082E+09 | 0.112006E+09 | 0.449843E+09 | 0.181433E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.206140E+09 | 0.125277E+09 | 80862769.86 | 0.282107E+09 | 0.148816E+09 |
February | 0.177011E+09 | 98324877.05 | 78686512.39 | 0.253126E+09 | 0.110843E+09 |
March | 0.167509E+09 | 73965634.87 | 93543734.09 | 0.259870E+09 | 74619756.04 |
April | 0.113838E+09 | 32090702.63 | 81746939.17 | 0.217099E+09 | 25331791.30 |
May | 84580621.94 | 6213479.77 | 78367142.18 | 0.221590E+09 | 4757058.39 |
June | 74895808.02 | 1254904.26 | 73640903.76 | 0.220368E+09 | 3952909.49 |
July | 80739855.26 | 1097554.60 | 79642300.66 | 0.210618E+09 | 1049037.25 |
August | 85648160.46 | 4561320.68 | 81086839.78 | 0.195393E+09 | 3589917.71 |
September | 0.111112E+09 | 28824581.51 | 82287586.02 | 0.211434E+09 | 13060975.22 |
October | 0.197557E+09 | 0.110312E+09 | 87245272.99 | 0.340130E+09 | 61475686.80 |
November | 0.238875E+09 | 0.157914E+09 | 80961026.03 | 0.376795E+09 | 0.109369E+09 |
December | 0.220296E+09 | 0.138066E+09 | 82229496.04 | 0.311257E+09 | 0.152128E+09 |
Annual Sum or Average | 0.175820E+10 | 0.777902E+09 | 0.980301E+09 | 0.309979E+10 | 0.708994E+09 |
Minimum of Months | 74895808.02 | 1097554.60 | 73640903.76 | 0.195393E+09 | 1049037.25 |
Maximum of Months | 0.238875E+09 | 0.157914E+09 | 93543734.09 | 0.376795E+09 | 0.152128E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.206140E+09 | 0.125277E+09 | 80862769.86 | 0.282107E+09 | 0.148816E+09 |
February | 0.177011E+09 | 98324877.05 | 78686512.39 | 0.253126E+09 | 0.110843E+09 |
March | 0.167509E+09 | 73965634.87 | 93543734.09 | 0.259870E+09 | 74619756.04 |
April | 0.113838E+09 | 32090702.63 | 81746939.17 | 0.217099E+09 | 25331791.30 |
May | 84580621.94 | 6213479.77 | 78367142.18 | 0.221590E+09 | 4757058.39 |
June | 74895808.02 | 1254904.26 | 73640903.76 | 0.220368E+09 | 3952909.49 |
July | 80739855.26 | 1097554.60 | 79642300.66 | 0.210618E+09 | 1049037.25 |
August | 85648160.46 | 4561320.68 | 81086839.78 | 0.195393E+09 | 3589917.71 |
September | 0.111112E+09 | 28824581.51 | 82287586.02 | 0.211434E+09 | 13060975.22 |
October | 0.197557E+09 | 0.110312E+09 | 87245272.99 | 0.340130E+09 | 61475686.80 |
November | 0.238875E+09 | 0.157914E+09 | 80961026.03 | 0.376795E+09 | 0.109369E+09 |
December | 0.220296E+09 | 0.138066E+09 | 82229496.04 | 0.311257E+09 | 0.152128E+09 |
Annual Sum or Average | 0.175820E+10 | 0.777902E+09 | 0.980301E+09 | 0.309979E+10 | 0.708994E+09 |
Minimum of Months | 74895808.02 | 1097554.60 | 73640903.76 | 0.195393E+09 | 1049037.25 |
Maximum of Months | 0.238875E+09 | 0.157914E+09 | 93543734.09 | 0.376795E+09 | 0.152128E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_DOOR
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.246825E+09 | 0.150002E+09 | 96822527.06 | 0.337360E+09 | 0.176840E+09 |
February | 0.211948E+09 | 0.117731E+09 | 94216745.09 | 0.302596E+09 | 0.131735E+09 |
March | 0.200570E+09 | 88564115.43 | 0.112006E+09 | 0.310298E+09 | 88803474.50 |
April | 0.136306E+09 | 38424393.94 | 97881203.48 | 0.258625E+09 | 30170541.81 |
May | 0.101274E+09 | 7439824.46 | 93834341.29 | 0.263323E+09 | 5704892.95 |
June | 89677875.40 | 1502582.74 | 88175292.66 | 0.261886E+09 | 4695926.99 |
July | 96675353.01 | 1314177.22 | 95361175.79 | 0.250426E+09 | 1264266.58 |
August | 0.102552E+09 | 5461581.34 | 97090821.32 | 0.232558E+09 | 4291453.44 |
September | 0.133042E+09 | 34513643.65 | 98528556.95 | 0.251968E+09 | 15565240.14 |
October | 0.236549E+09 | 0.132084E+09 | 0.104465E+09 | 0.405850E+09 | 73181461.68 |
November | 0.286022E+09 | 0.189082E+09 | 96940175.90 | 0.450025E+09 | 0.130105E+09 |
December | 0.263775E+09 | 0.165316E+09 | 98459001.84 | 0.372082E+09 | 0.180822E+09 |
Annual Sum or Average | 0.210522E+10 | 0.931436E+09 | 0.117378E+10 | 0.369700E+10 | 0.843178E+09 |
Minimum of Months | 89677875.40 | 1314177.22 | 88175292.66 | 0.232558E+09 | 1264266.58 |
Maximum of Months | 0.286022E+09 | 0.189082E+09 | 0.112006E+09 | 0.450025E+09 | 0.180822E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.206140E+09 | 0.125277E+09 | 80862769.86 | 0.282921E+09 | 0.147060E+09 |
February | 0.177011E+09 | 98324877.05 | 78686512.39 | 0.253776E+09 | 0.109445E+09 |
March | 0.167509E+09 | 73965634.87 | 93543734.09 | 0.260274E+09 | 73674190.18 |
April | 0.113838E+09 | 32090702.63 | 81746939.17 | 0.217293E+09 | 24941299.92 |
May | 84580621.94 | 6213479.77 | 78367142.18 | 0.221546E+09 | 4696494.65 |
June | 74895808.02 | 1254904.26 | 73640903.76 | 0.220138E+09 | 3934157.00 |
July | 80739855.26 | 1097554.60 | 79642300.66 | 0.210130E+09 | 1064251.39 |
August | 85648160.46 | 4561320.68 | 81086839.78 | 0.194949E+09 | 3669935.37 |
September | 0.111112E+09 | 28824581.51 | 82287586.02 | 0.211208E+09 | 13223542.62 |
October | 0.197557E+09 | 0.110312E+09 | 87245272.99 | 0.340076E+09 | 61452697.82 |
November | 0.238875E+09 | 0.157914E+09 | 80961026.03 | 0.376988E+09 | 0.108908E+09 |
December | 0.220296E+09 | 0.138066E+09 | 82229496.04 | 0.311885E+09 | 0.150925E+09 |
Annual Sum or Average | 0.175820E+10 | 0.777902E+09 | 0.980301E+09 | 0.310119E+10 | 0.702995E+09 |
Minimum of Months | 74895808.02 | 1097554.60 | 73640903.76 | 0.194949E+09 | 1064251.39 |
Maximum of Months | 0.238875E+09 | 0.157914E+09 | 93543734.09 | 0.376988E+09 | 0.150925E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.206140E+09 | 0.125277E+09 | 80862769.86 | 0.282921E+09 | 0.147060E+09 |
February | 0.177011E+09 | 98324877.05 | 78686512.39 | 0.253776E+09 | 0.109445E+09 |
March | 0.167509E+09 | 73965634.87 | 93543734.09 | 0.260274E+09 | 73674190.18 |
April | 0.113838E+09 | 32090702.63 | 81746939.17 | 0.217293E+09 | 24941299.92 |
May | 84580621.94 | 6213479.77 | 78367142.18 | 0.221546E+09 | 4696494.65 |
June | 74895808.02 | 1254904.26 | 73640903.76 | 0.220138E+09 | 3934157.00 |
July | 80739855.26 | 1097554.60 | 79642300.66 | 0.210130E+09 | 1064251.39 |
August | 85648160.46 | 4561320.68 | 81086839.78 | 0.194949E+09 | 3669935.37 |
September | 0.111112E+09 | 28824581.51 | 82287586.02 | 0.211208E+09 | 13223542.62 |
October | 0.197557E+09 | 0.110312E+09 | 87245272.99 | 0.340076E+09 | 61452697.82 |
November | 0.238875E+09 | 0.157914E+09 | 80961026.03 | 0.376988E+09 | 0.108908E+09 |
December | 0.220296E+09 | 0.138066E+09 | 82229496.04 | 0.311885E+09 | 0.150925E+09 |
Annual Sum or Average | 0.175820E+10 | 0.777902E+09 | 0.980301E+09 | 0.310119E+10 | 0.702995E+09 |
Minimum of Months | 74895808.02 | 1097554.60 | 73640903.76 | 0.194949E+09 | 1064251.39 |
Maximum of Months | 0.238875E+09 | 0.157914E+09 | 93543734.09 | 0.376988E+09 | 0.150925E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_DOOR
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.246825E+09 | 0.150002E+09 | 96822527.06 | 0.338332E+09 | 0.174761E+09 |
February | 0.211948E+09 | 0.117731E+09 | 94216745.09 | 0.303374E+09 | 0.130079E+09 |
March | 0.200570E+09 | 88564115.43 | 0.112006E+09 | 0.310783E+09 | 87685857.42 |
April | 0.136306E+09 | 38424393.94 | 97881203.48 | 0.258856E+09 | 29711751.73 |
May | 0.101274E+09 | 7439824.46 | 93834341.29 | 0.263264E+09 | 5636021.58 |
June | 89677875.40 | 1502582.74 | 88175292.66 | 0.261605E+09 | 4675572.30 |
July | 96675353.01 | 1314177.22 | 95361175.79 | 0.249836E+09 | 1283447.14 |
August | 0.102552E+09 | 5461581.34 | 97090821.32 | 0.232021E+09 | 4388242.49 |
September | 0.133042E+09 | 34513643.65 | 98528556.95 | 0.251694E+09 | 15763699.85 |
October | 0.236549E+09 | 0.132084E+09 | 0.104465E+09 | 0.405784E+09 | 73161657.05 |
November | 0.286022E+09 | 0.189082E+09 | 96940175.90 | 0.450257E+09 | 0.129563E+09 |
December | 0.263775E+09 | 0.165316E+09 | 98459001.84 | 0.372831E+09 | 0.179397E+09 |
Annual Sum or Average | 0.210522E+10 | 0.931436E+09 | 0.117378E+10 | 0.369864E+10 | 0.836106E+09 |
Minimum of Months | 89677875.40 | 1314177.22 | 88175292.66 | 0.232021E+09 | 1283447.14 |
Maximum of Months | 0.286022E+09 | 0.189082E+09 | 0.112006E+09 | 0.450257E+09 | 0.179397E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.206140E+09 | 0.125277E+09 | 80862769.86 | 0.284036E+09 | 0.142906E+09 |
February | 0.177011E+09 | 98324877.05 | 78686512.39 | 0.255010E+09 | 0.105231E+09 |
March | 0.167509E+09 | 73965634.87 | 93543734.09 | 0.260920E+09 | 70432582.73 |
April | 0.113838E+09 | 32090702.63 | 81746939.17 | 0.216569E+09 | 23919154.82 |
May | 84580621.94 | 6213479.77 | 78367142.18 | 0.219034E+09 | 4780101.36 |
June | 74895808.02 | 1254904.26 | 73640903.76 | 0.216498E+09 | 4096741.86 |
July | 80739855.26 | 1097554.60 | 79642300.66 | 0.205118E+09 | 1348347.20 |
August | 85648160.46 | 4561320.68 | 81086839.78 | 0.190564E+09 | 4664621.14 |
September | 0.111112E+09 | 28824581.51 | 82287586.02 | 0.208592E+09 | 15283949.11 |
October | 0.197557E+09 | 0.110312E+09 | 87245272.99 | 0.338577E+09 | 62742776.28 |
November | 0.238875E+09 | 0.157914E+09 | 80961026.03 | 0.376747E+09 | 0.108034E+09 |
December | 0.220296E+09 | 0.138066E+09 | 82229496.04 | 0.312771E+09 | 0.147784E+09 |
Annual Sum or Average | 0.175820E+10 | 0.777902E+09 | 0.980301E+09 | 0.308443E+10 | 0.691223E+09 |
Minimum of Months | 74895808.02 | 1097554.60 | 73640903.76 | 0.190564E+09 | 1348347.20 |
Maximum of Months | 0.238875E+09 | 0.157914E+09 | 93543734.09 | 0.376747E+09 | 0.147784E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.206140E+09 | 0.125277E+09 | 80862769.86 | 0.284036E+09 | 0.142906E+09 |
February | 0.177011E+09 | 98324877.05 | 78686512.39 | 0.255010E+09 | 0.105231E+09 |
March | 0.167509E+09 | 73965634.87 | 93543734.09 | 0.260920E+09 | 70432582.73 |
April | 0.113838E+09 | 32090702.63 | 81746939.17 | 0.216569E+09 | 23919154.82 |
May | 84580621.94 | 6213479.77 | 78367142.18 | 0.219034E+09 | 4780101.36 |
June | 74895808.02 | 1254904.26 | 73640903.76 | 0.216498E+09 | 4096741.86 |
July | 80739855.26 | 1097554.60 | 79642300.66 | 0.205118E+09 | 1348347.20 |
August | 85648160.46 | 4561320.68 | 81086839.78 | 0.190564E+09 | 4664621.14 |
September | 0.111112E+09 | 28824581.51 | 82287586.02 | 0.208592E+09 | 15283949.11 |
October | 0.197557E+09 | 0.110312E+09 | 87245272.99 | 0.338577E+09 | 62742776.28 |
November | 0.238875E+09 | 0.157914E+09 | 80961026.03 | 0.376747E+09 | 0.108034E+09 |
December | 0.220296E+09 | 0.138066E+09 | 82229496.04 | 0.312771E+09 | 0.147784E+09 |
Annual Sum or Average | 0.175820E+10 | 0.777902E+09 | 0.980301E+09 | 0.308443E+10 | 0.691223E+09 |
Minimum of Months | 74895808.02 | 1097554.60 | 73640903.76 | 0.190564E+09 | 1348347.20 |
Maximum of Months | 0.238875E+09 | 0.157914E+09 | 93543734.09 | 0.376747E+09 | 0.147784E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_DOOR
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.246825E+09 | 0.150002E+09 | 96822527.06 | 0.339669E+09 | 0.169832E+09 |
February | 0.211948E+09 | 0.117731E+09 | 94216745.09 | 0.304850E+09 | 0.125083E+09 |
March | 0.200570E+09 | 88564115.43 | 0.112006E+09 | 0.311555E+09 | 83840973.43 |
April | 0.136306E+09 | 38424393.94 | 97881203.48 | 0.257977E+09 | 28495288.36 |
May | 0.101274E+09 | 7439824.46 | 93834341.29 | 0.260245E+09 | 5737280.03 |
June | 89677875.40 | 1502582.74 | 88175292.66 | 0.257236E+09 | 4869132.27 |
July | 96675353.01 | 1314177.22 | 95361175.79 | 0.243839E+09 | 1626810.32 |
August | 0.102552E+09 | 5461581.34 | 97090821.32 | 0.226760E+09 | 5577722.06 |
September | 0.133042E+09 | 34513643.65 | 98528556.95 | 0.248534E+09 | 18216990.06 |
October | 0.236549E+09 | 0.132084E+09 | 0.104465E+09 | 0.403965E+09 | 74700221.87 |
November | 0.286022E+09 | 0.189082E+09 | 96940175.90 | 0.449956E+09 | 0.128526E+09 |
December | 0.263775E+09 | 0.165316E+09 | 98459001.84 | 0.373887E+09 | 0.175669E+09 |
Annual Sum or Average | 0.210522E+10 | 0.931436E+09 | 0.117378E+10 | 0.367847E+10 | 0.822174E+09 |
Minimum of Months | 89677875.40 | 1314177.22 | 88175292.66 | 0.226760E+09 | 1626810.32 |
Maximum of Months | 0.286022E+09 | 0.189082E+09 | 0.112006E+09 | 0.449956E+09 | 0.175669E+09 |
Report: WindowZoneSummaryMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 664.71 | 378.46 | 493.18 | 299.72 | 193.46 | 0.00 | 0.00 |
February | 666.61 | 301.08 | 468.86 | 260.44 | 208.42 | 0.00 | 0.00 |
March | 620.52 | 177.91 | 400.76 | 176.96 | 223.80 | 0.00 | 0.00 |
April | 541.28 | 59.61 | 281.43 | 79.33 | 202.09 | 0.00 | 0.00 |
May | 541.20 | 9.78 | 202.35 | 14.87 | 187.49 | 0.00 | 0.00 |
June | 553.34 | 7.57 | 185.16 | 3.10 | 182.05 | 0.00 | 0.00 |
July | 518.81 | 2.55 | 193.16 | 2.63 | 190.54 | 0.00 | 0.00 |
August | 474.21 | 7.76 | 204.91 | 10.91 | 193.99 | 0.00 | 0.00 |
September | 527.15 | 29.48 | 274.69 | 71.26 | 203.43 | 0.00 | 0.00 |
October | 813.94 | 141.56 | 472.64 | 263.91 | 208.73 | 0.00 | 0.00 |
November | 929.04 | 271.26 | 590.54 | 390.39 | 200.15 | 0.00 | 0.00 |
December | 738.79 | 374.68 | 527.04 | 330.31 | 196.73 | 0.00 | 0.00 |
Annual Sum or Average | 632.13 | 146.14 | 357.25 | 158.06 | 199.19 | 0.00 | 0.00 |
Minimum of Months | 474.21 | 2.55 | 185.16 | 2.63 | 182.05 | 0.00 | 0.00 |
Maximum of Months | 929.04 | 378.46 | 590.54 | 390.39 | 223.80 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 329.80 | 194.39 | 246.59 | 149.86 | 96.73 | 0.00 | 0.00 |
February | 331.42 | 153.58 | 234.43 | 130.22 | 104.21 | 0.00 | 0.00 |
March | 309.44 | 90.49 | 200.38 | 88.48 | 111.90 | 0.00 | 0.00 |
April | 271.29 | 30.42 | 140.71 | 39.67 | 101.05 | 0.00 | 0.00 |
May | 272.61 | 4.93 | 101.18 | 7.43 | 93.74 | 0.00 | 0.00 |
June | 279.47 | 3.78 | 92.58 | 1.55 | 91.03 | 0.00 | 0.00 |
July | 262.48 | 1.17 | 96.58 | 1.31 | 95.27 | 0.00 | 0.00 |
August | 239.88 | 3.54 | 102.45 | 5.46 | 97.00 | 0.00 | 0.00 |
September | 265.42 | 13.94 | 137.34 | 35.63 | 101.71 | 0.00 | 0.00 |
October | 407.63 | 70.29 | 236.32 | 131.96 | 104.36 | 0.00 | 0.00 |
November | 464.05 | 135.99 | 295.27 | 195.20 | 100.08 | 0.00 | 0.00 |
December | 367.68 | 190.15 | 263.52 | 165.16 | 98.36 | 0.00 | 0.00 |
Annual Sum or Average | 316.61 | 74.05 | 178.63 | 79.03 | 99.60 | 0.00 | 0.00 |
Minimum of Months | 239.88 | 1.17 | 92.58 | 1.31 | 91.03 | 0.00 | 0.00 |
Maximum of Months | 464.05 | 194.39 | 295.27 | 195.20 | 111.90 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 331.27 | 189.59 | 246.08 | 149.55 | 96.53 | 0.00 | 0.00 |
February | 331.57 | 153.64 | 233.95 | 129.95 | 104.00 | 0.00 | 0.00 |
March | 308.35 | 94.42 | 199.97 | 88.30 | 111.67 | 0.00 | 0.00 |
April | 265.22 | 34.79 | 140.42 | 39.59 | 100.84 | 0.00 | 0.00 |
May | 260.79 | 6.92 | 100.97 | 7.42 | 93.55 | 0.00 | 0.00 |
June | 267.13 | 5.56 | 92.39 | 1.55 | 90.84 | 0.00 | 0.00 |
July | 248.61 | 1.89 | 96.38 | 1.31 | 95.07 | 0.00 | 0.00 |
August | 230.54 | 5.82 | 102.24 | 5.45 | 96.80 | 0.00 | 0.00 |
September | 259.66 | 19.35 | 137.06 | 35.56 | 101.51 | 0.00 | 0.00 |
October | 405.42 | 77.38 | 235.84 | 131.69 | 104.15 | 0.00 | 0.00 |
November | 463.39 | 139.43 | 294.67 | 194.80 | 99.87 | 0.00 | 0.00 |
December | 368.31 | 188.66 | 262.98 | 164.82 | 98.16 | 0.00 | 0.00 |
Annual Sum or Average | 311.50 | 76.11 | 178.26 | 78.87 | 99.39 | 0.00 | 0.00 |
Minimum of Months | 230.54 | 1.89 | 92.39 | 1.31 | 90.84 | 0.00 | 0.00 |
Maximum of Months | 463.39 | 189.59 | 294.67 | 194.80 | 111.67 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 332.47 | 186.47 | 246.08 | 149.55 | 96.53 | 0.00 | 0.00 |
February | 332.07 | 152.26 | 233.95 | 129.95 | 104.00 | 0.00 | 0.00 |
March | 308.44 | 94.20 | 199.97 | 88.30 | 111.67 | 0.00 | 0.00 |
April | 264.90 | 35.31 | 140.42 | 39.59 | 100.84 | 0.00 | 0.00 |
May | 259.68 | 7.43 | 100.97 | 7.42 | 93.55 | 0.00 | 0.00 |
June | 265.82 | 5.89 | 92.39 | 1.55 | 90.84 | 0.00 | 0.00 |
July | 247.09 | 2.08 | 96.38 | 1.31 | 95.07 | 0.00 | 0.00 |
August | 229.67 | 6.21 | 102.24 | 5.45 | 96.80 | 0.00 | 0.00 |
September | 259.35 | 20.19 | 137.06 | 35.56 | 101.51 | 0.00 | 0.00 |
October | 405.29 | 77.96 | 235.84 | 131.69 | 104.15 | 0.00 | 0.00 |
November | 463.55 | 139.01 | 294.67 | 194.80 | 99.87 | 0.00 | 0.00 |
December | 368.98 | 186.93 | 262.98 | 164.82 | 98.16 | 0.00 | 0.00 |
Annual Sum or Average | 311.25 | 75.82 | 178.26 | 78.87 | 99.39 | 0.00 | 0.00 |
Minimum of Months | 229.67 | 2.08 | 92.39 | 1.31 | 90.84 | 0.00 | 0.00 |
Maximum of Months | 463.55 | 186.93 | 294.67 | 194.80 | 111.67 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 333.72 | 183.67 | 246.08 | 149.55 | 96.53 | 0.00 | 0.00 |
February | 332.75 | 150.63 | 233.95 | 129.95 | 104.00 | 0.00 | 0.00 |
March | 308.82 | 93.10 | 199.97 | 88.30 | 111.67 | 0.00 | 0.00 |
April | 265.35 | 34.56 | 140.42 | 39.59 | 100.84 | 0.00 | 0.00 |
May | 260.29 | 7.11 | 100.97 | 7.42 | 93.55 | 0.00 | 0.00 |
June | 266.59 | 5.71 | 92.39 | 1.55 | 90.84 | 0.00 | 0.00 |
July | 247.66 | 1.92 | 96.38 | 1.31 | 95.07 | 0.00 | 0.00 |
August | 230.19 | 5.87 | 102.24 | 5.45 | 96.80 | 0.00 | 0.00 |
September | 259.60 | 19.49 | 137.06 | 35.56 | 101.51 | 0.00 | 0.00 |
October | 405.50 | 77.16 | 235.84 | 131.69 | 104.15 | 0.00 | 0.00 |
November | 463.89 | 138.03 | 294.67 | 194.80 | 99.87 | 0.00 | 0.00 |
December | 369.75 | 185.29 | 262.98 | 164.82 | 98.16 | 0.00 | 0.00 |
Annual Sum or Average | 311.82 | 74.87 | 178.26 | 78.87 | 99.39 | 0.00 | 0.00 |
Minimum of Months | 230.19 | 1.92 | 92.39 | 1.31 | 90.84 | 0.00 | 0.00 |
Maximum of Months | 463.89 | 185.29 | 294.67 | 194.80 | 111.67 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 672.52 | 357.48 | 492.16 | 299.10 | 193.06 | 0.00 | 0.00 |
February | 668.55 | 294.55 | 467.90 | 259.90 | 207.99 | 0.00 | 0.00 |
March | 619.06 | 180.38 | 399.93 | 176.59 | 223.34 | 0.00 | 0.00 |
April | 531.44 | 64.77 | 280.85 | 79.17 | 201.68 | 0.00 | 0.00 |
May | 521.73 | 12.61 | 201.94 | 14.83 | 187.10 | 0.00 | 0.00 |
June | 535.67 | 10.49 | 184.78 | 3.10 | 181.68 | 0.00 | 0.00 |
July | 495.53 | 3.05 | 192.77 | 2.62 | 190.15 | 0.00 | 0.00 |
August | 460.99 | 9.81 | 204.49 | 10.89 | 193.60 | 0.00 | 0.00 |
September | 518.26 | 34.88 | 274.13 | 71.11 | 203.01 | 0.00 | 0.00 |
October | 810.01 | 149.38 | 471.67 | 263.37 | 208.30 | 0.00 | 0.00 |
November | 928.65 | 271.40 | 589.33 | 389.59 | 199.74 | 0.00 | 0.00 |
December | 742.62 | 364.14 | 525.96 | 329.64 | 196.32 | 0.00 | 0.00 |
Annual Sum or Average | 625.03 | 145.41 | 356.52 | 157.74 | 198.78 | 0.00 | 0.00 |
Minimum of Months | 460.99 | 3.05 | 184.78 | 2.62 | 181.68 | 0.00 | 0.00 |
Maximum of Months | 928.65 | 364.14 | 589.33 | 389.59 | 223.34 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 336.10 | 178.13 | 246.08 | 149.55 | 96.53 | 0.00 | 0.00 |
