Program Version:EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:19
Tabular Output Report in Format: HTML
Building: RetailStripmall
Environment: RUNPERIOD 1 ** Rochester International Arpt MN USA TMY3 WMO#=726440
Simulation Timestamp: 2020-06-03 19:19:07
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2020-06-03 19:19:07
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 2852.27 | 1364.51 | 1364.51 |
Net Site Energy | 2852.27 | 1364.51 | 1364.51 |
Total Source Energy | 6213.03 | 2972.29 | 2972.29 |
Net Source Energy | 6213.03 | 2972.29 | 2972.29 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 2090.32 |
Net Conditioned Building Area | 2090.32 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 1353.87 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 140.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 708.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 166.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 128.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 287.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 66.36 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1498.40 | 1353.87 | 0.00 | 0.00 | 0.00 | 87.30 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 1353.87 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 140.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 708.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 166.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 128.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 287.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 66.36 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 418.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 236.40 | 647.68 | 0.00 | 0.00 | 0.00 | 0.04 |
Other | 61.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 716.83 | 647.68 | 0.00 | 0.00 | 0.00 | 0.04 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 418.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 236.40 | 647.68 | 0.00 | 0.00 | 0.00 | 0.04 |
Other | 61.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 716.83 | 647.68 | 0.00 | 0.00 | 0.00 | 0.04 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1498.402 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1498.402 | 100.00 |
Total On-Site and Utility Electric Sources | 1498.402 | 100.00 |
Total Electricity End Uses | 1498.402 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 87.30 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 87.30 | 100.00 |
Total Water End Uses | 87.30 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 8.17 |
Time Setpoint Not Met During Occupied Cooling | 0.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 2872.00 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Meter |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2006
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Meter |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTRIPMALL
| Meter |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 6A
| Meter |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_ROCHESTER
| Meter |ZoneCoolingSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ZoneHeatingSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ZoneElectricSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |SpaceGainsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |PeakSpaceGainsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |SpaceGainComponentsAtCoolingPeakMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ComfortReportSimple55Monthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |OccupantComfortDataSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |DXReportMonthly
| PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL |WindowReportMonthly
| LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR |WindowEnergyReportMonthly
| LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR |WindowZoneSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |WindowEnergyZoneSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| GAS TANK1 | GAS TANK2 | GAS TANK3 | GAS TANK4 | GAS TANK5 | GAS TANK6 | GAS TANK7 |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC_1:1_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_2:2_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_3:3_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_4:4_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_5:5_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_6:6_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_7:7_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_8:8_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_9:9_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_10:10_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL |FanReportMonthly
| PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN |ZoneTemperatureOscillationReportMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |MechanicalVentilationLoadsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2020-06-03 19:19:07
GeneralValue | |
Program Version and Build | EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:19 |
RunPeriod | RUNPERIOD 1 |
Weather File | Rochester International Arpt MN USA TMY3 WMO#=726440 |
Latitude [deg] | 43.90 |
Longitude [deg] | -92.5 |
Elevation [m] | 398.00 |
Time Zone | -6.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Above Ground Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Window Opening Area [m2] | 124.29 | 0.00 | 0.00 | 124.29 | 0.00 |
Gross Window-Wall Ratio [%] | 10.50 | 0.00 | 0.00 | 26.24 | 0.00 |
Above Ground Window-Wall Ratio [%] | 10.50 | 0.00 | 0.00 | 26.24 | 0.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Above Ground Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Window Opening Area [m2] | 124.29 | 0.00 | 0.00 | 124.29 | 0.00 |
Gross Window-Wall Ratio [%] | 10.50 | 0.00 | 0.00 | 26.24 | 0.00 |
Above Ground Window-Wall Ratio [%] | 10.50 | 0.00 | 0.00 | 26.24 | 0.00 |
Total | |
Gross Roof Area [m2] | 2090.32 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
LGSTORE1 | 348.39 | Yes | Yes | 1805.20 | 1.00 | 276.30 | 0.00 | 20.75 | 20.75 | 28.8173 | 11.61 | 4.3000 |
SMSTORE1 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.37 | 10.37 | 28.8173 | 11.61 | 4.3000 |
SMSTORE2 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.35 | 10.35 | 22.6280 | 11.61 | 4.3000 |
SMSTORE3 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.35 | 10.35 | 22.6280 | 11.61 | 4.3000 |
SMSTORE4 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.35 | 10.35 | 22.6280 | 11.61 | 4.3000 |
LGSTORE2 | 348.39 | Yes | Yes | 1805.20 | 1.00 | 157.89 | 0.00 | 20.70 | 20.70 | 18.3225 | 11.61 | 4.3000 |
SMSTORE5 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.35 | 10.35 | 18.3225 | 11.61 | 4.3000 |
SMSTORE6 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.35 | 10.35 | 18.3225 | 11.61 | 4.3000 |
SMSTORE7 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.35 | 10.35 | 18.3225 | 11.61 | 4.3000 |
SMSTORE8 | 174.19 | Yes | Yes | 902.60 | 1.00 | 197.36 | 0.00 | 10.35 | 10.35 | 18.3225 | 11.61 | 4.3000 |
Total | 2090.32 | 10831.20 | 1184.15 | 0.00 | 124.29 | 124.29 | 22.0226 | 11.61 | 4.3000 | |||
Conditioned Total | 2090.32 | 10831.20 | 1184.15 | 0.00 | 124.29 | 124.29 | 22.0226 | 11.61 | 4.3000 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:19:07
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 04-AUG-13:39 | 02-FEB-12:09 | - | - | - | 06-JAN-13:09 |
Heating | 0.00 | 503448.11 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 81955.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 43732.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 8089.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 16727.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 5464.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 155969.82 | 503448.11 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 503448.11 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 81955.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 43732.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 8089.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 16727.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 5464.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:19:07
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 1467.59 | 0.00 | 0.00 | 0.00 |
Cooling | 444.45 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 2244.57 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 528.26 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 407.66 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 910.33 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 210.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 4745.44 | 1467.59 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 702.09 | 0.00 | 0.00 | 0.00 |
Cooling | 212.62 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1073.80 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 252.72 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 195.02 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 435.50 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 100.55 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2270.20 | 702.09 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 702.09 | 0.00 | 0.00 | 0.00 |
Cooling | 212.62 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1073.80 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 252.72 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 195.02 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 435.50 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 100.55 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2270.20 | 702.09 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:19:07
AirTerminal:SingleDuct:UncontrolledDesign Size Maximum Air Flow Rate [m3/s] | |
LGSTORE1 DIRECT AIR | 2.42 |
SMSTORE1 DIRECT AIR | 1.23 |
SMSTORE2 DIRECT AIR | 1.24 |
SMSTORE3 DIRECT AIR | 1.24 |
SMSTORE4 DIRECT AIR | 1.25 |
LGSTORE2 DIRECT AIR | 2.31 |
SMSTORE5 DIRECT AIR | 1.26 |
SMSTORE6 DIRECT AIR | 1.26 |
SMSTORE7 DIRECT AIR | 1.27 |
SMSTORE8 DIRECT AIR | 1.45 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC_1:1 | 2.42 | 2.42 | 2.42 | 2.42 | 2.42 | 2.42 | 1.00 | 1.00 | 2.42 |
PSZ-AC_2:2 | 1.23 | 1.23 | 1.23 | 1.23 | 1.23 | 1.23 | 1.00 | 1.00 | 1.23 |
PSZ-AC_3:3 | 1.24 | 1.24 | 1.24 | 1.24 | 1.24 | 1.24 | 1.00 | 1.00 | 1.24 |
PSZ-AC_4:4 | 1.24 | 1.24 | 1.24 | 1.24 | 1.24 | 1.24 | 1.00 | 1.00 | 1.24 |
PSZ-AC_5:5 | 1.25 | 1.25 | 1.25 | 1.25 | 1.25 | 1.25 | 1.00 | 1.00 | 1.25 |
PSZ-AC_6:6 | 2.31 | 2.31 | 2.31 | 2.31 | 2.31 | 2.31 | 1.00 | 1.00 | 2.31 |
PSZ-AC_7:7 | 1.26 | 1.26 | 1.26 | 1.26 | 1.26 | 1.26 | 1.00 | 1.00 | 1.26 |
PSZ-AC_8:8 | 1.26 | 1.26 | 1.26 | 1.26 | 1.26 | 1.26 | 1.00 | 1.00 | 1.26 |
PSZ-AC_9:9 | 1.27 | 1.27 | 1.27 | 1.27 | 1.27 | 1.27 | 1.00 | 1.00 | 1.27 |
PSZ-AC_10:10 | 1.45 | 1.45 | 1.45 | 1.45 | 1.45 | 1.45 | 1.00 | 1.00 | 1.45 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC_1:1_OA_CONTROLLER | 2.42 | 0.530908 |
PSZ-AC_2:2_OA_CONTROLLER | 1.23 | 0.265454 |
PSZ-AC_3:3_OA_CONTROLLER | 1.24 | 0.265454 |
PSZ-AC_4:4_OA_CONTROLLER | 1.24 | 0.265454 |
PSZ-AC_5:5_OA_CONTROLLER | 1.25 | 0.265454 |
PSZ-AC_6:6_OA_CONTROLLER | 2.31 | 0.530908 |
PSZ-AC_7:7_OA_CONTROLLER | 1.26 | 0.265454 |
PSZ-AC_8:8_OA_CONTROLLER | 1.26 | 0.265454 |
PSZ-AC_9:9_OA_CONTROLLER | 1.27 | 0.265454 |
PSZ-AC_10:10_OA_CONTROLLER | 1.45 | 0.265454 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC_1:1_UNITARY_PACKAGE_DX | 2.42 | 2.42 | 2.42 | 2.42 | 55675.07 | 81662.66 | 40.00 | 1.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_DX | 1.23 | 1.23 | 1.23 | 1.23 | 28121.66 | 41257.18 | 40.00 | 1.00 |
PSZ-AC_3:3_UNITARY_PACKAGE_DX | 1.24 | 1.24 | 1.24 | 1.24 | 28777.58 | 41437.20 | 40.00 | 1.00 |
PSZ-AC_4:4_UNITARY_PACKAGE_DX | 1.24 | 1.24 | 1.24 | 1.24 | 28872.37 | 41502.31 | 40.00 | 1.00 |
PSZ-AC_5:5_UNITARY_PACKAGE_DX | 1.25 | 1.25 | 1.25 | 1.25 | 29073.49 | 41660.15 | 40.00 | 1.00 |
PSZ-AC_6:6_UNITARY_PACKAGE_DX | 2.31 | 2.31 | 2.31 | 2.31 | 54697.68 | 79286.24 | 40.00 | 1.00 |
PSZ-AC_7:7_UNITARY_PACKAGE_DX | 1.26 | 1.26 | 1.26 | 1.26 | 29902.46 | 42061.63 | 40.00 | 1.00 |
PSZ-AC_8:8_UNITARY_PACKAGE_DX | 1.26 | 1.26 | 1.26 | 1.26 | 29937.35 | 42037.50 | 40.00 | 1.00 |
PSZ-AC_9:9_UNITARY_PACKAGE_DX | 1.27 | 1.27 | 1.27 | 1.27 | 30273.99 | 42281.06 | 40.00 | 1.00 |
PSZ-AC_10:10_UNITARY_PACKAGE_DX | 1.45 | 1.45 | 1.45 | 1.45 | 34353.96 | 46104.04 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | Speed 2 Design Size Rated Total Cooling Capacity [W] | Speed 2 User-Specified Rated Total Cooling Capacity [W] | Speed 1 Design Size Rated Total Cooling Capacity [W] | Speed 1 User-Specified Rated Total Cooling Capacity [W] | Speed 2 Design Size Rated Sensible Heat Ratio | Speed 2 User-Specified Rated Sensible Heat Ratio | Speed 1 Design Size Rated Sensible Heat Ratio | Speed 1 User-Specified Rated Sensible Heat Ratio | |
PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | 2.42 | 1.21 | 2.42 | 52738.53 | 55675.07 | 27837.53 | 55675.07 | 0.695025 | 0.695030 | 0.695030 | 0.695030 |
PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | 1.23 | 0.613585 | 1.23 | 26627.18 | 28121.66 | 14060.83 | 28121.66 | 0.696580 | 0.696580 | 0.696580 | 0.696580 |
PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | 1.24 | 0.617710 | 1.24 | 27280.15 | 28777.58 | 14388.79 | 28777.58 | 0.692272 | 0.692270 | 0.692270 | 0.692270 |
PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | 1.24 | 0.619205 | 1.24 | 27371.81 | 28872.37 | 14436.18 | 28872.37 | 0.692044 | 0.692040 | 0.692040 | 0.692040 |
PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | 1.25 | 0.622820 | 1.25 | 27564.48 | 29073.49 | 14536.75 | 29073.49 | 0.691752 | 0.691750 | 0.691750 | 0.691750 |
PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | 2.31 | 1.15 | 2.31 | 51917.14 | 54697.68 | 27348.84 | 54697.68 | 0.687624 | 0.687620 | 0.687620 | 0.687620 |
PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | 1.26 | 0.632025 | 1.26 | 28377.23 | 29902.46 | 14951.23 | 29902.46 | 0.688270 | 0.688270 | 0.688270 | 0.688270 |
PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | 1.26 | 0.631475 | 1.26 | 28414.54 | 29937.35 | 14968.67 | 29937.35 | 0.687747 | 0.687750 | 0.687750 | 0.687750 |
PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | 1.27 | 0.637055 | 1.27 | 28738.63 | 30273.99 | 15137.00 | 30273.99 | 0.687135 | 0.687140 | 0.687140 | 0.687140 |
PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | 1.45 | 0.724680 | 1.45 | 32607.35 | 34353.96 | 17176.98 | 34353.96 | 0.687762 | 0.687760 | 0.687760 | 0.687760 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | 2.42 | 2643.58 |
PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | 1.23 | 1399.10 |
PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | 1.24 | 1408.51 |
PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | 1.24 | 1411.92 |
PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | 1.25 | 1420.17 |
PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | 2.31 | 2524.36 |
PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | 1.26 | 1441.16 |
PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | 1.26 | 1439.90 |
PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | 1.27 | 1452.63 |
PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | 1.45 | 1586.33 |
Design Size Nominal Capacity [W] | |
PSZ-AC_1:1_UNITARY_PACKAGE_HEATCOIL | 81662.66 |
PSZ-AC_2:2_UNITARY_PACKAGE_HEATCOIL | 41257.18 |
PSZ-AC_3:3_UNITARY_PACKAGE_HEATCOIL | 41437.20 |
PSZ-AC_4:4_UNITARY_PACKAGE_HEATCOIL | 41502.31 |
PSZ-AC_5:5_UNITARY_PACKAGE_HEATCOIL | 41660.15 |
PSZ-AC_6:6_UNITARY_PACKAGE_HEATCOIL | 79286.24 |
PSZ-AC_7:7_UNITARY_PACKAGE_HEATCOIL | 42061.63 |
PSZ-AC_8:8_UNITARY_PACKAGE_HEATCOIL | 42037.50 |
PSZ-AC_9:9_UNITARY_PACKAGE_HEATCOIL | 42281.06 |
PSZ-AC_10:10_UNITARY_PACKAGE_HEATCOIL | 46104.04 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:19:07
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
LGSTORE1_WALL_3 | LGSTORE1_WALL_3_DOOR_1 | LGSTORE1_WALL_3_DOOR_2 | |
LGSTORE1_WALL_1 | LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | |
SMSTORE1_WALL_1 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | |
SMSTORE1_WALL_3 | SMSTORE1_WALL_3_DOOR | |
SMSTORE2_WALL_1 | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | |
SMSTORE2_WALL_3 | SMSTORE2_WALL_3_DOOR | |
SMSTORE3_WALL_1 | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | |
SMSTORE3_WALL_3 | SMSTORE3_WALL_3_DOOR | |
SMSTORE4_WALL_1 | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | |
SMSTORE4_WALL_3 | SMSTORE4_WALL_3_DOOR | |
LGSTORE2_WALL_3 | LGSTORE2_WALL_3_DOOR_1 | LGSTORE2_WALL_3_DOOR_2 | |
LGSTORE2_WALL_1 | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | |
SMSTORE5_WALL_1 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | |
SMSTORE5_WALL_3 | SMSTORE5_WALL_3_DOOR | |
SMSTORE6_WALL_1 | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | |
SMSTORE6_WALL_3 | SMSTORE6_WALL_3_DOOR | |
SMSTORE7_WALL_1 | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | |
SMSTORE7_WALL_3 | SMSTORE7_WALL_3_DOOR | |
SMSTORE8_WALL_1 | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR | |
SMSTORE8_WALL_3 | SMSTORE8_WALL_3_DOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2020-06-03 19:19:07
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2020-06-03 19:19:07
VersionVersion ID | |
1 | 9.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 7.40 | -0.00 | -7.60 | -12.60 | -7.70 | 0.30 | 7.00 | 14.20 | 19.20 | 20.90 | 20.00 | 15.40 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Rochester International Arpt MN USA TMY3 WMO#=726440 | 43.90 | -92.50 | -6.00 | 398.00 | 96634 | 1.1486 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 6.38 | 33.50 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RetailStripmall | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 10 | 118 | 48 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | LGSTORE1 | 0.0 | 0.00 | 0.00 | 0.00 | 7.62 | 11.43 | 2.59 | 1 | 1 | 1 | 0.00 | 15.24 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 1805.20 | TARP | TARP | 348.39 | 276.30 | 247.76 | 20.75 | 6 | 8 | 0 | Yes |
2 | SMSTORE1 | 0.0 | 0.00 | 0.00 | 0.00 | 19.05 | 11.43 | 2.59 | 1 | 1 | 1 | 15.24 | 22.86 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.67 | 10.37 | 6 | 4 | 0 | Yes |
3 | SMSTORE2 | 0.0 | 0.00 | 0.00 | 0.00 | 26.67 | 11.43 | 2.59 | 1 | 1 | 1 | 22.86 | 30.48 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.35 | 6 | 4 | 0 | Yes |
4 | SMSTORE3 | 0.0 | 0.00 | 0.00 | 0.00 | 34.29 | 11.43 | 2.59 | 1 | 1 | 1 | 30.48 | 38.10 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.35 | 6 | 4 | 0 | Yes |
5 | SMSTORE4 | 0.0 | 0.00 | 0.00 | 0.00 | 41.91 | 11.43 | 2.59 | 1 | 1 | 1 | 38.10 | 45.72 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.35 | 6 | 4 | 0 | Yes |
6 | LGSTORE2 | 0.0 | 0.00 | 0.00 | 0.00 | 53.34 | 11.43 | 2.59 | 1 | 1 | 1 | 45.72 | 60.96 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 1805.20 | TARP | TARP | 348.39 | 157.89 | 129.43 | 20.70 | 6 | 8 | 0 | Yes |
7 | SMSTORE5 | 0.0 | 0.00 | 0.00 | 0.00 | 64.77 | 11.43 | 2.59 | 1 | 1 | 1 | 60.96 | 68.58 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.35 | 6 | 4 | 0 | Yes |
8 | SMSTORE6 | 0.0 | 0.00 | 0.00 | 0.00 | 72.39 | 11.43 | 2.59 | 1 | 1 | 1 | 68.58 | 76.20 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.35 | 6 | 4 | 0 | Yes |
9 | SMSTORE7 | 0.0 | 0.00 | 0.00 | 0.00 | 80.01 | 11.43 | 2.59 | 1 | 1 | 1 | 76.20 | 83.82 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.35 | 6 | 4 | 0 | Yes |
10 | SMSTORE8 | 0.0 | 0.00 | 0.00 | 0.00 | 87.63 | 11.43 | 2.59 | 1 | 1 | 1 | 83.82 | 91.44 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 197.36 | 183.13 | 10.35 | 6 | 4 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | LGSTORE1 | 348.39 | 30.0 | 11.614 | 8.610E-002 | 28.817 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 33.117 | No |
2 | SMSTORE1 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 28.817 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 33.117 | No |
3 | SMSTORE2 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 22.628 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 26.928 | No |
4 | SMSTORE3 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 22.628 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 26.928 | No |
5 | SMSTORE4 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 22.628 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 26.928 | No |
6 | LGSTORE2 | 348.39 | 30.0 | 11.614 | 8.610E-002 | 18.322 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 22.622 | No |
7 | SMSTORE5 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 18.322 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 22.622 | No |
8 | SMSTORE6 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 18.322 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 22.622 | No |
9 | SMSTORE7 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 18.322 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 22.622 | No |
10 | SMSTORE8 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 18.322 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 22.622 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | |
1 | LGSTORE1 | TYPE1_OCC_SCH | LGSTORE1 | 348.39 | 30.0 | 30.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 30 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
2 | SMSTORE1 | TYPE1_OCC_SCH | SMSTORE1 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
3 | SMSTORE2 | TYPE2_OCC_SCH | SMSTORE2 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
4 | SMSTORE3 | TYPE2_OCC_SCH | SMSTORE3 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
5 | SMSTORE4 | TYPE2_OCC_SCH | SMSTORE4 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
6 | LGSTORE2 | TYPE3_OCC_SCH | LGSTORE2 | 348.39 | 30.0 | 30.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 30 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
7 | SMSTORE5 | TYPE3_OCC_SCH | SMSTORE5 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
8 | SMSTORE6 | TYPE3_OCC_SCH | SMSTORE6 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
9 | SMSTORE7 | TYPE3_OCC_SCH | SMSTORE7 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
10 | SMSTORE8 | TYPE3_OCC_SCH | SMSTORE8 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | LGSTORE1_LIGHTS | TYPE1_LIGHT_SCH | LGSTORE1 | 348.39 | 30.0 | 6383.296 | 18.322 | 212.804 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 6383.296 |
2 | LGSTORE1_LIGHTS_ALLOWANCE | TYPE1_LIGHT_SCH | LGSTORE1 | 348.39 | 30.0 | 3656.252 | 10.495 | 121.891 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3656.252 |
3 | SMSTORE1_LIGHTS | TYPE1_LIGHT_SCH | SMSTORE1 | 174.19 | 15.0 | 3191.648 | 18.322 | 212.805 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3191.648 |
4 | SMSTORE1_LIGHTS_ALLOWANCE | TYPE1_LIGHT_SCH | SMSTORE1 | 174.19 | 15.0 | 1828.126 | 10.495 | 121.891 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1828.126 |
5 | SMSTORE2_LIGHTS | TYPE2_LIGHT_SCH | SMSTORE2 | 174.19 | 15.0 | 3191.648 | 18.322 | 212.805 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3191.648 |
6 | SMSTORE2_LIGHTS_ALLOWANCE | TYPE2_LIGHT_SCH | SMSTORE2 | 174.19 | 15.0 | 750.000 | 4.306 | 50.007 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 750.000 |
7 | SMSTORE3_LIGHTS | TYPE2_LIGHT_SCH | SMSTORE3 | 174.19 | 15.0 | 3191.648 | 18.322 | 212.805 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3191.648 |
8 | SMSTORE3_LIGHTS_ALLOWANCE | TYPE2_LIGHT_SCH | SMSTORE3 | 174.19 | 15.0 | 750.000 | 4.306 | 50.007 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 750.000 |
9 | SMSTORE4_LIGHTS | TYPE2_LIGHT_SCH | SMSTORE4 | 174.19 | 15.0 | 3191.648 | 18.322 | 212.805 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3191.648 |
10 | SMSTORE4_LIGHTS_ALLOWANCE | TYPE2_LIGHT_SCH | SMSTORE4 | 174.19 | 15.0 | 750.000 | 4.306 | 50.007 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 750.000 |
11 | LGSTORE2_LIGHTS | TYPE3_LIGHT_SCH | LGSTORE2 | 348.39 | 30.0 | 6383.296 | 18.322 | 212.804 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 6383.296 |
12 | LGSTORE2_LIGHTS_ALLOWANCE | TYPE3_LIGHT_SCH | LGSTORE2 | 348.39 | 30.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
13 | SMSTORE5_LIGHTS | TYPE3_LIGHT_SCH | SMSTORE5 | 174.19 | 15.0 | 3191.648 | 18.322 | 212.805 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3191.648 |
14 | SMSTORE5_LIGHTS_ALLOWANCE | TYPE3_LIGHT_SCH | SMSTORE5 | 174.19 | 15.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
15 | SMSTORE6_LIGHTS | TYPE3_LIGHT_SCH | SMSTORE6 | 174.19 | 15.0 | 3191.648 | 18.322 | 212.805 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3191.648 |
16 | SMSTORE6_LIGHTS_ALLOWANCE | TYPE3_LIGHT_SCH | SMSTORE6 | 174.19 | 15.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
17 | SMSTORE7_LIGHTS | TYPE3_LIGHT_SCH | SMSTORE7 | 174.19 | 15.0 | 3191.648 | 18.322 | 212.805 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3191.648 |
18 | SMSTORE7_LIGHTS_ALLOWANCE | TYPE3_LIGHT_SCH | SMSTORE7 | 174.19 | 15.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
19 | SMSTORE8_LIGHTS | TYPE3_LIGHT_SCH | SMSTORE8 | 174.19 | 15.0 | 3191.648 | 18.322 | 212.805 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3191.648 |
20 | SMSTORE8_LIGHTS_ALLOWANCE | TYPE3_LIGHT_SCH | SMSTORE8 | 174.19 | 15.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | LGSTORE1_MISCPLUG_EQUIP | TYPE1_EQUIP_SCH | LGSTORE1 | 348.39 | 30.0 | 1498.062 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1498.062 |
2 | SMSTORE1_MISCPLUG_EQUIP | TYPE1_EQUIP_SCH | SMSTORE1 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
3 | SMSTORE2_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE2 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
4 | SMSTORE3_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE3 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
5 | SMSTORE4_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE4 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
6 | LGSTORE2_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | LGSTORE2 | 348.39 | 30.0 | 1498.062 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1498.062 |
7 | SMSTORE5_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE5 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
8 | SMSTORE6_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE6 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
9 | SMSTORE7_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE7 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
10 | SMSTORE8_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE8 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.975 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.2832 | 0.900 | 0.900 | 0.770 | 0.700 | Rough |
5 | NONRES_EXT_WALL | 20 | 4 | 7 | 0.167 | 0.5136 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
6 | LGSTORE1_FLOOR_FFACTOR | 30 | 2 | 7 | 0.167 | 0.1995 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
7 | SMSTORE1_FLOOR_FFACTOR | 31 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
8 | SMSTORE2_FLOOR_FFACTOR | 32 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | SMSTORE3_FLOOR_FFACTOR | 33 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
10 | SMSTORE4_FLOOR_FFACTOR | 34 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
11 | LGSTORE2_FLOOR_FFACTOR | 35 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | SMSTORE5_FLOOR_FFACTOR | 36 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | SMSTORE6_FLOOR_FFACTOR | 37 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | SMSTORE7_FLOOR_FFACTOR | 38 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | SMSTORE8_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.2888 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2516 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
6 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 3.472 |
7 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
8 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
9 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
10 | NONRES_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.713 |
11 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
12 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.937 |
13 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
14 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
15 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
16 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
17 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
18 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
19 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
20 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
21 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
22 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
23 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
24 | ~FC_Insulation_7 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_8 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_9 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
30 | ~FC_Insulation_10 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.386 |
31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.9747885 | 3.9747885 | 3.9747885 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
14 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
15 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
16 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
17 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
18 | 3 | -0.61927053E-06 | 0.12767249E-08 | -0.37968499E-05 | 0.16832131E-17 |
19 | 2 | 0.77611055 | 0.17315568E-02 | 1.0534842 | -0.72792597E-06 |
20 | 1 | -21.915918 | 0.11588205 | -6.3286394 | 0.20197014 |
21 | 0 | 21.365777 | 0.10835518 | 5.5011278 | |
22 | 7 | -0.33207909E-12 | 0.79542070E-15 | -0.11586622E-12 | 0.10783435E-15 |
23 | 6 | 0.31762832E-07 | 0.14865645E-09 | 0.72503568E-08 | -0.15188138E-12 |
24 | 5 | -0.20568023E-03 | 0.12486053E-05 | -0.10556626E-03 | 0.71569697E-08 |
25 | 4 | 0.31018727 | 0.59758545E-03 | 0.10618022 | -0.36135240E-04 |
26 | 3 | -7.6231853 | 0.18239075E-01 | -2.4448349 | 0.30759039E-01 |
27 | 2 | 42.047589 | 0.63983780E-01 | 15.698525 | -0.34644559 |
28 | 1 | -81.446794 | 0.28535822E-01 | -29.529986 | 1.0978209 |
29 | 0 | 46.824333 | 0.56745654E-03 | 16.282146 | |
30 | 7 | -0.21163652E-08 | -0.68723841E-15 | 0.43910983E-14 | -0.57684426E-16 |
31 | 6 | 0.56109385E-05 | 0.38186281E-08 | 0.31898696E-02 | -0.26759299E-04 |
32 | 5 | -0.40164657E-03 | 0.22608617E-05 | -0.22372456 | 0.19561502E-02 |
33 | 4 | 0.92272104E-02 | 0.10289840E-03 | 4.8295456 | -0.45264980E-01 |
34 | 3 | -0.80993241E-01 | 0.81813938E-03 | -38.021416 | 0.39865375 |
35 | 2 | 0.28754352 | 0.13608947E-02 | 116.48395 | -1.4179393 |
36 | 1 | -0.41499682 | 0.41453381E-03 | -143.90731 | 2.0490399 |
37 | 0 | 0.20232414 | 0.10048102E-04 | 60.838472 | |
38 | 7 | -0.37862368E-08 | -0.38757603E-14 | 0.11479940E-14 | -0.41635801E-16 |
39 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
40 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
41 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
42 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
43 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
44 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
45 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
46 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479937E-14 | -0.41635796E-16 |
47 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
48 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
49 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
50 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
51 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
52 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
53 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
54 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479940E-14 | -0.41635801E-16 |
55 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
56 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
57 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
58 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
59 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
60 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
61 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
62 | 7 | -0.37862368E-08 | -0.38757603E-14 | 0.11479940E-14 | -0.41635801E-16 |
63 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
64 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
65 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
66 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
67 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
68 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
69 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
70 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479937E-14 | -0.41635796E-16 |
71 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
72 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
73 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
74 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
75 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
76 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
77 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
78 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479937E-14 | -0.41635796E-16 |
79 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
80 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
81 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
82 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
83 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
84 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
85 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
86 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479940E-14 | -0.41635801E-16 |
87 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
88 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
89 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
90 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
91 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
92 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
93 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
94 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479936E-14 | -0.41635794E-16 |
95 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
96 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
97 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
98 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
99 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
100 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
101 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
102 | 7 | -0.14484255E-08 | -0.22640907E-15 | 0.11860658E-13 | -0.17473455E-15 |
103 | 6 | 0.80640390E-05 | 0.55493782E-08 | 0.31828288E-02 | -0.26700235E-04 |
104 | 5 | -0.58275339E-03 | 0.32892043E-05 | -0.22332434 | 0.19526176E-02 |
105 | 4 | 0.13421983E-01 | 0.14977251E-03 | 4.8228790 | -0.45200897E-01 |
106 | 3 | -0.11791368 | 0.11914425E-02 | -37.983753 | 0.39823745 |
107 | 2 | 0.41875064 | 0.19825898E-02 | 116.41064 | -1.4169588 |
108 | 1 | -0.60444169 | 0.60433957E-03 | -143.86415 | 2.0483306 |
109 | 0 | 0.29470347 | 0.14596444E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.47_SHGC_0.4 | 29 | 1 | VerySmooth | 2.672 | 0.394 | 0.315 | 0.401 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 2.40629E-002 | 0.31435 | 0.46917 | 0.46917 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11822 | 1.00000 | No |
Calculation Method | Value {days} | Allowable Number Figures in Shadow Overlap {} | Polygon Clipping Algorithm | Sky Diffuse Modeling Algorithm | External Shading Calculation Method | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | AverageOverDaysInFrequency | 30 | 15000 | SutherlandHodgman | SimpleSkyDiffuseModeling | InternalCalculation | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | GAS TANK1 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
2 | WaterHeater:Mixed | GAS TANK2 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
3 | WaterHeater:Mixed | GAS TANK3 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
4 | WaterHeater:Mixed | GAS TANK4 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
5 | WaterHeater:Mixed | GAS TANK5 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
6 | WaterHeater:Mixed | GAS TANK6 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
7 | WaterHeater:Mixed | GAS TANK7 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | LGSTORE1_WALL_2 | 0 | 118.41 | 56.08 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 4 | No | No |
2 | LGSTORE1_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 4 | No | No |
3 | LGSTORE1_WALL_3_DOOR_1 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 0 | No | No |
4 | LGSTORE1_WALL_3_DOOR_2 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 0 | No | No |
5 | LGSTORE1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 0 | No | No |
6 | LGSTORE1_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 4 | No | No |
7 | LGSTORE1_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 1 | No | No |
8 | LGSTORE1_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 1 | No | No |
9 | LGSTORE1_WALL_1_WINDOW_3 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 1 | No | No |
10 | LGSTORE1_WALL_1_WINDOW_4 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 1 | No | No |
11 | LGSTORE1_WALL_1_DOOR_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 1 | No | No |
12 | LGSTORE1_WALL_1_DOOR_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 1 | No | No |
13 | LGSTORE1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 0 | No | No |
14 | LGSTORE1_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 0 | No | No |
15 | LGSTORE1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 0 | No | No |
16 | SMSTORE1_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
17 | SMSTORE1_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
18 | SMSTORE1_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
19 | SMSTORE1_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
20 | SMSTORE1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
21 | SMSTORE1_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
22 | SMSTORE1_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
23 | SMSTORE1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
24 | SMSTORE1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
25 | SMSTORE1_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
26 | SMSTORE1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
27 | SMSTORE2_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
28 | SMSTORE2_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
29 | SMSTORE2_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
30 | SMSTORE2_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
31 | SMSTORE2_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
32 | SMSTORE2_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
33 | SMSTORE2_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
34 | SMSTORE2_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
35 | SMSTORE2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
36 | SMSTORE2_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
37 | SMSTORE2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
38 | SMSTORE3_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
39 | SMSTORE3_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
40 | SMSTORE3_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
41 | SMSTORE3_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
42 | SMSTORE3_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
43 | SMSTORE3_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
44 | SMSTORE3_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
45 | SMSTORE3_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
46 | SMSTORE3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
47 | SMSTORE3_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
48 | SMSTORE3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
49 | SMSTORE4_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
50 | SMSTORE4_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
51 | SMSTORE4_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
52 | SMSTORE4_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
53 | SMSTORE4_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
54 | SMSTORE4_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 3 | No | No |
55 | SMSTORE4_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
56 | SMSTORE4_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
57 | SMSTORE4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
58 | SMSTORE4_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
59 | SMSTORE4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
60 | LGSTORE2_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
61 | LGSTORE2_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 4 | No | No |
62 | LGSTORE2_WALL_3_DOOR_1 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
63 | LGSTORE2_WALL_3_DOOR_2 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
64 | LGSTORE2_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
65 | LGSTORE2_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 4 | No | No |
66 | LGSTORE2_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
67 | LGSTORE2_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
68 | LGSTORE2_WALL_1_WINDOW_3 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
69 | LGSTORE2_WALL_1_WINDOW_4 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
70 | LGSTORE2_WALL_1_DOOR_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
71 | LGSTORE2_WALL_1_DOOR_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
72 | LGSTORE2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
73 | LGSTORE2_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
74 | LGSTORE2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
75 | SMSTORE5_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
76 | SMSTORE5_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
77 | SMSTORE5_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
78 | SMSTORE5_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
79 | SMSTORE5_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
80 | SMSTORE5_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
81 | SMSTORE5_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
82 | SMSTORE5_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
83 | SMSTORE5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
84 | SMSTORE5_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
85 | SMSTORE5_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
86 | SMSTORE6_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
87 | SMSTORE6_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
88 | SMSTORE6_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
89 | SMSTORE6_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
90 | SMSTORE6_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
91 | SMSTORE6_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
92 | SMSTORE6_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
93 | SMSTORE6_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
94 | SMSTORE6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
95 | SMSTORE6_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
96 | SMSTORE6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
97 | SMSTORE7_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
98 | SMSTORE7_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
99 | SMSTORE7_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
100 | SMSTORE7_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
101 | SMSTORE7_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
102 | SMSTORE7_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 3 | No | No |
103 | SMSTORE7_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
104 | SMSTORE7_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
105 | SMSTORE7_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
106 | SMSTORE7_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
107 | SMSTORE7_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
108 | SMSTORE8_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 4 | No | No |
109 | SMSTORE8_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 1 | No | No |
110 | SMSTORE8_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 1 | No | No |
111 | SMSTORE8_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 1 | No | No |
112 | SMSTORE8_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
113 | SMSTORE8_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 3 | No | No |
114 | SMSTORE8_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
115 | SMSTORE8_WALL_4 | 0 | 118.41 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 3 | No | No |
116 | SMSTORE8_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
117 | SMSTORE8_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
118 | SMSTORE8_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | LGSTORE1_INFILTRATION | TYPE1_INFIL_SCH | LGSTORE1 | 348.39 | 30.0 | 0.286 | 8.224E-004 | 4.530E-004 | 0.571 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | LGSTORE1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | LGSTORE1 | 348.39 | 30.0 | 0.389 | 1.116E-003 | 6.149E-004 | 0.776 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | SMSTORE1_INFILTRATION | TYPE1_INFIL_SCH | SMSTORE1 | 174.19 | 15.0 | 8.210E-002 | 4.713E-004 | 3.194E-004 | 0.327 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | SMSTORE1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE1 | 174.19 | 15.0 | 0.222 | 1.276E-003 | 8.648E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
5 | SMSTORE2_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE2 | 174.19 | 15.0 | 8.210E-002 | 4.713E-004 | 3.194E-004 | 0.327 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | SMSTORE2_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE2 | 174.19 | 15.0 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
7 | SMSTORE3_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE3 | 174.19 | 15.0 | 8.210E-002 | 4.713E-004 | 3.194E-004 | 0.327 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | SMSTORE3_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE3 | 174.19 | 15.0 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | SMSTORE4_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE4 | 174.19 | 15.0 | 8.210E-002 | 4.713E-004 | 3.194E-004 | 0.327 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | SMSTORE4_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE4 | 174.19 | 15.0 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
11 | LGSTORE2_INFILTRATION | TYPE3_INFIL_SCH | LGSTORE2 | 348.39 | 30.0 | 0.164 | 4.713E-004 | 3.194E-004 | 0.327 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | LGSTORE2_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | LGSTORE2 | 348.39 | 30.0 | 0.389 | 1.116E-003 | 7.565E-004 | 0.776 | 1.000 | 0.000 | 0.000 | 0.000 |
13 | SMSTORE5_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE5 | 174.19 | 15.0 | 8.210E-002 | 4.713E-004 | 3.194E-004 | 0.327 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | SMSTORE5_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE5 | 174.19 | 15.0 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
15 | SMSTORE6_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE6 | 174.19 | 15.0 | 8.210E-002 | 4.713E-004 | 3.194E-004 | 0.327 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | SMSTORE6_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE6 | 174.19 | 15.0 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
17 | SMSTORE7_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE7 | 174.19 | 15.0 | 8.210E-002 | 4.713E-004 | 3.194E-004 | 0.327 | 0.000 | 0.000 | 0.224 | 0.000 |
18 | SMSTORE7_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE7 | 174.19 | 15.0 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
19 | SMSTORE8_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE8 | 174.19 | 15.0 | 0.204 | 1.172E-003 | 5.440E-004 | 0.815 | 0.000 | 0.000 | 0.224 | 0.000 |
20 | SMSTORE8_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE8 | 174.19 | 15.0 | 0.222 | 1.276E-003 | 5.921E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | LGSTORE1 | Mixing/Well-Stirred |
2 | SMSTORE1 | Mixing/Well-Stirred |
3 | SMSTORE2 | Mixing/Well-Stirred |
4 | SMSTORE3 | Mixing/Well-Stirred |
5 | SMSTORE4 | Mixing/Well-Stirred |
6 | LGSTORE2 | Mixing/Well-Stirred |
7 | SMSTORE5 | Mixing/Well-Stirred |
8 | SMSTORE6 | Mixing/Well-Stirred |
9 | SMSTORE7 | Mixing/Well-Stirred |
10 | SMSTORE8 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone LGSTORE1 | 1.2000 |
3 | Zone SMSTORE1 | 1.2000 |
4 | Zone SMSTORE2 | 1.2000 |
5 | Zone SMSTORE3 | 1.2000 |
6 | Zone SMSTORE4 | 1.2000 |
7 | Zone LGSTORE2 | 1.2000 |
8 | Zone SMSTORE5 | 1.2000 |
9 | Zone SMSTORE6 | 1.2000 |
10 | Zone SMSTORE7 | 1.2000 |
11 | Zone SMSTORE8 | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone LGSTORE1 | 1.2000 |
3 | Zone SMSTORE1 | 1.2000 |
4 | Zone SMSTORE2 | 1.2000 |
5 | Zone SMSTORE3 | 1.2000 |
6 | Zone SMSTORE4 | 1.2000 |
7 | Zone LGSTORE2 | 1.2000 |
8 | Zone SMSTORE5 | 1.2000 |
9 | Zone SMSTORE6 | 1.2000 |
10 | Zone SMSTORE7 | 1.2000 |
11 | Zone SMSTORE8 | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | LGSTORE1 | Cooling | 24756.46770 | 29707.76124 | 1.90532 | 2.28638 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 31.20000 | 1.53444E-002 | 348.38640 | 29.99610 | 0.53091 | 0.00000 |
2 | LGSTORE1 | Heating | 44547.56702 | 53457.08042 | 2.01277 | 2.41532 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -26.20000 | 3.61342E-004 | 348.38640 | 29.99610 | 0.53091 | 0.00000 |
3 | SMSTORE1 | Cooling | 12972.24309 | 15566.69171 | 0.99839 | 1.19806 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 31.11167 | 1.53444E-002 | 174.19320 | 14.99800 | 0.26545 | 0.00000 |
4 | SMSTORE1 | Heating | 22634.00071 | 27160.80086 | 1.02264 | 1.22717 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -26.20000 | 3.61342E-004 | 174.19320 | 14.99800 | 0.26545 | 0.00000 |
5 | SMSTORE2 | Cooling | 12242.52546 | 14691.03055 | 0.94222 | 1.13066 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 31.11167 | 1.53444E-002 | 174.19320 | 14.99800 | 0.26545 | 0.00000 |
6 | SMSTORE2 | Heating | 22786.23012 | 27343.47614 | 1.02952 | 1.23542 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -26.20000 | 3.61342E-004 | 174.19320 | 14.99800 | 0.26545 | 0.00000 |
7 | SMSTORE3 | Cooling | 12205.27611 | 14646.33133 | 0.93935 | 1.12722 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 31.11167 | 1.53444E-002 | 174.19320 | 14.99800 | 0.26545 | 0.00000 |
8 | SMSTORE3 | Heating | 22841.29234 | 27409.55080 | 1.03200 | 1.23841 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -26.20000 | 3.61342E-004 | 174.19320 | 14.99800 | 0.26545 | 0.00000 |
9 | SMSTORE4 | Cooling | 12157.64973 | 14589.17967 | 0.93569 | 1.12283 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 31.11167 | 1.53444E-002 | 174.19320 | 14.99800 | 0.26545 | 0.00000 |
10 | SMSTORE4 | Heating | 22974.76835 | 27569.72202 | 1.03804 | 1.24564 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -26.20000 | 3.61342E-004 | 174.19320 | 14.99800 | 0.26545 | 0.00000 |
11 | LGSTORE2 | Cooling | 22272.32880 | 26726.79456 | 1.71407 | 2.05689 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 31.02333 | 1.53444E-002 | 348.38640 | 29.99610 | 0.53091 | 0.00000 |
12 | LGSTORE2 | Heating | 42537.73705 | 51045.28446 | 1.92200 | 2.30640 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -26.20000 | 3.61342E-004 | 348.38640 | 29.99610 | 0.53091 | 0.00000 |
13 | SMSTORE5 | Cooling | 11603.85951 | 13924.63142 | 0.89305 | 1.07167 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 31.02333 | 1.53444E-002 | 174.19320 | 14.99800 | 0.26545 | 0.00000 |
14 | SMSTORE5 | Heating | 23314.26579 | 27977.11895 | 1.05338 | 1.26405 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -26.20000 | 3.61342E-004 | 174.19320 | 14.99800 | 0.26545 | 0.00000 |
15 | SMSTORE6 | Cooling | 11521.80981 | 13826.17178 | 0.88674 | 1.06409 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 31.02333 | 1.53444E-002 | 174.19320 | 14.99800 | 0.26545 | 0.00000 |
16 | SMSTORE6 | Heating | 23293.85452 | 27952.62543 | 1.05246 | 1.26295 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -26.20000 | 3.61342E-004 | 174.19320 | 14.99800 | 0.26545 | 0.00000 |
17 | SMSTORE7 | Cooling | 11427.55267 | 13713.06320 | 0.87948 | 1.05538 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 31.02333 | 1.53444E-002 | 174.19320 | 14.99800 | 0.26545 | 0.00000 |
18 | SMSTORE7 | Heating | 23499.81767 | 28199.78120 | 1.06176 | 1.27411 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -26.20000 | 3.61342E-004 | 174.19320 | 14.99800 | 0.26545 | 0.00000 |
19 | SMSTORE8 | Cooling | 11634.07341 | 13960.88809 | 0.89524 | 1.07429 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | 30.67000 | 1.53444E-002 | 174.19320 | 14.99800 | 0.26545 | 0.00000 |
20 | SMSTORE8 | Heating | 26732.88651 | 32079.46381 | 1.20780 | 1.44936 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -26.20000 | 3.61342E-004 | 174.19320 | 14.99800 | 0.26545 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC_1:1 | Cooling | Sensible | 33731.18 | 2.28638 | 2.28638 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-AC_1:1 | Heating | Sensible | 81662.66 | 2.41532 | 2.41532 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
3 | PSZ-AC_2:2 | Cooling | Sensible | 17564.88 | 1.19806 | 1.19806 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-AC_2:2 | Heating | Sensible | 41257.18 | 1.22717 | 1.22717 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
5 | PSZ-AC_3:3 | Cooling | Sensible | 16701.07 | 1.13066 | 1.13066 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
6 | PSZ-AC_3:3 | Heating | Sensible | 41437.20 | 1.23542 | 1.23542 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
7 | PSZ-AC_4:4 | Cooling | Sensible | 16656.67 | 1.12722 | 1.12722 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
8 | PSZ-AC_4:4 | Heating | Sensible | 41502.31 | 1.23841 | 1.23841 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
9 | PSZ-AC_5:5 | Cooling | Sensible | 16600.35 | 1.12283 | 1.12283 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
10 | PSZ-AC_5:5 | Heating | Sensible | 41660.15 | 1.24564 | 1.24564 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
11 | PSZ-AC_6:6 | Cooling | Sensible | 30780.48 | 2.05689 | 2.05689 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
12 | PSZ-AC_6:6 | Heating | Sensible | 79286.24 | 2.30640 | 2.30640 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
13 | PSZ-AC_7:7 | Cooling | Sensible | 15942.59 | 1.07167 | 1.07167 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
14 | PSZ-AC_7:7 | Heating | Sensible | 42061.63 | 1.26405 | 1.26405 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
15 | PSZ-AC_8:8 | Cooling | Sensible | 15845.98 | 1.06409 | 1.06409 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
16 | PSZ-AC_8:8 | Heating | Sensible | 42037.50 | 1.26295 | 1.26295 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
17 | PSZ-AC_9:9 | Cooling | Sensible | 15734.57 | 1.05538 | 1.05538 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
18 | PSZ-AC_9:9 | Heating | Sensible | 42281.06 | 1.27411 | 1.27411 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
19 | PSZ-AC_10:10 | Cooling | Sensible | 15865.83 | 1.07429 | 1.07429 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
20 | PSZ-AC_10:10 | Heating | Sensible | 46104.04 | 1.44936 | 1.44936 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:Uncontrolled | LGSTORE1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.41532 |
2 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.22717 |
3 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE2 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.23542 |
4 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.23841 |
5 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE4 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.24564 |
6 | AirTerminal:SingleDuct:Uncontrolled | LGSTORE2 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.30640 |
7 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE5 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.26405 |
8 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.26295 |
9 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE7 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.27411 |
10 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE8 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.44936 |
11 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.41532 |
12 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.41532 |
13 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.41532 |
14 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 2.41532 |
15 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.41532 |
16 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Main Design Air Flow Rate [m3/s] | 2.41532 |
17 | AirLoopHVAC | PSZ-AC_1:1 | User Heating Air Flow Ratio [] | 1.00000 |
18 | AirLoopHVAC | PSZ-AC_1:1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
19 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.22717 |
20 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.22717 |
21 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.22717 |
22 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.22717 |
23 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.22717 |
24 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Main Design Air Flow Rate [m3/s] | 1.22717 |
25 | AirLoopHVAC | PSZ-AC_2:2 | User Heating Air Flow Ratio [] | 1.00000 |
26 | AirLoopHVAC | PSZ-AC_2:2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
27 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.23542 |
28 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.23542 |
29 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.23542 |
30 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.23542 |
31 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.23542 |
32 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Main Design Air Flow Rate [m3/s] | 1.23542 |
33 | AirLoopHVAC | PSZ-AC_3:3 | User Heating Air Flow Ratio [] | 1.00000 |
34 | AirLoopHVAC | PSZ-AC_3:3 | Calculated Heating Air Flow Ratio [] | 1.00000 |
35 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.23841 |
36 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.23841 |
37 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.23841 |
38 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.23841 |
39 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.23841 |
40 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Main Design Air Flow Rate [m3/s] | 1.23841 |
41 | AirLoopHVAC | PSZ-AC_4:4 | User Heating Air Flow Ratio [] | 1.00000 |
42 | AirLoopHVAC | PSZ-AC_4:4 | Calculated Heating Air Flow Ratio [] | 1.00000 |
43 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.24564 |
44 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.24564 |
45 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.24564 |
46 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.24564 |
47 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.24564 |
48 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Main Design Air Flow Rate [m3/s] | 1.24564 |
49 | AirLoopHVAC | PSZ-AC_5:5 | User Heating Air Flow Ratio [] | 1.00000 |
50 | AirLoopHVAC | PSZ-AC_5:5 | Calculated Heating Air Flow Ratio [] | 1.00000 |
51 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.30640 |
52 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.30640 |
53 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.30640 |
54 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Heating Design Air Flow Rate [m3/s] | 2.30640 |
55 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.30640 |
56 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Main Design Air Flow Rate [m3/s] | 2.30640 |
57 | AirLoopHVAC | PSZ-AC_6:6 | User Heating Air Flow Ratio [] | 1.00000 |
58 | AirLoopHVAC | PSZ-AC_6:6 | Calculated Heating Air Flow Ratio [] | 1.00000 |
59 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.26405 |
60 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.26405 |
61 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.26405 |
62 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.26405 |
63 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.26405 |
64 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Main Design Air Flow Rate [m3/s] | 1.26405 |
65 | AirLoopHVAC | PSZ-AC_7:7 | User Heating Air Flow Ratio [] | 1.00000 |
66 | AirLoopHVAC | PSZ-AC_7:7 | Calculated Heating Air Flow Ratio [] | 1.00000 |
67 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.26295 |
68 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.26295 |
69 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.26295 |
70 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.26295 |
71 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.26295 |
72 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Main Design Air Flow Rate [m3/s] | 1.26295 |
73 | AirLoopHVAC | PSZ-AC_8:8 | User Heating Air Flow Ratio [] | 1.00000 |
74 | AirLoopHVAC | PSZ-AC_8:8 | Calculated Heating Air Flow Ratio [] | 1.00000 |
75 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.27411 |
76 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.27411 |
77 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.27411 |
78 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.27411 |
79 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.27411 |
80 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Main Design Air Flow Rate [m3/s] | 1.27411 |
81 | AirLoopHVAC | PSZ-AC_9:9 | User Heating Air Flow Ratio [] | 1.00000 |
82 | AirLoopHVAC | PSZ-AC_9:9 | Calculated Heating Air Flow Ratio [] | 1.00000 |
83 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.44936 |
84 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.44936 |
85 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.44936 |
86 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.44936 |
87 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.44936 |
88 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Main Design Air Flow Rate [m3/s] | 1.44936 |
89 | AirLoopHVAC | PSZ-AC_10:10 | User Heating Air Flow Ratio [] | 1.00000 |
90 | AirLoopHVAC | PSZ-AC_10:10 | Calculated Heating Air Flow Ratio [] | 1.00000 |
91 | AirLoopHVAC | PSZ-AC_1:1 | Design Supply Air Flow Rate [m3/s] | 2.41532 |
92 | AirLoopHVAC | PSZ-AC_2:2 | Design Supply Air Flow Rate [m3/s] | 1.22717 |
93 | AirLoopHVAC | PSZ-AC_3:3 | Design Supply Air Flow Rate [m3/s] | 1.23542 |
94 | AirLoopHVAC | PSZ-AC_4:4 | Design Supply Air Flow Rate [m3/s] | 1.23841 |
95 | AirLoopHVAC | PSZ-AC_5:5 | Design Supply Air Flow Rate [m3/s] | 1.24564 |
96 | AirLoopHVAC | PSZ-AC_6:6 | Design Supply Air Flow Rate [m3/s] | 2.30640 |
97 | AirLoopHVAC | PSZ-AC_7:7 | Design Supply Air Flow Rate [m3/s] | 1.26405 |
98 | AirLoopHVAC | PSZ-AC_8:8 | Design Supply Air Flow Rate [m3/s] | 1.26295 |
99 | AirLoopHVAC | PSZ-AC_9:9 | Design Supply Air Flow Rate [m3/s] | 1.27411 |
100 | AirLoopHVAC | PSZ-AC_10:10 | Design Supply Air Flow Rate [m3/s] | 1.44936 |
101 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.41532 |
102 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.53091 |
103 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.41532 |
104 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.41532 |
105 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.41532 |
106 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 2.41532 |
107 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.41532 |
108 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.20766 |
109 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 2.41532 |
110 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 52738.53118 |
111 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 55675.07000 |
112 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 27837.53500 |
113 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 55675.07000 |
114 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.69503 |
115 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.69503 |
116 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.69503 |
117 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.69503 |
118 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 55675.07000 |
119 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 81662.66467 |
120 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
121 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
122 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.41532 |
123 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 2643.58191 |
124 | Coil:Heating:Fuel | PSZ-AC_1:1_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 81662.66467 |
125 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.22717 |
126 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.26545 |
127 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.22717 |
128 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.22717 |
129 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.22717 |
130 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.22717 |
131 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.22717 |
132 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.61359 |
133 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.22717 |
134 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 26627.17805 |
135 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 28121.66000 |
136 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 14060.83000 |
137 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 28121.66000 |
138 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.69658 |
139 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.69658 |
140 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.69658 |
141 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.69658 |
142 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 28121.66000 |
143 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 41257.18134 |
144 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
145 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
146 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.22717 |
147 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1399.10439 |
148 | Coil:Heating:Fuel | PSZ-AC_2:2_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 41257.18134 |
149 | Controller:OutdoorAir | PSZ-AC_3:3_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.23542 |
150 | Controller:OutdoorAir | PSZ-AC_3:3_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.26545 |
151 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.23542 |
152 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.23542 |
153 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.23542 |
154 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.23542 |
155 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.23542 |
156 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.61771 |
157 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.23542 |
158 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 27280.14930 |
159 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 28777.58000 |
160 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 14388.79000 |
161 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 28777.58000 |
162 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.69227 |
163 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.69227 |
164 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.69227 |
165 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.69227 |
166 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 28777.58000 |
167 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 41437.19806 |
168 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
169 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
170 | Fan:SystemModel | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.23542 |
171 | Fan:SystemModel | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1408.51487 |
172 | Coil:Heating:Fuel | PSZ-AC_3:3_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 41437.19806 |
173 | Controller:OutdoorAir | PSZ-AC_4:4_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.23841 |
174 | Controller:OutdoorAir | PSZ-AC_4:4_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.26545 |
175 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.23841 |
176 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.23841 |
177 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.23841 |
178 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.23841 |
179 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.23841 |
180 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.61921 |
181 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.23841 |
182 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 27371.80954 |
183 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 28872.37000 |
184 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 14436.18500 |
185 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 28872.37000 |
186 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.69204 |
187 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.69204 |
188 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.69204 |
189 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.69204 |
190 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 28872.37000 |
191 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 41502.31125 |
192 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
193 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
194 | Fan:SystemModel | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.23841 |
195 | Fan:SystemModel | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1411.91873 |
196 | Coil:Heating:Fuel | PSZ-AC_4:4_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 41502.31125 |
