Program Version:EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:18
Tabular Output Report in Format: HTML
Building: RetailStripmall
Environment: RUNPERIOD 1 ** Rochester International Arpt MN USA TMY3 WMO#=726440
Simulation Timestamp: 2020-06-03 19:18:54
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2020-06-03 19:18:54
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 2446.10 | 1170.21 | 1170.21 |
Net Site Energy | 2446.10 | 1170.21 | 1170.21 |
Total Source Energy | 5606.14 | 2681.96 | 2681.96 |
Net Source Energy | 5606.14 | 2681.96 | 2681.96 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 2090.32 |
Net Conditioned Building Area | 2090.32 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 1027.68 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 125.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 704.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 110.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 128.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 283.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 66.30 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1418.42 | 1027.68 | 0.00 | 0.00 | 0.00 | 87.30 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 1027.68 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 125.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 704.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 110.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 128.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 283.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 66.30 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 389.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 227.18 | 491.64 | 0.00 | 0.00 | 0.00 | 0.04 |
Other | 61.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 678.57 | 491.64 | 0.00 | 0.00 | 0.00 | 0.04 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 389.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 227.18 | 491.64 | 0.00 | 0.00 | 0.00 | 0.04 |
Other | 61.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 678.57 | 491.64 | 0.00 | 0.00 | 0.00 | 0.04 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1418.421 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1418.421 | 100.00 |
Total On-Site and Utility Electric Sources | 1418.421 | 100.00 |
Total Electricity End Uses | 1418.421 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 87.30 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 87.30 | 100.00 |
Total Water End Uses | 87.30 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 8.33 |
Time Setpoint Not Met During Occupied Cooling | 0.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 2776.33 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Meter |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2009
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Meter |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTRIPMALL
| Meter |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 6A
| Meter |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_ROCHESTER
| Meter |ZoneCoolingSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ZoneHeatingSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ZoneElectricSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |SpaceGainsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |PeakSpaceGainsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |SpaceGainComponentsAtCoolingPeakMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ComfortReportSimple55Monthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |OccupantComfortDataSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |DXReportMonthly
| PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL |WindowReportMonthly
| LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR |WindowEnergyReportMonthly
| LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR |WindowZoneSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |WindowEnergyZoneSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| GAS TANK1 | GAS TANK2 | GAS TANK3 | GAS TANK4 | GAS TANK5 | GAS TANK6 | GAS TANK7 |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC_1:1_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_2:2_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_3:3_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_4:4_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_5:5_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_6:6_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_7:7_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_8:8_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_9:9_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_10:10_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL |FanReportMonthly
| PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN |ZoneTemperatureOscillationReportMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |MechanicalVentilationLoadsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2020-06-03 19:18:54
GeneralValue | |
Program Version and Build | EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:18 |
RunPeriod | RUNPERIOD 1 |
Weather File | Rochester International Arpt MN USA TMY3 WMO#=726440 |
Latitude [deg] | 43.90 |
Longitude [deg] | -92.5 |
Elevation [m] | 398.00 |
Time Zone | -6.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Above Ground Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Window Opening Area [m2] | 124.29 | 0.00 | 0.00 | 124.29 | 0.00 |
Gross Window-Wall Ratio [%] | 10.50 | 0.00 | 0.00 | 26.24 | 0.00 |
Above Ground Window-Wall Ratio [%] | 10.50 | 0.00 | 0.00 | 26.24 | 0.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Above Ground Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Window Opening Area [m2] | 124.29 | 0.00 | 0.00 | 124.29 | 0.00 |
Gross Window-Wall Ratio [%] | 10.50 | 0.00 | 0.00 | 26.24 | 0.00 |
Above Ground Window-Wall Ratio [%] | 10.50 | 0.00 | 0.00 | 26.24 | 0.00 |
Total | |
Gross Roof Area [m2] | 2090.32 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
LGSTORE1 | 348.39 | Yes | Yes | 1805.20 | 1.00 | 276.30 | 0.00 | 20.75 | 20.75 | 24.9638 | 11.61 | 4.3000 |
SMSTORE1 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.37 | 10.37 | 27.8378 | 11.61 | 4.3000 |
SMSTORE2 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.35 | 10.35 | 25.6850 | 11.61 | 4.3000 |
SMSTORE3 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.35 | 10.35 | 25.6850 | 11.61 | 4.3000 |
SMSTORE4 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.35 | 10.35 | 25.6850 | 11.61 | 4.3000 |
LGSTORE2 | 348.39 | Yes | Yes | 1805.20 | 1.00 | 157.89 | 0.00 | 20.70 | 20.70 | 18.3225 | 11.61 | 4.3000 |
SMSTORE5 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.35 | 10.35 | 18.3225 | 11.61 | 4.3000 |
SMSTORE6 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.35 | 10.35 | 18.3225 | 11.61 | 4.3000 |
SMSTORE7 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.35 | 10.35 | 18.3225 | 11.61 | 4.3000 |
SMSTORE8 | 174.19 | Yes | Yes | 902.60 | 1.00 | 197.36 | 0.00 | 10.35 | 10.35 | 18.3225 | 11.61 | 4.3000 |
Total | 2090.32 | 10831.20 | 1184.15 | 0.00 | 124.29 | 124.29 | 22.0629 | 11.61 | 4.3000 | |||
Conditioned Total | 2090.32 | 10831.20 | 1184.15 | 0.00 | 124.29 | 124.29 | 22.0629 | 11.61 | 4.3000 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:18:54
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 04-AUG-13:00 | 02-FEB-12:09 | - | - | - | 06-JAN-13:09 |
Heating | 0.00 | 441652.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 76736.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 43812.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 8089.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 16442.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 5464.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 150546.18 | 441652.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 441652.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 76736.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 43812.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 8089.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 16442.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 5464.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:18:54
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 1114.01 | 0.00 | 0.00 | 0.00 |
Cooling | 396.38 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 2230.12 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 350.42 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 407.66 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 897.58 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 209.99 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 4492.14 | 1114.01 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 532.94 | 0.00 | 0.00 | 0.00 |
Cooling | 189.62 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1066.88 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 167.64 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 195.02 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 429.40 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 100.46 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2149.02 | 532.94 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 532.94 | 0.00 | 0.00 | 0.00 |
Cooling | 189.62 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1066.88 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 167.64 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 195.02 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 429.40 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 100.46 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2149.02 | 532.94 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:18:54
AirTerminal:SingleDuct:UncontrolledDesign Size Maximum Air Flow Rate [m3/s] | |
LGSTORE1 DIRECT AIR | 2.34 |
SMSTORE1 DIRECT AIR | 1.21 |
SMSTORE2 DIRECT AIR | 1.21 |
SMSTORE3 DIRECT AIR | 1.22 |
SMSTORE4 DIRECT AIR | 1.23 |
LGSTORE2 DIRECT AIR | 2.27 |
SMSTORE5 DIRECT AIR | 1.24 |
SMSTORE6 DIRECT AIR | 1.24 |
SMSTORE7 DIRECT AIR | 1.25 |
SMSTORE8 DIRECT AIR | 1.40 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC_1:1 | 2.34 | 2.34 | 2.34 | 2.34 | 2.34 | 2.34 | 1.00 | 1.00 | 2.34 |
PSZ-AC_2:2 | 1.21 | 1.21 | 1.21 | 1.21 | 1.21 | 1.21 | 1.00 | 1.00 | 1.21 |
PSZ-AC_3:3 | 1.21 | 1.21 | 1.21 | 1.21 | 1.21 | 1.21 | 1.00 | 1.00 | 1.21 |
PSZ-AC_4:4 | 1.22 | 1.22 | 1.22 | 1.22 | 1.22 | 1.22 | 1.00 | 1.00 | 1.22 |
PSZ-AC_5:5 | 1.23 | 1.23 | 1.23 | 1.23 | 1.23 | 1.23 | 1.00 | 1.00 | 1.23 |
PSZ-AC_6:6 | 2.27 | 2.27 | 2.27 | 2.27 | 2.27 | 2.27 | 1.00 | 1.00 | 2.27 |
PSZ-AC_7:7 | 1.24 | 1.24 | 1.24 | 1.24 | 1.24 | 1.24 | 1.00 | 1.00 | 1.24 |
PSZ-AC_8:8 | 1.24 | 1.24 | 1.24 | 1.24 | 1.24 | 1.24 | 1.00 | 1.00 | 1.24 |
PSZ-AC_9:9 | 1.25 | 1.25 | 1.25 | 1.25 | 1.25 | 1.25 | 1.00 | 1.00 | 1.25 |
PSZ-AC_10:10 | 1.40 | 1.40 | 1.40 | 1.40 | 1.40 | 1.40 | 1.00 | 1.00 | 1.40 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC_1:1_OA_CONTROLLER | 2.34 | 0.411453 |
PSZ-AC_2:2_OA_CONTROLLER | 1.21 | 0.205727 |
PSZ-AC_3:3_OA_CONTROLLER | 1.21 | 0.205727 |
PSZ-AC_4:4_OA_CONTROLLER | 1.22 | 0.205727 |
PSZ-AC_5:5_OA_CONTROLLER | 1.23 | 0.205727 |
PSZ-AC_6:6_OA_CONTROLLER | 2.27 | 0.411453 |
PSZ-AC_7:7_OA_CONTROLLER | 1.24 | 0.205727 |
PSZ-AC_8:8_OA_CONTROLLER | 1.24 | 0.205727 |
PSZ-AC_9:9_OA_CONTROLLER | 1.25 | 0.205727 |
PSZ-AC_10:10_OA_CONTROLLER | 1.40 | 0.205727 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC_1:1_UNITARY_PACKAGE_DX | 2.34 | 2.34 | 2.34 | 2.34 | 52314.18 | 73546.52 | 40.00 | 1.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_DX | 1.21 | 1.21 | 1.21 | 1.21 | 26526.76 | 37529.79 | 40.00 | 1.00 |
PSZ-AC_3:3_UNITARY_PACKAGE_DX | 1.21 | 1.21 | 1.21 | 1.21 | 26740.57 | 37730.70 | 40.00 | 1.00 |
PSZ-AC_4:4_UNITARY_PACKAGE_DX | 1.22 | 1.22 | 1.22 | 1.22 | 26788.55 | 37796.65 | 40.00 | 1.00 |
PSZ-AC_5:5_UNITARY_PACKAGE_DX | 1.23 | 1.23 | 1.23 | 1.23 | 26997.62 | 37952.94 | 40.00 | 1.00 |
PSZ-AC_6:6_UNITARY_PACKAGE_DX | 2.27 | 2.27 | 2.27 | 2.27 | 51097.51 | 71873.76 | 40.00 | 1.00 |
PSZ-AC_7:7_UNITARY_PACKAGE_DX | 1.24 | 1.24 | 1.24 | 1.24 | 28060.19 | 38350.31 | 40.00 | 1.00 |
PSZ-AC_8:8_UNITARY_PACKAGE_DX | 1.24 | 1.24 | 1.24 | 1.24 | 28088.22 | 38325.79 | 40.00 | 1.00 |
PSZ-AC_9:9_UNITARY_PACKAGE_DX | 1.25 | 1.25 | 1.25 | 1.25 | 28358.19 | 38534.06 | 40.00 | 1.00 |
PSZ-AC_10:10_UNITARY_PACKAGE_DX | 1.40 | 1.40 | 1.40 | 1.40 | 31549.03 | 41709.55 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | Speed 2 Design Size Rated Total Cooling Capacity [W] | Speed 2 User-Specified Rated Total Cooling Capacity [W] | Speed 1 Design Size Rated Total Cooling Capacity [W] | Speed 1 User-Specified Rated Total Cooling Capacity [W] | Speed 2 Design Size Rated Sensible Heat Ratio | Speed 2 User-Specified Rated Sensible Heat Ratio | Speed 1 Design Size Rated Sensible Heat Ratio | Speed 1 User-Specified Rated Sensible Heat Ratio | |
PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | 2.34 | 1.17 | 2.34 | 49440.21 | 52314.18 | 26157.09 | 52314.18 | 0.703481 | 0.703480 | 0.703480 | 0.703480 |
PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | 1.21 | 0.602885 | 1.21 | 25040.86 | 26526.76 | 13263.38 | 26526.76 | 0.707638 | 0.707640 | 0.707640 | 0.707640 |
PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | 1.21 | 0.607490 | 1.21 | 25243.46 | 26740.57 | 13370.28 | 26740.57 | 0.707522 | 0.707520 | 0.707520 | 0.707520 |
PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | 1.22 | 0.609000 | 1.22 | 25287.32 | 26788.55 | 13394.27 | 26788.55 | 0.707713 | 0.707710 | 0.707710 | 0.707710 |
PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | 1.23 | 0.612585 | 1.23 | 25488.46 | 26997.62 | 13498.81 | 26997.62 | 0.707187 | 0.707190 | 0.707190 | 0.707190 |
PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | 2.27 | 1.13 | 2.27 | 48325.36 | 51097.51 | 25548.76 | 51097.51 | 0.700839 | 0.700840 | 0.700840 | 0.700840 |
PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | 1.24 | 0.621695 | 1.24 | 26538.97 | 28060.19 | 14030.09 | 28060.19 | 0.700680 | 0.700680 | 0.700680 | 0.700680 |
PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | 1.24 | 0.621135 | 1.24 | 26569.31 | 28088.22 | 14044.11 | 28088.22 | 0.700168 | 0.700170 | 0.700170 | 0.700170 |
PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | 1.25 | 0.625910 | 1.25 | 26828.45 | 28358.19 | 14179.09 | 28358.19 | 0.699655 | 0.699650 | 0.699650 | 0.699650 |
PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | 1.40 | 0.698685 | 1.40 | 29841.38 | 31549.03 | 15774.51 | 31549.03 | 0.700561 | 0.700560 | 0.700560 | 0.700560 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | 2.34 | 2563.55 |
PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | 1.21 | 1374.71 |
PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | 1.21 | 1385.21 |
PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | 1.22 | 1388.66 |
PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | 1.23 | 1396.83 |
PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | 2.27 | 2479.65 |
PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | 1.24 | 1417.60 |
PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | 1.24 | 1416.32 |
PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | 1.25 | 1427.21 |
PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | 1.40 | 1593.16 |
Design Size Nominal Capacity [W] | |
PSZ-AC_1:1_UNITARY_PACKAGE_HEATCOIL | 73546.52 |
PSZ-AC_2:2_UNITARY_PACKAGE_HEATCOIL | 37529.79 |
PSZ-AC_3:3_UNITARY_PACKAGE_HEATCOIL | 37730.70 |
PSZ-AC_4:4_UNITARY_PACKAGE_HEATCOIL | 37796.65 |
PSZ-AC_5:5_UNITARY_PACKAGE_HEATCOIL | 37952.94 |
PSZ-AC_6:6_UNITARY_PACKAGE_HEATCOIL | 71873.76 |
PSZ-AC_7:7_UNITARY_PACKAGE_HEATCOIL | 38350.31 |
PSZ-AC_8:8_UNITARY_PACKAGE_HEATCOIL | 38325.79 |
PSZ-AC_9:9_UNITARY_PACKAGE_HEATCOIL | 38534.06 |
PSZ-AC_10:10_UNITARY_PACKAGE_HEATCOIL | 41709.55 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:18:54
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
LGSTORE1_WALL_3 | LGSTORE1_WALL_3_DOOR_1 | LGSTORE1_WALL_3_DOOR_2 | |
LGSTORE1_WALL_1 | LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | |
SMSTORE1_WALL_1 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | |
SMSTORE1_WALL_3 | SMSTORE1_WALL_3_DOOR | |
SMSTORE2_WALL_1 | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | |
SMSTORE2_WALL_3 | SMSTORE2_WALL_3_DOOR | |
SMSTORE3_WALL_1 | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | |
SMSTORE3_WALL_3 | SMSTORE3_WALL_3_DOOR | |
SMSTORE4_WALL_1 | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | |
SMSTORE4_WALL_3 | SMSTORE4_WALL_3_DOOR | |
LGSTORE2_WALL_3 | LGSTORE2_WALL_3_DOOR_1 | LGSTORE2_WALL_3_DOOR_2 | |
LGSTORE2_WALL_1 | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | |
SMSTORE5_WALL_1 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | |
SMSTORE5_WALL_3 | SMSTORE5_WALL_3_DOOR | |
SMSTORE6_WALL_1 | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | |
SMSTORE6_WALL_3 | SMSTORE6_WALL_3_DOOR | |
SMSTORE7_WALL_1 | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | |
SMSTORE7_WALL_3 | SMSTORE7_WALL_3_DOOR | |
SMSTORE8_WALL_1 | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR | |
SMSTORE8_WALL_3 | SMSTORE8_WALL_3_DOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2020-06-03 19:18:54
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2020-06-03 19:18:54
VersionVersion ID | |
1 | 9.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 7.40 | -0.00 | -7.60 | -12.60 | -7.70 | 0.30 | 7.00 | 14.20 | 19.20 | 20.90 | 20.00 | 15.40 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Rochester International Arpt MN USA TMY3 WMO#=726440 | 43.90 | -92.50 | -6.00 | 398.00 | 96634 | 1.1486 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 6.38 | 33.50 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RetailStripmall | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 10 | 118 | 48 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | LGSTORE1 | 0.0 | 0.00 | 0.00 | 0.00 | 7.62 | 11.43 | 2.59 | 1 | 1 | 1 | 0.00 | 15.24 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 1805.20 | TARP | TARP | 348.39 | 276.30 | 247.76 | 20.75 | 6 | 8 | 0 | Yes |
2 | SMSTORE1 | 0.0 | 0.00 | 0.00 | 0.00 | 19.05 | 11.43 | 2.59 | 1 | 1 | 1 | 15.24 | 22.86 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.67 | 10.37 | 6 | 4 | 0 | Yes |
3 | SMSTORE2 | 0.0 | 0.00 | 0.00 | 0.00 | 26.67 | 11.43 | 2.59 | 1 | 1 | 1 | 22.86 | 30.48 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.35 | 6 | 4 | 0 | Yes |
4 | SMSTORE3 | 0.0 | 0.00 | 0.00 | 0.00 | 34.29 | 11.43 | 2.59 | 1 | 1 | 1 | 30.48 | 38.10 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.35 | 6 | 4 | 0 | Yes |
5 | SMSTORE4 | 0.0 | 0.00 | 0.00 | 0.00 | 41.91 | 11.43 | 2.59 | 1 | 1 | 1 | 38.10 | 45.72 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.35 | 6 | 4 | 0 | Yes |
6 | LGSTORE2 | 0.0 | 0.00 | 0.00 | 0.00 | 53.34 | 11.43 | 2.59 | 1 | 1 | 1 | 45.72 | 60.96 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 1805.20 | TARP | TARP | 348.39 | 157.89 | 129.43 | 20.70 | 6 | 8 | 0 | Yes |
7 | SMSTORE5 | 0.0 | 0.00 | 0.00 | 0.00 | 64.77 | 11.43 | 2.59 | 1 | 1 | 1 | 60.96 | 68.58 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.35 | 6 | 4 | 0 | Yes |
8 | SMSTORE6 | 0.0 | 0.00 | 0.00 | 0.00 | 72.39 | 11.43 | 2.59 | 1 | 1 | 1 | 68.58 | 76.20 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.35 | 6 | 4 | 0 | Yes |
9 | SMSTORE7 | 0.0 | 0.00 | 0.00 | 0.00 | 80.01 | 11.43 | 2.59 | 1 | 1 | 1 | 76.20 | 83.82 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.35 | 6 | 4 | 0 | Yes |
10 | SMSTORE8 | 0.0 | 0.00 | 0.00 | 0.00 | 87.63 | 11.43 | 2.59 | 1 | 1 | 1 | 83.82 | 91.44 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 197.36 | 183.13 | 10.35 | 6 | 4 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | LGSTORE1 | 348.39 | 30.0 | 11.614 | 8.610E-002 | 24.964 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 29.264 | No |
2 | SMSTORE1 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 27.838 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 32.138 | No |
3 | SMSTORE2 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 25.685 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 29.985 | No |
4 | SMSTORE3 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 25.685 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 29.985 | No |
5 | SMSTORE4 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 25.685 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 29.985 | No |
6 | LGSTORE2 | 348.39 | 30.0 | 11.614 | 8.610E-002 | 18.322 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 22.622 | No |
7 | SMSTORE5 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 18.322 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 22.622 | No |
8 | SMSTORE6 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 18.322 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 22.622 | No |
9 | SMSTORE7 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 18.322 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 22.622 | No |
10 | SMSTORE8 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 18.322 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 22.622 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | |
1 | LGSTORE1 | TYPE1_OCC_SCH | LGSTORE1 | 348.39 | 30.0 | 30.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 30 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
2 | SMSTORE1 | TYPE1_OCC_SCH | SMSTORE1 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
3 | SMSTORE2 | TYPE2_OCC_SCH | SMSTORE2 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
4 | SMSTORE3 | TYPE2_OCC_SCH | SMSTORE3 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
5 | SMSTORE4 | TYPE2_OCC_SCH | SMSTORE4 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
6 | LGSTORE2 | TYPE3_OCC_SCH | LGSTORE2 | 348.39 | 30.0 | 30.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 30 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
7 | SMSTORE5 | TYPE3_OCC_SCH | SMSTORE5 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
8 | SMSTORE6 | TYPE3_OCC_SCH | SMSTORE6 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
9 | SMSTORE7 | TYPE3_OCC_SCH | SMSTORE7 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
10 | SMSTORE8 | TYPE3_OCC_SCH | SMSTORE8 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | LGSTORE1_LIGHTS | TYPE1_LIGHT_SCH | LGSTORE1 | 348.39 | 30.0 | 6383.296 | 18.322 | 212.804 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 6383.296 |
2 | LGSTORE1_LIGHTS_ALLOWANCE | TYPE1_LIGHT_SCH | LGSTORE1 | 348.39 | 30.0 | 2313.751 | 6.641 | 77.135 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2313.751 |
3 | SMSTORE1_LIGHTS | TYPE1_LIGHT_SCH | SMSTORE1 | 174.19 | 15.0 | 3191.648 | 18.322 | 212.805 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3191.648 |
4 | SMSTORE1_LIGHTS_ALLOWANCE | TYPE1_LIGHT_SCH | SMSTORE1 | 174.19 | 15.0 | 1657.501 | 9.515 | 110.515 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1657.501 |
5 | SMSTORE2_LIGHTS | TYPE2_LIGHT_SCH | SMSTORE2 | 174.19 | 15.0 | 3191.648 | 18.322 | 212.805 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3191.648 |
6 | SMSTORE2_LIGHTS_ALLOWANCE | TYPE2_LIGHT_SCH | SMSTORE2 | 174.19 | 15.0 | 1282.501 | 7.363 | 85.511 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1282.501 |
7 | SMSTORE3_LIGHTS | TYPE2_LIGHT_SCH | SMSTORE3 | 174.19 | 15.0 | 3191.648 | 18.322 | 212.805 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3191.648 |
8 | SMSTORE3_LIGHTS_ALLOWANCE | TYPE2_LIGHT_SCH | SMSTORE3 | 174.19 | 15.0 | 1282.501 | 7.363 | 85.511 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1282.501 |
9 | SMSTORE4_LIGHTS | TYPE2_LIGHT_SCH | SMSTORE4 | 174.19 | 15.0 | 3191.648 | 18.322 | 212.805 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3191.648 |
10 | SMSTORE4_LIGHTS_ALLOWANCE | TYPE2_LIGHT_SCH | SMSTORE4 | 174.19 | 15.0 | 1282.501 | 7.363 | 85.511 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1282.501 |
11 | LGSTORE2_LIGHTS | TYPE3_LIGHT_SCH | LGSTORE2 | 348.39 | 30.0 | 6383.296 | 18.322 | 212.804 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 6383.296 |
12 | LGSTORE2_LIGHTS_ALLOWANCE | TYPE3_LIGHT_SCH | LGSTORE2 | 348.39 | 30.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
13 | SMSTORE5_LIGHTS | TYPE3_LIGHT_SCH | SMSTORE5 | 174.19 | 15.0 | 3191.648 | 18.322 | 212.805 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3191.648 |
14 | SMSTORE5_LIGHTS_ALLOWANCE | TYPE3_LIGHT_SCH | SMSTORE5 | 174.19 | 15.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
15 | SMSTORE6_LIGHTS | TYPE3_LIGHT_SCH | SMSTORE6 | 174.19 | 15.0 | 3191.648 | 18.322 | 212.805 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3191.648 |
16 | SMSTORE6_LIGHTS_ALLOWANCE | TYPE3_LIGHT_SCH | SMSTORE6 | 174.19 | 15.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
17 | SMSTORE7_LIGHTS | TYPE3_LIGHT_SCH | SMSTORE7 | 174.19 | 15.0 | 3191.648 | 18.322 | 212.805 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3191.648 |
18 | SMSTORE7_LIGHTS_ALLOWANCE | TYPE3_LIGHT_SCH | SMSTORE7 | 174.19 | 15.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
19 | SMSTORE8_LIGHTS | TYPE3_LIGHT_SCH | SMSTORE8 | 174.19 | 15.0 | 3191.648 | 18.322 | 212.805 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3191.648 |
20 | SMSTORE8_LIGHTS_ALLOWANCE | TYPE3_LIGHT_SCH | SMSTORE8 | 174.19 | 15.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | LGSTORE1_MISCPLUG_EQUIP | TYPE1_EQUIP_SCH | LGSTORE1 | 348.39 | 30.0 | 1498.062 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1498.062 |
2 | SMSTORE1_MISCPLUG_EQUIP | TYPE1_EQUIP_SCH | SMSTORE1 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
3 | SMSTORE2_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE2 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
4 | SMSTORE3_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE3 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
5 | SMSTORE4_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE4 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
6 | LGSTORE2_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | LGSTORE2 | 348.39 | 30.0 | 1498.062 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1498.062 |
7 | SMSTORE5_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE5 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
8 | SMSTORE6_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE6 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
9 | SMSTORE7_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE7 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
10 | SMSTORE8_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE8 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.975 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.2832 | 0.900 | 0.900 | 0.770 | 0.700 | Rough |
5 | NONRES_EXT_WALL | 20 | 4 | 7 | 0.167 | 0.3843 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
6 | LGSTORE1_FLOOR_FFACTOR | 30 | 2 | 7 | 0.167 | 0.1464 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
7 | SMSTORE1_FLOOR_FFACTOR | 31 | 2 | 7 | 0.167 | 0.8283E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
8 | SMSTORE2_FLOOR_FFACTOR | 32 | 2 | 7 | 0.167 | 0.8283E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | SMSTORE3_FLOOR_FFACTOR | 33 | 2 | 7 | 0.167 | 0.8283E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
10 | SMSTORE4_FLOOR_FFACTOR | 34 | 2 | 7 | 0.167 | 0.8283E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
11 | LGSTORE2_FLOOR_FFACTOR | 35 | 2 | 7 | 0.167 | 0.8283E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | SMSTORE5_FLOOR_FFACTOR | 36 | 2 | 7 | 0.167 | 0.8283E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | SMSTORE6_FLOOR_FFACTOR | 37 | 2 | 7 | 0.167 | 0.8283E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | SMSTORE7_FLOOR_FFACTOR | 38 | 2 | 7 | 0.167 | 0.8283E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | SMSTORE8_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.2111 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2516 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
6 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 3.472 |
7 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
8 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
9 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
10 | NONRES_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.368 |
11 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
12 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 6.756 |
13 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
14 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.00 |
15 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
16 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.00 |
17 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
18 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.00 |
19 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
20 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.00 |
21 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
22 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.00 |
23 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
24 | ~FC_Insulation_7 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.00 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_8 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.00 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_9 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.00 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
30 | ~FC_Insulation_10 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.659 |
31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.9747885 | 3.9747885 | 3.9747885 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
14 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
15 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
16 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
17 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
18 | 3 | -0.61927053E-06 | 0.12767249E-08 | -0.37968499E-05 | 0.16832131E-17 |
19 | 2 | 0.77611055 | 0.17315568E-02 | 1.0534842 | -0.72792597E-06 |
20 | 1 | -21.915918 | 0.11588205 | -6.3286394 | 0.20197014 |
21 | 0 | 21.365777 | 0.10835518 | 5.5011278 | |
22 | 7 | -0.35963630E-12 | 0.61482467E-15 | -0.13288964E-12 | 0.15093609E-15 |
23 | 6 | 0.33258387E-07 | 0.11249777E-09 | 0.75805110E-08 | -0.16019892E-12 |
24 | 5 | -0.21313350E-03 | 0.93714421E-06 | -0.10927814E-03 | 0.74776115E-08 |
25 | 4 | 0.31870195 | 0.44521373E-03 | 0.10925225 | -0.37358013E-04 |
26 | 3 | -7.7913368 | 0.13499397E-01 | -2.4947666 | 0.31584435E-01 |
27 | 2 | 42.601618 | 0.47079245E-01 | 15.902165 | -0.35261900 |
28 | 1 | -81.870774 | 0.20888078E-01 | -29.712230 | 1.1068570 |
29 | 0 | 46.824331 | 0.41326549E-03 | 16.278015 | |
30 | 7 | -0.28997596E-08 | -0.17578320E-14 | 0.22751757E-14 | -0.53829073E-16 |
31 | 6 | 0.41991781E-05 | 0.27986603E-08 | 0.31940183E-02 | -0.26794102E-04 |
32 | 5 | -0.29588474E-03 | 0.16552611E-05 | -0.22396035 | 0.19582313E-02 |
33 | 4 | 0.67666006E-02 | 0.75295852E-04 | 4.8334724 | -0.45302727E-01 |
34 | 3 | -0.59297736E-01 | 0.59838054E-03 | -38.043598 | 0.39889893 |
35 | 2 | 0.21038411 | 0.99492606E-03 | 116.52712 | -1.4185167 |
36 | 1 | -0.30354941 | 0.30287292E-03 | -143.93272 | 2.0494576 |
37 | 0 | 0.14796861 | 0.73483799E-05 | 60.838472 | |
38 | 7 | -0.51571905E-08 | -0.97500959E-14 | 0.15789915E-14 | -0.32998988E-16 |
39 | 6 | 0.26247599E-05 | 0.15902949E-08 | 0.31989528E-02 | -0.26835497E-04 |
40 | 5 | -0.17282397E-03 | 0.93714128E-06 | -0.22424071 | 0.19607060E-02 |
41 | 4 | 0.38696203E-02 | 0.42548205E-04 | 4.8381400 | -0.45347597E-01 |
42 | 3 | -0.33643188E-01 | 0.33758390E-03 | -38.069955 | 0.39919029 |
43 | 2 | 0.11898200 | 0.56044665E-03 | 116.57840 | -1.4192028 |
44 | 1 | -0.17142224 | 0.17027190E-03 | -143.96290 | 2.0499538 |
45 | 0 | 0.83499932E-01 | 0.41268798E-05 | 60.838472 | |
46 | 7 | -0.51571905E-08 | -0.97500958E-14 | 0.15789913E-14 | -0.32998984E-16 |
47 | 6 | 0.26247599E-05 | 0.15902949E-08 | 0.31989528E-02 | -0.26835497E-04 |
48 | 5 | -0.17282397E-03 | 0.93714128E-06 | -0.22424071 | 0.19607060E-02 |
49 | 4 | 0.38696203E-02 | 0.42548205E-04 | 4.8381400 | -0.45347597E-01 |
50 | 3 | -0.33643188E-01 | 0.33758390E-03 | -38.069955 | 0.39919029 |
51 | 2 | 0.11898200 | 0.56044665E-03 | 116.57840 | -1.4192028 |
52 | 1 | -0.17142224 | 0.17027190E-03 | -143.96290 | 2.0499538 |
53 | 0 | 0.83499932E-01 | 0.41268798E-05 | 60.838472 | |
54 | 7 | -0.51571905E-08 | -0.97500959E-14 | 0.15789911E-14 | -0.32998980E-16 |
55 | 6 | 0.26247599E-05 | 0.15902949E-08 | 0.31989528E-02 | -0.26835497E-04 |
56 | 5 | -0.17282397E-03 | 0.93714128E-06 | -0.22424071 | 0.19607060E-02 |
57 | 4 | 0.38696203E-02 | 0.42548205E-04 | 4.8381400 | -0.45347597E-01 |
58 | 3 | -0.33643188E-01 | 0.33758390E-03 | -38.069955 | 0.39919029 |
59 | 2 | 0.11898200 | 0.56044665E-03 | 116.57840 | -1.4192028 |
60 | 1 | -0.17142224 | 0.17027190E-03 | -143.96290 | 2.0499538 |
61 | 0 | 0.83499932E-01 | 0.41268798E-05 | 60.838472 | |
62 | 7 | -0.51571905E-08 | -0.97500959E-14 | 0.15789915E-14 | -0.32998988E-16 |
63 | 6 | 0.26247599E-05 | 0.15902949E-08 | 0.31989528E-02 | -0.26835497E-04 |
64 | 5 | -0.17282397E-03 | 0.93714128E-06 | -0.22424071 | 0.19607060E-02 |
65 | 4 | 0.38696203E-02 | 0.42548205E-04 | 4.8381400 | -0.45347597E-01 |
66 | 3 | -0.33643188E-01 | 0.33758390E-03 | -38.069955 | 0.39919029 |
67 | 2 | 0.11898200 | 0.56044665E-03 | 116.57840 | -1.4192028 |
68 | 1 | -0.17142224 | 0.17027190E-03 | -143.96290 | 2.0499538 |
69 | 0 | 0.83499932E-01 | 0.41268798E-05 | 60.838472 | |
70 | 7 | -0.51571905E-08 | -0.97500958E-14 | 0.15789913E-14 | -0.32998984E-16 |
71 | 6 | 0.26247599E-05 | 0.15902949E-08 | 0.31989528E-02 | -0.26835497E-04 |
72 | 5 | -0.17282397E-03 | 0.93714128E-06 | -0.22424071 | 0.19607060E-02 |
73 | 4 | 0.38696203E-02 | 0.42548205E-04 | 4.8381400 | -0.45347597E-01 |
74 | 3 | -0.33643188E-01 | 0.33758390E-03 | -38.069955 | 0.39919029 |
75 | 2 | 0.11898200 | 0.56044665E-03 | 116.57840 | -1.4192028 |
76 | 1 | -0.17142224 | 0.17027190E-03 | -143.96290 | 2.0499538 |
77 | 0 | 0.83499932E-01 | 0.41268798E-05 | 60.838472 | |
78 | 7 | -0.51571905E-08 | -0.97500957E-14 | 0.15789917E-14 | -0.32998991E-16 |
79 | 6 | 0.26247599E-05 | 0.15902949E-08 | 0.31989528E-02 | -0.26835497E-04 |
80 | 5 | -0.17282397E-03 | 0.93714128E-06 | -0.22424071 | 0.19607060E-02 |
81 | 4 | 0.38696203E-02 | 0.42548205E-04 | 4.8381400 | -0.45347597E-01 |
82 | 3 | -0.33643188E-01 | 0.33758390E-03 | -38.069955 | 0.39919029 |
83 | 2 | 0.11898200 | 0.56044665E-03 | 116.57840 | -1.4192028 |
84 | 1 | -0.17142224 | 0.17027190E-03 | -143.96290 | 2.0499538 |
85 | 0 | 0.83499932E-01 | 0.41268798E-05 | 60.838472 | |
86 | 7 | -0.51571905E-08 | -0.97500959E-14 | 0.15789915E-14 | -0.32998988E-16 |
87 | 6 | 0.26247599E-05 | 0.15902949E-08 | 0.31989528E-02 | -0.26835497E-04 |
88 | 5 | -0.17282397E-03 | 0.93714128E-06 | -0.22424071 | 0.19607060E-02 |
89 | 4 | 0.38696203E-02 | 0.42548205E-04 | 4.8381400 | -0.45347597E-01 |
90 | 3 | -0.33643188E-01 | 0.33758390E-03 | -38.069955 | 0.39919029 |
91 | 2 | 0.11898200 | 0.56044665E-03 | 116.57840 | -1.4192028 |
92 | 1 | -0.17142224 | 0.17027190E-03 | -143.96290 | 2.0499538 |
93 | 0 | 0.83499932E-01 | 0.41268798E-05 | 60.838472 | |
94 | 7 | -0.51571905E-08 | -0.97500958E-14 | 0.15789913E-14 | -0.32998984E-16 |
95 | 6 | 0.26247599E-05 | 0.15902949E-08 | 0.31989528E-02 | -0.26835497E-04 |
96 | 5 | -0.17282397E-03 | 0.93714128E-06 | -0.22424071 | 0.19607060E-02 |
97 | 4 | 0.38696203E-02 | 0.42548205E-04 | 4.8381400 | -0.45347597E-01 |
98 | 3 | -0.33643188E-01 | 0.33758390E-03 | -38.069955 | 0.39919029 |
99 | 2 | 0.11898200 | 0.56044665E-03 | 116.57840 | -1.4192028 |
100 | 1 | -0.17142224 | 0.17027190E-03 | -143.96290 | 2.0499538 |
101 | 0 | 0.83499932E-01 | 0.41268798E-05 | 60.838472 | |
102 | 7 | -0.19967951E-08 | -0.58252365E-15 | 0.72897552E-14 | -0.10630581E-15 |
103 | 6 | 0.59274927E-05 | 0.40433693E-08 | 0.31889525E-02 | -0.26751606E-04 |
104 | 5 | -0.42514865E-03 | 0.23948505E-05 | -0.22367243 | 0.19556901E-02 |
105 | 4 | 0.97725356E-02 | 0.10900143E-03 | 4.8286774 | -0.45256634E-01 |
106 | 3 | -0.85796444E-01 | 0.86675557E-03 | -38.016512 | 0.39859954 |
107 | 2 | 0.30461848 | 0.14417950E-02 | 116.47440 | -1.4178116 |
108 | 1 | -0.43965446 | 0.43929230E-03 | -143.90169 | 2.0489476 |
109 | 0 | 0.21434897 | 0.10616597E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.47_SHGC_0.4 | 29 | 1 | VerySmooth | 2.672 | 0.394 | 0.315 | 0.401 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 2.40629E-002 | 0.31435 | 0.46917 | 0.46917 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11822 | 1.00000 | No |
Calculation Method | Value {days} | Allowable Number Figures in Shadow Overlap {} | Polygon Clipping Algorithm | Sky Diffuse Modeling Algorithm | External Shading Calculation Method | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | AverageOverDaysInFrequency | 30 | 15000 | SutherlandHodgman | SimpleSkyDiffuseModeling | InternalCalculation | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | GAS TANK1 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
2 | WaterHeater:Mixed | GAS TANK2 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
3 | WaterHeater:Mixed | GAS TANK3 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
4 | WaterHeater:Mixed | GAS TANK4 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
5 | WaterHeater:Mixed | GAS TANK5 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
6 | WaterHeater:Mixed | GAS TANK6 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
7 | WaterHeater:Mixed | GAS TANK7 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | LGSTORE1_WALL_2 | 0 | 118.41 | 56.08 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 4 | No | No |
2 | LGSTORE1_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 4 | No | No |
3 | LGSTORE1_WALL_3_DOOR_1 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 0 | No | No |
4 | LGSTORE1_WALL_3_DOOR_2 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 0 | No | No |
5 | LGSTORE1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 0 | No | No |
6 | LGSTORE1_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 4 | No | No |
7 | LGSTORE1_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 1 | No | No |
8 | LGSTORE1_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 1 | No | No |
9 | LGSTORE1_WALL_1_WINDOW_3 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 1 | No | No |
10 | LGSTORE1_WALL_1_WINDOW_4 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 1 | No | No |
11 | LGSTORE1_WALL_1_DOOR_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 1 | No | No |
12 | LGSTORE1_WALL_1_DOOR_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 1 | No | No |
13 | LGSTORE1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 0 | No | No |
14 | LGSTORE1_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 0 | No | No |
15 | LGSTORE1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 0 | No | No |
16 | SMSTORE1_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
17 | SMSTORE1_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
18 | SMSTORE1_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
19 | SMSTORE1_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
20 | SMSTORE1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
21 | SMSTORE1_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
22 | SMSTORE1_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
23 | SMSTORE1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
24 | SMSTORE1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
25 | SMSTORE1_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
26 | SMSTORE1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
27 | SMSTORE2_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
28 | SMSTORE2_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
29 | SMSTORE2_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
30 | SMSTORE2_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
31 | SMSTORE2_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
32 | SMSTORE2_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
33 | SMSTORE2_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
34 | SMSTORE2_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
35 | SMSTORE2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
36 | SMSTORE2_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
37 | SMSTORE2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
38 | SMSTORE3_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
39 | SMSTORE3_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
40 | SMSTORE3_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
41 | SMSTORE3_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
42 | SMSTORE3_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
43 | SMSTORE3_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
44 | SMSTORE3_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
45 | SMSTORE3_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
46 | SMSTORE3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
47 | SMSTORE3_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
48 | SMSTORE3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
49 | SMSTORE4_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
50 | SMSTORE4_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
51 | SMSTORE4_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
52 | SMSTORE4_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
53 | SMSTORE4_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
54 | SMSTORE4_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 3 | No | No |
55 | SMSTORE4_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
56 | SMSTORE4_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
57 | SMSTORE4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
58 | SMSTORE4_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
59 | SMSTORE4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
60 | LGSTORE2_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
61 | LGSTORE2_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 4 | No | No |
62 | LGSTORE2_WALL_3_DOOR_1 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
63 | LGSTORE2_WALL_3_DOOR_2 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
64 | LGSTORE2_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
65 | LGSTORE2_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 4 | No | No |
66 | LGSTORE2_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
67 | LGSTORE2_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
68 | LGSTORE2_WALL_1_WINDOW_3 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
69 | LGSTORE2_WALL_1_WINDOW_4 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
70 | LGSTORE2_WALL_1_DOOR_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
71 | LGSTORE2_WALL_1_DOOR_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
72 | LGSTORE2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
73 | LGSTORE2_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
74 | LGSTORE2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
75 | SMSTORE5_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
76 | SMSTORE5_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
77 | SMSTORE5_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
78 | SMSTORE5_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
79 | SMSTORE5_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
80 | SMSTORE5_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
81 | SMSTORE5_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
82 | SMSTORE5_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
83 | SMSTORE5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
84 | SMSTORE5_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
85 | SMSTORE5_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
86 | SMSTORE6_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
87 | SMSTORE6_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
88 | SMSTORE6_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
89 | SMSTORE6_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
90 | SMSTORE6_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
91 | SMSTORE6_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
92 | SMSTORE6_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
93 | SMSTORE6_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
94 | SMSTORE6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
95 | SMSTORE6_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
96 | SMSTORE6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
97 | SMSTORE7_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
98 | SMSTORE7_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
99 | SMSTORE7_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
100 | SMSTORE7_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
101 | SMSTORE7_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
102 | SMSTORE7_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 3 | No | No |
103 | SMSTORE7_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
104 | SMSTORE7_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
105 | SMSTORE7_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
106 | SMSTORE7_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
107 | SMSTORE7_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
108 | SMSTORE8_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 4 | No | No |
109 | SMSTORE8_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 1 | No | No |
110 | SMSTORE8_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 1 | No | No |
111 | SMSTORE8_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 1 | No | No |
112 | SMSTORE8_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
113 | SMSTORE8_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 3 | No | No |
114 | SMSTORE8_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
115 | SMSTORE8_WALL_4 | 0 | 118.41 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 3 | No | No |
116 | SMSTORE8_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
117 | SMSTORE8_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
118 | SMSTORE8_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | LGSTORE1_INFILTRATION | TYPE1_INFIL_SCH | LGSTORE1 | 348.39 | 30.0 | 0.286 | 8.224E-004 | 4.530E-004 | 0.571 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | LGSTORE1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | LGSTORE1 | 348.39 | 30.0 | 0.389 | 1.116E-003 | 6.149E-004 | 0.776 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | SMSTORE1_INFILTRATION | TYPE1_INFIL_SCH | SMSTORE1 | 174.19 | 15.0 | 8.210E-002 | 4.713E-004 | 3.194E-004 | 0.327 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | SMSTORE1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE1 | 174.19 | 15.0 | 0.222 | 1.276E-003 | 8.648E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
5 | SMSTORE2_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE2 | 174.19 | 15.0 | 8.210E-002 | 4.713E-004 | 3.194E-004 | 0.327 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | SMSTORE2_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE2 | 174.19 | 15.0 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
7 | SMSTORE3_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE3 | 174.19 | 15.0 | 8.210E-002 | 4.713E-004 | 3.194E-004 | 0.327 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | SMSTORE3_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE3 | 174.19 | 15.0 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | SMSTORE4_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE4 | 174.19 | 15.0 | 8.210E-002 | 4.713E-004 | 3.194E-004 | 0.327 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | SMSTORE4_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE4 | 174.19 | 15.0 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
11 | LGSTORE2_INFILTRATION | TYPE3_INFIL_SCH | LGSTORE2 | 348.39 | 30.0 | 0.164 | 4.713E-004 | 3.194E-004 | 0.327 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | LGSTORE2_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | LGSTORE2 | 348.39 | 30.0 | 0.389 | 1.116E-003 | 7.565E-004 | 0.776 | 1.000 | 0.000 | 0.000 | 0.000 |
13 | SMSTORE5_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE5 | 174.19 | 15.0 | 8.210E-002 | 4.713E-004 | 3.194E-004 | 0.327 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | SMSTORE5_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE5 | 174.19 | 15.0 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
15 | SMSTORE6_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE6 | 174.19 | 15.0 | 8.210E-002 | 4.713E-004 | 3.194E-004 | 0.327 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | SMSTORE6_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE6 | 174.19 | 15.0 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
17 | SMSTORE7_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE7 | 174.19 | 15.0 | 8.210E-002 | 4.713E-004 | 3.194E-004 | 0.327 | 0.000 | 0.000 | 0.224 | 0.000 |
18 | SMSTORE7_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE7 | 174.19 | 15.0 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
19 | SMSTORE8_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE8 | 174.19 | 15.0 | 0.204 | 1.172E-003 | 5.440E-004 | 0.815 | 0.000 | 0.000 | 0.224 | 0.000 |
20 | SMSTORE8_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE8 | 174.19 | 15.0 | 0.222 | 1.276E-003 | 5.921E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | LGSTORE1 | Mixing/Well-Stirred |
2 | SMSTORE1 | Mixing/Well-Stirred |
3 | SMSTORE2 | Mixing/Well-Stirred |
4 | SMSTORE3 | Mixing/Well-Stirred |
5 | SMSTORE4 | Mixing/Well-Stirred |
6 | LGSTORE2 | Mixing/Well-Stirred |
7 | SMSTORE5 | Mixing/Well-Stirred |
8 | SMSTORE6 | Mixing/Well-Stirred |
9 | SMSTORE7 | Mixing/Well-Stirred |
10 | SMSTORE8 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone LGSTORE1 | 1.2000 |
3 | Zone SMSTORE1 | 1.2000 |
4 | Zone SMSTORE2 | 1.2000 |
5 | Zone SMSTORE3 | 1.2000 |
6 | Zone SMSTORE4 | 1.2000 |
7 | Zone LGSTORE2 | 1.2000 |
8 | Zone SMSTORE5 | 1.2000 |
9 | Zone SMSTORE6 | 1.2000 |
10 | Zone SMSTORE7 | 1.2000 |
11 | Zone SMSTORE8 | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone LGSTORE1 | 1.2000 |
3 | Zone SMSTORE1 | 1.2000 |
4 | Zone SMSTORE2 | 1.2000 |
5 | Zone SMSTORE3 | 1.2000 |
6 | Zone SMSTORE4 | 1.2000 |
7 | Zone LGSTORE2 | 1.2000 |
8 | Zone SMSTORE5 | 1.2000 |
9 | Zone SMSTORE6 | 1.2000 |
10 | Zone SMSTORE7 | 1.2000 |
11 | Zone SMSTORE8 | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | LGSTORE1 | Cooling | 23532.95068 | 28239.54082 | 1.81115 | 2.17337 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 31.20000 | 1.53444E-002 | 348.38640 | 29.99610 | 0.41145 | 0.00000 |
2 | LGSTORE1 | Heating | 43199.03596 | 51838.84315 | 1.95183 | 2.34220 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -26.20000 | 3.61342E-004 | 348.38640 | 29.99610 | 0.41145 | 0.00000 |
3 | SMSTORE1 | Cooling | 12866.14382 | 15439.37258 | 0.99022 | 1.18826 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 31.11167 | 1.53444E-002 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
4 | SMSTORE1 | Heating | 22239.34888 | 26687.21866 | 1.00481 | 1.20577 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -26.20000 | 3.61342E-004 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
5 | SMSTORE2 | Cooling | 13069.58127 | 15683.49753 | 0.97972 | 1.17566 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 25.37000 | 1.53444E-002 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
6 | SMSTORE2 | Heating | 22409.24776 | 26891.09731 | 1.01248 | 1.21498 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -26.20000 | 3.61342E-004 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
7 | SMSTORE3 | Cooling | 12976.22900 | 15571.47480 | 0.97254 | 1.16705 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 25.37000 | 1.53444E-002 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
8 | SMSTORE3 | Heating | 22465.02190 | 26958.02628 | 1.01500 | 1.21800 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -26.20000 | 3.61342E-004 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
9 | SMSTORE4 | Cooling | 13004.16612 | 15604.99934 | 0.97472 | 1.16966 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 25.37000 | 1.53444E-002 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
10 | SMSTORE4 | Heating | 22597.18353 | 27116.62024 | 1.02097 | 1.22517 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -26.20000 | 3.61342E-004 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
11 | LGSTORE2 | Cooling | 22501.69450 | 27002.03340 | 1.73173 | 2.07807 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 31.02333 | 1.53444E-002 | 348.38640 | 29.99610 | 0.41145 | 0.00000 |
12 | LGSTORE2 | Heating | 41784.29463 | 50141.15356 | 1.88795 | 2.26554 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -26.20000 | 3.61342E-004 | 348.38640 | 29.99610 | 0.41145 | 0.00000 |
13 | SMSTORE5 | Cooling | 11738.01492 | 14085.61791 | 0.87794 | 1.05352 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 27.17200 | 1.53444E-002 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
14 | SMSTORE5 | Heating | 22933.20196 | 27519.84235 | 1.03616 | 1.24339 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -26.20000 | 3.61342E-004 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
15 | SMSTORE6 | Cooling | 11654.11553 | 13984.93863 | 0.87152 | 1.04582 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 27.17200 | 1.53444E-002 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
16 | SMSTORE6 | Heating | 22912.46688 | 27494.96025 | 1.03522 | 1.24227 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -26.20000 | 3.61342E-004 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
17 | SMSTORE7 | Cooling | 11525.00917 | 13830.01101 | 0.86165 | 1.03398 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 27.17200 | 1.53444E-002 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
18 | SMSTORE7 | Heating | 23088.58777 | 27706.30532 | 1.04318 | 1.25182 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -26.20000 | 3.61342E-004 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
19 | SMSTORE8 | Cooling | 11720.10525 | 14064.12630 | 0.90187 | 1.08224 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | 30.67000 | 1.53444E-002 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
20 | SMSTORE8 | Heating | 25774.06942 | 30928.88331 | 1.16448 | 1.39737 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -26.20000 | 3.61342E-004 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC_1:1 | Cooling | Sensible | 31277.02 | 2.17337 | 2.17337 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-AC_1:1 | Heating | Sensible | 73546.52 | 2.34220 | 2.34220 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
3 | PSZ-AC_2:2 | Cooling | Sensible | 16932.70 | 1.18826 | 1.18826 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-AC_2:2 | Heating | Sensible | 37529.79 | 1.20577 | 1.20577 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
5 | PSZ-AC_3:3 | Cooling | Sensible | 16908.70 | 1.18688 | 1.18688 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
6 | PSZ-AC_3:3 | Heating | Sensible | 37730.70 | 1.21498 | 1.21498 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
7 | PSZ-AC_4:4 | Cooling | Sensible | 16949.46 | 1.19018 | 1.19018 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
8 | PSZ-AC_4:4 | Heating | Sensible | 37796.65 | 1.21800 | 1.21800 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
9 | PSZ-AC_5:5 | Cooling | Sensible | 16837.89 | 1.18144 | 1.18144 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
10 | PSZ-AC_5:5 | Heating | Sensible | 37952.94 | 1.22517 | 1.22517 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
11 | PSZ-AC_6:6 | Cooling | Sensible | 30029.50 | 2.07807 | 2.07807 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
12 | PSZ-AC_6:6 | Heating | Sensible | 71873.76 | 2.26554 | 2.26554 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
13 | PSZ-AC_7:7 | Cooling | Sensible | 15530.69 | 1.07941 | 1.07941 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
14 | PSZ-AC_7:7 | Heating | Sensible | 38350.31 | 1.24339 | 1.24339 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
15 | PSZ-AC_8:8 | Cooling | Sensible | 15432.78 | 1.07173 | 1.07173 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
16 | PSZ-AC_8:8 | Heating | Sensible | 38325.79 | 1.24227 | 1.24227 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
17 | PSZ-AC_9:9 | Cooling | Sensible | 15335.55 | 1.06413 | 1.06413 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
18 | PSZ-AC_9:9 | Heating | Sensible | 38534.06 | 1.25182 | 1.25182 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
19 | PSZ-AC_10:10 | Cooling | Sensible | 15492.06 | 1.08224 | 1.08224 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
20 | PSZ-AC_10:10 | Heating | Sensible | 41709.55 | 1.39737 | 1.39737 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:Uncontrolled | LGSTORE1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.34220 |
2 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.20577 |
3 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE2 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.21498 |
4 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.21800 |
5 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE4 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.22517 |
6 | AirTerminal:SingleDuct:Uncontrolled | LGSTORE2 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.26554 |
7 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE5 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.24339 |
8 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.24227 |
9 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE7 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.25182 |
10 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE8 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.39737 |
11 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.34220 |
12 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.34220 |
13 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.34220 |
14 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 2.34220 |
15 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.34220 |
16 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Main Design Air Flow Rate [m3/s] | 2.34220 |
17 | AirLoopHVAC | PSZ-AC_1:1 | User Heating Air Flow Ratio [] | 1.00000 |
18 | AirLoopHVAC | PSZ-AC_1:1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
19 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.20577 |
20 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.20577 |
21 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.20577 |
22 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.20577 |
23 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.20577 |
24 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Main Design Air Flow Rate [m3/s] | 1.20577 |
25 | AirLoopHVAC | PSZ-AC_2:2 | User Heating Air Flow Ratio [] | 1.00000 |
26 | AirLoopHVAC | PSZ-AC_2:2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
27 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.21498 |
28 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.21498 |
29 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.21498 |
30 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.21498 |
31 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.21498 |
32 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Main Design Air Flow Rate [m3/s] | 1.21498 |
33 | AirLoopHVAC | PSZ-AC_3:3 | User Heating Air Flow Ratio [] | 1.00000 |
34 | AirLoopHVAC | PSZ-AC_3:3 | Calculated Heating Air Flow Ratio [] | 1.00000 |
35 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.21800 |
36 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.21800 |
37 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.21800 |
38 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.21800 |
39 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.21800 |
40 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Main Design Air Flow Rate [m3/s] | 1.21800 |
41 | AirLoopHVAC | PSZ-AC_4:4 | User Heating Air Flow Ratio [] | 1.00000 |
42 | AirLoopHVAC | PSZ-AC_4:4 | Calculated Heating Air Flow Ratio [] | 1.00000 |
43 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.22517 |
44 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.22517 |
45 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.22517 |
46 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.22517 |
47 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.22517 |
48 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Main Design Air Flow Rate [m3/s] | 1.22517 |
49 | AirLoopHVAC | PSZ-AC_5:5 | User Heating Air Flow Ratio [] | 1.00000 |
50 | AirLoopHVAC | PSZ-AC_5:5 | Calculated Heating Air Flow Ratio [] | 1.00000 |
51 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.26554 |
52 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.26554 |
53 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.26554 |
54 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Heating Design Air Flow Rate [m3/s] | 2.26554 |
55 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.26554 |
56 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Main Design Air Flow Rate [m3/s] | 2.26554 |
57 | AirLoopHVAC | PSZ-AC_6:6 | User Heating Air Flow Ratio [] | 1.00000 |
58 | AirLoopHVAC | PSZ-AC_6:6 | Calculated Heating Air Flow Ratio [] | 1.00000 |
59 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.24339 |
60 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.24339 |
61 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.24339 |
62 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.24339 |
63 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.24339 |
64 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Main Design Air Flow Rate [m3/s] | 1.24339 |
65 | AirLoopHVAC | PSZ-AC_7:7 | User Heating Air Flow Ratio [] | 1.00000 |
66 | AirLoopHVAC | PSZ-AC_7:7 | Calculated Heating Air Flow Ratio [] | 1.00000 |
67 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.24227 |
68 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.24227 |
69 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.24227 |
70 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.24227 |
71 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.24227 |
72 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Main Design Air Flow Rate [m3/s] | 1.24227 |
73 | AirLoopHVAC | PSZ-AC_8:8 | User Heating Air Flow Ratio [] | 1.00000 |
74 | AirLoopHVAC | PSZ-AC_8:8 | Calculated Heating Air Flow Ratio [] | 1.00000 |
75 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.25182 |
76 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.25182 |
77 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.25182 |
78 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.25182 |
79 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.25182 |
80 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Main Design Air Flow Rate [m3/s] | 1.25182 |
81 | AirLoopHVAC | PSZ-AC_9:9 | User Heating Air Flow Ratio [] | 1.00000 |
82 | AirLoopHVAC | PSZ-AC_9:9 | Calculated Heating Air Flow Ratio [] | 1.00000 |
83 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.39737 |
84 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.39737 |
85 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.39737 |
86 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.39737 |
87 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.39737 |
88 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Main Design Air Flow Rate [m3/s] | 1.39737 |
89 | AirLoopHVAC | PSZ-AC_10:10 | User Heating Air Flow Ratio [] | 1.00000 |
90 | AirLoopHVAC | PSZ-AC_10:10 | Calculated Heating Air Flow Ratio [] | 1.00000 |
91 | AirLoopHVAC | PSZ-AC_1:1 | Design Supply Air Flow Rate [m3/s] | 2.34220 |
92 | AirLoopHVAC | PSZ-AC_2:2 | Design Supply Air Flow Rate [m3/s] | 1.20577 |
93 | AirLoopHVAC | PSZ-AC_3:3 | Design Supply Air Flow Rate [m3/s] | 1.21498 |
94 | AirLoopHVAC | PSZ-AC_4:4 | Design Supply Air Flow Rate [m3/s] | 1.21800 |
95 | AirLoopHVAC | PSZ-AC_5:5 | Design Supply Air Flow Rate [m3/s] | 1.22517 |
96 | AirLoopHVAC | PSZ-AC_6:6 | Design Supply Air Flow Rate [m3/s] | 2.26554 |
97 | AirLoopHVAC | PSZ-AC_7:7 | Design Supply Air Flow Rate [m3/s] | 1.24339 |
98 | AirLoopHVAC | PSZ-AC_8:8 | Design Supply Air Flow Rate [m3/s] | 1.24227 |
99 | AirLoopHVAC | PSZ-AC_9:9 | Design Supply Air Flow Rate [m3/s] | 1.25182 |
100 | AirLoopHVAC | PSZ-AC_10:10 | Design Supply Air Flow Rate [m3/s] | 1.39737 |
101 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.34220 |
102 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41145 |
103 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.34220 |
104 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.34220 |
105 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.34220 |
106 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 2.34220 |
107 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.34220 |
108 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.17110 |
109 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 2.34220 |
110 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 49440.21089 |
111 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 52314.18000 |
112 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 26157.09000 |
113 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 52314.18000 |
114 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.70348 |
115 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.70348 |
116 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.70348 |
117 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.70348 |
118 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 52314.18000 |
119 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 73546.52430 |
120 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
121 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
122 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.34220 |
123 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 2563.55098 |
124 | Coil:Heating:Fuel | PSZ-AC_1:1_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 73546.52430 |
125 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.20577 |
126 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20573 |
127 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.20577 |
128 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.20577 |
129 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.20577 |
130 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.20577 |
131 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.20577 |
132 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.60289 |
133 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.20577 |
134 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 25040.86243 |
135 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 26526.76000 |
136 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 13263.38000 |
137 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 26526.76000 |
138 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.70764 |
139 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.70764 |
140 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.70764 |
141 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.70764 |
142 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 26526.76000 |
143 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 37529.78777 |
144 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
145 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
146 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.20577 |
147 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1374.70685 |
148 | Coil:Heating:Fuel | PSZ-AC_2:2_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 37529.78777 |
149 | Controller:OutdoorAir | PSZ-AC_3:3_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.21498 |
150 | Controller:OutdoorAir | PSZ-AC_3:3_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20573 |
151 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.21498 |
152 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.21498 |
153 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.21498 |
154 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.21498 |
155 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.21498 |
156 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.60749 |
157 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.21498 |
158 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 25243.45587 |
159 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 26740.57000 |
160 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 13370.28500 |
161 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 26740.57000 |
162 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.70752 |
163 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.70752 |
164 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.70752 |
165 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.70752 |
166 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 26740.57000 |
167 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 37730.69918 |
168 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
169 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
170 | Fan:SystemModel | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.21498 |
171 | Fan:SystemModel | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1385.20973 |
172 | Coil:Heating:Fuel | PSZ-AC_3:3_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 37730.69918 |
173 | Controller:OutdoorAir | PSZ-AC_4:4_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.21800 |
174 | Controller:OutdoorAir | PSZ-AC_4:4_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20573 |
175 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.21800 |
176 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.21800 |
177 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.21800 |
178 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.21800 |
179 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.21800 |
180 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.60900 |
181 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.21800 |
