Program Version:EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:18
Tabular Output Report in Format: HTML
Building: RetailStripmall
Environment: RUNPERIOD 1 ** Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930
Simulation Timestamp: 2020-06-03 19:18:58
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2020-06-03 19:18:58
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1583.51 | 757.54 | 757.54 |
Net Site Energy | 1583.51 | 757.54 | 757.54 |
Total Source Energy | 4425.27 | 2117.03 | 2117.03 |
Net Source Energy | 4425.27 | 2117.03 | 2117.03 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 2090.32 |
Net Conditioned Building Area | 2090.32 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 283.10 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 44.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 704.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 110.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 128.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 248.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 64.37 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1300.41 | 283.10 | 0.00 | 0.00 | 0.00 | 87.30 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 283.10 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 44.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 704.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 110.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 128.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 248.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 64.37 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 389.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 170.78 | 135.43 | 0.00 | 0.00 | 0.00 | 0.04 |
Other | 61.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 622.11 | 135.43 | 0.00 | 0.00 | 0.00 | 0.04 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 389.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 170.78 | 135.43 | 0.00 | 0.00 | 0.00 | 0.04 |
Other | 61.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 622.11 | 135.43 | 0.00 | 0.00 | 0.00 | 0.04 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1300.409 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1300.409 | 100.00 |
Total On-Site and Utility Electric Sources | 1300.409 | 100.00 |
Total Electricity End Uses | 1300.409 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 87.30 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 87.30 | 100.00 |
Total Water End Uses | 87.30 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 0.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 911.33 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Meter |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2009
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Meter |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTRIPMALL
| Meter |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4C
| Meter |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_SEATTLE
| Meter |ZoneCoolingSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ZoneHeatingSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ZoneElectricSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |SpaceGainsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |PeakSpaceGainsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |SpaceGainComponentsAtCoolingPeakMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ComfortReportSimple55Monthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |OccupantComfortDataSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |DXReportMonthly
| PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL |WindowReportMonthly
| LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR |WindowEnergyReportMonthly
| LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR |WindowZoneSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |WindowEnergyZoneSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| GAS TANK1 | GAS TANK2 | GAS TANK3 | GAS TANK4 | GAS TANK5 | GAS TANK6 | GAS TANK7 |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC_1:1_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_2:2_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_3:3_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_4:4_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_5:5_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_6:6_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_7:7_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_8:8_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_9:9_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_10:10_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL |FanReportMonthly
| PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN |ZoneTemperatureOscillationReportMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |MechanicalVentilationLoadsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2020-06-03 19:18:58
GeneralValue | |
Program Version and Build | EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:18 |
RunPeriod | RUNPERIOD 1 |
Weather File | Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930 |
Latitude [deg] | 47.47 |
Longitude [deg] | -122.3 |
Elevation [m] | 122.00 |
Time Zone | -8.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Above Ground Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Window Opening Area [m2] | 124.29 | 0.00 | 0.00 | 124.29 | 0.00 |
Gross Window-Wall Ratio [%] | 10.50 | 0.00 | 0.00 | 26.24 | 0.00 |
Above Ground Window-Wall Ratio [%] | 10.50 | 0.00 | 0.00 | 26.24 | 0.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Above Ground Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Window Opening Area [m2] | 124.29 | 0.00 | 0.00 | 124.29 | 0.00 |
Gross Window-Wall Ratio [%] | 10.50 | 0.00 | 0.00 | 26.24 | 0.00 |
Above Ground Window-Wall Ratio [%] | 10.50 | 0.00 | 0.00 | 26.24 | 0.00 |
Total | |
Gross Roof Area [m2] | 2090.32 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
LGSTORE1 | 348.39 | Yes | Yes | 1805.20 | 1.00 | 276.30 | 0.00 | 20.75 | 20.75 | 24.9638 | 11.61 | 4.3000 |
SMSTORE1 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.37 | 10.37 | 27.8378 | 11.61 | 4.3000 |
SMSTORE2 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.35 | 10.35 | 25.6850 | 11.61 | 4.3000 |
SMSTORE3 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.35 | 10.35 | 25.6850 | 11.61 | 4.3000 |
SMSTORE4 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.35 | 10.35 | 25.6850 | 11.61 | 4.3000 |
LGSTORE2 | 348.39 | Yes | Yes | 1805.20 | 1.00 | 157.89 | 0.00 | 20.70 | 20.70 | 18.3225 | 11.61 | 4.3000 |
SMSTORE5 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.35 | 10.35 | 18.3225 | 11.61 | 4.3000 |
SMSTORE6 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.35 | 10.35 | 18.3225 | 11.61 | 4.3000 |
SMSTORE7 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.35 | 10.35 | 18.3225 | 11.61 | 4.3000 |
SMSTORE8 | 174.19 | Yes | Yes | 902.60 | 1.00 | 197.36 | 0.00 | 10.35 | 10.35 | 18.3225 | 11.61 | 4.3000 |
Total | 2090.32 | 10831.20 | 1184.15 | 0.00 | 124.29 | 124.29 | 22.0629 | 11.61 | 4.3000 | |||
Conditioned Total | 2090.32 | 10831.20 | 1184.15 | 0.00 | 124.29 | 124.29 | 22.0629 | 11.61 | 4.3000 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:18:58
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 29-AUG-13:39 | 19-FEB-09:09 | - | - | - | 06-JAN-13:09 |
Heating | 0.00 | 152633.90 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 38918.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 43812.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 8089.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 14352.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 7471.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 112644.66 | 152633.90 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 152633.90 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 38918.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 43812.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 8089.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 14352.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 7471.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:18:58
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 306.88 | 0.00 | 0.00 | 0.00 |
Cooling | 140.62 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 2230.12 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 350.08 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 407.66 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 786.07 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 203.86 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 4118.39 | 306.88 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 146.81 | 0.00 | 0.00 | 0.00 |
Cooling | 67.27 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1066.88 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 167.47 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 195.02 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 376.05 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 97.53 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1970.22 | 146.81 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 146.81 | 0.00 | 0.00 | 0.00 |
Cooling | 67.27 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1066.88 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 167.47 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 195.02 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 376.05 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 97.53 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1970.22 | 146.81 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:18:58
AirTerminal:SingleDuct:UncontrolledDesign Size Maximum Air Flow Rate [m3/s] | |
LGSTORE1 DIRECT AIR | 2.07 |
SMSTORE1 DIRECT AIR | 1.14 |
SMSTORE2 DIRECT AIR | 1.14 |
SMSTORE3 DIRECT AIR | 1.15 |
SMSTORE4 DIRECT AIR | 1.14 |
LGSTORE2 DIRECT AIR | 2.00 |
SMSTORE5 DIRECT AIR | 1.04 |
SMSTORE6 DIRECT AIR | 1.03 |
SMSTORE7 DIRECT AIR | 1.02 |
SMSTORE8 DIRECT AIR | 1.02 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC_1:1 | 2.07 | 2.07 | 2.07 | 2.07 | 2.07 | 2.07 | 1.00 | 1.00 | 2.07 |
PSZ-AC_2:2 | 1.14 | 1.14 | 1.14 | 1.14 | 1.14 | 1.14 | 1.00 | 1.00 | 1.14 |
PSZ-AC_3:3 | 1.14 | 1.14 | 1.14 | 1.14 | 1.14 | 1.14 | 1.00 | 1.00 | 1.14 |
PSZ-AC_4:4 | 1.15 | 1.15 | 1.15 | 1.15 | 1.15 | 1.15 | 1.00 | 1.00 | 1.15 |
PSZ-AC_5:5 | 1.14 | 1.14 | 1.14 | 1.14 | 1.14 | 1.14 | 1.00 | 1.000000 | 1.14 |
PSZ-AC_6:6 | 2.00 | 2.00 | 2.00 | 2.00 | 2.00 | 2.00 | 1.00 | 1.00 | 2.00 |
PSZ-AC_7:7 | 1.04 | 1.04 | 1.04 | 1.04 | 1.04 | 1.04 | 1.00 | 1.00 | 1.04 |
PSZ-AC_8:8 | 1.03 | 1.03 | 1.03 | 1.03 | 1.03 | 1.03 | 1.00 | 1.00 | 1.03 |
PSZ-AC_9:9 | 1.02 | 1.02 | 1.02 | 1.02 | 1.02 | 1.02 | 1.00 | 1.00 | 1.02 |
PSZ-AC_10:10 | 1.02 | 1.02 | 1.02 | 1.02 | 1.02 | 1.02 | 1.00 | 1.00 | 1.02 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC_1:1_OA_CONTROLLER | 2.07 | 0.411453 |
PSZ-AC_2:2_OA_CONTROLLER | 1.14 | 0.205727 |
PSZ-AC_3:3_OA_CONTROLLER | 1.14 | 0.205727 |
PSZ-AC_4:4_OA_CONTROLLER | 1.15 | 0.205727 |
PSZ-AC_5:5_OA_CONTROLLER | 1.14 | 0.205727 |
PSZ-AC_6:6_OA_CONTROLLER | 2.00 | 0.411453 |
PSZ-AC_7:7_OA_CONTROLLER | 1.04 | 0.205727 |
PSZ-AC_8:8_OA_CONTROLLER | 1.03 | 0.205727 |
PSZ-AC_9:9_OA_CONTROLLER | 1.02 | 0.205727 |
PSZ-AC_10:10_OA_CONTROLLER | 1.02 | 0.205727 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC_1:1_UNITARY_PACKAGE_DX | 2.07 | 2.07 | 2.07 | 2.07 | 34903.68 | 59163.99 | 40.00 | 1.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_DX | 1.14 | 1.14 | 1.14 | 1.14 | 19057.24 | 31956.19 | 40.00 | 1.00 |
PSZ-AC_3:3_UNITARY_PACKAGE_DX | 1.14 | 1.14 | 1.14 | 1.14 | 19055.76 | 31952.59 | 40.00 | 1.00 |
PSZ-AC_4:4_UNITARY_PACKAGE_DX | 1.15 | 1.15 | 1.15 | 1.15 | 19107.22 | 32028.66 | 40.00 | 1.00 |
PSZ-AC_5:5_UNITARY_PACKAGE_DX | 1.14 | 1.14 | 1.14 | 1.14 | 18976.33 | 31834.54 | 40.00 | 1.00 |
PSZ-AC_6:6_UNITARY_PACKAGE_DX | 2.00 | 2.00 | 2.00 | 2.00 | 33739.81 | 57516.69 | 40.00 | 1.00 |
PSZ-AC_7:7_UNITARY_PACKAGE_DX | 1.04 | 1.04 | 1.04 | 1.04 | 17460.67 | 29588.90 | 40.00 | 1.00 |
PSZ-AC_8:8_UNITARY_PACKAGE_DX | 1.03 | 1.03 | 1.03 | 1.03 | 17343.94 | 29416.34 | 40.00 | 1.00 |
PSZ-AC_9:9_UNITARY_PACKAGE_DX | 1.02 | 1.02 | 1.02 | 1.02 | 17211.89 | 29221.12 | 40.00 | 1.00 |
PSZ-AC_10:10_UNITARY_PACKAGE_DX | 1.02 | 1.02 | 1.02 | 1.02 | 17115.56 | 29201.40 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | Speed 2 Design Size Rated Total Cooling Capacity [W] | Speed 2 User-Specified Rated Total Cooling Capacity [W] | Speed 1 Design Size Rated Total Cooling Capacity [W] | Speed 1 User-Specified Rated Total Cooling Capacity [W] | Speed 2 Design Size Rated Sensible Heat Ratio | Speed 2 User-Specified Rated Sensible Heat Ratio | Speed 1 Design Size Rated Sensible Heat Ratio | Speed 1 User-Specified Rated Sensible Heat Ratio | |
PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | 2.07 | 1.04 | 2.07 | 34335.87 | 34903.68 | 17451.84 | 34903.68 | 0.792674 | 0.792670 | 0.792670 | 0.792670 |
PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | 1.14 | 0.571230 | 1.14 | 18911.77 | 19057.24 | 9528.62 | 19057.24 | 0.795849 | 0.795850 | 0.795850 | 0.795850 |
PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | 1.14 | 0.571150 | 1.14 | 18909.12 | 19055.76 | 9527.88 | 19055.76 | 0.795826 | 0.795830 | 0.795830 | 0.795830 |
PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | 1.15 | 0.572835 | 1.15 | 18964.91 | 19107.22 | 9553.61 | 19107.22 | 0.795917 | 0.795920 | 0.795920 | 0.795920 |
PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | 1.14 | 0.568530 | 1.14 | 18822.38 | 18976.33 | 9488.17 | 18976.33 | 0.795673 | 0.795670 | 0.795670 | 0.795670 |
PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | 2.00 | 1.00 | 2.00 | 33126.14 | 33739.81 | 16869.90 | 33739.81 | 0.791968 | 0.791970 | 0.791970 | 0.791970 |
PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | 1.04 | 0.518705 | 1.04 | 17172.82 | 17460.67 | 8730.33 | 17460.67 | 0.792594 | 0.792600 | 0.792600 | 0.792600 |
PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | 1.03 | 0.514880 | 1.03 | 17046.18 | 17343.94 | 8671.97 | 17343.94 | 0.792343 | 0.792340 | 0.792340 | 0.792340 |
PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | 1.02 | 0.510545 | 1.02 | 16902.67 | 17211.89 | 8605.94 | 17211.89 | 0.792050 | 0.792050 | 0.792050 | 0.792050 |
PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | 1.02 | 0.510100 | 1.02 | 16887.93 | 17115.56 | 8557.78 | 17115.56 | 0.793766 | 0.793770 | 0.793770 | 0.793770 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | 2.07 | 2270.26 |
PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | 1.14 | 1302.52 |
PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | 1.14 | 1302.34 |
PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | 1.15 | 1306.19 |
PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | 1.14 | 1296.37 |
PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | 2.00 | 2190.27 |
PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | 1.04 | 1182.77 |
PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | 1.03 | 1174.04 |
PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | 1.02 | 1164.16 |
PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | 1.02 | 1163.15 |
Design Size Nominal Capacity [W] | |
PSZ-AC_1:1_UNITARY_PACKAGE_HEATCOIL | 59163.99 |
PSZ-AC_2:2_UNITARY_PACKAGE_HEATCOIL | 31956.19 |
PSZ-AC_3:3_UNITARY_PACKAGE_HEATCOIL | 31952.59 |
PSZ-AC_4:4_UNITARY_PACKAGE_HEATCOIL | 32028.66 |
PSZ-AC_5:5_UNITARY_PACKAGE_HEATCOIL | 31834.54 |
PSZ-AC_6:6_UNITARY_PACKAGE_HEATCOIL | 57516.69 |
PSZ-AC_7:7_UNITARY_PACKAGE_HEATCOIL | 29588.90 |
PSZ-AC_8:8_UNITARY_PACKAGE_HEATCOIL | 29416.34 |
PSZ-AC_9:9_UNITARY_PACKAGE_HEATCOIL | 29221.12 |
PSZ-AC_10:10_UNITARY_PACKAGE_HEATCOIL | 29201.40 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:18:58
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
LGSTORE1_WALL_3 | LGSTORE1_WALL_3_DOOR_1 | LGSTORE1_WALL_3_DOOR_2 | |
LGSTORE1_WALL_1 | LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | |
SMSTORE1_WALL_1 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | |
SMSTORE1_WALL_3 | SMSTORE1_WALL_3_DOOR | |
SMSTORE2_WALL_1 | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | |
SMSTORE2_WALL_3 | SMSTORE2_WALL_3_DOOR | |
SMSTORE3_WALL_1 | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | |
SMSTORE3_WALL_3 | SMSTORE3_WALL_3_DOOR | |
SMSTORE4_WALL_1 | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | |
SMSTORE4_WALL_3 | SMSTORE4_WALL_3_DOOR | |
LGSTORE2_WALL_3 | LGSTORE2_WALL_3_DOOR_1 | LGSTORE2_WALL_3_DOOR_2 | |
LGSTORE2_WALL_1 | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | |
SMSTORE5_WALL_1 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | |
SMSTORE5_WALL_3 | SMSTORE5_WALL_3_DOOR | |
SMSTORE6_WALL_1 | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | |
SMSTORE6_WALL_3 | SMSTORE6_WALL_3_DOOR | |
SMSTORE7_WALL_1 | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | |
SMSTORE7_WALL_3 | SMSTORE7_WALL_3_DOOR | |
SMSTORE8_WALL_1 | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR | |
SMSTORE8_WALL_3 | SMSTORE8_WALL_3_DOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2020-06-03 19:18:58
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2020-06-03 19:18:58
VersionVersion ID | |
1 | 9.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 11.40 | 8.10 | 5.40 | 4.50 | 5.80 | 8.30 | 10.90 | 13.00 | 15.60 | 17.70 | 18.80 | 15.10 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930 | 47.47 | -122.32 | -8.00 | 122.00 | 99868 | 1.1870 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 11.22 | 14.30 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RetailStripmall | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 10 | 118 | 48 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | LGSTORE1 | 0.0 | 0.00 | 0.00 | 0.00 | 7.62 | 11.43 | 2.59 | 1 | 1 | 1 | 0.00 | 15.24 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 1805.20 | TARP | TARP | 348.39 | 276.30 | 247.76 | 20.75 | 6 | 8 | 0 | Yes |
2 | SMSTORE1 | 0.0 | 0.00 | 0.00 | 0.00 | 19.05 | 11.43 | 2.59 | 1 | 1 | 1 | 15.24 | 22.86 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.67 | 10.37 | 6 | 4 | 0 | Yes |
3 | SMSTORE2 | 0.0 | 0.00 | 0.00 | 0.00 | 26.67 | 11.43 | 2.59 | 1 | 1 | 1 | 22.86 | 30.48 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.35 | 6 | 4 | 0 | Yes |
4 | SMSTORE3 | 0.0 | 0.00 | 0.00 | 0.00 | 34.29 | 11.43 | 2.59 | 1 | 1 | 1 | 30.48 | 38.10 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.35 | 6 | 4 | 0 | Yes |
5 | SMSTORE4 | 0.0 | 0.00 | 0.00 | 0.00 | 41.91 | 11.43 | 2.59 | 1 | 1 | 1 | 38.10 | 45.72 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.35 | 6 | 4 | 0 | Yes |
6 | LGSTORE2 | 0.0 | 0.00 | 0.00 | 0.00 | 53.34 | 11.43 | 2.59 | 1 | 1 | 1 | 45.72 | 60.96 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 1805.20 | TARP | TARP | 348.39 | 157.89 | 129.43 | 20.70 | 6 | 8 | 0 | Yes |
7 | SMSTORE5 | 0.0 | 0.00 | 0.00 | 0.00 | 64.77 | 11.43 | 2.59 | 1 | 1 | 1 | 60.96 | 68.58 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.35 | 6 | 4 | 0 | Yes |
8 | SMSTORE6 | 0.0 | 0.00 | 0.00 | 0.00 | 72.39 | 11.43 | 2.59 | 1 | 1 | 1 | 68.58 | 76.20 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.35 | 6 | 4 | 0 | Yes |
9 | SMSTORE7 | 0.0 | 0.00 | 0.00 | 0.00 | 80.01 | 11.43 | 2.59 | 1 | 1 | 1 | 76.20 | 83.82 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.35 | 6 | 4 | 0 | Yes |
10 | SMSTORE8 | 0.0 | 0.00 | 0.00 | 0.00 | 87.63 | 11.43 | 2.59 | 1 | 1 | 1 | 83.82 | 91.44 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 197.36 | 183.13 | 10.35 | 6 | 4 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | LGSTORE1 | 348.39 | 30.0 | 11.614 | 8.610E-002 | 24.964 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 29.264 | No |
2 | SMSTORE1 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 27.838 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 32.138 | No |
3 | SMSTORE2 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 25.685 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 29.985 | No |
4 | SMSTORE3 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 25.685 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 29.985 | No |
5 | SMSTORE4 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 25.685 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 29.985 | No |
6 | LGSTORE2 | 348.39 | 30.0 | 11.614 | 8.610E-002 | 18.322 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 22.622 | No |
7 | SMSTORE5 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 18.322 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 22.622 | No |
8 | SMSTORE6 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 18.322 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 22.622 | No |
9 | SMSTORE7 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 18.322 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 22.622 | No |
10 | SMSTORE8 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 18.322 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 22.622 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | |
1 | LGSTORE1 | TYPE1_OCC_SCH | LGSTORE1 | 348.39 | 30.0 | 30.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 30 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
2 | SMSTORE1 | TYPE1_OCC_SCH | SMSTORE1 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
3 | SMSTORE2 | TYPE2_OCC_SCH | SMSTORE2 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
4 | SMSTORE3 | TYPE2_OCC_SCH | SMSTORE3 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
5 | SMSTORE4 | TYPE2_OCC_SCH | SMSTORE4 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
6 | LGSTORE2 | TYPE3_OCC_SCH | LGSTORE2 | 348.39 | 30.0 | 30.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 30 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
7 | SMSTORE5 | TYPE3_OCC_SCH | SMSTORE5 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
8 | SMSTORE6 | TYPE3_OCC_SCH | SMSTORE6 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
9 | SMSTORE7 | TYPE3_OCC_SCH | SMSTORE7 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
10 | SMSTORE8 | TYPE3_OCC_SCH | SMSTORE8 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | LGSTORE1_LIGHTS | TYPE1_LIGHT_SCH | LGSTORE1 | 348.39 | 30.0 | 6383.296 | 18.322 | 212.804 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 6383.296 |
2 | LGSTORE1_LIGHTS_ALLOWANCE | TYPE1_LIGHT_SCH | LGSTORE1 | 348.39 | 30.0 | 2313.751 | 6.641 | 77.135 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2313.751 |
3 | SMSTORE1_LIGHTS | TYPE1_LIGHT_SCH | SMSTORE1 | 174.19 | 15.0 | 3191.648 | 18.322 | 212.805 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3191.648 |
4 | SMSTORE1_LIGHTS_ALLOWANCE | TYPE1_LIGHT_SCH | SMSTORE1 | 174.19 | 15.0 | 1657.501 | 9.515 | 110.515 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1657.501 |
5 | SMSTORE2_LIGHTS | TYPE2_LIGHT_SCH | SMSTORE2 | 174.19 | 15.0 | 3191.648 | 18.322 | 212.805 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3191.648 |
6 | SMSTORE2_LIGHTS_ALLOWANCE | TYPE2_LIGHT_SCH | SMSTORE2 | 174.19 | 15.0 | 1282.501 | 7.363 | 85.511 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1282.501 |
7 | SMSTORE3_LIGHTS | TYPE2_LIGHT_SCH | SMSTORE3 | 174.19 | 15.0 | 3191.648 | 18.322 | 212.805 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3191.648 |
8 | SMSTORE3_LIGHTS_ALLOWANCE | TYPE2_LIGHT_SCH | SMSTORE3 | 174.19 | 15.0 | 1282.501 | 7.363 | 85.511 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1282.501 |
9 | SMSTORE4_LIGHTS | TYPE2_LIGHT_SCH | SMSTORE4 | 174.19 | 15.0 | 3191.648 | 18.322 | 212.805 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3191.648 |
10 | SMSTORE4_LIGHTS_ALLOWANCE | TYPE2_LIGHT_SCH | SMSTORE4 | 174.19 | 15.0 | 1282.501 | 7.363 | 85.511 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1282.501 |
11 | LGSTORE2_LIGHTS | TYPE3_LIGHT_SCH | LGSTORE2 | 348.39 | 30.0 | 6383.296 | 18.322 | 212.804 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 6383.296 |
12 | LGSTORE2_LIGHTS_ALLOWANCE | TYPE3_LIGHT_SCH | LGSTORE2 | 348.39 | 30.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
13 | SMSTORE5_LIGHTS | TYPE3_LIGHT_SCH | SMSTORE5 | 174.19 | 15.0 | 3191.648 | 18.322 | 212.805 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3191.648 |
14 | SMSTORE5_LIGHTS_ALLOWANCE | TYPE3_LIGHT_SCH | SMSTORE5 | 174.19 | 15.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
15 | SMSTORE6_LIGHTS | TYPE3_LIGHT_SCH | SMSTORE6 | 174.19 | 15.0 | 3191.648 | 18.322 | 212.805 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3191.648 |
16 | SMSTORE6_LIGHTS_ALLOWANCE | TYPE3_LIGHT_SCH | SMSTORE6 | 174.19 | 15.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
17 | SMSTORE7_LIGHTS | TYPE3_LIGHT_SCH | SMSTORE7 | 174.19 | 15.0 | 3191.648 | 18.322 | 212.805 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3191.648 |
18 | SMSTORE7_LIGHTS_ALLOWANCE | TYPE3_LIGHT_SCH | SMSTORE7 | 174.19 | 15.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
19 | SMSTORE8_LIGHTS | TYPE3_LIGHT_SCH | SMSTORE8 | 174.19 | 15.0 | 3191.648 | 18.322 | 212.805 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3191.648 |
20 | SMSTORE8_LIGHTS_ALLOWANCE | TYPE3_LIGHT_SCH | SMSTORE8 | 174.19 | 15.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | LGSTORE1_MISCPLUG_EQUIP | TYPE1_EQUIP_SCH | LGSTORE1 | 348.39 | 30.0 | 1498.062 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1498.062 |
2 | SMSTORE1_MISCPLUG_EQUIP | TYPE1_EQUIP_SCH | SMSTORE1 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
3 | SMSTORE2_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE2 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
4 | SMSTORE3_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE3 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
5 | SMSTORE4_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE4 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
6 | LGSTORE2_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | LGSTORE2 | 348.39 | 30.0 | 1498.062 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1498.062 |
7 | SMSTORE5_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE5 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
8 | SMSTORE6_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE6 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
9 | SMSTORE7_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE7 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
10 | SMSTORE8_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE8 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.975 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.2832 | 0.900 | 0.900 | 0.770 | 0.700 | Rough |
5 | NONRES_EXT_WALL | 20 | 4 | 7 | 0.167 | 0.3843 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
6 | LGSTORE1_FLOOR_FFACTOR | 30 | 2 | 7 | 0.167 | 0.1995 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
7 | SMSTORE1_FLOOR_FFACTOR | 31 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
8 | SMSTORE2_FLOOR_FFACTOR | 32 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | SMSTORE3_FLOOR_FFACTOR | 33 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
10 | SMSTORE4_FLOOR_FFACTOR | 34 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
11 | LGSTORE2_FLOOR_FFACTOR | 35 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | SMSTORE5_FLOOR_FFACTOR | 36 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | SMSTORE6_FLOOR_FFACTOR | 37 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | SMSTORE7_FLOOR_FFACTOR | 38 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | SMSTORE8_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.2888 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2516 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
6 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 3.472 |
7 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
8 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
9 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
10 | NONRES_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.368 |
11 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
12 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.937 |
13 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
14 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
15 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
16 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
17 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
18 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
19 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
20 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
21 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
22 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
23 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
24 | ~FC_Insulation_7 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_8 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_9 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
30 | ~FC_Insulation_10 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.386 |
31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.9747885 | 3.9747885 | 3.9747885 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
14 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
15 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
16 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
17 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
18 | 3 | -0.61927053E-06 | 0.12767249E-08 | -0.37968499E-05 | 0.16832131E-17 |
19 | 2 | 0.77611055 | 0.17315568E-02 | 1.0534842 | -0.72792597E-06 |
20 | 1 | -21.915918 | 0.11588205 | -6.3286394 | 0.20197014 |
21 | 0 | 21.365777 | 0.10835518 | 5.5011278 | |
22 | 7 | -0.35963630E-12 | 0.61482467E-15 | -0.13288964E-12 | 0.15093609E-15 |
23 | 6 | 0.33258387E-07 | 0.11249777E-09 | 0.75805110E-08 | -0.16019892E-12 |
24 | 5 | -0.21313350E-03 | 0.93714421E-06 | -0.10927814E-03 | 0.74776115E-08 |
25 | 4 | 0.31870195 | 0.44521373E-03 | 0.10925225 | -0.37358013E-04 |
26 | 3 | -7.7913368 | 0.13499397E-01 | -2.4947666 | 0.31584435E-01 |
27 | 2 | 42.601618 | 0.47079245E-01 | 15.902165 | -0.35261900 |
28 | 1 | -81.870774 | 0.20888078E-01 | -29.712230 | 1.1068570 |
29 | 0 | 46.824331 | 0.41326549E-03 | 16.278015 | |
30 | 7 | -0.21163652E-08 | -0.68723841E-15 | 0.43910983E-14 | -0.57684426E-16 |
31 | 6 | 0.56109385E-05 | 0.38186281E-08 | 0.31898696E-02 | -0.26759299E-04 |
32 | 5 | -0.40164657E-03 | 0.22608617E-05 | -0.22372456 | 0.19561502E-02 |
33 | 4 | 0.92272104E-02 | 0.10289840E-03 | 4.8295456 | -0.45264980E-01 |
34 | 3 | -0.80993241E-01 | 0.81813938E-03 | -38.021416 | 0.39865375 |
35 | 2 | 0.28754352 | 0.13608947E-02 | 116.48395 | -1.4179393 |
36 | 1 | -0.41499682 | 0.41453381E-03 | -143.90731 | 2.0490399 |
37 | 0 | 0.20232414 | 0.10048102E-04 | 60.838472 | |
38 | 7 | -0.37862368E-08 | -0.38757603E-14 | 0.11479940E-14 | -0.41635801E-16 |
39 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
40 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
41 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
42 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
43 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
44 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
45 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
46 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479937E-14 | -0.41635796E-16 |
47 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
48 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
49 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
50 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
51 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
52 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
53 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
54 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479940E-14 | -0.41635801E-16 |
55 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
56 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
57 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
58 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
59 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
60 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
61 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
62 | 7 | -0.37862368E-08 | -0.38757603E-14 | 0.11479940E-14 | -0.41635801E-16 |
63 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
64 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
65 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
66 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
67 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
68 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
69 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
70 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479937E-14 | -0.41635796E-16 |
71 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
72 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
73 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
74 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
75 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
76 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
77 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
78 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479937E-14 | -0.41635796E-16 |
79 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
80 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
81 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
82 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
83 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
84 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
85 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
86 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479940E-14 | -0.41635801E-16 |
87 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
88 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
89 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
90 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
91 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
92 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
93 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
94 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479936E-14 | -0.41635794E-16 |
95 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
96 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
97 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
98 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
99 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
100 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
101 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
102 | 7 | -0.14484255E-08 | -0.22640907E-15 | 0.11860658E-13 | -0.17473455E-15 |
103 | 6 | 0.80640390E-05 | 0.55493782E-08 | 0.31828288E-02 | -0.26700235E-04 |
104 | 5 | -0.58275339E-03 | 0.32892043E-05 | -0.22332434 | 0.19526176E-02 |
105 | 4 | 0.13421983E-01 | 0.14977251E-03 | 4.8228790 | -0.45200897E-01 |
106 | 3 | -0.11791368 | 0.11914425E-02 | -37.983753 | 0.39823745 |
107 | 2 | 0.41875064 | 0.19825898E-02 | 116.41064 | -1.4169588 |
108 | 1 | -0.60444169 | 0.60433957E-03 | -143.86415 | 2.0483306 |
109 | 0 | 0.29470347 | 0.14596444E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.51_SHGC_0.4 | 29 | 1 | VerySmooth | 2.899 | 0.395 | 0.315 | 0.401 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 1.82741E-002 | 0.31435 | 0.46434 | 0.46434 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.10459 | 1.00000 | No |
Calculation Method | Value {days} | Allowable Number Figures in Shadow Overlap {} | Polygon Clipping Algorithm | Sky Diffuse Modeling Algorithm | External Shading Calculation Method | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | AverageOverDaysInFrequency | 30 | 15000 | SutherlandHodgman | SimpleSkyDiffuseModeling | InternalCalculation | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | GAS TANK1 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
2 | WaterHeater:Mixed | GAS TANK2 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
3 | WaterHeater:Mixed | GAS TANK3 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
4 | WaterHeater:Mixed | GAS TANK4 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
5 | WaterHeater:Mixed | GAS TANK5 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
6 | WaterHeater:Mixed | GAS TANK6 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
7 | WaterHeater:Mixed | GAS TANK7 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | LGSTORE1_WALL_2 | 0 | 118.41 | 56.08 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 4 | No | No |
2 | LGSTORE1_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 4 | No | No |
3 | LGSTORE1_WALL_3_DOOR_1 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 0 | No | No |
4 | LGSTORE1_WALL_3_DOOR_2 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 0 | No | No |
5 | LGSTORE1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 0 | No | No |
6 | LGSTORE1_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 4 | No | No |
7 | LGSTORE1_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 1 | No | No |
8 | LGSTORE1_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 1 | No | No |
9 | LGSTORE1_WALL_1_WINDOW_3 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 1 | No | No |
10 | LGSTORE1_WALL_1_WINDOW_4 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 1 | No | No |
11 | LGSTORE1_WALL_1_DOOR_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 1 | No | No |
12 | LGSTORE1_WALL_1_DOOR_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 1 | No | No |
13 | LGSTORE1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 0 | No | No |
14 | LGSTORE1_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 0 | No | No |
15 | LGSTORE1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 0 | No | No |
16 | SMSTORE1_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
17 | SMSTORE1_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
18 | SMSTORE1_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
19 | SMSTORE1_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
20 | SMSTORE1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
21 | SMSTORE1_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
22 | SMSTORE1_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
23 | SMSTORE1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
24 | SMSTORE1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
25 | SMSTORE1_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
26 | SMSTORE1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
27 | SMSTORE2_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
28 | SMSTORE2_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
29 | SMSTORE2_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
30 | SMSTORE2_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
31 | SMSTORE2_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
32 | SMSTORE2_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
33 | SMSTORE2_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
34 | SMSTORE2_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
35 | SMSTORE2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
36 | SMSTORE2_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
37 | SMSTORE2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
38 | SMSTORE3_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
39 | SMSTORE3_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
40 | SMSTORE3_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
41 | SMSTORE3_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
42 | SMSTORE3_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
43 | SMSTORE3_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
44 | SMSTORE3_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
45 | SMSTORE3_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
46 | SMSTORE3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
47 | SMSTORE3_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
48 | SMSTORE3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
49 | SMSTORE4_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
50 | SMSTORE4_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
51 | SMSTORE4_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
52 | SMSTORE4_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
53 | SMSTORE4_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
54 | SMSTORE4_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 3 | No | No |
55 | SMSTORE4_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
56 | SMSTORE4_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
57 | SMSTORE4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
58 | SMSTORE4_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
59 | SMSTORE4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
60 | LGSTORE2_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
61 | LGSTORE2_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 4 | No | No |
62 | LGSTORE2_WALL_3_DOOR_1 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
63 | LGSTORE2_WALL_3_DOOR_2 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
64 | LGSTORE2_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
65 | LGSTORE2_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 4 | No | No |
66 | LGSTORE2_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
67 | LGSTORE2_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
68 | LGSTORE2_WALL_1_WINDOW_3 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
69 | LGSTORE2_WALL_1_WINDOW_4 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
70 | LGSTORE2_WALL_1_DOOR_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
71 | LGSTORE2_WALL_1_DOOR_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
72 | LGSTORE2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
73 | LGSTORE2_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
74 | LGSTORE2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
75 | SMSTORE5_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
76 | SMSTORE5_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
77 | SMSTORE5_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
78 | SMSTORE5_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
79 | SMSTORE5_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
80 | SMSTORE5_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
81 | SMSTORE5_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
82 | SMSTORE5_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
83 | SMSTORE5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
84 | SMSTORE5_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
85 | SMSTORE5_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
86 | SMSTORE6_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
87 | SMSTORE6_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
88 | SMSTORE6_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
89 | SMSTORE6_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
90 | SMSTORE6_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
91 | SMSTORE6_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
92 | SMSTORE6_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
93 | SMSTORE6_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
94 | SMSTORE6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
95 | SMSTORE6_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
96 | SMSTORE6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
97 | SMSTORE7_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
98 | SMSTORE7_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
99 | SMSTORE7_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
100 | SMSTORE7_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
101 | SMSTORE7_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
102 | SMSTORE7_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 3 | No | No |
103 | SMSTORE7_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
104 | SMSTORE7_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
105 | SMSTORE7_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
106 | SMSTORE7_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
107 | SMSTORE7_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
108 | SMSTORE8_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 4 | No | No |
109 | SMSTORE8_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 1 | No | No |
110 | SMSTORE8_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 1 | No | No |
111 | SMSTORE8_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 1 | No | No |
112 | SMSTORE8_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
113 | SMSTORE8_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 3 | No | No |
114 | SMSTORE8_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
115 | SMSTORE8_WALL_4 | 0 | 118.41 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 3 | No | No |
116 | SMSTORE8_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
117 | SMSTORE8_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
118 | SMSTORE8_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | LGSTORE1_INFILTRATION | TYPE1_INFIL_SCH | LGSTORE1 | 348.39 | 30.0 | 0.286 | 8.224E-004 | 4.530E-004 | 0.571 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | LGSTORE1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | LGSTORE1 | 348.39 | 30.0 | 0.389 | 1.116E-003 | 6.149E-004 | 0.776 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | SMSTORE1_INFILTRATION | TYPE1_INFIL_SCH | SMSTORE1 | 174.19 | 15.0 | 8.210E-002 | 4.713E-004 | 3.194E-004 | 0.327 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | SMSTORE1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE1 | 174.19 | 15.0 | 0.222 | 1.276E-003 | 8.648E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
5 | SMSTORE2_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE2 | 174.19 | 15.0 | 8.210E-002 | 4.713E-004 | 3.194E-004 | 0.327 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | SMSTORE2_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE2 | 174.19 | 15.0 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
7 | SMSTORE3_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE3 | 174.19 | 15.0 | 8.210E-002 | 4.713E-004 | 3.194E-004 | 0.327 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | SMSTORE3_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE3 | 174.19 | 15.0 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | SMSTORE4_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE4 | 174.19 | 15.0 | 8.210E-002 | 4.713E-004 | 3.194E-004 | 0.327 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | SMSTORE4_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE4 | 174.19 | 15.0 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
11 | LGSTORE2_INFILTRATION | TYPE3_INFIL_SCH | LGSTORE2 | 348.39 | 30.0 | 0.164 | 4.713E-004 | 3.194E-004 | 0.327 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | LGSTORE2_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | LGSTORE2 | 348.39 | 30.0 | 0.389 | 1.116E-003 | 7.565E-004 | 0.776 | 1.000 | 0.000 | 0.000 | 0.000 |
13 | SMSTORE5_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE5 | 174.19 | 15.0 | 8.210E-002 | 4.713E-004 | 3.194E-004 | 0.327 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | SMSTORE5_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE5 | 174.19 | 15.0 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
15 | SMSTORE6_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE6 | 174.19 | 15.0 | 8.210E-002 | 4.713E-004 | 3.194E-004 | 0.327 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | SMSTORE6_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE6 | 174.19 | 15.0 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
17 | SMSTORE7_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE7 | 174.19 | 15.0 | 8.210E-002 | 4.713E-004 | 3.194E-004 | 0.327 | 0.000 | 0.000 | 0.224 | 0.000 |
18 | SMSTORE7_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE7 | 174.19 | 15.0 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
19 | SMSTORE8_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE8 | 174.19 | 15.0 | 0.204 | 1.172E-003 | 5.440E-004 | 0.815 | 0.000 | 0.000 | 0.224 | 0.000 |
20 | SMSTORE8_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE8 | 174.19 | 15.0 | 0.222 | 1.276E-003 | 5.921E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | LGSTORE1 | Mixing/Well-Stirred |
2 | SMSTORE1 | Mixing/Well-Stirred |
3 | SMSTORE2 | Mixing/Well-Stirred |
4 | SMSTORE3 | Mixing/Well-Stirred |
5 | SMSTORE4 | Mixing/Well-Stirred |
6 | LGSTORE2 | Mixing/Well-Stirred |
7 | SMSTORE5 | Mixing/Well-Stirred |
8 | SMSTORE6 | Mixing/Well-Stirred |
9 | SMSTORE7 | Mixing/Well-Stirred |
10 | SMSTORE8 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone LGSTORE1 | 1.2000 |
3 | Zone SMSTORE1 | 1.2000 |
4 | Zone SMSTORE2 | 1.2000 |
5 | Zone SMSTORE3 | 1.2000 |
6 | Zone SMSTORE4 | 1.2000 |
7 | Zone LGSTORE2 | 1.2000 |
8 | Zone SMSTORE5 | 1.2000 |
9 | Zone SMSTORE6 | 1.2000 |
10 | Zone SMSTORE7 | 1.2000 |
11 | Zone SMSTORE8 | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone LGSTORE1 | 1.2000 |
3 | Zone SMSTORE1 | 1.2000 |
4 | Zone SMSTORE2 | 1.2000 |
5 | Zone SMSTORE3 | 1.2000 |
6 | Zone SMSTORE4 | 1.2000 |
7 | Zone LGSTORE2 | 1.2000 |
8 | Zone SMSTORE5 | 1.2000 |
9 | Zone SMSTORE6 | 1.2000 |
10 | Zone SMSTORE7 | 1.2000 |
11 | Zone SMSTORE8 | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | LGSTORE1 | Cooling | 23221.10784 | 27865.32941 | 1.72853 | 2.07423 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 29.40000 | 8.79438E-003 | 348.38640 | 29.99610 | 0.41145 | 0.00000 |
2 | LGSTORE1 | Heating | 23928.05397 | 28713.66476 | 1.04631 | 1.25557 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -4.20000 | 2.69032E-003 | 348.38640 | 29.99610 | 0.41145 | 0.00000 |
3 | SMSTORE1 | Cooling | 12789.88137 | 15347.85764 | 0.95205 | 1.14246 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 29.22667 | 8.79438E-003 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
4 | SMSTORE1 | Heating | 12203.56184 | 14644.27421 | 0.53362 | 0.64035 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -4.20000 | 2.69032E-003 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
5 | SMSTORE2 | Cooling | 12788.10230 | 15345.72276 | 0.95191 | 1.14230 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 29.22667 | 8.79438E-003 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
6 | SMSTORE2 | Heating | 12395.72147 | 14874.86577 | 0.54203 | 0.65043 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -4.20000 | 2.69032E-003 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
7 | SMSTORE3 | Cooling | 12825.89158 | 15391.06989 | 0.95473 | 1.14567 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 29.22667 | 8.79438E-003 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
8 | SMSTORE3 | Heating | 12506.80393 | 15008.16472 | 0.54688 | 0.65626 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -4.20000 | 2.69032E-003 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
9 | SMSTORE4 | Cooling | 12729.46484 | 15275.35781 | 0.94755 | 1.13706 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 29.22667 | 8.79438E-003 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
10 | SMSTORE4 | Heating | 12670.21620 | 15204.25943 | 0.55403 | 0.66483 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -4.20000 | 2.69032E-003 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
11 | LGSTORE2 | Cooling | 22402.96126 | 26883.55351 | 1.66763 | 2.00115 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 29.14000 | 8.79438E-003 | 348.38640 | 29.99610 | 0.41145 | 0.00000 |
12 | LGSTORE2 | Heating | 23796.65917 | 28555.99101 | 1.04057 | 1.24869 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -4.20000 | 2.69032E-003 | 348.38640 | 29.99610 | 0.41145 | 0.00000 |
13 | SMSTORE5 | Cooling | 11613.92593 | 13936.71112 | 0.86451 | 1.03741 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 29.14000 | 8.79438E-003 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
14 | SMSTORE5 | Heating | 12983.09432 | 15579.71318 | 0.56771 | 0.68125 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -4.20000 | 2.69032E-003 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
15 | SMSTORE6 | Cooling | 11528.20822 | 13833.84986 | 0.85813 | 1.02976 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 29.14000 | 8.79438E-003 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
16 | SMSTORE6 | Heating | 12968.23268 | 15561.87921 | 0.56706 | 0.68047 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -4.20000 | 2.69032E-003 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
17 | SMSTORE7 | Cooling | 11431.23339 | 13717.48006 | 0.85091 | 1.02109 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 29.14000 | 8.79438E-003 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
18 | SMSTORE7 | Heating | 13134.54718 | 15761.45662 | 0.57433 | 0.68920 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -4.20000 | 2.69032E-003 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
19 | SMSTORE8 | Cooling | 11421.25290 | 13705.50348 | 0.85017 | 1.02020 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:10:00 | 28.96667 | 8.79438E-003 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
20 | SMSTORE8 | Heating | 14527.49187 | 17432.99024 | 0.63523 | 0.76228 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -4.20000 | 2.69032E-003 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC_1:1 | Cooling | Sensible | 30139.11 | 2.07423 | 2.07423 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
2 | PSZ-AC_1:1 | Heating | Sensible | 40714.73 | 1.25557 | 1.25557 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
3 | PSZ-AC_2:2 | Cooling | Sensible | 16441.92 | 1.14246 | 1.14246 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
4 | PSZ-AC_2:2 | Heating | Sensible | 20640.57 | 0.64035 | 0.64035 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
5 | PSZ-AC_3:3 | Cooling | Sensible | 16431.84 | 1.14230 | 1.14230 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
6 | PSZ-AC_3:3 | Heating | Sensible | 20867.80 | 0.65043 | 0.65043 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
7 | PSZ-AC_4:4 | Cooling | Sensible | 16474.92 | 1.14567 | 1.14567 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
8 | PSZ-AC_4:4 | Heating | Sensible | 20999.16 | 0.65626 | 0.65626 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
9 | PSZ-AC_5:5 | Cooling | Sensible | 16361.33 | 1.13706 | 1.13706 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
10 | PSZ-AC_5:5 | Heating | Sensible | 21192.40 | 0.66483 | 0.66483 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
11 | PSZ-AC_6:6 | Cooling | Sensible | 29103.70 | 2.00115 | 2.00115 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
12 | PSZ-AC_6:6 | Heating | Sensible | 40559.46 | 1.24869 | 1.24869 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
13 | PSZ-AC_7:7 | Cooling | Sensible | 15041.35 | 1.03741 | 1.03741 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
14 | PSZ-AC_7:7 | Heating | Sensible | 21562.39 | 0.68125 | 0.68125 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
15 | PSZ-AC_8:8 | Cooling | Sensible | 14940.62 | 1.02976 | 1.02976 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
16 | PSZ-AC_8:8 | Heating | Sensible | 21544.82 | 0.68047 | 0.68047 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
17 | PSZ-AC_9:9 | Cooling | Sensible | 14826.41 | 1.02109 | 1.02109 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
18 | PSZ-AC_9:9 | Heating | Sensible | 21741.49 | 0.68920 | 0.68920 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
19 | PSZ-AC_10:10 | Cooling | Sensible | 14763.80 | 1.02020 | 1.02020 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
20 | PSZ-AC_10:10 | Heating | Sensible | 23388.60 | 0.76228 | 0.76228 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:Uncontrolled | LGSTORE1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.07423 |
2 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.14246 |
3 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE2 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.14230 |
4 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.14567 |
5 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE4 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.13706 |
6 | AirTerminal:SingleDuct:Uncontrolled | LGSTORE2 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.00115 |
7 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE5 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.03741 |
8 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.02976 |
9 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE7 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.02109 |
10 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE8 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.02020 |
11 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.07423 |
12 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.07423 |
13 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.07423 |
14 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 2.07423 |
15 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.07423 |
16 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Main Design Air Flow Rate [m3/s] | 2.07423 |
17 | AirLoopHVAC | PSZ-AC_1:1 | User Heating Air Flow Ratio [] | 1.00000 |
18 | AirLoopHVAC | PSZ-AC_1:1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
19 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.14246 |
20 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.14246 |
21 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.14246 |
22 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.14246 |
23 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.14246 |
24 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Main Design Air Flow Rate [m3/s] | 1.14246 |
25 | AirLoopHVAC | PSZ-AC_2:2 | User Heating Air Flow Ratio [] | 1.00000 |
26 | AirLoopHVAC | PSZ-AC_2:2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
27 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.14230 |
28 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.14230 |
29 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.14230 |
30 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.14230 |
31 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.14230 |
32 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Main Design Air Flow Rate [m3/s] | 1.14230 |
33 | AirLoopHVAC | PSZ-AC_3:3 | User Heating Air Flow Ratio [] | 1.00000 |
34 | AirLoopHVAC | PSZ-AC_3:3 | Calculated Heating Air Flow Ratio [] | 1.00000 |
35 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.14567 |
36 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.14567 |
37 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.14567 |
38 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.14567 |
39 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.14567 |
40 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Main Design Air Flow Rate [m3/s] | 1.14567 |
41 | AirLoopHVAC | PSZ-AC_4:4 | User Heating Air Flow Ratio [] | 1.00000 |
42 | AirLoopHVAC | PSZ-AC_4:4 | Calculated Heating Air Flow Ratio [] | 1.00000 |
43 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.13706 |
44 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.13706 |
45 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.13706 |
46 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.13706 |
47 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.13706 |
48 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Main Design Air Flow Rate [m3/s] | 1.13706 |
49 | AirLoopHVAC | PSZ-AC_5:5 | User Heating Air Flow Ratio [] | 1.00000 |
50 | AirLoopHVAC | PSZ-AC_5:5 | Calculated Heating Air Flow Ratio [] | 1.00000 |
51 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.00115 |
52 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.00115 |
53 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.00115 |
54 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Heating Design Air Flow Rate [m3/s] | 2.00115 |
55 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.00115 |
56 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Main Design Air Flow Rate [m3/s] | 2.00115 |
57 | AirLoopHVAC | PSZ-AC_6:6 | User Heating Air Flow Ratio [] | 1.00000 |
58 | AirLoopHVAC | PSZ-AC_6:6 | Calculated Heating Air Flow Ratio [] | 1.00000 |
59 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.03741 |
60 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.03741 |
61 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.03741 |
62 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.03741 |
63 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.03741 |
64 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Main Design Air Flow Rate [m3/s] | 1.03741 |
65 | AirLoopHVAC | PSZ-AC_7:7 | User Heating Air Flow Ratio [] | 1.00000 |
66 | AirLoopHVAC | PSZ-AC_7:7 | Calculated Heating Air Flow Ratio [] | 1.00000 |
67 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.02976 |
68 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.02976 |
69 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.02976 |
70 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.02976 |
71 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.02976 |
72 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Main Design Air Flow Rate [m3/s] | 1.02976 |
73 | AirLoopHVAC | PSZ-AC_8:8 | User Heating Air Flow Ratio [] | 1.00000 |
74 | AirLoopHVAC | PSZ-AC_8:8 | Calculated Heating Air Flow Ratio [] | 1.00000 |
75 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.02109 |
76 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.02109 |
77 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.02109 |
78 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.02109 |
79 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.02109 |
80 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Main Design Air Flow Rate [m3/s] | 1.02109 |
81 | AirLoopHVAC | PSZ-AC_9:9 | User Heating Air Flow Ratio [] | 1.00000 |
82 | AirLoopHVAC | PSZ-AC_9:9 | Calculated Heating Air Flow Ratio [] | 1.00000 |
83 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.02020 |
84 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.02020 |
85 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.02020 |
86 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.02020 |
87 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.02020 |
88 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Main Design Air Flow Rate [m3/s] | 1.02020 |
89 | AirLoopHVAC | PSZ-AC_10:10 | User Heating Air Flow Ratio [] | 1.00000 |
90 | AirLoopHVAC | PSZ-AC_10:10 | Calculated Heating Air Flow Ratio [] | 1.00000 |
91 | AirLoopHVAC | PSZ-AC_1:1 | Design Supply Air Flow Rate [m3/s] | 2.07423 |
92 | AirLoopHVAC | PSZ-AC_2:2 | Design Supply Air Flow Rate [m3/s] | 1.14246 |
93 | AirLoopHVAC | PSZ-AC_3:3 | Design Supply Air Flow Rate [m3/s] | 1.14230 |
94 | AirLoopHVAC | PSZ-AC_4:4 | Design Supply Air Flow Rate [m3/s] | 1.14567 |
95 | AirLoopHVAC | PSZ-AC_5:5 | Design Supply Air Flow Rate [m3/s] | 1.13706 |
96 | AirLoopHVAC | PSZ-AC_6:6 | Design Supply Air Flow Rate [m3/s] | 2.00115 |
97 | AirLoopHVAC | PSZ-AC_7:7 | Design Supply Air Flow Rate [m3/s] | 1.03741 |
98 | AirLoopHVAC | PSZ-AC_8:8 | Design Supply Air Flow Rate [m3/s] | 1.02976 |
99 | AirLoopHVAC | PSZ-AC_9:9 | Design Supply Air Flow Rate [m3/s] | 1.02109 |
100 | AirLoopHVAC | PSZ-AC_10:10 | Design Supply Air Flow Rate [m3/s] | 1.02020 |
101 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.07423 |
102 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41145 |
103 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.07423 |
104 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.07423 |
105 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.07423 |
106 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 2.07423 |
107 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.07423 |
108 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.03712 |
109 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 2.07423 |
110 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 34335.87154 |
111 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 34903.68000 |
112 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 17451.84000 |
113 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 34903.68000 |
114 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.79267 |
115 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.79267 |
116 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.79267 |
117 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.79267 |
118 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 34903.68000 |
119 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 59163.99161 |
120 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
121 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
122 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.07423 |
123 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 2270.25688 |
124 | Coil:Heating:Fuel | PSZ-AC_1:1_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 59163.99161 |
125 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.14246 |
126 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20573 |
127 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.14246 |
128 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.14246 |
129 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.14246 |
130 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.14246 |
131 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.14246 |
132 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.57123 |
133 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.14246 |
134 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 18911.76957 |
135 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 19057.24000 |
136 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 9528.62000 |
137 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 19057.24000 |
138 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.79585 |
139 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.79585 |
140 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.79585 |
141 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.79585 |
142 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 19057.24000 |
143 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 31956.19187 |
144 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
145 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
146 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.14246 |
147 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1302.52499 |
148 | Coil:Heating:Fuel | PSZ-AC_2:2_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 31956.19187 |
149 | Controller:OutdoorAir | PSZ-AC_3:3_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.14230 |
150 | Controller:OutdoorAir | PSZ-AC_3:3_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20573 |
151 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.14230 |
152 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.14230 |
153 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.14230 |
154 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.14230 |
155 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.14230 |
156 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.57115 |
157 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.14230 |
158 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 18909.12101 |
159 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 19055.76000 |
160 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 9527.88000 |
161 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 19055.76000 |
162 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.79583 |
163 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.79583 |
164 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.79583 |
165 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.79583 |
166 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 19055.76000 |
167 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 31952.59291 |
168 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
169 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
170 | Fan:SystemModel | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.14230 |
171 | Fan:SystemModel | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1302.34372 |
172 | Coil:Heating:Fuel | PSZ-AC_3:3_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 31952.59291 |
173 | Controller:OutdoorAir | PSZ-AC_4:4_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.14567 |
174 | Controller:OutdoorAir | PSZ-AC_4:4_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20573 |
175 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.14567 |
176 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.14567 |
177 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.14567 |
178 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.14567 |
179 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.14567 |
180 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.57284 |
181 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.14567 |
182 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 18964.90647 |
183 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 19107.22000 |
184 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 9553.61000 |
185 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 19107.22000 |
186 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.79592 |
187 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.79592 |
188 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.79592 |
189 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.79592 |
190 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 19107.22000 |
191 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 32028.66063 |
192 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
193 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
194 | Fan:SystemModel | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.14567 |
195 | Fan:SystemModel | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1306.19220 |