February | 333.97 | 146.81 | 233.95 | 129.95 | 104.00 | 0.00 | 0.00 |
March | 309.65 | 89.34 | 199.97 | 88.30 | 111.67 | 0.00 | 0.00 |
April | 266.98 | 31.49 | 140.42 | 39.59 | 100.84 | 0.00 | 0.00 |
May | 263.37 | 5.80 | 100.97 | 7.42 | 93.55 | 0.00 | 0.00 |
June | 270.63 | 4.94 | 92.39 | 1.55 | 90.84 | 0.00 | 0.00 |
July | 250.37 | 1.30 | 96.38 | 1.31 | 95.07 | 0.00 | 0.00 |
August | 232.41 | 4.38 | 102.24 | 5.45 | 96.80 | 0.00 | 0.00 |
September | 260.15 | 16.31 | 137.06 | 35.56 | 101.51 | 0.00 | 0.00 |
October | 405.35 | 73.52 | 235.84 | 131.69 | 104.15 | 0.00 | 0.00 |
November | 464.17 | 134.95 | 294.67 | 194.80 | 99.87 | 0.00 | 0.00 |
December | 370.99 | 181.72 | 262.98 | 164.82 | 98.16 | 0.00 | 0.00 |
Annual Sum or Average | 313.49 | 72.06 | 178.26 | 78.87 | 99.39 | 0.00 | 0.00 |
Minimum of Months | 232.41 | 1.30 | 92.39 | 1.31 | 90.84 | 0.00 | 0.00 |
Maximum of Months | 464.17 | 181.72 | 294.67 | 194.80 | 111.67 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 336.61 | 177.15 | 246.08 | 149.55 | 96.53 | 0.00 | 0.00 |
February | 334.35 | 146.09 | 233.95 | 129.95 | 104.00 | 0.00 | 0.00 |
March | 309.90 | 88.87 | 199.97 | 88.30 | 111.67 | 0.00 | 0.00 |
April | 267.29 | 31.19 | 140.42 | 39.59 | 100.84 | 0.00 | 0.00 |
May | 263.78 | 5.68 | 100.97 | 7.42 | 93.55 | 0.00 | 0.00 |
June | 271.07 | 4.86 | 92.39 | 1.55 | 90.84 | 0.00 | 0.00 |
July | 250.77 | 1.26 | 96.38 | 1.31 | 95.07 | 0.00 | 0.00 |
August | 232.73 | 4.28 | 102.24 | 5.45 | 96.80 | 0.00 | 0.00 |
September | 260.35 | 16.08 | 137.06 | 35.56 | 101.51 | 0.00 | 0.00 |
October | 405.51 | 73.23 | 235.84 | 131.69 | 104.15 | 0.00 | 0.00 |
November | 464.36 | 134.58 | 294.67 | 194.80 | 99.87 | 0.00 | 0.00 |
December | 371.34 | 181.11 | 262.98 | 164.82 | 98.16 | 0.00 | 0.00 |
Annual Sum or Average | 313.82 | 71.70 | 178.26 | 78.87 | 99.39 | 0.00 | 0.00 |
Minimum of Months | 232.73 | 1.26 | 92.39 | 1.31 | 90.84 | 0.00 | 0.00 |
Maximum of Months | 464.36 | 181.11 | 294.67 | 194.80 | 111.67 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 337.58 | 175.06 | 246.08 | 149.55 | 96.53 | 0.00 | 0.00 |
February | 335.20 | 144.25 | 233.95 | 129.95 | 104.00 | 0.00 | 0.00 |
March | 310.38 | 87.75 | 199.97 | 88.30 | 111.67 | 0.00 | 0.00 |
April | 267.53 | 30.71 | 140.42 | 39.59 | 100.84 | 0.00 | 0.00 |
May | 263.72 | 5.61 | 100.97 | 7.42 | 93.55 | 0.00 | 0.00 |
June | 270.79 | 4.84 | 92.39 | 1.55 | 90.84 | 0.00 | 0.00 |
July | 250.19 | 1.27 | 96.38 | 1.31 | 95.07 | 0.00 | 0.00 |
August | 232.20 | 4.38 | 102.24 | 5.45 | 96.80 | 0.00 | 0.00 |
September | 260.07 | 16.29 | 137.06 | 35.56 | 101.51 | 0.00 | 0.00 |
October | 405.44 | 73.20 | 235.84 | 131.69 | 104.15 | 0.00 | 0.00 |
November | 464.60 | 134.02 | 294.67 | 194.80 | 99.87 | 0.00 | 0.00 |
December | 372.09 | 179.68 | 262.98 | 164.82 | 98.16 | 0.00 | 0.00 |
Annual Sum or Average | 313.96 | 71.10 | 178.26 | 78.87 | 99.39 | 0.00 | 0.00 |
Minimum of Months | 232.20 | 1.27 | 92.39 | 1.31 | 90.84 | 0.00 | 0.00 |
Maximum of Months | 464.60 | 179.68 | 294.67 | 194.80 | 111.67 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 338.91 | 170.12 | 246.08 | 149.55 | 96.53 | 0.00 | 0.00 |
February | 336.83 | 138.70 | 233.95 | 129.95 | 104.00 | 0.00 | 0.00 |
March | 311.15 | 83.90 | 199.97 | 88.30 | 111.67 | 0.00 | 0.00 |
April | 266.63 | 29.45 | 140.42 | 39.59 | 100.84 | 0.00 | 0.00 |
May | 260.72 | 5.71 | 100.97 | 7.42 | 93.55 | 0.00 | 0.00 |
June | 266.29 | 5.04 | 92.39 | 1.55 | 90.84 | 0.00 | 0.00 |
July | 244.20 | 1.61 | 96.38 | 1.31 | 95.07 | 0.00 | 0.00 |
August | 226.96 | 5.57 | 102.24 | 5.45 | 96.80 | 0.00 | 0.00 |
September | 256.84 | 18.82 | 137.06 | 35.56 | 101.51 | 0.00 | 0.00 |
October | 403.64 | 74.74 | 235.84 | 131.69 | 104.15 | 0.00 | 0.00 |
November | 464.29 | 132.95 | 294.67 | 194.80 | 99.87 | 0.00 | 0.00 |
December | 373.14 | 175.94 | 262.98 | 164.82 | 98.16 | 0.00 | 0.00 |
Annual Sum or Average | 312.26 | 69.91 | 178.26 | 78.87 | 99.39 | 0.00 | 0.00 |
Minimum of Months | 226.96 | 1.61 | 92.39 | 1.31 | 90.84 | 0.00 | 0.00 |
Maximum of Months | 464.29 | 175.94 | 294.67 | 194.80 | 111.67 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.178037E+10 | 0.101367E+10 | 0.132092E+10 | 0.802760E+09 | 0.518160E+09 | 0.00 | 0.00 |
February | 0.161267E+10 | 0.728384E+09 | 0.113427E+10 | 0.630055E+09 | 0.504215E+09 | 0.00 | 0.00 |
March | 0.166199E+10 | 0.476514E+09 | 0.107338E+10 | 0.473964E+09 | 0.599418E+09 | 0.00 | 0.00 |
April | 0.140300E+10 | 0.154520E+09 | 0.729460E+09 | 0.205634E+09 | 0.523826E+09 | 0.00 | 0.00 |
May | 0.144956E+10 | 26192764.26 | 0.541984E+09 | 39815324.31 | 0.502168E+09 | 0.00 | 0.00 |
June | 0.143425E+10 | 19616354.43 | 0.479924E+09 | 8041294.43 | 0.471883E+09 | 0.00 | 0.00 |
July | 0.138957E+10 | 6833577.82 | 0.517372E+09 | 7033014.36 | 0.510339E+09 | 0.00 | 0.00 |
August | 0.127012E+10 | 20787304.01 | 0.548824E+09 | 29228462.76 | 0.519596E+09 | 0.00 | 0.00 |
September | 0.136638E+10 | 76411646.06 | 0.711995E+09 | 0.184705E+09 | 0.527290E+09 | 0.00 | 0.00 |
October | 0.218005E+10 | 0.379148E+09 | 0.126592E+10 | 0.706866E+09 | 0.559059E+09 | 0.00 | 0.00 |
November | 0.240807E+10 | 0.703099E+09 | 0.153069E+10 | 0.101190E+10 | 0.518790E+09 | 0.00 | 0.00 |
December | 0.197876E+10 | 0.100355E+10 | 0.141163E+10 | 0.884714E+09 | 0.526918E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.199348E+11 | 0.460873E+10 | 0.112664E+11 | 0.498472E+10 | 0.628166E+10 | 0.00 | 0.00 |
Minimum of Months | 0.127012E+10 | 6833577.82 | 0.479924E+09 | 7033014.36 | 0.471883E+09 | 0.00 | 0.00 |
Maximum of Months | 0.240807E+10 | 0.101367E+10 | 0.153069E+10 | 0.101190E+10 | 0.599418E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.883336E+09 | 0.520642E+09 | 0.660460E+09 | 0.401380E+09 | 0.259080E+09 | 0.00 | 0.00 |
February | 0.801779E+09 | 0.371536E+09 | 0.567135E+09 | 0.315028E+09 | 0.252107E+09 | 0.00 | 0.00 |
March | 0.828796E+09 | 0.242362E+09 | 0.536691E+09 | 0.236982E+09 | 0.299709E+09 | 0.00 | 0.00 |
April | 0.703181E+09 | 78857331.76 | 0.364730E+09 | 0.102817E+09 | 0.261913E+09 | 0.00 | 0.00 |
May | 0.730166E+09 | 13202935.00 | 0.270992E+09 | 19907662.15 | 0.251084E+09 | 0.00 | 0.00 |
June | 0.724392E+09 | 9804439.77 | 0.239962E+09 | 4020647.22 | 0.235942E+09 | 0.00 | 0.00 |
July | 0.703027E+09 | 3141313.41 | 0.258686E+09 | 3516507.18 | 0.255170E+09 | 0.00 | 0.00 |
August | 0.642498E+09 | 9468217.05 | 0.274412E+09 | 14614231.38 | 0.259798E+09 | 0.00 | 0.00 |
September | 0.687964E+09 | 36128156.16 | 0.355998E+09 | 92352442.07 | 0.263645E+09 | 0.00 | 0.00 |
October | 0.109178E+10 | 0.188268E+09 | 0.632962E+09 | 0.353433E+09 | 0.279529E+09 | 0.00 | 0.00 |
November | 0.120281E+10 | 0.352483E+09 | 0.765344E+09 | 0.505950E+09 | 0.259395E+09 | 0.00 | 0.00 |
December | 0.984806E+09 | 0.509310E+09 | 0.705816E+09 | 0.442357E+09 | 0.263459E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.998454E+10 | 0.233520E+10 | 0.563319E+10 | 0.249236E+10 | 0.314083E+10 | 0.00 | 0.00 |
Minimum of Months | 0.642498E+09 | 3141313.41 | 0.239962E+09 | 3516507.18 | 0.235942E+09 | 0.00 | 0.00 |
Maximum of Months | 0.120281E+10 | 0.520642E+09 | 0.765344E+09 | 0.505950E+09 | 0.299709E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.887285E+09 | 0.507794E+09 | 0.659104E+09 | 0.400556E+09 | 0.258548E+09 | 0.00 | 0.00 |
February | 0.802131E+09 | 0.371688E+09 | 0.565971E+09 | 0.314381E+09 | 0.251590E+09 | 0.00 | 0.00 |
March | 0.825893E+09 | 0.252894E+09 | 0.535589E+09 | 0.236495E+09 | 0.299094E+09 | 0.00 | 0.00 |
April | 0.687453E+09 | 90163221.09 | 0.363981E+09 | 0.102606E+09 | 0.261375E+09 | 0.00 | 0.00 |
May | 0.698494E+09 | 18526697.27 | 0.270435E+09 | 19866784.00 | 0.250569E+09 | 0.00 | 0.00 |
June | 0.692404E+09 | 14414375.55 | 0.239469E+09 | 4012391.27 | 0.235457E+09 | 0.00 | 0.00 |
July | 0.665878E+09 | 5059322.64 | 0.258155E+09 | 3509286.43 | 0.254646E+09 | 0.00 | 0.00 |
August | 0.617491E+09 | 15580398.22 | 0.273849E+09 | 14584222.69 | 0.259265E+09 | 0.00 | 0.00 |
September | 0.673046E+09 | 50144383.72 | 0.355267E+09 | 92162806.66 | 0.263104E+09 | 0.00 | 0.00 |
October | 0.108588E+10 | 0.207249E+09 | 0.631663E+09 | 0.352707E+09 | 0.278955E+09 | 0.00 | 0.00 |
November | 0.120111E+10 | 0.361413E+09 | 0.763773E+09 | 0.504911E+09 | 0.258862E+09 | 0.00 | 0.00 |
December | 0.986487E+09 | 0.505305E+09 | 0.704367E+09 | 0.441449E+09 | 0.262918E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.982356E+10 | 0.240023E+10 | 0.562162E+10 | 0.248724E+10 | 0.313438E+10 | 0.00 | 0.00 |
Minimum of Months | 0.617491E+09 | 5059322.64 | 0.239469E+09 | 3509286.43 | 0.235457E+09 | 0.00 | 0.00 |
Maximum of Months | 0.120111E+10 | 0.507794E+09 | 0.763773E+09 | 0.504911E+09 | 0.299094E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.890486E+09 | 0.499428E+09 | 0.659104E+09 | 0.400556E+09 | 0.258548E+09 | 0.00 | 0.00 |
February | 0.803346E+09 | 0.368346E+09 | 0.565971E+09 | 0.314381E+09 | 0.251590E+09 | 0.00 | 0.00 |
March | 0.826138E+09 | 0.252311E+09 | 0.535589E+09 | 0.236495E+09 | 0.299094E+09 | 0.00 | 0.00 |
April | 0.686624E+09 | 91536069.88 | 0.363981E+09 | 0.102606E+09 | 0.261375E+09 | 0.00 | 0.00 |
May | 0.695538E+09 | 19892274.07 | 0.270435E+09 | 19866784.00 | 0.250569E+09 | 0.00 | 0.00 |
June | 0.689001E+09 | 15274209.39 | 0.239469E+09 | 4012391.27 | 0.235457E+09 | 0.00 | 0.00 |
July | 0.661799E+09 | 5566937.80 | 0.258155E+09 | 3509286.43 | 0.254646E+09 | 0.00 | 0.00 |
August | 0.615156E+09 | 16624817.02 | 0.273849E+09 | 14584222.69 | 0.259265E+09 | 0.00 | 0.00 |
September | 0.672234E+09 | 52322735.49 | 0.355267E+09 | 92162806.66 | 0.263104E+09 | 0.00 | 0.00 |
October | 0.108554E+10 | 0.208814E+09 | 0.631663E+09 | 0.352707E+09 | 0.278955E+09 | 0.00 | 0.00 |
November | 0.120151E+10 | 0.360324E+09 | 0.763773E+09 | 0.504911E+09 | 0.258862E+09 | 0.00 | 0.00 |
December | 0.988279E+09 | 0.500687E+09 | 0.704367E+09 | 0.441449E+09 | 0.262918E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.981565E+10 | 0.239113E+10 | 0.562162E+10 | 0.248724E+10 | 0.313438E+10 | 0.00 | 0.00 |
Minimum of Months | 0.615156E+09 | 5566937.80 | 0.239469E+09 | 3509286.43 | 0.235457E+09 | 0.00 | 0.00 |
Maximum of Months | 0.120151E+10 | 0.500687E+09 | 0.763773E+09 | 0.504911E+09 | 0.299094E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.893834E+09 | 0.491929E+09 | 0.659104E+09 | 0.400556E+09 | 0.258548E+09 | 0.00 | 0.00 |
February | 0.804979E+09 | 0.364408E+09 | 0.565971E+09 | 0.314381E+09 | 0.251590E+09 | 0.00 | 0.00 |
March | 0.827157E+09 | 0.249357E+09 | 0.535589E+09 | 0.236495E+09 | 0.299094E+09 | 0.00 | 0.00 |
April | 0.687780E+09 | 89586564.70 | 0.363981E+09 | 0.102606E+09 | 0.261375E+09 | 0.00 | 0.00 |
May | 0.697158E+09 | 19048981.84 | 0.270435E+09 | 19866784.00 | 0.250569E+09 | 0.00 | 0.00 |
June | 0.691003E+09 | 14805561.04 | 0.239469E+09 | 4012391.27 | 0.235457E+09 | 0.00 | 0.00 |
July | 0.663345E+09 | 5150563.32 | 0.258155E+09 | 3509286.43 | 0.254646E+09 | 0.00 | 0.00 |
August | 0.616537E+09 | 15724123.68 | 0.273849E+09 | 14584222.69 | 0.259265E+09 | 0.00 | 0.00 |
September | 0.672877E+09 | 50515979.91 | 0.355267E+09 | 92162806.66 | 0.263104E+09 | 0.00 | 0.00 |
October | 0.108608E+10 | 0.206666E+09 | 0.631663E+09 | 0.352707E+09 | 0.278955E+09 | 0.00 | 0.00 |
November | 0.120240E+10 | 0.357767E+09 | 0.763773E+09 | 0.504911E+09 | 0.258862E+09 | 0.00 | 0.00 |
December | 0.990350E+09 | 0.496274E+09 | 0.704367E+09 | 0.441449E+09 | 0.262918E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.983350E+10 | 0.236123E+10 | 0.562162E+10 | 0.248724E+10 | 0.313438E+10 | 0.00 | 0.00 |
Minimum of Months | 0.616537E+09 | 5150563.32 | 0.239469E+09 | 3509286.43 | 0.235457E+09 | 0.00 | 0.00 |
Maximum of Months | 0.120240E+10 | 0.496274E+09 | 0.763773E+09 | 0.504911E+09 | 0.299094E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.180127E+10 | 0.957484E+09 | 0.131821E+10 | 0.801112E+09 | 0.517096E+09 | 0.00 | 0.00 |
February | 0.161737E+10 | 0.712577E+09 | 0.113194E+10 | 0.628762E+09 | 0.503180E+09 | 0.00 | 0.00 |
March | 0.165808E+10 | 0.483124E+09 | 0.107118E+10 | 0.472991E+09 | 0.598188E+09 | 0.00 | 0.00 |
April | 0.137749E+10 | 0.167877E+09 | 0.727962E+09 | 0.205212E+09 | 0.522750E+09 | 0.00 | 0.00 |
May | 0.139739E+10 | 33781027.82 | 0.540871E+09 | 39733568.00 | 0.501137E+09 | 0.00 | 0.00 |
June | 0.138845E+10 | 27199005.42 | 0.478939E+09 | 8024782.53 | 0.470914E+09 | 0.00 | 0.00 |
July | 0.132723E+10 | 8175244.72 | 0.516310E+09 | 7018572.86 | 0.509292E+09 | 0.00 | 0.00 |
August | 0.123472E+10 | 26285635.68 | 0.547697E+09 | 29168445.38 | 0.518529E+09 | 0.00 | 0.00 |
September | 0.134332E+10 | 90396920.29 | 0.710533E+09 | 0.184326E+09 | 0.526207E+09 | 0.00 | 0.00 |
October | 0.216953E+10 | 0.400087E+09 | 0.126333E+10 | 0.705415E+09 | 0.557911E+09 | 0.00 | 0.00 |
November | 0.240705E+10 | 0.703469E+09 | 0.152755E+10 | 0.100982E+10 | 0.517724E+09 | 0.00 | 0.00 |
December | 0.198903E+10 | 0.975309E+09 | 0.140873E+10 | 0.882898E+09 | 0.525836E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.197109E+11 | 0.458577E+10 | 0.112432E+11 | 0.497448E+10 | 0.626876E+10 | 0.00 | 0.00 |
Minimum of Months | 0.123472E+10 | 8175244.72 | 0.478939E+09 | 7018572.86 | 0.470914E+09 | 0.00 | 0.00 |
Maximum of Months | 0.240705E+10 | 0.975309E+09 | 0.152755E+10 | 0.100982E+10 | 0.598188E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.900214E+09 | 0.477107E+09 | 0.659104E+09 | 0.400556E+09 | 0.258548E+09 | 0.00 | 0.00 |
February | 0.807946E+09 | 0.355153E+09 | 0.565971E+09 | 0.314381E+09 | 0.251590E+09 | 0.00 | 0.00 |
March | 0.829354E+09 | 0.239287E+09 | 0.535589E+09 | 0.236495E+09 | 0.299094E+09 | 0.00 | 0.00 |
April | 0.692008E+09 | 81627061.44 | 0.363981E+09 | 0.102606E+09 | 0.261375E+09 | 0.00 | 0.00 |
May | 0.705422E+09 | 15546224.23 | 0.270435E+09 | 19866784.00 | 0.250569E+09 | 0.00 | 0.00 |
June | 0.701476E+09 | 12804985.79 | 0.239469E+09 | 4012391.27 | 0.235457E+09 | 0.00 | 0.00 |
July | 0.670599E+09 | 3472779.78 | 0.258155E+09 | 3509286.43 | 0.254646E+09 | 0.00 | 0.00 |
August | 0.622494E+09 | 11731363.18 | 0.273849E+09 | 14584222.69 | 0.259265E+09 | 0.00 | 0.00 |
September | 0.674304E+09 | 42267251.29 | 0.355267E+09 | 92162806.66 | 0.263104E+09 | 0.00 | 0.00 |
October | 0.108568E+10 | 0.196926E+09 | 0.631663E+09 | 0.352707E+09 | 0.278955E+09 | 0.00 | 0.00 |
November | 0.120313E+10 | 0.349781E+09 | 0.763773E+09 | 0.504911E+09 | 0.258862E+09 | 0.00 | 0.00 |
December | 0.993667E+09 | 0.486718E+09 | 0.704367E+09 | 0.441449E+09 | 0.262918E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.988630E+10 | 0.227242E+10 | 0.562162E+10 | 0.248724E+10 | 0.313438E+10 | 0.00 | 0.00 |
Minimum of Months | 0.622494E+09 | 3472779.78 | 0.239469E+09 | 3509286.43 | 0.235457E+09 | 0.00 | 0.00 |
Maximum of Months | 0.120313E+10 | 0.486718E+09 | 0.763773E+09 | 0.504911E+09 | 0.299094E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.901574E+09 | 0.474472E+09 | 0.659104E+09 | 0.400556E+09 | 0.258548E+09 | 0.00 | 0.00 |
February | 0.808849E+09 | 0.353421E+09 | 0.565971E+09 | 0.314381E+09 | 0.251590E+09 | 0.00 | 0.00 |
March | 0.830037E+09 | 0.238043E+09 | 0.535589E+09 | 0.236495E+09 | 0.299094E+09 | 0.00 | 0.00 |
April | 0.692822E+09 | 80834019.06 | 0.363981E+09 | 0.102606E+09 | 0.261375E+09 | 0.00 | 0.00 |
May | 0.706503E+09 | 15218347.83 | 0.270435E+09 | 19866784.00 | 0.250569E+09 | 0.00 | 0.00 |
June | 0.702622E+09 | 12601644.13 | 0.239469E+09 | 4012391.27 | 0.235457E+09 | 0.00 | 0.00 |
July | 0.671663E+09 | 3362209.41 | 0.258155E+09 | 3509286.43 | 0.254646E+09 | 0.00 | 0.00 |
August | 0.623343E+09 | 11471217.62 | 0.273849E+09 | 14584222.69 | 0.259265E+09 | 0.00 | 0.00 |
September | 0.674837E+09 | 41687145.86 | 0.355267E+09 | 92162806.66 | 0.263104E+09 | 0.00 | 0.00 |
October | 0.108611E+10 | 0.196133E+09 | 0.631663E+09 | 0.352707E+09 | 0.278955E+09 | 0.00 | 0.00 |
November | 0.120361E+10 | 0.348843E+09 | 0.763773E+09 | 0.504911E+09 | 0.258862E+09 | 0.00 | 0.00 |
December | 0.994597E+09 | 0.485078E+09 | 0.704367E+09 | 0.441449E+09 | 0.262918E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.989657E+10 | 0.226116E+10 | 0.562162E+10 | 0.248724E+10 | 0.313438E+10 | 0.00 | 0.00 |
Minimum of Months | 0.623343E+09 | 3362209.41 | 0.239469E+09 | 3509286.43 | 0.235457E+09 | 0.00 | 0.00 |
Maximum of Months | 0.120361E+10 | 0.485078E+09 | 0.763773E+09 | 0.504911E+09 | 0.299094E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.904175E+09 | 0.468881E+09 | 0.659104E+09 | 0.400556E+09 | 0.258548E+09 | 0.00 | 0.00 |
February | 0.810927E+09 | 0.348970E+09 | 0.565971E+09 | 0.314381E+09 | 0.251590E+09 | 0.00 | 0.00 |
March | 0.831331E+09 | 0.235034E+09 | 0.535589E+09 | 0.236495E+09 | 0.299094E+09 | 0.00 | 0.00 |
April | 0.693442E+09 | 79594248.13 | 0.363981E+09 | 0.102606E+09 | 0.261375E+09 | 0.00 | 0.00 |
May | 0.706355E+09 | 15028382.52 | 0.270435E+09 | 19866784.00 | 0.250569E+09 | 0.00 | 0.00 |
June | 0.701881E+09 | 12543803.26 | 0.239469E+09 | 4012391.27 | 0.235457E+09 | 0.00 | 0.00 |
July | 0.670096E+09 | 3411874.22 | 0.258155E+09 | 3509286.43 | 0.254646E+09 | 0.00 | 0.00 |
August | 0.621920E+09 | 11728066.75 | 0.273849E+09 | 14584222.69 | 0.259265E+09 | 0.00 | 0.00 |
September | 0.674111E+09 | 42210781.22 | 0.355267E+09 | 92162806.66 | 0.263104E+09 | 0.00 | 0.00 |
October | 0.108594E+10 | 0.196067E+09 | 0.631663E+09 | 0.352707E+09 | 0.278955E+09 | 0.00 | 0.00 |
November | 0.120423E+10 | 0.347378E+09 | 0.763773E+09 | 0.504911E+09 | 0.258862E+09 | 0.00 | 0.00 |
December | 0.996600E+09 | 0.481247E+09 | 0.704367E+09 | 0.441449E+09 | 0.262918E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.990101E+10 | 0.224209E+10 | 0.562162E+10 | 0.248724E+10 | 0.313438E+10 | 0.00 | 0.00 |
Minimum of Months | 0.621920E+09 | 3411874.22 | 0.239469E+09 | 3509286.43 | 0.235457E+09 | 0.00 | 0.00 |
Maximum of Months | 0.120423E+10 | 0.481247E+09 | 0.763773E+09 | 0.504911E+09 | 0.299094E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.907740E+09 | 0.455643E+09 | 0.659104E+09 | 0.400556E+09 | 0.258548E+09 | 0.00 | 0.00 |
February | 0.814869E+09 | 0.335544E+09 | 0.565971E+09 | 0.314381E+09 | 0.251590E+09 | 0.00 | 0.00 |
March | 0.833394E+09 | 0.224706E+09 | 0.535589E+09 | 0.236495E+09 | 0.299094E+09 | 0.00 | 0.00 |