182 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 25287.32330 |
183 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 26788.55000 |
184 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 13394.27500 |
185 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 26788.55000 |
186 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.70771 |
187 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.70771 |
188 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.70771 |
189 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.70771 |
190 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 26788.55000 |
191 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 37796.65409 |
192 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
193 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
194 | Fan:SystemModel | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.21800 |
195 | Fan:SystemModel | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1388.65762 |
196 | Coil:Heating:Fuel | PSZ-AC_4:4_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 37796.65409 |
197 | Controller:OutdoorAir | PSZ-AC_5:5_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.22517 |
198 | Controller:OutdoorAir | PSZ-AC_5:5_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20573 |
199 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.22517 |
200 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.22517 |
201 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.22517 |
202 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.22517 |
203 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.22517 |
204 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.61259 |
205 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.22517 |
206 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 25488.46017 |
207 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 26997.62000 |
208 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 13498.81000 |
209 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 26997.62000 |
210 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.70719 |
211 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.70719 |
212 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.70719 |
213 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.70719 |
214 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 26997.62000 |
215 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 37952.94114 |
216 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
217 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
218 | Fan:SystemModel | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.22517 |
219 | Fan:SystemModel | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1396.82794 |
220 | Coil:Heating:Fuel | PSZ-AC_5:5_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 37952.94114 |
221 | Controller:OutdoorAir | PSZ-AC_6:6_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.26554 |
222 | Controller:OutdoorAir | PSZ-AC_6:6_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41145 |
223 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.26554 |
224 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.26554 |
225 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.26554 |
226 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 2.26554 |
227 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.26554 |
228 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.13277 |
229 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 2.26554 |
230 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 48325.36004 |
231 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 51097.51000 |
232 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 25548.75500 |
233 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 51097.51000 |
234 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.70084 |
235 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.70084 |
236 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.70084 |
237 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.70084 |
238 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 51097.51000 |
239 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 71873.75749 |
240 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
241 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
242 | Fan:SystemModel | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.26554 |
243 | Fan:SystemModel | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 2479.64892 |
244 | Coil:Heating:Fuel | PSZ-AC_6:6_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 71873.75749 |
245 | Controller:OutdoorAir | PSZ-AC_7:7_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.24339 |
246 | Controller:OutdoorAir | PSZ-AC_7:7_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20573 |
247 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.24339 |
248 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.24339 |
249 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.24339 |
250 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.24339 |
251 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.24339 |
252 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.62170 |
253 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.24339 |
254 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 26538.96996 |
255 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 28060.19000 |
256 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 14030.09500 |
257 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 28060.19000 |
258 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.70068 |
259 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.70068 |
260 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.70068 |
261 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.70068 |
262 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 28060.19000 |
263 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 38350.30579 |
264 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
265 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
266 | Fan:SystemModel | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.24339 |
267 | Fan:SystemModel | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1417.60272 |
268 | Coil:Heating:Fuel | PSZ-AC_7:7_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 38350.30579 |
269 | Controller:OutdoorAir | PSZ-AC_8:8_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.24227 |
270 | Controller:OutdoorAir | PSZ-AC_8:8_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20573 |
271 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.24227 |
272 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.24227 |
273 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.24227 |
274 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.24227 |
275 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.24227 |
276 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.62114 |
277 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.24227 |
278 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 26569.30594 |
279 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 28088.22000 |
280 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 14044.11000 |
281 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 28088.22000 |
282 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.70017 |
283 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.70017 |
284 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.70017 |
285 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.70017 |
286 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 28088.22000 |
287 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 38325.78591 |
288 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
289 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
290 | Fan:SystemModel | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.24227 |
291 | Fan:SystemModel | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1416.32090 |
292 | Coil:Heating:Fuel | PSZ-AC_8:8_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 38325.78591 |
293 | Controller:OutdoorAir | PSZ-AC_9:9_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.25182 |
294 | Controller:OutdoorAir | PSZ-AC_9:9_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20573 |
295 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.25182 |
296 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.25182 |
297 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.25182 |
298 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.25182 |
299 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.25182 |
300 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.62591 |
301 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.25182 |
302 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 26828.45138 |
303 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 28358.19000 |
304 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 14179.09500 |
305 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 28358.19000 |
306 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.69966 |
307 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.69965 |
308 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.69965 |
309 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.69965 |
310 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 28358.19000 |
311 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 38534.05523 |
312 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
313 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
314 | Fan:SystemModel | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.25182 |
315 | Fan:SystemModel | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1427.20851 |
316 | Coil:Heating:Fuel | PSZ-AC_9:9_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 38534.05523 |
317 | Controller:OutdoorAir | PSZ-AC_10:10_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.39737 |
318 | Controller:OutdoorAir | PSZ-AC_10:10_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20573 |
319 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.39737 |
320 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.39737 |
321 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.39737 |
322 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.39737 |
323 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.39737 |
324 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.69869 |
325 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.39737 |
326 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 29841.37687 |
327 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 31549.03000 |
328 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 15774.51500 |
329 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 31549.03000 |
330 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.70056 |
331 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.70056 |
332 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.70056 |
333 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.70056 |
334 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 31549.03000 |
335 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 41709.54617 |
336 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
337 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
338 | Fan:SystemModel | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.39737 |
339 | Fan:SystemModel | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1593.15728 |
340 | Coil:Heating:Fuel | PSZ-AC_10:10_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 41709.54617 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | 50470.1 | 9.94 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | 25577.7 | 31.07 | |||
3 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | 25784.2 | 41.27 | |||
4 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | 25829.8 | 51.64 | |||
5 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | 26033.2 | 61.70 | |||
6 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | 49313.4 | 40.97 | |||
7 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | 27081.0 | 89.06 | |||
8 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | 27109.9 | 99.48 | |||
9 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | 27372.3 | 109.03 | |||
10 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | 30448.6 | 108.46 |
Zone Name | # Surfaces | |
1 | LGSTORE1 | 15 |
2 | SMSTORE1 | 11 |
3 | SMSTORE2 | 11 |
4 | SMSTORE3 | 11 |
5 | SMSTORE4 | 11 |
6 | LGSTORE2 | 15 |
7 | SMSTORE5 | 11 |
8 | SMSTORE6 | 11 |
9 | SMSTORE7 | 11 |
10 | SMSTORE8 | 11 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | LGSTORE1_WALL_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | LGSTORE1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 71.15 | 78.94 | 71.15 | 0.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | LGSTORE1_WALL_3_DOOR_1 | Door | LGSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
4 | LGSTORE1_WALL_3_DOOR_2 | Door | LGSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
5 | LGSTORE1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
6 | LGSTORE1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 58.20 | 78.94 | 58.20 | 180.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
7 | LGSTORE1_WALL_1_WINDOW_1 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.47_SHGC_0.4 | N/A | 2.672 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
8 | LGSTORE1_WALL_1_WINDOW_2 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.47_SHGC_0.4 | N/A | 2.672 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
9 | LGSTORE1_WALL_1_WINDOW_3 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.47_SHGC_0.4 | N/A | 2.672 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
10 | LGSTORE1_WALL_1_WINDOW_4 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.47_SHGC_0.4 | N/A | 2.672 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
11 | LGSTORE1_WALL_1_DOOR_1 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.47_SHGC_0.4 | N/A | 2.672 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
12 | LGSTORE1_WALL_1_DOOR_2 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.47_SHGC_0.4 | N/A | 2.672 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
13 | LGSTORE1_FLOOR | Floor | CTF - ConductionTransferFunction | LGSTORE1_FLOOR_FFACTOR | 0.146 | 0.141 | 348.39 | 348.39 | 348.39 | 270.00 | 180.00 | 22.86 | 15.24 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | LGSTORE1_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 348.39 | 348.39 | 348.39 | 270.00 | 0.00 | 22.86 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
15 | LGSTORE1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 696.77 | 696.77 | 696.77 | 0.00 | 90.00 | 696.77 | 1.00 | 0.00 | LGSTORE1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
16 | SMSTORE1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 29.10 | 39.47 | 29.10 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
17 | SMSTORE1_WALL_1_WINDOW_1 | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.47_SHGC_0.4 | N/A | 2.672 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
18 | SMSTORE1_WALL_1_WINDOW_2 | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.47_SHGC_0.4 | N/A | 2.672 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
19 | SMSTORE1_WALL_1_DOOR | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.47_SHGC_0.4 | N/A | 2.672 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
20 | SMSTORE1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | SMSTORE1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 35.57 | 39.47 | 35.57 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | SMSTORE1_WALL_3_DOOR | Door | SMSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
23 | SMSTORE1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE2_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
24 | SMSTORE1_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE1_FLOOR_FFACTOR | 8.283E-002 | 8.119E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | SMSTORE1_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
26 | SMSTORE1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
27 | SMSTORE2_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 29.12 | 39.47 | 29.12 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | SMSTORE2_WALL_1_WINDOW_1 | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.47_SHGC_0.4 | N/A | 2.672 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
29 | SMSTORE2_WALL_1_WINDOW_2 | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.47_SHGC_0.4 | N/A | 2.672 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
30 | SMSTORE2_WALL_1_DOOR | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.47_SHGC_0.4 | N/A | 2.672 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
31 | SMSTORE2_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
32 | SMSTORE2_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | SMSTORE2_WALL_3_DOOR | Door | SMSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
34 | SMSTORE2_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE3_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | SMSTORE2_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE2_FLOOR_FFACTOR | 8.283E-002 | 8.119E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
36 | SMSTORE2_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
37 | SMSTORE2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
38 | SMSTORE3_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 29.12 | 39.47 | 29.12 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
39 | SMSTORE3_WALL_1_WINDOW_1 | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.47_SHGC_0.4 | N/A | 2.672 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
40 | SMSTORE3_WALL_1_WINDOW_2 | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.47_SHGC_0.4 | N/A | 2.672 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
41 | SMSTORE3_WALL_1_DOOR | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.47_SHGC_0.4 | N/A | 2.672 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
42 | SMSTORE3_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE2_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | SMSTORE3_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | SMSTORE3_WALL_3_DOOR | Door | SMSTORE3_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
45 | SMSTORE3_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE4_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | SMSTORE3_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE3_FLOOR_FFACTOR | 8.283E-002 | 8.119E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
47 | SMSTORE3_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
48 | SMSTORE3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
49 | SMSTORE4_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 29.12 | 39.47 | 29.12 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | SMSTORE4_WALL_1_WINDOW_1 | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.47_SHGC_0.4 | N/A | 2.672 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
51 | SMSTORE4_WALL_1_WINDOW_2 | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.47_SHGC_0.4 | N/A | 2.672 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
52 | SMSTORE4_WALL_1_DOOR | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.47_SHGC_0.4 | N/A | 2.672 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | SMSTORE4_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE3_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | SMSTORE4_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | SMSTORE4_WALL_3_DOOR | Door | SMSTORE4_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | SMSTORE4_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE2_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | SMSTORE4_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE4_FLOOR_FFACTOR | 8.283E-002 | 8.119E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | SMSTORE4_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | SMSTORE4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | LGSTORE2_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE4_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | LGSTORE2_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 71.19 | 78.94 | 71.19 | 0.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
62 | LGSTORE2_WALL_3_DOOR_1 | Door | LGSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
63 | LGSTORE2_WALL_3_DOOR_2 | Door | LGSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
64 | LGSTORE2_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE5_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | LGSTORE2_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 58.24 | 78.94 | 58.24 | 180.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
66 | LGSTORE2_WALL_1_WINDOW_1 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.47_SHGC_0.4 | N/A | 2.672 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | LGSTORE2_WALL_1_WINDOW_2 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.47_SHGC_0.4 | N/A | 2.672 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | LGSTORE2_WALL_1_WINDOW_3 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.47_SHGC_0.4 | N/A | 2.672 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | LGSTORE2_WALL_1_WINDOW_4 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.47_SHGC_0.4 | N/A | 2.672 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | LGSTORE2_WALL_1_DOOR_1 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.47_SHGC_0.4 | N/A | 2.672 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
71 | LGSTORE2_WALL_1_DOOR_2 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.47_SHGC_0.4 | N/A | 2.672 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
72 | LGSTORE2_FLOOR | Floor | CTF - ConductionTransferFunction | LGSTORE2_FLOOR_FFACTOR | 8.283E-002 | 8.119E-002 | 348.39 | 348.39 | 348.39 | 270.00 | 180.00 | 22.86 | 15.24 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
73 | LGSTORE2_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 348.39 | 348.39 | 348.39 | 270.00 | 0.00 | 22.86 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
74 | LGSTORE2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 696.77 | 696.77 | 696.77 | 0.00 | 90.00 | 696.77 | 1.00 | 0.00 | LGSTORE2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
75 | SMSTORE5_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 29.12 | 39.47 | 29.12 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | SMSTORE5_WALL_1_WINDOW_1 | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.47_SHGC_0.4 | N/A | 2.672 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
77 | SMSTORE5_WALL_1_WINDOW_2 | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.47_SHGC_0.4 | N/A | 2.672 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | SMSTORE5_WALL_1_DOOR | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.47_SHGC_0.4 | N/A | 2.672 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
79 | SMSTORE5_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE2_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | SMSTORE5_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | SMSTORE5_WALL_3_DOOR | Door | SMSTORE5_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
82 | SMSTORE5_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE6_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
83 | SMSTORE5_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE5_FLOOR_FFACTOR | 8.283E-002 | 8.119E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
84 | SMSTORE5_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
85 | SMSTORE5_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE5_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
86 | SMSTORE6_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 29.12 | 39.47 | 29.12 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | SMSTORE6_WALL_1_WINDOW_1 | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.47_SHGC_0.4 | N/A | 2.672 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
88 | SMSTORE6_WALL_1_WINDOW_2 | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.47_SHGC_0.4 | N/A | 2.672 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
89 | SMSTORE6_WALL_1_DOOR | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.47_SHGC_0.4 | N/A | 2.672 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
90 | SMSTORE6_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE5_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
91 | SMSTORE6_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
92 | SMSTORE6_WALL_3_DOOR | Door | SMSTORE6_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
93 | SMSTORE6_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE7_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | SMSTORE6_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE6_FLOOR_FFACTOR | 8.283E-002 | 8.119E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
95 | SMSTORE6_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
96 | SMSTORE6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
97 | SMSTORE7_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 29.12 | 39.47 | 29.12 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | SMSTORE7_WALL_1_WINDOW_1 | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.47_SHGC_0.4 | N/A | 2.672 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
99 | SMSTORE7_WALL_1_WINDOW_2 | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.47_SHGC_0.4 | N/A | 2.672 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
100 | SMSTORE7_WALL_1_DOOR | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.47_SHGC_0.4 | N/A | 2.672 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
101 | SMSTORE7_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE6_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
102 | SMSTORE7_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 35.59 | 39.47 | 35.59 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | SMSTORE7_WALL_3_DOOR | Door | SMSTORE7_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
104 | SMSTORE7_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE8_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | SMSTORE7_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE7_FLOOR_FFACTOR | 8.283E-002 | 8.119E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
106 | SMSTORE7_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
107 | SMSTORE7_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE7_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
108 | SMSTORE8_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 29.12 | 39.47 | 29.12 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | SMSTORE8_WALL_1_WINDOW_1 | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.47_SHGC_0.4 | N/A | 2.672 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
110 | SMSTORE8_WALL_1_WINDOW_2 | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.47_SHGC_0.4 | N/A | 2.672 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
111 | SMSTORE8_WALL_1_DOOR | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.47_SHGC_0.4 | N/A | 2.672 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
112 | SMSTORE8_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE7_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
113 | SMSTORE8_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | SMSTORE8_WALL_3_DOOR | Door | SMSTORE8_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
115 | SMSTORE8_WALL_4 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | SMSTORE8_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE8_FLOOR_FFACTOR | 0.211 | 0.201 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | SMSTORE8_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | SMSTORE8_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE8_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1 |
2 | VETERANS DAY | Holiday | InputFile | 11/11 | 1 |
3 | CHRISTMAS | Holiday | InputFile | 12/25 | 1 |
4 | INDEPENDENCE DAY | Holiday | InputFile | 07/04 | 1 |
5 | MLK DAY | Holiday | InputFile | 01/16 | 1 |
6 | PRESIDENTS DAY | Holiday | InputFile | 02/20 | 1 |
7 | MEMORIAL DAY | Holiday | InputFile | 05/29 | 1 |
8 | LABOR DAY | Holiday | InputFile | 09/04 | 1 |
9 | COLUMBUS DAY | Holiday | InputFile | 10/09 | 1 |
10 | THANKSGIVING | Holiday | InputFile | 11/23 | 1 |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
NumberofWarmupDays | |
1 | 11 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | LGSTORE1 | RunPeriod: RUNPERIOD 1 | 4.9800631144E-002 | 0.2754758933 | Pass | Pass | 0.3429860015 | 3.0639913653 | Pass | Pass |
2 | SMSTORE1 | RunPeriod: RUNPERIOD 1 | 5.3917932335E-002 | 0.2187283045 | Pass | Pass | 9.8332040248E-002 | 0.3561191711 | Pass | Pass |
3 | SMSTORE2 | RunPeriod: RUNPERIOD 1 | 6.1195123118E-002 | 0.3056920240 | Pass | Pass | 6.5813615019E-002 | 0.3784361020 | Pass | Pass |
4 | SMSTORE3 | RunPeriod: RUNPERIOD 1 | 6.9193059013E-002 | 0.3520075852 | Pass | Pass | 6.2712073642E-002 | 0.3696846028 | Pass | Pass |
5 | SMSTORE4 | RunPeriod: RUNPERIOD 1 | 7.4262633546E-002 | 0.3773862735 | Pass | Pass | 5.9161997592E-002 | 0.3528422395 | Pass | Pass |
6 | LGSTORE2 | RunPeriod: RUNPERIOD 1 | 9.0503699453E-002 | 0.4450562897 | Pass | Pass | 2.5863800136E-002 | 9.4367296765E-002 | Pass | Pass |
7 | SMSTORE5 | RunPeriod: RUNPERIOD 1 | 8.8968797895E-002 | 0.4292377686 | Pass | Pass | 2.6133665469E-002 | 8.9153751058E-002 | Pass | Pass |
8 | SMSTORE6 | RunPeriod: RUNPERIOD 1 | 8.9336758248E-002 | 0.4107149653 | Pass | Pass | 2.3780154677E-002 | 8.5022745833E-002 | Pass | Pass |
9 | SMSTORE7 | RunPeriod: RUNPERIOD 1 | 9.2241270358E-002 | 0.4132099524 | Pass | Pass | 2.4060417298E-002 | 8.3883516846E-002 | Pass | Pass |
10 | SMSTORE8 | RunPeriod: RUNPERIOD 1 | 0.1988019041 | 0.4504052006 | Pass | Pass | 0.4040132253 | 1.8908183836 | Pass | Pass |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2020-06-03 19:18:54
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | -26.20 | 0.00 | -26.20 | Wetbulb [C] | 5.70 | 310.00 |
ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 31.20 | 10.60 | 23.10 | Wetbulb [C] | 6.70 | 200.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2020-06-03 19:18:54
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_2 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE1_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 78.94 | 71.15 | 0.00 | 90.00 | N |
LGSTORE1_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 78.94 | 58.20 | 180.00 | 90.00 | S |
LGSTORE1_ROOF | NONRES_ROOF | 0.23 | 0.273 | 0.283 | 348.39 | 348.39 | 270.00 | 0.00 | |
SMSTORE1_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 29.10 | 180.00 | 90.00 | S |
SMSTORE1_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 35.57 | 0.00 | 90.00 | N |
SMSTORE1_ROOF | NONRES_ROOF | 0.23 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE2_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 29.12 | 180.00 | 90.00 | S |
SMSTORE2_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE2_ROOF | NONRES_ROOF | 0.23 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE3_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 29.12 | 180.00 | 90.00 | S |
SMSTORE3_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE3_ROOF | NONRES_ROOF | 0.23 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE4_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 29.12 | 180.00 | 90.00 | S |
SMSTORE4_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE4_ROOF | NONRES_ROOF | 0.23 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
LGSTORE2_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 78.94 | 71.19 | 0.00 | 90.00 | N |
LGSTORE2_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 78.94 | 58.24 | 180.00 | 90.00 | S |
LGSTORE2_ROOF | NONRES_ROOF | 0.23 | 0.273 | 0.283 | 348.39 | 348.39 | 270.00 | 0.00 | |
SMSTORE5_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 29.12 | 180.00 | 90.00 | S |
SMSTORE5_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE5_ROOF | NONRES_ROOF | 0.23 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE6_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 29.12 | 180.00 | 90.00 | S |
SMSTORE6_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE6_ROOF | NONRES_ROOF | 0.23 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE7_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 29.12 | 180.00 | 90.00 | S |
SMSTORE7_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE7_ROOF | NONRES_ROOF | 0.23 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE8_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 29.12 | 180.00 | 90.00 | S |
SMSTORE8_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE8_WALL_4 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE8_ROOF | NONRES_ROOF | 0.23 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
LGSTORE1_FLOOR | LGSTORE1_FLOOR_FFACTOR | 1.00 | 0.146 | 348.39 | 348.39 | 270.00 | 180.00 | ||
SMSTORE1_FLOOR | SMSTORE1_FLOOR_FFACTOR | 1.00 | 0.083 | 174.19 | 174.19 | 270.00 | 180.00 | ||
SMSTORE2_FLOOR | SMSTORE2_FLOOR_FFACTOR | 1.00 | 0.083 | 174.19 | 174.19 | 270.00 | 180.00 | ||
SMSTORE3_FLOOR | SMSTORE3_FLOOR_FFACTOR | 1.00 | 0.083 | 174.19 | 174.19 | 270.00 | 180.00 | ||
SMSTORE4_FLOOR | SMSTORE4_FLOOR_FFACTOR | 1.00 | 0.083 | 174.19 | 174.19 | 270.00 | 180.00 | ||
LGSTORE2_FLOOR | LGSTORE2_FLOOR_FFACTOR | 1.00 | 0.083 | 348.39 | 348.39 | 270.00 | 180.00 | ||
SMSTORE5_FLOOR | SMSTORE5_FLOOR_FFACTOR | 1.00 | 0.083 | 174.19 | 174.19 | 270.00 | 180.00 | ||
SMSTORE6_FLOOR | SMSTORE6_FLOOR_FFACTOR | 1.00 | 0.083 | 174.19 | 174.19 | 270.00 | 180.00 | ||
SMSTORE7_FLOOR | SMSTORE7_FLOOR_FFACTOR | 1.00 | 0.083 | 174.19 | 174.19 | 270.00 | 180.00 | ||
SMSTORE8_FLOOR | SMSTORE8_FLOOR_FFACTOR | 1.00 | 0.211 | 174.19 | 174.19 | 270.00 | 180.00 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.47_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.672 | 0.394 | 0.401 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE1_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.47_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.672 | 0.394 | 0.401 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE1_WALL_1_WINDOW_3 | NONRESWINDOW_U_0.47_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.672 | 0.394 | 0.401 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE1_WALL_1_WINDOW_4 | NONRESWINDOW_U_0.47_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.672 | 0.394 | 0.401 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE1_WALL_1_DOOR_1 | NONRESWINDOW_U_0.47_SHGC_0.4 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.672 | 0.394 | 0.401 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE1_WALL_1_DOOR_2 | NONRESWINDOW_U_0.47_SHGC_0.4 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.672 | 0.394 | 0.401 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE1_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.47_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.672 | 0.394 | 0.401 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE1_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.47_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.672 | 0.394 | 0.401 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE1_WALL_1_DOOR | NONRESWINDOW_U_0.47_SHGC_0.4 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.672 | 0.394 | 0.401 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE2_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.47_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.672 | 0.394 | 0.401 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE2_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.47_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.672 | 0.394 | 0.401 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE2_WALL_1_DOOR | NONRESWINDOW_U_0.47_SHGC_0.4 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.672 | 0.394 | 0.401 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE3_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.47_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.672 | 0.394 | 0.401 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE3_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.47_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.672 | 0.394 | 0.401 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE3_WALL_1_DOOR | NONRESWINDOW_U_0.47_SHGC_0.4 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.672 | 0.394 | 0.401 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE4_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.47_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.672 | 0.394 | 0.401 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE4_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.47_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.672 | 0.394 | 0.401 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE4_WALL_1_DOOR | NONRESWINDOW_U_0.47_SHGC_0.4 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.672 | 0.394 | 0.401 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE2_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.47_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.672 | 0.394 | 0.401 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE2_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.47_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.672 | 0.394 | 0.401 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE2_WALL_1_WINDOW_3 | NONRESWINDOW_U_0.47_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.672 | 0.394 | 0.401 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE2_WALL_1_WINDOW_4 | NONRESWINDOW_U_0.47_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.672 | 0.394 | 0.401 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE2_WALL_1_DOOR_1 | NONRESWINDOW_U_0.47_SHGC_0.4 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.672 | 0.394 | 0.401 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE2_WALL_1_DOOR_2 | NONRESWINDOW_U_0.47_SHGC_0.4 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.672 | 0.394 | 0.401 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE5_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.47_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.672 | 0.394 | 0.401 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE5_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.47_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.672 | 0.394 | 0.401 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE5_WALL_1_DOOR | NONRESWINDOW_U_0.47_SHGC_0.4 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.672 | 0.394 | 0.401 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE6_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.47_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.672 | 0.394 | 0.401 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE6_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.47_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.672 | 0.394 | 0.401 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE6_WALL_1_DOOR | NONRESWINDOW_U_0.47_SHGC_0.4 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.672 | 0.394 | 0.401 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE7_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.47_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.672 | 0.394 | 0.401 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE7_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.47_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.672 | 0.394 | 0.401 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE7_WALL_1_DOOR | NONRESWINDOW_U_0.47_SHGC_0.4 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.672 | 0.394 | 0.401 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE8_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.47_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.672 | 0.394 | 0.401 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE8_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.47_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.672 | 0.394 | 0.401 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE8_WALL_1_DOOR | NONRESWINDOW_U_0.47_SHGC_0.4 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.672 | 0.394 | 0.401 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | ||
Total or Average | 124.29 | 2.672 | 0.394 | 0.401 | ||||||||||||
North Total or Average | 0.00 | - | - | - | ||||||||||||
Non-North Total or Average | 124.29 | 2.672 | 0.394 | 0.401 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
LGSTORE1_WALL_3_DOOR_1 | SWINGING DOOR_CON | 2.492 | 3.975 | 3.90 | LGSTORE1_WALL_3 |
LGSTORE1_WALL_3_DOOR_2 | SWINGING DOOR_CON | 2.492 | 3.975 | 3.90 | LGSTORE1_WALL_3 |
SMSTORE1_WALL_3_DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 3.90 | SMSTORE1_WALL_3 |
SMSTORE2_WALL_3_DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 3.88 | SMSTORE2_WALL_3 |
SMSTORE3_WALL_3_DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 3.88 | SMSTORE3_WALL_3 |
SMSTORE4_WALL_3_DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 3.88 | SMSTORE4_WALL_3 |
LGSTORE2_WALL_3_DOOR_1 | SWINGING DOOR_CON | 2.492 | 3.975 | 3.88 | LGSTORE2_WALL_3 |
LGSTORE2_WALL_3_DOOR_2 | SWINGING DOOR_CON | 2.492 | 3.975 | 3.88 | LGSTORE2_WALL_3 |
SMSTORE5_WALL_3_DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 3.88 | SMSTORE5_WALL_3 |
SMSTORE6_WALL_3_DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 3.88 | SMSTORE6_WALL_3 |
SMSTORE7_WALL_3_DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 3.88 | SMSTORE7_WALL_3 |
SMSTORE8_WALL_3_DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 3.88 | SMSTORE8_WALL_3 |
Report: Shading Summary
For: Entire Facility
Timestamp: 2020-06-03 19:18:54
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
LGSTORE1_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_DOOR_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_DOOR_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_DOOR_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_DOOR_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2020-06-03 19:18:54
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
LGSTORE1_LIGHTS | LGSTORE1 | 18.3225 | 348.39 | 6383.30 | LightsWired | TYPE1_LIGHT_SCH | 98.40 | 168.00 | 98.38 | 0.0000 | Y | 117.88 |
LGSTORE1_LIGHTS_ALLOWANCE | LGSTORE1 | 6.6413 | 348.39 | 2313.75 | LightsWired | TYPE1_LIGHT_SCH | 98.40 | 168.00 | 98.38 | 0.0000 | Y | 42.73 |
SMSTORE1_LIGHTS | SMSTORE1 | 18.3225 | 174.19 | 3191.65 | LightsWired | TYPE1_LIGHT_SCH | 98.40 | 168.00 | 98.38 | 0.0000 | Y | 58.94 |
SMSTORE1_LIGHTS_ALLOWANCE | SMSTORE1 | 9.5153 | 174.19 | 1657.50 | LightsWired | TYPE1_LIGHT_SCH | 98.40 | 168.00 | 98.38 | 0.0000 | Y | 30.61 |
SMSTORE2_LIGHTS | SMSTORE2 | 18.3225 | 174.19 | 3191.65 | LightsWired | TYPE2_LIGHT_SCH | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 46.71 |
SMSTORE2_LIGHTS_ALLOWANCE | SMSTORE2 | 7.3625 | 174.19 | 1282.50 | LightsWired | TYPE2_LIGHT_SCH | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 18.77 |
SMSTORE3_LIGHTS | SMSTORE3 | 18.3225 | 174.19 | 3191.65 | LightsWired | TYPE2_LIGHT_SCH | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 46.71 |
SMSTORE3_LIGHTS_ALLOWANCE | SMSTORE3 | 7.3625 | 174.19 | 1282.50 | LightsWired | TYPE2_LIGHT_SCH | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 18.77 |
SMSTORE4_LIGHTS | SMSTORE4 | 18.3225 | 174.19 | 3191.65 | LightsWired | TYPE2_LIGHT_SCH | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 46.71 |
SMSTORE4_LIGHTS_ALLOWANCE | SMSTORE4 | 7.3625 | 174.19 | 1282.50 | LightsWired | TYPE2_LIGHT_SCH | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 18.77 |
LGSTORE2_LIGHTS | LGSTORE2 | 18.3225 | 348.39 | 6383.30 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 168.00 | 71.66 | 0.0000 | Y | 85.86 |
LGSTORE2_LIGHTS_ALLOWANCE | LGSTORE2 | 0.0000 | 348.39 | 0.00 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE5_LIGHTS | SMSTORE5 | 18.3225 | 174.19 | 3191.65 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 168.00 | 71.66 | 0.0000 | Y | 42.93 |
SMSTORE5_LIGHTS_ALLOWANCE | SMSTORE5 | 0.0000 | 174.19 | 0.00 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE6_LIGHTS | SMSTORE6 | 18.3225 | 174.19 | 3191.65 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 168.00 | 71.66 | 0.0000 | Y | 42.93 |
SMSTORE6_LIGHTS_ALLOWANCE | SMSTORE6 | 0.0000 | 174.19 | 0.00 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE7_LIGHTS | SMSTORE7 | 18.3225 | 174.19 | 3191.65 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 168.00 | 71.66 | 0.0000 | Y | 42.93 |
SMSTORE7_LIGHTS_ALLOWANCE | SMSTORE7 | 0.0000 | 174.19 | 0.00 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE8_LIGHTS | SMSTORE8 | 18.3225 | 174.19 | 3191.65 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 168.00 | 71.66 | 0.0000 | Y | 42.93 |
SMSTORE8_LIGHTS_ALLOWANCE | SMSTORE8 | 0.0000 | 174.19 | 0.00 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
Interior Lighting Total | 11.0315 | 4180.64 | 46118.53 | 704.17 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS | 7048.38 | AstronomicalClock | - | 83.63 | 83.63 | 110.65 | |
Exterior Lighting Total | 7048.38 | 110.65 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2020-06-03 19:18:54
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 52314.18 | 36801.98 | 15512.20 | 0.70 | 3.30 | |||
PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 26526.76 | 18771.40 | 7755.36 | 0.71 | 3.50 | |||
PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 26740.57 | 18919.49 | 7821.08 | 0.71 | 3.50 | |||
PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 26788.55 | 18958.52 | 7830.03 | 0.71 | 3.50 | |||
PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 26997.62 | 19092.45 | 7905.17 | 0.71 | 3.50 | |||
PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 51097.51 | 35811.18 | 15286.33 | 0.70 | 3.30 | |||
PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 28060.19 | 19661.21 | 8398.98 | 0.70 | 3.50 | |||
PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 28088.22 | 19666.53 | 8421.69 | 0.70 | 3.50 | |||
PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 28358.19 | 19840.81 | 8517.38 | 0.70 | 3.50 | |||
PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 31549.03 | 22101.99 | 9447.04 | 0.70 | 3.50 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | 50470.1 | 9.94 | ||||
PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | 25577.7 | 31.07 | ||||
PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | 25784.2 | 41.27 | ||||
PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | 25829.8 | 51.64 | ||||
PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | 26033.2 | 61.70 | ||||
PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | 49313.4 | 40.97 | ||||
PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | 27081.0 | 89.06 | ||||
PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | 27109.9 | 99.48 | ||||
PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | 27372.3 | 109.03 | ||||
PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | 30448.6 | 108.46 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
PSZ-AC_1:1_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 73546.52 | 0.80 | |
PSZ-AC_2:2_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 37529.79 | 0.80 | |
PSZ-AC_3:3_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 37730.70 | 0.80 | |
PSZ-AC_4:4_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 37796.65 | 0.80 | |
PSZ-AC_5:5_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 37952.94 | 0.80 | |
PSZ-AC_6:6_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 71873.76 | 0.80 | |
PSZ-AC_7:7_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 38350.31 | 0.80 | |
PSZ-AC_8:8_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 38325.79 | 0.80 | |
PSZ-AC_9:9_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 38534.06 | 0.80 | |
PSZ-AC_10:10_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 41709.55 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.57 | 622.50 | 2.34 | 2563.55 | 1094.51 | 1.00 | 1.26 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 |
PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.55 | 622.50 | 1.21 | 1374.71 | 1140.11 | 1.00 | 1.32 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 |
PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.55 | 622.50 | 1.21 | 1385.21 | 1140.11 | 1.00 | 1.32 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 |
PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.55 | 622.50 | 1.22 | 1388.66 | 1140.11 | 1.00 | 1.32 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 |
PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.55 | 622.50 | 1.23 | 1396.83 | 1140.11 | 1.00 | 1.32 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 |
PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.57 | 622.50 | 2.27 | 2479.65 | 1094.51 | 1.00 | 1.27 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 |
PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.55 | 622.50 | 1.24 | 1417.60 | 1140.11 | 1.00 | 1.31 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 |
PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.55 | 622.50 | 1.24 | 1416.32 | 1140.11 | 1.00 | 1.31 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 |
PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.55 | 622.50 | 1.25 | 1427.21 | 1140.11 | 1.00 | 1.31 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 |
PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.55 | 622.50 | 1.40 | 1593.16 | 1140.11 | 1.00 | 1.29 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
GAS TANK1 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK2 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK3 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK4 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK5 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK6 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK7 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:18:54
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
LGSTORE1 | 23532.95 | 28239.54 | 81.06 | 1.811 | 2.173 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 23.89 | 23.88 | 0.00996 | 31.20 | 0.01534 | 0.411 | 0.00 |
SMSTORE1 | 12866.14 | 15439.37 | 88.63 | 0.990 | 1.188 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 23.89 | 23.88 | 0.00994 | 31.11 | 0.01534 | 0.206 | 0.00 |
SMSTORE2 | 13069.58 | 15683.50 | 90.04 | 0.980 | 1.176 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 23.89 | 23.89 | 0.00904 | 25.37 | 0.01534 | 0.206 | 0.00 |
SMSTORE3 | 12976.23 | 15571.47 | 89.39 | 0.973 | 1.167 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 23.89 | 23.89 | 0.00905 | 25.37 | 0.01534 | 0.206 | 0.00 |
SMSTORE4 | 13004.17 | 15605.00 | 89.58 | 0.975 | 1.170 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 23.89 | 23.89 | 0.00905 | 25.37 | 0.01534 | 0.206 | 0.00 |
LGSTORE2 | 22501.69 | 27002.03 | 77.51 | 1.732 | 2.078 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 23.89 | 23.88 | 0.00998 | 31.02 | 0.01534 | 0.411 | 0.00 |
SMSTORE5 | 11738.01 | 14085.62 | 80.86 | 0.878 | 1.054 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 23.89 | 23.89 | 0.00915 | 27.17 | 0.01534 | 0.206 | 0.00 |
SMSTORE6 | 11654.12 | 13984.94 | 80.28 | 0.872 | 1.046 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 23.89 | 23.89 | 0.00915 | 27.17 | 0.01534 | 0.206 | 0.00 |
SMSTORE7 | 11525.01 | 13830.01 | 79.39 | 0.862 | 1.034 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 23.89 | 23.89 | 0.00917 | 27.17 | 0.01534 | 0.206 | 0.00 |
SMSTORE8 | 11720.11 | 14064.13 | 80.74 | 0.902 | 1.082 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | 23.89 | 23.88 | 0.01010 | 30.67 | 0.01534 | 0.206 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
LGSTORE1 | 43199.04 | 51838.84 | 148.80 | 1.952 | 2.342 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00647 | -26.20 | 0.00036 | 0.411 | 0.00 |
SMSTORE1 | 22239.35 | 26687.22 | 153.20 | 1.005 | 1.206 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00637 | -26.20 | 0.00036 | 0.206 | 0.00 |
SMSTORE2 | 22409.25 | 26891.10 | 154.38 | 1.012 | 1.215 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00638 | -26.20 | 0.00036 | 0.206 | 0.00 |
SMSTORE3 | 22465.02 | 26958.03 | 154.76 | 1.015 | 1.218 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00639 | -26.20 | 0.00036 | 0.206 | 0.00 |
SMSTORE4 | 22597.18 | 27116.62 | 155.67 | 1.021 | 1.225 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00639 | -26.20 | 0.00036 | 0.206 | 0.00 |
LGSTORE2 | 41784.29 | 50141.15 | 143.92 | 1.888 | 2.266 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00646 | -26.20 | 0.00036 | 0.411 | 0.00 |
SMSTORE5 | 22933.20 | 27519.84 | 157.98 | 1.036 | 1.243 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00641 | -26.20 | 0.00036 | 0.206 | 0.00 |
SMSTORE6 | 22912.47 | 27494.96 | 157.84 | 1.035 | 1.242 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00641 | -26.20 | 0.00036 | 0.206 | 0.00 |
SMSTORE7 | 23088.59 | 27706.31 | 159.06 | 1.043 | 1.252 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00642 | -26.20 | 0.00036 | 0.206 | 0.00 |
SMSTORE8 | 25774.07 | 30928.88 | 177.56 | 1.164 | 1.397 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00649 | -26.20 | 0.00036 | 0.206 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC_1:1 | 2.17 | 2.17 | 2.34 | 2.34 | 2.3422 | 2.3422 | 2.3422 | 1.0000 | 1.0000 |
PSZ-AC_2:2 | 1.19 | 1.19 | 1.21 | 1.21 | 1.2058 | 1.2058 | 1.2058 | 1.0000 | 1.0000 |
PSZ-AC_3:3 | 1.19 | 1.19 | 1.21 | 1.21 | 1.2150 | 1.2150 | 1.2150 | 1.0000 | 1.0000 |
PSZ-AC_4:4 | 1.19 | 1.19 | 1.22 | 1.22 | 1.2180 | 1.2180 | 1.2180 | 1.0000 | 1.0000 |
PSZ-AC_5:5 | 1.18 | 1.18 | 1.23 | 1.23 | 1.2252 | 1.2252 | 1.2252 | 1.0000 | 1.0000 |
PSZ-AC_6:6 | 2.08 | 2.08 | 2.27 | 2.27 | 2.2655 | 2.2655 | 2.2655 | 1.0000 | 1.0000 |
PSZ-AC_7:7 | 1.08 | 1.08 | 1.24 | 1.24 | 1.2434 | 1.2434 | 1.2434 | 1.0000 | 1.0000 |
PSZ-AC_8:8 | 1.07 | 1.07 | 1.24 | 1.24 | 1.2423 | 1.2423 | 1.2423 | 1.0000 | 1.0000 |
PSZ-AC_9:9 | 1.06 | 1.06 | 1.25 | 1.25 | 1.2518 | 1.2518 | 1.2518 | 1.0000 | 1.0000 |
PSZ-AC_10:10 | 1.08 | 1.08 | 1.40 | 1.40 | 1.3974 | 1.3974 | 1.3974 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_1:1 | 52314.180 | 0.000 | 2.342200 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 52314.18 | 36588.58 | 2.342200 | 25.27 | 18.32 | 0.01097633 | 12.80 | 11.67 | 0.00850000 | 31.20 | 0.01534436 | 23.10 | 17.5670 | 23.88 | 0.00995629 | 51.3593 | 23532.95 | 0.00 | -999.00 | -999.00 |
PSZ-AC_1:1_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_1:1 | 73546.524 | 73546.524 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 73546.52 | 73546.52 | 2.342200 | 12.79 | 8.41 | 0.00539495 | 40.00 | 20.60 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 17.5670 | 21.10 | 0.00646764 | 39.7354 | 43199.04 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_2:2 | 26526.760 | 0.000 | 1.205770 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 26526.76 | 18728.21 | 1.205770 | 25.15 | 18.21 | 0.01087969 | 12.80 | 11.67 | 0.00850000 | 31.20 | 0.01534436 | 23.10 | 17.0619 | 23.88 | 0.00994365 | 51.2957 | 12861.87 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_2:2 | 37529.788 | 37529.788 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 37529.79 | 37529.79 | 1.205767 | 13.03 | 8.46 | 0.00534792 | 40.00 | 20.60 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 17.0619 | 21.10 | 0.00637375 | 39.1661 | 22239.35 | 0.00 | -999.00 | -999.00 |
PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_3:3 | 26740.570 | 0.000 | 1.214980 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 26740.57 | 18872.73 | 1.214980 | 25.15 | 18.21 | 0.01088279 | 12.80 | 11.67 | 0.00850000 | 31.20 | 0.01534436 | 23.10 | 16.9325 | 23.89 | 0.00904389 | 46.7103 | 12841.56 | 0.00 | -999.00 | -999.00 |
PSZ-AC_3:3_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_3:3 | 37730.699 | 37730.699 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 37730.70 | 37730.70 | 1.214979 | 13.09 | 8.51 | 0.00536347 | 40.00 | 20.60 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 16.9325 | 21.10 | 0.00638311 | 39.2230 | 22409.25 | 0.00 | -999.00 | -999.00 |
PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_4:4 | 26788.550 | 0.000 | 1.218000 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 26788.55 | 18917.24 | 1.218000 | 25.15 | 18.21 | 0.01087767 | 12.80 | 11.67 | 0.00850000 | 31.20 | 0.01534436 | 23.10 | 16.8905 | 23.89 | 0.00904636 | 46.7228 | 12876.06 | 0.00 | -999.00 | -999.00 |
PSZ-AC_4:4_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_4:4 | 37796.654 | 37796.654 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 37796.65 | 37796.65 | 1.218003 | 13.11 | 8.52 | 0.00536854 | 40.00 | 20.60 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 16.8905 | 21.10 | 0.00638616 | 39.2416 | 22465.02 | 0.00 | -999.00 | -999.00 |
PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_5:5 | 26997.620 | 0.000 | 1.225170 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 26997.62 | 19035.36 | 1.225170 | 25.16 | 18.22 | 0.01089177 | 12.80 | 11.67 | 0.00850000 | 31.20 | 0.01534436 | 23.10 | 16.7917 | 23.89 | 0.00904741 | 46.7282 | 12781.63 | 0.00 | -999.00 | -999.00 |
PSZ-AC_5:5_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_5:5 | 37952.941 | 37952.941 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 37952.94 | 37952.94 | 1.225170 | 13.16 | 8.56 | 0.00538044 | 40.00 | 20.60 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 16.7917 | 21.10 | 0.00639331 | 39.2851 | 22597.18 | 0.00 | -999.00 | -999.00 |
PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_6:6 | 51097.510 | 0.000 | 2.265540 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 51097.51 | 35494.35 | 2.265540 | 25.33 | 18.39 | 0.01104417 | 12.80 | 11.67 | 0.00850000 | 31.20 | 0.01534436 | 23.10 | 18.1614 | 23.88 | 0.00997725 | 51.4652 | 22477.09 | 0.00 | -999.00 | -999.00 |
PSZ-AC_6:6_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_6:6 | 71873.757 | 71873.757 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 71873.76 | 71873.76 | 2.265543 | 12.51 | 8.23 | 0.00535514 | 40.00 | 20.60 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 18.1614 | 21.10 | 0.00646335 | 39.7085 | 41784.29 | 0.00 | -999.00 | -999.00 |
PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_7:7 | 28060.190 | 0.000 | 1.243390 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 28060.19 | 19408.43 | 1.243390 | 25.28 | 18.40 | 0.01107029 | 12.80 | 11.67 | 0.00850000 | 31.20 | 0.01534436 | 23.10 | 16.5456 | 23.89 | 0.00914510 | 47.2265 | 11675.19 | 0.00 | -999.00 | -999.00 |
PSZ-AC_7:7_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_7:7 | 38350.306 | 38350.306 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 38350.31 | 38350.31 | 1.243391 | 13.28 | 8.64 | 0.00541008 | 40.00 | 20.60 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 16.5456 | 21.10 | 0.00641104 | 39.3929 | 22933.20 | 0.00 | -999.00 | -999.00 |
PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_8:8 | 28088.220 | 0.000 | 1.242270 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 28088.22 | 19398.35 | 1.242270 | 25.29 | 18.41 | 0.01108473 | 12.80 | 11.67 | 0.00850000 | 31.20 | 0.01534436 | 23.10 | 16.5605 | 23.89 | 0.00915378 | 47.2708 | 11592.32 | 0.00 | -999.00 | -999.00 |
PSZ-AC_8:8_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_8:8 | 38325.786 | 38325.786 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 38325.79 | 38325.79 | 1.242267 | 13.27 | 8.64 | 0.00540825 | 40.00 | 20.60 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 16.5606 | 21.10 | 0.00640994 | 39.3862 | 22912.47 | 0.00 | -999.00 | -999.00 |
PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_9:9 | 28358.190 | 0.000 | 1.251820 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 28358.19 | 19555.05 | 1.251820 | 25.30 | 18.43 | 0.01109923 | 12.80 | 11.67 | 0.00850000 | 31.20 | 0.01534436 | 23.10 | 16.4342 | 23.89 | 0.00917022 | 47.3546 | 11510.02 | 0.00 | -999.00 | -999.00 |
PSZ-AC_9:9_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_9:9 | 38534.055 | 38534.055 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 38534.06 | 38534.06 | 1.251817 | 13.33 | 8.68 | 0.00542364 | 40.00 | 20.60 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 16.4343 | 21.10 | 0.00641920 | 39.4425 | 23088.59 | 0.00 | -999.00 | -999.00 |
PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_10:10 | 31549.030 | 0.000 | 1.397370 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | 31549.03 | 21693.30 | 1.397370 | 25.23 | 18.41 | 0.01111007 | 12.80 | 11.67 | 0.00850000 | 30.93 | 0.01534436 | 23.03 | 14.7224 | 23.88 | 0.01010475 | 52.1133 | 11677.80 | 0.00 | -999.00 | -999.00 |
PSZ-AC_10:10_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_10:10 | 41709.546 | 41709.546 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 41709.55 | 41709.55 | 1.397372 | 14.14 | 9.22 | 0.00558916 | 40.00 | 20.60 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 14.7224 | 21.10 | 0.00649169 | 39.8847 | 25774.07 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2020-06-03 19:18:54
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | LGSTORE1 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 52314.180 | 0.000 | 2.342200 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1025.2445 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 52314.18 | 36588.58 | 1.0000 | 2.69014746 | 2.342200 | 25.27 | 18.32 | 0.01097633 | 53358.1 | 12.80 | 11.67 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 52314.18 | 31.20 | 0.01534436 | 23.10 | 0.41145340 | 17.5670 | 23.88 | 0.00995629 | 23.88 | 0.00995629 | 51.3593 | 23532.95 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_1:1_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | LGSTORE1 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 73546.524 | 73546.524 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.342200 | 2.69014768 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 73546.52 | 73546.52 | 1.0000 | 2.69014768 | 2.342200 | 12.79 | 8.41 | 0.00539495 | 26475.6 | 40.00 | 20.60 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 73546.52 | -26.20 | 0.00036134 | -26.20 | 0.41145340 | 17.5670 | 21.10 | 0.00646764 | 21.10 | 0.00646764 | 39.7354 | 43199.04 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | SMSTORE1 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 26526.760 | 0.000 | 1.205770 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1025.0648 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 26526.76 | 18728.21 | 1.0000 | 1.38489416 | 1.205770 | 25.15 | 18.21 | 0.01087969 | 52990.8 | 12.80 | 11.67 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 26526.76 | 31.20 | 0.01534436 | 23.10 | 0.20572670 | 17.0619 | 23.88 | 0.00994450 | 23.88 | 0.00994365 | 51.2957 | 12861.87 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | SMSTORE1 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 37529.788 | 37529.788 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.205767 | 1.38489068 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 37529.79 | 37529.79 | 1.0000 | 1.38489068 | 1.205767 | 13.03 | 8.46 | 0.00534792 | 26599.0 | 40.00 | 20.60 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 37529.79 | -26.20 | 0.00036134 | -26.20 | 0.20572670 | 17.0619 | 21.10 | 0.00637375 | 21.10 | 0.00637375 | 39.1661 | 22239.35 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_3:3 | SMSTORE2 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 26740.570 | 0.000 | 1.214980 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1025.0706 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 26740.57 | 18872.73 | 1.0000 | 1.39547236 | 1.214980 | 25.15 | 18.21 | 0.01088279 | 53000.7 | 12.80 | 11.67 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 26740.57 | 31.20 | 0.01534436 | 23.10 | 0.20572670 | 16.9325 | 23.88 | 0.00994645 | 23.89 | 0.00904389 | 46.7103 | 12841.56 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_3:3_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_3:3 | SMSTORE2 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 37730.699 | 37730.699 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.214979 | 1.39547137 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 37730.70 | 37730.70 | 1.0000 | 1.39547137 | 1.214979 | 13.09 | 8.51 | 0.00536347 | 26700.4 | 40.00 | 20.60 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 37730.70 | -26.20 | 0.00036134 | -26.20 | 0.20572670 | 16.9325 | 21.10 | 0.00638311 | 21.10 | 0.00638311 | 39.2230 | 22409.25 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_4:4 | SMSTORE3 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 26788.550 | 0.000 | 1.218000 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1025.0610 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 26788.55 | 18917.24 | 1.0000 | 1.39894100 | 1.218000 | 25.15 | 18.21 | 0.01087767 | 52984.2 | 12.80 | 11.67 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 26788.55 | 31.20 | 0.01534436 | 23.10 | 0.20572670 | 16.8905 | 23.88 | 0.00994329 | 23.89 | 0.00904636 | 46.7228 | 12876.06 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_4:4_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_4:4 | SMSTORE3 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 37796.654 | 37796.654 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.218003 | 1.39894480 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 37796.65 | 37796.65 | 1.0000 | 1.39894480 | 1.218003 | 13.11 | 8.52 | 0.00536854 | 26733.4 | 40.00 | 20.60 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 37796.65 | -26.20 | 0.00036134 | -26.20 | 0.20572670 | 16.8905 | 21.10 | 0.00638616 | 21.10 | 0.00638616 | 39.2416 | 22465.02 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_5:5 | SMSTORE4 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 26997.620 | 0.000 | 1.225170 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1025.0872 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 26997.62 | 19035.36 | 1.0000 | 1.40717614 | 1.225170 | 25.16 | 18.22 | 0.01089177 | 53029.7 | 12.80 | 11.67 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 26997.62 | 31.20 | 0.01534436 | 23.10 | 0.20572670 | 16.7917 | 23.88 | 0.00995200 | 23.89 | 0.00904741 | 46.7282 | 12781.63 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_5:5_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_5:5 | SMSTORE4 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 37952.941 | 37952.941 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.225170 | 1.40717564 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 37952.94 | 37952.94 | 1.0000 | 1.40717564 | 1.225170 | 13.16 | 8.56 | 0.00538044 | 26810.9 | 40.00 | 20.60 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 37952.94 | -26.20 | 0.00036134 | -26.20 | 0.20572670 | 16.7917 | 21.10 | 0.00639331 | 21.10 | 0.00639331 | 39.2851 | 22597.18 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_6:6 | LGSTORE2 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 51097.510 | 0.000 | 2.265540 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1025.3706 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 51097.51 | 35494.35 | 1.0000 | 2.60209917 | 2.265540 | 25.33 | 18.39 | 0.01104417 | 53597.8 | 12.80 | 11.67 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 51097.51 | 31.20 | 0.01534436 | 23.10 | 0.41145340 | 18.1614 | 23.88 | 0.00998111 | 23.88 | 0.00997725 | 51.4652 | 22477.09 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_6:6_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_6:6 | LGSTORE2 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 71873.757 | 71873.757 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.265543 | 2.60210226 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 71873.76 | 71873.76 | 1.0000 | 2.60210226 | 2.265543 | 12.51 | 8.23 | 0.00535514 | 26090.1 | 40.00 | 20.60 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 71873.76 | -26.20 | 0.00036134 | -26.20 | 0.41145340 | 18.1614 | 21.10 | 0.00646335 | 21.10 | 0.00646335 | 39.7085 | 41784.29 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_7:7 | SMSTORE5 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 28060.190 | 0.000 | 1.243390 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1025.4191 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 28060.19 | 19408.43 | 1.0000 | 1.42810283 | 1.243390 | 25.28 | 18.40 | 0.01107029 | 53608.5 | 12.80 | 11.67 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 28060.19 | 31.20 | 0.01534436 | 23.10 | 0.20572670 | 16.5456 | 23.88 | 0.01006255 | 23.89 | 0.00914510 | 47.2265 | 11675.19 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_7:7_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_7:7 | SMSTORE5 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 38350.306 | 38350.306 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.243391 | 1.42810432 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 38350.31 | 38350.31 | 1.0000 | 1.42810432 | 1.243391 | 13.28 | 8.64 | 0.00541008 | 27003.9 | 40.00 | 20.60 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 38350.31 | -26.20 | 0.00036134 | -26.20 | 0.20572670 | 16.5456 | 21.10 | 0.00641104 | 21.10 | 0.00641104 | 39.3929 | 22933.20 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_8:8 | SMSTORE6 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 28088.220 | 0.000 | 1.242270 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1025.4460 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 28088.22 | 19398.35 | 1.0000 | 1.42681645 | 1.242270 | 25.29 | 18.41 | 0.01108473 | 53655.5 | 12.80 | 11.67 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 28088.22 | 31.20 | 0.01534436 | 23.10 | 0.20572670 | 16.5605 | 23.88 | 0.01007151 | 23.89 | 0.00915378 | 47.2708 | 11592.32 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_8:8_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_8:8 | SMSTORE6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 38325.786 | 38325.786 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.242267 | 1.42681301 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 38325.79 | 38325.79 | 1.0000 | 1.42681301 | 1.242267 | 13.27 | 8.64 | 0.00540825 | 26992.1 | 40.00 | 20.60 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 38325.79 | -26.20 | 0.00036134 | -26.20 | 0.20572670 | 16.5606 | 21.10 | 0.00640994 | 21.10 | 0.00640994 | 39.3862 | 22912.47 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_9:9 | SMSTORE7 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 28358.190 | 0.000 | 1.251820 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1025.4729 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 28358.19 | 19555.05 | 1.0000 | 1.43778516 | 1.251820 | 25.30 | 18.43 | 0.01109923 | 53702.8 | 12.80 | 11.67 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 28358.19 | 31.20 | 0.01534436 | 23.10 | 0.20572670 | 16.4342 | 23.88 | 0.01008050 | 23.89 | 0.00917022 | 47.3546 | 11510.02 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_9:9_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_9:9 | SMSTORE7 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 38534.055 | 38534.055 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.251817 | 1.43778128 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 38534.06 | 38534.06 | 1.0000 | 1.43778128 | 1.251817 | 13.33 | 8.68 | 0.00542364 | 27091.6 | 40.00 | 20.60 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 38534.06 | -26.20 | 0.00036134 | -26.20 | 0.20572670 | 16.4343 | 21.10 | 0.00641920 | 21.10 | 0.00641920 | 39.4425 | 23088.59 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_10:10 | SMSTORE8 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 31549.030 | 0.000 | 1.397370 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1025.4931 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | 31549.03 | 21693.30 | 1.0000 | 1.60495746 | 1.397370 | 25.23 | 18.41 | 0.01111007 | 53655.8 | 12.80 | 11.67 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 31549.03 | 30.93 | 0.01534436 | 23.03 | 0.20572670 | 14.7224 | 23.88 | 0.01011387 | 23.88 | 0.01010475 | 52.1133 | 11677.80 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_10:10_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_10:10 | SMSTORE8 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 41709.546 | 41709.546 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.397372 | 1.60495940 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 41709.55 | 41709.55 | 1.0000 | 1.60495940 | 1.397372 | 14.14 | 9.22 | 0.00558916 | 28331.2 | 40.00 | 20.60 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 41709.55 | -26.20 | 0.00036134 | -26.20 | 0.20572670 | 14.7224 | 21.10 | 0.00649169 | 21.10 | 0.00649169 | 39.8847 | 25774.07 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2020-06-03 19:18:54