196 | Coil:Heating:Fuel | PSZ-AC_4:4_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 32028.66063 |
197 | Controller:OutdoorAir | PSZ-AC_5:5_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.13706 |
198 | Controller:OutdoorAir | PSZ-AC_5:5_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20573 |
199 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.13706 |
200 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.13706 |
201 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.13706 |
202 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.13706 |
203 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.13706 |
204 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.56853 |
205 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.13706 |
206 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 18822.38040 |
207 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 18976.33000 |
208 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 9488.16500 |
209 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 18976.33000 |
210 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.79567 |
211 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.79567 |
212 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.79567 |
213 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.79567 |
214 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 18976.33000 |
215 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 31834.53669 |
216 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
217 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
218 | Fan:SystemModel | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.13706 |
219 | Fan:SystemModel | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1296.37198 |
220 | Coil:Heating:Fuel | PSZ-AC_5:5_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 31834.53669 |
221 | Controller:OutdoorAir | PSZ-AC_6:6_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.00115 |
222 | Controller:OutdoorAir | PSZ-AC_6:6_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41145 |
223 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.00115 |
224 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.00115 |
225 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.00115 |
226 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 2.00115 |
227 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.00115 |
228 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.00058 |
229 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 2.00115 |
230 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 33126.13806 |
231 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 33739.81000 |
232 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 16869.90500 |
233 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 33739.81000 |
234 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.79197 |
235 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.79197 |
236 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.79197 |
237 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.79197 |
238 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 33739.81000 |
239 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 57516.68813 |
240 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
241 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
242 | Fan:SystemModel | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.00115 |
243 | Fan:SystemModel | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 2190.27094 |
244 | Coil:Heating:Fuel | PSZ-AC_6:6_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 57516.68813 |
245 | Controller:OutdoorAir | PSZ-AC_7:7_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.03741 |
246 | Controller:OutdoorAir | PSZ-AC_7:7_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20573 |
247 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.03741 |
248 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.03741 |
249 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.03741 |
250 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.03741 |
251 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.03741 |
252 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.51871 |
253 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.03741 |
254 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 17172.81907 |
255 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 17460.67000 |
256 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 8730.33500 |
257 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 17460.67000 |
258 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.79259 |
259 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.79260 |
260 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.79260 |
261 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.79260 |
262 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 17460.67000 |
263 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 29588.89514 |
264 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
265 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
266 | Fan:SystemModel | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.03741 |
267 | Fan:SystemModel | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1182.76532 |
268 | Coil:Heating:Fuel | PSZ-AC_7:7_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 29588.89514 |
269 | Controller:OutdoorAir | PSZ-AC_8:8_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.02976 |
270 | Controller:OutdoorAir | PSZ-AC_8:8_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20573 |
271 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.02976 |
272 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.02976 |
273 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.02976 |
274 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.02976 |
275 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.02976 |
276 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.51488 |
277 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.02976 |
278 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 17046.18441 |
279 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 17343.94000 |
280 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 8671.97000 |
281 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 17343.94000 |
282 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.79234 |
283 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.79234 |
284 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.79234 |
285 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.79234 |
286 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 17343.94000 |
287 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 29416.34127 |
288 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
289 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
290 | Fan:SystemModel | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.02976 |
291 | Fan:SystemModel | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1174.03578 |
292 | Coil:Heating:Fuel | PSZ-AC_8:8_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 29416.34127 |
293 | Controller:OutdoorAir | PSZ-AC_9:9_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.02109 |
294 | Controller:OutdoorAir | PSZ-AC_9:9_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20573 |
295 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.02109 |
296 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.02109 |
297 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.02109 |
298 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.02109 |
299 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.02109 |
300 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.51055 |
301 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.02109 |
302 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 16902.66512 |
303 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 17211.89000 |
304 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 8605.94500 |
305 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 17211.89000 |
306 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.79205 |
307 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.79205 |
308 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.79205 |
309 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.79205 |
310 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 17211.89000 |
311 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 29221.12133 |
312 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
313 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
314 | Fan:SystemModel | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.02109 |
315 | Fan:SystemModel | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1164.15977 |
316 | Coil:Heating:Fuel | PSZ-AC_9:9_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 29221.12133 |
317 | Controller:OutdoorAir | PSZ-AC_10:10_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.02020 |
318 | Controller:OutdoorAir | PSZ-AC_10:10_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20573 |
319 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.02020 |
320 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.02020 |
321 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.02020 |
322 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.02020 |
323 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.02020 |
324 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.51010 |
325 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.02020 |
326 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 16887.93246 |
327 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 17115.56000 |
328 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 8557.78000 |
329 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 17115.56000 |
330 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.79377 |
331 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.79377 |
332 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.79377 |
333 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.79377 |
334 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 17115.56000 |
335 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 29201.39995 |
336 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
337 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
338 | Fan:SystemModel | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.02020 |
339 | Fan:SystemModel | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1163.14551 |
340 | Coil:Heating:Fuel | PSZ-AC_10:10_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 29201.39995 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | 33277.7 | 10.05 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | 18161.8 | 28.43 | |||
3 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | 18160.4 | 38.47 | |||
4 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | 18209.3 | 48.40 | |||
5 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | 18085.1 | 64.51 | |||
6 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | 32171.1 | 43.15 | |||
7 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | 16647.5 | 102.55 | |||
8 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | 16536.7 | 114.29 | |||
9 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | 16411.5 | 126.21 | |||
10 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | 16315.9 | 137.87 |
Zone Name | # Surfaces | |
1 | LGSTORE1 | 15 |
2 | SMSTORE1 | 11 |
3 | SMSTORE2 | 11 |
4 | SMSTORE3 | 11 |
5 | SMSTORE4 | 11 |
6 | LGSTORE2 | 15 |
7 | SMSTORE5 | 11 |
8 | SMSTORE6 | 11 |
9 | SMSTORE7 | 11 |
10 | SMSTORE8 | 11 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | LGSTORE1_WALL_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | LGSTORE1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 71.15 | 78.94 | 71.15 | 0.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | LGSTORE1_WALL_3_DOOR_1 | Door | LGSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
4 | LGSTORE1_WALL_3_DOOR_2 | Door | LGSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
5 | LGSTORE1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
6 | LGSTORE1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 58.20 | 78.94 | 58.20 | 180.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
7 | LGSTORE1_WALL_1_WINDOW_1 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.51_SHGC_0.4 | N/A | 2.899 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
8 | LGSTORE1_WALL_1_WINDOW_2 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.51_SHGC_0.4 | N/A | 2.899 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
9 | LGSTORE1_WALL_1_WINDOW_3 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.51_SHGC_0.4 | N/A | 2.899 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
10 | LGSTORE1_WALL_1_WINDOW_4 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.51_SHGC_0.4 | N/A | 2.899 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
11 | LGSTORE1_WALL_1_DOOR_1 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.51_SHGC_0.4 | N/A | 2.899 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
12 | LGSTORE1_WALL_1_DOOR_2 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.51_SHGC_0.4 | N/A | 2.899 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
13 | LGSTORE1_FLOOR | Floor | CTF - ConductionTransferFunction | LGSTORE1_FLOOR_FFACTOR | 0.199 | 0.190 | 348.39 | 348.39 | 348.39 | 270.00 | 180.00 | 22.86 | 15.24 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | LGSTORE1_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 348.39 | 348.39 | 348.39 | 270.00 | 0.00 | 22.86 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
15 | LGSTORE1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 696.77 | 696.77 | 696.77 | 0.00 | 90.00 | 696.77 | 1.00 | 0.00 | LGSTORE1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
16 | SMSTORE1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 29.10 | 39.47 | 29.10 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
17 | SMSTORE1_WALL_1_WINDOW_1 | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.51_SHGC_0.4 | N/A | 2.899 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
18 | SMSTORE1_WALL_1_WINDOW_2 | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.51_SHGC_0.4 | N/A | 2.899 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
19 | SMSTORE1_WALL_1_DOOR | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.51_SHGC_0.4 | N/A | 2.899 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
20 | SMSTORE1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | SMSTORE1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 35.57 | 39.47 | 35.57 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | SMSTORE1_WALL_3_DOOR | Door | SMSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
23 | SMSTORE1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE2_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
24 | SMSTORE1_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE1_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | SMSTORE1_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
26 | SMSTORE1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
27 | SMSTORE2_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 29.12 | 39.47 | 29.12 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | SMSTORE2_WALL_1_WINDOW_1 | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.51_SHGC_0.4 | N/A | 2.899 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
29 | SMSTORE2_WALL_1_WINDOW_2 | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.51_SHGC_0.4 | N/A | 2.899 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
30 | SMSTORE2_WALL_1_DOOR | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.51_SHGC_0.4 | N/A | 2.899 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
31 | SMSTORE2_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
32 | SMSTORE2_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | SMSTORE2_WALL_3_DOOR | Door | SMSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
34 | SMSTORE2_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE3_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | SMSTORE2_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE2_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
36 | SMSTORE2_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
37 | SMSTORE2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
38 | SMSTORE3_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 29.12 | 39.47 | 29.12 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
39 | SMSTORE3_WALL_1_WINDOW_1 | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.51_SHGC_0.4 | N/A | 2.899 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
40 | SMSTORE3_WALL_1_WINDOW_2 | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.51_SHGC_0.4 | N/A | 2.899 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
41 | SMSTORE3_WALL_1_DOOR | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.51_SHGC_0.4 | N/A | 2.899 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
42 | SMSTORE3_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE2_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | SMSTORE3_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | SMSTORE3_WALL_3_DOOR | Door | SMSTORE3_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
45 | SMSTORE3_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE4_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | SMSTORE3_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE3_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
47 | SMSTORE3_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
48 | SMSTORE3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
49 | SMSTORE4_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 29.12 | 39.47 | 29.12 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | SMSTORE4_WALL_1_WINDOW_1 | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.51_SHGC_0.4 | N/A | 2.899 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
51 | SMSTORE4_WALL_1_WINDOW_2 | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.51_SHGC_0.4 | N/A | 2.899 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
52 | SMSTORE4_WALL_1_DOOR | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.51_SHGC_0.4 | N/A | 2.899 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | SMSTORE4_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE3_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | SMSTORE4_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | SMSTORE4_WALL_3_DOOR | Door | SMSTORE4_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | SMSTORE4_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE2_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | SMSTORE4_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE4_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | SMSTORE4_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | SMSTORE4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | LGSTORE2_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE4_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | LGSTORE2_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 71.19 | 78.94 | 71.19 | 0.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
62 | LGSTORE2_WALL_3_DOOR_1 | Door | LGSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
63 | LGSTORE2_WALL_3_DOOR_2 | Door | LGSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
64 | LGSTORE2_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE5_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | LGSTORE2_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 58.24 | 78.94 | 58.24 | 180.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
66 | LGSTORE2_WALL_1_WINDOW_1 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.51_SHGC_0.4 | N/A | 2.899 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | LGSTORE2_WALL_1_WINDOW_2 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.51_SHGC_0.4 | N/A | 2.899 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | LGSTORE2_WALL_1_WINDOW_3 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.51_SHGC_0.4 | N/A | 2.899 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | LGSTORE2_WALL_1_WINDOW_4 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.51_SHGC_0.4 | N/A | 2.899 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | LGSTORE2_WALL_1_DOOR_1 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.51_SHGC_0.4 | N/A | 2.899 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
71 | LGSTORE2_WALL_1_DOOR_2 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.51_SHGC_0.4 | N/A | 2.899 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
72 | LGSTORE2_FLOOR | Floor | CTF - ConductionTransferFunction | LGSTORE2_FLOOR_FFACTOR | 0.112 | 0.109 | 348.39 | 348.39 | 348.39 | 270.00 | 180.00 | 22.86 | 15.24 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
73 | LGSTORE2_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 348.39 | 348.39 | 348.39 | 270.00 | 0.00 | 22.86 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
74 | LGSTORE2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 696.77 | 696.77 | 696.77 | 0.00 | 90.00 | 696.77 | 1.00 | 0.00 | LGSTORE2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
75 | SMSTORE5_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 29.12 | 39.47 | 29.12 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | SMSTORE5_WALL_1_WINDOW_1 | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.51_SHGC_0.4 | N/A | 2.899 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
77 | SMSTORE5_WALL_1_WINDOW_2 | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.51_SHGC_0.4 | N/A | 2.899 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | SMSTORE5_WALL_1_DOOR | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.51_SHGC_0.4 | N/A | 2.899 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
79 | SMSTORE5_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE2_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | SMSTORE5_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | SMSTORE5_WALL_3_DOOR | Door | SMSTORE5_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
82 | SMSTORE5_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE6_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
83 | SMSTORE5_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE5_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
84 | SMSTORE5_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
85 | SMSTORE5_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE5_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
86 | SMSTORE6_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 29.12 | 39.47 | 29.12 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | SMSTORE6_WALL_1_WINDOW_1 | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.51_SHGC_0.4 | N/A | 2.899 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
88 | SMSTORE6_WALL_1_WINDOW_2 | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.51_SHGC_0.4 | N/A | 2.899 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
89 | SMSTORE6_WALL_1_DOOR | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.51_SHGC_0.4 | N/A | 2.899 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
90 | SMSTORE6_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE5_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
91 | SMSTORE6_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
92 | SMSTORE6_WALL_3_DOOR | Door | SMSTORE6_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
93 | SMSTORE6_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE7_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | SMSTORE6_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE6_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
95 | SMSTORE6_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
96 | SMSTORE6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
97 | SMSTORE7_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 29.12 | 39.47 | 29.12 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | SMSTORE7_WALL_1_WINDOW_1 | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.51_SHGC_0.4 | N/A | 2.899 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
99 | SMSTORE7_WALL_1_WINDOW_2 | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.51_SHGC_0.4 | N/A | 2.899 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
100 | SMSTORE7_WALL_1_DOOR | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.51_SHGC_0.4 | N/A | 2.899 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
101 | SMSTORE7_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE6_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
102 | SMSTORE7_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 35.59 | 39.47 | 35.59 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | SMSTORE7_WALL_3_DOOR | Door | SMSTORE7_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
104 | SMSTORE7_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE8_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | SMSTORE7_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE7_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
106 | SMSTORE7_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
107 | SMSTORE7_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE7_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
108 | SMSTORE8_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 29.12 | 39.47 | 29.12 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | SMSTORE8_WALL_1_WINDOW_1 | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.51_SHGC_0.4 | N/A | 2.899 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
110 | SMSTORE8_WALL_1_WINDOW_2 | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.51_SHGC_0.4 | N/A | 2.899 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
111 | SMSTORE8_WALL_1_DOOR | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.51_SHGC_0.4 | N/A | 2.899 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
112 | SMSTORE8_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE7_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
113 | SMSTORE8_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | SMSTORE8_WALL_3_DOOR | Door | SMSTORE8_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
115 | SMSTORE8_WALL_4 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | SMSTORE8_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE8_FLOOR_FFACTOR | 0.289 | 0.270 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | SMSTORE8_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | SMSTORE8_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE8_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1 |
2 | VETERANS DAY | Holiday | InputFile | 11/11 | 1 |
3 | CHRISTMAS | Holiday | InputFile | 12/25 | 1 |
4 | INDEPENDENCE DAY | Holiday | InputFile | 07/04 | 1 |
5 | MLK DAY | Holiday | InputFile | 01/16 | 1 |
6 | PRESIDENTS DAY | Holiday | InputFile | 02/20 | 1 |
7 | MEMORIAL DAY | Holiday | InputFile | 05/29 | 1 |
8 | LABOR DAY | Holiday | InputFile | 09/04 | 1 |
9 | COLUMBUS DAY | Holiday | InputFile | 10/09 | 1 |
10 | THANKSGIVING | Holiday | InputFile | 11/23 | 1 |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
NumberofWarmupDays | |
1 | 10 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | LGSTORE1 | RunPeriod: RUNPERIOD 1 | 2.9824213680E-002 | 0.1654963274 | Pass | Pass | 0.1446597382 | 0.5961019566 | Pass | Pass |
2 | SMSTORE1 | RunPeriod: RUNPERIOD 1 | 5.3934892161E-002 | 0.1357341529 | Pass | Pass | 8.5859404679E-002 | 0.2931228029 | Pass | Pass |
3 | SMSTORE2 | RunPeriod: RUNPERIOD 1 | 3.3620284662E-002 | 0.1708812021 | Pass | Pass | 0.2184280279 | 1.4452974620 | Pass | Pass |
4 | SMSTORE3 | RunPeriod: RUNPERIOD 1 | 4.0475263879E-002 | 0.2212654468 | Pass | Pass | 0.1085625858 | 0.3877558198 | Pass | Pass |
5 | SMSTORE4 | RunPeriod: RUNPERIOD 1 | 4.5372113445E-002 | 0.2574685740 | Pass | Pass | 9.6627497049E-002 | 0.3538711617 | Pass | Pass |
6 | LGSTORE2 | RunPeriod: RUNPERIOD 1 | 5.6919360063E-002 | 0.2971898501 | Pass | Pass | 3.2990432299E-002 | 0.1037253111 | Pass | Pass |
7 | SMSTORE5 | RunPeriod: RUNPERIOD 1 | 5.7132607580E-002 | 0.3000722788 | Pass | Pass | 3.0569476223E-002 | 9.5169097749E-002 | Pass | Pass |
8 | SMSTORE6 | RunPeriod: RUNPERIOD 1 | 5.8316722562E-002 | 0.3030712033 | Pass | Pass | 3.0414582248E-002 | 9.5418949101E-002 | Pass | Pass |
9 | SMSTORE7 | RunPeriod: RUNPERIOD 1 | 6.3179164868E-002 | 0.3222172902 | Pass | Pass | 2.9506057955E-002 | 9.6443653388E-002 | Pass | Pass |
10 | SMSTORE8 | RunPeriod: RUNPERIOD 1 | 8.2700212356E-002 | 0.4085417598 | Pass | Pass | 2.4533734553E-002 | 8.5055944534E-002 | Pass | Pass |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2020-06-03 19:18:58
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | -4.20 | 0.00 | -4.20 | Wetbulb [C] | 4.30 | 20.00 |
SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 29.40 | 10.40 | 18.30 | Wetbulb [C] | 4.20 | 350.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2020-06-03 19:18:58
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_2 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE1_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 78.94 | 71.15 | 0.00 | 90.00 | N |
LGSTORE1_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 78.94 | 58.20 | 180.00 | 90.00 | S |
LGSTORE1_ROOF | NONRES_ROOF | 0.23 | 0.273 | 0.283 | 348.39 | 348.39 | 270.00 | 0.00 | |
SMSTORE1_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 29.10 | 180.00 | 90.00 | S |
SMSTORE1_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 35.57 | 0.00 | 90.00 | N |
SMSTORE1_ROOF | NONRES_ROOF | 0.23 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE2_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 29.12 | 180.00 | 90.00 | S |
SMSTORE2_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE2_ROOF | NONRES_ROOF | 0.23 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE3_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 29.12 | 180.00 | 90.00 | S |
SMSTORE3_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE3_ROOF | NONRES_ROOF | 0.23 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE4_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 29.12 | 180.00 | 90.00 | S |
SMSTORE4_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE4_ROOF | NONRES_ROOF | 0.23 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
LGSTORE2_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 78.94 | 71.19 | 0.00 | 90.00 | N |
LGSTORE2_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 78.94 | 58.24 | 180.00 | 90.00 | S |
LGSTORE2_ROOF | NONRES_ROOF | 0.23 | 0.273 | 0.283 | 348.39 | 348.39 | 270.00 | 0.00 | |
SMSTORE5_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 29.12 | 180.00 | 90.00 | S |
SMSTORE5_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE5_ROOF | NONRES_ROOF | 0.23 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE6_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 29.12 | 180.00 | 90.00 | S |
SMSTORE6_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE6_ROOF | NONRES_ROOF | 0.23 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE7_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 29.12 | 180.00 | 90.00 | S |
SMSTORE7_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE7_ROOF | NONRES_ROOF | 0.23 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE8_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 29.12 | 180.00 | 90.00 | S |
SMSTORE8_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE8_WALL_4 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE8_ROOF | NONRES_ROOF | 0.23 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
LGSTORE1_FLOOR | LGSTORE1_FLOOR_FFACTOR | 1.00 | 0.199 | 348.39 | 348.39 | 270.00 | 180.00 | ||
SMSTORE1_FLOOR | SMSTORE1_FLOOR_FFACTOR | 1.00 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | ||
SMSTORE2_FLOOR | SMSTORE2_FLOOR_FFACTOR | 1.00 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | ||
SMSTORE3_FLOOR | SMSTORE3_FLOOR_FFACTOR | 1.00 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | ||
SMSTORE4_FLOOR | SMSTORE4_FLOOR_FFACTOR | 1.00 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | ||
LGSTORE2_FLOOR | LGSTORE2_FLOOR_FFACTOR | 1.00 | 0.112 | 348.39 | 348.39 | 270.00 | 180.00 | ||
SMSTORE5_FLOOR | SMSTORE5_FLOOR_FFACTOR | 1.00 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | ||
SMSTORE6_FLOOR | SMSTORE6_FLOOR_FFACTOR | 1.00 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | ||
SMSTORE7_FLOOR | SMSTORE7_FLOOR_FFACTOR | 1.00 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | ||
SMSTORE8_FLOOR | SMSTORE8_FLOOR_FFACTOR | 1.00 | 0.289 | 174.19 | 174.19 | 270.00 | 180.00 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.51_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.899 | 0.395 | 0.401 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE1_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.51_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.899 | 0.395 | 0.401 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE1_WALL_1_WINDOW_3 | NONRESWINDOW_U_0.51_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.899 | 0.395 | 0.401 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE1_WALL_1_WINDOW_4 | NONRESWINDOW_U_0.51_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.899 | 0.395 | 0.401 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE1_WALL_1_DOOR_1 | NONRESWINDOW_U_0.51_SHGC_0.4 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.899 | 0.395 | 0.401 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE1_WALL_1_DOOR_2 | NONRESWINDOW_U_0.51_SHGC_0.4 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.899 | 0.395 | 0.401 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE1_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.51_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.899 | 0.395 | 0.401 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE1_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.51_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.899 | 0.395 | 0.401 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE1_WALL_1_DOOR | NONRESWINDOW_U_0.51_SHGC_0.4 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.899 | 0.395 | 0.401 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE2_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.51_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.899 | 0.395 | 0.401 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE2_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.51_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.899 | 0.395 | 0.401 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE2_WALL_1_DOOR | NONRESWINDOW_U_0.51_SHGC_0.4 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.899 | 0.395 | 0.401 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE3_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.51_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.899 | 0.395 | 0.401 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE3_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.51_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.899 | 0.395 | 0.401 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE3_WALL_1_DOOR | NONRESWINDOW_U_0.51_SHGC_0.4 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.899 | 0.395 | 0.401 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE4_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.51_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.899 | 0.395 | 0.401 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE4_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.51_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.899 | 0.395 | 0.401 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE4_WALL_1_DOOR | NONRESWINDOW_U_0.51_SHGC_0.4 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.899 | 0.395 | 0.401 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE2_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.51_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.899 | 0.395 | 0.401 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE2_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.51_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.899 | 0.395 | 0.401 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE2_WALL_1_WINDOW_3 | NONRESWINDOW_U_0.51_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.899 | 0.395 | 0.401 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE2_WALL_1_WINDOW_4 | NONRESWINDOW_U_0.51_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.899 | 0.395 | 0.401 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE2_WALL_1_DOOR_1 | NONRESWINDOW_U_0.51_SHGC_0.4 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.899 | 0.395 | 0.401 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE2_WALL_1_DOOR_2 | NONRESWINDOW_U_0.51_SHGC_0.4 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.899 | 0.395 | 0.401 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE5_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.51_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.899 | 0.395 | 0.401 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE5_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.51_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.899 | 0.395 | 0.401 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE5_WALL_1_DOOR | NONRESWINDOW_U_0.51_SHGC_0.4 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.899 | 0.395 | 0.401 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE6_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.51_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.899 | 0.395 | 0.401 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE6_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.51_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.899 | 0.395 | 0.401 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE6_WALL_1_DOOR | NONRESWINDOW_U_0.51_SHGC_0.4 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.899 | 0.395 | 0.401 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE7_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.51_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.899 | 0.395 | 0.401 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE7_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.51_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.899 | 0.395 | 0.401 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE7_WALL_1_DOOR | NONRESWINDOW_U_0.51_SHGC_0.4 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.899 | 0.395 | 0.401 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE8_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.51_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.899 | 0.395 | 0.401 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE8_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.51_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.899 | 0.395 | 0.401 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE8_WALL_1_DOOR | NONRESWINDOW_U_0.51_SHGC_0.4 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.899 | 0.395 | 0.401 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | ||
Total or Average | 124.29 | 2.899 | 0.395 | 0.401 | ||||||||||||
North Total or Average | 0.00 | - | - | - | ||||||||||||
Non-North Total or Average | 124.29 | 2.899 | 0.395 | 0.401 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
LGSTORE1_WALL_3_DOOR_1 | SWINGING DOOR_CON | 2.492 | 3.975 | 3.90 | LGSTORE1_WALL_3 |
LGSTORE1_WALL_3_DOOR_2 | SWINGING DOOR_CON | 2.492 | 3.975 | 3.90 | LGSTORE1_WALL_3 |
SMSTORE1_WALL_3_DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 3.90 | SMSTORE1_WALL_3 |
SMSTORE2_WALL_3_DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 3.88 | SMSTORE2_WALL_3 |
SMSTORE3_WALL_3_DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 3.88 | SMSTORE3_WALL_3 |
SMSTORE4_WALL_3_DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 3.88 | SMSTORE4_WALL_3 |
LGSTORE2_WALL_3_DOOR_1 | SWINGING DOOR_CON | 2.492 | 3.975 | 3.88 | LGSTORE2_WALL_3 |
LGSTORE2_WALL_3_DOOR_2 | SWINGING DOOR_CON | 2.492 | 3.975 | 3.88 | LGSTORE2_WALL_3 |
SMSTORE5_WALL_3_DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 3.88 | SMSTORE5_WALL_3 |
SMSTORE6_WALL_3_DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 3.88 | SMSTORE6_WALL_3 |
SMSTORE7_WALL_3_DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 3.88 | SMSTORE7_WALL_3 |
SMSTORE8_WALL_3_DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 3.88 | SMSTORE8_WALL_3 |
Report: Shading Summary
For: Entire Facility
Timestamp: 2020-06-03 19:18:58
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
LGSTORE1_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_DOOR_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_DOOR_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_DOOR_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_DOOR_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2020-06-03 19:18:58
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
LGSTORE1_LIGHTS | LGSTORE1 | 18.3225 | 348.39 | 6383.30 | LightsWired | TYPE1_LIGHT_SCH | 98.40 | 168.00 | 98.38 | 0.0000 | Y | 117.88 |
LGSTORE1_LIGHTS_ALLOWANCE | LGSTORE1 | 6.6413 | 348.39 | 2313.75 | LightsWired | TYPE1_LIGHT_SCH | 98.40 | 168.00 | 98.38 | 0.0000 | Y | 42.73 |
SMSTORE1_LIGHTS | SMSTORE1 | 18.3225 | 174.19 | 3191.65 | LightsWired | TYPE1_LIGHT_SCH | 98.40 | 168.00 | 98.38 | 0.0000 | Y | 58.94 |
SMSTORE1_LIGHTS_ALLOWANCE | SMSTORE1 | 9.5153 | 174.19 | 1657.50 | LightsWired | TYPE1_LIGHT_SCH | 98.40 | 168.00 | 98.38 | 0.0000 | Y | 30.61 |
SMSTORE2_LIGHTS | SMSTORE2 | 18.3225 | 174.19 | 3191.65 | LightsWired | TYPE2_LIGHT_SCH | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 46.71 |
SMSTORE2_LIGHTS_ALLOWANCE | SMSTORE2 | 7.3625 | 174.19 | 1282.50 | LightsWired | TYPE2_LIGHT_SCH | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 18.77 |
SMSTORE3_LIGHTS | SMSTORE3 | 18.3225 | 174.19 | 3191.65 | LightsWired | TYPE2_LIGHT_SCH | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 46.71 |
SMSTORE3_LIGHTS_ALLOWANCE | SMSTORE3 | 7.3625 | 174.19 | 1282.50 | LightsWired | TYPE2_LIGHT_SCH | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 18.77 |
SMSTORE4_LIGHTS | SMSTORE4 | 18.3225 | 174.19 | 3191.65 | LightsWired | TYPE2_LIGHT_SCH | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 46.71 |
SMSTORE4_LIGHTS_ALLOWANCE | SMSTORE4 | 7.3625 | 174.19 | 1282.50 | LightsWired | TYPE2_LIGHT_SCH | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 18.77 |
LGSTORE2_LIGHTS | LGSTORE2 | 18.3225 | 348.39 | 6383.30 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 168.00 | 71.66 | 0.0000 | Y | 85.86 |
LGSTORE2_LIGHTS_ALLOWANCE | LGSTORE2 | 0.0000 | 348.39 | 0.00 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE5_LIGHTS | SMSTORE5 | 18.3225 | 174.19 | 3191.65 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 168.00 | 71.66 | 0.0000 | Y | 42.93 |
SMSTORE5_LIGHTS_ALLOWANCE | SMSTORE5 | 0.0000 | 174.19 | 0.00 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE6_LIGHTS | SMSTORE6 | 18.3225 | 174.19 | 3191.65 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 168.00 | 71.66 | 0.0000 | Y | 42.93 |
SMSTORE6_LIGHTS_ALLOWANCE | SMSTORE6 | 0.0000 | 174.19 | 0.00 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE7_LIGHTS | SMSTORE7 | 18.3225 | 174.19 | 3191.65 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 168.00 | 71.66 | 0.0000 | Y | 42.93 |
SMSTORE7_LIGHTS_ALLOWANCE | SMSTORE7 | 0.0000 | 174.19 | 0.00 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE8_LIGHTS | SMSTORE8 | 18.3225 | 174.19 | 3191.65 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 168.00 | 71.66 | 0.0000 | Y | 42.93 |
SMSTORE8_LIGHTS_ALLOWANCE | SMSTORE8 | 0.0000 | 174.19 | 0.00 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
Interior Lighting Total | 11.0315 | 4180.64 | 46118.53 | 704.17 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS | 7048.38 | AstronomicalClock | - | 83.55 | 83.55 | 110.54 | |
Exterior Lighting Total | 7048.38 | 110.54 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2020-06-03 19:18:58
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 34903.68 | 27667.10 | 7236.58 | 0.79 | 3.50 | |||
PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 19057.24 | 15166.70 | 3890.54 | 0.80 | 3.50 | |||
PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 19055.76 | 15165.15 | 3890.61 | 0.80 | 3.50 | |||
PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 19107.22 | 15207.82 | 3899.40 | 0.80 | 3.50 | |||
PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 18976.33 | 15098.90 | 3877.43 | 0.80 | 3.91 | |||
PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 33739.81 | 26720.92 | 7018.89 | 0.79 | 3.50 | |||
PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 17460.67 | 13839.33 | 3621.34 | 0.79 | 3.91 | |||
PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 17343.94 | 13742.30 | 3601.64 | 0.79 | 3.91 | |||
PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 17211.89 | 13632.68 | 3579.21 | 0.79 | 3.91 | |||
PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 17115.56 | 13585.82 | 3529.74 | 0.79 | 3.91 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | 33277.7 | 10.05 | ||||
PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | 18161.8 | 28.43 | ||||
PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | 18160.4 | 38.47 | ||||
PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | 18209.3 | 48.40 | ||||
PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | 18085.1 | 64.51 | ||||
PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | 32171.1 | 43.15 | ||||
PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | 16647.5 | 102.55 | ||||
PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | 16536.7 | 114.29 | ||||
PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | 16411.5 | 126.21 | ||||
PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | 16315.9 | 137.87 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
PSZ-AC_1:1_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 59163.99 | 0.80 | |
PSZ-AC_2:2_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 31956.19 | 0.80 | |
PSZ-AC_3:3_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 31952.59 | 0.80 | |
PSZ-AC_4:4_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 32028.66 | 0.80 | |
PSZ-AC_5:5_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 31834.54 | 0.80 | |
PSZ-AC_6:6_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 57516.69 | 0.80 | |
PSZ-AC_7:7_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 29588.90 | 0.80 | |
PSZ-AC_8:8_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 29416.34 | 0.80 | |
PSZ-AC_9:9_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 29221.12 | 0.80 | |
PSZ-AC_10:10_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 29201.40 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.57 | 622.50 | 2.07 | 2270.26 | 1094.51 | 1.00 | 1.28 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 |
PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.55 | 622.50 | 1.14 | 1302.52 | 1140.11 | 1.00 | 1.33 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 |
PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.55 | 622.50 | 1.14 | 1302.34 | 1140.11 | 1.00 | 1.33 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 |
PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.55 | 622.50 | 1.15 | 1306.19 | 1140.11 | 1.00 | 1.33 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 |
PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.55 | 622.50 | 1.14 | 1296.37 | 1140.11 | 1.00 | 1.33 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 |
PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.57 | 622.50 | 2.00 | 2190.27 | 1094.51 | 1.00 | 1.29 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 |
PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.55 | 622.50 | 1.04 | 1182.77 | 1140.11 | 1.00 | 1.35 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 |
PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.55 | 622.50 | 1.03 | 1174.04 | 1140.11 | 1.00 | 1.35 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 |
PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.55 | 622.50 | 1.02 | 1164.16 | 1140.11 | 1.00 | 1.36 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 |
PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.55 | 622.50 | 1.02 | 1163.15 | 1140.11 | 1.00 | 1.36 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
GAS TANK1 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK2 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK3 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK4 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK5 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK6 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK7 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:18:58
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
LGSTORE1 | 23221.11 | 27865.33 | 79.98 | 1.729 | 2.074 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 23.89 | 23.89 | 0.00879 | 29.40 | 0.00879 | 0.411 | 0.00 |
SMSTORE1 | 12789.88 | 15347.86 | 88.11 | 0.952 | 1.142 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 23.89 | 23.89 | 0.00877 | 29.23 | 0.00879 | 0.206 | 0.00 |
SMSTORE2 | 12788.10 | 15345.72 | 88.10 | 0.952 | 1.142 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 23.89 | 23.89 | 0.00877 | 29.23 | 0.00879 | 0.206 | 0.00 |
SMSTORE3 | 12825.89 | 15391.07 | 88.36 | 0.955 | 1.146 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 23.89 | 23.89 | 0.00877 | 29.23 | 0.00879 | 0.206 | 0.00 |
SMSTORE4 | 12729.46 | 15275.36 | 87.69 | 0.948 | 1.137 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 23.89 | 23.89 | 0.00877 | 29.23 | 0.00879 | 0.206 | 0.00 |
LGSTORE2 | 22402.96 | 26883.55 | 77.17 | 1.668 | 2.001 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 23.89 | 23.89 | 0.00880 | 29.14 | 0.00879 | 0.411 | 0.00 |
SMSTORE5 | 11613.93 | 13936.71 | 80.01 | 0.865 | 1.037 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 23.89 | 23.89 | 0.00879 | 29.14 | 0.00879 | 0.206 | 0.00 |
SMSTORE6 | 11528.21 | 13833.85 | 79.42 | 0.858 | 1.030 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 23.89 | 23.89 | 0.00879 | 29.14 | 0.00879 | 0.206 | 0.00 |
SMSTORE7 | 11431.23 | 13717.48 | 78.75 | 0.851 | 1.021 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 23.89 | 23.89 | 0.00879 | 29.14 | 0.00879 | 0.206 | 0.00 |
SMSTORE8 | 11421.25 | 13705.50 | 78.68 | 0.850 | 1.020 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:10:00 | 23.89 | 23.89 | 0.00879 | 28.97 | 0.00879 | 0.206 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
LGSTORE1 | 23928.05 | 28713.66 | 82.42 | 1.046 | 1.256 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.10 | 0.00650 | -4.20 | 0.00269 | 0.411 | 0.00 |
SMSTORE1 | 12203.56 | 14644.27 | 84.07 | 0.534 | 0.640 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.10 | 0.00640 | -4.20 | 0.00269 | 0.206 | 0.00 |
SMSTORE2 | 12395.72 | 14874.87 | 85.39 | 0.542 | 0.650 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.10 | 0.00641 | -4.20 | 0.00269 | 0.206 | 0.00 |
SMSTORE3 | 12506.80 | 15008.16 | 86.16 | 0.547 | 0.656 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.10 | 0.00642 | -4.20 | 0.00269 | 0.206 | 0.00 |
SMSTORE4 | 12670.22 | 15204.26 | 87.28 | 0.554 | 0.665 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.10 | 0.00643 | -4.20 | 0.00269 | 0.206 | 0.00 |
LGSTORE2 | 23796.66 | 28555.99 | 81.97 | 1.041 | 1.249 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.10 | 0.00653 | -4.20 | 0.00269 | 0.411 | 0.00 |
SMSTORE5 | 12983.09 | 15579.71 | 89.44 | 0.568 | 0.681 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.10 | 0.00646 | -4.20 | 0.00269 | 0.206 | 0.00 |
SMSTORE6 | 12968.23 | 15561.88 | 89.34 | 0.567 | 0.680 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.10 | 0.00646 | -4.20 | 0.00269 | 0.206 | 0.00 |
SMSTORE7 | 13134.55 | 15761.46 | 90.48 | 0.574 | 0.689 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.10 | 0.00647 | -4.20 | 0.00269 | 0.206 | 0.00 |
SMSTORE8 | 14527.49 | 17432.99 | 100.08 | 0.635 | 0.762 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.10 | 0.00652 | -4.20 | 0.00269 | 0.206 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC_1:1 | 2.07 | 2.07 | 1.26 | 1.26 | 2.0742 | 2.0742 | 2.0742 | 1.0000 | 1.0000 |
PSZ-AC_2:2 | 1.14 | 1.14 | 0.64 | 0.64 | 1.1425 | 1.1425 | 1.1425 | 1.0000 | 1.0000 |
PSZ-AC_3:3 | 1.14 | 1.14 | 0.65 | 0.65 | 1.1423 | 1.1423 | 1.1423 | 1.0000 | 1.0000 |
PSZ-AC_4:4 | 1.15 | 1.15 | 0.66 | 0.66 | 1.1457 | 1.1457 | 1.1457 | 1.0000 | 1.0000 |
PSZ-AC_5:5 | 1.14 | 1.14 | 0.66 | 0.66 | 1.1371 | 1.1371 | 1.1371 | 1.0000 | 1.0000 |
PSZ-AC_6:6 | 2.00 | 2.00 | 1.25 | 1.25 | 2.0012 | 2.0012 | 2.0012 | 1.0000 | 1.0000 |
PSZ-AC_7:7 | 1.04 | 1.04 | 0.68 | 0.68 | 1.0374 | 1.0374 | 1.0374 | 1.0000 | 1.0000 |
PSZ-AC_8:8 | 1.03 | 1.03 | 0.68 | 0.68 | 1.0298 | 1.0298 | 1.0298 | 1.0000 | 1.0000 |
PSZ-AC_9:9 | 1.02 | 1.02 | 0.69 | 0.69 | 1.0211 | 1.0211 | 1.0211 | 1.0000 | 1.0000 |
PSZ-AC_10:10 | 1.02 | 1.02 | 0.76 | 0.76 | 1.0202 | 1.0202 | 1.0202 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_1:1 | 34903.680 | 0.000 | 2.074230 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 34903.68 | 33143.17 | 2.074230 | 24.98 | 16.81 | 0.00878945 | 12.80 | 11.97 | 0.00850000 | 29.40 | 0.00879438 | 18.30 | 19.8364 | 23.89 | 0.00878824 | 46.9241 | 23221.11 | 0.00 | -999.00 | -999.00 |
PSZ-AC_1:1_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_1:1 | 59163.992 | 59163.992 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 59163.99 | 59163.99 | 2.074231 | 12.81 | 8.52 | 0.00525320 | 40.00 | 20.98 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 19.8364 | 21.10 | 0.00650244 | 41.2706 | 23928.05 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_2:2 | 19057.240 | 0.000 | 1.142460 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 19057.24 | 18144.99 | 1.142460 | 24.88 | 16.76 | 0.00877198 | 12.80 | 11.97 | 0.00850000 | 29.40 | 0.00879438 | 18.30 | 18.0073 | 23.89 | 0.00876672 | 46.8107 | 12772.16 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_2:2 | 31956.192 | 31956.192 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 31956.19 | 31956.19 | 1.142456 | 12.98 | 8.54 | 0.00520500 | 40.00 | 20.98 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 18.0074 | 21.10 | 0.00639532 | 40.5986 | 12203.56 | 0.00 | -999.00 | -999.00 |
PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_3:3 | 19055.760 | 0.000 | 1.142300 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 19055.76 | 18143.19 | 1.142300 | 24.88 | 16.77 | 0.00877212 | 12.80 | 11.97 | 0.00850000 | 29.40 | 0.00879438 | 18.30 | 18.0099 | 23.89 | 0.00876676 | 46.8109 | 12763.63 | 0.00 | -999.00 | -999.00 |
PSZ-AC_3:3_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_3:3 | 31952.593 | 31952.593 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 31952.59 | 31952.59 | 1.142297 | 13.10 | 8.63 | 0.00523425 | 40.00 | 20.98 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 18.0099 | 21.10 | 0.00641111 | 40.6979 | 12395.72 | 0.00 | -999.00 | -999.00 |
PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_4:4 | 19107.220 | 0.000 | 1.145670 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 19107.22 | 18193.67 | 1.145670 | 24.88 | 16.76 | 0.00877160 | 12.80 | 11.97 | 0.00850000 | 29.40 | 0.00879438 | 18.30 | 17.9569 | 23.89 | 0.00876612 | 46.8075 | 12800.09 | 0.00 | -999.00 | -999.00 |
PSZ-AC_4:4_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_4:4 | 32028.661 | 32028.661 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 32028.66 | 32028.66 | 1.145672 | 13.17 | 8.68 | 0.00525073 | 40.00 | 20.98 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 17.9569 | 21.10 | 0.00641990 | 40.7531 | 12506.80 | 0.00 | -999.00 | -999.00 |
PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_5:5 | 18976.330 | 0.000 | 1.137060 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 18976.33 | 18065.13 | 1.137060 | 24.89 | 16.77 | 0.00877298 | 12.80 | 11.97 | 0.00850000 | 29.40 | 0.00879438 | 18.30 | 18.0929 | 23.89 | 0.00876776 | 46.8162 | 12703.95 | 0.00 | -999.00 | -999.00 |
PSZ-AC_5:5_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_5:5 | 31834.537 | 31834.537 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 31834.54 | 31834.54 | 1.137059 | 13.28 | 8.76 | 0.00527475 | 40.00 | 20.98 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 18.0929 | 21.10 | 0.00643284 | 40.8345 | 12670.22 | 0.00 | -999.00 | -999.00 |
PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_6:6 | 33739.810 | 0.000 | 2.001150 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 33739.81 | 32001.44 | 2.001150 | 25.01 | 16.83 | 0.00879651 | 12.80 | 11.97 | 0.00850000 | 29.31 | 0.00879438 | 18.27 | 20.5608 | 23.89 | 0.00879687 | 46.9695 | 22380.72 | 0.00 | -999.00 | -999.00 |
PSZ-AC_6:6_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_6:6 | 57516.688 | 57516.688 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 57516.69 | 57516.69 | 2.001151 | 12.77 | 8.51 | 0.00526215 | 40.00 | 20.98 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 20.5608 | 21.10 | 0.00652606 | 41.4186 | 23796.66 | 0.00 | -999.00 | -999.00 |
PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_7:7 | 17460.670 | 0.000 | 1.037410 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 17460.67 | 16578.62 | 1.037410 | 24.98 | 16.82 | 0.00878997 | 12.80 | 11.97 | 0.00850000 | 29.40 | 0.00879438 | 18.30 | 19.8308 | 23.89 | 0.00878835 | 46.9246 | 11604.36 | 0.00 | -999.00 | -999.00 |
PSZ-AC_7:7_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_7:7 | 29588.895 | 29588.895 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 29588.90 | 29588.90 | 1.037413 | 13.46 | 8.89 | 0.00531923 | 40.00 | 20.98 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 19.8307 | 21.10 | 0.00645658 | 40.9837 | 12983.09 | 0.00 | -999.00 | -999.00 |
PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_8:8 | 17343.940 | 0.000 | 1.029760 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 17343.94 | 16464.34 | 1.029760 | 24.99 | 16.82 | 0.00879134 | 12.80 | 11.97 | 0.00850000 | 29.40 | 0.00879438 | 18.30 | 19.9781 | 23.89 | 0.00879007 | 46.9336 | 11501.43 | 0.00 | -999.00 | -999.00 |
PSZ-AC_8:8_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_8:8 | 29416.341 | 29416.341 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 29416.34 | 29416.34 | 1.029757 | 13.46 | 8.89 | 0.00531717 | 40.00 | 20.98 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 19.9782 | 21.10 | 0.00645549 | 40.9768 | 12968.23 | 0.00 | -999.00 | -999.00 |
PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_9:9 | 17211.890 | 0.000 | 1.021090 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 17211.89 | 16335.09 | 1.021090 | 25.00 | 16.82 | 0.00879291 | 12.80 | 11.97 | 0.00850000 | 29.40 | 0.00879438 | 18.30 | 20.1478 | 23.89 | 0.00879204 | 46.9440 | 11404.76 | 0.00 | -999.00 | -999.00 |
PSZ-AC_9:9_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_9:9 | 29221.121 | 29221.121 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 29221.12 | 29221.12 | 1.021094 | 13.55 | 8.96 | 0.00534026 | 40.00 | 20.98 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 20.1477 | 21.10 | 0.00646786 | 41.0545 | 13134.55 | 0.00 | -999.00 | -999.00 |
PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_10:10 | 17115.560 | 0.000 | 1.020200 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:10:00 | 17115.56 | 16240.30 | 1.020200 | 24.95 | 16.81 | 0.00879298 | 12.80 | 11.97 | 0.00850000 | 29.14 | 0.00879438 | 18.22 | 20.1653 | 23.89 | 0.00879239 | 46.9458 | 11405.77 | 0.00 | -999.00 | -999.00 |
PSZ-AC_10:10_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_10:10 | 29201.400 | 29201.400 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 29201.40 | 29201.40 | 1.020205 | 14.28 | 9.44 | 0.00548517 | 40.00 | 20.98 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 20.1652 | 21.10 | 0.00651828 | 41.3722 | 14527.49 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2020-06-03 19:18:58
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | LGSTORE1 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 34903.680 | 0.000 | 2.074230 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.1792 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 34903.68 | 33143.17 | 1.0000 | 2.46209189 | 2.074230 | 24.98 | 16.81 | 0.00878945 | 47493.1 | 12.80 | 11.97 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 34903.68 | 29.40 | 0.00879438 | 18.30 | 0.41145340 | 19.8364 | 23.89 | 0.00878824 | 23.89 | 0.00878824 | 46.9241 | 23221.11 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_1:1_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | LGSTORE1 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 59163.992 | 59163.992 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.074231 | 2.46209271 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 59163.99 | 59163.99 | 1.0000 | 2.46209271 | 2.074231 | 12.81 | 8.52 | 0.00525320 | 26138.3 | 40.00 | 20.98 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 59163.99 | -4.20 | 0.00269032 | -4.20 | 0.41145340 | 19.8364 | 21.11 | 0.00650244 | 21.10 | 0.00650244 | 41.2706 | 23928.05 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | SMSTORE1 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 19057.240 | 0.000 | 1.142460 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.1467 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 19057.24 | 18144.99 | 1.0000 | 1.35608949 | 1.142460 | 24.88 | 16.76 | 0.00877198 | 47347.1 | 12.80 | 11.97 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 19057.24 | 29.40 | 0.00879438 | 18.30 | 0.20572670 | 18.0073 | 23.89 | 0.00876706 | 23.89 | 0.00876672 | 46.8107 | 12772.16 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | SMSTORE1 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 31956.192 | 31956.192 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.142456 | 1.35608434 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 31956.19 | 31956.19 | 1.0000 | 1.35608434 | 1.142456 | 12.98 | 8.54 | 0.00520500 | 26181.5 | 40.00 | 20.98 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 31956.19 | -4.20 | 0.00269032 | -4.20 | 0.20572670 | 18.0074 | 21.11 | 0.00639532 | 21.10 | 0.00639532 | 40.5986 | 12203.56 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_3:3 | SMSTORE2 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 19055.760 | 0.000 | 1.142300 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.1469 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 19055.76 | 18143.19 | 1.0000 | 1.35589957 | 1.142300 | 24.88 | 16.77 | 0.00877212 | 47348.1 | 12.80 | 11.97 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 19055.76 | 29.40 | 0.00879438 | 18.30 | 0.20572670 | 18.0099 | 23.89 | 0.00876721 | 23.89 | 0.00876676 | 46.8109 | 12763.63 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_3:3_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_3:3 | SMSTORE2 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 31952.593 | 31952.593 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.142297 | 1.35589561 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 31952.59 | 31952.59 | 1.0000 | 1.35589561 | 1.142297 | 13.10 | 8.63 | 0.00523425 | 26383.2 | 40.00 | 20.98 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 31952.59 | -4.20 | 0.00269032 | -4.20 | 0.20572670 | 18.0099 | 21.11 | 0.00641111 | 21.10 | 0.00641111 | 40.6979 | 12395.72 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_4:4 | SMSTORE3 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 19107.220 | 0.000 | 1.145670 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.1460 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 19107.22 | 18193.67 | 1.0000 | 1.35989973 | 1.145670 | 24.88 | 16.76 | 0.00877160 | 47343.9 | 12.80 | 11.97 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 19107.22 | 29.40 | 0.00879438 | 18.30 | 0.20572670 | 17.9569 | 23.89 | 0.00876660 | 23.89 | 0.00876612 | 46.8075 | 12800.09 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_4:4_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_4:4 | SMSTORE3 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 32028.661 | 32028.661 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.145672 | 1.35990233 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 32028.66 | 32028.66 | 1.0000 | 1.35990233 | 1.145672 | 13.17 | 8.68 | 0.00525073 | 26497.0 | 40.00 | 20.98 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 32028.66 | -4.20 | 0.00269032 | -4.20 | 0.20572670 | 17.9569 | 21.11 | 0.00641990 | 21.10 | 0.00641990 | 40.7531 | 12506.80 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_5:5 | SMSTORE4 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 18976.330 | 0.000 | 1.137060 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.1485 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 18976.33 | 18065.13 | 1.0000 | 1.34967974 | 1.137060 | 24.89 | 16.77 | 0.00877298 | 47355.0 | 12.80 | 11.97 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 18976.33 | 29.40 | 0.00879438 | 18.30 | 0.20572670 | 18.0929 | 23.89 | 0.00876824 | 23.89 | 0.00876776 | 46.8162 | 12703.95 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_5:5_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_5:5 | SMSTORE4 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 31834.537 | 31834.537 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.137059 | 1.34967831 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 31834.54 | 31834.54 | 1.0000 | 1.34967831 | 1.137059 | 13.28 | 8.76 | 0.00527475 | 26661.4 | 40.00 | 20.98 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 31834.54 | -4.20 | 0.00269032 | -4.20 | 0.20572670 | 18.0929 | 21.11 | 0.00643284 | 21.10 | 0.00643284 | 40.8345 | 12670.22 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_6:6 | LGSTORE2 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 33739.810 | 0.000 | 2.001150 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.1923 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 33739.81 | 32001.44 | 1.0000 | 2.37534661 | 2.001150 | 25.01 | 16.83 | 0.00879651 | 47534.8 | 12.80 | 11.97 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 33739.81 | 29.31 | 0.00879438 | 18.27 | 0.41145340 | 20.5608 | 23.89 | 0.00879707 | 23.89 | 0.00879687 | 46.9695 | 22380.72 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_6:6_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_6:6 | LGSTORE2 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 57516.688 | 57516.688 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.001151 | 2.37534798 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 57516.69 | 57516.69 | 1.0000 | 2.37534798 | 2.001151 | 12.77 | 8.51 | 0.00526215 | 26114.6 | 40.00 | 20.98 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 57516.69 | -4.20 | 0.00269032 | -4.20 | 0.41145340 | 20.5608 | 21.11 | 0.00652606 | 21.10 | 0.00652606 | 41.4186 | 23796.66 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_7:7 | SMSTORE5 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 17460.670 | 0.000 | 1.037410 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.1801 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 17460.67 | 16578.62 | 1.0000 | 1.23139611 | 1.037410 | 24.98 | 16.82 | 0.00878997 | 47496.7 | 12.80 | 11.97 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 17460.67 | 29.40 | 0.00879438 | 18.30 | 0.20572670 | 19.8308 | 23.89 | 0.00878888 | 23.89 | 0.00878835 | 46.9246 | 11604.36 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_7:7_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_7:7 | SMSTORE5 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 29588.895 | 29588.895 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.037413 | 1.23140019 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 29588.90 | 29588.90 | 1.0000 | 1.23140019 | 1.037413 | 13.46 | 8.89 | 0.00531923 | 26965.3 | 40.00 | 20.98 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 29588.90 | -4.20 | 0.00269032 | -4.20 | 0.20572670 | 19.8307 | 21.11 | 0.00645658 | 21.10 | 0.00645658 | 40.9837 | 12983.09 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_8:8 | SMSTORE6 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 17343.940 | 0.000 | 1.029760 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.1827 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 17343.94 | 16464.34 | 1.0000 | 1.22231563 | 1.029760 | 24.99 | 16.82 | 0.00879134 | 47508.5 | 12.80 | 11.97 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 17343.94 | 29.40 | 0.00879438 | 18.30 | 0.20572670 | 19.9781 | 23.89 | 0.00879058 | 23.89 | 0.00879007 | 46.9336 | 11501.43 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_8:8_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_8:8 | SMSTORE6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 29416.341 | 29416.341 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.029757 | 1.22231169 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 29416.34 | 29416.34 | 1.0000 | 1.22231169 | 1.029757 | 13.46 | 8.89 | 0.00531717 | 26951.2 | 40.00 | 20.98 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 29416.34 | -4.20 | 0.00269032 | -4.20 | 0.20572670 | 19.9782 | 21.11 | 0.00645549 | 21.10 | 0.00645549 | 40.9768 | 12968.23 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_9:9 | SMSTORE7 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 17211.890 | 0.000 | 1.021090 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.1856 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 17211.89 | 16335.09 | 1.0000 | 1.21202442 | 1.021090 | 25.00 | 16.82 | 0.00879291 | 47522.1 | 12.80 | 11.97 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 17211.89 | 29.40 | 0.00879438 | 18.30 | 0.20572670 | 20.1478 | 23.89 | 0.00879254 | 23.89 | 0.00879204 | 46.9440 | 11404.76 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_9:9_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_9:9 | SMSTORE7 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 29221.121 | 29221.121 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.021094 | 1.21202958 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 29221.12 | 29221.12 | 1.0000 | 1.21202958 | 1.021094 | 13.55 | 8.96 | 0.00534026 | 27107.8 | 40.00 | 20.98 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 29221.12 | -4.20 | 0.00269032 | -4.20 | 0.20572670 | 20.1477 | 21.11 | 0.00646786 | 21.10 | 0.00646786 | 41.0545 | 13134.55 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_10:10 | SMSTORE8 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 17115.560 | 0.000 | 1.020200 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.1857 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:10:00 | 17115.56 | 16240.30 | 1.0000 | 1.21096800 | 1.020200 | 24.95 | 16.81 | 0.00879298 | 47468.5 | 12.80 | 11.97 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 17115.56 | 29.14 | 0.00879438 | 18.22 | 0.20572670 | 20.1653 | 23.89 | 0.00879263 | 23.89 | 0.00879239 | 46.9458 | 11405.77 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_10:10_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_10:10 | SMSTORE8 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 29201.400 | 29201.400 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.020205 | 1.21097362 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 29201.40 | 29201.40 | 1.0000 | 1.21097362 | 1.020205 | 14.28 | 9.44 | 0.00548517 | 28208.7 | 40.00 | 20.98 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 29201.40 | -4.20 | 0.00269032 | -4.20 | 0.20572670 | 20.1652 | 21.11 | 0.00651828 | 21.10 | 0.00651828 | 41.3722 | 14527.49 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2020-06-03 19:18:58