April | 0.691115E+09 | 76333401.57 | 0.363981E+09 | 0.102606E+09 | 0.261375E+09 | 0.00 | 0.00 |
May | 0.698313E+09 | 15297267.33 | 0.270435E+09 | 19866784.00 | 0.250569E+09 | 0.00 | 0.00 |
June | 0.690232E+09 | 13062602.52 | 0.239469E+09 | 4012391.27 | 0.235457E+09 | 0.00 | 0.00 |
July | 0.654075E+09 | 4323470.03 | 0.258155E+09 | 3509286.43 | 0.254646E+09 | 0.00 | 0.00 |
August | 0.607887E+09 | 14906798.36 | 0.273849E+09 | 14584222.69 | 0.259265E+09 | 0.00 | 0.00 |
September | 0.665718E+09 | 48784650.09 | 0.355267E+09 | 92162806.66 | 0.263104E+09 | 0.00 | 0.00 |
October | 0.108112E+10 | 0.200185E+09 | 0.631663E+09 | 0.352707E+09 | 0.278955E+09 | 0.00 | 0.00 |
November | 0.120345E+10 | 0.344595E+09 | 0.763773E+09 | 0.504911E+09 | 0.258862E+09 | 0.00 | 0.00 |
December | 0.999429E+09 | 0.471236E+09 | 0.704367E+09 | 0.441449E+09 | 0.262918E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.984734E+10 | 0.220462E+10 | 0.562162E+10 | 0.248724E+10 | 0.313438E+10 | 0.00 | 0.00 |
Minimum of Months | 0.607887E+09 | 4323470.03 | 0.239469E+09 | 3509286.43 | 0.235457E+09 | 0.00 | 0.00 |
Maximum of Months | 0.120345E+10 | 0.471236E+09 | 0.763773E+09 | 0.504911E+09 | 0.299094E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 13.39 | 10.37 | 7.87 | 1.20 | 0.37 | 63.33 | 149.51 | 0.00 |
February | 16.97 | 12.77 | 9.69 | 1.81 | 4.63 | 75.94 | 163.32 | 0.01 |
March | 22.37 | 15.59 | 11.23 | 1.86 | 10.07 | 92.70 | 193.23 | 0.00 |
April | 29.13 | 18.31 | 11.93 | 1.64 | 16.17 | 89.20 | 259.84 | 0.01 |
May | 32.98 | 21.95 | 16.72 | 2.17 | 21.14 | 97.31 | 248.85 | 0.02 |
June | 33.59 | 24.37 | 20.62 | 1.55 | 23.45 | 107.22 | 203.36 | 0.06 |
July | 31.67 | 26.28 | 24.51 | 2.27 | 24.88 | 132.35 | 83.14 | 0.02 |
August | 30.03 | 26.31 | 25.11 | 1.75 | 23.81 | 127.44 | 60.46 | 0.00 |
September | 28.75 | 24.69 | 23.21 | 1.33 | 20.22 | 105.62 | 105.60 | 0.08 |
October | 25.09 | 18.73 | 15.36 | 0.77 | 12.83 | 75.09 | 190.08 | 0.00 |
November | 19.63 | 14.45 | 10.99 | 0.66 | 5.78 | 58.54 | 201.10 | 0.00 |
December | 14.52 | 10.87 | 7.89 | 0.97 | 0.94 | 60.91 | 153.60 | 0.01 |
Annual Sum or Average | 24.88 | 18.75 | 15.46 | 1.50 | 13.74 | 90.59 | 167.44 | 0.02 |
Minimum of Months | 13.39 | 10.37 | 7.87 | 0.66 | 0.37 | 58.54 | 60.46 | 0.00 |
Maximum of Months | 33.59 | 26.31 | 25.11 | 2.27 | 24.88 | 132.35 | 259.84 | 0.08 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 23.60 | 12-JAN-14:00 | 14.18 | 7.40 | 3.80 | 8.15 | 163.00 | 476.00 |
February | 27.10 | 22-FEB-14:00 | 16.17 | 9.10 | 1.50 | 15.39 | 225.00 | 451.00 |
March | 35.60 | 28-MAR-14:00 | 18.47 | 7.70 | 0.00 | 19.52 | 182.00 | 699.00 |
April | 40.30 | 15-APR-14:00 | 20.63 | 10.00 | 6.70 | 28.43 | 201.00 | 649.50 |
May | 44.50 | 03-MAY-14:00 | 20.60 | 5.30 | 2.80 | 28.91 | 150.00 | 809.00 |
June | 44.60 | 07-JUN-15:00 | 21.49 | 9.10 | 3.10 | 28.43 | 167.00 | 640.50 |
July | 40.40 | 02-JUL-15:00 | 26.34 | 21.60 | 2.10 | 29.87 | 200.00 | 545.50 |
August | 37.30 | 07-AUG-14:00 | 26.56 | 22.90 | 3.00 | 29.87 | 311.00 | 370.00 |
September | 37.50 | 17-SEP-19:00 | 27.67 | 24.60 | 0.20 | 28.59 | 0.00 | 0.00 |
October | 36.40 | 02-OCT-14:20 | 21.02 | 13.00 | 1.80 | 21.61 | 187.33 | 678.83 |
November | 30.30 | 04-NOV-13:00 | 17.14 | 8.90 | 1.10 | 14.84 | 155.00 | 710.00 |
December | 24.60 | 28-DEC-13:00 | 15.28 | 8.90 | 2.80 | 10.88 | 181.50 | 535.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 23.60 | 14.18 | 5.30 | 0.00 | 8.15 | 0.00 | 0.00 | |
Maximum of Months | 44.60 | 27.67 | 24.60 | 6.70 | 29.87 | 311.00 | 809.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 4.80 | 05-JAN-06:00 | 4.73 | 4.60 | 0.00 | -10.2 | 0.00 | 0.00 |
February | 6.90 | 02-FEB-05:00 | 6.67 | 6.50 | 0.00 | -7.8 | 0.00 | 0.00 |
March | 13.30 | 01-MAR-03:00 | 10.55 | 8.30 | 0.80 | -1.4 | 0.00 | 0.00 |
April | 17.40 | 11-APR-04:00 | 13.57 | 10.90 | 0.00 | 3.06 | 0.00 | 0.00 |
May | 22.70 | 13-MAY-04:00 | 20.32 | 19.30 | 2.10 | 20.40 | 0.00 | 0.00 |
June | 23.30 | 18-JUN-04:00 | 21.80 | 21.20 | 2.70 | 17.75 | 0.00 | 0.00 |
July | 23.20 | 19-JUL-02:00 | 23.20 | 23.20 | 2.30 | 15.39 | 0.00 | 0.00 |
August | 23.40 | 15-AUG-23:00 | 22.91 | 22.80 | 2.40 | 21.78 | 0.00 | 0.00 |
September | 23.00 | 27-SEP-04:00 | 20.73 | 19.70 | 0.00 | 10.30 | 0.00 | 0.00 |
October | 15.50 | 31-OCT-04:00 | 14.07 | 13.20 | 0.00 | 1.80 | 0.00 | 0.00 |
November | 9.50 | 27-NOV-05:00 | 8.75 | 8.10 | 0.00 | -5.0 | 0.00 | 0.00 |
December | 5.00 | 21-DEC-04:00 | 4.08 | 3.00 | 0.00 | -10.5 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 4.80 | 4.08 | 3.00 | 0.00 | -10.5 | 0.00 | 0.00 | |
Maximum of Months | 23.40 | 23.20 | 23.20 | 2.70 | 21.78 | 0.00 | 0.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 15.61 | 17-JAN-14:00 | 18.20 | 14.10 | 1.00 | 11.07 | 198.00 | 56.50 |
February | 18.14 | 25-FEB-16:00 | 21.20 | 16.60 | 5.90 | 10.88 | 107.50 | 156.50 |
March | 21.36 | 10-MAR-18:49 | 29.25 | 17.73 | 2.10 | 21.44 | 0.00 | 0.00 |
April | 23.40 | 18-APR-13:00 | 37.10 | 17.80 | 5.70 | 23.49 | 233.50 | 671.50 |
May | 27.40 | 22-MAY-22:00 | 29.40 | 26.80 | 0.00 | 20.40 | 0.00 | 0.00 |
June | 28.92 | 28-JUN-12:00 | 34.40 | 27.50 | 1.00 | 25.49 | 332.50 | 501.50 |
July | 29.17 | 01-JUL-16:00 | 37.20 | 26.80 | 2.30 | 25.66 | 196.00 | 196.00 |
August | 29.16 | 27-AUG-15:00 | 35.10 | 27.40 | 1.30 | 29.55 | 256.00 | 129.00 |
September | 28.10 | 14-SEP-16:00 | 33.70 | 26.40 | 1.40 | 26.48 | 122.50 | 108.50 |
October | 23.05 | 06-OCT-10:00 | 28.60 | 20.80 | 1.30 | 20.22 | 327.00 | 348.50 |
November | 18.91 | 08-NOV-17:10 | 27.55 | 14.47 | 0.17 | 16.67 | 28.00 | 65.33 |
December | 15.64 | 29-DEC-19:00 | 16.80 | 14.90 | 4.80 | 13.54 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 15.61 | 16.80 | 14.10 | 0.00 | 10.88 | 0.00 | 0.00 | |
Maximum of Months | 29.17 | 37.20 | 27.50 | 5.90 | 29.55 | 332.50 | 671.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 14.10 | 17-JAN-13:00 | 17.80 | 15.47 | 0.90 | 9.72 | 260.50 | 81.50 |
February | 16.60 | 25-FEB-16:00 | 21.20 | 18.14 | 5.90 | 10.88 | 107.50 | 156.50 |
March | 18.30 | 10-MAR-19:00 | 27.70 | 21.24 | 2.10 | 21.44 | 0.00 | 0.00 |
April | 19.30 | 26-APR-23:10 | 28.53 | 22.03 | 0.00 | 15.60 | 0.00 | 0.00 |
May | 26.80 | 22-MAY-22:00 | 29.40 | 27.40 | 0.00 | 20.40 | 0.00 | 0.00 |
June | 27.50 | 28-JUN-12:00 | 34.40 | 28.92 | 1.00 | 25.49 | 332.50 | 501.50 |
July | 27.30 | 18-JUL-06:19 | 29.10 | 27.69 | 1.17 | 26.48 | 20.00 | 0.00 |
August | 28.80 | 12-AUG-07:00 | 29.10 | 28.83 | 2.90 | 26.81 | 113.00 | 6.50 |
September | 26.50 | 12-SEP-14:00 | 30.50 | 27.38 | 0.90 | 25.99 | 260.00 | 20.00 |
October | 21.10 | 06-OCT-08:00 | 25.50 | 22.40 | 0.30 | 17.21 | 239.00 | 159.00 |
November | 16.30 | 08-NOV-21:19 | 20.10 | 17.58 | 0.00 | 10.95 | 0.00 | 0.00 |
December | 14.90 | 29-DEC-20:10 | 16.72 | 15.59 | 4.73 | 13.13 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 14.10 | 16.72 | 15.47 | 0.00 | 9.72 | 0.00 | 0.00 | |
Maximum of Months | 28.80 | 34.40 | 28.92 | 5.90 | 26.81 | 332.50 | 501.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 20.92 | 27.26 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 21.74 | 33.91 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 24.21 | 44.04 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 27.79 | 55.91 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 31.48 | 58.43 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 34.27 | 54.82 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 35.42 | 39.75 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 34.60 | 34.68 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 32.04 | 35.55 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 28.44 | 39.44 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 24.77 | 33.85 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 22.02 | 26.79 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 28.18 | 40.37 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 20.92 | 26.79 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 35.42 | 58.43 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK1
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.302522E+09 | -186925331.9 | 0.00 | 0.00 | 744.00 | 0.00 | -115596872.7 | 58.99 | 0.00 | 0.00 |
February | 0.268979E+09 | -166087665.7 | 0.00 | 0.00 | 672.00 | 0.00 | -102890989.3 | 58.99 | 0.00 | 0.00 |
March | 0.286934E+09 | -174351585.4 | 0.00 | 0.00 | 744.00 | 0.00 | -112582345.4 | 58.99 | 0.00 | 0.00 |
April | 0.257571E+09 | -149647091.9 | 0.00 | 0.00 | 720.00 | 0.00 | -107924166.7 | 58.99 | 0.00 | 0.00 |
May | 0.247234E+09 | -136563311.6 | 0.00 | 0.00 | 744.00 | 0.00 | -110670706.7 | 58.99 | 0.00 | 0.00 |
June | 0.226573E+09 | -119768245.0 | 0.00 | 0.00 | 720.00 | 0.00 | -106804320.6 | 58.99 | 0.00 | 0.00 |
July | 0.226007E+09 | -115774309.1 | 0.00 | 0.00 | 744.00 | 0.00 | -110232409.1 | 58.99 | 0.00 | 0.00 |
August | 0.232499E+09 | -122182570.6 | 0.00 | 0.00 | 744.00 | 0.00 | -110315967.7 | 58.99 | 0.00 | 0.00 |
September | 0.236522E+09 | -129450592.5 | 0.00 | 0.00 | 720.00 | 0.00 | -107071802.0 | 58.99 | 0.00 | 0.00 |
October | 0.261524E+09 | -150054852.9 | 0.00 | 0.00 | 744.00 | 0.00 | -111469430.4 | 58.99 | 0.00 | 0.00 |
November | 0.271040E+09 | -162147945.2 | 0.00 | 0.00 | 720.00 | 0.00 | -108891882.3 | 58.99 | 0.00 | 0.00 |
December | 0.295961E+09 | -181758979.9 | 0.00 | 0.00 | 744.00 | 0.00 | -114202067.4 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.311337E+10 | -.179471E+10 | 8760.00 | -.131865E+10 | 58.99 | |||||
Minimum of Months | 0.226007E+09 | -186925331.9 | 0.00 | 0.00 | 672.00 | 0.00 | -115596872.7 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.302522E+09 | -115774309.1 | 0.00 | 0.00 | 744.00 | 0.00 | -102890989.3 | 58.99 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK2
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.301471E+09 | -186914109.5 | 0.00 | 0.00 | 744.00 | 0.00 | -114557095.8 | 58.99 | 0.00 | 0.00 |
February | 0.268489E+09 | -166095185.7 | 0.00 | 0.00 | 672.00 | 0.00 | -102394136.3 | 58.99 | 0.00 | 0.00 |
March | 0.286650E+09 | -174344865.4 | 0.00 | 0.00 | 744.00 | 0.00 | -112305376.8 | 58.99 | 0.00 | 0.00 |
April | 0.257427E+09 | -149627667.0 | 0.00 | 0.00 | 720.00 | 0.00 | -107799730.1 | 58.99 | 0.00 | 0.00 |
May | 0.247219E+09 | -136560841.4 | 0.00 | 0.00 | 744.00 | 0.00 | -110657916.5 | 58.99 | 0.00 | 0.00 |
June | 0.226607E+09 | -119752055.8 | 0.00 | 0.00 | 720.00 | 0.00 | -106855027.2 | 58.99 | 0.00 | 0.00 |
July | 0.226089E+09 | -115749424.0 | 0.00 | 0.00 | 744.00 | 0.00 | -110339248.3 | 58.99 | 0.00 | 0.00 |
August | 0.232601E+09 | -122193938.2 | 0.00 | 0.00 | 744.00 | 0.00 | -110407397.0 | 58.99 | 0.00 | 0.00 |
September | 0.236603E+09 | -129446868.1 | 0.00 | 0.00 | 720.00 | 0.00 | -107156173.9 | 58.99 | 0.00 | 0.00 |
October | 0.261527E+09 | -150056128.2 | 0.00 | 0.00 | 744.00 | 0.00 | -111470837.9 | 58.99 | 0.00 | 0.00 |
November | 0.270922E+09 | -162153513.7 | 0.00 | 0.00 | 720.00 | 0.00 | -108768007.9 | 58.99 | 0.00 | 0.00 |
December | 0.295364E+09 | -181750829.7 | 0.00 | 0.00 | 744.00 | 0.00 | -113612940.6 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.311097E+10 | -.179465E+10 | 8760.00 | -.131632E+10 | 58.99 | |||||
Minimum of Months | 0.226089E+09 | -186914109.5 | 0.00 | 0.00 | 672.00 | 0.00 | -114557095.8 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.301471E+09 | -115749424.0 | 0.00 | 0.00 | 744.00 | 0.00 | -102394136.3 | 58.99 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK3
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.279878E+09 | -164368146.0 | 0.00 | 0.00 | 744.00 | 0.00 | -115509898.9 | 58.99 | 0.00 | 0.00 |
February | 0.248469E+09 | -146181178.0 | 0.00 | 0.00 | 672.00 | 0.00 | -102287801.6 | 59.00 | 0.00 | 0.00 |
March | 0.266875E+09 | -155706658.0 | 0.00 | 0.00 | 744.00 | 0.00 | -111167954.4 | 58.98 | 0.00 | 0.00 |
April | 0.237168E+09 | -131516971.4 | 0.00 | 0.00 | 720.00 | 0.00 | -105651493.9 | 58.99 | 0.00 | 0.00 |
May | 0.229118E+09 | -121189368.8 | 0.00 | 0.00 | 744.00 | 0.00 | -107928853.2 | 58.98 | 0.00 | 0.00 |
June | 0.210947E+09 | -106762146.9 | 0.00 | 0.00 | 720.00 | 0.00 | -104184788.0 | 58.98 | 0.00 | 0.00 |
July | 0.208600E+09 | -101107782.6 | 0.00 | 0.00 | 744.00 | 0.00 | -107492630.6 | 58.99 | 0.00 | 0.00 |
August | 0.217245E+09 | -109213555.4 | 0.00 | 0.00 | 744.00 | 0.00 | -108031023.6 | 58.99 | 0.00 | 0.00 |
September | 0.218597E+09 | -113726514.1 | 0.00 | 0.00 | 720.00 | 0.00 | -104870638.0 | 58.99 | 0.00 | 0.00 |
October | 0.241519E+09 | -132005118.1 | 0.00 | 0.00 | 744.00 | 0.00 | -109513640.2 | 58.99 | 0.00 | 0.00 |
November | 0.251125E+09 | -143173969.8 | 0.00 | 0.00 | 720.00 | 0.00 | -107950760.2 | 58.99 | 0.00 | 0.00 |
December | 0.272552E+09 | -158654258.9 | 0.00 | 0.00 | 744.00 | 0.00 | -113897907.5 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.288209E+10 | -.158361E+10 | 8760.00 | -.129849E+10 | 58.99 | |||||
Minimum of Months | 0.208600E+09 | -164368146.0 | 0.00 | 0.00 | 672.00 | 0.00 | -115509898.9 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.279878E+09 | -101107782.6 | 0.00 | 0.00 | 744.00 | 0.00 | -102287801.6 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK4
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.280384E+09 | -164340682.5 | 0.00 | 0.00 | 744.00 | 0.00 | -116043383.8 | 59.00 | 0.00 | 0.00 |
February | 0.248654E+09 | -146190605.3 | 0.00 | 0.00 | 672.00 | 0.00 | -102463830.1 | 58.99 | 0.00 | 0.00 |
March | 0.266918E+09 | -155697209.0 | 0.00 | 0.00 | 744.00 | 0.00 | -111220946.3 | 58.99 | 0.00 | 0.00 |
April | 0.237057E+09 | -131499605.3 | 0.00 | 0.00 | 720.00 | 0.00 | -105557165.1 | 58.99 | 0.00 | 0.00 |
May | 0.228927E+09 | -121150887.6 | 0.00 | 0.00 | 744.00 | 0.00 | -107776242.7 | 58.99 | 0.00 | 0.00 |
June | 0.210753E+09 | -106725984.0 | 0.00 | 0.00 | 720.00 | 0.00 | -104027395.0 | 58.99 | 0.00 | 0.00 |
July | 0.208395E+09 | -101134763.4 | 0.00 | 0.00 | 744.00 | 0.00 | -107260595.9 | 58.99 | 0.00 | 0.00 |
August | 0.217088E+09 | -109201505.3 | 0.00 | 0.00 | 744.00 | 0.00 | -107886190.8 | 59.00 | 0.00 | 0.00 |
September | 0.218457E+09 | -113733986.1 | 0.00 | 0.00 | 720.00 | 0.00 | -104722752.0 | 58.99 | 0.00 | 0.00 |
October | 0.241438E+09 | -131990578.1 | 0.00 | 0.00 | 744.00 | 0.00 | -109447831.3 | 58.99 | 0.00 | 0.00 |
November | 0.251182E+09 | -143143026.3 | 0.00 | 0.00 | 720.00 | 0.00 | -108038478.7 | 58.99 | 0.00 | 0.00 |
December | 0.272822E+09 | -158654818.8 | 0.00 | 0.00 | 744.00 | 0.00 | -114166843.6 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.288208E+10 | -.158346E+10 | 8760.00 | -.129861E+10 | 58.99 | |||||
Minimum of Months | 0.208395E+09 | -164340682.5 | 0.00 | 0.00 | 672.00 | 0.00 | -116043383.8 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.280384E+09 | -101134763.4 | 0.00 | 0.00 | 744.00 | 0.00 | -102463830.1 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK5
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.272731E+09 | -155353651.9 | 0.00 | 0.00 | 744.00 | 0.00 | -117376937.5 | 58.99 | 0.00 | 0.00 |
February | 0.241445E+09 | -138244527.3 | 0.00 | 0.00 | 672.00 | 0.00 | -103200894.0 | 58.99 | 0.00 | 0.00 |
March | 0.259245E+09 | -147357937.3 | 0.00 | 0.00 | 744.00 | 0.00 | -111887378.0 | 58.98 | 0.00 | 0.00 |
April | 0.230662E+09 | -124440238.6 | 0.00 | 0.00 | 720.00 | 0.00 | -106221732.5 | 58.99 | 0.00 | 0.00 |
May | 0.222947E+09 | -114582571.7 | 0.00 | 0.00 | 744.00 | 0.00 | -108363948.8 | 58.99 | 0.00 | 0.00 |
June | 0.205643E+09 | -101008713.4 | 0.00 | 0.00 | 720.00 | 0.00 | -104634762.2 | 58.99 | 0.00 | 0.00 |
July | 0.203278E+09 | -95648264.6 | 0.00 | 0.00 | 744.00 | 0.00 | -107629839.8 | 58.98 | 0.00 | 0.00 |
August | 0.211722E+09 | -103363716.9 | 0.00 | 0.00 | 744.00 | 0.00 | -108358625.9 | 58.99 | 0.00 | 0.00 |
September | 0.212836E+09 | -107648564.5 | 0.00 | 0.00 | 720.00 | 0.00 | -105187929.9 | 58.99 | 0.00 | 0.00 |
October | 0.234683E+09 | -124758430.6 | 0.00 | 0.00 | 744.00 | 0.00 | -109924661.6 | 58.99 | 0.00 | 0.00 |
November | 0.243710E+09 | -135181578.4 | 0.00 | 0.00 | 720.00 | 0.00 | -108528480.6 | 59.00 | 0.00 | 0.00 |
December | 0.265015E+09 | -150037605.1 | 0.00 | 0.00 | 744.00 | 0.00 | -114977699.6 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.280392E+10 | -.149763E+10 | 8760.00 | -.130629E+10 | 58.99 | |||||
Minimum of Months | 0.203278E+09 | -155353651.9 | 0.00 | 0.00 | 672.00 | 0.00 | -117376937.5 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.272731E+09 | -95648264.6 | 0.00 | 0.00 | 744.00 | 0.00 | -103200894.0 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK6
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.272857E+09 | -155351725.9 | 0.00 | 0.00 | 744.00 | 0.00 | -117505534.1 | 58.99 | 0.00 | 0.00 |
February | 0.241498E+09 | -138240849.4 | 0.00 | 0.00 | 672.00 | 0.00 | -103257640.8 | 58.99 | 0.00 | 0.00 |
March | 0.259331E+09 | -147351523.7 | 0.00 | 0.00 | 744.00 | 0.00 | -111979674.7 | 58.98 | 0.00 | 0.00 |
April | 0.230815E+09 | -124462495.9 | 0.00 | 0.00 | 720.00 | 0.00 | -106352364.1 | 58.99 | 0.00 | 0.00 |
May | 0.223129E+09 | -114604681.5 | 0.00 | 0.00 | 744.00 | 0.00 | -108523876.2 | 58.99 | 0.00 | 0.00 |
June | 0.205824E+09 | -100989690.2 | 0.00 | 0.00 | 720.00 | 0.00 | -104834491.4 | 58.99 | 0.00 | 0.00 |
July | 0.203480E+09 | -95667517.9 | 0.00 | 0.00 | 744.00 | 0.00 | -107812017.1 | 58.98 | 0.00 | 0.00 |
August | 0.211911E+09 | -103355423.2 | 0.00 | 0.00 | 744.00 | 0.00 | -108555806.1 | 58.99 | 0.00 | 0.00 |
September | 0.213000E+09 | -107639328.8 | 0.00 | 0.00 | 720.00 | 0.00 | -105361104.1 | 58.99 | 0.00 | 0.00 |
October | 0.234829E+09 | -124748592.2 | 0.00 | 0.00 | 744.00 | 0.00 | -110080566.0 | 58.99 | 0.00 | 0.00 |
November | 0.243801E+09 | -135203531.1 | 0.00 | 0.00 | 720.00 | 0.00 | -108597411.4 | 58.99 | 0.00 | 0.00 |
December | 0.265064E+09 | -150035142.8 | 0.00 | 0.00 | 744.00 | 0.00 | -115028990.2 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.280554E+10 | -.149765E+10 | 8760.00 | -.130789E+10 | 58.99 | |||||
Minimum of Months | 0.203480E+09 | -155351725.9 | 0.00 | 0.00 | 672.00 | 0.00 | -117505534.1 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.272857E+09 | -95667517.9 | 0.00 | 0.00 | 744.00 | 0.00 | -103257640.8 | 58.99 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK7
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.273034E+09 | -155351715.9 | 0.00 | 0.00 | 744.00 | 0.00 | -117682100.3 | 58.99 | 0.00 | 0.00 |