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-AC_1:1_OA_CONTROLLER | DifferentialDryBulb | 0.41 | 2.34 | - | |||
PSZ-AC_2:2_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.21 | - | |||
PSZ-AC_3:3_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.21 | - | |||
PSZ-AC_4:4_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.22 | - | |||
PSZ-AC_5:5_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.23 | - | |||
PSZ-AC_6:6_OA_CONTROLLER | DifferentialDryBulb | 0.41 | 2.27 | - | |||
PSZ-AC_7:7_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.24 | - | |||
PSZ-AC_8:8_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.24 | - | |||
PSZ-AC_9:9_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.25 | - | |||
PSZ-AC_10:10_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.40 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
LGSTORE1 | 3653.67 | 3872.33 | 2103.83 |
SMSTORE1 | 3042.00 | 3515.83 | 1349.67 |
SMSTORE2 | 2648.83 | 2809.50 | 1388.17 |
SMSTORE3 | 2712.50 | 2848.00 | 1464.67 |
SMSTORE4 | 2764.33 | 2913.17 | 1556.67 |
LGSTORE2 | 2664.67 | 2788.00 | 1627.50 |
SMSTORE5 | 2645.50 | 2813.17 | 1650.00 |
SMSTORE6 | 2645.83 | 2834.67 | 1666.17 |
SMSTORE7 | 2677.50 | 2881.50 | 1733.83 |
SMSTORE8 | 2808.67 | 2993.83 | 1973.83 |
Facility | 4391.33 | 4341.83 | 2776.33 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
LGSTORE1 | 37.00 | 0.00 | 8.33 | 0.00 |
SMSTORE1 | 9.83 | 0.00 | 3.33 | 0.00 |
SMSTORE2 | 7.67 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 12.50 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 14.50 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 30.83 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 27.17 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 28.33 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 36.67 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 170.83 | 0.00 | 0.00 | 0.00 |
Facility | 224.83 | 0.00 | 8.33 | 0.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2020-06-03 19:18:54
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
LGSTORE1 | 9.03 | 30.00 | 1805.20 | 1.264 | 0.404 | 0.000 | 0.000 |
SMSTORE1 | 4.51 | 15.00 | 902.60 | 1.119 | 0.429 | 0.000 | 0.000 |
SMSTORE2 | 3.78 | 15.00 | 902.60 | 1.267 | 0.556 | 0.000 | 0.000 |
SMSTORE3 | 3.78 | 15.00 | 902.60 | 1.263 | 0.556 | 0.000 | 0.000 |
SMSTORE4 | 3.78 | 15.00 | 902.60 | 1.252 | 0.556 | 0.000 | 0.000 |
LGSTORE2 | 13.21 | 30.00 | 1805.20 | 1.199 | 0.522 | 0.000 | 0.000 |
SMSTORE5 | 6.60 | 15.00 | 902.60 | 1.238 | 0.591 | 0.000 | 0.000 |
SMSTORE6 | 6.60 | 15.00 | 902.60 | 1.231 | 0.591 | 0.000 | 0.000 |
SMSTORE7 | 6.60 | 15.00 | 902.60 | 1.219 | 0.591 | 0.000 | 0.000 |
SMSTORE8 | 6.60 | 15.00 | 902.60 | 1.231 | 0.642 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
LGSTORE1 | 9.03 | 30.00 | 1805.20 | 0.000 | 0.000 | 0.000 | 0.000 |
SMSTORE1 | 4.51 | 15.00 | 902.60 | 0.000 | 0.000 | 0.000 | 0.000 |
SMSTORE2 | 3.78 | 15.00 | 902.60 | 0.806 | 0.000 | 0.000 | 0.000 |
SMSTORE3 | 3.78 | 15.00 | 902.60 | 0.806 | 0.000 | 0.000 | 0.000 |
SMSTORE4 | 3.78 | 15.00 | 902.60 | 0.806 | 0.000 | 0.000 | 0.000 |
LGSTORE2 | 13.21 | 30.00 | 1805.20 | 0.807 | 0.000 | 0.000 | 0.000 |
SMSTORE5 | 6.60 | 15.00 | 902.60 | 0.807 | 0.000 | 0.000 | 0.000 |
SMSTORE6 | 6.60 | 15.00 | 902.60 | 0.807 | 0.000 | 0.000 | 0.000 |
SMSTORE7 | 6.60 | 15.00 | 902.60 | 0.807 | 0.000 | 0.000 | 0.000 |
SMSTORE8 | 6.60 | 15.00 | 902.60 | 0.807 | 0.000 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2020-06-03 19:18:54
Surfaces by ClassTotal | Outdoors | |
Wall | 40 | 22 |
Floor | 10 | 10 |
Roof | 10 | 10 |
Internal Mass | 10 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 36 | 36 |
Door | 12 | 12 |
Glass Door | 12 | 12 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 10 |
Conditioned Zones | 10 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 0 |
Defaulted Fields | 0 |
Fields with Defaults | 0 |
Autosized Fields | 0 |
Autosizable Fields | 0 |
Autocalculated Fields | 0 |
Autocalculatable Fields | 0 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2020-06-03 19:18:54
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1418.42 | 3973.34 | 12-FEB-07:30 | 150546.18 | 04-AUG-14:00 |
Electricity:Building | 832.89 | 2755.34 | 01-JAN-00:10 | 51902.14 | 01-JAN-11:10 |
Electricity:Zone:LGSTORE1 | 186.96 | 509.76 | 01-JAN-00:10 | 9610.45 | 01-JAN-10:10 |
InteriorLights:Electricity | 704.17 | 2305.93 | 01-JAN-00:10 | 43812.60 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:LGSTORE1 | 160.61 | 434.85 | 01-JAN-00:10 | 8262.19 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity | 704.17 | 2305.93 | 01-JAN-00:10 | 43812.60 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE1 | 102.73 | 279.91 | 01-JAN-00:10 | 5280.82 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE1 | 89.55 | 242.46 | 01-JAN-00:10 | 4606.69 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE2 | 75.94 | 261.16 | 01-JAN-00:10 | 4924.57 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE2 | 65.47 | 223.71 | 01-JAN-00:10 | 4250.44 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE3 | 75.94 | 261.16 | 01-JAN-00:10 | 4924.57 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE3 | 65.47 | 223.71 | 01-JAN-00:10 | 4250.44 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE4 | 75.94 | 261.16 | 01-JAN-00:10 | 4924.57 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE4 | 65.47 | 223.71 | 01-JAN-00:10 | 4250.44 | 01-JAN-10:10 |
Electricity:Zone:LGSTORE2 | 105.13 | 394.07 | 01-JAN-00:10 | 7412.39 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:LGSTORE2 | 85.86 | 319.16 | 01-JAN-00:10 | 6064.13 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE5 | 52.56 | 197.03 | 01-JAN-00:10 | 3706.19 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE5 | 42.93 | 159.58 | 01-JAN-00:10 | 3032.07 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE6 | 52.56 | 197.03 | 01-JAN-00:10 | 3706.19 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE6 | 42.93 | 159.58 | 01-JAN-00:10 | 3032.07 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE7 | 52.56 | 197.03 | 01-JAN-00:10 | 3706.19 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE7 | 42.93 | 159.58 | 01-JAN-00:10 | 3032.07 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE8 | 52.56 | 197.03 | 01-JAN-00:10 | 3706.19 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE8 | 42.93 | 159.58 | 01-JAN-00:10 | 3032.07 | 01-JAN-11:10 |
InteriorEquipment:Electricity | 128.72 | 449.42 | 01-JAN-00:10 | 8089.53 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:LGSTORE1 | 26.36 | 74.90 | 01-JAN-00:10 | 1348.26 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity | 128.72 | 449.42 | 01-JAN-00:10 | 8089.53 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE1 | 13.18 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE2 | 10.47 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE3 | 10.47 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE4 | 10.47 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:LGSTORE2 | 19.26 | 74.90 | 01-JAN-00:10 | 1348.26 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE5 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE6 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE7 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE8 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
Electricity:Plant | 66.30 | 1218.00 | 06-JAN-00:20 | 11884.51 | 07-JAN-14:10 |
WaterSystems:Electricity | 66.30 | 1218.00 | 06-JAN-00:20 | 11884.51 | 07-JAN-14:10 |
Water Heater:WaterSystems:Electricity | 66.30 | 1218.00 | 06-JAN-00:20 | 11884.51 | 07-JAN-14:10 |
ElectricityPurchased:Facility | 1418.42 | 3973.34 | 12-FEB-07:30 | 150546.18 | 04-AUG-14:00 |
ElectricityPurchased:Plant | 1418.42 | 3973.34 | 12-FEB-07:30 | 150546.18 | 04-AUG-14:00 |
Cogeneration:ElectricityPurchased | 1418.42 | 3973.34 | 12-FEB-07:30 | 150546.18 | 04-AUG-14:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1418.42 | 3973.34 | 12-FEB-07:30 | 150546.18 | 04-AUG-14:00 |
ElectricityNet:Plant | 1418.42 | 3973.34 | 12-FEB-07:30 | 150546.18 | 04-AUG-14:00 |
Cogeneration:ElectricityNet | 1418.42 | 3973.34 | 12-FEB-07:30 | 150546.18 | 04-AUG-14:00 |
Electricity:HVAC | 408.57 | 0.00 | 01-JAN-00:10 | 93179.33 | 04-AUG-14:00 |
Fans:Electricity | 283.42 | 0.00 | 01-JAN-00:10 | 16442.89 | 02-JAN-08:10 |
General:Fans:Electricity | 283.42 | 0.00 | 01-JAN-00:10 | 16442.89 | 02-JAN-08:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 125.16 | 0.00 | 01-JAN-00:10 | 76736.44 | 04-AUG-14:00 |
ExteriorLights:Electricity | 110.65 | 0.00 | 01-JAN-08:00 | 7048.38 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 110.65 | 0.00 | 01-JAN-08:00 | 7048.38 | 01-JAN-00:10 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Gas:Facility | 1027.68 | 0.00 | 01-JAN-00:10 | 441652.67 | 02-FEB-12:10 |
Gas:HVAC | 1027.68 | 0.00 | 01-JAN-00:10 | 441652.67 | 02-FEB-12:10 |
Heating:Gas | 1027.68 | 0.00 | 01-JAN-00:10 | 441652.67 | 02-FEB-12:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water:Plant | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
WaterSystems:Water | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water Heater:WaterSystems:Water | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
MainsWater:Facility | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
MainsWater:Plant | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
WaterSystems:MainsWater | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water Heater:WaterSystems:MainsWater | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:Facility | 2037.90 | 0.00 | 01-JAN-00:10 | 574826.74 | 02-FEB-12:10 |
EnergyTransfer:Building | 791.85 | 0.00 | 01-JAN-00:10 | 232017.13 | 02-FEB-08:10 |
EnergyTransfer:Zone:LGSTORE1 | 146.50 | 0.00 | 01-JAN-00:10 | 42771.00 | 02-FEB-08:10 |
Heating:EnergyTransfer | 444.13 | 0.00 | 01-JAN-00:10 | 232017.13 | 02-FEB-08:10 |
Heating:EnergyTransfer:Zone:LGSTORE1 | 65.95 | 0.00 | 01-JAN-00:10 | 42771.00 | 02-FEB-08:10 |
Cooling:EnergyTransfer | 347.72 | 0.00 | 01-JAN-00:10 | 111675.60 | 04-AUG-15:00 |
Cooling:EnergyTransfer:Zone:LGSTORE1 | 80.56 | 0.00 | 01-JAN-00:10 | 20254.18 | 03-FEB-00:10 |
EnergyTransfer:Zone:SMSTORE1 | 72.76 | 0.00 | 01-JAN-00:10 | 20370.05 | 04-FEB-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE1 | 26.39 | 0.00 | 01-JAN-00:10 | 20370.05 | 04-FEB-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE1 | 46.37 | 0.00 | 01-JAN-00:10 | 13260.20 | 06-AUG-17:20 |
EnergyTransfer:Zone:SMSTORE2 | 62.39 | 0.00 | 01-JAN-00:10 | 20282.05 | 10-DEC-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE2 | 30.26 | 0.00 | 01-JAN-00:10 | 20282.05 | 10-DEC-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE2 | 32.12 | 0.00 | 01-JAN-00:10 | 9896.15 | 04-AUG-15:00 |
EnergyTransfer:Zone:SMSTORE3 | 63.37 | 0.00 | 01-JAN-00:10 | 20503.07 | 29-JAN-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE3 | 31.91 | 0.00 | 01-JAN-00:10 | 20503.07 | 29-JAN-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE3 | 31.47 | 0.00 | 01-JAN-00:10 | 9892.96 | 04-AUG-15:00 |
EnergyTransfer:Zone:SMSTORE4 | 63.81 | 0.00 | 01-JAN-00:10 | 20712.93 | 29-JAN-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE4 | 34.16 | 0.00 | 01-JAN-00:10 | 20712.93 | 29-JAN-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE4 | 29.65 | 0.00 | 01-JAN-00:10 | 9753.09 | 04-AUG-15:00 |
EnergyTransfer:Zone:LGSTORE2 | 115.08 | 0.00 | 01-JAN-00:10 | 41670.55 | 02-FEB-08:10 |
Heating:EnergyTransfer:Zone:LGSTORE2 | 69.63 | 0.00 | 01-JAN-00:10 | 41670.55 | 02-FEB-08:10 |
Cooling:EnergyTransfer:Zone:LGSTORE2 | 45.44 | 0.00 | 01-JAN-00:10 | 17228.05 | 04-AUG-15:00 |
EnergyTransfer:Zone:SMSTORE5 | 61.88 | 0.00 | 01-JAN-00:10 | 21862.48 | 02-FEB-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE5 | 39.50 | 0.00 | 01-JAN-00:10 | 21862.48 | 02-FEB-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE5 | 22.39 | 0.00 | 01-JAN-00:10 | 9055.17 | 04-AUG-15:00 |
EnergyTransfer:Zone:SMSTORE6 | 61.76 | 0.00 | 01-JAN-00:10 | 21903.93 | 02-FEB-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE6 | 40.00 | 0.00 | 01-JAN-00:10 | 21903.93 | 02-FEB-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE6 | 21.75 | 0.00 | 01-JAN-00:10 | 8985.27 | 04-AUG-15:00 |
EnergyTransfer:Zone:SMSTORE7 | 62.81 | 0.00 | 01-JAN-00:10 | 22724.71 | 02-FEB-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE7 | 42.50 | 0.00 | 01-JAN-00:10 | 22724.71 | 02-FEB-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE7 | 20.32 | 0.00 | 01-JAN-00:10 | 8916.17 | 04-AUG-15:00 |
EnergyTransfer:Zone:SMSTORE8 | 81.49 | 0.00 | 01-JAN-00:10 | 27851.26 | 29-JAN-09:10 |
Heating:EnergyTransfer:Zone:SMSTORE8 | 63.84 | 0.00 | 01-JAN-00:10 | 27851.26 | 29-JAN-09:10 |
Cooling:EnergyTransfer:Zone:SMSTORE8 | 17.66 | 0.00 | 01-JAN-00:10 | 9234.18 | 04-AUG-15:00 |
EnergyTransfer:HVAC | 1246.05 | 0.00 | 01-JAN-00:10 | 353322.13 | 02-FEB-12:10 |
HeatingCoils:EnergyTransfer | 822.14 | 0.00 | 01-JAN-00:10 | 353322.13 | 02-FEB-12:10 |
CoolingCoils:EnergyTransfer | 423.90 | 0.00 | 01-JAN-00:10 | 268277.94 | 04-AUG-13:00 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2020-06-03 19:18:54
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
LGSTORE1 | 0.000 | 0.000 | 65.948 | -80.556 | 0.000 | 0.000 | 13.514 | 160.608 | 26.357 | 17.726 | 0.000 | 2.553 | 0.001 | 0.000 | -16.258 | 0.000 | -92.432 | -97.460 |
SMSTORE1 | 0.000 | 0.000 | 26.387 | -46.370 | 0.000 | 0.000 | 6.688 | 89.549 | 13.179 | 8.767 | 0.000 | 1.397 | 0.000 | 0.000 | -8.475 | 0.000 | -44.180 | -46.941 |
SMSTORE2 | 0.000 | 0.000 | 30.265 | -32.122 | 0.000 | 0.000 | 4.060 | 65.475 | 10.467 | 8.762 | 0.000 | 1.352 | 0.003 | 0.000 | -8.300 | 0.000 | -45.689 | -34.269 |
SMSTORE3 | 0.000 | 0.000 | 31.905 | -31.466 | 0.000 | 0.000 | 4.065 | 65.475 | 10.467 | 8.778 | 0.000 | 1.352 | 0.004 | 0.000 | -8.214 | 0.000 | -45.526 | -36.835 |
SMSTORE4 | 0.000 | 0.000 | 34.162 | -29.645 | 0.000 | 0.000 | 4.072 | 65.475 | 10.467 | 8.803 | 0.000 | 1.352 | 0.002 | 0.000 | -8.128 | 0.000 | -45.343 | -41.214 |
LGSTORE2 | 0.000 | 0.000 | 69.635 | -45.440 | 0.000 | 0.000 | 14.028 | 85.864 | 19.261 | 17.770 | 0.000 | 2.386 | 0.009 | 0.000 | -15.683 | 0.000 | -82.311 | -65.512 |
SMSTORE5 | 0.000 | 0.000 | 39.498 | -22.386 | 0.000 | 0.000 | 7.017 | 42.932 | 9.631 | 8.875 | 0.000 | 1.356 | 0.003 | 0.000 | -7.864 | 0.000 | -45.393 | -33.666 |
SMSTORE6 | 0.000 | 0.000 | 40.003 | -21.752 | 0.000 | 0.000 | 7.022 | 42.932 | 9.631 | 8.887 | 0.000 | 1.356 | 0.004 | 0.000 | -7.835 | 0.000 | -45.328 | -34.917 |
SMSTORE7 | 0.000 | 0.000 | 42.498 | -20.317 | 0.000 | 0.000 | 7.034 | 42.932 | 9.631 | 8.917 | 0.000 | 1.357 | 0.001 | 0.000 | -7.738 | 0.000 | -45.125 | -39.188 |
SMSTORE8 | 0.000 | 0.000 | 63.836 | -17.658 | 0.000 | 0.000 | 7.059 | 42.932 | 9.631 | 9.013 | 0.000 | 1.450 | 0.002 | 0.000 | -7.337 | 0.000 | -60.192 | -48.735 |
Total Facility | 0.000 | 0.000 | 444.136 | -347.711 | 0.000 | 0.000 | 74.559 | 704.173 | 128.721 | 106.299 | 0.000 | 15.912 | 0.029 | 0.000 | -95.832 | 0.000 | -551.519 | -478.737 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
LGSTORE1 | 28-JUL-07:02 | 0.00 | 0.00 | 0.00 | -33396.73 | 0.00 | 0.00 | 0.00 | 434.85 | 74.90 | 245.37 | 0.00 | 0.00 | 32897.52 | 0.00 | -0.00 | 0.00 | -255.92 | 0.00 |
SMSTORE1 | 24-SEP-17:01 | 0.00 | 0.00 | 0.00 | -28141.57 | 0.00 | 0.00 | 630.36 | 4606.69 | 674.13 | 0.00 | 0.00 | 0.00 | 22868.91 | 0.00 | -129.81 | 0.00 | -508.71 | 0.00 |
SMSTORE2 | 08-SEP-06:02 | 0.00 | 0.00 | 0.00 | -23707.62 | 0.00 | 0.00 | 0.00 | 223.71 | 37.45 | 0.00 | 0.00 | 0.00 | 23704.42 | 0.00 | -214.08 | 0.00 | -43.88 | 0.00 |
SMSTORE3 | 08-SEP-06:02 | 0.00 | 0.00 | 0.00 | -23786.54 | 0.00 | 0.00 | 0.00 | 223.71 | 37.45 | 0.00 | 0.00 | 0.00 | 23784.14 | 0.00 | -214.77 | 0.00 | -43.99 | 0.00 |
SMSTORE4 | 08-SEP-06:02 | 0.00 | 0.00 | 0.00 | -23776.88 | 0.00 | 0.00 | 0.00 | 223.71 | 37.45 | 0.00 | 0.00 | 0.00 | 23771.02 | 0.00 | -211.93 | 0.00 | -43.36 | 0.00 |
LGSTORE2 | 12-SEP-07:02 | 0.00 | 0.00 | 0.00 | -35653.10 | 0.00 | 0.00 | 0.00 | 319.16 | 74.90 | 0.00 | 0.00 | 0.00 | 36083.77 | 0.00 | -219.60 | 0.00 | -605.14 | 0.00 |
SMSTORE5 | 28-JUL-07:02 | 0.00 | 0.00 | 0.00 | -17938.91 | 0.00 | 0.00 | 0.00 | 159.58 | 37.45 | 125.15 | 0.00 | 0.00 | 17745.76 | 0.00 | -0.00 | 0.00 | -129.04 | 0.00 |
SMSTORE6 | 28-JUL-07:02 | 0.00 | 0.00 | 0.00 | -17872.66 | 0.00 | 0.00 | 0.00 | 159.58 | 37.45 | 126.38 | 0.00 | 0.00 | 17676.15 | 0.00 | -0.00 | 0.00 | -126.89 | 0.00 |
SMSTORE7 | 03-JUL-07:02 | 0.00 | 0.00 | 0.00 | -16798.59 | 0.00 | 0.00 | 0.00 | 159.58 | 37.45 | 164.77 | 0.00 | 0.00 | 16621.76 | 0.00 | -0.00 | 0.00 | -184.98 | 0.00 |
SMSTORE8 | 04-JUL-08:62 | 0.00 | 0.00 | 0.00 | -16982.73 | 0.00 | 0.00 | 0.00 | 159.58 | 37.45 | 306.49 | 0.00 | 0.00 | 16566.67 | 0.00 | -0.00 | 0.00 | -87.47 | 0.00 |
Total Facility | 28-JUL-07:02 | 0.00 | 0.00 | 0.00 | -151309.91 | 0.00 | 0.00 | 157.59 | 8346.03 | 1460.61 | 1542.56 | 0.00 | 0.00 | 141332.45 | 0.00 | 0.00 | 0.00 | -1529.32 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
LGSTORE1 | 29-JAN-08:11 | 0.00 | 0.00 | 74298.99 | 0.00 | 0.00 | 0.00 | 123.30 | 434.85 | 74.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -31.27 | 0.00 | -6183.38 | -68717.40 |
SMSTORE1 | 29-JAN-08:11 | 0.00 | 0.00 | 37900.20 | 0.00 | 0.00 | 0.00 | 61.65 | 242.46 | 37.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -30.10 | 0.00 | -2717.26 | -35494.40 |
SMSTORE2 | 29-JAN-08:11 | 0.00 | 0.00 | 38153.32 | 0.00 | 0.00 | 0.00 | 0.00 | 223.71 | 37.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -22.31 | 0.00 | -2714.47 | -35677.70 |
SMSTORE3 | 29-JAN-08:11 | 0.00 | 0.00 | 38267.53 | 0.00 | 0.00 | 0.00 | 0.00 | 223.71 | 37.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -17.82 | 0.00 | -2701.64 | -35809.23 |
SMSTORE4 | 29-JAN-08:11 | 0.00 | 0.00 | 38433.50 | 0.00 | 0.00 | 0.00 | 0.00 | 223.71 | 37.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -16.28 | 0.00 | -2700.02 | -35978.35 |
LGSTORE2 | 02-FEB-08:12 | 0.00 | 0.00 | 72457.24 | 0.00 | 0.00 | 0.00 | 0.00 | 319.16 | 74.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1670.20 | 0.00 | -5598.72 | -65582.39 |
SMSTORE5 | 02-FEB-08:12 | 0.00 | 0.00 | 38714.46 | 0.00 | 0.00 | 0.00 | 0.00 | 159.58 | 37.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -839.81 | 0.00 | -3137.97 | -34933.71 |
SMSTORE6 | 02-FEB-08:12 | 0.00 | 0.00 | 38693.11 | 0.00 | 0.00 | 0.00 | 0.00 | 159.58 | 37.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -839.64 | 0.00 | -3137.78 | -34912.72 |
SMSTORE7 | 02-FEB-08:12 | 0.00 | 0.00 | 38912.07 | 0.00 | 0.00 | 0.00 | 0.00 | 159.58 | 37.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -837.53 | 0.00 | -3136.68 | -35134.89 |
SMSTORE8 | 19-JAN-01:11 | 0.00 | 0.00 | 43647.43 | 0.00 | 0.00 | 0.00 | 0.00 | 159.58 | 37.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -816.72 | 0.00 | -7894.11 | -35133.63 |
Total Facility | 02-FEB-08:12 | 0.00 | 0.00 | 375257.45 | 0.00 | 0.00 | 0.00 | 369.90 | 8346.03 | 1460.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -10139.93 | 0.00 | -37687.21 | -337606.84 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2020-06-03 19:18:54
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 2.3422 | 0.0000 | 29.9961 | 1.0000 | 0.4115 | 2.3422 | 0.1893 | 1.0000 | 0.4115 | 0.1757 | ||
PSZ-AC_2:2 | 1.2058 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.2058 | 0.1731 | 1.0000 | 0.2057 | 0.1706 | ||
PSZ-AC_3:3 | 1.2150 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.2150 | 0.1733 | 1.0000 | 0.2057 | 0.1693 | ||
PSZ-AC_4:4 | 1.2180 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.2180 | 0.1729 | 1.0000 | 0.2057 | 0.1689 | ||
PSZ-AC_5:5 | 1.2252 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.2252 | 0.1741 | 1.0000 | 0.2057 | 0.1679 | ||
PSZ-AC_6:6 | 2.2655 | 0.0000 | 29.9961 | 1.0000 | 0.4115 | 2.2655 | 0.1980 | 1.0000 | 0.4115 | 0.1816 | ||
PSZ-AC_7:7 | 1.2434 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.2434 | 0.1906 | 1.0000 | 0.2057 | 0.1655 | ||
PSZ-AC_8:8 | 1.2423 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.2423 | 0.1920 | 1.0000 | 0.2057 | 0.1656 | ||
PSZ-AC_9:9 | 1.2518 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.2518 | 0.1933 | 1.0000 | 0.2057 | 0.1643 | ||
PSZ-AC_10:10 | 1.3974 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.3974 | 0.1901 | 1.0000 | 0.2057 | 0.1472 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 2.3422 | 0.0000 | 29.9961 | 1.0000 | 0.4115 | 2.3422 | 1.0000 | 1.0000 | 0.4115 | 0.1757 | ||
PSZ-AC_2:2 | 1.2058 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.2058 | 1.0000 | 1.0000 | 0.2057 | 0.1706 | ||
PSZ-AC_3:3 | 1.2150 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.2150 | 1.0000 | 1.0000 | 0.2057 | 0.1693 | ||
PSZ-AC_4:4 | 1.2180 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.2180 | 1.0000 | 1.0000 | 0.2057 | 0.1689 | ||
PSZ-AC_5:5 | 1.2252 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.2252 | 1.0000 | 1.0000 | 0.2057 | 0.1679 | ||
PSZ-AC_6:6 | 2.2655 | 0.0000 | 29.9961 | 1.0000 | 0.4115 | 2.2655 | 1.0000 | 1.0000 | 0.4115 | 0.1816 | ||
PSZ-AC_7:7 | 1.2434 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.2434 | 1.0000 | 1.0000 | 0.2057 | 0.1655 | ||
PSZ-AC_8:8 | 1.2423 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.2423 | 1.0000 | 1.0000 | 0.2057 | 0.1656 | ||
PSZ-AC_9:9 | 1.2518 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.2518 | 1.0000 | 1.0000 | 0.2057 | 0.1643 | ||
PSZ-AC_10:10 | 1.3974 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.3974 | 1.0000 | 1.0000 | 0.2057 | 0.1472 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
LGSTORE1 | PSZ-AC_1:1 | 0.000000 | 29.9961 | 0.001181 | 348.39 | 0.4115 | 1.0000 | 0.4115 | 1.000 | 0.4115 |
SMSTORE1 | PSZ-AC_2:2 | 0.000000 | 14.9980 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE2 | PSZ-AC_3:3 | 0.000000 | 14.9980 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE3 | PSZ-AC_4:4 | 0.000000 | 14.9980 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE4 | PSZ-AC_5:5 | 0.000000 | 14.9980 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
LGSTORE2 | PSZ-AC_6:6 | 0.000000 | 29.9961 | 0.001181 | 348.39 | 0.4115 | 1.0000 | 0.4115 | 1.000 | 0.4115 |
SMSTORE5 | PSZ-AC_7:7 | 0.000000 | 14.9980 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE6 | PSZ-AC_8:8 | 0.000000 | 14.9980 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE7 | PSZ-AC_9:9 | 0.000000 | 14.9980 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE8 | PSZ-AC_10:10 | 0.000000 | 14.9980 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC_1:1 | 0.000000 | 30.00 | 0.001181 | 348.3864 | 0.4115 | 0.4115 | 0.4115 |
PSZ-AC_2:2 | 0.000000 | 15.00 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_3:3 | 0.000000 | 15.00 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_4:4 | 0.000000 | 15.00 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_5:5 | 0.000000 | 15.00 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_6:6 | 0.000000 | 30.00 | 0.001181 | 348.3864 | 0.4115 | 0.4115 | 0.4115 |
PSZ-AC_7:7 | 0.000000 | 15.00 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_8:8 | 0.000000 | 15.00 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_9:9 | 0.000000 | 15.00 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_10:10 | 0.000000 | 15.00 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LGSTORE1 | PSZ-AC_1:1 | 2.3422 | 2.3422 | 2.3422 | 0.4115 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE1 | PSZ-AC_2:2 | 1.2058 | 1.2058 | 1.2058 | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE2 | PSZ-AC_3:3 | 1.2150 | 1.2150 | 1.2150 | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE3 | PSZ-AC_4:4 | 1.2180 | 1.2180 | 1.2180 | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE4 | PSZ-AC_5:5 | 1.2252 | 1.2252 | 1.2252 | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
LGSTORE2 | PSZ-AC_6:6 | 2.2655 | 2.2655 | 2.2655 | 0.4115 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE5 | PSZ-AC_7:7 | 1.2434 | 1.2434 | 1.2434 | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE6 | PSZ-AC_8:8 | 1.2423 | 1.2423 | 1.2423 | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE7 | PSZ-AC_9:9 | 1.2518 | 1.2518 | 1.2518 | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE8 | PSZ-AC_10:10 | 1.3974 | 1.3974 | 1.3974 | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 2.3422 | 2.3422 | 2.3422 | 2.3422 | 0.4115 | 1.0000 |
PSZ-AC_2:2 | 1.2058 | 1.2058 | 1.2058 | 1.2058 | 0.2057 | 1.0000 |
PSZ-AC_3:3 | 1.2150 | 1.2150 | 1.2150 | 1.2150 | 0.2057 | 1.0000 |
PSZ-AC_4:4 | 1.2180 | 1.2180 | 1.2180 | 1.2180 | 0.2057 | 1.0000 |
PSZ-AC_5:5 | 1.2252 | 1.2252 | 1.2252 | 1.2252 | 0.2057 | 1.0000 |
PSZ-AC_6:6 | 2.2655 | 2.2655 | 2.2655 | 2.2655 | 0.4115 | 1.0000 |
PSZ-AC_7:7 | 1.2434 | 1.2434 | 1.2434 | 1.2434 | 0.2057 | 1.0000 |
PSZ-AC_8:8 | 1.2423 | 1.2423 | 1.2423 | 1.2423 | 0.2057 | 1.0000 |
PSZ-AC_9:9 | 1.2518 | 1.2518 | 1.2518 | 1.2518 | 0.2057 | 1.0000 |
PSZ-AC_10:10 | 1.3974 | 1.3974 | 1.3974 | 1.3974 | 0.2057 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LGSTORE1 | PSZ-AC_1:1 | 2.3422 | 2.3422 | 2.3422 | 0.4115 | 0.1757 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE1 | PSZ-AC_2:2 | 1.2058 | 1.2058 | 1.2058 | 0.2057 | 0.1706 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE2 | PSZ-AC_3:3 | 1.2150 | 1.2150 | 1.2150 | 0.2057 | 0.1693 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE3 | PSZ-AC_4:4 | 1.2180 | 1.2180 | 1.2180 | 0.2057 | 0.1689 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE4 | PSZ-AC_5:5 | 1.2252 | 1.2252 | 1.2252 | 0.2057 | 0.1679 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
LGSTORE2 | PSZ-AC_6:6 | 2.2655 | 2.2655 | 2.2655 | 0.4115 | 0.1816 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE5 | PSZ-AC_7:7 | 1.2434 | 1.2434 | 1.2434 | 0.2057 | 0.1655 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE6 | PSZ-AC_8:8 | 1.2423 | 1.2423 | 1.2423 | 0.2057 | 0.1656 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE7 | PSZ-AC_9:9 | 1.2518 | 1.2518 | 1.2518 | 0.2057 | 0.1643 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE8 | PSZ-AC_10:10 | 1.3974 | 1.3974 | 1.3974 | 0.2057 | 0.1472 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 2.3422 | 2.3422 | 2.3422 | 2.3422 | 0.4115 | 1.0000 |
PSZ-AC_2:2 | 1.2058 | 1.2058 | 1.2058 | 1.2058 | 0.2057 | 1.0000 |
PSZ-AC_3:3 | 1.2150 | 1.2150 | 1.2150 | 1.2150 | 0.2057 | 1.0000 |
PSZ-AC_4:4 | 1.2180 | 1.2180 | 1.2180 | 1.2180 | 0.2057 | 1.0000 |
PSZ-AC_5:5 | 1.2252 | 1.2252 | 1.2252 | 1.2252 | 0.2057 | 1.0000 |
PSZ-AC_6:6 | 2.2655 | 2.2655 | 2.2655 | 2.2655 | 0.4115 | 1.0000 |
PSZ-AC_7:7 | 1.2434 | 1.2434 | 1.2434 | 1.2434 | 0.2057 | 1.0000 |
PSZ-AC_8:8 | 1.2423 | 1.2423 | 1.2423 | 1.2423 | 0.2057 | 1.0000 |
PSZ-AC_9:9 | 1.2518 | 1.2518 | 1.2518 | 1.2518 | 0.2057 | 1.0000 |
PSZ-AC_10:10 | 1.3974 | 1.3974 | 1.3974 | 1.3974 | 0.2057 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2020-06-03 19:18:54
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Rochester International Arpt MN USA TMY3 WMO#=726440 |
Total gross floor area [m2] | 2090.32 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
LGSTORE1 | 348.39 | 348.39 | 0.00 | 112.00 |
SMSTORE1 | 174.19 | 174.19 | 0.00 | 112.00 |
SMSTORE2 | 174.19 | 174.19 | 0.00 | 84.29 |
SMSTORE3 | 174.19 | 174.19 | 0.00 | 84.29 |
SMSTORE4 | 174.19 | 174.19 | 0.00 | 84.29 |
LGSTORE2 | 348.39 | 348.39 | 0.00 | 77.29 |
SMSTORE5 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE6 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE7 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE8 | 174.19 | 174.19 | 0.00 | 77.29 |
Totals | 2090.32 | 2090.32 | 0.00 |
Data | |
Number of hours heating loads not met | 8.33 |
Number of hours cooling loads not met | 0.00 |
Number of hours not met | 8.33 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Fuel Use [GJ] | Additional Fuel Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- Not Subdivided | 0.00 | 0.00 | 1027.68 | 441652.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- Not Subdivided | 125.16 | 76736.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 704.17 | 43812.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 110.65 | 7048.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 128.72 | 8089.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 283.42 | 16442.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 66.30 | 11884.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 128.72 | 1418.42 |
Natural Gas | 0.00 | 1027.68 |
Additional | 0.00 | 0.00 |
Total | 128.72 | 2446.10 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 336.87 |
Space Heating | 0.00 |
Space Cooling | 59.88 |
Fans (All) | 135.58 |
Service Water Heating | 31.72 |
Receptacle Equipment | 61.58 |
Miscellaneous (All) | 678.57 |
Subtotal | 678.57 |
Natural Gas [MJ/m2] | |
Space Heating | 491.64 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 491.64 |
Subtotal | 491.64 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 28.79 |
Space Heating | 42.01 |
Space Cooling | 5.12 |
Fans (All) | 11.59 |
Service Water Heating | 2.71 |
Receptacle Equipment | 5.26 |
Miscellaneous | 4.52 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
TYPE1_OCC_SCH | 1630. | 5840. |
TYPE2_OCC_SCH | 995. | 4429. |
TYPE3_OCC_SCH | 1709. | 4064. |
TYPE1_LIGHT_SCH | 5131. | 8760. |
TYPE2_LIGHT_SCH | 4096. | 8760. |
TYPE3_LIGHT_SCH | 3767. | 8760. |
TYPE1_EQUIP_SCH | 4888. | 8760. |
TYPE2_EQUIP_SCH | 3911. | 8760. |
TYPE3_EQUIP_SCH | 3600. | 8760. |
TYPE1_INFIL_SCH | 4302. | 8760. |
TYPE2_INFIL_SCH | 5164. | 8760. |
TYPE3_INFIL_SCH | 5438. | 8760. |
INFIL_DOOR_OPENING_SCH | 2505. | 4380. |
TYPE1_MINOA_MOTORIZEDDAMPER_SCH | 5579. | 5579. |
TYPE2_MINOA_MOTORIZEDDAMPER_SCH | 4429. | 4429. |
TYPE3_MINOA_MOTORIZEDDAMPER_SCH | 4064. | 4064. |
TYPE1_SWH_SCH | 2063. | 6048. |
TYPE2_SWH_SCH | 1831. | 4429. |
TYPE3_SWH_SCH | 1733. | 4064. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 7118. | 8760. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 5839. | 5839. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 7300. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
TYPE1_HTGSETP_SCH_NO_OPTIMUM | LGSTORE1 DUALSPSCHED | January | 21.11 | 365 | 21.11 | 365 |
TYPE1_CLGSETP_SCH_NO_OPTIMUM | LGSTORE1 DUALSPSCHED | July | 23.89 | 365 | 23.89 | 365 |
TYPE2_HTGSETP_SCH_NO_OPTIMUM | SMSTORE2 DUALSPSCHED | January | 21.11 | 365 | 15.56 | 365 |
TYPE2_CLGSETP_SCH_NO_OPTIMUM | SMSTORE2 DUALSPSCHED | July | 23.89 | 365 | 29.44 | 365 |
TYPE3_HTGSETP_SCH_NO_OPTIMUM | LGSTORE2 DUALSPSCHED | January | 21.11 | 365 | 15.56 | 365 |
TYPE3_CLGSETP_SCH_NO_OPTIMUM | LGSTORE2 DUALSPSCHED | July | 23.89 | 365 | 29.44 | 365 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Meter
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.287607E+12 |
February | 0.000 | 0.200498E+12 |
March | 0.000 | 0.120872E+12 |
April | 0.000 | 0.548954E+11 |
May | 0.000 | 0.217374E+10 |
June | 0.000 | 0.173262E+09 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.164854E+10 |
October | 0.000 | 0.200825E+11 |
November | 0.000 | 0.117543E+12 |
December | 0.000 | 0.222187E+12 |
Annual Sum or Average | 0.102768E+13 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.287607E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Meter
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.287607E+12 |
February | 0.000 | 0.200498E+12 |
March | 0.000 | 0.120872E+12 |
April | 0.000 | 0.548954E+11 |
May | 0.000 | 0.217374E+10 |
June | 0.000 | 0.173262E+09 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.164854E+10 |
October | 0.000 | 0.200825E+11 |
November | 0.000 | 0.117543E+12 |
December | 0.000 | 0.222187E+12 |
Annual Sum or Average | 0.102768E+13 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.287607E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2009
For: Meter
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.287607E+12 |
February | 0.000 | 0.200498E+12 |
March | 0.000 | 0.120872E+12 |
April | 0.000 | 0.548954E+11 |
May | 0.000 | 0.217374E+10 |
June | 0.000 | 0.173262E+09 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.164854E+10 |
October | 0.000 | 0.200825E+11 |
November | 0.000 | 0.117543E+12 |
December | 0.000 | 0.222187E+12 |
Annual Sum or Average | 0.102768E+13 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.287607E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Meter
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.287607E+12 |
February | 0.000 | 0.200498E+12 |
March | 0.000 | 0.120872E+12 |
April | 0.000 | 0.548954E+11 |
May | 0.000 | 0.217374E+10 |
June | 0.000 | 0.173262E+09 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.164854E+10 |
October | 0.000 | 0.200825E+11 |
November | 0.000 | 0.117543E+12 |
December | 0.000 | 0.222187E+12 |
Annual Sum or Average | 0.102768E+13 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.287607E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTRIPMALL
For: Meter
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.287607E+12 |
February | 0.000 | 0.200498E+12 |
March | 0.000 | 0.120872E+12 |
April | 0.000 | 0.548954E+11 |
May | 0.000 | 0.217374E+10 |
June | 0.000 | 0.173262E+09 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.164854E+10 |
October | 0.000 | 0.200825E+11 |
November | 0.000 | 0.117543E+12 |
December | 0.000 | 0.222187E+12 |
Annual Sum or Average | 0.102768E+13 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.287607E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.287607E+12 |
February | 0.000 | 0.200498E+12 |
March | 0.000 | 0.120872E+12 |
April | 0.000 | 0.548954E+11 |
May | 0.000 | 0.217374E+10 |
June | 0.000 | 0.173262E+09 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.164854E+10 |
October | 0.000 | 0.200825E+11 |
November | 0.000 | 0.117543E+12 |
December | 0.000 | 0.222187E+12 |
Annual Sum or Average | 0.102768E+13 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.287607E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.287607E+12 |
February | 0.000 | 0.200498E+12 |
March | 0.000 | 0.120872E+12 |
April | 0.000 | 0.548954E+11 |
May | 0.000 | 0.217374E+10 |
June | 0.000 | 0.173262E+09 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.164854E+10 |
October | 0.000 | 0.200825E+11 |
November | 0.000 | 0.117543E+12 |
December | 0.000 | 0.222187E+12 |
Annual Sum or Average | 0.102768E+13 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.287607E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 6A
For: Meter
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.287607E+12 |
February | 0.000 | 0.200498E+12 |
March | 0.000 | 0.120872E+12 |
April | 0.000 | 0.548954E+11 |
May | 0.000 | 0.217374E+10 |
June | 0.000 | 0.173262E+09 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.164854E+10 |
October | 0.000 | 0.200825E+11 |
November | 0.000 | 0.117543E+12 |
December | 0.000 | 0.222187E+12 |
Annual Sum or Average | 0.102768E+13 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.287607E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_ROCHESTER
For: Meter
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.287607E+12 |
February | 0.000 | 0.200498E+12 |
March | 0.000 | 0.120872E+12 |
April | 0.000 | 0.548954E+11 |
May | 0.000 | 0.217374E+10 |
June | 0.000 | 0.173262E+09 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.164854E+10 |
October | 0.000 | 0.200825E+11 |
November | 0.000 | 0.117543E+12 |
December | 0.000 | 0.222187E+12 |
Annual Sum or Average | 0.102768E+13 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.287607E+12 |
Report: ZoneCoolingSummaryMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.378273E+09 | 18192.80 | 06-JAN-00:01 | -25.1 | -25.3 | 0.567718E+09 | 680.12 | 21-JAN-13:09 | -5.9 | -6.6 |
February | 0.579451E+09 | 21714.81 | 03-FEB-00:01 | -32.8 | -32.9 | 0.512628E+09 | 680.12 | 24-FEB-13:09 | 6.88 | 4.27 |
March | 0.153299E+10 | 11182.10 | 11-MAR-00:23 | -10.6 | -11.0 | 0.577777E+09 | 898.99 | 19-MAR-17:10 | 17.93 | 13.47 |
April | 0.393884E+10 | 13207.96 | 16-APR-16:04 | 28.80 | 20.53 | 0.606801E+09 | 898.99 | 30-APR-17:19 | 15.60 | 8.86 |
May | 0.787452E+10 | 13965.56 | 31-MAY-15:00 | 30.00 | 19.68 | 0.728969E+09 | 899.01 | 14-MAY-12:30 | 20.00 | 14.49 |
June | 0.133584E+11 | 32657.30 | 28-JUN-07:02 | 21.57 | 18.56 | 0.715845E+09 | 898.99 | 04-JUN-17:19 | 13.70 | 10.68 |
July | 0.162794E+11 | 33413.25 | 28-JUL-07:02 | 20.87 | 18.05 | 0.753566E+09 | 899.02 | 22-JUL-12:20 | 19.60 | 14.21 |
August | 0.162555E+11 | 29558.25 | 23-AUG-07:03 | 18.40 | 17.23 | 0.743036E+09 | 899.02 | 19-AUG-12:00 | 19.40 | 18.26 |
September | 0.122091E+11 | 33301.77 | 08-SEP-07:02 | 17.03 | 15.56 | 0.704796E+09 | 899.03 | 15-SEP-12:20 | 20.37 | 12.73 |
October | 0.541438E+10 | 7296.19 | 31-OCT-18:00 | 0.00 | -1.7 | 0.636020E+09 | 899.02 | 20-OCT-12:00 | 21.80 | 12.59 |
November | 0.220499E+10 | 12770.00 | 25-NOV-00:12 | -13.5 | -13.8 | 0.579418E+09 | 898.96 | 03-NOV-12:00 | 15.60 | 11.01 |
December | 0.531301E+09 | 17082.17 | 09-DEC-00:01 | -22.8 | -23.0 | 0.570648E+09 | 680.12 | 16-DEC-13:20 | -4.4 | -5.9 |
Annual Sum or Average | 0.805571E+11 | 0.769722E+10 | ||||||||
Minimum of Months | 0.378273E+09 | 7296.19 | -32.8 | -32.9 | 0.512628E+09 | 680.12 | -5.9 | -6.6 | ||
Maximum of Months | 0.162794E+11 | 33413.25 | 30.00 | 20.53 | 0.753566E+09 | 899.03 | 21.80 | 18.26 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 77210094.46 | 5907.18 | 02-JAN-18:03 | -12.0 | -12.6 | 0.286018E+09 | 356.74 | 01-JAN-18:00 | -1.1 | -1.4 |
February | 0.232557E+09 | 2708.14 | 24-FEB-20:10 | 3.12 | 2.38 | 0.261374E+09 | 381.31 | 20-FEB-18:00 | -1.1 | -3.4 |
March | 0.826124E+09 | 3482.59 | 20-MAR-19:40 | 0.57 | -1.1 | 0.300658E+09 | 449.50 | 19-MAR-16:10 | 18.80 | 13.88 |
April | 0.230311E+10 | 26699.98 | 19-APR-20:02 | 8.72 | 4.75 | 0.316167E+09 | 449.51 | 14-APR-12:00 | 20.60 | 16.23 |
May | 0.520798E+10 | 27568.61 | 21-MAY-19:42 | 12.77 | 7.02 | 0.367748E+09 | 449.51 | 14-MAY-12:09 | 19.60 | 14.24 |
June | 0.796921E+10 | 22827.84 | 23-JUN-22:40 | 18.17 | 13.68 | 0.358393E+09 | 449.50 | 04-JUN-12:09 | 14.50 | 11.48 |
July | 0.945502E+10 | 23345.65 | 23-JUL-20:57 | 19.40 | 13.32 | 0.374514E+09 | 449.51 | 22-JUL-12:09 | 19.50 | 14.17 |
August | 0.932581E+10 | 26336.45 | 06-AUG-19:15 | 15.90 | 10.99 | 0.369036E+09 | 449.51 | 19-AUG-12:00 | 19.40 | 18.26 |
September | 0.693914E+10 | 28141.54 | 24-SEP-17:01 | 13.53 | 6.95 | 0.356278E+09 | 449.53 | 01-SEP-12:00 | 23.30 | 13.91 |
October | 0.276000E+10 | 27026.14 | 11-OCT-20:29 | 11.85 | 6.49 | 0.336433E+09 | 449.51 | 20-OCT-12:00 | 21.80 | 12.59 |
November | 0.111753E+10 | 4300.14 | 05-NOV-17:10 | 10.63 | 7.95 | 0.300026E+09 | 449.50 | 05-NOV-16:10 | 14.35 | 10.15 |
December | 0.156822E+09 | 3882.46 | 17-DEC-11:03 | -3.1 | -3.9 | 0.290781E+09 | 387.53 | 03-DEC-18:00 | 0.60 | -0.6 |
Annual Sum or Average | 0.463705E+11 | 0.391743E+10 | ||||||||
Minimum of Months | 77210094.46 | 2708.14 | -12.0 | -12.6 | 0.261374E+09 | 356.74 | -1.1 | -3.4 | ||
Maximum of Months | 0.945502E+10 | 28141.54 | 19.40 | 13.68 | 0.374514E+09 | 449.53 | 23.30 | 18.26 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 26001387.52 | 1396.17 | 13-JAN-18:07 | 1.93 | 0.57 | 0.169144E+09 | 340.06 | 21-JAN-13:09 | -5.9 | -6.6 |
February | 0.102047E+09 | 2967.71 | 10-FEB-11:43 | 1.20 | -0.3 | 0.153637E+09 | 340.06 | 18-FEB-13:30 | -6.7 | -7.9 |
March | 0.496681E+09 | 4986.00 | 16-MAR-19:55 | -7.8 | -9.1 | 0.177909E+09 | 370.29 | 23-MAR-17:49 | 14.27 | 9.13 |
April | 0.152406E+10 | 7097.24 | 18-APR-14:00 | 28.30 | 20.64 | 0.182042E+09 | 449.44 | 15-APR-12:09 | 27.88 | 20.23 |
May | 0.327400E+10 | 13245.12 | 13-MAY-06:01 | 12.98 | 12.64 | 0.221844E+09 | 449.50 | 27-MAY-12:09 | 20.28 | 16.28 |
June | 0.569028E+10 | 18687.30 | 28-JUN-06:02 | 19.27 | 17.31 | 0.220868E+09 | 449.49 | 03-JUN-12:00 | 13.90 | 10.75 |
July | 0.668850E+10 | 20678.91 | 01-JUL-06:02 | 17.15 | 15.45 | 0.224113E+09 | 449.51 | 22-JUL-12:09 | 19.50 | 14.17 |
August | 0.684440E+10 | 21356.60 | 06-AUG-07:01 | 13.22 | 11.57 | 0.230205E+09 | 449.51 | 19-AUG-12:00 | 19.40 | 18.26 |
September | 0.486459E+10 | 23716.02 | 08-SEP-06:02 | 14.27 | 13.20 | 0.212366E+09 | 449.49 | 23-SEP-12:09 | 19.60 | 10.56 |
October | 0.187803E+10 | 3967.82 | 20-OCT-15:00 | 23.30 | 13.34 | 0.189639E+09 | 449.49 | 21-OCT-12:09 | 19.02 | 12.94 |
November | 0.701623E+09 | 5536.04 | 21-NOV-20:23 | -10.3 | -11.0 | 0.172945E+09 | 443.48 | 04-NOV-12:00 | 13.90 | 6.79 |
December | 32549164.78 | 3635.42 | 29-DEC-18:23 | -2.0 | -2.7 | 0.168940E+09 | 340.06 | 16-DEC-13:20 | -4.4 | -5.9 |
Annual Sum or Average | 0.321228E+11 | 0.232365E+10 | ||||||||
Minimum of Months | 26001387.52 | 1396.17 | -10.3 | -11.0 | 0.153637E+09 | 340.06 | -6.7 | -7.9 | ||
Maximum of Months | 0.684440E+10 | 23716.02 | 28.30 | 20.64 | 0.230205E+09 | 449.51 | 27.88 | 20.23 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 23661204.48 | 4141.53 | 11-JAN-18:43 | -4.4 | -4.8 | 0.169144E+09 | 340.06 | 21-JAN-13:09 | -5.9 | -6.6 |
February | 80987297.93 | 2616.13 | 07-FEB-11:55 | 2.20 | 0.77 | 0.153634E+09 | 340.06 | 18-FEB-13:30 | -6.7 | -7.9 |
March | 0.422802E+09 | 3046.76 | 25-MAR-07:01 | 1.28 | 0.13 | 0.177395E+09 | 366.63 | 23-MAR-17:49 | 14.27 | 9.13 |
April | 0.143089E+10 | 7048.61 | 18-APR-14:00 | 28.30 | 20.64 | 0.181430E+09 | 449.45 | 15-APR-12:09 | 27.88 | 20.23 |
May | 0.314352E+10 | 11666.42 | 13-MAY-06:01 | 12.98 | 12.64 | 0.221485E+09 | 449.50 | 27-MAY-12:09 | 20.28 | 16.28 |
June | 0.566640E+10 | 18762.73 | 28-JUN-06:02 | 19.27 | 17.31 | 0.220652E+09 | 449.46 | 17-JUN-12:09 | 26.02 | 17.80 |
July | 0.670041E+10 | 20756.62 | 01-JUL-06:02 | 17.15 | 15.45 | 0.224112E+09 | 449.51 | 22-JUL-12:09 | 19.50 | 14.17 |
August | 0.684286E+10 | 22059.10 | 06-AUG-07:01 | 13.22 | 11.57 | 0.230203E+09 | 449.51 | 19-AUG-12:00 | 19.40 | 18.26 |
September | 0.482535E+10 | 23794.98 | 08-SEP-06:02 | 14.27 | 13.20 | 0.211757E+09 | 449.49 | 23-SEP-12:09 | 19.60 | 10.56 |
October | 0.168365E+10 | 3802.29 | 23-OCT-07:01 | -1.2 | -2.5 | 0.187939E+09 | 449.49 | 21-OCT-12:09 | 19.02 | 12.94 |
November | 0.625991E+09 | 3697.58 | 04-NOV-07:01 | 0.37 | -1.1 | 0.171984E+09 | 436.46 | 04-NOV-12:00 | 13.90 | 6.79 |
December | 20387901.17 | 4256.03 | 05-DEC-11:23 | -5.0 | -7.5 | 0.168939E+09 | 340.06 | 16-DEC-13:20 | -4.4 | -5.9 |
Annual Sum or Average | 0.314669E+11 | 0.231867E+10 | ||||||||
Minimum of Months | 20387901.17 | 2616.13 | -5.0 | -7.5 | 0.153634E+09 | 340.06 | -6.7 | -7.9 | ||
Maximum of Months | 0.684286E+10 | 23794.98 | 28.30 | 20.64 | 0.230203E+09 | 449.51 | 27.88 | 20.23 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 13630810.69 | 1006.16 | 13-JAN-18:07 | 1.93 | 0.57 | 0.169144E+09 | 340.06 | 21-JAN-13:09 | -5.9 | -6.6 |
February | 51669268.71 | 3251.63 | 10-FEB-20:13 | -0.2 | -0.7 | 0.153637E+09 | 340.06 | 18-FEB-13:30 | -6.7 | -7.9 |
March | 0.331886E+09 | 2433.85 | 20-MAR-07:01 | 4.68 | 3.31 | 0.176810E+09 | 360.29 | 23-MAR-17:49 | 14.27 | 9.13 |
April | 0.126831E+10 | 6857.23 | 18-APR-14:00 | 28.30 | 20.64 | 0.180571E+09 | 449.45 | 15-APR-12:09 | 27.88 | 20.23 |
May | 0.285593E+10 | 7644.94 | 13-MAY-06:01 | 12.98 | 12.64 | 0.220662E+09 | 449.50 | 27-MAY-12:09 | 20.28 | 16.28 |
June | 0.543607E+10 | 18720.68 | 28-JUN-06:02 | 19.27 | 17.31 | 0.220037E+09 | 449.47 | 17-JUN-12:09 | 26.02 | 17.80 |
July | 0.648024E+10 | 20279.37 | 01-JUL-06:02 | 17.15 | 15.45 | 0.224095E+09 | 449.51 | 22-JUL-12:09 | 19.50 | 14.17 |
August | 0.661001E+10 | 19669.47 | 06-AUG-07:01 | 13.22 | 11.57 | 0.230185E+09 | 449.51 | 19-AUG-12:00 | 19.40 | 18.26 |
September | 0.461898E+10 | 23785.42 | 08-SEP-06:02 | 14.27 | 13.20 | 0.210711E+09 | 449.49 | 23-SEP-12:09 | 19.60 | 10.56 |
October | 0.143957E+10 | 3743.11 | 23-OCT-07:01 | -1.2 | -2.5 | 0.185912E+09 | 449.49 | 21-OCT-12:09 | 19.02 | 12.94 |
November | 0.528382E+09 | 3694.58 | 13-NOV-19:03 | -2.3 | -3.2 | 0.170573E+09 | 425.49 | 04-NOV-12:00 | 13.90 | 6.79 |
December | 11086060.30 | 4735.56 | 05-DEC-20:03 | -6.7 | -9.0 | 0.168940E+09 | 340.06 | 16-DEC-13:20 | -4.4 | -5.9 |
Annual Sum or Average | 0.296458E+11 | 0.231128E+10 | ||||||||
Minimum of Months | 11086060.30 | 1006.16 | -6.7 | -9.0 | 0.153637E+09 | 340.06 | -6.7 | -7.9 | ||
Maximum of Months | 0.661001E+10 | 23785.42 | 28.30 | 20.64 | 0.230185E+09 | 449.51 | 27.88 | 20.23 |
Report: ZoneCoolingSummaryMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 3186978.83 | 5930.60 | 13-JAN-18:03 | 1.93 | 0.57 | 0.578272E+09 | 906.82 | 21-JAN-15:00 | -4.4 | -5.3 |
February | 15663631.68 | 1523.32 | 24-FEB-12:00 | 6.10 | 3.15 | 0.526488E+09 | 906.82 | 18-FEB-15:09 | -6.7 | -7.5 |
March | 0.301989E+09 | 3611.34 | 24-MAR-18:20 | 7.80 | 4.23 | 0.603457E+09 | 1123.24 | 25-MAR-14:00 | 18.90 | 10.41 |
April | 0.169314E+10 | 11576.55 | 18-APR-14:10 | 28.30 | 20.64 | 0.612849E+09 | 1198.53 | 15-APR-14:09 | 29.50 | 20.38 |
May | 0.398962E+10 | 12974.19 | 31-MAY-15:00 | 30.00 | 19.68 | 0.744774E+09 | 1198.66 | 06-MAY-14:00 | 21.10 | 11.56 |
June | 0.868339E+10 | 32864.52 | 12-JUN-07:03 | 18.48 | 17.31 | 0.746960E+09 | 1198.63 | 17-JUN-14:09 | 24.18 | 18.98 |
July | 0.104060E+11 | 33217.13 | 28-JUL-07:02 | 20.87 | 18.05 | 0.766917E+09 | 1198.64 | 22-JUL-14:00 | 20.60 | 14.31 |
August | 0.106465E+11 | 30953.06 | 14-AUG-07:02 | 16.57 | 16.08 | 0.789086E+09 | 1198.70 | 12-AUG-14:50 | 22.25 | 17.58 |
September | 0.723424E+10 | 35675.27 | 12-SEP-07:02 | 15.93 | 14.77 | 0.714412E+09 | 1198.66 | 23-SEP-14:00 | 20.60 | 11.38 |
October | 0.176207E+10 | 5200.75 | 20-OCT-15:00 | 23.30 | 13.34 | 0.620966E+09 | 1198.68 | 21-OCT-14:00 | 21.10 | 14.39 |
November | 0.704263E+09 | 7303.33 | 10-NOV-18:17 | -1.3 | -2.9 | 0.570538E+09 | 1126.56 | 04-NOV-14:00 | 14.40 | 6.79 |
December | 1284512.75 | 867.99 | 02-DEC-12:00 | 5.00 | 2.78 | 0.579251E+09 | 906.82 | 16-DEC-15:09 | -2.8 | -4.1 |
Annual Sum or Average | 0.454414E+11 | 0.785397E+10 | ||||||||
Minimum of Months | 1284512.75 | 867.99 | -1.3 | -2.9 | 0.526488E+09 | 906.82 | -6.7 | -7.5 | ||
Maximum of Months | 0.106465E+11 | 35675.27 | 30.00 | 20.64 | 0.789086E+09 | 1198.70 | 29.50 | 20.38 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 198992.87 | 201.04 | 13-JAN-12:00 | 3.90 | 1.49 | 0.289135E+09 | 453.41 | 21-JAN-15:00 | -4.4 | -5.3 |
February | 5807829.33 | 657.88 | 24-FEB-12:00 | 6.10 | 3.15 | 0.263244E+09 | 453.41 | 18-FEB-15:09 | -6.7 | -7.5 |
March | 0.118214E+09 | 4246.81 | 21-MAR-19:03 | -5.1 | -7.0 | 0.301547E+09 | 556.45 | 25-MAR-14:00 | 18.90 | 10.41 |
April | 0.781499E+09 | 5994.89 | 18-APR-14:10 | 28.30 | 20.64 | 0.306039E+09 | 599.26 | 15-APR-14:09 | 29.50 | 20.38 |
May | 0.183777E+10 | 6770.21 | 31-MAY-15:00 | 30.00 | 19.68 | 0.371536E+09 | 599.33 | 06-MAY-14:00 | 21.10 | 11.56 |
June | 0.435384E+10 | 17683.67 | 28-JUN-07:02 | 21.57 | 18.56 | 0.373024E+09 | 599.31 | 17-JUN-14:09 | 24.18 | 18.98 |
July | 0.528760E+10 | 17946.25 | 28-JUL-07:02 | 20.87 | 18.05 | 0.383458E+09 | 599.32 | 22-JUL-14:00 | 20.60 | 14.31 |
August | 0.540586E+10 | 14411.67 | 14-AUG-07:02 | 16.57 | 16.08 | 0.394544E+09 | 599.35 | 12-AUG-14:50 | 22.25 | 17.58 |
September | 0.358554E+10 | 17112.93 | 11-SEP-07:03 | 20.37 | 17.94 | 0.356981E+09 | 599.33 | 23-SEP-14:00 | 20.60 | 11.38 |
October | 0.728883E+09 | 2617.01 | 20-OCT-15:00 | 23.30 | 13.34 | 0.309902E+09 | 599.33 | 21-OCT-14:00 | 21.10 | 14.39 |
November | 0.281111E+09 | 2237.85 | 04-NOV-17:15 | 7.07 | 3.15 | 0.284784E+09 | 557.69 | 04-NOV-14:00 | 14.40 | 6.79 |
December | 308150.66 | 289.76 | 02-DEC-12:00 | 5.00 | 2.78 | 0.289625E+09 | 453.41 | 16-DEC-15:09 | -2.8 | -4.1 |
Annual Sum or Average | 0.223866E+11 | 0.392382E+10 | ||||||||
Minimum of Months | 198992.87 | 201.04 | -5.1 | -7.0 | 0.263244E+09 | 453.41 | -6.7 | -7.5 | ||
Maximum of Months | 0.540586E+10 | 17946.25 | 30.00 | 20.64 | 0.394544E+09 | 599.35 | 29.50 | 20.38 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 123931.78 | 147.94 | 13-JAN-12:00 | 3.90 | 1.49 | 0.289135E+09 | 453.41 | 21-JAN-15:00 | -4.4 | -5.3 |
February | 4714587.90 | 600.13 | 24-FEB-12:00 | 6.10 | 3.15 | 0.263244E+09 | 453.41 | 18-FEB-15:09 | -6.7 | -7.5 |
March | 0.103839E+09 | 3599.40 | 21-MAR-17:43 | -2.0 | -4.9 | 0.301333E+09 | 553.07 | 25-MAR-14:00 | 18.90 | 10.41 |
April | 0.737068E+09 | 5875.19 | 18-APR-14:10 | 28.30 | 20.64 | 0.305546E+09 | 599.26 | 15-APR-14:09 | 29.50 | 20.38 |
May | 0.171968E+10 | 6670.71 | 31-MAY-15:00 | 30.00 | 19.68 | 0.370011E+09 | 599.33 | 06-MAY-14:00 | 21.10 | 11.56 |
June | 0.424905E+10 | 17611.88 | 28-JUN-07:02 | 21.57 | 18.56 | 0.372418E+09 | 599.31 | 17-JUN-14:09 | 24.18 | 18.98 |
July | 0.518782E+10 | 17880.01 | 28-JUL-07:02 | 20.87 | 18.05 | 0.383452E+09 | 599.32 | 22-JUL-14:00 | 20.60 | 14.31 |
August | 0.530683E+10 | 13507.84 | 28-AUG-07:03 | 18.98 | 18.65 | 0.394539E+09 | 599.35 | 12-AUG-14:50 | 22.25 | 17.58 |
September | 0.350201E+10 | 16464.36 | 11-SEP-07:03 | 20.37 | 17.94 | 0.356441E+09 | 599.33 | 23-SEP-14:00 | 20.60 | 11.38 |
October | 0.679350E+09 | 2521.49 | 20-OCT-15:00 | 23.30 | 13.34 | 0.309076E+09 | 599.33 | 21-OCT-14:00 | 21.10 | 14.39 |
November | 0.261777E+09 | 2212.47 | 04-NOV-17:15 | 7.07 | 3.15 | 0.284187E+09 | 552.96 | 04-NOV-14:00 | 14.40 | 6.79 |
December | 221065.52 | 239.98 | 02-DEC-12:00 | 5.00 | 2.78 | 0.289625E+09 | 453.41 | 16-DEC-15:09 | -2.8 | -4.1 |
Annual Sum or Average | 0.217525E+11 | 0.391901E+10 | ||||||||
Minimum of Months | 123931.78 | 147.94 | -2.0 | -4.9 | 0.263244E+09 | 453.41 | -6.7 | -7.5 | ||
Maximum of Months | 0.530683E+10 | 17880.01 | 30.00 | 20.64 | 0.394539E+09 | 599.35 | 29.50 | 20.38 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | -2.8 | -3.2 | 0.289135E+09 | 453.41 | 21-JAN-15:00 | -4.4 | -5.3 |
February | 2330170.67 | 2500.04 | 25-FEB-11:15 | 2.57 | 1.05 | 0.263242E+09 | 453.41 | 18-FEB-15:09 | -6.7 | -7.5 |
March | 67812631.98 | 2687.43 | 22-MAR-18:35 | 1.67 | 0.24 | 0.300755E+09 | 543.40 | 25-MAR-14:00 | 18.90 | 10.41 |
April | 0.622256E+09 | 5565.65 | 18-APR-14:20 | 28.30 | 20.64 | 0.304202E+09 | 599.27 | 15-APR-14:09 | 29.50 | 20.38 |
May | 0.143891E+10 | 6449.09 | 31-MAY-15:00 | 30.00 | 19.68 | 0.365770E+09 | 599.33 | 06-MAY-14:00 | 21.10 | 11.56 |
June | 0.401287E+10 | 16377.69 | 28-JUN-07:02 | 21.57 | 18.56 | 0.371014E+09 | 599.31 | 17-JUN-14:09 | 24.18 | 18.98 |
July | 0.497878E+10 | 16808.80 | 03-JUL-07:02 | 20.37 | 18.84 | 0.383429E+09 | 599.32 | 22-JUL-14:00 | 20.60 | 14.31 |
August | 0.510433E+10 | 12947.13 | 03-AUG-07:02 | 24.18 | 22.73 | 0.394528E+09 | 599.35 | 12-AUG-14:50 | 22.25 | 17.58 |
September | 0.331897E+10 | 14645.71 | 11-SEP-07:03 | 20.37 | 17.94 | 0.355158E+09 | 599.33 | 23-SEP-14:00 | 20.60 | 11.38 |
October | 0.551260E+09 | 2294.42 | 20-OCT-15:00 | 23.30 | 13.34 | 0.307329E+09 | 599.33 | 21-OCT-14:39 | 20.87 | 14.25 |
November | 0.219602E+09 | 2654.66 | 16-NOV-18:05 | 1.78 | -0.6 | 0.283096E+09 | 544.12 | 04-NOV-14:00 | 14.40 | 6.79 |
December | 15891.68 | 26.49 | 02-DEC-12:00 | 5.00 | 2.78 | 0.289625E+09 | 453.41 | 16-DEC-15:09 | -2.8 | -4.1 |
Annual Sum or Average | 0.203171E+11 | 0.390728E+10 | ||||||||
Minimum of Months | 0.00 | 0.00 | -2.8 | -3.2 | 0.263242E+09 | 453.41 | -6.7 | -7.5 | ||
Maximum of Months | 0.510433E+10 | 16808.80 | 30.00 | 22.73 | 0.394528E+09 | 599.35 | 29.50 | 20.38 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | -2.8 | -3.2 | 0.289136E+09 | 453.41 | 21-JAN-15:00 | -4.4 | -5.3 |
February | 0.00 | 0.00 | 01-FEB-00:02 | -24.1 | -24.4 | 0.263244E+09 | 453.41 | 18-FEB-15:09 | -6.7 | -7.5 |
March | 4644889.51 | 488.67 | 24-MAR-17:10 | 9.82 | 5.11 | 0.299442E+09 | 511.39 | 25-MAR-14:00 | 18.90 | 10.41 |
April | 0.391580E+09 | 5057.01 | 18-APR-14:10 | 28.30 | 20.64 | 0.301035E+09 | 599.28 | 15-APR-14:09 | 29.50 | 20.38 |
May | 0.880912E+09 | 6084.51 | 31-MAY-15:00 | 30.00 | 19.68 | 0.354974E+09 | 599.33 | 06-MAY-14:00 | 21.10 | 11.56 |
June | 0.355965E+10 | 14055.62 | 26-JUN-07:02 | 23.58 | 21.50 | 0.367994E+09 | 599.32 | 17-JUN-14:09 | 24.18 | 18.98 |
July | 0.462665E+10 | 16994.68 | 04-JUL-08:62 | 22.30 | 19.60 | 0.383271E+09 | 599.32 | 22-JUL-14:00 | 20.60 | 14.31 |
August | 0.482009E+10 | 12066.81 | 03-AUG-07:02 | 24.18 | 22.73 | 0.394498E+09 | 599.35 | 12-AUG-14:50 | 22.25 | 17.58 |
September | 0.303737E+10 | 8777.65 | 07-SEP-14:10 | 32.12 | 18.40 | 0.352354E+09 | 599.33 | 23-SEP-14:00 | 20.60 | 11.38 |
October | 0.235693E+09 | 2225.43 | 25-OCT-17:45 | 3.05 | 0.62 | 0.304621E+09 | 599.33 | 21-OCT-14:50 | 20.98 | 14.32 |
November | 0.101581E+09 | 1793.10 | 04-NOV-17:15 | 7.07 | 3.15 | 0.281624E+09 | 528.82 | 04-NOV-14:00 | 14.40 | 6.79 |
December | 0.00 | 0.00 | 01-DEC-00:03 | -0.7 | -1.2 | 0.289625E+09 | 453.41 | 16-DEC-15:09 | -2.8 | -4.1 |
Annual Sum or Average | 0.176582E+11 | 0.388182E+10 | ||||||||
Minimum of Months | 0.00 | 0.00 | -24.1 | -24.4 | 0.263244E+09 | 453.41 | -6.7 | -7.5 | ||
Maximum of Months | 0.482009E+10 | 16994.68 | 32.12 | 22.73 | 0.394498E+09 | 599.35 | 29.50 | 20.38 |
Report: ZoneHeatingSummaryMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.199767E+11 | 74299.04 | 29-JAN-08:11 | -22.8 |
February | 0.133025E+11 | 74100.91 | 02-FEB-08:12 | -36.3 |
March | 0.723861E+10 | 73193.55 | 15-MAR-07:01 | -6.7 |
April | 0.299938E+10 | 73198.52 | 04-APR-07:01 | -4.8 |
May | 0.224925E+09 | 73134.59 | 03-MAY-07:01 | 5.65 |
June | 66639249.03 | 3803.89 | 12-JUN-07:05 | 18.48 |
July | 33382575.05 | 3838.12 | 06-JUL-07:05 | 19.50 |
August | 33607439.33 | 3790.20 | 23-AUG-07:05 | 18.40 |
September | 0.149690E+09 | 73128.00 | 30-SEP-07:01 | 0.97 |
October | 0.573630E+09 | 73170.63 | 28-OCT-07:01 | 0.05 |
November | 0.691717E+10 | 73340.15 | 26-NOV-08:61 | -25.2 |
December | 0.144315E+11 | 73442.36 | 09-DEC-08:61 | -22.8 |
Annual Sum or Average | 0.659477E+11 | |||
Minimum of Months | 33382575.05 | 3790.20 | -36.3 | |
Maximum of Months | 0.199767E+11 | 74299.04 | 19.50 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.829895E+10 | 37900.26 | 29-JAN-08:11 | -22.8 |
February | 0.536984E+10 | 37781.31 | 02-FEB-08:12 | -36.3 |
March | 0.264211E+10 | 37375.72 | 15-MAR-07:01 | -6.7 |
April | 0.972253E+09 | 37381.02 | 04-APR-07:01 | -4.8 |
May | 67103683.09 | 22465.83 | 02-MAY-07:01 | 2.98 |
June | 33101762.49 | 2228.21 | 12-JUN-07:05 | 18.48 |
July | 22351931.17 | 2112.16 | 01-JUL-07:05 | 19.97 |
August | 25617576.02 | 2189.09 | 23-AUG-07:05 | 18.40 |
September | 56661131.17 | 11620.49 | 30-SEP-07:01 | 0.97 |
October | 0.157588E+09 | 33799.38 | 27-OCT-07:01 | 1.73 |
November | 0.278008E+10 | 37403.91 | 26-NOV-08:61 | -25.2 |
December | 0.596094E+10 | 37436.31 | 10-DEC-08:61 | -21.2 |
Annual Sum or Average | 0.263866E+11 | |||
Minimum of Months | 22351931.17 | 2112.16 | -36.3 | |
Maximum of Months | 0.829895E+10 | 37900.26 | 19.97 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.922841E+10 | 38153.38 | 29-JAN-08:11 | -22.8 |
February | 0.606612E+10 | 37940.97 | 02-FEB-07:12 | -36.7 |
March | 0.310827E+10 | 37554.66 | 06-MAR-07:01 | -12.7 |
April | 0.122804E+10 | 37541.78 | 04-APR-06:01 | -5.5 |
May | 77099182.90 | 19785.44 | 02-MAY-06:02 | 2.30 |
June | 83213533.97 | 2803.41 | 11-JUN-16:11 | 32.43 |
July | 70134056.54 | 2149.14 | 01-JUL-06:04 | 17.15 |
August | 51105582.32 | 2137.88 | 29-AUG-06:05 | 17.30 |
September | 72964702.60 | 9565.19 | 30-SEP-06:03 | 0.60 |
October | 0.226103E+09 | 27880.54 | 17-OCT-06:02 | 1.35 |
November | 0.327633E+10 | 37634.54 | 26-NOV-08:61 | -25.2 |
December | 0.677695E+10 | 37606.85 | 10-DEC-08:61 | -21.2 |
Annual Sum or Average | 0.302647E+11 | |||
Minimum of Months | 51105582.32 | 2137.88 | -36.7 | |
Maximum of Months | 0.922841E+10 | 38153.38 | 32.43 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.962626E+10 | 38267.60 | 29-JAN-08:11 | -22.8 |
February | 0.636142E+10 | 37768.32 | 05-FEB-08:61 | -20.4 |
March | 0.331684E+10 | 37631.33 | 06-MAR-07:01 | -12.7 |
April | 0.134814E+10 | 37606.15 | 04-APR-06:01 | -5.5 |
May | 88311281.88 | 24927.47 | 02-MAY-06:02 | 2.30 |
June | 85068440.21 | 2806.87 | 11-JUN-16:11 | 32.43 |
July | 70054555.58 | 2156.68 | 01-JUL-06:04 | 17.15 |
August | 50947986.39 | 2145.54 | 29-AUG-06:05 | 17.30 |
September | 78009364.56 | 13653.00 | 30-SEP-06:03 | 0.60 |
October | 0.276223E+09 | 33330.86 | 17-OCT-06:02 | 1.35 |
November | 0.349187E+10 | 37743.79 | 26-NOV-08:61 | -25.2 |
December | 0.711192E+10 | 37917.88 | 09-DEC-07:12 | -22.8 |
Annual Sum or Average | 0.319051E+11 | |||
Minimum of Months | 50947986.39 | 2145.54 | -25.2 | |
Maximum of Months | 0.962626E+10 | 38267.60 | 32.43 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.101171E+11 | 38433.56 | 29-JAN-08:11 | -22.8 |
February | 0.675568E+10 | 38189.12 | 02-FEB-07:12 | -36.7 |
March | 0.364970E+10 | 37754.81 | 05-MAR-08:61 | -9.8 |
April | 0.152030E+10 | 37756.68 | 04-APR-06:01 | -5.5 |
May | 0.109454E+09 | 29829.36 | 02-MAY-06:02 | 2.30 |
June | 88512531.03 | 2819.96 | 11-JUN-16:11 | 32.43 |
July | 70085991.86 | 2152.96 | 02-JUL-16:12 | 29.23 |
August | 49512520.97 | 2105.39 | 13-AUG-07:04 | 17.20 |
September | 89191034.89 | 18205.74 | 30-SEP-06:03 | 0.60 |
October | 0.352319E+09 | 36826.75 | 08-OCT-07:02 | 2.43 |
November | 0.378660E+10 | 37908.09 | 26-NOV-08:61 | -25.2 |
December | 0.757295E+10 | 38088.31 | 09-DEC-07:12 | -22.8 |
Annual Sum or Average | 0.341614E+11 | |||
Minimum of Months | 49512520.97 | 2105.39 | -36.7 | |
Maximum of Months | 0.101171E+11 | 38433.56 | 32.43 |
Report: ZoneHeatingSummaryMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.201642E+11 | 71905.30 | 30-JAN-08:61 | -29.3 |
February | 0.136079E+11 | 72457.27 | 02-FEB-08:12 | -36.3 |
March | 0.767860E+10 | 71707.75 | 06-MAR-08:61 | -11.8 |
April | 0.332310E+10 | 71616.69 | 04-APR-07:01 | -4.8 |
May | 0.274700E+09 | 71546.90 | 03-MAY-07:01 | 5.65 |
June | 0.133975E+09 | 5531.91 | 11-JUN-16:02 | 32.62 |
July | 86239856.79 | 4096.59 | 02-JUL-16:12 | 29.23 |
August | 65099601.38 | 3787.24 | 23-AUG-07:05 | 18.40 |
September | 0.201647E+09 | 71554.06 | 30-SEP-07:01 | 0.97 |
October | 0.946377E+09 | 71584.18 | 23-OCT-07:01 | -1.2 |
November | 0.781939E+10 | 71866.82 | 26-NOV-09:01 | -22.7 |
December | 0.153337E+11 | 71953.95 | 09-DEC-08:61 | -22.8 |
Annual Sum or Average | 0.696349E+11 | |||
Minimum of Months | 65099601.38 | 3787.24 | -36.3 | |
Maximum of Months | 0.201642E+11 | 72457.27 | 32.62 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.111915E+11 | 38428.37 | 30-JAN-08:61 | -29.3 |
February | 0.765240E+10 | 38714.48 | 02-FEB-08:12 | -36.3 |
March | 0.446237E+10 | 38229.62 | 06-MAR-08:61 | -11.8 |
April | 0.200622E+10 | 38175.07 | 04-APR-07:01 | -4.8 |
May | 0.178559E+09 | 38134.19 | 03-MAY-07:01 | 5.65 |
June | 75479109.71 | 2867.86 | 11-JUN-16:11 | 32.43 |
July | 47816971.76 | 2183.08 | 02-JUL-16:12 | 29.23 |
August | 34271734.14 | 2042.82 | 28-AUG-07:05 | 18.98 |
September | 0.121413E+09 | 38139.30 | 30-SEP-07:01 | 0.97 |
October | 0.641894E+09 | 38156.57 | 23-OCT-07:01 | -1.2 |
November | 0.447245E+10 | 38322.27 | 26-NOV-09:01 | -22.7 |
December | 0.861300E+10 | 38299.11 | 11-DEC-08:61 | -21.7 |
Annual Sum or Average | 0.394974E+11 | |||
Minimum of Months | 34271734.14 | 2042.82 | -36.3 | |
Maximum of Months | 0.111915E+11 | 38714.48 | 32.43 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.112424E+11 | 38349.47 | 19-JAN-08:61 | -28.3 |
February | 0.772733E+10 | 38693.13 | 02-FEB-08:12 | -36.3 |
March | 0.455332E+10 | 38208.73 | 06-MAR-08:61 | -11.8 |
April | 0.207887E+10 | 38151.68 | 04-APR-07:01 | -4.8 |
May | 0.192987E+09 | 38110.75 | 02-MAY-07:01 | 2.98 |
June | 77189289.28 | 2869.97 | 11-JUN-16:11 | 32.43 |
July | 47912341.08 | 2183.31 | 02-JUL-16:12 | 29.23 |
August | 34454386.62 | 2003.93 | 28-AUG-07:05 | 18.98 |
September | 0.128543E+09 | 38116.13 | 30-SEP-07:01 | 0.97 |
October | 0.694215E+09 | 38133.33 | 23-OCT-07:01 | -1.2 |
November | 0.454038E+10 | 38300.91 | 26-NOV-09:01 | -22.7 |
December | 0.868528E+10 | 38276.38 | 11-DEC-08:61 | -21.7 |
Annual Sum or Average | 0.400029E+11 | |||
Minimum of Months | 34454386.62 | 2003.93 | -36.3 | |
Maximum of Months | 0.112424E+11 | 38693.13 | 32.43 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.116872E+11 | 38780.90 | 29-JAN-09:12 | -22.8 |
February | 0.813383E+10 | 38912.08 | 02-FEB-08:12 | -36.3 |
March | 0.496259E+10 | 38423.60 | 06-MAR-08:61 | -11.8 |
April | 0.238035E+10 | 38406.26 | 03-APR-07:01 | -6.6 |
May | 0.237453E+09 | 38312.63 | 03-MAY-07:01 | 5.65 |
June | 86167472.90 | 9567.65 | 05-JUN-07:02 | 9.50 |
July | 50308963.79 | 2197.94 | 02-JUL-16:12 | 29.23 |
August | 37094291.76 | 1914.44 | 23-AUG-07:05 | 18.40 |
September | 0.152403E+09 | 38313.01 | 30-SEP-07:01 | 0.97 |
October | 0.861447E+09 | 38332.27 | 23-OCT-07:01 | -1.2 |
November | 0.482774E+10 | 38454.54 | 28-NOV-08:61 | -16.1 |
December | 0.908093E+10 | 38566.01 | 09-DEC-08:61 | -22.8 |
Annual Sum or Average | 0.424975E+11 | |||
Minimum of Months | 37094291.76 | 1914.44 | -36.3 | |
Maximum of Months | 0.116872E+11 | 38912.08 | 29.23 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.169427E+11 | 43647.09 | 19-JAN-01:11 | -22.4 |
February | 0.120546E+11 | 42269.25 | 02-FEB-08:12 | -36.3 |
March | 0.794390E+10 | 41609.81 | 06-MAR-05:32 | -14.8 |
April | 0.408166E+10 | 41561.78 | 03-APR-07:01 | -6.6 |
May | 0.507122E+09 | 41316.11 | 03-MAY-07:01 | 5.65 |
June | 0.183471E+09 | 40065.61 | 05-JUN-07:02 | 9.50 |
July | 71334619.52 | 2333.68 | 02-JUL-16:12 | 29.23 |
August | 67926555.72 | 1922.64 | 04-AUG-07:05 | 24.18 |
September | 0.287811E+09 | 41306.49 | 30-SEP-07:01 | 0.97 |
October | 0.159252E+10 | 41338.02 | 28-OCT-07:01 | 0.05 |
November | 0.711319E+10 | 41622.28 | 28-NOV-08:61 | -16.1 |
December | 0.129891E+11 | 41882.19 | 11-DEC-08:12 | -21.7 |
Annual Sum or Average | 0.638354E+11 | |||
Minimum of Months | 67926555.72 | 1922.64 | -36.3 | |
Maximum of Months | 0.169427E+11 | 43647.09 | 29.23 |
Report: ZoneElectricSummaryMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.136196E+11 | 8262.19 | 01-JAN-10:09 | 0.223514E+10 | 1348.26 | 01-JAN-10:09 |
February | 0.123234E+11 | 8262.19 | 01-FEB-10:09 | 0.202238E+10 | 1348.26 | 01-FEB-10:09 |
March | 0.136478E+11 | 8262.19 | 01-MAR-10:09 | 0.223972E+10 | 1348.26 | 01-MAR-10:09 |
April | 0.132157E+11 | 8262.19 | 01-APR-09:09 | 0.216880E+10 | 1348.26 | 01-APR-09:09 |
May | 0.136196E+11 | 8262.19 | 01-MAY-09:09 | 0.223514E+10 | 1348.26 | 01-MAY-09:09 |
June | 0.132157E+11 | 8262.19 | 01-JUN-09:09 | 0.216880E+10 | 1348.26 | 01-JUN-09:09 |
July | 0.136478E+11 | 8262.19 | 01-JUL-09:09 | 0.223972E+10 | 1348.26 | 01-JUL-09:09 |
August | 0.136196E+11 | 8262.19 | 01-AUG-09:09 | 0.223514E+10 | 1348.26 | 01-AUG-09:09 |
September | 0.132439E+11 | 8262.19 | 01-SEP-09:09 | 0.217339E+10 | 1348.26 | 01-SEP-09:09 |
October | 0.136196E+11 | 8262.19 | 01-OCT-09:09 | 0.223514E+10 | 1348.26 | 01-OCT-09:09 |
November | 0.131593E+11 | 8262.19 | 01-NOV-09:09 | 0.215964E+10 | 1348.26 | 01-NOV-09:09 |
December | 0.136759E+11 | 8262.19 | 01-DEC-10:09 | 0.224431E+10 | 1348.26 | 01-DEC-10:09 |
Annual Sum or Average | 0.160608E+12 | 0.263573E+11 | ||||
Minimum of Months | 0.123234E+11 | 8262.19 | 0.202238E+10 | 1348.26 | ||
Maximum of Months | 0.136759E+11 | 8262.19 | 0.224431E+10 | 1348.26 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.759377E+10 | 4606.69 | 01-JAN-10:09 | 0.111757E+10 | 674.13 | 01-JAN-10:09 |
February | 0.687105E+10 | 4606.69 | 01-FEB-10:09 | 0.101119E+10 | 674.13 | 01-FEB-10:09 |
March | 0.760948E+10 | 4606.69 | 01-MAR-10:09 | 0.111986E+10 | 674.13 | 01-MAR-10:09 |
April | 0.736857E+10 | 4606.69 | 01-APR-09:09 | 0.108440E+10 | 674.13 | 01-APR-09:09 |
May | 0.759377E+10 | 4606.69 | 01-MAY-09:09 | 0.111757E+10 | 674.13 | 01-MAY-09:09 |
June | 0.736857E+10 | 4606.69 | 01-JUN-09:09 | 0.108440E+10 | 674.13 | 01-JUN-09:09 |
July | 0.760948E+10 | 4606.69 | 01-JUL-09:09 | 0.111986E+10 | 674.13 | 01-JUL-09:09 |
August | 0.759377E+10 | 4606.69 | 01-AUG-09:09 | 0.111757E+10 | 674.13 | 01-AUG-09:09 |
September | 0.738428E+10 | 4606.69 | 01-SEP-09:09 | 0.108669E+10 | 674.13 | 01-SEP-09:09 |
October | 0.759377E+10 | 4606.69 | 01-OCT-09:09 | 0.111757E+10 | 674.13 | 01-OCT-09:09 |
November | 0.733715E+10 | 4606.69 | 01-NOV-09:09 | 0.107982E+10 | 674.13 | 01-NOV-09:09 |
December | 0.762519E+10 | 4606.69 | 01-DEC-10:09 | 0.112215E+10 | 674.13 | 01-DEC-10:09 |
Annual Sum or Average | 0.895488E+11 | 0.131787E+11 | ||||
Minimum of Months | 0.687105E+10 | 4606.69 | 0.101119E+10 | 674.13 | ||
Maximum of Months | 0.762519E+10 | 4606.69 | 0.112215E+10 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.552790E+10 | 4250.44 | 01-JAN-10:09 | 0.883781E+09 | 674.13 | 01-JAN-10:09 |
February | 0.500604E+10 | 4250.44 | 01-FEB-09:09 | 0.800324E+09 | 674.13 | 01-FEB-09:09 |
March | 0.564387E+10 | 4250.44 | 01-MAR-09:09 | 0.902118E+09 | 674.13 | 01-MAR-09:09 |
April | 0.536361E+10 | 4250.44 | 01-APR-08:09 | 0.857490E+09 | 674.13 | 01-APR-08:09 |
May | 0.558588E+10 | 4250.44 | 01-MAY-08:09 | 0.892950E+09 | 674.13 | 01-MAY-08:09 |
June | 0.545059E+10 | 4250.44 | 01-JUN-08:09 | 0.871243E+09 | 674.13 | 01-JUN-08:09 |
July | 0.549891E+10 | 4250.44 | 01-JUL-08:09 | 0.879197E+09 | 674.13 | 01-JUL-08:09 |
August | 0.564387E+10 | 4250.44 | 01-AUG-08:09 | 0.902118E+09 | 674.13 | 01-AUG-08:09 |
September | 0.536361E+10 | 4250.44 | 01-SEP-08:09 | 0.857490E+09 | 674.13 | 01-SEP-08:09 |
October | 0.552790E+10 | 4250.44 | 01-OCT-09:09 | 0.883781E+09 | 674.13 | 01-OCT-09:09 |
November | 0.536361E+10 | 4250.44 | 01-NOV-08:09 | 0.857490E+09 | 674.13 | 01-NOV-08:09 |
December | 0.549891E+10 | 4250.44 | 01-DEC-09:09 | 0.879197E+09 | 674.13 | 01-DEC-09:09 |
Annual Sum or Average | 0.654747E+11 | 0.104672E+11 | ||||
Minimum of Months | 0.500604E+10 | 4250.44 | 0.800324E+09 | 674.13 | ||
Maximum of Months | 0.564387E+10 | 4250.44 | 0.902118E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.552790E+10 | 4250.44 | 01-JAN-10:09 | 0.883781E+09 | 674.13 | 01-JAN-10:09 |
February | 0.500604E+10 | 4250.44 | 01-FEB-09:09 | 0.800324E+09 | 674.13 | 01-FEB-09:09 |
March | 0.564387E+10 | 4250.44 | 01-MAR-09:09 | 0.902118E+09 | 674.13 | 01-MAR-09:09 |
April | 0.536361E+10 | 4250.44 | 01-APR-08:09 | 0.857490E+09 | 674.13 | 01-APR-08:09 |
May | 0.558588E+10 | 4250.44 | 01-MAY-08:09 | 0.892950E+09 | 674.13 | 01-MAY-08:09 |
June | 0.545059E+10 | 4250.44 | 01-JUN-08:09 | 0.871243E+09 | 674.13 | 01-JUN-08:09 |
July | 0.549891E+10 | 4250.44 | 01-JUL-08:09 | 0.879197E+09 | 674.13 | 01-JUL-08:09 |
August | 0.564387E+10 | 4250.44 | 01-AUG-08:09 | 0.902118E+09 | 674.13 | 01-AUG-08:09 |
September | 0.536361E+10 | 4250.44 | 01-SEP-08:09 | 0.857490E+09 | 674.13 | 01-SEP-08:09 |
October | 0.552790E+10 | 4250.44 | 01-OCT-09:09 | 0.883781E+09 | 674.13 | 01-OCT-09:09 |
November | 0.536361E+10 | 4250.44 | 01-NOV-08:09 | 0.857490E+09 | 674.13 | 01-NOV-08:09 |
December | 0.549891E+10 | 4250.44 | 01-DEC-09:09 | 0.879197E+09 | 674.13 | 01-DEC-09:09 |
Annual Sum or Average | 0.654747E+11 | 0.104672E+11 | ||||
Minimum of Months | 0.500604E+10 | 4250.44 | 0.800324E+09 | 674.13 | ||
Maximum of Months | 0.564387E+10 | 4250.44 | 0.902118E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.552790E+10 | 4250.44 | 01-JAN-10:09 | 0.883781E+09 | 674.13 | 01-JAN-10:09 |
February | 0.500604E+10 | 4250.44 | 01-FEB-09:09 | 0.800324E+09 | 674.13 | 01-FEB-09:09 |
March | 0.564387E+10 | 4250.44 | 01-MAR-09:09 | 0.902118E+09 | 674.13 | 01-MAR-09:09 |
April | 0.536361E+10 | 4250.44 | 01-APR-08:09 | 0.857490E+09 | 674.13 | 01-APR-08:09 |
May | 0.558588E+10 | 4250.44 | 01-MAY-08:09 | 0.892950E+09 | 674.13 | 01-MAY-08:09 |
June | 0.545059E+10 | 4250.44 | 01-JUN-08:09 | 0.871243E+09 | 674.13 | 01-JUN-08:09 |
July | 0.549891E+10 | 4250.44 | 01-JUL-08:09 | 0.879197E+09 | 674.13 | 01-JUL-08:09 |
August | 0.564387E+10 | 4250.44 | 01-AUG-08:09 | 0.902118E+09 | 674.13 | 01-AUG-08:09 |
September | 0.536361E+10 | 4250.44 | 01-SEP-08:09 | 0.857490E+09 | 674.13 | 01-SEP-08:09 |
October | 0.552790E+10 | 4250.44 | 01-OCT-09:09 | 0.883781E+09 | 674.13 | 01-OCT-09:09 |
November | 0.536361E+10 | 4250.44 | 01-NOV-08:09 | 0.857490E+09 | 674.13 | 01-NOV-08:09 |
