Program Version:EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:20
Tabular Output Report in Format: HTML
Building: RetailStripmall
Environment: RUNPERIOD 1 ** International Falls Intl Ap MN USA TMY3 WMO#=727470
Simulation Timestamp: 2020-06-03 19:20:47
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2020-06-03 19:20:47
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 3076.45 | 1471.76 | 1471.76 |
Net Site Energy | 3076.45 | 1471.76 | 1471.76 |
Total Source Energy | 6437.57 | 3079.71 | 3079.71 |
Net Source Energy | 6437.57 | 3079.71 | 3079.71 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 2090.32 |
Net Conditioned Building Area | 2090.32 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 1586.92 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 108.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 708.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 166.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 128.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 309.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 67.51 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1489.53 | 1586.92 | 0.00 | 0.00 | 0.00 | 87.30 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 1586.92 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 108.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 708.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 166.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 128.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 309.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 67.51 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 418.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 232.26 | 759.18 | 0.00 | 0.00 | 0.00 | 0.04 |
Other | 61.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 712.59 | 759.18 | 0.00 | 0.00 | 0.00 | 0.04 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 418.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 232.26 | 759.18 | 0.00 | 0.00 | 0.00 | 0.04 |
Other | 61.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 712.59 | 759.18 | 0.00 | 0.00 | 0.00 | 0.04 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1489.531 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1489.531 | 100.00 |
Total On-Site and Utility Electric Sources | 1489.531 | 100.00 |
Total Electricity End Uses | 1489.531 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 87.30 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 87.30 | 100.00 |
Total Water End Uses | 87.30 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 9.33 |
Time Setpoint Not Met During Occupied Cooling | 0.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 2944.67 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Meter |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2006
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Meter |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTRIPMALL
| Meter |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 7
| Meter |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_INTERNATIONALFALLS
| Meter |ZoneCoolingSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ZoneHeatingSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ZoneElectricSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |SpaceGainsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |PeakSpaceGainsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |SpaceGainComponentsAtCoolingPeakMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ComfortReportSimple55Monthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |OccupantComfortDataSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |DXReportMonthly
| PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL |WindowReportMonthly
| LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR |WindowEnergyReportMonthly
| LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR |WindowZoneSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |WindowEnergyZoneSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| GAS TANK1 | GAS TANK2 | GAS TANK3 | GAS TANK4 | GAS TANK5 | GAS TANK6 | GAS TANK7 |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC_1:1_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_2:2_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_3:3_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_4:4_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_5:5_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_6:6_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_7:7_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_8:8_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_9:9_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_10:10_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL |FanReportMonthly
| PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN |ZoneTemperatureOscillationReportMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |MechanicalVentilationLoadsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2020-06-03 19:20:47
GeneralValue | |
Program Version and Build | EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:20 |
RunPeriod | RUNPERIOD 1 |
Weather File | International Falls Intl Ap MN USA TMY3 WMO#=727470 |
Latitude [deg] | 48.57 |
Longitude [deg] | -93.4 |
Elevation [m] | 359.00 |
Time Zone | -6.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Above Ground Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Window Opening Area [m2] | 124.29 | 0.00 | 0.00 | 124.29 | 0.00 |
Gross Window-Wall Ratio [%] | 10.50 | 0.00 | 0.00 | 26.24 | 0.00 |
Above Ground Window-Wall Ratio [%] | 10.50 | 0.00 | 0.00 | 26.24 | 0.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Above Ground Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Window Opening Area [m2] | 124.29 | 0.00 | 0.00 | 124.29 | 0.00 |
Gross Window-Wall Ratio [%] | 10.50 | 0.00 | 0.00 | 26.24 | 0.00 |
Above Ground Window-Wall Ratio [%] | 10.50 | 0.00 | 0.00 | 26.24 | 0.00 |
Total | |
Gross Roof Area [m2] | 2090.32 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
LGSTORE1 | 348.39 | Yes | Yes | 1805.20 | 1.00 | 276.30 | 0.00 | 20.75 | 20.75 | 28.8173 | 11.61 | 4.3000 |
SMSTORE1 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.37 | 10.37 | 28.8173 | 11.61 | 4.3000 |
SMSTORE2 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.35 | 10.35 | 22.6280 | 11.61 | 4.3000 |
SMSTORE3 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.35 | 10.35 | 22.6280 | 11.61 | 4.3000 |
SMSTORE4 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.35 | 10.35 | 22.6280 | 11.61 | 4.3000 |
LGSTORE2 | 348.39 | Yes | Yes | 1805.20 | 1.00 | 157.89 | 0.00 | 20.70 | 20.70 | 18.3225 | 11.61 | 4.3000 |
SMSTORE5 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.35 | 10.35 | 18.3225 | 11.61 | 4.3000 |
SMSTORE6 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.35 | 10.35 | 18.3225 | 11.61 | 4.3000 |
SMSTORE7 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.35 | 10.35 | 18.3225 | 11.61 | 4.3000 |
SMSTORE8 | 174.19 | Yes | Yes | 902.60 | 1.00 | 197.36 | 0.00 | 10.35 | 10.35 | 18.3225 | 11.61 | 4.3000 |
Total | 2090.32 | 10831.20 | 1184.15 | 0.00 | 124.29 | 124.29 | 22.0226 | 11.61 | 4.3000 | |||
Conditioned Total | 2090.32 | 10831.20 | 1184.15 | 0.00 | 124.29 | 124.29 | 22.0226 | 11.61 | 4.3000 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:20:47
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 29-JUN-15:50 | 09-JAN-08:09 | - | - | - | 06-JAN-13:09 |
Heating | 0.00 | 510403.87 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 73735.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 43732.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 8089.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 18035.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 4795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 148388.75 | 510403.87 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 510403.87 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 73735.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 43732.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 8089.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 18035.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 4795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:20:47
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 1720.22 | 0.00 | 0.00 | 0.00 |
Cooling | 344.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 2244.57 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 527.55 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 407.66 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 979.09 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 213.80 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 4717.34 | 1720.22 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 822.95 | 0.00 | 0.00 | 0.00 |
Cooling | 164.89 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1073.80 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 252.38 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 195.02 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 468.39 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 102.28 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2256.76 | 822.95 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 822.95 | 0.00 | 0.00 | 0.00 |
Cooling | 164.89 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1073.80 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 252.38 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 195.02 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 468.39 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 102.28 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2256.76 | 822.95 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:20:47
AirTerminal:SingleDuct:UncontrolledDesign Size Maximum Air Flow Rate [m3/s] | |
LGSTORE1 DIRECT AIR | 2.57 |
SMSTORE1 DIRECT AIR | 1.33 |
SMSTORE2 DIRECT AIR | 1.34 |
SMSTORE3 DIRECT AIR | 1.35 |
SMSTORE4 DIRECT AIR | 1.35 |
LGSTORE2 DIRECT AIR | 2.49 |
SMSTORE5 DIRECT AIR | 1.37 |
SMSTORE6 DIRECT AIR | 1.37 |
SMSTORE7 DIRECT AIR | 1.38 |
SMSTORE8 DIRECT AIR | 1.53 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC_1:1 | 2.57 | 2.57 | 2.57 | 2.57 | 2.57 | 2.57 | 1.00 | 1.00 | 2.57 |
PSZ-AC_2:2 | 1.33 | 1.33 | 1.33 | 1.33 | 1.33 | 1.33 | 1.00 | 1.00 | 1.33 |
PSZ-AC_3:3 | 1.34 | 1.34 | 1.34 | 1.34 | 1.34 | 1.34 | 1.00 | 1.00 | 1.34 |
PSZ-AC_4:4 | 1.35 | 1.35 | 1.35 | 1.35 | 1.35 | 1.35 | 1.00 | 1.00 | 1.35 |
PSZ-AC_5:5 | 1.35 | 1.35 | 1.35 | 1.35 | 1.35 | 1.35 | 1.00 | 1.00 | 1.35 |
PSZ-AC_6:6 | 2.49 | 2.49 | 2.49 | 2.49 | 2.49 | 2.49 | 1.00 | 1.00 | 2.49 |
PSZ-AC_7:7 | 1.37 | 1.37 | 1.37 | 1.37 | 1.37 | 1.37 | 1.00 | 1.00 | 1.37 |
PSZ-AC_8:8 | 1.37 | 1.37 | 1.37 | 1.37 | 1.37 | 1.37 | 1.00 | 1.00 | 1.37 |
PSZ-AC_9:9 | 1.38 | 1.38 | 1.38 | 1.38 | 1.38 | 1.38 | 1.00 | 1.00 | 1.38 |
PSZ-AC_10:10 | 1.53 | 1.53 | 1.53 | 1.53 | 1.53 | 1.53 | 1.00 | 1.00 | 1.53 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC_1:1_OA_CONTROLLER | 2.57 | 0.530908 |
PSZ-AC_2:2_OA_CONTROLLER | 1.33 | 0.265454 |
PSZ-AC_3:3_OA_CONTROLLER | 1.34 | 0.265454 |
PSZ-AC_4:4_OA_CONTROLLER | 1.35 | 0.265454 |
PSZ-AC_5:5_OA_CONTROLLER | 1.35 | 0.265454 |
PSZ-AC_6:6_OA_CONTROLLER | 2.49 | 0.530908 |
PSZ-AC_7:7_OA_CONTROLLER | 1.37 | 0.265454 |
PSZ-AC_8:8_OA_CONTROLLER | 1.37 | 0.265454 |
PSZ-AC_9:9_OA_CONTROLLER | 1.38 | 0.265454 |
PSZ-AC_10:10_OA_CONTROLLER | 1.53 | 0.265454 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC_1:1_UNITARY_PACKAGE_DX | 2.57 | 2.57 | 2.57 | 2.57 | 53025.40 | 89352.93 | 40.00 | 1.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_DX | 1.33 | 1.33 | 1.33 | 1.33 | 27366.06 | 45813.83 | 40.00 | 1.00 |
PSZ-AC_3:3_UNITARY_PACKAGE_DX | 1.34 | 1.34 | 1.34 | 1.34 | 27909.67 | 45990.67 | 40.00 | 1.00 |
PSZ-AC_4:4_UNITARY_PACKAGE_DX | 1.35 | 1.35 | 1.35 | 1.35 | 27992.76 | 46056.33 | 40.00 | 1.00 |
PSZ-AC_5:5_UNITARY_PACKAGE_DX | 1.35 | 1.35 | 1.35 | 1.35 | 28171.51 | 46215.82 | 40.00 | 1.00 |
PSZ-AC_6:6_UNITARY_PACKAGE_DX | 2.49 | 2.49 | 2.49 | 2.49 | 52565.71 | 87663.62 | 40.00 | 1.00 |
PSZ-AC_7:7_UNITARY_PACKAGE_DX | 1.37 | 1.37 | 1.37 | 1.37 | 28884.68 | 46619.67 | 40.00 | 1.00 |
PSZ-AC_8:8_UNITARY_PACKAGE_DX | 1.37 | 1.37 | 1.37 | 1.37 | 28915.04 | 46595.59 | 40.00 | 1.00 |
PSZ-AC_9:9_UNITARY_PACKAGE_DX | 1.38 | 1.38 | 1.38 | 1.38 | 29225.78 | 46832.46 | 40.00 | 1.00 |
PSZ-AC_10:10_UNITARY_PACKAGE_DX | 1.53 | 1.53 | 1.53 | 1.53 | 32568.42 | 49994.47 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | Speed 2 Design Size Rated Total Cooling Capacity [W] | Speed 2 User-Specified Rated Total Cooling Capacity [W] | Speed 1 Design Size Rated Total Cooling Capacity [W] | Speed 1 User-Specified Rated Total Cooling Capacity [W] | Speed 2 Design Size Rated Sensible Heat Ratio | Speed 2 User-Specified Rated Sensible Heat Ratio | Speed 1 Design Size Rated Sensible Heat Ratio | Speed 1 User-Specified Rated Sensible Heat Ratio | |
PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | 2.57 | 1.28 | 2.57 | 49824.17 | 53025.40 | 26512.70 | 53025.40 | 0.725541 | 0.725540 | 0.725540 | 0.725540 |
PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | 1.33 | 0.667495 | 1.33 | 25697.27 | 27366.06 | 13683.03 | 27366.06 | 0.727891 | 0.727890 | 0.727890 | 0.727890 |
PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | 1.34 | 0.671530 | 1.34 | 26236.85 | 27909.67 | 13954.83 | 27909.67 | 0.723868 | 0.723870 | 0.723870 | 0.723870 |
PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | 1.35 | 0.673025 | 1.35 | 26316.40 | 27992.76 | 13996.38 | 27992.76 | 0.723649 | 0.723650 | 0.723650 | 0.723650 |
PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | 1.35 | 0.676665 | 1.35 | 26486.55 | 28171.51 | 14085.75 | 28171.51 | 0.723365 | 0.723370 | 0.723370 | 0.723370 |
PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | 2.49 | 1.24 | 2.49 | 49478.64 | 52565.71 | 26282.85 | 52565.71 | 0.719192 | 0.719190 | 0.719190 | 0.719190 |
PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | 1.37 | 0.685885 | 1.37 | 27182.15 | 28884.68 | 14442.34 | 28884.68 | 0.720032 | 0.720030 | 0.720030 | 0.720030 |
PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | 1.37 | 0.685335 | 1.37 | 27214.71 | 28915.04 | 14457.52 | 28915.04 | 0.719497 | 0.719500 | 0.719500 | 0.719500 |
PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | 1.38 | 0.690740 | 1.38 | 27513.33 | 29225.78 | 14612.89 | 29225.78 | 0.718681 | 0.718680 | 0.718680 | 0.718680 |
PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | 1.53 | 0.762880 | 1.53 | 30681.52 | 32568.42 | 16284.21 | 32568.42 | 0.716116 | 0.716120 | 0.716120 | 0.716120 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | 2.57 | 2808.76 |
PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | 1.33 | 1522.03 |
PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | 1.34 | 1531.23 |
PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | 1.35 | 1534.65 |
PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | 1.35 | 1542.95 |
PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | 2.49 | 2724.40 |
PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | 1.37 | 1563.96 |
PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | 1.37 | 1562.71 |
PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | 1.38 | 1575.04 |
PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | 1.53 | 1669.96 |
Design Size Nominal Capacity [W] | |
PSZ-AC_1:1_UNITARY_PACKAGE_HEATCOIL | 89352.93 |
PSZ-AC_2:2_UNITARY_PACKAGE_HEATCOIL | 45813.83 |
PSZ-AC_3:3_UNITARY_PACKAGE_HEATCOIL | 45990.67 |
PSZ-AC_4:4_UNITARY_PACKAGE_HEATCOIL | 46056.33 |
PSZ-AC_5:5_UNITARY_PACKAGE_HEATCOIL | 46215.82 |
PSZ-AC_6:6_UNITARY_PACKAGE_HEATCOIL | 87663.62 |
PSZ-AC_7:7_UNITARY_PACKAGE_HEATCOIL | 46619.67 |
PSZ-AC_8:8_UNITARY_PACKAGE_HEATCOIL | 46595.59 |
PSZ-AC_9:9_UNITARY_PACKAGE_HEATCOIL | 46832.46 |
PSZ-AC_10:10_UNITARY_PACKAGE_HEATCOIL | 49994.47 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:20:47
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
LGSTORE1_WALL_3 | LGSTORE1_WALL_3_DOOR_1 | LGSTORE1_WALL_3_DOOR_2 | |
LGSTORE1_WALL_1 | LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | |
SMSTORE1_WALL_1 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | |
SMSTORE1_WALL_3 | SMSTORE1_WALL_3_DOOR | |
SMSTORE2_WALL_1 | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | |
SMSTORE2_WALL_3 | SMSTORE2_WALL_3_DOOR | |
SMSTORE3_WALL_1 | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | |
SMSTORE3_WALL_3 | SMSTORE3_WALL_3_DOOR | |
SMSTORE4_WALL_1 | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | |
SMSTORE4_WALL_3 | SMSTORE4_WALL_3_DOOR | |
LGSTORE2_WALL_3 | LGSTORE2_WALL_3_DOOR_1 | LGSTORE2_WALL_3_DOOR_2 | |
LGSTORE2_WALL_1 | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | |
SMSTORE5_WALL_1 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | |
SMSTORE5_WALL_3 | SMSTORE5_WALL_3_DOOR | |
SMSTORE6_WALL_1 | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | |
SMSTORE6_WALL_3 | SMSTORE6_WALL_3_DOOR | |
SMSTORE7_WALL_1 | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | |
SMSTORE7_WALL_3 | SMSTORE7_WALL_3_DOOR | |
SMSTORE8_WALL_1 | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR | |
SMSTORE8_WALL_3 | SMSTORE8_WALL_3_DOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2020-06-03 19:20:47
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2020-06-03 19:20:47
VersionVersion ID | |
1 | 9.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 5.40 | -2.00 | -14.60 | -16.90 | -11.50 | -6.20 | 4.00 | 13.40 | 18.00 | 19.70 | 17.90 | 12.30 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | International Falls Intl Ap MN USA TMY3 WMO#=727470 | 48.57 | -93.40 | -6.00 | 359.00 | 97086 | 1.1539 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 3.29 | 36.60 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RetailStripmall | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 10 | 118 | 48 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | LGSTORE1 | 0.0 | 0.00 | 0.00 | 0.00 | 7.62 | 11.43 | 2.59 | 1 | 1 | 1 | 0.00 | 15.24 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 1805.20 | TARP | TARP | 348.39 | 276.30 | 247.76 | 20.75 | 6 | 8 | 0 | Yes |
2 | SMSTORE1 | 0.0 | 0.00 | 0.00 | 0.00 | 19.05 | 11.43 | 2.59 | 1 | 1 | 1 | 15.24 | 22.86 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.67 | 10.37 | 6 | 4 | 0 | Yes |
3 | SMSTORE2 | 0.0 | 0.00 | 0.00 | 0.00 | 26.67 | 11.43 | 2.59 | 1 | 1 | 1 | 22.86 | 30.48 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.35 | 6 | 4 | 0 | Yes |
4 | SMSTORE3 | 0.0 | 0.00 | 0.00 | 0.00 | 34.29 | 11.43 | 2.59 | 1 | 1 | 1 | 30.48 | 38.10 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.35 | 6 | 4 | 0 | Yes |
5 | SMSTORE4 | 0.0 | 0.00 | 0.00 | 0.00 | 41.91 | 11.43 | 2.59 | 1 | 1 | 1 | 38.10 | 45.72 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.35 | 6 | 4 | 0 | Yes |
6 | LGSTORE2 | 0.0 | 0.00 | 0.00 | 0.00 | 53.34 | 11.43 | 2.59 | 1 | 1 | 1 | 45.72 | 60.96 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 1805.20 | TARP | TARP | 348.39 | 157.89 | 129.43 | 20.70 | 6 | 8 | 0 | Yes |
7 | SMSTORE5 | 0.0 | 0.00 | 0.00 | 0.00 | 64.77 | 11.43 | 2.59 | 1 | 1 | 1 | 60.96 | 68.58 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.35 | 6 | 4 | 0 | Yes |
8 | SMSTORE6 | 0.0 | 0.00 | 0.00 | 0.00 | 72.39 | 11.43 | 2.59 | 1 | 1 | 1 | 68.58 | 76.20 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.35 | 6 | 4 | 0 | Yes |
9 | SMSTORE7 | 0.0 | 0.00 | 0.00 | 0.00 | 80.01 | 11.43 | 2.59 | 1 | 1 | 1 | 76.20 | 83.82 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.35 | 6 | 4 | 0 | Yes |
10 | SMSTORE8 | 0.0 | 0.00 | 0.00 | 0.00 | 87.63 | 11.43 | 2.59 | 1 | 1 | 1 | 83.82 | 91.44 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 197.36 | 183.13 | 10.35 | 6 | 4 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | LGSTORE1 | 348.39 | 30.0 | 11.614 | 8.610E-002 | 28.817 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 33.117 | No |
2 | SMSTORE1 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 28.817 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 33.117 | No |
3 | SMSTORE2 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 22.628 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 26.928 | No |
4 | SMSTORE3 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 22.628 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 26.928 | No |
5 | SMSTORE4 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 22.628 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 26.928 | No |
6 | LGSTORE2 | 348.39 | 30.0 | 11.614 | 8.610E-002 | 18.322 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 22.622 | No |
7 | SMSTORE5 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 18.322 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 22.622 | No |
8 | SMSTORE6 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 18.322 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 22.622 | No |
9 | SMSTORE7 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 18.322 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 22.622 | No |
10 | SMSTORE8 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 18.322 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 22.622 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | |
1 | LGSTORE1 | TYPE1_OCC_SCH | LGSTORE1 | 348.39 | 30.0 | 30.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 30 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
2 | SMSTORE1 | TYPE1_OCC_SCH | SMSTORE1 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
3 | SMSTORE2 | TYPE2_OCC_SCH | SMSTORE2 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
4 | SMSTORE3 | TYPE2_OCC_SCH | SMSTORE3 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
5 | SMSTORE4 | TYPE2_OCC_SCH | SMSTORE4 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
6 | LGSTORE2 | TYPE3_OCC_SCH | LGSTORE2 | 348.39 | 30.0 | 30.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 30 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
7 | SMSTORE5 | TYPE3_OCC_SCH | SMSTORE5 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
8 | SMSTORE6 | TYPE3_OCC_SCH | SMSTORE6 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
9 | SMSTORE7 | TYPE3_OCC_SCH | SMSTORE7 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
10 | SMSTORE8 | TYPE3_OCC_SCH | SMSTORE8 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | LGSTORE1_LIGHTS | TYPE1_LIGHT_SCH | LGSTORE1 | 348.39 | 30.0 | 6383.296 | 18.322 | 212.804 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 6383.296 |
2 | LGSTORE1_LIGHTS_ALLOWANCE | TYPE1_LIGHT_SCH | LGSTORE1 | 348.39 | 30.0 | 3656.252 | 10.495 | 121.891 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3656.252 |
3 | SMSTORE1_LIGHTS | TYPE1_LIGHT_SCH | SMSTORE1 | 174.19 | 15.0 | 3191.648 | 18.322 | 212.805 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3191.648 |
4 | SMSTORE1_LIGHTS_ALLOWANCE | TYPE1_LIGHT_SCH | SMSTORE1 | 174.19 | 15.0 | 1828.126 | 10.495 | 121.891 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1828.126 |
5 | SMSTORE2_LIGHTS | TYPE2_LIGHT_SCH | SMSTORE2 | 174.19 | 15.0 | 3191.648 | 18.322 | 212.805 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3191.648 |
6 | SMSTORE2_LIGHTS_ALLOWANCE | TYPE2_LIGHT_SCH | SMSTORE2 | 174.19 | 15.0 | 750.000 | 4.306 | 50.007 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 750.000 |
7 | SMSTORE3_LIGHTS | TYPE2_LIGHT_SCH | SMSTORE3 | 174.19 | 15.0 | 3191.648 | 18.322 | 212.805 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3191.648 |
8 | SMSTORE3_LIGHTS_ALLOWANCE | TYPE2_LIGHT_SCH | SMSTORE3 | 174.19 | 15.0 | 750.000 | 4.306 | 50.007 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 750.000 |
9 | SMSTORE4_LIGHTS | TYPE2_LIGHT_SCH | SMSTORE4 | 174.19 | 15.0 | 3191.648 | 18.322 | 212.805 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3191.648 |
10 | SMSTORE4_LIGHTS_ALLOWANCE | TYPE2_LIGHT_SCH | SMSTORE4 | 174.19 | 15.0 | 750.000 | 4.306 | 50.007 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 750.000 |
11 | LGSTORE2_LIGHTS | TYPE3_LIGHT_SCH | LGSTORE2 | 348.39 | 30.0 | 6383.296 | 18.322 | 212.804 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 6383.296 |
12 | LGSTORE2_LIGHTS_ALLOWANCE | TYPE3_LIGHT_SCH | LGSTORE2 | 348.39 | 30.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
13 | SMSTORE5_LIGHTS | TYPE3_LIGHT_SCH | SMSTORE5 | 174.19 | 15.0 | 3191.648 | 18.322 | 212.805 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3191.648 |
14 | SMSTORE5_LIGHTS_ALLOWANCE | TYPE3_LIGHT_SCH | SMSTORE5 | 174.19 | 15.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
15 | SMSTORE6_LIGHTS | TYPE3_LIGHT_SCH | SMSTORE6 | 174.19 | 15.0 | 3191.648 | 18.322 | 212.805 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3191.648 |
16 | SMSTORE6_LIGHTS_ALLOWANCE | TYPE3_LIGHT_SCH | SMSTORE6 | 174.19 | 15.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
17 | SMSTORE7_LIGHTS | TYPE3_LIGHT_SCH | SMSTORE7 | 174.19 | 15.0 | 3191.648 | 18.322 | 212.805 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3191.648 |
18 | SMSTORE7_LIGHTS_ALLOWANCE | TYPE3_LIGHT_SCH | SMSTORE7 | 174.19 | 15.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
19 | SMSTORE8_LIGHTS | TYPE3_LIGHT_SCH | SMSTORE8 | 174.19 | 15.0 | 3191.648 | 18.322 | 212.805 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3191.648 |
20 | SMSTORE8_LIGHTS_ALLOWANCE | TYPE3_LIGHT_SCH | SMSTORE8 | 174.19 | 15.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | LGSTORE1_MISCPLUG_EQUIP | TYPE1_EQUIP_SCH | LGSTORE1 | 348.39 | 30.0 | 1498.062 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1498.062 |
2 | SMSTORE1_MISCPLUG_EQUIP | TYPE1_EQUIP_SCH | SMSTORE1 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
3 | SMSTORE2_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE2 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
4 | SMSTORE3_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE3 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
5 | SMSTORE4_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE4 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
6 | LGSTORE2_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | LGSTORE2 | 348.39 | 30.0 | 1498.062 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1498.062 |
7 | SMSTORE5_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE5 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
8 | SMSTORE6_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE6 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
9 | SMSTORE7_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE7 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
10 | SMSTORE8_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE8 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.975 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.2284 | 0.900 | 0.900 | 0.770 | 0.700 | Rough |
5 | NONRES_EXT_WALL | 20 | 4 | 7 | 0.167 | 0.3843 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
6 | LGSTORE1_FLOOR_FFACTOR | 30 | 2 | 7 | 0.167 | 0.1995 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
7 | SMSTORE1_FLOOR_FFACTOR | 31 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
8 | SMSTORE2_FLOOR_FFACTOR | 32 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | SMSTORE3_FLOOR_FFACTOR | 33 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
10 | SMSTORE4_FLOOR_FFACTOR | 34 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
11 | LGSTORE2_FLOOR_FFACTOR | 35 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | SMSTORE5_FLOOR_FFACTOR | 36 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | SMSTORE6_FLOOR_FFACTOR | 37 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | SMSTORE7_FLOOR_FFACTOR | 38 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | SMSTORE8_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.2888 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2516 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
6 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.319 |
7 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
8 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
9 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
10 | NONRES_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.368 |
11 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
12 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.937 |
13 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
14 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
15 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
16 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
17 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
18 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
19 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
20 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
21 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
22 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
23 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
24 | ~FC_Insulation_7 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_8 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_9 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
30 | ~FC_Insulation_10 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.386 |
31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.9747885 | 3.9747885 | 3.9747885 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
14 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
15 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
16 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
17 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
18 | 3 | -0.62451068E-06 | 0.10350887E-08 | -0.38276125E-05 | 0.11995084E-16 |
19 | 2 | 0.77976586 | 0.13989883E-02 | 1.0579789 | -0.73382352E-06 |
20 | 1 | -21.958702 | 0.93426804E-01 | -6.3215779 | 0.20283230 |
21 | 0 | 21.361010 | 0.87247630E-01 | 5.4456762 | |
22 | 7 | -0.35963630E-12 | 0.61482467E-15 | -0.13288964E-12 | 0.15093609E-15 |
23 | 6 | 0.33258387E-07 | 0.11249777E-09 | 0.75805110E-08 | -0.16019892E-12 |
24 | 5 | -0.21313350E-03 | 0.93714421E-06 | -0.10927814E-03 | 0.74776115E-08 |
25 | 4 | 0.31870195 | 0.44521373E-03 | 0.10925225 | -0.37358013E-04 |
26 | 3 | -7.7913368 | 0.13499397E-01 | -2.4947666 | 0.31584435E-01 |
27 | 2 | 42.601618 | 0.47079245E-01 | 15.902165 | -0.35261900 |
28 | 1 | -81.870774 | 0.20888078E-01 | -29.712230 | 1.1068570 |
29 | 0 | 46.824331 | 0.41326549E-03 | 16.278015 | |
30 | 7 | -0.21163652E-08 | -0.68723841E-15 | 0.43910983E-14 | -0.57684426E-16 |
31 | 6 | 0.56109385E-05 | 0.38186281E-08 | 0.31898696E-02 | -0.26759299E-04 |
32 | 5 | -0.40164657E-03 | 0.22608617E-05 | -0.22372456 | 0.19561502E-02 |
33 | 4 | 0.92272104E-02 | 0.10289840E-03 | 4.8295456 | -0.45264980E-01 |
34 | 3 | -0.80993241E-01 | 0.81813938E-03 | -38.021416 | 0.39865375 |
35 | 2 | 0.28754352 | 0.13608947E-02 | 116.48395 | -1.4179393 |
36 | 1 | -0.41499682 | 0.41453381E-03 | -143.90731 | 2.0490399 |
37 | 0 | 0.20232414 | 0.10048102E-04 | 60.838472 | |
38 | 7 | -0.37862368E-08 | -0.38757603E-14 | 0.11479940E-14 | -0.41635801E-16 |
39 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
40 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
41 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
42 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
43 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
44 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
45 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
46 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479937E-14 | -0.41635796E-16 |
47 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
48 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
49 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
50 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
51 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
52 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
53 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
54 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479940E-14 | -0.41635801E-16 |
55 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
56 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
57 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
58 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
59 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
60 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
61 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
62 | 7 | -0.37862368E-08 | -0.38757603E-14 | 0.11479940E-14 | -0.41635801E-16 |
63 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
64 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
65 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
66 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
67 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
68 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
69 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
70 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479937E-14 | -0.41635796E-16 |
71 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
72 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
73 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
74 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
75 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
76 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
77 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
78 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479937E-14 | -0.41635796E-16 |
79 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
80 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
81 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
82 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
83 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
84 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
85 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
86 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479940E-14 | -0.41635801E-16 |
87 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
88 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
89 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
90 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
91 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
92 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
93 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
94 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479936E-14 | -0.41635794E-16 |
95 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
96 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
97 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
98 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
99 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
100 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
101 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
102 | 7 | -0.14484255E-08 | -0.22640907E-15 | 0.11860658E-13 | -0.17473455E-15 |
103 | 6 | 0.80640390E-05 | 0.55493782E-08 | 0.31828288E-02 | -0.26700235E-04 |
104 | 5 | -0.58275339E-03 | 0.32892043E-05 | -0.22332434 | 0.19526176E-02 |
105 | 4 | 0.13421983E-01 | 0.14977251E-03 | 4.8228790 | -0.45200897E-01 |
106 | 3 | -0.11791368 | 0.11914425E-02 | -37.983753 | 0.39823745 |
107 | 2 | 0.41875064 | 0.19825898E-02 | 116.41064 | -1.4169588 |
108 | 1 | -0.60444169 | 0.60433957E-03 | -143.86415 | 2.0483306 |
109 | 0 | 0.29470347 | 0.14596444E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.46_SHGC_0.45 | 29 | 1 | VerySmooth | 2.615 | 0.446 | 0.367 | 0.451 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 2.53892E-002 | 0.36619 | 0.42302 | 0.42302 | 0.45000 | 0.13324 | 0.16828 | 0.00000 | 0.84000 | 0.84000 | 0.12001 | 1.00000 | No |
Calculation Method | Value {days} | Allowable Number Figures in Shadow Overlap {} | Polygon Clipping Algorithm | Sky Diffuse Modeling Algorithm | External Shading Calculation Method | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | AverageOverDaysInFrequency | 30 | 15000 | SutherlandHodgman | SimpleSkyDiffuseModeling | InternalCalculation | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | GAS TANK1 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
2 | WaterHeater:Mixed | GAS TANK2 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
3 | WaterHeater:Mixed | GAS TANK3 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
4 | WaterHeater:Mixed | GAS TANK4 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
5 | WaterHeater:Mixed | GAS TANK5 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
6 | WaterHeater:Mixed | GAS TANK6 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
7 | WaterHeater:Mixed | GAS TANK7 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | LGSTORE1_WALL_2 | 0 | 118.41 | 56.08 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 4 | No | No |
2 | LGSTORE1_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 4 | No | No |
3 | LGSTORE1_WALL_3_DOOR_1 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 0 | No | No |
4 | LGSTORE1_WALL_3_DOOR_2 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 0 | No | No |
5 | LGSTORE1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 0 | No | No |
6 | LGSTORE1_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 4 | No | No |
7 | LGSTORE1_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 1 | No | No |
8 | LGSTORE1_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 1 | No | No |
9 | LGSTORE1_WALL_1_WINDOW_3 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 1 | No | No |
10 | LGSTORE1_WALL_1_WINDOW_4 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 1 | No | No |
11 | LGSTORE1_WALL_1_DOOR_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 1 | No | No |
12 | LGSTORE1_WALL_1_DOOR_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 1 | No | No |
13 | LGSTORE1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 0 | No | No |
14 | LGSTORE1_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 0 | No | No |
15 | LGSTORE1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 0 | No | No |
16 | SMSTORE1_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
17 | SMSTORE1_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
18 | SMSTORE1_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
19 | SMSTORE1_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
20 | SMSTORE1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
21 | SMSTORE1_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
22 | SMSTORE1_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
23 | SMSTORE1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
24 | SMSTORE1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
25 | SMSTORE1_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
26 | SMSTORE1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
27 | SMSTORE2_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
28 | SMSTORE2_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
29 | SMSTORE2_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
30 | SMSTORE2_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
31 | SMSTORE2_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
32 | SMSTORE2_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
33 | SMSTORE2_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
34 | SMSTORE2_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
35 | SMSTORE2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
36 | SMSTORE2_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
37 | SMSTORE2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
38 | SMSTORE3_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
39 | SMSTORE3_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
40 | SMSTORE3_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
41 | SMSTORE3_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
42 | SMSTORE3_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
43 | SMSTORE3_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
44 | SMSTORE3_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
45 | SMSTORE3_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
46 | SMSTORE3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
47 | SMSTORE3_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
48 | SMSTORE3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
49 | SMSTORE4_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
50 | SMSTORE4_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
51 | SMSTORE4_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
52 | SMSTORE4_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
53 | SMSTORE4_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
54 | SMSTORE4_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 3 | No | No |
55 | SMSTORE4_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
56 | SMSTORE4_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
57 | SMSTORE4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
58 | SMSTORE4_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
59 | SMSTORE4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
60 | LGSTORE2_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
61 | LGSTORE2_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 4 | No | No |
62 | LGSTORE2_WALL_3_DOOR_1 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
63 | LGSTORE2_WALL_3_DOOR_2 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
64 | LGSTORE2_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
65 | LGSTORE2_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 4 | No | No |
66 | LGSTORE2_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
67 | LGSTORE2_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
68 | LGSTORE2_WALL_1_WINDOW_3 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
69 | LGSTORE2_WALL_1_WINDOW_4 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
70 | LGSTORE2_WALL_1_DOOR_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
71 | LGSTORE2_WALL_1_DOOR_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
72 | LGSTORE2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
73 | LGSTORE2_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
74 | LGSTORE2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
75 | SMSTORE5_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
76 | SMSTORE5_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
77 | SMSTORE5_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
78 | SMSTORE5_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
79 | SMSTORE5_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
80 | SMSTORE5_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
81 | SMSTORE5_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
82 | SMSTORE5_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
83 | SMSTORE5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
84 | SMSTORE5_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
85 | SMSTORE5_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
86 | SMSTORE6_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
87 | SMSTORE6_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
88 | SMSTORE6_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
89 | SMSTORE6_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
90 | SMSTORE6_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
91 | SMSTORE6_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
92 | SMSTORE6_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
93 | SMSTORE6_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
94 | SMSTORE6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
95 | SMSTORE6_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
96 | SMSTORE6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
97 | SMSTORE7_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
98 | SMSTORE7_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
99 | SMSTORE7_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
100 | SMSTORE7_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
101 | SMSTORE7_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
102 | SMSTORE7_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 3 | No | No |
103 | SMSTORE7_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
104 | SMSTORE7_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
105 | SMSTORE7_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
106 | SMSTORE7_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
107 | SMSTORE7_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
108 | SMSTORE8_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 4 | No | No |
109 | SMSTORE8_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 1 | No | No |
110 | SMSTORE8_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 1 | No | No |
111 | SMSTORE8_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 1 | No | No |
112 | SMSTORE8_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
113 | SMSTORE8_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 3 | No | No |
114 | SMSTORE8_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
115 | SMSTORE8_WALL_4 | 0 | 118.41 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 3 | No | No |
116 | SMSTORE8_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
117 | SMSTORE8_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
118 | SMSTORE8_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | LGSTORE1_INFILTRATION | TYPE1_INFIL_SCH | LGSTORE1 | 348.39 | 30.0 | 0.286 | 8.224E-004 | 4.530E-004 | 0.571 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | LGSTORE1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | LGSTORE1 | 348.39 | 30.0 | 0.389 | 1.116E-003 | 6.149E-004 | 0.776 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | SMSTORE1_INFILTRATION | TYPE1_INFIL_SCH | SMSTORE1 | 174.19 | 15.0 | 8.210E-002 | 4.713E-004 | 3.194E-004 | 0.327 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | SMSTORE1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE1 | 174.19 | 15.0 | 0.222 | 1.276E-003 | 8.648E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
5 | SMSTORE2_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE2 | 174.19 | 15.0 | 8.210E-002 | 4.713E-004 | 3.194E-004 | 0.327 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | SMSTORE2_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE2 | 174.19 | 15.0 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
7 | SMSTORE3_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE3 | 174.19 | 15.0 | 8.210E-002 | 4.713E-004 | 3.194E-004 | 0.327 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | SMSTORE3_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE3 | 174.19 | 15.0 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | SMSTORE4_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE4 | 174.19 | 15.0 | 8.210E-002 | 4.713E-004 | 3.194E-004 | 0.327 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | SMSTORE4_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE4 | 174.19 | 15.0 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
11 | LGSTORE2_INFILTRATION | TYPE3_INFIL_SCH | LGSTORE2 | 348.39 | 30.0 | 0.164 | 4.713E-004 | 3.194E-004 | 0.327 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | LGSTORE2_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | LGSTORE2 | 348.39 | 30.0 | 0.389 | 1.116E-003 | 7.565E-004 | 0.776 | 1.000 | 0.000 | 0.000 | 0.000 |
13 | SMSTORE5_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE5 | 174.19 | 15.0 | 8.210E-002 | 4.713E-004 | 3.194E-004 | 0.327 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | SMSTORE5_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE5 | 174.19 | 15.0 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
15 | SMSTORE6_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE6 | 174.19 | 15.0 | 8.210E-002 | 4.713E-004 | 3.194E-004 | 0.327 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | SMSTORE6_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE6 | 174.19 | 15.0 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
17 | SMSTORE7_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE7 | 174.19 | 15.0 | 8.210E-002 | 4.713E-004 | 3.194E-004 | 0.327 | 0.000 | 0.000 | 0.224 | 0.000 |
18 | SMSTORE7_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE7 | 174.19 | 15.0 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
19 | SMSTORE8_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE8 | 174.19 | 15.0 | 0.204 | 1.172E-003 | 5.440E-004 | 0.815 | 0.000 | 0.000 | 0.224 | 0.000 |
20 | SMSTORE8_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE8 | 174.19 | 15.0 | 0.222 | 1.276E-003 | 5.921E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | LGSTORE1 | Mixing/Well-Stirred |
2 | SMSTORE1 | Mixing/Well-Stirred |
3 | SMSTORE2 | Mixing/Well-Stirred |
4 | SMSTORE3 | Mixing/Well-Stirred |
5 | SMSTORE4 | Mixing/Well-Stirred |
6 | LGSTORE2 | Mixing/Well-Stirred |
7 | SMSTORE5 | Mixing/Well-Stirred |
8 | SMSTORE6 | Mixing/Well-Stirred |
9 | SMSTORE7 | Mixing/Well-Stirred |
10 | SMSTORE8 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone LGSTORE1 | 1.2000 |
3 | Zone SMSTORE1 | 1.2000 |
4 | Zone SMSTORE2 | 1.2000 |
5 | Zone SMSTORE3 | 1.2000 |
6 | Zone SMSTORE4 | 1.2000 |
7 | Zone LGSTORE2 | 1.2000 |
8 | Zone SMSTORE5 | 1.2000 |
9 | Zone SMSTORE6 | 1.2000 |
10 | Zone SMSTORE7 | 1.2000 |
11 | Zone SMSTORE8 | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone LGSTORE1 | 1.2000 |
3 | Zone SMSTORE1 | 1.2000 |
4 | Zone SMSTORE2 | 1.2000 |
5 | Zone SMSTORE3 | 1.2000 |
6 | Zone SMSTORE4 | 1.2000 |
7 | Zone LGSTORE2 | 1.2000 |
8 | Zone SMSTORE5 | 1.2000 |
9 | Zone SMSTORE6 | 1.2000 |
10 | Zone SMSTORE7 | 1.2000 |
11 | Zone SMSTORE8 | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | LGSTORE1 | Cooling | 23685.57185 | 28422.68622 | 1.81409 | 2.17691 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 30.10000 | 1.27032E-002 | 348.38640 | 29.99610 | 0.53091 | 0.00000 |
2 | LGSTORE1 | Heating | 47552.48604 | 57062.98325 | 2.13853 | 2.56624 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -32.70000 | 1.83376E-004 | 348.38640 | 29.99610 | 0.53091 | 0.00000 |
3 | SMSTORE1 | Cooling | 12570.55492 | 15084.66590 | 0.96279 | 1.15535 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 29.99667 | 1.27032E-002 | 174.19320 | 14.99800 | 0.26545 | 0.00000 |
4 | SMSTORE1 | Heating | 24738.23927 | 29685.88712 | 1.11249 | 1.33499 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -32.70000 | 1.83376E-004 | 174.19320 | 14.99800 | 0.26545 | 0.00000 |
5 | SMSTORE2 | Cooling | 11842.35259 | 14210.82311 | 0.90702 | 1.08842 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 29.99667 | 1.27032E-002 | 174.19320 | 14.99800 | 0.26545 | 0.00000 |
6 | SMSTORE2 | Heating | 24887.77509 | 29865.33011 | 1.11921 | 1.34306 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -32.70000 | 1.83376E-004 | 174.19320 | 14.99800 | 0.26545 | 0.00000 |
7 | SMSTORE3 | Cooling | 11804.60598 | 14165.52717 | 0.90412 | 1.08495 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 29.99667 | 1.27032E-002 | 174.19320 | 14.99800 | 0.26545 | 0.00000 |
8 | SMSTORE3 | Heating | 24943.30651 | 29931.96782 | 1.12171 | 1.34605 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -32.70000 | 1.83376E-004 | 174.19320 | 14.99800 | 0.26545 | 0.00000 |
9 | SMSTORE4 | Cooling | 11755.10127 | 14106.12152 | 0.90033 | 1.08040 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 29.99667 | 1.27032E-002 | 174.19320 | 14.99800 | 0.26545 | 0.00000 |
10 | SMSTORE4 | Heating | 25078.17011 | 30093.80414 | 1.12778 | 1.35333 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -32.70000 | 1.83376E-004 | 174.19320 | 14.99800 | 0.26545 | 0.00000 |
11 | LGSTORE2 | Cooling | 21501.41699 | 25801.70039 | 1.64678 | 1.97614 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 29.99667 | 1.27032E-002 | 348.38640 | 29.99610 | 0.53091 | 0.00000 |
12 | LGSTORE2 | Heating | 46123.82874 | 55348.59449 | 2.07430 | 2.48916 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -32.70000 | 1.83376E-004 | 348.38640 | 29.99610 | 0.53091 | 0.00000 |
13 | SMSTORE5 | Cooling | 11193.35071 | 13432.02085 | 0.85731 | 1.02877 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 29.99667 | 1.27032E-002 | 174.19320 | 14.99800 | 0.26545 | 0.00000 |
14 | SMSTORE5 | Heating | 25419.66766 | 30503.60120 | 1.14314 | 1.37177 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -32.70000 | 1.83376E-004 | 174.19320 | 14.99800 | 0.26545 | 0.00000 |
15 | SMSTORE6 | Cooling | 11105.48328 | 13326.57993 | 0.85058 | 1.02069 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 29.99667 | 1.27032E-002 | 174.19320 | 14.99800 | 0.26545 | 0.00000 |
16 | SMSTORE6 | Heating | 25399.30390 | 30479.16468 | 1.14222 | 1.37067 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -32.70000 | 1.83376E-004 | 174.19320 | 14.99800 | 0.26545 | 0.00000 |
17 | SMSTORE7 | Cooling | 10972.70927 | 13167.25112 | 0.84041 | 1.00849 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 29.99667 | 1.27032E-002 | 174.19320 | 14.99800 | 0.26545 | 0.00000 |
18 | SMSTORE7 | Heating | 25599.61109 | 30719.53331 | 1.15123 | 1.38148 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -32.70000 | 1.83376E-004 | 174.19320 | 14.99800 | 0.26545 | 0.00000 |
19 | SMSTORE8 | Cooling | 10702.91861 | 12843.50233 | 0.81971 | 0.98365 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 29.68667 | 1.27032E-002 | 174.19320 | 14.99800 | 0.26545 | 0.00000 |
20 | SMSTORE8 | Heating | 28273.61496 | 33928.33795 | 1.27147 | 1.52576 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -32.70000 | 1.83376E-004 | 174.19320 | 14.99800 | 0.26545 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC_1:1 | Cooling | Sensible | 31808.54 | 2.17691 | 2.17691 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-AC_1:1 | Heating | Sensible | 89352.93 | 2.56624 | 2.56624 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
3 | PSZ-AC_2:2 | Cooling | Sensible | 16762.49 | 1.15535 | 1.15535 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-AC_2:2 | Heating | Sensible | 45813.83 | 1.33499 | 1.33499 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
5 | PSZ-AC_3:3 | Cooling | Sensible | 15900.64 | 1.08842 | 1.08842 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
6 | PSZ-AC_3:3 | Heating | Sensible | 45990.67 | 1.34306 | 1.34306 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
7 | PSZ-AC_4:4 | Cooling | Sensible | 15855.66 | 1.08495 | 1.08495 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
8 | PSZ-AC_4:4 | Heating | Sensible | 46056.33 | 1.34605 | 1.34605 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
9 | PSZ-AC_5:5 | Cooling | Sensible | 15797.12 | 1.08040 | 1.08040 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
10 | PSZ-AC_5:5 | Heating | Sensible | 46215.82 | 1.35333 | 1.35333 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
11 | PSZ-AC_6:6 | Cooling | Sensible | 29214.66 | 1.97614 | 1.97614 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
12 | PSZ-AC_6:6 | Heating | Sensible | 87663.62 | 2.48916 | 2.48916 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
13 | PSZ-AC_7:7 | Cooling | Sensible | 15131.05 | 1.02877 | 1.02877 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
14 | PSZ-AC_7:7 | Heating | Sensible | 46619.67 | 1.37177 | 1.37177 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
15 | PSZ-AC_8:8 | Cooling | Sensible | 15027.53 | 1.02069 | 1.02069 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
16 | PSZ-AC_8:8 | Heating | Sensible | 46595.59 | 1.37067 | 1.37067 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
17 | PSZ-AC_9:9 | Cooling | Sensible | 14871.26 | 1.00849 | 1.00849 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
18 | PSZ-AC_9:9 | Heating | Sensible | 46832.46 | 1.38148 | 1.38148 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
19 | PSZ-AC_10:10 | Cooling | Sensible | 14505.74 | 0.98365 | 0.98365 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
20 | PSZ-AC_10:10 | Heating | Sensible | 49994.47 | 1.52576 | 1.52576 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:Uncontrolled | LGSTORE1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.56624 |
2 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.33499 |
3 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE2 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.34306 |
4 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.34605 |
5 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE4 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.35333 |
6 | AirTerminal:SingleDuct:Uncontrolled | LGSTORE2 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.48916 |
7 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE5 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.37177 |
8 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.37067 |
9 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE7 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.38148 |
10 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE8 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.52576 |
11 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.56624 |
12 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.56624 |
13 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.56624 |
14 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 2.56624 |
15 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.56624 |
16 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Main Design Air Flow Rate [m3/s] | 2.56624 |
17 | AirLoopHVAC | PSZ-AC_1:1 | User Heating Air Flow Ratio [] | 1.00000 |
18 | AirLoopHVAC | PSZ-AC_1:1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
19 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.33499 |
20 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.33499 |
21 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.33499 |
22 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.33499 |
23 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.33499 |
24 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Main Design Air Flow Rate [m3/s] | 1.33499 |
25 | AirLoopHVAC | PSZ-AC_2:2 | User Heating Air Flow Ratio [] | 1.00000 |
26 | AirLoopHVAC | PSZ-AC_2:2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
27 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.34306 |
28 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.34306 |
29 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.34306 |
30 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.34306 |
31 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.34306 |
32 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Main Design Air Flow Rate [m3/s] | 1.34306 |
33 | AirLoopHVAC | PSZ-AC_3:3 | User Heating Air Flow Ratio [] | 1.00000 |
34 | AirLoopHVAC | PSZ-AC_3:3 | Calculated Heating Air Flow Ratio [] | 1.00000 |
35 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.34605 |
36 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.34605 |
37 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.34605 |
38 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.34605 |
39 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.34605 |
40 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Main Design Air Flow Rate [m3/s] | 1.34605 |
41 | AirLoopHVAC | PSZ-AC_4:4 | User Heating Air Flow Ratio [] | 1.00000 |
42 | AirLoopHVAC | PSZ-AC_4:4 | Calculated Heating Air Flow Ratio [] | 1.00000 |
43 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.35333 |
44 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.35333 |
45 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.35333 |
46 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.35333 |
47 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.35333 |
48 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Main Design Air Flow Rate [m3/s] | 1.35333 |
49 | AirLoopHVAC | PSZ-AC_5:5 | User Heating Air Flow Ratio [] | 1.00000 |
50 | AirLoopHVAC | PSZ-AC_5:5 | Calculated Heating Air Flow Ratio [] | 1.00000 |
51 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.48916 |
52 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.48916 |
53 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.48916 |
54 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Heating Design Air Flow Rate [m3/s] | 2.48916 |
55 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.48916 |
56 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Main Design Air Flow Rate [m3/s] | 2.48916 |
57 | AirLoopHVAC | PSZ-AC_6:6 | User Heating Air Flow Ratio [] | 1.00000 |
58 | AirLoopHVAC | PSZ-AC_6:6 | Calculated Heating Air Flow Ratio [] | 1.00000 |
59 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.37177 |
60 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.37177 |
61 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.37177 |
62 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.37177 |
63 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.37177 |
64 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Main Design Air Flow Rate [m3/s] | 1.37177 |
65 | AirLoopHVAC | PSZ-AC_7:7 | User Heating Air Flow Ratio [] | 1.00000 |
66 | AirLoopHVAC | PSZ-AC_7:7 | Calculated Heating Air Flow Ratio [] | 1.00000 |
67 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.37067 |
68 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.37067 |
69 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.37067 |
70 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.37067 |
71 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.37067 |
72 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Main Design Air Flow Rate [m3/s] | 1.37067 |
73 | AirLoopHVAC | PSZ-AC_8:8 | User Heating Air Flow Ratio [] | 1.00000 |
74 | AirLoopHVAC | PSZ-AC_8:8 | Calculated Heating Air Flow Ratio [] | 1.00000 |
75 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.38148 |
76 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.38148 |
77 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.38148 |
78 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.38148 |
79 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.38148 |
80 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Main Design Air Flow Rate [m3/s] | 1.38148 |
81 | AirLoopHVAC | PSZ-AC_9:9 | User Heating Air Flow Ratio [] | 1.00000 |
82 | AirLoopHVAC | PSZ-AC_9:9 | Calculated Heating Air Flow Ratio [] | 1.00000 |
83 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.52576 |
84 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.52576 |
85 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.52576 |
86 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.52576 |
87 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.52576 |
88 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Main Design Air Flow Rate [m3/s] | 1.52576 |
89 | AirLoopHVAC | PSZ-AC_10:10 | User Heating Air Flow Ratio [] | 1.00000 |
90 | AirLoopHVAC | PSZ-AC_10:10 | Calculated Heating Air Flow Ratio [] | 1.00000 |
91 | AirLoopHVAC | PSZ-AC_1:1 | Design Supply Air Flow Rate [m3/s] | 2.56624 |
92 | AirLoopHVAC | PSZ-AC_2:2 | Design Supply Air Flow Rate [m3/s] | 1.33499 |
93 | AirLoopHVAC | PSZ-AC_3:3 | Design Supply Air Flow Rate [m3/s] | 1.34306 |
94 | AirLoopHVAC | PSZ-AC_4:4 | Design Supply Air Flow Rate [m3/s] | 1.34605 |
95 | AirLoopHVAC | PSZ-AC_5:5 | Design Supply Air Flow Rate [m3/s] | 1.35333 |
96 | AirLoopHVAC | PSZ-AC_6:6 | Design Supply Air Flow Rate [m3/s] | 2.48916 |
97 | AirLoopHVAC | PSZ-AC_7:7 | Design Supply Air Flow Rate [m3/s] | 1.37177 |
98 | AirLoopHVAC | PSZ-AC_8:8 | Design Supply Air Flow Rate [m3/s] | 1.37067 |
99 | AirLoopHVAC | PSZ-AC_9:9 | Design Supply Air Flow Rate [m3/s] | 1.38148 |
100 | AirLoopHVAC | PSZ-AC_10:10 | Design Supply Air Flow Rate [m3/s] | 1.52576 |
101 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.56624 |
102 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.53091 |
103 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.56624 |
104 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.56624 |
105 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.56624 |
106 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 2.56624 |
107 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.56624 |
108 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.28312 |
109 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 2.56624 |
110 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 49824.16564 |
111 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 53025.40000 |
112 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 26512.70000 |
113 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 53025.40000 |
114 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.72554 |
115 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.72554 |
116 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.72554 |
117 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.72554 |
118 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 53025.40000 |
119 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 89352.93002 |
120 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
121 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
122 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.56624 |
123 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 2808.76485 |
124 | Coil:Heating:Fuel | PSZ-AC_1:1_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 89352.93002 |
125 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.33499 |
126 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.26545 |
127 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.33499 |
128 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.33499 |
129 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.33499 |
130 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.33499 |
131 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.33499 |
132 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.66750 |
133 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.33499 |
134 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 25697.26923 |
135 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 27366.06000 |
136 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 13683.03000 |
137 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 27366.06000 |
138 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.72789 |
139 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.72789 |
140 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.72789 |
141 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.72789 |
142 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 27366.06000 |
143 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 45813.83333 |
144 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
145 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
146 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.33499 |
147 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1522.03185 |
148 | Coil:Heating:Fuel | PSZ-AC_2:2_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 45813.83333 |
149 | Controller:OutdoorAir | PSZ-AC_3:3_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.34306 |
150 | Controller:OutdoorAir | PSZ-AC_3:3_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.26545 |
151 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.34306 |
152 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.34306 |
153 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.34306 |
154 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.34306 |
155 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.34306 |
156 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.67153 |
157 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.34306 |
158 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 26236.85372 |
159 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 27909.67000 |
160 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 13954.83500 |
161 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 27909.67000 |
162 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.72387 |
163 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.72387 |
164 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.72387 |
165 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.72387 |
166 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 27909.67000 |
167 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 45990.66544 |
168 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
169 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
170 | Fan:SystemModel | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.34306 |
171 | Fan:SystemModel | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1531.23285 |
172 | Coil:Heating:Fuel | PSZ-AC_3:3_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 45990.66544 |
173 | Controller:OutdoorAir | PSZ-AC_4:4_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.34605 |
174 | Controller:OutdoorAir | PSZ-AC_4:4_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.26545 |
175 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.34605 |
176 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.34605 |
177 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.34605 |
178 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.34605 |
179 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.34605 |
180 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.67303 |
181 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.34605 |
182 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 26316.40468 |
183 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 27992.76000 |
184 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 13996.38000 |
185 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 27992.76000 |
186 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.72365 |
187 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.72365 |
188 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.72365 |
189 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.72365 |
190 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 27992.76000 |
191 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 46056.33382 |
192 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
193 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
194 | Fan:SystemModel | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.34605 |