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-AC_1:1_OA_CONTROLLER | DifferentialDryBulb | 0.41 | 2.07 | - | |||
PSZ-AC_2:2_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.14 | - | |||
PSZ-AC_3:3_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.14 | - | |||
PSZ-AC_4:4_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.15 | - | |||
PSZ-AC_5:5_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.14 | - | |||
PSZ-AC_6:6_OA_CONTROLLER | DifferentialDryBulb | 0.41 | 2.00 | - | |||
PSZ-AC_7:7_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.04 | - | |||
PSZ-AC_8:8_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.03 | - | |||
PSZ-AC_9:9_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.02 | - | |||
PSZ-AC_10:10_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.02 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
LGSTORE1 | 1754.17 | 3346.83 | 174.00 |
SMSTORE1 | 1748.00 | 2952.83 | 35.67 |
SMSTORE2 | 1394.00 | 2393.33 | 70.50 |
SMSTORE3 | 1394.67 | 2447.50 | 102.67 |
SMSTORE4 | 1360.33 | 2555.67 | 141.83 |
LGSTORE2 | 1185.33 | 2546.17 | 262.50 |
SMSTORE5 | 1094.67 | 2608.00 | 282.67 |
SMSTORE6 | 1089.00 | 2648.50 | 307.17 |
SMSTORE7 | 1119.17 | 2730.00 | 398.00 |
SMSTORE8 | 1354.00 | 2948.00 | 781.83 |
Facility | 2749.17 | 4091.00 | 911.33 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
LGSTORE1 | 1.33 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 0.00 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 0.50 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 0.50 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 0.67 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 1.67 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 11.00 | 0.00 | 0.00 | 0.00 |
Facility | 12.33 | 0.00 | 0.00 | 0.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2020-06-03 19:18:58
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
LGSTORE1 | 9.03 | 30.00 | 1805.20 | 1.265 | 0.379 | 0.000 | 0.000 |
SMSTORE1 | 4.51 | 15.00 | 902.60 | 1.254 | 0.412 | 0.000 | 0.000 |
SMSTORE2 | 3.78 | 15.00 | 902.60 | 1.342 | 0.536 | 0.000 | 0.000 |
SMSTORE3 | 3.78 | 15.00 | 902.60 | 1.335 | 0.536 | 0.000 | 0.000 |
SMSTORE4 | 3.78 | 15.00 | 902.60 | 1.307 | 0.536 | 0.000 | 0.000 |
LGSTORE2 | 13.22 | 30.00 | 1805.20 | 1.217 | 0.502 | 0.000 | 0.000 |
SMSTORE5 | 6.61 | 15.00 | 902.60 | 1.227 | 0.570 | 0.000 | 0.000 |
SMSTORE6 | 6.61 | 15.00 | 902.60 | 1.213 | 0.570 | 0.000 | 0.000 |
SMSTORE7 | 6.61 | 15.00 | 902.60 | 1.186 | 0.570 | 0.000 | 0.000 |
SMSTORE8 | 6.61 | 15.00 | 902.60 | 1.137 | 0.603 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
LGSTORE1 | 9.03 | 30.00 | 1805.20 | 0.000 | 0.000 | 0.000 | 0.000 |
SMSTORE1 | 4.51 | 15.00 | 902.60 | 0.000 | 0.000 | 0.000 | 0.000 |
SMSTORE2 | 3.78 | 15.00 | 902.60 | 0.807 | 0.000 | 0.000 | 0.000 |
SMSTORE3 | 3.78 | 15.00 | 902.60 | 0.807 | 0.000 | 0.000 | 0.000 |
SMSTORE4 | 3.78 | 15.00 | 902.60 | 0.807 | 0.000 | 0.000 | 0.000 |
LGSTORE2 | 13.22 | 30.00 | 1805.20 | 0.808 | 0.000 | 0.000 | 0.000 |
SMSTORE5 | 6.61 | 15.00 | 902.60 | 0.808 | 0.000 | 0.000 | 0.000 |
SMSTORE6 | 6.61 | 15.00 | 902.60 | 0.808 | 0.000 | 0.000 | 0.000 |
SMSTORE7 | 6.61 | 15.00 | 902.60 | 0.808 | 0.000 | 0.000 | 0.000 |
SMSTORE8 | 6.61 | 15.00 | 902.60 | 0.808 | 0.000 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2020-06-03 19:18:58
Surfaces by ClassTotal | Outdoors | |
Wall | 40 | 22 |
Floor | 10 | 10 |
Roof | 10 | 10 |
Internal Mass | 10 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 36 | 36 |
Door | 12 | 12 |
Glass Door | 12 | 12 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 10 |
Conditioned Zones | 10 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 0 |
Defaulted Fields | 0 |
Fields with Defaults | 0 |
Autosized Fields | 0 |
Autosizable Fields | 0 |
Autocalculated Fields | 0 |
Autocalculatable Fields | 0 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2020-06-03 19:18:58
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1300.41 | 3973.34 | 15-JAN-08:00 | 112644.66 | 29-AUG-13:40 |
Electricity:Building | 832.89 | 2755.34 | 01-JAN-00:10 | 51902.14 | 01-JAN-11:10 |
Electricity:Zone:LGSTORE1 | 186.96 | 509.76 | 01-JAN-00:10 | 9610.45 | 01-JAN-10:10 |
InteriorLights:Electricity | 704.17 | 2305.93 | 01-JAN-00:10 | 43812.60 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:LGSTORE1 | 160.61 | 434.85 | 01-JAN-00:10 | 8262.19 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity | 704.17 | 2305.93 | 01-JAN-00:10 | 43812.60 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE1 | 102.73 | 279.91 | 01-JAN-00:10 | 5280.82 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE1 | 89.55 | 242.46 | 01-JAN-00:10 | 4606.69 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE2 | 75.94 | 261.16 | 01-JAN-00:10 | 4924.57 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE2 | 65.47 | 223.71 | 01-JAN-00:10 | 4250.44 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE3 | 75.94 | 261.16 | 01-JAN-00:10 | 4924.57 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE3 | 65.47 | 223.71 | 01-JAN-00:10 | 4250.44 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE4 | 75.94 | 261.16 | 01-JAN-00:10 | 4924.57 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE4 | 65.47 | 223.71 | 01-JAN-00:10 | 4250.44 | 01-JAN-10:10 |
Electricity:Zone:LGSTORE2 | 105.13 | 394.07 | 01-JAN-00:10 | 7412.39 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:LGSTORE2 | 85.86 | 319.16 | 01-JAN-00:10 | 6064.13 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE5 | 52.56 | 197.03 | 01-JAN-00:10 | 3706.19 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE5 | 42.93 | 159.58 | 01-JAN-00:10 | 3032.07 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE6 | 52.56 | 197.03 | 01-JAN-00:10 | 3706.19 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE6 | 42.93 | 159.58 | 01-JAN-00:10 | 3032.07 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE7 | 52.56 | 197.03 | 01-JAN-00:10 | 3706.19 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE7 | 42.93 | 159.58 | 01-JAN-00:10 | 3032.07 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE8 | 52.56 | 197.03 | 01-JAN-00:10 | 3706.19 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE8 | 42.93 | 159.58 | 01-JAN-00:10 | 3032.07 | 01-JAN-11:10 |
InteriorEquipment:Electricity | 128.72 | 449.42 | 01-JAN-00:10 | 8089.53 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:LGSTORE1 | 26.36 | 74.90 | 01-JAN-00:10 | 1348.26 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity | 128.72 | 449.42 | 01-JAN-00:10 | 8089.53 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE1 | 13.18 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE2 | 10.47 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE3 | 10.47 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE4 | 10.47 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:LGSTORE2 | 19.26 | 74.90 | 01-JAN-00:10 | 1348.26 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE5 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE6 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE7 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE8 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
Electricity:Plant | 64.37 | 1218.00 | 08-JAN-08:10 | 11860.52 | 04-JAN-13:30 |
WaterSystems:Electricity | 64.37 | 1218.00 | 08-JAN-08:10 | 11860.52 | 04-JAN-13:30 |
Water Heater:WaterSystems:Electricity | 64.37 | 1218.00 | 08-JAN-08:10 | 11860.52 | 04-JAN-13:30 |
ElectricityPurchased:Facility | 1300.41 | 3973.34 | 15-JAN-08:00 | 112644.66 | 29-AUG-13:40 |
ElectricityPurchased:Plant | 1300.41 | 3973.34 | 15-JAN-08:00 | 112644.66 | 29-AUG-13:40 |
Cogeneration:ElectricityPurchased | 1300.41 | 3973.34 | 15-JAN-08:00 | 112644.66 | 29-AUG-13:40 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1300.41 | 3973.34 | 15-JAN-08:00 | 112644.66 | 29-AUG-13:40 |
ElectricityNet:Plant | 1300.41 | 3973.34 | 15-JAN-08:00 | 112644.66 | 29-AUG-13:40 |
Cogeneration:ElectricityNet | 1300.41 | 3973.34 | 15-JAN-08:00 | 112644.66 | 29-AUG-13:40 |
Electricity:HVAC | 292.61 | 0.00 | 01-JAN-00:10 | 55149.79 | 29-AUG-15:00 |
Fans:Electricity | 248.21 | 0.00 | 01-JAN-00:10 | 14352.07 | 01-JAN-13:30 |
General:Fans:Electricity | 248.21 | 0.00 | 01-JAN-00:10 | 14352.07 | 01-JAN-13:30 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 44.40 | 0.00 | 01-JAN-00:10 | 40797.72 | 29-AUG-15:00 |
ExteriorLights:Electricity | 110.54 | 0.00 | 01-JAN-08:10 | 7048.38 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 110.54 | 0.00 | 01-JAN-08:10 | 7048.38 | 01-JAN-00:10 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Gas:Facility | 283.10 | 0.00 | 01-JAN-00:10 | 152633.90 | 19-FEB-09:10 |
Gas:HVAC | 283.10 | 0.00 | 01-JAN-00:10 | 152633.90 | 19-FEB-09:10 |
Heating:Gas | 283.10 | 0.00 | 01-JAN-00:10 | 152633.90 | 19-FEB-09:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water:Plant | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
WaterSystems:Water | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water Heater:WaterSystems:Water | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
MainsWater:Facility | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
MainsWater:Plant | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
WaterSystems:MainsWater | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water Heater:WaterSystems:MainsWater | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:Facility | 832.64 | 0.00 | 01-JAN-00:10 | 240556.08 | 29-AUG-15:00 |
EnergyTransfer:Building | 445.27 | 0.00 | 01-JAN-00:10 | 104312.06 | 26-DEC-08:10 |
EnergyTransfer:Zone:LGSTORE1 | 96.89 | 0.00 | 01-JAN-00:10 | 22301.16 | 19-FEB-08:10 |
Heating:EnergyTransfer | 102.14 | 0.00 | 01-JAN-00:10 | 104312.06 | 26-DEC-08:10 |
Heating:EnergyTransfer:Zone:LGSTORE1 | 11.29 | 0.00 | 01-JAN-00:10 | 22301.16 | 19-FEB-08:10 |
Cooling:EnergyTransfer | 343.13 | 0.00 | 01-JAN-00:10 | 98407.88 | 10-AUG-16:40 |
Cooling:EnergyTransfer:Zone:LGSTORE1 | 85.60 | 0.00 | 01-JAN-00:10 | 16905.77 | 10-AUG-17:00 |
EnergyTransfer:Zone:SMSTORE1 | 52.23 | 0.00 | 01-JAN-00:10 | 11431.24 | 06-JUL-20:20 |
Heating:EnergyTransfer:Zone:SMSTORE1 | 3.50 | 0.00 | 01-JAN-00:10 | 7668.22 | 19-FEB-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE1 | 48.73 | 0.00 | 01-JAN-00:10 | 11431.24 | 06-JUL-20:20 |
EnergyTransfer:Zone:SMSTORE2 | 38.27 | 0.00 | 01-JAN-00:10 | 9727.17 | 19-FEB-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE2 | 5.23 | 0.00 | 01-JAN-00:10 | 9727.17 | 19-FEB-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE2 | 33.05 | 0.00 | 01-JAN-00:10 | 8919.06 | 10-AUG-16:40 |
EnergyTransfer:Zone:SMSTORE3 | 37.85 | 0.00 | 01-JAN-00:10 | 10686.76 | 19-FEB-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE3 | 6.03 | 0.00 | 01-JAN-00:10 | 10686.76 | 19-FEB-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE3 | 31.82 | 0.00 | 01-JAN-00:10 | 8918.20 | 10-AUG-16:40 |
EnergyTransfer:Zone:SMSTORE4 | 36.45 | 0.00 | 01-JAN-00:10 | 11536.60 | 19-FEB-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE4 | 7.08 | 0.00 | 01-JAN-00:10 | 11536.60 | 19-FEB-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE4 | 29.37 | 0.00 | 01-JAN-00:10 | 8775.39 | 10-AUG-16:40 |
EnergyTransfer:Zone:LGSTORE2 | 59.44 | 0.00 | 01-JAN-00:10 | 24858.14 | 16-JAN-09:10 |
Heating:EnergyTransfer:Zone:LGSTORE2 | 16.57 | 0.00 | 01-JAN-00:10 | 24858.14 | 16-JAN-09:10 |
Cooling:EnergyTransfer:Zone:LGSTORE2 | 42.87 | 0.00 | 01-JAN-00:10 | 14961.88 | 10-AUG-16:40 |
EnergyTransfer:Zone:SMSTORE5 | 30.64 | 0.00 | 01-JAN-00:10 | 13163.50 | 16-JAN-09:10 |
Heating:EnergyTransfer:Zone:SMSTORE5 | 10.17 | 0.00 | 01-JAN-00:10 | 13163.50 | 16-JAN-09:10 |
Cooling:EnergyTransfer:Zone:SMSTORE5 | 20.46 | 0.00 | 01-JAN-00:10 | 7851.19 | 10-AUG-16:40 |
EnergyTransfer:Zone:SMSTORE6 | 30.26 | 0.00 | 01-JAN-00:10 | 13456.06 | 16-JAN-09:10 |
Heating:EnergyTransfer:Zone:SMSTORE6 | 10.61 | 0.00 | 01-JAN-00:10 | 13456.06 | 16-JAN-09:10 |
Cooling:EnergyTransfer:Zone:SMSTORE6 | 19.65 | 0.00 | 01-JAN-00:10 | 7780.98 | 10-AUG-16:40 |
EnergyTransfer:Zone:SMSTORE7 | 29.97 | 0.00 | 01-JAN-00:10 | 14512.17 | 16-JAN-09:10 |
Heating:EnergyTransfer:Zone:SMSTORE7 | 12.23 | 0.00 | 01-JAN-00:10 | 14512.17 | 16-JAN-09:10 |
Cooling:EnergyTransfer:Zone:SMSTORE7 | 17.73 | 0.00 | 01-JAN-00:10 | 7681.17 | 10-AUG-16:40 |
EnergyTransfer:Zone:SMSTORE8 | 33.27 | 0.00 | 01-JAN-00:10 | 16853.36 | 26-DEC-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE8 | 19.42 | 0.00 | 01-JAN-00:10 | 16853.36 | 26-DEC-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE8 | 13.85 | 0.00 | 01-JAN-00:10 | 7647.13 | 10-AUG-16:40 |
EnergyTransfer:HVAC | 387.38 | 0.00 | 01-JAN-00:10 | 146505.85 | 29-AUG-14:40 |
HeatingCoils:EnergyTransfer | 226.48 | 0.00 | 01-JAN-00:10 | 122107.12 | 19-FEB-09:10 |
CoolingCoils:EnergyTransfer | 160.90 | 0.00 | 01-JAN-00:10 | 146505.85 | 29-AUG-14:40 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2020-06-03 19:18:58
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
LGSTORE1 | 0.000 | 0.000 | 11.292 | -85.602 | 0.000 | 0.000 | 13.343 | 160.608 | 26.357 | 15.855 | 0.000 | 0.738 | 0.001 | 0.000 | -12.827 | 0.000 | -54.260 | -75.504 |
SMSTORE1 | 0.000 | 0.000 | 3.503 | -48.729 | 0.000 | 0.000 | 6.545 | 89.549 | 13.179 | 7.826 | 0.000 | 0.410 | 0.002 | 0.000 | -6.781 | 0.000 | -27.419 | -38.083 |
SMSTORE2 | 0.000 | 0.000 | 5.226 | -33.045 | 0.000 | 0.000 | 4.002 | 65.475 | 10.467 | 7.834 | 0.000 | 0.399 | 0.001 | 0.000 | -6.618 | 0.000 | -28.133 | -25.607 |
SMSTORE3 | 0.000 | 0.000 | 6.026 | -31.819 | 0.000 | 0.000 | 4.011 | 65.475 | 10.467 | 7.854 | 0.000 | 0.399 | 0.000 | 0.000 | -6.518 | 0.000 | -27.950 | -27.944 |
SMSTORE4 | 0.000 | 0.000 | 7.081 | -29.365 | 0.000 | 0.000 | 4.026 | 65.475 | 10.467 | 7.886 | 0.000 | 0.399 | 0.001 | 0.000 | -6.413 | 0.000 | -27.707 | -31.850 |
LGSTORE2 | 0.000 | 0.000 | 16.574 | -42.871 | 0.000 | 0.000 | 13.935 | 85.864 | 19.261 | 15.954 | 0.000 | 0.701 | 0.004 | 0.000 | -12.253 | 0.000 | -49.246 | -47.920 |
SMSTORE5 | 0.000 | 0.000 | 10.174 | -20.465 | 0.000 | 0.000 | 6.979 | 42.932 | 9.631 | 7.979 | 0.000 | 0.399 | 0.000 | 0.000 | -6.113 | 0.000 | -27.281 | -24.236 |
SMSTORE6 | 0.000 | 0.000 | 10.614 | -19.647 | 0.000 | 0.000 | 6.989 | 42.932 | 9.631 | 7.995 | 0.000 | 0.399 | 0.003 | 0.000 | -6.069 | 0.000 | -27.187 | -25.656 |
SMSTORE7 | 0.000 | 0.000 | 12.232 | -17.734 | 0.000 | 0.000 | 7.010 | 42.932 | 9.631 | 8.033 | 0.000 | 0.399 | 0.001 | 0.000 | -5.950 | 0.000 | -26.953 | -29.599 |
SMSTORE8 | 0.000 | 0.000 | 19.419 | -13.846 | 0.000 | 0.000 | 7.055 | 42.932 | 9.631 | 8.145 | 0.000 | 0.417 | 0.004 | 0.000 | -5.518 | 0.000 | -33.276 | -34.961 |
Total Facility | 0.000 | 0.000 | 102.141 | -343.124 | 0.000 | 0.000 | 73.896 | 704.173 | 128.721 | 95.363 | 0.000 | 4.660 | 0.017 | 0.000 | -75.060 | 0.000 | -329.412 | -361.359 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
LGSTORE1 | 24-JUL-07:03 | 0.00 | 0.00 | 0.00 | -28507.23 | 0.00 | 0.00 | 96.81 | 434.85 | 74.90 | 104.94 | 0.00 | 0.00 | 28117.55 | 0.00 | -0.00 | 0.00 | -321.82 | 0.00 |
SMSTORE1 | 03-OCT-20:07 | 0.00 | 0.00 | 0.00 | -24223.84 | 0.00 | 0.00 | 315.18 | 4606.69 | 674.13 | 0.00 | 0.00 | 0.00 | 19011.80 | 0.00 | -286.40 | 0.00 | -97.56 | 0.00 |
SMSTORE2 | 01-AUG-06:01 | 0.00 | 0.00 | 0.00 | -21755.06 | 0.00 | 0.00 | 0.00 | 223.71 | 37.45 | 0.00 | 0.00 | 0.00 | 21744.94 | 0.00 | -183.44 | 0.00 | -67.60 | 0.00 |
SMSTORE3 | 01-AUG-06:01 | 0.00 | 0.00 | 0.00 | -21836.25 | 0.00 | 0.00 | 0.00 | 223.71 | 37.45 | 0.00 | 0.00 | 0.00 | 21826.74 | 0.00 | -183.97 | 0.00 | -67.69 | 0.00 |
SMSTORE4 | 14-SEP-06:01 | 0.00 | 0.00 | 0.00 | -20984.18 | 0.00 | 0.00 | 0.00 | 223.71 | 37.45 | 0.00 | 0.00 | 0.00 | 21009.28 | 0.00 | -286.25 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 14-AUG-07:02 | 0.00 | 0.00 | 0.00 | -31960.31 | 0.00 | 0.00 | 0.00 | 319.16 | 74.90 | 5.83 | 0.00 | 0.00 | 32108.05 | 0.00 | -0.00 | 0.00 | -547.63 | 0.00 |
SMSTORE5 | 14-AUG-07:02 | 0.00 | 0.00 | 0.00 | -16434.61 | 0.00 | 0.00 | 0.00 | 159.58 | 37.45 | 4.22 | 0.00 | 0.00 | 16538.07 | 0.00 | -0.00 | 0.00 | -304.71 | 0.00 |
SMSTORE6 | 14-AUG-07:02 | 0.00 | 0.00 | 0.00 | -16164.91 | 0.00 | 0.00 | 0.00 | 159.58 | 37.45 | 5.78 | 0.00 | 0.00 | 16264.73 | 0.00 | -0.00 | 0.00 | -302.63 | 0.00 |
SMSTORE7 | 14-AUG-07:02 | 0.00 | 0.00 | 0.00 | -13140.54 | 0.00 | 0.00 | 0.00 | 159.58 | 37.45 | 9.97 | 0.00 | 0.00 | 13235.66 | 0.00 | -0.00 | 0.00 | -302.12 | 0.00 |
SMSTORE8 | 10-AUG-16:40 | 0.00 | 0.00 | 0.00 | -7646.83 | 0.00 | 0.00 | 745.94 | 3032.07 | 674.13 | 404.15 | 0.00 | 2022.70 | 767.84 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 14-AUG-07:02 | 0.00 | 0.00 | 0.00 | -130645.81 | 0.00 | 0.00 | 304.81 | 8346.03 | 1460.61 | 129.51 | 0.00 | 0.00 | 123997.74 | 0.00 | 0.00 | 0.00 | -3592.88 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
LGSTORE1 | 06-JAN-08:61 | 0.00 | 0.00 | 59348.14 | 0.00 | 0.00 | 0.00 | 0.00 | 434.85 | 74.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -653.53 | 0.00 | -1637.93 | -57566.43 |
SMSTORE1 | 06-JAN-08:61 | 0.00 | 0.00 | 32016.86 | 0.00 | 0.00 | 0.00 | 0.00 | 242.46 | 37.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -351.74 | 0.00 | -984.20 | -30960.83 |
SMSTORE2 | 19-FEB-08:61 | 0.00 | 0.00 | 31991.85 | 0.00 | 0.00 | 0.00 | 0.00 | 223.71 | 37.45 | 111.22 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -1193.96 | -31170.28 |
SMSTORE3 | 19-FEB-08:61 | 0.00 | 0.00 | 32065.97 | 0.00 | 0.00 | 0.00 | 0.00 | 223.71 | 37.45 | 119.45 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -1177.58 | -31269.00 |
SMSTORE4 | 19-FEB-08:61 | 0.00 | 0.00 | 31879.80 | 0.00 | 0.00 | 0.00 | 0.00 | 223.71 | 37.45 | 126.07 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -1163.12 | -31103.91 |
LGSTORE2 | 17-JAN-08:61 | 0.00 | 0.00 | 57745.44 | 0.00 | 0.00 | 0.00 | 0.00 | 319.16 | 74.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -645.37 | 0.00 | -1312.32 | -56181.81 |
SMSTORE5 | 07-JAN-08:61 | 0.00 | 0.00 | 29730.37 | 0.00 | 0.00 | 0.00 | 0.00 | 159.58 | 37.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -445.40 | 0.00 | -1053.76 | -28428.24 |
SMSTORE6 | 07-JAN-08:61 | 0.00 | 0.00 | 29562.68 | 0.00 | 0.00 | 0.00 | 0.00 | 159.58 | 37.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -443.28 | 0.00 | -1049.69 | -28266.74 |
SMSTORE7 | 06-JAN-08:61 | 0.00 | 0.00 | 29375.07 | 0.00 | 0.00 | 0.00 | 0.00 | 159.58 | 37.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -304.28 | 0.00 | -897.71 | -28370.12 |
SMSTORE8 | 19-FEB-09:12 | 0.00 | 0.00 | 29523.23 | 0.00 | 0.00 | 0.00 | 0.00 | 159.58 | 37.45 | 1498.32 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -1504.28 | -29714.31 |
Total Facility | 26-DEC-08:61 | 0.00 | 0.00 | 276565.93 | 0.00 | 0.00 | 0.00 | 387.07 | 8346.03 | 1460.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -5487.78 | 0.00 | -11321.69 | -269950.16 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2020-06-03 19:18:58
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 2.0742 | 0.0000 | 29.9961 | 1.0000 | 0.4115 | 2.0742 | 0.1984 | 1.0000 | 0.4115 | 0.1984 | ||
PSZ-AC_2:2 | 1.1425 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.1425 | 0.1801 | 1.0000 | 0.2057 | 0.1801 | ||
PSZ-AC_3:3 | 1.1423 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.1423 | 0.1801 | 1.0000 | 0.2057 | 0.1801 | ||
PSZ-AC_4:4 | 1.1457 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.1457 | 0.1796 | 1.0000 | 0.2057 | 0.1796 | ||
PSZ-AC_5:5 | 1.1371 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.1371 | 0.1809 | 1.0000 | 0.2057 | 0.1809 | ||
PSZ-AC_6:6 | 2.0012 | 0.0000 | 29.9961 | 1.0000 | 0.4115 | 2.0012 | 0.2056 | 1.0000 | 0.4115 | 0.2056 | ||
PSZ-AC_7:7 | 1.0374 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.0374 | 0.1983 | 1.0000 | 0.2057 | 0.1983 | ||
PSZ-AC_8:8 | 1.0298 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.0298 | 0.1998 | 1.0000 | 0.2057 | 0.1998 | ||
PSZ-AC_9:9 | 1.0211 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.0211 | 0.2015 | 1.0000 | 0.2057 | 0.2015 | ||
PSZ-AC_10:10 | 1.0202 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.0202 | 0.2017 | 1.0000 | 0.2057 | 0.2017 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 2.0742 | 0.0000 | 29.9961 | 1.0000 | 0.4115 | 2.0742 | 1.0000 | 1.0000 | 0.4115 | 0.1984 | ||
PSZ-AC_2:2 | 1.1425 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.1425 | 1.0000 | 1.0000 | 0.2057 | 0.1801 | ||
PSZ-AC_3:3 | 1.1423 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.1423 | 1.0000 | 1.0000 | 0.2057 | 0.1801 | ||
PSZ-AC_4:4 | 1.1457 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.1457 | 1.0000 | 1.0000 | 0.2057 | 0.1796 | ||
PSZ-AC_5:5 | 1.1371 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.1371 | 1.0000 | 1.0000 | 0.2057 | 0.1809 | ||
PSZ-AC_6:6 | 2.0012 | 0.0000 | 29.9961 | 1.0000 | 0.4115 | 2.0012 | 1.0000 | 1.0000 | 0.4115 | 0.2056 | ||
PSZ-AC_7:7 | 1.0374 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.0374 | 1.0000 | 1.0000 | 0.2057 | 0.1983 | ||
PSZ-AC_8:8 | 1.0298 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.0298 | 1.0000 | 1.0000 | 0.2057 | 0.1998 | ||
PSZ-AC_9:9 | 1.0211 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.0211 | 1.0000 | 1.0000 | 0.2057 | 0.2015 | ||
PSZ-AC_10:10 | 1.0202 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.0202 | 1.0000 | 1.0000 | 0.2057 | 0.2017 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
LGSTORE1 | PSZ-AC_1:1 | 0.000000 | 29.9961 | 0.001181 | 348.39 | 0.4115 | 1.0000 | 0.4115 | 1.000 | 0.4115 |
SMSTORE1 | PSZ-AC_2:2 | 0.000000 | 14.9980 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE2 | PSZ-AC_3:3 | 0.000000 | 14.9980 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE3 | PSZ-AC_4:4 | 0.000000 | 14.9980 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE4 | PSZ-AC_5:5 | 0.000000 | 14.9980 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
LGSTORE2 | PSZ-AC_6:6 | 0.000000 | 29.9961 | 0.001181 | 348.39 | 0.4115 | 1.0000 | 0.4115 | 1.000 | 0.4115 |
SMSTORE5 | PSZ-AC_7:7 | 0.000000 | 14.9980 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE6 | PSZ-AC_8:8 | 0.000000 | 14.9980 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE7 | PSZ-AC_9:9 | 0.000000 | 14.9980 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE8 | PSZ-AC_10:10 | 0.000000 | 14.9980 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC_1:1 | 0.000000 | 30.00 | 0.001181 | 348.3864 | 0.4115 | 0.4115 | 0.4115 |
PSZ-AC_2:2 | 0.000000 | 15.00 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_3:3 | 0.000000 | 15.00 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_4:4 | 0.000000 | 15.00 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_5:5 | 0.000000 | 15.00 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_6:6 | 0.000000 | 30.00 | 0.001181 | 348.3864 | 0.4115 | 0.4115 | 0.4115 |
PSZ-AC_7:7 | 0.000000 | 15.00 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_8:8 | 0.000000 | 15.00 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_9:9 | 0.000000 | 15.00 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_10:10 | 0.000000 | 15.00 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LGSTORE1 | PSZ-AC_1:1 | 2.0742 | 2.0742 | 2.0742 | 0.4115 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE1 | PSZ-AC_2:2 | 1.1425 | 1.1425 | 1.1425 | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE2 | PSZ-AC_3:3 | 1.1423 | 1.1423 | 1.1423 | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE3 | PSZ-AC_4:4 | 1.1457 | 1.1457 | 1.1457 | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE4 | PSZ-AC_5:5 | 1.1371 | 1.1371 | 1.1371 | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
LGSTORE2 | PSZ-AC_6:6 | 2.0012 | 2.0012 | 2.0012 | 0.4115 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE5 | PSZ-AC_7:7 | 1.0374 | 1.0374 | 1.0374 | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE6 | PSZ-AC_8:8 | 1.0298 | 1.0298 | 1.0298 | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE7 | PSZ-AC_9:9 | 1.0211 | 1.0211 | 1.0211 | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE8 | PSZ-AC_10:10 | 1.0202 | 1.0202 | 1.0202 | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 2.0742 | 2.0742 | 2.0742 | 2.0742 | 0.4115 | 1.0000 |
PSZ-AC_2:2 | 1.1425 | 1.1425 | 1.1425 | 1.1425 | 0.2057 | 1.0000 |
PSZ-AC_3:3 | 1.1423 | 1.1423 | 1.1423 | 1.1423 | 0.2057 | 1.0000 |
PSZ-AC_4:4 | 1.1457 | 1.1457 | 1.1457 | 1.1457 | 0.2057 | 1.0000 |
PSZ-AC_5:5 | 1.1371 | 1.1371 | 1.1371 | 1.1371 | 0.2057 | 1.0000 |
PSZ-AC_6:6 | 2.0012 | 2.0012 | 2.0012 | 2.0012 | 0.4115 | 1.0000 |
PSZ-AC_7:7 | 1.0374 | 1.0374 | 1.0374 | 1.0374 | 0.2057 | 1.0000 |
PSZ-AC_8:8 | 1.0298 | 1.0298 | 1.0298 | 1.0298 | 0.2057 | 1.0000 |
PSZ-AC_9:9 | 1.0211 | 1.0211 | 1.0211 | 1.0211 | 0.2057 | 1.0000 |
PSZ-AC_10:10 | 1.0202 | 1.0202 | 1.0202 | 1.0202 | 0.2057 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LGSTORE1 | PSZ-AC_1:1 | 2.0742 | 2.0742 | 2.0742 | 0.4115 | 0.3277 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE1 | PSZ-AC_2:2 | 1.1425 | 1.1425 | 1.1425 | 0.2057 | 0.3213 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE2 | PSZ-AC_3:3 | 1.1423 | 1.1423 | 1.1423 | 0.2057 | 0.3163 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE3 | PSZ-AC_4:4 | 1.1457 | 1.1457 | 1.1457 | 0.2057 | 0.3135 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE4 | PSZ-AC_5:5 | 1.1371 | 1.1371 | 1.1371 | 0.2057 | 0.3094 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
LGSTORE2 | PSZ-AC_6:6 | 2.0012 | 2.0012 | 2.0012 | 0.4115 | 0.3295 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE5 | PSZ-AC_7:7 | 1.0374 | 1.0374 | 1.0374 | 0.2057 | 0.3020 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE6 | PSZ-AC_8:8 | 1.0298 | 1.0298 | 1.0298 | 0.2057 | 0.3023 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE7 | PSZ-AC_9:9 | 1.0211 | 1.0211 | 1.0211 | 0.2057 | 0.2985 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE8 | PSZ-AC_10:10 | 1.0202 | 1.0202 | 1.0202 | 0.2057 | 0.2699 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 2.0742 | 2.0742 | 2.0742 | 2.0742 | 0.4115 | 1.0000 |
PSZ-AC_2:2 | 1.1425 | 1.1425 | 1.1425 | 1.1425 | 0.2057 | 1.0000 |
PSZ-AC_3:3 | 1.1423 | 1.1423 | 1.1423 | 1.1423 | 0.2057 | 1.0000 |
PSZ-AC_4:4 | 1.1457 | 1.1457 | 1.1457 | 1.1457 | 0.2057 | 1.0000 |
PSZ-AC_5:5 | 1.1371 | 1.1371 | 1.1371 | 1.1371 | 0.2057 | 1.0000 |
PSZ-AC_6:6 | 2.0012 | 2.0012 | 2.0012 | 2.0012 | 0.4115 | 1.0000 |
PSZ-AC_7:7 | 1.0374 | 1.0374 | 1.0374 | 1.0374 | 0.2057 | 1.0000 |
PSZ-AC_8:8 | 1.0298 | 1.0298 | 1.0298 | 1.0298 | 0.2057 | 1.0000 |
PSZ-AC_9:9 | 1.0211 | 1.0211 | 1.0211 | 1.0211 | 0.2057 | 1.0000 |
PSZ-AC_10:10 | 1.0202 | 1.0202 | 1.0202 | 1.0202 | 0.2057 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2020-06-03 19:18:58
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930 |
Total gross floor area [m2] | 2090.32 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
LGSTORE1 | 348.39 | 348.39 | 0.00 | 112.00 |
SMSTORE1 | 174.19 | 174.19 | 0.00 | 112.00 |
SMSTORE2 | 174.19 | 174.19 | 0.00 | 84.29 |
SMSTORE3 | 174.19 | 174.19 | 0.00 | 84.29 |
SMSTORE4 | 174.19 | 174.19 | 0.00 | 84.29 |
LGSTORE2 | 348.39 | 348.39 | 0.00 | 77.29 |
SMSTORE5 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE6 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE7 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE8 | 174.19 | 174.19 | 0.00 | 77.29 |
Totals | 2090.32 | 2090.32 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 0.00 |
Number of hours not met | 0.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Fuel Use [GJ] | Additional Fuel Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- Not Subdivided | 0.00 | 0.00 | 283.10 | 152633.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- Not Subdivided | 44.40 | 40797.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 704.17 | 43812.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 110.54 | 7048.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 128.72 | 8089.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 248.21 | 14352.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 64.37 | 11860.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 128.72 | 1300.41 |
Natural Gas | 0.00 | 283.10 |
Additional | 0.00 | 0.00 |
Total | 128.72 | 1583.51 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 336.87 |
Space Heating | 0.00 |
Space Cooling | 21.24 |
Fans (All) | 118.74 |
Service Water Heating | 30.79 |
Receptacle Equipment | 61.58 |
Miscellaneous (All) | 622.11 |
Subtotal | 622.11 |
Natural Gas [MJ/m2] | |
Space Heating | 135.43 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 135.43 |
Subtotal | 135.43 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 44.47 |
Space Heating | 17.88 |
Space Cooling | 2.80 |
Fans (All) | 15.67 |
Service Water Heating | 4.06 |
Receptacle Equipment | 8.13 |
Miscellaneous | 6.98 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
TYPE1_OCC_SCH | 1630. | 5840. |
TYPE2_OCC_SCH | 995. | 4429. |
TYPE3_OCC_SCH | 1709. | 4064. |
TYPE1_LIGHT_SCH | 5131. | 8760. |
TYPE2_LIGHT_SCH | 4096. | 8760. |
TYPE3_LIGHT_SCH | 3767. | 8760. |
TYPE1_EQUIP_SCH | 4888. | 8760. |
TYPE2_EQUIP_SCH | 3911. | 8760. |
TYPE3_EQUIP_SCH | 3600. | 8760. |
TYPE1_INFIL_SCH | 4302. | 8760. |
TYPE2_INFIL_SCH | 5164. | 8760. |
TYPE3_INFIL_SCH | 5438. | 8760. |
INFIL_DOOR_OPENING_SCH | 2505. | 4380. |
TYPE1_MINOA_MOTORIZEDDAMPER_SCH | 5579. | 5579. |
TYPE2_MINOA_MOTORIZEDDAMPER_SCH | 4429. | 4429. |
TYPE3_MINOA_MOTORIZEDDAMPER_SCH | 4064. | 4064. |
TYPE1_SWH_SCH | 2063. | 6048. |
TYPE2_SWH_SCH | 1831. | 4429. |
TYPE3_SWH_SCH | 1733. | 4064. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 7118. | 8760. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 5839. | 5839. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 7300. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
TYPE1_HTGSETP_SCH_NO_OPTIMUM | LGSTORE1 DUALSPSCHED | January | 21.11 | 365 | 21.11 | 365 |
TYPE1_CLGSETP_SCH_NO_OPTIMUM | LGSTORE1 DUALSPSCHED | July | 23.89 | 365 | 23.89 | 365 |
TYPE2_HTGSETP_SCH_NO_OPTIMUM | SMSTORE2 DUALSPSCHED | January | 21.11 | 365 | 15.56 | 365 |
TYPE2_CLGSETP_SCH_NO_OPTIMUM | SMSTORE2 DUALSPSCHED | July | 23.89 | 365 | 29.44 | 365 |
TYPE3_HTGSETP_SCH_NO_OPTIMUM | LGSTORE2 DUALSPSCHED | January | 21.11 | 365 | 15.56 | 365 |
TYPE3_CLGSETP_SCH_NO_OPTIMUM | LGSTORE2 DUALSPSCHED | July | 23.89 | 365 | 29.44 | 365 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Meter
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.842861E+11 |
February | 0.000 | 0.547525E+11 |
March | 0.000 | 0.242969E+11 |
April | 0.000 | 0.764459E+10 |
May | 0.000 | 0.830863E+09 |
June | 0.000 | 0.179770E+08 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.249889E+08 |
October | 0.000 | 0.397776E+10 |
November | 0.000 | 0.385385E+11 |
December | 0.000 | 0.687296E+11 |
Annual Sum or Average | 0.283100E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.842861E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Meter
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.842861E+11 |
February | 0.000 | 0.547525E+11 |
March | 0.000 | 0.242969E+11 |
April | 0.000 | 0.764459E+10 |
May | 0.000 | 0.830863E+09 |
June | 0.000 | 0.179770E+08 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.249889E+08 |
October | 0.000 | 0.397776E+10 |
November | 0.000 | 0.385385E+11 |
December | 0.000 | 0.687296E+11 |
Annual Sum or Average | 0.283100E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.842861E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2009
For: Meter
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.842861E+11 |
February | 0.000 | 0.547525E+11 |
March | 0.000 | 0.242969E+11 |
April | 0.000 | 0.764459E+10 |
May | 0.000 | 0.830863E+09 |
June | 0.000 | 0.179770E+08 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.249889E+08 |
October | 0.000 | 0.397776E+10 |
November | 0.000 | 0.385385E+11 |
December | 0.000 | 0.687296E+11 |
Annual Sum or Average | 0.283100E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.842861E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Meter
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.842861E+11 |
February | 0.000 | 0.547525E+11 |
March | 0.000 | 0.242969E+11 |
April | 0.000 | 0.764459E+10 |
May | 0.000 | 0.830863E+09 |
June | 0.000 | 0.179770E+08 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.249889E+08 |
October | 0.000 | 0.397776E+10 |
November | 0.000 | 0.385385E+11 |
December | 0.000 | 0.687296E+11 |
Annual Sum or Average | 0.283100E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.842861E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTRIPMALL
For: Meter
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.842861E+11 |
February | 0.000 | 0.547525E+11 |
March | 0.000 | 0.242969E+11 |
April | 0.000 | 0.764459E+10 |
May | 0.000 | 0.830863E+09 |
June | 0.000 | 0.179770E+08 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.249889E+08 |
October | 0.000 | 0.397776E+10 |
November | 0.000 | 0.385385E+11 |
December | 0.000 | 0.687296E+11 |
Annual Sum or Average | 0.283100E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.842861E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.842861E+11 |
February | 0.000 | 0.547525E+11 |
March | 0.000 | 0.242969E+11 |
April | 0.000 | 0.764459E+10 |
May | 0.000 | 0.830863E+09 |
June | 0.000 | 0.179770E+08 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.249889E+08 |
October | 0.000 | 0.397776E+10 |
November | 0.000 | 0.385385E+11 |
December | 0.000 | 0.687296E+11 |
Annual Sum or Average | 0.283100E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.842861E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.842861E+11 |
February | 0.000 | 0.547525E+11 |
March | 0.000 | 0.242969E+11 |
April | 0.000 | 0.764459E+10 |
May | 0.000 | 0.830863E+09 |
June | 0.000 | 0.179770E+08 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.249889E+08 |
October | 0.000 | 0.397776E+10 |
November | 0.000 | 0.385385E+11 |
December | 0.000 | 0.687296E+11 |
Annual Sum or Average | 0.283100E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.842861E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4C
For: Meter
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.842861E+11 |
February | 0.000 | 0.547525E+11 |
March | 0.000 | 0.242969E+11 |
April | 0.000 | 0.764459E+10 |
May | 0.000 | 0.830863E+09 |
June | 0.000 | 0.179770E+08 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.249889E+08 |
October | 0.000 | 0.397776E+10 |
November | 0.000 | 0.385385E+11 |
December | 0.000 | 0.687296E+11 |
Annual Sum or Average | 0.283100E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.842861E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_SEATTLE
For: Meter
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.842861E+11 |
February | 0.000 | 0.547525E+11 |
March | 0.000 | 0.242969E+11 |
April | 0.000 | 0.764459E+10 |
May | 0.000 | 0.830863E+09 |
June | 0.000 | 0.179770E+08 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.249889E+08 |
October | 0.000 | 0.397776E+10 |
November | 0.000 | 0.385385E+11 |
December | 0.000 | 0.687296E+11 |
Annual Sum or Average | 0.283100E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.842861E+11 |
Report: ZoneCoolingSummaryMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.215768E+10 | 8092.37 | 07-JAN-00:25 | -1.4 | -1.4 | 0.569517E+09 | 685.77 | 29-JAN-18:00 | 9.40 | 5.53 |
February | 0.263137E+10 | 7878.16 | 18-FEB-00:25 | -1.1 | -2.1 | 0.529180E+09 | 787.07 | 26-FEB-18:30 | 10.55 | 8.02 |
March | 0.448430E+10 | 6388.70 | 01-MAR-23:00 | 3.90 | 2.96 | 0.603955E+09 | 886.45 | 10-MAR-13:00 | 16.70 | 12.01 |
April | 0.601354E+10 | 11841.41 | 27-APR-15:00 | 27.20 | 17.27 | 0.651069E+09 | 899.02 | 29-APR-12:00 | 20.00 | 14.69 |
May | 0.816305E+10 | 11049.19 | 15-MAY-16:30 | 24.15 | 12.90 | 0.725541E+09 | 899.05 | 07-MAY-12:09 | 19.60 | 15.91 |
June | 0.101316E+11 | 12709.48 | 28-JUN-17:00 | 26.70 | 16.72 | 0.719020E+09 | 899.06 | 11-JUN-16:10 | 21.70 | 14.98 |
July | 0.134348E+11 | 28508.28 | 24-JUL-07:03 | 19.37 | 15.36 | 0.753391E+09 | 899.06 | 30-JUL-12:00 | 26.10 | 17.73 |
August | 0.142966E+11 | 27408.76 | 10-AUG-07:03 | 19.83 | 15.96 | 0.742921E+09 | 899.06 | 12-AUG-12:30 | 24.00 | 16.23 |
September | 0.104087E+11 | 27318.93 | 14-SEP-07:02 | 14.18 | 13.39 | 0.723369E+09 | 899.05 | 09-SEP-12:00 | 20.60 | 14.37 |
October | 0.696818E+10 | 9938.84 | 04-OCT-14:50 | 21.60 | 11.46 | 0.695137E+09 | 898.99 | 08-OCT-16:30 | 19.15 | 12.83 |
November | 0.406104E+10 | 7601.53 | 04-NOV-14:00 | 21.10 | 15.93 | 0.582127E+09 | 899.02 | 04-NOV-12:39 | 20.03 | 15.76 |
December | 0.285141E+10 | 7434.92 | 22-DEC-00:25 | 0.00 | -1.0 | 0.572811E+09 | 720.90 | 03-DEC-13:00 | 12.20 | 5.90 |
Annual Sum or Average | 0.856022E+11 | 0.786804E+10 | ||||||||
Minimum of Months | 0.215768E+10 | 6388.70 | -1.4 | -2.1 | 0.529180E+09 | 685.77 | 9.40 | 5.53 | ||
Maximum of Months | 0.142966E+11 | 28508.28 | 27.20 | 17.27 | 0.753391E+09 | 899.06 | 26.10 | 17.73 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.870980E+09 | 3758.56 | 08-JAN-10:03 | -1.3 | -1.3 | 0.299805E+09 | 424.08 | 29-JAN-18:00 | 9.40 | 5.53 |
February | 0.123938E+10 | 3150.31 | 27-FEB-15:00 | 20.00 | 12.15 | 0.280937E+09 | 449.49 | 26-FEB-18:30 | 10.55 | 8.02 |
March | 0.226293E+10 | 21593.39 | 18-MAR-18:08 | 18.03 | 9.07 | 0.326707E+09 | 449.49 | 19-MAR-17:30 | 10.30 | 6.57 |
April | 0.340995E+10 | 21074.14 | 02-APR-17:27 | 18.60 | 11.34 | 0.342963E+09 | 449.52 | 29-APR-12:00 | 20.00 | 14.69 |
May | 0.502813E+10 | 23915.84 | 21-MAY-17:07 | 15.60 | 9.60 | 0.368871E+09 | 449.51 | 07-MAY-12:09 | 19.60 | 15.91 |
June | 0.629830E+10 | 21278.08 | 03-JUN-19:57 | 17.20 | 10.91 | 0.359228E+09 | 449.53 | 11-JUN-16:10 | 21.70 | 14.98 |
July | 0.796250E+10 | 21406.17 | 06-JUL-21:08 | 16.02 | 11.05 | 0.375055E+09 | 449.54 | 23-JUL-17:40 | 26.30 | 15.79 |
August | 0.845187E+10 | 20944.99 | 01-AUG-07:01 | 11.47 | 11.42 | 0.370102E+09 | 449.53 | 12-AUG-12:30 | 24.00 | 16.23 |
September | 0.621147E+10 | 20269.03 | 03-SEP-07:01 | 13.40 | 12.40 | 0.362271E+09 | 449.53 | 09-SEP-12:00 | 20.60 | 14.37 |
October | 0.390814E+10 | 24224.06 | 03-OCT-20:07 | 14.90 | 9.39 | 0.361309E+09 | 449.50 | 08-OCT-16:40 | 18.87 | 12.76 |
November | 0.193275E+10 | 5862.43 | 05-NOV-07:02 | 12.80 | 12.15 | 0.309072E+09 | 449.51 | 04-NOV-12:30 | 19.75 | 15.62 |
December | 0.115297E+10 | 3171.74 | 06-DEC-20:10 | 1.87 | 1.44 | 0.304185E+09 | 439.26 | 03-DEC-18:00 | 8.90 | 3.54 |
Annual Sum or Average | 0.487294E+11 | 0.406051E+10 | ||||||||
Minimum of Months | 0.870980E+09 | 3150.31 | -1.3 | -1.3 | 0.280937E+09 | 424.08 | 8.90 | 3.54 | ||
Maximum of Months | 0.845187E+10 | 24224.06 | 20.00 | 12.40 | 0.375055E+09 | 449.54 | 26.30 | 16.23 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.569406E+09 | 2677.54 | 25-JAN-08:61 | 4.60 | 3.83 | 0.169573E+09 | 340.06 | 21-JAN-13:20 | 2.07 | 1.82 |
February | 0.833490E+09 | 3564.11 | 10-FEB-08:61 | 0.78 | -0.2 | 0.159282E+09 | 406.80 | 25-FEB-13:30 | 14.70 | 11.85 |
March | 0.169384E+10 | 3534.69 | 02-MAR-08:61 | 2.15 | 1.09 | 0.188791E+09 | 449.26 | 18-MAR-12:00 | 17.20 | 10.93 |
April | 0.228896E+10 | 7191.21 | 30-APR-07:01 | 12.20 | 12.20 | 0.198061E+09 | 449.51 | 29-APR-12:00 | 20.00 | 14.69 |
May | 0.324121E+10 | 12898.06 | 05-MAY-06:02 | 13.90 | 11.48 | 0.221910E+09 | 449.50 | 20-MAY-12:09 | 16.20 | 10.62 |
June | 0.419342E+10 | 15598.28 | 11-JUN-07:01 | 12.98 | 11.37 | 0.221600E+09 | 449.51 | 10-JUN-12:09 | 22.38 | 14.88 |
July | 0.542072E+10 | 19597.01 | 25-JUL-06:02 | 13.98 | 13.26 | 0.223901E+09 | 449.53 | 29-JUL-12:30 | 20.85 | 14.88 |
August | 0.606775E+10 | 21760.68 | 01-AUG-06:01 | 11.32 | 11.32 | 0.230146E+09 | 449.53 | 12-AUG-12:30 | 24.00 | 16.23 |
September | 0.407863E+10 | 21408.15 | 14-SEP-06:01 | 12.07 | 11.66 | 0.217613E+09 | 449.53 | 09-SEP-12:00 | 20.60 | 14.37 |
October | 0.255727E+10 | 5445.42 | 04-OCT-14:00 | 21.10 | 11.38 | 0.207773E+09 | 449.49 | 07-OCT-12:09 | 16.28 | 11.83 |
November | 0.131969E+10 | 4286.20 | 04-NOV-14:00 | 21.10 | 15.93 | 0.173119E+09 | 449.51 | 04-NOV-12:39 | 20.03 | 15.76 |
December | 0.780920E+09 | 3515.30 | 06-DEC-08:61 | 1.07 | 0.85 | 0.169754E+09 | 369.54 | 02-DEC-13:00 | 12.20 | 5.78 |
Annual Sum or Average | 0.330453E+11 | 0.238152E+10 | ||||||||
Minimum of Months | 0.569406E+09 | 2677.54 | 0.78 | -0.2 | 0.159282E+09 | 340.06 | 2.07 | 1.82 | ||
Maximum of Months | 0.606775E+10 | 21760.68 | 21.10 | 15.93 | 0.230146E+09 | 449.53 | 24.00 | 16.23 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.478762E+09 | 3595.10 | 21-JAN-10:33 | -0.6 | -0.8 | 0.169467E+09 | 340.06 | 21-JAN-13:20 | 2.07 | 1.82 |
February | 0.725525E+09 | 2953.67 | 16-FEB-10:03 | 2.30 | 1.04 | 0.158584E+09 | 398.79 | 25-FEB-13:30 | 14.70 | 11.85 |
March | 0.152255E+10 | 3456.37 | 02-MAR-08:61 | 2.15 | 1.09 | 0.186825E+09 | 448.22 | 18-MAR-12:00 | 17.20 | 10.93 |
April | 0.214011E+10 | 6459.14 | 27-APR-15:00 | 27.20 | 17.27 | 0.195943E+09 | 449.51 | 29-APR-12:00 | 20.00 | 14.69 |
May | 0.311922E+10 | 11919.95 | 05-MAY-06:02 | 13.90 | 11.48 | 0.221221E+09 | 449.50 | 06-MAY-12:00 | 23.90 | 17.57 |
June | 0.412143E+10 | 15075.47 | 11-JUN-07:01 | 12.98 | 11.37 | 0.221528E+09 | 449.51 | 10-JUN-12:09 | 22.38 | 14.88 |
July | 0.537988E+10 | 19682.72 | 25-JUL-06:02 | 13.98 | 13.26 | 0.223892E+09 | 449.53 | 29-JUL-12:30 | 20.85 | 14.88 |
August | 0.604521E+10 | 21841.91 | 01-AUG-06:01 | 11.32 | 11.32 | 0.230140E+09 | 449.53 | 12-AUG-12:30 | 24.00 | 16.23 |
September | 0.400074E+10 | 21458.23 | 14-SEP-06:01 | 12.07 | 11.66 | 0.217448E+09 | 449.53 | 09-SEP-12:00 | 20.60 | 14.37 |
October | 0.243572E+10 | 5360.59 | 04-OCT-14:00 | 21.10 | 11.38 | 0.205330E+09 | 449.49 | 07-OCT-12:09 | 16.28 | 11.83 |
November | 0.118157E+10 | 3979.57 | 04-NOV-14:00 | 21.10 | 15.93 | 0.171948E+09 | 449.51 | 04-NOV-12:50 | 20.32 | 15.90 |
December | 0.668669E+09 | 2753.95 | 30-DEC-08:61 | 4.32 | 4.10 | 0.169526E+09 | 364.65 | 02-DEC-13:00 | 12.20 | 5.78 |
Annual Sum or Average | 0.318194E+11 | 0.237185E+10 | ||||||||
Minimum of Months | 0.478762E+09 | 2753.95 | -0.6 | -0.8 | 0.158584E+09 | 340.06 | 2.07 | 1.82 | ||
Maximum of Months | 0.604521E+10 | 21841.91 | 27.20 | 17.27 | 0.230140E+09 | 449.53 | 24.00 | 17.57 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.361856E+09 | 2980.12 | 14-JAN-18:25 | 1.65 | -1.4 | 0.169356E+09 | 340.06 | 21-JAN-13:20 | 2.07 | 1.82 |
February | 0.597093E+09 | 3098.76 | 13-FEB-11:53 | 1.70 | 0.20 | 0.157712E+09 | 387.58 | 25-FEB-13:39 | 14.60 | 11.76 |
March | 0.130822E+10 | 3371.26 | 02-MAR-08:61 | 2.15 | 1.09 | 0.184174E+09 | 439.28 | 18-MAR-12:00 | 17.20 | 10.93 |
April | 0.191662E+10 | 6163.96 | 27-APR-15:00 | 27.20 | 17.27 | 0.192663E+09 | 449.51 | 29-APR-12:00 | 20.00 | 14.69 |
May | 0.285803E+10 | 8244.18 | 05-MAY-06:02 | 13.90 | 11.48 | 0.219479E+09 | 449.50 | 06-MAY-12:00 | 23.90 | 17.57 |
June | 0.386378E+10 | 11628.13 | 29-JUN-06:02 | 12.70 | 11.22 | 0.221208E+09 | 449.51 | 10-JUN-12:09 | 22.38 | 14.88 |
July | 0.513380E+10 | 17634.41 | 25-JUL-06:02 | 13.98 | 13.26 | 0.223853E+09 | 449.52 | 29-JUL-12:30 | 20.85 | 14.88 |
August | 0.580048E+10 | 20986.66 | 15-AUG-06:02 | 14.72 | 12.01 | 0.230103E+09 | 449.53 | 12-AUG-12:30 | 24.00 | 16.23 |
September | 0.375293E+10 | 20989.57 | 14-SEP-06:01 | 12.07 | 11.66 | 0.216897E+09 | 449.52 | 09-SEP-12:00 | 20.60 | 14.37 |
October | 0.222646E+10 | 5152.74 | 04-OCT-14:00 | 21.10 | 11.38 | 0.201684E+09 | 449.49 | 07-OCT-12:09 | 16.28 | 11.83 |
November | 0.101304E+10 | 3482.58 | 04-NOV-14:00 | 21.10 | 15.93 | 0.170356E+09 | 449.51 | 04-NOV-12:00 | 20.60 | 16.04 |
December | 0.532854E+09 | 2705.07 | 30-DEC-08:61 | 4.32 | 4.10 | 0.169297E+09 | 357.99 | 02-DEC-13:00 | 12.20 | 5.78 |
Annual Sum or Average | 0.293652E+11 | 0.235678E+10 | ||||||||
Minimum of Months | 0.361856E+09 | 2705.07 | 1.65 | -1.4 | 0.157712E+09 | 340.06 | 2.07 | 1.82 | ||
Maximum of Months | 0.580048E+10 | 20989.57 | 27.20 | 17.27 | 0.230103E+09 | 449.53 | 24.00 | 17.57 |
Report: ZoneCoolingSummaryMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.203519E+09 | 6216.24 | 05-JAN-20:43 | 2.70 | 2.41 | 0.578316E+09 | 906.82 | 21-JAN-15:09 | 3.30 | 2.80 |
February | 0.593656E+09 | 3816.04 | 28-FEB-20:00 | 9.40 | 7.97 | 0.534135E+09 | 1057.48 | 27-FEB-17:10 | 18.62 | 12.13 |
March | 0.167729E+10 | 4633.71 | 01-MAR-19:10 | 7.02 | 2.83 | 0.612778E+09 | 1198.65 | 18-MAR-14:00 | 20.00 | 10.31 |
April | 0.276015E+10 | 10057.40 | 27-APR-15:00 | 27.20 | 17.27 | 0.635883E+09 | 1198.70 | 29-APR-14:09 | 21.28 | 14.85 |
May | 0.427915E+10 | 9189.01 | 06-MAY-13:50 | 23.90 | 16.78 | 0.730871E+09 | 1198.65 | 20-MAY-14:00 | 17.80 | 10.33 |
June | 0.576913E+10 | 11657.89 | 12-JUN-07:02 | 15.50 | 13.88 | 0.754101E+09 | 1198.70 | 03-JUN-14:09 | 21.02 | 13.80 |
July | 0.799989E+10 | 31113.83 | 24-JUL-07:03 | 19.37 | 15.36 | 0.765912E+09 | 1198.74 | 22-JUL-14:09 | 24.60 | 16.62 |
August | 0.916648E+10 | 31967.15 | 14-AUG-07:02 | 16.98 | 14.61 | 0.788627E+09 | 1198.72 | 12-AUG-14:00 | 25.70 | 17.06 |
September | 0.568957E+10 | 22724.09 | 14-SEP-07:02 | 14.18 | 13.39 | 0.735447E+09 | 1198.71 | 02-SEP-14:09 | 19.90 | 14.62 |
October | 0.321591E+10 | 8636.87 | 04-OCT-14:40 | 21.50 | 11.44 | 0.661435E+09 | 1198.64 | 07-OCT-14:09 | 17.38 | 12.03 |
November | 0.113615E+10 | 5046.18 | 12-NOV-11:35 | 4.80 | 4.13 | 0.569961E+09 | 1198.64 | 04-NOV-14:00 | 21.10 | 15.92 |
December | 0.380201E+09 | 5078.24 | 22-DEC-20:45 | 4.72 | 2.13 | 0.579345E+09 | 906.82 | 02-DEC-15:00 | 10.60 | 4.55 |
Annual Sum or Average | 0.428711E+11 | 0.794681E+10 | ||||||||
Minimum of Months | 0.203519E+09 | 3816.04 | 2.70 | 2.13 | 0.534135E+09 | 906.82 | 3.30 | 2.80 | ||
Maximum of Months | 0.916648E+10 | 31967.15 | 27.20 | 17.27 | 0.788627E+09 | 1198.74 | 25.70 | 17.06 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 85584307.60 | 3134.26 | 05-JAN-19:43 | 2.20 | 1.79 | 0.289157E+09 | 453.41 | 21-JAN-15:09 | 3.30 | 2.80 |
February | 0.255292E+09 | 2661.73 | 14-FEB-20:15 | 3.70 | 2.19 | 0.266747E+09 | 524.93 | 27-FEB-17:10 | 18.62 | 12.13 |
March | 0.712312E+09 | 2231.30 | 01-MAR-09:35 | 5.77 | 1.88 | 0.305420E+09 | 599.32 | 18-MAR-14:00 | 20.00 | 10.31 |
April | 0.121595E+10 | 5154.70 | 27-APR-15:00 | 27.20 | 17.27 | 0.315694E+09 | 599.35 | 29-APR-14:20 | 21.47 | 14.92 |
May | 0.197919E+10 | 4664.59 | 06-MAY-13:50 | 23.90 | 16.78 | 0.362156E+09 | 599.33 | 20-MAY-14:00 | 17.80 | 10.33 |
June | 0.278033E+10 | 5656.62 | 28-JUN-15:00 | 26.10 | 15.52 | 0.376372E+09 | 599.34 | 03-JUN-14:09 | 21.02 | 13.80 |
July | 0.397920E+10 | 14669.45 | 24-JUL-07:03 | 19.37 | 15.36 | 0.382870E+09 | 599.37 | 22-JUL-14:09 | 24.60 | 16.62 |
August | 0.461503E+10 | 16438.23 | 14-AUG-07:02 | 16.98 | 14.61 | 0.394288E+09 | 599.36 | 12-AUG-14:00 | 25.70 | 17.06 |
September | 0.275605E+10 | 9465.46 | 14-SEP-07:02 | 14.18 | 13.39 | 0.366660E+09 | 599.35 | 02-SEP-14:09 | 19.90 | 14.62 |
October | 0.143169E+10 | 4366.77 | 04-OCT-14:40 | 21.50 | 11.44 | 0.328523E+09 | 599.32 | 07-OCT-14:09 | 17.38 | 12.03 |
November | 0.489349E+09 | 2998.86 | 13-NOV-10:53 | 2.80 | 2.80 | 0.284463E+09 | 599.32 | 04-NOV-14:00 | 21.10 | 15.92 |
December | 0.164647E+09 | 2648.49 | 18-DEC-19:35 | 3.87 | 3.20 | 0.289665E+09 | 453.41 | 02-DEC-15:00 | 10.60 | 4.55 |
Annual Sum or Average | 0.204646E+11 | 0.396202E+10 | ||||||||
Minimum of Months | 85584307.60 | 2231.30 | 2.20 | 1.79 | 0.266747E+09 | 453.41 | 3.30 | 2.80 | ||
Maximum of Months | 0.461503E+10 | 16438.23 | 27.20 | 17.27 | 0.394288E+09 | 599.37 | 25.70 | 17.06 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 73715659.94 | 3498.36 | 06-JAN-18:53 | 0.60 | 0.60 | 0.289155E+09 | 453.41 | 21-JAN-15:09 | 3.30 | 2.80 |
February | 0.234077E+09 | 2045.48 | 05-FEB-11:55 | 6.70 | 4.94 | 0.266492E+09 | 521.66 | 27-FEB-17:10 | 18.62 | 12.13 |
March | 0.654262E+09 | 2383.68 | 24-MAR-09:35 | 5.00 | 0.25 | 0.304706E+09 | 599.32 | 18-MAR-14:00 | 20.00 | 10.31 |
April | 0.114022E+10 | 4996.61 | 27-APR-15:00 | 27.20 | 17.27 | 0.314077E+09 | 599.35 | 29-APR-14:20 | 21.47 | 14.92 |
May | 0.187578E+10 | 4561.54 | 06-MAY-13:50 | 23.90 | 16.78 | 0.359202E+09 | 599.33 | 20-MAY-14:00 | 17.80 | 10.33 |
June | 0.266583E+10 | 5571.87 | 28-JUN-15:00 | 26.10 | 15.52 | 0.375625E+09 | 599.34 | 03-JUN-14:09 | 21.02 | 13.80 |
July | 0.387187E+10 | 13847.01 | 24-JUL-07:03 | 19.37 | 15.36 | 0.382777E+09 | 599.37 | 22-JUL-14:09 | 24.60 | 16.62 |
August | 0.451312E+10 | 16168.42 | 14-AUG-07:02 | 16.98 | 14.61 | 0.394249E+09 | 599.36 | 12-AUG-14:00 | 25.70 | 17.06 |
September | 0.266589E+10 | 8408.02 | 14-SEP-07:02 | 14.18 | 13.39 | 0.365611E+09 | 599.35 | 02-SEP-14:09 | 19.90 | 14.62 |
October | 0.135570E+10 | 4242.08 | 04-OCT-14:50 | 21.60 | 11.46 | 0.326725E+09 | 599.32 | 07-OCT-14:09 | 17.38 | 12.03 |
November | 0.452095E+09 | 2229.95 | 24-NOV-10:25 | 5.85 | 4.20 | 0.284087E+09 | 599.32 | 04-NOV-14:00 | 21.10 | 15.92 |
December | 0.144865E+09 | 2481.32 | 22-DEC-20:35 | 4.63 | 1.97 | 0.289657E+09 | 453.41 | 02-DEC-15:00 | 10.60 | 4.55 |
Annual Sum or Average | 0.196474E+11 | 0.395236E+10 | ||||||||
Minimum of Months | 73715659.94 | 2045.48 | 0.60 | 0.25 | 0.266492E+09 | 453.41 | 3.30 | 2.80 | ||
Maximum of Months | 0.451312E+10 | 16168.42 | 27.20 | 17.27 | 0.394249E+09 | 599.37 | 25.70 | 17.06 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 39087456.05 | 3398.49 | 06-JAN-20:03 | 1.10 | 1.10 | 0.289129E+09 | 453.41 | 21-JAN-15:09 | 3.30 | 2.80 |
February | 0.173393E+09 | 2783.55 | 06-FEB-20:55 | 3.30 | 2.38 | 0.265923E+09 | 516.83 | 27-FEB-15:50 | 19.50 | 12.37 |
March | 0.504789E+09 | 2603.97 | 22-MAR-10:05 | 4.08 | 3.56 | 0.303278E+09 | 599.32 | 18-MAR-14:00 | 20.00 | 10.31 |
April | 0.968150E+09 | 4685.16 | 27-APR-15:00 | 27.20 | 17.27 | 0.310755E+09 | 599.35 | 29-APR-14:20 | 21.47 | 14.92 |
May | 0.164900E+10 | 4323.60 | 06-MAY-13:50 | 23.90 | 16.78 | 0.352951E+09 | 599.32 | 13-MAY-14:00 | 20.00 | 11.55 |
June | 0.240433E+10 | 5390.53 | 28-JUN-16:50 | 26.60 | 16.64 | 0.373442E+09 | 599.34 | 03-JUN-14:09 | 21.02 | 13.80 |
July | 0.361712E+10 | 11079.01 | 24-JUL-07:03 | 19.37 | 15.36 | 0.382463E+09 | 599.37 | 22-JUL-14:09 | 24.60 | 16.62 |
August | 0.428076E+10 | 13142.63 | 14-AUG-07:02 | 16.98 | 14.61 | 0.394117E+09 | 599.36 | 12-AUG-14:00 | 25.70 | 17.06 |
September | 0.247163E+10 | 5642.63 | 14-SEP-14:10 | 23.90 | 17.08 | 0.362951E+09 | 599.35 | 02-SEP-14:09 | 19.90 | 14.62 |
October | 0.117739E+10 | 3958.64 | 04-OCT-14:50 | 21.60 | 11.46 | 0.323375E+09 | 599.32 | 07-OCT-14:09 | 17.38 | 12.03 |
November | 0.357339E+09 | 2546.39 | 30-NOV-20:25 | 4.40 | 3.53 | 0.283462E+09 | 599.32 | 04-NOV-14:00 | 21.10 | 15.92 |
December | 91566294.93 | 3173.00 | 21-DEC-18:33 | 2.10 | 0.44 | 0.289634E+09 | 453.41 | 02-DEC-15:50 | 10.78 | 4.71 |
Annual Sum or Average | 0.177346E+11 | 0.393148E+10 | ||||||||
Minimum of Months | 39087456.05 | 2546.39 | 1.10 | 0.44 | 0.265923E+09 | 453.41 | 3.30 | 2.80 | ||
Maximum of Months | 0.428076E+10 | 13142.63 | 27.20 | 17.27 | 0.394117E+09 | 599.37 | 25.70 | 17.06 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 2605327.49 | 371.27 | 11-JAN-18:10 | 12.70 | 9.54 | 0.289136E+09 | 453.41 | 21-JAN-15:09 | 3.30 | 2.80 |
February | 44331470.30 | 1252.56 | 28-FEB-18:10 | 10.92 | 8.67 | 0.264892E+09 | 495.47 | 27-FEB-15:50 | 19.50 | 12.37 |
March | 0.155525E+09 | 1600.45 | 02-MAR-12:00 | 10.00 | 6.55 | 0.301139E+09 | 589.88 | 18-MAR-14:00 | 20.00 | 10.31 |
April | 0.581287E+09 | 4285.60 | 27-APR-15:00 | 27.20 | 17.27 | 0.304672E+09 | 599.35 | 29-APR-14:39 | 21.83 | 15.07 |
May | 0.117448E+10 | 3869.20 | 06-MAY-13:50 | 23.90 | 16.78 | 0.340067E+09 | 599.32 | 13-MAY-14:00 | 20.00 | 11.55 |
June | 0.190069E+10 | 5027.81 | 28-JUN-15:00 | 26.10 | 15.52 | 0.366798E+09 | 599.34 | 03-JUN-14:09 | 21.02 | 13.80 |
July | 0.309829E+10 | 7323.75 | 24-JUL-15:00 | 30.60 | 18.76 | 0.380876E+09 | 599.37 | 22-JUL-14:20 | 24.80 | 16.69 |
August | 0.382963E+10 | 7647.13 | 10-AUG-16:40 | 31.60 | 18.69 | 0.393302E+09 | 599.36 | 12-AUG-14:00 | 25.70 | 17.06 |
September | 0.211612E+10 | 5506.65 | 14-SEP-14:10 | 23.90 | 17.08 | 0.355830E+09 | 599.34 | 09-SEP-14:50 | 21.60 | 14.75 |
October | 0.780821E+09 | 3359.35 | 04-OCT-14:50 | 21.60 | 11.46 | 0.316884E+09 | 599.32 | 07-OCT-14:09 | 17.38 | 12.03 |
November | 0.153982E+09 | 2297.02 | 21-NOV-20:05 | 5.60 | 4.06 | 0.282448E+09 | 599.34 | 04-NOV-14:00 | 21.10 | 15.92 |
December | 8301224.83 | 1513.20 | 29-DEC-19:05 | 9.32 | 7.90 | 0.289625E+09 | 453.41 | 09-DEC-15:09 | 5.60 | 4.26 |
Annual Sum or Average | 0.138461E+11 | 0.388567E+10 | ||||||||
Minimum of Months | 2605327.49 | 371.27 | 5.60 | 4.06 | 0.264892E+09 | 453.41 | 3.30 | 2.80 | ||
Maximum of Months | 0.382963E+10 | 7647.13 | 31.60 | 18.76 | 0.393302E+09 | 599.37 | 25.70 | 17.06 |
Report: ZoneHeatingSummaryMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.362919E+10 | 59348.20 | 06-JAN-08:61 | -2.7 |
February | 0.217805E+10 | 59308.95 | 09-FEB-08:61 | -0.6 |
March | 0.684950E+09 | 59300.15 | 07-MAR-08:61 | 7.15 |
April | 0.271490E+09 | 59295.53 | 19-APR-07:01 | 4.18 |
May | 0.178023E+09 | 2334.12 | 05-MAY-07:03 | 14.18 |
June | 76745348.70 | 2462.59 | 10-JUN-07:04 | 15.87 |
July | 25571941.46 | 3396.93 | 24-JUL-07:05 | 19.37 |
August | 38665283.98 | 3313.31 | 10-AUG-07:05 | 19.83 |
September | 76153488.89 | 3072.87 | 14-SEP-07:03 | 14.18 |
October | 0.200446E+09 | 25272.27 | 31-OCT-07:01 | 11.20 |
November | 0.120666E+10 | 59332.87 | 13-NOV-08:61 | 0.78 |
December | 0.272564E+10 | 59337.86 | 11-DEC-08:61 | 2.88 |
Annual Sum or Average | 0.112916E+11 | |||
Minimum of Months | 25571941.46 | 2334.12 | -2.7 | |
Maximum of Months | 0.362919E+10 | 59348.20 | 19.83 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.114670E+10 | 32016.97 | 06-JAN-08:61 | -2.7 |
February | 0.645785E+09 | 31992.15 | 21-FEB-08:61 | 1.28 |
March | 0.165480E+09 | 25439.70 | 24-MAR-07:01 | 2.48 |
April | 0.111793E+09 | 6395.61 | 19-APR-07:01 | 4.18 |
May | 64932972.78 | 1680.59 | 05-MAY-07:03 | 14.18 |
June | 20115813.31 | 1759.30 | 10-JUN-07:04 | 15.87 |
July | 25523266.59 | 2096.70 | 24-JUL-07:05 | 19.37 |
August | 27208123.39 | 2046.20 | 10-AUG-07:05 | 19.83 |
September | 32496814.61 | 1943.06 | 14-SEP-07:03 | 14.18 |
October | 90817066.47 | 1559.96 | 09-OCT-07:02 | 10.78 |
November | 0.330852E+09 | 24444.28 | 30-NOV-08:61 | 5.10 |
December | 0.841732E+09 | 32008.20 | 22-DEC-08:61 | 0.10 |
Annual Sum or Average | 0.350343E+10 | |||
Minimum of Months | 20115813.31 | 1559.96 | -2.7 | |
Maximum of Months | 0.114670E+10 | 32016.97 | 19.83 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.173410E+10 | 31893.88 | 16-JAN-08:61 | -1.0 |
February | 0.974127E+09 | 31991.86 | 19-FEB-08:61 | -4.7 |
March | 0.233955E+09 | 25569.08 | 06-MAR-07:02 | 6.70 |
April | 0.115259E+09 | 9319.91 | 19-APR-06:03 | 2.48 |
May | 62232279.96 | 1681.40 | 05-MAY-06:03 | 13.90 |
June | 21002896.45 | 1747.97 | 11-JUN-07:03 | 12.98 |
July | 42249264.36 | 2023.95 | 24-JUL-06:05 | 17.48 |
August | 51897991.37 | 2065.83 | 10-AUG-19:02 | 29.18 |
September | 23384854.57 | 1906.51 | 14-SEP-06:03 | 12.07 |
October | 79428631.18 | 1370.92 | 09-OCT-07:02 | 10.78 |
November | 0.587313E+09 | 20608.60 | 24-NOV-07:02 | 1.20 |
December | 0.130113E+10 | 31692.93 | 26-DEC-07:01 | -1.6 |
Annual Sum or Average | 0.522607E+10 | |||
Minimum of Months | 21002896.45 | 1370.92 | -4.7 | |
Maximum of Months | 0.173410E+10 | 31991.86 | 29.18 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.197981E+10 | 31967.57 | 16-JAN-08:61 | -1.0 |
February | 0.111686E+10 | 32065.98 | 19-FEB-08:61 | -4.7 |
March | 0.298549E+09 | 31263.46 | 06-MAR-07:02 | 6.70 |
April | 0.126610E+09 | 13027.66 | 19-APR-06:03 | 2.48 |
May | 71878546.99 | 1652.15 | 05-MAY-06:03 | 13.90 |
June | 21950626.35 | 1736.25 | 11-JUN-07:03 | 12.98 |
July | 41137141.18 | 2043.97 | 24-JUL-06:05 | 17.48 |
August | 51040641.78 | 2068.73 | 10-AUG-19:02 | 29.18 |
September | 25056241.77 | 1913.88 | 14-SEP-06:03 | 12.07 |
October | 85958263.33 | 1315.24 | 06-OCT-06:03 | 11.02 |
November | 0.710729E+09 | 26732.12 | 24-NOV-07:02 | 1.20 |
December | 0.149642E+10 | 31766.93 | 26-DEC-07:01 | -1.6 |
Annual Sum or Average | 0.602600E+10 | |||
Minimum of Months | 21950626.35 | 1315.24 | -4.7 | |
Maximum of Months | 0.197981E+10 | 32065.98 | 29.18 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.228357E+10 | 31782.77 | 16-JAN-08:61 | -1.0 |
February | 0.131158E+10 | 31879.81 | 19-FEB-08:61 | -4.7 |
March | 0.400119E+09 | 31088.70 | 06-MAR-07:02 | 6.70 |
April | 0.148339E+09 | 16804.37 | 19-APR-06:03 | 2.48 |
May | 84399110.92 | 1506.09 | 05-MAY-06:03 | 13.90 |
June | 26125328.61 | 1616.20 | 11-JUN-07:03 | 12.98 |
July | 37473958.95 | 1950.13 | 24-JUL-06:05 | 17.48 |
August | 49171676.06 | 2072.91 | 10-AUG-19:02 | 29.18 |
September | 29758876.58 | 1885.78 | 14-SEP-06:03 | 12.07 |
October | 98346096.64 | 3064.75 | 30-OCT-06:05 | 7.20 |
November | 0.865213E+09 | 30779.76 | 24-NOV-07:02 | 1.20 |
December | 0.174701E+10 | 31585.26 | 26-DEC-07:01 | -1.6 |
Annual Sum or Average | 0.708111E+10 | |||
Minimum of Months | 26125328.61 | 1506.09 | -4.7 | |
Maximum of Months | 0.228357E+10 | 31879.81 | 29.18 |
Report: ZoneHeatingSummaryMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.509749E+10 | 57745.51 | 06-JAN-08:61 | -2.7 |
February | 0.301763E+10 | 57724.01 | 08-FEB-08:61 | -0.4 |
March | 0.117492E+10 | 57721.07 | 25-MAR-07:01 | 2.15 |
April | 0.407181E+09 | 57712.87 | 19-APR-07:01 | 4.18 |
May | 0.187403E+09 | 8666.53 | 29-MAY-08:61 | 10.60 |
June | 92666823.67 | 2488.84 | 12-JUN-07:04 | 15.50 |
July | 55755150.46 | 3451.45 | 24-JUL-07:05 | 19.37 |
August | 60361811.31 | 3354.58 | 13-AUG-16:12 | 27.97 |
September | 0.106056E+09 | 2838.85 | 14-SEP-07:03 | 14.18 |
October | 0.281643E+09 | 57225.40 | 30-OCT-07:01 | 7.20 |
November | 0.209388E+10 | 57736.81 | 13-NOV-08:61 | 0.78 |
December | 0.399873E+10 | 57740.34 | 26-DEC-08:61 | -1.1 |
Annual Sum or Average | 0.165737E+11 | |||
Minimum of Months | 55755150.46 | 2488.84 | -2.7 | |
Maximum of Months | 0.509749E+10 | 57745.51 | 27.97 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.304156E+10 | 29730.43 | 07-JAN-08:61 | -3.8 |
February | 0.185127E+10 | 29719.39 | 08-FEB-08:61 | -0.4 |
March | 0.790556E+09 | 29718.20 | 25-MAR-07:01 | 2.15 |
April | 0.271215E+09 | 29712.90 | 19-APR-07:01 | 4.18 |
May | 0.108390E+09 | 9170.98 | 29-MAY-08:61 | 10.60 |
June | 60269443.20 | 1286.32 | 12-JUN-07:04 | 15.50 |
July | 33343148.80 | 1787.98 | 24-JUL-07:05 | 19.37 |
August | 35572919.06 | 1765.10 | 13-AUG-16:12 | 27.97 |
September | 63003146.09 | 1451.93 | 14-SEP-07:03 | 14.18 |
October | 0.185762E+09 | 29454.63 | 30-OCT-07:01 | 7.20 |
November | 0.131241E+10 | 29725.00 | 24-NOV-08:61 | 1.97 |
December | 0.242074E+10 | 29728.16 | 26-DEC-08:61 | -1.1 |
Annual Sum or Average | 0.101741E+11 | |||
Minimum of Months | 33343148.80 | 1286.32 | -3.8 | |
Maximum of Months | 0.304156E+10 | 29730.43 | 27.97 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.313338E+10 | 29562.73 | 07-JAN-08:61 | -3.8 |
February | 0.192646E+10 | 29551.79 | 08-FEB-08:61 | -0.4 |
March | 0.856600E+09 | 29550.72 | 25-MAR-07:01 | 2.15 |
April | 0.301512E+09 | 29545.33 | 19-APR-07:01 | 4.18 |
May | 0.113394E+09 | 13690.67 | 29-MAY-08:61 | 10.60 |
June | 66663337.83 | 1224.23 | 12-JUN-07:04 | 15.50 |
July | 36478054.83 | 1731.07 | 24-JUL-07:05 | 19.37 |
August | 38096758.98 | 1759.80 | 13-AUG-16:12 | 27.97 |
September | 66984500.62 | 1409.27 | 14-SEP-07:03 | 14.18 |
October | 0.208476E+09 | 29290.30 | 30-OCT-07:01 | 7.20 |
November | 0.136931E+10 | 29557.42 | 24-NOV-08:61 | 1.97 |
December | 0.249638E+10 | 29560.50 | 26-DEC-08:61 | -1.1 |
Annual Sum or Average | 0.106138E+11 | |||
Minimum of Months | 36478054.83 | 1224.23 | -3.8 | |
Maximum of Months | 0.313338E+10 | 29562.73 | 27.97 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.348672E+10 | 29375.14 | 06-JAN-08:61 | -2.7 |
February | 0.221117E+10 | 29363.46 | 08-FEB-08:61 | -0.4 |
March | 0.108399E+10 | 29360.92 | 25-MAR-07:01 | 2.15 |
April | 0.416945E+09 | 29357.62 | 19-APR-07:01 | 4.18 |
May | 0.133985E+09 | 24197.41 | 29-MAY-08:61 | 10.60 |
June | 87193180.18 | 1123.21 | 05-JUN-07:01 | 11.97 |
July | 53734201.48 | 1643.72 | 30-JUL-16:02 | 27.62 |
August | 47387405.83 | 1756.37 | 13-AUG-16:12 | 27.97 |
September | 79922688.23 | 1291.65 | 14-SEP-07:03 | 14.18 |
October | 0.271325E+09 | 29105.54 | 30-OCT-07:01 | 7.20 |
November | 0.156229E+10 | 29369.97 | 13-NOV-08:61 | 0.78 |
December | 0.279712E+10 | 29371.66 | 11-DEC-08:61 | 2.88 |
Annual Sum or Average | 0.122318E+11 | |||
Minimum of Months | 47387405.83 | 1123.21 | -2.7 | |
Maximum of Months | 0.348672E+10 | 29375.14 | 27.97 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.508129E+10 | 29417.39 | 16-JAN-09:13 | -0.4 |
February | 0.348855E+10 | 29523.24 | 19-FEB-09:12 | -2.9 |
March | 0.211554E+10 | 29338.41 | 07-MAR-08:61 | 7.15 |
April | 0.987903E+09 | 29330.61 | 19-APR-07:01 | 4.18 |
May | 0.298599E+09 | 28905.23 | 18-MAY-07:01 | 6.10 |
June | 0.116898E+09 | 16118.43 | 14-JUN-07:03 | 10.68 |
July | 0.103201E+09 | 1660.70 | 30-JUL-16:02 | 27.62 |
August | 79196240.57 | 1751.49 | 13-AUG-16:12 | 27.97 |
September | 0.110131E+09 | 10684.87 | 28-SEP-07:03 | 9.08 |
October | 0.588383E+09 | 29082.25 | 30-OCT-07:01 | 7.20 |
November | 0.236596E+10 | 29356.57 | 13-NOV-08:61 | 0.78 |
December | 0.408356E+10 | 29367.93 | 26-DEC-08:13 | -1.1 |
Annual Sum or Average | 0.194192E+11 | |||
Minimum of Months | 79196240.57 | 1660.70 | -2.9 | |
Maximum of Months | 0.508129E+10 | 29523.24 | 27.97 |
Report: ZoneElectricSummaryMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.136196E+11 | 8262.19 | 01-JAN-10:09 | 0.223514E+10 | 1348.26 | 01-JAN-10:09 |
February | 0.123234E+11 | 8262.19 | 01-FEB-10:09 | 0.202238E+10 | 1348.26 | 01-FEB-10:09 |
March | 0.136478E+11 | 8262.19 | 01-MAR-10:09 | 0.223972E+10 | 1348.26 | 01-MAR-10:09 |
April | 0.132157E+11 | 8262.19 | 01-APR-09:09 | 0.216880E+10 | 1348.26 | 01-APR-09:09 |
May | 0.136196E+11 | 8262.19 | 01-MAY-09:09 | 0.223514E+10 | 1348.26 | 01-MAY-09:09 |
June | 0.132157E+11 | 8262.19 | 01-JUN-09:09 | 0.216880E+10 | 1348.26 | 01-JUN-09:09 |
July | 0.136478E+11 | 8262.19 | 01-JUL-09:09 | 0.223972E+10 | 1348.26 | 01-JUL-09:09 |
August | 0.136196E+11 | 8262.19 | 01-AUG-09:09 | 0.223514E+10 | 1348.26 | 01-AUG-09:09 |
September | 0.132439E+11 | 8262.19 | 01-SEP-09:09 | 0.217339E+10 | 1348.26 | 01-SEP-09:09 |
October | 0.136196E+11 | 8262.19 | 01-OCT-09:09 | 0.223514E+10 | 1348.26 | 01-OCT-09:09 |
November | 0.131593E+11 | 8262.19 | 01-NOV-09:09 | 0.215964E+10 | 1348.26 | 01-NOV-09:09 |
December | 0.136759E+11 | 8262.19 | 01-DEC-10:09 | 0.224431E+10 | 1348.26 | 01-DEC-10:09 |
Annual Sum or Average | 0.160608E+12 | 0.263573E+11 | ||||
Minimum of Months | 0.123234E+11 | 8262.19 | 0.202238E+10 | 1348.26 | ||
Maximum of Months | 0.136759E+11 | 8262.19 | 0.224431E+10 | 1348.26 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.759377E+10 | 4606.69 | 01-JAN-10:09 | 0.111757E+10 | 674.13 | 01-JAN-10:09 |
February | 0.687105E+10 | 4606.69 | 01-FEB-10:09 | 0.101119E+10 | 674.13 | 01-FEB-10:09 |
March | 0.760948E+10 | 4606.69 | 01-MAR-10:09 | 0.111986E+10 | 674.13 | 01-MAR-10:09 |
April | 0.736857E+10 | 4606.69 | 01-APR-09:09 | 0.108440E+10 | 674.13 | 01-APR-09:09 |
May | 0.759377E+10 | 4606.69 | 01-MAY-09:09 | 0.111757E+10 | 674.13 | 01-MAY-09:09 |
June | 0.736857E+10 | 4606.69 | 01-JUN-09:09 | 0.108440E+10 | 674.13 | 01-JUN-09:09 |
July | 0.760948E+10 | 4606.69 | 01-JUL-09:09 | 0.111986E+10 | 674.13 | 01-JUL-09:09 |
August | 0.759377E+10 | 4606.69 | 01-AUG-09:09 | 0.111757E+10 | 674.13 | 01-AUG-09:09 |
September | 0.738428E+10 | 4606.69 | 01-SEP-09:09 | 0.108669E+10 | 674.13 | 01-SEP-09:09 |
October | 0.759377E+10 | 4606.69 | 01-OCT-09:09 | 0.111757E+10 | 674.13 | 01-OCT-09:09 |
November | 0.733715E+10 | 4606.69 | 01-NOV-09:09 | 0.107982E+10 | 674.13 | 01-NOV-09:09 |
December | 0.762519E+10 | 4606.69 | 01-DEC-10:09 | 0.112215E+10 | 674.13 | 01-DEC-10:09 |
Annual Sum or Average | 0.895488E+11 | 0.131787E+11 | ||||
Minimum of Months | 0.687105E+10 | 4606.69 | 0.101119E+10 | 674.13 | ||
Maximum of Months | 0.762519E+10 | 4606.69 | 0.112215E+10 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.552790E+10 | 4250.44 | 01-JAN-10:09 | 0.883781E+09 | 674.13 | 01-JAN-10:09 |
February | 0.500604E+10 | 4250.44 | 01-FEB-09:09 | 0.800324E+09 | 674.13 | 01-FEB-09:09 |
March | 0.564387E+10 | 4250.44 | 01-MAR-09:09 | 0.902118E+09 | 674.13 | 01-MAR-09:09 |
April | 0.536361E+10 | 4250.44 | 01-APR-08:09 | 0.857490E+09 | 674.13 | 01-APR-08:09 |
May | 0.558588E+10 | 4250.44 | 01-MAY-08:09 | 0.892950E+09 | 674.13 | 01-MAY-08:09 |
June | 0.545059E+10 | 4250.44 | 01-JUN-08:09 | 0.871243E+09 | 674.13 | 01-JUN-08:09 |
July | 0.549891E+10 | 4250.44 | 01-JUL-08:09 | 0.879197E+09 | 674.13 | 01-JUL-08:09 |
August | 0.564387E+10 | 4250.44 | 01-AUG-08:09 | 0.902118E+09 | 674.13 | 01-AUG-08:09 |
September | 0.536361E+10 | 4250.44 | 01-SEP-08:09 | 0.857490E+09 | 674.13 | 01-SEP-08:09 |
October | 0.552790E+10 | 4250.44 | 01-OCT-09:09 | 0.883781E+09 | 674.13 | 01-OCT-09:09 |
November | 0.536361E+10 | 4250.44 | 01-NOV-08:09 | 0.857490E+09 | 674.13 | 01-NOV-08:09 |
December | 0.549891E+10 | 4250.44 | 01-DEC-09:09 | 0.879197E+09 | 674.13 | 01-DEC-09:09 |
Annual Sum or Average | 0.654747E+11 | 0.104672E+11 | ||||
Minimum of Months | 0.500604E+10 | 4250.44 | 0.800324E+09 | 674.13 | ||
Maximum of Months | 0.564387E+10 | 4250.44 | 0.902118E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.552790E+10 | 4250.44 | 01-JAN-10:09 | 0.883781E+09 | 674.13 | 01-JAN-10:09 |
February | 0.500604E+10 | 4250.44 | 01-FEB-09:09 | 0.800324E+09 | 674.13 | 01-FEB-09:09 |
March | 0.564387E+10 | 4250.44 | 01-MAR-09:09 | 0.902118E+09 | 674.13 | 01-MAR-09:09 |
April | 0.536361E+10 | 4250.44 | 01-APR-08:09 | 0.857490E+09 | 674.13 | 01-APR-08:09 |
May | 0.558588E+10 | 4250.44 | 01-MAY-08:09 | 0.892950E+09 | 674.13 | 01-MAY-08:09 |
June | 0.545059E+10 | 4250.44 | 01-JUN-08:09 | 0.871243E+09 | 674.13 | 01-JUN-08:09 |
July | 0.549891E+10 | 4250.44 | 01-JUL-08:09 | 0.879197E+09 | 674.13 | 01-JUL-08:09 |
August | 0.564387E+10 | 4250.44 | 01-AUG-08:09 | 0.902118E+09 | 674.13 | 01-AUG-08:09 |
September | 0.536361E+10 | 4250.44 | 01-SEP-08:09 | 0.857490E+09 | 674.13 | 01-SEP-08:09 |
October | 0.552790E+10 | 4250.44 | 01-OCT-09:09 | 0.883781E+09 | 674.13 | 01-OCT-09:09 |
November | 0.536361E+10 | 4250.44 | 01-NOV-08:09 | 0.857490E+09 | 674.13 | 01-NOV-08:09 |
December | 0.549891E+10 | 4250.44 | 01-DEC-09:09 | 0.879197E+09 | 674.13 | 01-DEC-09:09 |
Annual Sum or Average | 0.654747E+11 | 0.104672E+11 | ||||
Minimum of Months | 0.500604E+10 | 4250.44 | 0.800324E+09 | 674.13 | ||
Maximum of Months | 0.564387E+10 | 4250.44 | 0.902118E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.552790E+10 | 4250.44 | 01-JAN-10:09 | 0.883781E+09 | 674.13 | 01-JAN-10:09 |
February | 0.500604E+10 | 4250.44 | 01-FEB-09:09 | 0.800324E+09 | 674.13 | 01-FEB-09:09 |
March | 0.564387E+10 | 4250.44 | 01-MAR-09:09 | 0.902118E+09 | 674.13 | 01-MAR-09:09 |
April | 0.536361E+10 | 4250.44 | 01-APR-08:09 | 0.857490E+09 | 674.13 | 01-APR-08:09 |
May | 0.558588E+10 | 4250.44 | 01-MAY-08:09 | 0.892950E+09 | 674.13 | 01-MAY-08:09 |
June | 0.545059E+10 | 4250.44 | 01-JUN-08:09 | 0.871243E+09 | 674.13 | 01-JUN-08:09 |
July | 0.549891E+10 | 4250.44 | 01-JUL-08:09 | 0.879197E+09 | 674.13 | 01-JUL-08:09 |
August | 0.564387E+10 | 4250.44 | 01-AUG-08:09 | 0.902118E+09 | 674.13 | 01-AUG-08:09 |
September | 0.536361E+10 | 4250.44 | 01-SEP-08:09 | 0.857490E+09 | 674.13 | 01-SEP-08:09 |
October | 0.552790E+10 | 4250.44 | 01-OCT-09:09 | 0.883781E+09 | 674.13 | 01-OCT-09:09 |
November | 0.536361E+10 | 4250.44 | 01-NOV-08:09 | 0.857490E+09 | 674.13 | 01-NOV-08:09 |
December | 0.549891E+10 | 4250.44 | 01-DEC-09:09 | 0.879197E+09 | 674.13 | 01-DEC-09:09 |
Annual Sum or Average | 0.654747E+11 | 0.104672E+11 | ||||
Minimum of Months | 0.500604E+10 | 4250.44 | 0.800324E+09 | 674.13 | ||
Maximum of Months | 0.564387E+10 | 4250.44 | 0.902118E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.724555E+10 | 6064.13 | 01-JAN-11:09 | 0.162546E+10 | 1348.26 | 01-JAN-11:09 |
February | 0.656305E+10 | 6064.13 | 01-FEB-10:09 | 0.147229E+10 | 1348.26 | 01-FEB-10:09 |
March | 0.741101E+10 | 6064.13 | 01-MAR-10:09 | 0.166213E+10 | 1348.26 | 01-MAR-10:09 |
April | 0.703184E+10 | 6064.13 | 01-APR-09:09 | 0.157746E+10 | 1348.26 | 01-APR-09:09 |
May | 0.732828E+10 | 6064.13 | 01-MAY-09:09 | 0.164379E+10 | 1348.26 | 01-MAY-09:09 |
June | 0.715593E+10 | 6064.13 | 01-JUN-09:09 | 0.160496E+10 | 1348.26 | 01-JUN-09:09 |
July | 0.720419E+10 | 6064.13 | 01-JUL-09:09 | 0.161629E+10 | 1348.26 | 01-JUL-09:09 |
August | 0.741101E+10 | 6064.13 | 01-AUG-09:09 | 0.166213E+10 | 1348.26 | 01-AUG-09:09 |
September | 0.703184E+10 | 6064.13 | 01-SEP-09:09 | 0.157746E+10 | 1348.26 | 01-SEP-09:09 |
October | 0.724555E+10 | 6064.13 | 01-OCT-10:09 | 0.162546E+10 | 1348.26 | 01-OCT-10:09 |
November | 0.703184E+10 | 6064.13 | 01-NOV-09:09 | 0.157746E+10 | 1348.26 | 01-NOV-09:09 |
December | 0.720419E+10 | 6064.13 | 01-DEC-10:09 | 0.161629E+10 | 1348.26 | 01-DEC-10:09 |