December | 0.549891E+10 | 4250.44 | 01-DEC-09:09 | 0.879197E+09 | 674.13 | 01-DEC-09:09 |
Annual Sum or Average | 0.654747E+11 | 0.104672E+11 | ||||
Minimum of Months | 0.500604E+10 | 4250.44 | 0.800324E+09 | 674.13 | ||
Maximum of Months | 0.564387E+10 | 4250.44 | 0.902118E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.724555E+10 | 6064.13 | 01-JAN-11:09 | 0.162546E+10 | 1348.26 | 01-JAN-11:09 |
February | 0.656305E+10 | 6064.13 | 01-FEB-10:09 | 0.147229E+10 | 1348.26 | 01-FEB-10:09 |
March | 0.741101E+10 | 6064.13 | 01-MAR-10:09 | 0.166213E+10 | 1348.26 | 01-MAR-10:09 |
April | 0.703184E+10 | 6064.13 | 01-APR-09:09 | 0.157746E+10 | 1348.26 | 01-APR-09:09 |
May | 0.732828E+10 | 6064.13 | 01-MAY-09:09 | 0.164379E+10 | 1348.26 | 01-MAY-09:09 |
June | 0.715593E+10 | 6064.13 | 01-JUN-09:09 | 0.160496E+10 | 1348.26 | 01-JUN-09:09 |
July | 0.720419E+10 | 6064.13 | 01-JUL-09:09 | 0.161629E+10 | 1348.26 | 01-JUL-09:09 |
August | 0.741101E+10 | 6064.13 | 01-AUG-09:09 | 0.166213E+10 | 1348.26 | 01-AUG-09:09 |
September | 0.703184E+10 | 6064.13 | 01-SEP-09:09 | 0.157746E+10 | 1348.26 | 01-SEP-09:09 |
October | 0.724555E+10 | 6064.13 | 01-OCT-10:09 | 0.162546E+10 | 1348.26 | 01-OCT-10:09 |
November | 0.703184E+10 | 6064.13 | 01-NOV-09:09 | 0.157746E+10 | 1348.26 | 01-NOV-09:09 |
December | 0.720419E+10 | 6064.13 | 01-DEC-10:09 | 0.161629E+10 | 1348.26 | 01-DEC-10:09 |
Annual Sum or Average | 0.858643E+11 | 0.192612E+11 | ||||
Minimum of Months | 0.656305E+10 | 6064.13 | 0.147229E+10 | 1348.26 | ||
Maximum of Months | 0.741101E+10 | 6064.13 | 0.166213E+10 | 1348.26 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.362278E+10 | 3032.07 | 01-JAN-11:09 | 0.812728E+09 | 674.13 | 01-JAN-11:09 |
February | 0.328152E+10 | 3032.07 | 01-FEB-10:09 | 0.736147E+09 | 674.13 | 01-FEB-10:09 |
March | 0.370550E+10 | 3032.07 | 01-MAR-10:09 | 0.831065E+09 | 674.13 | 01-MAR-10:09 |
April | 0.351592E+10 | 3032.07 | 01-APR-09:09 | 0.788729E+09 | 674.13 | 01-APR-09:09 |
May | 0.366414E+10 | 3032.07 | 01-MAY-09:09 | 0.821897E+09 | 674.13 | 01-MAY-09:09 |
June | 0.357797E+10 | 3032.07 | 01-JUN-09:09 | 0.802482E+09 | 674.13 | 01-JUN-09:09 |
July | 0.360209E+10 | 3032.07 | 01-JUL-09:09 | 0.808144E+09 | 674.13 | 01-JUL-09:09 |
August | 0.370550E+10 | 3032.07 | 01-AUG-09:09 | 0.831065E+09 | 674.13 | 01-AUG-09:09 |
September | 0.351592E+10 | 3032.07 | 01-SEP-09:09 | 0.788729E+09 | 674.13 | 01-SEP-09:09 |
October | 0.362278E+10 | 3032.07 | 01-OCT-10:09 | 0.812728E+09 | 674.13 | 01-OCT-10:09 |
November | 0.351592E+10 | 3032.07 | 01-NOV-09:09 | 0.788729E+09 | 674.13 | 01-NOV-09:09 |
December | 0.360209E+10 | 3032.07 | 01-DEC-10:09 | 0.808144E+09 | 674.13 | 01-DEC-10:09 |
Annual Sum or Average | 0.429321E+11 | 0.963059E+10 | ||||
Minimum of Months | 0.328152E+10 | 3032.07 | 0.736147E+09 | 674.13 | ||
Maximum of Months | 0.370550E+10 | 3032.07 | 0.831065E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.362278E+10 | 3032.07 | 01-JAN-11:09 | 0.812728E+09 | 674.13 | 01-JAN-11:09 |
February | 0.328152E+10 | 3032.07 | 01-FEB-10:09 | 0.736147E+09 | 674.13 | 01-FEB-10:09 |
March | 0.370550E+10 | 3032.07 | 01-MAR-10:09 | 0.831065E+09 | 674.13 | 01-MAR-10:09 |
April | 0.351592E+10 | 3032.07 | 01-APR-09:09 | 0.788729E+09 | 674.13 | 01-APR-09:09 |
May | 0.366414E+10 | 3032.07 | 01-MAY-09:09 | 0.821897E+09 | 674.13 | 01-MAY-09:09 |
June | 0.357797E+10 | 3032.07 | 01-JUN-09:09 | 0.802482E+09 | 674.13 | 01-JUN-09:09 |
July | 0.360209E+10 | 3032.07 | 01-JUL-09:09 | 0.808144E+09 | 674.13 | 01-JUL-09:09 |
August | 0.370550E+10 | 3032.07 | 01-AUG-09:09 | 0.831065E+09 | 674.13 | 01-AUG-09:09 |
September | 0.351592E+10 | 3032.07 | 01-SEP-09:09 | 0.788729E+09 | 674.13 | 01-SEP-09:09 |
October | 0.362278E+10 | 3032.07 | 01-OCT-10:09 | 0.812728E+09 | 674.13 | 01-OCT-10:09 |
November | 0.351592E+10 | 3032.07 | 01-NOV-09:09 | 0.788729E+09 | 674.13 | 01-NOV-09:09 |
December | 0.360209E+10 | 3032.07 | 01-DEC-10:09 | 0.808144E+09 | 674.13 | 01-DEC-10:09 |
Annual Sum or Average | 0.429321E+11 | 0.963059E+10 | ||||
Minimum of Months | 0.328152E+10 | 3032.07 | 0.736147E+09 | 674.13 | ||
Maximum of Months | 0.370550E+10 | 3032.07 | 0.831065E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.362278E+10 | 3032.07 | 01-JAN-11:09 | 0.812728E+09 | 674.13 | 01-JAN-11:09 |
February | 0.328152E+10 | 3032.07 | 01-FEB-10:09 | 0.736147E+09 | 674.13 | 01-FEB-10:09 |
March | 0.370550E+10 | 3032.07 | 01-MAR-10:09 | 0.831065E+09 | 674.13 | 01-MAR-10:09 |
April | 0.351592E+10 | 3032.07 | 01-APR-09:09 | 0.788729E+09 | 674.13 | 01-APR-09:09 |
May | 0.366414E+10 | 3032.07 | 01-MAY-09:09 | 0.821897E+09 | 674.13 | 01-MAY-09:09 |
June | 0.357797E+10 | 3032.07 | 01-JUN-09:09 | 0.802482E+09 | 674.13 | 01-JUN-09:09 |
July | 0.360209E+10 | 3032.07 | 01-JUL-09:09 | 0.808144E+09 | 674.13 | 01-JUL-09:09 |
August | 0.370550E+10 | 3032.07 | 01-AUG-09:09 | 0.831065E+09 | 674.13 | 01-AUG-09:09 |
September | 0.351592E+10 | 3032.07 | 01-SEP-09:09 | 0.788729E+09 | 674.13 | 01-SEP-09:09 |
October | 0.362278E+10 | 3032.07 | 01-OCT-10:09 | 0.812728E+09 | 674.13 | 01-OCT-10:09 |
November | 0.351592E+10 | 3032.07 | 01-NOV-09:09 | 0.788729E+09 | 674.13 | 01-NOV-09:09 |
December | 0.360209E+10 | 3032.07 | 01-DEC-10:09 | 0.808144E+09 | 674.13 | 01-DEC-10:09 |
Annual Sum or Average | 0.429321E+11 | 0.963059E+10 | ||||
Minimum of Months | 0.328152E+10 | 3032.07 | 0.736147E+09 | 674.13 | ||
Maximum of Months | 0.370550E+10 | 3032.07 | 0.831065E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.362278E+10 | 3032.07 | 01-JAN-11:09 | 0.812728E+09 | 674.13 | 01-JAN-11:09 |
February | 0.328152E+10 | 3032.07 | 01-FEB-10:09 | 0.736147E+09 | 674.13 | 01-FEB-10:09 |
March | 0.370550E+10 | 3032.07 | 01-MAR-10:09 | 0.831065E+09 | 674.13 | 01-MAR-10:09 |
April | 0.351592E+10 | 3032.07 | 01-APR-09:09 | 0.788729E+09 | 674.13 | 01-APR-09:09 |
May | 0.366414E+10 | 3032.07 | 01-MAY-09:09 | 0.821897E+09 | 674.13 | 01-MAY-09:09 |
June | 0.357797E+10 | 3032.07 | 01-JUN-09:09 | 0.802482E+09 | 674.13 | 01-JUN-09:09 |
July | 0.360209E+10 | 3032.07 | 01-JUL-09:09 | 0.808144E+09 | 674.13 | 01-JUL-09:09 |
August | 0.370550E+10 | 3032.07 | 01-AUG-09:09 | 0.831065E+09 | 674.13 | 01-AUG-09:09 |
September | 0.351592E+10 | 3032.07 | 01-SEP-09:09 | 0.788729E+09 | 674.13 | 01-SEP-09:09 |
October | 0.362278E+10 | 3032.07 | 01-OCT-10:09 | 0.812728E+09 | 674.13 | 01-OCT-10:09 |
November | 0.351592E+10 | 3032.07 | 01-NOV-09:09 | 0.788729E+09 | 674.13 | 01-NOV-09:09 |
December | 0.360209E+10 | 3032.07 | 01-DEC-10:09 | 0.808144E+09 | 674.13 | 01-DEC-10:09 |
Annual Sum or Average | 0.429321E+11 | 0.963059E+10 | ||||
Minimum of Months | 0.328152E+10 | 3032.07 | 0.736147E+09 | 674.13 | ||
Maximum of Months | 0.370550E+10 | 3032.07 | 0.831065E+09 | 674.13 |
Report: SpaceGainsMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.180574E+10 | 0.136196E+11 | 0.223514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183211E+11 |
February | 0.163016E+10 | 0.123234E+11 | 0.202238E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137426E+11 |
March | 0.178954E+10 | 0.136478E+11 | 0.223972E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105725E+11 |
April | 0.174484E+10 | 0.132157E+11 | 0.216880E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132339E+09 | 0.677281E+10 |
May | 0.179537E+10 | 0.136196E+11 | 0.223514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111299E+09 | 0.352204E+10 |
June | 0.173447E+10 | 0.132157E+11 | 0.216880E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.687692E+09 | 0.181358E+10 |
July | 0.181028E+10 | 0.136478E+11 | 0.223972E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.560240E+09 | 0.943689E+09 |
August | 0.178501E+10 | 0.136196E+11 | 0.223514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.605488E+09 | 0.124008E+10 |
September | 0.174937E+10 | 0.132439E+11 | 0.217339E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.455838E+09 | 0.294767E+10 |
October | 0.180574E+10 | 0.136196E+11 | 0.223514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.630968E+10 |
November | 0.174613E+10 | 0.131593E+11 | 0.215964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108657E+11 |
December | 0.181481E+10 | 0.136759E+11 | 0.224431E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153808E+11 |
Annual Sum or Average | 0.212115E+11 | 0.160608E+12 | 0.263573E+11 | 0.255290E+10 | 0.924322E+11 | ||||
Minimum of Months | 0.163016E+10 | 0.123234E+11 | 0.202238E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.943689E+09 |
Maximum of Months | 0.181481E+10 | 0.136759E+11 | 0.224431E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.687692E+09 | 0.183211E+11 |
Report: SpaceGainsMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.902868E+09 | 0.759377E+10 | 0.111757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.886054E+10 |
February | 0.815075E+09 | 0.687105E+10 | 0.101119E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.665575E+10 |
March | 0.894769E+09 | 0.760948E+10 | 0.111986E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.503539E+10 |
April | 0.872416E+09 | 0.736857E+10 | 0.108440E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 69930148.36 | 0.327231E+10 |
May | 0.897684E+09 | 0.759377E+10 | 0.111757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 61007759.88 | 0.166597E+10 |
June | 0.867232E+09 | 0.736857E+10 | 0.108440E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.373039E+09 | 0.824913E+09 |
July | 0.905135E+09 | 0.760948E+10 | 0.111986E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.309338E+09 | 0.379418E+09 |
August | 0.892501E+09 | 0.759377E+10 | 0.111757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.332890E+09 | 0.479095E+09 |
September | 0.874683E+09 | 0.738428E+10 | 0.108669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.250892E+09 | 0.135842E+10 |
October | 0.902868E+09 | 0.759377E+10 | 0.111757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.304078E+10 |
November | 0.873064E+09 | 0.733715E+10 | 0.107982E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.519909E+10 |
December | 0.907403E+09 | 0.762519E+10 | 0.112215E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.740834E+10 |
Annual Sum or Average | 0.106057E+11 | 0.895488E+11 | 0.131787E+11 | 0.139710E+10 | 0.441800E+11 | ||||
Minimum of Months | 0.815075E+09 | 0.687105E+10 | 0.101119E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.379418E+09 |
Maximum of Months | 0.907403E+09 | 0.762519E+10 | 0.112215E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.373039E+09 | 0.886054E+10 |
Report: SpaceGainsMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.537120E+09 | 0.552790E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.914685E+10 |
February | 0.487879E+09 | 0.500604E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.688493E+10 |
March | 0.551374E+09 | 0.564387E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.517659E+10 |
April | 0.524810E+09 | 0.536361E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 64930613.34 | 0.335095E+10 |
May | 0.544247E+09 | 0.558588E+10 | 0.892950E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 60974167.88 | 0.173293E+10 |
June | 0.532585E+09 | 0.545059E+10 | 0.871243E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.357480E+09 | 0.868014E+09 |
July | 0.536472E+09 | 0.549891E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.295970E+09 | 0.433771E+09 |
August | 0.551374E+09 | 0.564387E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.327167E+09 | 0.548062E+09 |
September | 0.524810E+09 | 0.536361E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.245287E+09 | 0.143203E+10 |
October | 0.537120E+09 | 0.552790E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.309743E+10 |
November | 0.518979E+09 | 0.536361E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.536545E+10 |
December | 0.536472E+09 | 0.549891E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.765234E+10 |
Annual Sum or Average | 0.638324E+10 | 0.654747E+11 | 0.104672E+11 | 0.135181E+10 | 0.456894E+11 | ||||
Minimum of Months | 0.487879E+09 | 0.500604E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.433771E+09 |
Maximum of Months | 0.551374E+09 | 0.564387E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.357480E+09 | 0.914685E+10 |
Report: SpaceGainsMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.537120E+09 | 0.552790E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.913176E+10 |
February | 0.487879E+09 | 0.500604E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.687180E+10 |
March | 0.551374E+09 | 0.564387E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.515471E+10 |
April | 0.524810E+09 | 0.536361E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 64968301.56 | 0.333190E+10 |
May | 0.544247E+09 | 0.558588E+10 | 0.892950E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 60973819.68 | 0.172365E+10 |
June | 0.532585E+09 | 0.545059E+10 | 0.871243E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.357315E+09 | 0.864852E+09 |
July | 0.536472E+09 | 0.549891E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.295933E+09 | 0.434361E+09 |
August | 0.551374E+09 | 0.564387E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.327169E+09 | 0.548236E+09 |
September | 0.524810E+09 | 0.536361E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.245289E+09 | 0.142267E+10 |
October | 0.537120E+09 | 0.552790E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.306472E+10 |
November | 0.518979E+09 | 0.536361E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.533967E+10 |
December | 0.536472E+09 | 0.549891E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.763779E+10 |
Annual Sum or Average | 0.638324E+10 | 0.654747E+11 | 0.104672E+11 | 0.135165E+10 | 0.455261E+11 | ||||
Minimum of Months | 0.487879E+09 | 0.500604E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.434361E+09 |
Maximum of Months | 0.551374E+09 | 0.564387E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.357315E+09 | 0.913176E+10 |
Report: SpaceGainsMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.537120E+09 | 0.552790E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.912265E+10 |
February | 0.487879E+09 | 0.500604E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.686267E+10 |
March | 0.551374E+09 | 0.564387E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.513570E+10 |
April | 0.524810E+09 | 0.536361E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 65116690.70 | 0.331144E+10 |
May | 0.544247E+09 | 0.558588E+10 | 0.892950E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 60973181.70 | 0.170701E+10 |
June | 0.532585E+09 | 0.545059E+10 | 0.871243E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.357611E+09 | 0.852851E+09 |
July | 0.536472E+09 | 0.549891E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.296015E+09 | 0.430243E+09 |
August | 0.551374E+09 | 0.564387E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.327184E+09 | 0.543585E+09 |
September | 0.524810E+09 | 0.536361E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.245302E+09 | 0.140538E+10 |
October | 0.537120E+09 | 0.552790E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.303177E+10 |
November | 0.518979E+09 | 0.536361E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.531268E+10 |
December | 0.536472E+09 | 0.549891E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.762731E+10 |
Annual Sum or Average | 0.638324E+10 | 0.654747E+11 | 0.104672E+11 | 0.135220E+10 | 0.453433E+11 | ||||
Minimum of Months | 0.487879E+09 | 0.500604E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.430243E+09 |
Maximum of Months | 0.551374E+09 | 0.564387E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.357611E+09 | 0.912265E+10 |
Report: SpaceGainsMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.183632E+10 | 0.724555E+10 | 0.162546E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165884E+11 |
February | 0.167188E+10 | 0.656305E+10 | 0.147229E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124570E+11 |
March | 0.189386E+10 | 0.741101E+10 | 0.166213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.934389E+10 |
April | 0.180380E+10 | 0.703184E+10 | 0.157746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116142E+09 | 0.598713E+10 |
May | 0.186509E+10 | 0.732828E+10 | 0.164379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107380E+09 | 0.306276E+10 |
June | 0.182945E+10 | 0.715593E+10 | 0.160496E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.633035E+09 | 0.153351E+10 |
July | 0.183943E+10 | 0.720419E+10 | 0.161629E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.522009E+09 | 0.808957E+09 |
August | 0.189386E+10 | 0.741101E+10 | 0.166213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.576102E+09 | 0.103384E+10 |
September | 0.180380E+10 | 0.703184E+10 | 0.157746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.431685E+09 | 0.254932E+10 |
October | 0.183632E+10 | 0.724555E+10 | 0.162546E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.545604E+10 |
November | 0.176881E+10 | 0.703184E+10 | 0.157746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.961539E+10 |
December | 0.183943E+10 | 0.720419E+10 | 0.161629E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138748E+11 |
Annual Sum or Average | 0.218821E+11 | 0.858643E+11 | 0.192612E+11 | 0.238635E+10 | 0.823111E+11 | ||||
Minimum of Months | 0.167188E+10 | 0.656305E+10 | 0.147229E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.808957E+09 |
Maximum of Months | 0.189386E+10 | 0.741101E+10 | 0.166213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.633035E+09 | 0.165884E+11 |
Report: SpaceGainsMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.918158E+09 | 0.362278E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.919404E+10 |
February | 0.835938E+09 | 0.328152E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.690285E+10 |
March | 0.946926E+09 | 0.370550E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.515289E+10 |
April | 0.901896E+09 | 0.351592E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 65762849.43 | 0.330016E+10 |
May | 0.932542E+09 | 0.366414E+10 | 0.821897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 61001791.57 | 0.167230E+10 |
June | 0.914724E+09 | 0.357797E+10 | 0.802482E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.359366E+09 | 0.828297E+09 |
July | 0.919713E+09 | 0.360209E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.297010E+09 | 0.428691E+09 |
August | 0.946926E+09 | 0.370550E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.327422E+09 | 0.544028E+09 |
September | 0.901896E+09 | 0.351592E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.245410E+09 | 0.138653E+10 |
October | 0.918158E+09 | 0.362278E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.299761E+10 |
November | 0.884402E+09 | 0.351592E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.530350E+10 |
December | 0.919713E+09 | 0.360209E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.768161E+10 |
Annual Sum or Average | 0.109410E+11 | 0.429321E+11 | 0.963059E+10 | 0.135597E+10 | 0.453925E+11 | ||||
Minimum of Months | 0.835938E+09 | 0.328152E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.428691E+09 |
Maximum of Months | 0.946926E+09 | 0.370550E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.359366E+09 | 0.919404E+10 |
Report: SpaceGainsMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.918158E+09 | 0.362278E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.919307E+10 |
February | 0.835938E+09 | 0.328152E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.690094E+10 |
March | 0.946926E+09 | 0.370550E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.514762E+10 |
April | 0.901896E+09 | 0.351592E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 65868499.13 | 0.329209E+10 |
May | 0.932542E+09 | 0.366414E+10 | 0.821897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 61001360.33 | 0.165798E+10 |
June | 0.914724E+09 | 0.357797E+10 | 0.802482E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.359560E+09 | 0.821812E+09 |
July | 0.919713E+09 | 0.360209E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.297079E+09 | 0.426901E+09 |
August | 0.946926E+09 | 0.370550E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.327435E+09 | 0.542133E+09 |
September | 0.901896E+09 | 0.351592E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.245418E+09 | 0.138058E+10 |
October | 0.918158E+09 | 0.362278E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.298860E+10 |
November | 0.884402E+09 | 0.351592E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.529620E+10 |
December | 0.919713E+09 | 0.360209E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.767963E+10 |
Annual Sum or Average | 0.109410E+11 | 0.429321E+11 | 0.963059E+10 | 0.135636E+10 | 0.453275E+11 | ||||
Minimum of Months | 0.835938E+09 | 0.328152E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.426901E+09 |
Maximum of Months | 0.946926E+09 | 0.370550E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.359560E+09 | 0.919307E+10 |
Report: SpaceGainsMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.918158E+09 | 0.362278E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.918627E+10 |
February | 0.835938E+09 | 0.328152E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.689081E+10 |
March | 0.946926E+09 | 0.370550E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.512710E+10 |
April | 0.901896E+09 | 0.351592E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 66157692.22 | 0.326541E+10 |
May | 0.932542E+09 | 0.366414E+10 | 0.821897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 61000144.77 | 0.161708E+10 |
June | 0.914724E+09 | 0.357797E+10 | 0.802482E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.359970E+09 | 0.805338E+09 |
July | 0.919713E+09 | 0.360209E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.297213E+09 | 0.421754E+09 |
August | 0.946926E+09 | 0.370550E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.327455E+09 | 0.536833E+09 |
September | 0.901896E+09 | 0.351592E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.245431E+09 | 0.136499E+10 |
October | 0.918158E+09 | 0.362278E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.296535E+10 |
November | 0.884402E+09 | 0.351592E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.527592E+10 |
December | 0.919713E+09 | 0.360209E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.766799E+10 |
Annual Sum or Average | 0.109410E+11 | 0.429321E+11 | 0.963059E+10 | 0.135723E+10 | 0.451249E+11 | ||||
Minimum of Months | 0.835938E+09 | 0.328152E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.421754E+09 |
Maximum of Months | 0.946926E+09 | 0.370550E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.359970E+09 | 0.918627E+10 |
Report: SpaceGainsMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.918158E+09 | 0.362278E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121281E+11 |
February | 0.835938E+09 | 0.328152E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.904831E+10 |
March | 0.946926E+09 | 0.370550E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.685755E+10 |
April | 0.901896E+09 | 0.351592E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 75447690.56 | 0.423865E+10 |
May | 0.932542E+09 | 0.366414E+10 | 0.821897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 64907084.17 | 0.209664E+10 |
June | 0.914724E+09 | 0.357797E+10 | 0.802482E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.391216E+09 | 0.112340E+10 |
July | 0.919713E+09 | 0.360209E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.312649E+09 | 0.675855E+09 |
August | 0.946926E+09 | 0.370550E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.346851E+09 | 0.916549E+09 |
September | 0.901896E+09 | 0.351592E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.259225E+09 | 0.193377E+10 |
October | 0.918158E+09 | 0.362278E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.396558E+10 |
November | 0.884402E+09 | 0.351592E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.706019E+10 |
December | 0.919713E+09 | 0.360209E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101472E+11 |
Annual Sum or Average | 0.109410E+11 | 0.429321E+11 | 0.963059E+10 | 0.145030E+10 | 0.601918E+11 | ||||
Minimum of Months | 0.835938E+09 | 0.328152E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.675855E+09 |
Maximum of Months | 0.946926E+09 | 0.370550E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.391216E+09 | 0.121281E+11 |
Report: PeakSpaceGainsMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2159.72 | 01-JAN-13:09 | 8262.19 | 01-JAN-10:09 | 1348.26 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 27093.23 | 30-JAN-18:00 |
February | 2159.72 | 03-FEB-13:09 | 8262.19 | 01-FEB-10:09 | 1348.26 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 30579.84 | 02-FEB-12:10 |
March | 2159.72 | 03-MAR-13:09 | 8262.19 | 01-MAR-10:09 | 1348.26 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 18280.31 | 05-MAR-18:00 |
April | 2159.72 | 01-APR-12:09 | 8262.19 | 01-APR-09:09 | 1348.26 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3063.42 | 15-APR-15:00 | 13352.65 | 03-APR-11:10 |
May | 2159.72 | 05-MAY-12:09 | 8262.19 | 01-MAY-09:09 | 1348.26 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2841.42 | 31-MAY-13:00 | 6826.62 | 01-MAY-17:00 |
June | 2159.72 | 02-JUN-12:09 | 8262.19 | 01-JUN-09:09 | 1348.26 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4515.30 | 11-JUN-15:00 | 5715.13 | 01-JUN-14:00 |
July | 2159.72 | 01-JUL-12:09 | 8262.19 | 01-JUL-09:09 | 1348.26 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2863.08 | 26-JUL-16:00 | 4144.31 | 10-JUL-12:00 |
August | 2159.72 | 04-AUG-12:09 | 8262.19 | 01-AUG-09:09 | 1348.26 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4501.84 | 04-AUG-15:00 | 4057.97 | 06-AUG-11:10 |
September | 2159.72 | 01-SEP-12:09 | 8262.19 | 01-SEP-09:09 | 1348.26 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3870.70 | 06-SEP-14:00 | 6784.76 | 29-SEP-17:00 |
October | 2159.72 | 01-OCT-12:09 | 8262.19 | 01-OCT-09:09 | 1348.26 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 8703.39 | 31-OCT-17:00 |
November | 2159.72 | 03-NOV-12:09 | 8262.19 | 01-NOV-09:09 | 1348.26 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 23907.30 | 25-NOV-18:00 |
December | 2159.72 | 01-DEC-13:09 | 8262.19 | 01-DEC-10:09 | 1348.26 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 25624.65 | 09-DEC-12:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2159.72 | 8262.19 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4057.97 | |||||
Maximum of Months | 2159.72 | 8262.19 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 4515.30 | 30579.84 |
Report: PeakSpaceGainsMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1079.86 | 01-JAN-13:09 | 4606.69 | 01-JAN-10:09 | 674.13 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 15128.87 | 30-JAN-18:00 |
February | 1079.86 | 03-FEB-13:09 | 4606.69 | 01-FEB-10:09 | 674.13 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 16973.76 | 02-FEB-12:10 |
March | 1079.86 | 03-MAR-13:09 | 4606.69 | 01-MAR-10:09 | 674.13 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 10065.95 | 05-MAR-18:00 |
April | 1079.86 | 01-APR-12:09 | 4606.69 | 01-APR-09:09 | 674.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1627.66 | 15-APR-15:00 | 7359.01 | 03-APR-11:10 |
May | 1079.86 | 05-MAY-12:09 | 4606.69 | 01-MAY-09:09 | 674.13 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1568.79 | 31-MAY-13:00 | 3768.08 | 01-MAY-11:05 |
June | 1079.86 | 02-JUN-12:09 | 4606.69 | 01-JUN-09:09 | 674.13 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2441.07 | 11-JUN-15:00 | 3345.31 | 02-JUN-11:05 |
July | 1079.86 | 01-JUL-12:09 | 4606.69 | 01-JUL-09:09 | 674.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1580.80 | 26-JUL-16:00 | 2264.31 | 10-JUL-12:00 |
August | 1079.86 | 04-AUG-12:09 | 4606.69 | 01-AUG-09:09 | 674.13 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2507.04 | 04-AUG-15:00 | 2237.45 | 06-AUG-11:10 |
September | 1079.86 | 01-SEP-12:09 | 4606.69 | 01-SEP-09:09 | 674.13 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2137.05 | 06-SEP-14:00 | 3740.63 | 29-SEP-17:00 |
October | 1079.86 | 01-OCT-12:09 | 4606.69 | 01-OCT-09:09 | 674.13 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 4921.43 | 31-OCT-17:00 |
November | 1079.86 | 03-NOV-12:09 | 4606.69 | 01-NOV-09:09 | 674.13 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 13095.88 | 25-NOV-18:00 |
December | 1079.86 | 01-DEC-13:09 | 4606.69 | 01-DEC-10:09 | 674.13 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 13636.94 | 09-DEC-12:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1079.86 | 4606.69 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2237.45 | |||||
Maximum of Months | 1079.86 | 4606.69 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 2507.04 | 16973.76 |
Report: PeakSpaceGainsMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1079.86 | 07-JAN-13:09 | 4250.44 | 01-JAN-10:09 | 674.13 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 15128.84 | 30-JAN-18:00 |
February | 1079.86 | 04-FEB-13:09 | 4250.44 | 01-FEB-09:09 | 674.13 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 16973.72 | 02-FEB-12:10 |
March | 1079.86 | 04-MAR-13:09 | 4250.44 | 01-MAR-09:09 | 674.13 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 10065.93 | 05-MAR-18:00 |
April | 1079.86 | 01-APR-12:09 | 4250.44 | 01-APR-08:09 | 674.13 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1627.64 | 15-APR-15:00 | 7358.99 | 03-APR-11:10 |
May | 1079.86 | 06-MAY-12:09 | 4250.44 | 01-MAY-08:09 | 674.13 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1568.78 | 31-MAY-13:00 | 3681.40 | 01-MAY-17:00 |
June | 1079.86 | 03-JUN-12:09 | 4250.44 | 01-JUN-08:09 | 674.13 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2441.00 | 11-JUN-15:00 | 3354.41 | 02-JUN-11:05 |
July | 1079.86 | 01-JUL-12:09 | 4250.44 | 01-JUL-08:09 | 674.13 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1580.76 | 26-JUL-16:00 | 2264.30 | 10-JUL-12:00 |
August | 1079.86 | 05-AUG-12:09 | 4250.44 | 01-AUG-08:09 | 674.13 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2507.00 | 04-AUG-15:00 | 2237.44 | 06-AUG-11:10 |
September | 1079.86 | 02-SEP-12:09 | 4250.44 | 01-SEP-08:09 | 674.13 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2137.02 | 06-SEP-14:00 | 3736.06 | 29-SEP-17:00 |
October | 1079.86 | 07-OCT-12:09 | 4250.44 | 01-OCT-09:09 | 674.13 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 4920.30 | 31-OCT-17:00 |
November | 1079.86 | 04-NOV-12:09 | 4250.44 | 01-NOV-08:09 | 674.13 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 13095.84 | 25-NOV-18:00 |
December | 1079.86 | 02-DEC-13:09 | 4250.44 | 01-DEC-09:09 | 674.13 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 13636.85 | 09-DEC-12:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1079.86 | 4250.44 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2237.44 | |||||
Maximum of Months | 1079.86 | 4250.44 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 2507.00 | 16973.72 |
Report: PeakSpaceGainsMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1079.86 | 07-JAN-13:09 | 4250.44 | 01-JAN-10:09 | 674.13 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 15128.84 | 30-JAN-18:00 |
February | 1079.86 | 04-FEB-13:09 | 4250.44 | 01-FEB-09:09 | 674.13 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 16973.72 | 02-FEB-12:10 |
March | 1079.86 | 04-MAR-13:09 | 4250.44 | 01-MAR-09:09 | 674.13 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 10065.93 | 05-MAR-18:00 |
April | 1079.86 | 01-APR-12:09 | 4250.44 | 01-APR-08:09 | 674.13 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1627.63 | 15-APR-15:00 | 7358.99 | 03-APR-11:10 |
May | 1079.86 | 06-MAY-12:09 | 4250.44 | 01-MAY-08:09 | 674.13 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1568.78 | 31-MAY-13:00 | 3681.40 | 01-MAY-17:00 |
June | 1079.86 | 03-JUN-12:09 | 4250.44 | 01-JUN-08:09 | 674.13 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2440.99 | 11-JUN-15:00 | 3347.90 | 02-JUN-11:05 |
July | 1079.86 | 01-JUL-12:09 | 4250.44 | 01-JUL-08:09 | 674.13 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1580.76 | 26-JUL-16:00 | 2264.30 | 10-JUL-12:00 |
August | 1079.86 | 05-AUG-12:09 | 4250.44 | 01-AUG-08:09 | 674.13 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2507.00 | 04-AUG-15:00 | 2237.44 | 06-AUG-11:10 |
September | 1079.86 | 02-SEP-12:09 | 4250.44 | 01-SEP-08:09 | 674.13 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2137.02 | 06-SEP-14:00 | 3735.96 | 29-SEP-17:00 |
October | 1079.86 | 07-OCT-12:09 | 4250.44 | 01-OCT-09:09 | 674.13 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 4920.27 | 31-OCT-17:00 |
November | 1079.86 | 04-NOV-12:09 | 4250.44 | 01-NOV-08:09 | 674.13 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 13095.84 | 25-NOV-18:00 |
December | 1079.86 | 02-DEC-13:09 | 4250.44 | 01-DEC-09:09 | 674.13 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 13636.85 | 09-DEC-12:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1079.86 | 4250.44 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2237.44 | |||||
Maximum of Months | 1079.86 | 4250.44 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 2507.00 | 16973.72 |
Report: PeakSpaceGainsMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1079.86 | 07-JAN-13:09 | 4250.44 | 01-JAN-10:09 | 674.13 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 15128.84 | 30-JAN-18:00 |
February | 1079.86 | 04-FEB-13:09 | 4250.44 | 01-FEB-09:09 | 674.13 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 16973.72 | 02-FEB-12:10 |
March | 1079.86 | 04-MAR-13:09 | 4250.44 | 01-MAR-09:09 | 674.13 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 10065.93 | 05-MAR-18:00 |
April | 1079.86 | 01-APR-12:09 | 4250.44 | 01-APR-08:09 | 674.13 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1627.61 | 15-APR-15:00 | 7358.99 | 03-APR-11:10 |
May | 1079.86 | 06-MAY-12:09 | 4250.44 | 01-MAY-08:09 | 674.13 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1568.77 | 31-MAY-13:00 | 3681.41 | 01-MAY-17:00 |
June | 1079.86 | 03-JUN-12:09 | 4250.44 | 01-JUN-08:09 | 674.13 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2440.97 | 11-JUN-15:00 | 3297.63 | 02-JUN-11:05 |
July | 1079.86 | 01-JUL-12:09 | 4250.44 | 01-JUL-08:09 | 674.13 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1580.73 | 26-JUL-16:00 | 2264.30 | 10-JUL-12:00 |
August | 1079.86 | 05-AUG-12:09 | 4250.44 | 01-AUG-08:09 | 674.13 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2506.98 | 04-AUG-15:00 | 2237.44 | 06-AUG-11:10 |
September | 1079.86 | 02-SEP-12:09 | 4250.44 | 01-SEP-08:09 | 674.13 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2137.01 | 06-SEP-14:00 | 3735.98 | 29-SEP-17:00 |
October | 1079.86 | 07-OCT-12:09 | 4250.44 | 01-OCT-09:09 | 674.13 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 4920.26 | 31-OCT-17:00 |
November | 1079.86 | 04-NOV-12:09 | 4250.44 | 01-NOV-08:09 | 674.13 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 13095.84 | 25-NOV-18:00 |
December | 1079.86 | 02-DEC-13:09 | 4250.44 | 01-DEC-09:09 | 674.13 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 13636.85 | 09-DEC-12:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1079.86 | 4250.44 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2237.44 | |||||
Maximum of Months | 1079.86 | 4250.44 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 2506.98 | 16973.72 |
Report: PeakSpaceGainsMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2879.63 | 07-JAN-15:09 | 6064.13 | 01-JAN-11:09 | 1348.26 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 26557.51 | 30-JAN-18:00 |
February | 2879.63 | 04-FEB-15:09 | 6064.13 | 01-FEB-10:09 | 1348.26 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 29822.37 | 02-FEB-12:10 |
March | 2879.63 | 04-MAR-15:09 | 6064.13 | 01-MAR-10:09 | 1348.26 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 17706.52 | 05-MAR-18:00 |
April | 2879.63 | 01-APR-14:09 | 6064.13 | 01-APR-09:09 | 1348.26 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2878.53 | 15-APR-15:00 | 12943.17 | 03-APR-11:10 |
May | 2879.63 | 06-MAY-14:09 | 6064.13 | 01-MAY-09:09 | 1348.26 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2758.46 | 31-MAY-13:00 | 6496.07 | 01-MAY-17:00 |
June | 2879.63 | 03-JUN-14:09 | 6064.13 | 01-JUN-09:09 | 1348.26 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4305.60 | 11-JUN-15:00 | 5517.78 | 01-JUN-14:00 |
July | 2879.63 | 01-JUL-14:09 | 6064.13 | 01-JUL-09:09 | 1348.26 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2779.33 | 26-JUL-16:00 | 3987.67 | 10-JUL-12:00 |
August | 2879.63 | 05-AUG-14:09 | 6064.13 | 01-AUG-09:09 | 1348.26 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4402.51 | 04-AUG-15:00 | 3935.01 | 06-AUG-11:10 |
September | 2879.63 | 02-SEP-14:09 | 6064.13 | 01-SEP-09:09 | 1348.26 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3757.59 | 06-SEP-14:00 | 6571.74 | 29-SEP-17:00 |
October | 2879.63 | 07-OCT-14:09 | 6064.13 | 01-OCT-10:09 | 1348.26 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 8621.58 | 31-OCT-17:00 |
November | 2879.63 | 04-NOV-14:09 | 6064.13 | 01-NOV-09:09 | 1348.26 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 23054.20 | 25-NOV-18:00 |
December | 2879.63 | 02-DEC-15:09 | 6064.13 | 01-DEC-10:09 | 1348.26 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 24111.67 | 09-DEC-12:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2879.63 | 6064.13 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3935.01 | |||||
Maximum of Months | 2879.63 | 6064.13 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 4402.51 | 29822.37 |
Report: PeakSpaceGainsMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1439.81 | 07-JAN-15:09 | 3032.07 | 01-JAN-11:09 | 674.13 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 15128.83 | 30-JAN-18:00 |
February | 1439.81 | 04-FEB-15:09 | 3032.07 | 01-FEB-10:09 | 674.13 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 16973.71 | 02-FEB-12:10 |
March | 1439.81 | 04-MAR-15:09 | 3032.07 | 01-MAR-10:09 | 674.13 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 10065.93 | 05-MAR-18:00 |
April | 1439.81 | 01-APR-14:09 | 3032.07 | 01-APR-09:09 | 674.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1627.60 | 15-APR-15:00 | 7358.98 | 03-APR-11:10 |
May | 1439.81 | 06-MAY-14:09 | 3032.07 | 01-MAY-09:09 | 674.13 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1568.76 | 31-MAY-13:00 | 3681.40 | 01-MAY-17:00 |
June | 1439.81 | 03-JUN-14:09 | 3032.07 | 01-JUN-09:09 | 674.13 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2440.96 | 11-JUN-15:00 | 3139.39 | 01-JUN-14:00 |
July | 1439.81 | 01-JUL-14:09 | 3032.07 | 01-JUL-09:09 | 674.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1580.65 | 26-JUL-16:00 | 2264.31 | 10-JUL-12:00 |
August | 1439.81 | 05-AUG-14:09 | 3032.07 | 01-AUG-09:09 | 674.13 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2506.96 | 04-AUG-15:00 | 2237.44 | 06-AUG-11:10 |
September | 1439.81 | 02-SEP-14:09 | 3032.07 | 01-SEP-09:09 | 674.13 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2136.99 | 06-SEP-14:00 | 3735.96 | 29-SEP-17:00 |
October | 1439.81 | 07-OCT-14:09 | 3032.07 | 01-OCT-10:09 | 674.13 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 4920.25 | 31-OCT-17:00 |
November | 1439.81 | 04-NOV-14:09 | 3032.07 | 01-NOV-09:09 | 674.13 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 13095.83 | 25-NOV-18:00 |
December | 1439.81 | 02-DEC-15:09 | 3032.07 | 01-DEC-10:09 | 674.13 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 13636.84 | 09-DEC-12:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1439.81 | 3032.07 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2237.44 | |||||
Maximum of Months | 1439.81 | 3032.07 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 2506.96 | 16973.71 |
Report: PeakSpaceGainsMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1439.81 | 07-JAN-15:09 | 3032.07 | 01-JAN-11:09 | 674.13 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 15128.83 | 30-JAN-18:00 |
February | 1439.81 | 04-FEB-15:09 | 3032.07 | 01-FEB-10:09 | 674.13 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 16973.71 | 02-FEB-12:10 |
March | 1439.81 | 04-MAR-15:09 | 3032.07 | 01-MAR-10:09 | 674.13 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 10065.93 | 05-MAR-18:00 |
April | 1439.81 | 01-APR-14:09 | 3032.07 | 01-APR-09:09 | 674.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1627.59 | 15-APR-15:00 | 7358.98 | 03-APR-11:10 |
May | 1439.81 | 06-MAY-14:09 | 3032.07 | 01-MAY-09:09 | 674.13 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1568.75 | 31-MAY-13:00 | 3681.40 | 01-MAY-17:00 |
June | 1439.81 | 03-JUN-14:09 | 3032.07 | 01-JUN-09:09 | 674.13 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2440.95 | 11-JUN-15:00 | 3126.07 | 01-JUN-14:00 |
July | 1439.81 | 01-JUL-14:09 | 3032.07 | 01-JUL-09:09 | 674.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1580.64 | 26-JUL-16:00 | 2263.57 | 10-JUL-12:00 |
August | 1439.81 | 05-AUG-14:09 | 3032.07 | 01-AUG-09:09 | 674.13 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2506.95 | 04-AUG-15:00 | 2237.44 | 06-AUG-11:10 |
September | 1439.81 | 02-SEP-14:09 | 3032.07 | 01-SEP-09:09 | 674.13 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2136.98 | 06-SEP-14:00 | 3735.96 | 29-SEP-17:00 |
October | 1439.81 | 07-OCT-14:09 | 3032.07 | 01-OCT-10:09 | 674.13 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 4920.25 | 31-OCT-17:00 |
November | 1439.81 | 04-NOV-14:09 | 3032.07 | 01-NOV-09:09 | 674.13 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 13095.83 | 25-NOV-18:00 |
December | 1439.81 | 02-DEC-15:09 | 3032.07 | 01-DEC-10:09 | 674.13 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 13636.84 | 09-DEC-12:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1439.81 | 3032.07 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2237.44 | |||||
Maximum of Months | 1439.81 | 3032.07 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 2506.95 | 16973.71 |
Report: PeakSpaceGainsMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1439.81 | 07-JAN-15:09 | 3032.07 | 01-JAN-11:09 | 674.13 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 15128.83 | 30-JAN-18:00 |
February | 1439.81 | 04-FEB-15:09 | 3032.07 | 01-FEB-10:09 | 674.13 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 16973.71 | 02-FEB-12:10 |
March | 1439.81 | 04-MAR-15:09 | 3032.07 | 01-MAR-10:09 | 674.13 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 10065.93 | 05-MAR-18:00 |
April | 1439.81 | 01-APR-14:09 | 3032.07 | 01-APR-09:09 | 674.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1627.56 | 15-APR-15:00 | 7358.98 | 03-APR-11:10 |
May | 1439.81 | 06-MAY-14:09 | 3032.07 | 01-MAY-09:09 | 674.13 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1568.74 | 31-MAY-13:00 | 3681.40 | 01-MAY-17:00 |
June | 1439.81 | 03-JUN-14:09 | 3032.07 | 01-JUN-09:09 | 674.13 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2440.93 | 11-JUN-15:00 | 3092.66 | 01-JUN-14:00 |
July | 1439.81 | 01-JUL-14:09 | 3032.07 | 01-JUL-09:09 | 674.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1580.62 | 26-JUL-16:00 | 2236.96 | 10-JUL-12:00 |
August | 1439.81 | 05-AUG-14:09 | 3032.07 | 01-AUG-09:09 | 674.13 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2506.94 | 04-AUG-15:00 | 2237.44 | 06-AUG-11:10 |
September | 1439.81 | 02-SEP-14:09 | 3032.07 | 01-SEP-09:09 | 674.13 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2136.97 | 06-SEP-14:00 | 3735.96 | 29-SEP-17:00 |
October | 1439.81 | 07-OCT-14:09 | 3032.07 | 01-OCT-10:09 | 674.13 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 4920.25 | 31-OCT-17:00 |
November | 1439.81 | 04-NOV-14:09 | 3032.07 | 01-NOV-09:09 | 674.13 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 13095.83 | 25-NOV-18:00 |
December | 1439.81 | 02-DEC-15:09 | 3032.07 | 01-DEC-10:09 | 674.13 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 13636.84 | 09-DEC-12:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1439.81 | 3032.07 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2236.96 | |||||
Maximum of Months | 1439.81 | 3032.07 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 2506.94 | 16973.71 |
Report: PeakSpaceGainsMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1439.81 | 07-JAN-15:09 | 3032.07 | 01-JAN-11:09 | 674.13 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 15663.84 | 30-JAN-18:00 |
February | 1439.81 | 04-FEB-15:09 | 3032.07 | 01-FEB-10:09 | 674.13 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 17730.17 | 02-FEB-12:10 |
March | 1439.81 | 04-MAR-15:09 | 3032.07 | 01-MAR-10:09 | 674.13 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 10638.98 | 05-MAR-18:00 |
April | 1439.81 | 01-APR-14:09 | 3032.07 | 01-APR-09:09 | 674.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1812.14 | 15-APR-15:00 | 7767.90 | 03-APR-11:10 |
May | 1439.81 | 06-MAY-14:09 | 3032.07 | 01-MAY-09:09 | 674.13 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1651.60 | 31-MAY-13:00 | 4011.50 | 01-MAY-17:00 |
June | 1439.81 | 03-JUN-14:09 | 3032.07 | 01-JUN-09:09 | 674.13 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2650.20 | 11-JUN-15:00 | 3096.89 | 01-JUN-14:00 |
July | 1439.81 | 01-JUL-14:09 | 3032.07 | 01-JUL-09:09 | 674.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1664.05 | 26-JUL-16:00 | 2285.03 | 10-JUL-12:00 |
August | 1439.81 | 05-AUG-14:09 | 3032.07 | 01-AUG-09:09 | 674.13 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2606.07 | 04-AUG-15:00 | 2353.47 | 06-AUG-11:10 |
September | 1439.81 | 02-SEP-14:09 | 3032.07 | 01-SEP-09:09 | 674.13 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2249.86 | 06-SEP-14:00 | 3948.65 | 29-SEP-17:00 |
October | 1439.81 | 07-OCT-14:09 | 3032.07 | 01-OCT-10:09 | 674.13 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 5001.93 | 31-OCT-17:00 |
November | 1439.81 | 04-NOV-14:09 | 3032.07 | 01-NOV-09:09 | 674.13 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 13947.79 | 25-NOV-18:00 |
December | 1439.81 | 02-DEC-15:09 | 3032.07 | 01-DEC-10:09 | 674.13 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 15147.81 | 09-DEC-12:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1439.81 | 3032.07 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2285.03 | |||||
Maximum of Months | 1439.81 | 3032.07 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 2650.20 | 17730.17 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 18192.80 | 06-JAN-00:01 | 1439.81 | 34788.19 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1203.29 |
February | 21714.81 | 03-FEB-00:01 | 1619.79 | 39136.71 | 6741.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 888.62 |
March | 11182.10 | 11-MAR-00:23 | 539.93 | 13045.57 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 529.62 |
April | 13207.96 | 16-APR-16:04 | 10798.60 | 41310.97 | 6741.28 | 0.00 | 0.00 | 0.00 | 0.00 | 2480.23 | 0.00 |
May | 13965.56 | 31-MAY-15:00 | 899.88 | 8262.19 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 2822.75 | 0.00 |
June | 32657.30 | 28-JUN-07:02 | 899.88 | 2174.26 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 202.80 |
July | 33413.25 | 28-JUL-07:02 | 0.00 | 2174.26 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 255.92 |
August | 29558.25 | 23-AUG-07:03 | 719.91 | 1739.41 | 299.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 484.55 |
September | 33301.77 | 08-SEP-07:02 | 0.00 | 2174.26 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 503.20 |
October | 7296.19 | 31-OCT-18:00 | 1799.77 | 8262.19 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1676.52 |
November | 12770.00 | 25-NOV-00:12 | 1079.86 | 26091.14 | 4494.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 905.78 |
December | 17082.17 | 09-DEC-00:01 | 1439.81 | 34788.19 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3643.91 |
Annual Sum or Average | |||||||||||
Minimum of Months | 7296.19 | 0.00 | 1739.41 | 299.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 33413.25 | 10798.60 | 41310.97 | 6741.28 | 0.00 | 0.00 | 0.00 | 0.00 | 2822.75 | 3643.91 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5907.18 | 02-JAN-18:03 | 3599.52 | 18426.77 | 2696.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1561.75 |
February | 2708.14 | 24-FEB-20:10 | 539.93 | 4606.69 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.27 |
March | 3482.59 | 20-MAR-19:40 | 539.93 | 4606.69 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 476.99 |
April | 26699.98 | 19-APR-20:02 | 5399.28 | 46066.91 | 6741.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.78 |
May | 27568.61 | 21-MAY-19:42 | 7199.04 | 46066.91 | 6741.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.74 |
June | 22827.84 | 23-JUN-22:40 | 3239.57 | 41460.22 | 6067.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.61 |
July | 23345.65 | 23-JUL-20:57 | 5399.28 | 46066.91 | 6741.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.31 |
August | 26336.45 | 06-AUG-19:15 | 7199.04 | 46066.91 | 6741.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.67 |
September | 28141.54 | 24-SEP-17:01 | 10798.56 | 46066.91 | 6741.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 508.71 |
October | 27026.14 | 11-OCT-20:29 | 5399.28 | 46066.91 | 6741.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 116.24 |
November | 4300.14 | 05-NOV-17:10 | 2159.71 | 9213.38 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 595.40 |
December | 3882.46 | 17-DEC-11:03 | 1079.86 | 13820.07 | 2022.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1080.78 |
Annual Sum or Average | |||||||||||
Minimum of Months | 2708.14 | 539.93 | 4606.69 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.31 | |
Maximum of Months | 28141.54 | 10798.56 | 46066.91 | 6741.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1561.75 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1396.17 | 13-JAN-18:07 | 2699.64 | 12751.32 | 2022.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 888.06 |
February | 2967.71 | 10-FEB-11:43 | 539.93 | 12751.32 | 2022.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1212.35 |
March | 4986.00 | 16-MAR-19:55 | 359.95 | 8948.30 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 198.06 |
April | 7097.24 | 18-APR-14:00 | 539.93 | 4250.44 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1179.74 | 0.00 |
May | 13245.12 | 13-MAY-06:01 | 0.00 | 1565.95 | 262.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.27 |
June | 18687.30 | 28-JUN-06:02 | 0.00 | 1118.54 | 187.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.11 |
July | 20678.91 | 01-JUL-06:02 | 0.00 | 1118.54 | 187.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.85 |
August | 21356.60 | 06-AUG-07:01 | 0.00 | 1565.95 | 262.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 534.63 |
September | 23716.02 | 08-SEP-06:02 | 0.00 | 1342.24 | 224.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.88 |
October | 3967.82 | 20-OCT-15:00 | 359.95 | 4250.44 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 157.73 |
November | 5536.04 | 21-NOV-20:23 | 359.95 | 8948.30 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 152.56 |
December | 3635.42 | 29-DEC-18:23 | 2699.64 | 12751.32 | 2022.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1115.66 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1396.17 | 0.00 | 1118.54 | 187.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 23716.02 | 2699.64 | 12751.32 | 2022.38 | 0.00 | 0.00 | 0.00 | 0.00 | 1179.74 | 1212.35 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4141.53 | 11-JAN-18:43 | 2699.64 | 12751.32 | 2022.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1026.27 |
February | 2616.13 | 07-FEB-11:55 | 359.95 | 8500.88 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 893.33 |
March | 3046.76 | 25-MAR-07:01 | 899.88 | 22370.74 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 928.08 |
April | 7048.61 | 18-APR-14:00 | 539.93 | 4250.44 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1179.73 | 0.00 |
May | 11666.42 | 13-MAY-06:01 | 0.00 | 1565.95 | 262.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.27 |
June | 18762.73 | 28-JUN-06:02 | 0.00 | 1118.54 | 187.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.23 |
July | 20756.62 | 01-JUL-06:02 | 0.00 | 1118.54 | 187.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.97 |
August | 22059.10 | 06-AUG-07:01 | 0.00 | 1565.95 | 262.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 534.71 |
September | 23794.98 | 08-SEP-06:02 | 0.00 | 1342.24 | 224.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.99 |
October | 3802.29 | 23-OCT-07:01 | 899.88 | 22370.74 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1058.01 |
November | 3697.58 | 04-NOV-07:01 | 629.92 | 15659.52 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1029.84 |
December | 4256.03 | 05-DEC-11:23 | 539.93 | 12751.32 | 2022.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1613.15 |
Annual Sum or Average | |||||||||||
Minimum of Months | 2616.13 | 0.00 | 1118.54 | 187.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 23794.98 | 2699.64 | 22370.74 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 1179.73 | 1613.15 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1006.16 | 13-JAN-18:07 | 2699.64 | 12751.32 | 2022.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 888.06 |
February | 3251.63 | 10-FEB-20:13 | 269.96 | 6711.22 | 1123.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 544.30 |
March | 2433.85 | 20-MAR-07:01 | 899.88 | 22370.74 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 740.25 |
April | 6857.23 | 18-APR-14:00 | 539.93 | 4250.44 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1179.72 | 0.00 |
May | 7644.94 | 13-MAY-06:01 | 0.00 | 1565.95 | 262.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.27 |
June | 18720.68 | 28-JUN-06:02 | 0.00 | 1118.54 | 187.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.69 |
July | 20279.37 | 01-JUL-06:02 | 0.00 | 1118.54 | 187.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.51 |
August | 19669.47 | 06-AUG-07:01 | 0.00 | 1565.95 | 262.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 534.43 |
September | 23785.42 | 08-SEP-06:02 | 0.00 | 1342.24 | 224.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.36 |
October | 3743.11 | 23-OCT-07:01 | 899.88 | 22370.74 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1047.98 |
November | 3694.58 | 13-NOV-19:03 | 1079.86 | 12751.32 | 2022.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1048.02 |
December | 4735.56 | 05-DEC-20:03 | 359.95 | 8948.30 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 398.44 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1006.16 | 0.00 | 1118.54 | 187.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 23785.42 | 2699.64 | 22370.74 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 1179.72 | 1048.02 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5930.60 | 13-JAN-18:03 | 3671.52 | 18192.39 | 4044.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1564.74 |
February | 1523.32 | 24-FEB-12:00 | 1547.80 | 6064.13 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1314.73 |
March | 3611.34 | 24-MAR-18:20 | 935.88 | 6064.13 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1199.15 |
April | 11576.55 | 18-APR-14:10 | 2483.68 | 6064.13 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 2084.14 | 0.00 |
May | 12974.19 | 31-MAY-15:00 | 2483.68 | 6064.13 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 2746.56 | 0.00 |
June | 32864.52 | 12-JUN-07:03 | 0.00 | 1276.66 | 299.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 399.43 |
July | 33217.13 | 28-JUL-07:02 | 0.00 | 1595.82 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 241.65 |
August | 30953.06 | 14-AUG-07:02 | 0.00 | 1595.82 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 568.66 |
September | 35675.27 | 12-SEP-07:02 | 0.00 | 1595.82 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 605.14 |
October | 5200.75 | 20-OCT-15:00 | 2483.68 | 6064.13 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 277.56 |
November | 7303.33 | 10-NOV-18:17 | 3671.52 | 18192.39 | 4044.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2359.19 |
December | 867.99 | 02-DEC-12:00 | 2087.73 | 6064.13 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1459.23 |
Annual Sum or Average | |||||||||||
Minimum of Months | 867.99 | 0.00 | 1276.66 | 299.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 35675.27 | 3671.52 | 18192.39 | 4044.77 | 0.00 | 0.00 | 0.00 | 0.00 | 2746.56 | 2359.19 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 201.04 | 13-JAN-12:00 | 773.90 | 3032.07 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 853.18 |
February | 657.88 | 24-FEB-12:00 | 773.90 | 3032.07 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 730.21 |
March | 4246.81 | 21-MAR-19:03 | 593.92 | 4787.47 | 1123.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 174.24 |
April | 5994.89 | 18-APR-14:10 | 1241.83 | 3032.07 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1178.92 | 0.00 |
May | 6770.21 | 31-MAY-15:00 | 1241.83 | 3032.07 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1562.61 | 0.00 |
June | 17683.67 | 28-JUN-07:02 | 0.00 | 797.91 | 187.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.87 |
July | 17946.25 | 28-JUL-07:02 | 0.00 | 797.91 | 187.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 129.04 |
August | 14411.67 | 14-AUG-07:02 | 0.00 | 797.91 | 187.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 319.27 |
September | 17112.93 | 11-SEP-07:03 | 0.00 | 638.33 | 149.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 169.72 |
October | 2617.01 | 20-OCT-15:00 | 1241.83 | 3032.07 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 157.73 |
November | 2237.85 | 04-NOV-17:15 | 395.95 | 3191.65 | 749.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 661.85 |
December | 289.76 | 02-DEC-12:00 | 1043.86 | 3032.07 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 807.62 |
Annual Sum or Average | |||||||||||
Minimum of Months | 201.04 | 0.00 | 638.33 | 149.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17946.25 | 1241.83 | 4787.47 | 1123.55 | 0.00 | 0.00 | 0.00 | 0.00 | 1562.61 | 853.18 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 147.94 | 13-JAN-12:00 | 773.90 | 3032.07 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 853.18 |
February | 600.13 | 24-FEB-12:00 | 773.90 | 3032.07 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 730.21 |
March | 3599.40 | 21-MAR-17:43 | 1835.76 | 9096.20 | 2022.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1168.45 |
April | 5875.19 | 18-APR-14:10 | 1241.83 | 3032.07 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1178.92 | 0.00 |
May | 6670.71 | 31-MAY-15:00 | 1241.83 | 3032.07 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1562.61 | 0.00 |
June | 17611.88 | 28-JUN-07:02 | 0.00 | 797.91 | 187.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 102.56 |
July | 17880.01 | 28-JUL-07:02 | 0.00 | 797.91 | 187.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 126.89 |
August | 13507.84 | 28-AUG-07:03 | 0.00 | 638.33 | 149.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 224.81 |
September | 16464.36 | 11-SEP-07:03 | 0.00 | 638.33 | 149.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 169.52 |
October | 2521.49 | 20-OCT-15:00 | 1241.83 | 3032.07 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 157.73 |
November | 2212.47 | 04-NOV-17:15 | 395.95 | 3191.65 | 749.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 657.27 |
December | 239.98 | 02-DEC-12:00 | 1043.86 | 3032.07 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 807.62 |
Annual Sum or Average | |||||||||||
Minimum of Months | 147.94 | 0.00 | 638.33 | 149.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17880.01 | 1835.76 | 9096.20 | 2022.38 | 0.00 | 0.00 | 0.00 | 0.00 | 1562.61 | 1168.45 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:05 | 0.00 | 319.16 | 74.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 689.47 |
February | 2500.04 | 25-FEB-11:15 | 2087.72 | 6064.13 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 906.25 |
March | 2687.43 | 22-MAR-18:35 | 935.88 | 6064.13 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 902.63 |
April | 5565.65 | 18-APR-14:20 | 1241.83 | 3032.07 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1178.14 | 0.00 |
May | 6449.09 | 31-MAY-15:00 | 1241.83 | 3032.07 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1562.60 | 0.00 |
June | 16377.69 | 28-JUN-07:02 | 0.00 | 797.91 | 187.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.65 |
July | 16808.80 | 03-JUL-07:02 | 0.00 | 797.91 | 187.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 184.98 |
August | 12947.13 | 03-AUG-07:02 | 0.00 | 957.49 | 224.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.39 |
September | 14645.71 | 11-SEP-07:03 | 0.00 | 638.33 | 149.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 168.87 |
October | 2294.42 | 20-OCT-15:00 | 1241.83 | 3032.07 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 157.73 |
November | 2654.66 | 16-NOV-18:05 | 1223.84 | 6064.13 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 885.61 |
December | 26.49 | 02-DEC-12:00 | 1043.86 | 3032.07 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 807.62 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 319.16 | 74.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16808.80 | 2087.72 | 6064.13 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 1562.60 | 906.25 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:05 | 0.00 | 319.16 | 74.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1661.04 |
February | 0.00 | 01-FEB-00:02 | 0.00 | 797.91 | 187.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3312.58 |
March | 488.67 | 24-MAR-17:10 | 1223.84 | 6064.13 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 827.92 |
April | 5057.01 | 18-APR-14:10 | 1241.83 | 3032.07 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1307.37 | 0.00 |
May | 6084.51 | 31-MAY-15:00 | 1241.83 | 3032.07 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1638.68 | 0.00 |
June | 14055.62 | 26-JUN-07:02 | 0.00 | 797.91 | 187.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.35 |
July | 16994.68 | 04-JUL-08:62 | 0.00 | 797.91 | 187.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.47 |
August | 12066.81 | 03-AUG-07:02 | 0.00 | 957.49 | 224.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.17 |
September | 8777.65 | 07-SEP-14:10 | 1241.83 | 3032.07 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 2126.13 | 0.00 |
October | 2225.43 | 25-OCT-17:45 | 1223.84 | 6064.13 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1103.28 |
November | 1793.10 | 04-NOV-17:15 | 395.95 | 3191.65 | 749.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 760.31 |
December | 0.00 | 01-DEC-00:03 | 0.00 | 478.75 | 112.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1910.90 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 319.16 | 74.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16994.68 | 1241.83 | 6064.13 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 2126.13 | 3312.58 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | |
January | 0.111983E+12 | 87229.99 | 14-JAN-17:19 | 0.287607E+12 | 390351.07 | 30-JAN-17:00 |
February | 0.100463E+12 | 85110.05 | 11-FEB-17:49 | 0.200498E+12 | 441652.67 | 02-FEB-12:09 |
March | 0.111209E+12 | 84125.30 | 24-MAR-18:00 | 0.120872E+12 | 257276.61 | 05-MAR-17:00 |
April | 0.108713E+12 | 119405.28 | 15-APR-14:20 | 0.548954E+11 | 217529.87 | 03-APR-07:10 |
May | 0.114778E+12 | 121320.19 | 31-MAY-12:20 | 0.217374E+10 | 91003.60 | 02-MAY-07:10 |
June | 0.132239E+12 | 141138.85 | 11-JUN-14:00 | 0.173262E+09 | 10527.34 | 05-JUN-07:10 |
July | 0.143428E+12 | 139668.49 | 26-JUL-15:50 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.143768E+12 | 150546.18 | 04-AUG-13:00 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 0.122019E+12 | 132052.17 | 06-SEP-13:00 | 0.164854E+10 | 80594.45 | 30-SEP-07:10 |
October | 0.110240E+12 | 87111.02 | 20-OCT-14:30 | 0.200825E+11 | 93573.67 | 17-OCT-07:10 |
November | 0.107801E+12 | 85091.27 | 18-NOV-17:30 | 0.117543E+12 | 326140.43 | 25-NOV-17:00 |
December | 0.111779E+12 | 85092.94 | 01-DEC-18:30 | 0.222187E+12 | 369259.43 | 09-DEC-12:09 |
Annual Sum or Average | 0.141842E+13 | 0.102768E+13 | ||||
Minimum of Months | 0.100463E+12 | 84125.30 | 0.00 | 0.00 | ||
Maximum of Months | 0.143768E+12 | 150546.18 | 0.287607E+12 | 441652.67 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.595337E+11 | 0.116890E+11 | 0.108804E+11 | 0.00 | 0.240434E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.583666E+10 | 0.00 |
February | 0.539017E+11 | 0.973946E+10 | 0.985143E+10 | 0.00 | 0.216620E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.530867E+10 | 0.00 |
March | 0.604219E+11 | 0.965065E+10 | 0.110523E+11 | 0.00 | 0.241915E+11 | 0.00 | 0.00 | 601711.68 | 0.00 | 0.00 | 0.00 | 0.589234E+10 | 0.00 |
April | 0.577706E+11 | 0.817894E+10 | 0.105581E+11 | 0.00 | 0.231239E+11 | 0.00 | 0.00 | 0.350655E+10 | 0.00 | 0.00 | 0.00 | 0.557462E+10 | 0.00 |
May | 0.599558E+11 | 0.743886E+10 | 0.109629E+11 | 0.00 | 0.243392E+11 | 0.00 | 0.00 | 0.645476E+10 | 0.00 | 0.00 | 0.00 | 0.562691E+10 | 0.00 |
June | 0.584038E+11 | 0.669032E+10 | 0.106818E+11 | 0.00 | 0.236165E+11 | 0.00 | 0.00 | 0.274999E+11 | 0.00 | 0.00 | 0.00 | 0.534629E+10 | 0.00 |
July | 0.593665E+11 | 0.713014E+10 | 0.108460E+11 | 0.00 | 0.239242E+11 | 0.00 | 0.00 | 0.367729E+11 | 0.00 | 0.00 | 0.00 | 0.538863E+10 | 0.00 |
August | 0.603780E+11 | 0.800555E+10 | 0.110454E+11 | 0.00 | 0.244211E+11 | 0.00 | 0.00 | 0.345192E+11 | 0.00 | 0.00 | 0.00 | 0.539849E+10 | 0.00 |
September | 0.578145E+11 | 0.882176E+10 | 0.105649E+11 | 0.00 | 0.233376E+11 | 0.00 | 0.00 | 0.162490E+11 | 0.00 | 0.00 | 0.00 | 0.523147E+10 | 0.00 |
October | 0.595337E+11 | 0.103146E+11 | 0.108804E+11 | 0.00 | 0.238514E+11 | 0.00 | 0.00 | 0.153805E+09 | 0.00 | 0.00 | 0.00 | 0.550616E+10 | 0.00 |
November | 0.576828E+11 | 0.110166E+11 | 0.105443E+11 | 0.00 | 0.231090E+11 | 0.00 | 0.00 | 1319543.67 | 0.00 | 0.00 | 0.00 | 0.544720E+10 | 0.00 |
December | 0.594104E+11 | 0.119724E+11 | 0.108529E+11 | 0.00 | 0.237960E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.574717E+10 | 0.00 |
Annual Sum or Average | 0.704173E+12 | 0.110648E+12 | 0.128721E+12 | 0.283416E+12 | 0.00 | 0.125158E+12 | 0.663046E+11 | ||||||
Minimum of Months | 0.539017E+11 | 0.669032E+10 | 0.985143E+10 | 0.00 | 0.216620E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.523147E+10 | 0.00 |
Maximum of Months | 0.604219E+11 | 0.119724E+11 | 0.110523E+11 | 0.00 | 0.244211E+11 | 0.00 | 0.00 | 0.367729E+11 | 0.00 | 0.00 | 0.00 | 0.589234E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS [J] | COOLING:GAS [] | WATERSYSTEMS:GAS [] | COGENERATION:GAS [] | HUMIDIFIER:GAS [] | |
January | 0.00 | 0.00 | 0.287607E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.200498E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.120872E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.548954E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.217374E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.173262E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.164854E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.200825E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.117543E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.222187E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.102768E+13 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.287607E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum}[W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum}[W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum}[W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum}[W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 43812.60 | 01-JAN-11:09 | 7048.38 | 01-JAN-00:10 | 8089.53 | 01-JAN-11:09 | 0.00 | 16442.89 | 02-JAN-08:09 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 43812.60 | 01-FEB-10:09 | 7048.38 | 01-FEB-00:10 | 8089.53 | 01-FEB-10:09 | 0.00 | 16442.89 | 01-FEB-08:09 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 43812.60 | 01-MAR-10:09 | 7048.38 | 01-MAR-00:10 | 8089.53 | 01-MAR-10:09 | 0.00 | 16442.89 | 26-MAR-08:09 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 43812.60 | 01-APR-09:09 | 7048.38 | 01-APR-00:10 | 8089.53 | 01-APR-09:09 | 0.00 | 16442.89 | 12-APR-07:10 | 0.00 | 0.00 | 01-APR-00:10 |
May | 43812.60 | 01-MAY-09:09 | 7048.38 | 01-MAY-00:10 | 8089.53 | 01-MAY-09:09 | 0.00 | 16442.89 | 01-MAY-07:10 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 43812.60 | 01-JUN-09:09 | 7048.38 | 01-JUN-00:10 | 8089.53 | 01-JUN-09:09 | 0.00 | 16442.89 | 09-JUN-17:19 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 43812.60 | 01-JUL-09:09 | 7048.38 | 01-JUL-00:10 | 8089.53 | 01-JUL-09:09 | 0.00 | 16442.89 | 01-JUL-08:20 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 43812.60 | 01-AUG-09:09 | 7048.38 | 01-AUG-00:10 | 8089.53 | 01-AUG-09:09 | 0.00 | 16442.89 | 01-AUG-11:09 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 43812.60 | 01-SEP-09:09 | 7048.38 | 01-SEP-00:10 | 8089.53 | 01-SEP-09:09 | 0.00 | 16442.89 | 01-SEP-11:39 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 43812.60 | 01-OCT-10:09 | 7048.38 | 01-OCT-00:10 | 8089.53 | 01-OCT-10:09 | 0.00 | 16442.89 | 08-OCT-08:09 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 43812.60 | 01-NOV-09:09 | 7048.38 | 01-NOV-00:10 | 8089.53 | 01-NOV-09:09 | 0.00 | 16442.89 | 16-NOV-08:09 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 43812.60 | 01-DEC-10:09 | 7048.38 | 01-DEC-00:10 | 8089.53 | 01-DEC-10:09 | 0.00 | 16442.89 | 01-DEC-08:09 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 43812.60 | 7048.38 | 8089.53 | 0.00 | 16442.89 | 0.00 | 0.00 | |||||
Maximum of Months | 43812.60 | 7048.38 | 8089.53 | 0.00 | 16442.89 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum}[W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum}[W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 11884.51 | 07-JAN-14:09 | 0.00 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 9763.61 | 15-FEB-13:50 | 0.00 |