195 | Fan:SystemModel | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1534.64980 |
196 | Coil:Heating:Fuel | PSZ-AC_4:4_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 46056.33382 |
197 | Controller:OutdoorAir | PSZ-AC_5:5_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.35333 |
198 | Controller:OutdoorAir | PSZ-AC_5:5_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.26545 |
199 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.35333 |
200 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.35333 |
201 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.35333 |
202 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.35333 |
203 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.35333 |
204 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.67667 |
205 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.35333 |
206 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 26486.55280 |
207 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 28171.51000 |
208 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 14085.75500 |
209 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 28171.51000 |
210 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.72337 |
211 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.72337 |
212 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.72337 |
213 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.72337 |
214 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 28171.51000 |
215 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 46215.81742 |
216 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
217 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
218 | Fan:SystemModel | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.35333 |
219 | Fan:SystemModel | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1542.94844 |
220 | Coil:Heating:Fuel | PSZ-AC_5:5_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 46215.81742 |
221 | Controller:OutdoorAir | PSZ-AC_6:6_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.48916 |
222 | Controller:OutdoorAir | PSZ-AC_6:6_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.53091 |
223 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.48916 |
224 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.48916 |
225 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.48916 |
226 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 2.48916 |
227 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.48916 |
228 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.24458 |
229 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 2.48916 |
230 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 49478.64066 |
231 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 52565.71000 |
232 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 26282.85500 |
233 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 52565.71000 |
234 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.71919 |
235 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.71919 |
236 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.71919 |
237 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.71919 |
238 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 52565.71000 |
239 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 87663.61758 |
240 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
241 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
242 | Fan:SystemModel | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.48916 |
243 | Fan:SystemModel | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 2724.40249 |
244 | Coil:Heating:Fuel | PSZ-AC_6:6_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 87663.61758 |
245 | Controller:OutdoorAir | PSZ-AC_7:7_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.37177 |
246 | Controller:OutdoorAir | PSZ-AC_7:7_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.26545 |
247 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.37177 |
248 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.37177 |
249 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.37177 |
250 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.37177 |
251 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.37177 |
252 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.68589 |
253 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.37177 |
254 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 27182.15029 |
255 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 28884.68000 |
256 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 14442.34000 |
257 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 28884.68000 |
258 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.72003 |
259 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.72003 |
260 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.72003 |
261 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.72003 |
262 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 28884.68000 |
263 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 46619.66663 |
264 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
265 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
266 | Fan:SystemModel | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.37177 |
267 | Fan:SystemModel | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1563.96412 |
268 | Coil:Heating:Fuel | PSZ-AC_7:7_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 46619.66663 |
269 | Controller:OutdoorAir | PSZ-AC_8:8_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.37067 |
270 | Controller:OutdoorAir | PSZ-AC_8:8_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.26545 |
271 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.37067 |
272 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.37067 |
273 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.37067 |
274 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.37067 |
275 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.37067 |
276 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.68534 |
277 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.37067 |
278 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 27214.70822 |
279 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 28915.04000 |
280 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 14457.52000 |
281 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 28915.04000 |
282 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.71950 |
283 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.71950 |
284 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.71950 |
285 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.71950 |
286 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 28915.04000 |
287 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 46595.58568 |
288 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
289 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
290 | Fan:SystemModel | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.37067 |
291 | Fan:SystemModel | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1562.71110 |
292 | Coil:Heating:Fuel | PSZ-AC_8:8_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 46595.58568 |
293 | Controller:OutdoorAir | PSZ-AC_9:9_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.38148 |
294 | Controller:OutdoorAir | PSZ-AC_9:9_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.26545 |
295 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.38148 |
296 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.38148 |
297 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.38148 |
298 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.38148 |
299 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.38148 |
300 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.69074 |
301 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.38148 |
302 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 27513.32576 |
303 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 29225.78000 |
304 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 14612.89000 |
305 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 29225.78000 |
306 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.71868 |
307 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.71868 |
308 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.71868 |
309 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.71868 |
310 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 29225.78000 |
311 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 46832.45797 |
312 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
313 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
314 | Fan:SystemModel | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.38148 |
315 | Fan:SystemModel | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1575.03641 |
316 | Coil:Heating:Fuel | PSZ-AC_9:9_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 46832.45797 |
317 | Controller:OutdoorAir | PSZ-AC_10:10_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.52576 |
318 | Controller:OutdoorAir | PSZ-AC_10:10_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.26545 |
319 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.52576 |
320 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.52576 |
321 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.52576 |
322 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.52576 |
323 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.52576 |
324 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.76288 |
325 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.52576 |
326 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 30681.52432 |
327 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 32568.42000 |
328 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 16284.21000 |
329 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 32568.42000 |
330 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.71612 |
331 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.71612 |
332 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.71612 |
333 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.71612 |
334 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 32568.42000 |
335 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 49994.46880 |
336 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
337 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
338 | Fan:SystemModel | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.52576 |
339 | Fan:SystemModel | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1669.95811 |
340 | Coil:Heating:Fuel | PSZ-AC_10:10_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 49994.46880 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | 51007.6 | 9.85 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | 26316.5 | 30.42 | |||
3 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | 26853.5 | 40.24 | |||
4 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | 26934.3 | 50.49 | |||
5 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | 27107.3 | 60.55 | |||
6 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | 50607.8 | 40.74 | |||
7 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | 27805.7 | 88.42 | |||
8 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | 27836.9 | 98.74 | |||
9 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | 28139.1 | 108.11 | |||
10 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | 31368.1 | 107.50 |
Zone Name | # Surfaces | |
1 | LGSTORE1 | 15 |
2 | SMSTORE1 | 11 |
3 | SMSTORE2 | 11 |
4 | SMSTORE3 | 11 |
5 | SMSTORE4 | 11 |
6 | LGSTORE2 | 15 |
7 | SMSTORE5 | 11 |
8 | SMSTORE6 | 11 |
9 | SMSTORE7 | 11 |
10 | SMSTORE8 | 11 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | LGSTORE1_WALL_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | LGSTORE1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 71.15 | 78.94 | 71.15 | 0.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | LGSTORE1_WALL_3_DOOR_1 | Door | LGSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
4 | LGSTORE1_WALL_3_DOOR_2 | Door | LGSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
5 | LGSTORE1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
6 | LGSTORE1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 58.20 | 78.94 | 58.20 | 180.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
7 | LGSTORE1_WALL_1_WINDOW_1 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.46_SHGC_0.45 | N/A | 2.615 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
8 | LGSTORE1_WALL_1_WINDOW_2 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.46_SHGC_0.45 | N/A | 2.615 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
9 | LGSTORE1_WALL_1_WINDOW_3 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.46_SHGC_0.45 | N/A | 2.615 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
10 | LGSTORE1_WALL_1_WINDOW_4 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.46_SHGC_0.45 | N/A | 2.615 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
11 | LGSTORE1_WALL_1_DOOR_1 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.46_SHGC_0.45 | N/A | 2.615 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
12 | LGSTORE1_WALL_1_DOOR_2 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.46_SHGC_0.45 | N/A | 2.615 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
13 | LGSTORE1_FLOOR | Floor | CTF - ConductionTransferFunction | LGSTORE1_FLOOR_FFACTOR | 0.199 | 0.190 | 348.39 | 348.39 | 348.39 | 270.00 | 180.00 | 22.86 | 15.24 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | LGSTORE1_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 348.39 | 348.39 | 348.39 | 270.00 | 0.00 | 22.86 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
15 | LGSTORE1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 696.77 | 696.77 | 696.77 | 0.00 | 90.00 | 696.77 | 1.00 | 0.00 | LGSTORE1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
16 | SMSTORE1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 29.10 | 39.47 | 29.10 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
17 | SMSTORE1_WALL_1_WINDOW_1 | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.46_SHGC_0.45 | N/A | 2.615 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
18 | SMSTORE1_WALL_1_WINDOW_2 | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.46_SHGC_0.45 | N/A | 2.615 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
19 | SMSTORE1_WALL_1_DOOR | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.46_SHGC_0.45 | N/A | 2.615 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
20 | SMSTORE1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | SMSTORE1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 35.57 | 39.47 | 35.57 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | SMSTORE1_WALL_3_DOOR | Door | SMSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
23 | SMSTORE1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE2_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
24 | SMSTORE1_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE1_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | SMSTORE1_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
26 | SMSTORE1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
27 | SMSTORE2_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 29.12 | 39.47 | 29.12 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | SMSTORE2_WALL_1_WINDOW_1 | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.46_SHGC_0.45 | N/A | 2.615 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
29 | SMSTORE2_WALL_1_WINDOW_2 | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.46_SHGC_0.45 | N/A | 2.615 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
30 | SMSTORE2_WALL_1_DOOR | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.46_SHGC_0.45 | N/A | 2.615 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
31 | SMSTORE2_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
32 | SMSTORE2_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | SMSTORE2_WALL_3_DOOR | Door | SMSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
34 | SMSTORE2_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE3_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | SMSTORE2_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE2_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
36 | SMSTORE2_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
37 | SMSTORE2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
38 | SMSTORE3_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 29.12 | 39.47 | 29.12 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
39 | SMSTORE3_WALL_1_WINDOW_1 | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.46_SHGC_0.45 | N/A | 2.615 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
40 | SMSTORE3_WALL_1_WINDOW_2 | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.46_SHGC_0.45 | N/A | 2.615 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
41 | SMSTORE3_WALL_1_DOOR | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.46_SHGC_0.45 | N/A | 2.615 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
42 | SMSTORE3_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE2_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | SMSTORE3_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | SMSTORE3_WALL_3_DOOR | Door | SMSTORE3_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
45 | SMSTORE3_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE4_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | SMSTORE3_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE3_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
47 | SMSTORE3_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
48 | SMSTORE3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
49 | SMSTORE4_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 29.12 | 39.47 | 29.12 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | SMSTORE4_WALL_1_WINDOW_1 | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.46_SHGC_0.45 | N/A | 2.615 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
51 | SMSTORE4_WALL_1_WINDOW_2 | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.46_SHGC_0.45 | N/A | 2.615 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
52 | SMSTORE4_WALL_1_DOOR | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.46_SHGC_0.45 | N/A | 2.615 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | SMSTORE4_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE3_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | SMSTORE4_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | SMSTORE4_WALL_3_DOOR | Door | SMSTORE4_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | SMSTORE4_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE2_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | SMSTORE4_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE4_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | SMSTORE4_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | SMSTORE4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | LGSTORE2_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE4_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | LGSTORE2_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 71.19 | 78.94 | 71.19 | 0.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
62 | LGSTORE2_WALL_3_DOOR_1 | Door | LGSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
63 | LGSTORE2_WALL_3_DOOR_2 | Door | LGSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
64 | LGSTORE2_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE5_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | LGSTORE2_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 58.24 | 78.94 | 58.24 | 180.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
66 | LGSTORE2_WALL_1_WINDOW_1 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.46_SHGC_0.45 | N/A | 2.615 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | LGSTORE2_WALL_1_WINDOW_2 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.46_SHGC_0.45 | N/A | 2.615 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | LGSTORE2_WALL_1_WINDOW_3 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.46_SHGC_0.45 | N/A | 2.615 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | LGSTORE2_WALL_1_WINDOW_4 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.46_SHGC_0.45 | N/A | 2.615 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | LGSTORE2_WALL_1_DOOR_1 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.46_SHGC_0.45 | N/A | 2.615 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
71 | LGSTORE2_WALL_1_DOOR_2 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.46_SHGC_0.45 | N/A | 2.615 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
72 | LGSTORE2_FLOOR | Floor | CTF - ConductionTransferFunction | LGSTORE2_FLOOR_FFACTOR | 0.112 | 0.109 | 348.39 | 348.39 | 348.39 | 270.00 | 180.00 | 22.86 | 15.24 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
73 | LGSTORE2_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 348.39 | 348.39 | 348.39 | 270.00 | 0.00 | 22.86 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
74 | LGSTORE2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 696.77 | 696.77 | 696.77 | 0.00 | 90.00 | 696.77 | 1.00 | 0.00 | LGSTORE2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
75 | SMSTORE5_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 29.12 | 39.47 | 29.12 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | SMSTORE5_WALL_1_WINDOW_1 | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.46_SHGC_0.45 | N/A | 2.615 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
77 | SMSTORE5_WALL_1_WINDOW_2 | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.46_SHGC_0.45 | N/A | 2.615 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | SMSTORE5_WALL_1_DOOR | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.46_SHGC_0.45 | N/A | 2.615 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
79 | SMSTORE5_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE2_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | SMSTORE5_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | SMSTORE5_WALL_3_DOOR | Door | SMSTORE5_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
82 | SMSTORE5_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE6_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
83 | SMSTORE5_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE5_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
84 | SMSTORE5_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
85 | SMSTORE5_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE5_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
86 | SMSTORE6_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 29.12 | 39.47 | 29.12 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | SMSTORE6_WALL_1_WINDOW_1 | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.46_SHGC_0.45 | N/A | 2.615 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
88 | SMSTORE6_WALL_1_WINDOW_2 | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.46_SHGC_0.45 | N/A | 2.615 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
89 | SMSTORE6_WALL_1_DOOR | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.46_SHGC_0.45 | N/A | 2.615 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
90 | SMSTORE6_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE5_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
91 | SMSTORE6_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
92 | SMSTORE6_WALL_3_DOOR | Door | SMSTORE6_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
93 | SMSTORE6_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE7_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | SMSTORE6_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE6_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
95 | SMSTORE6_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
96 | SMSTORE6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
97 | SMSTORE7_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 29.12 | 39.47 | 29.12 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | SMSTORE7_WALL_1_WINDOW_1 | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.46_SHGC_0.45 | N/A | 2.615 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
99 | SMSTORE7_WALL_1_WINDOW_2 | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.46_SHGC_0.45 | N/A | 2.615 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
100 | SMSTORE7_WALL_1_DOOR | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.46_SHGC_0.45 | N/A | 2.615 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
101 | SMSTORE7_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE6_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
102 | SMSTORE7_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 35.59 | 39.47 | 35.59 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | SMSTORE7_WALL_3_DOOR | Door | SMSTORE7_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
104 | SMSTORE7_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE8_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | SMSTORE7_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE7_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
106 | SMSTORE7_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
107 | SMSTORE7_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE7_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
108 | SMSTORE8_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 29.12 | 39.47 | 29.12 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | SMSTORE8_WALL_1_WINDOW_1 | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.46_SHGC_0.45 | N/A | 2.615 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
110 | SMSTORE8_WALL_1_WINDOW_2 | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.46_SHGC_0.45 | N/A | 2.615 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
111 | SMSTORE8_WALL_1_DOOR | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.46_SHGC_0.45 | N/A | 2.615 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
112 | SMSTORE8_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE7_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
113 | SMSTORE8_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | SMSTORE8_WALL_3_DOOR | Door | SMSTORE8_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
115 | SMSTORE8_WALL_4 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | SMSTORE8_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE8_FLOOR_FFACTOR | 0.289 | 0.270 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | SMSTORE8_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | SMSTORE8_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE8_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1 |
2 | VETERANS DAY | Holiday | InputFile | 11/11 | 1 |
3 | CHRISTMAS | Holiday | InputFile | 12/25 | 1 |
4 | INDEPENDENCE DAY | Holiday | InputFile | 07/04 | 1 |
5 | MLK DAY | Holiday | InputFile | 01/16 | 1 |
6 | PRESIDENTS DAY | Holiday | InputFile | 02/20 | 1 |
7 | MEMORIAL DAY | Holiday | InputFile | 05/29 | 1 |
8 | LABOR DAY | Holiday | InputFile | 09/04 | 1 |
9 | COLUMBUS DAY | Holiday | InputFile | 10/09 | 1 |
10 | THANKSGIVING | Holiday | InputFile | 11/23 | 1 |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
NumberofWarmupDays | |
1 | 6 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | LGSTORE1 | RunPeriod: RUNPERIOD 1 | 0.1162143292 | 0.4068766594 | Pass | Pass | 0.1747227098 | 0.5634009634 | Pass | Pass |
2 | SMSTORE1 | RunPeriod: RUNPERIOD 1 | 7.9918304873E-002 | 0.4054453172 | Pass | Pass | 0.1167775809 | 0.6616146457 | Pass | Pass |
3 | SMSTORE2 | RunPeriod: RUNPERIOD 1 | 0.1364449398 | 0.4430026092 | Pass | Pass | 0.1485628455 | 0.3724215618 | Pass | Pass |
4 | SMSTORE3 | RunPeriod: RUNPERIOD 1 | 0.1624110250 | 0.4574653031 | Pass | Pass | 0.2257343820 | 0.5517317884 | Pass | Pass |
5 | SMSTORE4 | RunPeriod: RUNPERIOD 1 | 0.1631128629 | 0.4294756095 | Pass | Pass | 0.3075533491 | 0.7081876108 | Pass | Pass |
6 | LGSTORE2 | RunPeriod: RUNPERIOD 1 | 0.2229455046 | 0.4585488756 | Pass | Pass | 0.3011677852 | 0.5963692506 | Pass | Pass |
7 | SMSTORE5 | RunPeriod: RUNPERIOD 1 | 0.2175283239 | 0.4995100852 | Pass | Pass | 0.1787293612 | 0.4294465277 | Pass | Pass |
8 | SMSTORE6 | RunPeriod: RUNPERIOD 1 | 0.2149458002 | 0.4554212154 | Pass | Pass | 0.3409987463 | 0.6975052568 | Pass | Pass |
9 | SMSTORE7 | RunPeriod: RUNPERIOD 1 | 0.2275875206 | 0.4712386870 | Pass | Pass | 0.3225422319 | 0.6028315469 | Pass | Pass |
10 | SMSTORE8 | RunPeriod: RUNPERIOD 1 | 0.4266922456 | 0.6552482269 | Pass | Pass | 0.4369947583 | 0.9023240697 | Pass | Pass |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2020-06-03 19:20:47
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | -32.70 | 0.00 | -32.70 | Wetbulb [C] | 2.40 | 210.00 |
INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 30.10 | 12.40 | 21.10 | Wetbulb [C] | 4.70 | 200.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2020-06-03 19:20:47
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_2 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE1_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 78.94 | 71.15 | 0.00 | 90.00 | N |
LGSTORE1_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 78.94 | 58.20 | 180.00 | 90.00 | S |
LGSTORE1_ROOF | NONRES_ROOF | 0.23 | 0.221 | 0.228 | 348.39 | 348.39 | 270.00 | 0.00 | |
SMSTORE1_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 29.10 | 180.00 | 90.00 | S |
SMSTORE1_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 35.57 | 0.00 | 90.00 | N |
SMSTORE1_ROOF | NONRES_ROOF | 0.23 | 0.221 | 0.228 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE2_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 29.12 | 180.00 | 90.00 | S |
SMSTORE2_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE2_ROOF | NONRES_ROOF | 0.23 | 0.221 | 0.228 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE3_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 29.12 | 180.00 | 90.00 | S |
SMSTORE3_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE3_ROOF | NONRES_ROOF | 0.23 | 0.221 | 0.228 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE4_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 29.12 | 180.00 | 90.00 | S |
SMSTORE4_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE4_ROOF | NONRES_ROOF | 0.23 | 0.221 | 0.228 | 174.19 | 174.19 | 270.00 | 0.00 | |
LGSTORE2_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 78.94 | 71.19 | 0.00 | 90.00 | N |
LGSTORE2_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 78.94 | 58.24 | 180.00 | 90.00 | S |
LGSTORE2_ROOF | NONRES_ROOF | 0.23 | 0.221 | 0.228 | 348.39 | 348.39 | 270.00 | 0.00 | |
SMSTORE5_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 29.12 | 180.00 | 90.00 | S |
SMSTORE5_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE5_ROOF | NONRES_ROOF | 0.23 | 0.221 | 0.228 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE6_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 29.12 | 180.00 | 90.00 | S |
SMSTORE6_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE6_ROOF | NONRES_ROOF | 0.23 | 0.221 | 0.228 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE7_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 29.12 | 180.00 | 90.00 | S |
SMSTORE7_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE7_ROOF | NONRES_ROOF | 0.23 | 0.221 | 0.228 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE8_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 29.12 | 180.00 | 90.00 | S |
SMSTORE8_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE8_WALL_4 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE8_ROOF | NONRES_ROOF | 0.23 | 0.221 | 0.228 | 174.19 | 174.19 | 270.00 | 0.00 | |
LGSTORE1_FLOOR | LGSTORE1_FLOOR_FFACTOR | 1.00 | 0.199 | 348.39 | 348.39 | 270.00 | 180.00 | ||
SMSTORE1_FLOOR | SMSTORE1_FLOOR_FFACTOR | 1.00 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | ||
SMSTORE2_FLOOR | SMSTORE2_FLOOR_FFACTOR | 1.00 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | ||
SMSTORE3_FLOOR | SMSTORE3_FLOOR_FFACTOR | 1.00 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | ||
SMSTORE4_FLOOR | SMSTORE4_FLOOR_FFACTOR | 1.00 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | ||
LGSTORE2_FLOOR | LGSTORE2_FLOOR_FFACTOR | 1.00 | 0.112 | 348.39 | 348.39 | 270.00 | 180.00 | ||
SMSTORE5_FLOOR | SMSTORE5_FLOOR_FFACTOR | 1.00 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | ||
SMSTORE6_FLOOR | SMSTORE6_FLOOR_FFACTOR | 1.00 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | ||
SMSTORE7_FLOOR | SMSTORE7_FLOOR_FFACTOR | 1.00 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | ||
SMSTORE8_FLOOR | SMSTORE8_FLOOR_FFACTOR | 1.00 | 0.289 | 174.19 | 174.19 | 270.00 | 180.00 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.46_SHGC_0.45 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.615 | 0.446 | 0.451 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE1_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.46_SHGC_0.45 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.615 | 0.446 | 0.451 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE1_WALL_1_WINDOW_3 | NONRESWINDOW_U_0.46_SHGC_0.45 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.615 | 0.446 | 0.451 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE1_WALL_1_WINDOW_4 | NONRESWINDOW_U_0.46_SHGC_0.45 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.615 | 0.446 | 0.451 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE1_WALL_1_DOOR_1 | NONRESWINDOW_U_0.46_SHGC_0.45 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.615 | 0.446 | 0.451 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE1_WALL_1_DOOR_2 | NONRESWINDOW_U_0.46_SHGC_0.45 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.615 | 0.446 | 0.451 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE1_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.46_SHGC_0.45 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.615 | 0.446 | 0.451 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE1_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.46_SHGC_0.45 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.615 | 0.446 | 0.451 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE1_WALL_1_DOOR | NONRESWINDOW_U_0.46_SHGC_0.45 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.615 | 0.446 | 0.451 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE2_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.46_SHGC_0.45 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.615 | 0.446 | 0.451 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE2_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.46_SHGC_0.45 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.615 | 0.446 | 0.451 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE2_WALL_1_DOOR | NONRESWINDOW_U_0.46_SHGC_0.45 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.615 | 0.446 | 0.451 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE3_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.46_SHGC_0.45 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.615 | 0.446 | 0.451 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE3_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.46_SHGC_0.45 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.615 | 0.446 | 0.451 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE3_WALL_1_DOOR | NONRESWINDOW_U_0.46_SHGC_0.45 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.615 | 0.446 | 0.451 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE4_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.46_SHGC_0.45 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.615 | 0.446 | 0.451 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE4_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.46_SHGC_0.45 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.615 | 0.446 | 0.451 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE4_WALL_1_DOOR | NONRESWINDOW_U_0.46_SHGC_0.45 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.615 | 0.446 | 0.451 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE2_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.46_SHGC_0.45 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.615 | 0.446 | 0.451 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE2_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.46_SHGC_0.45 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.615 | 0.446 | 0.451 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE2_WALL_1_WINDOW_3 | NONRESWINDOW_U_0.46_SHGC_0.45 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.615 | 0.446 | 0.451 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE2_WALL_1_WINDOW_4 | NONRESWINDOW_U_0.46_SHGC_0.45 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.615 | 0.446 | 0.451 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE2_WALL_1_DOOR_1 | NONRESWINDOW_U_0.46_SHGC_0.45 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.615 | 0.446 | 0.451 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE2_WALL_1_DOOR_2 | NONRESWINDOW_U_0.46_SHGC_0.45 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.615 | 0.446 | 0.451 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE5_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.46_SHGC_0.45 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.615 | 0.446 | 0.451 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE5_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.46_SHGC_0.45 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.615 | 0.446 | 0.451 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE5_WALL_1_DOOR | NONRESWINDOW_U_0.46_SHGC_0.45 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.615 | 0.446 | 0.451 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE6_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.46_SHGC_0.45 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.615 | 0.446 | 0.451 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE6_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.46_SHGC_0.45 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.615 | 0.446 | 0.451 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE6_WALL_1_DOOR | NONRESWINDOW_U_0.46_SHGC_0.45 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.615 | 0.446 | 0.451 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE7_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.46_SHGC_0.45 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.615 | 0.446 | 0.451 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE7_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.46_SHGC_0.45 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.615 | 0.446 | 0.451 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE7_WALL_1_DOOR | NONRESWINDOW_U_0.46_SHGC_0.45 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.615 | 0.446 | 0.451 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE8_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.46_SHGC_0.45 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.615 | 0.446 | 0.451 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE8_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.46_SHGC_0.45 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.615 | 0.446 | 0.451 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE8_WALL_1_DOOR | NONRESWINDOW_U_0.46_SHGC_0.45 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.615 | 0.446 | 0.451 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | ||
Total or Average | 124.29 | 2.615 | 0.446 | 0.451 | ||||||||||||
North Total or Average | 0.00 | - | - | - | ||||||||||||
Non-North Total or Average | 124.29 | 2.615 | 0.446 | 0.451 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
LGSTORE1_WALL_3_DOOR_1 | SWINGING DOOR_CON | 2.492 | 3.975 | 3.90 | LGSTORE1_WALL_3 |
LGSTORE1_WALL_3_DOOR_2 | SWINGING DOOR_CON | 2.492 | 3.975 | 3.90 | LGSTORE1_WALL_3 |
SMSTORE1_WALL_3_DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 3.90 | SMSTORE1_WALL_3 |
SMSTORE2_WALL_3_DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 3.88 | SMSTORE2_WALL_3 |
SMSTORE3_WALL_3_DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 3.88 | SMSTORE3_WALL_3 |
SMSTORE4_WALL_3_DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 3.88 | SMSTORE4_WALL_3 |
LGSTORE2_WALL_3_DOOR_1 | SWINGING DOOR_CON | 2.492 | 3.975 | 3.88 | LGSTORE2_WALL_3 |
LGSTORE2_WALL_3_DOOR_2 | SWINGING DOOR_CON | 2.492 | 3.975 | 3.88 | LGSTORE2_WALL_3 |
SMSTORE5_WALL_3_DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 3.88 | SMSTORE5_WALL_3 |
SMSTORE6_WALL_3_DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 3.88 | SMSTORE6_WALL_3 |
SMSTORE7_WALL_3_DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 3.88 | SMSTORE7_WALL_3 |
SMSTORE8_WALL_3_DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 3.88 | SMSTORE8_WALL_3 |
Report: Shading Summary
For: Entire Facility
Timestamp: 2020-06-03 19:20:47
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
LGSTORE1_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_DOOR_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_DOOR_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_DOOR_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_DOOR_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2020-06-03 19:20:47
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
LGSTORE1_LIGHTS | LGSTORE1 | 18.3225 | 348.39 | 6383.30 | LightsWired | TYPE1_LIGHT_SCH | 98.40 | 168.00 | 98.38 | 0.0000 | Y | 117.88 |
LGSTORE1_LIGHTS_ALLOWANCE | LGSTORE1 | 10.4948 | 348.39 | 3656.25 | LightsWired | TYPE1_LIGHT_SCH | 98.40 | 168.00 | 98.38 | 0.0000 | Y | 67.52 |
SMSTORE1_LIGHTS | SMSTORE1 | 18.3225 | 174.19 | 3191.65 | LightsWired | TYPE1_LIGHT_SCH | 98.40 | 168.00 | 98.38 | 0.0000 | Y | 58.94 |
SMSTORE1_LIGHTS_ALLOWANCE | SMSTORE1 | 10.4948 | 174.19 | 1828.13 | LightsWired | TYPE1_LIGHT_SCH | 98.40 | 168.00 | 98.38 | 0.0000 | Y | 33.76 |
SMSTORE2_LIGHTS | SMSTORE2 | 18.3225 | 174.19 | 3191.65 | LightsWired | TYPE2_LIGHT_SCH | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 46.71 |
SMSTORE2_LIGHTS_ALLOWANCE | SMSTORE2 | 4.3056 | 174.19 | 750.00 | LightsWired | TYPE2_LIGHT_SCH | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 10.98 |
SMSTORE3_LIGHTS | SMSTORE3 | 18.3225 | 174.19 | 3191.65 | LightsWired | TYPE2_LIGHT_SCH | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 46.71 |
SMSTORE3_LIGHTS_ALLOWANCE | SMSTORE3 | 4.3056 | 174.19 | 750.00 | LightsWired | TYPE2_LIGHT_SCH | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 10.98 |
SMSTORE4_LIGHTS | SMSTORE4 | 18.3225 | 174.19 | 3191.65 | LightsWired | TYPE2_LIGHT_SCH | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 46.71 |
SMSTORE4_LIGHTS_ALLOWANCE | SMSTORE4 | 4.3056 | 174.19 | 750.00 | LightsWired | TYPE2_LIGHT_SCH | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 10.98 |
LGSTORE2_LIGHTS | LGSTORE2 | 18.3225 | 348.39 | 6383.30 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 168.00 | 71.66 | 0.0000 | Y | 85.86 |
LGSTORE2_LIGHTS_ALLOWANCE | LGSTORE2 | 0.0000 | 348.39 | 0.00 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE5_LIGHTS | SMSTORE5 | 18.3225 | 174.19 | 3191.65 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 168.00 | 71.66 | 0.0000 | Y | 42.93 |
SMSTORE5_LIGHTS_ALLOWANCE | SMSTORE5 | 0.0000 | 174.19 | 0.00 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE6_LIGHTS | SMSTORE6 | 18.3225 | 174.19 | 3191.65 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 168.00 | 71.66 | 0.0000 | Y | 42.93 |
SMSTORE6_LIGHTS_ALLOWANCE | SMSTORE6 | 0.0000 | 174.19 | 0.00 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE7_LIGHTS | SMSTORE7 | 18.3225 | 174.19 | 3191.65 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 168.00 | 71.66 | 0.0000 | Y | 42.93 |
SMSTORE7_LIGHTS_ALLOWANCE | SMSTORE7 | 0.0000 | 174.19 | 0.00 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE8_LIGHTS | SMSTORE8 | 18.3225 | 174.19 | 3191.65 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 168.00 | 71.66 | 0.0000 | Y | 42.93 |
SMSTORE8_LIGHTS_ALLOWANCE | SMSTORE8 | 0.0000 | 174.19 | 0.00 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
Interior Lighting Total | 11.0113 | 4180.64 | 46034.15 | 708.74 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS | 10625.34 | AstronomicalClock | - | 83.52 | 83.52 | 166.58 | |
Exterior Lighting Total | 10625.34 | 166.58 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2020-06-03 19:20:47
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 53025.40 | 38472.05 | 14553.35 | 0.73 | 3.30 | |||
PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 27366.06 | 19919.48 | 7446.58 | 0.73 | 3.50 | |||
PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 27909.67 | 20202.97 | 7706.70 | 0.72 | 3.50 | |||
PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 27992.76 | 20256.96 | 7735.80 | 0.72 | 3.50 | |||
PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 28171.51 | 20378.43 | 7793.08 | 0.72 | 3.50 | |||
PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 52565.71 | 37804.73 | 14760.98 | 0.72 | 3.30 | |||
PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 28884.68 | 20797.84 | 8086.84 | 0.72 | 3.50 | |||
PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 28915.04 | 20804.37 | 8110.67 | 0.72 | 3.50 | |||
PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 29225.78 | 21003.98 | 8221.80 | 0.72 | 3.50 | |||
PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 32568.42 | 23322.90 | 9245.52 | 0.72 | 3.50 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | 51007.6 | 9.85 | ||||
PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | 26316.5 | 30.42 | ||||
PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | 26853.5 | 40.24 | ||||
PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | 26934.3 | 50.49 | ||||
PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | 27107.3 | 60.55 | ||||
PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | 50607.8 | 40.74 | ||||
PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | 27805.7 | 88.42 | ||||
PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | 27836.9 | 98.74 | ||||
PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | 28139.1 | 108.11 | ||||
PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | 31368.1 | 107.50 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
PSZ-AC_1:1_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 89352.93 | 0.79 | |
PSZ-AC_2:2_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 45813.83 | 0.80 | |
PSZ-AC_3:3_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 45990.67 | 0.80 | |
PSZ-AC_4:4_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 46056.33 | 0.80 | |
PSZ-AC_5:5_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 46215.82 | 0.80 | |
PSZ-AC_6:6_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 87663.62 | 0.79 | |
PSZ-AC_7:7_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 46619.67 | 0.80 | |
PSZ-AC_8:8_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 46595.59 | 0.80 | |
PSZ-AC_9:9_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 46832.46 | 0.80 | |
PSZ-AC_10:10_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 49994.47 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.57 | 622.50 | 2.57 | 2808.76 | 1094.51 | 1.00 | 1.25 | General | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 |
PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.55 | 622.50 | 1.33 | 1522.03 | 1140.11 | 1.00 | 1.30 | General | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 |
PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.55 | 622.50 | 1.34 | 1531.23 | 1140.11 | 1.00 | 1.30 | General | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 |
PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.55 | 622.50 | 1.35 | 1534.65 | 1140.11 | 1.00 | 1.30 | General | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 |
PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.55 | 622.50 | 1.35 | 1542.95 | 1140.11 | 1.00 | 1.30 | General | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 |
PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.57 | 622.50 | 2.49 | 2724.40 | 1094.51 | 1.00 | 1.26 | General | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 |
PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.55 | 622.50 | 1.37 | 1563.96 | 1140.11 | 1.00 | 1.29 | General | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 |
PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.55 | 622.50 | 1.37 | 1562.71 | 1140.11 | 1.00 | 1.29 | General | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 |
PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.55 | 622.50 | 1.38 | 1575.04 | 1140.11 | 1.00 | 1.29 | General | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 |
PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.57 | 622.50 | 1.53 | 1669.96 | 1094.51 | 1.00 | 1.33 | General | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
GAS TANK1 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK2 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK3 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK4 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK5 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK6 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK7 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:20:47
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
LGSTORE1 | 23685.57 | 28422.69 | 81.58 | 1.814 | 2.177 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 23.89 | 23.89 | 0.00947 | 30.10 | 0.01270 | 0.531 | 0.00 |
SMSTORE1 | 12570.55 | 15084.67 | 86.60 | 0.963 | 1.155 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 23.89 | 23.89 | 0.00949 | 30.00 | 0.01270 | 0.265 | 0.00 |
SMSTORE2 | 11842.35 | 14210.82 | 81.58 | 0.907 | 1.088 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 23.89 | 23.89 | 0.00954 | 30.00 | 0.01270 | 0.265 | 0.00 |
SMSTORE3 | 11804.61 | 14165.53 | 81.32 | 0.904 | 1.085 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 23.89 | 23.89 | 0.00954 | 30.00 | 0.01270 | 0.265 | 0.00 |
SMSTORE4 | 11755.10 | 14106.12 | 80.98 | 0.900 | 1.080 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 23.89 | 23.89 | 0.00954 | 30.00 | 0.01270 | 0.265 | 0.00 |
LGSTORE2 | 21501.42 | 25801.70 | 74.06 | 1.647 | 1.976 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 23.89 | 23.89 | 0.00954 | 30.00 | 0.01270 | 0.531 | 0.00 |
SMSTORE5 | 11193.35 | 13432.02 | 77.11 | 0.857 | 1.029 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 23.89 | 23.89 | 0.00958 | 30.00 | 0.01270 | 0.265 | 0.00 |
SMSTORE6 | 11105.48 | 13326.58 | 76.50 | 0.851 | 1.021 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 23.89 | 23.89 | 0.00959 | 30.00 | 0.01270 | 0.265 | 0.00 |
SMSTORE7 | 10972.71 | 13167.25 | 75.59 | 0.840 | 1.008 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 23.89 | 23.89 | 0.00960 | 30.00 | 0.01270 | 0.265 | 0.00 |
SMSTORE8 | 10702.92 | 12843.50 | 73.73 | 0.820 | 0.984 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 23.89 | 23.89 | 0.00964 | 29.69 | 0.01270 | 0.265 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
LGSTORE1 | 47552.49 | 57062.98 | 163.79 | 2.139 | 2.566 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00655 | -32.70 | 0.00018 | 0.531 | 0.00 |
SMSTORE1 | 24738.24 | 29685.89 | 170.42 | 1.112 | 1.335 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00645 | -32.70 | 0.00018 | 0.265 | 0.00 |
SMSTORE2 | 24887.78 | 29865.33 | 171.45 | 1.119 | 1.343 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00646 | -32.70 | 0.00018 | 0.265 | 0.00 |
SMSTORE3 | 24943.31 | 29931.97 | 171.83 | 1.122 | 1.346 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00646 | -32.70 | 0.00018 | 0.265 | 0.00 |
SMSTORE4 | 25078.17 | 30093.80 | 172.76 | 1.128 | 1.353 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00647 | -32.70 | 0.00018 | 0.265 | 0.00 |
LGSTORE2 | 46123.83 | 55348.59 | 158.87 | 2.074 | 2.489 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00653 | -32.70 | 0.00018 | 0.531 | 0.00 |
SMSTORE5 | 25419.67 | 30503.60 | 175.11 | 1.143 | 1.372 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00648 | -32.70 | 0.00018 | 0.265 | 0.00 |
SMSTORE6 | 25399.30 | 30479.16 | 174.97 | 1.142 | 1.371 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00648 | -32.70 | 0.00018 | 0.265 | 0.00 |
SMSTORE7 | 25599.61 | 30719.53 | 176.35 | 1.151 | 1.381 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00649 | -32.70 | 0.00018 | 0.265 | 0.00 |
SMSTORE8 | 28273.61 | 33928.34 | 194.77 | 1.271 | 1.526 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00658 | -32.70 | 0.00018 | 0.265 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC_1:1 | 2.18 | 2.18 | 2.57 | 2.57 | 2.5662 | 2.5662 | 2.5662 | 1.0000 | 1.0000 |
PSZ-AC_2:2 | 1.16 | 1.16 | 1.33 | 1.33 | 1.3350 | 1.3350 | 1.3350 | 1.0000 | 1.0000 |
PSZ-AC_3:3 | 1.09 | 1.09 | 1.34 | 1.34 | 1.3431 | 1.3431 | 1.3431 | 1.0000 | 1.0000 |
PSZ-AC_4:4 | 1.08 | 1.08 | 1.35 | 1.35 | 1.3461 | 1.3461 | 1.3461 | 1.0000 | 1.0000 |
PSZ-AC_5:5 | 1.08 | 1.08 | 1.35 | 1.35 | 1.3533 | 1.3533 | 1.3533 | 1.0000 | 1.0000 |
PSZ-AC_6:6 | 1.98 | 1.98 | 2.49 | 2.49 | 2.4892 | 2.4892 | 2.4892 | 1.0000 | 1.0000 |
PSZ-AC_7:7 | 1.03 | 1.03 | 1.37 | 1.37 | 1.3718 | 1.3718 | 1.3718 | 1.0000 | 1.0000 |
PSZ-AC_8:8 | 1.02 | 1.02 | 1.37 | 1.37 | 1.3707 | 1.3707 | 1.3707 | 1.0000 | 1.0000 |
PSZ-AC_9:9 | 1.01 | 1.01 | 1.38 | 1.38 | 1.3815 | 1.3815 | 1.3815 | 1.0000 | 1.0000 |
PSZ-AC_10:10 | 0.98 | 0.98 | 1.53 | 1.53 | 1.5258 | 1.5258 | 1.5258 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_1:1 | 53025.400 | 0.000 | 2.566240 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 53025.40 | 40652.82 | 2.566240 | 25.40 | 17.86 | 0.01026097 | 12.80 | 11.72 | 0.00850000 | 30.10 | 0.01270324 | 21.10 | 20.6882 | 23.89 | 0.00947323 | 49.1276 | 23685.57 | 0.00 | -999.00 | -999.00 |
PSZ-AC_1:1_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_1:1 | 89352.930 | 89352.930 | -999.0 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 89352.93 | 89352.93 | 2.566241 | 9.97 | 6.95 | 0.00523391 | 40.00 | 20.66 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 20.6881 | 21.10 | 0.00655131 | 40.4332 | 47552.49 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_2:2 | 27366.060 | 0.000 | 1.334990 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 27366.06 | 21046.59 | 1.334990 | 25.31 | 17.80 | 0.01022689 | 12.80 | 11.72 | 0.00850000 | 30.10 | 0.01270324 | 21.10 | 19.8843 | 23.89 | 0.00948773 | 49.2020 | 12569.18 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_2:2 | 45813.833 | 45813.833 | -999.0 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 45813.83 | 45813.83 | 1.334987 | 10.40 | 7.12 | 0.00520492 | 40.00 | 20.66 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 19.8844 | 21.10 | 0.00645124 | 39.8244 | 24738.24 | 0.00 | -999.00 | -999.00 |
PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_3:3 | 27909.670 | 0.000 | 1.343060 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 27909.67 | 21260.79 | 1.343060 | 25.40 | 17.89 | 0.01030951 | 12.80 | 11.72 | 0.00850000 | 30.10 | 0.01270324 | 21.10 | 19.7649 | 23.89 | 0.00953663 | 49.4517 | 11839.69 | 0.00 | -999.00 | -999.00 |
PSZ-AC_3:3_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_3:3 | 45990.665 | 45990.665 | -999.0 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 45990.67 | 45990.67 | 1.343057 | 10.47 | 7.16 | 0.00521824 | 40.00 | 20.66 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 19.7649 | 21.10 | 0.00645852 | 39.8688 | 24887.78 | 0.00 | -999.00 | -999.00 |
PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_4:4 | 27992.760 | 0.000 | 1.346050 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 27992.76 | 21313.08 | 1.346050 | 25.41 | 17.90 | 0.01031404 | 12.80 | 11.72 | 0.00850000 | 30.10 | 0.01270324 | 21.10 | 19.7210 | 23.89 | 0.00953929 | 49.4653 | 11801.62 | 0.00 | -999.00 | -999.00 |
PSZ-AC_4:4_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_4:4 | 46056.334 | 46056.334 | -999.0 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 46056.33 | 46056.33 | 1.346054 | 10.49 | 7.18 | 0.00522316 | 40.00 | 20.66 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 19.7209 | 21.10 | 0.00646120 | 39.8852 | 24943.31 | 0.00 | -999.00 | -999.00 |
PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_5:5 | 28171.510 | 0.000 | 1.353330 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 28171.51 | 21434.72 | 1.353330 | 25.41 | 17.91 | 0.01031997 | 12.80 | 11.72 | 0.00850000 | 30.10 | 0.01270324 | 21.10 | 19.6149 | 23.89 | 0.00954281 | 49.4833 | 11752.08 | 0.00 | -999.00 | -999.00 |
PSZ-AC_5:5_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_5:5 | 46215.817 | 46215.817 | -999.0 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 46215.82 | 46215.82 | 1.353333 | 10.55 | 7.22 | 0.00523499 | 40.00 | 20.66 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 19.6148 | 21.10 | 0.00646764 | 39.9245 | 25078.17 | 0.00 | -999.00 | -999.00 |
PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_6:6 | 52565.710 | 0.000 | 2.489160 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 52565.71 | 39723.06 | 2.489160 | 25.56 | 18.01 | 0.01039051 | 12.80 | 11.72 | 0.00850000 | 30.10 | 0.01270324 | 21.10 | 21.3288 | 23.89 | 0.00953940 | 49.4653 | 21490.11 | 0.00 | -999.00 | -999.00 |
PSZ-AC_6:6_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_6:6 | 87663.618 | 87663.618 | -999.0 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 87663.62 | 87663.62 | 2.489163 | 9.63 | 6.72 | 0.00517694 | 40.00 | 20.66 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 21.3288 | 21.10 | 0.00653075 | 40.3073 | 46123.83 | 0.00 | -999.00 | -999.00 |
PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_7:7 | 28884.680 | 0.000 | 1.371770 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 28884.68 | 21804.55 | 1.371770 | 25.49 | 17.99 | 0.01039019 | 12.80 | 11.72 | 0.00850000 | 30.10 | 0.01270324 | 21.10 | 19.3512 | 23.89 | 0.00958448 | 49.6960 | 11188.30 | 0.00 | -999.00 | -999.00 |
PSZ-AC_7:7_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_7:7 | 46619.667 | 46619.667 | -999.0 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 46619.67 | 46619.67 | 1.371766 | 10.69 | 7.32 | 0.00526439 | 40.00 | 20.66 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 19.3512 | 21.10 | 0.00648355 | 40.0216 | 25419.67 | 0.00 | -999.00 | -999.00 |
PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_8:8 | 28915.040 | 0.000 | 1.370670 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 28915.04 | 21799.90 | 1.370670 | 25.50 | 18.00 | 0.01040158 | 12.80 | 11.72 | 0.00850000 | 30.10 | 0.01270324 | 21.10 | 19.3667 | 23.89 | 0.00959129 | 49.7308 | 11100.68 | 0.00 | -999.00 | -999.00 |
PSZ-AC_8:8_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_8:8 | 46595.586 | 46595.586 | -999.0 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 46595.59 | 46595.59 | 1.370667 | 10.68 | 7.32 | 0.00526263 | 40.00 | 20.66 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 19.3668 | 21.10 | 0.00648259 | 40.0158 | 25399.30 | 0.00 | -999.00 | -999.00 |
PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_9:9 | 29225.780 | 0.000 | 1.381480 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 29225.78 | 21991.75 | 1.381480 | 25.52 | 18.02 | 0.01041903 | 12.80 | 11.72 | 0.00850000 | 30.10 | 0.01270324 | 21.10 | 19.2152 | 23.89 | 0.00960175 | 49.7841 | 10968.41 | 0.00 | -999.00 | -999.00 |
PSZ-AC_9:9_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_9:9 | 46832.458 | 46832.458 | -999.0 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 46832.46 | 46832.46 | 1.381478 | 10.76 | 7.38 | 0.00527971 | 40.00 | 20.66 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 19.2152 | 21.10 | 0.00649191 | 40.0727 | 25599.61 | 0.00 | -999.00 | -999.00 |
PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_10:10 | 32568.420 | 0.000 | 1.525760 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 32568.42 | 24335.17 | 1.525760 | 25.57 | 18.08 | 0.01048013 | 12.80 | 11.72 | 0.00850000 | 30.10 | 0.01270324 | 21.10 | 17.3981 | 23.89 | 0.00964438 | 50.0020 | 10659.01 | 0.00 | -999.00 | -999.00 |
PSZ-AC_10:10_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_10:10 | 49994.469 | 49994.469 | -999.0 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 49994.47 | 49994.47 | 1.525765 | 11.74 | 8.05 | 0.00546956 | 40.00 | 20.66 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 17.3981 | 21.10 | 0.00658296 | 40.6294 | 28273.61 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2020-06-03 19:20:47
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | LGSTORE1 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 53025.400 | 0.000 | 2.566240 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.9146 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 53025.40 | 40652.82 | 1.0000 | 2.96124812 | 2.566240 | 25.40 | 17.86 | 0.01026097 | 51671.0 | 12.80 | 11.72 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 53025.40 | 30.10 | 0.01270324 | 21.10 | 0.53090778 | 20.6882 | 23.89 | 0.00947323 | 23.89 | 0.00947323 | 49.1276 | 23685.57 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_1:1_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | LGSTORE1 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 89352.930 | 89352.930 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.566241 | 2.96124925 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 89352.93 | 89352.93 | 1.0000 | 2.96124925 | 2.566241 | 9.97 | 6.95 | 0.00523391 | 23206.8 | 40.00 | 20.66 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 89352.93 | -32.70 | 0.00018338 | -32.70 | 0.53090778 | 20.6881 | 21.10 | 0.00655131 | 21.10 | 0.00655131 | 40.4332 | 47552.49 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | SMSTORE1 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 27366.060 | 0.000 | 1.334990 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.8513 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 27366.06 | 21046.59 | 1.0000 | 1.54047814 | 1.334990 | 25.31 | 17.80 | 0.01022689 | 51494.4 | 12.80 | 11.72 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 27366.06 | 30.10 | 0.01270324 | 21.10 | 0.26545389 | 19.8843 | 23.89 | 0.00948810 | 23.89 | 0.00948773 | 49.2020 | 12569.18 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | SMSTORE1 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 45813.833 | 45813.833 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.334987 | 1.54047465 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 45813.83 | 45813.83 | 1.0000 | 1.54047465 | 1.334987 | 10.40 | 7.12 | 0.00520492 | 23571.9 | 40.00 | 20.66 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 45813.83 | -32.70 | 0.00018338 | -32.70 | 0.26545389 | 19.8844 | 21.10 | 0.00645124 | 21.10 | 0.00645124 | 39.8244 | 24738.24 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_3:3 | SMSTORE2 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 27909.670 | 0.000 | 1.343060 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.0049 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 27909.67 | 21260.79 | 1.0000 | 1.54979032 | 1.343060 | 25.40 | 17.89 | 0.01030951 | 51795.1 | 12.80 | 11.72 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 27909.67 | 30.10 | 0.01270324 | 21.10 | 0.26545389 | 19.7649 | 23.89 | 0.00953717 | 23.89 | 0.00953663 | 49.4517 | 11839.69 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_3:3_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_3:3 | SMSTORE2 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 45990.665 | 45990.665 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.343057 | 1.54978714 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 45990.67 | 45990.67 | 1.0000 | 1.54978714 | 1.343057 | 10.47 | 7.16 | 0.00521824 | 23670.7 | 40.00 | 20.66 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 45990.67 | -32.70 | 0.00018338 | -32.70 | 0.26545389 | 19.7649 | 21.10 | 0.00645852 | 21.10 | 0.00645852 | 39.8688 | 24887.78 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_4:4 | SMSTORE3 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 27992.760 | 0.000 | 1.346050 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.0133 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 27992.76 | 21313.08 | 1.0000 | 1.55324055 | 1.346050 | 25.41 | 17.90 | 0.01031404 | 51811.6 | 12.80 | 11.72 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 27992.76 | 30.10 | 0.01270324 | 21.10 | 0.26545389 | 19.7210 | 23.89 | 0.00953987 | 23.89 | 0.00953929 | 49.4653 | 11801.62 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_4:4_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_4:4 | SMSTORE3 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 46056.334 | 46056.334 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.346054 | 1.55324549 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 46056.33 | 46056.33 | 1.0000 | 1.55324549 | 1.346054 | 10.49 | 7.18 | 0.00522316 | 23707.1 | 40.00 | 20.66 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 46056.33 | -32.70 | 0.00018338 | -32.70 | 0.26545389 | 19.7209 | 21.10 | 0.00646120 | 21.10 | 0.00646120 | 39.8852 | 24943.31 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_5:5 | SMSTORE4 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 28171.510 | 0.000 | 1.353330 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.0243 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 28171.51 | 21434.72 | 1.0000 | 1.56164113 | 1.353330 | 25.41 | 17.91 | 0.01031997 | 51833.3 | 12.80 | 11.72 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 28171.51 | 30.10 | 0.01270324 | 21.10 | 0.26545389 | 19.6149 | 23.89 | 0.00954339 | 23.89 | 0.00954281 | 49.4833 | 11752.08 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_5:5_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_5:5 | SMSTORE4 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 46215.817 | 46215.817 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.353333 | 1.56164470 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 46215.82 | 46215.82 | 1.0000 | 1.56164470 | 1.353333 | 10.55 | 7.22 | 0.00523499 | 23794.9 | 40.00 | 20.66 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 46215.82 | -32.70 | 0.00018338 | -32.70 | 0.26545389 | 19.6148 | 21.10 | 0.00646764 | 21.10 | 0.00646764 | 39.9245 | 25078.17 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_6:6 | LGSTORE2 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 52565.710 | 0.000 | 2.489160 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.1554 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 52565.71 | 39723.06 | 1.0000 | 2.87230360 | 2.489160 | 25.56 | 18.01 | 0.01039051 | 52159.8 | 12.80 | 11.72 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 52565.71 | 30.10 | 0.01270324 | 21.10 | 0.53090778 | 21.3288 | 23.89 | 0.00954031 | 23.89 | 0.00953940 | 49.4653 | 21490.11 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_6:6_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_6:6 | LGSTORE2 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 87663.618 | 87663.618 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.489163 | 2.87230696 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 87663.62 | 87663.62 | 1.0000 | 2.87230696 | 2.489163 | 9.63 | 6.72 | 0.00517694 | 22713.7 | 40.00 | 20.66 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 87663.62 | -32.70 | 0.00018338 | -32.70 | 0.53090778 | 21.3288 | 21.10 | 0.00653075 | 21.10 | 0.00653075 | 40.3073 | 46123.83 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_7:7 | SMSTORE5 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 28884.680 | 0.000 | 1.371770 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.1548 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 28884.68 | 21804.55 | 1.0000 | 1.58291950 | 1.371770 | 25.49 | 17.99 | 0.01039019 | 52091.0 | 12.80 | 11.72 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 28884.68 | 30.10 | 0.01270324 | 21.10 | 0.26545389 | 19.3512 | 23.89 | 0.00958530 | 23.89 | 0.00958448 | 49.6960 | 11188.30 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_7:7_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_7:7 | SMSTORE5 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 46619.667 | 46619.667 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.371766 | 1.58291502 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 46619.67 | 46619.67 | 1.0000 | 1.58291502 | 1.371766 | 10.69 | 7.32 | 0.00526439 | 24012.9 | 40.00 | 20.66 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 46619.67 | -32.70 | 0.00018338 | -32.70 | 0.26545389 | 19.3512 | 21.10 | 0.00648355 | 21.10 | 0.00648355 | 40.0216 | 25419.67 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_8:8 | SMSTORE6 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 28915.040 | 0.000 | 1.370670 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.1760 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 28915.04 | 21799.90 | 1.0000 | 1.58165018 | 1.370670 | 25.50 | 18.00 | 0.01040158 | 52133.0 | 12.80 | 11.72 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 28915.04 | 30.10 | 0.01270324 | 21.10 | 0.26545389 | 19.3667 | 23.89 | 0.00959211 | 23.89 | 0.00959129 | 49.7308 | 11100.68 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_8:8_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_8:8 | SMSTORE6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 46595.586 | 46595.586 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.370667 | 1.58164682 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 46595.59 | 46595.59 | 1.0000 | 1.58164682 | 1.370667 | 10.68 | 7.32 | 0.00526263 | 24000.0 | 40.00 | 20.66 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 46595.59 | -32.70 | 0.00018338 | -32.70 | 0.26545389 | 19.3668 | 21.10 | 0.00648259 | 21.10 | 0.00648259 | 40.0158 | 25399.30 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_9:9 | SMSTORE7 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 29225.780 | 0.000 | 1.381480 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.2084 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 29225.78 | 21991.75 | 1.0000 | 1.59412411 | 1.381480 | 25.52 | 18.02 | 0.01041903 | 52197.5 | 12.80 | 11.72 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 29225.78 | 30.10 | 0.01270324 | 21.10 | 0.26545389 | 19.2152 | 23.89 | 0.00960254 | 23.89 | 0.00960175 | 49.7841 | 10968.41 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_9:9_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_9:9 | SMSTORE7 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 46832.458 | 46832.458 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.381478 | 1.59412148 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 46832.46 | 46832.46 | 1.0000 | 1.59412148 | 1.381478 | 10.76 | 7.38 | 0.00527971 | 24125.8 | 40.00 | 20.66 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 46832.46 | -32.70 | 0.00018338 | -32.70 | 0.26545389 | 19.2152 | 21.10 | 0.00649191 | 21.10 | 0.00649191 | 40.0727 | 25599.61 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_10:10 | SMSTORE8 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 32568.420 | 0.000 | 1.525760 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.3220 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 32568.42 | 24335.17 | 1.0000 | 1.76061239 | 1.525760 | 25.57 | 18.08 | 0.01048013 | 52401.8 | 12.80 | 11.72 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 32568.42 | 30.10 | 0.01270324 | 21.10 | 0.26545389 | 17.3981 | 23.89 | 0.00965386 | 23.89 | 0.00964438 | 50.0020 | 10659.01 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_10:10_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_10:10 | SMSTORE8 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 49994.469 | 49994.469 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.525765 | 1.76061809 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 49994.47 | 49994.47 | 1.0000 | 1.76061809 | 1.525765 | 11.74 | 8.05 | 0.00546956 | 25596.6 | 40.00 | 20.66 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 49994.47 | -32.70 | 0.00018338 | -32.70 | 0.26545389 | 17.3981 | 21.10 | 0.00658296 | 21.10 | 0.00658296 | 40.6294 | 28273.61 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2020-06-03 19:20:47