Annual Sum or Average | 0.858643E+11 | 0.192612E+11 | ||||
Minimum of Months | 0.656305E+10 | 6064.13 | 0.147229E+10 | 1348.26 | ||
Maximum of Months | 0.741101E+10 | 6064.13 | 0.166213E+10 | 1348.26 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.362278E+10 | 3032.07 | 01-JAN-11:09 | 0.812728E+09 | 674.13 | 01-JAN-11:09 |
February | 0.328152E+10 | 3032.07 | 01-FEB-10:09 | 0.736147E+09 | 674.13 | 01-FEB-10:09 |
March | 0.370550E+10 | 3032.07 | 01-MAR-10:09 | 0.831065E+09 | 674.13 | 01-MAR-10:09 |
April | 0.351592E+10 | 3032.07 | 01-APR-09:09 | 0.788729E+09 | 674.13 | 01-APR-09:09 |
May | 0.366414E+10 | 3032.07 | 01-MAY-09:09 | 0.821897E+09 | 674.13 | 01-MAY-09:09 |
June | 0.357797E+10 | 3032.07 | 01-JUN-09:09 | 0.802482E+09 | 674.13 | 01-JUN-09:09 |
July | 0.360209E+10 | 3032.07 | 01-JUL-09:09 | 0.808144E+09 | 674.13 | 01-JUL-09:09 |
August | 0.370550E+10 | 3032.07 | 01-AUG-09:09 | 0.831065E+09 | 674.13 | 01-AUG-09:09 |
September | 0.351592E+10 | 3032.07 | 01-SEP-09:09 | 0.788729E+09 | 674.13 | 01-SEP-09:09 |
October | 0.362278E+10 | 3032.07 | 01-OCT-10:09 | 0.812728E+09 | 674.13 | 01-OCT-10:09 |
November | 0.351592E+10 | 3032.07 | 01-NOV-09:09 | 0.788729E+09 | 674.13 | 01-NOV-09:09 |
December | 0.360209E+10 | 3032.07 | 01-DEC-10:09 | 0.808144E+09 | 674.13 | 01-DEC-10:09 |
Annual Sum or Average | 0.429321E+11 | 0.963059E+10 | ||||
Minimum of Months | 0.328152E+10 | 3032.07 | 0.736147E+09 | 674.13 | ||
Maximum of Months | 0.370550E+10 | 3032.07 | 0.831065E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.362278E+10 | 3032.07 | 01-JAN-11:09 | 0.812728E+09 | 674.13 | 01-JAN-11:09 |
February | 0.328152E+10 | 3032.07 | 01-FEB-10:09 | 0.736147E+09 | 674.13 | 01-FEB-10:09 |
March | 0.370550E+10 | 3032.07 | 01-MAR-10:09 | 0.831065E+09 | 674.13 | 01-MAR-10:09 |
April | 0.351592E+10 | 3032.07 | 01-APR-09:09 | 0.788729E+09 | 674.13 | 01-APR-09:09 |
May | 0.366414E+10 | 3032.07 | 01-MAY-09:09 | 0.821897E+09 | 674.13 | 01-MAY-09:09 |
June | 0.357797E+10 | 3032.07 | 01-JUN-09:09 | 0.802482E+09 | 674.13 | 01-JUN-09:09 |
July | 0.360209E+10 | 3032.07 | 01-JUL-09:09 | 0.808144E+09 | 674.13 | 01-JUL-09:09 |
August | 0.370550E+10 | 3032.07 | 01-AUG-09:09 | 0.831065E+09 | 674.13 | 01-AUG-09:09 |
September | 0.351592E+10 | 3032.07 | 01-SEP-09:09 | 0.788729E+09 | 674.13 | 01-SEP-09:09 |
October | 0.362278E+10 | 3032.07 | 01-OCT-10:09 | 0.812728E+09 | 674.13 | 01-OCT-10:09 |
November | 0.351592E+10 | 3032.07 | 01-NOV-09:09 | 0.788729E+09 | 674.13 | 01-NOV-09:09 |
December | 0.360209E+10 | 3032.07 | 01-DEC-10:09 | 0.808144E+09 | 674.13 | 01-DEC-10:09 |
Annual Sum or Average | 0.429321E+11 | 0.963059E+10 | ||||
Minimum of Months | 0.328152E+10 | 3032.07 | 0.736147E+09 | 674.13 | ||
Maximum of Months | 0.370550E+10 | 3032.07 | 0.831065E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.362278E+10 | 3032.07 | 01-JAN-11:09 | 0.812728E+09 | 674.13 | 01-JAN-11:09 |
February | 0.328152E+10 | 3032.07 | 01-FEB-10:09 | 0.736147E+09 | 674.13 | 01-FEB-10:09 |
March | 0.370550E+10 | 3032.07 | 01-MAR-10:09 | 0.831065E+09 | 674.13 | 01-MAR-10:09 |
April | 0.351592E+10 | 3032.07 | 01-APR-09:09 | 0.788729E+09 | 674.13 | 01-APR-09:09 |
May | 0.366414E+10 | 3032.07 | 01-MAY-09:09 | 0.821897E+09 | 674.13 | 01-MAY-09:09 |
June | 0.357797E+10 | 3032.07 | 01-JUN-09:09 | 0.802482E+09 | 674.13 | 01-JUN-09:09 |
July | 0.360209E+10 | 3032.07 | 01-JUL-09:09 | 0.808144E+09 | 674.13 | 01-JUL-09:09 |
August | 0.370550E+10 | 3032.07 | 01-AUG-09:09 | 0.831065E+09 | 674.13 | 01-AUG-09:09 |
September | 0.351592E+10 | 3032.07 | 01-SEP-09:09 | 0.788729E+09 | 674.13 | 01-SEP-09:09 |
October | 0.362278E+10 | 3032.07 | 01-OCT-10:09 | 0.812728E+09 | 674.13 | 01-OCT-10:09 |
November | 0.351592E+10 | 3032.07 | 01-NOV-09:09 | 0.788729E+09 | 674.13 | 01-NOV-09:09 |
December | 0.360209E+10 | 3032.07 | 01-DEC-10:09 | 0.808144E+09 | 674.13 | 01-DEC-10:09 |
Annual Sum or Average | 0.429321E+11 | 0.963059E+10 | ||||
Minimum of Months | 0.328152E+10 | 3032.07 | 0.736147E+09 | 674.13 | ||
Maximum of Months | 0.370550E+10 | 3032.07 | 0.831065E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.362278E+10 | 3032.07 | 01-JAN-11:09 | 0.812728E+09 | 674.13 | 01-JAN-11:09 |
February | 0.328152E+10 | 3032.07 | 01-FEB-10:09 | 0.736147E+09 | 674.13 | 01-FEB-10:09 |
March | 0.370550E+10 | 3032.07 | 01-MAR-10:09 | 0.831065E+09 | 674.13 | 01-MAR-10:09 |
April | 0.351592E+10 | 3032.07 | 01-APR-09:09 | 0.788729E+09 | 674.13 | 01-APR-09:09 |
May | 0.366414E+10 | 3032.07 | 01-MAY-09:09 | 0.821897E+09 | 674.13 | 01-MAY-09:09 |
June | 0.357797E+10 | 3032.07 | 01-JUN-09:09 | 0.802482E+09 | 674.13 | 01-JUN-09:09 |
July | 0.360209E+10 | 3032.07 | 01-JUL-09:09 | 0.808144E+09 | 674.13 | 01-JUL-09:09 |
August | 0.370550E+10 | 3032.07 | 01-AUG-09:09 | 0.831065E+09 | 674.13 | 01-AUG-09:09 |
September | 0.351592E+10 | 3032.07 | 01-SEP-09:09 | 0.788729E+09 | 674.13 | 01-SEP-09:09 |
October | 0.362278E+10 | 3032.07 | 01-OCT-10:09 | 0.812728E+09 | 674.13 | 01-OCT-10:09 |
November | 0.351592E+10 | 3032.07 | 01-NOV-09:09 | 0.788729E+09 | 674.13 | 01-NOV-09:09 |
December | 0.360209E+10 | 3032.07 | 01-DEC-10:09 | 0.808144E+09 | 674.13 | 01-DEC-10:09 |
Annual Sum or Average | 0.429321E+11 | 0.963059E+10 | ||||
Minimum of Months | 0.328152E+10 | 3032.07 | 0.736147E+09 | 674.13 | ||
Maximum of Months | 0.370550E+10 | 3032.07 | 0.831065E+09 | 674.13 |
Report: SpaceGainsMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.180574E+10 | 0.136196E+11 | 0.223514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.754493E+10 |
February | 0.163016E+10 | 0.123234E+11 | 0.202238E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.607565E+10 |
March | 0.178954E+10 | 0.136478E+11 | 0.223972E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.557093E+10 |
April | 0.174484E+10 | 0.132157E+11 | 0.216880E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39725394.58 | 0.448457E+10 |
May | 0.179537E+10 | 0.136196E+11 | 0.223514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4301743.60 | 0.387985E+10 |
June | 0.173447E+10 | 0.132157E+11 | 0.216880E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22410495.18 | 0.286395E+10 |
July | 0.181028E+10 | 0.136478E+11 | 0.223972E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.212148E+09 | 0.196529E+10 |
August | 0.178501E+10 | 0.136196E+11 | 0.223514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.454341E+09 | 0.163738E+10 |
September | 0.174937E+10 | 0.132439E+11 | 0.217339E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5249777.50 | 0.268597E+10 |
October | 0.180574E+10 | 0.136196E+11 | 0.223514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.468737E+10 |
November | 0.174613E+10 | 0.131593E+11 | 0.215964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.598485E+10 |
December | 0.181481E+10 | 0.136759E+11 | 0.224431E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.687944E+10 |
Annual Sum or Average | 0.212115E+11 | 0.160608E+12 | 0.263573E+11 | 0.738177E+09 | 0.542602E+11 | ||||
Minimum of Months | 0.163016E+10 | 0.123234E+11 | 0.202238E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163738E+10 |
Maximum of Months | 0.181481E+10 | 0.136759E+11 | 0.224431E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.454341E+09 | 0.754493E+10 |
Report: SpaceGainsMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.902868E+09 | 0.759377E+10 | 0.111757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.384395E+10 |
February | 0.815075E+09 | 0.687105E+10 | 0.101119E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.309372E+10 |
March | 0.894769E+09 | 0.760948E+10 | 0.111986E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.286282E+10 |
April | 0.872416E+09 | 0.736857E+10 | 0.108440E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22030374.75 | 0.228173E+10 |
May | 0.897684E+09 | 0.759377E+10 | 0.111757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2413389.30 | 0.193525E+10 |
June | 0.867232E+09 | 0.736857E+10 | 0.108440E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12427967.22 | 0.135983E+10 |
July | 0.905135E+09 | 0.760948E+10 | 0.111986E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117415E+09 | 0.899884E+09 |
August | 0.892501E+09 | 0.759377E+10 | 0.111757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.252302E+09 | 0.729663E+09 |
September | 0.874683E+09 | 0.738428E+10 | 0.108669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2958109.65 | 0.138958E+10 |
October | 0.902868E+09 | 0.759377E+10 | 0.111757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.239785E+10 |
November | 0.873064E+09 | 0.733715E+10 | 0.107982E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.306766E+10 |
December | 0.907403E+09 | 0.762519E+10 | 0.112215E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.355720E+10 |
Annual Sum or Average | 0.106057E+11 | 0.895488E+11 | 0.131787E+11 | 0.409546E+09 | 0.274191E+11 | ||||
Minimum of Months | 0.815075E+09 | 0.687105E+10 | 0.101119E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.729663E+09 |
Maximum of Months | 0.907403E+09 | 0.762519E+10 | 0.112215E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.252302E+09 | 0.384395E+10 |
Report: SpaceGainsMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.537120E+09 | 0.552790E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.394081E+10 |
February | 0.487879E+09 | 0.500604E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.316388E+10 |
March | 0.551374E+09 | 0.564387E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.289509E+10 |
April | 0.524810E+09 | 0.536361E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21668013.32 | 0.232916E+10 |
May | 0.544247E+09 | 0.558588E+10 | 0.892950E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2413432.14 | 0.200428E+10 |
June | 0.532585E+09 | 0.545059E+10 | 0.871243E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12427557.41 | 0.142910E+10 |
July | 0.536472E+09 | 0.549891E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110579E+09 | 0.973744E+09 |
August | 0.551374E+09 | 0.564387E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.248536E+09 | 0.792319E+09 |
September | 0.524810E+09 | 0.536361E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2958261.97 | 0.143643E+10 |
October | 0.537120E+09 | 0.552790E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.242626E+10 |
November | 0.518979E+09 | 0.536361E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.310542E+10 |
December | 0.536472E+09 | 0.549891E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.363639E+10 |
Annual Sum or Average | 0.638324E+10 | 0.654747E+11 | 0.104672E+11 | 0.398582E+09 | 0.281329E+11 | ||||
Minimum of Months | 0.487879E+09 | 0.500604E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.792319E+09 |
Maximum of Months | 0.551374E+09 | 0.564387E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.248536E+09 | 0.394081E+10 |
Report: SpaceGainsMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.537120E+09 | 0.552790E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.392850E+10 |
February | 0.487879E+09 | 0.500604E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.314731E+10 |
March | 0.551374E+09 | 0.564387E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.286470E+10 |
April | 0.524810E+09 | 0.536361E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21672934.11 | 0.229554E+10 |
May | 0.544247E+09 | 0.558588E+10 | 0.892950E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2413562.58 | 0.199171E+10 |
June | 0.532585E+09 | 0.545059E+10 | 0.871243E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12427547.85 | 0.142633E+10 |
July | 0.536472E+09 | 0.549891E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110584E+09 | 0.972690E+09 |
August | 0.551374E+09 | 0.564387E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.248538E+09 | 0.791749E+09 |
September | 0.524810E+09 | 0.536361E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2958223.28 | 0.143298E+10 |
October | 0.537120E+09 | 0.552790E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.238980E+10 |
November | 0.518979E+09 | 0.536361E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.308374E+10 |
December | 0.536472E+09 | 0.549891E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.362514E+10 |
Annual Sum or Average | 0.638324E+10 | 0.654747E+11 | 0.104672E+11 | 0.398595E+09 | 0.279502E+11 | ||||
Minimum of Months | 0.487879E+09 | 0.500604E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.791749E+09 |
Maximum of Months | 0.551374E+09 | 0.564387E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.248538E+09 | 0.392850E+10 |
Report: SpaceGainsMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.537120E+09 | 0.552790E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.391940E+10 |
February | 0.487879E+09 | 0.500604E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.313143E+10 |
March | 0.551374E+09 | 0.564387E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.282946E+10 |
April | 0.524810E+09 | 0.536361E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21682846.20 | 0.224932E+10 |
May | 0.544247E+09 | 0.558588E+10 | 0.892950E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2413799.87 | 0.196489E+10 |
June | 0.532585E+09 | 0.545059E+10 | 0.871243E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12427517.31 | 0.141786E+10 |
July | 0.536472E+09 | 0.549891E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110617E+09 | 0.968057E+09 |
August | 0.551374E+09 | 0.564387E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.248561E+09 | 0.787457E+09 |
September | 0.524810E+09 | 0.536361E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2958123.36 | 0.142378E+10 |
October | 0.537120E+09 | 0.552790E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.233935E+10 |
November | 0.518979E+09 | 0.536361E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.305911E+10 |
December | 0.536472E+09 | 0.549891E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.361672E+10 |
Annual Sum or Average | 0.638324E+10 | 0.654747E+11 | 0.104672E+11 | 0.398661E+09 | 0.277068E+11 | ||||
Minimum of Months | 0.487879E+09 | 0.500604E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.787457E+09 |
Maximum of Months | 0.551374E+09 | 0.564387E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.248561E+09 | 0.391940E+10 |
Report: SpaceGainsMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.183632E+10 | 0.724555E+10 | 0.162546E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.702214E+10 |
February | 0.167188E+10 | 0.656305E+10 | 0.147229E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.559323E+10 |
March | 0.189386E+10 | 0.741101E+10 | 0.166213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.500741E+10 |
April | 0.180380E+10 | 0.703184E+10 | 0.157746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38165739.97 | 0.393304E+10 |
May | 0.186509E+10 | 0.732828E+10 | 0.164379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4234905.10 | 0.343432E+10 |
June | 0.182945E+10 | 0.715593E+10 | 0.160496E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21839026.03 | 0.256212E+10 |
July | 0.183943E+10 | 0.720419E+10 | 0.161629E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.194777E+09 | 0.177093E+10 |
August | 0.189386E+10 | 0.741101E+10 | 0.166213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.437098E+09 | 0.144994E+10 |
September | 0.180380E+10 | 0.703184E+10 | 0.157746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5189901.96 | 0.249879E+10 |
October | 0.183632E+10 | 0.724555E+10 | 0.162546E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.407495E+10 |
November | 0.176881E+10 | 0.703184E+10 | 0.157746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.543573E+10 |
December | 0.183943E+10 | 0.720419E+10 | 0.161629E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.646325E+10 |
Annual Sum or Average | 0.218821E+11 | 0.858643E+11 | 0.192612E+11 | 0.701305E+09 | 0.492458E+11 | ||||
Minimum of Months | 0.167188E+10 | 0.656305E+10 | 0.147229E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.144994E+10 |
Maximum of Months | 0.189386E+10 | 0.741101E+10 | 0.166213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.437098E+09 | 0.702214E+10 |
Report: SpaceGainsMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.918158E+09 | 0.362278E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.392274E+10 |
February | 0.835938E+09 | 0.328152E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.311671E+10 |
March | 0.946926E+09 | 0.370550E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.277560E+10 |
April | 0.901896E+09 | 0.351592E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21733965.23 | 0.215588E+10 |
May | 0.932542E+09 | 0.366414E+10 | 0.821897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2414136.27 | 0.187487E+10 |
June | 0.914724E+09 | 0.357797E+10 | 0.802482E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12428150.46 | 0.140302E+10 |
July | 0.919713E+09 | 0.360209E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110845E+09 | 0.965296E+09 |
August | 0.946926E+09 | 0.370550E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.248808E+09 | 0.786664E+09 |
September | 0.901896E+09 | 0.351592E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2960239.95 | 0.138898E+10 |
October | 0.918158E+09 | 0.362278E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.224485E+10 |
November | 0.884402E+09 | 0.351592E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.302865E+10 |
December | 0.919713E+09 | 0.360209E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.361781E+10 |
Annual Sum or Average | 0.109410E+11 | 0.429321E+11 | 0.963059E+10 | 0.399190E+09 | 0.272811E+11 | ||||
Minimum of Months | 0.835938E+09 | 0.328152E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.786664E+09 |
Maximum of Months | 0.946926E+09 | 0.370550E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.248808E+09 | 0.392274E+10 |
Report: SpaceGainsMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.918158E+09 | 0.362278E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.392016E+10 |
February | 0.835938E+09 | 0.328152E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.311284E+10 |
March | 0.946926E+09 | 0.370550E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.276826E+10 |
April | 0.901896E+09 | 0.351592E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21743155.60 | 0.214116E+10 |
May | 0.932542E+09 | 0.366414E+10 | 0.821897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2414078.82 | 0.185165E+10 |
June | 0.914724E+09 | 0.357797E+10 | 0.802482E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12428124.72 | 0.139541E+10 |
July | 0.919713E+09 | 0.360209E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110868E+09 | 0.962600E+09 |
August | 0.946926E+09 | 0.370550E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.248822E+09 | 0.784716E+09 |
September | 0.901896E+09 | 0.351592E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2960362.20 | 0.138095E+10 |
October | 0.918158E+09 | 0.362278E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.223011E+10 |
November | 0.884402E+09 | 0.351592E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.302356E+10 |
December | 0.919713E+09 | 0.360209E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.361572E+10 |
Annual Sum or Average | 0.109410E+11 | 0.429321E+11 | 0.963059E+10 | 0.399236E+09 | 0.271871E+11 | ||||
Minimum of Months | 0.835938E+09 | 0.328152E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.784716E+09 |
Maximum of Months | 0.946926E+09 | 0.370550E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.248822E+09 | 0.392016E+10 |
Report: SpaceGainsMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.918158E+09 | 0.362278E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.390935E+10 |
February | 0.835938E+09 | 0.328152E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.310038E+10 |
March | 0.946926E+09 | 0.370550E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.274956E+10 |
April | 0.901896E+09 | 0.351592E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21772699.31 | 0.210835E+10 |
May | 0.932542E+09 | 0.366414E+10 | 0.821897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2413928.68 | 0.180081E+10 |
June | 0.914724E+09 | 0.357797E+10 | 0.802482E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12428057.88 | 0.137297E+10 |
July | 0.919713E+09 | 0.360209E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110944E+09 | 0.954186E+09 |
August | 0.946926E+09 | 0.370550E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.248853E+09 | 0.778745E+09 |
September | 0.901896E+09 | 0.351592E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2960397.69 | 0.136012E+10 |
October | 0.918158E+09 | 0.362278E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.220024E+10 |
November | 0.884402E+09 | 0.351592E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.301099E+10 |
December | 0.919713E+09 | 0.360209E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.360716E+10 |
Annual Sum or Average | 0.109410E+11 | 0.429321E+11 | 0.963059E+10 | 0.399372E+09 | 0.269529E+11 | ||||
Minimum of Months | 0.835938E+09 | 0.328152E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.778745E+09 |
Maximum of Months | 0.946926E+09 | 0.370550E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.248853E+09 | 0.390935E+10 |
Report: SpaceGainsMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.918158E+09 | 0.362278E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.471800E+10 |
February | 0.835938E+09 | 0.328152E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.378443E+10 |
March | 0.946926E+09 | 0.370550E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.340570E+10 |
April | 0.901896E+09 | 0.351592E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 22881821.34 | 0.267715E+10 |
May | 0.932542E+09 | 0.366414E+10 | 0.821897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2480715.70 | 0.222822E+10 |
June | 0.914724E+09 | 0.357797E+10 | 0.802482E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12999451.86 | 0.177978E+10 |
July | 0.919713E+09 | 0.360209E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116242E+09 | 0.131374E+10 |
August | 0.946926E+09 | 0.370550E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.259741E+09 | 0.111335E+10 |
September | 0.901896E+09 | 0.351592E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3023784.86 | 0.157985E+10 |
October | 0.918158E+09 | 0.362278E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.273421E+10 |
November | 0.884402E+09 | 0.351592E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.365049E+10 |
December | 0.919713E+09 | 0.360209E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.429108E+10 |
Annual Sum or Average | 0.109410E+11 | 0.429321E+11 | 0.963059E+10 | 0.417368E+09 | 0.332760E+11 | ||||
Minimum of Months | 0.835938E+09 | 0.328152E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111335E+10 |
Maximum of Months | 0.946926E+09 | 0.370550E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.259741E+09 | 0.471800E+10 |
Report: PeakSpaceGainsMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2159.72 | 01-JAN-13:09 | 8262.19 | 01-JAN-10:09 | 1348.26 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 11073.09 | 07-JAN-12:10 |
February | 2159.72 | 03-FEB-13:09 | 8262.19 | 01-FEB-10:09 | 1348.26 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 11497.81 | 18-FEB-18:00 |
March | 2159.72 | 03-MAR-13:09 | 8262.19 | 01-MAR-10:09 | 1348.26 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 8318.97 | 22-MAR-11:10 |
April | 2159.72 | 01-APR-12:09 | 8262.19 | 01-APR-09:09 | 1348.26 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1622.03 | 01-APR-16:00 | 7205.19 | 18-APR-17:00 |
May | 2159.72 | 05-MAY-12:09 | 8262.19 | 01-MAY-09:09 | 1348.26 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 520.46 | 05-MAY-16:00 | 6879.67 | 23-MAY-17:00 |
June | 2159.72 | 02-JUN-12:09 | 8262.19 | 01-JUN-09:09 | 1348.26 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1324.58 | 28-JUN-17:00 | 6158.67 | 13-JUN-11:05 |
July | 2159.72 | 01-JUL-12:09 | 8262.19 | 01-JUL-09:09 | 1348.26 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3115.25 | 24-JUL-15:00 | 4945.53 | 09-JUL-13:00 |
August | 2159.72 | 04-AUG-12:09 | 8262.19 | 01-AUG-09:09 | 1348.26 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3619.14 | 10-AUG-17:00 | 5166.23 | 01-AUG-11:05 |
September | 2159.72 | 01-SEP-12:09 | 8262.19 | 01-SEP-09:09 | 1348.26 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 524.09 | 14-SEP-17:00 | 5917.75 | 16-SEP-11:05 |
October | 2159.72 | 01-OCT-12:09 | 8262.19 | 01-OCT-09:09 | 1348.26 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 | 6274.58 | 31-OCT-17:00 |
November | 2159.72 | 03-NOV-12:09 | 8262.19 | 01-NOV-09:09 | 1348.26 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 9145.90 | 12-NOV-17:00 |
December | 2159.72 | 01-DEC-13:09 | 8262.19 | 01-DEC-10:09 | 1348.26 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 10952.13 | 26-DEC-13:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2159.72 | 8262.19 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4945.53 | |||||
Maximum of Months | 2159.72 | 8262.19 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 3619.14 | 11497.81 |
Report: PeakSpaceGainsMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1079.86 | 01-JAN-13:09 | 4606.69 | 01-JAN-10:09 | 674.13 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 6267.69 | 07-JAN-12:10 |
February | 1079.86 | 03-FEB-13:09 | 4606.69 | 01-FEB-10:09 | 674.13 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 6364.89 | 18-FEB-18:00 |
March | 1079.86 | 03-MAR-13:09 | 4606.69 | 01-MAR-10:09 | 674.13 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 4609.32 | 22-MAR-11:10 |
April | 1079.86 | 01-APR-12:09 | 4606.69 | 01-APR-09:09 | 674.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 890.83 | 01-APR-16:00 | 3999.34 | 18-APR-17:00 |
May | 1079.86 | 05-MAY-12:09 | 4606.69 | 01-MAY-09:09 | 674.13 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 293.07 | 05-MAY-16:00 | 4004.22 | 23-MAY-17:00 |
June | 1079.86 | 02-JUN-12:09 | 4606.69 | 01-JUN-09:09 | 674.13 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 743.77 | 28-JUN-17:00 | 3525.57 | 13-JUN-11:05 |
July | 1079.86 | 01-JUL-12:09 | 4606.69 | 01-JUL-09:09 | 674.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1749.23 | 24-JUL-15:00 | 2776.94 | 09-JUL-13:00 |
August | 1079.86 | 04-AUG-12:09 | 4606.69 | 01-AUG-09:09 | 674.13 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2037.88 | 10-AUG-17:00 | 2886.18 | 01-AUG-11:05 |
September | 1079.86 | 01-SEP-12:09 | 4606.69 | 01-SEP-09:09 | 674.13 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 294.27 | 14-SEP-17:00 | 3345.70 | 16-SEP-11:05 |
October | 1079.86 | 01-OCT-12:09 | 4606.69 | 01-OCT-09:09 | 674.13 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 | 3672.24 | 29-OCT-11:05 |
November | 1079.86 | 03-NOV-12:09 | 4606.69 | 01-NOV-09:09 | 674.13 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 5149.93 | 12-NOV-17:00 |
December | 1079.86 | 01-DEC-13:09 | 4606.69 | 01-DEC-10:09 | 674.13 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 6122.92 | 26-DEC-12:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1079.86 | 4606.69 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2776.94 | |||||
Maximum of Months | 1079.86 | 4606.69 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 2037.88 | 6364.89 |
Report: PeakSpaceGainsMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1079.86 | 07-JAN-13:09 | 4250.44 | 01-JAN-10:09 | 674.13 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 6267.69 | 07-JAN-12:10 |
February | 1079.86 | 04-FEB-13:09 | 4250.44 | 01-FEB-09:09 | 674.13 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 6364.88 | 18-FEB-18:00 |
March | 1079.86 | 04-MAR-13:09 | 4250.44 | 01-MAR-09:09 | 674.13 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 4607.21 | 22-MAR-11:10 |
April | 1079.86 | 01-APR-12:09 | 4250.44 | 01-APR-08:09 | 674.13 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 890.82 | 01-APR-16:00 | 3999.33 | 18-APR-17:00 |
May | 1079.86 | 06-MAY-12:09 | 4250.44 | 01-MAY-08:09 | 674.13 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 293.07 | 05-MAY-16:00 | 3965.51 | 23-MAY-17:00 |
June | 1079.86 | 03-JUN-12:09 | 4250.44 | 01-JUN-08:09 | 674.13 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 743.76 | 28-JUN-17:00 | 3525.90 | 13-JUN-11:05 |
July | 1079.86 | 01-JUL-12:09 | 4250.44 | 01-JUL-08:09 | 674.13 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1749.23 | 24-JUL-15:00 | 2776.95 | 09-JUL-13:00 |
August | 1079.86 | 05-AUG-12:09 | 4250.44 | 01-AUG-08:09 | 674.13 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2037.87 | 10-AUG-17:00 | 2887.72 | 01-AUG-11:10 |
September | 1079.86 | 02-SEP-12:09 | 4250.44 | 01-SEP-08:09 | 674.13 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 294.27 | 14-SEP-17:00 | 3350.93 | 16-SEP-11:05 |
October | 1079.86 | 07-OCT-12:09 | 4250.44 | 01-OCT-09:09 | 674.13 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 | 3524.76 | 29-OCT-11:05 |
November | 1079.86 | 04-NOV-12:09 | 4250.44 | 01-NOV-08:09 | 674.13 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 5149.93 | 12-NOV-17:00 |
December | 1079.86 | 02-DEC-13:09 | 4250.44 | 01-DEC-09:09 | 674.13 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 6122.92 | 26-DEC-12:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1079.86 | 4250.44 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2776.95 | |||||
Maximum of Months | 1079.86 | 4250.44 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 2037.87 | 6364.88 |
Report: PeakSpaceGainsMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1079.86 | 07-JAN-13:09 | 4250.44 | 01-JAN-10:09 | 674.13 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 6267.69 | 07-JAN-12:10 |
February | 1079.86 | 04-FEB-13:09 | 4250.44 | 01-FEB-09:09 | 674.13 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 6364.88 | 18-FEB-18:00 |
March | 1079.86 | 04-MAR-13:09 | 4250.44 | 01-MAR-09:09 | 674.13 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 4607.21 | 22-MAR-11:10 |
April | 1079.86 | 01-APR-12:09 | 4250.44 | 01-APR-08:09 | 674.13 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 890.82 | 01-APR-16:00 | 3999.33 | 18-APR-17:00 |
May | 1079.86 | 06-MAY-12:09 | 4250.44 | 01-MAY-08:09 | 674.13 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 293.07 | 05-MAY-16:00 | 3939.90 | 23-MAY-17:00 |
June | 1079.86 | 03-JUN-12:09 | 4250.44 | 01-JUN-08:09 | 674.13 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 743.76 | 28-JUN-17:00 | 3524.69 | 13-JUN-11:05 |
July | 1079.86 | 01-JUL-12:09 | 4250.44 | 01-JUL-08:09 | 674.13 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1749.22 | 24-JUL-15:00 | 2776.95 | 09-JUL-13:00 |
August | 1079.86 | 05-AUG-12:09 | 4250.44 | 01-AUG-08:09 | 674.13 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2037.87 | 10-AUG-17:00 | 2887.72 | 01-AUG-11:10 |
September | 1079.86 | 02-SEP-12:09 | 4250.44 | 01-SEP-08:09 | 674.13 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 294.27 | 14-SEP-17:00 | 3350.80 | 16-SEP-11:05 |
October | 1079.86 | 07-OCT-12:09 | 4250.44 | 01-OCT-09:09 | 674.13 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 | 3443.91 | 29-OCT-11:05 |
November | 1079.86 | 04-NOV-12:09 | 4250.44 | 01-NOV-08:09 | 674.13 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 5149.93 | 12-NOV-17:00 |
December | 1079.86 | 02-DEC-13:09 | 4250.44 | 01-DEC-09:09 | 674.13 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 6122.92 | 26-DEC-12:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1079.86 | 4250.44 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2776.95 | |||||
Maximum of Months | 1079.86 | 4250.44 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 2037.87 | 6364.88 |
Report: PeakSpaceGainsMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1079.86 | 07-JAN-13:09 | 4250.44 | 01-JAN-10:09 | 674.13 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 6267.69 | 07-JAN-12:10 |
February | 1079.86 | 04-FEB-13:09 | 4250.44 | 01-FEB-09:09 | 674.13 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 6364.88 | 18-FEB-18:00 |
March | 1079.86 | 04-MAR-13:09 | 4250.44 | 01-MAR-09:09 | 674.13 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 4607.21 | 22-MAR-11:10 |
April | 1079.86 | 01-APR-12:09 | 4250.44 | 01-APR-08:09 | 674.13 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 890.81 | 01-APR-16:00 | 3999.33 | 18-APR-17:00 |
May | 1079.86 | 06-MAY-12:09 | 4250.44 | 01-MAY-08:09 | 674.13 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 293.06 | 05-MAY-16:00 | 3879.09 | 23-MAY-17:00 |
June | 1079.86 | 03-JUN-12:09 | 4250.44 | 01-JUN-08:09 | 674.13 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 743.76 | 28-JUN-17:00 | 3513.83 | 13-JUN-11:05 |
July | 1079.86 | 01-JUL-12:09 | 4250.44 | 01-JUL-08:09 | 674.13 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1749.22 | 24-JUL-15:00 | 2776.95 | 09-JUL-13:00 |
August | 1079.86 | 05-AUG-12:09 | 4250.44 | 01-AUG-08:09 | 674.13 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2037.87 | 10-AUG-17:00 | 2884.17 | 01-AUG-11:05 |
September | 1079.86 | 02-SEP-12:09 | 4250.44 | 01-SEP-08:09 | 674.13 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 294.26 | 14-SEP-17:00 | 3344.23 | 16-SEP-11:05 |
October | 1079.86 | 07-OCT-12:09 | 4250.44 | 01-OCT-09:09 | 674.13 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 | 3389.56 | 31-OCT-16:50 |
November | 1079.86 | 04-NOV-12:09 | 4250.44 | 01-NOV-08:09 | 674.13 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 5149.93 | 12-NOV-17:00 |
December | 1079.86 | 02-DEC-13:09 | 4250.44 | 01-DEC-09:09 | 674.13 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 6122.92 | 26-DEC-12:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1079.86 | 4250.44 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2776.95 | |||||
Maximum of Months | 1079.86 | 4250.44 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 2037.87 | 6364.88 |
Report: PeakSpaceGainsMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2879.63 | 07-JAN-15:09 | 6064.13 | 01-JAN-11:09 | 1348.26 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 10980.65 | 07-JAN-12:10 |
February | 2879.63 | 04-FEB-15:09 | 6064.13 | 01-FEB-10:09 | 1348.26 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 11187.35 | 18-FEB-18:00 |
March | 2879.63 | 04-MAR-15:09 | 6064.13 | 01-MAR-10:09 | 1348.26 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 8097.42 | 22-MAR-11:10 |
April | 2879.63 | 01-APR-14:09 | 6064.13 | 01-APR-09:09 | 1348.26 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1567.65 | 01-APR-16:00 | 7026.71 | 18-APR-17:00 |
May | 2879.63 | 06-MAY-14:09 | 6064.13 | 01-MAY-09:09 | 1348.26 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 513.84 | 05-MAY-16:00 | 6465.17 | 23-MAY-17:00 |
June | 2879.63 | 03-JUN-14:09 | 6064.13 | 01-JUN-09:09 | 1348.26 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1304.55 | 28-JUN-17:00 | 5904.47 | 13-JUN-11:05 |
July | 2879.63 | 01-JUL-14:09 | 6064.13 | 01-JUL-09:09 | 1348.26 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3068.18 | 24-JUL-15:00 | 4856.32 | 09-JUL-13:00 |
August | 2879.63 | 05-AUG-14:09 | 6064.13 | 01-AUG-09:09 | 1348.26 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3572.99 | 10-AUG-17:00 | 5027.03 | 01-AUG-11:05 |
September | 2879.63 | 02-SEP-14:09 | 6064.13 | 01-SEP-09:09 | 1348.26 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 516.23 | 14-SEP-17:00 | 5817.20 | 16-SEP-11:05 |
October | 2879.63 | 07-OCT-14:09 | 6064.13 | 01-OCT-10:09 | 1348.26 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 | 5983.29 | 31-OCT-17:00 |
November | 2879.63 | 04-NOV-14:09 | 6064.13 | 01-NOV-09:09 | 1348.26 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 9029.24 | 12-NOV-17:00 |
December | 2879.63 | 02-DEC-15:09 | 6064.13 | 01-DEC-10:09 | 1348.26 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 10742.65 | 26-DEC-12:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2879.63 | 6064.13 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4856.32 | |||||
Maximum of Months | 2879.63 | 6064.13 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 3572.99 | 11187.35 |
Report: PeakSpaceGainsMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1439.81 | 07-JAN-15:09 | 3032.07 | 01-JAN-11:09 | 674.13 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 6267.68 | 07-JAN-12:10 |
February | 1439.81 | 04-FEB-15:09 | 3032.07 | 01-FEB-10:09 | 674.13 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 6364.87 | 18-FEB-18:00 |
March | 1439.81 | 04-MAR-15:09 | 3032.07 | 01-MAR-10:09 | 674.13 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 4607.21 | 22-MAR-11:10 |
April | 1439.81 | 01-APR-14:09 | 3032.07 | 01-APR-09:09 | 674.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 890.83 | 01-APR-16:00 | 3999.32 | 18-APR-17:00 |
May | 1439.81 | 06-MAY-14:09 | 3032.07 | 01-MAY-09:09 | 674.13 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 293.08 | 05-MAY-16:00 | 3632.27 | 23-MAY-17:00 |
June | 1439.81 | 03-JUN-14:09 | 3032.07 | 01-JUN-09:09 | 674.13 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 743.76 | 28-JUN-17:00 | 3340.65 | 13-JUN-11:05 |
July | 1439.81 | 01-JUL-14:09 | 3032.07 | 01-JUL-09:09 | 674.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1749.25 | 24-JUL-15:00 | 2741.49 | 09-JUL-13:00 |
August | 1439.81 | 05-AUG-14:09 | 3032.07 | 01-AUG-09:09 | 674.13 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2037.89 | 10-AUG-17:00 | 2854.35 | 01-AUG-11:05 |
September | 1439.81 | 02-SEP-14:09 | 3032.07 | 01-SEP-09:09 | 674.13 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 294.32 | 14-SEP-17:00 | 3304.21 | 16-SEP-11:05 |
October | 1439.81 | 07-OCT-14:09 | 3032.07 | 01-OCT-10:09 | 674.13 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 | 3392.07 | 31-OCT-17:00 |
November | 1439.81 | 04-NOV-14:09 | 3032.07 | 01-NOV-09:09 | 674.13 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 5149.92 | 12-NOV-17:00 |
December | 1439.81 | 02-DEC-15:09 | 3032.07 | 01-DEC-10:09 | 674.13 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 6122.91 | 26-DEC-12:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1439.81 | 3032.07 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2741.49 | |||||
Maximum of Months | 1439.81 | 3032.07 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 2037.89 | 6364.87 |
Report: PeakSpaceGainsMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1439.81 | 07-JAN-15:09 | 3032.07 | 01-JAN-11:09 | 674.13 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 6267.68 | 07-JAN-12:10 |
February | 1439.81 | 04-FEB-15:09 | 3032.07 | 01-FEB-10:09 | 674.13 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 6364.87 | 18-FEB-18:00 |
March | 1439.81 | 04-MAR-15:09 | 3032.07 | 01-MAR-10:09 | 674.13 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 4607.21 | 22-MAR-11:10 |
April | 1439.81 | 01-APR-14:09 | 3032.07 | 01-APR-09:09 | 674.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 890.83 | 01-APR-16:00 | 3999.32 | 18-APR-17:00 |
May | 1439.81 | 06-MAY-14:09 | 3032.07 | 01-MAY-09:09 | 674.13 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 293.07 | 05-MAY-16:00 | 3619.12 | 23-MAY-17:00 |
June | 1439.81 | 03-JUN-14:09 | 3032.07 | 01-JUN-09:09 | 674.13 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 743.76 | 28-JUN-17:00 | 3317.44 | 13-JUN-11:05 |
July | 1439.81 | 01-JUL-14:09 | 3032.07 | 01-JUL-09:09 | 674.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1749.25 | 24-JUL-15:00 | 2724.47 | 09-JUL-13:00 |
August | 1439.81 | 05-AUG-14:09 | 3032.07 | 01-AUG-09:09 | 674.13 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2037.89 | 10-AUG-17:00 | 2851.45 | 01-AUG-11:05 |
September | 1439.81 | 02-SEP-14:09 | 3032.07 | 01-SEP-09:09 | 674.13 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 294.32 | 14-SEP-17:00 | 3288.30 | 16-SEP-11:05 |
October | 1439.81 | 07-OCT-14:09 | 3032.07 | 01-OCT-10:09 | 674.13 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 | 3392.07 | 31-OCT-17:00 |
November | 1439.81 | 04-NOV-14:09 | 3032.07 | 01-NOV-09:09 | 674.13 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 5149.92 | 12-NOV-17:00 |
December | 1439.81 | 02-DEC-15:09 | 3032.07 | 01-DEC-10:09 | 674.13 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 6122.91 | 26-DEC-12:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1439.81 | 3032.07 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2724.47 | |||||
Maximum of Months | 1439.81 | 3032.07 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 2037.89 | 6364.87 |
Report: PeakSpaceGainsMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1439.81 | 07-JAN-15:09 | 3032.07 | 01-JAN-11:09 | 674.13 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 6267.68 | 07-JAN-12:10 |
February | 1439.81 | 04-FEB-15:09 | 3032.07 | 01-FEB-10:09 | 674.13 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 6364.87 | 18-FEB-18:00 |
March | 1439.81 | 04-MAR-15:09 | 3032.07 | 01-MAR-10:09 | 674.13 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 4607.21 | 22-MAR-11:10 |
April | 1439.81 | 01-APR-14:09 | 3032.07 | 01-APR-09:09 | 674.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 890.83 | 01-APR-16:00 | 3999.32 | 18-APR-17:00 |
May | 1439.81 | 06-MAY-14:09 | 3032.07 | 01-MAY-09:09 | 674.13 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 293.07 | 05-MAY-16:00 | 3617.77 | 23-MAY-17:00 |
June | 1439.81 | 03-JUN-14:09 | 3032.07 | 01-JUN-09:09 | 674.13 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 743.76 | 28-JUN-17:00 | 3245.19 | 13-JUN-11:05 |
July | 1439.81 | 01-JUL-14:09 | 3032.07 | 01-JUL-09:09 | 674.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1749.25 | 24-JUL-15:00 | 2681.17 | 09-JUL-13:00 |
August | 1439.81 | 05-AUG-14:09 | 3032.07 | 01-AUG-09:09 | 674.13 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2037.89 | 10-AUG-17:00 | 2844.14 | 01-AUG-11:05 |
September | 1439.81 | 02-SEP-14:09 | 3032.07 | 01-SEP-09:09 | 674.13 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 294.53 | 14-SEP-17:00 | 3247.33 | 16-SEP-11:05 |
October | 1439.81 | 07-OCT-14:09 | 3032.07 | 01-OCT-10:09 | 674.13 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 | 3392.07 | 31-OCT-17:00 |
November | 1439.81 | 04-NOV-14:09 | 3032.07 | 01-NOV-09:09 | 674.13 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 5149.92 | 12-NOV-17:00 |
December | 1439.81 | 02-DEC-15:09 | 3032.07 | 01-DEC-10:09 | 674.13 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 6122.92 | 26-DEC-12:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1439.81 | 3032.07 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2681.17 | |||||
Maximum of Months | 1439.81 | 3032.07 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 2037.89 | 6364.87 |
Report: PeakSpaceGainsMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1439.81 | 07-JAN-15:09 | 3032.07 | 01-JAN-11:09 | 674.13 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 6359.97 | 07-JAN-12:10 |
February | 1439.81 | 04-FEB-15:09 | 3032.07 | 01-FEB-10:09 | 674.13 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 6674.91 | 18-FEB-18:00 |
March | 1439.81 | 04-MAR-15:09 | 3032.07 | 01-MAR-10:09 | 674.13 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 4828.45 | 22-MAR-11:10 |
April | 1439.81 | 01-APR-14:09 | 3032.07 | 01-APR-09:09 | 674.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 945.16 | 01-APR-16:00 | 4177.56 | 18-APR-17:00 |
May | 1439.81 | 06-MAY-14:09 | 3032.07 | 01-MAY-09:09 | 674.13 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 299.69 | 05-MAY-16:00 | 3745.68 | 23-MAY-17:00 |
June | 1439.81 | 03-JUN-14:09 | 3032.07 | 01-JUN-09:09 | 674.13 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 763.76 | 28-JUN-17:00 | 3189.81 | 13-JUN-11:05 |
July | 1439.81 | 01-JUL-14:09 | 3032.07 | 01-JUL-09:09 | 674.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1796.30 | 24-JUL-15:00 | 2610.24 | 09-JUL-13:00 |
August | 1439.81 | 05-AUG-14:09 | 3032.07 | 01-AUG-09:09 | 674.13 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2083.99 | 10-AUG-17:00 | 2927.65 | 01-AUG-11:05 |
September | 1439.81 | 02-SEP-14:09 | 3032.07 | 01-SEP-09:09 | 674.13 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 302.45 | 14-SEP-17:00 | 3175.79 | 16-SEP-11:05 |
October | 1439.81 | 07-OCT-14:09 | 3032.07 | 01-OCT-10:09 | 674.13 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 | 3682.96 | 31-OCT-17:00 |
November | 1439.81 | 04-NOV-14:09 | 3032.07 | 01-NOV-09:09 | 674.13 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 5273.74 | 29-NOV-18:00 |
December | 1439.81 | 02-DEC-15:09 | 3032.07 | 01-DEC-10:09 | 674.13 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 6350.04 | 26-DEC-13:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1439.81 | 3032.07 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2610.24 | |||||
Maximum of Months | 1439.81 | 3032.07 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 2083.99 | 6674.91 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 8092.37 | 07-JAN-00:25 | 359.95 | 8697.05 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 257.06 |
February | 7878.16 | 18-FEB-00:25 | 359.95 | 8697.05 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 251.42 |
March | 6388.70 | 01-MAR-23:00 | 1079.86 | 8262.19 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 156.84 |
April | 11841.41 | 27-APR-15:00 | 899.88 | 8262.19 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 1568.32 | 0.00 |
May | 11049.19 | 15-MAY-16:30 | 1799.77 | 8262.19 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 120.02 | 0.00 |
June | 12709.48 | 28-JUN-17:00 | 1799.77 | 8262.19 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 1324.58 | 0.00 |
July | 28508.28 | 24-JUL-07:03 | 719.91 | 1739.41 | 299.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 321.82 |
August | 27408.76 | 10-AUG-07:03 | 719.91 | 1739.41 | 299.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 325.47 |
September | 27318.93 | 14-SEP-07:02 | 1079.86 | 2609.11 | 449.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 669.78 |
October | 9938.84 | 04-OCT-14:50 | 899.88 | 8262.19 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1119.67 |
November | 7601.53 | 04-NOV-14:00 | 1439.81 | 8262.19 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1300.90 |
December | 7434.92 | 22-DEC-00:25 | 359.95 | 8697.05 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 392.88 |
Annual Sum or Average | |||||||||||
Minimum of Months | 6388.70 | 359.95 | 1739.41 | 299.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 28508.28 | 1799.77 | 8697.05 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 1568.32 | 1300.90 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3758.56 | 08-JAN-10:03 | 539.93 | 13820.07 | 2022.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1018.13 |
February | 3150.31 | 27-FEB-15:00 | 719.90 | 4606.69 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1053.09 |
March | 21593.39 | 18-MAR-18:08 | 8998.80 | 46066.91 | 6741.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 256.82 |
April | 21074.14 | 02-APR-17:27 | 9718.70 | 41460.22 | 6067.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 213.50 |
May | 23915.84 | 21-MAY-17:07 | 10798.56 | 46066.91 | 6741.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 343.53 |
June | 21278.08 | 03-JUN-19:57 | 2159.71 | 18426.77 | 2696.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.44 |
July | 21406.17 | 06-JUL-21:08 | 2159.71 | 18426.77 | 2696.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.87 |
August | 20944.99 | 01-AUG-07:01 | 719.90 | 1939.66 | 299.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 575.72 |
September | 20269.03 | 03-SEP-07:01 | 629.92 | 1697.20 | 262.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 418.52 |
October | 24224.06 | 03-OCT-20:07 | 5399.28 | 46066.91 | 6741.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.56 |
November | 5862.43 | 05-NOV-07:02 | 539.93 | 1454.74 | 224.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 489.43 |
December | 3171.74 | 06-DEC-20:10 | 539.93 | 4606.69 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.88 |
Annual Sum or Average | |||||||||||
Minimum of Months | 3150.31 | 539.93 | 1454.74 | 224.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.88 | |
Maximum of Months | 24224.06 | 10798.56 | 46066.91 | 6741.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1053.09 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2677.54 | 25-JAN-08:61 | 899.88 | 22370.74 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 729.81 |
February | 3564.11 | 10-FEB-08:61 | 899.88 | 22370.74 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 893.45 |
March | 3534.69 | 02-MAR-08:61 | 899.88 | 22370.74 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 914.61 |
April | 7191.21 | 30-APR-07:01 | 0.00 | 1565.95 | 262.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 504.48 |
May | 12898.06 | 05-MAY-06:02 | 0.00 | 1342.24 | 224.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.05 |
June | 15598.28 | 11-JUN-07:01 | 0.00 | 1565.95 | 262.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 486.63 |
July | 19597.01 | 25-JUL-06:02 | 0.00 | 1342.24 | 224.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.28 |
August | 21760.68 | 01-AUG-06:01 | 0.00 | 1565.95 | 262.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.60 |
September | 21408.15 | 14-SEP-06:01 | 0.00 | 1565.95 | 262.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5445.42 | 04-OCT-14:00 | 539.93 | 4250.44 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 754.85 |
November | 4286.20 | 04-NOV-14:00 | 719.90 | 4250.44 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 743.60 |
December | 3515.30 | 06-DEC-08:61 | 899.88 | 22370.74 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 867.61 |
Annual Sum or Average | |||||||||||
Minimum of Months | 2677.54 | 0.00 | 1342.24 | 224.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 21760.68 | 899.88 | 22370.74 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 914.61 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3595.10 | 21-JAN-10:33 | 539.93 | 12751.32 | 2022.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 982.79 |
February | 2953.67 | 16-FEB-10:03 | 539.93 | 12751.32 | 2022.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 959.96 |
March | 3456.37 | 02-MAR-08:61 | 899.88 | 22370.74 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 900.45 |
April | 6459.14 | 27-APR-15:00 | 359.95 | 4250.44 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 875.75 | 0.00 |
May | 11919.95 | 05-MAY-06:02 | 0.00 | 1342.24 | 224.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.05 |
June | 15075.47 | 11-JUN-07:01 | 0.00 | 1565.95 | 262.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 486.58 |
July | 19682.72 | 25-JUL-06:02 | 0.00 | 1342.24 | 224.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.46 |
August | 21841.91 | 01-AUG-06:01 | 0.00 | 1565.95 | 262.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.69 |
September | 21458.23 | 14-SEP-06:01 | 0.00 | 1565.95 | 262.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5360.59 | 04-OCT-14:00 | 539.93 | 4250.44 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 754.85 |
November | 3979.57 | 04-NOV-14:00 | 719.90 | 4250.44 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 743.60 |
December | 2753.95 | 30-DEC-08:61 | 719.90 | 17896.59 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 753.76 |
Annual Sum or Average | |||||||||||
Minimum of Months | 2753.95 | 0.00 | 1342.24 | 224.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 21841.91 | 899.88 | 22370.74 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 875.75 | 982.79 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2980.12 | 14-JAN-18:25 | 179.98 | 4474.15 | 749.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 991.18 |
February | 3098.76 | 13-FEB-11:53 | 539.93 | 12751.32 | 2022.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 957.24 |
March | 3371.26 | 02-MAR-08:61 | 899.88 | 22370.74 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 882.31 |
April | 6163.96 | 27-APR-15:00 | 359.95 | 4250.44 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 875.75 | 0.00 |
May | 8244.18 | 05-MAY-06:02 | 0.00 | 1342.24 | 224.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.04 |
June | 11628.13 | 29-JUN-06:02 | 0.00 | 1342.24 | 224.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.12 |
July | 17634.41 | 25-JUL-06:02 | 0.00 | 1342.24 | 224.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.23 |
August | 20986.66 | 15-AUG-06:02 | 0.00 | 1342.24 | 224.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.90 |
September | 20989.57 | 14-SEP-06:01 | 0.00 | 1565.95 | 262.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5152.74 | 04-OCT-14:00 | 539.93 | 4250.44 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 754.85 |
November | 3482.58 | 04-NOV-14:00 | 719.90 | 4250.44 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 743.61 |
December | 2705.07 | 30-DEC-08:61 | 719.90 | 17896.59 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 742.75 |
Annual Sum or Average | |||||||||||
Minimum of Months | 2705.07 | 0.00 | 1342.24 | 224.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 20989.57 | 899.88 | 22370.74 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 875.75 | 991.18 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6216.24 | 05-JAN-20:43 | 1187.85 | 9574.94 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 188.86 |
February | 3816.04 | 28-FEB-20:00 | 935.88 | 6064.13 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 973.34 |
March | 4633.71 | 01-MAR-19:10 | 935.88 | 6064.13 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1069.52 |
April | 10057.40 | 27-APR-15:00 | 2483.68 | 6064.13 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 1537.30 | 0.00 |
May | 9189.01 | 06-MAY-13:50 | 2771.64 | 6064.13 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 1.71 | 0.00 |
June | 11657.89 | 12-JUN-07:02 | 0.00 | 1595.82 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 678.54 |
July | 31113.83 | 24-JUL-07:03 | 0.00 | 1276.66 | 299.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 318.22 |
August | 31967.15 | 14-AUG-07:02 | 0.00 | 1595.82 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 547.63 |
September | 22724.09 | 14-SEP-07:02 | 0.00 | 1914.99 | 449.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 669.23 |
October | 8636.87 | 04-OCT-14:40 | 2483.68 | 6064.13 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1139.42 |
November | 5046.18 | 12-NOV-11:35 | 791.90 | 12128.26 | 2696.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1252.21 |
December | 5078.24 | 22-DEC-20:45 | 791.90 | 6383.30 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 430.25 |
Annual Sum or Average | |||||||||||
Minimum of Months | 3816.04 | 0.00 | 1276.66 | 299.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 31967.15 | 2771.64 | 12128.26 | 2696.51 | 0.00 | 0.00 | 0.00 | 0.00 | 1537.30 | 1252.21 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3134.26 | 05-JAN-19:43 | 1403.81 | 9096.20 | 2022.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 857.60 |
February | 2661.73 | 14-FEB-20:15 | 395.95 | 3191.65 | 749.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 128.74 |
March | 2231.30 | 01-MAR-09:35 | 395.95 | 3191.65 | 749.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 656.09 |
April | 5154.70 | 27-APR-15:00 | 1241.83 | 3032.07 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 875.75 | 0.00 |
May | 4664.59 | 06-MAY-13:50 | 1385.82 | 3032.07 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.96 | 0.00 |
June | 5656.62 | 28-JUN-15:00 | 1241.83 | 3032.07 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 590.81 | 0.00 |
July | 14669.45 | 24-JUL-07:03 | 0.00 | 638.33 | 149.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 181.01 |
August | 16438.23 | 14-AUG-07:02 | 0.00 | 797.91 | 187.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 304.71 |
September | 9465.46 | 14-SEP-07:02 | 0.00 | 957.49 | 224.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 382.40 |
October | 4366.77 | 04-OCT-14:40 | 1241.83 | 3032.07 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 648.71 |
November | 2998.86 | 13-NOV-10:53 | 593.92 | 9096.20 | 2022.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 786.51 |
December | 2648.49 | 18-DEC-19:35 | 935.88 | 6064.13 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 776.29 |
Annual Sum or Average | |||||||||||
Minimum of Months | 2231.30 | 0.00 | 638.33 | 149.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16438.23 | 1403.81 | 9096.20 | 2022.38 | 0.00 | 0.00 | 0.00 | 0.00 | 875.75 | 857.60 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3498.36 | 06-JAN-18:53 | 1835.76 | 9096.20 | 2022.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 885.83 |
February | 2045.48 | 05-FEB-11:55 | 395.95 | 6064.13 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 630.70 |
March | 2383.68 | 24-MAR-09:35 | 395.95 | 6064.13 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 807.38 |
April | 4996.61 | 27-APR-15:00 | 1241.83 | 3032.07 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 875.74 | 0.00 |
May | 4561.54 | 06-MAY-13:50 | 1385.82 | 3032.07 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.96 | 0.00 |
June | 5571.87 | 28-JUN-15:00 | 1241.83 | 3032.07 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 590.81 | 0.00 |
July | 13847.01 | 24-JUL-07:03 | 0.00 | 638.33 | 149.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 180.75 |
August | 16168.42 | 14-AUG-07:02 | 0.00 | 797.91 | 187.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 302.63 |
September | 8408.02 | 14-SEP-07:02 | 0.00 | 957.49 | 224.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 382.27 |
October | 4242.08 | 04-OCT-14:50 | 1241.83 | 3032.07 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 622.09 |
November | 2229.95 | 24-NOV-10:25 | 395.95 | 6064.13 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 678.40 |
December | 2481.32 | 22-DEC-20:35 | 395.95 | 3191.65 | 749.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 195.30 |
Annual Sum or Average | |||||||||||
Minimum of Months | 2045.48 | 0.00 | 638.33 | 149.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16168.42 | 1835.76 | 9096.20 | 2022.38 | 0.00 | 0.00 | 0.00 | 0.00 | 875.74 | 885.83 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3398.49 | 06-JAN-20:03 | 593.92 | 4787.47 | 1123.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.43 |
February | 2783.55 | 06-FEB-20:55 | 395.95 | 3191.65 | 749.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.41 |
March | 2603.97 | 22-MAR-10:05 | 1547.79 | 6064.13 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 862.11 |
April | 4685.16 | 27-APR-15:00 | 1241.83 | 3032.07 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 875.74 | 0.00 |
May | 4323.60 | 06-MAY-13:50 | 1385.82 | 3032.07 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.95 | 0.00 |
June | 5390.53 | 28-JUN-16:50 | 1277.83 | 3032.07 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 718.51 | 0.00 |
July | 11079.01 | 24-JUL-07:03 | 0.00 | 638.33 | 149.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 179.97 |
August | 13142.63 | 14-AUG-07:02 | 0.00 | 797.91 | 187.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 302.12 |
September | 5642.63 | 14-SEP-14:10 | 1241.83 | 3032.07 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1.02 | 0.00 |
October | 3958.64 | 04-OCT-14:50 | 1241.83 | 3032.07 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 622.09 |
November | 2546.39 | 30-NOV-20:25 | 395.95 | 3191.65 | 749.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 126.27 |
December | 3173.00 | 21-DEC-18:33 | 1835.76 | 9096.20 | 2022.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 848.62 |
Annual Sum or Average | |||||||||||
Minimum of Months | 2546.39 | 0.00 | 638.33 | 149.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13142.63 | 1835.76 | 9096.20 | 2022.38 | 0.00 | 0.00 | 0.00 | 0.00 | 875.74 | 862.11 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 371.27 | 11-JAN-18:10 | 1223.84 | 6064.13 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 519.91 |
February | 1252.56 | 28-FEB-18:10 | 1223.84 | 6064.13 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 534.66 |
March | 1600.45 | 02-MAR-12:00 | 773.90 | 3032.07 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 510.87 |
April | 4285.60 | 27-APR-15:00 | 1241.83 | 3032.07 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 906.71 | 0.00 |
May | 3869.20 | 06-MAY-13:50 | 1385.82 | 3032.07 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.98 | 0.00 |
June | 5027.81 | 28-JUN-15:00 | 1241.83 | 3032.07 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 614.18 | 0.00 |
July | 7323.75 | 24-JUL-15:00 | 1241.83 | 3032.07 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1796.30 | 0.00 |
August | 7647.13 | 10-AUG-16:40 | 1277.83 | 3032.07 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 2022.70 | 0.00 |
September | 5506.65 | 14-SEP-14:10 | 1241.83 | 3032.07 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1.04 | 0.00 |
October | 3359.35 | 04-OCT-14:50 | 1241.83 | 3032.07 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 648.87 |
November | 2297.02 | 21-NOV-20:05 | 395.95 | 3191.65 | 749.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.23 |
December | 1513.20 | 29-DEC-19:05 | 935.88 | 6064.13 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 620.78 |
Annual Sum or Average | |||||||||||
Minimum of Months | 371.27 | 395.95 | 3032.07 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7647.13 | 1385.82 | 6064.13 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 2022.70 | 648.87 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | |
January | 0.108745E+12 | 84261.37 | 04-JAN-19:30 | 0.842861E+11 | 150284.59 | 16-JAN-09:09 |
February | 0.975114E+11 | 82997.79 | 17-FEB-17:00 | 0.547525E+11 | 152633.90 | 19-FEB-09:09 |
March | 0.107921E+12 | 80921.05 | 02-MAR-19:30 | 0.242969E+11 | 91368.99 | 05-MAR-09:09 |
April | 0.103526E+12 | 98757.75 | 27-APR-14:00 | 0.764459E+10 | 63913.17 | 19-APR-07:10 |
May | 0.107628E+12 | 97192.96 | 06-MAY-13:00 | 0.830863E+09 | 20876.46 | 18-MAY-08:39 |
June | 0.106519E+12 | 99877.66 | 28-JUN-16:49 | 17976987.27 | 5117.55 | 14-JUN-07:10 |
July | 0.115777E+12 | 109643.08 | 24-JUL-14:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.123316E+12 | 112644.66 | 29-AUG-13:39 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 0.107988E+12 | 100155.91 | 14-SEP-13:39 | 24988927.17 | 4454.74 | 28-SEP-07:10 |
October | 0.107585E+12 | 84240.53 | 04-OCT-14:00 | 0.397776E+10 | 36327.28 | 31-OCT-07:10 |
November | 0.105101E+12 | 81600.36 | 15-NOV-19:40 | 0.385385E+11 | 103541.95 | 12-NOV-17:00 |
December | 0.108792E+12 | 82990.44 | 13-DEC-17:40 | 0.687296E+11 | 147615.99 | 26-DEC-12:09 |
Annual Sum or Average | 0.130041E+13 | 0.283100E+12 | ||||
Minimum of Months | 0.975114E+11 | 80921.05 | 0.00 | 0.00 | ||
Maximum of Months | 0.123316E+12 | 112644.66 | 0.842861E+11 | 152633.90 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.595337E+11 | 0.120189E+11 | 0.108804E+11 | 0.00 | 0.207232E+11 | 0.00 | 0.00 | 44226.62 | 0.00 | 0.00 | 0.00 | 0.558859E+10 | 0.00 |
February | 0.539017E+11 | 0.990862E+10 | 0.985143E+10 | 0.00 | 0.187882E+11 | 0.00 | 0.00 | 1185653.65 | 0.00 | 0.00 | 0.00 | 0.506030E+10 | 0.00 |
March | 0.604219E+11 | 0.967179E+10 | 0.110523E+11 | 0.00 | 0.211582E+11 | 0.00 | 0.00 | 3642877.49 | 0.00 | 0.00 | 0.00 | 0.561302E+10 | 0.00 |
April | 0.577706E+11 | 0.805630E+10 | 0.105581E+11 | 0.00 | 0.203372E+11 | 0.00 | 0.00 | 0.146048E+10 | 0.00 | 0.00 | 0.00 | 0.534313E+10 | 0.00 |
May | 0.599558E+11 | 0.715552E+10 | 0.109629E+11 | 0.00 | 0.212966E+11 | 0.00 | 0.00 | 0.280811E+10 | 0.00 | 0.00 | 0.00 | 0.544852E+10 | 0.00 |
June | 0.584038E+11 | 0.629703E+10 | 0.106818E+11 | 0.00 | 0.208131E+11 | 0.00 | 0.00 | 0.509721E+10 | 0.00 | 0.00 | 0.00 | 0.522604E+10 | 0.00 |
July | 0.593665E+11 | 0.679605E+10 | 0.108460E+11 | 0.00 | 0.210820E+11 | 0.00 | 0.00 | 0.123728E+11 | 0.00 | 0.00 | 0.00 | 0.531369E+10 | 0.00 |
August | 0.603780E+11 | 0.780256E+10 | 0.110454E+11 | 0.00 | 0.214379E+11 | 0.00 | 0.00 | 0.173032E+11 | 0.00 | 0.00 | 0.00 | 0.534935E+10 | 0.00 |
September | 0.578145E+11 | 0.879215E+10 | 0.105649E+11 | 0.00 | 0.206055E+11 | 0.00 | 0.00 | 0.504155E+10 | 0.00 | 0.00 | 0.00 | 0.516964E+10 | 0.00 |
October | 0.595337E+11 | 0.104330E+11 | 0.108804E+11 | 0.00 | 0.210985E+11 | 0.00 | 0.00 | 0.237439E+09 | 0.00 | 0.00 | 0.00 | 0.540204E+10 | 0.00 |
November | 0.576828E+11 | 0.112788E+11 | 0.105443E+11 | 0.00 | 0.202112E+11 | 0.00 | 0.00 | 75700892.40 | 0.00 | 0.00 | 0.00 | 0.530805E+10 | 0.00 |
December | 0.594104E+11 | 0.123276E+11 | 0.108529E+11 | 0.00 | 0.206534E+11 | 0.00 | 0.00 | 8005.24 | 0.00 | 0.00 | 0.00 | 0.554720E+10 | 0.00 |
Annual Sum or Average | 0.704173E+12 | 0.110538E+12 | 0.128721E+12 | 0.248205E+12 | 0.00 | 0.444013E+11 | 0.643696E+11 | ||||||
Minimum of Months | 0.539017E+11 | 0.629703E+10 | 0.985143E+10 | 0.00 | 0.187882E+11 | 0.00 | 0.00 | 8005.24 | 0.00 | 0.00 | 0.00 | 0.506030E+10 | 0.00 |
Maximum of Months | 0.604219E+11 | 0.123276E+11 | 0.110523E+11 | 0.00 | 0.214379E+11 | 0.00 | 0.00 | 0.173032E+11 | 0.00 | 0.00 | 0.00 | 0.561302E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS [J] | COOLING:GAS [] | WATERSYSTEMS:GAS [] | COGENERATION:GAS [] | HUMIDIFIER:GAS [] | |
January | 0.00 | 0.00 | 0.842861E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.547525E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.242969E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.764459E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.830863E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 17976987.27 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 24988927.17 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.397776E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.385385E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.687296E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.283100E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.842861E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum}[W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum}[W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum}[W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum}[W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 43812.60 | 01-JAN-11:09 | 7048.38 | 01-JAN-00:10 | 8089.53 | 01-JAN-11:09 | 0.00 | 14352.07 | 01-JAN-13:30 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 43812.60 | 01-FEB-10:09 | 7048.38 | 01-FEB-00:10 | 8089.53 | 01-FEB-10:09 | 0.00 | 14352.07 | 01-FEB-08:39 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 43812.60 | 01-MAR-10:09 | 7048.38 | 01-MAR-00:10 | 8089.53 | 01-MAR-10:09 | 0.00 | 14352.07 | 01-MAR-08:00 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 43812.60 | 01-APR-09:09 | 7048.38 | 01-APR-00:10 | 8089.53 | 01-APR-09:09 | 0.00 | 14352.07 | 01-APR-12:09 | 0.00 | 0.00 | 01-APR-00:10 |
May | 43812.60 | 01-MAY-09:09 | 7048.38 | 01-MAY-00:10 | 8089.53 | 01-MAY-09:09 | 0.00 | 14352.07 | 01-MAY-13:20 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 43812.60 | 01-JUN-09:09 | 7048.38 | 01-JUN-00:10 | 8089.53 | 01-JUN-09:09 | 0.00 | 14352.07 | 01-JUN-08:50 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 43812.60 | 01-JUL-09:09 | 7048.38 | 01-JUL-00:10 | 8089.53 | 01-JUL-09:09 | 0.00 | 14352.07 | 01-JUL-07:49 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 43812.60 | 01-AUG-09:09 | 7048.38 | 01-AUG-00:10 | 8089.53 | 01-AUG-09:09 | 0.00 | 14352.07 | 01-AUG-09:09 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 43812.60 | 01-SEP-09:09 | 7048.38 | 01-SEP-00:10 | 8089.53 | 01-SEP-09:09 | 0.00 | 14352.07 | 01-SEP-08:39 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 43812.60 | 01-OCT-10:09 | 7048.38 | 01-OCT-00:10 | 8089.53 | 01-OCT-10:09 | 0.00 | 14352.07 | 01-OCT-16:19 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 43812.60 | 01-NOV-09:09 | 7048.38 | 01-NOV-00:10 | 8089.53 | 01-NOV-09:09 | 0.00 | 14352.07 | 02-NOV-08:30 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 43812.60 | 01-DEC-10:09 | 7048.38 | 01-DEC-00:10 | 8089.53 | 01-DEC-10:09 | 0.00 | 14352.07 | 01-DEC-09:20 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 43812.60 | 7048.38 | 8089.53 | 0.00 | 14352.07 | 0.00 | 0.00 | |||||
Maximum of Months | 43812.60 | 7048.38 | 8089.53 | 0.00 | 14352.07 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum}[W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum}[W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 66.43 | 11-JAN-23:10 | 0.00 | 0.00 | 0.00 | 11860.52 | 04-JAN-13:30 | 0.00 |
February | 657.02 | 28-FEB-21:10 | 0.00 | 0.00 | 0.00 | 11804.13 | 17-FEB-16:30 | 0.00 |
March | 824.43 | 18-MAR-18:10 | 0.00 | 0.00 | 0.00 | 11856.11 | 02-MAR-14:50 | 0.00 |
April | 27045.75 | 27-APR-14:00 | 0.00 | 0.00 | 0.00 | 7601.35 | 14-APR-12:09 | 0.00 |
May | 23804.51 | 06-MAY-12:00 | 0.00 | 0.00 | 0.00 | 9720.20 | 18-MAY-12:30 | 0.00 |
June | 27097.48 | 28-JUN-16:00 | 0.00 | 0.00 | 0.00 | 11615.51 | 27-JUN-13:09 | 0.00 |
July | 37937.43 | 24-JUL-14:00 | 0.00 | 0.00 | 0.00 | 11832.34 | 06-JUL-12:09 | 0.00 |
August | 40797.72 | 29-AUG-14:00 | 0.00 | 0.00 | 0.00 | 9707.09 | 21-AUG-12:00 | 0.00 |
September | 27878.36 | 14-SEP-13:00 | 0.00 | 0.00 | 0.00 | 7588.68 | 22-SEP-12:39 | 0.00 |
October | 12917.45 | 04-OCT-14:00 | 0.00 | 0.00 | 0.00 | 9693.31 | 28-OCT-14:20 | 0.00 |
November | 7733.80 | 04-NOV-13:00 | 0.00 | 0.00 | 0.00 | 9719.61 | 06-NOV-13:30 | 0.00 |
December | 6.54 | 03-DEC-23:10 | 0.00 | 0.00 | 0.00 | 9698.63 | 08-DEC-15:20 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.54 | 0.00 | 0.00 | 0.00 | 7588.68 | 0.00 | ||