February | 0.241598E+09 | -138246471.4 | 0.00 | 0.00 | 672.00 | 0.00 | -103351938.8 | 58.99 | 0.00 | 0.00 |
March | 0.259408E+09 | -147294632.0 | 0.00 | 0.00 | 744.00 | 0.00 | -112113776.6 | 59.00 | 0.00 | 0.00 |
April | 0.230870E+09 | -124452137.9 | 0.00 | 0.00 | 720.00 | 0.00 | -106417782.1 | 58.99 | 0.00 | 0.00 |
May | 0.223165E+09 | -114566717.2 | 0.00 | 0.00 | 744.00 | 0.00 | -108597862.1 | 58.99 | 0.00 | 0.00 |
June | 0.205881E+09 | -101008518.2 | 0.00 | 0.00 | 720.00 | 0.00 | -104872505.5 | 58.99 | 0.00 | 0.00 |
July | 0.203514E+09 | -95622454.3 | 0.00 | 0.00 | 744.00 | 0.00 | -107891530.8 | 58.99 | 0.00 | 0.00 |
August | 0.211932E+09 | -103341087.5 | 0.00 | 0.00 | 744.00 | 0.00 | -108591138.5 | 58.99 | 0.00 | 0.00 |
September | 0.213041E+09 | -107625301.3 | 0.00 | 0.00 | 720.00 | 0.00 | -105415677.1 | 58.99 | 0.00 | 0.00 |
October | 0.234879E+09 | -124769683.4 | 0.00 | 0.00 | 744.00 | 0.00 | -110109609.6 | 58.99 | 0.00 | 0.00 |
November | 0.243841E+09 | -135200920.3 | 0.00 | 0.00 | 720.00 | 0.00 | -108640101.6 | 58.99 | 0.00 | 0.00 |
December | 0.265175E+09 | -150037217.8 | 0.00 | 0.00 | 744.00 | 0.00 | -115137550.9 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.280634E+10 | -.149752E+10 | 8760.00 | -.130882E+10 | 58.99 | |||||
Minimum of Months | 0.203514E+09 | -155351715.9 | 0.00 | 0.00 | 672.00 | 0.00 | -117682100.3 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.273034E+09 | -95622454.3 | 0.00 | 0.00 | 744.00 | 0.00 | -103351938.8 | 59.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 319.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 303.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 364.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 379.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 406.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 386.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 379.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 372.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 344.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 347.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 317.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 315.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4237.50 | ||||||||||
Minimum of Months | 303.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 406.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.109515E+09 | 63210.34 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 1182821.95 | 7885.48 | 02-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5313095.23 | 16537.85 | 23-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.116011E+09 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.109515E+09 | 63210.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 22404824.78 | 33042.67 | 02-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5408.15 | 36.05 | 21-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 22410232.93 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 22404824.78 | 33042.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_3:3_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 88523770.54 | 32885.67 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 502654.52 | 1044.76 | 02-FEB-08:63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 3523406.54 | 4954.56 | 23-DEC-08:63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 92549831.60 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 88523770.54 | 32885.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_4:4_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.126766E+09 | 32950.97 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 1323760.66 | 2589.14 | 02-FEB-08:63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6097244.49 | 7054.41 | 23-DEC-08:63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.134187E+09 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.126766E+09 | 32950.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_5:5_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.169394E+09 | 32847.98 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3035165.95 | 4208.99 | 02-FEB-08:63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 8628956.19 | 9052.56 | 23-DEC-08:63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.181058E+09 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.169394E+09 | 32847.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_6:6_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.289068E+09 | 60153.02 | 01-JAN-10:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6899750.33 | 18353.36 | 02-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16253730.75 | 33444.33 | 23-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.312221E+09 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.289068E+09 | 60153.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_7:7_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.151206E+09 | 31708.20 | 01-JAN-10:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 2634793.40 | 8045.22 | 02-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7330491.56 | 15794.45 | 23-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.161171E+09 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.151206E+09 | 31708.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_8:8_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.161570E+09 | 31590.89 | 01-JAN-10:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3596146.34 | 8983.82 | 02-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 8726626.69 | 17036.51 | 23-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.173893E+09 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.161570E+09 | 31590.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_9:9_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.190470E+09 | 31609.66 | 01-JAN-10:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 7319493.51 | 11756.05 | 02-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 12739391.42 | 20272.42 | 23-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.210529E+09 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.190470E+09 | 31609.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_10:10_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.241382E+09 | 33853.41 | 01-JAN-10:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 19013155.27 | 19003.58 | 02-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 21783257.61 | 27095.88 | 23-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.282179E+09 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.241382E+09 | 33853.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.238603E+10 | 0.214545E+10 | 9135.55 | 12-JAN-15:00 | 8700.57 | 0.00 |
February | 0.00 | 0.00 | 0.782202E+10 | 0.684924E+10 | 14898.07 | 22-FEB-15:00 | 13860.46 | 0.00 |
March | 0.00 | 0.00 | 0.188898E+11 | 0.164662E+11 | 53466.74 | 11-MAR-09:02 | 43046.38 | 0.00 |
April | 0.00 | 0.00 | 0.304616E+11 | 0.275799E+11 | 55178.20 | 26-APR-08:61 | 39185.02 | 0.00 |
May | 0.00 | 0.00 | 0.447322E+11 | 0.361638E+11 | 58181.91 | 24-MAY-08:61 | 30458.71 | 0.00 |
June | 0.00 | 0.00 | 0.512291E+11 | 0.365685E+11 | 59292.83 | 26-JUN-08:61 | 27667.32 | 0.00 |
July | 0.00 | 0.00 | 0.588917E+11 | 0.349235E+11 | 59368.59 | 18-JUL-08:61 | 26813.53 | 0.00 |
August | 0.00 | 0.00 | 0.584694E+11 | 0.324751E+11 | 59428.66 | 26-AUG-08:61 | 26982.99 | 0.00 |
September | 0.00 | 0.00 | 0.483573E+11 | 0.289190E+11 | 59205.20 | 06-SEP-08:61 | 28069.80 | 0.00 |
October | 0.00 | 0.00 | 0.306741E+11 | 0.244362E+11 | 56837.13 | 12-OCT-08:62 | 31646.39 | 0.00 |
November | 0.00 | 0.00 | 0.164150E+11 | 0.142386E+11 | 44845.29 | 09-NOV-09:02 | 32773.66 | 0.00 |
December | 0.00 | 0.00 | 0.503114E+10 | 0.440301E+10 | 11633.87 | 28-DEC-15:00 | 10573.70 | 0.00 |
Annual Sum or Average | 0.373359E+12 | 0.265169E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.238603E+10 | 0.214545E+10 | 9135.55 | 8700.57 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.588917E+11 | 0.365685E+11 | 59428.66 | 43046.38 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.225393E+10 | 0.203701E+10 | 4999.67 | 12-JAN-15:00 | 4782.62 | 0.00 |
February | 0.00 | 0.00 | 0.499073E+10 | 0.443556E+10 | 7937.62 | 22-FEB-14:40 | 7395.29 | 0.00 |
March | 0.00 | 0.00 | 0.102104E+11 | 0.907068E+10 | 27735.34 | 11-MAR-09:02 | 23195.90 | 0.00 |
April | 0.00 | 0.00 | 0.153616E+11 | 0.140848E+11 | 28548.64 | 26-APR-08:61 | 21209.11 | 0.00 |
May | 0.00 | 0.00 | 0.221700E+11 | 0.181828E+11 | 30016.34 | 24-MAY-08:61 | 17111.96 | 0.00 |
June | 0.00 | 0.00 | 0.251273E+11 | 0.182143E+11 | 30584.52 | 26-JUN-08:61 | 15651.20 | 0.00 |
July | 0.00 | 0.00 | 0.286626E+11 | 0.173437E+11 | 30865.49 | 18-JUL-08:61 | 14872.82 | 0.00 |
August | 0.00 | 0.00 | 0.284333E+11 | 0.161360E+11 | 30934.14 | 12-AUG-08:61 | 13796.05 | 0.00 |
September | 0.00 | 0.00 | 0.234699E+11 | 0.144093E+11 | 30522.19 | 12-SEP-08:61 | 15873.80 | 0.00 |
October | 0.00 | 0.00 | 0.153945E+11 | 0.125498E+11 | 29345.71 | 12-OCT-08:62 | 17677.92 | 0.00 |
November | 0.00 | 0.00 | 0.903123E+10 | 0.798473E+10 | 22817.04 | 09-NOV-09:02 | 17673.11 | 0.00 |
December | 0.00 | 0.00 | 0.378685E+10 | 0.335726E+10 | 6157.41 | 28-DEC-14:50 | 5628.06 | 0.00 |
Annual Sum or Average | 0.188892E+12 | 0.137806E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.225393E+10 | 0.203701E+10 | 4999.67 | 4782.62 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.286626E+11 | 0.182143E+11 | 30934.14 | 23195.90 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.926817E+09 | 0.851340E+09 | 4509.41 | 12-JAN-15:00 | 4317.78 | 0.00 |
February | 0.00 | 0.00 | 0.318573E+10 | 0.284708E+10 | 7563.37 | 22-FEB-14:40 | 7049.96 | 0.00 |
March | 0.00 | 0.00 | 0.774887E+10 | 0.687404E+10 | 28153.16 | 11-MAR-08:62 | 21231.98 | 0.00 |
April | 0.00 | 0.00 | 0.122788E+11 | 0.112121E+11 | 28756.41 | 26-APR-07:01 | 20064.91 | 0.00 |
May | 0.00 | 0.00 | 0.183513E+11 | 0.149362E+11 | 30204.76 | 24-MAY-07:01 | 16136.77 | 0.00 |
June | 0.00 | 0.00 | 0.208484E+11 | 0.149050E+11 | 30888.93 | 25-JUN-08:61 | 13193.88 | 0.00 |
July | 0.00 | 0.00 | 0.233137E+11 | 0.137337E+11 | 30925.30 | 28-JUL-07:01 | 13637.20 | 0.00 |
August | 0.00 | 0.00 | 0.236661E+11 | 0.130588E+11 | 30979.83 | 21-AUG-07:02 | 11662.46 | 0.00 |
September | 0.00 | 0.00 | 0.190343E+11 | 0.113702E+11 | 31007.88 | 09-SEP-07:01 | 13496.80 | 0.00 |
October | 0.00 | 0.00 | 0.121790E+11 | 0.984685E+10 | 29571.33 | 12-OCT-07:02 | 16345.48 | 0.00 |
November | 0.00 | 0.00 | 0.670678E+10 | 0.596714E+10 | 10460.11 | 09-NOV-13:20 | 9225.09 | 0.00 |
December | 0.00 | 0.00 | 0.206979E+10 | 0.185348E+10 | 5713.00 | 28-DEC-14:00 | 5275.94 | 0.00 |
Annual Sum or Average | 0.150310E+12 | 0.107456E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.926817E+09 | 0.851340E+09 | 4509.41 | 4317.78 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.236661E+11 | 0.149362E+11 | 31007.88 | 21231.98 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.814832E+09 | 0.747920E+09 | 4367.45 | 12-JAN-15:00 | 4181.01 | 0.00 |
February | 0.00 | 0.00 | 0.308540E+10 | 0.275769E+10 | 7503.58 | 24-FEB-15:00 | 6377.94 | 0.00 |
March | 0.00 | 0.00 | 0.771740E+10 | 0.684546E+10 | 28208.87 | 11-MAR-08:62 | 21270.82 | 0.00 |
April | 0.00 | 0.00 | 0.123276E+11 | 0.112568E+11 | 28816.40 | 26-APR-07:01 | 20134.72 | 0.00 |
May | 0.00 | 0.00 | 0.184790E+11 | 0.150488E+11 | 30259.36 | 24-MAY-07:01 | 16206.39 | 0.00 |
June | 0.00 | 0.00 | 0.209796E+11 | 0.150143E+11 | 30949.08 | 25-JUN-08:61 | 13315.96 | 0.00 |
July | 0.00 | 0.00 | 0.234699E+11 | 0.138550E+11 | 30985.52 | 28-JUL-07:01 | 13704.40 | 0.00 |
August | 0.00 | 0.00 | 0.237825E+11 | 0.131458E+11 | 31040.16 | 21-AUG-07:02 | 11800.33 | 0.00 |
September | 0.00 | 0.00 | 0.191263E+11 | 0.114390E+11 | 31068.26 | 09-SEP-07:01 | 13541.89 | 0.00 |
October | 0.00 | 0.00 | 0.122267E+11 | 0.988810E+10 | 29630.83 | 12-OCT-07:02 | 16401.84 | 0.00 |
November | 0.00 | 0.00 | 0.665835E+10 | 0.592330E+10 | 10431.61 | 09-NOV-13:20 | 9198.80 | 0.00 |
December | 0.00 | 0.00 | 0.194795E+10 | 0.174469E+10 | 5583.35 | 28-DEC-14:00 | 5154.55 | 0.00 |
Annual Sum or Average | 0.150616E+12 | 0.107667E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.814832E+09 | 0.747920E+09 | 4367.45 | 4181.01 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.237825E+11 | 0.150488E+11 | 31068.26 | 21270.82 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.679161E+09 | 0.622263E+09 | 4150.36 | 12-JAN-15:00 | 3970.98 | 0.00 |
February | 0.00 | 0.00 | 0.290675E+10 | 0.259927E+10 | 7353.74 | 24-FEB-15:00 | 6244.64 | 0.00 |
March | 0.00 | 0.00 | 0.752198E+10 | 0.667020E+10 | 28108.35 | 11-MAR-08:62 | 21104.26 | 0.00 |
April | 0.00 | 0.00 | 0.121753E+11 | 0.111145E+11 | 28715.68 | 26-APR-07:01 | 19978.20 | 0.00 |
May | 0.00 | 0.00 | 0.183393E+11 | 0.149272E+11 | 30166.97 | 24-MAY-07:01 | 16079.70 | 0.00 |
June | 0.00 | 0.00 | 0.208338E+11 | 0.148950E+11 | 30854.50 | 25-JUN-08:61 | 13169.65 | 0.00 |
July | 0.00 | 0.00 | 0.233378E+11 | 0.137549E+11 | 30890.82 | 28-JUL-07:01 | 13525.95 | 0.00 |
August | 0.00 | 0.00 | 0.236193E+11 | 0.130252E+11 | 30945.29 | 21-AUG-07:02 | 11678.42 | 0.00 |
September | 0.00 | 0.00 | 0.189666E+11 | 0.113189E+11 | 30973.31 | 09-SEP-07:01 | 13401.42 | 0.00 |
October | 0.00 | 0.00 | 0.120734E+11 | 0.975699E+10 | 29534.05 | 12-OCT-07:02 | 16269.19 | 0.00 |
November | 0.00 | 0.00 | 0.648537E+10 | 0.576749E+10 | 10301.21 | 09-NOV-13:30 | 9106.85 | 0.00 |
December | 0.00 | 0.00 | 0.176600E+10 | 0.158226E+10 | 5387.50 | 28-DEC-14:00 | 4970.03 | 0.00 |
Annual Sum or Average | 0.148705E+12 | 0.106034E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.679161E+09 | 0.622263E+09 | 4150.36 | 3970.98 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.236193E+11 | 0.149272E+11 | 30973.31 | 21104.26 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.931405E+09 | 0.841062E+09 | 7207.16 | 12-JAN-15:10 | 6781.18 | 0.00 |
February | 0.00 | 0.00 | 0.485014E+10 | 0.429856E+10 | 13459.94 | 24-FEB-15:20 | 11222.50 | 0.00 |
March | 0.00 | 0.00 | 0.134538E+11 | 0.118294E+11 | 51187.71 | 11-MAR-09:02 | 39920.52 | 0.00 |
April | 0.00 | 0.00 | 0.220338E+11 | 0.201164E+11 | 52281.86 | 26-APR-08:61 | 38001.94 | 0.00 |
May | 0.00 | 0.00 | 0.335219E+11 | 0.271900E+11 | 55176.05 | 24-MAY-08:61 | 29711.12 | 0.00 |
June | 0.00 | 0.00 | 0.381515E+11 | 0.271796E+11 | 56519.76 | 25-JUN-09:01 | 24785.90 | 0.00 |
July | 0.00 | 0.00 | 0.424957E+11 | 0.247757E+11 | 56576.37 | 28-JUL-08:61 | 26431.27 | 0.00 |
August | 0.00 | 0.00 | 0.432967E+11 | 0.235252E+11 | 56765.28 | 21-AUG-08:61 | 21553.02 | 0.00 |
September | 0.00 | 0.00 | 0.344025E+11 | 0.203151E+11 | 56822.70 | 04-SEP-09:01 | 23015.90 | 0.00 |
October | 0.00 | 0.00 | 0.218775E+11 | 0.175353E+11 | 54112.97 | 12-OCT-08:62 | 29836.39 | 0.00 |
November | 0.00 | 0.00 | 0.114612E+11 | 0.100771E+11 | 41737.23 | 11-NOV-10:02 | 33237.36 | 0.00 |
December | 0.00 | 0.00 | 0.264032E+10 | 0.234492E+10 | 9630.69 | 28-DEC-14:00 | 8744.91 | 0.00 |
Annual Sum or Average | 0.269116E+12 | 0.190028E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.931405E+09 | 0.841062E+09 | 7207.16 | 6781.18 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.432967E+11 | 0.271900E+11 | 56822.70 | 39920.52 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.443073E+09 | 0.400672E+09 | 3694.92 | 12-JAN-15:10 | 3492.50 | 0.00 |
February | 0.00 | 0.00 | 0.248132E+10 | 0.220795E+10 | 6993.77 | 24-FEB-15:20 | 5847.62 | 0.00 |
March | 0.00 | 0.00 | 0.697175E+10 | 0.614828E+10 | 26926.79 | 11-MAR-09:02 | 21069.61 | 0.00 |
April | 0.00 | 0.00 | 0.114641E+11 | 0.104785E+11 | 27477.53 | 26-APR-08:61 | 20035.68 | 0.00 |
May | 0.00 | 0.00 | 0.174494E+11 | 0.141727E+11 | 29015.83 | 24-MAY-08:61 | 15705.02 | 0.00 |
June | 0.00 | 0.00 | 0.198251E+11 | 0.141470E+11 | 29734.69 | 25-JUN-09:01 | 12993.99 | 0.00 |
July | 0.00 | 0.00 | 0.220831E+11 | 0.129057E+11 | 29776.38 | 28-JUL-08:61 | 13938.49 | 0.00 |
August | 0.00 | 0.00 | 0.224771E+11 | 0.122414E+11 | 29863.85 | 21-AUG-08:61 | 11317.12 | 0.00 |
September | 0.00 | 0.00 | 0.178757E+11 | 0.105827E+11 | 29894.06 | 04-SEP-09:01 | 12097.78 | 0.00 |
October | 0.00 | 0.00 | 0.113678E+11 | 0.913702E+10 | 28466.24 | 12-OCT-08:62 | 15819.68 | 0.00 |
November | 0.00 | 0.00 | 0.594249E+10 | 0.524292E+10 | 20313.50 | 11-NOV-10:02 | 16212.90 | 0.00 |
December | 0.00 | 0.00 | 0.132881E+10 | 0.118560E+10 | 4968.13 | 28-DEC-14:00 | 4528.36 | 0.00 |
Annual Sum or Average | 0.139710E+12 | 0.988504E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.443073E+09 | 0.400672E+09 | 3694.92 | 3492.50 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.224771E+11 | 0.141727E+11 | 29894.06 | 21069.61 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.411191E+09 | 0.371258E+09 | 3612.19 | 12-JAN-15:10 | 3413.14 | 0.00 |
February | 0.00 | 0.00 | 0.241467E+10 | 0.214900E+10 | 6927.87 | 24-FEB-15:20 | 5789.58 | 0.00 |
March | 0.00 | 0.00 | 0.688928E+10 | 0.607406E+10 | 26826.43 | 11-MAR-09:02 | 20956.28 | 0.00 |
April | 0.00 | 0.00 | 0.113901E+11 | 0.104093E+11 | 27376.18 | 26-APR-08:61 | 19923.97 | 0.00 |
May | 0.00 | 0.00 | 0.173712E+11 | 0.141043E+11 | 28909.65 | 24-MAY-08:61 | 15613.11 | 0.00 |
June | 0.00 | 0.00 | 0.197438E+11 | 0.140800E+11 | 29627.19 | 25-JUN-09:01 | 12907.17 | 0.00 |
July | 0.00 | 0.00 | 0.220049E+11 | 0.128462E+11 | 29681.12 | 28-JUL-08:61 | 13851.78 | 0.00 |
August | 0.00 | 0.00 | 0.223983E+11 | 0.121826E+11 | 29755.90 | 21-AUG-08:61 | 11249.72 | 0.00 |
September | 0.00 | 0.00 | 0.178050E+11 | 0.105290E+11 | 29785.99 | 04-SEP-09:01 | 12030.74 | 0.00 |
October | 0.00 | 0.00 | 0.113021E+11 | 0.908048E+10 | 28363.76 | 12-OCT-08:62 | 15729.65 | 0.00 |
November | 0.00 | 0.00 | 0.587816E+10 | 0.518497E+10 | 19795.15 | 11-NOV-10:02 | 15764.78 | 0.00 |
December | 0.00 | 0.00 | 0.127580E+10 | 0.113893E+10 | 4895.90 | 28-DEC-14:00 | 4460.81 | 0.00 |
Annual Sum or Average | 0.138884E+12 | 0.981501E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.411191E+09 | 0.371258E+09 | 3612.19 | 3413.14 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.223983E+11 | 0.141043E+11 | 29785.99 | 20956.28 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.356615E+09 | 0.321259E+09 | 3453.01 | 12-JAN-15:10 | 3261.53 | 0.00 |