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
LGSTORE1 | 3573.00 | 3905.67 | 2076.00 |
SMSTORE1 | 3025.67 | 3759.00 | 1508.17 |
SMSTORE2 | 2613.00 | 3027.17 | 1591.00 |
SMSTORE3 | 2667.17 | 3067.83 | 1685.33 |
SMSTORE4 | 2697.17 | 3103.50 | 1755.17 |
LGSTORE2 | 2582.83 | 2920.67 | 1789.00 |
SMSTORE5 | 2555.67 | 2933.17 | 1800.33 |
SMSTORE6 | 2561.50 | 2958.50 | 1833.00 |
SMSTORE7 | 2598.17 | 3013.17 | 1916.00 |
SMSTORE8 | 2725.00 | 3173.67 | 2187.50 |
Facility | 4416.83 | 4494.33 | 2944.67 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
LGSTORE1 | 26.00 | 0.00 | 9.33 | 0.00 |
SMSTORE1 | 12.50 | 0.00 | 5.67 | 0.00 |
SMSTORE2 | 10.50 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 12.83 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 15.17 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 25.00 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 22.67 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 23.67 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 31.50 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 184.83 | 0.00 | 0.00 | 0.00 |
Facility | 222.00 | 0.00 | 9.33 | 0.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2020-06-03 19:20:47
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
LGSTORE1 | 9.02 | 30.00 | 1805.20 | 1.073 | 0.390 | 0.000 | 0.000 |
SMSTORE1 | 4.51 | 15.00 | 902.60 | 0.823 | 0.423 | 0.000 | 0.000 |
SMSTORE2 | 3.78 | 15.00 | 902.60 | 1.073 | 0.552 | 0.000 | 0.000 |
SMSTORE3 | 3.78 | 15.00 | 902.60 | 1.073 | 0.552 | 0.000 | 0.000 |
SMSTORE4 | 3.78 | 15.00 | 902.60 | 1.073 | 0.552 | 0.000 | 0.000 |
LGSTORE2 | 13.24 | 30.00 | 1805.20 | 1.073 | 0.517 | 0.000 | 0.000 |
SMSTORE5 | 6.62 | 15.00 | 902.60 | 1.073 | 0.587 | 0.000 | 0.000 |
SMSTORE6 | 6.62 | 15.00 | 902.60 | 1.073 | 0.587 | 0.000 | 0.000 |
SMSTORE7 | 6.62 | 15.00 | 902.60 | 1.073 | 0.587 | 0.000 | 0.000 |
SMSTORE8 | 6.62 | 15.00 | 902.60 | 1.073 | 0.624 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
LGSTORE1 | 9.02 | 30.00 | 1805.20 | 1.019 | 0.000 | 0.000 | 0.000 |
SMSTORE1 | 4.51 | 15.00 | 902.60 | 0.000 | 0.000 | 0.000 | 0.000 |
SMSTORE2 | 3.78 | 15.00 | 902.60 | 1.036 | 0.000 | 0.000 | 0.000 |
SMSTORE3 | 3.78 | 15.00 | 902.60 | 1.036 | 0.000 | 0.000 | 0.000 |
SMSTORE4 | 3.78 | 15.00 | 902.60 | 1.036 | 0.000 | 0.000 | 0.000 |
LGSTORE2 | 13.24 | 30.00 | 1805.20 | 1.036 | 0.000 | 0.000 | 0.000 |
SMSTORE5 | 6.62 | 15.00 | 902.60 | 1.036 | 0.000 | 0.000 | 0.000 |
SMSTORE6 | 6.62 | 15.00 | 902.60 | 1.036 | 0.000 | 0.000 | 0.000 |
SMSTORE7 | 6.62 | 15.00 | 902.60 | 1.036 | 0.000 | 0.000 | 0.000 |
SMSTORE8 | 6.62 | 15.00 | 902.60 | 1.036 | 0.000 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2020-06-03 19:20:47
Surfaces by ClassTotal | Outdoors | |
Wall | 40 | 22 |
Floor | 10 | 10 |
Roof | 10 | 10 |
Internal Mass | 10 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 36 | 36 |
Door | 12 | 12 |
Glass Door | 12 | 12 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 10 |
Conditioned Zones | 10 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 0 |
Defaulted Fields | 0 |
Fields with Defaults | 0 |
Autosized Fields | 0 |
Autosizable Fields | 0 |
Autocalculated Fields | 0 |
Autocalculatable Fields | 0 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2020-06-03 19:20:47
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1489.53 | 3969.13 | 29-JAN-08:00 | 148388.75 | 29-JUN-15:50 |
Electricity:Building | 837.46 | 2751.13 | 01-JAN-00:10 | 51821.98 | 01-JAN-11:10 |
Electricity:Zone:LGSTORE1 | 211.76 | 576.88 | 01-JAN-00:10 | 10885.83 | 01-JAN-10:10 |
InteriorLights:Electricity | 708.74 | 2301.71 | 01-JAN-00:10 | 43732.45 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:LGSTORE1 | 185.40 | 501.98 | 01-JAN-00:10 | 9537.57 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity | 708.74 | 2301.71 | 01-JAN-00:10 | 43732.45 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE1 | 105.88 | 288.44 | 01-JAN-00:10 | 5442.91 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE1 | 92.70 | 250.99 | 01-JAN-00:10 | 4768.79 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE2 | 68.15 | 234.53 | 01-JAN-00:10 | 4418.69 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE2 | 57.68 | 197.08 | 01-JAN-00:10 | 3744.57 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE3 | 68.15 | 234.53 | 01-JAN-00:10 | 4418.69 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE3 | 57.68 | 197.08 | 01-JAN-00:10 | 3744.57 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE4 | 68.15 | 234.53 | 01-JAN-00:10 | 4418.69 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE4 | 57.68 | 197.08 | 01-JAN-00:10 | 3744.57 | 01-JAN-10:10 |
Electricity:Zone:LGSTORE2 | 105.13 | 394.07 | 01-JAN-00:10 | 7412.39 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:LGSTORE2 | 85.86 | 319.16 | 01-JAN-00:10 | 6064.13 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE5 | 52.56 | 197.03 | 01-JAN-00:10 | 3706.19 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE5 | 42.93 | 159.58 | 01-JAN-00:10 | 3032.07 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE6 | 52.56 | 197.03 | 01-JAN-00:10 | 3706.19 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE6 | 42.93 | 159.58 | 01-JAN-00:10 | 3032.07 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE7 | 52.56 | 197.03 | 01-JAN-00:10 | 3706.19 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE7 | 42.93 | 159.58 | 01-JAN-00:10 | 3032.07 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE8 | 52.56 | 197.03 | 01-JAN-00:10 | 3706.19 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE8 | 42.93 | 159.58 | 01-JAN-00:10 | 3032.07 | 01-JAN-11:10 |
InteriorEquipment:Electricity | 128.72 | 449.42 | 01-JAN-00:10 | 8089.53 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:LGSTORE1 | 26.36 | 74.90 | 01-JAN-00:10 | 1348.26 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity | 128.72 | 449.42 | 01-JAN-00:10 | 8089.53 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE1 | 13.18 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE2 | 10.47 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE3 | 10.47 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE4 | 10.47 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:LGSTORE2 | 19.26 | 74.90 | 01-JAN-00:10 | 1348.26 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE5 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE6 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE7 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE8 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
Electricity:Plant | 67.51 | 1218.00 | 01-JAN-18:10 | 12559.68 | 22-DEC-20:30 |
WaterSystems:Electricity | 67.51 | 1218.00 | 01-JAN-18:10 | 12559.68 | 22-DEC-20:30 |
Water Heater:WaterSystems:Electricity | 67.51 | 1218.00 | 01-JAN-18:10 | 12559.68 | 22-DEC-20:30 |
ElectricityPurchased:Facility | 1489.53 | 3969.13 | 29-JAN-08:00 | 148388.75 | 29-JUN-15:50 |
ElectricityPurchased:Plant | 1489.53 | 3969.13 | 29-JAN-08:00 | 148388.75 | 29-JUN-15:50 |
Cogeneration:ElectricityPurchased | 1489.53 | 3969.13 | 29-JAN-08:00 | 148388.75 | 29-JUN-15:50 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1489.53 | 3969.13 | 29-JAN-08:00 | 148388.75 | 29-JUN-15:50 |
ElectricityNet:Plant | 1489.53 | 3969.13 | 29-JAN-08:00 | 148388.75 | 29-JUN-15:50 |
Cogeneration:ElectricityNet | 1489.53 | 3969.13 | 29-JAN-08:00 | 148388.75 | 29-JUN-15:50 |
Electricity:HVAC | 417.99 | 0.00 | 03-JAN-01:10 | 92521.53 | 29-JUN-16:10 |
Fans:Electricity | 309.15 | 0.00 | 03-JAN-01:10 | 18035.70 | 02-JAN-20:20 |
General:Fans:Electricity | 309.15 | 0.00 | 03-JAN-01:10 | 18035.70 | 02-JAN-20:20 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 108.83 | 0.00 | 01-JAN-00:10 | 74485.83 | 29-JUN-16:10 |
ExteriorLights:Electricity | 166.58 | 0.00 | 01-JAN-08:20 | 10625.34 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 166.58 | 0.00 | 01-JAN-08:20 | 10625.34 | 01-JAN-00:10 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Gas:Facility | 1586.92 | 0.00 | 03-JAN-01:10 | 510403.87 | 09-JAN-08:10 |
Gas:HVAC | 1586.92 | 0.00 | 03-JAN-01:10 | 510403.87 | 09-JAN-08:10 |
Heating:Gas | 1586.92 | 0.00 | 03-JAN-01:10 | 510403.87 | 09-JAN-08:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water:Plant | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
WaterSystems:Water | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water Heater:WaterSystems:Water | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
MainsWater:Facility | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
MainsWater:Plant | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
WaterSystems:MainsWater | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water Heater:WaterSystems:MainsWater | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:Facility | 2444.04 | 0.00 | 03-JAN-01:10 | 630905.74 | 09-JAN-08:10 |
EnergyTransfer:Building | 814.02 | 0.00 | 03-JAN-01:10 | 223929.26 | 09-JAN-08:10 |
EnergyTransfer:Zone:LGSTORE1 | 151.15 | 0.00 | 01-JAN-00:10 | 40793.10 | 09-JAN-08:10 |
Heating:EnergyTransfer | 523.29 | 0.00 | 03-JAN-01:10 | 223767.59 | 09-JAN-08:10 |
Heating:EnergyTransfer:Zone:LGSTORE1 | 71.39 | 0.00 | 01-JAN-00:10 | 40793.10 | 09-JAN-08:10 |
Cooling:EnergyTransfer | 290.73 | 0.00 | 01-JAN-00:10 | 102559.21 | 29-JUN-16:10 |
Cooling:EnergyTransfer:Zone:LGSTORE1 | 79.76 | 0.00 | 01-JAN-00:10 | 23836.55 | 28-JAN-00:10 |
EnergyTransfer:Zone:SMSTORE1 | 71.75 | 0.00 | 01-JAN-00:10 | 19616.66 | 09-JAN-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE1 | 30.98 | 0.00 | 01-JAN-00:10 | 19455.00 | 09-JAN-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE1 | 40.77 | 0.00 | 01-JAN-00:10 | 9662.85 | 29-JUN-16:10 |
EnergyTransfer:Zone:SMSTORE2 | 63.14 | 0.00 | 01-JAN-00:10 | 20299.98 | 01-JAN-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE2 | 38.40 | 0.00 | 01-JAN-00:10 | 20299.98 | 01-JAN-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE2 | 24.75 | 0.00 | 01-JAN-00:10 | 8996.90 | 29-JUN-16:10 |
EnergyTransfer:Zone:SMSTORE3 | 64.18 | 0.00 | 01-JAN-00:10 | 20579.78 | 01-JAN-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE3 | 40.74 | 0.00 | 01-JAN-00:10 | 20531.16 | 01-JAN-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE3 | 23.44 | 0.00 | 01-JAN-00:10 | 8923.79 | 29-JUN-16:10 |
EnergyTransfer:Zone:SMSTORE4 | 65.18 | 0.00 | 01-JAN-00:40 | 21021.63 | 24-DEC-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE4 | 43.08 | 0.00 | 01-JAN-00:40 | 21021.63 | 24-DEC-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE4 | 22.09 | 0.00 | 01-JAN-00:10 | 8815.15 | 29-JUN-16:10 |
EnergyTransfer:Zone:LGSTORE2 | 118.74 | 0.00 | 01-JAN-00:10 | 39829.30 | 09-JAN-08:10 |
Heating:EnergyTransfer:Zone:LGSTORE2 | 82.16 | 0.00 | 01-JAN-00:10 | 39829.30 | 09-JAN-08:10 |
Cooling:EnergyTransfer:Zone:LGSTORE2 | 36.58 | 0.00 | 01-JAN-00:10 | 15696.05 | 29-JUN-16:10 |
EnergyTransfer:Zone:SMSTORE5 | 64.30 | 0.00 | 01-JAN-00:10 | 21935.05 | 25-DEC-09:10 |
Heating:EnergyTransfer:Zone:SMSTORE5 | 46.32 | 0.00 | 01-JAN-00:10 | 21622.02 | 25-DEC-09:10 |
Cooling:EnergyTransfer:Zone:SMSTORE5 | 17.97 | 0.00 | 01-JAN-00:10 | 8315.91 | 29-JUN-16:10 |
EnergyTransfer:Zone:SMSTORE6 | 64.24 | 0.00 | 01-JAN-00:40 | 21990.33 | 25-DEC-09:10 |
Heating:EnergyTransfer:Zone:SMSTORE6 | 46.86 | 0.00 | 01-JAN-00:40 | 21659.41 | 25-DEC-09:10 |
Cooling:EnergyTransfer:Zone:SMSTORE6 | 17.39 | 0.00 | 01-JAN-00:10 | 8236.60 | 29-JUN-16:10 |
EnergyTransfer:Zone:SMSTORE7 | 65.59 | 0.00 | 01-JAN-00:10 | 21633.55 | 09-JAN-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE7 | 49.81 | 0.00 | 01-JAN-00:10 | 21633.55 | 09-JAN-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE7 | 15.78 | 0.00 | 01-JAN-00:10 | 8054.61 | 29-JUN-16:10 |
EnergyTransfer:Zone:SMSTORE8 | 85.75 | 0.00 | 01-JAN-00:40 | 25244.21 | 24-DEC-09:10 |
Heating:EnergyTransfer:Zone:SMSTORE8 | 73.56 | 0.00 | 01-JAN-00:40 | 25244.21 | 24-DEC-09:10 |
Cooling:EnergyTransfer:Zone:SMSTORE8 | 12.19 | 0.00 | 01-JAN-00:10 | 7654.95 | 29-JUN-16:10 |
EnergyTransfer:HVAC | 1630.02 | 0.00 | 03-JAN-01:10 | 406976.48 | 09-JAN-08:10 |
HeatingCoils:EnergyTransfer | 1265.53 | 0.00 | 03-JAN-01:10 | 406976.48 | 09-JAN-08:10 |
CoolingCoils:EnergyTransfer | 364.49 | 0.00 | 01-JAN-00:10 | 244277.21 | 15-JUL-14:00 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2020-06-03 19:20:47
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
LGSTORE1 | 0.000 | 0.000 | 71.394 | -79.761 | 0.000 | 0.000 | 13.636 | 185.400 | 26.357 | 20.709 | 0.000 | 1.420 | 0.008 | 0.000 | -18.154 | 0.000 | -95.017 | -125.984 |
SMSTORE1 | 0.000 | 0.000 | 30.981 | -40.770 | 0.000 | 0.000 | 6.747 | 92.700 | 13.179 | 10.253 | 0.000 | 0.784 | 0.000 | 0.000 | -9.419 | 0.000 | -47.738 | -56.717 |
SMSTORE2 | 0.000 | 0.000 | 38.398 | -24.746 | 0.000 | 0.000 | 4.111 | 57.682 | 10.467 | 10.270 | 0.000 | 0.771 | 0.001 | 0.000 | -9.130 | 0.000 | -48.807 | -39.017 |
SMSTORE3 | 0.000 | 0.000 | 40.741 | -23.442 | 0.000 | 0.000 | 4.116 | 57.682 | 10.467 | 10.294 | 0.000 | 0.771 | 0.001 | 0.000 | -9.018 | 0.000 | -48.667 | -42.945 |
SMSTORE4 | 0.000 | 0.000 | 43.083 | -22.093 | 0.000 | 0.000 | 4.120 | 57.682 | 10.467 | 10.315 | 0.000 | 0.772 | 0.000 | 0.000 | -8.949 | 0.000 | -48.567 | -46.829 |
LGSTORE2 | 0.000 | 0.000 | 82.157 | -36.581 | 0.000 | 0.000 | 14.157 | 85.864 | 19.261 | 20.776 | 0.000 | 1.359 | 0.000 | 0.000 | -17.455 | 0.000 | -87.391 | -82.147 |
SMSTORE5 | 0.000 | 0.000 | 46.322 | -17.974 | 0.000 | 0.000 | 7.078 | 42.932 | 9.631 | 10.367 | 0.000 | 0.773 | 0.000 | 0.000 | -8.766 | 0.000 | -48.743 | -41.621 |
SMSTORE6 | 0.000 | 0.000 | 46.856 | -17.388 | 0.000 | 0.000 | 7.081 | 42.932 | 9.631 | 10.378 | 0.000 | 0.774 | 0.001 | 0.000 | -8.740 | 0.000 | -48.700 | -42.825 |
SMSTORE7 | 0.000 | 0.000 | 49.807 | -15.778 | 0.000 | 0.000 | 7.091 | 42.932 | 9.631 | 10.412 | 0.000 | 0.774 | 0.001 | 0.000 | -8.638 | 0.000 | -48.546 | -47.685 |
SMSTORE8 | 0.000 | 0.000 | 73.557 | -12.189 | 0.000 | 0.000 | 7.117 | 42.932 | 9.631 | 10.537 | 0.000 | 0.820 | 0.000 | 0.000 | -8.203 | 0.000 | -59.945 | -64.258 |
Total Facility | 0.000 | 0.000 | 523.295 | -290.722 | 0.000 | 0.000 | 75.255 | 708.738 | 128.721 | 124.312 | 0.000 | 9.018 | 0.011 | 0.000 | -106.471 | 0.000 | -582.121 | -590.026 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
LGSTORE1 | 09-AUG-07:03 | 0.00 | 0.00 | 0.00 | -32371.13 | 0.00 | 0.00 | 95.33 | 501.98 | 74.90 | 225.57 | 0.00 | 0.00 | 31864.52 | 0.00 | -0.00 | 0.00 | -391.17 | 0.00 |
SMSTORE1 | 24-JUL-07:03 | 0.00 | 0.00 | 0.00 | -18762.33 | 0.00 | 0.00 | 46.64 | 250.99 | 37.45 | 162.05 | 0.00 | 0.00 | 18402.10 | 0.00 | -0.00 | 0.00 | -136.90 | 0.00 |
SMSTORE2 | 10-AUG-06:03 | 0.00 | 0.00 | 0.00 | -18174.53 | 0.00 | 0.00 | 0.00 | 197.08 | 37.45 | 0.00 | 0.00 | 0.00 | 18049.56 | 0.00 | -106.08 | 0.00 | -3.50 | 0.00 |
SMSTORE3 | 10-AUG-06:03 | 0.00 | 0.00 | 0.00 | -18135.51 | 0.00 | 0.00 | 0.00 | 197.08 | 37.45 | 0.00 | 0.00 | 0.00 | 18009.84 | 0.00 | -105.38 | 0.00 | -3.49 | 0.00 |
SMSTORE4 | 24-JUL-06:03 | 0.00 | 0.00 | 0.00 | -16577.09 | 0.00 | 0.00 | 0.00 | 197.08 | 37.45 | 0.00 | 0.00 | 0.00 | 16383.05 | 0.00 | -5.77 | 0.00 | -34.73 | 0.00 |
LGSTORE2 | 29-JUN-07:02 | 0.00 | 0.00 | 0.00 | -30456.08 | 0.00 | 0.00 | 0.00 | 319.16 | 74.90 | 318.03 | 0.00 | 27.50 | 29716.48 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 29-JUN-07:02 | 0.00 | 0.00 | 0.00 | -16558.65 | 0.00 | 0.00 | 0.00 | 159.58 | 37.45 | 161.92 | 0.00 | 23.16 | 16176.54 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 29-JUN-07:02 | 0.00 | 0.00 | 0.00 | -16493.96 | 0.00 | 0.00 | 0.00 | 159.58 | 37.45 | 163.50 | 0.00 | 26.02 | 16107.40 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 29-JUN-07:02 | 0.00 | 0.00 | 0.00 | -14587.29 | 0.00 | 0.00 | 0.00 | 159.58 | 37.45 | 168.22 | 0.00 | 32.52 | 14189.51 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 23-JUL-08:62 | 0.00 | 0.00 | 0.00 | -13200.59 | 0.00 | 0.00 | 0.00 | 159.58 | 37.45 | 476.92 | 0.00 | 0.00 | 12546.53 | 0.00 | -0.00 | 0.00 | -19.89 | 0.00 |
Total Facility | 24-JUL-07:03 | 0.00 | 0.00 | 0.00 | -138011.71 | 0.00 | 0.00 | 300.52 | 7622.93 | 1460.61 | 2045.84 | 0.00 | 0.00 | 128200.00 | 0.00 | 0.00 | 0.00 | -1618.20 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
LGSTORE1 | 10-MAY-07:01 | 0.00 | 0.00 | 81970.75 | 0.00 | 0.00 | 0.00 | 131.41 | 501.98 | 74.90 | 38.98 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -1109.47 | -81608.54 |
SMSTORE1 | 08-APR-07:01 | 0.00 | 0.00 | 40842.53 | 0.00 | 0.00 | 0.00 | 0.00 | 250.99 | 37.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -249.31 | 0.00 | -827.66 | -40054.00 |
SMSTORE2 | 21-FEB-07:01 | 0.00 | 0.00 | 40939.26 | 0.00 | 0.00 | 0.00 | 0.00 | 197.08 | 37.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -357.61 | 0.00 | -159.32 | -40656.87 |
SMSTORE3 | 21-FEB-07:01 | 0.00 | 0.00 | 41169.40 | 0.00 | 0.00 | 0.00 | 0.00 | 197.08 | 37.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -344.71 | 0.00 | -153.88 | -40905.34 |
SMSTORE4 | 21-FEB-07:01 | 0.00 | 0.00 | 41410.01 | 0.00 | 0.00 | 0.00 | 0.00 | 197.08 | 37.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -338.22 | 0.00 | -150.99 | -41155.34 |
LGSTORE2 | 01-NOV-07:01 | 0.00 | 0.00 | 81066.38 | 0.00 | 0.00 | 0.00 | 0.00 | 319.16 | 74.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -356.91 | 0.00 | -713.32 | -80390.22 |
SMSTORE5 | 01-NOV-07:01 | 0.00 | 0.00 | 43109.90 | 0.00 | 0.00 | 0.00 | 0.00 | 159.58 | 37.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -178.12 | 0.00 | -403.50 | -42725.31 |
SMSTORE6 | 18-APR-07:01 | 0.00 | 0.00 | 44082.67 | 0.00 | 0.00 | 0.00 | 0.00 | 159.58 | 37.45 | 63.50 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -350.35 | -43992.86 |
SMSTORE7 | 18-APR-07:01 | 0.00 | 0.00 | 44478.29 | 0.00 | 0.00 | 0.00 | 0.00 | 159.58 | 37.45 | 75.12 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -324.46 | -44425.99 |
SMSTORE8 | 18-APR-07:01 | 0.00 | 0.00 | 47910.06 | 0.00 | 0.00 | 0.00 | 0.00 | 159.58 | 37.45 | 113.12 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -313.03 | -47907.18 |
Total Facility | 21-FEB-08:61 | 0.00 | 0.00 | 381818.06 | 0.00 | 0.00 | 0.00 | 394.13 | 7622.93 | 1460.61 | 1129.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -9718.91 | -382706.78 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2020-06-03 19:20:47
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 2.5662 | 0.0000 | 29.9961 | 1.0000 | 0.5309 | 2.5662 | 0.2439 | 1.0000 | 0.5309 | 0.2069 | ||
PSZ-AC_2:2 | 1.3350 | 0.0000 | 14.9980 | 1.0000 | 0.2655 | 1.3350 | 0.2298 | 1.0000 | 0.2655 | 0.1988 | ||
PSZ-AC_3:3 | 1.3431 | 0.0000 | 14.9980 | 1.0000 | 0.2655 | 1.3431 | 0.2439 | 1.0000 | 0.2655 | 0.1976 | ||
PSZ-AC_4:4 | 1.3461 | 0.0000 | 14.9980 | 1.0000 | 0.2655 | 1.3461 | 0.2447 | 1.0000 | 0.2655 | 0.1972 | ||
PSZ-AC_5:5 | 1.3533 | 0.0000 | 14.9980 | 1.0000 | 0.2655 | 1.3533 | 0.2457 | 1.0000 | 0.2655 | 0.1961 | ||
PSZ-AC_6:6 | 2.4892 | 0.0000 | 29.9961 | 1.0000 | 0.5309 | 2.4892 | 0.2687 | 1.0000 | 0.5309 | 0.2133 | ||
PSZ-AC_7:7 | 1.3718 | 0.0000 | 14.9980 | 1.0000 | 0.2655 | 1.3718 | 0.2580 | 1.0000 | 0.2655 | 0.1935 | ||
PSZ-AC_8:8 | 1.3707 | 0.0000 | 14.9980 | 1.0000 | 0.2655 | 1.3707 | 0.2601 | 1.0000 | 0.2655 | 0.1937 | ||
PSZ-AC_9:9 | 1.3815 | 0.0000 | 14.9980 | 1.0000 | 0.2655 | 1.3815 | 0.2632 | 1.0000 | 0.2655 | 0.1922 | ||
PSZ-AC_10:10 | 1.5258 | 0.0000 | 14.9980 | 1.0000 | 0.2655 | 1.5258 | 0.2699 | 1.0000 | 0.2655 | 0.1740 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 2.5662 | 0.0000 | 29.9961 | 1.0000 | 0.5309 | 2.5662 | 1.0000 | 1.0000 | 0.5309 | 0.2069 | ||
PSZ-AC_2:2 | 1.3350 | 0.0000 | 14.9980 | 1.0000 | 0.2655 | 1.3350 | 1.0000 | 1.0000 | 0.2655 | 0.1988 | ||
PSZ-AC_3:3 | 1.3431 | 0.0000 | 14.9980 | 1.0000 | 0.2655 | 1.3431 | 1.0000 | 1.0000 | 0.2655 | 0.1976 | ||
PSZ-AC_4:4 | 1.3461 | 0.0000 | 14.9980 | 1.0000 | 0.2655 | 1.3461 | 1.0000 | 1.0000 | 0.2655 | 0.1972 | ||
PSZ-AC_5:5 | 1.3533 | 0.0000 | 14.9980 | 1.0000 | 0.2655 | 1.3533 | 1.0000 | 1.0000 | 0.2655 | 0.1961 | ||
PSZ-AC_6:6 | 2.4892 | 0.0000 | 29.9961 | 1.0000 | 0.5309 | 2.4892 | 1.0000 | 1.0000 | 0.5309 | 0.2133 | ||
PSZ-AC_7:7 | 1.3718 | 0.0000 | 14.9980 | 1.0000 | 0.2655 | 1.3718 | 1.0000 | 1.0000 | 0.2655 | 0.1935 | ||
PSZ-AC_8:8 | 1.3707 | 0.0000 | 14.9980 | 1.0000 | 0.2655 | 1.3707 | 1.0000 | 1.0000 | 0.2655 | 0.1937 | ||
PSZ-AC_9:9 | 1.3815 | 0.0000 | 14.9980 | 1.0000 | 0.2655 | 1.3815 | 1.0000 | 1.0000 | 0.2655 | 0.1922 | ||
PSZ-AC_10:10 | 1.5258 | 0.0000 | 14.9980 | 1.0000 | 0.2655 | 1.5258 | 1.0000 | 1.0000 | 0.2655 | 0.1740 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
LGSTORE1 | PSZ-AC_1:1 | 0.000000 | 29.9961 | 0.001524 | 348.39 | 0.5309 | 1.0000 | 0.5309 | 1.000 | 0.5309 |
SMSTORE1 | PSZ-AC_2:2 | 0.000000 | 14.9980 | 0.001524 | 174.19 | 0.2655 | 1.0000 | 0.2655 | 1.000 | 0.2655 |
SMSTORE2 | PSZ-AC_3:3 | 0.000000 | 14.9980 | 0.001524 | 174.19 | 0.2655 | 1.0000 | 0.2655 | 1.000 | 0.2655 |
SMSTORE3 | PSZ-AC_4:4 | 0.000000 | 14.9980 | 0.001524 | 174.19 | 0.2655 | 1.0000 | 0.2655 | 1.000 | 0.2655 |
SMSTORE4 | PSZ-AC_5:5 | 0.000000 | 14.9980 | 0.001524 | 174.19 | 0.2655 | 1.0000 | 0.2655 | 1.000 | 0.2655 |
LGSTORE2 | PSZ-AC_6:6 | 0.000000 | 29.9961 | 0.001524 | 348.39 | 0.5309 | 1.0000 | 0.5309 | 1.000 | 0.5309 |
SMSTORE5 | PSZ-AC_7:7 | 0.000000 | 14.9980 | 0.001524 | 174.19 | 0.2655 | 1.0000 | 0.2655 | 1.000 | 0.2655 |
SMSTORE6 | PSZ-AC_8:8 | 0.000000 | 14.9980 | 0.001524 | 174.19 | 0.2655 | 1.0000 | 0.2655 | 1.000 | 0.2655 |
SMSTORE7 | PSZ-AC_9:9 | 0.000000 | 14.9980 | 0.001524 | 174.19 | 0.2655 | 1.0000 | 0.2655 | 1.000 | 0.2655 |
SMSTORE8 | PSZ-AC_10:10 | 0.000000 | 14.9980 | 0.001524 | 174.19 | 0.2655 | 1.0000 | 0.2655 | 1.000 | 0.2655 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC_1:1 | 0.000000 | 30.00 | 0.001524 | 348.3864 | 0.5309 | 0.5309 | 0.5309 |
PSZ-AC_2:2 | 0.000000 | 15.00 | 0.001524 | 174.1932 | 0.2655 | 0.2655 | 0.2655 |
PSZ-AC_3:3 | 0.000000 | 15.00 | 0.001524 | 174.1932 | 0.2655 | 0.2655 | 0.2655 |
PSZ-AC_4:4 | 0.000000 | 15.00 | 0.001524 | 174.1932 | 0.2655 | 0.2655 | 0.2655 |
PSZ-AC_5:5 | 0.000000 | 15.00 | 0.001524 | 174.1932 | 0.2655 | 0.2655 | 0.2655 |
PSZ-AC_6:6 | 0.000000 | 30.00 | 0.001524 | 348.3864 | 0.5309 | 0.5309 | 0.5309 |
PSZ-AC_7:7 | 0.000000 | 15.00 | 0.001524 | 174.1932 | 0.2655 | 0.2655 | 0.2655 |
PSZ-AC_8:8 | 0.000000 | 15.00 | 0.001524 | 174.1932 | 0.2655 | 0.2655 | 0.2655 |
PSZ-AC_9:9 | 0.000000 | 15.00 | 0.001524 | 174.1932 | 0.2655 | 0.2655 | 0.2655 |
PSZ-AC_10:10 | 0.000000 | 15.00 | 0.001524 | 174.1932 | 0.2655 | 0.2655 | 0.2655 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LGSTORE1 | PSZ-AC_1:1 | 2.5662 | 2.5662 | 2.5662 | 0.5309 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE1 | PSZ-AC_2:2 | 1.3350 | 1.3350 | 1.3350 | 0.2655 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE2 | PSZ-AC_3:3 | 1.3431 | 1.3431 | 1.3431 | 0.2655 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE3 | PSZ-AC_4:4 | 1.3461 | 1.3461 | 1.3461 | 0.2655 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE4 | PSZ-AC_5:5 | 1.3533 | 1.3533 | 1.3533 | 0.2655 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
LGSTORE2 | PSZ-AC_6:6 | 2.4892 | 2.4892 | 2.4892 | 0.5309 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE5 | PSZ-AC_7:7 | 1.3718 | 1.3718 | 1.3718 | 0.2655 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE6 | PSZ-AC_8:8 | 1.3707 | 1.3707 | 1.3707 | 0.2655 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE7 | PSZ-AC_9:9 | 1.3815 | 1.3815 | 1.3815 | 0.2655 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE8 | PSZ-AC_10:10 | 1.5258 | 1.5258 | 1.5258 | 0.2655 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 2.5662 | 2.5662 | 2.5662 | 2.5662 | 0.5309 | 1.0000 |
PSZ-AC_2:2 | 1.3350 | 1.3350 | 1.3350 | 1.3350 | 0.2655 | 1.0000 |
PSZ-AC_3:3 | 1.3431 | 1.3431 | 1.3431 | 1.3431 | 0.2655 | 1.0000 |
PSZ-AC_4:4 | 1.3461 | 1.3461 | 1.3461 | 1.3461 | 0.2655 | 1.0000 |
PSZ-AC_5:5 | 1.3533 | 1.3533 | 1.3533 | 1.3533 | 0.2655 | 1.0000 |
PSZ-AC_6:6 | 2.4892 | 2.4892 | 2.4892 | 2.4892 | 0.5309 | 1.0000 |
PSZ-AC_7:7 | 1.3718 | 1.3718 | 1.3718 | 1.3718 | 0.2655 | 1.0000 |
PSZ-AC_8:8 | 1.3707 | 1.3707 | 1.3707 | 1.3707 | 0.2655 | 1.0000 |
PSZ-AC_9:9 | 1.3815 | 1.3815 | 1.3815 | 1.3815 | 0.2655 | 1.0000 |
PSZ-AC_10:10 | 1.5258 | 1.5258 | 1.5258 | 1.5258 | 0.2655 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LGSTORE1 | PSZ-AC_1:1 | 2.5662 | 2.5662 | 2.5662 | 0.5309 | 0.2069 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE1 | PSZ-AC_2:2 | 1.3350 | 1.3350 | 1.3350 | 0.2655 | 0.1988 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE2 | PSZ-AC_3:3 | 1.3431 | 1.3431 | 1.3431 | 0.2655 | 0.1976 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE3 | PSZ-AC_4:4 | 1.3461 | 1.3461 | 1.3461 | 0.2655 | 0.1972 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE4 | PSZ-AC_5:5 | 1.3533 | 1.3533 | 1.3533 | 0.2655 | 0.1961 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
LGSTORE2 | PSZ-AC_6:6 | 2.4892 | 2.4892 | 2.4892 | 0.5309 | 0.2133 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE5 | PSZ-AC_7:7 | 1.3718 | 1.3718 | 1.3718 | 0.2655 | 0.1935 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE6 | PSZ-AC_8:8 | 1.3707 | 1.3707 | 1.3707 | 0.2655 | 0.1937 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE7 | PSZ-AC_9:9 | 1.3815 | 1.3815 | 1.3815 | 0.2655 | 0.1922 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE8 | PSZ-AC_10:10 | 1.5258 | 1.5258 | 1.5258 | 0.2655 | 0.1740 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 2.5662 | 2.5662 | 2.5662 | 2.5662 | 0.5309 | 1.0000 |
PSZ-AC_2:2 | 1.3350 | 1.3350 | 1.3350 | 1.3350 | 0.2655 | 1.0000 |
PSZ-AC_3:3 | 1.3431 | 1.3431 | 1.3431 | 1.3431 | 0.2655 | 1.0000 |
PSZ-AC_4:4 | 1.3461 | 1.3461 | 1.3461 | 1.3461 | 0.2655 | 1.0000 |
PSZ-AC_5:5 | 1.3533 | 1.3533 | 1.3533 | 1.3533 | 0.2655 | 1.0000 |
PSZ-AC_6:6 | 2.4892 | 2.4892 | 2.4892 | 2.4892 | 0.5309 | 1.0000 |
PSZ-AC_7:7 | 1.3718 | 1.3718 | 1.3718 | 1.3718 | 0.2655 | 1.0000 |
PSZ-AC_8:8 | 1.3707 | 1.3707 | 1.3707 | 1.3707 | 0.2655 | 1.0000 |
PSZ-AC_9:9 | 1.3815 | 1.3815 | 1.3815 | 1.3815 | 0.2655 | 1.0000 |
PSZ-AC_10:10 | 1.5258 | 1.5258 | 1.5258 | 1.5258 | 0.2655 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2020-06-03 19:20:47
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** International Falls Intl Ap MN USA TMY3 WMO#=727470 |
Total gross floor area [m2] | 2090.32 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
LGSTORE1 | 348.39 | 348.39 | 0.00 | 112.00 |
SMSTORE1 | 174.19 | 174.19 | 0.00 | 112.00 |
SMSTORE2 | 174.19 | 174.19 | 0.00 | 84.29 |
SMSTORE3 | 174.19 | 174.19 | 0.00 | 84.29 |
SMSTORE4 | 174.19 | 174.19 | 0.00 | 84.29 |
LGSTORE2 | 348.39 | 348.39 | 0.00 | 77.29 |
SMSTORE5 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE6 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE7 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE8 | 174.19 | 174.19 | 0.00 | 77.29 |
Totals | 2090.32 | 2090.32 | 0.00 |
Data | |
Number of hours heating loads not met | 9.33 |
Number of hours cooling loads not met | 0.00 |
Number of hours not met | 9.33 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Fuel Use [GJ] | Additional Fuel Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- Not Subdivided | 0.00 | 0.00 | 1586.92 | 510403.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- Not Subdivided | 108.83 | 74485.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 708.74 | 43732.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 166.58 | 10625.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 128.72 | 8089.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 309.15 | 18035.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 67.51 | 12559.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 128.72 | 1489.53 |
Natural Gas | 0.00 | 1586.92 |
Additional | 0.00 | 0.00 |
Total | 128.72 | 3076.45 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 339.06 |
Space Heating | 0.00 |
Space Cooling | 52.06 |
Fans (All) | 147.90 |
Service Water Heating | 32.30 |
Receptacle Equipment | 61.58 |
Miscellaneous (All) | 712.59 |
Subtotal | 712.59 |
Natural Gas [MJ/m2] | |
Space Heating | 759.18 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 759.18 |
Subtotal | 759.18 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 23.04 |
Space Heating | 51.58 |
Space Cooling | 3.54 |
Fans (All) | 10.05 |
Service Water Heating | 2.19 |
Receptacle Equipment | 4.18 |
Miscellaneous | 5.41 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
TYPE1_OCC_SCH | 1630. | 5840. |
TYPE2_OCC_SCH | 995. | 4429. |
TYPE3_OCC_SCH | 1709. | 4064. |
TYPE1_LIGHT_SCH | 5131. | 8760. |
TYPE2_LIGHT_SCH | 4096. | 8760. |
TYPE3_LIGHT_SCH | 3767. | 8760. |
TYPE1_EQUIP_SCH | 4888. | 8760. |
TYPE2_EQUIP_SCH | 3911. | 8760. |
TYPE3_EQUIP_SCH | 3600. | 8760. |
TYPE1_INFIL_SCH | 4302. | 8760. |
TYPE2_INFIL_SCH | 5164. | 8760. |
TYPE3_INFIL_SCH | 5438. | 8760. |
INFIL_DOOR_OPENING_SCH | 2505. | 4380. |
TYPE1_MINOA_MOTORIZEDDAMPER_SCH | 5579. | 5579. |
TYPE2_MINOA_MOTORIZEDDAMPER_SCH | 4429. | 4429. |
TYPE3_MINOA_MOTORIZEDDAMPER_SCH | 4064. | 4064. |
TYPE1_SWH_SCH | 2063. | 6048. |
TYPE2_SWH_SCH | 1831. | 4429. |
TYPE3_SWH_SCH | 1733. | 4064. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 7118. | 8760. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 5839. | 5839. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 7300. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
TYPE1_HTGSETP_SCH_NO_OPTIMUM | LGSTORE1 DUALSPSCHED | January | 21.11 | 365 | 21.11 | 365 |
TYPE1_CLGSETP_SCH_NO_OPTIMUM | LGSTORE1 DUALSPSCHED | July | 23.89 | 365 | 23.89 | 365 |
TYPE2_HTGSETP_SCH_NO_OPTIMUM | SMSTORE2 DUALSPSCHED | January | 21.11 | 365 | 15.56 | 365 |
TYPE2_CLGSETP_SCH_NO_OPTIMUM | SMSTORE2 DUALSPSCHED | July | 23.89 | 365 | 29.44 | 365 |
TYPE3_HTGSETP_SCH_NO_OPTIMUM | LGSTORE2 DUALSPSCHED | January | 21.11 | 365 | 15.56 | 365 |
TYPE3_CLGSETP_SCH_NO_OPTIMUM | LGSTORE2 DUALSPSCHED | July | 23.89 | 365 | 29.44 | 365 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Meter
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.392046E+12 |
February | 0.000 | 0.269757E+12 |
March | 0.000 | 0.230519E+12 |
April | 0.000 | 0.912281E+11 |
May | 0.000 | 0.991912E+10 |
June | 0.000 | 0.246683E+09 |
July | 0.000 | 3799488.196 |
August | 0.000 | 0.231575E+08 |
September | 0.000 | 0.445893E+10 |
October | 0.000 | 0.624183E+11 |
November | 0.000 | 0.165431E+12 |
December | 0.000 | 0.360872E+12 |
Annual Sum or Average | 0.158692E+13 | |
Minimum of Months | 0.000 | 3799488.196 |
Maximum of Months | 0.000 | 0.392046E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Meter
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.392046E+12 |
February | 0.000 | 0.269757E+12 |
March | 0.000 | 0.230519E+12 |
April | 0.000 | 0.912281E+11 |
May | 0.000 | 0.991912E+10 |
June | 0.000 | 0.246683E+09 |
July | 0.000 | 3799488.196 |
August | 0.000 | 0.231575E+08 |
September | 0.000 | 0.445893E+10 |
October | 0.000 | 0.624183E+11 |
November | 0.000 | 0.165431E+12 |
December | 0.000 | 0.360872E+12 |
Annual Sum or Average | 0.158692E+13 | |
Minimum of Months | 0.000 | 3799488.196 |
Maximum of Months | 0.000 | 0.392046E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2006
For: Meter
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.392046E+12 |
February | 0.000 | 0.269757E+12 |
March | 0.000 | 0.230519E+12 |
April | 0.000 | 0.912281E+11 |
May | 0.000 | 0.991912E+10 |
June | 0.000 | 0.246683E+09 |
July | 0.000 | 3799488.196 |
August | 0.000 | 0.231575E+08 |
September | 0.000 | 0.445893E+10 |
October | 0.000 | 0.624183E+11 |
November | 0.000 | 0.165431E+12 |
December | 0.000 | 0.360872E+12 |
Annual Sum or Average | 0.158692E+13 | |
Minimum of Months | 0.000 | 3799488.196 |
Maximum of Months | 0.000 | 0.392046E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Meter
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.392046E+12 |
February | 0.000 | 0.269757E+12 |
March | 0.000 | 0.230519E+12 |
April | 0.000 | 0.912281E+11 |
May | 0.000 | 0.991912E+10 |
June | 0.000 | 0.246683E+09 |
July | 0.000 | 3799488.196 |
August | 0.000 | 0.231575E+08 |
September | 0.000 | 0.445893E+10 |
October | 0.000 | 0.624183E+11 |
November | 0.000 | 0.165431E+12 |
December | 0.000 | 0.360872E+12 |
Annual Sum or Average | 0.158692E+13 | |
Minimum of Months | 0.000 | 3799488.196 |
Maximum of Months | 0.000 | 0.392046E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTRIPMALL
For: Meter
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.392046E+12 |
February | 0.000 | 0.269757E+12 |
March | 0.000 | 0.230519E+12 |
April | 0.000 | 0.912281E+11 |
May | 0.000 | 0.991912E+10 |
June | 0.000 | 0.246683E+09 |
July | 0.000 | 3799488.196 |
August | 0.000 | 0.231575E+08 |
September | 0.000 | 0.445893E+10 |
October | 0.000 | 0.624183E+11 |
November | 0.000 | 0.165431E+12 |
December | 0.000 | 0.360872E+12 |
Annual Sum or Average | 0.158692E+13 | |
Minimum of Months | 0.000 | 3799488.196 |
Maximum of Months | 0.000 | 0.392046E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.392046E+12 |
February | 0.000 | 0.269757E+12 |
March | 0.000 | 0.230519E+12 |
April | 0.000 | 0.912281E+11 |
May | 0.000 | 0.991912E+10 |
June | 0.000 | 0.246683E+09 |
July | 0.000 | 3799488.196 |
August | 0.000 | 0.231575E+08 |
September | 0.000 | 0.445893E+10 |
October | 0.000 | 0.624183E+11 |
November | 0.000 | 0.165431E+12 |
December | 0.000 | 0.360872E+12 |
Annual Sum or Average | 0.158692E+13 | |
Minimum of Months | 0.000 | 3799488.196 |
Maximum of Months | 0.000 | 0.392046E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.392046E+12 |
February | 0.000 | 0.269757E+12 |
March | 0.000 | 0.230519E+12 |
April | 0.000 | 0.912281E+11 |
May | 0.000 | 0.991912E+10 |
June | 0.000 | 0.246683E+09 |
July | 0.000 | 3799488.196 |
August | 0.000 | 0.231575E+08 |
September | 0.000 | 0.445893E+10 |
October | 0.000 | 0.624183E+11 |
November | 0.000 | 0.165431E+12 |
December | 0.000 | 0.360872E+12 |
Annual Sum or Average | 0.158692E+13 | |
Minimum of Months | 0.000 | 3799488.196 |
Maximum of Months | 0.000 | 0.392046E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 7
For: Meter
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.392046E+12 |
February | 0.000 | 0.269757E+12 |
March | 0.000 | 0.230519E+12 |
April | 0.000 | 0.912281E+11 |
May | 0.000 | 0.991912E+10 |
June | 0.000 | 0.246683E+09 |
July | 0.000 | 3799488.196 |
August | 0.000 | 0.231575E+08 |
September | 0.000 | 0.445893E+10 |
October | 0.000 | 0.624183E+11 |
November | 0.000 | 0.165431E+12 |
December | 0.000 | 0.360872E+12 |
Annual Sum or Average | 0.158692E+13 | |
Minimum of Months | 0.000 | 3799488.196 |
Maximum of Months | 0.000 | 0.392046E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_INTERNATIONALFALLS
For: Meter
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.392046E+12 |
February | 0.000 | 0.269757E+12 |
March | 0.000 | 0.230519E+12 |
April | 0.000 | 0.912281E+11 |
May | 0.000 | 0.991912E+10 |
June | 0.000 | 0.246683E+09 |
July | 0.000 | 3799488.196 |
August | 0.000 | 0.231575E+08 |
September | 0.000 | 0.445893E+10 |
October | 0.000 | 0.624183E+11 |
November | 0.000 | 0.165431E+12 |
December | 0.000 | 0.360872E+12 |
Annual Sum or Average | 0.158692E+13 | |
Minimum of Months | 0.000 | 3799488.196 |
Maximum of Months | 0.000 | 0.392046E+12 |
Report: ZoneCoolingSummaryMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.515152E+09 | 28552.53 | 06-JAN-00:01 | -32.3 | -32.4 | 0.567602E+09 | 680.12 | 15-JAN-13:09 | -6.9 | -7.6 |
February | 0.789460E+09 | 23686.73 | 25-FEB-00:01 | -24.1 | -24.4 | 0.512390E+09 | 680.12 | 26-FEB-13:09 | -4.3 | -4.6 |
March | 0.130281E+10 | 21525.11 | 23-MAR-07:04 | -17.6 | -17.9 | 0.562779E+09 | 701.33 | 26-MAR-17:30 | 9.45 | 4.65 |
April | 0.339509E+10 | 17371.39 | 05-APR-07:04 | -11.2 | -12.1 | 0.582823E+09 | 898.99 | 23-APR-12:50 | 22.43 | 15.13 |
May | 0.887455E+10 | 13610.37 | 25-MAY-16:40 | 29.17 | 19.39 | 0.706299E+09 | 899.05 | 27-MAY-12:00 | 21.90 | 13.68 |
June | 0.121721E+11 | 30392.70 | 29-JUN-07:02 | 24.72 | 20.62 | 0.715374E+09 | 899.00 | 17-JUN-12:00 | 23.30 | 13.55 |
July | 0.163072E+11 | 31029.34 | 14-JUL-07:03 | 19.40 | 17.91 | 0.752480E+09 | 898.99 | 01-JUL-12:00 | 15.60 | 14.15 |
August | 0.155404E+11 | 32387.28 | 09-AUG-07:03 | 19.68 | 18.07 | 0.741059E+09 | 899.00 | 18-AUG-12:00 | 15.60 | 12.29 |
September | 0.110319E+11 | 28245.58 | 01-SEP-07:03 | 16.38 | 15.95 | 0.697277E+09 | 899.07 | 10-SEP-17:00 | 14.40 | 11.00 |
October | 0.670555E+10 | 16926.94 | 30-OCT-07:03 | -9.0 | -9.3 | 0.613202E+09 | 899.04 | 22-OCT-16:30 | 17.80 | 11.53 |
November | 0.243267E+10 | 18175.80 | 25-NOV-00:01 | -15.0 | -15.4 | 0.553689E+09 | 742.14 | 01-NOV-17:40 | 13.70 | 11.40 |
December | 0.694564E+09 | 23351.35 | 02-DEC-00:01 | -23.5 | -23.7 | 0.570411E+09 | 680.12 | 16-DEC-13:09 | -8.3 | -8.6 |
Annual Sum or Average | 0.797614E+11 | 0.757538E+10 | ||||||||
Minimum of Months | 0.515152E+09 | 13610.37 | -32.3 | -32.4 | 0.512390E+09 | 680.12 | -8.3 | -8.6 | ||
Maximum of Months | 0.163072E+11 | 32387.28 | 29.17 | 20.62 | 0.752480E+09 | 899.07 | 23.30 | 15.13 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 58246053.22 | 9269.02 | 27-JAN-08:04 | -22.1 | -22.3 | 0.286165E+09 | 361.10 | 29-JAN-18:00 | -3.3 | -4.0 |
February | 0.186410E+09 | 11898.52 | 10-FEB-08:04 | -21.9 | -22.2 | 0.260151E+09 | 381.37 | 20-FEB-18:00 | 4.40 | 1.27 |
March | 0.440078E+09 | 11080.46 | 07-MAR-08:04 | -19.0 | -19.3 | 0.289442E+09 | 423.86 | 26-MAR-17:00 | 8.90 | 4.39 |
April | 0.157153E+10 | 9019.92 | 05-APR-07:03 | -11.2 | -12.1 | 0.306601E+09 | 449.50 | 23-APR-12:09 | 20.97 | 14.44 |
May | 0.499282E+10 | 10219.83 | 26-MAY-07:03 | 20.08 | 16.34 | 0.359928E+09 | 449.53 | 28-MAY-16:00 | 21.30 | 13.36 |
June | 0.690399E+10 | 17457.32 | 28-JUN-07:03 | 23.17 | 20.19 | 0.359304E+09 | 449.50 | 11-JUN-17:10 | 15.00 | 13.05 |
July | 0.887890E+10 | 18766.94 | 24-JUL-07:03 | 20.97 | 18.40 | 0.376522E+09 | 449.52 | 07-JUL-12:00 | 20.60 | 12.99 |
August | 0.832013E+10 | 18722.08 | 10-AUG-07:03 | 15.60 | 15.19 | 0.370863E+09 | 449.49 | 20-AUG-17:19 | 21.83 | 15.52 |
September | 0.567946E+10 | 17177.69 | 01-SEP-07:03 | 16.38 | 15.95 | 0.352372E+09 | 449.51 | 15-SEP-12:00 | 18.90 | 12.09 |
October | 0.282271E+10 | 6419.81 | 30-OCT-07:02 | -9.0 | -9.3 | 0.321327E+09 | 449.52 | 22-OCT-16:10 | 18.53 | 12.08 |
November | 0.825588E+09 | 8682.44 | 23-NOV-08:03 | -10.0 | -10.5 | 0.287638E+09 | 397.94 | 19-NOV-18:00 | 1.10 | -0.7 |
December | 90771154.88 | 9589.10 | 16-DEC-08:04 | -14.0 | -14.4 | 0.288269E+09 | 358.15 | 31-DEC-18:00 | -5.6 | -5.9 |
Annual Sum or Average | 0.407706E+11 | 0.385858E+10 | ||||||||
Minimum of Months | 58246053.22 | 6419.81 | -22.1 | -22.3 | 0.260151E+09 | 358.15 | -5.6 | -5.9 | ||
Maximum of Months | 0.887890E+10 | 18766.94 | 23.17 | 20.19 | 0.376522E+09 | 449.53 | 21.83 | 15.52 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 14198958.68 | 11096.59 | 21-JAN-07:04 | -21.8 | -22.0 | 0.169143E+09 | 340.06 | 21-JAN-13:09 | -7.0 | -8.5 |
February | 48460536.59 | 10173.74 | 04-FEB-07:04 | -15.5 | -15.8 | 0.153637E+09 | 340.06 | 04-FEB-13:09 | 5.37 | 1.21 |
March | 0.156681E+09 | 9743.06 | 11-MAR-07:04 | -15.1 | -15.4 | 0.173637E+09 | 340.06 | 11-MAR-13:09 | -1.7 | -4.2 |
April | 0.786837E+09 | 7329.44 | 07-APR-06:03 | -5.7 | -7.0 | 0.174939E+09 | 415.82 | 22-APR-12:00 | 16.10 | 6.64 |
May | 0.294744E+10 | 9022.03 | 26-MAY-06:03 | 19.50 | 15.69 | 0.210488E+09 | 449.52 | 27-MAY-12:30 | 21.80 | 13.52 |
June | 0.431861E+10 | 16026.49 | 29-JUN-06:03 | 23.17 | 19.91 | 0.219398E+09 | 449.50 | 10-JUN-12:20 | 18.50 | 17.61 |
July | 0.570040E+10 | 16535.66 | 24-JUL-06:03 | 18.68 | 16.81 | 0.223491E+09 | 449.49 | 01-JUL-12:00 | 15.60 | 14.15 |
August | 0.534178E+10 | 18185.33 | 10-AUG-06:03 | 15.10 | 14.70 | 0.229126E+09 | 449.49 | 05-AUG-12:09 | 20.60 | 14.58 |
September | 0.340041E+10 | 16514.94 | 01-SEP-06:03 | 16.10 | 15.79 | 0.204830E+09 | 449.50 | 09-SEP-12:00 | 18.30 | 10.30 |
October | 0.162965E+10 | 6440.32 | 06-OCT-06:04 | -3.6 | -4.0 | 0.179568E+09 | 449.50 | 21-OCT-12:20 | 18.33 | 11.06 |
November | 0.381817E+09 | 10754.70 | 29-NOV-07:04 | -18.4 | -18.6 | 0.164596E+09 | 356.53 | 01-NOV-17:40 | 13.70 | 11.40 |
December | 20300628.17 | 11457.03 | 01-DEC-07:04 | -20.3 | -20.5 | 0.168939E+09 | 340.06 | 16-DEC-13:09 | -8.3 | -8.6 |
Annual Sum or Average | 0.247466E+11 | 0.227179E+10 | ||||||||
Minimum of Months | 14198958.68 | 6440.32 | -21.8 | -22.0 | 0.153637E+09 | 340.06 | -8.3 | -8.6 | ||
Maximum of Months | 0.570040E+10 | 18185.33 | 23.17 | 19.91 | 0.229126E+09 | 449.52 | 21.80 | 17.61 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 14381503.56 | 11952.56 | 21-JAN-07:04 | -21.8 | -22.0 | 0.169143E+09 | 340.06 | 21-JAN-13:09 | -7.0 | -8.5 |
February | 33986471.77 | 10515.68 | 27-FEB-07:05 | -19.2 | -19.5 | 0.153637E+09 | 340.06 | 04-FEB-13:09 | 5.37 | 1.21 |
March | 0.116268E+09 | 9986.89 | 11-MAR-07:04 | -15.1 | -15.4 | 0.173632E+09 | 340.06 | 11-MAR-13:09 | -1.7 | -4.2 |
April | 0.656948E+09 | 7927.71 | 04-APR-06:04 | -9.2 | -10.6 | 0.174135E+09 | 408.97 | 22-APR-12:00 | 16.10 | 6.64 |
May | 0.272680E+10 | 8380.61 | 26-MAY-06:03 | 19.50 | 15.69 | 0.209247E+09 | 449.49 | 27-MAY-12:00 | 21.90 | 13.68 |
June | 0.414511E+10 | 16026.85 | 29-JUN-06:03 | 23.17 | 19.91 | 0.218927E+09 | 449.50 | 17-JUN-12:00 | 23.30 | 13.55 |
July | 0.559335E+10 | 16590.30 | 24-JUL-06:03 | 18.68 | 16.81 | 0.223395E+09 | 449.49 | 01-JUL-12:00 | 15.60 | 14.15 |
August | 0.521536E+10 | 18146.32 | 10-AUG-06:03 | 15.10 | 14.70 | 0.228988E+09 | 449.49 | 05-AUG-12:09 | 20.60 | 14.58 |
September | 0.319183E+10 | 16293.43 | 01-SEP-06:03 | 16.10 | 15.79 | 0.203810E+09 | 449.50 | 09-SEP-12:00 | 18.30 | 10.30 |
October | 0.142849E+10 | 8205.03 | 30-OCT-06:04 | -9.4 | -9.8 | 0.178842E+09 | 449.50 | 21-OCT-12:30 | 18.60 | 11.13 |
November | 0.304063E+09 | 11005.94 | 29-NOV-07:04 | -18.4 | -18.6 | 0.164439E+09 | 349.56 | 01-NOV-17:40 | 13.70 | 11.40 |
December | 16238844.82 | 11548.01 | 08-DEC-07:04 | -20.4 | -20.7 | 0.168939E+09 | 340.06 | 16-DEC-13:09 | -8.3 | -8.6 |
Annual Sum or Average | 0.234428E+11 | 0.226713E+10 | ||||||||
Minimum of Months | 14381503.56 | 7927.71 | -21.8 | -22.0 | 0.153637E+09 | 340.06 | -8.3 | -8.6 | ||
Maximum of Months | 0.559335E+10 | 18146.32 | 23.17 | 19.91 | 0.228988E+09 | 449.50 | 23.30 | 14.58 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 12312865.16 | 11699.74 | 23-JAN-07:05 | -22.2 | -22.4 | 0.169143E+09 | 340.06 | 21-JAN-13:09 | -7.0 | -8.5 |
February | 25964698.89 | 11007.19 | 27-FEB-07:05 | -19.2 | -19.5 | 0.153637E+09 | 340.06 | 04-FEB-13:09 | 5.37 | 1.21 |
March | 92095194.22 | 11367.27 | 18-MAR-06:04 | -20.2 | -20.4 | 0.173632E+09 | 340.06 | 11-MAR-13:09 | -1.7 | -4.2 |
April | 0.551306E+09 | 8848.18 | 05-APR-06:04 | -13.5 | -14.0 | 0.173436E+09 | 403.52 | 22-APR-12:00 | 16.10 | 6.64 |
May | 0.251310E+10 | 6869.84 | 26-MAY-06:03 | 19.50 | 15.69 | 0.208147E+09 | 449.49 | 27-MAY-12:00 | 21.90 | 13.68 |
June | 0.393362E+10 | 15968.38 | 29-JUN-06:03 | 23.17 | 19.91 | 0.218432E+09 | 449.50 | 17-JUN-12:00 | 23.30 | 13.55 |
July | 0.541037E+10 | 16588.24 | 24-JUL-06:03 | 18.68 | 16.81 | 0.223254E+09 | 449.49 | 01-JUL-12:00 | 15.60 | 14.15 |
August | 0.502537E+10 | 16572.34 | 09-AUG-06:03 | 18.98 | 17.80 | 0.228797E+09 | 449.49 | 05-AUG-12:09 | 20.60 | 14.58 |
September | 0.299542E+10 | 14711.78 | 01-SEP-06:03 | 16.10 | 15.79 | 0.202943E+09 | 449.50 | 09-SEP-12:00 | 18.30 | 10.30 |
October | 0.128152E+10 | 8387.41 | 30-OCT-06:04 | -9.4 | -9.8 | 0.178359E+09 | 449.50 | 21-OCT-12:39 | 18.87 | 11.19 |
November | 0.239601E+09 | 8351.23 | 24-NOV-07:04 | -10.0 | -10.7 | 0.164321E+09 | 344.04 | 01-NOV-17:40 | 13.70 | 11.40 |
December | 13181032.09 | 10236.14 | 29-DEC-07:04 | -16.5 | -16.8 | 0.168939E+09 | 340.06 | 16-DEC-13:09 | -8.3 | -8.6 |
Annual Sum or Average | 0.220939E+11 | 0.226304E+10 | ||||||||
Minimum of Months | 12312865.16 | 6869.84 | -22.2 | -22.4 | 0.153637E+09 | 340.06 | -8.3 | -8.6 | ||
Maximum of Months | 0.541037E+10 | 16588.24 | 23.17 | 19.91 | 0.228797E+09 | 449.50 | 23.30 | 14.58 |
Report: ZoneCoolingSummaryMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 20762376.00 | 20298.63 | 24-JAN-08:05 | -15.9 | -16.2 | 0.578270E+09 | 906.81 | 14-JAN-15:00 | -12.8 | -13.3 |
February | 25090325.77 | 19552.45 | 04-FEB-08:05 | -14.6 | -14.9 | 0.526487E+09 | 906.82 | 04-FEB-15:09 | 7.80 | 2.57 |
March | 92014649.20 | 20009.92 | 14-MAR-07:05 | -15.5 | -16.3 | 0.596389E+09 | 906.82 | 25-MAR-14:09 | 0.60 | -1.0 |
April | 0.773442E+09 | 17909.82 | 05-APR-07:04 | -11.2 | -12.1 | 0.591249E+09 | 1154.81 | 22-APR-14:00 | 18.30 | 7.79 |
May | 0.408466E+10 | 12393.53 | 01-MAY-07:03 | -0.9 | -3.9 | 0.705479E+09 | 1198.64 | 27-MAY-14:00 | 22.20 | 14.07 |
June | 0.661577E+10 | 30467.00 | 29-JUN-07:02 | 24.72 | 20.62 | 0.745352E+09 | 1198.69 | 17-JUN-14:09 | 23.90 | 13.77 |
July | 0.925972E+10 | 30308.73 | 24-JUL-07:03 | 20.97 | 18.40 | 0.763321E+09 | 1198.61 | 01-JUL-14:09 | 21.78 | 16.77 |
August | 0.860012E+10 | 28666.22 | 09-AUG-07:03 | 19.68 | 18.07 | 0.782701E+09 | 1198.63 | 19-AUG-14:09 | 21.78 | 14.60 |
September | 0.494907E+10 | 22673.48 | 01-SEP-07:03 | 16.38 | 15.95 | 0.690637E+09 | 1198.67 | 02-SEP-14:09 | 14.97 | 13.41 |
October | 0.189821E+10 | 12637.74 | 25-OCT-07:03 | -3.2 | -3.4 | 0.606618E+09 | 1198.65 | 21-OCT-14:09 | 20.00 | 11.40 |
November | 0.236454E+09 | 17325.07 | 23-NOV-09:04 | -10.0 | -10.5 | 0.559301E+09 | 943.99 | 01-NOV-16:10 | 17.62 | 13.18 |
December | 25988224.57 | 19200.93 | 08-DEC-08:05 | -19.9 | -20.2 | 0.579249E+09 | 906.82 | 16-DEC-15:09 | -5.6 | -6.2 |
Annual Sum or Average | 0.365813E+11 | 0.772505E+10 | ||||||||
Minimum of Months | 20762376.00 | 12393.53 | -19.9 | -20.2 | 0.526487E+09 | 906.81 | -12.8 | -13.3 | ||
Maximum of Months | 0.925972E+10 | 30467.00 | 24.72 | 20.62 | 0.782701E+09 | 1198.69 | 23.90 | 16.77 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 8474172.92 | 9228.75 | 24-JAN-08:05 | -15.9 | -16.2 | 0.289135E+09 | 453.41 | 14-JAN-15:00 | -12.8 | -13.3 |
February | 8692347.83 | 10041.66 | 11-FEB-08:04 | -15.5 | -15.9 | 0.263243E+09 | 453.41 | 04-FEB-15:09 | 7.80 | 2.57 |
March | 42925321.62 | 9826.38 | 14-MAR-07:05 | -15.5 | -16.3 | 0.298194E+09 | 453.41 | 25-MAR-14:09 | 0.60 | -1.0 |
April | 0.318752E+09 | 8836.38 | 05-APR-07:04 | -11.2 | -12.1 | 0.295653E+09 | 575.25 | 22-APR-14:00 | 18.30 | 7.79 |
May | 0.193555E+10 | 6192.98 | 01-MAY-07:03 | -0.9 | -3.9 | 0.352730E+09 | 599.32 | 27-MAY-14:00 | 22.20 | 14.07 |
June | 0.329339E+10 | 16565.14 | 29-JUN-07:02 | 24.72 | 20.62 | 0.372753E+09 | 599.34 | 17-JUN-14:09 | 23.90 | 13.77 |
July | 0.471521E+10 | 16364.56 | 24-JUL-07:03 | 20.97 | 18.40 | 0.381688E+09 | 599.30 | 01-JUL-14:09 | 21.78 | 16.77 |
August | 0.433267E+10 | 13364.55 | 09-AUG-07:03 | 19.68 | 18.07 | 0.391464E+09 | 599.32 | 19-AUG-14:09 | 21.78 | 14.60 |
September | 0.234011E+10 | 10463.26 | 01-SEP-07:03 | 16.38 | 15.95 | 0.345617E+09 | 599.33 | 02-SEP-14:09 | 14.97 | 13.41 |
October | 0.872250E+09 | 6146.21 | 25-OCT-07:03 | -3.2 | -3.4 | 0.303443E+09 | 599.32 | 21-OCT-14:09 | 20.00 | 11.40 |
November | 98355702.89 | 9101.44 | 25-NOV-08:05 | -18.2 | -18.6 | 0.279692E+09 | 473.17 | 01-NOV-16:10 | 17.62 | 13.18 |
December | 7591072.49 | 7030.75 | 03-DEC-09:05 | -12.1 | -12.2 | 0.289624E+09 | 453.41 | 16-DEC-15:09 | -5.6 | -6.2 |
Annual Sum or Average | 0.179740E+11 | 0.386324E+10 | ||||||||
Minimum of Months | 7591072.49 | 6146.21 | -18.2 | -18.6 | 0.263243E+09 | 453.41 | -12.8 | -13.3 | ||
Maximum of Months | 0.471521E+10 | 16565.14 | 24.72 | 20.62 | 0.391464E+09 | 599.34 | 23.90 | 16.77 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 6748950.72 | 8742.34 | 31-JAN-08:05 | -15.6 | -16.0 | 0.289135E+09 | 453.41 | 14-JAN-15:00 | -12.8 | -13.3 |
February | 8207611.45 | 9048.72 | 19-FEB-09:05 | -21.4 | -21.7 | 0.263243E+09 | 453.41 | 04-FEB-15:09 | 7.80 | 2.57 |
March | 36565879.04 | 9838.93 | 14-MAR-07:05 | -15.5 | -16.3 | 0.298194E+09 | 453.41 | 25-MAR-14:09 | 0.60 | -1.0 |
April | 0.290250E+09 | 8910.60 | 05-APR-07:04 | -11.2 | -12.1 | 0.295123E+09 | 571.34 | 22-APR-14:00 | 18.30 | 7.79 |
May | 0.183278E+10 | 6157.26 | 01-MAY-07:03 | -0.9 | -3.9 | 0.351707E+09 | 599.32 | 27-MAY-14:00 | 22.20 | 14.07 |
June | 0.317583E+10 | 16500.48 | 29-JUN-07:02 | 24.72 | 20.62 | 0.372139E+09 | 599.34 | 17-JUN-14:09 | 23.90 | 13.77 |
July | 0.461051E+10 | 16306.85 | 24-JUL-07:03 | 20.97 | 18.40 | 0.381559E+09 | 599.30 | 01-JUL-14:09 | 21.78 | 16.77 |
August | 0.423538E+10 | 12658.48 | 09-AUG-07:03 | 19.68 | 18.07 | 0.391259E+09 | 599.32 | 19-AUG-14:09 | 21.78 | 14.60 |
September | 0.226201E+10 | 9803.08 | 01-SEP-07:03 | 16.38 | 15.95 | 0.344927E+09 | 599.33 | 02-SEP-14:09 | 14.97 | 13.41 |
October | 0.832655E+09 | 6194.97 | 25-OCT-07:03 | -3.2 | -3.4 | 0.303198E+09 | 599.32 | 21-OCT-14:09 | 20.00 | 11.40 |
November | 91116062.47 | 9632.14 | 25-NOV-08:05 | -18.2 | -18.6 | 0.279637E+09 | 470.92 | 01-NOV-16:10 | 17.62 | 13.18 |
December | 6057094.99 | 7461.59 | 07-DEC-08:04 | -7.8 | -7.9 | 0.289624E+09 | 453.41 | 16-DEC-15:09 | -5.6 | -6.2 |
Annual Sum or Average | 0.173881E+11 | 0.385974E+10 | ||||||||
Minimum of Months | 6057094.99 | 6157.26 | -21.4 | -21.7 | 0.263243E+09 | 453.41 | -12.8 | -13.3 | ||
Maximum of Months | 0.461051E+10 | 16500.48 | 24.72 | 20.62 | 0.391259E+09 | 599.34 | 23.90 | 16.77 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 6111701.68 | 9754.70 | 31-JAN-08:05 | -15.6 | -16.0 | 0.289135E+09 | 453.41 | 14-JAN-15:00 | -12.8 | -13.3 |
February | 7947231.98 | 8979.41 | 15-FEB-08:05 | -22.6 | -23.0 | 0.263243E+09 | 453.41 | 04-FEB-15:09 | 7.80 | 2.57 |
March | 23846845.40 | 10294.07 | 16-MAR-07:15 | -20.5 | -20.9 | 0.298194E+09 | 453.41 | 25-MAR-14:09 | 0.60 | -1.0 |
April | 0.208625E+09 | 6816.81 | 06-APR-07:04 | -4.6 | -5.6 | 0.293553E+09 | 559.81 | 22-APR-14:00 | 18.30 | 7.79 |
May | 0.152885E+10 | 5367.88 | 25-MAY-16:10 | 29.12 | 19.56 | 0.348758E+09 | 599.32 | 27-MAY-14:00 | 22.20 | 14.07 |
June | 0.284568E+10 | 14592.56 | 29-JUN-07:02 | 24.72 | 20.62 | 0.370219E+09 | 599.34 | 17-JUN-14:09 | 23.90 | 13.77 |
July | 0.434115E+10 | 14546.53 | 24-JUL-07:03 | 20.97 | 18.40 | 0.381142E+09 | 599.31 | 01-JUL-14:09 | 21.78 | 16.77 |
August | 0.399117E+10 | 10519.38 | 09-AUG-07:03 | 19.68 | 18.07 | 0.390647E+09 | 599.32 | 19-AUG-14:09 | 21.78 | 14.60 |
September | 0.204984E+10 | 7682.51 | 01-SEP-07:03 | 16.38 | 15.95 | 0.343163E+09 | 599.35 | 02-SEP-14:09 | 14.97 | 13.41 |
October | 0.706776E+09 | 7817.28 | 30-OCT-07:04 | -9.0 | -9.3 | 0.302556E+09 | 599.32 | 21-OCT-14:09 | 20.00 | 11.40 |
November | 62014290.79 | 7774.06 | 13-NOV-08:04 | -7.5 | -8.4 | 0.279484E+09 | 464.23 | 01-NOV-16:10 | 17.62 | 13.18 |
December | 6221694.77 | 8992.95 | 01-DEC-08:05 | -21.0 | -21.2 | 0.289624E+09 | 453.41 | 16-DEC-15:09 | -5.6 | -6.2 |
Annual Sum or Average | 0.157782E+11 | 0.384972E+10 | ||||||||
Minimum of Months | 6111701.68 | 5367.88 | -22.6 | -23.0 | 0.263243E+09 | 453.41 | -12.8 | -13.3 | ||
Maximum of Months | 0.434115E+10 | 14592.56 | 29.12 | 20.62 | 0.390647E+09 | 599.35 | 23.90 | 16.77 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 3136434.74 | 6896.57 | 30-JAN-08:04 | -4.7 | -5.0 | 0.289135E+09 | 453.41 | 14-JAN-15:00 | -12.8 | -13.3 |
February | 3344608.75 | 7283.80 | 08-FEB-08:04 | -5.5 | -6.4 | 0.263243E+09 | 453.41 | 04-FEB-15:09 | 7.80 | 2.57 |
March | 6383448.87 | 8950.63 | 18-MAR-07:05 | -20.6 | -20.8 | 0.298194E+09 | 453.41 | 25-MAR-14:09 | 0.60 | -1.0 |
April | 43164162.79 | 7017.36 | 06-APR-07:04 | -4.6 | -5.6 | 0.289585E+09 | 526.78 | 22-APR-14:00 | 18.30 | 7.79 |
May | 0.825228E+09 | 6050.42 | 01-MAY-07:04 | -0.9 | -3.9 | 0.341512E+09 | 599.32 | 27-MAY-14:00 | 22.20 | 14.07 |
June | 0.210119E+10 | 12548.70 | 30-JUN-07:02 | 26.02 | 21.72 | 0.364788E+09 | 599.35 | 17-JUN-14:09 | 23.90 | 13.77 |
July | 0.374396E+10 | 13209.57 | 23-JUL-08:62 | 23.58 | 21.21 | 0.379662E+09 | 599.31 | 01-JUL-14:09 | 21.78 | 16.77 |
August | 0.345892E+10 | 7175.69 | 08-AUG-15:00 | 30.60 | 23.35 | 0.388570E+09 | 599.32 | 19-AUG-14:09 | 21.78 | 14.60 |
September | 0.156947E+10 | 6298.56 | 01-SEP-14:20 | 25.77 | 18.00 | 0.339218E+09 | 599.34 | 02-SEP-14:09 | 14.97 | 13.41 |
October | 0.411017E+09 | 6930.56 | 25-OCT-07:03 | -3.2 | -3.4 | 0.301455E+09 | 599.33 | 21-OCT-14:09 | 20.00 | 11.40 |
November | 19916922.97 | 7866.32 | 25-NOV-08:05 | -18.2 | -18.6 | 0.279172E+09 | 453.41 | 18-NOV-15:09 | 4.90 | 1.39 |
December | 3111948.67 | 6969.24 | 30-DEC-08:04 | -4.6 | -5.2 | 0.289625E+09 | 453.41 | 16-DEC-15:09 | -5.6 | -6.2 |
Annual Sum or Average | 0.121888E+11 | 0.382416E+10 | ||||||||
Minimum of Months | 3111948.67 | 6050.42 | -20.6 | -20.8 | 0.263243E+09 | 453.41 | -12.8 | -13.3 | ||
Maximum of Months | 0.374396E+10 | 13209.57 | 30.60 | 23.35 | 0.388570E+09 | 599.35 | 23.90 | 16.77 |
Report: ZoneHeatingSummaryMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.200666E+11 | 77257.05 | 16-JAN-08:61 | -1.1 |
February | 0.127741E+11 | 79065.62 | 21-FEB-08:61 | 2.57 |
March | 0.102959E+11 | 78451.61 | 28-MAR-07:01 | 1.88 |
April | 0.325807E+10 | 80367.28 | 08-APR-07:01 | 4.60 |
May | 0.116267E+09 | 81969.77 | 10-MAY-07:01 | 9.40 |
June | 8208881.89 | 4946.62 | 30-JUN-07:05 | 26.02 |
July | 16484805.43 | 3304.98 | 29-JUL-07:05 | 22.48 |
August | 1380181.85 | 1788.04 | 09-AUG-07:05 | 19.68 |
September | 541765.52 | 1774.03 | 23-SEP-07:05 | 4.37 |
October | 0.102241E+10 | 81538.19 | 31-OCT-07:01 | 8.72 |
November | 0.578088E+10 | 78985.25 | 20-NOV-08:61 | 3.98 |
December | 0.180524E+11 | 77453.19 | 17-DEC-08:61 | -0.8 |
Annual Sum or Average | 0.713932E+11 | |||
Minimum of Months | 541765.52 | 1774.03 | -1.1 | |
Maximum of Months | 0.200666E+11 | 81969.77 | 26.02 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.907020E+10 | 39496.04 | 16-JAN-08:61 | -1.1 |
February | 0.547250E+10 | 40341.12 | 21-FEB-08:61 | 2.57 |
March | 0.419076E+10 | 39945.38 | 28-MAR-07:01 | 1.88 |
April | 0.108097E+10 | 40842.91 | 08-APR-07:01 | 4.60 |
May | 15638928.91 | 27867.63 | 01-MAY-07:01 | -0.9 |
June | 5731817.46 | 2682.46 | 30-JUN-07:05 | 26.02 |
July | 9877640.81 | 1914.79 | 29-JUL-07:05 | 22.48 |
August | 1225218.47 | 1148.63 | 09-AUG-07:05 | 19.68 |
September | 32849.72 | 219.00 | 01-SEP-07:05 | 16.38 |
October | 0.337916E+09 | 36874.00 | 30-OCT-07:01 | -9.0 |
November | 0.250534E+10 | 39733.85 | 14-NOV-08:61 | 2.38 |
December | 0.829089E+10 | 39520.41 | 17-DEC-08:61 | -0.8 |
Annual Sum or Average | 0.309811E+11 | |||
Minimum of Months | 32849.72 | 219.00 | -9.0 | |
Maximum of Months | 0.907020E+10 | 40842.91 | 26.02 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.105996E+11 | 40052.44 | 16-JAN-08:61 | -1.1 |
February | 0.671296E+10 | 40939.02 | 21-FEB-07:01 | 2.70 |
March | 0.530317E+10 | 39506.71 | 28-MAR-06:01 | 1.70 |
April | 0.161058E+10 | 40093.41 | 08-APR-06:01 | 3.48 |
May | 58255782.22 | 38082.07 | 01-MAY-06:01 | -3.5 |
June | 34587080.47 | 2999.79 | 29-JUN-19:02 | 30.73 |
July | 52817671.75 | 2656.14 | 29-JUL-17:12 | 29.43 |
August | 15766206.47 | 1731.30 | 08-AUG-19:12 | 26.13 |
September | 724608.07 | 431.13 | 28-SEP-11:10 | 8.98 |
October | 0.793704E+09 | 36747.94 | 30-OCT-06:01 | -9.4 |
November | 0.350387E+10 | 39779.08 | 14-NOV-07:01 | 2.70 |
December | 0.971130E+10 | 39996.93 | 17-DEC-08:61 | -0.8 |
Annual Sum or Average | 0.383974E+11 | |||
Minimum of Months | 724608.07 | 431.13 | -9.4 | |
Maximum of Months | 0.105996E+11 | 40939.02 | 30.73 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.110780E+11 | 40261.81 | 16-JAN-08:61 | -1.1 |
February | 0.707829E+10 | 41169.15 | 21-FEB-07:01 | 2.70 |
March | 0.564209E+10 | 39672.32 | 28-MAR-06:01 | 1.70 |
April | 0.181491E+10 | 40264.29 | 09-APR-07:01 | 2.12 |
May | 83062117.15 | 38284.29 | 01-MAY-06:01 | -3.5 |
June | 35660515.73 | 3007.82 | 29-JUN-19:02 | 30.73 |
July | 53507738.44 | 2665.88 | 29-JUL-17:12 | 29.43 |
August | 16277781.73 | 1740.49 | 08-AUG-19:12 | 26.13 |
September | 1141477.91 | 435.13 | 03-SEP-16:25 | 21.70 |
October | 0.952464E+09 | 36947.28 | 30-OCT-06:01 | -9.4 |
November | 0.381760E+10 | 39956.81 | 14-NOV-07:01 | 2.70 |
December | 0.101679E+11 | 40178.67 | 17-DEC-08:61 | -0.8 |
Annual Sum or Average | 0.407410E+11 | |||
Minimum of Months | 1141477.91 | 435.13 | -9.4 | |
Maximum of Months | 0.110780E+11 | 41169.15 | 30.73 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.115244E+11 | 40496.52 | 16-JAN-08:61 | -1.1 |
February | 0.746628E+10 | 41409.76 | 21-FEB-07:01 | 2.70 |
March | 0.602889E+10 | 39892.77 | 28-MAR-06:01 | 1.70 |
April | 0.203034E+10 | 40490.46 | 09-APR-07:01 | 2.12 |
May | 0.112756E+09 | 39229.73 | 02-MAY-06:02 | 1.18 |
June | 37957223.82 | 3020.26 | 29-JUN-19:02 | 30.73 |
July | 54805599.91 | 2678.06 | 29-JUL-17:12 | 29.43 |
August | 17177873.31 | 1754.74 | 08-AUG-19:12 | 26.13 |
September | 2651162.95 | 572.08 | 24-SEP-07:10 | 7.38 |
October | 0.109030E+10 | 38875.83 | 10-OCT-06:02 | 3.90 |
November | 0.411370E+10 | 40183.86 | 14-NOV-07:01 | 2.70 |
December | 0.106037E+11 | 40409.55 | 17-DEC-08:61 | -0.8 |
Annual Sum or Average | 0.430830E+11 | |||
Minimum of Months | 2651162.95 | 572.08 | -1.1 | |
Maximum of Months | 0.115244E+11 | 41409.76 | 30.73 |
Report: ZoneHeatingSummaryMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.217584E+11 | 76880.56 | 16-JAN-09:01 | -1.0 |
February | 0.141708E+11 | 78427.10 | 21-FEB-08:61 | 2.57 |
March | 0.115515E+11 | 77110.78 | 28-MAR-07:01 | 1.88 |
April | 0.405392E+10 | 79514.37 | 30-APR-08:61 | 5.97 |
May | 0.251187E+09 | 80505.30 | 10-MAY-07:01 | 9.40 |
June | 37433071.32 | 5032.49 | 24-JUN-17:02 | 29.22 |
July | 72266674.29 | 5196.11 | 29-JUL-17:02 | 29.72 |
August | 13378882.46 | 2703.00 | 26-AUG-17:03 | 25.63 |
September | 30793947.38 | 20661.47 | 28-SEP-07:02 | 6.78 |
October | 0.218890E+10 | 80441.36 | 31-OCT-07:01 | 8.72 |
November | 0.795254E+10 | 81060.30 | 01-NOV-07:01 | 11.78 |
December | 0.200756E+11 | 76798.46 | 17-DEC-09:01 | -0.5 |
Annual Sum or Average | 0.821567E+11 | |||
Minimum of Months | 13378882.46 | 2703.00 | -1.0 | |
Maximum of Months | 0.217584E+11 | 81060.30 | 29.72 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.120599E+11 | 41129.07 | 16-JAN-09:01 | -1.0 |
February | 0.794082E+10 | 41900.74 | 21-FEB-08:61 | 2.57 |
March | 0.656919E+10 | 41250.48 | 28-MAR-07:01 | 1.88 |
April | 0.240127E+10 | 42466.92 | 30-APR-08:61 | 5.97 |
May | 0.170907E+09 | 42947.34 | 10-MAY-07:01 | 9.40 |
June | 25213783.41 | 2643.45 | 24-JUN-17:02 | 29.22 |
July | 43231082.55 | 2718.49 | 29-JUL-17:02 | 29.72 |
August | 10951694.17 | 1473.66 | 26-AUG-17:03 | 25.63 |
September | 23385327.84 | 10824.84 | 28-SEP-07:02 | 6.78 |
October | 0.134570E+10 | 42903.59 | 31-OCT-07:01 | 8.72 |
November | 0.458062E+10 | 43106.64 | 01-NOV-07:01 | 11.78 |
December | 0.111504E+11 | 41088.54 | 17-DEC-09:01 | -0.5 |
Annual Sum or Average | 0.463216E+11 | |||
Minimum of Months | 10951694.17 | 1473.66 | -1.0 | |
Maximum of Months | 0.120599E+11 | 43106.64 | 29.72 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.121147E+11 | 41117.80 | 16-JAN-09:01 | -1.0 |
February | 0.800549E+10 | 41894.36 | 21-FEB-08:61 | 2.57 |
March | 0.666473E+10 | 41260.87 | 28-MAR-07:01 | 1.88 |
April | 0.249619E+10 | 44082.06 | 18-APR-07:01 | 13.58 |
May | 0.195953E+09 | 42962.63 | 10-MAY-07:01 | 9.40 |
June | 27176663.82 | 3853.06 | 04-JUN-08:62 | 13.27 |
July | 43546756.67 | 2723.56 | 29-JUL-17:02 | 29.72 |
August | 11294195.29 | 1479.17 | 26-AUG-17:03 | 25.63 |
September | 28621795.18 | 12379.09 | 28-SEP-07:02 | 6.78 |
October | 0.140009E+10 | 42904.79 | 31-OCT-07:01 | 8.72 |
November | 0.466527E+10 | 43145.75 | 01-NOV-07:01 | 11.78 |
December | 0.112029E+11 | 41079.77 | 17-DEC-09:01 | -0.5 |
Annual Sum or Average | 0.468560E+11 | |||
Minimum of Months | 11294195.29 | 1479.17 | -1.0 | |
Maximum of Months | 0.121147E+11 | 44082.06 | 29.72 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.125698E+11 | 41254.88 | 16-JAN-09:01 | -1.0 |
February | 0.845763E+10 | 42208.72 | 21-FEB-08:61 | 2.57 |
March | 0.717488E+10 | 41631.67 | 28-MAR-07:01 | 1.88 |
April | 0.290344E+10 | 44477.67 | 18-APR-07:01 | 13.58 |
May | 0.307492E+09 | 43340.51 | 10-MAY-07:01 | 9.40 |
June | 37350786.48 | 11492.90 | 04-JUN-08:62 | 13.27 |
July | 44082659.01 | 2741.82 | 29-JUL-17:02 | 29.72 |
August | 12494946.45 | 1496.90 | 26-AUG-17:03 | 25.63 |
September | 52075456.87 | 17860.00 | 28-SEP-07:02 | 6.78 |
October | 0.158562E+10 | 43221.79 | 31-OCT-07:01 | 8.72 |
November | 0.501964E+10 | 43467.89 | 01-NOV-07:01 | 11.78 |
December | 0.116423E+11 | 41388.43 | 17-DEC-09:01 | -0.5 |
Annual Sum or Average | 0.498069E+11 | |||
Minimum of Months | 12494946.45 | 1496.90 | -1.0 | |
Maximum of Months | 0.125698E+11 | 44477.67 | 29.72 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.176068E+11 | 44301.36 | 16-JAN-09:01 | -1.0 |
February | 0.126303E+11 | 45333.15 | 21-FEB-08:61 | 2.57 |
March | 0.110833E+11 | 45094.31 | 28-MAR-07:01 | 1.88 |
April | 0.523953E+10 | 47909.62 | 18-APR-07:01 | 13.58 |
May | 0.923550E+09 | 46821.39 | 10-MAY-07:01 | 9.40 |
June | 0.143014E+09 | 32360.35 | 04-JUN-08:62 | 13.27 |
July | 52659799.42 | 2808.39 | 29-JUL-17:12 | 29.43 |
August | 17597540.88 | 3143.71 | 19-AUG-07:05 | 9.87 |
September | 0.215858E+09 | 44107.29 | 28-SEP-07:02 | 6.78 |
October | 0.242814E+10 | 46525.65 | 31-OCT-07:01 | 8.72 |
November | 0.709768E+10 | 46614.93 | 01-NOV-07:01 | 11.78 |
December | 0.161181E+11 | 44418.27 | 17-DEC-09:01 | -0.5 |
Annual Sum or Average | 0.735565E+11 | |||
Minimum of Months | 17597540.88 | 2808.39 | -1.0 | |
Maximum of Months | 0.176068E+11 | 47909.62 | 29.43 |
Report: ZoneElectricSummaryMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.157219E+11 | 9537.57 | 01-JAN-10:09 | 0.223514E+10 | 1348.26 | 01-JAN-10:09 |
February | 0.142256E+11 | 9537.57 | 01-FEB-10:09 | 0.202238E+10 | 1348.26 | 01-FEB-10:09 |
March | 0.157545E+11 | 9537.57 | 01-MAR-10:09 | 0.223972E+10 | 1348.26 | 01-MAR-10:09 |
April | 0.152557E+11 | 9537.57 | 01-APR-09:09 | 0.216880E+10 | 1348.26 | 01-APR-09:09 |
May | 0.157219E+11 | 9537.57 | 01-MAY-09:09 | 0.223514E+10 | 1348.26 | 01-MAY-09:09 |
June | 0.152557E+11 | 9537.57 | 01-JUN-09:09 | 0.216880E+10 | 1348.26 | 01-JUN-09:09 |
July | 0.157545E+11 | 9537.57 | 01-JUL-09:09 | 0.223972E+10 | 1348.26 | 01-JUL-09:09 |
August | 0.157219E+11 | 9537.57 | 01-AUG-09:09 | 0.223514E+10 | 1348.26 | 01-AUG-09:09 |
September | 0.152882E+11 | 9537.57 | 01-SEP-09:09 | 0.217339E+10 | 1348.26 | 01-SEP-09:09 |
October | 0.157219E+11 | 9537.57 | 01-OCT-09:09 | 0.223514E+10 | 1348.26 | 01-OCT-09:09 |
November | 0.151906E+11 | 9537.57 | 01-NOV-09:09 | 0.215964E+10 | 1348.26 | 01-NOV-09:09 |
December | 0.157870E+11 | 9537.57 | 01-DEC-10:09 | 0.224431E+10 | 1348.26 | 01-DEC-10:09 |
Annual Sum or Average | 0.185400E+12 | 0.263573E+11 | ||||
Minimum of Months | 0.142256E+11 | 9537.57 | 0.202238E+10 | 1348.26 | ||
Maximum of Months | 0.157870E+11 | 9537.57 | 0.224431E+10 | 1348.26 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.786097E+10 | 4768.79 | 01-JAN-10:09 | 0.111757E+10 | 674.13 | 01-JAN-10:09 |
February | 0.711282E+10 | 4768.79 | 01-FEB-10:09 | 0.101119E+10 | 674.13 | 01-FEB-10:09 |
March | 0.787723E+10 | 4768.79 | 01-MAR-10:09 | 0.111986E+10 | 674.13 | 01-MAR-10:09 |
April | 0.762785E+10 | 4768.79 | 01-APR-09:09 | 0.108440E+10 | 674.13 | 01-APR-09:09 |
May | 0.786097E+10 | 4768.79 | 01-MAY-09:09 | 0.111757E+10 | 674.13 | 01-MAY-09:09 |
June | 0.762785E+10 | 4768.79 | 01-JUN-09:09 | 0.108440E+10 | 674.13 | 01-JUN-09:09 |
July | 0.787723E+10 | 4768.79 | 01-JUL-09:09 | 0.111986E+10 | 674.13 | 01-JUL-09:09 |
August | 0.786097E+10 | 4768.79 | 01-AUG-09:09 | 0.111757E+10 | 674.13 | 01-AUG-09:09 |
September | 0.764411E+10 | 4768.79 | 01-SEP-09:09 | 0.108669E+10 | 674.13 | 01-SEP-09:09 |
October | 0.786097E+10 | 4768.79 | 01-OCT-09:09 | 0.111757E+10 | 674.13 | 01-OCT-09:09 |
November | 0.759532E+10 | 4768.79 | 01-NOV-09:09 | 0.107982E+10 | 674.13 | 01-NOV-09:09 |
December | 0.789349E+10 | 4768.79 | 01-DEC-10:09 | 0.112215E+10 | 674.13 | 01-DEC-10:09 |
Annual Sum or Average | 0.926998E+11 | 0.131787E+11 | ||||
Minimum of Months | 0.711282E+10 | 4768.79 | 0.101119E+10 | 674.13 | ||
Maximum of Months | 0.789349E+10 | 4768.79 | 0.112215E+10 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.486999E+10 | 3744.57 | 01-JAN-10:09 | 0.883781E+09 | 674.13 | 01-JAN-10:09 |
February | 0.441023E+10 | 3744.57 | 01-FEB-09:09 | 0.800324E+09 | 674.13 | 01-FEB-09:09 |
March | 0.497215E+10 | 3744.57 | 01-MAR-09:09 | 0.902118E+09 | 674.13 | 01-MAR-09:09 |
April | 0.472525E+10 | 3744.57 | 01-APR-08:09 | 0.857490E+09 | 674.13 | 01-APR-08:09 |
May | 0.492107E+10 | 3744.57 | 01-MAY-08:09 | 0.892950E+09 | 674.13 | 01-MAY-08:09 |
June | 0.480187E+10 | 3744.57 | 01-JUN-08:09 | 0.871243E+09 | 674.13 | 01-JUN-08:09 |
July | 0.484444E+10 | 3744.57 | 01-JUL-08:09 | 0.879197E+09 | 674.13 | 01-JUL-08:09 |
August | 0.497215E+10 | 3744.57 | 01-AUG-08:09 | 0.902118E+09 | 674.13 | 01-AUG-08:09 |
September | 0.472525E+10 | 3744.57 | 01-SEP-08:09 | 0.857490E+09 | 674.13 | 01-SEP-08:09 |
October | 0.486999E+10 | 3744.57 | 01-OCT-09:09 | 0.883781E+09 | 674.13 | 01-OCT-09:09 |
November | 0.472525E+10 | 3744.57 | 01-NOV-08:09 | 0.857490E+09 | 674.13 | 01-NOV-08:09 |
December | 0.484444E+10 | 3744.57 | 01-DEC-09:09 | 0.879197E+09 | 674.13 | 01-DEC-09:09 |
Annual Sum or Average | 0.576821E+11 | 0.104672E+11 | ||||
Minimum of Months | 0.441023E+10 | 3744.57 | 0.800324E+09 | 674.13 | ||
Maximum of Months | 0.497215E+10 | 3744.57 | 0.902118E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.486999E+10 | 3744.57 | 01-JAN-10:09 | 0.883781E+09 | 674.13 | 01-JAN-10:09 |
February | 0.441023E+10 | 3744.57 | 01-FEB-09:09 | 0.800324E+09 | 674.13 | 01-FEB-09:09 |
March | 0.497215E+10 | 3744.57 | 01-MAR-09:09 | 0.902118E+09 | 674.13 | 01-MAR-09:09 |
April | 0.472525E+10 | 3744.57 | 01-APR-08:09 | 0.857490E+09 | 674.13 | 01-APR-08:09 |
May | 0.492107E+10 | 3744.57 | 01-MAY-08:09 | 0.892950E+09 | 674.13 | 01-MAY-08:09 |
June | 0.480187E+10 | 3744.57 | 01-JUN-08:09 | 0.871243E+09 | 674.13 | 01-JUN-08:09 |
July | 0.484444E+10 | 3744.57 | 01-JUL-08:09 | 0.879197E+09 | 674.13 | 01-JUL-08:09 |
August | 0.497215E+10 | 3744.57 | 01-AUG-08:09 | 0.902118E+09 | 674.13 | 01-AUG-08:09 |
September | 0.472525E+10 | 3744.57 | 01-SEP-08:09 | 0.857490E+09 | 674.13 | 01-SEP-08:09 |
October | 0.486999E+10 | 3744.57 | 01-OCT-09:09 | 0.883781E+09 | 674.13 | 01-OCT-09:09 |
November | 0.472525E+10 | 3744.57 | 01-NOV-08:09 | 0.857490E+09 | 674.13 | 01-NOV-08:09 |
December | 0.484444E+10 | 3744.57 | 01-DEC-09:09 | 0.879197E+09 | 674.13 | 01-DEC-09:09 |
Annual Sum or Average | 0.576821E+11 | 0.104672E+11 | ||||
Minimum of Months | 0.441023E+10 | 3744.57 | 0.800324E+09 | 674.13 | ||
Maximum of Months | 0.497215E+10 | 3744.57 | 0.902118E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.486999E+10 | 3744.57 | 01-JAN-10:09 | 0.883781E+09 | 674.13 | 01-JAN-10:09 |
February | 0.441023E+10 | 3744.57 | 01-FEB-09:09 | 0.800324E+09 | 674.13 | 01-FEB-09:09 |
March | 0.497215E+10 | 3744.57 | 01-MAR-09:09 | 0.902118E+09 | 674.13 | 01-MAR-09:09 |
April | 0.472525E+10 | 3744.57 | 01-APR-08:09 | 0.857490E+09 | 674.13 | 01-APR-08:09 |
May | 0.492107E+10 | 3744.57 | 01-MAY-08:09 | 0.892950E+09 | 674.13 | 01-MAY-08:09 |
June | 0.480187E+10 | 3744.57 | 01-JUN-08:09 | 0.871243E+09 | 674.13 | 01-JUN-08:09 |
July | 0.484444E+10 | 3744.57 | 01-JUL-08:09 | 0.879197E+09 | 674.13 | 01-JUL-08:09 |
August | 0.497215E+10 | 3744.57 | 01-AUG-08:09 | 0.902118E+09 | 674.13 | 01-AUG-08:09 |
September | 0.472525E+10 | 3744.57 | 01-SEP-08:09 | 0.857490E+09 | 674.13 | 01-SEP-08:09 |
October | 0.486999E+10 | 3744.57 | 01-OCT-09:09 | 0.883781E+09 | 674.13 | 01-OCT-09:09 |
November | 0.472525E+10 | 3744.57 | 01-NOV-08:09 | 0.857490E+09 | 674.13 | 01-NOV-08:09 |
December | 0.484444E+10 | 3744.57 | 01-DEC-09:09 | 0.879197E+09 | 674.13 | 01-DEC-09:09 |
Annual Sum or Average | 0.576821E+11 | 0.104672E+11 | ||||
Minimum of Months | 0.441023E+10 | 3744.57 | 0.800324E+09 | 674.13 | ||
Maximum of Months | 0.497215E+10 | 3744.57 | 0.902118E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.724555E+10 | 6064.13 | 01-JAN-11:09 | 0.162546E+10 | 1348.26 | 01-JAN-11:09 |
February | 0.656305E+10 | 6064.13 | 01-FEB-10:09 | 0.147229E+10 | 1348.26 | 01-FEB-10:09 |