197 | Controller:OutdoorAir | PSZ-AC_5:5_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.24564 |
198 | Controller:OutdoorAir | PSZ-AC_5:5_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.26545 |
199 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.24564 |
200 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.24564 |
201 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.24564 |
202 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.24564 |
203 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.24564 |
204 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.62282 |
205 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.24564 |
206 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 27564.48006 |
207 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 29073.49000 |
208 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 14536.74500 |
209 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 29073.49000 |
210 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.69175 |
211 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.69175 |
212 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.69175 |
213 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.69175 |
214 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 29073.49000 |
215 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 41660.15307 |
216 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
217 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
218 | Fan:SystemModel | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.24564 |
219 | Fan:SystemModel | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1420.17025 |
220 | Coil:Heating:Fuel | PSZ-AC_5:5_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 41660.15307 |
221 | Controller:OutdoorAir | PSZ-AC_6:6_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.30640 |
222 | Controller:OutdoorAir | PSZ-AC_6:6_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.53091 |
223 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.30640 |
224 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.30640 |
225 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.30640 |
226 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 2.30640 |
227 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.30640 |
228 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.15320 |
229 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 2.30640 |
230 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 51917.13685 |
231 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 54697.68000 |
232 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 27348.84000 |
233 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 54697.68000 |
234 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.68762 |
235 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.68762 |
236 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.68762 |
237 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.68762 |
238 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 54697.68000 |
239 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 79286.23740 |
240 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
241 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
242 | Fan:SystemModel | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.30640 |
243 | Fan:SystemModel | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 2524.36403 |
244 | Coil:Heating:Fuel | PSZ-AC_6:6_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 79286.23740 |
245 | Controller:OutdoorAir | PSZ-AC_7:7_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.26405 |
246 | Controller:OutdoorAir | PSZ-AC_7:7_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.26545 |
247 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.26405 |
248 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.26405 |
249 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.26405 |
250 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.26405 |
251 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.26405 |
252 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.63203 |
253 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.26405 |
254 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 28377.22551 |
255 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 29902.46000 |
256 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 14951.23000 |
257 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 29902.46000 |
258 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.68827 |
259 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.68827 |
260 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.68827 |
261 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.68827 |
262 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 29902.46000 |
263 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 42061.63427 |
264 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
265 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
266 | Fan:SystemModel | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.26405 |
267 | Fan:SystemModel | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1441.15992 |
268 | Coil:Heating:Fuel | PSZ-AC_7:7_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 42061.63427 |
269 | Controller:OutdoorAir | PSZ-AC_8:8_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.26295 |
270 | Controller:OutdoorAir | PSZ-AC_8:8_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.26545 |
271 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.26295 |
272 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.26295 |
273 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.26295 |
274 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.26295 |
275 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.26295 |
276 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.63148 |
277 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.26295 |
278 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 28414.53539 |
279 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 29937.35000 |
280 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 14968.67500 |
281 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 29937.35000 |
282 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.68775 |
283 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.68775 |
284 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.68775 |
285 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.68775 |
286 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 29937.35000 |
287 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 42037.49724 |
288 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
289 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
290 | Fan:SystemModel | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.26295 |
291 | Fan:SystemModel | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1439.89813 |
292 | Coil:Heating:Fuel | PSZ-AC_8:8_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 42037.49724 |
293 | Controller:OutdoorAir | PSZ-AC_9:9_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.27411 |
294 | Controller:OutdoorAir | PSZ-AC_9:9_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.26545 |
295 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.27411 |
296 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.27411 |
297 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.27411 |
298 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.27411 |
299 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.27411 |
300 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.63706 |
301 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.27411 |
302 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 28738.62732 |
303 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 30273.99000 |
304 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 15136.99500 |
305 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 30273.99000 |
306 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.68714 |
307 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.68714 |
308 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.68714 |
309 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.68714 |
310 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 30273.99000 |
311 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 42281.05677 |
312 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
313 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
314 | Fan:SystemModel | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.27411 |
315 | Fan:SystemModel | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1452.63055 |
316 | Coil:Heating:Fuel | PSZ-AC_9:9_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 42281.05677 |
317 | Controller:OutdoorAir | PSZ-AC_10:10_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.44936 |
318 | Controller:OutdoorAir | PSZ-AC_10:10_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.26545 |
319 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.44936 |
320 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.44936 |
321 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.44936 |
322 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.44936 |
323 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.44936 |
324 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.72468 |
325 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.44936 |
326 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 32607.34568 |
327 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 34353.96000 |
328 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 17176.98000 |
329 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 34353.96000 |
330 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.68776 |
331 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.68776 |
332 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.68776 |
333 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.68776 |
334 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 34353.96000 |
335 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 46104.04448 |
336 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
337 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
338 | Fan:SystemModel | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.44936 |
339 | Fan:SystemModel | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1586.33114 |
340 | Coil:Heating:Fuel | PSZ-AC_10:10_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 46104.04448 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | 53772.3 | 9.98 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | 27155.0 | 31.30 | |||
3 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | 27804.1 | 41.15 | |||
4 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | 27896.6 | 51.55 | |||
5 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | 28092.0 | 61.72 | |||
6 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | 52879.8 | 41.19 | |||
7 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | 28906.2 | 89.91 | |||
8 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | 28941.9 | 100.36 | |||
9 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | 29269.7 | 109.82 | |||
10 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | 33211.6 | 107.30 |
Zone Name | # Surfaces | |
1 | LGSTORE1 | 15 |
2 | SMSTORE1 | 11 |
3 | SMSTORE2 | 11 |
4 | SMSTORE3 | 11 |
5 | SMSTORE4 | 11 |
6 | LGSTORE2 | 15 |
7 | SMSTORE5 | 11 |
8 | SMSTORE6 | 11 |
9 | SMSTORE7 | 11 |
10 | SMSTORE8 | 11 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | LGSTORE1_WALL_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.514 | 0.477 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | LGSTORE1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.514 | 0.477 | 71.15 | 78.94 | 71.15 | 0.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | LGSTORE1_WALL_3_DOOR_1 | Door | LGSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
4 | LGSTORE1_WALL_3_DOOR_2 | Door | LGSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
5 | LGSTORE1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
6 | LGSTORE1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.514 | 0.477 | 58.20 | 78.94 | 58.20 | 180.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
7 | LGSTORE1_WALL_1_WINDOW_1 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.47_SHGC_0.4 | N/A | 2.672 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
8 | LGSTORE1_WALL_1_WINDOW_2 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.47_SHGC_0.4 | N/A | 2.672 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
9 | LGSTORE1_WALL_1_WINDOW_3 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.47_SHGC_0.4 | N/A | 2.672 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
10 | LGSTORE1_WALL_1_WINDOW_4 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.47_SHGC_0.4 | N/A | 2.672 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
11 | LGSTORE1_WALL_1_DOOR_1 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.47_SHGC_0.4 | N/A | 2.672 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
12 | LGSTORE1_WALL_1_DOOR_2 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.47_SHGC_0.4 | N/A | 2.672 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
13 | LGSTORE1_FLOOR | Floor | CTF - ConductionTransferFunction | LGSTORE1_FLOOR_FFACTOR | 0.199 | 0.190 | 348.39 | 348.39 | 348.39 | 270.00 | 180.00 | 22.86 | 15.24 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | LGSTORE1_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 348.39 | 348.39 | 348.39 | 270.00 | 0.00 | 22.86 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
15 | LGSTORE1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 696.77 | 696.77 | 696.77 | 0.00 | 90.00 | 696.77 | 1.00 | 0.00 | LGSTORE1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
16 | SMSTORE1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.514 | 0.477 | 29.10 | 39.47 | 29.10 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
17 | SMSTORE1_WALL_1_WINDOW_1 | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.47_SHGC_0.4 | N/A | 2.672 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
18 | SMSTORE1_WALL_1_WINDOW_2 | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.47_SHGC_0.4 | N/A | 2.672 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
19 | SMSTORE1_WALL_1_DOOR | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.47_SHGC_0.4 | N/A | 2.672 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
20 | SMSTORE1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | SMSTORE1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.514 | 0.477 | 35.57 | 39.47 | 35.57 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | SMSTORE1_WALL_3_DOOR | Door | SMSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
23 | SMSTORE1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE2_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
24 | SMSTORE1_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE1_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | SMSTORE1_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
26 | SMSTORE1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
27 | SMSTORE2_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.514 | 0.477 | 29.12 | 39.47 | 29.12 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | SMSTORE2_WALL_1_WINDOW_1 | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.47_SHGC_0.4 | N/A | 2.672 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
29 | SMSTORE2_WALL_1_WINDOW_2 | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.47_SHGC_0.4 | N/A | 2.672 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
30 | SMSTORE2_WALL_1_DOOR | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.47_SHGC_0.4 | N/A | 2.672 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
31 | SMSTORE2_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
32 | SMSTORE2_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.514 | 0.477 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | SMSTORE2_WALL_3_DOOR | Door | SMSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
34 | SMSTORE2_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE3_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | SMSTORE2_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE2_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
36 | SMSTORE2_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
37 | SMSTORE2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
38 | SMSTORE3_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.514 | 0.477 | 29.12 | 39.47 | 29.12 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
39 | SMSTORE3_WALL_1_WINDOW_1 | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.47_SHGC_0.4 | N/A | 2.672 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
40 | SMSTORE3_WALL_1_WINDOW_2 | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.47_SHGC_0.4 | N/A | 2.672 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
41 | SMSTORE3_WALL_1_DOOR | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.47_SHGC_0.4 | N/A | 2.672 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
42 | SMSTORE3_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE2_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | SMSTORE3_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.514 | 0.477 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | SMSTORE3_WALL_3_DOOR | Door | SMSTORE3_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
45 | SMSTORE3_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE4_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | SMSTORE3_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE3_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
47 | SMSTORE3_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
48 | SMSTORE3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
49 | SMSTORE4_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.514 | 0.477 | 29.12 | 39.47 | 29.12 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | SMSTORE4_WALL_1_WINDOW_1 | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.47_SHGC_0.4 | N/A | 2.672 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
51 | SMSTORE4_WALL_1_WINDOW_2 | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.47_SHGC_0.4 | N/A | 2.672 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
52 | SMSTORE4_WALL_1_DOOR | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.47_SHGC_0.4 | N/A | 2.672 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | SMSTORE4_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE3_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | SMSTORE4_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.514 | 0.477 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | SMSTORE4_WALL_3_DOOR | Door | SMSTORE4_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | SMSTORE4_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE2_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | SMSTORE4_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE4_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | SMSTORE4_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | SMSTORE4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | LGSTORE2_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE4_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | LGSTORE2_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.514 | 0.477 | 71.19 | 78.94 | 71.19 | 0.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
62 | LGSTORE2_WALL_3_DOOR_1 | Door | LGSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
63 | LGSTORE2_WALL_3_DOOR_2 | Door | LGSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
64 | LGSTORE2_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE5_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | LGSTORE2_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.514 | 0.477 | 58.24 | 78.94 | 58.24 | 180.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
66 | LGSTORE2_WALL_1_WINDOW_1 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.47_SHGC_0.4 | N/A | 2.672 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | LGSTORE2_WALL_1_WINDOW_2 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.47_SHGC_0.4 | N/A | 2.672 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | LGSTORE2_WALL_1_WINDOW_3 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.47_SHGC_0.4 | N/A | 2.672 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | LGSTORE2_WALL_1_WINDOW_4 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.47_SHGC_0.4 | N/A | 2.672 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | LGSTORE2_WALL_1_DOOR_1 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.47_SHGC_0.4 | N/A | 2.672 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
71 | LGSTORE2_WALL_1_DOOR_2 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.47_SHGC_0.4 | N/A | 2.672 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
72 | LGSTORE2_FLOOR | Floor | CTF - ConductionTransferFunction | LGSTORE2_FLOOR_FFACTOR | 0.112 | 0.109 | 348.39 | 348.39 | 348.39 | 270.00 | 180.00 | 22.86 | 15.24 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
73 | LGSTORE2_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 348.39 | 348.39 | 348.39 | 270.00 | 0.00 | 22.86 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
74 | LGSTORE2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 696.77 | 696.77 | 696.77 | 0.00 | 90.00 | 696.77 | 1.00 | 0.00 | LGSTORE2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
75 | SMSTORE5_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.514 | 0.477 | 29.12 | 39.47 | 29.12 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | SMSTORE5_WALL_1_WINDOW_1 | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.47_SHGC_0.4 | N/A | 2.672 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
77 | SMSTORE5_WALL_1_WINDOW_2 | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.47_SHGC_0.4 | N/A | 2.672 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | SMSTORE5_WALL_1_DOOR | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.47_SHGC_0.4 | N/A | 2.672 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
79 | SMSTORE5_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE2_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | SMSTORE5_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.514 | 0.477 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | SMSTORE5_WALL_3_DOOR | Door | SMSTORE5_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
82 | SMSTORE5_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE6_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
83 | SMSTORE5_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE5_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
84 | SMSTORE5_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
85 | SMSTORE5_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE5_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
86 | SMSTORE6_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.514 | 0.477 | 29.12 | 39.47 | 29.12 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | SMSTORE6_WALL_1_WINDOW_1 | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.47_SHGC_0.4 | N/A | 2.672 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
88 | SMSTORE6_WALL_1_WINDOW_2 | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.47_SHGC_0.4 | N/A | 2.672 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
89 | SMSTORE6_WALL_1_DOOR | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.47_SHGC_0.4 | N/A | 2.672 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
90 | SMSTORE6_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE5_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
91 | SMSTORE6_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.514 | 0.477 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
92 | SMSTORE6_WALL_3_DOOR | Door | SMSTORE6_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
93 | SMSTORE6_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE7_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | SMSTORE6_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE6_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
95 | SMSTORE6_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
96 | SMSTORE6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
97 | SMSTORE7_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.514 | 0.477 | 29.12 | 39.47 | 29.12 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | SMSTORE7_WALL_1_WINDOW_1 | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.47_SHGC_0.4 | N/A | 2.672 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
99 | SMSTORE7_WALL_1_WINDOW_2 | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.47_SHGC_0.4 | N/A | 2.672 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
100 | SMSTORE7_WALL_1_DOOR | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.47_SHGC_0.4 | N/A | 2.672 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
101 | SMSTORE7_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE6_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
102 | SMSTORE7_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.514 | 0.477 | 35.59 | 39.47 | 35.59 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | SMSTORE7_WALL_3_DOOR | Door | SMSTORE7_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
104 | SMSTORE7_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE8_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | SMSTORE7_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE7_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
106 | SMSTORE7_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
107 | SMSTORE7_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE7_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
108 | SMSTORE8_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.514 | 0.477 | 29.12 | 39.47 | 29.12 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | SMSTORE8_WALL_1_WINDOW_1 | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.47_SHGC_0.4 | N/A | 2.672 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
110 | SMSTORE8_WALL_1_WINDOW_2 | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.47_SHGC_0.4 | N/A | 2.672 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
111 | SMSTORE8_WALL_1_DOOR | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.47_SHGC_0.4 | N/A | 2.672 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
112 | SMSTORE8_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE7_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
113 | SMSTORE8_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.514 | 0.477 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | SMSTORE8_WALL_3_DOOR | Door | SMSTORE8_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
115 | SMSTORE8_WALL_4 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.514 | 0.477 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | SMSTORE8_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE8_FLOOR_FFACTOR | 0.289 | 0.270 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | SMSTORE8_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | SMSTORE8_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE8_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1 |
2 | VETERANS DAY | Holiday | InputFile | 11/11 | 1 |
3 | CHRISTMAS | Holiday | InputFile | 12/25 | 1 |
4 | INDEPENDENCE DAY | Holiday | InputFile | 07/04 | 1 |
5 | MLK DAY | Holiday | InputFile | 01/16 | 1 |
6 | PRESIDENTS DAY | Holiday | InputFile | 02/20 | 1 |
7 | MEMORIAL DAY | Holiday | InputFile | 05/29 | 1 |
8 | LABOR DAY | Holiday | InputFile | 09/04 | 1 |
9 | COLUMBUS DAY | Holiday | InputFile | 10/09 | 1 |
10 | THANKSGIVING | Holiday | InputFile | 11/23 | 1 |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
NumberofWarmupDays | |
1 | 9 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | LGSTORE1 | RunPeriod: RUNPERIOD 1 | 5.3875720239E-002 | 0.3041251562 | Pass | Pass | 0.4002839224 | 4.1388809578 | Pass | Pass |
2 | SMSTORE1 | RunPeriod: RUNPERIOD 1 | 5.6181624186E-002 | 0.2322820240 | Pass | Pass | 4.7489111017E-002 | 0.1364033701 | Pass | Pass |
3 | SMSTORE2 | RunPeriod: RUNPERIOD 1 | 6.7483104327E-002 | 0.3397884480 | Pass | Pass | 3.0799125335E-002 | 0.1027241051 | Pass | Pass |
4 | SMSTORE3 | RunPeriod: RUNPERIOD 1 | 7.5845459053E-002 | 0.3776686255 | Pass | Pass | 2.9551292688E-002 | 0.1008828237 | Pass | Pass |
5 | SMSTORE4 | RunPeriod: RUNPERIOD 1 | 8.0320493962E-002 | 0.4005150937 | Pass | Pass | 2.8578531684E-002 | 9.8860374276E-002 | Pass | Pass |
6 | LGSTORE2 | RunPeriod: RUNPERIOD 1 | 9.3054241883E-002 | 0.4259414069 | Pass | Pass | 3.2418464207E-002 | 0.1359465348 | Pass | Pass |
7 | SMSTORE5 | RunPeriod: RUNPERIOD 1 | 9.1395374675E-002 | 0.4068696385 | Pass | Pass | 3.9395501533E-002 | 0.1858971799 | Pass | Pass |
8 | SMSTORE6 | RunPeriod: RUNPERIOD 1 | 9.1909603225E-002 | 0.4068297532 | Pass | Pass | 3.8295304964E-002 | 0.1754541521 | Pass | Pass |
9 | SMSTORE7 | RunPeriod: RUNPERIOD 1 | 9.9176089911E-002 | 0.4116679190 | Pass | Pass | 7.2285594714E-002 | 0.3203759463 | Pass | Pass |
10 | SMSTORE8 | RunPeriod: RUNPERIOD 1 | 0.2116999404 | 0.4520367000 | Pass | Pass | 1.6912980160 | 6.7224475594 | Pass | Pass |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2020-06-03 19:19:07
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | -26.20 | 0.00 | -26.20 | Wetbulb [C] | 5.70 | 310.00 |
ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 31.20 | 10.60 | 23.10 | Wetbulb [C] | 6.70 | 200.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2020-06-03 19:19:07
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_2 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE1_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 78.94 | 71.15 | 0.00 | 90.00 | N |
LGSTORE1_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 78.94 | 58.20 | 180.00 | 90.00 | S |
LGSTORE1_ROOF | NONRES_ROOF | 0.23 | 0.273 | 0.283 | 348.39 | 348.39 | 270.00 | 0.00 | |
SMSTORE1_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 39.47 | 29.10 | 180.00 | 90.00 | S |
SMSTORE1_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 39.47 | 35.57 | 0.00 | 90.00 | N |
SMSTORE1_ROOF | NONRES_ROOF | 0.23 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE2_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 39.47 | 29.12 | 180.00 | 90.00 | S |
SMSTORE2_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE2_ROOF | NONRES_ROOF | 0.23 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE3_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 39.47 | 29.12 | 180.00 | 90.00 | S |
SMSTORE3_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE3_ROOF | NONRES_ROOF | 0.23 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE4_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 39.47 | 29.12 | 180.00 | 90.00 | S |
SMSTORE4_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE4_ROOF | NONRES_ROOF | 0.23 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
LGSTORE2_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 78.94 | 71.19 | 0.00 | 90.00 | N |
LGSTORE2_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 78.94 | 58.24 | 180.00 | 90.00 | S |
LGSTORE2_ROOF | NONRES_ROOF | 0.23 | 0.273 | 0.283 | 348.39 | 348.39 | 270.00 | 0.00 | |
SMSTORE5_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 39.47 | 29.12 | 180.00 | 90.00 | S |
SMSTORE5_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE5_ROOF | NONRES_ROOF | 0.23 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE6_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 39.47 | 29.12 | 180.00 | 90.00 | S |
SMSTORE6_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE6_ROOF | NONRES_ROOF | 0.23 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE7_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 39.47 | 29.12 | 180.00 | 90.00 | S |
SMSTORE7_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE7_ROOF | NONRES_ROOF | 0.23 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE8_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 39.47 | 29.12 | 180.00 | 90.00 | S |
SMSTORE8_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE8_WALL_4 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE8_ROOF | NONRES_ROOF | 0.23 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
LGSTORE1_FLOOR | LGSTORE1_FLOOR_FFACTOR | 1.00 | 0.199 | 348.39 | 348.39 | 270.00 | 180.00 | ||
SMSTORE1_FLOOR | SMSTORE1_FLOOR_FFACTOR | 1.00 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | ||
SMSTORE2_FLOOR | SMSTORE2_FLOOR_FFACTOR | 1.00 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | ||
SMSTORE3_FLOOR | SMSTORE3_FLOOR_FFACTOR | 1.00 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | ||
SMSTORE4_FLOOR | SMSTORE4_FLOOR_FFACTOR | 1.00 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | ||
LGSTORE2_FLOOR | LGSTORE2_FLOOR_FFACTOR | 1.00 | 0.112 | 348.39 | 348.39 | 270.00 | 180.00 | ||
SMSTORE5_FLOOR | SMSTORE5_FLOOR_FFACTOR | 1.00 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | ||
SMSTORE6_FLOOR | SMSTORE6_FLOOR_FFACTOR | 1.00 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | ||
SMSTORE7_FLOOR | SMSTORE7_FLOOR_FFACTOR | 1.00 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | ||
SMSTORE8_FLOOR | SMSTORE8_FLOOR_FFACTOR | 1.00 | 0.289 | 174.19 | 174.19 | 270.00 | 180.00 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.47_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.672 | 0.394 | 0.401 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE1_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.47_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.672 | 0.394 | 0.401 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE1_WALL_1_WINDOW_3 | NONRESWINDOW_U_0.47_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.672 | 0.394 | 0.401 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE1_WALL_1_WINDOW_4 | NONRESWINDOW_U_0.47_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.672 | 0.394 | 0.401 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE1_WALL_1_DOOR_1 | NONRESWINDOW_U_0.47_SHGC_0.4 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.672 | 0.394 | 0.401 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE1_WALL_1_DOOR_2 | NONRESWINDOW_U_0.47_SHGC_0.4 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.672 | 0.394 | 0.401 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE1_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.47_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.672 | 0.394 | 0.401 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE1_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.47_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.672 | 0.394 | 0.401 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE1_WALL_1_DOOR | NONRESWINDOW_U_0.47_SHGC_0.4 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.672 | 0.394 | 0.401 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE2_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.47_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.672 | 0.394 | 0.401 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE2_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.47_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.672 | 0.394 | 0.401 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE2_WALL_1_DOOR | NONRESWINDOW_U_0.47_SHGC_0.4 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.672 | 0.394 | 0.401 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE3_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.47_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.672 | 0.394 | 0.401 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE3_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.47_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.672 | 0.394 | 0.401 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE3_WALL_1_DOOR | NONRESWINDOW_U_0.47_SHGC_0.4 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.672 | 0.394 | 0.401 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE4_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.47_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.672 | 0.394 | 0.401 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE4_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.47_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.672 | 0.394 | 0.401 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE4_WALL_1_DOOR | NONRESWINDOW_U_0.47_SHGC_0.4 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.672 | 0.394 | 0.401 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE2_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.47_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.672 | 0.394 | 0.401 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE2_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.47_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.672 | 0.394 | 0.401 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE2_WALL_1_WINDOW_3 | NONRESWINDOW_U_0.47_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.672 | 0.394 | 0.401 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE2_WALL_1_WINDOW_4 | NONRESWINDOW_U_0.47_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.672 | 0.394 | 0.401 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE2_WALL_1_DOOR_1 | NONRESWINDOW_U_0.47_SHGC_0.4 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.672 | 0.394 | 0.401 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE2_WALL_1_DOOR_2 | NONRESWINDOW_U_0.47_SHGC_0.4 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.672 | 0.394 | 0.401 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE5_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.47_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.672 | 0.394 | 0.401 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE5_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.47_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.672 | 0.394 | 0.401 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE5_WALL_1_DOOR | NONRESWINDOW_U_0.47_SHGC_0.4 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.672 | 0.394 | 0.401 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE6_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.47_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.672 | 0.394 | 0.401 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE6_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.47_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.672 | 0.394 | 0.401 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE6_WALL_1_DOOR | NONRESWINDOW_U_0.47_SHGC_0.4 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.672 | 0.394 | 0.401 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE7_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.47_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.672 | 0.394 | 0.401 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE7_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.47_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.672 | 0.394 | 0.401 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE7_WALL_1_DOOR | NONRESWINDOW_U_0.47_SHGC_0.4 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.672 | 0.394 | 0.401 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE8_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.47_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.672 | 0.394 | 0.401 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE8_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.47_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.672 | 0.394 | 0.401 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE8_WALL_1_DOOR | NONRESWINDOW_U_0.47_SHGC_0.4 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.672 | 0.394 | 0.401 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | ||
Total or Average | 124.29 | 2.672 | 0.394 | 0.401 | ||||||||||||
North Total or Average | 0.00 | - | - | - | ||||||||||||
Non-North Total or Average | 124.29 | 2.672 | 0.394 | 0.401 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
LGSTORE1_WALL_3_DOOR_1 | SWINGING DOOR_CON | 2.492 | 3.975 | 3.90 | LGSTORE1_WALL_3 |
LGSTORE1_WALL_3_DOOR_2 | SWINGING DOOR_CON | 2.492 | 3.975 | 3.90 | LGSTORE1_WALL_3 |
SMSTORE1_WALL_3_DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 3.90 | SMSTORE1_WALL_3 |
SMSTORE2_WALL_3_DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 3.88 | SMSTORE2_WALL_3 |
SMSTORE3_WALL_3_DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 3.88 | SMSTORE3_WALL_3 |
SMSTORE4_WALL_3_DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 3.88 | SMSTORE4_WALL_3 |
LGSTORE2_WALL_3_DOOR_1 | SWINGING DOOR_CON | 2.492 | 3.975 | 3.88 | LGSTORE2_WALL_3 |
LGSTORE2_WALL_3_DOOR_2 | SWINGING DOOR_CON | 2.492 | 3.975 | 3.88 | LGSTORE2_WALL_3 |
SMSTORE5_WALL_3_DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 3.88 | SMSTORE5_WALL_3 |
SMSTORE6_WALL_3_DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 3.88 | SMSTORE6_WALL_3 |
SMSTORE7_WALL_3_DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 3.88 | SMSTORE7_WALL_3 |
SMSTORE8_WALL_3_DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 3.88 | SMSTORE8_WALL_3 |
Report: Shading Summary
For: Entire Facility
Timestamp: 2020-06-03 19:19:07
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
LGSTORE1_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_DOOR_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_DOOR_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_DOOR_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_DOOR_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2020-06-03 19:19:07
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
LGSTORE1_LIGHTS | LGSTORE1 | 18.3225 | 348.39 | 6383.30 | LightsWired | TYPE1_LIGHT_SCH | 98.40 | 168.00 | 98.38 | 0.0000 | Y | 117.88 |
LGSTORE1_LIGHTS_ALLOWANCE | LGSTORE1 | 10.4948 | 348.39 | 3656.25 | LightsWired | TYPE1_LIGHT_SCH | 98.40 | 168.00 | 98.38 | 0.0000 | Y | 67.52 |
SMSTORE1_LIGHTS | SMSTORE1 | 18.3225 | 174.19 | 3191.65 | LightsWired | TYPE1_LIGHT_SCH | 98.40 | 168.00 | 98.38 | 0.0000 | Y | 58.94 |
SMSTORE1_LIGHTS_ALLOWANCE | SMSTORE1 | 10.4948 | 174.19 | 1828.13 | LightsWired | TYPE1_LIGHT_SCH | 98.40 | 168.00 | 98.38 | 0.0000 | Y | 33.76 |
SMSTORE2_LIGHTS | SMSTORE2 | 18.3225 | 174.19 | 3191.65 | LightsWired | TYPE2_LIGHT_SCH | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 46.71 |
SMSTORE2_LIGHTS_ALLOWANCE | SMSTORE2 | 4.3056 | 174.19 | 750.00 | LightsWired | TYPE2_LIGHT_SCH | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 10.98 |
SMSTORE3_LIGHTS | SMSTORE3 | 18.3225 | 174.19 | 3191.65 | LightsWired | TYPE2_LIGHT_SCH | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 46.71 |
SMSTORE3_LIGHTS_ALLOWANCE | SMSTORE3 | 4.3056 | 174.19 | 750.00 | LightsWired | TYPE2_LIGHT_SCH | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 10.98 |
SMSTORE4_LIGHTS | SMSTORE4 | 18.3225 | 174.19 | 3191.65 | LightsWired | TYPE2_LIGHT_SCH | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 46.71 |
SMSTORE4_LIGHTS_ALLOWANCE | SMSTORE4 | 4.3056 | 174.19 | 750.00 | LightsWired | TYPE2_LIGHT_SCH | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 10.98 |
LGSTORE2_LIGHTS | LGSTORE2 | 18.3225 | 348.39 | 6383.30 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 168.00 | 71.66 | 0.0000 | Y | 85.86 |
LGSTORE2_LIGHTS_ALLOWANCE | LGSTORE2 | 0.0000 | 348.39 | 0.00 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE5_LIGHTS | SMSTORE5 | 18.3225 | 174.19 | 3191.65 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 168.00 | 71.66 | 0.0000 | Y | 42.93 |
SMSTORE5_LIGHTS_ALLOWANCE | SMSTORE5 | 0.0000 | 174.19 | 0.00 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE6_LIGHTS | SMSTORE6 | 18.3225 | 174.19 | 3191.65 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 168.00 | 71.66 | 0.0000 | Y | 42.93 |
SMSTORE6_LIGHTS_ALLOWANCE | SMSTORE6 | 0.0000 | 174.19 | 0.00 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE7_LIGHTS | SMSTORE7 | 18.3225 | 174.19 | 3191.65 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 168.00 | 71.66 | 0.0000 | Y | 42.93 |
SMSTORE7_LIGHTS_ALLOWANCE | SMSTORE7 | 0.0000 | 174.19 | 0.00 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE8_LIGHTS | SMSTORE8 | 18.3225 | 174.19 | 3191.65 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 168.00 | 71.66 | 0.0000 | Y | 42.93 |
SMSTORE8_LIGHTS_ALLOWANCE | SMSTORE8 | 0.0000 | 174.19 | 0.00 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
Interior Lighting Total | 11.0113 | 4180.64 | 46034.15 | 708.74 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS | 10625.34 | AstronomicalClock | - | 83.63 | 83.63 | 166.80 | |
Exterior Lighting Total | 10625.34 | 166.80 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2020-06-03 19:19:07
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 55675.07 | 38695.84 | 16979.23 | 0.70 | 3.30 | |||
PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 28121.66 | 19588.99 | 8532.67 | 0.70 | 3.50 | |||
PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 28777.58 | 19921.86 | 8855.72 | 0.69 | 3.50 | |||
PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 28872.37 | 19980.83 | 8891.54 | 0.69 | 3.50 | |||
PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 29073.49 | 20111.59 | 8961.90 | 0.69 | 3.50 | |||
PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 54697.68 | 37611.22 | 17086.46 | 0.69 | 3.30 | |||
PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 29902.46 | 20580.97 | 9321.49 | 0.69 | 3.50 | |||
PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 29937.35 | 20589.41 | 9347.94 | 0.69 | 3.50 | |||
PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 30273.99 | 20802.47 | 9471.52 | 0.69 | 3.50 | |||
PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 34353.96 | 23627.28 | 10726.68 | 0.69 | 3.50 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | 53772.3 | 9.98 | ||||
PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | 27155.0 | 31.30 | ||||
PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | 27804.1 | 41.15 | ||||
PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | 27896.6 | 51.55 | ||||
PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | 28092.0 | 61.72 | ||||
PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | 52879.8 | 41.19 | ||||
PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | 28906.2 | 89.91 | ||||
PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | 28941.9 | 100.36 | ||||
PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | 29269.7 | 109.82 | ||||
PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | 33211.6 | 107.30 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
PSZ-AC_1:1_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 81662.66 | 0.79 | |
PSZ-AC_2:2_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 41257.18 | 0.80 | |
PSZ-AC_3:3_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 41437.20 | 0.80 | |
PSZ-AC_4:4_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 41502.31 | 0.80 | |
PSZ-AC_5:5_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 41660.15 | 0.80 | |
PSZ-AC_6:6_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 79286.24 | 0.79 | |
PSZ-AC_7:7_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 42061.63 | 0.80 | |
PSZ-AC_8:8_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 42037.50 | 0.80 | |
PSZ-AC_9:9_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 42281.06 | 0.80 | |
PSZ-AC_10:10_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 46104.04 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.57 | 622.50 | 2.42 | 2643.58 | 1094.51 | 1.00 | 1.26 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 |
PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.55 | 622.50 | 1.23 | 1399.10 | 1140.11 | 1.00 | 1.32 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 |
PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.55 | 622.50 | 1.24 | 1408.51 | 1140.11 | 1.00 | 1.31 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 |
PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.55 | 622.50 | 1.24 | 1411.92 | 1140.11 | 1.00 | 1.31 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 |
PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.55 | 622.50 | 1.25 | 1420.17 | 1140.11 | 1.00 | 1.31 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 |
PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.57 | 622.50 | 2.31 | 2524.36 | 1094.51 | 1.00 | 1.27 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 |
PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.55 | 622.50 | 1.26 | 1441.16 | 1140.11 | 1.00 | 1.31 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 |
PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.55 | 622.50 | 1.26 | 1439.90 | 1140.11 | 1.00 | 1.31 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 |
PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.55 | 622.50 | 1.27 | 1452.63 | 1140.11 | 1.00 | 1.31 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 |
PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.57 | 622.50 | 1.45 | 1586.33 | 1094.51 | 1.00 | 1.34 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
GAS TANK1 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK2 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK3 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK4 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK5 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK6 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK7 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:19:07
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
LGSTORE1 | 24756.47 | 29707.76 | 85.27 | 1.905 | 2.286 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 23.89 | 23.88 | 0.00990 | 31.20 | 0.01534 | 0.531 | 0.00 |
SMSTORE1 | 12972.24 | 15566.69 | 89.36 | 0.998 | 1.198 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 23.89 | 23.88 | 0.00993 | 31.11 | 0.01534 | 0.265 | 0.00 |
SMSTORE2 | 12242.53 | 14691.03 | 84.34 | 0.942 | 1.131 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 23.89 | 23.88 | 0.01000 | 31.11 | 0.01534 | 0.265 | 0.00 |
SMSTORE3 | 12205.28 | 14646.33 | 84.08 | 0.939 | 1.127 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 23.89 | 23.88 | 0.01001 | 31.11 | 0.01534 | 0.265 | 0.00 |
SMSTORE4 | 12157.65 | 14589.18 | 83.75 | 0.936 | 1.123 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 23.89 | 23.88 | 0.01001 | 31.11 | 0.01534 | 0.265 | 0.00 |
LGSTORE2 | 22272.33 | 26726.79 | 76.72 | 1.714 | 2.057 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 23.89 | 23.88 | 0.00999 | 31.02 | 0.01534 | 0.531 | 0.00 |
SMSTORE5 | 11603.86 | 13924.63 | 79.94 | 0.893 | 1.072 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 23.89 | 23.88 | 0.01007 | 31.02 | 0.01534 | 0.265 | 0.00 |
SMSTORE6 | 11521.81 | 13826.17 | 79.37 | 0.887 | 1.064 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 23.89 | 23.88 | 0.01008 | 31.02 | 0.01534 | 0.265 | 0.00 |
SMSTORE7 | 11427.55 | 13713.06 | 78.72 | 0.879 | 1.055 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 23.89 | 23.88 | 0.01009 | 31.02 | 0.01534 | 0.265 | 0.00 |
SMSTORE8 | 11634.07 | 13960.89 | 80.15 | 0.895 | 1.074 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | 23.89 | 23.88 | 0.01011 | 30.67 | 0.01534 | 0.265 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
LGSTORE1 | 44547.57 | 53457.08 | 153.44 | 2.013 | 2.415 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00650 | -26.20 | 0.00036 | 0.531 | 0.00 |
SMSTORE1 | 22634.00 | 27160.80 | 155.92 | 1.023 | 1.227 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00640 | -26.20 | 0.00036 | 0.265 | 0.00 |
SMSTORE2 | 22786.23 | 27343.48 | 156.97 | 1.030 | 1.235 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00640 | -26.20 | 0.00036 | 0.265 | 0.00 |
SMSTORE3 | 22841.29 | 27409.55 | 157.35 | 1.032 | 1.238 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00641 | -26.20 | 0.00036 | 0.265 | 0.00 |
SMSTORE4 | 22974.77 | 27569.72 | 158.27 | 1.038 | 1.246 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00641 | -26.20 | 0.00036 | 0.265 | 0.00 |
LGSTORE2 | 42537.74 | 51045.28 | 146.52 | 1.922 | 2.306 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00648 | -26.20 | 0.00036 | 0.531 | 0.00 |
SMSTORE5 | 23314.27 | 27977.12 | 160.61 | 1.053 | 1.264 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00643 | -26.20 | 0.00036 | 0.265 | 0.00 |
SMSTORE6 | 23293.85 | 27952.63 | 160.47 | 1.052 | 1.263 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00643 | -26.20 | 0.00036 | 0.265 | 0.00 |
SMSTORE7 | 23499.82 | 28199.78 | 161.89 | 1.062 | 1.274 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00644 | -26.20 | 0.00036 | 0.265 | 0.00 |
SMSTORE8 | 26732.89 | 32079.46 | 184.16 | 1.208 | 1.449 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00653 | -26.20 | 0.00036 | 0.265 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC_1:1 | 2.29 | 2.29 | 2.42 | 2.42 | 2.4153 | 2.4153 | 2.4153 | 1.0000 | 1.0000 |
PSZ-AC_2:2 | 1.20 | 1.20 | 1.23 | 1.23 | 1.2272 | 1.2272 | 1.2272 | 1.0000 | 1.0000 |
PSZ-AC_3:3 | 1.13 | 1.13 | 1.24 | 1.24 | 1.2354 | 1.2354 | 1.2354 | 1.0000 | 1.0000 |
PSZ-AC_4:4 | 1.13 | 1.13 | 1.24 | 1.24 | 1.2384 | 1.2384 | 1.2384 | 1.0000 | 1.0000 |
PSZ-AC_5:5 | 1.12 | 1.12 | 1.25 | 1.25 | 1.2456 | 1.2456 | 1.2456 | 1.0000 | 1.0000 |
PSZ-AC_6:6 | 2.06 | 2.06 | 2.31 | 2.31 | 2.3064 | 2.3064 | 2.3064 | 1.0000 | 1.0000 |
PSZ-AC_7:7 | 1.07 | 1.07 | 1.26 | 1.26 | 1.2641 | 1.2641 | 1.2641 | 1.0000 | 1.0000 |
PSZ-AC_8:8 | 1.06 | 1.06 | 1.26 | 1.26 | 1.2629 | 1.2629 | 1.2629 | 1.0000 | 1.0000 |
PSZ-AC_9:9 | 1.06 | 1.06 | 1.27 | 1.27 | 1.2741 | 1.2741 | 1.2741 | 1.0000 | 1.0000 |
PSZ-AC_10:10 | 1.07 | 1.07 | 1.45 | 1.45 | 1.4494 | 1.4494 | 1.4494 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_1:1 | 55675.070 | 0.000 | 2.415320 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 55675.07 | 38338.41 | 2.415320 | 25.58 | 18.56 | 0.01116165 | 12.80 | 11.67 | 0.00850000 | 31.20 | 0.01534436 | 23.10 | 21.9808 | 23.88 | 0.00989668 | 51.0567 | 24756.47 | 0.00 | -999.00 | -999.00 |
PSZ-AC_1:1_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_1:1 | 81662.665 | 81662.665 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 81662.66 | 81662.66 | 2.415321 | 10.71 | 7.17 | 0.00515328 | 40.00 | 20.60 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 21.9808 | 21.10 | 0.00650334 | 39.9525 | 44547.57 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_2:2 | 28121.660 | 0.000 | 1.227170 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 28121.66 | 19397.59 | 1.227170 | 25.51 | 18.52 | 0.01113339 | 12.80 | 11.67 | 0.00850000 | 31.20 | 0.01534436 | 23.10 | 21.6314 | 23.88 | 0.00993391 | 51.2462 | 12970.09 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_2:2 | 41257.181 | 41257.181 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 41257.18 | 41257.18 | 1.227166 | 10.87 | 7.17 | 0.00509007 | 40.00 | 20.60 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 21.6315 | 21.10 | 0.00639530 | 39.2972 | 22634.00 | 0.00 | -999.00 | -999.00 |
PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_3:3 | 28777.580 | 0.000 | 1.235420 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 28777.58 | 19603.27 | 1.235420 | 25.60 | 18.64 | 0.01125821 | 12.80 | 11.67 | 0.00850000 | 31.20 | 0.01534436 | 23.10 | 21.4869 | 23.88 | 0.01000315 | 51.5977 | 12238.95 | 0.00 | -999.00 | -999.00 |
PSZ-AC_3:3_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_3:3 | 41437.198 | 41437.198 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 41437.20 | 41437.20 | 1.235420 | 10.94 | 7.22 | 0.00510521 | 40.00 | 20.60 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 21.4869 | 21.10 | 0.00640348 | 39.3469 | 22786.23 | 0.00 | -999.00 | -999.00 |
PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_4:4 | 28872.370 | 0.000 | 1.238410 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 28872.37 | 19654.76 | 1.238410 | 25.61 | 18.65 | 0.01126494 | 12.80 | 11.67 | 0.00850000 | 31.20 | 0.01534436 | 23.10 | 21.4351 | 23.88 | 0.01000687 | 51.6166 | 12201.37 | 0.00 | -999.00 | -999.00 |
PSZ-AC_4:4_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_4:4 | 41502.311 | 41502.311 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 41502.31 | 41502.31 | 1.238406 | 10.96 | 7.24 | 0.00511065 | 40.00 | 20.60 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 21.4351 | 21.10 | 0.00640642 | 39.3648 | 22841.29 | 0.00 | -999.00 | -999.00 |
PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_5:5 | 29073.490 | 0.000 | 1.245640 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 29073.49 | 19774.94 | 1.245640 | 25.61 | 18.66 | 0.01127353 | 12.80 | 11.67 | 0.00850000 | 31.20 | 0.01534436 | 23.10 | 21.3106 | 23.88 | 0.01001165 | 51.6408 | 12153.70 | 0.00 | -999.00 | -999.00 |
PSZ-AC_5:5_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_5:5 | 41660.153 | 41660.153 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 41660.15 | 41660.15 | 1.245643 | 11.02 | 7.28 | 0.00512372 | 40.00 | 20.60 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 21.3106 | 21.10 | 0.00641346 | 39.4076 | 22974.77 | 0.00 | -999.00 | -999.00 |
PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_6:6 | 54697.680 | 0.000 | 2.306400 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 54697.68 | 36901.82 | 2.306400 | 25.77 | 18.79 | 0.01137496 | 12.80 | 11.67 | 0.00850000 | 31.20 | 0.01534436 | 23.10 | 23.0189 | 23.88 | 0.00998955 | 51.5276 | 22259.03 | 0.00 | -999.00 | -999.00 |
PSZ-AC_6:6_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_6:6 | 79286.237 | 79286.237 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 79286.24 | 79286.24 | 2.306397 | 10.21 | 6.84 | 0.00507466 | 40.00 | 20.60 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 23.0189 | 21.10 | 0.00648404 | 39.8343 | 42537.74 | 0.00 | -999.00 | -999.00 |
PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_7:7 | 29902.460 | 0.000 | 1.264050 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 29902.46 | 20133.49 | 1.264050 | 25.70 | 18.76 | 0.01137793 | 12.80 | 11.67 | 0.00850000 | 31.20 | 0.01534436 | 23.10 | 21.0003 | 23.88 | 0.01006768 | 51.9251 | 11596.96 | 0.00 | -999.00 | -999.00 |
PSZ-AC_7:7_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_7:7 | 42061.634 | 42061.634 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 42061.63 | 42061.63 | 1.264054 | 11.17 | 7.39 | 0.00515631 | 40.00 | 20.60 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 21.0002 | 21.10 | 0.00643093 | 39.5138 | 23314.27 | 0.00 | -999.00 | -999.00 |
PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_8:8 | 29937.350 | 0.000 | 1.262950 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 29937.35 | 20126.15 | 1.262950 | 25.71 | 18.78 | 0.01139391 | 12.80 | 11.67 | 0.00850000 | 31.20 | 0.01534436 | 23.10 | 21.0186 | 23.88 | 0.01007659 | 51.9704 | 11515.19 | 0.00 | -999.00 | -999.00 |
PSZ-AC_8:8_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_8:8 | 42037.497 | 42037.497 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 42037.50 | 42037.50 | 1.262947 | 11.16 | 7.38 | 0.00515435 | 40.00 | 20.60 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 21.0186 | 21.10 | 0.00642987 | 39.5074 | 23293.85 | 0.00 | -999.00 | -999.00 |
PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_9:9 | 30273.990 | 0.000 | 1.274110 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 30273.99 | 20316.28 | 1.274110 | 25.73 | 18.80 | 0.01141257 | 12.80 | 11.67 | 0.00850000 | 31.20 | 0.01534436 | 23.10 | 20.8345 | 23.88 | 0.01008696 | 52.0229 | 11420.90 | 0.00 | -999.00 | -999.00 |
PSZ-AC_9:9_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_9:9 | 42281.057 | 42281.057 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 42281.06 | 42281.06 | 1.274115 | 11.25 | 7.44 | 0.00517389 | 40.00 | 20.60 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 20.8344 | 21.10 | 0.00644043 | 39.5716 | 23499.82 | 0.00 | -999.00 | -999.00 |
PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_10:10 | 34353.960 | 0.000 | 1.449360 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | 34353.96 | 22988.91 | 1.449360 | 25.66 | 18.79 | 0.01142425 | 12.80 | 11.67 | 0.00850000 | 31.02 | 0.01534436 | 23.05 | 18.3152 | 23.88 | 0.01011371 | 52.1588 | 11577.79 | 0.00 | -999.00 | -999.00 |
PSZ-AC_10:10_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_10:10 | 46104.044 | 46104.044 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 46104.04 | 46104.04 | 1.449359 | 12.44 | 8.25 | 0.00540391 | 40.00 | 20.60 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 18.3153 | 21.10 | 0.00653455 | 40.1453 | 26732.89 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2020-06-03 19:19:07
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | LGSTORE1 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 55675.070 | 0.000 | 2.415320 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1025.5890 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 55675.07 | 38338.41 | 1.0000 | 2.77412986 | 2.415320 | 25.58 | 18.56 | 0.01116165 | 54152.1 | 12.80 | 11.67 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 55675.07 | 31.20 | 0.01534436 | 23.10 | 0.53090778 | 21.9808 | 23.88 | 0.00989668 | 23.88 | 0.00989668 | 51.0567 | 24756.47 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_1:1_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | LGSTORE1 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 81662.665 | 81662.665 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.415321 | 2.77413080 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 81662.66 | 81662.66 | 1.0000 | 2.77413080 | 2.415321 | 10.71 | 7.17 | 0.00515328 | 23747.5 | 40.00 | 20.60 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 81662.66 | -26.20 | 0.00036134 | -26.20 | 0.53090778 | 21.9808 | 21.10 | 0.00650334 | 21.10 | 0.00650334 | 39.9525 | 44547.57 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | SMSTORE1 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 28121.660 | 0.000 | 1.227170 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1025.5364 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 28121.66 | 19397.59 | 1.0000 | 1.40947326 | 1.227170 | 25.51 | 18.52 | 0.01113339 | 54000.4 | 12.80 | 11.67 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 28121.66 | 31.20 | 0.01534436 | 23.10 | 0.26545389 | 21.6314 | 23.88 | 0.00993454 | 23.88 | 0.00993391 | 51.2462 | 12970.09 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | SMSTORE1 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 41257.181 | 41257.181 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.227166 | 1.40946896 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 41257.18 | 41257.18 | 1.0000 | 1.40946896 | 1.227166 | 10.87 | 7.17 | 0.00509007 | 23755.5 | 40.00 | 20.60 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 41257.18 | -26.20 | 0.00036134 | -26.20 | 0.26545389 | 21.6315 | 21.10 | 0.00639530 | 21.10 | 0.00639530 | 39.2972 | 22634.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_3:3 | SMSTORE2 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 28777.580 | 0.000 | 1.235420 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1025.7684 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 28777.58 | 19603.27 | 1.0000 | 1.41894884 | 1.235420 | 25.60 | 18.64 | 0.01125821 | 54417.9 | 12.80 | 11.67 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 28777.58 | 31.20 | 0.01534436 | 23.10 | 0.26545389 | 21.4869 | 23.88 | 0.01000407 | 23.88 | 0.01000315 | 51.5977 | 12238.95 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_3:3_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_3:3 | SMSTORE2 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 41437.198 | 41437.198 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.235420 | 1.41894915 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 41437.20 | 41437.20 | 1.0000 | 1.41894915 | 1.235420 | 10.94 | 7.22 | 0.00510521 | 23863.0 | 40.00 | 20.60 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 41437.20 | -26.20 | 0.00036134 | -26.20 | 0.26545389 | 21.4869 | 21.10 | 0.00640348 | 21.10 | 0.00640348 | 39.3469 | 22786.23 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_4:4 | SMSTORE3 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 28872.370 | 0.000 | 1.238410 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1025.7810 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 28872.37 | 19654.76 | 1.0000 | 1.42238302 | 1.238410 | 25.61 | 18.65 | 0.01126494 | 54440.5 | 12.80 | 11.67 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 28872.37 | 31.20 | 0.01534436 | 23.10 | 0.26545389 | 21.4351 | 23.88 | 0.01000783 | 23.88 | 0.01000687 | 51.6166 | 12201.37 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_4:4_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_4:4 | SMSTORE3 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 41502.311 | 41502.311 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.238406 | 1.42237823 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 41502.31 | 41502.31 | 1.0000 | 1.42237823 | 1.238406 | 10.96 | 7.24 | 0.00511065 | 23901.6 | 40.00 | 20.60 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 41502.31 | -26.20 | 0.00036134 | -26.20 | 0.26545389 | 21.4351 | 21.10 | 0.00640642 | 21.10 | 0.00640642 | 39.3648 | 22841.29 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_5:5 | SMSTORE4 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 29073.490 | 0.000 | 1.245640 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1025.7969 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 29073.49 | 19774.94 | 1.0000 | 1.43068708 | 1.245640 | 25.61 | 18.66 | 0.01127353 | 54469.3 | 12.80 | 11.67 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 29073.49 | 31.20 | 0.01534436 | 23.10 | 0.26545389 | 21.3106 | 23.88 | 0.01001262 | 23.88 | 0.01001165 | 51.6408 | 12153.70 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_5:5_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_5:5 | SMSTORE4 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 41660.153 | 41660.153 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.245643 | 1.43069088 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 41660.15 | 41660.15 | 1.0000 | 1.43069088 | 1.245643 | 11.02 | 7.28 | 0.00512372 | 23994.3 | 40.00 | 20.60 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 41660.15 | -26.20 | 0.00036134 | -26.20 | 0.26545389 | 21.3106 | 21.10 | 0.00641346 | 21.10 | 0.00641346 | 39.4076 | 22974.77 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_6:6 | LGSTORE2 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 54697.680 | 0.000 | 2.306400 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1025.9855 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 54697.68 | 36901.82 | 1.0000 | 2.64902916 | 2.306400 | 25.77 | 18.79 | 0.01137496 | 54891.4 | 12.80 | 11.67 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 54697.68 | 31.20 | 0.01534436 | 23.10 | 0.53090778 | 23.0189 | 23.88 | 0.00999287 | 23.88 | 0.00998955 | 51.5276 | 22259.03 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_6:6_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_6:6 | LGSTORE2 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 79286.237 | 79286.237 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.306397 | 2.64902555 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 79286.24 | 79286.24 | 1.0000 | 2.64902555 | 2.306397 | 10.21 | 6.84 | 0.00507466 | 23051.6 | 40.00 | 20.60 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 79286.24 | -26.20 | 0.00036134 | -26.20 | 0.53090778 | 23.0189 | 21.10 | 0.00648404 | 21.10 | 0.00648404 | 39.8343 | 42537.74 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_7:7 | SMSTORE5 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 29902.460 | 0.000 | 1.264050 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1025.9910 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 29902.46 | 20133.49 | 1.0000 | 1.45183199 | 1.264050 | 25.70 | 18.76 | 0.01137793 | 54820.6 | 12.80 | 11.67 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 29902.46 | 31.20 | 0.01534436 | 23.10 | 0.26545389 | 21.0003 | 23.88 | 0.01007093 | 23.88 | 0.01006768 | 51.9251 | 11596.96 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_7:7_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_7:7 | SMSTORE5 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 42061.634 | 42061.634 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.264054 | 1.45183604 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 42061.63 | 42061.63 | 1.0000 | 1.45183604 | 1.264054 | 11.17 | 7.39 | 0.00515631 | 24225.5 | 40.00 | 20.60 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 42061.63 | -26.20 | 0.00036134 | -26.20 | 0.26545389 | 21.0002 | 21.10 | 0.00643093 | 21.10 | 0.00643093 | 39.5138 | 23314.27 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_8:8 | SMSTORE6 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 29937.350 | 0.000 | 1.262950 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1026.0207 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 29937.35 | 20126.15 | 1.0000 | 1.45056858 | 1.262950 | 25.71 | 18.78 | 0.01139391 | 54874.5 | 12.80 | 11.67 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 29937.35 | 31.20 | 0.01534436 | 23.10 | 0.26545389 | 21.0186 | 23.88 | 0.01007986 | 23.88 | 0.01007659 | 51.9704 | 11515.19 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_8:8_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_8:8 | SMSTORE6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 42037.497 | 42037.497 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.262947 | 1.45056490 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 42037.50 | 42037.50 | 1.0000 | 1.45056490 | 1.262947 | 11.16 | 7.38 | 0.00515435 | 24211.7 | 40.00 | 20.60 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 42037.50 | -26.20 | 0.00036134 | -26.20 | 0.26545389 | 21.0186 | 21.10 | 0.00642987 | 21.10 | 0.00642987 | 39.5074 | 23293.85 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_9:9 | SMSTORE7 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 30273.990 | 0.000 | 1.274110 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1026.0554 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 30273.99 | 20316.28 | 1.0000 | 1.46338647 | 1.274110 | 25.73 | 18.80 | 0.01141257 | 54937.6 | 12.80 | 11.67 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 30273.99 | 31.20 | 0.01534436 | 23.10 | 0.26545389 | 20.8345 | 23.88 | 0.01009029 | 23.88 | 0.01008696 | 52.0229 | 11420.90 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_9:9_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_9:9 | SMSTORE7 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 42281.057 | 42281.057 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.274115 | 1.46339164 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 42281.06 | 42281.06 | 1.0000 | 1.46339164 | 1.274115 | 11.25 | 7.44 | 0.00517389 | 24349.4 | 40.00 | 20.60 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 42281.06 | -26.20 | 0.00036134 | -26.20 | 0.26545389 | 20.8344 | 21.10 | 0.00644043 | 21.10 | 0.00644043 | 39.5716 | 23499.82 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_10:10 | SMSTORE8 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 34353.960 | 0.000 | 1.449360 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1026.0771 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | 34353.96 | 22988.91 | 1.0000 | 1.66467087 | 1.449360 | 25.66 | 18.79 | 0.01142425 | 54896.7 | 12.80 | 11.67 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 34353.96 | 31.02 | 0.01534436 | 23.05 | 0.26545389 | 18.3152 | 23.88 | 0.01012968 | 23.88 | 0.01011371 | 52.1588 | 11577.79 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_10:10_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_10:10 | SMSTORE8 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 46104.044 | 46104.044 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.449359 | 1.66466947 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 46104.04 | 46104.04 | 1.0000 | 1.66466947 | 1.449359 | 12.44 | 8.25 | 0.00540391 | 26138.3 | 40.00 | 20.60 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 46104.04 | -26.20 | 0.00036134 | -26.20 | 0.26545389 | 18.3153 | 21.10 | 0.00653455 | 21.10 | 0.00653455 | 40.1453 | 26732.89 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2020-06-03 19:19:07