Maximum of Months | 40797.72 | 0.00 | 0.00 | 0.00 | 11860.52 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 84261.37 | 04-JAN-19:30 | 43812.60 | 8089.53 | 7048.38 | 0.00 | 14352.07 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 82997.79 | 17-FEB-17:00 | 43812.60 | 8089.53 | 7048.38 | 0.00 | 14352.07 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 80921.05 | 02-MAR-19:30 | 43812.60 | 8089.53 | 7048.38 | 0.00 | 14352.07 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 98757.75 | 27-APR-14:00 | 43812.60 | 8089.53 | 0.00 | 0.00 | 14352.07 | 0.00 | 0.00 | 27045.75 | 0.00 |
May | 97192.96 | 06-MAY-13:00 | 43812.60 | 8089.53 | 0.00 | 0.00 | 14352.07 | 0.00 | 0.00 | 23347.36 | 0.00 |
June | 99877.66 | 28-JUN-16:49 | 43812.60 | 8089.53 | 0.00 | 0.00 | 14352.07 | 0.00 | 0.00 | 26902.87 | 0.00 |
July | 109643.08 | 24-JUL-14:00 | 43812.60 | 8089.53 | 0.00 | 0.00 | 14352.07 | 0.00 | 0.00 | 37937.43 | 0.00 |
August | 112644.66 | 29-AUG-13:39 | 43812.60 | 8089.53 | 0.00 | 0.00 | 14352.07 | 0.00 | 0.00 | 38918.99 | 0.00 |
September | 100155.91 | 14-SEP-13:39 | 43812.60 | 8089.53 | 0.00 | 0.00 | 14352.07 | 0.00 | 0.00 | 27285.59 | 0.00 |
October | 84240.53 | 04-OCT-14:00 | 43812.60 | 8089.53 | 0.00 | 0.00 | 14352.07 | 0.00 | 0.00 | 12917.45 | 0.00 |
November | 81600.36 | 15-NOV-19:40 | 43812.60 | 8089.53 | 7048.38 | 0.00 | 14352.07 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 82990.44 | 13-DEC-17:40 | 43812.60 | 8089.53 | 7048.38 | 0.00 | 14352.07 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 80921.05 | 43812.60 | 8089.53 | 0.00 | 0.00 | 14352.07 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 112644.66 | 43812.60 | 8089.53 | 7048.38 | 0.00 | 14352.07 | 0.00 | 0.00 | 38918.99 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS {Maximum}[W] | HEATING:GAS {TIMESTAMP} | COOLING:GAS [] | WATERSYSTEMS:GAS [] | COGENERATION:GAS [] | |
January | 0.00 | 0.00 | 150284.59 | 16-JAN-09:09 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 152633.90 | 19-FEB-09:09 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 91368.99 | 05-MAR-09:09 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 63913.17 | 19-APR-07:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 20876.46 | 18-MAY-08:39 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 5117.55 | 14-JUN-07:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 4454.74 | 28-SEP-07:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 36327.28 | 31-OCT-07:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 103541.95 | 12-NOV-17:00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 147615.99 | 26-DEC-12:09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 152633.90 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.50 | 20.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.50 | 20.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.33 | 20.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1.33 | 20.52 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.50 | 20.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 20.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.33 | 20.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.50 | 20.45 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.33 | 20.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 20.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.33 | 20.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.50 | 20.44 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.33 | 20.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.33 | 20.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.33 | 20.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.67 | 20.44 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.33 | 20.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.83 | 20.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.50 | 20.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.33 | 20.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1.67 | 20.43 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.83 | 20.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 4.50 | 20.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3.00 | 19.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 1.17 | 20.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.17 | 20.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.17 | 20.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 2.00 | 20.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 11.00 | 20.08 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 4.50 | 20.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: LGSTORE1
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 496.00 | 21.11 | 60.33 | 20.97 | 60.33 | 20.97 |
February | 438.00 | 21.29 | 42.67 | 20.99 | 42.67 | 20.99 |
March | 491.83 | 21.63 | 15.00 | 21.09 | 15.00 | 21.09 |
April | 376.17 | 22.21 | 35.50 | 23.65 | 3.00 | 21.16 |
May | 181.17 | 22.85 | 98.67 | 23.89 | 0.00 | 0.00 |
June | 49.67 | 23.35 | 233.83 | 23.89 | 0.00 | 0.00 |
July | 13.33 | 23.75 | 383.83 | 23.89 | 0.00 | 0.00 |
August | 6.83 | 23.65 | 437.00 | 23.89 | 0.00 | 0.00 |
September | 48.00 | 23.25 | 320.83 | 23.88 | 0.00 | 0.00 |
October | 309.33 | 22.45 | 48.83 | 23.89 | 0.00 | 0.00 |
November | 440.50 | 21.42 | 37.83 | 22.90 | 13.17 | 21.06 |
December | 496.00 | 21.11 | 39.83 | 20.97 | 39.83 | 20.97 |
Annual Sum or Average | 3346.83 | 21.67 | 1754.17 | 23.60 | 174.00 | 21.00 |
Minimum of Months | 6.83 | 21.11 | 15.00 | 20.97 | 0.00 | 0.00 |
Maximum of Months | 496.00 | 23.75 | 437.00 | 23.89 | 60.33 | 21.16 |
Report: ComfortReportSimple55Monthly
For: SMSTORE1
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 496.00 | 21.67 | 16.00 | 21.16 | 16.00 | 21.16 |
February | 422.67 | 21.89 | 14.67 | 21.15 | 14.67 | 21.15 |
March | 465.00 | 22.41 | 0.17 | 21.45 | 0.17 | 21.45 |
April | 290.67 | 22.79 | 53.17 | 23.85 | 0.00 | 0.00 |
May | 97.17 | 23.24 | 140.00 | 23.88 | 0.00 | 0.00 |
June | 18.83 | 23.67 | 267.50 | 23.88 | 0.00 | 0.00 |
July | 7.17 | 23.76 | 379.00 | 23.86 | 0.00 | 0.00 |
August | 0.17 | 23.34 | 431.33 | 23.86 | 0.00 | 0.00 |
September | 15.00 | 23.56 | 341.83 | 23.87 | 0.00 | 0.00 |
October | 222.67 | 22.95 | 65.67 | 23.89 | 0.00 | 0.00 |
November | 421.50 | 22.07 | 34.17 | 23.87 | 0.33 | 21.44 |
December | 496.00 | 21.77 | 4.50 | 21.27 | 4.50 | 21.27 |
Annual Sum or Average | 2952.83 | 22.18 | 1748.00 | 23.81 | 35.67 | 21.18 |
Minimum of Months | 0.17 | 21.67 | 0.17 | 21.15 | 0.00 | 0.00 |
Maximum of Months | 496.00 | 23.76 | 431.33 | 23.89 | 16.00 | 21.45 |
Report: ComfortReportSimple55Monthly
For: SMSTORE2
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 371.00 | 21.13 | 32.33 | 21.11 | 32.33 | 21.11 |
February | 328.00 | 21.35 | 20.50 | 21.11 | 20.50 | 21.11 |
March | 363.83 | 21.72 | 1.67 | 21.11 | 1.67 | 21.11 |
April | 259.17 | 22.32 | 39.17 | 24.03 | 0.00 | 0.00 |
May | 97.83 | 22.91 | 98.17 | 24.05 | 0.00 | 0.00 |
June | 17.00 | 23.41 | 211.83 | 24.06 | 0.00 | 0.00 |
July | 4.17 | 24.24 | 309.83 | 24.06 | 0.50 | 27.79 |
August | 1.00 | 25.75 | 352.17 | 24.05 | 0.50 | 27.93 |
September | 23.33 | 23.23 | 254.83 | 24.01 | 0.00 | 0.00 |
October | 222.50 | 22.53 | 45.00 | 24.00 | 0.00 | 0.00 |
November | 336.50 | 21.50 | 14.33 | 23.78 | 0.83 | 21.11 |
December | 369.00 | 21.15 | 14.17 | 21.11 | 14.17 | 21.11 |
Annual Sum or Average | 2393.33 | 21.68 | 1394.00 | 23.90 | 70.50 | 21.21 |
Minimum of Months | 1.00 | 21.13 | 1.67 | 21.11 | 0.00 | 0.00 |
Maximum of Months | 371.00 | 25.75 | 352.17 | 24.06 | 32.33 | 27.93 |
Report: ComfortReportSimple55Monthly
For: SMSTORE3
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 371.00 | 21.13 | 44.83 | 21.11 | 44.83 | 21.11 |
February | 329.50 | 21.32 | 26.17 | 21.11 | 26.17 | 21.11 |
March | 371.00 | 21.66 | 4.67 | 21.11 | 4.67 | 21.11 |
April | 273.00 | 22.25 | 32.33 | 24.02 | 0.00 | 0.00 |
May | 110.33 | 22.89 | 89.00 | 24.06 | 0.00 | 0.00 |
June | 18.33 | 23.39 | 207.17 | 24.06 | 0.00 | 0.00 |
July | 4.83 | 24.16 | 308.00 | 24.06 | 0.50 | 27.79 |
August | 1.33 | 25.71 | 351.83 | 24.05 | 0.67 | 27.87 |
September | 29.33 | 23.22 | 250.83 | 24.01 | 0.00 | 0.00 |
October | 231.33 | 22.37 | 42.00 | 23.99 | 0.00 | 0.00 |
November | 338.50 | 21.44 | 16.00 | 23.24 | 4.00 | 21.11 |
December | 369.00 | 21.14 | 21.83 | 21.11 | 21.83 | 21.11 |
Annual Sum or Average | 2447.50 | 21.65 | 1394.67 | 23.83 | 102.67 | 21.19 |
Minimum of Months | 1.33 | 21.13 | 4.67 | 21.11 | 0.00 | 0.00 |
Maximum of Months | 371.00 | 25.71 | 351.83 | 24.06 | 44.83 | 27.87 |
Report: ComfortReportSimple55Monthly
For: SMSTORE4
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 371.00 | 21.12 | 59.33 | 21.11 | 59.33 | 21.11 |
February | 334.33 | 21.31 | 33.33 | 21.11 | 33.33 | 21.11 |
March | 377.83 | 21.57 | 8.33 | 21.11 | 8.33 | 21.11 |
April | 292.50 | 22.13 | 28.00 | 24.05 | 0.00 | 0.00 |
May | 135.50 | 22.82 | 76.17 | 24.06 | 0.00 | 0.00 |
June | 29.17 | 23.35 | 189.50 | 24.06 | 0.00 | 0.00 |
July | 6.00 | 23.92 | 298.17 | 24.06 | 0.33 | 27.70 |
August | 2.67 | 24.31 | 347.33 | 24.05 | 0.50 | 27.86 |
September | 43.00 | 23.12 | 236.67 | 24.00 | 0.00 | 0.00 |
October | 249.67 | 22.19 | 34.00 | 23.99 | 0.00 | 0.00 |
November | 345.00 | 21.39 | 16.50 | 22.75 | 7.00 | 21.11 |
December | 369.00 | 21.12 | 33.00 | 21.11 | 33.00 | 21.11 |
Annual Sum or Average | 2555.67 | 21.63 | 1360.33 | 23.74 | 141.83 | 21.15 |
Minimum of Months | 2.67 | 21.12 | 8.33 | 21.11 | 0.00 | 0.00 |
Maximum of Months | 377.83 | 24.31 | 347.33 | 24.06 | 59.33 | 27.86 |
Report: ComfortReportSimple55Monthly
For: LGSTORE2
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.11 | 104.50 | 21.11 | 104.50 | 21.11 |
February | 308.00 | 21.22 | 70.50 | 21.11 | 70.50 | 21.11 |
March | 348.00 | 21.32 | 14.50 | 21.11 | 14.50 | 21.11 |
April | 290.00 | 21.83 | 19.17 | 23.68 | 1.83 | 21.11 |
May | 203.33 | 22.66 | 52.67 | 23.96 | 0.00 | 0.00 |
June | 53.33 | 23.16 | 125.67 | 23.95 | 0.00 | 0.00 |
July | 8.17 | 23.66 | 246.67 | 23.95 | 0.17 | 27.56 |
August | 5.33 | 23.65 | 300.67 | 23.93 | 0.33 | 27.69 |
September | 70.50 | 22.87 | 162.00 | 23.93 | 0.00 | 0.00 |
October | 260.33 | 21.86 | 13.83 | 23.90 | 0.00 | 0.00 |
November | 321.17 | 21.24 | 17.17 | 21.84 | 12.67 | 21.11 |
December | 338.00 | 21.11 | 58.00 | 21.11 | 58.00 | 21.11 |
Annual Sum or Average | 2546.17 | 21.56 | 1185.33 | 23.31 | 262.50 | 21.12 |
Minimum of Months | 5.33 | 21.11 | 13.83 | 21.11 | 0.00 | 0.00 |
Maximum of Months | 348.00 | 23.66 | 300.67 | 23.96 | 104.50 | 27.69 |
Report: ComfortReportSimple55Monthly
For: SMSTORE5
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.11 | 108.67 | 21.11 | 108.67 | 21.11 |
February | 308.00 | 21.21 | 76.33 | 21.11 | 76.33 | 21.11 |
March | 348.00 | 21.30 | 18.83 | 21.11 | 18.83 | 21.11 |
April | 294.00 | 21.79 | 17.83 | 23.46 | 3.17 | 21.11 |
May | 223.33 | 22.63 | 42.83 | 23.97 | 0.00 | 0.00 |
June | 65.83 | 23.17 | 90.00 | 23.97 | 0.00 | 0.00 |
July | 11.33 | 23.61 | 225.83 | 23.96 | 0.00 | 0.00 |
August | 8.83 | 23.64 | 281.50 | 23.93 | 0.33 | 27.61 |
September | 82.00 | 22.87 | 145.17 | 23.93 | 0.00 | 0.00 |
October | 266.33 | 21.83 | 8.50 | 23.88 | 0.00 | 0.00 |
November | 322.33 | 21.23 | 18.50 | 21.69 | 14.67 | 21.11 |
December | 338.00 | 21.11 | 60.67 | 21.11 | 60.67 | 21.11 |
Annual Sum or Average | 2608.00 | 21.57 | 1094.67 | 23.21 | 282.67 | 21.12 |
Minimum of Months | 8.83 | 21.11 | 8.50 | 21.11 | 0.00 | 0.00 |
Maximum of Months | 348.00 | 23.64 | 281.50 | 23.97 | 108.67 | 27.61 |
Report: ComfortReportSimple55Monthly
For: SMSTORE6
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.11 | 116.67 | 21.11 | 116.67 | 21.11 |
February | 308.00 | 21.20 | 83.00 | 21.11 | 83.00 | 21.11 |
March | 348.00 | 21.28 | 21.33 | 21.11 | 21.33 | 21.11 |
April | 297.50 | 21.76 | 17.17 | 23.33 | 3.83 | 21.11 |
May | 233.67 | 22.55 | 38.00 | 23.98 | 0.00 | 0.00 |
June | 75.67 | 23.15 | 84.00 | 23.97 | 0.00 | 0.00 |
July | 14.50 | 23.60 | 221.17 | 23.96 | 0.00 | 0.00 |
August | 10.83 | 23.60 | 277.33 | 23.93 | 0.33 | 27.58 |
September | 89.50 | 22.83 | 138.83 | 23.93 | 0.00 | 0.00 |
October | 269.50 | 21.79 | 6.17 | 23.87 | 0.00 | 0.00 |
November | 323.33 | 21.22 | 19.83 | 21.58 | 16.50 | 21.11 |
December | 338.00 | 21.11 | 65.50 | 21.11 | 65.50 | 21.11 |
Annual Sum or Average | 2648.50 | 21.57 | 1089.00 | 23.15 | 307.17 | 21.12 |
Minimum of Months | 10.83 | 21.11 | 6.17 | 21.11 | 0.00 | 0.00 |
Maximum of Months | 348.00 | 23.60 | 277.33 | 23.98 | 116.67 | 27.58 |
Report: ComfortReportSimple55Monthly
For: SMSTORE7
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.11 | 144.83 | 21.11 | 144.83 | 21.11 |
February | 308.00 | 21.18 | 108.00 | 21.11 | 108.00 | 21.11 |
March | 348.00 | 21.24 | 31.50 | 21.11 | 31.50 | 21.11 |
April | 300.00 | 21.66 | 18.00 | 22.91 | 6.67 | 21.11 |
May | 250.00 | 22.38 | 32.50 | 23.97 | 0.00 | 0.00 |
June | 98.83 | 23.05 | 71.83 | 23.98 | 0.00 | 0.00 |
July | 23.33 | 23.50 | 209.17 | 23.96 | 0.00 | 0.00 |
August | 14.17 | 23.45 | 265.67 | 23.93 | 0.17 | 27.60 |
September | 109.00 | 22.74 | 126.33 | 23.93 | 0.00 | 0.00 |
October | 276.67 | 21.71 | 3.17 | 23.57 | 0.33 | 21.11 |
November | 324.00 | 21.20 | 23.33 | 21.31 | 21.67 | 21.11 |
December | 338.00 | 21.11 | 84.83 | 21.11 | 84.83 | 21.11 |
Annual Sum or Average | 2730.00 | 21.55 | 1119.17 | 22.94 | 398.00 | 21.11 |
Minimum of Months | 14.17 | 21.11 | 3.17 | 21.11 | 0.00 | 0.00 |
Maximum of Months | 348.00 | 23.50 | 265.67 | 23.98 | 144.83 | 27.60 |
Report: ComfortReportSimple55Monthly
For: SMSTORE8
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.11 | 255.00 | 21.11 | 255.00 | 21.11 |
February | 308.00 | 21.15 | 157.00 | 21.11 | 157.00 | 21.11 |
March | 348.00 | 21.18 | 81.50 | 21.11 | 81.50 | 21.11 |
April | 310.83 | 21.54 | 27.33 | 21.20 | 26.67 | 21.11 |
May | 278.83 | 22.04 | 21.33 | 23.80 | 1.33 | 21.11 |
June | 157.00 | 22.83 | 46.50 | 23.98 | 0.00 | 0.00 |
July | 56.00 | 23.24 | 175.50 | 23.96 | 0.00 | 0.00 |
August | 31.00 | 23.17 | 224.50 | 23.93 | 0.00 | 0.00 |
September | 149.67 | 22.49 | 105.00 | 23.94 | 0.00 | 0.00 |
October | 306.00 | 21.67 | 4.17 | 21.11 | 4.17 | 21.11 |
November | 324.67 | 21.16 | 63.83 | 21.11 | 63.83 | 21.11 |
December | 338.00 | 21.11 | 192.33 | 21.11 | 192.33 | 21.11 |
Annual Sum or Average | 2948.00 | 21.54 | 1354.00 | 22.31 | 781.83 | 21.11 |
Minimum of Months | 31.00 | 21.11 | 4.17 | 21.11 | 0.00 | 0.00 |
Maximum of Months | 348.00 | 23.24 | 255.00 | 23.98 | 255.00 | 21.11 |
Report: OccupantComfortDataSummaryMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 496.00000 | 21.09638 | 29.08543 | -0.4450 | 9.33639 |
February | 448.00000 | 21.33720 | 30.40974 | -0.3557 | 8.58634 |
March | 496.00000 | 21.64460 | 31.34226 | -0.2385 | 6.99481 |
April | 480.00000 | 22.54971 | 34.28787 | 0.01934 | 6.49854 |
May | 496.00000 | 23.47556 | 37.43790 | -0.6320 | 14.65559 |
June | 480.00000 | 23.81607 | 39.14670 | -0.4703 | 9.97622 |
July | 496.00000 | 23.88508 | 43.38744 | -0.3760 | 8.19990 |
August | 496.00000 | 23.88534 | 46.51770 | -0.3486 | 7.75487 |
September | 480.00000 | 23.79650 | 44.74829 | -0.4330 | 9.39170 |
October | 496.00000 | 22.97808 | 37.63280 | 0.15918 | 6.54823 |
November | 480.00000 | 21.61274 | 36.98876 | -0.2158 | 7.41874 |
December | 496.00000 | 21.10717 | 31.28067 | -0.4094 | 8.65054 |
Annual Sum or Average | 5840.00000 | 22.60529 | 36.88721 | -0.3122 | 8.67212 |
Minimum of Months | 448.00000 | 21.09638 | 29.08543 | -0.6320 | 6.49854 |
Maximum of Months | 496.00000 | 23.88534 | 46.51770 | 0.15918 | 14.65559 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 496.00000 | 21.64564 | 29.53220 | -0.2980 | 7.45927 |
February | 448.00000 | 21.97229 | 30.27749 | -0.1965 | 7.16100 |
March | 496.00000 | 22.47844 | 30.46684 | -0.0461 | 6.09220 |
April | 480.00000 | 23.19481 | 33.26939 | 0.17213 | 6.58748 |
May | 496.00000 | 23.72881 | 36.82051 | -0.5330 | 11.51215 |
June | 480.00000 | 23.84245 | 38.89742 | -0.4425 | 9.27714 |
July | 496.00000 | 23.85158 | 43.08848 | -0.3778 | 8.19423 |
August | 496.00000 | 23.84781 | 46.13603 | -0.3522 | 7.78035 |
September | 480.00000 | 23.83894 | 44.35440 | -0.4077 | 8.74061 |
October | 496.00000 | 23.44962 | 36.68843 | 0.26840 | 7.02693 |
November | 480.00000 | 22.26790 | 36.61020 | -0.0637 | 6.63105 |
December | 496.00000 | 21.74462 | 31.50758 | -0.2522 | 6.99665 |
Annual Sum or Average | 5840.00000 | 22.99367 | 36.50179 | -0.2112 | 7.79318 |
Minimum of Months | 448.00000 | 21.64564 | 29.53220 | -0.5330 | 6.09220 |
Maximum of Months | 496.00000 | 23.85158 | 46.13603 | 0.26840 | 11.51215 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 21.13333 | 29.29690 | -0.4169 | 8.77553 |
February | 336.00000 | 21.41591 | 30.29233 | -0.3174 | 8.03755 |
March | 379.00000 | 21.81293 | 30.75330 | -0.1823 | 6.58824 |
April | 360.00000 | 22.76320 | 33.55792 | 0.07913 | 6.53100 |
May | 375.00000 | 23.64844 | 37.03468 | -0.5606 | 12.57812 |
June | 366.00000 | 23.93454 | 38.43439 | -0.4236 | 9.06664 |
July | 369.00000 | 24.00120 | 43.15923 | -0.3358 | 7.71861 |
August | 379.00000 | 24.00532 | 46.36216 | -0.3058 | 7.29565 |
September | 360.00000 | 23.88477 | 44.21202 | -0.4002 | 8.83384 |
October | 371.00000 | 23.08078 | 36.91626 | 0.18707 | 6.64390 |
November | 360.00000 | 21.66118 | 36.70415 | -0.1951 | 7.13168 |
December | 369.00000 | 21.15003 | 31.08736 | -0.3855 | 8.22376 |
Annual Sum or Average | 4395.00000 | 22.71777 | 36.52622 | -0.2717 | 8.12284 |
Minimum of Months | 336.00000 | 21.13333 | 29.29690 | -0.5606 | 6.53100 |
Maximum of Months | 379.00000 | 24.00532 | 46.36216 | 0.18707 | 12.57812 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 21.12709 | 29.30978 | -0.4322 | 9.05117 |
February | 336.00000 | 21.37208 | 30.39923 | -0.3387 | 8.22997 |
March | 379.00000 | 21.71204 | 30.94523 | -0.2144 | 6.78527 |
April | 360.00000 | 22.64147 | 33.79958 | 0.04437 | 6.54400 |
May | 375.00000 | 23.60734 | 37.13462 | -0.5808 | 13.17565 |
June | 366.00000 | 23.92878 | 38.45259 | -0.4289 | 9.17237 |
July | 369.00000 | 23.99973 | 43.17065 | -0.3379 | 7.75311 |
August | 379.00000 | 24.00425 | 46.36957 | -0.3071 | 7.31294 |
September | 360.00000 | 23.87333 | 44.25492 | -0.4077 | 8.99628 |
October | 371.00000 | 22.94754 | 37.22484 | 0.15119 | 6.56824 |
November | 360.00000 | 21.59163 | 36.88389 | -0.2212 | 7.26822 |
December | 369.00000 | 21.13696 | 31.10917 | -0.4007 | 8.47106 |
Annual Sum or Average | 4395.00000 | 22.67204 | 36.62958 | -0.2898 | 8.28192 |
Minimum of Months | 336.00000 | 21.12709 | 29.30978 | -0.5808 | 6.54400 |
Maximum of Months | 379.00000 | 24.00425 | 46.36957 | 0.15119 | 13.17565 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 21.12092 | 29.32346 | -0.4489 | 9.36125 |
February | 336.00000 | 21.31929 | 30.53225 | -0.3631 | 8.47361 |
March | 379.00000 | 21.58065 | 31.20544 | -0.2547 | 7.05501 |
April | 360.00000 | 22.45823 | 34.16946 | -0.0060 | 6.57564 |
May | 375.00000 | 23.50413 | 37.38201 | -0.6260 | 14.56359 |
June | 366.00000 | 23.90510 | 38.52648 | -0.4465 | 9.54070 |
July | 369.00000 | 23.99358 | 43.22342 | -0.3482 | 7.90488 |
August | 379.00000 | 23.99799 | 46.42268 | -0.3170 | 7.44453 |
September | 360.00000 | 23.83700 | 44.38564 | -0.4290 | 9.46959 |
October | 371.00000 | 22.74859 | 37.69249 | 0.09861 | 6.50172 |
November | 360.00000 | 21.49531 | 37.13762 | -0.2541 | 7.41740 |
December | 369.00000 | 21.12510 | 31.13043 | -0.4168 | 8.74619 |
Annual Sum or Average | 4395.00000 | 22.60065 | 36.80266 | -0.3179 | 8.59423 |
Minimum of Months | 336.00000 | 21.12092 | 29.32346 | -0.6260 | 6.50172 |
Maximum of Months | 379.00000 | 23.99799 | 46.42268 | 0.09861 | 14.56359 |
Report: OccupantComfortDataSummaryMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.11077 | 30.08539 | -0.5003 | 10.35482 |
February | 308.00000 | 21.21874 | 31.49891 | -0.4241 | 9.26941 |
March | 348.00000 | 21.32151 | 32.41636 | -0.3388 | 7.83044 |
April | 330.00000 | 22.08131 | 35.54319 | -0.1078 | 6.76085 |
May | 344.00000 | 23.16361 | 38.74384 | -0.7546 | 18.74154 |
June | 336.00000 | 23.77665 | 39.21350 | -0.5106 | 10.88970 |
July | 338.00000 | 23.91269 | 43.92441 | -0.3895 | 8.45776 |
August | 348.00000 | 23.90439 | 47.01803 | -0.3621 | 7.97935 |
September | 330.00000 | 23.65126 | 45.44938 | -0.5070 | 11.31237 |
October | 340.00000 | 22.33050 | 39.25942 | -0.0106 | 6.53985 |
November | 330.00000 | 21.30611 | 38.36035 | -0.3295 | 8.00360 |
December | 338.00000 | 21.11091 | 31.87127 | -0.4653 | 9.62328 |
Annual Sum or Average | 4030.00000 | 22.41737 | 37.82409 | -0.3921 | 9.65850 |
Minimum of Months | 308.00000 | 21.11077 | 30.08539 | -0.7546 | 6.53985 |
Maximum of Months | 348.00000 | 23.91269 | 47.01803 | -0.0106 | 18.74154 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.11083 | 30.01780 | -0.5039 | 10.42815 |
February | 308.00000 | 21.21043 | 31.44960 | -0.4331 | 9.39531 |
March | 348.00000 | 21.29956 | 32.39624 | -0.3563 | 8.04877 |
April | 330.00000 | 22.02218 | 35.59238 | -0.1364 | 6.87867 |
May | 344.00000 | 23.07680 | 38.88426 | -0.8061 | 20.54382 |
June | 336.00000 | 23.75744 | 39.23005 | -0.5416 | 11.61654 |
July | 338.00000 | 23.90957 | 43.93442 | -0.4171 | 8.91601 |
August | 348.00000 | 23.90314 | 47.03143 | -0.3889 | 8.38714 |
September | 330.00000 | 23.62353 | 45.50259 | -0.5388 | 12.07163 |
October | 340.00000 | 22.27513 | 39.32383 | -0.0378 | 6.57567 |
November | 330.00000 | 21.28981 | 38.34144 | -0.3426 | 8.13158 |
December | 338.00000 | 21.11060 | 31.80159 | -0.4703 | 9.71862 |
Annual Sum or Average | 4030.00000 | 22.39232 | 37.83467 | -0.4149 | 10.07457 |
Minimum of Months | 308.00000 | 21.11060 | 30.01780 | -0.8061 | 6.57567 |
Maximum of Months | 348.00000 | 23.90957 | 47.03143 | -0.0378 | 20.54382 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.11053 | 30.01902 | -0.5091 | 10.53903 |
February | 308.00000 | 21.20234 | 31.46999 | -0.4402 | 9.50619 |
March | 348.00000 | 21.27934 | 32.44083 | -0.3666 | 8.18065 |
April | 330.00000 | 21.97088 | 35.70139 | -0.1535 | 6.96674 |
May | 344.00000 | 22.98571 | 39.09521 | -0.8434 | 21.97418 |
June | 336.00000 | 23.73054 | 39.30621 | -0.5575 | 12.05709 |
July | 338.00000 | 23.90473 | 43.96416 | -0.4243 | 9.05556 |
August | 348.00000 | 23.90027 | 47.05732 | -0.3949 | 8.49307 |
September | 330.00000 | 23.58897 | 45.61269 | -0.5557 | 12.57753 |
October | 340.00000 | 22.21841 | 39.46044 | -0.0555 | 6.61575 |
November | 330.00000 | 21.27554 | 38.38297 | -0.3506 | 8.21749 |
December | 338.00000 | 21.11045 | 31.80232 | -0.4753 | 9.81839 |
Annual Sum or Average | 4030.00000 | 22.36626 | 37.90220 | -0.4277 | 10.35088 |
Minimum of Months | 308.00000 | 21.11045 | 30.01902 | -0.8434 | 6.61575 |
Maximum of Months | 348.00000 | 23.90473 | 47.05732 | -0.0555 | 21.97418 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.10947 | 30.02213 | -0.5251 | 10.89115 |
February | 308.00000 | 21.18479 | 31.51396 | -0.4597 | 9.84269 |
March | 348.00000 | 21.23901 | 32.53159 | -0.3902 | 8.51705 |
April | 330.00000 | 21.86480 | 35.93200 | -0.1893 | 7.19183 |
May | 344.00000 | 22.78955 | 39.55198 | -0.9210 | 25.10572 |
June | 336.00000 | 23.64951 | 39.52348 | -0.5976 | 13.26933 |
July | 338.00000 | 23.88808 | 44.04912 | -0.4408 | 9.40592 |
August | 348.00000 | 23.89066 | 47.12199 | -0.4069 | 8.72952 |
September | 330.00000 | 23.49936 | 45.88896 | -0.5942 | 13.81471 |
October | 340.00000 | 22.10760 | 39.73237 | -0.0894 | 6.69349 |
November | 330.00000 | 21.24984 | 38.45799 | -0.3681 | 8.44015 |
December | 338.00000 | 21.10961 | 31.80421 | -0.4899 | 10.11735 |
Annual Sum or Average | 4030.00000 | 22.30807 | 38.05423 | -0.4566 | 11.02314 |
Minimum of Months | 308.00000 | 21.10947 | 30.02213 | -0.9210 | 6.69349 |
Maximum of Months | 348.00000 | 23.89066 | 47.12199 | -0.0894 | 25.10572 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.10997 | 29.93815 | -0.5889 | 12.40381 |
February | 308.00000 | 21.15481 | 31.49880 | -0.5289 | 11.25952 |
March | 348.00000 | 21.17833 | 32.58288 | -0.4637 | 9.79017 |
April | 330.00000 | 21.66586 | 36.34352 | -0.2781 | 8.00767 |
May | 344.00000 | 22.38524 | 40.44857 | -1.0956 | 32.73732 |
June | 336.00000 | 23.39542 | 40.17936 | -0.7156 | 17.33142 |
July | 338.00000 | 23.80444 | 44.30825 | -0.4999 | 10.89210 |
August | 348.00000 | 23.84067 | 47.37139 | -0.4474 | 9.67944 |
September | 330.00000 | 23.25188 | 46.57349 | -0.6986 | 17.54022 |
October | 340.00000 | 21.88468 | 40.17979 | -0.1690 | 7.03733 |
November | 330.00000 | 21.20719 | 38.43957 | -0.4234 | 9.33480 |
December | 338.00000 | 21.10992 | 31.70198 | -0.5474 | 11.38888 |
Annual Sum or Average | 4030.00000 | 22.17472 | 38.34231 | -0.5387 | 13.14655 |
Minimum of Months | 308.00000 | 21.10992 | 29.93815 | -1.0956 | 7.03733 |
Maximum of Months | 348.00000 | 23.84067 | 47.37139 | -0.1690 | 32.73732 |
Report: DXReportMonthly
For: PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 1276.25 | 392.45 | 3.33 | 1251.16 | 25.10 | 0.00 | 0.00 | 27-FEB-20:40 | 0.00 | 01-FEB-00:10 | 0.30 | 27-FEB-20:40 | 0.28 | 27-FEB-20:40 | 0.02 | 27-FEB-20:40 | 0.09 | 27-FEB-20:40 | 0.00 | 01-FEB-00:10 |
March | 16880.22 | 5175.82 | 8.18 | 16880.22 | 0.00 | 0.00 | 0.00 | 18-MAR-14:00 | 0.00 | 01-MAR-00:10 | 3.82 | 18-MAR-14:00 | 3.82 | 18-MAR-14:00 | 0.00 | 18-MAR-13:50 | 1.17 | 18-MAR-14:00 | 0.00 | 01-MAR-00:10 |
April | 0.100887E+10 | 0.298117E+09 | 60.93 | 0.978717E+09 | 30152084.71 | 0.00 | 0.55 | 27-APR-15:00 | 0.00 | 01-APR-00:10 | 16468.34 | 27-APR-15:00 | 15784.88 | 27-APR-15:00 | 939.39 | 29-APR-15:00 | 4818.29 | 27-APR-15:00 | 0.00 | 01-APR-00:10 |
May | 0.205452E+10 | 0.591691E+09 | 172.13 | 0.185334E+10 | 0.201180E+09 | 0.00 | 0.49 | 06-MAY-13:00 | 0.00 | 01-MAY-00:10 | 15052.79 | 06-MAY-13:00 | 13488.49 | 15-MAY-17:00 | 2838.41 | 06-MAY-12:50 | 4205.71 | 06-MAY-13:00 | 0.00 | 01-MAY-00:10 |
June | 0.356876E+10 | 0.103309E+10 | 281.17 | 0.339696E+10 | 0.171801E+09 | 0.00 | 0.56 | 28-JUN-17:00 | 0.00 | 01-JUN-00:10 | 16705.76 | 28-JUN-17:00 | 16389.72 | 28-JUN-17:00 | 1493.43 | 21-JUN-17:10 | 4842.86 | 28-JUN-17:00 | 0.00 | 01-JUN-00:10 |
July | 0.886281E+10 | 0.253835E+10 | 370.49 | 0.779173E+10 | 0.107108E+10 | 0.00 | 0.90 | 24-JUL-07:03 | 0.00 | 01-JUL-00:05 | 30653.77 | 24-JUL-07:03 | 23626.15 | 24-JUL-07:03 | 7027.61 | 24-JUL-07:03 | 7311.15 | 24-JUL-07:03 | 0.00 | 01-JUL-00:05 |
August | 0.121517E+11 | 0.348381E+10 | 390.95 | 0.106957E+11 | 0.145597E+10 | 0.00 | 0.92 | 10-AUG-07:03 | 0.00 | 01-AUG-00:10 | 31893.92 | 10-AUG-07:03 | 23332.35 | 10-AUG-07:03 | 10704.45 | 26-AUG-07:02 | 7551.21 | 10-AUG-07:03 | 0.00 | 01-AUG-00:10 |
September | 0.352960E+10 | 0.998380E+09 | 249.85 | 0.293987E+10 | 0.589732E+09 | 0.00 | 0.68 | 14-SEP-07:02 | 0.00 | 01-SEP-00:10 | 21122.92 | 14-SEP-07:02 | 15230.10 | 14-SEP-17:00 | 8007.19 | 14-SEP-07:02 | 5400.15 | 14-SEP-07:02 | 0.00 | 01-SEP-00:10 |
October | 0.167431E+09 | 48702283.34 | 79.51 | 0.165017E+09 | 2413473.69 | 0.00 | 0.31 | 04-OCT-15:00 | 0.00 | 01-OCT-00:05 | 8379.45 | 04-OCT-15:00 | 8379.45 | 04-OCT-15:00 | 531.43 | 08-OCT-14:00 | 2392.85 | 04-OCT-15:00 | 0.00 | 01-OCT-00:05 |
November | 67617968.94 | 19854236.95 | 19.01 | 51602693.93 | 16015275.01 | 0.00 | 0.23 | 04-NOV-14:00 | 0.00 | 01-NOV-00:10 | 6444.06 | 04-NOV-14:00 | 5008.43 | 04-NOV-14:00 | 1435.62 | 04-NOV-14:00 | 1870.06 | 04-NOV-14:00 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.314113E+11 | 0.901200E+10 | 1635.56 | 0.278729E+11 | 0.353834E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.121517E+11 | 0.348381E+10 | 390.95 | 0.106957E+11 | 0.145597E+10 | 0.00 | 0.92 | 0.00 | 31893.92 | 23626.15 | 10704.45 | 7551.21 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 133719.19 | 44226.62 | 0.42 | 131365.25 | 2353.94 | 0.00 | 0.02 | 11-JAN-23:10 | 0.00 | 01-JAN-00:05 | 200.92 | 11-JAN-23:10 | 197.04 | 11-JAN-23:10 | 3.88 | 11-JAN-23:10 | 66.43 | 11-JAN-23:10 | 0.00 | 01-JAN-00:05 |
February | 3757515.74 | 1184602.07 | 8.00 | 3749660.50 | 7855.24 | 0.00 | 0.16 | 28-FEB-21:10 | 0.00 | 01-FEB-00:10 | 2064.97 | 28-FEB-21:10 | 2064.97 | 28-FEB-21:10 | 7.92 | 27-FEB-23:50 | 657.02 | 28-FEB-21:10 | 0.00 | 01-FEB-00:10 |
March | 11719579.71 | 3424351.49 | 18.80 | 11545620.48 | 173959.23 | 0.00 | 1.00 | 08-MAR-21:02 | 0.00 | 01-MAR-00:10 | 18295.39 | 08-MAR-21:02 | 18295.39 | 08-MAR-21:02 | 153.11 | 11-MAR-00:10 | 4218.39 | 08-MAR-21:02 | 0.00 | 01-MAR-00:10 |
April | 0.721261E+09 | 0.204427E+09 | 70.17 | 0.697587E+09 | 23674316.09 | 0.00 | 1.00 | 01-APR-18:31 | 0.00 | 01-APR-00:10 | 18616.26 | 29-APR-18:01 | 18337.89 | 02-APR-17:21 | 3507.13 | 29-APR-18:01 | 4364.02 | 01-APR-18:31 | 0.00 | 01-APR-00:10 |
May | 0.139597E+10 | 0.388587E+09 | 170.37 | 0.125864E+10 | 0.137324E+09 | 0.00 | 1.00 | 04-MAY-20:01 | 0.00 | 01-MAY-00:10 | 19336.01 | 07-MAY-17:02 | 18157.95 | 14-MAY-18:00 | 5919.86 | 06-MAY-19:13 | 4491.61 | 07-MAY-17:02 | 0.00 | 01-MAY-00:10 |
June | 0.252838E+10 | 0.700185E+09 | 254.70 | 0.238157E+10 | 0.146807E+09 | 0.00 | 1.00 | 03-JUN-18:01 | 0.00 | 01-JUN-00:10 | 19051.80 | 11-JUN-17:53 | 18411.61 | 27-JUN-20:55 | 4758.70 | 28-JUN-20:55 | 4462.35 | 10-JUN-18:01 | 0.00 | 01-JUN-00:10 |
July | 0.560446E+10 | 0.155184E+10 | 307.02 | 0.490566E+10 | 0.698800E+09 | 0.00 | 1.00 | 02-JUL-22:22 | 0.00 | 01-JUL-00:05 | 19799.59 | 15-JUL-18:02 | 18317.60 | 23-JUL-19:12 | 6584.55 | 15-JUL-21:23 | 4630.35 | 15-JUL-18:02 | 0.00 | 01-JUL-00:05 |
August | 0.740210E+10 | 0.205497E+10 | 330.05 | 0.649188E+10 | 0.910220E+09 | 0.00 | 1.00 | 01-AUG-20:15 | 0.00 | 01-AUG-00:10 | 19673.58 | 26-AUG-18:02 | 18662.62 | 08-AUG-21:57 | 7972.45 | 30-AUG-07:02 | 4666.24 | 24-AUG-20:50 | 0.00 | 01-AUG-00:10 |
September | 0.234419E+10 | 0.640575E+09 | 203.76 | 0.193725E+10 | 0.406943E+09 | 0.00 | 1.00 | 02-SEP-18:01 | 0.00 | 01-SEP-00:10 | 19523.12 | 23-SEP-18:02 | 18249.18 | 10-SEP-17:01 | 6810.79 | 14-SEP-07:02 | 4500.23 | 23-SEP-18:02 | 0.00 | 01-SEP-00:10 |
October | 0.132439E+09 | 38176989.16 | 88.87 | 0.130095E+09 | 2343262.48 | 0.00 | 1.00 | 02-OCT-20:02 | 0.00 | 01-OCT-00:05 | 18288.84 | 23-OCT-20:04 | 18095.32 | 14-OCT-22:02 | 1841.64 | 08-OCT-17:06 | 4218.74 | 23-OCT-20:04 | 0.00 | 01-OCT-00:05 |
November | 52277408.47 | 15247063.23 | 14.11 | 40467498.44 | 11809910.03 | 0.00 | 0.28 | 04-NOV-14:00 | 0.00 | 01-NOV-00:10 | 4376.56 | 04-NOV-14:00 | 3426.46 | 04-NOV-14:00 | 950.10 | 04-NOV-14:00 | 1252.60 | 04-NOV-14:00 | 0.00 | 01-NOV-00:10 |
December | 24189.29 | 8005.24 | 0.50 | 24189.29 | 0.00 | 0.00 | 0.00 | 03-DEC-23:10 | 0.00 | 01-DEC-00:05 | 19.82 | 03-DEC-23:10 | 19.82 | 03-DEC-23:10 | 0.00 | 01-DEC-00:05 | 6.54 | 03-DEC-23:10 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.201967E+11 | 0.559867E+10 | 1466.77 | 0.178586E+11 | 0.233810E+10 | 0.00 | ||||||||||||||
Minimum of Months | 24189.29 | 8005.24 | 0.42 | 24189.29 | 0.00 | 0.00 | 0.00 | 0.00 | 19.82 | 19.82 | 0.00 | 6.54 | 0.00 | |||||||
Maximum of Months | 0.740210E+10 | 0.205497E+10 | 330.05 | 0.649188E+10 | 0.910220E+09 | 0.00 | 1.00 | 0.00 | 19799.59 | 18662.62 | 7972.45 | 4666.24 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 912.71 | 280.64 | 3.67 | 900.88 | 11.83 | 0.00 | 0.00 | 27-FEB-12:00 | 0.00 | 01-FEB-00:10 | 0.23 | 27-FEB-12:00 | 0.23 | 27-FEB-12:00 | 0.01 | 27-FEB-19:30 | 0.07 | 27-FEB-12:00 | 0.00 | 01-FEB-00:10 |
March | 542841.83 | 165623.91 | 9.50 | 542748.03 | 93.80 | 0.00 | 0.03 | 18-MAR-16:00 | 0.00 | 01-MAR-00:10 | 350.25 | 18-MAR-16:00 | 350.25 | 18-MAR-16:00 | 0.02 | 10-MAR-13:10 | 106.64 | 18-MAR-16:00 | 0.00 | 01-MAR-00:10 |
April | 0.502045E+09 | 0.147597E+09 | 51.93 | 0.488408E+09 | 13637418.16 | 0.00 | 0.55 | 27-APR-15:00 | 0.00 | 01-APR-00:10 | 9067.76 | 27-APR-15:00 | 8735.57 | 27-APR-15:00 | 523.31 | 29-APR-14:50 | 2650.28 | 27-APR-15:00 | 0.00 | 01-APR-00:10 |
May | 0.101154E+10 | 0.290955E+09 | 139.67 | 0.916433E+09 | 95106874.63 | 0.00 | 0.51 | 06-MAY-13:00 | 0.00 | 01-MAY-00:10 | 8524.67 | 06-MAY-13:00 | 7175.82 | 15-MAY-16:30 | 1577.62 | 06-MAY-12:50 | 2370.91 | 06-MAY-13:00 | 0.00 | 01-MAY-00:10 |
June | 0.172145E+10 | 0.497982E+09 | 234.95 | 0.164973E+10 | 71722619.80 | 0.00 | 0.65 | 12-JUN-06:02 | 0.00 | 01-JUN-00:10 | 10809.40 | 12-JUN-06:02 | 8738.94 | 28-JUN-17:00 | 3766.85 | 12-JUN-06:02 | 2792.67 | 12-JUN-06:02 | 0.00 | 01-JUN-00:10 |
July | 0.400833E+10 | 0.114773E+10 | 271.66 | 0.355317E+10 | 0.455158E+09 | 0.00 | 1.00 | 25-JUL-06:02 | 0.00 | 01-JUL-00:05 | 18666.26 | 25-JUL-06:02 | 13208.72 | 24-JUL-06:03 | 6922.15 | 25-JUL-06:02 | 4314.33 | 25-JUL-06:02 | 0.00 | 01-JUL-00:05 |
August | 0.550282E+10 | 0.157793E+10 | 291.95 | 0.487210E+10 | 0.630719E+09 | 0.00 | 1.00 | 01-AUG-06:01 | 0.00 | 01-AUG-00:10 | 19287.11 | 25-AUG-06:03 | 13964.73 | 15-AUG-06:02 | 7481.30 | 26-AUG-06:02 | 4453.57 | 25-AUG-06:03 | 0.00 | 01-AUG-00:10 |
September | 0.174597E+10 | 0.492456E+09 | 183.41 | 0.145941E+10 | 0.286560E+09 | 0.00 | 1.00 | 14-SEP-06:01 | 0.00 | 01-SEP-00:10 | 18308.84 | 14-SEP-06:01 | 11537.54 | 14-SEP-06:01 | 6771.30 | 14-SEP-06:01 | 4224.04 | 14-SEP-06:01 | 0.00 | 01-SEP-00:10 |
October | 93634710.60 | 27226123.36 | 70.82 | 92600255.97 | 1034454.63 | 0.00 | 0.31 | 04-OCT-15:00 | 0.00 | 01-OCT-00:05 | 4601.55 | 04-OCT-15:00 | 4601.55 | 04-OCT-15:00 | 267.22 | 08-OCT-14:00 | 1313.51 | 04-OCT-15:00 | 0.00 | 01-OCT-00:05 |
November | 39229775.66 | 11477925.54 | 10.50 | 30103500.06 | 9126275.60 | 0.00 | 0.24 | 04-NOV-14:00 | 0.00 | 01-NOV-00:10 | 3723.62 | 04-NOV-14:00 | 2911.09 | 04-NOV-14:00 | 812.53 | 04-NOV-14:00 | 1076.98 | 04-NOV-14:00 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.146256E+11 | 0.419351E+10 | 1268.06 | 0.130625E+11 | 0.156307E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.550282E+10 | 0.157793E+10 | 291.95 | 0.487210E+10 | 0.630719E+09 | 0.00 | 1.00 | 0.00 | 19287.11 | 13964.73 | 7481.30 | 4453.57 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 655.93 | 201.75 | 3.00 | 645.79 | 10.13 | 0.00 | 0.00 | 27-FEB-19:40 | 0.00 | 01-FEB-00:10 | 0.15 | 27-FEB-19:40 | 0.14 | 27-FEB-19:40 | 0.01 | 27-FEB-19:40 | 0.05 | 27-FEB-19:40 | 0.00 | 01-FEB-00:10 |
March | 131915.35 | 40341.70 | 7.33 | 131885.92 | 29.43 | 0.00 | 0.01 | 18-MAR-16:00 | 0.00 | 01-MAR-00:10 | 152.59 | 18-MAR-16:00 | 152.59 | 18-MAR-16:00 | 0.01 | 10-MAR-13:50 | 46.63 | 18-MAR-16:00 | 0.00 | 01-MAR-00:10 |
April | 0.484992E+09 | 0.142962E+09 | 47.48 | 0.471714E+09 | 13277853.05 | 0.00 | 0.54 | 27-APR-15:00 | 0.00 | 01-APR-00:10 | 8929.48 | 27-APR-15:00 | 8601.54 | 27-APR-15:00 | 514.13 | 29-APR-14:50 | 2616.32 | 27-APR-15:00 | 0.00 | 01-APR-00:10 |
May | 0.984989E+09 | 0.283693E+09 | 132.90 | 0.892609E+09 | 92380047.46 | 0.00 | 0.51 | 06-MAY-13:00 | 0.00 | 01-MAY-00:10 | 8487.19 | 06-MAY-13:00 | 7100.69 | 15-MAY-16:30 | 1570.08 | 06-MAY-12:50 | 2362.59 | 06-MAY-13:00 | 0.00 | 01-MAY-00:10 |
June | 0.169450E+10 | 0.490563E+09 | 230.79 | 0.162417E+10 | 70326141.41 | 0.00 | 0.59 | 12-JUN-06:02 | 0.00 | 01-JUN-00:10 | 9684.03 | 12-JUN-06:02 | 8719.47 | 28-JUN-17:00 | 3377.90 | 12-JUN-06:02 | 2576.56 | 28-JUN-17:00 | 0.00 | 01-JUN-00:10 |
July | 0.398362E+10 | 0.114129E+10 | 271.14 | 0.353136E+10 | 0.452268E+09 | 0.00 | 1.00 | 25-JUL-06:02 | 0.00 | 01-JUL-00:05 | 18767.30 | 31-JUL-06:03 | 13524.17 | 24-JUL-06:03 | 6935.06 | 25-JUL-06:02 | 4359.92 | 31-JUL-06:03 | 0.00 | 01-JUL-00:05 |
August | 0.548626E+10 | 0.157397E+10 | 291.81 | 0.485754E+10 | 0.628725E+09 | 0.00 | 1.00 | 01-AUG-06:01 | 0.00 | 01-AUG-00:10 | 19339.71 | 25-AUG-06:03 | 14008.85 | 15-AUG-06:02 | 7499.82 | 26-AUG-06:02 | 4465.70 | 25-AUG-06:03 | 0.00 | 01-AUG-00:10 |
September | 0.172482E+10 | 0.486838E+09 | 181.91 | 0.144197E+10 | 0.282851E+09 | 0.00 | 1.00 | 14-SEP-06:01 | 0.00 | 01-SEP-00:10 | 18358.28 | 14-SEP-06:01 | 11567.24 | 14-SEP-06:01 | 6791.03 | 14-SEP-06:01 | 4235.44 | 14-SEP-06:01 | 0.00 | 01-SEP-00:10 |
October | 88039020.92 | 25605452.83 | 64.07 | 87160059.01 | 878961.91 | 0.00 | 0.31 | 04-OCT-15:00 | 0.00 | 01-OCT-00:05 | 4518.69 | 04-OCT-15:00 | 4518.69 | 04-OCT-15:00 | 246.86 | 08-OCT-14:00 | 1291.94 | 04-OCT-15:00 | 0.00 | 01-OCT-00:05 |
November | 33177172.96 | 9759037.28 | 7.67 | 25486062.02 | 7691110.94 | 0.00 | 0.22 | 04-NOV-14:00 | 0.00 | 01-NOV-00:10 | 3325.05 | 04-NOV-14:00 | 2597.41 | 04-NOV-14:00 | 727.64 | 04-NOV-14:00 | 968.09 | 04-NOV-14:00 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.144805E+11 | 0.415471E+10 | 1238.09 | 0.129321E+11 | 0.154840E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.548626E+10 | 0.157397E+10 | 291.81 | 0.485754E+10 | 0.628725E+09 | 0.00 | 1.00 | 0.00 | 19339.71 | 14008.85 | 7499.82 | 4465.70 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 349.73 | 96.22 | 2.17 | 347.01 | 2.71 | 0.00 | 0.00 | 27-FEB-13:50 | 0.00 | 01-FEB-00:10 | 0.15 | 27-FEB-13:50 | 0.15 | 27-FEB-13:50 | 0.00 | 27-FEB-19:50 | 0.04 | 27-FEB-13:50 | 0.00 | 01-FEB-00:10 |
March | 8308.01 | 2279.26 | 5.83 | 8308.01 | 0.00 | 0.00 | 0.00 | 18-MAR-14:00 | 0.00 | 01-MAR-00:10 | 2.06 | 18-MAR-14:00 | 2.06 | 18-MAR-14:00 | 0.00 | 14-MAR-18:30 | 0.56 | 18-MAR-14:00 | 0.00 | 01-MAR-00:10 |
April | 0.453351E+09 | 0.120052E+09 | 42.64 | 0.440879E+09 | 12472559.99 | 0.00 | 0.53 | 27-APR-15:00 | 0.00 | 01-APR-00:10 | 8617.08 | 27-APR-15:00 | 8296.37 | 27-APR-15:00 | 491.78 | 29-APR-15:00 | 2267.28 | 27-APR-15:00 | 0.00 | 01-APR-00:10 |
May | 0.921504E+09 | 0.238023E+09 | 118.86 | 0.835714E+09 | 85789692.18 | 0.00 | 0.50 | 06-MAY-13:00 | 0.00 | 01-MAY-00:10 | 8249.26 | 06-MAY-13:00 | 6894.09 | 15-MAY-16:40 | 1527.04 | 06-MAY-12:50 | 2059.73 | 06-MAY-13:00 | 0.00 | 01-MAY-00:10 |
June | 0.160720E+10 | 0.417009E+09 | 217.75 | 0.154182E+10 | 65376190.61 | 0.00 | 0.54 | 28-JUN-17:00 | 0.00 | 01-JUN-00:10 | 8684.45 | 28-JUN-17:00 | 8557.13 | 28-JUN-17:00 | 1857.34 | 12-JUN-06:02 | 2266.08 | 28-JUN-17:00 | 0.00 | 01-JUN-00:10 |
July | 0.383833E+10 | 0.985687E+09 | 269.45 | 0.340488E+10 | 0.433453E+09 | 0.00 | 0.90 | 31-JUL-06:03 | 0.00 | 01-JUL-00:05 | 16569.66 | 31-JUL-06:03 | 11930.98 | 24-JUL-06:03 | 5791.37 | 25-JUL-06:02 | 3540.08 | 31-JUL-06:03 | 0.00 | 01-JUL-00:05 |
August | 0.531599E+10 | 0.136694E+10 | 288.50 | 0.471029E+10 | 0.605701E+09 | 0.00 | 1.00 | 14-AUG-06:02 | 0.00 | 01-AUG-00:10 | 18946.16 | 26-AUG-06:02 | 13867.00 | 15-AUG-06:02 | 7478.09 | 26-AUG-06:02 | 3917.69 | 26-AUG-06:02 | 0.00 | 01-AUG-00:10 |
September | 0.164768E+10 | 0.416827E+09 | 171.48 | 0.137850E+10 | 0.269178E+09 | 0.00 | 0.99 | 14-SEP-06:01 | 0.00 | 01-SEP-00:10 | 17957.58 | 14-SEP-06:01 | 11284.90 | 14-SEP-06:01 | 6672.68 | 14-SEP-06:01 | 3719.79 | 14-SEP-06:01 | 0.00 | 01-SEP-00:10 |
October | 79044908.44 | 20584610.18 | 57.33 | 78377299.07 | 667609.37 | 0.00 | 0.30 | 04-OCT-15:00 | 0.00 | 01-OCT-00:05 | 4325.95 | 04-OCT-15:00 | 4325.95 | 04-OCT-15:00 | 215.04 | 08-OCT-14:00 | 1109.51 | 04-OCT-15:00 | 0.00 | 01-OCT-00:05 |
November | 24464611.99 | 6488928.16 | 6.50 | 18824641.49 | 5639970.50 | 0.00 | 0.18 | 04-NOV-14:00 | 0.00 | 01-NOV-00:10 | 2700.79 | 04-NOV-14:00 | 2106.34 | 04-NOV-14:00 | 594.45 | 04-NOV-14:00 | 710.42 | 04-NOV-14:00 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.138876E+11 | 0.357161E+10 | 1180.50 | 0.124093E+11 | 0.147828E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.531599E+10 | 0.136694E+10 | 288.50 | 0.471029E+10 | 0.605701E+09 | 0.00 | 1.00 | 0.00 | 18946.16 | 13867.00 | 7478.09 | 3917.69 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 159.26 | 48.99 | 0.33 | 159.26 | 0.00 | 0.00 | 0.00 | 27-FEB-14:50 | 0.00 | 01-FEB-00:10 | 0.19 | 27-FEB-14:50 | 0.19 | 27-FEB-14:50 | 0.00 | 01-FEB-00:10 | 0.06 | 27-FEB-14:50 | 0.00 | 01-FEB-00:10 |
March | 8552.02 | 2621.72 | 3.50 | 8552.02 | 0.00 | 0.00 | 0.00 | 18-MAR-13:50 | 0.00 | 01-MAR-00:10 | 2.52 | 18-MAR-13:50 | 2.52 | 18-MAR-13:50 | 0.00 | 18-MAR-15:00 | 0.77 | 18-MAR-13:50 | 0.00 | 01-MAR-00:10 |
April | 0.696182E+09 | 0.208215E+09 | 35.00 | 0.672918E+09 | 23263999.38 | 0.00 | 0.51 | 27-APR-15:00 | 0.00 | 01-APR-00:10 | 14696.67 | 27-APR-15:00 | 13923.72 | 27-APR-15:00 | 879.51 | 29-APR-15:00 | 4342.46 | 27-APR-15:00 | 0.00 | 01-APR-00:10 |
May | 0.136095E+10 | 0.395836E+09 | 90.33 | 0.122971E+10 | 0.131241E+09 | 0.00 | 0.47 | 06-MAY-13:30 | 0.00 | 01-MAY-00:10 | 13697.86 | 06-MAY-13:30 | 11455.87 | 06-MAY-13:50 | 2549.55 | 06-MAY-12:50 | 3855.90 | 06-MAY-13:30 | 0.00 | 01-MAY-00:10 |
June | 0.253881E+10 | 0.741283E+09 | 191.47 | 0.242643E+10 | 0.112380E+09 | 0.00 | 0.52 | 28-JUN-17:00 | 0.00 | 01-JUN-00:10 | 14917.67 | 28-JUN-17:00 | 14514.98 | 28-JUN-17:00 | 1299.23 | 21-JUN-17:00 | 4369.05 | 28-JUN-17:00 | 0.00 | 01-JUN-00:10 |
July | 0.637791E+10 | 0.184120E+10 | 256.72 | 0.561359E+10 | 0.764320E+09 | 0.00 | 1.00 | 24-JUL-07:03 | 0.00 | 01-JUL-00:05 | 33746.28 | 24-JUL-07:03 | 26473.05 | 24-JUL-07:03 | 8545.33 | 31-JUL-07:03 | 7799.82 | 24-JUL-07:03 | 0.00 | 01-JUL-00:05 |
August | 0.907494E+10 | 0.262182E+10 | 284.85 | 0.799118E+10 | 0.108376E+10 | 0.00 | 1.00 | 14-AUG-07:02 | 0.00 | 01-AUG-00:10 | 33716.57 | 14-AUG-07:02 | 24259.15 | 10-AUG-07:03 | 11053.98 | 30-AUG-07:02 | 7793.29 | 14-AUG-07:02 | 0.00 | 01-AUG-00:10 |
September | 0.260933E+10 | 0.741694E+09 | 147.39 | 0.216872E+10 | 0.440608E+09 | 0.00 | 0.55 | 14-SEP-14:10 | 0.00 | 01-SEP-00:10 | 16427.69 | 14-SEP-14:10 | 13803.98 | 12-SEP-14:10 | 5656.87 | 14-SEP-07:02 | 4519.58 | 14-SEP-14:10 | 0.00 | 01-SEP-00:10 |
October | 0.106505E+09 | 31115482.51 | 39.67 | 0.106028E+09 | 476892.90 | 0.00 | 0.28 | 04-OCT-15:00 | 0.00 | 01-OCT-00:05 | 7085.43 | 04-OCT-15:00 | 7085.43 | 04-OCT-15:00 | 223.95 | 08-OCT-14:00 | 2043.29 | 04-OCT-15:00 | 0.00 | 01-OCT-00:05 |
November | 20528619.71 | 6174111.34 | 3.83 | 15731173.15 | 4797446.56 | 0.00 | 0.11 | 04-NOV-14:20 | 0.00 | 01-NOV-00:10 | 2890.47 | 04-NOV-14:20 | 2235.86 | 04-NOV-14:20 | 656.88 | 04-NOV-14:10 | 865.29 | 04-NOV-14:20 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.227852E+11 | 0.658735E+10 | 1053.09 | 0.202243E+11 | 0.256085E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.907494E+10 | 0.262182E+10 | 284.85 | 0.799118E+10 | 0.108376E+10 | 0.00 | 1.00 | 0.00 | 33746.28 | 26473.05 | 11053.98 | 7799.82 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 40.81 | 11.23 | 0.17 | 40.81 | 0.00 | 0.00 | 0.00 | 27-FEB-15:00 | 0.00 | 01-FEB-00:10 | 0.07 | 27-FEB-15:00 | 0.07 | 27-FEB-15:00 | 0.00 | 01-FEB-00:10 | 0.02 | 27-FEB-15:00 | 0.00 | 01-FEB-00:10 |
March | 3636.80 | 997.27 | 3.33 | 3636.80 | 0.00 | 0.00 | 0.00 | 18-MAR-14:00 | 0.00 | 01-MAR-00:10 | 1.40 | 18-MAR-14:00 | 1.40 | 18-MAR-14:00 | 0.00 | 01-MAR-00:10 | 0.38 | 18-MAR-14:00 | 0.00 | 01-MAR-00:10 |
April | 0.350408E+09 | 93893753.38 | 34.17 | 0.339158E+09 | 11250944.01 | 0.00 | 0.51 | 27-APR-15:00 | 0.00 | 01-APR-00:10 | 7566.75 | 27-APR-15:00 | 7175.67 | 27-APR-15:00 | 434.86 | 29-APR-15:00 | 2001.27 | 27-APR-15:00 | 0.00 | 01-APR-00:10 |
May | 0.677460E+09 | 0.176431E+09 | 85.58 | 0.613112E+09 | 64348303.79 | 0.00 | 0.46 | 06-MAY-13:30 | 0.00 | 01-MAY-00:10 | 7024.39 | 06-MAY-13:30 | 5886.40 | 06-MAY-13:50 | 1296.15 | 06-MAY-12:50 | 1770.59 | 06-MAY-13:30 | 0.00 | 01-MAY-00:10 |
June | 0.127969E+10 | 0.334482E+09 | 183.58 | 0.122531E+10 | 54375005.99 | 0.00 | 0.52 | 28-JUN-17:00 | 0.00 | 01-JUN-00:10 | 7726.17 | 28-JUN-17:00 | 7529.72 | 28-JUN-17:00 | 656.55 | 21-JUN-17:00 | 2024.02 | 28-JUN-17:00 | 0.00 | 01-JUN-00:10 |
July | 0.324797E+10 | 0.839203E+09 | 254.25 | 0.286588E+10 | 0.382094E+09 | 0.00 | 0.92 | 24-JUL-07:03 | 0.00 | 01-JUL-00:05 | 15647.94 | 24-JUL-07:03 | 12292.18 | 24-JUL-07:03 | 3915.88 | 31-JUL-07:03 | 3321.82 | 24-JUL-07:03 | 0.00 | 01-JUL-00:05 |
August | 0.465217E+10 | 0.120265E+10 | 283.54 | 0.410676E+10 | 0.545408E+09 | 0.00 | 1.00 | 14-AUG-07:02 | 0.00 | 01-AUG-00:10 | 17451.25 | 14-AUG-07:02 | 11905.39 | 14-AUG-07:02 | 5545.85 | 14-AUG-07:02 | 3608.40 | 14-AUG-07:02 | 0.00 | 01-AUG-00:10 |
September | 0.132089E+10 | 0.335978E+09 | 144.88 | 0.110098E+10 | 0.219911E+09 | 0.00 | 0.55 | 14-SEP-14:10 | 0.00 | 01-SEP-00:10 | 8463.86 | 14-SEP-14:10 | 7138.49 | 12-SEP-14:10 | 2094.08 | 23-SEP-14:00 | 2084.22 | 14-SEP-14:10 | 0.00 | 01-SEP-00:10 |
October | 52570148.18 | 13750192.45 | 40.33 | 52394109.09 | 176039.08 | 0.00 | 0.27 | 04-OCT-15:00 | 0.00 | 01-OCT-00:05 | 3624.66 | 04-OCT-15:00 | 3624.66 | 04-OCT-15:00 | 94.63 | 08-OCT-14:00 | 935.84 | 04-OCT-15:00 | 0.00 | 01-OCT-00:05 |
November | 9107260.55 | 2454700.34 | 3.83 | 7006340.48 | 2100920.07 | 0.00 | 0.10 | 04-NOV-14:30 | 0.00 | 01-NOV-00:10 | 1370.56 | 04-NOV-14:30 | 1063.37 | 04-NOV-14:30 | 307.19 | 04-NOV-14:30 | 367.87 | 04-NOV-14:30 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.115903E+11 | 0.299884E+10 | 1033.67 | 0.103106E+11 | 0.127966E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.465217E+10 | 0.120265E+10 | 283.54 | 0.410676E+10 | 0.545408E+09 | 0.00 | 1.00 | 0.00 | 17451.25 | 12292.18 | 5545.85 | 3608.40 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 73.81 | 20.31 | 0.17 | 73.81 | 0.00 | 0.00 | 0.00 | 27-FEB-15:10 | 0.00 | 01-FEB-00:10 | 0.12 | 27-FEB-15:10 | 0.12 | 27-FEB-15:10 | 0.00 | 01-FEB-00:10 | 0.03 | 27-FEB-15:10 | 0.00 | 01-FEB-00:10 |
March | 3167.89 | 868.61 | 3.17 | 3167.89 | 0.00 | 0.00 | 0.00 | 18-MAR-14:00 | 0.00 | 01-MAR-00:10 | 1.25 | 18-MAR-14:00 | 1.25 | 18-MAR-14:00 | 0.00 | 01-MAR-00:10 | 0.34 | 18-MAR-14:00 | 0.00 | 01-MAR-00:10 |
April | 0.337089E+09 | 90519229.87 | 33.00 | 0.326299E+09 | 10790054.97 | 0.00 | 0.50 | 27-APR-15:00 | 0.00 | 01-APR-00:10 | 7393.89 | 27-APR-15:00 | 7008.70 | 27-APR-15:00 | 420.41 | 29-APR-15:00 | 1959.55 | 27-APR-15:00 | 0.00 | 01-APR-00:10 |
May | 0.644805E+09 | 0.168177E+09 | 82.03 | 0.583218E+09 | 61586685.65 | 0.00 | 0.46 | 06-MAY-13:30 | 0.00 | 01-MAY-00:10 | 6895.11 | 06-MAY-13:30 | 5774.23 | 06-MAY-13:50 | 1271.47 | 06-MAY-12:50 | 1740.33 | 06-MAY-13:30 | 0.00 | 01-MAY-00:10 |
June | 0.123959E+10 | 0.324317E+09 | 176.81 | 0.118701E+10 | 52577573.31 | 0.00 | 0.52 | 28-JUN-17:00 | 0.00 | 01-JUN-00:10 | 7637.05 | 28-JUN-17:00 | 7441.25 | 28-JUN-17:00 | 646.90 | 21-JUN-17:00 | 2001.92 | 28-JUN-17:00 | 0.00 | 01-JUN-00:10 |
July | 0.318208E+10 | 0.822781E+09 | 250.23 | 0.280773E+10 | 0.374350E+09 | 0.00 | 0.88 | 24-JUL-07:03 | 0.00 | 01-JUL-00:05 | 14613.63 | 24-JUL-07:03 | 11466.92 | 24-JUL-07:03 | 3604.56 | 31-JUL-07:03 | 3145.45 | 24-JUL-07:03 | 0.00 | 01-JUL-00:05 |
August | 0.457725E+10 | 0.118403E+10 | 282.22 | 0.404057E+10 | 0.536679E+09 | 0.00 | 0.99 | 14-AUG-07:02 | 0.00 | 01-AUG-00:10 | 17177.41 | 14-AUG-07:02 | 11705.05 | 14-AUG-07:02 | 5472.36 | 14-AUG-07:02 | 3559.76 | 14-AUG-07:02 | 0.00 | 01-AUG-00:10 |
September | 0.128853E+10 | 0.327927E+09 | 139.63 | 0.107394E+10 | 0.214586E+09 | 0.00 | 0.54 | 14-SEP-14:10 | 0.00 | 01-SEP-00:10 | 8367.51 | 14-SEP-14:10 | 7047.61 | 12-SEP-14:20 | 2061.80 | 23-SEP-14:00 | 2061.80 | 14-SEP-14:10 | 0.00 | 01-SEP-00:10 |
October | 49559201.46 | 12979362.62 | 39.75 | 49434199.02 | 125002.44 | 0.00 | 0.27 | 04-OCT-15:00 | 0.00 | 01-OCT-00:05 | 3507.29 | 04-OCT-15:00 | 3507.29 | 04-OCT-15:00 | 76.58 | 08-OCT-14:00 | 907.13 | 04-OCT-15:00 | 0.00 | 01-OCT-00:05 |
November | 7791249.45 | 2104046.99 | 3.50 | 5996724.60 | 1794524.84 | 0.00 | 0.09 | 04-NOV-14:30 | 0.00 | 01-NOV-00:10 | 1233.82 | 04-NOV-14:30 | 956.70 | 04-NOV-14:30 | 277.12 | 04-NOV-14:30 | 331.95 | 04-NOV-14:30 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.113267E+11 | 0.293283E+10 | 1010.49 | 0.100742E+11 | 0.125249E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.457725E+10 | 0.118403E+10 | 282.22 | 0.404057E+10 | 0.536679E+09 | 0.00 | 0.99 | 0.00 | 17177.41 | 11705.05 | 5472.36 | 3559.76 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 2252.86 | 617.71 | 2.67 | 2252.86 | 0.00 | 0.00 | 0.00 | 18-MAR-14:10 | 0.00 | 01-MAR-00:10 | 0.80 | 18-MAR-14:10 | 0.80 | 18-MAR-14:10 | 0.00 | 01-MAR-00:10 | 0.22 | 18-MAR-14:10 | 0.00 | 01-MAR-00:10 |
April | 0.309051E+09 | 83406139.97 | 33.08 | 0.299363E+09 | 9688405.65 | 0.00 | 0.48 | 27-APR-15:00 | 0.00 | 01-APR-00:10 | 7059.59 | 27-APR-15:00 | 6687.06 | 27-APR-15:00 | 383.93 | 29-APR-15:00 | 1879.78 | 27-APR-15:00 | 0.00 | 01-APR-00:10 |
May | 0.577457E+09 | 0.151205E+09 | 71.72 | 0.521940E+09 | 55517255.27 | 0.00 | 0.44 | 06-MAY-13:30 | 0.00 | 01-MAY-00:10 | 6604.36 | 06-MAY-13:30 | 5525.55 | 06-MAY-13:50 | 1215.03 | 06-MAY-12:50 | 1673.49 | 06-MAY-13:30 | 0.00 | 01-MAY-00:10 |
June | 0.114873E+10 | 0.301383E+09 | 164.61 | 0.110084E+10 | 47884682.91 | 0.00 | 0.51 | 28-JUN-17:00 | 0.00 | 01-JUN-00:10 | 7453.55 | 28-JUN-17:00 | 7260.40 | 28-JUN-17:00 | 625.14 | 21-JUN-17:00 | 1957.99 | 28-JUN-17:00 | 0.00 | 01-JUN-00:10 |
July | 0.303756E+10 | 0.787126E+09 | 243.31 | 0.268128E+10 | 0.356281E+09 | 0.00 | 0.71 | 24-JUL-07:03 | 0.00 | 01-JUL-00:05 | 11052.39 | 24-JUL-07:03 | 10257.13 | 24-JUL-15:00 | 2587.36 | 31-JUL-07:03 | 2858.55 | 24-JUL-15:00 | 0.00 | 01-JUL-00:05 |
August | 0.442376E+10 | 0.114633E+10 | 278.04 | 0.390664E+10 | 0.517123E+09 | 0.00 | 0.79 | 14-AUG-07:02 | 0.00 | 01-AUG-00:10 | 12735.31 | 14-AUG-07:02 | 10801.96 | 10-AUG-17:00 | 4083.79 | 14-AUG-07:02 | 3061.11 | 29-AUG-15:00 | 0.00 | 01-AUG-00:10 |
September | 0.122419E+10 | 0.312005E+09 | 129.80 | 0.102050E+10 | 0.203690E+09 | 0.00 | 0.54 | 14-SEP-14:10 | 0.00 | 01-SEP-00:10 | 8214.67 | 14-SEP-14:10 | 6889.29 | 12-SEP-14:10 | 2001.55 | 14-SEP-13:00 | 2027.03 | 14-SEP-14:10 | 0.00 | 01-SEP-00:10 |
October | 42605480.03 | 11198113.43 | 32.67 | 42577478.73 | 28001.30 | 0.00 | 0.25 | 04-OCT-15:00 | 0.00 | 01-OCT-00:05 | 3232.88 | 04-OCT-15:00 | 3232.88 | 04-OCT-15:00 | 24.79 | 08-OCT-14:00 | 840.12 | 04-OCT-15:00 | 0.00 | 01-OCT-00:05 |
November | 5388581.73 | 1460783.88 | 3.33 | 4153272.91 | 1235308.82 | 0.00 | 0.07 | 04-NOV-14:30 | 0.00 | 01-NOV-00:10 | 960.53 | 04-NOV-14:30 | 744.08 | 04-NOV-14:30 | 216.45 | 04-NOV-14:30 | 259.70 | 04-NOV-14:30 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.107688E+11 | 0.279411E+10 | 959.23 | 0.957730E+10 | 0.119145E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.442376E+10 | 0.114633E+10 | 278.04 | 0.390664E+10 | 0.517123E+09 | 0.00 | 0.79 | 0.00 | 12735.31 | 10801.96 | 4083.79 | 3061.11 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 0.261922E+09 | 71286546.28 | 27.92 | 0.254644E+09 | 7278220.63 | 0.00 | 0.46 | 27-APR-15:00 | 0.00 | 01-APR-00:10 | 6627.79 | 27-APR-15:00 | 6285.58 | 27-APR-15:00 | 342.21 | 27-APR-15:00 | 1776.66 | 27-APR-15:00 | 0.00 | 01-APR-00:10 |
May | 0.467780E+09 | 0.123511E+09 | 59.53 | 0.424062E+09 | 43718278.00 | 0.00 | 0.41 | 06-MAY-13:30 | 0.00 | 01-MAY-00:10 | 6082.27 | 06-MAY-13:30 | 5068.06 | 06-MAY-13:50 | 1112.88 | 06-MAY-12:50 | 1553.69 | 06-MAY-13:30 | 0.00 | 01-MAY-00:10 |
June | 0.973102E+09 | 0.256914E+09 | 144.03 | 0.935984E+09 | 37118480.05 | 0.00 | 0.49 | 28-JUN-17:00 | 0.00 | 01-JUN-00:10 | 7035.85 | 28-JUN-17:00 | 6866.51 | 28-JUN-17:00 | 558.44 | 21-JUN-17:00 | 1860.23 | 28-JUN-17:00 | 0.00 | 01-JUN-00:10 |
July | 0.275714E+10 | 0.717554E+09 | 227.50 | 0.244464E+10 | 0.312501E+09 | 0.00 | 0.70 | 24-JUL-15:00 | 0.00 | 01-JUL-00:05 | 10673.90 | 24-JUL-15:00 | 10176.10 | 24-JUL-15:00 | 1511.44 | 27-JUL-17:00 | 2833.09 | 24-JUL-15:00 | 0.00 | 01-JUL-00:05 |
August | 0.420331E+10 | 0.109075E+10 | 260.62 | 0.372413E+10 | 0.479176E+09 | 0.00 | 0.74 | 29-AUG-15:00 | 0.00 | 01-AUG-00:10 | 11665.12 | 29-AUG-14:50 | 10768.70 | 10-AUG-17:00 | 2112.08 | 30-AUG-13:00 | 3038.29 | 29-AUG-15:00 | 0.00 | 01-AUG-00:10 |
September | 0.112982E+10 | 0.288873E+09 | 114.31 | 0.943097E+09 | 0.186728E+09 | 0.00 | 0.53 | 14-SEP-14:10 | 0.00 | 01-SEP-00:10 | 8039.90 | 14-SEP-14:10 | 6716.26 | 14-SEP-14:10 | 1972.07 | 14-SEP-13:00 | 1988.03 | 14-SEP-14:10 | 0.00 | 01-SEP-00:10 |
October | 30529465.89 | 8099967.38 | 19.83 | 30529057.03 | 408.86 | 0.00 | 0.21 | 04-OCT-15:00 | 0.00 | 01-OCT-00:05 | 2635.02 | 04-OCT-15:00 | 2635.02 | 04-OCT-15:00 | 0.07 | 08-OCT-14:10 | 692.50 | 04-OCT-15:00 | 0.00 | 01-OCT-00:05 |
November | 2492880.67 | 680058.69 | 3.17 | 1929192.98 | 563687.69 | 0.00 | 0.04 | 04-NOV-14:30 | 0.00 | 01-NOV-00:10 | 546.22 | 04-NOV-14:30 | 423.60 | 04-NOV-14:30 | 122.62 | 04-NOV-14:30 | 148.82 | 04-NOV-14:30 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.982610E+10 | 0.255767E+10 | 856.89 | 0.875902E+10 | 0.106708E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.420331E+10 | 0.109075E+10 | 260.62 | 0.372413E+10 | 0.479176E+09 | 0.00 | 0.74 | 0.00 | 11665.12 | 10768.70 | 2112.08 | 3038.29 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 60.46 | 35.89 | 24.57 | 47.28 | 93.09 | 0.00 | 0.00 | 744.00 |
February | 93.01 | 57.58 | 35.44 | 82.76 | 81.55 | 0.00 | 0.00 | 672.00 |
March | 100.09 | 53.40 | 46.69 | 89.78 | 71.21 | 0.00 | 0.00 | 744.00 |
April | 105.64 | 45.87 | 59.77 | 89.46 | 59.94 | 0.00 | 0.00 | 720.00 |
May | 96.58 | 28.76 | 67.81 | 72.10 | 52.41 | 0.00 | 0.00 | 744.00 |
June | 88.36 | 23.71 | 64.64 | 62.24 | 42.03 | 0.00 | 0.00 | 720.00 |
July | 96.35 | 35.28 | 61.07 | 77.97 | 37.51 | 0.00 | 0.00 | 744.00 |
August | 103.53 | 48.27 | 55.26 | 98.28 | 36.44 | 0.00 | 0.00 | 744.00 |
September | 114.75 | 63.39 | 51.37 | 112.08 | 51.17 | 0.00 | 0.00 | 720.00 |
October | 103.94 | 64.19 | 39.75 | 101.04 | 67.88 | 0.00 | 0.00 | 744.00 |
November | 61.42 | 35.20 | 26.23 | 51.30 | 77.91 | 0.00 | 0.00 | 720.00 |
December | 64.26 | 41.58 | 22.68 | 57.34 | 94.41 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 90.66 | 44.34 | 46.32 | 78.43 | 63.72 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 60.46 | 23.71 | 22.68 | 47.28 | 36.44 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 114.75 | 64.19 | 67.81 | 112.08 | 94.41 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 60.46 | 35.89 | 24.57 | 47.28 | 93.09 | 0.00 | 0.00 | 744.00 |
February | 93.01 | 57.58 | 35.44 | 82.76 | 81.55 | 0.00 | 0.00 | 672.00 |
March | 100.09 | 53.40 | 46.69 | 89.78 | 71.21 | 0.00 | 0.00 | 744.00 |
April | 105.64 | 45.87 | 59.77 | 89.46 | 59.94 | 0.00 | 0.00 | 720.00 |
May | 96.58 | 28.76 | 67.81 | 72.10 | 52.41 | 0.00 | 0.00 | 744.00 |
June | 88.36 | 23.71 | 64.64 | 62.24 | 42.03 | 0.00 | 0.00 | 720.00 |
July | 96.35 | 35.28 | 61.07 | 77.97 | 37.51 | 0.00 | 0.00 | 744.00 |
August | 103.53 | 48.27 | 55.26 | 98.28 | 36.44 | 0.00 | 0.00 | 744.00 |
September | 114.75 | 63.39 | 51.37 | 112.08 | 51.17 | 0.00 | 0.00 | 720.00 |
October | 103.94 | 64.19 | 39.75 | 101.04 | 67.88 | 0.00 | 0.00 | 744.00 |
November | 61.42 | 35.20 | 26.23 | 51.30 | 77.91 | 0.00 | 0.00 | 720.00 |
December | 64.26 | 41.58 | 22.68 | 57.34 | 94.41 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 90.66 | 44.34 | 46.32 | 78.43 | 63.72 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 60.46 | 23.71 | 22.68 | 47.28 | 36.44 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 114.75 | 64.19 | 67.81 | 112.08 | 94.41 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_3
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 60.46 | 35.89 | 24.57 | 47.28 | 93.09 | 0.00 | 0.00 | 744.00 |
February | 93.01 | 57.58 | 35.44 | 82.76 | 81.55 | 0.00 | 0.00 | 672.00 |
March | 100.09 | 53.40 | 46.69 | 89.78 | 71.21 | 0.00 | 0.00 | 744.00 |
April | 105.64 | 45.87 | 59.77 | 89.46 | 59.94 | 0.00 | 0.00 | 720.00 |
May | 96.58 | 28.76 | 67.81 | 72.10 | 52.41 | 0.00 | 0.00 | 744.00 |
June | 88.36 | 23.71 | 64.64 | 62.24 | 42.03 | 0.00 | 0.00 | 720.00 |
July | 96.35 | 35.28 | 61.07 | 77.97 | 37.51 | 0.00 | 0.00 | 744.00 |
August | 103.53 | 48.27 | 55.26 | 98.28 | 36.44 | 0.00 | 0.00 | 744.00 |
September | 114.75 | 63.39 | 51.37 | 112.08 | 51.17 | 0.00 | 0.00 | 720.00 |
October | 103.94 | 64.19 | 39.75 | 101.04 | 67.88 | 0.00 | 0.00 | 744.00 |
November | 61.42 | 35.20 | 26.23 | 51.30 | 77.91 | 0.00 | 0.00 | 720.00 |
December | 64.26 | 41.58 | 22.68 | 57.34 | 94.41 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 90.66 | 44.34 | 46.32 | 78.43 | 63.72 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 60.46 | 23.71 | 22.68 | 47.28 | 36.44 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 114.75 | 64.19 | 67.81 | 112.08 | 94.41 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_4
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 60.46 | 35.89 | 24.57 | 47.28 | 93.09 | 0.00 | 0.00 | 744.00 |
February | 93.01 | 57.58 | 35.44 | 82.76 | 81.55 | 0.00 | 0.00 | 672.00 |
March | 100.09 | 53.40 | 46.69 | 89.78 | 71.21 | 0.00 | 0.00 | 744.00 |
April | 105.64 | 45.87 | 59.77 | 89.46 | 59.94 | 0.00 | 0.00 | 720.00 |
May | 96.58 | 28.76 | 67.81 | 72.10 | 52.41 | 0.00 | 0.00 | 744.00 |
June | 88.36 | 23.71 | 64.64 | 62.24 | 42.03 | 0.00 | 0.00 | 720.00 |
July | 96.35 | 35.28 | 61.07 | 77.97 | 37.51 | 0.00 | 0.00 | 744.00 |
August | 103.53 | 48.27 | 55.26 | 98.28 | 36.44 | 0.00 | 0.00 | 744.00 |
September | 114.75 | 63.39 | 51.37 | 112.08 | 51.17 | 0.00 | 0.00 | 720.00 |
October | 103.94 | 64.19 | 39.75 | 101.04 | 67.88 | 0.00 | 0.00 | 744.00 |
November | 61.42 | 35.20 | 26.23 | 51.30 | 77.91 | 0.00 | 0.00 | 720.00 |
December | 64.26 | 41.58 | 22.68 | 57.34 | 94.41 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 90.66 | 44.34 | 46.32 | 78.43 | 63.72 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 60.46 | 23.71 | 22.68 | 47.28 | 36.44 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 114.75 | 64.19 | 67.81 | 112.08 | 94.41 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_DOOR_1
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 72.79 | 43.21 | 29.58 | 57.07 | 110.80 | 0.00 | 0.00 | 744.00 |
February | 111.98 | 69.32 | 42.66 | 99.81 | 97.12 | 0.00 | 0.00 | 672.00 |
March | 120.50 | 64.29 | 56.22 | 108.20 | 84.82 | 0.00 | 0.00 | 744.00 |
April | 127.19 | 55.23 | 71.96 | 107.86 | 71.41 | 0.00 | 0.00 | 720.00 |
May | 116.27 | 34.63 | 81.64 | 86.97 | 62.48 | 0.00 | 0.00 | 744.00 |
June | 106.38 | 28.55 | 77.83 | 75.07 | 50.13 | 0.00 | 0.00 | 720.00 |
July | 116.01 | 42.47 | 73.53 | 93.90 | 44.79 | 0.00 | 0.00 | 744.00 |
August | 124.65 | 58.12 | 66.53 | 118.26 | 43.54 | 0.00 | 0.00 | 744.00 |
September | 138.16 | 76.31 | 61.84 | 134.91 | 61.13 | 0.00 | 0.00 | 720.00 |
October | 125.14 | 77.28 | 47.86 | 121.72 | 80.93 | 0.00 | 0.00 | 744.00 |
November | 73.95 | 42.37 | 31.58 | 61.87 | 92.82 | 0.00 | 0.00 | 720.00 |
December | 77.36 | 50.06 | 27.31 | 69.13 | 112.46 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 109.15 | 53.39 | 55.76 | 94.52 | 75.94 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 72.79 | 28.55 | 27.31 | 57.07 | 43.54 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 138.16 | 77.28 | 81.64 | 134.91 | 112.46 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_DOOR_2
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 72.79 | 43.21 | 29.58 | 57.07 | 110.80 | 0.00 | 0.00 | 744.00 |
February | 111.98 | 69.32 | 42.66 | 99.81 | 97.12 | 0.00 | 0.00 | 672.00 |
March | 120.50 | 64.29 | 56.22 | 108.20 | 84.82 | 0.00 | 0.00 | 744.00 |
April | 127.19 | 55.23 | 71.96 | 107.86 | 71.41 | 0.00 | 0.00 | 720.00 |
May | 116.27 | 34.63 | 81.64 | 86.97 | 62.48 | 0.00 | 0.00 | 744.00 |
June | 106.38 | 28.55 | 77.83 | 75.07 | 50.13 | 0.00 | 0.00 | 720.00 |
July | 116.01 | 42.47 | 73.53 | 93.90 | 44.79 | 0.00 | 0.00 | 744.00 |
August | 124.65 | 58.12 | 66.53 | 118.26 | 43.54 | 0.00 | 0.00 | 744.00 |
September | 138.16 | 76.31 | 61.84 | 134.91 | 61.13 | 0.00 | 0.00 | 720.00 |
October | 125.14 | 77.28 | 47.86 | 121.72 | 80.93 | 0.00 | 0.00 | 744.00 |
November | 73.95 | 42.37 | 31.58 | 61.87 | 92.82 | 0.00 | 0.00 | 720.00 |
December | 77.36 | 50.06 | 27.31 | 69.13 | 112.46 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 109.15 | 53.39 | 55.76 | 94.52 | 75.94 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 72.79 | 28.55 | 27.31 | 57.07 | 43.54 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 138.16 | 77.28 | 81.64 | 134.91 | 112.46 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 60.46 | 35.89 | 24.57 | 46.50 | 98.96 | 0.00 | 0.00 | 744.00 |
February | 93.01 | 57.58 | 35.44 | 81.47 | 87.15 | 0.00 | 0.00 | 672.00 |
March | 100.09 | 53.40 | 46.69 | 88.12 | 77.43 | 0.00 | 0.00 | 744.00 |
April | 105.64 | 45.87 | 59.77 | 87.47 | 64.56 | 0.00 | 0.00 | 720.00 |
May | 96.58 | 28.76 | 67.81 | 70.74 | 55.00 | 0.00 | 0.00 | 744.00 |
June | 88.36 | 23.71 | 64.64 | 61.46 | 43.48 | 0.00 | 0.00 | 720.00 |
July | 96.35 | 35.28 | 61.07 | 77.59 | 38.43 | 0.00 | 0.00 | 744.00 |
August | 103.53 | 48.27 | 55.26 | 97.90 | 37.28 | 0.00 | 0.00 | 744.00 |
September | 114.75 | 63.39 | 51.37 | 111.54 | 52.41 | 0.00 | 0.00 | 720.00 |
October | 103.94 | 64.19 | 39.75 | 99.84 | 71.51 | 0.00 | 0.00 | 744.00 |
November | 61.42 | 35.20 | 26.23 | 50.37 | 83.16 | 0.00 | 0.00 | 720.00 |
December | 64.26 | 41.58 | 22.68 | 56.52 | 100.22 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 90.66 | 44.34 | 46.32 | 77.42 | 67.38 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 60.46 | 23.71 | 22.68 | 46.50 | 37.28 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 114.75 | 64.19 | 67.81 | 111.54 | 100.22 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 60.46 | 35.89 | 24.57 | 46.50 | 98.96 | 0.00 | 0.00 | 744.00 |
February | 93.01 | 57.58 | 35.44 | 81.47 | 87.15 | 0.00 | 0.00 | 672.00 |
March | 100.09 | 53.40 | 46.69 | 88.12 | 77.43 | 0.00 | 0.00 | 744.00 |
April | 105.64 | 45.87 | 59.77 | 87.47 | 64.56 | 0.00 | 0.00 | 720.00 |
May | 96.58 | 28.76 | 67.81 | 70.74 | 55.00 | 0.00 | 0.00 | 744.00 |
June | 88.36 | 23.71 | 64.64 | 61.46 | 43.48 | 0.00 | 0.00 | 720.00 |
July | 96.35 | 35.28 | 61.07 | 77.59 | 38.43 | 0.00 | 0.00 | 744.00 |
August | 103.53 | 48.27 | 55.26 | 97.90 | 37.28 | 0.00 | 0.00 | 744.00 |
September | 114.75 | 63.39 | 51.37 | 111.54 | 52.41 | 0.00 | 0.00 | 720.00 |
October | 103.94 | 64.19 | 39.75 | 99.84 | 71.51 | 0.00 | 0.00 | 744.00 |
November | 61.42 | 35.20 | 26.23 | 50.37 | 83.16 | 0.00 | 0.00 | 720.00 |
December | 64.26 | 41.58 | 22.68 | 56.52 | 100.22 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 90.66 | 44.34 | 46.32 | 77.42 | 67.38 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 60.46 | 23.71 | 22.68 | 46.50 | 37.28 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 114.75 | 64.19 | 67.81 | 111.54 | 100.22 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_DOOR
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 72.79 | 43.21 | 29.58 | 56.14 | 117.74 | 0.00 | 0.00 | 744.00 |
February | 111.98 | 69.32 | 42.66 | 98.26 | 103.74 | 0.00 | 0.00 | 672.00 |
March | 120.50 | 64.29 | 56.22 | 106.23 | 92.17 | 0.00 | 0.00 | 744.00 |
April | 127.19 | 55.23 | 71.96 | 105.48 | 76.87 | 0.00 | 0.00 | 720.00 |
May | 116.27 | 34.63 | 81.64 | 85.35 | 65.53 | 0.00 | 0.00 | 744.00 |
June | 106.38 | 28.55 | 77.83 | 74.13 | 51.84 | 0.00 | 0.00 | 720.00 |
July | 116.01 | 42.47 | 73.53 | 93.44 | 45.87 | 0.00 | 0.00 | 744.00 |
August | 124.65 | 58.12 | 66.53 | 117.81 | 44.52 | 0.00 | 0.00 | 744.00 |
September | 138.16 | 76.31 | 61.84 | 134.27 | 62.59 | 0.00 | 0.00 | 720.00 |
October | 125.14 | 77.28 | 47.86 | 120.29 | 85.21 | 0.00 | 0.00 | 744.00 |
November | 73.95 | 42.37 | 31.58 | 60.75 | 99.01 | 0.00 | 0.00 | 720.00 |
December | 77.36 | 50.06 | 27.31 | 68.15 | 119.32 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 109.15 | 53.39 | 55.76 | 93.31 | 80.26 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 72.79 | 28.55 | 27.31 | 56.14 | 44.52 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 138.16 | 77.28 | 81.64 | 134.27 | 119.32 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 60.46 | 35.89 | 24.57 | 46.78 | 94.58 | 0.00 | 0.00 | 744.00 |
February | 93.01 | 57.58 | 35.44 | 81.98 | 83.33 | 0.00 | 0.00 | 672.00 |
March | 100.09 | 53.40 | 46.69 | 88.67 | 74.11 | 0.00 | 0.00 | 744.00 |
April | 105.64 | 45.87 | 59.77 | 88.03 | 62.64 | 0.00 | 0.00 | 720.00 |
May | 96.58 | 28.76 | 67.81 | 70.94 | 54.85 | 0.00 | 0.00 | 744.00 |
June | 88.36 | 23.71 | 64.64 | 61.39 | 44.47 | 0.00 | 0.00 | 720.00 |
July | 96.35 | 35.28 | 61.07 | 77.39 | 39.97 | 0.00 | 0.00 | 744.00 |
August | 103.53 | 48.27 | 55.26 | 97.72 | 38.94 | 0.00 | 0.00 | 744.00 |
September | 114.75 | 63.39 | 51.37 | 111.55 | 53.25 | 0.00 | 0.00 | 720.00 |
October | 103.94 | 64.19 | 39.75 | 100.28 | 69.83 | 0.00 | 0.00 | 744.00 |
November | 61.42 | 35.20 | 26.23 | 50.79 | 79.66 | 0.00 | 0.00 | 720.00 |
December | 64.26 | 41.58 | 22.68 | 56.88 | 96.06 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 90.66 | 44.34 | 46.32 | 77.66 | 65.90 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 60.46 | 23.71 | 22.68 | 46.78 | 38.94 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 114.75 | 64.19 | 67.81 | 111.55 | 96.06 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 60.46 | 35.89 | 24.57 | 46.78 | 94.58 | 0.00 | 0.00 | 744.00 |
February | 93.01 | 57.58 | 35.44 | 81.98 | 83.33 | 0.00 | 0.00 | 672.00 |
March | 100.09 | 53.40 | 46.69 | 88.67 | 74.11 | 0.00 | 0.00 | 744.00 |
April | 105.64 | 45.87 | 59.77 | 88.03 | 62.64 | 0.00 | 0.00 | 720.00 |
May | 96.58 | 28.76 | 67.81 | 70.94 | 54.85 | 0.00 | 0.00 | 744.00 |
June | 88.36 | 23.71 | 64.64 | 61.39 | 44.47 | 0.00 | 0.00 | 720.00 |
July | 96.35 | 35.28 | 61.07 | 77.39 | 39.97 | 0.00 | 0.00 | 744.00 |
August | 103.53 | 48.27 | 55.26 | 97.72 | 38.94 | 0.00 | 0.00 | 744.00 |
September | 114.75 | 63.39 | 51.37 | 111.55 | 53.25 | 0.00 | 0.00 | 720.00 |
October | 103.94 | 64.19 | 39.75 | 100.28 | 69.83 | 0.00 | 0.00 | 744.00 |
November | 61.42 | 35.20 | 26.23 | 50.79 | 79.66 | 0.00 | 0.00 | 720.00 |
December | 64.26 | 41.58 | 22.68 | 56.88 | 96.06 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 90.66 | 44.34 | 46.32 | 77.66 | 65.90 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 60.46 | 23.71 | 22.68 | 46.78 | 38.94 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 114.75 | 64.19 | 67.81 | 111.55 | 96.06 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_DOOR
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 72.39 | 42.98 | 29.42 | 56.17 | 111.92 | 0.00 | 0.00 | 744.00 |
February | 111.37 | 68.94 | 42.43 | 98.34 | 98.65 | 0.00 | 0.00 | 672.00 |
March | 119.84 | 63.93 | 55.91 | 106.30 | 87.74 | 0.00 | 0.00 | 744.00 |
April | 126.49 | 54.93 | 71.56 | 105.58 | 74.16 | 0.00 | 0.00 | 720.00 |
May | 115.64 | 34.44 | 81.20 | 85.12 | 64.97 | 0.00 | 0.00 | 744.00 |
June | 105.80 | 28.39 | 77.40 | 73.65 | 52.69 | 0.00 | 0.00 | 720.00 |
July | 115.37 | 42.24 | 73.13 | 92.70 | 47.39 | 0.00 | 0.00 | 744.00 |
August | 123.96 | 57.80 | 66.16 | 116.96 | 46.21 | 0.00 | 0.00 | 744.00 |
September | 137.40 | 75.90 | 61.50 | 133.54 | 63.20 | 0.00 | 0.00 | 720.00 |
October | 124.46 | 76.86 | 47.60 | 120.16 | 82.73 | 0.00 | 0.00 | 744.00 |
November | 73.55 | 42.14 | 31.41 | 60.93 | 94.33 | 0.00 | 0.00 | 720.00 |
December | 76.94 | 49.78 | 27.16 | 68.21 | 113.75 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 108.55 | 53.10 | 55.46 | 93.09 | 78.05 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 72.39 | 28.39 | 27.16 | 56.17 | 46.21 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 137.40 | 76.86 | 81.20 | 133.54 | 113.75 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 60.46 | 35.89 | 24.57 | 46.92 | 93.01 | 0.00 | 0.00 | 744.00 |
February | 93.01 | 57.58 | 35.44 | 82.26 | 81.86 | 0.00 | 0.00 | 672.00 |
March | 100.09 | 53.40 | 46.69 | 89.02 | 72.50 | 0.00 | 0.00 | 744.00 |
April | 105.64 | 45.87 | 59.77 | 88.49 | 61.28 | 0.00 | 0.00 | 720.00 |
May | 96.58 | 28.76 | 67.81 | 71.18 | 54.18 | 0.00 | 0.00 | 744.00 |
June | 88.36 | 23.71 | 64.64 | 61.47 | 44.20 | 0.00 | 0.00 | 720.00 |
July | 96.35 | 35.28 | 61.07 | 77.43 | 39.84 | 0.00 | 0.00 | 744.00 |
August | 103.53 | 48.27 | 55.26 | 97.73 | 38.87 | 0.00 | 0.00 | 744.00 |
September | 114.75 | 63.39 | 51.37 | 111.62 | 52.91 | 0.00 | 0.00 | 720.00 |
October | 103.94 | 64.19 | 39.75 | 100.62 | 68.40 | 0.00 | 0.00 | 744.00 |
November | 61.42 | 35.20 | 26.23 | 51.03 | 78.12 | 0.00 | 0.00 | 720.00 |
December | 64.26 | 41.58 | 22.68 | 57.04 | 94.61 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 90.66 | 44.34 | 46.32 | 77.86 | 64.91 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 60.46 | 23.71 | 22.68 | 46.92 | 38.87 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 114.75 | 64.19 | 67.81 | 111.62 | 94.61 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 60.46 | 35.89 | 24.57 | 46.92 | 93.01 | 0.00 | 0.00 | 744.00 |
February | 93.01 | 57.58 | 35.44 | 82.26 | 81.86 | 0.00 | 0.00 | 672.00 |
March | 100.09 | 53.40 | 46.69 | 89.02 | 72.50 | 0.00 | 0.00 | 744.00 |
April | 105.64 | 45.87 | 59.77 | 88.49 | 61.28 | 0.00 | 0.00 | 720.00 |
May | 96.58 | 28.76 | 67.81 | 71.18 | 54.18 | 0.00 | 0.00 | 744.00 |
June | 88.36 | 23.71 | 64.64 | 61.47 | 44.20 | 0.00 | 0.00 | 720.00 |
July | 96.35 | 35.28 | 61.07 | 77.43 | 39.84 | 0.00 | 0.00 | 744.00 |
August | 103.53 | 48.27 | 55.26 | 97.73 | 38.87 | 0.00 | 0.00 | 744.00 |
September | 114.75 | 63.39 | 51.37 | 111.62 | 52.91 | 0.00 | 0.00 | 720.00 |
October | 103.94 | 64.19 | 39.75 | 100.62 | 68.40 | 0.00 | 0.00 | 744.00 |
November | 61.42 | 35.20 | 26.23 | 51.03 | 78.12 | 0.00 | 0.00 | 720.00 |
December | 64.26 | 41.58 | 22.68 | 57.04 | 94.61 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 90.66 | 44.34 | 46.32 | 77.86 | 64.91 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 60.46 | 23.71 | 22.68 | 46.92 | 38.87 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 114.75 | 64.19 | 67.81 | 111.62 | 94.61 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_DOOR
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 72.39 | 42.98 | 29.42 | 56.34 | 110.05 | 0.00 | 0.00 | 744.00 |
February | 111.37 | 68.94 | 42.43 | 98.68 | 96.92 | 0.00 | 0.00 | 672.00 |
March | 119.84 | 63.93 | 55.91 | 106.72 | 85.83 | 0.00 | 0.00 | 744.00 |
April | 126.49 | 54.93 | 71.56 | 106.13 | 72.55 | 0.00 | 0.00 | 720.00 |
May | 115.64 | 34.44 | 81.20 | 85.41 | 64.17 | 0.00 | 0.00 | 744.00 |
June | 105.80 | 28.39 | 77.40 | 73.74 | 52.37 | 0.00 | 0.00 | 720.00 |
July | 115.37 | 42.24 | 73.13 | 92.74 | 47.24 | 0.00 | 0.00 | 744.00 |
August | 123.96 | 57.80 | 66.16 | 116.97 | 46.12 | 0.00 | 0.00 | 744.00 |
September | 137.40 | 75.90 | 61.50 | 133.63 | 62.80 | 0.00 | 0.00 | 720.00 |
October | 124.46 | 76.86 | 47.60 | 120.56 | 81.05 | 0.00 | 0.00 | 744.00 |
November | 73.55 | 42.14 | 31.41 | 61.22 | 92.50 | 0.00 | 0.00 | 720.00 |
December | 76.94 | 49.78 | 27.16 | 68.40 | 112.03 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 108.55 | 53.10 | 55.46 | 93.33 | 76.88 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 72.39 | 28.39 | 27.16 | 56.34 | 46.12 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 137.40 | 76.86 | 81.20 | 133.63 | 112.03 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 60.46 | 35.89 | 24.57 | 47.09 | 91.83 | 0.00 | 0.00 | 744.00 |
February | 93.01 | 57.58 | 35.44 | 82.57 | 80.72 | 0.00 | 0.00 | 672.00 |
March | 100.09 | 53.40 | 46.69 | 89.45 | 70.99 | 0.00 | 0.00 | 744.00 |
April | 105.64 | 45.87 | 59.77 | 89.15 | 59.78 | 0.00 | 0.00 | 720.00 |
May | 96.58 | 28.76 | 67.81 | 71.69 | 53.18 | 0.00 | 0.00 | 744.00 |