February | 0.00 | 0.00 | 0.227077E+10 | 0.202248E+10 | 6808.25 | 24-FEB-15:20 | 5685.46 | 0.00 |
March | 0.00 | 0.00 | 0.671901E+10 | 0.592256E+10 | 26831.76 | 11-MAR-09:02 | 20882.49 | 0.00 |
April | 0.00 | 0.00 | 0.113007E+11 | 0.103265E+11 | 27381.73 | 26-APR-08:61 | 19871.36 | 0.00 |
May | 0.00 | 0.00 | 0.173354E+11 | 0.140759E+11 | 28919.76 | 24-MAY-08:61 | 15571.66 | 0.00 |
June | 0.00 | 0.00 | 0.197397E+11 | 0.140800E+11 | 29644.48 | 25-JUN-09:01 | 12840.73 | 0.00 |
July | 0.00 | 0.00 | 0.220445E+11 | 0.128785E+11 | 29704.91 | 28-JUL-08:61 | 13841.41 | 0.00 |
August | 0.00 | 0.00 | 0.224492E+11 | 0.122216E+11 | 29773.26 | 21-AUG-08:61 | 11241.39 | 0.00 |
September | 0.00 | 0.00 | 0.178321E+11 | 0.105511E+11 | 29803.37 | 04-SEP-09:01 | 12023.86 | 0.00 |
October | 0.00 | 0.00 | 0.112806E+11 | 0.906333E+10 | 28376.57 | 12-OCT-08:62 | 15702.92 | 0.00 |
November | 0.00 | 0.00 | 0.578542E+10 | 0.510267E+10 | 18628.14 | 11-NOV-10:02 | 14771.01 | 0.00 |
December | 0.00 | 0.00 | 0.117097E+10 | 0.104711E+10 | 4770.46 | 28-DEC-14:00 | 4344.51 | 0.00 |
Annual Sum or Average | 0.138285E+12 | 0.976130E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.356615E+09 | 0.321259E+09 | 3453.01 | 3261.53 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.224492E+11 | 0.140800E+11 | 29803.37 | 20882.49 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.357385E+09 | 0.324209E+09 | 3502.36 | 12-JAN-15:10 | 3326.38 | 0.00 |
February | 0.00 | 0.00 | 0.222788E+10 | 0.199783E+10 | 7010.18 | 22-FEB-14:00 | 6500.04 | 0.00 |
March | 0.00 | 0.00 | 0.675765E+10 | 0.598226E+10 | 28598.31 | 11-MAR-09:02 | 22211.57 | 0.00 |
April | 0.00 | 0.00 | 0.118232E+11 | 0.108289E+11 | 29172.16 | 17-APR-08:61 | 21602.32 | 0.00 |
May | 0.00 | 0.00 | 0.183631E+11 | 0.149907E+11 | 31158.98 | 24-MAY-08:61 | 15585.05 | 0.00 |
June | 0.00 | 0.00 | 0.209753E+11 | 0.151187E+11 | 31761.53 | 24-JUN-08:61 | 14275.54 | 0.00 |
July | 0.00 | 0.00 | 0.236369E+11 | 0.140512E+11 | 31729.96 | 26-JUL-08:61 | 14039.36 | 0.00 |
August | 0.00 | 0.00 | 0.241653E+11 | 0.134713E+11 | 31725.21 | 21-AUG-08:61 | 12289.56 | 0.00 |
September | 0.00 | 0.00 | 0.192076E+11 | 0.116067E+11 | 31781.67 | 09-SEP-08:61 | 13728.44 | 0.00 |
October | 0.00 | 0.00 | 0.122161E+11 | 0.990189E+10 | 30379.46 | 12-OCT-08:62 | 16462.86 | 0.00 |
November | 0.00 | 0.00 | 0.615920E+10 | 0.546413E+10 | 19283.46 | 11-NOV-10:02 | 15372.71 | 0.00 |
December | 0.00 | 0.00 | 0.121443E+10 | 0.109425E+10 | 4967.38 | 28-DEC-14:00 | 4548.95 | 0.00 |
Annual Sum or Average | 0.147104E+12 | 0.104832E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.357385E+09 | 0.324209E+09 | 3502.36 | 3326.38 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.241653E+11 | 0.151187E+11 | 31781.67 | 22211.57 | 0.00 |
Report: FanReportMonthly
For: PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.195541E+10 | 0.37 | 2690.45 | 01-JAN-09:01 | 0.90 |
February | 0.176668E+10 | 0.37 | 1277.56 | 02-FEB-09:02 | 0.61 |
March | 0.195712E+10 | 0.37 | 2690.45 | 11-MAR-09:02 | 0.89 |
April | 0.198125E+10 | 0.38 | 2690.45 | 01-APR-08:62 | 0.89 |
May | 0.235756E+10 | 0.41 | 2690.45 | 01-MAY-08:61 | 0.89 |
June | 0.250684E+10 | 0.43 | 2690.45 | 01-JUN-08:61 | 0.89 |
July | 0.268525E+10 | 0.43 | 2690.45 | 01-JUL-08:61 | 0.88 |
August | 0.264681E+10 | 0.43 | 2690.45 | 01-AUG-08:61 | 0.88 |
September | 0.227075E+10 | 0.40 | 2690.45 | 01-SEP-08:61 | 0.88 |
October | 0.199241E+10 | 0.37 | 2690.45 | 01-OCT-07:02 | 0.89 |
November | 0.188692E+10 | 0.37 | 2150.76 | 09-NOV-09:02 | 0.80 |
December | 0.196050E+10 | 0.37 | 1498.52 | 23-DEC-09:02 | 0.67 |
Annual Sum or Average | 0.259675E+11 | 0.39 | |||
Minimum of Months | 0.176668E+10 | 0.37 | 1277.56 | 0.61 | |
Maximum of Months | 0.268525E+10 | 0.43 | 2690.45 | 0.90 |
Report: FanReportMonthly
For: PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.849520E+09 | 0.40 | 1463.30 | 02-JAN-09:01 | 0.92 |
February | 0.790284E+09 | 0.40 | 585.32 | 01-FEB-17:30 | 0.56 |
March | 0.912169E+09 | 0.40 | 1463.30 | 11-MAR-09:02 | 0.92 |
April | 0.963209E+09 | 0.41 | 1463.30 | 01-APR-08:62 | 0.92 |
May | 0.120036E+10 | 0.43 | 1463.30 | 01-MAY-08:61 | 0.92 |
June | 0.128761E+10 | 0.44 | 1463.30 | 01-JUN-08:61 | 0.92 |
July | 0.137536E+10 | 0.45 | 1463.30 | 01-JUL-08:61 | 0.91 |
August | 0.135182E+10 | 0.44 | 1463.30 | 01-AUG-08:61 | 0.91 |
September | 0.114713E+10 | 0.42 | 1463.30 | 01-SEP-08:61 | 0.91 |
October | 0.958863E+09 | 0.40 | 1463.30 | 01-OCT-07:02 | 0.92 |
November | 0.868523E+09 | 0.40 | 1146.85 | 09-NOV-09:02 | 0.82 |
December | 0.860520E+09 | 0.41 | 586.28 | 21-DEC-09:02 | 0.56 |
Annual Sum or Average | 0.125654E+11 | 0.42 | |||
Minimum of Months | 0.790284E+09 | 0.40 | 585.32 | 0.56 | |
Maximum of Months | 0.137536E+10 | 0.45 | 1463.30 | 0.92 |
Report: FanReportMonthly
For: PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.844909E+09 | 0.30 | 1455.50 | 01-JAN-09:01 | 0.93 |
February | 0.762926E+09 | 0.30 | 609.94 | 02-FEB-08:63 | 0.58 |
March | 0.859776E+09 | 0.31 | 1455.50 | 11-MAR-08:62 | 0.92 |
April | 0.864637E+09 | 0.31 | 1455.50 | 01-APR-07:02 | 0.92 |
May | 0.106648E+10 | 0.35 | 1455.50 | 01-MAY-07:01 | 0.93 |
June | 0.113672E+10 | 0.36 | 1455.50 | 01-JUN-07:01 | 0.92 |
July | 0.119334E+10 | 0.36 | 1455.50 | 01-JUL-07:01 | 0.91 |
August | 0.119478E+10 | 0.37 | 1455.50 | 01-AUG-07:01 | 0.91 |
September | 0.997816E+09 | 0.34 | 1455.50 | 01-SEP-07:01 | 0.91 |
October | 0.861796E+09 | 0.31 | 1455.50 | 01-OCT-08:61 | 0.92 |
November | 0.817407E+09 | 0.30 | 582.20 | 05-NOV-15:40 | 0.56 |
December | 0.838460E+09 | 0.30 | 713.77 | 23-DEC-08:63 | 0.64 |
Annual Sum or Average | 0.114390E+11 | 0.33 | |||
Minimum of Months | 0.762926E+09 | 0.30 | 582.20 | 0.56 | |
Maximum of Months | 0.119478E+10 | 0.37 | 1455.50 | 0.93 |
Report: FanReportMonthly
For: PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.847803E+09 | 0.30 | 1458.74 | 01-JAN-09:01 | 0.93 |
February | 0.764649E+09 | 0.30 | 652.27 | 02-FEB-08:63 | 0.60 |
March | 0.861708E+09 | 0.31 | 1458.74 | 11-MAR-08:62 | 0.92 |
April | 0.866777E+09 | 0.31 | 1458.74 | 01-APR-07:02 | 0.92 |
May | 0.107131E+10 | 0.35 | 1458.74 | 01-MAY-07:01 | 0.93 |
June | 0.114261E+10 | 0.36 | 1458.74 | 01-JUN-07:01 | 0.92 |
July | 0.120144E+10 | 0.36 | 1458.74 | 01-JUL-07:01 | 0.91 |
August | 0.120045E+10 | 0.37 | 1458.74 | 01-AUG-07:01 | 0.91 |
September | 0.100130E+10 | 0.34 | 1458.74 | 01-SEP-07:01 | 0.91 |
October | 0.864058E+09 | 0.31 | 1458.74 | 01-OCT-08:61 | 0.92 |
November | 0.819229E+09 | 0.30 | 583.50 | 03-NOV-07:15 | 0.56 |
December | 0.840397E+09 | 0.30 | 770.88 | 23-DEC-08:63 | 0.67 |
Annual Sum or Average | 0.114817E+11 | 0.33 | |||
Minimum of Months | 0.764649E+09 | 0.30 | 583.50 | 0.56 | |
Maximum of Months | 0.120144E+10 | 0.37 | 1458.74 | 0.93 |
Report: FanReportMonthly
For: PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.845972E+09 | 0.30 | 1453.62 | 01-JAN-09:01 | 0.93 |
February | 0.762012E+09 | 0.30 | 693.21 | 02-FEB-08:63 | 0.63 |
March | 0.858613E+09 | 0.31 | 1453.62 | 11-MAR-08:62 | 0.92 |
April | 0.862063E+09 | 0.31 | 1453.62 | 01-APR-07:02 | 0.92 |
May | 0.106508E+10 | 0.35 | 1453.62 | 01-MAY-07:01 | 0.93 |
June | 0.113527E+10 | 0.36 | 1453.62 | 01-JUN-07:01 | 0.92 |
July | 0.119486E+10 | 0.36 | 1453.62 | 01-JUL-07:01 | 0.91 |
August | 0.119258E+10 | 0.37 | 1453.62 | 01-AUG-07:01 | 0.91 |
September | 0.994524E+09 | 0.34 | 1453.62 | 01-SEP-07:01 | 0.91 |
October | 0.860179E+09 | 0.31 | 1453.62 | 01-OCT-08:61 | 0.92 |
November | 0.816355E+09 | 0.30 | 581.45 | 01-NOV-13:20 | 0.56 |
December | 0.837517E+09 | 0.30 | 821.81 | 23-DEC-08:63 | 0.70 |
Annual Sum or Average | 0.114250E+11 | 0.33 | |||
Minimum of Months | 0.762012E+09 | 0.30 | 581.45 | 0.56 | |
Maximum of Months | 0.119486E+10 | 0.37 | 1453.62 | 0.93 |
Report: FanReportMonthly
For: PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.136624E+10 | 0.27 | 2543.62 | 01-JAN-10:01 | 0.89 |
February | 0.123088E+10 | 0.27 | 1483.10 | 02-FEB-09:02 | 0.68 |
March | 0.138895E+10 | 0.28 | 2543.62 | 11-MAR-09:02 | 0.89 |
April | 0.140319E+10 | 0.28 | 2543.62 | 01-APR-08:62 | 0.89 |
May | 0.176842E+10 | 0.31 | 2543.62 | 01-MAY-08:61 | 0.89 |
June | 0.190233E+10 | 0.33 | 2543.62 | 01-JUN-08:61 | 0.89 |
July | 0.200701E+10 | 0.33 | 2543.62 | 01-JUL-08:61 | 0.88 |
August | 0.200795E+10 | 0.33 | 2543.62 | 01-AUG-08:61 | 0.88 |
September | 0.165311E+10 | 0.31 | 2543.62 | 01-SEP-08:61 | 0.88 |
October | 0.139654E+10 | 0.27 | 2543.62 | 01-OCT-09:01 | 0.89 |
November | 0.131893E+10 | 0.27 | 2018.70 | 11-NOV-10:02 | 0.80 |
December | 0.135199E+10 | 0.27 | 1865.98 | 23-DEC-09:02 | 0.78 |
Annual Sum or Average | 0.187955E+11 | 0.29 | |||
Minimum of Months | 0.123088E+10 | 0.27 | 1483.10 | 0.68 | |
Maximum of Months | 0.200795E+10 | 0.33 | 2543.62 | 0.89 |
Report: FanReportMonthly
For: PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.750325E+09 | 0.28 | 1396.99 | 01-JAN-10:01 | 0.93 |
February | 0.675989E+09 | 0.28 | 771.47 | 02-FEB-09:02 | 0.69 |
March | 0.762760E+09 | 0.29 | 1396.99 | 11-MAR-09:02 | 0.92 |
April | 0.769991E+09 | 0.29 | 1396.99 | 01-APR-08:62 | 0.92 |
May | 0.969314E+09 | 0.32 | 1396.99 | 01-MAY-08:61 | 0.92 |
June | 0.103769E+10 | 0.34 | 1396.99 | 01-JUN-08:61 | 0.92 |
July | 0.109316E+10 | 0.34 | 1396.99 | 01-JUL-08:61 | 0.91 |
August | 0.109225E+10 | 0.34 | 1396.99 | 01-AUG-08:61 | 0.91 |
September | 0.902968E+09 | 0.31 | 1396.99 | 01-SEP-08:61 | 0.91 |
October | 0.766166E+09 | 0.28 | 1396.99 | 01-OCT-09:01 | 0.92 |
November | 0.724332E+09 | 0.28 | 1005.29 | 11-NOV-10:02 | 0.79 |
December | 0.742498E+09 | 0.28 | 976.32 | 23-DEC-09:02 | 0.78 |
Annual Sum or Average | 0.102874E+11 | 0.30 | |||
Minimum of Months | 0.675989E+09 | 0.28 | 771.47 | 0.69 | |
Maximum of Months | 0.109316E+10 | 0.34 | 1396.99 | 0.93 |
Report: FanReportMonthly
For: PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.747483E+09 | 0.28 | 1391.16 | 01-JAN-10:01 | 0.93 |
February | 0.673194E+09 | 0.28 | 793.84 | 02-FEB-09:02 | 0.70 |
March | 0.759551E+09 | 0.29 | 1391.16 | 11-MAR-09:02 | 0.92 |
April | 0.766405E+09 | 0.29 | 1391.16 | 01-APR-08:62 | 0.92 |
May | 0.965000E+09 | 0.32 | 1391.16 | 01-MAY-08:61 | 0.92 |
June | 0.103314E+10 | 0.34 | 1391.16 | 01-JUN-08:61 | 0.92 |
July | 0.108879E+10 | 0.34 | 1391.16 | 01-JUL-08:61 | 0.91 |
August | 0.108795E+10 | 0.34 | 1391.16 | 01-AUG-08:61 | 0.91 |
September | 0.899144E+09 | 0.31 | 1391.16 | 01-SEP-08:61 | 0.91 |
October | 0.762831E+09 | 0.28 | 1391.16 | 01-OCT-09:01 | 0.92 |
November | 0.721296E+09 | 0.28 | 973.28 | 11-NOV-10:02 | 0.78 |
December | 0.739438E+09 | 0.28 | 1006.60 | 23-DEC-09:02 | 0.80 |
Annual Sum or Average | 0.102442E+11 | 0.30 | |||
Minimum of Months | 0.673194E+09 | 0.28 | 793.84 | 0.70 | |
Maximum of Months | 0.108879E+10 | 0.34 | 1391.16 | 0.93 |
Report: FanReportMonthly
For: PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.748745E+09 | 0.28 | 1392.09 | 01-JAN-10:01 | 0.93 |
February | 0.673744E+09 | 0.28 | 867.48 | 02-FEB-09:02 | 0.73 |
March | 0.759987E+09 | 0.29 | 1392.09 | 11-MAR-09:02 | 0.92 |
April | 0.765655E+09 | 0.29 | 1392.09 | 01-APR-08:62 | 0.92 |
May | 0.964567E+09 | 0.32 | 1392.09 | 01-MAY-08:61 | 0.92 |
June | 0.103404E+10 | 0.34 | 1392.09 | 01-JUN-08:61 | 0.92 |
July | 0.109149E+10 | 0.34 | 1392.09 | 01-JUL-08:61 | 0.91 |
August | 0.109102E+10 | 0.34 | 1392.09 | 01-AUG-08:61 | 0.91 |
September | 0.900718E+09 | 0.31 | 1392.09 | 01-SEP-08:61 | 0.91 |
October | 0.763403E+09 | 0.28 | 1392.09 | 01-OCT-09:01 | 0.92 |
November | 0.721745E+09 | 0.28 | 900.26 | 11-NOV-10:02 | 0.75 |
December | 0.740039E+09 | 0.28 | 1092.52 | 23-DEC-09:02 | 0.83 |
Annual Sum or Average | 0.102552E+11 | 0.30 | |||
Minimum of Months | 0.673744E+09 | 0.28 | 867.48 | 0.73 | |
Maximum of Months | 0.109149E+10 | 0.34 | 1392.09 | 0.93 |
Report: FanReportMonthly
For: PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.809706E+09 | 0.28 | 1503.58 | 01-JAN-10:01 | 0.93 |
February | 0.728000E+09 | 0.28 | 1107.85 | 02-FEB-09:02 | 0.80 |
March | 0.820723E+09 | 0.29 | 1503.58 | 11-MAR-09:02 | 0.92 |
April | 0.823645E+09 | 0.29 | 1503.58 | 02-APR-09:01 | 0.92 |
May | 0.103769E+10 | 0.32 | 1503.58 | 01-MAY-08:61 | 0.92 |
June | 0.111903E+10 | 0.34 | 1503.58 | 01-JUN-08:61 | 0.92 |
July | 0.118933E+10 | 0.34 | 1503.58 | 01-JUL-08:61 | 0.91 |
August | 0.119203E+10 | 0.35 | 1503.58 | 01-AUG-08:61 | 0.91 |
September | 0.982457E+09 | 0.32 | 1503.58 | 01-SEP-08:61 | 0.91 |
October | 0.827761E+09 | 0.28 | 1503.58 | 01-OCT-09:01 | 0.92 |
November | 0.779521E+09 | 0.28 | 935.67 | 11-NOV-10:02 | 0.73 |
December | 0.799524E+09 | 0.28 | 1323.50 | 23-DEC-09:02 | 0.88 |
Annual Sum or Average | 0.111094E+11 | 0.30 | |||
Minimum of Months | 0.728000E+09 | 0.28 | 935.67 | 0.73 | |
Maximum of Months | 0.119203E+10 | 0.35 | 1503.58 | 0.93 |
Report: ZoneTemperatureOscillationReportMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 1.03 | 1.09 |
February | 0.14 | 0.00 |
March | 0.00 | 0.00 |
April | 0.36 | 0.69 |
May | 1.12 | 0.00 |
June | 1.68 | 0.00 |
July | 1.87 | 0.00 |
August | 1.33 | 0.00 |
September | 0.33 | 0.00 |
October | 1.42 | 0.18 |
November | 0.25 | 1.50 |
December | 0.53 | 1.11 |
Annual Sum or Average | 10.07 | 0.26 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 1.87 | 1.50 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 1.08 | 0.85 |
February | 0.14 | 0.00 |
March | 0.00 | 0.00 |
April | 0.28 | 0.00 |
May | 0.54 | 0.00 |
June | 0.60 | 0.00 |
July | 0.62 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 1.50 | 0.12 |
November | 0.00 | 0.00 |
December | 0.28 | 0.37 |
Annual Sum or Average | 5.04 | 0.24 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 1.50 | 0.85 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.72 | 0.00 |
February | 0.28 | 0.00 |
March | 1.62 | 0.75 |
April | 4.55 | 0.74 |
May | 5.22 | 0.72 |
June | 5.42 | 0.66 |
July | 5.62 | 0.66 |
August | 3.97 | 0.71 |
September | 4.33 | 0.72 |
October | 2.60 | 0.75 |
November | 0.44 | 0.61 |
December | 0.33 | 0.00 |
Annual Sum or Average | 35.09 | 0.68 |
Minimum of Months | 0.28 | 0.00 |
Maximum of Months | 5.62 | 0.75 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.42 | 0.00 |
February | 0.19 | 0.00 |
March | 1.62 | 0.75 |
April | 4.55 | 0.74 |
May | 5.18 | 0.74 |
June | 5.25 | 0.68 |
July | 5.37 | 0.68 |
August | 3.97 | 0.71 |
September | 4.33 | 0.72 |
October | 2.60 | 0.75 |
November | 0.44 | 0.61 |
December | 0.28 | 0.00 |
Annual Sum or Average | 34.19 | 0.69 |
Minimum of Months | 0.19 | 0.00 |
Maximum of Months | 5.37 | 0.75 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.33 | 0.00 |
February | 0.19 | 0.00 |
March | 1.62 | 0.75 |
April | 4.55 | 0.74 |
May | 5.22 | 0.73 |
June | 5.50 | 0.66 |
July | 5.62 | 0.66 |
August | 3.92 | 0.71 |
September | 4.33 | 0.72 |
October | 2.54 | 0.75 |
November | 0.35 | 0.75 |
December | 0.28 | 0.00 |
Annual Sum or Average | 34.45 | 0.69 |
Minimum of Months | 0.19 | 0.00 |
Maximum of Months | 5.62 | 0.75 |
Report: ZoneTemperatureOscillationReportMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 1.06 | 0.78 |
February | 0.14 | 0.00 |
March | 0.46 | 3.30 |
April | 2.12 | 2.52 |
May | 1.98 | 1.75 |
June | 2.38 | 1.39 |
July | 2.85 | 2.00 |
August | 2.34 | 1.95 |
September | 2.38 | 2.41 |
October | 1.61 | 3.01 |
November | 0.35 | 3.30 |
December | 0.61 | 1.35 |
Annual Sum or Average | 18.27 | 2.04 |
Minimum of Months | 0.14 | 0.00 |
Maximum of Months | 2.85 | 3.30 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.89 | 0.31 |
February | 0.14 | 0.00 |
March | 0.38 | 1.65 |
April | 1.87 | 1.21 |
May | 1.48 | 1.17 |
June | 1.22 | 1.03 |
July | 2.06 | 1.28 |
August | 1.88 | 1.17 |
September | 1.71 | 1.44 |
October | 1.47 | 1.59 |
November | 0.35 | 1.65 |
December | 0.36 | 0.38 |
Annual Sum or Average | 13.80 | 1.19 |
Minimum of Months | 0.14 | 0.00 |
Maximum of Months | 2.06 | 1.65 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 1.06 | 0.52 |
February | 0.14 | 0.00 |
March | 0.38 | 1.65 |
April | 1.87 | 1.21 |
May | 1.48 | 1.17 |
June | 1.22 | 1.03 |
July | 2.06 | 1.28 |
August | 1.88 | 1.17 |
September | 1.71 | 1.44 |
October | 1.47 | 1.59 |
November | 0.35 | 1.65 |
December | 0.53 | 0.78 |
Annual Sum or Average | 14.13 | 1.21 |
Minimum of Months | 0.14 | 0.00 |
Maximum of Months | 2.06 | 1.65 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 1.08 | 0.76 |
February | 0.22 | 0.62 |
March | 0.38 | 1.65 |
April | 1.62 | 1.40 |
May | 1.48 | 1.17 |
June | 1.16 | 1.00 |
July | 2.06 | 1.28 |
August | 1.88 | 1.17 |
September | 1.71 | 1.44 |
October | 1.47 | 1.59 |
November | 0.30 | 1.65 |
December | 0.53 | 0.78 |
Annual Sum or Average | 13.88 | 1.24 |
Minimum of Months | 0.22 | 0.62 |
Maximum of Months | 2.06 | 1.65 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 1.28 | 0.97 |
February | 0.08 | 1.65 |
March | 0.46 | 1.65 |
April | 1.87 | 1.21 |
May | 1.39 | 1.24 |
June | 1.47 | 0.85 |
July | 2.50 | 1.02 |
August | 1.91 | 0.96 |
September | 1.96 | 1.32 |
October | 1.61 | 1.51 |
November | 0.35 | 1.65 |
December | 0.25 | 1.65 |
Annual Sum or Average | 15.13 | 1.17 |
Minimum of Months | 0.08 | 0.85 |
Maximum of Months | 2.50 | 1.65 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_1:1
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.260944E+10 | 0.136894E+09 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.386974E+10 | 1478527.44 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.704107E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.106129E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.151227E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.165735E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.175136E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.168342E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.140967E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.997500E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.622563E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.332377E+10 | 6641369.04 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.123798E+12 | 0.145014E+09 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.260944E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.175136E+11 | 0.136894E+09 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_2:2