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-AC_1:1_OA_CONTROLLER | DifferentialDryBulb | 0.53 | 2.42 | - | |||
PSZ-AC_6:6_OA_CONTROLLER | DifferentialDryBulb | 0.53 | 2.31 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
LGSTORE1 | 3686.83 | 3978.17 | 2140.67 |
SMSTORE1 | 3078.00 | 3598.50 | 1352.83 |
SMSTORE2 | 2716.17 | 2936.50 | 1481.67 |
SMSTORE3 | 2766.83 | 2971.67 | 1559.17 |
SMSTORE4 | 2799.50 | 3008.50 | 1620.00 |
LGSTORE2 | 2676.83 | 2904.33 | 1721.83 |
SMSTORE5 | 2607.67 | 2817.33 | 1620.17 |
SMSTORE6 | 2607.83 | 2838.83 | 1642.50 |
SMSTORE7 | 2649.00 | 2898.17 | 1723.83 |
SMSTORE8 | 2782.00 | 3021.50 | 1980.83 |
Facility | 4387.83 | 4469.33 | 2872.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
LGSTORE1 | 40.50 | 0.00 | 8.17 | 0.00 |
SMSTORE1 | 12.33 | 0.00 | 4.83 | 0.00 |
SMSTORE2 | 17.00 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 21.83 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 26.00 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 38.00 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 37.50 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 38.83 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 50.00 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 198.67 | 0.00 | 0.00 | 0.00 |
Facility | 275.83 | 0.00 | 8.17 | 0.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2020-06-03 19:19:07
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
LGSTORE1 | 9.03 | 30.00 | 1805.20 | 1.457 | 0.404 | 0.000 | 0.000 |
SMSTORE1 | 4.51 | 15.00 | 902.60 | 0.827 | 0.429 | 0.000 | 0.000 |
SMSTORE2 | 3.78 | 15.00 | 902.60 | 1.075 | 0.556 | 0.000 | 0.000 |
SMSTORE3 | 3.78 | 15.00 | 902.60 | 1.074 | 0.556 | 0.000 | 0.000 |
SMSTORE4 | 3.78 | 15.00 | 902.60 | 1.074 | 0.556 | 0.000 | 0.000 |
LGSTORE2 | 13.22 | 30.00 | 1805.20 | 1.381 | 0.522 | 0.000 | 0.000 |
SMSTORE5 | 6.61 | 15.00 | 902.60 | 1.075 | 0.591 | 0.000 | 0.000 |
SMSTORE6 | 6.61 | 15.00 | 902.60 | 1.075 | 0.591 | 0.000 | 0.000 |
SMSTORE7 | 6.61 | 15.00 | 902.60 | 1.074 | 0.591 | 0.000 | 0.000 |
SMSTORE8 | 6.61 | 15.00 | 902.60 | 1.074 | 0.642 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
LGSTORE1 | 9.03 | 30.00 | 1805.20 | 0.000 | 0.000 | 0.000 | 0.000 |
SMSTORE1 | 4.51 | 15.00 | 902.60 | 0.000 | 0.000 | 0.000 | 0.000 |
SMSTORE2 | 3.78 | 15.00 | 902.60 | 1.041 | 0.000 | 0.000 | 0.000 |
SMSTORE3 | 3.78 | 15.00 | 902.60 | 1.041 | 0.000 | 0.000 | 0.000 |
SMSTORE4 | 3.78 | 15.00 | 902.60 | 1.041 | 0.000 | 0.000 | 0.000 |
LGSTORE2 | 13.22 | 30.00 | 1805.20 | 1.041 | 0.000 | 0.000 | 0.000 |
SMSTORE5 | 6.61 | 15.00 | 902.60 | 1.041 | 0.000 | 0.000 | 0.000 |
SMSTORE6 | 6.61 | 15.00 | 902.60 | 1.041 | 0.000 | 0.000 | 0.000 |
SMSTORE7 | 6.61 | 15.00 | 902.60 | 1.041 | 0.000 | 0.000 | 0.000 |
SMSTORE8 | 6.61 | 15.00 | 902.60 | 1.041 | 0.000 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2020-06-03 19:19:07
Surfaces by ClassTotal | Outdoors | |
Wall | 40 | 22 |
Floor | 10 | 10 |
Roof | 10 | 10 |
Internal Mass | 10 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 36 | 36 |
Door | 12 | 12 |
Glass Door | 12 | 12 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 10 |
Conditioned Zones | 10 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 0 |
Defaulted Fields | 0 |
Fields with Defaults | 0 |
Autosized Fields | 0 |
Autosizable Fields | 0 |
Autocalculated Fields | 0 |
Autocalculatable Fields | 0 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2020-06-03 19:19:07
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1498.40 | 3969.13 | 20-FEB-07:30 | 155969.82 | 04-AUG-13:40 |
Electricity:Building | 837.46 | 2751.13 | 01-JAN-00:10 | 51821.98 | 01-JAN-11:10 |
Electricity:Zone:LGSTORE1 | 211.76 | 576.88 | 01-JAN-00:10 | 10885.83 | 01-JAN-10:10 |
InteriorLights:Electricity | 708.74 | 2301.71 | 01-JAN-00:10 | 43732.45 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:LGSTORE1 | 185.40 | 501.98 | 01-JAN-00:10 | 9537.57 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity | 708.74 | 2301.71 | 01-JAN-00:10 | 43732.45 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE1 | 105.88 | 288.44 | 01-JAN-00:10 | 5442.91 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE1 | 92.70 | 250.99 | 01-JAN-00:10 | 4768.79 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE2 | 68.15 | 234.53 | 01-JAN-00:10 | 4418.69 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE2 | 57.68 | 197.08 | 01-JAN-00:10 | 3744.57 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE3 | 68.15 | 234.53 | 01-JAN-00:10 | 4418.69 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE3 | 57.68 | 197.08 | 01-JAN-00:10 | 3744.57 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE4 | 68.15 | 234.53 | 01-JAN-00:10 | 4418.69 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE4 | 57.68 | 197.08 | 01-JAN-00:10 | 3744.57 | 01-JAN-10:10 |
Electricity:Zone:LGSTORE2 | 105.13 | 394.07 | 01-JAN-00:10 | 7412.39 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:LGSTORE2 | 85.86 | 319.16 | 01-JAN-00:10 | 6064.13 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE5 | 52.56 | 197.03 | 01-JAN-00:10 | 3706.19 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE5 | 42.93 | 159.58 | 01-JAN-00:10 | 3032.07 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE6 | 52.56 | 197.03 | 01-JAN-00:10 | 3706.19 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE6 | 42.93 | 159.58 | 01-JAN-00:10 | 3032.07 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE7 | 52.56 | 197.03 | 01-JAN-00:10 | 3706.19 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE7 | 42.93 | 159.58 | 01-JAN-00:10 | 3032.07 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE8 | 52.56 | 197.03 | 01-JAN-00:10 | 3706.19 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE8 | 42.93 | 159.58 | 01-JAN-00:10 | 3032.07 | 01-JAN-11:10 |
InteriorEquipment:Electricity | 128.72 | 449.42 | 01-JAN-00:10 | 8089.53 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:LGSTORE1 | 26.36 | 74.90 | 01-JAN-00:10 | 1348.26 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity | 128.72 | 449.42 | 01-JAN-00:10 | 8089.53 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE1 | 13.18 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE2 | 10.47 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE3 | 10.47 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE4 | 10.47 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:LGSTORE2 | 19.26 | 74.90 | 01-JAN-00:10 | 1348.26 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE5 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE6 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE7 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE8 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
Electricity:Plant | 66.36 | 1218.00 | 06-JAN-00:10 | 11887.04 | 07-JAN-14:00 |
WaterSystems:Electricity | 66.36 | 1218.00 | 06-JAN-00:10 | 11887.04 | 07-JAN-14:00 |
Water Heater:WaterSystems:Electricity | 66.36 | 1218.00 | 06-JAN-00:10 | 11887.04 | 07-JAN-14:00 |
ElectricityPurchased:Facility | 1498.40 | 3969.13 | 20-FEB-07:30 | 155969.82 | 04-AUG-13:40 |
ElectricityPurchased:Plant | 1498.40 | 3969.13 | 20-FEB-07:30 | 155969.82 | 04-AUG-13:40 |
Cogeneration:ElectricityPurchased | 1498.40 | 3969.13 | 20-FEB-07:30 | 155969.82 | 04-AUG-13:40 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1498.40 | 3969.13 | 20-FEB-07:30 | 155969.82 | 04-AUG-13:40 |
ElectricityNet:Plant | 1498.40 | 3969.13 | 20-FEB-07:30 | 155969.82 | 04-AUG-13:40 |
Cogeneration:ElectricityNet | 1498.40 | 3969.13 | 20-FEB-07:30 | 155969.82 | 04-AUG-13:40 |
Electricity:HVAC | 427.78 | 0.00 | 01-JAN-00:10 | 99448.08 | 04-AUG-16:00 |
Fans:Electricity | 287.44 | 0.00 | 01-JAN-00:10 | 16727.67 | 01-JAN-09:30 |
General:Fans:Electricity | 287.44 | 0.00 | 01-JAN-00:10 | 16727.67 | 01-JAN-09:30 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 140.34 | 0.00 | 01-JAN-00:10 | 82720.41 | 04-AUG-16:00 |
ExteriorLights:Electricity | 166.80 | 0.00 | 01-JAN-08:00 | 10625.34 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 166.80 | 0.00 | 01-JAN-08:00 | 10625.34 | 01-JAN-00:10 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Gas:Facility | 1353.87 | 0.00 | 01-JAN-00:10 | 503448.11 | 02-FEB-12:10 |
Gas:HVAC | 1353.87 | 0.00 | 01-JAN-00:10 | 503448.11 | 02-FEB-12:10 |
Heating:Gas | 1353.87 | 0.00 | 01-JAN-00:10 | 503448.11 | 02-FEB-12:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water:Plant | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
WaterSystems:Water | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water Heater:WaterSystems:Water | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
MainsWater:Facility | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
MainsWater:Plant | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
WaterSystems:MainsWater | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water Heater:WaterSystems:MainsWater | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:Facility | 2371.80 | 0.00 | 01-JAN-00:10 | 628503.63 | 02-FEB-12:10 |
EnergyTransfer:Building | 819.88 | 0.00 | 01-JAN-00:10 | 236871.65 | 02-FEB-08:10 |
EnergyTransfer:Zone:LGSTORE1 | 156.19 | 0.00 | 01-JAN-00:10 | 44251.10 | 02-FEB-08:10 |
Heating:EnergyTransfer | 483.47 | 0.00 | 01-JAN-00:10 | 236871.65 | 02-FEB-08:10 |
Heating:EnergyTransfer:Zone:LGSTORE1 | 68.07 | 0.00 | 01-JAN-00:10 | 44251.10 | 02-FEB-08:10 |
Cooling:EnergyTransfer | 336.41 | 0.00 | 01-JAN-00:10 | 111807.53 | 04-AUG-15:00 |
Cooling:EnergyTransfer:Zone:LGSTORE1 | 88.11 | 0.00 | 01-JAN-00:10 | 22378.01 | 06-JAN-00:10 |
EnergyTransfer:Zone:SMSTORE1 | 73.25 | 0.00 | 01-JAN-00:10 | 19517.78 | 10-DEC-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE1 | 27.85 | 0.00 | 01-JAN-00:10 | 19494.73 | 31-JAN-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE1 | 45.40 | 0.00 | 01-JAN-00:10 | 10199.76 | 04-AUG-15:00 |
EnergyTransfer:Zone:SMSTORE2 | 63.06 | 0.00 | 01-JAN-00:10 | 19788.39 | 05-FEB-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE2 | 34.72 | 0.00 | 01-JAN-00:10 | 19788.39 | 05-FEB-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE2 | 28.34 | 0.00 | 01-JAN-00:10 | 9504.25 | 04-AUG-15:00 |
EnergyTransfer:Zone:SMSTORE3 | 64.04 | 0.00 | 01-JAN-00:10 | 19420.79 | 26-NOV-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE3 | 36.96 | 0.00 | 01-JAN-00:10 | 19420.79 | 26-NOV-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE3 | 27.08 | 0.00 | 01-JAN-00:10 | 9438.48 | 04-AUG-15:00 |
EnergyTransfer:Zone:SMSTORE4 | 64.90 | 0.00 | 01-JAN-00:10 | 20727.70 | 29-JAN-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE4 | 39.12 | 0.00 | 01-JAN-00:10 | 20727.70 | 29-JAN-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE4 | 25.78 | 0.00 | 01-JAN-00:10 | 9336.94 | 04-AUG-15:00 |
EnergyTransfer:Zone:LGSTORE2 | 118.60 | 0.00 | 01-JAN-00:10 | 44769.07 | 02-FEB-08:10 |
Heating:EnergyTransfer:Zone:LGSTORE2 | 75.54 | 0.00 | 01-JAN-00:10 | 44769.07 | 02-FEB-08:10 |
Cooling:EnergyTransfer:Zone:LGSTORE2 | 43.07 | 0.00 | 01-JAN-00:10 | 17181.68 | 04-AUG-15:00 |
EnergyTransfer:Zone:SMSTORE5 | 63.72 | 0.00 | 01-JAN-00:10 | 21520.33 | 02-FEB-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE5 | 42.16 | 0.00 | 01-JAN-00:10 | 21520.33 | 02-FEB-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE5 | 21.57 | 0.00 | 01-JAN-00:10 | 9058.68 | 04-AUG-15:00 |
EnergyTransfer:Zone:SMSTORE6 | 63.59 | 0.00 | 01-JAN-00:10 | 21553.39 | 02-FEB-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE6 | 42.64 | 0.00 | 01-JAN-00:10 | 21553.39 | 02-FEB-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE6 | 20.95 | 0.00 | 01-JAN-00:10 | 8992.01 | 04-AUG-15:00 |
EnergyTransfer:Zone:SMSTORE7 | 64.90 | 0.00 | 01-JAN-00:10 | 22006.25 | 02-FEB-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE7 | 45.45 | 0.00 | 01-JAN-00:10 | 22006.25 | 02-FEB-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE7 | 19.46 | 0.00 | 01-JAN-00:10 | 8923.30 | 04-AUG-15:00 |
EnergyTransfer:Zone:SMSTORE8 | 87.64 | 0.00 | 01-JAN-00:10 | 27262.11 | 02-FEB-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE8 | 70.97 | 0.00 | 01-JAN-00:10 | 27262.11 | 02-FEB-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE8 | 16.67 | 0.00 | 01-JAN-00:10 | 9309.25 | 04-AUG-15:00 |
EnergyTransfer:HVAC | 1551.92 | 0.00 | 01-JAN-00:10 | 401540.87 | 02-FEB-12:10 |
HeatingCoils:EnergyTransfer | 1079.86 | 0.00 | 01-JAN-00:10 | 401540.87 | 02-FEB-12:10 |
CoolingCoils:EnergyTransfer | 472.06 | 0.00 | 01-JAN-00:10 | 290882.17 | 04-AUG-13:00 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2020-06-03 19:19:07
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
LGSTORE1 | 0.000 | 0.000 | 68.074 | -88.110 | 0.000 | 0.000 | 13.566 | 185.400 | 26.357 | 17.801 | 0.000 | 2.553 | 0.001 | 0.000 | -16.092 | 0.000 | -91.946 | -117.603 |
SMSTORE1 | 0.000 | 0.000 | 27.847 | -45.401 | 0.000 | 0.000 | 6.719 | 92.700 | 13.179 | 8.815 | 0.000 | 1.397 | 0.000 | 0.000 | -8.373 | 0.000 | -43.816 | -53.066 |
SMSTORE2 | 0.000 | 0.000 | 34.720 | -28.341 | 0.000 | 0.000 | 4.097 | 57.682 | 10.467 | 8.834 | 0.000 | 1.353 | 0.004 | 0.000 | -8.088 | 0.000 | -45.072 | -35.651 |
SMSTORE3 | 0.000 | 0.000 | 36.959 | -27.076 | 0.000 | 0.000 | 4.102 | 57.682 | 10.467 | 8.858 | 0.000 | 1.353 | 0.001 | 0.000 | -7.979 | 0.000 | -44.875 | -39.490 |
SMSTORE4 | 0.000 | 0.000 | 39.123 | -25.775 | 0.000 | 0.000 | 4.107 | 57.682 | 10.467 | 8.877 | 0.000 | 1.353 | 0.002 | 0.000 | -7.913 | 0.000 | -44.743 | -43.179 |
LGSTORE2 | 0.000 | 0.000 | 75.535 | -43.067 | 0.000 | 0.000 | 14.106 | 85.864 | 19.261 | 17.880 | 0.000 | 2.387 | 0.001 | 0.000 | -15.393 | 0.000 | -81.565 | -75.008 |
SMSTORE5 | 0.000 | 0.000 | 42.157 | -21.564 | 0.000 | 0.000 | 7.055 | 42.932 | 9.631 | 8.930 | 0.000 | 1.356 | 0.001 | 0.000 | -7.731 | 0.000 | -44.996 | -37.770 |
SMSTORE6 | 0.000 | 0.000 | 42.639 | -20.947 | 0.000 | 0.000 | 7.060 | 42.932 | 9.631 | 8.941 | 0.000 | 1.356 | 0.001 | 0.000 | -7.704 | 0.000 | -44.937 | -38.972 |
SMSTORE7 | 0.000 | 0.000 | 45.446 | -19.456 | 0.000 | 0.000 | 7.070 | 42.932 | 9.631 | 8.972 | 0.000 | 1.357 | 0.000 | 0.000 | -7.605 | 0.000 | -44.739 | -43.609 |
SMSTORE8 | 0.000 | 0.000 | 70.973 | -16.667 | 0.000 | 0.000 | 7.092 | 42.932 | 9.631 | 9.079 | 0.000 | 1.452 | 0.000 | 0.000 | -7.171 | 0.000 | -59.579 | -57.743 |
Total Facility | 0.000 | 0.000 | 483.473 | -336.405 | 0.000 | 0.000 | 74.975 | 708.738 | 128.721 | 106.987 | 0.000 | 15.917 | 0.011 | 0.000 | -94.048 | 0.000 | -546.268 | -542.091 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
LGSTORE1 | 12-SEP-07:02 | 0.00 | 0.00 | 0.00 | -34865.63 | 0.00 | 0.00 | 96.86 | 501.98 | 74.90 | 0.00 | 0.00 | 0.00 | 35076.53 | 0.00 | -220.50 | 0.00 | -664.14 | 0.00 |
SMSTORE1 | 12-SEP-07:02 | 0.00 | 0.00 | 0.00 | -19370.08 | 0.00 | 0.00 | 47.44 | 250.99 | 37.45 | 0.00 | 0.00 | 0.00 | 19495.35 | 0.00 | -114.95 | 0.00 | -346.20 | 0.00 |
SMSTORE2 | 11-SEP-06:03 | 0.00 | 0.00 | 0.00 | -18265.35 | 0.00 | 0.00 | 0.00 | 197.08 | 37.45 | 0.00 | 0.00 | 0.00 | 18166.69 | 0.00 | -97.74 | 0.00 | -38.13 | 0.00 |
SMSTORE3 | 11-SEP-06:03 | 0.00 | 0.00 | 0.00 | -18298.33 | 0.00 | 0.00 | 0.00 | 197.08 | 37.45 | 0.00 | 0.00 | 0.00 | 18199.07 | 0.00 | -97.32 | 0.00 | -37.96 | 0.00 |
SMSTORE4 | 11-SEP-06:03 | 0.00 | 0.00 | 0.00 | -18070.14 | 0.00 | 0.00 | 0.00 | 197.08 | 37.45 | 0.00 | 0.00 | 0.00 | 17968.64 | 0.00 | -95.69 | 0.00 | -37.34 | 0.00 |
LGSTORE2 | 11-SEP-07:03 | 0.00 | 0.00 | 0.00 | -32910.08 | 0.00 | 0.00 | 0.00 | 319.16 | 74.90 | 225.30 | 0.00 | 0.00 | 32594.87 | 0.00 | -0.00 | 0.00 | -304.16 | 0.00 |
SMSTORE5 | 30-JUN-07:02 | 0.00 | 0.00 | 0.00 | -16839.97 | 0.00 | 0.00 | 0.00 | 159.58 | 37.45 | 200.59 | 0.00 | 0.00 | 16491.84 | 0.00 | -0.00 | 0.00 | -49.50 | 0.00 |
SMSTORE6 | 30-JUN-07:02 | 0.00 | 0.00 | 0.00 | -16792.18 | 0.00 | 0.00 | 0.00 | 159.58 | 37.45 | 201.88 | 0.00 | 0.00 | 16440.38 | 0.00 | -0.00 | 0.00 | -47.12 | 0.00 |
SMSTORE7 | 30-JUN-07:02 | 0.00 | 0.00 | 0.00 | -16600.41 | 0.00 | 0.00 | 0.00 | 159.58 | 37.45 | 205.44 | 0.00 | 0.00 | 16237.07 | 0.00 | -0.00 | 0.00 | -39.14 | 0.00 |
SMSTORE8 | 04-JUL-08:62 | 0.00 | 0.00 | 0.00 | -15021.29 | 0.00 | 0.00 | 0.00 | 159.58 | 37.45 | 311.19 | 0.00 | 0.00 | 14596.81 | 0.00 | -0.00 | 0.00 | -83.75 | 0.00 |
Total Facility | 05-JUL-07:02 | 0.00 | 0.00 | 0.00 | -145563.96 | 0.00 | 0.00 | 298.76 | 7622.93 | 1460.61 | 1668.03 | 0.00 | 0.00 | 136275.39 | 0.00 | 0.00 | 0.00 | -1761.76 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
LGSTORE1 | 30-JAN-00:42 | 0.00 | 0.00 | 82587.27 | 0.00 | 0.00 | 0.00 | 0.00 | 501.98 | 74.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1989.87 | 0.00 | -6614.84 | -74559.44 |
SMSTORE1 | 29-APR-07:01 | 0.00 | 0.00 | 36969.06 | 0.00 | 0.00 | 0.00 | 0.00 | 250.99 | 37.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -47.94 | 0.00 | -760.96 | -36448.60 |
SMSTORE2 | 20-NOV-07:01 | 0.00 | 0.00 | 38231.26 | 0.00 | 0.00 | 0.00 | 0.00 | 197.08 | 37.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -197.12 | 0.00 | -181.58 | -38087.10 |
SMSTORE3 | 20-NOV-07:01 | 0.00 | 0.00 | 38435.38 | 0.00 | 0.00 | 0.00 | 0.00 | 197.08 | 37.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -185.67 | 0.00 | -172.46 | -38311.78 |
SMSTORE4 | 20-NOV-07:01 | 0.00 | 0.00 | 38667.37 | 0.00 | 0.00 | 0.00 | 0.00 | 197.08 | 37.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -179.27 | 0.00 | -167.03 | -38555.61 |
LGSTORE2 | 02-FEB-08:11 | 0.00 | 0.00 | 79922.10 | 0.00 | 0.00 | 0.00 | 0.00 | 319.16 | 74.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1658.38 | 0.00 | -5580.75 | -73077.04 |
SMSTORE5 | 20-NOV-08:61 | 0.00 | 0.00 | 39872.90 | 0.00 | 0.00 | 0.00 | 0.00 | 159.58 | 37.45 | 54.50 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -394.53 | -39729.90 |
SMSTORE6 | 20-NOV-08:61 | 0.00 | 0.00 | 39876.37 | 0.00 | 0.00 | 0.00 | 0.00 | 159.58 | 37.45 | 56.65 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -389.53 | -39740.52 |
SMSTORE7 | 20-NOV-08:61 | 0.00 | 0.00 | 40227.45 | 0.00 | 0.00 | 0.00 | 0.00 | 159.58 | 37.45 | 65.72 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -367.63 | -40122.57 |
SMSTORE8 | 20-NOV-08:61 | 0.00 | 0.00 | 44214.99 | 0.00 | 0.00 | 0.00 | 0.00 | 159.58 | 37.45 | 95.59 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -433.06 | -44074.54 |
Total Facility | 09-JAN-08:61 | 0.00 | 0.00 | 364514.60 | 0.00 | 0.00 | 0.00 | 411.26 | 7622.93 | 1460.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -463.79 | 0.00 | -13855.76 | -359689.87 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2020-06-03 19:19:07
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 2.4153 | 0.0000 | 29.9961 | 1.0000 | 0.5309 | 2.4153 | 0.2322 | 1.0000 | 0.5309 | 0.2198 | ||
PSZ-AC_2:2 | 1.2272 | 0.0000 | 14.9980 | 1.0000 | 0.2655 | 1.2272 | 0.2216 | 1.0000 | 0.2655 | 0.2163 | ||
PSZ-AC_3:3 | 1.2354 | 0.0000 | 14.9980 | 1.0000 | 0.2655 | 1.2354 | 0.2348 | 1.0000 | 0.2655 | 0.2149 | ||
PSZ-AC_4:4 | 1.2384 | 0.0000 | 14.9980 | 1.0000 | 0.2655 | 1.2384 | 0.2355 | 1.0000 | 0.2655 | 0.2144 | ||
PSZ-AC_5:5 | 1.2456 | 0.0000 | 14.9980 | 1.0000 | 0.2655 | 1.2456 | 0.2364 | 1.0000 | 0.2655 | 0.2131 | ||
PSZ-AC_6:6 | 2.3064 | 0.0000 | 29.9961 | 1.0000 | 0.5309 | 2.3064 | 0.2581 | 1.0000 | 0.5309 | 0.2302 | ||
PSZ-AC_7:7 | 1.2641 | 0.0000 | 14.9980 | 1.0000 | 0.2655 | 1.2641 | 0.2477 | 1.0000 | 0.2655 | 0.2100 | ||
PSZ-AC_8:8 | 1.2629 | 0.0000 | 14.9980 | 1.0000 | 0.2655 | 1.2629 | 0.2495 | 1.0000 | 0.2655 | 0.2102 | ||
PSZ-AC_9:9 | 1.2741 | 0.0000 | 14.9980 | 1.0000 | 0.2655 | 1.2741 | 0.2515 | 1.0000 | 0.2655 | 0.2083 | ||
PSZ-AC_10:10 | 1.4494 | 0.0000 | 14.9980 | 1.0000 | 0.2655 | 1.4494 | 0.2471 | 1.0000 | 0.2655 | 0.1832 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 2.4153 | 0.0000 | 29.9961 | 1.0000 | 0.5309 | 2.4153 | 1.0000 | 1.0000 | 0.5309 | 0.2198 | ||
PSZ-AC_2:2 | 1.2272 | 0.0000 | 14.9980 | 1.0000 | 0.2655 | 1.2272 | 1.0000 | 1.0000 | 0.2655 | 0.2163 | ||
PSZ-AC_3:3 | 1.2354 | 0.0000 | 14.9980 | 1.0000 | 0.2655 | 1.2354 | 1.0000 | 1.0000 | 0.2655 | 0.2149 | ||
PSZ-AC_4:4 | 1.2384 | 0.0000 | 14.9980 | 1.0000 | 0.2655 | 1.2384 | 1.0000 | 1.0000 | 0.2655 | 0.2144 | ||
PSZ-AC_5:5 | 1.2456 | 0.0000 | 14.9980 | 1.0000 | 0.2655 | 1.2456 | 1.0000 | 1.0000 | 0.2655 | 0.2131 | ||
PSZ-AC_6:6 | 2.3064 | 0.0000 | 29.9961 | 1.0000 | 0.5309 | 2.3064 | 1.0000 | 1.0000 | 0.5309 | 0.2302 | ||
PSZ-AC_7:7 | 1.2641 | 0.0000 | 14.9980 | 1.0000 | 0.2655 | 1.2641 | 1.0000 | 1.0000 | 0.2655 | 0.2100 | ||
PSZ-AC_8:8 | 1.2629 | 0.0000 | 14.9980 | 1.0000 | 0.2655 | 1.2629 | 1.0000 | 1.0000 | 0.2655 | 0.2102 | ||
PSZ-AC_9:9 | 1.2741 | 0.0000 | 14.9980 | 1.0000 | 0.2655 | 1.2741 | 1.0000 | 1.0000 | 0.2655 | 0.2083 | ||
PSZ-AC_10:10 | 1.4494 | 0.0000 | 14.9980 | 1.0000 | 0.2655 | 1.4494 | 1.0000 | 1.0000 | 0.2655 | 0.1832 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
LGSTORE1 | PSZ-AC_1:1 | 0.000000 | 29.9961 | 0.001524 | 348.39 | 0.5309 | 1.0000 | 0.5309 | 1.000 | 0.5309 |
SMSTORE1 | PSZ-AC_2:2 | 0.000000 | 14.9980 | 0.001524 | 174.19 | 0.2655 | 1.0000 | 0.2655 | 1.000 | 0.2655 |
SMSTORE2 | PSZ-AC_3:3 | 0.000000 | 14.9980 | 0.001524 | 174.19 | 0.2655 | 1.0000 | 0.2655 | 1.000 | 0.2655 |
SMSTORE3 | PSZ-AC_4:4 | 0.000000 | 14.9980 | 0.001524 | 174.19 | 0.2655 | 1.0000 | 0.2655 | 1.000 | 0.2655 |
SMSTORE4 | PSZ-AC_5:5 | 0.000000 | 14.9980 | 0.001524 | 174.19 | 0.2655 | 1.0000 | 0.2655 | 1.000 | 0.2655 |
LGSTORE2 | PSZ-AC_6:6 | 0.000000 | 29.9961 | 0.001524 | 348.39 | 0.5309 | 1.0000 | 0.5309 | 1.000 | 0.5309 |
SMSTORE5 | PSZ-AC_7:7 | 0.000000 | 14.9980 | 0.001524 | 174.19 | 0.2655 | 1.0000 | 0.2655 | 1.000 | 0.2655 |
SMSTORE6 | PSZ-AC_8:8 | 0.000000 | 14.9980 | 0.001524 | 174.19 | 0.2655 | 1.0000 | 0.2655 | 1.000 | 0.2655 |
SMSTORE7 | PSZ-AC_9:9 | 0.000000 | 14.9980 | 0.001524 | 174.19 | 0.2655 | 1.0000 | 0.2655 | 1.000 | 0.2655 |
SMSTORE8 | PSZ-AC_10:10 | 0.000000 | 14.9980 | 0.001524 | 174.19 | 0.2655 | 1.0000 | 0.2655 | 1.000 | 0.2655 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC_1:1 | 0.000000 | 30.00 | 0.001524 | 348.3864 | 0.5309 | 0.5309 | 0.5309 |
PSZ-AC_2:2 | 0.000000 | 15.00 | 0.001524 | 174.1932 | 0.2655 | 0.2655 | 0.2655 |
PSZ-AC_3:3 | 0.000000 | 15.00 | 0.001524 | 174.1932 | 0.2655 | 0.2655 | 0.2655 |
PSZ-AC_4:4 | 0.000000 | 15.00 | 0.001524 | 174.1932 | 0.2655 | 0.2655 | 0.2655 |
PSZ-AC_5:5 | 0.000000 | 15.00 | 0.001524 | 174.1932 | 0.2655 | 0.2655 | 0.2655 |
PSZ-AC_6:6 | 0.000000 | 30.00 | 0.001524 | 348.3864 | 0.5309 | 0.5309 | 0.5309 |
PSZ-AC_7:7 | 0.000000 | 15.00 | 0.001524 | 174.1932 | 0.2655 | 0.2655 | 0.2655 |
PSZ-AC_8:8 | 0.000000 | 15.00 | 0.001524 | 174.1932 | 0.2655 | 0.2655 | 0.2655 |
PSZ-AC_9:9 | 0.000000 | 15.00 | 0.001524 | 174.1932 | 0.2655 | 0.2655 | 0.2655 |
PSZ-AC_10:10 | 0.000000 | 15.00 | 0.001524 | 174.1932 | 0.2655 | 0.2655 | 0.2655 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LGSTORE1 | PSZ-AC_1:1 | 2.4153 | 2.4153 | 2.4153 | 0.5309 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE1 | PSZ-AC_2:2 | 1.2272 | 1.2272 | 1.2272 | 0.2655 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE2 | PSZ-AC_3:3 | 1.2354 | 1.2354 | 1.2354 | 0.2655 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE3 | PSZ-AC_4:4 | 1.2384 | 1.2384 | 1.2384 | 0.2655 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE4 | PSZ-AC_5:5 | 1.2456 | 1.2456 | 1.2456 | 0.2655 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
LGSTORE2 | PSZ-AC_6:6 | 2.3064 | 2.3064 | 2.3064 | 0.5309 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE5 | PSZ-AC_7:7 | 1.2641 | 1.2641 | 1.2641 | 0.2655 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE6 | PSZ-AC_8:8 | 1.2629 | 1.2629 | 1.2629 | 0.2655 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE7 | PSZ-AC_9:9 | 1.2741 | 1.2741 | 1.2741 | 0.2655 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE8 | PSZ-AC_10:10 | 1.4494 | 1.4494 | 1.4494 | 0.2655 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 2.4153 | 2.4153 | 2.4153 | 2.4153 | 0.5309 | 1.0000 |
PSZ-AC_2:2 | 1.2272 | 1.2272 | 1.2272 | 1.2272 | 0.2655 | 1.0000 |
PSZ-AC_3:3 | 1.2354 | 1.2354 | 1.2354 | 1.2354 | 0.2655 | 1.0000 |
PSZ-AC_4:4 | 1.2384 | 1.2384 | 1.2384 | 1.2384 | 0.2655 | 1.0000 |
PSZ-AC_5:5 | 1.2456 | 1.2456 | 1.2456 | 1.2456 | 0.2655 | 1.0000 |
PSZ-AC_6:6 | 2.3064 | 2.3064 | 2.3064 | 2.3064 | 0.5309 | 1.0000 |
PSZ-AC_7:7 | 1.2641 | 1.2641 | 1.2641 | 1.2641 | 0.2655 | 1.0000 |
PSZ-AC_8:8 | 1.2629 | 1.2629 | 1.2629 | 1.2629 | 0.2655 | 1.0000 |
PSZ-AC_9:9 | 1.2741 | 1.2741 | 1.2741 | 1.2741 | 0.2655 | 1.0000 |
PSZ-AC_10:10 | 1.4494 | 1.4494 | 1.4494 | 1.4494 | 0.2655 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LGSTORE1 | PSZ-AC_1:1 | 2.4153 | 2.4153 | 2.4153 | 0.5309 | 0.2198 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE1 | PSZ-AC_2:2 | 1.2272 | 1.2272 | 1.2272 | 0.2655 | 0.2163 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE2 | PSZ-AC_3:3 | 1.2354 | 1.2354 | 1.2354 | 0.2655 | 0.2149 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE3 | PSZ-AC_4:4 | 1.2384 | 1.2384 | 1.2384 | 0.2655 | 0.2144 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE4 | PSZ-AC_5:5 | 1.2456 | 1.2456 | 1.2456 | 0.2655 | 0.2131 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
LGSTORE2 | PSZ-AC_6:6 | 2.3064 | 2.3064 | 2.3064 | 0.5309 | 0.2302 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE5 | PSZ-AC_7:7 | 1.2641 | 1.2641 | 1.2641 | 0.2655 | 0.2100 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE6 | PSZ-AC_8:8 | 1.2629 | 1.2629 | 1.2629 | 0.2655 | 0.2102 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE7 | PSZ-AC_9:9 | 1.2741 | 1.2741 | 1.2741 | 0.2655 | 0.2083 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE8 | PSZ-AC_10:10 | 1.4494 | 1.4494 | 1.4494 | 0.2655 | 0.1832 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 2.4153 | 2.4153 | 2.4153 | 2.4153 | 0.5309 | 1.0000 |
PSZ-AC_2:2 | 1.2272 | 1.2272 | 1.2272 | 1.2272 | 0.2655 | 1.0000 |
PSZ-AC_3:3 | 1.2354 | 1.2354 | 1.2354 | 1.2354 | 0.2655 | 1.0000 |
PSZ-AC_4:4 | 1.2384 | 1.2384 | 1.2384 | 1.2384 | 0.2655 | 1.0000 |
PSZ-AC_5:5 | 1.2456 | 1.2456 | 1.2456 | 1.2456 | 0.2655 | 1.0000 |
PSZ-AC_6:6 | 2.3064 | 2.3064 | 2.3064 | 2.3064 | 0.5309 | 1.0000 |
PSZ-AC_7:7 | 1.2641 | 1.2641 | 1.2641 | 1.2641 | 0.2655 | 1.0000 |
PSZ-AC_8:8 | 1.2629 | 1.2629 | 1.2629 | 1.2629 | 0.2655 | 1.0000 |
PSZ-AC_9:9 | 1.2741 | 1.2741 | 1.2741 | 1.2741 | 0.2655 | 1.0000 |
PSZ-AC_10:10 | 1.4494 | 1.4494 | 1.4494 | 1.4494 | 0.2655 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2020-06-03 19:19:07
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Rochester International Arpt MN USA TMY3 WMO#=726440 |
Total gross floor area [m2] | 2090.32 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
LGSTORE1 | 348.39 | 348.39 | 0.00 | 112.00 |
SMSTORE1 | 174.19 | 174.19 | 0.00 | 112.00 |
SMSTORE2 | 174.19 | 174.19 | 0.00 | 84.29 |
SMSTORE3 | 174.19 | 174.19 | 0.00 | 84.29 |
SMSTORE4 | 174.19 | 174.19 | 0.00 | 84.29 |
LGSTORE2 | 348.39 | 348.39 | 0.00 | 77.29 |
SMSTORE5 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE6 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE7 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE8 | 174.19 | 174.19 | 0.00 | 77.29 |
Totals | 2090.32 | 2090.32 | 0.00 |
Data | |
Number of hours heating loads not met | 8.17 |
Number of hours cooling loads not met | 0.00 |
Number of hours not met | 8.17 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Fuel Use [GJ] | Additional Fuel Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- Not Subdivided | 0.00 | 0.00 | 1353.87 | 503448.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- Not Subdivided | 140.34 | 82720.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 708.74 | 43732.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 166.80 | 10625.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 128.72 | 8089.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 287.44 | 16727.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 66.36 | 11887.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 128.72 | 1498.40 |
Natural Gas | 0.00 | 1353.87 |
Additional | 0.00 | 0.00 |
Total | 128.72 | 2852.27 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 339.06 |
Space Heating | 0.00 |
Space Cooling | 67.14 |
Fans (All) | 137.51 |
Service Water Heating | 31.75 |
Receptacle Equipment | 61.58 |
Miscellaneous (All) | 716.83 |
Subtotal | 716.83 |
Natural Gas [MJ/m2] | |
Space Heating | 647.68 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 647.68 |
Subtotal | 647.68 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 24.85 |
Space Heating | 47.47 |
Space Cooling | 4.92 |
Fans (All) | 10.08 |
Service Water Heating | 2.33 |
Receptacle Equipment | 4.51 |
Miscellaneous | 5.85 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
TYPE1_OCC_SCH | 1630. | 5840. |
TYPE2_OCC_SCH | 995. | 4429. |
TYPE3_OCC_SCH | 1709. | 4064. |
TYPE1_LIGHT_SCH | 5131. | 8760. |
TYPE2_LIGHT_SCH | 4096. | 8760. |
TYPE3_LIGHT_SCH | 3767. | 8760. |
TYPE1_EQUIP_SCH | 4888. | 8760. |
TYPE2_EQUIP_SCH | 3911. | 8760. |
TYPE3_EQUIP_SCH | 3600. | 8760. |
TYPE1_INFIL_SCH | 4302. | 8760. |
TYPE2_INFIL_SCH | 5164. | 8760. |
TYPE3_INFIL_SCH | 5438. | 8760. |
INFIL_DOOR_OPENING_SCH | 2505. | 4380. |
TYPE1_MINOA_MOTORIZEDDAMPER_SCH | 5579. | 5579. |
TYPE2_MINOA_MOTORIZEDDAMPER_SCH | 4429. | 4429. |
TYPE3_MINOA_MOTORIZEDDAMPER_SCH | 4064. | 4064. |
TYPE1_SWH_SCH | 2063. | 6048. |
TYPE2_SWH_SCH | 1831. | 4429. |
TYPE3_SWH_SCH | 1733. | 4064. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 7118. | 8760. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 5839. | 5839. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 7300. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
TYPE1_HTGSETP_SCH_NO_OPTIMUM | LGSTORE1 DUALSPSCHED | January | 21.11 | 365 | 21.11 | 365 |
TYPE1_CLGSETP_SCH_NO_OPTIMUM | LGSTORE1 DUALSPSCHED | July | 23.89 | 365 | 23.89 | 365 |
TYPE2_HTGSETP_SCH_NO_OPTIMUM | SMSTORE2 DUALSPSCHED | January | 21.11 | 365 | 15.56 | 365 |
TYPE2_CLGSETP_SCH_NO_OPTIMUM | SMSTORE2 DUALSPSCHED | July | 23.89 | 365 | 29.44 | 365 |
TYPE3_HTGSETP_SCH_NO_OPTIMUM | LGSTORE2 DUALSPSCHED | January | 21.11 | 365 | 15.56 | 365 |
TYPE3_CLGSETP_SCH_NO_OPTIMUM | LGSTORE2 DUALSPSCHED | July | 23.89 | 365 | 29.44 | 365 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Meter
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.360299E+12 |
February | 0.000 | 0.257047E+12 |
March | 0.000 | 0.165279E+12 |
April | 0.000 | 0.825589E+11 |
May | 0.000 | 0.613625E+10 |
June | 0.000 | 0.133351E+10 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.562622E+10 |
October | 0.000 | 0.403581E+11 |
November | 0.000 | 0.154709E+12 |
December | 0.000 | 0.280522E+12 |
Annual Sum or Average | 0.135387E+13 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.360299E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Meter
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.360299E+12 |
February | 0.000 | 0.257047E+12 |
March | 0.000 | 0.165279E+12 |
April | 0.000 | 0.825589E+11 |
May | 0.000 | 0.613625E+10 |
June | 0.000 | 0.133351E+10 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.562622E+10 |
October | 0.000 | 0.403581E+11 |
November | 0.000 | 0.154709E+12 |
December | 0.000 | 0.280522E+12 |
Annual Sum or Average | 0.135387E+13 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.360299E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2006
For: Meter
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.360299E+12 |
February | 0.000 | 0.257047E+12 |
March | 0.000 | 0.165279E+12 |
April | 0.000 | 0.825589E+11 |
May | 0.000 | 0.613625E+10 |
June | 0.000 | 0.133351E+10 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.562622E+10 |
October | 0.000 | 0.403581E+11 |
November | 0.000 | 0.154709E+12 |
December | 0.000 | 0.280522E+12 |
Annual Sum or Average | 0.135387E+13 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.360299E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Meter
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.360299E+12 |
February | 0.000 | 0.257047E+12 |
March | 0.000 | 0.165279E+12 |
April | 0.000 | 0.825589E+11 |
May | 0.000 | 0.613625E+10 |
June | 0.000 | 0.133351E+10 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.562622E+10 |
October | 0.000 | 0.403581E+11 |
November | 0.000 | 0.154709E+12 |
December | 0.000 | 0.280522E+12 |
Annual Sum or Average | 0.135387E+13 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.360299E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTRIPMALL
For: Meter
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.360299E+12 |
February | 0.000 | 0.257047E+12 |
March | 0.000 | 0.165279E+12 |
April | 0.000 | 0.825589E+11 |
May | 0.000 | 0.613625E+10 |
June | 0.000 | 0.133351E+10 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.562622E+10 |
October | 0.000 | 0.403581E+11 |
November | 0.000 | 0.154709E+12 |
December | 0.000 | 0.280522E+12 |
Annual Sum or Average | 0.135387E+13 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.360299E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.360299E+12 |
February | 0.000 | 0.257047E+12 |
March | 0.000 | 0.165279E+12 |
April | 0.000 | 0.825589E+11 |
May | 0.000 | 0.613625E+10 |
June | 0.000 | 0.133351E+10 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.562622E+10 |
October | 0.000 | 0.403581E+11 |
November | 0.000 | 0.154709E+12 |
December | 0.000 | 0.280522E+12 |
Annual Sum or Average | 0.135387E+13 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.360299E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.360299E+12 |
February | 0.000 | 0.257047E+12 |
March | 0.000 | 0.165279E+12 |
April | 0.000 | 0.825589E+11 |
May | 0.000 | 0.613625E+10 |
June | 0.000 | 0.133351E+10 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.562622E+10 |
October | 0.000 | 0.403581E+11 |
November | 0.000 | 0.154709E+12 |
December | 0.000 | 0.280522E+12 |
Annual Sum or Average | 0.135387E+13 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.360299E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 6A
For: Meter
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.360299E+12 |
February | 0.000 | 0.257047E+12 |
March | 0.000 | 0.165279E+12 |
April | 0.000 | 0.825589E+11 |
May | 0.000 | 0.613625E+10 |
June | 0.000 | 0.133351E+10 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.562622E+10 |
October | 0.000 | 0.403581E+11 |
November | 0.000 | 0.154709E+12 |
December | 0.000 | 0.280522E+12 |
Annual Sum or Average | 0.135387E+13 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.360299E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_ROCHESTER
For: Meter
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.360299E+12 |
February | 0.000 | 0.257047E+12 |
March | 0.000 | 0.165279E+12 |
April | 0.000 | 0.825589E+11 |
May | 0.000 | 0.613625E+10 |
June | 0.000 | 0.133351E+10 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.562622E+10 |
October | 0.000 | 0.403581E+11 |
November | 0.000 | 0.154709E+12 |
December | 0.000 | 0.280522E+12 |
Annual Sum or Average | 0.135387E+13 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.360299E+12 |
Report: ZoneCoolingSummaryMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.408254E+09 | 24279.43 | 06-JAN-00:01 | -25.1 | -25.3 | 0.567657E+09 | 680.12 | 21-JAN-13:09 | -5.9 | -6.6 |
February | 0.648394E+09 | 28834.75 | 03-FEB-00:01 | -32.8 | -32.9 | 0.512552E+09 | 680.12 | 24-FEB-13:09 | 6.88 | 4.27 |
March | 0.171296E+10 | 15733.43 | 07-MAR-20:52 | -10.6 | -11.7 | 0.574189E+09 | 898.99 | 19-MAR-17:00 | 16.10 | 12.47 |
April | 0.423458E+10 | 13648.23 | 16-APR-16:04 | 28.80 | 20.53 | 0.599523E+09 | 898.97 | 16-APR-16:30 | 28.60 | 20.42 |
May | 0.830349E+10 | 14541.98 | 31-MAY-15:00 | 30.00 | 19.68 | 0.719385E+09 | 899.04 | 14-MAY-17:00 | 20.00 | 16.10 |
June | 0.142214E+11 | 29496.57 | 30-JUN-07:02 | 23.07 | 20.54 | 0.710064E+09 | 898.98 | 23-JUN-12:09 | 23.40 | 14.77 |
July | 0.174155E+11 | 33464.44 | 04-JUL-07:02 | 20.87 | 18.53 | 0.753561E+09 | 899.03 | 09-JUL-12:20 | 19.47 | 17.74 |
August | 0.175991E+11 | 30423.67 | 23-AUG-07:03 | 18.40 | 17.23 | 0.743016E+09 | 899.04 | 06-AUG-17:19 | 18.67 | 11.74 |
September | 0.135751E+11 | 34887.81 | 12-SEP-07:02 | 15.93 | 14.77 | 0.698575E+09 | 899.04 | 15-SEP-12:09 | 20.18 | 12.84 |
October | 0.652269E+10 | 9697.56 | 27-OCT-23:25 | -0.4 | -1.8 | 0.625626E+09 | 899.03 | 20-OCT-12:00 | 21.80 | 12.59 |
November | 0.278319E+10 | 17367.47 | 25-NOV-00:01 | -13.4 | -13.7 | 0.570754E+09 | 883.13 | 03-NOV-12:00 | 15.60 | 11.01 |
December | 0.686372E+09 | 23004.01 | 09-DEC-00:01 | -22.8 | -23.0 | 0.570528E+09 | 680.12 | 16-DEC-13:20 | -4.4 | -5.9 |
Annual Sum or Average | 0.881111E+11 | 0.764543E+10 | ||||||||
Minimum of Months | 0.408254E+09 | 9697.56 | -32.8 | -32.9 | 0.512552E+09 | 680.12 | -5.9 | -6.6 | ||
Maximum of Months | 0.175991E+11 | 34887.81 | 30.00 | 20.54 | 0.753561E+09 | 899.04 | 28.60 | 20.42 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 74875013.70 | 8993.01 | 10-JAN-08:04 | -11.9 | -12.2 | 0.285557E+09 | 351.75 | 01-JAN-18:00 | -1.1 | -1.4 |
February | 0.206437E+09 | 9070.96 | 15-FEB-08:04 | -12.1 | -12.6 | 0.260577E+09 | 376.34 | 20-FEB-18:00 | -1.1 | -3.4 |
March | 0.769146E+09 | 8374.71 | 13-MAR-07:04 | -9.6 | -10.6 | 0.296364E+09 | 449.50 | 19-MAR-16:10 | 18.80 | 13.88 |
April | 0.214787E+10 | 7477.58 | 03-APR-07:04 | -6.6 | -7.4 | 0.310429E+09 | 449.50 | 30-APR-17:40 | 15.60 | 8.94 |
May | 0.475048E+10 | 7824.43 | 31-MAY-15:00 | 30.00 | 19.68 | 0.364043E+09 | 449.50 | 13-MAY-12:09 | 16.37 | 15.31 |
June | 0.772936E+10 | 18719.20 | 28-JUN-07:03 | 21.57 | 18.56 | 0.356882E+09 | 449.49 | 23-JUN-12:09 | 23.40 | 14.77 |
July | 0.929570E+10 | 19109.51 | 28-JUL-07:03 | 20.87 | 18.05 | 0.376754E+09 | 449.49 | 23-JUL-16:19 | 22.80 | 15.34 |
August | 0.928987E+10 | 18451.93 | 14-AUG-07:02 | 16.57 | 16.08 | 0.371460E+09 | 449.50 | 06-AUG-17:19 | 18.67 | 11.74 |
September | 0.698872E+10 | 19377.80 | 12-SEP-07:02 | 15.93 | 14.77 | 0.352815E+09 | 449.50 | 24-SEP-17:19 | 13.17 | 6.81 |
October | 0.287650E+10 | 5492.28 | 26-OCT-07:02 | 0.18 | -1.1 | 0.327282E+09 | 449.52 | 20-OCT-12:00 | 21.80 | 12.59 |
November | 0.113034E+10 | 9489.29 | 24-NOV-08:04 | -13.6 | -14.0 | 0.294758E+09 | 449.48 | 05-NOV-17:40 | 9.23 | 7.03 |
December | 0.142767E+09 | 9629.39 | 07-DEC-08:04 | -14.4 | -15.2 | 0.290167E+09 | 380.56 | 03-DEC-18:00 | 0.60 | -0.6 |
Annual Sum or Average | 0.454021E+11 | 0.388709E+10 | ||||||||
Minimum of Months | 74875013.70 | 5492.28 | -14.4 | -15.2 | 0.260577E+09 | 351.75 | -1.1 | -3.4 | ||
Maximum of Months | 0.929570E+10 | 19377.80 | 30.00 | 19.68 | 0.376754E+09 | 449.52 | 23.40 | 15.34 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 21301655.12 | 9464.04 | 21-JAN-07:05 | -13.9 | -14.2 | 0.169143E+09 | 340.06 | 21-JAN-13:09 | -5.9 | -6.6 |
February | 51064177.08 | 7907.03 | 16-FEB-07:05 | -18.8 | -19.1 | 0.153637E+09 | 340.06 | 25-FEB-13:09 | 4.50 | 2.48 |
March | 0.332460E+09 | 9094.11 | 06-MAR-07:05 | -12.7 | -13.3 | 0.175585E+09 | 340.06 | 11-MAR-13:09 | 3.98 | 1.28 |
April | 0.118945E+10 | 7003.13 | 04-APR-06:04 | -5.5 | -6.1 | 0.177909E+09 | 449.46 | 15-APR-12:09 | 27.88 | 20.23 |
May | 0.260489E+10 | 7053.17 | 31-MAY-15:00 | 30.00 | 19.68 | 0.214616E+09 | 449.50 | 13-MAY-12:09 | 16.37 | 15.31 |
June | 0.508050E+10 | 16753.90 | 30-JUN-06:02 | 21.38 | 19.38 | 0.216760E+09 | 449.47 | 17-JUN-12:09 | 26.02 | 17.80 |
July | 0.601851E+10 | 17498.89 | 28-JUL-06:03 | 18.27 | 17.22 | 0.224024E+09 | 449.49 | 22-JUL-12:09 | 19.50 | 14.17 |
August | 0.623721E+10 | 16135.82 | 23-AUG-06:03 | 17.88 | 17.07 | 0.230054E+09 | 449.49 | 19-AUG-12:00 | 19.40 | 18.26 |
September | 0.452072E+10 | 18274.49 | 11-SEP-06:03 | 19.50 | 17.29 | 0.206833E+09 | 449.49 | 23-SEP-12:09 | 19.60 | 10.56 |
October | 0.160496E+10 | 6242.62 | 23-OCT-06:04 | -3.0 | -3.9 | 0.181842E+09 | 449.50 | 21-OCT-12:09 | 19.02 | 12.94 |
November | 0.661524E+09 | 8330.30 | 25-NOV-07:05 | -17.9 | -18.1 | 0.167229E+09 | 398.36 | 04-NOV-12:00 | 13.90 | 6.79 |
December | 19395936.05 | 8634.30 | 27-DEC-07:04 | -10.3 | -10.7 | 0.168940E+09 | 340.06 | 16-DEC-13:20 | -4.4 | -5.9 |
Annual Sum or Average | 0.283420E+11 | 0.228657E+10 | ||||||||
Minimum of Months | 19395936.05 | 6242.62 | -18.8 | -19.1 | 0.153637E+09 | 340.06 | -5.9 | -6.6 | ||
Maximum of Months | 0.623721E+10 | 18274.49 | 30.00 | 19.68 | 0.230054E+09 | 449.50 | 27.88 | 20.23 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 14404331.20 | 9242.42 | 21-JAN-07:05 | -13.9 | -14.2 | 0.169143E+09 | 340.06 | 21-JAN-13:09 | -5.9 | -6.6 |
February | 37761002.25 | 7525.97 | 09-FEB-07:03 | -6.0 | -6.2 | 0.153637E+09 | 340.06 | 25-FEB-13:09 | 4.50 | 2.48 |
March | 0.267075E+09 | 9152.51 | 06-MAR-07:05 | -12.7 | -13.3 | 0.175284E+09 | 340.06 | 11-MAR-13:09 | 3.98 | 1.28 |
April | 0.107276E+10 | 7448.33 | 03-APR-06:05 | -7.1 | -7.8 | 0.177373E+09 | 449.46 | 15-APR-12:09 | 27.88 | 20.23 |
May | 0.238407E+10 | 6923.67 | 31-MAY-15:00 | 30.00 | 19.68 | 0.213122E+09 | 449.50 | 13-MAY-12:09 | 16.37 | 15.31 |
June | 0.494341E+10 | 16778.94 | 30-JUN-06:02 | 21.38 | 19.38 | 0.216254E+09 | 449.47 | 17-JUN-12:09 | 26.02 | 17.80 |
July | 0.592313E+10 | 17085.86 | 28-JUL-06:03 | 18.27 | 17.22 | 0.224007E+09 | 449.49 | 22-JUL-12:09 | 19.50 | 14.17 |
August | 0.612674E+10 | 16141.52 | 23-AUG-06:03 | 17.88 | 17.07 | 0.230035E+09 | 449.49 | 19-AUG-12:00 | 19.40 | 18.26 |
September | 0.436329E+10 | 18307.53 | 11-SEP-06:03 | 19.50 | 17.29 | 0.206176E+09 | 449.49 | 23-SEP-12:09 | 19.60 | 10.56 |
October | 0.136937E+10 | 6466.84 | 23-OCT-06:04 | -3.0 | -3.9 | 0.180477E+09 | 449.50 | 21-OCT-12:39 | 19.37 | 13.16 |
November | 0.559928E+09 | 9456.47 | 24-NOV-07:05 | -13.9 | -14.3 | 0.166328E+09 | 389.97 | 04-NOV-12:00 | 13.90 | 6.79 |
December | 14950660.81 | 8705.16 | 28-DEC-07:05 | -17.5 | -17.8 | 0.168940E+09 | 340.06 | 16-DEC-13:20 | -4.4 | -5.9 |
Annual Sum or Average | 0.270769E+11 | 0.228078E+10 | ||||||||
Minimum of Months | 14404331.20 | 6466.84 | -17.5 | -17.8 | 0.153637E+09 | 340.06 | -5.9 | -6.6 | ||
Maximum of Months | 0.612674E+10 | 18307.53 | 30.00 | 19.68 | 0.230035E+09 | 449.50 | 27.88 | 20.23 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 14210361.28 | 9480.58 | 21-JAN-07:05 | -13.9 | -14.2 | 0.169143E+09 | 340.06 | 21-JAN-13:09 | -5.9 | -6.6 |
February | 26664140.35 | 7943.11 | 18-FEB-07:05 | -16.5 | -16.8 | 0.153637E+09 | 340.06 | 25-FEB-13:09 | 4.50 | 2.48 |
March | 0.215805E+09 | 8502.99 | 06-MAR-07:05 | -12.7 | -13.3 | 0.175069E+09 | 340.06 | 11-MAR-13:09 | 3.98 | 1.28 |
April | 0.970273E+09 | 7309.86 | 01-APR-06:04 | -5.8 | -6.2 | 0.176949E+09 | 449.46 | 15-APR-12:09 | 27.88 | 20.23 |
May | 0.218644E+10 | 6780.66 | 31-MAY-15:00 | 30.00 | 19.68 | 0.211724E+09 | 449.50 | 13-MAY-12:20 | 15.53 | 14.51 |
June | 0.476332E+10 | 16758.05 | 30-JUN-06:02 | 21.38 | 19.38 | 0.215829E+09 | 449.47 | 17-JUN-12:09 | 26.02 | 17.80 |
July | 0.575201E+10 | 16500.55 | 03-JUL-06:02 | 19.08 | 17.91 | 0.223980E+09 | 449.49 | 22-JUL-12:09 | 19.50 | 14.17 |
August | 0.595311E+10 | 16118.76 | 23-AUG-06:03 | 17.88 | 17.07 | 0.230009E+09 | 449.49 | 19-AUG-12:00 | 19.40 | 18.26 |
September | 0.420245E+10 | 18079.19 | 11-SEP-06:03 | 19.50 | 17.29 | 0.205674E+09 | 449.49 | 23-SEP-12:09 | 19.60 | 10.56 |
October | 0.119285E+10 | 6589.52 | 23-OCT-06:04 | -3.0 | -3.9 | 0.179590E+09 | 449.50 | 21-OCT-12:00 | 19.60 | 13.31 |
November | 0.484346E+09 | 7831.73 | 22-NOV-07:04 | -7.7 | -8.8 | 0.165800E+09 | 384.00 | 04-NOV-12:00 | 13.90 | 6.79 |
December | 14241918.47 | 8412.95 | 04-DEC-07:04 | -9.7 | -10.0 | 0.168940E+09 | 340.06 | 16-DEC-13:30 | -4.2 | -5.6 |
Annual Sum or Average | 0.257757E+11 | 0.227634E+10 | ||||||||
Minimum of Months | 14210361.28 | 6589.52 | -16.5 | -16.8 | 0.153637E+09 | 340.06 | -5.9 | -6.6 | ||
Maximum of Months | 0.595311E+10 | 18079.19 | 30.00 | 19.68 | 0.230009E+09 | 449.50 | 27.88 | 20.23 |
Report: ZoneCoolingSummaryMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 195001.52 | 248.01 | 13-JAN-12:00 | 3.90 | 1.49 | 0.578270E+09 | 906.81 | 21-JAN-15:00 | -4.4 | -5.3 |
February | 6758008.33 | 1086.26 | 24-FEB-12:00 | 6.10 | 3.15 | 0.526487E+09 | 906.81 | 18-FEB-15:09 | -6.7 | -7.5 |
March | 0.233373E+09 | 3215.07 | 24-MAR-17:05 | 9.82 | 5.11 | 0.600508E+09 | 1074.47 | 25-MAR-14:00 | 18.90 | 10.41 |
April | 0.145903E+10 | 10715.74 | 18-APR-14:10 | 28.30 | 20.64 | 0.605325E+09 | 1198.55 | 15-APR-14:09 | 29.50 | 20.38 |
May | 0.352888E+10 | 12348.96 | 31-MAY-15:00 | 30.00 | 19.68 | 0.716769E+09 | 1198.68 | 06-MAY-14:00 | 21.10 | 11.56 |
June | 0.816692E+10 | 29503.52 | 12-JUN-07:03 | 18.48 | 17.31 | 0.737131E+09 | 1198.65 | 17-JUN-14:09 | 24.18 | 18.98 |
July | 0.991285E+10 | 31809.91 | 03-JUL-07:03 | 20.37 | 18.84 | 0.766660E+09 | 1198.64 | 22-JUL-14:00 | 20.60 | 14.31 |
August | 0.102818E+11 | 26879.30 | 23-AUG-07:03 | 18.40 | 17.23 | 0.788991E+09 | 1198.69 | 12-AUG-14:50 | 22.25 | 17.58 |
September | 0.706030E+10 | 32925.00 | 11-SEP-07:03 | 20.37 | 17.94 | 0.704150E+09 | 1198.67 | 23-SEP-14:00 | 20.60 | 11.38 |
October | 0.170811E+10 | 6239.38 | 22-OCT-09:03 | 6.70 | 5.35 | 0.609892E+09 | 1198.66 | 21-OCT-14:00 | 21.10 | 14.39 |
November | 0.709500E+09 | 6863.58 | 15-NOV-20:23 | 4.45 | 2.95 | 0.562822E+09 | 1054.42 | 04-NOV-14:00 | 14.40 | 6.79 |
December | 529792.48 | 526.46 | 02-DEC-12:00 | 5.00 | 2.78 | 0.579250E+09 | 906.82 | 16-DEC-15:09 | -2.8 | -4.1 |
Annual Sum or Average | 0.430682E+11 | 0.777626E+10 | ||||||||
Minimum of Months | 195001.52 | 248.01 | 3.90 | 1.49 | 0.526487E+09 | 906.81 | -6.7 | -7.5 | ||
Maximum of Months | 0.102818E+11 | 32925.00 | 30.00 | 20.64 | 0.788991E+09 | 1198.69 | 29.50 | 20.38 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 5442176.62 | 8664.30 | 18-JAN-08:05 | -12.3 | -12.7 | 0.289135E+09 | 453.41 | 21-JAN-15:00 | -4.4 | -5.3 |
February | 8762783.15 | 7299.10 | 17-FEB-08:05 | -6.9 | -7.7 | 0.263243E+09 | 453.41 | 18-FEB-15:09 | -6.7 | -7.5 |
March | 0.109190E+09 | 7658.28 | 08-MAR-08:05 | -9.0 | -10.3 | 0.300253E+09 | 535.16 | 25-MAR-14:00 | 18.90 | 10.41 |
April | 0.701862E+09 | 7299.50 | 03-APR-07:05 | -6.6 | -7.4 | 0.302484E+09 | 599.27 | 15-APR-14:09 | 29.50 | 20.38 |
May | 0.163509E+10 | 6462.01 | 31-MAY-15:00 | 30.00 | 19.68 | 0.356975E+09 | 599.33 | 06-MAY-14:00 | 21.10 | 11.56 |
June | 0.413149E+10 | 16847.39 | 30-JUN-07:02 | 23.07 | 20.54 | 0.368226E+09 | 599.32 | 17-JUN-14:09 | 24.18 | 18.98 |
July | 0.506465E+10 | 16240.92 | 02-JUL-08:62 | 24.18 | 20.57 | 0.383304E+09 | 599.31 | 22-JUL-14:00 | 20.60 | 14.31 |
August | 0.526224E+10 | 13208.65 | 03-AUG-07:02 | 24.18 | 22.73 | 0.394433E+09 | 599.32 | 19-AUG-14:09 | 18.98 | 18.58 |
September | 0.356445E+10 | 16004.74 | 11-SEP-07:03 | 20.37 | 17.94 | 0.351535E+09 | 599.33 | 23-SEP-14:00 | 20.60 | 11.38 |
October | 0.756620E+09 | 5629.41 | 23-OCT-07:03 | -1.2 | -2.5 | 0.304884E+09 | 599.33 | 21-OCT-14:09 | 20.52 | 14.03 |
November | 0.314072E+09 | 7150.64 | 12-NOV-09:04 | -5.3 | -6.5 | 0.281446E+09 | 526.05 | 04-NOV-14:00 | 14.40 | 6.79 |
December | 11194859.30 | 9026.95 | 25-DEC-09:05 | -12.5 | -12.9 | 0.289624E+09 | 453.41 | 16-DEC-15:09 | -2.8 | -4.1 |
Annual Sum or Average | 0.215651E+11 | 0.388554E+10 | ||||||||
Minimum of Months | 5442176.62 | 5629.41 | -12.5 | -12.9 | 0.263243E+09 | 453.41 | -6.7 | -7.5 | ||
Maximum of Months | 0.526224E+10 | 16847.39 | 30.00 | 22.73 | 0.394433E+09 | 599.33 | 29.50 | 20.38 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 4879732.12 | 8674.58 | 18-JAN-08:05 | -12.3 | -12.7 | 0.289135E+09 | 453.41 | 21-JAN-15:00 | -4.4 | -5.3 |
February | 8116791.27 | 7334.12 | 17-FEB-08:05 | -6.9 | -7.7 | 0.263243E+09 | 453.41 | 18-FEB-15:09 | -6.7 | -7.5 |
March | 97871817.68 | 8139.53 | 13-MAR-07:05 | -9.6 | -10.6 | 0.300117E+09 | 532.61 | 25-MAR-14:00 | 18.90 | 10.41 |
April | 0.664559E+09 | 7017.33 | 03-APR-07:05 | -6.6 | -7.4 | 0.302119E+09 | 599.27 | 15-APR-14:09 | 29.50 | 20.38 |
May | 0.152688E+10 | 6346.28 | 31-MAY-15:00 | 30.00 | 19.68 | 0.354888E+09 | 599.33 | 06-MAY-14:00 | 21.10 | 11.56 |
June | 0.402611E+10 | 16799.63 | 30-JUN-07:02 | 23.07 | 20.54 | 0.367739E+09 | 599.32 | 17-JUN-14:09 | 24.18 | 18.98 |
July | 0.496431E+10 | 16191.05 | 02-JUL-08:62 | 24.18 | 20.57 | 0.383266E+09 | 599.31 | 22-JUL-14:00 | 20.60 | 14.31 |
August | 0.516142E+10 | 13163.91 | 03-AUG-07:02 | 24.18 | 22.73 | 0.394415E+09 | 599.32 | 19-AUG-14:09 | 18.98 | 18.58 |
September | 0.347822E+10 | 15399.09 | 11-SEP-07:03 | 20.37 | 17.94 | 0.351001E+09 | 599.33 | 23-SEP-14:00 | 20.60 | 11.38 |
October | 0.709397E+09 | 5706.01 | 23-OCT-07:03 | -1.2 | -2.5 | 0.304370E+09 | 599.33 | 21-OCT-14:09 | 20.52 | 14.03 |
November | 0.294834E+09 | 6863.88 | 29-NOV-08:05 | -5.5 | -6.3 | 0.281250E+09 | 522.97 | 04-NOV-14:00 | 14.40 | 6.79 |
December | 10720354.08 | 8040.88 | 27-DEC-08:05 | -11.6 | -11.9 | 0.289624E+09 | 453.41 | 16-DEC-15:09 | -2.8 | -4.1 |
Annual Sum or Average | 0.209473E+11 | 0.388117E+10 | ||||||||
Minimum of Months | 4879732.12 | 5706.01 | -12.3 | -12.7 | 0.263243E+09 | 453.41 | -6.7 | -7.5 | ||
Maximum of Months | 0.516142E+10 | 16799.63 | 30.00 | 22.73 | 0.394415E+09 | 599.33 | 29.50 | 20.38 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 4522921.44 | 8825.38 | 10-JAN-08:05 | -11.9 | -12.2 | 0.289135E+09 | 453.41 | 21-JAN-15:00 | -4.4 | -5.3 |
February | 8352439.72 | 8856.58 | 15-FEB-08:05 | -12.1 | -12.6 | 0.263243E+09 | 453.41 | 18-FEB-15:09 | -6.7 | -7.5 |
March | 63649752.92 | 8118.48 | 13-MAR-07:05 | -9.6 | -10.6 | 0.299712E+09 | 523.26 | 25-MAR-14:00 | 18.90 | 10.41 |
April | 0.555987E+09 | 7316.35 | 03-APR-07:05 | -6.6 | -7.4 | 0.301028E+09 | 599.28 | 15-APR-14:09 | 29.50 | 20.38 |
May | 0.126574E+10 | 6075.50 | 31-MAY-15:00 | 30.00 | 19.68 | 0.349898E+09 | 599.33 | 06-MAY-14:00 | 21.10 | 11.56 |
June | 0.376647E+10 | 16607.88 | 30-JUN-07:02 | 23.07 | 20.54 | 0.366554E+09 | 599.32 | 17-JUN-14:09 | 24.18 | 18.98 |
July | 0.472909E+10 | 15981.73 | 04-JUL-08:62 | 22.30 | 19.60 | 0.383139E+09 | 599.31 | 22-JUL-14:00 | 20.60 | 14.31 |
August | 0.493900E+10 | 13156.11 | 03-AUG-07:02 | 24.18 | 22.73 | 0.394359E+09 | 599.32 | 19-AUG-14:09 | 18.98 | 18.58 |
September | 0.329007E+10 | 13436.92 | 11-SEP-07:03 | 20.37 | 17.94 | 0.349928E+09 | 599.33 | 23-SEP-14:00 | 20.60 | 11.38 |
October | 0.579228E+09 | 5982.12 | 23-OCT-07:03 | -1.2 | -2.5 | 0.303096E+09 | 599.33 | 21-OCT-14:09 | 20.52 | 14.03 |
November | 0.243362E+09 | 8179.35 | 21-NOV-08:05 | -10.0 | -10.7 | 0.280819E+09 | 515.70 | 04-NOV-14:00 | 14.40 | 6.79 |
December | 10936307.33 | 8959.69 | 25-DEC-09:05 | -12.5 | -12.9 | 0.289624E+09 | 453.41 | 16-DEC-15:09 | -2.8 | -4.1 |
Annual Sum or Average | 0.194564E+11 | 0.387054E+10 | ||||||||
Minimum of Months | 4522921.44 | 5982.12 | -12.5 | -12.9 | 0.263243E+09 | 453.41 | -6.7 | -7.5 | ||
Maximum of Months | 0.493900E+10 | 16607.88 | 30.00 | 22.73 | 0.394359E+09 | 599.33 | 29.50 | 20.38 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 1858098.71 | 6861.98 | 17-JAN-08:05 | -5.9 | -6.1 | 0.289135E+09 | 453.41 | 21-JAN-15:00 | -4.4 | -5.3 |
February | 2746818.66 | 6503.50 | 13-FEB-08:05 | -4.3 | -5.1 | 0.263244E+09 | 453.41 | 18-FEB-15:09 | -6.7 | -7.5 |
March | 6038336.87 | 5147.26 | 09-MAR-08:04 | -1.0 | -2.0 | 0.298732E+09 | 488.57 | 25-MAR-14:00 | 18.90 | 10.41 |
April | 0.311133E+09 | 5096.48 | 28-APR-07:04 | 1.70 | 0.95 | 0.298587E+09 | 599.29 | 15-APR-14:09 | 29.50 | 20.38 |
May | 0.706330E+09 | 5720.22 | 31-MAY-15:00 | 30.00 | 19.68 | 0.339509E+09 | 599.33 | 06-MAY-14:00 | 21.10 | 11.56 |
June | 0.326451E+10 | 9981.79 | 26-JUN-07:02 | 23.58 | 21.50 | 0.364089E+09 | 599.32 | 17-JUN-14:09 | 24.18 | 18.98 |
July | 0.434201E+10 | 15031.12 | 04-JUL-08:62 | 22.30 | 19.60 | 0.382616E+09 | 599.32 | 22-JUL-14:00 | 20.60 | 14.31 |
August | 0.464155E+10 | 12883.53 | 03-AUG-07:02 | 24.18 | 22.73 | 0.394110E+09 | 599.33 | 19-AUG-14:09 | 18.98 | 18.58 |
September | 0.300425E+10 | 8879.78 | 07-SEP-14:10 | 32.12 | 18.40 | 0.347814E+09 | 599.33 | 23-SEP-14:00 | 20.60 | 11.38 |
October | 0.261750E+09 | 5534.08 | 23-OCT-07:04 | -1.2 | -2.5 | 0.301078E+09 | 599.33 | 21-OCT-14:39 | 20.87 | 14.25 |
November | 0.121881E+09 | 5574.59 | 16-NOV-08:04 | 0.37 | -0.8 | 0.280065E+09 | 499.99 | 04-NOV-14:00 | 14.40 | 6.79 |
December | 3263574.88 | 7655.98 | 20-DEC-08:05 | -8.4 | -8.9 | 0.289625E+09 | 453.41 | 16-DEC-15:09 | -2.8 | -4.1 |
Annual Sum or Average | 0.166673E+11 | 0.384860E+10 | ||||||||
Minimum of Months | 1858098.71 | 5096.48 | -8.4 | -8.9 | 0.263244E+09 | 453.41 | -6.7 | -7.5 | ||
Maximum of Months | 0.464155E+10 | 15031.12 | 32.12 | 22.73 | 0.394110E+09 | 599.33 | 29.50 | 20.38 |
Report: ZoneHeatingSummaryMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.205596E+11 | 82587.10 | 30-JAN-00:42 | -26.0 |
February | 0.138219E+11 | 82186.57 | 02-FEB-08:11 | -36.3 |
March | 0.771563E+10 | 80985.45 | 05-MAR-08:61 | -9.8 |
April | 0.334220E+10 | 80990.16 | 04-APR-07:01 | -4.8 |
May | 0.279052E+09 | 80919.09 | 03-MAY-07:01 | 5.65 |
June | 79178127.94 | 3838.88 | 28-JUN-07:05 | 21.57 |
July | 38212591.86 | 4013.80 | 28-JUL-07:05 | 20.87 |
August | 33509667.53 | 3929.65 | 23-AUG-07:05 | 18.40 |
September | 0.165969E+09 | 80913.31 | 30-SEP-07:01 | 0.97 |
October | 0.603580E+09 | 80954.82 | 28-OCT-07:01 | 0.05 |
November | 0.686446E+10 | 81084.11 | 28-NOV-08:61 | -16.1 |
December | 0.145708E+11 | 81265.35 | 09-DEC-08:61 | -22.8 |
Annual Sum or Average | 0.680740E+11 | |||
Minimum of Months | 33509667.53 | 3838.88 | -36.3 | |
Maximum of Months | 0.205596E+11 | 82587.10 | 21.57 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.873823E+10 | 35182.35 | 16-JAN-08:61 | -2.1 |
February | 0.575049E+10 | 36341.77 | 10-FEB-08:61 | 3.62 |
March | 0.295105E+10 | 36270.95 | 23-MAR-07:01 | 2.98 |
April | 0.114502E+10 | 36969.01 | 29-APR-07:01 | 5.97 |
May | 15232338.62 | 35951.45 | 02-MAY-07:01 | 2.98 |
June | 4946605.80 | 1561.62 | 28-JUN-07:05 | 21.57 |
July | 8118963.96 | 1633.38 | 02-JUL-07:05 | 22.07 |
August | 3496492.09 | 1956.60 | 04-AUG-07:05 | 24.18 |
September | 13429176.15 | 32359.77 | 30-SEP-07:01 | 0.97 |
October | 93185664.28 | 36052.69 | 24-OCT-07:01 | 3.50 |
November | 0.289105E+10 | 35458.23 | 15-NOV-08:61 | 1.52 |
December | 0.623287E+10 | 35228.44 | 02-DEC-08:61 | -1.0 |
Annual Sum or Average | 0.278471E+11 | |||
Minimum of Months | 3496492.09 | 1561.62 | -2.1 | |
Maximum of Months | 0.873823E+10 | 36969.01 | 24.18 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.102787E+11 | 35783.79 | 09-JAN-07:01 | -2.4 |
February | 0.694419E+10 | 36478.08 | 20-FEB-08:61 | 1.78 |
March | 0.388236E+10 | 36681.47 | 12-MAR-07:01 | 4.22 |
April | 0.166413E+10 | 37201.24 | 10-APR-06:01 | 7.12 |
May | 49209595.66 | 35519.47 | 02-MAY-06:01 | 2.30 |
June | 58690536.71 | 3395.90 | 11-JUN-16:02 | 32.62 |
July | 51445263.74 | 2389.77 | 02-JUL-16:12 | 29.23 |
August | 27407922.39 | 1836.25 | 27-AUG-16:02 | 27.20 |
September | 46020834.17 | 31481.16 | 30-SEP-06:02 | 0.60 |
October | 0.312865E+09 | 35541.98 | 08-OCT-07:01 | 2.43 |
November | 0.375605E+10 | 38229.92 | 20-NOV-07:01 | 10.78 |
December | 0.764832E+10 | 35677.73 | 14-DEC-07:01 | -1.2 |
Annual Sum or Average | 0.347194E+11 | |||
Minimum of Months | 27407922.39 | 1836.25 | -2.4 | |
Maximum of Months | 0.102787E+11 | 38229.92 | 32.62 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.107614E+11 | 35974.16 | 16-JAN-08:61 | -2.1 |
February | 0.732221E+10 | 36686.03 | 20-FEB-08:61 | 1.78 |
March | 0.418842E+10 | 36857.33 | 12-MAR-07:01 | 4.22 |
April | 0.184627E+10 | 37399.53 | 10-APR-06:01 | 7.12 |
May | 67837502.55 | 35682.85 | 02-MAY-06:01 | 2.30 |
June | 59540800.28 | 3404.46 | 11-JUN-16:02 | 32.62 |
July | 52372353.56 | 2393.89 | 02-JUL-16:12 | 29.23 |
August | 27877883.93 | 1846.02 | 27-AUG-16:02 | 27.20 |
September | 56246479.87 | 34754.92 | 30-SEP-06:02 | 0.60 |
October | 0.436942E+09 | 35708.56 | 08-OCT-07:01 | 2.43 |
November | 0.405688E+10 | 38434.03 | 20-NOV-07:01 | 10.78 |
December | 0.808250E+10 | 35817.45 | 14-DEC-07:01 | -1.2 |
Annual Sum or Average | 0.369585E+11 | |||
Minimum of Months | 27877883.93 | 1846.02 | -2.1 | |
Maximum of Months | 0.107614E+11 | 38434.03 | 32.62 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.112064E+11 | 36203.96 | 16-JAN-08:61 | -2.1 |
February | 0.769105E+10 | 36925.75 | 20-FEB-08:61 | 1.78 |
March | 0.452140E+10 | 37084.21 | 12-MAR-07:01 | 4.22 |
April | 0.203847E+10 | 37630.18 | 10-APR-06:01 | 7.12 |
May | 89999149.95 | 36507.34 | 01-MAY-06:02 | 6.20 |
June | 61760370.66 | 3415.48 | 11-JUN-16:02 | 32.62 |
July | 54427101.04 | 2406.49 | 02-JUL-16:12 | 29.23 |
August | 28731771.03 | 1858.49 | 27-AUG-16:02 | 27.20 |
September | 68979604.60 | 34952.86 | 30-SEP-06:02 | 0.60 |
October | 0.539674E+09 | 35915.48 | 08-OCT-07:01 | 2.43 |
November | 0.431812E+10 | 38666.02 | 20-NOV-07:01 | 10.78 |
December | 0.850384E+10 | 36023.99 | 14-DEC-07:01 | -1.2 |
Annual Sum or Average | 0.391229E+11 | |||
Minimum of Months | 28731771.03 | 1858.49 | -2.1 | |
Maximum of Months | 0.112064E+11 | 38666.02 | 32.62 |
Report: ZoneHeatingSummaryMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.213795E+11 | 79355.12 | 29-JAN-09:12 | -22.8 |
February | 0.146929E+11 | 79922.12 | 02-FEB-08:11 | -36.3 |
March | 0.870662E+10 | 78852.17 | 13-MAR-07:01 | -9.6 |
April | 0.402932E+10 | 78747.36 | 04-APR-07:01 | -4.8 |
May | 0.378493E+09 | 78675.06 | 02-MAY-07:01 | 2.98 |
June | 0.160425E+09 | 32661.69 | 05-JUN-07:01 | 9.50 |
July | 87992732.67 | 4652.09 | 02-JUL-16:02 | 29.32 |
August | 61722860.35 | 3670.81 | 23-AUG-07:05 | 18.40 |
September | 0.242655E+09 | 78680.99 | 30-SEP-07:01 | 0.97 |
October | 0.120364E+10 | 78712.96 | 23-OCT-07:01 | -1.2 |
November | 0.835511E+10 | 78821.71 | 25-NOV-08:61 | -18.2 |
December | 0.162367E+11 | 79019.83 | 12-DEC-08:61 | -19.3 |
Annual Sum or Average | 0.755350E+11 | |||
Minimum of Months | 61722860.35 | 3670.81 | -36.3 | |
Maximum of Months | 0.213795E+11 | 79922.12 | 29.32 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.117726E+11 | 36616.89 | 16-JAN-09:01 | -1.6 |
February | 0.818301E+10 | 37669.71 | 20-FEB-09:01 | 2.20 |
March | 0.498262E+10 | 38637.31 | 19-MAR-08:61 | 7.25 |
April | 0.236322E+10 | 39636.29 | 24-APR-07:01 | 12.15 |
May | 0.136804E+09 | 38224.20 | 01-MAY-07:01 | 6.88 |
June | 56862582.33 | 18700.91 | 05-JUN-07:01 | 9.50 |
July | 37733627.16 | 2438.42 | 02-JUL-16:12 | 29.23 |
August | 18982465.01 | 2036.78 | 04-AUG-07:05 | 24.18 |
September | 97458754.10 | 37510.22 | 28-SEP-07:01 | 6.28 |
October | 0.755922E+09 | 39136.36 | 01-OCT-08:61 | 10.72 |
November | 0.471680E+10 | 39871.71 | 20-NOV-08:61 | 11.88 |
December | 0.903491E+10 | 36497.67 | 02-DEC-08:61 | -1.0 |
Annual Sum or Average | 0.421569E+11 | |||
Minimum of Months | 18982465.01 | 2036.78 | -1.6 | |
Maximum of Months | 0.117726E+11 | 39871.71 | 29.23 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.118229E+11 | 36595.19 | 16-JAN-09:01 | -1.6 |
February | 0.824008E+10 | 37663.84 | 20-FEB-09:01 | 2.20 |
March | 0.506732E+10 | 38641.16 | 19-MAR-08:61 | 7.25 |
April | 0.244058E+10 | 39651.60 | 24-APR-07:01 | 12.15 |
May | 0.154578E+09 | 38240.24 | 01-MAY-07:01 | 6.88 |
June | 63728352.37 | 23085.02 | 05-JUN-07:01 | 9.50 |
July | 38040111.16 | 2439.92 | 02-JUL-16:12 | 29.23 |
August | 19052274.37 | 2037.34 | 04-AUG-07:05 | 24.18 |
September | 0.107596E+09 | 37513.33 | 28-SEP-07:01 | 6.28 |
October | 0.808020E+09 | 39136.48 | 01-OCT-08:61 | 10.72 |
November | 0.478065E+10 | 39875.18 | 20-NOV-08:61 | 11.88 |
December | 0.909638E+10 | 36490.89 | 02-DEC-08:61 | -1.0 |
Annual Sum or Average | 0.426389E+11 | |||
Minimum of Months | 19052274.37 | 2037.34 | -1.6 | |
Maximum of Months | 0.118229E+11 | 39875.18 | 29.23 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.123132E+11 | 36873.41 | 16-JAN-09:01 | -1.6 |
February | 0.867747E+10 | 37987.07 | 20-FEB-09:01 | 2.20 |
March | 0.550480E+10 | 38999.54 | 19-MAR-08:61 | 7.25 |
April | 0.279011E+10 | 40041.27 | 24-APR-07:01 | 12.15 |
May | 0.234569E+09 | 39680.59 | 04-MAY-07:01 | 13.68 |
June | 90223957.07 | 36067.72 | 05-JUN-07:01 | 9.50 |
July | 38744501.79 | 2457.97 | 02-JUL-16:12 | 29.23 |
August | 19595408.17 | 1932.04 | 04-AUG-07:05 | 24.18 |
September | 0.143868E+09 | 37833.08 | 28-SEP-07:01 | 6.28 |
October | 0.100428E+10 | 39465.23 | 01-OCT-08:61 | 10.72 |
November | 0.510195E+10 | 40226.26 | 20-NOV-08:61 | 11.88 |
December | 0.952720E+10 | 36818.40 | 02-DEC-08:61 | -1.0 |
Annual Sum or Average | 0.454460E+11 | |||
Minimum of Months | 19595408.17 | 1932.04 | -1.6 | |
Maximum of Months | 0.123132E+11 | 40226.26 | 29.23 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.184274E+11 | 40593.61 | 13-JAN-08:61 | -1.0 |
February | 0.133497E+11 | 41911.62 | 10-FEB-08:61 | 3.62 |
March | 0.919705E+10 | 43062.85 | 19-MAR-08:61 | 7.25 |
April | 0.499398E+10 | 44124.63 | 24-APR-07:01 | 12.15 |
May | 0.719304E+09 | 43624.23 | 04-MAY-07:01 | 13.68 |
June | 0.222724E+09 | 42508.72 | 06-JUN-07:01 | 11.78 |
July | 42795832.99 | 2563.60 | 02-JUL-16:12 | 29.23 |
August | 25364402.80 | 1987.47 | 27-AUG-16:02 | 27.20 |
September | 0.317518E+09 | 41777.45 | 28-SEP-07:01 | 6.28 |
October | 0.185294E+10 | 43397.23 | 01-OCT-08:61 | 10.72 |
November | 0.773404E+10 | 44214.54 | 20-NOV-08:61 | 11.88 |
December | 0.140894E+11 | 40659.35 | 02-DEC-08:61 | -1.0 |
Annual Sum or Average | 0.709723E+11 | |||
Minimum of Months | 25364402.80 | 1987.47 | -1.0 | |
Maximum of Months | 0.184274E+11 | 44214.54 | 29.23 |
Report: ZoneElectricSummaryMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.157219E+11 | 9537.57 | 01-JAN-10:09 | 0.223514E+10 | 1348.26 | 01-JAN-10:09 |
February | 0.142256E+11 | 9537.57 | 01-FEB-10:09 | 0.202238E+10 | 1348.26 | 01-FEB-10:09 |
March | 0.157545E+11 | 9537.57 | 01-MAR-10:09 | 0.223972E+10 | 1348.26 | 01-MAR-10:09 |
April | 0.152557E+11 | 9537.57 | 01-APR-09:09 | 0.216880E+10 | 1348.26 | 01-APR-09:09 |
May | 0.157219E+11 | 9537.57 | 01-MAY-09:09 | 0.223514E+10 | 1348.26 | 01-MAY-09:09 |
June | 0.152557E+11 | 9537.57 | 01-JUN-09:09 | 0.216880E+10 | 1348.26 | 01-JUN-09:09 |
July | 0.157545E+11 | 9537.57 | 01-JUL-09:09 | 0.223972E+10 | 1348.26 | 01-JUL-09:09 |
August | 0.157219E+11 | 9537.57 | 01-AUG-09:09 | 0.223514E+10 | 1348.26 | 01-AUG-09:09 |
September | 0.152882E+11 | 9537.57 | 01-SEP-09:09 | 0.217339E+10 | 1348.26 | 01-SEP-09:09 |
October | 0.157219E+11 | 9537.57 | 01-OCT-09:09 | 0.223514E+10 | 1348.26 | 01-OCT-09:09 |
November | 0.151906E+11 | 9537.57 | 01-NOV-09:09 | 0.215964E+10 | 1348.26 | 01-NOV-09:09 |
December | 0.157870E+11 | 9537.57 | 01-DEC-10:09 | 0.224431E+10 | 1348.26 | 01-DEC-10:09 |
Annual Sum or Average | 0.185400E+12 | 0.263573E+11 | ||||
Minimum of Months | 0.142256E+11 | 9537.57 | 0.202238E+10 | 1348.26 | ||
Maximum of Months | 0.157870E+11 | 9537.57 | 0.224431E+10 | 1348.26 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.786097E+10 | 4768.79 | 01-JAN-10:09 | 0.111757E+10 | 674.13 | 01-JAN-10:09 |
February | 0.711282E+10 | 4768.79 | 01-FEB-10:09 | 0.101119E+10 | 674.13 | 01-FEB-10:09 |
March | 0.787723E+10 | 4768.79 | 01-MAR-10:09 | 0.111986E+10 | 674.13 | 01-MAR-10:09 |
April | 0.762785E+10 | 4768.79 | 01-APR-09:09 | 0.108440E+10 | 674.13 | 01-APR-09:09 |
May | 0.786097E+10 | 4768.79 | 01-MAY-09:09 | 0.111757E+10 | 674.13 | 01-MAY-09:09 |
June | 0.762785E+10 | 4768.79 | 01-JUN-09:09 | 0.108440E+10 | 674.13 | 01-JUN-09:09 |
July | 0.787723E+10 | 4768.79 | 01-JUL-09:09 | 0.111986E+10 | 674.13 | 01-JUL-09:09 |
August | 0.786097E+10 | 4768.79 | 01-AUG-09:09 | 0.111757E+10 | 674.13 | 01-AUG-09:09 |
September | 0.764411E+10 | 4768.79 | 01-SEP-09:09 | 0.108669E+10 | 674.13 | 01-SEP-09:09 |
October | 0.786097E+10 | 4768.79 | 01-OCT-09:09 | 0.111757E+10 | 674.13 | 01-OCT-09:09 |
November | 0.759532E+10 | 4768.79 | 01-NOV-09:09 | 0.107982E+10 | 674.13 | 01-NOV-09:09 |
December | 0.789349E+10 | 4768.79 | 01-DEC-10:09 | 0.112215E+10 | 674.13 | 01-DEC-10:09 |
Annual Sum or Average | 0.926998E+11 | 0.131787E+11 | ||||
Minimum of Months | 0.711282E+10 | 4768.79 | 0.101119E+10 | 674.13 | ||
Maximum of Months | 0.789349E+10 | 4768.79 | 0.112215E+10 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.486999E+10 | 3744.57 | 01-JAN-10:09 | 0.883781E+09 | 674.13 | 01-JAN-10:09 |
February | 0.441023E+10 | 3744.57 | 01-FEB-09:09 | 0.800324E+09 | 674.13 | 01-FEB-09:09 |
March | 0.497215E+10 | 3744.57 | 01-MAR-09:09 | 0.902118E+09 | 674.13 | 01-MAR-09:09 |
April | 0.472525E+10 | 3744.57 | 01-APR-08:09 | 0.857490E+09 | 674.13 | 01-APR-08:09 |
May | 0.492107E+10 | 3744.57 | 01-MAY-08:09 | 0.892950E+09 | 674.13 | 01-MAY-08:09 |
June | 0.480187E+10 | 3744.57 | 01-JUN-08:09 | 0.871243E+09 | 674.13 | 01-JUN-08:09 |
July | 0.484444E+10 | 3744.57 | 01-JUL-08:09 | 0.879197E+09 | 674.13 | 01-JUL-08:09 |
August | 0.497215E+10 | 3744.57 | 01-AUG-08:09 | 0.902118E+09 | 674.13 | 01-AUG-08:09 |
September | 0.472525E+10 | 3744.57 | 01-SEP-08:09 | 0.857490E+09 | 674.13 | 01-SEP-08:09 |
October | 0.486999E+10 | 3744.57 | 01-OCT-09:09 | 0.883781E+09 | 674.13 | 01-OCT-09:09 |
November | 0.472525E+10 | 3744.57 | 01-NOV-08:09 | 0.857490E+09 | 674.13 | 01-NOV-08:09 |
December | 0.484444E+10 | 3744.57 | 01-DEC-09:09 | 0.879197E+09 | 674.13 | 01-DEC-09:09 |
Annual Sum or Average | 0.576821E+11 | 0.104672E+11 | ||||
Minimum of Months | 0.441023E+10 | 3744.57 | 0.800324E+09 | 674.13 | ||
Maximum of Months | 0.497215E+10 | 3744.57 | 0.902118E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.486999E+10 | 3744.57 | 01-JAN-10:09 | 0.883781E+09 | 674.13 | 01-JAN-10:09 |
February | 0.441023E+10 | 3744.57 | 01-FEB-09:09 | 0.800324E+09 | 674.13 | 01-FEB-09:09 |
March | 0.497215E+10 | 3744.57 | 01-MAR-09:09 | 0.902118E+09 | 674.13 | 01-MAR-09:09 |
April | 0.472525E+10 | 3744.57 | 01-APR-08:09 | 0.857490E+09 | 674.13 | 01-APR-08:09 |
May | 0.492107E+10 | 3744.57 | 01-MAY-08:09 | 0.892950E+09 | 674.13 | 01-MAY-08:09 |
June | 0.480187E+10 | 3744.57 | 01-JUN-08:09 | 0.871243E+09 | 674.13 | 01-JUN-08:09 |
July | 0.484444E+10 | 3744.57 | 01-JUL-08:09 | 0.879197E+09 | 674.13 | 01-JUL-08:09 |
August | 0.497215E+10 | 3744.57 | 01-AUG-08:09 | 0.902118E+09 | 674.13 | 01-AUG-08:09 |
September | 0.472525E+10 | 3744.57 | 01-SEP-08:09 | 0.857490E+09 | 674.13 | 01-SEP-08:09 |
October | 0.486999E+10 | 3744.57 | 01-OCT-09:09 | 0.883781E+09 | 674.13 | 01-OCT-09:09 |
November | 0.472525E+10 | 3744.57 | 01-NOV-08:09 | 0.857490E+09 | 674.13 | 01-NOV-08:09 |
December | 0.484444E+10 | 3744.57 | 01-DEC-09:09 | 0.879197E+09 | 674.13 | 01-DEC-09:09 |
Annual Sum or Average | 0.576821E+11 | 0.104672E+11 | ||||
Minimum of Months | 0.441023E+10 | 3744.57 | 0.800324E+09 | 674.13 | ||
Maximum of Months | 0.497215E+10 | 3744.57 | 0.902118E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.486999E+10 | 3744.57 | 01-JAN-10:09 | 0.883781E+09 | 674.13 | 01-JAN-10:09 |
February | 0.441023E+10 | 3744.57 | 01-FEB-09:09 | 0.800324E+09 | 674.13 | 01-FEB-09:09 |
March | 0.497215E+10 | 3744.57 | 01-MAR-09:09 | 0.902118E+09 | 674.13 | 01-MAR-09:09 |
April | 0.472525E+10 | 3744.57 | 01-APR-08:09 | 0.857490E+09 | 674.13 | 01-APR-08:09 |
May | 0.492107E+10 | 3744.57 | 01-MAY-08:09 | 0.892950E+09 | 674.13 | 01-MAY-08:09 |
June | 0.480187E+10 | 3744.57 | 01-JUN-08:09 | 0.871243E+09 | 674.13 | 01-JUN-08:09 |
July | 0.484444E+10 | 3744.57 | 01-JUL-08:09 | 0.879197E+09 | 674.13 | 01-JUL-08:09 |
August | 0.497215E+10 | 3744.57 | 01-AUG-08:09 | 0.902118E+09 | 674.13 | 01-AUG-08:09 |
September | 0.472525E+10 | 3744.57 | 01-SEP-08:09 | 0.857490E+09 | 674.13 | 01-SEP-08:09 |
October | 0.486999E+10 | 3744.57 | 01-OCT-09:09 | 0.883781E+09 | 674.13 | 01-OCT-09:09 |
November | 0.472525E+10 | 3744.57 | 01-NOV-08:09 | 0.857490E+09 | 674.13 | 01-NOV-08:09 |
December | 0.484444E+10 | 3744.57 | 01-DEC-09:09 | 0.879197E+09 | 674.13 | 01-DEC-09:09 |
Annual Sum or Average | 0.576821E+11 | 0.104672E+11 | ||||
Minimum of Months | 0.441023E+10 | 3744.57 | 0.800324E+09 | 674.13 | ||
Maximum of Months | 0.497215E+10 | 3744.57 | 0.902118E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.724555E+10 | 6064.13 | 01-JAN-11:09 | 0.162546E+10 | 1348.26 | 01-JAN-11:09 |
February | 0.656305E+10 | 6064.13 | 01-FEB-10:09 | 0.147229E+10 | 1348.26 | 01-FEB-10:09 |
March | 0.741101E+10 | 6064.13 | 01-MAR-10:09 | 0.166213E+10 | 1348.26 | 01-MAR-10:09 |
April | 0.703184E+10 | 6064.13 | 01-APR-09:09 | 0.157746E+10 | 1348.26 | 01-APR-09:09 |
May | 0.732828E+10 | 6064.13 | 01-MAY-09:09 | 0.164379E+10 | 1348.26 | 01-MAY-09:09 |
June | 0.715593E+10 | 6064.13 | 01-JUN-09:09 | 0.160496E+10 | 1348.26 | 01-JUN-09:09 |
July | 0.720419E+10 | 6064.13 | 01-JUL-09:09 | 0.161629E+10 | 1348.26 | 01-JUL-09:09 |