June | 88.36 | 23.71 | 64.64 | 61.72 | 43.62 | 0.00 | 0.00 | 720.00 |
July | 96.35 | 35.28 | 61.07 | 77.59 | 39.37 | 0.00 | 0.00 | 744.00 |
August | 103.53 | 48.27 | 55.26 | 97.89 | 38.41 | 0.00 | 0.00 | 744.00 |
September | 114.75 | 63.39 | 51.37 | 111.83 | 52.24 | 0.00 | 0.00 | 720.00 |
October | 103.94 | 64.19 | 39.75 | 101.12 | 66.72 | 0.00 | 0.00 | 744.00 |
November | 61.42 | 35.20 | 26.23 | 51.33 | 76.77 | 0.00 | 0.00 | 720.00 |
December | 64.26 | 41.58 | 22.68 | 57.21 | 93.54 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 90.66 | 44.34 | 46.32 | 78.18 | 63.86 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 60.46 | 23.71 | 22.68 | 47.09 | 38.41 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 114.75 | 64.19 | 67.81 | 111.83 | 93.54 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 60.46 | 35.89 | 24.57 | 47.09 | 91.83 | 0.00 | 0.00 | 744.00 |
February | 93.01 | 57.58 | 35.44 | 82.57 | 80.72 | 0.00 | 0.00 | 672.00 |
March | 100.09 | 53.40 | 46.69 | 89.45 | 70.99 | 0.00 | 0.00 | 744.00 |
April | 105.64 | 45.87 | 59.77 | 89.15 | 59.78 | 0.00 | 0.00 | 720.00 |
May | 96.58 | 28.76 | 67.81 | 71.69 | 53.18 | 0.00 | 0.00 | 744.00 |
June | 88.36 | 23.71 | 64.64 | 61.72 | 43.62 | 0.00 | 0.00 | 720.00 |
July | 96.35 | 35.28 | 61.07 | 77.59 | 39.37 | 0.00 | 0.00 | 744.00 |
August | 103.53 | 48.27 | 55.26 | 97.89 | 38.41 | 0.00 | 0.00 | 744.00 |
September | 114.75 | 63.39 | 51.37 | 111.83 | 52.24 | 0.00 | 0.00 | 720.00 |
October | 103.94 | 64.19 | 39.75 | 101.12 | 66.72 | 0.00 | 0.00 | 744.00 |
November | 61.42 | 35.20 | 26.23 | 51.33 | 76.77 | 0.00 | 0.00 | 720.00 |
December | 64.26 | 41.58 | 22.68 | 57.21 | 93.54 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 90.66 | 44.34 | 46.32 | 78.18 | 63.86 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 60.46 | 23.71 | 22.68 | 47.09 | 38.41 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 114.75 | 64.19 | 67.81 | 111.83 | 93.54 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_DOOR
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 72.39 | 42.98 | 29.42 | 56.54 | 108.65 | 0.00 | 0.00 | 744.00 |
February | 111.37 | 68.94 | 42.43 | 99.05 | 95.56 | 0.00 | 0.00 | 672.00 |
March | 119.84 | 63.93 | 55.91 | 107.24 | 84.04 | 0.00 | 0.00 | 744.00 |
April | 126.49 | 54.93 | 71.56 | 106.92 | 70.78 | 0.00 | 0.00 | 720.00 |
May | 115.64 | 34.44 | 81.20 | 86.02 | 62.99 | 0.00 | 0.00 | 744.00 |
June | 105.80 | 28.39 | 77.40 | 74.04 | 51.68 | 0.00 | 0.00 | 720.00 |
July | 115.37 | 42.24 | 73.13 | 92.94 | 46.69 | 0.00 | 0.00 | 744.00 |
August | 123.96 | 57.80 | 66.16 | 117.16 | 45.58 | 0.00 | 0.00 | 744.00 |
September | 137.40 | 75.90 | 61.50 | 133.88 | 62.01 | 0.00 | 0.00 | 720.00 |
October | 124.46 | 76.86 | 47.60 | 121.16 | 79.05 | 0.00 | 0.00 | 744.00 |
November | 73.55 | 42.14 | 31.41 | 61.58 | 90.89 | 0.00 | 0.00 | 720.00 |
December | 76.94 | 49.78 | 27.16 | 68.61 | 110.76 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 108.55 | 53.10 | 55.46 | 93.71 | 75.64 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 72.39 | 28.39 | 27.16 | 56.54 | 45.58 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 137.40 | 76.86 | 81.20 | 133.88 | 110.76 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 60.46 | 35.89 | 24.57 | 47.75 | 88.06 | 0.00 | 0.00 | 744.00 |
February | 93.01 | 57.58 | 35.44 | 83.62 | 77.43 | 0.00 | 0.00 | 672.00 |
March | 100.09 | 53.40 | 46.69 | 90.58 | 67.46 | 0.00 | 0.00 | 744.00 |
April | 105.64 | 45.87 | 59.77 | 90.68 | 56.41 | 0.00 | 0.00 | 720.00 |
May | 96.58 | 28.76 | 67.81 | 73.14 | 50.45 | 0.00 | 0.00 | 744.00 |
June | 88.36 | 23.71 | 64.64 | 62.49 | 41.70 | 0.00 | 0.00 | 720.00 |
July | 96.35 | 35.28 | 61.07 | 78.02 | 37.78 | 0.00 | 0.00 | 744.00 |
August | 103.53 | 48.27 | 55.26 | 98.30 | 36.81 | 0.00 | 0.00 | 744.00 |
September | 114.75 | 63.39 | 51.37 | 112.53 | 50.23 | 0.00 | 0.00 | 720.00 |
October | 103.94 | 64.19 | 39.75 | 102.37 | 63.07 | 0.00 | 0.00 | 744.00 |
November | 61.42 | 35.20 | 26.23 | 52.15 | 73.37 | 0.00 | 0.00 | 720.00 |
December | 64.26 | 41.58 | 22.68 | 57.82 | 90.15 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 90.66 | 44.34 | 46.32 | 79.08 | 61.00 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 60.46 | 23.71 | 22.68 | 47.75 | 36.81 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 114.75 | 64.19 | 67.81 | 112.53 | 90.15 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 60.46 | 35.89 | 24.57 | 47.75 | 88.06 | 0.00 | 0.00 | 744.00 |
February | 93.01 | 57.58 | 35.44 | 83.62 | 77.43 | 0.00 | 0.00 | 672.00 |
March | 100.09 | 53.40 | 46.69 | 90.58 | 67.46 | 0.00 | 0.00 | 744.00 |
April | 105.64 | 45.87 | 59.77 | 90.68 | 56.41 | 0.00 | 0.00 | 720.00 |
May | 96.58 | 28.76 | 67.81 | 73.14 | 50.45 | 0.00 | 0.00 | 744.00 |
June | 88.36 | 23.71 | 64.64 | 62.49 | 41.70 | 0.00 | 0.00 | 720.00 |
July | 96.35 | 35.28 | 61.07 | 78.02 | 37.78 | 0.00 | 0.00 | 744.00 |
August | 103.53 | 48.27 | 55.26 | 98.30 | 36.81 | 0.00 | 0.00 | 744.00 |
September | 114.75 | 63.39 | 51.37 | 112.53 | 50.23 | 0.00 | 0.00 | 720.00 |
October | 103.94 | 64.19 | 39.75 | 102.37 | 63.07 | 0.00 | 0.00 | 744.00 |
November | 61.42 | 35.20 | 26.23 | 52.15 | 73.37 | 0.00 | 0.00 | 720.00 |
December | 64.26 | 41.58 | 22.68 | 57.82 | 90.15 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 90.66 | 44.34 | 46.32 | 79.08 | 61.00 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 60.46 | 23.71 | 22.68 | 47.75 | 36.81 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 114.75 | 64.19 | 67.81 | 112.53 | 90.15 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_3
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 60.46 | 35.89 | 24.57 | 47.75 | 88.06 | 0.00 | 0.00 | 744.00 |
February | 93.01 | 57.58 | 35.44 | 83.62 | 77.43 | 0.00 | 0.00 | 672.00 |
March | 100.09 | 53.40 | 46.69 | 90.58 | 67.46 | 0.00 | 0.00 | 744.00 |
April | 105.64 | 45.87 | 59.77 | 90.68 | 56.41 | 0.00 | 0.00 | 720.00 |
May | 96.58 | 28.76 | 67.81 | 73.14 | 50.45 | 0.00 | 0.00 | 744.00 |
June | 88.36 | 23.71 | 64.64 | 62.49 | 41.70 | 0.00 | 0.00 | 720.00 |
July | 96.35 | 35.28 | 61.07 | 78.02 | 37.78 | 0.00 | 0.00 | 744.00 |
August | 103.53 | 48.27 | 55.26 | 98.30 | 36.81 | 0.00 | 0.00 | 744.00 |
September | 114.75 | 63.39 | 51.37 | 112.53 | 50.23 | 0.00 | 0.00 | 720.00 |
October | 103.94 | 64.19 | 39.75 | 102.37 | 63.07 | 0.00 | 0.00 | 744.00 |
November | 61.42 | 35.20 | 26.23 | 52.15 | 73.37 | 0.00 | 0.00 | 720.00 |
December | 64.26 | 41.58 | 22.68 | 57.82 | 90.15 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 90.66 | 44.34 | 46.32 | 79.08 | 61.00 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 60.46 | 23.71 | 22.68 | 47.75 | 36.81 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 114.75 | 64.19 | 67.81 | 112.53 | 90.15 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_4
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 60.46 | 35.89 | 24.57 | 47.75 | 88.06 | 0.00 | 0.00 | 744.00 |
February | 93.01 | 57.58 | 35.44 | 83.62 | 77.43 | 0.00 | 0.00 | 672.00 |
March | 100.09 | 53.40 | 46.69 | 90.58 | 67.46 | 0.00 | 0.00 | 744.00 |
April | 105.64 | 45.87 | 59.77 | 90.68 | 56.41 | 0.00 | 0.00 | 720.00 |
May | 96.58 | 28.76 | 67.81 | 73.14 | 50.45 | 0.00 | 0.00 | 744.00 |
June | 88.36 | 23.71 | 64.64 | 62.49 | 41.70 | 0.00 | 0.00 | 720.00 |
July | 96.35 | 35.28 | 61.07 | 78.02 | 37.78 | 0.00 | 0.00 | 744.00 |
August | 103.53 | 48.27 | 55.26 | 98.30 | 36.81 | 0.00 | 0.00 | 744.00 |
September | 114.75 | 63.39 | 51.37 | 112.53 | 50.23 | 0.00 | 0.00 | 720.00 |
October | 103.94 | 64.19 | 39.75 | 102.37 | 63.07 | 0.00 | 0.00 | 744.00 |
November | 61.42 | 35.20 | 26.23 | 52.15 | 73.37 | 0.00 | 0.00 | 720.00 |
December | 64.26 | 41.58 | 22.68 | 57.82 | 90.15 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 90.66 | 44.34 | 46.32 | 79.08 | 61.00 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 60.46 | 23.71 | 22.68 | 47.75 | 36.81 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 114.75 | 64.19 | 67.81 | 112.53 | 90.15 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_DOOR_1
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 72.39 | 42.98 | 29.42 | 57.34 | 104.20 | 0.00 | 0.00 | 744.00 |
February | 111.37 | 68.94 | 42.43 | 100.30 | 91.68 | 0.00 | 0.00 | 672.00 |
March | 119.84 | 63.93 | 55.91 | 108.59 | 79.88 | 0.00 | 0.00 | 744.00 |
April | 126.49 | 54.93 | 71.56 | 108.74 | 66.81 | 0.00 | 0.00 | 720.00 |
May | 115.64 | 34.44 | 81.20 | 87.75 | 59.78 | 0.00 | 0.00 | 744.00 |
June | 105.80 | 28.39 | 77.40 | 74.97 | 49.43 | 0.00 | 0.00 | 720.00 |
July | 115.37 | 42.24 | 73.13 | 93.47 | 44.81 | 0.00 | 0.00 | 744.00 |
August | 123.96 | 57.80 | 66.16 | 117.67 | 43.69 | 0.00 | 0.00 | 744.00 |
September | 137.40 | 75.90 | 61.50 | 134.72 | 59.63 | 0.00 | 0.00 | 720.00 |
October | 124.46 | 76.86 | 47.60 | 122.65 | 74.75 | 0.00 | 0.00 | 744.00 |
November | 73.55 | 42.14 | 31.41 | 62.56 | 86.88 | 0.00 | 0.00 | 720.00 |
December | 76.94 | 49.78 | 27.16 | 69.35 | 106.74 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 108.55 | 53.10 | 55.46 | 94.79 | 72.27 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 72.39 | 28.39 | 27.16 | 57.34 | 43.69 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 137.40 | 76.86 | 81.20 | 134.72 | 106.74 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_DOOR_2
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 72.39 | 42.98 | 29.42 | 57.34 | 104.20 | 0.00 | 0.00 | 744.00 |
February | 111.37 | 68.94 | 42.43 | 100.30 | 91.68 | 0.00 | 0.00 | 672.00 |
March | 119.84 | 63.93 | 55.91 | 108.59 | 79.88 | 0.00 | 0.00 | 744.00 |
April | 126.49 | 54.93 | 71.56 | 108.74 | 66.81 | 0.00 | 0.00 | 720.00 |
May | 115.64 | 34.44 | 81.20 | 87.75 | 59.78 | 0.00 | 0.00 | 744.00 |
June | 105.80 | 28.39 | 77.40 | 74.97 | 49.43 | 0.00 | 0.00 | 720.00 |
July | 115.37 | 42.24 | 73.13 | 93.47 | 44.81 | 0.00 | 0.00 | 744.00 |
August | 123.96 | 57.80 | 66.16 | 117.67 | 43.69 | 0.00 | 0.00 | 744.00 |
September | 137.40 | 75.90 | 61.50 | 134.72 | 59.63 | 0.00 | 0.00 | 720.00 |
October | 124.46 | 76.86 | 47.60 | 122.65 | 74.75 | 0.00 | 0.00 | 744.00 |
November | 73.55 | 42.14 | 31.41 | 62.56 | 86.88 | 0.00 | 0.00 | 720.00 |
December | 76.94 | 49.78 | 27.16 | 69.35 | 106.74 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 108.55 | 53.10 | 55.46 | 94.79 | 72.27 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 72.39 | 28.39 | 27.16 | 57.34 | 43.69 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 137.40 | 76.86 | 81.20 | 134.72 | 106.74 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 60.46 | 35.89 | 24.57 | 47.55 | 88.52 | 0.00 | 0.00 | 744.00 |
February | 93.01 | 57.58 | 35.44 | 83.42 | 77.63 | 0.00 | 0.00 | 672.00 |
March | 100.09 | 53.40 | 46.69 | 90.49 | 67.33 | 0.00 | 0.00 | 744.00 |
April | 105.64 | 45.87 | 59.77 | 90.77 | 56.08 | 0.00 | 0.00 | 720.00 |
May | 96.58 | 28.76 | 67.81 | 73.43 | 49.97 | 0.00 | 0.00 | 744.00 |
June | 88.36 | 23.71 | 64.64 | 62.65 | 41.42 | 0.00 | 0.00 | 720.00 |
July | 96.35 | 35.28 | 61.07 | 78.18 | 37.49 | 0.00 | 0.00 | 744.00 |
August | 103.53 | 48.27 | 55.26 | 98.42 | 36.49 | 0.00 | 0.00 | 744.00 |
September | 114.75 | 63.39 | 51.37 | 112.58 | 49.86 | 0.00 | 0.00 | 720.00 |
October | 103.94 | 64.19 | 39.75 | 102.35 | 62.62 | 0.00 | 0.00 | 744.00 |
November | 61.42 | 35.20 | 26.23 | 52.07 | 73.42 | 0.00 | 0.00 | 720.00 |
December | 64.26 | 41.58 | 22.68 | 57.67 | 90.49 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 90.66 | 44.34 | 46.32 | 79.09 | 60.87 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 60.46 | 23.71 | 22.68 | 47.55 | 36.49 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 114.75 | 64.19 | 67.81 | 112.58 | 90.49 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 60.46 | 35.89 | 24.57 | 47.55 | 88.52 | 0.00 | 0.00 | 744.00 |
February | 93.01 | 57.58 | 35.44 | 83.42 | 77.63 | 0.00 | 0.00 | 672.00 |
March | 100.09 | 53.40 | 46.69 | 90.49 | 67.33 | 0.00 | 0.00 | 744.00 |
April | 105.64 | 45.87 | 59.77 | 90.77 | 56.08 | 0.00 | 0.00 | 720.00 |
May | 96.58 | 28.76 | 67.81 | 73.43 | 49.97 | 0.00 | 0.00 | 744.00 |
June | 88.36 | 23.71 | 64.64 | 62.65 | 41.42 | 0.00 | 0.00 | 720.00 |
July | 96.35 | 35.28 | 61.07 | 78.18 | 37.49 | 0.00 | 0.00 | 744.00 |
August | 103.53 | 48.27 | 55.26 | 98.42 | 36.49 | 0.00 | 0.00 | 744.00 |
September | 114.75 | 63.39 | 51.37 | 112.58 | 49.86 | 0.00 | 0.00 | 720.00 |
October | 103.94 | 64.19 | 39.75 | 102.35 | 62.62 | 0.00 | 0.00 | 744.00 |
November | 61.42 | 35.20 | 26.23 | 52.07 | 73.42 | 0.00 | 0.00 | 720.00 |
December | 64.26 | 41.58 | 22.68 | 57.67 | 90.49 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 90.66 | 44.34 | 46.32 | 79.09 | 60.87 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 60.46 | 23.71 | 22.68 | 47.55 | 36.49 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 114.75 | 64.19 | 67.81 | 112.58 | 90.49 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_DOOR
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 72.39 | 42.98 | 29.42 | 57.12 | 104.70 | 0.00 | 0.00 | 744.00 |
February | 111.37 | 68.94 | 42.43 | 100.08 | 91.89 | 0.00 | 0.00 | 672.00 |
March | 119.84 | 63.93 | 55.91 | 108.50 | 79.70 | 0.00 | 0.00 | 744.00 |
April | 126.49 | 54.93 | 71.56 | 108.87 | 66.40 | 0.00 | 0.00 | 720.00 |
May | 115.64 | 34.44 | 81.20 | 88.11 | 59.19 | 0.00 | 0.00 | 744.00 |
June | 105.80 | 28.39 | 77.40 | 75.18 | 49.08 | 0.00 | 0.00 | 720.00 |
July | 115.37 | 42.24 | 73.13 | 93.67 | 44.46 | 0.00 | 0.00 | 744.00 |
August | 123.96 | 57.80 | 66.16 | 117.82 | 43.30 | 0.00 | 0.00 | 744.00 |
September | 137.40 | 75.90 | 61.50 | 134.80 | 59.18 | 0.00 | 0.00 | 720.00 |
October | 124.46 | 76.86 | 47.60 | 122.65 | 74.20 | 0.00 | 0.00 | 744.00 |
November | 73.55 | 42.14 | 31.41 | 62.47 | 86.92 | 0.00 | 0.00 | 720.00 |
December | 76.94 | 49.78 | 27.16 | 69.17 | 107.11 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 108.55 | 53.10 | 55.46 | 94.82 | 72.09 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 72.39 | 28.39 | 27.16 | 57.12 | 43.30 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 137.40 | 76.86 | 81.20 | 134.80 | 107.11 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 60.46 | 35.89 | 24.57 | 47.61 | 88.14 | 0.00 | 0.00 | 744.00 |
February | 93.01 | 57.58 | 35.44 | 83.52 | 77.25 | 0.00 | 0.00 | 672.00 |
March | 100.09 | 53.40 | 46.69 | 90.63 | 66.84 | 0.00 | 0.00 | 744.00 |
April | 105.64 | 45.87 | 59.77 | 91.03 | 55.50 | 0.00 | 0.00 | 720.00 |
May | 96.58 | 28.76 | 67.81 | 73.85 | 49.27 | 0.00 | 0.00 | 744.00 |
June | 88.36 | 23.71 | 64.64 | 62.88 | 41.04 | 0.00 | 0.00 | 720.00 |
July | 96.35 | 35.28 | 61.07 | 78.31 | 37.24 | 0.00 | 0.00 | 744.00 |
August | 103.53 | 48.27 | 55.26 | 98.53 | 36.28 | 0.00 | 0.00 | 744.00 |
September | 114.75 | 63.39 | 51.37 | 112.75 | 49.47 | 0.00 | 0.00 | 720.00 |
October | 103.94 | 64.19 | 39.75 | 102.56 | 62.00 | 0.00 | 0.00 | 744.00 |
November | 61.42 | 35.20 | 26.23 | 52.16 | 73.02 | 0.00 | 0.00 | 720.00 |
December | 64.26 | 41.58 | 22.68 | 57.72 | 90.13 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 90.66 | 44.34 | 46.32 | 79.26 | 60.44 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 60.46 | 23.71 | 22.68 | 47.61 | 36.28 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 114.75 | 64.19 | 67.81 | 112.75 | 90.13 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 60.46 | 35.89 | 24.57 | 47.61 | 88.14 | 0.00 | 0.00 | 744.00 |
February | 93.01 | 57.58 | 35.44 | 83.52 | 77.25 | 0.00 | 0.00 | 672.00 |
March | 100.09 | 53.40 | 46.69 | 90.63 | 66.84 | 0.00 | 0.00 | 744.00 |
April | 105.64 | 45.87 | 59.77 | 91.03 | 55.50 | 0.00 | 0.00 | 720.00 |
May | 96.58 | 28.76 | 67.81 | 73.85 | 49.27 | 0.00 | 0.00 | 744.00 |
June | 88.36 | 23.71 | 64.64 | 62.88 | 41.04 | 0.00 | 0.00 | 720.00 |
July | 96.35 | 35.28 | 61.07 | 78.31 | 37.24 | 0.00 | 0.00 | 744.00 |
August | 103.53 | 48.27 | 55.26 | 98.53 | 36.28 | 0.00 | 0.00 | 744.00 |
September | 114.75 | 63.39 | 51.37 | 112.75 | 49.47 | 0.00 | 0.00 | 720.00 |
October | 103.94 | 64.19 | 39.75 | 102.56 | 62.00 | 0.00 | 0.00 | 744.00 |
November | 61.42 | 35.20 | 26.23 | 52.16 | 73.02 | 0.00 | 0.00 | 720.00 |
December | 64.26 | 41.58 | 22.68 | 57.72 | 90.13 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 90.66 | 44.34 | 46.32 | 79.26 | 60.44 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 60.46 | 23.71 | 22.68 | 47.61 | 36.28 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 114.75 | 64.19 | 67.81 | 112.75 | 90.13 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_DOOR
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 72.39 | 42.98 | 29.42 | 57.18 | 104.25 | 0.00 | 0.00 | 744.00 |
February | 111.37 | 68.94 | 42.43 | 100.21 | 91.43 | 0.00 | 0.00 | 672.00 |
March | 119.84 | 63.93 | 55.91 | 108.66 | 79.12 | 0.00 | 0.00 | 744.00 |
April | 126.49 | 54.93 | 71.56 | 109.18 | 65.71 | 0.00 | 0.00 | 720.00 |
May | 115.64 | 34.44 | 81.20 | 88.61 | 58.36 | 0.00 | 0.00 | 744.00 |
June | 105.80 | 28.39 | 77.40 | 75.45 | 48.63 | 0.00 | 0.00 | 720.00 |
July | 115.37 | 42.24 | 73.13 | 93.82 | 44.16 | 0.00 | 0.00 | 744.00 |
August | 123.96 | 57.80 | 66.16 | 117.95 | 43.05 | 0.00 | 0.00 | 744.00 |
September | 137.40 | 75.90 | 61.50 | 135.00 | 58.71 | 0.00 | 0.00 | 720.00 |
October | 124.46 | 76.86 | 47.60 | 122.90 | 73.46 | 0.00 | 0.00 | 744.00 |
November | 73.55 | 42.14 | 31.41 | 62.58 | 86.44 | 0.00 | 0.00 | 720.00 |
December | 76.94 | 49.78 | 27.16 | 69.24 | 106.68 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 108.55 | 53.10 | 55.46 | 95.02 | 71.58 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 72.39 | 28.39 | 27.16 | 57.18 | 43.05 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 137.40 | 76.86 | 81.20 | 135.00 | 106.68 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 60.46 | 35.89 | 24.57 | 47.78 | 86.73 | 0.00 | 0.00 | 744.00 |
February | 93.01 | 57.58 | 35.44 | 83.82 | 75.89 | 0.00 | 0.00 | 672.00 |
March | 100.09 | 53.40 | 46.69 | 90.96 | 65.42 | 0.00 | 0.00 | 744.00 |
April | 105.64 | 45.87 | 59.77 | 91.59 | 54.05 | 0.00 | 0.00 | 720.00 |
May | 96.58 | 28.76 | 67.81 | 74.72 | 47.65 | 0.00 | 0.00 | 744.00 |
June | 88.36 | 23.71 | 64.64 | 63.46 | 40.02 | 0.00 | 0.00 | 720.00 |
July | 96.35 | 35.28 | 61.07 | 78.60 | 36.55 | 0.00 | 0.00 | 744.00 |
August | 103.53 | 48.27 | 55.26 | 98.75 | 35.71 | 0.00 | 0.00 | 744.00 |
September | 114.75 | 63.39 | 51.37 | 113.12 | 48.50 | 0.00 | 0.00 | 720.00 |
October | 103.94 | 64.19 | 39.75 | 102.98 | 60.64 | 0.00 | 0.00 | 744.00 |
November | 61.42 | 35.20 | 26.23 | 52.38 | 71.89 | 0.00 | 0.00 | 720.00 |
December | 64.26 | 41.58 | 22.68 | 57.90 | 88.86 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 90.66 | 44.34 | 46.32 | 79.63 | 59.25 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 60.46 | 23.71 | 22.68 | 47.78 | 35.71 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 114.75 | 64.19 | 67.81 | 113.12 | 88.86 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 60.46 | 35.89 | 24.57 | 47.78 | 86.73 | 0.00 | 0.00 | 744.00 |
February | 93.01 | 57.58 | 35.44 | 83.82 | 75.89 | 0.00 | 0.00 | 672.00 |
March | 100.09 | 53.40 | 46.69 | 90.96 | 65.42 | 0.00 | 0.00 | 744.00 |
April | 105.64 | 45.87 | 59.77 | 91.59 | 54.05 | 0.00 | 0.00 | 720.00 |
May | 96.58 | 28.76 | 67.81 | 74.72 | 47.65 | 0.00 | 0.00 | 744.00 |
June | 88.36 | 23.71 | 64.64 | 63.46 | 40.02 | 0.00 | 0.00 | 720.00 |
July | 96.35 | 35.28 | 61.07 | 78.60 | 36.55 | 0.00 | 0.00 | 744.00 |
August | 103.53 | 48.27 | 55.26 | 98.75 | 35.71 | 0.00 | 0.00 | 744.00 |
September | 114.75 | 63.39 | 51.37 | 113.12 | 48.50 | 0.00 | 0.00 | 720.00 |
October | 103.94 | 64.19 | 39.75 | 102.98 | 60.64 | 0.00 | 0.00 | 744.00 |
November | 61.42 | 35.20 | 26.23 | 52.38 | 71.89 | 0.00 | 0.00 | 720.00 |
December | 64.26 | 41.58 | 22.68 | 57.90 | 88.86 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 90.66 | 44.34 | 46.32 | 79.63 | 59.25 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 60.46 | 23.71 | 22.68 | 47.78 | 35.71 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 114.75 | 64.19 | 67.81 | 113.12 | 88.86 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_DOOR
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 72.39 | 42.98 | 29.42 | 57.40 | 102.57 | 0.00 | 0.00 | 744.00 |
February | 111.37 | 68.94 | 42.43 | 100.58 | 89.83 | 0.00 | 0.00 | 672.00 |
March | 119.84 | 63.93 | 55.91 | 109.06 | 77.44 | 0.00 | 0.00 | 744.00 |
April | 126.49 | 54.93 | 71.56 | 109.85 | 64.00 | 0.00 | 0.00 | 720.00 |
May | 115.64 | 34.44 | 81.20 | 89.65 | 56.44 | 0.00 | 0.00 | 744.00 |
June | 105.80 | 28.39 | 77.40 | 76.14 | 47.42 | 0.00 | 0.00 | 720.00 |
July | 115.37 | 42.24 | 73.13 | 94.18 | 43.35 | 0.00 | 0.00 | 744.00 |
August | 123.96 | 57.80 | 66.16 | 118.22 | 42.38 | 0.00 | 0.00 | 744.00 |
September | 137.40 | 75.90 | 61.50 | 135.45 | 57.56 | 0.00 | 0.00 | 720.00 |
October | 124.46 | 76.86 | 47.60 | 123.40 | 71.85 | 0.00 | 0.00 | 744.00 |
November | 73.55 | 42.14 | 31.41 | 62.85 | 85.10 | 0.00 | 0.00 | 720.00 |
December | 76.94 | 49.78 | 27.16 | 69.45 | 105.17 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 108.55 | 53.10 | 55.46 | 95.47 | 70.17 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 72.39 | 28.39 | 27.16 | 57.40 | 42.38 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 137.40 | 76.86 | 81.20 | 135.45 | 105.17 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 60.46 | 35.89 | 24.57 | 48.47 | 81.07 | 0.00 | 0.00 | 744.00 |
February | 93.01 | 57.58 | 35.44 | 84.91 | 70.49 | 0.00 | 0.00 | 672.00 |
March | 100.09 | 53.40 | 46.69 | 92.06 | 59.99 | 0.00 | 0.00 | 744.00 |
April | 105.64 | 45.87 | 59.77 | 93.10 | 49.03 | 0.00 | 0.00 | 720.00 |
May | 96.58 | 28.76 | 67.81 | 76.78 | 42.78 | 0.00 | 0.00 | 744.00 |
June | 88.36 | 23.71 | 64.64 | 65.17 | 36.33 | 0.00 | 0.00 | 720.00 |
July | 96.35 | 35.28 | 61.07 | 79.62 | 33.74 | 0.00 | 0.00 | 744.00 |
August | 103.53 | 48.27 | 55.26 | 99.48 | 33.33 | 0.00 | 0.00 | 744.00 |
September | 114.75 | 63.39 | 51.37 | 114.13 | 45.32 | 0.00 | 0.00 | 720.00 |
October | 103.94 | 64.19 | 39.75 | 104.05 | 56.52 | 0.00 | 0.00 | 744.00 |
November | 61.42 | 35.20 | 26.23 | 53.05 | 67.72 | 0.00 | 0.00 | 720.00 |
December | 64.26 | 41.58 | 22.68 | 58.53 | 83.82 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 90.66 | 44.34 | 46.32 | 80.74 | 54.94 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 60.46 | 23.71 | 22.68 | 48.47 | 33.33 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 114.75 | 64.19 | 67.81 | 114.13 | 83.82 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 60.46 | 35.89 | 24.57 | 48.47 | 81.07 | 0.00 | 0.00 | 744.00 |
February | 93.01 | 57.58 | 35.44 | 84.91 | 70.49 | 0.00 | 0.00 | 672.00 |
March | 100.09 | 53.40 | 46.69 | 92.06 | 59.99 | 0.00 | 0.00 | 744.00 |
April | 105.64 | 45.87 | 59.77 | 93.10 | 49.03 | 0.00 | 0.00 | 720.00 |
May | 96.58 | 28.76 | 67.81 | 76.78 | 42.78 | 0.00 | 0.00 | 744.00 |
June | 88.36 | 23.71 | 64.64 | 65.17 | 36.33 | 0.00 | 0.00 | 720.00 |
July | 96.35 | 35.28 | 61.07 | 79.62 | 33.74 | 0.00 | 0.00 | 744.00 |
August | 103.53 | 48.27 | 55.26 | 99.48 | 33.33 | 0.00 | 0.00 | 744.00 |
September | 114.75 | 63.39 | 51.37 | 114.13 | 45.32 | 0.00 | 0.00 | 720.00 |
October | 103.94 | 64.19 | 39.75 | 104.05 | 56.52 | 0.00 | 0.00 | 744.00 |
November | 61.42 | 35.20 | 26.23 | 53.05 | 67.72 | 0.00 | 0.00 | 720.00 |
December | 64.26 | 41.58 | 22.68 | 58.53 | 83.82 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 90.66 | 44.34 | 46.32 | 80.74 | 54.94 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 60.46 | 23.71 | 22.68 | 48.47 | 33.33 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 114.75 | 64.19 | 67.81 | 114.13 | 83.82 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_DOOR
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 72.39 | 42.98 | 29.42 | 58.24 | 95.86 | 0.00 | 0.00 | 744.00 |
February | 111.37 | 68.94 | 42.43 | 101.90 | 83.43 | 0.00 | 0.00 | 672.00 |
March | 119.84 | 63.93 | 55.91 | 110.41 | 71.00 | 0.00 | 0.00 | 744.00 |
April | 126.49 | 54.93 | 71.56 | 111.68 | 58.07 | 0.00 | 0.00 | 720.00 |
May | 115.64 | 34.44 | 81.20 | 92.13 | 50.70 | 0.00 | 0.00 | 744.00 |
June | 105.80 | 28.39 | 77.40 | 78.20 | 43.07 | 0.00 | 0.00 | 720.00 |
July | 115.37 | 42.24 | 73.13 | 95.40 | 40.03 | 0.00 | 0.00 | 744.00 |
August | 123.96 | 57.80 | 66.16 | 119.10 | 39.58 | 0.00 | 0.00 | 744.00 |
September | 137.40 | 75.90 | 61.50 | 136.67 | 53.80 | 0.00 | 0.00 | 720.00 |
October | 124.46 | 76.86 | 47.60 | 124.69 | 66.99 | 0.00 | 0.00 | 744.00 |
November | 73.55 | 42.14 | 31.41 | 63.67 | 80.16 | 0.00 | 0.00 | 720.00 |
December | 76.94 | 49.78 | 27.16 | 70.22 | 99.19 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 108.55 | 53.10 | 55.46 | 96.81 | 65.08 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 72.39 | 28.39 | 27.16 | 58.24 | 39.58 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 137.40 | 76.86 | 81.20 | 136.67 | 99.19 | 0.00 | 0.00 | 744.00 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.161938E+09 | 96138523.70 | 65799337.47 | 0.126623E+09 | 0.249327E+09 |
February | 0.225014E+09 | 0.139290E+09 | 85724535.56 | 0.200218E+09 | 0.197275E+09 |
March | 0.268082E+09 | 0.143015E+09 | 0.125067E+09 | 0.240456E+09 | 0.190718E+09 |
April | 0.273827E+09 | 0.118907E+09 | 0.154920E+09 | 0.231883E+09 | 0.155359E+09 |
May | 0.258668E+09 | 77034632.29 | 0.181634E+09 | 0.193109E+09 | 0.140381E+09 |
June | 0.229021E+09 | 61464616.56 | 0.167556E+09 | 0.161325E+09 | 0.108950E+09 |
July | 0.258075E+09 | 94492485.45 | 0.163583E+09 | 0.208836E+09 | 0.100479E+09 |
August | 0.277296E+09 | 0.129296E+09 | 0.148000E+09 | 0.263222E+09 | 97603256.21 |
September | 0.297439E+09 | 0.164298E+09 | 0.133141E+09 | 0.290521E+09 | 0.132639E+09 |
October | 0.278396E+09 | 0.171917E+09 | 0.106479E+09 | 0.270637E+09 | 0.181807E+09 |
November | 0.159213E+09 | 91228882.84 | 67984236.35 | 0.132976E+09 | 0.201944E+09 |
December | 0.172112E+09 | 0.111360E+09 | 60751916.90 | 0.153571E+09 | 0.252855E+09 |
Annual Sum or Average | 0.285908E+10 | 0.139844E+10 | 0.146064E+10 | 0.247338E+10 | 0.200934E+10 |
Minimum of Months | 0.159213E+09 | 61464616.56 | 60751916.90 | 0.126623E+09 | 97603256.21 |
Maximum of Months | 0.297439E+09 | 0.171917E+09 | 0.181634E+09 | 0.290521E+09 | 0.252855E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.161938E+09 | 96138523.70 | 65799337.47 | 0.126623E+09 | 0.249327E+09 |
February | 0.225014E+09 | 0.139290E+09 | 85724535.56 | 0.200218E+09 | 0.197275E+09 |
March | 0.268082E+09 | 0.143015E+09 | 0.125067E+09 | 0.240456E+09 | 0.190718E+09 |
April | 0.273827E+09 | 0.118907E+09 | 0.154920E+09 | 0.231883E+09 | 0.155359E+09 |
May | 0.258668E+09 | 77034632.29 | 0.181634E+09 | 0.193109E+09 | 0.140381E+09 |
June | 0.229021E+09 | 61464616.56 | 0.167556E+09 | 0.161325E+09 | 0.108950E+09 |
July | 0.258075E+09 | 94492485.45 | 0.163583E+09 | 0.208836E+09 | 0.100479E+09 |
August | 0.277296E+09 | 0.129296E+09 | 0.148000E+09 | 0.263222E+09 | 97603256.21 |
September | 0.297439E+09 | 0.164298E+09 | 0.133141E+09 | 0.290521E+09 | 0.132639E+09 |
October | 0.278396E+09 | 0.171917E+09 | 0.106479E+09 | 0.270637E+09 | 0.181807E+09 |
November | 0.159213E+09 | 91228882.84 | 67984236.35 | 0.132976E+09 | 0.201944E+09 |
December | 0.172112E+09 | 0.111360E+09 | 60751916.90 | 0.153571E+09 | 0.252855E+09 |
Annual Sum or Average | 0.285908E+10 | 0.139844E+10 | 0.146064E+10 | 0.247338E+10 | 0.200934E+10 |
Minimum of Months | 0.159213E+09 | 61464616.56 | 60751916.90 | 0.126623E+09 | 97603256.21 |
Maximum of Months | 0.297439E+09 | 0.171917E+09 | 0.181634E+09 | 0.290521E+09 | 0.252855E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_3
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.161938E+09 | 96138523.70 | 65799337.47 | 0.126623E+09 | 0.249327E+09 |
February | 0.225014E+09 | 0.139290E+09 | 85724535.56 | 0.200218E+09 | 0.197275E+09 |
March | 0.268082E+09 | 0.143015E+09 | 0.125067E+09 | 0.240456E+09 | 0.190718E+09 |
April | 0.273827E+09 | 0.118907E+09 | 0.154920E+09 | 0.231883E+09 | 0.155359E+09 |
May | 0.258668E+09 | 77034632.29 | 0.181634E+09 | 0.193109E+09 | 0.140381E+09 |
June | 0.229021E+09 | 61464616.56 | 0.167556E+09 | 0.161325E+09 | 0.108950E+09 |
July | 0.258075E+09 | 94492485.45 | 0.163583E+09 | 0.208836E+09 | 0.100479E+09 |
August | 0.277296E+09 | 0.129296E+09 | 0.148000E+09 | 0.263222E+09 | 97603256.21 |
September | 0.297439E+09 | 0.164298E+09 | 0.133141E+09 | 0.290521E+09 | 0.132639E+09 |
October | 0.278396E+09 | 0.171917E+09 | 0.106479E+09 | 0.270637E+09 | 0.181807E+09 |
November | 0.159213E+09 | 91228882.84 | 67984236.35 | 0.132976E+09 | 0.201944E+09 |
December | 0.172112E+09 | 0.111360E+09 | 60751916.90 | 0.153571E+09 | 0.252855E+09 |
Annual Sum or Average | 0.285908E+10 | 0.139844E+10 | 0.146064E+10 | 0.247338E+10 | 0.200934E+10 |
Minimum of Months | 0.159213E+09 | 61464616.56 | 60751916.90 | 0.126623E+09 | 97603256.21 |
Maximum of Months | 0.297439E+09 | 0.171917E+09 | 0.181634E+09 | 0.290521E+09 | 0.252855E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_4
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.161938E+09 | 96138523.70 | 65799337.47 | 0.126623E+09 | 0.249327E+09 |
February | 0.225014E+09 | 0.139290E+09 | 85724535.56 | 0.200218E+09 | 0.197275E+09 |
March | 0.268082E+09 | 0.143015E+09 | 0.125067E+09 | 0.240456E+09 | 0.190718E+09 |
April | 0.273827E+09 | 0.118907E+09 | 0.154920E+09 | 0.231883E+09 | 0.155359E+09 |
May | 0.258668E+09 | 77034632.29 | 0.181634E+09 | 0.193109E+09 | 0.140381E+09 |
June | 0.229021E+09 | 61464616.56 | 0.167556E+09 | 0.161325E+09 | 0.108950E+09 |
July | 0.258075E+09 | 94492485.45 | 0.163583E+09 | 0.208836E+09 | 0.100479E+09 |
August | 0.277296E+09 | 0.129296E+09 | 0.148000E+09 | 0.263222E+09 | 97603256.21 |
September | 0.297439E+09 | 0.164298E+09 | 0.133141E+09 | 0.290521E+09 | 0.132639E+09 |
October | 0.278396E+09 | 0.171917E+09 | 0.106479E+09 | 0.270637E+09 | 0.181807E+09 |
November | 0.159213E+09 | 91228882.84 | 67984236.35 | 0.132976E+09 | 0.201944E+09 |
December | 0.172112E+09 | 0.111360E+09 | 60751916.90 | 0.153571E+09 | 0.252855E+09 |
Annual Sum or Average | 0.285908E+10 | 0.139844E+10 | 0.146064E+10 | 0.247338E+10 | 0.200934E+10 |
Minimum of Months | 0.159213E+09 | 61464616.56 | 60751916.90 | 0.126623E+09 | 97603256.21 |
Maximum of Months | 0.297439E+09 | 0.171917E+09 | 0.181634E+09 | 0.290521E+09 | 0.252855E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_DOOR_1
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.194965E+09 | 0.115746E+09 | 79218939.19 | 0.152850E+09 | 0.296773E+09 |
February | 0.270905E+09 | 0.167698E+09 | 0.103208E+09 | 0.241458E+09 | 0.234962E+09 |
March | 0.322757E+09 | 0.172182E+09 | 0.150574E+09 | 0.289813E+09 | 0.227188E+09 |
April | 0.329673E+09 | 0.143158E+09 | 0.186516E+09 | 0.279576E+09 | 0.185098E+09 |
May | 0.311423E+09 | 92745642.82 | 0.218677E+09 | 0.232940E+09 | 0.167347E+09 |
June | 0.275729E+09 | 74000163.36 | 0.201728E+09 | 0.194570E+09 | 0.129948E+09 |
July | 0.310709E+09 | 0.113764E+09 | 0.196945E+09 | 0.251506E+09 | 0.119973E+09 |
August | 0.333850E+09 | 0.155666E+09 | 0.178184E+09 | 0.316756E+09 | 0.116615E+09 |
September | 0.358101E+09 | 0.197806E+09 | 0.160295E+09 | 0.349696E+09 | 0.158444E+09 |
October | 0.335174E+09 | 0.206979E+09 | 0.128195E+09 | 0.326013E+09 | 0.216765E+09 |
November | 0.191684E+09 | 0.109835E+09 | 81849442.44 | 0.160362E+09 | 0.240583E+09 |
December | 0.207214E+09 | 0.134072E+09 | 73142110.47 | 0.185153E+09 | 0.301201E+09 |
Annual Sum or Average | 0.344218E+10 | 0.168365E+10 | 0.175853E+10 | 0.298069E+10 | 0.239490E+10 |
Minimum of Months | 0.191684E+09 | 74000163.36 | 73142110.47 | 0.152850E+09 | 0.116615E+09 |
Maximum of Months | 0.358101E+09 | 0.206979E+09 | 0.218677E+09 | 0.349696E+09 | 0.301201E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_DOOR_2
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.194965E+09 | 0.115746E+09 | 79218939.19 | 0.152850E+09 | 0.296773E+09 |
February | 0.270905E+09 | 0.167698E+09 | 0.103208E+09 | 0.241458E+09 | 0.234962E+09 |
March | 0.322757E+09 | 0.172182E+09 | 0.150574E+09 | 0.289813E+09 | 0.227188E+09 |
April | 0.329673E+09 | 0.143158E+09 | 0.186516E+09 | 0.279576E+09 | 0.185098E+09 |
May | 0.311423E+09 | 92745642.82 | 0.218677E+09 | 0.232940E+09 | 0.167347E+09 |
June | 0.275729E+09 | 74000163.36 | 0.201728E+09 | 0.194570E+09 | 0.129948E+09 |
July | 0.310709E+09 | 0.113764E+09 | 0.196945E+09 | 0.251506E+09 | 0.119973E+09 |
August | 0.333850E+09 | 0.155666E+09 | 0.178184E+09 | 0.316756E+09 | 0.116615E+09 |
September | 0.358101E+09 | 0.197806E+09 | 0.160295E+09 | 0.349696E+09 | 0.158444E+09 |
October | 0.335174E+09 | 0.206979E+09 | 0.128195E+09 | 0.326013E+09 | 0.216765E+09 |
November | 0.191684E+09 | 0.109835E+09 | 81849442.44 | 0.160362E+09 | 0.240583E+09 |
December | 0.207214E+09 | 0.134072E+09 | 73142110.47 | 0.185153E+09 | 0.301201E+09 |
Annual Sum or Average | 0.344218E+10 | 0.168365E+10 | 0.175853E+10 | 0.298069E+10 | 0.239490E+10 |
Minimum of Months | 0.191684E+09 | 74000163.36 | 73142110.47 | 0.152850E+09 | 0.116615E+09 |
Maximum of Months | 0.358101E+09 | 0.206979E+09 | 0.218677E+09 | 0.349696E+09 | 0.301201E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.161938E+09 | 96138523.70 | 65799337.47 | 0.124556E+09 | 0.265064E+09 |
February | 0.225014E+09 | 0.139290E+09 | 85724535.56 | 0.197090E+09 | 0.210831E+09 |
March | 0.268082E+09 | 0.143015E+09 | 0.125067E+09 | 0.236032E+09 | 0.207383E+09 |
April | 0.273827E+09 | 0.118907E+09 | 0.154920E+09 | 0.226723E+09 | 0.167351E+09 |
May | 0.258668E+09 | 77034632.29 | 0.181634E+09 | 0.189479E+09 | 0.147300E+09 |
June | 0.229021E+09 | 61464616.56 | 0.167556E+09 | 0.159295E+09 | 0.112712E+09 |
July | 0.258075E+09 | 94492485.45 | 0.163583E+09 | 0.207811E+09 | 0.102928E+09 |
August | 0.277296E+09 | 0.129296E+09 | 0.148000E+09 | 0.262209E+09 | 99839111.75 |
September | 0.297439E+09 | 0.164298E+09 | 0.133141E+09 | 0.289116E+09 | 0.135835E+09 |
October | 0.278396E+09 | 0.171917E+09 | 0.106479E+09 | 0.267420E+09 | 0.191519E+09 |
November | 0.159213E+09 | 91228882.84 | 67984236.35 | 0.130553E+09 | 0.215563E+09 |
December | 0.172112E+09 | 0.111360E+09 | 60751916.90 | 0.151378E+09 | 0.268436E+09 |
Annual Sum or Average | 0.285908E+10 | 0.139844E+10 | 0.146064E+10 | 0.244166E+10 | 0.212476E+10 |
Minimum of Months | 0.159213E+09 | 61464616.56 | 60751916.90 | 0.124556E+09 | 99839111.75 |
Maximum of Months | 0.297439E+09 | 0.171917E+09 | 0.181634E+09 | 0.289116E+09 | 0.268436E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.161938E+09 | 96138523.70 | 65799337.47 | 0.124556E+09 | 0.265064E+09 |
February | 0.225014E+09 | 0.139290E+09 | 85724535.56 | 0.197090E+09 | 0.210831E+09 |
March | 0.268082E+09 | 0.143015E+09 | 0.125067E+09 | 0.236032E+09 | 0.207383E+09 |
April | 0.273827E+09 | 0.118907E+09 | 0.154920E+09 | 0.226723E+09 | 0.167351E+09 |
May | 0.258668E+09 | 77034632.29 | 0.181634E+09 | 0.189479E+09 | 0.147300E+09 |
June | 0.229021E+09 | 61464616.56 | 0.167556E+09 | 0.159295E+09 | 0.112712E+09 |
July | 0.258075E+09 | 94492485.45 | 0.163583E+09 | 0.207811E+09 | 0.102928E+09 |
August | 0.277296E+09 | 0.129296E+09 | 0.148000E+09 | 0.262209E+09 | 99839111.75 |
September | 0.297439E+09 | 0.164298E+09 | 0.133141E+09 | 0.289116E+09 | 0.135835E+09 |
October | 0.278396E+09 | 0.171917E+09 | 0.106479E+09 | 0.267420E+09 | 0.191519E+09 |
November | 0.159213E+09 | 91228882.84 | 67984236.35 | 0.130553E+09 | 0.215563E+09 |
December | 0.172112E+09 | 0.111360E+09 | 60751916.90 | 0.151378E+09 | 0.268436E+09 |
Annual Sum or Average | 0.285908E+10 | 0.139844E+10 | 0.146064E+10 | 0.244166E+10 | 0.212476E+10 |
Minimum of Months | 0.159213E+09 | 61464616.56 | 60751916.90 | 0.124556E+09 | 99839111.75 |
Maximum of Months | 0.297439E+09 | 0.171917E+09 | 0.181634E+09 | 0.289116E+09 | 0.268436E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_DOOR
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.194965E+09 | 0.115746E+09 | 79218939.19 | 0.150359E+09 | 0.315352E+09 |
February | 0.270905E+09 | 0.167698E+09 | 0.103208E+09 | 0.237705E+09 | 0.250960E+09 |
March | 0.322757E+09 | 0.172182E+09 | 0.150574E+09 | 0.284519E+09 | 0.246863E+09 |
April | 0.329673E+09 | 0.143158E+09 | 0.186516E+09 | 0.273414E+09 | 0.199252E+09 |
May | 0.311423E+09 | 92745642.82 | 0.218677E+09 | 0.228604E+09 | 0.175513E+09 |
June | 0.275729E+09 | 74000163.36 | 0.201728E+09 | 0.192132E+09 | 0.134378E+09 |
July | 0.310709E+09 | 0.113764E+09 | 0.196945E+09 | 0.250275E+09 | 0.122854E+09 |
August | 0.333850E+09 | 0.155666E+09 | 0.178184E+09 | 0.315544E+09 | 0.119248E+09 |
September | 0.358101E+09 | 0.197806E+09 | 0.160295E+09 | 0.348025E+09 | 0.162224E+09 |
October | 0.335174E+09 | 0.206979E+09 | 0.128195E+09 | 0.322187E+09 | 0.228216E+09 |
November | 0.191684E+09 | 0.109835E+09 | 81849442.44 | 0.157460E+09 | 0.256637E+09 |
December | 0.207214E+09 | 0.134072E+09 | 73142110.47 | 0.182527E+09 | 0.319599E+09 |
Annual Sum or Average | 0.344218E+10 | 0.168365E+10 | 0.175853E+10 | 0.294275E+10 | 0.253110E+10 |
Minimum of Months | 0.191684E+09 | 74000163.36 | 73142110.47 | 0.150359E+09 | 0.119248E+09 |
Maximum of Months | 0.358101E+09 | 0.206979E+09 | 0.218677E+09 | 0.348025E+09 | 0.319599E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.161938E+09 | 96138523.70 | 65799337.47 | 0.125295E+09 | 0.253336E+09 |
February | 0.225014E+09 | 0.139290E+09 | 85724535.56 | 0.198325E+09 | 0.201585E+09 |
March | 0.268082E+09 | 0.143015E+09 | 0.125067E+09 | 0.237500E+09 | 0.198498E+09 |
April | 0.273827E+09 | 0.118907E+09 | 0.154920E+09 | 0.228181E+09 | 0.162362E+09 |
May | 0.258668E+09 | 77034632.29 | 0.181634E+09 | 0.189997E+09 | 0.146920E+09 |
June | 0.229021E+09 | 61464616.56 | 0.167556E+09 | 0.159128E+09 | 0.115265E+09 |
July | 0.258075E+09 | 94492485.45 | 0.163583E+09 | 0.207287E+09 | 0.107047E+09 |
August | 0.277296E+09 | 0.129296E+09 | 0.148000E+09 | 0.261728E+09 | 0.104298E+09 |
September | 0.297439E+09 | 0.164298E+09 | 0.133141E+09 | 0.289126E+09 | 0.138029E+09 |
October | 0.278396E+09 | 0.171917E+09 | 0.106479E+09 | 0.268601E+09 | 0.187024E+09 |
November | 0.159213E+09 | 91228882.84 | 67984236.35 | 0.131651E+09 | 0.206488E+09 |
December | 0.172112E+09 | 0.111360E+09 | 60751916.90 | 0.152337E+09 | 0.257287E+09 |
Annual Sum or Average | 0.285908E+10 | 0.139844E+10 | 0.146064E+10 | 0.244916E+10 | 0.207814E+10 |
Minimum of Months | 0.159213E+09 | 61464616.56 | 60751916.90 | 0.125295E+09 | 0.104298E+09 |
Maximum of Months | 0.297439E+09 | 0.171917E+09 | 0.181634E+09 | 0.289126E+09 | 0.257287E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.161938E+09 | 96138523.70 | 65799337.47 | 0.125295E+09 | 0.253336E+09 |
February | 0.225014E+09 | 0.139290E+09 | 85724535.56 | 0.198325E+09 | 0.201585E+09 |
March | 0.268082E+09 | 0.143015E+09 | 0.125067E+09 | 0.237500E+09 | 0.198498E+09 |
April | 0.273827E+09 | 0.118907E+09 | 0.154920E+09 | 0.228181E+09 | 0.162362E+09 |
May | 0.258668E+09 | 77034632.29 | 0.181634E+09 | 0.189997E+09 | 0.146920E+09 |
June | 0.229021E+09 | 61464616.56 | 0.167556E+09 | 0.159128E+09 | 0.115265E+09 |
July | 0.258075E+09 | 94492485.45 | 0.163583E+09 | 0.207287E+09 | 0.107047E+09 |
August | 0.277296E+09 | 0.129296E+09 | 0.148000E+09 | 0.261728E+09 | 0.104298E+09 |
September | 0.297439E+09 | 0.164298E+09 | 0.133141E+09 | 0.289126E+09 | 0.138029E+09 |
October | 0.278396E+09 | 0.171917E+09 | 0.106479E+09 | 0.268601E+09 | 0.187024E+09 |
November | 0.159213E+09 | 91228882.84 | 67984236.35 | 0.131651E+09 | 0.206488E+09 |
December | 0.172112E+09 | 0.111360E+09 | 60751916.90 | 0.152337E+09 | 0.257287E+09 |
Annual Sum or Average | 0.285908E+10 | 0.139844E+10 | 0.146064E+10 | 0.244916E+10 | 0.207814E+10 |
Minimum of Months | 0.159213E+09 | 61464616.56 | 60751916.90 | 0.125295E+09 | 0.104298E+09 |
Maximum of Months | 0.297439E+09 | 0.171917E+09 | 0.181634E+09 | 0.289126E+09 | 0.257287E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_DOOR
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.193899E+09 | 0.115113E+09 | 78786048.81 | 0.150441E+09 | 0.299766E+09 |
February | 0.269425E+09 | 0.166781E+09 | 0.102644E+09 | 0.237899E+09 | 0.238663E+09 |
March | 0.320993E+09 | 0.171242E+09 | 0.149751E+09 | 0.284719E+09 | 0.235008E+09 |
April | 0.327872E+09 | 0.142375E+09 | 0.185496E+09 | 0.273663E+09 | 0.192225E+09 |
May | 0.309721E+09 | 92238836.03 | 0.217482E+09 | 0.227983E+09 | 0.174020E+09 |
June | 0.274222E+09 | 73595790.88 | 0.200626E+09 | 0.190892E+09 | 0.136561E+09 |
July | 0.309011E+09 | 0.113142E+09 | 0.195869E+09 | 0.248296E+09 | 0.126938E+09 |
August | 0.332026E+09 | 0.154815E+09 | 0.177210E+09 | 0.313254E+09 | 0.123759E+09 |
September | 0.356144E+09 | 0.196725E+09 | 0.159419E+09 | 0.346140E+09 | 0.163824E+09 |
October | 0.333343E+09 | 0.205848E+09 | 0.127494E+09 | 0.321834E+09 | 0.221585E+09 |
November | 0.190637E+09 | 0.109235E+09 | 81402177.73 | 0.157921E+09 | 0.244497E+09 |
December | 0.206082E+09 | 0.133339E+09 | 72742426.81 | 0.182685E+09 | 0.304669E+09 |
Annual Sum or Average | 0.342337E+10 | 0.167445E+10 | 0.174892E+10 | 0.293573E+10 | 0.246152E+10 |
Minimum of Months | 0.190637E+09 | 73595790.88 | 72742426.81 | 0.150441E+09 | 0.123759E+09 |
Maximum of Months | 0.356144E+09 | 0.205848E+09 | 0.217482E+09 | 0.346140E+09 | 0.304669E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.161938E+09 | 96138523.70 | 65799337.47 | 0.125683E+09 | 0.249126E+09 |
February | 0.225014E+09 | 0.139290E+09 | 85724535.56 | 0.199002E+09 | 0.198045E+09 |
March | 0.268082E+09 | 0.143015E+09 | 0.125067E+09 | 0.238436E+09 | 0.194183E+09 |
April | 0.273827E+09 | 0.118907E+09 | 0.154920E+09 | 0.229372E+09 | 0.158833E+09 |
May | 0.258668E+09 | 77034632.29 | 0.181634E+09 | 0.190646E+09 | 0.145119E+09 |
June | 0.229021E+09 | 61464616.56 | 0.167556E+09 | 0.159326E+09 | 0.114573E+09 |
July | 0.258075E+09 | 94492485.45 | 0.163583E+09 | 0.207376E+09 | 0.106712E+09 |
August | 0.277296E+09 | 0.129296E+09 | 0.148000E+09 | 0.261771E+09 | 0.104111E+09 |
September | 0.297439E+09 | 0.164298E+09 | 0.133141E+09 | 0.289314E+09 | 0.137146E+09 |
October | 0.278396E+09 | 0.171917E+09 | 0.106479E+09 | 0.269503E+09 | 0.183208E+09 |
November | 0.159213E+09 | 91228882.84 | 67984236.35 | 0.132280E+09 | 0.202486E+09 |
December | 0.172112E+09 | 0.111360E+09 | 60751916.90 | 0.152771E+09 | 0.253405E+09 |
Annual Sum or Average | 0.285908E+10 | 0.139844E+10 | 0.146064E+10 | 0.245548E+10 | 0.204695E+10 |
Minimum of Months | 0.159213E+09 | 61464616.56 | 60751916.90 | 0.125683E+09 | 0.104111E+09 |
Maximum of Months | 0.297439E+09 | 0.171917E+09 | 0.181634E+09 | 0.289314E+09 | 0.253405E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.161938E+09 | 96138523.70 | 65799337.47 | 0.125683E+09 | 0.249126E+09 |
February | 0.225014E+09 | 0.139290E+09 | 85724535.56 | 0.199002E+09 | 0.198045E+09 |
March | 0.268082E+09 | 0.143015E+09 | 0.125067E+09 | 0.238436E+09 | 0.194183E+09 |
April | 0.273827E+09 | 0.118907E+09 | 0.154920E+09 | 0.229372E+09 | 0.158833E+09 |
May | 0.258668E+09 | 77034632.29 | 0.181634E+09 | 0.190646E+09 | 0.145119E+09 |
June | 0.229021E+09 | 61464616.56 | 0.167556E+09 | 0.159326E+09 | 0.114573E+09 |
July | 0.258075E+09 | 94492485.45 | 0.163583E+09 | 0.207376E+09 | 0.106712E+09 |
August | 0.277296E+09 | 0.129296E+09 | 0.148000E+09 | 0.261771E+09 | 0.104111E+09 |
September | 0.297439E+09 | 0.164298E+09 | 0.133141E+09 | 0.289314E+09 | 0.137146E+09 |
October | 0.278396E+09 | 0.171917E+09 | 0.106479E+09 | 0.269503E+09 | 0.183208E+09 |
November | 0.159213E+09 | 91228882.84 | 67984236.35 | 0.132280E+09 | 0.202486E+09 |
December | 0.172112E+09 | 0.111360E+09 | 60751916.90 | 0.152771E+09 | 0.253405E+09 |
Annual Sum or Average | 0.285908E+10 | 0.139844E+10 | 0.146064E+10 | 0.245548E+10 | 0.204695E+10 |
Minimum of Months | 0.159213E+09 | 61464616.56 | 60751916.90 | 0.125683E+09 | 0.104111E+09 |
Maximum of Months | 0.297439E+09 | 0.171917E+09 | 0.181634E+09 | 0.289314E+09 | 0.253405E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_DOOR
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.193899E+09 | 0.115113E+09 | 78786048.81 | 0.150913E+09 | 0.294759E+09 |
February | 0.269425E+09 | 0.166781E+09 | 0.102644E+09 | 0.238716E+09 | 0.234461E+09 |
March | 0.320993E+09 | 0.171242E+09 | 0.149751E+09 | 0.285845E+09 | 0.229894E+09 |
April | 0.327872E+09 | 0.142375E+09 | 0.185496E+09 | 0.275089E+09 | 0.188046E+09 |
May | 0.309721E+09 | 92238836.03 | 0.217482E+09 | 0.228760E+09 | 0.171885E+09 |
June | 0.274222E+09 | 73595790.88 | 0.200626E+09 | 0.191132E+09 | 0.135741E+09 |
July | 0.309011E+09 | 0.113142E+09 | 0.195869E+09 | 0.248404E+09 | 0.126541E+09 |
August | 0.332026E+09 | 0.154815E+09 | 0.177210E+09 | 0.313306E+09 | 0.123537E+09 |
September | 0.356144E+09 | 0.196725E+09 | 0.159419E+09 | 0.346367E+09 | 0.162774E+09 |
October | 0.333343E+09 | 0.205848E+09 | 0.127494E+09 | 0.322920E+09 | 0.217072E+09 |
November | 0.190637E+09 | 0.109235E+09 | 81402177.73 | 0.158682E+09 | 0.239749E+09 |
December | 0.206082E+09 | 0.133339E+09 | 72742426.81 | 0.183210E+09 | 0.300051E+09 |
Annual Sum or Average | 0.342337E+10 | 0.167445E+10 | 0.174892E+10 | 0.294334E+10 | 0.242451E+10 |
Minimum of Months | 0.190637E+09 | 73595790.88 | 72742426.81 | 0.150913E+09 | 0.123537E+09 |
Maximum of Months | 0.356144E+09 | 0.205848E+09 | 0.217482E+09 | 0.346367E+09 | 0.300051E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.161938E+09 | 96138523.70 | 65799337.47 | 0.126118E+09 | 0.245967E+09 |
February | 0.225014E+09 | 0.139290E+09 | 85724535.56 | 0.199752E+09 | 0.195288E+09 |
March | 0.268082E+09 | 0.143015E+09 | 0.125067E+09 | 0.239581E+09 | 0.190133E+09 |
April | 0.273827E+09 | 0.118907E+09 | 0.154920E+09 | 0.231072E+09 | 0.154958E+09 |
May | 0.258668E+09 | 77034632.29 | 0.181634E+09 | 0.192008E+09 | 0.142429E+09 |
June | 0.229021E+09 | 61464616.56 | 0.167556E+09 | 0.159981E+09 | 0.113061E+09 |
July | 0.258075E+09 | 94492485.45 | 0.163583E+09 | 0.207823E+09 | 0.105458E+09 |
August | 0.277296E+09 | 0.129296E+09 | 0.148000E+09 | 0.262189E+09 | 0.102886E+09 |
September | 0.297439E+09 | 0.164298E+09 | 0.133141E+09 | 0.289855E+09 | 0.135414E+09 |
October | 0.278396E+09 | 0.171917E+09 | 0.106479E+09 | 0.270843E+09 | 0.178698E+09 |
November | 0.159213E+09 | 91228882.84 | 67984236.35 | 0.133050E+09 | 0.198980E+09 |
December | 0.172112E+09 | 0.111360E+09 | 60751916.90 | 0.153222E+09 | 0.250545E+09 |
Annual Sum or Average | 0.285908E+10 | 0.139844E+10 | 0.146064E+10 | 0.246549E+10 | 0.201382E+10 |
Minimum of Months | 0.159213E+09 | 61464616.56 | 60751916.90 | 0.126118E+09 | 0.102886E+09 |
Maximum of Months | 0.297439E+09 | 0.171917E+09 | 0.181634E+09 | 0.289855E+09 | 0.250545E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.161938E+09 | 96138523.70 | 65799337.47 | 0.126118E+09 | 0.245967E+09 |
February | 0.225014E+09 | 0.139290E+09 | 85724535.56 | 0.199752E+09 | 0.195288E+09 |
March | 0.268082E+09 | 0.143015E+09 | 0.125067E+09 | 0.239581E+09 | 0.190133E+09 |
April | 0.273827E+09 | 0.118907E+09 | 0.154920E+09 | 0.231072E+09 | 0.154958E+09 |
May | 0.258668E+09 | 77034632.29 | 0.181634E+09 | 0.192008E+09 | 0.142429E+09 |
June | 0.229021E+09 | 61464616.56 | 0.167556E+09 | 0.159981E+09 | 0.113061E+09 |
July | 0.258075E+09 | 94492485.45 | 0.163583E+09 | 0.207823E+09 | 0.105458E+09 |
August | 0.277296E+09 | 0.129296E+09 | 0.148000E+09 | 0.262189E+09 | 0.102886E+09 |
September | 0.297439E+09 | 0.164298E+09 | 0.133141E+09 | 0.289855E+09 | 0.135414E+09 |
October | 0.278396E+09 | 0.171917E+09 | 0.106479E+09 | 0.270843E+09 | 0.178698E+09 |
November | 0.159213E+09 | 91228882.84 | 67984236.35 | 0.133050E+09 | 0.198980E+09 |
December | 0.172112E+09 | 0.111360E+09 | 60751916.90 | 0.153222E+09 | 0.250545E+09 |
Annual Sum or Average | 0.285908E+10 | 0.139844E+10 | 0.146064E+10 | 0.246549E+10 | 0.201382E+10 |
Minimum of Months | 0.159213E+09 | 61464616.56 | 60751916.90 | 0.126118E+09 | 0.102886E+09 |
Maximum of Months | 0.297439E+09 | 0.171917E+09 | 0.181634E+09 | 0.289855E+09 | 0.250545E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_DOOR
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.193899E+09 | 0.115113E+09 | 78786048.81 | 0.151443E+09 | 0.291001E+09 |
February | 0.269425E+09 | 0.166781E+09 | 0.102644E+09 | 0.239622E+09 | 0.231190E+09 |
March | 0.320993E+09 | 0.171242E+09 | 0.149751E+09 | 0.287221E+09 | 0.225097E+09 |
April | 0.327872E+09 | 0.142375E+09 | 0.185496E+09 | 0.277125E+09 | 0.183467E+09 |
May | 0.309721E+09 | 92238836.03 | 0.217482E+09 | 0.230394E+09 | 0.168706E+09 |
June | 0.274222E+09 | 73595790.88 | 0.200626E+09 | 0.191921E+09 | 0.133955E+09 |
July | 0.309011E+09 | 0.113142E+09 | 0.195869E+09 | 0.248943E+09 | 0.125058E+09 |
August | 0.332026E+09 | 0.154815E+09 | 0.177210E+09 | 0.313811E+09 | 0.122090E+09 |
September | 0.356144E+09 | 0.196725E+09 | 0.159419E+09 | 0.347021E+09 | 0.160721E+09 |
October | 0.333343E+09 | 0.205848E+09 | 0.127494E+09 | 0.324526E+09 | 0.211741E+09 |
November | 0.190637E+09 | 0.109235E+09 | 81402177.73 | 0.159611E+09 | 0.235595E+09 |
December | 0.206082E+09 | 0.133339E+09 | 72742426.81 | 0.183757E+09 | 0.296649E+09 |
Annual Sum or Average | 0.342337E+10 | 0.167445E+10 | 0.174892E+10 | 0.295540E+10 | 0.238527E+10 |
Minimum of Months | 0.190637E+09 | 73595790.88 | 72742426.81 | 0.151443E+09 | 0.122090E+09 |
Maximum of Months | 0.356144E+09 | 0.205848E+09 | 0.217482E+09 | 0.347021E+09 | 0.296649E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.161938E+09 | 96138523.70 | 65799337.47 | 0.127885E+09 | 0.235871E+09 |
February | 0.225014E+09 | 0.139290E+09 | 85724535.56 | 0.202285E+09 | 0.187317E+09 |
March | 0.268082E+09 | 0.143015E+09 | 0.125067E+09 | 0.242621E+09 | 0.180673E+09 |
April | 0.273827E+09 | 0.118907E+09 | 0.154920E+09 | 0.235039E+09 | 0.146215E+09 |
May | 0.258668E+09 | 77034632.29 | 0.181634E+09 | 0.195898E+09 | 0.135136E+09 |
June | 0.229021E+09 | 61464616.56 | 0.167556E+09 | 0.161973E+09 | 0.108095E+09 |
July | 0.258075E+09 | 94492485.45 | 0.163583E+09 | 0.208972E+09 | 0.101178E+09 |
August | 0.277296E+09 | 0.129296E+09 | 0.148000E+09 | 0.263295E+09 | 98579013.38 |
September | 0.297439E+09 | 0.164298E+09 | 0.133141E+09 | 0.291665E+09 | 0.130204E+09 |
October | 0.278396E+09 | 0.171917E+09 | 0.106479E+09 | 0.274187E+09 | 0.168921E+09 |
November | 0.159213E+09 | 91228882.84 | 67984236.35 | 0.135175E+09 | 0.190166E+09 |
December | 0.172112E+09 | 0.111360E+09 | 60751916.90 | 0.154875E+09 | 0.241445E+09 |
Annual Sum or Average | 0.285908E+10 | 0.139844E+10 | 0.146064E+10 | 0.249387E+10 | 0.192380E+10 |
Minimum of Months | 0.159213E+09 | 61464616.56 | 60751916.90 | 0.127885E+09 | 98579013.38 |
Maximum of Months | 0.297439E+09 | 0.171917E+09 | 0.181634E+09 | 0.291665E+09 | 0.241445E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.161938E+09 | 96138523.70 | 65799337.47 | 0.127885E+09 | 0.235871E+09 |
February | 0.225014E+09 | 0.139290E+09 | 85724535.56 | 0.202285E+09 | 0.187317E+09 |
March | 0.268082E+09 | 0.143015E+09 | 0.125067E+09 | 0.242621E+09 | 0.180673E+09 |
April | 0.273827E+09 | 0.118907E+09 | 0.154920E+09 | 0.235039E+09 | 0.146215E+09 |
May | 0.258668E+09 | 77034632.29 | 0.181634E+09 | 0.195898E+09 | 0.135136E+09 |
June | 0.229021E+09 | 61464616.56 | 0.167556E+09 | 0.161973E+09 | 0.108095E+09 |
July | 0.258075E+09 | 94492485.45 | 0.163583E+09 | 0.208972E+09 | 0.101178E+09 |
August | 0.277296E+09 | 0.129296E+09 | 0.148000E+09 | 0.263295E+09 | 98579013.38 |
September | 0.297439E+09 | 0.164298E+09 | 0.133141E+09 | 0.291665E+09 | 0.130204E+09 |
October | 0.278396E+09 | 0.171917E+09 | 0.106479E+09 | 0.274187E+09 | 0.168921E+09 |
November | 0.159213E+09 | 91228882.84 | 67984236.35 | 0.135175E+09 | 0.190166E+09 |
December | 0.172112E+09 | 0.111360E+09 | 60751916.90 | 0.154875E+09 | 0.241445E+09 |
Annual Sum or Average | 0.285908E+10 | 0.139844E+10 | 0.146064E+10 | 0.249387E+10 | 0.192380E+10 |
Minimum of Months | 0.159213E+09 | 61464616.56 | 60751916.90 | 0.127885E+09 | 98579013.38 |
Maximum of Months | 0.297439E+09 | 0.171917E+09 | 0.181634E+09 | 0.291665E+09 | 0.241445E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_3
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.161938E+09 | 96138523.70 | 65799337.47 | 0.127885E+09 | 0.235871E+09 |
February | 0.225014E+09 | 0.139290E+09 | 85724535.56 | 0.202285E+09 | 0.187317E+09 |
March | 0.268082E+09 | 0.143015E+09 | 0.125067E+09 | 0.242621E+09 | 0.180673E+09 |
April | 0.273827E+09 | 0.118907E+09 | 0.154920E+09 | 0.235039E+09 | 0.146215E+09 |
May | 0.258668E+09 | 77034632.29 | 0.181634E+09 | 0.195898E+09 | 0.135136E+09 |
June | 0.229021E+09 | 61464616.56 | 0.167556E+09 | 0.161973E+09 | 0.108095E+09 |
July | 0.258075E+09 | 94492485.45 | 0.163583E+09 | 0.208972E+09 | 0.101178E+09 |
August | 0.277296E+09 | 0.129296E+09 | 0.148000E+09 | 0.263295E+09 | 98579013.38 |
September | 0.297439E+09 | 0.164298E+09 | 0.133141E+09 | 0.291665E+09 | 0.130204E+09 |
October | 0.278396E+09 | 0.171917E+09 | 0.106479E+09 | 0.274187E+09 | 0.168921E+09 |
November | 0.159213E+09 | 91228882.84 | 67984236.35 | 0.135175E+09 | 0.190166E+09 |
December | 0.172112E+09 | 0.111360E+09 | 60751916.90 | 0.154875E+09 | 0.241445E+09 |
Annual Sum or Average | 0.285908E+10 | 0.139844E+10 | 0.146064E+10 | 0.249387E+10 | 0.192380E+10 |
Minimum of Months | 0.159213E+09 | 61464616.56 | 60751916.90 | 0.127885E+09 | 98579013.38 |
Maximum of Months | 0.297439E+09 | 0.171917E+09 | 0.181634E+09 | 0.291665E+09 | 0.241445E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_4
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.161938E+09 | 96138523.70 | 65799337.47 | 0.127885E+09 | 0.235871E+09 |
February | 0.225014E+09 | 0.139290E+09 | 85724535.56 | 0.202285E+09 | 0.187317E+09 |
March | 0.268082E+09 | 0.143015E+09 | 0.125067E+09 | 0.242621E+09 | 0.180673E+09 |
April | 0.273827E+09 | 0.118907E+09 | 0.154920E+09 | 0.235039E+09 | 0.146215E+09 |
May | 0.258668E+09 | 77034632.29 | 0.181634E+09 | 0.195898E+09 | 0.135136E+09 |
June | 0.229021E+09 | 61464616.56 | 0.167556E+09 | 0.161973E+09 | 0.108095E+09 |
July | 0.258075E+09 | 94492485.45 | 0.163583E+09 | 0.208972E+09 | 0.101178E+09 |
August | 0.277296E+09 | 0.129296E+09 | 0.148000E+09 | 0.263295E+09 | 98579013.38 |
September | 0.297439E+09 | 0.164298E+09 | 0.133141E+09 | 0.291665E+09 | 0.130204E+09 |
October | 0.278396E+09 | 0.171917E+09 | 0.106479E+09 | 0.274187E+09 | 0.168921E+09 |
November | 0.159213E+09 | 91228882.84 | 67984236.35 | 0.135175E+09 | 0.190166E+09 |
December | 0.172112E+09 | 0.111360E+09 | 60751916.90 | 0.154875E+09 | 0.241445E+09 |
Annual Sum or Average | 0.285908E+10 | 0.139844E+10 | 0.146064E+10 | 0.249387E+10 | 0.192380E+10 |
Minimum of Months | 0.159213E+09 | 61464616.56 | 60751916.90 | 0.127885E+09 | 98579013.38 |
Maximum of Months | 0.297439E+09 | 0.171917E+09 | 0.181634E+09 | 0.291665E+09 | 0.241445E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_DOOR_1
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.193899E+09 | 0.115113E+09 | 78786048.81 | 0.153571E+09 | 0.279084E+09 |
February | 0.269425E+09 | 0.166781E+09 | 0.102644E+09 | 0.242655E+09 | 0.221800E+09 |
March | 0.320993E+09 | 0.171242E+09 | 0.149751E+09 | 0.290850E+09 | 0.213945E+09 |
April | 0.327872E+09 | 0.142375E+09 | 0.185496E+09 | 0.281855E+09 | 0.173178E+09 |
May | 0.309721E+09 | 92238836.03 | 0.217482E+09 | 0.235029E+09 | 0.160118E+09 |
June | 0.274222E+09 | 73595790.88 | 0.200626E+09 | 0.194324E+09 | 0.128115E+09 |
July | 0.309011E+09 | 0.113142E+09 | 0.195869E+09 | 0.250341E+09 | 0.120015E+09 |
August | 0.332026E+09 | 0.154815E+09 | 0.177210E+09 | 0.315157E+09 | 0.117009E+09 |
September | 0.356144E+09 | 0.196725E+09 | 0.159419E+09 | 0.349191E+09 | 0.154563E+09 |
October | 0.333343E+09 | 0.205848E+09 | 0.127494E+09 | 0.328502E+09 | 0.200214E+09 |
November | 0.190637E+09 | 0.109235E+09 | 81402177.73 | 0.162155E+09 | 0.225197E+09 |
December | 0.206082E+09 | 0.133339E+09 | 72742426.81 | 0.185736E+09 | 0.285883E+09 |
Annual Sum or Average | 0.342337E+10 | 0.167445E+10 | 0.174892E+10 | 0.298937E+10 | 0.227912E+10 |
Minimum of Months | 0.190637E+09 | 73595790.88 | 72742426.81 | 0.153571E+09 | 0.117009E+09 |
Maximum of Months | 0.356144E+09 | 0.205848E+09 | 0.217482E+09 | 0.349191E+09 | 0.285883E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_DOOR_2
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.193899E+09 | 0.115113E+09 | 78786048.81 | 0.153571E+09 | 0.279084E+09 |
February | 0.269425E+09 | 0.166781E+09 | 0.102644E+09 | 0.242655E+09 | 0.221800E+09 |
March | 0.320993E+09 | 0.171242E+09 | 0.149751E+09 | 0.290850E+09 | 0.213945E+09 |
April | 0.327872E+09 | 0.142375E+09 | 0.185496E+09 | 0.281855E+09 | 0.173178E+09 |
May | 0.309721E+09 | 92238836.03 | 0.217482E+09 | 0.235029E+09 | 0.160118E+09 |
June | 0.274222E+09 | 73595790.88 | 0.200626E+09 | 0.194324E+09 | 0.128115E+09 |
July | 0.309011E+09 | 0.113142E+09 | 0.195869E+09 | 0.250341E+09 | 0.120015E+09 |
August | 0.332026E+09 | 0.154815E+09 | 0.177210E+09 | 0.315157E+09 | 0.117009E+09 |
September | 0.356144E+09 | 0.196725E+09 | 0.159419E+09 | 0.349191E+09 | 0.154563E+09 |
October | 0.333343E+09 | 0.205848E+09 | 0.127494E+09 | 0.328502E+09 | 0.200214E+09 |
November | 0.190637E+09 | 0.109235E+09 | 81402177.73 | 0.162155E+09 | 0.225197E+09 |
December | 0.206082E+09 | 0.133339E+09 | 72742426.81 | 0.185736E+09 | 0.285883E+09 |
Annual Sum or Average | 0.342337E+10 | 0.167445E+10 | 0.174892E+10 | 0.298937E+10 | 0.227912E+10 |
Minimum of Months | 0.190637E+09 | 73595790.88 | 72742426.81 | 0.153571E+09 | 0.117009E+09 |
Maximum of Months | 0.356144E+09 | 0.205848E+09 | 0.217482E+09 | 0.349191E+09 | 0.285883E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.161938E+09 | 96138523.70 | 65799337.47 | 0.127371E+09 | 0.237083E+09 |
February | 0.225014E+09 | 0.139290E+09 | 85724535.56 | 0.201798E+09 | 0.187814E+09 |
March | 0.268082E+09 | 0.143015E+09 | 0.125067E+09 | 0.242371E+09 | 0.180330E+09 |
April | 0.273827E+09 | 0.118907E+09 | 0.154920E+09 | 0.235281E+09 | 0.145354E+09 |
May | 0.258668E+09 | 77034632.29 | 0.181634E+09 | 0.196678E+09 | 0.133848E+09 |
June | 0.229021E+09 | 61464616.56 | 0.167556E+09 | 0.162394E+09 | 0.107370E+09 |
July | 0.258075E+09 | 94492485.45 | 0.163583E+09 | 0.209410E+09 | 0.100418E+09 |
August | 0.277296E+09 | 0.129296E+09 | 0.148000E+09 | 0.263618E+09 | 97740573.49 |
September | 0.297439E+09 | 0.164298E+09 | 0.133141E+09 | 0.291813E+09 | 0.129241E+09 |
October | 0.278396E+09 | 0.171917E+09 | 0.106479E+09 | 0.274148E+09 | 0.167727E+09 |
November | 0.159213E+09 | 91228882.84 | 67984236.35 | 0.134954E+09 | 0.190317E+09 |
December | 0.172112E+09 | 0.111360E+09 | 60751916.90 | 0.154459E+09 | 0.242361E+09 |
Annual Sum or Average | 0.285908E+10 | 0.139844E+10 | 0.146064E+10 | 0.249429E+10 | 0.191960E+10 |
Minimum of Months | 0.159213E+09 | 61464616.56 | 60751916.90 | 0.127371E+09 | 97740573.49 |
Maximum of Months | 0.297439E+09 | 0.171917E+09 | 0.181634E+09 | 0.291813E+09 | 0.242361E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.161938E+09 | 96138523.70 | 65799337.47 | 0.127371E+09 | 0.237083E+09 |
February | 0.225014E+09 | 0.139290E+09 | 85724535.56 | 0.201798E+09 | 0.187814E+09 |
March | 0.268082E+09 | 0.143015E+09 | 0.125067E+09 | 0.242371E+09 | 0.180330E+09 |
April | 0.273827E+09 | 0.118907E+09 | 0.154920E+09 | 0.235281E+09 | 0.145354E+09 |
May | 0.258668E+09 | 77034632.29 | 0.181634E+09 | 0.196678E+09 | 0.133848E+09 |
June | 0.229021E+09 | 61464616.56 | 0.167556E+09 | 0.162394E+09 | 0.107370E+09 |
July | 0.258075E+09 | 94492485.45 | 0.163583E+09 | 0.209410E+09 | 0.100418E+09 |
August | 0.277296E+09 | 0.129296E+09 | 0.148000E+09 | 0.263618E+09 | 97740573.49 |
September | 0.297439E+09 | 0.164298E+09 | 0.133141E+09 | 0.291813E+09 | 0.129241E+09 |
October | 0.278396E+09 | 0.171917E+09 | 0.106479E+09 | 0.274148E+09 | 0.167727E+09 |
November | 0.159213E+09 | 91228882.84 | 67984236.35 | 0.134954E+09 | 0.190317E+09 |
December | 0.172112E+09 | 0.111360E+09 | 60751916.90 | 0.154459E+09 | 0.242361E+09 |
Annual Sum or Average | 0.285908E+10 | 0.139844E+10 | 0.146064E+10 | 0.249429E+10 | 0.191960E+10 |
Minimum of Months | 0.159213E+09 | 61464616.56 | 60751916.90 | 0.127371E+09 | 97740573.49 |
Maximum of Months | 0.297439E+09 | 0.171917E+09 | 0.181634E+09 | 0.291813E+09 | 0.242361E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_DOOR
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.193899E+09 | 0.115113E+09 | 78786048.81 | 0.152987E+09 | 0.280419E+09 |
February | 0.269425E+09 | 0.166781E+09 | 0.102644E+09 | 0.242117E+09 | 0.222312E+09 |
March | 0.320993E+09 | 0.171242E+09 | 0.149751E+09 | 0.290599E+09 | 0.213461E+09 |
April | 0.327872E+09 | 0.142375E+09 | 0.185496E+09 | 0.282190E+09 | 0.172096E+09 |
May | 0.309721E+09 | 92238836.03 | 0.217482E+09 | 0.236000E+09 | 0.158540E+09 |
June | 0.274222E+09 | 73595790.88 | 0.200626E+09 | 0.194860E+09 | 0.127218E+09 |
July | 0.309011E+09 | 0.113142E+09 | 0.195869E+09 | 0.250891E+09 | 0.119082E+09 |
August | 0.332026E+09 | 0.154815E+09 | 0.177210E+09 | 0.315575E+09 | 0.115986E+09 |
September | 0.356144E+09 | 0.196725E+09 | 0.159419E+09 | 0.349409E+09 | 0.153388E+09 |
October | 0.333343E+09 | 0.205848E+09 | 0.127494E+09 | 0.328507E+09 | 0.198736E+09 |
November | 0.190637E+09 | 0.109235E+09 | 81402177.73 | 0.161925E+09 | 0.225296E+09 |
December | 0.206082E+09 | 0.133339E+09 | 72742426.81 | 0.185273E+09 | 0.286881E+09 |
Annual Sum or Average | 0.342337E+10 | 0.167445E+10 | 0.174892E+10 | 0.299033E+10 | 0.227342E+10 |
Minimum of Months | 0.190637E+09 | 73595790.88 | 72742426.81 | 0.152987E+09 | 0.115986E+09 |
Maximum of Months | 0.356144E+09 | 0.205848E+09 | 0.217482E+09 | 0.349409E+09 | 0.286881E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.161938E+09 | 96138523.70 | 65799337.47 | 0.127515E+09 | 0.236069E+09 |
February | 0.225014E+09 | 0.139290E+09 | 85724535.56 | 0.202049E+09 | 0.186876E+09 |
March | 0.268082E+09 | 0.143015E+09 | 0.125067E+09 | 0.242731E+09 | 0.179017E+09 |
April | 0.273827E+09 | 0.118907E+09 | 0.154920E+09 | 0.235943E+09 | 0.143859E+09 |
May | 0.258668E+09 | 77034632.29 | 0.181634E+09 | 0.197794E+09 | 0.131968E+09 |
June | 0.229021E+09 | 61464616.56 | 0.167556E+09 | 0.162992E+09 | 0.106387E+09 |
July | 0.258075E+09 | 94492485.45 | 0.163583E+09 | 0.209747E+09 | 99748545.15 |
August | 0.277296E+09 | 0.129296E+09 | 0.148000E+09 | 0.263903E+09 | 97160628.33 |
September | 0.297439E+09 | 0.164298E+09 | 0.133141E+09 | 0.292243E+09 | 0.128222E+09 |
October | 0.278396E+09 | 0.171917E+09 | 0.106479E+09 | 0.274694E+09 | 0.166058E+09 |
November | 0.159213E+09 | 91228882.84 | 67984236.35 | 0.135194E+09 | 0.189272E+09 |
December | 0.172112E+09 | 0.111360E+09 | 60751916.90 | 0.154608E+09 | 0.241403E+09 |
Annual Sum or Average | 0.285908E+10 | 0.139844E+10 | 0.146064E+10 | 0.249941E+10 | 0.190604E+10 |
Minimum of Months | 0.159213E+09 | 61464616.56 | 60751916.90 | 0.127515E+09 | 97160628.33 |
Maximum of Months | 0.297439E+09 | 0.171917E+09 | 0.181634E+09 | 0.292243E+09 | 0.241403E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.161938E+09 | 96138523.70 | 65799337.47 | 0.127515E+09 | 0.236069E+09 |
February | 0.225014E+09 | 0.139290E+09 | 85724535.56 | 0.202049E+09 | 0.186876E+09 |
March | 0.268082E+09 | 0.143015E+09 | 0.125067E+09 | 0.242731E+09 | 0.179017E+09 |
April | 0.273827E+09 | 0.118907E+09 | 0.154920E+09 | 0.235943E+09 | 0.143859E+09 |
May | 0.258668E+09 | 77034632.29 | 0.181634E+09 | 0.197794E+09 | 0.131968E+09 |
June | 0.229021E+09 | 61464616.56 | 0.167556E+09 | 0.162992E+09 | 0.106387E+09 |
July | 0.258075E+09 | 94492485.45 | 0.163583E+09 | 0.209747E+09 | 99748545.15 |
August | 0.277296E+09 | 0.129296E+09 | 0.148000E+09 | 0.263903E+09 | 97160628.33 |
September | 0.297439E+09 | 0.164298E+09 | 0.133141E+09 | 0.292243E+09 | 0.128222E+09 |
October | 0.278396E+09 | 0.171917E+09 | 0.106479E+09 | 0.274694E+09 | 0.166058E+09 |
November | 0.159213E+09 | 91228882.84 | 67984236.35 | 0.135194E+09 | 0.189272E+09 |
December | 0.172112E+09 | 0.111360E+09 | 60751916.90 | 0.154608E+09 | 0.241403E+09 |
Annual Sum or Average | 0.285908E+10 | 0.139844E+10 | 0.146064E+10 | 0.249941E+10 | 0.190604E+10 |
Minimum of Months | 0.159213E+09 | 61464616.56 | 60751916.90 | 0.127515E+09 | 97160628.33 |
Maximum of Months | 0.297439E+09 | 0.171917E+09 | 0.181634E+09 | 0.292243E+09 | 0.241403E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_DOOR
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.193899E+09 | 0.115113E+09 | 78786048.81 | 0.153164E+09 | 0.279212E+09 |
February | 0.269425E+09 | 0.166781E+09 | 0.102644E+09 | 0.242420E+09 | 0.221196E+09 |
March | 0.320993E+09 | 0.171242E+09 | 0.149751E+09 | 0.291035E+09 | 0.211902E+09 |
April | 0.327872E+09 | 0.142375E+09 | 0.185496E+09 | 0.282987E+09 | 0.170327E+09 |
May | 0.309721E+09 | 92238836.03 | 0.217482E+09 | 0.237337E+09 | 0.156317E+09 |
June | 0.274222E+09 | 73595790.88 | 0.200626E+09 | 0.195579E+09 | 0.126056E+09 |
July | 0.309011E+09 | 0.113142E+09 | 0.195869E+09 | 0.251298E+09 | 0.118288E+09 |
August | 0.332026E+09 | 0.154815E+09 | 0.177210E+09 | 0.315919E+09 | 0.115297E+09 |
September | 0.356144E+09 | 0.196725E+09 | 0.159419E+09 | 0.349927E+09 | 0.152177E+09 |
October | 0.333343E+09 | 0.205848E+09 | 0.127494E+09 | 0.329163E+09 | 0.196758E+09 |
November | 0.190637E+09 | 0.109235E+09 | 81402177.73 | 0.162214E+09 | 0.224054E+09 |
December | 0.206082E+09 | 0.133339E+09 | 72742426.81 | 0.185454E+09 | 0.285741E+09 |
Annual Sum or Average | 0.342337E+10 | 0.167445E+10 | 0.174892E+10 | 0.299650E+10 | 0.225733E+10 |
Minimum of Months | 0.190637E+09 | 73595790.88 | 72742426.81 | 0.153164E+09 | 0.115297E+09 |
Maximum of Months | 0.356144E+09 | 0.205848E+09 | 0.217482E+09 | 0.349927E+09 | 0.285741E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.161938E+09 | 96138523.70 | 65799337.47 | 0.127985E+09 | 0.232298E+09 |
February | 0.225014E+09 | 0.139290E+09 | 85724535.56 | 0.202785E+09 | 0.183602E+09 |
March | 0.268082E+09 | 0.143015E+09 | 0.125067E+09 | 0.243624E+09 | 0.175229E+09 |
April | 0.273827E+09 | 0.118907E+09 | 0.154920E+09 | 0.237396E+09 | 0.140106E+09 |
May | 0.258668E+09 | 77034632.29 | 0.181634E+09 | 0.200125E+09 | 0.127622E+09 |
June | 0.229021E+09 | 61464616.56 | 0.167556E+09 | 0.164484E+09 | 0.103729E+09 |
July | 0.258075E+09 | 94492485.45 | 0.163583E+09 | 0.210532E+09 | 97903158.79 |
August | 0.277296E+09 | 0.129296E+09 | 0.148000E+09 | 0.264497E+09 | 95647342.60 |
September | 0.297439E+09 | 0.164298E+09 | 0.133141E+09 | 0.293208E+09 | 0.125702E+09 |
October | 0.278396E+09 | 0.171917E+09 | 0.106479E+09 | 0.275827E+09 | 0.162419E+09 |
November | 0.159213E+09 | 91228882.84 | 67984236.35 | 0.135760E+09 | 0.186341E+09 |
December | 0.172112E+09 | 0.111360E+09 | 60751916.90 | 0.155067E+09 | 0.238008E+09 |
Annual Sum or Average | 0.285908E+10 | 0.139844E+10 | 0.146064E+10 | 0.251129E+10 | 0.186861E+10 |
Minimum of Months | 0.159213E+09 | 61464616.56 | 60751916.90 | 0.127985E+09 | 95647342.60 |
Maximum of Months | 0.297439E+09 | 0.171917E+09 | 0.181634E+09 | 0.293208E+09 | 0.238008E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.161938E+09 | 96138523.70 | 65799337.47 | 0.127985E+09 | 0.232298E+09 |
February | 0.225014E+09 | 0.139290E+09 | 85724535.56 | 0.202785E+09 | 0.183602E+09 |
March | 0.268082E+09 | 0.143015E+09 | 0.125067E+09 | 0.243624E+09 | 0.175229E+09 |
April | 0.273827E+09 | 0.118907E+09 | 0.154920E+09 | 0.237396E+09 | 0.140106E+09 |
May | 0.258668E+09 | 77034632.29 | 0.181634E+09 | 0.200125E+09 | 0.127622E+09 |
June | 0.229021E+09 | 61464616.56 | 0.167556E+09 | 0.164484E+09 | 0.103729E+09 |
July | 0.258075E+09 | 94492485.45 | 0.163583E+09 | 0.210532E+09 | 97903158.79 |
August | 0.277296E+09 | 0.129296E+09 | 0.148000E+09 | 0.264497E+09 | 95647342.60 |
September | 0.297439E+09 | 0.164298E+09 | 0.133141E+09 | 0.293208E+09 | 0.125702E+09 |
October | 0.278396E+09 | 0.171917E+09 | 0.106479E+09 | 0.275827E+09 | 0.162419E+09 |
November | 0.159213E+09 | 91228882.84 | 67984236.35 | 0.135760E+09 | 0.186341E+09 |
December | 0.172112E+09 | 0.111360E+09 | 60751916.90 | 0.155067E+09 | 0.238008E+09 |
Annual Sum or Average | 0.285908E+10 | 0.139844E+10 | 0.146064E+10 | 0.251129E+10 | 0.186861E+10 |
Minimum of Months | 0.159213E+09 | 61464616.56 | 60751916.90 | 0.127985E+09 | 95647342.60 |
Maximum of Months | 0.297439E+09 | 0.171917E+09 | 0.181634E+09 | 0.293208E+09 | 0.238008E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_DOOR
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.193899E+09 | 0.115113E+09 | 78786048.81 | 0.153739E+09 | 0.274730E+09 |
February | 0.269425E+09 | 0.166781E+09 | 0.102644E+09 | 0.243314E+09 | 0.217312E+09 |
March | 0.320993E+09 | 0.171242E+09 | 0.149751E+09 | 0.292116E+09 | 0.207408E+09 |
April | 0.327872E+09 | 0.142375E+09 | 0.185496E+09 | 0.284732E+09 | 0.165887E+09 |
May | 0.309721E+09 | 92238836.03 | 0.217482E+09 | 0.240121E+09 | 0.151175E+09 |
June | 0.274222E+09 | 73595790.88 | 0.200626E+09 | 0.197366E+09 | 0.122914E+09 |
July | 0.309011E+09 | 0.113142E+09 | 0.195869E+09 | 0.252247E+09 | 0.116109E+09 |
August | 0.332026E+09 | 0.154815E+09 | 0.177210E+09 | 0.316636E+09 | 0.113507E+09 |
September | 0.356144E+09 | 0.196725E+09 | 0.159419E+09 | 0.351084E+09 | 0.149195E+09 |
October | 0.333343E+09 | 0.205848E+09 | 0.127494E+09 | 0.330522E+09 | 0.192453E+09 |
November | 0.190637E+09 | 0.109235E+09 | 81402177.73 | 0.162901E+09 | 0.220577E+09 |
December | 0.206082E+09 | 0.133339E+09 | 72742426.81 | 0.186010E+09 | 0.281700E+09 |
Annual Sum or Average | 0.342337E+10 | 0.167445E+10 | 0.174892E+10 | 0.301079E+10 | 0.221297E+10 |
Minimum of Months | 0.190637E+09 | 73595790.88 | 72742426.81 | 0.153739E+09 | 0.113507E+09 |
Maximum of Months | 0.356144E+09 | 0.205848E+09 | 0.217482E+09 | 0.351084E+09 | 0.281700E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.161938E+09 | 96138523.70 | 65799337.47 | 0.129816E+09 | 0.217132E+09 |
February | 0.225014E+09 | 0.139290E+09 | 85724535.56 | 0.205419E+09 | 0.170525E+09 |
March | 0.268082E+09 | 0.143015E+09 | 0.125067E+09 | 0.246585E+09 | 0.160667E+09 |
April | 0.273827E+09 | 0.118907E+09 | 0.154920E+09 | 0.241320E+09 | 0.127094E+09 |
May | 0.258668E+09 | 77034632.29 | 0.181634E+09 | 0.205660E+09 | 0.114585E+09 |
June | 0.229021E+09 | 61464616.56 | 0.167556E+09 | 0.168931E+09 | 94159149.05 |
July | 0.258075E+09 | 94492485.45 | 0.163583E+09 | 0.213245E+09 | 90362704.81 |
August | 0.277296E+09 | 0.129296E+09 | 0.148000E+09 | 0.266453E+09 | 89280616.18 |
September | 0.297439E+09 | 0.164298E+09 | 0.133141E+09 | 0.295833E+09 | 0.117457E+09 |
October | 0.278396E+09 | 0.171917E+09 | 0.106479E+09 | 0.278694E+09 | 0.151375E+09 |