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.147054E+10 | 28006030.98 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.212279E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.363547E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.530466E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.752691E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.818282E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.858403E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.824265E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.689598E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.495886E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.323890E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.188590E+10 | 6760.19 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.620495E+11 | 28012791.17 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.147054E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.858403E+10 | 28006030.98 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_3:3
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.109472E+10 | 0.110655E+09 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.160555E+10 | 628318.15 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.291190E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.428296E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.623659E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.676751E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.695359E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.683621E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.556358E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.398572E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.256707E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.139073E+10 | 4404258.18 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.501962E+11 | 0.115687E+09 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.109472E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.695359E+10 | 0.110655E+09 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_4:4
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.106793E+10 | 0.158458E+09 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.158249E+10 | 1654700.83 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.290711E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.429794E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.627523E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.680846E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.700213E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.687110E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.558895E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.399975E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.255810E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.136146E+10 | 7621555.61 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.503206E+11 | 0.167734E+09 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.106793E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.700213E+10 | 0.158458E+09 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_5:5
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.103001E+10 | 0.211742E+09 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.153507E+10 | 3793957.44 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.285738E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.425496E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.623081E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.676167E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.696197E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.682258E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.554366E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.396070E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.251421E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.131139E+10 | 10786195.23 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.497844E+11 | 0.226322E+09 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.103001E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.696197E+10 | 0.211742E+09 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_6:6
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.162419E+10 | 0.361335E+09 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.255089E+10 | 8624687.92 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.503988E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.767325E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.113993E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.124187E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.126960E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.125060E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.100546E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.711658E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.438138E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.207565E+10 | 20317163.44 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.895365E+11 | 0.390277E+09 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.162419E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.126960E+11 | 0.361335E+09 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_7:7
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.871077E+09 | 0.189008E+09 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.134069E+10 | 3293491.75 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.262537E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.398285E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.590870E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.642047E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.656213E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.645723E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.520163E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.369304E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.228736E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.110089E+10 | 9163114.45 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.464514E+11 | 0.201464E+09 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.871077E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.656213E+10 | 0.189008E+09 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_8:8
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.859659E+09 | 0.201962E+09 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.132084E+10 | 4495182.93 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.260177E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.395962E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.588211E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.639313E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.653714E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.643269E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.518000E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.367362E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.226847E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.108383E+10 | 10908283.37 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.461929E+11 | 0.217366E+09 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.859659E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.653714E+10 | 0.201962E+09 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_9:9
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.846272E+09 | 0.238087E+09 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.128485E+10 | 9149366.88 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.256180E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.393770E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.587330E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.639406E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.655078E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.644846E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.518850E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.366971E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.224688E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.105680E+10 | 15924239.27 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.460591E+11 | 0.263161E+09 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.846272E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.655078E+10 | 0.238087E+09 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_10:10
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.907662E+09 | 0.301728E+09 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.133058E+10 | 23766444.09 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.264582E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.415433E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.625285E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.684122E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.707135E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.698815E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.561943E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.397129E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.240311E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.112827E+10 | 27229072.01 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.493141E+11 | 0.352723E+09 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.907662E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.707135E+10 | 0.301728E+09 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_1:1
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.195541E+10 | 0.238603E+10 | 0.109515E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.176668E+10 | 0.782202E+10 | 1182821.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.195712E+10 | 0.188898E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.198125E+10 | 0.304616E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.235756E+10 | 0.447322E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.250684E+10 | 0.512291E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.268525E+10 | 0.588917E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.264681E+10 | 0.584694E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.227075E+10 | 0.483573E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.199241E+10 | 0.306741E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.188692E+10 | 0.164150E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.196050E+10 | 0.503114E+10 | 5313095.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.259675E+11 | 0.373359E+12 | 0.116011E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.176668E+10 | 0.238603E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.268525E+10 | 0.588917E+11 | 0.109515E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_2:2
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.849520E+09 | 0.225393E+10 | 22404824.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.790284E+09 | 0.499073E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.912169E+09 | 0.102104E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.963209E+09 | 0.153616E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.120036E+10 | 0.221700E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.128761E+10 | 0.251273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.137536E+10 | 0.286626E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.135182E+10 | 0.284333E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.114713E+10 | 0.234699E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.958863E+09 | 0.153945E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.868523E+09 | 0.903123E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.860520E+09 | 0.378685E+10 | 5408.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.125654E+11 | 0.188892E+12 | 22410232.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.790284E+09 | 0.225393E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.137536E+10 | 0.286626E+11 | 22404824.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_3:3
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.844909E+09 | 0.926817E+09 | 88523770.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.762926E+09 | 0.318573E+10 | 502654.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.859776E+09 | 0.774887E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.864637E+09 | 0.122788E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.106648E+10 | 0.183513E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.113672E+10 | 0.208484E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.119334E+10 | 0.233137E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.119478E+10 | 0.236661E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.997816E+09 | 0.190343E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.861796E+09 | 0.121790E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.817407E+09 | 0.670678E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.838460E+09 | 0.206979E+10 | 3523406.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.114390E+11 | 0.150310E+12 | 92549831.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.762926E+09 | 0.926817E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.119478E+10 | 0.236661E+11 | 88523770.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_4:4
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.847803E+09 | 0.814832E+09 | 0.126766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.764649E+09 | 0.308540E+10 | 1323760.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.861708E+09 | 0.771740E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.866777E+09 | 0.123276E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.107131E+10 | 0.184790E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.114261E+10 | 0.209796E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.120144E+10 | 0.234699E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.120045E+10 | 0.237825E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.100130E+10 | 0.191263E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.864058E+09 | 0.122267E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.819229E+09 | 0.665835E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.840397E+09 | 0.194795E+10 | 6097244.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.114817E+11 | 0.150616E+12 | 0.134187E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.764649E+09 | 0.814832E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.120144E+10 | 0.237825E+11 | 0.126766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_5:5
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.845972E+09 | 0.679161E+09 | 0.169394E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.762012E+09 | 0.290675E+10 | 3035165.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.858613E+09 | 0.752198E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.862063E+09 | 0.121753E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.106508E+10 | 0.183393E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.113527E+10 | 0.208338E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.119486E+10 | 0.233378E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.119258E+10 | 0.236193E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.994524E+09 | 0.189666E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.860179E+09 | 0.120734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.816355E+09 | 0.648537E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.837517E+09 | 0.176600E+10 | 8628956.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.114250E+11 | 0.148705E+12 | 0.181058E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.762012E+09 | 0.679161E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.119486E+10 | 0.236193E+11 | 0.169394E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_6:6
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.136624E+10 | 0.931405E+09 | 0.289068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.123088E+10 | 0.485014E+10 | 6899750.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.138895E+10 | 0.134538E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.140319E+10 | 0.220338E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.176842E+10 | 0.335219E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.190233E+10 | 0.381515E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.200701E+10 | 0.424957E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.200795E+10 | 0.432967E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.165311E+10 | 0.344025E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.139654E+10 | 0.218775E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.131893E+10 | 0.114612E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.135199E+10 | 0.264032E+10 | 16253730.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.187955E+11 | 0.269116E+12 | 0.312221E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.123088E+10 | 0.931405E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.200795E+10 | 0.432967E+11 | 0.289068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_7:7
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.750325E+09 | 0.443073E+09 | 0.151206E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.675989E+09 | 0.248132E+10 | 2634793.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.762760E+09 | 0.697175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.769991E+09 | 0.114641E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.969314E+09 | 0.174494E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.103769E+10 | 0.198251E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.109316E+10 | 0.220831E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.109225E+10 | 0.224771E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.902968E+09 | 0.178757E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.766166E+09 | 0.113678E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.724332E+09 | 0.594249E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.742498E+09 | 0.132881E+10 | 7330491.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.102874E+11 | 0.139710E+12 | 0.161171E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.675989E+09 | 0.443073E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.109316E+10 | 0.224771E+11 | 0.151206E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_8:8