August | 0.741101E+10 | 6064.13 | 01-AUG-09:09 | 0.166213E+10 | 1348.26 | 01-AUG-09:09 |
September | 0.703184E+10 | 6064.13 | 01-SEP-09:09 | 0.157746E+10 | 1348.26 | 01-SEP-09:09 |
October | 0.724555E+10 | 6064.13 | 01-OCT-10:09 | 0.162546E+10 | 1348.26 | 01-OCT-10:09 |
November | 0.703184E+10 | 6064.13 | 01-NOV-09:09 | 0.157746E+10 | 1348.26 | 01-NOV-09:09 |
December | 0.720419E+10 | 6064.13 | 01-DEC-10:09 | 0.161629E+10 | 1348.26 | 01-DEC-10:09 |
Annual Sum or Average | 0.858643E+11 | 0.192612E+11 | ||||
Minimum of Months | 0.656305E+10 | 6064.13 | 0.147229E+10 | 1348.26 | ||
Maximum of Months | 0.741101E+10 | 6064.13 | 0.166213E+10 | 1348.26 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.362278E+10 | 3032.07 | 01-JAN-11:09 | 0.812728E+09 | 674.13 | 01-JAN-11:09 |
February | 0.328152E+10 | 3032.07 | 01-FEB-10:09 | 0.736147E+09 | 674.13 | 01-FEB-10:09 |
March | 0.370550E+10 | 3032.07 | 01-MAR-10:09 | 0.831065E+09 | 674.13 | 01-MAR-10:09 |
April | 0.351592E+10 | 3032.07 | 01-APR-09:09 | 0.788729E+09 | 674.13 | 01-APR-09:09 |
May | 0.366414E+10 | 3032.07 | 01-MAY-09:09 | 0.821897E+09 | 674.13 | 01-MAY-09:09 |
June | 0.357797E+10 | 3032.07 | 01-JUN-09:09 | 0.802482E+09 | 674.13 | 01-JUN-09:09 |
July | 0.360209E+10 | 3032.07 | 01-JUL-09:09 | 0.808144E+09 | 674.13 | 01-JUL-09:09 |
August | 0.370550E+10 | 3032.07 | 01-AUG-09:09 | 0.831065E+09 | 674.13 | 01-AUG-09:09 |
September | 0.351592E+10 | 3032.07 | 01-SEP-09:09 | 0.788729E+09 | 674.13 | 01-SEP-09:09 |
October | 0.362278E+10 | 3032.07 | 01-OCT-10:09 | 0.812728E+09 | 674.13 | 01-OCT-10:09 |
November | 0.351592E+10 | 3032.07 | 01-NOV-09:09 | 0.788729E+09 | 674.13 | 01-NOV-09:09 |
December | 0.360209E+10 | 3032.07 | 01-DEC-10:09 | 0.808144E+09 | 674.13 | 01-DEC-10:09 |
Annual Sum or Average | 0.429321E+11 | 0.963059E+10 | ||||
Minimum of Months | 0.328152E+10 | 3032.07 | 0.736147E+09 | 674.13 | ||
Maximum of Months | 0.370550E+10 | 3032.07 | 0.831065E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.362278E+10 | 3032.07 | 01-JAN-11:09 | 0.812728E+09 | 674.13 | 01-JAN-11:09 |
February | 0.328152E+10 | 3032.07 | 01-FEB-10:09 | 0.736147E+09 | 674.13 | 01-FEB-10:09 |
March | 0.370550E+10 | 3032.07 | 01-MAR-10:09 | 0.831065E+09 | 674.13 | 01-MAR-10:09 |
April | 0.351592E+10 | 3032.07 | 01-APR-09:09 | 0.788729E+09 | 674.13 | 01-APR-09:09 |
May | 0.366414E+10 | 3032.07 | 01-MAY-09:09 | 0.821897E+09 | 674.13 | 01-MAY-09:09 |
June | 0.357797E+10 | 3032.07 | 01-JUN-09:09 | 0.802482E+09 | 674.13 | 01-JUN-09:09 |
July | 0.360209E+10 | 3032.07 | 01-JUL-09:09 | 0.808144E+09 | 674.13 | 01-JUL-09:09 |
August | 0.370550E+10 | 3032.07 | 01-AUG-09:09 | 0.831065E+09 | 674.13 | 01-AUG-09:09 |
September | 0.351592E+10 | 3032.07 | 01-SEP-09:09 | 0.788729E+09 | 674.13 | 01-SEP-09:09 |
October | 0.362278E+10 | 3032.07 | 01-OCT-10:09 | 0.812728E+09 | 674.13 | 01-OCT-10:09 |
November | 0.351592E+10 | 3032.07 | 01-NOV-09:09 | 0.788729E+09 | 674.13 | 01-NOV-09:09 |
December | 0.360209E+10 | 3032.07 | 01-DEC-10:09 | 0.808144E+09 | 674.13 | 01-DEC-10:09 |
Annual Sum or Average | 0.429321E+11 | 0.963059E+10 | ||||
Minimum of Months | 0.328152E+10 | 3032.07 | 0.736147E+09 | 674.13 | ||
Maximum of Months | 0.370550E+10 | 3032.07 | 0.831065E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.362278E+10 | 3032.07 | 01-JAN-11:09 | 0.812728E+09 | 674.13 | 01-JAN-11:09 |
February | 0.328152E+10 | 3032.07 | 01-FEB-10:09 | 0.736147E+09 | 674.13 | 01-FEB-10:09 |
March | 0.370550E+10 | 3032.07 | 01-MAR-10:09 | 0.831065E+09 | 674.13 | 01-MAR-10:09 |
April | 0.351592E+10 | 3032.07 | 01-APR-09:09 | 0.788729E+09 | 674.13 | 01-APR-09:09 |
May | 0.366414E+10 | 3032.07 | 01-MAY-09:09 | 0.821897E+09 | 674.13 | 01-MAY-09:09 |
June | 0.357797E+10 | 3032.07 | 01-JUN-09:09 | 0.802482E+09 | 674.13 | 01-JUN-09:09 |
July | 0.360209E+10 | 3032.07 | 01-JUL-09:09 | 0.808144E+09 | 674.13 | 01-JUL-09:09 |
August | 0.370550E+10 | 3032.07 | 01-AUG-09:09 | 0.831065E+09 | 674.13 | 01-AUG-09:09 |
September | 0.351592E+10 | 3032.07 | 01-SEP-09:09 | 0.788729E+09 | 674.13 | 01-SEP-09:09 |
October | 0.362278E+10 | 3032.07 | 01-OCT-10:09 | 0.812728E+09 | 674.13 | 01-OCT-10:09 |
November | 0.351592E+10 | 3032.07 | 01-NOV-09:09 | 0.788729E+09 | 674.13 | 01-NOV-09:09 |
December | 0.360209E+10 | 3032.07 | 01-DEC-10:09 | 0.808144E+09 | 674.13 | 01-DEC-10:09 |
Annual Sum or Average | 0.429321E+11 | 0.963059E+10 | ||||
Minimum of Months | 0.328152E+10 | 3032.07 | 0.736147E+09 | 674.13 | ||
Maximum of Months | 0.370550E+10 | 3032.07 | 0.831065E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.362278E+10 | 3032.07 | 01-JAN-11:09 | 0.812728E+09 | 674.13 | 01-JAN-11:09 |
February | 0.328152E+10 | 3032.07 | 01-FEB-10:09 | 0.736147E+09 | 674.13 | 01-FEB-10:09 |
March | 0.370550E+10 | 3032.07 | 01-MAR-10:09 | 0.831065E+09 | 674.13 | 01-MAR-10:09 |
April | 0.351592E+10 | 3032.07 | 01-APR-09:09 | 0.788729E+09 | 674.13 | 01-APR-09:09 |
May | 0.366414E+10 | 3032.07 | 01-MAY-09:09 | 0.821897E+09 | 674.13 | 01-MAY-09:09 |
June | 0.357797E+10 | 3032.07 | 01-JUN-09:09 | 0.802482E+09 | 674.13 | 01-JUN-09:09 |
July | 0.360209E+10 | 3032.07 | 01-JUL-09:09 | 0.808144E+09 | 674.13 | 01-JUL-09:09 |
August | 0.370550E+10 | 3032.07 | 01-AUG-09:09 | 0.831065E+09 | 674.13 | 01-AUG-09:09 |
September | 0.351592E+10 | 3032.07 | 01-SEP-09:09 | 0.788729E+09 | 674.13 | 01-SEP-09:09 |
October | 0.362278E+10 | 3032.07 | 01-OCT-10:09 | 0.812728E+09 | 674.13 | 01-OCT-10:09 |
November | 0.351592E+10 | 3032.07 | 01-NOV-09:09 | 0.788729E+09 | 674.13 | 01-NOV-09:09 |
December | 0.360209E+10 | 3032.07 | 01-DEC-10:09 | 0.808144E+09 | 674.13 | 01-DEC-10:09 |
Annual Sum or Average | 0.429321E+11 | 0.963059E+10 | ||||
Minimum of Months | 0.328152E+10 | 3032.07 | 0.736147E+09 | 674.13 | ||
Maximum of Months | 0.370550E+10 | 3032.07 | 0.831065E+09 | 674.13 |
Report: SpaceGainsMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.180574E+10 | 0.157219E+11 | 0.223514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183087E+11 |
February | 0.163016E+10 | 0.142256E+11 | 0.202238E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137229E+11 |
March | 0.178954E+10 | 0.157545E+11 | 0.223972E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105210E+11 |
April | 0.174484E+10 | 0.152557E+11 | 0.216880E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132338E+09 | 0.669965E+10 |
May | 0.179537E+10 | 0.157219E+11 | 0.223514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111299E+09 | 0.342623E+10 |
June | 0.173447E+10 | 0.152557E+11 | 0.216880E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.687695E+09 | 0.176344E+10 |
July | 0.181028E+10 | 0.157545E+11 | 0.223972E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.560245E+09 | 0.944644E+09 |
August | 0.178501E+10 | 0.157219E+11 | 0.223514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.605499E+09 | 0.124357E+10 |
September | 0.174937E+10 | 0.152882E+11 | 0.217339E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.455851E+09 | 0.290426E+10 |
October | 0.180574E+10 | 0.157219E+11 | 0.223514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.624285E+10 |
November | 0.174613E+10 | 0.151906E+11 | 0.215964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108036E+11 |
December | 0.181481E+10 | 0.157870E+11 | 0.224431E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153655E+11 |
Annual Sum or Average | 0.212115E+11 | 0.185400E+12 | 0.263573E+11 | 0.255293E+10 | 0.919463E+11 | ||||
Minimum of Months | 0.163016E+10 | 0.142256E+11 | 0.202238E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.944644E+09 |
Maximum of Months | 0.181481E+10 | 0.157870E+11 | 0.224431E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.687695E+09 | 0.183087E+11 |
Report: SpaceGainsMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.902868E+09 | 0.786097E+10 | 0.111757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.885275E+10 |
February | 0.815075E+09 | 0.711282E+10 | 0.101119E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.664714E+10 |
March | 0.894769E+09 | 0.787723E+10 | 0.111986E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.499844E+10 |
April | 0.872416E+09 | 0.762785E+10 | 0.108440E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 69920186.20 | 0.322189E+10 |
May | 0.897684E+09 | 0.786097E+10 | 0.111757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 61004852.06 | 0.160958E+10 |
June | 0.867232E+09 | 0.762785E+10 | 0.108440E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.373018E+09 | 0.794673E+09 |
July | 0.905135E+09 | 0.787723E+10 | 0.111986E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.309313E+09 | 0.380324E+09 |
August | 0.892501E+09 | 0.786097E+10 | 0.111757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.332864E+09 | 0.480022E+09 |
September | 0.874683E+09 | 0.764411E+10 | 0.108669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.250837E+09 | 0.131347E+10 |
October | 0.902868E+09 | 0.786097E+10 | 0.111757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.296517E+10 |
November | 0.873064E+09 | 0.759532E+10 | 0.107982E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.515130E+10 |
December | 0.907403E+09 | 0.789349E+10 | 0.112215E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.740099E+10 |
Annual Sum or Average | 0.106057E+11 | 0.926998E+11 | 0.131787E+11 | 0.139696E+10 | 0.438158E+11 | ||||
Minimum of Months | 0.815075E+09 | 0.711282E+10 | 0.101119E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.380324E+09 |
Maximum of Months | 0.907403E+09 | 0.789349E+10 | 0.112215E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.373018E+09 | 0.885275E+10 |
Report: SpaceGainsMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.537120E+09 | 0.486999E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.912966E+10 |
February | 0.487879E+09 | 0.441023E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.686653E+10 |
March | 0.551374E+09 | 0.497215E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.512289E+10 |
April | 0.524810E+09 | 0.472525E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 65256832.89 | 0.327837E+10 |
May | 0.544247E+09 | 0.492107E+10 | 0.892950E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 60970513.49 | 0.163048E+10 |
June | 0.532585E+09 | 0.480187E+10 | 0.871243E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.357767E+09 | 0.808737E+09 |
July | 0.536472E+09 | 0.484444E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.296067E+09 | 0.424949E+09 |
August | 0.551374E+09 | 0.497215E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.327172E+09 | 0.538408E+09 |
September | 0.524810E+09 | 0.472525E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.245405E+09 | 0.135936E+10 |
October | 0.537120E+09 | 0.486999E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.299404E+10 |
November | 0.518979E+09 | 0.472525E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.528326E+10 |
December | 0.536472E+09 | 0.484444E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.763520E+10 |
Annual Sum or Average | 0.638324E+10 | 0.576821E+11 | 0.104672E+11 | 0.135264E+10 | 0.450719E+11 | ||||
Minimum of Months | 0.487879E+09 | 0.441023E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.424949E+09 |
Maximum of Months | 0.551374E+09 | 0.497215E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.357767E+09 | 0.912966E+10 |
Report: SpaceGainsMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.537120E+09 | 0.486999E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.911480E+10 |
February | 0.487879E+09 | 0.441023E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.685232E+10 |
March | 0.551374E+09 | 0.497215E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.510082E+10 |
April | 0.524810E+09 | 0.472525E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 65384707.29 | 0.325668E+10 |
May | 0.544247E+09 | 0.492107E+10 | 0.892950E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 60969928.85 | 0.160519E+10 |
June | 0.532585E+09 | 0.480187E+10 | 0.871243E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.357767E+09 | 0.799724E+09 |
July | 0.536472E+09 | 0.484444E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.296077E+09 | 0.423368E+09 |
August | 0.551374E+09 | 0.497215E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.327185E+09 | 0.536203E+09 |
September | 0.524810E+09 | 0.472525E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.245417E+09 | 0.134713E+10 |
October | 0.537120E+09 | 0.486999E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.296371E+10 |
November | 0.518979E+09 | 0.472525E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.525577E+10 |
December | 0.536472E+09 | 0.484444E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.761946E+10 |
Annual Sum or Average | 0.638324E+10 | 0.576821E+11 | 0.104672E+11 | 0.135280E+10 | 0.448752E+11 | ||||
Minimum of Months | 0.487879E+09 | 0.441023E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.423368E+09 |
Maximum of Months | 0.551374E+09 | 0.497215E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.357767E+09 | 0.911480E+10 |
Report: SpaceGainsMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.537120E+09 | 0.486999E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.910785E+10 |
February | 0.487879E+09 | 0.441023E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.684461E+10 |
March | 0.551374E+09 | 0.497215E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.508793E+10 |
April | 0.524810E+09 | 0.472525E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 65540004.90 | 0.324226E+10 |
May | 0.544247E+09 | 0.492107E+10 | 0.892950E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 60969469.12 | 0.158311E+10 |
June | 0.532585E+09 | 0.480187E+10 | 0.871243E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.358030E+09 | 0.790882E+09 |
July | 0.536472E+09 | 0.484444E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.296153E+09 | 0.419620E+09 |
August | 0.551374E+09 | 0.497215E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.327199E+09 | 0.532115E+09 |
September | 0.524810E+09 | 0.472525E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.245429E+09 | 0.133717E+10 |
October | 0.537120E+09 | 0.486999E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.294603E+10 |
November | 0.518979E+09 | 0.472525E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.524048E+10 |
December | 0.536472E+09 | 0.484444E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.761064E+10 |
Annual Sum or Average | 0.638324E+10 | 0.576821E+11 | 0.104672E+11 | 0.135332E+10 | 0.447427E+11 | ||||
Minimum of Months | 0.487879E+09 | 0.441023E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.419620E+09 |
Maximum of Months | 0.551374E+09 | 0.497215E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.358030E+09 | 0.910785E+10 |
Report: SpaceGainsMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.183632E+10 | 0.724555E+10 | 0.162546E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165737E+11 |
February | 0.167188E+10 | 0.656305E+10 | 0.147229E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124329E+11 |
March | 0.189386E+10 | 0.741101E+10 | 0.166213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.928298E+10 |
April | 0.180380E+10 | 0.703184E+10 | 0.157746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116607E+09 | 0.589410E+10 |
May | 0.186509E+10 | 0.732828E+10 | 0.164379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107377E+09 | 0.286298E+10 |
June | 0.182945E+10 | 0.715593E+10 | 0.160496E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.632843E+09 | 0.145603E+10 |
July | 0.183943E+10 | 0.720419E+10 | 0.161629E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.521806E+09 | 0.795561E+09 |
August | 0.189386E+10 | 0.741101E+10 | 0.166213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.576076E+09 | 0.102336E+10 |
September | 0.180380E+10 | 0.703184E+10 | 0.157746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.431870E+09 | 0.247324E+10 |
October | 0.183632E+10 | 0.724555E+10 | 0.162546E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.537051E+10 |
November | 0.176881E+10 | 0.703184E+10 | 0.157746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.954716E+10 |
December | 0.183943E+10 | 0.720419E+10 | 0.161629E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138527E+11 |
Annual Sum or Average | 0.218821E+11 | 0.858643E+11 | 0.192612E+11 | 0.238658E+10 | 0.815652E+11 | ||||
Minimum of Months | 0.167188E+10 | 0.656305E+10 | 0.147229E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.795561E+09 |
Maximum of Months | 0.189386E+10 | 0.741101E+10 | 0.166213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.632843E+09 | 0.165737E+11 |
Report: SpaceGainsMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.918158E+09 | 0.362278E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.918642E+10 |
February | 0.835938E+09 | 0.328152E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.689158E+10 |
March | 0.946926E+09 | 0.370550E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.512440E+10 |
April | 0.901896E+09 | 0.351592E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 66011805.71 | 0.325338E+10 |
May | 0.932542E+09 | 0.366414E+10 | 0.821897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 60999342.32 | 0.155578E+10 |
June | 0.914724E+09 | 0.357797E+10 | 0.802482E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.359204E+09 | 0.785847E+09 |
July | 0.919713E+09 | 0.360209E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.296899E+09 | 0.421801E+09 |
August | 0.946926E+09 | 0.370550E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.327395E+09 | 0.537959E+09 |
September | 0.901896E+09 | 0.351592E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.245508E+09 | 0.134050E+10 |
October | 0.918158E+09 | 0.362278E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.295540E+10 |
November | 0.884402E+09 | 0.351592E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.527135E+10 |
December | 0.919713E+09 | 0.360209E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.767142E+10 |
Annual Sum or Average | 0.109410E+11 | 0.429321E+11 | 0.963059E+10 | 0.135602E+10 | 0.449958E+11 | ||||
Minimum of Months | 0.835938E+09 | 0.328152E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.421801E+09 |
Maximum of Months | 0.946926E+09 | 0.370550E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.359204E+09 | 0.918642E+10 |
Report: SpaceGainsMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.918158E+09 | 0.362278E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.918568E+10 |
February | 0.835938E+09 | 0.328152E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.689001E+10 |
March | 0.946926E+09 | 0.370550E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.512025E+10 |
April | 0.901896E+09 | 0.351592E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 66123470.39 | 0.324646E+10 |
May | 0.932542E+09 | 0.366414E+10 | 0.821897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 60998933.40 | 0.153796E+10 |
June | 0.914724E+09 | 0.357797E+10 | 0.802482E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.359404E+09 | 0.780120E+09 |
July | 0.919713E+09 | 0.360209E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.296968E+09 | 0.419691E+09 |
August | 0.946926E+09 | 0.370550E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.327407E+09 | 0.535856E+09 |
September | 0.901896E+09 | 0.351592E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.245519E+09 | 0.133448E+10 |
October | 0.918158E+09 | 0.362278E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.294901E+10 |
November | 0.884402E+09 | 0.351592E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.526746E+10 |
December | 0.919713E+09 | 0.360209E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.766967E+10 |
Annual Sum or Average | 0.109410E+11 | 0.429321E+11 | 0.963059E+10 | 0.135642E+10 | 0.449367E+11 | ||||
Minimum of Months | 0.835938E+09 | 0.328152E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.419691E+09 |
Maximum of Months | 0.946926E+09 | 0.370550E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.359404E+09 | 0.918568E+10 |
Report: SpaceGainsMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.918158E+09 | 0.362278E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.917972E+10 |
February | 0.835938E+09 | 0.328152E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.688008E+10 |
March | 0.946926E+09 | 0.370550E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.510120E+10 |
April | 0.901896E+09 | 0.351592E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 66460772.74 | 0.322103E+10 |
May | 0.932542E+09 | 0.366414E+10 | 0.821897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 60997769.89 | 0.149213E+10 |
June | 0.914724E+09 | 0.357797E+10 | 0.802482E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.359896E+09 | 0.764038E+09 |
July | 0.919713E+09 | 0.360209E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.297121E+09 | 0.412856E+09 |
August | 0.946926E+09 | 0.370550E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.327428E+09 | 0.529313E+09 |
September | 0.901896E+09 | 0.351592E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.245538E+09 | 0.132001E+10 |
October | 0.918158E+09 | 0.362278E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.292863E+10 |
November | 0.884402E+09 | 0.351592E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.525213E+10 |
December | 0.919713E+09 | 0.360209E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.765830E+10 |
Annual Sum or Average | 0.109410E+11 | 0.429321E+11 | 0.963059E+10 | 0.135744E+10 | 0.447394E+11 | ||||
Minimum of Months | 0.835938E+09 | 0.328152E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.412856E+09 |
Maximum of Months | 0.946926E+09 | 0.370550E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.359896E+09 | 0.917972E+10 |
Report: SpaceGainsMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.918158E+09 | 0.362278E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121185E+11 |
February | 0.835938E+09 | 0.328152E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.903376E+10 |
March | 0.946926E+09 | 0.370550E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.681927E+10 |
April | 0.901896E+09 | 0.351592E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 76541052.21 | 0.416057E+10 |
May | 0.932542E+09 | 0.366414E+10 | 0.821897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 64904711.76 | 0.191755E+10 |
June | 0.914724E+09 | 0.357797E+10 | 0.802482E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.391935E+09 | 0.105282E+10 |
July | 0.919713E+09 | 0.360209E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.312782E+09 | 0.645314E+09 |
August | 0.946926E+09 | 0.370550E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.346847E+09 | 0.889984E+09 |
September | 0.901896E+09 | 0.351592E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.259343E+09 | 0.186993E+10 |
October | 0.918158E+09 | 0.362278E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.390664E+10 |
November | 0.884402E+09 | 0.351592E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.702802E+10 |
December | 0.919713E+09 | 0.360209E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101365E+11 |
Annual Sum or Average | 0.109410E+11 | 0.429321E+11 | 0.963059E+10 | 0.145235E+10 | 0.595789E+11 | ||||
Minimum of Months | 0.835938E+09 | 0.328152E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.645314E+09 |
Maximum of Months | 0.946926E+09 | 0.370550E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.391935E+09 | 0.121185E+11 |
Report: PeakSpaceGainsMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2159.72 | 01-JAN-13:09 | 9537.57 | 01-JAN-10:09 | 1348.26 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 27093.22 | 30-JAN-18:00 |
February | 2159.72 | 03-FEB-13:09 | 9537.57 | 01-FEB-10:09 | 1348.26 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 30579.84 | 02-FEB-12:10 |
March | 2159.72 | 03-MAR-13:09 | 9537.57 | 01-MAR-10:09 | 1348.26 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 18280.29 | 05-MAR-18:00 |
April | 2159.72 | 01-APR-12:09 | 9537.57 | 01-APR-09:09 | 1348.26 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3063.45 | 15-APR-15:00 | 13352.65 | 03-APR-11:10 |
May | 2159.72 | 05-MAY-12:09 | 9537.57 | 01-MAY-09:09 | 1348.26 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2841.43 | 31-MAY-13:00 | 6826.63 | 01-MAY-17:00 |
June | 2159.72 | 02-JUN-12:09 | 9537.57 | 01-JUN-09:09 | 1348.26 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4515.31 | 11-JUN-15:00 | 5525.42 | 01-JUN-14:00 |
July | 2159.72 | 01-JUL-12:09 | 9537.57 | 01-JUL-09:09 | 1348.26 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2863.14 | 26-JUL-16:00 | 4144.30 | 10-JUL-12:00 |
August | 2159.72 | 04-AUG-12:09 | 9537.57 | 01-AUG-09:09 | 1348.26 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4501.90 | 04-AUG-15:00 | 4057.97 | 06-AUG-11:10 |
September | 2159.72 | 01-SEP-12:09 | 9537.57 | 01-SEP-09:09 | 1348.26 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3870.71 | 06-SEP-14:00 | 6784.76 | 29-SEP-17:00 |
October | 2159.72 | 01-OCT-12:09 | 9537.57 | 01-OCT-09:09 | 1348.26 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 | 8703.36 | 31-OCT-17:00 |
November | 2159.72 | 03-NOV-12:09 | 9537.57 | 01-NOV-09:09 | 1348.26 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 23907.28 | 25-NOV-18:00 |
December | 2159.72 | 01-DEC-13:09 | 9537.57 | 01-DEC-10:09 | 1348.26 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 25624.65 | 09-DEC-12:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2159.72 | 9537.57 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4057.97 | |||||
Maximum of Months | 2159.72 | 9537.57 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 4515.31 | 30579.84 |
Report: PeakSpaceGainsMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1079.86 | 01-JAN-13:09 | 4768.79 | 01-JAN-10:09 | 674.13 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 15128.86 | 30-JAN-18:00 |
February | 1079.86 | 03-FEB-13:09 | 4768.79 | 01-FEB-10:09 | 674.13 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 16973.76 | 02-FEB-12:10 |
March | 1079.86 | 03-MAR-13:09 | 4768.79 | 01-MAR-10:09 | 674.13 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 10065.94 | 05-MAR-18:00 |
April | 1079.86 | 01-APR-12:09 | 4768.79 | 01-APR-09:09 | 674.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1627.65 | 15-APR-15:00 | 7359.01 | 03-APR-11:10 |
May | 1079.86 | 05-MAY-12:09 | 4768.79 | 01-MAY-09:09 | 674.13 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1568.79 | 31-MAY-13:00 | 3681.42 | 01-MAY-17:00 |
June | 1079.86 | 02-JUN-12:09 | 4768.79 | 01-JUN-09:09 | 674.13 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2441.06 | 11-JUN-15:00 | 3163.77 | 01-JUN-14:00 |
July | 1079.86 | 01-JUL-12:09 | 4768.79 | 01-JUL-09:09 | 674.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1580.79 | 26-JUL-16:00 | 2264.32 | 10-JUL-12:00 |
August | 1079.86 | 04-AUG-12:09 | 4768.79 | 01-AUG-09:09 | 674.13 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2507.03 | 04-AUG-15:00 | 2237.44 | 06-AUG-11:10 |
September | 1079.86 | 01-SEP-12:09 | 4768.79 | 01-SEP-09:09 | 674.13 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2137.05 | 06-SEP-14:00 | 3735.98 | 29-SEP-17:00 |
October | 1079.86 | 01-OCT-12:09 | 4768.79 | 01-OCT-09:09 | 674.13 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 | 4920.26 | 31-OCT-17:00 |
November | 1079.86 | 03-NOV-12:09 | 4768.79 | 01-NOV-09:09 | 674.13 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 13095.87 | 25-NOV-18:00 |
December | 1079.86 | 01-DEC-13:09 | 4768.79 | 01-DEC-10:09 | 674.13 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 13636.94 | 09-DEC-12:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1079.86 | 4768.79 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2237.44 | |||||
Maximum of Months | 1079.86 | 4768.79 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 2507.03 | 16973.76 |
Report: PeakSpaceGainsMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1079.86 | 07-JAN-13:09 | 3744.57 | 01-JAN-10:09 | 674.13 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 15128.83 | 30-JAN-18:00 |
February | 1079.86 | 04-FEB-13:09 | 3744.57 | 01-FEB-09:09 | 674.13 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 16973.72 | 02-FEB-12:10 |
March | 1079.86 | 04-MAR-13:09 | 3744.57 | 01-MAR-09:09 | 674.13 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 10065.93 | 05-MAR-18:00 |
April | 1079.86 | 01-APR-12:09 | 3744.57 | 01-APR-08:09 | 674.13 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1627.59 | 15-APR-15:00 | 7358.99 | 03-APR-11:10 |
May | 1079.86 | 06-MAY-12:09 | 3744.57 | 01-MAY-08:09 | 674.13 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1568.76 | 31-MAY-13:00 | 3681.40 | 01-MAY-17:00 |
June | 1079.86 | 03-JUN-12:09 | 3744.57 | 01-JUN-08:09 | 674.13 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2440.92 | 11-JUN-15:00 | 3079.48 | 01-JUN-14:00 |
July | 1079.86 | 01-JUL-12:09 | 3744.57 | 01-JUL-08:09 | 674.13 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1580.67 | 26-JUL-16:00 | 2254.17 | 10-JUL-12:00 |
August | 1079.86 | 05-AUG-12:09 | 3744.57 | 01-AUG-08:09 | 674.13 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2506.94 | 04-AUG-15:00 | 2237.44 | 06-AUG-11:10 |
September | 1079.86 | 02-SEP-12:09 | 3744.57 | 01-SEP-08:09 | 674.13 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2136.99 | 06-SEP-14:00 | 3735.98 | 29-SEP-17:00 |
October | 1079.86 | 07-OCT-12:09 | 3744.57 | 01-OCT-09:09 | 674.13 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 | 4920.25 | 31-OCT-17:00 |
November | 1079.86 | 04-NOV-12:09 | 3744.57 | 01-NOV-08:09 | 674.13 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 13095.83 | 25-NOV-18:00 |
December | 1079.86 | 02-DEC-13:09 | 3744.57 | 01-DEC-09:09 | 674.13 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 13636.85 | 09-DEC-12:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1079.86 | 3744.57 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2237.44 | |||||
Maximum of Months | 1079.86 | 3744.57 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 2506.94 | 16973.72 |
Report: PeakSpaceGainsMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1079.86 | 07-JAN-13:09 | 3744.57 | 01-JAN-10:09 | 674.13 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 15128.83 | 30-JAN-18:00 |
February | 1079.86 | 04-FEB-13:09 | 3744.57 | 01-FEB-09:09 | 674.13 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 16973.72 | 02-FEB-12:10 |
March | 1079.86 | 04-MAR-13:09 | 3744.57 | 01-MAR-09:09 | 674.13 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 10065.93 | 05-MAR-18:00 |
April | 1079.86 | 01-APR-12:09 | 3744.57 | 01-APR-08:09 | 674.13 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1627.58 | 15-APR-15:00 | 7358.99 | 03-APR-11:10 |
May | 1079.86 | 06-MAY-12:09 | 3744.57 | 01-MAY-08:09 | 674.13 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1568.75 | 31-MAY-13:00 | 3681.40 | 01-MAY-17:00 |
June | 1079.86 | 03-JUN-12:09 | 3744.57 | 01-JUN-08:09 | 674.13 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2440.91 | 11-JUN-15:00 | 3063.73 | 01-JUN-14:00 |
July | 1079.86 | 01-JUL-12:09 | 3744.57 | 01-JUL-08:09 | 674.13 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1580.66 | 26-JUL-16:00 | 2239.55 | 10-JUL-12:00 |
August | 1079.86 | 05-AUG-12:09 | 3744.57 | 01-AUG-08:09 | 674.13 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2506.93 | 04-AUG-15:00 | 2237.44 | 06-AUG-11:10 |
September | 1079.86 | 02-SEP-12:09 | 3744.57 | 01-SEP-08:09 | 674.13 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2136.98 | 06-SEP-14:00 | 3735.94 | 29-SEP-17:00 |
October | 1079.86 | 07-OCT-12:09 | 3744.57 | 01-OCT-09:09 | 674.13 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 | 4920.25 | 31-OCT-17:00 |
November | 1079.86 | 04-NOV-12:09 | 3744.57 | 01-NOV-08:09 | 674.13 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 13095.83 | 25-NOV-18:00 |
December | 1079.86 | 02-DEC-13:09 | 3744.57 | 01-DEC-09:09 | 674.13 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 13636.85 | 09-DEC-12:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1079.86 | 3744.57 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2237.44 | |||||
Maximum of Months | 1079.86 | 3744.57 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 2506.93 | 16973.72 |
Report: PeakSpaceGainsMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1079.86 | 07-JAN-13:09 | 3744.57 | 01-JAN-10:09 | 674.13 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 15128.83 | 30-JAN-18:00 |
February | 1079.86 | 04-FEB-13:09 | 3744.57 | 01-FEB-09:09 | 674.13 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 16973.72 | 02-FEB-12:10 |
March | 1079.86 | 04-MAR-13:09 | 3744.57 | 01-MAR-09:09 | 674.13 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 10065.93 | 05-MAR-18:00 |
April | 1079.86 | 01-APR-12:09 | 3744.57 | 01-APR-08:09 | 674.13 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1627.57 | 15-APR-15:00 | 7358.99 | 03-APR-11:10 |
May | 1079.86 | 06-MAY-12:09 | 3744.57 | 01-MAY-08:09 | 674.13 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1568.74 | 31-MAY-13:00 | 3681.40 | 01-MAY-17:00 |
June | 1079.86 | 03-JUN-12:09 | 3744.57 | 01-JUN-08:09 | 674.13 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2440.89 | 11-JUN-15:00 | 3042.40 | 01-JUN-14:00 |
July | 1079.86 | 01-JUL-12:09 | 3744.57 | 01-JUL-08:09 | 674.13 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1580.64 | 26-JUL-16:00 | 2222.51 | 10-JUL-12:00 |
August | 1079.86 | 05-AUG-12:09 | 3744.57 | 01-AUG-08:09 | 674.13 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2506.91 | 04-AUG-15:00 | 2237.44 | 06-AUG-11:10 |
September | 1079.86 | 02-SEP-12:09 | 3744.57 | 01-SEP-08:09 | 674.13 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2136.98 | 06-SEP-14:00 | 3735.94 | 29-SEP-17:00 |
October | 1079.86 | 07-OCT-12:09 | 3744.57 | 01-OCT-09:09 | 674.13 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 | 4920.25 | 31-OCT-17:00 |
November | 1079.86 | 04-NOV-12:09 | 3744.57 | 01-NOV-08:09 | 674.13 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 13095.83 | 25-NOV-18:00 |
December | 1079.86 | 02-DEC-13:09 | 3744.57 | 01-DEC-09:09 | 674.13 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 13636.85 | 09-DEC-12:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1079.86 | 3744.57 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2222.51 | |||||
Maximum of Months | 1079.86 | 3744.57 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 2506.91 | 16973.72 |
Report: PeakSpaceGainsMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2879.63 | 07-JAN-15:09 | 6064.13 | 01-JAN-11:09 | 1348.26 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 26557.50 | 30-JAN-18:00 |
February | 2879.63 | 04-FEB-15:09 | 6064.13 | 01-FEB-10:09 | 1348.26 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 29822.36 | 02-FEB-12:10 |
March | 2879.63 | 04-MAR-15:09 | 6064.13 | 01-MAR-10:09 | 1348.26 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 17706.51 | 05-MAR-18:00 |
April | 2879.63 | 01-APR-14:09 | 6064.13 | 01-APR-09:09 | 1348.26 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2878.51 | 15-APR-15:00 | 12943.16 | 03-APR-11:10 |
May | 2879.63 | 06-MAY-14:09 | 6064.13 | 01-MAY-09:09 | 1348.26 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2758.43 | 31-MAY-13:00 | 6496.06 | 01-MAY-17:00 |
June | 2879.63 | 03-JUN-14:09 | 6064.13 | 01-JUN-09:09 | 1348.26 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4305.52 | 11-JUN-15:00 | 5205.31 | 01-JUN-14:00 |
July | 2879.63 | 01-JUL-14:09 | 6064.13 | 01-JUL-09:09 | 1348.26 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2779.27 | 26-JUL-16:00 | 3820.40 | 10-JUL-12:00 |
August | 2879.63 | 05-AUG-14:09 | 6064.13 | 01-AUG-09:09 | 1348.26 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4402.47 | 04-AUG-15:00 | 3934.98 | 06-AUG-11:10 |
September | 2879.63 | 02-SEP-14:09 | 6064.13 | 01-SEP-09:09 | 1348.26 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3757.57 | 06-SEP-14:00 | 6571.70 | 29-SEP-17:00 |
October | 2879.63 | 07-OCT-14:09 | 6064.13 | 01-OCT-10:09 | 1348.26 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 | 8621.56 | 31-OCT-17:00 |
November | 2879.63 | 04-NOV-14:09 | 6064.13 | 01-NOV-09:09 | 1348.26 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 23054.19 | 25-NOV-18:00 |
December | 2879.63 | 02-DEC-15:09 | 6064.13 | 01-DEC-10:09 | 1348.26 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 24111.66 | 09-DEC-12:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2879.63 | 6064.13 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3820.40 | |||||
Maximum of Months | 2879.63 | 6064.13 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 4402.47 | 29822.36 |
Report: PeakSpaceGainsMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1439.81 | 07-JAN-15:09 | 3032.07 | 01-JAN-11:09 | 674.13 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 15128.83 | 30-JAN-18:00 |
February | 1439.81 | 04-FEB-15:09 | 3032.07 | 01-FEB-10:09 | 674.13 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 16973.71 | 02-FEB-12:10 |
March | 1439.81 | 04-MAR-15:09 | 3032.07 | 01-MAR-10:09 | 674.13 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 10065.92 | 05-MAR-18:00 |
April | 1439.81 | 01-APR-14:09 | 3032.07 | 01-APR-09:09 | 674.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1627.58 | 15-APR-15:00 | 7358.98 | 03-APR-11:10 |
May | 1439.81 | 06-MAY-14:09 | 3032.07 | 01-MAY-09:09 | 674.13 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1568.74 | 31-MAY-13:00 | 3681.39 | 01-MAY-17:00 |
June | 1439.81 | 03-JUN-14:09 | 3032.07 | 01-JUN-09:09 | 674.13 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2440.92 | 11-JUN-15:00 | 2963.30 | 01-JUN-14:00 |
July | 1439.81 | 01-JUL-14:09 | 3032.07 | 01-JUL-09:09 | 674.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1580.61 | 26-JUL-16:00 | 2172.01 | 10-JUL-12:00 |
August | 1439.81 | 05-AUG-14:09 | 3032.07 | 01-AUG-09:09 | 674.13 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2506.94 | 04-AUG-15:00 | 2235.44 | 06-AUG-11:10 |
September | 1439.81 | 02-SEP-14:09 | 3032.07 | 01-SEP-09:09 | 674.13 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2136.97 | 06-SEP-14:00 | 3735.94 | 29-SEP-17:00 |
October | 1439.81 | 07-OCT-14:09 | 3032.07 | 01-OCT-10:09 | 674.13 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 | 4920.24 | 31-OCT-17:00 |
November | 1439.81 | 04-NOV-14:09 | 3032.07 | 01-NOV-09:09 | 674.13 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 13095.82 | 25-NOV-18:00 |
December | 1439.81 | 02-DEC-15:09 | 3032.07 | 01-DEC-10:09 | 674.13 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 13636.84 | 09-DEC-12:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1439.81 | 3032.07 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2172.01 | |||||
Maximum of Months | 1439.81 | 3032.07 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 2506.94 | 16973.71 |
Report: PeakSpaceGainsMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1439.81 | 07-JAN-15:09 | 3032.07 | 01-JAN-11:09 | 674.13 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 15128.83 | 30-JAN-18:00 |
February | 1439.81 | 04-FEB-15:09 | 3032.07 | 01-FEB-10:09 | 674.13 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 16973.71 | 02-FEB-12:10 |
March | 1439.81 | 04-MAR-15:09 | 3032.07 | 01-MAR-10:09 | 674.13 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 10065.92 | 05-MAR-18:00 |
April | 1439.81 | 01-APR-14:09 | 3032.07 | 01-APR-09:09 | 674.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1627.57 | 15-APR-15:00 | 7358.98 | 03-APR-11:10 |
May | 1439.81 | 06-MAY-14:09 | 3032.07 | 01-MAY-09:09 | 674.13 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1568.74 | 31-MAY-13:00 | 3681.39 | 01-MAY-17:00 |
June | 1439.81 | 03-JUN-14:09 | 3032.07 | 01-JUN-09:09 | 674.13 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2440.91 | 11-JUN-15:00 | 2943.97 | 01-JUN-14:00 |
July | 1439.81 | 01-JUL-14:09 | 3032.07 | 01-JUL-09:09 | 674.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1580.60 | 26-JUL-16:00 | 2158.78 | 10-JUL-12:00 |
August | 1439.81 | 05-AUG-14:09 | 3032.07 | 01-AUG-09:09 | 674.13 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2506.93 | 04-AUG-15:00 | 2230.34 | 06-AUG-11:10 |
September | 1439.81 | 02-SEP-14:09 | 3032.07 | 01-SEP-09:09 | 674.13 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2136.97 | 06-SEP-14:00 | 3735.94 | 29-SEP-17:00 |
October | 1439.81 | 07-OCT-14:09 | 3032.07 | 01-OCT-10:09 | 674.13 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 | 4920.24 | 31-OCT-17:00 |
November | 1439.81 | 04-NOV-14:09 | 3032.07 | 01-NOV-09:09 | 674.13 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 13095.82 | 25-NOV-18:00 |
December | 1439.81 | 02-DEC-15:09 | 3032.07 | 01-DEC-10:09 | 674.13 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 13636.84 | 09-DEC-12:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1439.81 | 3032.07 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2158.78 | |||||
Maximum of Months | 1439.81 | 3032.07 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 2506.93 | 16973.71 |
Report: PeakSpaceGainsMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1439.81 | 07-JAN-15:09 | 3032.07 | 01-JAN-11:09 | 674.13 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 15128.83 | 30-JAN-18:00 |
February | 1439.81 | 04-FEB-15:09 | 3032.07 | 01-FEB-10:09 | 674.13 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 16973.71 | 02-FEB-12:10 |
March | 1439.81 | 04-MAR-15:09 | 3032.07 | 01-MAR-10:09 | 674.13 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 10065.92 | 05-MAR-18:00 |
April | 1439.81 | 01-APR-14:09 | 3032.07 | 01-APR-09:09 | 674.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1627.54 | 15-APR-15:00 | 7358.98 | 03-APR-11:10 |
May | 1439.81 | 06-MAY-14:09 | 3032.07 | 01-MAY-09:09 | 674.13 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1568.72 | 31-MAY-13:00 | 3681.39 | 01-MAY-17:00 |
June | 1439.81 | 03-JUN-14:09 | 3032.07 | 01-JUN-09:09 | 674.13 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2440.88 | 11-JUN-15:00 | 2896.40 | 01-JUN-14:00 |
July | 1439.81 | 01-JUL-14:09 | 3032.07 | 01-JUL-09:09 | 674.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1580.58 | 26-JUL-16:00 | 2116.88 | 10-JUL-12:00 |
August | 1439.81 | 05-AUG-14:09 | 3032.07 | 01-AUG-09:09 | 674.13 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2506.92 | 04-AUG-15:00 | 2217.24 | 06-AUG-11:10 |
September | 1439.81 | 02-SEP-14:09 | 3032.07 | 01-SEP-09:09 | 674.13 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2136.96 | 06-SEP-14:00 | 3735.94 | 29-SEP-17:00 |
October | 1439.81 | 07-OCT-14:09 | 3032.07 | 01-OCT-10:09 | 674.13 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 | 4920.24 | 31-OCT-17:00 |
November | 1439.81 | 04-NOV-14:09 | 3032.07 | 01-NOV-09:09 | 674.13 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 13095.82 | 25-NOV-18:00 |
December | 1439.81 | 02-DEC-15:09 | 3032.07 | 01-DEC-10:09 | 674.13 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 13636.84 | 09-DEC-12:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1439.81 | 3032.07 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2116.88 | |||||
Maximum of Months | 1439.81 | 3032.07 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 2506.92 | 16973.71 |
Report: PeakSpaceGainsMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1439.81 | 07-JAN-15:09 | 3032.07 | 01-JAN-11:09 | 674.13 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 15663.83 | 30-JAN-18:00 |
February | 1439.81 | 04-FEB-15:09 | 3032.07 | 01-FEB-10:09 | 674.13 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 17730.17 | 02-FEB-12:10 |
March | 1439.81 | 04-MAR-15:09 | 3032.07 | 01-MAR-10:09 | 674.13 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 10638.98 | 05-MAR-18:00 |
April | 1439.81 | 01-APR-14:09 | 3032.07 | 01-APR-09:09 | 674.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1812.10 | 15-APR-15:00 | 7767.90 | 03-APR-11:10 |
May | 1439.81 | 06-MAY-14:09 | 3032.07 | 01-MAY-09:09 | 674.13 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1651.57 | 31-MAY-13:00 | 4011.50 | 01-MAY-17:00 |
June | 1439.81 | 03-JUN-14:09 | 3032.07 | 01-JUN-09:09 | 674.13 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2650.14 | 11-JUN-15:00 | 2959.57 | 05-JUN-12:00 |
July | 1439.81 | 01-JUL-14:09 | 3032.07 | 01-JUL-09:09 | 674.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1664.00 | 26-JUL-16:00 | 2159.96 | 10-JUL-11:10 |
August | 1439.81 | 05-AUG-14:09 | 3032.07 | 01-AUG-09:09 | 674.13 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2606.04 | 04-AUG-15:00 | 2255.99 | 06-AUG-11:10 |
September | 1439.81 | 02-SEP-14:09 | 3032.07 | 01-SEP-09:09 | 674.13 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2249.84 | 06-SEP-14:00 | 3948.63 | 29-SEP-17:00 |
October | 1439.81 | 07-OCT-14:09 | 3032.07 | 01-OCT-10:09 | 674.13 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 | 5001.92 | 31-OCT-17:00 |
November | 1439.81 | 04-NOV-14:09 | 3032.07 | 01-NOV-09:09 | 674.13 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 13947.78 | 25-NOV-18:00 |
December | 1439.81 | 02-DEC-15:09 | 3032.07 | 01-DEC-10:09 | 674.13 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 15147.80 | 09-DEC-12:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1439.81 | 3032.07 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2159.96 | |||||
Maximum of Months | 1439.81 | 3032.07 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 2650.14 | 17730.17 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 24279.43 | 06-JAN-00:01 | 1619.79 | 45177.96 | 6741.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1201.69 |
February | 28834.75 | 03-FEB-00:01 | 1799.77 | 50197.74 | 7490.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 887.47 |
March | 15733.43 | 07-MAR-20:52 | 6479.16 | 57225.42 | 8089.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 675.65 |
April | 13648.23 | 16-APR-16:04 | 10798.60 | 47687.85 | 6741.28 | 0.00 | 0.00 | 0.00 | 0.00 | 2480.23 | 0.00 |
May | 14541.98 | 31-MAY-15:00 | 899.88 | 9537.57 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 2822.75 | 0.00 |
June | 29496.57 | 30-JUN-07:02 | 0.00 | 2509.89 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 124.02 |
July | 33464.44 | 04-JUL-07:02 | 899.88 | 2509.89 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 319.29 |
August | 30423.67 | 23-AUG-07:03 | 719.91 | 2007.91 | 299.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 485.09 |
September | 34887.81 | 12-SEP-07:02 | 899.88 | 2509.89 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 664.14 |
October | 9697.56 | 27-OCT-23:25 | 359.95 | 10039.55 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 369.10 |
November | 17367.47 | 25-NOV-00:01 | 1259.84 | 35138.42 | 5243.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 941.99 |
December | 23004.01 | 09-DEC-00:01 | 1799.77 | 50197.74 | 7490.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3643.35 |
Annual Sum or Average | |||||||||||
Minimum of Months | 9697.56 | 0.00 | 2007.91 | 299.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 34887.81 | 10798.60 | 57225.42 | 8089.53 | 0.00 | 0.00 | 0.00 | 0.00 | 2822.75 | 3643.35 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 8993.01 | 10-JAN-08:04 | 899.88 | 2509.89 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1560.11 |
February | 9070.96 | 15-FEB-08:04 | 899.88 | 2509.89 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1710.46 |
March | 8374.71 | 13-MAR-07:04 | 899.88 | 2509.89 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1517.37 |
April | 7477.58 | 03-APR-07:04 | 899.88 | 2509.89 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1488.26 |
May | 7824.43 | 31-MAY-15:00 | 449.94 | 4768.79 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1562.62 | 0.00 |
June | 18719.20 | 28-JUN-07:03 | 359.95 | 1003.95 | 149.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.22 |
July | 19109.51 | 28-JUL-07:03 | 0.00 | 1003.95 | 149.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 128.53 |
August | 18451.93 | 14-AUG-07:02 | 449.94 | 1254.94 | 187.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 320.21 |
September | 19377.80 | 12-SEP-07:02 | 449.94 | 1254.94 | 187.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 346.20 |
October | 5492.28 | 26-OCT-07:02 | 899.88 | 2509.89 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 991.92 |
November | 9489.29 | 24-NOV-08:04 | 0.00 | 2509.89 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1802.55 |
December | 9629.39 | 07-DEC-08:04 | 899.88 | 2509.89 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1767.39 |
Annual Sum or Average | |||||||||||
Minimum of Months | 5492.28 | 0.00 | 1003.95 | 149.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19377.80 | 899.88 | 4768.79 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1562.62 | 1802.55 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 9464.04 | 21-JAN-07:05 | 0.00 | 1970.82 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 370.57 |
February | 7907.03 | 16-FEB-07:05 | 0.00 | 1970.82 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 231.04 |
March | 9094.11 | 06-MAR-07:05 | 0.00 | 1970.82 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 667.18 |
April | 7003.13 | 04-APR-06:04 | 0.00 | 1970.82 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 136.96 |
May | 7053.17 | 31-MAY-15:00 | 359.95 | 3744.57 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1562.58 | 0.00 |
June | 16753.90 | 30-JUN-06:02 | 0.00 | 985.41 | 187.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.28 |
July | 17498.89 | 28-JUL-06:03 | 0.00 | 788.33 | 149.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.40 |
August | 16135.82 | 23-AUG-06:03 | 0.00 | 788.33 | 149.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.92 |
September | 18274.49 | 11-SEP-06:03 | 0.00 | 788.33 | 149.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.13 |
October | 6242.62 | 23-OCT-06:04 | 0.00 | 985.41 | 187.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 148.03 |
November | 8330.30 | 25-NOV-07:05 | 0.00 | 1970.82 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 498.98 |
December | 8634.30 | 27-DEC-07:04 | 0.00 | 1970.82 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 127.84 |
Annual Sum or Average | |||||||||||
Minimum of Months | 6242.62 | 0.00 | 788.33 | 149.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18274.49 | 359.95 | 3744.57 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1562.58 | 667.18 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 9242.42 | 21-JAN-07:05 | 0.00 | 1970.82 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 370.36 |
February | 7525.97 | 09-FEB-07:03 | 0.00 | 1773.74 | 337.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 144.60 |
March | 9152.51 | 06-MAR-07:05 | 0.00 | 1970.82 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 668.67 |
April | 7448.33 | 03-APR-06:05 | 0.00 | 1970.82 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 366.51 |
May | 6923.67 | 31-MAY-15:00 | 359.95 | 3744.57 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1562.58 | 0.00 |
June | 16778.94 | 30-JUN-06:02 | 0.00 | 985.41 | 187.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.15 |
July | 17085.86 | 28-JUL-06:03 | 0.00 | 788.33 | 149.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.40 |
August | 16141.52 | 23-AUG-06:03 | 0.00 | 788.33 | 149.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.66 |
September | 18307.53 | 11-SEP-06:03 | 0.00 | 788.33 | 149.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.96 |
October | 6466.84 | 23-OCT-06:04 | 0.00 | 985.41 | 187.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 148.86 |
November | 9456.47 | 24-NOV-07:05 | 0.00 | 1970.82 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 418.04 |
December | 8705.16 | 28-DEC-07:05 | 0.00 | 1970.82 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 240.75 |
Annual Sum or Average | |||||||||||
Minimum of Months | 6466.84 | 0.00 | 788.33 | 149.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18307.53 | 359.95 | 3744.57 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1562.58 | 668.67 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 9480.58 | 21-JAN-07:05 | 0.00 | 1970.82 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 370.88 |
February | 7943.11 | 18-FEB-07:05 | 0.00 | 1970.82 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 180.60 |
March | 8502.99 | 06-MAR-07:05 | 0.00 | 1970.82 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 667.11 |
April | 7309.86 | 01-APR-06:04 | 0.00 | 1576.66 | 299.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.82 |
May | 6780.66 | 31-MAY-15:00 | 359.95 | 3744.57 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1562.57 | 0.00 |
June | 16758.05 | 30-JUN-06:02 | 0.00 | 985.41 | 187.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.43 |
July | 16500.55 | 03-JUL-06:02 | 0.00 | 985.41 | 187.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.07 |
August | 16118.76 | 23-AUG-06:03 | 0.00 | 788.33 | 149.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.82 |
September | 18079.19 | 11-SEP-06:03 | 0.00 | 788.33 | 149.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.34 |
October | 6589.52 | 23-OCT-06:04 | 0.00 | 985.41 | 187.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 149.32 |
November | 7831.73 | 22-NOV-07:04 | 0.00 | 1970.82 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 367.19 |
December | 8412.95 | 04-DEC-07:04 | 0.00 | 1970.82 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 234.55 |
Annual Sum or Average | |||||||||||
Minimum of Months | 6589.52 | 0.00 | 788.33 | 149.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18079.19 | 359.95 | 3744.57 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1562.57 | 667.11 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 248.01 | 13-JAN-12:00 | 1547.80 | 6064.13 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1538.88 |
February | 1086.26 | 24-FEB-12:00 | 1547.80 | 6064.13 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1314.74 |
March | 3215.07 | 24-MAR-17:05 | 2447.68 | 12128.26 | 2696.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1071.87 |
April | 10715.74 | 18-APR-14:10 | 2483.68 | 6064.13 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 2084.08 | 0.00 |
May | 12348.96 | 31-MAY-15:00 | 2483.68 | 6064.13 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 2746.53 | 0.00 |
June | 29503.52 | 12-JUN-07:03 | 0.00 | 1276.66 | 299.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 387.97 |
July | 31809.91 | 03-JUL-07:03 | 0.00 | 1276.66 | 299.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 327.38 |
August | 26879.30 | 23-AUG-07:03 | 0.00 | 1276.66 | 299.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 433.34 |
September | 32925.00 | 11-SEP-07:03 | 0.00 | 1276.66 | 299.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 304.16 |
October | 6239.38 | 22-OCT-09:03 | 1187.85 | 9574.94 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1408.41 |
November | 6863.58 | 15-NOV-20:23 | 1187.85 | 9574.94 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 496.72 |
December | 526.46 | 02-DEC-12:00 | 2087.73 | 6064.13 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1459.22 |
Annual Sum or Average | |||||||||||
Minimum of Months | 248.01 | 0.00 | 1276.66 | 299.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 32925.00 | 2483.68 | 12128.26 | 2696.51 | 0.00 | 0.00 | 0.00 | 0.00 | 2746.53 | 1538.88 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 8664.30 | 18-JAN-08:05 | 0.00 | 1595.82 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2079.68 |
February | 7299.10 | 17-FEB-08:05 | 0.00 | 1595.82 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1619.62 |
March | 7658.28 | 08-MAR-08:05 | 0.00 | 1595.82 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1472.05 |
April | 7299.50 | 03-APR-07:05 | 0.00 | 1595.82 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1482.87 |
May | 6462.01 | 31-MAY-15:00 | 1241.83 | 3032.07 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1562.60 | 0.00 |
June | 16847.39 | 30-JUN-07:02 | 0.00 | 797.91 | 187.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.50 |
July | 16240.92 | 02-JUL-08:62 | 0.00 | 638.33 | 149.81 | 0.00 | 0.00 | 0.00 | 0.00 | 4.09 | 0.00 |
August | 13208.65 | 03-AUG-07:02 | 0.00 | 957.49 | 224.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.07 |
September | 16004.74 | 11-SEP-07:03 | 0.00 | 638.33 | 149.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 169.43 |
October | 5629.41 | 23-OCT-07:03 | 0.00 | 1595.82 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1051.22 |
November | 7150.64 | 12-NOV-09:04 | 0.00 | 1595.82 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1238.86 |
December | 9026.95 | 25-DEC-09:05 | 0.00 | 1595.82 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1657.76 |
Annual Sum or Average | |||||||||||
Minimum of Months | 5629.41 | 0.00 | 638.33 | 149.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16847.39 | 1241.83 | 3032.07 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1562.60 | 2079.68 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 8674.58 | 18-JAN-08:05 | 0.00 | 1595.82 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2079.66 |
February | 7334.12 | 17-FEB-08:05 | 0.00 | 1595.82 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1620.87 |
March | 8139.53 | 13-MAR-07:05 | 0.00 | 1595.82 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1510.68 |
April | 7017.33 | 03-APR-07:05 | 0.00 | 1595.82 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1477.08 |
May | 6346.28 | 31-MAY-15:00 | 1241.83 | 3032.07 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1562.59 | 0.00 |
June | 16799.63 | 30-JUN-07:02 | 0.00 | 797.91 | 187.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.12 |
July | 16191.05 | 02-JUL-08:62 | 0.00 | 638.33 | 149.81 | 0.00 | 0.00 | 0.00 | 0.00 | 6.80 | 0.00 |
August | 13163.91 | 03-AUG-07:02 | 0.00 | 957.49 | 224.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.64 |
September | 15399.09 | 11-SEP-07:03 | 0.00 | 638.33 | 149.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 169.16 |
October | 5706.01 | 23-OCT-07:03 | 0.00 | 1595.82 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1053.49 |
November | 6863.88 | 29-NOV-08:05 | 0.00 | 1595.82 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1500.88 |
December | 8040.88 | 27-DEC-08:05 | 0.00 | 1595.82 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1567.31 |
Annual Sum or Average | |||||||||||
Minimum of Months | 5706.01 | 0.00 | 638.33 | 149.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16799.63 | 1241.83 | 3032.07 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1562.59 | 2079.66 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 8825.38 | 10-JAN-08:05 | 0.00 | 1595.82 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1560.62 |
February | 8856.58 | 15-FEB-08:05 | 0.00 | 1595.82 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1706.55 |
March | 8118.48 | 13-MAR-07:05 | 0.00 | 1595.82 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1510.29 |
April | 7316.35 | 03-APR-07:05 | 0.00 | 1595.82 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1482.29 |
May | 6075.50 | 31-MAY-15:00 | 1241.83 | 3032.07 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1562.58 | 0.00 |
June | 16607.88 | 30-JUN-07:02 | 0.00 | 797.91 | 187.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.14 |
July | 15981.73 | 04-JUL-08:62 | 0.00 | 797.91 | 187.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.66 |
August | 13156.11 | 03-AUG-07:02 | 0.00 | 957.49 | 224.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.87 |
September | 13436.92 | 11-SEP-07:03 | 0.00 | 638.33 | 149.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 168.49 |
October | 5982.12 | 23-OCT-07:03 | 0.00 | 1595.82 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1061.97 |
November | 8179.35 | 21-NOV-08:05 | 0.00 | 1595.82 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1771.34 |
December | 8959.69 | 25-DEC-09:05 | 0.00 | 1595.82 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1657.04 |
Annual Sum or Average | |||||||||||
Minimum of Months | 5982.12 | 0.00 | 638.33 | 149.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16607.88 | 1241.83 | 3032.07 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1562.58 | 1771.34 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6861.98 | 17-JAN-08:05 | 0.00 | 1595.82 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1576.17 |
February | 6503.50 | 13-FEB-08:05 | 0.00 | 1595.82 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1815.41 |
March | 5147.26 | 09-MAR-08:04 | 0.00 | 1595.82 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1087.82 |
April | 5096.48 | 28-APR-07:04 | 0.00 | 1595.82 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1487.44 |
May | 5720.22 | 31-MAY-15:00 | 1241.83 | 3032.07 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1638.66 | 0.00 |
June | 9981.79 | 26-JUN-07:02 | 0.00 | 797.91 | 187.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.83 |
July | 15031.12 | 04-JUL-08:62 | 0.00 | 797.91 | 187.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.75 |
August | 12883.53 | 03-AUG-07:02 | 0.00 | 957.49 | 224.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.23 |
September | 8879.78 | 07-SEP-14:10 | 1241.83 | 3032.07 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 2126.14 | 0.00 |
October | 5534.08 | 23-OCT-07:04 | 0.00 | 1595.82 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1263.36 |
November | 5574.59 | 16-NOV-08:04 | 0.00 | 1595.82 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1352.97 |
December | 7655.98 | 20-DEC-08:05 | 0.00 | 1595.82 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1923.62 |
Annual Sum or Average | |||||||||||
Minimum of Months | 5096.48 | 0.00 | 797.91 | 187.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15031.12 | 1241.83 | 3032.07 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 2126.14 | 1923.62 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | |
January | 0.118887E+12 | 89948.45 | 07-JAN-17:00 | 0.360299E+12 | 445900.79 | 30-JAN-17:00 |
February | 0.106263E+12 | 90545.67 | 06-FEB-18:00 | 0.257047E+12 | 503448.11 | 02-FEB-12:09 |
March | 0.116916E+12 | 86764.07 | 06-MAR-18:49 | 0.165279E+12 | 337864.36 | 06-MAR-08:09 |
April | 0.113868E+12 | 119684.82 | 18-APR-14:30 | 0.825589E+11 | 288376.78 | 03-APR-07:10 |
May | 0.120306E+12 | 123851.27 | 31-MAY-12:39 | 0.613625E+10 | 148340.27 | 02-MAY-07:10 |
June | 0.138977E+12 | 150010.83 | 11-JUN-14:00 | 0.133351E+10 | 46599.97 | 05-JUN-07:10 |
July | 0.151132E+12 | 143880.09 | 26-JUL-15:50 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.152827E+12 | 155969.82 | 04-AUG-13:39 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 0.129765E+12 | 136032.04 | 06-SEP-13:00 | 0.562622E+10 | 142095.09 | 30-SEP-07:10 |
October | 0.116496E+12 | 88566.70 | 23-OCT-17:19 | 0.403581E+11 | 144252.15 | 27-OCT-07:10 |
November | 0.114203E+12 | 88819.44 | 09-NOV-18:49 | 0.154709E+12 | 374375.17 | 25-NOV-17:00 |
December | 0.118765E+12 | 87031.61 | 31-DEC-16:49 | 0.280522E+12 | 420096.14 | 09-DEC-12:09 |
Annual Sum or Average | 0.149840E+13 | 0.135387E+13 | ||||
Minimum of Months | 0.106263E+12 | 86764.07 | 0.00 | 0.00 | ||
Maximum of Months | 0.152827E+12 | 155969.82 | 0.360299E+12 | 503448.11 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.599295E+11 | 0.176211E+11 | 0.108804E+11 | 0.00 | 0.246185E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.583718E+10 | 0.00 |
February | 0.542583E+11 | 0.146821E+11 | 0.985143E+10 | 0.00 | 0.221571E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.531450E+10 | 0.00 |
March | 0.607812E+11 | 0.145482E+11 | 0.110523E+11 | 0.00 | 0.246157E+11 | 0.00 | 0.00 | 22245389.19 | 0.00 | 0.00 | 0.00 | 0.589651E+10 | 0.00 |
April | 0.581548E+11 | 0.123296E+11 | 0.105581E+11 | 0.00 | 0.234438E+11 | 0.00 | 0.00 | 0.379945E+10 | 0.00 | 0.00 | 0.00 | 0.558215E+10 | 0.00 |
May | 0.603309E+11 | 0.112140E+11 | 0.109629E+11 | 0.00 | 0.244103E+11 | 0.00 | 0.00 | 0.774803E+10 | 0.00 | 0.00 | 0.00 | 0.563964E+10 | 0.00 |
June | 0.587570E+11 | 0.100856E+11 | 0.106818E+11 | 0.00 | 0.238450E+11 | 0.00 | 0.00 | 0.302547E+11 | 0.00 | 0.00 | 0.00 | 0.535260E+10 | 0.00 |
July | 0.597776E+11 | 0.107486E+11 | 0.108460E+11 | 0.00 | 0.242213E+11 | 0.00 | 0.00 | 0.401521E+11 | 0.00 | 0.00 | 0.00 | 0.538611E+10 | 0.00 |
August | 0.607324E+11 | 0.120683E+11 | 0.110454E+11 | 0.00 | 0.246844E+11 | 0.00 | 0.00 | 0.388927E+11 | 0.00 | 0.00 | 0.00 | 0.540336E+10 | 0.00 |
September | 0.582036E+11 | 0.132987E+11 | 0.105649E+11 | 0.00 | 0.235278E+11 | 0.00 | 0.00 | 0.189345E+11 | 0.00 | 0.00 | 0.00 | 0.523518E+10 | 0.00 |
October | 0.599295E+11 | 0.155491E+11 | 0.108804E+11 | 0.00 | 0.241411E+11 | 0.00 | 0.00 | 0.482868E+09 | 0.00 | 0.00 | 0.00 | 0.551260E+10 | 0.00 |
November | 0.580572E+11 | 0.166074E+11 | 0.105443E+11 | 0.00 | 0.234883E+11 | 0.00 | 0.00 | 51775649.47 | 0.00 | 0.00 | 0.00 | 0.545352E+10 | 0.00 |
December | 0.598264E+11 | 0.180482E+11 | 0.108529E+11 | 0.00 | 0.242875E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.574965E+10 | 0.00 |
Annual Sum or Average | 0.708738E+12 | 0.166801E+12 | 0.128721E+12 | 0.287441E+12 | 0.00 | 0.140338E+12 | 0.663630E+11 | ||||||
Minimum of Months | 0.542583E+11 | 0.100856E+11 | 0.985143E+10 | 0.00 | 0.221571E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.523518E+10 | 0.00 |
Maximum of Months | 0.607812E+11 | 0.180482E+11 | 0.110523E+11 | 0.00 | 0.246844E+11 | 0.00 | 0.00 | 0.401521E+11 | 0.00 | 0.00 | 0.00 | 0.589651E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS [J] | COOLING:GAS [] | WATERSYSTEMS:GAS [] | COGENERATION:GAS [] | HUMIDIFIER:GAS [] | |
January | 0.00 | 0.00 | 0.360299E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.257047E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.165279E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.825589E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.613625E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.133351E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.562622E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.403581E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.154709E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.280522E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.135387E+13 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.360299E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum}[W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum}[W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum}[W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum}[W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 43732.45 | 01-JAN-11:09 | 10625.34 | 01-JAN-00:10 | 8089.53 | 01-JAN-11:09 | 0.00 | 16727.67 | 01-JAN-09:30 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 43732.45 | 01-FEB-10:09 | 10625.34 | 01-FEB-00:10 | 8089.53 | 01-FEB-10:09 | 0.00 | 16727.67 | 01-FEB-18:19 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 43732.45 | 01-MAR-10:09 | 10625.34 | 01-MAR-00:10 | 8089.53 | 01-MAR-10:09 | 0.00 | 16727.67 | 03-MAR-08:09 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 43732.45 | 01-APR-09:09 | 10625.34 | 01-APR-00:10 | 8089.53 | 01-APR-09:09 | 0.00 | 16727.67 | 02-APR-14:50 | 0.00 | 0.00 | 01-APR-00:10 |
May | 43732.45 | 01-MAY-09:09 | 10625.34 | 01-MAY-00:10 | 8089.53 | 01-MAY-09:09 | 0.00 | 16727.67 | 01-MAY-11:09 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 43732.45 | 01-JUN-09:09 | 10625.34 | 01-JUN-00:10 | 8089.53 | 01-JUN-09:09 | 0.00 | 16727.67 | 01-JUN-10:30 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 43732.45 | 01-JUL-09:09 | 10625.34 | 01-JUL-00:10 | 8089.53 | 01-JUL-09:09 | 0.00 | 16727.67 | 01-JUL-12:09 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 43732.45 | 01-AUG-09:09 | 10625.34 | 01-AUG-00:10 | 8089.53 | 01-AUG-09:09 | 0.00 | 16727.67 | 01-AUG-08:20 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 43732.45 | 01-SEP-09:09 | 10625.34 | 01-SEP-00:10 | 8089.53 | 01-SEP-09:09 | 0.00 | 16727.67 | 01-SEP-14:20 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 43732.45 | 01-OCT-10:09 | 10625.34 | 01-OCT-00:10 | 8089.53 | 01-OCT-10:09 | 0.00 | 16727.67 | 04-OCT-09:20 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 43732.45 | 01-NOV-09:09 | 10625.34 | 01-NOV-00:10 | 8089.53 | 01-NOV-09:09 | 0.00 | 16727.67 | 01-NOV-07:10 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 43732.45 | 01-DEC-10:09 | 10625.34 | 01-DEC-00:10 | 8089.53 | 01-DEC-10:09 | 0.00 | 16727.67 | 01-DEC-14:30 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 43732.45 | 10625.34 | 8089.53 | 0.00 | 16727.67 | 0.00 | 0.00 | |||||
Maximum of Months | 43732.45 | 10625.34 | 8089.53 | 0.00 | 16727.67 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum}[W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum}[W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 11887.04 | 07-JAN-13:00 | 0.00 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 11370.67 | 06-FEB-18:00 | 0.00 |
March | 709.49 | 19-MAR-17:10 | 0.00 | 0.00 | 0.00 | 9736.23 | 11-MAR-12:20 | 0.00 |
April | 45855.52 | 18-APR-14:09 | 0.00 | 0.00 | 0.00 | 9748.06 | 19-APR-12:09 | 0.00 |
May | 48549.12 | 31-MAY-14:00 | 0.00 | 0.00 | 0.00 | 9734.11 | 25-MAY-13:30 | 0.00 |
June | 73971.40 | 11-JUN-14:00 | 0.00 | 0.00 | 0.00 | 9732.55 | 06-JUN-12:39 | 0.00 |
July | 69001.57 | 26-JUL-15:20 | 0.00 | 0.00 | 0.00 | 9715.56 | 25-JUL-12:09 | 0.00 |
August | 82720.41 | 04-AUG-15:00 | 0.00 | 0.00 | 0.00 | 9690.90 | 29-AUG-11:39 | 0.00 |
September | 62140.63 | 06-SEP-14:09 | 0.00 | 0.00 | 0.00 | 9715.71 | 30-SEP-13:39 | 0.00 |
October | 15490.55 | 20-OCT-14:00 | 0.00 | 0.00 | 0.00 | 11829.68 | 27-OCT-11:00 | 0.00 |
November | 862.27 | 08-NOV-22:00 | 0.00 | 0.00 | 0.00 | 9730.41 | 04-NOV-12:09 | 0.00 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 9748.45 | 01-DEC-13:39 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 9690.90 | 0.00 | ||