March | 0.741101E+10 | 6064.13 | 01-MAR-10:09 | 0.166213E+10 | 1348.26 | 01-MAR-10:09 |
April | 0.703184E+10 | 6064.13 | 01-APR-09:09 | 0.157746E+10 | 1348.26 | 01-APR-09:09 |
May | 0.732828E+10 | 6064.13 | 01-MAY-09:09 | 0.164379E+10 | 1348.26 | 01-MAY-09:09 |
June | 0.715593E+10 | 6064.13 | 01-JUN-09:09 | 0.160496E+10 | 1348.26 | 01-JUN-09:09 |
July | 0.720419E+10 | 6064.13 | 01-JUL-09:09 | 0.161629E+10 | 1348.26 | 01-JUL-09:09 |
August | 0.741101E+10 | 6064.13 | 01-AUG-09:09 | 0.166213E+10 | 1348.26 | 01-AUG-09:09 |
September | 0.703184E+10 | 6064.13 | 01-SEP-09:09 | 0.157746E+10 | 1348.26 | 01-SEP-09:09 |
October | 0.724555E+10 | 6064.13 | 01-OCT-10:09 | 0.162546E+10 | 1348.26 | 01-OCT-10:09 |
November | 0.703184E+10 | 6064.13 | 01-NOV-09:09 | 0.157746E+10 | 1348.26 | 01-NOV-09:09 |
December | 0.720419E+10 | 6064.13 | 01-DEC-10:09 | 0.161629E+10 | 1348.26 | 01-DEC-10:09 |
Annual Sum or Average | 0.858643E+11 | 0.192612E+11 | ||||
Minimum of Months | 0.656305E+10 | 6064.13 | 0.147229E+10 | 1348.26 | ||
Maximum of Months | 0.741101E+10 | 6064.13 | 0.166213E+10 | 1348.26 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.362278E+10 | 3032.07 | 01-JAN-11:09 | 0.812728E+09 | 674.13 | 01-JAN-11:09 |
February | 0.328152E+10 | 3032.07 | 01-FEB-10:09 | 0.736147E+09 | 674.13 | 01-FEB-10:09 |
March | 0.370550E+10 | 3032.07 | 01-MAR-10:09 | 0.831065E+09 | 674.13 | 01-MAR-10:09 |
April | 0.351592E+10 | 3032.07 | 01-APR-09:09 | 0.788729E+09 | 674.13 | 01-APR-09:09 |
May | 0.366414E+10 | 3032.07 | 01-MAY-09:09 | 0.821897E+09 | 674.13 | 01-MAY-09:09 |
June | 0.357797E+10 | 3032.07 | 01-JUN-09:09 | 0.802482E+09 | 674.13 | 01-JUN-09:09 |
July | 0.360209E+10 | 3032.07 | 01-JUL-09:09 | 0.808144E+09 | 674.13 | 01-JUL-09:09 |
August | 0.370550E+10 | 3032.07 | 01-AUG-09:09 | 0.831065E+09 | 674.13 | 01-AUG-09:09 |
September | 0.351592E+10 | 3032.07 | 01-SEP-09:09 | 0.788729E+09 | 674.13 | 01-SEP-09:09 |
October | 0.362278E+10 | 3032.07 | 01-OCT-10:09 | 0.812728E+09 | 674.13 | 01-OCT-10:09 |
November | 0.351592E+10 | 3032.07 | 01-NOV-09:09 | 0.788729E+09 | 674.13 | 01-NOV-09:09 |
December | 0.360209E+10 | 3032.07 | 01-DEC-10:09 | 0.808144E+09 | 674.13 | 01-DEC-10:09 |
Annual Sum or Average | 0.429321E+11 | 0.963059E+10 | ||||
Minimum of Months | 0.328152E+10 | 3032.07 | 0.736147E+09 | 674.13 | ||
Maximum of Months | 0.370550E+10 | 3032.07 | 0.831065E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.362278E+10 | 3032.07 | 01-JAN-11:09 | 0.812728E+09 | 674.13 | 01-JAN-11:09 |
February | 0.328152E+10 | 3032.07 | 01-FEB-10:09 | 0.736147E+09 | 674.13 | 01-FEB-10:09 |
March | 0.370550E+10 | 3032.07 | 01-MAR-10:09 | 0.831065E+09 | 674.13 | 01-MAR-10:09 |
April | 0.351592E+10 | 3032.07 | 01-APR-09:09 | 0.788729E+09 | 674.13 | 01-APR-09:09 |
May | 0.366414E+10 | 3032.07 | 01-MAY-09:09 | 0.821897E+09 | 674.13 | 01-MAY-09:09 |
June | 0.357797E+10 | 3032.07 | 01-JUN-09:09 | 0.802482E+09 | 674.13 | 01-JUN-09:09 |
July | 0.360209E+10 | 3032.07 | 01-JUL-09:09 | 0.808144E+09 | 674.13 | 01-JUL-09:09 |
August | 0.370550E+10 | 3032.07 | 01-AUG-09:09 | 0.831065E+09 | 674.13 | 01-AUG-09:09 |
September | 0.351592E+10 | 3032.07 | 01-SEP-09:09 | 0.788729E+09 | 674.13 | 01-SEP-09:09 |
October | 0.362278E+10 | 3032.07 | 01-OCT-10:09 | 0.812728E+09 | 674.13 | 01-OCT-10:09 |
November | 0.351592E+10 | 3032.07 | 01-NOV-09:09 | 0.788729E+09 | 674.13 | 01-NOV-09:09 |
December | 0.360209E+10 | 3032.07 | 01-DEC-10:09 | 0.808144E+09 | 674.13 | 01-DEC-10:09 |
Annual Sum or Average | 0.429321E+11 | 0.963059E+10 | ||||
Minimum of Months | 0.328152E+10 | 3032.07 | 0.736147E+09 | 674.13 | ||
Maximum of Months | 0.370550E+10 | 3032.07 | 0.831065E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.362278E+10 | 3032.07 | 01-JAN-11:09 | 0.812728E+09 | 674.13 | 01-JAN-11:09 |
February | 0.328152E+10 | 3032.07 | 01-FEB-10:09 | 0.736147E+09 | 674.13 | 01-FEB-10:09 |
March | 0.370550E+10 | 3032.07 | 01-MAR-10:09 | 0.831065E+09 | 674.13 | 01-MAR-10:09 |
April | 0.351592E+10 | 3032.07 | 01-APR-09:09 | 0.788729E+09 | 674.13 | 01-APR-09:09 |
May | 0.366414E+10 | 3032.07 | 01-MAY-09:09 | 0.821897E+09 | 674.13 | 01-MAY-09:09 |
June | 0.357797E+10 | 3032.07 | 01-JUN-09:09 | 0.802482E+09 | 674.13 | 01-JUN-09:09 |
July | 0.360209E+10 | 3032.07 | 01-JUL-09:09 | 0.808144E+09 | 674.13 | 01-JUL-09:09 |
August | 0.370550E+10 | 3032.07 | 01-AUG-09:09 | 0.831065E+09 | 674.13 | 01-AUG-09:09 |
September | 0.351592E+10 | 3032.07 | 01-SEP-09:09 | 0.788729E+09 | 674.13 | 01-SEP-09:09 |
October | 0.362278E+10 | 3032.07 | 01-OCT-10:09 | 0.812728E+09 | 674.13 | 01-OCT-10:09 |
November | 0.351592E+10 | 3032.07 | 01-NOV-09:09 | 0.788729E+09 | 674.13 | 01-NOV-09:09 |
December | 0.360209E+10 | 3032.07 | 01-DEC-10:09 | 0.808144E+09 | 674.13 | 01-DEC-10:09 |
Annual Sum or Average | 0.429321E+11 | 0.963059E+10 | ||||
Minimum of Months | 0.328152E+10 | 3032.07 | 0.736147E+09 | 674.13 | ||
Maximum of Months | 0.370550E+10 | 3032.07 | 0.831065E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.362278E+10 | 3032.07 | 01-JAN-11:09 | 0.812728E+09 | 674.13 | 01-JAN-11:09 |
February | 0.328152E+10 | 3032.07 | 01-FEB-10:09 | 0.736147E+09 | 674.13 | 01-FEB-10:09 |
March | 0.370550E+10 | 3032.07 | 01-MAR-10:09 | 0.831065E+09 | 674.13 | 01-MAR-10:09 |
April | 0.351592E+10 | 3032.07 | 01-APR-09:09 | 0.788729E+09 | 674.13 | 01-APR-09:09 |
May | 0.366414E+10 | 3032.07 | 01-MAY-09:09 | 0.821897E+09 | 674.13 | 01-MAY-09:09 |
June | 0.357797E+10 | 3032.07 | 01-JUN-09:09 | 0.802482E+09 | 674.13 | 01-JUN-09:09 |
July | 0.360209E+10 | 3032.07 | 01-JUL-09:09 | 0.808144E+09 | 674.13 | 01-JUL-09:09 |
August | 0.370550E+10 | 3032.07 | 01-AUG-09:09 | 0.831065E+09 | 674.13 | 01-AUG-09:09 |
September | 0.351592E+10 | 3032.07 | 01-SEP-09:09 | 0.788729E+09 | 674.13 | 01-SEP-09:09 |
October | 0.362278E+10 | 3032.07 | 01-OCT-10:09 | 0.812728E+09 | 674.13 | 01-OCT-10:09 |
November | 0.351592E+10 | 3032.07 | 01-NOV-09:09 | 0.788729E+09 | 674.13 | 01-NOV-09:09 |
December | 0.360209E+10 | 3032.07 | 01-DEC-10:09 | 0.808144E+09 | 674.13 | 01-DEC-10:09 |
Annual Sum or Average | 0.429321E+11 | 0.963059E+10 | ||||
Minimum of Months | 0.328152E+10 | 3032.07 | 0.736147E+09 | 674.13 | ||
Maximum of Months | 0.370550E+10 | 3032.07 | 0.831065E+09 | 674.13 |
Report: SpaceGainsMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.180574E+10 | 0.157219E+11 | 0.223514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.180654E+11 |
February | 0.163016E+10 | 0.142256E+11 | 0.202238E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132764E+11 |
March | 0.178954E+10 | 0.157545E+11 | 0.223972E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115132E+11 |
April | 0.174484E+10 | 0.152557E+11 | 0.216880E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11722384.70 | 0.691096E+10 |
May | 0.179537E+10 | 0.157219E+11 | 0.223514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.167417E+09 | 0.309056E+10 |
June | 0.173447E+10 | 0.152557E+11 | 0.216880E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.409200E+09 | 0.161052E+10 |
July | 0.181028E+10 | 0.157545E+11 | 0.223972E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.578937E+09 | 0.103777E+10 |
August | 0.178501E+10 | 0.157219E+11 | 0.223514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.240933E+09 | 0.163346E+10 |
September | 0.174937E+10 | 0.152882E+11 | 0.217339E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11544373.53 | 0.367916E+10 |
October | 0.180574E+10 | 0.157219E+11 | 0.223514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.639831E+10 |
November | 0.174613E+10 | 0.151906E+11 | 0.215964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102761E+11 |
December | 0.181481E+10 | 0.157870E+11 | 0.224431E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175257E+11 |
Annual Sum or Average | 0.212115E+11 | 0.185400E+12 | 0.263573E+11 | 0.141975E+10 | 0.950175E+11 | ||||
Minimum of Months | 0.163016E+10 | 0.142256E+11 | 0.202238E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103777E+10 |
Maximum of Months | 0.181481E+10 | 0.157870E+11 | 0.224431E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.578937E+09 | 0.180654E+11 |
Report: SpaceGainsMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.902868E+09 | 0.786097E+10 | 0.111757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.920946E+10 |
February | 0.815075E+09 | 0.711282E+10 | 0.101119E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.665543E+10 |
March | 0.894769E+09 | 0.787723E+10 | 0.111986E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.588448E+10 |
April | 0.872416E+09 | 0.762785E+10 | 0.108440E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6244719.20 | 0.341586E+10 |
May | 0.897684E+09 | 0.786097E+10 | 0.111757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 93110737.73 | 0.151955E+10 |
June | 0.867232E+09 | 0.762785E+10 | 0.108440E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.223898E+09 | 0.767812E+09 |
July | 0.905135E+09 | 0.787723E+10 | 0.111986E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.320436E+09 | 0.479207E+09 |
August | 0.892501E+09 | 0.786097E+10 | 0.111757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133584E+09 | 0.753492E+09 |
September | 0.874683E+09 | 0.764411E+10 | 0.108669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6463657.42 | 0.180079E+10 |
October | 0.902868E+09 | 0.786097E+10 | 0.111757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.324997E+10 |
November | 0.873064E+09 | 0.759532E+10 | 0.107982E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.511951E+10 |
December | 0.907403E+09 | 0.789349E+10 | 0.112215E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.888250E+10 |
Annual Sum or Average | 0.106057E+11 | 0.926998E+11 | 0.131787E+11 | 0.783737E+09 | 0.477381E+11 | ||||
Minimum of Months | 0.815075E+09 | 0.711282E+10 | 0.101119E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.479207E+09 |
Maximum of Months | 0.907403E+09 | 0.789349E+10 | 0.112215E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.320436E+09 | 0.920946E+10 |
Report: SpaceGainsMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.537120E+09 | 0.486999E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.940202E+10 |
February | 0.487879E+09 | 0.441023E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.685007E+10 |
March | 0.551374E+09 | 0.497215E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.598747E+10 |
April | 0.524810E+09 | 0.472525E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4120323.44 | 0.348355E+10 |
May | 0.544247E+09 | 0.492107E+10 | 0.892950E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 93086707.00 | 0.152956E+10 |
June | 0.532585E+09 | 0.480187E+10 | 0.871243E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.221587E+09 | 0.789726E+09 |
July | 0.536472E+09 | 0.484444E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.312523E+09 | 0.515090E+09 |
August | 0.551374E+09 | 0.497215E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133410E+09 | 0.795860E+09 |
September | 0.524810E+09 | 0.472525E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6463309.10 | 0.181374E+10 |
October | 0.537120E+09 | 0.486999E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.329307E+10 |
November | 0.518979E+09 | 0.472525E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.524209E+10 |
December | 0.536472E+09 | 0.484444E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.910482E+10 |
Annual Sum or Average | 0.638324E+10 | 0.576821E+11 | 0.104672E+11 | 0.771191E+09 | 0.488071E+11 | ||||
Minimum of Months | 0.487879E+09 | 0.441023E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.515090E+09 |
Maximum of Months | 0.551374E+09 | 0.497215E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.312523E+09 | 0.940202E+10 |
Report: SpaceGainsMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.537120E+09 | 0.486999E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.939162E+10 |
February | 0.487879E+09 | 0.441023E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.683831E+10 |
March | 0.551374E+09 | 0.497215E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.597842E+10 |
April | 0.524810E+09 | 0.472525E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4236484.28 | 0.346505E+10 |
May | 0.544247E+09 | 0.492107E+10 | 0.892950E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 93086491.66 | 0.150983E+10 |
June | 0.532585E+09 | 0.480187E+10 | 0.871243E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.221591E+09 | 0.780960E+09 |
July | 0.536472E+09 | 0.484444E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.312525E+09 | 0.512991E+09 |
August | 0.551374E+09 | 0.497215E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133409E+09 | 0.792656E+09 |
September | 0.524810E+09 | 0.472525E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6463238.12 | 0.179904E+10 |
October | 0.537120E+09 | 0.486999E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.327751E+10 |
November | 0.518979E+09 | 0.472525E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.522799E+10 |
December | 0.536472E+09 | 0.484444E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.909216E+10 |
Annual Sum or Average | 0.638324E+10 | 0.576821E+11 | 0.104672E+11 | 0.771312E+09 | 0.486665E+11 | ||||
Minimum of Months | 0.487879E+09 | 0.441023E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.512991E+09 |
Maximum of Months | 0.551374E+09 | 0.497215E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.312525E+09 | 0.939162E+10 |
Report: SpaceGainsMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.537120E+09 | 0.486999E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.938686E+10 |
February | 0.487879E+09 | 0.441023E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.683241E+10 |
March | 0.551374E+09 | 0.497215E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.597322E+10 |
April | 0.524810E+09 | 0.472525E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4353649.17 | 0.345186E+10 |
May | 0.544247E+09 | 0.492107E+10 | 0.892950E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 93086227.14 | 0.149317E+10 |
June | 0.532585E+09 | 0.480187E+10 | 0.871243E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.221745E+09 | 0.771910E+09 |
July | 0.536472E+09 | 0.484444E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.312580E+09 | 0.509288E+09 |
August | 0.551374E+09 | 0.497215E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133408E+09 | 0.787891E+09 |
September | 0.524810E+09 | 0.472525E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6463285.43 | 0.178695E+10 |
October | 0.537120E+09 | 0.486999E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.326814E+10 |
November | 0.518979E+09 | 0.472525E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.521962E+10 |
December | 0.536472E+09 | 0.484444E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.908582E+10 |
Annual Sum or Average | 0.638324E+10 | 0.576821E+11 | 0.104672E+11 | 0.771636E+09 | 0.485671E+11 | ||||
Minimum of Months | 0.487879E+09 | 0.441023E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.509288E+09 |
Maximum of Months | 0.551374E+09 | 0.497215E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.312580E+09 | 0.938686E+10 |
Report: SpaceGainsMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.183632E+10 | 0.724555E+10 | 0.162546E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168562E+11 |
February | 0.167188E+10 | 0.656305E+10 | 0.147229E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123115E+11 |
March | 0.189386E+10 | 0.741101E+10 | 0.166213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107148E+11 |
April | 0.180380E+10 | 0.703184E+10 | 0.157746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8282549.28 | 0.622820E+10 |
May | 0.186509E+10 | 0.732828E+10 | 0.164379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163549E+09 | 0.267673E+10 |
June | 0.182945E+10 | 0.715593E+10 | 0.160496E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.391703E+09 | 0.138723E+10 |
July | 0.183943E+10 | 0.720419E+10 | 0.161629E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.549813E+09 | 0.932230E+09 |
August | 0.189386E+10 | 0.741101E+10 | 0.166213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.234520E+09 | 0.143933E+10 |
September | 0.180380E+10 | 0.703184E+10 | 0.157746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11342509.38 | 0.322280E+10 |
October | 0.183632E+10 | 0.724555E+10 | 0.162546E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.586540E+10 |
November | 0.176881E+10 | 0.703184E+10 | 0.157746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.941418E+10 |
December | 0.183943E+10 | 0.720419E+10 | 0.161629E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163426E+11 |
Annual Sum or Average | 0.218821E+11 | 0.858643E+11 | 0.192612E+11 | 0.135921E+10 | 0.873913E+11 | ||||
Minimum of Months | 0.167188E+10 | 0.656305E+10 | 0.147229E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.932230E+09 |
Maximum of Months | 0.189386E+10 | 0.741101E+10 | 0.166213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.549813E+09 | 0.168562E+11 |
Report: SpaceGainsMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.918158E+09 | 0.362278E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.943657E+10 |
February | 0.835938E+09 | 0.328152E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.686653E+10 |
March | 0.946926E+09 | 0.370550E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.600119E+10 |
April | 0.901896E+09 | 0.351592E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4710105.44 | 0.345753E+10 |
May | 0.932542E+09 | 0.366414E+10 | 0.821897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 93112738.48 | 0.147765E+10 |
June | 0.914724E+09 | 0.357797E+10 | 0.802482E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.222631E+09 | 0.761927E+09 |
July | 0.919713E+09 | 0.360209E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.312915E+09 | 0.509616E+09 |
August | 0.946926E+09 | 0.370550E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133457E+09 | 0.788929E+09 |
September | 0.901896E+09 | 0.351592E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6463795.07 | 0.178699E+10 |
October | 0.918158E+09 | 0.362278E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.327588E+10 |
November | 0.884402E+09 | 0.351592E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.524487E+10 |
December | 0.919713E+09 | 0.360209E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.913524E+10 |
Annual Sum or Average | 0.109410E+11 | 0.429321E+11 | 0.963059E+10 | 0.773290E+09 | 0.487429E+11 | ||||
Minimum of Months | 0.835938E+09 | 0.328152E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.509616E+09 |
Maximum of Months | 0.946926E+09 | 0.370550E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.312915E+09 | 0.943657E+10 |
Report: SpaceGainsMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.918158E+09 | 0.362278E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.943602E+10 |
February | 0.835938E+09 | 0.328152E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.686561E+10 |
March | 0.946926E+09 | 0.370550E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.599965E+10 |
April | 0.901896E+09 | 0.351592E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4809765.71 | 0.345114E+10 |
May | 0.932542E+09 | 0.366414E+10 | 0.821897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 93112715.96 | 0.146783E+10 |
June | 0.914724E+09 | 0.357797E+10 | 0.802482E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.222707E+09 | 0.755571E+09 |
July | 0.919713E+09 | 0.360209E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.312964E+09 | 0.507392E+09 |
August | 0.946926E+09 | 0.370550E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133457E+09 | 0.786193E+09 |
September | 0.901896E+09 | 0.351592E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6463739.04 | 0.178113E+10 |
October | 0.918158E+09 | 0.362278E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.327262E+10 |
November | 0.884402E+09 | 0.351592E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.524224E+10 |
December | 0.919713E+09 | 0.360209E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.913443E+10 |
Annual Sum or Average | 0.109410E+11 | 0.429321E+11 | 0.963059E+10 | 0.773514E+09 | 0.486998E+11 | ||||
Minimum of Months | 0.835938E+09 | 0.328152E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.507392E+09 |
Maximum of Months | 0.946926E+09 | 0.370550E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.312964E+09 | 0.943602E+10 |
Report: SpaceGainsMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.918158E+09 | 0.362278E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.943122E+10 |
February | 0.835938E+09 | 0.328152E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.685967E+10 |
March | 0.946926E+09 | 0.370550E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.599148E+10 |
April | 0.901896E+09 | 0.351592E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5150389.17 | 0.342795E+10 |
May | 0.932542E+09 | 0.366414E+10 | 0.821897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 93112707.50 | 0.143745E+10 |
June | 0.914724E+09 | 0.357797E+10 | 0.802482E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.222969E+09 | 0.735155E+09 |
July | 0.919713E+09 | 0.360209E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.313068E+09 | 0.500130E+09 |
August | 0.946926E+09 | 0.370550E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133455E+09 | 0.777665E+09 |
September | 0.901896E+09 | 0.351592E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6463898.74 | 0.176482E+10 |
October | 0.918158E+09 | 0.362278E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.326190E+10 |
November | 0.884402E+09 | 0.351592E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.523050E+10 |
December | 0.919713E+09 | 0.360209E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.912840E+10 |
Annual Sum or Average | 0.109410E+11 | 0.429321E+11 | 0.963059E+10 | 0.774220E+09 | 0.485463E+11 | ||||
Minimum of Months | 0.835938E+09 | 0.328152E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.500130E+09 |
Maximum of Months | 0.946926E+09 | 0.370550E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.313068E+09 | 0.943122E+10 |
Report: SpaceGainsMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.918158E+09 | 0.362278E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114646E+11 |
February | 0.835938E+09 | 0.328152E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.859639E+10 |
March | 0.946926E+09 | 0.370550E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.719657E+10 |
April | 0.901896E+09 | 0.351592E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7898701.86 | 0.430274E+10 |
May | 0.932542E+09 | 0.366414E+10 | 0.821897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 96976621.18 | 0.178398E+10 |
June | 0.914724E+09 | 0.357797E+10 | 0.802482E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.240482E+09 | 0.923758E+09 |
July | 0.919713E+09 | 0.360209E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.328467E+09 | 0.667813E+09 |
August | 0.946926E+09 | 0.370550E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139619E+09 | 0.105129E+10 |
September | 0.901896E+09 | 0.351592E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6666450.35 | 0.223856E+10 |
October | 0.918158E+09 | 0.362278E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.396497E+10 |
November | 0.884402E+09 | 0.351592E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.652321E+10 |
December | 0.919713E+09 | 0.360209E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112308E+11 |
Annual Sum or Average | 0.109410E+11 | 0.429321E+11 | 0.963059E+10 | 0.820109E+09 | 0.599447E+11 | ||||
Minimum of Months | 0.835938E+09 | 0.328152E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.667813E+09 |
Maximum of Months | 0.946926E+09 | 0.370550E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.328467E+09 | 0.114646E+11 |
Report: PeakSpaceGainsMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2159.72 | 01-JAN-13:09 | 9537.57 | 01-JAN-10:09 | 1348.26 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 29650.73 | 04-JAN-12:10 |
February | 2159.72 | 03-FEB-13:09 | 9537.57 | 01-FEB-10:09 | 1348.26 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 24227.00 | 13-FEB-12:10 |
March | 2159.72 | 03-MAR-13:09 | 9537.57 | 01-MAR-10:09 | 1348.26 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 19891.01 | 15-MAR-11:10 |
April | 2159.72 | 01-APR-12:09 | 9537.57 | 01-APR-09:09 | 1348.26 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1378.32 | 23-APR-16:00 | 13878.53 | 04-APR-17:00 |
May | 2159.72 | 05-MAY-12:09 | 9537.57 | 01-MAY-09:09 | 1348.26 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2372.82 | 25-MAY-17:00 | 7122.11 | 01-MAY-11:10 |
June | 2159.72 | 02-JUN-12:09 | 9537.57 | 01-JUN-09:09 | 1348.26 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5141.32 | 29-JUN-16:00 | 5353.85 | 09-JUN-11:05 |
July | 2159.72 | 01-JUL-12:09 | 9537.57 | 01-JUL-09:09 | 1348.26 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3436.46 | 15-JUL-15:00 | 5049.66 | 08-JUL-11:05 |
August | 2159.72 | 04-AUG-12:09 | 9537.57 | 01-AUG-09:09 | 1348.26 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3198.40 | 08-AUG-16:00 | 6169.96 | 17-AUG-14:00 |
September | 2159.72 | 01-SEP-12:09 | 9537.57 | 01-SEP-09:09 | 1348.26 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1015.50 | 01-SEP-15:00 | 7095.19 | 27-SEP-11:05 |
October | 2159.72 | 01-OCT-12:09 | 9537.57 | 01-OCT-09:09 | 1348.26 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 | 11545.37 | 31-OCT-17:00 |
November | 2159.72 | 03-NOV-12:09 | 9537.57 | 01-NOV-09:09 | 1348.26 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 19541.93 | 25-NOV-12:10 |
December | 2159.72 | 01-DEC-13:09 | 9537.57 | 01-DEC-10:09 | 1348.26 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 28376.27 | 24-DEC-12:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2159.72 | 9537.57 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5049.66 | |||||
Maximum of Months | 2159.72 | 9537.57 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 5141.32 | 29650.73 |
Report: PeakSpaceGainsMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1079.86 | 01-JAN-13:09 | 4768.79 | 01-JAN-10:09 | 674.13 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 16165.69 | 04-JAN-12:10 |
February | 1079.86 | 03-FEB-13:09 | 4768.79 | 01-FEB-10:09 | 674.13 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 13587.84 | 01-FEB-18:00 |
March | 1079.86 | 03-MAR-13:09 | 4768.79 | 01-MAR-10:09 | 674.13 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 11080.80 | 15-MAR-11:10 |
April | 1079.86 | 01-APR-12:09 | 4768.79 | 01-APR-09:09 | 674.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 741.48 | 23-APR-16:00 | 7581.97 | 04-APR-11:10 |
May | 1079.86 | 05-MAY-12:09 | 4768.79 | 01-MAY-09:09 | 674.13 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1340.67 | 25-MAY-17:00 | 4027.25 | 08-MAY-11:05 |
June | 1079.86 | 02-JUN-12:09 | 4768.79 | 01-JUN-09:09 | 674.13 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2831.08 | 29-JUN-16:00 | 3077.16 | 09-JUN-11:05 |
July | 1079.86 | 01-JUL-12:09 | 4768.79 | 01-JUL-09:09 | 674.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1871.86 | 15-JUL-15:00 | 2839.82 | 08-JUL-11:05 |
August | 1079.86 | 04-AUG-12:09 | 4768.79 | 01-AUG-09:09 | 674.13 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1756.58 | 08-AUG-16:00 | 3391.30 | 17-AUG-14:00 |
September | 1079.86 | 01-SEP-12:09 | 4768.79 | 01-SEP-09:09 | 674.13 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 568.63 | 01-SEP-15:00 | 4055.70 | 27-SEP-11:05 |
October | 1079.86 | 01-OCT-12:09 | 4768.79 | 01-OCT-09:09 | 674.13 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 | 6354.09 | 29-OCT-17:00 |
November | 1079.86 | 03-NOV-12:09 | 4768.79 | 01-NOV-09:09 | 674.13 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 10932.58 | 25-NOV-17:00 |
December | 1079.86 | 01-DEC-13:09 | 4768.79 | 01-DEC-10:09 | 674.13 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 15663.79 | 24-DEC-12:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1079.86 | 4768.79 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2839.82 | |||||
Maximum of Months | 1079.86 | 4768.79 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 2831.08 | 16165.69 |
Report: PeakSpaceGainsMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1079.86 | 07-JAN-13:09 | 3744.57 | 01-JAN-10:09 | 674.13 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 16165.63 | 04-JAN-12:10 |
February | 1079.86 | 04-FEB-13:09 | 3744.57 | 01-FEB-09:09 | 674.13 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 13587.84 | 01-FEB-18:00 |
March | 1079.86 | 04-MAR-13:09 | 3744.57 | 01-MAR-09:09 | 674.13 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 11080.78 | 15-MAR-11:10 |
April | 1079.86 | 01-APR-12:09 | 3744.57 | 01-APR-08:09 | 674.13 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 741.45 | 23-APR-16:00 | 7581.94 | 04-APR-11:10 |
May | 1079.86 | 06-MAY-12:09 | 3744.57 | 01-MAY-08:09 | 674.13 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1340.64 | 25-MAY-17:00 | 4004.72 | 01-MAY-11:10 |
June | 1079.86 | 03-JUN-12:09 | 3744.57 | 01-JUN-08:09 | 674.13 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2831.01 | 29-JUN-16:00 | 3010.54 | 09-JUN-11:05 |
July | 1079.86 | 01-JUL-12:09 | 3744.57 | 01-JUL-08:09 | 674.13 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1871.78 | 15-JUL-15:00 | 2830.27 | 08-JUL-11:05 |
August | 1079.86 | 05-AUG-12:09 | 3744.57 | 01-AUG-08:09 | 674.13 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1756.51 | 08-AUG-16:00 | 3295.92 | 17-AUG-12:00 |
September | 1079.86 | 02-SEP-12:09 | 3744.57 | 01-SEP-08:09 | 674.13 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 568.60 | 01-SEP-15:00 | 3888.52 | 27-SEP-11:05 |
October | 1079.86 | 07-OCT-12:09 | 3744.57 | 01-OCT-09:09 | 674.13 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 | 6354.10 | 29-OCT-17:00 |
November | 1079.86 | 04-NOV-12:09 | 3744.57 | 01-NOV-08:09 | 674.13 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 10932.57 | 25-NOV-17:00 |
December | 1079.86 | 02-DEC-13:09 | 3744.57 | 01-DEC-09:09 | 674.13 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 15663.75 | 24-DEC-12:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1079.86 | 3744.57 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2830.27 | |||||
Maximum of Months | 1079.86 | 3744.57 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 2831.01 | 16165.63 |
Report: PeakSpaceGainsMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1079.86 | 07-JAN-13:09 | 3744.57 | 01-JAN-10:09 | 674.13 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 16165.63 | 04-JAN-12:10 |
February | 1079.86 | 04-FEB-13:09 | 3744.57 | 01-FEB-09:09 | 674.13 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 13587.84 | 01-FEB-18:00 |
March | 1079.86 | 04-MAR-13:09 | 3744.57 | 01-MAR-09:09 | 674.13 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 11080.78 | 15-MAR-11:10 |
April | 1079.86 | 01-APR-12:09 | 3744.57 | 01-APR-08:09 | 674.13 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 741.44 | 23-APR-16:00 | 7581.94 | 04-APR-11:10 |
May | 1079.86 | 06-MAY-12:09 | 3744.57 | 01-MAY-08:09 | 674.13 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1340.64 | 25-MAY-17:00 | 4004.72 | 01-MAY-11:10 |
June | 1079.86 | 03-JUN-12:09 | 3744.57 | 01-JUN-08:09 | 674.13 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2831.00 | 29-JUN-16:00 | 2990.35 | 09-JUN-11:05 |
July | 1079.86 | 01-JUL-12:09 | 3744.57 | 01-JUL-08:09 | 674.13 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1871.77 | 15-JUL-15:00 | 2827.52 | 08-JUL-11:05 |
August | 1079.86 | 05-AUG-12:09 | 3744.57 | 01-AUG-08:09 | 674.13 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1756.50 | 08-AUG-16:00 | 3280.46 | 17-AUG-12:00 |
September | 1079.86 | 02-SEP-12:09 | 3744.57 | 01-SEP-08:09 | 674.13 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 568.59 | 01-SEP-15:00 | 3851.11 | 27-SEP-11:05 |
October | 1079.86 | 07-OCT-12:09 | 3744.57 | 01-OCT-09:09 | 674.13 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 | 6354.10 | 29-OCT-17:00 |
November | 1079.86 | 04-NOV-12:09 | 3744.57 | 01-NOV-08:09 | 674.13 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 10932.57 | 25-NOV-17:00 |
December | 1079.86 | 02-DEC-13:09 | 3744.57 | 01-DEC-09:09 | 674.13 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 15663.75 | 24-DEC-12:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1079.86 | 3744.57 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2827.52 | |||||
Maximum of Months | 1079.86 | 3744.57 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 2831.00 | 16165.63 |
Report: PeakSpaceGainsMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1079.86 | 07-JAN-13:09 | 3744.57 | 01-JAN-10:09 | 674.13 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 16165.63 | 04-JAN-12:10 |
February | 1079.86 | 04-FEB-13:09 | 3744.57 | 01-FEB-09:09 | 674.13 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 13587.84 | 01-FEB-18:00 |
March | 1079.86 | 04-MAR-13:09 | 3744.57 | 01-MAR-09:09 | 674.13 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 11080.78 | 15-MAR-11:10 |
April | 1079.86 | 01-APR-12:09 | 3744.57 | 01-APR-08:09 | 674.13 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 741.44 | 23-APR-16:00 | 7581.94 | 04-APR-11:10 |
May | 1079.86 | 06-MAY-12:09 | 3744.57 | 01-MAY-08:09 | 674.13 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1340.63 | 25-MAY-17:00 | 4004.72 | 01-MAY-11:10 |
June | 1079.86 | 03-JUN-12:09 | 3744.57 | 01-JUN-08:09 | 674.13 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2830.99 | 29-JUN-16:00 | 2950.69 | 09-JUN-11:05 |
July | 1079.86 | 01-JUL-12:09 | 3744.57 | 01-JUL-08:09 | 674.13 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1871.75 | 15-JUL-15:00 | 2821.44 | 08-JUL-11:05 |
August | 1079.86 | 05-AUG-12:09 | 3744.57 | 01-AUG-08:09 | 674.13 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1756.49 | 08-AUG-16:00 | 3254.40 | 17-AUG-12:00 |
September | 1079.86 | 02-SEP-12:09 | 3744.57 | 01-SEP-08:09 | 674.13 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 568.59 | 01-SEP-15:00 | 3843.65 | 27-SEP-11:05 |
October | 1079.86 | 07-OCT-12:09 | 3744.57 | 01-OCT-09:09 | 674.13 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 | 6354.10 | 29-OCT-17:00 |
November | 1079.86 | 04-NOV-12:09 | 3744.57 | 01-NOV-08:09 | 674.13 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 10932.57 | 25-NOV-17:00 |
December | 1079.86 | 02-DEC-13:09 | 3744.57 | 01-DEC-09:09 | 674.13 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 15663.75 | 24-DEC-12:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1079.86 | 3744.57 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2821.44 | |||||
Maximum of Months | 1079.86 | 3744.57 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 2830.99 | 16165.63 |
Report: PeakSpaceGainsMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2879.63 | 07-JAN-15:09 | 6064.13 | 01-JAN-11:09 | 1348.26 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 28478.39 | 04-JAN-12:10 |
February | 2879.63 | 04-FEB-15:09 | 6064.13 | 01-FEB-10:09 | 1348.26 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 23771.48 | 01-FEB-18:00 |
March | 2879.63 | 04-MAR-15:09 | 6064.13 | 01-MAR-10:09 | 1348.26 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 19458.23 | 15-MAR-11:10 |
April | 2879.63 | 01-APR-14:09 | 6064.13 | 01-APR-09:09 | 1348.26 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1308.81 | 23-APR-16:00 | 13325.66 | 04-APR-11:10 |
May | 2879.63 | 06-MAY-14:09 | 6064.13 | 01-MAY-09:09 | 1348.26 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2349.33 | 25-MAY-17:00 | 7022.80 | 01-MAY-11:10 |
June | 2879.63 | 03-JUN-14:09 | 6064.13 | 01-JUN-09:09 | 1348.26 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4979.85 | 29-JUN-16:00 | 4993.10 | 09-JUN-11:05 |
July | 2879.63 | 01-JUL-14:09 | 6064.13 | 01-JUL-09:09 | 1348.26 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3297.88 | 15-JUL-15:00 | 4790.15 | 08-JUL-11:05 |
August | 2879.63 | 05-AUG-14:09 | 6064.13 | 01-AUG-09:09 | 1348.26 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3090.95 | 08-AUG-16:00 | 5553.82 | 17-AUG-14:00 |
September | 2879.63 | 02-SEP-14:09 | 6064.13 | 01-SEP-09:09 | 1348.26 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 997.77 | 01-SEP-15:00 | 6740.88 | 27-SEP-11:10 |
October | 2879.63 | 07-OCT-14:09 | 6064.13 | 01-OCT-10:09 | 1348.26 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 | 11158.01 | 31-OCT-17:00 |
November | 2879.63 | 04-NOV-14:09 | 6064.13 | 01-NOV-09:09 | 1348.26 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 19159.88 | 25-NOV-17:00 |
December | 2879.63 | 02-DEC-15:09 | 6064.13 | 01-DEC-10:09 | 1348.26 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 27543.33 | 24-DEC-12:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2879.63 | 6064.13 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4790.15 | |||||
Maximum of Months | 2879.63 | 6064.13 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 4979.85 | 28478.39 |
Report: PeakSpaceGainsMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1439.81 | 07-JAN-15:09 | 3032.07 | 01-JAN-11:09 | 674.13 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 16165.62 | 04-JAN-12:10 |
February | 1439.81 | 04-FEB-15:09 | 3032.07 | 01-FEB-10:09 | 674.13 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 13587.83 | 01-FEB-18:00 |
March | 1439.81 | 04-MAR-15:09 | 3032.07 | 01-MAR-10:09 | 674.13 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 11080.77 | 15-MAR-11:10 |
April | 1439.81 | 01-APR-14:09 | 3032.07 | 01-APR-09:09 | 674.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 741.44 | 23-APR-16:00 | 7581.93 | 04-APR-11:10 |
May | 1439.81 | 06-MAY-14:09 | 3032.07 | 01-MAY-09:09 | 674.13 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1340.63 | 25-MAY-17:00 | 4004.71 | 01-MAY-11:10 |
June | 1439.81 | 03-JUN-14:09 | 3032.07 | 01-JUN-09:09 | 674.13 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2831.00 | 29-JUN-16:00 | 2848.19 | 09-JUN-11:05 |
July | 1439.81 | 01-JUL-14:09 | 3032.07 | 01-JUL-09:09 | 674.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1871.77 | 15-JUL-15:00 | 2743.05 | 08-JUL-11:05 |
August | 1439.81 | 05-AUG-14:09 | 3032.07 | 01-AUG-09:09 | 674.13 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1756.49 | 08-AUG-16:00 | 3165.92 | 17-AUG-12:00 |
September | 1439.81 | 02-SEP-14:09 | 3032.07 | 01-SEP-09:09 | 674.13 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 568.61 | 01-SEP-15:00 | 3839.24 | 27-SEP-11:10 |
October | 1439.81 | 07-OCT-14:09 | 3032.07 | 01-OCT-10:09 | 674.13 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 | 6354.09 | 29-OCT-17:00 |
November | 1439.81 | 04-NOV-14:09 | 3032.07 | 01-NOV-09:09 | 674.13 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 10932.55 | 25-NOV-17:00 |
December | 1439.81 | 02-DEC-15:09 | 3032.07 | 01-DEC-10:09 | 674.13 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 15663.76 | 24-DEC-12:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1439.81 | 3032.07 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2743.05 | |||||
Maximum of Months | 1439.81 | 3032.07 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 2831.00 | 16165.62 |
Report: PeakSpaceGainsMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1439.81 | 07-JAN-15:09 | 3032.07 | 01-JAN-11:09 | 674.13 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 16165.62 | 04-JAN-12:10 |
February | 1439.81 | 04-FEB-15:09 | 3032.07 | 01-FEB-10:09 | 674.13 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 13587.83 | 01-FEB-18:00 |
March | 1439.81 | 04-MAR-15:09 | 3032.07 | 01-MAR-10:09 | 674.13 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 11080.77 | 15-MAR-11:10 |
April | 1439.81 | 01-APR-14:09 | 3032.07 | 01-APR-09:09 | 674.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 741.44 | 23-APR-16:00 | 7581.93 | 04-APR-11:10 |
May | 1439.81 | 06-MAY-14:09 | 3032.07 | 01-MAY-09:09 | 674.13 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1340.62 | 25-MAY-17:00 | 4004.71 | 01-MAY-11:10 |
June | 1439.81 | 03-JUN-14:09 | 3032.07 | 01-JUN-09:09 | 674.13 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2831.00 | 29-JUN-16:00 | 2826.86 | 09-JUN-11:05 |
July | 1439.81 | 01-JUL-14:09 | 3032.07 | 01-JUL-09:09 | 674.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1871.76 | 15-JUL-15:00 | 2727.28 | 08-JUL-11:05 |
August | 1439.81 | 05-AUG-14:09 | 3032.07 | 01-AUG-09:09 | 674.13 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1756.48 | 08-AUG-16:00 | 3150.80 | 17-AUG-12:00 |
September | 1439.81 | 02-SEP-14:09 | 3032.07 | 01-SEP-09:09 | 674.13 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 568.61 | 01-SEP-15:00 | 3839.24 | 27-SEP-11:10 |
October | 1439.81 | 07-OCT-14:09 | 3032.07 | 01-OCT-10:09 | 674.13 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 | 6354.09 | 29-OCT-17:00 |
November | 1439.81 | 04-NOV-14:09 | 3032.07 | 01-NOV-09:09 | 674.13 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 10932.55 | 25-NOV-17:00 |
December | 1439.81 | 02-DEC-15:09 | 3032.07 | 01-DEC-10:09 | 674.13 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 15663.76 | 24-DEC-12:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1439.81 | 3032.07 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2727.28 | |||||
Maximum of Months | 1439.81 | 3032.07 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 2831.00 | 16165.62 |
Report: PeakSpaceGainsMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1439.81 | 07-JAN-15:09 | 3032.07 | 01-JAN-11:09 | 674.13 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 16165.62 | 04-JAN-12:10 |
February | 1439.81 | 04-FEB-15:09 | 3032.07 | 01-FEB-10:09 | 674.13 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 13587.83 | 01-FEB-18:00 |
March | 1439.81 | 04-MAR-15:09 | 3032.07 | 01-MAR-10:09 | 674.13 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 11080.77 | 15-MAR-11:10 |
April | 1439.81 | 01-APR-14:09 | 3032.07 | 01-APR-09:09 | 674.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 741.43 | 23-APR-16:00 | 7581.93 | 04-APR-11:10 |
May | 1439.81 | 06-MAY-14:09 | 3032.07 | 01-MAY-09:09 | 674.13 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1340.61 | 25-MAY-17:00 | 4004.71 | 01-MAY-11:10 |
June | 1439.81 | 03-JUN-14:09 | 3032.07 | 01-JUN-09:09 | 674.13 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2830.98 | 29-JUN-16:00 | 2755.93 | 09-JUN-11:05 |
July | 1439.81 | 01-JUL-14:09 | 3032.07 | 01-JUL-09:09 | 674.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1871.74 | 15-JUL-15:00 | 2674.96 | 08-JUL-11:05 |
August | 1439.81 | 05-AUG-14:09 | 3032.07 | 01-AUG-09:09 | 674.13 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1756.47 | 08-AUG-16:00 | 3104.26 | 17-AUG-12:00 |
September | 1439.81 | 02-SEP-14:09 | 3032.07 | 01-SEP-09:09 | 674.13 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 568.61 | 01-SEP-15:00 | 3839.24 | 27-SEP-11:10 |
October | 1439.81 | 07-OCT-14:09 | 3032.07 | 01-OCT-10:09 | 674.13 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 | 6354.09 | 29-OCT-17:00 |
November | 1439.81 | 04-NOV-14:09 | 3032.07 | 01-NOV-09:09 | 674.13 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 10932.55 | 25-NOV-17:00 |
December | 1439.81 | 02-DEC-15:09 | 3032.07 | 01-DEC-10:09 | 674.13 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 15663.76 | 24-DEC-12:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1439.81 | 3032.07 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2674.96 | |||||
Maximum of Months | 1439.81 | 3032.07 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 2830.98 | 16165.62 |
Report: PeakSpaceGainsMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1439.81 | 07-JAN-15:09 | 3032.07 | 01-JAN-11:09 | 674.13 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 17336.39 | 04-JAN-12:10 |
February | 1439.81 | 04-FEB-15:09 | 3032.07 | 01-FEB-10:09 | 674.13 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 14079.44 | 13-FEB-12:10 |
March | 1439.81 | 04-MAR-15:09 | 3032.07 | 01-MAR-10:09 | 674.13 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 11512.95 | 15-MAR-11:10 |
April | 1439.81 | 01-APR-14:09 | 3032.07 | 01-APR-09:09 | 674.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 810.78 | 23-APR-16:00 | 8118.09 | 04-APR-17:00 |
May | 1439.81 | 06-MAY-14:09 | 3032.07 | 01-MAY-09:09 | 674.13 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1363.98 | 25-MAY-17:00 | 4103.87 | 01-MAY-11:10 |
June | 1439.81 | 03-JUN-14:09 | 3032.07 | 01-JUN-09:09 | 674.13 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2992.10 | 29-JUN-16:00 | 2670.00 | 09-JUN-11:05 |
July | 1439.81 | 01-JUL-14:09 | 3032.07 | 01-JUL-09:09 | 674.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2009.97 | 15-JUL-15:00 | 2574.41 | 08-JUL-11:05 |
August | 1439.81 | 05-AUG-14:09 | 3032.07 | 01-AUG-09:09 | 674.13 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1863.59 | 08-AUG-16:00 | 3279.24 | 17-AUG-14:00 |
September | 1439.81 | 02-SEP-14:09 | 3032.07 | 01-SEP-09:09 | 674.13 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 586.29 | 01-SEP-15:00 | 3983.08 | 27-SEP-11:10 |
October | 1439.81 | 07-OCT-14:09 | 3032.07 | 01-OCT-10:09 | 674.13 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 | 6727.54 | 31-OCT-17:00 |
November | 1439.81 | 04-NOV-14:09 | 3032.07 | 01-NOV-09:09 | 674.13 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 11327.48 | 25-NOV-12:10 |
December | 1439.81 | 02-DEC-15:09 | 3032.07 | 01-DEC-10:09 | 674.13 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 16495.60 | 24-DEC-12:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1439.81 | 3032.07 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2574.41 | |||||
Maximum of Months | 1439.81 | 3032.07 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 2992.10 | 17336.39 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 28552.53 | 06-JAN-00:01 | 1799.77 | 50197.74 | 7490.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 613.81 |
February | 23686.73 | 25-FEB-00:01 | 1619.79 | 45177.96 | 6741.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 747.60 |
March | 21525.11 | 23-MAR-07:04 | 1799.77 | 5019.77 | 749.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2979.11 |
April | 17371.39 | 05-APR-07:04 | 1799.77 | 5019.77 | 749.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2469.60 |
May | 13610.37 | 25-MAY-16:40 | 1799.77 | 9537.57 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 2364.53 | 0.00 |
June | 30392.70 | 29-JUN-07:02 | 899.88 | 2509.89 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 21.71 | 0.00 |
July | 31029.34 | 14-JUL-07:03 | 0.00 | 2007.91 | 299.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 306.86 |
August | 32387.28 | 09-AUG-07:03 | 719.91 | 2007.91 | 299.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 391.17 |
September | 28245.58 | 01-SEP-07:03 | 0.00 | 2007.91 | 299.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 602.10 |
October | 16926.94 | 30-OCT-07:03 | 1799.77 | 5019.77 | 749.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2787.23 |
November | 18175.80 | 25-NOV-00:01 | 1259.84 | 35138.42 | 5243.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1297.08 |
December | 23351.35 | 02-DEC-00:01 | 1619.79 | 45177.96 | 6741.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 872.32 |
Annual Sum or Average | |||||||||||
Minimum of Months | 13610.37 | 0.00 | 2007.91 | 299.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 32387.28 | 1799.77 | 50197.74 | 7490.31 | 0.00 | 0.00 | 0.00 | 0.00 | 2364.53 | 2979.11 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 9269.02 | 27-JAN-08:04 | 0.00 | 2509.89 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2070.28 |
February | 11898.52 | 10-FEB-08:04 | 0.00 | 2509.89 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2086.30 |
March | 11080.46 | 07-MAR-08:04 | 899.88 | 2509.89 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1762.83 |
April | 9019.92 | 05-APR-07:03 | 899.88 | 2509.89 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1394.69 |
May | 10219.83 | 26-MAY-07:03 | 0.00 | 752.97 | 112.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 168.51 |
June | 17457.32 | 28-JUN-07:03 | 359.95 | 1003.95 | 149.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.32 |
July | 18766.94 | 24-JUL-07:03 | 359.95 | 1003.95 | 149.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 136.90 |
August | 18722.08 | 10-AUG-07:03 | 359.95 | 1003.95 | 149.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 335.51 |
September | 17177.69 | 01-SEP-07:03 | 0.00 | 1003.95 | 149.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 316.92 |
October | 6419.81 | 30-OCT-07:02 | 899.88 | 2509.89 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1414.93 |
November | 8682.44 | 23-NOV-08:03 | 899.88 | 2509.89 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1661.85 |
December | 9589.10 | 16-DEC-08:04 | 0.00 | 2509.89 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1753.17 |
Annual Sum or Average | |||||||||||
Minimum of Months | 6419.81 | 0.00 | 752.97 | 112.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.32 | |
Maximum of Months | 18766.94 | 899.88 | 2509.89 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2086.30 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 11096.59 | 21-JAN-07:04 | 0.00 | 1970.82 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 134.46 |
February | 10173.74 | 04-FEB-07:04 | 0.00 | 1970.82 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 171.59 |
March | 9743.06 | 11-MAR-07:04 | 0.00 | 1970.82 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 160.11 |
April | 7329.44 | 07-APR-06:03 | 0.00 | 1773.74 | 337.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 138.36 |
May | 9022.03 | 26-MAY-06:03 | 0.00 | 591.25 | 112.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.89 |
June | 16026.49 | 29-JUN-06:03 | 0.00 | 788.33 | 149.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.37 |
July | 16535.66 | 24-JUL-06:03 | 0.00 | 788.33 | 149.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.22 |
August | 18185.33 | 10-AUG-06:03 | 0.00 | 788.33 | 149.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 |
September | 16514.94 | 01-SEP-06:03 | 0.00 | 788.33 | 149.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.05 |
October | 6440.32 | 06-OCT-06:04 | 0.00 | 985.41 | 187.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.33 |
November | 10754.70 | 29-NOV-07:04 | 0.00 | 1970.82 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 164.98 |
December | 11457.03 | 01-DEC-07:04 | 0.00 | 1970.82 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 432.67 |
Annual Sum or Average | |||||||||||
Minimum of Months | 6440.32 | 0.00 | 591.25 | 112.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | |
Maximum of Months | 18185.33 | 0.00 | 1970.82 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 432.67 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 11952.56 | 21-JAN-07:04 | 0.00 | 1970.82 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 134.73 |
February | 10515.68 | 27-FEB-07:05 | 0.00 | 1970.82 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 255.12 |
March | 9986.89 | 11-MAR-07:04 | 0.00 | 1970.82 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 160.76 |
April | 7927.71 | 04-APR-06:04 | 0.00 | 1970.82 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 221.12 |
May | 8380.61 | 26-MAY-06:03 | 0.00 | 591.25 | 112.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.84 |
June | 16026.85 | 29-JUN-06:03 | 0.00 | 788.33 | 149.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.12 |
July | 16590.30 | 24-JUL-06:03 | 0.00 | 788.33 | 149.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.30 |
August | 18146.32 | 10-AUG-06:03 | 0.00 | 788.33 | 149.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.49 |
September | 16293.43 | 01-SEP-06:03 | 0.00 | 788.33 | 149.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.94 |
October | 8205.03 | 30-OCT-06:04 | 0.00 | 1576.66 | 299.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 141.89 |
November | 11005.94 | 29-NOV-07:04 | 0.00 | 1970.82 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 165.50 |
December | 11548.01 | 08-DEC-07:04 | 0.00 | 1970.82 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 183.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 7927.71 | 0.00 | 591.25 | 112.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.49 | |
Maximum of Months | 18146.32 | 0.00 | 1970.82 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 255.12 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 11699.74 | 23-JAN-07:05 | 0.00 | 1970.82 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 225.17 |
February | 11007.19 | 27-FEB-07:05 | 0.00 | 1970.82 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 255.26 |
March | 11367.27 | 18-MAR-06:04 | 0.00 | 1970.82 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 8848.18 | 05-APR-06:04 | 0.00 | 1970.82 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6869.84 | 26-MAY-06:03 | 0.00 | 591.25 | 112.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.73 |
June | 15968.38 | 29-JUN-06:03 | 0.00 | 788.33 | 149.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.18 |
July | 16588.24 | 24-JUL-06:03 | 0.00 | 788.33 | 149.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.73 |
August | 16572.34 | 09-AUG-06:03 | 0.00 | 788.33 | 149.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.91 |
September | 14711.78 | 01-SEP-06:03 | 0.00 | 788.33 | 149.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.89 |
October | 8387.41 | 30-OCT-06:04 | 0.00 | 1576.66 | 299.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 142.39 |
November | 8351.23 | 24-NOV-07:04 | 0.00 | 1970.82 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 140.95 |
December | 10236.14 | 29-DEC-07:04 | 0.00 | 1970.82 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 140.43 |
Annual Sum or Average | |||||||||||
Minimum of Months | 6869.84 | 0.00 | 591.25 | 112.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16588.24 | 0.00 | 1970.82 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 255.26 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 20298.63 | 24-JAN-08:05 | 0.00 | 3191.65 | 749.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2938.35 |
February | 19552.45 | 04-FEB-08:05 | 0.00 | 3191.65 | 749.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3021.23 |
March | 20009.92 | 14-MAR-07:05 | 0.00 | 3191.65 | 749.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3340.63 |
April | 17909.82 | 05-APR-07:04 | 0.00 | 3191.65 | 749.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2424.01 |
May | 12393.53 | 01-MAY-07:03 | 0.00 | 3191.65 | 749.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1640.37 |
June | 30467.00 | 29-JUN-07:02 | 0.00 | 1595.82 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 27.50 | 0.00 |
July | 30308.73 | 24-JUL-07:03 | 0.00 | 1276.66 | 299.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 260.60 |
August | 28666.22 | 09-AUG-07:03 | 0.00 | 1276.66 | 299.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 343.09 |
September | 22673.48 | 01-SEP-07:03 | 0.00 | 1276.66 | 299.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 557.36 |
October | 12637.74 | 25-OCT-07:03 | 0.00 | 1914.99 | 449.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1739.11 |
November | 17325.07 | 23-NOV-09:04 | 0.00 | 3191.65 | 749.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2691.78 |
December | 19200.93 | 08-DEC-08:05 | 0.00 | 3191.65 | 749.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3515.40 |
Annual Sum or Average | |||||||||||
Minimum of Months | 12393.53 | 0.00 | 1276.66 | 299.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 30467.00 | 0.00 | 3191.65 | 749.03 | 0.00 | 0.00 | 0.00 | 0.00 | 27.50 | 3515.40 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 9228.75 | 24-JAN-08:05 | 0.00 | 1595.82 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1662.69 |
February | 10041.66 | 11-FEB-08:04 | 0.00 | 1595.82 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1564.17 |
March | 9826.38 | 14-MAR-07:05 | 0.00 | 1595.82 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1866.08 |
April | 8836.38 | 05-APR-07:04 | 0.00 | 1595.82 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1390.24 |
May | 6192.98 | 01-MAY-07:03 | 0.00 | 1595.82 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 941.28 |
June | 16565.14 | 29-JUN-07:02 | 0.00 | 797.91 | 187.26 | 0.00 | 0.00 | 0.00 | 0.00 | 23.16 | 0.00 |
July | 16364.56 | 24-JUL-07:03 | 0.00 | 638.33 | 149.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 140.12 |
August | 13364.55 | 09-AUG-07:03 | 0.00 | 638.33 | 149.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 191.92 |
September | 10463.26 | 01-SEP-07:03 | 0.00 | 638.33 | 149.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 314.55 |
October | 6146.21 | 25-OCT-07:03 | 0.00 | 957.49 | 224.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 994.14 |
November | 9101.44 | 25-NOV-08:05 | 0.00 | 1595.82 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1911.13 |
December | 7030.75 | 03-DEC-09:05 | 0.00 | 1595.82 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1731.59 |
Annual Sum or Average | |||||||||||
Minimum of Months | 6146.21 | 0.00 | 638.33 | 149.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16565.14 | 0.00 | 1595.82 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 23.16 | 1911.13 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 8742.34 | 31-JAN-08:05 | 0.00 | 1595.82 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1933.98 |
February | 9048.72 | 19-FEB-09:05 | 0.00 | 1595.82 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2146.44 |
March | 9838.93 | 14-MAR-07:05 | 0.00 | 1595.82 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1866.09 |
April | 8910.60 | 05-APR-07:04 | 0.00 | 1595.82 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1392.08 |
May | 6157.26 | 01-MAY-07:03 | 0.00 | 1595.82 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 936.09 |
June | 16500.48 | 29-JUN-07:02 | 0.00 | 797.91 | 187.26 | 0.00 | 0.00 | 0.00 | 0.00 | 26.02 | 0.00 |
July | 16306.85 | 24-JUL-07:03 | 0.00 | 638.33 | 149.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 137.34 |
August | 12658.48 | 09-AUG-07:03 | 0.00 | 638.33 | 149.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 191.66 |
September | 9803.08 | 01-SEP-07:03 | 0.00 | 638.33 | 149.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 314.32 |
October | 6194.97 | 25-OCT-07:03 | 0.00 | 957.49 | 224.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 995.21 |
November | 9632.14 | 25-NOV-08:05 | 0.00 | 1595.82 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1911.11 |
December | 7461.59 | 07-DEC-08:04 | 0.00 | 1595.82 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1338.69 |
Annual Sum or Average | |||||||||||
Minimum of Months | 6157.26 | 0.00 | 638.33 | 149.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16500.48 | 0.00 | 1595.82 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 26.02 | 2146.44 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 9754.70 | 31-JAN-08:05 | 0.00 | 1595.82 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1933.97 |
February | 8979.41 | 15-FEB-08:05 | 0.00 | 1595.82 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2081.17 |
March | 10294.07 | 16-MAR-07:15 | 0.00 | 638.33 | 149.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2037.70 |
April | 6816.81 | 06-APR-07:04 | 0.00 | 1595.82 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1178.77 |
May | 5367.88 | 25-MAY-16:10 | 1277.83 | 3032.07 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1325.03 | 0.00 |
June | 14592.56 | 29-JUN-07:02 | 0.00 | 797.91 | 187.26 | 0.00 | 0.00 | 0.00 | 0.00 | 32.52 | 0.00 |
July | 14546.53 | 24-JUL-07:03 | 0.00 | 638.33 | 149.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 133.41 |
August | 10519.38 | 09-AUG-07:03 | 0.00 | 638.33 | 149.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 190.87 |
September | 7682.51 | 01-SEP-07:03 | 0.00 | 638.33 | 149.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 313.59 |
October | 7817.28 | 30-OCT-07:04 | 0.00 | 1595.82 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1416.69 |
November | 7774.06 | 13-NOV-08:04 | 0.00 | 1595.82 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1402.94 |
December | 8992.95 | 01-DEC-08:05 | 0.00 | 1595.82 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2244.80 |
Annual Sum or Average | |||||||||||
Minimum of Months | 5367.88 | 0.00 | 638.33 | 149.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14592.56 | 1277.83 | 3032.07 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1325.03 | 2244.80 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6896.57 | 30-JAN-08:04 | 0.00 | 1595.82 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1495.97 |
February | 7283.80 | 08-FEB-08:04 | 0.00 | 1595.82 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1356.94 |
March | 8950.63 | 18-MAR-07:05 | 0.00 | 1595.82 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1832.09 |
April | 7017.36 | 06-APR-07:04 | 0.00 | 1595.82 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1352.13 |
May | 6050.42 | 01-MAY-07:04 | 0.00 | 1595.82 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 973.14 |
June | 12548.70 | 30-JUN-07:02 | 0.00 | 957.49 | 224.71 | 0.00 | 0.00 | 0.00 | 0.00 | 99.97 | 0.00 |
July | 13209.57 | 23-JUL-08:62 | 0.00 | 797.91 | 187.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.89 |
August | 7175.69 | 08-AUG-15:00 | 1241.83 | 3032.07 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1851.39 | 0.00 |
September | 6298.56 | 01-SEP-14:20 | 1241.83 | 3032.07 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 500.54 | 0.00 |
October | 6930.56 | 25-OCT-07:03 | 0.00 | 957.49 | 224.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1006.56 |
November | 7866.32 | 25-NOV-08:05 | 0.00 | 1595.82 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2256.13 |
December | 6969.24 | 30-DEC-08:04 | 0.00 | 1595.82 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1497.69 |
Annual Sum or Average | |||||||||||
Minimum of Months | 6050.42 | 0.00 | 797.91 | 187.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13209.57 | 1241.83 | 3032.07 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1851.39 | 2256.13 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | |
January | 0.121325E+12 | 92323.22 | 06-JAN-18:19 | 0.392046E+12 | 510403.87 | 09-JAN-08:09 |
February | 0.108209E+12 | 89736.31 | 23-FEB-18:10 | 0.269757E+12 | 481124.02 | 14-FEB-08:09 |
March | 0.118932E+12 | 88078.74 | 02-MAR-18:40 | 0.230519E+12 | 428271.89 | 15-MAR-07:10 |
April | 0.112222E+12 | 97539.87 | 23-APR-15:50 | 0.912281E+11 | 306424.57 | 05-APR-07:10 |
May | 0.124084E+12 | 121405.93 | 25-MAY-16:19 | 0.991912E+10 | 194388.13 | 01-MAY-07:10 |
June | 0.134011E+12 | 148388.75 | 29-JUN-15:50 | 0.246683E+09 | 20290.16 | 03-JUN-07:10 |
July | 0.148647E+12 | 143620.07 | 15-JUL-14:09 | 3799488.20 | 2370.61 | 09-JUL-08:09 |
August | 0.144408E+12 | 137919.45 | 08-AUG-14:00 | 23157496.73 | 5463.22 | 19-AUG-07:30 |
September | 0.120562E+12 | 117324.27 | 01-SEP-13:50 | 0.445893E+10 | 70724.65 | 23-SEP-07:10 |
October | 0.119226E+12 | 93500.74 | 19-OCT-17:40 | 0.624183E+11 | 262081.92 | 30-OCT-07:10 |
November | 0.116476E+12 | 90493.63 | 02-NOV-17:10 | 0.165431E+12 | 386768.90 | 25-NOV-08:09 |
December | 0.121430E+12 | 92060.81 | 26-DEC-16:19 | 0.360872E+12 | 469330.58 | 20-DEC-08:09 |
Annual Sum or Average | 0.148953E+13 | 0.158692E+13 | ||||
Minimum of Months | 0.108209E+12 | 88078.74 | 3799488.20 | 2370.61 | ||
Maximum of Months | 0.148647E+12 | 148388.75 | 0.392046E+12 | 510403.87 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.599295E+11 | 0.182777E+11 | 0.108804E+11 | 0.00 | 0.263255E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.591203E+10 | 0.00 |
February | 0.542583E+11 | 0.150136E+11 | 0.985143E+10 | 0.00 | 0.237015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.538406E+10 | 0.00 |
March | 0.607812E+11 | 0.145928E+11 | 0.110523E+11 | 0.00 | 0.265136E+11 | 0.00 | 0.00 | 424032.81 | 0.00 | 0.00 | 0.00 | 0.599131E+10 | 0.00 |
April | 0.581548E+11 | 0.120810E+11 | 0.105581E+11 | 0.00 | 0.252387E+11 | 0.00 | 0.00 | 0.499276E+09 | 0.00 | 0.00 | 0.00 | 0.568992E+10 | 0.00 |
May | 0.603309E+11 | 0.106466E+11 | 0.109629E+11 | 0.00 | 0.262942E+11 | 0.00 | 0.00 | 0.100990E+11 | 0.00 | 0.00 | 0.00 | 0.575004E+10 | 0.00 |
June | 0.587570E+11 | 0.930780E+10 | 0.106818E+11 | 0.00 | 0.256779E+11 | 0.00 | 0.00 | 0.241161E+11 | 0.00 | 0.00 | 0.00 | 0.547034E+10 | 0.00 |
July | 0.597776E+11 | 0.100856E+11 | 0.108460E+11 | 0.00 | 0.260897E+11 | 0.00 | 0.00 | 0.363437E+11 | 0.00 | 0.00 | 0.00 | 0.550491E+10 | 0.00 |
August | 0.607324E+11 | 0.116603E+11 | 0.110454E+11 | 0.00 | 0.265881E+11 | 0.00 | 0.00 | 0.288671E+11 | 0.00 | 0.00 | 0.00 | 0.551460E+10 | 0.00 |
September | 0.582036E+11 | 0.132286E+11 | 0.105649E+11 | 0.00 | 0.253405E+11 | 0.00 | 0.00 | 0.788565E+10 | 0.00 | 0.00 | 0.00 | 0.533837E+10 | 0.00 |
October | 0.599295E+11 | 0.157850E+11 | 0.108804E+11 | 0.00 | 0.260169E+11 | 0.00 | 0.00 | 0.101386E+10 | 0.00 | 0.00 | 0.00 | 0.560042E+10 | 0.00 |
November | 0.580572E+11 | 0.171302E+11 | 0.105443E+11 | 0.00 | 0.252114E+11 | 0.00 | 0.00 | 6412122.17 | 0.00 | 0.00 | 0.00 | 0.552606E+10 | 0.00 |
December | 0.598264E+11 | 0.187686E+11 | 0.108529E+11 | 0.00 | 0.261556E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.582638E+10 | 0.00 |
Annual Sum or Average | 0.708738E+12 | 0.166578E+12 | 0.128721E+12 | 0.309154E+12 | 0.00 | 0.108831E+12 | 0.675084E+11 | ||||||
Minimum of Months | 0.542583E+11 | 0.930780E+10 | 0.985143E+10 | 0.00 | 0.237015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.533837E+10 | 0.00 |
Maximum of Months | 0.607812E+11 | 0.187686E+11 | 0.110523E+11 | 0.00 | 0.265881E+11 | 0.00 | 0.00 | 0.363437E+11 | 0.00 | 0.00 | 0.00 | 0.599131E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS [J] | COOLING:GAS [] | WATERSYSTEMS:GAS [] | COGENERATION:GAS [] | HUMIDIFIER:GAS [] | |
January | 0.00 | 0.00 | 0.392046E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.269757E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.230519E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.912281E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.991912E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.246683E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 3799488.20 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 23157496.73 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.445893E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.624183E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.165431E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.360872E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.158692E+13 | ||||||
Minimum of Months | 0.00 | 0.00 | 3799488.20 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.392046E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum}[W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum}[W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum}[W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum}[W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 43732.45 | 01-JAN-11:09 | 10625.34 | 01-JAN-00:10 | 8089.53 | 01-JAN-11:09 | 0.00 | 18035.70 | 01-JAN-09:09 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 43732.45 | 01-FEB-10:09 | 10625.34 | 01-FEB-00:10 | 8089.53 | 01-FEB-10:09 | 0.00 | 18035.70 | 01-FEB-08:09 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 43732.45 | 01-MAR-10:09 | 10625.34 | 01-MAR-00:10 | 8089.53 | 01-MAR-10:09 | 0.00 | 18035.70 | 01-MAR-08:09 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 43732.45 | 01-APR-09:09 | 10625.34 | 01-APR-00:10 | 8089.53 | 01-APR-09:09 | 0.00 | 18035.70 | 01-APR-07:10 | 0.00 | 0.00 | 01-APR-00:10 |
May | 43732.45 | 01-MAY-09:09 | 10625.34 | 01-MAY-00:10 | 8089.53 | 01-MAY-09:09 | 0.00 | 18035.70 | 01-MAY-07:10 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 43732.45 | 01-JUN-09:09 | 10625.34 | 01-JUN-00:10 | 8089.53 | 01-JUN-09:09 | 0.00 | 18035.70 | 01-JUN-07:10 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 43732.45 | 01-JUL-09:09 | 10625.34 | 01-JUL-00:10 | 8089.53 | 01-JUL-09:09 | 0.00 | 18035.70 | 01-JUL-07:10 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 43732.45 | 01-AUG-09:09 | 10625.34 | 01-AUG-00:10 | 8089.53 | 01-AUG-09:09 | 0.00 | 18035.70 | 01-AUG-07:10 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 43732.45 | 01-SEP-09:09 | 10625.34 | 01-SEP-00:10 | 8089.53 | 01-SEP-09:09 | 0.00 | 18035.70 | 01-SEP-07:10 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 43732.45 | 01-OCT-10:09 | 10625.34 | 01-OCT-00:10 | 8089.53 | 01-OCT-10:09 | 0.00 | 18035.70 | 01-OCT-08:09 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 43732.45 | 01-NOV-09:09 | 10625.34 | 01-NOV-00:10 | 8089.53 | 01-NOV-09:09 | 0.00 | 18035.70 | 01-NOV-07:10 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 43732.45 | 01-DEC-10:09 | 10625.34 | 01-DEC-00:10 | 8089.53 | 01-DEC-10:09 | 0.00 | 18035.70 | 01-DEC-08:09 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 43732.45 | 10625.34 | 8089.53 | 0.00 | 18035.70 | 0.00 | 0.00 | |||||
Maximum of Months | 43732.45 | 10625.34 | 8089.53 | 0.00 | 18035.70 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum}[W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum}[W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 11906.57 | 17-JAN-13:30 | 0.00 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 11912.66 | 23-FEB-13:20 | 0.00 |
March | 138.29 | 26-MAR-19:30 | 0.00 | 0.00 | 0.00 | 9772.60 | 15-MAR-12:50 | 0.00 |
April | 23324.89 | 23-APR-15:00 | 0.00 | 0.00 | 0.00 | 9758.96 | 29-APR-12:39 | 0.00 |
May | 43952.03 | 25-MAY-16:10 | 0.00 | 0.00 | 0.00 | 11834.27 | 03-MAY-16:10 | 0.00 |