March | 527.60 | 25-MAR-21:40 | 0.00 | 0.00 | 0.00 | 9759.95 | 24-MAR-12:20 | 0.00 |
April | 44977.99 | 18-APR-14:09 | 0.00 | 0.00 | 0.00 | 9755.18 | 11-APR-12:30 | 0.00 |
May | 46679.82 | 31-MAY-14:00 | 0.00 | 0.00 | 0.00 | 9763.32 | 30-MAY-12:00 | 0.00 |
June | 69465.26 | 11-JUN-14:00 | 0.00 | 0.00 | 0.00 | 7976.41 | 02-JUN-12:09 | 0.00 |
July | 64630.51 | 26-JUL-15:20 | 0.00 | 0.00 | 0.00 | 9714.59 | 31-JUL-12:09 | 0.00 |
August | 76736.44 | 04-AUG-13:00 | 0.00 | 0.00 | 0.00 | 9713.08 | 16-AUG-12:09 | 0.00 |
September | 58355.14 | 06-SEP-14:09 | 0.00 | 0.00 | 0.00 | 9714.87 | 26-SEP-13:00 | 0.00 |
October | 14934.54 | 20-OCT-14:00 | 0.00 | 0.00 | 0.00 | 7602.45 | 31-OCT-12:30 | 0.00 |
November | 790.25 | 03-NOV-20:40 | 0.00 | 0.00 | 0.00 | 9729.01 | 04-NOV-12:00 | 0.00 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 11607.50 | 16-DEC-11:30 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 7602.45 | 0.00 | ||
Maximum of Months | 76736.44 | 0.00 | 0.00 | 0.00 | 11884.51 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 87229.99 | 14-JAN-17:19 | 43812.60 | 8089.53 | 7048.38 | 0.00 | 16442.89 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 85110.05 | 11-FEB-17:49 | 43812.60 | 8089.53 | 7048.38 | 0.00 | 16442.89 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 84125.30 | 24-MAR-18:00 | 43812.60 | 8089.53 | 7048.38 | 0.00 | 16442.89 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 119405.28 | 15-APR-14:20 | 43812.60 | 8089.53 | 0.00 | 0.00 | 16442.89 | 0.00 | 0.00 | 43687.84 | 0.00 |
May | 121320.19 | 31-MAY-12:20 | 43812.60 | 8089.53 | 0.00 | 0.00 | 16442.89 | 0.00 | 0.00 | 45370.77 | 0.00 |
June | 141138.85 | 11-JUN-14:00 | 43812.60 | 8089.53 | 0.00 | 0.00 | 16442.89 | 0.00 | 0.00 | 69465.26 | 0.00 |
July | 139668.49 | 26-JUL-15:50 | 43812.60 | 8089.53 | 0.00 | 0.00 | 16442.89 | 0.00 | 0.00 | 64359.73 | 0.00 |
August | 150546.18 | 04-AUG-13:00 | 43812.60 | 8089.53 | 0.00 | 0.00 | 16442.89 | 0.00 | 0.00 | 76736.44 | 0.00 |
September | 132052.17 | 06-SEP-13:00 | 43812.60 | 8089.53 | 0.00 | 0.00 | 16442.89 | 0.00 | 0.00 | 58243.00 | 0.00 |
October | 87111.02 | 20-OCT-14:30 | 43812.60 | 8089.53 | 0.00 | 0.00 | 16442.89 | 0.00 | 0.00 | 13307.36 | 0.00 |
November | 85091.27 | 18-NOV-17:30 | 43812.60 | 8089.53 | 7048.38 | 0.00 | 16442.89 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 85092.94 | 01-DEC-18:30 | 43812.60 | 8089.53 | 7048.38 | 0.00 | 16442.89 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 84125.30 | 43812.60 | 8089.53 | 0.00 | 0.00 | 16442.89 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 150546.18 | 43812.60 | 8089.53 | 7048.38 | 0.00 | 16442.89 | 0.00 | 0.00 | 76736.44 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS {Maximum}[W] | HEATING:GAS {TIMESTAMP} | COOLING:GAS [] | WATERSYSTEMS:GAS [] | COGENERATION:GAS [] | |
January | 0.00 | 0.00 | 390351.07 | 30-JAN-17:00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 441652.67 | 02-FEB-12:09 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 257276.61 | 05-MAR-17:00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 217529.87 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 91003.60 | 02-MAY-07:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 10527.34 | 05-JUN-07:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 80594.45 | 30-SEP-07:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 93573.67 | 17-OCT-07:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 326140.43 | 25-NOV-17:00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 369259.43 | 09-DEC-12:09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 441652.67 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 13.50 | 17.43 | 2.83 | 20.26 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 8.33 | 17.40 | 1.67 | 20.24 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 4.17 | 19.68 | 1.17 | 20.29 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.67 | 20.44 | 0.17 | 20.29 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.17 | 20.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 2.17 | 20.17 | 0.83 | 20.28 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 8.00 | 18.31 | 1.67 | 20.32 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 37.00 | 18.09 | 8.33 | 20.28 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 13.50 | 20.54 | 2.83 | 20.32 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 4.17 | 20.29 | 1.50 | 20.32 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 2.33 | 20.25 | 0.83 | 20.26 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.83 | 20.40 | 0.17 | 20.34 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1.17 | 20.40 | 0.17 | 20.38 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1.33 | 20.22 | 0.67 | 20.28 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 9.83 | 20.29 | 3.33 | 20.30 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 4.17 | 20.40 | 1.50 | 20.38 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 4.17 | 18.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 1.17 | 20.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.33 | 20.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.50 | 20.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1.50 | 18.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 7.67 | 18.88 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 4.17 | 20.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 6.50 | 17.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 2.33 | 18.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.67 | 20.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.17 | 20.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.83 | 20.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 2.00 | 17.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 12.50 | 18.31 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 6.50 | 20.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 7.33 | 17.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3.00 | 17.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.67 | 20.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.17 | 20.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.83 | 20.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 2.50 | 17.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 14.50 | 18.19 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 7.33 | 20.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 11.67 | 16.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6.83 | 17.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 2.00 | 18.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.17 | 20.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1.83 | 19.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 8.33 | 17.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 30.83 | 17.43 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 11.67 | 20.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 10.67 | 17.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6.17 | 17.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 2.00 | 19.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.17 | 20.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1.67 | 19.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6.50 | 17.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 27.17 | 17.52 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 10.67 | 20.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 11.17 | 17.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6.33 | 17.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 2.00 | 18.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.17 | 20.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1.83 | 18.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6.83 | 17.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 28.33 | 17.48 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 11.17 | 20.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 13.17 | 16.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 7.50 | 17.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 2.83 | 18.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.33 | 17.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 2.33 | 18.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 10.50 | 17.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 36.67 | 17.25 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 13.17 | 18.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 56.50 | 15.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 37.50 | 15.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 20.83 | 15.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5.17 | 16.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.17 | 20.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 17.67 | 15.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 33.00 | 15.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 170.83 | 15.38 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 56.50 | 20.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: LGSTORE1
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 496.00 | 21.04 | 469.17 | 21.04 | 469.17 | 21.04 |
February | 448.00 | 21.05 | 313.67 | 21.03 | 313.67 | 21.03 |
March | 493.17 | 21.24 | 246.50 | 21.04 | 246.50 | 21.04 |
April | 409.00 | 21.55 | 149.67 | 22.03 | 97.50 | 21.03 |
May | 162.83 | 22.82 | 223.33 | 23.85 | 15.17 | 23.32 |
June | 104.00 | 23.42 | 377.17 | 23.89 | 59.17 | 23.89 |
July | 123.50 | 23.89 | 488.00 | 23.89 | 123.50 | 23.89 |
August | 138.83 | 23.89 | 475.33 | 23.89 | 137.00 | 23.89 |
September | 125.17 | 22.38 | 254.33 | 23.87 | 5.00 | 22.97 |
October | 419.67 | 21.72 | 36.17 | 22.49 | 17.67 | 21.03 |
November | 456.17 | 21.42 | 182.33 | 21.07 | 181.50 | 21.05 |
December | 496.00 | 21.05 | 438.00 | 21.04 | 438.00 | 21.04 |
Annual Sum or Average | 3872.33 | 21.62 | 3653.67 | 22.51 | 2103.83 | 21.49 |
Minimum of Months | 104.00 | 21.04 | 36.17 | 21.03 | 5.00 | 21.03 |
Maximum of Months | 496.00 | 23.89 | 488.00 | 23.89 | 469.17 | 23.89 |
Report: ComfortReportSimple55Monthly
For: SMSTORE1
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 496.00 | 21.17 | 388.67 | 21.10 | 388.67 | 21.10 |
February | 448.00 | 21.29 | 222.83 | 21.10 | 222.83 | 21.10 |
March | 487.17 | 21.65 | 121.50 | 21.12 | 121.50 | 21.12 |
April | 376.17 | 21.98 | 79.33 | 22.99 | 25.33 | 21.13 |
May | 94.00 | 23.03 | 255.00 | 23.86 | 8.67 | 23.84 |
June | 59.83 | 23.57 | 381.67 | 23.85 | 36.67 | 23.88 |
July | 73.50 | 23.87 | 474.00 | 23.83 | 72.00 | 23.88 |
August | 83.33 | 23.86 | 460.83 | 23.84 | 80.17 | 23.88 |
September | 94.67 | 22.95 | 232.33 | 23.85 | 0.00 | 0.00 |
October | 387.00 | 22.38 | 26.33 | 23.75 | 1.50 | 21.38 |
November | 420.17 | 21.68 | 127.00 | 21.27 | 119.83 | 21.11 |
December | 496.00 | 21.29 | 272.50 | 21.11 | 272.50 | 21.11 |
Annual Sum or Average | 3515.83 | 21.81 | 3042.00 | 22.81 | 1349.67 | 21.51 |
Minimum of Months | 59.83 | 21.17 | 26.33 | 21.10 | 0.00 | 0.00 |
Maximum of Months | 496.00 | 23.87 | 474.00 | 23.86 | 388.67 | 23.88 |
Report: ComfortReportSimple55Monthly
For: SMSTORE2
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 371.00 | 21.11 | 344.33 | 21.11 | 344.33 | 21.11 |
February | 336.00 | 21.11 | 213.67 | 21.11 | 213.67 | 21.11 |
March | 377.33 | 21.29 | 147.83 | 21.11 | 147.83 | 21.11 |
April | 298.00 | 21.54 | 82.50 | 22.66 | 40.00 | 21.17 |
May | 83.83 | 22.75 | 196.33 | 24.00 | 9.50 | 24.13 |
June | 67.67 | 23.79 | 301.33 | 24.08 | 44.67 | 24.29 |
July | 78.50 | 24.26 | 367.00 | 24.08 | 78.50 | 24.26 |
August | 89.17 | 24.11 | 367.83 | 24.06 | 88.50 | 24.12 |
September | 91.50 | 22.59 | 194.67 | 24.07 | 1.50 | 25.56 |
October | 313.33 | 21.78 | 19.33 | 23.10 | 5.67 | 21.11 |
November | 334.17 | 21.44 | 122.50 | 21.11 | 122.50 | 21.11 |
December | 369.00 | 21.11 | 291.50 | 21.11 | 291.50 | 21.11 |
Annual Sum or Average | 2809.50 | 21.64 | 2648.83 | 22.76 | 1388.17 | 21.61 |
Minimum of Months | 67.67 | 21.11 | 19.33 | 21.11 | 1.50 | 21.11 |
Maximum of Months | 377.33 | 24.26 | 367.83 | 24.08 | 344.33 | 25.56 |
Report: ComfortReportSimple55Monthly
For: SMSTORE3
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 371.00 | 21.11 | 347.17 | 21.11 | 347.17 | 21.11 |
February | 336.00 | 21.11 | 229.00 | 21.11 | 229.00 | 21.11 |
March | 379.00 | 21.28 | 162.50 | 21.11 | 162.50 | 21.11 |
April | 301.50 | 21.53 | 91.67 | 22.49 | 49.83 | 21.16 |
May | 90.17 | 22.74 | 190.83 | 24.00 | 10.00 | 23.93 |
June | 72.17 | 23.73 | 299.50 | 24.08 | 44.83 | 24.30 |
July | 77.83 | 24.26 | 367.00 | 24.08 | 77.83 | 24.26 |
August | 89.33 | 24.11 | 368.50 | 24.06 | 88.67 | 24.12 |
September | 94.67 | 22.51 | 193.83 | 24.07 | 1.83 | 24.75 |
October | 324.50 | 21.74 | 17.67 | 22.63 | 8.17 | 21.11 |
November | 342.83 | 21.44 | 133.67 | 21.11 | 133.67 | 21.11 |
December | 369.00 | 21.11 | 311.17 | 21.11 | 311.17 | 21.11 |
Annual Sum or Average | 2848.00 | 21.63 | 2712.50 | 22.71 | 1464.67 | 21.58 |
Minimum of Months | 72.17 | 21.11 | 17.67 | 21.11 | 1.83 | 21.11 |
Maximum of Months | 379.00 | 24.26 | 368.50 | 24.08 | 347.17 | 24.75 |
Report: ComfortReportSimple55Monthly
For: SMSTORE4
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 371.00 | 21.11 | 349.50 | 21.11 | 349.50 | 21.11 |
February | 336.00 | 21.11 | 247.17 | 21.11 | 247.17 | 21.11 |
March | 379.00 | 21.25 | 174.83 | 21.11 | 174.83 | 21.11 |
April | 307.67 | 21.52 | 99.67 | 22.34 | 59.17 | 21.15 |
May | 106.67 | 22.75 | 177.67 | 23.98 | 11.00 | 23.74 |
June | 83.33 | 23.60 | 294.33 | 24.08 | 47.17 | 24.26 |
July | 81.83 | 24.22 | 366.50 | 24.08 | 81.83 | 24.22 |
August | 91.67 | 24.09 | 367.00 | 24.05 | 90.83 | 24.09 |
September | 101.33 | 22.39 | 190.00 | 24.05 | 2.50 | 23.77 |
October | 332.33 | 21.67 | 17.33 | 21.92 | 12.33 | 21.11 |
November | 353.33 | 21.44 | 146.83 | 21.11 | 146.83 | 21.11 |
December | 369.00 | 21.11 | 333.50 | 21.11 | 333.50 | 21.11 |
Annual Sum or Average | 2913.17 | 21.63 | 2764.33 | 22.65 | 1556.67 | 21.57 |
Minimum of Months | 81.83 | 21.11 | 17.33 | 21.11 | 2.50 | 21.11 |
Maximum of Months | 379.00 | 24.22 | 367.00 | 24.08 | 349.50 | 24.26 |
Report: ComfortReportSimple55Monthly
For: LGSTORE2
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.11 | 328.33 | 21.11 | 328.33 | 21.11 |
February | 308.00 | 21.11 | 272.33 | 21.11 | 272.33 | 21.11 |
March | 348.00 | 21.20 | 210.00 | 21.11 | 210.00 | 21.11 |
April | 285.50 | 21.44 | 108.67 | 21.99 | 77.17 | 21.17 |
May | 149.17 | 22.78 | 133.33 | 23.88 | 11.50 | 23.52 |
June | 95.83 | 23.22 | 260.83 | 23.96 | 41.33 | 24.14 |
July | 80.17 | 24.01 | 336.50 | 23.96 | 80.17 | 24.01 |
August | 89.17 | 23.94 | 336.17 | 23.94 | 89.00 | 23.94 |
September | 100.17 | 22.05 | 163.00 | 23.96 | 2.17 | 22.18 |
October | 324.00 | 21.57 | 13.00 | 21.11 | 13.00 | 21.11 |
November | 330.00 | 21.30 | 175.50 | 21.11 | 175.50 | 21.11 |
December | 338.00 | 21.11 | 327.00 | 21.11 | 327.00 | 21.11 |
Annual Sum or Average | 2788.00 | 21.60 | 2664.67 | 22.45 | 1627.50 | 21.51 |
Minimum of Months | 80.17 | 21.11 | 13.00 | 21.11 | 2.17 | 21.11 |
Maximum of Months | 348.00 | 24.01 | 336.50 | 23.96 | 328.33 | 24.14 |
Report: ComfortReportSimple55Monthly
For: SMSTORE5
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.11 | 328.17 | 21.11 | 328.17 | 21.11 |
February | 308.00 | 21.11 | 273.17 | 21.11 | 273.17 | 21.11 |
March | 348.00 | 21.20 | 213.33 | 21.11 | 213.33 | 21.11 |
April | 286.50 | 21.44 | 108.67 | 21.88 | 81.83 | 21.17 |
May | 161.17 | 22.82 | 122.50 | 23.87 | 12.33 | 23.39 |
June | 98.83 | 23.18 | 252.83 | 23.96 | 41.50 | 24.09 |
July | 81.83 | 23.99 | 334.67 | 23.96 | 81.83 | 23.99 |
August | 90.67 | 23.94 | 331.17 | 23.94 | 90.33 | 23.94 |
September | 103.50 | 22.10 | 156.00 | 23.95 | 2.50 | 22.04 |
October | 326.67 | 21.58 | 16.33 | 21.11 | 16.33 | 21.11 |
November | 330.00 | 21.29 | 181.33 | 21.11 | 181.33 | 21.11 |
December | 338.00 | 21.11 | 327.33 | 21.11 | 327.33 | 21.11 |
Annual Sum or Average | 2813.17 | 21.61 | 2645.50 | 22.42 | 1650.00 | 21.50 |
Minimum of Months | 81.83 | 21.11 | 16.33 | 21.11 | 2.50 | 21.11 |
Maximum of Months | 348.00 | 23.99 | 334.67 | 23.96 | 328.17 | 24.09 |
Report: ComfortReportSimple55Monthly
For: SMSTORE6
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.11 | 329.17 | 21.11 | 329.17 | 21.11 |
February | 308.00 | 21.11 | 274.33 | 21.11 | 274.33 | 21.11 |
March | 348.00 | 21.19 | 216.33 | 21.11 | 216.33 | 21.11 |
April | 287.17 | 21.42 | 110.67 | 21.84 | 84.83 | 21.15 |
May | 170.17 | 22.78 | 118.33 | 23.85 | 13.17 | 23.28 |
June | 102.00 | 23.13 | 248.50 | 23.96 | 41.50 | 24.09 |
July | 82.50 | 23.98 | 333.67 | 23.96 | 82.50 | 23.98 |
August | 91.50 | 23.94 | 329.83 | 23.94 | 91.00 | 23.94 |
September | 108.50 | 22.12 | 154.50 | 23.95 | 2.83 | 22.09 |
October | 328.83 | 21.57 | 18.50 | 21.11 | 18.50 | 21.11 |
November | 330.00 | 21.27 | 184.50 | 21.11 | 184.50 | 21.11 |
December | 338.00 | 21.11 | 327.50 | 21.11 | 327.50 | 21.11 |
Annual Sum or Average | 2834.67 | 21.61 | 2645.83 | 22.41 | 1666.17 | 21.50 |
Minimum of Months | 82.50 | 21.11 | 18.50 | 21.11 | 2.83 | 21.11 |
Maximum of Months | 348.00 | 23.98 | 333.67 | 23.96 | 329.17 | 24.09 |
Report: ComfortReportSimple55Monthly
For: SMSTORE7
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.11 | 332.33 | 21.11 | 332.33 | 21.11 |
February | 308.00 | 21.11 | 281.33 | 21.11 | 281.33 | 21.11 |
March | 348.00 | 21.18 | 230.50 | 21.11 | 230.50 | 21.11 |
April | 290.17 | 21.40 | 125.33 | 21.73 | 100.33 | 21.15 |
May | 194.00 | 22.67 | 104.67 | 23.81 | 14.50 | 23.13 |
June | 106.33 | 23.02 | 239.67 | 23.97 | 42.50 | 24.08 |
July | 84.33 | 23.98 | 332.67 | 23.96 | 84.33 | 23.98 |
August | 94.33 | 23.93 | 327.50 | 23.94 | 93.33 | 23.93 |
September | 114.83 | 22.09 | 152.17 | 23.94 | 3.33 | 21.94 |
October | 333.50 | 21.54 | 23.50 | 21.11 | 23.50 | 21.11 |
November | 330.00 | 21.24 | 198.83 | 21.11 | 198.83 | 21.11 |
December | 338.00 | 21.11 | 329.00 | 21.11 | 329.00 | 21.11 |
Annual Sum or Average | 2881.50 | 21.60 | 2677.50 | 22.36 | 1733.83 | 21.49 |
Minimum of Months | 84.33 | 21.11 | 23.50 | 21.11 | 3.33 | 21.11 |
Maximum of Months | 348.00 | 23.98 | 332.67 | 23.97 | 332.33 | 24.08 |
Report: ComfortReportSimple55Monthly
For: SMSTORE8
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.11 | 340.00 | 21.11 | 340.00 | 21.11 |
February | 308.00 | 21.11 | 298.33 | 21.11 | 298.33 | 21.11 |
March | 348.00 | 21.14 | 275.17 | 21.11 | 275.17 | 21.11 |
April | 299.83 | 21.37 | 206.67 | 21.42 | 187.00 | 21.14 |
May | 253.50 | 22.49 | 71.17 | 23.50 | 23.83 | 22.64 |
June | 118.50 | 22.83 | 213.83 | 23.97 | 46.83 | 24.06 |
July | 89.50 | 23.97 | 327.17 | 23.96 | 89.00 | 23.97 |
August | 101.50 | 23.92 | 315.67 | 23.94 | 96.67 | 23.93 |
September | 129.33 | 22.02 | 149.50 | 23.90 | 5.83 | 21.67 |
October | 337.67 | 21.49 | 49.00 | 21.11 | 49.00 | 21.11 |
November | 330.00 | 21.19 | 224.17 | 21.11 | 224.17 | 21.11 |
December | 338.00 | 21.11 | 338.00 | 21.11 | 338.00 | 21.11 |
Annual Sum or Average | 2993.83 | 21.60 | 2808.67 | 22.21 | 1973.83 | 21.47 |
Minimum of Months | 89.50 | 21.11 | 49.00 | 21.11 | 5.83 | 21.11 |
Maximum of Months | 348.00 | 23.97 | 340.00 | 23.97 | 340.00 | 24.06 |
Report: OccupantComfortDataSummaryMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 496.00000 | 21.01492 | 10.05009 | -0.7303 | 16.71794 |
February | 448.00000 | 21.02912 | 14.56664 | -0.6527 | 14.56765 |
March | 496.00000 | 21.23219 | 21.03194 | -0.5016 | 11.45125 |
April | 480.00000 | 21.88341 | 29.19594 | -0.2309 | 9.30451 |
May | 496.00000 | 23.51215 | 42.42571 | -0.6063 | 14.92754 |
June | 480.00000 | 23.77611 | 50.06621 | -0.3748 | 8.85946 |
July | 496.00000 | 23.89518 | 55.97463 | -0.2531 | 6.48062 |
August | 496.00000 | 23.89384 | 54.21976 | -0.2660 | 6.68371 |
September | 480.00000 | 23.49103 | 37.67265 | -0.5629 | 14.44660 |
October | 496.00000 | 22.04157 | 28.28600 | -0.1400 | 7.25642 |
November | 480.00000 | 21.52488 | 21.90071 | -0.3999 | 10.76397 |
December | 496.00000 | 21.02665 | 12.82439 | -0.6675 | 14.79746 |
Annual Sum or Average | 5840.00000 | 22.36764 | 31.62224 | -0.4478 | 11.33395 |
Minimum of Months | 448.00000 | 21.01492 | 10.05009 | -0.7303 | 6.48062 |
Maximum of Months | 496.00000 | 23.89518 | 55.97463 | -0.1400 | 16.71794 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 496.00000 | 21.13372 | 10.86088 | -0.6392 | 14.03135 |
February | 448.00000 | 21.26505 | 15.30197 | -0.5429 | 11.89012 |
March | 496.00000 | 21.65845 | 21.33741 | -0.3620 | 9.24582 |
April | 480.00000 | 22.36288 | 29.01007 | -0.0950 | 7.93818 |
May | 496.00000 | 23.68401 | 41.64991 | -0.5243 | 12.12865 |
June | 480.00000 | 23.80381 | 48.28379 | -0.3632 | 8.27297 |
July | 496.00000 | 23.82544 | 53.48236 | -0.2873 | 6.95352 |
August | 496.00000 | 23.82959 | 52.17259 | -0.2987 | 7.13818 |
September | 480.00000 | 23.64740 | 36.71316 | -0.5173 | 12.02309 |
October | 496.00000 | 22.69148 | 27.95005 | 0.00526 | 6.54307 |
November | 480.00000 | 21.91985 | 22.04281 | -0.2824 | 9.26320 |
December | 496.00000 | 21.25803 | 13.64031 | -0.5617 | 12.12528 |
Annual Sum or Average | 5840.00000 | 22.59710 | 31.13383 | -0.3716 | 9.78353 |
Minimum of Months | 448.00000 | 21.13372 | 10.86088 | -0.6392 | 6.54307 |
Maximum of Months | 496.00000 | 23.82959 | 53.48236 | 0.00526 | 14.03135 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 21.10997 | 9.45322 | -0.6833 | 15.04686 |
February | 336.00000 | 21.10992 | 14.12444 | -0.6036 | 13.01454 |
March | 379.00000 | 21.30319 | 20.19310 | -0.4554 | 10.23935 |
April | 360.00000 | 21.95750 | 28.63309 | -0.1869 | 8.80481 |
May | 375.00000 | 23.65486 | 41.96431 | -0.5405 | 13.18867 |
June | 366.00000 | 23.92766 | 49.09859 | -0.3232 | 8.20476 |
July | 369.00000 | 24.03764 | 54.72689 | -0.2153 | 6.36986 |
August | 379.00000 | 24.01698 | 52.90515 | -0.2368 | 6.54548 |
September | 360.00000 | 23.62572 | 36.84495 | -0.5228 | 13.25695 |
October | 371.00000 | 22.10744 | 28.06981 | -0.1168 | 6.96228 |
November | 360.00000 | 21.61011 | 21.99085 | -0.3613 | 10.01302 |
December | 369.00000 | 21.10986 | 12.25269 | -0.6257 | 13.45016 |
Annual Sum or Average | 4395.00000 | 22.47555 | 31.00843 | -0.4047 | 10.40021 |
Minimum of Months | 336.00000 | 21.10986 | 9.45322 | -0.6833 | 6.36986 |
Maximum of Months | 379.00000 | 24.03764 | 54.72689 | -0.1168 | 15.04686 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 21.10983 | 9.45357 | -0.6954 | 15.39242 |
February | 336.00000 | 21.10958 | 14.12490 | -0.6155 | 13.31081 |
March | 379.00000 | 21.27925 | 20.23798 | -0.4719 | 10.49932 |
April | 360.00000 | 21.92434 | 28.70869 | -0.2034 | 8.94321 |
May | 375.00000 | 23.63107 | 42.03286 | -0.5554 | 13.65430 |
June | 366.00000 | 23.91545 | 49.13573 | -0.3287 | 8.36423 |
July | 369.00000 | 24.03741 | 54.71795 | -0.2150 | 6.36794 |
August | 379.00000 | 24.01660 | 52.91327 | -0.2369 | 6.54461 |
September | 360.00000 | 23.59294 | 36.90039 | -0.5359 | 13.80029 |
October | 371.00000 | 22.01104 | 28.25371 | -0.1480 | 7.07097 |
November | 360.00000 | 21.55762 | 22.11281 | -0.3847 | 10.19815 |
December | 369.00000 | 21.10981 | 12.25270 | -0.6378 | 13.76765 |
Annual Sum or Average | 4395.00000 | 22.45251 | 31.05751 | -0.4178 | 10.63406 |
Minimum of Months | 336.00000 | 21.10958 | 9.45357 | -0.6954 | 6.36794 |
Maximum of Months | 379.00000 | 24.03741 | 54.71795 | -0.1480 | 15.39242 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 21.10997 | 9.45351 | -0.7095 | 15.81148 |
February | 336.00000 | 21.10992 | 14.12415 | -0.6303 | 13.69856 |
March | 379.00000 | 21.25194 | 20.28840 | -0.4925 | 10.85547 |
April | 360.00000 | 21.87737 | 28.82439 | -0.2259 | 9.11103 |
May | 375.00000 | 23.57842 | 42.19435 | -0.5855 | 14.53212 |
June | 366.00000 | 23.87933 | 49.36057 | -0.3481 | 8.83071 |
July | 369.00000 | 24.03440 | 54.90257 | -0.2219 | 6.42316 |
August | 379.00000 | 24.01336 | 53.09263 | -0.2441 | 6.61278 |
September | 360.00000 | 23.53330 | 37.04867 | -0.5631 | 14.79393 |
October | 371.00000 | 21.89671 | 28.47408 | -0.1841 | 7.22126 |
November | 360.00000 | 21.48058 | 22.29450 | -0.4157 | 10.44290 |
December | 369.00000 | 21.10980 | 12.25245 | -0.6531 | 14.18603 |
Annual Sum or Average | 4395.00000 | 22.41747 | 31.18035 | -0.4382 | 11.01705 |
Minimum of Months | 336.00000 | 21.10980 | 9.45351 | -0.7095 | 6.42316 |
Maximum of Months | 379.00000 | 24.03440 | 54.90257 | -0.1841 | 15.81148 |
Report: OccupantComfortDataSummaryMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.10989 | 10.08192 | -0.7608 | 17.37387 |
February | 308.00000 | 21.10995 | 14.78863 | -0.6820 | 15.09325 |
March | 348.00000 | 21.20004 | 21.08735 | -0.5492 | 11.95720 |
April | 330.00000 | 21.77450 | 29.74136 | -0.2829 | 9.63377 |
May | 344.00000 | 23.40541 | 43.32591 | -0.6722 | 16.94108 |
June | 336.00000 | 23.70486 | 50.35572 | -0.4185 | 10.39367 |
July | 338.00000 | 23.94724 | 55.74597 | -0.2604 | 6.65924 |
August | 348.00000 | 23.92522 | 54.07263 | -0.2818 | 6.88779 |
September | 330.00000 | 23.36203 | 37.76012 | -0.6352 | 17.20441 |
October | 340.00000 | 21.67373 | 29.61710 | -0.2574 | 7.62191 |
November | 330.00000 | 21.30268 | 23.36666 | -0.4965 | 11.46797 |
December | 338.00000 | 21.10995 | 12.89677 | -0.7078 | 15.72766 |
Annual Sum or Average | 4030.00000 | 22.31326 | 32.06442 | -0.4991 | 12.21666 |
Minimum of Months | 308.00000 | 21.10989 | 10.08192 | -0.7608 | 6.65924 |
Maximum of Months | 348.00000 | 23.94724 | 55.74597 | -0.2574 | 17.37387 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.10995 | 10.01425 | -0.7531 | 17.11707 |
February | 308.00000 | 21.10996 | 14.72112 | -0.6790 | 14.98720 |
March | 348.00000 | 21.19712 | 21.02692 | -0.5539 | 12.02035 |
April | 330.00000 | 21.76724 | 29.70815 | -0.2948 | 9.69121 |
May | 344.00000 | 23.38675 | 43.34513 | -0.7017 | 17.79740 |
June | 336.00000 | 23.69437 | 50.46557 | -0.4488 | 10.98270 |
July | 338.00000 | 23.94739 | 55.93084 | -0.2878 | 6.96550 |
August | 348.00000 | 23.92540 | 54.24250 | -0.3090 | 7.21843 |
September | 330.00000 | 23.35996 | 37.75089 | -0.6612 | 17.84654 |
October | 340.00000 | 21.66379 | 29.56968 | -0.2731 | 7.77117 |
November | 330.00000 | 21.29225 | 23.32049 | -0.5036 | 11.50386 |
December | 338.00000 | 21.10996 | 12.82700 | -0.7027 | 15.56499 |
Annual Sum or Average | 4030.00000 | 22.30812 | 32.07219 | -0.5129 | 12.42796 |
Minimum of Months | 308.00000 | 21.10995 | 10.01425 | -0.7531 | 6.96550 |
Maximum of Months | 348.00000 | 23.94739 | 55.93084 | -0.2731 | 17.84654 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.10995 | 10.01421 | -0.7549 | 17.17365 |
February | 308.00000 | 21.10996 | 14.72122 | -0.6821 | 15.07374 |
March | 348.00000 | 21.19147 | 21.03768 | -0.5598 | 12.13580 |
April | 330.00000 | 21.75146 | 29.75256 | -0.3041 | 9.77616 |
May | 344.00000 | 23.33756 | 43.48357 | -0.7268 | 18.63536 |
June | 336.00000 | 23.67499 | 50.57064 | -0.4608 | 11.34148 |
July | 338.00000 | 23.94685 | 56.00201 | -0.2924 | 7.02119 |
August | 348.00000 | 23.92497 | 54.30357 | -0.3135 | 7.27821 |
September | 330.00000 | 23.34089 | 37.80343 | -0.6725 | 18.25096 |
October | 340.00000 | 21.63847 | 29.62402 | -0.2835 | 7.85761 |
November | 330.00000 | 21.27393 | 23.36401 | -0.5119 | 11.61490 |
December | 338.00000 | 21.10996 | 12.82708 | -0.7056 | 15.64727 |
Annual Sum or Average | 4030.00000 | 22.29525 | 32.12104 | -0.5212 | 12.62395 |
Minimum of Months | 308.00000 | 21.10995 | 10.01421 | -0.7549 | 7.02119 |
Maximum of Months | 348.00000 | 23.94685 | 56.00201 | -0.2835 | 18.63536 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.10995 | 10.01413 | -0.7637 | 17.45077 |
February | 308.00000 | 21.10984 | 14.72096 | -0.6943 | 15.41817 |
March | 348.00000 | 21.17566 | 21.06741 | -0.5788 | 12.53884 |
April | 330.00000 | 21.70742 | 29.87245 | -0.3311 | 10.08130 |
May | 344.00000 | 23.19664 | 43.89223 | -0.7921 | 20.95529 |
June | 336.00000 | 23.62856 | 50.83816 | -0.4856 | 12.17340 |
July | 338.00000 | 23.94560 | 56.17831 | -0.2992 | 7.10933 |
August | 348.00000 | 23.92385 | 54.45250 | -0.3198 | 7.36918 |
September | 330.00000 | 23.29320 | 37.94304 | -0.6965 | 19.18158 |
October | 340.00000 | 21.58564 | 29.73605 | -0.3061 | 8.07774 |
November | 330.00000 | 21.23994 | 23.44458 | -0.5311 | 11.93774 |
December | 338.00000 | 21.10996 | 12.82672 | -0.7169 | 15.98392 |
Annual Sum or Average | 4030.00000 | 22.26302 | 32.24569 | -0.5419 | 13.16553 |
Minimum of Months | 308.00000 | 21.10984 | 10.01413 | -0.7921 | 7.10933 |
Maximum of Months | 348.00000 | 23.94560 | 56.17831 | -0.2992 | 20.95529 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.10997 | 9.84267 | -0.8253 | 19.54361 |
February | 308.00000 | 21.10997 | 14.58058 | -0.7617 | 17.51448 |
March | 348.00000 | 21.14157 | 20.95962 | -0.6567 | 14.49107 |
April | 330.00000 | 21.60459 | 29.98906 | -0.4239 | 11.55701 |
May | 344.00000 | 22.84273 | 44.74093 | -0.9665 | 27.77883 |
June | 336.00000 | 23.52959 | 51.35500 | -0.5505 | 14.47614 |
July | 338.00000 | 23.94168 | 56.59764 | -0.3171 | 7.38116 |
August | 348.00000 | 23.92069 | 54.76229 | -0.3333 | 7.60723 |
September | 330.00000 | 23.18600 | 38.13324 | -0.7522 | 21.54854 |
October | 340.00000 | 21.50373 | 29.76182 | -0.3624 | 8.84305 |
November | 330.00000 | 21.19394 | 23.48369 | -0.5900 | 13.27723 |
December | 338.00000 | 21.10997 | 12.69582 | -0.7758 | 17.85779 |
Annual Sum or Average | 4030.00000 | 22.19315 | 32.40816 | -0.6086 | 15.13477 |
Minimum of Months | 308.00000 | 21.10997 | 9.84267 | -0.9665 | 7.38116 |
Maximum of Months | 348.00000 | 23.94168 | 56.59764 | -0.3171 | 27.77883 |
Report: DXReportMonthly
For: PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 |
March | 2653.61 | 867.49 | 3.87 | 2060.08 | 593.53 | 0.00 | 0.00 | 19-MAR-19:10 | 0.00 | 01-MAR-00:02 | 0.51 | 19-MAR-19:10 | 0.40 | 19-MAR-19:10 | 0.11 | 19-MAR-19:10 | 0.17 | 19-MAR-19:10 | 0.00 | 01-MAR-00:02 |
April | 0.244429E+10 | 0.768018E+09 | 65.33 | 0.173428E+10 | 0.710008E+09 | 0.00 | 0.55 | 16-APR-16:04 | 0.00 | 01-APR-00:05 | 25267.47 | 16-APR-16:10 | 18391.39 | 16-APR-16:04 | 7575.95 | 18-APR-12:40 | 7947.84 | 16-APR-16:10 | 0.00 | 01-APR-00:05 |
May | 0.414303E+10 | 0.129364E+10 | 211.63 | 0.292782E+10 | 0.121520E+10 | 0.00 | 0.55 | 31-MAY-15:00 | 0.00 | 01-MAY-00:10 | 24509.81 | 31-MAY-15:00 | 19653.34 | 31-MAY-15:00 | 9150.01 | 29-MAY-14:00 | 7974.72 | 31-MAY-15:00 | 0.00 | 01-MAY-00:10 |
June | 0.182338E+11 | 0.564789E+10 | 356.97 | 0.125870E+11 | 0.564680E+10 | 0.00 | 1.00 | 26-JUN-07:02 | 0.00 | 01-JUN-00:10 | 57605.93 | 26-JUN-07:02 | 31549.49 | 26-JUN-07:02 | 27875.92 | 30-JUN-07:02 | 14029.42 | 27-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.249054E+11 | 0.751971E+10 | 452.68 | 0.160149E+11 | 0.889051E+10 | 0.00 | 1.00 | 02-JUL-07:02 | 0.00 | 01-JUL-00:03 | 56983.53 | 07-JUL-07:02 | 30841.99 | 28-JUL-07:02 | 31582.76 | 07-JUL-07:02 | 13717.97 | 26-JUL-07:02 | 0.00 | 01-JUL-00:03 |
August | 0.220703E+11 | 0.669449E+10 | 436.85 | 0.145291E+11 | 0.754120E+10 | 0.00 | 1.00 | 03-AUG-07:02 | 0.00 | 01-AUG-00:10 | 59063.10 | 03-AUG-07:02 | 28707.02 | 04-AUG-07:02 | 30937.35 | 03-AUG-07:03 | 14102.38 | 03-AUG-07:02 | 0.00 | 01-AUG-00:10 |
September | 0.103123E+11 | 0.325259E+10 | 282.65 | 0.833262E+10 | 0.197967E+10 | 0.00 | 0.91 | 11-SEP-07:03 | 0.00 | 01-SEP-00:10 | 48860.68 | 11-SEP-07:03 | 27154.25 | 11-SEP-07:03 | 21706.43 | 11-SEP-07:03 | 12208.99 | 11-SEP-07:03 | 0.00 | 01-SEP-00:10 |
October | 97898129.47 | 31336071.59 | 49.38 | 91383200.66 | 6514928.80 | 0.00 | 0.22 | 20-OCT-15:00 | 0.00 | 01-OCT-00:10 | 8703.54 | 20-OCT-15:00 | 8394.21 | 20-OCT-15:00 | 680.38 | 21-OCT-15:00 | 2785.77 | 20-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 13705.59 | 4467.64 | 7.08 | 12221.43 | 1484.16 | 0.00 | 0.00 | 03-NOV-14:40 | 0.00 | 01-NOV-00:10 | 1.48 | 03-NOV-14:40 | 1.37 | 03-NOV-14:50 | 0.16 | 03-NOV-14:00 | 0.48 | 03-NOV-14:40 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.822070E+11 | 0.252077E+11 | 1866.44 | 0.562171E+11 | 0.259899E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.249054E+11 | 0.751971E+10 | 452.68 | 0.160149E+11 | 0.889051E+10 | 0.00 | 1.00 | 0.00 | 59063.10 | 31549.49 | 31582.76 | 14102.38 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 |
March | 1843623.78 | 600844.20 | 1.83 | 1675260.65 | 168363.13 | 0.00 | 0.09 | 25-MAR-21:40 | 0.00 | 01-MAR-00:02 | 1628.95 | 25-MAR-21:40 | 1505.89 | 25-MAR-21:40 | 138.38 | 19-MAR-22:10 | 527.60 | 25-MAR-21:40 | 0.00 | 01-MAR-00:02 |
April | 0.150719E+10 | 0.433034E+09 | 66.61 | 0.109030E+10 | 0.416894E+09 | 0.00 | 1.00 | 14-APR-20:15 | 0.00 | 01-APR-00:05 | 27663.30 | 16-APR-19:37 | 24963.87 | 19-APR-20:02 | 10513.90 | 16-APR-21:53 | 6560.20 | 16-APR-19:37 | 0.00 | 01-APR-00:05 |
May | 0.292692E+10 | 0.819610E+09 | 177.07 | 0.206851E+10 | 0.858412E+09 | 0.00 | 1.00 | 06-MAY-18:15 | 0.00 | 01-MAY-00:10 | 27984.44 | 29-MAY-17:01 | 24963.87 | 20-MAY-20:52 | 12452.92 | 29-MAY-19:57 | 6478.22 | 31-MAY-20:11 | 0.00 | 01-MAY-00:10 |
June | 0.106565E+11 | 0.303085E+10 | 325.24 | 0.744283E+10 | 0.321367E+10 | 0.00 | 1.00 | 08-JUN-20:01 | 0.00 | 01-JUN-00:10 | 28870.11 | 27-JUN-07:02 | 21820.40 | 23-JUN-22:11 | 14080.59 | 11-JUN-22:42 | 6697.69 | 27-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.148254E+11 | 0.407257E+10 | 388.48 | 0.961314E+10 | 0.521229E+10 | 0.00 | 1.00 | 01-JUL-19:12 | 0.00 | 01-JUL-00:03 | 28842.78 | 17-JUL-20:02 | 22078.06 | 23-JUL-18:57 | 15795.18 | 20-JUL-07:03 | 6643.38 | 16-JUL-19:08 | 0.00 | 01-JUL-00:03 |
August | 0.133304E+11 | 0.369326E+10 | 376.10 | 0.879513E+10 | 0.453526E+10 | 0.00 | 1.00 | 01-AUG-20:02 | 0.00 | 01-AUG-00:10 | 29271.26 | 03-AUG-07:02 | 22168.35 | 06-AUG-17:01 | 15894.99 | 28-AUG-20:02 | 6726.67 | 03-AUG-07:02 | 0.00 | 01-AUG-00:10 |
September | 0.627751E+10 | 0.178202E+10 | 239.66 | 0.504622E+10 | 0.123130E+10 | 0.00 | 1.00 | 01-SEP-20:01 | 0.00 | 01-SEP-00:10 | 27800.88 | 11-SEP-22:54 | 24963.87 | 24-SEP-17:01 | 13303.31 | 11-SEP-20:01 | 6441.17 | 10-SEP-18:21 | 0.00 | 01-SEP-00:10 |
October | 87171763.36 | 26189409.31 | 47.35 | 81641387.45 | 5530375.91 | 0.00 | 1.00 | 11-OCT-20:29 | 0.00 | 01-OCT-00:10 | 24963.87 | 11-OCT-20:29 | 24634.33 | 11-OCT-20:29 | 515.07 | 21-OCT-15:00 | 5737.82 | 11-OCT-20:29 | 0.00 | 01-OCT-00:10 |
November | 4059221.26 | 1308136.55 | 16.94 | 3779702.74 | 279518.52 | 0.00 | 0.14 | 03-NOV-20:40 | 0.00 | 01-NOV-00:10 | 2482.39 | 03-NOV-20:40 | 2482.39 | 03-NOV-20:40 | 266.53 | 06-NOV-23:10 | 790.25 | 03-NOV-20:40 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.496170E+11 | 0.138594E+11 | 1639.30 | 0.341432E+11 | 0.154738E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.148254E+11 | 0.407257E+10 | 388.48 | 0.961314E+10 | 0.521229E+10 | 0.00 | 1.00 | 0.00 | 29271.26 | 24963.87 | 15894.99 | 6726.67 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 |
April | 0.104598E+10 | 0.307004E+09 | 49.78 | 0.746860E+09 | 0.299118E+09 | 0.00 | 0.57 | 18-APR-14:00 | 0.00 | 01-APR-00:05 | 13568.03 | 18-APR-14:00 | 9817.43 | 15-APR-15:00 | 4058.64 | 18-APR-12:40 | 3955.18 | 18-APR-14:00 | 0.00 | 01-APR-00:05 |
May | 0.204385E+10 | 0.599463E+09 | 154.96 | 0.147481E+10 | 0.569045E+09 | 0.00 | 0.57 | 31-MAY-13:00 | 0.00 | 01-MAY-00:10 | 13320.33 | 31-MAY-13:00 | 10639.99 | 31-MAY-13:00 | 4917.47 | 29-MAY-14:00 | 4047.57 | 31-MAY-13:00 | 0.00 | 01-MAY-00:10 |
June | 0.800191E+10 | 0.231602E+10 | 272.97 | 0.557421E+10 | 0.242770E+10 | 0.00 | 1.00 | 11-JUN-07:03 | 0.00 | 01-JUN-00:10 | 29433.93 | 26-JUN-06:02 | 15631.61 | 28-JUN-06:02 | 15652.63 | 26-JUN-06:02 | 6663.79 | 26-JUN-06:02 | 0.00 | 01-JUN-00:10 |
July | 0.107642E+11 | 0.304675E+10 | 328.33 | 0.708810E+10 | 0.367608E+10 | 0.00 | 1.00 | 01-JUL-06:02 | 0.00 | 01-JUL-00:03 | 29065.03 | 27-JUL-06:02 | 15860.58 | 01-JUL-06:02 | 16444.41 | 20-JUL-06:03 | 6595.70 | 26-JUL-06:02 | 0.00 | 01-JUL-00:03 |
August | 0.104044E+11 | 0.296331E+10 | 326.02 | 0.699657E+10 | 0.340780E+10 | 0.00 | 1.00 | 03-AUG-06:02 | 0.00 | 01-AUG-00:10 | 30248.18 | 04-AUG-06:02 | 15377.59 | 03-AUG-06:02 | 15473.63 | 04-AUG-06:03 | 6749.13 | 03-AUG-06:02 | 0.00 | 01-AUG-00:10 |
September | 0.458596E+10 | 0.136108E+10 | 209.21 | 0.378440E+10 | 0.801560E+09 | 0.00 | 1.00 | 08-SEP-06:02 | 0.00 | 01-SEP-00:10 | 27818.05 | 11-SEP-06:02 | 15928.14 | 11-SEP-06:02 | 12856.29 | 12-SEP-06:02 | 6390.64 | 11-SEP-06:02 | 0.00 | 01-SEP-00:10 |
October | 60916158.75 | 18290851.41 | 30.50 | 56995824.90 | 3920333.85 | 0.00 | 0.24 | 20-OCT-15:00 | 0.00 | 01-OCT-00:10 | 4910.14 | 20-OCT-15:00 | 4772.27 | 20-OCT-15:00 | 425.96 | 21-OCT-15:00 | 1473.49 | 20-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 10158.80 | 3121.47 | 9.92 | 9148.30 | 1010.50 | 0.00 | 0.00 | 03-NOV-14:40 | 0.00 | 01-NOV-00:10 | 0.84 | 03-NOV-14:30 | 0.78 | 03-NOV-14:40 | 0.09 | 03-NOV-12:00 | 0.26 | 03-NOV-14:30 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.369072E+11 | 0.106119E+11 | 1381.68 | 0.257220E+11 | 0.111852E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.107642E+11 | 0.304675E+10 | 328.33 | 0.708810E+10 | 0.367608E+10 | 0.00 | 1.00 | 0.00 | 30248.18 | 15928.14 | 16444.41 | 6749.13 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 |
April | 0.102686E+10 | 0.301802E+09 | 49.07 | 0.732349E+09 | 0.294510E+09 | 0.00 | 0.57 | 18-APR-14:00 | 0.00 | 01-APR-00:05 | 13510.15 | 18-APR-14:00 | 9652.70 | 15-APR-15:00 | 4044.05 | 18-APR-12:40 | 3941.49 | 18-APR-14:00 | 0.00 | 01-APR-00:05 |
May | 0.199690E+10 | 0.586387E+09 | 151.91 | 0.144089E+10 | 0.556012E+09 | 0.00 | 0.57 | 31-MAY-13:00 | 0.00 | 01-MAY-00:10 | 13293.28 | 31-MAY-13:00 | 10618.16 | 31-MAY-13:00 | 4859.53 | 29-MAY-14:00 | 4041.51 | 31-MAY-13:00 | 0.00 | 01-MAY-00:10 |
June | 0.799552E+10 | 0.231456E+10 | 269.82 | 0.557047E+10 | 0.242505E+10 | 0.00 | 1.00 | 11-JUN-07:03 | 0.00 | 01-JUN-00:10 | 29489.32 | 26-JUN-06:02 | 15670.29 | 28-JUN-06:02 | 15666.61 | 26-JUN-06:02 | 6675.92 | 26-JUN-06:02 | 0.00 | 01-JUN-00:10 |
July | 0.107843E+11 | 0.305255E+10 | 328.46 | 0.710193E+10 | 0.368240E+10 | 0.00 | 1.00 | 01-JUL-06:02 | 0.00 | 01-JUL-00:03 | 29118.35 | 27-JUL-06:02 | 15898.78 | 01-JUL-06:02 | 16470.73 | 20-JUL-06:03 | 6607.61 | 26-JUL-06:02 | 0.00 | 01-JUL-00:03 |
August | 0.104004E+11 | 0.296287E+10 | 326.01 | 0.699489E+10 | 0.340547E+10 | 0.00 | 1.00 | 03-AUG-06:02 | 0.00 | 01-AUG-00:10 | 30305.86 | 04-AUG-06:02 | 15425.06 | 03-AUG-06:02 | 15485.88 | 04-AUG-06:03 | 6761.30 | 03-AUG-06:02 | 0.00 | 01-AUG-00:10 |
September | 0.457975E+10 | 0.135950E+10 | 208.45 | 0.377814E+10 | 0.801610E+09 | 0.00 | 1.00 | 08-SEP-06:02 | 0.00 | 01-SEP-00:10 | 27870.82 | 11-SEP-06:02 | 16220.36 | 10-SEP-07:03 | 12871.59 | 12-SEP-06:02 | 6402.59 | 11-SEP-06:02 | 0.00 | 01-SEP-00:10 |
October | 55281872.53 | 16641006.63 | 27.67 | 51886918.29 | 3394954.24 | 0.00 | 0.23 | 20-OCT-15:00 | 0.00 | 01-OCT-00:10 | 4694.49 | 20-OCT-15:00 | 4563.71 | 20-OCT-15:00 | 383.27 | 21-OCT-15:00 | 1412.67 | 20-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 7963.71 | 2447.15 | 7.67 | 7237.92 | 725.79 | 0.00 | 0.00 | 03-NOV-14:40 | 0.00 | 01-NOV-00:10 | 0.75 | 03-NOV-14:40 | 0.70 | 03-NOV-14:50 | 0.07 | 03-NOV-11:00 | 0.23 | 03-NOV-14:40 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.368390E+11 | 0.105943E+11 | 1369.06 | 0.256706E+11 | 0.111684E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.107843E+11 | 0.305255E+10 | 328.46 | 0.710193E+10 | 0.368240E+10 | 0.00 | 1.00 | 0.00 | 30305.86 | 16220.36 | 16470.73 | 6761.30 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 |
April | 0.978152E+09 | 0.288594E+09 | 45.74 | 0.695064E+09 | 0.283089E+09 | 0.00 | 0.55 | 18-APR-14:00 | 0.00 | 01-APR-00:05 | 13291.20 | 18-APR-14:00 | 9456.69 | 18-APR-14:00 | 3999.57 | 18-APR-12:40 | 3889.98 | 18-APR-14:00 | 0.00 | 01-APR-00:05 |
May | 0.188421E+10 | 0.555226E+09 | 143.64 | 0.135877E+10 | 0.525441E+09 | 0.00 | 0.56 | 31-MAY-13:00 | 0.00 | 01-MAY-00:10 | 13107.07 | 31-MAY-13:00 | 10448.78 | 31-MAY-13:00 | 4715.79 | 29-MAY-14:00 | 3996.94 | 31-MAY-13:00 | 0.00 | 01-MAY-00:10 |
June | 0.778395E+10 | 0.226009E+10 | 262.27 | 0.541528E+10 | 0.236867E+10 | 0.00 | 1.00 | 12-JUN-06:02 | 0.00 | 01-JUN-00:10 | 29714.45 | 26-JUN-06:02 | 15749.15 | 28-JUN-06:02 | 15818.92 | 26-JUN-06:02 | 6727.69 | 26-JUN-06:02 | 0.00 | 01-JUN-00:10 |
July | 0.105213E+11 | 0.298654E+10 | 326.12 | 0.692067E+10 | 0.360062E+10 | 0.00 | 1.00 | 02-JUL-07:02 | 0.00 | 01-JUL-00:03 | 29340.48 | 27-JUL-06:02 | 15701.79 | 02-JUL-07:02 | 16637.69 | 20-JUL-06:03 | 6658.50 | 26-JUL-06:02 | 0.00 | 01-JUL-00:03 |
August | 0.101310E+11 | 0.289477E+10 | 322.93 | 0.680750E+10 | 0.332350E+10 | 0.00 | 1.00 | 03-AUG-06:02 | 0.00 | 01-AUG-00:10 | 30524.57 | 04-AUG-06:02 | 15398.49 | 03-AUG-06:02 | 15729.68 | 04-AUG-06:03 | 6813.67 | 03-AUG-06:02 | 0.00 | 01-AUG-00:10 |
September | 0.446636E+10 | 0.132986E+10 | 204.52 | 0.368054E+10 | 0.785815E+09 | 0.00 | 1.00 | 08-SEP-06:02 | 0.00 | 01-SEP-00:10 | 28083.08 | 11-SEP-06:02 | 16065.23 | 11-SEP-06:02 | 13000.40 | 12-SEP-06:02 | 6451.67 | 11-SEP-06:02 | 0.00 | 01-SEP-00:10 |
October | 47031216.63 | 14214271.14 | 22.00 | 44367237.11 | 2663979.52 | 0.00 | 0.21 | 20-OCT-15:00 | 0.00 | 01-OCT-00:10 | 4375.39 | 20-OCT-15:00 | 4249.96 | 20-OCT-15:00 | 310.02 | 21-OCT-15:00 | 1322.40 | 20-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 4458.81 | 1370.86 | 3.17 | 4050.23 | 408.58 | 0.00 | 0.00 | 03-NOV-14:50 | 0.00 | 01-NOV-00:10 | 0.62 | 03-NOV-14:40 | 0.58 | 03-NOV-15:00 | 0.06 | 03-NOV-14:00 | 0.19 | 03-NOV-14:40 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.358120E+11 | 0.103293E+11 | 1330.39 | 0.249222E+11 | 0.108898E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.105213E+11 | 0.298654E+10 | 326.12 | 0.692067E+10 | 0.360062E+10 | 0.00 | 1.00 | 0.00 | 30524.57 | 16065.23 | 16637.69 | 6813.67 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 |
April | 0.156794E+10 | 0.495322E+09 | 40.81 | 0.108702E+10 | 0.480917E+09 | 0.00 | 0.52 | 18-APR-14:10 | 0.00 | 01-APR-00:05 | 23602.21 | 18-APR-14:10 | 16448.27 | 18-APR-14:10 | 7483.73 | 18-APR-12:40 | 7379.09 | 18-APR-14:10 | 0.00 | 01-APR-00:05 |
May | 0.297988E+10 | 0.941179E+09 | 129.76 | 0.212003E+10 | 0.859854E+09 | 0.00 | 0.54 | 31-MAY-15:00 | 0.00 | 01-MAY-00:10 | 23508.75 | 31-MAY-15:00 | 18580.97 | 31-MAY-15:00 | 7848.88 | 29-MAY-14:10 | 7658.16 | 31-MAY-15:00 | 0.00 | 01-MAY-00:10 |
June | 0.132087E+11 | 0.410705E+10 | 255.10 | 0.908148E+10 | 0.412727E+10 | 0.00 | 1.00 | 11-JUN-08:62 | 0.00 | 01-JUN-00:10 | 56497.99 | 26-JUN-07:02 | 31377.42 | 28-JUN-07:02 | 27617.64 | 12-JUN-07:03 | 13713.84 | 25-JUN-08:62 | 0.00 | 01-JUN-00:10 |
July | 0.181712E+11 | 0.551573E+10 | 322.26 | 0.117106E+11 | 0.646064E+10 | 0.00 | 1.00 | 02-JUL-08:62 | 0.00 | 01-JUL-00:03 | 55592.04 | 07-JUL-07:02 | 30748.87 | 02-JUL-08:62 | 31397.43 | 20-JUL-07:03 | 13685.32 | 02-JUL-08:62 | 0.00 | 01-JUL-00:03 |
August | 0.171737E+11 | 0.524907E+10 | 323.78 | 0.113382E+11 | 0.583548E+10 | 0.00 | 1.00 | 03-AUG-07:02 | 0.00 | 01-AUG-00:10 | 57229.47 | 04-AUG-07:02 | 28911.13 | 03-AUG-07:02 | 29563.43 | 28-AUG-07:03 | 13769.31 | 04-AUG-07:02 | 0.00 | 01-AUG-00:10 |
September | 0.764993E+10 | 0.243773E+10 | 191.65 | 0.619659E+10 | 0.145334E+10 | 0.00 | 1.00 | 11-SEP-07:03 | 0.00 | 01-SEP-00:10 | 53586.47 | 11-SEP-07:03 | 30191.84 | 11-SEP-07:03 | 23394.63 | 11-SEP-07:03 | 13025.47 | 11-SEP-07:03 | 0.00 | 01-SEP-00:10 |
October | 57325866.94 | 18547983.25 | 13.50 | 54086930.23 | 3238936.71 | 0.00 | 0.18 | 20-OCT-15:00 | 0.00 | 01-OCT-00:10 | 6885.53 | 20-OCT-15:00 | 6598.09 | 20-OCT-15:00 | 287.51 | 21-OCT-15:00 | 2227.27 | 20-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.608087E+11 | 0.187646E+11 | 1276.86 | 0.415880E+11 | 0.192207E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.181712E+11 | 0.551573E+10 | 323.78 | 0.117106E+11 | 0.646064E+10 | 0.00 | 1.00 | 0.00 | 57229.47 | 31377.42 | 31397.43 | 13769.31 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 |
April | 0.808594E+09 | 0.242150E+09 | 39.64 | 0.560525E+09 | 0.248068E+09 | 0.00 | 0.50 | 18-APR-14:10 | 0.00 | 01-APR-00:05 | 12364.65 | 18-APR-14:10 | 8615.52 | 18-APR-14:10 | 3902.78 | 18-APR-12:40 | 3667.91 | 18-APR-14:10 | 0.00 | 01-APR-00:05 |
May | 0.151442E+10 | 0.453237E+09 | 127.92 | 0.107955E+10 | 0.434870E+09 | 0.00 | 0.52 | 31-MAY-15:00 | 0.00 | 01-MAY-00:10 | 12347.04 | 31-MAY-15:00 | 9756.35 | 31-MAY-15:00 | 4075.01 | 29-MAY-13:50 | 3816.19 | 31-MAY-15:00 | 0.00 | 01-MAY-00:10 |
June | 0.682829E+10 | 0.201395E+10 | 253.39 | 0.469987E+10 | 0.212842E+10 | 0.00 | 1.00 | 25-JUN-08:62 | 0.00 | 01-JUN-00:10 | 31026.73 | 26-JUN-07:02 | 17240.57 | 28-JUN-07:02 | 14574.44 | 12-JUN-07:03 | 7101.27 | 25-JUN-08:62 | 0.00 | 01-JUN-00:10 |
July | 0.940532E+10 | 0.270741E+10 | 321.63 | 0.607262E+10 | 0.333270E+10 | 0.00 | 1.00 | 02-JUL-08:62 | 0.00 | 01-JUL-00:03 | 30535.63 | 07-JUL-07:02 | 16874.63 | 02-JUL-08:62 | 16801.78 | 07-JUL-07:02 | 7086.68 | 02-JUL-08:62 | 0.00 | 01-JUL-00:03 |
August | 0.886195E+10 | 0.256929E+10 | 320.43 | 0.586574E+10 | 0.299621E+10 | 0.00 | 1.00 | 03-AUG-07:02 | 0.00 | 01-AUG-00:10 | 31409.31 | 04-AUG-07:02 | 15833.61 | 03-AUG-07:02 | 15709.11 | 04-AUG-07:03 | 7129.40 | 04-AUG-07:02 | 0.00 | 01-AUG-00:10 |
September | 0.397047E+10 | 0.119969E+10 | 191.27 | 0.321895E+10 | 0.751525E+09 | 0.00 | 0.96 | 11-SEP-07:03 | 0.00 | 01-SEP-00:10 | 27696.92 | 11-SEP-07:03 | 15616.96 | 11-SEP-07:03 | 12079.95 | 11-SEP-07:03 | 6442.66 | 11-SEP-07:03 | 0.00 | 01-SEP-00:10 |
October | 27434799.25 | 8391401.30 | 12.33 | 25986116.03 | 1448683.22 | 0.00 | 0.17 | 20-OCT-15:00 | 0.00 | 01-OCT-00:10 | 3587.15 | 20-OCT-15:00 | 3440.30 | 20-OCT-15:00 | 146.86 | 20-OCT-15:00 | 1096.64 | 20-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.314165E+11 | 0.919411E+10 | 1266.62 | 0.215232E+11 | 0.989324E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.940532E+10 | 0.270741E+10 | 321.63 | 0.607262E+10 | 0.333270E+10 | 0.00 | 1.00 | 0.00 | 31409.31 | 17240.57 | 16801.78 | 7129.40 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 |
April | 0.789895E+09 | 0.236937E+09 | 39.31 | 0.546227E+09 | 0.243668E+09 | 0.00 | 0.50 | 18-APR-14:10 | 0.00 | 01-APR-00:05 | 12221.79 | 18-APR-14:10 | 8494.19 | 18-APR-14:10 | 3873.54 | 18-APR-12:40 | 3630.70 | 18-APR-14:10 | 0.00 | 01-APR-00:05 |
May | 0.146480E+10 | 0.439205E+09 | 123.87 | 0.104345E+10 | 0.421351E+09 | 0.00 | 0.51 | 31-MAY-15:00 | 0.00 | 01-MAY-00:10 | 12240.01 | 31-MAY-15:00 | 9655.59 | 31-MAY-15:00 | 3984.63 | 29-MAY-13:40 | 3787.66 | 31-MAY-15:00 | 0.00 | 01-MAY-00:10 |
June | 0.673445E+10 | 0.198851E+10 | 250.64 | 0.462746E+10 | 0.210698E+10 | 0.00 | 1.00 | 25-JUN-08:62 | 0.00 | 01-JUN-00:10 | 31047.23 | 26-JUN-07:02 | 17226.59 | 28-JUN-07:02 | 14488.77 | 30-JUN-07:02 | 7108.15 | 25-JUN-08:62 | 0.00 | 01-JUN-00:10 |
July | 0.928905E+10 | 0.267663E+10 | 320.04 | 0.598851E+10 | 0.330054E+10 | 0.00 | 1.00 | 02-JUL-08:62 | 0.00 | 01-JUL-00:03 | 30564.09 | 07-JUL-07:02 | 16860.38 | 02-JUL-08:62 | 16840.57 | 07-JUL-07:02 | 7093.55 | 02-JUL-08:62 | 0.00 | 01-JUL-00:03 |
August | 0.875147E+10 | 0.253980E+10 | 319.26 | 0.578493E+10 | 0.296654E+10 | 0.00 | 1.00 | 03-AUG-07:02 | 0.00 | 01-AUG-00:10 | 31435.88 | 04-AUG-07:02 | 15783.02 | 03-AUG-07:02 | 15782.32 | 04-AUG-07:03 | 7136.43 | 04-AUG-07:02 | 0.00 | 01-AUG-00:10 |
September | 0.392446E+10 | 0.118708E+10 | 189.83 | 0.317751E+10 | 0.746945E+09 | 0.00 | 0.92 | 11-SEP-07:03 | 0.00 | 01-SEP-00:10 | 26553.25 | 11-SEP-07:03 | 14950.85 | 11-SEP-07:03 | 11602.40 | 11-SEP-07:03 | 6239.62 | 11-SEP-07:03 | 0.00 | 01-SEP-00:10 |
October | 25801277.63 | 7901157.13 | 11.00 | 24433629.34 | 1367648.29 | 0.00 | 0.17 | 20-OCT-15:00 | 0.00 | 01-OCT-00:10 | 3491.58 | 20-OCT-15:00 | 3344.08 | 20-OCT-15:00 | 147.50 | 20-OCT-15:00 | 1068.69 | 20-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.309799E+11 | 0.907607E+10 | 1253.94 | 0.211925E+11 | 0.978739E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.928905E+10 | 0.267663E+10 | 320.04 | 0.598851E+10 | 0.330054E+10 | 0.00 | 1.00 | 0.00 | 31435.88 | 17226.59 | 16840.57 | 7136.43 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 |
April | 0.743944E+09 | 0.224207E+09 | 37.97 | 0.512133E+09 | 0.231811E+09 | 0.00 | 0.48 | 18-APR-14:10 | 0.00 | 01-APR-00:05 | 11850.27 | 18-APR-14:10 | 8194.23 | 18-APR-14:10 | 3784.69 | 18-APR-12:40 | 3536.21 | 18-APR-14:10 | 0.00 | 01-APR-00:05 |
May | 0.134997E+10 | 0.406818E+09 | 110.03 | 0.962069E+09 | 0.387897E+09 | 0.00 | 0.50 | 31-MAY-15:00 | 0.00 | 01-MAY-00:10 | 12001.02 | 31-MAY-15:00 | 9444.56 | 31-MAY-15:00 | 3772.14 | 29-MAY-13:40 | 3727.02 | 31-MAY-15:00 | 0.00 | 01-MAY-00:10 |
June | 0.653412E+10 | 0.193542E+10 | 248.02 | 0.448052E+10 | 0.205360E+10 | 0.00 | 1.00 | 26-JUN-07:02 | 0.00 | 01-JUN-00:10 | 31312.98 | 26-JUN-07:02 | 16932.34 | 26-JUN-07:02 | 14676.06 | 30-JUN-07:02 | 7168.39 | 27-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.905685E+10 | 0.261662E+10 | 316.84 | 0.583069E+10 | 0.322616E+10 | 0.00 | 1.00 | 02-JUL-08:62 | 0.00 | 01-JUL-00:03 | 30852.11 | 07-JUL-07:02 | 16965.62 | 02-JUL-08:62 | 17052.36 | 07-JUL-07:02 | 7161.09 | 02-JUL-08:62 | 0.00 | 01-JUL-00:03 |
August | 0.853533E+10 | 0.248350E+10 | 314.68 | 0.563651E+10 | 0.289881E+10 | 0.00 | 1.00 | 03-AUG-07:02 | 0.00 | 01-AUG-00:10 | 31721.38 | 04-AUG-07:02 | 15794.56 | 03-AUG-07:02 | 16002.98 | 04-AUG-07:02 | 7204.69 | 04-AUG-07:02 | 0.00 | 01-AUG-00:10 |
September | 0.383503E+10 | 0.116320E+10 | 184.44 | 0.310142E+10 | 0.733601E+09 | 0.00 | 0.83 | 11-SEP-07:03 | 0.00 | 01-SEP-00:10 | 23252.96 | 11-SEP-07:03 | 13060.73 | 11-SEP-07:03 | 10192.22 | 11-SEP-07:03 | 5636.99 | 11-SEP-07:03 | 0.00 | 01-SEP-00:10 |
October | 22178743.01 | 6812586.18 | 9.33 | 21035914.07 | 1142828.94 | 0.00 | 0.15 | 20-OCT-15:00 | 0.00 | 01-OCT-00:10 | 3263.54 | 20-OCT-15:00 | 3123.09 | 20-OCT-15:00 | 140.44 | 20-OCT-15:00 | 1001.99 | 20-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.300774E+11 | 0.883657E+10 | 1221.31 | 0.205444E+11 | 0.953302E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.905685E+10 | 0.261662E+10 | 316.84 | 0.583069E+10 | 0.322616E+10 | 0.00 | 1.00 | 0.00 | 31721.38 | 16965.62 | 17052.36 | 7204.69 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 |
April | 0.685628E+09 | 0.209483E+09 | 32.92 | 0.468232E+09 | 0.217396E+09 | 0.00 | 0.42 | 18-APR-14:10 | 0.00 | 01-APR-00:05 | 11465.61 | 18-APR-14:10 | 7853.51 | 18-APR-14:10 | 3759.58 | 18-APR-12:30 | 3473.31 | 18-APR-14:10 | 0.00 | 01-APR-00:05 |
May | 0.117796E+10 | 0.359992E+09 | 83.22 | 0.843204E+09 | 0.334760E+09 | 0.00 | 0.45 | 31-MAY-13:00 | 0.00 | 01-MAY-00:10 | 11894.47 | 31-MAY-13:00 | 9247.51 | 31-MAY-15:00 | 3507.08 | 29-MAY-13:40 | 3740.86 | 31-MAY-13:00 | 0.00 | 01-MAY-00:10 |
June | 0.628669E+10 | 0.188554E+10 | 237.62 | 0.430726E+10 | 0.197943E+10 | 0.00 | 1.00 | 26-JUN-07:02 | 0.00 | 01-JUN-00:10 | 35008.08 | 26-JUN-07:02 | 17491.39 | 26-JUN-07:02 | 17516.69 | 26-JUN-07:02 | 7962.65 | 26-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.882497E+10 | 0.257841E+10 | 305.40 | 0.569782E+10 | 0.312716E+10 | 0.00 | 1.00 | 04-JUL-08:62 | 0.00 | 01-JUL-00:03 | 34109.84 | 04-JUL-08:62 | 17451.36 | 04-JUL-08:62 | 16658.48 | 04-JUL-08:62 | 7805.65 | 04-JUL-08:62 | 0.00 | 01-JUL-00:03 |
August | 0.840223E+10 | 0.246879E+10 | 301.51 | 0.556841E+10 | 0.283381E+10 | 0.00 | 1.00 | 03-AUG-07:02 | 0.00 | 01-AUG-00:10 | 36018.41 | 04-AUG-07:02 | 15272.98 | 03-AUG-07:02 | 20971.93 | 04-AUG-07:02 | 8018.62 | 03-AUG-07:02 | 0.00 | 01-AUG-00:10 |
September | 0.384282E+10 | 0.117623E+10 | 174.72 | 0.311305E+10 | 0.729767E+09 | 0.00 | 0.57 | 06-SEP-14:10 | 0.00 | 01-SEP-00:10 | 15553.25 | 06-SEP-14:10 | 12393.49 | 07-SEP-14:10 | 4381.46 | 11-SEP-07:03 | 4917.05 | 06-SEP-14:10 | 0.00 | 01-SEP-00:10 |
October | 17728724.84 | 5479774.28 | 6.33 | 16875079.02 | 853645.82 | 0.00 | 0.13 | 20-OCT-15:00 | 0.00 | 01-OCT-00:10 | 3012.00 | 20-OCT-15:00 | 2888.27 | 20-OCT-15:00 | 123.73 | 20-OCT-15:00 | 930.91 | 20-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.292380E+11 | 0.868392E+10 | 1141.72 | 0.200149E+11 | 0.922318E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.882497E+10 | 0.257841E+10 | 305.40 | 0.569782E+10 | 0.312716E+10 | 0.00 | 1.00 | 0.00 | 36018.41 | 17491.39 | 20971.93 | 8018.62 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 119.63 | 81.86 | 37.77 | 92.52 | 161.01 | 0.00 | 0.00 | 744.00 |
February | 128.24 | 86.65 | 41.59 | 100.68 | 130.58 | 0.00 | 0.00 | 672.00 |
March | 111.62 | 58.80 | 52.82 | 87.25 | 94.22 | 0.00 | 0.00 | 744.00 |
April | 100.51 | 46.99 | 53.52 | 77.48 | 70.56 | 0.00 | 0.00 | 720.00 |
May | 83.26 | 22.56 | 60.70 | 60.21 | 44.39 | 0.00 | 0.00 | 744.00 |
June | 80.83 | 16.45 | 64.39 | 68.65 | 30.92 | 0.00 | 0.00 | 720.00 |
July | 85.57 | 21.55 | 64.02 | 76.23 | 25.95 | 0.00 | 0.00 | 744.00 |
August | 96.41 | 34.57 | 61.84 | 94.24 | 31.19 | 0.00 | 0.00 | 744.00 |
September | 116.87 | 61.59 | 55.28 | 117.09 | 52.10 | 0.00 | 0.00 | 720.00 |
October | 122.06 | 76.59 | 45.47 | 116.85 | 74.53 | 0.00 | 0.00 | 744.00 |
November | 92.05 | 57.62 | 34.43 | 75.70 | 108.06 | 0.00 | 0.00 | 720.00 |
December | 98.13 | 74.32 | 23.81 | 86.04 | 148.71 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 102.78 | 53.11 | 49.68 | 87.67 | 80.78 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 80.83 | 16.45 | 23.81 | 60.21 | 25.95 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 128.24 | 86.65 | 64.39 | 117.09 | 161.01 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 119.63 | 81.86 | 37.77 | 92.52 | 161.01 | 0.00 | 0.00 | 744.00 |
February | 128.24 | 86.65 | 41.59 | 100.68 | 130.58 | 0.00 | 0.00 | 672.00 |
March | 111.62 | 58.80 | 52.82 | 87.25 | 94.22 | 0.00 | 0.00 | 744.00 |
April | 100.51 | 46.99 | 53.52 | 77.48 | 70.56 | 0.00 | 0.00 | 720.00 |
May | 83.26 | 22.56 | 60.70 | 60.21 | 44.39 | 0.00 | 0.00 | 744.00 |
June | 80.83 | 16.45 | 64.39 | 68.65 | 30.92 | 0.00 | 0.00 | 720.00 |
July | 85.57 | 21.55 | 64.02 | 76.23 | 25.95 | 0.00 | 0.00 | 744.00 |
August | 96.41 | 34.57 | 61.84 | 94.24 | 31.19 | 0.00 | 0.00 | 744.00 |
September | 116.87 | 61.59 | 55.28 | 117.09 | 52.10 | 0.00 | 0.00 | 720.00 |
October | 122.06 | 76.59 | 45.47 | 116.85 | 74.53 | 0.00 | 0.00 | 744.00 |
November | 92.05 | 57.62 | 34.43 | 75.70 | 108.06 | 0.00 | 0.00 | 720.00 |
December | 98.13 | 74.32 | 23.81 | 86.04 | 148.71 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 102.78 | 53.11 | 49.68 | 87.67 | 80.78 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 80.83 | 16.45 | 23.81 | 60.21 | 25.95 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 128.24 | 86.65 | 64.39 | 117.09 | 161.01 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_3
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 119.63 | 81.86 | 37.77 | 92.52 | 161.01 | 0.00 | 0.00 | 744.00 |
February | 128.24 | 86.65 | 41.59 | 100.68 | 130.58 | 0.00 | 0.00 | 672.00 |
March | 111.62 | 58.80 | 52.82 | 87.25 | 94.22 | 0.00 | 0.00 | 744.00 |
April | 100.51 | 46.99 | 53.52 | 77.48 | 70.56 | 0.00 | 0.00 | 720.00 |
May | 83.26 | 22.56 | 60.70 | 60.21 | 44.39 | 0.00 | 0.00 | 744.00 |
June | 80.83 | 16.45 | 64.39 | 68.65 | 30.92 | 0.00 | 0.00 | 720.00 |
July | 85.57 | 21.55 | 64.02 | 76.23 | 25.95 | 0.00 | 0.00 | 744.00 |
August | 96.41 | 34.57 | 61.84 | 94.24 | 31.19 | 0.00 | 0.00 | 744.00 |
September | 116.87 | 61.59 | 55.28 | 117.09 | 52.10 | 0.00 | 0.00 | 720.00 |
October | 122.06 | 76.59 | 45.47 | 116.85 | 74.53 | 0.00 | 0.00 | 744.00 |
November | 92.05 | 57.62 | 34.43 | 75.70 | 108.06 | 0.00 | 0.00 | 720.00 |
December | 98.13 | 74.32 | 23.81 | 86.04 | 148.71 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 102.78 | 53.11 | 49.68 | 87.67 | 80.78 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 80.83 | 16.45 | 23.81 | 60.21 | 25.95 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 128.24 | 86.65 | 64.39 | 117.09 | 161.01 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_4
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 119.63 | 81.86 | 37.77 | 92.52 | 161.01 | 0.00 | 0.00 | 744.00 |
February | 128.24 | 86.65 | 41.59 | 100.68 | 130.58 | 0.00 | 0.00 | 672.00 |
March | 111.62 | 58.80 | 52.82 | 87.25 | 94.22 | 0.00 | 0.00 | 744.00 |
April | 100.51 | 46.99 | 53.52 | 77.48 | 70.56 | 0.00 | 0.00 | 720.00 |
May | 83.26 | 22.56 | 60.70 | 60.21 | 44.39 | 0.00 | 0.00 | 744.00 |
June | 80.83 | 16.45 | 64.39 | 68.65 | 30.92 | 0.00 | 0.00 | 720.00 |
July | 85.57 | 21.55 | 64.02 | 76.23 | 25.95 | 0.00 | 0.00 | 744.00 |
August | 96.41 | 34.57 | 61.84 | 94.24 | 31.19 | 0.00 | 0.00 | 744.00 |
September | 116.87 | 61.59 | 55.28 | 117.09 | 52.10 | 0.00 | 0.00 | 720.00 |
October | 122.06 | 76.59 | 45.47 | 116.85 | 74.53 | 0.00 | 0.00 | 744.00 |
November | 92.05 | 57.62 | 34.43 | 75.70 | 108.06 | 0.00 | 0.00 | 720.00 |
December | 98.13 | 74.32 | 23.81 | 86.04 | 148.71 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 102.78 | 53.11 | 49.68 | 87.67 | 80.78 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 80.83 | 16.45 | 23.81 | 60.21 | 25.95 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 128.24 | 86.65 | 64.39 | 117.09 | 161.01 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_DOOR_1
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 144.03 | 98.55 | 45.48 | 111.87 | 191.45 | 0.00 | 0.00 | 744.00 |
February | 154.40 | 104.32 | 50.07 | 121.67 | 155.31 | 0.00 | 0.00 | 672.00 |
March | 134.38 | 70.79 | 63.59 | 105.37 | 112.09 | 0.00 | 0.00 | 744.00 |
April | 121.01 | 56.57 | 64.44 | 93.43 | 84.03 | 0.00 | 0.00 | 720.00 |
May | 100.24 | 27.17 | 73.08 | 72.61 | 52.99 | 0.00 | 0.00 | 744.00 |
June | 97.32 | 19.80 | 77.52 | 82.57 | 36.96 | 0.00 | 0.00 | 720.00 |
July | 103.02 | 25.94 | 77.08 | 91.68 | 31.08 | 0.00 | 0.00 | 744.00 |
August | 116.07 | 41.62 | 74.46 | 113.34 | 37.31 | 0.00 | 0.00 | 744.00 |
September | 140.70 | 74.15 | 66.55 | 140.90 | 62.23 | 0.00 | 0.00 | 720.00 |
October | 146.95 | 92.21 | 54.74 | 140.82 | 88.90 | 0.00 | 0.00 | 744.00 |
November | 110.83 | 69.38 | 41.45 | 91.37 | 128.56 | 0.00 | 0.00 | 720.00 |
December | 118.14 | 89.48 | 28.66 | 103.83 | 176.94 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 123.75 | 63.94 | 59.81 | 105.70 | 96.21 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 97.32 | 19.80 | 28.66 | 72.61 | 31.08 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 154.40 | 104.32 | 77.52 | 140.90 | 191.45 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_DOOR_2
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 144.03 | 98.55 | 45.48 | 111.87 | 191.45 | 0.00 | 0.00 | 744.00 |
February | 154.40 | 104.32 | 50.07 | 121.67 | 155.31 | 0.00 | 0.00 | 672.00 |
March | 134.38 | 70.79 | 63.59 | 105.37 | 112.09 | 0.00 | 0.00 | 744.00 |
April | 121.01 | 56.57 | 64.44 | 93.43 | 84.03 | 0.00 | 0.00 | 720.00 |
May | 100.24 | 27.17 | 73.08 | 72.61 | 52.99 | 0.00 | 0.00 | 744.00 |
June | 97.32 | 19.80 | 77.52 | 82.57 | 36.96 | 0.00 | 0.00 | 720.00 |
July | 103.02 | 25.94 | 77.08 | 91.68 | 31.08 | 0.00 | 0.00 | 744.00 |
August | 116.07 | 41.62 | 74.46 | 113.34 | 37.31 | 0.00 | 0.00 | 744.00 |
September | 140.70 | 74.15 | 66.55 | 140.90 | 62.23 | 0.00 | 0.00 | 720.00 |
October | 146.95 | 92.21 | 54.74 | 140.82 | 88.90 | 0.00 | 0.00 | 744.00 |
November | 110.83 | 69.38 | 41.45 | 91.37 | 128.56 | 0.00 | 0.00 | 720.00 |
December | 118.14 | 89.48 | 28.66 | 103.83 | 176.94 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 123.75 | 63.94 | 59.81 | 105.70 | 96.21 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 97.32 | 19.80 | 28.66 | 72.61 | 31.08 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 154.40 | 104.32 | 77.52 | 140.90 | 191.45 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 119.63 | 81.86 | 37.77 | 91.32 | 165.95 | 0.00 | 0.00 | 744.00 |
February | 128.24 | 86.65 | 41.59 | 99.36 | 135.77 | 0.00 | 0.00 | 672.00 |
March | 111.62 | 58.80 | 52.82 | 85.73 | 99.86 | 0.00 | 0.00 | 744.00 |
April | 100.51 | 46.99 | 53.52 | 76.24 | 75.69 | 0.00 | 0.00 | 720.00 |
May | 83.26 | 22.56 | 60.70 | 58.94 | 46.69 | 0.00 | 0.00 | 744.00 |
June | 80.83 | 16.45 | 64.39 | 68.10 | 32.02 | 0.00 | 0.00 | 720.00 |
July | 85.57 | 21.55 | 64.02 | 76.04 | 26.30 | 0.00 | 0.00 | 744.00 |
August | 96.41 | 34.57 | 61.84 | 94.08 | 31.62 | 0.00 | 0.00 | 744.00 |
September | 116.87 | 61.59 | 55.28 | 116.57 | 53.73 | 0.00 | 0.00 | 720.00 |
October | 122.06 | 76.59 | 45.47 | 115.35 | 78.96 | 0.00 | 0.00 | 744.00 |
November | 92.05 | 57.62 | 34.43 | 74.62 | 113.04 | 0.00 | 0.00 | 720.00 |
December | 98.13 | 74.32 | 23.81 | 85.10 | 154.07 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 102.78 | 53.11 | 49.68 | 86.72 | 84.23 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 80.83 | 16.45 | 23.81 | 58.94 | 26.30 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 128.24 | 86.65 | 64.39 | 116.57 | 165.95 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 119.63 | 81.86 | 37.77 | 91.32 | 165.95 | 0.00 | 0.00 | 744.00 |
February | 128.24 | 86.65 | 41.59 | 99.36 | 135.77 | 0.00 | 0.00 | 672.00 |
March | 111.62 | 58.80 | 52.82 | 85.73 | 99.86 | 0.00 | 0.00 | 744.00 |
April | 100.51 | 46.99 | 53.52 | 76.24 | 75.69 | 0.00 | 0.00 | 720.00 |
May | 83.26 | 22.56 | 60.70 | 58.94 | 46.69 | 0.00 | 0.00 | 744.00 |
June | 80.83 | 16.45 | 64.39 | 68.10 | 32.02 | 0.00 | 0.00 | 720.00 |
July | 85.57 | 21.55 | 64.02 | 76.04 | 26.30 | 0.00 | 0.00 | 744.00 |
August | 96.41 | 34.57 | 61.84 | 94.08 | 31.62 | 0.00 | 0.00 | 744.00 |
September | 116.87 | 61.59 | 55.28 | 116.57 | 53.73 | 0.00 | 0.00 | 720.00 |
October | 122.06 | 76.59 | 45.47 | 115.35 | 78.96 | 0.00 | 0.00 | 744.00 |
November | 92.05 | 57.62 | 34.43 | 74.62 | 113.04 | 0.00 | 0.00 | 720.00 |
December | 98.13 | 74.32 | 23.81 | 85.10 | 154.07 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 102.78 | 53.11 | 49.68 | 86.72 | 84.23 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 80.83 | 16.45 | 23.81 | 58.94 | 26.30 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 128.24 | 86.65 | 64.39 | 116.57 | 165.95 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_DOOR
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 144.03 | 98.55 | 45.48 | 110.43 | 197.31 | 0.00 | 0.00 | 744.00 |
February | 154.40 | 104.32 | 50.07 | 120.08 | 161.45 | 0.00 | 0.00 | 672.00 |
March | 134.38 | 70.79 | 63.59 | 103.55 | 118.76 | 0.00 | 0.00 | 744.00 |
April | 121.01 | 56.57 | 64.44 | 91.94 | 90.11 | 0.00 | 0.00 | 720.00 |
May | 100.24 | 27.17 | 73.08 | 71.08 | 55.71 | 0.00 | 0.00 | 744.00 |
June | 97.32 | 19.80 | 77.52 | 81.91 | 38.26 | 0.00 | 0.00 | 720.00 |
July | 103.02 | 25.94 | 77.08 | 91.44 | 31.49 | 0.00 | 0.00 | 744.00 |
August | 116.07 | 41.62 | 74.46 | 113.15 | 37.80 | 0.00 | 0.00 | 744.00 |
September | 140.70 | 74.15 | 66.55 | 140.28 | 64.16 | 0.00 | 0.00 | 720.00 |
October | 146.95 | 92.21 | 54.74 | 139.04 | 94.11 | 0.00 | 0.00 | 744.00 |
November | 110.83 | 69.38 | 41.45 | 90.08 | 134.44 | 0.00 | 0.00 | 720.00 |
December | 118.14 | 89.48 | 28.66 | 102.72 | 183.29 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 123.75 | 63.94 | 59.81 | 104.55 | 100.28 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 97.32 | 19.80 | 28.66 | 71.08 | 31.49 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 154.40 | 104.32 | 77.52 | 140.28 | 197.31 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 119.63 | 81.86 | 37.77 | 91.61 | 161.30 | 0.00 | 0.00 | 744.00 |
February | 128.24 | 86.65 | 41.59 | 99.68 | 131.59 | 0.00 | 0.00 | 672.00 |
March | 111.62 | 58.80 | 52.82 | 86.10 | 96.49 | 0.00 | 0.00 | 744.00 |
April | 100.51 | 46.99 | 53.52 | 76.47 | 73.26 | 0.00 | 0.00 | 720.00 |
May | 83.26 | 22.56 | 60.70 | 59.06 | 46.79 | 0.00 | 0.00 | 744.00 |
June | 80.83 | 16.45 | 64.39 | 67.76 | 33.47 | 0.00 | 0.00 | 720.00 |
July | 85.57 | 21.55 | 64.02 | 75.60 | 28.46 | 0.00 | 0.00 | 744.00 |
August | 96.41 | 34.57 | 61.84 | 93.87 | 33.58 | 0.00 | 0.00 | 744.00 |
September | 116.87 | 61.59 | 55.28 | 116.55 | 54.58 | 0.00 | 0.00 | 720.00 |
October | 122.06 | 76.59 | 45.47 | 116.04 | 76.05 | 0.00 | 0.00 | 744.00 |
November | 92.05 | 57.62 | 34.43 | 75.00 | 109.32 | 0.00 | 0.00 | 720.00 |
December | 98.13 | 74.32 | 23.81 | 85.35 | 149.86 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 102.78 | 53.11 | 49.68 | 86.85 | 82.66 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 80.83 | 16.45 | 23.81 | 59.06 | 28.46 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 128.24 | 86.65 | 64.39 | 116.55 | 161.30 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 119.63 | 81.86 | 37.77 | 91.61 | 161.30 | 0.00 | 0.00 | 744.00 |
February | 128.24 | 86.65 | 41.59 | 99.68 | 131.59 | 0.00 | 0.00 | 672.00 |
March | 111.62 | 58.80 | 52.82 | 86.10 | 96.49 | 0.00 | 0.00 | 744.00 |
April | 100.51 | 46.99 | 53.52 | 76.47 | 73.26 | 0.00 | 0.00 | 720.00 |
May | 83.26 | 22.56 | 60.70 | 59.06 | 46.79 | 0.00 | 0.00 | 744.00 |
June | 80.83 | 16.45 | 64.39 | 67.76 | 33.47 | 0.00 | 0.00 | 720.00 |
July | 85.57 | 21.55 | 64.02 | 75.60 | 28.46 | 0.00 | 0.00 | 744.00 |
August | 96.41 | 34.57 | 61.84 | 93.87 | 33.58 | 0.00 | 0.00 | 744.00 |
September | 116.87 | 61.59 | 55.28 | 116.55 | 54.58 | 0.00 | 0.00 | 720.00 |
October | 122.06 | 76.59 | 45.47 | 116.04 | 76.05 | 0.00 | 0.00 | 744.00 |
November | 92.05 | 57.62 | 34.43 | 75.00 | 109.32 | 0.00 | 0.00 | 720.00 |
December | 98.13 | 74.32 | 23.81 | 85.35 | 149.86 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 102.78 | 53.11 | 49.68 | 86.85 | 82.66 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 80.83 | 16.45 | 23.81 | 59.06 | 28.46 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 128.24 | 86.65 | 64.39 | 116.55 | 161.30 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_DOOR
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 143.24 | 98.01 | 45.23 | 110.19 | 190.73 | 0.00 | 0.00 | 744.00 |
February | 153.55 | 103.75 | 49.80 | 119.82 | 155.62 | 0.00 | 0.00 | 672.00 |
March | 133.65 | 70.40 | 63.25 | 103.44 | 114.12 | 0.00 | 0.00 | 744.00 |
April | 120.35 | 56.26 | 64.09 | 91.72 | 86.73 | 0.00 | 0.00 | 720.00 |
May | 99.70 | 27.02 | 72.68 | 70.84 | 55.50 | 0.00 | 0.00 | 744.00 |
June | 96.79 | 19.69 | 77.10 | 81.06 | 39.73 | 0.00 | 0.00 | 720.00 |
July | 102.46 | 25.80 | 76.65 | 90.43 | 33.83 | 0.00 | 0.00 | 744.00 |
August | 115.44 | 41.39 | 74.05 | 112.29 | 39.88 | 0.00 | 0.00 | 744.00 |
September | 139.94 | 73.75 | 66.19 | 139.49 | 64.78 | 0.00 | 0.00 | 720.00 |
October | 146.15 | 91.71 | 54.44 | 139.11 | 90.15 | 0.00 | 0.00 | 744.00 |
November | 110.22 | 69.00 | 41.22 | 90.05 | 129.30 | 0.00 | 0.00 | 720.00 |
December | 117.49 | 88.99 | 28.51 | 102.45 | 177.29 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 123.07 | 63.59 | 59.48 | 104.15 | 97.86 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 96.79 | 19.69 | 28.51 | 70.84 | 33.83 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 153.55 | 103.75 | 77.10 | 139.49 | 190.73 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 119.63 | 81.86 | 37.77 | 91.75 | 159.90 | 0.00 | 0.00 | 744.00 |
February | 128.24 | 86.65 | 41.59 | 99.84 | 130.30 | 0.00 | 0.00 | 672.00 |
March | 111.62 | 58.80 | 52.82 | 86.34 | 95.19 | 0.00 | 0.00 | 744.00 |
April | 100.51 | 46.99 | 53.52 | 76.68 | 72.14 | 0.00 | 0.00 | 720.00 |
May | 83.26 | 22.56 | 60.70 | 59.25 | 46.24 | 0.00 | 0.00 | 744.00 |
June | 80.83 | 16.45 | 64.39 | 67.80 | 33.33 | 0.00 | 0.00 | 720.00 |
July | 85.57 | 21.55 | 64.02 | 75.58 | 28.52 | 0.00 | 0.00 | 744.00 |
August | 96.41 | 34.57 | 61.84 | 93.87 | 33.59 | 0.00 | 0.00 | 744.00 |
September | 116.87 | 61.59 | 55.28 | 116.63 | 54.22 | 0.00 | 0.00 | 720.00 |
October | 122.06 | 76.59 | 45.47 | 116.45 | 74.67 | 0.00 | 0.00 | 744.00 |
November | 92.05 | 57.62 | 34.43 | 75.24 | 107.83 | 0.00 | 0.00 | 720.00 |
December | 98.13 | 74.32 | 23.81 | 85.48 | 148.50 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 102.78 | 53.11 | 49.68 | 87.00 | 81.81 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 80.83 | 16.45 | 23.81 | 59.25 | 28.52 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 128.24 | 86.65 | 64.39 | 116.63 | 159.90 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 119.63 | 81.86 | 37.77 | 91.75 | 159.90 | 0.00 | 0.00 | 744.00 |
February | 128.24 | 86.65 | 41.59 | 99.84 | 130.30 | 0.00 | 0.00 | 672.00 |
March | 111.62 | 58.80 | 52.82 | 86.34 | 95.19 | 0.00 | 0.00 | 744.00 |
April | 100.51 | 46.99 | 53.52 | 76.68 | 72.14 | 0.00 | 0.00 | 720.00 |
May | 83.26 | 22.56 | 60.70 | 59.25 | 46.24 | 0.00 | 0.00 | 744.00 |
June | 80.83 | 16.45 | 64.39 | 67.80 | 33.33 | 0.00 | 0.00 | 720.00 |
July | 85.57 | 21.55 | 64.02 | 75.58 | 28.52 | 0.00 | 0.00 | 744.00 |
August | 96.41 | 34.57 | 61.84 | 93.87 | 33.59 | 0.00 | 0.00 | 744.00 |
September | 116.87 | 61.59 | 55.28 | 116.63 | 54.22 | 0.00 | 0.00 | 720.00 |
October | 122.06 | 76.59 | 45.47 | 116.45 | 74.67 | 0.00 | 0.00 | 744.00 |
November | 92.05 | 57.62 | 34.43 | 75.24 | 107.83 | 0.00 | 0.00 | 720.00 |
December | 98.13 | 74.32 | 23.81 | 85.48 | 148.50 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 102.78 | 53.11 | 49.68 | 87.00 | 81.81 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 80.83 | 16.45 | 23.81 | 59.25 | 28.52 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 128.24 | 86.65 | 64.39 | 116.63 | 159.90 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_DOOR
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 143.24 | 98.01 | 45.23 | 110.36 | 189.06 | 0.00 | 0.00 | 744.00 |
February | 153.55 | 103.75 | 49.80 | 120.02 | 154.08 | 0.00 | 0.00 | 672.00 |
March | 133.65 | 70.40 | 63.25 | 103.72 | 112.58 | 0.00 | 0.00 | 744.00 |
April | 120.35 | 56.26 | 64.09 | 91.97 | 85.40 | 0.00 | 0.00 | 720.00 |
May | 99.70 | 27.02 | 72.68 | 71.07 | 54.84 | 0.00 | 0.00 | 744.00 |
June | 96.79 | 19.69 | 77.10 | 81.12 | 39.56 | 0.00 | 0.00 | 720.00 |
July | 102.46 | 25.80 | 76.65 | 90.41 | 33.90 | 0.00 | 0.00 | 744.00 |
August | 115.44 | 41.39 | 74.05 | 112.28 | 39.90 | 0.00 | 0.00 | 744.00 |
September | 139.94 | 73.75 | 66.19 | 139.59 | 64.35 | 0.00 | 0.00 | 720.00 |
October | 146.15 | 91.71 | 54.44 | 139.60 | 88.52 | 0.00 | 0.00 | 744.00 |
November | 110.22 | 69.00 | 41.22 | 90.34 | 127.53 | 0.00 | 0.00 | 720.00 |
December | 117.49 | 88.99 | 28.51 | 102.61 | 175.67 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 123.07 | 63.59 | 59.48 | 104.34 | 96.84 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 96.79 | 19.69 | 28.51 | 71.07 | 33.90 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 153.55 | 103.75 | 77.10 | 139.60 | 189.06 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 119.63 | 81.86 | 37.77 | 91.92 | 158.97 | 0.00 | 0.00 | 744.00 |
February | 128.24 | 86.65 | 41.59 | 100.04 | 129.36 | 0.00 | 0.00 | 672.00 |