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.747483E+09 | 0.411191E+09 | 0.161570E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.673194E+09 | 0.241467E+10 | 3596146.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.759551E+09 | 0.688928E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.766405E+09 | 0.113901E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.965000E+09 | 0.173712E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.103314E+10 | 0.197438E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.108879E+10 | 0.220049E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.108795E+10 | 0.223983E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.899144E+09 | 0.178050E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.762831E+09 | 0.113021E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.721296E+09 | 0.587816E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.739438E+09 | 0.127580E+10 | 8726626.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.102442E+11 | 0.138884E+12 | 0.173893E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.673194E+09 | 0.411191E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.108879E+10 | 0.223983E+11 | 0.161570E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_9:9
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.748745E+09 | 0.356615E+09 | 0.190470E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.673744E+09 | 0.227077E+10 | 7319493.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.759987E+09 | 0.671901E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.765655E+09 | 0.113007E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.964567E+09 | 0.173354E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.103404E+10 | 0.197397E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.109149E+10 | 0.220445E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.109102E+10 | 0.224492E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.900718E+09 | 0.178321E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.763403E+09 | 0.112806E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.721745E+09 | 0.578542E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.740039E+09 | 0.117097E+10 | 12739391.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.102552E+11 | 0.138285E+12 | 0.210529E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.673744E+09 | 0.356615E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.109149E+10 | 0.224492E+11 | 0.190470E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_10:10
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.809706E+09 | 0.357385E+09 | 0.241382E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.728000E+09 | 0.222788E+10 | 19013155.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.820723E+09 | 0.675765E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.823645E+09 | 0.118232E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.103769E+10 | 0.183631E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.111903E+10 | 0.209753E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.118933E+10 | 0.236369E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.119203E+10 | 0.241653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.982457E+09 | 0.192076E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.827761E+09 | 0.122161E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.779521E+09 | 0.615920E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.799524E+09 | 0.121443E+10 | 21783257.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.111094E+11 | 0.147104E+12 | 0.282179E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.728000E+09 | 0.357385E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.119203E+10 | 0.241653E+11 | 0.241382E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_1:1
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.195541E+10 | 0.00 | 0.00 | 0.00 | 0.654028E+09 | 0.00 | 0.136894E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.176668E+10 | 0.00 | 0.00 | 0.00 | 0.210306E+10 | 0.00 | 1478527.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.195712E+10 | 0.00 | 0.00 | 0.00 | 0.508395E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.198125E+10 | 0.00 | 0.00 | 0.00 | 0.863161E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.235756E+10 | 0.00 | 0.00 | 0.00 | 0.127651E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.250684E+10 | 0.00 | 0.00 | 0.00 | 0.140667E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.268525E+10 | 0.00 | 0.00 | 0.00 | 0.148283E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.264681E+10 | 0.00 | 0.00 | 0.00 | 0.141874E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.227075E+10 | 0.00 | 0.00 | 0.00 | 0.118259E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.199241E+10 | 0.00 | 0.00 | 0.00 | 0.798259E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.188692E+10 | 0.00 | 0.00 | 0.00 | 0.433871E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.196050E+10 | 0.00 | 0.00 | 0.00 | 0.136327E+10 | 0.00 | 6641369.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.259675E+11 | 0.00 | 0.00 | 0.00 | 0.978306E+11 | 0.00 | 0.145014E+09 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.176668E+10 | 0.00 | 0.00 | 0.00 | 0.654028E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.268525E+10 | 0.00 | 0.00 | 0.00 | 0.148283E+11 | 0.00 | 0.136894E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_2:2
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.849520E+09 | 0.00 | 0.00 | 0.00 | 0.621023E+09 | 0.00 | 28006030.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.790284E+09 | 0.00 | 0.00 | 0.00 | 0.133251E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.912169E+09 | 0.00 | 0.00 | 0.00 | 0.272330E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.963209E+09 | 0.00 | 0.00 | 0.00 | 0.434145E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.120036E+10 | 0.00 | 0.00 | 0.00 | 0.632654E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.128761E+10 | 0.00 | 0.00 | 0.00 | 0.689521E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.137536E+10 | 0.00 | 0.00 | 0.00 | 0.720867E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.135182E+10 | 0.00 | 0.00 | 0.00 | 0.689083E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.114713E+10 | 0.00 | 0.00 | 0.00 | 0.574885E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.958863E+09 | 0.00 | 0.00 | 0.00 | 0.399999E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.868523E+09 | 0.00 | 0.00 | 0.00 | 0.237038E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.860520E+09 | 0.00 | 0.00 | 0.00 | 0.102538E+10 | 0.00 | 6760.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.125654E+11 | 0.00 | 0.00 | 0.00 | 0.494841E+11 | 0.00 | 28012791.17 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.790284E+09 | 0.00 | 0.00 | 0.00 | 0.621023E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.137536E+10 | 0.00 | 0.00 | 0.00 | 0.720867E+10 | 0.00 | 28006030.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_3:3
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.844909E+09 | 0.00 | 0.00 | 0.00 | 0.249815E+09 | 0.00 | 0.110655E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.762926E+09 | 0.00 | 0.00 | 0.00 | 0.842628E+09 | 0.00 | 628318.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.859776E+09 | 0.00 | 0.00 | 0.00 | 0.205213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.864637E+09 | 0.00 | 0.00 | 0.00 | 0.341832E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.106648E+10 | 0.00 | 0.00 | 0.00 | 0.517011E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.113672E+10 | 0.00 | 0.00 | 0.00 | 0.563079E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.119334E+10 | 0.00 | 0.00 | 0.00 | 0.576025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.119478E+10 | 0.00 | 0.00 | 0.00 | 0.564143E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.997816E+09 | 0.00 | 0.00 | 0.00 | 0.456576E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.861796E+09 | 0.00 | 0.00 | 0.00 | 0.312392E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.817407E+09 | 0.00 | 0.00 | 0.00 | 0.174966E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.838460E+09 | 0.00 | 0.00 | 0.00 | 0.552271E+09 | 0.00 | 4404258.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.114390E+11 | 0.00 | 0.00 | 0.00 | 0.387571E+11 | 0.00 | 0.115687E+09 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.762926E+09 | 0.00 | 0.00 | 0.00 | 0.249815E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.119478E+10 | 0.00 | 0.00 | 0.00 | 0.576025E+10 | 0.00 | 0.110655E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_4:4
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.847803E+09 | 0.00 | 0.00 | 0.00 | 0.220129E+09 | 0.00 | 0.158458E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.764649E+09 | 0.00 | 0.00 | 0.00 | 0.817844E+09 | 0.00 | 1654700.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.861708E+09 | 0.00 | 0.00 | 0.00 | 0.204540E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.866777E+09 | 0.00 | 0.00 | 0.00 | 0.343116E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.107131E+10 | 0.00 | 0.00 | 0.00 | 0.520392E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.114261E+10 | 0.00 | 0.00 | 0.00 | 0.566586E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.120144E+10 | 0.00 | 0.00 | 0.00 | 0.580068E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.120045E+10 | 0.00 | 0.00 | 0.00 | 0.567064E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.100130E+10 | 0.00 | 0.00 | 0.00 | 0.458764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.864058E+09 | 0.00 | 0.00 | 0.00 | 0.313569E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.819229E+09 | 0.00 | 0.00 | 0.00 | 0.173887E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.840397E+09 | 0.00 | 0.00 | 0.00 | 0.521061E+09 | 0.00 | 7621555.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.114817E+11 | 0.00 | 0.00 | 0.00 | 0.388389E+11 | 0.00 | 0.167734E+09 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.764649E+09 | 0.00 | 0.00 | 0.00 | 0.220129E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.120144E+10 | 0.00 | 0.00 | 0.00 | 0.580068E+10 | 0.00 | 0.158458E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_5:5
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.845972E+09 | 0.00 | 0.00 | 0.00 | 0.184040E+09 | 0.00 | 0.211742E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.762012E+09 | 0.00 | 0.00 | 0.00 | 0.773055E+09 | 0.00 | 3793957.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.858613E+09 | 0.00 | 0.00 | 0.00 | 0.199877E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.862063E+09 | 0.00 | 0.00 | 0.00 | 0.339289E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.106508E+10 | 0.00 | 0.00 | 0.00 | 0.516573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.113527E+10 | 0.00 | 0.00 | 0.00 | 0.562640E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.119486E+10 | 0.00 | 0.00 | 0.00 | 0.576711E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.119258E+10 | 0.00 | 0.00 | 0.00 | 0.563000E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.994524E+09 | 0.00 | 0.00 | 0.00 | 0.454914E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.860179E+09 | 0.00 | 0.00 | 0.00 | 0.310052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.816355E+09 | 0.00 | 0.00 | 0.00 | 0.169786E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.837517E+09 | 0.00 | 0.00 | 0.00 | 0.473876E+09 | 0.00 | 10786195.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.114250E+11 | 0.00 | 0.00 | 0.00 | 0.383594E+11 | 0.00 | 0.226322E+09 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.762012E+09 | 0.00 | 0.00 | 0.00 | 0.184040E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.119486E+10 | 0.00 | 0.00 | 0.00 | 0.576711E+10 | 0.00 | 0.211742E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_6:6
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.136624E+10 | 0.00 | 0.00 | 0.00 | 0.257953E+09 | 0.00 | 0.361335E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.123088E+10 | 0.00 | 0.00 | 0.00 | 0.132000E+10 | 0.00 | 8624687.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.138895E+10 | 0.00 | 0.00 | 0.00 | 0.365093E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.140319E+10 | 0.00 | 0.00 | 0.00 | 0.627007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.176842E+10 | 0.00 | 0.00 | 0.00 | 0.963085E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.190233E+10 | 0.00 | 0.00 | 0.00 | 0.105164E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.200701E+10 | 0.00 | 0.00 | 0.00 | 0.106890E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.200795E+10 | 0.00 | 0.00 | 0.00 | 0.104980E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.165311E+10 | 0.00 | 0.00 | 0.00 | 0.840152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.139654E+10 | 0.00 | 0.00 | 0.00 | 0.572004E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.131893E+10 | 0.00 | 0.00 | 0.00 | 0.306245E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.135199E+10 | 0.00 | 0.00 | 0.00 | 0.723661E+09 | 0.00 | 20317163.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.187955E+11 | 0.00 | 0.00 | 0.00 | 0.707409E+11 | 0.00 | 0.390277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.123088E+10 | 0.00 | 0.00 | 0.00 | 0.257953E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.200795E+10 | 0.00 | 0.00 | 0.00 | 0.106890E+11 | 0.00 | 0.361335E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_7:7
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.750325E+09 | 0.00 | 0.00 | 0.00 | 0.120752E+09 | 0.00 | 0.189008E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.675989E+09 | 0.00 | 0.00 | 0.00 | 0.664698E+09 | 0.00 | 3293491.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.762760E+09 | 0.00 | 0.00 | 0.00 | 0.186261E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.769991E+09 | 0.00 | 0.00 | 0.00 | 0.321286E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.969314E+09 | 0.00 | 0.00 | 0.00 | 0.493939E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.103769E+10 | 0.00 | 0.00 | 0.00 | 0.538279E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.109316E+10 | 0.00 | 0.00 | 0.00 | 0.546897E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.109225E+10 | 0.00 | 0.00 | 0.00 | 0.536497E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.902968E+09 | 0.00 | 0.00 | 0.00 | 0.429867E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.766166E+09 | 0.00 | 0.00 | 0.00 | 0.292688E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.724332E+09 | 0.00 | 0.00 | 0.00 | 0.156303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.742498E+09 | 0.00 | 0.00 | 0.00 | 0.358390E+09 | 0.00 | 9163114.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.102874E+11 | 0.00 | 0.00 | 0.00 | 0.361640E+11 | 0.00 | 0.201464E+09 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.675989E+09 | 0.00 | 0.00 | 0.00 | 0.120752E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.109316E+10 | 0.00 | 0.00 | 0.00 | 0.546897E+10 | 0.00 | 0.189008E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_8:8
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.747483E+09 | 0.00 | 0.00 | 0.00 | 0.112176E+09 | 0.00 | 0.201962E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.673194E+09 | 0.00 | 0.00 | 0.00 | 0.647646E+09 | 0.00 | 4495182.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.759551E+09 | 0.00 | 0.00 | 0.00 | 0.184222E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.766405E+09 | 0.00 | 0.00 | 0.00 | 0.319321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.965000E+09 | 0.00 | 0.00 | 0.00 | 0.491711E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.103314E+10 | 0.00 | 0.00 | 0.00 | 0.535999E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.108879E+10 | 0.00 | 0.00 | 0.00 | 0.544835E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.108795E+10 | 0.00 | 0.00 | 0.00 | 0.534475E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.899144E+09 | 0.00 | 0.00 | 0.00 | 0.428086E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.762831E+09 | 0.00 | 0.00 | 0.00 | 0.291078E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.721296E+09 | 0.00 | 0.00 | 0.00 | 0.154718E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.739438E+09 | 0.00 | 0.00 | 0.00 | 0.344390E+09 | 0.00 | 10908283.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.102442E+11 | 0.00 | 0.00 | 0.00 | 0.359487E+11 | 0.00 | 0.217366E+09 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.673194E+09 | 0.00 | 0.00 | 0.00 | 0.112176E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.108879E+10 | 0.00 | 0.00 | 0.00 | 0.544835E+10 | 0.00 | 0.201962E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_9:9
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.748745E+09 | 0.00 | 0.00 | 0.00 | 97527115.77 | 0.00 | 0.238087E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.673744E+09 | 0.00 | 0.00 | 0.00 | 0.611105E+09 | 0.00 | 9149366.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.759987E+09 | 0.00 | 0.00 | 0.00 | 0.180181E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.765655E+09 | 0.00 | 0.00 | 0.00 | 0.317205E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.964567E+09 | 0.00 | 0.00 | 0.00 | 0.490873E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.103404E+10 | 0.00 | 0.00 | 0.00 | 0.536002E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.109149E+10 | 0.00 | 0.00 | 0.00 | 0.545929E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.109102E+10 | 0.00 | 0.00 | 0.00 | 0.535743E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.900718E+09 | 0.00 | 0.00 | 0.00 | 0.428778E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.763403E+09 | 0.00 | 0.00 | 0.00 | 0.290630E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.721745E+09 | 0.00 | 0.00 | 0.00 | 0.152513E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.740039E+09 | 0.00 | 0.00 | 0.00 | 0.316758E+09 | 0.00 | 15924239.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.102552E+11 | 0.00 | 0.00 | 0.00 | 0.358039E+11 | 0.00 | 0.263161E+09 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.673744E+09 | 0.00 | 0.00 | 0.00 | 97527115.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.109149E+10 | 0.00 | 0.00 | 0.00 | 0.545929E+10 | 0.00 | 0.238087E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_10:10