June | 74485.83 | 29-JUN-16:10 | 0.00 | 0.00 | 0.00 | 7613.25 | 05-JUN-12:30 | 0.00 |
July | 68905.02 | 15-JUL-13:00 | 0.00 | 0.00 | 0.00 | 9280.66 | 30-JUL-12:09 | 0.00 |
August | 61907.98 | 08-AUG-14:00 | 0.00 | 0.00 | 0.00 | 9727.47 | 02-AUG-12:00 | 0.00 |
September | 40443.79 | 01-SEP-14:20 | 0.00 | 0.00 | 0.00 | 9731.60 | 28-SEP-12:50 | 0.00 |
October | 14891.23 | 19-OCT-14:00 | 0.00 | 0.00 | 0.00 | 11828.31 | 26-OCT-14:20 | 0.00 |
November | 722.42 | 01-NOV-20:19 | 0.00 | 0.00 | 0.00 | 11875.44 | 08-NOV-13:50 | 0.00 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 12559.68 | 22-DEC-20:30 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 7613.25 | 0.00 | ||
Maximum of Months | 74485.83 | 0.00 | 0.00 | 0.00 | 12559.68 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 92323.22 | 06-JAN-18:19 | 43732.45 | 8089.53 | 10625.34 | 0.00 | 18035.70 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 89736.31 | 23-FEB-18:10 | 43732.45 | 8089.53 | 10625.34 | 0.00 | 18035.70 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 88078.74 | 02-MAR-18:40 | 43732.45 | 8089.53 | 10625.34 | 0.00 | 18035.70 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 97539.87 | 23-APR-15:50 | 43732.45 | 8089.53 | 0.00 | 0.00 | 18035.70 | 0.00 | 0.00 | 22850.78 | 0.00 |
May | 121405.93 | 25-MAY-16:19 | 43732.45 | 8089.53 | 0.00 | 0.00 | 18035.70 | 0.00 | 0.00 | 43898.63 | 0.00 |
June | 148388.75 | 29-JUN-15:50 | 43732.45 | 8089.53 | 0.00 | 0.00 | 18035.70 | 0.00 | 0.00 | 73735.80 | 0.00 |
July | 143620.07 | 15-JUL-14:09 | 43732.45 | 8089.53 | 0.00 | 0.00 | 18035.70 | 0.00 | 0.00 | 68677.15 | 0.00 |
August | 137919.45 | 08-AUG-14:00 | 43732.45 | 8089.53 | 0.00 | 0.00 | 18035.70 | 0.00 | 0.00 | 61907.98 | 0.00 |
September | 117324.27 | 01-SEP-13:50 | 43732.45 | 8089.53 | 0.00 | 0.00 | 18035.70 | 0.00 | 0.00 | 39869.90 | 0.00 |
October | 93500.74 | 19-OCT-17:40 | 43732.45 | 8089.53 | 10625.34 | 0.00 | 18035.70 | 0.00 | 0.00 | 7564.22 | 0.00 |
November | 90493.63 | 02-NOV-17:10 | 43732.45 | 8089.53 | 10625.34 | 0.00 | 18035.70 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 92060.81 | 26-DEC-16:19 | 43732.45 | 8089.53 | 10625.34 | 0.00 | 18035.70 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 88078.74 | 43732.45 | 8089.53 | 0.00 | 0.00 | 18035.70 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 148388.75 | 43732.45 | 8089.53 | 10625.34 | 0.00 | 18035.70 | 0.00 | 0.00 | 73735.80 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS {Maximum}[W] | HEATING:GAS {TIMESTAMP} | COOLING:GAS [] | WATERSYSTEMS:GAS [] | COGENERATION:GAS [] | |
January | 0.00 | 0.00 | 510403.87 | 09-JAN-08:09 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 481124.02 | 14-FEB-08:09 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 428271.89 | 15-MAR-07:10 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 306424.57 | 05-APR-07:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 194388.13 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 20290.16 | 03-JUN-07:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 2370.61 | 09-JUL-08:09 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 5463.22 | 19-AUG-07:30 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 70724.65 | 23-SEP-07:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 262081.92 | 30-OCT-07:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 386768.90 | 25-NOV-08:09 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 469330.58 | 20-DEC-08:09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||
Minimum of Months | 0.00 | 0.00 | 2370.61 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 510403.87 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 8.50 | 18.98 | 3.00 | 20.11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5.00 | 19.96 | 2.00 | 20.14 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 3.83 | 20.24 | 1.50 | 20.14 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.67 | 20.45 | 0.17 | 20.47 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1.17 | 20.45 | 0.17 | 20.50 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6.83 | 19.63 | 2.50 | 20.06 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 26.00 | 19.63 | 9.33 | 20.12 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 8.50 | 20.45 | 3.00 | 20.50 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 4.67 | 20.27 | 2.00 | 20.24 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 2.83 | 20.38 | 1.17 | 20.34 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 1.33 | 20.43 | 0.67 | 20.40 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.17 | 20.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 3.50 | 20.29 | 1.83 | 20.26 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 12.50 | 20.32 | 5.67 | 20.29 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 4.67 | 20.48 | 2.00 | 20.40 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.50 | 20.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 2.67 | 19.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 1.50 | 20.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.17 | 20.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 2.67 | 20.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 10.50 | 20.15 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3.50 | 20.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 4.50 | 19.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3.00 | 20.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 1.50 | 20.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.33 | 20.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 3.50 | 19.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 12.83 | 19.89 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 4.50 | 20.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 5.33 | 19.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3.17 | 20.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 1.83 | 20.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.50 | 20.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 4.33 | 19.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 15.17 | 19.72 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 5.33 | 20.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 8.67 | 17.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5.33 | 18.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 3.00 | 19.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.50 | 20.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1.17 | 20.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6.33 | 18.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 25.00 | 18.57 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 8.67 | 20.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 8.33 | 17.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4.33 | 19.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 2.50 | 19.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.33 | 20.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1.17 | 20.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6.00 | 18.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 22.67 | 18.71 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 8.33 | 20.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 8.50 | 17.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4.83 | 18.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 2.50 | 19.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.33 | 20.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1.17 | 20.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6.33 | 18.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 23.67 | 18.58 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 8.50 | 20.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 10.17 | 17.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6.33 | 18.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 4.50 | 19.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.83 | 20.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1.50 | 20.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 8.17 | 17.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 31.50 | 18.11 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 10.17 | 20.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 51.50 | 15.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 43.83 | 15.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 28.33 | 15.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6.83 | 17.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.17 | 20.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.17 | 20.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 7.17 | 17.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 46.83 | 15.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 184.83 | 15.46 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 51.50 | 20.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: LGSTORE1
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 496.00 | 21.03 | 492.83 | 21.03 | 492.83 | 21.03 |
February | 448.00 | 21.02 | 370.67 | 21.00 | 370.67 | 21.00 |
March | 496.00 | 21.05 | 355.00 | 21.02 | 355.00 | 21.02 |
April | 467.83 | 21.44 | 129.67 | 21.11 | 125.17 | 21.01 |
May | 275.50 | 22.40 | 121.83 | 23.70 | 8.33 | 21.11 |
June | 102.67 | 23.18 | 319.50 | 23.89 | 30.17 | 23.89 |
July | 37.67 | 23.73 | 463.33 | 23.89 | 29.67 | 23.89 |
August | 16.17 | 22.82 | 444.83 | 23.89 | 0.00 | 0.00 |
September | 159.00 | 22.07 | 198.17 | 23.88 | 0.00 | 0.00 |
October | 431.00 | 21.35 | 32.67 | 22.12 | 19.67 | 20.96 |
November | 479.83 | 21.13 | 166.33 | 21.00 | 166.33 | 21.00 |
December | 496.00 | 21.02 | 478.17 | 21.01 | 478.17 | 21.01 |
Annual Sum or Average | 3905.67 | 21.36 | 3573.00 | 22.27 | 2076.00 | 21.10 |
Minimum of Months | 16.17 | 21.02 | 32.67 | 21.00 | 0.00 | 0.00 |
Maximum of Months | 496.00 | 23.73 | 492.83 | 23.89 | 492.83 | 23.89 |
Report: ComfortReportSimple55Monthly
For: SMSTORE1
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 496.00 | 21.17 | 420.50 | 21.11 | 420.50 | 21.11 |
February | 448.00 | 21.24 | 288.67 | 21.12 | 288.67 | 21.12 |
March | 496.00 | 21.38 | 224.17 | 21.13 | 224.17 | 21.13 |
April | 463.67 | 22.02 | 51.67 | 21.49 | 44.67 | 21.11 |
May | 239.17 | 22.76 | 137.33 | 23.83 | 3.00 | 21.10 |
June | 57.67 | 23.35 | 319.83 | 23.89 | 11.17 | 23.89 |
July | 20.67 | 23.78 | 459.00 | 23.88 | 16.50 | 23.89 |
August | 10.33 | 22.96 | 438.50 | 23.89 | 0.00 | 0.00 |
September | 137.67 | 22.39 | 174.67 | 23.88 | 0.00 | 0.00 |
October | 419.00 | 21.93 | 14.33 | 23.40 | 2.50 | 21.11 |
November | 474.83 | 21.55 | 103.00 | 21.12 | 103.00 | 21.12 |
December | 496.00 | 21.20 | 394.00 | 21.12 | 394.00 | 21.12 |
Annual Sum or Average | 3759.00 | 21.65 | 3025.67 | 22.53 | 1508.17 | 21.17 |
Minimum of Months | 10.33 | 21.17 | 14.33 | 21.11 | 0.00 | 0.00 |
Maximum of Months | 496.00 | 23.78 | 459.00 | 23.89 | 420.50 | 23.89 |
Report: ComfortReportSimple55Monthly
For: SMSTORE2
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 371.00 | 21.11 | 371.00 | 21.11 | 371.00 | 21.11 |
February | 336.00 | 21.11 | 285.00 | 21.11 | 285.00 | 21.11 |
March | 379.00 | 21.11 | 255.17 | 21.11 | 255.17 | 21.11 |
April | 354.83 | 21.51 | 90.50 | 21.16 | 89.67 | 21.11 |
May | 223.83 | 22.37 | 88.33 | 23.94 | 4.50 | 21.11 |
June | 88.83 | 23.32 | 218.67 | 24.06 | 28.33 | 24.17 |
July | 38.33 | 24.26 | 345.33 | 24.06 | 34.00 | 24.39 |
August | 14.67 | 22.93 | 337.67 | 24.03 | 1.17 | 25.43 |
September | 155.17 | 22.06 | 93.33 | 23.99 | 0.00 | 0.00 |
October | 336.50 | 21.34 | 19.00 | 21.99 | 13.17 | 21.11 |
November | 360.00 | 21.16 | 148.50 | 21.11 | 148.50 | 21.11 |
December | 369.00 | 21.11 | 360.50 | 21.11 | 360.50 | 21.11 |
Annual Sum or Average | 3027.17 | 21.44 | 2613.00 | 22.33 | 1591.00 | 21.24 |
Minimum of Months | 14.67 | 21.11 | 19.00 | 21.11 | 0.00 | 0.00 |
Maximum of Months | 379.00 | 24.26 | 371.00 | 24.06 | 371.00 | 25.43 |
Report: ComfortReportSimple55Monthly
For: SMSTORE3
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 371.00 | 21.11 | 371.00 | 21.11 | 371.00 | 21.11 |
February | 336.00 | 21.11 | 301.50 | 21.11 | 301.50 | 21.11 |
March | 379.00 | 21.11 | 273.00 | 21.11 | 273.00 | 21.11 |
April | 355.17 | 21.47 | 105.33 | 21.15 | 104.50 | 21.11 |
May | 233.33 | 22.33 | 82.33 | 23.87 | 6.17 | 21.11 |
June | 99.50 | 23.26 | 207.17 | 24.07 | 32.33 | 24.14 |
July | 40.83 | 24.22 | 343.83 | 24.06 | 35.67 | 24.37 |
August | 16.00 | 22.89 | 333.17 | 24.03 | 1.17 | 25.41 |
September | 167.50 | 22.05 | 85.17 | 23.98 | 0.00 | 0.00 |
October | 340.50 | 21.33 | 24.17 | 21.65 | 19.50 | 21.11 |
November | 360.00 | 21.15 | 173.17 | 21.11 | 173.17 | 21.11 |
December | 369.00 | 21.11 | 367.33 | 21.11 | 367.33 | 21.11 |
Annual Sum or Average | 3067.83 | 21.45 | 2667.17 | 22.27 | 1685.33 | 21.24 |
Minimum of Months | 16.00 | 21.11 | 24.17 | 21.11 | 0.00 | 0.00 |
Maximum of Months | 379.00 | 24.22 | 371.00 | 24.07 | 371.00 | 25.41 |
Report: ComfortReportSimple55Monthly
For: SMSTORE4
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 371.00 | 21.11 | 371.00 | 21.11 | 371.00 | 21.11 |
February | 336.00 | 21.11 | 308.17 | 21.11 | 308.17 | 21.11 |
March | 379.00 | 21.11 | 283.83 | 21.11 | 283.83 | 21.11 |
April | 355.50 | 21.44 | 117.67 | 21.14 | 116.83 | 21.11 |
May | 240.33 | 22.28 | 81.33 | 23.79 | 8.17 | 21.11 |
June | 111.17 | 23.23 | 194.67 | 24.07 | 38.67 | 24.10 |
July | 45.83 | 24.13 | 340.17 | 24.06 | 38.50 | 24.33 |
August | 19.00 | 22.91 | 329.50 | 24.03 | 1.67 | 24.97 |
September | 174.67 | 22.02 | 78.50 | 23.98 | 0.00 | 0.00 |
October | 342.00 | 21.31 | 30.00 | 21.48 | 26.00 | 21.11 |
November | 360.00 | 21.15 | 193.33 | 21.11 | 193.33 | 21.11 |
December | 369.00 | 21.11 | 369.00 | 21.11 | 369.00 | 21.11 |
Annual Sum or Average | 3103.50 | 21.45 | 2697.17 | 22.22 | 1755.17 | 21.25 |
Minimum of Months | 19.00 | 21.11 | 30.00 | 21.11 | 0.00 | 0.00 |
Maximum of Months | 379.00 | 24.13 | 371.00 | 24.07 | 371.00 | 24.97 |
Report: ComfortReportSimple55Monthly
For: LGSTORE2
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.11 | 340.00 | 21.11 | 340.00 | 21.11 |
February | 308.00 | 21.11 | 303.17 | 21.11 | 303.17 | 21.11 |
March | 348.00 | 21.11 | 295.83 | 21.11 | 295.83 | 21.11 |
April | 326.33 | 21.39 | 149.83 | 21.13 | 149.17 | 21.11 |
May | 228.50 | 22.22 | 67.00 | 23.55 | 8.83 | 21.11 |
June | 131.33 | 23.24 | 160.83 | 23.94 | 52.00 | 23.96 |
July | 57.33 | 23.84 | 306.83 | 23.96 | 43.00 | 24.16 |
August | 30.83 | 22.89 | 298.83 | 23.93 | 3.33 | 23.89 |
September | 166.67 | 21.95 | 66.00 | 23.91 | 1.83 | 23.80 |
October | 315.67 | 21.29 | 39.83 | 21.30 | 37.17 | 21.11 |
November | 330.00 | 21.14 | 216.67 | 21.11 | 216.67 | 21.11 |
December | 338.00 | 21.11 | 338.00 | 21.11 | 338.00 | 21.11 |
Annual Sum or Average | 2920.67 | 21.47 | 2582.83 | 22.09 | 1789.00 | 21.27 |
Minimum of Months | 30.83 | 21.11 | 39.83 | 21.11 | 1.83 | 21.11 |
Maximum of Months | 348.00 | 23.84 | 340.00 | 23.96 | 340.00 | 24.16 |
Report: ComfortReportSimple55Monthly
For: SMSTORE5
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.11 | 340.00 | 21.11 | 340.00 | 21.11 |
February | 308.00 | 21.11 | 302.83 | 21.11 | 302.83 | 21.11 |
March | 348.00 | 21.11 | 298.00 | 21.11 | 298.00 | 21.11 |
April | 326.67 | 21.40 | 154.33 | 21.13 | 153.67 | 21.11 |
May | 232.33 | 22.26 | 59.33 | 23.42 | 10.67 | 21.11 |
June | 135.00 | 23.28 | 150.33 | 23.95 | 51.83 | 23.96 |
July | 57.33 | 23.83 | 297.67 | 23.96 | 42.00 | 24.16 |
August | 32.33 | 22.96 | 292.83 | 23.94 | 3.17 | 23.89 |
September | 168.00 | 22.00 | 61.83 | 23.92 | 1.00 | 23.89 |
October | 317.50 | 21.31 | 42.33 | 21.20 | 41.00 | 21.11 |
November | 330.00 | 21.14 | 218.17 | 21.11 | 218.17 | 21.11 |
December | 338.00 | 21.11 | 338.00 | 21.11 | 338.00 | 21.11 |
Annual Sum or Average | 2933.17 | 21.48 | 2555.67 | 22.06 | 1800.33 | 21.27 |
Minimum of Months | 32.33 | 21.11 | 42.33 | 21.11 | 1.00 | 21.11 |
Maximum of Months | 348.00 | 23.83 | 340.00 | 23.96 | 340.00 | 24.16 |
Report: ComfortReportSimple55Monthly
For: SMSTORE6
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.11 | 340.00 | 21.11 | 340.00 | 21.11 |
February | 308.00 | 21.11 | 304.00 | 21.11 | 304.00 | 21.11 |
March | 348.00 | 21.11 | 305.50 | 21.11 | 305.50 | 21.11 |
April | 327.00 | 21.39 | 162.33 | 21.13 | 161.67 | 21.11 |
May | 237.33 | 22.25 | 53.50 | 23.31 | 11.83 | 21.11 |
June | 143.83 | 23.26 | 146.67 | 23.94 | 54.17 | 23.95 |
July | 60.50 | 23.81 | 294.00 | 23.96 | 44.00 | 24.15 |
August | 34.17 | 22.94 | 287.83 | 23.94 | 3.67 | 23.89 |
September | 173.33 | 22.01 | 60.33 | 23.91 | 1.67 | 23.83 |
October | 318.33 | 21.31 | 45.67 | 21.16 | 44.83 | 21.11 |
November | 330.00 | 21.14 | 223.67 | 21.11 | 223.67 | 21.11 |
December | 338.00 | 21.11 | 338.00 | 21.11 | 338.00 | 21.11 |
Annual Sum or Average | 2958.50 | 21.49 | 2561.50 | 22.03 | 1833.00 | 21.27 |
Minimum of Months | 34.17 | 21.11 | 45.67 | 21.11 | 1.67 | 21.11 |
Maximum of Months | 348.00 | 23.81 | 340.00 | 23.96 | 340.00 | 24.15 |
Report: ComfortReportSimple55Monthly
For: SMSTORE7
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.11 | 340.00 | 21.11 | 340.00 | 21.11 |
February | 308.00 | 21.11 | 308.00 | 21.11 | 308.00 | 21.11 |
March | 348.00 | 21.11 | 315.83 | 21.11 | 315.83 | 21.11 |
April | 329.17 | 21.36 | 182.83 | 21.12 | 182.33 | 21.11 |
May | 245.83 | 22.19 | 55.50 | 22.95 | 19.50 | 21.11 |
June | 163.67 | 23.20 | 139.00 | 23.93 | 58.50 | 23.94 |
July | 66.33 | 23.75 | 285.17 | 23.96 | 47.00 | 24.13 |
August | 39.67 | 22.87 | 279.83 | 23.93 | 4.50 | 23.89 |
September | 183.50 | 22.00 | 54.83 | 23.90 | 3.17 | 23.74 |
October | 321.00 | 21.31 | 58.17 | 21.11 | 58.17 | 21.11 |
November | 330.00 | 21.13 | 241.00 | 21.11 | 241.00 | 21.11 |
December | 338.00 | 21.11 | 338.00 | 21.11 | 338.00 | 21.11 |
Annual Sum or Average | 3013.17 | 21.50 | 2598.17 | 21.98 | 1916.00 | 21.28 |
Minimum of Months | 39.67 | 21.11 | 54.83 | 21.11 | 3.17 | 21.11 |
Maximum of Months | 348.00 | 23.75 | 340.00 | 23.96 | 340.00 | 24.13 |
Report: ComfortReportSimple55Monthly
For: SMSTORE8
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.11 | 340.00 | 21.11 | 340.00 | 21.11 |
February | 308.00 | 21.11 | 308.00 | 21.11 | 308.00 | 21.11 |
March | 348.00 | 21.11 | 348.00 | 21.11 | 348.00 | 21.11 |
April | 329.67 | 21.26 | 266.17 | 21.11 | 266.17 | 21.11 |
May | 277.33 | 22.11 | 60.17 | 21.79 | 45.50 | 21.11 |
June | 209.00 | 23.05 | 122.83 | 23.87 | 66.33 | 23.81 |
July | 83.67 | 23.58 | 249.50 | 23.97 | 57.33 | 24.08 |
August | 69.50 | 22.92 | 257.50 | 23.93 | 19.67 | 23.88 |
September | 210.50 | 22.01 | 43.33 | 23.83 | 7.00 | 23.21 |
October | 330.00 | 21.35 | 105.50 | 21.11 | 105.50 | 21.11 |
November | 330.00 | 21.13 | 286.00 | 21.11 | 286.00 | 21.11 |
December | 338.00 | 21.11 | 338.00 | 21.11 | 338.00 | 21.11 |
Annual Sum or Average | 3173.67 | 21.53 | 2725.00 | 21.82 | 2187.50 | 21.30 |
Minimum of Months | 69.50 | 21.11 | 43.33 | 21.11 | 7.00 | 21.11 |
Maximum of Months | 348.00 | 23.58 | 348.00 | 23.97 | 348.00 | 24.08 |
Report: OccupantComfortDataSummaryMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 496.00000 | 21.00039 | 7.15899 | -0.7468 | 17.23773 |
February | 448.00000 | 21.00126 | 9.16848 | -0.6859 | 15.48712 |
March | 496.00000 | 21.02757 | 13.08625 | -0.6298 | 13.86909 |
April | 480.00000 | 21.48995 | 18.20118 | -0.4025 | 9.86502 |
May | 496.00000 | 23.04712 | 30.81385 | -0.8291 | 22.83722 |
June | 480.00000 | 23.72463 | 44.76819 | -0.4517 | 10.43564 |
July | 496.00000 | 23.86819 | 50.16035 | -0.3010 | 7.19415 |
August | 496.00000 | 23.84358 | 48.22731 | -0.3251 | 7.60544 |
September | 480.00000 | 23.25247 | 38.16772 | -0.6403 | 16.20768 |
October | 496.00000 | 21.68035 | 27.81137 | -0.2113 | 7.67137 |
November | 480.00000 | 21.11680 | 17.01101 | -0.5052 | 11.01021 |
December | 496.00000 | 20.99965 | 8.50730 | -0.7201 | 16.38150 |
Annual Sum or Average | 5840.00000 | 22.17815 | 26.19147 | -0.5366 | 12.97503 |
Minimum of Months | 448.00000 | 20.99965 | 7.15899 | -0.8291 | 7.19415 |
Maximum of Months | 496.00000 | 23.86819 | 50.16035 | -0.2113 | 22.83722 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 496.00000 | 21.13479 | 7.97115 | -0.6613 | 14.59057 |
February | 448.00000 | 21.21047 | 10.11117 | -0.5863 | 12.69346 |
March | 496.00000 | 21.35582 | 13.83262 | -0.5071 | 11.04543 |
April | 480.00000 | 22.05687 | 18.52014 | -0.2531 | 7.96241 |
May | 496.00000 | 23.32720 | 30.87795 | -0.7280 | 18.68658 |
June | 480.00000 | 23.81457 | 43.33224 | -0.4257 | 9.44099 |
July | 496.00000 | 23.88410 | 48.21441 | -0.3184 | 7.34843 |
August | 496.00000 | 23.86793 | 46.76728 | -0.3411 | 7.71123 |
September | 480.00000 | 23.43321 | 37.42909 | -0.6038 | 14.56404 |
October | 496.00000 | 22.21458 | 28.08835 | -0.1039 | 6.93817 |
November | 480.00000 | 21.55247 | 17.46772 | -0.3979 | 9.20095 |
December | 496.00000 | 21.17099 | 9.29928 | -0.6317 | 13.77770 |
Annual Sum or Average | 5840.00000 | 22.42527 | 26.08814 | -0.4626 | 11.16030 |
Minimum of Months | 448.00000 | 21.13479 | 7.97115 | -0.7280 | 6.93817 |
Maximum of Months | 496.00000 | 23.88410 | 48.21441 | -0.1039 | 18.68658 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 21.10996 | 6.62772 | -0.7268 | 16.28812 |
February | 336.00000 | 21.10997 | 8.81731 | -0.6606 | 14.40596 |
March | 379.00000 | 21.10986 | 12.83754 | -0.6005 | 12.83309 |
April | 360.00000 | 21.54018 | 17.49872 | -0.3926 | 9.45535 |
May | 375.00000 | 22.99699 | 31.22219 | -0.8617 | 24.25681 |
June | 366.00000 | 23.79737 | 44.75450 | -0.4587 | 10.76347 |
July | 369.00000 | 23.99213 | 50.30732 | -0.3009 | 7.39889 |
August | 379.00000 | 23.93546 | 49.07235 | -0.3372 | 7.91475 |
September | 360.00000 | 23.09005 | 38.27367 | -0.7361 | 19.46540 |
October | 371.00000 | 21.56923 | 28.19024 | -0.2627 | 7.85150 |
November | 360.00000 | 21.15937 | 17.18297 | -0.5163 | 11.03285 |
December | 369.00000 | 21.10989 | 8.24443 | -0.7031 | 15.57457 |
Annual Sum or Average | 4395.00000 | 22.22064 | 26.23479 | -0.5456 | 13.09576 |
Minimum of Months | 336.00000 | 21.10986 | 6.62772 | -0.8617 | 7.39889 |
Maximum of Months | 379.00000 | 23.99213 | 50.30732 | -0.2627 | 24.25681 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 21.10996 | 6.62697 | -0.7414 | 16.73008 |
February | 336.00000 | 21.10997 | 8.81602 | -0.6766 | 14.84861 |
March | 379.00000 | 21.10983 | 12.83746 | -0.6159 | 13.22565 |
April | 360.00000 | 21.50307 | 17.54024 | -0.4155 | 9.76351 |
May | 375.00000 | 22.93178 | 31.35759 | -0.8962 | 25.65231 |
June | 366.00000 | 23.76448 | 44.92256 | -0.4783 | 11.34202 |
July | 369.00000 | 23.98540 | 50.40863 | -0.3075 | 7.50235 |
August | 379.00000 | 23.92518 | 49.19813 | -0.3456 | 8.06992 |
September | 360.00000 | 23.02864 | 38.46917 | -0.7662 | 20.56304 |
October | 371.00000 | 21.53197 | 28.27303 | -0.2848 | 8.05945 |
November | 360.00000 | 21.15200 | 17.20355 | -0.5349 | 11.42763 |
December | 369.00000 | 21.10989 | 8.24353 | -0.7182 | 16.02344 |
Annual Sum or Average | 4395.00000 | 22.19906 | 26.30754 | -0.5643 | 13.59281 |
Minimum of Months | 336.00000 | 21.10983 | 6.62697 | -0.8962 | 7.50235 |
Maximum of Months | 379.00000 | 23.98540 | 50.40863 | -0.2848 | 25.65231 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 21.10996 | 6.62626 | -0.7525 | 17.08487 |
February | 336.00000 | 21.10989 | 8.81498 | -0.6895 | 15.22645 |
March | 379.00000 | 21.10998 | 12.83658 | -0.6289 | 13.57766 |
April | 360.00000 | 21.47085 | 17.57735 | -0.4342 | 10.03222 |
May | 375.00000 | 22.87223 | 31.49529 | -0.9257 | 26.85341 |
June | 366.00000 | 23.73042 | 45.13771 | -0.4971 | 11.90592 |
July | 369.00000 | 23.97599 | 50.59361 | -0.3154 | 7.63137 |
August | 379.00000 | 23.91096 | 49.39882 | -0.3551 | 8.25891 |
September | 360.00000 | 22.97570 | 38.65192 | -0.7903 | 21.43953 |
October | 371.00000 | 21.50648 | 28.32966 | -0.2993 | 8.20484 |
November | 360.00000 | 21.14654 | 17.21880 | -0.5491 | 11.74235 |
December | 369.00000 | 21.10996 | 8.24268 | -0.7301 | 16.38857 |
Annual Sum or Average | 4395.00000 | 22.17957 | 26.39379 | -0.5798 | 14.02108 |
Minimum of Months | 336.00000 | 21.10989 | 6.62626 | -0.9257 | 7.63137 |
Maximum of Months | 379.00000 | 23.97599 | 50.59361 | -0.2993 | 26.85341 |
Report: OccupantComfortDataSummaryMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.10992 | 7.17328 | -0.7903 | 18.28984 |
February | 308.00000 | 21.10993 | 9.41843 | -0.7256 | 16.27486 |
March | 348.00000 | 21.10994 | 13.51220 | -0.6630 | 14.49071 |
April | 330.00000 | 21.42231 | 18.11365 | -0.4689 | 10.57818 |
May | 344.00000 | 22.77250 | 32.50059 | -0.9698 | 28.46379 |
June | 336.00000 | 23.62631 | 46.12871 | -0.5349 | 12.79126 |
July | 338.00000 | 23.88900 | 51.45742 | -0.3385 | 7.90882 |
August | 348.00000 | 23.81580 | 50.50774 | -0.3802 | 8.66615 |
September | 330.00000 | 22.88273 | 39.53600 | -0.8239 | 22.61345 |
October | 340.00000 | 21.47372 | 29.02991 | -0.3217 | 8.47554 |
November | 330.00000 | 21.13780 | 17.80183 | -0.5842 | 12.55433 |
December | 338.00000 | 21.10992 | 8.79824 | -0.7688 | 17.59522 |
Annual Sum or Average | 4030.00000 | 22.13211 | 27.15478 | -0.6133 | 14.88273 |
Minimum of Months | 308.00000 | 21.10992 | 7.17328 | -0.9698 | 7.90882 |
Maximum of Months | 348.00000 | 23.88900 | 51.45742 | -0.3217 | 28.46379 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.10993 | 7.12145 | -0.7796 | 17.92969 |
February | 308.00000 | 21.10994 | 9.36588 | -0.7194 | 16.07627 |
March | 348.00000 | 21.10981 | 13.46078 | -0.6602 | 14.39298 |
April | 330.00000 | 21.42723 | 18.05431 | -0.4741 | 10.65765 |
May | 344.00000 | 22.77936 | 32.42962 | -0.9873 | 29.08837 |
June | 336.00000 | 23.63360 | 46.04618 | -0.5552 | 13.21205 |
July | 338.00000 | 23.89142 | 51.40994 | -0.3629 | 8.24842 |
August | 348.00000 | 23.82360 | 50.41689 | -0.4021 | 8.98791 |
September | 330.00000 | 22.90371 | 39.42784 | -0.8391 | 23.05778 |
October | 340.00000 | 21.48139 | 28.95904 | -0.3292 | 8.56316 |
November | 330.00000 | 21.13985 | 17.74074 | -0.5841 | 12.53930 |
December | 338.00000 | 21.10993 | 8.74471 | -0.7592 | 17.27754 |
Annual Sum or Average | 4030.00000 | 22.13711 | 27.08799 | -0.6203 | 14.99581 |
Minimum of Months | 308.00000 | 21.10981 | 7.12145 | -0.9873 | 8.24842 |
Maximum of Months | 348.00000 | 23.89142 | 51.40994 | -0.3292 | 29.08837 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.10993 | 7.12133 | -0.7813 | 17.98460 |
February | 308.00000 | 21.10994 | 9.36574 | -0.7221 | 16.15467 |
March | 348.00000 | 21.10995 | 13.46064 | -0.6642 | 14.50039 |
April | 330.00000 | 21.41269 | 18.07109 | -0.4835 | 10.80992 |
May | 344.00000 | 22.74858 | 32.50696 | -1.0055 | 29.85541 |
June | 336.00000 | 23.61125 | 46.18340 | -0.5695 | 13.66012 |
July | 338.00000 | 23.88689 | 51.51685 | -0.3693 | 8.36696 |
August | 348.00000 | 23.81566 | 50.52642 | -0.4091 | 9.14288 |
September | 330.00000 | 22.88018 | 39.50868 | -0.8515 | 23.51615 |
October | 340.00000 | 21.47360 | 28.97603 | -0.3352 | 8.63201 |
November | 330.00000 | 21.13833 | 17.74483 | -0.5889 | 12.65060 |
December | 338.00000 | 21.10993 | 8.74466 | -0.7611 | 17.33615 |
Annual Sum or Average | 4030.00000 | 22.12766 | 27.13419 | -0.6277 | 15.21170 |
Minimum of Months | 308.00000 | 21.10993 | 7.12133 | -1.0055 | 8.36696 |
Maximum of Months | 348.00000 | 23.88689 | 51.51685 | -0.3352 | 29.85541 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.10993 | 7.11996 | -0.7908 | 18.29924 |
February | 308.00000 | 21.10994 | 9.36348 | -0.7341 | 16.52284 |
March | 348.00000 | 21.10989 | 13.45894 | -0.6809 | 14.96677 |
April | 330.00000 | 21.36909 | 18.12134 | -0.5140 | 11.35727 |
May | 344.00000 | 22.65893 | 32.73542 | -1.0580 | 32.11199 |
June | 336.00000 | 23.54236 | 46.59776 | -0.6092 | 14.97365 |
July | 338.00000 | 23.87175 | 51.81642 | -0.3839 | 8.68185 |
August | 348.00000 | 23.79073 | 50.82055 | -0.4255 | 9.55357 |
September | 330.00000 | 22.81719 | 39.72411 | -0.8821 | 24.68573 |
October | 340.00000 | 21.45421 | 29.01879 | -0.3511 | 8.83664 |
November | 330.00000 | 21.13382 | 17.75718 | -0.6048 | 13.03605 |
December | 338.00000 | 21.10993 | 8.74368 | -0.7707 | 17.64682 |
Annual Sum or Average | 4030.00000 | 22.10011 | 27.26462 | -0.6498 | 15.88614 |
Minimum of Months | 308.00000 | 21.10989 | 7.11996 | -1.0580 | 8.68185 |
Maximum of Months | 348.00000 | 23.87175 | 51.81642 | -0.3511 | 32.11199 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.10995 | 7.06018 | -0.8613 | 20.78424 |
February | 308.00000 | 21.10996 | 9.28770 | -0.8089 | 18.98588 |
March | 348.00000 | 21.10996 | 13.36901 | -0.7699 | 17.70251 |
April | 330.00000 | 21.26078 | 18.19055 | -0.6240 | 13.81472 |
May | 344.00000 | 22.43614 | 33.22635 | -1.2213 | 39.34369 |
June | 336.00000 | 23.35650 | 47.62580 | -0.7322 | 19.18990 |
July | 338.00000 | 23.81707 | 52.59234 | -0.4351 | 9.91810 |
August | 348.00000 | 23.70475 | 51.57518 | -0.4780 | 11.00752 |
September | 330.00000 | 22.67123 | 40.11572 | -0.9621 | 27.95551 |
October | 340.00000 | 21.41960 | 29.01916 | -0.4033 | 9.70811 |
November | 330.00000 | 21.12591 | 17.75388 | -0.6671 | 14.71765 |
December | 338.00000 | 21.10995 | 8.69120 | -0.8355 | 19.86538 |
Annual Sum or Average | 4030.00000 | 22.02921 | 27.53697 | -0.7326 | 18.58461 |
Minimum of Months | 308.00000 | 21.10995 | 7.06018 | -1.2213 | 9.70811 |
Maximum of Months | 348.00000 | 23.81707 | 52.59234 | -0.4033 | 39.34369 |
Report: DXReportMonthly
For: PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 |
April | 0.498571E+09 | 0.159900E+09 | 30.83 | 0.448901E+09 | 49670510.10 | 0.00 | 0.35 | 23-APR-16:10 | 0.00 | 01-APR-00:05 | 14962.87 | 23-APR-16:10 | 13015.64 | 23-APR-16:07 | 1960.76 | 23-APR-16:40 | 4871.18 | 23-APR-16:10 | 0.00 | 01-APR-00:05 |
May | 0.736690E+10 | 0.232985E+10 | 251.56 | 0.648265E+10 | 0.884245E+09 | 0.00 | 0.54 | 25-MAY-16:20 | 0.00 | 01-MAY-00:10 | 24837.98 | 25-MAY-16:10 | 19900.16 | 25-MAY-16:40 | 5996.79 | 26-MAY-12:10 | 7922.69 | 25-MAY-16:20 | 0.00 | 01-MAY-00:10 |
June | 0.175005E+11 | 0.539774E+10 | 399.56 | 0.131699E+11 | 0.433056E+10 | 0.00 | 1.00 | 29-JUN-07:02 | 0.00 | 01-JUN-00:10 | 59223.29 | 30-JUN-07:02 | 36136.47 | 29-JUN-07:02 | 28650.93 | 30-JUN-07:03 | 14544.26 | 30-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.268271E+11 | 0.814781E+10 | 471.07 | 0.192123E+11 | 0.761488E+10 | 0.00 | 1.00 | 04-JUL-07:02 | 0.00 | 01-JUL-00:05 | 57974.49 | 04-JUL-07:02 | 34900.44 | 22-JUL-07:03 | 25445.43 | 04-JUL-07:02 | 14025.20 | 04-JUL-07:02 | 0.00 | 01-JUL-00:05 |
August | 0.217807E+11 | 0.659455E+10 | 454.72 | 0.160794E+11 | 0.570127E+10 | 0.00 | 1.00 | 09-AUG-07:03 | 0.00 | 01-AUG-00:10 | 56373.91 | 09-AUG-07:03 | 35811.16 | 09-AUG-07:03 | 20562.74 | 09-AUG-07:03 | 13636.61 | 09-AUG-07:03 | 0.00 | 01-AUG-00:10 |
September | 0.684794E+10 | 0.211608E+10 | 274.69 | 0.577452E+10 | 0.107342E+10 | 0.00 | 0.86 | 01-SEP-07:03 | 0.00 | 01-SEP-00:10 | 45925.48 | 01-SEP-07:03 | 29249.55 | 01-SEP-07:03 | 16675.93 | 01-SEP-07:03 | 11668.42 | 01-SEP-07:03 | 0.00 | 01-SEP-00:10 |
October | 0.868483E+09 | 0.271881E+09 | 55.50 | 0.823348E+09 | 45135576.66 | 0.00 | 0.25 | 22-OCT-14:00 | 0.00 | 01-OCT-00:05 | 10296.97 | 22-OCT-14:00 | 9524.63 | 19-OCT-15:00 | 1298.63 | 22-OCT-13:00 | 3157.11 | 19-OCT-15:00 | 0.00 | 01-OCT-00:05 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 |
Annual Sum or Average | 0.816902E+11 | 0.250178E+11 | 1937.93 | 0.619910E+11 | 0.196992E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.268271E+11 | 0.814781E+10 | 471.07 | 0.192123E+11 | 0.761488E+10 | 0.00 | 1.00 | 0.00 | 59223.29 | 36136.47 | 28650.93 | 14544.26 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 |
March | 1287838.74 | 424032.81 | 2.83 | 1287838.74 | 0.00 | 0.00 | 0.02 | 26-MAR-19:30 | 0.00 | 01-MAR-00:05 | 421.42 | 26-MAR-19:30 | 421.42 | 26-MAR-19:30 | 0.00 | 01-MAR-00:05 | 138.29 | 26-MAR-19:30 | 0.00 | 01-MAR-00:05 |
April | 0.473743E+09 | 0.147248E+09 | 81.83 | 0.450430E+09 | 23312895.38 | 0.00 | 0.38 | 23-APR-16:10 | 0.00 | 01-APR-00:05 | 8416.17 | 23-APR-16:10 | 7371.24 | 23-APR-16:07 | 1049.41 | 23-APR-16:20 | 2563.78 | 23-APR-16:10 | 0.00 | 01-APR-00:05 |
May | 0.486588E+10 | 0.146821E+10 | 321.22 | 0.439777E+10 | 0.468102E+09 | 0.00 | 0.61 | 26-MAY-07:03 | 0.00 | 01-MAY-00:10 | 15030.52 | 26-MAY-07:03 | 11893.53 | 26-MAY-07:03 | 3233.98 | 26-MAY-12:10 | 3965.01 | 25-MAY-16:10 | 0.00 | 01-MAY-00:10 |
June | 0.100427E+11 | 0.295621E+10 | 428.73 | 0.785872E+10 | 0.218401E+10 | 0.00 | 1.00 | 25-JUN-07:03 | 0.00 | 01-JUN-00:10 | 30022.21 | 30-JUN-07:02 | 20529.55 | 28-JUN-07:03 | 12485.23 | 30-JUN-07:03 | 7066.88 | 30-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.142850E+11 | 0.414836E+10 | 482.41 | 0.106313E+11 | 0.365366E+10 | 0.00 | 1.00 | 04-JUL-07:02 | 0.00 | 01-JUL-00:05 | 29255.88 | 04-JUL-07:02 | 21254.22 | 24-JUL-07:03 | 10291.22 | 05-JUL-07:03 | 6763.70 | 04-JUL-07:02 | 0.00 | 01-JUL-00:05 |
August | 0.118552E+11 | 0.343082E+10 | 472.64 | 0.903960E+10 | 0.281558E+10 | 0.00 | 1.00 | 09-AUG-07:03 | 0.00 | 01-AUG-00:10 | 28711.96 | 09-AUG-07:03 | 20186.16 | 09-AUG-07:03 | 8525.80 | 09-AUG-07:03 | 6579.76 | 09-AUG-07:03 | 0.00 | 01-AUG-00:10 |
September | 0.460027E+10 | 0.137192E+10 | 332.64 | 0.402630E+10 | 0.573961E+09 | 0.00 | 0.92 | 01-SEP-07:03 | 0.00 | 01-SEP-00:10 | 25165.49 | 01-SEP-07:03 | 18103.20 | 01-SEP-07:03 | 7062.29 | 01-SEP-07:03 | 5954.64 | 01-SEP-07:03 | 0.00 | 01-SEP-00:10 |
October | 0.873596E+09 | 0.267508E+09 | 124.00 | 0.842184E+09 | 31411972.68 | 0.00 | 0.26 | 19-OCT-15:00 | 0.00 | 01-OCT-00:05 | 5661.09 | 22-OCT-14:00 | 5334.87 | 19-OCT-15:00 | 692.83 | 22-OCT-13:00 | 1650.58 | 19-OCT-15:00 | 0.00 | 01-OCT-00:05 |
November | 19700756.82 | 6412122.17 | 11.17 | 17417582.14 | 2283174.68 | 0.00 | 0.12 | 01-NOV-20:20 | 0.00 | 01-NOV-00:10 | 2242.80 | 01-NOV-20:20 | 1923.72 | 01-NOV-20:20 | 319.08 | 01-NOV-20:20 | 722.42 | 01-NOV-20:20 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 |
Annual Sum or Average | 0.470174E+11 | 0.137971E+11 | 2257.47 | 0.372651E+11 | 0.975232E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.142850E+11 | 0.414836E+10 | 482.41 | 0.106313E+11 | 0.365366E+10 | 0.00 | 1.00 | 0.00 | 30022.21 | 21254.22 | 12485.23 | 7066.88 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 |
April | 0.118792E+09 | 36120720.81 | 19.33 | 0.108506E+09 | 10286120.52 | 0.00 | 0.31 | 23-APR-16:00 | 0.00 | 01-APR-00:05 | 6805.88 | 23-APR-16:00 | 5934.92 | 23-APR-16:00 | 870.96 | 23-APR-16:00 | 2118.42 | 23-APR-16:00 | 0.00 | 01-APR-00:05 |
May | 0.280609E+10 | 0.843335E+09 | 164.14 | 0.244590E+10 | 0.360191E+09 | 0.00 | 0.55 | 26-MAY-06:03 | 0.00 | 01-MAY-00:10 | 13862.30 | 26-MAY-06:03 | 10367.07 | 26-MAY-06:03 | 3495.23 | 26-MAY-06:03 | 3766.87 | 25-MAY-16:10 | 0.00 | 01-MAY-00:10 |
June | 0.678878E+10 | 0.198808E+10 | 286.83 | 0.511535E+10 | 0.167342E+10 | 0.00 | 1.00 | 25-JUN-07:03 | 0.00 | 01-JUN-00:10 | 31220.07 | 30-JUN-06:02 | 19032.09 | 29-JUN-06:03 | 14910.43 | 30-JUN-06:03 | 7261.98 | 30-JUN-06:02 | 0.00 | 01-JUN-00:10 |
July | 0.100509E+11 | 0.290212E+10 | 338.12 | 0.720813E+10 | 0.284273E+10 | 0.00 | 1.00 | 04-JUL-07:02 | 0.00 | 01-JUL-00:05 | 30931.77 | 04-JUL-07:02 | 18371.21 | 21-JUL-06:03 | 14759.67 | 04-JUL-07:02 | 6986.80 | 04-JUL-07:02 | 0.00 | 01-JUL-00:05 |
August | 0.802506E+10 | 0.230779E+10 | 330.35 | 0.586376E+10 | 0.216130E+10 | 0.00 | 1.00 | 09-AUG-06:03 | 0.00 | 01-AUG-00:10 | 29884.42 | 09-AUG-06:03 | 18851.35 | 10-AUG-06:03 | 11564.06 | 09-AUG-06:03 | 6795.72 | 09-AUG-06:03 | 0.00 | 01-AUG-00:10 |
September | 0.211902E+10 | 0.620519E+09 | 165.57 | 0.180882E+10 | 0.310200E+09 | 0.00 | 1.00 | 01-SEP-06:03 | 0.00 | 01-SEP-00:10 | 29843.13 | 01-SEP-06:03 | 17386.32 | 01-SEP-06:03 | 12456.82 | 01-SEP-06:03 | 6790.48 | 01-SEP-06:03 | 0.00 | 01-SEP-00:10 |
October | 0.260000E+09 | 77112343.17 | 27.50 | 0.246043E+09 | 13957353.68 | 0.00 | 0.21 | 19-OCT-15:00 | 0.00 | 01-OCT-00:05 | 4462.66 | 19-OCT-15:00 | 4194.00 | 19-OCT-15:00 | 524.51 | 22-OCT-13:20 | 1326.11 | 19-OCT-15:00 | 0.00 | 01-OCT-00:05 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 |
Annual Sum or Average | 0.301686E+11 | 0.877508E+10 | 1331.84 | 0.227965E+11 | 0.737209E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.100509E+11 | 0.290212E+10 | 338.12 | 0.720813E+10 | 0.284273E+10 | 0.00 | 1.00 | 0.00 | 31220.07 | 19032.09 | 14910.43 | 7261.98 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 |
April | 97569557.95 | 29801928.10 | 13.50 | 88066799.78 | 9502758.17 | 0.00 | 0.29 | 23-APR-16:00 | 0.00 | 01-APR-00:05 | 6462.30 | 23-APR-16:00 | 5624.23 | 23-APR-16:00 | 838.06 | 23-APR-16:00 | 2019.48 | 23-APR-16:00 | 0.00 | 01-APR-00:05 |
May | 0.268019E+10 | 0.807360E+09 | 159.06 | 0.232917E+10 | 0.351020E+09 | 0.00 | 0.52 | 26-MAY-06:03 | 0.00 | 01-MAY-00:10 | 12936.03 | 26-MAY-06:03 | 9777.97 | 25-MAY-16:10 | 3285.56 | 26-MAY-06:03 | 3730.77 | 25-MAY-16:10 | 0.00 | 01-MAY-00:10 |
June | 0.660784E+10 | 0.193776E+10 | 282.67 | 0.496292E+10 | 0.164492E+10 | 0.00 | 1.00 | 25-JUN-07:03 | 0.00 | 01-JUN-00:10 | 31311.86 | 30-JUN-06:02 | 19055.19 | 29-JUN-06:03 | 14972.38 | 30-JUN-06:03 | 7283.60 | 30-JUN-06:02 | 0.00 | 01-JUN-00:10 |
July | 0.992582E+10 | 0.286938E+10 | 335.37 | 0.710774E+10 | 0.281808E+10 | 0.00 | 1.00 | 04-JUL-07:02 | 0.00 | 01-JUL-00:05 | 31022.41 | 04-JUL-07:02 | 18390.25 | 21-JUL-06:03 | 14842.71 | 04-JUL-07:02 | 7007.53 | 04-JUL-07:02 | 0.00 | 01-JUL-00:05 |
August | 0.787693E+10 | 0.226805E+10 | 325.68 | 0.574593E+10 | 0.213100E+10 | 0.00 | 1.00 | 09-AUG-06:03 | 0.00 | 01-AUG-00:10 | 29970.81 | 09-AUG-06:03 | 18828.52 | 10-AUG-06:03 | 11630.97 | 09-AUG-06:03 | 6815.63 | 09-AUG-06:03 | 0.00 | 01-AUG-00:10 |
September | 0.199549E+10 | 0.585136E+09 | 159.15 | 0.170220E+10 | 0.293293E+09 | 0.00 | 0.99 | 01-SEP-06:03 | 0.00 | 01-SEP-00:10 | 29531.36 | 01-SEP-06:03 | 17162.28 | 01-SEP-06:03 | 12369.09 | 01-SEP-06:03 | 6742.19 | 01-SEP-06:03 | 0.00 | 01-SEP-00:10 |
October | 0.231715E+09 | 68905038.56 | 26.17 | 0.219276E+09 | 12439130.31 | 0.00 | 0.19 | 19-OCT-15:00 | 0.00 | 01-OCT-00:05 | 4166.73 | 19-OCT-15:00 | 3911.45 | 19-OCT-15:00 | 489.06 | 22-OCT-13:20 | 1242.65 | 19-OCT-15:00 | 0.00 | 01-OCT-00:05 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 |
Annual Sum or Average | 0.294156E+11 | 0.856640E+10 | 1301.59 | 0.221553E+11 | 0.726026E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.992582E+10 | 0.286938E+10 | 335.37 | 0.710774E+10 | 0.281808E+10 | 0.00 | 1.00 | 0.00 | 31311.86 | 19055.19 | 14972.38 | 7283.60 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 |
April | 84549489.75 | 25941615.68 | 11.00 | 75638770.66 | 8910719.09 | 0.00 | 0.28 | 23-APR-16:00 | 0.00 | 01-APR-00:05 | 6197.94 | 23-APR-16:00 | 5384.91 | 23-APR-16:00 | 813.03 | 23-APR-16:00 | 1943.35 | 23-APR-16:00 | 0.00 | 01-APR-00:05 |
May | 0.254600E+10 | 0.769148E+09 | 153.97 | 0.220680E+10 | 0.339196E+09 | 0.00 | 0.50 | 25-MAY-16:10 | 0.00 | 01-MAY-00:10 | 12142.42 | 25-MAY-16:10 | 9634.95 | 25-MAY-16:10 | 2964.50 | 26-MAY-12:10 | 3690.40 | 25-MAY-16:10 | 0.00 | 01-MAY-00:10 |
June | 0.638460E+10 | 0.187627E+10 | 275.94 | 0.477924E+10 | 0.160536E+10 | 0.00 | 1.00 | 25-JUN-07:03 | 0.00 | 01-JUN-00:10 | 31491.43 | 30-JUN-06:02 | 19055.10 | 29-JUN-06:03 | 15179.95 | 30-JUN-06:03 | 7330.16 | 30-JUN-06:02 | 0.00 | 01-JUN-00:10 |
July | 0.971187E+10 | 0.281357E+10 | 332.42 | 0.693853E+10 | 0.277334E+10 | 0.00 | 1.00 | 04-JUL-07:02 | 0.00 | 01-JUL-00:05 | 31205.37 | 04-JUL-07:02 | 18254.52 | 24-JUL-06:03 | 15052.75 | 04-JUL-07:02 | 7051.49 | 04-JUL-07:02 | 0.00 | 01-JUL-00:05 |
August | 0.765593E+10 | 0.220874E+10 | 319.61 | 0.557279E+10 | 0.208313E+10 | 0.00 | 1.00 | 09-AUG-06:03 | 0.00 | 01-AUG-00:10 | 30147.99 | 09-AUG-06:03 | 18354.83 | 09-AUG-06:03 | 11793.16 | 09-AUG-06:03 | 6857.35 | 09-AUG-06:03 | 0.00 | 01-AUG-00:10 |
September | 0.187376E+10 | 0.550328E+09 | 151.65 | 0.159810E+10 | 0.275659E+09 | 0.00 | 0.91 | 01-SEP-06:03 | 0.00 | 01-SEP-00:10 | 26727.67 | 01-SEP-06:03 | 15444.15 | 01-SEP-06:03 | 11283.52 | 01-SEP-06:03 | 6258.52 | 01-SEP-06:03 | 0.00 | 01-SEP-00:10 |
October | 0.209464E+09 | 62425124.70 | 25.17 | 0.198236E+09 | 11228068.17 | 0.00 | 0.18 | 19-OCT-15:00 | 0.00 | 01-OCT-00:05 | 3932.10 | 19-OCT-15:00 | 3687.32 | 19-OCT-15:00 | 462.73 | 22-OCT-13:30 | 1176.24 | 19-OCT-15:00 | 0.00 | 01-OCT-00:05 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 |
Annual Sum or Average | 0.284662E+11 | 0.830641E+10 | 1269.77 | 0.213693E+11 | 0.709683E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.971187E+10 | 0.281357E+10 | 332.42 | 0.693853E+10 | 0.277334E+10 | 0.00 | 1.00 | 0.00 | 31491.43 | 19055.10 | 15179.95 | 7330.16 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 |
April | 0.120149E+09 | 39393671.51 | 7.67 | 0.104114E+09 | 16035321.75 | 0.00 | 0.26 | 23-APR-16:00 | 0.00 | 01-APR-00:05 | 10684.50 | 23-APR-16:00 | 9136.82 | 23-APR-16:00 | 1550.27 | 23-APR-15:00 | 3569.19 | 23-APR-16:00 | 0.00 | 01-APR-00:05 |
May | 0.434124E+10 | 0.139842E+10 | 149.97 | 0.370512E+10 | 0.636116E+09 | 0.00 | 0.49 | 25-MAY-15:00 | 0.00 | 01-MAY-00:10 | 22156.75 | 25-MAY-15:00 | 17240.60 | 25-MAY-16:10 | 5578.99 | 26-MAY-12:10 | 7125.75 | 25-MAY-16:10 | 0.00 | 01-MAY-00:10 |
June | 0.111570E+11 | 0.348693E+10 | 262.57 | 0.820425E+10 | 0.295279E+10 | 0.00 | 1.00 | 25-JUN-08:62 | 0.00 | 01-JUN-00:10 | 58349.11 | 30-JUN-07:02 | 36105.21 | 29-JUN-07:02 | 27610.09 | 30-JUN-07:03 | 14414.27 | 30-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.172165E+11 | 0.530270E+10 | 323.80 | 0.120985E+11 | 0.511799E+10 | 0.00 | 1.00 | 04-JUL-08:62 | 0.00 | 01-JUL-00:05 | 58063.19 | 23-JUL-08:62 | 34112.97 | 24-JUL-07:03 | 26957.99 | 23-JUL-08:62 | 14145.53 | 30-JUL-08:62 | 0.00 | 01-JUL-00:05 |
August | 0.135075E+11 | 0.414331E+10 | 308.67 | 0.962773E+10 | 0.387975E+10 | 0.00 | 0.93 | 09-AUG-07:03 | 0.00 | 01-AUG-00:10 | 50759.07 | 09-AUG-07:03 | 31632.86 | 09-AUG-07:03 | 19126.21 | 09-AUG-07:03 | 12566.63 | 09-AUG-07:03 | 0.00 | 01-AUG-00:10 |
September | 0.299421E+10 | 0.935604E+09 | 141.50 | 0.251596E+10 | 0.478243E+09 | 0.00 | 0.75 | 01-SEP-07:03 | 0.00 | 01-SEP-00:10 | 38713.63 | 01-SEP-07:03 | 23047.82 | 01-SEP-07:03 | 15665.81 | 01-SEP-07:03 | 10152.50 | 01-SEP-07:03 | 0.00 | 01-SEP-00:10 |
October | 0.303645E+09 | 96313166.53 | 22.00 | 0.285094E+09 | 18551189.29 | 0.00 | 0.17 | 19-OCT-15:00 | 0.00 | 01-OCT-00:05 | 6860.34 | 19-OCT-15:00 | 6309.85 | 19-OCT-15:00 | 800.18 | 22-OCT-13:40 | 2183.10 | 19-OCT-15:00 | 0.00 | 01-OCT-00:05 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 |
Annual Sum or Average | 0.496402E+11 | 0.154027E+11 | 1216.17 | 0.365408E+11 | 0.130995E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.172165E+11 | 0.530270E+10 | 323.80 | 0.120985E+11 | 0.511799E+10 | 0.00 | 1.00 | 0.00 | 58349.11 | 36105.21 | 27610.09 | 14414.27 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 |
April | 62489013.54 | 19365736.47 | 7.83 | 54310275.09 | 8178738.46 | 0.00 | 0.25 | 23-APR-16:00 | 0.00 | 01-APR-00:05 | 5652.59 | 23-APR-16:00 | 4841.19 | 23-APR-16:00 | 811.40 | 23-APR-16:00 | 1784.90 | 23-APR-16:00 | 0.00 | 01-APR-00:05 |
May | 0.229380E+10 | 0.698717E+09 | 149.89 | 0.196318E+10 | 0.330613E+09 | 0.00 | 0.47 | 25-MAY-15:00 | 0.00 | 01-MAY-00:10 | 11678.76 | 25-MAY-15:00 | 9099.76 | 25-MAY-16:10 | 2906.91 | 26-MAY-12:10 | 3561.31 | 25-MAY-16:10 | 0.00 | 01-MAY-00:10 |
June | 0.587865E+10 | 0.174078E+10 | 264.32 | 0.434071E+10 | 0.153794E+10 | 0.00 | 1.00 | 25-JUN-08:62 | 0.00 | 01-JUN-00:10 | 32046.89 | 30-JUN-07:02 | 19914.99 | 29-JUN-07:02 | 15085.85 | 30-JUN-07:02 | 7468.15 | 30-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.905731E+10 | 0.264353E+10 | 325.93 | 0.639673E+10 | 0.266057E+10 | 0.00 | 1.00 | 04-JUL-08:62 | 0.00 | 01-JUL-00:05 | 31910.64 | 23-JUL-08:62 | 18822.13 | 24-JUL-07:03 | 14798.57 | 23-JUL-08:62 | 7328.29 | 30-JUL-08:62 | 0.00 | 01-JUL-00:05 |
August | 0.713665E+10 | 0.207267E+10 | 311.58 | 0.511475E+10 | 0.202190E+10 | 0.00 | 0.83 | 09-AUG-07:03 | 0.00 | 01-AUG-00:10 | 24074.83 | 09-AUG-07:03 | 15120.25 | 09-AUG-07:03 | 8954.58 | 09-AUG-07:03 | 5804.69 | 09-AUG-07:03 | 0.00 | 01-AUG-00:10 |
September | 0.159808E+10 | 0.471938E+09 | 142.67 | 0.134845E+10 | 0.249627E+09 | 0.00 | 0.66 | 01-SEP-07:03 | 0.00 | 01-SEP-00:10 | 18122.40 | 01-SEP-07:03 | 10892.82 | 01-SEP-07:03 | 7229.57 | 01-SEP-07:03 | 4609.19 | 01-SEP-07:03 | 0.00 | 01-SEP-00:10 |
October | 0.163345E+09 | 48900409.12 | 22.00 | 0.153840E+09 | 9504255.82 | 0.00 | 0.17 | 19-OCT-15:00 | 0.00 | 01-OCT-00:05 | 3687.48 | 19-OCT-15:00 | 3402.57 | 19-OCT-15:00 | 410.67 | 22-OCT-13:40 | 1107.49 | 19-OCT-15:00 | 0.00 | 01-OCT-00:05 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 |
Annual Sum or Average | 0.261903E+11 | 0.769590E+10 | 1224.22 | 0.193720E+11 | 0.681834E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.905731E+10 | 0.264353E+10 | 325.93 | 0.639673E+10 | 0.266057E+10 | 0.00 | 1.00 | 0.00 | 32046.89 | 19914.99 | 15085.85 | 7468.15 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 |
April | 58445580.07 | 18154036.57 | 7.50 | 50553909.39 | 7891670.68 | 0.00 | 0.24 | 23-APR-16:00 | 0.00 | 01-APR-00:05 | 5506.60 | 23-APR-16:00 | 4709.27 | 23-APR-16:00 | 797.33 | 23-APR-16:00 | 1741.61 | 23-APR-16:00 | 0.00 | 01-APR-00:05 |
May | 0.221828E+10 | 0.676818E+09 | 146.56 | 0.189503E+10 | 0.323248E+09 | 0.00 | 0.47 | 25-MAY-15:00 | 0.00 | 01-MAY-00:10 | 11538.90 | 25-MAY-15:00 | 8983.18 | 25-MAY-16:10 | 2875.62 | 26-MAY-12:10 | 3525.73 | 25-MAY-16:10 | 0.00 | 01-MAY-00:10 |
June | 0.574561E+10 | 0.170342E+10 | 259.63 | 0.423073E+10 | 0.151488E+10 | 0.00 | 1.00 | 29-JUN-07:02 | 0.00 | 01-JUN-00:10 | 32073.33 | 30-JUN-07:02 | 19862.15 | 29-JUN-07:02 | 15162.86 | 30-JUN-07:02 | 7475.88 | 30-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.892558E+10 | 0.260783E+10 | 324.79 | 0.629101E+10 | 0.263457E+10 | 0.00 | 1.00 | 23-JUL-08:62 | 0.00 | 01-JUL-00:05 | 31936.69 | 23-JUL-08:62 | 18777.42 | 24-JUL-07:03 | 14870.14 | 23-JUL-08:62 | 7291.33 | 23-JUL-08:62 | 0.00 | 01-JUL-00:05 |
August | 0.701425E+10 | 0.203905E+10 | 309.47 | 0.501800E+10 | 0.199625E+10 | 0.00 | 0.80 | 09-AUG-07:03 | 0.00 | 01-AUG-00:10 | 22905.94 | 09-AUG-07:03 | 14340.83 | 09-AUG-07:03 | 8565.11 | 09-AUG-07:03 | 5580.34 | 09-AUG-07:03 | 0.00 | 01-AUG-00:10 |
September | 0.154160E+10 | 0.455621E+09 | 141.00 | 0.129899E+10 | 0.242615E+09 | 0.00 | 0.62 | 01-SEP-07:03 | 0.00 | 01-SEP-00:10 | 16961.70 | 01-SEP-07:03 | 10160.17 | 01-SEP-07:03 | 6801.54 | 01-SEP-07:03 | 4360.85 | 01-SEP-07:03 | 0.00 | 01-SEP-00:10 |
October | 0.155083E+09 | 46469644.86 | 22.00 | 0.145990E+09 | 9093135.21 | 0.00 | 0.16 | 19-OCT-15:00 | 0.00 | 01-OCT-00:05 | 3598.94 | 19-OCT-15:00 | 3317.60 | 19-OCT-15:00 | 397.10 | 22-OCT-13:40 | 1082.03 | 19-OCT-15:00 | 0.00 | 01-OCT-00:05 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 |
Annual Sum or Average | 0.256588E+11 | 0.754737E+10 | 1210.94 | 0.189303E+11 | 0.672854E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.892558E+10 | 0.260783E+10 | 324.79 | 0.629101E+10 | 0.263457E+10 | 0.00 | 1.00 | 0.00 | 32073.33 | 19862.15 | 15162.86 | 7475.88 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 |
April | 47242350.04 | 14783576.53 | 6.17 | 40238811.92 | 7003538.12 | 0.00 | 0.22 | 23-APR-16:00 | 0.00 | 01-APR-00:05 | 5083.18 | 23-APR-16:00 | 4331.99 | 23-APR-16:00 | 751.19 | 23-APR-16:00 | 1615.92 | 23-APR-16:00 | 0.00 | 01-APR-00:05 |
May | 0.201411E+10 | 0.617649E+09 | 139.17 | 0.171334E+10 | 0.300773E+09 | 0.00 | 0.45 | 25-MAY-16:10 | 0.00 | 01-MAY-00:10 | 11160.48 | 25-MAY-15:00 | 8673.69 | 25-MAY-16:10 | 2781.08 | 26-MAY-12:10 | 3432.34 | 25-MAY-16:10 | 0.00 | 01-MAY-00:10 |
June | 0.539568E+10 | 0.160610E+10 | 249.82 | 0.394687E+10 | 0.144881E+10 | 0.00 | 1.00 | 30-JUN-07:02 | 0.00 | 01-JUN-00:10 | 32388.68 | 30-JUN-07:02 | 17855.03 | 29-JUN-07:02 | 15519.80 | 30-JUN-07:02 | 7555.71 | 30-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.860718E+10 | 0.252294E+10 | 321.83 | 0.604080E+10 | 0.256638E+10 | 0.00 | 1.00 | 23-JUL-08:62 | 0.00 | 01-JUL-00:05 | 32251.63 | 23-JUL-08:62 | 17058.06 | 23-JUL-08:62 | 15193.57 | 23-JUL-08:62 | 7368.31 | 23-JUL-08:62 | 0.00 | 01-JUL-00:05 |
August | 0.673014E+10 | 0.196162E+10 | 302.56 | 0.479882E+10 | 0.193132E+10 | 0.00 | 0.69 | 09-AUG-07:03 | 0.00 | 01-AUG-00:10 | 19317.05 | 09-AUG-07:03 | 12000.87 | 09-AUG-07:03 | 7316.18 | 09-AUG-07:03 | 5005.24 | 08-AUG-15:00 | 0.00 | 01-AUG-00:10 |
September | 0.141089E+10 | 0.417819E+09 | 135.58 | 0.118583E+10 | 0.225055E+09 | 0.00 | 0.50 | 01-SEP-07:03 | 0.00 | 01-SEP-00:10 | 13178.44 | 01-SEP-07:03 | 8743.23 | 01-SEP-15:00 | 5352.75 | 01-SEP-07:03 | 3515.25 | 01-SEP-07:03 | 0.00 | 01-SEP-00:10 |
October | 0.136467E+09 | 40993076.75 | 20.67 | 0.128368E+09 | 8099827.80 | 0.00 | 0.15 | 19-OCT-15:00 | 0.00 | 01-OCT-00:05 | 3386.30 | 19-OCT-15:00 | 3115.96 | 19-OCT-15:00 | 360.81 | 22-OCT-13:50 | 1020.98 | 19-OCT-15:00 | 0.00 | 01-OCT-00:05 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 |
Annual Sum or Average | 0.243417E+11 | 0.718191E+10 | 1175.79 | 0.178543E+11 | 0.648744E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.860718E+10 | 0.252294E+10 | 321.83 | 0.604080E+10 | 0.256638E+10 | 0.00 | 1.00 | 0.00 | 32388.68 | 17855.03 | 15519.80 | 7555.71 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 |
April | 26789971.05 | 8566316.05 | 2.83 | 22322139.23 | 4467831.82 | 0.00 | 0.16 | 23-APR-16:00 | 0.00 | 01-APR-00:05 | 3922.51 | 23-APR-16:00 | 3296.59 | 23-APR-16:00 | 625.92 | 23-APR-16:00 | 1268.16 | 23-APR-16:00 | 0.00 | 01-APR-00:05 |
May | 0.156942E+10 | 0.489440E+09 | 113.83 | 0.131826E+10 | 0.251158E+09 | 0.00 | 0.38 | 25-MAY-16:10 | 0.00 | 01-MAY-00:10 | 10294.89 | 25-MAY-15:00 | 7913.09 | 25-MAY-16:20 | 2548.51 | 26-MAY-12:10 | 3232.90 | 25-MAY-16:10 | 0.00 | 01-MAY-00:10 |
June | 0.470460E+10 | 0.142277E+10 | 224.69 | 0.338405E+10 | 0.132055E+10 | 0.00 | 0.98 | 30-JUN-07:02 | 0.00 | 01-JUN-00:10 | 35734.05 | 30-JUN-07:02 | 16392.14 | 30-JUN-07:02 | 19341.90 | 30-JUN-07:02 | 8295.76 | 30-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.802932E+10 | 0.238544E+10 | 312.18 | 0.557671E+10 | 0.245261E+10 | 0.00 | 0.93 | 23-JUL-08:62 | 0.00 | 01-JUL-00:05 | 32734.91 | 23-JUL-08:62 | 16398.50 | 23-JUL-08:62 | 16336.41 | 23-JUL-08:62 | 7640.92 | 23-JUL-08:62 | 0.00 | 01-JUL-00:05 |
August | 0.624889E+10 | 0.184051E+10 | 282.58 | 0.443080E+10 | 0.181809E+10 | 0.00 | 0.58 | 08-AUG-15:00 | 0.00 | 01-AUG-00:10 | 17302.44 | 08-AUG-15:00 | 11187.86 | 08-AUG-15:00 | 6114.58 | 08-AUG-15:00 | 5123.64 | 08-AUG-15:00 | 0.00 | 01-AUG-00:10 |
September | 0.121026E+10 | 0.360673E+09 | 123.83 | 0.101172E+10 | 0.198538E+09 | 0.00 | 0.40 | 01-SEP-14:10 | 0.00 | 01-SEP-00:10 | 11095.20 | 01-SEP-14:10 | 8719.29 | 01-SEP-15:00 | 2723.73 | 01-SEP-12:20 | 3277.68 | 01-SEP-14:20 | 0.00 | 01-SEP-00:10 |
October | 0.110383E+09 | 33352548.59 | 19.33 | 0.103504E+09 | 6878929.09 | 0.00 | 0.13 | 19-OCT-15:00 | 0.00 | 01-OCT-00:05 | 3113.19 | 19-OCT-15:00 | 2849.33 | 19-OCT-15:00 | 314.10 | 22-OCT-14:10 | 944.93 | 19-OCT-15:00 | 0.00 | 01-OCT-00:05 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 |
Annual Sum or Average | 0.218997E+11 | 0.654076E+10 | 1079.29 | 0.158474E+11 | 0.605229E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.802932E+10 | 0.238544E+10 | 312.18 | 0.557671E+10 | 0.245261E+10 | 0.00 | 0.98 | 0.00 | 35734.05 | 16398.50 | 19341.90 | 8295.76 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 131.26 | 91.31 | 39.96 | 95.47 | 174.10 | 0.00 | 0.00 | 744.00 |
February | 166.25 | 112.29 | 53.96 | 138.87 | 144.73 | 0.00 | 0.00 | 672.00 |
March | 146.56 | 92.78 | 53.78 | 119.82 | 120.66 | 0.00 | 0.00 | 744.00 |
April | 132.74 | 72.06 | 60.68 | 111.95 | 78.68 | 0.00 | 0.00 | 720.00 |
May | 111.57 | 38.13 | 73.44 | 96.44 | 45.63 | 0.00 | 0.00 | 744.00 |
June | 100.11 | 26.67 | 73.44 | 90.79 | 32.66 | 0.00 | 0.00 | 720.00 |
July | 109.45 | 34.66 | 74.79 | 105.44 | 30.21 | 0.00 | 0.00 | 744.00 |
August | 116.90 | 48.90 | 68.00 | 115.47 | 36.36 | 0.00 | 0.00 | 744.00 |
September | 125.26 | 66.73 | 58.53 | 120.78 | 56.18 | 0.00 | 0.00 | 720.00 |
October | 106.96 | 62.92 | 44.04 | 94.50 | 80.55 | 0.00 | 0.00 | 744.00 |
November | 95.23 | 59.75 | 35.47 | 75.76 | 114.82 | 0.00 | 0.00 | 720.00 |
December | 101.35 | 66.45 | 34.90 | 67.04 | 170.47 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 120.00 | 64.08 | 55.92 | 102.43 | 90.19 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 95.23 | 26.67 | 34.90 | 67.04 | 30.21 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 166.25 | 112.29 | 74.79 | 138.87 | 174.10 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 131.26 | 91.31 | 39.96 | 95.47 | 174.10 | 0.00 | 0.00 | 744.00 |
February | 166.25 | 112.29 | 53.96 | 138.87 | 144.73 | 0.00 | 0.00 | 672.00 |
March | 146.56 | 92.78 | 53.78 | 119.82 | 120.66 | 0.00 | 0.00 | 744.00 |
April | 132.74 | 72.06 | 60.68 | 111.95 | 78.68 | 0.00 | 0.00 | 720.00 |
May | 111.57 | 38.13 | 73.44 | 96.44 | 45.63 | 0.00 | 0.00 | 744.00 |
June | 100.11 | 26.67 | 73.44 | 90.79 | 32.66 | 0.00 | 0.00 | 720.00 |
July | 109.45 | 34.66 | 74.79 | 105.44 | 30.21 | 0.00 | 0.00 | 744.00 |
August | 116.90 | 48.90 | 68.00 | 115.47 | 36.36 | 0.00 | 0.00 | 744.00 |
September | 125.26 | 66.73 | 58.53 | 120.78 | 56.18 | 0.00 | 0.00 | 720.00 |
October | 106.96 | 62.92 | 44.04 | 94.50 | 80.55 | 0.00 | 0.00 | 744.00 |
November | 95.23 | 59.75 | 35.47 | 75.76 | 114.82 | 0.00 | 0.00 | 720.00 |
December | 101.35 | 66.45 | 34.90 | 67.04 | 170.47 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 120.00 | 64.08 | 55.92 | 102.43 | 90.19 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 95.23 | 26.67 | 34.90 | 67.04 | 30.21 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 166.25 | 112.29 | 74.79 | 138.87 | 174.10 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_3
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 131.26 | 91.31 | 39.96 | 95.47 | 174.10 | 0.00 | 0.00 | 744.00 |
February | 166.25 | 112.29 | 53.96 | 138.87 | 144.73 | 0.00 | 0.00 | 672.00 |
March | 146.56 | 92.78 | 53.78 | 119.82 | 120.66 | 0.00 | 0.00 | 744.00 |
April | 132.74 | 72.06 | 60.68 | 111.95 | 78.68 | 0.00 | 0.00 | 720.00 |
May | 111.57 | 38.13 | 73.44 | 96.44 | 45.63 | 0.00 | 0.00 | 744.00 |
June | 100.11 | 26.67 | 73.44 | 90.79 | 32.66 | 0.00 | 0.00 | 720.00 |
July | 109.45 | 34.66 | 74.79 | 105.44 | 30.21 | 0.00 | 0.00 | 744.00 |
August | 116.90 | 48.90 | 68.00 | 115.47 | 36.36 | 0.00 | 0.00 | 744.00 |
September | 125.26 | 66.73 | 58.53 | 120.78 | 56.18 | 0.00 | 0.00 | 720.00 |
October | 106.96 | 62.92 | 44.04 | 94.50 | 80.55 | 0.00 | 0.00 | 744.00 |
November | 95.23 | 59.75 | 35.47 | 75.76 | 114.82 | 0.00 | 0.00 | 720.00 |
December | 101.35 | 66.45 | 34.90 | 67.04 | 170.47 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 120.00 | 64.08 | 55.92 | 102.43 | 90.19 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 95.23 | 26.67 | 34.90 | 67.04 | 30.21 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 166.25 | 112.29 | 74.79 | 138.87 | 174.10 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_4
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 131.26 | 91.31 | 39.96 | 95.47 | 174.10 | 0.00 | 0.00 | 744.00 |
February | 166.25 | 112.29 | 53.96 | 138.87 | 144.73 | 0.00 | 0.00 | 672.00 |
March | 146.56 | 92.78 | 53.78 | 119.82 | 120.66 | 0.00 | 0.00 | 744.00 |
April | 132.74 | 72.06 | 60.68 | 111.95 | 78.68 | 0.00 | 0.00 | 720.00 |
May | 111.57 | 38.13 | 73.44 | 96.44 | 45.63 | 0.00 | 0.00 | 744.00 |
June | 100.11 | 26.67 | 73.44 | 90.79 | 32.66 | 0.00 | 0.00 | 720.00 |
July | 109.45 | 34.66 | 74.79 | 105.44 | 30.21 | 0.00 | 0.00 | 744.00 |
August | 116.90 | 48.90 | 68.00 | 115.47 | 36.36 | 0.00 | 0.00 | 744.00 |
September | 125.26 | 66.73 | 58.53 | 120.78 | 56.18 | 0.00 | 0.00 | 720.00 |
October | 106.96 | 62.92 | 44.04 | 94.50 | 80.55 | 0.00 | 0.00 | 744.00 |
November | 95.23 | 59.75 | 35.47 | 75.76 | 114.82 | 0.00 | 0.00 | 720.00 |
December | 101.35 | 66.45 | 34.90 | 67.04 | 170.47 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 120.00 | 64.08 | 55.92 | 102.43 | 90.19 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 95.23 | 26.67 | 34.90 | 67.04 | 30.21 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 166.25 | 112.29 | 74.79 | 138.87 | 174.10 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_DOOR_1
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 158.03 | 109.93 | 48.11 | 115.42 | 207.09 | 0.00 | 0.00 | 744.00 |
February | 200.16 | 135.19 | 64.97 | 167.69 | 172.23 | 0.00 | 0.00 | 672.00 |
March | 176.46 | 111.70 | 64.75 | 144.57 | 143.64 | 0.00 | 0.00 | 744.00 |
April | 159.81 | 86.75 | 73.06 | 134.97 | 93.77 | 0.00 | 0.00 | 720.00 |
May | 134.32 | 45.91 | 88.41 | 116.17 | 54.50 | 0.00 | 0.00 | 744.00 |
June | 120.52 | 32.11 | 88.41 | 109.26 | 39.06 | 0.00 | 0.00 | 720.00 |
July | 131.77 | 41.73 | 90.04 | 126.82 | 36.15 | 0.00 | 0.00 | 744.00 |
August | 140.74 | 58.87 | 81.87 | 138.94 | 43.47 | 0.00 | 0.00 | 744.00 |
September | 150.81 | 80.34 | 70.47 | 145.45 | 67.11 | 0.00 | 0.00 | 720.00 |
October | 128.77 | 75.75 | 53.02 | 113.89 | 96.10 | 0.00 | 0.00 | 744.00 |
November | 114.65 | 71.94 | 42.71 | 91.46 | 136.76 | 0.00 | 0.00 | 720.00 |
December | 122.02 | 80.00 | 42.02 | 81.12 | 202.73 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 144.48 | 77.15 | 67.33 | 123.49 | 107.44 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 114.65 | 32.11 | 42.02 | 81.12 | 36.15 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 200.16 | 135.19 | 90.04 | 167.69 | 207.09 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_DOOR_2
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 158.03 | 109.93 | 48.11 | 115.42 | 207.09 | 0.00 | 0.00 | 744.00 |
February | 200.16 | 135.19 | 64.97 | 167.69 | 172.23 | 0.00 | 0.00 | 672.00 |
March | 176.46 | 111.70 | 64.75 | 144.57 | 143.64 | 0.00 | 0.00 | 744.00 |
April | 159.81 | 86.75 | 73.06 | 134.97 | 93.77 | 0.00 | 0.00 | 720.00 |
May | 134.32 | 45.91 | 88.41 | 116.17 | 54.50 | 0.00 | 0.00 | 744.00 |
June | 120.52 | 32.11 | 88.41 | 109.26 | 39.06 | 0.00 | 0.00 | 720.00 |
July | 131.77 | 41.73 | 90.04 | 126.82 | 36.15 | 0.00 | 0.00 | 744.00 |
August | 140.74 | 58.87 | 81.87 | 138.94 | 43.47 | 0.00 | 0.00 | 744.00 |
September | 150.81 | 80.34 | 70.47 | 145.45 | 67.11 | 0.00 | 0.00 | 720.00 |
October | 128.77 | 75.75 | 53.02 | 113.89 | 96.10 | 0.00 | 0.00 | 744.00 |
November | 114.65 | 71.94 | 42.71 | 91.46 | 136.76 | 0.00 | 0.00 | 720.00 |
December | 122.02 | 80.00 | 42.02 | 81.12 | 202.73 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 144.48 | 77.15 | 67.33 | 123.49 | 107.44 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 114.65 | 32.11 | 42.02 | 81.12 | 36.15 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 200.16 | 135.19 | 90.04 | 167.69 | 207.09 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 131.26 | 91.31 | 39.96 | 94.28 | 178.99 | 0.00 | 0.00 | 744.00 |
February | 166.25 | 112.29 | 53.96 | 137.29 | 149.88 | 0.00 | 0.00 | 672.00 |
March | 146.56 | 92.78 | 53.78 | 118.46 | 126.25 | 0.00 | 0.00 | 744.00 |
April | 132.74 | 72.06 | 60.68 | 110.40 | 84.12 | 0.00 | 0.00 | 720.00 |
May | 111.57 | 38.13 | 73.44 | 95.01 | 48.07 | 0.00 | 0.00 | 744.00 |
June | 100.11 | 26.67 | 73.44 | 89.81 | 33.90 | 0.00 | 0.00 | 720.00 |
July | 109.45 | 34.66 | 74.79 | 105.02 | 30.79 | 0.00 | 0.00 | 744.00 |
August | 116.90 | 48.90 | 68.00 | 115.11 | 36.97 | 0.00 | 0.00 | 744.00 |
September | 125.26 | 66.73 | 58.53 | 120.08 | 57.57 | 0.00 | 0.00 | 720.00 |
October | 106.96 | 62.92 | 44.04 | 93.72 | 84.24 | 0.00 | 0.00 | 744.00 |
November | 95.23 | 59.75 | 35.47 | 74.87 | 119.46 | 0.00 | 0.00 | 720.00 |
December | 101.35 | 66.45 | 34.90 | 66.10 | 175.79 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 120.00 | 64.08 | 55.92 | 101.42 | 93.60 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 95.23 | 26.67 | 34.90 | 66.10 | 30.79 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 166.25 | 112.29 | 74.79 | 137.29 | 178.99 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 131.26 | 91.31 | 39.96 | 94.28 | 178.99 | 0.00 | 0.00 | 744.00 |
February | 166.25 | 112.29 | 53.96 | 137.29 | 149.88 | 0.00 | 0.00 | 672.00 |
March | 146.56 | 92.78 | 53.78 | 118.46 | 126.25 | 0.00 | 0.00 | 744.00 |
April | 132.74 | 72.06 | 60.68 | 110.40 | 84.12 | 0.00 | 0.00 | 720.00 |
May | 111.57 | 38.13 | 73.44 | 95.01 | 48.07 | 0.00 | 0.00 | 744.00 |
June | 100.11 | 26.67 | 73.44 | 89.81 | 33.90 | 0.00 | 0.00 | 720.00 |
July | 109.45 | 34.66 | 74.79 | 105.02 | 30.79 | 0.00 | 0.00 | 744.00 |
August | 116.90 | 48.90 | 68.00 | 115.11 | 36.97 | 0.00 | 0.00 | 744.00 |
September | 125.26 | 66.73 | 58.53 | 120.08 | 57.57 | 0.00 | 0.00 | 720.00 |
October | 106.96 | 62.92 | 44.04 | 93.72 | 84.24 | 0.00 | 0.00 | 744.00 |
November | 95.23 | 59.75 | 35.47 | 74.87 | 119.46 | 0.00 | 0.00 | 720.00 |
December | 101.35 | 66.45 | 34.90 | 66.10 | 175.79 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 120.00 | 64.08 | 55.92 | 101.42 | 93.60 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 95.23 | 26.67 | 34.90 | 66.10 | 30.79 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 166.25 | 112.29 | 74.79 | 137.29 | 178.99 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_DOOR
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 158.03 | 109.93 | 48.11 | 114.01 | 212.88 | 0.00 | 0.00 | 744.00 |
February | 200.16 | 135.19 | 64.97 | 165.79 | 178.33 | 0.00 | 0.00 | 672.00 |
March | 176.46 | 111.70 | 64.75 | 142.93 | 150.26 | 0.00 | 0.00 | 744.00 |
April | 159.81 | 86.75 | 73.06 | 133.11 | 100.20 | 0.00 | 0.00 | 720.00 |
May | 134.32 | 45.91 | 88.41 | 114.46 | 57.37 | 0.00 | 0.00 | 744.00 |
June | 120.52 | 32.11 | 88.41 | 108.09 | 40.52 | 0.00 | 0.00 | 720.00 |
July | 131.77 | 41.73 | 90.04 | 126.32 | 36.84 | 0.00 | 0.00 | 744.00 |
August | 140.74 | 58.87 | 81.87 | 138.53 | 44.19 | 0.00 | 0.00 | 744.00 |
September | 150.81 | 80.34 | 70.47 | 144.63 | 68.74 | 0.00 | 0.00 | 720.00 |
October | 128.77 | 75.75 | 53.02 | 112.97 | 100.44 | 0.00 | 0.00 | 744.00 |
November | 114.65 | 71.94 | 42.71 | 90.40 | 142.21 | 0.00 | 0.00 | 720.00 |
December | 122.02 | 80.00 | 42.02 | 79.99 | 209.03 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 144.48 | 77.15 | 67.33 | 122.29 | 111.47 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 114.65 | 32.11 | 42.02 | 79.99 | 36.84 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 200.16 | 135.19 | 90.04 | 165.79 | 212.88 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 131.26 | 91.31 | 39.96 | 94.64 | 173.81 | 0.00 | 0.00 | 744.00 |
February | 166.25 | 112.29 | 53.96 | 137.76 | 145.19 | 0.00 | 0.00 | 672.00 |
March | 146.56 | 92.78 | 53.78 | 118.81 | 122.21 | 0.00 | 0.00 | 744.00 |
April | 132.74 | 72.06 | 60.68 | 110.97 | 80.28 | 0.00 | 0.00 | 720.00 |
May | 111.57 | 38.13 | 73.44 | 95.73 | 46.58 | 0.00 | 0.00 | 744.00 |
June | 100.11 | 26.67 | 73.44 | 90.19 | 33.87 | 0.00 | 0.00 | 720.00 |
July | 109.45 | 34.66 | 74.79 | 104.91 | 31.86 | 0.00 | 0.00 | 744.00 |
August | 116.90 | 48.90 | 68.00 | 115.13 | 37.70 | 0.00 | 0.00 | 744.00 |
September | 125.26 | 66.73 | 58.53 | 120.58 | 56.38 | 0.00 | 0.00 | 720.00 |
October | 106.96 | 62.92 | 44.04 | 94.30 | 80.52 | 0.00 | 0.00 | 744.00 |
November | 95.23 | 59.75 | 35.47 | 75.28 | 114.84 | 0.00 | 0.00 | 720.00 |
December | 101.35 | 66.45 | 34.90 | 66.38 | 170.53 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 120.00 | 64.08 | 55.92 | 101.79 | 90.92 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 95.23 | 26.67 | 34.90 | 66.38 | 31.86 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 166.25 | 112.29 | 74.79 | 137.76 | 173.81 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 131.26 | 91.31 | 39.96 | 94.64 | 173.81 | 0.00 | 0.00 | 744.00 |
February | 166.25 | 112.29 | 53.96 | 137.76 | 145.19 | 0.00 | 0.00 | 672.00 |
March | 146.56 | 92.78 | 53.78 | 118.81 | 122.21 | 0.00 | 0.00 | 744.00 |
April | 132.74 | 72.06 | 60.68 | 110.97 | 80.28 | 0.00 | 0.00 | 720.00 |
May | 111.57 | 38.13 | 73.44 | 95.73 | 46.58 | 0.00 | 0.00 | 744.00 |
June | 100.11 | 26.67 | 73.44 | 90.19 | 33.87 | 0.00 | 0.00 | 720.00 |
July | 109.45 | 34.66 | 74.79 | 104.91 | 31.86 | 0.00 | 0.00 | 744.00 |
August | 116.90 | 48.90 | 68.00 | 115.13 | 37.70 | 0.00 | 0.00 | 744.00 |
September | 125.26 | 66.73 | 58.53 | 120.58 | 56.38 | 0.00 | 0.00 | 720.00 |
October | 106.96 | 62.92 | 44.04 | 94.30 | 80.52 | 0.00 | 0.00 | 744.00 |
November | 95.23 | 59.75 | 35.47 | 75.28 | 114.84 | 0.00 | 0.00 | 720.00 |
December | 101.35 | 66.45 | 34.90 | 66.38 | 170.53 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 120.00 | 64.08 | 55.92 | 101.79 | 90.92 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 95.23 | 26.67 | 34.90 | 66.38 | 31.86 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 166.25 | 112.29 | 74.79 | 137.76 | 173.81 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_DOOR
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 157.17 | 109.33 | 47.85 | 113.83 | 205.56 | 0.00 | 0.00 | 744.00 |
February | 199.07 | 134.45 | 64.61 | 165.47 | 171.78 | 0.00 | 0.00 | 672.00 |
March | 175.49 | 111.09 | 64.40 | 142.58 | 144.65 | 0.00 | 0.00 | 744.00 |
April | 158.94 | 86.28 | 72.66 | 133.07 | 95.10 | 0.00 | 0.00 | 720.00 |
May | 133.59 | 45.66 | 87.93 | 114.71 | 55.27 | 0.00 | 0.00 | 744.00 |
June | 119.86 | 31.93 | 87.93 | 107.97 | 40.22 | 0.00 | 0.00 | 720.00 |
July | 131.05 | 41.50 | 89.55 | 125.52 | 37.86 | 0.00 | 0.00 | 744.00 |
August | 139.97 | 58.55 | 81.43 | 137.80 | 44.77 | 0.00 | 0.00 | 744.00 |
September | 149.99 | 79.90 | 70.08 | 144.45 | 66.92 | 0.00 | 0.00 | 720.00 |
October | 128.07 | 75.34 | 52.73 | 113.05 | 95.47 | 0.00 | 0.00 | 744.00 |
November | 114.02 | 71.55 | 42.47 | 90.41 | 135.95 | 0.00 | 0.00 | 720.00 |
December | 121.36 | 79.56 | 41.79 | 79.90 | 201.63 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 143.69 | 76.73 | 66.96 | 122.08 | 107.66 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 114.02 | 31.93 | 41.79 | 79.90 | 37.86 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 199.07 | 134.45 | 89.55 | 165.47 | 205.56 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 131.26 | 91.31 | 39.96 | 94.81 | 172.32 | 0.00 | 0.00 | 744.00 |
February | 166.25 | 112.29 | 53.96 | 138.01 | 143.65 | 0.00 | 0.00 | 672.00 |
March | 146.56 | 92.78 | 53.78 | 119.02 | 120.77 | 0.00 | 0.00 | 744.00 |
April | 132.74 | 72.06 | 60.68 | 111.30 | 78.82 | 0.00 | 0.00 | 720.00 |
May | 111.57 | 38.13 | 73.44 | 96.16 | 45.63 | 0.00 | 0.00 | 744.00 |
June | 100.11 | 26.67 | 73.44 | 90.50 | 33.32 | 0.00 | 0.00 | 720.00 |
July | 109.45 | 34.66 | 74.79 | 105.02 | 31.65 | 0.00 | 0.00 | 744.00 |
August | 116.90 | 48.90 | 68.00 | 115.25 | 37.40 | 0.00 | 0.00 | 744.00 |
September | 125.26 | 66.73 | 58.53 | 120.88 | 55.52 | 0.00 | 0.00 | 720.00 |
October | 106.96 | 62.92 | 44.04 | 94.58 | 79.14 | 0.00 | 0.00 | 744.00 |
November | 95.23 | 59.75 | 35.47 | 75.50 | 113.24 | 0.00 | 0.00 | 720.00 |
December | 101.35 | 66.45 | 34.90 | 66.51 | 168.94 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 120.00 | 64.08 | 55.92 | 102.03 | 89.81 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 95.23 | 26.67 | 34.90 | 66.51 | 31.65 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 166.25 | 112.29 | 74.79 | 138.01 | 172.32 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 131.26 | 91.31 | 39.96 | 94.81 | 172.32 | 0.00 | 0.00 | 744.00 |
February | 166.25 | 112.29 | 53.96 | 138.01 | 143.65 | 0.00 | 0.00 | 672.00 |
March | 146.56 | 92.78 | 53.78 | 119.02 | 120.77 | 0.00 | 0.00 | 744.00 |
April | 132.74 | 72.06 | 60.68 | 111.30 | 78.82 | 0.00 | 0.00 | 720.00 |
May | 111.57 | 38.13 | 73.44 | 96.16 | 45.63 | 0.00 | 0.00 | 744.00 |
June | 100.11 | 26.67 | 73.44 | 90.50 | 33.32 | 0.00 | 0.00 | 720.00 |
July | 109.45 | 34.66 | 74.79 | 105.02 | 31.65 | 0.00 | 0.00 | 744.00 |
August | 116.90 | 48.90 | 68.00 | 115.25 | 37.40 | 0.00 | 0.00 | 744.00 |
September | 125.26 | 66.73 | 58.53 | 120.88 | 55.52 | 0.00 | 0.00 | 720.00 |
October | 106.96 | 62.92 | 44.04 | 94.58 | 79.14 | 0.00 | 0.00 | 744.00 |
November | 95.23 | 59.75 | 35.47 | 75.50 | 113.24 | 0.00 | 0.00 | 720.00 |
December | 101.35 | 66.45 | 34.90 | 66.51 | 168.94 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 120.00 | 64.08 | 55.92 | 102.03 | 89.81 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 95.23 | 26.67 | 34.90 | 66.51 | 31.65 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 166.25 | 112.29 | 74.79 | 138.01 | 172.32 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_DOOR
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 157.17 | 109.33 | 47.85 | 114.03 | 203.78 | 0.00 | 0.00 | 744.00 |
February | 199.07 | 134.45 | 64.61 | 165.77 | 169.95 | 0.00 | 0.00 | 672.00 |
March | 175.49 | 111.09 | 64.40 | 142.84 | 142.93 | 0.00 | 0.00 | 744.00 |
April | 158.94 | 86.28 | 72.66 | 133.48 | 93.37 | 0.00 | 0.00 | 720.00 |
May | 133.59 | 45.66 | 87.93 | 115.22 | 54.15 | 0.00 | 0.00 | 744.00 |
June | 119.86 | 31.93 | 87.93 | 108.34 | 39.57 | 0.00 | 0.00 | 720.00 |
July | 131.05 | 41.50 | 89.55 | 125.65 | 37.61 | 0.00 | 0.00 | 744.00 |
August | 139.97 | 58.55 | 81.43 | 137.95 | 44.42 | 0.00 | 0.00 | 744.00 |
September | 149.99 | 79.90 | 70.08 | 144.81 | 65.90 | 0.00 | 0.00 | 720.00 |
October | 128.07 | 75.34 | 52.73 | 113.39 | 93.83 | 0.00 | 0.00 | 744.00 |
November | 114.02 | 71.55 | 42.47 | 90.67 | 134.04 | 0.00 | 0.00 | 720.00 |
December | 121.36 | 79.56 | 41.79 | 80.06 | 199.74 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 143.69 | 76.73 | 66.96 | 122.37 | 106.34 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 114.02 | 31.93 | 41.79 | 80.06 | 37.61 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 199.07 | 134.45 | 89.55 | 165.77 | 203.78 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 131.26 | 91.31 | 39.96 | 94.93 | 171.57 | 0.00 | 0.00 | 744.00 |
February | 166.25 | 112.29 | 53.96 | 138.20 | 142.82 | 0.00 | 0.00 | 672.00 |
March | 146.56 | 92.78 | 53.78 | 119.20 | 119.91 | 0.00 | 0.00 | 744.00 |
April | 132.74 | 72.06 | 60.68 | 111.57 | 77.95 | 0.00 | 0.00 | 720.00 |
May | 111.57 | 38.13 | 73.44 | 96.53 | 44.95 | 0.00 | 0.00 | 744.00 |
June | 100.11 | 26.67 | 73.44 | 90.80 | 32.81 | 0.00 | 0.00 | 720.00 |
July | 109.45 | 34.66 | 74.79 | 105.17 | 31.31 | 0.00 | 0.00 | 744.00 |
August | 116.90 | 48.90 | 68.00 | 115.38 | 37.03 | 0.00 | 0.00 | 744.00 |