March | 111.62 | 58.80 | 52.82 | 86.62 | 94.13 | 0.00 | 0.00 | 744.00 |
April | 100.51 | 46.99 | 53.52 | 76.97 | 71.12 | 0.00 | 0.00 | 720.00 |
May | 83.26 | 22.56 | 60.70 | 59.63 | 45.48 | 0.00 | 0.00 | 744.00 |
June | 80.83 | 16.45 | 64.39 | 68.06 | 32.77 | 0.00 | 0.00 | 720.00 |
July | 85.57 | 21.55 | 64.02 | 75.73 | 28.16 | 0.00 | 0.00 | 744.00 |
August | 96.41 | 34.57 | 61.84 | 94.00 | 33.21 | 0.00 | 0.00 | 744.00 |
September | 116.87 | 61.59 | 55.28 | 116.86 | 53.53 | 0.00 | 0.00 | 720.00 |
October | 122.06 | 76.59 | 45.47 | 116.91 | 73.51 | 0.00 | 0.00 | 744.00 |
November | 92.05 | 57.62 | 34.43 | 75.55 | 106.54 | 0.00 | 0.00 | 720.00 |
December | 98.13 | 74.32 | 23.81 | 85.63 | 147.47 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 102.78 | 53.11 | 49.68 | 87.25 | 80.96 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 80.83 | 16.45 | 23.81 | 59.63 | 28.16 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 128.24 | 86.65 | 64.39 | 116.91 | 158.97 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 119.63 | 81.86 | 37.77 | 91.92 | 158.97 | 0.00 | 0.00 | 744.00 |
February | 128.24 | 86.65 | 41.59 | 100.04 | 129.36 | 0.00 | 0.00 | 672.00 |
March | 111.62 | 58.80 | 52.82 | 86.62 | 94.13 | 0.00 | 0.00 | 744.00 |
April | 100.51 | 46.99 | 53.52 | 76.97 | 71.12 | 0.00 | 0.00 | 720.00 |
May | 83.26 | 22.56 | 60.70 | 59.63 | 45.48 | 0.00 | 0.00 | 744.00 |
June | 80.83 | 16.45 | 64.39 | 68.06 | 32.77 | 0.00 | 0.00 | 720.00 |
July | 85.57 | 21.55 | 64.02 | 75.73 | 28.16 | 0.00 | 0.00 | 744.00 |
August | 96.41 | 34.57 | 61.84 | 94.00 | 33.21 | 0.00 | 0.00 | 744.00 |
September | 116.87 | 61.59 | 55.28 | 116.86 | 53.53 | 0.00 | 0.00 | 720.00 |
October | 122.06 | 76.59 | 45.47 | 116.91 | 73.51 | 0.00 | 0.00 | 744.00 |
November | 92.05 | 57.62 | 34.43 | 75.55 | 106.54 | 0.00 | 0.00 | 720.00 |
December | 98.13 | 74.32 | 23.81 | 85.63 | 147.47 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 102.78 | 53.11 | 49.68 | 87.25 | 80.96 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 80.83 | 16.45 | 23.81 | 59.63 | 28.16 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 128.24 | 86.65 | 64.39 | 116.91 | 158.97 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_DOOR
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 143.24 | 98.01 | 45.23 | 110.56 | 187.94 | 0.00 | 0.00 | 744.00 |
February | 153.55 | 103.75 | 49.80 | 120.26 | 152.96 | 0.00 | 0.00 | 672.00 |
March | 133.65 | 70.40 | 63.25 | 104.06 | 111.31 | 0.00 | 0.00 | 744.00 |
April | 120.35 | 56.26 | 64.09 | 92.32 | 84.19 | 0.00 | 0.00 | 720.00 |
May | 99.70 | 27.02 | 72.68 | 71.53 | 53.94 | 0.00 | 0.00 | 744.00 |
June | 96.79 | 19.69 | 77.10 | 81.42 | 38.90 | 0.00 | 0.00 | 720.00 |
July | 102.46 | 25.80 | 76.65 | 90.59 | 33.48 | 0.00 | 0.00 | 744.00 |
August | 115.44 | 41.39 | 74.05 | 112.45 | 39.45 | 0.00 | 0.00 | 744.00 |
September | 139.94 | 73.75 | 66.19 | 139.86 | 63.54 | 0.00 | 0.00 | 720.00 |
October | 146.15 | 91.71 | 54.44 | 140.14 | 87.13 | 0.00 | 0.00 | 744.00 |
November | 110.22 | 69.00 | 41.22 | 90.71 | 125.99 | 0.00 | 0.00 | 720.00 |
December | 117.49 | 88.99 | 28.51 | 102.80 | 174.44 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 123.07 | 63.59 | 59.48 | 104.64 | 95.84 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 96.79 | 19.69 | 28.51 | 71.53 | 33.48 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 153.55 | 103.75 | 77.10 | 140.14 | 187.94 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 119.63 | 81.86 | 37.77 | 92.95 | 154.86 | 0.00 | 0.00 | 744.00 |
February | 128.24 | 86.65 | 41.59 | 101.18 | 125.49 | 0.00 | 0.00 | 672.00 |
March | 111.62 | 58.80 | 52.82 | 87.76 | 90.44 | 0.00 | 0.00 | 744.00 |
April | 100.51 | 46.99 | 53.52 | 77.85 | 68.07 | 0.00 | 0.00 | 720.00 |
May | 83.26 | 22.56 | 60.70 | 60.67 | 43.29 | 0.00 | 0.00 | 744.00 |
June | 80.83 | 16.45 | 64.39 | 68.54 | 30.98 | 0.00 | 0.00 | 720.00 |
July | 85.57 | 21.55 | 64.02 | 75.87 | 26.86 | 0.00 | 0.00 | 744.00 |
August | 96.41 | 34.57 | 61.84 | 94.19 | 31.78 | 0.00 | 0.00 | 744.00 |
September | 116.87 | 61.59 | 55.28 | 117.34 | 51.56 | 0.00 | 0.00 | 720.00 |
October | 122.06 | 76.59 | 45.47 | 118.17 | 70.71 | 0.00 | 0.00 | 744.00 |
November | 92.05 | 57.62 | 34.43 | 76.64 | 102.50 | 0.00 | 0.00 | 720.00 |
December | 98.13 | 74.32 | 23.81 | 86.53 | 143.23 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 102.78 | 53.11 | 49.68 | 88.07 | 78.09 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 80.83 | 16.45 | 23.81 | 60.67 | 26.86 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 128.24 | 86.65 | 64.39 | 118.17 | 154.86 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 119.63 | 81.86 | 37.77 | 92.95 | 154.86 | 0.00 | 0.00 | 744.00 |
February | 128.24 | 86.65 | 41.59 | 101.18 | 125.49 | 0.00 | 0.00 | 672.00 |
March | 111.62 | 58.80 | 52.82 | 87.76 | 90.44 | 0.00 | 0.00 | 744.00 |
April | 100.51 | 46.99 | 53.52 | 77.85 | 68.07 | 0.00 | 0.00 | 720.00 |
May | 83.26 | 22.56 | 60.70 | 60.67 | 43.29 | 0.00 | 0.00 | 744.00 |
June | 80.83 | 16.45 | 64.39 | 68.54 | 30.98 | 0.00 | 0.00 | 720.00 |
July | 85.57 | 21.55 | 64.02 | 75.87 | 26.86 | 0.00 | 0.00 | 744.00 |
August | 96.41 | 34.57 | 61.84 | 94.19 | 31.78 | 0.00 | 0.00 | 744.00 |
September | 116.87 | 61.59 | 55.28 | 117.34 | 51.56 | 0.00 | 0.00 | 720.00 |
October | 122.06 | 76.59 | 45.47 | 118.17 | 70.71 | 0.00 | 0.00 | 744.00 |
November | 92.05 | 57.62 | 34.43 | 76.64 | 102.50 | 0.00 | 0.00 | 720.00 |
December | 98.13 | 74.32 | 23.81 | 86.53 | 143.23 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 102.78 | 53.11 | 49.68 | 88.07 | 78.09 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 80.83 | 16.45 | 23.81 | 60.67 | 26.86 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 128.24 | 86.65 | 64.39 | 118.17 | 154.86 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_3
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 119.63 | 81.86 | 37.77 | 92.95 | 154.86 | 0.00 | 0.00 | 744.00 |
February | 128.24 | 86.65 | 41.59 | 101.18 | 125.49 | 0.00 | 0.00 | 672.00 |
March | 111.62 | 58.80 | 52.82 | 87.76 | 90.44 | 0.00 | 0.00 | 744.00 |
April | 100.51 | 46.99 | 53.52 | 77.85 | 68.07 | 0.00 | 0.00 | 720.00 |
May | 83.26 | 22.56 | 60.70 | 60.67 | 43.29 | 0.00 | 0.00 | 744.00 |
June | 80.83 | 16.45 | 64.39 | 68.54 | 30.98 | 0.00 | 0.00 | 720.00 |
July | 85.57 | 21.55 | 64.02 | 75.87 | 26.86 | 0.00 | 0.00 | 744.00 |
August | 96.41 | 34.57 | 61.84 | 94.19 | 31.78 | 0.00 | 0.00 | 744.00 |
September | 116.87 | 61.59 | 55.28 | 117.34 | 51.56 | 0.00 | 0.00 | 720.00 |
October | 122.06 | 76.59 | 45.47 | 118.17 | 70.71 | 0.00 | 0.00 | 744.00 |
November | 92.05 | 57.62 | 34.43 | 76.64 | 102.50 | 0.00 | 0.00 | 720.00 |
December | 98.13 | 74.32 | 23.81 | 86.53 | 143.23 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 102.78 | 53.11 | 49.68 | 88.07 | 78.09 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 80.83 | 16.45 | 23.81 | 60.67 | 26.86 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 128.24 | 86.65 | 64.39 | 118.17 | 154.86 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_4
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 119.63 | 81.86 | 37.77 | 92.95 | 154.86 | 0.00 | 0.00 | 744.00 |
February | 128.24 | 86.65 | 41.59 | 101.18 | 125.49 | 0.00 | 0.00 | 672.00 |
March | 111.62 | 58.80 | 52.82 | 87.76 | 90.44 | 0.00 | 0.00 | 744.00 |
April | 100.51 | 46.99 | 53.52 | 77.85 | 68.07 | 0.00 | 0.00 | 720.00 |
May | 83.26 | 22.56 | 60.70 | 60.67 | 43.29 | 0.00 | 0.00 | 744.00 |
June | 80.83 | 16.45 | 64.39 | 68.54 | 30.98 | 0.00 | 0.00 | 720.00 |
July | 85.57 | 21.55 | 64.02 | 75.87 | 26.86 | 0.00 | 0.00 | 744.00 |
August | 96.41 | 34.57 | 61.84 | 94.19 | 31.78 | 0.00 | 0.00 | 744.00 |
September | 116.87 | 61.59 | 55.28 | 117.34 | 51.56 | 0.00 | 0.00 | 720.00 |
October | 122.06 | 76.59 | 45.47 | 118.17 | 70.71 | 0.00 | 0.00 | 744.00 |
November | 92.05 | 57.62 | 34.43 | 76.64 | 102.50 | 0.00 | 0.00 | 720.00 |
December | 98.13 | 74.32 | 23.81 | 86.53 | 143.23 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 102.78 | 53.11 | 49.68 | 88.07 | 78.09 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 80.83 | 16.45 | 23.81 | 60.67 | 26.86 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 128.24 | 86.65 | 64.39 | 118.17 | 154.86 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_DOOR_1
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 143.24 | 98.01 | 45.23 | 111.79 | 183.12 | 0.00 | 0.00 | 744.00 |
February | 153.55 | 103.75 | 49.80 | 121.62 | 148.41 | 0.00 | 0.00 | 672.00 |
March | 133.65 | 70.40 | 63.25 | 105.42 | 106.98 | 0.00 | 0.00 | 744.00 |
April | 120.35 | 56.26 | 64.09 | 93.38 | 80.59 | 0.00 | 0.00 | 720.00 |
May | 99.70 | 27.02 | 72.68 | 72.77 | 51.36 | 0.00 | 0.00 | 744.00 |
June | 96.79 | 19.69 | 77.10 | 82.01 | 36.80 | 0.00 | 0.00 | 720.00 |
July | 102.46 | 25.80 | 76.65 | 90.77 | 31.94 | 0.00 | 0.00 | 744.00 |
August | 115.44 | 41.39 | 74.05 | 112.69 | 37.76 | 0.00 | 0.00 | 744.00 |
September | 139.94 | 73.75 | 66.19 | 140.45 | 61.21 | 0.00 | 0.00 | 720.00 |
October | 146.15 | 91.71 | 54.44 | 141.65 | 83.84 | 0.00 | 0.00 | 744.00 |
November | 110.22 | 69.00 | 41.22 | 92.02 | 121.25 | 0.00 | 0.00 | 720.00 |
December | 117.49 | 88.99 | 28.51 | 103.87 | 169.45 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 123.07 | 63.59 | 59.48 | 105.61 | 92.46 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 96.79 | 19.69 | 28.51 | 72.77 | 31.94 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 153.55 | 103.75 | 77.10 | 141.65 | 183.12 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_DOOR_2
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 143.24 | 98.01 | 45.23 | 111.79 | 183.12 | 0.00 | 0.00 | 744.00 |
February | 153.55 | 103.75 | 49.80 | 121.62 | 148.41 | 0.00 | 0.00 | 672.00 |
March | 133.65 | 70.40 | 63.25 | 105.42 | 106.98 | 0.00 | 0.00 | 744.00 |
April | 120.35 | 56.26 | 64.09 | 93.38 | 80.59 | 0.00 | 0.00 | 720.00 |
May | 99.70 | 27.02 | 72.68 | 72.77 | 51.36 | 0.00 | 0.00 | 744.00 |
June | 96.79 | 19.69 | 77.10 | 82.01 | 36.80 | 0.00 | 0.00 | 720.00 |
July | 102.46 | 25.80 | 76.65 | 90.77 | 31.94 | 0.00 | 0.00 | 744.00 |
August | 115.44 | 41.39 | 74.05 | 112.69 | 37.76 | 0.00 | 0.00 | 744.00 |
September | 139.94 | 73.75 | 66.19 | 140.45 | 61.21 | 0.00 | 0.00 | 720.00 |
October | 146.15 | 91.71 | 54.44 | 141.65 | 83.84 | 0.00 | 0.00 | 744.00 |
November | 110.22 | 69.00 | 41.22 | 92.02 | 121.25 | 0.00 | 0.00 | 720.00 |
December | 117.49 | 88.99 | 28.51 | 103.87 | 169.45 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 123.07 | 63.59 | 59.48 | 105.61 | 92.46 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 96.79 | 19.69 | 28.51 | 72.77 | 31.94 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 153.55 | 103.75 | 77.10 | 141.65 | 183.12 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 119.63 | 81.86 | 37.77 | 92.42 | 156.05 | 0.00 | 0.00 | 744.00 |
February | 128.24 | 86.65 | 41.59 | 100.68 | 126.37 | 0.00 | 0.00 | 672.00 |
March | 111.62 | 58.80 | 52.82 | 87.41 | 90.97 | 0.00 | 0.00 | 744.00 |
April | 100.51 | 46.99 | 53.52 | 77.79 | 68.20 | 0.00 | 0.00 | 720.00 |
May | 83.26 | 22.56 | 60.70 | 60.83 | 43.04 | 0.00 | 0.00 | 744.00 |
June | 80.83 | 16.45 | 64.39 | 68.83 | 30.63 | 0.00 | 0.00 | 720.00 |
July | 85.57 | 21.55 | 64.02 | 76.14 | 26.51 | 0.00 | 0.00 | 744.00 |
August | 96.41 | 34.57 | 61.84 | 94.37 | 31.47 | 0.00 | 0.00 | 744.00 |
September | 116.87 | 61.59 | 55.28 | 117.39 | 51.34 | 0.00 | 0.00 | 720.00 |
October | 122.06 | 76.59 | 45.47 | 117.99 | 70.68 | 0.00 | 0.00 | 744.00 |
November | 92.05 | 57.62 | 34.43 | 76.39 | 103.03 | 0.00 | 0.00 | 720.00 |
December | 98.13 | 74.32 | 23.81 | 86.17 | 144.32 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 102.78 | 53.11 | 49.68 | 87.96 | 78.33 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 80.83 | 16.45 | 23.81 | 60.83 | 26.51 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 128.24 | 86.65 | 64.39 | 117.99 | 156.05 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 119.63 | 81.86 | 37.77 | 92.42 | 156.05 | 0.00 | 0.00 | 744.00 |
February | 128.24 | 86.65 | 41.59 | 100.68 | 126.37 | 0.00 | 0.00 | 672.00 |
March | 111.62 | 58.80 | 52.82 | 87.41 | 90.97 | 0.00 | 0.00 | 744.00 |
April | 100.51 | 46.99 | 53.52 | 77.79 | 68.20 | 0.00 | 0.00 | 720.00 |
May | 83.26 | 22.56 | 60.70 | 60.83 | 43.04 | 0.00 | 0.00 | 744.00 |
June | 80.83 | 16.45 | 64.39 | 68.83 | 30.63 | 0.00 | 0.00 | 720.00 |
July | 85.57 | 21.55 | 64.02 | 76.14 | 26.51 | 0.00 | 0.00 | 744.00 |
August | 96.41 | 34.57 | 61.84 | 94.37 | 31.47 | 0.00 | 0.00 | 744.00 |
September | 116.87 | 61.59 | 55.28 | 117.39 | 51.34 | 0.00 | 0.00 | 720.00 |
October | 122.06 | 76.59 | 45.47 | 117.99 | 70.68 | 0.00 | 0.00 | 744.00 |
November | 92.05 | 57.62 | 34.43 | 76.39 | 103.03 | 0.00 | 0.00 | 720.00 |
December | 98.13 | 74.32 | 23.81 | 86.17 | 144.32 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 102.78 | 53.11 | 49.68 | 87.96 | 78.33 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 80.83 | 16.45 | 23.81 | 60.83 | 26.51 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 128.24 | 86.65 | 64.39 | 117.99 | 156.05 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_DOOR
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 143.24 | 98.01 | 45.23 | 111.19 | 184.47 | 0.00 | 0.00 | 744.00 |
February | 153.55 | 103.75 | 49.80 | 121.05 | 149.41 | 0.00 | 0.00 | 672.00 |
March | 133.65 | 70.40 | 63.25 | 105.03 | 107.57 | 0.00 | 0.00 | 744.00 |
April | 120.35 | 56.26 | 64.09 | 93.32 | 80.72 | 0.00 | 0.00 | 720.00 |
May | 99.70 | 27.02 | 72.68 | 72.97 | 51.05 | 0.00 | 0.00 | 744.00 |
June | 96.79 | 19.69 | 77.10 | 82.36 | 36.37 | 0.00 | 0.00 | 720.00 |
July | 102.46 | 25.80 | 76.65 | 91.10 | 31.52 | 0.00 | 0.00 | 744.00 |
August | 115.44 | 41.39 | 74.05 | 112.91 | 37.39 | 0.00 | 0.00 | 744.00 |
September | 139.94 | 73.75 | 66.19 | 140.51 | 60.94 | 0.00 | 0.00 | 720.00 |
October | 146.15 | 91.71 | 54.44 | 141.45 | 83.78 | 0.00 | 0.00 | 744.00 |
November | 110.22 | 69.00 | 41.22 | 91.74 | 121.83 | 0.00 | 0.00 | 720.00 |
December | 117.49 | 88.99 | 28.51 | 103.46 | 170.70 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 123.07 | 63.59 | 59.48 | 105.50 | 92.71 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 96.79 | 19.69 | 28.51 | 72.97 | 31.52 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 153.55 | 103.75 | 77.10 | 141.45 | 184.47 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 119.63 | 81.86 | 37.77 | 92.45 | 155.93 | 0.00 | 0.00 | 744.00 |
February | 128.24 | 86.65 | 41.59 | 100.72 | 126.16 | 0.00 | 0.00 | 672.00 |
March | 111.62 | 58.80 | 52.82 | 87.50 | 90.65 | 0.00 | 0.00 | 744.00 |
April | 100.51 | 46.99 | 53.52 | 77.93 | 67.77 | 0.00 | 0.00 | 720.00 |
May | 83.26 | 22.56 | 60.70 | 61.16 | 42.53 | 0.00 | 0.00 | 744.00 |
June | 80.83 | 16.45 | 64.39 | 69.01 | 30.34 | 0.00 | 0.00 | 720.00 |
July | 85.57 | 21.55 | 64.02 | 76.26 | 26.34 | 0.00 | 0.00 | 744.00 |
August | 96.41 | 34.57 | 61.84 | 94.46 | 31.30 | 0.00 | 0.00 | 744.00 |
September | 116.87 | 61.59 | 55.28 | 117.50 | 51.05 | 0.00 | 0.00 | 720.00 |
October | 122.06 | 76.59 | 45.47 | 118.13 | 70.30 | 0.00 | 0.00 | 744.00 |
November | 92.05 | 57.62 | 34.43 | 76.49 | 102.67 | 0.00 | 0.00 | 720.00 |
December | 98.13 | 74.32 | 23.81 | 86.21 | 144.13 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 102.78 | 53.11 | 49.68 | 88.08 | 78.04 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 80.83 | 16.45 | 23.81 | 61.16 | 26.34 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 128.24 | 86.65 | 64.39 | 118.13 | 155.93 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 119.63 | 81.86 | 37.77 | 92.45 | 155.93 | 0.00 | 0.00 | 744.00 |
February | 128.24 | 86.65 | 41.59 | 100.72 | 126.16 | 0.00 | 0.00 | 672.00 |
March | 111.62 | 58.80 | 52.82 | 87.50 | 90.65 | 0.00 | 0.00 | 744.00 |
April | 100.51 | 46.99 | 53.52 | 77.93 | 67.77 | 0.00 | 0.00 | 720.00 |
May | 83.26 | 22.56 | 60.70 | 61.16 | 42.53 | 0.00 | 0.00 | 744.00 |
June | 80.83 | 16.45 | 64.39 | 69.01 | 30.34 | 0.00 | 0.00 | 720.00 |
July | 85.57 | 21.55 | 64.02 | 76.26 | 26.34 | 0.00 | 0.00 | 744.00 |
August | 96.41 | 34.57 | 61.84 | 94.46 | 31.30 | 0.00 | 0.00 | 744.00 |
September | 116.87 | 61.59 | 55.28 | 117.50 | 51.05 | 0.00 | 0.00 | 720.00 |
October | 122.06 | 76.59 | 45.47 | 118.13 | 70.30 | 0.00 | 0.00 | 744.00 |
November | 92.05 | 57.62 | 34.43 | 76.49 | 102.67 | 0.00 | 0.00 | 720.00 |
December | 98.13 | 74.32 | 23.81 | 86.21 | 144.13 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 102.78 | 53.11 | 49.68 | 88.08 | 78.04 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 80.83 | 16.45 | 23.81 | 61.16 | 26.34 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 128.24 | 86.65 | 64.39 | 118.13 | 155.93 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_DOOR
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 143.24 | 98.01 | 45.23 | 111.21 | 184.33 | 0.00 | 0.00 | 744.00 |
February | 153.55 | 103.75 | 49.80 | 121.10 | 149.16 | 0.00 | 0.00 | 672.00 |
March | 133.65 | 70.40 | 63.25 | 105.14 | 107.19 | 0.00 | 0.00 | 744.00 |
April | 120.35 | 56.26 | 64.09 | 93.49 | 80.20 | 0.00 | 0.00 | 720.00 |
May | 99.70 | 27.02 | 72.68 | 73.37 | 50.44 | 0.00 | 0.00 | 744.00 |
June | 96.79 | 19.69 | 77.10 | 82.58 | 36.02 | 0.00 | 0.00 | 720.00 |
July | 102.46 | 25.80 | 76.65 | 91.23 | 31.32 | 0.00 | 0.00 | 744.00 |
August | 115.44 | 41.39 | 74.05 | 113.02 | 37.18 | 0.00 | 0.00 | 744.00 |
September | 139.94 | 73.75 | 66.19 | 140.65 | 60.59 | 0.00 | 0.00 | 720.00 |
October | 146.15 | 91.71 | 54.44 | 141.62 | 83.33 | 0.00 | 0.00 | 744.00 |
November | 110.22 | 69.00 | 41.22 | 91.85 | 121.40 | 0.00 | 0.00 | 720.00 |
December | 117.49 | 88.99 | 28.51 | 103.50 | 170.47 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 123.07 | 63.59 | 59.48 | 105.64 | 92.37 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 96.79 | 19.69 | 28.51 | 73.37 | 31.32 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 153.55 | 103.75 | 77.10 | 141.62 | 184.33 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 119.63 | 81.86 | 37.77 | 92.56 | 155.20 | 0.00 | 0.00 | 744.00 |
February | 128.24 | 86.65 | 41.59 | 100.89 | 125.15 | 0.00 | 0.00 | 672.00 |
March | 111.62 | 58.80 | 52.82 | 87.80 | 89.34 | 0.00 | 0.00 | 744.00 |
April | 100.51 | 46.99 | 53.52 | 78.33 | 66.24 | 0.00 | 0.00 | 720.00 |
May | 83.26 | 22.56 | 60.70 | 62.00 | 41.10 | 0.00 | 0.00 | 744.00 |
June | 80.83 | 16.45 | 64.39 | 69.41 | 29.60 | 0.00 | 0.00 | 720.00 |
July | 85.57 | 21.55 | 64.02 | 76.46 | 25.94 | 0.00 | 0.00 | 744.00 |
August | 96.41 | 34.57 | 61.84 | 94.63 | 30.90 | 0.00 | 0.00 | 744.00 |
September | 116.87 | 61.59 | 55.28 | 117.74 | 50.29 | 0.00 | 0.00 | 720.00 |
October | 122.06 | 76.59 | 45.47 | 118.47 | 69.23 | 0.00 | 0.00 | 744.00 |
November | 92.05 | 57.62 | 34.43 | 76.73 | 101.52 | 0.00 | 0.00 | 720.00 |
December | 98.13 | 74.32 | 23.81 | 86.34 | 143.11 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 102.78 | 53.11 | 49.68 | 88.38 | 77.08 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 80.83 | 16.45 | 23.81 | 62.00 | 25.94 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 128.24 | 86.65 | 64.39 | 118.47 | 155.20 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 119.63 | 81.86 | 37.77 | 92.56 | 155.20 | 0.00 | 0.00 | 744.00 |
February | 128.24 | 86.65 | 41.59 | 100.89 | 125.15 | 0.00 | 0.00 | 672.00 |
March | 111.62 | 58.80 | 52.82 | 87.80 | 89.34 | 0.00 | 0.00 | 744.00 |
April | 100.51 | 46.99 | 53.52 | 78.33 | 66.24 | 0.00 | 0.00 | 720.00 |
May | 83.26 | 22.56 | 60.70 | 62.00 | 41.10 | 0.00 | 0.00 | 744.00 |
June | 80.83 | 16.45 | 64.39 | 69.41 | 29.60 | 0.00 | 0.00 | 720.00 |
July | 85.57 | 21.55 | 64.02 | 76.46 | 25.94 | 0.00 | 0.00 | 744.00 |
August | 96.41 | 34.57 | 61.84 | 94.63 | 30.90 | 0.00 | 0.00 | 744.00 |
September | 116.87 | 61.59 | 55.28 | 117.74 | 50.29 | 0.00 | 0.00 | 720.00 |
October | 122.06 | 76.59 | 45.47 | 118.47 | 69.23 | 0.00 | 0.00 | 744.00 |
November | 92.05 | 57.62 | 34.43 | 76.73 | 101.52 | 0.00 | 0.00 | 720.00 |
December | 98.13 | 74.32 | 23.81 | 86.34 | 143.11 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 102.78 | 53.11 | 49.68 | 88.38 | 77.08 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 80.83 | 16.45 | 23.81 | 62.00 | 25.94 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 128.24 | 86.65 | 64.39 | 118.47 | 155.20 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_DOOR
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 143.24 | 98.01 | 45.23 | 111.35 | 183.46 | 0.00 | 0.00 | 744.00 |
February | 153.55 | 103.75 | 49.80 | 121.30 | 147.96 | 0.00 | 0.00 | 672.00 |
March | 133.65 | 70.40 | 63.25 | 105.50 | 105.63 | 0.00 | 0.00 | 744.00 |
April | 120.35 | 56.26 | 64.09 | 93.97 | 78.39 | 0.00 | 0.00 | 720.00 |
May | 99.70 | 27.02 | 72.68 | 74.38 | 48.75 | 0.00 | 0.00 | 744.00 |
June | 96.79 | 19.69 | 77.10 | 83.06 | 35.15 | 0.00 | 0.00 | 720.00 |
July | 102.46 | 25.80 | 76.65 | 91.48 | 30.85 | 0.00 | 0.00 | 744.00 |
August | 115.44 | 41.39 | 74.05 | 113.22 | 36.71 | 0.00 | 0.00 | 744.00 |
September | 139.94 | 73.75 | 66.19 | 140.94 | 59.69 | 0.00 | 0.00 | 720.00 |
October | 146.15 | 91.71 | 54.44 | 142.03 | 82.06 | 0.00 | 0.00 | 744.00 |
November | 110.22 | 69.00 | 41.22 | 92.15 | 120.04 | 0.00 | 0.00 | 720.00 |
December | 117.49 | 88.99 | 28.51 | 103.67 | 169.25 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 123.07 | 63.59 | 59.48 | 106.00 | 91.23 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 96.79 | 19.69 | 28.51 | 74.38 | 30.85 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 153.55 | 103.75 | 77.10 | 142.03 | 183.46 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 119.63 | 81.86 | 37.77 | 93.26 | 151.06 | 0.00 | 0.00 | 744.00 |
February | 128.24 | 86.65 | 41.59 | 101.76 | 120.14 | 0.00 | 0.00 | 672.00 |
March | 111.62 | 58.80 | 52.82 | 88.95 | 83.60 | 0.00 | 0.00 | 744.00 |
April | 100.51 | 46.99 | 53.52 | 79.64 | 60.07 | 0.00 | 0.00 | 720.00 |
May | 83.26 | 22.56 | 60.70 | 64.30 | 36.38 | 0.00 | 0.00 | 744.00 |
June | 80.83 | 16.45 | 64.39 | 70.55 | 26.87 | 0.00 | 0.00 | 720.00 |
July | 85.57 | 21.55 | 64.02 | 77.09 | 24.26 | 0.00 | 0.00 | 744.00 |
August | 96.41 | 34.57 | 61.84 | 95.06 | 29.19 | 0.00 | 0.00 | 744.00 |
September | 116.87 | 61.59 | 55.28 | 118.34 | 47.54 | 0.00 | 0.00 | 720.00 |
October | 122.06 | 76.59 | 45.47 | 119.41 | 65.22 | 0.00 | 0.00 | 744.00 |
November | 92.05 | 57.62 | 34.43 | 77.48 | 96.96 | 0.00 | 0.00 | 720.00 |
December | 98.13 | 74.32 | 23.81 | 86.93 | 138.28 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 102.78 | 53.11 | 49.68 | 89.33 | 73.08 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 80.83 | 16.45 | 23.81 | 64.30 | 24.26 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 128.24 | 86.65 | 64.39 | 119.41 | 151.06 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 119.63 | 81.86 | 37.77 | 93.26 | 151.06 | 0.00 | 0.00 | 744.00 |
February | 128.24 | 86.65 | 41.59 | 101.76 | 120.14 | 0.00 | 0.00 | 672.00 |
March | 111.62 | 58.80 | 52.82 | 88.95 | 83.60 | 0.00 | 0.00 | 744.00 |
April | 100.51 | 46.99 | 53.52 | 79.64 | 60.07 | 0.00 | 0.00 | 720.00 |
May | 83.26 | 22.56 | 60.70 | 64.30 | 36.38 | 0.00 | 0.00 | 744.00 |
June | 80.83 | 16.45 | 64.39 | 70.55 | 26.87 | 0.00 | 0.00 | 720.00 |
July | 85.57 | 21.55 | 64.02 | 77.09 | 24.26 | 0.00 | 0.00 | 744.00 |
August | 96.41 | 34.57 | 61.84 | 95.06 | 29.19 | 0.00 | 0.00 | 744.00 |
September | 116.87 | 61.59 | 55.28 | 118.34 | 47.54 | 0.00 | 0.00 | 720.00 |
October | 122.06 | 76.59 | 45.47 | 119.41 | 65.22 | 0.00 | 0.00 | 744.00 |
November | 92.05 | 57.62 | 34.43 | 77.48 | 96.96 | 0.00 | 0.00 | 720.00 |
December | 98.13 | 74.32 | 23.81 | 86.93 | 138.28 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 102.78 | 53.11 | 49.68 | 89.33 | 73.08 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 80.83 | 16.45 | 23.81 | 64.30 | 24.26 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 128.24 | 86.65 | 64.39 | 119.41 | 151.06 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_DOOR
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 143.24 | 98.01 | 45.23 | 112.21 | 178.50 | 0.00 | 0.00 | 744.00 |
February | 153.55 | 103.75 | 49.80 | 122.37 | 141.98 | 0.00 | 0.00 | 672.00 |
March | 133.65 | 70.40 | 63.25 | 106.90 | 98.82 | 0.00 | 0.00 | 744.00 |
April | 120.35 | 56.26 | 64.09 | 95.56 | 71.07 | 0.00 | 0.00 | 720.00 |
May | 99.70 | 27.02 | 72.68 | 77.14 | 43.17 | 0.00 | 0.00 | 744.00 |
June | 96.79 | 19.69 | 77.10 | 84.43 | 31.93 | 0.00 | 0.00 | 720.00 |
July | 102.46 | 25.80 | 76.65 | 92.23 | 28.86 | 0.00 | 0.00 | 744.00 |
August | 115.44 | 41.39 | 74.05 | 113.74 | 34.70 | 0.00 | 0.00 | 744.00 |
September | 139.94 | 73.75 | 66.19 | 141.66 | 56.46 | 0.00 | 0.00 | 720.00 |
October | 146.15 | 91.71 | 54.44 | 143.17 | 77.33 | 0.00 | 0.00 | 744.00 |
November | 110.22 | 69.00 | 41.22 | 93.07 | 114.64 | 0.00 | 0.00 | 720.00 |
December | 117.49 | 88.99 | 28.51 | 104.38 | 163.50 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 123.07 | 63.59 | 59.48 | 107.15 | 86.49 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 96.79 | 19.69 | 28.51 | 77.14 | 28.86 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 153.55 | 103.75 | 77.10 | 143.17 | 178.50 | 0.00 | 0.00 | 744.00 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.320420E+09 | 0.219248E+09 | 0.101171E+09 | 0.247803E+09 | 0.431242E+09 |
February | 0.310244E+09 | 0.209629E+09 | 0.100615E+09 | 0.243560E+09 | 0.315910E+09 |
March | 0.298959E+09 | 0.157481E+09 | 0.141478E+09 | 0.233687E+09 | 0.252369E+09 |
April | 0.260528E+09 | 0.121793E+09 | 0.138735E+09 | 0.200823E+09 | 0.182901E+09 |
May | 0.223012E+09 | 60435776.82 | 0.162576E+09 | 0.161273E+09 | 0.118887E+09 |
June | 0.209524E+09 | 42632042.87 | 0.166892E+09 | 0.177943E+09 | 80140305.11 |
July | 0.229186E+09 | 57717198.46 | 0.171469E+09 | 0.204181E+09 | 69516835.36 |
August | 0.258228E+09 | 92583616.90 | 0.165644E+09 | 0.252405E+09 | 83544934.57 |
September | 0.302924E+09 | 0.159644E+09 | 0.143280E+09 | 0.303508E+09 | 0.135032E+09 |
October | 0.326917E+09 | 0.205140E+09 | 0.121778E+09 | 0.312967E+09 | 0.199633E+09 |
November | 0.238598E+09 | 0.149360E+09 | 89237204.53 | 0.196202E+09 | 0.280080E+09 |
December | 0.262824E+09 | 0.199060E+09 | 63763438.80 | 0.230438E+09 | 0.398305E+09 |
Annual Sum or Average | 0.324136E+10 | 0.167472E+10 | 0.156664E+10 | 0.276479E+10 | 0.254756E+10 |
Minimum of Months | 0.209524E+09 | 42632042.87 | 63763438.80 | 0.161273E+09 | 69516835.36 |
Maximum of Months | 0.326917E+09 | 0.219248E+09 | 0.171469E+09 | 0.312967E+09 | 0.431242E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.320420E+09 | 0.219248E+09 | 0.101171E+09 | 0.247803E+09 | 0.431242E+09 |
February | 0.310244E+09 | 0.209629E+09 | 0.100615E+09 | 0.243560E+09 | 0.315910E+09 |
March | 0.298959E+09 | 0.157481E+09 | 0.141478E+09 | 0.233687E+09 | 0.252369E+09 |
April | 0.260528E+09 | 0.121793E+09 | 0.138735E+09 | 0.200823E+09 | 0.182901E+09 |
May | 0.223012E+09 | 60435776.82 | 0.162576E+09 | 0.161273E+09 | 0.118887E+09 |
June | 0.209524E+09 | 42632042.87 | 0.166892E+09 | 0.177943E+09 | 80140305.11 |
July | 0.229186E+09 | 57717198.46 | 0.171469E+09 | 0.204181E+09 | 69516835.36 |
August | 0.258228E+09 | 92583616.90 | 0.165644E+09 | 0.252405E+09 | 83544934.57 |
September | 0.302924E+09 | 0.159644E+09 | 0.143280E+09 | 0.303508E+09 | 0.135032E+09 |
October | 0.326917E+09 | 0.205140E+09 | 0.121778E+09 | 0.312967E+09 | 0.199633E+09 |
November | 0.238598E+09 | 0.149360E+09 | 89237204.53 | 0.196202E+09 | 0.280080E+09 |
December | 0.262824E+09 | 0.199060E+09 | 63763438.80 | 0.230438E+09 | 0.398305E+09 |
Annual Sum or Average | 0.324136E+10 | 0.167472E+10 | 0.156664E+10 | 0.276479E+10 | 0.254756E+10 |
Minimum of Months | 0.209524E+09 | 42632042.87 | 63763438.80 | 0.161273E+09 | 69516835.36 |
Maximum of Months | 0.326917E+09 | 0.219248E+09 | 0.171469E+09 | 0.312967E+09 | 0.431242E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_3
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.320420E+09 | 0.219248E+09 | 0.101171E+09 | 0.247803E+09 | 0.431242E+09 |
February | 0.310244E+09 | 0.209629E+09 | 0.100615E+09 | 0.243560E+09 | 0.315910E+09 |
March | 0.298959E+09 | 0.157481E+09 | 0.141478E+09 | 0.233687E+09 | 0.252369E+09 |
April | 0.260528E+09 | 0.121793E+09 | 0.138735E+09 | 0.200823E+09 | 0.182901E+09 |
May | 0.223012E+09 | 60435776.82 | 0.162576E+09 | 0.161273E+09 | 0.118887E+09 |
June | 0.209524E+09 | 42632042.87 | 0.166892E+09 | 0.177943E+09 | 80140305.11 |
July | 0.229186E+09 | 57717198.46 | 0.171469E+09 | 0.204181E+09 | 69516835.36 |
August | 0.258228E+09 | 92583616.90 | 0.165644E+09 | 0.252405E+09 | 83544934.57 |
September | 0.302924E+09 | 0.159644E+09 | 0.143280E+09 | 0.303508E+09 | 0.135032E+09 |
October | 0.326917E+09 | 0.205140E+09 | 0.121778E+09 | 0.312967E+09 | 0.199633E+09 |
November | 0.238598E+09 | 0.149360E+09 | 89237204.53 | 0.196202E+09 | 0.280080E+09 |
December | 0.262824E+09 | 0.199060E+09 | 63763438.80 | 0.230438E+09 | 0.398305E+09 |
Annual Sum or Average | 0.324136E+10 | 0.167472E+10 | 0.156664E+10 | 0.276479E+10 | 0.254756E+10 |
Minimum of Months | 0.209524E+09 | 42632042.87 | 63763438.80 | 0.161273E+09 | 69516835.36 |
Maximum of Months | 0.326917E+09 | 0.219248E+09 | 0.171469E+09 | 0.312967E+09 | 0.431242E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_4
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.320420E+09 | 0.219248E+09 | 0.101171E+09 | 0.247803E+09 | 0.431242E+09 |
February | 0.310244E+09 | 0.209629E+09 | 0.100615E+09 | 0.243560E+09 | 0.315910E+09 |
March | 0.298959E+09 | 0.157481E+09 | 0.141478E+09 | 0.233687E+09 | 0.252369E+09 |
April | 0.260528E+09 | 0.121793E+09 | 0.138735E+09 | 0.200823E+09 | 0.182901E+09 |
May | 0.223012E+09 | 60435776.82 | 0.162576E+09 | 0.161273E+09 | 0.118887E+09 |
June | 0.209524E+09 | 42632042.87 | 0.166892E+09 | 0.177943E+09 | 80140305.11 |
July | 0.229186E+09 | 57717198.46 | 0.171469E+09 | 0.204181E+09 | 69516835.36 |
August | 0.258228E+09 | 92583616.90 | 0.165644E+09 | 0.252405E+09 | 83544934.57 |
September | 0.302924E+09 | 0.159644E+09 | 0.143280E+09 | 0.303508E+09 | 0.135032E+09 |
October | 0.326917E+09 | 0.205140E+09 | 0.121778E+09 | 0.312967E+09 | 0.199633E+09 |
November | 0.238598E+09 | 0.149360E+09 | 89237204.53 | 0.196202E+09 | 0.280080E+09 |
December | 0.262824E+09 | 0.199060E+09 | 63763438.80 | 0.230438E+09 | 0.398305E+09 |
Annual Sum or Average | 0.324136E+10 | 0.167472E+10 | 0.156664E+10 | 0.276479E+10 | 0.254756E+10 |
Minimum of Months | 0.209524E+09 | 42632042.87 | 63763438.80 | 0.161273E+09 | 69516835.36 |
Maximum of Months | 0.326917E+09 | 0.219248E+09 | 0.171469E+09 | 0.312967E+09 | 0.431242E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_DOOR_1
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.385768E+09 | 0.263963E+09 | 0.121805E+09 | 0.299630E+09 | 0.512789E+09 |
February | 0.373517E+09 | 0.252382E+09 | 0.121136E+09 | 0.294338E+09 | 0.375723E+09 |
March | 0.359930E+09 | 0.189599E+09 | 0.170332E+09 | 0.282236E+09 | 0.300230E+09 |
April | 0.313661E+09 | 0.146632E+09 | 0.167029E+09 | 0.242174E+09 | 0.217813E+09 |
May | 0.268494E+09 | 72761494.47 | 0.195733E+09 | 0.194476E+09 | 0.141917E+09 |
June | 0.252256E+09 | 51326735.82 | 0.200929E+09 | 0.214033E+09 | 95793994.98 |
July | 0.275928E+09 | 69488469.20 | 0.206439E+09 | 0.245549E+09 | 83240417.34 |
August | 0.310893E+09 | 0.111466E+09 | 0.199427E+09 | 0.303579E+09 | 99926609.85 |
September | 0.364704E+09 | 0.192202E+09 | 0.172502E+09 | 0.365223E+09 | 0.161306E+09 |
October | 0.393591E+09 | 0.246977E+09 | 0.146614E+09 | 0.377183E+09 | 0.238103E+09 |
November | 0.287259E+09 | 0.179822E+09 | 0.107437E+09 | 0.236830E+09 | 0.333230E+09 |
December | 0.316426E+09 | 0.239658E+09 | 76767824.34 | 0.278099E+09 | 0.473906E+09 |
Annual Sum or Average | 0.390243E+10 | 0.201628E+10 | 0.188615E+10 | 0.333335E+10 | 0.303398E+10 |
Minimum of Months | 0.252256E+09 | 51326735.82 | 76767824.34 | 0.194476E+09 | 83240417.34 |
Maximum of Months | 0.393591E+09 | 0.263963E+09 | 0.206439E+09 | 0.377183E+09 | 0.512789E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_DOOR_2
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.385768E+09 | 0.263963E+09 | 0.121805E+09 | 0.299630E+09 | 0.512789E+09 |
February | 0.373517E+09 | 0.252382E+09 | 0.121136E+09 | 0.294338E+09 | 0.375723E+09 |
March | 0.359930E+09 | 0.189599E+09 | 0.170332E+09 | 0.282236E+09 | 0.300230E+09 |
April | 0.313661E+09 | 0.146632E+09 | 0.167029E+09 | 0.242174E+09 | 0.217813E+09 |
May | 0.268494E+09 | 72761494.47 | 0.195733E+09 | 0.194476E+09 | 0.141917E+09 |
June | 0.252256E+09 | 51326735.82 | 0.200929E+09 | 0.214033E+09 | 95793994.98 |
July | 0.275928E+09 | 69488469.20 | 0.206439E+09 | 0.245549E+09 | 83240417.34 |
August | 0.310893E+09 | 0.111466E+09 | 0.199427E+09 | 0.303579E+09 | 99926609.85 |
September | 0.364704E+09 | 0.192202E+09 | 0.172502E+09 | 0.365223E+09 | 0.161306E+09 |
October | 0.393591E+09 | 0.246977E+09 | 0.146614E+09 | 0.377183E+09 | 0.238103E+09 |
November | 0.287259E+09 | 0.179822E+09 | 0.107437E+09 | 0.236830E+09 | 0.333230E+09 |
December | 0.316426E+09 | 0.239658E+09 | 76767824.34 | 0.278099E+09 | 0.473906E+09 |
Annual Sum or Average | 0.390243E+10 | 0.201628E+10 | 0.188615E+10 | 0.333335E+10 | 0.303398E+10 |
Minimum of Months | 0.252256E+09 | 51326735.82 | 76767824.34 | 0.194476E+09 | 83240417.34 |
Maximum of Months | 0.393591E+09 | 0.263963E+09 | 0.206439E+09 | 0.377183E+09 | 0.512789E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.320420E+09 | 0.219248E+09 | 0.101171E+09 | 0.244582E+09 | 0.444471E+09 |
February | 0.310244E+09 | 0.209629E+09 | 0.100615E+09 | 0.240362E+09 | 0.328457E+09 |
March | 0.298959E+09 | 0.157481E+09 | 0.141478E+09 | 0.229614E+09 | 0.267472E+09 |
April | 0.260528E+09 | 0.121793E+09 | 0.138735E+09 | 0.197621E+09 | 0.196194E+09 |
May | 0.223012E+09 | 60435776.82 | 0.162576E+09 | 0.157862E+09 | 0.125043E+09 |
June | 0.209524E+09 | 42632042.87 | 0.166892E+09 | 0.176515E+09 | 83001051.80 |
July | 0.229186E+09 | 57717198.46 | 0.171469E+09 | 0.203663E+09 | 70450865.65 |
August | 0.258228E+09 | 92583616.90 | 0.165644E+09 | 0.251978E+09 | 84678696.57 |
September | 0.302924E+09 | 0.159644E+09 | 0.143280E+09 | 0.302143E+09 | 0.139273E+09 |
October | 0.326917E+09 | 0.205140E+09 | 0.121778E+09 | 0.308964E+09 | 0.211498E+09 |
November | 0.238598E+09 | 0.149360E+09 | 89237204.53 | 0.193409E+09 | 0.293002E+09 |
December | 0.262824E+09 | 0.199060E+09 | 63763438.80 | 0.227945E+09 | 0.412660E+09 |
Annual Sum or Average | 0.324136E+10 | 0.167472E+10 | 0.156664E+10 | 0.273466E+10 | 0.265620E+10 |
Minimum of Months | 0.209524E+09 | 42632042.87 | 63763438.80 | 0.157862E+09 | 70450865.65 |
Maximum of Months | 0.326917E+09 | 0.219248E+09 | 0.171469E+09 | 0.308964E+09 | 0.444471E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.320420E+09 | 0.219248E+09 | 0.101171E+09 | 0.244582E+09 | 0.444471E+09 |
February | 0.310244E+09 | 0.209629E+09 | 0.100615E+09 | 0.240362E+09 | 0.328457E+09 |
March | 0.298959E+09 | 0.157481E+09 | 0.141478E+09 | 0.229614E+09 | 0.267472E+09 |
April | 0.260528E+09 | 0.121793E+09 | 0.138735E+09 | 0.197621E+09 | 0.196194E+09 |
May | 0.223012E+09 | 60435776.82 | 0.162576E+09 | 0.157862E+09 | 0.125043E+09 |
June | 0.209524E+09 | 42632042.87 | 0.166892E+09 | 0.176515E+09 | 83001051.80 |
July | 0.229186E+09 | 57717198.46 | 0.171469E+09 | 0.203663E+09 | 70450865.65 |
August | 0.258228E+09 | 92583616.90 | 0.165644E+09 | 0.251978E+09 | 84678696.57 |
September | 0.302924E+09 | 0.159644E+09 | 0.143280E+09 | 0.302143E+09 | 0.139273E+09 |
October | 0.326917E+09 | 0.205140E+09 | 0.121778E+09 | 0.308964E+09 | 0.211498E+09 |
November | 0.238598E+09 | 0.149360E+09 | 89237204.53 | 0.193409E+09 | 0.293002E+09 |
December | 0.262824E+09 | 0.199060E+09 | 63763438.80 | 0.227945E+09 | 0.412660E+09 |
Annual Sum or Average | 0.324136E+10 | 0.167472E+10 | 0.156664E+10 | 0.273466E+10 | 0.265620E+10 |
Minimum of Months | 0.209524E+09 | 42632042.87 | 63763438.80 | 0.157862E+09 | 70450865.65 |
Maximum of Months | 0.326917E+09 | 0.219248E+09 | 0.171469E+09 | 0.308964E+09 | 0.444471E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_DOOR
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.385768E+09 | 0.263963E+09 | 0.121805E+09 | 0.295779E+09 | 0.528479E+09 |
February | 0.373517E+09 | 0.252382E+09 | 0.121136E+09 | 0.290500E+09 | 0.390579E+09 |
March | 0.359930E+09 | 0.189599E+09 | 0.170332E+09 | 0.277341E+09 | 0.318094E+09 |
April | 0.313661E+09 | 0.146632E+09 | 0.167029E+09 | 0.238318E+09 | 0.233553E+09 |
May | 0.268494E+09 | 72761494.47 | 0.195733E+09 | 0.190376E+09 | 0.149201E+09 |
June | 0.252256E+09 | 51326735.82 | 0.200929E+09 | 0.212303E+09 | 99176012.26 |
July | 0.275928E+09 | 69488469.20 | 0.206439E+09 | 0.244920E+09 | 84342273.11 |
August | 0.310893E+09 | 0.111466E+09 | 0.199427E+09 | 0.303070E+09 | 0.101250E+09 |
September | 0.364704E+09 | 0.192202E+09 | 0.172502E+09 | 0.363597E+09 | 0.166298E+09 |
October | 0.393591E+09 | 0.246977E+09 | 0.146614E+09 | 0.372415E+09 | 0.252077E+09 |
November | 0.287259E+09 | 0.179822E+09 | 0.107437E+09 | 0.233482E+09 | 0.348471E+09 |
December | 0.316426E+09 | 0.239658E+09 | 76767824.34 | 0.275119E+09 | 0.490911E+09 |
Annual Sum or Average | 0.390243E+10 | 0.201628E+10 | 0.188615E+10 | 0.329722E+10 | 0.316243E+10 |
Minimum of Months | 0.252256E+09 | 51326735.82 | 76767824.34 | 0.190376E+09 | 84342273.11 |
Maximum of Months | 0.393591E+09 | 0.263963E+09 | 0.206439E+09 | 0.372415E+09 | 0.528479E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.320420E+09 | 0.219248E+09 | 0.101171E+09 | 0.245381E+09 | 0.432032E+09 |
February | 0.310244E+09 | 0.209629E+09 | 0.100615E+09 | 0.241147E+09 | 0.318343E+09 |
March | 0.298959E+09 | 0.157481E+09 | 0.141478E+09 | 0.230619E+09 | 0.258438E+09 |
April | 0.260528E+09 | 0.121793E+09 | 0.138735E+09 | 0.198217E+09 | 0.189878E+09 |
May | 0.223012E+09 | 60435776.82 | 0.162576E+09 | 0.158193E+09 | 0.125336E+09 |
June | 0.209524E+09 | 42632042.87 | 0.166892E+09 | 0.175627E+09 | 86750752.73 |
July | 0.229186E+09 | 57717198.46 | 0.171469E+09 | 0.202486E+09 | 76233387.04 |
August | 0.258228E+09 | 92583616.90 | 0.165644E+09 | 0.251413E+09 | 89941218.20 |
September | 0.302924E+09 | 0.159644E+09 | 0.143280E+09 | 0.302087E+09 | 0.141472E+09 |
October | 0.326917E+09 | 0.205140E+09 | 0.121778E+09 | 0.310811E+09 | 0.203705E+09 |
November | 0.238598E+09 | 0.149360E+09 | 89237204.53 | 0.194404E+09 | 0.283351E+09 |
December | 0.262824E+09 | 0.199060E+09 | 63763438.80 | 0.228590E+09 | 0.401378E+09 |
Annual Sum or Average | 0.324136E+10 | 0.167472E+10 | 0.156664E+10 | 0.273897E+10 | 0.260686E+10 |
Minimum of Months | 0.209524E+09 | 42632042.87 | 63763438.80 | 0.158193E+09 | 76233387.04 |
Maximum of Months | 0.326917E+09 | 0.219248E+09 | 0.171469E+09 | 0.310811E+09 | 0.432032E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.320420E+09 | 0.219248E+09 | 0.101171E+09 | 0.245381E+09 | 0.432032E+09 |
February | 0.310244E+09 | 0.209629E+09 | 0.100615E+09 | 0.241147E+09 | 0.318343E+09 |
March | 0.298959E+09 | 0.157481E+09 | 0.141478E+09 | 0.230619E+09 | 0.258438E+09 |
April | 0.260528E+09 | 0.121793E+09 | 0.138735E+09 | 0.198217E+09 | 0.189878E+09 |
May | 0.223012E+09 | 60435776.82 | 0.162576E+09 | 0.158193E+09 | 0.125336E+09 |
June | 0.209524E+09 | 42632042.87 | 0.166892E+09 | 0.175627E+09 | 86750752.73 |
July | 0.229186E+09 | 57717198.46 | 0.171469E+09 | 0.202486E+09 | 76233387.04 |
August | 0.258228E+09 | 92583616.90 | 0.165644E+09 | 0.251413E+09 | 89941218.20 |
September | 0.302924E+09 | 0.159644E+09 | 0.143280E+09 | 0.302087E+09 | 0.141472E+09 |
October | 0.326917E+09 | 0.205140E+09 | 0.121778E+09 | 0.310811E+09 | 0.203705E+09 |
November | 0.238598E+09 | 0.149360E+09 | 89237204.53 | 0.194404E+09 | 0.283351E+09 |
December | 0.262824E+09 | 0.199060E+09 | 63763438.80 | 0.228590E+09 | 0.401378E+09 |
Annual Sum or Average | 0.324136E+10 | 0.167472E+10 | 0.156664E+10 | 0.273897E+10 | 0.260686E+10 |
Minimum of Months | 0.209524E+09 | 42632042.87 | 63763438.80 | 0.158193E+09 | 76233387.04 |
Maximum of Months | 0.326917E+09 | 0.219248E+09 | 0.171469E+09 | 0.310811E+09 | 0.432032E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_DOOR
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.383660E+09 | 0.262521E+09 | 0.121139E+09 | 0.295133E+09 | 0.510852E+09 |
February | 0.371476E+09 | 0.251003E+09 | 0.120474E+09 | 0.289869E+09 | 0.376476E+09 |
March | 0.357964E+09 | 0.188563E+09 | 0.169401E+09 | 0.277042E+09 | 0.305671E+09 |
April | 0.311947E+09 | 0.145831E+09 | 0.166116E+09 | 0.237746E+09 | 0.224792E+09 |
May | 0.267027E+09 | 72363890.67 | 0.194663E+09 | 0.189740E+09 | 0.148647E+09 |
June | 0.250877E+09 | 51046261.85 | 0.199831E+09 | 0.210110E+09 | 0.102983E+09 |
July | 0.274420E+09 | 69108750.79 | 0.205311E+09 | 0.242197E+09 | 90617520.69 |
August | 0.309194E+09 | 0.110857E+09 | 0.198337E+09 | 0.300746E+09 | 0.106817E+09 |
September | 0.362712E+09 | 0.191152E+09 | 0.171559E+09 | 0.361549E+09 | 0.167904E+09 |
October | 0.391441E+09 | 0.245628E+09 | 0.145813E+09 | 0.372591E+09 | 0.241468E+09 |
November | 0.285689E+09 | 0.178839E+09 | 0.106850E+09 | 0.233417E+09 | 0.335148E+09 |
December | 0.314697E+09 | 0.238348E+09 | 76348328.03 | 0.274403E+09 | 0.474861E+09 |
Annual Sum or Average | 0.388110E+10 | 0.200526E+10 | 0.187584E+10 | 0.328454E+10 | 0.308624E+10 |
Minimum of Months | 0.250877E+09 | 51046261.85 | 76348328.03 | 0.189740E+09 | 90617520.69 |
Maximum of Months | 0.391441E+09 | 0.262521E+09 | 0.205311E+09 | 0.372591E+09 | 0.510852E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.320420E+09 | 0.219248E+09 | 0.101171E+09 | 0.245757E+09 | 0.428280E+09 |
February | 0.310244E+09 | 0.209629E+09 | 0.100615E+09 | 0.241533E+09 | 0.315214E+09 |
March | 0.298959E+09 | 0.157481E+09 | 0.141478E+09 | 0.231242E+09 | 0.254963E+09 |
April | 0.260528E+09 | 0.121793E+09 | 0.138735E+09 | 0.198758E+09 | 0.186978E+09 |
May | 0.223012E+09 | 60435776.82 | 0.162576E+09 | 0.158699E+09 | 0.123860E+09 |
June | 0.209524E+09 | 42632042.87 | 0.166892E+09 | 0.175745E+09 | 86378827.35 |
July | 0.229186E+09 | 57717198.46 | 0.171469E+09 | 0.202439E+09 | 76395803.91 |
August | 0.258228E+09 | 92583616.90 | 0.165644E+09 | 0.251409E+09 | 89976006.22 |
September | 0.302924E+09 | 0.159644E+09 | 0.143280E+09 | 0.302311E+09 | 0.140542E+09 |
October | 0.326917E+09 | 0.205140E+09 | 0.121778E+09 | 0.311905E+09 | 0.200009E+09 |
November | 0.238598E+09 | 0.149360E+09 | 89237204.53 | 0.195030E+09 | 0.279500E+09 |
December | 0.262824E+09 | 0.199060E+09 | 63763438.80 | 0.228938E+09 | 0.397740E+09 |
Annual Sum or Average | 0.324136E+10 | 0.167472E+10 | 0.156664E+10 | 0.274377E+10 | 0.257984E+10 |
Minimum of Months | 0.209524E+09 | 42632042.87 | 63763438.80 | 0.158699E+09 | 76395803.91 |
Maximum of Months | 0.326917E+09 | 0.219248E+09 | 0.171469E+09 | 0.311905E+09 | 0.428280E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.320420E+09 | 0.219248E+09 | 0.101171E+09 | 0.245757E+09 | 0.428280E+09 |
February | 0.310244E+09 | 0.209629E+09 | 0.100615E+09 | 0.241533E+09 | 0.315214E+09 |
March | 0.298959E+09 | 0.157481E+09 | 0.141478E+09 | 0.231242E+09 | 0.254963E+09 |
April | 0.260528E+09 | 0.121793E+09 | 0.138735E+09 | 0.198758E+09 | 0.186978E+09 |
May | 0.223012E+09 | 60435776.82 | 0.162576E+09 | 0.158699E+09 | 0.123860E+09 |
June | 0.209524E+09 | 42632042.87 | 0.166892E+09 | 0.175745E+09 | 86378827.35 |
July | 0.229186E+09 | 57717198.46 | 0.171469E+09 | 0.202439E+09 | 76395803.91 |
August | 0.258228E+09 | 92583616.90 | 0.165644E+09 | 0.251409E+09 | 89976006.22 |
September | 0.302924E+09 | 0.159644E+09 | 0.143280E+09 | 0.302311E+09 | 0.140542E+09 |
October | 0.326917E+09 | 0.205140E+09 | 0.121778E+09 | 0.311905E+09 | 0.200009E+09 |
November | 0.238598E+09 | 0.149360E+09 | 89237204.53 | 0.195030E+09 | 0.279500E+09 |
December | 0.262824E+09 | 0.199060E+09 | 63763438.80 | 0.228938E+09 | 0.397740E+09 |
Annual Sum or Average | 0.324136E+10 | 0.167472E+10 | 0.156664E+10 | 0.274377E+10 | 0.257984E+10 |
Minimum of Months | 0.209524E+09 | 42632042.87 | 63763438.80 | 0.158699E+09 | 76395803.91 |
Maximum of Months | 0.326917E+09 | 0.219248E+09 | 0.171469E+09 | 0.311905E+09 | 0.428280E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_DOOR
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.383660E+09 | 0.262521E+09 | 0.121139E+09 | 0.295592E+09 | 0.506377E+09 |
February | 0.371476E+09 | 0.251003E+09 | 0.120474E+09 | 0.290341E+09 | 0.372750E+09 |
March | 0.357964E+09 | 0.188563E+09 | 0.169401E+09 | 0.277795E+09 | 0.301539E+09 |
April | 0.311947E+09 | 0.145831E+09 | 0.166116E+09 | 0.238397E+09 | 0.221347E+09 |
May | 0.267027E+09 | 72363890.67 | 0.194663E+09 | 0.190348E+09 | 0.146896E+09 |
June | 0.250877E+09 | 51046261.85 | 0.199831E+09 | 0.210251E+09 | 0.102542E+09 |
July | 0.274420E+09 | 69108750.79 | 0.205311E+09 | 0.242141E+09 | 90809578.92 |
August | 0.309194E+09 | 0.110857E+09 | 0.198337E+09 | 0.300740E+09 | 0.106858E+09 |
September | 0.362712E+09 | 0.191152E+09 | 0.171559E+09 | 0.361818E+09 | 0.166801E+09 |
October | 0.391441E+09 | 0.245628E+09 | 0.145813E+09 | 0.373903E+09 | 0.237084E+09 |
November | 0.285689E+09 | 0.178839E+09 | 0.106850E+09 | 0.234174E+09 | 0.330570E+09 |
December | 0.314697E+09 | 0.238348E+09 | 76348328.03 | 0.274827E+09 | 0.470522E+09 |
Annual Sum or Average | 0.388110E+10 | 0.200526E+10 | 0.187584E+10 | 0.329033E+10 | 0.305410E+10 |
Minimum of Months | 0.250877E+09 | 51046261.85 | 76348328.03 | 0.190348E+09 | 90809578.92 |
Maximum of Months | 0.391441E+09 | 0.262521E+09 | 0.205311E+09 | 0.373903E+09 | 0.506377E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.320420E+09 | 0.219248E+09 | 0.101171E+09 | 0.246204E+09 | 0.425781E+09 |
February | 0.310244E+09 | 0.209629E+09 | 0.100615E+09 | 0.242009E+09 | 0.312942E+09 |
March | 0.298959E+09 | 0.157481E+09 | 0.141478E+09 | 0.231999E+09 | 0.252106E+09 |
April | 0.260528E+09 | 0.121793E+09 | 0.138735E+09 | 0.199505E+09 | 0.184352E+09 |
May | 0.223012E+09 | 60435776.82 | 0.162576E+09 | 0.159721E+09 | 0.121819E+09 |
June | 0.209524E+09 | 42632042.87 | 0.166892E+09 | 0.176409E+09 | 84929182.02 |
July | 0.229186E+09 | 57717198.46 | 0.171469E+09 | 0.202840E+09 | 75433340.70 |
August | 0.258228E+09 | 92583616.90 | 0.165644E+09 | 0.251777E+09 | 88955187.54 |
September | 0.302924E+09 | 0.159644E+09 | 0.143280E+09 | 0.302891E+09 | 0.138758E+09 |
October | 0.326917E+09 | 0.205140E+09 | 0.121778E+09 | 0.313124E+09 | 0.196878E+09 |
November | 0.238598E+09 | 0.149360E+09 | 89237204.53 | 0.195823E+09 | 0.276141E+09 |
December | 0.262824E+09 | 0.199060E+09 | 63763438.80 | 0.229364E+09 | 0.394974E+09 |
Annual Sum or Average | 0.324136E+10 | 0.167472E+10 | 0.156664E+10 | 0.275166E+10 | 0.255307E+10 |
Minimum of Months | 0.209524E+09 | 42632042.87 | 63763438.80 | 0.159721E+09 | 75433340.70 |
Maximum of Months | 0.326917E+09 | 0.219248E+09 | 0.171469E+09 | 0.313124E+09 | 0.425781E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.320420E+09 | 0.219248E+09 | 0.101171E+09 | 0.246204E+09 | 0.425781E+09 |
February | 0.310244E+09 | 0.209629E+09 | 0.100615E+09 | 0.242009E+09 | 0.312942E+09 |
March | 0.298959E+09 | 0.157481E+09 | 0.141478E+09 | 0.231999E+09 | 0.252106E+09 |
April | 0.260528E+09 | 0.121793E+09 | 0.138735E+09 | 0.199505E+09 | 0.184352E+09 |
May | 0.223012E+09 | 60435776.82 | 0.162576E+09 | 0.159721E+09 | 0.121819E+09 |
June | 0.209524E+09 | 42632042.87 | 0.166892E+09 | 0.176409E+09 | 84929182.02 |
July | 0.229186E+09 | 57717198.46 | 0.171469E+09 | 0.202840E+09 | 75433340.70 |
August | 0.258228E+09 | 92583616.90 | 0.165644E+09 | 0.251777E+09 | 88955187.54 |
September | 0.302924E+09 | 0.159644E+09 | 0.143280E+09 | 0.302891E+09 | 0.138758E+09 |
October | 0.326917E+09 | 0.205140E+09 | 0.121778E+09 | 0.313124E+09 | 0.196878E+09 |
November | 0.238598E+09 | 0.149360E+09 | 89237204.53 | 0.195823E+09 | 0.276141E+09 |
December | 0.262824E+09 | 0.199060E+09 | 63763438.80 | 0.229364E+09 | 0.394974E+09 |
Annual Sum or Average | 0.324136E+10 | 0.167472E+10 | 0.156664E+10 | 0.275166E+10 | 0.255307E+10 |
Minimum of Months | 0.209524E+09 | 42632042.87 | 63763438.80 | 0.159721E+09 | 75433340.70 |
Maximum of Months | 0.326917E+09 | 0.219248E+09 | 0.171469E+09 | 0.313124E+09 | 0.425781E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_DOOR
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.383660E+09 | 0.262521E+09 | 0.121139E+09 | 0.296136E+09 | 0.503392E+09 |
February | 0.371476E+09 | 0.251003E+09 | 0.120474E+09 | 0.290923E+09 | 0.370043E+09 |
March | 0.357964E+09 | 0.188563E+09 | 0.169401E+09 | 0.278712E+09 | 0.298145E+09 |
April | 0.311947E+09 | 0.145831E+09 | 0.166116E+09 | 0.239297E+09 | 0.218228E+09 |
May | 0.267027E+09 | 72363890.67 | 0.194663E+09 | 0.191578E+09 | 0.144483E+09 |
June | 0.250877E+09 | 51046261.85 | 0.199831E+09 | 0.211053E+09 | 0.100829E+09 |
July | 0.274420E+09 | 69108750.79 | 0.205311E+09 | 0.242625E+09 | 89672955.62 |
August | 0.309194E+09 | 0.110857E+09 | 0.198337E+09 | 0.301185E+09 | 0.105653E+09 |
September | 0.362712E+09 | 0.191152E+09 | 0.171559E+09 | 0.362515E+09 | 0.164691E+09 |
October | 0.391441E+09 | 0.245628E+09 | 0.145813E+09 | 0.375361E+09 | 0.233373E+09 |
November | 0.285689E+09 | 0.178839E+09 | 0.106850E+09 | 0.235130E+09 | 0.326579E+09 |
December | 0.314697E+09 | 0.238348E+09 | 76348328.03 | 0.275344E+09 | 0.467221E+09 |
Annual Sum or Average | 0.388110E+10 | 0.200526E+10 | 0.187584E+10 | 0.329986E+10 | 0.302231E+10 |
Minimum of Months | 0.250877E+09 | 51046261.85 | 76348328.03 | 0.191578E+09 | 89672955.62 |
Maximum of Months | 0.391441E+09 | 0.262521E+09 | 0.205311E+09 | 0.375361E+09 | 0.503392E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.320420E+09 | 0.219248E+09 | 0.101171E+09 | 0.248962E+09 | 0.414778E+09 |
February | 0.310244E+09 | 0.209629E+09 | 0.100615E+09 | 0.244780E+09 | 0.303583E+09 |
March | 0.298959E+09 | 0.157481E+09 | 0.141478E+09 | 0.235053E+09 | 0.242234E+09 |
April | 0.260528E+09 | 0.121793E+09 | 0.138735E+09 | 0.201778E+09 | 0.176437E+09 |
May | 0.223012E+09 | 60435776.82 | 0.162576E+09 | 0.162491E+09 | 0.115951E+09 |
June | 0.209524E+09 | 42632042.87 | 0.166892E+09 | 0.177651E+09 | 80306602.38 |
July | 0.229186E+09 | 57717198.46 | 0.171469E+09 | 0.203215E+09 | 71932956.42 |
August | 0.258228E+09 | 92583616.90 | 0.165644E+09 | 0.252286E+09 | 85126056.53 |
September | 0.302924E+09 | 0.159644E+09 | 0.143280E+09 | 0.304156E+09 | 0.133649E+09 |
October | 0.326917E+09 | 0.205140E+09 | 0.121778E+09 | 0.316512E+09 | 0.189384E+09 |
November | 0.238598E+09 | 0.149360E+09 | 89237204.53 | 0.198662E+09 | 0.265671E+09 |
December | 0.262824E+09 | 0.199060E+09 | 63763438.80 | 0.231761E+09 | 0.383635E+09 |
Annual Sum or Average | 0.324136E+10 | 0.167472E+10 | 0.156664E+10 | 0.277731E+10 | 0.246269E+10 |
Minimum of Months | 0.209524E+09 | 42632042.87 | 63763438.80 | 0.162491E+09 | 71932956.42 |
Maximum of Months | 0.326917E+09 | 0.219248E+09 | 0.171469E+09 | 0.316512E+09 | 0.414778E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.320420E+09 | 0.219248E+09 | 0.101171E+09 | 0.248962E+09 | 0.414778E+09 |
February | 0.310244E+09 | 0.209629E+09 | 0.100615E+09 | 0.244780E+09 | 0.303583E+09 |
March | 0.298959E+09 | 0.157481E+09 | 0.141478E+09 | 0.235053E+09 | 0.242234E+09 |
April | 0.260528E+09 | 0.121793E+09 | 0.138735E+09 | 0.201778E+09 | 0.176437E+09 |
May | 0.223012E+09 | 60435776.82 | 0.162576E+09 | 0.162491E+09 | 0.115951E+09 |
June | 0.209524E+09 | 42632042.87 | 0.166892E+09 | 0.177651E+09 | 80306602.38 |
July | 0.229186E+09 | 57717198.46 | 0.171469E+09 | 0.203215E+09 | 71932956.42 |
August | 0.258228E+09 | 92583616.90 | 0.165644E+09 | 0.252286E+09 | 85126056.53 |
September | 0.302924E+09 | 0.159644E+09 | 0.143280E+09 | 0.304156E+09 | 0.133649E+09 |
October | 0.326917E+09 | 0.205140E+09 | 0.121778E+09 | 0.316512E+09 | 0.189384E+09 |
November | 0.238598E+09 | 0.149360E+09 | 89237204.53 | 0.198662E+09 | 0.265671E+09 |
December | 0.262824E+09 | 0.199060E+09 | 63763438.80 | 0.231761E+09 | 0.383635E+09 |
Annual Sum or Average | 0.324136E+10 | 0.167472E+10 | 0.156664E+10 | 0.277731E+10 | 0.246269E+10 |
Minimum of Months | 0.209524E+09 | 42632042.87 | 63763438.80 | 0.162491E+09 | 71932956.42 |
Maximum of Months | 0.326917E+09 | 0.219248E+09 | 0.171469E+09 | 0.316512E+09 | 0.414778E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_3
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.320420E+09 | 0.219248E+09 | 0.101171E+09 | 0.248962E+09 | 0.414778E+09 |
February | 0.310244E+09 | 0.209629E+09 | 0.100615E+09 | 0.244780E+09 | 0.303583E+09 |
March | 0.298959E+09 | 0.157481E+09 | 0.141478E+09 | 0.235053E+09 | 0.242234E+09 |
April | 0.260528E+09 | 0.121793E+09 | 0.138735E+09 | 0.201778E+09 | 0.176437E+09 |
May | 0.223012E+09 | 60435776.82 | 0.162576E+09 | 0.162491E+09 | 0.115951E+09 |
June | 0.209524E+09 | 42632042.87 | 0.166892E+09 | 0.177651E+09 | 80306602.38 |
July | 0.229186E+09 | 57717198.46 | 0.171469E+09 | 0.203215E+09 | 71932956.42 |
August | 0.258228E+09 | 92583616.90 | 0.165644E+09 | 0.252286E+09 | 85126056.53 |
September | 0.302924E+09 | 0.159644E+09 | 0.143280E+09 | 0.304156E+09 | 0.133649E+09 |
October | 0.326917E+09 | 0.205140E+09 | 0.121778E+09 | 0.316512E+09 | 0.189384E+09 |
November | 0.238598E+09 | 0.149360E+09 | 89237204.53 | 0.198662E+09 | 0.265671E+09 |
December | 0.262824E+09 | 0.199060E+09 | 63763438.80 | 0.231761E+09 | 0.383635E+09 |
Annual Sum or Average | 0.324136E+10 | 0.167472E+10 | 0.156664E+10 | 0.277731E+10 | 0.246269E+10 |
Minimum of Months | 0.209524E+09 | 42632042.87 | 63763438.80 | 0.162491E+09 | 71932956.42 |
Maximum of Months | 0.326917E+09 | 0.219248E+09 | 0.171469E+09 | 0.316512E+09 | 0.414778E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_4
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.320420E+09 | 0.219248E+09 | 0.101171E+09 | 0.248962E+09 | 0.414778E+09 |
February | 0.310244E+09 | 0.209629E+09 | 0.100615E+09 | 0.244780E+09 | 0.303583E+09 |
March | 0.298959E+09 | 0.157481E+09 | 0.141478E+09 | 0.235053E+09 | 0.242234E+09 |
April | 0.260528E+09 | 0.121793E+09 | 0.138735E+09 | 0.201778E+09 | 0.176437E+09 |
May | 0.223012E+09 | 60435776.82 | 0.162576E+09 | 0.162491E+09 | 0.115951E+09 |
June | 0.209524E+09 | 42632042.87 | 0.166892E+09 | 0.177651E+09 | 80306602.38 |
July | 0.229186E+09 | 57717198.46 | 0.171469E+09 | 0.203215E+09 | 71932956.42 |
August | 0.258228E+09 | 92583616.90 | 0.165644E+09 | 0.252286E+09 | 85126056.53 |
September | 0.302924E+09 | 0.159644E+09 | 0.143280E+09 | 0.304156E+09 | 0.133649E+09 |
October | 0.326917E+09 | 0.205140E+09 | 0.121778E+09 | 0.316512E+09 | 0.189384E+09 |
November | 0.238598E+09 | 0.149360E+09 | 89237204.53 | 0.198662E+09 | 0.265671E+09 |
December | 0.262824E+09 | 0.199060E+09 | 63763438.80 | 0.231761E+09 | 0.383635E+09 |
Annual Sum or Average | 0.324136E+10 | 0.167472E+10 | 0.156664E+10 | 0.277731E+10 | 0.246269E+10 |
Minimum of Months | 0.209524E+09 | 42632042.87 | 63763438.80 | 0.162491E+09 | 71932956.42 |
Maximum of Months | 0.326917E+09 | 0.219248E+09 | 0.171469E+09 | 0.316512E+09 | 0.414778E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_DOOR_1
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.383660E+09 | 0.262521E+09 | 0.121139E+09 | 0.299426E+09 | 0.490470E+09 |
February | 0.371476E+09 | 0.251003E+09 | 0.120474E+09 | 0.294228E+09 | 0.359045E+09 |
March | 0.357964E+09 | 0.188563E+09 | 0.169401E+09 | 0.282369E+09 | 0.286536E+09 |
April | 0.311947E+09 | 0.145831E+09 | 0.166116E+09 | 0.242029E+09 | 0.208894E+09 |
May | 0.267027E+09 | 72363890.67 | 0.194663E+09 | 0.194906E+09 | 0.137566E+09 |
June | 0.250877E+09 | 51046261.85 | 0.199831E+09 | 0.212574E+09 | 95374975.17 |
July | 0.274420E+09 | 69108750.79 | 0.205311E+09 | 0.243119E+09 | 85539977.39 |
August | 0.309194E+09 | 0.110857E+09 | 0.198337E+09 | 0.301826E+09 | 0.101140E+09 |
September | 0.362712E+09 | 0.191152E+09 | 0.171559E+09 | 0.364043E+09 | 0.158663E+09 |
October | 0.391441E+09 | 0.245628E+09 | 0.145813E+09 | 0.379390E+09 | 0.224547E+09 |
November | 0.285689E+09 | 0.178839E+09 | 0.106850E+09 | 0.238528E+09 | 0.314270E+09 |
December | 0.314697E+09 | 0.238348E+09 | 76348328.03 | 0.278196E+09 | 0.453867E+09 |
Annual Sum or Average | 0.388110E+10 | 0.200526E+10 | 0.187584E+10 | 0.333063E+10 | 0.291591E+10 |
Minimum of Months | 0.250877E+09 | 51046261.85 | 76348328.03 | 0.194906E+09 | 85539977.39 |
Maximum of Months | 0.391441E+09 | 0.262521E+09 | 0.205311E+09 | 0.379390E+09 | 0.490470E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_DOOR_2
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.383660E+09 | 0.262521E+09 | 0.121139E+09 | 0.299426E+09 | 0.490470E+09 |
February | 0.371476E+09 | 0.251003E+09 | 0.120474E+09 | 0.294228E+09 | 0.359045E+09 |
March | 0.357964E+09 | 0.188563E+09 | 0.169401E+09 | 0.282369E+09 | 0.286536E+09 |
April | 0.311947E+09 | 0.145831E+09 | 0.166116E+09 | 0.242029E+09 | 0.208894E+09 |
May | 0.267027E+09 | 72363890.67 | 0.194663E+09 | 0.194906E+09 | 0.137566E+09 |
June | 0.250877E+09 | 51046261.85 | 0.199831E+09 | 0.212574E+09 | 95374975.17 |
July | 0.274420E+09 | 69108750.79 | 0.205311E+09 | 0.243119E+09 | 85539977.39 |
August | 0.309194E+09 | 0.110857E+09 | 0.198337E+09 | 0.301826E+09 | 0.101140E+09 |
September | 0.362712E+09 | 0.191152E+09 | 0.171559E+09 | 0.364043E+09 | 0.158663E+09 |
October | 0.391441E+09 | 0.245628E+09 | 0.145813E+09 | 0.379390E+09 | 0.224547E+09 |
November | 0.285689E+09 | 0.178839E+09 | 0.106850E+09 | 0.238528E+09 | 0.314270E+09 |
December | 0.314697E+09 | 0.238348E+09 | 76348328.03 | 0.278196E+09 | 0.453867E+09 |
Annual Sum or Average | 0.388110E+10 | 0.200526E+10 | 0.187584E+10 | 0.333063E+10 | 0.291591E+10 |
Minimum of Months | 0.250877E+09 | 51046261.85 | 76348328.03 | 0.194906E+09 | 85539977.39 |
Maximum of Months | 0.391441E+09 | 0.262521E+09 | 0.205311E+09 | 0.379390E+09 | 0.490470E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.320420E+09 | 0.219248E+09 | 0.101171E+09 | 0.247546E+09 | 0.417957E+09 |
February | 0.310244E+09 | 0.209629E+09 | 0.100615E+09 | 0.243570E+09 | 0.305714E+09 |
March | 0.298959E+09 | 0.157481E+09 | 0.141478E+09 | 0.234131E+09 | 0.243650E+09 |
April | 0.260528E+09 | 0.121793E+09 | 0.138735E+09 | 0.201638E+09 | 0.176785E+09 |
May | 0.223012E+09 | 60435776.82 | 0.162576E+09 | 0.162924E+09 | 0.115278E+09 |
June | 0.209524E+09 | 42632042.87 | 0.166892E+09 | 0.178404E+09 | 79391685.08 |
July | 0.229186E+09 | 57717198.46 | 0.171469E+09 | 0.203946E+09 | 71012027.29 |
August | 0.258228E+09 | 92583616.90 | 0.165644E+09 | 0.252765E+09 | 84302203.25 |
September | 0.302924E+09 | 0.159644E+09 | 0.143280E+09 | 0.304270E+09 | 0.133079E+09 |
October | 0.326917E+09 | 0.205140E+09 | 0.121778E+09 | 0.316018E+09 | 0.189320E+09 |
November | 0.238598E+09 | 0.149360E+09 | 89237204.53 | 0.198008E+09 | 0.267053E+09 |
December | 0.262824E+09 | 0.199060E+09 | 63763438.80 | 0.230811E+09 | 0.386556E+09 |
Annual Sum or Average | 0.324136E+10 | 0.167472E+10 | 0.156664E+10 | 0.277403E+10 | 0.247010E+10 |
Minimum of Months | 0.209524E+09 | 42632042.87 | 63763438.80 | 0.162924E+09 | 71012027.29 |
Maximum of Months | 0.326917E+09 | 0.219248E+09 | 0.171469E+09 | 0.316018E+09 | 0.417957E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.320420E+09 | 0.219248E+09 | 0.101171E+09 | 0.247546E+09 | 0.417957E+09 |
February | 0.310244E+09 | 0.209629E+09 | 0.100615E+09 | 0.243570E+09 | 0.305714E+09 |
March | 0.298959E+09 | 0.157481E+09 | 0.141478E+09 | 0.234131E+09 | 0.243650E+09 |
April | 0.260528E+09 | 0.121793E+09 | 0.138735E+09 | 0.201638E+09 | 0.176785E+09 |
May | 0.223012E+09 | 60435776.82 | 0.162576E+09 | 0.162924E+09 | 0.115278E+09 |
June | 0.209524E+09 | 42632042.87 | 0.166892E+09 | 0.178404E+09 | 79391685.08 |
July | 0.229186E+09 | 57717198.46 | 0.171469E+09 | 0.203946E+09 | 71012027.29 |
August | 0.258228E+09 | 92583616.90 | 0.165644E+09 | 0.252765E+09 | 84302203.25 |
September | 0.302924E+09 | 0.159644E+09 | 0.143280E+09 | 0.304270E+09 | 0.133079E+09 |
October | 0.326917E+09 | 0.205140E+09 | 0.121778E+09 | 0.316018E+09 | 0.189320E+09 |
November | 0.238598E+09 | 0.149360E+09 | 89237204.53 | 0.198008E+09 | 0.267053E+09 |
December | 0.262824E+09 | 0.199060E+09 | 63763438.80 | 0.230811E+09 | 0.386556E+09 |
Annual Sum or Average | 0.324136E+10 | 0.167472E+10 | 0.156664E+10 | 0.277403E+10 | 0.247010E+10 |
Minimum of Months | 0.209524E+09 | 42632042.87 | 63763438.80 | 0.162924E+09 | 71012027.29 |
Maximum of Months | 0.326917E+09 | 0.219248E+09 | 0.171469E+09 | 0.316018E+09 | 0.417957E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_DOOR
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.383660E+09 | 0.262521E+09 | 0.121139E+09 | 0.297800E+09 | 0.494087E+09 |
February | 0.371476E+09 | 0.251003E+09 | 0.120474E+09 | 0.292847E+09 | 0.361455E+09 |
March | 0.357964E+09 | 0.188563E+09 | 0.169401E+09 | 0.281322E+09 | 0.288107E+09 |
April | 0.311947E+09 | 0.145831E+09 | 0.166116E+09 | 0.241889E+09 | 0.209234E+09 |
May | 0.267027E+09 | 72363890.67 | 0.194663E+09 | 0.195453E+09 | 0.136730E+09 |
June | 0.250877E+09 | 51046261.85 | 0.199831E+09 | 0.213487E+09 | 94269862.98 |
July | 0.274420E+09 | 69108750.79 | 0.205311E+09 | 0.244006E+09 | 84436235.58 |
August | 0.309194E+09 | 0.110857E+09 | 0.198337E+09 | 0.302422E+09 | 0.100141E+09 |
September | 0.362712E+09 | 0.191152E+09 | 0.171559E+09 | 0.364212E+09 | 0.157949E+09 |
October | 0.391441E+09 | 0.245628E+09 | 0.145813E+09 | 0.378858E+09 | 0.224403E+09 |
November | 0.285689E+09 | 0.178839E+09 | 0.106850E+09 | 0.237790E+09 | 0.315789E+09 |
December | 0.314697E+09 | 0.238348E+09 | 76348328.03 | 0.277110E+09 | 0.457194E+09 |
Annual Sum or Average | 0.388110E+10 | 0.200526E+10 | 0.187584E+10 | 0.332720E+10 | 0.292380E+10 |
Minimum of Months | 0.250877E+09 | 51046261.85 | 76348328.03 | 0.195453E+09 | 84436235.58 |
Maximum of Months | 0.391441E+09 | 0.262521E+09 | 0.205311E+09 | 0.378858E+09 | 0.494087E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.320420E+09 | 0.219248E+09 | 0.101171E+09 | 0.247606E+09 | 0.417649E+09 |
February | 0.310244E+09 | 0.209629E+09 | 0.100615E+09 | 0.243667E+09 | 0.305212E+09 |
March | 0.298959E+09 | 0.157481E+09 | 0.141478E+09 | 0.234372E+09 | 0.242798E+09 |
April | 0.260528E+09 | 0.121793E+09 | 0.138735E+09 | 0.201996E+09 | 0.175655E+09 |
May | 0.223012E+09 | 60435776.82 | 0.162576E+09 | 0.163800E+09 | 0.113906E+09 |
June | 0.209524E+09 | 42632042.87 | 0.166892E+09 | 0.178876E+09 | 78634472.80 |
July | 0.229186E+09 | 57717198.46 | 0.171469E+09 | 0.204242E+09 | 70557018.54 |
August | 0.258228E+09 | 92583616.90 | 0.165644E+09 | 0.253015E+09 | 83839735.60 |
September | 0.302924E+09 | 0.159644E+09 | 0.143280E+09 | 0.304564E+09 | 0.132310E+09 |
October | 0.326917E+09 | 0.205140E+09 | 0.121778E+09 | 0.316407E+09 | 0.188297E+09 |
November | 0.238598E+09 | 0.149360E+09 | 89237204.53 | 0.198254E+09 | 0.266116E+09 |
December | 0.262824E+09 | 0.199060E+09 | 63763438.80 | 0.230900E+09 | 0.386039E+09 |
Annual Sum or Average | 0.324136E+10 | 0.167472E+10 | 0.156664E+10 | 0.277770E+10 | 0.246101E+10 |
Minimum of Months | 0.209524E+09 | 42632042.87 | 63763438.80 | 0.163800E+09 | 70557018.54 |
Maximum of Months | 0.326917E+09 | 0.219248E+09 | 0.171469E+09 | 0.316407E+09 | 0.417649E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.320420E+09 | 0.219248E+09 | 0.101171E+09 | 0.247606E+09 | 0.417649E+09 |
February | 0.310244E+09 | 0.209629E+09 | 0.100615E+09 | 0.243667E+09 | 0.305212E+09 |
March | 0.298959E+09 | 0.157481E+09 | 0.141478E+09 | 0.234372E+09 | 0.242798E+09 |
April | 0.260528E+09 | 0.121793E+09 | 0.138735E+09 | 0.201996E+09 | 0.175655E+09 |
May | 0.223012E+09 | 60435776.82 | 0.162576E+09 | 0.163800E+09 | 0.113906E+09 |
June | 0.209524E+09 | 42632042.87 | 0.166892E+09 | 0.178876E+09 | 78634472.80 |
July | 0.229186E+09 | 57717198.46 | 0.171469E+09 | 0.204242E+09 | 70557018.54 |
August | 0.258228E+09 | 92583616.90 | 0.165644E+09 | 0.253015E+09 | 83839735.60 |
September | 0.302924E+09 | 0.159644E+09 | 0.143280E+09 | 0.304564E+09 | 0.132310E+09 |
October | 0.326917E+09 | 0.205140E+09 | 0.121778E+09 | 0.316407E+09 | 0.188297E+09 |
November | 0.238598E+09 | 0.149360E+09 | 89237204.53 | 0.198254E+09 | 0.266116E+09 |
December | 0.262824E+09 | 0.199060E+09 | 63763438.80 | 0.230900E+09 | 0.386039E+09 |
Annual Sum or Average | 0.324136E+10 | 0.167472E+10 | 0.156664E+10 | 0.277770E+10 | 0.246101E+10 |
Minimum of Months | 0.209524E+09 | 42632042.87 | 63763438.80 | 0.163800E+09 | 70557018.54 |
Maximum of Months | 0.326917E+09 | 0.219248E+09 | 0.171469E+09 | 0.316407E+09 | 0.417649E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_DOOR
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.383660E+09 | 0.262521E+09 | 0.121139E+09 | 0.297873E+09 | 0.493719E+09 |
February | 0.371476E+09 | 0.251003E+09 | 0.120474E+09 | 0.292964E+09 | 0.360856E+09 |
March | 0.357964E+09 | 0.188563E+09 | 0.169401E+09 | 0.281616E+09 | 0.287095E+09 |
April | 0.311947E+09 | 0.145831E+09 | 0.166116E+09 | 0.242321E+09 | 0.207891E+09 |
May | 0.267027E+09 | 72363890.67 | 0.194663E+09 | 0.196503E+09 | 0.135102E+09 |
June | 0.250877E+09 | 51046261.85 | 0.199831E+09 | 0.214054E+09 | 93372744.87 |
July | 0.274420E+09 | 69108750.79 | 0.205311E+09 | 0.244362E+09 | 83896312.33 |
August | 0.309194E+09 | 0.110857E+09 | 0.198337E+09 | 0.302724E+09 | 99593413.76 |
September | 0.362712E+09 | 0.191152E+09 | 0.171559E+09 | 0.364566E+09 | 0.157038E+09 |
October | 0.391441E+09 | 0.245628E+09 | 0.145813E+09 | 0.379327E+09 | 0.223189E+09 |
November | 0.285689E+09 | 0.178839E+09 | 0.106850E+09 | 0.238087E+09 | 0.314675E+09 |
December | 0.314697E+09 | 0.238348E+09 | 76348328.03 | 0.277219E+09 | 0.456576E+09 |
Annual Sum or Average | 0.388110E+10 | 0.200526E+10 | 0.187584E+10 | 0.333162E+10 | 0.291300E+10 |
Minimum of Months | 0.250877E+09 | 51046261.85 | 76348328.03 | 0.196503E+09 | 83896312.33 |
Maximum of Months | 0.391441E+09 | 0.262521E+09 | 0.205311E+09 | 0.379327E+09 | 0.493719E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.320420E+09 | 0.219248E+09 | 0.101171E+09 | 0.247907E+09 | 0.415693E+09 |
February | 0.310244E+09 | 0.209629E+09 | 0.100615E+09 | 0.244063E+09 | 0.302771E+09 |
March | 0.298959E+09 | 0.157481E+09 | 0.141478E+09 | 0.235154E+09 | 0.239282E+09 |
April | 0.260528E+09 | 0.121793E+09 | 0.138735E+09 | 0.203023E+09 | 0.171693E+09 |
May | 0.223012E+09 | 60435776.82 | 0.162576E+09 | 0.166062E+09 | 0.110087E+09 |
June | 0.209524E+09 | 42632042.87 | 0.166892E+09 | 0.179903E+09 | 76724621.64 |
July | 0.229186E+09 | 57717198.46 | 0.171469E+09 | 0.204792E+09 | 69478562.08 |
August | 0.258228E+09 | 92583616.90 | 0.165644E+09 | 0.253449E+09 | 82767711.63 |
September | 0.302924E+09 | 0.159644E+09 | 0.143280E+09 | 0.305193E+09 | 0.130354E+09 |
October | 0.326917E+09 | 0.205140E+09 | 0.121778E+09 | 0.317317E+09 | 0.185420E+09 |
November | 0.238598E+09 | 0.149360E+09 | 89237204.53 | 0.198873E+09 | 0.263146E+09 |
December | 0.262824E+09 | 0.199060E+09 | 63763438.80 | 0.231264E+09 | 0.383300E+09 |
Annual Sum or Average | 0.324136E+10 | 0.167472E+10 | 0.156664E+10 | 0.278700E+10 | 0.243072E+10 |
Minimum of Months | 0.209524E+09 | 42632042.87 | 63763438.80 | 0.166062E+09 | 69478562.08 |
Maximum of Months | 0.326917E+09 | 0.219248E+09 | 0.171469E+09 | 0.317317E+09 | 0.415693E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.320420E+09 | 0.219248E+09 | 0.101171E+09 | 0.247907E+09 | 0.415693E+09 |
February | 0.310244E+09 | 0.209629E+09 | 0.100615E+09 | 0.244063E+09 | 0.302771E+09 |
March | 0.298959E+09 | 0.157481E+09 | 0.141478E+09 | 0.235154E+09 | 0.239282E+09 |
April | 0.260528E+09 | 0.121793E+09 | 0.138735E+09 | 0.203023E+09 | 0.171693E+09 |
May | 0.223012E+09 | 60435776.82 | 0.162576E+09 | 0.166062E+09 | 0.110087E+09 |
June | 0.209524E+09 | 42632042.87 | 0.166892E+09 | 0.179903E+09 | 76724621.64 |
July | 0.229186E+09 | 57717198.46 | 0.171469E+09 | 0.204792E+09 | 69478562.08 |
August | 0.258228E+09 | 92583616.90 | 0.165644E+09 | 0.253449E+09 | 82767711.63 |
September | 0.302924E+09 | 0.159644E+09 | 0.143280E+09 | 0.305193E+09 | 0.130354E+09 |
October | 0.326917E+09 | 0.205140E+09 | 0.121778E+09 | 0.317317E+09 | 0.185420E+09 |
November | 0.238598E+09 | 0.149360E+09 | 89237204.53 | 0.198873E+09 | 0.263146E+09 |
December | 0.262824E+09 | 0.199060E+09 | 63763438.80 | 0.231264E+09 | 0.383300E+09 |
Annual Sum or Average | 0.324136E+10 | 0.167472E+10 | 0.156664E+10 | 0.278700E+10 | 0.243072E+10 |
Minimum of Months | 0.209524E+09 | 42632042.87 | 63763438.80 | 0.166062E+09 | 69478562.08 |
Maximum of Months | 0.326917E+09 | 0.219248E+09 | 0.171469E+09 | 0.317317E+09 | 0.415693E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_DOOR
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.383660E+09 | 0.262521E+09 | 0.121139E+09 | 0.298240E+09 | 0.491383E+09 |
February | 0.371476E+09 | 0.251003E+09 | 0.120474E+09 | 0.293447E+09 | 0.357945E+09 |
March | 0.357964E+09 | 0.188563E+09 | 0.169401E+09 | 0.282569E+09 | 0.282922E+09 |
April | 0.311947E+09 | 0.145831E+09 | 0.166116E+09 | 0.243560E+09 | 0.203184E+09 |
May | 0.267027E+09 | 72363890.67 | 0.194663E+09 | 0.199210E+09 | 0.130578E+09 |
June | 0.250877E+09 | 51046261.85 | 0.199831E+09 | 0.215287E+09 | 91113212.20 |
July | 0.274420E+09 | 69108750.79 | 0.205311E+09 | 0.245025E+09 | 82621885.02 |
August | 0.309194E+09 | 0.110857E+09 | 0.198337E+09 | 0.303248E+09 | 98327978.70 |
September | 0.362712E+09 | 0.191152E+09 | 0.171559E+09 | 0.365325E+09 | 0.154726E+09 |
October | 0.391441E+09 | 0.245628E+09 | 0.145813E+09 | 0.380425E+09 | 0.219783E+09 |
November | 0.285689E+09 | 0.178839E+09 | 0.106850E+09 | 0.238840E+09 | 0.311153E+09 |
December | 0.314697E+09 | 0.238348E+09 | 76348328.03 | 0.277661E+09 | 0.453314E+09 |
Annual Sum or Average | 0.388110E+10 | 0.200526E+10 | 0.187584E+10 | 0.334284E+10 | 0.287705E+10 |
Minimum of Months | 0.250877E+09 | 51046261.85 | 76348328.03 | 0.199210E+09 | 82621885.02 |
Maximum of Months | 0.391441E+09 | 0.262521E+09 | 0.205311E+09 | 0.380425E+09 | 0.491383E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.320420E+09 | 0.219248E+09 | 0.101171E+09 | 0.249797E+09 | 0.404610E+09 |
February | 0.310244E+09 | 0.209629E+09 | 0.100615E+09 | 0.246177E+09 | 0.290643E+09 |
March | 0.298959E+09 | 0.157481E+09 | 0.141478E+09 | 0.238238E+09 | 0.223909E+09 |
April | 0.260528E+09 | 0.121793E+09 | 0.138735E+09 | 0.206431E+09 | 0.155691E+09 |
May | 0.223012E+09 | 60435776.82 | 0.162576E+09 | 0.172228E+09 | 97438017.51 |
June | 0.209524E+09 | 42632042.87 | 0.166892E+09 | 0.182859E+09 | 69650161.74 |
July | 0.229186E+09 | 57717198.46 | 0.171469E+09 | 0.206470E+09 | 64974416.74 |