Maximum of Months | 82720.41 | 0.00 | 0.00 | 0.00 | 11887.04 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 89948.45 | 07-JAN-17:00 | 43732.45 | 8089.53 | 10625.34 | 0.00 | 16727.67 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 90545.67 | 06-FEB-18:00 | 43732.45 | 8089.53 | 10625.34 | 0.00 | 16727.67 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 86764.07 | 06-MAR-18:49 | 43732.45 | 8089.53 | 10625.34 | 0.00 | 16727.67 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 119684.82 | 18-APR-14:30 | 43732.45 | 8089.53 | 0.00 | 0.00 | 16727.67 | 0.00 | 0.00 | 45665.76 | 0.00 |
May | 123851.27 | 31-MAY-12:39 | 43732.45 | 8089.53 | 0.00 | 0.00 | 16727.67 | 0.00 | 0.00 | 47697.24 | 0.00 |
June | 150010.83 | 11-JUN-14:00 | 43732.45 | 8089.53 | 0.00 | 0.00 | 16727.67 | 0.00 | 0.00 | 73971.40 | 0.00 |
July | 143880.09 | 26-JUL-15:50 | 43732.45 | 8089.53 | 0.00 | 0.00 | 16727.67 | 0.00 | 0.00 | 68684.72 | 0.00 |
August | 155969.82 | 04-AUG-13:39 | 43732.45 | 8089.53 | 0.00 | 0.00 | 16727.67 | 0.00 | 0.00 | 81955.40 | 0.00 |
September | 136032.04 | 06-SEP-13:00 | 43732.45 | 8089.53 | 0.00 | 0.00 | 16727.67 | 0.00 | 0.00 | 62018.37 | 0.00 |
October | 88566.70 | 23-OCT-17:19 | 43732.45 | 8089.53 | 10625.34 | 0.00 | 16727.67 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 88819.44 | 09-NOV-18:49 | 43732.45 | 8089.53 | 10625.34 | 0.00 | 16727.67 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 87031.61 | 31-DEC-16:49 | 43732.45 | 8089.53 | 10625.34 | 0.00 | 16727.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 86764.07 | 43732.45 | 8089.53 | 0.00 | 0.00 | 16727.67 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 155969.82 | 43732.45 | 8089.53 | 10625.34 | 0.00 | 16727.67 | 0.00 | 0.00 | 81955.40 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS {Maximum}[W] | HEATING:GAS {TIMESTAMP} | COOLING:GAS [] | WATERSYSTEMS:GAS [] | COGENERATION:GAS [] | |
January | 0.00 | 0.00 | 445900.79 | 30-JAN-17:00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 503448.11 | 02-FEB-12:09 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 337864.36 | 06-MAR-08:09 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 288376.78 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 148340.27 | 02-MAY-07:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 46599.97 | 05-JUN-07:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 142095.09 | 30-SEP-07:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 144252.15 | 27-OCT-07:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 374375.17 | 25-NOV-17:00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 420096.14 | 09-DEC-12:09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 503448.11 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 15.33 | 17.10 | 2.83 | 20.33 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 10.00 | 17.04 | 1.67 | 20.34 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 4.17 | 19.42 | 1.33 | 20.34 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.83 | 20.45 | 0.17 | 20.33 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.17 | 20.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 2.00 | 20.17 | 0.83 | 20.34 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 8.00 | 17.83 | 1.33 | 20.38 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 40.50 | 17.70 | 8.17 | 20.34 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 15.33 | 20.55 | 2.83 | 20.38 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 5.17 | 20.13 | 2.00 | 20.10 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 2.50 | 20.06 | 1.00 | 19.99 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 1.17 | 20.34 | 0.50 | 20.34 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.17 | 20.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1.67 | 20.33 | 0.50 | 20.25 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1.67 | 20.11 | 0.83 | 20.08 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 12.33 | 20.17 | 4.83 | 20.12 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 5.17 | 20.53 | 2.00 | 20.34 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 7.17 | 18.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3.83 | 18.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 1.33 | 20.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.17 | 20.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1.17 | 20.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 3.33 | 18.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 17.00 | 18.49 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 7.17 | 20.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 9.00 | 17.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4.67 | 17.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 1.83 | 19.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.17 | 20.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1.17 | 20.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5.00 | 17.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 21.83 | 17.95 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 9.00 | 20.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 10.00 | 17.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5.17 | 17.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 2.00 | 19.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.33 | 20.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1.50 | 20.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7.00 | 17.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 26.00 | 17.76 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 10.00 | 20.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 13.33 | 16.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 9.67 | 16.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 2.67 | 18.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.17 | 20.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 2.33 | 18.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 9.83 | 16.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.00 | 16.92 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 13.33 | 20.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 13.17 | 16.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 8.00 | 17.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 3.33 | 18.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.50 | 20.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 2.17 | 19.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 10.33 | 17.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 37.50 | 17.32 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 13.17 | 20.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 14.00 | 16.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 8.33 | 16.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 3.50 | 18.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.50 | 20.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 2.17 | 19.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 10.33 | 17.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.83 | 17.25 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 14.00 | 20.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 17.33 | 16.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 12.33 | 16.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 4.17 | 18.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 1.00 | 19.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 3.17 | 18.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 12.00 | 17.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 50.00 | 16.95 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 17.33 | 19.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 63.83 | 14.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 43.33 | 15.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 25.50 | 15.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7.00 | 16.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.33 | 20.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.17 | 20.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 20.33 | 15.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 38.17 | 15.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 198.67 | 15.24 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 63.83 | 20.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: LGSTORE1
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 496.00 | 21.04 | 469.67 | 21.03 | 469.67 | 21.03 |
February | 448.00 | 21.04 | 328.83 | 21.02 | 328.83 | 21.02 |
March | 494.67 | 21.19 | 262.83 | 21.02 | 262.83 | 21.02 |
April | 411.17 | 21.42 | 159.67 | 21.92 | 109.00 | 21.00 |
May | 207.33 | 22.57 | 210.00 | 23.83 | 16.17 | 23.15 |
June | 132.17 | 23.14 | 373.83 | 23.89 | 58.83 | 23.89 |
July | 122.00 | 23.89 | 488.50 | 23.89 | 121.67 | 23.89 |
August | 136.50 | 23.89 | 477.00 | 23.89 | 134.00 | 23.89 |
September | 139.17 | 22.14 | 262.50 | 23.85 | 5.83 | 22.27 |
October | 426.50 | 21.55 | 41.67 | 22.35 | 21.50 | 20.92 |
November | 468.67 | 21.34 | 177.67 | 21.03 | 177.67 | 21.03 |
December | 496.00 | 21.03 | 434.67 | 21.02 | 434.67 | 21.02 |
Annual Sum or Average | 3978.17 | 21.56 | 3686.83 | 22.48 | 2140.67 | 21.46 |
Minimum of Months | 122.00 | 21.03 | 41.67 | 21.02 | 5.83 | 20.92 |
Maximum of Months | 496.00 | 23.89 | 488.50 | 23.89 | 469.67 | 23.89 |
Report: ComfortReportSimple55Monthly
For: SMSTORE1
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 496.00 | 21.14 | 416.17 | 21.10 | 416.17 | 21.10 |
February | 448.00 | 21.26 | 248.83 | 21.10 | 248.83 | 21.10 |
March | 488.67 | 21.52 | 156.83 | 21.12 | 156.83 | 21.12 |
April | 403.67 | 21.87 | 90.00 | 22.68 | 39.00 | 21.11 |
May | 153.17 | 22.60 | 191.17 | 23.86 | 1.50 | 21.12 |
June | 60.17 | 22.71 | 358.67 | 23.89 | 8.00 | 23.89 |
July | 22.00 | 23.87 | 471.50 | 23.89 | 20.67 | 23.89 |
August | 30.83 | 23.84 | 457.33 | 23.89 | 27.00 | 23.89 |
September | 127.33 | 22.42 | 236.33 | 23.88 | 0.00 | 0.00 |
October | 413.17 | 22.08 | 22.83 | 23.10 | 6.50 | 21.11 |
November | 459.50 | 21.66 | 131.50 | 21.11 | 131.50 | 21.11 |
December | 496.00 | 21.26 | 296.83 | 21.11 | 296.83 | 21.11 |
Annual Sum or Average | 3598.50 | 21.65 | 3078.00 | 22.71 | 1352.83 | 21.22 |
Minimum of Months | 22.00 | 21.14 | 22.83 | 21.10 | 0.00 | 0.00 |
Maximum of Months | 496.00 | 23.87 | 471.50 | 23.89 | 416.17 | 23.89 |
Report: ComfortReportSimple55Monthly
For: SMSTORE2
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 371.00 | 21.11 | 351.67 | 21.11 | 351.67 | 21.11 |
February | 336.00 | 21.11 | 254.83 | 21.11 | 254.83 | 21.11 |
March | 379.00 | 21.20 | 196.00 | 21.11 | 196.00 | 21.11 |
April | 311.83 | 21.38 | 107.50 | 22.04 | 74.33 | 21.13 |
May | 174.50 | 22.37 | 133.33 | 23.94 | 3.50 | 22.47 |
June | 84.67 | 22.71 | 274.67 | 24.08 | 15.50 | 24.74 |
July | 37.33 | 24.44 | 363.50 | 24.07 | 36.67 | 24.46 |
August | 51.50 | 24.11 | 358.67 | 24.04 | 47.17 | 24.19 |
September | 121.67 | 21.94 | 175.33 | 24.03 | 2.33 | 22.04 |
October | 340.00 | 21.47 | 13.83 | 21.31 | 12.83 | 21.11 |
November | 360.00 | 21.30 | 149.83 | 21.11 | 149.83 | 21.11 |
December | 369.00 | 21.11 | 337.00 | 21.11 | 337.00 | 21.11 |
Annual Sum or Average | 2936.50 | 21.47 | 2716.17 | 22.56 | 1481.67 | 21.33 |
Minimum of Months | 37.33 | 21.11 | 13.83 | 21.11 | 2.33 | 21.11 |
Maximum of Months | 379.00 | 24.44 | 363.50 | 24.08 | 351.67 | 24.74 |
Report: ComfortReportSimple55Monthly
For: SMSTORE3
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 371.00 | 21.11 | 353.17 | 21.11 | 353.17 | 21.11 |
February | 336.00 | 21.11 | 275.50 | 21.11 | 275.50 | 21.11 |
March | 379.00 | 21.19 | 209.00 | 21.11 | 209.00 | 21.11 |
April | 312.83 | 21.36 | 113.83 | 21.90 | 84.00 | 21.12 |
May | 188.83 | 22.34 | 123.33 | 23.90 | 4.83 | 22.16 |
June | 87.67 | 22.63 | 271.83 | 24.07 | 15.67 | 24.72 |
July | 38.67 | 24.41 | 363.17 | 24.06 | 37.33 | 24.44 |
August | 53.00 | 24.09 | 357.17 | 24.04 | 48.33 | 24.18 |
September | 127.50 | 21.92 | 171.00 | 24.02 | 2.50 | 21.55 |
October | 348.17 | 21.46 | 18.00 | 21.11 | 18.00 | 21.11 |
November | 360.00 | 21.25 | 165.50 | 21.11 | 165.50 | 21.11 |
December | 369.00 | 21.11 | 345.33 | 21.11 | 345.33 | 21.11 |
Annual Sum or Average | 2971.67 | 21.46 | 2766.83 | 22.50 | 1559.17 | 21.33 |
Minimum of Months | 38.67 | 21.11 | 18.00 | 21.11 | 2.50 | 21.11 |
Maximum of Months | 379.00 | 24.41 | 363.17 | 24.07 | 353.17 | 24.72 |
Report: ComfortReportSimple55Monthly
For: SMSTORE4
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 371.00 | 21.11 | 354.00 | 21.11 | 354.00 | 21.11 |
February | 336.00 | 21.11 | 284.00 | 21.11 | 284.00 | 21.11 |
March | 379.00 | 21.18 | 228.67 | 21.11 | 228.67 | 21.11 |
April | 314.33 | 21.34 | 118.33 | 21.82 | 90.67 | 21.12 |
May | 202.17 | 22.30 | 114.00 | 23.86 | 6.00 | 22.09 |
June | 90.83 | 22.57 | 268.67 | 24.07 | 16.67 | 24.63 |
July | 40.83 | 24.38 | 361.83 | 24.06 | 38.83 | 24.43 |
August | 58.33 | 24.06 | 355.33 | 24.04 | 52.67 | 24.15 |
September | 132.00 | 21.91 | 169.00 | 24.01 | 2.83 | 21.49 |
October | 355.00 | 21.46 | 22.17 | 21.11 | 22.17 | 21.11 |
November | 360.00 | 21.22 | 175.50 | 21.11 | 175.50 | 21.11 |
December | 369.00 | 21.11 | 348.00 | 21.11 | 348.00 | 21.11 |
Annual Sum or Average | 3008.50 | 21.46 | 2799.50 | 22.46 | 1620.00 | 21.33 |
Minimum of Months | 40.83 | 21.11 | 22.17 | 21.11 | 2.83 | 21.11 |
Maximum of Months | 379.00 | 24.38 | 361.83 | 24.07 | 354.00 | 24.63 |
Report: ComfortReportSimple55Monthly
For: LGSTORE2
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.11 | 332.33 | 21.11 | 332.33 | 21.11 |
February | 308.00 | 21.11 | 281.67 | 21.11 | 281.67 | 21.11 |
March | 348.00 | 21.16 | 228.67 | 21.11 | 228.67 | 21.11 |
April | 290.17 | 21.34 | 126.00 | 21.73 | 100.83 | 21.14 |
May | 206.67 | 22.37 | 93.67 | 23.79 | 13.83 | 23.10 |
June | 110.00 | 22.81 | 248.50 | 23.96 | 43.00 | 24.12 |
July | 84.67 | 23.99 | 334.67 | 23.96 | 84.67 | 23.99 |
August | 96.00 | 23.94 | 333.17 | 23.94 | 95.17 | 23.94 |
September | 121.67 | 21.88 | 159.33 | 23.94 | 2.83 | 21.93 |
October | 331.17 | 21.44 | 19.00 | 21.11 | 19.00 | 21.11 |
November | 330.00 | 21.18 | 191.83 | 21.11 | 191.83 | 21.11 |
December | 338.00 | 21.11 | 328.00 | 21.11 | 328.00 | 21.11 |
Annual Sum or Average | 2904.33 | 21.55 | 2676.83 | 22.37 | 1721.83 | 21.50 |
Minimum of Months | 84.67 | 21.11 | 19.00 | 21.11 | 2.83 | 21.11 |
Maximum of Months | 348.00 | 23.99 | 334.67 | 23.96 | 332.33 | 24.12 |
Report: ComfortReportSimple55Monthly
For: SMSTORE5
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.11 | 331.83 | 21.11 | 331.83 | 21.11 |
February | 308.00 | 21.11 | 281.33 | 21.11 | 281.33 | 21.11 |
March | 348.00 | 21.16 | 231.83 | 21.11 | 231.83 | 21.11 |
April | 290.33 | 21.33 | 127.67 | 21.68 | 103.17 | 21.11 |
May | 211.83 | 22.31 | 74.67 | 23.76 | 10.00 | 22.61 |
June | 94.67 | 22.57 | 222.33 | 23.97 | 24.33 | 24.26 |
July | 39.50 | 24.07 | 330.00 | 23.96 | 38.83 | 24.08 |
August | 57.67 | 23.95 | 319.00 | 23.94 | 54.17 | 23.98 |
September | 125.83 | 21.88 | 146.67 | 23.94 | 2.33 | 21.11 |
October | 333.50 | 21.46 | 21.17 | 21.11 | 21.17 | 21.11 |
November | 330.00 | 21.19 | 193.00 | 21.11 | 193.00 | 21.11 |
December | 338.00 | 21.11 | 328.17 | 21.11 | 328.17 | 21.11 |
Annual Sum or Average | 2817.33 | 21.46 | 2607.67 | 22.32 | 1620.17 | 21.33 |
Minimum of Months | 39.50 | 21.11 | 21.17 | 21.11 | 2.33 | 21.11 |
Maximum of Months | 348.00 | 24.07 | 331.83 | 23.97 | 331.83 | 24.26 |
Report: ComfortReportSimple55Monthly
For: SMSTORE6
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.11 | 332.67 | 21.11 | 332.67 | 21.11 |
February | 308.00 | 21.11 | 282.67 | 21.11 | 282.67 | 21.11 |
March | 348.00 | 21.16 | 235.50 | 21.11 | 235.50 | 21.11 |
April | 291.17 | 21.33 | 133.17 | 21.63 | 109.83 | 21.11 |
May | 222.17 | 22.28 | 69.17 | 23.73 | 10.50 | 22.55 |
June | 96.83 | 22.54 | 218.17 | 23.97 | 25.17 | 24.22 |
July | 41.17 | 24.06 | 328.67 | 23.96 | 40.33 | 24.07 |
August | 60.33 | 23.92 | 315.17 | 23.94 | 55.50 | 23.97 |
September | 128.00 | 21.87 | 144.83 | 23.94 | 2.50 | 21.11 |
October | 335.17 | 21.46 | 22.50 | 21.11 | 22.50 | 21.11 |
November | 330.00 | 21.18 | 196.67 | 21.11 | 196.67 | 21.11 |
December | 338.00 | 21.11 | 328.67 | 21.11 | 328.67 | 21.11 |
Annual Sum or Average | 2838.83 | 21.47 | 2607.83 | 22.30 | 1642.50 | 21.34 |
Minimum of Months | 41.17 | 21.11 | 22.50 | 21.11 | 2.50 | 21.11 |
Maximum of Months | 348.00 | 24.06 | 332.67 | 23.97 | 332.67 | 24.22 |
Report: ComfortReportSimple55Monthly
For: SMSTORE7
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.11 | 334.83 | 21.11 | 334.83 | 21.11 |
February | 308.00 | 21.11 | 287.83 | 21.11 | 287.83 | 21.11 |
March | 348.00 | 21.15 | 245.17 | 21.11 | 245.17 | 21.11 |
April | 295.33 | 21.32 | 163.17 | 21.51 | 141.50 | 21.11 |
May | 252.00 | 22.25 | 64.00 | 23.63 | 12.67 | 22.37 |
June | 103.33 | 22.50 | 209.67 | 23.97 | 28.50 | 24.18 |
July | 47.67 | 24.01 | 325.17 | 23.96 | 45.17 | 24.04 |
August | 65.00 | 23.90 | 310.17 | 23.94 | 58.67 | 23.97 |
September | 133.50 | 21.86 | 142.33 | 23.93 | 2.83 | 21.11 |
October | 337.33 | 21.44 | 29.17 | 21.11 | 29.17 | 21.11 |
November | 330.00 | 21.17 | 206.17 | 21.11 | 206.17 | 21.11 |
December | 338.00 | 21.11 | 331.33 | 21.11 | 331.33 | 21.11 |
Annual Sum or Average | 2898.17 | 21.47 | 2649.00 | 22.25 | 1723.83 | 21.34 |
Minimum of Months | 47.67 | 21.11 | 29.17 | 21.11 | 2.83 | 21.11 |
Maximum of Months | 348.00 | 24.01 | 334.83 | 23.97 | 334.83 | 24.18 |
Report: ComfortReportSimple55Monthly
For: SMSTORE8
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.11 | 340.00 | 21.11 | 340.00 | 21.11 |
February | 308.00 | 21.11 | 304.00 | 21.11 | 304.00 | 21.11 |
March | 348.00 | 21.12 | 291.83 | 21.11 | 291.83 | 21.11 |
April | 304.50 | 21.32 | 223.17 | 21.33 | 207.17 | 21.11 |
May | 289.17 | 22.08 | 62.67 | 22.87 | 28.33 | 21.60 |
June | 121.50 | 22.47 | 180.00 | 23.96 | 38.50 | 23.98 |
July | 70.17 | 23.86 | 311.00 | 23.96 | 60.00 | 23.98 |
August | 84.33 | 23.83 | 298.83 | 23.94 | 71.33 | 23.95 |
September | 147.83 | 21.88 | 138.50 | 23.83 | 7.67 | 21.11 |
October | 340.00 | 21.40 | 64.17 | 21.11 | 64.17 | 21.11 |
November | 330.00 | 21.15 | 229.83 | 21.11 | 229.83 | 21.11 |
December | 338.00 | 21.11 | 338.00 | 21.11 | 338.00 | 21.11 |
Annual Sum or Average | 3021.50 | 21.49 | 2782.00 | 22.11 | 1980.83 | 21.36 |
Minimum of Months | 70.17 | 21.11 | 62.67 | 21.11 | 7.67 | 21.11 |
Maximum of Months | 348.00 | 23.86 | 340.00 | 23.96 | 340.00 | 23.98 |
Report: OccupantComfortDataSummaryMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 496.00000 | 21.00750 | 9.88123 | -0.7389 | 17.02931 |
February | 448.00000 | 21.02038 | 14.40611 | -0.6635 | 14.92232 |
March | 496.00000 | 21.17556 | 20.96876 | -0.5238 | 11.87147 |
April | 480.00000 | 21.76359 | 29.28900 | -0.2657 | 9.66123 |
May | 496.00000 | 23.31530 | 42.80226 | -0.6698 | 17.23710 |
June | 480.00000 | 23.67230 | 50.34219 | -0.3956 | 9.84704 |
July | 496.00000 | 23.89465 | 55.87792 | -0.2354 | 6.32411 |
August | 496.00000 | 23.89249 | 54.06571 | -0.2450 | 6.48883 |
September | 480.00000 | 23.37893 | 37.71120 | -0.5773 | 15.50803 |
October | 496.00000 | 21.87128 | 28.43631 | -0.1669 | 7.37371 |
November | 480.00000 | 21.38011 | 22.03346 | -0.4259 | 10.74637 |
December | 496.00000 | 21.01459 | 12.65962 | -0.6712 | 14.96701 |
Annual Sum or Average | 5840.00000 | 22.28967 | 31.64409 | -0.4638 | 11.81025 |
Minimum of Months | 448.00000 | 21.00750 | 9.88123 | -0.7389 | 6.32411 |
Maximum of Months | 496.00000 | 23.89465 | 55.87792 | -0.1669 | 17.23710 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 496.00000 | 21.11158 | 10.47289 | -0.6599 | 14.60863 |
February | 448.00000 | 21.22746 | 14.96442 | -0.5677 | 12.46235 |
March | 496.00000 | 21.52537 | 21.26958 | -0.4082 | 9.81219 |
April | 480.00000 | 22.16797 | 29.01009 | -0.1549 | 8.24662 |
May | 496.00000 | 23.46238 | 40.22805 | -0.6255 | 15.32328 |
June | 480.00000 | 23.72581 | 46.39795 | -0.4111 | 9.66958 |
July | 496.00000 | 23.89262 | 49.63909 | -0.2951 | 7.02340 |
August | 496.00000 | 23.88721 | 48.05693 | -0.3084 | 7.23465 |
September | 480.00000 | 23.49162 | 35.86509 | -0.5742 | 14.44697 |
October | 496.00000 | 22.35728 | 28.45600 | -0.0700 | 6.74435 |
November | 480.00000 | 21.72317 | 22.24930 | -0.3337 | 9.34610 |
December | 496.00000 | 21.23051 | 13.30902 | -0.5794 | 12.55111 |
Annual Sum or Average | 5840.00000 | 22.49069 | 30.07960 | -0.4149 | 10.60945 |
Minimum of Months | 448.00000 | 21.11158 | 10.47289 | -0.6599 | 6.74435 |
Maximum of Months | 496.00000 | 23.89262 | 49.63909 | -0.0700 | 15.32328 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 21.10989 | 9.25909 | -0.7185 | 16.08599 |
February | 336.00000 | 21.10985 | 13.97590 | -0.6423 | 14.02407 |
March | 379.00000 | 21.19781 | 20.22959 | -0.5192 | 11.27804 |
April | 360.00000 | 21.72454 | 28.90826 | -0.2776 | 9.35406 |
May | 375.00000 | 23.17663 | 42.36392 | -0.7416 | 19.54454 |
June | 366.00000 | 23.67795 | 48.52787 | -0.4429 | 11.50260 |
July | 369.00000 | 24.02215 | 52.68817 | -0.2633 | 6.86950 |
August | 379.00000 | 23.98956 | 50.76995 | -0.2865 | 7.12662 |
September | 360.00000 | 23.27626 | 36.84474 | -0.6614 | 18.34111 |
October | 371.00000 | 21.66307 | 28.79489 | -0.2359 | 7.47756 |
November | 360.00000 | 21.29283 | 22.65487 | -0.4581 | 10.58305 |
December | 369.00000 | 21.10997 | 12.10776 | -0.6592 | 14.35455 |
Annual Sum or Average | 4395.00000 | 22.28999 | 30.74106 | -0.4912 | 12.19124 |
Minimum of Months | 336.00000 | 21.10985 | 9.25909 | -0.7416 | 6.86950 |
Maximum of Months | 379.00000 | 24.02215 | 52.68817 | -0.2359 | 19.54454 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 21.10996 | 9.25821 | -0.7322 | 16.49507 |
February | 336.00000 | 21.10979 | 13.97550 | -0.6570 | 14.41247 |
March | 379.00000 | 21.18436 | 20.25627 | -0.5371 | 11.63074 |
April | 360.00000 | 21.69647 | 29.00056 | -0.2971 | 9.56553 |
May | 375.00000 | 23.09427 | 42.70275 | -0.7816 | 20.94929 |
June | 366.00000 | 23.64968 | 48.69910 | -0.4585 | 12.01096 |
July | 369.00000 | 24.01937 | 52.79791 | -0.2679 | 6.92196 |
August | 379.00000 | 23.98592 | 50.88543 | -0.2919 | 7.19603 |
September | 360.00000 | 23.23721 | 36.95928 | -0.6823 | 19.14307 |
October | 371.00000 | 21.59651 | 28.94245 | -0.2643 | 7.66729 |
November | 360.00000 | 21.24773 | 22.76453 | -0.4836 | 10.94636 |
December | 369.00000 | 21.10997 | 12.10755 | -0.6740 | 14.76216 |
Annual Sum or Average | 4395.00000 | 22.26409 | 30.84396 | -0.5096 | 12.62148 |
Minimum of Months | 336.00000 | 21.10979 | 9.25821 | -0.7816 | 6.92196 |
Maximum of Months | 379.00000 | 24.01937 | 52.79791 | -0.2643 | 20.94929 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 21.10985 | 9.25754 | -0.7429 | 16.82987 |
February | 336.00000 | 21.10989 | 13.97489 | -0.6689 | 14.74571 |
March | 379.00000 | 21.17500 | 20.27416 | -0.5514 | 11.93991 |
April | 360.00000 | 21.67325 | 29.08363 | -0.3126 | 9.74910 |
May | 375.00000 | 23.01712 | 43.01898 | -0.8156 | 22.18586 |
June | 366.00000 | 23.62463 | 48.91911 | -0.4719 | 12.43100 |
July | 369.00000 | 24.01543 | 53.01276 | -0.2730 | 6.98047 |
August | 379.00000 | 23.98117 | 51.08307 | -0.2973 | 7.26863 |
September | 360.00000 | 23.20683 | 37.07938 | -0.6975 | 19.71717 |
October | 371.00000 | 21.55347 | 29.03966 | -0.2826 | 7.80985 |
November | 360.00000 | 21.22134 | 22.82882 | -0.5008 | 11.23734 |
December | 369.00000 | 21.10997 | 12.10710 | -0.6864 | 15.11868 |
Annual Sum or Average | 4395.00000 | 22.24369 | 30.95586 | -0.5241 | 12.98140 |
Minimum of Months | 336.00000 | 21.10985 | 9.25754 | -0.8156 | 6.98047 |
Maximum of Months | 379.00000 | 24.01543 | 53.01276 | -0.2730 | 22.18586 |
Report: OccupantComfortDataSummaryMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.10992 | 9.90725 | -0.7783 | 17.94448 |
February | 308.00000 | 21.10993 | 14.62542 | -0.7039 | 15.73288 |
March | 348.00000 | 21.16043 | 21.02265 | -0.5844 | 12.69019 |
April | 330.00000 | 21.65367 | 29.92234 | -0.3379 | 10.17575 |
May | 344.00000 | 22.95786 | 44.48006 | -0.8457 | 23.11978 |
June | 336.00000 | 23.54657 | 51.05822 | -0.4856 | 12.74032 |
July | 338.00000 | 23.94285 | 56.17483 | -0.2725 | 6.80816 |
August | 348.00000 | 23.92053 | 54.36173 | -0.2909 | 7.01765 |
September | 330.00000 | 23.18000 | 38.06342 | -0.7034 | 19.92555 |
October | 340.00000 | 21.50482 | 29.81936 | -0.3052 | 7.96756 |
November | 330.00000 | 21.18479 | 23.48123 | -0.5369 | 11.97164 |
December | 338.00000 | 21.10993 | 12.73398 | -0.7247 | 16.24229 |
Annual Sum or Average | 4030.00000 | 22.20896 | 32.30209 | -0.5463 | 13.50452 |
Minimum of Months | 308.00000 | 21.10992 | 9.90725 | -0.8457 | 6.80816 |
Maximum of Months | 348.00000 | 23.94285 | 56.17483 | -0.2725 | 23.11978 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.10994 | 9.76686 | -0.7684 | 17.61490 |
February | 308.00000 | 21.10994 | 14.51981 | -0.6978 | 15.53449 |
March | 348.00000 | 21.16124 | 20.91813 | -0.5845 | 12.66072 |
April | 330.00000 | 21.64527 | 29.81150 | -0.3466 | 10.17922 |
May | 344.00000 | 22.88653 | 44.23454 | -0.8897 | 24.72917 |
June | 336.00000 | 23.52607 | 49.85218 | -0.5253 | 13.59232 |
July | 338.00000 | 23.94024 | 53.98352 | -0.3148 | 7.35469 |
August | 348.00000 | 23.91415 | 51.95628 | -0.3361 | 7.63995 |
September | 330.00000 | 23.14438 | 37.60780 | -0.7409 | 21.00875 |
October | 340.00000 | 21.50341 | 29.78280 | -0.3159 | 8.09858 |
November | 330.00000 | 21.18599 | 23.43704 | -0.5378 | 11.93769 |
December | 338.00000 | 21.10994 | 12.63948 | -0.7171 | 15.99841 |
Annual Sum or Average | 4030.00000 | 22.19684 | 31.69912 | -0.5637 | 13.84380 |
Minimum of Months | 308.00000 | 21.10994 | 9.76686 | -0.8897 | 7.35469 |
Maximum of Months | 348.00000 | 23.94024 | 53.98352 | -0.3148 | 24.72917 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.10994 | 9.76662 | -0.7700 | 17.66334 |
February | 308.00000 | 21.10995 | 14.51977 | -0.7005 | 15.60983 |
March | 348.00000 | 21.15774 | 20.92546 | -0.5893 | 12.76384 |
April | 330.00000 | 21.63345 | 29.85786 | -0.3547 | 10.26864 |
May | 344.00000 | 22.82255 | 44.47718 | -0.9191 | 25.86604 |
June | 336.00000 | 23.50995 | 49.99191 | -0.5363 | 13.94970 |
July | 338.00000 | 23.93833 | 54.11263 | -0.3198 | 7.42404 |
August | 348.00000 | 23.91235 | 52.06843 | -0.3411 | 7.71699 |
September | 330.00000 | 23.12535 | 37.67956 | -0.7524 | 21.43162 |
October | 340.00000 | 21.48921 | 29.81538 | -0.3236 | 8.17438 |
November | 330.00000 | 21.18047 | 23.44961 | -0.5428 | 12.02724 |
December | 338.00000 | 21.10994 | 12.63950 | -0.7195 | 16.07089 |
Annual Sum or Average | 4030.00000 | 22.18525 | 31.76606 | -0.5716 | 14.06361 |
Minimum of Months | 308.00000 | 21.10994 | 9.76662 | -0.9191 | 7.42404 |
Maximum of Months | 348.00000 | 23.93833 | 54.11263 | -0.3198 | 25.86604 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.10994 | 9.76475 | -0.7791 | 17.95955 |
February | 308.00000 | 21.10995 | 14.51847 | -0.7129 | 15.97209 |
March | 348.00000 | 21.14729 | 20.94555 | -0.6074 | 13.18026 |
April | 330.00000 | 21.59885 | 29.98956 | -0.3804 | 10.61563 |
May | 344.00000 | 22.66984 | 45.04212 | -0.9881 | 28.65385 |
June | 336.00000 | 23.47032 | 50.34826 | -0.5610 | 14.80858 |
July | 338.00000 | 23.93152 | 54.44088 | -0.3292 | 7.57348 |
August | 348.00000 | 23.90685 | 52.33733 | -0.3493 | 7.86463 |
September | 330.00000 | 23.08662 | 37.83445 | -0.7741 | 22.28562 |
October | 340.00000 | 21.45402 | 29.89469 | -0.3432 | 8.39969 |
November | 330.00000 | 21.16810 | 23.47631 | -0.5577 | 12.33680 |
December | 338.00000 | 21.10994 | 12.63877 | -0.7308 | 16.41384 |
Annual Sum or Average | 4030.00000 | 22.15697 | 31.92850 | -0.5920 | 14.65857 |
Minimum of Months | 308.00000 | 21.10994 | 9.76475 | -0.9881 | 7.57348 |
Maximum of Months | 348.00000 | 23.93152 | 54.44088 | -0.3292 | 28.65385 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.10995 | 9.67132 | -0.8513 | 20.47692 |
February | 308.00000 | 21.10996 | 14.43677 | -0.7896 | 18.44192 |
March | 348.00000 | 21.12287 | 20.89575 | -0.6908 | 15.41701 |
April | 330.00000 | 21.52110 | 30.20966 | -0.4769 | 12.40082 |
May | 344.00000 | 22.35433 | 46.06853 | -1.1603 | 36.14857 |
June | 336.00000 | 23.38022 | 51.09775 | -0.6318 | 17.36943 |
July | 338.00000 | 23.90565 | 55.19495 | -0.3568 | 8.09969 |
August | 348.00000 | 23.88465 | 52.90790 | -0.3690 | 8.30963 |
September | 330.00000 | 23.00550 | 38.07961 | -0.8228 | 24.44538 |
October | 340.00000 | 21.39867 | 29.94001 | -0.3980 | 9.24700 |
November | 330.00000 | 21.14615 | 23.47628 | -0.6173 | 13.83022 |
December | 338.00000 | 21.10996 | 12.56200 | -0.7964 | 18.55445 |
Annual Sum or Average | 4030.00000 | 22.09686 | 32.20817 | -0.6627 | 16.88503 |
Minimum of Months | 308.00000 | 21.10995 | 9.67132 | -1.1603 | 8.09969 |
Maximum of Months | 348.00000 | 23.90565 | 55.19495 | -0.3568 | 36.14857 |
Report: DXReportMonthly
For: PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 |
March | 640.03 | 209.23 | 0.75 | 481.88 | 158.15 | 0.00 | 0.00 | 19-MAR-17:50 | 0.00 | 01-MAR-00:02 | 0.48 | 19-MAR-17:50 | 0.36 | 19-MAR-17:50 | 0.12 | 19-MAR-17:50 | 0.16 | 19-MAR-17:50 | 0.00 | 01-MAR-00:02 |
April | 0.257723E+10 | 0.808937E+09 | 62.50 | 0.180419E+10 | 0.773041E+09 | 0.00 | 0.55 | 16-APR-16:04 | 0.00 | 01-APR-00:05 | 27358.79 | 16-APR-16:10 | 19634.93 | 16-APR-16:04 | 8379.27 | 18-APR-12:30 | 8571.41 | 16-APR-16:04 | 0.00 | 01-APR-00:05 |
May | 0.433135E+10 | 0.135219E+10 | 188.92 | 0.303237E+10 | 0.129898E+10 | 0.00 | 0.56 | 31-MAY-15:00 | 0.00 | 01-MAY-00:10 | 26718.10 | 31-MAY-15:00 | 21192.80 | 31-MAY-15:00 | 9670.06 | 29-MAY-14:00 | 8652.33 | 31-MAY-15:00 | 0.00 | 01-MAY-00:10 |
June | 0.198725E+11 | 0.612844E+10 | 344.28 | 0.135169E+11 | 0.635562E+10 | 0.00 | 1.00 | 26-JUN-07:02 | 0.00 | 01-JUN-00:10 | 61330.92 | 26-JUN-07:02 | 33084.61 | 26-JUN-07:02 | 29889.85 | 30-JUN-07:02 | 14931.55 | 27-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.273725E+11 | 0.822740E+10 | 451.66 | 0.173264E+11 | 0.100460E+11 | 0.00 | 1.00 | 04-JUL-07:02 | 0.00 | 01-JUL-00:05 | 60637.02 | 07-JUL-07:03 | 30888.49 | 26-JUL-07:03 | 33703.93 | 07-JUL-07:03 | 14599.56 | 26-JUL-07:03 | 0.00 | 01-JUL-00:05 |
August | 0.245592E+11 | 0.741024E+10 | 436.92 | 0.159154E+11 | 0.864378E+10 | 0.00 | 1.00 | 03-AUG-07:02 | 0.00 | 01-AUG-00:10 | 62929.30 | 03-AUG-07:02 | 30152.00 | 04-AUG-07:02 | 33270.58 | 03-AUG-07:02 | 15008.54 | 03-AUG-07:02 | 0.00 | 01-AUG-00:10 |
September | 0.114965E+11 | 0.361005E+10 | 273.10 | 0.918420E+10 | 0.231233E+10 | 0.00 | 0.93 | 11-SEP-07:03 | 0.00 | 01-SEP-00:10 | 52860.94 | 11-SEP-07:03 | 29222.12 | 11-SEP-07:03 | 23638.82 | 11-SEP-07:03 | 13158.61 | 11-SEP-07:03 | 0.00 | 01-SEP-00:10 |
October | 0.113107E+09 | 36147069.63 | 45.00 | 0.103810E+09 | 9297374.07 | 0.00 | 0.23 | 20-OCT-15:00 | 0.00 | 01-OCT-00:05 | 9568.85 | 20-OCT-15:00 | 9111.04 | 20-OCT-15:00 | 862.64 | 21-OCT-15:00 | 3057.13 | 20-OCT-15:00 | 0.00 | 01-OCT-00:05 |
November | 8931.74 | 2909.90 | 2.17 | 8043.56 | 888.18 | 0.00 | 0.00 | 03-NOV-14:50 | 0.00 | 01-NOV-00:10 | 1.55 | 03-NOV-14:40 | 1.42 | 03-NOV-15:00 | 0.16 | 03-NOV-14:00 | 0.50 | 03-NOV-14:40 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.903224E+11 | 0.275734E+11 | 1805.29 | 0.608833E+11 | 0.294391E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.273725E+11 | 0.822740E+10 | 451.66 | 0.173264E+11 | 0.100460E+11 | 0.00 | 1.00 | 0.00 | 62929.30 | 33084.61 | 33703.93 | 15008.54 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 |
March | 68624199.46 | 22245179.96 | 21.47 | 59272550.24 | 9351649.22 | 0.00 | 0.11 | 19-MAR-17:10 | 0.00 | 01-MAR-00:02 | 2198.97 | 19-MAR-17:10 | 1787.74 | 19-MAR-17:10 | 411.23 | 19-MAR-17:10 | 709.39 | 19-MAR-17:10 | 0.00 | 01-MAR-00:02 |
April | 0.188677E+10 | 0.566821E+09 | 109.72 | 0.144846E+10 | 0.438308E+09 | 0.00 | 0.57 | 16-APR-16:10 | 0.00 | 01-APR-00:05 | 14389.20 | 18-APR-14:00 | 10334.23 | 16-APR-16:04 | 4458.96 | 18-APR-12:40 | 4209.59 | 16-APR-16:10 | 0.00 | 01-APR-00:05 |
May | 0.505997E+10 | 0.151465E+10 | 342.17 | 0.391859E+10 | 0.114139E+10 | 0.00 | 0.58 | 31-MAY-13:00 | 0.00 | 01-MAY-00:10 | 14150.06 | 31-MAY-13:00 | 11229.51 | 31-MAY-15:00 | 3786.78 | 29-MAY-14:10 | 4286.96 | 31-MAY-13:00 | 0.00 | 01-MAY-00:10 |
June | 0.122471E+11 | 0.360255E+10 | 413.67 | 0.891580E+10 | 0.333133E+10 | 0.00 | 1.00 | 26-JUN-07:02 | 0.00 | 01-JUN-00:10 | 30570.23 | 26-JUN-07:02 | 21096.44 | 28-JUN-07:03 | 12812.86 | 26-JUN-07:02 | 7061.29 | 26-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.161745E+11 | 0.465751E+10 | 492.62 | 0.112075E+11 | 0.496698E+10 | 0.00 | 1.00 | 02-JUL-07:03 | 0.00 | 01-JUL-00:05 | 30252.34 | 26-JUL-07:03 | 21303.87 | 28-JUL-07:03 | 12099.12 | 26-JUL-07:03 | 6942.34 | 26-JUL-07:03 | 0.00 | 01-JUL-00:05 |
August | 0.156119E+11 | 0.449759E+10 | 487.62 | 0.110138E+11 | 0.459803E+10 | 0.00 | 1.00 | 03-AUG-07:02 | 0.00 | 01-AUG-00:10 | 31251.23 | 03-AUG-07:02 | 20199.29 | 05-AUG-07:03 | 15165.22 | 03-AUG-07:03 | 7139.33 | 03-AUG-07:02 | 0.00 | 01-AUG-00:10 |
September | 0.815440E+10 | 0.243604E+10 | 360.06 | 0.686358E+10 | 0.129082E+10 | 0.00 | 1.00 | 11-SEP-07:03 | 0.00 | 01-SEP-00:10 | 29360.61 | 11-SEP-07:03 | 20289.10 | 11-SEP-07:03 | 9302.46 | 12-SEP-07:02 | 6738.32 | 11-SEP-07:03 | 0.00 | 01-SEP-00:10 |
October | 0.763114E+09 | 0.237009E+09 | 135.00 | 0.688051E+09 | 75062569.44 | 0.00 | 0.26 | 20-OCT-15:00 | 0.00 | 01-OCT-00:05 | 5697.80 | 20-OCT-15:00 | 5487.57 | 20-OCT-15:00 | 734.05 | 02-OCT-15:00 | 1699.45 | 20-OCT-15:00 | 0.00 | 01-OCT-00:05 |
November | 0.160417E+09 | 51772739.57 | 34.19 | 0.142417E+09 | 18000544.62 | 0.00 | 0.18 | 03-NOV-20:10 | 0.00 | 01-NOV-00:10 | 3338.62 | 03-NOV-20:10 | 3338.62 | 03-NOV-20:10 | 607.71 | 08-NOV-21:10 | 1052.70 | 03-NOV-20:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.601268E+11 | 0.175862E+11 | 2396.52 | 0.442575E+11 | 0.158693E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.161745E+11 | 0.465751E+10 | 492.62 | 0.112075E+11 | 0.496698E+10 | 0.00 | 1.00 | 0.00 | 31251.23 | 21303.87 | 15165.22 | 7139.33 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 |
April | 0.110572E+10 | 0.328378E+09 | 48.17 | 0.795604E+09 | 0.310112E+09 | 0.00 | 0.52 | 18-APR-14:00 | 0.00 | 01-APR-00:05 | 13359.53 | 18-APR-14:00 | 9218.71 | 18-APR-14:00 | 4279.66 | 18-APR-12:30 | 3931.59 | 18-APR-14:00 | 0.00 | 01-APR-00:05 |
May | 0.250704E+10 | 0.743646E+09 | 164.72 | 0.183991E+10 | 0.667134E+09 | 0.00 | 0.54 | 31-MAY-13:00 | 0.00 | 01-MAY-00:10 | 13414.53 | 31-MAY-13:00 | 10467.11 | 31-MAY-15:00 | 3602.04 | 30-MAY-13:00 | 4106.77 | 31-MAY-13:00 | 0.00 | 01-MAY-00:10 |
June | 0.864853E+10 | 0.252429E+10 | 277.82 | 0.604503E+10 | 0.260350E+10 | 0.00 | 1.00 | 12-JUN-06:03 | 0.00 | 01-JUN-00:10 | 31734.21 | 26-JUN-06:02 | 18619.04 | 30-JUN-06:02 | 15260.27 | 26-JUN-06:02 | 7175.17 | 26-JUN-06:02 | 0.00 | 01-JUN-00:10 |
July | 0.115659E+11 | 0.330686E+10 | 351.59 | 0.766278E+10 | 0.390314E+10 | 0.00 | 1.00 | 02-JUL-07:03 | 0.00 | 01-JUL-00:05 | 31894.44 | 27-JUL-06:03 | 19049.34 | 02-JUL-07:03 | 16568.20 | 27-JUL-06:03 | 7126.68 | 26-JUL-06:03 | 0.00 | 01-JUL-00:05 |
August | 0.114383E+11 | 0.328310E+10 | 352.18 | 0.775531E+10 | 0.368297E+10 | 0.00 | 1.00 | 03-AUG-06:02 | 0.00 | 01-AUG-00:10 | 32709.01 | 04-AUG-06:02 | 17227.07 | 23-AUG-06:03 | 18580.17 | 04-AUG-06:02 | 7264.76 | 03-AUG-06:02 | 0.00 | 01-AUG-00:10 |
September | 0.535546E+10 | 0.159734E+10 | 213.71 | 0.438172E+10 | 0.973739E+09 | 0.00 | 1.00 | 11-SEP-06:03 | 0.00 | 01-SEP-00:10 | 30195.50 | 11-SEP-06:03 | 19976.81 | 11-SEP-06:03 | 11023.17 | 12-SEP-06:03 | 6919.54 | 11-SEP-06:03 | 0.00 | 01-SEP-00:10 |
October | 0.150874E+09 | 45345019.84 | 24.00 | 0.135573E+09 | 15300482.99 | 0.00 | 0.21 | 20-OCT-15:00 | 0.00 | 01-OCT-00:05 | 4635.92 | 20-OCT-15:00 | 4438.67 | 20-OCT-15:00 | 590.49 | 21-OCT-15:00 | 1401.70 | 20-OCT-15:00 | 0.00 | 01-OCT-00:05 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.407718E+11 | 0.118290E+11 | 1432.19 | 0.286159E+11 | 0.121559E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.115659E+11 | 0.330686E+10 | 352.18 | 0.775531E+10 | 0.390314E+10 | 0.00 | 1.00 | 0.00 | 32709.01 | 19976.81 | 18580.17 | 7264.76 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 |
April | 0.105752E+10 | 0.314882E+09 | 45.33 | 0.757404E+09 | 0.300113E+09 | 0.00 | 0.52 | 18-APR-14:00 | 0.00 | 01-APR-00:05 | 13161.19 | 18-APR-14:00 | 9061.51 | 18-APR-14:00 | 4229.51 | 18-APR-12:30 | 3881.67 | 18-APR-14:00 | 0.00 | 01-APR-00:05 |
May | 0.232291E+10 | 0.690768E+09 | 149.00 | 0.169889E+10 | 0.624021E+09 | 0.00 | 0.53 | 31-MAY-13:00 | 0.00 | 01-MAY-00:10 | 13263.80 | 31-MAY-13:00 | 10340.75 | 31-MAY-15:00 | 3549.89 | 30-MAY-13:00 | 4068.25 | 31-MAY-13:00 | 0.00 | 01-MAY-00:10 |
June | 0.852639E+10 | 0.249182E+10 | 276.40 | 0.595071E+10 | 0.257568E+10 | 0.00 | 1.00 | 12-JUN-06:03 | 0.00 | 01-JUN-00:10 | 31839.46 | 26-JUN-06:02 | 18661.55 | 30-JUN-06:02 | 15311.05 | 26-JUN-06:02 | 7198.85 | 26-JUN-06:02 | 0.00 | 01-JUN-00:10 |
July | 0.114444E+11 | 0.327565E+10 | 349.95 | 0.757197E+10 | 0.387243E+10 | 0.00 | 1.00 | 02-JUL-07:03 | 0.00 | 01-JUL-00:05 | 31999.53 | 27-JUL-06:03 | 19093.62 | 02-JUL-07:03 | 16651.45 | 27-JUL-06:03 | 7149.80 | 26-JUL-06:03 | 0.00 | 01-JUL-00:05 |
August | 0.113010E+11 | 0.324778E+10 | 350.82 | 0.765056E+10 | 0.365043E+10 | 0.00 | 1.00 | 03-AUG-06:02 | 0.00 | 01-AUG-00:10 | 32815.74 | 04-AUG-06:02 | 17253.77 | 23-AUG-06:03 | 18658.30 | 04-AUG-06:02 | 7288.65 | 03-AUG-06:02 | 0.00 | 01-AUG-00:10 |
September | 0.526221E+10 | 0.157185E+10 | 208.50 | 0.429889E+10 | 0.963315E+09 | 0.00 | 1.00 | 11-SEP-06:03 | 0.00 | 01-SEP-00:10 | 30292.72 | 11-SEP-06:03 | 20028.20 | 11-SEP-06:03 | 10803.89 | 12-SEP-06:03 | 6941.99 | 11-SEP-06:03 | 0.00 | 01-SEP-00:10 |
October | 0.122948E+09 | 37022177.43 | 19.83 | 0.111003E+09 | 11945094.90 | 0.00 | 0.20 | 20-OCT-15:00 | 0.00 | 01-OCT-00:05 | 4386.05 | 20-OCT-15:00 | 4196.50 | 20-OCT-15:00 | 544.63 | 21-OCT-15:00 | 1330.20 | 20-OCT-15:00 | 0.00 | 01-OCT-00:05 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.400374E+11 | 0.116298E+11 | 1399.84 | 0.280394E+11 | 0.119979E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.114444E+11 | 0.327565E+10 | 350.82 | 0.765056E+10 | 0.387243E+10 | 0.00 | 1.00 | 0.00 | 32815.74 | 20028.20 | 18658.30 | 7288.65 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 |
April | 0.101214E+10 | 0.302258E+09 | 43.67 | 0.721771E+09 | 0.290370E+09 | 0.00 | 0.51 | 18-APR-14:00 | 0.00 | 01-APR-00:05 | 12966.66 | 18-APR-14:00 | 8906.50 | 18-APR-14:00 | 4179.27 | 18-APR-12:30 | 3834.29 | 18-APR-14:00 | 0.00 | 01-APR-00:05 |
May | 0.216320E+10 | 0.645027E+09 | 139.50 | 0.157748E+10 | 0.585716E+09 | 0.00 | 0.52 | 31-MAY-13:00 | 0.00 | 01-MAY-00:10 | 13090.58 | 31-MAY-13:00 | 10205.79 | 31-MAY-15:00 | 3502.46 | 30-MAY-13:00 | 4025.47 | 31-MAY-13:00 | 0.00 | 01-MAY-00:10 |
June | 0.834289E+10 | 0.244359E+10 | 272.52 | 0.580981E+10 | 0.253308E+10 | 0.00 | 1.00 | 26-JUN-06:02 | 0.00 | 01-JUN-00:10 | 32048.45 | 26-JUN-06:02 | 18700.60 | 30-JUN-06:02 | 15476.28 | 26-JUN-06:02 | 7248.18 | 26-JUN-06:02 | 0.00 | 01-JUN-00:10 |
July | 0.112263E+11 | 0.321976E+10 | 347.68 | 0.741127E+10 | 0.381504E+10 | 0.00 | 1.00 | 03-JUL-06:02 | 0.00 | 01-JUL-00:05 | 32211.11 | 27-JUL-06:03 | 18865.01 | 02-JUL-07:03 | 16860.13 | 27-JUL-06:03 | 7198.21 | 26-JUL-06:03 | 0.00 | 01-JUL-00:05 |
August | 0.110867E+11 | 0.319290E+10 | 349.05 | 0.748968E+10 | 0.359701E+10 | 0.00 | 1.00 | 03-AUG-06:02 | 0.00 | 01-AUG-00:10 | 33030.27 | 04-AUG-06:02 | 17287.08 | 23-AUG-06:03 | 18870.58 | 04-AUG-06:02 | 7339.20 | 03-AUG-06:02 | 0.00 | 01-AUG-00:10 |
September | 0.514854E+10 | 0.154133E+10 | 205.17 | 0.420100E+10 | 0.947540E+09 | 0.00 | 0.99 | 11-SEP-06:03 | 0.00 | 01-SEP-00:10 | 30061.55 | 11-SEP-06:03 | 19823.80 | 11-SEP-06:03 | 10237.75 | 11-SEP-06:03 | 6914.25 | 11-SEP-06:03 | 0.00 | 01-SEP-00:10 |
October | 0.104630E+09 | 31563347.89 | 17.67 | 94767826.50 | 9862260.23 | 0.00 | 0.19 | 20-OCT-15:00 | 0.00 | 01-OCT-00:05 | 4189.62 | 20-OCT-15:00 | 4005.64 | 20-OCT-15:00 | 505.80 | 21-OCT-15:00 | 1273.94 | 20-OCT-15:00 | 0.00 | 01-OCT-00:05 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.390844E+11 | 0.113764E+11 | 1375.24 | 0.273058E+11 | 0.117786E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.112263E+11 | 0.321976E+10 | 349.05 | 0.748968E+10 | 0.381504E+10 | 0.00 | 1.00 | 0.00 | 33030.27 | 19823.80 | 18870.58 | 7339.20 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 |
April | 0.150799E+10 | 0.479047E+09 | 36.50 | 0.101910E+10 | 0.488886E+09 | 0.00 | 0.50 | 18-APR-14:10 | 0.00 | 01-APR-00:05 | 24006.52 | 18-APR-14:10 | 16280.17 | 18-APR-14:10 | 7997.53 | 18-APR-12:30 | 7536.22 | 18-APR-14:10 | 0.00 | 01-APR-00:05 |
May | 0.269008E+10 | 0.856984E+09 | 93.67 | 0.188773E+10 | 0.802350E+09 | 0.00 | 0.52 | 31-MAY-15:00 | 0.00 | 01-MAY-00:10 | 24358.68 | 31-MAY-15:00 | 18882.04 | 31-MAY-15:00 | 7416.05 | 29-MAY-13:40 | 7955.61 | 31-MAY-15:00 | 0.00 | 01-MAY-00:10 |
June | 0.132990E+11 | 0.414507E+10 | 245.62 | 0.891985E+10 | 0.437912E+10 | 0.00 | 1.00 | 26-JUN-07:02 | 0.00 | 01-JUN-00:10 | 60416.98 | 26-JUN-07:02 | 32333.69 | 26-JUN-07:02 | 28753.64 | 30-JUN-07:02 | 14665.25 | 27-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.184059E+11 | 0.559862E+10 | 315.17 | 0.115533E+11 | 0.685259E+10 | 0.00 | 1.00 | 02-JUL-08:62 | 0.00 | 01-JUL-00:05 | 59497.44 | 07-JUL-07:03 | 32316.56 | 02-JUL-08:62 | 32986.67 | 07-JUL-07:03 | 14649.38 | 02-JUL-08:62 | 0.00 | 01-JUL-00:05 |
August | 0.175422E+11 | 0.536847E+10 | 318.11 | 0.113078E+11 | 0.623438E+10 | 0.00 | 1.00 | 03-AUG-07:02 | 0.00 | 01-AUG-00:10 | 61371.85 | 04-AUG-07:02 | 30094.12 | 03-AUG-07:02 | 31592.48 | 04-AUG-07:03 | 14741.33 | 04-AUG-07:02 | 0.00 | 01-AUG-00:10 |
September | 0.783465E+10 | 0.250376E+10 | 178.76 | 0.622857E+10 | 0.160608E+10 | 0.00 | 0.96 | 11-SEP-07:03 | 0.00 | 01-SEP-00:10 | 54068.77 | 11-SEP-07:03 | 30051.41 | 11-SEP-07:03 | 24017.36 | 11-SEP-07:03 | 13334.15 | 11-SEP-07:03 | 0.00 | 01-SEP-00:10 |
October | 50121131.03 | 16282241.56 | 8.00 | 46509303.45 | 3611827.57 | 0.00 | 0.16 | 20-OCT-15:00 | 0.00 | 01-OCT-00:05 | 6665.78 | 20-OCT-15:00 | 6252.62 | 20-OCT-15:00 | 413.16 | 20-OCT-15:00 | 2165.50 | 20-OCT-15:00 | 0.00 | 01-OCT-00:05 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.613299E+11 | 0.189682E+11 | 1195.84 | 0.409629E+11 | 0.203670E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.184059E+11 | 0.559862E+10 | 318.11 | 0.115533E+11 | 0.685259E+10 | 0.00 | 1.00 | 0.00 | 61371.85 | 32333.69 | 32986.67 | 14741.33 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 |
April | 0.906409E+09 | 0.272832E+09 | 42.00 | 0.634269E+09 | 0.272141E+09 | 0.00 | 0.48 | 18-APR-14:10 | 0.00 | 01-APR-00:05 | 12530.08 | 18-APR-14:10 | 8506.27 | 18-APR-14:20 | 4135.82 | 18-APR-12:30 | 3731.33 | 18-APR-14:10 | 0.00 | 01-APR-00:05 |
May | 0.183633E+10 | 0.551911E+09 | 119.67 | 0.132296E+10 | 0.513369E+09 | 0.00 | 0.50 | 31-MAY-15:00 | 0.00 | 01-MAY-00:10 | 12777.50 | 31-MAY-15:00 | 9912.50 | 31-MAY-15:00 | 3479.62 | 30-MAY-13:00 | 3957.75 | 31-MAY-15:00 | 0.00 | 01-MAY-00:10 |
June | 0.782322E+10 | 0.231034E+10 | 270.00 | 0.538732E+10 | 0.243590E+10 | 0.00 | 1.00 | 26-JUN-07:02 | 0.00 | 01-JUN-00:10 | 33082.28 | 26-JUN-07:02 | 19436.99 | 30-JUN-07:02 | 16104.56 | 26-JUN-07:02 | 7542.88 | 26-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.105468E+11 | 0.304661E+10 | 338.00 | 0.685898E+10 | 0.368786E+10 | 0.00 | 1.00 | 02-JUL-08:62 | 0.00 | 01-JUL-00:05 | 32763.83 | 27-JUL-07:02 | 19447.75 | 02-JUL-08:62 | 15947.24 | 27-JUL-07:02 | 7521.20 | 02-JUL-08:62 | 0.00 | 01-JUL-00:05 |
August | 0.104782E+11 | 0.304018E+10 | 348.43 | 0.698176E+10 | 0.349643E+10 | 0.00 | 1.00 | 03-AUG-07:02 | 0.00 | 01-AUG-00:10 | 33794.04 | 04-AUG-07:02 | 15732.57 | 03-AUG-07:02 | 18673.99 | 04-AUG-07:03 | 7600.71 | 04-AUG-07:02 | 0.00 | 01-AUG-00:10 |
September | 0.480422E+10 | 0.144921E+10 | 198.86 | 0.387851E+10 | 0.925708E+09 | 0.00 | 0.91 | 11-SEP-07:03 | 0.00 | 01-SEP-00:10 | 27644.59 | 11-SEP-07:03 | 17935.15 | 11-SEP-07:03 | 9709.43 | 11-SEP-07:03 | 6527.30 | 11-SEP-07:03 | 0.00 | 01-SEP-00:10 |
October | 76377820.56 | 23137657.53 | 12.33 | 68581371.62 | 7796448.94 | 0.00 | 0.18 | 20-OCT-15:00 | 0.00 | 01-OCT-00:05 | 3945.14 | 20-OCT-15:00 | 3711.22 | 20-OCT-15:00 | 502.98 | 21-OCT-15:00 | 1204.63 | 20-OCT-15:00 | 0.00 | 01-OCT-00:05 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.364716E+11 | 0.106942E+11 | 1329.28 | 0.251324E+11 | 0.113392E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.105468E+11 | 0.304661E+10 | 348.43 | 0.698176E+10 | 0.368786E+10 | 0.00 | 1.00 | 0.00 | 33794.04 | 19447.75 | 18673.99 | 7600.71 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 |
April | 0.879739E+09 | 0.265231E+09 | 40.17 | 0.613346E+09 | 0.266393E+09 | 0.00 | 0.47 | 18-APR-14:10 | 0.00 | 01-APR-00:05 | 12351.59 | 18-APR-14:10 | 8365.33 | 18-APR-14:20 | 4089.67 | 18-APR-12:40 | 3684.20 | 18-APR-14:10 | 0.00 | 01-APR-00:05 |
May | 0.174784E+10 | 0.526279E+09 | 111.92 | 0.125703E+10 | 0.490819E+09 | 0.00 | 0.50 | 31-MAY-15:00 | 0.00 | 01-MAY-00:10 | 12644.55 | 31-MAY-15:00 | 9795.25 | 31-MAY-15:00 | 3436.12 | 30-MAY-13:00 | 3921.94 | 31-MAY-15:00 | 0.00 | 01-MAY-00:10 |
June | 0.770192E+10 | 0.227704E+10 | 267.71 | 0.529279E+10 | 0.240913E+10 | 0.00 | 1.00 | 26-JUN-07:02 | 0.00 | 01-JUN-00:10 | 33111.96 | 26-JUN-07:02 | 19402.41 | 30-JUN-07:02 | 16171.27 | 26-JUN-07:02 | 7551.27 | 26-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.104097E+11 | 0.300985E+10 | 337.08 | 0.675635E+10 | 0.365334E+10 | 0.00 | 1.00 | 02-JUL-08:62 | 0.00 | 01-JUL-00:05 | 32798.97 | 27-JUL-07:02 | 19413.18 | 02-JUL-08:62 | 16021.79 | 27-JUL-07:02 | 7529.20 | 02-JUL-08:62 | 0.00 | 01-JUL-00:05 |
August | 0.103442E+11 | 0.300414E+10 | 347.56 | 0.687893E+10 | 0.346528E+10 | 0.00 | 1.00 | 03-AUG-07:02 | 0.00 | 01-AUG-00:10 | 33830.07 | 04-AUG-07:02 | 15700.74 | 03-AUG-07:02 | 18703.50 | 04-AUG-07:02 | 7609.57 | 04-AUG-07:02 | 0.00 | 01-AUG-00:10 |
September | 0.473066E+10 | 0.142866E+10 | 197.11 | 0.381371E+10 | 0.916948E+09 | 0.00 | 0.88 | 11-SEP-07:03 | 0.00 | 01-SEP-00:10 | 26683.17 | 11-SEP-07:03 | 17275.01 | 11-SEP-07:03 | 9408.16 | 11-SEP-07:03 | 6352.12 | 11-SEP-07:03 | 0.00 | 01-SEP-00:10 |
October | 71667348.97 | 21730806.34 | 11.67 | 64394101.12 | 7273247.85 | 0.00 | 0.17 | 20-OCT-15:00 | 0.00 | 01-OCT-00:05 | 3855.46 | 20-OCT-15:00 | 3623.52 | 20-OCT-15:00 | 484.84 | 21-OCT-15:00 | 1178.49 | 20-OCT-15:00 | 0.00 | 01-OCT-00:05 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.358857E+11 | 0.105329E+11 | 1313.22 | 0.246766E+11 | 0.112092E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.104097E+11 | 0.300985E+10 | 347.56 | 0.687893E+10 | 0.365334E+10 | 0.00 | 1.00 | 0.00 | 33830.07 | 19413.18 | 18703.50 | 7609.57 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 |
April | 0.813987E+09 | 0.246601E+09 | 38.00 | 0.562975E+09 | 0.251013E+09 | 0.00 | 0.45 | 18-APR-14:10 | 0.00 | 01-APR-00:05 | 11909.32 | 18-APR-14:10 | 8023.15 | 18-APR-14:20 | 3974.36 | 18-APR-12:30 | 3570.18 | 18-APR-14:10 | 0.00 | 01-APR-00:05 |
May | 0.156105E+10 | 0.472350E+09 | 98.50 | 0.111876E+10 | 0.442290E+09 | 0.00 | 0.48 | 31-MAY-15:00 | 0.00 | 01-MAY-00:10 | 12345.41 | 31-MAY-15:00 | 9536.61 | 31-MAY-15:00 | 3329.10 | 30-MAY-13:00 | 3845.09 | 31-MAY-15:00 | 0.00 | 01-MAY-00:10 |
June | 0.742107E+10 | 0.220144E+10 | 262.67 | 0.507971E+10 | 0.234135E+10 | 0.00 | 1.00 | 26-JUN-07:02 | 0.00 | 01-JUN-00:10 | 33450.82 | 26-JUN-07:02 | 19279.37 | 30-JUN-07:02 | 16498.64 | 26-JUN-07:02 | 7634.64 | 26-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.101072E+11 | 0.293066E+10 | 333.08 | 0.653724E+10 | 0.356997E+10 | 0.00 | 1.00 | 04-JUL-08:62 | 0.00 | 01-JUL-00:05 | 32983.94 | 05-JUL-07:02 | 18298.64 | 04-JUL-08:62 | 15485.13 | 05-JUL-07:02 | 7501.70 | 04-JUL-08:62 | 0.00 | 01-JUL-00:05 |
August | 0.100671E+11 | 0.293139E+10 | 344.00 | 0.667319E+10 | 0.339386E+10 | 0.00 | 1.00 | 03-AUG-07:02 | 0.00 | 01-AUG-00:10 | 34193.34 | 04-AUG-07:02 | 15760.00 | 03-AUG-07:02 | 19009.72 | 04-AUG-07:02 | 7695.11 | 04-AUG-07:02 | 0.00 | 01-AUG-00:10 |
September | 0.459336E+10 | 0.139124E+10 | 192.92 | 0.369544E+10 | 0.897921E+09 | 0.00 | 0.79 | 11-SEP-07:03 | 0.00 | 01-SEP-00:10 | 23535.30 | 11-SEP-07:03 | 15164.15 | 11-SEP-07:03 | 8371.15 | 11-SEP-07:03 | 5765.53 | 11-SEP-07:03 | 0.00 | 01-SEP-00:10 |
October | 61710523.54 | 18760312.34 | 10.00 | 55552984.28 | 6157539.26 | 0.00 | 0.16 | 20-OCT-15:00 | 0.00 | 01-OCT-00:05 | 3635.64 | 20-OCT-15:00 | 3412.39 | 20-OCT-15:00 | 438.75 | 21-OCT-15:00 | 1114.53 | 20-OCT-15:00 | 0.00 | 01-OCT-00:05 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.346254E+11 | 0.101924E+11 | 1279.17 | 0.237229E+11 | 0.109026E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.101072E+11 | 0.293139E+10 | 344.00 | 0.667319E+10 | 0.356997E+10 | 0.00 | 1.00 | 0.00 | 34193.34 | 19279.37 | 19009.72 | 7695.11 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 |
April | 0.696827E+09 | 0.214459E+09 | 33.42 | 0.471648E+09 | 0.225179E+09 | 0.00 | 0.39 | 18-APR-14:10 | 0.00 | 01-APR-00:05 | 11411.20 | 18-APR-14:10 | 7599.32 | 18-APR-14:10 | 3924.48 | 18-APR-12:10 | 3481.15 | 18-APR-14:10 | 0.00 | 01-APR-00:05 |
May | 0.128371E+10 | 0.394227E+09 | 79.67 | 0.915464E+09 | 0.368242E+09 | 0.00 | 0.43 | 31-MAY-13:00 | 0.00 | 01-MAY-00:10 | 12227.35 | 31-MAY-13:00 | 9317.10 | 31-MAY-15:00 | 3220.38 | 30-MAY-13:00 | 3865.13 | 31-MAY-13:00 | 0.00 | 01-MAY-00:10 |
June | 0.707660E+10 | 0.213012E+10 | 252.82 | 0.481811E+10 | 0.225849E+10 | 0.00 | 0.76 | 26-JUN-07:02 | 0.00 | 01-JUN-00:10 | 26814.22 | 26-JUN-07:02 | 12715.58 | 26-JUN-07:02 | 14098.64 | 26-JUN-07:02 | 6592.33 | 26-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.980045E+10 | 0.287914E+10 | 324.96 | 0.632637E+10 | 0.347408E+10 | 0.00 | 0.91 | 04-JUL-08:62 | 0.00 | 01-JUL-00:05 | 32993.86 | 04-JUL-08:62 | 17737.44 | 04-JUL-08:62 | 15256.42 | 04-JUL-08:62 | 7749.34 | 04-JUL-08:62 | 0.00 | 01-JUL-00:05 |
August | 0.990185E+10 | 0.291688E+10 | 334.76 | 0.655551E+10 | 0.334634E+10 | 0.00 | 1.00 | 03-AUG-07:02 | 0.00 | 01-AUG-00:10 | 39336.53 | 04-AUG-07:02 | 16015.51 | 03-AUG-07:02 | 23985.90 | 04-AUG-07:02 | 8731.68 | 03-AUG-07:02 | 0.00 | 01-AUG-00:10 |
September | 0.459132E+10 | 0.140504E+10 | 185.99 | 0.369299E+10 | 0.898326E+09 | 0.00 | 0.56 | 06-SEP-14:10 | 0.00 | 01-SEP-00:10 | 16616.06 | 06-SEP-14:10 | 13073.01 | 07-SEP-14:10 | 4596.19 | 11-SEP-12:20 | 5258.78 | 06-SEP-14:10 | 0.00 | 01-SEP-00:10 |
October | 51927085.42 | 15870153.43 | 8.83 | 47142523.46 | 4784561.95 | 0.00 | 0.14 | 20-OCT-15:00 | 0.00 | 01-OCT-00:05 | 3451.19 | 20-OCT-15:00 | 3239.97 | 20-OCT-15:00 | 363.44 | 21-OCT-15:00 | 1064.98 | 20-OCT-15:00 | 0.00 | 01-OCT-00:05 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.334027E+11 | 0.995574E+10 | 1220.46 | 0.228272E+11 | 0.105754E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.990185E+10 | 0.291688E+10 | 334.76 | 0.655551E+10 | 0.347408E+10 | 0.00 | 1.00 | 0.00 | 39336.53 | 17737.44 | 23985.90 | 8731.68 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 119.63 | 81.86 | 37.77 | 92.78 | 160.08 | 0.00 | 0.00 | 744.00 |
February | 128.24 | 86.65 | 41.59 | 101.00 | 129.51 | 0.00 | 0.00 | 672.00 |
March | 111.62 | 58.80 | 52.82 | 87.72 | 92.82 | 0.00 | 0.00 | 744.00 |
April | 100.51 | 46.99 | 53.52 | 78.05 | 68.89 | 0.00 | 0.00 | 720.00 |
May | 83.26 | 22.56 | 60.70 | 61.23 | 43.09 | 0.00 | 0.00 | 744.00 |
June | 80.83 | 16.45 | 64.39 | 69.15 | 30.34 | 0.00 | 0.00 | 720.00 |
July | 85.57 | 21.55 | 64.02 | 76.35 | 25.98 | 0.00 | 0.00 | 744.00 |
August | 96.41 | 34.57 | 61.84 | 94.28 | 31.32 | 0.00 | 0.00 | 744.00 |
September | 116.87 | 61.59 | 55.28 | 117.34 | 51.66 | 0.00 | 0.00 | 720.00 |
October | 122.06 | 76.59 | 45.47 | 117.29 | 73.66 | 0.00 | 0.00 | 744.00 |
November | 92.05 | 57.62 | 34.43 | 76.04 | 107.01 | 0.00 | 0.00 | 720.00 |
December | 98.13 | 74.32 | 23.81 | 86.19 | 147.91 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 102.78 | 53.11 | 49.68 | 88.05 | 79.96 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 80.83 | 16.45 | 23.81 | 61.23 | 25.98 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 128.24 | 86.65 | 64.39 | 117.34 | 160.08 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 119.63 | 81.86 | 37.77 | 92.78 | 160.08 | 0.00 | 0.00 | 744.00 |
February | 128.24 | 86.65 | 41.59 | 101.00 | 129.51 | 0.00 | 0.00 | 672.00 |
March | 111.62 | 58.80 | 52.82 | 87.72 | 92.82 | 0.00 | 0.00 | 744.00 |
April | 100.51 | 46.99 | 53.52 | 78.05 | 68.89 | 0.00 | 0.00 | 720.00 |
May | 83.26 | 22.56 | 60.70 | 61.23 | 43.09 | 0.00 | 0.00 | 744.00 |
June | 80.83 | 16.45 | 64.39 | 69.15 | 30.34 | 0.00 | 0.00 | 720.00 |
July | 85.57 | 21.55 | 64.02 | 76.35 | 25.98 | 0.00 | 0.00 | 744.00 |
August | 96.41 | 34.57 | 61.84 | 94.28 | 31.32 | 0.00 | 0.00 | 744.00 |
September | 116.87 | 61.59 | 55.28 | 117.34 | 51.66 | 0.00 | 0.00 | 720.00 |
October | 122.06 | 76.59 | 45.47 | 117.29 | 73.66 | 0.00 | 0.00 | 744.00 |
November | 92.05 | 57.62 | 34.43 | 76.04 | 107.01 | 0.00 | 0.00 | 720.00 |
December | 98.13 | 74.32 | 23.81 | 86.19 | 147.91 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 102.78 | 53.11 | 49.68 | 88.05 | 79.96 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 80.83 | 16.45 | 23.81 | 61.23 | 25.98 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 128.24 | 86.65 | 64.39 | 117.34 | 160.08 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_3
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 119.63 | 81.86 | 37.77 | 92.78 | 160.08 | 0.00 | 0.00 | 744.00 |
February | 128.24 | 86.65 | 41.59 | 101.00 | 129.51 | 0.00 | 0.00 | 672.00 |
March | 111.62 | 58.80 | 52.82 | 87.72 | 92.82 | 0.00 | 0.00 | 744.00 |
April | 100.51 | 46.99 | 53.52 | 78.05 | 68.89 | 0.00 | 0.00 | 720.00 |
May | 83.26 | 22.56 | 60.70 | 61.23 | 43.09 | 0.00 | 0.00 | 744.00 |
June | 80.83 | 16.45 | 64.39 | 69.15 | 30.34 | 0.00 | 0.00 | 720.00 |
July | 85.57 | 21.55 | 64.02 | 76.35 | 25.98 | 0.00 | 0.00 | 744.00 |
August | 96.41 | 34.57 | 61.84 | 94.28 | 31.32 | 0.00 | 0.00 | 744.00 |
September | 116.87 | 61.59 | 55.28 | 117.34 | 51.66 | 0.00 | 0.00 | 720.00 |
October | 122.06 | 76.59 | 45.47 | 117.29 | 73.66 | 0.00 | 0.00 | 744.00 |
November | 92.05 | 57.62 | 34.43 | 76.04 | 107.01 | 0.00 | 0.00 | 720.00 |
December | 98.13 | 74.32 | 23.81 | 86.19 | 147.91 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 102.78 | 53.11 | 49.68 | 88.05 | 79.96 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 80.83 | 16.45 | 23.81 | 61.23 | 25.98 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 128.24 | 86.65 | 64.39 | 117.34 | 160.08 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_4
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 119.63 | 81.86 | 37.77 | 92.78 | 160.08 | 0.00 | 0.00 | 744.00 |
February | 128.24 | 86.65 | 41.59 | 101.00 | 129.51 | 0.00 | 0.00 | 672.00 |
March | 111.62 | 58.80 | 52.82 | 87.72 | 92.82 | 0.00 | 0.00 | 744.00 |
April | 100.51 | 46.99 | 53.52 | 78.05 | 68.89 | 0.00 | 0.00 | 720.00 |
May | 83.26 | 22.56 | 60.70 | 61.23 | 43.09 | 0.00 | 0.00 | 744.00 |
June | 80.83 | 16.45 | 64.39 | 69.15 | 30.34 | 0.00 | 0.00 | 720.00 |
July | 85.57 | 21.55 | 64.02 | 76.35 | 25.98 | 0.00 | 0.00 | 744.00 |
August | 96.41 | 34.57 | 61.84 | 94.28 | 31.32 | 0.00 | 0.00 | 744.00 |
September | 116.87 | 61.59 | 55.28 | 117.34 | 51.66 | 0.00 | 0.00 | 720.00 |
October | 122.06 | 76.59 | 45.47 | 117.29 | 73.66 | 0.00 | 0.00 | 744.00 |
November | 92.05 | 57.62 | 34.43 | 76.04 | 107.01 | 0.00 | 0.00 | 720.00 |
December | 98.13 | 74.32 | 23.81 | 86.19 | 147.91 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 102.78 | 53.11 | 49.68 | 88.05 | 79.96 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 80.83 | 16.45 | 23.81 | 61.23 | 25.98 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 128.24 | 86.65 | 64.39 | 117.34 | 160.08 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_DOOR_1
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 144.03 | 98.55 | 45.48 | 112.18 | 190.34 | 0.00 | 0.00 | 744.00 |
February | 154.40 | 104.32 | 50.07 | 122.06 | 154.02 | 0.00 | 0.00 | 672.00 |
March | 134.38 | 70.79 | 63.59 | 105.94 | 110.41 | 0.00 | 0.00 | 744.00 |
April | 121.01 | 56.57 | 64.44 | 94.13 | 82.04 | 0.00 | 0.00 | 720.00 |
May | 100.24 | 27.17 | 73.08 | 73.83 | 51.44 | 0.00 | 0.00 | 744.00 |
June | 97.32 | 19.80 | 77.52 | 83.17 | 36.27 | 0.00 | 0.00 | 720.00 |
July | 103.02 | 25.94 | 77.08 | 91.81 | 31.12 | 0.00 | 0.00 | 744.00 |
August | 116.07 | 41.62 | 74.46 | 113.39 | 37.46 | 0.00 | 0.00 | 744.00 |
September | 140.70 | 74.15 | 66.55 | 141.19 | 61.72 | 0.00 | 0.00 | 720.00 |
October | 146.95 | 92.21 | 54.74 | 141.35 | 87.86 | 0.00 | 0.00 | 744.00 |
November | 110.83 | 69.38 | 41.45 | 91.78 | 127.33 | 0.00 | 0.00 | 720.00 |
December | 118.14 | 89.48 | 28.66 | 104.02 | 175.99 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 123.75 | 63.94 | 59.81 | 106.15 | 95.22 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 97.32 | 19.80 | 28.66 | 73.83 | 31.12 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 154.40 | 104.32 | 77.52 | 141.35 | 190.34 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_DOOR_2
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 144.03 | 98.55 | 45.48 | 112.18 | 190.34 | 0.00 | 0.00 | 744.00 |
February | 154.40 | 104.32 | 50.07 | 122.06 | 154.02 | 0.00 | 0.00 | 672.00 |
March | 134.38 | 70.79 | 63.59 | 105.94 | 110.41 | 0.00 | 0.00 | 744.00 |
April | 121.01 | 56.57 | 64.44 | 94.13 | 82.04 | 0.00 | 0.00 | 720.00 |
May | 100.24 | 27.17 | 73.08 | 73.83 | 51.44 | 0.00 | 0.00 | 744.00 |
June | 97.32 | 19.80 | 77.52 | 83.17 | 36.27 | 0.00 | 0.00 | 720.00 |
July | 103.02 | 25.94 | 77.08 | 91.81 | 31.12 | 0.00 | 0.00 | 744.00 |
August | 116.07 | 41.62 | 74.46 | 113.39 | 37.46 | 0.00 | 0.00 | 744.00 |
September | 140.70 | 74.15 | 66.55 | 141.19 | 61.72 | 0.00 | 0.00 | 720.00 |
October | 146.95 | 92.21 | 54.74 | 141.35 | 87.86 | 0.00 | 0.00 | 744.00 |
November | 110.83 | 69.38 | 41.45 | 91.78 | 127.33 | 0.00 | 0.00 | 720.00 |
December | 118.14 | 89.48 | 28.66 | 104.02 | 175.99 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 123.75 | 63.94 | 59.81 | 106.15 | 95.22 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 97.32 | 19.80 | 28.66 | 73.83 | 31.12 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 154.40 | 104.32 | 77.52 | 141.35 | 190.34 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 119.63 | 81.86 | 37.77 | 91.53 | 164.86 | 0.00 | 0.00 | 744.00 |
February | 128.24 | 86.65 | 41.59 | 99.63 | 134.55 | 0.00 | 0.00 | 672.00 |
March | 111.62 | 58.80 | 52.82 | 86.26 | 98.16 | 0.00 | 0.00 | 744.00 |
April | 100.51 | 46.99 | 53.52 | 76.93 | 73.82 | 0.00 | 0.00 | 720.00 |
May | 83.26 | 22.56 | 60.70 | 60.19 | 45.38 | 0.00 | 0.00 | 744.00 |
June | 80.83 | 16.45 | 64.39 | 68.69 | 31.47 | 0.00 | 0.00 | 720.00 |
July | 85.57 | 21.55 | 64.02 | 76.14 | 26.45 | 0.00 | 0.00 | 744.00 |
August | 96.41 | 34.57 | 61.84 | 94.14 | 31.81 | 0.00 | 0.00 | 744.00 |
September | 116.87 | 61.59 | 55.28 | 117.05 | 52.98 | 0.00 | 0.00 | 720.00 |
October | 122.06 | 76.59 | 45.47 | 116.26 | 77.37 | 0.00 | 0.00 | 744.00 |
November | 92.05 | 57.62 | 34.43 | 75.10 | 111.56 | 0.00 | 0.00 | 720.00 |
December | 98.13 | 74.32 | 23.81 | 85.25 | 153.13 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 102.78 | 53.11 | 49.68 | 87.19 | 83.22 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 80.83 | 16.45 | 23.81 | 60.19 | 26.45 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 128.24 | 86.65 | 64.39 | 117.05 | 164.86 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 119.63 | 81.86 | 37.77 | 91.53 | 164.86 | 0.00 | 0.00 | 744.00 |
February | 128.24 | 86.65 | 41.59 | 99.63 | 134.55 | 0.00 | 0.00 | 672.00 |
March | 111.62 | 58.80 | 52.82 | 86.26 | 98.16 | 0.00 | 0.00 | 744.00 |
April | 100.51 | 46.99 | 53.52 | 76.93 | 73.82 | 0.00 | 0.00 | 720.00 |
May | 83.26 | 22.56 | 60.70 | 60.19 | 45.38 | 0.00 | 0.00 | 744.00 |
June | 80.83 | 16.45 | 64.39 | 68.69 | 31.47 | 0.00 | 0.00 | 720.00 |
July | 85.57 | 21.55 | 64.02 | 76.14 | 26.45 | 0.00 | 0.00 | 744.00 |
August | 96.41 | 34.57 | 61.84 | 94.14 | 31.81 | 0.00 | 0.00 | 744.00 |
September | 116.87 | 61.59 | 55.28 | 117.05 | 52.98 | 0.00 | 0.00 | 720.00 |
October | 122.06 | 76.59 | 45.47 | 116.26 | 77.37 | 0.00 | 0.00 | 744.00 |
November | 92.05 | 57.62 | 34.43 | 75.10 | 111.56 | 0.00 | 0.00 | 720.00 |
December | 98.13 | 74.32 | 23.81 | 85.25 | 153.13 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 102.78 | 53.11 | 49.68 | 87.19 | 83.22 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 80.83 | 16.45 | 23.81 | 60.19 | 26.45 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 128.24 | 86.65 | 64.39 | 117.05 | 164.86 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_DOOR
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 144.03 | 98.55 | 45.48 | 110.69 | 196.01 | 0.00 | 0.00 | 744.00 |
February | 154.40 | 104.32 | 50.07 | 120.41 | 159.99 | 0.00 | 0.00 | 672.00 |
March | 134.38 | 70.79 | 63.59 | 104.19 | 116.72 | 0.00 | 0.00 | 744.00 |
April | 121.01 | 56.57 | 64.44 | 92.77 | 87.87 | 0.00 | 0.00 | 720.00 |
May | 100.24 | 27.17 | 73.08 | 72.58 | 54.14 | 0.00 | 0.00 | 744.00 |
June | 97.32 | 19.80 | 77.52 | 82.61 | 37.60 | 0.00 | 0.00 | 720.00 |
July | 103.02 | 25.94 | 77.08 | 91.56 | 31.66 | 0.00 | 0.00 | 744.00 |
August | 116.07 | 41.62 | 74.46 | 113.23 | 38.03 | 0.00 | 0.00 | 744.00 |
September | 140.70 | 74.15 | 66.55 | 140.85 | 63.27 | 0.00 | 0.00 | 720.00 |
October | 146.95 | 92.21 | 54.74 | 140.12 | 92.22 | 0.00 | 0.00 | 744.00 |
November | 110.83 | 69.38 | 41.45 | 90.66 | 132.68 | 0.00 | 0.00 | 720.00 |
December | 118.14 | 89.48 | 28.66 | 102.89 | 182.15 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 123.75 | 63.94 | 59.81 | 105.13 | 99.07 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 97.32 | 19.80 | 28.66 | 72.58 | 31.66 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 154.40 | 104.32 | 77.52 | 140.85 | 196.01 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 119.63 | 81.86 | 37.77 | 91.87 | 159.53 | 0.00 | 0.00 | 744.00 |
February | 128.24 | 86.65 | 41.59 | 100.01 | 129.64 | 0.00 | 0.00 | 672.00 |
March | 111.62 | 58.80 | 52.82 | 86.76 | 93.91 | 0.00 | 0.00 | 744.00 |
April | 100.51 | 46.99 | 53.52 | 77.38 | 70.28 | 0.00 | 0.00 | 720.00 |
May | 83.26 | 22.56 | 60.70 | 60.97 | 43.73 | 0.00 | 0.00 | 744.00 |
June | 80.83 | 16.45 | 64.39 | 68.77 | 31.58 | 0.00 | 0.00 | 720.00 |
July | 85.57 | 21.55 | 64.02 | 75.94 | 27.64 | 0.00 | 0.00 | 744.00 |
August | 96.41 | 34.57 | 61.84 | 94.12 | 32.76 | 0.00 | 0.00 | 744.00 |
September | 116.87 | 61.59 | 55.28 | 117.31 | 52.35 | 0.00 | 0.00 | 720.00 |
October | 122.06 | 76.59 | 45.47 | 117.17 | 73.29 | 0.00 | 0.00 | 744.00 |
November | 92.05 | 57.62 | 34.43 | 75.70 | 106.52 | 0.00 | 0.00 | 720.00 |
December | 98.13 | 74.32 | 23.81 | 85.55 | 148.15 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 102.78 | 53.11 | 49.68 | 87.56 | 80.55 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 80.83 | 16.45 | 23.81 | 60.97 | 27.64 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 128.24 | 86.65 | 64.39 | 117.31 | 159.53 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 119.63 | 81.86 | 37.77 | 91.87 | 159.53 | 0.00 | 0.00 | 744.00 |
February | 128.24 | 86.65 | 41.59 | 100.01 | 129.64 | 0.00 | 0.00 | 672.00 |
March | 111.62 | 58.80 | 52.82 | 86.76 | 93.91 | 0.00 | 0.00 | 744.00 |
April | 100.51 | 46.99 | 53.52 | 77.38 | 70.28 | 0.00 | 0.00 | 720.00 |
May | 83.26 | 22.56 | 60.70 | 60.97 | 43.73 | 0.00 | 0.00 | 744.00 |
June | 80.83 | 16.45 | 64.39 | 68.77 | 31.58 | 0.00 | 0.00 | 720.00 |
July | 85.57 | 21.55 | 64.02 | 75.94 | 27.64 | 0.00 | 0.00 | 744.00 |
August | 96.41 | 34.57 | 61.84 | 94.12 | 32.76 | 0.00 | 0.00 | 744.00 |
September | 116.87 | 61.59 | 55.28 | 117.31 | 52.35 | 0.00 | 0.00 | 720.00 |
October | 122.06 | 76.59 | 45.47 | 117.17 | 73.29 | 0.00 | 0.00 | 744.00 |
November | 92.05 | 57.62 | 34.43 | 75.70 | 106.52 | 0.00 | 0.00 | 720.00 |
December | 98.13 | 74.32 | 23.81 | 85.55 | 148.15 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 102.78 | 53.11 | 49.68 | 87.56 | 80.55 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 80.83 | 16.45 | 23.81 | 60.97 | 27.64 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 128.24 | 86.65 | 64.39 | 117.31 | 159.53 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_DOOR
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 143.24 | 98.01 | 45.23 | 110.50 | 188.60 | 0.00 | 0.00 | 744.00 |
February | 153.55 | 103.75 | 49.80 | 120.23 | 153.29 | 0.00 | 0.00 | 672.00 |
March | 133.65 | 70.40 | 63.25 | 104.23 | 111.06 | 0.00 | 0.00 | 744.00 |
April | 120.35 | 56.26 | 64.09 | 92.81 | 83.19 | 0.00 | 0.00 | 720.00 |
May | 99.70 | 27.02 | 72.68 | 73.12 | 51.87 | 0.00 | 0.00 | 744.00 |
June | 96.79 | 19.69 | 77.10 | 82.27 | 37.50 | 0.00 | 0.00 | 720.00 |
July | 102.46 | 25.80 | 76.65 | 90.84 | 32.86 | 0.00 | 0.00 | 744.00 |
August | 115.44 | 41.39 | 74.05 | 112.60 | 38.90 | 0.00 | 0.00 | 744.00 |
September | 139.94 | 73.75 | 66.19 | 140.40 | 62.14 | 0.00 | 0.00 | 720.00 |
October | 146.15 | 91.71 | 54.44 | 140.45 | 86.88 | 0.00 | 0.00 | 744.00 |
November | 110.22 | 69.00 | 41.22 | 90.90 | 125.98 | 0.00 | 0.00 | 720.00 |
December | 117.49 | 88.99 | 28.51 | 102.70 | 175.25 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 123.07 | 63.59 | 59.48 | 105.00 | 95.35 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 96.79 | 19.69 | 28.51 | 73.12 | 32.86 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 153.55 | 103.75 | 77.10 | 140.45 | 188.60 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 119.63 | 81.86 | 37.77 | 92.03 | 158.06 | 0.00 | 0.00 | 744.00 |
February | 128.24 | 86.65 | 41.59 | 100.20 | 128.19 | 0.00 | 0.00 | 672.00 |
March | 111.62 | 58.80 | 52.82 | 87.03 | 92.45 | 0.00 | 0.00 | 744.00 |
April | 100.51 | 46.99 | 53.52 | 77.66 | 68.93 | 0.00 | 0.00 | 720.00 |
May | 83.26 | 22.56 | 60.70 | 61.46 | 42.67 | 0.00 | 0.00 | 744.00 |
June | 80.83 | 16.45 | 64.39 | 68.97 | 31.13 | 0.00 | 0.00 | 720.00 |
July | 85.57 | 21.55 | 64.02 | 76.03 | 27.48 | 0.00 | 0.00 | 744.00 |
August | 96.41 | 34.57 | 61.84 | 94.22 | 32.54 | 0.00 | 0.00 | 744.00 |
September | 116.87 | 61.59 | 55.28 | 117.49 | 51.69 | 0.00 | 0.00 | 720.00 |
October | 122.06 | 76.59 | 45.47 | 117.57 | 71.81 | 0.00 | 0.00 | 744.00 |
November | 92.05 | 57.62 | 34.43 | 75.99 | 104.85 | 0.00 | 0.00 | 720.00 |
December | 98.13 | 74.32 | 23.81 | 85.70 | 146.64 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 102.78 | 53.11 | 49.68 | 87.79 | 79.47 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 80.83 | 16.45 | 23.81 | 61.46 | 27.48 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 128.24 | 86.65 | 64.39 | 117.57 | 158.06 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 119.63 | 81.86 | 37.77 | 92.03 | 158.06 | 0.00 | 0.00 | 744.00 |
February | 128.24 | 86.65 | 41.59 | 100.20 | 128.19 | 0.00 | 0.00 | 672.00 |
March | 111.62 | 58.80 | 52.82 | 87.03 | 92.45 | 0.00 | 0.00 | 744.00 |
April | 100.51 | 46.99 | 53.52 | 77.66 | 68.93 | 0.00 | 0.00 | 720.00 |
May | 83.26 | 22.56 | 60.70 | 61.46 | 42.67 | 0.00 | 0.00 | 744.00 |
June | 80.83 | 16.45 | 64.39 | 68.97 | 31.13 | 0.00 | 0.00 | 720.00 |
July | 85.57 | 21.55 | 64.02 | 76.03 | 27.48 | 0.00 | 0.00 | 744.00 |
August | 96.41 | 34.57 | 61.84 | 94.22 | 32.54 | 0.00 | 0.00 | 744.00 |
September | 116.87 | 61.59 | 55.28 | 117.49 | 51.69 | 0.00 | 0.00 | 720.00 |
October | 122.06 | 76.59 | 45.47 | 117.57 | 71.81 | 0.00 | 0.00 | 744.00 |
November | 92.05 | 57.62 | 34.43 | 75.99 | 104.85 | 0.00 | 0.00 | 720.00 |
December | 98.13 | 74.32 | 23.81 | 85.70 | 146.64 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 102.78 | 53.11 | 49.68 | 87.79 | 79.47 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 80.83 | 16.45 | 23.81 | 61.46 | 27.48 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 128.24 | 86.65 | 64.39 | 117.57 | 158.06 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_DOOR
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 143.24 | 98.01 | 45.23 | 110.70 | 186.85 | 0.00 | 0.00 | 744.00 |
February | 153.55 | 103.75 | 49.80 | 120.47 | 151.57 | 0.00 | 0.00 | 672.00 |
March | 133.65 | 70.40 | 63.25 | 104.55 | 109.31 | 0.00 | 0.00 | 744.00 |
April | 120.35 | 56.26 | 64.09 | 93.15 | 81.58 | 0.00 | 0.00 | 720.00 |
May | 99.70 | 27.02 | 72.68 | 73.71 | 50.61 | 0.00 | 0.00 | 744.00 |
June | 96.79 | 19.69 | 77.10 | 82.52 | 36.96 | 0.00 | 0.00 | 720.00 |
July | 102.46 | 25.80 | 76.65 | 90.95 | 32.66 | 0.00 | 0.00 | 744.00 |
August | 115.44 | 41.39 | 74.05 | 112.72 | 38.65 | 0.00 | 0.00 | 744.00 |
September | 139.94 | 73.75 | 66.19 | 140.63 | 61.36 | 0.00 | 0.00 | 720.00 |
October | 146.15 | 91.71 | 54.44 | 140.94 | 85.12 | 0.00 | 0.00 | 744.00 |
November | 110.22 | 69.00 | 41.22 | 91.24 | 123.99 | 0.00 | 0.00 | 720.00 |
December | 117.49 | 88.99 | 28.51 | 102.89 | 173.44 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 123.07 | 63.59 | 59.48 | 105.29 | 94.07 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 96.79 | 19.69 | 28.51 | 73.71 | 32.66 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 153.55 | 103.75 | 77.10 | 140.94 | 186.85 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 119.63 | 81.86 | 37.77 | 92.16 | 157.34 | 0.00 | 0.00 | 744.00 |
February | 128.24 | 86.65 | 41.59 | 100.36 | 127.42 | 0.00 | 0.00 | 672.00 |
March | 111.62 | 58.80 | 52.82 | 87.23 | 91.60 | 0.00 | 0.00 | 744.00 |
April | 100.51 | 46.99 | 53.52 | 77.88 | 68.11 | 0.00 | 0.00 | 720.00 |
May | 83.26 | 22.56 | 60.70 | 61.87 | 41.92 | 0.00 | 0.00 | 744.00 |
June | 80.83 | 16.45 | 64.39 | 69.17 | 30.69 | 0.00 | 0.00 | 720.00 |
July | 85.57 | 21.55 | 64.02 | 76.15 | 27.18 | 0.00 | 0.00 | 744.00 |
August | 96.41 | 34.57 | 61.84 | 94.33 | 32.23 | 0.00 | 0.00 | 744.00 |
September | 116.87 | 61.59 | 55.28 | 117.64 | 51.21 | 0.00 | 0.00 | 720.00 |
October | 122.06 | 76.59 | 45.47 | 117.83 | 71.04 | 0.00 | 0.00 | 744.00 |
November | 92.05 | 57.62 | 34.43 | 76.19 | 103.94 | 0.00 | 0.00 | 720.00 |
December | 98.13 | 74.32 | 23.81 | 85.84 | 145.78 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 102.78 | 53.11 | 49.68 | 87.98 | 78.81 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 80.83 | 16.45 | 23.81 | 61.87 | 27.18 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 128.24 | 86.65 | 64.39 | 117.83 | 157.34 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 119.63 | 81.86 | 37.77 | 92.16 | 157.34 | 0.00 | 0.00 | 744.00 |
February | 128.24 | 86.65 | 41.59 | 100.36 | 127.42 | 0.00 | 0.00 | 672.00 |