September | 125.26 | 66.73 | 58.53 | 121.12 | 54.93 | 0.00 | 0.00 | 720.00 |
October | 106.96 | 62.92 | 44.04 | 94.77 | 78.43 | 0.00 | 0.00 | 744.00 |
November | 95.23 | 59.75 | 35.47 | 75.66 | 112.33 | 0.00 | 0.00 | 720.00 |
December | 101.35 | 66.45 | 34.90 | 66.62 | 168.11 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 120.00 | 64.08 | 55.92 | 102.23 | 89.12 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 95.23 | 26.67 | 34.90 | 66.62 | 31.31 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 166.25 | 112.29 | 74.79 | 138.20 | 171.57 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 131.26 | 91.31 | 39.96 | 94.93 | 171.57 | 0.00 | 0.00 | 744.00 |
February | 166.25 | 112.29 | 53.96 | 138.20 | 142.82 | 0.00 | 0.00 | 672.00 |
March | 146.56 | 92.78 | 53.78 | 119.20 | 119.91 | 0.00 | 0.00 | 744.00 |
April | 132.74 | 72.06 | 60.68 | 111.57 | 77.95 | 0.00 | 0.00 | 720.00 |
May | 111.57 | 38.13 | 73.44 | 96.53 | 44.95 | 0.00 | 0.00 | 744.00 |
June | 100.11 | 26.67 | 73.44 | 90.80 | 32.81 | 0.00 | 0.00 | 720.00 |
July | 109.45 | 34.66 | 74.79 | 105.17 | 31.31 | 0.00 | 0.00 | 744.00 |
August | 116.90 | 48.90 | 68.00 | 115.38 | 37.03 | 0.00 | 0.00 | 744.00 |
September | 125.26 | 66.73 | 58.53 | 121.12 | 54.93 | 0.00 | 0.00 | 720.00 |
October | 106.96 | 62.92 | 44.04 | 94.77 | 78.43 | 0.00 | 0.00 | 744.00 |
November | 95.23 | 59.75 | 35.47 | 75.66 | 112.33 | 0.00 | 0.00 | 720.00 |
December | 101.35 | 66.45 | 34.90 | 66.62 | 168.11 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 120.00 | 64.08 | 55.92 | 102.23 | 89.12 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 95.23 | 26.67 | 34.90 | 66.62 | 31.31 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 166.25 | 112.29 | 74.79 | 138.20 | 171.57 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_DOOR
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 157.17 | 109.33 | 47.85 | 114.18 | 202.89 | 0.00 | 0.00 | 744.00 |
February | 199.07 | 134.45 | 64.61 | 166.00 | 168.95 | 0.00 | 0.00 | 672.00 |
March | 175.49 | 111.09 | 64.40 | 143.05 | 141.90 | 0.00 | 0.00 | 744.00 |
April | 158.94 | 86.28 | 72.66 | 133.80 | 92.33 | 0.00 | 0.00 | 720.00 |
May | 133.59 | 45.66 | 87.93 | 115.66 | 53.34 | 0.00 | 0.00 | 744.00 |
June | 119.86 | 31.93 | 87.93 | 108.70 | 38.97 | 0.00 | 0.00 | 720.00 |
July | 131.05 | 41.50 | 89.55 | 125.84 | 37.21 | 0.00 | 0.00 | 744.00 |
August | 139.97 | 58.55 | 81.43 | 138.11 | 43.97 | 0.00 | 0.00 | 744.00 |
September | 149.99 | 79.90 | 70.08 | 145.09 | 65.19 | 0.00 | 0.00 | 720.00 |
October | 128.07 | 75.34 | 52.73 | 113.62 | 92.98 | 0.00 | 0.00 | 744.00 |
November | 114.02 | 71.55 | 42.47 | 90.87 | 132.96 | 0.00 | 0.00 | 720.00 |
December | 121.36 | 79.56 | 41.79 | 80.19 | 198.75 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 143.69 | 76.73 | 66.96 | 122.61 | 105.53 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 114.02 | 31.93 | 41.79 | 80.19 | 37.21 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 199.07 | 134.45 | 89.55 | 166.00 | 202.89 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 131.26 | 91.31 | 39.96 | 95.84 | 167.98 | 0.00 | 0.00 | 744.00 |
February | 166.25 | 112.29 | 53.96 | 139.44 | 139.49 | 0.00 | 0.00 | 672.00 |
March | 146.56 | 92.78 | 53.78 | 120.09 | 116.73 | 0.00 | 0.00 | 744.00 |
April | 132.74 | 72.06 | 60.68 | 112.48 | 75.54 | 0.00 | 0.00 | 720.00 |
May | 111.57 | 38.13 | 73.44 | 97.35 | 43.49 | 0.00 | 0.00 | 744.00 |
June | 100.11 | 26.67 | 73.44 | 91.38 | 31.61 | 0.00 | 0.00 | 720.00 |
July | 109.45 | 34.66 | 74.79 | 105.37 | 30.36 | 0.00 | 0.00 | 744.00 |
August | 116.90 | 48.90 | 68.00 | 115.72 | 36.03 | 0.00 | 0.00 | 744.00 |
September | 125.26 | 66.73 | 58.53 | 121.78 | 53.79 | 0.00 | 0.00 | 720.00 |
October | 106.96 | 62.92 | 44.04 | 95.42 | 76.77 | 0.00 | 0.00 | 744.00 |
November | 95.23 | 59.75 | 35.47 | 76.46 | 109.33 | 0.00 | 0.00 | 720.00 |
December | 101.35 | 66.45 | 34.90 | 67.40 | 164.39 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 120.00 | 64.08 | 55.92 | 102.96 | 86.91 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 95.23 | 26.67 | 34.90 | 67.40 | 30.36 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 166.25 | 112.29 | 74.79 | 139.44 | 167.98 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 131.26 | 91.31 | 39.96 | 95.84 | 167.98 | 0.00 | 0.00 | 744.00 |
February | 166.25 | 112.29 | 53.96 | 139.44 | 139.49 | 0.00 | 0.00 | 672.00 |
March | 146.56 | 92.78 | 53.78 | 120.09 | 116.73 | 0.00 | 0.00 | 744.00 |
April | 132.74 | 72.06 | 60.68 | 112.48 | 75.54 | 0.00 | 0.00 | 720.00 |
May | 111.57 | 38.13 | 73.44 | 97.35 | 43.49 | 0.00 | 0.00 | 744.00 |
June | 100.11 | 26.67 | 73.44 | 91.38 | 31.61 | 0.00 | 0.00 | 720.00 |
July | 109.45 | 34.66 | 74.79 | 105.37 | 30.36 | 0.00 | 0.00 | 744.00 |
August | 116.90 | 48.90 | 68.00 | 115.72 | 36.03 | 0.00 | 0.00 | 744.00 |
September | 125.26 | 66.73 | 58.53 | 121.78 | 53.79 | 0.00 | 0.00 | 720.00 |
October | 106.96 | 62.92 | 44.04 | 95.42 | 76.77 | 0.00 | 0.00 | 744.00 |
November | 95.23 | 59.75 | 35.47 | 76.46 | 109.33 | 0.00 | 0.00 | 720.00 |
December | 101.35 | 66.45 | 34.90 | 67.40 | 164.39 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 120.00 | 64.08 | 55.92 | 102.96 | 86.91 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 95.23 | 26.67 | 34.90 | 67.40 | 30.36 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 166.25 | 112.29 | 74.79 | 139.44 | 167.98 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_3
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 131.26 | 91.31 | 39.96 | 95.84 | 167.98 | 0.00 | 0.00 | 744.00 |
February | 166.25 | 112.29 | 53.96 | 139.44 | 139.49 | 0.00 | 0.00 | 672.00 |
March | 146.56 | 92.78 | 53.78 | 120.09 | 116.73 | 0.00 | 0.00 | 744.00 |
April | 132.74 | 72.06 | 60.68 | 112.48 | 75.54 | 0.00 | 0.00 | 720.00 |
May | 111.57 | 38.13 | 73.44 | 97.35 | 43.49 | 0.00 | 0.00 | 744.00 |
June | 100.11 | 26.67 | 73.44 | 91.38 | 31.61 | 0.00 | 0.00 | 720.00 |
July | 109.45 | 34.66 | 74.79 | 105.37 | 30.36 | 0.00 | 0.00 | 744.00 |
August | 116.90 | 48.90 | 68.00 | 115.72 | 36.03 | 0.00 | 0.00 | 744.00 |
September | 125.26 | 66.73 | 58.53 | 121.78 | 53.79 | 0.00 | 0.00 | 720.00 |
October | 106.96 | 62.92 | 44.04 | 95.42 | 76.77 | 0.00 | 0.00 | 744.00 |
November | 95.23 | 59.75 | 35.47 | 76.46 | 109.33 | 0.00 | 0.00 | 720.00 |
December | 101.35 | 66.45 | 34.90 | 67.40 | 164.39 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 120.00 | 64.08 | 55.92 | 102.96 | 86.91 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 95.23 | 26.67 | 34.90 | 67.40 | 30.36 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 166.25 | 112.29 | 74.79 | 139.44 | 167.98 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_4
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 131.26 | 91.31 | 39.96 | 95.84 | 167.98 | 0.00 | 0.00 | 744.00 |
February | 166.25 | 112.29 | 53.96 | 139.44 | 139.49 | 0.00 | 0.00 | 672.00 |
March | 146.56 | 92.78 | 53.78 | 120.09 | 116.73 | 0.00 | 0.00 | 744.00 |
April | 132.74 | 72.06 | 60.68 | 112.48 | 75.54 | 0.00 | 0.00 | 720.00 |
May | 111.57 | 38.13 | 73.44 | 97.35 | 43.49 | 0.00 | 0.00 | 744.00 |
June | 100.11 | 26.67 | 73.44 | 91.38 | 31.61 | 0.00 | 0.00 | 720.00 |
July | 109.45 | 34.66 | 74.79 | 105.37 | 30.36 | 0.00 | 0.00 | 744.00 |
August | 116.90 | 48.90 | 68.00 | 115.72 | 36.03 | 0.00 | 0.00 | 744.00 |
September | 125.26 | 66.73 | 58.53 | 121.78 | 53.79 | 0.00 | 0.00 | 720.00 |
October | 106.96 | 62.92 | 44.04 | 95.42 | 76.77 | 0.00 | 0.00 | 744.00 |
November | 95.23 | 59.75 | 35.47 | 76.46 | 109.33 | 0.00 | 0.00 | 720.00 |
December | 101.35 | 66.45 | 34.90 | 67.40 | 164.39 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 120.00 | 64.08 | 55.92 | 102.96 | 86.91 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 95.23 | 26.67 | 34.90 | 67.40 | 30.36 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 166.25 | 112.29 | 74.79 | 139.44 | 167.98 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_DOOR_1
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 157.17 | 109.33 | 47.85 | 115.27 | 198.68 | 0.00 | 0.00 | 744.00 |
February | 199.07 | 134.45 | 64.61 | 167.47 | 165.06 | 0.00 | 0.00 | 672.00 |
March | 175.49 | 111.09 | 64.40 | 144.12 | 138.16 | 0.00 | 0.00 | 744.00 |
April | 158.94 | 86.28 | 72.66 | 134.89 | 89.50 | 0.00 | 0.00 | 720.00 |
May | 133.59 | 45.66 | 87.93 | 116.64 | 51.62 | 0.00 | 0.00 | 744.00 |
June | 119.86 | 31.93 | 87.93 | 109.40 | 37.56 | 0.00 | 0.00 | 720.00 |
July | 131.05 | 41.50 | 89.55 | 126.08 | 36.09 | 0.00 | 0.00 | 744.00 |
August | 139.97 | 58.55 | 81.43 | 138.51 | 42.80 | 0.00 | 0.00 | 744.00 |
September | 149.99 | 79.90 | 70.08 | 145.87 | 63.86 | 0.00 | 0.00 | 720.00 |
October | 128.07 | 75.34 | 52.73 | 114.39 | 91.03 | 0.00 | 0.00 | 744.00 |
November | 114.02 | 71.55 | 42.47 | 91.82 | 129.44 | 0.00 | 0.00 | 720.00 |
December | 121.36 | 79.56 | 41.79 | 81.12 | 194.39 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 143.69 | 76.73 | 66.96 | 123.48 | 102.93 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 114.02 | 31.93 | 41.79 | 81.12 | 36.09 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 199.07 | 134.45 | 89.55 | 167.47 | 198.68 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_DOOR_2
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 157.17 | 109.33 | 47.85 | 115.27 | 198.68 | 0.00 | 0.00 | 744.00 |
February | 199.07 | 134.45 | 64.61 | 167.47 | 165.06 | 0.00 | 0.00 | 672.00 |
March | 175.49 | 111.09 | 64.40 | 144.12 | 138.16 | 0.00 | 0.00 | 744.00 |
April | 158.94 | 86.28 | 72.66 | 134.89 | 89.50 | 0.00 | 0.00 | 720.00 |
May | 133.59 | 45.66 | 87.93 | 116.64 | 51.62 | 0.00 | 0.00 | 744.00 |
June | 119.86 | 31.93 | 87.93 | 109.40 | 37.56 | 0.00 | 0.00 | 720.00 |
July | 131.05 | 41.50 | 89.55 | 126.08 | 36.09 | 0.00 | 0.00 | 744.00 |
August | 139.97 | 58.55 | 81.43 | 138.51 | 42.80 | 0.00 | 0.00 | 744.00 |
September | 149.99 | 79.90 | 70.08 | 145.87 | 63.86 | 0.00 | 0.00 | 720.00 |
October | 128.07 | 75.34 | 52.73 | 114.39 | 91.03 | 0.00 | 0.00 | 744.00 |
November | 114.02 | 71.55 | 42.47 | 91.82 | 129.44 | 0.00 | 0.00 | 720.00 |
December | 121.36 | 79.56 | 41.79 | 81.12 | 194.39 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 143.69 | 76.73 | 66.96 | 123.48 | 102.93 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 114.02 | 31.93 | 41.79 | 81.12 | 36.09 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 199.07 | 134.45 | 89.55 | 167.47 | 198.68 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 131.26 | 91.31 | 39.96 | 95.32 | 169.24 | 0.00 | 0.00 | 744.00 |
February | 166.25 | 112.29 | 53.96 | 138.83 | 140.46 | 0.00 | 0.00 | 672.00 |
March | 146.56 | 92.78 | 53.78 | 119.71 | 117.47 | 0.00 | 0.00 | 744.00 |
April | 132.74 | 72.06 | 60.68 | 112.26 | 75.82 | 0.00 | 0.00 | 720.00 |
May | 111.57 | 38.13 | 73.44 | 97.35 | 43.41 | 0.00 | 0.00 | 744.00 |
June | 100.11 | 26.67 | 73.44 | 91.50 | 31.42 | 0.00 | 0.00 | 720.00 |
July | 109.45 | 34.66 | 74.79 | 105.53 | 30.10 | 0.00 | 0.00 | 744.00 |
August | 116.90 | 48.90 | 68.00 | 115.73 | 35.83 | 0.00 | 0.00 | 744.00 |
September | 125.26 | 66.73 | 58.53 | 121.64 | 53.77 | 0.00 | 0.00 | 720.00 |
October | 106.96 | 62.92 | 44.04 | 95.21 | 76.96 | 0.00 | 0.00 | 744.00 |
November | 95.23 | 59.75 | 35.47 | 76.13 | 110.03 | 0.00 | 0.00 | 720.00 |
December | 101.35 | 66.45 | 34.90 | 66.99 | 165.72 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 120.00 | 64.08 | 55.92 | 102.75 | 87.30 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 95.23 | 26.67 | 34.90 | 66.99 | 30.10 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 166.25 | 112.29 | 74.79 | 138.83 | 169.24 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 131.26 | 91.31 | 39.96 | 95.32 | 169.24 | 0.00 | 0.00 | 744.00 |
February | 166.25 | 112.29 | 53.96 | 138.83 | 140.46 | 0.00 | 0.00 | 672.00 |
March | 146.56 | 92.78 | 53.78 | 119.71 | 117.47 | 0.00 | 0.00 | 744.00 |
April | 132.74 | 72.06 | 60.68 | 112.26 | 75.82 | 0.00 | 0.00 | 720.00 |
May | 111.57 | 38.13 | 73.44 | 97.35 | 43.41 | 0.00 | 0.00 | 744.00 |
June | 100.11 | 26.67 | 73.44 | 91.50 | 31.42 | 0.00 | 0.00 | 720.00 |
July | 109.45 | 34.66 | 74.79 | 105.53 | 30.10 | 0.00 | 0.00 | 744.00 |
August | 116.90 | 48.90 | 68.00 | 115.73 | 35.83 | 0.00 | 0.00 | 744.00 |
September | 125.26 | 66.73 | 58.53 | 121.64 | 53.77 | 0.00 | 0.00 | 720.00 |
October | 106.96 | 62.92 | 44.04 | 95.21 | 76.96 | 0.00 | 0.00 | 744.00 |
November | 95.23 | 59.75 | 35.47 | 76.13 | 110.03 | 0.00 | 0.00 | 720.00 |
December | 101.35 | 66.45 | 34.90 | 66.99 | 165.72 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 120.00 | 64.08 | 55.92 | 102.75 | 87.30 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 95.23 | 26.67 | 34.90 | 66.99 | 30.10 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 166.25 | 112.29 | 74.79 | 138.83 | 169.24 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_DOOR
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 157.17 | 109.33 | 47.85 | 114.66 | 200.12 | 0.00 | 0.00 | 744.00 |
February | 199.07 | 134.45 | 64.61 | 166.77 | 166.16 | 0.00 | 0.00 | 672.00 |
March | 175.49 | 111.09 | 64.40 | 143.68 | 139.01 | 0.00 | 0.00 | 744.00 |
April | 158.94 | 86.28 | 72.66 | 134.64 | 89.80 | 0.00 | 0.00 | 720.00 |
May | 133.59 | 45.66 | 87.93 | 116.66 | 51.51 | 0.00 | 0.00 | 744.00 |
June | 119.86 | 31.93 | 87.93 | 109.55 | 37.32 | 0.00 | 0.00 | 720.00 |
July | 131.05 | 41.50 | 89.55 | 126.28 | 35.78 | 0.00 | 0.00 | 744.00 |
August | 139.97 | 58.55 | 81.43 | 138.54 | 42.55 | 0.00 | 0.00 | 744.00 |
September | 149.99 | 79.90 | 70.08 | 145.72 | 63.81 | 0.00 | 0.00 | 720.00 |
October | 128.07 | 75.34 | 52.73 | 114.16 | 91.23 | 0.00 | 0.00 | 744.00 |
November | 114.02 | 71.55 | 42.47 | 91.44 | 130.22 | 0.00 | 0.00 | 720.00 |
December | 121.36 | 79.56 | 41.79 | 80.65 | 195.91 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 143.69 | 76.73 | 66.96 | 123.24 | 103.36 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 114.02 | 31.93 | 41.79 | 80.65 | 35.78 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 199.07 | 134.45 | 89.55 | 166.77 | 200.12 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 131.26 | 91.31 | 39.96 | 95.34 | 169.13 | 0.00 | 0.00 | 744.00 |
February | 166.25 | 112.29 | 53.96 | 138.87 | 140.30 | 0.00 | 0.00 | 672.00 |
March | 146.56 | 92.78 | 53.78 | 119.77 | 117.21 | 0.00 | 0.00 | 744.00 |
April | 132.74 | 72.06 | 60.68 | 112.40 | 75.38 | 0.00 | 0.00 | 720.00 |
May | 111.57 | 38.13 | 73.44 | 97.61 | 43.00 | 0.00 | 0.00 | 744.00 |
June | 100.11 | 26.67 | 73.44 | 91.75 | 31.10 | 0.00 | 0.00 | 720.00 |
July | 109.45 | 34.66 | 74.79 | 105.66 | 29.90 | 0.00 | 0.00 | 744.00 |
August | 116.90 | 48.90 | 68.00 | 115.85 | 35.61 | 0.00 | 0.00 | 744.00 |
September | 125.26 | 66.73 | 58.53 | 121.77 | 53.48 | 0.00 | 0.00 | 720.00 |
October | 106.96 | 62.92 | 44.04 | 95.29 | 76.67 | 0.00 | 0.00 | 744.00 |
November | 95.23 | 59.75 | 35.47 | 76.19 | 109.73 | 0.00 | 0.00 | 720.00 |
December | 101.35 | 66.45 | 34.90 | 67.01 | 165.60 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 120.00 | 64.08 | 55.92 | 102.86 | 87.04 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 95.23 | 26.67 | 34.90 | 67.01 | 29.90 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 166.25 | 112.29 | 74.79 | 138.87 | 169.13 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 131.26 | 91.31 | 39.96 | 95.34 | 169.13 | 0.00 | 0.00 | 744.00 |
February | 166.25 | 112.29 | 53.96 | 138.87 | 140.30 | 0.00 | 0.00 | 672.00 |
March | 146.56 | 92.78 | 53.78 | 119.77 | 117.21 | 0.00 | 0.00 | 744.00 |
April | 132.74 | 72.06 | 60.68 | 112.40 | 75.38 | 0.00 | 0.00 | 720.00 |
May | 111.57 | 38.13 | 73.44 | 97.61 | 43.00 | 0.00 | 0.00 | 744.00 |
June | 100.11 | 26.67 | 73.44 | 91.75 | 31.10 | 0.00 | 0.00 | 720.00 |
July | 109.45 | 34.66 | 74.79 | 105.66 | 29.90 | 0.00 | 0.00 | 744.00 |
August | 116.90 | 48.90 | 68.00 | 115.85 | 35.61 | 0.00 | 0.00 | 744.00 |
September | 125.26 | 66.73 | 58.53 | 121.77 | 53.48 | 0.00 | 0.00 | 720.00 |
October | 106.96 | 62.92 | 44.04 | 95.29 | 76.67 | 0.00 | 0.00 | 744.00 |
November | 95.23 | 59.75 | 35.47 | 76.19 | 109.73 | 0.00 | 0.00 | 720.00 |
December | 101.35 | 66.45 | 34.90 | 67.01 | 165.60 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 120.00 | 64.08 | 55.92 | 102.86 | 87.04 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 95.23 | 26.67 | 34.90 | 67.01 | 29.90 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 166.25 | 112.29 | 74.79 | 138.87 | 169.13 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_DOOR
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 157.17 | 109.33 | 47.85 | 114.69 | 199.99 | 0.00 | 0.00 | 744.00 |
February | 199.07 | 134.45 | 64.61 | 166.82 | 165.98 | 0.00 | 0.00 | 672.00 |
March | 175.49 | 111.09 | 64.40 | 143.75 | 138.70 | 0.00 | 0.00 | 744.00 |
April | 158.94 | 86.28 | 72.66 | 134.81 | 89.28 | 0.00 | 0.00 | 720.00 |
May | 133.59 | 45.66 | 87.93 | 116.97 | 51.03 | 0.00 | 0.00 | 744.00 |
June | 119.86 | 31.93 | 87.93 | 109.85 | 36.94 | 0.00 | 0.00 | 720.00 |
July | 131.05 | 41.50 | 89.55 | 126.44 | 35.54 | 0.00 | 0.00 | 744.00 |
August | 139.97 | 58.55 | 81.43 | 138.68 | 42.30 | 0.00 | 0.00 | 744.00 |
September | 149.99 | 79.90 | 70.08 | 145.88 | 63.47 | 0.00 | 0.00 | 720.00 |
October | 128.07 | 75.34 | 52.73 | 114.26 | 90.89 | 0.00 | 0.00 | 744.00 |
November | 114.02 | 71.55 | 42.47 | 91.52 | 129.87 | 0.00 | 0.00 | 720.00 |
December | 121.36 | 79.56 | 41.79 | 80.67 | 195.76 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 143.69 | 76.73 | 66.96 | 123.38 | 103.05 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 114.02 | 31.93 | 41.79 | 80.67 | 35.54 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 199.07 | 134.45 | 89.55 | 166.82 | 199.99 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 131.26 | 91.31 | 39.96 | 95.45 | 168.35 | 0.00 | 0.00 | 744.00 |
February | 166.25 | 112.29 | 53.96 | 139.05 | 139.37 | 0.00 | 0.00 | 672.00 |
March | 146.56 | 92.78 | 53.78 | 120.00 | 115.90 | 0.00 | 0.00 | 744.00 |
April | 132.74 | 72.06 | 60.68 | 112.87 | 73.67 | 0.00 | 0.00 | 720.00 |
May | 111.57 | 38.13 | 73.44 | 98.38 | 41.64 | 0.00 | 0.00 | 744.00 |
June | 100.11 | 26.67 | 73.44 | 92.48 | 30.09 | 0.00 | 0.00 | 720.00 |
July | 109.45 | 34.66 | 74.79 | 106.01 | 29.33 | 0.00 | 0.00 | 744.00 |
August | 116.90 | 48.90 | 68.00 | 116.12 | 35.02 | 0.00 | 0.00 | 744.00 |
September | 125.26 | 66.73 | 58.53 | 122.11 | 52.65 | 0.00 | 0.00 | 720.00 |
October | 106.96 | 62.92 | 44.04 | 95.53 | 75.70 | 0.00 | 0.00 | 744.00 |
November | 95.23 | 59.75 | 35.47 | 76.40 | 108.48 | 0.00 | 0.00 | 720.00 |
December | 101.35 | 66.45 | 34.90 | 67.10 | 164.77 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 120.00 | 64.08 | 55.92 | 103.19 | 86.03 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 95.23 | 26.67 | 34.90 | 67.10 | 29.33 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 166.25 | 112.29 | 74.79 | 139.05 | 168.35 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 131.26 | 91.31 | 39.96 | 95.45 | 168.35 | 0.00 | 0.00 | 744.00 |
February | 166.25 | 112.29 | 53.96 | 139.05 | 139.37 | 0.00 | 0.00 | 672.00 |
March | 146.56 | 92.78 | 53.78 | 120.00 | 115.90 | 0.00 | 0.00 | 744.00 |
April | 132.74 | 72.06 | 60.68 | 112.87 | 73.67 | 0.00 | 0.00 | 720.00 |
May | 111.57 | 38.13 | 73.44 | 98.38 | 41.64 | 0.00 | 0.00 | 744.00 |
June | 100.11 | 26.67 | 73.44 | 92.48 | 30.09 | 0.00 | 0.00 | 720.00 |
July | 109.45 | 34.66 | 74.79 | 106.01 | 29.33 | 0.00 | 0.00 | 744.00 |
August | 116.90 | 48.90 | 68.00 | 116.12 | 35.02 | 0.00 | 0.00 | 744.00 |
September | 125.26 | 66.73 | 58.53 | 122.11 | 52.65 | 0.00 | 0.00 | 720.00 |
October | 106.96 | 62.92 | 44.04 | 95.53 | 75.70 | 0.00 | 0.00 | 744.00 |
November | 95.23 | 59.75 | 35.47 | 76.40 | 108.48 | 0.00 | 0.00 | 720.00 |
December | 101.35 | 66.45 | 34.90 | 67.10 | 164.77 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 120.00 | 64.08 | 55.92 | 103.19 | 86.03 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 95.23 | 26.67 | 34.90 | 67.10 | 29.33 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 166.25 | 112.29 | 74.79 | 139.05 | 168.35 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_DOOR
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 157.17 | 109.33 | 47.85 | 114.82 | 199.05 | 0.00 | 0.00 | 744.00 |
February | 199.07 | 134.45 | 64.61 | 167.04 | 164.86 | 0.00 | 0.00 | 672.00 |
March | 175.49 | 111.09 | 64.40 | 144.04 | 137.13 | 0.00 | 0.00 | 744.00 |
April | 158.94 | 86.28 | 72.66 | 135.39 | 87.25 | 0.00 | 0.00 | 720.00 |
May | 133.59 | 45.66 | 87.93 | 117.89 | 49.42 | 0.00 | 0.00 | 744.00 |
June | 119.86 | 31.93 | 87.93 | 110.72 | 35.74 | 0.00 | 0.00 | 720.00 |
July | 131.05 | 41.50 | 89.55 | 126.86 | 34.86 | 0.00 | 0.00 | 744.00 |
August | 139.97 | 58.55 | 81.43 | 139.01 | 41.59 | 0.00 | 0.00 | 744.00 |
September | 149.99 | 79.90 | 70.08 | 146.29 | 62.48 | 0.00 | 0.00 | 720.00 |
October | 128.07 | 75.34 | 52.73 | 114.54 | 89.74 | 0.00 | 0.00 | 744.00 |
November | 114.02 | 71.55 | 42.47 | 91.77 | 128.39 | 0.00 | 0.00 | 720.00 |
December | 121.36 | 79.56 | 41.79 | 80.78 | 194.77 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 143.69 | 76.73 | 66.96 | 123.78 | 101.85 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 114.02 | 31.93 | 41.79 | 80.78 | 34.86 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 199.07 | 134.45 | 89.55 | 167.04 | 199.05 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 131.26 | 91.31 | 39.96 | 96.23 | 163.96 | 0.00 | 0.00 | 744.00 |
February | 166.25 | 112.29 | 53.96 | 140.11 | 134.55 | 0.00 | 0.00 | 672.00 |
March | 146.56 | 92.78 | 53.78 | 121.16 | 109.71 | 0.00 | 0.00 | 744.00 |
April | 132.74 | 72.06 | 60.68 | 114.61 | 66.79 | 0.00 | 0.00 | 720.00 |
May | 111.57 | 38.13 | 73.44 | 100.96 | 36.65 | 0.00 | 0.00 | 744.00 |
June | 100.11 | 26.67 | 73.44 | 94.83 | 26.44 | 0.00 | 0.00 | 720.00 |
July | 109.45 | 34.66 | 74.79 | 107.26 | 26.99 | 0.00 | 0.00 | 744.00 |
August | 116.90 | 48.90 | 68.00 | 116.98 | 32.72 | 0.00 | 0.00 | 744.00 |
September | 125.26 | 66.73 | 58.53 | 123.05 | 49.68 | 0.00 | 0.00 | 720.00 |
October | 106.96 | 62.92 | 44.04 | 96.29 | 71.87 | 0.00 | 0.00 | 744.00 |
November | 95.23 | 59.75 | 35.47 | 77.20 | 103.38 | 0.00 | 0.00 | 720.00 |
December | 101.35 | 66.45 | 34.90 | 67.68 | 160.23 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 120.00 | 64.08 | 55.92 | 104.43 | 81.70 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 95.23 | 26.67 | 34.90 | 67.68 | 26.44 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 166.25 | 112.29 | 74.79 | 140.11 | 163.96 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 131.26 | 91.31 | 39.96 | 96.23 | 163.96 | 0.00 | 0.00 | 744.00 |
February | 166.25 | 112.29 | 53.96 | 140.11 | 134.55 | 0.00 | 0.00 | 672.00 |
March | 146.56 | 92.78 | 53.78 | 121.16 | 109.71 | 0.00 | 0.00 | 744.00 |
April | 132.74 | 72.06 | 60.68 | 114.61 | 66.79 | 0.00 | 0.00 | 720.00 |
May | 111.57 | 38.13 | 73.44 | 100.96 | 36.65 | 0.00 | 0.00 | 744.00 |
June | 100.11 | 26.67 | 73.44 | 94.83 | 26.44 | 0.00 | 0.00 | 720.00 |
July | 109.45 | 34.66 | 74.79 | 107.26 | 26.99 | 0.00 | 0.00 | 744.00 |
August | 116.90 | 48.90 | 68.00 | 116.98 | 32.72 | 0.00 | 0.00 | 744.00 |
September | 125.26 | 66.73 | 58.53 | 123.05 | 49.68 | 0.00 | 0.00 | 720.00 |
October | 106.96 | 62.92 | 44.04 | 96.29 | 71.87 | 0.00 | 0.00 | 744.00 |
November | 95.23 | 59.75 | 35.47 | 77.20 | 103.38 | 0.00 | 0.00 | 720.00 |
December | 101.35 | 66.45 | 34.90 | 67.68 | 160.23 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 120.00 | 64.08 | 55.92 | 104.43 | 81.70 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 95.23 | 26.67 | 34.90 | 67.68 | 26.44 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 166.25 | 112.29 | 74.79 | 140.11 | 163.96 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_DOOR
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 157.17 | 109.33 | 47.85 | 115.77 | 193.78 | 0.00 | 0.00 | 744.00 |
February | 199.07 | 134.45 | 64.61 | 168.34 | 159.09 | 0.00 | 0.00 | 672.00 |
March | 175.49 | 111.09 | 64.40 | 145.45 | 129.74 | 0.00 | 0.00 | 744.00 |
April | 158.94 | 86.28 | 72.66 | 137.50 | 79.08 | 0.00 | 0.00 | 720.00 |
May | 133.59 | 45.66 | 87.93 | 121.01 | 43.51 | 0.00 | 0.00 | 744.00 |
June | 119.86 | 31.93 | 87.93 | 113.54 | 31.42 | 0.00 | 0.00 | 720.00 |
July | 131.05 | 41.50 | 89.55 | 128.36 | 32.09 | 0.00 | 0.00 | 744.00 |
August | 139.97 | 58.55 | 81.43 | 140.04 | 38.88 | 0.00 | 0.00 | 744.00 |
September | 149.99 | 79.90 | 70.08 | 147.42 | 58.97 | 0.00 | 0.00 | 720.00 |
October | 128.07 | 75.34 | 52.73 | 115.47 | 85.20 | 0.00 | 0.00 | 744.00 |
November | 114.02 | 71.55 | 42.47 | 92.75 | 122.33 | 0.00 | 0.00 | 720.00 |
December | 121.36 | 79.56 | 41.79 | 81.49 | 189.33 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 143.69 | 76.73 | 66.96 | 125.27 | 96.70 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 114.02 | 31.93 | 41.79 | 81.49 | 31.42 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 199.07 | 134.45 | 89.55 | 168.34 | 193.78 | 0.00 | 0.00 | 744.00 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.351577E+09 | 0.244551E+09 | 0.107025E+09 | 0.255695E+09 | 0.466311E+09 |
February | 0.402201E+09 | 0.271655E+09 | 0.130547E+09 | 0.335964E+09 | 0.350121E+09 |
March | 0.392557E+09 | 0.248500E+09 | 0.144057E+09 | 0.320938E+09 | 0.323180E+09 |
April | 0.344062E+09 | 0.186770E+09 | 0.157293E+09 | 0.290168E+09 | 0.203941E+09 |
May | 0.298819E+09 | 0.102128E+09 | 0.196691E+09 | 0.258305E+09 | 0.122223E+09 |
June | 0.259473E+09 | 69129244.31 | 0.190344E+09 | 0.235318E+09 | 84665785.95 |
July | 0.293144E+09 | 92833301.21 | 0.200311E+09 | 0.282404E+09 | 80915341.77 |
August | 0.313101E+09 | 0.130960E+09 | 0.182141E+09 | 0.309263E+09 | 97386919.24 |
September | 0.324682E+09 | 0.172968E+09 | 0.151713E+09 | 0.313051E+09 | 0.145614E+09 |
October | 0.286482E+09 | 0.168527E+09 | 0.117954E+09 | 0.253110E+09 | 0.215752E+09 |
November | 0.246825E+09 | 0.154883E+09 | 91941667.14 | 0.196371E+09 | 0.297622E+09 |
December | 0.271462E+09 | 0.177973E+09 | 93488665.27 | 0.179567E+09 | 0.456574E+09 |
Annual Sum or Average | 0.378438E+10 | 0.202088E+10 | 0.176351E+10 | 0.323015E+10 | 0.284431E+10 |
Minimum of Months | 0.246825E+09 | 69129244.31 | 91941667.14 | 0.179567E+09 | 80915341.77 |
Maximum of Months | 0.402201E+09 | 0.271655E+09 | 0.200311E+09 | 0.335964E+09 | 0.466311E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.351577E+09 | 0.244551E+09 | 0.107025E+09 | 0.255695E+09 | 0.466311E+09 |
February | 0.402201E+09 | 0.271655E+09 | 0.130547E+09 | 0.335964E+09 | 0.350121E+09 |
March | 0.392557E+09 | 0.248500E+09 | 0.144057E+09 | 0.320938E+09 | 0.323180E+09 |
April | 0.344062E+09 | 0.186770E+09 | 0.157293E+09 | 0.290168E+09 | 0.203941E+09 |
May | 0.298819E+09 | 0.102128E+09 | 0.196691E+09 | 0.258305E+09 | 0.122223E+09 |
June | 0.259473E+09 | 69129244.31 | 0.190344E+09 | 0.235318E+09 | 84665785.95 |
July | 0.293144E+09 | 92833301.21 | 0.200311E+09 | 0.282404E+09 | 80915341.77 |
August | 0.313101E+09 | 0.130960E+09 | 0.182141E+09 | 0.309263E+09 | 97386919.24 |
September | 0.324682E+09 | 0.172968E+09 | 0.151713E+09 | 0.313051E+09 | 0.145614E+09 |
October | 0.286482E+09 | 0.168527E+09 | 0.117954E+09 | 0.253110E+09 | 0.215752E+09 |
November | 0.246825E+09 | 0.154883E+09 | 91941667.14 | 0.196371E+09 | 0.297622E+09 |
December | 0.271462E+09 | 0.177973E+09 | 93488665.27 | 0.179567E+09 | 0.456574E+09 |
Annual Sum or Average | 0.378438E+10 | 0.202088E+10 | 0.176351E+10 | 0.323015E+10 | 0.284431E+10 |
Minimum of Months | 0.246825E+09 | 69129244.31 | 91941667.14 | 0.179567E+09 | 80915341.77 |
Maximum of Months | 0.402201E+09 | 0.271655E+09 | 0.200311E+09 | 0.335964E+09 | 0.466311E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_3
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.351577E+09 | 0.244551E+09 | 0.107025E+09 | 0.255695E+09 | 0.466311E+09 |
February | 0.402201E+09 | 0.271655E+09 | 0.130547E+09 | 0.335964E+09 | 0.350121E+09 |
March | 0.392557E+09 | 0.248500E+09 | 0.144057E+09 | 0.320938E+09 | 0.323180E+09 |
April | 0.344062E+09 | 0.186770E+09 | 0.157293E+09 | 0.290168E+09 | 0.203941E+09 |
May | 0.298819E+09 | 0.102128E+09 | 0.196691E+09 | 0.258305E+09 | 0.122223E+09 |
June | 0.259473E+09 | 69129244.31 | 0.190344E+09 | 0.235318E+09 | 84665785.95 |
July | 0.293144E+09 | 92833301.21 | 0.200311E+09 | 0.282404E+09 | 80915341.77 |
August | 0.313101E+09 | 0.130960E+09 | 0.182141E+09 | 0.309263E+09 | 97386919.24 |
September | 0.324682E+09 | 0.172968E+09 | 0.151713E+09 | 0.313051E+09 | 0.145614E+09 |
October | 0.286482E+09 | 0.168527E+09 | 0.117954E+09 | 0.253110E+09 | 0.215752E+09 |
November | 0.246825E+09 | 0.154883E+09 | 91941667.14 | 0.196371E+09 | 0.297622E+09 |
December | 0.271462E+09 | 0.177973E+09 | 93488665.27 | 0.179567E+09 | 0.456574E+09 |
Annual Sum or Average | 0.378438E+10 | 0.202088E+10 | 0.176351E+10 | 0.323015E+10 | 0.284431E+10 |
Minimum of Months | 0.246825E+09 | 69129244.31 | 91941667.14 | 0.179567E+09 | 80915341.77 |
Maximum of Months | 0.402201E+09 | 0.271655E+09 | 0.200311E+09 | 0.335964E+09 | 0.466311E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_4
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.351577E+09 | 0.244551E+09 | 0.107025E+09 | 0.255695E+09 | 0.466311E+09 |
February | 0.402201E+09 | 0.271655E+09 | 0.130547E+09 | 0.335964E+09 | 0.350121E+09 |
March | 0.392557E+09 | 0.248500E+09 | 0.144057E+09 | 0.320938E+09 | 0.323180E+09 |
April | 0.344062E+09 | 0.186770E+09 | 0.157293E+09 | 0.290168E+09 | 0.203941E+09 |
May | 0.298819E+09 | 0.102128E+09 | 0.196691E+09 | 0.258305E+09 | 0.122223E+09 |
June | 0.259473E+09 | 69129244.31 | 0.190344E+09 | 0.235318E+09 | 84665785.95 |
July | 0.293144E+09 | 92833301.21 | 0.200311E+09 | 0.282404E+09 | 80915341.77 |
August | 0.313101E+09 | 0.130960E+09 | 0.182141E+09 | 0.309263E+09 | 97386919.24 |
September | 0.324682E+09 | 0.172968E+09 | 0.151713E+09 | 0.313051E+09 | 0.145614E+09 |
October | 0.286482E+09 | 0.168527E+09 | 0.117954E+09 | 0.253110E+09 | 0.215752E+09 |
November | 0.246825E+09 | 0.154883E+09 | 91941667.14 | 0.196371E+09 | 0.297622E+09 |
December | 0.271462E+09 | 0.177973E+09 | 93488665.27 | 0.179567E+09 | 0.456574E+09 |
Annual Sum or Average | 0.378438E+10 | 0.202088E+10 | 0.176351E+10 | 0.323015E+10 | 0.284431E+10 |
Minimum of Months | 0.246825E+09 | 69129244.31 | 91941667.14 | 0.179567E+09 | 80915341.77 |
Maximum of Months | 0.402201E+09 | 0.271655E+09 | 0.200311E+09 | 0.335964E+09 | 0.466311E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_DOOR_1
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.423280E+09 | 0.294427E+09 | 0.128853E+09 | 0.309149E+09 | 0.554670E+09 |
February | 0.484229E+09 | 0.327058E+09 | 0.157172E+09 | 0.405671E+09 | 0.416652E+09 |
March | 0.472618E+09 | 0.299181E+09 | 0.173437E+09 | 0.387220E+09 | 0.384719E+09 |
April | 0.414233E+09 | 0.224861E+09 | 0.189372E+09 | 0.349847E+09 | 0.243048E+09 |
May | 0.359762E+09 | 0.122956E+09 | 0.236806E+09 | 0.311152E+09 | 0.145962E+09 |
June | 0.312392E+09 | 83227971.77 | 0.229164E+09 | 0.283200E+09 | 0.101232E+09 |
July | 0.352930E+09 | 0.111766E+09 | 0.241164E+09 | 0.339687E+09 | 96830149.12 |
August | 0.376957E+09 | 0.157669E+09 | 0.219288E+09 | 0.372147E+09 | 0.116441E+09 |
September | 0.390900E+09 | 0.208245E+09 | 0.182655E+09 | 0.376997E+09 | 0.173938E+09 |
October | 0.344909E+09 | 0.202898E+09 | 0.142011E+09 | 0.305038E+09 | 0.257405E+09 |
November | 0.297164E+09 | 0.186471E+09 | 0.110693E+09 | 0.237070E+09 | 0.354471E+09 |
December | 0.326826E+09 | 0.214270E+09 | 0.112555E+09 | 0.217265E+09 | 0.542995E+09 |
Annual Sum or Average | 0.455620E+10 | 0.243303E+10 | 0.212317E+10 | 0.389444E+10 | 0.338836E+10 |
Minimum of Months | 0.297164E+09 | 83227971.77 | 0.110693E+09 | 0.217265E+09 | 96830149.12 |
Maximum of Months | 0.484229E+09 | 0.327058E+09 | 0.241164E+09 | 0.405671E+09 | 0.554670E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_DOOR_2
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.423280E+09 | 0.294427E+09 | 0.128853E+09 | 0.309149E+09 | 0.554670E+09 |
February | 0.484229E+09 | 0.327058E+09 | 0.157172E+09 | 0.405671E+09 | 0.416652E+09 |
March | 0.472618E+09 | 0.299181E+09 | 0.173437E+09 | 0.387220E+09 | 0.384719E+09 |
April | 0.414233E+09 | 0.224861E+09 | 0.189372E+09 | 0.349847E+09 | 0.243048E+09 |
May | 0.359762E+09 | 0.122956E+09 | 0.236806E+09 | 0.311152E+09 | 0.145962E+09 |
June | 0.312392E+09 | 83227971.77 | 0.229164E+09 | 0.283200E+09 | 0.101232E+09 |
July | 0.352930E+09 | 0.111766E+09 | 0.241164E+09 | 0.339687E+09 | 96830149.12 |
August | 0.376957E+09 | 0.157669E+09 | 0.219288E+09 | 0.372147E+09 | 0.116441E+09 |
September | 0.390900E+09 | 0.208245E+09 | 0.182655E+09 | 0.376997E+09 | 0.173938E+09 |
October | 0.344909E+09 | 0.202898E+09 | 0.142011E+09 | 0.305038E+09 | 0.257405E+09 |
November | 0.297164E+09 | 0.186471E+09 | 0.110693E+09 | 0.237070E+09 | 0.354471E+09 |
December | 0.326826E+09 | 0.214270E+09 | 0.112555E+09 | 0.217265E+09 | 0.542995E+09 |
Annual Sum or Average | 0.455620E+10 | 0.243303E+10 | 0.212317E+10 | 0.389444E+10 | 0.338836E+10 |
Minimum of Months | 0.297164E+09 | 83227971.77 | 0.110693E+09 | 0.217265E+09 | 96830149.12 |
Maximum of Months | 0.484229E+09 | 0.327058E+09 | 0.241164E+09 | 0.405671E+09 | 0.554670E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.351577E+09 | 0.244551E+09 | 0.107025E+09 | 0.252530E+09 | 0.479419E+09 |
February | 0.402201E+09 | 0.271655E+09 | 0.130547E+09 | 0.332127E+09 | 0.362587E+09 |
March | 0.392557E+09 | 0.248500E+09 | 0.144057E+09 | 0.317289E+09 | 0.338145E+09 |
April | 0.344062E+09 | 0.186770E+09 | 0.157293E+09 | 0.286166E+09 | 0.218050E+09 |
May | 0.298819E+09 | 0.102128E+09 | 0.196691E+09 | 0.254479E+09 | 0.128747E+09 |
June | 0.259473E+09 | 69129244.31 | 0.190344E+09 | 0.232790E+09 | 87873680.32 |
July | 0.293144E+09 | 92833301.21 | 0.200311E+09 | 0.281280E+09 | 82475524.42 |
August | 0.313101E+09 | 0.130960E+09 | 0.182141E+09 | 0.308311E+09 | 99032864.90 |
September | 0.324682E+09 | 0.172968E+09 | 0.151713E+09 | 0.311243E+09 | 0.149229E+09 |
October | 0.286482E+09 | 0.168527E+09 | 0.117954E+09 | 0.251033E+09 | 0.225639E+09 |
November | 0.246825E+09 | 0.154883E+09 | 91941667.14 | 0.194064E+09 | 0.309642E+09 |
December | 0.271462E+09 | 0.177973E+09 | 93488665.27 | 0.177044E+09 | 0.470844E+09 |
Annual Sum or Average | 0.378438E+10 | 0.202088E+10 | 0.176351E+10 | 0.319835E+10 | 0.295168E+10 |
Minimum of Months | 0.246825E+09 | 69129244.31 | 91941667.14 | 0.177044E+09 | 82475524.42 |
Maximum of Months | 0.402201E+09 | 0.271655E+09 | 0.200311E+09 | 0.332127E+09 | 0.479419E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.351577E+09 | 0.244551E+09 | 0.107025E+09 | 0.252530E+09 | 0.479419E+09 |
February | 0.402201E+09 | 0.271655E+09 | 0.130547E+09 | 0.332127E+09 | 0.362587E+09 |
March | 0.392557E+09 | 0.248500E+09 | 0.144057E+09 | 0.317289E+09 | 0.338145E+09 |
April | 0.344062E+09 | 0.186770E+09 | 0.157293E+09 | 0.286166E+09 | 0.218050E+09 |
May | 0.298819E+09 | 0.102128E+09 | 0.196691E+09 | 0.254479E+09 | 0.128747E+09 |
June | 0.259473E+09 | 69129244.31 | 0.190344E+09 | 0.232790E+09 | 87873680.32 |
July | 0.293144E+09 | 92833301.21 | 0.200311E+09 | 0.281280E+09 | 82475524.42 |
August | 0.313101E+09 | 0.130960E+09 | 0.182141E+09 | 0.308311E+09 | 99032864.90 |
September | 0.324682E+09 | 0.172968E+09 | 0.151713E+09 | 0.311243E+09 | 0.149229E+09 |
October | 0.286482E+09 | 0.168527E+09 | 0.117954E+09 | 0.251033E+09 | 0.225639E+09 |
November | 0.246825E+09 | 0.154883E+09 | 91941667.14 | 0.194064E+09 | 0.309642E+09 |
December | 0.271462E+09 | 0.177973E+09 | 93488665.27 | 0.177044E+09 | 0.470844E+09 |
Annual Sum or Average | 0.378438E+10 | 0.202088E+10 | 0.176351E+10 | 0.319835E+10 | 0.295168E+10 |
Minimum of Months | 0.246825E+09 | 69129244.31 | 91941667.14 | 0.177044E+09 | 82475524.42 |
Maximum of Months | 0.402201E+09 | 0.271655E+09 | 0.200311E+09 | 0.332127E+09 | 0.479419E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_DOOR
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.423280E+09 | 0.294427E+09 | 0.128853E+09 | 0.305357E+09 | 0.570191E+09 |
February | 0.484229E+09 | 0.327058E+09 | 0.157172E+09 | 0.401083E+09 | 0.431406E+09 |
March | 0.472618E+09 | 0.299181E+09 | 0.173437E+09 | 0.382822E+09 | 0.402467E+09 |
April | 0.414233E+09 | 0.224861E+09 | 0.189372E+09 | 0.345021E+09 | 0.259731E+09 |
May | 0.359762E+09 | 0.122956E+09 | 0.236806E+09 | 0.306567E+09 | 0.153670E+09 |
June | 0.312392E+09 | 83227971.77 | 0.229164E+09 | 0.280168E+09 | 0.105026E+09 |
July | 0.352930E+09 | 0.111766E+09 | 0.241164E+09 | 0.338348E+09 | 98664921.55 |
August | 0.376957E+09 | 0.157669E+09 | 0.219288E+09 | 0.371029E+09 | 0.118358E+09 |
September | 0.390900E+09 | 0.208245E+09 | 0.182655E+09 | 0.374872E+09 | 0.178163E+09 |
October | 0.344909E+09 | 0.202898E+09 | 0.142011E+09 | 0.302567E+09 | 0.269021E+09 |
November | 0.297164E+09 | 0.186471E+09 | 0.110693E+09 | 0.234318E+09 | 0.368620E+09 |
December | 0.326826E+09 | 0.214270E+09 | 0.112555E+09 | 0.214247E+09 | 0.559874E+09 |
Annual Sum or Average | 0.455620E+10 | 0.243303E+10 | 0.212317E+10 | 0.385640E+10 | 0.351519E+10 |
Minimum of Months | 0.297164E+09 | 83227971.77 | 0.110693E+09 | 0.214247E+09 | 98664921.55 |
Maximum of Months | 0.484229E+09 | 0.327058E+09 | 0.241164E+09 | 0.401083E+09 | 0.570191E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.351577E+09 | 0.244551E+09 | 0.107025E+09 | 0.253494E+09 | 0.465534E+09 |
February | 0.402201E+09 | 0.271655E+09 | 0.130547E+09 | 0.333278E+09 | 0.351236E+09 |
March | 0.392557E+09 | 0.248500E+09 | 0.144057E+09 | 0.318232E+09 | 0.327340E+09 |
April | 0.344062E+09 | 0.186770E+09 | 0.157293E+09 | 0.287629E+09 | 0.208082E+09 |
May | 0.298819E+09 | 0.102128E+09 | 0.196691E+09 | 0.256409E+09 | 0.124756E+09 |
June | 0.259473E+09 | 69129244.31 | 0.190344E+09 | 0.233781E+09 | 87781252.70 |
July | 0.293144E+09 | 92833301.21 | 0.200311E+09 | 0.280978E+09 | 85345725.64 |
August | 0.313101E+09 | 0.130960E+09 | 0.182141E+09 | 0.308359E+09 | 0.100970E+09 |
September | 0.324682E+09 | 0.172968E+09 | 0.151713E+09 | 0.312552E+09 | 0.146139E+09 |
October | 0.286482E+09 | 0.168527E+09 | 0.117954E+09 | 0.252571E+09 | 0.215660E+09 |
November | 0.246825E+09 | 0.154883E+09 | 91941667.14 | 0.195132E+09 | 0.297663E+09 |
December | 0.271462E+09 | 0.177973E+09 | 93488665.27 | 0.177782E+09 | 0.456736E+09 |
Annual Sum or Average | 0.378438E+10 | 0.202088E+10 | 0.176351E+10 | 0.321020E+10 | 0.286724E+10 |
Minimum of Months | 0.246825E+09 | 69129244.31 | 91941667.14 | 0.177782E+09 | 85345725.64 |
Maximum of Months | 0.402201E+09 | 0.271655E+09 | 0.200311E+09 | 0.333278E+09 | 0.465534E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.351577E+09 | 0.244551E+09 | 0.107025E+09 | 0.253494E+09 | 0.465534E+09 |
February | 0.402201E+09 | 0.271655E+09 | 0.130547E+09 | 0.333278E+09 | 0.351236E+09 |
March | 0.392557E+09 | 0.248500E+09 | 0.144057E+09 | 0.318232E+09 | 0.327340E+09 |
April | 0.344062E+09 | 0.186770E+09 | 0.157293E+09 | 0.287629E+09 | 0.208082E+09 |
May | 0.298819E+09 | 0.102128E+09 | 0.196691E+09 | 0.256409E+09 | 0.124756E+09 |
June | 0.259473E+09 | 69129244.31 | 0.190344E+09 | 0.233781E+09 | 87781252.70 |
July | 0.293144E+09 | 92833301.21 | 0.200311E+09 | 0.280978E+09 | 85345725.64 |
August | 0.313101E+09 | 0.130960E+09 | 0.182141E+09 | 0.308359E+09 | 0.100970E+09 |
September | 0.324682E+09 | 0.172968E+09 | 0.151713E+09 | 0.312552E+09 | 0.146139E+09 |
October | 0.286482E+09 | 0.168527E+09 | 0.117954E+09 | 0.252571E+09 | 0.215660E+09 |
November | 0.246825E+09 | 0.154883E+09 | 91941667.14 | 0.195132E+09 | 0.297663E+09 |
December | 0.271462E+09 | 0.177973E+09 | 93488665.27 | 0.177782E+09 | 0.456736E+09 |
Annual Sum or Average | 0.378438E+10 | 0.202088E+10 | 0.176351E+10 | 0.321020E+10 | 0.286724E+10 |
Minimum of Months | 0.246825E+09 | 69129244.31 | 91941667.14 | 0.177782E+09 | 85345725.64 |
Maximum of Months | 0.402201E+09 | 0.271655E+09 | 0.200311E+09 | 0.333278E+09 | 0.465534E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_DOOR
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.420967E+09 | 0.292818E+09 | 0.128149E+09 | 0.304882E+09 | 0.550576E+09 |
February | 0.481583E+09 | 0.325271E+09 | 0.156313E+09 | 0.400301E+09 | 0.415566E+09 |
March | 0.470035E+09 | 0.297546E+09 | 0.172489E+09 | 0.381894E+09 | 0.387422E+09 |
April | 0.411970E+09 | 0.223632E+09 | 0.188338E+09 | 0.344924E+09 | 0.246488E+09 |
May | 0.357796E+09 | 0.122284E+09 | 0.235512E+09 | 0.307232E+09 | 0.148043E+09 |
June | 0.310685E+09 | 82773174.11 | 0.227912E+09 | 0.279856E+09 | 0.104249E+09 |
July | 0.351002E+09 | 0.111156E+09 | 0.239846E+09 | 0.336180E+09 | 0.101413E+09 |
August | 0.374897E+09 | 0.156808E+09 | 0.218090E+09 | 0.369096E+09 | 0.119903E+09 |
September | 0.388764E+09 | 0.207107E+09 | 0.181657E+09 | 0.374414E+09 | 0.173450E+09 |
October | 0.343024E+09 | 0.201789E+09 | 0.141235E+09 | 0.302787E+09 | 0.255694E+09 |
November | 0.295541E+09 | 0.185452E+09 | 0.110088E+09 | 0.234345E+09 | 0.352375E+09 |
December | 0.325040E+09 | 0.213099E+09 | 0.111940E+09 | 0.213992E+09 | 0.540043E+09 |
Annual Sum or Average | 0.453130E+10 | 0.241974E+10 | 0.211157E+10 | 0.384990E+10 | 0.339522E+10 |
Minimum of Months | 0.295541E+09 | 82773174.11 | 0.110088E+09 | 0.213992E+09 | 0.101413E+09 |
Maximum of Months | 0.481583E+09 | 0.325271E+09 | 0.239846E+09 | 0.400301E+09 | 0.550576E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.351577E+09 | 0.244551E+09 | 0.107025E+09 | 0.253929E+09 | 0.461531E+09 |
February | 0.402201E+09 | 0.271655E+09 | 0.130547E+09 | 0.333872E+09 | 0.347524E+09 |
March | 0.392557E+09 | 0.248500E+09 | 0.144057E+09 | 0.318793E+09 | 0.323471E+09 |
April | 0.344062E+09 | 0.186770E+09 | 0.157293E+09 | 0.288496E+09 | 0.204313E+09 |
May | 0.298819E+09 | 0.102128E+09 | 0.196691E+09 | 0.257556E+09 | 0.122215E+09 |
June | 0.259473E+09 | 69129244.31 | 0.190344E+09 | 0.234577E+09 | 86360394.26 |
July | 0.293144E+09 | 92833301.21 | 0.200311E+09 | 0.281287E+09 | 84782088.34 |
August | 0.313101E+09 | 0.130960E+09 | 0.182141E+09 | 0.308675E+09 | 0.100184E+09 |
September | 0.324682E+09 | 0.172968E+09 | 0.151713E+09 | 0.313319E+09 | 0.143919E+09 |
October | 0.286482E+09 | 0.168527E+09 | 0.117954E+09 | 0.253332E+09 | 0.211982E+09 |
November | 0.246825E+09 | 0.154883E+09 | 91941667.14 | 0.195684E+09 | 0.293508E+09 |
December | 0.271462E+09 | 0.177973E+09 | 93488665.27 | 0.178134E+09 | 0.452494E+09 |
Annual Sum or Average | 0.378438E+10 | 0.202088E+10 | 0.176351E+10 | 0.321765E+10 | 0.283228E+10 |
Minimum of Months | 0.246825E+09 | 69129244.31 | 91941667.14 | 0.178134E+09 | 84782088.34 |
Maximum of Months | 0.402201E+09 | 0.271655E+09 | 0.200311E+09 | 0.333872E+09 | 0.461531E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.351577E+09 | 0.244551E+09 | 0.107025E+09 | 0.253929E+09 | 0.461531E+09 |
February | 0.402201E+09 | 0.271655E+09 | 0.130547E+09 | 0.333872E+09 | 0.347524E+09 |
March | 0.392557E+09 | 0.248500E+09 | 0.144057E+09 | 0.318793E+09 | 0.323471E+09 |
April | 0.344062E+09 | 0.186770E+09 | 0.157293E+09 | 0.288496E+09 | 0.204313E+09 |
May | 0.298819E+09 | 0.102128E+09 | 0.196691E+09 | 0.257556E+09 | 0.122215E+09 |
June | 0.259473E+09 | 69129244.31 | 0.190344E+09 | 0.234577E+09 | 86360394.26 |
July | 0.293144E+09 | 92833301.21 | 0.200311E+09 | 0.281287E+09 | 84782088.34 |
August | 0.313101E+09 | 0.130960E+09 | 0.182141E+09 | 0.308675E+09 | 0.100184E+09 |
September | 0.324682E+09 | 0.172968E+09 | 0.151713E+09 | 0.313319E+09 | 0.143919E+09 |
October | 0.286482E+09 | 0.168527E+09 | 0.117954E+09 | 0.253332E+09 | 0.211982E+09 |
November | 0.246825E+09 | 0.154883E+09 | 91941667.14 | 0.195684E+09 | 0.293508E+09 |
December | 0.271462E+09 | 0.177973E+09 | 93488665.27 | 0.178134E+09 | 0.452494E+09 |
Annual Sum or Average | 0.378438E+10 | 0.202088E+10 | 0.176351E+10 | 0.321765E+10 | 0.283228E+10 |
Minimum of Months | 0.246825E+09 | 69129244.31 | 91941667.14 | 0.178134E+09 | 84782088.34 |
Maximum of Months | 0.402201E+09 | 0.271655E+09 | 0.200311E+09 | 0.333872E+09 | 0.461531E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_DOOR
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.420967E+09 | 0.292818E+09 | 0.128149E+09 | 0.305415E+09 | 0.545794E+09 |
February | 0.481583E+09 | 0.325271E+09 | 0.156313E+09 | 0.401024E+09 | 0.411143E+09 |
March | 0.470035E+09 | 0.297546E+09 | 0.172489E+09 | 0.382579E+09 | 0.382813E+09 |
April | 0.411970E+09 | 0.223632E+09 | 0.188338E+09 | 0.345973E+09 | 0.242009E+09 |
May | 0.357796E+09 | 0.122284E+09 | 0.235512E+09 | 0.308610E+09 | 0.145025E+09 |
June | 0.310685E+09 | 82773174.11 | 0.227912E+09 | 0.280815E+09 | 0.102566E+09 |
July | 0.351002E+09 | 0.111156E+09 | 0.239846E+09 | 0.336553E+09 | 0.100745E+09 |
August | 0.374897E+09 | 0.156808E+09 | 0.218090E+09 | 0.369478E+09 | 0.118970E+09 |
September | 0.388764E+09 | 0.207107E+09 | 0.181657E+09 | 0.375335E+09 | 0.170811E+09 |
October | 0.343024E+09 | 0.201789E+09 | 0.141235E+09 | 0.303706E+09 | 0.251317E+09 |
November | 0.295541E+09 | 0.185452E+09 | 0.110088E+09 | 0.235018E+09 | 0.347427E+09 |
December | 0.325040E+09 | 0.213099E+09 | 0.111940E+09 | 0.214423E+09 | 0.534979E+09 |
Annual Sum or Average | 0.453130E+10 | 0.241974E+10 | 0.211157E+10 | 0.385893E+10 | 0.335360E+10 |
Minimum of Months | 0.295541E+09 | 82773174.11 | 0.110088E+09 | 0.214423E+09 | 0.100745E+09 |
Maximum of Months | 0.481583E+09 | 0.325271E+09 | 0.239846E+09 | 0.401024E+09 | 0.545794E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.351577E+09 | 0.244551E+09 | 0.107025E+09 | 0.254266E+09 | 0.459543E+09 |
February | 0.402201E+09 | 0.271655E+09 | 0.130547E+09 | 0.334341E+09 | 0.345499E+09 |
March | 0.392557E+09 | 0.248500E+09 | 0.144057E+09 | 0.319264E+09 | 0.321162E+09 |
April | 0.344062E+09 | 0.186770E+09 | 0.157293E+09 | 0.289192E+09 | 0.202049E+09 |
May | 0.298819E+09 | 0.102128E+09 | 0.196691E+09 | 0.258535E+09 | 0.120402E+09 |
June | 0.259473E+09 | 69129244.31 | 0.190344E+09 | 0.235345E+09 | 85044676.36 |
July | 0.293144E+09 | 92833301.21 | 0.200311E+09 | 0.281688E+09 | 83871857.47 |
August | 0.313101E+09 | 0.130960E+09 | 0.182141E+09 | 0.309041E+09 | 99178060.08 |
September | 0.324682E+09 | 0.172968E+09 | 0.151713E+09 | 0.313939E+09 | 0.142376E+09 |
October | 0.286482E+09 | 0.168527E+09 | 0.117954E+09 | 0.253839E+09 | 0.210064E+09 |
November | 0.246825E+09 | 0.154883E+09 | 91941667.14 | 0.196118E+09 | 0.291153E+09 |
December | 0.271462E+09 | 0.177973E+09 | 93488665.27 | 0.178423E+09 | 0.450273E+09 |
Annual Sum or Average | 0.378438E+10 | 0.202088E+10 | 0.176351E+10 | 0.322399E+10 | 0.281062E+10 |
Minimum of Months | 0.246825E+09 | 69129244.31 | 91941667.14 | 0.178423E+09 | 83871857.47 |
Maximum of Months | 0.402201E+09 | 0.271655E+09 | 0.200311E+09 | 0.334341E+09 | 0.459543E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.351577E+09 | 0.244551E+09 | 0.107025E+09 | 0.254266E+09 | 0.459543E+09 |
February | 0.402201E+09 | 0.271655E+09 | 0.130547E+09 | 0.334341E+09 | 0.345499E+09 |
March | 0.392557E+09 | 0.248500E+09 | 0.144057E+09 | 0.319264E+09 | 0.321162E+09 |
April | 0.344062E+09 | 0.186770E+09 | 0.157293E+09 | 0.289192E+09 | 0.202049E+09 |
May | 0.298819E+09 | 0.102128E+09 | 0.196691E+09 | 0.258535E+09 | 0.120402E+09 |
June | 0.259473E+09 | 69129244.31 | 0.190344E+09 | 0.235345E+09 | 85044676.36 |
July | 0.293144E+09 | 92833301.21 | 0.200311E+09 | 0.281688E+09 | 83871857.47 |
August | 0.313101E+09 | 0.130960E+09 | 0.182141E+09 | 0.309041E+09 | 99178060.08 |
September | 0.324682E+09 | 0.172968E+09 | 0.151713E+09 | 0.313939E+09 | 0.142376E+09 |
October | 0.286482E+09 | 0.168527E+09 | 0.117954E+09 | 0.253839E+09 | 0.210064E+09 |
November | 0.246825E+09 | 0.154883E+09 | 91941667.14 | 0.196118E+09 | 0.291153E+09 |
December | 0.271462E+09 | 0.177973E+09 | 93488665.27 | 0.178423E+09 | 0.450273E+09 |
Annual Sum or Average | 0.378438E+10 | 0.202088E+10 | 0.176351E+10 | 0.322399E+10 | 0.281062E+10 |
Minimum of Months | 0.246825E+09 | 69129244.31 | 91941667.14 | 0.178423E+09 | 83871857.47 |
Maximum of Months | 0.402201E+09 | 0.271655E+09 | 0.200311E+09 | 0.334341E+09 | 0.459543E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_DOOR
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.420967E+09 | 0.292818E+09 | 0.128149E+09 | 0.305826E+09 | 0.543419E+09 |
February | 0.481583E+09 | 0.325271E+09 | 0.156313E+09 | 0.401598E+09 | 0.408731E+09 |
March | 0.470035E+09 | 0.297546E+09 | 0.172489E+09 | 0.383154E+09 | 0.380060E+09 |
April | 0.411970E+09 | 0.223632E+09 | 0.188338E+09 | 0.346816E+09 | 0.239322E+09 |
May | 0.357796E+09 | 0.122284E+09 | 0.235512E+09 | 0.309783E+09 | 0.142879E+09 |
June | 0.310685E+09 | 82773174.11 | 0.227912E+09 | 0.281739E+09 | 0.101012E+09 |
July | 0.351002E+09 | 0.111156E+09 | 0.239846E+09 | 0.337037E+09 | 99670765.00 |
August | 0.374897E+09 | 0.156808E+09 | 0.218090E+09 | 0.369919E+09 | 0.117781E+09 |
September | 0.388764E+09 | 0.207107E+09 | 0.181657E+09 | 0.376077E+09 | 0.168983E+09 |
October | 0.343024E+09 | 0.201789E+09 | 0.141235E+09 | 0.304321E+09 | 0.249039E+09 |
November | 0.295541E+09 | 0.185452E+09 | 0.110088E+09 | 0.235548E+09 | 0.344625E+09 |
December | 0.325040E+09 | 0.213099E+09 | 0.111940E+09 | 0.214776E+09 | 0.532326E+09 |
Annual Sum or Average | 0.453130E+10 | 0.241974E+10 | 0.211157E+10 | 0.386659E+10 | 0.332785E+10 |
Minimum of Months | 0.295541E+09 | 82773174.11 | 0.110088E+09 | 0.214776E+09 | 99670765.00 |
Maximum of Months | 0.481583E+09 | 0.325271E+09 | 0.239846E+09 | 0.401598E+09 | 0.543419E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.351577E+09 | 0.244551E+09 | 0.107025E+09 | 0.256701E+09 | 0.449912E+09 |
February | 0.402201E+09 | 0.271655E+09 | 0.130547E+09 | 0.337330E+09 | 0.337447E+09 |
March | 0.392557E+09 | 0.248500E+09 | 0.144057E+09 | 0.321655E+09 | 0.312647E+09 |
April | 0.344062E+09 | 0.186770E+09 | 0.157293E+09 | 0.291551E+09 | 0.195810E+09 |
May | 0.298819E+09 | 0.102128E+09 | 0.196691E+09 | 0.260735E+09 | 0.116482E+09 |
June | 0.259473E+09 | 69129244.31 | 0.190344E+09 | 0.236859E+09 | 81944309.82 |
July | 0.293144E+09 | 92833301.21 | 0.200311E+09 | 0.282210E+09 | 81315344.66 |
August | 0.313101E+09 | 0.130960E+09 | 0.182141E+09 | 0.309942E+09 | 96515853.88 |
September | 0.324682E+09 | 0.172968E+09 | 0.151713E+09 | 0.315656E+09 | 0.139434E+09 |
October | 0.286482E+09 | 0.168527E+09 | 0.117954E+09 | 0.255575E+09 | 0.205627E+09 |
November | 0.246825E+09 | 0.154883E+09 | 91941667.14 | 0.198181E+09 | 0.283382E+09 |
December | 0.271462E+09 | 0.177973E+09 | 93488665.27 | 0.180530E+09 | 0.440304E+09 |
Annual Sum or Average | 0.378438E+10 | 0.202088E+10 | 0.176351E+10 | 0.324692E+10 | 0.274082E+10 |
Minimum of Months | 0.246825E+09 | 69129244.31 | 91941667.14 | 0.180530E+09 | 81315344.66 |
Maximum of Months | 0.402201E+09 | 0.271655E+09 | 0.200311E+09 | 0.337330E+09 | 0.449912E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.351577E+09 | 0.244551E+09 | 0.107025E+09 | 0.256701E+09 | 0.449912E+09 |
February | 0.402201E+09 | 0.271655E+09 | 0.130547E+09 | 0.337330E+09 | 0.337447E+09 |
March | 0.392557E+09 | 0.248500E+09 | 0.144057E+09 | 0.321655E+09 | 0.312647E+09 |
April | 0.344062E+09 | 0.186770E+09 | 0.157293E+09 | 0.291551E+09 | 0.195810E+09 |
May | 0.298819E+09 | 0.102128E+09 | 0.196691E+09 | 0.260735E+09 | 0.116482E+09 |
June | 0.259473E+09 | 69129244.31 | 0.190344E+09 | 0.236859E+09 | 81944309.82 |
July | 0.293144E+09 | 92833301.21 | 0.200311E+09 | 0.282210E+09 | 81315344.66 |
August | 0.313101E+09 | 0.130960E+09 | 0.182141E+09 | 0.309942E+09 | 96515853.88 |
September | 0.324682E+09 | 0.172968E+09 | 0.151713E+09 | 0.315656E+09 | 0.139434E+09 |
October | 0.286482E+09 | 0.168527E+09 | 0.117954E+09 | 0.255575E+09 | 0.205627E+09 |
November | 0.246825E+09 | 0.154883E+09 | 91941667.14 | 0.198181E+09 | 0.283382E+09 |
December | 0.271462E+09 | 0.177973E+09 | 93488665.27 | 0.180530E+09 | 0.440304E+09 |
Annual Sum or Average | 0.378438E+10 | 0.202088E+10 | 0.176351E+10 | 0.324692E+10 | 0.274082E+10 |
Minimum of Months | 0.246825E+09 | 69129244.31 | 91941667.14 | 0.180530E+09 | 81315344.66 |
Maximum of Months | 0.402201E+09 | 0.271655E+09 | 0.200311E+09 | 0.337330E+09 | 0.449912E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_3
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.351577E+09 | 0.244551E+09 | 0.107025E+09 | 0.256701E+09 | 0.449912E+09 |
February | 0.402201E+09 | 0.271655E+09 | 0.130547E+09 | 0.337330E+09 | 0.337447E+09 |
March | 0.392557E+09 | 0.248500E+09 | 0.144057E+09 | 0.321655E+09 | 0.312647E+09 |
April | 0.344062E+09 | 0.186770E+09 | 0.157293E+09 | 0.291551E+09 | 0.195810E+09 |
May | 0.298819E+09 | 0.102128E+09 | 0.196691E+09 | 0.260735E+09 | 0.116482E+09 |
June | 0.259473E+09 | 69129244.31 | 0.190344E+09 | 0.236859E+09 | 81944309.82 |
July | 0.293144E+09 | 92833301.21 | 0.200311E+09 | 0.282210E+09 | 81315344.66 |
August | 0.313101E+09 | 0.130960E+09 | 0.182141E+09 | 0.309942E+09 | 96515853.88 |
September | 0.324682E+09 | 0.172968E+09 | 0.151713E+09 | 0.315656E+09 | 0.139434E+09 |
October | 0.286482E+09 | 0.168527E+09 | 0.117954E+09 | 0.255575E+09 | 0.205627E+09 |
November | 0.246825E+09 | 0.154883E+09 | 91941667.14 | 0.198181E+09 | 0.283382E+09 |
December | 0.271462E+09 | 0.177973E+09 | 93488665.27 | 0.180530E+09 | 0.440304E+09 |
Annual Sum or Average | 0.378438E+10 | 0.202088E+10 | 0.176351E+10 | 0.324692E+10 | 0.274082E+10 |
Minimum of Months | 0.246825E+09 | 69129244.31 | 91941667.14 | 0.180530E+09 | 81315344.66 |
Maximum of Months | 0.402201E+09 | 0.271655E+09 | 0.200311E+09 | 0.337330E+09 | 0.449912E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_4
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.351577E+09 | 0.244551E+09 | 0.107025E+09 | 0.256701E+09 | 0.449912E+09 |
February | 0.402201E+09 | 0.271655E+09 | 0.130547E+09 | 0.337330E+09 | 0.337447E+09 |
March | 0.392557E+09 | 0.248500E+09 | 0.144057E+09 | 0.321655E+09 | 0.312647E+09 |
April | 0.344062E+09 | 0.186770E+09 | 0.157293E+09 | 0.291551E+09 | 0.195810E+09 |
May | 0.298819E+09 | 0.102128E+09 | 0.196691E+09 | 0.260735E+09 | 0.116482E+09 |
June | 0.259473E+09 | 69129244.31 | 0.190344E+09 | 0.236859E+09 | 81944309.82 |
July | 0.293144E+09 | 92833301.21 | 0.200311E+09 | 0.282210E+09 | 81315344.66 |
August | 0.313101E+09 | 0.130960E+09 | 0.182141E+09 | 0.309942E+09 | 96515853.88 |
September | 0.324682E+09 | 0.172968E+09 | 0.151713E+09 | 0.315656E+09 | 0.139434E+09 |
October | 0.286482E+09 | 0.168527E+09 | 0.117954E+09 | 0.255575E+09 | 0.205627E+09 |
November | 0.246825E+09 | 0.154883E+09 | 91941667.14 | 0.198181E+09 | 0.283382E+09 |
December | 0.271462E+09 | 0.177973E+09 | 93488665.27 | 0.180530E+09 | 0.440304E+09 |
Annual Sum or Average | 0.378438E+10 | 0.202088E+10 | 0.176351E+10 | 0.324692E+10 | 0.274082E+10 |
Minimum of Months | 0.246825E+09 | 69129244.31 | 91941667.14 | 0.180530E+09 | 81315344.66 |
Maximum of Months | 0.402201E+09 | 0.271655E+09 | 0.200311E+09 | 0.337330E+09 | 0.449912E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_DOOR_1
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.420967E+09 | 0.292818E+09 | 0.128149E+09 | 0.308726E+09 | 0.532140E+09 |
February | 0.481583E+09 | 0.325271E+09 | 0.156313E+09 | 0.405149E+09 | 0.399303E+09 |
March | 0.470035E+09 | 0.297546E+09 | 0.172489E+09 | 0.386020E+09 | 0.370057E+09 |
April | 0.411970E+09 | 0.223632E+09 | 0.188338E+09 | 0.349646E+09 | 0.231993E+09 |
May | 0.357796E+09 | 0.122284E+09 | 0.235512E+09 | 0.312416E+09 | 0.138260E+09 |
June | 0.310685E+09 | 82773174.11 | 0.227912E+09 | 0.283561E+09 | 97351703.25 |
July | 0.351002E+09 | 0.111156E+09 | 0.239846E+09 | 0.337684E+09 | 96654374.85 |
August | 0.374897E+09 | 0.156808E+09 | 0.218090E+09 | 0.370998E+09 | 0.114645E+09 |
September | 0.388764E+09 | 0.207107E+09 | 0.181657E+09 | 0.378101E+09 | 0.165514E+09 |
October | 0.343024E+09 | 0.201789E+09 | 0.141235E+09 | 0.306385E+09 | 0.243823E+09 |
November | 0.295541E+09 | 0.185452E+09 | 0.110088E+09 | 0.238007E+09 | 0.335500E+09 |
December | 0.325040E+09 | 0.213099E+09 | 0.111940E+09 | 0.217279E+09 | 0.520644E+09 |
Annual Sum or Average | 0.453130E+10 | 0.241974E+10 | 0.211157E+10 | 0.389397E+10 | 0.324589E+10 |
Minimum of Months | 0.295541E+09 | 82773174.11 | 0.110088E+09 | 0.217279E+09 | 96654374.85 |
Maximum of Months | 0.481583E+09 | 0.325271E+09 | 0.239846E+09 | 0.405149E+09 | 0.532140E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_DOOR_2
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.420967E+09 | 0.292818E+09 | 0.128149E+09 | 0.308726E+09 | 0.532140E+09 |
February | 0.481583E+09 | 0.325271E+09 | 0.156313E+09 | 0.405149E+09 | 0.399303E+09 |
March | 0.470035E+09 | 0.297546E+09 | 0.172489E+09 | 0.386020E+09 | 0.370057E+09 |
April | 0.411970E+09 | 0.223632E+09 | 0.188338E+09 | 0.349646E+09 | 0.231993E+09 |
May | 0.357796E+09 | 0.122284E+09 | 0.235512E+09 | 0.312416E+09 | 0.138260E+09 |
June | 0.310685E+09 | 82773174.11 | 0.227912E+09 | 0.283561E+09 | 97351703.25 |
July | 0.351002E+09 | 0.111156E+09 | 0.239846E+09 | 0.337684E+09 | 96654374.85 |
August | 0.374897E+09 | 0.156808E+09 | 0.218090E+09 | 0.370998E+09 | 0.114645E+09 |
September | 0.388764E+09 | 0.207107E+09 | 0.181657E+09 | 0.378101E+09 | 0.165514E+09 |
October | 0.343024E+09 | 0.201789E+09 | 0.141235E+09 | 0.306385E+09 | 0.243823E+09 |
November | 0.295541E+09 | 0.185452E+09 | 0.110088E+09 | 0.238007E+09 | 0.335500E+09 |
December | 0.325040E+09 | 0.213099E+09 | 0.111940E+09 | 0.217279E+09 | 0.520644E+09 |
Annual Sum or Average | 0.453130E+10 | 0.241974E+10 | 0.211157E+10 | 0.389397E+10 | 0.324589E+10 |
Minimum of Months | 0.295541E+09 | 82773174.11 | 0.110088E+09 | 0.217279E+09 | 96654374.85 |
Maximum of Months | 0.481583E+09 | 0.325271E+09 | 0.239846E+09 | 0.405149E+09 | 0.532140E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.351577E+09 | 0.244551E+09 | 0.107025E+09 | 0.255309E+09 | 0.453285E+09 |
February | 0.402201E+09 | 0.271655E+09 | 0.130547E+09 | 0.335855E+09 | 0.339805E+09 |
March | 0.392557E+09 | 0.248500E+09 | 0.144057E+09 | 0.320629E+09 | 0.314641E+09 |
April | 0.344062E+09 | 0.186770E+09 | 0.157293E+09 | 0.290967E+09 | 0.196521E+09 |
May | 0.298819E+09 | 0.102128E+09 | 0.196691E+09 | 0.260747E+09 | 0.116257E+09 |
June | 0.259473E+09 | 69129244.31 | 0.190344E+09 | 0.237174E+09 | 81431591.44 |
July | 0.293144E+09 | 92833301.21 | 0.200311E+09 | 0.282640E+09 | 80624277.15 |
August | 0.313101E+09 | 0.130960E+09 | 0.182141E+09 | 0.309980E+09 | 95962552.49 |
September | 0.324682E+09 | 0.172968E+09 | 0.151713E+09 | 0.315284E+09 | 0.139362E+09 |
October | 0.286482E+09 | 0.168527E+09 | 0.117954E+09 | 0.255011E+09 | 0.206125E+09 |
November | 0.246825E+09 | 0.154883E+09 | 91941667.14 | 0.197322E+09 | 0.285186E+09 |
December | 0.271462E+09 | 0.177973E+09 | 93488665.27 | 0.179433E+09 | 0.443871E+09 |
Annual Sum or Average | 0.378438E+10 | 0.202088E+10 | 0.176351E+10 | 0.324035E+10 | 0.275307E+10 |
Minimum of Months | 0.246825E+09 | 69129244.31 | 91941667.14 | 0.179433E+09 | 80624277.15 |
Maximum of Months | 0.402201E+09 | 0.271655E+09 | 0.200311E+09 | 0.335855E+09 | 0.453285E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.351577E+09 | 0.244551E+09 | 0.107025E+09 | 0.255309E+09 | 0.453285E+09 |
February | 0.402201E+09 | 0.271655E+09 | 0.130547E+09 | 0.335855E+09 | 0.339805E+09 |
March | 0.392557E+09 | 0.248500E+09 | 0.144057E+09 | 0.320629E+09 | 0.314641E+09 |
April | 0.344062E+09 | 0.186770E+09 | 0.157293E+09 | 0.290967E+09 | 0.196521E+09 |
May | 0.298819E+09 | 0.102128E+09 | 0.196691E+09 | 0.260747E+09 | 0.116257E+09 |
June | 0.259473E+09 | 69129244.31 | 0.190344E+09 | 0.237174E+09 | 81431591.44 |
July | 0.293144E+09 | 92833301.21 | 0.200311E+09 | 0.282640E+09 | 80624277.15 |
August | 0.313101E+09 | 0.130960E+09 | 0.182141E+09 | 0.309980E+09 | 95962552.49 |
September | 0.324682E+09 | 0.172968E+09 | 0.151713E+09 | 0.315284E+09 | 0.139362E+09 |
October | 0.286482E+09 | 0.168527E+09 | 0.117954E+09 | 0.255011E+09 | 0.206125E+09 |
November | 0.246825E+09 | 0.154883E+09 | 91941667.14 | 0.197322E+09 | 0.285186E+09 |
December | 0.271462E+09 | 0.177973E+09 | 93488665.27 | 0.179433E+09 | 0.443871E+09 |
Annual Sum or Average | 0.378438E+10 | 0.202088E+10 | 0.176351E+10 | 0.324035E+10 | 0.275307E+10 |
Minimum of Months | 0.246825E+09 | 69129244.31 | 91941667.14 | 0.179433E+09 | 80624277.15 |
Maximum of Months | 0.402201E+09 | 0.271655E+09 | 0.200311E+09 | 0.335855E+09 | 0.453285E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_DOOR
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.420967E+09 | 0.292818E+09 | 0.128149E+09 | 0.307117E+09 | 0.535993E+09 |
February | 0.481583E+09 | 0.325271E+09 | 0.156313E+09 | 0.403457E+09 | 0.401986E+09 |
March | 0.470035E+09 | 0.297546E+09 | 0.172489E+09 | 0.384844E+09 | 0.372325E+09 |
April | 0.411970E+09 | 0.223632E+09 | 0.188338E+09 | 0.348986E+09 | 0.232768E+09 |
May | 0.357796E+09 | 0.122284E+09 | 0.235512E+09 | 0.312462E+09 | 0.137962E+09 |
June | 0.310685E+09 | 82773174.11 | 0.227912E+09 | 0.283960E+09 | 96726914.16 |
July | 0.351002E+09 | 0.111156E+09 | 0.239846E+09 | 0.338216E+09 | 95821113.21 |
August | 0.374897E+09 | 0.156808E+09 | 0.218090E+09 | 0.371079E+09 | 0.113965E+09 |
September | 0.388764E+09 | 0.207107E+09 | 0.181657E+09 | 0.377706E+09 | 0.165386E+09 |
October | 0.343024E+09 | 0.201789E+09 | 0.141235E+09 | 0.305756E+09 | 0.244346E+09 |
November | 0.295541E+09 | 0.185452E+09 | 0.110088E+09 | 0.237025E+09 | 0.337534E+09 |
December | 0.325040E+09 | 0.213099E+09 | 0.111940E+09 | 0.216016E+09 | 0.524717E+09 |
Annual Sum or Average | 0.453130E+10 | 0.241974E+10 | 0.211157E+10 | 0.388662E+10 | 0.325953E+10 |
Minimum of Months | 0.295541E+09 | 82773174.11 | 0.110088E+09 | 0.216016E+09 | 95821113.21 |
Maximum of Months | 0.481583E+09 | 0.325271E+09 | 0.239846E+09 | 0.403457E+09 | 0.535993E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.351577E+09 | 0.244551E+09 | 0.107025E+09 | 0.255357E+09 | 0.453001E+09 |
February | 0.402201E+09 | 0.271655E+09 | 0.130547E+09 | 0.335946E+09 | 0.339422E+09 |
March | 0.392557E+09 | 0.248500E+09 | 0.144057E+09 | 0.320782E+09 | 0.313946E+09 |
April | 0.344062E+09 | 0.186770E+09 | 0.157293E+09 | 0.291338E+09 | 0.195392E+09 |
May | 0.298819E+09 | 0.102128E+09 | 0.196691E+09 | 0.261439E+09 | 0.115170E+09 |
June | 0.259473E+09 | 69129244.31 | 0.190344E+09 | 0.237828E+09 | 80602684.20 |
July | 0.293144E+09 | 92833301.21 | 0.200311E+09 | 0.283011E+09 | 80093349.71 |
August | 0.313101E+09 | 0.130960E+09 | 0.182141E+09 | 0.310282E+09 | 95389641.36 |
September | 0.324682E+09 | 0.172968E+09 | 0.151713E+09 | 0.315632E+09 | 0.138622E+09 |
October | 0.286482E+09 | 0.168527E+09 | 0.117954E+09 | 0.255236E+09 | 0.205364E+09 |
November | 0.246825E+09 | 0.154883E+09 | 91941667.14 | 0.197477E+09 | 0.284415E+09 |
December | 0.271462E+09 | 0.177973E+09 | 93488665.27 | 0.179478E+09 | 0.443547E+09 |
Annual Sum or Average | 0.378438E+10 | 0.202088E+10 | 0.176351E+10 | 0.324381E+10 | 0.274496E+10 |
Minimum of Months | 0.246825E+09 | 69129244.31 | 91941667.14 | 0.179478E+09 | 80093349.71 |
Maximum of Months | 0.402201E+09 | 0.271655E+09 | 0.200311E+09 | 0.335946E+09 | 0.453001E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.351577E+09 | 0.244551E+09 | 0.107025E+09 | 0.255357E+09 | 0.453001E+09 |
February | 0.402201E+09 | 0.271655E+09 | 0.130547E+09 | 0.335946E+09 | 0.339422E+09 |
March | 0.392557E+09 | 0.248500E+09 | 0.144057E+09 | 0.320782E+09 | 0.313946E+09 |
April | 0.344062E+09 | 0.186770E+09 | 0.157293E+09 | 0.291338E+09 | 0.195392E+09 |
May | 0.298819E+09 | 0.102128E+09 | 0.196691E+09 | 0.261439E+09 | 0.115170E+09 |
June | 0.259473E+09 | 69129244.31 | 0.190344E+09 | 0.237828E+09 | 80602684.20 |
July | 0.293144E+09 | 92833301.21 | 0.200311E+09 | 0.283011E+09 | 80093349.71 |
August | 0.313101E+09 | 0.130960E+09 | 0.182141E+09 | 0.310282E+09 | 95389641.36 |
September | 0.324682E+09 | 0.172968E+09 | 0.151713E+09 | 0.315632E+09 | 0.138622E+09 |
October | 0.286482E+09 | 0.168527E+09 | 0.117954E+09 | 0.255236E+09 | 0.205364E+09 |
November | 0.246825E+09 | 0.154883E+09 | 91941667.14 | 0.197477E+09 | 0.284415E+09 |
December | 0.271462E+09 | 0.177973E+09 | 93488665.27 | 0.179478E+09 | 0.443547E+09 |
Annual Sum or Average | 0.378438E+10 | 0.202088E+10 | 0.176351E+10 | 0.324381E+10 | 0.274496E+10 |
Minimum of Months | 0.246825E+09 | 69129244.31 | 91941667.14 | 0.179478E+09 | 80093349.71 |
Maximum of Months | 0.402201E+09 | 0.271655E+09 | 0.200311E+09 | 0.335946E+09 | 0.453001E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_DOOR
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.420967E+09 | 0.292818E+09 | 0.128149E+09 | 0.307176E+09 | 0.535652E+09 |
February | 0.481583E+09 | 0.325271E+09 | 0.156313E+09 | 0.403568E+09 | 0.401528E+09 |
March | 0.470035E+09 | 0.297546E+09 | 0.172489E+09 | 0.385029E+09 | 0.371497E+09 |
April | 0.411970E+09 | 0.223632E+09 | 0.188338E+09 | 0.349437E+09 | 0.231426E+09 |
May | 0.357796E+09 | 0.122284E+09 | 0.235512E+09 | 0.313294E+09 | 0.136672E+09 |
June | 0.310685E+09 | 82773174.11 | 0.227912E+09 | 0.284744E+09 | 95742903.43 |
July | 0.351002E+09 | 0.111156E+09 | 0.239846E+09 | 0.338662E+09 | 95190649.09 |
August | 0.374897E+09 | 0.156808E+09 | 0.218090E+09 | 0.371443E+09 | 0.113285E+09 |
September | 0.388764E+09 | 0.207107E+09 | 0.181657E+09 | 0.378124E+09 | 0.164508E+09 |
October | 0.343024E+09 | 0.201789E+09 | 0.141235E+09 | 0.306028E+09 | 0.243440E+09 |
November | 0.295541E+09 | 0.185452E+09 | 0.110088E+09 | 0.237214E+09 | 0.336615E+09 |
December | 0.325040E+09 | 0.213099E+09 | 0.111940E+09 | 0.216071E+09 | 0.524328E+09 |
Annual Sum or Average | 0.453130E+10 | 0.241974E+10 | 0.211157E+10 | 0.389079E+10 | 0.324988E+10 |
Minimum of Months | 0.295541E+09 | 82773174.11 | 0.110088E+09 | 0.216071E+09 | 95190649.09 |
Maximum of Months | 0.481583E+09 | 0.325271E+09 | 0.239846E+09 | 0.403568E+09 | 0.535652E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.351577E+09 | 0.244551E+09 | 0.107025E+09 | 0.255644E+09 | 0.450902E+09 |
February | 0.402201E+09 | 0.271655E+09 | 0.130547E+09 | 0.336389E+09 | 0.337166E+09 |
March | 0.392557E+09 | 0.248500E+09 | 0.144057E+09 | 0.321416E+09 | 0.310420E+09 |
April | 0.344062E+09 | 0.186770E+09 | 0.157293E+09 | 0.292571E+09 | 0.190945E+09 |
May | 0.298819E+09 | 0.102128E+09 | 0.196691E+09 | 0.263498E+09 | 0.111533E+09 |
June | 0.259473E+09 | 69129244.31 | 0.190344E+09 | 0.239698E+09 | 77992495.76 |
July | 0.293144E+09 | 92833301.21 | 0.200311E+09 | 0.283945E+09 | 78547990.28 |
August | 0.313101E+09 | 0.130960E+09 | 0.182141E+09 | 0.311010E+09 | 93798246.59 |
September | 0.324682E+09 | 0.172968E+09 | 0.151713E+09 | 0.316514E+09 | 0.136472E+09 |
October | 0.286482E+09 | 0.168527E+09 | 0.117954E+09 | 0.255862E+09 | 0.202761E+09 |
November | 0.246825E+09 | 0.154883E+09 | 91941667.14 | 0.198020E+09 | 0.281192E+09 |
December | 0.271462E+09 | 0.177973E+09 | 93488665.27 | 0.179721E+09 | 0.441315E+09 |
Annual Sum or Average | 0.378438E+10 | 0.202088E+10 | 0.176351E+10 | 0.325429E+10 | 0.271304E+10 |
Minimum of Months | 0.246825E+09 | 69129244.31 | 91941667.14 | 0.179721E+09 | 77992495.76 |
Maximum of Months | 0.402201E+09 | 0.271655E+09 | 0.200311E+09 | 0.336389E+09 | 0.450902E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.351577E+09 | 0.244551E+09 | 0.107025E+09 | 0.255644E+09 | 0.450902E+09 |
February | 0.402201E+09 | 0.271655E+09 | 0.130547E+09 | 0.336389E+09 | 0.337166E+09 |
March | 0.392557E+09 | 0.248500E+09 | 0.144057E+09 | 0.321416E+09 | 0.310420E+09 |
April | 0.344062E+09 | 0.186770E+09 | 0.157293E+09 | 0.292571E+09 | 0.190945E+09 |
May | 0.298819E+09 | 0.102128E+09 | 0.196691E+09 | 0.263498E+09 | 0.111533E+09 |
June | 0.259473E+09 | 69129244.31 | 0.190344E+09 | 0.239698E+09 | 77992495.76 |
July | 0.293144E+09 | 92833301.21 | 0.200311E+09 | 0.283945E+09 | 78547990.28 |
August | 0.313101E+09 | 0.130960E+09 | 0.182141E+09 | 0.311010E+09 | 93798246.59 |
September | 0.324682E+09 | 0.172968E+09 | 0.151713E+09 | 0.316514E+09 | 0.136472E+09 |
October | 0.286482E+09 | 0.168527E+09 | 0.117954E+09 | 0.255862E+09 | 0.202761E+09 |
November | 0.246825E+09 | 0.154883E+09 | 91941667.14 | 0.198020E+09 | 0.281192E+09 |
December | 0.271462E+09 | 0.177973E+09 | 93488665.27 | 0.179721E+09 | 0.441315E+09 |
Annual Sum or Average | 0.378438E+10 | 0.202088E+10 | 0.176351E+10 | 0.325429E+10 | 0.271304E+10 |
Minimum of Months | 0.246825E+09 | 69129244.31 | 91941667.14 | 0.179721E+09 | 77992495.76 |
Maximum of Months | 0.402201E+09 | 0.271655E+09 | 0.200311E+09 | 0.336389E+09 | 0.450902E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_DOOR
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.420967E+09 | 0.292818E+09 | 0.128149E+09 | 0.307531E+09 | 0.533144E+09 |
February | 0.481583E+09 | 0.325271E+09 | 0.156313E+09 | 0.404109E+09 | 0.398837E+09 |
March | 0.470035E+09 | 0.297546E+09 | 0.172489E+09 | 0.385804E+09 | 0.367293E+09 |
April | 0.411970E+09 | 0.223632E+09 | 0.188338E+09 | 0.350933E+09 | 0.226144E+09 |
May | 0.357796E+09 | 0.122284E+09 | 0.235512E+09 | 0.315769E+09 | 0.132361E+09 |
June | 0.310685E+09 | 82773174.11 | 0.227912E+09 | 0.286984E+09 | 92649326.40 |
July | 0.351002E+09 | 0.111156E+09 | 0.239846E+09 | 0.339787E+09 | 93363976.02 |
August | 0.374897E+09 | 0.156808E+09 | 0.218090E+09 | 0.372318E+09 | 0.111402E+09 |
September | 0.388764E+09 | 0.207107E+09 | 0.181657E+09 | 0.379182E+09 | 0.161960E+09 |
October | 0.343024E+09 | 0.201789E+09 | 0.141235E+09 | 0.306786E+09 | 0.240348E+09 |
November | 0.295541E+09 | 0.185452E+09 | 0.110088E+09 | 0.237876E+09 | 0.332782E+09 |
December | 0.325040E+09 | 0.213099E+09 | 0.111940E+09 | 0.216369E+09 | 0.521660E+09 |
Annual Sum or Average | 0.453130E+10 | 0.241974E+10 | 0.211157E+10 | 0.390345E+10 | 0.321195E+10 |
Minimum of Months | 0.295541E+09 | 82773174.11 | 0.110088E+09 | 0.216369E+09 | 92649326.40 |
Maximum of Months | 0.481583E+09 | 0.325271E+09 | 0.239846E+09 | 0.404109E+09 | 0.533144E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.351577E+09 | 0.244551E+09 | 0.107025E+09 | 0.257730E+09 | 0.439143E+09 |
February | 0.402201E+09 | 0.271655E+09 | 0.130547E+09 | 0.338955E+09 | 0.325492E+09 |
March | 0.392557E+09 | 0.248500E+09 | 0.144057E+09 | 0.324511E+09 | 0.293838E+09 |
April | 0.344062E+09 | 0.186770E+09 | 0.157293E+09 | 0.297065E+09 | 0.173117E+09 |
May | 0.298819E+09 | 0.102128E+09 | 0.196691E+09 | 0.270423E+09 | 98162119.61 |
June | 0.259473E+09 | 69129244.31 | 0.190344E+09 | 0.245797E+09 | 68526923.59 |