August | 0.258228E+09 | 92583616.90 | 0.165644E+09 | 0.254610E+09 | 78180565.85 |
September | 0.302924E+09 | 0.159644E+09 | 0.143280E+09 | 0.306736E+09 | 0.123233E+09 |
October | 0.326917E+09 | 0.205140E+09 | 0.121778E+09 | 0.319826E+09 | 0.174676E+09 |
November | 0.238598E+09 | 0.149360E+09 | 89237204.53 | 0.200838E+09 | 0.251324E+09 |
December | 0.262824E+09 | 0.199060E+09 | 63763438.80 | 0.232831E+09 | 0.370372E+09 |
Annual Sum or Average | 0.324136E+10 | 0.167472E+10 | 0.156664E+10 | 0.281704E+10 | 0.230470E+10 |
Minimum of Months | 0.209524E+09 | 42632042.87 | 63763438.80 | 0.172228E+09 | 64974416.74 |
Maximum of Months | 0.326917E+09 | 0.219248E+09 | 0.171469E+09 | 0.319826E+09 | 0.404610E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.320420E+09 | 0.219248E+09 | 0.101171E+09 | 0.249797E+09 | 0.404610E+09 |
February | 0.310244E+09 | 0.209629E+09 | 0.100615E+09 | 0.246177E+09 | 0.290643E+09 |
March | 0.298959E+09 | 0.157481E+09 | 0.141478E+09 | 0.238238E+09 | 0.223909E+09 |
April | 0.260528E+09 | 0.121793E+09 | 0.138735E+09 | 0.206431E+09 | 0.155691E+09 |
May | 0.223012E+09 | 60435776.82 | 0.162576E+09 | 0.172228E+09 | 97438017.51 |
June | 0.209524E+09 | 42632042.87 | 0.166892E+09 | 0.182859E+09 | 69650161.74 |
July | 0.229186E+09 | 57717198.46 | 0.171469E+09 | 0.206470E+09 | 64974416.74 |
August | 0.258228E+09 | 92583616.90 | 0.165644E+09 | 0.254610E+09 | 78180565.85 |
September | 0.302924E+09 | 0.159644E+09 | 0.143280E+09 | 0.306736E+09 | 0.123233E+09 |
October | 0.326917E+09 | 0.205140E+09 | 0.121778E+09 | 0.319826E+09 | 0.174676E+09 |
November | 0.238598E+09 | 0.149360E+09 | 89237204.53 | 0.200838E+09 | 0.251324E+09 |
December | 0.262824E+09 | 0.199060E+09 | 63763438.80 | 0.232831E+09 | 0.370372E+09 |
Annual Sum or Average | 0.324136E+10 | 0.167472E+10 | 0.156664E+10 | 0.281704E+10 | 0.230470E+10 |
Minimum of Months | 0.209524E+09 | 42632042.87 | 63763438.80 | 0.172228E+09 | 64974416.74 |
Maximum of Months | 0.326917E+09 | 0.219248E+09 | 0.171469E+09 | 0.319826E+09 | 0.404610E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_DOOR
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.383660E+09 | 0.262521E+09 | 0.121139E+09 | 0.300549E+09 | 0.478106E+09 |
February | 0.371476E+09 | 0.251003E+09 | 0.120474E+09 | 0.296026E+09 | 0.343490E+09 |
March | 0.357964E+09 | 0.188563E+09 | 0.169401E+09 | 0.286330E+09 | 0.264689E+09 |
April | 0.311947E+09 | 0.145831E+09 | 0.166116E+09 | 0.247686E+09 | 0.184223E+09 |
May | 0.267027E+09 | 72363890.67 | 0.194663E+09 | 0.206602E+09 | 0.115632E+09 |
June | 0.250877E+09 | 51046261.85 | 0.199831E+09 | 0.218838E+09 | 82757741.15 |
July | 0.274420E+09 | 69108750.79 | 0.205311E+09 | 0.247040E+09 | 77307410.22 |
August | 0.309194E+09 | 0.110857E+09 | 0.198337E+09 | 0.304648E+09 | 92929682.04 |
September | 0.362712E+09 | 0.191152E+09 | 0.171559E+09 | 0.367188E+09 | 0.146337E+09 |
October | 0.391441E+09 | 0.245628E+09 | 0.145813E+09 | 0.383459E+09 | 0.207108E+09 |
November | 0.285689E+09 | 0.178839E+09 | 0.106850E+09 | 0.241231E+09 | 0.297148E+09 |
December | 0.314697E+09 | 0.238348E+09 | 76348328.03 | 0.279566E+09 | 0.437908E+09 |
Annual Sum or Average | 0.388110E+10 | 0.200526E+10 | 0.187584E+10 | 0.337916E+10 | 0.272763E+10 |
Minimum of Months | 0.250877E+09 | 51046261.85 | 76348328.03 | 0.206602E+09 | 77307410.22 |
Maximum of Months | 0.391441E+09 | 0.262521E+09 | 0.205311E+09 | 0.383459E+09 | 0.478106E+09 |
Report: WindowZoneSummaryMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 593.81 | 1026.93 | 766.58 | 524.54 | 242.05 | 0.00 | 0.00 |
February | 646.04 | 832.95 | 821.76 | 555.26 | 266.51 | 0.00 | 0.00 |
March | 559.74 | 601.08 | 715.24 | 376.76 | 338.48 | 0.00 | 0.00 |
April | 496.77 | 450.32 | 644.07 | 301.09 | 342.98 | 0.00 | 0.00 |
May | 386.07 | 283.52 | 533.54 | 144.59 | 388.95 | 0.00 | 0.00 |
June | 439.75 | 197.59 | 517.98 | 105.39 | 412.59 | 0.00 | 0.00 |
July | 488.28 | 165.98 | 548.31 | 138.08 | 410.23 | 0.00 | 0.00 |
August | 603.64 | 199.39 | 617.79 | 221.50 | 396.29 | 0.00 | 0.00 |
September | 750.18 | 332.85 | 748.88 | 394.67 | 354.21 | 0.00 | 0.00 |
October | 749.04 | 475.93 | 782.13 | 490.78 | 291.35 | 0.00 | 0.00 |
November | 485.52 | 689.34 | 589.86 | 369.25 | 220.61 | 0.00 | 0.00 |
December | 551.80 | 948.71 | 628.79 | 476.24 | 152.55 | 0.00 | 0.00 |
Annual Sum or Average | 562.08 | 515.54 | 658.62 | 340.29 | 318.33 | 0.00 | 0.00 |
Minimum of Months | 386.07 | 165.98 | 517.98 | 105.39 | 152.55 | 0.00 | 0.00 |
Maximum of Months | 750.18 | 1026.93 | 821.76 | 555.26 | 412.59 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 293.06 | 529.20 | 383.29 | 262.27 | 121.02 | 0.00 | 0.00 |
February | 318.79 | 432.99 | 410.88 | 277.63 | 133.25 | 0.00 | 0.00 |
March | 275.00 | 318.49 | 357.62 | 188.38 | 169.24 | 0.00 | 0.00 |
April | 244.43 | 241.49 | 322.04 | 150.55 | 171.49 | 0.00 | 0.00 |
May | 188.96 | 149.08 | 266.77 | 72.29 | 194.48 | 0.00 | 0.00 |
June | 218.11 | 102.31 | 258.99 | 52.70 | 206.29 | 0.00 | 0.00 |
July | 243.52 | 84.10 | 274.16 | 69.04 | 205.11 | 0.00 | 0.00 |
August | 301.31 | 101.03 | 308.90 | 110.75 | 198.15 | 0.00 | 0.00 |
September | 373.41 | 171.62 | 374.44 | 197.33 | 177.11 | 0.00 | 0.00 |
October | 369.75 | 252.04 | 391.06 | 245.39 | 145.67 | 0.00 | 0.00 |
November | 239.31 | 360.52 | 294.93 | 184.62 | 110.31 | 0.00 | 0.00 |
December | 272.93 | 491.42 | 314.39 | 238.12 | 76.27 | 0.00 | 0.00 |
Annual Sum or Average | 277.98 | 268.73 | 329.31 | 170.15 | 159.16 | 0.00 | 0.00 |
Minimum of Months | 188.96 | 84.10 | 258.99 | 52.70 | 76.27 | 0.00 | 0.00 |
Maximum of Months | 373.41 | 529.20 | 410.88 | 277.63 | 206.29 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 293.42 | 513.33 | 382.50 | 261.73 | 120.77 | 0.00 | 0.00 |
February | 319.18 | 418.80 | 410.04 | 277.06 | 132.98 | 0.00 | 0.00 |
March | 275.64 | 307.10 | 356.89 | 187.99 | 168.89 | 0.00 | 0.00 |
April | 244.67 | 233.24 | 321.37 | 150.24 | 171.14 | 0.00 | 0.00 |
May | 188.97 | 149.09 | 266.22 | 72.15 | 194.08 | 0.00 | 0.00 |
June | 216.58 | 106.67 | 258.46 | 52.59 | 205.87 | 0.00 | 0.00 |
July | 241.63 | 90.76 | 273.59 | 68.90 | 204.69 | 0.00 | 0.00 |
August | 300.02 | 107.04 | 308.26 | 110.52 | 197.74 | 0.00 | 0.00 |
September | 372.58 | 173.94 | 373.67 | 196.93 | 176.74 | 0.00 | 0.00 |
October | 371.20 | 242.26 | 390.26 | 244.89 | 145.37 | 0.00 | 0.00 |
November | 240.06 | 347.94 | 294.32 | 184.24 | 110.08 | 0.00 | 0.00 |
December | 273.14 | 477.01 | 313.75 | 237.63 | 76.12 | 0.00 | 0.00 |
Annual Sum or Average | 277.86 | 263.19 | 328.63 | 169.80 | 158.84 | 0.00 | 0.00 |
Minimum of Months | 188.97 | 90.76 | 258.46 | 52.59 | 76.12 | 0.00 | 0.00 |
Maximum of Months | 372.58 | 513.33 | 410.04 | 277.06 | 205.87 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 293.87 | 508.86 | 382.50 | 261.73 | 120.77 | 0.00 | 0.00 |
February | 319.69 | 414.67 | 410.04 | 277.06 | 132.98 | 0.00 | 0.00 |
March | 276.39 | 302.97 | 356.89 | 187.99 | 168.89 | 0.00 | 0.00 |
April | 245.34 | 229.67 | 321.37 | 150.24 | 171.14 | 0.00 | 0.00 |
May | 189.57 | 147.33 | 266.22 | 72.15 | 194.08 | 0.00 | 0.00 |
June | 216.72 | 106.21 | 258.46 | 52.59 | 205.87 | 0.00 | 0.00 |
July | 241.57 | 90.95 | 273.59 | 68.90 | 204.69 | 0.00 | 0.00 |
August | 300.01 | 107.08 | 308.26 | 110.52 | 197.74 | 0.00 | 0.00 |
September | 372.85 | 172.79 | 373.67 | 196.93 | 176.74 | 0.00 | 0.00 |
October | 372.50 | 237.87 | 390.26 | 244.89 | 145.37 | 0.00 | 0.00 |
November | 240.83 | 343.20 | 294.32 | 184.24 | 110.08 | 0.00 | 0.00 |
December | 273.56 | 472.67 | 313.75 | 237.63 | 76.12 | 0.00 | 0.00 |
Annual Sum or Average | 278.34 | 260.46 | 328.63 | 169.80 | 158.84 | 0.00 | 0.00 |
Minimum of Months | 189.57 | 90.95 | 258.46 | 52.59 | 76.12 | 0.00 | 0.00 |
Maximum of Months | 372.85 | 508.86 | 410.04 | 277.06 | 205.87 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 294.41 | 505.88 | 382.50 | 261.73 | 120.77 | 0.00 | 0.00 |
February | 320.33 | 411.67 | 410.04 | 277.06 | 132.98 | 0.00 | 0.00 |
March | 277.30 | 299.57 | 356.89 | 187.99 | 168.89 | 0.00 | 0.00 |
April | 246.26 | 226.44 | 321.37 | 150.24 | 171.14 | 0.00 | 0.00 |
May | 190.79 | 144.91 | 266.22 | 72.15 | 194.08 | 0.00 | 0.00 |
June | 217.54 | 104.43 | 258.46 | 52.59 | 205.87 | 0.00 | 0.00 |
July | 242.05 | 89.81 | 273.59 | 68.90 | 204.69 | 0.00 | 0.00 |
August | 300.45 | 105.87 | 308.26 | 110.52 | 197.74 | 0.00 | 0.00 |
September | 373.57 | 170.60 | 373.67 | 196.93 | 176.74 | 0.00 | 0.00 |
October | 373.96 | 234.14 | 390.26 | 244.89 | 145.37 | 0.00 | 0.00 |
November | 241.81 | 339.07 | 294.32 | 184.24 | 110.08 | 0.00 | 0.00 |
December | 274.07 | 469.37 | 313.75 | 237.63 | 76.12 | 0.00 | 0.00 |
Annual Sum or Average | 279.15 | 257.75 | 328.63 | 169.80 | 158.84 | 0.00 | 0.00 |
Minimum of Months | 190.79 | 89.81 | 258.46 | 52.59 | 76.12 | 0.00 | 0.00 |
Maximum of Months | 373.96 | 505.88 | 410.04 | 277.06 | 205.87 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 595.39 | 985.68 | 765.01 | 523.46 | 241.55 | 0.00 | 0.00 |
February | 647.97 | 798.79 | 820.08 | 554.12 | 265.96 | 0.00 | 0.00 |
March | 561.88 | 575.72 | 713.77 | 375.99 | 337.78 | 0.00 | 0.00 |
April | 498.13 | 433.46 | 642.75 | 300.48 | 342.27 | 0.00 | 0.00 |
May | 388.21 | 275.89 | 532.45 | 144.29 | 388.15 | 0.00 | 0.00 |
June | 438.18 | 197.52 | 516.92 | 105.18 | 411.74 | 0.00 | 0.00 |
July | 485.03 | 171.30 | 547.19 | 137.80 | 409.38 | 0.00 | 0.00 |
August | 602.15 | 202.65 | 616.52 | 221.05 | 395.48 | 0.00 | 0.00 |
September | 750.27 | 328.67 | 747.35 | 393.86 | 353.49 | 0.00 | 0.00 |
October | 755.98 | 450.50 | 780.52 | 489.77 | 290.75 | 0.00 | 0.00 |
November | 490.62 | 652.48 | 588.65 | 368.49 | 220.16 | 0.00 | 0.00 |
December | 553.85 | 911.84 | 627.50 | 475.26 | 152.24 | 0.00 | 0.00 |
Annual Sum or Average | 563.50 | 497.29 | 657.27 | 339.59 | 317.68 | 0.00 | 0.00 |
Minimum of Months | 388.21 | 171.30 | 516.92 | 105.18 | 152.24 | 0.00 | 0.00 |
Maximum of Months | 755.98 | 985.68 | 820.08 | 554.12 | 411.74 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 296.03 | 496.56 | 382.50 | 261.73 | 120.77 | 0.00 | 0.00 |
February | 322.42 | 402.15 | 410.04 | 277.06 | 132.98 | 0.00 | 0.00 |
March | 279.86 | 289.50 | 356.89 | 187.99 | 168.89 | 0.00 | 0.00 |
April | 248.91 | 217.13 | 321.37 | 150.24 | 171.14 | 0.00 | 0.00 |
May | 194.63 | 137.13 | 266.22 | 72.15 | 194.08 | 0.00 | 0.00 |
June | 220.02 | 97.63 | 258.46 | 52.59 | 205.87 | 0.00 | 0.00 |
July | 243.39 | 84.55 | 273.59 | 68.90 | 204.69 | 0.00 | 0.00 |
August | 301.66 | 100.34 | 308.26 | 110.52 | 197.74 | 0.00 | 0.00 |
September | 375.29 | 163.62 | 373.67 | 196.93 | 176.74 | 0.00 | 0.00 |
October | 377.42 | 225.15 | 390.26 | 244.89 | 145.37 | 0.00 | 0.00 |
November | 244.52 | 327.89 | 294.32 | 184.24 | 110.08 | 0.00 | 0.00 |
December | 275.81 | 459.34 | 313.75 | 237.63 | 76.12 | 0.00 | 0.00 |
Annual Sum or Average | 281.43 | 249.37 | 328.63 | 169.80 | 158.84 | 0.00 | 0.00 |
Minimum of Months | 194.63 | 84.55 | 258.46 | 52.59 | 76.12 | 0.00 | 0.00 |
Maximum of Months | 377.42 | 496.56 | 410.04 | 277.06 | 205.87 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 296.10 | 496.20 | 382.50 | 261.73 | 120.77 | 0.00 | 0.00 |
February | 322.54 | 401.49 | 410.04 | 277.06 | 132.98 | 0.00 | 0.00 |
March | 280.15 | 288.49 | 356.89 | 187.99 | 168.89 | 0.00 | 0.00 |
April | 249.35 | 215.74 | 321.37 | 150.24 | 171.14 | 0.00 | 0.00 |
May | 195.68 | 135.50 | 266.22 | 72.15 | 194.08 | 0.00 | 0.00 |
June | 220.60 | 96.70 | 258.46 | 52.59 | 205.87 | 0.00 | 0.00 |
July | 243.74 | 84.01 | 273.59 | 68.90 | 204.69 | 0.00 | 0.00 |
August | 301.95 | 99.79 | 308.26 | 110.52 | 197.74 | 0.00 | 0.00 |
September | 375.65 | 162.68 | 373.67 | 196.93 | 176.74 | 0.00 | 0.00 |
October | 377.89 | 223.93 | 390.26 | 244.89 | 145.37 | 0.00 | 0.00 |
November | 244.83 | 326.74 | 294.32 | 184.24 | 110.08 | 0.00 | 0.00 |
December | 275.92 | 458.73 | 313.75 | 237.63 | 76.12 | 0.00 | 0.00 |
Annual Sum or Average | 281.80 | 248.45 | 328.63 | 169.80 | 158.84 | 0.00 | 0.00 |
Minimum of Months | 195.68 | 84.01 | 258.46 | 52.59 | 76.12 | 0.00 | 0.00 |
Maximum of Months | 377.89 | 496.20 | 410.04 | 277.06 | 205.87 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 296.46 | 493.86 | 382.50 | 261.73 | 120.77 | 0.00 | 0.00 |
February | 323.07 | 398.27 | 410.04 | 277.06 | 132.98 | 0.00 | 0.00 |
March | 281.09 | 284.30 | 356.89 | 187.99 | 168.89 | 0.00 | 0.00 |
April | 250.62 | 210.87 | 321.37 | 150.24 | 171.14 | 0.00 | 0.00 |
May | 198.38 | 130.96 | 266.22 | 72.15 | 194.08 | 0.00 | 0.00 |
June | 221.87 | 94.35 | 258.46 | 52.59 | 205.87 | 0.00 | 0.00 |
July | 244.40 | 82.73 | 273.59 | 68.90 | 204.69 | 0.00 | 0.00 |
August | 302.47 | 98.52 | 308.26 | 110.52 | 197.74 | 0.00 | 0.00 |
September | 376.43 | 160.27 | 373.67 | 196.93 | 176.74 | 0.00 | 0.00 |
October | 378.98 | 220.51 | 390.26 | 244.89 | 145.37 | 0.00 | 0.00 |
November | 245.59 | 323.09 | 294.32 | 184.24 | 110.08 | 0.00 | 0.00 |
December | 276.35 | 455.46 | 313.75 | 237.63 | 76.12 | 0.00 | 0.00 |
Annual Sum or Average | 282.75 | 245.38 | 328.63 | 169.80 | 158.84 | 0.00 | 0.00 |
Minimum of Months | 198.38 | 82.73 | 258.46 | 52.59 | 76.12 | 0.00 | 0.00 |
Maximum of Months | 378.98 | 493.86 | 410.04 | 277.06 | 205.87 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 298.74 | 480.63 | 382.50 | 261.73 | 120.77 | 0.00 | 0.00 |
February | 325.88 | 382.27 | 410.04 | 277.06 | 132.98 | 0.00 | 0.00 |
March | 284.80 | 266.02 | 356.89 | 187.99 | 168.89 | 0.00 | 0.00 |
April | 254.84 | 191.20 | 321.37 | 150.24 | 171.14 | 0.00 | 0.00 |
May | 205.74 | 115.93 | 266.22 | 72.15 | 194.08 | 0.00 | 0.00 |
June | 225.52 | 85.67 | 258.46 | 52.59 | 205.87 | 0.00 | 0.00 |
July | 246.41 | 77.38 | 273.59 | 68.90 | 204.69 | 0.00 | 0.00 |
August | 303.86 | 93.07 | 308.26 | 110.52 | 197.74 | 0.00 | 0.00 |
September | 378.34 | 151.54 | 373.67 | 196.93 | 176.74 | 0.00 | 0.00 |
October | 381.99 | 207.76 | 390.26 | 244.89 | 145.37 | 0.00 | 0.00 |
November | 248.03 | 308.56 | 294.32 | 184.24 | 110.08 | 0.00 | 0.00 |
December | 278.24 | 440.06 | 313.75 | 237.63 | 76.12 | 0.00 | 0.00 |
Annual Sum or Average | 285.81 | 232.66 | 328.63 | 169.80 | 158.84 | 0.00 | 0.00 |
Minimum of Months | 205.74 | 77.38 | 258.46 | 52.59 | 76.12 | 0.00 | 0.00 |
Maximum of Months | 381.99 | 480.63 | 410.04 | 277.06 | 205.87 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.159047E+10 | 0.275054E+10 | 0.205322E+10 | 0.140492E+10 | 0.648296E+09 | 0.00 | 0.00 |
February | 0.156291E+10 | 0.201508E+10 | 0.198801E+10 | 0.134328E+10 | 0.644733E+09 | 0.00 | 0.00 |
March | 0.149921E+10 | 0.160993E+10 | 0.191570E+10 | 0.100912E+10 | 0.906573E+09 | 0.00 | 0.00 |
April | 0.128764E+10 | 0.116723E+10 | 0.166943E+10 | 0.780436E+09 | 0.888997E+09 | 0.00 | 0.00 |
May | 0.103404E+10 | 0.759382E+09 | 0.142904E+10 | 0.387266E+09 | 0.104177E+10 | 0.00 | 0.00 |
June | 0.113984E+10 | 0.512149E+09 | 0.134261E+10 | 0.273182E+09 | 0.106943E+10 | 0.00 | 0.00 |
July | 0.130782E+10 | 0.444548E+09 | 0.146860E+10 | 0.369846E+09 | 0.109875E+10 | 0.00 | 0.00 |
August | 0.161678E+10 | 0.534033E+09 | 0.165470E+10 | 0.593266E+09 | 0.106143E+10 | 0.00 | 0.00 |
September | 0.194448E+10 | 0.862741E+09 | 0.194110E+10 | 0.102298E+10 | 0.918125E+09 | 0.00 | 0.00 |
October | 0.200623E+10 | 0.127474E+10 | 0.209485E+10 | 0.131451E+10 | 0.780340E+09 | 0.00 | 0.00 |
November | 0.125846E+10 | 0.178678E+10 | 0.152891E+10 | 0.957086E+09 | 0.571823E+09 | 0.00 | 0.00 |
December | 0.147795E+10 | 0.254103E+10 | 0.168415E+10 | 0.127556E+10 | 0.408589E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.177258E+11 | 0.162582E+11 | 0.207703E+11 | 0.107314E+11 | 0.100389E+11 | 0.00 | 0.00 |
Minimum of Months | 0.103404E+10 | 0.444548E+09 | 0.134261E+10 | 0.273182E+09 | 0.408589E+09 | 0.00 | 0.00 |
Maximum of Months | 0.200623E+10 | 0.275054E+10 | 0.209485E+10 | 0.140492E+10 | 0.109875E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.784943E+09 | 0.141742E+10 | 0.102661E+10 | 0.702460E+09 | 0.324148E+09 | 0.00 | 0.00 |
February | 0.771224E+09 | 0.104749E+10 | 0.994005E+09 | 0.671639E+09 | 0.322366E+09 | 0.00 | 0.00 |
March | 0.736567E+09 | 0.853037E+09 | 0.957848E+09 | 0.504561E+09 | 0.453287E+09 | 0.00 | 0.00 |
April | 0.633560E+09 | 0.625940E+09 | 0.834717E+09 | 0.390218E+09 | 0.444498E+09 | 0.00 | 0.00 |
May | 0.506099E+09 | 0.399287E+09 | 0.714518E+09 | 0.193633E+09 | 0.520885E+09 | 0.00 | 0.00 |
June | 0.565333E+09 | 0.265178E+09 | 0.671304E+09 | 0.136591E+09 | 0.534713E+09 | 0.00 | 0.00 |
July | 0.652246E+09 | 0.225244E+09 | 0.734299E+09 | 0.184923E+09 | 0.549376E+09 | 0.00 | 0.00 |
August | 0.807027E+09 | 0.270608E+09 | 0.827348E+09 | 0.296633E+09 | 0.530715E+09 | 0.00 | 0.00 |
September | 0.967882E+09 | 0.444843E+09 | 0.970552E+09 | 0.511490E+09 | 0.459063E+09 | 0.00 | 0.00 |
October | 0.990343E+09 | 0.675073E+09 | 0.104743E+10 | 0.657256E+09 | 0.390170E+09 | 0.00 | 0.00 |
November | 0.620296E+09 | 0.934473E+09 | 0.764454E+09 | 0.478543E+09 | 0.285911E+09 | 0.00 | 0.00 |
December | 0.731008E+09 | 0.131623E+10 | 0.842073E+09 | 0.637778E+09 | 0.204295E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.876653E+10 | 0.847483E+10 | 0.103852E+11 | 0.536572E+10 | 0.501943E+10 | 0.00 | 0.00 |
Minimum of Months | 0.506099E+09 | 0.225244E+09 | 0.671304E+09 | 0.136591E+09 | 0.204295E+09 | 0.00 | 0.00 |
Maximum of Months | 0.990343E+09 | 0.141742E+10 | 0.104743E+10 | 0.702460E+09 | 0.549376E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.785894E+09 | 0.137491E+10 | 0.102450E+10 | 0.701017E+09 | 0.323482E+09 | 0.00 | 0.00 |
February | 0.772160E+09 | 0.101316E+10 | 0.991964E+09 | 0.670260E+09 | 0.321704E+09 | 0.00 | 0.00 |
March | 0.738278E+09 | 0.822546E+09 | 0.955881E+09 | 0.503525E+09 | 0.452356E+09 | 0.00 | 0.00 |
April | 0.634180E+09 | 0.604548E+09 | 0.833003E+09 | 0.389417E+09 | 0.443586E+09 | 0.00 | 0.00 |
May | 0.506127E+09 | 0.399317E+09 | 0.713051E+09 | 0.193235E+09 | 0.519815E+09 | 0.00 | 0.00 |
June | 0.561363E+09 | 0.276484E+09 | 0.669925E+09 | 0.136310E+09 | 0.533615E+09 | 0.00 | 0.00 |
July | 0.647169E+09 | 0.243084E+09 | 0.732791E+09 | 0.184543E+09 | 0.548248E+09 | 0.00 | 0.00 |
August | 0.803572E+09 | 0.286699E+09 | 0.825649E+09 | 0.296024E+09 | 0.529625E+09 | 0.00 | 0.00 |
September | 0.965723E+09 | 0.450847E+09 | 0.968559E+09 | 0.510439E+09 | 0.458120E+09 | 0.00 | 0.00 |
October | 0.994211E+09 | 0.648878E+09 | 0.104528E+10 | 0.655907E+09 | 0.389369E+09 | 0.00 | 0.00 |
November | 0.622224E+09 | 0.901850E+09 | 0.762885E+09 | 0.477560E+09 | 0.285324E+09 | 0.00 | 0.00 |
December | 0.731582E+09 | 0.127762E+10 | 0.840344E+09 | 0.636469E+09 | 0.203875E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.876248E+10 | 0.829994E+10 | 0.103638E+11 | 0.535471E+10 | 0.500912E+10 | 0.00 | 0.00 |
Minimum of Months | 0.506127E+09 | 0.243084E+09 | 0.669925E+09 | 0.136310E+09 | 0.203875E+09 | 0.00 | 0.00 |
Maximum of Months | 0.994211E+09 | 0.137491E+10 | 0.104528E+10 | 0.701017E+09 | 0.548248E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.787103E+09 | 0.136294E+10 | 0.102450E+10 | 0.701017E+09 | 0.323482E+09 | 0.00 | 0.00 |
February | 0.773402E+09 | 0.100317E+10 | 0.991964E+09 | 0.670260E+09 | 0.321704E+09 | 0.00 | 0.00 |
March | 0.740276E+09 | 0.811463E+09 | 0.955881E+09 | 0.503525E+09 | 0.452356E+09 | 0.00 | 0.00 |
April | 0.635910E+09 | 0.595302E+09 | 0.833003E+09 | 0.389417E+09 | 0.443586E+09 | 0.00 | 0.00 |
May | 0.507747E+09 | 0.394616E+09 | 0.713051E+09 | 0.193235E+09 | 0.519815E+09 | 0.00 | 0.00 |
June | 0.561740E+09 | 0.275299E+09 | 0.669925E+09 | 0.136310E+09 | 0.533615E+09 | 0.00 | 0.00 |
July | 0.647020E+09 | 0.243601E+09 | 0.732791E+09 | 0.184543E+09 | 0.548248E+09 | 0.00 | 0.00 |
August | 0.803557E+09 | 0.286810E+09 | 0.825649E+09 | 0.296024E+09 | 0.529625E+09 | 0.00 | 0.00 |
September | 0.966440E+09 | 0.447884E+09 | 0.968559E+09 | 0.510439E+09 | 0.458120E+09 | 0.00 | 0.00 |
October | 0.997713E+09 | 0.637102E+09 | 0.104528E+10 | 0.655907E+09 | 0.389369E+09 | 0.00 | 0.00 |
November | 0.624233E+09 | 0.889570E+09 | 0.762885E+09 | 0.477560E+09 | 0.285324E+09 | 0.00 | 0.00 |
December | 0.732702E+09 | 0.126600E+10 | 0.840344E+09 | 0.636469E+09 | 0.203875E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.877784E+10 | 0.821376E+10 | 0.103638E+11 | 0.535471E+10 | 0.500912E+10 | 0.00 | 0.00 |
Minimum of Months | 0.507747E+09 | 0.243601E+09 | 0.669925E+09 | 0.136310E+09 | 0.203875E+09 | 0.00 | 0.00 |
Maximum of Months | 0.997713E+09 | 0.136294E+10 | 0.104528E+10 | 0.701017E+09 | 0.548248E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.788541E+09 | 0.135495E+10 | 0.102450E+10 | 0.701017E+09 | 0.323482E+09 | 0.00 | 0.00 |
February | 0.774937E+09 | 0.995923E+09 | 0.991964E+09 | 0.670260E+09 | 0.321704E+09 | 0.00 | 0.00 |
March | 0.742710E+09 | 0.802356E+09 | 0.955881E+09 | 0.503525E+09 | 0.452356E+09 | 0.00 | 0.00 |
April | 0.638306E+09 | 0.586930E+09 | 0.833003E+09 | 0.389417E+09 | 0.443586E+09 | 0.00 | 0.00 |
May | 0.511020E+09 | 0.388121E+09 | 0.713051E+09 | 0.193235E+09 | 0.519815E+09 | 0.00 | 0.00 |
June | 0.563871E+09 | 0.270687E+09 | 0.669925E+09 | 0.136310E+09 | 0.533615E+09 | 0.00 | 0.00 |
July | 0.648304E+09 | 0.240540E+09 | 0.732791E+09 | 0.184543E+09 | 0.548248E+09 | 0.00 | 0.00 |
August | 0.804738E+09 | 0.283563E+09 | 0.825649E+09 | 0.296024E+09 | 0.529625E+09 | 0.00 | 0.00 |
September | 0.968297E+09 | 0.442206E+09 | 0.968559E+09 | 0.510439E+09 | 0.458120E+09 | 0.00 | 0.00 |
October | 0.100161E+10 | 0.627130E+09 | 0.104528E+10 | 0.655907E+09 | 0.389369E+09 | 0.00 | 0.00 |
November | 0.626775E+09 | 0.878859E+09 | 0.762885E+09 | 0.477560E+09 | 0.285324E+09 | 0.00 | 0.00 |
December | 0.734071E+09 | 0.125717E+10 | 0.840344E+09 | 0.636469E+09 | 0.203875E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.880318E+10 | 0.812843E+10 | 0.103638E+11 | 0.535471E+10 | 0.500912E+10 | 0.00 | 0.00 |
Minimum of Months | 0.511020E+09 | 0.240540E+09 | 0.669925E+09 | 0.136310E+09 | 0.203875E+09 | 0.00 | 0.00 |
Maximum of Months | 0.100161E+10 | 0.135495E+10 | 0.104528E+10 | 0.701017E+09 | 0.548248E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.159469E+10 | 0.264005E+10 | 0.204900E+10 | 0.140203E+10 | 0.646964E+09 | 0.00 | 0.00 |
February | 0.156757E+10 | 0.193242E+10 | 0.198393E+10 | 0.134052E+10 | 0.643409E+09 | 0.00 | 0.00 |
March | 0.150494E+10 | 0.154200E+10 | 0.191176E+10 | 0.100705E+10 | 0.904712E+09 | 0.00 | 0.00 |
April | 0.129116E+10 | 0.112353E+10 | 0.166601E+10 | 0.778834E+09 | 0.887171E+09 | 0.00 | 0.00 |
May | 0.103977E+10 | 0.738935E+09 | 0.142610E+10 | 0.386471E+09 | 0.103963E+10 | 0.00 | 0.00 |
June | 0.113575E+10 | 0.511976E+09 | 0.133985E+10 | 0.272621E+09 | 0.106723E+10 | 0.00 | 0.00 |
July | 0.129910E+10 | 0.458812E+09 | 0.146558E+10 | 0.369086E+09 | 0.109650E+10 | 0.00 | 0.00 |
August | 0.161279E+10 | 0.542784E+09 | 0.165130E+10 | 0.592048E+09 | 0.105925E+10 | 0.00 | 0.00 |
September | 0.194471E+10 | 0.851921E+09 | 0.193712E+10 | 0.102088E+10 | 0.916240E+09 | 0.00 | 0.00 |
October | 0.202483E+10 | 0.120663E+10 | 0.209055E+10 | 0.131181E+10 | 0.778738E+09 | 0.00 | 0.00 |
November | 0.127170E+10 | 0.169122E+10 | 0.152577E+10 | 0.955121E+09 | 0.570648E+09 | 0.00 | 0.00 |
December | 0.148343E+10 | 0.244227E+10 | 0.168069E+10 | 0.127294E+10 | 0.407750E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.177705E+11 | 0.156825E+11 | 0.207277E+11 | 0.107094E+11 | 0.100182E+11 | 0.00 | 0.00 |
Minimum of Months | 0.103977E+10 | 0.458812E+09 | 0.133985E+10 | 0.272621E+09 | 0.407750E+09 | 0.00 | 0.00 |
Maximum of Months | 0.202483E+10 | 0.264005E+10 | 0.209055E+10 | 0.140203E+10 | 0.109650E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.792891E+09 | 0.133000E+10 | 0.102450E+10 | 0.701017E+09 | 0.323482E+09 | 0.00 | 0.00 |
February | 0.779987E+09 | 0.972882E+09 | 0.991964E+09 | 0.670260E+09 | 0.321704E+09 | 0.00 | 0.00 |
March | 0.749578E+09 | 0.775402E+09 | 0.955881E+09 | 0.503525E+09 | 0.452356E+09 | 0.00 | 0.00 |
April | 0.645164E+09 | 0.562803E+09 | 0.833003E+09 | 0.389417E+09 | 0.443586E+09 | 0.00 | 0.00 |
May | 0.521301E+09 | 0.367286E+09 | 0.713051E+09 | 0.193235E+09 | 0.519815E+09 | 0.00 | 0.00 |
June | 0.570294E+09 | 0.253053E+09 | 0.669925E+09 | 0.136310E+09 | 0.533615E+09 | 0.00 | 0.00 |
July | 0.651897E+09 | 0.226460E+09 | 0.732791E+09 | 0.184543E+09 | 0.548248E+09 | 0.00 | 0.00 |
August | 0.807953E+09 | 0.268745E+09 | 0.825649E+09 | 0.296024E+09 | 0.529625E+09 | 0.00 | 0.00 |
September | 0.972752E+09 | 0.424106E+09 | 0.968559E+09 | 0.510439E+09 | 0.458120E+09 | 0.00 | 0.00 |
October | 0.101089E+10 | 0.603042E+09 | 0.104528E+10 | 0.655907E+09 | 0.389369E+09 | 0.00 | 0.00 |
November | 0.633802E+09 | 0.849892E+09 | 0.762885E+09 | 0.477560E+09 | 0.285324E+09 | 0.00 | 0.00 |
December | 0.738731E+09 | 0.123031E+10 | 0.840344E+09 | 0.636469E+09 | 0.203875E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.887524E+10 | 0.786398E+10 | 0.103638E+11 | 0.535471E+10 | 0.500912E+10 | 0.00 | 0.00 |
Minimum of Months | 0.521301E+09 | 0.226460E+09 | 0.669925E+09 | 0.136310E+09 | 0.203875E+09 | 0.00 | 0.00 |
Maximum of Months | 0.101089E+10 | 0.133000E+10 | 0.104528E+10 | 0.701017E+09 | 0.548248E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.793081E+09 | 0.132901E+10 | 0.102450E+10 | 0.701017E+09 | 0.323482E+09 | 0.00 | 0.00 |
February | 0.780298E+09 | 0.971278E+09 | 0.991964E+09 | 0.670260E+09 | 0.321704E+09 | 0.00 | 0.00 |
March | 0.750355E+09 | 0.772684E+09 | 0.955881E+09 | 0.503525E+09 | 0.452356E+09 | 0.00 | 0.00 |
April | 0.646313E+09 | 0.559200E+09 | 0.833003E+09 | 0.389417E+09 | 0.443586E+09 | 0.00 | 0.00 |
May | 0.524102E+09 | 0.362912E+09 | 0.713051E+09 | 0.193235E+09 | 0.519815E+09 | 0.00 | 0.00 |
June | 0.571805E+09 | 0.250641E+09 | 0.669925E+09 | 0.136310E+09 | 0.533615E+09 | 0.00 | 0.00 |
July | 0.652846E+09 | 0.225010E+09 | 0.732791E+09 | 0.184543E+09 | 0.548248E+09 | 0.00 | 0.00 |
August | 0.808753E+09 | 0.267272E+09 | 0.825649E+09 | 0.296024E+09 | 0.529625E+09 | 0.00 | 0.00 |
September | 0.973693E+09 | 0.421658E+09 | 0.968559E+09 | 0.510439E+09 | 0.458120E+09 | 0.00 | 0.00 |
October | 0.101214E+10 | 0.599781E+09 | 0.104528E+10 | 0.655907E+09 | 0.389369E+09 | 0.00 | 0.00 |
November | 0.634590E+09 | 0.846903E+09 | 0.762885E+09 | 0.477560E+09 | 0.285324E+09 | 0.00 | 0.00 |
December | 0.739019E+09 | 0.122865E+10 | 0.840344E+09 | 0.636469E+09 | 0.203875E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.888699E+10 | 0.783501E+10 | 0.103638E+11 | 0.535471E+10 | 0.500912E+10 | 0.00 | 0.00 |
Minimum of Months | 0.524102E+09 | 0.225010E+09 | 0.669925E+09 | 0.136310E+09 | 0.203875E+09 | 0.00 | 0.00 |
Maximum of Months | 0.101214E+10 | 0.132901E+10 | 0.104528E+10 | 0.701017E+09 | 0.548248E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.794050E+09 | 0.132276E+10 | 0.102450E+10 | 0.701017E+09 | 0.323482E+09 | 0.00 | 0.00 |
February | 0.781571E+09 | 0.963485E+09 | 0.991964E+09 | 0.670260E+09 | 0.321704E+09 | 0.00 | 0.00 |
March | 0.752874E+09 | 0.761482E+09 | 0.955881E+09 | 0.503525E+09 | 0.452356E+09 | 0.00 | 0.00 |
April | 0.649604E+09 | 0.546568E+09 | 0.833003E+09 | 0.389417E+09 | 0.443586E+09 | 0.00 | 0.00 |
May | 0.531333E+09 | 0.350751E+09 | 0.713051E+09 | 0.193235E+09 | 0.519815E+09 | 0.00 | 0.00 |
June | 0.575092E+09 | 0.244562E+09 | 0.669925E+09 | 0.136310E+09 | 0.533615E+09 | 0.00 | 0.00 |
July | 0.654609E+09 | 0.221579E+09 | 0.732791E+09 | 0.184543E+09 | 0.548248E+09 | 0.00 | 0.00 |
August | 0.810145E+09 | 0.263863E+09 | 0.825649E+09 | 0.296024E+09 | 0.529625E+09 | 0.00 | 0.00 |
September | 0.975709E+09 | 0.415432E+09 | 0.968559E+09 | 0.510439E+09 | 0.458120E+09 | 0.00 | 0.00 |
October | 0.101506E+10 | 0.590622E+09 | 0.104528E+10 | 0.655907E+09 | 0.389369E+09 | 0.00 | 0.00 |
November | 0.636581E+09 | 0.837440E+09 | 0.762885E+09 | 0.477560E+09 | 0.285324E+09 | 0.00 | 0.00 |
December | 0.740186E+09 | 0.121991E+10 | 0.840344E+09 | 0.636469E+09 | 0.203875E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.891681E+10 | 0.773846E+10 | 0.103638E+11 | 0.535471E+10 | 0.500912E+10 | 0.00 | 0.00 |
Minimum of Months | 0.531333E+09 | 0.221579E+09 | 0.669925E+09 | 0.136310E+09 | 0.203875E+09 | 0.00 | 0.00 |
Maximum of Months | 0.101506E+10 | 0.132276E+10 | 0.104528E+10 | 0.701017E+09 | 0.548248E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.800142E+09 | 0.128733E+10 | 0.102450E+10 | 0.701017E+09 | 0.323482E+09 | 0.00 | 0.00 |
February | 0.788379E+09 | 0.924776E+09 | 0.991964E+09 | 0.670260E+09 | 0.321704E+09 | 0.00 | 0.00 |
March | 0.762803E+09 | 0.712504E+09 | 0.955881E+09 | 0.503525E+09 | 0.452356E+09 | 0.00 | 0.00 |
April | 0.660545E+09 | 0.495602E+09 | 0.833003E+09 | 0.389417E+09 | 0.443586E+09 | 0.00 | 0.00 |
May | 0.551057E+09 | 0.310508E+09 | 0.713051E+09 | 0.193235E+09 | 0.519815E+09 | 0.00 | 0.00 |
June | 0.584556E+09 | 0.222058E+09 | 0.669925E+09 | 0.136310E+09 | 0.533615E+09 | 0.00 | 0.00 |
July | 0.659979E+09 | 0.207256E+09 | 0.732791E+09 | 0.184543E+09 | 0.548248E+09 | 0.00 | 0.00 |
August | 0.813868E+09 | 0.249291E+09 | 0.825649E+09 | 0.296024E+09 | 0.529625E+09 | 0.00 | 0.00 |
September | 0.980659E+09 | 0.392802E+09 | 0.968559E+09 | 0.510439E+09 | 0.458120E+09 | 0.00 | 0.00 |
October | 0.102311E+10 | 0.556459E+09 | 0.104528E+10 | 0.655907E+09 | 0.389369E+09 | 0.00 | 0.00 |
November | 0.642903E+09 | 0.799790E+09 | 0.762885E+09 | 0.477560E+09 | 0.285324E+09 | 0.00 | 0.00 |
December | 0.745226E+09 | 0.117865E+10 | 0.840344E+09 | 0.636469E+09 | 0.203875E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.901323E+10 | 0.733702E+10 | 0.103638E+11 | 0.535471E+10 | 0.500912E+10 | 0.00 | 0.00 |
Minimum of Months | 0.551057E+09 | 0.207256E+09 | 0.669925E+09 | 0.136310E+09 | 0.203875E+09 | 0.00 | 0.00 |
Maximum of Months | 0.102311E+10 | 0.128733E+10 | 0.104528E+10 | 0.701017E+09 | 0.548248E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -12.6 | -13.1 | -15.2 | 6.10 | -26.1 | 37.55 | 107.22 | 0.02 |
February | -7.7 | -8.6 | -10.9 | 6.39 | -21.3 | 45.57 | 135.04 | 0.00 |
March | 0.33 | -1.3 | -4.2 | 6.99 | -10.6 | 74.69 | 127.11 | 0.00 |
April | 7.02 | 4.42 | 1.63 | 6.38 | -3.6 | 77.59 | 184.47 | 0.02 |
May | 14.19 | 11.29 | 8.94 | 5.14 | 4.69 | 102.33 | 182.89 | 0.00 |
June | 19.16 | 15.70 | 13.79 | 4.87 | 8.84 | 110.26 | 213.51 | 0.04 |
July | 20.92 | 17.86 | 16.31 | 4.22 | 9.95 | 102.99 | 231.93 | 0.03 |
August | 20.05 | 16.99 | 15.28 | 4.97 | 11.01 | 95.97 | 190.14 | 0.00 |
September | 15.39 | 11.23 | 8.10 | 4.97 | 3.17 | 72.67 | 177.74 | 0.01 |
October | 7.43 | 4.70 | 1.56 | 5.55 | -3.9 | 55.50 | 131.91 | 0.00 |
November | -0.0 | -1.4 | -3.9 | 6.30 | -10.9 | 41.35 | 79.05 | 0.00 |
December | -7.6 | -8.4 | -10.6 | 6.09 | -20.0 | 22.97 | 92.59 | 0.00 |
Annual Sum or Average | 6.46 | 4.18 | 1.81 | 5.66 | -4.8 | 70.09 | 154.52 | 0.01 |
Minimum of Months | -12.6 | -13.1 | -15.2 | 4.22 | -26.1 | 22.97 | 79.05 | 0.00 |
Maximum of Months | 20.92 | 17.86 | 16.31 | 6.99 | 11.01 | 110.26 | 231.93 | 0.04 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 6.10 | 17-JAN-23:19 | 3.74 | 0.93 | 10.63 | -0.4 | 0.00 | 0.00 |
February | 8.30 | 24-FEB-14:00 | 5.61 | 2.80 | 5.20 | -7.3 | 71.00 | 794.50 |
March | 18.90 | 19-MAR-15:00 | 13.92 | 10.60 | 8.80 | 7.95 | 139.50 | 237.50 |
April | 30.00 | 15-APR-15:20 | 19.10 | 13.53 | 12.70 | 15.70 | 115.83 | 790.83 |
May | 30.00 | 31-MAY-12:00 | 19.68 | 14.40 | 6.20 | 19.52 | 251.00 | 580.50 |
June | 33.30 | 11-JUN-14:00 | 24.80 | 21.70 | 10.30 | 24.50 | 281.00 | 458.50 |
July | 30.00 | 26-JUL-15:20 | 25.66 | 24.23 | 5.13 | 20.98 | 260.33 | 436.00 |
August | 33.90 | 04-AUG-14:00 | 25.30 | 22.20 | 4.60 | 23.82 | 194.50 | 612.00 |
September | 32.20 | 06-SEP-13:00 | 21.17 | 16.10 | 6.20 | 18.28 | 135.00 | 769.00 |
October | 23.30 | 20-OCT-14:00 | 13.34 | 5.60 | 7.20 | 7.35 | 55.00 | 745.50 |
November | 16.10 | 03-NOV-13:00 | 10.46 | 5.60 | 6.70 | 0.51 | 82.00 | 691.00 |
December | 7.20 | 02-DEC-13:00 | 3.93 | 0.00 | 7.70 | -3.9 | 75.00 | 301.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.10 | 3.74 | 0.00 | 4.60 | -7.3 | 0.00 | 0.00 | |
Maximum of Months | 33.90 | 25.66 | 24.23 | 12.70 | 24.50 | 281.00 | 794.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -31.1 | 31-JAN-03:00 | -31.3 | -34.4 | 4.60 | -46.7 | 0.00 | 0.00 |
February | -36.7 | 02-FEB-05:00 | -36.8 | -40.2 | 3.10 | -59.6 | 0.00 | 0.00 |
March | -17.2 | 06-MAR-00:00 | -17.6 | -20.0 | 5.20 | -36.8 | 0.00 | 0.00 |
April | -7.2 | 03-APR-05:19 | -8.0 | -9.8 | 7.37 | -15.9 | 0.00 | 0.00 |
May | 0.60 | 03-MAY-02:00 | -0.0 | -1.1 | 1.50 | -15.5 | 0.00 | 0.00 |
June | 5.00 | 01-JUN-04:00 | 5.00 | 5.00 | 3.10 | -7.8 | 30.50 | 132.50 |
July | 10.00 | 23-JUL-03:00 | 9.66 | 9.40 | 2.60 | -4.3 | 0.00 | 0.00 |
August | 8.30 | 07-AUG-03:00 | 7.41 | 6.70 | 3.10 | -3.2 | 0.00 | 0.00 |
September | -1.1 | 30-SEP-00:00 | -2.4 | -4.4 | 4.10 | -17.8 | 0.00 | 0.00 |
October | -3.3 | 23-OCT-05:00 | -4.2 | -6.1 | 3.60 | -19.1 | 0.00 | 0.00 |
November | -28.9 | 26-NOV-06:00 | -29.0 | -30.6 | 1.50 | -50.2 | 0.00 | 0.00 |
December | -22.8 | 09-DEC-00:20 | -23.0 | -25.0 | 13.40 | -37.7 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -36.7 | -36.8 | -40.2 | 1.50 | -59.6 | 0.00 | 0.00 | |
Maximum of Months | 10.00 | 9.66 | 9.40 | 13.40 | -3.2 | 30.50 | 132.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 5.60 | 18-JAN-00:00 | 5.60 | 5.60 | 7.70 | 0.30 | 0.00 | 0.00 |
February | 5.87 | 24-FEB-15:00 | 8.30 | 3.30 | 5.70 | -7.3 | 54.50 | 665.50 |
March | 13.92 | 19-MAR-15:00 | 18.90 | 10.60 | 8.80 | 7.95 | 139.50 | 237.50 |
April | 20.93 | 18-APR-11:00 | 27.80 | 17.80 | 13.90 | 17.57 | 334.00 | 447.00 |
May | 19.92 | 29-MAY-13:00 | 23.30 | 18.30 | 6.20 | 20.75 | 379.00 | 52.00 |
June | 24.80 | 11-JUN-14:00 | 33.30 | 21.70 | 10.30 | 24.50 | 281.00 | 458.50 |
July | 26.15 | 26-JUL-18:00 | 27.80 | 25.60 | 3.10 | 19.35 | 33.50 | 51.00 |
August | 26.63 | 04-AUG-12:00 | 31.70 | 25.00 | 4.60 | 25.66 | 235.00 | 593.50 |
September | 21.17 | 06-SEP-13:00 | 32.20 | 16.10 | 6.20 | 18.28 | 135.00 | 769.00 |
October | 14.83 | 02-OCT-14:00 | 18.30 | 12.80 | 3.60 | 12.41 | 202.00 | 164.00 |
November | 13.03 | 09-NOV-04:00 | 15.00 | 11.70 | 10.30 | 10.88 | 0.00 | 0.00 |
December | 3.93 | 02-DEC-13:00 | 7.20 | 0.00 | 7.70 | -3.9 | 75.00 | 301.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 3.93 | 5.60 | 0.00 | 3.10 | -7.3 | 0.00 | 0.00 | |
Maximum of Months | 26.63 | 33.30 | 25.60 | 13.90 | 25.66 | 379.00 | 769.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 5.60 | 18-JAN-00:00 | 5.60 | 5.60 | 7.70 | 0.30 | 0.00 | 0.00 |
February | 3.30 | 24-FEB-15:00 | 8.30 | 5.87 | 5.70 | -7.3 | 54.50 | 665.50 |
March | 11.10 | 26-MAR-05:00 | 13.30 | 12.04 | 8.20 | 9.13 | 0.00 | 0.00 |
April | 18.30 | 18-APR-09:00 | 25.60 | 20.52 | 14.40 | 15.57 | 196.00 | 741.50 |
May | 18.30 | 29-MAY-13:00 | 23.30 | 19.92 | 6.20 | 20.75 | 379.00 | 52.00 |
June | 22.20 | 13-JUN-11:00 | 26.70 | 23.34 | 8.80 | 16.85 | 273.50 | 600.50 |
July | 25.60 | 26-JUL-18:00 | 27.80 | 26.15 | 3.10 | 19.35 | 33.50 | 51.00 |
August | 25.00 | 04-AUG-12:00 | 31.70 | 26.63 | 4.60 | 25.66 | 235.00 | 593.50 |
September | 18.30 | 12-SEP-02:00 | 18.90 | 18.46 | 5.70 | 14.28 | 0.00 | 0.00 |
October | 12.80 | 02-OCT-13:00 | 17.40 | 14.50 | 3.40 | 11.65 | 249.50 | 141.50 |
November | 11.70 | 08-NOV-10:00 | 13.90 | 12.62 | 7.20 | 9.91 | 158.00 | 0.50 |
December | 0.00 | 02-DEC-11:00 | 5.00 | 2.78 | 7.20 | -8.3 | 115.50 | 562.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 0.00 | 5.00 | 2.78 | 3.10 | -8.3 | 0.00 | 0.00 | |
Maximum of Months | 25.60 | 31.70 | 26.63 | 14.40 | 25.66 | 379.00 | 741.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 4.29 | 14.52 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 3.18 | 19.75 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 3.75 | 28.43 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 5.88 | 38.20 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 9.06 | 44.89 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 12.40 | 51.07 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 15.02 | 51.61 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 16.22 | 43.31 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 15.63 | 34.41 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 13.44 | 22.83 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 10.25 | 13.98 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 6.92 | 10.24 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 9.71 | 31.16 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 3.18 | 10.24 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 16.22 | 51.61 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK1
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.395436E+09 | -268563202.2 | 0.00 | 0.00 | 744.00 | 0.00 | -126872715.7 | 58.99 | 0.00 | 0.00 |
February | 0.362814E+09 | -248798832.6 | 0.00 | 0.00 | 672.00 | 0.00 | -114015283.6 | 59.00 | 0.00 | 0.00 |
March | 0.401794E+09 | -276970810.9 | 0.00 | 0.00 | 744.00 | 0.00 | -124822698.0 | 58.99 | 0.00 | 0.00 |
April | 0.372483E+09 | -254737229.0 | 0.00 | 0.00 | 720.00 | 0.00 | -117745980.4 | 58.99 | 0.00 | 0.00 |
May | 0.363045E+09 | -247765643.4 | 0.00 | 0.00 | 744.00 | 0.00 | -115279198.9 | 58.99 | 0.00 | 0.00 |
June | 0.335464E+09 | -225755501.6 | 0.00 | 0.00 | 720.00 | 0.00 | -109708608.7 | 58.99 | 0.00 | 0.00 |
July | 0.328436E+09 | -215989607.0 | 0.00 | 0.00 | 744.00 | 0.00 | -112446643.8 | 58.99 | 0.00 | 0.00 |
August | 0.326848E+09 | -214295098.0 | 0.00 | 0.00 | 744.00 | 0.00 | -112552643.7 | 58.99 | 0.00 | 0.00 |
September | 0.318896E+09 | -208173374.1 | 0.00 | 0.00 | 720.00 | 0.00 | -110723017.4 | 58.99 | 0.00 | 0.00 |
October | 0.343914E+09 | -223683144.8 | 0.00 | 0.00 | 744.00 | 0.00 | -120230989.5 | 58.99 | 0.00 | 0.00 |
November | 0.350199E+09 | -230934204.6 | 0.00 | 0.00 | 720.00 | 0.00 | -119265271.5 | 58.99 | 0.00 | 0.00 |
December | 0.382218E+09 | -255966586.7 | 0.00 | 0.00 | 744.00 | 0.00 | -126251425.0 | 59.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.428155E+10 | -.287163E+10 | 8760.00 | -.140991E+10 | 58.99 | |||||
Minimum of Months | 0.318896E+09 | -276970810.9 | 0.00 | 0.00 | 672.00 | 0.00 | -126872715.7 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.401794E+09 | -208173374.1 | 0.00 | 0.00 | 744.00 | 0.00 | -109708608.7 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK2
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.394103E+09 | -268561952.8 | 0.00 | 0.00 | 744.00 | 0.00 | -125540679.3 | 59.00 | 0.00 | 0.00 |
February | 0.361266E+09 | -248803067.7 | 0.00 | 0.00 | 672.00 | 0.00 | -112462612.2 | 58.99 | 0.00 | 0.00 |
March | 0.399409E+09 | -276976606.9 | 0.00 | 0.00 | 744.00 | 0.00 | -122432038.6 | 58.99 | 0.00 | 0.00 |
April | 0.370165E+09 | -254739234.9 | 0.00 | 0.00 | 720.00 | 0.00 | -115425809.8 | 58.99 | 0.00 | 0.00 |
May | 0.361787E+09 | -247767099.3 | 0.00 | 0.00 | 744.00 | 0.00 | -114020028.5 | 58.99 | 0.00 | 0.00 |
June | 0.334926E+09 | -225764525.3 | 0.00 | 0.00 | 720.00 | 0.00 | -109161571.3 | 58.99 | 0.00 | 0.00 |
July | 0.328337E+09 | -215982358.5 | 0.00 | 0.00 | 744.00 | 0.00 | -112354995.8 | 58.99 | 0.00 | 0.00 |
August | 0.326665E+09 | -214292188.9 | 0.00 | 0.00 | 744.00 | 0.00 | -112372800.8 | 58.99 | 0.00 | 0.00 |
September | 0.318044E+09 | -208169190.8 | 0.00 | 0.00 | 720.00 | 0.00 | -109874527.0 | 58.99 | 0.00 | 0.00 |
October | 0.341301E+09 | -223673168.3 | 0.00 | 0.00 | 744.00 | 0.00 | -117628317.5 | 58.99 | 0.00 | 0.00 |
November | 0.348186E+09 | -230933811.3 | 0.00 | 0.00 | 720.00 | 0.00 | -117252219.2 | 58.99 | 0.00 | 0.00 |
December | 0.380474E+09 | -255980976.9 | 0.00 | 0.00 | 744.00 | 0.00 | -124493402.7 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.426466E+10 | -.287164E+10 | 8760.00 | -.139302E+10 | 58.99 | |||||
Minimum of Months | 0.318044E+09 | -276976606.9 | 0.00 | 0.00 | 672.00 | 0.00 | -125540679.3 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.399409E+09 | -208169190.8 | 0.00 | 0.00 | 744.00 | 0.00 | -109161571.3 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK3
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.364163E+09 | -236168813.7 | 0.00 | 0.00 | 744.00 | 0.00 | -127994611.2 | 58.99 | 0.00 | 0.00 |
February | 0.333499E+09 | -218968938.2 | 0.00 | 0.00 | 672.00 | 0.00 | -114529846.2 | 58.99 | 0.00 | 0.00 |
March | 0.371788E+09 | -247377296.9 | 0.00 | 0.00 | 744.00 | 0.00 | -124410569.5 | 58.99 | 0.00 | 0.00 |
April | 0.340650E+09 | -223869156.9 | 0.00 | 0.00 | 720.00 | 0.00 | -116781004.0 | 58.99 | 0.00 | 0.00 |
May | 0.333564E+09 | -219767090.7 | 0.00 | 0.00 | 744.00 | 0.00 | -113796972.6 | 59.00 | 0.00 | 0.00 |
June | 0.309048E+09 | -201197177.7 | 0.00 | 0.00 | 720.00 | 0.00 | -107851233.1 | 58.99 | 0.00 | 0.00 |
July | 0.299105E+09 | -188648186.8 | 0.00 | 0.00 | 744.00 | 0.00 | -110457026.8 | 59.00 | 0.00 | 0.00 |
August | 0.302380E+09 | -191541958.4 | 0.00 | 0.00 | 744.00 | 0.00 | -110837740.7 | 58.99 | 0.00 | 0.00 |
September | 0.292001E+09 | -182832003.2 | 0.00 | 0.00 | 720.00 | 0.00 | -109169382.0 | 58.99 | 0.00 | 0.00 |
October | 0.316228E+09 | -196718116.8 | 0.00 | 0.00 | 744.00 | 0.00 | -119510112.0 | 58.99 | 0.00 | 0.00 |
November | 0.323149E+09 | -203898914.5 | 0.00 | 0.00 | 720.00 | 0.00 | -119249986.3 | 58.99 | 0.00 | 0.00 |
December | 0.350216E+09 | -223417567.2 | 0.00 | 0.00 | 744.00 | 0.00 | -126798350.7 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.393579E+10 | -.253441E+10 | 8760.00 | -.140139E+10 | 58.99 | |||||
Minimum of Months | 0.292001E+09 | -247377296.9 | 0.00 | 0.00 | 672.00 | 0.00 | -127994611.2 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.371788E+09 | -182832003.2 | 0.00 | 0.00 | 744.00 | 0.00 | -107851233.1 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK4
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.364633E+09 | -236159646.9 | 0.00 | 0.00 | 744.00 | 0.00 | -128473735.1 | 59.00 | 0.00 | 0.00 |
February | 0.333906E+09 | -218949119.7 | 0.00 | 0.00 | 672.00 | 0.00 | -114956873.8 | 59.00 | 0.00 | 0.00 |
March | 0.372291E+09 | -247376634.0 | 0.00 | 0.00 | 744.00 | 0.00 | -124913920.2 | 58.99 | 0.00 | 0.00 |
April | 0.341093E+09 | -223870016.5 | 0.00 | 0.00 | 720.00 | 0.00 | -117223370.4 | 58.99 | 0.00 | 0.00 |
May | 0.333823E+09 | -219787022.1 | 0.00 | 0.00 | 744.00 | 0.00 | -114035954.9 | 58.99 | 0.00 | 0.00 |
June | 0.309110E+09 | -201217165.8 | 0.00 | 0.00 | 720.00 | 0.00 | -107892773.6 | 58.99 | 0.00 | 0.00 |
July | 0.299064E+09 | -188655524.1 | 0.00 | 0.00 | 744.00 | 0.00 | -110408920.2 | 58.99 | 0.00 | 0.00 |
August | 0.302373E+09 | -191550915.7 | 0.00 | 0.00 | 744.00 | 0.00 | -110821720.0 | 58.99 | 0.00 | 0.00 |
September | 0.292175E+09 | -182814072.2 | 0.00 | 0.00 | 720.00 | 0.00 | -109360451.2 | 59.00 | 0.00 | 0.00 |
October | 0.316887E+09 | -196735981.7 | 0.00 | 0.00 | 744.00 | 0.00 | -120151437.7 | 58.99 | 0.00 | 0.00 |
November | 0.323727E+09 | -203873353.7 | 0.00 | 0.00 | 720.00 | 0.00 | -119854107.1 | 59.00 | 0.00 | 0.00 |
December | 0.350666E+09 | -223426675.4 | 0.00 | 0.00 | 744.00 | 0.00 | -127239580.0 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.393975E+10 | -.253442E+10 | 8760.00 | -.140533E+10 | 58.99 | |||||
Minimum of Months | 0.292175E+09 | -247376634.0 | 0.00 | 0.00 | 672.00 | 0.00 | -128473735.1 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.372291E+09 | -182814072.2 | 0.00 | 0.00 | 744.00 | 0.00 | -107892773.6 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK5
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.353379E+09 | -223213786.1 | 0.00 | 0.00 | 744.00 | 0.00 | -130164970.7 | 59.00 | 0.00 | 0.00 |
February | 0.323569E+09 | -207060292.2 | 0.00 | 0.00 | 672.00 | 0.00 | -116508319.9 | 58.99 | 0.00 | 0.00 |
March | 0.360910E+09 | -234064493.7 | 0.00 | 0.00 | 744.00 | 0.00 | -126845386.6 | 58.99 | 0.00 | 0.00 |
April | 0.330839E+09 | -211840767.6 | 0.00 | 0.00 | 720.00 | 0.00 | -118997878.6 | 59.00 | 0.00 | 0.00 |
May | 0.323583E+09 | -207835748.7 | 0.00 | 0.00 | 744.00 | 0.00 | -115747427.7 | 59.00 | 0.00 | 0.00 |
June | 0.299564E+09 | -190381650.6 | 0.00 | 0.00 | 720.00 | 0.00 | -109182463.9 | 58.99 | 0.00 | 0.00 |
July | 0.289694E+09 | -178417935.7 | 0.00 | 0.00 | 744.00 | 0.00 | -111275567.7 | 58.99 | 0.00 | 0.00 |
August | 0.292937E+09 | -181315396.6 | 0.00 | 0.00 | 744.00 | 0.00 | -111621332.5 | 58.96 | 0.00 | 0.00 |
September | 0.283653E+09 | -172983433.6 | 0.00 | 0.00 | 720.00 | 0.00 | -110669912.7 | 59.00 | 0.00 | 0.00 |
October | 0.308155E+09 | -185943830.1 | 0.00 | 0.00 | 744.00 | 0.00 | -122211652.2 | 58.99 | 0.00 | 0.00 |
November | 0.314525E+09 | -192582936.1 | 0.00 | 0.00 | 720.00 | 0.00 | -121942499.4 | 58.99 | 0.00 | 0.00 |
December | 0.340394E+09 | -211287865.7 | 0.00 | 0.00 | 744.00 | 0.00 | -129106008.2 | 59.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.382120E+10 | -.239693E+10 | 8760.00 | -.142427E+10 | 58.99 | |||||
Minimum of Months | 0.283653E+09 | -234064493.7 | 0.00 | 0.00 | 672.00 | 0.00 | -130164970.7 | 58.96 | 0.00 | 0.00 |
Maximum of Months | 0.360910E+09 | -172983433.6 | 0.00 | 0.00 | 744.00 | 0.00 | -109182463.9 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK6
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.353259E+09 | -223212110.8 | 0.00 | 0.00 | 744.00 | 0.00 | -130047370.6 | 59.00 | 0.00 | 0.00 |
February | 0.323491E+09 | -207059698.5 | 0.00 | 0.00 | 672.00 | 0.00 | -116431637.3 | 58.99 | 0.00 | 0.00 |
March | 0.360871E+09 | -234068351.6 | 0.00 | 0.00 | 744.00 | 0.00 | -126802446.2 | 58.99 | 0.00 | 0.00 |
April | 0.330873E+09 | -211852818.8 | 0.00 | 0.00 | 720.00 | 0.00 | -119020395.0 | 58.99 | 0.00 | 0.00 |
May | 0.323740E+09 | -207840519.3 | 0.00 | 0.00 | 744.00 | 0.00 | -115899130.8 | 58.99 | 0.00 | 0.00 |
June | 0.299725E+09 | -190387418.9 | 0.00 | 0.00 | 720.00 | 0.00 | -109337984.9 | 58.99 | 0.00 | 0.00 |
July | 0.289836E+09 | -178412890.3 | 0.00 | 0.00 | 744.00 | 0.00 | -111422928.4 | 59.00 | 0.00 | 0.00 |
August | 0.293092E+09 | -181204135.1 | 0.00 | 0.00 | 744.00 | 0.00 | -111887669.9 | 59.01 | 0.00 | 0.00 |
September | 0.283748E+09 | -173031712.4 | 0.00 | 0.00 | 720.00 | 0.00 | -110716313.1 | 58.98 | 0.00 | 0.00 |
October | 0.308248E+09 | -185932296.2 | 0.00 | 0.00 | 744.00 | 0.00 | -122316081.5 | 58.99 | 0.00 | 0.00 |
November | 0.314556E+09 | -192569149.1 | 0.00 | 0.00 | 720.00 | 0.00 | -121986376.1 | 59.00 | 0.00 | 0.00 |
December | 0.340274E+09 | -211319614.6 | 0.00 | 0.00 | 744.00 | 0.00 | -128954085.1 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.382171E+10 | -.239689E+10 | 8760.00 | -.142482E+10 | 58.99 | |||||
Minimum of Months | 0.283748E+09 | -234068351.6 | 0.00 | 0.00 | 672.00 | 0.00 | -130047370.6 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.360871E+09 | -173031712.4 | 0.00 | 0.00 | 744.00 | 0.00 | -109337984.9 | 59.01 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK7
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.353301E+09 | -223212703.2 | 0.00 | 0.00 | 744.00 | 0.00 | -130087905.7 | 59.00 | 0.00 | 0.00 |
February | 0.323550E+09 | -207061741.4 | 0.00 | 0.00 | 672.00 | 0.00 | -116488542.7 | 58.99 | 0.00 | 0.00 |
March | 0.360986E+09 | -234066017.4 | 0.00 | 0.00 | 744.00 | 0.00 | -126919853.2 | 58.99 | 0.00 | 0.00 |
April | 0.331055E+09 | -211840224.2 | 0.00 | 0.00 | 720.00 | 0.00 | -119215192.7 | 59.00 | 0.00 | 0.00 |
May | 0.324038E+09 | -207828304.3 | 0.00 | 0.00 | 744.00 | 0.00 | -116209514.2 | 59.00 | 0.00 | 0.00 |
June | 0.299884E+09 | -190379566.6 | 0.00 | 0.00 | 720.00 | 0.00 | -109504351.4 | 58.99 | 0.00 | 0.00 |
July | 0.289908E+09 | -178428618.0 | 0.00 | 0.00 | 744.00 | 0.00 | -111479097.8 | 58.99 | 0.00 | 0.00 |
August | 0.293143E+09 | -181314137.9 | 0.00 | 0.00 | 744.00 | 0.00 | -111828517.6 | 58.96 | 0.00 | 0.00 |
September | 0.283897E+09 | -172989287.7 | 0.00 | 0.00 | 720.00 | 0.00 | -110907957.7 | 59.00 | 0.00 | 0.00 |
October | 0.308425E+09 | -185921249.3 | 0.00 | 0.00 | 744.00 | 0.00 | -122503338.3 | 59.00 | 0.00 | 0.00 |
November | 0.314700E+09 | -192566612.5 | 0.00 | 0.00 | 720.00 | 0.00 | -122133618.5 | 59.00 | 0.00 | 0.00 |
December | 0.340334E+09 | -211322130.0 | 0.00 | 0.00 | 744.00 | 0.00 | -129011926.8 | 58.98 | 0.00 | 0.00 |
Annual Sum or Average | 0.382322E+10 | -.239693E+10 | 8760.00 | -.142629E+10 | 58.99 | |||||
Minimum of Months | 0.283897E+09 | -234066017.4 | 0.00 | 0.00 | 672.00 | 0.00 | -130087905.7 | 58.96 | 0.00 | 0.00 |
Maximum of Months | 0.360986E+09 | -172989287.7 | 0.00 | 0.00 | 744.00 | 0.00 | -109504351.4 | 59.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 214.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 226.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 334.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 285.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 428.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 400.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 414.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 410.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 326.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 325.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 254.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 186.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3807.33 | ||||||||||
Minimum of Months | 186.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 428.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.416170E+11 | 73546.52 | 01-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.289611E+11 | 73546.52 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.171208E+11 | 73546.52 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.749127E+10 | 73546.52 | 01-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.201727E+09 | 73546.52 | 01-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.113523E+09 | 73546.52 | 29-SEP-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.202887E+10 | 73546.52 | 08-OCT-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.166134E+11 | 73546.52 | 10-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.319690E+11 | 73546.52 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.146117E+12 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.416170E+11 | 73546.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.161876E+11 | 37529.79 | 01-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109154E+11 | 37529.79 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.588508E+10 | 37529.79 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.234560E+10 | 37529.79 | 01-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 12726402.36 | 22032.15 | 02-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 7344300.90 | 10722.78 | 30-SEP-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.330412E+09 | 33843.40 | 27-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.601674E+10 | 37529.79 | 10-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.121498E+11 | 37529.79 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.538507E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.161876E+11 | 37529.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_3:3_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.177686E+11 | 37730.70 | 01-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121958E+11 | 37730.70 | 01-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.693240E+10 | 37730.70 | 01-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.291958E+10 | 37730.70 | 02-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 50554672.46 | 20048.96 | 02-MAY-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 28259026.74 | 9181.55 | 30-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.709547E+09 | 28438.77 | 17-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.691570E+10 | 37730.70 | 11-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.135744E+11 | 37730.70 | 01-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.610949E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.177686E+11 | 37730.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_4:4_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.181625E+11 | 37796.65 | 01-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.125069E+11 | 37796.65 | 01-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.720034E+10 | 37796.65 | 01-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.309085E+10 | 37796.65 | 01-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 72923798.77 | 25607.15 | 02-MAY-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 35894695.02 | 13675.66 | 30-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.867406E+09 | 34262.23 | 17-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.716833E+10 | 37796.65 | 11-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.139161E+11 | 37796.65 | 01-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.630212E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.181625E+11 | 37796.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_5:5_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.186506E+11 | 37952.94 | 01-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.129201E+11 | 37952.94 | 01-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.760301E+10 | 37952.94 | 01-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.333866E+10 | 37952.94 | 01-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.101491E+09 | 30910.63 | 02-MAY-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 54707937.47 | 18683.49 | 30-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.108696E+10 | 37952.94 | 08-OCT-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.751107E+10 | 37952.94 | 10-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.143753E+11 | 37952.94 | 01-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.656419E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.186506E+11 | 37952.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_6:6_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.360725E+11 | 71873.76 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.252158E+11 | 71873.76 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.154461E+11 | 71873.76 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.712345E+10 | 71873.76 | 01-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.305022E+09 | 71873.76 | 01-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 2352312.59 | 1001.62 | 05-JUN-11:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.241884E+09 | 71873.76 | 29-SEP-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.304771E+10 | 71873.76 | 01-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.150591E+11 | 71873.76 | 10-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.280942E+11 | 71873.76 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.130608E+12 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.360725E+11 | 71873.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_7:7_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.189108E+11 | 38350.31 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.132440E+11 | 38350.31 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.813711E+10 | 38350.31 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.376886E+10 | 38350.31 | 01-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.164547E+09 | 38350.31 | 01-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 3245913.41 | 734.15 | 05-JUN-11:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.133956E+09 | 38350.31 | 29-SEP-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.160887E+10 | 38350.31 | 01-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.793174E+10 | 38350.31 | 05-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.147586E+11 | 38350.31 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.686617E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.189108E+11 | 38350.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_8:8_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.189631E+11 | 38325.79 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.133216E+11 | 38325.79 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.824251E+10 | 38325.79 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.385881E+10 | 38325.79 | 01-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.178204E+09 | 38325.79 | 01-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 8144561.86 | 1376.97 | 05-JUN-11:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.152342E+09 | 38325.79 | 29-SEP-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.169744E+10 | 38325.79 | 01-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.801554E+10 | 38325.79 | 05-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.148327E+11 | 38325.79 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.692703E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.189631E+11 | 38325.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_9:9_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.193895E+11 | 38534.06 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.137162E+11 | 38534.06 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.866861E+10 | 38534.06 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.418968E+10 | 38534.06 | 01-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.220252E+09 | 38534.06 | 01-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 24996385.50 | 8821.67 | 05-JUN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.200727E+09 | 38534.06 | 29-SEP-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.194796E+10 | 38534.06 | 01-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.832123E+10 | 38534.06 | 05-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.152144E+11 | 38534.06 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.718936E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.193895E+11 | 38534.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_10:10_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.243631E+11 | 41709.55 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.174016E+11 | 41709.55 | 01-FEB-06:52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.114617E+11 | 41709.55 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.578956E+10 | 41709.55 | 01-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.431540E+09 | 41709.55 | 01-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 99870386.22 | 41709.55 | 05-JUN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.350198E+09 | 41709.55 | 27-SEP-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.274085E+10 | 41709.55 | 01-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.104813E+11 | 41709.55 | 01-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.188654E+11 | 41709.55 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.919852E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.243631E+11 | 41709.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 2653.61 | 2060.08 | 0.51 | 19-MAR-19:10 | 0.40 | 0.00 |
April | 0.00 | 0.00 | 0.244429E+10 | 0.173428E+10 | 25267.47 | 16-APR-16:10 | 18377.13 | 0.00 |
May | 0.00 | 0.00 | 0.414303E+10 | 0.292782E+10 | 24509.81 | 31-MAY-15:00 | 19653.34 | 0.00 |
June | 0.00 | 0.00 | 0.182338E+11 | 0.125870E+11 | 57605.93 | 26-JUN-07:02 | 31549.49 | 0.00 |
July | 0.00 | 0.00 | 0.249054E+11 | 0.160149E+11 | 56983.53 | 07-JUL-07:02 | 25400.77 | 0.00 |
August | 0.00 | 0.00 | 0.220703E+11 | 0.145291E+11 | 59063.10 | 03-AUG-07:02 | 28132.87 | 0.00 |
September | 0.00 | 0.00 | 0.103123E+11 | 0.833262E+10 | 48860.68 | 11-SEP-07:03 | 27154.25 | 0.00 |
October | 0.00 | 0.00 | 97898129.47 | 91383200.66 | 8703.54 | 20-OCT-15:00 | 8394.21 | 0.00 |
November | 0.00 | 0.00 | 13705.59 | 12221.43 | 1.48 | 03-NOV-14:40 | 1.36 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.822070E+11 | 0.562171E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.249054E+11 | 0.160149E+11 | 59063.10 | 31549.49 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 1843623.78 | 1675260.65 | 1628.95 | 25-MAR-21:40 | 1505.89 | 0.00 |
April | 0.00 | 0.00 | 0.150719E+10 | 0.109030E+10 | 27663.30 | 16-APR-19:37 | 18294.36 | 0.00 |
May | 0.00 | 0.00 | 0.292692E+10 | 0.206851E+10 | 27984.44 | 29-MAY-17:01 | 16223.94 | 0.00 |
June | 0.00 | 0.00 | 0.106565E+11 | 0.744283E+10 | 28870.11 | 27-JUN-07:02 | 15971.74 | 0.00 |
July | 0.00 | 0.00 | 0.148254E+11 | 0.961314E+10 | 28842.78 | 17-JUL-20:02 | 13296.56 | 0.00 |
August | 0.00 | 0.00 | 0.133304E+11 | 0.879513E+10 | 29271.26 | 03-AUG-07:02 | 16613.79 | 0.00 |
September | 0.00 | 0.00 | 0.627751E+10 | 0.504622E+10 | 27800.88 | 11-SEP-22:54 | 15472.69 | 0.00 |
October | 0.00 | 0.00 | 87171763.36 | 81641387.45 | 24963.87 | 11-OCT-20:29 | 24634.33 | 0.00 |
November | 0.00 | 0.00 | 4059221.26 | 3779702.74 | 2482.39 | 03-NOV-20:40 | 2482.39 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.496170E+11 | 0.341432E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.148254E+11 | 0.961314E+10 | 29271.26 | 24634.33 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.104598E+10 | 0.746860E+09 | 13568.03 | 18-APR-14:00 | 9685.60 | 0.00 |
May | 0.00 | 0.00 | 0.204385E+10 | 0.147481E+10 | 13320.33 | 31-MAY-13:00 | 10639.99 | 0.00 |
June | 0.00 | 0.00 | 0.800191E+10 | 0.557421E+10 | 29433.93 | 26-JUN-06:02 | 13781.30 | 0.00 |
July | 0.00 | 0.00 | 0.107642E+11 | 0.708810E+10 | 29065.03 | 27-JUL-06:02 | 13286.60 | 0.00 |
August | 0.00 | 0.00 | 0.104044E+11 | 0.699657E+10 | 30248.18 | 04-AUG-06:02 | 14811.67 | 0.00 |
September | 0.00 | 0.00 | 0.458596E+10 | 0.378440E+10 | 27818.05 | 11-SEP-06:02 | 15928.14 | 0.00 |
October | 0.00 | 0.00 | 60916158.75 | 56995824.90 | 4910.14 | 20-OCT-15:00 | 4772.27 | 0.00 |
November | 0.00 | 0.00 | 10158.80 | 9148.30 | 0.84 | 03-NOV-14:30 | 0.77 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.369072E+11 | 0.257220E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.107642E+11 | 0.708810E+10 | 30248.18 | 15928.14 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.102686E+10 | 0.732349E+09 | 13510.15 | 18-APR-14:00 | 9640.25 | 0.00 |
May | 0.00 | 0.00 | 0.199690E+10 | 0.144089E+10 | 13293.28 | 31-MAY-13:00 | 10618.16 | 0.00 |
June | 0.00 | 0.00 | 0.799552E+10 | 0.557047E+10 | 29489.32 | 26-JUN-06:02 | 13822.71 | 0.00 |
July | 0.00 | 0.00 | 0.107843E+11 | 0.710193E+10 | 29118.35 | 27-JUL-06:02 | 13316.40 | 0.00 |
August | 0.00 | 0.00 | 0.104004E+11 | 0.699489E+10 | 30305.86 | 04-AUG-06:02 | 14858.75 | 0.00 |
September | 0.00 | 0.00 | 0.457975E+10 | 0.377814E+10 | 27870.82 | 11-SEP-06:02 | 15972.83 | 0.00 |
October | 0.00 | 0.00 | 55281872.53 | 51886918.29 | 4694.49 | 20-OCT-15:00 | 4563.71 | 0.00 |
November | 0.00 | 0.00 | 7963.71 | 7237.92 | 0.75 | 03-NOV-14:40 | 0.70 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.368390E+11 | 0.256706E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.107843E+11 | 0.710193E+10 | 30305.86 | 15972.83 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.978152E+09 | 0.695064E+09 | 13291.20 | 18-APR-14:00 | 9456.69 | 0.00 |
May | 0.00 | 0.00 | 0.188421E+10 | 0.135877E+10 | 13107.07 | 31-MAY-13:00 | 10448.78 | 0.00 |
June | 0.00 | 0.00 | 0.778395E+10 | 0.541528E+10 | 29714.45 | 26-JUN-06:02 | 13895.53 | 0.00 |
July | 0.00 | 0.00 | 0.105213E+11 | 0.692067E+10 | 29340.48 | 27-JUL-06:02 | 13371.99 | 0.00 |
August | 0.00 | 0.00 | 0.101310E+11 | 0.680750E+10 | 30524.57 | 04-AUG-06:02 | 14823.76 | 0.00 |
September | 0.00 | 0.00 | 0.446636E+10 | 0.368054E+10 | 28083.08 | 11-SEP-06:02 | 16065.23 | 0.00 |
October | 0.00 | 0.00 | 47031216.63 | 44367237.11 | 4375.39 | 20-OCT-15:00 | 4249.96 | 0.00 |
November | 0.00 | 0.00 | 4458.81 | 4050.23 | 0.62 | 03-NOV-14:40 | 0.57 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.358120E+11 | 0.249222E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.105213E+11 | 0.692067E+10 | 30524.57 | 16065.23 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.156794E+10 | 0.108702E+10 | 23602.21 | 18-APR-14:10 | 16448.27 | 0.00 |
May | 0.00 | 0.00 | 0.297988E+10 | 0.212003E+10 | 23508.75 | 31-MAY-15:00 | 18580.97 | 0.00 |
June | 0.00 | 0.00 | 0.132087E+11 | 0.908148E+10 | 56497.99 | 26-JUN-07:02 | 31052.04 | 0.00 |
July | 0.00 | 0.00 | 0.181712E+11 | 0.117106E+11 | 55592.04 | 07-JUL-07:02 | 25028.37 | 0.00 |
August | 0.00 | 0.00 | 0.171737E+11 | 0.113382E+11 | 57229.47 | 04-AUG-07:02 | 28780.73 | 0.00 |
September | 0.00 | 0.00 | 0.764993E+10 | 0.619659E+10 | 53586.47 | 11-SEP-07:03 | 30191.84 | 0.00 |
October | 0.00 | 0.00 | 57325866.94 | 54086930.23 | 6885.53 | 20-OCT-15:00 | 6598.09 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.608087E+11 | 0.415880E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.181712E+11 | 0.117106E+11 | 57229.47 | 31052.04 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.808594E+09 | 0.560525E+09 | 12364.65 | 18-APR-14:10 | 8615.52 | 0.00 |
May | 0.00 | 0.00 | 0.151442E+10 | 0.107955E+10 | 12347.04 | 31-MAY-15:00 | 9756.35 | 0.00 |
June | 0.00 | 0.00 | 0.682829E+10 | 0.469987E+10 | 31026.73 | 26-JUN-07:02 | 17017.94 | 0.00 |
July | 0.00 | 0.00 | 0.940532E+10 | 0.607262E+10 | 30535.63 | 07-JUL-07:02 | 13733.85 | 0.00 |
August | 0.00 | 0.00 | 0.886195E+10 | 0.586574E+10 | 31409.31 | 04-AUG-07:02 | 15760.44 | 0.00 |
September | 0.00 | 0.00 | 0.397047E+10 | 0.321895E+10 | 27696.92 | 11-SEP-07:03 | 15616.96 | 0.00 |
October | 0.00 | 0.00 | 27434799.25 | 25986116.03 | 3587.15 | 20-OCT-15:00 | 3440.30 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.314165E+11 | 0.215232E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.940532E+10 | 0.607262E+10 | 31409.31 | 17017.94 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.789895E+09 | 0.546227E+09 | 12221.79 | 18-APR-14:10 | 8494.19 | 0.00 |
May | 0.00 | 0.00 | 0.146480E+10 | 0.104345E+10 | 12240.01 | 31-MAY-15:00 | 9655.59 | 0.00 |
June | 0.00 | 0.00 | 0.673445E+10 | 0.462746E+10 | 31047.23 | 26-JUN-07:02 | 16960.48 | 0.00 |
July | 0.00 | 0.00 | 0.928905E+10 | 0.598851E+10 | 30564.09 | 07-JUL-07:02 | 13723.52 | 0.00 |
August | 0.00 | 0.00 | 0.875147E+10 | 0.578493E+10 | 31435.88 | 04-AUG-07:02 | 15708.72 | 0.00 |
September | 0.00 | 0.00 | 0.392446E+10 | 0.317751E+10 | 26553.25 | 11-SEP-07:03 | 14950.85 | 0.00 |
October | 0.00 | 0.00 | 25801277.63 | 24433629.34 | 3491.58 | 20-OCT-15:00 | 3344.08 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.309799E+11 | 0.211925E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.928905E+10 | 0.598851E+10 | 31435.88 | 16960.48 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.743944E+09 | 0.512133E+09 | 11850.27 | 18-APR-14:10 | 8194.23 | 0.00 |
May | 0.00 | 0.00 | 0.134997E+10 | 0.962069E+09 | 12001.02 | 31-MAY-15:00 | 9444.56 | 0.00 |
June | 0.00 | 0.00 | 0.653412E+10 | 0.448052E+10 | 31312.98 | 26-JUN-07:02 | 16932.34 | 0.00 |
July | 0.00 | 0.00 | 0.905685E+10 | 0.583069E+10 | 30852.11 | 07-JUL-07:02 | 13799.75 | 0.00 |
August | 0.00 | 0.00 | 0.853533E+10 | 0.563651E+10 | 31721.38 | 04-AUG-07:02 | 15718.40 | 0.00 |
September | 0.00 | 0.00 | 0.383503E+10 | 0.310142E+10 | 23252.96 | 11-SEP-07:03 | 13060.73 | 0.00 |
October | 0.00 | 0.00 | 22178743.01 | 21035914.07 | 3263.54 | 20-OCT-15:00 | 3123.09 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.300774E+11 | 0.205444E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.905685E+10 | 0.583069E+10 | 31721.38 | 16932.34 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.685628E+09 | 0.468232E+09 | 11465.61 | 18-APR-14:10 | 7853.51 | 0.00 |
May | 0.00 | 0.00 | 0.117796E+10 | 0.843204E+09 | 11894.47 | 31-MAY-13:00 | 9226.89 | 0.00 |
June | 0.00 | 0.00 | 0.628669E+10 | 0.430726E+10 | 35008.08 | 26-JUN-07:02 | 17491.39 | 0.00 |
July | 0.00 | 0.00 | 0.882497E+10 | 0.569782E+10 | 34109.84 | 04-JUL-08:62 | 17451.36 | 0.00 |
August | 0.00 | 0.00 | 0.840223E+10 | 0.556841E+10 | 36018.41 | 04-AUG-07:02 | 15046.48 | 0.00 |
September | 0.00 | 0.00 | 0.384282E+10 | 0.311305E+10 | 15553.25 | 06-SEP-14:10 | 12097.00 | 0.00 |
October | 0.00 | 0.00 | 17728724.84 | 16875079.02 | 3012.00 | 20-OCT-15:00 | 2888.27 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.292380E+11 | 0.200149E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.882497E+10 | 0.569782E+10 | 36018.41 | 17491.39 | 0.00 |
Report: FanReportMonthly
For: PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.470372E+10 | 0.71 | 2563.55 | 01-JAN-08:08 | 0.94 |
February | 0.424021E+10 | 0.69 | 2563.55 | 01-FEB-08:13 | 0.95 |
March | 0.467160E+10 | 0.65 | 2563.55 | 01-MAR-08:09 | 0.95 |
April | 0.451525E+10 | 0.64 | 2563.55 | 01-APR-07:40 | 0.94 |
May | 0.465149E+10 | 0.63 | 2563.55 | 01-MAY-08:20 | 0.94 |
June | 0.451288E+10 | 0.63 | 2563.55 | 03-JUN-18:10 | 0.94 |
July | 0.466054E+10 | 0.63 | 2563.55 | 01-JUL-07:30 | 0.93 |
August | 0.465131E+10 | 0.63 | 2563.55 | 01-AUG-08:00 | 0.92 |
September | 0.452210E+10 | 0.64 | 2563.55 | 01-SEP-07:40 | 0.93 |
October | 0.465148E+10 | 0.64 | 2563.55 | 02-OCT-16:00 | 0.93 |
November | 0.450400E+10 | 0.65 | 2563.55 | 01-NOV-08:30 | 0.94 |
December | 0.469726E+10 | 0.68 | 2563.55 | 01-DEC-09:20 | 0.94 |
Annual Sum or Average | 0.549818E+11 | 0.65 | |||
Minimum of Months | 0.424021E+10 | 0.63 | 2563.55 | 0.92 | |
Maximum of Months | 0.470372E+10 | 0.71 | 2563.55 | 0.95 |
Report: FanReportMonthly
For: PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.189369E+10 | 0.61 | 1374.71 | 01-JAN-12:40 | 0.98 |
February | 0.170774E+10 | 0.55 | 1374.71 | 03-FEB-08:08 | 0.99 |
March | 0.194628E+10 | 0.55 | 1374.71 | 01-MAR-11:10 | 0.98 |
April | 0.194435E+10 | 0.57 | 1374.71 | 01-APR-07:09 | 0.98 |
May | 0.234099E+10 | 0.64 | 1374.71 | 02-MAY-09:10 | 0.98 |
June | 0.217704E+10 | 0.63 | 1374.71 | 08-JUN-11:10 | 0.97 |
July | 0.218702E+10 | 0.60 | 1374.71 | 01-JUL-08:70 | 0.97 |
August | 0.224305E+10 | 0.61 | 1374.71 | 02-AUG-09:20 | 0.97 |
September | 0.215905E+10 | 0.62 | 1374.71 | 01-SEP-07:40 | 0.97 |
October | 0.203327E+10 | 0.62 | 1374.71 | 01-OCT-12:10 | 0.98 |
November | 0.188809E+10 | 0.57 | 1374.71 | 06-NOV-20:30 | 0.97 |
December | 0.186894E+10 | 0.55 | 1374.71 | 01-DEC-09:40 | 0.98 |
Annual Sum or Average | 0.243895E+11 | 0.59 | |||
Minimum of Months | 0.170774E+10 | 0.55 | 1374.71 | 0.97 | |
Maximum of Months | 0.234099E+10 | 0.64 | 1374.71 | 0.99 |
Report: FanReportMonthly
For: PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.201062E+10 | 0.55 | 1385.21 | 01-JAN-08:06 | 0.98 |
February | 0.181945E+10 | 0.55 | 1385.21 | 07-FEB-17:10 | 0.98 |
March | 0.204479E+10 | 0.54 | 1385.21 | 01-MAR-07:50 | 0.99 |
April | 0.194483E+10 | 0.53 | 1385.21 | 01-APR-07:02 | 0.98 |
May | 0.202462E+10 | 0.53 | 1385.21 | 01-MAY-07:10 | 0.98 |
June | 0.197475E+10 | 0.53 | 1385.21 | 01-JUN-18:00 | 0.97 |
July | 0.199470E+10 | 0.52 | 1385.21 | 01-JUL-07:05 | 0.97 |
August | 0.204457E+10 | 0.53 | 1385.21 | 01-AUG-08:20 | 0.96 |