November | 0.159213E+09 | 91228882.84 | 67984236.35 | 0.137515E+09 | 0.175526E+09 |
December | 0.172112E+09 | 0.111360E+09 | 60751916.90 | 0.156761E+09 | 0.224495E+09 |
Annual Sum or Average | 0.285908E+10 | 0.139844E+10 | 0.146064E+10 | 0.254623E+10 | 0.173266E+10 |
Minimum of Months | 0.159213E+09 | 61464616.56 | 60751916.90 | 0.129816E+09 | 89280616.18 |
Maximum of Months | 0.297439E+09 | 0.171917E+09 | 0.181634E+09 | 0.295833E+09 | 0.224495E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.161938E+09 | 96138523.70 | 65799337.47 | 0.129816E+09 | 0.217132E+09 |
February | 0.225014E+09 | 0.139290E+09 | 85724535.56 | 0.205419E+09 | 0.170525E+09 |
March | 0.268082E+09 | 0.143015E+09 | 0.125067E+09 | 0.246585E+09 | 0.160667E+09 |
April | 0.273827E+09 | 0.118907E+09 | 0.154920E+09 | 0.241320E+09 | 0.127094E+09 |
May | 0.258668E+09 | 77034632.29 | 0.181634E+09 | 0.205660E+09 | 0.114585E+09 |
June | 0.229021E+09 | 61464616.56 | 0.167556E+09 | 0.168931E+09 | 94159149.05 |
July | 0.258075E+09 | 94492485.45 | 0.163583E+09 | 0.213245E+09 | 90362704.81 |
August | 0.277296E+09 | 0.129296E+09 | 0.148000E+09 | 0.266453E+09 | 89280616.18 |
September | 0.297439E+09 | 0.164298E+09 | 0.133141E+09 | 0.295833E+09 | 0.117457E+09 |
October | 0.278396E+09 | 0.171917E+09 | 0.106479E+09 | 0.278694E+09 | 0.151375E+09 |
November | 0.159213E+09 | 91228882.84 | 67984236.35 | 0.137515E+09 | 0.175526E+09 |
December | 0.172112E+09 | 0.111360E+09 | 60751916.90 | 0.156761E+09 | 0.224495E+09 |
Annual Sum or Average | 0.285908E+10 | 0.139844E+10 | 0.146064E+10 | 0.254623E+10 | 0.173266E+10 |
Minimum of Months | 0.159213E+09 | 61464616.56 | 60751916.90 | 0.129816E+09 | 89280616.18 |
Maximum of Months | 0.297439E+09 | 0.171917E+09 | 0.181634E+09 | 0.295833E+09 | 0.224495E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_DOOR
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.193899E+09 | 0.115113E+09 | 78786048.81 | 0.155979E+09 | 0.256760E+09 |
February | 0.269425E+09 | 0.166781E+09 | 0.102644E+09 | 0.246528E+09 | 0.201838E+09 |
March | 0.320993E+09 | 0.171242E+09 | 0.149751E+09 | 0.295709E+09 | 0.190173E+09 |
April | 0.327872E+09 | 0.142375E+09 | 0.185496E+09 | 0.289464E+09 | 0.150528E+09 |
May | 0.309721E+09 | 92238836.03 | 0.217482E+09 | 0.246764E+09 | 0.135801E+09 |
June | 0.274222E+09 | 73595790.88 | 0.200626E+09 | 0.202689E+09 | 0.111632E+09 |
July | 0.309011E+09 | 0.113142E+09 | 0.195869E+09 | 0.255511E+09 | 0.107219E+09 |
August | 0.332026E+09 | 0.154815E+09 | 0.177210E+09 | 0.318991E+09 | 0.105998E+09 |
September | 0.356144E+09 | 0.196725E+09 | 0.159419E+09 | 0.354237E+09 | 0.139445E+09 |
October | 0.333343E+09 | 0.205848E+09 | 0.127494E+09 | 0.333970E+09 | 0.179415E+09 |
November | 0.190637E+09 | 0.109235E+09 | 81402177.73 | 0.165035E+09 | 0.207781E+09 |
December | 0.206082E+09 | 0.133339E+09 | 72742426.81 | 0.188068E+09 | 0.265667E+09 |
Annual Sum or Average | 0.342337E+10 | 0.167445E+10 | 0.174892E+10 | 0.305294E+10 | 0.205226E+10 |
Minimum of Months | 0.190637E+09 | 73595790.88 | 72742426.81 | 0.155979E+09 | 0.105998E+09 |
Maximum of Months | 0.356144E+09 | 0.205848E+09 | 0.217482E+09 | 0.354237E+09 | 0.265667E+09 |
Report: WindowZoneSummaryMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 303.24 | 593.96 | 387.43 | 230.01 | 157.42 | 0.00 | 0.00 |
February | 530.67 | 520.43 | 596.01 | 368.95 | 227.06 | 0.00 | 0.00 |
March | 575.51 | 454.47 | 641.37 | 342.15 | 299.21 | 0.00 | 0.00 |
April | 573.56 | 382.57 | 676.95 | 293.96 | 382.99 | 0.00 | 0.00 |
May | 462.33 | 334.61 | 618.85 | 184.30 | 434.55 | 0.00 | 0.00 |
June | 399.09 | 268.40 | 566.18 | 151.95 | 414.23 | 0.00 | 0.00 |
July | 499.68 | 239.64 | 617.43 | 226.07 | 391.36 | 0.00 | 0.00 |
August | 629.63 | 232.84 | 663.41 | 309.33 | 354.08 | 0.00 | 0.00 |
September | 718.16 | 326.95 | 735.32 | 406.17 | 329.15 | 0.00 | 0.00 |
October | 647.61 | 433.38 | 666.04 | 411.30 | 254.74 | 0.00 | 0.00 |
November | 328.95 | 497.28 | 393.60 | 225.53 | 168.07 | 0.00 | 0.00 |
December | 367.60 | 602.53 | 411.77 | 266.42 | 145.34 | 0.00 | 0.00 |
Annual Sum or Average | 502.75 | 406.75 | 580.95 | 284.15 | 296.79 | 0.00 | 0.00 |
Minimum of Months | 303.24 | 232.84 | 387.43 | 151.95 | 145.34 | 0.00 | 0.00 |
Maximum of Months | 718.16 | 602.53 | 735.32 | 411.30 | 434.55 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 149.14 | 315.67 | 193.71 | 115.00 | 78.71 | 0.00 | 0.00 |
February | 261.19 | 278.03 | 298.01 | 184.47 | 113.53 | 0.00 | 0.00 |
March | 282.47 | 247.02 | 320.68 | 171.08 | 149.61 | 0.00 | 0.00 |
April | 280.42 | 206.00 | 338.47 | 146.98 | 191.50 | 0.00 | 0.00 |
May | 226.84 | 175.52 | 309.42 | 92.15 | 217.27 | 0.00 | 0.00 |
June | 197.04 | 138.81 | 283.09 | 75.98 | 207.11 | 0.00 | 0.00 |
July | 248.62 | 122.73 | 308.71 | 113.03 | 195.68 | 0.00 | 0.00 |
August | 313.61 | 119.07 | 331.71 | 154.67 | 177.04 | 0.00 | 0.00 |
September | 357.35 | 167.40 | 367.66 | 203.09 | 164.57 | 0.00 | 0.00 |
October | 319.98 | 228.22 | 333.02 | 205.65 | 127.37 | 0.00 | 0.00 |
November | 161.48 | 265.34 | 196.80 | 112.77 | 84.03 | 0.00 | 0.00 |
December | 181.18 | 319.77 | 205.88 | 133.21 | 72.67 | 0.00 | 0.00 |
Annual Sum or Average | 248.16 | 215.01 | 290.47 | 142.08 | 148.40 | 0.00 | 0.00 |
Minimum of Months | 149.14 | 119.07 | 193.71 | 75.98 | 72.67 | 0.00 | 0.00 |
Maximum of Months | 357.35 | 319.77 | 367.66 | 205.65 | 217.27 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 149.73 | 301.09 | 193.32 | 114.77 | 78.55 | 0.00 | 0.00 |
February | 262.30 | 265.31 | 297.39 | 184.09 | 113.30 | 0.00 | 0.00 |
March | 283.65 | 235.96 | 320.03 | 170.73 | 149.30 | 0.00 | 0.00 |
April | 281.64 | 199.44 | 337.78 | 146.68 | 191.10 | 0.00 | 0.00 |
May | 226.99 | 174.68 | 308.79 | 91.96 | 216.83 | 0.00 | 0.00 |
June | 196.43 | 141.62 | 282.51 | 75.82 | 206.69 | 0.00 | 0.00 |
July | 247.49 | 127.33 | 308.08 | 112.80 | 195.28 | 0.00 | 0.00 |
August | 312.39 | 124.09 | 331.03 | 154.35 | 176.68 | 0.00 | 0.00 |
September | 356.63 | 169.71 | 366.91 | 202.67 | 164.24 | 0.00 | 0.00 |
October | 320.73 | 222.38 | 332.34 | 205.23 | 127.11 | 0.00 | 0.00 |
November | 162.51 | 253.65 | 196.40 | 112.54 | 83.86 | 0.00 | 0.00 |
December | 181.96 | 305.87 | 205.46 | 132.94 | 72.52 | 0.00 | 0.00 |
Annual Sum or Average | 248.42 | 209.85 | 289.88 | 141.79 | 148.09 | 0.00 | 0.00 |
Minimum of Months | 149.73 | 124.09 | 193.32 | 75.82 | 72.52 | 0.00 | 0.00 |
Maximum of Months | 356.63 | 305.87 | 366.91 | 205.23 | 216.83 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 150.19 | 296.08 | 193.32 | 114.77 | 78.55 | 0.00 | 0.00 |
February | 263.19 | 260.64 | 297.39 | 184.09 | 113.30 | 0.00 | 0.00 |
March | 284.77 | 230.83 | 320.03 | 170.73 | 149.30 | 0.00 | 0.00 |
April | 283.11 | 195.10 | 337.78 | 146.68 | 191.10 | 0.00 | 0.00 |
May | 227.77 | 172.54 | 308.79 | 91.96 | 216.83 | 0.00 | 0.00 |
June | 196.68 | 140.77 | 282.51 | 75.82 | 206.69 | 0.00 | 0.00 |
July | 247.59 | 126.93 | 308.08 | 112.80 | 195.28 | 0.00 | 0.00 |
August | 312.44 | 123.86 | 331.03 | 154.35 | 176.68 | 0.00 | 0.00 |
September | 356.87 | 168.62 | 366.91 | 202.67 | 164.24 | 0.00 | 0.00 |
October | 321.81 | 217.85 | 332.34 | 205.23 | 127.11 | 0.00 | 0.00 |
November | 163.29 | 248.73 | 196.40 | 112.54 | 83.86 | 0.00 | 0.00 |
December | 182.48 | 301.25 | 205.46 | 132.94 | 72.52 | 0.00 | 0.00 |
Annual Sum or Average | 249.06 | 206.70 | 289.88 | 141.79 | 148.09 | 0.00 | 0.00 |
Minimum of Months | 150.19 | 123.86 | 193.32 | 75.82 | 72.52 | 0.00 | 0.00 |
Maximum of Months | 356.87 | 301.25 | 366.91 | 205.23 | 216.83 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 150.72 | 292.31 | 193.32 | 114.77 | 78.55 | 0.00 | 0.00 |
February | 264.19 | 257.01 | 297.39 | 184.09 | 113.30 | 0.00 | 0.00 |
March | 286.13 | 226.02 | 320.03 | 170.73 | 149.30 | 0.00 | 0.00 |
April | 285.21 | 190.35 | 337.78 | 146.68 | 191.10 | 0.00 | 0.00 |
May | 229.39 | 169.34 | 308.79 | 91.96 | 216.83 | 0.00 | 0.00 |
June | 197.49 | 138.92 | 282.51 | 75.82 | 206.69 | 0.00 | 0.00 |
July | 248.13 | 125.44 | 308.08 | 112.80 | 195.28 | 0.00 | 0.00 |
August | 312.94 | 122.41 | 331.03 | 154.35 | 176.68 | 0.00 | 0.00 |
September | 357.54 | 166.49 | 366.91 | 202.67 | 164.24 | 0.00 | 0.00 |
October | 323.41 | 212.49 | 332.34 | 205.23 | 127.11 | 0.00 | 0.00 |
November | 164.24 | 244.43 | 196.40 | 112.54 | 83.86 | 0.00 | 0.00 |
December | 183.02 | 297.84 | 205.46 | 132.94 | 72.52 | 0.00 | 0.00 |
Annual Sum or Average | 250.08 | 203.35 | 289.88 | 141.79 | 148.09 | 0.00 | 0.00 |
Minimum of Months | 150.72 | 122.41 | 193.32 | 75.82 | 72.52 | 0.00 | 0.00 |
Maximum of Months | 357.54 | 297.84 | 366.91 | 205.23 | 216.83 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 305.66 | 560.65 | 386.63 | 229.53 | 157.10 | 0.00 | 0.00 |
February | 535.07 | 493.08 | 594.79 | 368.19 | 226.60 | 0.00 | 0.00 |
March | 579.52 | 429.58 | 640.05 | 341.45 | 298.60 | 0.00 | 0.00 |
April | 580.19 | 359.26 | 675.56 | 293.36 | 382.20 | 0.00 | 0.00 |
May | 468.06 | 321.38 | 617.58 | 183.92 | 433.65 | 0.00 | 0.00 |
June | 399.90 | 265.67 | 565.02 | 151.64 | 413.38 | 0.00 | 0.00 |
July | 499.02 | 240.72 | 616.16 | 225.60 | 390.56 | 0.00 | 0.00 |
August | 628.55 | 234.59 | 662.05 | 308.70 | 353.35 | 0.00 | 0.00 |
September | 719.54 | 320.19 | 733.81 | 405.34 | 328.47 | 0.00 | 0.00 |
October | 654.78 | 401.77 | 664.68 | 410.46 | 254.22 | 0.00 | 0.00 |
November | 333.72 | 467.23 | 392.80 | 225.07 | 167.72 | 0.00 | 0.00 |
December | 369.99 | 574.05 | 410.92 | 265.88 | 145.05 | 0.00 | 0.00 |
Annual Sum or Average | 505.90 | 388.55 | 579.75 | 283.57 | 296.18 | 0.00 | 0.00 |
Minimum of Months | 305.66 | 234.59 | 386.63 | 151.64 | 145.05 | 0.00 | 0.00 |
Maximum of Months | 719.54 | 574.05 | 733.81 | 410.46 | 433.65 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 152.23 | 281.73 | 193.32 | 114.77 | 78.55 | 0.00 | 0.00 |
February | 266.91 | 247.16 | 297.39 | 184.09 | 113.30 | 0.00 | 0.00 |
March | 289.48 | 214.35 | 320.03 | 170.73 | 149.30 | 0.00 | 0.00 |
April | 290.41 | 178.55 | 337.78 | 146.68 | 191.10 | 0.00 | 0.00 |
May | 234.97 | 159.14 | 308.79 | 91.96 | 216.83 | 0.00 | 0.00 |
June | 200.48 | 131.93 | 282.51 | 75.82 | 206.69 | 0.00 | 0.00 |
July | 250.04 | 119.44 | 308.08 | 112.80 | 195.28 | 0.00 | 0.00 |
August | 314.67 | 116.29 | 331.03 | 154.35 | 176.68 | 0.00 | 0.00 |
September | 359.97 | 158.90 | 366.91 | 202.67 | 164.24 | 0.00 | 0.00 |
October | 327.36 | 199.44 | 332.34 | 205.23 | 127.11 | 0.00 | 0.00 |
November | 166.60 | 233.77 | 196.40 | 112.54 | 83.86 | 0.00 | 0.00 |
December | 184.51 | 288.08 | 205.46 | 132.94 | 72.52 | 0.00 | 0.00 |
Annual Sum or Average | 253.01 | 193.83 | 289.88 | 141.79 | 148.09 | 0.00 | 0.00 |
Minimum of Months | 152.23 | 116.29 | 193.32 | 75.82 | 72.52 | 0.00 | 0.00 |
Maximum of Months | 359.97 | 288.08 | 366.91 | 205.23 | 216.83 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 152.40 | 280.52 | 193.32 | 114.77 | 78.55 | 0.00 | 0.00 |
February | 267.24 | 245.93 | 297.39 | 184.09 | 113.30 | 0.00 | 0.00 |
March | 289.91 | 212.79 | 320.03 | 170.73 | 149.30 | 0.00 | 0.00 |
April | 291.23 | 176.71 | 337.78 | 146.68 | 191.10 | 0.00 | 0.00 |
May | 236.31 | 156.90 | 308.79 | 91.96 | 216.83 | 0.00 | 0.00 |
June | 201.22 | 130.72 | 282.51 | 75.82 | 206.69 | 0.00 | 0.00 |
July | 250.44 | 118.65 | 308.08 | 112.80 | 195.28 | 0.00 | 0.00 |
August | 315.01 | 115.60 | 331.03 | 154.35 | 176.68 | 0.00 | 0.00 |
September | 360.50 | 157.65 | 366.91 | 202.67 | 164.24 | 0.00 | 0.00 |
October | 328.01 | 197.46 | 332.34 | 205.23 | 127.11 | 0.00 | 0.00 |
November | 166.90 | 232.48 | 196.40 | 112.54 | 83.86 | 0.00 | 0.00 |
December | 184.69 | 286.94 | 205.46 | 132.94 | 72.52 | 0.00 | 0.00 |
Annual Sum or Average | 253.53 | 192.46 | 289.88 | 141.79 | 148.09 | 0.00 | 0.00 |
Minimum of Months | 152.40 | 115.60 | 193.32 | 75.82 | 72.52 | 0.00 | 0.00 |
Maximum of Months | 360.50 | 286.94 | 366.91 | 205.23 | 216.83 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 152.97 | 276.03 | 193.32 | 114.77 | 78.55 | 0.00 | 0.00 |
February | 268.22 | 241.61 | 297.39 | 184.09 | 113.30 | 0.00 | 0.00 |
March | 290.98 | 208.28 | 320.03 | 170.73 | 149.30 | 0.00 | 0.00 |
April | 293.03 | 172.11 | 337.78 | 146.68 | 191.10 | 0.00 | 0.00 |
May | 239.09 | 151.74 | 308.79 | 91.96 | 216.83 | 0.00 | 0.00 |
June | 203.06 | 127.46 | 282.51 | 75.82 | 206.69 | 0.00 | 0.00 |
July | 251.39 | 116.46 | 308.08 | 112.80 | 195.28 | 0.00 | 0.00 |
August | 315.72 | 113.80 | 331.03 | 154.35 | 176.68 | 0.00 | 0.00 |
September | 361.69 | 154.55 | 366.91 | 202.67 | 164.24 | 0.00 | 0.00 |
October | 329.37 | 193.13 | 332.34 | 205.23 | 127.11 | 0.00 | 0.00 |
November | 167.60 | 228.88 | 196.40 | 112.54 | 83.86 | 0.00 | 0.00 |
December | 185.24 | 282.90 | 205.46 | 132.94 | 72.52 | 0.00 | 0.00 |
Annual Sum or Average | 254.74 | 188.68 | 289.88 | 141.79 | 148.09 | 0.00 | 0.00 |
Minimum of Months | 152.97 | 113.80 | 193.32 | 75.82 | 72.52 | 0.00 | 0.00 |
Maximum of Months | 361.69 | 282.90 | 366.91 | 205.23 | 216.83 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 155.17 | 258.00 | 193.32 | 114.77 | 78.55 | 0.00 | 0.00 |
February | 271.73 | 224.41 | 297.39 | 184.09 | 113.30 | 0.00 | 0.00 |
March | 294.53 | 190.97 | 320.03 | 170.73 | 149.30 | 0.00 | 0.00 |
April | 297.88 | 156.14 | 337.78 | 146.68 | 191.10 | 0.00 | 0.00 |
May | 245.70 | 136.26 | 308.79 | 91.96 | 216.83 | 0.00 | 0.00 |
June | 208.55 | 115.72 | 282.51 | 75.82 | 206.69 | 0.00 | 0.00 |
July | 254.63 | 107.51 | 308.08 | 112.80 | 195.28 | 0.00 | 0.00 |
August | 318.06 | 106.24 | 331.03 | 154.35 | 176.68 | 0.00 | 0.00 |
September | 364.93 | 144.43 | 366.91 | 202.67 | 164.24 | 0.00 | 0.00 |
October | 332.79 | 180.02 | 332.34 | 205.23 | 127.11 | 0.00 | 0.00 |
November | 169.78 | 215.60 | 196.40 | 112.54 | 83.86 | 0.00 | 0.00 |
December | 187.27 | 266.82 | 205.46 | 132.94 | 72.52 | 0.00 | 0.00 |
Annual Sum or Average | 258.29 | 174.96 | 289.88 | 141.79 | 148.09 | 0.00 | 0.00 |
Minimum of Months | 155.17 | 106.24 | 193.32 | 75.82 | 72.52 | 0.00 | 0.00 |
Maximum of Months | 364.93 | 266.82 | 366.91 | 205.23 | 216.83 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.812190E+09 | 0.159085E+10 | 0.103768E+10 | 0.616046E+09 | 0.421635E+09 | 0.00 | 0.00 |
February | 0.128379E+10 | 0.125902E+10 | 0.144187E+10 | 0.892554E+09 | 0.549314E+09 | 0.00 | 0.00 |
March | 0.154145E+10 | 0.121725E+10 | 0.171784E+10 | 0.916424E+09 | 0.801416E+09 | 0.00 | 0.00 |
April | 0.148668E+10 | 0.991628E+09 | 0.175465E+10 | 0.761942E+09 | 0.992711E+09 | 0.00 | 0.00 |
May | 0.123831E+10 | 0.896215E+09 | 0.165752E+10 | 0.493630E+09 | 0.116389E+10 | 0.00 | 0.00 |
June | 0.103444E+10 | 0.695696E+09 | 0.146754E+10 | 0.393859E+09 | 0.107368E+10 | 0.00 | 0.00 |
July | 0.133835E+10 | 0.641862E+09 | 0.165372E+10 | 0.605498E+09 | 0.104822E+10 | 0.00 | 0.00 |
August | 0.168640E+10 | 0.623642E+09 | 0.177688E+10 | 0.828518E+09 | 0.948366E+09 | 0.00 | 0.00 |
September | 0.186147E+10 | 0.847444E+09 | 0.190596E+10 | 0.105280E+10 | 0.853154E+09 | 0.00 | 0.00 |
October | 0.173457E+10 | 0.116076E+10 | 0.178393E+10 | 0.110163E+10 | 0.682304E+09 | 0.00 | 0.00 |
November | 0.852628E+09 | 0.128894E+10 | 0.102022E+10 | 0.584585E+09 | 0.435636E+09 | 0.00 | 0.00 |
December | 0.984591E+09 | 0.161382E+10 | 0.110288E+10 | 0.713586E+09 | 0.389292E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.158549E+11 | 0.128271E+11 | 0.183207E+11 | 0.896107E+10 | 0.935962E+10 | 0.00 | 0.00 |
Minimum of Months | 0.812190E+09 | 0.623642E+09 | 0.102022E+10 | 0.393859E+09 | 0.389292E+09 | 0.00 | 0.00 |
Maximum of Months | 0.186147E+10 | 0.161382E+10 | 0.190596E+10 | 0.110163E+10 | 0.116389E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.399469E+09 | 0.845478E+09 | 0.518840E+09 | 0.308023E+09 | 0.210818E+09 | 0.00 | 0.00 |
February | 0.631882E+09 | 0.672618E+09 | 0.720934E+09 | 0.446277E+09 | 0.274657E+09 | 0.00 | 0.00 |
March | 0.756581E+09 | 0.661626E+09 | 0.858920E+09 | 0.458212E+09 | 0.400708E+09 | 0.00 | 0.00 |
April | 0.726858E+09 | 0.533953E+09 | 0.877327E+09 | 0.380971E+09 | 0.496356E+09 | 0.00 | 0.00 |
May | 0.607562E+09 | 0.470113E+09 | 0.828760E+09 | 0.246815E+09 | 0.581945E+09 | 0.00 | 0.00 |
June | 0.510721E+09 | 0.359801E+09 | 0.733770E+09 | 0.196929E+09 | 0.536840E+09 | 0.00 | 0.00 |
July | 0.665898E+09 | 0.328711E+09 | 0.826859E+09 | 0.302749E+09 | 0.524110E+09 | 0.00 | 0.00 |
August | 0.839963E+09 | 0.318926E+09 | 0.888442E+09 | 0.414259E+09 | 0.474183E+09 | 0.00 | 0.00 |
September | 0.926256E+09 | 0.433894E+09 | 0.952979E+09 | 0.526402E+09 | 0.426577E+09 | 0.00 | 0.00 |
October | 0.857027E+09 | 0.611255E+09 | 0.891966E+09 | 0.550814E+09 | 0.341152E+09 | 0.00 | 0.00 |
November | 0.418566E+09 | 0.687761E+09 | 0.510110E+09 | 0.292293E+09 | 0.217818E+09 | 0.00 | 0.00 |
December | 0.485284E+09 | 0.856470E+09 | 0.551439E+09 | 0.356793E+09 | 0.194646E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.782607E+10 | 0.678061E+10 | 0.916035E+10 | 0.448054E+10 | 0.467981E+10 | 0.00 | 0.00 |
Minimum of Months | 0.399469E+09 | 0.318926E+09 | 0.510110E+09 | 0.196929E+09 | 0.194646E+09 | 0.00 | 0.00 |
Maximum of Months | 0.926256E+09 | 0.856470E+09 | 0.952979E+09 | 0.550814E+09 | 0.581945E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.401029E+09 | 0.806437E+09 | 0.517775E+09 | 0.307390E+09 | 0.210385E+09 | 0.00 | 0.00 |
February | 0.634547E+09 | 0.641832E+09 | 0.719454E+09 | 0.445361E+09 | 0.274093E+09 | 0.00 | 0.00 |
March | 0.759718E+09 | 0.632003E+09 | 0.857157E+09 | 0.457271E+09 | 0.399885E+09 | 0.00 | 0.00 |
April | 0.730023E+09 | 0.516949E+09 | 0.875525E+09 | 0.380189E+09 | 0.495336E+09 | 0.00 | 0.00 |
May | 0.607977E+09 | 0.467859E+09 | 0.827058E+09 | 0.246308E+09 | 0.580750E+09 | 0.00 | 0.00 |
June | 0.509146E+09 | 0.367091E+09 | 0.732263E+09 | 0.196525E+09 | 0.535738E+09 | 0.00 | 0.00 |
July | 0.662869E+09 | 0.341032E+09 | 0.825161E+09 | 0.302127E+09 | 0.523034E+09 | 0.00 | 0.00 |
August | 0.836710E+09 | 0.332354E+09 | 0.886618E+09 | 0.413408E+09 | 0.473209E+09 | 0.00 | 0.00 |
September | 0.924392E+09 | 0.439882E+09 | 0.951022E+09 | 0.525321E+09 | 0.425701E+09 | 0.00 | 0.00 |
October | 0.859036E+09 | 0.595632E+09 | 0.890135E+09 | 0.549683E+09 | 0.340452E+09 | 0.00 | 0.00 |
November | 0.421221E+09 | 0.657472E+09 | 0.509063E+09 | 0.291692E+09 | 0.217371E+09 | 0.00 | 0.00 |
December | 0.487359E+09 | 0.819241E+09 | 0.550307E+09 | 0.356060E+09 | 0.194246E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.783403E+10 | 0.661778E+10 | 0.914154E+10 | 0.447134E+10 | 0.467020E+10 | 0.00 | 0.00 |
Minimum of Months | 0.401029E+09 | 0.332354E+09 | 0.509063E+09 | 0.196525E+09 | 0.194246E+09 | 0.00 | 0.00 |
Maximum of Months | 0.924392E+09 | 0.819241E+09 | 0.951022E+09 | 0.549683E+09 | 0.580750E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.402279E+09 | 0.793010E+09 | 0.517775E+09 | 0.307390E+09 | 0.210385E+09 | 0.00 | 0.00 |
February | 0.636718E+09 | 0.630549E+09 | 0.719454E+09 | 0.445361E+09 | 0.274093E+09 | 0.00 | 0.00 |
March | 0.762716E+09 | 0.618259E+09 | 0.857157E+09 | 0.457271E+09 | 0.399885E+09 | 0.00 | 0.00 |
April | 0.733831E+09 | 0.505710E+09 | 0.875525E+09 | 0.380189E+09 | 0.495336E+09 | 0.00 | 0.00 |
May | 0.610050E+09 | 0.462124E+09 | 0.827058E+09 | 0.246308E+09 | 0.580750E+09 | 0.00 | 0.00 |
June | 0.509784E+09 | 0.364885E+09 | 0.732263E+09 | 0.196525E+09 | 0.535738E+09 | 0.00 | 0.00 |
July | 0.663156E+09 | 0.339964E+09 | 0.825161E+09 | 0.302127E+09 | 0.523034E+09 | 0.00 | 0.00 |
August | 0.836848E+09 | 0.331759E+09 | 0.886618E+09 | 0.413408E+09 | 0.473209E+09 | 0.00 | 0.00 |
September | 0.924994E+09 | 0.437066E+09 | 0.951022E+09 | 0.525321E+09 | 0.425701E+09 | 0.00 | 0.00 |
October | 0.861925E+09 | 0.583488E+09 | 0.890135E+09 | 0.549683E+09 | 0.340452E+09 | 0.00 | 0.00 |
November | 0.423242E+09 | 0.644721E+09 | 0.509063E+09 | 0.291692E+09 | 0.217371E+09 | 0.00 | 0.00 |
December | 0.488752E+09 | 0.806860E+09 | 0.550307E+09 | 0.356060E+09 | 0.194246E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.785430E+10 | 0.651840E+10 | 0.914154E+10 | 0.447134E+10 | 0.467020E+10 | 0.00 | 0.00 |
Minimum of Months | 0.402279E+09 | 0.331759E+09 | 0.509063E+09 | 0.196525E+09 | 0.194246E+09 | 0.00 | 0.00 |
Maximum of Months | 0.924994E+09 | 0.806860E+09 | 0.951022E+09 | 0.549683E+09 | 0.580750E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.403677E+09 | 0.782933E+09 | 0.517775E+09 | 0.307390E+09 | 0.210385E+09 | 0.00 | 0.00 |
February | 0.639126E+09 | 0.621766E+09 | 0.719454E+09 | 0.445361E+09 | 0.274093E+09 | 0.00 | 0.00 |
March | 0.766382E+09 | 0.605360E+09 | 0.857157E+09 | 0.457271E+09 | 0.399885E+09 | 0.00 | 0.00 |
April | 0.739267E+09 | 0.493381E+09 | 0.875525E+09 | 0.380189E+09 | 0.495336E+09 | 0.00 | 0.00 |
May | 0.614408E+09 | 0.453564E+09 | 0.827058E+09 | 0.246308E+09 | 0.580750E+09 | 0.00 | 0.00 |
June | 0.511883E+09 | 0.360076E+09 | 0.732263E+09 | 0.196525E+09 | 0.535738E+09 | 0.00 | 0.00 |
July | 0.664588E+09 | 0.335973E+09 | 0.825161E+09 | 0.302127E+09 | 0.523034E+09 | 0.00 | 0.00 |
August | 0.838189E+09 | 0.327862E+09 | 0.886618E+09 | 0.413408E+09 | 0.473209E+09 | 0.00 | 0.00 |
September | 0.926731E+09 | 0.431548E+09 | 0.951022E+09 | 0.525321E+09 | 0.425701E+09 | 0.00 | 0.00 |
October | 0.866211E+09 | 0.569136E+09 | 0.890135E+09 | 0.549683E+09 | 0.340452E+09 | 0.00 | 0.00 |
November | 0.425711E+09 | 0.633555E+09 | 0.509063E+09 | 0.291692E+09 | 0.217371E+09 | 0.00 | 0.00 |
December | 0.490201E+09 | 0.797738E+09 | 0.550307E+09 | 0.356060E+09 | 0.194246E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.788637E+10 | 0.641289E+10 | 0.914154E+10 | 0.447134E+10 | 0.467020E+10 | 0.00 | 0.00 |
Minimum of Months | 0.403677E+09 | 0.327862E+09 | 0.509063E+09 | 0.196525E+09 | 0.194246E+09 | 0.00 | 0.00 |
Maximum of Months | 0.926731E+09 | 0.797738E+09 | 0.951022E+09 | 0.549683E+09 | 0.580750E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.818682E+09 | 0.150165E+10 | 0.103555E+10 | 0.614781E+09 | 0.420769E+09 | 0.00 | 0.00 |
February | 0.129445E+10 | 0.119286E+10 | 0.143891E+10 | 0.890722E+09 | 0.548186E+09 | 0.00 | 0.00 |
March | 0.155218E+10 | 0.115058E+10 | 0.171431E+10 | 0.914543E+09 | 0.799771E+09 | 0.00 | 0.00 |
April | 0.150386E+10 | 0.931212E+09 | 0.175105E+10 | 0.760378E+09 | 0.990673E+09 | 0.00 | 0.00 |
May | 0.125365E+10 | 0.860778E+09 | 0.165412E+10 | 0.492616E+09 | 0.116150E+10 | 0.00 | 0.00 |
June | 0.103654E+10 | 0.688607E+09 | 0.146453E+10 | 0.393050E+09 | 0.107148E+10 | 0.00 | 0.00 |
July | 0.133657E+10 | 0.644742E+09 | 0.165032E+10 | 0.604255E+09 | 0.104607E+10 | 0.00 | 0.00 |
August | 0.168350E+10 | 0.628333E+09 | 0.177324E+10 | 0.826817E+09 | 0.946418E+09 | 0.00 | 0.00 |
September | 0.186504E+10 | 0.829940E+09 | 0.190204E+10 | 0.105064E+10 | 0.851402E+09 | 0.00 | 0.00 |
October | 0.175375E+10 | 0.107611E+10 | 0.178027E+10 | 0.109937E+10 | 0.680903E+09 | 0.00 | 0.00 |
November | 0.865007E+09 | 0.121106E+10 | 0.101813E+10 | 0.583385E+09 | 0.434741E+09 | 0.00 | 0.00 |
December | 0.990972E+09 | 0.153755E+10 | 0.110061E+10 | 0.712121E+09 | 0.388493E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.159542E+11 | 0.122534E+11 | 0.182831E+11 | 0.894267E+10 | 0.934040E+10 | 0.00 | 0.00 |
Minimum of Months | 0.818682E+09 | 0.628333E+09 | 0.101813E+10 | 0.393050E+09 | 0.388493E+09 | 0.00 | 0.00 |
Maximum of Months | 0.186504E+10 | 0.153755E+10 | 0.190204E+10 | 0.109937E+10 | 0.116150E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.407726E+09 | 0.754583E+09 | 0.517775E+09 | 0.307390E+09 | 0.210385E+09 | 0.00 | 0.00 |
February | 0.645712E+09 | 0.597940E+09 | 0.719454E+09 | 0.445361E+09 | 0.274093E+09 | 0.00 | 0.00 |
March | 0.775340E+09 | 0.574119E+09 | 0.857157E+09 | 0.457271E+09 | 0.399885E+09 | 0.00 | 0.00 |
April | 0.752752E+09 | 0.462803E+09 | 0.875525E+09 | 0.380189E+09 | 0.495336E+09 | 0.00 | 0.00 |
May | 0.629355E+09 | 0.426234E+09 | 0.827058E+09 | 0.246308E+09 | 0.580750E+09 | 0.00 | 0.00 |
June | 0.519648E+09 | 0.341958E+09 | 0.732263E+09 | 0.196525E+09 | 0.535738E+09 | 0.00 | 0.00 |
July | 0.669710E+09 | 0.319918E+09 | 0.825161E+09 | 0.302127E+09 | 0.523034E+09 | 0.00 | 0.00 |
August | 0.842812E+09 | 0.311467E+09 | 0.886618E+09 | 0.413408E+09 | 0.473209E+09 | 0.00 | 0.00 |
September | 0.933034E+09 | 0.411871E+09 | 0.951022E+09 | 0.525321E+09 | 0.425701E+09 | 0.00 | 0.00 |
October | 0.876801E+09 | 0.534189E+09 | 0.890135E+09 | 0.549683E+09 | 0.340452E+09 | 0.00 | 0.00 |
November | 0.431831E+09 | 0.605930E+09 | 0.509063E+09 | 0.291692E+09 | 0.217371E+09 | 0.00 | 0.00 |
December | 0.494190E+09 | 0.771602E+09 | 0.550307E+09 | 0.356060E+09 | 0.194246E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.797891E+10 | 0.611261E+10 | 0.914154E+10 | 0.447134E+10 | 0.467020E+10 | 0.00 | 0.00 |
Minimum of Months | 0.407726E+09 | 0.311467E+09 | 0.509063E+09 | 0.196525E+09 | 0.194246E+09 | 0.00 | 0.00 |
Maximum of Months | 0.933034E+09 | 0.771602E+09 | 0.951022E+09 | 0.549683E+09 | 0.580750E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.408191E+09 | 0.751347E+09 | 0.517775E+09 | 0.307390E+09 | 0.210385E+09 | 0.00 | 0.00 |
February | 0.646516E+09 | 0.594946E+09 | 0.719454E+09 | 0.445361E+09 | 0.274093E+09 | 0.00 | 0.00 |
March | 0.776495E+09 | 0.569934E+09 | 0.857157E+09 | 0.457271E+09 | 0.399885E+09 | 0.00 | 0.00 |
April | 0.754872E+09 | 0.458043E+09 | 0.875525E+09 | 0.380189E+09 | 0.495336E+09 | 0.00 | 0.00 |
May | 0.632924E+09 | 0.420252E+09 | 0.827058E+09 | 0.246308E+09 | 0.580750E+09 | 0.00 | 0.00 |
June | 0.521561E+09 | 0.338829E+09 | 0.732263E+09 | 0.196525E+09 | 0.535738E+09 | 0.00 | 0.00 |
July | 0.670791E+09 | 0.317785E+09 | 0.825161E+09 | 0.302127E+09 | 0.523034E+09 | 0.00 | 0.00 |
August | 0.843724E+09 | 0.309618E+09 | 0.886618E+09 | 0.413408E+09 | 0.473209E+09 | 0.00 | 0.00 |
September | 0.934413E+09 | 0.408620E+09 | 0.951022E+09 | 0.525321E+09 | 0.425701E+09 | 0.00 | 0.00 |
October | 0.878549E+09 | 0.528872E+09 | 0.890135E+09 | 0.549683E+09 | 0.340452E+09 | 0.00 | 0.00 |
November | 0.432601E+09 | 0.602596E+09 | 0.509063E+09 | 0.291692E+09 | 0.217371E+09 | 0.00 | 0.00 |
December | 0.494669E+09 | 0.768547E+09 | 0.550307E+09 | 0.356060E+09 | 0.194246E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.799531E+10 | 0.606939E+10 | 0.914154E+10 | 0.447134E+10 | 0.467020E+10 | 0.00 | 0.00 |
Minimum of Months | 0.408191E+09 | 0.309618E+09 | 0.509063E+09 | 0.196525E+09 | 0.194246E+09 | 0.00 | 0.00 |
Maximum of Months | 0.934413E+09 | 0.768547E+09 | 0.951022E+09 | 0.549683E+09 | 0.580750E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.409709E+09 | 0.739324E+09 | 0.517775E+09 | 0.307390E+09 | 0.210385E+09 | 0.00 | 0.00 |
February | 0.648882E+09 | 0.584515E+09 | 0.719454E+09 | 0.445361E+09 | 0.274093E+09 | 0.00 | 0.00 |
March | 0.779363E+09 | 0.557864E+09 | 0.857157E+09 | 0.457271E+09 | 0.399885E+09 | 0.00 | 0.00 |
April | 0.759523E+09 | 0.446097E+09 | 0.875525E+09 | 0.380189E+09 | 0.495336E+09 | 0.00 | 0.00 |
May | 0.640370E+09 | 0.406418E+09 | 0.827058E+09 | 0.246308E+09 | 0.580750E+09 | 0.00 | 0.00 |
June | 0.526332E+09 | 0.330371E+09 | 0.732263E+09 | 0.196525E+09 | 0.535738E+09 | 0.00 | 0.00 |
July | 0.673310E+09 | 0.311914E+09 | 0.825161E+09 | 0.302127E+09 | 0.523034E+09 | 0.00 | 0.00 |
August | 0.845630E+09 | 0.304801E+09 | 0.886618E+09 | 0.413408E+09 | 0.473209E+09 | 0.00 | 0.00 |
September | 0.937499E+09 | 0.400599E+09 | 0.951022E+09 | 0.525321E+09 | 0.425701E+09 | 0.00 | 0.00 |
October | 0.882175E+09 | 0.517289E+09 | 0.890135E+09 | 0.549683E+09 | 0.340452E+09 | 0.00 | 0.00 |
November | 0.434420E+09 | 0.593257E+09 | 0.509063E+09 | 0.291692E+09 | 0.217371E+09 | 0.00 | 0.00 |
December | 0.496143E+09 | 0.757716E+09 | 0.550307E+09 | 0.356060E+09 | 0.194246E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.803336E+10 | 0.595017E+10 | 0.914154E+10 | 0.447134E+10 | 0.467020E+10 | 0.00 | 0.00 |
Minimum of Months | 0.409709E+09 | 0.304801E+09 | 0.509063E+09 | 0.196525E+09 | 0.194246E+09 | 0.00 | 0.00 |
Maximum of Months | 0.937499E+09 | 0.757716E+09 | 0.951022E+09 | 0.549683E+09 | 0.580750E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.415608E+09 | 0.691022E+09 | 0.517775E+09 | 0.307390E+09 | 0.210385E+09 | 0.00 | 0.00 |
February | 0.657362E+09 | 0.542886E+09 | 0.719454E+09 | 0.445361E+09 | 0.274093E+09 | 0.00 | 0.00 |
March | 0.788877E+09 | 0.511506E+09 | 0.857157E+09 | 0.457271E+09 | 0.399885E+09 | 0.00 | 0.00 |
April | 0.772101E+09 | 0.404714E+09 | 0.875525E+09 | 0.380189E+09 | 0.495336E+09 | 0.00 | 0.00 |
May | 0.658082E+09 | 0.364971E+09 | 0.827058E+09 | 0.246308E+09 | 0.580750E+09 | 0.00 | 0.00 |
June | 0.540550E+09 | 0.299950E+09 | 0.732263E+09 | 0.196525E+09 | 0.535738E+09 | 0.00 | 0.00 |
July | 0.682000E+09 | 0.287944E+09 | 0.825161E+09 | 0.302127E+09 | 0.523034E+09 | 0.00 | 0.00 |
August | 0.851898E+09 | 0.284559E+09 | 0.886618E+09 | 0.413408E+09 | 0.473209E+09 | 0.00 | 0.00 |
September | 0.945903E+09 | 0.374358E+09 | 0.951022E+09 | 0.525321E+09 | 0.425701E+09 | 0.00 | 0.00 |
October | 0.891356E+09 | 0.482164E+09 | 0.890135E+09 | 0.549683E+09 | 0.340452E+09 | 0.00 | 0.00 |
November | 0.440064E+09 | 0.558831E+09 | 0.509063E+09 | 0.291692E+09 | 0.217371E+09 | 0.00 | 0.00 |
December | 0.501589E+09 | 0.714656E+09 | 0.550307E+09 | 0.356060E+09 | 0.194246E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.814539E+10 | 0.551756E+10 | 0.914154E+10 | 0.447134E+10 | 0.467020E+10 | 0.00 | 0.00 |
Minimum of Months | 0.415608E+09 | 0.284559E+09 | 0.509063E+09 | 0.196525E+09 | 0.194246E+09 | 0.00 | 0.00 |
Maximum of Months | 0.945903E+09 | 0.714656E+09 | 0.951022E+09 | 0.549683E+09 | 0.580750E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 4.50 | 3.11 | 1.22 | 3.91 | -4.2 | 29.50 | 44.23 | 0.00 |
February | 5.82 | 4.09 | 1.77 | 3.94 | -3.8 | 43.80 | 82.64 | 0.00 |
March | 8.33 | 5.86 | 2.94 | 3.85 | -1.4 | 65.55 | 100.60 | 0.02 |
April | 10.85 | 8.03 | 5.25 | 4.23 | 1.21 | 89.73 | 150.02 | 0.00 |
May | 12.97 | 10.01 | 7.49 | 3.85 | 3.74 | 114.98 | 168.60 | 0.00 |
June | 15.59 | 11.79 | 8.88 | 4.02 | 5.93 | 107.53 | 199.74 | 0.01 |
July | 17.66 | 13.40 | 10.38 | 3.76 | 8.02 | 92.25 | 247.81 | 0.00 |
August | 18.80 | 14.56 | 11.86 | 3.84 | 8.90 | 79.20 | 215.47 | 0.01 |
September | 15.09 | 12.54 | 10.74 | 2.23 | 5.46 | 68.06 | 162.11 | 0.01 |
October | 11.43 | 9.18 | 7.19 | 4.02 | 2.09 | 48.18 | 106.36 | 0.04 |
November | 8.07 | 6.72 | 5.29 | 3.86 | 0.12 | 33.26 | 46.10 | 0.00 |
December | 5.42 | 4.09 | 2.46 | 3.51 | -3.8 | 24.03 | 50.49 | 0.04 |
Annual Sum or Average | 11.24 | 8.64 | 6.31 | 3.75 | 1.89 | 66.43 | 131.49 | 0.01 |
Minimum of Months | 4.50 | 3.11 | 1.22 | 2.23 | -4.2 | 24.03 | 44.23 | 0.00 |
Maximum of Months | 18.80 | 14.56 | 11.86 | 4.23 | 8.90 | 114.98 | 247.81 | 0.04 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 14.40 | 11-JAN-14:20 | 10.48 | 7.20 | 8.40 | 3.88 | 99.17 | 130.33 |
February | 20.00 | 27-FEB-14:00 | 12.15 | 5.60 | 2.60 | 5.54 | 87.00 | 691.00 |
March | 20.60 | 18-MAR-15:00 | 10.40 | 0.00 | 6.20 | 6.55 | 111.50 | 465.50 |
April | 27.20 | 27-APR-15:09 | 17.20 | 11.02 | 4.10 | 12.63 | 151.33 | 598.33 |
May | 25.00 | 05-MAY-15:00 | 17.35 | 12.80 | 2.60 | 18.99 | 208.50 | 29.50 |
June | 26.70 | 28-JUN-16:00 | 16.72 | 10.60 | 3.10 | 11.84 | 131.50 | 527.00 |
July | 30.60 | 24-JUL-14:00 | 18.76 | 12.20 | 3.10 | 20.75 | 267.00 | 383.50 |
August | 31.80 | 10-AUG-16:00 | 18.67 | 11.10 | 2.60 | 16.85 | 50.50 | 750.50 |
September | 25.00 | 14-SEP-16:00 | 16.67 | 11.70 | 3.10 | 13.54 | 100.50 | 235.00 |
October | 21.70 | 04-OCT-14:00 | 11.47 | 1.70 | 5.20 | 4.92 | 56.50 | 783.50 |
November | 21.10 | 04-NOV-13:00 | 15.93 | 12.80 | 0.00 | 6.95 | 52.50 | 729.00 |
December | 13.30 | 14-DEC-11:00 | 8.42 | 3.60 | 13.90 | 5.33 | 127.50 | 85.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 13.30 | 8.42 | 0.00 | 0.00 | 3.88 | 50.50 | 29.50 | |
Maximum of Months | 31.80 | 18.76 | 12.80 | 13.90 | 20.75 | 267.00 | 783.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -3.9 | 07-JAN-07:00 | -3.9 | -3.9 | 2.10 | -14.4 | 0.00 | 0.00 |
February | -5.6 | 19-FEB-05:10 | -6.1 | -7.3 | 3.77 | -22.8 | 0.00 | 0.00 |
March | -0.6 | 01-MAR-06:00 | -1.9 | -3.9 | 1.50 | -17.3 | 16.50 | 102.00 |
April | 1.70 | 19-APR-04:00 | 1.21 | 0.60 | 3.10 | -11.9 | 0.00 | 0.00 |
May | 4.40 | 11-MAY-02:00 | 3.92 | 3.30 | 3.10 | -10.9 | 0.00 | 0.00 |
June | 8.30 | 15-JUN-02:00 | 7.50 | 6.70 | 3.10 | -3.2 | 0.00 | 0.00 |
July | 11.10 | 03-JUL-03:00 | 8.18 | 5.00 | 2.60 | 5.54 | 0.00 | 0.00 |
August | 11.00 | 06-AUG-04:00 | 10.56 | 10.20 | 2.60 | -3.2 | 11.00 | 135.50 |
September | 7.20 | 27-SEP-04:49 | 6.72 | 6.20 | 0.25 | -4.0 | 0.00 | 0.00 |
October | 5.60 | 13-OCT-04:00 | 4.51 | 3.30 | 2.10 | -8.5 | 0.00 | 0.00 |
November | 0.00 | 11-NOV-06:00 | -0.2 | -0.6 | 2.10 | -16.0 | 0.00 | 0.00 |
December | -1.7 | 26-DEC-06:00 | -1.7 | -1.7 | 2.10 | -15.7 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -5.6 | -6.1 | -7.3 | 0.25 | -22.8 | 0.00 | 0.00 | |
Maximum of Months | 11.10 | 10.56 | 10.20 | 3.77 | 5.54 | 16.50 | 135.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.48 | 11-JAN-21:00 | 11.10 | 10.00 | 4.60 | 6.75 | 0.00 | 0.00 |
February | 12.41 | 27-FEB-15:00 | 19.40 | 6.70 | 2.60 | 6.35 | 88.00 | 342.50 |
March | 12.44 | 09-MAR-11:00 | 17.20 | 8.90 | 2.10 | 12.41 | 178.00 | 40.00 |
April | 17.27 | 27-APR-14:00 | 27.20 | 11.10 | 4.10 | 12.41 | 147.50 | 646.00 |
May | 17.57 | 06-MAY-12:00 | 23.90 | 13.90 | 5.20 | 15.57 | 365.50 | 282.50 |
June | 16.72 | 28-JUN-16:00 | 26.70 | 10.60 | 3.10 | 11.84 | 131.50 | 527.00 |
July | 19.16 | 31-JUL-15:00 | 28.90 | 13.90 | 4.10 | 14.65 | 45.00 | 848.50 |
August | 20.12 | 29-AUG-12:00 | 28.90 | 15.70 | 2.60 | 17.39 | 136.50 | 655.00 |
September | 17.96 | 23-SEP-13:00 | 23.30 | 15.00 | 2.10 | 9.72 | 148.00 | 670.50 |
October | 15.15 | 01-OCT-11:00 | 17.20 | 13.90 | 4.60 | 13.73 | 236.50 | 63.50 |
November | 16.04 | 04-NOV-12:00 | 20.60 | 13.30 | 0.00 | 7.95 | 62.00 | 746.50 |
December | 10.70 | 16-DEC-11:00 | 11.70 | 10.00 | 6.70 | 7.35 | 89.50 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 10.48 | 11.10 | 6.70 | 0.00 | 6.35 | 0.00 | 0.00 | |
Maximum of Months | 20.12 | 28.90 | 15.70 | 6.70 | 17.39 | 365.50 | 848.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.00 | 11-JAN-21:00 | 11.10 | 10.48 | 4.60 | 6.75 | 0.00 | 0.00 |
February | 11.70 | 24-FEB-00:00 | 12.80 | 12.15 | 4.10 | 8.74 | 0.00 | 0.00 |
March | 11.70 | 09-MAR-16:00 | 12.80 | 12.15 | 2.10 | 8.74 | 37.50 | 0.00 |
April | 12.80 | 28-APR-12:00 | 16.70 | 14.34 | 4.10 | 8.35 | 265.50 | 596.00 |
May | 13.90 | 05-MAY-16:00 | 22.80 | 17.09 | 2.60 | 19.17 | 111.50 | 27.50 |
June | 13.90 | 12-JUN-12:00 | 16.70 | 15.00 | 3.60 | 13.16 | 263.50 | 0.00 |
July | 15.00 | 11-JUL-09:20 | 16.13 | 15.49 | 4.60 | 12.91 | 204.17 | 28.17 |
August | 16.40 | 30-AUG-07:00 | 17.40 | 16.76 | 5.20 | 12.41 | 168.50 | 34.50 |
September | 15.00 | 14-SEP-11:20 | 20.37 | 16.92 | 2.10 | 6.88 | 152.83 | 748.17 |
October | 13.90 | 01-OCT-10:00 | 16.70 | 15.00 | 4.10 | 13.16 | 184.50 | 0.00 |
November | 13.90 | 03-NOV-19:00 | 15.00 | 14.31 | 4.60 | 11.46 | 0.00 | 0.00 |
December | 10.00 | 16-DEC-10:00 | 11.10 | 10.48 | 7.70 | 6.75 | 81.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 10.00 | 11.10 | 10.48 | 2.10 | 6.75 | 0.00 | 0.00 | |
Maximum of Months | 16.40 | 22.80 | 17.09 | 7.70 | 19.17 | 265.50 | 748.17 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 11.48 | 8.35 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 11.14 | 14.81 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 11.69 | 23.26 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 12.99 | 36.00 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 14.72 | 45.46 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 16.40 | 49.26 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 17.58 | 51.50 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 17.95 | 42.11 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 17.39 | 30.76 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 16.06 | 18.91 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 14.32 | 9.65 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 12.65 | 7.39 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 14.55 | 28.19 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 11.14 | 7.39 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 17.95 | 51.50 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK1
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.357021E+09 | -233293035.7 | 0.00 | 0.00 | 744.00 | 0.00 | -123727902.3 | 58.99 | 0.00 | 0.00 |
February | 0.324284E+09 | -213321360.1 | 0.00 | 0.00 | 672.00 | 0.00 | -110962727.0 | 58.99 | 0.00 | 0.00 |
March | 0.358585E+09 | -237164149.7 | 0.00 | 0.00 | 744.00 | 0.00 | -121421298.3 | 58.99 | 0.00 | 0.00 |
April | 0.335286E+09 | -220633538.5 | 0.00 | 0.00 | 720.00 | 0.00 | -114652268.4 | 58.99 | 0.00 | 0.00 |
May | 0.334716E+09 | -219624526.4 | 0.00 | 0.00 | 744.00 | 0.00 | -115091373.0 | 58.99 | 0.00 | 0.00 |
June | 0.316320E+09 | -206388215.1 | 0.00 | 0.00 | 720.00 | 0.00 | -109931809.1 | 58.99 | 0.00 | 0.00 |
July | 0.316343E+09 | -203422928.3 | 0.00 | 0.00 | 744.00 | 0.00 | -112920490.1 | 58.99 | 0.00 | 0.00 |
August | 0.318354E+09 | -205617489.1 | 0.00 | 0.00 | 744.00 | 0.00 | -112736061.3 | 58.99 | 0.00 | 0.00 |
September | 0.309307E+09 | -199734465.4 | 0.00 | 0.00 | 720.00 | 0.00 | -109572474.9 | 58.99 | 0.00 | 0.00 |
October | 0.327195E+09 | -210823142.8 | 0.00 | 0.00 | 744.00 | 0.00 | -116371869.8 | 58.99 | 0.00 | 0.00 |
November | 0.328950E+09 | -211654304.3 | 0.00 | 0.00 | 720.00 | 0.00 | -117295897.6 | 58.99 | 0.00 | 0.00 |
December | 0.351141E+09 | -227813675.0 | 0.00 | 0.00 | 744.00 | 0.00 | -123327609.2 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.397750E+10 | -.258949E+10 | 8760.00 | -.138801E+10 | 58.99 | |||||
Minimum of Months | 0.309307E+09 | -237164149.7 | 0.00 | 0.00 | 672.00 | 0.00 | -123727902.3 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.358585E+09 | -199734465.4 | 0.00 | 0.00 | 744.00 | 0.00 | -109572474.9 | 58.99 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK2
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.354613E+09 | -233294002.8 | 0.00 | 0.00 | 744.00 | 0.00 | -121318508.8 | 58.99 | 0.00 | 0.00 |
February | 0.321916E+09 | -213320811.0 | 0.00 | 0.00 | 672.00 | 0.00 | -108594989.6 | 58.99 | 0.00 | 0.00 |
March | 0.355378E+09 | -237169605.5 | 0.00 | 0.00 | 744.00 | 0.00 | -118208714.5 | 58.99 | 0.00 | 0.00 |
April | 0.332761E+09 | -220635282.8 | 0.00 | 0.00 | 720.00 | 0.00 | -112125337.1 | 58.99 | 0.00 | 0.00 |
May | 0.333345E+09 | -219629102.7 | 0.00 | 0.00 | 744.00 | 0.00 | -113715931.3 | 58.99 | 0.00 | 0.00 |
June | 0.315696E+09 | -206392460.8 | 0.00 | 0.00 | 720.00 | 0.00 | -109303585.1 | 58.99 | 0.00 | 0.00 |
July | 0.316011E+09 | -203426909.3 | 0.00 | 0.00 | 744.00 | 0.00 | -112583770.1 | 58.99 | 0.00 | 0.00 |
August | 0.318084E+09 | -205614403.8 | 0.00 | 0.00 | 744.00 | 0.00 | -112469114.7 | 58.99 | 0.00 | 0.00 |
September | 0.308820E+09 | -199736156.4 | 0.00 | 0.00 | 720.00 | 0.00 | -109083560.8 | 58.99 | 0.00 | 0.00 |
October | 0.325340E+09 | -210823355.1 | 0.00 | 0.00 | 744.00 | 0.00 | -114516868.2 | 58.99 | 0.00 | 0.00 |
November | 0.326500E+09 | -211650665.4 | 0.00 | 0.00 | 720.00 | 0.00 | -114849286.1 | 59.00 | 0.00 | 0.00 |
December | 0.348592E+09 | -227813849.8 | 0.00 | 0.00 | 744.00 | 0.00 | -120777774.5 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.395705E+10 | -.258951E+10 | 8760.00 | -.136755E+10 | 58.99 | |||||
Minimum of Months | 0.308820E+09 | -237169605.5 | 0.00 | 0.00 | 672.00 | 0.00 | -121318508.8 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.355378E+09 | -199736156.4 | 0.00 | 0.00 | 744.00 | 0.00 | -108594989.6 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK3
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.328725E+09 | -205142744.4 | 0.00 | 0.00 | 744.00 | 0.00 | -123582713.7 | 59.00 | 0.00 | 0.00 |
February | 0.298289E+09 | -187715895.7 | 0.00 | 0.00 | 672.00 | 0.00 | -110572951.6 | 59.00 | 0.00 | 0.00 |
March | 0.332011E+09 | -211799732.2 | 0.00 | 0.00 | 744.00 | 0.00 | -120210789.1 | 59.00 | 0.00 | 0.00 |
April | 0.307091E+09 | -193891644.9 | 0.00 | 0.00 | 720.00 | 0.00 | -113198877.6 | 58.99 | 0.00 | 0.00 |
May | 0.308425E+09 | -194787025.9 | 0.00 | 0.00 | 744.00 | 0.00 | -113638203.5 | 58.99 | 0.00 | 0.00 |
June | 0.292458E+09 | -183960611.8 | 0.00 | 0.00 | 720.00 | 0.00 | -108497205.0 | 58.99 | 0.00 | 0.00 |
July | 0.289006E+09 | -177690472.6 | 0.00 | 0.00 | 744.00 | 0.00 | -111315275.3 | 59.00 | 0.00 | 0.00 |
August | 0.294894E+09 | -183787874.3 | 0.00 | 0.00 | 744.00 | 0.00 | -111106408.2 | 58.99 | 0.00 | 0.00 |
September | 0.283790E+09 | -175414742.3 | 0.00 | 0.00 | 720.00 | 0.00 | -108375161.9 | 58.99 | 0.00 | 0.00 |
October | 0.300795E+09 | -185411845.9 | 0.00 | 0.00 | 744.00 | 0.00 | -115382846.0 | 58.99 | 0.00 | 0.00 |
November | 0.303585E+09 | -186870579.2 | 0.00 | 0.00 | 720.00 | 0.00 | -116714600.0 | 59.00 | 0.00 | 0.00 |
December | 0.321874E+09 | -198879380.9 | 0.00 | 0.00 | 744.00 | 0.00 | -122994653.2 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.366094E+10 | -.228535E+10 | 8760.00 | -.137559E+10 | 58.99 | |||||
Minimum of Months | 0.283790E+09 | -211799732.2 | 0.00 | 0.00 | 672.00 | 0.00 | -123582713.7 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.332011E+09 | -175414742.3 | 0.00 | 0.00 | 744.00 | 0.00 | -108375161.9 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK4
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.329239E+09 | -205146269.9 | 0.00 | 0.00 | 744.00 | 0.00 | -124092474.8 | 59.00 | 0.00 | 0.00 |
February | 0.298797E+09 | -187763345.6 | 0.00 | 0.00 | 672.00 | 0.00 | -111033351.0 | 58.98 | 0.00 | 0.00 |
March | 0.332688E+09 | -211853922.4 | 0.00 | 0.00 | 744.00 | 0.00 | -120833945.4 | 58.98 | 0.00 | 0.00 |
April | 0.307735E+09 | -193896919.8 | 0.00 | 0.00 | 720.00 | 0.00 | -113838336.9 | 58.99 | 0.00 | 0.00 |
May | 0.308748E+09 | -194783313.0 | 0.00 | 0.00 | 744.00 | 0.00 | -113964251.6 | 58.99 | 0.00 | 0.00 |
June | 0.292560E+09 | -183959656.8 | 0.00 | 0.00 | 720.00 | 0.00 | -108600113.6 | 58.99 | 0.00 | 0.00 |
July | 0.289057E+09 | -177696394.0 | 0.00 | 0.00 | 744.00 | 0.00 | -111360857.8 | 59.00 | 0.00 | 0.00 |
August | 0.294916E+09 | -183782142.5 | 0.00 | 0.00 | 744.00 | 0.00 | -111133969.4 | 58.99 | 0.00 | 0.00 |
September | 0.283936E+09 | -175374972.0 | 0.00 | 0.00 | 720.00 | 0.00 | -108560725.6 | 59.00 | 0.00 | 0.00 |
October | 0.301441E+09 | -185406822.3 | 0.00 | 0.00 | 744.00 | 0.00 | -116034056.2 | 58.99 | 0.00 | 0.00 |
November | 0.304167E+09 | -186878863.4 | 0.00 | 0.00 | 720.00 | 0.00 | -117288422.0 | 58.99 | 0.00 | 0.00 |
December | 0.322366E+09 | -198882385.9 | 0.00 | 0.00 | 744.00 | 0.00 | -123483501.4 | 58.98 | 0.00 | 0.00 |
Annual Sum or Average | 0.366565E+10 | -.228543E+10 | 8760.00 | -.138022E+10 | 58.99 | |||||
Minimum of Months | 0.283936E+09 | -211853922.4 | 0.00 | 0.00 | 672.00 | 0.00 | -124092474.8 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.332688E+09 | -175374972.0 | 0.00 | 0.00 | 744.00 | 0.00 | -108560725.6 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK5
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.319583E+09 | -193895912.7 | 0.00 | 0.00 | 744.00 | 0.00 | -125687109.3 | 59.00 | 0.00 | 0.00 |
February | 0.290196E+09 | -177534185.1 | 0.00 | 0.00 | 672.00 | 0.00 | -112662278.6 | 58.99 | 0.00 | 0.00 |
March | 0.323538E+09 | -200427192.7 | 0.00 | 0.00 | 744.00 | 0.00 | -123110836.9 | 58.99 | 0.00 | 0.00 |
April | 0.299856E+09 | -183488790.5 | 0.00 | 0.00 | 720.00 | 0.00 | -116367194.0 | 58.99 | 0.00 | 0.00 |
May | 0.300311E+09 | -184190909.6 | 0.00 | 0.00 | 744.00 | 0.00 | -116120040.5 | 59.00 | 0.00 | 0.00 |
June | 0.283846E+09 | -174038910.4 | 0.00 | 0.00 | 720.00 | 0.00 | -109806962.5 | 59.00 | 0.00 | 0.00 |
July | 0.280357E+09 | -168072459.4 | 0.00 | 0.00 | 744.00 | 0.00 | -112284824.7 | 58.99 | 0.00 | 0.00 |
August | 0.286001E+09 | -173901407.1 | 0.00 | 0.00 | 744.00 | 0.00 | -112099494.0 | 58.99 | 0.00 | 0.00 |
September | 0.275777E+09 | -165976308.6 | 0.00 | 0.00 | 720.00 | 0.00 | -109800756.4 | 59.00 | 0.00 | 0.00 |
October | 0.293855E+09 | -175219459.7 | 0.00 | 0.00 | 744.00 | 0.00 | -118635212.1 | 59.00 | 0.00 | 0.00 |
November | 0.295623E+09 | -176503183.5 | 0.00 | 0.00 | 720.00 | 0.00 | -119119982.1 | 58.99 | 0.00 | 0.00 |
December | 0.313012E+09 | -188085810.5 | 0.00 | 0.00 | 744.00 | 0.00 | -124925942.9 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.356196E+10 | -.216133E+10 | 8760.00 | -.140062E+10 | 58.99 | |||||
Minimum of Months | 0.275777E+09 | -200427192.7 | 0.00 | 0.00 | 672.00 | 0.00 | -125687109.3 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.323538E+09 | -165976308.6 | 0.00 | 0.00 | 744.00 | 0.00 | -109800756.4 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK6
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.319579E+09 | -193895880.0 | 0.00 | 0.00 | 744.00 | 0.00 | -125683417.5 | 59.00 | 0.00 | 0.00 |
February | 0.290237E+09 | -177534583.3 | 0.00 | 0.00 | 672.00 | 0.00 | -112702727.7 | 58.99 | 0.00 | 0.00 |
March | 0.323684E+09 | -200427647.9 | 0.00 | 0.00 | 744.00 | 0.00 | -123256138.2 | 58.99 | 0.00 | 0.00 |
April | 0.300114E+09 | -183484273.0 | 0.00 | 0.00 | 720.00 | 0.00 | -116629395.1 | 58.99 | 0.00 | 0.00 |
May | 0.300658E+09 | -184208900.3 | 0.00 | 0.00 | 744.00 | 0.00 | -116449408.2 | 58.99 | 0.00 | 0.00 |
June | 0.284004E+09 | -174061408.0 | 0.00 | 0.00 | 720.00 | 0.00 | -109942513.4 | 58.99 | 0.00 | 0.00 |
July | 0.280487E+09 | -168101725.3 | 0.00 | 0.00 | 744.00 | 0.00 | -112384788.7 | 58.98 | 0.00 | 0.00 |
August | 0.286122E+09 | -173906204.4 | 0.00 | 0.00 | 744.00 | 0.00 | -112215450.0 | 58.99 | 0.00 | 0.00 |
September | 0.275967E+09 | -165974326.8 | 0.00 | 0.00 | 720.00 | 0.00 | -109992346.8 | 59.00 | 0.00 | 0.00 |
October | 0.294135E+09 | -175223329.2 | 0.00 | 0.00 | 744.00 | 0.00 | -118911318.8 | 59.00 | 0.00 | 0.00 |
November | 0.295722E+09 | -176493580.8 | 0.00 | 0.00 | 720.00 | 0.00 | -119228126.8 | 58.99 | 0.00 | 0.00 |
December | 0.313040E+09 | -188067496.2 | 0.00 | 0.00 | 744.00 | 0.00 | -124972400.6 | 59.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.356375E+10 | -.216138E+10 | 8760.00 | -.140237E+10 | 58.99 | |||||
Minimum of Months | 0.275967E+09 | -200427647.9 | 0.00 | 0.00 | 672.00 | 0.00 | -125683417.5 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.323684E+09 | -165974326.8 | 0.00 | 0.00 | 744.00 | 0.00 | -109942513.4 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK7
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.319694E+09 | -193897496.6 | 0.00 | 0.00 | 744.00 | 0.00 | -125796780.3 | 59.00 | 0.00 | 0.00 |
February | 0.290358E+09 | -177538212.3 | 0.00 | 0.00 | 672.00 | 0.00 | -112819670.5 | 58.99 | 0.00 | 0.00 |
March | 0.323872E+09 | -200429833.4 | 0.00 | 0.00 | 744.00 | 0.00 | -123442488.1 | 58.99 | 0.00 | 0.00 |
April | 0.300376E+09 | -183479575.7 | 0.00 | 0.00 | 720.00 | 0.00 | -116896190.4 | 58.99 | 0.00 | 0.00 |
May | 0.301069E+09 | -184207575.6 | 0.00 | 0.00 | 744.00 | 0.00 | -116861200.4 | 58.99 | 0.00 | 0.00 |
June | 0.284190E+09 | -174066737.5 | 0.00 | 0.00 | 720.00 | 0.00 | -110123057.4 | 58.99 | 0.00 | 0.00 |
July | 0.280591E+09 | -168099372.1 | 0.00 | 0.00 | 744.00 | 0.00 | -112491405.0 | 58.98 | 0.00 | 0.00 |
August | 0.286218E+09 | -173896574.4 | 0.00 | 0.00 | 744.00 | 0.00 | -112321242.5 | 59.00 | 0.00 | 0.00 |
September | 0.276134E+09 | -166012660.8 | 0.00 | 0.00 | 720.00 | 0.00 | -110121708.9 | 58.98 | 0.00 | 0.00 |
October | 0.294415E+09 | -175252123.9 | 0.00 | 0.00 | 744.00 | 0.00 | -119162662.1 | 58.99 | 0.00 | 0.00 |
November | 0.295866E+09 | -176510281.1 | 0.00 | 0.00 | 720.00 | 0.00 | -119355260.7 | 58.99 | 0.00 | 0.00 |
December | 0.313137E+09 | -188084449.6 | 0.00 | 0.00 | 744.00 | 0.00 | -125052773.3 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.356592E+10 | -.216147E+10 | 8760.00 | -.140444E+10 | 58.99 | |||||
Minimum of Months | 0.276134E+09 | -200429833.4 | 0.00 | 0.00 | 672.00 | 0.00 | -125796780.3 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.323872E+09 | -166012660.8 | 0.00 | 0.00 | 744.00 | 0.00 | -110121708.9 | 59.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 237.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 259.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 247.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 379.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 427.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 375.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 471.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 366.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 301.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 245.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 242.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 160.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3714.00 | ||||||||||
Minimum of Months | 160.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 471.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.108270E+11 | 59163.99 | 01-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.705904E+10 | 59163.99 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.237584E+10 | 59163.99 | 05-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.471793E+09 | 59163.99 | 01-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 11335499.93 | 4247.63 | 18-MAY-08:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 44864074.97 | 24228.67 | 31-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.421757E+10 | 59163.99 | 13-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.849017E+10 | 59163.99 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.334977E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.108270E+11 | 59163.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.336292E+10 | 31956.19 | 05-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.198768E+10 | 31956.19 | 13-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.369326E+09 | 25147.88 | 24-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 29861608.03 | 5335.10 | 19-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 29024.66 | 48.37 | 31-OCT-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.115206E+10 | 24129.19 | 30-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.250421E+10 | 31956.19 | 22-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.940609E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.336292E+10 | 31956.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_3:3_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.450126E+10 | 31952.59 | 01-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.275735E+10 | 31952.59 | 12-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.745648E+09 | 25962.81 | 06-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.110077E+09 | 8925.37 | 19-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 393360.85 | 340.23 | 18-MAY-07:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6159214.20 | 1205.26 | 30-OCT-07:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.174437E+10 | 20894.68 | 24-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.353078E+10 | 31952.59 | 18-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.133960E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.450126E+10 | 31952.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_4:4_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.483117E+10 | 32028.66 | 01-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.298058E+10 | 32028.66 | 12-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.930778E+09 | 32028.66 | 06-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.165347E+09 | 12982.54 | 19-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 762756.84 | 849.21 | 18-MAY-07:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 21297686.84 | 2146.83 | 30-OCT-07:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.195823E+10 | 27486.91 | 24-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.382845E+10 | 32028.66 | 18-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.147166E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.483117E+10 | 32028.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_5:5_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.526535E+10 | 31834.54 | 01-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.329044E+10 | 31834.54 | 06-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.120466E+10 | 31834.54 | 06-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.267396E+09 | 17112.90 | 19-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 2616801.18 | 1289.66 | 18-MAY-07:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 67498542.77 | 5116.22 | 29-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.224075E+10 | 31834.54 | 24-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.422533E+10 | 31834.54 | 18-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.165640E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.526535E+10 | 31834.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_6:6_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.114271E+11 | 57516.69 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.740150E+10 | 57516.69 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.350167E+10 | 57516.69 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.106537E+10 | 57516.69 | 01-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 40069823.35 | 6923.69 | 29-MAY-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.574485E+09 | 57516.69 | 29-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.558297E+10 | 57516.69 | 11-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.954834E+10 | 57516.69 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.391415E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.114271E+11 | 57516.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_7:7_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.610603E+10 | 29588.90 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.397599E+10 | 29588.90 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.195254E+10 | 29588.90 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.630206E+09 | 29588.90 | 01-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 32246349.87 | 8469.33 | 29-MAY-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.364410E+09 | 29588.90 | 29-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.301662E+10 | 29588.90 | 11-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.510510E+10 | 29588.90 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.211831E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.610603E+10 | 29588.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_8:8_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.622163E+10 | 29416.34 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.408020E+10 | 29416.34 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.208085E+10 | 29416.34 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.706023E+09 | 29416.34 | 01-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 47812314.04 | 13226.53 | 29-MAY-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.421622E+09 | 29416.34 | 16-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.311514E+10 | 29416.34 | 11-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.521240E+10 | 29416.34 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.218857E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.622163E+10 | 29416.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_9:9_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.662395E+10 | 29221.12 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.443254E+10 | 29221.12 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.245602E+10 | 29221.12 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.922572E+09 | 29221.12 | 01-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.104160E+09 | 24273.58 | 29-MAY-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 828560.05 | 686.44 | 28-SEP-08:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.568596E+09 | 29221.12 | 16-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.340446E+10 | 29221.12 | 02-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.558087E+10 | 29221.12 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.240940E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.662395E+10 | 29221.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_10:10_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.826247E+10 | 29201.40 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.583663E+10 | 29201.40 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.382016E+10 | 29201.40 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.174703E+10 | 29201.40 | 01-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.425293E+09 | 29201.40 | 11-MAY-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 14381589.82 | 16376.16 | 14-JUN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 19162581.68 | 10691.37 | 28-SEP-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.111325E+10 | 29201.40 | 15-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.439866E+10 | 29201.40 | 01-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.695801E+10 | 29201.40 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.325950E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.826247E+10 | 29201.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 1276.25 | 1251.16 | 0.30 | 27-FEB-20:40 | 0.28 | 0.00 |
March | 0.00 | 0.00 | 16880.22 | 16880.22 | 3.82 | 18-MAR-14:00 | 3.82 | 0.00 |
April | 0.00 | 0.00 | 0.100887E+10 | 0.978717E+09 | 16468.34 | 27-APR-15:00 | 15784.88 | 0.00 |
May | 0.00 | 0.00 | 0.205452E+10 | 0.185334E+10 | 15052.79 | 06-MAY-13:00 | 12461.30 | 0.00 |
June | 0.00 | 0.00 | 0.356876E+10 | 0.339696E+10 | 16705.76 | 28-JUN-17:00 | 16389.72 | 0.00 |
July | 0.00 | 0.00 | 0.886281E+10 | 0.779173E+10 | 30653.77 | 24-JUL-07:03 | 23626.15 | 0.00 |
August | 0.00 | 0.00 | 0.121517E+11 | 0.106957E+11 | 31893.92 | 10-AUG-07:03 | 23332.35 | 0.00 |
September | 0.00 | 0.00 | 0.352960E+10 | 0.293987E+10 | 21122.92 | 14-SEP-07:02 | 13115.73 | 0.00 |
October | 0.00 | 0.00 | 0.167431E+09 | 0.165017E+09 | 8379.45 | 04-OCT-15:00 | 8379.45 | 0.00 |
November | 0.00 | 0.00 | 67617968.94 | 51602693.93 | 6444.06 | 04-NOV-14:00 | 5008.43 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 |
Annual Sum or Average | 0.314113E+11 | 0.278729E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.121517E+11 | 0.106957E+11 | 31893.92 | 23626.15 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 133719.19 | 131365.25 | 200.92 | 11-JAN-23:10 | 197.04 | 0.00 |
February | 0.00 | 0.00 | 3757515.74 | 3749660.50 | 2064.97 | 28-FEB-21:10 | 2064.97 | 0.00 |
March | 0.00 | 0.00 | 11719579.71 | 11545620.48 | 18295.39 | 08-MAR-21:02 | 18295.39 | 0.00 |
April | 0.00 | 0.00 | 0.721261E+09 | 0.697587E+09 | 18616.26 | 29-APR-18:01 | 15109.12 | 0.00 |
May | 0.00 | 0.00 | 0.139597E+10 | 0.125864E+10 | 19336.01 | 07-MAY-17:02 | 15422.15 | 0.00 |
June | 0.00 | 0.00 | 0.252838E+10 | 0.238157E+10 | 19051.80 | 11-JUN-17:53 | 16087.72 | 0.00 |
July | 0.00 | 0.00 | 0.560446E+10 | 0.490566E+10 | 19799.59 | 15-JUL-18:02 | 14424.85 | 0.00 |
August | 0.00 | 0.00 | 0.740210E+10 | 0.649188E+10 | 19673.58 | 26-AUG-18:02 | 13166.21 | 0.00 |
September | 0.00 | 0.00 | 0.234419E+10 | 0.193725E+10 | 19523.12 | 23-SEP-18:02 | 13748.90 | 0.00 |
October | 0.00 | 0.00 | 0.132439E+09 | 0.130095E+09 | 18288.84 | 23-OCT-20:04 | 17922.18 | 0.00 |
November | 0.00 | 0.00 | 52277408.47 | 40467498.44 | 4376.56 | 04-NOV-14:00 | 3426.46 | 0.00 |
December | 0.00 | 0.00 | 24189.29 | 24189.29 | 19.82 | 03-DEC-23:10 | 19.82 | 0.00 |
Annual Sum or Average | 0.201967E+11 | 0.178586E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 24189.29 | 24189.29 | 19.82 | 19.82 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.740210E+10 | 0.649188E+10 | 19799.59 | 18295.39 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 912.71 | 900.88 | 0.23 | 27-FEB-12:00 | 0.23 | 0.00 |
March | 0.00 | 0.00 | 542841.83 | 542748.03 | 350.25 | 18-MAR-16:00 | 350.25 | 0.00 |
April | 0.00 | 0.00 | 0.502045E+09 | 0.488408E+09 | 9067.76 | 27-APR-15:00 | 8735.57 | 0.00 |
May | 0.00 | 0.00 | 0.101154E+10 | 0.916433E+09 | 8524.67 | 06-MAY-13:00 | 7106.04 | 0.00 |
June | 0.00 | 0.00 | 0.172145E+10 | 0.164973E+10 | 10809.40 | 12-JUN-06:02 | 7042.55 | 0.00 |
July | 0.00 | 0.00 | 0.400833E+10 | 0.355317E+10 | 18666.26 | 25-JUL-06:02 | 11744.12 | 0.00 |
August | 0.00 | 0.00 | 0.550282E+10 | 0.487210E+10 | 19287.11 | 25-AUG-06:03 | 13338.06 | 0.00 |
September | 0.00 | 0.00 | 0.174597E+10 | 0.145941E+10 | 18308.84 | 14-SEP-06:01 | 11537.54 | 0.00 |
October | 0.00 | 0.00 | 93634710.60 | 92600255.97 | 4601.55 | 04-OCT-15:00 | 4601.55 | 0.00 |
November | 0.00 | 0.00 | 39229775.66 | 30103500.06 | 3723.62 | 04-NOV-14:00 | 2911.09 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 |
Annual Sum or Average | 0.146256E+11 | 0.130625E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.550282E+10 | 0.487210E+10 | 19287.11 | 13338.06 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 655.93 | 645.79 | 0.15 | 27-FEB-19:40 | 0.14 | 0.00 |
March | 0.00 | 0.00 | 131915.35 | 131885.92 | 152.59 | 18-MAR-16:00 | 152.59 | 0.00 |
April | 0.00 | 0.00 | 0.484992E+09 | 0.471714E+09 | 8929.48 | 27-APR-15:00 | 8601.54 | 0.00 |
May | 0.00 | 0.00 | 0.984989E+09 | 0.892609E+09 | 8487.19 | 06-MAY-13:00 | 7074.01 | 0.00 |
June | 0.00 | 0.00 | 0.169450E+10 | 0.162417E+10 | 9684.03 | 12-JUN-06:02 | 6306.14 | 0.00 |
July | 0.00 | 0.00 | 0.398362E+10 | 0.353136E+10 | 18767.30 | 31-JUL-06:03 | 13444.29 | 0.00 |
August | 0.00 | 0.00 | 0.548626E+10 | 0.485754E+10 | 19339.71 | 25-AUG-06:03 | 13377.64 | 0.00 |
September | 0.00 | 0.00 | 0.172482E+10 | 0.144197E+10 | 18358.28 | 14-SEP-06:01 | 11567.24 | 0.00 |
October | 0.00 | 0.00 | 88039020.92 | 87160059.01 | 4518.69 | 04-OCT-15:00 | 4518.69 | 0.00 |
November | 0.00 | 0.00 | 33177172.96 | 25486062.02 | 3325.05 | 04-NOV-14:00 | 2597.41 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 |
Annual Sum or Average | 0.144805E+11 | 0.129321E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.548626E+10 | 0.485754E+10 | 19339.71 | 13444.29 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 349.73 | 347.01 | 0.15 | 27-FEB-13:50 | 0.15 | 0.00 |
March | 0.00 | 0.00 | 8308.01 | 8308.01 | 2.06 | 18-MAR-14:00 | 2.06 | 0.00 |
April | 0.00 | 0.00 | 0.453351E+09 | 0.440879E+09 | 8617.08 | 27-APR-15:00 | 8296.37 | 0.00 |
May | 0.00 | 0.00 | 0.921504E+09 | 0.835714E+09 | 8249.26 | 06-MAY-13:00 | 6867.91 | 0.00 |
June | 0.00 | 0.00 | 0.160720E+10 | 0.154182E+10 | 8684.45 | 28-JUN-17:00 | 8557.13 | 0.00 |
July | 0.00 | 0.00 | 0.383833E+10 | 0.340488E+10 | 16569.66 | 31-JUL-06:03 | 11846.17 | 0.00 |
August | 0.00 | 0.00 | 0.531599E+10 | 0.471029E+10 | 18946.16 | 26-AUG-06:02 | 11468.07 | 0.00 |
September | 0.00 | 0.00 | 0.164768E+10 | 0.137850E+10 | 17957.58 | 14-SEP-06:01 | 11284.90 | 0.00 |
October | 0.00 | 0.00 | 79044908.44 | 78377299.07 | 4325.95 | 04-OCT-15:00 | 4325.95 | 0.00 |
November | 0.00 | 0.00 | 24464611.99 | 18824641.49 | 2700.79 | 04-NOV-14:00 | 2106.34 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 |
Annual Sum or Average | 0.138876E+11 | 0.124093E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.531599E+10 | 0.471029E+10 | 18946.16 | 11846.17 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 159.26 | 159.26 | 0.19 | 27-FEB-14:50 | 0.19 | 0.00 |
March | 0.00 | 0.00 | 8552.02 | 8552.02 | 2.52 | 18-MAR-13:50 | 2.52 | 0.00 |
April | 0.00 | 0.00 | 0.696182E+09 | 0.672918E+09 | 14696.67 | 27-APR-15:00 | 13923.72 | 0.00 |
May | 0.00 | 0.00 | 0.136095E+10 | 0.122971E+10 | 13697.86 | 06-MAY-13:30 | 11392.19 | 0.00 |
June | 0.00 | 0.00 | 0.253881E+10 | 0.242643E+10 | 14917.67 | 28-JUN-17:00 | 14514.98 | 0.00 |
July | 0.00 | 0.00 | 0.637791E+10 | 0.561359E+10 | 33746.28 | 24-JUL-07:03 | 26473.05 | 0.00 |
August | 0.00 | 0.00 | 0.907494E+10 | 0.799118E+10 | 33716.57 | 14-AUG-07:02 | 22970.77 | 0.00 |
September | 0.00 | 0.00 | 0.260933E+10 | 0.216872E+10 | 16427.69 | 14-SEP-14:10 | 13701.35 | 0.00 |
October | 0.00 | 0.00 | 0.106505E+09 | 0.106028E+09 | 7085.43 | 04-OCT-15:00 | 7085.43 | 0.00 |
November | 0.00 | 0.00 | 20528619.71 | 15731173.15 | 2890.47 | 04-NOV-14:20 | 2235.86 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 |
Annual Sum or Average | 0.227852E+11 | 0.202243E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.907494E+10 | 0.799118E+10 | 33746.28 | 26473.05 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 40.81 | 40.81 | 0.07 | 27-FEB-15:00 | 0.07 | 0.00 |
March | 0.00 | 0.00 | 3636.80 | 3636.80 | 1.40 | 18-MAR-14:00 | 1.40 | 0.00 |
April | 0.00 | 0.00 | 0.350408E+09 | 0.339158E+09 | 7566.75 | 27-APR-15:00 | 7175.67 | 0.00 |
May | 0.00 | 0.00 | 0.677460E+09 | 0.613112E+09 | 7024.39 | 06-MAY-13:30 | 5850.16 | 0.00 |
June | 0.00 | 0.00 | 0.127969E+10 | 0.122531E+10 | 7726.17 | 28-JUN-17:00 | 7529.72 | 0.00 |
July | 0.00 | 0.00 | 0.324797E+10 | 0.286588E+10 | 15647.94 | 24-JUL-07:03 | 12292.18 | 0.00 |
August | 0.00 | 0.00 | 0.465217E+10 | 0.410676E+10 | 17451.25 | 14-AUG-07:02 | 11905.39 | 0.00 |
September | 0.00 | 0.00 | 0.132089E+10 | 0.110098E+10 | 8463.86 | 14-SEP-14:10 | 7073.88 | 0.00 |
October | 0.00 | 0.00 | 52570148.18 | 52394109.09 | 3624.66 | 04-OCT-15:00 | 3624.66 | 0.00 |
November | 0.00 | 0.00 | 9107260.55 | 7006340.48 | 1370.56 | 04-NOV-14:30 | 1063.37 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 |
Annual Sum or Average | 0.115903E+11 | 0.103106E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.465217E+10 | 0.410676E+10 | 17451.25 | 12292.18 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 73.81 | 73.81 | 0.12 | 27-FEB-15:10 | 0.12 | 0.00 |
March | 0.00 | 0.00 | 3167.89 | 3167.89 | 1.25 | 18-MAR-14:00 | 1.25 | 0.00 |
April | 0.00 | 0.00 | 0.337089E+09 | 0.326299E+09 | 7393.89 | 27-APR-15:00 | 7008.70 | 0.00 |
May | 0.00 | 0.00 | 0.644805E+09 | 0.583218E+09 | 6895.11 | 06-MAY-13:30 | 5737.04 | 0.00 |
June | 0.00 | 0.00 | 0.123959E+10 | 0.118701E+10 | 7637.05 | 28-JUN-17:00 | 7441.25 | 0.00 |
July | 0.00 | 0.00 | 0.318208E+10 | 0.280773E+10 | 14613.63 | 24-JUL-07:03 | 11466.92 | 0.00 |
August | 0.00 | 0.00 | 0.457725E+10 | 0.404057E+10 | 17177.41 | 14-AUG-07:02 | 11705.05 | 0.00 |
September | 0.00 | 0.00 | 0.128853E+10 | 0.107394E+10 | 8367.51 | 14-SEP-14:10 | 6988.78 | 0.00 |
October | 0.00 | 0.00 | 49559201.46 | 49434199.02 | 3507.29 | 04-OCT-15:00 | 3507.29 | 0.00 |
November | 0.00 | 0.00 | 7791249.45 | 5996724.60 | 1233.82 | 04-NOV-14:30 | 956.70 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 |
Annual Sum or Average | 0.113267E+11 | 0.100742E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.457725E+10 | 0.404057E+10 | 17177.41 | 11705.05 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 2252.86 | 2252.86 | 0.80 | 18-MAR-14:10 | 0.80 | 0.00 |
April | 0.00 | 0.00 | 0.309051E+09 | 0.299363E+09 | 7059.59 | 27-APR-15:00 | 6687.06 | 0.00 |
May | 0.00 | 0.00 | 0.577457E+09 | 0.521940E+09 | 6604.36 | 06-MAY-13:30 | 5484.39 | 0.00 |
June | 0.00 | 0.00 | 0.114873E+10 | 0.110084E+10 | 7453.55 | 28-JUN-17:00 | 7260.40 | 0.00 |
July | 0.00 | 0.00 | 0.303756E+10 | 0.268128E+10 | 11052.39 | 24-JUL-07:03 | 8645.31 | 0.00 |
August | 0.00 | 0.00 | 0.442376E+10 | 0.390664E+10 | 12735.31 | 14-AUG-07:02 | 8651.52 | 0.00 |
September | 0.00 | 0.00 | 0.122419E+10 | 0.102050E+10 | 8214.67 | 14-SEP-14:10 | 6854.26 | 0.00 |
October | 0.00 | 0.00 | 42605480.03 | 42577478.73 | 3232.88 | 04-OCT-15:00 | 3232.88 | 0.00 |
November | 0.00 | 0.00 | 5388581.73 | 4153272.91 | 960.53 | 04-NOV-14:30 | 744.08 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 |
Annual Sum or Average | 0.107688E+11 | 0.957730E+10 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.442376E+10 | 0.390664E+10 | 12735.31 | 8651.52 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.261922E+09 | 0.254644E+09 | 6627.79 | 27-APR-15:00 | 6285.58 | 0.00 |
May | 0.00 | 0.00 | 0.467780E+09 | 0.424062E+09 | 6082.27 | 06-MAY-13:30 | 5044.55 | 0.00 |
June | 0.00 | 0.00 | 0.973102E+09 | 0.935984E+09 | 7035.85 | 28-JUN-17:00 | 6866.51 | 0.00 |
July | 0.00 | 0.00 | 0.275714E+10 | 0.244464E+10 | 10673.90 | 24-JUL-15:00 | 10176.10 | 0.00 |
August | 0.00 | 0.00 | 0.420331E+10 | 0.372413E+10 | 11665.12 | 29-AUG-14:50 | 10226.13 | 0.00 |
September | 0.00 | 0.00 | 0.112982E+10 | 0.943097E+09 | 8039.90 | 14-SEP-14:10 | 6716.26 | 0.00 |
October | 0.00 | 0.00 | 30529465.89 | 30529057.03 | 2635.02 | 04-OCT-15:00 | 2635.02 | 0.00 |
November | 0.00 | 0.00 | 2492880.67 | 1929192.98 | 546.22 | 04-NOV-14:30 | 423.60 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 |
Annual Sum or Average | 0.982610E+10 | 0.875902E+10 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.420331E+10 | 0.372413E+10 | 11665.12 | 10226.13 | 0.00 |
Report: FanReportMonthly
For: PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.412041E+10 | 0.62 | 2270.26 | 01-JAN-08:10 | 0.91 |
February | 0.372803E+10 | 0.62 | 2270.26 | 01-FEB-08:02 | 0.91 |
March | 0.412748E+10 | 0.62 | 2270.26 | 01-MAR-09:35 | 0.91 |
April | 0.399656E+10 | 0.62 | 2270.26 | 01-APR-13:00 | 0.91 |
May | 0.411915E+10 | 0.61 | 2270.26 | 01-MAY-17:50 | 0.91 |
June | 0.399656E+10 | 0.62 | 2270.26 | 01-JUN-12:50 | 0.91 |
July | 0.412733E+10 | 0.61 | 2270.26 | 01-JUL-19:30 | 0.91 |
August | 0.411915E+10 | 0.61 | 2270.26 | 01-AUG-07:40 | 0.90 |
September | 0.400473E+10 | 0.62 | 2270.26 | 01-SEP-16:40 | 0.90 |
October | 0.411915E+10 | 0.61 | 2270.26 | 01-OCT-15:10 | 0.90 |
November | 0.398051E+10 | 0.61 | 2270.26 | 02-NOV-08:30 | 0.91 |
December | 0.413611E+10 | 0.62 | 2270.26 | 01-DEC-13:10 | 0.91 |
Annual Sum or Average | 0.485752E+11 | 0.62 | |||
Minimum of Months | 0.372803E+10 | 0.61 | 2270.26 | 0.90 | |
Maximum of Months | 0.413611E+10 | 0.62 | 2270.26 | 0.91 |
Report: FanReportMonthly
For: PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.176976E+10 | 0.49 | 1302.52 | 01-JAN-09:06 | 0.95 |
February | 0.162672E+10 | 0.53 | 1302.52 | 01-FEB-09:50 | 0.95 |
March | 0.188772E+10 | 0.61 | 1302.52 | 03-MAR-17:50 | 0.94 |
April | 0.194895E+10 | 0.63 | 1302.52 | 02-APR-12:00 | 0.95 |
May | 0.218964E+10 | 0.63 | 1302.52 | 03-MAY-18:30 | 0.94 |
June | 0.219202E+10 | 0.62 | 1302.52 | 02-JUN-17:10 | 0.95 |
July | 0.219971E+10 | 0.61 | 1302.52 | 01-JUL-12:40 | 0.94 |
August | 0.217575E+10 | 0.60 | 1302.52 | 01-AUG-17:00 | 0.94 |
September | 0.220906E+10 | 0.63 | 1302.52 | 01-SEP-13:30 | 0.94 |