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.809706E+09 | 0.00 | 0.00 | 0.00 | 97956359.76 | 0.00 | 0.301728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.728000E+09 | 0.00 | 0.00 | 0.00 | 0.602581E+09 | 0.00 | 23766444.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.820723E+09 | 0.00 | 0.00 | 0.00 | 0.182510E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.823645E+09 | 0.00 | 0.00 | 0.00 | 0.333069E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.103769E+10 | 0.00 | 0.00 | 0.00 | 0.521516E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.111903E+10 | 0.00 | 0.00 | 0.00 | 0.572219E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.118933E+10 | 0.00 | 0.00 | 0.00 | 0.588202E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.119203E+10 | 0.00 | 0.00 | 0.00 | 0.579611E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.982457E+09 | 0.00 | 0.00 | 0.00 | 0.463698E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.827761E+09 | 0.00 | 0.00 | 0.00 | 0.314353E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.779521E+09 | 0.00 | 0.00 | 0.00 | 0.162359E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.799524E+09 | 0.00 | 0.00 | 0.00 | 0.328744E+09 | 0.00 | 27229072.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.111094E+11 | 0.00 | 0.00 | 0.00 | 0.382046E+11 | 0.00 | 0.352723E+09 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.728000E+09 | 0.00 | 0.00 | 0.00 | 97956359.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.119203E+10 | 0.00 | 0.00 | 0.00 | 0.588202E+10 | 0.00 | 0.301728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.390874E+10 | 283594.23 | 0.00 | 6511869.96 | 0.00 | 33463307.78 | 0.351315E+10 | 0.00 | 0.57 |
February | 0.138072E+10 | 0.198604E+09 | 0.00 | 9153552.03 | 0.00 | 684046.26 | 0.224254E+10 | 0.00 | 0.57 |
March | 0.292250E+09 | 0.274855E+10 | 0.00 | 5250135.19 | 5949068.70 | 0.00 | 0.588333E+09 | 0.00 | 0.57 |
April | 13375498.94 | 0.804829E+10 | 0.00 | 455516.58 | 0.203158E+09 | 0.00 | 15844509.65 | 0.00 | 0.58 |
May | 64252.91 | 0.157742E+11 | 0.00 | 12107.44 | 0.194061E+09 | 0.00 | 598326.63 | 0.00 | 0.58 |
June | 0.00 | 0.203577E+11 | 0.00 | 0.00 | 0.199277E+09 | 0.00 | 0.00 | 0.00 | 0.58 |
July | 0.00 | 0.251898E+11 | 0.00 | 0.00 | 0.146247E+09 | 0.00 | 0.00 | 0.00 | 0.58 |
August | 0.00 | 0.250956E+11 | 0.00 | 0.00 | 0.247215E+09 | 0.00 | 0.00 | 0.00 | 0.58 |
September | 0.00 | 0.191215E+11 | 0.00 | 0.00 | 0.396175E+09 | 0.00 | 0.00 | 0.00 | 0.58 |
October | 84607793.27 | 0.729868E+10 | 0.00 | 1039396.77 | 0.118355E+09 | 0.00 | 49236780.46 | 0.00 | 0.57 |
November | 0.376059E+09 | 0.142437E+10 | 0.00 | 8787431.87 | 97923.58 | 0.00 | 0.154792E+10 | 0.00 | 0.57 |
December | 0.245382E+10 | 10109830.15 | 0.00 | 10945658.21 | 0.00 | 1617329.52 | 0.408986E+10 | 0.00 | 0.57 |
Annual Sum or Average | 0.850964E+10 | 0.125268E+12 | 0.00 | 42155668.06 | 0.151053E+10 | 35764683.56 | 0.120475E+11 | 0.00 | 0.58 |
Minimum of Months | 0.00 | 283594.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.57 |
Maximum of Months | 0.390874E+10 | 0.251898E+11 | 0.00 | 10945658.21 | 0.396175E+09 | 33463307.78 | 0.408986E+10 | 0.00 | 0.58 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.112036E+10 | 136529.27 | 0.00 | 4676164.30 | 0.00 | 8598985.40 | 0.143123E+10 | 0.00 | 0.44 |
February | 0.434682E+09 | 0.103108E+09 | 0.00 | 5448937.15 | 0.00 | 0.00 | 0.687276E+09 | 0.00 | 0.45 |
March | 98788203.86 | 0.125966E+10 | 0.00 | 2798057.86 | 12549253.75 | 0.00 | 0.156768E+09 | 0.00 | 0.47 |
April | 5883644.54 | 0.345643E+10 | 0.00 | 266711.42 | 0.113913E+09 | 0.00 | 4879404.21 | 0.00 | 0.48 |
May | 10138.84 | 0.693138E+10 | 0.00 | 3997.70 | 0.106072E+09 | 0.00 | 29958.83 | 0.00 | 0.50 |
June | 0.00 | 0.900844E+10 | 0.00 | 0.00 | 0.107354E+09 | 0.00 | 0.00 | 0.00 | 0.51 |
July | 0.00 | 0.111230E+11 | 0.00 | 0.00 | 0.104915E+09 | 0.00 | 0.00 | 0.00 | 0.51 |
August | 0.00 | 0.111016E+11 | 0.00 | 0.00 | 0.166216E+09 | 0.00 | 0.00 | 0.00 | 0.51 |
September | 0.00 | 0.820888E+10 | 0.00 | 0.00 | 0.301428E+09 | 0.00 | 0.00 | 0.00 | 0.50 |
October | 18972859.08 | 0.320670E+10 | 0.00 | 214377.32 | 94523397.66 | 0.00 | 5451446.98 | 0.00 | 0.47 |
November | 0.136050E+09 | 0.709548E+09 | 0.00 | 4395626.58 | 790643.88 | 0.00 | 0.336929E+09 | 0.00 | 0.46 |
December | 0.775791E+09 | 5257315.21 | 0.00 | 6533444.56 | 0.00 | 0.00 | 0.130506E+10 | 0.00 | 0.44 |
Annual Sum or Average | 0.259053E+10 | 0.551142E+11 | 0.00 | 24337316.88 | 0.100776E+10 | 8598985.40 | 0.392763E+10 | 0.00 | 0.48 |
Minimum of Months | 0.00 | 136529.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.44 |
Maximum of Months | 0.112036E+10 | 0.111230E+11 | 0.00 | 6533444.56 | 0.301428E+09 | 8598985.40 | 0.143123E+10 | 0.00 | 0.51 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.172653E+10 | 178457.41 | 0.00 | 2021200.60 | 0.00 | 40179389.49 | 0.885975E+09 | 0.00 | 0.45 |
February | 0.777693E+09 | 0.100101E+09 | 0.00 | 2755303.63 | 469510.49 | 0.00 | 0.512276E+09 | 0.00 | 0.45 |
March | 0.213940E+09 | 0.109780E+10 | 0.00 | 1606849.55 | 58674907.90 | 0.00 | 0.186670E+09 | 0.00 | 0.46 |
April | 11915247.18 | 0.297357E+10 | 0.00 | 251640.62 | 0.264095E+09 | 0.00 | 3154666.76 | 0.00 | 0.46 |
May | 1717943.00 | 0.580008E+10 | 0.00 | 58790.64 | 0.460402E+09 | 0.00 | 1665191.29 | 0.00 | 0.47 |
June | 17352.15 | 0.725481E+10 | 0.00 | 17.62 | 0.594246E+09 | 0.00 | 11860.92 | 0.00 | 0.47 |
July | 0.00 | 0.861914E+10 | 0.00 | 0.00 | 0.682966E+09 | 0.00 | 0.00 | 0.00 | 0.46 |
August | 0.00 | 0.881540E+10 | 0.00 | 0.00 | 0.687451E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
September | 1121878.39 | 0.647671E+10 | 0.00 | 40515.20 | 0.578673E+09 | 0.00 | 26267.11 | 0.00 | 0.46 |
October | 76703937.70 | 0.269735E+10 | 0.00 | 665256.01 | 0.192360E+09 | 0.00 | 38359033.06 | 0.00 | 0.46 |
November | 0.364644E+09 | 0.663880E+09 | 0.00 | 2048986.23 | 12246225.70 | 0.00 | 0.322371E+09 | 0.00 | 0.46 |
December | 0.129537E+10 | 5568768.11 | 0.00 | 3524396.70 | 0.00 | 697720.33 | 0.913365E+09 | 0.00 | 0.45 |
Annual Sum or Average | 0.446965E+10 | 0.445046E+11 | 0.00 | 12972956.81 | 0.353158E+10 | 40877109.82 | 0.286387E+10 | 0.00 | 0.46 |
Minimum of Months | 0.00 | 178457.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.45 |
Maximum of Months | 0.172653E+10 | 0.881540E+10 | 0.00 | 3524396.70 | 0.687451E+09 | 40179389.49 | 0.913365E+09 | 0.00 | 0.47 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.178457E+10 | 163701.54 | 0.00 | 1744287.35 | 0.00 | 56315385.36 | 0.785740E+09 | 0.00 | 0.45 |
February | 0.788952E+09 | 98923074.28 | 0.00 | 2642225.14 | 465974.64 | 613708.07 | 0.497129E+09 | 0.00 | 0.45 |
March | 0.217822E+09 | 0.109691E+10 | 0.00 | 1608444.94 | 58680047.60 | 0.00 | 0.182461E+09 | 0.00 | 0.46 |
April | 12254611.19 | 0.297945E+10 | 0.00 | 263146.93 | 0.260846E+09 | 0.00 | 3106646.76 | 0.00 | 0.46 |
May | 1788199.39 | 0.581924E+10 | 0.00 | 62170.60 | 0.452059E+09 | 0.00 | 1667969.74 | 0.00 | 0.47 |
June | 0.00 | 0.727360E+10 | 0.00 | 2155.21 | 0.591919E+09 | 0.00 | 2303.80 | 0.00 | 0.47 |
July | 0.00 | 0.865660E+10 | 0.00 | 0.00 | 0.672841E+09 | 0.00 | 0.00 | 0.00 | 0.46 |
August | 0.00 | 0.884449E+10 | 0.00 | 0.00 | 0.681257E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
September | 312660.71 | 0.650919E+10 | 0.00 | 37781.97 | 0.563424E+09 | 0.00 | 820438.46 | 0.00 | 0.46 |
October | 77189850.92 | 0.270297E+10 | 0.00 | 683612.32 | 0.191109E+09 | 0.00 | 38270300.20 | 0.00 | 0.46 |
November | 0.372465E+09 | 0.662539E+09 | 0.00 | 2014623.23 | 12231290.78 | 0.00 | 0.314446E+09 | 0.00 | 0.46 |
December | 0.131108E+10 | 5431983.39 | 0.00 | 3338282.47 | 0.00 | 688309.21 | 0.892712E+09 | 0.00 | 0.45 |
Annual Sum or Average | 0.456644E+10 | 0.446495E+11 | 0.00 | 12396730.17 | 0.348483E+10 | 57617402.64 | 0.271636E+10 | 0.00 | 0.46 |
Minimum of Months | 0.00 | 163701.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.45 |
Maximum of Months | 0.178457E+10 | 0.884449E+10 | 0.00 | 3338282.47 | 0.681257E+09 | 56315385.36 | 0.892712E+09 | 0.00 | 0.47 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.186761E+10 | 144536.65 | 0.00 | 1426156.32 | 0.00 | 75601658.10 | 0.652419E+09 | 0.00 | 0.45 |
February | 0.819472E+09 | 96608471.96 | 0.00 | 2429401.54 | 454614.08 | 607297.44 | 0.463506E+09 | 0.00 | 0.45 |
March | 0.226496E+09 | 0.108799E+10 | 0.00 | 1542046.30 | 58922173.34 | 0.00 | 0.174260E+09 | 0.00 | 0.46 |
April | 11363158.22 | 0.296970E+10 | 0.00 | 239012.08 | 0.265776E+09 | 0.00 | 3224934.62 | 0.00 | 0.46 |
May | 1692595.89 | 0.579906E+10 | 0.00 | 56592.14 | 0.460148E+09 | 0.00 | 1667647.57 | 0.00 | 0.47 |
June | 12132.31 | 0.724296E+10 | 0.00 | 587.53 | 0.603223E+09 | 0.00 | 3917.41 | 0.00 | 0.47 |
July | 0.00 | 0.861192E+10 | 0.00 | 0.00 | 0.693320E+09 | 0.00 | 0.00 | 0.00 | 0.46 |
August | 0.00 | 0.880129E+10 | 0.00 | 0.00 | 0.693143E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
September | 1117796.29 | 0.645475E+10 | 0.00 | 41037.37 | 0.590630E+09 | 0.00 | 31658.20 | 0.00 | 0.46 |
October | 76208084.33 | 0.268862E+10 | 0.00 | 655355.27 | 0.192289E+09 | 0.00 | 39430134.24 | 0.00 | 0.46 |
November | 0.382551E+09 | 0.656172E+09 | 0.00 | 1938866.88 | 12211856.54 | 0.00 | 0.305723E+09 | 0.00 | 0.46 |
December | 0.133906E+10 | 5247067.34 | 0.00 | 3046938.05 | 0.00 | 1394954.61 | 0.858954E+09 | 0.00 | 0.45 |
Annual Sum or Average | 0.472559E+10 | 0.444145E+11 | 0.00 | 11375993.49 | 0.357012E+10 | 77603910.15 | 0.249922E+10 | 0.00 | 0.46 |
Minimum of Months | 0.00 | 144536.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.45 |
Maximum of Months | 0.186761E+10 | 0.880129E+10 | 0.00 | 3046938.05 | 0.693320E+09 | 75601658.10 | 0.858954E+09 | 0.00 | 0.47 |
Report: MechanicalVentilationLoadsMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.337553E+10 | 0.00 | 0.00 | 1990720.67 | 0.00 | 0.121494E+09 | 0.104542E+10 | 0.00 | 0.42 |
February | 0.121765E+10 | 0.146228E+09 | 0.00 | 4478692.71 | 384696.15 | 3064315.85 | 0.933198E+09 | 0.00 | 0.42 |
March | 0.283546E+09 | 0.211867E+10 | 0.00 | 2758549.22 | 51162049.26 | 0.00 | 0.254762E+09 | 0.00 | 0.43 |
April | 11413716.60 | 0.580980E+10 | 0.00 | 146434.13 | 0.348679E+09 | 0.00 | 2465777.09 | 0.00 | 0.42 |
May | 142850.30 | 0.114664E+11 | 0.00 | 16238.45 | 0.360274E+09 | 0.00 | 551758.47 | 0.00 | 0.43 |
June | 0.00 | 0.143697E+11 | 0.00 | 0.00 | 0.382650E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
July | 0.00 | 0.167689E+11 | 0.00 | 0.00 | 0.547787E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
August | 0.00 | 0.174184E+11 | 0.00 | 0.00 | 0.547930E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
September | 18927.85 | 0.125538E+11 | 0.00 | 14598.20 | 0.719717E+09 | 0.00 | 29067.30 | 0.00 | 0.43 |
October | 83380171.77 | 0.526571E+10 | 0.00 | 727661.34 | 0.245130E+09 | 0.00 | 25152997.54 | 0.00 | 0.42 |
November | 0.416798E+09 | 0.119203E+10 | 0.00 | 3719630.33 | 19635180.93 | 0.00 | 0.550825E+09 | 0.00 | 0.42 |
December | 0.212851E+10 | 6419797.25 | 0.00 | 4892920.19 | 0.00 | 3203952.35 | 0.180895E+10 | 0.00 | 0.41 |
Annual Sum or Average | 0.751699E+10 | 0.871159E+11 | 0.00 | 18745445.25 | 0.322335E+10 | 0.127763E+09 | 0.462135E+10 | 0.00 | 0.43 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.337553E+10 | 0.174184E+11 | 0.00 | 4892920.19 | 0.719717E+09 | 0.121494E+09 | 0.180895E+10 | 0.00 | 0.44 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.170720E+10 | 0.00 | 0.00 | 903113.05 | 0.00 | 69972426.49 | 0.476924E+09 | 0.00 | 0.42 |
February | 0.617487E+09 | 72750336.36 | 0.00 | 2235675.21 | 187548.09 | 1543376.58 | 0.456146E+09 | 0.00 | 0.42 |
March | 0.143742E+09 | 0.105714E+10 | 0.00 | 1393322.77 | 25313066.19 | 0.00 | 0.125628E+09 | 0.00 | 0.43 |
April | 5642412.94 | 0.290388E+10 | 0.00 | 65387.06 | 0.180853E+09 | 0.00 | 1250533.28 | 0.00 | 0.42 |
May | 94391.66 | 0.571636E+10 | 0.00 | 6000.54 | 0.194642E+09 | 0.00 | 242341.29 | 0.00 | 0.43 |
June | 0.00 | 0.715769E+10 | 0.00 | 0.00 | 0.202622E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
July | 0.00 | 0.833521E+10 | 0.00 | 0.00 | 0.285002E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
August | 0.00 | 0.864340E+10 | 0.00 | 0.00 | 0.290888E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
September | 84688.87 | 0.623346E+10 | 0.00 | 7356.70 | 0.368724E+09 | 0.00 | 128174.85 | 0.00 | 0.43 |
October | 42351608.67 | 0.262279E+10 | 0.00 | 363147.79 | 0.122396E+09 | 0.00 | 12065507.61 | 0.00 | 0.42 |
November | 0.209344E+09 | 0.592270E+09 | 0.00 | 1879547.09 | 9594592.16 | 0.00 | 0.274836E+09 | 0.00 | 0.42 |
December | 0.107628E+10 | 3169939.21 | 0.00 | 2387454.91 | 0.00 | 1612896.45 | 0.889940E+09 | 0.00 | 0.41 |
Annual Sum or Average | 0.380223E+10 | 0.433381E+11 | 0.00 | 9241005.09 | 0.168022E+10 | 73128699.52 | 0.223716E+10 | 0.00 | 0.43 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.170720E+10 | 0.864340E+10 | 0.00 | 2387454.91 | 0.368724E+09 | 69972426.49 | 0.889940E+09 | 0.00 | 0.44 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.172595E+10 | 0.00 | 0.00 | 830165.18 | 0.00 | 73145852.08 | 0.443281E+09 | 0.00 | 0.42 |
February | 0.626497E+09 | 72104504.77 | 0.00 | 2157759.34 | 188580.44 | 1531206.78 | 0.445980E+09 | 0.00 | 0.42 |
March | 0.147007E+09 | 0.105341E+10 | 0.00 | 1365460.52 | 25399804.72 | 0.00 | 0.122589E+09 | 0.00 | 0.43 |
April | 5591288.86 | 0.290023E+10 | 0.00 | 64515.22 | 0.182077E+09 | 0.00 | 1267476.02 | 0.00 | 0.42 |
May | 64976.65 | 0.570446E+10 | 0.00 | 5004.52 | 0.199717E+09 | 0.00 | 274630.33 | 0.00 | 0.43 |
June | 0.00 | 0.714265E+10 | 0.00 | 0.00 | 0.208028E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
July | 0.00 | 0.832247E+10 | 0.00 | 0.00 | 0.285525E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
August | 0.00 | 0.862069E+10 | 0.00 | 0.00 | 0.300173E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
September | 89715.41 | 0.621938E+10 | 0.00 | 7055.45 | 0.371289E+09 | 0.00 | 138914.24 | 0.00 | 0.43 |
October | 42095195.19 | 0.261655E+10 | 0.00 | 358043.27 | 0.123050E+09 | 0.00 | 12358519.23 | 0.00 | 0.42 |
November | 0.211540E+09 | 0.589897E+09 | 0.00 | 1846396.15 | 9603373.90 | 0.00 | 0.273708E+09 | 0.00 | 0.42 |
December | 0.110276E+10 | 3133672.73 | 0.00 | 2288106.74 | 0.00 | 1606392.15 | 0.860974E+09 | 0.00 | 0.41 |
Annual Sum or Average | 0.386159E+10 | 0.432450E+11 | 0.00 | 8922506.39 | 0.170505E+10 | 76283451.01 | 0.216057E+10 | 0.00 | 0.43 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.172595E+10 | 0.862069E+10 | 0.00 | 2288106.74 | 0.371289E+09 | 73145852.08 | 0.860974E+09 | 0.00 | 0.44 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.174705E+10 | 0.00 | 0.00 | 702011.88 | 0.00 | 92274468.73 | 0.377364E+09 | 0.00 | 0.42 |
February | 0.648601E+09 | 70673002.74 | 0.00 | 1977181.39 | 191325.68 | 2335290.98 | 0.416679E+09 | 0.00 | 0.42 |
March | 0.148296E+09 | 0.104497E+10 | 0.00 | 1292300.71 | 25940833.30 | 0.00 | 0.120502E+09 | 0.00 | 0.43 |
April | 5423152.46 | 0.289496E+10 | 0.00 | 62072.30 | 0.184906E+09 | 0.00 | 1319089.19 | 0.00 | 0.42 |
May | 171852.26 | 0.568784E+10 | 0.00 | 3456.44 | 0.211665E+09 | 0.00 | 156740.66 | 0.00 | 0.43 |
June | 0.00 | 0.712802E+10 | 0.00 | 0.00 | 0.219405E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
July | 0.00 | 0.832371E+10 | 0.00 | 0.00 | 0.288697E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
August | 0.00 | 0.862595E+10 | 0.00 | 0.00 | 0.302659E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
September | 85517.05 | 0.622129E+10 | 0.00 | 7480.22 | 0.372964E+09 | 0.00 | 128384.12 | 0.00 | 0.43 |
October | 41645781.72 | 0.261273E+10 | 0.00 | 349482.17 | 0.124374E+09 | 0.00 | 12607149.15 | 0.00 | 0.42 |
November | 0.213336E+09 | 0.586228E+09 | 0.00 | 1785294.13 | 9622095.67 | 0.00 | 0.272651E+09 | 0.00 | 0.42 |
December | 0.114889E+10 | 3064601.68 | 0.00 | 2078478.96 | 0.00 | 2460242.10 | 0.804921E+09 | 0.00 | 0.41 |
Annual Sum or Average | 0.395350E+10 | 0.431994E+11 | 0.00 | 8257758.20 | 0.174042E+10 | 97070001.81 | 0.200633E+10 | 0.00 | 0.43 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.174705E+10 | 0.862595E+10 | 0.00 | 2078478.96 | 0.372964E+09 | 92274468.73 | 0.804921E+09 | 0.00 | 0.44 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:21:12
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.171740E+10 | 0.00 | 0.00 | 665772.55 | 0.00 | 0.115052E+09 | 0.355436E+09 | 0.00 | 0.42 |
February | 0.651645E+09 | 69324158.76 | 0.00 | 1858138.85 | 194250.09 | 4984324.98 | 0.385252E+09 | 0.00 | 0.42 |
March | 0.155946E+09 | 0.103254E+10 | 0.00 | 1224057.03 | 24572087.94 | 0.00 | 0.111347E+09 | 0.00 | 0.43 |
April | 5075105.36 | 0.289924E+10 | 0.00 | 61940.28 | 0.177609E+09 | 0.00 | 1652459.17 | 0.00 | 0.42 |
May | 407737.83 | 0.571168E+10 | 0.00 | 21803.13 | 0.177587E+09 | 0.00 | 242115.79 | 0.00 | 0.43 |
June | 276445.34 | 0.718427E+10 | 0.00 | 897.62 | 0.194333E+09 | 0.00 | 477547.88 | 0.00 | 0.44 |
July | 0.00 | 0.843233E+10 | 0.00 | 0.00 | 0.246096E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
August | 0.00 | 0.884096E+10 | 0.00 | 0.00 | 0.225178E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
September | 117233.53 | 0.641215E+10 | 0.00 | 15604.24 | 0.302131E+09 | 0.00 | 149281.05 | 0.00 | 0.43 |
October | 40173339.39 | 0.266377E+10 | 0.00 | 347904.09 | 0.117072E+09 | 0.00 | 12918554.92 | 0.00 | 0.42 |
November | 0.215024E+09 | 0.592421E+09 | 0.00 | 1844824.94 | 9316178.42 | 0.00 | 0.263742E+09 | 0.00 | 0.42 |
December | 0.115764E+10 | 3043324.02 | 0.00 | 2062614.61 | 0.00 | 5573569.77 | 0.760797E+09 | 0.00 | 0.41 |
Annual Sum or Average | 0.394370E+10 | 0.438417E+11 | 0.00 | 8103557.34 | 0.147409E+10 | 0.125610E+09 | 0.189201E+10 | 0.00 | 0.43 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.171740E+10 | 0.884096E+10 | 0.00 | 2062614.61 | 0.302131E+09 | 0.115052E+09 | 0.760797E+09 | 0.00 | 0.44 |