July | 0.293144E+09 | 92833301.21 | 0.200311E+09 | 0.287281E+09 | 72287587.73 |
August | 0.313101E+09 | 0.130960E+09 | 0.182141E+09 | 0.313318E+09 | 87640096.27 |
September | 0.324682E+09 | 0.172968E+09 | 0.151713E+09 | 0.318941E+09 | 0.128768E+09 |
October | 0.286482E+09 | 0.168527E+09 | 0.117954E+09 | 0.257900E+09 | 0.192501E+09 |
November | 0.246825E+09 | 0.154883E+09 | 91941667.14 | 0.200092E+09 | 0.267961E+09 |
December | 0.271462E+09 | 0.177973E+09 | 93488665.27 | 0.181270E+09 | 0.429156E+09 |
Annual Sum or Average | 0.378438E+10 | 0.202088E+10 | 0.176351E+10 | 0.329328E+10 | 0.257659E+10 |
Minimum of Months | 0.246825E+09 | 69129244.31 | 91941667.14 | 0.181270E+09 | 68526923.59 |
Maximum of Months | 0.402201E+09 | 0.271655E+09 | 0.200311E+09 | 0.338955E+09 | 0.439143E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.351577E+09 | 0.244551E+09 | 0.107025E+09 | 0.257730E+09 | 0.439143E+09 |
February | 0.402201E+09 | 0.271655E+09 | 0.130547E+09 | 0.338955E+09 | 0.325492E+09 |
March | 0.392557E+09 | 0.248500E+09 | 0.144057E+09 | 0.324511E+09 | 0.293838E+09 |
April | 0.344062E+09 | 0.186770E+09 | 0.157293E+09 | 0.297065E+09 | 0.173117E+09 |
May | 0.298819E+09 | 0.102128E+09 | 0.196691E+09 | 0.270423E+09 | 98162119.61 |
June | 0.259473E+09 | 69129244.31 | 0.190344E+09 | 0.245797E+09 | 68526923.59 |
July | 0.293144E+09 | 92833301.21 | 0.200311E+09 | 0.287281E+09 | 72287587.73 |
August | 0.313101E+09 | 0.130960E+09 | 0.182141E+09 | 0.313318E+09 | 87640096.27 |
September | 0.324682E+09 | 0.172968E+09 | 0.151713E+09 | 0.318941E+09 | 0.128768E+09 |
October | 0.286482E+09 | 0.168527E+09 | 0.117954E+09 | 0.257900E+09 | 0.192501E+09 |
November | 0.246825E+09 | 0.154883E+09 | 91941667.14 | 0.200092E+09 | 0.267961E+09 |
December | 0.271462E+09 | 0.177973E+09 | 93488665.27 | 0.181270E+09 | 0.429156E+09 |
Annual Sum or Average | 0.378438E+10 | 0.202088E+10 | 0.176351E+10 | 0.329328E+10 | 0.257659E+10 |
Minimum of Months | 0.246825E+09 | 69129244.31 | 91941667.14 | 0.181270E+09 | 68526923.59 |
Maximum of Months | 0.402201E+09 | 0.271655E+09 | 0.200311E+09 | 0.338955E+09 | 0.439143E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_DOOR
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.420967E+09 | 0.292818E+09 | 0.128149E+09 | 0.310086E+09 | 0.519025E+09 |
February | 0.481583E+09 | 0.325271E+09 | 0.156313E+09 | 0.407239E+09 | 0.384861E+09 |
March | 0.470035E+09 | 0.297546E+09 | 0.172489E+09 | 0.389586E+09 | 0.347496E+09 |
April | 0.411970E+09 | 0.223632E+09 | 0.188338E+09 | 0.356391E+09 | 0.204983E+09 |
May | 0.357796E+09 | 0.122284E+09 | 0.235512E+09 | 0.324106E+09 | 0.116536E+09 |
June | 0.310685E+09 | 82773174.11 | 0.227912E+09 | 0.294298E+09 | 81436920.32 |
July | 0.351002E+09 | 0.111156E+09 | 0.239846E+09 | 0.343793E+09 | 85954674.22 |
August | 0.374897E+09 | 0.156808E+09 | 0.218090E+09 | 0.375094E+09 | 0.104127E+09 |
September | 0.388764E+09 | 0.207107E+09 | 0.181657E+09 | 0.382103E+09 | 0.152854E+09 |
October | 0.343024E+09 | 0.201789E+09 | 0.141235E+09 | 0.309267E+09 | 0.228195E+09 |
November | 0.295541E+09 | 0.185452E+09 | 0.110088E+09 | 0.240397E+09 | 0.317079E+09 |
December | 0.325040E+09 | 0.213099E+09 | 0.111940E+09 | 0.218265E+09 | 0.507093E+09 |
Annual Sum or Average | 0.453130E+10 | 0.241974E+10 | 0.211157E+10 | 0.395063E+10 | 0.304964E+10 |
Minimum of Months | 0.295541E+09 | 82773174.11 | 0.110088E+09 | 0.218265E+09 | 81436920.32 |
Maximum of Months | 0.481583E+09 | 0.325271E+09 | 0.239846E+09 | 0.407239E+09 | 0.519025E+09 |
Report: WindowZoneSummaryMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 612.71 | 1110.58 | 841.12 | 585.07 | 256.05 | 0.00 | 0.00 |
February | 890.87 | 923.36 | 1065.34 | 719.55 | 345.79 | 0.00 | 0.00 |
March | 768.44 | 769.92 | 939.17 | 594.52 | 344.65 | 0.00 | 0.00 |
April | 717.73 | 502.26 | 850.58 | 461.73 | 388.86 | 0.00 | 0.00 |
May | 618.10 | 291.52 | 714.90 | 244.33 | 470.57 | 0.00 | 0.00 |
June | 581.66 | 208.77 | 641.46 | 170.90 | 470.56 | 0.00 | 0.00 |
July | 675.40 | 193.15 | 701.33 | 222.10 | 479.23 | 0.00 | 0.00 |
August | 739.75 | 232.39 | 749.07 | 313.31 | 435.76 | 0.00 | 0.00 |
September | 774.00 | 358.92 | 802.67 | 427.61 | 375.06 | 0.00 | 0.00 |
October | 605.78 | 514.42 | 685.39 | 403.19 | 282.20 | 0.00 | 0.00 |
November | 485.96 | 732.80 | 610.20 | 382.90 | 227.30 | 0.00 | 0.00 |
December | 430.40 | 1087.32 | 649.45 | 425.79 | 223.67 | 0.00 | 0.00 |
Annual Sum or Average | 656.69 | 575.66 | 768.96 | 410.63 | 358.33 | 0.00 | 0.00 |
Minimum of Months | 430.40 | 193.15 | 610.20 | 170.90 | 223.67 | 0.00 | 0.00 |
Maximum of Months | 890.87 | 1110.58 | 1065.34 | 719.55 | 479.23 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 302.57 | 570.87 | 420.56 | 292.54 | 128.03 | 0.00 | 0.00 |
February | 440.37 | 478.08 | 532.67 | 359.77 | 172.89 | 0.00 | 0.00 |
March | 379.85 | 402.76 | 469.58 | 297.26 | 172.32 | 0.00 | 0.00 |
April | 353.92 | 268.45 | 425.29 | 230.86 | 194.43 | 0.00 | 0.00 |
May | 304.48 | 153.51 | 357.45 | 122.17 | 235.29 | 0.00 | 0.00 |
June | 287.71 | 108.32 | 320.73 | 85.45 | 235.28 | 0.00 | 0.00 |
July | 336.36 | 98.42 | 350.66 | 111.05 | 239.62 | 0.00 | 0.00 |
August | 368.75 | 118.14 | 374.54 | 156.66 | 217.88 | 0.00 | 0.00 |
September | 384.78 | 183.88 | 401.34 | 213.80 | 187.53 | 0.00 | 0.00 |
October | 300.41 | 268.93 | 342.69 | 201.60 | 141.10 | 0.00 | 0.00 |
November | 240.14 | 381.13 | 305.10 | 191.45 | 113.65 | 0.00 | 0.00 |
December | 212.19 | 560.62 | 324.73 | 212.89 | 111.83 | 0.00 | 0.00 |
Annual Sum or Average | 325.12 | 298.66 | 384.48 | 205.31 | 179.17 | 0.00 | 0.00 |
Minimum of Months | 212.19 | 98.42 | 305.10 | 85.45 | 111.83 | 0.00 | 0.00 |
Maximum of Months | 440.37 | 570.87 | 532.67 | 359.77 | 239.62 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 303.12 | 553.18 | 419.70 | 291.94 | 127.76 | 0.00 | 0.00 |
February | 440.99 | 462.15 | 531.57 | 359.04 | 172.54 | 0.00 | 0.00 |
March | 380.21 | 389.08 | 468.62 | 296.65 | 171.97 | 0.00 | 0.00 |
April | 355.01 | 255.65 | 424.42 | 230.39 | 194.03 | 0.00 | 0.00 |
May | 306.17 | 148.43 | 356.72 | 121.92 | 234.80 | 0.00 | 0.00 |
June | 288.36 | 107.95 | 320.07 | 85.27 | 234.80 | 0.00 | 0.00 |
July | 335.33 | 101.59 | 349.94 | 110.82 | 239.12 | 0.00 | 0.00 |
August | 368.06 | 120.16 | 373.77 | 156.34 | 217.43 | 0.00 | 0.00 |
September | 385.62 | 179.68 | 400.51 | 213.37 | 187.15 | 0.00 | 0.00 |
October | 301.65 | 256.50 | 341.99 | 201.18 | 140.81 | 0.00 | 0.00 |
November | 240.98 | 365.63 | 304.47 | 191.06 | 113.41 | 0.00 | 0.00 |
December | 212.65 | 542.68 | 324.06 | 212.46 | 111.60 | 0.00 | 0.00 |
Annual Sum or Average | 325.67 | 289.50 | 383.69 | 204.89 | 178.80 | 0.00 | 0.00 |
Minimum of Months | 212.65 | 101.59 | 304.47 | 85.27 | 111.60 | 0.00 | 0.00 |
Maximum of Months | 440.99 | 553.18 | 531.57 | 359.04 | 239.12 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 303.64 | 548.41 | 419.70 | 291.94 | 127.76 | 0.00 | 0.00 |
February | 441.78 | 457.25 | 531.57 | 359.04 | 172.54 | 0.00 | 0.00 |
March | 380.88 | 384.47 | 468.62 | 296.65 | 171.97 | 0.00 | 0.00 |
April | 356.08 | 251.02 | 424.42 | 230.39 | 194.03 | 0.00 | 0.00 |
May | 307.54 | 145.41 | 356.72 | 121.92 | 234.80 | 0.00 | 0.00 |
June | 289.34 | 106.21 | 320.07 | 85.27 | 234.80 | 0.00 | 0.00 |
July | 335.70 | 100.92 | 349.94 | 110.82 | 239.12 | 0.00 | 0.00 |
August | 368.44 | 119.23 | 373.77 | 156.34 | 217.43 | 0.00 | 0.00 |
September | 386.56 | 176.95 | 400.51 | 213.37 | 187.15 | 0.00 | 0.00 |
October | 302.56 | 252.12 | 341.99 | 201.18 | 140.81 | 0.00 | 0.00 |
November | 241.66 | 360.51 | 304.47 | 191.06 | 113.41 | 0.00 | 0.00 |
December | 213.07 | 537.62 | 324.06 | 212.46 | 111.60 | 0.00 | 0.00 |
Annual Sum or Average | 326.43 | 285.96 | 383.69 | 204.89 | 178.80 | 0.00 | 0.00 |
Minimum of Months | 213.07 | 100.92 | 304.47 | 85.27 | 111.60 | 0.00 | 0.00 |
Maximum of Months | 441.78 | 548.41 | 531.57 | 359.04 | 239.12 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 304.05 | 546.04 | 419.70 | 291.94 | 127.76 | 0.00 | 0.00 |
February | 442.41 | 454.58 | 531.57 | 359.04 | 172.54 | 0.00 | 0.00 |
March | 381.45 | 381.71 | 468.62 | 296.65 | 171.97 | 0.00 | 0.00 |
April | 356.94 | 248.23 | 424.42 | 230.39 | 194.03 | 0.00 | 0.00 |
May | 308.71 | 143.25 | 356.72 | 121.92 | 234.80 | 0.00 | 0.00 |
June | 290.29 | 104.59 | 320.07 | 85.27 | 234.80 | 0.00 | 0.00 |
July | 336.18 | 99.84 | 349.94 | 110.82 | 239.12 | 0.00 | 0.00 |
August | 368.88 | 118.03 | 373.77 | 156.34 | 217.43 | 0.00 | 0.00 |
September | 387.33 | 175.05 | 400.51 | 213.37 | 187.15 | 0.00 | 0.00 |
October | 303.17 | 249.84 | 341.99 | 201.18 | 140.81 | 0.00 | 0.00 |
November | 242.20 | 357.61 | 304.47 | 191.06 | 113.41 | 0.00 | 0.00 |
December | 213.42 | 534.97 | 324.06 | 212.46 | 111.60 | 0.00 | 0.00 |
Annual Sum or Average | 327.07 | 283.77 | 383.69 | 204.89 | 178.80 | 0.00 | 0.00 |
Minimum of Months | 213.42 | 99.84 | 304.47 | 85.27 | 111.60 | 0.00 | 0.00 |
Maximum of Months | 442.41 | 546.04 | 531.57 | 359.04 | 239.12 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 613.89 | 1069.27 | 839.40 | 583.87 | 255.53 | 0.00 | 0.00 |
February | 892.70 | 888.06 | 1063.15 | 718.07 | 345.08 | 0.00 | 0.00 |
March | 768.61 | 743.24 | 937.24 | 593.30 | 343.94 | 0.00 | 0.00 |
April | 719.71 | 481.18 | 848.84 | 460.78 | 388.06 | 0.00 | 0.00 |
May | 622.67 | 277.20 | 713.44 | 243.83 | 469.60 | 0.00 | 0.00 |
June | 584.32 | 201.57 | 640.15 | 170.55 | 469.60 | 0.00 | 0.00 |
July | 673.61 | 193.61 | 699.89 | 221.64 | 478.25 | 0.00 | 0.00 |
August | 739.91 | 229.75 | 747.54 | 312.67 | 434.86 | 0.00 | 0.00 |
September | 778.87 | 342.89 | 801.02 | 426.73 | 374.29 | 0.00 | 0.00 |
October | 610.46 | 489.15 | 683.98 | 402.36 | 281.62 | 0.00 | 0.00 |
November | 489.48 | 696.19 | 608.94 | 382.11 | 226.83 | 0.00 | 0.00 |
December | 431.85 | 1046.33 | 648.12 | 424.91 | 223.21 | 0.00 | 0.00 |
Annual Sum or Average | 658.79 | 553.50 | 767.38 | 409.79 | 357.60 | 0.00 | 0.00 |
Minimum of Months | 431.85 | 193.61 | 608.94 | 170.55 | 223.21 | 0.00 | 0.00 |
Maximum of Months | 892.70 | 1069.27 | 1063.15 | 718.07 | 478.25 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 305.31 | 538.59 | 419.70 | 291.94 | 127.76 | 0.00 | 0.00 |
February | 444.43 | 447.09 | 531.57 | 359.04 | 172.54 | 0.00 | 0.00 |
March | 383.10 | 373.96 | 468.62 | 296.65 | 171.97 | 0.00 | 0.00 |
April | 359.15 | 241.44 | 424.42 | 230.39 | 194.03 | 0.00 | 0.00 |
May | 311.36 | 138.32 | 356.72 | 121.92 | 234.80 | 0.00 | 0.00 |
June | 292.56 | 100.15 | 320.07 | 85.27 | 234.80 | 0.00 | 0.00 |
July | 337.33 | 95.98 | 349.94 | 110.82 | 239.12 | 0.00 | 0.00 |
August | 370.01 | 114.21 | 373.77 | 156.34 | 217.43 | 0.00 | 0.00 |
September | 388.99 | 171.34 | 400.51 | 213.37 | 187.15 | 0.00 | 0.00 |
October | 304.58 | 245.14 | 341.99 | 201.18 | 140.81 | 0.00 | 0.00 |
November | 243.70 | 350.27 | 304.47 | 191.06 | 113.41 | 0.00 | 0.00 |
December | 214.64 | 527.35 | 324.06 | 212.46 | 111.60 | 0.00 | 0.00 |
Annual Sum or Average | 328.75 | 277.96 | 383.69 | 204.89 | 178.80 | 0.00 | 0.00 |
Minimum of Months | 214.64 | 95.98 | 304.47 | 85.27 | 111.60 | 0.00 | 0.00 |
Maximum of Months | 444.43 | 538.59 | 531.57 | 359.04 | 239.12 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 305.36 | 538.25 | 419.70 | 291.94 | 127.76 | 0.00 | 0.00 |
February | 444.55 | 446.58 | 531.57 | 359.04 | 172.54 | 0.00 | 0.00 |
March | 383.28 | 373.13 | 468.62 | 296.65 | 171.97 | 0.00 | 0.00 |
April | 359.61 | 240.05 | 424.42 | 230.39 | 194.03 | 0.00 | 0.00 |
May | 312.19 | 137.03 | 356.72 | 121.92 | 234.80 | 0.00 | 0.00 |
June | 293.36 | 99.13 | 320.07 | 85.27 | 234.80 | 0.00 | 0.00 |
July | 337.77 | 95.35 | 349.94 | 110.82 | 239.12 | 0.00 | 0.00 |
August | 370.37 | 113.52 | 373.77 | 156.34 | 217.43 | 0.00 | 0.00 |
September | 389.42 | 170.43 | 400.51 | 213.37 | 187.15 | 0.00 | 0.00 |
October | 304.85 | 244.24 | 341.99 | 201.18 | 140.81 | 0.00 | 0.00 |
November | 243.89 | 349.32 | 304.47 | 191.06 | 113.41 | 0.00 | 0.00 |
December | 214.69 | 526.96 | 324.06 | 212.46 | 111.60 | 0.00 | 0.00 |
Annual Sum or Average | 329.10 | 277.14 | 383.69 | 204.89 | 178.80 | 0.00 | 0.00 |
Minimum of Months | 214.69 | 95.35 | 304.47 | 85.27 | 111.60 | 0.00 | 0.00 |
Maximum of Months | 444.55 | 538.25 | 531.57 | 359.04 | 239.12 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 305.71 | 535.75 | 419.70 | 291.94 | 127.76 | 0.00 | 0.00 |
February | 445.14 | 443.60 | 531.57 | 359.04 | 172.54 | 0.00 | 0.00 |
March | 384.05 | 368.93 | 468.62 | 296.65 | 171.97 | 0.00 | 0.00 |
April | 361.14 | 234.58 | 424.42 | 230.39 | 194.03 | 0.00 | 0.00 |
May | 314.65 | 132.70 | 356.72 | 121.92 | 234.80 | 0.00 | 0.00 |
June | 295.67 | 95.92 | 320.07 | 85.27 | 234.80 | 0.00 | 0.00 |
July | 338.89 | 93.51 | 349.94 | 110.82 | 239.12 | 0.00 | 0.00 |
August | 371.24 | 111.63 | 373.77 | 156.34 | 217.43 | 0.00 | 0.00 |
September | 390.51 | 167.79 | 400.51 | 213.37 | 187.15 | 0.00 | 0.00 |
October | 305.60 | 241.14 | 341.99 | 201.18 | 140.81 | 0.00 | 0.00 |
November | 244.57 | 345.36 | 304.47 | 191.06 | 113.41 | 0.00 | 0.00 |
December | 214.98 | 524.30 | 324.06 | 212.46 | 111.60 | 0.00 | 0.00 |
Annual Sum or Average | 330.16 | 273.91 | 383.69 | 204.89 | 178.80 | 0.00 | 0.00 |
Minimum of Months | 214.98 | 93.51 | 304.47 | 85.27 | 111.60 | 0.00 | 0.00 |
Maximum of Months | 445.14 | 535.75 | 531.57 | 359.04 | 239.12 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 308.22 | 521.69 | 419.70 | 291.94 | 127.76 | 0.00 | 0.00 |
February | 448.56 | 428.18 | 531.57 | 359.04 | 172.54 | 0.00 | 0.00 |
March | 387.77 | 349.15 | 468.62 | 296.65 | 171.97 | 0.00 | 0.00 |
April | 366.71 | 212.66 | 424.42 | 230.39 | 194.03 | 0.00 | 0.00 |
May | 322.94 | 116.81 | 356.72 | 121.92 | 234.80 | 0.00 | 0.00 |
June | 303.20 | 84.29 | 320.07 | 85.27 | 234.80 | 0.00 | 0.00 |
July | 342.87 | 86.07 | 349.94 | 110.82 | 239.12 | 0.00 | 0.00 |
August | 374.00 | 104.32 | 373.77 | 156.34 | 217.43 | 0.00 | 0.00 |
September | 393.51 | 158.33 | 400.51 | 213.37 | 187.15 | 0.00 | 0.00 |
October | 308.04 | 228.94 | 341.99 | 201.18 | 140.81 | 0.00 | 0.00 |
November | 247.14 | 329.09 | 304.47 | 191.06 | 113.41 | 0.00 | 0.00 |
December | 216.85 | 509.78 | 324.06 | 212.46 | 111.60 | 0.00 | 0.00 |
Annual Sum or Average | 334.13 | 260.11 | 383.69 | 204.89 | 178.80 | 0.00 | 0.00 |
Minimum of Months | 216.85 | 84.29 | 304.47 | 85.27 | 111.60 | 0.00 | 0.00 |
Maximum of Months | 448.56 | 521.69 | 531.57 | 359.04 | 239.12 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.164107E+10 | 0.297458E+10 | 0.225287E+10 | 0.156706E+10 | 0.685807E+09 | 0.00 | 0.00 |
February | 0.215519E+10 | 0.223379E+10 | 0.257726E+10 | 0.174073E+10 | 0.836531E+09 | 0.00 | 0.00 |
March | 0.205819E+10 | 0.206216E+10 | 0.251546E+10 | 0.159236E+10 | 0.923102E+09 | 0.00 | 0.00 |
April | 0.186036E+10 | 0.130186E+10 | 0.220472E+10 | 0.119680E+10 | 0.100792E+10 | 0.00 | 0.00 |
May | 0.165552E+10 | 0.780817E+09 | 0.191480E+10 | 0.654424E+09 | 0.126038E+10 | 0.00 | 0.00 |
June | 0.150767E+10 | 0.541125E+09 | 0.166268E+10 | 0.442973E+09 | 0.121970E+10 | 0.00 | 0.00 |
July | 0.180899E+10 | 0.517321E+09 | 0.187844E+10 | 0.594866E+09 | 0.128357E+10 | 0.00 | 0.00 |
August | 0.198135E+10 | 0.622429E+09 | 0.200632E+10 | 0.839181E+09 | 0.116714E+10 | 0.00 | 0.00 |
September | 0.200620E+10 | 0.930330E+09 | 0.208053E+10 | 0.110836E+10 | 0.972163E+09 | 0.00 | 0.00 |
October | 0.162251E+10 | 0.137781E+10 | 0.183574E+10 | 0.107991E+10 | 0.755838E+09 | 0.00 | 0.00 |
November | 0.125962E+10 | 0.189943E+10 | 0.158163E+10 | 0.992476E+09 | 0.589153E+09 | 0.00 | 0.00 |
December | 0.115279E+10 | 0.291228E+10 | 0.173950E+10 | 0.114043E+10 | 0.599066E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.207095E+11 | 0.181539E+11 | 0.242499E+11 | 0.129496E+11 | 0.113004E+11 | 0.00 | 0.00 |
Minimum of Months | 0.115279E+10 | 0.517321E+09 | 0.158163E+10 | 0.442973E+09 | 0.589153E+09 | 0.00 | 0.00 |
Maximum of Months | 0.215519E+10 | 0.297458E+10 | 0.257726E+10 | 0.174073E+10 | 0.128357E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.810412E+09 | 0.152902E+10 | 0.112643E+10 | 0.783530E+09 | 0.342903E+09 | 0.00 | 0.00 |
February | 0.106533E+10 | 0.115658E+10 | 0.128863E+10 | 0.870367E+09 | 0.418265E+09 | 0.00 | 0.00 |
March | 0.101740E+10 | 0.107876E+10 | 0.125773E+10 | 0.796180E+09 | 0.461551E+09 | 0.00 | 0.00 |
April | 0.917351E+09 | 0.695829E+09 | 0.110236E+10 | 0.598400E+09 | 0.503958E+09 | 0.00 | 0.00 |
May | 0.815523E+09 | 0.411163E+09 | 0.957400E+09 | 0.327212E+09 | 0.630188E+09 | 0.00 | 0.00 |
June | 0.745747E+09 | 0.280773E+09 | 0.831338E+09 | 0.221486E+09 | 0.609852E+09 | 0.00 | 0.00 |
July | 0.900908E+09 | 0.263616E+09 | 0.939219E+09 | 0.297433E+09 | 0.641786E+09 | 0.00 | 0.00 |
August | 0.987651E+09 | 0.316423E+09 | 0.100316E+10 | 0.419590E+09 | 0.583569E+09 | 0.00 | 0.00 |
September | 0.997357E+09 | 0.476621E+09 | 0.104026E+10 | 0.554181E+09 | 0.486082E+09 | 0.00 | 0.00 |
October | 0.804631E+09 | 0.720299E+09 | 0.917872E+09 | 0.539953E+09 | 0.377919E+09 | 0.00 | 0.00 |
November | 0.622445E+09 | 0.987902E+09 | 0.790814E+09 | 0.496238E+09 | 0.294576E+09 | 0.00 | 0.00 |
December | 0.568332E+09 | 0.150156E+10 | 0.869749E+09 | 0.570216E+09 | 0.299533E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.102531E+11 | 0.941854E+10 | 0.121250E+11 | 0.647479E+10 | 0.565018E+10 | 0.00 | 0.00 |
Minimum of Months | 0.568332E+09 | 0.263616E+09 | 0.790814E+09 | 0.221486E+09 | 0.294576E+09 | 0.00 | 0.00 |
Maximum of Months | 0.106533E+10 | 0.152902E+10 | 0.128863E+10 | 0.870367E+09 | 0.641786E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.811867E+09 | 0.148164E+10 | 0.112412E+10 | 0.781921E+09 | 0.342199E+09 | 0.00 | 0.00 |
February | 0.106685E+10 | 0.111803E+10 | 0.128599E+10 | 0.868580E+09 | 0.417407E+09 | 0.00 | 0.00 |
March | 0.101836E+10 | 0.104210E+10 | 0.125515E+10 | 0.794545E+09 | 0.460603E+09 | 0.00 | 0.00 |
April | 0.920179E+09 | 0.662649E+09 | 0.110009E+10 | 0.597171E+09 | 0.502924E+09 | 0.00 | 0.00 |
May | 0.820050E+09 | 0.397554E+09 | 0.955434E+09 | 0.326540E+09 | 0.628894E+09 | 0.00 | 0.00 |
June | 0.747418E+09 | 0.279812E+09 | 0.829631E+09 | 0.221032E+09 | 0.608600E+09 | 0.00 | 0.00 |
July | 0.898136E+09 | 0.272105E+09 | 0.937291E+09 | 0.296822E+09 | 0.640468E+09 | 0.00 | 0.00 |
August | 0.985813E+09 | 0.321844E+09 | 0.100110E+10 | 0.418729E+09 | 0.582371E+09 | 0.00 | 0.00 |
September | 0.999518E+09 | 0.465729E+09 | 0.103813E+10 | 0.553043E+09 | 0.485084E+09 | 0.00 | 0.00 |
October | 0.807928E+09 | 0.687013E+09 | 0.915987E+09 | 0.538844E+09 | 0.377143E+09 | 0.00 | 0.00 |
November | 0.624609E+09 | 0.947700E+09 | 0.789191E+09 | 0.495219E+09 | 0.293971E+09 | 0.00 | 0.00 |
December | 0.569555E+09 | 0.145351E+10 | 0.867963E+09 | 0.569046E+09 | 0.298918E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.102703E+11 | 0.912969E+10 | 0.121001E+11 | 0.646149E+10 | 0.563858E+10 | 0.00 | 0.00 |
Minimum of Months | 0.569555E+09 | 0.272105E+09 | 0.789191E+09 | 0.221032E+09 | 0.293971E+09 | 0.00 | 0.00 |
Maximum of Months | 0.106685E+10 | 0.148164E+10 | 0.128599E+10 | 0.868580E+09 | 0.640468E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.813271E+09 | 0.146885E+10 | 0.112412E+10 | 0.781921E+09 | 0.342199E+09 | 0.00 | 0.00 |
February | 0.106876E+10 | 0.110619E+10 | 0.128599E+10 | 0.868580E+09 | 0.417407E+09 | 0.00 | 0.00 |
March | 0.102016E+10 | 0.102975E+10 | 0.125515E+10 | 0.794545E+09 | 0.460603E+09 | 0.00 | 0.00 |
April | 0.922963E+09 | 0.650633E+09 | 0.110009E+10 | 0.597171E+09 | 0.502924E+09 | 0.00 | 0.00 |
May | 0.823722E+09 | 0.389454E+09 | 0.955434E+09 | 0.326540E+09 | 0.628894E+09 | 0.00 | 0.00 |
June | 0.749968E+09 | 0.275286E+09 | 0.829631E+09 | 0.221032E+09 | 0.608600E+09 | 0.00 | 0.00 |
July | 0.899127E+09 | 0.270308E+09 | 0.937291E+09 | 0.296822E+09 | 0.640468E+09 | 0.00 | 0.00 |
August | 0.986827E+09 | 0.319338E+09 | 0.100110E+10 | 0.418729E+09 | 0.582371E+09 | 0.00 | 0.00 |
September | 0.100197E+10 | 0.458648E+09 | 0.103813E+10 | 0.553043E+09 | 0.485084E+09 | 0.00 | 0.00 |
October | 0.810368E+09 | 0.675280E+09 | 0.915987E+09 | 0.538844E+09 | 0.377143E+09 | 0.00 | 0.00 |
November | 0.626383E+09 | 0.934440E+09 | 0.789191E+09 | 0.495219E+09 | 0.293971E+09 | 0.00 | 0.00 |
December | 0.570689E+09 | 0.143997E+10 | 0.867963E+09 | 0.569046E+09 | 0.298918E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.102942E+11 | 0.901815E+10 | 0.121001E+11 | 0.646149E+10 | 0.563858E+10 | 0.00 | 0.00 |
Minimum of Months | 0.570689E+09 | 0.270308E+09 | 0.789191E+09 | 0.221032E+09 | 0.293971E+09 | 0.00 | 0.00 |
Maximum of Months | 0.106876E+10 | 0.146885E+10 | 0.128599E+10 | 0.868580E+09 | 0.640468E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.814358E+09 | 0.146251E+10 | 0.112412E+10 | 0.781921E+09 | 0.342199E+09 | 0.00 | 0.00 |
February | 0.107028E+10 | 0.109973E+10 | 0.128599E+10 | 0.868580E+09 | 0.417407E+09 | 0.00 | 0.00 |
March | 0.102168E+10 | 0.102238E+10 | 0.125515E+10 | 0.794545E+09 | 0.460603E+09 | 0.00 | 0.00 |
April | 0.925197E+09 | 0.643419E+09 | 0.110009E+10 | 0.597171E+09 | 0.502924E+09 | 0.00 | 0.00 |
May | 0.826853E+09 | 0.383682E+09 | 0.955434E+09 | 0.326540E+09 | 0.628894E+09 | 0.00 | 0.00 |
June | 0.752428E+09 | 0.271101E+09 | 0.829631E+09 | 0.221032E+09 | 0.608600E+09 | 0.00 | 0.00 |
July | 0.900412E+09 | 0.267414E+09 | 0.937291E+09 | 0.296822E+09 | 0.640468E+09 | 0.00 | 0.00 |
August | 0.988000E+09 | 0.316137E+09 | 0.100110E+10 | 0.418729E+09 | 0.582371E+09 | 0.00 | 0.00 |
September | 0.100395E+10 | 0.453735E+09 | 0.103813E+10 | 0.553043E+09 | 0.485084E+09 | 0.00 | 0.00 |
October | 0.811998E+09 | 0.669165E+09 | 0.915987E+09 | 0.538844E+09 | 0.377143E+09 | 0.00 | 0.00 |
November | 0.627782E+09 | 0.926931E+09 | 0.789191E+09 | 0.495219E+09 | 0.293971E+09 | 0.00 | 0.00 |
December | 0.571620E+09 | 0.143287E+10 | 0.867963E+09 | 0.569046E+09 | 0.298918E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.103146E+11 | 0.894907E+10 | 0.121001E+11 | 0.646149E+10 | 0.563858E+10 | 0.00 | 0.00 |
Minimum of Months | 0.571620E+09 | 0.267414E+09 | 0.789191E+09 | 0.221032E+09 | 0.293971E+09 | 0.00 | 0.00 |
Maximum of Months | 0.107028E+10 | 0.146251E+10 | 0.128599E+10 | 0.868580E+09 | 0.640468E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.164425E+10 | 0.286393E+10 | 0.224824E+10 | 0.156384E+10 | 0.684398E+09 | 0.00 | 0.00 |
February | 0.215961E+10 | 0.214839E+10 | 0.257197E+10 | 0.173716E+10 | 0.834813E+09 | 0.00 | 0.00 |
March | 0.205866E+10 | 0.199070E+10 | 0.251030E+10 | 0.158909E+10 | 0.921207E+09 | 0.00 | 0.00 |
April | 0.186549E+10 | 0.124722E+10 | 0.220019E+10 | 0.119434E+10 | 0.100585E+10 | 0.00 | 0.00 |
May | 0.166777E+10 | 0.742446E+09 | 0.191087E+10 | 0.653080E+09 | 0.125779E+10 | 0.00 | 0.00 |
June | 0.151456E+10 | 0.522480E+09 | 0.165926E+10 | 0.442063E+09 | 0.121720E+10 | 0.00 | 0.00 |
July | 0.180421E+10 | 0.518570E+09 | 0.187458E+10 | 0.593645E+09 | 0.128094E+10 | 0.00 | 0.00 |
August | 0.198176E+10 | 0.615353E+09 | 0.200220E+10 | 0.837458E+09 | 0.116474E+10 | 0.00 | 0.00 |
September | 0.201882E+10 | 0.888763E+09 | 0.207625E+10 | 0.110609E+10 | 0.970167E+09 | 0.00 | 0.00 |
October | 0.163507E+10 | 0.131015E+10 | 0.183197E+10 | 0.107769E+10 | 0.754286E+09 | 0.00 | 0.00 |
November | 0.126873E+10 | 0.180452E+10 | 0.157838E+10 | 0.990439E+09 | 0.587943E+09 | 0.00 | 0.00 |
December | 0.115667E+10 | 0.280250E+10 | 0.173593E+10 | 0.113809E+10 | 0.597835E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.207756E+11 | 0.174550E+11 | 0.242001E+11 | 0.129230E+11 | 0.112772E+11 | 0.00 | 0.00 |
Minimum of Months | 0.115667E+10 | 0.518570E+09 | 0.157838E+10 | 0.442063E+09 | 0.587943E+09 | 0.00 | 0.00 |
Maximum of Months | 0.215961E+10 | 0.286393E+10 | 0.257197E+10 | 0.173716E+10 | 0.128094E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.817729E+09 | 0.144256E+10 | 0.112412E+10 | 0.781921E+09 | 0.342199E+09 | 0.00 | 0.00 |
February | 0.107516E+10 | 0.108159E+10 | 0.128599E+10 | 0.868580E+09 | 0.417407E+09 | 0.00 | 0.00 |
March | 0.102610E+10 | 0.100160E+10 | 0.125515E+10 | 0.794545E+09 | 0.460603E+09 | 0.00 | 0.00 |
April | 0.930917E+09 | 0.625808E+09 | 0.110009E+10 | 0.597171E+09 | 0.502924E+09 | 0.00 | 0.00 |
May | 0.833956E+09 | 0.370476E+09 | 0.955434E+09 | 0.326540E+09 | 0.628894E+09 | 0.00 | 0.00 |
June | 0.758308E+09 | 0.259589E+09 | 0.829631E+09 | 0.221032E+09 | 0.608600E+09 | 0.00 | 0.00 |
July | 0.903496E+09 | 0.257069E+09 | 0.937291E+09 | 0.296822E+09 | 0.640468E+09 | 0.00 | 0.00 |
August | 0.991038E+09 | 0.305890E+09 | 0.100110E+10 | 0.418729E+09 | 0.582371E+09 | 0.00 | 0.00 |
September | 0.100827E+10 | 0.444110E+09 | 0.103813E+10 | 0.553043E+09 | 0.485084E+09 | 0.00 | 0.00 |
October | 0.815777E+09 | 0.656594E+09 | 0.915987E+09 | 0.538844E+09 | 0.377143E+09 | 0.00 | 0.00 |
November | 0.631669E+09 | 0.907904E+09 | 0.789191E+09 | 0.495219E+09 | 0.293971E+09 | 0.00 | 0.00 |
December | 0.574882E+09 | 0.141246E+10 | 0.867963E+09 | 0.569046E+09 | 0.298918E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.103673E+11 | 0.876566E+10 | 0.121001E+11 | 0.646149E+10 | 0.563858E+10 | 0.00 | 0.00 |
Minimum of Months | 0.574882E+09 | 0.257069E+09 | 0.789191E+09 | 0.221032E+09 | 0.293971E+09 | 0.00 | 0.00 |
Maximum of Months | 0.107516E+10 | 0.144256E+10 | 0.128599E+10 | 0.868580E+09 | 0.640468E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.817885E+09 | 0.144165E+10 | 0.112412E+10 | 0.781921E+09 | 0.342199E+09 | 0.00 | 0.00 |
February | 0.107546E+10 | 0.108037E+10 | 0.128599E+10 | 0.868580E+09 | 0.417407E+09 | 0.00 | 0.00 |
March | 0.102659E+10 | 0.999387E+09 | 0.125515E+10 | 0.794545E+09 | 0.460603E+09 | 0.00 | 0.00 |
April | 0.932111E+09 | 0.622209E+09 | 0.110009E+10 | 0.597171E+09 | 0.502924E+09 | 0.00 | 0.00 |
May | 0.836172E+09 | 0.367012E+09 | 0.955434E+09 | 0.326540E+09 | 0.628894E+09 | 0.00 | 0.00 |
June | 0.760399E+09 | 0.256948E+09 | 0.829631E+09 | 0.221032E+09 | 0.608600E+09 | 0.00 | 0.00 |
July | 0.904683E+09 | 0.255377E+09 | 0.937291E+09 | 0.296822E+09 | 0.640468E+09 | 0.00 | 0.00 |
August | 0.992008E+09 | 0.304064E+09 | 0.100110E+10 | 0.418729E+09 | 0.582371E+09 | 0.00 | 0.00 |
September | 0.100939E+10 | 0.441751E+09 | 0.103813E+10 | 0.553043E+09 | 0.485084E+09 | 0.00 | 0.00 |
October | 0.816500E+09 | 0.654166E+09 | 0.915987E+09 | 0.538844E+09 | 0.377143E+09 | 0.00 | 0.00 |
November | 0.632166E+09 | 0.905443E+09 | 0.789191E+09 | 0.495219E+09 | 0.293971E+09 | 0.00 | 0.00 |
December | 0.575026E+09 | 0.141142E+10 | 0.867963E+09 | 0.569046E+09 | 0.298918E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.103784E+11 | 0.873980E+10 | 0.121001E+11 | 0.646149E+10 | 0.563858E+10 | 0.00 | 0.00 |
Minimum of Months | 0.575026E+09 | 0.255377E+09 | 0.789191E+09 | 0.221032E+09 | 0.293971E+09 | 0.00 | 0.00 |
Maximum of Months | 0.107546E+10 | 0.144165E+10 | 0.128599E+10 | 0.868580E+09 | 0.640468E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.818816E+09 | 0.143494E+10 | 0.112412E+10 | 0.781921E+09 | 0.342199E+09 | 0.00 | 0.00 |
February | 0.107688E+10 | 0.107317E+10 | 0.128599E+10 | 0.868580E+09 | 0.417407E+09 | 0.00 | 0.00 |
March | 0.102863E+10 | 0.988130E+09 | 0.125515E+10 | 0.794545E+09 | 0.460603E+09 | 0.00 | 0.00 |
April | 0.936072E+09 | 0.608032E+09 | 0.110009E+10 | 0.597171E+09 | 0.502924E+09 | 0.00 | 0.00 |
May | 0.842764E+09 | 0.355426E+09 | 0.955434E+09 | 0.326540E+09 | 0.628894E+09 | 0.00 | 0.00 |
June | 0.766381E+09 | 0.248634E+09 | 0.829631E+09 | 0.221032E+09 | 0.608600E+09 | 0.00 | 0.00 |
July | 0.907677E+09 | 0.250460E+09 | 0.937291E+09 | 0.296822E+09 | 0.640468E+09 | 0.00 | 0.00 |
August | 0.994337E+09 | 0.298998E+09 | 0.100110E+10 | 0.418729E+09 | 0.582371E+09 | 0.00 | 0.00 |
September | 0.101221E+10 | 0.434904E+09 | 0.103813E+10 | 0.553043E+09 | 0.485084E+09 | 0.00 | 0.00 |
October | 0.818507E+09 | 0.645868E+09 | 0.915987E+09 | 0.538844E+09 | 0.377143E+09 | 0.00 | 0.00 |
November | 0.633915E+09 | 0.895165E+09 | 0.789191E+09 | 0.495219E+09 | 0.293971E+09 | 0.00 | 0.00 |
December | 0.575810E+09 | 0.140429E+10 | 0.867963E+09 | 0.569046E+09 | 0.298918E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.104120E+11 | 0.863802E+10 | 0.121001E+11 | 0.646149E+10 | 0.563858E+10 | 0.00 | 0.00 |
Minimum of Months | 0.575810E+09 | 0.248634E+09 | 0.789191E+09 | 0.221032E+09 | 0.293971E+09 | 0.00 | 0.00 |
Maximum of Months | 0.107688E+10 | 0.143494E+10 | 0.128599E+10 | 0.868580E+09 | 0.640468E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.825540E+09 | 0.139731E+10 | 0.112412E+10 | 0.781921E+09 | 0.342199E+09 | 0.00 | 0.00 |
February | 0.108514E+10 | 0.103584E+10 | 0.128599E+10 | 0.868580E+09 | 0.417407E+09 | 0.00 | 0.00 |
March | 0.103860E+10 | 0.935169E+09 | 0.125515E+10 | 0.794545E+09 | 0.460603E+09 | 0.00 | 0.00 |
April | 0.950519E+09 | 0.551216E+09 | 0.110009E+10 | 0.597171E+09 | 0.502924E+09 | 0.00 | 0.00 |
May | 0.864951E+09 | 0.312860E+09 | 0.955434E+09 | 0.326540E+09 | 0.628894E+09 | 0.00 | 0.00 |
June | 0.785893E+09 | 0.218491E+09 | 0.829631E+09 | 0.221032E+09 | 0.608600E+09 | 0.00 | 0.00 |
July | 0.918355E+09 | 0.230530E+09 | 0.937291E+09 | 0.296822E+09 | 0.640468E+09 | 0.00 | 0.00 |
August | 0.100173E+10 | 0.279407E+09 | 0.100110E+10 | 0.418729E+09 | 0.582371E+09 | 0.00 | 0.00 |
September | 0.101998E+10 | 0.410389E+09 | 0.103813E+10 | 0.553043E+09 | 0.485084E+09 | 0.00 | 0.00 |
October | 0.825065E+09 | 0.613196E+09 | 0.915987E+09 | 0.538844E+09 | 0.377143E+09 | 0.00 | 0.00 |
November | 0.640580E+09 | 0.852999E+09 | 0.789191E+09 | 0.495219E+09 | 0.293971E+09 | 0.00 | 0.00 |
December | 0.580803E+09 | 0.136540E+10 | 0.867963E+09 | 0.569046E+09 | 0.298918E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.105372E+11 | 0.820281E+10 | 0.121001E+11 | 0.646149E+10 | 0.563858E+10 | 0.00 | 0.00 |
Minimum of Months | 0.580803E+09 | 0.218491E+09 | 0.789191E+09 | 0.221032E+09 | 0.293971E+09 | 0.00 | 0.00 |
Maximum of Months | 0.108514E+10 | 0.139731E+10 | 0.128599E+10 | 0.868580E+09 | 0.640468E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -16.9 | -17.3 | -20.0 | 3.73 | -31.9 | 33.25 | 98.18 | 0.00 |
February | -11.6 | -12.6 | -16.7 | 4.33 | -26.7 | 48.91 | 138.70 | 0.00 |
March | -6.2 | -7.5 | -10.8 | 3.55 | -19.4 | 56.69 | 163.76 | 0.01 |
April | 3.97 | 0.48 | -4.8 | 4.72 | -9.1 | 70.41 | 207.70 | 0.01 |
May | 13.43 | 8.45 | 3.53 | 3.60 | 2.20 | 102.27 | 202.62 | 0.00 |
June | 18.03 | 14.18 | 11.55 | 3.74 | 7.84 | 104.36 | 210.60 | 0.06 |
July | 19.67 | 16.51 | 14.78 | 3.14 | 8.96 | 101.67 | 223.82 | 0.04 |
August | 17.94 | 15.19 | 13.59 | 3.45 | 8.98 | 87.39 | 175.79 | 0.04 |
September | 12.29 | 9.87 | 7.80 | 3.78 | 3.33 | 70.27 | 143.96 | 0.00 |
October | 5.42 | 3.48 | 1.07 | 3.53 | -4.7 | 51.74 | 90.11 | 0.00 |
November | -2.0 | -3.6 | -6.9 | 4.42 | -13.7 | 34.68 | 65.95 | 0.00 |
December | -14.6 | -15.1 | -18.1 | 3.91 | -28.3 | 29.58 | 68.99 | 0.00 |
Annual Sum or Average | 3.36 | 1.07 | -2.0 | 3.82 | -8.5 | 66.03 | 149.18 | 0.01 |
Minimum of Months | -16.9 | -17.3 | -20.0 | 3.14 | -31.9 | 29.58 | 65.95 | 0.00 |
Maximum of Months | 19.67 | 16.51 | 14.78 | 4.72 | 8.98 | 104.36 | 223.82 | 0.06 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 1.10 | 29-JAN-14:00 | -0.9 | -4.4 | 2.60 | -11.4 | 145.00 | 110.00 |
February | 8.90 | 20-FEB-15:00 | 2.85 | -6.7 | 8.80 | -9.0 | 49.00 | 646.00 |
March | 11.10 | 26-MAR-15:00 | 5.46 | -1.1 | 5.20 | -5.7 | 53.00 | 842.00 |
April | 26.70 | 23-APR-15:00 | 16.93 | 11.10 | 11.30 | 12.03 | 75.50 | 811.00 |
May | 29.40 | 25-MAY-17:00 | 19.24 | 13.90 | 1.50 | 16.49 | 47.50 | 582.00 |
June | 35.00 | 29-JUN-15:00 | 24.70 | 21.10 | 6.70 | 24.66 | 132.00 | 705.00 |
July | 31.10 | 15-JUL-14:20 | 25.34 | 23.33 | 8.07 | 19.92 | 299.67 | 518.33 |
August | 30.60 | 08-AUG-14:00 | 23.35 | 20.60 | 6.70 | 17.93 | 163.50 | 672.50 |
September | 26.10 | 01-SEP-14:00 | 17.80 | 13.30 | 3.60 | 14.28 | 112.00 | 751.50 |
October | 22.20 | 19-OCT-14:00 | 13.60 | 7.20 | 6.70 | 8.15 | 35.50 | 701.50 |
November | 18.30 | 01-NOV-14:00 | 13.43 | 10.00 | 3.10 | 11.84 | 105.00 | 30.50 |
December | 1.10 | 28-DEC-02:00 | 0.43 | -0.6 | 4.60 | -5.5 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 1.10 | -0.9 | -6.7 | 1.50 | -11.4 | 0.00 | 0.00 | |
Maximum of Months | 35.00 | 25.34 | 23.33 | 11.30 | 24.66 | 299.67 | 842.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -35.6 | 06-JAN-08:00 | -35.7 | -37.8 | 0.00 | -57.8 | 27.00 | 381.00 |
February | -33.3 | 14-FEB-06:00 | -33.4 | -36.7 | 0.00 | -55.6 | 0.00 | 0.00 |
March | -28.9 | 05-MAR-06:00 | -29.1 | -32.2 | 1.50 | -50.6 | 27.00 | 41.50 |
April | -13.9 | 05-APR-05:00 | -14.3 | -16.1 | 0.00 | -32.5 | 14.50 | 199.00 |
May | -3.9 | 01-MAY-05:00 | -6.0 | -12.2 | 0.00 | -22.4 | 35.00 | 415.00 |
June | 1.10 | 04-JUN-04:00 | 0.61 | 0.00 | 0.00 | -14.9 | 37.00 | 169.50 |
July | 6.10 | 02-JUL-04:00 | 6.10 | 6.10 | 0.00 | -8.8 | 33.50 | 204.50 |
August | 4.40 | 19-AUG-03:00 | 4.40 | 4.40 | 0.00 | -10.7 | 0.00 | 0.00 |
September | 1.10 | 06-SEP-03:00 | 1.10 | 1.10 | 0.00 | -14.7 | 0.00 | 0.00 |
October | -10.0 | 30-OCT-03:00 | -10.6 | -12.8 | 1.50 | -28.2 | 0.00 | 0.00 |
November | -20.6 | 29-NOV-05:00 | -20.8 | -22.2 | 2.10 | -37.8 | 0.00 | 0.00 |
December | -31.1 | 24-DEC-06:19 | -31.3 | -35.1 | 3.33 | -53.1 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -35.6 | -35.7 | -37.8 | 0.00 | -57.8 | 0.00 | 0.00 | |
Maximum of Months | 6.10 | 6.10 | 6.10 | 3.33 | -8.8 | 37.00 | 415.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -0.4 | 16-JAN-12:00 | 0.00 | -1.1 | 5.70 | -6.6 | 172.50 | 3.00 |
February | 3.33 | 21-FEB-12:00 | 6.70 | -1.1 | 7.70 | -6.0 | 270.00 | 303.00 |
March | 5.46 | 26-MAR-15:00 | 11.10 | -1.1 | 5.20 | -5.7 | 53.00 | 842.00 |
April | 16.93 | 23-APR-15:00 | 26.70 | 11.10 | 11.30 | 12.03 | 75.50 | 811.00 |
May | 19.90 | 26-MAY-11:00 | 25.60 | 17.20 | 6.20 | 22.64 | 300.50 | 6.00 |
June | 24.70 | 29-JUN-15:00 | 35.00 | 21.10 | 6.70 | 24.66 | 132.00 | 705.00 |
July | 25.75 | 15-JUL-13:00 | 31.10 | 23.90 | 7.70 | 18.99 | 333.00 | 421.00 |
August | 23.35 | 08-AUG-14:00 | 30.60 | 20.60 | 6.70 | 17.93 | 163.50 | 672.50 |
September | 18.67 | 01-SEP-00:00 | 19.00 | 17.50 | 2.80 | 16.30 | 0.00 | 0.00 |
October | 13.70 | 19-OCT-13:00 | 21.70 | 7.80 | 5.70 | 7.75 | 54.50 | 739.00 |
November | 14.29 | 21-NOV-12:00 | 15.00 | 13.90 | 5.20 | 11.46 | 134.50 | 25.50 |
December | 0.43 | 28-DEC-02:00 | 1.10 | -0.6 | 4.60 | -5.5 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -0.4 | 0.00 | -1.1 | 2.80 | -6.6 | 0.00 | 0.00 | |
Maximum of Months | 25.75 | 35.00 | 23.90 | 11.30 | 24.66 | 333.00 | 842.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -1.1 | 16-JAN-11:00 | -0.6 | -0.8 | 5.70 | -7.3 | 164.50 | 5.00 |
February | -0.6 | 21-FEB-08:00 | 4.40 | 2.24 | 8.80 | -6.6 | 123.00 | 89.50 |
March | 0.00 | 29-MAR-20:00 | 1.70 | 0.95 | 1.50 | -4.8 | 0.00 | 0.00 |
April | 11.10 | 23-APR-13:00 | 24.40 | 16.06 | 10.80 | 9.72 | 98.50 | 903.50 |
May | 17.20 | 26-MAY-11:00 | 25.60 | 19.90 | 6.20 | 22.64 | 300.50 | 6.00 |
June | 22.80 | 29-JUN-23:19 | 26.30 | 23.71 | 5.20 | 14.28 | 0.00 | 0.00 |
July | 23.90 | 15-JUL-13:00 | 31.10 | 25.75 | 7.70 | 18.99 | 333.00 | 421.00 |
August | 20.60 | 08-AUG-14:00 | 30.60 | 23.35 | 6.70 | 17.93 | 163.50 | 672.50 |
September | 17.92 | 01-SEP-00:10 | 19.75 | 18.15 | 3.22 | 13.22 | 0.00 | 0.00 |
October | 12.20 | 07-OCT-12:20 | 14.47 | 13.16 | 3.43 | 9.18 | 163.17 | 18.50 |
November | 13.90 | 21-NOV-12:00 | 15.00 | 14.29 | 5.20 | 11.46 | 134.50 | 25.50 |
December | -0.0 | 06-DEC-02:00 | 0.00 | -0.0 | 3.60 | -6.4 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -1.1 | -0.6 | -0.8 | 1.50 | -7.3 | 0.00 | 0.00 | |
Maximum of Months | 23.90 | 31.10 | 25.75 | 10.80 | 22.64 | 333.00 | 903.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 1.89 | 11.66 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 0.58 | 19.92 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 0.81 | 26.63 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 2.58 | 37.52 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 5.43 | 45.25 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 8.61 | 47.76 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 11.25 | 48.86 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 12.66 | 38.94 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 12.41 | 29.23 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 10.60 | 17.37 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 7.72 | 10.89 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 4.55 | 9.11 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 6.63 | 28.63 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 0.58 | 9.11 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 12.66 | 48.86 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK1
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.407195E+09 | -280351520.8 | 0.00 | 0.00 | 744.00 | 0.00 | -126843919.9 | 59.00 | 0.00 | 0.00 |
February | 0.374747E+09 | -260421388.8 | 0.00 | 0.00 | 672.00 | 0.00 | -114325435.7 | 58.99 | 0.00 | 0.00 |
March | 0.417437E+09 | -291685399.8 | 0.00 | 0.00 | 744.00 | 0.00 | -125751693.2 | 58.99 | 0.00 | 0.00 |
April | 0.389789E+09 | -270596767.9 | 0.00 | 0.00 | 720.00 | 0.00 | -119191961.2 | 58.99 | 0.00 | 0.00 |
May | 0.382413E+09 | -265730596.0 | 0.00 | 0.00 | 744.00 | 0.00 | -116682335.1 | 58.99 | 0.00 | 0.00 |
June | 0.354250E+09 | -244139418.0 | 0.00 | 0.00 | 720.00 | 0.00 | -110110083.5 | 58.99 | 0.00 | 0.00 |
July | 0.347056E+09 | -234516666.7 | 0.00 | 0.00 | 744.00 | 0.00 | -112538849.6 | 58.99 | 0.00 | 0.00 |
August | 0.344727E+09 | -232115844.6 | 0.00 | 0.00 | 744.00 | 0.00 | -112611056.1 | 58.99 | 0.00 | 0.00 |
September | 0.334987E+09 | -223627958.9 | 0.00 | 0.00 | 720.00 | 0.00 | -111358749.8 | 58.99 | 0.00 | 0.00 |
October | 0.358375E+09 | -237653744.0 | 0.00 | 0.00 | 744.00 | 0.00 | -120720786.3 | 58.99 | 0.00 | 0.00 |
November | 0.363131E+09 | -242958515.1 | 0.00 | 0.00 | 720.00 | 0.00 | -120172495.1 | 58.99 | 0.00 | 0.00 |
December | 0.394293E+09 | -267640149.6 | 0.00 | 0.00 | 744.00 | 0.00 | -126652692.6 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.446840E+10 | -.305144E+10 | 8760.00 | -.141696E+10 | 58.99 | |||||
Minimum of Months | 0.334987E+09 | -291685399.8 | 0.00 | 0.00 | 672.00 | 0.00 | -126843919.9 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.417437E+09 | -223627958.9 | 0.00 | 0.00 | 744.00 | 0.00 | -110110083.5 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK2
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.405843E+09 | -280355090.4 | 0.00 | 0.00 | 744.00 | 0.00 | -125488180.1 | 59.00 | 0.00 | 0.00 |
February | 0.373143E+09 | -260432120.9 | 0.00 | 0.00 | 672.00 | 0.00 | -112710636.6 | 58.99 | 0.00 | 0.00 |
March | 0.415355E+09 | -291676152.1 | 0.00 | 0.00 | 744.00 | 0.00 | -123678768.2 | 58.99 | 0.00 | 0.00 |
April | 0.387206E+09 | -270605306.9 | 0.00 | 0.00 | 720.00 | 0.00 | -116600415.7 | 58.99 | 0.00 | 0.00 |
May | 0.380908E+09 | -265735119.8 | 0.00 | 0.00 | 744.00 | 0.00 | -115172426.7 | 58.99 | 0.00 | 0.00 |
June | 0.353502E+09 | -244142625.0 | 0.00 | 0.00 | 720.00 | 0.00 | -109358950.5 | 58.99 | 0.00 | 0.00 |
July | 0.346703E+09 | -234519539.3 | 0.00 | 0.00 | 744.00 | 0.00 | -112183235.4 | 58.99 | 0.00 | 0.00 |
August | 0.344383E+09 | -232123299.8 | 0.00 | 0.00 | 744.00 | 0.00 | -112259486.2 | 58.99 | 0.00 | 0.00 |
September | 0.334123E+09 | -223624678.6 | 0.00 | 0.00 | 720.00 | 0.00 | -110497881.1 | 58.99 | 0.00 | 0.00 |
October | 0.356310E+09 | -237652751.8 | 0.00 | 0.00 | 744.00 | 0.00 | -118657624.8 | 58.99 | 0.00 | 0.00 |
November | 0.361143E+09 | -242956630.7 | 0.00 | 0.00 | 720.00 | 0.00 | -118186524.3 | 58.99 | 0.00 | 0.00 |
December | 0.392683E+09 | -267642210.3 | 0.00 | 0.00 | 744.00 | 0.00 | -125041262.1 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.445130E+10 | -.305147E+10 | 8760.00 | -.139984E+10 | 58.99 | |||||
Minimum of Months | 0.334123E+09 | -291676152.1 | 0.00 | 0.00 | 672.00 | 0.00 | -125488180.1 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.415355E+09 | -223624678.6 | 0.00 | 0.00 | 744.00 | 0.00 | -109358950.5 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK3
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.374696E+09 | -246547088.3 | 0.00 | 0.00 | 744.00 | 0.00 | -128149002.1 | 58.99 | 0.00 | 0.00 |
February | 0.344168E+09 | -229186534.4 | 0.00 | 0.00 | 672.00 | 0.00 | -114981393.2 | 58.99 | 0.00 | 0.00 |
March | 0.386400E+09 | -260508304.0 | 0.00 | 0.00 | 744.00 | 0.00 | -125891983.3 | 59.00 | 0.00 | 0.00 |
April | 0.356616E+09 | -237823522.4 | 0.00 | 0.00 | 720.00 | 0.00 | -118792971.3 | 58.99 | 0.00 | 0.00 |
May | 0.351768E+09 | -235695742.1 | 0.00 | 0.00 | 744.00 | 0.00 | -116072126.8 | 58.99 | 0.00 | 0.00 |
June | 0.326717E+09 | -217576945.5 | 0.00 | 0.00 | 720.00 | 0.00 | -109140408.8 | 59.00 | 0.00 | 0.00 |
July | 0.315874E+09 | -204852288.4 | 0.00 | 0.00 | 744.00 | 0.00 | -111021796.4 | 58.99 | 0.00 | 0.00 |
August | 0.318915E+09 | -207497503.9 | 0.00 | 0.00 | 744.00 | 0.00 | -111417544.6 | 58.99 | 0.00 | 0.00 |
September | 0.307501E+09 | -196397698.5 | 0.00 | 0.00 | 720.00 | 0.00 | -111103069.9 | 58.99 | 0.00 | 0.00 |
October | 0.329875E+09 | -209003090.4 | 0.00 | 0.00 | 744.00 | 0.00 | -120871417.7 | 59.00 | 0.00 | 0.00 |
November | 0.335094E+09 | -214501049.1 | 0.00 | 0.00 | 720.00 | 0.00 | -120593167.4 | 59.00 | 0.00 | 0.00 |
December | 0.361364E+09 | -233624238.9 | 0.00 | 0.00 | 744.00 | 0.00 | -127739635.2 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.410899E+10 | -.269321E+10 | 8760.00 | -.141577E+10 | 58.99 | |||||
Minimum of Months | 0.307501E+09 | -260508304.0 | 0.00 | 0.00 | 672.00 | 0.00 | -128149002.1 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.386400E+09 | -196397698.5 | 0.00 | 0.00 | 744.00 | 0.00 | -109140408.8 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK4
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.375197E+09 | -246543628.6 | 0.00 | 0.00 | 744.00 | 0.00 | -128653869.5 | 58.99 | 0.00 | 0.00 |
February | 0.344669E+09 | -229180070.7 | 0.00 | 0.00 | 672.00 | 0.00 | -115488617.6 | 58.99 | 0.00 | 0.00 |
March | 0.386934E+09 | -260506687.4 | 0.00 | 0.00 | 744.00 | 0.00 | -126427697.4 | 59.00 | 0.00 | 0.00 |
April | 0.357226E+09 | -237789840.2 | 0.00 | 0.00 | 720.00 | 0.00 | -119435820.9 | 59.00 | 0.00 | 0.00 |
May | 0.352277E+09 | -235706782.0 | 0.00 | 0.00 | 744.00 | 0.00 | -116570698.0 | 58.99 | 0.00 | 0.00 |
June | 0.326997E+09 | -217605169.3 | 0.00 | 0.00 | 720.00 | 0.00 | -109391437.5 | 58.99 | 0.00 | 0.00 |
July | 0.315999E+09 | -204833357.8 | 0.00 | 0.00 | 744.00 | 0.00 | -111165490.6 | 59.00 | 0.00 | 0.00 |
August | 0.319052E+09 | -207491811.5 | 0.00 | 0.00 | 744.00 | 0.00 | -111560587.1 | 58.99 | 0.00 | 0.00 |
September | 0.307913E+09 | -196396260.5 | 0.00 | 0.00 | 720.00 | 0.00 | -111517167.0 | 58.99 | 0.00 | 0.00 |
October | 0.330448E+09 | -208975126.9 | 0.00 | 0.00 | 744.00 | 0.00 | -121472677.9 | 59.01 | 0.00 | 0.00 |
November | 0.335658E+09 | -214519776.5 | 0.00 | 0.00 | 720.00 | 0.00 | -121137902.3 | 58.99 | 0.00 | 0.00 |
December | 0.361885E+09 | -233612771.0 | 0.00 | 0.00 | 744.00 | 0.00 | -128272456.2 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.411426E+10 | -.269316E+10 | 8760.00 | -.142109E+10 | 58.99 | |||||
Minimum of Months | 0.307913E+09 | -260506687.4 | 0.00 | 0.00 | 672.00 | 0.00 | -128653869.5 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.386934E+09 | -196396260.5 | 0.00 | 0.00 | 744.00 | 0.00 | -109391437.5 | 59.01 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK5
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.363163E+09 | -233024567.0 | 0.00 | 0.00 | 744.00 | 0.00 | -130138516.8 | 58.99 | 0.00 | 0.00 |
February | 0.333678E+09 | -216716464.8 | 0.00 | 0.00 | 672.00 | 0.00 | -116961111.4 | 59.00 | 0.00 | 0.00 |
March | 0.374482E+09 | -246518254.5 | 0.00 | 0.00 | 744.00 | 0.00 | -127963592.4 | 58.99 | 0.00 | 0.00 |
April | 0.345931E+09 | -225040275.2 | 0.00 | 0.00 | 720.00 | 0.00 | -120890473.0 | 58.99 | 0.00 | 0.00 |
May | 0.340794E+09 | -222893277.0 | 0.00 | 0.00 | 744.00 | 0.00 | -117900890.4 | 58.99 | 0.00 | 0.00 |
June | 0.316346E+09 | -205907813.5 | 0.00 | 0.00 | 720.00 | 0.00 | -110438428.0 | 58.99 | 0.00 | 0.00 |
July | 0.305593E+09 | -193730802.5 | 0.00 | 0.00 | 744.00 | 0.00 | -111862409.7 | 58.99 | 0.00 | 0.00 |
August | 0.308631E+09 | -196330421.8 | 0.00 | 0.00 | 744.00 | 0.00 | -112300229.6 | 58.99 | 0.00 | 0.00 |
September | 0.298303E+09 | -185854043.7 | 0.00 | 0.00 | 720.00 | 0.00 | -112448850.9 | 58.99 | 0.00 | 0.00 |
October | 0.319975E+09 | -197554979.4 | 0.00 | 0.00 | 744.00 | 0.00 | -122420007.8 | 58.99 | 0.00 | 0.00 |
November | 0.325161E+09 | -202592164.3 | 0.00 | 0.00 | 720.00 | 0.00 | -122568775.1 | 58.99 | 0.00 | 0.00 |
December | 0.350756E+09 | -220930448.0 | 0.00 | 0.00 | 744.00 | 0.00 | -129825633.5 | 59.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.398281E+10 | -.254709E+10 | 8760.00 | -.143572E+10 | 58.99 | |||||
Minimum of Months | 0.298303E+09 | -246518254.5 | 0.00 | 0.00 | 672.00 | 0.00 | -130138516.8 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.374482E+09 | -185854043.7 | 0.00 | 0.00 | 744.00 | 0.00 | -110438428.0 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK6
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.363030E+09 | -233030919.6 | 0.00 | 0.00 | 744.00 | 0.00 | -129999104.9 | 58.99 | 0.00 | 0.00 |
February | 0.333569E+09 | -216712795.1 | 0.00 | 0.00 | 672.00 | 0.00 | -116856247.2 | 59.00 | 0.00 | 0.00 |
March | 0.374381E+09 | -246508998.9 | 0.00 | 0.00 | 744.00 | 0.00 | -127872219.8 | 58.99 | 0.00 | 0.00 |
April | 0.345883E+09 | -225049198.1 | 0.00 | 0.00 | 720.00 | 0.00 | -120833955.9 | 58.99 | 0.00 | 0.00 |
May | 0.340839E+09 | -222893688.1 | 0.00 | 0.00 | 744.00 | 0.00 | -117945791.5 | 59.00 | 0.00 | 0.00 |
June | 0.316410E+09 | -205901556.1 | 0.00 | 0.00 | 720.00 | 0.00 | -110508860.1 | 58.99 | 0.00 | 0.00 |
July | 0.305704E+09 | -193727922.3 | 0.00 | 0.00 | 744.00 | 0.00 | -111975817.2 | 58.99 | 0.00 | 0.00 |
August | 0.308705E+09 | -196333940.8 | 0.00 | 0.00 | 744.00 | 0.00 | -112370636.2 | 58.99 | 0.00 | 0.00 |
September | 0.298317E+09 | -185858406.9 | 0.00 | 0.00 | 720.00 | 0.00 | -112459029.5 | 58.99 | 0.00 | 0.00 |
October | 0.319979E+09 | -197556305.6 | 0.00 | 0.00 | 744.00 | 0.00 | -122422626.4 | 58.99 | 0.00 | 0.00 |
November | 0.325089E+09 | -202596806.7 | 0.00 | 0.00 | 720.00 | 0.00 | -122492555.9 | 58.99 | 0.00 | 0.00 |
December | 0.350616E+09 | -220935149.4 | 0.00 | 0.00 | 744.00 | 0.00 | -129680592.9 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.398252E+10 | -.254711E+10 | 8760.00 | -.143542E+10 | 58.99 | |||||
Minimum of Months | 0.298317E+09 | -246508998.9 | 0.00 | 0.00 | 672.00 | 0.00 | -129999104.9 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.374381E+09 | -185858406.9 | 0.00 | 0.00 | 744.00 | 0.00 | -110508860.1 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK7
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.363062E+09 | -233029452.8 | 0.00 | 0.00 | 744.00 | 0.00 | -130032217.1 | 58.99 | 0.00 | 0.00 |
February | 0.333614E+09 | -216713732.8 | 0.00 | 0.00 | 672.00 | 0.00 | -116900504.4 | 59.00 | 0.00 | 0.00 |
March | 0.374468E+09 | -246513454.2 | 0.00 | 0.00 | 744.00 | 0.00 | -127954492.4 | 58.99 | 0.00 | 0.00 |
April | 0.346066E+09 | -225043949.4 | 0.00 | 0.00 | 720.00 | 0.00 | -121022127.0 | 58.99 | 0.00 | 0.00 |
May | 0.341060E+09 | -222903723.1 | 0.00 | 0.00 | 744.00 | 0.00 | -118155953.2 | 58.99 | 0.00 | 0.00 |
June | 0.316604E+09 | -205873439.2 | 0.00 | 0.00 | 720.00 | 0.00 | -110730247.9 | 59.00 | 0.00 | 0.00 |
July | 0.305821E+09 | -193729104.6 | 0.00 | 0.00 | 744.00 | 0.00 | -112092226.4 | 58.99 | 0.00 | 0.00 |
August | 0.308810E+09 | -196325395.9 | 0.00 | 0.00 | 744.00 | 0.00 | -112485044.4 | 58.99 | 0.00 | 0.00 |
September | 0.298461E+09 | -185852360.9 | 0.00 | 0.00 | 720.00 | 0.00 | -112608629.7 | 58.99 | 0.00 | 0.00 |
October | 0.320093E+09 | -197556277.1 | 0.00 | 0.00 | 744.00 | 0.00 | -122537083.1 | 58.99 | 0.00 | 0.00 |
November | 0.325190E+09 | -202600746.1 | 0.00 | 0.00 | 720.00 | 0.00 | -122588758.4 | 58.99 | 0.00 | 0.00 |
December | 0.350652E+09 | -220935612.2 | 0.00 | 0.00 | 744.00 | 0.00 | -129716642.4 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.398390E+10 | -.254708E+10 | 8760.00 | -.143682E+10 | 58.99 | |||||
Minimum of Months | 0.298461E+09 | -246513454.2 | 0.00 | 0.00 | 672.00 | 0.00 | -130032217.1 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.374468E+09 | -185852360.9 | 0.00 | 0.00 | 744.00 | 0.00 | -110730247.9 | 59.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 243.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 265.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 254.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 296.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 437.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 401.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 409.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 352.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 344.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 299.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 255.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 226.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3785.50 | ||||||||||
Minimum of Months | 226.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 437.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.563247E+11 | 89352.93 | 01-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.388020E+11 | 89352.93 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.326258E+11 | 89352.93 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.123606E+11 | 89352.93 | 01-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.897757E+09 | 89352.93 | 01-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 3131777.82 | 2059.23 | 04-JUN-07:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.175383E+09 | 9329.02 | 23-SEP-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.708331E+10 | 89352.93 | 06-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.225701E+11 | 89352.93 | 03-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.517610E+11 | 89352.93 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.222604E+12 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.563247E+11 | 89352.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.225613E+11 | 45813.83 | 01-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.149332E+11 | 45813.83 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.123669E+11 | 45813.83 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.406022E+10 | 45813.83 | 02-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.194467E+09 | 34104.20 | 01-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 25551436.49 | 3179.78 | 23-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.246587E+10 | 45813.83 | 30-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.848385E+10 | 45813.83 | 06-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.207149E+11 | 45813.83 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.858062E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.225613E+11 | 45813.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_3:3_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.250459E+11 | 45990.67 | 01-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.171064E+11 | 45990.67 | 01-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145156E+11 | 45990.67 | 01-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.542459E+10 | 45990.67 | 02-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.457527E+09 | 45990.67 | 01-MAY-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 394283.81 | 499.33 | 04-JUN-07:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.150076E+09 | 3245.23 | 23-SEP-06:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.374611E+10 | 45990.67 | 30-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.103953E+11 | 45990.67 | 05-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.230263E+11 | 45990.67 | 01-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.998683E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.250459E+11 | 45990.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_4:4_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.255570E+11 | 46056.33 | 01-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.174939E+11 | 46056.33 | 01-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.148932E+11 | 46056.33 | 01-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.571893E+10 | 46056.33 | 02-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.552596E+09 | 46056.33 | 01-MAY-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 3609510.13 | 1490.52 | 04-JUN-07:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.220950E+09 | 3715.43 | 23-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.405934E+10 | 46056.33 | 30-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.107800E+11 | 46056.33 | 04-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.235122E+11 | 46056.33 | 01-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.102792E+12 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.255570E+11 | 46056.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_5:5_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.260169E+11 | 46215.82 | 01-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.178892E+11 | 46215.82 | 01-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.152966E+11 | 46215.82 | 01-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.600321E+10 | 46215.82 | 01-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.635783E+09 | 46215.82 | 01-MAY-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 7853630.28 | 1643.55 | 04-JUN-07:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 241708.14 | 402.85 | 19-AUG-06:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.280599E+09 | 3667.17 | 23-SEP-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.430115E+10 | 46215.82 | 30-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.111274E+11 | 46215.82 | 04-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.239557E+11 | 46215.82 | 01-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.105515E+12 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.260169E+11 | 46215.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_6:6_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.489937E+11 | 87663.62 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.336272E+11 | 87663.62 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.288928E+11 | 87663.62 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.116103E+11 | 87663.62 | 01-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.132024E+10 | 87663.62 | 01-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16680151.70 | 4592.86 | 03-JUN-07:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 595549.57 | 913.12 | 19-AUG-07:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.742730E+09 | 29171.68 | 23-SEP-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.868504E+10 | 87663.62 | 06-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.213453E+11 | 87663.62 | 01-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.451995E+11 | 87663.62 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.200434E+12 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.489937E+11 | 87663.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_7:7_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.253764E+11 | 46619.67 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.174142E+11 | 46619.67 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.149632E+11 | 46619.67 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.599230E+10 | 46619.67 | 01-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.658110E+09 | 46619.67 | 01-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6799732.26 | 2353.56 | 04-JUN-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.355632E+09 | 14583.61 | 23-SEP-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.441731E+10 | 46619.67 | 06-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.110373E+11 | 46619.67 | 02-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.234211E+11 | 46619.67 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.103642E+12 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.253764E+11 | 46619.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_8:8_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.254377E+11 | 46595.59 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.174840E+11 | 46595.59 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.150692E+11 | 46595.59 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.610827E+10 | 46595.59 | 01-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.706968E+09 | 46595.59 | 01-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 9635509.61 | 5026.76 | 04-JUN-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 197778.80 | 329.63 | 19-AUG-07:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.381899E+09 | 16265.98 | 23-SEP-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.450223E+10 | 46595.59 | 06-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.111306E+11 | 46595.59 | 01-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.234782E+11 | 46595.59 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.104309E+12 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.254377E+11 | 46595.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_9:9_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.259139E+11 | 46832.46 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.179538E+11 | 46832.46 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.155899E+11 | 46832.46 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.655524E+10 | 46832.46 | 01-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.888550E+09 | 46832.46 | 01-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 24717914.99 | 13230.96 | 04-JUN-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1718557.92 | 1104.64 | 19-AUG-07:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.464096E+09 | 22338.76 | 23-SEP-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.477277E+10 | 46832.46 | 05-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.114987E+11 | 46832.46 | 01-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.239327E+11 | 46832.46 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.107596E+12 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.259139E+11 | 46832.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_10:10_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.314129E+11 | 49994.47 | 01-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.224164E+11 | 49994.47 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.196197E+11 | 49994.47 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.892203E+10 | 49994.47 | 01-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.160231E+10 | 49994.47 | 01-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124336E+09 | 35887.37 | 04-JUN-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 3039590.56 | 3792.98 | 09-JUL-08:65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 15766766.84 | 5553.88 | 19-AUG-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.761536E+09 | 49994.47 | 23-SEP-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.575227E+10 | 49994.47 | 04-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.135602E+11 | 49994.47 | 01-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.287782E+11 | 49994.47 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.132969E+12 | |||||||
Minimum of Months | 3039590.56 | 3792.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.314129E+11 | 49994.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.498571E+09 | 0.448901E+09 | 14962.87 | 23-APR-16:10 | 13014.78 | 0.00 |
May | 0.00 | 0.00 | 0.736690E+10 | 0.648265E+10 | 24837.98 | 25-MAY-16:10 | 19828.43 | 0.00 |
June | 0.00 | 0.00 | 0.175005E+11 | 0.131699E+11 | 59223.29 | 30-JUN-07:02 | 30705.31 | 0.00 |
July | 0.00 | 0.00 | 0.268271E+11 | 0.192123E+11 | 57974.49 | 04-JUL-07:02 | 32529.06 | 0.00 |
August | 0.00 | 0.00 | 0.217807E+11 | 0.160794E+11 | 56373.91 | 09-AUG-07:03 | 35811.16 | 0.00 |
September | 0.00 | 0.00 | 0.684794E+10 | 0.577452E+10 | 45925.48 | 01-SEP-07:03 | 29249.55 | 0.00 |
October | 0.00 | 0.00 | 0.868483E+09 | 0.823348E+09 | 10296.97 | 22-OCT-14:00 | 9204.17 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 | 0.00 |
Annual Sum or Average | 0.816902E+11 | 0.619910E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.268271E+11 | 0.192123E+11 | 59223.29 | 35811.16 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 1287838.74 | 1287838.74 | 421.42 | 26-MAR-19:30 | 421.42 | 0.00 |
April | 0.00 | 0.00 | 0.473743E+09 | 0.450430E+09 | 8416.17 | 23-APR-16:10 | 7370.74 | 0.00 |
May | 0.00 | 0.00 | 0.486588E+10 | 0.439777E+10 | 15030.52 | 26-MAY-07:03 | 11893.53 | 0.00 |
June | 0.00 | 0.00 | 0.100427E+11 | 0.785872E+10 | 30022.21 | 30-JUN-07:02 | 17741.30 | 0.00 |
July | 0.00 | 0.00 | 0.142850E+11 | 0.106313E+11 | 29255.88 | 04-JUL-07:02 | 19276.59 | 0.00 |
August | 0.00 | 0.00 | 0.118552E+11 | 0.903960E+10 | 28711.96 | 09-AUG-07:03 | 20186.16 | 0.00 |
September | 0.00 | 0.00 | 0.460027E+10 | 0.402630E+10 | 25165.49 | 01-SEP-07:03 | 18103.20 | 0.00 |
October | 0.00 | 0.00 | 0.873596E+09 | 0.842184E+09 | 5661.09 | 22-OCT-14:00 | 5094.14 | 0.00 |
November | 0.00 | 0.00 | 19700756.82 | 17417582.14 | 2242.80 | 01-NOV-20:20 | 1923.72 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 | 0.00 |
Annual Sum or Average | 0.470174E+11 | 0.372651E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.142850E+11 | 0.106313E+11 | 30022.21 | 20186.16 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.118792E+09 | 0.108506E+09 | 6805.88 | 23-APR-16:00 | 5934.92 | 0.00 |
May | 0.00 | 0.00 | 0.280609E+10 | 0.244590E+10 | 13862.30 | 26-MAY-06:03 | 10367.07 | 0.00 |
June | 0.00 | 0.00 | 0.678878E+10 | 0.511535E+10 | 31220.07 | 30-JUN-06:02 | 16391.65 | 0.00 |
July | 0.00 | 0.00 | 0.100509E+11 | 0.720813E+10 | 30931.77 | 04-JUL-07:02 | 16172.10 | 0.00 |
August | 0.00 | 0.00 | 0.802506E+10 | 0.586376E+10 | 29884.42 | 09-AUG-06:03 | 18320.36 | 0.00 |
September | 0.00 | 0.00 | 0.211902E+10 | 0.180882E+10 | 29843.13 | 01-SEP-06:03 | 17386.32 | 0.00 |
October | 0.00 | 0.00 | 0.260000E+09 | 0.246043E+09 | 4462.66 | 19-OCT-15:00 | 4194.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 | 0.00 |
Annual Sum or Average | 0.301686E+11 | 0.227965E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.100509E+11 | 0.720813E+10 | 31220.07 | 18320.36 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 97569557.95 | 88066799.78 | 6462.30 | 23-APR-16:00 | 5624.23 | 0.00 |
May | 0.00 | 0.00 | 0.268019E+10 | 0.232917E+10 | 12936.03 | 26-MAY-06:03 | 9650.48 | 0.00 |
June | 0.00 | 0.00 | 0.660784E+10 | 0.496292E+10 | 31311.86 | 30-JUN-06:02 | 16420.47 | 0.00 |
July | 0.00 | 0.00 | 0.992582E+10 | 0.710774E+10 | 31022.41 | 04-JUL-07:02 | 16179.70 | 0.00 |
August | 0.00 | 0.00 | 0.787693E+10 | 0.574593E+10 | 29970.81 | 09-AUG-06:03 | 18339.84 | 0.00 |
September | 0.00 | 0.00 | 0.199549E+10 | 0.170220E+10 | 29531.36 | 01-SEP-06:03 | 17162.28 | 0.00 |
October | 0.00 | 0.00 | 0.231715E+09 | 0.219276E+09 | 4166.73 | 19-OCT-15:00 | 3911.45 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 | 0.00 |
Annual Sum or Average | 0.294156E+11 | 0.221553E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.992582E+10 | 0.710774E+10 | 31311.86 | 18339.84 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 84549489.75 | 75638770.66 | 6197.94 | 23-APR-16:00 | 5384.91 | 0.00 |
May | 0.00 | 0.00 | 0.254600E+10 | 0.220680E+10 | 12142.42 | 25-MAY-16:10 | 9634.95 | 0.00 |
June | 0.00 | 0.00 | 0.638460E+10 | 0.477924E+10 | 31491.43 | 30-JUN-06:02 | 16386.94 | 0.00 |
July | 0.00 | 0.00 | 0.971187E+10 | 0.693853E+10 | 31205.37 | 04-JUL-07:02 | 16152.63 | 0.00 |
August | 0.00 | 0.00 | 0.765593E+10 | 0.557279E+10 | 30147.99 | 09-AUG-06:03 | 18354.83 | 0.00 |
September | 0.00 | 0.00 | 0.187376E+10 | 0.159810E+10 | 26727.67 | 01-SEP-06:03 | 15444.15 | 0.00 |
October | 0.00 | 0.00 | 0.209464E+09 | 0.198236E+09 | 3932.10 | 19-OCT-15:00 | 3687.32 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 | 0.00 |
Annual Sum or Average | 0.284662E+11 | 0.213693E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.971187E+10 | 0.693853E+10 | 31491.43 | 18354.83 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.120149E+09 | 0.104114E+09 | 10684.50 | 23-APR-16:00 | 9136.82 | 0.00 |
May | 0.00 | 0.00 | 0.434124E+10 | 0.370512E+10 | 22156.75 | 25-MAY-15:00 | 17113.04 | 0.00 |
June | 0.00 | 0.00 | 0.111570E+11 | 0.820425E+10 | 58349.11 | 30-JUN-07:02 | 30890.44 | 0.00 |
July | 0.00 | 0.00 | 0.172165E+11 | 0.120985E+11 | 58063.19 | 23-JUL-08:62 | 31105.20 | 0.00 |
August | 0.00 | 0.00 | 0.135075E+11 | 0.962773E+10 | 50759.07 | 09-AUG-07:03 | 31632.86 | 0.00 |
September | 0.00 | 0.00 | 0.299421E+10 | 0.251596E+10 | 38713.63 | 01-SEP-07:03 | 23047.82 | 0.00 |
October | 0.00 | 0.00 | 0.303645E+09 | 0.285094E+09 | 6860.34 | 19-OCT-15:00 | 6309.85 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 | 0.00 |
Annual Sum or Average | 0.496402E+11 | 0.365408E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.172165E+11 | 0.120985E+11 | 58349.11 | 31632.86 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 62489013.54 | 54310275.09 | 5652.59 | 23-APR-16:00 | 4841.19 | 0.00 |
May | 0.00 | 0.00 | 0.229380E+10 | 0.196318E+10 | 11678.76 | 25-MAY-15:00 | 9031.90 | 0.00 |
June | 0.00 | 0.00 | 0.587865E+10 | 0.434071E+10 | 32046.89 | 30-JUN-07:02 | 16961.04 | 0.00 |
July | 0.00 | 0.00 | 0.905731E+10 | 0.639673E+10 | 31910.64 | 23-JUL-08:62 | 17112.07 | 0.00 |
August | 0.00 | 0.00 | 0.713665E+10 | 0.511475E+10 | 24074.83 | 09-AUG-07:03 | 15120.25 | 0.00 |
September | 0.00 | 0.00 | 0.159808E+10 | 0.134845E+10 | 18122.40 | 01-SEP-07:03 | 10892.82 | 0.00 |
October | 0.00 | 0.00 | 0.163345E+09 | 0.153840E+09 | 3687.48 | 19-OCT-15:00 | 3402.57 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 | 0.00 |
Annual Sum or Average | 0.261903E+11 | 0.193720E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.905731E+10 | 0.639673E+10 | 32046.89 | 17112.07 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 58445580.07 | 50553909.39 | 5506.60 | 23-APR-16:00 | 4709.27 | 0.00 |
May | 0.00 | 0.00 | 0.221828E+10 | 0.189503E+10 | 11538.90 | 25-MAY-15:00 | 8909.40 | 0.00 |
June | 0.00 | 0.00 | 0.574561E+10 | 0.423073E+10 | 32073.33 | 30-JUN-07:02 | 16910.47 | 0.00 |
July | 0.00 | 0.00 | 0.892558E+10 | 0.629101E+10 | 31936.69 | 23-JUL-08:62 | 17066.55 | 0.00 |
August | 0.00 | 0.00 | 0.701425E+10 | 0.501800E+10 | 22905.94 | 09-AUG-07:03 | 14340.83 | 0.00 |
September | 0.00 | 0.00 | 0.154160E+10 | 0.129899E+10 | 16961.70 | 01-SEP-07:03 | 10160.17 | 0.00 |
October | 0.00 | 0.00 | 0.155083E+09 | 0.145990E+09 | 3598.94 | 19-OCT-15:00 | 3317.60 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 | 0.00 |
Annual Sum or Average | 0.256588E+11 | 0.189303E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.892558E+10 | 0.629101E+10 | 32073.33 | 17066.55 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 47242350.04 | 40238811.92 | 5083.18 | 23-APR-16:00 | 4331.99 | 0.00 |
May | 0.00 | 0.00 | 0.201411E+10 | 0.171334E+10 | 11160.48 | 25-MAY-15:00 | 8583.20 | 0.00 |
June | 0.00 | 0.00 | 0.539568E+10 | 0.394687E+10 | 32388.68 | 30-JUN-07:02 | 16868.89 | 0.00 |
July | 0.00 | 0.00 | 0.860718E+10 | 0.604080E+10 | 32251.63 | 23-JUL-08:62 | 17058.06 | 0.00 |
August | 0.00 | 0.00 | 0.673014E+10 | 0.479882E+10 | 19317.05 | 09-AUG-07:03 | 12000.87 | 0.00 |
September | 0.00 | 0.00 | 0.141089E+10 | 0.118583E+10 | 13178.44 | 01-SEP-07:03 | 7825.69 | 0.00 |
October | 0.00 | 0.00 | 0.136467E+09 | 0.128368E+09 | 3386.30 | 19-OCT-15:00 | 3115.96 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 | 0.00 |
Annual Sum or Average | 0.243417E+11 | 0.178543E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.860718E+10 | 0.604080E+10 | 32388.68 | 17058.06 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 26789971.05 | 22322139.23 | 3922.51 | 23-APR-16:00 | 3296.59 | 0.00 |
May | 0.00 | 0.00 | 0.156942E+10 | 0.131826E+10 | 10294.89 | 25-MAY-15:00 | 7813.35 | 0.00 |
June | 0.00 | 0.00 | 0.470460E+10 | 0.338405E+10 | 35734.05 | 30-JUN-07:02 | 16392.14 | 0.00 |
July | 0.00 | 0.00 | 0.802932E+10 | 0.557671E+10 | 32734.91 | 23-JUL-08:62 | 16398.50 | 0.00 |
August | 0.00 | 0.00 | 0.624889E+10 | 0.443080E+10 | 17302.44 | 08-AUG-15:00 | 11187.86 | 0.00 |
September | 0.00 | 0.00 | 0.121026E+10 | 0.101172E+10 | 11095.20 | 01-SEP-14:10 | 8619.11 | 0.00 |
October | 0.00 | 0.00 | 0.110383E+09 | 0.103504E+09 | 3113.19 | 19-OCT-15:00 | 2849.33 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 | 0.00 |
Annual Sum or Average | 0.218997E+11 | 0.158474E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.802932E+10 | 0.557671E+10 | 35734.05 | 16398.50 | 0.00 |
Report: FanReportMonthly
For: PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.513973E+10 | 0.69 | 2808.76 | 17-JAN-16:20 | 0.94 |
February | 0.463181E+10 | 0.67 | 2808.76 | 07-FEB-21:35 | 0.94 |
March | 0.512042E+10 | 0.66 | 2808.76 | 09-MAR-13:10 | 0.94 |
April | 0.494776E+10 | 0.64 | 2808.76 | 01-APR-16:00 | 0.94 |
May | 0.509622E+10 | 0.63 | 2808.76 | 17-MAY-22:10 | 0.93 |
June | 0.494455E+10 | 0.63 | 2808.76 | 13-JUN-13:20 | 0.93 |
July | 0.510633E+10 | 0.63 | 2808.76 | 01-JUL-09:40 | 0.93 |
August | 0.509622E+10 | 0.63 | 2808.76 | 10-AUG-16:30 | 0.93 |
September | 0.495466E+10 | 0.63 | 2808.76 | 14-SEP-18:40 | 0.93 |
October | 0.509642E+10 | 0.63 | 2808.76 | 29-OCT-09:47 | 0.94 |
November | 0.492863E+10 | 0.64 | 2808.76 | 05-NOV-07:50 | 0.94 |
December | 0.514429E+10 | 0.67 | 2808.76 | 05-DEC-14:30 | 0.94 |
Annual Sum or Average | 0.602071E+11 | 0.65 | |||
Minimum of Months | 0.463181E+10 | 0.63 | 2808.76 | 0.93 | |
Maximum of Months | 0.514429E+10 | 0.69 | 2808.76 | 0.94 |
Report: FanReportMonthly
For: PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.208331E+10 | 0.59 | 1522.03 | 19-JAN-09:00 | 0.98 |
February | 0.187426E+10 | 0.54 | 1522.03 | 09-FEB-15:50 | 0.98 |
March | 0.210182E+10 | 0.53 | 1522.03 | 02-MAR-10:50 | 0.98 |
April | 0.201816E+10 | 0.58 | 1522.03 | 05-APR-11:30 | 0.98 |
May | 0.218202E+10 | 0.70 | 1522.03 | 01-MAY-13:30 | 0.98 |
June | 0.217805E+10 | 0.70 | 1522.03 | 17-JUN-12:00 | 0.97 |