September | 0.194483E+10 | 0.53 | 1385.21 | 01-SEP-07:07 | 0.97 |
October | 0.200468E+10 | 0.53 | 1385.21 | 01-OCT-07:03 | 0.98 |
November | 0.194490E+10 | 0.53 | 1385.21 | 01-NOV-08:15 | 0.98 |
December | 0.199873E+10 | 0.55 | 1385.21 | 01-DEC-07:07 | 0.98 |
Annual Sum or Average | 0.237515E+11 | 0.54 | |||
Minimum of Months | 0.181945E+10 | 0.52 | 1385.21 | 0.96 | |
Maximum of Months | 0.204479E+10 | 0.55 | 1385.21 | 0.99 |
Report: FanReportMonthly
For: PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.201922E+10 | 0.56 | 1388.66 | 01-JAN-08:07 | 0.98 |
February | 0.182608E+10 | 0.56 | 1388.66 | 01-FEB-11:00 | 0.99 |
March | 0.205018E+10 | 0.54 | 1388.66 | 01-MAR-08:30 | 0.99 |
April | 0.194968E+10 | 0.53 | 1388.66 | 01-APR-06:40 | 0.98 |
May | 0.202966E+10 | 0.53 | 1388.66 | 01-MAY-07:30 | 0.98 |
June | 0.197967E+10 | 0.53 | 1388.66 | 03-JUN-15:30 | 0.97 |
July | 0.199967E+10 | 0.52 | 1388.66 | 01-JUL-07:05 | 0.97 |
August | 0.204966E+10 | 0.53 | 1388.66 | 07-AUG-14:10 | 0.98 |
September | 0.194968E+10 | 0.53 | 1388.66 | 01-SEP-07:00 | 0.97 |
October | 0.200967E+10 | 0.53 | 1388.66 | 01-OCT-08:30 | 0.98 |
November | 0.195057E+10 | 0.54 | 1388.66 | 03-NOV-13:20 | 0.98 |
December | 0.200564E+10 | 0.55 | 1388.66 | 01-DEC-07:35 | 0.98 |
Annual Sum or Average | 0.238194E+11 | 0.54 | |||
Minimum of Months | 0.182608E+10 | 0.52 | 1388.66 | 0.97 | |
Maximum of Months | 0.205018E+10 | 0.56 | 1388.66 | 0.99 |
Report: FanReportMonthly
For: PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.203346E+10 | 0.57 | 1396.83 | 03-JAN-18:40 | 0.99 |
February | 0.183806E+10 | 0.57 | 1396.83 | 02-FEB-19:00 | 0.99 |
March | 0.206232E+10 | 0.54 | 1396.83 | 01-MAR-11:10 | 0.98 |
April | 0.196115E+10 | 0.53 | 1396.83 | 01-APR-09:30 | 0.98 |
May | 0.204160E+10 | 0.53 | 1396.83 | 01-MAY-07:03 | 0.98 |
June | 0.199132E+10 | 0.53 | 1396.83 | 08-JUN-07:25 | 0.97 |
July | 0.201143E+10 | 0.52 | 1396.83 | 02-JUL-10:40 | 0.97 |
August | 0.206172E+10 | 0.53 | 1396.83 | 01-AUG-09:00 | 0.96 |
September | 0.196115E+10 | 0.53 | 1396.83 | 10-SEP-08:30 | 0.97 |
October | 0.202149E+10 | 0.53 | 1396.83 | 01-OCT-07:30 | 0.98 |
November | 0.196289E+10 | 0.54 | 1396.83 | 05-NOV-08:20 | 0.98 |
December | 0.201841E+10 | 0.56 | 1396.83 | 01-DEC-08:07 | 0.98 |
Annual Sum or Average | 0.239650E+11 | 0.54 | |||
Minimum of Months | 0.183806E+10 | 0.52 | 1396.83 | 0.96 | |
Maximum of Months | 0.206232E+10 | 0.57 | 1396.83 | 0.99 |
Report: FanReportMonthly
For: PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.335826E+10 | 0.55 | 2479.65 | 01-JAN-09:04 | 0.94 |
February | 0.302627E+10 | 0.52 | 2479.65 | 08-FEB-08:10 | 0.94 |
March | 0.338708E+10 | 0.49 | 2479.65 | 08-MAR-08:04 | 0.95 |
April | 0.321363E+10 | 0.47 | 2479.65 | 11-APR-13:00 | 0.93 |
May | 0.334753E+10 | 0.47 | 2479.65 | 01-MAY-12:00 | 0.94 |
June | 0.326719E+10 | 0.47 | 2479.65 | 09-JUN-17:20 | 0.93 |
July | 0.329397E+10 | 0.46 | 2479.65 | 07-JUL-19:15 | 0.93 |
August | 0.338323E+10 | 0.47 | 2479.65 | 07-AUG-18:10 | 0.94 |
September | 0.321363E+10 | 0.47 | 2479.65 | 08-SEP-19:25 | 0.93 |
October | 0.331182E+10 | 0.47 | 2479.65 | 07-OCT-17:30 | 0.94 |
November | 0.322234E+10 | 0.49 | 2479.65 | 12-NOV-11:00 | 0.94 |
December | 0.331714E+10 | 0.51 | 2479.65 | 03-DEC-15:10 | 0.94 |
Annual Sum or Average | 0.393421E+11 | 0.49 | |||
Minimum of Months | 0.302627E+10 | 0.46 | 2479.65 | 0.93 | |
Maximum of Months | 0.338708E+10 | 0.55 | 2479.65 | 0.95 |
Report: FanReportMonthly
For: PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.191680E+10 | 0.57 | 1417.60 | 01-JAN-10:40 | 0.98 |
February | 0.172813E+10 | 0.54 | 1417.60 | 02-FEB-20:40 | 0.99 |
March | 0.193612E+10 | 0.51 | 1417.60 | 01-MAR-19:40 | 0.98 |
April | 0.183721E+10 | 0.49 | 1417.60 | 01-APR-07:13 | 0.98 |
May | 0.191376E+10 | 0.49 | 1417.60 | 02-MAY-09:55 | 0.98 |
June | 0.186783E+10 | 0.49 | 1417.60 | 08-JUN-19:10 | 0.97 |
July | 0.188314E+10 | 0.48 | 1417.60 | 03-JUL-08:00 | 0.96 |
August | 0.193418E+10 | 0.49 | 1417.60 | 02-AUG-17:40 | 0.97 |
September | 0.183721E+10 | 0.49 | 1417.60 | 06-SEP-11:20 | 0.97 |
October | 0.189335E+10 | 0.49 | 1417.60 | 13-OCT-09:20 | 0.98 |
November | 0.184149E+10 | 0.51 | 1417.60 | 10-NOV-20:50 | 0.98 |
December | 0.189512E+10 | 0.53 | 1417.60 | 04-DEC-09:20 | 0.98 |
Annual Sum or Average | 0.224844E+11 | 0.51 | |||
Minimum of Months | 0.172813E+10 | 0.48 | 1417.60 | 0.96 | |
Maximum of Months | 0.193612E+10 | 0.57 | 1417.60 | 0.99 |
Report: FanReportMonthly
For: PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.191528E+10 | 0.58 | 1416.32 | 01-JAN-10:10 | 0.98 |
February | 0.172691E+10 | 0.54 | 1416.32 | 01-FEB-10:40 | 0.99 |
March | 0.193455E+10 | 0.51 | 1416.32 | 01-MAR-08:09 | 0.99 |
April | 0.183561E+10 | 0.49 | 1416.32 | 01-APR-08:40 | 0.98 |
May | 0.191203E+10 | 0.49 | 1416.32 | 01-MAY-07:02 | 0.98 |
June | 0.186614E+10 | 0.49 | 1416.32 | 05-JUN-11:10 | 0.97 |
July | 0.188144E+10 | 0.48 | 1416.32 | 01-JUL-08:20 | 0.97 |
August | 0.193243E+10 | 0.49 | 1416.32 | 01-AUG-08:40 | 0.96 |
September | 0.183555E+10 | 0.49 | 1416.32 | 01-SEP-07:50 | 0.97 |
October | 0.189164E+10 | 0.49 | 1416.32 | 03-OCT-09:30 | 0.98 |
November | 0.183994E+10 | 0.51 | 1416.32 | 01-NOV-08:65 | 0.98 |
December | 0.189356E+10 | 0.53 | 1416.32 | 01-DEC-08:09 | 0.98 |
Annual Sum or Average | 0.224651E+11 | 0.51 | |||
Minimum of Months | 0.172691E+10 | 0.48 | 1416.32 | 0.96 | |
Maximum of Months | 0.193455E+10 | 0.58 | 1416.32 | 0.99 |
Report: FanReportMonthly
For: PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.193476E+10 | 0.59 | 1427.21 | 04-JAN-08:07 | 0.99 |
February | 0.174285E+10 | 0.55 | 1427.21 | 10-FEB-10:50 | 0.98 |
March | 0.195034E+10 | 0.51 | 1427.21 | 06-MAR-13:50 | 0.98 |
April | 0.184996E+10 | 0.49 | 1427.21 | 01-APR-14:20 | 0.98 |
May | 0.192673E+10 | 0.49 | 1427.21 | 02-MAY-12:30 | 0.98 |
June | 0.188049E+10 | 0.49 | 1427.21 | 17-JUN-09:20 | 0.97 |
July | 0.189590E+10 | 0.48 | 1427.21 | 15-JUL-08:40 | 0.97 |
August | 0.194728E+10 | 0.49 | 1427.21 | 05-AUG-09:40 | 0.97 |
September | 0.184966E+10 | 0.49 | 1427.21 | 01-SEP-07:30 | 0.97 |
October | 0.190618E+10 | 0.49 | 1427.21 | 16-OCT-11:50 | 0.98 |
November | 0.185479E+10 | 0.51 | 1427.21 | 04-NOV-08:63 | 0.98 |
December | 0.190948E+10 | 0.53 | 1427.21 | 22-DEC-10:40 | 0.98 |
Annual Sum or Average | 0.226484E+11 | 0.51 | |||
Minimum of Months | 0.174285E+10 | 0.48 | 1427.21 | 0.97 | |
Maximum of Months | 0.195034E+10 | 0.59 | 1427.21 | 0.99 |
Report: FanReportMonthly
For: PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.225759E+10 | 0.73 | 1593.16 | 01-JAN-09:50 | 0.98 |
February | 0.200631E+10 | 0.67 | 1593.16 | 01-FEB-08:08 | 0.99 |
March | 0.220822E+10 | 0.59 | 1593.16 | 01-MAR-09:20 | 0.98 |
April | 0.207221E+10 | 0.51 | 1593.16 | 01-APR-08:70 | 0.98 |
May | 0.215076E+10 | 0.49 | 1593.16 | 01-MAY-07:06 | 0.98 |
June | 0.209914E+10 | 0.49 | 1593.16 | 03-JUN-09:50 | 0.98 |
July | 0.211635E+10 | 0.48 | 1593.16 | 01-JUL-08:20 | 0.97 |
August | 0.217370E+10 | 0.49 | 1593.16 | 01-AUG-11:10 | 0.97 |
September | 0.206473E+10 | 0.49 | 1593.16 | 01-SEP-08:40 | 0.97 |
October | 0.212782E+10 | 0.49 | 1593.16 | 01-OCT-08:40 | 0.98 |
November | 0.209994E+10 | 0.58 | 1593.16 | 01-NOV-07:15 | 0.98 |
December | 0.219175E+10 | 0.65 | 1593.16 | 01-DEC-08:10 | 0.98 |
Annual Sum or Average | 0.255685E+11 | 0.55 | |||
Minimum of Months | 0.200631E+10 | 0.48 | 1593.16 | 0.97 | |
Maximum of Months | 0.225759E+10 | 0.73 | 1593.16 | 0.99 |
Report: ZoneTemperatureOscillationReportMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 2.89 | 0.42 |
February | 2.38 | 0.37 |
March | 2.02 | 0.49 |
April | 0.88 | 0.88 |
May | 0.06 | 1.50 |
June | 0.08 | 0.00 |
July | 0.08 | 0.00 |
August | 0.08 | 0.00 |
September | 0.35 | 0.24 |
October | 0.56 | 1.50 |
November | 1.47 | 0.62 |
December | 3.16 | 0.79 |
Annual Sum or Average | 14.01 | 0.59 |
Minimum of Months | 0.06 | 0.00 |
Maximum of Months | 3.16 | 1.50 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.55 | 0.34 |
February | 0.56 | 0.64 |
March | 0.89 | 4.05 |
April | 1.05 | 3.92 |
May | 1.76 | 3.49 |
June | 2.79 | 2.43 |
July | 5.31 | 2.80 |
August | 5.32 | 3.93 |
September | 2.92 | 2.50 |
October | 1.44 | 3.85 |
November | 0.82 | 2.51 |
December | 0.68 | 0.00 |
Annual Sum or Average | 24.11 | 2.98 |
Minimum of Months | 0.55 | 0.00 |
Maximum of Months | 5.32 | 4.05 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 1.33 | 0.00 |
February | 0.57 | 0.00 |
March | 0.24 | 0.00 |
April | 0.98 | 0.43 |
May | 1.01 | 0.63 |
June | 2.93 | 0.71 |
July | 3.17 | 0.75 |
August | 2.13 | 0.75 |
September | 1.40 | 0.75 |
October | 1.36 | 0.61 |
November | 0.94 | 0.43 |
December | 0.54 | 0.00 |
Annual Sum or Average | 16.60 | 0.57 |
Minimum of Months | 0.24 | 0.00 |
Maximum of Months | 3.17 | 0.75 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 1.55 | 0.00 |
February | 0.84 | 0.00 |
March | 0.44 | 0.00 |
April | 0.92 | 0.46 |
May | 1.01 | 0.63 |
June | 3.18 | 0.71 |
July | 3.17 | 0.75 |
August | 2.13 | 0.75 |
September | 1.34 | 0.70 |
October | 1.36 | 0.57 |
November | 0.85 | 0.35 |
December | 0.82 | 0.00 |
Annual Sum or Average | 17.61 | 0.53 |
Minimum of Months | 0.44 | 0.00 |
Maximum of Months | 3.18 | 0.75 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 1.89 | 0.00 |
February | 1.25 | 0.00 |
March | 0.75 | 0.00 |
April | 0.89 | 0.47 |
May | 0.85 | 0.60 |
June | 3.04 | 0.73 |
July | 3.00 | 0.75 |
August | 1.97 | 0.75 |
September | 1.18 | 0.75 |
October | 0.78 | 0.75 |
November | 0.79 | 0.13 |
December | 1.23 | 0.00 |
Annual Sum or Average | 17.60 | 0.48 |
Minimum of Months | 0.75 | 0.00 |
Maximum of Months | 3.04 | 0.75 |
Report: ZoneTemperatureOscillationReportMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 3.52 | 0.00 |
February | 2.29 | 0.00 |
March | 0.89 | 0.00 |
April | 0.74 | 1.50 |
May | 0.00 | 0.00 |
June | 1.51 | 2.21 |
July | 1.29 | 2.59 |
August | 0.73 | 2.67 |
September | 0.68 | 3.30 |
October | 0.22 | 3.30 |
November | 1.30 | 0.00 |
December | 2.63 | 0.00 |
Annual Sum or Average | 15.83 | 0.81 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 3.52 | 3.30 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 2.63 | 0.00 |
February | 2.00 | 0.00 |
March | 0.71 | 0.00 |
April | 0.66 | 0.64 |
May | 0.00 | 0.00 |
June | 1.18 | 1.18 |
July | 1.21 | 1.38 |
August | 0.73 | 1.34 |
September | 0.63 | 1.65 |
October | 0.08 | 1.65 |
November | 0.98 | 0.00 |
December | 2.38 | 0.00 |
Annual Sum or Average | 13.19 | 0.43 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 2.63 | 1.65 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 2.62 | 0.00 |
February | 2.10 | 0.00 |
March | 0.71 | 0.00 |
April | 0.45 | 0.63 |
May | 0.00 | 0.00 |
June | 1.18 | 1.18 |
July | 1.21 | 1.38 |
August | 0.73 | 1.34 |
September | 0.63 | 1.65 |
October | 0.08 | 1.65 |
November | 0.98 | 0.00 |
December | 2.44 | 0.00 |
Annual Sum or Average | 13.12 | 0.42 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 2.62 | 1.65 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 3.02 | 0.00 |
February | 2.43 | 0.00 |
March | 0.89 | 0.00 |
April | 0.57 | 0.50 |
May | 0.00 | 0.00 |
June | 1.01 | 1.38 |
July | 1.12 | 1.49 |
August | 0.65 | 1.51 |
September | 0.63 | 1.65 |
October | 0.00 | 0.00 |
November | 1.09 | 0.00 |
December | 2.74 | 0.00 |
Annual Sum or Average | 14.15 | 0.38 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 3.02 | 1.65 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 4.81 | 0.00 |
February | 3.99 | 0.00 |
March | 3.24 | 0.00 |
April | 1.80 | 0.16 |
May | 0.46 | 0.00 |
June | 0.96 | 1.46 |
July | 1.15 | 1.45 |
August | 0.65 | 1.51 |
September | 0.79 | 1.30 |
October | 0.08 | 0.00 |
November | 2.71 | 0.00 |
December | 4.37 | 0.00 |
Annual Sum or Average | 25.02 | 0.21 |
Minimum of Months | 0.08 | 0.00 |
Maximum of Months | 4.81 | 1.51 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_1:1
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.470372E+10 | 0.520212E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.424021E+10 | 0.362014E+11 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.467161E+10 | 0.214011E+11 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.528327E+10 | 0.936409E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.594513E+10 | 0.252158E+09 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.101608E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.121802E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.113458E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.777469E+10 | 0.141903E+09 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.468281E+10 | 0.253609E+10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.450401E+10 | 0.207667E+11 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.469726E+10 | 0.399612E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.801895E+11 | 0.182646E+12 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.424021E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.121802E+11 | 0.520212E+11 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_2:2
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.189369E+10 | 0.202346E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.170774E+10 | 0.136443E+11 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.194688E+10 | 0.735636E+10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.237738E+10 | 0.293200E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.316060E+10 | 15908002.95 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.520790E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.625959E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.593631E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.394106E+10 | 9180376.12 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.205946E+10 | 0.413015E+09 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.188940E+10 | 0.752093E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.186894E+10 | 0.151872E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.382489E+11 | 0.673134E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.170774E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.625959E+10 | 0.202346E+11 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_3:3
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.201062E+10 | 0.222108E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.181945E+10 | 0.152448E+11 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.204479E+10 | 0.866550E+10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.225184E+10 | 0.364948E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.262409E+10 | 63193340.57 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.429077E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.504145E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.500788E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.330591E+10 | 35323783.42 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.202297E+10 | 0.886934E+09 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.194491E+10 | 0.864463E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.199873E+10 | 0.169680E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.343634E+11 | 0.763686E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.181945E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.504145E+10 | 0.222108E+11 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_4:4
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.201922E+10 | 0.227031E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.182608E+10 | 0.156336E+11 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.205018E+10 | 0.900043E+10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.225148E+10 | 0.386356E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.261605E+10 | 91154748.46 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.429423E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.505222E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.501253E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.330918E+10 | 44868368.77 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.202631E+10 | 0.108426E+10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.195058E+10 | 0.896042E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.200564E+10 | 0.173952E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.344137E+11 | 0.787765E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.182608E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.505222E+10 | 0.227031E+11 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_5:5
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.203346E+10 | 0.233132E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.183806E+10 | 0.161501E+11 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.206232E+10 | 0.950377E+10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.224974E+10 | 0.417332E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.259683E+10 | 0.126864E+09 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.425140E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.499797E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.495649E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.329101E+10 | 68384921.84 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.203570E+10 | 0.135870E+10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.196289E+10 | 0.938883E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.201841E+10 | 0.179691E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.342943E+11 | 0.820523E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.183806E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.499797E+10 | 0.233132E+11 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_6:6
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.335826E+10 | 0.450906E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.302627E+10 | 0.315197E+11 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.338708E+10 | 0.193077E+11 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.370895E+10 | 0.890431E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.428871E+10 | 0.381278E+09 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.737423E+10 | 2940390.74 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.880970E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.863230E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.565135E+10 | 0.302356E+09 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.333037E+10 | 0.380964E+10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.322234E+10 | 0.188239E+11 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.331714E+10 | 0.351178E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.581067E+11 | 0.163260E+12 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.302627E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.880970E+10 | 0.450906E+11 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_7:7
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.191680E+10 | 0.236385E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.172813E+10 | 0.165550E+11 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.193612E+10 | 0.101714E+11 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.207936E+10 | 0.471108E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.236700E+10 | 0.205684E+09 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.388178E+10 | 4057391.76 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.459055E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.450346E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.303691E+10 | 0.167445E+09 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.190174E+10 | 0.201108E+10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.184149E+10 | 0.991468E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.189512E+10 | 0.184482E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.316785E+11 | 0.858271E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.172813E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.459055E+10 | 0.236385E+11 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_8:8
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.191528E+10 | 0.237039E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.172691E+10 | 0.166520E+11 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.193455E+10 | 0.103031E+11 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.207254E+10 | 0.482351E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.235124E+10 | 0.222755E+09 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.385465E+10 | 10180702.32 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.455808E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.447223E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.302263E+10 | 0.190427E+09 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.189954E+10 | 0.212180E+10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.183994E+10 | 0.100194E+11 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.189356E+10 | 0.185408E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.315412E+11 | 0.865879E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.172691E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.455808E+10 | 0.237039E+11 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_9:9
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.193476E+10 | 0.242369E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.174285E+10 | 0.171453E+11 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.195034E+10 | 0.108358E+11 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.207417E+10 | 0.523711E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.233355E+10 | 0.275315E+09 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.381591E+10 | 31245481.88 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.451252E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.443078E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.301286E+10 | 0.250908E+09 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.191299E+10 | 0.243494E+10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.185479E+10 | 0.104015E+11 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.190948E+10 | 0.190180E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.314850E+11 | 0.898670E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.174285E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.451252E+10 | 0.242369E+11 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_10:10
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.225759E+10 | 0.304539E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.200631E+10 | 0.217520E+11 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.220822E+10 | 0.143272E+11 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.228169E+10 | 0.723696E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.251075E+10 | 0.539426E+09 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.398468E+10 | 0.124838E+09 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.469476E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.464249E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.324096E+10 | 0.437747E+09 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.213330E+10 | 0.342607E+10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.209994E+10 | 0.131017E+11 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.219175E+10 | 0.235818E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.342524E+11 | 0.114982E+12 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.200631E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.469476E+10 | 0.304539E+11 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_1:1
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.470372E+10 | 0.00 | 0.416170E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.424021E+10 | 0.00 | 0.289611E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.467160E+10 | 2653.61 | 0.171208E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.451525E+10 | 0.244429E+10 | 0.749127E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.465149E+10 | 0.414303E+10 | 0.201727E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.451288E+10 | 0.182338E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.466054E+10 | 0.249054E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.465131E+10 | 0.220703E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.452210E+10 | 0.103123E+11 | 0.113523E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.465148E+10 | 97898129.47 | 0.202887E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.450400E+10 | 13705.59 | 0.166134E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.469726E+10 | 0.00 | 0.319690E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.549818E+11 | 0.822070E+11 | 0.146117E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.424021E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.470372E+10 | 0.249054E+11 | 0.416170E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_2:2
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.189369E+10 | 0.00 | 0.161876E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.170774E+10 | 0.00 | 0.109154E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.194628E+10 | 1843623.78 | 0.588508E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.194435E+10 | 0.150719E+10 | 0.234560E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.234099E+10 | 0.292692E+10 | 12726402.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.217704E+10 | 0.106565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.218702E+10 | 0.148254E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.224305E+10 | 0.133304E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.215905E+10 | 0.627751E+10 | 7344300.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.203327E+10 | 87171763.36 | 0.330412E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.188809E+10 | 4059221.26 | 0.601674E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.186894E+10 | 0.00 | 0.121498E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.243895E+11 | 0.496170E+11 | 0.538507E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.170774E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.234099E+10 | 0.148254E+11 | 0.161876E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_3:3
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.201062E+10 | 0.00 | 0.177686E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.181945E+10 | 0.00 | 0.121958E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.204479E+10 | 0.00 | 0.693240E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.194483E+10 | 0.104598E+10 | 0.291958E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.202462E+10 | 0.204385E+10 | 50554672.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.197475E+10 | 0.800191E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.199470E+10 | 0.107642E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.204457E+10 | 0.104044E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.194483E+10 | 0.458596E+10 | 28259026.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.200468E+10 | 60916158.75 | 0.709547E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.194490E+10 | 10158.80 | 0.691570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.199873E+10 | 0.00 | 0.135744E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.237515E+11 | 0.369072E+11 | 0.610949E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.181945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.204479E+10 | 0.107642E+11 | 0.177686E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_4:4
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.201922E+10 | 0.00 | 0.181625E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.182608E+10 | 0.00 | 0.125069E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.205018E+10 | 0.00 | 0.720034E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.194968E+10 | 0.102686E+10 | 0.309085E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.202966E+10 | 0.199690E+10 | 72923798.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.197967E+10 | 0.799552E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.199967E+10 | 0.107843E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.204966E+10 | 0.104004E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.194968E+10 | 0.457975E+10 | 35894695.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.200967E+10 | 55281872.53 | 0.867406E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.195057E+10 | 7963.71 | 0.716833E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.200564E+10 | 0.00 | 0.139161E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.238194E+11 | 0.368390E+11 | 0.630212E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.182608E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.205018E+10 | 0.107843E+11 | 0.181625E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_5:5
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.203346E+10 | 0.00 | 0.186506E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.183806E+10 | 0.00 | 0.129201E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.206232E+10 | 0.00 | 0.760301E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.196115E+10 | 0.978152E+09 | 0.333866E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.204160E+10 | 0.188421E+10 | 0.101491E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.199132E+10 | 0.778395E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.201143E+10 | 0.105213E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.206172E+10 | 0.101310E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.196115E+10 | 0.446636E+10 | 54707937.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.202149E+10 | 47031216.63 | 0.108696E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.196289E+10 | 4458.81 | 0.751107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.201841E+10 | 0.00 | 0.143753E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.239650E+11 | 0.358120E+11 | 0.656419E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.183806E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.206232E+10 | 0.105213E+11 | 0.186506E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_6:6
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.335826E+10 | 0.00 | 0.360725E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.302627E+10 | 0.00 | 0.252158E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.338708E+10 | 0.00 | 0.154461E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.321363E+10 | 0.156794E+10 | 0.712345E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.334753E+10 | 0.297988E+10 | 0.305022E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.326719E+10 | 0.132087E+11 | 2352312.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.329397E+10 | 0.181712E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.338323E+10 | 0.171737E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.321363E+10 | 0.764993E+10 | 0.241884E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.331182E+10 | 57325866.94 | 0.304771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.322234E+10 | 0.00 | 0.150591E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.331714E+10 | 0.00 | 0.280942E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.393421E+11 | 0.608087E+11 | 0.130608E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.302627E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.338708E+10 | 0.181712E+11 | 0.360725E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_7:7
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.191680E+10 | 0.00 | 0.189108E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.172813E+10 | 0.00 | 0.132440E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.193612E+10 | 0.00 | 0.813711E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.183721E+10 | 0.808594E+09 | 0.376886E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.191376E+10 | 0.151442E+10 | 0.164547E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.186783E+10 | 0.682829E+10 | 3245913.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.188314E+10 | 0.940532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.193418E+10 | 0.886195E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.183721E+10 | 0.397047E+10 | 0.133956E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.189335E+10 | 27434799.25 | 0.160887E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.184149E+10 | 0.00 | 0.793174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.189512E+10 | 0.00 | 0.147586E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.224844E+11 | 0.314165E+11 | 0.686617E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.172813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.193612E+10 | 0.940532E+10 | 0.189108E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_8:8
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.191528E+10 | 0.00 | 0.189631E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.172691E+10 | 0.00 | 0.133216E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.193455E+10 | 0.00 | 0.824251E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.183561E+10 | 0.789895E+09 | 0.385881E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.191203E+10 | 0.146480E+10 | 0.178204E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.186614E+10 | 0.673445E+10 | 8144561.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.188144E+10 | 0.928905E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.193243E+10 | 0.875147E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.183555E+10 | 0.392446E+10 | 0.152342E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.189164E+10 | 25801277.63 | 0.169744E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.183994E+10 | 0.00 | 0.801554E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.189356E+10 | 0.00 | 0.148327E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.224651E+11 | 0.309799E+11 | 0.692703E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.172691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.193455E+10 | 0.928905E+10 | 0.189631E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_9:9
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.193476E+10 | 0.00 | 0.193895E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.174285E+10 | 0.00 | 0.137162E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.195034E+10 | 0.00 | 0.866861E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.184996E+10 | 0.743944E+09 | 0.418968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.192673E+10 | 0.134997E+10 | 0.220252E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.188049E+10 | 0.653412E+10 | 24996385.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.189590E+10 | 0.905685E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.194728E+10 | 0.853533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.184966E+10 | 0.383503E+10 | 0.200727E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.190618E+10 | 22178743.01 | 0.194796E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.185479E+10 | 0.00 | 0.832123E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.190948E+10 | 0.00 | 0.152144E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.226484E+11 | 0.300774E+11 | 0.718936E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.174285E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.195034E+10 | 0.905685E+10 | 0.193895E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_10:10
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.225759E+10 | 0.00 | 0.243631E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.200631E+10 | 0.00 | 0.174016E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.220822E+10 | 0.00 | 0.114617E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.207221E+10 | 0.685628E+09 | 0.578956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.215076E+10 | 0.117796E+10 | 0.431540E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.209914E+10 | 0.628669E+10 | 99870386.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.211635E+10 | 0.882497E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.217370E+10 | 0.840223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.206473E+10 | 0.384282E+10 | 0.350198E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.212782E+10 | 17728724.84 | 0.274085E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.209994E+10 | 0.00 | 0.104813E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.219175E+10 | 0.00 | 0.188654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.255685E+11 | 0.292380E+11 | 0.919852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.200631E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.225759E+10 | 0.882497E+10 | 0.243631E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_1:1
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.470372E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.520212E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.424021E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.362014E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.467160E+10 | 0.00 | 0.00 | 0.00 | 867.49 | 0.00 | 0.214011E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.451525E+10 | 0.00 | 0.00 | 0.00 | 0.768018E+09 | 0.00 | 0.936409E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.465149E+10 | 0.00 | 0.00 | 0.00 | 0.129364E+10 | 0.00 | 0.252158E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.451288E+10 | 0.00 | 0.00 | 0.00 | 0.564789E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.466054E+10 | 0.00 | 0.00 | 0.00 | 0.751971E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.465131E+10 | 0.00 | 0.00 | 0.00 | 0.669449E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.452210E+10 | 0.00 | 0.00 | 0.00 | 0.325259E+10 | 0.00 | 0.141903E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.465148E+10 | 0.00 | 0.00 | 0.00 | 31336071.59 | 0.00 | 0.253609E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.450400E+10 | 0.00 | 0.00 | 0.00 | 4467.64 | 0.00 | 0.207667E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.469726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.399612E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.549818E+11 | 0.00 | 0.00 | 0.00 | 0.252077E+11 | 0.00 | 0.182646E+12 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.424021E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.470372E+10 | 0.00 | 0.00 | 0.00 | 0.751971E+10 | 0.00 | 0.520212E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_2:2
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.189369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.202346E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.170774E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136443E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.194628E+10 | 0.00 | 0.00 | 0.00 | 600844.20 | 0.00 | 0.735636E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.194435E+10 | 0.00 | 0.00 | 0.00 | 0.433034E+09 | 0.00 | 0.293200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.234099E+10 | 0.00 | 0.00 | 0.00 | 0.819610E+09 | 0.00 | 15908002.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.217704E+10 | 0.00 | 0.00 | 0.00 | 0.303085E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.218702E+10 | 0.00 | 0.00 | 0.00 | 0.407257E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.224305E+10 | 0.00 | 0.00 | 0.00 | 0.369326E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.215905E+10 | 0.00 | 0.00 | 0.00 | 0.178202E+10 | 0.00 | 9180376.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.203327E+10 | 0.00 | 0.00 | 0.00 | 26189409.31 | 0.00 | 0.413015E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.188809E+10 | 0.00 | 0.00 | 0.00 | 1308136.55 | 0.00 | 0.752093E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.186894E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.151872E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.243895E+11 | 0.00 | 0.00 | 0.00 | 0.138594E+11 | 0.00 | 0.673134E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.170774E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.234099E+10 | 0.00 | 0.00 | 0.00 | 0.407257E+10 | 0.00 | 0.202346E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_3:3
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.201062E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.222108E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.181945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.152448E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.204479E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.866550E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.194483E+10 | 0.00 | 0.00 | 0.00 | 0.307004E+09 | 0.00 | 0.364948E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.202462E+10 | 0.00 | 0.00 | 0.00 | 0.599463E+09 | 0.00 | 63193340.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.197475E+10 | 0.00 | 0.00 | 0.00 | 0.231602E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.199470E+10 | 0.00 | 0.00 | 0.00 | 0.304675E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.204457E+10 | 0.00 | 0.00 | 0.00 | 0.296331E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.194483E+10 | 0.00 | 0.00 | 0.00 | 0.136108E+10 | 0.00 | 35323783.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.200468E+10 | 0.00 | 0.00 | 0.00 | 18290851.41 | 0.00 | 0.886934E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.194490E+10 | 0.00 | 0.00 | 0.00 | 3121.47 | 0.00 | 0.864463E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.199873E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.237515E+11 | 0.00 | 0.00 | 0.00 | 0.106119E+11 | 0.00 | 0.763686E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.181945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.204479E+10 | 0.00 | 0.00 | 0.00 | 0.304675E+10 | 0.00 | 0.222108E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_4:4
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.201922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.227031E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.182608E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156336E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.205018E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.900043E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.194968E+10 | 0.00 | 0.00 | 0.00 | 0.301802E+09 | 0.00 | 0.386356E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.202966E+10 | 0.00 | 0.00 | 0.00 | 0.586387E+09 | 0.00 | 91154748.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.197967E+10 | 0.00 | 0.00 | 0.00 | 0.231456E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.199967E+10 | 0.00 | 0.00 | 0.00 | 0.305255E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.204966E+10 | 0.00 | 0.00 | 0.00 | 0.296287E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.194968E+10 | 0.00 | 0.00 | 0.00 | 0.135950E+10 | 0.00 | 44868368.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.200967E+10 | 0.00 | 0.00 | 0.00 | 16641006.63 | 0.00 | 0.108426E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.195057E+10 | 0.00 | 0.00 | 0.00 | 2447.15 | 0.00 | 0.896042E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.200564E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.173952E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.238194E+11 | 0.00 | 0.00 | 0.00 | 0.105943E+11 | 0.00 | 0.787765E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.182608E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.205018E+10 | 0.00 | 0.00 | 0.00 | 0.305255E+10 | 0.00 | 0.227031E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_5:5
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.203346E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.233132E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.183806E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161501E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.206232E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.950377E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.196115E+10 | 0.00 | 0.00 | 0.00 | 0.288594E+09 | 0.00 | 0.417332E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.204160E+10 | 0.00 | 0.00 | 0.00 | 0.555226E+09 | 0.00 | 0.126864E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.199132E+10 | 0.00 | 0.00 | 0.00 | 0.226009E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.201143E+10 | 0.00 | 0.00 | 0.00 | 0.298654E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.206172E+10 | 0.00 | 0.00 | 0.00 | 0.289477E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.196115E+10 | 0.00 | 0.00 | 0.00 | 0.132986E+10 | 0.00 | 68384921.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.202149E+10 | 0.00 | 0.00 | 0.00 | 14214271.14 | 0.00 | 0.135870E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.196289E+10 | 0.00 | 0.00 | 0.00 | 1370.86 | 0.00 | 0.938883E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.201841E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179691E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.239650E+11 | 0.00 | 0.00 | 0.00 | 0.103293E+11 | 0.00 | 0.820523E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.183806E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.206232E+10 | 0.00 | 0.00 | 0.00 | 0.298654E+10 | 0.00 | 0.233132E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_6:6
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.335826E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.450906E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.302627E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.315197E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.338708E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.193077E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.321363E+10 | 0.00 | 0.00 | 0.00 | 0.495322E+09 | 0.00 | 0.890431E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.334753E+10 | 0.00 | 0.00 | 0.00 | 0.941179E+09 | 0.00 | 0.381278E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.326719E+10 | 0.00 | 0.00 | 0.00 | 0.410705E+10 | 0.00 | 2940390.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.329397E+10 | 0.00 | 0.00 | 0.00 | 0.551573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.338323E+10 | 0.00 | 0.00 | 0.00 | 0.524907E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.321363E+10 | 0.00 | 0.00 | 0.00 | 0.243773E+10 | 0.00 | 0.302356E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.331182E+10 | 0.00 | 0.00 | 0.00 | 18547983.25 | 0.00 | 0.380964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.322234E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188239E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.331714E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.351178E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.393421E+11 | 0.00 | 0.00 | 0.00 | 0.187646E+11 | 0.00 | 0.163260E+12 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.302627E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.338708E+10 | 0.00 | 0.00 | 0.00 | 0.551573E+10 | 0.00 | 0.450906E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_7:7
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.191680E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.236385E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.172813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165550E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.193612E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101714E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.183721E+10 | 0.00 | 0.00 | 0.00 | 0.242150E+09 | 0.00 | 0.471108E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.191376E+10 | 0.00 | 0.00 | 0.00 | 0.453237E+09 | 0.00 | 0.205684E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.186783E+10 | 0.00 | 0.00 | 0.00 | 0.201395E+10 | 0.00 | 4057391.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.188314E+10 | 0.00 | 0.00 | 0.00 | 0.270741E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.193418E+10 | 0.00 | 0.00 | 0.00 | 0.256929E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.183721E+10 | 0.00 | 0.00 | 0.00 | 0.119969E+10 | 0.00 | 0.167445E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.189335E+10 | 0.00 | 0.00 | 0.00 | 8391401.30 | 0.00 | 0.201108E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.184149E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.991468E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.189512E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.184482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.224844E+11 | 0.00 | 0.00 | 0.00 | 0.919411E+10 | 0.00 | 0.858271E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.172813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.193612E+10 | 0.00 | 0.00 | 0.00 | 0.270741E+10 | 0.00 | 0.236385E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_8:8
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.191528E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.237039E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.172691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.166520E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.193455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103031E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.183561E+10 | 0.00 | 0.00 | 0.00 | 0.236937E+09 | 0.00 | 0.482351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.191203E+10 | 0.00 | 0.00 | 0.00 | 0.439205E+09 | 0.00 | 0.222755E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.186614E+10 | 0.00 | 0.00 | 0.00 | 0.198851E+10 | 0.00 | 10180702.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.188144E+10 | 0.00 | 0.00 | 0.00 | 0.267663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.193243E+10 | 0.00 | 0.00 | 0.00 | 0.253980E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.183555E+10 | 0.00 | 0.00 | 0.00 | 0.118708E+10 | 0.00 | 0.190427E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.189164E+10 | 0.00 | 0.00 | 0.00 | 7901157.13 | 0.00 | 0.212180E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.183994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100194E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.189356E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.224651E+11 | 0.00 | 0.00 | 0.00 | 0.907607E+10 | 0.00 | 0.865879E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.172691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.193455E+10 | 0.00 | 0.00 | 0.00 | 0.267663E+10 | 0.00 | 0.237039E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_9:9
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.193476E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.242369E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.174285E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.195034E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.184996E+10 | 0.00 | 0.00 | 0.00 | 0.224207E+09 | 0.00 | 0.523711E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.192673E+10 | 0.00 | 0.00 | 0.00 | 0.406818E+09 | 0.00 | 0.275315E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.188049E+10 | 0.00 | 0.00 | 0.00 | 0.193542E+10 | 0.00 | 31245481.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.189590E+10 | 0.00 | 0.00 | 0.00 | 0.261662E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.194728E+10 | 0.00 | 0.00 | 0.00 | 0.248350E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.184966E+10 | 0.00 | 0.00 | 0.00 | 0.116320E+10 | 0.00 | 0.250908E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.190618E+10 | 0.00 | 0.00 | 0.00 | 6812586.18 | 0.00 | 0.243494E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.185479E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.190948E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.190180E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.226484E+11 | 0.00 | 0.00 | 0.00 | 0.883657E+10 | 0.00 | 0.898670E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.174285E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.195034E+10 | 0.00 | 0.00 | 0.00 | 0.261662E+10 | 0.00 | 0.242369E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_10:10
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.225759E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.304539E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.200631E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.217520E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.220822E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143272E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.207221E+10 | 0.00 | 0.00 | 0.00 | 0.209483E+09 | 0.00 | 0.723696E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.215076E+10 | 0.00 | 0.00 | 0.00 | 0.359992E+09 | 0.00 | 0.539426E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.209914E+10 | 0.00 | 0.00 | 0.00 | 0.188554E+10 | 0.00 | 0.124838E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.211635E+10 | 0.00 | 0.00 | 0.00 | 0.257841E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.217370E+10 | 0.00 | 0.00 | 0.00 | 0.246879E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.206473E+10 | 0.00 | 0.00 | 0.00 | 0.117623E+10 | 0.00 | 0.437747E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.212782E+10 | 0.00 | 0.00 | 0.00 | 5479774.28 | 0.00 | 0.342607E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.209994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131017E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.219175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.235818E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.255685E+11 | 0.00 | 0.00 | 0.00 | 0.868392E+10 | 0.00 | 0.114982E+12 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.200631E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.225759E+10 | 0.00 | 0.00 | 0.00 | 0.257841E+10 | 0.00 | 0.304539E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.132834E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.257232E+11 | 0.00 | 0.00 | 0.52 |
February | 0.301845E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.177670E+11 | 0.00 | 0.00 | 0.53 |
March | 0.549110E+10 | 0.00 | 0.00 | 92959.68 | 0.00 | 0.108043E+11 | 0.137204E+09 | 0.00 | 0.53 |
April | 0.570222E+10 | 0.481218E+09 | 0.00 | 2527549.43 | 2207044.68 | 0.461432E+10 | 0.129109E+10 | 0.00 | 0.65 |
May | 0.229168E+10 | 0.542391E+09 | 0.00 | 12789543.62 | 0.00 | 76421099.15 | 0.726701E+10 | 0.00 | 1.04 |
June | 0.891399E+09 | 0.399047E+10 | 0.00 | 15836507.42 | 7561909.61 | 0.00 | 0.476744E+10 | 0.00 | 1.20 |
July | 15277332.79 | 0.555989E+10 | 0.00 | 23676612.27 | 2740945.94 | 0.00 | 0.430503E+10 | 0.00 | 1.45 |
August | 17349710.89 | 0.443934E+10 | 0.00 | 22605733.58 | 1745419.49 | 0.00 | 0.580246E+10 | 0.00 | 1.45 |
September | 0.239357E+10 | 0.137148E+10 | 0.00 | 22191547.75 | 22573.54 | 33670688.70 | 0.637519E+10 | 0.00 | 1.12 |
October | 0.869190E+10 | 0.00 | 0.00 | 2281524.89 | 0.00 | 0.986198E+09 | 0.216025E+10 | 0.00 | 0.60 |
November | 0.581647E+10 | 0.00 | 0.00 | 400579.81 | 0.00 | 0.103081E+11 | 0.640116E+09 | 0.00 | 0.53 |
December | 0.374227E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.193759E+11 | 0.00 | 0.00 | 0.52 |
Annual Sum or Average | 0.394000E+11 | 0.163848E+11 | 0.00 | 0.102403E+09 | 14277893.26 | 0.896891E+11 | 0.327458E+11 | 0.00 | 0.85 |
Minimum of Months | 15277332.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.52 |
Maximum of Months | 0.869190E+10 | 0.555989E+10 | 0.00 | 23676612.27 | 7561909.61 | 0.257232E+11 | 0.726701E+10 | 0.00 | 1.45 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.501635E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.948855E+10 | 0.00 | 0.00 | 0.39 |
February | 0.106334E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.653720E+10 | 0.00 | 0.00 | 0.39 |
March | 0.234851E+10 | 0.00 | 0.00 | 248548.79 | 0.00 | 0.353169E+10 | 0.249405E+09 | 0.00 | 0.42 |
April | 0.203309E+10 | 0.248643E+09 | 0.00 | 1431597.66 | 122212.97 | 0.161549E+10 | 0.101787E+10 | 0.00 | 0.56 |
May | 0.670299E+09 | 0.336562E+09 | 0.00 | 6949488.28 | 93129.34 | 3823394.18 | 0.466700E+10 | 0.00 | 1.13 |
June | 0.254331E+09 | 0.204737E+10 | 0.00 | 5368813.09 | 10198075.60 | 0.00 | 0.246964E+10 | 0.00 | 1.12 |
July | 2897232.51 | 0.310157E+10 | 0.00 | 4528884.16 | 5154081.20 | 0.00 | 0.147691E+10 | 0.00 | 1.27 |
August | 3350858.55 | 0.241623E+10 | 0.00 | 6722150.93 | 1711957.42 | 0.00 | 0.208671E+10 | 0.00 | 1.33 |
September | 0.779495E+09 | 0.756239E+09 | 0.00 | 6653972.65 | 186683.67 | 0.00 | 0.335862E+10 | 0.00 | 1.03 |
October | 0.314926E+10 | 0.00 | 0.00 | 2283615.76 | 0.00 | 80999815.49 | 0.182710E+10 | 0.00 | 0.56 |
November | 0.185943E+10 | 0.00 | 0.00 | 851209.19 | 0.00 | 0.376417E+10 | 0.761068E+09 | 0.00 | 0.43 |
December | 0.122241E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.711861E+10 | 0.00 | 0.00 | 0.38 |
Annual Sum or Average | 0.138880E+11 | 0.890661E+10 | 0.00 | 35038280.50 | 17466140.21 | 0.321405E+11 | 0.179143E+11 | 0.00 | 0.75 |
Minimum of Months | 2897232.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.314926E+10 | 0.310157E+10 | 0.00 | 6949488.28 | 10198075.60 | 0.948855E+10 | 0.466700E+10 | 0.00 | 1.33 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.187512E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104688E+11 | 0.00 | 0.00 | 0.41 |
February | 0.701812E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.741432E+10 | 0.00 | 0.00 | 0.41 |
March | 0.189246E+10 | 0.00 | 0.00 | 3760.61 | 0.00 | 0.451089E+10 | 19988960.55 | 0.00 | 0.42 |
April | 0.201816E+10 | 0.178565E+09 | 0.00 | 545368.26 | 10221260.20 | 0.204232E+10 | 0.421538E+09 | 0.00 | 0.51 |
May | 0.105075E+10 | 0.257077E+09 | 0.00 | 3247612.21 | 5933661.64 | 18954022.02 | 0.262936E+10 | 0.00 | 0.86 |
June | 0.442456E+09 | 0.157798E+10 | 0.00 | 3274681.24 | 78328646.16 | 0.00 | 0.170293E+10 | 0.00 | 0.95 |
July | 48081628.33 | 0.210659E+10 | 0.00 | 3428517.33 | 0.101586E+09 | 0.00 | 0.127378E+10 | 0.00 | 1.05 |
August | 0.104448E+09 | 0.189705E+10 | 0.00 | 3939931.50 | 68341457.67 | 0.00 | 0.146421E+10 | 0.00 | 1.09 |
September | 0.110455E+10 | 0.589180E+09 | 0.00 | 3602204.04 | 15698937.70 | 13675304.57 | 0.208573E+10 | 0.00 | 0.83 |
October | 0.334292E+10 | 0.00 | 0.00 | 603752.76 | 0.00 | 0.392543E+09 | 0.637727E+09 | 0.00 | 0.48 |
November | 0.178310E+10 | 0.00 | 0.00 | 160833.46 | 0.00 | 0.436050E+10 | 0.219749E+09 | 0.00 | 0.42 |
December | 0.475291E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.842421E+10 | 0.00 | 0.00 | 0.41 |
Annual Sum or Average | 0.131515E+11 | 0.660644E+10 | 0.00 | 18806661.40 | 0.280110E+09 | 0.376463E+11 | 0.104550E+11 | 0.00 | 0.66 |
Minimum of Months | 48081628.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.334292E+10 | 0.210659E+10 | 0.00 | 3939931.50 | 0.101586E+09 | 0.104688E+11 | 0.262936E+10 | 0.00 | 1.09 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.163084E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104933E+11 | 0.00 | 0.00 | 0.41 |
February | 0.599957E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.751606E+10 | 0.00 | 0.00 | 0.41 |
March | 0.168426E+10 | 0.00 | 0.00 | 175.78 | 0.00 | 0.472589E+10 | 3285202.37 | 0.00 | 0.42 |
April | 0.192154E+10 | 0.177142E+09 | 0.00 | 505664.65 | 10211799.94 | 0.215065E+10 | 0.388587E+09 | 0.00 | 0.51 |
May | 0.110349E+10 | 0.253325E+09 | 0.00 | 3054354.75 | 5909730.01 | 29839180.45 | 0.249082E+10 | 0.00 | 0.84 |
June | 0.459702E+09 | 0.157911E+10 | 0.00 | 3214168.76 | 78323270.98 | 0.00 | 0.167043E+10 | 0.00 | 0.95 |
July | 48357657.59 | 0.211079E+10 | 0.00 | 3434396.01 | 0.101485E+09 | 0.00 | 0.127395E+10 | 0.00 | 1.05 |
August | 0.105097E+09 | 0.189652E+10 | 0.00 | 3947004.40 | 68276532.12 | 0.00 | 0.146908E+10 | 0.00 | 1.09 |
September | 0.110895E+10 | 0.589663E+09 | 0.00 | 3541746.82 | 15689352.97 | 19360424.43 | 0.204951E+10 | 0.00 | 0.83 |
October | 0.324689E+10 | 0.00 | 0.00 | 477016.73 | 0.00 | 0.522717E+09 | 0.525592E+09 | 0.00 | 0.47 |
November | 0.165369E+10 | 0.00 | 0.00 | 103472.43 | 0.00 | 0.451313E+10 | 0.160526E+09 | 0.00 | 0.42 |
December | 0.317795E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.858168E+10 | 0.00 | 0.00 | 0.41 |
Annual Sum or Average | 0.124128E+11 | 0.660654E+10 | 0.00 | 18278000.32 | 0.279896E+09 | 0.385526E+11 | 0.100318E+11 | 0.00 | 0.65 |
Minimum of Months | 48357657.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.324689E+10 | 0.211079E+10 | 0.00 | 3947004.40 | 0.101485E+09 | 0.104933E+11 | 0.249082E+10 | 0.00 | 1.09 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.140611E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105158E+11 | 0.00 | 0.00 | 0.41 |
February | 0.431642E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.768446E+10 | 0.00 | 0.00 | 0.41 |
March | 0.135100E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.505299E+10 | 0.00 | 0.00 | 0.42 |
April | 0.181136E+10 | 0.173416E+09 | 0.00 | 433970.26 | 10228421.70 | 0.226896E+10 | 0.345912E+09 | 0.00 | 0.50 |
May | 0.116905E+10 | 0.243707E+09 | 0.00 | 2629156.28 | 5873361.32 | 66573895.78 | 0.221505E+10 | 0.00 | 0.81 |
June | 0.562145E+09 | 0.155575E+10 | 0.00 | 2910446.63 | 77805965.42 | 0.00 | 0.152438E+10 | 0.00 | 0.94 |
July | 47994098.86 | 0.207373E+10 | 0.00 | 3259298.86 | 0.101010E+09 | 0.00 | 0.128016E+10 | 0.00 | 1.05 |
August | 0.108587E+09 | 0.186060E+10 | 0.00 | 3732737.48 | 68073424.38 | 0.00 | 0.146824E+10 | 0.00 | 1.09 |
September | 0.113514E+10 | 0.584574E+09 | 0.00 | 3268883.96 | 15738074.19 | 31264242.26 | 0.192912E+10 | 0.00 | 0.82 |
October | 0.310905E+10 | 0.00 | 0.00 | 347945.79 | 0.00 | 0.720057E+09 | 0.383597E+09 | 0.00 | 0.47 |
November | 0.147729E+10 | 0.00 | 0.00 | 33632.67 | 0.00 | 0.472955E+10 | 80029005.56 | 0.00 | 0.42 |
December | 0.129952E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.876950E+10 | 0.00 | 0.00 | 0.41 |
Annual Sum or Average | 0.114738E+11 | 0.649178E+10 | 0.00 | 16616071.93 | 0.278730E+09 | 0.398391E+11 | 0.922649E+10 | 0.00 | 0.65 |
Minimum of Months | 47994098.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.310905E+10 | 0.207373E+10 | 0.00 | 3732737.48 | 0.101010E+09 | 0.105158E+11 | 0.221505E+10 | 0.00 | 1.09 |
Report: MechanicalVentilationLoadsMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 29842598.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.195012E+11 | 0.00 | 0.00 | 0.38 |
February | 0.192471E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146851E+11 | 0.00 | 0.00 | 0.38 |
March | 0.157685E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101198E+11 | 0.00 | 0.00 | 0.39 |
April | 0.251140E+10 | 0.324335E+09 | 0.00 | 564367.40 | 26672021.61 | 0.492978E+10 | 0.514136E+09 | 0.00 | 0.45 |
May | 0.210297E+10 | 0.433707E+09 | 0.00 | 3215594.09 | 103643.21 | 0.247475E+09 | 0.304164E+10 | 0.00 | 0.66 |
June | 0.101400E+10 | 0.285183E+10 | 0.00 | 4186047.83 | 90000046.92 | 0.00 | 0.241481E+10 | 0.00 | 0.81 |
July | 31818963.91 | 0.402780E+10 | 0.00 | 4436505.58 | 61250036.79 | 0.00 | 0.198367E+10 | 0.00 | 0.91 |
August | 42133658.15 | 0.347963E+10 | 0.00 | 6039568.99 | 33888592.11 | 0.00 | 0.258059E+10 | 0.00 | 0.97 |
September | 0.192241E+10 | 0.114133E+10 | 0.00 | 4468422.53 | 18564661.28 | 0.102366E+09 | 0.295515E+10 | 0.00 | 0.70 |
October | 0.491494E+10 | 0.00 | 0.00 | 321040.91 | 0.00 | 0.208264E+10 | 0.413071E+09 | 0.00 | 0.41 |
November | 0.206681E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.937294E+10 | 0.00 | 0.00 | 0.38 |
December | 17551283.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163132E+11 | 0.00 | 0.00 | 0.37 |
Annual Sum or Average | 0.164232E+11 | 0.122586E+11 | 0.00 | 23231547.33 | 0.230479E+09 | 0.773545E+11 | 0.139031E+11 | 0.00 | 0.57 |
Minimum of Months | 17551283.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.37 |
Maximum of Months | 0.491494E+10 | 0.402780E+10 | 0.00 | 6039568.99 | 90000046.92 | 0.195012E+11 | 0.304164E+10 | 0.00 | 0.97 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 7475069.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.975005E+10 | 0.00 | 0.00 | 0.38 |
February | 82769769.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.734873E+10 | 0.00 | 0.00 | 0.38 |
March | 0.706823E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.513243E+10 | 0.00 | 0.00 | 0.39 |
April | 0.114263E+10 | 0.161285E+09 | 0.00 | 268178.72 | 13746778.97 | 0.257707E+10 | 0.259974E+09 | 0.00 | 0.45 |
May | 0.106809E+10 | 0.214486E+09 | 0.00 | 1473973.58 | 3830.41 | 0.142781E+09 | 0.150830E+10 | 0.00 | 0.68 |
June | 0.512741E+09 | 0.142278E+10 | 0.00 | 2060923.24 | 45183184.34 | 0.00 | 0.128201E+10 | 0.00 | 0.85 |
July | 20235819.93 | 0.201042E+10 | 0.00 | 2212436.38 | 29889642.85 | 0.00 | 0.108000E+10 | 0.00 | 0.97 |
August | 29768121.70 | 0.173269E+10 | 0.00 | 3038618.03 | 16574704.67 | 0.00 | 0.141173E+10 | 0.00 | 1.04 |
September | 0.945176E+09 | 0.571039E+09 | 0.00 | 2191079.15 | 9316363.33 | 79096859.75 | 0.153043E+10 | 0.00 | 0.74 |
October | 0.216393E+10 | 0.00 | 0.00 | 140548.02 | 0.00 | 0.133923E+10 | 0.193309E+09 | 0.00 | 0.41 |
November | 0.964684E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.474364E+10 | 0.00 | 0.00 | 0.38 |
December | 6555386.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.815057E+10 | 0.00 | 0.00 | 0.37 |
Annual Sum or Average | 0.765087E+10 | 0.611270E+10 | 0.00 | 11385757.11 | 0.114715E+09 | 0.392636E+11 | 0.726575E+10 | 0.00 | 0.59 |
Minimum of Months | 6555386.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.37 |
Maximum of Months | 0.216393E+10 | 0.201042E+10 | 0.00 | 3038618.03 | 45183184.34 | 0.975005E+10 | 0.153043E+10 | 0.00 | 1.04 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 4955860.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.975256E+10 | 0.00 | 0.00 | 0.38 |
February | 74605356.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.735691E+10 | 0.00 | 0.00 | 0.38 |
March | 0.661685E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.517579E+10 | 0.00 | 0.00 | 0.39 |
April | 0.108098E+10 | 0.160150E+09 | 0.00 | 254290.23 | 14181837.21 | 0.263772E+10 | 0.248155E+09 | 0.00 | 0.45 |
May | 0.112712E+10 | 0.210220E+09 | 0.00 | 1319492.31 | 912.34 | 0.147688E+09 | 0.136214E+10 | 0.00 | 0.66 |
June | 0.518744E+09 | 0.141264E+10 | 0.00 | 1978224.84 | 45766989.21 | 697027.30 | 0.125124E+10 | 0.00 | 0.85 |
July | 21482178.24 | 0.199386E+10 | 0.00 | 2139975.55 | 29788479.93 | 0.00 | 0.107048E+10 | 0.00 | 0.97 |
August | 30943912.24 | 0.172032E+10 | 0.00 | 2959485.17 | 16557537.37 | 0.00 | 0.140294E+10 | 0.00 | 1.03 |
September | 0.949636E+09 | 0.568974E+09 | 0.00 | 2106547.87 | 9385090.91 | 90887472.26 | 0.148297E+10 | 0.00 | 0.73 |
October | 0.210997E+10 | 0.00 | 0.00 | 126683.39 | 0.00 | 0.139379E+10 | 0.178419E+09 | 0.00 | 0.41 |
November | 0.928352E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.477448E+10 | 0.00 | 0.00 | 0.38 |
December | 6555640.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.815058E+10 | 0.00 | 0.00 | 0.37 |
Annual Sum or Average | 0.751503E+10 | 0.606617E+10 | 0.00 | 10884699.35 | 0.115681E+09 | 0.394811E+11 | 0.699634E+10 | 0.00 | 0.58 |
Minimum of Months | 4955860.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.37 |
Maximum of Months | 0.210997E+10 | 0.199386E+10 | 0.00 | 2959485.17 | 45766989.21 | 0.975256E+10 | 0.148297E+10 | 0.00 | 1.03 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.975751E+10 | 0.00 | 0.00 | 0.38 |
February | 36443048.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.739498E+10 | 0.00 | 0.00 | 0.38 |
March | 0.470695E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.536163E+10 | 0.00 | 0.00 | 0.39 |
April | 0.880984E+09 | 0.159101E+09 | 0.00 | 213055.36 | 14004112.57 | 0.282848E+10 | 0.223819E+09 | 0.00 | 0.44 |
May | 0.121636E+10 | 0.200288E+09 | 0.00 | 974191.12 | 0.00 | 0.178437E+09 | 0.105856E+10 | 0.00 | 0.63 |
June | 0.536348E+09 | 0.138877E+10 | 0.00 | 1789489.49 | 46409864.53 | 17400784.04 | 0.116607E+10 | 0.00 | 0.84 |
July | 32686319.23 | 0.195384E+10 | 0.00 | 1979458.55 | 30408956.96 | 0.00 | 0.104012E+10 | 0.00 | 0.96 |
August | 42111788.43 | 0.169264E+10 | 0.00 | 2777408.90 | 16497961.94 | 0.00 | 0.137877E+10 | 0.00 | 1.03 |
September | 0.897665E+09 | 0.562702E+09 | 0.00 | 1915402.93 | 9399857.84 | 0.182052E+09 | 0.137820E+10 | 0.00 | 0.72 |
October | 0.196154E+10 | 0.00 | 0.00 | 97513.30 | 0.00 | 0.154275E+10 | 0.149201E+09 | 0.00 | 0.41 |
November | 0.811214E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.488138E+10 | 0.00 | 0.00 | 0.38 |
December | 2176308.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.815492E+10 | 0.00 | 0.00 | 0.37 |
Annual Sum or Average | 0.688822E+10 | 0.595734E+10 | 0.00 | 9746519.65 | 0.116721E+09 | 0.402995E+11 | 0.639473E+10 | 0.00 | 0.58 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.37 |
Maximum of Months | 0.196154E+10 | 0.195384E+10 | 0.00 | 2777408.90 | 46409864.53 | 0.975751E+10 | 0.137877E+10 | 0.00 | 1.03 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:18:54
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.973712E+10 | 0.00 | 0.00 | 0.38 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.741632E+10 | 0.00 | 0.00 | 0.38 |
March | 0.105154E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.569458E+10 | 0.00 | 0.00 | 0.39 |
April | 0.403495E+09 | 0.139203E+09 | 0.00 | 106114.08 | 23871777.57 | 0.328217E+10 | 0.157329E+09 | 0.00 | 0.42 |
May | 0.130788E+10 | 0.184336E+09 | 0.00 | 445344.36 | 3121137.85 | 0.308447E+09 | 0.535535E+09 | 0.00 | 0.59 |
June | 0.463773E+09 | 0.131924E+10 | 0.00 | 1409895.16 | 42331044.89 | 0.102127E+09 | 0.107820E+10 | 0.00 | 0.85 |
July | 74149559.84 | 0.187154E+10 | 0.00 | 1612880.22 | 28589709.19 | 0.00 | 0.100704E+10 | 0.00 | 1.00 |
August | 69116206.96 | 0.164842E+10 | 0.00 | 2335781.85 | 16462794.69 | 0.00 | 0.136537E+10 | 0.00 | 1.06 |
September | 0.826968E+09 | 0.550988E+09 | 0.00 | 1552254.16 | 8674093.29 | 0.324800E+09 | 0.122221E+10 | 0.00 | 0.73 |
October | 0.134662E+10 | 0.00 | 0.00 | 57762.54 | 0.00 | 0.215762E+10 | 94604452.65 | 0.00 | 0.40 |
November | 0.505568E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.516501E+10 | 0.00 | 0.00 | 0.38 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.814172E+10 | 0.00 | 0.00 | 0.37 |
Annual Sum or Average | 0.510273E+10 | 0.571373E+10 | 0.00 | 7520032.36 | 0.123051E+09 | 0.423299E+11 | 0.546029E+10 | 0.00 | 0.58 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.37 |
Maximum of Months | 0.134662E+10 | 0.187154E+10 | 0.00 | 2335781.85 | 42331044.89 | 0.973712E+10 | 0.136537E+10 | 0.00 | 1.06 |