March | 111.62 | 58.80 | 52.82 | 87.23 | 91.60 | 0.00 | 0.00 | 744.00 |
April | 100.51 | 46.99 | 53.52 | 77.88 | 68.11 | 0.00 | 0.00 | 720.00 |
May | 83.26 | 22.56 | 60.70 | 61.87 | 41.92 | 0.00 | 0.00 | 744.00 |
June | 80.83 | 16.45 | 64.39 | 69.17 | 30.69 | 0.00 | 0.00 | 720.00 |
July | 85.57 | 21.55 | 64.02 | 76.15 | 27.18 | 0.00 | 0.00 | 744.00 |
August | 96.41 | 34.57 | 61.84 | 94.33 | 32.23 | 0.00 | 0.00 | 744.00 |
September | 116.87 | 61.59 | 55.28 | 117.64 | 51.21 | 0.00 | 0.00 | 720.00 |
October | 122.06 | 76.59 | 45.47 | 117.83 | 71.04 | 0.00 | 0.00 | 744.00 |
November | 92.05 | 57.62 | 34.43 | 76.19 | 103.94 | 0.00 | 0.00 | 720.00 |
December | 98.13 | 74.32 | 23.81 | 85.84 | 145.78 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 102.78 | 53.11 | 49.68 | 87.98 | 78.81 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 80.83 | 16.45 | 23.81 | 61.87 | 27.18 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 128.24 | 86.65 | 64.39 | 117.83 | 157.34 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_DOOR
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 143.24 | 98.01 | 45.23 | 110.85 | 185.99 | 0.00 | 0.00 | 744.00 |
February | 153.55 | 103.75 | 49.80 | 120.66 | 150.64 | 0.00 | 0.00 | 672.00 |
March | 133.65 | 70.40 | 63.25 | 104.81 | 108.31 | 0.00 | 0.00 | 744.00 |
April | 120.35 | 56.26 | 64.09 | 93.42 | 80.61 | 0.00 | 0.00 | 720.00 |
May | 99.70 | 27.02 | 72.68 | 74.20 | 49.73 | 0.00 | 0.00 | 744.00 |
June | 96.79 | 19.69 | 77.10 | 82.76 | 36.44 | 0.00 | 0.00 | 720.00 |
July | 102.46 | 25.80 | 76.65 | 91.09 | 32.31 | 0.00 | 0.00 | 744.00 |
August | 115.44 | 41.39 | 74.05 | 112.84 | 38.28 | 0.00 | 0.00 | 744.00 |
September | 139.94 | 73.75 | 66.19 | 140.80 | 60.80 | 0.00 | 0.00 | 720.00 |
October | 146.15 | 91.71 | 54.44 | 141.25 | 84.20 | 0.00 | 0.00 | 744.00 |
November | 110.22 | 69.00 | 41.22 | 91.49 | 122.92 | 0.00 | 0.00 | 720.00 |
December | 117.49 | 88.99 | 28.51 | 103.05 | 172.42 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 123.07 | 63.59 | 59.48 | 105.52 | 93.29 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 96.79 | 19.69 | 28.51 | 74.20 | 32.31 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 153.55 | 103.75 | 77.10 | 141.25 | 185.99 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 119.63 | 81.86 | 37.77 | 93.14 | 153.82 | 0.00 | 0.00 | 744.00 |
February | 128.24 | 86.65 | 41.59 | 101.45 | 124.11 | 0.00 | 0.00 | 672.00 |
March | 111.62 | 58.80 | 52.82 | 88.24 | 88.57 | 0.00 | 0.00 | 744.00 |
April | 100.51 | 46.99 | 53.52 | 78.56 | 65.75 | 0.00 | 0.00 | 720.00 |
May | 83.26 | 22.56 | 60.70 | 62.55 | 40.42 | 0.00 | 0.00 | 744.00 |
June | 80.83 | 16.45 | 64.39 | 69.37 | 29.59 | 0.00 | 0.00 | 720.00 |
July | 85.57 | 21.55 | 64.02 | 76.20 | 26.29 | 0.00 | 0.00 | 744.00 |
August | 96.41 | 34.57 | 61.84 | 94.41 | 31.33 | 0.00 | 0.00 | 744.00 |
September | 116.87 | 61.59 | 55.28 | 117.84 | 50.20 | 0.00 | 0.00 | 720.00 |
October | 122.06 | 76.59 | 45.47 | 118.70 | 69.30 | 0.00 | 0.00 | 744.00 |
November | 92.05 | 57.62 | 34.43 | 77.03 | 101.01 | 0.00 | 0.00 | 720.00 |
December | 98.13 | 74.32 | 23.81 | 86.69 | 142.10 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 102.78 | 53.11 | 49.68 | 88.61 | 76.65 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 80.83 | 16.45 | 23.81 | 62.55 | 26.29 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 128.24 | 86.65 | 64.39 | 118.70 | 153.82 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 119.63 | 81.86 | 37.77 | 93.14 | 153.82 | 0.00 | 0.00 | 744.00 |
February | 128.24 | 86.65 | 41.59 | 101.45 | 124.11 | 0.00 | 0.00 | 672.00 |
March | 111.62 | 58.80 | 52.82 | 88.24 | 88.57 | 0.00 | 0.00 | 744.00 |
April | 100.51 | 46.99 | 53.52 | 78.56 | 65.75 | 0.00 | 0.00 | 720.00 |
May | 83.26 | 22.56 | 60.70 | 62.55 | 40.42 | 0.00 | 0.00 | 744.00 |
June | 80.83 | 16.45 | 64.39 | 69.37 | 29.59 | 0.00 | 0.00 | 720.00 |
July | 85.57 | 21.55 | 64.02 | 76.20 | 26.29 | 0.00 | 0.00 | 744.00 |
August | 96.41 | 34.57 | 61.84 | 94.41 | 31.33 | 0.00 | 0.00 | 744.00 |
September | 116.87 | 61.59 | 55.28 | 117.84 | 50.20 | 0.00 | 0.00 | 720.00 |
October | 122.06 | 76.59 | 45.47 | 118.70 | 69.30 | 0.00 | 0.00 | 744.00 |
November | 92.05 | 57.62 | 34.43 | 77.03 | 101.01 | 0.00 | 0.00 | 720.00 |
December | 98.13 | 74.32 | 23.81 | 86.69 | 142.10 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 102.78 | 53.11 | 49.68 | 88.61 | 76.65 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 80.83 | 16.45 | 23.81 | 62.55 | 26.29 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 128.24 | 86.65 | 64.39 | 118.70 | 153.82 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_3
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 119.63 | 81.86 | 37.77 | 93.14 | 153.82 | 0.00 | 0.00 | 744.00 |
February | 128.24 | 86.65 | 41.59 | 101.45 | 124.11 | 0.00 | 0.00 | 672.00 |
March | 111.62 | 58.80 | 52.82 | 88.24 | 88.57 | 0.00 | 0.00 | 744.00 |
April | 100.51 | 46.99 | 53.52 | 78.56 | 65.75 | 0.00 | 0.00 | 720.00 |
May | 83.26 | 22.56 | 60.70 | 62.55 | 40.42 | 0.00 | 0.00 | 744.00 |
June | 80.83 | 16.45 | 64.39 | 69.37 | 29.59 | 0.00 | 0.00 | 720.00 |
July | 85.57 | 21.55 | 64.02 | 76.20 | 26.29 | 0.00 | 0.00 | 744.00 |
August | 96.41 | 34.57 | 61.84 | 94.41 | 31.33 | 0.00 | 0.00 | 744.00 |
September | 116.87 | 61.59 | 55.28 | 117.84 | 50.20 | 0.00 | 0.00 | 720.00 |
October | 122.06 | 76.59 | 45.47 | 118.70 | 69.30 | 0.00 | 0.00 | 744.00 |
November | 92.05 | 57.62 | 34.43 | 77.03 | 101.01 | 0.00 | 0.00 | 720.00 |
December | 98.13 | 74.32 | 23.81 | 86.69 | 142.10 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 102.78 | 53.11 | 49.68 | 88.61 | 76.65 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 80.83 | 16.45 | 23.81 | 62.55 | 26.29 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 128.24 | 86.65 | 64.39 | 118.70 | 153.82 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_4
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 119.63 | 81.86 | 37.77 | 93.14 | 153.82 | 0.00 | 0.00 | 744.00 |
February | 128.24 | 86.65 | 41.59 | 101.45 | 124.11 | 0.00 | 0.00 | 672.00 |
March | 111.62 | 58.80 | 52.82 | 88.24 | 88.57 | 0.00 | 0.00 | 744.00 |
April | 100.51 | 46.99 | 53.52 | 78.56 | 65.75 | 0.00 | 0.00 | 720.00 |
May | 83.26 | 22.56 | 60.70 | 62.55 | 40.42 | 0.00 | 0.00 | 744.00 |
June | 80.83 | 16.45 | 64.39 | 69.37 | 29.59 | 0.00 | 0.00 | 720.00 |
July | 85.57 | 21.55 | 64.02 | 76.20 | 26.29 | 0.00 | 0.00 | 744.00 |
August | 96.41 | 34.57 | 61.84 | 94.41 | 31.33 | 0.00 | 0.00 | 744.00 |
September | 116.87 | 61.59 | 55.28 | 117.84 | 50.20 | 0.00 | 0.00 | 720.00 |
October | 122.06 | 76.59 | 45.47 | 118.70 | 69.30 | 0.00 | 0.00 | 744.00 |
November | 92.05 | 57.62 | 34.43 | 77.03 | 101.01 | 0.00 | 0.00 | 720.00 |
December | 98.13 | 74.32 | 23.81 | 86.69 | 142.10 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 102.78 | 53.11 | 49.68 | 88.61 | 76.65 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 80.83 | 16.45 | 23.81 | 62.55 | 26.29 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 128.24 | 86.65 | 64.39 | 118.70 | 153.82 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_DOOR_1
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 143.24 | 98.01 | 45.23 | 112.02 | 181.87 | 0.00 | 0.00 | 744.00 |
February | 153.55 | 103.75 | 49.80 | 121.95 | 146.77 | 0.00 | 0.00 | 672.00 |
March | 133.65 | 70.40 | 63.25 | 106.01 | 104.76 | 0.00 | 0.00 | 744.00 |
April | 120.35 | 56.26 | 64.09 | 94.24 | 77.84 | 0.00 | 0.00 | 720.00 |
May | 99.70 | 27.02 | 72.68 | 75.01 | 47.96 | 0.00 | 0.00 | 744.00 |
June | 96.79 | 19.69 | 77.10 | 83.01 | 35.15 | 0.00 | 0.00 | 720.00 |
July | 102.46 | 25.80 | 76.65 | 91.17 | 31.27 | 0.00 | 0.00 | 744.00 |
August | 115.44 | 41.39 | 74.05 | 112.95 | 37.22 | 0.00 | 0.00 | 744.00 |
September | 139.94 | 73.75 | 66.19 | 141.05 | 59.60 | 0.00 | 0.00 | 720.00 |
October | 146.15 | 91.71 | 54.44 | 142.28 | 82.16 | 0.00 | 0.00 | 744.00 |
November | 110.22 | 69.00 | 41.22 | 92.49 | 119.48 | 0.00 | 0.00 | 720.00 |
December | 117.49 | 88.99 | 28.51 | 104.06 | 168.10 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 123.07 | 63.59 | 59.48 | 106.27 | 90.75 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 96.79 | 19.69 | 28.51 | 75.01 | 31.27 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 153.55 | 103.75 | 77.10 | 142.28 | 181.87 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_DOOR_2
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 143.24 | 98.01 | 45.23 | 112.02 | 181.87 | 0.00 | 0.00 | 744.00 |
February | 153.55 | 103.75 | 49.80 | 121.95 | 146.77 | 0.00 | 0.00 | 672.00 |
March | 133.65 | 70.40 | 63.25 | 106.01 | 104.76 | 0.00 | 0.00 | 744.00 |
April | 120.35 | 56.26 | 64.09 | 94.24 | 77.84 | 0.00 | 0.00 | 720.00 |
May | 99.70 | 27.02 | 72.68 | 75.01 | 47.96 | 0.00 | 0.00 | 744.00 |
June | 96.79 | 19.69 | 77.10 | 83.01 | 35.15 | 0.00 | 0.00 | 720.00 |
July | 102.46 | 25.80 | 76.65 | 91.17 | 31.27 | 0.00 | 0.00 | 744.00 |
August | 115.44 | 41.39 | 74.05 | 112.95 | 37.22 | 0.00 | 0.00 | 744.00 |
September | 139.94 | 73.75 | 66.19 | 141.05 | 59.60 | 0.00 | 0.00 | 720.00 |
October | 146.15 | 91.71 | 54.44 | 142.28 | 82.16 | 0.00 | 0.00 | 744.00 |
November | 110.22 | 69.00 | 41.22 | 92.49 | 119.48 | 0.00 | 0.00 | 720.00 |
December | 117.49 | 88.99 | 28.51 | 104.06 | 168.10 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 123.07 | 63.59 | 59.48 | 106.27 | 90.75 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 96.79 | 19.69 | 28.51 | 75.01 | 31.27 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 153.55 | 103.75 | 77.10 | 142.28 | 181.87 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 119.63 | 81.86 | 37.77 | 92.59 | 155.10 | 0.00 | 0.00 | 744.00 |
February | 128.24 | 86.65 | 41.59 | 100.92 | 125.15 | 0.00 | 0.00 | 672.00 |
March | 111.62 | 58.80 | 52.82 | 87.83 | 89.28 | 0.00 | 0.00 | 744.00 |
April | 100.51 | 46.99 | 53.52 | 78.47 | 66.06 | 0.00 | 0.00 | 720.00 |
May | 83.26 | 22.56 | 60.70 | 62.87 | 40.20 | 0.00 | 0.00 | 744.00 |
June | 80.83 | 16.45 | 64.39 | 69.68 | 29.32 | 0.00 | 0.00 | 720.00 |
July | 85.57 | 21.55 | 64.02 | 76.46 | 26.01 | 0.00 | 0.00 | 744.00 |
August | 96.41 | 34.57 | 61.84 | 94.60 | 31.07 | 0.00 | 0.00 | 744.00 |
September | 116.87 | 61.59 | 55.28 | 117.98 | 49.98 | 0.00 | 0.00 | 720.00 |
October | 122.06 | 76.59 | 45.47 | 118.45 | 69.44 | 0.00 | 0.00 | 744.00 |
November | 92.05 | 57.62 | 34.43 | 76.72 | 101.76 | 0.00 | 0.00 | 720.00 |
December | 98.13 | 74.32 | 23.81 | 86.31 | 143.32 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 102.78 | 53.11 | 49.68 | 88.50 | 77.00 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 80.83 | 16.45 | 23.81 | 62.87 | 26.01 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 128.24 | 86.65 | 64.39 | 118.45 | 155.10 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 119.63 | 81.86 | 37.77 | 92.59 | 155.10 | 0.00 | 0.00 | 744.00 |
February | 128.24 | 86.65 | 41.59 | 100.92 | 125.15 | 0.00 | 0.00 | 672.00 |
March | 111.62 | 58.80 | 52.82 | 87.83 | 89.28 | 0.00 | 0.00 | 744.00 |
April | 100.51 | 46.99 | 53.52 | 78.47 | 66.06 | 0.00 | 0.00 | 720.00 |
May | 83.26 | 22.56 | 60.70 | 62.87 | 40.20 | 0.00 | 0.00 | 744.00 |
June | 80.83 | 16.45 | 64.39 | 69.68 | 29.32 | 0.00 | 0.00 | 720.00 |
July | 85.57 | 21.55 | 64.02 | 76.46 | 26.01 | 0.00 | 0.00 | 744.00 |
August | 96.41 | 34.57 | 61.84 | 94.60 | 31.07 | 0.00 | 0.00 | 744.00 |
September | 116.87 | 61.59 | 55.28 | 117.98 | 49.98 | 0.00 | 0.00 | 720.00 |
October | 122.06 | 76.59 | 45.47 | 118.45 | 69.44 | 0.00 | 0.00 | 744.00 |
November | 92.05 | 57.62 | 34.43 | 76.72 | 101.76 | 0.00 | 0.00 | 720.00 |
December | 98.13 | 74.32 | 23.81 | 86.31 | 143.32 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 102.78 | 53.11 | 49.68 | 88.50 | 77.00 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 80.83 | 16.45 | 23.81 | 62.87 | 26.01 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 128.24 | 86.65 | 64.39 | 118.45 | 155.10 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_DOOR
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 143.24 | 98.01 | 45.23 | 111.39 | 183.33 | 0.00 | 0.00 | 744.00 |
February | 153.55 | 103.75 | 49.80 | 121.34 | 147.95 | 0.00 | 0.00 | 672.00 |
March | 133.65 | 70.40 | 63.25 | 105.54 | 105.56 | 0.00 | 0.00 | 744.00 |
April | 120.35 | 56.26 | 64.09 | 94.14 | 78.18 | 0.00 | 0.00 | 720.00 |
May | 99.70 | 27.02 | 72.68 | 75.41 | 47.68 | 0.00 | 0.00 | 744.00 |
June | 96.79 | 19.69 | 77.10 | 83.38 | 34.81 | 0.00 | 0.00 | 720.00 |
July | 102.46 | 25.80 | 76.65 | 91.48 | 30.93 | 0.00 | 0.00 | 744.00 |
August | 115.44 | 41.39 | 74.05 | 113.19 | 36.91 | 0.00 | 0.00 | 744.00 |
September | 139.94 | 73.75 | 66.19 | 141.22 | 59.33 | 0.00 | 0.00 | 720.00 |
October | 146.15 | 91.71 | 54.44 | 142.01 | 82.31 | 0.00 | 0.00 | 744.00 |
November | 110.22 | 69.00 | 41.22 | 92.13 | 120.33 | 0.00 | 0.00 | 720.00 |
December | 117.49 | 88.99 | 28.51 | 103.63 | 169.50 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 123.07 | 63.59 | 59.48 | 106.15 | 91.14 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 96.79 | 19.69 | 28.51 | 75.41 | 30.93 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 153.55 | 103.75 | 77.10 | 142.01 | 183.33 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 119.63 | 81.86 | 37.77 | 92.61 | 155.00 | 0.00 | 0.00 | 744.00 |
February | 128.24 | 86.65 | 41.59 | 100.95 | 124.97 | 0.00 | 0.00 | 672.00 |
March | 111.62 | 58.80 | 52.82 | 87.91 | 89.01 | 0.00 | 0.00 | 744.00 |
April | 100.51 | 46.99 | 53.52 | 78.60 | 65.67 | 0.00 | 0.00 | 720.00 |
May | 83.26 | 22.56 | 60.70 | 63.23 | 39.64 | 0.00 | 0.00 | 744.00 |
June | 80.83 | 16.45 | 64.39 | 69.86 | 29.03 | 0.00 | 0.00 | 720.00 |
July | 85.57 | 21.55 | 64.02 | 76.58 | 25.84 | 0.00 | 0.00 | 744.00 |
August | 96.41 | 34.57 | 61.84 | 94.71 | 30.90 | 0.00 | 0.00 | 744.00 |
September | 116.87 | 61.59 | 55.28 | 118.11 | 49.69 | 0.00 | 0.00 | 720.00 |
October | 122.06 | 76.59 | 45.47 | 118.57 | 69.12 | 0.00 | 0.00 | 744.00 |
November | 92.05 | 57.62 | 34.43 | 76.78 | 101.50 | 0.00 | 0.00 | 720.00 |
December | 98.13 | 74.32 | 23.81 | 86.34 | 143.15 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 102.78 | 53.11 | 49.68 | 88.62 | 76.74 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 80.83 | 16.45 | 23.81 | 63.23 | 25.84 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 128.24 | 86.65 | 64.39 | 118.57 | 155.00 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 119.63 | 81.86 | 37.77 | 92.61 | 155.00 | 0.00 | 0.00 | 744.00 |
February | 128.24 | 86.65 | 41.59 | 100.95 | 124.97 | 0.00 | 0.00 | 672.00 |
March | 111.62 | 58.80 | 52.82 | 87.91 | 89.01 | 0.00 | 0.00 | 744.00 |
April | 100.51 | 46.99 | 53.52 | 78.60 | 65.67 | 0.00 | 0.00 | 720.00 |
May | 83.26 | 22.56 | 60.70 | 63.23 | 39.64 | 0.00 | 0.00 | 744.00 |
June | 80.83 | 16.45 | 64.39 | 69.86 | 29.03 | 0.00 | 0.00 | 720.00 |
July | 85.57 | 21.55 | 64.02 | 76.58 | 25.84 | 0.00 | 0.00 | 744.00 |
August | 96.41 | 34.57 | 61.84 | 94.71 | 30.90 | 0.00 | 0.00 | 744.00 |
September | 116.87 | 61.59 | 55.28 | 118.11 | 49.69 | 0.00 | 0.00 | 720.00 |
October | 122.06 | 76.59 | 45.47 | 118.57 | 69.12 | 0.00 | 0.00 | 744.00 |
November | 92.05 | 57.62 | 34.43 | 76.78 | 101.50 | 0.00 | 0.00 | 720.00 |
December | 98.13 | 74.32 | 23.81 | 86.34 | 143.15 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 102.78 | 53.11 | 49.68 | 88.62 | 76.74 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 80.83 | 16.45 | 23.81 | 63.23 | 25.84 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 128.24 | 86.65 | 64.39 | 118.57 | 155.00 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_DOOR
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 143.24 | 98.01 | 45.23 | 111.41 | 183.22 | 0.00 | 0.00 | 744.00 |
February | 153.55 | 103.75 | 49.80 | 121.38 | 147.74 | 0.00 | 0.00 | 672.00 |
March | 133.65 | 70.40 | 63.25 | 105.63 | 105.24 | 0.00 | 0.00 | 744.00 |
April | 120.35 | 56.26 | 64.09 | 94.29 | 77.71 | 0.00 | 0.00 | 720.00 |
May | 99.70 | 27.02 | 72.68 | 75.84 | 47.02 | 0.00 | 0.00 | 744.00 |
June | 96.79 | 19.69 | 77.10 | 83.60 | 34.48 | 0.00 | 0.00 | 720.00 |
July | 102.46 | 25.80 | 76.65 | 91.63 | 30.72 | 0.00 | 0.00 | 744.00 |
August | 115.44 | 41.39 | 74.05 | 113.32 | 36.71 | 0.00 | 0.00 | 744.00 |
September | 139.94 | 73.75 | 66.19 | 141.37 | 58.98 | 0.00 | 0.00 | 720.00 |
October | 146.15 | 91.71 | 54.44 | 142.15 | 81.93 | 0.00 | 0.00 | 744.00 |
November | 110.22 | 69.00 | 41.22 | 92.21 | 120.01 | 0.00 | 0.00 | 720.00 |
December | 117.49 | 88.99 | 28.51 | 103.66 | 169.30 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 123.07 | 63.59 | 59.48 | 106.29 | 90.82 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 96.79 | 19.69 | 28.51 | 75.84 | 30.72 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 153.55 | 103.75 | 77.10 | 142.15 | 183.22 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 119.63 | 81.86 | 37.77 | 92.72 | 154.30 | 0.00 | 0.00 | 744.00 |
February | 128.24 | 86.65 | 41.59 | 101.12 | 123.96 | 0.00 | 0.00 | 672.00 |
March | 111.62 | 58.80 | 52.82 | 88.20 | 87.71 | 0.00 | 0.00 | 744.00 |
April | 100.51 | 46.99 | 53.52 | 79.00 | 64.10 | 0.00 | 0.00 | 720.00 |
May | 83.26 | 22.56 | 60.70 | 64.11 | 38.09 | 0.00 | 0.00 | 744.00 |
June | 80.83 | 16.45 | 64.39 | 70.30 | 28.23 | 0.00 | 0.00 | 720.00 |
July | 85.57 | 21.55 | 64.02 | 76.85 | 25.36 | 0.00 | 0.00 | 744.00 |
August | 96.41 | 34.57 | 61.84 | 94.92 | 30.43 | 0.00 | 0.00 | 744.00 |
September | 116.87 | 61.59 | 55.28 | 118.36 | 48.94 | 0.00 | 0.00 | 720.00 |
October | 122.06 | 76.59 | 45.47 | 118.89 | 68.06 | 0.00 | 0.00 | 744.00 |
November | 92.05 | 57.62 | 34.43 | 77.00 | 100.43 | 0.00 | 0.00 | 720.00 |
December | 98.13 | 74.32 | 23.81 | 86.47 | 142.14 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 102.78 | 53.11 | 49.68 | 88.93 | 75.75 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 80.83 | 16.45 | 23.81 | 64.11 | 25.36 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 128.24 | 86.65 | 64.39 | 118.89 | 154.30 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 119.63 | 81.86 | 37.77 | 92.72 | 154.30 | 0.00 | 0.00 | 744.00 |
February | 128.24 | 86.65 | 41.59 | 101.12 | 123.96 | 0.00 | 0.00 | 672.00 |
March | 111.62 | 58.80 | 52.82 | 88.20 | 87.71 | 0.00 | 0.00 | 744.00 |
April | 100.51 | 46.99 | 53.52 | 79.00 | 64.10 | 0.00 | 0.00 | 720.00 |
May | 83.26 | 22.56 | 60.70 | 64.11 | 38.09 | 0.00 | 0.00 | 744.00 |
June | 80.83 | 16.45 | 64.39 | 70.30 | 28.23 | 0.00 | 0.00 | 720.00 |
July | 85.57 | 21.55 | 64.02 | 76.85 | 25.36 | 0.00 | 0.00 | 744.00 |
August | 96.41 | 34.57 | 61.84 | 94.92 | 30.43 | 0.00 | 0.00 | 744.00 |
September | 116.87 | 61.59 | 55.28 | 118.36 | 48.94 | 0.00 | 0.00 | 720.00 |
October | 122.06 | 76.59 | 45.47 | 118.89 | 68.06 | 0.00 | 0.00 | 744.00 |
November | 92.05 | 57.62 | 34.43 | 77.00 | 100.43 | 0.00 | 0.00 | 720.00 |
December | 98.13 | 74.32 | 23.81 | 86.47 | 142.14 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 102.78 | 53.11 | 49.68 | 88.93 | 75.75 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 80.83 | 16.45 | 23.81 | 64.11 | 25.36 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 128.24 | 86.65 | 64.39 | 118.89 | 154.30 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_DOOR
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 143.24 | 98.01 | 45.23 | 111.55 | 182.37 | 0.00 | 0.00 | 744.00 |
February | 153.55 | 103.75 | 49.80 | 121.58 | 146.53 | 0.00 | 0.00 | 672.00 |
March | 133.65 | 70.40 | 63.25 | 105.98 | 103.70 | 0.00 | 0.00 | 744.00 |
April | 120.35 | 56.26 | 64.09 | 94.77 | 75.85 | 0.00 | 0.00 | 720.00 |
May | 99.70 | 27.02 | 72.68 | 76.89 | 45.19 | 0.00 | 0.00 | 744.00 |
June | 96.79 | 19.69 | 77.10 | 84.13 | 33.53 | 0.00 | 0.00 | 720.00 |
July | 102.46 | 25.80 | 76.65 | 91.95 | 30.15 | 0.00 | 0.00 | 744.00 |
August | 115.44 | 41.39 | 74.05 | 113.57 | 36.16 | 0.00 | 0.00 | 744.00 |
September | 139.94 | 73.75 | 66.19 | 141.68 | 58.10 | 0.00 | 0.00 | 720.00 |
October | 146.15 | 91.71 | 54.44 | 142.54 | 80.67 | 0.00 | 0.00 | 744.00 |
November | 110.22 | 69.00 | 41.22 | 92.47 | 118.74 | 0.00 | 0.00 | 720.00 |
December | 117.49 | 88.99 | 28.51 | 103.82 | 168.09 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 123.07 | 63.59 | 59.48 | 106.66 | 89.66 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 96.79 | 19.69 | 28.51 | 76.89 | 30.15 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 153.55 | 103.75 | 77.10 | 142.54 | 182.37 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 119.63 | 81.86 | 37.77 | 93.53 | 149.76 | 0.00 | 0.00 | 744.00 |
February | 128.24 | 86.65 | 41.59 | 102.10 | 118.65 | 0.00 | 0.00 | 672.00 |
March | 111.62 | 58.80 | 52.82 | 89.44 | 81.76 | 0.00 | 0.00 | 744.00 |
April | 100.51 | 46.99 | 53.52 | 80.41 | 57.43 | 0.00 | 0.00 | 720.00 |
May | 83.26 | 22.56 | 60.70 | 66.50 | 32.90 | 0.00 | 0.00 | 744.00 |
June | 80.83 | 16.45 | 64.39 | 71.70 | 25.04 | 0.00 | 0.00 | 720.00 |
July | 85.57 | 21.55 | 64.02 | 77.71 | 23.27 | 0.00 | 0.00 | 744.00 |
August | 96.41 | 34.57 | 61.84 | 95.50 | 28.40 | 0.00 | 0.00 | 744.00 |
September | 116.87 | 61.59 | 55.28 | 118.96 | 46.02 | 0.00 | 0.00 | 720.00 |
October | 122.06 | 76.59 | 45.47 | 119.86 | 63.73 | 0.00 | 0.00 | 744.00 |
November | 92.05 | 57.62 | 34.43 | 77.78 | 95.64 | 0.00 | 0.00 | 720.00 |
December | 98.13 | 74.32 | 23.81 | 87.10 | 137.13 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 102.78 | 53.11 | 49.68 | 89.98 | 71.43 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 80.83 | 16.45 | 23.81 | 66.50 | 23.27 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 128.24 | 86.65 | 64.39 | 119.86 | 149.76 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 119.63 | 81.86 | 37.77 | 93.53 | 149.76 | 0.00 | 0.00 | 744.00 |
February | 128.24 | 86.65 | 41.59 | 102.10 | 118.65 | 0.00 | 0.00 | 672.00 |
March | 111.62 | 58.80 | 52.82 | 89.44 | 81.76 | 0.00 | 0.00 | 744.00 |
April | 100.51 | 46.99 | 53.52 | 80.41 | 57.43 | 0.00 | 0.00 | 720.00 |
May | 83.26 | 22.56 | 60.70 | 66.50 | 32.90 | 0.00 | 0.00 | 744.00 |
June | 80.83 | 16.45 | 64.39 | 71.70 | 25.04 | 0.00 | 0.00 | 720.00 |
July | 85.57 | 21.55 | 64.02 | 77.71 | 23.27 | 0.00 | 0.00 | 744.00 |
August | 96.41 | 34.57 | 61.84 | 95.50 | 28.40 | 0.00 | 0.00 | 744.00 |
September | 116.87 | 61.59 | 55.28 | 118.96 | 46.02 | 0.00 | 0.00 | 720.00 |
October | 122.06 | 76.59 | 45.47 | 119.86 | 63.73 | 0.00 | 0.00 | 744.00 |
November | 92.05 | 57.62 | 34.43 | 77.78 | 95.64 | 0.00 | 0.00 | 720.00 |
December | 98.13 | 74.32 | 23.81 | 87.10 | 137.13 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 102.78 | 53.11 | 49.68 | 89.98 | 71.43 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 80.83 | 16.45 | 23.81 | 66.50 | 23.27 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 128.24 | 86.65 | 64.39 | 119.86 | 149.76 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_DOOR
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 143.24 | 98.01 | 45.23 | 112.54 | 176.93 | 0.00 | 0.00 | 744.00 |
February | 153.55 | 103.75 | 49.80 | 122.78 | 140.18 | 0.00 | 0.00 | 672.00 |
March | 133.65 | 70.40 | 63.25 | 107.50 | 96.62 | 0.00 | 0.00 | 744.00 |
April | 120.35 | 56.26 | 64.09 | 96.49 | 67.93 | 0.00 | 0.00 | 720.00 |
May | 99.70 | 27.02 | 72.68 | 79.77 | 39.05 | 0.00 | 0.00 | 744.00 |
June | 96.79 | 19.69 | 77.10 | 85.81 | 29.76 | 0.00 | 0.00 | 720.00 |
July | 102.46 | 25.80 | 76.65 | 92.99 | 27.69 | 0.00 | 0.00 | 744.00 |
August | 115.44 | 41.39 | 74.05 | 114.27 | 33.76 | 0.00 | 0.00 | 744.00 |
September | 139.94 | 73.75 | 66.19 | 142.41 | 54.65 | 0.00 | 0.00 | 720.00 |
October | 146.15 | 91.71 | 54.44 | 143.71 | 75.56 | 0.00 | 0.00 | 744.00 |
November | 110.22 | 69.00 | 41.22 | 93.43 | 113.06 | 0.00 | 0.00 | 720.00 |
December | 117.49 | 88.99 | 28.51 | 104.59 | 162.10 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 123.07 | 63.59 | 59.48 | 107.94 | 84.52 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 96.79 | 19.69 | 28.51 | 79.77 | 27.69 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 153.55 | 103.75 | 77.10 | 143.71 | 176.93 | 0.00 | 0.00 | 744.00 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.320420E+09 | 0.219248E+09 | 0.101171E+09 | 0.248499E+09 | 0.428751E+09 |
February | 0.310244E+09 | 0.209629E+09 | 0.100615E+09 | 0.244348E+09 | 0.313306E+09 |
March | 0.298959E+09 | 0.157481E+09 | 0.141478E+09 | 0.234947E+09 | 0.248600E+09 |
April | 0.260528E+09 | 0.121793E+09 | 0.138735E+09 | 0.202319E+09 | 0.178570E+09 |
May | 0.223012E+09 | 60435776.82 | 0.162576E+09 | 0.163999E+09 | 0.115405E+09 |
June | 0.209524E+09 | 42632042.87 | 0.166892E+09 | 0.179246E+09 | 78635270.91 |
July | 0.229186E+09 | 57717198.46 | 0.171469E+09 | 0.204489E+09 | 69596925.31 |
August | 0.258228E+09 | 92583616.90 | 0.165644E+09 | 0.252524E+09 | 83888008.30 |
September | 0.302924E+09 | 0.159644E+09 | 0.143280E+09 | 0.304140E+09 | 0.133893E+09 |
October | 0.326917E+09 | 0.205140E+09 | 0.121778E+09 | 0.314160E+09 | 0.197285E+09 |
November | 0.238598E+09 | 0.149360E+09 | 89237204.53 | 0.197097E+09 | 0.277383E+09 |
December | 0.262824E+09 | 0.199060E+09 | 63763438.80 | 0.230855E+09 | 0.396166E+09 |
Annual Sum or Average | 0.324136E+10 | 0.167472E+10 | 0.156664E+10 | 0.277662E+10 | 0.252148E+10 |
Minimum of Months | 0.209524E+09 | 42632042.87 | 63763438.80 | 0.163999E+09 | 69596925.31 |
Maximum of Months | 0.326917E+09 | 0.219248E+09 | 0.171469E+09 | 0.314160E+09 | 0.428751E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.320420E+09 | 0.219248E+09 | 0.101171E+09 | 0.248499E+09 | 0.428751E+09 |
February | 0.310244E+09 | 0.209629E+09 | 0.100615E+09 | 0.244348E+09 | 0.313306E+09 |
March | 0.298959E+09 | 0.157481E+09 | 0.141478E+09 | 0.234947E+09 | 0.248600E+09 |
April | 0.260528E+09 | 0.121793E+09 | 0.138735E+09 | 0.202319E+09 | 0.178570E+09 |
May | 0.223012E+09 | 60435776.82 | 0.162576E+09 | 0.163999E+09 | 0.115405E+09 |
June | 0.209524E+09 | 42632042.87 | 0.166892E+09 | 0.179246E+09 | 78635270.91 |
July | 0.229186E+09 | 57717198.46 | 0.171469E+09 | 0.204489E+09 | 69596925.31 |
August | 0.258228E+09 | 92583616.90 | 0.165644E+09 | 0.252524E+09 | 83888008.30 |
September | 0.302924E+09 | 0.159644E+09 | 0.143280E+09 | 0.304140E+09 | 0.133893E+09 |
October | 0.326917E+09 | 0.205140E+09 | 0.121778E+09 | 0.314160E+09 | 0.197285E+09 |
November | 0.238598E+09 | 0.149360E+09 | 89237204.53 | 0.197097E+09 | 0.277383E+09 |
December | 0.262824E+09 | 0.199060E+09 | 63763438.80 | 0.230855E+09 | 0.396166E+09 |
Annual Sum or Average | 0.324136E+10 | 0.167472E+10 | 0.156664E+10 | 0.277662E+10 | 0.252148E+10 |
Minimum of Months | 0.209524E+09 | 42632042.87 | 63763438.80 | 0.163999E+09 | 69596925.31 |
Maximum of Months | 0.326917E+09 | 0.219248E+09 | 0.171469E+09 | 0.314160E+09 | 0.428751E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_3
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.320420E+09 | 0.219248E+09 | 0.101171E+09 | 0.248499E+09 | 0.428751E+09 |
February | 0.310244E+09 | 0.209629E+09 | 0.100615E+09 | 0.244348E+09 | 0.313306E+09 |
March | 0.298959E+09 | 0.157481E+09 | 0.141478E+09 | 0.234947E+09 | 0.248600E+09 |
April | 0.260528E+09 | 0.121793E+09 | 0.138735E+09 | 0.202319E+09 | 0.178570E+09 |
May | 0.223012E+09 | 60435776.82 | 0.162576E+09 | 0.163999E+09 | 0.115405E+09 |
June | 0.209524E+09 | 42632042.87 | 0.166892E+09 | 0.179246E+09 | 78635270.91 |
July | 0.229186E+09 | 57717198.46 | 0.171469E+09 | 0.204489E+09 | 69596925.31 |
August | 0.258228E+09 | 92583616.90 | 0.165644E+09 | 0.252524E+09 | 83888008.30 |
September | 0.302924E+09 | 0.159644E+09 | 0.143280E+09 | 0.304140E+09 | 0.133893E+09 |
October | 0.326917E+09 | 0.205140E+09 | 0.121778E+09 | 0.314160E+09 | 0.197285E+09 |
November | 0.238598E+09 | 0.149360E+09 | 89237204.53 | 0.197097E+09 | 0.277383E+09 |
December | 0.262824E+09 | 0.199060E+09 | 63763438.80 | 0.230855E+09 | 0.396166E+09 |
Annual Sum or Average | 0.324136E+10 | 0.167472E+10 | 0.156664E+10 | 0.277662E+10 | 0.252148E+10 |
Minimum of Months | 0.209524E+09 | 42632042.87 | 63763438.80 | 0.163999E+09 | 69596925.31 |
Maximum of Months | 0.326917E+09 | 0.219248E+09 | 0.171469E+09 | 0.314160E+09 | 0.428751E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_4
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.320420E+09 | 0.219248E+09 | 0.101171E+09 | 0.248499E+09 | 0.428751E+09 |
February | 0.310244E+09 | 0.209629E+09 | 0.100615E+09 | 0.244348E+09 | 0.313306E+09 |
March | 0.298959E+09 | 0.157481E+09 | 0.141478E+09 | 0.234947E+09 | 0.248600E+09 |
April | 0.260528E+09 | 0.121793E+09 | 0.138735E+09 | 0.202319E+09 | 0.178570E+09 |
May | 0.223012E+09 | 60435776.82 | 0.162576E+09 | 0.163999E+09 | 0.115405E+09 |
June | 0.209524E+09 | 42632042.87 | 0.166892E+09 | 0.179246E+09 | 78635270.91 |
July | 0.229186E+09 | 57717198.46 | 0.171469E+09 | 0.204489E+09 | 69596925.31 |
August | 0.258228E+09 | 92583616.90 | 0.165644E+09 | 0.252524E+09 | 83888008.30 |
September | 0.302924E+09 | 0.159644E+09 | 0.143280E+09 | 0.304140E+09 | 0.133893E+09 |
October | 0.326917E+09 | 0.205140E+09 | 0.121778E+09 | 0.314160E+09 | 0.197285E+09 |
November | 0.238598E+09 | 0.149360E+09 | 89237204.53 | 0.197097E+09 | 0.277383E+09 |
December | 0.262824E+09 | 0.199060E+09 | 63763438.80 | 0.230855E+09 | 0.396166E+09 |
Annual Sum or Average | 0.324136E+10 | 0.167472E+10 | 0.156664E+10 | 0.277662E+10 | 0.252148E+10 |
Minimum of Months | 0.209524E+09 | 42632042.87 | 63763438.80 | 0.163999E+09 | 69596925.31 |
Maximum of Months | 0.326917E+09 | 0.219248E+09 | 0.171469E+09 | 0.314160E+09 | 0.428751E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_DOOR_1
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.385768E+09 | 0.263963E+09 | 0.121805E+09 | 0.300471E+09 | 0.509807E+09 |
February | 0.373517E+09 | 0.252382E+09 | 0.121136E+09 | 0.295292E+09 | 0.372604E+09 |
March | 0.359930E+09 | 0.189599E+09 | 0.170332E+09 | 0.283762E+09 | 0.295733E+09 |
April | 0.313661E+09 | 0.146632E+09 | 0.167029E+09 | 0.243977E+09 | 0.212649E+09 |
May | 0.268494E+09 | 72761494.47 | 0.195733E+09 | 0.197739E+09 | 0.137774E+09 |
June | 0.252256E+09 | 51326735.82 | 0.200929E+09 | 0.215584E+09 | 94012081.33 |
July | 0.275928E+09 | 69488469.20 | 0.206439E+09 | 0.245903E+09 | 83344291.09 |
August | 0.310893E+09 | 0.111466E+09 | 0.199427E+09 | 0.303704E+09 | 0.100346E+09 |
September | 0.364704E+09 | 0.192202E+09 | 0.172502E+09 | 0.365965E+09 | 0.159969E+09 |
October | 0.393591E+09 | 0.246977E+09 | 0.146614E+09 | 0.378596E+09 | 0.235328E+09 |
November | 0.287259E+09 | 0.179822E+09 | 0.107437E+09 | 0.237903E+09 | 0.330038E+09 |
December | 0.316426E+09 | 0.239658E+09 | 76767824.34 | 0.278600E+09 | 0.471359E+09 |
Annual Sum or Average | 0.390243E+10 | 0.201628E+10 | 0.188615E+10 | 0.334750E+10 | 0.300296E+10 |
Minimum of Months | 0.252256E+09 | 51326735.82 | 76767824.34 | 0.197739E+09 | 83344291.09 |
Maximum of Months | 0.393591E+09 | 0.263963E+09 | 0.206439E+09 | 0.378596E+09 | 0.509807E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_DOOR_2
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.385768E+09 | 0.263963E+09 | 0.121805E+09 | 0.300471E+09 | 0.509807E+09 |
February | 0.373517E+09 | 0.252382E+09 | 0.121136E+09 | 0.295292E+09 | 0.372604E+09 |
March | 0.359930E+09 | 0.189599E+09 | 0.170332E+09 | 0.283762E+09 | 0.295733E+09 |
April | 0.313661E+09 | 0.146632E+09 | 0.167029E+09 | 0.243977E+09 | 0.212649E+09 |
May | 0.268494E+09 | 72761494.47 | 0.195733E+09 | 0.197739E+09 | 0.137774E+09 |
June | 0.252256E+09 | 51326735.82 | 0.200929E+09 | 0.215584E+09 | 94012081.33 |
July | 0.275928E+09 | 69488469.20 | 0.206439E+09 | 0.245903E+09 | 83344291.09 |
August | 0.310893E+09 | 0.111466E+09 | 0.199427E+09 | 0.303704E+09 | 0.100346E+09 |
September | 0.364704E+09 | 0.192202E+09 | 0.172502E+09 | 0.365965E+09 | 0.159969E+09 |
October | 0.393591E+09 | 0.246977E+09 | 0.146614E+09 | 0.378596E+09 | 0.235328E+09 |
November | 0.287259E+09 | 0.179822E+09 | 0.107437E+09 | 0.237903E+09 | 0.330038E+09 |
December | 0.316426E+09 | 0.239658E+09 | 76767824.34 | 0.278600E+09 | 0.471359E+09 |
Annual Sum or Average | 0.390243E+10 | 0.201628E+10 | 0.188615E+10 | 0.334750E+10 | 0.300296E+10 |
Minimum of Months | 0.252256E+09 | 51326735.82 | 76767824.34 | 0.197739E+09 | 83344291.09 |
Maximum of Months | 0.393591E+09 | 0.263963E+09 | 0.206439E+09 | 0.378596E+09 | 0.509807E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.320420E+09 | 0.219248E+09 | 0.101171E+09 | 0.245154E+09 | 0.441564E+09 |
February | 0.310244E+09 | 0.209629E+09 | 0.100615E+09 | 0.241020E+09 | 0.325511E+09 |
March | 0.298959E+09 | 0.157481E+09 | 0.141478E+09 | 0.231028E+09 | 0.262899E+09 |
April | 0.260528E+09 | 0.121793E+09 | 0.138735E+09 | 0.199395E+09 | 0.191337E+09 |
May | 0.223012E+09 | 60435776.82 | 0.162576E+09 | 0.161210E+09 | 0.121536E+09 |
June | 0.209524E+09 | 42632042.87 | 0.166892E+09 | 0.178035E+09 | 81559883.00 |
July | 0.229186E+09 | 57717198.46 | 0.171469E+09 | 0.203923E+09 | 70841934.35 |
August | 0.258228E+09 | 92583616.90 | 0.165644E+09 | 0.252158E+09 | 85202916.45 |
September | 0.302924E+09 | 0.159644E+09 | 0.143280E+09 | 0.303394E+09 | 0.137331E+09 |
October | 0.326917E+09 | 0.205140E+09 | 0.121778E+09 | 0.311387E+09 | 0.207221E+09 |
November | 0.238598E+09 | 0.149360E+09 | 89237204.53 | 0.194661E+09 | 0.289172E+09 |
December | 0.262824E+09 | 0.199060E+09 | 63763438.80 | 0.228325E+09 | 0.410134E+09 |
Annual Sum or Average | 0.324136E+10 | 0.167472E+10 | 0.156664E+10 | 0.274969E+10 | 0.262431E+10 |
Minimum of Months | 0.209524E+09 | 42632042.87 | 63763438.80 | 0.161210E+09 | 70841934.35 |
Maximum of Months | 0.326917E+09 | 0.219248E+09 | 0.171469E+09 | 0.311387E+09 | 0.441564E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.320420E+09 | 0.219248E+09 | 0.101171E+09 | 0.245154E+09 | 0.441564E+09 |
February | 0.310244E+09 | 0.209629E+09 | 0.100615E+09 | 0.241020E+09 | 0.325511E+09 |
March | 0.298959E+09 | 0.157481E+09 | 0.141478E+09 | 0.231028E+09 | 0.262899E+09 |
April | 0.260528E+09 | 0.121793E+09 | 0.138735E+09 | 0.199395E+09 | 0.191337E+09 |
May | 0.223012E+09 | 60435776.82 | 0.162576E+09 | 0.161210E+09 | 0.121536E+09 |
June | 0.209524E+09 | 42632042.87 | 0.166892E+09 | 0.178035E+09 | 81559883.00 |
July | 0.229186E+09 | 57717198.46 | 0.171469E+09 | 0.203923E+09 | 70841934.35 |
August | 0.258228E+09 | 92583616.90 | 0.165644E+09 | 0.252158E+09 | 85202916.45 |
September | 0.302924E+09 | 0.159644E+09 | 0.143280E+09 | 0.303394E+09 | 0.137331E+09 |
October | 0.326917E+09 | 0.205140E+09 | 0.121778E+09 | 0.311387E+09 | 0.207221E+09 |
November | 0.238598E+09 | 0.149360E+09 | 89237204.53 | 0.194661E+09 | 0.289172E+09 |
December | 0.262824E+09 | 0.199060E+09 | 63763438.80 | 0.228325E+09 | 0.410134E+09 |
Annual Sum or Average | 0.324136E+10 | 0.167472E+10 | 0.156664E+10 | 0.274969E+10 | 0.262431E+10 |
Minimum of Months | 0.209524E+09 | 42632042.87 | 63763438.80 | 0.161210E+09 | 70841934.35 |
Maximum of Months | 0.326917E+09 | 0.219248E+09 | 0.171469E+09 | 0.311387E+09 | 0.441564E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_DOOR
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.385768E+09 | 0.263963E+09 | 0.121805E+09 | 0.296475E+09 | 0.524983E+09 |
February | 0.373517E+09 | 0.252382E+09 | 0.121136E+09 | 0.291304E+09 | 0.387045E+09 |
March | 0.359930E+09 | 0.189599E+09 | 0.170332E+09 | 0.279052E+09 | 0.312629E+09 |
April | 0.313661E+09 | 0.146632E+09 | 0.167029E+09 | 0.240452E+09 | 0.227749E+09 |
May | 0.268494E+09 | 72761494.47 | 0.195733E+09 | 0.194389E+09 | 0.145014E+09 |
June | 0.252256E+09 | 51326735.82 | 0.200929E+09 | 0.214128E+09 | 97457022.41 |
July | 0.275928E+09 | 69488469.20 | 0.206439E+09 | 0.245229E+09 | 84799867.98 |
August | 0.310893E+09 | 0.111466E+09 | 0.199427E+09 | 0.303281E+09 | 0.101868E+09 |
September | 0.364704E+09 | 0.192202E+09 | 0.172502E+09 | 0.365091E+09 | 0.163988E+09 |
October | 0.393591E+09 | 0.246977E+09 | 0.146614E+09 | 0.375308E+09 | 0.246989E+09 |
November | 0.287259E+09 | 0.179822E+09 | 0.107437E+09 | 0.234991E+09 | 0.343908E+09 |
December | 0.316426E+09 | 0.239658E+09 | 76767824.34 | 0.275582E+09 | 0.487881E+09 |
Annual Sum or Average | 0.390243E+10 | 0.201628E+10 | 0.188615E+10 | 0.331528E+10 | 0.312431E+10 |
Minimum of Months | 0.252256E+09 | 51326735.82 | 76767824.34 | 0.194389E+09 | 84799867.98 |
Maximum of Months | 0.393591E+09 | 0.263963E+09 | 0.206439E+09 | 0.375308E+09 | 0.524983E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.320420E+09 | 0.219248E+09 | 0.101171E+09 | 0.246064E+09 | 0.427272E+09 |
February | 0.310244E+09 | 0.209629E+09 | 0.100615E+09 | 0.241955E+09 | 0.313622E+09 |
March | 0.298959E+09 | 0.157481E+09 | 0.141478E+09 | 0.232377E+09 | 0.251536E+09 |
April | 0.260528E+09 | 0.121793E+09 | 0.138735E+09 | 0.200566E+09 | 0.182178E+09 |
May | 0.223012E+09 | 60435776.82 | 0.162576E+09 | 0.163304E+09 | 0.117123E+09 |
June | 0.209524E+09 | 42632042.87 | 0.166892E+09 | 0.178239E+09 | 81854190.55 |
July | 0.229186E+09 | 57717198.46 | 0.171469E+09 | 0.203391E+09 | 74027167.92 |
August | 0.258228E+09 | 92583616.90 | 0.165644E+09 | 0.252104E+09 | 87731618.48 |
September | 0.302924E+09 | 0.159644E+09 | 0.143280E+09 | 0.304058E+09 | 0.135686E+09 |
October | 0.326917E+09 | 0.205140E+09 | 0.121778E+09 | 0.313818E+09 | 0.196309E+09 |
November | 0.238598E+09 | 0.149360E+09 | 89237204.53 | 0.196219E+09 | 0.276112E+09 |
December | 0.262824E+09 | 0.199060E+09 | 63763438.80 | 0.229133E+09 | 0.396813E+09 |
Annual Sum or Average | 0.324136E+10 | 0.167472E+10 | 0.156664E+10 | 0.276123E+10 | 0.254026E+10 |
Minimum of Months | 0.209524E+09 | 42632042.87 | 63763438.80 | 0.163304E+09 | 74027167.92 |
Maximum of Months | 0.326917E+09 | 0.219248E+09 | 0.171469E+09 | 0.313818E+09 | 0.427272E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.320420E+09 | 0.219248E+09 | 0.101171E+09 | 0.246064E+09 | 0.427272E+09 |
February | 0.310244E+09 | 0.209629E+09 | 0.100615E+09 | 0.241955E+09 | 0.313622E+09 |
March | 0.298959E+09 | 0.157481E+09 | 0.141478E+09 | 0.232377E+09 | 0.251536E+09 |
April | 0.260528E+09 | 0.121793E+09 | 0.138735E+09 | 0.200566E+09 | 0.182178E+09 |
May | 0.223012E+09 | 60435776.82 | 0.162576E+09 | 0.163304E+09 | 0.117123E+09 |
June | 0.209524E+09 | 42632042.87 | 0.166892E+09 | 0.178239E+09 | 81854190.55 |
July | 0.229186E+09 | 57717198.46 | 0.171469E+09 | 0.203391E+09 | 74027167.92 |
August | 0.258228E+09 | 92583616.90 | 0.165644E+09 | 0.252104E+09 | 87731618.48 |
September | 0.302924E+09 | 0.159644E+09 | 0.143280E+09 | 0.304058E+09 | 0.135686E+09 |
October | 0.326917E+09 | 0.205140E+09 | 0.121778E+09 | 0.313818E+09 | 0.196309E+09 |
November | 0.238598E+09 | 0.149360E+09 | 89237204.53 | 0.196219E+09 | 0.276112E+09 |
December | 0.262824E+09 | 0.199060E+09 | 63763438.80 | 0.229133E+09 | 0.396813E+09 |
Annual Sum or Average | 0.324136E+10 | 0.167472E+10 | 0.156664E+10 | 0.276123E+10 | 0.254026E+10 |
Minimum of Months | 0.209524E+09 | 42632042.87 | 63763438.80 | 0.163304E+09 | 74027167.92 |
Maximum of Months | 0.326917E+09 | 0.219248E+09 | 0.171469E+09 | 0.313818E+09 | 0.427272E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_DOOR
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.383660E+09 | 0.262521E+09 | 0.121139E+09 | 0.295976E+09 | 0.505146E+09 |
February | 0.371476E+09 | 0.251003E+09 | 0.120474E+09 | 0.290868E+09 | 0.370835E+09 |
March | 0.357964E+09 | 0.188563E+09 | 0.169401E+09 | 0.279173E+09 | 0.297452E+09 |
April | 0.311947E+09 | 0.145831E+09 | 0.166116E+09 | 0.240570E+09 | 0.215636E+09 |
May | 0.267027E+09 | 72363890.67 | 0.194663E+09 | 0.195855E+09 | 0.138928E+09 |
June | 0.250877E+09 | 51046261.85 | 0.199831E+09 | 0.213250E+09 | 97190423.53 |
July | 0.274420E+09 | 69108750.79 | 0.205311E+09 | 0.243302E+09 | 88003884.39 |
August | 0.309194E+09 | 0.110857E+09 | 0.198337E+09 | 0.301594E+09 | 0.104203E+09 |
September | 0.362712E+09 | 0.191152E+09 | 0.171559E+09 | 0.363920E+09 | 0.161066E+09 |
October | 0.391441E+09 | 0.245628E+09 | 0.145813E+09 | 0.376185E+09 | 0.232708E+09 |
November | 0.285689E+09 | 0.178839E+09 | 0.106850E+09 | 0.235601E+09 | 0.326552E+09 |
December | 0.314697E+09 | 0.238348E+09 | 76348328.03 | 0.275070E+09 | 0.469392E+09 |
Annual Sum or Average | 0.388110E+10 | 0.200526E+10 | 0.187584E+10 | 0.331136E+10 | 0.300711E+10 |
Minimum of Months | 0.250877E+09 | 51046261.85 | 76348328.03 | 0.195855E+09 | 88003884.39 |
Maximum of Months | 0.391441E+09 | 0.262521E+09 | 0.205311E+09 | 0.376185E+09 | 0.505146E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.320420E+09 | 0.219248E+09 | 0.101171E+09 | 0.246485E+09 | 0.423345E+09 |
February | 0.310244E+09 | 0.209629E+09 | 0.100615E+09 | 0.242416E+09 | 0.310125E+09 |
March | 0.298959E+09 | 0.157481E+09 | 0.141478E+09 | 0.233089E+09 | 0.247613E+09 |
April | 0.260528E+09 | 0.121793E+09 | 0.138735E+09 | 0.201296E+09 | 0.178661E+09 |
May | 0.223012E+09 | 60435776.82 | 0.162576E+09 | 0.164622E+09 | 0.114287E+09 |
June | 0.209524E+09 | 42632042.87 | 0.166892E+09 | 0.178772E+09 | 80687901.89 |
July | 0.229186E+09 | 57717198.46 | 0.171469E+09 | 0.203629E+09 | 73593840.86 |
August | 0.258228E+09 | 92583616.90 | 0.165644E+09 | 0.252355E+09 | 87148022.23 |
September | 0.302924E+09 | 0.159644E+09 | 0.143280E+09 | 0.304541E+09 | 0.133980E+09 |
October | 0.326917E+09 | 0.205140E+09 | 0.121778E+09 | 0.314902E+09 | 0.192329E+09 |
November | 0.238598E+09 | 0.149360E+09 | 89237204.53 | 0.196958E+09 | 0.271773E+09 |
December | 0.262824E+09 | 0.199060E+09 | 63763438.80 | 0.229550E+09 | 0.392750E+09 |
Annual Sum or Average | 0.324136E+10 | 0.167472E+10 | 0.156664E+10 | 0.276861E+10 | 0.250629E+10 |
Minimum of Months | 0.209524E+09 | 42632042.87 | 63763438.80 | 0.164622E+09 | 73593840.86 |
Maximum of Months | 0.326917E+09 | 0.219248E+09 | 0.171469E+09 | 0.314902E+09 | 0.423345E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.320420E+09 | 0.219248E+09 | 0.101171E+09 | 0.246485E+09 | 0.423345E+09 |
February | 0.310244E+09 | 0.209629E+09 | 0.100615E+09 | 0.242416E+09 | 0.310125E+09 |
March | 0.298959E+09 | 0.157481E+09 | 0.141478E+09 | 0.233089E+09 | 0.247613E+09 |
April | 0.260528E+09 | 0.121793E+09 | 0.138735E+09 | 0.201296E+09 | 0.178661E+09 |
May | 0.223012E+09 | 60435776.82 | 0.162576E+09 | 0.164622E+09 | 0.114287E+09 |
June | 0.209524E+09 | 42632042.87 | 0.166892E+09 | 0.178772E+09 | 80687901.89 |
July | 0.229186E+09 | 57717198.46 | 0.171469E+09 | 0.203629E+09 | 73593840.86 |
August | 0.258228E+09 | 92583616.90 | 0.165644E+09 | 0.252355E+09 | 87148022.23 |
September | 0.302924E+09 | 0.159644E+09 | 0.143280E+09 | 0.304541E+09 | 0.133980E+09 |
October | 0.326917E+09 | 0.205140E+09 | 0.121778E+09 | 0.314902E+09 | 0.192329E+09 |
November | 0.238598E+09 | 0.149360E+09 | 89237204.53 | 0.196958E+09 | 0.271773E+09 |
December | 0.262824E+09 | 0.199060E+09 | 63763438.80 | 0.229550E+09 | 0.392750E+09 |
Annual Sum or Average | 0.324136E+10 | 0.167472E+10 | 0.156664E+10 | 0.276861E+10 | 0.250629E+10 |
Minimum of Months | 0.209524E+09 | 42632042.87 | 63763438.80 | 0.164622E+09 | 73593840.86 |
Maximum of Months | 0.326917E+09 | 0.219248E+09 | 0.171469E+09 | 0.314902E+09 | 0.423345E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_DOOR
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.383660E+09 | 0.262521E+09 | 0.121139E+09 | 0.296489E+09 | 0.500458E+09 |
February | 0.371476E+09 | 0.251003E+09 | 0.120474E+09 | 0.291432E+09 | 0.366668E+09 |
March | 0.357964E+09 | 0.188563E+09 | 0.169401E+09 | 0.280038E+09 | 0.292788E+09 |
April | 0.311947E+09 | 0.145831E+09 | 0.166116E+09 | 0.241451E+09 | 0.211457E+09 |
May | 0.267027E+09 | 72363890.67 | 0.194663E+09 | 0.197436E+09 | 0.135564E+09 |
June | 0.250877E+09 | 51046261.85 | 0.199831E+09 | 0.213891E+09 | 95806328.99 |
July | 0.274420E+09 | 69108750.79 | 0.205311E+09 | 0.243590E+09 | 87489463.81 |
August | 0.309194E+09 | 0.110857E+09 | 0.198337E+09 | 0.301897E+09 | 0.103511E+09 |
September | 0.362712E+09 | 0.191152E+09 | 0.171559E+09 | 0.364502E+09 | 0.159041E+09 |
October | 0.391441E+09 | 0.245628E+09 | 0.145813E+09 | 0.377489E+09 | 0.227981E+09 |
November | 0.285689E+09 | 0.178839E+09 | 0.106850E+09 | 0.236498E+09 | 0.321393E+09 |
December | 0.314697E+09 | 0.238348E+09 | 76348328.03 | 0.275577E+09 | 0.464543E+09 |
Annual Sum or Average | 0.388110E+10 | 0.200526E+10 | 0.187584E+10 | 0.332029E+10 | 0.296670E+10 |
Minimum of Months | 0.250877E+09 | 51046261.85 | 76348328.03 | 0.197436E+09 | 87489463.81 |
Maximum of Months | 0.391441E+09 | 0.262521E+09 | 0.205311E+09 | 0.377489E+09 | 0.500458E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.320420E+09 | 0.219248E+09 | 0.101171E+09 | 0.246832E+09 | 0.421419E+09 |
February | 0.310244E+09 | 0.209629E+09 | 0.100615E+09 | 0.242803E+09 | 0.308245E+09 |
March | 0.298959E+09 | 0.157481E+09 | 0.141478E+09 | 0.233650E+09 | 0.245354E+09 |
April | 0.260528E+09 | 0.121793E+09 | 0.138735E+09 | 0.201867E+09 | 0.176540E+09 |
May | 0.223012E+09 | 60435776.82 | 0.162576E+09 | 0.165713E+09 | 0.112281E+09 |
June | 0.209524E+09 | 42632042.87 | 0.166892E+09 | 0.179287E+09 | 79549466.09 |
July | 0.229186E+09 | 57717198.46 | 0.171469E+09 | 0.203950E+09 | 72789695.03 |
August | 0.258228E+09 | 92583616.90 | 0.165644E+09 | 0.252641E+09 | 86318069.06 |
September | 0.302924E+09 | 0.159644E+09 | 0.143280E+09 | 0.304919E+09 | 0.132747E+09 |
October | 0.326917E+09 | 0.205140E+09 | 0.121778E+09 | 0.315600E+09 | 0.190263E+09 |
November | 0.238598E+09 | 0.149360E+09 | 89237204.53 | 0.197478E+09 | 0.269419E+09 |
December | 0.262824E+09 | 0.199060E+09 | 63763438.80 | 0.229902E+09 | 0.390449E+09 |
Annual Sum or Average | 0.324136E+10 | 0.167472E+10 | 0.156664E+10 | 0.277464E+10 | 0.248537E+10 |
Minimum of Months | 0.209524E+09 | 42632042.87 | 63763438.80 | 0.165713E+09 | 72789695.03 |
Maximum of Months | 0.326917E+09 | 0.219248E+09 | 0.171469E+09 | 0.315600E+09 | 0.421419E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.320420E+09 | 0.219248E+09 | 0.101171E+09 | 0.246832E+09 | 0.421419E+09 |
February | 0.310244E+09 | 0.209629E+09 | 0.100615E+09 | 0.242803E+09 | 0.308245E+09 |
March | 0.298959E+09 | 0.157481E+09 | 0.141478E+09 | 0.233650E+09 | 0.245354E+09 |
April | 0.260528E+09 | 0.121793E+09 | 0.138735E+09 | 0.201867E+09 | 0.176540E+09 |
May | 0.223012E+09 | 60435776.82 | 0.162576E+09 | 0.165713E+09 | 0.112281E+09 |
June | 0.209524E+09 | 42632042.87 | 0.166892E+09 | 0.179287E+09 | 79549466.09 |
July | 0.229186E+09 | 57717198.46 | 0.171469E+09 | 0.203950E+09 | 72789695.03 |
August | 0.258228E+09 | 92583616.90 | 0.165644E+09 | 0.252641E+09 | 86318069.06 |
September | 0.302924E+09 | 0.159644E+09 | 0.143280E+09 | 0.304919E+09 | 0.132747E+09 |
October | 0.326917E+09 | 0.205140E+09 | 0.121778E+09 | 0.315600E+09 | 0.190263E+09 |
November | 0.238598E+09 | 0.149360E+09 | 89237204.53 | 0.197478E+09 | 0.269419E+09 |
December | 0.262824E+09 | 0.199060E+09 | 63763438.80 | 0.229902E+09 | 0.390449E+09 |
Annual Sum or Average | 0.324136E+10 | 0.167472E+10 | 0.156664E+10 | 0.277464E+10 | 0.248537E+10 |
Minimum of Months | 0.209524E+09 | 42632042.87 | 63763438.80 | 0.165713E+09 | 72789695.03 |
Maximum of Months | 0.326917E+09 | 0.219248E+09 | 0.171469E+09 | 0.315600E+09 | 0.421419E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_DOOR
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.383660E+09 | 0.262521E+09 | 0.121139E+09 | 0.296912E+09 | 0.498158E+09 |
February | 0.371476E+09 | 0.251003E+09 | 0.120474E+09 | 0.291905E+09 | 0.364428E+09 |
March | 0.357964E+09 | 0.188563E+09 | 0.169401E+09 | 0.280722E+09 | 0.290107E+09 |
April | 0.311947E+09 | 0.145831E+09 | 0.166116E+09 | 0.242142E+09 | 0.208939E+09 |
May | 0.267027E+09 | 72363890.67 | 0.194663E+09 | 0.198743E+09 | 0.133191E+09 |
June | 0.250877E+09 | 51046261.85 | 0.199831E+09 | 0.214509E+09 | 94459937.17 |
July | 0.274420E+09 | 69108750.79 | 0.205311E+09 | 0.243976E+09 | 86541304.36 |
August | 0.309194E+09 | 0.110857E+09 | 0.198337E+09 | 0.302242E+09 | 0.102532E+09 |
September | 0.362712E+09 | 0.191152E+09 | 0.171559E+09 | 0.364957E+09 | 0.157583E+09 |
October | 0.391441E+09 | 0.245628E+09 | 0.145813E+09 | 0.378331E+09 | 0.225534E+09 |
November | 0.285689E+09 | 0.178839E+09 | 0.106850E+09 | 0.237130E+09 | 0.318597E+09 |
December | 0.314697E+09 | 0.238348E+09 | 76348328.03 | 0.276006E+09 | 0.461799E+09 |
Annual Sum or Average | 0.388110E+10 | 0.200526E+10 | 0.187584E+10 | 0.332758E+10 | 0.294187E+10 |
Minimum of Months | 0.250877E+09 | 51046261.85 | 76348328.03 | 0.198743E+09 | 86541304.36 |
Maximum of Months | 0.391441E+09 | 0.262521E+09 | 0.205311E+09 | 0.378331E+09 | 0.498158E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.320420E+09 | 0.219248E+09 | 0.101171E+09 | 0.249470E+09 | 0.411993E+09 |
February | 0.310244E+09 | 0.209629E+09 | 0.100615E+09 | 0.245434E+09 | 0.300258E+09 |
March | 0.298959E+09 | 0.157481E+09 | 0.141478E+09 | 0.236351E+09 | 0.237233E+09 |
April | 0.260528E+09 | 0.121793E+09 | 0.138735E+09 | 0.203633E+09 | 0.170431E+09 |
May | 0.223012E+09 | 60435776.82 | 0.162576E+09 | 0.167523E+09 | 0.108256E+09 |
June | 0.209524E+09 | 42632042.87 | 0.166892E+09 | 0.179807E+09 | 76694851.75 |
July | 0.229186E+09 | 57717198.46 | 0.171469E+09 | 0.204105E+09 | 70418320.54 |
August | 0.258228E+09 | 92583616.90 | 0.165644E+09 | 0.252869E+09 | 83902282.32 |
September | 0.302924E+09 | 0.159644E+09 | 0.143280E+09 | 0.305444E+09 | 0.130125E+09 |
October | 0.326917E+09 | 0.205140E+09 | 0.121778E+09 | 0.317933E+09 | 0.185602E+09 |
November | 0.238598E+09 | 0.149360E+09 | 89237204.53 | 0.199669E+09 | 0.261816E+09 |
December | 0.262824E+09 | 0.199060E+09 | 63763438.80 | 0.232198E+09 | 0.380601E+09 |
Annual Sum or Average | 0.324136E+10 | 0.167472E+10 | 0.156664E+10 | 0.279444E+10 | 0.241733E+10 |
Minimum of Months | 0.209524E+09 | 42632042.87 | 63763438.80 | 0.167523E+09 | 70418320.54 |
Maximum of Months | 0.326917E+09 | 0.219248E+09 | 0.171469E+09 | 0.317933E+09 | 0.411993E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.320420E+09 | 0.219248E+09 | 0.101171E+09 | 0.249470E+09 | 0.411993E+09 |
February | 0.310244E+09 | 0.209629E+09 | 0.100615E+09 | 0.245434E+09 | 0.300258E+09 |
March | 0.298959E+09 | 0.157481E+09 | 0.141478E+09 | 0.236351E+09 | 0.237233E+09 |
April | 0.260528E+09 | 0.121793E+09 | 0.138735E+09 | 0.203633E+09 | 0.170431E+09 |
May | 0.223012E+09 | 60435776.82 | 0.162576E+09 | 0.167523E+09 | 0.108256E+09 |
June | 0.209524E+09 | 42632042.87 | 0.166892E+09 | 0.179807E+09 | 76694851.75 |
July | 0.229186E+09 | 57717198.46 | 0.171469E+09 | 0.204105E+09 | 70418320.54 |
August | 0.258228E+09 | 92583616.90 | 0.165644E+09 | 0.252869E+09 | 83902282.32 |
September | 0.302924E+09 | 0.159644E+09 | 0.143280E+09 | 0.305444E+09 | 0.130125E+09 |
October | 0.326917E+09 | 0.205140E+09 | 0.121778E+09 | 0.317933E+09 | 0.185602E+09 |
November | 0.238598E+09 | 0.149360E+09 | 89237204.53 | 0.199669E+09 | 0.261816E+09 |
December | 0.262824E+09 | 0.199060E+09 | 63763438.80 | 0.232198E+09 | 0.380601E+09 |
Annual Sum or Average | 0.324136E+10 | 0.167472E+10 | 0.156664E+10 | 0.279444E+10 | 0.241733E+10 |
Minimum of Months | 0.209524E+09 | 42632042.87 | 63763438.80 | 0.167523E+09 | 70418320.54 |
Maximum of Months | 0.326917E+09 | 0.219248E+09 | 0.171469E+09 | 0.317933E+09 | 0.411993E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_3
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.320420E+09 | 0.219248E+09 | 0.101171E+09 | 0.249470E+09 | 0.411993E+09 |
February | 0.310244E+09 | 0.209629E+09 | 0.100615E+09 | 0.245434E+09 | 0.300258E+09 |
March | 0.298959E+09 | 0.157481E+09 | 0.141478E+09 | 0.236351E+09 | 0.237233E+09 |
April | 0.260528E+09 | 0.121793E+09 | 0.138735E+09 | 0.203633E+09 | 0.170431E+09 |
May | 0.223012E+09 | 60435776.82 | 0.162576E+09 | 0.167523E+09 | 0.108256E+09 |
June | 0.209524E+09 | 42632042.87 | 0.166892E+09 | 0.179807E+09 | 76694851.75 |
July | 0.229186E+09 | 57717198.46 | 0.171469E+09 | 0.204105E+09 | 70418320.54 |
August | 0.258228E+09 | 92583616.90 | 0.165644E+09 | 0.252869E+09 | 83902282.32 |
September | 0.302924E+09 | 0.159644E+09 | 0.143280E+09 | 0.305444E+09 | 0.130125E+09 |
October | 0.326917E+09 | 0.205140E+09 | 0.121778E+09 | 0.317933E+09 | 0.185602E+09 |
November | 0.238598E+09 | 0.149360E+09 | 89237204.53 | 0.199669E+09 | 0.261816E+09 |
December | 0.262824E+09 | 0.199060E+09 | 63763438.80 | 0.232198E+09 | 0.380601E+09 |
Annual Sum or Average | 0.324136E+10 | 0.167472E+10 | 0.156664E+10 | 0.279444E+10 | 0.241733E+10 |
Minimum of Months | 0.209524E+09 | 42632042.87 | 63763438.80 | 0.167523E+09 | 70418320.54 |
Maximum of Months | 0.326917E+09 | 0.219248E+09 | 0.171469E+09 | 0.317933E+09 | 0.411993E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_4
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.320420E+09 | 0.219248E+09 | 0.101171E+09 | 0.249470E+09 | 0.411993E+09 |
February | 0.310244E+09 | 0.209629E+09 | 0.100615E+09 | 0.245434E+09 | 0.300258E+09 |
March | 0.298959E+09 | 0.157481E+09 | 0.141478E+09 | 0.236351E+09 | 0.237233E+09 |
April | 0.260528E+09 | 0.121793E+09 | 0.138735E+09 | 0.203633E+09 | 0.170431E+09 |
May | 0.223012E+09 | 60435776.82 | 0.162576E+09 | 0.167523E+09 | 0.108256E+09 |
June | 0.209524E+09 | 42632042.87 | 0.166892E+09 | 0.179807E+09 | 76694851.75 |
July | 0.229186E+09 | 57717198.46 | 0.171469E+09 | 0.204105E+09 | 70418320.54 |
August | 0.258228E+09 | 92583616.90 | 0.165644E+09 | 0.252869E+09 | 83902282.32 |
September | 0.302924E+09 | 0.159644E+09 | 0.143280E+09 | 0.305444E+09 | 0.130125E+09 |
October | 0.326917E+09 | 0.205140E+09 | 0.121778E+09 | 0.317933E+09 | 0.185602E+09 |
November | 0.238598E+09 | 0.149360E+09 | 89237204.53 | 0.199669E+09 | 0.261816E+09 |
December | 0.262824E+09 | 0.199060E+09 | 63763438.80 | 0.232198E+09 | 0.380601E+09 |
Annual Sum or Average | 0.324136E+10 | 0.167472E+10 | 0.156664E+10 | 0.279444E+10 | 0.241733E+10 |
Minimum of Months | 0.209524E+09 | 42632042.87 | 63763438.80 | 0.167523E+09 | 70418320.54 |
Maximum of Months | 0.326917E+09 | 0.219248E+09 | 0.171469E+09 | 0.317933E+09 | 0.411993E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_DOOR_1
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.383660E+09 | 0.262521E+09 | 0.121139E+09 | 0.300046E+09 | 0.487129E+09 |
February | 0.371476E+09 | 0.251003E+09 | 0.120474E+09 | 0.295026E+09 | 0.355071E+09 |
March | 0.357964E+09 | 0.188563E+09 | 0.169401E+09 | 0.283947E+09 | 0.280590E+09 |
April | 0.311947E+09 | 0.145831E+09 | 0.166116E+09 | 0.244262E+09 | 0.201756E+09 |
May | 0.267027E+09 | 72363890.67 | 0.194663E+09 | 0.200917E+09 | 0.128446E+09 |
June | 0.250877E+09 | 51046261.85 | 0.199831E+09 | 0.215159E+09 | 91097075.80 |
July | 0.274420E+09 | 69108750.79 | 0.205311E+09 | 0.244191E+09 | 83743623.89 |
August | 0.309194E+09 | 0.110857E+09 | 0.198337E+09 | 0.302531E+09 | 99689334.24 |
September | 0.362712E+09 | 0.191152E+09 | 0.171559E+09 | 0.365590E+09 | 0.154494E+09 |
October | 0.391441E+09 | 0.245628E+09 | 0.145813E+09 | 0.381093E+09 | 0.220065E+09 |
November | 0.285689E+09 | 0.178839E+09 | 0.106850E+09 | 0.239740E+09 | 0.309690E+09 |
December | 0.314697E+09 | 0.238348E+09 | 76348328.03 | 0.278727E+09 | 0.450245E+09 |
Annual Sum or Average | 0.388110E+10 | 0.200526E+10 | 0.187584E+10 | 0.335123E+10 | 0.286202E+10 |
Minimum of Months | 0.250877E+09 | 51046261.85 | 76348328.03 | 0.200917E+09 | 83743623.89 |
Maximum of Months | 0.391441E+09 | 0.262521E+09 | 0.205311E+09 | 0.381093E+09 | 0.487129E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_DOOR_2
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.383660E+09 | 0.262521E+09 | 0.121139E+09 | 0.300046E+09 | 0.487129E+09 |
February | 0.371476E+09 | 0.251003E+09 | 0.120474E+09 | 0.295026E+09 | 0.355071E+09 |
March | 0.357964E+09 | 0.188563E+09 | 0.169401E+09 | 0.283947E+09 | 0.280590E+09 |
April | 0.311947E+09 | 0.145831E+09 | 0.166116E+09 | 0.244262E+09 | 0.201756E+09 |
May | 0.267027E+09 | 72363890.67 | 0.194663E+09 | 0.200917E+09 | 0.128446E+09 |
June | 0.250877E+09 | 51046261.85 | 0.199831E+09 | 0.215159E+09 | 91097075.80 |
July | 0.274420E+09 | 69108750.79 | 0.205311E+09 | 0.244191E+09 | 83743623.89 |
August | 0.309194E+09 | 0.110857E+09 | 0.198337E+09 | 0.302531E+09 | 99689334.24 |
September | 0.362712E+09 | 0.191152E+09 | 0.171559E+09 | 0.365590E+09 | 0.154494E+09 |
October | 0.391441E+09 | 0.245628E+09 | 0.145813E+09 | 0.381093E+09 | 0.220065E+09 |
November | 0.285689E+09 | 0.178839E+09 | 0.106850E+09 | 0.239740E+09 | 0.309690E+09 |
December | 0.314697E+09 | 0.238348E+09 | 76348328.03 | 0.278727E+09 | 0.450245E+09 |
Annual Sum or Average | 0.388110E+10 | 0.200526E+10 | 0.187584E+10 | 0.335123E+10 | 0.286202E+10 |
Minimum of Months | 0.250877E+09 | 51046261.85 | 76348328.03 | 0.200917E+09 | 83743623.89 |
Maximum of Months | 0.391441E+09 | 0.262521E+09 | 0.205311E+09 | 0.381093E+09 | 0.487129E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.320420E+09 | 0.219248E+09 | 0.101171E+09 | 0.247985E+09 | 0.415407E+09 |
February | 0.310244E+09 | 0.209629E+09 | 0.100615E+09 | 0.244135E+09 | 0.302757E+09 |
March | 0.298959E+09 | 0.157481E+09 | 0.141478E+09 | 0.235248E+09 | 0.239131E+09 |
April | 0.260528E+09 | 0.121793E+09 | 0.138735E+09 | 0.203401E+09 | 0.171233E+09 |
May | 0.223012E+09 | 60435776.82 | 0.162576E+09 | 0.168395E+09 | 0.107662E+09 |
June | 0.209524E+09 | 42632042.87 | 0.166892E+09 | 0.180606E+09 | 75987154.16 |
July | 0.229186E+09 | 57717198.46 | 0.171469E+09 | 0.204789E+09 | 69668679.23 |
August | 0.258228E+09 | 92583616.90 | 0.165644E+09 | 0.253388E+09 | 83230715.36 |
September | 0.302924E+09 | 0.159644E+09 | 0.143280E+09 | 0.305811E+09 | 0.129543E+09 |
October | 0.326917E+09 | 0.205140E+09 | 0.121778E+09 | 0.317265E+09 | 0.185978E+09 |
November | 0.238598E+09 | 0.149360E+09 | 89237204.53 | 0.198853E+09 | 0.263759E+09 |
December | 0.262824E+09 | 0.199060E+09 | 63763438.80 | 0.231178E+09 | 0.383873E+09 |
Annual Sum or Average | 0.324136E+10 | 0.167472E+10 | 0.156664E+10 | 0.279105E+10 | 0.242823E+10 |
Minimum of Months | 0.209524E+09 | 42632042.87 | 63763438.80 | 0.168395E+09 | 69668679.23 |
Maximum of Months | 0.326917E+09 | 0.219248E+09 | 0.171469E+09 | 0.317265E+09 | 0.415407E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.320420E+09 | 0.219248E+09 | 0.101171E+09 | 0.247985E+09 | 0.415407E+09 |
February | 0.310244E+09 | 0.209629E+09 | 0.100615E+09 | 0.244135E+09 | 0.302757E+09 |
March | 0.298959E+09 | 0.157481E+09 | 0.141478E+09 | 0.235248E+09 | 0.239131E+09 |
April | 0.260528E+09 | 0.121793E+09 | 0.138735E+09 | 0.203401E+09 | 0.171233E+09 |
May | 0.223012E+09 | 60435776.82 | 0.162576E+09 | 0.168395E+09 | 0.107662E+09 |
June | 0.209524E+09 | 42632042.87 | 0.166892E+09 | 0.180606E+09 | 75987154.16 |
July | 0.229186E+09 | 57717198.46 | 0.171469E+09 | 0.204789E+09 | 69668679.23 |
August | 0.258228E+09 | 92583616.90 | 0.165644E+09 | 0.253388E+09 | 83230715.36 |
September | 0.302924E+09 | 0.159644E+09 | 0.143280E+09 | 0.305811E+09 | 0.129543E+09 |
October | 0.326917E+09 | 0.205140E+09 | 0.121778E+09 | 0.317265E+09 | 0.185978E+09 |
November | 0.238598E+09 | 0.149360E+09 | 89237204.53 | 0.198853E+09 | 0.263759E+09 |
December | 0.262824E+09 | 0.199060E+09 | 63763438.80 | 0.231178E+09 | 0.383873E+09 |
Annual Sum or Average | 0.324136E+10 | 0.167472E+10 | 0.156664E+10 | 0.279105E+10 | 0.242823E+10 |
Minimum of Months | 0.209524E+09 | 42632042.87 | 63763438.80 | 0.168395E+09 | 69668679.23 |
Maximum of Months | 0.326917E+09 | 0.219248E+09 | 0.171469E+09 | 0.317265E+09 | 0.415407E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_DOOR
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.383660E+09 | 0.262521E+09 | 0.121139E+09 | 0.298336E+09 | 0.491035E+09 |
February | 0.371476E+09 | 0.251003E+09 | 0.120474E+09 | 0.293535E+09 | 0.357923E+09 |
March | 0.357964E+09 | 0.188563E+09 | 0.169401E+09 | 0.282683E+09 | 0.282738E+09 |
April | 0.311947E+09 | 0.145831E+09 | 0.166116E+09 | 0.244007E+09 | 0.202639E+09 |
May | 0.267027E+09 | 72363890.67 | 0.194663E+09 | 0.201969E+09 | 0.127708E+09 |
June | 0.250877E+09 | 51046261.85 | 0.199831E+09 | 0.216119E+09 | 90238679.17 |
July | 0.274420E+09 | 69108750.79 | 0.205311E+09 | 0.245018E+09 | 82843212.75 |
August | 0.309194E+09 | 0.110857E+09 | 0.198337E+09 | 0.303170E+09 | 98873095.86 |
September | 0.362712E+09 | 0.191152E+09 | 0.171559E+09 | 0.366053E+09 | 0.153773E+09 |
October | 0.391441E+09 | 0.245628E+09 | 0.145813E+09 | 0.380353E+09 | 0.220449E+09 |
November | 0.285689E+09 | 0.178839E+09 | 0.106850E+09 | 0.238811E+09 | 0.311883E+09 |
December | 0.314697E+09 | 0.238348E+09 | 76348328.03 | 0.277557E+09 | 0.453990E+09 |
Annual Sum or Average | 0.388110E+10 | 0.200526E+10 | 0.187584E+10 | 0.334761E+10 | 0.287409E+10 |
Minimum of Months | 0.250877E+09 | 51046261.85 | 76348328.03 | 0.201969E+09 | 82843212.75 |
Maximum of Months | 0.391441E+09 | 0.262521E+09 | 0.205311E+09 | 0.380353E+09 | 0.491035E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.320420E+09 | 0.219248E+09 | 0.101171E+09 | 0.248034E+09 | 0.415165E+09 |
February | 0.310244E+09 | 0.209629E+09 | 0.100615E+09 | 0.244217E+09 | 0.302329E+09 |
March | 0.298959E+09 | 0.157481E+09 | 0.141478E+09 | 0.235453E+09 | 0.238412E+09 |
April | 0.260528E+09 | 0.121793E+09 | 0.138735E+09 | 0.203730E+09 | 0.170213E+09 |
May | 0.223012E+09 | 60435776.82 | 0.162576E+09 | 0.169362E+09 | 0.106170E+09 |
June | 0.209524E+09 | 42632042.87 | 0.166892E+09 | 0.181079E+09 | 75255481.00 |
July | 0.229186E+09 | 57717198.46 | 0.171469E+09 | 0.205113E+09 | 69200999.63 |
August | 0.258228E+09 | 92583616.90 | 0.165644E+09 | 0.253667E+09 | 82758206.32 |
September | 0.302924E+09 | 0.159644E+09 | 0.143280E+09 | 0.306132E+09 | 0.128789E+09 |
October | 0.326917E+09 | 0.205140E+09 | 0.121778E+09 | 0.317577E+09 | 0.185140E+09 |
November | 0.238598E+09 | 0.149360E+09 | 89237204.53 | 0.199026E+09 | 0.263080E+09 |
December | 0.262824E+09 | 0.199060E+09 | 63763438.80 | 0.231258E+09 | 0.383425E+09 |
Annual Sum or Average | 0.324136E+10 | 0.167472E+10 | 0.156664E+10 | 0.279465E+10 | 0.241994E+10 |
Minimum of Months | 0.209524E+09 | 42632042.87 | 63763438.80 | 0.169362E+09 | 69200999.63 |
Maximum of Months | 0.326917E+09 | 0.219248E+09 | 0.171469E+09 | 0.317577E+09 | 0.415165E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.320420E+09 | 0.219248E+09 | 0.101171E+09 | 0.248034E+09 | 0.415165E+09 |
February | 0.310244E+09 | 0.209629E+09 | 0.100615E+09 | 0.244217E+09 | 0.302329E+09 |
March | 0.298959E+09 | 0.157481E+09 | 0.141478E+09 | 0.235453E+09 | 0.238412E+09 |
April | 0.260528E+09 | 0.121793E+09 | 0.138735E+09 | 0.203730E+09 | 0.170213E+09 |
May | 0.223012E+09 | 60435776.82 | 0.162576E+09 | 0.169362E+09 | 0.106170E+09 |
June | 0.209524E+09 | 42632042.87 | 0.166892E+09 | 0.181079E+09 | 75255481.00 |
July | 0.229186E+09 | 57717198.46 | 0.171469E+09 | 0.205113E+09 | 69200999.63 |
August | 0.258228E+09 | 92583616.90 | 0.165644E+09 | 0.253667E+09 | 82758206.32 |
September | 0.302924E+09 | 0.159644E+09 | 0.143280E+09 | 0.306132E+09 | 0.128789E+09 |
October | 0.326917E+09 | 0.205140E+09 | 0.121778E+09 | 0.317577E+09 | 0.185140E+09 |
November | 0.238598E+09 | 0.149360E+09 | 89237204.53 | 0.199026E+09 | 0.263080E+09 |
December | 0.262824E+09 | 0.199060E+09 | 63763438.80 | 0.231258E+09 | 0.383425E+09 |
Annual Sum or Average | 0.324136E+10 | 0.167472E+10 | 0.156664E+10 | 0.279465E+10 | 0.241994E+10 |
Minimum of Months | 0.209524E+09 | 42632042.87 | 63763438.80 | 0.169362E+09 | 69200999.63 |
Maximum of Months | 0.326917E+09 | 0.219248E+09 | 0.171469E+09 | 0.317577E+09 | 0.415165E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_DOOR
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.383660E+09 | 0.262521E+09 | 0.121139E+09 | 0.298396E+09 | 0.490743E+09 |
February | 0.371476E+09 | 0.251003E+09 | 0.120474E+09 | 0.293635E+09 | 0.357413E+09 |
March | 0.357964E+09 | 0.188563E+09 | 0.169401E+09 | 0.282932E+09 | 0.281884E+09 |
April | 0.311947E+09 | 0.145831E+09 | 0.166116E+09 | 0.244405E+09 | 0.201426E+09 |
May | 0.267027E+09 | 72363890.67 | 0.194663E+09 | 0.203131E+09 | 0.125942E+09 |
June | 0.250877E+09 | 51046261.85 | 0.199831E+09 | 0.216688E+09 | 89370843.75 |
July | 0.274420E+09 | 69108750.79 | 0.205311E+09 | 0.245409E+09 | 82288491.13 |
August | 0.309194E+09 | 0.110857E+09 | 0.198337E+09 | 0.303506E+09 | 98312616.06 |
September | 0.362712E+09 | 0.191152E+09 | 0.171559E+09 | 0.366442E+09 | 0.152879E+09 |
October | 0.391441E+09 | 0.245628E+09 | 0.145813E+09 | 0.380728E+09 | 0.219454E+09 |
November | 0.285689E+09 | 0.178839E+09 | 0.106850E+09 | 0.239021E+09 | 0.311075E+09 |
December | 0.314697E+09 | 0.238348E+09 | 76348328.03 | 0.277654E+09 | 0.453456E+09 |
Annual Sum or Average | 0.388110E+10 | 0.200526E+10 | 0.187584E+10 | 0.335195E+10 | 0.286425E+10 |
Minimum of Months | 0.250877E+09 | 51046261.85 | 76348328.03 | 0.203131E+09 | 82288491.13 |
Maximum of Months | 0.391441E+09 | 0.262521E+09 | 0.205311E+09 | 0.380728E+09 | 0.490743E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.320420E+09 | 0.219248E+09 | 0.101171E+09 | 0.248341E+09 | 0.413267E+09 |
February | 0.310244E+09 | 0.209629E+09 | 0.100615E+09 | 0.244627E+09 | 0.299881E+09 |
March | 0.298959E+09 | 0.157481E+09 | 0.141478E+09 | 0.236222E+09 | 0.234923E+09 |
April | 0.260528E+09 | 0.121793E+09 | 0.138735E+09 | 0.204763E+09 | 0.166147E+09 |
May | 0.223012E+09 | 60435776.82 | 0.162576E+09 | 0.171699E+09 | 0.102031E+09 |
June | 0.209524E+09 | 42632042.87 | 0.166892E+09 | 0.182230E+09 | 73167413.59 |
July | 0.229186E+09 | 57717198.46 | 0.171469E+09 | 0.205843E+09 | 67912817.09 |
August | 0.258228E+09 | 92583616.90 | 0.165644E+09 | 0.254232E+09 | 81515377.96 |
September | 0.302924E+09 | 0.159644E+09 | 0.143280E+09 | 0.306783E+09 | 0.126851E+09 |
October | 0.326917E+09 | 0.205140E+09 | 0.121778E+09 | 0.318439E+09 | 0.182281E+09 |
November | 0.238598E+09 | 0.149360E+09 | 89237204.53 | 0.199576E+09 | 0.260303E+09 |
December | 0.262824E+09 | 0.199060E+09 | 63763438.80 | 0.231610E+09 | 0.380705E+09 |
Annual Sum or Average | 0.324136E+10 | 0.167472E+10 | 0.156664E+10 | 0.280437E+10 | 0.238898E+10 |
Minimum of Months | 0.209524E+09 | 42632042.87 | 63763438.80 | 0.171699E+09 | 67912817.09 |
Maximum of Months | 0.326917E+09 | 0.219248E+09 | 0.171469E+09 | 0.318439E+09 | 0.413267E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.320420E+09 | 0.219248E+09 | 0.101171E+09 | 0.248341E+09 | 0.413267E+09 |
February | 0.310244E+09 | 0.209629E+09 | 0.100615E+09 | 0.244627E+09 | 0.299881E+09 |
March | 0.298959E+09 | 0.157481E+09 | 0.141478E+09 | 0.236222E+09 | 0.234923E+09 |
April | 0.260528E+09 | 0.121793E+09 | 0.138735E+09 | 0.204763E+09 | 0.166147E+09 |
May | 0.223012E+09 | 60435776.82 | 0.162576E+09 | 0.171699E+09 | 0.102031E+09 |
June | 0.209524E+09 | 42632042.87 | 0.166892E+09 | 0.182230E+09 | 73167413.59 |
July | 0.229186E+09 | 57717198.46 | 0.171469E+09 | 0.205843E+09 | 67912817.09 |
August | 0.258228E+09 | 92583616.90 | 0.165644E+09 | 0.254232E+09 | 81515377.96 |
September | 0.302924E+09 | 0.159644E+09 | 0.143280E+09 | 0.306783E+09 | 0.126851E+09 |
October | 0.326917E+09 | 0.205140E+09 | 0.121778E+09 | 0.318439E+09 | 0.182281E+09 |
November | 0.238598E+09 | 0.149360E+09 | 89237204.53 | 0.199576E+09 | 0.260303E+09 |
December | 0.262824E+09 | 0.199060E+09 | 63763438.80 | 0.231610E+09 | 0.380705E+09 |
Annual Sum or Average | 0.324136E+10 | 0.167472E+10 | 0.156664E+10 | 0.280437E+10 | 0.238898E+10 |
Minimum of Months | 0.209524E+09 | 42632042.87 | 63763438.80 | 0.171699E+09 | 67912817.09 |
Maximum of Months | 0.326917E+09 | 0.219248E+09 | 0.171469E+09 | 0.318439E+09 | 0.413267E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_DOOR
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.383660E+09 | 0.262521E+09 | 0.121139E+09 | 0.298772E+09 | 0.488469E+09 |
February | 0.371476E+09 | 0.251003E+09 | 0.120474E+09 | 0.294136E+09 | 0.354494E+09 |
March | 0.357964E+09 | 0.188563E+09 | 0.169401E+09 | 0.283867E+09 | 0.277738E+09 |
April | 0.311947E+09 | 0.145831E+09 | 0.166116E+09 | 0.245654E+09 | 0.196596E+09 |
May | 0.267027E+09 | 72363890.67 | 0.194663E+09 | 0.205932E+09 | 0.121040E+09 |
June | 0.250877E+09 | 51046261.85 | 0.199831E+09 | 0.218072E+09 | 86900550.70 |
July | 0.274420E+09 | 69108750.79 | 0.205311E+09 | 0.246287E+09 | 80766859.11 |
August | 0.309194E+09 | 0.110857E+09 | 0.198337E+09 | 0.304186E+09 | 96845265.56 |
September | 0.362712E+09 | 0.191152E+09 | 0.171559E+09 | 0.367228E+09 | 0.150590E+09 |
October | 0.391441E+09 | 0.245628E+09 | 0.145813E+09 | 0.381768E+09 | 0.216064E+09 |
November | 0.285689E+09 | 0.178839E+09 | 0.106850E+09 | 0.239688E+09 | 0.307776E+09 |
December | 0.314697E+09 | 0.238348E+09 | 76348328.03 | 0.278084E+09 | 0.450215E+09 |
Annual Sum or Average | 0.388110E+10 | 0.200526E+10 | 0.187584E+10 | 0.336367E+10 | 0.282749E+10 |
Minimum of Months | 0.250877E+09 | 51046261.85 | 76348328.03 | 0.205932E+09 | 80766859.11 |
Maximum of Months | 0.391441E+09 | 0.262521E+09 | 0.205311E+09 | 0.381768E+09 | 0.488469E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.320420E+09 | 0.219248E+09 | 0.101171E+09 | 0.250524E+09 | 0.401121E+09 |
February | 0.310244E+09 | 0.209629E+09 | 0.100615E+09 | 0.247006E+09 | 0.287030E+09 |
March | 0.298959E+09 | 0.157481E+09 | 0.141478E+09 | 0.239551E+09 | 0.218990E+09 |
April | 0.260528E+09 | 0.121793E+09 | 0.138735E+09 | 0.208428E+09 | 0.148856E+09 |
May | 0.223012E+09 | 60435776.82 | 0.162576E+09 | 0.178122E+09 | 88110679.48 |
June | 0.209524E+09 | 42632042.87 | 0.166892E+09 | 0.185854E+09 | 64901901.98 |
July | 0.229186E+09 | 57717198.46 | 0.171469E+09 | 0.208149E+09 | 62334732.12 |
August | 0.258228E+09 | 92583616.90 | 0.165644E+09 | 0.255796E+09 | 76066552.16 |
September | 0.302924E+09 | 0.159644E+09 | 0.143280E+09 | 0.308346E+09 | 0.119286E+09 |
October | 0.326917E+09 | 0.205140E+09 | 0.121778E+09 | 0.321039E+09 | 0.170688E+09 |
November | 0.238598E+09 | 0.149360E+09 | 89237204.53 | 0.201614E+09 | 0.247896E+09 |
December | 0.262824E+09 | 0.199060E+09 | 63763438.80 | 0.233294E+09 | 0.367284E+09 |
Annual Sum or Average | 0.324136E+10 | 0.167472E+10 | 0.156664E+10 | 0.283772E+10 | 0.225256E+10 |
Minimum of Months | 0.209524E+09 | 42632042.87 | 63763438.80 | 0.178122E+09 | 62334732.12 |
Maximum of Months | 0.326917E+09 | 0.219248E+09 | 0.171469E+09 | 0.321039E+09 | 0.401121E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.320420E+09 | 0.219248E+09 | 0.101171E+09 | 0.250524E+09 | 0.401121E+09 |
February | 0.310244E+09 | 0.209629E+09 | 0.100615E+09 | 0.247006E+09 | 0.287030E+09 |
March | 0.298959E+09 | 0.157481E+09 | 0.141478E+09 | 0.239551E+09 | 0.218990E+09 |
April | 0.260528E+09 | 0.121793E+09 | 0.138735E+09 | 0.208428E+09 | 0.148856E+09 |
May | 0.223012E+09 | 60435776.82 | 0.162576E+09 | 0.178122E+09 | 88110679.48 |