October | 0.214677E+10 | 0.64 | 1302.52 | 03-OCT-09:10 | 0.95 |
November | 0.183899E+10 | 0.57 | 1302.52 | 09-NOV-15:40 | 0.95 |
December | 0.176232E+10 | 0.51 | 1302.52 | 01-DEC-09:40 | 0.95 |
Annual Sum or Average | 0.239474E+11 | 0.59 | |||
Minimum of Months | 0.162672E+10 | 0.49 | 1302.52 | 0.94 | |
Maximum of Months | 0.220906E+10 | 0.64 | 1302.52 | 0.95 |
Report: FanReportMonthly
For: PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.188475E+10 | 0.51 | 1302.34 | 30-JAN-08:05 | 0.95 |
February | 0.170659E+10 | 0.51 | 1302.34 | 01-FEB-08:06 | 0.95 |
March | 0.192226E+10 | 0.52 | 1302.34 | 01-MAR-08:20 | 0.95 |
April | 0.182849E+10 | 0.51 | 1302.34 | 01-APR-12:10 | 0.95 |
May | 0.190351E+10 | 0.52 | 1302.34 | 01-MAY-13:20 | 0.94 |
June | 0.185662E+10 | 0.52 | 1302.34 | 01-JUN-06:09 | 0.94 |
July | 0.187537E+10 | 0.51 | 1302.34 | 01-JUL-06:40 | 0.94 |
August | 0.192226E+10 | 0.52 | 1302.34 | 01-AUG-06:30 | 0.94 |
September | 0.182849E+10 | 0.51 | 1302.34 | 01-SEP-06:02 | 0.94 |
October | 0.188475E+10 | 0.51 | 1302.34 | 01-OCT-14:50 | 0.94 |
November | 0.182849E+10 | 0.51 | 1302.34 | 04-NOV-12:30 | 0.94 |
December | 0.187537E+10 | 0.51 | 1302.34 | 01-DEC-08:02 | 0.95 |
Annual Sum or Average | 0.223170E+11 | 0.51 | |||
Minimum of Months | 0.170659E+10 | 0.51 | 1302.34 | 0.94 | |
Maximum of Months | 0.192226E+10 | 0.52 | 1302.34 | 0.95 |
Report: FanReportMonthly
For: PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.189032E+10 | 0.51 | 1306.19 | 01-JAN-09:04 | 0.95 |
February | 0.171163E+10 | 0.51 | 1306.19 | 01-FEB-09:40 | 0.95 |
March | 0.192794E+10 | 0.52 | 1306.19 | 01-MAR-08:09 | 0.95 |
April | 0.183389E+10 | 0.51 | 1306.19 | 01-APR-08:70 | 0.95 |
May | 0.190913E+10 | 0.52 | 1306.19 | 06-MAY-10:10 | 0.94 |
June | 0.186211E+10 | 0.52 | 1306.19 | 01-JUN-09:50 | 0.94 |
July | 0.188092E+10 | 0.51 | 1306.19 | 01-JUL-07:07 | 0.94 |
August | 0.192794E+10 | 0.52 | 1306.19 | 01-AUG-09:10 | 0.94 |
September | 0.183389E+10 | 0.51 | 1306.19 | 12-SEP-10:10 | 0.94 |
October | 0.189032E+10 | 0.51 | 1306.19 | 07-OCT-06:10 | 0.94 |
November | 0.183389E+10 | 0.51 | 1306.19 | 05-NOV-14:30 | 0.94 |
December | 0.188092E+10 | 0.51 | 1306.19 | 01-DEC-11:20 | 0.95 |
Annual Sum or Average | 0.223829E+11 | 0.51 | |||
Minimum of Months | 0.171163E+10 | 0.51 | 1306.19 | 0.94 | |
Maximum of Months | 0.192794E+10 | 0.52 | 1306.19 | 0.95 |
Report: FanReportMonthly
For: PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.187611E+10 | 0.51 | 1296.37 | 01-JAN-08:50 | 0.95 |
February | 0.169877E+10 | 0.51 | 1296.37 | 01-FEB-08:40 | 0.95 |
March | 0.191345E+10 | 0.52 | 1296.37 | 01-MAR-08:06 | 0.95 |
April | 0.182011E+10 | 0.51 | 1296.37 | 01-APR-13:10 | 0.95 |
May | 0.189478E+10 | 0.52 | 1296.37 | 01-MAY-17:40 | 0.94 |
June | 0.184811E+10 | 0.52 | 1296.37 | 01-JUN-09:30 | 0.94 |
July | 0.186678E+10 | 0.51 | 1296.37 | 01-JUL-07:50 | 0.94 |
August | 0.191345E+10 | 0.52 | 1296.37 | 01-AUG-06:30 | 0.94 |
September | 0.182011E+10 | 0.51 | 1296.37 | 01-SEP-09:10 | 0.94 |
October | 0.187611E+10 | 0.51 | 1296.37 | 02-OCT-10:30 | 0.94 |
November | 0.182011E+10 | 0.51 | 1296.37 | 04-NOV-13:10 | 0.94 |
December | 0.186678E+10 | 0.51 | 1296.37 | 01-DEC-08:00 | 0.95 |
Annual Sum or Average | 0.222146E+11 | 0.51 | |||
Minimum of Months | 0.169877E+10 | 0.51 | 1296.37 | 0.94 | |
Maximum of Months | 0.191345E+10 | 0.52 | 1296.37 | 0.95 |
Report: FanReportMonthly
For: PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.292533E+10 | 0.45 | 2190.27 | 01-JAN-16:00 | 0.91 |
February | 0.264935E+10 | 0.45 | 2190.27 | 01-FEB-14:20 | 0.91 |
March | 0.298841E+10 | 0.46 | 2190.27 | 01-MAR-10:40 | 0.91 |
April | 0.283859E+10 | 0.45 | 2190.27 | 01-APR-08:70 | 0.91 |
May | 0.295687E+10 | 0.46 | 2190.27 | 02-MAY-16:00 | 0.91 |
June | 0.288590E+10 | 0.46 | 2190.27 | 01-JUN-14:20 | 0.91 |
July | 0.290956E+10 | 0.45 | 2190.27 | 01-JUL-09:50 | 0.91 |
August | 0.298841E+10 | 0.46 | 2190.27 | 01-AUG-13:00 | 0.90 |
September | 0.283859E+10 | 0.45 | 2190.27 | 01-SEP-16:10 | 0.90 |
October | 0.292533E+10 | 0.45 | 2190.27 | 01-OCT-13:40 | 0.90 |
November | 0.283859E+10 | 0.45 | 2190.27 | 01-NOV-11:15 | 0.90 |
December | 0.290956E+10 | 0.45 | 2190.27 | 01-DEC-10:00 | 0.91 |
Annual Sum or Average | 0.346545E+11 | 0.45 | |||
Minimum of Months | 0.264935E+10 | 0.45 | 2190.27 | 0.90 | |
Maximum of Months | 0.298841E+10 | 0.46 | 2190.27 | 0.91 |
Report: FanReportMonthly
For: PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.157970E+10 | 0.47 | 1182.77 | 02-JAN-09:00 | 0.95 |
February | 0.143067E+10 | 0.47 | 1182.77 | 01-FEB-09:40 | 0.95 |
March | 0.161376E+10 | 0.48 | 1182.77 | 02-MAR-08:15 | 0.95 |
April | 0.153286E+10 | 0.47 | 1182.77 | 03-APR-16:30 | 0.94 |
May | 0.159673E+10 | 0.48 | 1182.77 | 02-MAY-16:20 | 0.94 |
June | 0.155841E+10 | 0.48 | 1182.77 | 02-JUN-18:10 | 0.95 |
July | 0.157119E+10 | 0.47 | 1182.77 | 01-JUL-13:10 | 0.94 |
August | 0.161376E+10 | 0.48 | 1182.77 | 02-AUG-13:40 | 0.94 |
September | 0.153286E+10 | 0.47 | 1182.77 | 02-SEP-16:20 | 0.94 |
October | 0.157970E+10 | 0.47 | 1182.77 | 01-OCT-14:20 | 0.94 |
November | 0.153286E+10 | 0.47 | 1182.77 | 01-NOV-16:10 | 0.94 |
December | 0.157119E+10 | 0.47 | 1182.77 | 01-DEC-11:50 | 0.95 |
Annual Sum or Average | 0.187137E+11 | 0.47 | |||
Minimum of Months | 0.143067E+10 | 0.47 | 1182.77 | 0.94 | |
Maximum of Months | 0.161376E+10 | 0.48 | 1182.77 | 0.95 |
Report: FanReportMonthly
For: PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.156804E+10 | 0.47 | 1174.04 | 01-JAN-09:18 | 0.95 |
February | 0.142011E+10 | 0.47 | 1174.04 | 01-FEB-08:13 | 0.95 |
March | 0.160185E+10 | 0.48 | 1174.04 | 01-MAR-10:20 | 0.95 |
April | 0.152155E+10 | 0.47 | 1174.04 | 04-APR-09:10 | 0.94 |
May | 0.158495E+10 | 0.48 | 1174.04 | 03-MAY-15:20 | 0.94 |
June | 0.154691E+10 | 0.48 | 1174.04 | 01-JUN-13:00 | 0.95 |
July | 0.155959E+10 | 0.47 | 1174.04 | 01-JUL-14:20 | 0.94 |
August | 0.160185E+10 | 0.48 | 1174.04 | 03-AUG-15:10 | 0.94 |
September | 0.152155E+10 | 0.47 | 1174.04 | 04-SEP-09:20 | 0.94 |
October | 0.156804E+10 | 0.47 | 1174.04 | 02-OCT-14:00 | 0.94 |
November | 0.152155E+10 | 0.47 | 1174.04 | 01-NOV-14:30 | 0.94 |
December | 0.155959E+10 | 0.47 | 1174.04 | 01-DEC-18:30 | 0.95 |
Annual Sum or Average | 0.185756E+11 | 0.47 | |||
Minimum of Months | 0.142011E+10 | 0.47 | 1174.04 | 0.94 | |
Maximum of Months | 0.160185E+10 | 0.48 | 1174.04 | 0.95 |
Report: FanReportMonthly
For: PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.155485E+10 | 0.47 | 1164.16 | 02-JAN-17:20 | 0.95 |
February | 0.140817E+10 | 0.47 | 1164.16 | 01-FEB-09:05 | 0.95 |
March | 0.158838E+10 | 0.48 | 1164.16 | 01-MAR-19:30 | 0.95 |
April | 0.150875E+10 | 0.47 | 1164.16 | 01-APR-08:30 | 0.95 |
May | 0.157162E+10 | 0.48 | 1164.16 | 02-MAY-17:10 | 0.94 |
June | 0.153390E+10 | 0.48 | 1164.16 | 01-JUN-17:00 | 0.95 |
July | 0.154647E+10 | 0.47 | 1164.16 | 02-JUL-16:00 | 0.94 |
August | 0.158838E+10 | 0.48 | 1164.16 | 01-AUG-07:30 | 0.94 |
September | 0.150875E+10 | 0.47 | 1164.16 | 01-SEP-13:30 | 0.94 |
October | 0.155485E+10 | 0.47 | 1164.16 | 02-OCT-15:10 | 0.95 |
November | 0.150875E+10 | 0.47 | 1164.16 | 01-NOV-09:00 | 0.94 |
December | 0.154647E+10 | 0.47 | 1164.16 | 01-DEC-13:20 | 0.95 |
Annual Sum or Average | 0.184193E+11 | 0.47 | |||
Minimum of Months | 0.140817E+10 | 0.47 | 1164.16 | 0.94 | |
Maximum of Months | 0.158838E+10 | 0.48 | 1164.16 | 0.95 |
Report: FanReportMonthly
For: PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.155394E+10 | 0.47 | 1163.15 | 12-JAN-08:50 | 0.95 |
February | 0.140815E+10 | 0.48 | 1163.15 | 23-FEB-08:10 | 0.95 |
March | 0.158700E+10 | 0.48 | 1163.15 | 24-MAR-18:50 | 0.95 |
April | 0.150744E+10 | 0.47 | 1163.15 | 03-APR-14:50 | 0.94 |
May | 0.157025E+10 | 0.48 | 1163.15 | 01-MAY-08:15 | 0.94 |
June | 0.153256E+10 | 0.48 | 1163.15 | 01-JUN-14:00 | 0.95 |
July | 0.154512E+10 | 0.47 | 1163.15 | 12-JUL-18:20 | 0.94 |
August | 0.158700E+10 | 0.48 | 1163.15 | 25-AUG-09:20 | 0.94 |
September | 0.150744E+10 | 0.47 | 1163.15 | 20-SEP-15:40 | 0.94 |
October | 0.155350E+10 | 0.47 | 1163.15 | 02-OCT-08:30 | 0.94 |
November | 0.150744E+10 | 0.47 | 1163.15 | 08-NOV-18:40 | 0.94 |
December | 0.154512E+10 | 0.47 | 1163.15 | 18-DEC-12:00 | 0.95 |
Annual Sum or Average | 0.184049E+11 | 0.47 | |||
Minimum of Months | 0.140815E+10 | 0.47 | 1163.15 | 0.94 | |
Maximum of Months | 0.158700E+10 | 0.48 | 1163.15 | 0.95 |
Report: ZoneTemperatureOscillationReportMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.81 | 0.78 |
February | 0.17 | 1.50 |
March | 0.06 | 1.50 |
April | 0.08 | 1.50 |
May | 0.42 | 1.50 |
June | 0.00 | 0.00 |
July | 0.08 | 0.00 |
August | 0.08 | 0.00 |
September | 0.00 | 0.00 |
October | 0.61 | 1.50 |
November | 0.22 | 0.37 |
December | 0.08 | 1.50 |
Annual Sum or Average | 2.61 | 1.08 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.81 | 1.50 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 1.18 | 4.92 |
February | 0.83 | 5.10 |
March | 0.76 | 5.04 |
April | 1.66 | 5.20 |
May | 1.47 | 4.82 |
June | 3.09 | 4.83 |
July | 4.03 | 4.63 |
August | 3.74 | 3.33 |
September | 1.56 | 5.30 |
October | 0.83 | 4.05 |
November | 2.04 | 5.45 |
December | 2.51 | 5.18 |
Annual Sum or Average | 23.72 | 4.70 |
Minimum of Months | 0.76 | 3.33 |
Maximum of Months | 4.03 | 5.45 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.08 | 0.00 |
February | 0.14 | 0.75 |
March | 0.67 | 0.37 |
April | 1.61 | 0.75 |
May | 1.75 | 0.75 |
June | 0.93 | 0.75 |
July | 1.37 | 0.75 |
August | 1.43 | 0.75 |
September | 0.21 | 0.75 |
October | 1.67 | 0.67 |
November | 0.36 | 0.40 |
December | 0.08 | 0.00 |
Annual Sum or Average | 10.30 | 0.69 |
Minimum of Months | 0.08 | 0.00 |
Maximum of Months | 1.75 | 0.75 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.06 | 0.75 |
March | 0.25 | 0.75 |
April | 1.69 | 0.68 |
May | 1.75 | 0.75 |
June | 0.85 | 0.75 |
July | 1.37 | 0.75 |
August | 1.43 | 0.75 |
September | 0.21 | 0.75 |
October | 1.36 | 0.66 |
November | 0.53 | 0.28 |
December | 0.17 | 0.00 |
Annual Sum or Average | 9.66 | 0.69 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 1.75 | 0.75 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.06 | 0.75 |
March | 0.08 | 0.75 |
April | 0.94 | 0.75 |
May | 1.47 | 0.75 |
June | 0.88 | 0.75 |
July | 1.14 | 0.75 |
August | 1.43 | 0.75 |
September | 0.29 | 0.75 |
October | 1.22 | 0.65 |
November | 0.06 | 0.75 |
December | 0.04 | 0.00 |
Annual Sum or Average | 7.62 | 0.73 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 1.47 | 0.75 |
Report: ZoneTemperatureOscillationReportMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.35 | 0.00 |
February | 0.16 | 0.00 |
March | 0.00 | 0.00 |
April | 0.25 | 1.10 |
May | 0.17 | 3.30 |
June | 0.12 | 3.30 |
July | 0.17 | 3.30 |
August | 0.36 | 2.03 |
September | 0.12 | 3.30 |
October | 0.28 | 3.30 |
November | 0.00 | 0.00 |
December | 0.14 | 0.00 |
Annual Sum or Average | 2.13 | 1.81 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.36 | 3.30 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.35 | 0.00 |
February | 0.16 | 0.00 |
March | 0.00 | 0.00 |
April | 0.08 | 1.65 |
May | 0.17 | 1.65 |
June | 0.12 | 1.65 |
July | 0.17 | 1.65 |
August | 0.31 | 0.90 |
September | 0.12 | 1.65 |
October | 0.22 | 1.65 |
November | 0.00 | 0.00 |
December | 0.14 | 0.00 |
Annual Sum or Average | 1.85 | 0.94 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.35 | 1.65 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.35 | 0.00 |
February | 0.16 | 0.00 |
March | 0.00 | 0.00 |
April | 0.08 | 1.65 |
May | 0.17 | 1.65 |
June | 0.12 | 1.65 |
July | 0.17 | 1.65 |
August | 0.31 | 0.90 |
September | 0.12 | 1.65 |
October | 0.17 | 1.65 |
November | 0.00 | 0.00 |
December | 0.14 | 0.00 |
Annual Sum or Average | 1.79 | 0.92 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.35 | 1.65 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.59 | 0.00 |
February | 0.41 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.12 | 1.65 |
July | 0.17 | 1.65 |
August | 0.31 | 0.90 |
September | 0.12 | 1.65 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.19 | 0.00 |
Annual Sum or Average | 1.92 | 0.50 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.59 | 1.65 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 2.09 | 0.00 |
February | 1.42 | 0.00 |
March | 0.12 | 0.00 |
April | 0.08 | 0.00 |
May | 0.00 | 0.00 |
June | 0.12 | 1.65 |
July | 0.11 | 1.65 |
August | 0.22 | 1.24 |
September | 0.12 | 1.65 |
October | 0.14 | 0.00 |
November | 0.29 | 0.00 |
December | 1.78 | 0.00 |
Annual Sum or Average | 6.51 | 0.13 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 2.09 | 1.65 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_1:1
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.412041E+10 | 0.135338E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.372803E+10 | 0.882380E+10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.412748E+10 | 0.296980E+10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.429468E+10 | 0.589741E+09 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.471084E+10 | 14169374.91 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.502965E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.666567E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.760296E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.500311E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.416786E+10 | 56080093.71 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.400037E+10 | 0.527197E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.413611E+10 | 0.106127E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.575872E+11 | 0.418721E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.372803E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.760296E+10 | 0.135338E+11 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_2:2
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.176980E+10 | 0.420365E+10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.162790E+10 | 0.248460E+10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.189114E+10 | 0.461657E+09 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.215338E+10 | 37327010.03 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.257822E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.289221E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.375155E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.423072E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.284963E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.218495E+10 | 36280.82 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.185424E+10 | 0.144008E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.176233E+10 | 0.313026E+10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.295461E+11 | 0.117576E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.162790E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.423072E+10 | 0.420365E+10 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_3:3
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.188475E+10 | 0.562657E+10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.170659E+10 | 0.344669E+10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.192242E+10 | 0.932059E+09 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.197609E+10 | 0.137597E+09 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.219446E+10 | 491701.06 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.235460E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.302310E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.350019E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.232095E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.191198E+10 | 7699017.75 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.183997E+10 | 0.218046E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.187537E+10 | 0.441347E+10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.265105E+11 | 0.167450E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.170659E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.350019E+10 | 0.562657E+10 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_4:4
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.189032E+10 | 0.603896E+10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.171163E+10 | 0.372573E+10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.192798E+10 | 0.116347E+10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.197686E+10 | 0.206684E+09 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.219282E+10 | 953446.05 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.235267E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.302220E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.350191E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.232073E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.191593E+10 | 26622108.55 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.184365E+10 | 0.244779E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.188092E+10 | 0.478556E+10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.265376E+11 | 0.183958E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.171163E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.350191E+10 | 0.603896E+10 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_5:5
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.187611E+10 | 0.658168E+10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.169877E+10 | 0.411305E+10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.191345E+10 | 0.150582E+10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.194016E+10 | 0.334244E+09 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.213280E+10 | 3271001.48 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.226512E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.285246E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.328038E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.223693E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.189669E+10 | 84373178.46 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.182660E+10 | 0.280094E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.186678E+10 | 0.528166E+10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.257862E+11 | 0.207050E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.169877E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.328038E+10 | 0.658168E+10 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_6:6
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.292533E+10 | 0.142839E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.264935E+10 | 0.925188E+10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.298841E+10 | 0.437709E+10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.304681E+10 | 0.133171E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.335270E+10 | 50087279.19 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.362718E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.475076E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.561023E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.358028E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.295644E+10 | 0.718106E+09 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.284477E+10 | 0.697871E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.290956E+10 | 0.119354E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.412418E+11 | 0.489269E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.264935E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.561023E+10 | 0.142839E+11 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_7:7
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.157970E+10 | 0.763254E+10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.143067E+10 | 0.496999E+10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.161377E+10 | 0.244067E+10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.162676E+10 | 0.787758E+09 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.177316E+10 | 40307937.33 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.189289E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.241039E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.281641E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.186884E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.159345E+10 | 0.455512E+09 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.153532E+10 | 0.377078E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.157119E+10 | 0.638138E+10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.217126E+11 | 0.264789E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.143067E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.281641E+10 | 0.763254E+10 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_8:8
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.156804E+10 | 0.777704E+10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.142011E+10 | 0.510025E+10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.160186E+10 | 0.260107E+10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.161207E+10 | 0.882529E+09 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.175313E+10 | 59765392.55 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.187123E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.238237E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.278588E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.184948E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.158102E+10 | 0.527027E+09 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.152365E+10 | 0.389392E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.155959E+10 | 0.651550E+10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.215084E+11 | 0.273571E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.142011E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.278588E+10 | 0.777704E+10 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_9:9
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.155485E+10 | 0.827993E+10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.140817E+10 | 0.554068E+10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.158838E+10 | 0.307003E+10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.159216E+10 | 0.115321E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.172282E+10 | 0.130200E+09 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.183528E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.233360E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.273471E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.182076E+10 | 1035700.06 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.156605E+10 | 0.710745E+09 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.151021E+10 | 0.425557E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.154647E+10 | 0.697609E+10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.212134E+11 | 0.301175E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.140817E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.273471E+10 | 0.827993E+10 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_10:10
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.155394E+10 | 0.103281E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.140815E+10 | 0.729578E+10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.158700E+10 | 0.477521E+10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.157872E+10 | 0.218378E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.169376E+10 | 0.531617E+09 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.178947E+10 | 17976987.27 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.226268E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.267774E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.179631E+10 | 23953227.11 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.156160E+10 | 0.139156E+10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.150812E+10 | 0.549833E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.154512E+10 | 0.869752E+10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.209626E+11 | 0.407438E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.140815E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.267774E+10 | 0.103281E+11 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_1:1
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.412041E+10 | 0.00 | 0.108270E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.372803E+10 | 1276.25 | 0.705904E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.412748E+10 | 16880.22 | 0.237584E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.399656E+10 | 0.100887E+10 | 0.471793E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.411915E+10 | 0.205452E+10 | 11335499.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.399656E+10 | 0.356876E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.412733E+10 | 0.886281E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.411915E+10 | 0.121517E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.400473E+10 | 0.352960E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.411915E+10 | 0.167431E+09 | 44864074.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.398051E+10 | 67617968.94 | 0.421757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.413611E+10 | 0.00 | 0.849017E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.485752E+11 | 0.314113E+11 | 0.334977E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.372803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.413611E+10 | 0.121517E+11 | 0.108270E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_2:2
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.176976E+10 | 133719.19 | 0.336292E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.162672E+10 | 3757515.74 | 0.198768E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.188772E+10 | 11719579.71 | 0.369326E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.194895E+10 | 0.721261E+09 | 29861608.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.218964E+10 | 0.139597E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.219202E+10 | 0.252838E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.219971E+10 | 0.560446E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.217575E+10 | 0.740210E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.220906E+10 | 0.234419E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.214677E+10 | 0.132439E+09 | 29024.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.183899E+10 | 52277408.47 | 0.115206E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.176232E+10 | 24189.29 | 0.250421E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.239474E+11 | 0.201967E+11 | 0.940609E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.162672E+10 | 24189.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.220906E+10 | 0.740210E+10 | 0.336292E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_3:3
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.188475E+10 | 0.00 | 0.450126E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.170659E+10 | 912.71 | 0.275735E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.192226E+10 | 542841.83 | 0.745648E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.182849E+10 | 0.502045E+09 | 0.110077E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.190351E+10 | 0.101154E+10 | 393360.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.185662E+10 | 0.172145E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.187537E+10 | 0.400833E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.192226E+10 | 0.550282E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.182849E+10 | 0.174597E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.188475E+10 | 93634710.60 | 6159214.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.182849E+10 | 39229775.66 | 0.174437E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.187537E+10 | 0.00 | 0.353078E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.223170E+11 | 0.146256E+11 | 0.133960E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.170659E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.192226E+10 | 0.550282E+10 | 0.450126E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_4:4
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.189032E+10 | 0.00 | 0.483117E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.171163E+10 | 655.93 | 0.298058E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.192794E+10 | 131915.35 | 0.930778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.183389E+10 | 0.484992E+09 | 0.165347E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.190913E+10 | 0.984989E+09 | 762756.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.186211E+10 | 0.169450E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.188092E+10 | 0.398362E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.192794E+10 | 0.548626E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.183389E+10 | 0.172482E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.189032E+10 | 88039020.92 | 21297686.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.183389E+10 | 33177172.96 | 0.195823E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.188092E+10 | 0.00 | 0.382845E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.223829E+11 | 0.144805E+11 | 0.147166E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.171163E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.192794E+10 | 0.548626E+10 | 0.483117E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_5:5
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.187611E+10 | 0.00 | 0.526535E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.169877E+10 | 349.73 | 0.329044E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.191345E+10 | 8308.01 | 0.120466E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.182011E+10 | 0.453351E+09 | 0.267396E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.189478E+10 | 0.921504E+09 | 2616801.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.184811E+10 | 0.160720E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.186678E+10 | 0.383833E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.191345E+10 | 0.531599E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.182011E+10 | 0.164768E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.187611E+10 | 79044908.44 | 67498542.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.182011E+10 | 24464611.99 | 0.224075E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.186678E+10 | 0.00 | 0.422533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.222146E+11 | 0.138876E+11 | 0.165640E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.169877E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.191345E+10 | 0.531599E+10 | 0.526535E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_6:6
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.292533E+10 | 0.00 | 0.114271E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.264935E+10 | 159.26 | 0.740150E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.298841E+10 | 8552.02 | 0.350167E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.283859E+10 | 0.696182E+09 | 0.106537E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.295687E+10 | 0.136095E+10 | 40069823.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.288590E+10 | 0.253881E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.290956E+10 | 0.637791E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.298841E+10 | 0.907494E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.283859E+10 | 0.260933E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.292533E+10 | 0.106505E+09 | 0.574485E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.283859E+10 | 20528619.71 | 0.558297E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.290956E+10 | 0.00 | 0.954834E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.346545E+11 | 0.227852E+11 | 0.391415E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.264935E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.298841E+10 | 0.907494E+10 | 0.114271E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_7:7
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.157970E+10 | 0.00 | 0.610603E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.143067E+10 | 40.81 | 0.397599E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.161376E+10 | 3636.80 | 0.195254E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.153286E+10 | 0.350408E+09 | 0.630206E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.159673E+10 | 0.677460E+09 | 32246349.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.155841E+10 | 0.127969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.157119E+10 | 0.324797E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.161376E+10 | 0.465217E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.153286E+10 | 0.132089E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.157970E+10 | 52570148.18 | 0.364410E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.153286E+10 | 9107260.55 | 0.301662E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.157119E+10 | 0.00 | 0.510510E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.187137E+11 | 0.115903E+11 | 0.211831E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.143067E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.161376E+10 | 0.465217E+10 | 0.610603E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_8:8
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.156804E+10 | 0.00 | 0.622163E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.142011E+10 | 73.81 | 0.408020E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.160185E+10 | 3167.89 | 0.208085E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.152155E+10 | 0.337089E+09 | 0.706023E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.158495E+10 | 0.644805E+09 | 47812314.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.154691E+10 | 0.123959E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.155959E+10 | 0.318208E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.160185E+10 | 0.457725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.152155E+10 | 0.128853E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.156804E+10 | 49559201.46 | 0.421622E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.152155E+10 | 7791249.45 | 0.311514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.155959E+10 | 0.00 | 0.521240E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.185756E+11 | 0.113267E+11 | 0.218857E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.142011E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.160185E+10 | 0.457725E+10 | 0.622163E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_9:9
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.155485E+10 | 0.00 | 0.662395E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.140817E+10 | 0.00 | 0.443254E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.158838E+10 | 2252.86 | 0.245602E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.150875E+10 | 0.309051E+09 | 0.922572E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.157162E+10 | 0.577457E+09 | 0.104160E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.153390E+10 | 0.114873E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.154647E+10 | 0.303756E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.158838E+10 | 0.442376E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.150875E+10 | 0.122419E+10 | 828560.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.155485E+10 | 42605480.03 | 0.568596E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.150875E+10 | 5388581.73 | 0.340446E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.154647E+10 | 0.00 | 0.558087E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.184193E+11 | 0.107688E+11 | 0.240940E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.140817E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.158838E+10 | 0.442376E+10 | 0.662395E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_10:10
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.155394E+10 | 0.00 | 0.826247E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.140815E+10 | 0.00 | 0.583663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.158700E+10 | 0.00 | 0.382016E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.150744E+10 | 0.261922E+09 | 0.174703E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.157025E+10 | 0.467780E+09 | 0.425293E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.153256E+10 | 0.973102E+09 | 14381589.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.154512E+10 | 0.275714E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.158700E+10 | 0.420331E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.150744E+10 | 0.112982E+10 | 19162581.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.155350E+10 | 30529465.89 | 0.111325E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.150744E+10 | 2492880.67 | 0.439866E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.154512E+10 | 0.00 | 0.695801E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.184049E+11 | 0.982610E+10 | 0.325950E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.140815E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.158700E+10 | 0.420331E+10 | 0.826247E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_1:1
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.412041E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135338E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.372803E+10 | 0.00 | 0.00 | 0.00 | 392.45 | 0.00 | 0.882380E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.412748E+10 | 0.00 | 0.00 | 0.00 | 5175.82 | 0.00 | 0.296980E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.399656E+10 | 0.00 | 0.00 | 0.00 | 0.298117E+09 | 0.00 | 0.589741E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.411915E+10 | 0.00 | 0.00 | 0.00 | 0.591691E+09 | 0.00 | 14169374.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.399656E+10 | 0.00 | 0.00 | 0.00 | 0.103309E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.412733E+10 | 0.00 | 0.00 | 0.00 | 0.253835E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.411915E+10 | 0.00 | 0.00 | 0.00 | 0.348381E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.400473E+10 | 0.00 | 0.00 | 0.00 | 0.998380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.411915E+10 | 0.00 | 0.00 | 0.00 | 48702283.34 | 0.00 | 56080093.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.398051E+10 | 0.00 | 0.00 | 0.00 | 19854236.95 | 0.00 | 0.527197E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.413611E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106127E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.485752E+11 | 0.00 | 0.00 | 0.00 | 0.901200E+10 | 0.00 | 0.418721E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.372803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.413611E+10 | 0.00 | 0.00 | 0.00 | 0.348381E+10 | 0.00 | 0.135338E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_2:2
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.176976E+10 | 0.00 | 0.00 | 0.00 | 44226.62 | 0.00 | 0.420365E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.162672E+10 | 0.00 | 0.00 | 0.00 | 1184602.07 | 0.00 | 0.248460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.188772E+10 | 0.00 | 0.00 | 0.00 | 3424351.49 | 0.00 | 0.461657E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.194895E+10 | 0.00 | 0.00 | 0.00 | 0.204427E+09 | 0.00 | 37327010.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.218964E+10 | 0.00 | 0.00 | 0.00 | 0.388587E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.219202E+10 | 0.00 | 0.00 | 0.00 | 0.700185E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.219971E+10 | 0.00 | 0.00 | 0.00 | 0.155184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.217575E+10 | 0.00 | 0.00 | 0.00 | 0.205497E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.220906E+10 | 0.00 | 0.00 | 0.00 | 0.640575E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.214677E+10 | 0.00 | 0.00 | 0.00 | 38176989.16 | 0.00 | 36280.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.183899E+10 | 0.00 | 0.00 | 0.00 | 15247063.23 | 0.00 | 0.144008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.176232E+10 | 0.00 | 0.00 | 0.00 | 8005.24 | 0.00 | 0.313026E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.239474E+11 | 0.00 | 0.00 | 0.00 | 0.559867E+10 | 0.00 | 0.117576E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.162672E+10 | 0.00 | 0.00 | 0.00 | 8005.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.220906E+10 | 0.00 | 0.00 | 0.00 | 0.205497E+10 | 0.00 | 0.420365E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_3:3
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.188475E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.562657E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.170659E+10 | 0.00 | 0.00 | 0.00 | 280.64 | 0.00 | 0.344669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.192226E+10 | 0.00 | 0.00 | 0.00 | 165623.91 | 0.00 | 0.932059E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.182849E+10 | 0.00 | 0.00 | 0.00 | 0.147597E+09 | 0.00 | 0.137597E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.190351E+10 | 0.00 | 0.00 | 0.00 | 0.290955E+09 | 0.00 | 491701.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.185662E+10 | 0.00 | 0.00 | 0.00 | 0.497982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.187537E+10 | 0.00 | 0.00 | 0.00 | 0.114773E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.192226E+10 | 0.00 | 0.00 | 0.00 | 0.157793E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.182849E+10 | 0.00 | 0.00 | 0.00 | 0.492456E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.188475E+10 | 0.00 | 0.00 | 0.00 | 27226123.36 | 0.00 | 7699017.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.182849E+10 | 0.00 | 0.00 | 0.00 | 11477925.54 | 0.00 | 0.218046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.187537E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.441347E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.223170E+11 | 0.00 | 0.00 | 0.00 | 0.419351E+10 | 0.00 | 0.167450E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.170659E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.192226E+10 | 0.00 | 0.00 | 0.00 | 0.157793E+10 | 0.00 | 0.562657E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_4:4
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.189032E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.603896E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.171163E+10 | 0.00 | 0.00 | 0.00 | 201.75 | 0.00 | 0.372573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.192794E+10 | 0.00 | 0.00 | 0.00 | 40341.70 | 0.00 | 0.116347E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.183389E+10 | 0.00 | 0.00 | 0.00 | 0.142962E+09 | 0.00 | 0.206684E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.190913E+10 | 0.00 | 0.00 | 0.00 | 0.283693E+09 | 0.00 | 953446.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.186211E+10 | 0.00 | 0.00 | 0.00 | 0.490563E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.188092E+10 | 0.00 | 0.00 | 0.00 | 0.114129E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.192794E+10 | 0.00 | 0.00 | 0.00 | 0.157397E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.183389E+10 | 0.00 | 0.00 | 0.00 | 0.486838E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.189032E+10 | 0.00 | 0.00 | 0.00 | 25605452.83 | 0.00 | 26622108.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.183389E+10 | 0.00 | 0.00 | 0.00 | 9759037.28 | 0.00 | 0.244779E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.188092E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.478556E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.223829E+11 | 0.00 | 0.00 | 0.00 | 0.415471E+10 | 0.00 | 0.183958E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.171163E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.192794E+10 | 0.00 | 0.00 | 0.00 | 0.157397E+10 | 0.00 | 0.603896E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_5:5
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.187611E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.658168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.169877E+10 | 0.00 | 0.00 | 0.00 | 96.22 | 0.00 | 0.411305E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.191345E+10 | 0.00 | 0.00 | 0.00 | 2279.26 | 0.00 | 0.150582E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.182011E+10 | 0.00 | 0.00 | 0.00 | 0.120052E+09 | 0.00 | 0.334244E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.189478E+10 | 0.00 | 0.00 | 0.00 | 0.238023E+09 | 0.00 | 3271001.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.184811E+10 | 0.00 | 0.00 | 0.00 | 0.417009E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.186678E+10 | 0.00 | 0.00 | 0.00 | 0.985687E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.191345E+10 | 0.00 | 0.00 | 0.00 | 0.136694E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.182011E+10 | 0.00 | 0.00 | 0.00 | 0.416827E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.187611E+10 | 0.00 | 0.00 | 0.00 | 20584610.18 | 0.00 | 84373178.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.182011E+10 | 0.00 | 0.00 | 0.00 | 6488928.16 | 0.00 | 0.280094E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.186678E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.528166E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.222146E+11 | 0.00 | 0.00 | 0.00 | 0.357161E+10 | 0.00 | 0.207050E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.169877E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.191345E+10 | 0.00 | 0.00 | 0.00 | 0.136694E+10 | 0.00 | 0.658168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_6:6
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.292533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142839E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.264935E+10 | 0.00 | 0.00 | 0.00 | 48.99 | 0.00 | 0.925188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.298841E+10 | 0.00 | 0.00 | 0.00 | 2621.72 | 0.00 | 0.437709E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.283859E+10 | 0.00 | 0.00 | 0.00 | 0.208215E+09 | 0.00 | 0.133171E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.295687E+10 | 0.00 | 0.00 | 0.00 | 0.395836E+09 | 0.00 | 50087279.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.288590E+10 | 0.00 | 0.00 | 0.00 | 0.741283E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.290956E+10 | 0.00 | 0.00 | 0.00 | 0.184120E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.298841E+10 | 0.00 | 0.00 | 0.00 | 0.262182E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.283859E+10 | 0.00 | 0.00 | 0.00 | 0.741694E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.292533E+10 | 0.00 | 0.00 | 0.00 | 31115482.51 | 0.00 | 0.718106E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.283859E+10 | 0.00 | 0.00 | 0.00 | 6174111.34 | 0.00 | 0.697871E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.290956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119354E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.346545E+11 | 0.00 | 0.00 | 0.00 | 0.658735E+10 | 0.00 | 0.489269E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.264935E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.298841E+10 | 0.00 | 0.00 | 0.00 | 0.262182E+10 | 0.00 | 0.142839E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_7:7
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.157970E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.763254E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.143067E+10 | 0.00 | 0.00 | 0.00 | 11.23 | 0.00 | 0.496999E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.161376E+10 | 0.00 | 0.00 | 0.00 | 997.27 | 0.00 | 0.244067E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.153286E+10 | 0.00 | 0.00 | 0.00 | 93893753.38 | 0.00 | 0.787758E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.159673E+10 | 0.00 | 0.00 | 0.00 | 0.176431E+09 | 0.00 | 40307937.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.155841E+10 | 0.00 | 0.00 | 0.00 | 0.334482E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.157119E+10 | 0.00 | 0.00 | 0.00 | 0.839203E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.161376E+10 | 0.00 | 0.00 | 0.00 | 0.120265E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.153286E+10 | 0.00 | 0.00 | 0.00 | 0.335978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.157970E+10 | 0.00 | 0.00 | 0.00 | 13750192.45 | 0.00 | 0.455512E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.153286E+10 | 0.00 | 0.00 | 0.00 | 2454700.34 | 0.00 | 0.377078E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.157119E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.638138E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.187137E+11 | 0.00 | 0.00 | 0.00 | 0.299884E+10 | 0.00 | 0.264789E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.143067E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.161376E+10 | 0.00 | 0.00 | 0.00 | 0.120265E+10 | 0.00 | 0.763254E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_8:8
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.156804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.777704E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.142011E+10 | 0.00 | 0.00 | 0.00 | 20.31 | 0.00 | 0.510025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.160185E+10 | 0.00 | 0.00 | 0.00 | 868.61 | 0.00 | 0.260107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.152155E+10 | 0.00 | 0.00 | 0.00 | 90519229.87 | 0.00 | 0.882529E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.158495E+10 | 0.00 | 0.00 | 0.00 | 0.168177E+09 | 0.00 | 59765392.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.154691E+10 | 0.00 | 0.00 | 0.00 | 0.324317E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.155959E+10 | 0.00 | 0.00 | 0.00 | 0.822781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.160185E+10 | 0.00 | 0.00 | 0.00 | 0.118403E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.152155E+10 | 0.00 | 0.00 | 0.00 | 0.327927E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.156804E+10 | 0.00 | 0.00 | 0.00 | 12979362.62 | 0.00 | 0.527027E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.152155E+10 | 0.00 | 0.00 | 0.00 | 2104046.99 | 0.00 | 0.389392E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.155959E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.651550E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.185756E+11 | 0.00 | 0.00 | 0.00 | 0.293283E+10 | 0.00 | 0.273571E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.142011E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.160185E+10 | 0.00 | 0.00 | 0.00 | 0.118403E+10 | 0.00 | 0.777704E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_9:9
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.155485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.827993E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.140817E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.554068E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.158838E+10 | 0.00 | 0.00 | 0.00 | 617.71 | 0.00 | 0.307003E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.150875E+10 | 0.00 | 0.00 | 0.00 | 83406139.97 | 0.00 | 0.115321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.157162E+10 | 0.00 | 0.00 | 0.00 | 0.151205E+09 | 0.00 | 0.130200E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.153390E+10 | 0.00 | 0.00 | 0.00 | 0.301383E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.154647E+10 | 0.00 | 0.00 | 0.00 | 0.787126E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.158838E+10 | 0.00 | 0.00 | 0.00 | 0.114633E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.150875E+10 | 0.00 | 0.00 | 0.00 | 0.312005E+09 | 0.00 | 1035700.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.155485E+10 | 0.00 | 0.00 | 0.00 | 11198113.43 | 0.00 | 0.710745E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.150875E+10 | 0.00 | 0.00 | 0.00 | 1460783.88 | 0.00 | 0.425557E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.154647E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.697609E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.184193E+11 | 0.00 | 0.00 | 0.00 | 0.279411E+10 | 0.00 | 0.301175E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.140817E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.158838E+10 | 0.00 | 0.00 | 0.00 | 0.114633E+10 | 0.00 | 0.827993E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_10:10
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.155394E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103281E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.140815E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.729578E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.158700E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.477521E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.150744E+10 | 0.00 | 0.00 | 0.00 | 71286546.28 | 0.00 | 0.218378E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.157025E+10 | 0.00 | 0.00 | 0.00 | 0.123511E+09 | 0.00 | 0.531617E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.153256E+10 | 0.00 | 0.00 | 0.00 | 0.256914E+09 | 0.00 | 17976987.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.154512E+10 | 0.00 | 0.00 | 0.00 | 0.717554E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.158700E+10 | 0.00 | 0.00 | 0.00 | 0.109075E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.150744E+10 | 0.00 | 0.00 | 0.00 | 0.288873E+09 | 0.00 | 23953227.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.155350E+10 | 0.00 | 0.00 | 0.00 | 8099967.38 | 0.00 | 0.139156E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.150744E+10 | 0.00 | 0.00 | 0.00 | 680058.69 | 0.00 | 0.549833E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.154512E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.869752E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.184049E+11 | 0.00 | 0.00 | 0.00 | 0.255767E+10 | 0.00 | 0.407438E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.140815E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.158700E+10 | 0.00 | 0.00 | 0.00 | 0.109075E+10 | 0.00 | 0.103281E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.728784E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.659638E+10 | 0.00 | 0.00 | 0.53 |
February | 0.708870E+10 | 0.00 | 0.00 | 230209.19 | 0.00 | 0.426751E+10 | 0.214891E+09 | 0.00 | 0.54 |
March | 0.877906E+10 | 0.00 | 0.00 | 343737.01 | 0.00 | 0.155287E+10 | 0.361853E+09 | 0.00 | 0.54 |
April | 0.682673E+10 | 35230825.13 | 0.00 | 4427076.19 | 0.00 | 0.151343E+09 | 0.266167E+10 | 0.00 | 0.66 |
May | 0.335283E+10 | 28239656.47 | 0.00 | 13466257.90 | 0.00 | 0.00 | 0.726509E+10 | 0.00 | 0.90 |
June | 0.881734E+09 | 37938831.56 | 0.00 | 22128917.85 | 0.00 | 0.00 | 0.101720E+11 | 0.00 | 1.24 |
July | 0.136377E+09 | 0.454020E+09 | 0.00 | 28914328.31 | 0.00 | 0.00 | 0.976267E+10 | 0.00 | 1.42 |
August | 0.151159E+09 | 0.957750E+09 | 0.00 | 28153180.87 | 0.00 | 0.00 | 0.795211E+10 | 0.00 | 1.34 |
September | 0.112301E+10 | 62831571.70 | 0.00 | 21042933.18 | 0.00 | 0.00 | 0.103801E+11 | 0.00 | 1.19 |
October | 0.597121E+10 | 0.00 | 0.00 | 6291806.06 | 0.00 | 0.00 | 0.524282E+10 | 0.00 | 0.70 |
November | 0.738252E+10 | 0.00 | 0.00 | 1162559.56 | 0.00 | 0.304094E+10 | 0.956062E+09 | 0.00 | 0.56 |
December | 0.783119E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.531509E+10 | 0.00 | 0.00 | 0.53 |
Annual Sum or Average | 0.568124E+11 | 0.157601E+10 | 0.00 | 0.126161E+09 | 0.00 | 0.209241E+11 | 0.549694E+11 | 0.00 | 0.85 |
Minimum of Months | 0.136377E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.53 |
Maximum of Months | 0.877906E+10 | 0.957750E+09 | 0.00 | 28914328.31 | 0.00 | 0.659638E+10 | 0.103801E+11 | 0.00 | 1.42 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.219639E+10 | 0.00 | 0.00 | 20715.43 | 0.00 | 0.280626E+10 | 15063550.77 | 0.00 | 0.39 |
February | 0.260324E+10 | 0.00 | 0.00 | 420731.83 | 0.00 | 0.139510E+10 | 0.346829E+09 | 0.00 | 0.42 |
March | 0.350449E+10 | 0.00 | 0.00 | 969592.43 | 0.00 | 0.132211E+09 | 0.874840E+09 | 0.00 | 0.46 |
April | 0.220805E+10 | 17724075.37 | 0.00 | 3644616.35 | 0.00 | 2948500.97 | 0.255595E+10 | 0.00 | 0.65 |
May | 0.826623E+09 | 15620495.71 | 0.00 | 8604265.17 | 0.00 | 0.00 | 0.523000E+10 | 0.00 | 1.01 |
June | 0.147780E+09 | 19302256.66 | 0.00 | 11647361.66 | 0.00 | 0.00 | 0.611873E+10 | 0.00 | 1.37 |
July | 9979065.18 | 0.233787E+09 | 0.00 | 12718929.84 | 0.00 | 0.00 | 0.517786E+10 | 0.00 | 1.48 |
August | 8624096.73 | 0.491999E+09 | 0.00 | 10762092.43 | 0.00 | 0.00 | 0.419172E+10 | 0.00 | 1.35 |
September | 0.314967E+09 | 34372755.14 | 0.00 | 11262150.92 | 0.00 | 0.00 | 0.609464E+10 | 0.00 | 1.31 |
October | 0.186452E+10 | 0.00 | 0.00 | 5300324.16 | 0.00 | 0.00 | 0.419733E+10 | 0.00 | 0.75 |
November | 0.287299E+10 | 0.00 | 0.00 | 1181364.62 | 0.00 | 0.929043E+09 | 0.912559E+09 | 0.00 | 0.48 |
December | 0.264821E+10 | 0.00 | 0.00 | 63425.05 | 0.00 | 0.204744E+10 | 48154799.39 | 0.00 | 0.39 |
Annual Sum or Average | 0.192059E+11 | 0.812806E+09 | 0.00 | 66595569.89 | 0.00 | 0.731301E+10 | 0.357637E+11 | 0.00 | 0.84 |
Minimum of Months | 8624096.73 | 0.00 | 0.00 | 20715.43 | 0.00 | 0.00 | 15063550.77 | 0.00 | 0.39 |
Maximum of Months | 0.350449E+10 | 0.491999E+09 | 0.00 | 12718929.84 | 0.00 | 0.280626E+10 | 0.611873E+10 | 0.00 | 1.48 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.207715E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.322578E+10 | 0.00 | 0.00 | 0.41 |
February | 0.232233E+10 | 0.00 | 0.00 | 75230.71 | 0.00 | 0.197020E+10 | 92577337.54 | 0.00 | 0.43 |
March | 0.362221E+10 | 0.00 | 0.00 | 110028.32 | 0.00 | 0.437484E+09 | 0.159412E+09 | 0.00 | 0.44 |
April | 0.271153E+10 | 17911526.61 | 0.00 | 1163985.90 | 2284.56 | 27052943.74 | 0.953851E+09 | 0.00 | 0.52 |
May | 0.144570E+10 | 15384613.76 | 0.00 | 3858507.67 | 0.00 | 0.00 | 0.276455E+10 | 0.00 | 0.75 |
June | 0.441089E+09 | 19860483.95 | 0.00 | 6429005.85 | 25324.85 | 0.00 | 0.403470E+10 | 0.00 | 1.05 |
July | 0.167384E+09 | 0.202997E+09 | 0.00 | 6932043.77 | 3211690.38 | 0.00 | 0.350496E+10 | 0.00 | 1.14 |
August | 0.163845E+09 | 0.441993E+09 | 0.00 | 6019655.64 | 6354803.53 | 0.00 | 0.303252E+10 | 0.00 | 1.07 |
September | 0.654388E+09 | 33704641.18 | 0.00 | 5841003.55 | 0.00 | 0.00 | 0.368702E+10 | 0.00 | 0.97 |
October | 0.248388E+10 | 0.00 | 0.00 | 2056404.21 | 0.00 | 0.00 | 0.190032E+10 | 0.00 | 0.57 |
November | 0.268661E+10 | 0.00 | 0.00 | 253628.24 | 0.00 | 0.143296E+10 | 0.224520E+09 | 0.00 | 0.44 |
December | 0.231584E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.264778E+10 | 0.00 | 0.00 | 0.41 |
Annual Sum or Average | 0.210920E+11 | 0.731851E+09 | 0.00 | 32739493.86 | 9594103.32 | 0.974126E+10 | 0.203544E+11 | 0.00 | 0.68 |
Minimum of Months | 0.163845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.362221E+10 | 0.441993E+09 | 0.00 | 6932043.77 | 6354803.53 | 0.322578E+10 | 0.403470E+10 | 0.00 | 1.14 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.191208E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.338896E+10 | 0.00 | 0.00 | 0.41 |
February | 0.216594E+10 | 0.00 | 0.00 | 56241.75 | 0.00 | 0.212949E+10 | 66256570.99 | 0.00 | 0.42 |
March | 0.338649E+10 | 0.00 | 0.00 | 77307.83 | 0.00 | 0.662245E+09 | 0.126102E+09 | 0.00 | 0.43 |
April | 0.270790E+10 | 17881312.86 | 0.00 | 1009101.59 | 2164.57 | 69069076.65 | 0.830374E+09 | 0.00 | 0.51 |
May | 0.151212E+10 | 15265966.36 | 0.00 | 3601285.96 | 0.00 | 0.00 | 0.259539E+10 | 0.00 | 0.74 |
June | 0.462650E+09 | 19856648.62 | 0.00 | 6263043.15 | 25177.22 | 0.00 | 0.397199E+10 | 0.00 | 1.04 |
July | 0.174574E+09 | 0.202905E+09 | 0.00 | 6839150.94 | 3212451.48 | 0.00 | 0.348790E+10 | 0.00 | 1.14 |
August | 0.166492E+09 | 0.441893E+09 | 0.00 | 5977565.60 | 6354797.64 | 0.00 | 0.302990E+10 | 0.00 | 1.07 |
September | 0.699752E+09 | 33293968.50 | 0.00 | 5658986.20 | 0.00 | 0.00 | 0.358741E+10 | 0.00 | 0.96 |
October | 0.254207E+10 | 0.00 | 0.00 | 1857765.14 | 0.00 | 0.00 | 0.173614E+10 | 0.00 | 0.56 |
November | 0.257007E+10 | 0.00 | 0.00 | 202137.73 | 0.00 | 0.154478E+10 | 0.191377E+09 | 0.00 | 0.44 |
December | 0.217043E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.278922E+10 | 0.00 | 0.00 | 0.41 |
Annual Sum or Average | 0.204706E+11 | 0.731095E+09 | 0.00 | 31542585.89 | 9594590.91 | 0.105838E+11 | 0.196228E+11 | 0.00 | 0.68 |
Minimum of Months | 0.166492E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.338649E+10 | 0.441893E+09 | 0.00 | 6839150.94 | 6354797.64 | 0.338896E+10 | 0.397199E+10 | 0.00 | 1.14 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.167832E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.362081E+10 | 0.00 | 0.00 | 0.41 |
February | 0.189459E+10 | 0.00 | 0.00 | 38470.80 | 0.00 | 0.238762E+10 | 53014896.20 | 0.00 | 0.42 |
March | 0.315740E+10 | 0.00 | 0.00 | 51370.80 | 0.00 | 0.887911E+09 | 74179704.56 | 0.00 | 0.43 |
April | 0.269739E+10 | 17819279.21 | 0.00 | 781027.96 | 2469.48 | 0.152345E+09 | 0.629157E+09 | 0.00 | 0.50 |
May | 0.171152E+10 | 14753497.28 | 0.00 | 3017240.77 | 0.00 | 0.00 | 0.216665E+10 | 0.00 | 0.71 |
June | 0.572248E+09 | 19756795.89 | 0.00 | 5674305.65 | 26060.89 | 0.00 | 0.367282E+10 | 0.00 | 1.01 |
July | 0.199431E+09 | 0.200793E+09 | 0.00 | 6367579.52 | 3248208.33 | 0.00 | 0.335044E+10 | 0.00 | 1.12 |
August | 0.177875E+09 | 0.438108E+09 | 0.00 | 5554492.57 | 6408058.16 | 0.00 | 0.292682E+10 | 0.00 | 1.05 |
September | 0.815879E+09 | 31837823.15 | 0.00 | 5094976.12 | 0.00 | 0.00 | 0.327937E+10 | 0.00 | 0.93 |
October | 0.262990E+10 | 0.00 | 0.00 | 1563895.21 | 0.00 | 10649842.31 | 0.145203E+10 | 0.00 | 0.54 |
November | 0.242795E+10 | 0.00 | 0.00 | 130484.37 | 0.00 | 0.171444E+10 | 0.116462E+09 | 0.00 | 0.43 |
December | 0.193739E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.301863E+10 | 0.00 | 0.00 | 0.41 |
Annual Sum or Average | 0.198999E+11 | 0.723068E+09 | 0.00 | 28273843.77 | 9684796.86 | 0.117924E+11 | 0.177209E+11 | 0.00 | 0.67 |
Minimum of Months | 0.177875E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.315740E+10 | 0.438108E+09 | 0.00 | 6367579.52 | 6408058.16 | 0.362081E+10 | 0.367282E+10 | 0.00 | 1.12 |
Report: MechanicalVentilationLoadsMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.204773E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.769915E+10 | 0.00 | 0.00 | 0.38 |
February | 0.247606E+10 | 0.00 | 0.00 | 9443.48 | 0.00 | 0.538183E+10 | 23219659.49 | 0.00 | 0.38 |
March | 0.476355E+10 | 0.00 | 0.00 | 35714.39 | 0.00 | 0.250089E+10 | 71043266.56 | 0.00 | 0.39 |
April | 0.466070E+10 | 28274398.75 | 0.00 | 960018.40 | 0.00 | 0.580693E+09 | 0.662506E+09 | 0.00 | 0.44 |
May | 0.368305E+10 | 19491798.06 | 0.00 | 3616085.48 | 0.00 | 9637099.33 | 0.248116E+10 | 0.00 | 0.58 |
June | 0.115829E+10 | 30979464.30 | 0.00 | 8310845.43 | 48996.67 | 0.00 | 0.542812E+10 | 0.00 | 0.83 |
July | 0.265081E+09 | 0.367185E+09 | 0.00 | 9733346.93 | 3258643.99 | 0.00 | 0.527606E+10 | 0.00 | 0.94 |
August | 0.233908E+09 | 0.824620E+09 | 0.00 | 8194776.70 | 3905805.38 | 0.00 | 0.450534E+10 | 0.00 | 0.88 |
September | 0.183207E+10 | 37318971.75 | 0.00 | 7335737.34 | 0.00 | 0.00 | 0.456527E+10 | 0.00 | 0.76 |
October | 0.466735E+10 | 0.00 | 0.00 | 1847804.16 | 0.00 | 0.244616E+09 | 0.178802E+10 | 0.00 | 0.46 |
November | 0.369515E+10 | 0.00 | 0.00 | 124741.26 | 0.00 | 0.391374E+10 | 0.123214E+09 | 0.00 | 0.39 |
December | 0.268455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.644682E+10 | 0.00 | 0.00 | 0.38 |
Annual Sum or Average | 0.321675E+11 | 0.130787E+10 | 0.00 | 40168513.57 | 7213446.03 | 0.267774E+11 | 0.249240E+11 | 0.00 | 0.57 |
Minimum of Months | 0.233908E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.476355E+10 | 0.824620E+09 | 0.00 | 9733346.93 | 3905805.38 | 0.769915E+10 | 0.542812E+10 | 0.00 | 0.94 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.848828E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.401659E+10 | 0.00 | 0.00 | 0.38 |
February | 0.108391E+10 | 0.00 | 0.00 | 2068.53 | 0.00 | 0.283801E+10 | 7336001.47 | 0.00 | 0.38 |
March | 0.212174E+10 | 0.00 | 0.00 | 12649.75 | 0.00 | 0.149620E+10 | 31517594.98 | 0.00 | 0.39 |
April | 0.219398E+10 | 14264750.98 | 0.00 | 435421.98 | 0.00 | 0.422088E+09 | 0.301551E+09 | 0.00 | 0.43 |
May | 0.189943E+10 | 9599204.38 | 0.00 | 1664072.09 | 0.00 | 11803495.30 | 0.112031E+10 | 0.00 | 0.59 |
June | 0.657711E+09 | 15735646.66 | 0.00 | 3975019.69 | 18995.41 | 0.00 | 0.261161E+10 | 0.00 | 0.83 |
July | 0.166143E+09 | 0.183532E+09 | 0.00 | 4744758.57 | 1622985.81 | 0.00 | 0.263554E+10 | 0.00 | 0.95 |
August | 0.127288E+09 | 0.411765E+09 | 0.00 | 4015770.49 | 1934767.60 | 0.00 | 0.227910E+10 | 0.00 | 0.90 |
September | 0.945858E+09 | 18446428.62 | 0.00 | 3544344.00 | 0.00 | 0.00 | 0.224380E+10 | 0.00 | 0.77 |
October | 0.219537E+10 | 0.00 | 0.00 | 852303.28 | 0.00 | 0.275432E+09 | 0.840691E+09 | 0.00 | 0.45 |
November | 0.166785E+10 | 0.00 | 0.00 | 55711.54 | 0.00 | 0.212745E+10 | 57520656.34 | 0.00 | 0.39 |
December | 0.123316E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.332407E+10 | 0.00 | 0.00 | 0.38 |
Annual Sum or Average | 0.151413E+11 | 0.653343E+09 | 0.00 | 19302119.92 | 3576748.81 | 0.145116E+11 | 0.121290E+11 | 0.00 | 0.57 |
Minimum of Months | 0.127288E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.219537E+10 | 0.411765E+09 | 0.00 | 4744758.57 | 1934767.60 | 0.401659E+10 | 0.263554E+10 | 0.00 | 0.95 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.753998E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.411137E+10 | 0.00 | 0.00 | 0.38 |
February | 0.102018E+10 | 0.00 | 0.00 | 1199.01 | 0.00 | 0.290087E+10 | 5184450.33 | 0.00 | 0.38 |
March | 0.203181E+10 | 0.00 | 0.00 | 10455.74 | 0.00 | 0.158070E+10 | 28524403.61 | 0.00 | 0.39 |
April | 0.210704E+10 | 14213203.89 | 0.00 | 401072.77 | 0.00 | 0.501738E+09 | 0.280169E+09 | 0.00 | 0.43 |
May | 0.192562E+10 | 9311595.56 | 0.00 | 1513872.21 | 0.00 | 14521745.84 | 0.101498E+10 | 0.00 | 0.57 |
June | 0.709921E+09 | 15674663.79 | 0.00 | 3741220.62 | 19613.68 | 0.00 | 0.246344E+10 | 0.00 | 0.81 |
July | 0.192208E+09 | 0.182358E+09 | 0.00 | 4559589.14 | 1635092.38 | 0.00 | 0.254995E+10 | 0.00 | 0.94 |
August | 0.140324E+09 | 0.409906E+09 | 0.00 | 3875918.27 | 1942560.96 | 0.00 | 0.222049E+10 | 0.00 | 0.89 |
September | 0.964700E+09 | 17989531.35 | 0.00 | 3371354.93 | 0.00 | 0.00 | 0.214817E+10 | 0.00 | 0.75 |
October | 0.212358E+10 | 0.00 | 0.00 | 782697.87 | 0.00 | 0.352134E+09 | 0.783839E+09 | 0.00 | 0.45 |
November | 0.161022E+10 | 0.00 | 0.00 | 50780.39 | 0.00 | 0.218248E+10 | 54111005.24 | 0.00 | 0.39 |
December | 0.116975E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.338748E+10 | 0.00 | 0.00 | 0.38 |
Annual Sum or Average | 0.147494E+11 | 0.649453E+09 | 0.00 | 18308160.95 | 3597267.03 | 0.150313E+11 | 0.115489E+11 | 0.00 | 0.56 |
Minimum of Months | 0.140324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.212358E+10 | 0.409906E+09 | 0.00 | 4559589.14 | 1942560.96 | 0.411137E+10 | 0.254995E+10 | 0.00 | 0.94 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.431719E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.443337E+10 | 0.00 | 0.00 | 0.38 |
February | 0.890687E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.302929E+10 | 0.00 | 0.00 | 0.38 |
March | 0.178393E+10 | 0.00 | 0.00 | 5349.77 | 0.00 | 0.181836E+10 | 21431784.47 | 0.00 | 0.39 |
April | 0.186211E+10 | 14112198.37 | 0.00 | 326095.04 | 0.00 | 0.728974E+09 | 0.239787E+09 | 0.00 | 0.43 |
May | 0.194301E+10 | 8639568.52 | 0.00 | 1221365.20 | 0.00 | 58882201.35 | 0.806890E+09 | 0.00 | 0.56 |
June | 0.846347E+09 | 15558834.54 | 0.00 | 3218533.62 | 20435.50 | 0.00 | 0.211285E+10 | 0.00 | 0.77 |
July | 0.286389E+09 | 0.179713E+09 | 0.00 | 4107758.16 | 1662119.68 | 0.00 | 0.230555E+10 | 0.00 | 0.91 |
August | 0.173143E+09 | 0.406234E+09 | 0.00 | 3519743.35 | 1959610.87 | 0.00 | 0.207687E+10 | 0.00 | 0.86 |
September | 0.107268E+10 | 17132896.98 | 0.00 | 2992880.72 | 0.00 | 0.00 | 0.187592E+10 | 0.00 | 0.72 |
October | 0.198812E+10 | 0.00 | 0.00 | 623285.58 | 0.00 | 0.506739E+09 | 0.659418E+09 | 0.00 | 0.44 |
November | 0.144743E+10 | 0.00 | 0.00 | 42696.69 | 0.00 | 0.233920E+10 | 49724033.21 | 0.00 | 0.39 |
December | 0.849372E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.370766E+10 | 0.00 | 0.00 | 0.38 |
Annual Sum or Average | 0.135749E+11 | 0.641391E+09 | 0.00 | 16057708.13 | 3642166.05 | 0.166225E+11 | 0.101484E+11 | 0.00 | 0.55 |
Minimum of Months | 0.173143E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.198812E+10 | 0.406234E+09 | 0.00 | 4107758.16 | 1959610.87 | 0.443337E+10 | 0.230555E+10 | 0.00 | 0.91 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:18:58
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 19645462.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.483570E+10 | 0.00 | 0.00 | 0.38 |
February | 0.258650E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.364307E+10 | 0.00 | 0.00 | 0.38 |
March | 0.860115E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.272549E+10 | 0.00 | 0.00 | 0.39 |
April | 0.134915E+10 | 13912895.64 | 0.00 | 185459.59 | 0.00 | 0.123011E+10 | 0.147134E+09 | 0.00 | 0.42 |
May | 0.174978E+10 | 7181148.52 | 0.00 | 834201.00 | 0.00 | 0.310585E+09 | 0.512124E+09 | 0.00 | 0.53 |
June | 0.100700E+10 | 15114430.20 | 0.00 | 2344631.80 | 19892.70 | 1429954.00 | 0.157219E+10 | 0.00 | 0.71 |
July | 0.378897E+09 | 0.172926E+09 | 0.00 | 3220052.56 | 1671816.60 | 0.00 | 0.187767E+10 | 0.00 | 0.84 |
August | 0.265565E+09 | 0.398965E+09 | 0.00 | 2689924.10 | 1925448.08 | 0.00 | 0.169950E+10 | 0.00 | 0.79 |
September | 0.119522E+10 | 15276976.16 | 0.00 | 2415613.38 | 0.00 | 4075848.24 | 0.144200E+10 | 0.00 | 0.68 |
October | 0.168353E+10 | 0.00 | 0.00 | 322383.95 | 0.00 | 0.919570E+09 | 0.369699E+09 | 0.00 | 0.42 |
November | 0.665873E+09 | 0.00 | 0.00 | 33095.13 | 0.00 | 0.309255E+10 | 44691058.95 | 0.00 | 0.39 |
December | 63651231.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.448151E+10 | 0.00 | 0.00 | 0.38 |
Annual Sum or Average | 0.949708E+10 | 0.623376E+09 | 0.00 | 12045361.51 | 3617157.38 | 0.212441E+11 | 0.766501E+10 | 0.00 | 0.53 |
Minimum of Months | 19645462.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.174978E+10 | 0.398965E+09 | 0.00 | 3220052.56 | 1925448.08 | 0.483570E+10 | 0.187767E+10 | 0.00 | 0.84 |