June | 0.209524E+09 | 42632042.87 | 0.166892E+09 | 0.185854E+09 | 64901901.98 |
July | 0.229186E+09 | 57717198.46 | 0.171469E+09 | 0.208149E+09 | 62334732.12 |
August | 0.258228E+09 | 92583616.90 | 0.165644E+09 | 0.255796E+09 | 76066552.16 |
September | 0.302924E+09 | 0.159644E+09 | 0.143280E+09 | 0.308346E+09 | 0.119286E+09 |
October | 0.326917E+09 | 0.205140E+09 | 0.121778E+09 | 0.321039E+09 | 0.170688E+09 |
November | 0.238598E+09 | 0.149360E+09 | 89237204.53 | 0.201614E+09 | 0.247896E+09 |
December | 0.262824E+09 | 0.199060E+09 | 63763438.80 | 0.233294E+09 | 0.367284E+09 |
Annual Sum or Average | 0.324136E+10 | 0.167472E+10 | 0.156664E+10 | 0.283772E+10 | 0.225256E+10 |
Minimum of Months | 0.209524E+09 | 42632042.87 | 63763438.80 | 0.178122E+09 | 62334732.12 |
Maximum of Months | 0.326917E+09 | 0.219248E+09 | 0.171469E+09 | 0.321039E+09 | 0.401121E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_DOOR
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.383660E+09 | 0.262521E+09 | 0.121139E+09 | 0.301435E+09 | 0.473878E+09 |
February | 0.371476E+09 | 0.251003E+09 | 0.120474E+09 | 0.297035E+09 | 0.339128E+09 |
March | 0.357964E+09 | 0.188563E+09 | 0.169401E+09 | 0.287928E+09 | 0.258793E+09 |
April | 0.311947E+09 | 0.145831E+09 | 0.166116E+09 | 0.250100E+09 | 0.176080E+09 |
May | 0.267027E+09 | 72363890.67 | 0.194663E+09 | 0.213656E+09 | 0.104588E+09 |
June | 0.250877E+09 | 51046261.85 | 0.199831E+09 | 0.222426E+09 | 77129773.96 |
July | 0.274420E+09 | 69108750.79 | 0.205311E+09 | 0.249053E+09 | 74176317.74 |
August | 0.309194E+09 | 0.110857E+09 | 0.198337E+09 | 0.306064E+09 | 90423230.33 |
September | 0.362712E+09 | 0.191152E+09 | 0.171559E+09 | 0.369115E+09 | 0.141664E+09 |
October | 0.391441E+09 | 0.245628E+09 | 0.145813E+09 | 0.384918E+09 | 0.202376E+09 |
November | 0.285689E+09 | 0.178839E+09 | 0.106850E+09 | 0.242171E+09 | 0.293050E+09 |
December | 0.314697E+09 | 0.238348E+09 | 76348328.03 | 0.280130E+09 | 0.434178E+09 |
Annual Sum or Average | 0.388110E+10 | 0.200526E+10 | 0.187584E+10 | 0.340403E+10 | 0.266546E+10 |
Minimum of Months | 0.250877E+09 | 51046261.85 | 76348328.03 | 0.213656E+09 | 74176317.74 |
Maximum of Months | 0.391441E+09 | 0.262521E+09 | 0.205311E+09 | 0.384918E+09 | 0.473878E+09 |
Report: WindowZoneSummaryMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 595.48 | 1020.99 | 766.58 | 524.54 | 242.05 | 0.00 | 0.00 |
February | 648.14 | 826.07 | 821.76 | 555.26 | 266.51 | 0.00 | 0.00 |
March | 562.76 | 592.09 | 715.24 | 376.76 | 338.48 | 0.00 | 0.00 |
April | 500.47 | 439.65 | 644.07 | 301.09 | 342.98 | 0.00 | 0.00 |
May | 392.57 | 275.23 | 533.54 | 144.59 | 388.95 | 0.00 | 0.00 |
June | 442.96 | 193.89 | 517.98 | 105.39 | 412.59 | 0.00 | 0.00 |
July | 489.01 | 166.17 | 548.31 | 138.08 | 410.23 | 0.00 | 0.00 |
August | 603.91 | 200.21 | 617.79 | 221.50 | 396.29 | 0.00 | 0.00 |
September | 751.73 | 330.06 | 748.88 | 394.67 | 354.21 | 0.00 | 0.00 |
October | 751.88 | 470.35 | 782.13 | 490.78 | 291.35 | 0.00 | 0.00 |
November | 487.73 | 682.72 | 589.86 | 369.25 | 220.61 | 0.00 | 0.00 |
December | 552.80 | 943.62 | 628.79 | 476.24 | 152.55 | 0.00 | 0.00 |
Annual Sum or Average | 564.48 | 510.27 | 658.62 | 340.29 | 318.33 | 0.00 | 0.00 |
Minimum of Months | 392.57 | 166.17 | 517.98 | 105.39 | 152.55 | 0.00 | 0.00 |
Maximum of Months | 751.88 | 1020.99 | 821.76 | 555.26 | 412.59 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 293.75 | 525.73 | 383.29 | 262.27 | 121.02 | 0.00 | 0.00 |
February | 319.67 | 429.09 | 410.88 | 277.63 | 133.25 | 0.00 | 0.00 |
March | 276.70 | 313.03 | 357.62 | 188.38 | 169.24 | 0.00 | 0.00 |
April | 246.62 | 235.50 | 322.04 | 150.55 | 171.49 | 0.00 | 0.00 |
May | 192.95 | 144.89 | 266.77 | 72.29 | 194.48 | 0.00 | 0.00 |
June | 219.98 | 100.53 | 258.99 | 52.70 | 206.29 | 0.00 | 0.00 |
July | 243.83 | 84.56 | 274.16 | 69.04 | 205.11 | 0.00 | 0.00 |
August | 301.52 | 101.66 | 308.90 | 110.75 | 198.15 | 0.00 | 0.00 |
September | 374.95 | 169.23 | 374.44 | 197.33 | 177.11 | 0.00 | 0.00 |
October | 372.64 | 246.95 | 391.06 | 245.39 | 145.67 | 0.00 | 0.00 |
November | 240.86 | 355.81 | 294.93 | 184.62 | 110.31 | 0.00 | 0.00 |
December | 273.38 | 488.41 | 314.39 | 238.12 | 76.27 | 0.00 | 0.00 |
Annual Sum or Average | 279.51 | 265.50 | 329.31 | 170.15 | 159.16 | 0.00 | 0.00 |
Minimum of Months | 192.95 | 84.56 | 258.99 | 52.70 | 76.27 | 0.00 | 0.00 |
Maximum of Months | 374.95 | 525.73 | 410.88 | 277.63 | 206.29 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 294.24 | 507.65 | 382.50 | 261.73 | 120.77 | 0.00 | 0.00 |
February | 320.26 | 412.56 | 410.04 | 277.06 | 132.98 | 0.00 | 0.00 |
March | 277.75 | 298.88 | 356.89 | 187.99 | 168.89 | 0.00 | 0.00 |
April | 247.57 | 223.76 | 321.37 | 150.24 | 171.14 | 0.00 | 0.00 |
May | 195.07 | 139.33 | 266.22 | 72.15 | 194.08 | 0.00 | 0.00 |
June | 219.80 | 100.66 | 258.46 | 52.59 | 205.87 | 0.00 | 0.00 |
July | 242.71 | 88.13 | 273.59 | 68.90 | 204.69 | 0.00 | 0.00 |
August | 300.85 | 104.42 | 308.26 | 110.52 | 197.74 | 0.00 | 0.00 |
September | 375.01 | 166.84 | 373.67 | 196.93 | 176.74 | 0.00 | 0.00 |
October | 374.78 | 233.47 | 390.26 | 244.89 | 145.37 | 0.00 | 0.00 |
November | 242.30 | 339.03 | 294.32 | 184.24 | 110.08 | 0.00 | 0.00 |
December | 273.80 | 471.56 | 313.75 | 237.63 | 76.12 | 0.00 | 0.00 |
Annual Sum or Average | 280.12 | 256.46 | 328.63 | 169.80 | 158.84 | 0.00 | 0.00 |
Minimum of Months | 195.07 | 88.13 | 258.46 | 52.59 | 76.12 | 0.00 | 0.00 |
Maximum of Months | 375.01 | 507.65 | 410.04 | 277.06 | 205.87 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 294.75 | 502.97 | 382.50 | 261.73 | 120.77 | 0.00 | 0.00 |
February | 320.87 | 407.95 | 410.04 | 277.06 | 132.98 | 0.00 | 0.00 |
March | 278.60 | 294.21 | 356.89 | 187.99 | 168.89 | 0.00 | 0.00 |
April | 248.47 | 219.44 | 321.37 | 150.24 | 171.14 | 0.00 | 0.00 |
May | 196.64 | 135.95 | 266.22 | 72.15 | 194.08 | 0.00 | 0.00 |
June | 220.46 | 99.22 | 258.46 | 52.59 | 205.87 | 0.00 | 0.00 |
July | 243.00 | 87.62 | 273.59 | 68.90 | 204.69 | 0.00 | 0.00 |
August | 301.15 | 103.72 | 308.26 | 110.52 | 197.74 | 0.00 | 0.00 |
September | 375.61 | 164.74 | 373.67 | 196.93 | 176.74 | 0.00 | 0.00 |
October | 376.08 | 228.73 | 390.26 | 244.89 | 145.37 | 0.00 | 0.00 |
November | 243.21 | 333.69 | 294.32 | 184.24 | 110.08 | 0.00 | 0.00 |
December | 274.30 | 466.71 | 313.75 | 237.63 | 76.12 | 0.00 | 0.00 |
Annual Sum or Average | 280.87 | 253.02 | 328.63 | 169.80 | 158.84 | 0.00 | 0.00 |
Minimum of Months | 196.64 | 87.62 | 258.46 | 52.59 | 76.12 | 0.00 | 0.00 |
Maximum of Months | 376.08 | 502.97 | 410.04 | 277.06 | 205.87 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 295.17 | 500.67 | 382.50 | 261.73 | 120.77 | 0.00 | 0.00 |
February | 321.39 | 405.47 | 410.04 | 277.06 | 132.98 | 0.00 | 0.00 |
March | 279.28 | 291.52 | 356.89 | 187.99 | 168.89 | 0.00 | 0.00 |
April | 249.18 | 216.83 | 321.37 | 150.24 | 171.14 | 0.00 | 0.00 |
May | 197.94 | 133.57 | 266.22 | 72.15 | 194.08 | 0.00 | 0.00 |
June | 221.10 | 97.82 | 258.46 | 52.59 | 205.87 | 0.00 | 0.00 |
July | 243.38 | 86.66 | 273.59 | 68.90 | 204.69 | 0.00 | 0.00 |
August | 301.49 | 102.74 | 308.26 | 110.52 | 197.74 | 0.00 | 0.00 |
September | 376.08 | 163.22 | 373.67 | 196.93 | 176.74 | 0.00 | 0.00 |
October | 376.92 | 226.28 | 390.26 | 244.89 | 145.37 | 0.00 | 0.00 |
November | 243.86 | 330.80 | 294.32 | 184.24 | 110.08 | 0.00 | 0.00 |
December | 274.72 | 463.97 | 313.75 | 237.63 | 76.12 | 0.00 | 0.00 |
Annual Sum or Average | 281.48 | 250.91 | 328.63 | 169.80 | 158.84 | 0.00 | 0.00 |
Minimum of Months | 197.94 | 86.66 | 258.46 | 52.59 | 76.12 | 0.00 | 0.00 |
Maximum of Months | 376.92 | 500.67 | 410.04 | 277.06 | 205.87 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 596.61 | 979.03 | 765.01 | 523.46 | 241.55 | 0.00 | 0.00 |
February | 649.71 | 790.00 | 820.08 | 554.12 | 265.96 | 0.00 | 0.00 |
March | 565.00 | 563.81 | 713.77 | 375.99 | 337.78 | 0.00 | 0.00 |
April | 502.72 | 418.68 | 642.75 | 300.48 | 342.27 | 0.00 | 0.00 |
May | 400.21 | 257.58 | 532.45 | 144.29 | 388.15 | 0.00 | 0.00 |
June | 443.50 | 188.65 | 516.92 | 105.18 | 411.74 | 0.00 | 0.00 |
July | 487.16 | 167.70 | 547.19 | 137.80 | 409.38 | 0.00 | 0.00 |
August | 603.55 | 199.74 | 616.52 | 221.05 | 395.48 | 0.00 | 0.00 |
September | 753.45 | 320.02 | 747.35 | 393.86 | 353.49 | 0.00 | 0.00 |
October | 759.38 | 441.51 | 780.52 | 489.77 | 290.75 | 0.00 | 0.00 |
November | 493.11 | 642.99 | 588.65 | 368.49 | 220.16 | 0.00 | 0.00 |
December | 554.90 | 904.60 | 627.50 | 475.26 | 152.24 | 0.00 | 0.00 |
Annual Sum or Average | 566.98 | 488.12 | 657.27 | 339.59 | 317.68 | 0.00 | 0.00 |
Minimum of Months | 400.21 | 167.70 | 516.92 | 105.18 | 152.24 | 0.00 | 0.00 |
Maximum of Months | 759.38 | 979.03 | 820.08 | 554.12 | 411.74 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 296.56 | 493.52 | 382.50 | 261.73 | 120.77 | 0.00 | 0.00 |
February | 323.17 | 398.24 | 410.04 | 277.06 | 132.98 | 0.00 | 0.00 |
March | 281.20 | 284.12 | 356.89 | 187.99 | 168.89 | 0.00 | 0.00 |
April | 251.08 | 210.30 | 321.37 | 150.24 | 171.14 | 0.00 | 0.00 |
May | 201.15 | 128.07 | 266.22 | 72.15 | 194.08 | 0.00 | 0.00 |
June | 222.74 | 93.45 | 258.46 | 52.59 | 205.87 | 0.00 | 0.00 |
July | 244.40 | 82.95 | 273.59 | 68.90 | 204.69 | 0.00 | 0.00 |
August | 302.40 | 99.06 | 308.26 | 110.52 | 197.74 | 0.00 | 0.00 |
September | 377.19 | 159.28 | 373.67 | 196.93 | 176.74 | 0.00 | 0.00 |
October | 378.91 | 221.18 | 390.26 | 244.89 | 145.37 | 0.00 | 0.00 |
November | 245.57 | 323.84 | 294.32 | 184.24 | 110.08 | 0.00 | 0.00 |
December | 276.25 | 456.14 | 313.75 | 237.63 | 76.12 | 0.00 | 0.00 |
Annual Sum or Average | 283.16 | 245.13 | 328.63 | 169.80 | 158.84 | 0.00 | 0.00 |
Minimum of Months | 201.15 | 82.95 | 258.46 | 52.59 | 76.12 | 0.00 | 0.00 |
Maximum of Months | 378.91 | 493.52 | 410.04 | 277.06 | 205.87 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 296.62 | 493.23 | 382.50 | 261.73 | 120.77 | 0.00 | 0.00 |
February | 323.27 | 397.68 | 410.04 | 277.06 | 132.98 | 0.00 | 0.00 |
March | 281.45 | 283.27 | 356.89 | 187.99 | 168.89 | 0.00 | 0.00 |
April | 251.49 | 209.05 | 321.37 | 150.24 | 171.14 | 0.00 | 0.00 |
May | 202.30 | 126.30 | 266.22 | 72.15 | 194.08 | 0.00 | 0.00 |
June | 223.32 | 92.55 | 258.46 | 52.59 | 205.87 | 0.00 | 0.00 |
July | 244.79 | 82.40 | 273.59 | 68.90 | 204.69 | 0.00 | 0.00 |
August | 302.73 | 98.50 | 308.26 | 110.52 | 197.74 | 0.00 | 0.00 |
September | 377.59 | 158.36 | 373.67 | 196.93 | 176.74 | 0.00 | 0.00 |
October | 379.29 | 220.18 | 390.26 | 244.89 | 145.37 | 0.00 | 0.00 |
November | 245.78 | 323.01 | 294.32 | 184.24 | 110.08 | 0.00 | 0.00 |
December | 276.35 | 455.61 | 313.75 | 237.63 | 76.12 | 0.00 | 0.00 |
Annual Sum or Average | 283.52 | 244.30 | 328.63 | 169.80 | 158.84 | 0.00 | 0.00 |
Minimum of Months | 202.30 | 82.40 | 258.46 | 52.59 | 76.12 | 0.00 | 0.00 |
Maximum of Months | 379.29 | 493.23 | 410.04 | 277.06 | 205.87 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 296.99 | 490.96 | 382.50 | 261.73 | 120.77 | 0.00 | 0.00 |
February | 323.82 | 394.45 | 410.04 | 277.06 | 132.98 | 0.00 | 0.00 |
March | 282.37 | 279.11 | 356.89 | 187.99 | 168.89 | 0.00 | 0.00 |
April | 252.77 | 204.05 | 321.37 | 150.24 | 171.14 | 0.00 | 0.00 |
May | 205.10 | 121.38 | 266.22 | 72.15 | 194.08 | 0.00 | 0.00 |
June | 224.74 | 89.98 | 258.46 | 52.59 | 205.87 | 0.00 | 0.00 |
July | 245.66 | 80.87 | 273.59 | 68.90 | 204.69 | 0.00 | 0.00 |
August | 303.41 | 97.03 | 308.26 | 110.52 | 197.74 | 0.00 | 0.00 |
September | 378.39 | 155.98 | 373.67 | 196.93 | 176.74 | 0.00 | 0.00 |
October | 380.32 | 216.78 | 390.26 | 244.89 | 145.37 | 0.00 | 0.00 |
November | 246.46 | 319.59 | 294.32 | 184.24 | 110.08 | 0.00 | 0.00 |
December | 276.77 | 452.37 | 313.75 | 237.63 | 76.12 | 0.00 | 0.00 |
Annual Sum or Average | 284.51 | 241.17 | 328.63 | 169.80 | 158.84 | 0.00 | 0.00 |
Minimum of Months | 205.10 | 80.87 | 258.46 | 52.59 | 76.12 | 0.00 | 0.00 |
Maximum of Months | 380.32 | 490.96 | 410.04 | 277.06 | 205.87 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 299.61 | 476.45 | 382.50 | 261.73 | 120.77 | 0.00 | 0.00 |
February | 326.99 | 377.47 | 410.04 | 277.06 | 132.98 | 0.00 | 0.00 |
March | 286.37 | 260.14 | 356.89 | 187.99 | 168.89 | 0.00 | 0.00 |
April | 257.31 | 182.79 | 321.37 | 150.24 | 171.14 | 0.00 | 0.00 |
May | 212.78 | 104.84 | 266.22 | 72.15 | 194.08 | 0.00 | 0.00 |
June | 229.22 | 79.84 | 258.46 | 52.59 | 205.87 | 0.00 | 0.00 |
July | 248.41 | 74.24 | 273.59 | 68.90 | 204.69 | 0.00 | 0.00 |
August | 305.28 | 90.56 | 308.26 | 110.52 | 197.74 | 0.00 | 0.00 |
September | 380.33 | 146.70 | 373.67 | 196.93 | 176.74 | 0.00 | 0.00 |
October | 383.44 | 203.01 | 390.26 | 244.89 | 145.37 | 0.00 | 0.00 |
November | 249.00 | 304.34 | 294.32 | 184.24 | 110.08 | 0.00 | 0.00 |
December | 278.79 | 436.36 | 313.75 | 237.63 | 76.12 | 0.00 | 0.00 |
Annual Sum or Average | 287.91 | 227.38 | 328.63 | 169.80 | 158.84 | 0.00 | 0.00 |
Minimum of Months | 212.78 | 74.24 | 258.46 | 52.59 | 76.12 | 0.00 | 0.00 |
Maximum of Months | 383.44 | 476.45 | 410.04 | 277.06 | 205.87 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.159493E+10 | 0.273461E+10 | 0.205322E+10 | 0.140492E+10 | 0.648296E+09 | 0.00 | 0.00 |
February | 0.156797E+10 | 0.199843E+10 | 0.198801E+10 | 0.134328E+10 | 0.644733E+09 | 0.00 | 0.00 |
March | 0.150731E+10 | 0.158586E+10 | 0.191570E+10 | 0.100912E+10 | 0.906573E+09 | 0.00 | 0.00 |
April | 0.129723E+10 | 0.113958E+10 | 0.166943E+10 | 0.780436E+09 | 0.888997E+09 | 0.00 | 0.00 |
May | 0.105147E+10 | 0.737167E+09 | 0.142904E+10 | 0.387266E+09 | 0.104177E+10 | 0.00 | 0.00 |
June | 0.114815E+10 | 0.502565E+09 | 0.134261E+10 | 0.273182E+09 | 0.106943E+10 | 0.00 | 0.00 |
July | 0.130976E+10 | 0.445076E+09 | 0.146860E+10 | 0.369846E+09 | 0.109875E+10 | 0.00 | 0.00 |
August | 0.161751E+10 | 0.536243E+09 | 0.165470E+10 | 0.593266E+09 | 0.106143E+10 | 0.00 | 0.00 |
September | 0.194849E+10 | 0.855510E+09 | 0.194110E+10 | 0.102298E+10 | 0.918125E+09 | 0.00 | 0.00 |
October | 0.201383E+10 | 0.125980E+10 | 0.209485E+10 | 0.131451E+10 | 0.780340E+09 | 0.00 | 0.00 |
November | 0.126419E+10 | 0.176960E+10 | 0.152891E+10 | 0.957086E+09 | 0.571823E+09 | 0.00 | 0.00 |
December | 0.148062E+10 | 0.252738E+10 | 0.168415E+10 | 0.127556E+10 | 0.408589E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.178015E+11 | 0.160918E+11 | 0.207703E+11 | 0.107314E+11 | 0.100389E+11 | 0.00 | 0.00 |
Minimum of Months | 0.105147E+10 | 0.445076E+09 | 0.134261E+10 | 0.273182E+09 | 0.408589E+09 | 0.00 | 0.00 |
Maximum of Months | 0.201383E+10 | 0.273461E+10 | 0.209485E+10 | 0.140492E+10 | 0.109875E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.786781E+09 | 0.140811E+10 | 0.102661E+10 | 0.702460E+09 | 0.324148E+09 | 0.00 | 0.00 |
February | 0.773341E+09 | 0.103806E+10 | 0.994005E+09 | 0.671639E+09 | 0.322366E+09 | 0.00 | 0.00 |
March | 0.741106E+09 | 0.838425E+09 | 0.957848E+09 | 0.504561E+09 | 0.453287E+09 | 0.00 | 0.00 |
April | 0.639242E+09 | 0.610423E+09 | 0.834717E+09 | 0.390218E+09 | 0.444498E+09 | 0.00 | 0.00 |
May | 0.516809E+09 | 0.388087E+09 | 0.714518E+09 | 0.193633E+09 | 0.520885E+09 | 0.00 | 0.00 |
June | 0.570198E+09 | 0.260576E+09 | 0.671304E+09 | 0.136591E+09 | 0.534713E+09 | 0.00 | 0.00 |
July | 0.653075E+09 | 0.226484E+09 | 0.734299E+09 | 0.184923E+09 | 0.549376E+09 | 0.00 | 0.00 |
August | 0.807596E+09 | 0.272273E+09 | 0.827348E+09 | 0.296633E+09 | 0.530715E+09 | 0.00 | 0.00 |
September | 0.971880E+09 | 0.438650E+09 | 0.970552E+09 | 0.511490E+09 | 0.459063E+09 | 0.00 | 0.00 |
October | 0.998081E+09 | 0.661431E+09 | 0.104743E+10 | 0.657256E+09 | 0.390170E+09 | 0.00 | 0.00 |
November | 0.624311E+09 | 0.922250E+09 | 0.764454E+09 | 0.478543E+09 | 0.285911E+09 | 0.00 | 0.00 |
December | 0.732231E+09 | 0.130815E+10 | 0.842073E+09 | 0.637778E+09 | 0.204295E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.881465E+10 | 0.837292E+10 | 0.103852E+11 | 0.536572E+10 | 0.501943E+10 | 0.00 | 0.00 |
Minimum of Months | 0.516809E+09 | 0.226484E+09 | 0.671304E+09 | 0.136591E+09 | 0.204295E+09 | 0.00 | 0.00 |
Maximum of Months | 0.998081E+09 | 0.140811E+10 | 0.104743E+10 | 0.702460E+09 | 0.549376E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.788102E+09 | 0.135969E+10 | 0.102450E+10 | 0.701017E+09 | 0.323482E+09 | 0.00 | 0.00 |
February | 0.774775E+09 | 0.998076E+09 | 0.991964E+09 | 0.670260E+09 | 0.321704E+09 | 0.00 | 0.00 |
March | 0.743925E+09 | 0.800523E+09 | 0.955881E+09 | 0.503525E+09 | 0.452356E+09 | 0.00 | 0.00 |
April | 0.641701E+09 | 0.579990E+09 | 0.833003E+09 | 0.389417E+09 | 0.443586E+09 | 0.00 | 0.00 |
May | 0.522462E+09 | 0.373174E+09 | 0.713051E+09 | 0.193235E+09 | 0.519815E+09 | 0.00 | 0.00 |
June | 0.569728E+09 | 0.260899E+09 | 0.669925E+09 | 0.136310E+09 | 0.533615E+09 | 0.00 | 0.00 |
July | 0.650085E+09 | 0.236058E+09 | 0.732791E+09 | 0.184543E+09 | 0.548248E+09 | 0.00 | 0.00 |
August | 0.805802E+09 | 0.279666E+09 | 0.825649E+09 | 0.296024E+09 | 0.529625E+09 | 0.00 | 0.00 |
September | 0.972036E+09 | 0.432439E+09 | 0.968559E+09 | 0.510439E+09 | 0.458120E+09 | 0.00 | 0.00 |
October | 0.100382E+10 | 0.625326E+09 | 0.104528E+10 | 0.655907E+09 | 0.389369E+09 | 0.00 | 0.00 |
November | 0.628037E+09 | 0.878773E+09 | 0.762885E+09 | 0.477560E+09 | 0.285324E+09 | 0.00 | 0.00 |
December | 0.733336E+09 | 0.126302E+10 | 0.840344E+09 | 0.636469E+09 | 0.203875E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.883381E+10 | 0.808763E+10 | 0.103638E+11 | 0.535471E+10 | 0.500912E+10 | 0.00 | 0.00 |
Minimum of Months | 0.522462E+09 | 0.236058E+09 | 0.669925E+09 | 0.136310E+09 | 0.203875E+09 | 0.00 | 0.00 |
Maximum of Months | 0.100382E+10 | 0.135969E+10 | 0.104528E+10 | 0.701017E+09 | 0.548248E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.789457E+09 | 0.134715E+10 | 0.102450E+10 | 0.701017E+09 | 0.323482E+09 | 0.00 | 0.00 |
February | 0.776260E+09 | 0.986915E+09 | 0.991964E+09 | 0.670260E+09 | 0.321704E+09 | 0.00 | 0.00 |
March | 0.746214E+09 | 0.788012E+09 | 0.955881E+09 | 0.503525E+09 | 0.452356E+09 | 0.00 | 0.00 |
April | 0.644042E+09 | 0.568778E+09 | 0.833003E+09 | 0.389417E+09 | 0.443586E+09 | 0.00 | 0.00 |
May | 0.526680E+09 | 0.364137E+09 | 0.713051E+09 | 0.193235E+09 | 0.519815E+09 | 0.00 | 0.00 |
June | 0.571435E+09 | 0.257182E+09 | 0.669925E+09 | 0.136310E+09 | 0.533615E+09 | 0.00 | 0.00 |
July | 0.650848E+09 | 0.234677E+09 | 0.732791E+09 | 0.184543E+09 | 0.548248E+09 | 0.00 | 0.00 |
August | 0.806607E+09 | 0.277806E+09 | 0.825649E+09 | 0.296024E+09 | 0.529625E+09 | 0.00 | 0.00 |
September | 0.973583E+09 | 0.427001E+09 | 0.968559E+09 | 0.510439E+09 | 0.458120E+09 | 0.00 | 0.00 |
October | 0.100729E+10 | 0.612639E+09 | 0.104528E+10 | 0.655907E+09 | 0.389369E+09 | 0.00 | 0.00 |
November | 0.630412E+09 | 0.864937E+09 | 0.762885E+09 | 0.477560E+09 | 0.285324E+09 | 0.00 | 0.00 |
December | 0.734676E+09 | 0.125004E+10 | 0.840344E+09 | 0.636469E+09 | 0.203875E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.885751E+10 | 0.797927E+10 | 0.103638E+11 | 0.535471E+10 | 0.500912E+10 | 0.00 | 0.00 |
Minimum of Months | 0.526680E+09 | 0.234677E+09 | 0.669925E+09 | 0.136310E+09 | 0.203875E+09 | 0.00 | 0.00 |
Maximum of Months | 0.100729E+10 | 0.134715E+10 | 0.104528E+10 | 0.701017E+09 | 0.548248E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.790574E+09 | 0.134099E+10 | 0.102450E+10 | 0.701017E+09 | 0.323482E+09 | 0.00 | 0.00 |
February | 0.777508E+09 | 0.980915E+09 | 0.991964E+09 | 0.670260E+09 | 0.321704E+09 | 0.00 | 0.00 |
March | 0.748018E+09 | 0.780811E+09 | 0.955881E+09 | 0.503525E+09 | 0.452356E+09 | 0.00 | 0.00 |
April | 0.645876E+09 | 0.562017E+09 | 0.833003E+09 | 0.389417E+09 | 0.443586E+09 | 0.00 | 0.00 |
May | 0.530168E+09 | 0.357752E+09 | 0.713051E+09 | 0.193235E+09 | 0.519815E+09 | 0.00 | 0.00 |
June | 0.573084E+09 | 0.253559E+09 | 0.669925E+09 | 0.136310E+09 | 0.533615E+09 | 0.00 | 0.00 |
July | 0.651877E+09 | 0.232121E+09 | 0.732791E+09 | 0.184543E+09 | 0.548248E+09 | 0.00 | 0.00 |
August | 0.807524E+09 | 0.275168E+09 | 0.825649E+09 | 0.296024E+09 | 0.529625E+09 | 0.00 | 0.00 |
September | 0.974793E+09 | 0.423076E+09 | 0.968559E+09 | 0.510439E+09 | 0.458120E+09 | 0.00 | 0.00 |
October | 0.100953E+10 | 0.606059E+09 | 0.104528E+10 | 0.655907E+09 | 0.389369E+09 | 0.00 | 0.00 |
November | 0.632085E+09 | 0.857434E+09 | 0.762885E+09 | 0.477560E+09 | 0.285324E+09 | 0.00 | 0.00 |
December | 0.735809E+09 | 0.124270E+10 | 0.840344E+09 | 0.636469E+09 | 0.203875E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.887685E+10 | 0.791260E+10 | 0.103638E+11 | 0.535471E+10 | 0.500912E+10 | 0.00 | 0.00 |
Minimum of Months | 0.530168E+09 | 0.232121E+09 | 0.669925E+09 | 0.136310E+09 | 0.203875E+09 | 0.00 | 0.00 |
Maximum of Months | 0.100953E+10 | 0.134099E+10 | 0.104528E+10 | 0.701017E+09 | 0.548248E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.159797E+10 | 0.262223E+10 | 0.204900E+10 | 0.140203E+10 | 0.646964E+09 | 0.00 | 0.00 |
February | 0.157178E+10 | 0.191117E+10 | 0.198393E+10 | 0.134052E+10 | 0.643409E+09 | 0.00 | 0.00 |
March | 0.151329E+10 | 0.151011E+10 | 0.191176E+10 | 0.100705E+10 | 0.904712E+09 | 0.00 | 0.00 |
April | 0.130305E+10 | 0.108523E+10 | 0.166601E+10 | 0.778834E+09 | 0.887171E+09 | 0.00 | 0.00 |
May | 0.107193E+10 | 0.689914E+09 | 0.142610E+10 | 0.386471E+09 | 0.103963E+10 | 0.00 | 0.00 |
June | 0.114955E+10 | 0.488974E+09 | 0.133985E+10 | 0.272621E+09 | 0.106723E+10 | 0.00 | 0.00 |
July | 0.130480E+10 | 0.449160E+09 | 0.146558E+10 | 0.369086E+09 | 0.109650E+10 | 0.00 | 0.00 |
August | 0.161654E+10 | 0.534988E+09 | 0.165130E+10 | 0.592048E+09 | 0.105925E+10 | 0.00 | 0.00 |
September | 0.195295E+10 | 0.829483E+09 | 0.193712E+10 | 0.102088E+10 | 0.916240E+09 | 0.00 | 0.00 |
October | 0.203392E+10 | 0.118254E+10 | 0.209055E+10 | 0.131181E+10 | 0.778738E+09 | 0.00 | 0.00 |
November | 0.127815E+10 | 0.166664E+10 | 0.152577E+10 | 0.955121E+09 | 0.570648E+09 | 0.00 | 0.00 |
December | 0.148625E+10 | 0.242289E+10 | 0.168069E+10 | 0.127294E+10 | 0.407750E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.178802E+11 | 0.153933E+11 | 0.207277E+11 | 0.107094E+11 | 0.100182E+11 | 0.00 | 0.00 |
Minimum of Months | 0.107193E+10 | 0.449160E+09 | 0.133985E+10 | 0.272621E+09 | 0.407750E+09 | 0.00 | 0.00 |
Maximum of Months | 0.203392E+10 | 0.262223E+10 | 0.209055E+10 | 0.140203E+10 | 0.109650E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.794301E+09 | 0.132184E+10 | 0.102450E+10 | 0.701017E+09 | 0.323482E+09 | 0.00 | 0.00 |
February | 0.781802E+09 | 0.963434E+09 | 0.991964E+09 | 0.670260E+09 | 0.321704E+09 | 0.00 | 0.00 |
March | 0.753176E+09 | 0.760996E+09 | 0.955881E+09 | 0.503525E+09 | 0.452356E+09 | 0.00 | 0.00 |
April | 0.650807E+09 | 0.545103E+09 | 0.833003E+09 | 0.389417E+09 | 0.443586E+09 | 0.00 | 0.00 |
May | 0.538758E+09 | 0.343030E+09 | 0.713051E+09 | 0.193235E+09 | 0.519815E+09 | 0.00 | 0.00 |
June | 0.577331E+09 | 0.242213E+09 | 0.669925E+09 | 0.136310E+09 | 0.533615E+09 | 0.00 | 0.00 |
July | 0.654595E+09 | 0.222180E+09 | 0.732791E+09 | 0.184543E+09 | 0.548248E+09 | 0.00 | 0.00 |
August | 0.809946E+09 | 0.265334E+09 | 0.825649E+09 | 0.296024E+09 | 0.529625E+09 | 0.00 | 0.00 |
September | 0.977673E+09 | 0.412859E+09 | 0.968559E+09 | 0.510439E+09 | 0.458120E+09 | 0.00 | 0.00 |
October | 0.101488E+10 | 0.592404E+09 | 0.104528E+10 | 0.655907E+09 | 0.389369E+09 | 0.00 | 0.00 |
November | 0.636514E+09 | 0.839398E+09 | 0.762885E+09 | 0.477560E+09 | 0.285324E+09 | 0.00 | 0.00 |
December | 0.739911E+09 | 0.122173E+10 | 0.840344E+09 | 0.636469E+09 | 0.203875E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.892969E+10 | 0.773053E+10 | 0.103638E+11 | 0.535471E+10 | 0.500912E+10 | 0.00 | 0.00 |
Minimum of Months | 0.538758E+09 | 0.222180E+09 | 0.669925E+09 | 0.136310E+09 | 0.203875E+09 | 0.00 | 0.00 |
Maximum of Months | 0.101488E+10 | 0.132184E+10 | 0.104528E+10 | 0.701017E+09 | 0.548248E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.794458E+09 | 0.132107E+10 | 0.102450E+10 | 0.701017E+09 | 0.323482E+09 | 0.00 | 0.00 |
February | 0.782066E+09 | 0.962068E+09 | 0.991964E+09 | 0.670260E+09 | 0.321704E+09 | 0.00 | 0.00 |
March | 0.753834E+09 | 0.758705E+09 | 0.955881E+09 | 0.503525E+09 | 0.452356E+09 | 0.00 | 0.00 |
April | 0.651864E+09 | 0.541850E+09 | 0.833003E+09 | 0.389417E+09 | 0.443586E+09 | 0.00 | 0.00 |
May | 0.541853E+09 | 0.338283E+09 | 0.713051E+09 | 0.193235E+09 | 0.519815E+09 | 0.00 | 0.00 |
June | 0.578846E+09 | 0.239881E+09 | 0.669925E+09 | 0.136310E+09 | 0.533615E+09 | 0.00 | 0.00 |
July | 0.655636E+09 | 0.220690E+09 | 0.732791E+09 | 0.184543E+09 | 0.548248E+09 | 0.00 | 0.00 |
August | 0.810841E+09 | 0.263829E+09 | 0.825649E+09 | 0.296024E+09 | 0.529625E+09 | 0.00 | 0.00 |
September | 0.978705E+09 | 0.410456E+09 | 0.968559E+09 | 0.510439E+09 | 0.458120E+09 | 0.00 | 0.00 |
October | 0.101588E+10 | 0.589733E+09 | 0.104528E+10 | 0.655907E+09 | 0.389369E+09 | 0.00 | 0.00 |
November | 0.637068E+09 | 0.837231E+09 | 0.762885E+09 | 0.477560E+09 | 0.285324E+09 | 0.00 | 0.00 |
December | 0.740167E+09 | 0.122030E+10 | 0.840344E+09 | 0.636469E+09 | 0.203875E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.894122E+10 | 0.770410E+10 | 0.103638E+11 | 0.535471E+10 | 0.500912E+10 | 0.00 | 0.00 |
Minimum of Months | 0.541853E+09 | 0.220690E+09 | 0.669925E+09 | 0.136310E+09 | 0.203875E+09 | 0.00 | 0.00 |
Maximum of Months | 0.101588E+10 | 0.132107E+10 | 0.104528E+10 | 0.701017E+09 | 0.548248E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.795450E+09 | 0.131500E+10 | 0.102450E+10 | 0.701017E+09 | 0.323482E+09 | 0.00 | 0.00 |
February | 0.783387E+09 | 0.954254E+09 | 0.991964E+09 | 0.670260E+09 | 0.321704E+09 | 0.00 | 0.00 |
March | 0.756309E+09 | 0.747581E+09 | 0.955881E+09 | 0.503525E+09 | 0.452356E+09 | 0.00 | 0.00 |
April | 0.655180E+09 | 0.528889E+09 | 0.833003E+09 | 0.389417E+09 | 0.443586E+09 | 0.00 | 0.00 |
May | 0.549329E+09 | 0.325101E+09 | 0.713051E+09 | 0.193235E+09 | 0.519815E+09 | 0.00 | 0.00 |
June | 0.582532E+09 | 0.233235E+09 | 0.669925E+09 | 0.136310E+09 | 0.533615E+09 | 0.00 | 0.00 |
July | 0.657974E+09 | 0.216592E+09 | 0.732791E+09 | 0.184543E+09 | 0.548248E+09 | 0.00 | 0.00 |
August | 0.812650E+09 | 0.259876E+09 | 0.825649E+09 | 0.296024E+09 | 0.529625E+09 | 0.00 | 0.00 |
September | 0.980793E+09 | 0.404292E+09 | 0.968559E+09 | 0.510439E+09 | 0.458120E+09 | 0.00 | 0.00 |
October | 0.101865E+10 | 0.580625E+09 | 0.104528E+10 | 0.655907E+09 | 0.389369E+09 | 0.00 | 0.00 |
November | 0.638835E+09 | 0.828377E+09 | 0.762885E+09 | 0.477560E+09 | 0.285324E+09 | 0.00 | 0.00 |
December | 0.741304E+09 | 0.121162E+10 | 0.840344E+09 | 0.636469E+09 | 0.203875E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.897239E+10 | 0.760544E+10 | 0.103638E+11 | 0.535471E+10 | 0.500912E+10 | 0.00 | 0.00 |
Minimum of Months | 0.549329E+09 | 0.216592E+09 | 0.669925E+09 | 0.136310E+09 | 0.203875E+09 | 0.00 | 0.00 |
Maximum of Months | 0.101865E+10 | 0.131500E+10 | 0.104528E+10 | 0.701017E+09 | 0.548248E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.802483E+09 | 0.127612E+10 | 0.102450E+10 | 0.701017E+09 | 0.323482E+09 | 0.00 | 0.00 |
February | 0.791046E+09 | 0.913187E+09 | 0.991964E+09 | 0.670260E+09 | 0.321704E+09 | 0.00 | 0.00 |
March | 0.767025E+09 | 0.696769E+09 | 0.955881E+09 | 0.503525E+09 | 0.452356E+09 | 0.00 | 0.00 |
April | 0.666955E+09 | 0.473791E+09 | 0.833003E+09 | 0.389417E+09 | 0.443586E+09 | 0.00 | 0.00 |
May | 0.569899E+09 | 0.280809E+09 | 0.713051E+09 | 0.193235E+09 | 0.519815E+09 | 0.00 | 0.00 |
June | 0.594133E+09 | 0.206933E+09 | 0.669925E+09 | 0.136310E+09 | 0.533615E+09 | 0.00 | 0.00 |
July | 0.665351E+09 | 0.198846E+09 | 0.732791E+09 | 0.184543E+09 | 0.548248E+09 | 0.00 | 0.00 |
August | 0.817655E+09 | 0.242556E+09 | 0.825649E+09 | 0.296024E+09 | 0.529625E+09 | 0.00 | 0.00 |
September | 0.985806E+09 | 0.380235E+09 | 0.968559E+09 | 0.510439E+09 | 0.458120E+09 | 0.00 | 0.00 |
October | 0.102700E+10 | 0.543751E+09 | 0.104528E+10 | 0.655907E+09 | 0.389369E+09 | 0.00 | 0.00 |
November | 0.645396E+09 | 0.788840E+09 | 0.762885E+09 | 0.477560E+09 | 0.285324E+09 | 0.00 | 0.00 |
December | 0.746715E+09 | 0.116874E+10 | 0.840344E+09 | 0.636469E+09 | 0.203875E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.907946E+10 | 0.717058E+10 | 0.103638E+11 | 0.535471E+10 | 0.500912E+10 | 0.00 | 0.00 |
Minimum of Months | 0.569899E+09 | 0.198846E+09 | 0.669925E+09 | 0.136310E+09 | 0.203875E+09 | 0.00 | 0.00 |
Maximum of Months | 0.102700E+10 | 0.127612E+10 | 0.104528E+10 | 0.701017E+09 | 0.548248E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -12.6 | -13.1 | -15.2 | 6.10 | -26.1 | 37.55 | 107.22 | 0.02 |
February | -7.7 | -8.6 | -10.9 | 6.39 | -21.3 | 45.57 | 135.04 | 0.00 |
March | 0.33 | -1.3 | -4.2 | 6.99 | -10.6 | 74.69 | 127.11 | 0.00 |
April | 7.02 | 4.42 | 1.63 | 6.38 | -3.6 | 77.59 | 184.47 | 0.02 |
May | 14.19 | 11.29 | 8.94 | 5.14 | 4.69 | 102.33 | 182.89 | 0.00 |
June | 19.16 | 15.70 | 13.79 | 4.87 | 8.84 | 110.26 | 213.51 | 0.04 |
July | 20.92 | 17.86 | 16.31 | 4.22 | 9.95 | 102.99 | 231.93 | 0.03 |
August | 20.05 | 16.99 | 15.28 | 4.97 | 11.01 | 95.97 | 190.14 | 0.00 |
September | 15.39 | 11.23 | 8.10 | 4.97 | 3.17 | 72.67 | 177.74 | 0.01 |
October | 7.43 | 4.70 | 1.56 | 5.55 | -3.9 | 55.50 | 131.91 | 0.00 |
November | -0.0 | -1.4 | -3.9 | 6.30 | -10.9 | 41.35 | 79.05 | 0.00 |
December | -7.6 | -8.4 | -10.6 | 6.09 | -20.0 | 22.97 | 92.59 | 0.00 |
Annual Sum or Average | 6.46 | 4.18 | 1.81 | 5.66 | -4.8 | 70.09 | 154.52 | 0.01 |
Minimum of Months | -12.6 | -13.1 | -15.2 | 4.22 | -26.1 | 22.97 | 79.05 | 0.00 |
Maximum of Months | 20.92 | 17.86 | 16.31 | 6.99 | 11.01 | 110.26 | 231.93 | 0.04 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 6.10 | 17-JAN-23:19 | 3.74 | 0.93 | 10.63 | -0.4 | 0.00 | 0.00 |
February | 8.30 | 24-FEB-14:00 | 5.61 | 2.80 | 5.20 | -7.3 | 71.00 | 794.50 |
March | 18.90 | 19-MAR-15:00 | 13.92 | 10.60 | 8.80 | 7.95 | 139.50 | 237.50 |
April | 30.00 | 15-APR-15:20 | 19.10 | 13.53 | 12.70 | 15.70 | 115.83 | 790.83 |
May | 30.00 | 31-MAY-12:00 | 19.68 | 14.40 | 6.20 | 19.52 | 251.00 | 580.50 |
June | 33.30 | 11-JUN-14:00 | 24.80 | 21.70 | 10.30 | 24.50 | 281.00 | 458.50 |
July | 30.00 | 26-JUL-15:20 | 25.66 | 24.23 | 5.13 | 20.98 | 260.33 | 436.00 |
August | 33.90 | 04-AUG-14:00 | 25.30 | 22.20 | 4.60 | 23.82 | 194.50 | 612.00 |
September | 32.20 | 06-SEP-13:00 | 21.17 | 16.10 | 6.20 | 18.28 | 135.00 | 769.00 |
October | 23.30 | 20-OCT-14:00 | 13.34 | 5.60 | 7.20 | 7.35 | 55.00 | 745.50 |
November | 16.10 | 03-NOV-13:00 | 10.46 | 5.60 | 6.70 | 0.51 | 82.00 | 691.00 |
December | 7.20 | 02-DEC-13:00 | 3.93 | 0.00 | 7.70 | -3.9 | 75.00 | 301.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.10 | 3.74 | 0.00 | 4.60 | -7.3 | 0.00 | 0.00 | |
Maximum of Months | 33.90 | 25.66 | 24.23 | 12.70 | 24.50 | 281.00 | 794.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -31.1 | 31-JAN-03:00 | -31.3 | -34.4 | 4.60 | -46.7 | 0.00 | 0.00 |
February | -36.7 | 02-FEB-05:00 | -36.8 | -40.2 | 3.10 | -59.6 | 0.00 | 0.00 |
March | -17.2 | 06-MAR-00:00 | -17.6 | -20.0 | 5.20 | -36.8 | 0.00 | 0.00 |
April | -7.2 | 03-APR-05:19 | -8.0 | -9.8 | 7.37 | -15.9 | 0.00 | 0.00 |
May | 0.60 | 03-MAY-02:00 | -0.0 | -1.1 | 1.50 | -15.5 | 0.00 | 0.00 |
June | 5.00 | 01-JUN-04:00 | 5.00 | 5.00 | 3.10 | -7.8 | 30.50 | 132.50 |
July | 10.00 | 23-JUL-03:00 | 9.66 | 9.40 | 2.60 | -4.3 | 0.00 | 0.00 |
August | 8.30 | 07-AUG-03:00 | 7.41 | 6.70 | 3.10 | -3.2 | 0.00 | 0.00 |
September | -1.1 | 30-SEP-00:00 | -2.4 | -4.4 | 4.10 | -17.8 | 0.00 | 0.00 |
October | -3.3 | 23-OCT-05:00 | -4.2 | -6.1 | 3.60 | -19.1 | 0.00 | 0.00 |
November | -28.9 | 26-NOV-06:00 | -29.0 | -30.6 | 1.50 | -50.2 | 0.00 | 0.00 |
December | -22.8 | 09-DEC-00:20 | -23.0 | -25.0 | 13.40 | -37.7 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -36.7 | -36.8 | -40.2 | 1.50 | -59.6 | 0.00 | 0.00 | |
Maximum of Months | 10.00 | 9.66 | 9.40 | 13.40 | -3.2 | 30.50 | 132.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 5.60 | 18-JAN-00:00 | 5.60 | 5.60 | 7.70 | 0.30 | 0.00 | 0.00 |
February | 5.87 | 24-FEB-15:00 | 8.30 | 3.30 | 5.70 | -7.3 | 54.50 | 665.50 |
March | 13.92 | 19-MAR-15:00 | 18.90 | 10.60 | 8.80 | 7.95 | 139.50 | 237.50 |
April | 20.93 | 18-APR-11:00 | 27.80 | 17.80 | 13.90 | 17.57 | 334.00 | 447.00 |
May | 19.92 | 29-MAY-13:00 | 23.30 | 18.30 | 6.20 | 20.75 | 379.00 | 52.00 |
June | 24.80 | 11-JUN-14:00 | 33.30 | 21.70 | 10.30 | 24.50 | 281.00 | 458.50 |
July | 26.15 | 26-JUL-18:00 | 27.80 | 25.60 | 3.10 | 19.35 | 33.50 | 51.00 |
August | 26.63 | 04-AUG-12:00 | 31.70 | 25.00 | 4.60 | 25.66 | 235.00 | 593.50 |
September | 21.17 | 06-SEP-13:00 | 32.20 | 16.10 | 6.20 | 18.28 | 135.00 | 769.00 |
October | 14.83 | 02-OCT-14:00 | 18.30 | 12.80 | 3.60 | 12.41 | 202.00 | 164.00 |
November | 13.03 | 09-NOV-04:00 | 15.00 | 11.70 | 10.30 | 10.88 | 0.00 | 0.00 |
December | 3.93 | 02-DEC-13:00 | 7.20 | 0.00 | 7.70 | -3.9 | 75.00 | 301.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 3.93 | 5.60 | 0.00 | 3.10 | -7.3 | 0.00 | 0.00 | |
Maximum of Months | 26.63 | 33.30 | 25.60 | 13.90 | 25.66 | 379.00 | 769.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 5.60 | 18-JAN-00:00 | 5.60 | 5.60 | 7.70 | 0.30 | 0.00 | 0.00 |
February | 3.30 | 24-FEB-15:00 | 8.30 | 5.87 | 5.70 | -7.3 | 54.50 | 665.50 |
March | 11.10 | 26-MAR-05:00 | 13.30 | 12.04 | 8.20 | 9.13 | 0.00 | 0.00 |
April | 18.30 | 18-APR-09:00 | 25.60 | 20.52 | 14.40 | 15.57 | 196.00 | 741.50 |
May | 18.30 | 29-MAY-13:00 | 23.30 | 19.92 | 6.20 | 20.75 | 379.00 | 52.00 |
June | 22.20 | 13-JUN-11:00 | 26.70 | 23.34 | 8.80 | 16.85 | 273.50 | 600.50 |
July | 25.60 | 26-JUL-18:00 | 27.80 | 26.15 | 3.10 | 19.35 | 33.50 | 51.00 |
August | 25.00 | 04-AUG-12:00 | 31.70 | 26.63 | 4.60 | 25.66 | 235.00 | 593.50 |
September | 18.30 | 12-SEP-02:00 | 18.90 | 18.46 | 5.70 | 14.28 | 0.00 | 0.00 |
October | 12.80 | 02-OCT-13:00 | 17.40 | 14.50 | 3.40 | 11.65 | 249.50 | 141.50 |
November | 11.70 | 08-NOV-10:00 | 13.90 | 12.62 | 7.20 | 9.91 | 158.00 | 0.50 |
December | 0.00 | 02-DEC-11:00 | 5.00 | 2.78 | 7.20 | -8.3 | 115.50 | 562.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 0.00 | 5.00 | 2.78 | 3.10 | -8.3 | 0.00 | 0.00 | |
Maximum of Months | 25.60 | 31.70 | 26.63 | 14.40 | 25.66 | 379.00 | 741.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 4.29 | 14.52 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 3.18 | 19.75 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 3.75 | 28.43 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 5.88 | 38.20 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 9.06 | 44.89 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 12.40 | 51.07 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 15.02 | 51.61 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 16.22 | 43.31 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 15.63 | 34.41 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 13.44 | 22.83 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 10.25 | 13.98 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 6.92 | 10.24 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 9.71 | 31.16 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 3.18 | 10.24 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 16.22 | 51.61 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK1
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.395575E+09 | -268561394.1 | 0.00 | 0.00 | 744.00 | 0.00 | -127013796.2 | 58.99 | 0.00 | 0.00 |
February | 0.363011E+09 | -248805652.8 | 0.00 | 0.00 | 672.00 | 0.00 | -114205230.8 | 58.99 | 0.00 | 0.00 |
March | 0.402227E+09 | -276974583.9 | 0.00 | 0.00 | 744.00 | 0.00 | -125252743.4 | 58.99 | 0.00 | 0.00 |
April | 0.373117E+09 | -254729997.4 | 0.00 | 0.00 | 720.00 | 0.00 | -118386643.9 | 59.00 | 0.00 | 0.00 |
May | 0.363863E+09 | -247768975.8 | 0.00 | 0.00 | 744.00 | 0.00 | -116093911.9 | 58.99 | 0.00 | 0.00 |
June | 0.335825E+09 | -225753174.9 | 0.00 | 0.00 | 720.00 | 0.00 | -110071903.2 | 58.99 | 0.00 | 0.00 |
July | 0.328423E+09 | -215989298.1 | 0.00 | 0.00 | 744.00 | 0.00 | -112433912.5 | 58.99 | 0.00 | 0.00 |
August | 0.326805E+09 | -214294630.2 | 0.00 | 0.00 | 744.00 | 0.00 | -112509889.6 | 58.99 | 0.00 | 0.00 |
September | 0.319191E+09 | -208175078.4 | 0.00 | 0.00 | 720.00 | 0.00 | -111016095.7 | 58.99 | 0.00 | 0.00 |
October | 0.344461E+09 | -223672471.0 | 0.00 | 0.00 | 744.00 | 0.00 | -120788873.3 | 58.99 | 0.00 | 0.00 |
November | 0.350682E+09 | -230937287.5 | 0.00 | 0.00 | 720.00 | 0.00 | -119745042.8 | 58.99 | 0.00 | 0.00 |
December | 0.382389E+09 | -255963478.4 | 0.00 | 0.00 | 744.00 | 0.00 | -126425231.0 | 59.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.428557E+10 | -.287163E+10 | 8760.00 | -.141394E+10 | 58.99 | |||||
Minimum of Months | 0.319191E+09 | -276974583.9 | 0.00 | 0.00 | 672.00 | 0.00 | -127013796.2 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.402227E+09 | -208175078.4 | 0.00 | 0.00 | 744.00 | 0.00 | -110071903.2 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK2
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.394381E+09 | -268561576.8 | 0.00 | 0.00 | 744.00 | 0.00 | -125819803.4 | 58.99 | 0.00 | 0.00 |
February | 0.361588E+09 | -248804676.4 | 0.00 | 0.00 | 672.00 | 0.00 | -112782929.9 | 58.99 | 0.00 | 0.00 |
March | 0.400106E+09 | -276979157.2 | 0.00 | 0.00 | 744.00 | 0.00 | -123126575.4 | 58.99 | 0.00 | 0.00 |
April | 0.370989E+09 | -254722833.7 | 0.00 | 0.00 | 720.00 | 0.00 | -116266088.3 | 59.00 | 0.00 | 0.00 |
May | 0.362708E+09 | -247775160.9 | 0.00 | 0.00 | 744.00 | 0.00 | -114933004.8 | 58.99 | 0.00 | 0.00 |
June | 0.335228E+09 | -225759861.1 | 0.00 | 0.00 | 720.00 | 0.00 | -109467837.2 | 58.99 | 0.00 | 0.00 |
July | 0.328122E+09 | -215982762.0 | 0.00 | 0.00 | 744.00 | 0.00 | -112138984.4 | 58.99 | 0.00 | 0.00 |
August | 0.326511E+09 | -214293217.8 | 0.00 | 0.00 | 744.00 | 0.00 | -112217372.8 | 58.99 | 0.00 | 0.00 |
September | 0.318508E+09 | -208168070.4 | 0.00 | 0.00 | 720.00 | 0.00 | -110339832.1 | 58.99 | 0.00 | 0.00 |
October | 0.342373E+09 | -223684800.6 | 0.00 | 0.00 | 744.00 | 0.00 | -118687858.5 | 58.99 | 0.00 | 0.00 |
November | 0.348893E+09 | -230929980.5 | 0.00 | 0.00 | 720.00 | 0.00 | -117962741.3 | 58.99 | 0.00 | 0.00 |
December | 0.380739E+09 | -255980012.4 | 0.00 | 0.00 | 744.00 | 0.00 | -124758575.5 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.427014E+10 | -.287164E+10 | 8760.00 | -.139850E+10 | 58.99 | |||||
Minimum of Months | 0.318508E+09 | -276979157.2 | 0.00 | 0.00 | 672.00 | 0.00 | -125819803.4 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.400106E+09 | -208168070.4 | 0.00 | 0.00 | 744.00 | 0.00 | -109467837.2 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK3
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.364718E+09 | -236160078.6 | 0.00 | 0.00 | 744.00 | 0.00 | -128557615.7 | 59.00 | 0.00 | 0.00 |
February | 0.334064E+09 | -218955447.6 | 0.00 | 0.00 | 672.00 | 0.00 | -115108952.2 | 58.99 | 0.00 | 0.00 |
March | 0.372842E+09 | -247350832.1 | 0.00 | 0.00 | 744.00 | 0.00 | -125491368.5 | 59.00 | 0.00 | 0.00 |
April | 0.342001E+09 | -223863252.8 | 0.00 | 0.00 | 720.00 | 0.00 | -118137535.0 | 58.99 | 0.00 | 0.00 |
May | 0.335640E+09 | -219769514.3 | 0.00 | 0.00 | 744.00 | 0.00 | -115870702.0 | 58.99 | 0.00 | 0.00 |
June | 0.310184E+09 | -201213155.3 | 0.00 | 0.00 | 720.00 | 0.00 | -108970811.5 | 58.99 | 0.00 | 0.00 |
July | 0.299508E+09 | -188659692.1 | 0.00 | 0.00 | 744.00 | 0.00 | -110848474.2 | 58.99 | 0.00 | 0.00 |
August | 0.302796E+09 | -191549172.6 | 0.00 | 0.00 | 744.00 | 0.00 | -111247194.8 | 58.99 | 0.00 | 0.00 |
September | 0.293294E+09 | -182821762.1 | 0.00 | 0.00 | 720.00 | 0.00 | -110471818.9 | 58.99 | 0.00 | 0.00 |
October | 0.317891E+09 | -196717521.5 | 0.00 | 0.00 | 744.00 | 0.00 | -121173183.3 | 58.99 | 0.00 | 0.00 |
November | 0.324487E+09 | -203885866.2 | 0.00 | 0.00 | 720.00 | 0.00 | -120601175.8 | 59.00 | 0.00 | 0.00 |
December | 0.350761E+09 | -223425714.8 | 0.00 | 0.00 | 744.00 | 0.00 | -127335648.2 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.394819E+10 | -.253437E+10 | 8760.00 | -.141381E+10 | 58.99 | |||||
Minimum of Months | 0.293294E+09 | -247350832.1 | 0.00 | 0.00 | 672.00 | 0.00 | -128557615.7 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.372842E+09 | -182821762.1 | 0.00 | 0.00 | 744.00 | 0.00 | -108970811.5 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK4
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.365175E+09 | -236159854.4 | 0.00 | 0.00 | 744.00 | 0.00 | -129014992.5 | 59.00 | 0.00 | 0.00 |
February | 0.334502E+09 | -218955468.3 | 0.00 | 0.00 | 672.00 | 0.00 | -115546067.2 | 59.00 | 0.00 | 0.00 |
March | 0.373385E+09 | -247362512.6 | 0.00 | 0.00 | 744.00 | 0.00 | -126022892.8 | 59.00 | 0.00 | 0.00 |
April | 0.342528E+09 | -223878245.3 | 0.00 | 0.00 | 720.00 | 0.00 | -118649845.6 | 58.99 | 0.00 | 0.00 |
May | 0.336209E+09 | -219768745.9 | 0.00 | 0.00 | 744.00 | 0.00 | -116440119.4 | 58.99 | 0.00 | 0.00 |
June | 0.310408E+09 | -201210869.0 | 0.00 | 0.00 | 720.00 | 0.00 | -109196976.3 | 58.99 | 0.00 | 0.00 |
July | 0.299580E+09 | -188668149.3 | 0.00 | 0.00 | 744.00 | 0.00 | -110911953.5 | 58.99 | 0.00 | 0.00 |
August | 0.302885E+09 | -191544518.2 | 0.00 | 0.00 | 744.00 | 0.00 | -111340012.5 | 58.99 | 0.00 | 0.00 |
September | 0.293576E+09 | -182831298.4 | 0.00 | 0.00 | 720.00 | 0.00 | -110744514.8 | 58.99 | 0.00 | 0.00 |
October | 0.318548E+09 | -196723124.1 | 0.00 | 0.00 | 744.00 | 0.00 | -121825101.9 | 58.99 | 0.00 | 0.00 |
November | 0.325105E+09 | -203903735.5 | 0.00 | 0.00 | 720.00 | 0.00 | -121201036.3 | 58.99 | 0.00 | 0.00 |
December | 0.351258E+09 | -223422683.2 | 0.00 | 0.00 | 744.00 | 0.00 | -127835578.0 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.395316E+10 | -.253443E+10 | 8760.00 | -.141873E+10 | 58.99 | |||||
Minimum of Months | 0.293576E+09 | -247362512.6 | 0.00 | 0.00 | 672.00 | 0.00 | -129014992.5 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.373385E+09 | -182831298.4 | 0.00 | 0.00 | 744.00 | 0.00 | -109196976.3 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK5
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.353622E+09 | -223222740.4 | 0.00 | 0.00 | 744.00 | 0.00 | -130398761.6 | 58.99 | 0.00 | 0.00 |
February | 0.323945E+09 | -207054885.2 | 0.00 | 0.00 | 672.00 | 0.00 | -116889763.0 | 59.00 | 0.00 | 0.00 |
March | 0.361625E+09 | -234072573.1 | 0.00 | 0.00 | 744.00 | 0.00 | -127552213.5 | 58.99 | 0.00 | 0.00 |
April | 0.331828E+09 | -211844494.4 | 0.00 | 0.00 | 720.00 | 0.00 | -119983300.9 | 59.00 | 0.00 | 0.00 |
May | 0.325503E+09 | -207821647.4 | 0.00 | 0.00 | 744.00 | 0.00 | -117681005.5 | 59.00 | 0.00 | 0.00 |
June | 0.300367E+09 | -190377256.2 | 0.00 | 0.00 | 720.00 | 0.00 | -109990142.6 | 58.99 | 0.00 | 0.00 |
July | 0.289982E+09 | -178411962.6 | 0.00 | 0.00 | 744.00 | 0.00 | -111570225.2 | 59.00 | 0.00 | 0.00 |
August | 0.293167E+09 | -181204465.3 | 0.00 | 0.00 | 744.00 | 0.00 | -111962990.3 | 59.01 | 0.00 | 0.00 |
September | 0.284357E+09 | -173041365.1 | 0.00 | 0.00 | 720.00 | 0.00 | -111315596.1 | 58.98 | 0.00 | 0.00 |
October | 0.308919E+09 | -185916555.3 | 0.00 | 0.00 | 744.00 | 0.00 | -123002322.3 | 59.00 | 0.00 | 0.00 |
November | 0.315157E+09 | -192582122.0 | 0.00 | 0.00 | 720.00 | 0.00 | -122574864.1 | 58.99 | 0.00 | 0.00 |
December | 0.340746E+09 | -211277046.3 | 0.00 | 0.00 | 744.00 | 0.00 | -129469101.2 | 59.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.382922E+10 | -.239683E+10 | 8760.00 | -.143239E+10 | 58.99 | |||||
Minimum of Months | 0.284357E+09 | -234072573.1 | 0.00 | 0.00 | 672.00 | 0.00 | -130398761.6 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.361625E+09 | -173041365.1 | 0.00 | 0.00 | 744.00 | 0.00 | -109990142.6 | 59.01 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK6
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.353514E+09 | -223219885.1 | 0.00 | 0.00 | 744.00 | 0.00 | -130293962.0 | 58.99 | 0.00 | 0.00 |
February | 0.323835E+09 | -207061704.3 | 0.00 | 0.00 | 672.00 | 0.00 | -116772861.8 | 58.99 | 0.00 | 0.00 |
March | 0.361529E+09 | -234068024.6 | 0.00 | 0.00 | 744.00 | 0.00 | -127461013.4 | 58.99 | 0.00 | 0.00 |
April | 0.331822E+09 | -211850223.3 | 0.00 | 0.00 | 720.00 | 0.00 | -119971986.2 | 58.99 | 0.00 | 0.00 |
May | 0.325796E+09 | -207847540.1 | 0.00 | 0.00 | 744.00 | 0.00 | -117948959.0 | 58.99 | 0.00 | 0.00 |
June | 0.300545E+09 | -190381483.9 | 0.00 | 0.00 | 720.00 | 0.00 | -110163267.3 | 58.99 | 0.00 | 0.00 |
July | 0.290114E+09 | -178407131.7 | 0.00 | 0.00 | 744.00 | 0.00 | -111706642.7 | 59.00 | 0.00 | 0.00 |
August | 0.293321E+09 | -181176268.7 | 0.00 | 0.00 | 744.00 | 0.00 | -112144998.4 | 59.02 | 0.00 | 0.00 |
September | 0.284577E+09 | -173016191.9 | 0.00 | 0.00 | 720.00 | 0.00 | -111560491.1 | 58.99 | 0.00 | 0.00 |
October | 0.308945E+09 | -185943843.1 | 0.00 | 0.00 | 744.00 | 0.00 | -123000725.8 | 58.99 | 0.00 | 0.00 |
November | 0.315119E+09 | -192571464.5 | 0.00 | 0.00 | 720.00 | 0.00 | -122547732.9 | 58.99 | 0.00 | 0.00 |
December | 0.340597E+09 | -211319445.6 | 0.00 | 0.00 | 744.00 | 0.00 | -129277896.9 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.382971E+10 | -.239686E+10 | 8760.00 | -.143285E+10 | 58.99 | |||||
Minimum of Months | 0.284577E+09 | -234068024.6 | 0.00 | 0.00 | 672.00 | 0.00 | -130293962.0 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.361529E+09 | -173016191.9 | 0.00 | 0.00 | 744.00 | 0.00 | -110163267.3 | 59.02 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK7
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.353538E+09 | -223221447.1 | 0.00 | 0.00 | 744.00 | 0.00 | -130316377.5 | 58.99 | 0.00 | 0.00 |
February | 0.323884E+09 | -207060203.6 | 0.00 | 0.00 | 672.00 | 0.00 | -116823600.9 | 58.99 | 0.00 | 0.00 |
March | 0.361621E+09 | -234075024.8 | 0.00 | 0.00 | 744.00 | 0.00 | -127545732.9 | 58.99 | 0.00 | 0.00 |
April | 0.331982E+09 | -211846840.8 | 0.00 | 0.00 | 720.00 | 0.00 | -120134918.0 | 58.99 | 0.00 | 0.00 |
May | 0.326139E+09 | -207825345.4 | 0.00 | 0.00 | 744.00 | 0.00 | -118313171.4 | 59.00 | 0.00 | 0.00 |
June | 0.300695E+09 | -190387965.8 | 0.00 | 0.00 | 720.00 | 0.00 | -110306850.3 | 58.99 | 0.00 | 0.00 |
July | 0.290185E+09 | -178434407.4 | 0.00 | 0.00 | 744.00 | 0.00 | -111750804.1 | 58.99 | 0.00 | 0.00 |
August | 0.293389E+09 | -181232696.6 | 0.00 | 0.00 | 744.00 | 0.00 | -112156361.6 | 59.00 | 0.00 | 0.00 |
September | 0.284705E+09 | -173039150.8 | 0.00 | 0.00 | 720.00 | 0.00 | -111665974.1 | 58.98 | 0.00 | 0.00 |
October | 0.309078E+09 | -185942982.3 | 0.00 | 0.00 | 744.00 | 0.00 | -123134558.0 | 58.99 | 0.00 | 0.00 |
November | 0.315213E+09 | -192567869.4 | 0.00 | 0.00 | 720.00 | 0.00 | -122645342.2 | 59.00 | 0.00 | 0.00 |
December | 0.340653E+09 | -211313859.3 | 0.00 | 0.00 | 744.00 | 0.00 | -129339301.1 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.383108E+10 | -.239695E+10 | 8760.00 | -.143413E+10 | 58.99 | |||||
Minimum of Months | 0.284705E+09 | -234075024.8 | 0.00 | 0.00 | 672.00 | 0.00 | -130316377.5 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.361621E+09 | -173039150.8 | 0.00 | 0.00 | 744.00 | 0.00 | -110306850.3 | 59.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 214.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 226.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 334.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 285.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 428.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 400.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 414.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 410.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 326.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 325.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 254.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 186.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3807.33 | ||||||||||
Minimum of Months | 186.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 428.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.497630E+11 | 81662.66 | 01-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.352084E+11 | 81662.66 | 01-FEB-00:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.218609E+11 | 81662.66 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.102845E+11 | 81662.66 | 01-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.431105E+09 | 81662.66 | 01-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6690802.95 | 2589.41 | 03-JUN-08:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.351630E+09 | 81662.66 | 29-SEP-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.360318E+10 | 81662.66 | 06-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.203724E+11 | 81662.66 | 10-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.383970E+11 | 81662.66 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.180279E+12 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.497630E+11 | 81662.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.209245E+11 | 41257.18 | 01-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.146503E+11 | 41257.18 | 01-FEB-00:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.860727E+10 | 41257.18 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.396493E+10 | 41257.18 | 01-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.129382E+09 | 41257.18 | 02-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 3445834.21 | 1249.30 | 03-JUN-07:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.108327E+09 | 38215.90 | 30-SEP-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.128152E+10 | 41257.18 | 17-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.828537E+10 | 41257.18 | 10-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.158915E+11 | 41257.18 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.738465E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.209245E+11 | 41257.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_3:3_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.231908E+11 | 41437.20 | 01-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.164723E+11 | 41437.20 | 01-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.104280E+11 | 41437.20 | 01-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.510332E+10 | 41437.20 | 01-APR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.307790E+09 | 41437.20 | 02-MAY-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 40690054.17 | 2014.91 | 03-JUN-06:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.296852E+09 | 38092.16 | 30-SEP-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.239331E+10 | 41437.20 | 08-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.980139E+10 | 41437.20 | 10-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.180805E+11 | 41437.20 | 01-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.861150E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.231908E+11 | 41437.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_4:4_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.237180E+11 | 41502.31 | 01-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.168858E+11 | 41502.31 | 01-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.107926E+11 | 41502.31 | 01-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.534746E+10 | 41502.31 | 01-APR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.365458E+09 | 41502.31 | 02-MAY-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 67957012.06 | 2917.31 | 03-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.359935E+09 | 41502.31 | 30-SEP-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.269585E+10 | 41502.31 | 08-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.101953E+11 | 41502.31 | 10-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.185385E+11 | 41502.31 | 01-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.889670E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.237180E+11 | 41502.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_5:5_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.241708E+11 | 41660.15 | 01-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.172697E+11 | 41660.15 | 01-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.111645E+11 | 41660.15 | 01-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.558559E+10 | 41660.15 | 01-APR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.418900E+09 | 41660.15 | 01-MAY-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 87705704.00 | 4339.11 | 05-JUN-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.411408E+09 | 41660.15 | 30-SEP-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.292924E+10 | 41660.15 | 08-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.105132E+11 | 41660.15 | 10-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.189562E+11 | 41660.15 | 01-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.915074E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.241708E+11 | 41660.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_6:6_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.428035E+11 | 79286.24 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.304947E+11 | 79286.24 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.197677E+11 | 79286.24 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.983939E+10 | 79286.24 | 01-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.594334E+09 | 79286.24 | 01-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.122067E+09 | 31790.06 | 05-JUN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.677448E+09 | 79286.24 | 28-SEP-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.511194E+10 | 79286.24 | 01-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.186734E+11 | 79286.24 | 05-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.335939E+11 | 79286.24 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.161678E+12 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.428035E+11 | 79286.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_7:7_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.237360E+11 | 42061.63 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.169960E+11 | 42061.63 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.110654E+11 | 42061.63 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.562432E+10 | 42061.63 | 01-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.438749E+09 | 42061.63 | 01-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.110348E+09 | 21669.17 | 05-JUN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.449704E+09 | 42061.63 | 28-SEP-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.309374E+10 | 42061.63 | 01-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.104558E+11 | 42061.63 | 05-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.186088E+11 | 42061.63 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.905789E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.237360E+11 | 42061.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_8:8_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.237902E+11 | 42037.50 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.170536E+11 | 42037.50 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.111632E+11 | 42037.50 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.571510E+10 | 42037.50 | 01-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.474721E+09 | 42037.50 | 01-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124150E+09 | 26243.50 | 05-JUN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.475607E+09 | 42037.50 | 28-SEP-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.318510E+10 | 42037.50 | 01-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.105396E+11 | 42037.50 | 05-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.186725E+11 | 42037.50 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.911937E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.237902E+11 | 42037.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_9:9_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.243088E+11 | 42281.06 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.175001E+11 | 42281.06 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.116197E+11 | 42281.06 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.609500E+10 | 42281.06 | 01-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.599222E+09 | 42281.06 | 01-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.167120E+09 | 39788.38 | 05-JUN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.550823E+09 | 42281.06 | 27-SEP-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.347270E+10 | 42281.06 | 01-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.109041E+11 | 42281.06 | 01-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.191054E+11 | 42281.06 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.943230E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.243088E+11 | 42281.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_10:10_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.309573E+11 | 46104.04 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.224846E+11 | 46104.04 | 01-FEB-01:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.153597E+11 | 46104.04 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.829702E+10 | 46104.04 | 01-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.113964E+10 | 46104.04 | 01-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.335417E+09 | 46104.04 | 02-JUN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.809503E+09 | 46104.04 | 25-SEP-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.443739E+10 | 46104.04 | 01-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.136570E+11 | 46104.04 | 01-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.238918E+11 | 46104.04 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.121369E+12 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.309573E+11 | 46104.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 640.03 | 481.88 | 0.48 | 19-MAR-17:50 | 0.36 | 0.00 |
April | 0.00 | 0.00 | 0.257723E+10 | 0.180419E+10 | 27358.79 | 16-APR-16:10 | 19620.85 | 0.00 |
May | 0.00 | 0.00 | 0.433135E+10 | 0.303237E+10 | 26718.10 | 31-MAY-15:00 | 21192.80 | 0.00 |
June | 0.00 | 0.00 | 0.198725E+11 | 0.135169E+11 | 61330.92 | 26-JUN-07:02 | 33084.61 | 0.00 |
July | 0.00 | 0.00 | 0.273725E+11 | 0.173264E+11 | 60637.02 | 07-JUL-07:03 | 26933.10 | 0.00 |
August | 0.00 | 0.00 | 0.245592E+11 | 0.159154E+11 | 62929.30 | 03-AUG-07:02 | 29658.72 | 0.00 |
September | 0.00 | 0.00 | 0.114965E+11 | 0.918420E+10 | 52860.94 | 11-SEP-07:03 | 29222.12 | 0.00 |
October | 0.00 | 0.00 | 0.113107E+09 | 0.103810E+09 | 9568.85 | 20-OCT-15:00 | 9111.04 | 0.00 |
November | 0.00 | 0.00 | 8931.74 | 8043.56 | 1.55 | 03-NOV-14:40 | 1.41 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.903224E+11 | 0.608833E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.273725E+11 | 0.173264E+11 | 62929.30 | 33084.61 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 68624199.46 | 59272550.24 | 2198.97 | 19-MAR-17:10 | 1787.74 | 0.00 |
April | 0.00 | 0.00 | 0.188677E+10 | 0.144846E+10 | 14389.20 | 18-APR-14:00 | 10052.25 | 0.00 |
May | 0.00 | 0.00 | 0.505997E+10 | 0.391859E+10 | 14150.06 | 31-MAY-13:00 | 11138.35 | 0.00 |
June | 0.00 | 0.00 | 0.122471E+11 | 0.891580E+10 | 30570.23 | 26-JUN-07:02 | 17757.37 | 0.00 |
July | 0.00 | 0.00 | 0.161745E+11 | 0.112075E+11 | 30252.34 | 26-JUL-07:03 | 18153.21 | 0.00 |
August | 0.00 | 0.00 | 0.156119E+11 | 0.110138E+11 | 31251.23 | 03-AUG-07:02 | 16206.35 | 0.00 |
September | 0.00 | 0.00 | 0.815440E+10 | 0.686358E+10 | 29360.61 | 11-SEP-07:03 | 20289.10 | 0.00 |
October | 0.00 | 0.00 | 0.763114E+09 | 0.688051E+09 | 5697.80 | 20-OCT-15:00 | 5487.57 | 0.00 |
November | 0.00 | 0.00 | 0.160417E+09 | 0.142417E+09 | 3338.62 | 03-NOV-20:10 | 3338.62 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.601268E+11 | 0.442575E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.161745E+11 | 0.112075E+11 | 31251.23 | 20289.10 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.110572E+10 | 0.795604E+09 | 13359.53 | 18-APR-14:00 | 9218.71 | 0.00 |
May | 0.00 | 0.00 | 0.250704E+10 | 0.183991E+10 | 13414.53 | 31-MAY-13:00 | 10458.60 | 0.00 |
June | 0.00 | 0.00 | 0.864853E+10 | 0.604503E+10 | 31734.21 | 26-JUN-06:02 | 16473.94 | 0.00 |
July | 0.00 | 0.00 | 0.115659E+11 | 0.766278E+10 | 31894.44 | 27-JUL-06:03 | 15326.25 | 0.00 |
August | 0.00 | 0.00 | 0.114383E+11 | 0.775531E+10 | 32709.01 | 04-AUG-06:02 | 14128.84 | 0.00 |
September | 0.00 | 0.00 | 0.535546E+10 | 0.438172E+10 | 30195.50 | 11-SEP-06:03 | 19976.81 | 0.00 |
October | 0.00 | 0.00 | 0.150874E+09 | 0.135573E+09 | 4635.92 | 20-OCT-15:00 | 4438.67 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.407718E+11 | 0.286159E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.115659E+11 | 0.775531E+10 | 32709.01 | 19976.81 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.105752E+10 | 0.757404E+09 | 13161.19 | 18-APR-14:00 | 9061.51 | 0.00 |
May | 0.00 | 0.00 | 0.232291E+10 | 0.169889E+10 | 13263.80 | 31-MAY-13:00 | 10327.56 | 0.00 |
June | 0.00 | 0.00 | 0.852639E+10 | 0.595071E+10 | 31839.46 | 26-JUN-06:02 | 16528.41 | 0.00 |
July | 0.00 | 0.00 | 0.114444E+11 | 0.757197E+10 | 31999.53 | 27-JUL-06:03 | 15348.08 | 0.00 |
August | 0.00 | 0.00 | 0.113010E+11 | 0.765056E+10 | 32815.74 | 04-AUG-06:02 | 14157.45 | 0.00 |
September | 0.00 | 0.00 | 0.526221E+10 | 0.429889E+10 | 30292.72 | 11-SEP-06:03 | 20028.20 | 0.00 |
October | 0.00 | 0.00 | 0.122948E+09 | 0.111003E+09 | 4386.05 | 20-OCT-15:00 | 4196.50 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.400374E+11 | 0.280394E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.114444E+11 | 0.765056E+10 | 32815.74 | 20028.20 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.101214E+10 | 0.721771E+09 | 12966.66 | 18-APR-14:00 | 8906.50 | 0.00 |
May | 0.00 | 0.00 | 0.216320E+10 | 0.157748E+10 | 13090.58 | 31-MAY-13:00 | 10175.88 | 0.00 |
June | 0.00 | 0.00 | 0.834289E+10 | 0.580981E+10 | 32048.45 | 26-JUN-06:02 | 16572.17 | 0.00 |
July | 0.00 | 0.00 | 0.112263E+11 | 0.741127E+10 | 32211.11 | 27-JUL-06:03 | 15350.98 | 0.00 |
August | 0.00 | 0.00 | 0.110867E+11 | 0.748968E+10 | 33030.27 | 04-AUG-06:02 | 14159.70 | 0.00 |
September | 0.00 | 0.00 | 0.514854E+10 | 0.420100E+10 | 30061.55 | 11-SEP-06:03 | 19823.80 | 0.00 |
October | 0.00 | 0.00 | 0.104630E+09 | 94767826.50 | 4189.62 | 20-OCT-15:00 | 4005.64 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.390844E+11 | 0.273058E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.112263E+11 | 0.748968E+10 | 33030.27 | 19823.80 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.150799E+10 | 0.101910E+10 | 24006.52 | 18-APR-14:10 | 16280.17 | 0.00 |
May | 0.00 | 0.00 | 0.269008E+10 | 0.188773E+10 | 24358.68 | 31-MAY-15:00 | 18882.04 | 0.00 |
June | 0.00 | 0.00 | 0.132990E+11 | 0.891985E+10 | 60416.98 | 26-JUN-07:02 | 32333.69 | 0.00 |
July | 0.00 | 0.00 | 0.184059E+11 | 0.115533E+11 | 59497.44 | 07-JUL-07:03 | 26510.78 | 0.00 |
August | 0.00 | 0.00 | 0.175422E+11 | 0.113078E+11 | 61371.85 | 04-AUG-07:02 | 29812.19 | 0.00 |
September | 0.00 | 0.00 | 0.783465E+10 | 0.622857E+10 | 54068.77 | 11-SEP-07:03 | 30051.41 | 0.00 |
October | 0.00 | 0.00 | 50121131.03 | 46509303.45 | 6665.78 | 20-OCT-15:00 | 6252.62 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.613299E+11 | 0.409629E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.184059E+11 | 0.115533E+11 | 61371.85 | 32333.69 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.906409E+09 | 0.634269E+09 | 12530.08 | 18-APR-14:10 | 8505.81 | 0.00 |
May | 0.00 | 0.00 | 0.183633E+10 | 0.132296E+10 | 12777.50 | 31-MAY-15:00 | 9912.50 | 0.00 |
June | 0.00 | 0.00 | 0.782322E+10 | 0.538732E+10 | 33082.28 | 26-JUN-07:02 | 16977.72 | 0.00 |
July | 0.00 | 0.00 | 0.105468E+11 | 0.685898E+10 | 32763.83 | 27-JUL-07:02 | 16816.59 | 0.00 |
August | 0.00 | 0.00 | 0.104782E+11 | 0.698176E+10 | 33794.04 | 04-AUG-07:02 | 15160.57 | 0.00 |
September | 0.00 | 0.00 | 0.480422E+10 | 0.387851E+10 | 27644.59 | 11-SEP-07:03 | 17935.15 | 0.00 |
October | 0.00 | 0.00 | 76377820.56 | 68581371.62 | 3945.14 | 20-OCT-15:00 | 3711.22 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.364716E+11 | 0.251324E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.105468E+11 | 0.698176E+10 | 33794.04 | 17935.15 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.879739E+09 | 0.613346E+09 | 12351.59 | 18-APR-14:10 | 8364.08 | 0.00 |
May | 0.00 | 0.00 | 0.174784E+10 | 0.125703E+10 | 12644.55 | 31-MAY-15:00 | 9795.25 | 0.00 |
June | 0.00 | 0.00 | 0.770192E+10 | 0.529279E+10 | 33111.96 | 26-JUN-07:02 | 16940.69 | 0.00 |
July | 0.00 | 0.00 | 0.104097E+11 | 0.675635E+10 | 32798.97 | 27-JUL-07:02 | 16777.19 | 0.00 |
August | 0.00 | 0.00 | 0.103442E+11 | 0.687893E+10 | 33830.07 | 04-AUG-07:02 | 15126.57 | 0.00 |
September | 0.00 | 0.00 | 0.473066E+10 | 0.381371E+10 | 26683.17 | 11-SEP-07:03 | 17275.01 | 0.00 |
October | 0.00 | 0.00 | 71667348.97 | 64394101.12 | 3855.46 | 20-OCT-15:00 | 3623.52 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.358857E+11 | 0.246766E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.104097E+11 | 0.687893E+10 | 33830.07 | 17275.01 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.813987E+09 | 0.562975E+09 | 11909.32 | 18-APR-14:10 | 8020.09 | 0.00 |
May | 0.00 | 0.00 | 0.156105E+10 | 0.111876E+10 | 12345.41 | 31-MAY-15:00 | 9536.61 | 0.00 |
June | 0.00 | 0.00 | 0.742107E+10 | 0.507971E+10 | 33450.82 | 26-JUN-07:02 | 16952.18 | 0.00 |
July | 0.00 | 0.00 | 0.101072E+11 | 0.653724E+10 | 32983.94 | 05-JUL-07:02 | 17498.80 | 0.00 |
August | 0.00 | 0.00 | 0.100671E+11 | 0.667319E+10 | 34193.34 | 04-AUG-07:02 | 15183.61 | 0.00 |
September | 0.00 | 0.00 | 0.459336E+10 | 0.369544E+10 | 23535.30 | 11-SEP-07:03 | 15164.15 | 0.00 |
October | 0.00 | 0.00 | 61710523.54 | 55552984.28 | 3635.64 | 20-OCT-15:00 | 3412.39 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.346254E+11 | 0.237229E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.101072E+11 | 0.667319E+10 | 34193.34 | 17498.80 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.696827E+09 | 0.471648E+09 | 11411.20 | 18-APR-14:10 | 7599.32 | 0.00 |
May | 0.00 | 0.00 | 0.128371E+10 | 0.915464E+09 | 12227.35 | 31-MAY-13:00 | 9298.76 | 0.00 |
June | 0.00 | 0.00 | 0.707660E+10 | 0.481811E+10 | 26814.22 | 26-JUN-07:02 | 12715.58 | 0.00 |
July | 0.00 | 0.00 | 0.980045E+10 | 0.632637E+10 | 32993.86 | 04-JUL-08:62 | 17737.44 | 0.00 |
August | 0.00 | 0.00 | 0.990185E+10 | 0.655551E+10 | 39336.53 | 04-AUG-07:02 | 15350.63 | 0.00 |
September | 0.00 | 0.00 | 0.459132E+10 | 0.369299E+10 | 16616.06 | 06-SEP-14:10 | 12700.90 | 0.00 |
October | 0.00 | 0.00 | 51927085.42 | 47142523.46 | 3451.19 | 20-OCT-15:00 | 3239.97 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.334027E+11 | 0.228272E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.990185E+10 | 0.655551E+10 | 39336.53 | 17737.44 | 0.00 |
Report: FanReportMonthly
For: PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.485416E+10 | 0.72 | 2643.58 | 15-JAN-23:20 | 0.94 |
February | 0.437574E+10 | 0.69 | 2643.58 | 01-FEB-08:04 | 0.95 |
March | 0.481889E+10 | 0.66 | 2643.58 | 01-MAR-08:06 | 0.95 |
April | 0.465663E+10 | 0.64 | 2643.58 | 07-APR-20:27 | 0.94 |
May | 0.479681E+10 | 0.63 | 2643.58 | 01-MAY-07:40 | 0.94 |
June | 0.465376E+10 | 0.63 | 2643.58 | 02-JUN-08:50 | 0.94 |
July | 0.480603E+10 | 0.63 | 2643.58 | 01-JUL-07:40 | 0.93 |
August | 0.479652E+10 | 0.63 | 2643.58 | 01-AUG-08:70 | 0.92 |
September | 0.466328E+10 | 0.64 | 2643.58 | 01-SEP-07:30 | 0.93 |
October | 0.479667E+10 | 0.64 | 2643.58 | 01-OCT-07:30 | 0.94 |
November | 0.464455E+10 | 0.65 | 2643.58 | 04-NOV-08:65 | 0.94 |
December | 0.484397E+10 | 0.68 | 2643.58 | 31-DEC-11:00 | 0.94 |
Annual Sum or Average | 0.567070E+11 | 0.65 | |||
Minimum of Months | 0.437574E+10 | 0.63 | 2643.58 | 0.92 | |
Maximum of Months | 0.485416E+10 | 0.72 | 2643.58 | 0.95 |
Report: FanReportMonthly
For: PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.193862E+10 | 0.62 | 1399.10 | 01-JAN-08:07 | 0.98 |
February | 0.175009E+10 | 0.57 | 1399.10 | 01-FEB-07:20 | 0.99 |
March | 0.193758E+10 | 0.56 | 1399.10 | 01-MAR-08:05 | 0.99 |
April | 0.187190E+10 | 0.59 | 1399.10 | 01-APR-07:10 | 0.98 |
May | 0.201542E+10 | 0.70 | 1399.10 | 01-MAY-07:08 | 0.98 |
June | 0.201955E+10 | 0.70 | 1399.10 | 01-JUN-11:50 | 0.97 |
July | 0.209128E+10 | 0.70 | 1399.10 | 01-JUL-07:30 | 0.97 |
August | 0.210728E+10 | 0.69 | 1399.10 | 01-AUG-08:50 | 0.97 |
September | 0.196679E+10 | 0.70 | 1399.10 | 01-SEP-10:30 | 0.97 |
October | 0.192908E+10 | 0.64 | 1399.10 | 01-OCT-07:06 | 0.98 |
November | 0.185971E+10 | 0.58 | 1399.10 | 01-NOV-07:02 | 0.98 |
December | 0.190435E+10 | 0.55 | 1399.10 | 01-DEC-08:04 | 0.98 |
Annual Sum or Average | 0.233916E+11 | 0.63 | |||
Minimum of Months | 0.175009E+10 | 0.55 | 1399.10 | 0.97 | |
Maximum of Months | 0.210728E+10 | 0.70 | 1399.10 | 0.99 |
Report: FanReportMonthly
For: PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.205253E+10 | 0.57 | 1408.51 | 01-JAN-08:05 | 0.98 |
February | 0.185575E+10 | 0.56 | 1408.51 | 07-FEB-13:40 | 0.98 |
March | 0.207967E+10 | 0.54 | 1408.51 | 10-MAR-07:07 | 0.98 |
April | 0.197755E+10 | 0.53 | 1408.51 | 02-APR-07:08 | 0.98 |
May | 0.205869E+10 | 0.53 | 1408.51 | 01-MAY-07:10 | 0.98 |
June | 0.200798E+10 | 0.53 | 1408.51 | 01-JUN-09:20 | 0.98 |
July | 0.202826E+10 | 0.52 | 1408.51 | 06-JUL-06:50 | 0.97 |
August | 0.207897E+10 | 0.53 | 1408.51 | 06-AUG-10:00 | 0.97 |
September | 0.197755E+10 | 0.53 | 1408.51 | 04-SEP-09:10 | 0.97 |
October | 0.203840E+10 | 0.53 | 1408.51 | 05-OCT-14:50 | 0.98 |
November | 0.197861E+10 | 0.54 | 1408.51 | 09-NOV-15:40 | 0.98 |
December | 0.203585E+10 | 0.55 | 1408.51 | 07-DEC-19:40 | 0.99 |
Annual Sum or Average | 0.241698E+11 | 0.54 | |||
Minimum of Months | 0.185575E+10 | 0.52 | 1408.51 | 0.97 | |
Maximum of Months | 0.207967E+10 | 0.57 | 1408.51 | 0.99 |
Report: FanReportMonthly
For: PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.206341E+10 | 0.59 | 1411.92 | 02-JAN-18:40 | 0.99 |
February | 0.186365E+10 | 0.57 | 1411.92 | 25-FEB-07:40 | 0.98 |
March | 0.208531E+10 | 0.55 | 1411.92 | 02-MAR-09:30 | 0.98 |
April | 0.198233E+10 | 0.53 | 1411.92 | 06-APR-07:03 | 0.98 |
May | 0.206366E+10 | 0.53 | 1411.92 | 01-MAY-07:00 | 0.98 |
June | 0.201283E+10 | 0.53 | 1411.92 | 09-JUN-09:00 | 0.97 |
July | 0.203316E+10 | 0.52 | 1411.92 | 01-JUL-06:50 | 0.97 |
August | 0.208399E+10 | 0.53 | 1411.92 | 21-AUG-09:40 | 0.97 |
September | 0.198233E+10 | 0.53 | 1411.92 | 18-SEP-10:50 | 0.97 |
October | 0.204333E+10 | 0.53 | 1411.92 | 01-OCT-08:07 | 0.98 |
November | 0.198559E+10 | 0.54 | 1411.92 | 01-NOV-07:01 | 0.98 |
December | 0.204416E+10 | 0.56 | 1411.92 | 15-DEC-11:20 | 0.99 |
Annual Sum or Average | 0.242438E+11 | 0.54 | |||
Minimum of Months | 0.186365E+10 | 0.52 | 1411.92 | 0.97 | |
Maximum of Months | 0.208531E+10 | 0.59 | 1411.92 | 0.99 |
Report: FanReportMonthly
For: PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.207826E+10 | 0.60 | 1420.17 | 01-JAN-09:30 | 0.98 |
February | 0.187633E+10 | 0.58 | 1420.17 | 07-FEB-07:04 | 0.98 |
March | 0.209810E+10 | 0.55 | 1420.17 | 01-MAR-16:20 | 0.98 |
April | 0.199400E+10 | 0.53 | 1420.17 | 01-APR-07:03 | 0.98 |
May | 0.207572E+10 | 0.53 | 1420.17 | 01-MAY-16:00 | 0.98 |
June | 0.202459E+10 | 0.53 | 1420.17 | 01-JUN-10:30 | 0.97 |
July | 0.204505E+10 | 0.52 | 1420.17 | 02-JUL-09:50 | 0.97 |
August | 0.209617E+10 | 0.53 | 1420.17 | 01-AUG-08:00 | 0.97 |
September | 0.199392E+10 | 0.53 | 1420.17 | 01-SEP-11:30 | 0.98 |
October | 0.205527E+10 | 0.53 | 1420.17 | 06-OCT-07:02 | 0.98 |
November | 0.199754E+10 | 0.54 | 1420.17 | 06-NOV-08:08 | 0.98 |
December | 0.205725E+10 | 0.56 | 1420.17 | 01-DEC-07:06 | 0.98 |
Annual Sum or Average | 0.243922E+11 | 0.54 | |||
Minimum of Months | 0.187633E+10 | 0.52 | 1420.17 | 0.97 | |
Maximum of Months | 0.209810E+10 | 0.60 | 1420.17 | 0.98 |
Report: FanReportMonthly
For: PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.342689E+10 | 0.58 | 2524.36 | 01-JAN-09:10 | 0.94 |
February | 0.308597E+10 | 0.54 | 2524.36 | 01-FEB-08:40 | 0.95 |
March | 0.345037E+10 | 0.49 | 2524.36 | 01-MAR-18:10 | 0.94 |
April | 0.327221E+10 | 0.47 | 2524.36 | 01-APR-13:30 | 0.94 |
May | 0.340789E+10 | 0.47 | 2524.36 | 01-MAY-07:40 | 0.94 |
June | 0.332610E+10 | 0.47 | 2524.36 | 03-JUN-08:30 | 0.94 |
July | 0.335337E+10 | 0.46 | 2524.36 | 01-JUL-10:00 | 0.93 |
August | 0.344424E+10 | 0.47 | 2524.36 | 01-AUG-08:20 | 0.92 |
September | 0.327158E+10 | 0.47 | 2524.36 | 01-SEP-09:40 | 0.93 |
October | 0.337154E+10 | 0.47 | 2524.36 | 01-OCT-08:40 | 0.94 |
November | 0.328148E+10 | 0.49 | 2524.36 | 01-NOV-07:50 | 0.94 |
December | 0.337924E+10 | 0.51 | 2524.36 | 01-DEC-08:09 | 0.94 |
Annual Sum or Average | 0.400709E+11 | 0.49 | |||
Minimum of Months | 0.308597E+10 | 0.46 | 2524.36 | 0.92 | |
Maximum of Months | 0.345037E+10 | 0.58 | 2524.36 | 0.95 |
Report: FanReportMonthly
For: PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.196235E+10 | 0.59 | 1441.16 | 01-JAN-09:30 | 0.98 |
February | 0.176660E+10 | 0.55 | 1441.16 | 01-FEB-08:08 | 0.99 |
March | 0.197021E+10 | 0.51 | 1441.16 | 01-MAR-14:10 | 0.98 |
April | 0.186816E+10 | 0.49 | 1441.16 | 01-APR-09:50 | 0.98 |
May | 0.194557E+10 | 0.49 | 1441.16 | 01-MAY-11:00 | 0.98 |
June | 0.189887E+10 | 0.49 | 1441.16 | 02-JUN-08:65 | 0.98 |
July | 0.191444E+10 | 0.48 | 1441.16 | 01-JUL-07:50 | 0.97 |
August | 0.196632E+10 | 0.49 | 1441.16 | 01-AUG-08:20 | 0.96 |
September | 0.186774E+10 | 0.49 | 1441.16 | 01-SEP-19:20 | 0.98 |
October | 0.192481E+10 | 0.49 | 1441.16 | 02-OCT-07:30 | 0.98 |
November | 0.187409E+10 | 0.51 | 1441.16 | 01-NOV-10:10 | 0.98 |
December | 0.193166E+10 | 0.53 | 1441.16 | 01-DEC-09:30 | 0.98 |
Annual Sum or Average | 0.228908E+11 | 0.51 | |||
Minimum of Months | 0.176660E+10 | 0.48 | 1441.16 | 0.96 | |
Maximum of Months | 0.197021E+10 | 0.59 | 1441.16 | 0.99 |
Report: FanReportMonthly
For: PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.196091E+10 | 0.60 | 1439.90 | 01-JAN-09:17 | 0.98 |
February | 0.176487E+10 | 0.56 | 1439.90 | 01-FEB-08:07 | 0.99 |
March | 0.196877E+10 | 0.51 | 1439.90 | 01-MAR-09:30 | 0.98 |
April | 0.186651E+10 | 0.49 | 1439.90 | 01-APR-07:08 | 0.98 |
May | 0.194386E+10 | 0.49 | 1439.90 | 01-MAY-09:20 | 0.98 |
June | 0.189721E+10 | 0.49 | 1439.90 | 02-JUN-07:40 | 0.98 |
July | 0.191276E+10 | 0.48 | 1439.90 | 01-JUL-07:03 | 0.97 |
August | 0.196460E+10 | 0.49 | 1439.90 | 01-AUG-07:03 | 0.97 |
September | 0.186611E+10 | 0.49 | 1439.90 | 01-SEP-08:50 | 0.97 |
October | 0.192313E+10 | 0.49 | 1439.90 | 01-OCT-08:02 | 0.98 |
November | 0.187263E+10 | 0.51 | 1439.90 | 01-NOV-08:00 | 0.98 |
December | 0.192993E+10 | 0.53 | 1439.90 | 01-DEC-08:09 | 0.98 |
Annual Sum or Average | 0.228713E+11 | 0.51 | |||
Minimum of Months | 0.176487E+10 | 0.48 | 1439.90 | 0.97 | |
Maximum of Months | 0.196877E+10 | 0.60 | 1439.90 | 0.99 |
Report: FanReportMonthly
For: PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.198550E+10 | 0.61 | 1452.63 | 14-JAN-18:34 | 0.99 |
February | 0.178422E+10 | 0.57 | 1452.63 | 22-FEB-17:40 | 0.98 |
March | 0.198750E+10 | 0.52 | 1452.63 | 11-MAR-14:40 | 0.98 |
April | 0.188341E+10 | 0.49 | 1452.63 | 01-APR-07:06 | 0.98 |
May | 0.196105E+10 | 0.49 | 1452.63 | 24-MAY-14:10 | 0.97 |
June | 0.191399E+10 | 0.49 | 1452.63 | 01-JUN-11:00 | 0.97 |
July | 0.192967E+10 | 0.48 | 1452.63 | 01-JUL-07:50 | 0.97 |
August | 0.198197E+10 | 0.49 | 1452.63 | 01-AUG-07:03 | 0.97 |
September | 0.188261E+10 | 0.49 | 1452.63 | 01-SEP-08:50 | 0.97 |
October | 0.194013E+10 | 0.49 | 1452.63 | 19-OCT-07:05 | 0.98 |
November | 0.189104E+10 | 0.52 | 1452.63 | 06-NOV-13:10 | 0.97 |
December | 0.195004E+10 | 0.54 | 1452.63 | 01-DEC-08:04 | 0.98 |
Annual Sum or Average | 0.230911E+11 | 0.51 | |||
Minimum of Months | 0.178422E+10 | 0.48 | 1452.63 | 0.97 | |
Maximum of Months | 0.198750E+10 | 0.61 | 1452.63 | 0.99 |
Report: FanReportMonthly
For: PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.229592E+10 | 0.73 | 1586.33 | 03-JAN-11:50 | 0.95 |
February | 0.203387E+10 | 0.68 | 1586.33 | 13-FEB-14:50 | 0.94 |
March | 0.221931E+10 | 0.61 | 1586.33 | 02-MAR-16:50 | 0.94 |
April | 0.207105E+10 | 0.52 | 1586.33 | 04-APR-10:00 | 0.95 |
May | 0.214167E+10 | 0.47 | 1586.33 | 19-MAY-17:00 | 0.94 |
June | 0.209015E+10 | 0.47 | 1586.33 | 09-JUN-14:00 | 0.93 |
July | 0.210728E+10 | 0.46 | 1586.33 | 01-JUL-12:20 | 0.93 |
August | 0.216439E+10 | 0.47 | 1586.33 | 01-AUG-07:30 | 0.93 |
September | 0.205589E+10 | 0.47 | 1586.33 | 01-SEP-10:00 | 0.93 |
October | 0.211870E+10 | 0.47 | 1586.33 | 01-OCT-08:08 | 0.94 |
November | 0.210305E+10 | 0.57 | 1586.33 | 19-NOV-17:10 | 0.94 |
December | 0.221110E+10 | 0.66 | 1586.33 | 04-DEC-13:30 | 0.94 |
Annual Sum or Average | 0.256124E+11 | 0.55 | |||
Minimum of Months | 0.203387E+10 | 0.46 | 1586.33 | 0.93 | |
Maximum of Months | 0.229592E+10 | 0.73 | 1586.33 | 0.95 |
Report: ZoneTemperatureOscillationReportMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 2.82 | 0.23 |
February | 3.13 | 0.31 |
March | 2.55 | 0.62 |
April | 1.61 | 0.89 |
May | 0.36 | 1.50 |
June | 0.22 | 1.50 |
July | 0.06 | 0.00 |
August | 0.00 | 0.00 |
September | 0.44 | 1.12 |
October | 0.42 | 1.10 |
November | 1.45 | 0.69 |
December | 2.97 | 0.68 |
Annual Sum or Average | 16.03 | 0.59 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 3.13 | 1.50 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.97 | 0.00 |
February | 0.58 | 0.98 |
March | 0.69 | 3.37 |
April | 0.59 | 2.85 |
May | 0.40 | 2.95 |
June | 0.08 | 0.75 |
July | 0.06 | 0.00 |
August | 0.17 | 0.75 |
September | 0.68 | 2.85 |
October | 1.71 | 4.43 |
November | 1.02 | 2.89 |
December | 0.49 | 0.00 |
Annual Sum or Average | 7.43 | 2.47 |
Minimum of Months | 0.06 | 0.00 |
Maximum of Months | 1.71 | 4.43 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 2.03 | 0.00 |
February | 0.83 | 0.00 |
March | 0.27 | 0.00 |
April | 0.42 | 0.61 |
May | 0.24 | 0.75 |
June | 2.02 | 0.75 |
July | 2.58 | 0.75 |
August | 1.76 | 0.71 |
September | 1.02 | 0.63 |
October | 0.08 | 0.00 |
November | 0.64 | 0.00 |
December | 0.78 | 0.00 |
Annual Sum or Average | 12.66 | 0.46 |
Minimum of Months | 0.08 | 0.00 |
Maximum of Months | 2.58 | 0.75 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 2.43 | 0.00 |
February | 1.09 | 0.00 |
March | 0.30 | 0.00 |
April | 0.61 | 0.41 |
May | 0.24 | 0.75 |
June | 1.93 | 0.75 |
July | 2.50 | 0.75 |
August | 1.76 | 0.71 |
September | 0.85 | 0.75 |
October | 0.00 | 0.00 |
November | 0.73 | 0.00 |
December | 1.01 | 0.00 |
Annual Sum or Average | 13.44 | 0.42 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 2.50 | 0.75 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 2.51 | 0.00 |
February | 1.31 | 0.00 |
March | 0.43 | 0.00 |
April | 0.67 | 0.38 |
May | 0.24 | 0.75 |
June | 1.93 | 0.75 |
July | 2.44 | 0.75 |
August | 1.48 | 0.75 |
September | 0.85 | 0.75 |
October | 0.00 | 0.00 |
November | 0.76 | 0.00 |
December | 1.29 | 0.00 |
Annual Sum or Average | 13.92 | 0.39 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 2.51 | 0.75 |
Report: ZoneTemperatureOscillationReportMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 4.23 | 0.00 |
February | 2.40 | 0.00 |
March | 0.92 | 0.00 |
April | 0.63 | 2.22 |
May | 0.39 | 1.89 |
June | 1.36 | 2.96 |
July | 1.23 | 2.56 |
August | 0.87 | 2.25 |
September | 0.93 | 2.81 |
October | 0.08 | 3.30 |
November | 1.30 | 0.00 |
December | 2.76 | 0.00 |
Annual Sum or Average | 17.10 | 0.83 |
Minimum of Months | 0.08 | 0.00 |
Maximum of Months | 4.23 | 3.30 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 3.07 | 0.00 |
February | 1.81 | 0.00 |
March | 0.78 | 0.00 |
April | 0.58 | 0.96 |
May | 0.00 | 0.00 |
June | 1.22 | 1.46 |
July | 1.29 | 1.29 |
August | 0.87 | 1.12 |
September | 0.85 | 1.22 |
October | 0.00 | 0.00 |
November | 1.08 | 0.00 |
December | 2.08 | 0.00 |
Annual Sum or Average | 13.64 | 0.44 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 3.07 | 1.46 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 3.10 | 0.00 |
February | 1.84 | 0.00 |
March | 0.78 | 0.00 |
April | 0.58 | 0.96 |
May | 0.00 | 0.00 |
June | 1.22 | 1.46 |
July | 1.21 | 1.38 |
August | 0.87 | 1.12 |
September | 0.77 | 1.35 |
October | 0.00 | 0.00 |
November | 1.08 | 0.00 |
December | 2.12 | 0.00 |
Annual Sum or Average | 13.58 | 0.44 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 3.10 | 1.46 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 3.45 | 0.00 |
February | 2.10 | 0.00 |
March | 0.96 | 0.00 |
April | 0.71 | 0.79 |
May | 0.00 | 0.00 |
June | 1.33 | 1.34 |
July | 1.01 | 1.47 |
August | 0.79 | 1.24 |
September | 0.68 | 1.52 |
October | 0.00 | 0.00 |
November | 1.66 | 0.00 |
December | 2.07 | 0.00 |
Annual Sum or Average | 14.76 | 0.40 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 3.45 | 1.52 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 4.73 | 0.00 |
February | 3.85 | 0.00 |
March | 3.47 | 0.00 |
April | 1.83 | 0.23 |
May | 0.18 | 0.00 |
June | 1.00 | 1.65 |
July | 1.12 | 1.49 |
August | 0.79 | 1.24 |
September | 0.68 | 1.52 |
October | 0.25 | 0.00 |
November | 3.23 | 0.00 |
December | 4.69 | 0.00 |
Annual Sum or Average | 25.83 | 0.22 |
Minimum of Months | 0.18 | 0.00 |
Maximum of Months | 4.73 | 1.65 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_1:1
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.485416E+10 | 0.627925E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.437574E+10 | 0.444270E+11 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.481889E+10 | 0.275847E+11 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.546556E+10 | 0.129773E+11 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.614900E+10 | 0.543981E+09 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.107822E+11 | 8442653.57 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.130334E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.122068E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.827332E+10 | 0.443697E+09 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.483282E+10 | 0.454660E+10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.464455E+10 | 0.257065E+11 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.484397E+10 | 0.484505E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.842804E+11 | 0.227481E+12 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.437574E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.130334E+11 | 0.627925E+11 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_2:2
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.193862E+10 | 0.261556E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.175009E+10 | 0.183128E+11 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.195982E+10 | 0.107591E+11 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.243872E+10 | 0.495616E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.353007E+10 | 0.161728E+09 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.562211E+10 | 4307292.76 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.674879E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.660487E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.440283E+10 | 0.135409E+09 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.216609E+10 | 0.160189E+10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.191148E+10 | 0.103567E+11 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.190435E+10 | 0.198644E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.409778E+11 | 0.923081E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.175009E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.674879E+10 | 0.261556E+11 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_3:3
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.205253E+10 | 0.289885E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.185575E+10 | 0.205904E+11 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.207967E+10 | 0.130350E+11 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.230593E+10 | 0.637915E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.280233E+10 | 0.384737E+09 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.453227E+10 | 50862567.71 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.533512E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.536207E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.357489E+10 | 0.371065E+09 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.208375E+10 | 0.299164E+10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.197861E+10 | 0.122517E+11 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.203585E+10 | 0.226007E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.359988E+11 | 0.107644E+12 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.185575E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.536207E+10 | 0.289885E+11 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_4:4
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.206341E+10 | 0.296475E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.186365E+10 | 0.211073E+11 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.208531E+10 | 0.134908E+11 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.229722E+10 | 0.668433E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.275443E+10 | 0.456822E+09 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.450465E+10 | 84946265.07 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.530881E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.533177E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.355418E+10 | 0.449919E+09 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.208035E+10 | 0.336981E+10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.198559E+10 | 0.127442E+11 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.204416E+10 | 0.231732E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.358735E+11 | 0.111209E+12 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.186365E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.533177E+10 | 0.296475E+11 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_5:5
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.207826E+10 | 0.302135E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.187633E+10 | 0.215872E+11 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.209810E+10 | 0.139557E+11 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.229626E+10 | 0.698199E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.272075E+10 | 0.523626E+09 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.446819E+10 | 0.109632E+09 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.526481E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.528907E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.353525E+10 | 0.514260E+09 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.208683E+10 | 0.366155E+10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.199754E+10 | 0.131415E+11 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.205725E+10 | 0.236953E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.357686E+11 | 0.114384E+12 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.187633E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.528907E+10 | 0.302135E+11 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_6:6
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.342689E+10 | 0.540107E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.308597E+10 | 0.384792E+11 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.345037E+10 | 0.249435E+11 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.375126E+10 | 0.124156E+11 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.426488E+10 | 0.749948E+09 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.747117E+10 | 0.154028E+09 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.895199E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.881271E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.577533E+10 | 0.854824E+09 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.338782E+10 | 0.645040E+10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.328148E+10 | 0.235626E+11 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.337924E+10 | 0.423898E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.590391E+11 | 0.204011E+12 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.308597E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.895199E+10 | 0.540107E+11 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_7:7
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.196235E+10 | 0.296700E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.176660E+10 | 0.212450E+11 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.197021E+10 | 0.138317E+11 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.214100E+10 | 0.703040E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.249748E+10 | 0.548436E+09 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.420921E+10 | 0.137935E+09 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.496105E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.500650E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.331696E+10 | 0.562130E+09 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.194795E+10 | 0.386718E+10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.187409E+10 | 0.130697E+11 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.193166E+10 | 0.232610E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.335850E+11 | 0.113224E+12 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.176660E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.500650E+10 | 0.296700E+11 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_8:8
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.196091E+10 | 0.297377E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.176487E+10 | 0.213170E+11 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.196877E+10 | 0.139539E+11 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.213174E+10 | 0.714388E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.247014E+10 | 0.593401E+09 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.417425E+10 | 0.155187E+09 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.492261E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.496873E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.329477E+10 | 0.594509E+09 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.194486E+10 | 0.398137E+10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.187263E+10 | 0.131745E+11 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.192993E+10 | 0.233406E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.334042E+11 | 0.113992E+12 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.176487E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.496873E+10 | 0.297377E+11 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_9:9
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.198550E+10 | 0.303860E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.178422E+10 | 0.218752E+11 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.198750E+10 | 0.145246E+11 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.213001E+10 | 0.761874E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.243340E+10 | 0.749027E+09 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.411542E+10 | 0.208900E+09 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.486033E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.491336E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.327385E+10 | 0.688529E+09 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.195889E+10 | 0.434088E+10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.189104E+10 | 0.136301E+11 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.195004E+10 | 0.238817E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.332836E+11 | 0.117904E+12 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.178422E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.491336E+10 | 0.303860E+11 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_10:10
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.229592E+10 | 0.386967E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.203387E+10 | 0.281057E+11 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.221931E+10 | 0.191996E+11 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.228551E+10 | 0.103713E+11 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.253589E+10 | 0.142455E+10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.422027E+10 | 0.419271E+09 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.498643E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.508127E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.346092E+10 | 0.101188E+10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.213457E+10 | 0.554673E+10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.210305E+10 | 0.170712E+11 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.221110E+10 | 0.298647E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.355681E+11 | 0.151712E+12 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.203387E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.508127E+10 | 0.386967E+11 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_1:1
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.485416E+10 | 0.00 | 0.497630E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.437574E+10 | 0.00 | 0.352084E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.481889E+10 | 640.03 | 0.218609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.465663E+10 | 0.257723E+10 | 0.102845E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.479681E+10 | 0.433135E+10 | 0.431105E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.465376E+10 | 0.198725E+11 | 6690802.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.480603E+10 | 0.273725E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.479652E+10 | 0.245592E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.466328E+10 | 0.114965E+11 | 0.351630E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.479667E+10 | 0.113107E+09 | 0.360318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.464455E+10 | 8931.74 | 0.203724E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.484397E+10 | 0.00 | 0.383970E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.567070E+11 | 0.903224E+11 | 0.180279E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.437574E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.485416E+10 | 0.273725E+11 | 0.497630E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_2:2
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.193862E+10 | 0.00 | 0.209245E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.175009E+10 | 0.00 | 0.146503E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.193758E+10 | 68624199.46 | 0.860727E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.187190E+10 | 0.188677E+10 | 0.396493E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.201542E+10 | 0.505997E+10 | 0.129382E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.201955E+10 | 0.122471E+11 | 3445834.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.209128E+10 | 0.161745E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.210728E+10 | 0.156119E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.196679E+10 | 0.815440E+10 | 0.108327E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.192908E+10 | 0.763114E+09 | 0.128152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.185971E+10 | 0.160417E+09 | 0.828537E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.190435E+10 | 0.00 | 0.158915E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.233916E+11 | 0.601268E+11 | 0.738465E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.175009E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.210728E+10 | 0.161745E+11 | 0.209245E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_3:3
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.205253E+10 | 0.00 | 0.231908E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.185575E+10 | 0.00 | 0.164723E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.207967E+10 | 0.00 | 0.104280E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.197755E+10 | 0.110572E+10 | 0.510332E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.205869E+10 | 0.250704E+10 | 0.307790E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.200798E+10 | 0.864853E+10 | 40690054.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.202826E+10 | 0.115659E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.207897E+10 | 0.114383E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.197755E+10 | 0.535546E+10 | 0.296852E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.203840E+10 | 0.150874E+09 | 0.239331E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.197861E+10 | 0.00 | 0.980139E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.203585E+10 | 0.00 | 0.180805E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.241698E+11 | 0.407718E+11 | 0.861150E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.185575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.207967E+10 | 0.115659E+11 | 0.231908E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_4:4
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.206341E+10 | 0.00 | 0.237180E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.186365E+10 | 0.00 | 0.168858E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.208531E+10 | 0.00 | 0.107926E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.198233E+10 | 0.105752E+10 | 0.534746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.206366E+10 | 0.232291E+10 | 0.365458E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.201283E+10 | 0.852639E+10 | 67957012.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.203316E+10 | 0.114444E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.208399E+10 | 0.113010E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.198233E+10 | 0.526221E+10 | 0.359935E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.204333E+10 | 0.122948E+09 | 0.269585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.198559E+10 | 0.00 | 0.101953E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.204416E+10 | 0.00 | 0.185385E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.242438E+11 | 0.400374E+11 | 0.889670E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.186365E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.208531E+10 | 0.114444E+11 | 0.237180E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_5:5
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.207826E+10 | 0.00 | 0.241708E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.187633E+10 | 0.00 | 0.172697E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.209810E+10 | 0.00 | 0.111645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.199400E+10 | 0.101214E+10 | 0.558559E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.207572E+10 | 0.216320E+10 | 0.418900E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.202459E+10 | 0.834289E+10 | 87705704.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.204505E+10 | 0.112263E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.209617E+10 | 0.110867E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.199392E+10 | 0.514854E+10 | 0.411408E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.205527E+10 | 0.104630E+09 | 0.292924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.199754E+10 | 0.00 | 0.105132E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.205725E+10 | 0.00 | 0.189562E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.243922E+11 | 0.390844E+11 | 0.915074E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.187633E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.209810E+10 | 0.112263E+11 | 0.241708E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_6:6
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.342689E+10 | 0.00 | 0.428035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.308597E+10 | 0.00 | 0.304947E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.345037E+10 | 0.00 | 0.197677E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.327221E+10 | 0.150799E+10 | 0.983939E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.340789E+10 | 0.269008E+10 | 0.594334E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.332610E+10 | 0.132990E+11 | 0.122067E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.335337E+10 | 0.184059E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.344424E+10 | 0.175422E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.327158E+10 | 0.783465E+10 | 0.677448E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.337154E+10 | 50121131.03 | 0.511194E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.328148E+10 | 0.00 | 0.186734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.337924E+10 | 0.00 | 0.335939E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.400709E+11 | 0.613299E+11 | 0.161678E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.308597E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.345037E+10 | 0.184059E+11 | 0.428035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_7:7
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.196235E+10 | 0.00 | 0.237360E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.176660E+10 | 0.00 | 0.169960E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.197021E+10 | 0.00 | 0.110654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.186816E+10 | 0.906409E+09 | 0.562432E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.194557E+10 | 0.183633E+10 | 0.438749E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.189887E+10 | 0.782322E+10 | 0.110348E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.191444E+10 | 0.105468E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.196632E+10 | 0.104782E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.186774E+10 | 0.480422E+10 | 0.449704E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.192481E+10 | 76377820.56 | 0.309374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.187409E+10 | 0.00 | 0.104558E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.193166E+10 | 0.00 | 0.186088E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.228908E+11 | 0.364716E+11 | 0.905789E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.176660E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.197021E+10 | 0.105468E+11 | 0.237360E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_8:8
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.196091E+10 | 0.00 | 0.237902E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.176487E+10 | 0.00 | 0.170536E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.196877E+10 | 0.00 | 0.111632E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.186651E+10 | 0.879739E+09 | 0.571510E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.194386E+10 | 0.174784E+10 | 0.474721E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.189721E+10 | 0.770192E+10 | 0.124150E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.191276E+10 | 0.104097E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.196460E+10 | 0.103442E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.186611E+10 | 0.473066E+10 | 0.475607E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.192313E+10 | 71667348.97 | 0.318510E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.187263E+10 | 0.00 | 0.105396E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.192993E+10 | 0.00 | 0.186725E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.228713E+11 | 0.358857E+11 | 0.911937E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.176487E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.196877E+10 | 0.104097E+11 | 0.237902E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_9:9
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.198550E+10 | 0.00 | 0.243088E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.178422E+10 | 0.00 | 0.175001E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.198750E+10 | 0.00 | 0.116197E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.188341E+10 | 0.813987E+09 | 0.609500E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.196105E+10 | 0.156105E+10 | 0.599222E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.191399E+10 | 0.742107E+10 | 0.167120E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.192967E+10 | 0.101072E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.198197E+10 | 0.100671E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.188261E+10 | 0.459336E+10 | 0.550823E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.194013E+10 | 61710523.54 | 0.347270E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.189104E+10 | 0.00 | 0.109041E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.195004E+10 | 0.00 | 0.191054E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.230911E+11 | 0.346254E+11 | 0.943230E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.178422E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.198750E+10 | 0.101072E+11 | 0.243088E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_10:10
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.229592E+10 | 0.00 | 0.309573E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.203387E+10 | 0.00 | 0.224846E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.221931E+10 | 0.00 | 0.153597E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.207105E+10 | 0.696827E+09 | 0.829702E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.214167E+10 | 0.128371E+10 | 0.113964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.209015E+10 | 0.707660E+10 | 0.335417E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.210728E+10 | 0.980045E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.216439E+10 | 0.990185E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.205589E+10 | 0.459132E+10 | 0.809503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.211870E+10 | 51927085.42 | 0.443739E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.210305E+10 | 0.00 | 0.136570E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.221110E+10 | 0.00 | 0.238918E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.256124E+11 | 0.334027E+11 | 0.121369E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.203387E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.229592E+10 | 0.990185E+10 | 0.309573E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_1:1
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.485416E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.627925E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.437574E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.444270E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.481889E+10 | 0.00 | 0.00 | 0.00 | 209.23 | 0.00 | 0.275847E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.465663E+10 | 0.00 | 0.00 | 0.00 | 0.808937E+09 | 0.00 | 0.129773E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.479681E+10 | 0.00 | 0.00 | 0.00 | 0.135219E+10 | 0.00 | 0.543981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.465376E+10 | 0.00 | 0.00 | 0.00 | 0.612844E+10 | 0.00 | 8442653.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.480603E+10 | 0.00 | 0.00 | 0.00 | 0.822740E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.479652E+10 | 0.00 | 0.00 | 0.00 | 0.741024E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.466328E+10 | 0.00 | 0.00 | 0.00 | 0.361005E+10 | 0.00 | 0.443697E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.479667E+10 | 0.00 | 0.00 | 0.00 | 36147069.63 | 0.00 | 0.454660E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.464455E+10 | 0.00 | 0.00 | 0.00 | 2909.90 | 0.00 | 0.257065E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.484397E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.484505E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.567070E+11 | 0.00 | 0.00 | 0.00 | 0.275734E+11 | 0.00 | 0.227481E+12 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.437574E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.485416E+10 | 0.00 | 0.00 | 0.00 | 0.822740E+10 | 0.00 | 0.627925E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_2:2
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.193862E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.261556E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.175009E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.193758E+10 | 0.00 | 0.00 | 0.00 | 22245179.96 | 0.00 | 0.107591E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.187190E+10 | 0.00 | 0.00 | 0.00 | 0.566821E+09 | 0.00 | 0.495616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.201542E+10 | 0.00 | 0.00 | 0.00 | 0.151465E+10 | 0.00 | 0.161728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.201955E+10 | 0.00 | 0.00 | 0.00 | 0.360255E+10 | 0.00 | 4307292.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.209128E+10 | 0.00 | 0.00 | 0.00 | 0.465751E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.210728E+10 | 0.00 | 0.00 | 0.00 | 0.449759E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.196679E+10 | 0.00 | 0.00 | 0.00 | 0.243604E+10 | 0.00 | 0.135409E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.192908E+10 | 0.00 | 0.00 | 0.00 | 0.237009E+09 | 0.00 | 0.160189E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.185971E+10 | 0.00 | 0.00 | 0.00 | 51772739.57 | 0.00 | 0.103567E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.190435E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.198644E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.233916E+11 | 0.00 | 0.00 | 0.00 | 0.175862E+11 | 0.00 | 0.923081E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.175009E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.210728E+10 | 0.00 | 0.00 | 0.00 | 0.465751E+10 | 0.00 | 0.261556E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_3:3
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.205253E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.289885E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.185575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.205904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.207967E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130350E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.197755E+10 | 0.00 | 0.00 | 0.00 | 0.328378E+09 | 0.00 | 0.637915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.205869E+10 | 0.00 | 0.00 | 0.00 | 0.743646E+09 | 0.00 | 0.384737E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.200798E+10 | 0.00 | 0.00 | 0.00 | 0.252429E+10 | 0.00 | 50862567.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.202826E+10 | 0.00 | 0.00 | 0.00 | 0.330686E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.207897E+10 | 0.00 | 0.00 | 0.00 | 0.328310E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.197755E+10 | 0.00 | 0.00 | 0.00 | 0.159734E+10 | 0.00 | 0.371065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.203840E+10 | 0.00 | 0.00 | 0.00 | 45345019.84 | 0.00 | 0.299164E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.197861E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122517E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.203585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.226007E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.241698E+11 | 0.00 | 0.00 | 0.00 | 0.118290E+11 | 0.00 | 0.107644E+12 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.185575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.207967E+10 | 0.00 | 0.00 | 0.00 | 0.330686E+10 | 0.00 | 0.289885E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_4:4
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.206341E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.296475E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.186365E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.211073E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.208531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134908E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.198233E+10 | 0.00 | 0.00 | 0.00 | 0.314882E+09 | 0.00 | 0.668433E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.206366E+10 | 0.00 | 0.00 | 0.00 | 0.690768E+09 | 0.00 | 0.456822E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.201283E+10 | 0.00 | 0.00 | 0.00 | 0.249182E+10 | 0.00 | 84946265.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.203316E+10 | 0.00 | 0.00 | 0.00 | 0.327565E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.208399E+10 | 0.00 | 0.00 | 0.00 | 0.324778E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.198233E+10 | 0.00 | 0.00 | 0.00 | 0.157185E+10 | 0.00 | 0.449919E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.204333E+10 | 0.00 | 0.00 | 0.00 | 37022177.43 | 0.00 | 0.336981E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.198559E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127442E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.204416E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.231732E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.242438E+11 | 0.00 | 0.00 | 0.00 | 0.116298E+11 | 0.00 | 0.111209E+12 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.186365E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.208531E+10 | 0.00 | 0.00 | 0.00 | 0.327565E+10 | 0.00 | 0.296475E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_5:5
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.207826E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.302135E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.187633E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.215872E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.209810E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.199400E+10 | 0.00 | 0.00 | 0.00 | 0.302258E+09 | 0.00 | 0.698199E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.207572E+10 | 0.00 | 0.00 | 0.00 | 0.645027E+09 | 0.00 | 0.523626E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.202459E+10 | 0.00 | 0.00 | 0.00 | 0.244359E+10 | 0.00 | 0.109632E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.204505E+10 | 0.00 | 0.00 | 0.00 | 0.321976E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.209617E+10 | 0.00 | 0.00 | 0.00 | 0.319290E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.199392E+10 | 0.00 | 0.00 | 0.00 | 0.154133E+10 | 0.00 | 0.514260E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.205527E+10 | 0.00 | 0.00 | 0.00 | 31563347.89 | 0.00 | 0.366155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.199754E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131415E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.205725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.236953E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.243922E+11 | 0.00 | 0.00 | 0.00 | 0.113764E+11 | 0.00 | 0.114384E+12 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.187633E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.209810E+10 | 0.00 | 0.00 | 0.00 | 0.321976E+10 | 0.00 | 0.302135E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_6:6
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.342689E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.540107E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.308597E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.384792E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.345037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.249435E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.327221E+10 | 0.00 | 0.00 | 0.00 | 0.479047E+09 | 0.00 | 0.124156E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.340789E+10 | 0.00 | 0.00 | 0.00 | 0.856984E+09 | 0.00 | 0.749948E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.332610E+10 | 0.00 | 0.00 | 0.00 | 0.414507E+10 | 0.00 | 0.154028E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.335337E+10 | 0.00 | 0.00 | 0.00 | 0.559862E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.344424E+10 | 0.00 | 0.00 | 0.00 | 0.536847E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.327158E+10 | 0.00 | 0.00 | 0.00 | 0.250376E+10 | 0.00 | 0.854824E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.337154E+10 | 0.00 | 0.00 | 0.00 | 16282241.56 | 0.00 | 0.645040E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.328148E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.235626E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.337924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.423898E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.400709E+11 | 0.00 | 0.00 | 0.00 | 0.189682E+11 | 0.00 | 0.204011E+12 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.308597E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.345037E+10 | 0.00 | 0.00 | 0.00 | 0.559862E+10 | 0.00 | 0.540107E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_7:7
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.196235E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.296700E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.176660E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.212450E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.197021E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138317E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.186816E+10 | 0.00 | 0.00 | 0.00 | 0.272832E+09 | 0.00 | 0.703040E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.194557E+10 | 0.00 | 0.00 | 0.00 | 0.551911E+09 | 0.00 | 0.548436E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.189887E+10 | 0.00 | 0.00 | 0.00 | 0.231034E+10 | 0.00 | 0.137935E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.191444E+10 | 0.00 | 0.00 | 0.00 | 0.304661E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.196632E+10 | 0.00 | 0.00 | 0.00 | 0.304018E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.186774E+10 | 0.00 | 0.00 | 0.00 | 0.144921E+10 | 0.00 | 0.562130E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.192481E+10 | 0.00 | 0.00 | 0.00 | 23137657.53 | 0.00 | 0.386718E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.187409E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130697E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.193166E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.232610E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.228908E+11 | 0.00 | 0.00 | 0.00 | 0.106942E+11 | 0.00 | 0.113224E+12 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.176660E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.197021E+10 | 0.00 | 0.00 | 0.00 | 0.304661E+10 | 0.00 | 0.296700E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_8:8
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.196091E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.297377E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.176487E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.213170E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.196877E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139539E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.186651E+10 | 0.00 | 0.00 | 0.00 | 0.265231E+09 | 0.00 | 0.714388E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.194386E+10 | 0.00 | 0.00 | 0.00 | 0.526279E+09 | 0.00 | 0.593401E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.189721E+10 | 0.00 | 0.00 | 0.00 | 0.227704E+10 | 0.00 | 0.155187E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.191276E+10 | 0.00 | 0.00 | 0.00 | 0.300985E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.196460E+10 | 0.00 | 0.00 | 0.00 | 0.300414E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.186611E+10 | 0.00 | 0.00 | 0.00 | 0.142866E+10 | 0.00 | 0.594509E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.192313E+10 | 0.00 | 0.00 | 0.00 | 21730806.34 | 0.00 | 0.398137E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.187263E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131745E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.192993E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.233406E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.228713E+11 | 0.00 | 0.00 | 0.00 | 0.105329E+11 | 0.00 | 0.113992E+12 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.176487E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.196877E+10 | 0.00 | 0.00 | 0.00 | 0.300985E+10 | 0.00 | 0.297377E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_9:9
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.198550E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.303860E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.178422E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.218752E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.198750E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.145246E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.188341E+10 | 0.00 | 0.00 | 0.00 | 0.246601E+09 | 0.00 | 0.761874E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.196105E+10 | 0.00 | 0.00 | 0.00 | 0.472350E+09 | 0.00 | 0.749027E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.191399E+10 | 0.00 | 0.00 | 0.00 | 0.220144E+10 | 0.00 | 0.208900E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.192967E+10 | 0.00 | 0.00 | 0.00 | 0.293066E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.198197E+10 | 0.00 | 0.00 | 0.00 | 0.293139E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.188261E+10 | 0.00 | 0.00 | 0.00 | 0.139124E+10 | 0.00 | 0.688529E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.194013E+10 | 0.00 | 0.00 | 0.00 | 18760312.34 | 0.00 | 0.434088E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.189104E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136301E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.195004E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.238817E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.230911E+11 | 0.00 | 0.00 | 0.00 | 0.101924E+11 | 0.00 | 0.117904E+12 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.178422E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.198750E+10 | 0.00 | 0.00 | 0.00 | 0.293139E+10 | 0.00 | 0.303860E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_10:10
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.229592E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.386967E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.203387E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.281057E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.221931E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.191996E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.207105E+10 | 0.00 | 0.00 | 0.00 | 0.214459E+09 | 0.00 | 0.103713E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.214167E+10 | 0.00 | 0.00 | 0.00 | 0.394227E+09 | 0.00 | 0.142455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.209015E+10 | 0.00 | 0.00 | 0.00 | 0.213012E+10 | 0.00 | 0.419271E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.210728E+10 | 0.00 | 0.00 | 0.00 | 0.287914E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.216439E+10 | 0.00 | 0.00 | 0.00 | 0.291688E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.205589E+10 | 0.00 | 0.00 | 0.00 | 0.140504E+10 | 0.00 | 0.101188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.211870E+10 | 0.00 | 0.00 | 0.00 | 15870153.43 | 0.00 | 0.554673E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.210305E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.170712E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.221110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.298647E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.256124E+11 | 0.00 | 0.00 | 0.00 | 0.995574E+10 | 0.00 | 0.151712E+12 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.203387E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.229592E+10 | 0.00 | 0.00 | 0.00 | 0.291688E+10 | 0.00 | 0.386967E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.172088E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.330994E+11 | 0.00 | 0.00 | 0.68 |
February | 0.380861E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.229342E+11 | 0.00 | 0.00 | 0.68 |
March | 0.683799E+10 | 0.00 | 0.00 | 32817.09 | 0.00 | 0.141351E+11 | 78384075.36 | 0.00 | 0.68 |
April | 0.715834E+10 | 0.603404E+09 | 0.00 | 1247358.84 | 3766880.41 | 0.624273E+10 | 0.109531E+10 | 0.00 | 0.79 |
May | 0.364692E+10 | 0.658132E+09 | 0.00 | 7460392.49 | 0.00 | 0.164876E+09 | 0.650060E+10 | 0.00 | 1.10 |
June | 0.169094E+10 | 0.499727E+10 | 0.00 | 7396178.36 | 7778878.06 | 0.00 | 0.428834E+10 | 0.00 | 1.30 |
July | 15987260.96 | 0.686114E+10 | 0.00 | 9349681.43 | 1284368.41 | 0.00 | 0.436224E+10 | 0.00 | 1.56 |
August | 25843941.00 | 0.556069E+10 | 0.00 | 12446413.21 | 1822035.02 | 0.00 | 0.593834E+10 | 0.00 | 1.56 |
September | 0.327114E+10 | 0.177038E+10 | 0.00 | 10734212.14 | 18946.36 | 64107597.88 | 0.644567E+10 | 0.00 | 1.24 |
October | 0.114912E+11 | 0.00 | 0.00 | 1928217.61 | 0.00 | 0.118654E+10 | 0.197138E+10 | 0.00 | 0.75 |
November | 0.790425E+10 | 0.00 | 0.00 | 157650.98 | 0.00 | 0.131109E+11 | 0.310288E+09 | 0.00 | 0.68 |
December | 0.519643E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.245418E+11 | 0.00 | 0.00 | 0.68 |
Annual Sum or Average | 0.527685E+11 | 0.204510E+11 | 0.00 | 50752922.13 | 14671108.26 | 0.115480E+12 | 0.309905E+11 | 0.00 | 0.98 |
Minimum of Months | 15987260.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.68 |
Maximum of Months | 0.114912E+11 | 0.686114E+10 | 0.00 | 12446413.21 | 7778878.06 | 0.330994E+11 | 0.650060E+10 | 0.00 | 1.56 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.607150E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137493E+11 | 0.00 | 0.00 | 0.55 |
February | 0.126961E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.972107E+10 | 0.00 | 0.00 | 0.55 |
March | 0.268685E+10 | 0.00 | 0.00 | 122676.05 | 0.00 | 0.570865E+10 | 35046435.34 | 0.00 | 0.55 |
April | 0.251659E+10 | 0.276139E+09 | 0.00 | 866260.48 | 2575634.47 | 0.283560E+10 | 0.201810E+09 | 0.00 | 0.55 |
May | 0.143931E+10 | 0.372592E+09 | 0.00 | 4230193.95 | 2116369.51 | 62427018.50 | 0.124062E+10 | 0.00 | 0.58 |
June | 0.702288E+09 | 0.226079E+10 | 0.00 | 2951327.44 | 15962443.96 | 0.00 | 0.445507E+09 | 0.00 | 0.60 |
July | 13879952.94 | 0.309659E+10 | 0.00 | 2057288.89 | 29011000.17 | 0.00 | 0.199304E+09 | 0.00 | 0.60 |
August | 46551978.16 | 0.272923E+10 | 0.00 | 3005321.88 | 18045408.85 | 0.00 | 0.266335E+09 | 0.00 | 0.60 |
September | 0.135632E+10 | 0.861844E+09 | 0.00 | 4856903.94 | 2405170.77 | 52133587.77 | 0.102303E+10 | 0.00 | 0.58 |
October | 0.429677E+10 | 0.00 | 0.00 | 1437728.89 | 0.00 | 0.568037E+09 | 0.556681E+09 | 0.00 | 0.55 |
November | 0.261892E+10 | 0.00 | 0.00 | 347245.25 | 0.00 | 0.556159E+10 | 0.205040E+09 | 0.00 | 0.55 |
December | 0.148620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103669E+11 | 0.00 | 0.00 | 0.54 |
Annual Sum or Average | 0.190405E+11 | 0.959718E+10 | 0.00 | 19874946.76 | 70116027.73 | 0.486257E+11 | 0.417337E+10 | 0.00 | 0.57 |
Minimum of Months | 13879952.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.54 |
Maximum of Months | 0.429677E+10 | 0.309659E+10 | 0.00 | 4856903.94 | 29011000.17 | 0.137493E+11 | 0.124062E+10 | 0.00 | 0.60 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.212661E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148649E+11 | 0.00 | 0.00 | 0.58 |
February | 0.510991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109954E+11 | 0.00 | 0.00 | 0.58 |
March | 0.154527E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.748053E+10 | 0.00 | 0.00 | 0.59 |
April | 0.218691E+10 | 0.219771E+09 | 0.00 | 260334.81 | 15843941.11 | 0.363157E+10 | 0.100891E+09 | 0.00 | 0.58 |
May | 0.208404E+10 | 0.298939E+09 | 0.00 | 1294863.82 | 7194632.88 | 0.194551E+09 | 0.726979E+09 | 0.00 | 0.59 |
June | 0.968985E+09 | 0.183757E+10 | 0.00 | 1747697.30 | 97868895.80 | 0.00 | 0.395219E+09 | 0.00 | 0.60 |
July | 0.111710E+09 | 0.243642E+10 | 0.00 | 1649089.47 | 0.138894E+09 | 0.00 | 0.308932E+09 | 0.00 | 0.58 |
August | 0.237614E+09 | 0.230110E+10 | 0.00 | 1852821.31 | 84468357.16 | 0.00 | 0.357276E+09 | 0.00 | 0.60 |
September | 0.182531E+10 | 0.759053E+09 | 0.00 | 2243189.05 | 19904407.98 | 0.124999E+09 | 0.704933E+09 | 0.00 | 0.58 |
October | 0.396510E+10 | 0.00 | 0.00 | 255886.77 | 0.00 | 0.151305E+10 | 0.180224E+09 | 0.00 | 0.58 |
November | 0.194905E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.682378E+10 | 0.00 | 0.00 | 0.58 |
December | 0.186633E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123798E+11 | 0.00 | 0.00 | 0.57 |
Annual Sum or Average | 0.157843E+11 | 0.785285E+10 | 0.00 | 9303882.54 | 0.364174E+09 | 0.580086E+11 | 0.277445E+10 | 0.00 | 0.58 |
Minimum of Months | 0.111710E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.57 |
Maximum of Months | 0.396510E+10 | 0.243642E+10 | 0.00 | 2243189.05 | 0.138894E+09 | 0.148649E+11 | 0.726979E+09 | 0.00 | 0.60 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.150688E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149736E+11 | 0.00 | 0.00 | 0.58 |
February | 0.351610E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111831E+11 | 0.00 | 0.00 | 0.58 |
March | 0.128979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.773371E+10 | 0.00 | 0.00 | 0.59 |
April | 0.190874E+10 | 0.215740E+09 | 0.00 | 230593.75 | 16116043.46 | 0.390251E+10 | 98000911.01 | 0.00 | 0.58 |
May | 0.213445E+10 | 0.290337E+09 | 0.00 | 1061546.03 | 7060166.37 | 0.230096E+09 | 0.620975E+09 | 0.00 | 0.59 |
June | 0.984872E+09 | 0.182739E+10 | 0.00 | 1678567.57 | 97544224.43 | 1877075.93 | 0.373394E+09 | 0.00 | 0.60 |
July | 0.121517E+09 | 0.242294E+10 | 0.00 | 1601421.16 | 0.138351E+09 | 0.00 | 0.305589E+09 | 0.00 | 0.58 |
August | 0.252818E+09 | 0.228507E+10 | 0.00 | 1783285.36 | 83977607.45 | 0.00 | 0.347001E+09 | 0.00 | 0.60 |
September | 0.179883E+10 | 0.755940E+09 | 0.00 | 2115945.55 | 19898262.97 | 0.172046E+09 | 0.670950E+09 | 0.00 | 0.58 |
October | 0.369805E+10 | 0.00 | 0.00 | 194979.16 | 0.00 | 0.178971E+10 | 0.142738E+09 | 0.00 | 0.58 |
November | 0.178314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.698519E+10 | 0.00 | 0.00 | 0.58 |
December | 0.105030E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124867E+11 | 0.00 | 0.00 | 0.57 |
Annual Sum or Average | 0.145795E+11 | 0.779742E+10 | 0.00 | 8666338.58 | 0.362947E+09 | 0.594585E+11 | 0.255865E+10 | 0.00 | 0.58 |
Minimum of Months | 0.105030E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.57 |
Maximum of Months | 0.369805E+10 | 0.242294E+10 | 0.00 | 2115945.55 | 0.138351E+09 | 0.149736E+11 | 0.670950E+09 | 0.00 | 0.60 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.103276E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150419E+11 | 0.00 | 0.00 | 0.58 |
February | 0.260213E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112897E+11 | 0.00 | 0.00 | 0.58 |
March | 0.107409E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.794858E+10 | 0.00 | 0.00 | 0.59 |
April | 0.169157E+10 | 0.211450E+09 | 0.00 | 204929.22 | 16440948.53 | 0.412159E+10 | 88241287.99 | 0.00 | 0.58 |
May | 0.218401E+10 | 0.281536E+09 | 0.00 | 880325.40 | 6952925.69 | 0.272346E+09 | 0.508836E+09 | 0.00 | 0.59 |
June | 0.991728E+09 | 0.180753E+10 | 0.00 | 1575990.08 | 97239034.15 | 19345330.94 | 0.349255E+09 | 0.00 | 0.60 |
July | 0.131722E+09 | 0.239279E+10 | 0.00 | 1509895.23 | 0.137728E+09 | 0.00 | 0.306936E+09 | 0.00 | 0.58 |
August | 0.277318E+09 | 0.225638E+10 | 0.00 | 1715014.28 | 83479533.11 | 0.00 | 0.331745E+09 | 0.00 | 0.60 |
September | 0.179293E+10 | 0.750311E+09 | 0.00 | 1986297.03 | 19927000.45 | 0.213913E+09 | 0.627586E+09 | 0.00 | 0.58 |
October | 0.342184E+10 | 0.00 | 0.00 | 156658.93 | 0.00 | 0.208037E+10 | 0.110170E+09 | 0.00 | 0.58 |
November | 0.161503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.714478E+10 | 0.00 | 0.00 | 0.58 |
December | 76260705.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125230E+11 | 0.00 | 0.00 | 0.57 |
Annual Sum or Average | 0.136200E+11 | 0.769999E+10 | 0.00 | 8029110.16 | 0.361767E+09 | 0.606556E+11 | 0.232277E+10 | 0.00 | 0.59 |
Minimum of Months | 76260705.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.57 |
Maximum of Months | 0.342184E+10 | 0.239279E+10 | 0.00 | 1986297.03 | 0.137728E+09 | 0.150419E+11 | 0.627586E+09 | 0.00 | 0.60 |
Report: MechanicalVentilationLoadsMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 12836256.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.251350E+11 | 0.00 | 0.00 | 0.49 |
February | 0.177396E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189741E+11 | 0.00 | 0.00 | 0.49 |
March | 0.142385E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135913E+11 | 0.00 | 0.00 | 0.50 |
April | 0.237689E+10 | 0.393961E+09 | 0.00 | 392564.74 | 35772034.00 | 0.714470E+10 | 0.415393E+09 | 0.00 | 0.54 |
May | 0.350840E+10 | 0.491294E+09 | 0.00 | 1595469.40 | 0.00 | 0.390228E+09 | 0.158585E+10 | 0.00 | 0.68 |
June | 0.140296E+10 | 0.345535E+10 | 0.00 | 3383466.22 | 0.108673E+09 | 29868478.95 | 0.210418E+10 | 0.00 | 0.86 |
July | 72184349.49 | 0.475848E+10 | 0.00 | 3851390.08 | 74216434.96 | 0.00 | 0.193945E+10 | 0.00 | 0.97 |
August | 79537027.38 | 0.419415E+10 | 0.00 | 5448565.38 | 39546869.23 | 0.00 | 0.255802E+10 | 0.00 | 1.03 |
September | 0.268819E+10 | 0.144111E+10 | 0.00 | 3725094.26 | 23463945.16 | 0.275691E+09 | 0.244428E+10 | 0.00 | 0.77 |
October | 0.563958E+10 | 0.00 | 0.00 | 208484.07 | 0.00 | 0.336685E+10 | 0.255894E+09 | 0.00 | 0.51 |
November | 0.227000E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123481E+11 | 0.00 | 0.00 | 0.49 |
December | 17270386.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.210051E+11 | 0.00 | 0.00 | 0.48 |
Annual Sum or Average | 0.196691E+11 | 0.147343E+11 | 0.00 | 18605034.16 | 0.281672E+09 | 0.102261E+12 | 0.113031E+11 | 0.00 | 0.65 |
Minimum of Months | 12836256.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.48 |
Maximum of Months | 0.563958E+10 | 0.475848E+10 | 0.00 | 5448565.38 | 0.108673E+09 | 0.251350E+11 | 0.255802E+10 | 0.00 | 1.03 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 17518835.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140549E+11 | 0.00 | 0.00 | 0.54 |
February | 82928461.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106254E+11 | 0.00 | 0.00 | 0.54 |
March | 0.680077E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.760828E+10 | 0.00 | 0.00 | 0.55 |
April | 0.114466E+10 | 0.194901E+09 | 0.00 | 176726.40 | 19555137.62 | 0.414345E+10 | 93169429.54 | 0.00 | 0.54 |
May | 0.190084E+10 | 0.258491E+09 | 0.00 | 552265.53 | 380889.69 | 0.330389E+09 | 0.388172E+09 | 0.00 | 0.54 |
June | 0.774964E+09 | 0.173615E+10 | 0.00 | 1305807.05 | 59666027.23 | 87762548.38 | 0.301222E+09 | 0.00 | 0.55 |
July | 97320339.24 | 0.234528E+10 | 0.00 | 1157839.78 | 44558739.27 | 0.00 | 0.240368E+09 | 0.00 | 0.54 |
August | 0.140661E+09 | 0.215258E+10 | 0.00 | 1574198.40 | 24430466.99 | 0.00 | 0.264987E+09 | 0.00 | 0.55 |
September | 0.137807E+10 | 0.725821E+09 | 0.00 | 1636727.05 | 12345475.71 | 0.368106E+09 | 0.539774E+09 | 0.00 | 0.54 |
October | 0.267768E+10 | 0.00 | 0.00 | 95247.39 | 0.00 | 0.233862E+10 | 76870806.50 | 0.00 | 0.53 |
November | 0.110370E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.696664E+10 | 0.00 | 0.00 | 0.54 |
December | 48927961.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116005E+11 | 0.00 | 0.00 | 0.53 |
Annual Sum or Average | 0.100473E+11 | 0.741323E+10 | 0.00 | 6498811.61 | 0.160937E+09 | 0.581241E+11 | 0.190456E+10 | 0.00 | 0.54 |
Minimum of Months | 17518835.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.53 |
Maximum of Months | 0.267768E+10 | 0.234528E+10 | 0.00 | 1636727.05 | 59666027.23 | 0.140549E+11 | 0.539774E+09 | 0.00 | 0.55 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 17695650.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140562E+11 | 0.00 | 0.00 | 0.54 |
February | 74818176.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106316E+11 | 0.00 | 0.00 | 0.54 |
March | 0.620721E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.766760E+10 | 0.00 | 0.00 | 0.55 |
April | 0.106945E+10 | 0.192194E+09 | 0.00 | 161286.80 | 20337486.01 | 0.421943E+10 | 88779273.08 | 0.00 | 0.54 |
May | 0.193316E+10 | 0.252676E+09 | 0.00 | 464412.75 | 439536.95 | 0.350791E+09 | 0.316130E+09 | 0.00 | 0.54 |
June | 0.755411E+09 | 0.172316E+10 | 0.00 | 1255675.32 | 60862859.76 | 0.109725E+09 | 0.298943E+09 | 0.00 | 0.55 |
July | 0.106442E+09 | 0.232732E+10 | 0.00 | 1111295.87 | 44288368.49 | 0.00 | 0.236856E+09 | 0.00 | 0.54 |
August | 0.145915E+09 | 0.213654E+10 | 0.00 | 1527604.02 | 24261128.30 | 0.00 | 0.264692E+09 | 0.00 | 0.55 |
September | 0.136812E+10 | 0.722743E+09 | 0.00 | 1567830.18 | 12352254.71 | 0.385085E+09 | 0.528057E+09 | 0.00 | 0.54 |
October | 0.261260E+10 | 0.00 | 0.00 | 86034.50 | 0.00 | 0.240992E+10 | 65194609.37 | 0.00 | 0.53 |
November | 0.103905E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.703029E+10 | 0.00 | 0.00 | 0.54 |
December | 45299895.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116039E+11 | 0.00 | 0.00 | 0.53 |
Annual Sum or Average | 0.978868E+10 | 0.735463E+10 | 0.00 | 6174139.42 | 0.162542E+09 | 0.584646E+11 | 0.179865E+10 | 0.00 | 0.54 |
Minimum of Months | 17695650.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.53 |
Maximum of Months | 0.261260E+10 | 0.232732E+10 | 0.00 | 1567830.18 | 60862859.76 | 0.140562E+11 | 0.528057E+09 | 0.00 | 0.55 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 16606236.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141075E+11 | 0.00 | 0.00 | 0.54 |
February | 37449000.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106965E+11 | 0.00 | 0.00 | 0.54 |
March | 0.476581E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.781374E+10 | 0.00 | 0.00 | 0.55 |
April | 0.876065E+09 | 0.184117E+09 | 27290.74 | 124768.74 | 23458244.17 | 0.441155E+10 | 81181611.25 | 123.58 | 0.54 |
May | 0.187523E+10 | 0.237987E+09 | 0.00 | 317534.93 | 1624555.63 | 0.487281E+09 | 0.187905E+09 | 0.00 | 0.54 |
June | 0.708729E+09 | 0.169280E+10 | 0.00 | 1114054.68 | 60580101.38 | 0.166720E+09 | 0.288432E+09 | 0.00 | 0.55 |
July | 0.128716E+09 | 0.228300E+10 | 0.00 | 987509.58 | 44018996.56 | 0.00 | 0.228618E+09 | 0.00 | 0.54 |
August | 0.160636E+09 | 0.210014E+10 | 0.00 | 1411558.48 | 23111369.52 | 0.00 | 0.261992E+09 | 0.00 | 0.55 |
September | 0.133876E+10 | 0.715998E+09 | 0.00 | 1424709.74 | 12325621.19 | 0.436753E+09 | 0.496312E+09 | 0.00 | 0.54 |
October | 0.234706E+10 | 0.00 | 0.00 | 68746.54 | 0.00 | 0.267870E+10 | 47983016.54 | 0.00 | 0.53 |
November | 0.909699E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.716789E+10 | 0.00 | 0.00 | 0.54 |
December | 39748744.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116300E+11 | 0.00 | 0.00 | 0.53 |
Annual Sum or Average | 0.891528E+10 | 0.721404E+10 | 27290.74 | 5448882.70 | 0.165119E+09 | 0.595966E+11 | 0.159242E+10 | 123.58 | 0.54 |
Minimum of Months | 16606236.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.53 |
Maximum of Months | 0.234706E+10 | 0.228300E+10 | 27290.74 | 1424709.74 | 60580101.38 | 0.141075E+11 | 0.496312E+09 | 123.58 | 0.55 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:19:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 5849243.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148893E+11 | 0.00 | 0.00 | 0.57 |
February | 8019193.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112298E+11 | 0.00 | 0.00 | 0.56 |
March | 77465790.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.838767E+10 | 0.00 | 0.00 | 0.56 |
April | 0.403279E+09 | 0.165412E+09 | 691698.05 | 51694.54 | 26521839.49 | 0.491959E+10 | 47896628.49 | 34998.86 | 0.54 |
May | 0.145353E+10 | 0.215016E+09 | 0.00 | 118673.88 | 2649809.28 | 0.862496E+09 | 95203602.55 | 0.00 | 0.54 |
June | 0.583567E+09 | 0.162070E+10 | 0.00 | 814769.68 | 52587890.92 | 0.293278E+09 | 0.261323E+09 | 0.00 | 0.55 |
July | 0.183633E+09 | 0.218598E+10 | 0.00 | 745590.28 | 39589314.34 | 0.00 | 0.203477E+09 | 0.00 | 0.54 |
August | 0.198870E+09 | 0.202290E+10 | 0.00 | 1195670.02 | 22479177.23 | 0.00 | 0.240386E+09 | 0.00 | 0.55 |
September | 0.111305E+10 | 0.706659E+09 | 0.00 | 1153411.72 | 11129459.35 | 0.704827E+09 | 0.419522E+09 | 0.00 | 0.54 |
October | 0.137807E+10 | 0.00 | 0.00 | 44521.87 | 0.00 | 0.361519E+10 | 36961096.42 | 0.00 | 0.53 |
November | 0.499330E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.776237E+10 | 0.00 | 0.00 | 0.55 |
December | 8384794.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120906E+11 | 0.00 | 0.00 | 0.55 |
Annual Sum or Average | 0.591305E+10 | 0.691666E+10 | 691698.05 | 4124331.98 | 0.154957E+09 | 0.647551E+11 | 0.130477E+10 | 34998.86 | 0.55 |
Minimum of Months | 5849243.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.53 |