July | 0.226343E+10 | 0.70 | 1522.03 | 01-JUL-15:50 | 0.97 |
August | 0.227853E+10 | 0.69 | 1522.03 | 02-AUG-16:40 | 0.97 |
September | 0.212648E+10 | 0.70 | 1522.03 | 17-SEP-15:50 | 0.96 |
October | 0.210186E+10 | 0.63 | 1522.03 | 18-OCT-17:20 | 0.97 |
November | 0.200761E+10 | 0.52 | 1522.03 | 06-NOV-12:40 | 0.98 |
December | 0.206700E+10 | 0.57 | 1522.03 | 03-DEC-08:15 | 0.98 |
Annual Sum or Average | 0.252825E+11 | 0.62 | |||
Minimum of Months | 0.187426E+10 | 0.52 | 1522.03 | 0.96 | |
Maximum of Months | 0.227853E+10 | 0.70 | 1522.03 | 0.98 |
Report: FanReportMonthly
For: PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.222149E+10 | 0.55 | 1531.23 | 01-JAN-08:08 | 0.98 |
February | 0.200751E+10 | 0.54 | 1531.23 | 01-FEB-07:06 | 0.98 |
March | 0.226027E+10 | 0.54 | 1531.23 | 04-MAR-17:30 | 0.98 |
April | 0.214985E+10 | 0.53 | 1531.23 | 01-APR-06:02 | 0.98 |
May | 0.223805E+10 | 0.53 | 1531.23 | 01-MAY-06:04 | 0.98 |
June | 0.218293E+10 | 0.53 | 1531.23 | 20-JUN-09:40 | 0.97 |
July | 0.220498E+10 | 0.52 | 1531.23 | 01-JUL-07:30 | 0.97 |
August | 0.226010E+10 | 0.53 | 1531.23 | 22-AUG-07:20 | 0.97 |
September | 0.214985E+10 | 0.53 | 1531.23 | 05-SEP-17:40 | 0.97 |
October | 0.221600E+10 | 0.53 | 1531.23 | 06-OCT-15:40 | 0.97 |
November | 0.214985E+10 | 0.53 | 1531.23 | 01-NOV-06:40 | 0.97 |
December | 0.220860E+10 | 0.54 | 1531.23 | 28-DEC-20:20 | 0.98 |
Annual Sum or Average | 0.262495E+11 | 0.53 | |||
Minimum of Months | 0.200751E+10 | 0.52 | 1531.23 | 0.97 | |
Maximum of Months | 0.226027E+10 | 0.55 | 1531.23 | 0.98 |
Report: FanReportMonthly
For: PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.223147E+10 | 0.56 | 1534.65 | 01-JAN-11:30 | 0.98 |
February | 0.201357E+10 | 0.54 | 1534.65 | 01-FEB-20:30 | 0.98 |
March | 0.226571E+10 | 0.54 | 1534.65 | 01-MAR-10:30 | 0.98 |
April | 0.215465E+10 | 0.53 | 1534.65 | 01-APR-06:10 | 0.98 |
May | 0.224304E+10 | 0.53 | 1534.65 | 01-MAY-07:17 | 0.98 |
June | 0.218780E+10 | 0.53 | 1534.65 | 01-JUN-09:50 | 0.97 |
July | 0.220990E+10 | 0.52 | 1534.65 | 01-JUL-10:00 | 0.97 |
August | 0.226514E+10 | 0.53 | 1534.65 | 02-AUG-10:20 | 0.97 |
September | 0.215465E+10 | 0.53 | 1534.65 | 01-SEP-06:30 | 0.96 |
October | 0.222095E+10 | 0.53 | 1534.65 | 01-OCT-07:10 | 0.97 |
November | 0.215465E+10 | 0.53 | 1534.65 | 01-NOV-06:30 | 0.97 |
December | 0.221735E+10 | 0.55 | 1534.65 | 02-DEC-11:50 | 0.98 |
Annual Sum or Average | 0.263189E+11 | 0.54 | |||
Minimum of Months | 0.201357E+10 | 0.52 | 1534.65 | 0.96 | |
Maximum of Months | 0.226571E+10 | 0.56 | 1534.65 | 0.98 |
Report: FanReportMonthly
For: PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.224668E+10 | 0.58 | 1542.95 | 03-JAN-09:40 | 0.98 |
February | 0.202598E+10 | 0.55 | 1542.95 | 10-FEB-09:20 | 0.98 |
March | 0.227853E+10 | 0.54 | 1542.95 | 02-MAR-17:00 | 0.98 |
April | 0.216630E+10 | 0.53 | 1542.95 | 01-APR-11:20 | 0.98 |
May | 0.225517E+10 | 0.53 | 1542.95 | 03-MAY-06:40 | 0.98 |
June | 0.219963E+10 | 0.53 | 1542.95 | 04-JUN-13:50 | 0.97 |
July | 0.222185E+10 | 0.52 | 1542.95 | 03-JUL-10:20 | 0.96 |
August | 0.227739E+10 | 0.53 | 1542.95 | 04-AUG-13:10 | 0.97 |
September | 0.216630E+10 | 0.53 | 1542.95 | 01-SEP-07:00 | 0.96 |
October | 0.223295E+10 | 0.53 | 1542.95 | 03-OCT-10:10 | 0.98 |
November | 0.216630E+10 | 0.53 | 1542.95 | 04-NOV-14:20 | 0.98 |
December | 0.223151E+10 | 0.56 | 1542.95 | 04-DEC-08:50 | 0.98 |
Annual Sum or Average | 0.264686E+11 | 0.54 | |||
Minimum of Months | 0.202598E+10 | 0.52 | 1542.95 | 0.96 | |
Maximum of Months | 0.227853E+10 | 0.58 | 1542.95 | 0.98 |
Report: FanReportMonthly
For: PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.368795E+10 | 0.55 | 2724.40 | 02-JAN-20:20 | 0.94 |
February | 0.331636E+10 | 0.51 | 2724.40 | 01-FEB-20:00 | 0.94 |
March | 0.372557E+10 | 0.50 | 2724.40 | 01-MAR-15:20 | 0.94 |
April | 0.353083E+10 | 0.47 | 2724.40 | 01-APR-11:50 | 0.94 |
May | 0.367794E+10 | 0.47 | 2724.40 | 01-MAY-08:50 | 0.94 |
June | 0.358967E+10 | 0.47 | 2724.40 | 01-JUN-10:30 | 0.93 |
July | 0.361910E+10 | 0.46 | 2724.40 | 01-JUL-13:00 | 0.93 |
August | 0.371717E+10 | 0.47 | 2724.40 | 01-AUG-08:50 | 0.93 |
September | 0.353083E+10 | 0.47 | 2724.40 | 01-SEP-10:30 | 0.93 |
October | 0.363871E+10 | 0.47 | 2724.40 | 02-OCT-11:20 | 0.93 |
November | 0.353106E+10 | 0.47 | 2724.40 | 02-NOV-07:20 | 0.93 |
December | 0.365712E+10 | 0.53 | 2724.40 | 02-DEC-08:06 | 0.94 |
Annual Sum or Average | 0.432223E+11 | 0.49 | |||
Minimum of Months | 0.331636E+10 | 0.46 | 2724.40 | 0.93 | |
Maximum of Months | 0.372557E+10 | 0.55 | 2724.40 | 0.94 |
Report: FanReportMonthly
For: PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.211243E+10 | 0.56 | 1563.96 | 03-JAN-11:50 | 0.98 |
February | 0.190154E+10 | 0.53 | 1563.96 | 03-FEB-12:20 | 0.98 |
March | 0.213780E+10 | 0.51 | 1563.96 | 03-MAR-08:04 | 0.98 |
April | 0.202690E+10 | 0.49 | 1563.96 | 04-APR-07:17 | 0.98 |
May | 0.211135E+10 | 0.49 | 1563.96 | 12-MAY-12:10 | 0.97 |
June | 0.206068E+10 | 0.49 | 1563.96 | 06-JUN-16:30 | 0.97 |
July | 0.207757E+10 | 0.48 | 1563.96 | 03-JUL-12:50 | 0.96 |
August | 0.213387E+10 | 0.49 | 1563.96 | 09-AUG-17:20 | 0.96 |
September | 0.202690E+10 | 0.49 | 1563.96 | 07-SEP-11:50 | 0.97 |
October | 0.208883E+10 | 0.49 | 1563.96 | 04-OCT-12:40 | 0.97 |
November | 0.202698E+10 | 0.49 | 1563.96 | 04-NOV-14:40 | 0.98 |
December | 0.209540E+10 | 0.54 | 1563.96 | 07-DEC-12:40 | 0.98 |
Annual Sum or Average | 0.248003E+11 | 0.50 | |||
Minimum of Months | 0.190154E+10 | 0.48 | 1563.96 | 0.96 | |
Maximum of Months | 0.213780E+10 | 0.56 | 1563.96 | 0.98 |
Report: FanReportMonthly
For: PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.211123E+10 | 0.57 | 1562.71 | 01-JAN-10:10 | 0.98 |
February | 0.190046E+10 | 0.53 | 1562.71 | 01-FEB-08:09 | 0.98 |
March | 0.213638E+10 | 0.51 | 1562.71 | 01-MAR-08:30 | 0.98 |
April | 0.202527E+10 | 0.49 | 1562.71 | 01-APR-07:07 | 0.98 |
May | 0.210966E+10 | 0.49 | 1562.71 | 01-MAY-10:50 | 0.98 |
June | 0.205903E+10 | 0.49 | 1562.71 | 01-JUN-11:50 | 0.97 |
July | 0.207591E+10 | 0.48 | 1562.71 | 01-JUL-10:10 | 0.97 |
August | 0.213216E+10 | 0.49 | 1562.71 | 01-AUG-09:00 | 0.96 |
September | 0.202527E+10 | 0.49 | 1562.71 | 01-SEP-09:10 | 0.96 |
October | 0.208716E+10 | 0.49 | 1562.71 | 01-OCT-09:00 | 0.97 |
November | 0.202541E+10 | 0.49 | 1562.71 | 01-NOV-07:40 | 0.97 |
December | 0.209402E+10 | 0.55 | 1562.71 | 01-DEC-08:06 | 0.98 |
Annual Sum or Average | 0.247820E+11 | 0.51 | |||
Minimum of Months | 0.190046E+10 | 0.48 | 1562.71 | 0.96 | |
Maximum of Months | 0.213638E+10 | 0.57 | 1562.71 | 0.98 |
Report: FanReportMonthly
For: PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.213337E+10 | 0.58 | 1575.04 | 20-JAN-08:08 | 0.98 |
February | 0.192057E+10 | 0.55 | 1575.04 | 01-FEB-10:40 | 0.98 |
March | 0.215546E+10 | 0.52 | 1575.04 | 02-MAR-08:09 | 0.98 |
April | 0.204125E+10 | 0.49 | 1575.04 | 01-APR-10:20 | 0.98 |
May | 0.212630E+10 | 0.49 | 1575.04 | 01-MAY-07:04 | 0.98 |
June | 0.207527E+10 | 0.49 | 1575.04 | 01-JUN-17:00 | 0.97 |
July | 0.209228E+10 | 0.48 | 1575.04 | 01-JUL-11:50 | 0.97 |
August | 0.214898E+10 | 0.49 | 1575.04 | 23-AUG-11:40 | 0.96 |
September | 0.204125E+10 | 0.49 | 1575.04 | 01-SEP-08:50 | 0.96 |
October | 0.210362E+10 | 0.49 | 1575.04 | 01-OCT-08:50 | 0.97 |
November | 0.204166E+10 | 0.49 | 1575.04 | 01-NOV-09:40 | 0.97 |
December | 0.211521E+10 | 0.56 | 1575.04 | 01-DEC-11:50 | 0.98 |
Annual Sum or Average | 0.249952E+11 | 0.51 | |||
Minimum of Months | 0.192057E+10 | 0.48 | 1575.04 | 0.96 | |
Maximum of Months | 0.215546E+10 | 0.58 | 1575.04 | 0.98 |
Report: FanReportMonthly
For: PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.235785E+10 | 0.70 | 1669.96 | 02-JAN-12:00 | 0.94 |
February | 0.210946E+10 | 0.66 | 1669.96 | 01-FEB-10:20 | 0.94 |
March | 0.233165E+10 | 0.61 | 1669.96 | 01-MAR-08:10 | 0.94 |
April | 0.217773E+10 | 0.52 | 1669.96 | 02-APR-16:50 | 0.94 |
May | 0.225444E+10 | 0.47 | 1669.96 | 03-MAY-08:30 | 0.94 |
June | 0.220034E+10 | 0.47 | 1669.96 | 01-JUN-13:40 | 0.93 |
July | 0.221837E+10 | 0.46 | 1669.96 | 02-JUL-10:10 | 0.93 |
August | 0.227849E+10 | 0.47 | 1669.96 | 02-AUG-13:10 | 0.93 |
September | 0.216427E+10 | 0.47 | 1669.96 | 02-SEP-15:10 | 0.93 |
October | 0.223040E+10 | 0.47 | 1669.96 | 02-OCT-09:30 | 0.93 |
November | 0.217929E+10 | 0.52 | 1669.96 | 01-NOV-19:20 | 0.93 |
December | 0.232506E+10 | 0.67 | 1669.96 | 02-DEC-10:50 | 0.94 |
Annual Sum or Average | 0.268274E+11 | 0.54 | |||
Minimum of Months | 0.210946E+10 | 0.46 | 1669.96 | 0.93 | |
Maximum of Months | 0.235785E+10 | 0.70 | 1669.96 | 0.94 |
Report: ZoneTemperatureOscillationReportMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 2.73 | 0.13 |
February | 2.35 | 0.32 |
March | 3.12 | 0.58 |
April | 0.89 | 0.73 |
May | 0.06 | 0.00 |
June | 0.28 | 0.00 |
July | 0.06 | 0.00 |
August | 0.33 | 1.12 |
September | 0.56 | 0.30 |
October | 0.43 | 0.87 |
November | 1.17 | 0.27 |
December | 3.56 | 0.55 |
Annual Sum or Average | 15.52 | 0.43 |
Minimum of Months | 0.06 | 0.00 |
Maximum of Months | 3.56 | 1.12 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.73 | 0.00 |
February | 0.35 | 1.06 |
March | 0.76 | 4.55 |
April | 0.99 | 4.98 |
May | 0.81 | 1.78 |
June | 0.25 | 0.25 |
July | 0.06 | 0.00 |
August | 0.08 | 0.75 |
September | 0.53 | 1.11 |
October | 1.54 | 4.77 |
November | 0.91 | 4.64 |
December | 0.67 | 0.00 |
Annual Sum or Average | 7.68 | 2.93 |
Minimum of Months | 0.06 | 0.00 |
Maximum of Months | 1.54 | 4.98 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 1.54 | 0.00 |
February | 0.88 | 0.00 |
March | 0.22 | 0.00 |
April | 0.12 | 0.75 |
May | 0.64 | 0.55 |
June | 1.47 | 0.75 |
July | 2.19 | 0.75 |
August | 1.06 | 0.65 |
September | 0.39 | 0.27 |
October | 0.08 | 0.00 |
November | 0.28 | 0.00 |
December | 1.25 | 0.00 |
Annual Sum or Average | 10.12 | 0.39 |
Minimum of Months | 0.08 | 0.00 |
Maximum of Months | 2.19 | 0.75 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 2.06 | 0.00 |
February | 1.13 | 0.00 |
March | 0.50 | 0.00 |
April | 0.12 | 0.75 |
May | 0.39 | 0.75 |
June | 1.33 | 0.75 |
July | 2.19 | 0.75 |
August | 1.06 | 0.65 |
September | 0.31 | 0.34 |
October | 0.08 | 0.00 |
November | 0.42 | 0.00 |
December | 1.44 | 0.00 |
Annual Sum or Average | 11.03 | 0.35 |
Minimum of Months | 0.08 | 0.00 |
Maximum of Months | 2.19 | 0.75 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 2.19 | 0.00 |
February | 1.26 | 0.00 |
March | 0.65 | 0.00 |
April | 0.12 | 0.75 |
May | 0.39 | 0.75 |
June | 1.33 | 0.75 |
July | 2.19 | 0.75 |
August | 0.98 | 0.64 |
September | 0.22 | 0.47 |
October | 0.08 | 0.00 |
November | 0.51 | 0.00 |
December | 1.92 | 0.00 |
Annual Sum or Average | 11.86 | 0.32 |
Minimum of Months | 0.08 | 0.00 |
Maximum of Months | 2.19 | 0.75 |
Report: ZoneTemperatureOscillationReportMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 3.93 | 0.00 |
February | 2.28 | 0.00 |
March | 1.18 | 0.00 |
April | 0.43 | 0.95 |
May | 0.00 | 0.00 |
June | 0.75 | 1.71 |
July | 1.07 | 2.87 |
August | 0.60 | 1.00 |
September | 0.00 | 0.00 |
October | 0.08 | 0.00 |
November | 1.22 | 0.00 |
December | 3.61 | 0.00 |
Annual Sum or Average | 15.14 | 0.35 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 3.93 | 2.87 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 2.59 | 0.00 |
February | 1.69 | 0.00 |
March | 1.01 | 0.00 |
April | 0.38 | 0.55 |
May | 0.06 | 0.00 |
June | 0.75 | 0.86 |
July | 1.07 | 1.43 |
August | 0.43 | 0.69 |
September | 0.00 | 0.00 |
October | 0.08 | 0.00 |
November | 0.86 | 0.00 |
December | 2.66 | 0.00 |
Annual Sum or Average | 11.58 | 0.23 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 2.66 | 1.43 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 2.65 | 0.00 |
February | 1.82 | 0.00 |
March | 1.04 | 0.00 |
April | 0.43 | 0.48 |
May | 0.00 | 0.00 |
June | 0.67 | 0.96 |
July | 1.07 | 1.43 |
August | 0.43 | 0.69 |
September | 0.00 | 0.00 |
October | 0.08 | 0.00 |
November | 0.96 | 0.00 |
December | 2.66 | 0.00 |
Annual Sum or Average | 11.82 | 0.23 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 2.66 | 1.43 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 3.44 | 0.00 |
February | 2.07 | 0.00 |
March | 1.54 | 0.00 |
April | 0.49 | 0.42 |
May | 0.00 | 0.00 |
June | 0.50 | 1.28 |
July | 0.98 | 1.56 |
August | 0.26 | 1.13 |
September | 0.00 | 0.00 |
October | 0.08 | 0.00 |
November | 1.41 | 0.00 |
December | 2.88 | 0.00 |
Annual Sum or Average | 13.65 | 0.20 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 3.44 | 1.56 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 4.71 | 0.00 |
February | 3.81 | 0.00 |
March | 3.77 | 0.00 |
April | 2.28 | 0.03 |
May | 0.08 | 0.00 |
June | 0.47 | 1.36 |
July | 0.93 | 1.65 |
August | 0.18 | 1.65 |
September | 0.00 | 0.00 |
October | 0.82 | 0.00 |
November | 3.10 | 0.00 |
December | 4.26 | 0.00 |
Annual Sum or Average | 24.41 | 0.10 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 4.71 | 1.65 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_1:1
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.513973E+10 | 0.710721E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.463181E+10 | 0.489615E+11 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.512042E+10 | 0.411682E+11 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.510766E+10 | 0.155969E+11 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.742608E+10 | 0.113282E+10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.103423E+11 | 3951770.12 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.132541E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.116908E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.707074E+10 | 0.221303E+09 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.536830E+10 | 0.893793E+10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.492863E+10 | 0.284796E+11 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.514429E+10 | 0.653135E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.852249E+11 | 0.280888E+12 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.463181E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.132541E+11 | 0.710721E+11 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_2:2
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.208331E+10 | 0.282016E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.187426E+10 | 0.186665E+11 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.210224E+10 | 0.154586E+11 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.216541E+10 | 0.507528E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.365023E+10 | 0.243083E+09 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.513426E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.641179E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.570935E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.349841E+10 | 31939295.61 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.236937E+10 | 0.308233E+10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.201403E+10 | 0.106048E+11 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.206700E+10 | 0.258936E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.390797E+11 | 0.107258E+12 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.187426E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.641179E+10 | 0.282016E+11 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_3:3
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.222149E+10 | 0.313074E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.200751E+10 | 0.213830E+11 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.226027E+10 | 0.181445E+11 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.218597E+10 | 0.678074E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.308138E+10 | 0.571908E+09 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.417101E+10 | 492854.76 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.510709E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.456789E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.277037E+10 | 0.187595E+09 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.229311E+10 | 0.468263E+10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.214985E+10 | 0.129942E+11 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.220860E+10 | 0.287829E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.350246E+11 | 0.124835E+12 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.200751E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.510709E+10 | 0.313074E+11 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_4:4
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.223147E+10 | 0.319462E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.201357E+10 | 0.218674E+11 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.226571E+10 | 0.186165E+11 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.218445E+10 | 0.714866E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.305040E+10 | 0.690744E+09 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.412556E+10 | 4511887.66 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.507927E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.453320E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.273978E+10 | 0.276188E+09 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.228985E+10 | 0.507418E+10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.215465E+10 | 0.134750E+11 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.221735E+10 | 0.293902E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.348853E+11 | 0.128490E+12 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.201357E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.507927E+10 | 0.319462E+11 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_5:5
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.224668E+10 | 0.325211E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.202598E+10 | 0.223615E+11 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.227853E+10 | 0.191208E+11 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.219224E+10 | 0.750401E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.302432E+10 | 0.794729E+09 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.407589E+10 | 9817037.85 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.503541E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.448613E+10 | 302135.17 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.271663E+10 | 0.350749E+09 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.229538E+10 | 0.537643E+10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.216630E+10 | 0.139093E+11 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.223151E+10 | 0.299447E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.347750E+11 | 0.131893E+12 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.202598E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.503541E+10 | 0.325211E+11 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_6:6
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.368795E+10 | 0.618217E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.331636E+10 | 0.424318E+11 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.372557E+10 | 0.364578E+11 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.357022E+10 | 0.146502E+11 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.507636E+10 | 0.166591E+10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.707661E+10 | 21047510.03 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.892179E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.786048E+10 | 751482.11 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.446643E+10 | 0.937198E+09 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.373503E+10 | 0.109590E+11 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.353106E+10 | 0.269341E+11 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.365712E+10 | 0.570341E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.586250E+11 | 0.252914E+12 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.331636E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.892179E+10 | 0.618217E+11 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_7:7
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.211243E+10 | 0.317205E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.190154E+10 | 0.217678E+11 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.213780E+10 | 0.187041E+11 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.204626E+10 | 0.749038E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.281007E+10 | 0.822637E+09 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.380146E+10 | 8499665.33 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.472110E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.420655E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.249884E+10 | 0.444540E+09 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.213773E+10 | 0.552163E+10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.202698E+10 | 0.137967E+11 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.209540E+10 | 0.292764E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.324962E+11 | 0.129553E+12 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.190154E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.472110E+10 | 0.317205E+11 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_8:8
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.211123E+10 | 0.317971E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.190046E+10 | 0.218550E+11 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.213638E+10 | 0.188365E+11 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.204343E+10 | 0.763534E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.278648E+10 | 0.883710E+09 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.376245E+10 | 12044387.02 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.468374E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.417122E+10 | 247223.50 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.248089E+10 | 0.477374E+09 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.213363E+10 | 0.562779E+10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.202541E+10 | 0.139133E+11 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.209402E+10 | 0.293477E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.323293E+11 | 0.130386E+12 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.190046E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.468374E+10 | 0.317971E+11 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_9:9
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.213337E+10 | 0.323924E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.192057E+10 | 0.224422E+11 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.215546E+10 | 0.194874E+11 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.205603E+10 | 0.819404E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.274395E+10 | 0.111069E+10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.368137E+10 | 30897393.73 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.461522E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.411060E+10 | 2148197.40 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.245907E+10 | 0.580121E+09 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.214461E+10 | 0.596596E+10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.204166E+10 | 0.143734E+11 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.211521E+10 | 0.299158E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.321771E+11 | 0.134495E+12 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.192057E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.461522E+10 | 0.323924E+11 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_10:10
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.235785E+10 | 0.392661E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.210946E+10 | 0.280206E+11 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.233165E+10 | 0.245246E+11 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.218629E+10 | 0.111525E+11 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.274388E+10 | 0.200289E+10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.362310E+10 | 0.155420E+09 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.460382E+10 | 3799488.20 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.411900E+10 | 19708458.55 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.252494E+10 | 0.951920E+09 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.226375E+10 | 0.719033E+10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.217929E+10 | 0.169503E+11 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.232506E+10 | 0.359727E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.333681E+11 | 0.166211E+12 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.210946E+10 | 3799488.20 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.460382E+10 | 0.392661E+11 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_1:1
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.513973E+10 | 0.00 | 0.563247E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.463181E+10 | 0.00 | 0.388020E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.512042E+10 | 0.00 | 0.326258E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.494776E+10 | 0.498571E+09 | 0.123606E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.509622E+10 | 0.736690E+10 | 0.897757E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.494455E+10 | 0.175005E+11 | 3131777.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.510633E+10 | 0.268271E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.509622E+10 | 0.217807E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.495466E+10 | 0.684794E+10 | 0.175383E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.509642E+10 | 0.868483E+09 | 0.708331E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.492863E+10 | 0.00 | 0.225701E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.514429E+10 | 0.00 | 0.517610E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.602071E+11 | 0.816902E+11 | 0.222604E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.463181E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.514429E+10 | 0.268271E+11 | 0.563247E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_2:2
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.208331E+10 | 0.00 | 0.225613E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.187426E+10 | 0.00 | 0.149332E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.210182E+10 | 1287838.74 | 0.123669E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.201816E+10 | 0.473743E+09 | 0.406022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.218202E+10 | 0.486588E+10 | 0.194467E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.217805E+10 | 0.100427E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.226343E+10 | 0.142850E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.227853E+10 | 0.118552E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.212648E+10 | 0.460027E+10 | 25551436.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.210186E+10 | 0.873596E+09 | 0.246587E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.200761E+10 | 19700756.82 | 0.848385E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.206700E+10 | 0.00 | 0.207149E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.252825E+11 | 0.470174E+11 | 0.858062E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.187426E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.227853E+10 | 0.142850E+11 | 0.225613E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_3:3
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.222149E+10 | 0.00 | 0.250459E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.200751E+10 | 0.00 | 0.171064E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.226027E+10 | 0.00 | 0.145156E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.214985E+10 | 0.118792E+09 | 0.542459E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.223805E+10 | 0.280609E+10 | 0.457527E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.218293E+10 | 0.678878E+10 | 394283.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.220498E+10 | 0.100509E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.226010E+10 | 0.802506E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.214985E+10 | 0.211902E+10 | 0.150076E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.221600E+10 | 0.260000E+09 | 0.374611E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.214985E+10 | 0.00 | 0.103953E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.220860E+10 | 0.00 | 0.230263E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.262495E+11 | 0.301686E+11 | 0.998683E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.200751E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.226027E+10 | 0.100509E+11 | 0.250459E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_4:4
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.223147E+10 | 0.00 | 0.255570E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.201357E+10 | 0.00 | 0.174939E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.226571E+10 | 0.00 | 0.148932E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.215465E+10 | 97569557.95 | 0.571893E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.224304E+10 | 0.268019E+10 | 0.552596E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.218780E+10 | 0.660784E+10 | 3609510.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.220990E+10 | 0.992582E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.226514E+10 | 0.787693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.215465E+10 | 0.199549E+10 | 0.220950E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.222095E+10 | 0.231715E+09 | 0.405934E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.215465E+10 | 0.00 | 0.107800E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.221735E+10 | 0.00 | 0.235122E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.263189E+11 | 0.294156E+11 | 0.102792E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.201357E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.226571E+10 | 0.992582E+10 | 0.255570E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_5:5
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.224668E+10 | 0.00 | 0.260169E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.202598E+10 | 0.00 | 0.178892E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.227853E+10 | 0.00 | 0.152966E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.216630E+10 | 84549489.75 | 0.600321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.225517E+10 | 0.254600E+10 | 0.635783E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.219963E+10 | 0.638460E+10 | 7853630.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.222185E+10 | 0.971187E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.227739E+10 | 0.765593E+10 | 241708.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.216630E+10 | 0.187376E+10 | 0.280599E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.223295E+10 | 0.209464E+09 | 0.430115E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.216630E+10 | 0.00 | 0.111274E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.223151E+10 | 0.00 | 0.239557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.264686E+11 | 0.284662E+11 | 0.105515E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.202598E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.227853E+10 | 0.971187E+10 | 0.260169E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_6:6
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.368795E+10 | 0.00 | 0.489937E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.331636E+10 | 0.00 | 0.336272E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.372557E+10 | 0.00 | 0.288928E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.353083E+10 | 0.120149E+09 | 0.116103E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.367794E+10 | 0.434124E+10 | 0.132024E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.358967E+10 | 0.111570E+11 | 16680151.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.361910E+10 | 0.172165E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.371717E+10 | 0.135075E+11 | 595549.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.353083E+10 | 0.299421E+10 | 0.742730E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.363871E+10 | 0.303645E+09 | 0.868504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.353106E+10 | 0.00 | 0.213453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.365712E+10 | 0.00 | 0.451995E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.432223E+11 | 0.496402E+11 | 0.200434E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.331636E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.372557E+10 | 0.172165E+11 | 0.489937E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_7:7
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.211243E+10 | 0.00 | 0.253764E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.190154E+10 | 0.00 | 0.174142E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.213780E+10 | 0.00 | 0.149632E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.202690E+10 | 62489013.54 | 0.599230E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.211135E+10 | 0.229380E+10 | 0.658110E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.206068E+10 | 0.587865E+10 | 6799732.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.207757E+10 | 0.905731E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.213387E+10 | 0.713665E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.202690E+10 | 0.159808E+10 | 0.355632E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.208883E+10 | 0.163345E+09 | 0.441731E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.202698E+10 | 0.00 | 0.110373E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.209540E+10 | 0.00 | 0.234211E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.248003E+11 | 0.261903E+11 | 0.103642E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.190154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.213780E+10 | 0.905731E+10 | 0.253764E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_8:8
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.211123E+10 | 0.00 | 0.254377E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.190046E+10 | 0.00 | 0.174840E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.213638E+10 | 0.00 | 0.150692E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.202527E+10 | 58445580.07 | 0.610827E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.210966E+10 | 0.221828E+10 | 0.706968E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.205903E+10 | 0.574561E+10 | 9635509.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.207591E+10 | 0.892558E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.213216E+10 | 0.701425E+10 | 197778.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.202527E+10 | 0.154160E+10 | 0.381899E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.208716E+10 | 0.155083E+09 | 0.450223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.202541E+10 | 0.00 | 0.111306E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.209402E+10 | 0.00 | 0.234782E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.247820E+11 | 0.256588E+11 | 0.104309E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.190046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.213638E+10 | 0.892558E+10 | 0.254377E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_9:9
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.213337E+10 | 0.00 | 0.259139E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.192057E+10 | 0.00 | 0.179538E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.215546E+10 | 0.00 | 0.155899E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.204125E+10 | 47242350.04 | 0.655524E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.212630E+10 | 0.201411E+10 | 0.888550E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.207527E+10 | 0.539568E+10 | 24717914.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.209228E+10 | 0.860718E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.214898E+10 | 0.673014E+10 | 1718557.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.204125E+10 | 0.141089E+10 | 0.464096E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.210362E+10 | 0.136467E+09 | 0.477277E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.204166E+10 | 0.00 | 0.114987E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.211521E+10 | 0.00 | 0.239327E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.249952E+11 | 0.243417E+11 | 0.107596E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.192057E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.215546E+10 | 0.860718E+10 | 0.259139E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_10:10
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.235785E+10 | 0.00 | 0.314129E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.210946E+10 | 0.00 | 0.224164E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.233165E+10 | 0.00 | 0.196197E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.217773E+10 | 26789971.05 | 0.892203E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.225444E+10 | 0.156942E+10 | 0.160231E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.220034E+10 | 0.470460E+10 | 0.124336E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.221837E+10 | 0.802932E+10 | 3039590.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.227849E+10 | 0.624889E+10 | 15766766.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.216427E+10 | 0.121026E+10 | 0.761536E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.223040E+10 | 0.110383E+09 | 0.575227E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.217929E+10 | 0.00 | 0.135602E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.232506E+10 | 0.00 | 0.287782E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.268274E+11 | 0.218997E+11 | 0.132969E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.210946E+10 | 0.00 | 3039590.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.235785E+10 | 0.802932E+10 | 0.314129E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_1:1
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.513973E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.710721E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.463181E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.489615E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.512042E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.411682E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.494776E+10 | 0.00 | 0.00 | 0.00 | 0.159900E+09 | 0.00 | 0.155969E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.509622E+10 | 0.00 | 0.00 | 0.00 | 0.232985E+10 | 0.00 | 0.113282E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.494455E+10 | 0.00 | 0.00 | 0.00 | 0.539774E+10 | 0.00 | 3951770.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.510633E+10 | 0.00 | 0.00 | 0.00 | 0.814781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.509622E+10 | 0.00 | 0.00 | 0.00 | 0.659455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.495466E+10 | 0.00 | 0.00 | 0.00 | 0.211608E+10 | 0.00 | 0.221303E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.509642E+10 | 0.00 | 0.00 | 0.00 | 0.271881E+09 | 0.00 | 0.893793E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.492863E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.284796E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.514429E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.653135E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.602071E+11 | 0.00 | 0.00 | 0.00 | 0.250178E+11 | 0.00 | 0.280888E+12 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.463181E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.514429E+10 | 0.00 | 0.00 | 0.00 | 0.814781E+10 | 0.00 | 0.710721E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_2:2
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.208331E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.282016E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.187426E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.186665E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.210182E+10 | 0.00 | 0.00 | 0.00 | 424032.81 | 0.00 | 0.154586E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.201816E+10 | 0.00 | 0.00 | 0.00 | 0.147248E+09 | 0.00 | 0.507528E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.218202E+10 | 0.00 | 0.00 | 0.00 | 0.146821E+10 | 0.00 | 0.243083E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.217805E+10 | 0.00 | 0.00 | 0.00 | 0.295621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.226343E+10 | 0.00 | 0.00 | 0.00 | 0.414836E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.227853E+10 | 0.00 | 0.00 | 0.00 | 0.343082E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.212648E+10 | 0.00 | 0.00 | 0.00 | 0.137192E+10 | 0.00 | 31939295.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.210186E+10 | 0.00 | 0.00 | 0.00 | 0.267508E+09 | 0.00 | 0.308233E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.200761E+10 | 0.00 | 0.00 | 0.00 | 6412122.17 | 0.00 | 0.106048E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.206700E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.258936E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.252825E+11 | 0.00 | 0.00 | 0.00 | 0.137971E+11 | 0.00 | 0.107258E+12 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.187426E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.227853E+10 | 0.00 | 0.00 | 0.00 | 0.414836E+10 | 0.00 | 0.282016E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_3:3
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.222149E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.313074E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.200751E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.213830E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.226027E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181445E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.214985E+10 | 0.00 | 0.00 | 0.00 | 36120720.81 | 0.00 | 0.678074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.223805E+10 | 0.00 | 0.00 | 0.00 | 0.843335E+09 | 0.00 | 0.571908E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.218293E+10 | 0.00 | 0.00 | 0.00 | 0.198808E+10 | 0.00 | 492854.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.220498E+10 | 0.00 | 0.00 | 0.00 | 0.290212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.226010E+10 | 0.00 | 0.00 | 0.00 | 0.230779E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.214985E+10 | 0.00 | 0.00 | 0.00 | 0.620519E+09 | 0.00 | 0.187595E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.221600E+10 | 0.00 | 0.00 | 0.00 | 77112343.17 | 0.00 | 0.468263E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.214985E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129942E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.220860E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.287829E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.262495E+11 | 0.00 | 0.00 | 0.00 | 0.877508E+10 | 0.00 | 0.124835E+12 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.200751E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.226027E+10 | 0.00 | 0.00 | 0.00 | 0.290212E+10 | 0.00 | 0.313074E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_4:4
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.223147E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.319462E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.201357E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.218674E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.226571E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.186165E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.215465E+10 | 0.00 | 0.00 | 0.00 | 29801928.10 | 0.00 | 0.714866E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.224304E+10 | 0.00 | 0.00 | 0.00 | 0.807360E+09 | 0.00 | 0.690744E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.218780E+10 | 0.00 | 0.00 | 0.00 | 0.193776E+10 | 0.00 | 4511887.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.220990E+10 | 0.00 | 0.00 | 0.00 | 0.286938E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.226514E+10 | 0.00 | 0.00 | 0.00 | 0.226805E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.215465E+10 | 0.00 | 0.00 | 0.00 | 0.585136E+09 | 0.00 | 0.276188E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.222095E+10 | 0.00 | 0.00 | 0.00 | 68905038.56 | 0.00 | 0.507418E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.215465E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134750E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.221735E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.293902E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.263189E+11 | 0.00 | 0.00 | 0.00 | 0.856640E+10 | 0.00 | 0.128490E+12 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.201357E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.226571E+10 | 0.00 | 0.00 | 0.00 | 0.286938E+10 | 0.00 | 0.319462E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_5:5
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.224668E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.325211E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.202598E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.223615E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.227853E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.191208E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.216630E+10 | 0.00 | 0.00 | 0.00 | 25941615.68 | 0.00 | 0.750401E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.225517E+10 | 0.00 | 0.00 | 0.00 | 0.769148E+09 | 0.00 | 0.794729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.219963E+10 | 0.00 | 0.00 | 0.00 | 0.187627E+10 | 0.00 | 9817037.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.222185E+10 | 0.00 | 0.00 | 0.00 | 0.281357E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.227739E+10 | 0.00 | 0.00 | 0.00 | 0.220874E+10 | 0.00 | 302135.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.216630E+10 | 0.00 | 0.00 | 0.00 | 0.550328E+09 | 0.00 | 0.350749E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.223295E+10 | 0.00 | 0.00 | 0.00 | 62425124.70 | 0.00 | 0.537643E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.216630E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139093E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.223151E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.299447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.264686E+11 | 0.00 | 0.00 | 0.00 | 0.830641E+10 | 0.00 | 0.131893E+12 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.202598E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.227853E+10 | 0.00 | 0.00 | 0.00 | 0.281357E+10 | 0.00 | 0.325211E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_6:6
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.368795E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.618217E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.331636E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.424318E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.372557E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.364578E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.353083E+10 | 0.00 | 0.00 | 0.00 | 39393671.51 | 0.00 | 0.146502E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.367794E+10 | 0.00 | 0.00 | 0.00 | 0.139842E+10 | 0.00 | 0.166591E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.358967E+10 | 0.00 | 0.00 | 0.00 | 0.348693E+10 | 0.00 | 21047510.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.361910E+10 | 0.00 | 0.00 | 0.00 | 0.530270E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.371717E+10 | 0.00 | 0.00 | 0.00 | 0.414331E+10 | 0.00 | 751482.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.353083E+10 | 0.00 | 0.00 | 0.00 | 0.935604E+09 | 0.00 | 0.937198E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.363871E+10 | 0.00 | 0.00 | 0.00 | 96313166.53 | 0.00 | 0.109590E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.353106E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.269341E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.365712E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.570341E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.432223E+11 | 0.00 | 0.00 | 0.00 | 0.154027E+11 | 0.00 | 0.252914E+12 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.331636E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.372557E+10 | 0.00 | 0.00 | 0.00 | 0.530270E+10 | 0.00 | 0.618217E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_7:7
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.211243E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.317205E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.190154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.217678E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.213780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.187041E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.202690E+10 | 0.00 | 0.00 | 0.00 | 19365736.47 | 0.00 | 0.749038E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.211135E+10 | 0.00 | 0.00 | 0.00 | 0.698717E+09 | 0.00 | 0.822637E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.206068E+10 | 0.00 | 0.00 | 0.00 | 0.174078E+10 | 0.00 | 8499665.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.207757E+10 | 0.00 | 0.00 | 0.00 | 0.264353E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.213387E+10 | 0.00 | 0.00 | 0.00 | 0.207267E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.202690E+10 | 0.00 | 0.00 | 0.00 | 0.471938E+09 | 0.00 | 0.444540E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.208883E+10 | 0.00 | 0.00 | 0.00 | 48900409.12 | 0.00 | 0.552163E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.202698E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137967E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.209540E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.292764E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.248003E+11 | 0.00 | 0.00 | 0.00 | 0.769590E+10 | 0.00 | 0.129553E+12 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.190154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.213780E+10 | 0.00 | 0.00 | 0.00 | 0.264353E+10 | 0.00 | 0.317205E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_8:8
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.211123E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.317971E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.190046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.218550E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.213638E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188365E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.202527E+10 | 0.00 | 0.00 | 0.00 | 18154036.57 | 0.00 | 0.763534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.210966E+10 | 0.00 | 0.00 | 0.00 | 0.676818E+09 | 0.00 | 0.883710E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.205903E+10 | 0.00 | 0.00 | 0.00 | 0.170342E+10 | 0.00 | 12044387.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.207591E+10 | 0.00 | 0.00 | 0.00 | 0.260783E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.213216E+10 | 0.00 | 0.00 | 0.00 | 0.203905E+10 | 0.00 | 247223.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.202527E+10 | 0.00 | 0.00 | 0.00 | 0.455621E+09 | 0.00 | 0.477374E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.208716E+10 | 0.00 | 0.00 | 0.00 | 46469644.86 | 0.00 | 0.562779E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.202541E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139133E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.209402E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.293477E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.247820E+11 | 0.00 | 0.00 | 0.00 | 0.754737E+10 | 0.00 | 0.130386E+12 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.190046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.213638E+10 | 0.00 | 0.00 | 0.00 | 0.260783E+10 | 0.00 | 0.317971E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_9:9
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.213337E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.323924E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.192057E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.224422E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.215546E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.194874E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.204125E+10 | 0.00 | 0.00 | 0.00 | 14783576.53 | 0.00 | 0.819404E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.212630E+10 | 0.00 | 0.00 | 0.00 | 0.617649E+09 | 0.00 | 0.111069E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.207527E+10 | 0.00 | 0.00 | 0.00 | 0.160610E+10 | 0.00 | 30897393.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.209228E+10 | 0.00 | 0.00 | 0.00 | 0.252294E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.214898E+10 | 0.00 | 0.00 | 0.00 | 0.196162E+10 | 0.00 | 2148197.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.204125E+10 | 0.00 | 0.00 | 0.00 | 0.417819E+09 | 0.00 | 0.580121E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.210362E+10 | 0.00 | 0.00 | 0.00 | 40993076.75 | 0.00 | 0.596596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.204166E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.211521E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.299158E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.249952E+11 | 0.00 | 0.00 | 0.00 | 0.718191E+10 | 0.00 | 0.134495E+12 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.192057E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.215546E+10 | 0.00 | 0.00 | 0.00 | 0.252294E+10 | 0.00 | 0.323924E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_10:10
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.235785E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.392661E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.210946E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.280206E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.233165E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.245246E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.217773E+10 | 0.00 | 0.00 | 0.00 | 8566316.05 | 0.00 | 0.111525E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.225444E+10 | 0.00 | 0.00 | 0.00 | 0.489440E+09 | 0.00 | 0.200289E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.220034E+10 | 0.00 | 0.00 | 0.00 | 0.142277E+10 | 0.00 | 0.155420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.221837E+10 | 0.00 | 0.00 | 0.00 | 0.238544E+10 | 0.00 | 3799488.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.227849E+10 | 0.00 | 0.00 | 0.00 | 0.184051E+10 | 0.00 | 19708458.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.216427E+10 | 0.00 | 0.00 | 0.00 | 0.360673E+09 | 0.00 | 0.951920E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.223040E+10 | 0.00 | 0.00 | 0.00 | 33352548.59 | 0.00 | 0.719033E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.217929E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169503E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.232506E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.359727E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.268274E+11 | 0.00 | 0.00 | 0.00 | 0.654076E+10 | 0.00 | 0.166211E+12 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.210946E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3799488.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.235785E+10 | 0.00 | 0.00 | 0.00 | 0.238544E+10 | 0.00 | 0.392661E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.293063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.393672E+11 | 0.00 | 0.00 | 0.73 |
February | 0.459354E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.272067E+11 | 0.00 | 0.00 | 0.72 |
March | 0.746991E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.216903E+11 | 0.00 | 0.00 | 0.72 |
April | 0.940682E+10 | 31917542.57 | 0.00 | 569302.59 | 0.00 | 0.745262E+10 | 0.509983E+09 | 0.00 | 0.73 |
May | 0.529587E+10 | 0.545617E+09 | 0.00 | 6725026.11 | 0.00 | 0.410843E+09 | 0.291089E+10 | 0.00 | 0.73 |
June | 0.148585E+10 | 0.292544E+10 | 0.00 | 9220166.60 | 14182879.32 | 0.00 | 0.270857E+10 | 0.00 | 0.74 |
July | 0.354165E+09 | 0.496724E+10 | 0.00 | 8583578.06 | 25967362.77 | 0.00 | 0.176577E+10 | 0.00 | 0.74 |
August | 0.628958E+09 | 0.237215E+10 | 0.00 | 12470004.73 | 921240.97 | 0.00 | 0.268469E+10 | 0.00 | 0.73 |
September | 0.485756E+10 | 0.101667E+09 | 0.00 | 12557788.09 | 0.00 | 7253699.46 | 0.531352E+10 | 0.00 | 0.74 |
October | 0.116399E+11 | 0.00 | 0.00 | 2454878.52 | 0.00 | 0.427462E+10 | 0.157388E+10 | 0.00 | 0.72 |
November | 0.106960E+11 | 0.00 | 0.00 | 8062.17 | 0.00 | 0.138317E+11 | 24043470.70 | 0.00 | 0.72 |
December | 0.380640E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.361404E+11 | 0.00 | 0.00 | 0.72 |
Annual Sum or Average | 0.631656E+11 | 0.109440E+11 | 0.00 | 52588806.86 | 41071483.06 | 0.150382E+12 | 0.174913E+11 | 0.00 | 0.73 |
Minimum of Months | 0.354165E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.72 |
Maximum of Months | 0.116399E+11 | 0.496724E+10 | 0.00 | 12557788.09 | 25967362.77 | 0.393672E+11 | 0.531352E+10 | 0.00 | 0.74 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.911143E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148923E+11 | 0.00 | 0.00 | 0.54 |
February | 0.149893E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101658E+11 | 0.00 | 0.00 | 0.54 |
March | 0.236308E+10 | 0.00 | 0.00 | 2502.93 | 0.00 | 0.854241E+10 | 372272.86 | 0.00 | 0.55 |
April | 0.297157E+10 | 13393762.50 | 0.00 | 718925.65 | 0.00 | 0.297585E+10 | 0.338408E+09 | 0.00 | 0.55 |
May | 0.193853E+10 | 0.279147E+09 | 0.00 | 4630756.89 | 221617.73 | 99994859.32 | 0.106222E+10 | 0.00 | 0.57 |
June | 0.510834E+09 | 0.140658E+10 | 0.00 | 5339639.27 | 14446790.53 | 0.00 | 0.861132E+09 | 0.00 | 0.59 |
July | 92281933.88 | 0.233192E+10 | 0.00 | 4344450.73 | 32623531.33 | 0.00 | 0.498729E+09 | 0.00 | 0.59 |
August | 0.191661E+09 | 0.116732E+10 | 0.00 | 6340843.17 | 3330354.00 | 0.00 | 0.841789E+09 | 0.00 | 0.60 |
September | 0.185828E+10 | 52457548.72 | 0.00 | 7248364.12 | 0.00 | 0.00 | 0.181491E+10 | 0.00 | 0.58 |
October | 0.432616E+10 | 0.00 | 0.00 | 1733624.47 | 0.00 | 0.152322E+10 | 0.549557E+09 | 0.00 | 0.55 |
November | 0.297445E+10 | 0.00 | 0.00 | 42792.08 | 0.00 | 0.595417E+10 | 41150521.47 | 0.00 | 0.54 |
December | 0.107894E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136676E+11 | 0.00 | 0.00 | 0.54 |
Annual Sum or Average | 0.207158E+11 | 0.525081E+10 | 0.00 | 30401899.31 | 50622293.58 | 0.578213E+11 | 0.600826E+10 | 0.00 | 0.56 |
Minimum of Months | 92281933.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.54 |
Maximum of Months | 0.432616E+10 | 0.233192E+10 | 0.00 | 7248364.12 | 32623531.33 | 0.148923E+11 | 0.181491E+10 | 0.00 | 0.60 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 67971214.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.167000E+11 | 0.00 | 0.00 | 0.57 |
February | 0.569292E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119457E+11 | 0.00 | 0.00 | 0.58 |
March | 0.113275E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105931E+11 | 0.00 | 0.00 | 0.59 |
April | 0.260705E+10 | 8151549.28 | 0.00 | 106141.69 | 1841836.21 | 0.399580E+10 | 0.118801E+09 | 0.00 | 0.58 |
May | 0.249375E+10 | 0.264465E+09 | 0.00 | 1411882.91 | 2991447.71 | 0.235466E+09 | 0.500151E+09 | 0.00 | 0.59 |
June | 0.881028E+09 | 0.117119E+10 | 0.00 | 2686616.43 | 58261557.65 | 0.00 | 0.665298E+09 | 0.00 | 0.60 |
July | 0.299401E+09 | 0.183884E+10 | 0.00 | 2567710.45 | 0.108774E+09 | 0.00 | 0.504523E+09 | 0.00 | 0.59 |
August | 0.463333E+09 | 0.978631E+09 | 0.00 | 3693000.51 | 30211211.85 | 0.00 | 0.937447E+09 | 0.00 | 0.60 |
September | 0.265674E+10 | 49367624.69 | 0.00 | 2871665.75 | 17971.68 | 1116793.45 | 0.119845E+10 | 0.00 | 0.59 |
October | 0.379137E+10 | 0.00 | 0.00 | 459892.69 | 0.00 | 0.263340E+10 | 0.230085E+09 | 0.00 | 0.58 |
November | 0.224745E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.726410E+10 | 0.00 | 0.00 | 0.58 |
December | 0.154018E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154742E+11 | 0.00 | 0.00 | 0.57 |
Annual Sum or Average | 0.173642E+11 | 0.431064E+10 | 0.00 | 13796910.43 | 0.202098E+09 | 0.688430E+11 | 0.415476E+10 | 0.00 | 0.58 |
Minimum of Months | 67971214.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.57 |
Maximum of Months | 0.379137E+10 | 0.183884E+10 | 0.00 | 3693000.51 | 0.108774E+09 | 0.167000E+11 | 0.119845E+10 | 0.00 | 0.60 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 59610152.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.167490E+11 | 0.00 | 0.00 | 0.58 |
February | 0.408609E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121184E+11 | 0.00 | 0.00 | 0.58 |
March | 0.920275E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108075E+11 | 0.00 | 0.00 | 0.59 |
April | 0.235856E+10 | 7878225.23 | 0.00 | 68848.78 | 1894231.60 | 0.426495E+10 | 82143363.78 | 0.00 | 0.58 |
May | 0.239670E+10 | 0.261797E+09 | 0.00 | 1254879.91 | 2984686.96 | 0.352962E+09 | 0.452541E+09 | 0.00 | 0.59 |
June | 0.896604E+09 | 0.116368E+10 | 0.00 | 2494144.71 | 57990185.98 | 0.00 | 0.644926E+09 | 0.00 | 0.60 |
July | 0.309052E+09 | 0.182775E+10 | 0.00 | 2492614.28 | 0.108424E+09 | 0.00 | 0.497748E+09 | 0.00 | 0.59 |
August | 0.513019E+09 | 0.969565E+09 | 0.00 | 3542154.46 | 29919888.13 | 0.00 | 0.894950E+09 | 0.00 | 0.60 |
September | 0.271495E+10 | 48951976.95 | 0.00 | 2628260.96 | 15380.65 | 7886127.90 | 0.111545E+10 | 0.00 | 0.59 |
October | 0.359422E+10 | 0.00 | 0.00 | 400791.93 | 0.00 | 0.285027E+10 | 0.193655E+09 | 0.00 | 0.58 |
November | 0.198652E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.752132E+10 | 0.00 | 0.00 | 0.58 |
December | 75213342.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155845E+11 | 0.00 | 0.00 | 0.57 |
Annual Sum or Average | 0.162333E+11 | 0.427963E+10 | 0.00 | 12881695.04 | 0.201228E+09 | 0.702569E+11 | 0.388141E+10 | 0.00 | 0.58 |
Minimum of Months | 59610152.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.57 |
Maximum of Months | 0.359422E+10 | 0.182775E+10 | 0.00 | 3542154.46 | 0.108424E+09 | 0.167490E+11 | 0.111545E+10 | 0.00 | 0.60 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 53921197.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.167803E+11 | 0.00 | 0.00 | 0.58 |
February | 0.293023E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122445E+11 | 0.00 | 0.00 | 0.58 |
March | 0.678670E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110529E+11 | 0.00 | 0.00 | 0.59 |
April | 0.207557E+10 | 7666951.81 | 0.00 | 47113.30 | 1936915.99 | 0.456444E+10 | 51855605.80 | 0.00 | 0.58 |
May | 0.234156E+10 | 0.258078E+09 | 0.00 | 1109390.53 | 2984438.57 | 0.440813E+09 | 0.396675E+09 | 0.00 | 0.59 |
June | 0.918484E+09 | 0.114977E+10 | 0.00 | 2272221.61 | 58362377.98 | 0.00 | 0.621171E+09 | 0.00 | 0.60 |
July | 0.328183E+09 | 0.180491E+10 | 0.00 | 2366181.10 | 0.108177E+09 | 0.00 | 0.485131E+09 | 0.00 | 0.59 |
August | 0.572660E+09 | 0.954830E+09 | 0.00 | 3305285.90 | 29606764.49 | 0.00 | 0.848782E+09 | 0.00 | 0.60 |
September | 0.275221E+10 | 48126712.51 | 0.00 | 2399753.51 | 12264.90 | 36410910.87 | 0.103641E+10 | 0.00 | 0.59 |
October | 0.333915E+10 | 0.00 | 0.00 | 356576.15 | 0.00 | 0.310463E+10 | 0.183199E+09 | 0.00 | 0.58 |
November | 0.171404E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.779106E+10 | 0.00 | 0.00 | 0.58 |
December | 59485119.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156176E+11 | 0.00 | 0.00 | 0.57 |
Annual Sum or Average | 0.151269E+11 | 0.422337E+10 | 0.00 | 11856522.10 | 0.201080E+09 | 0.716326E+11 | 0.362323E+10 | 0.00 | 0.58 |
Minimum of Months | 53921197.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.57 |
Maximum of Months | 0.333915E+10 | 0.180491E+10 | 0.00 | 3305285.90 | 0.108177E+09 | 0.167803E+11 | 0.103641E+10 | 0.00 | 0.60 |
Report: MechanicalVentilationLoadsMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 84218623.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.311581E+11 | 0.00 | 0.00 | 0.54 |
February | 0.141272E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.229085E+11 | 0.00 | 0.00 | 0.53 |
March | 0.812124E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.206741E+11 | 0.00 | 0.00 | 0.54 |
April | 0.312150E+10 | 12865550.49 | 0.00 | 39539.57 | 3656212.94 | 0.888753E+10 | 58666652.62 | 0.00 | 0.53 |
May | 0.378921E+10 | 0.474785E+09 | 0.00 | 1819397.07 | 0.00 | 0.928752E+09 | 0.775838E+09 | 0.00 | 0.54 |
June | 0.156527E+10 | 0.223596E+10 | 0.00 | 3886230.20 | 39531419.51 | 3008919.65 | 0.108583E+10 | 0.00 | 0.55 |
July | 0.496492E+09 | 0.347893E+10 | 0.00 | 4421338.38 | 0.114186E+09 | 0.00 | 0.804694E+09 | 0.00 | 0.54 |
August | 0.103960E+10 | 0.182575E+10 | 0.00 | 5628818.49 | 7524185.32 | 0.00 | 0.131270E+10 | 0.00 | 0.55 |
September | 0.480742E+10 | 83430859.58 | 0.00 | 4009227.42 | 0.00 | 0.194106E+09 | 0.183634E+10 | 0.00 | 0.54 |
October | 0.540232E+10 | 0.00 | 0.00 | 538911.53 | 0.00 | 0.635921E+10 | 0.341939E+09 | 0.00 | 0.53 |
November | 0.200807E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154668E+11 | 0.00 | 33173.17 | 0.54 |
December | 89480263.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.290168E+11 | 0.00 | 0.00 | 0.53 |
Annual Sum or Average | 0.233570E+11 | 0.811171E+10 | 0.00 | 20343462.66 | 0.164898E+09 | 0.135597E+12 | 0.621600E+10 | 33173.17 | 0.54 |
Minimum of Months | 84218623.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.53 |
Maximum of Months | 0.540232E+10 | 0.347893E+10 | 0.00 | 5628818.49 | 0.114186E+09 | 0.311581E+11 | 0.183634E+10 | 33173.17 | 0.55 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 29136182.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155479E+11 | 0.00 | 0.00 | 0.54 |
February | 47584592.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114532E+11 | 0.00 | 0.00 | 0.53 |
March | 0.330001E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103990E+11 | 0.00 | 0.00 | 0.54 |
April | 0.138797E+10 | 6443984.94 | 0.00 | 15416.76 | 1825984.65 | 0.461018E+10 | 29240101.48 | 0.00 | 0.53 |
May | 0.186027E+10 | 0.239181E+09 | 0.00 | 868689.04 | 0.00 | 0.510489E+09 | 0.370616E+09 | 0.00 | 0.54 |
June | 0.790621E+09 | 0.112293E+10 | 0.00 | 1902117.91 | 19205935.07 | 1919721.36 | 0.529948E+09 | 0.00 | 0.55 |
July | 0.241481E+09 | 0.174520E+10 | 0.00 | 2186151.85 | 55304722.73 | 0.00 | 0.406539E+09 | 0.00 | 0.54 |
August | 0.504704E+09 | 0.916528E+09 | 0.00 | 2792618.16 | 3559772.16 | 0.00 | 0.665332E+09 | 0.00 | 0.55 |
September | 0.236481E+10 | 41756439.80 | 0.00 | 1978747.34 | 0.00 | 0.144347E+09 | 0.909044E+09 | 0.00 | 0.54 |
October | 0.252658E+10 | 0.00 | 0.00 | 261543.43 | 0.00 | 0.334961E+10 | 0.169700E+09 | 0.00 | 0.53 |
November | 0.897344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.783246E+10 | 0.00 | 16809.42 | 0.54 |
December | 28841630.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.144850E+11 | 0.00 | 0.00 | 0.53 |
Annual Sum or Average | 0.110093E+11 | 0.407204E+10 | 0.00 | 10005284.48 | 79896414.61 | 0.683341E+11 | 0.308042E+10 | 16809.42 | 0.54 |
Minimum of Months | 28841630.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.53 |
Maximum of Months | 0.252658E+10 | 0.174520E+10 | 0.00 | 2792618.16 | 55304722.73 | 0.155479E+11 | 0.909044E+09 | 16809.42 | 0.55 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 26587623.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155540E+11 | 0.00 | 0.00 | 0.54 |
February | 37413842.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114668E+11 | 0.00 | 0.00 | 0.53 |
March | 0.311274E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104198E+11 | 0.00 | 0.00 | 0.54 |
April | 0.130791E+10 | 6339797.09 | 0.00 | 11208.11 | 1851211.93 | 0.468667E+10 | 27039060.74 | 0.00 | 0.53 |
May | 0.181534E+10 | 0.236902E+09 | 0.00 | 801500.70 | 0.00 | 0.560921E+09 | 0.354018E+09 | 0.00 | 0.54 |
June | 0.806460E+09 | 0.111390E+10 | 0.00 | 1803472.52 | 19511552.70 | 2688743.76 | 0.510137E+09 | 0.00 | 0.55 |
July | 0.253335E+09 | 0.173271E+10 | 0.00 | 2132656.21 | 54725659.97 | 0.00 | 0.398404E+09 | 0.00 | 0.54 |
August | 0.531915E+09 | 0.908077E+09 | 0.00 | 2699066.07 | 3518432.19 | 0.00 | 0.643550E+09 | 0.00 | 0.55 |
September | 0.233383E+10 | 41444916.91 | 0.00 | 1892134.84 | 0.00 | 0.188200E+09 | 0.890025E+09 | 0.00 | 0.54 |
October | 0.245229E+10 | 0.00 | 0.00 | 246191.97 | 0.00 | 0.342796E+10 | 0.162537E+09 | 0.00 | 0.53 |
November | 0.834282E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.789501E+10 | 0.00 | 18641.61 | 0.54 |
December | 24533507.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.144912E+11 | 0.00 | 0.00 | 0.53 |
Annual Sum or Average | 0.107352E+11 | 0.403938E+10 | 0.00 | 9586230.43 | 79606856.79 | 0.686933E+11 | 0.298571E+10 | 18641.61 | 0.54 |
Minimum of Months | 24533507.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.53 |
Maximum of Months | 0.245229E+10 | 0.173271E+10 | 0.00 | 2699066.07 | 54725659.97 | 0.155540E+11 | 0.890025E+09 | 18641.61 | 0.55 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 20588462.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156016E+11 | 0.00 | 0.00 | 0.54 |
February | 21148062.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115189E+11 | 0.00 | 0.00 | 0.54 |
March | 0.199281E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105467E+11 | 0.00 | 0.00 | 0.54 |
April | 0.104555E+10 | 6019166.68 | 0.00 | 2788.13 | 1931289.41 | 0.495058E+10 | 7694394.07 | 0.00 | 0.53 |
May | 0.164067E+10 | 0.229943E+09 | 0.00 | 611419.49 | 0.00 | 0.753731E+09 | 0.303968E+09 | 0.00 | 0.54 |
June | 0.844000E+09 | 0.108675E+10 | 0.00 | 1532081.19 | 20648075.37 | 19548825.46 | 0.442120E+09 | 0.00 | 0.55 |
July | 0.282188E+09 | 0.169960E+10 | 0.00 | 1972381.50 | 53345598.86 | 0.00 | 0.379954E+09 | 0.00 | 0.54 |
August | 0.591359E+09 | 0.888012E+09 | 0.00 | 2467949.95 | 3403479.45 | 0.00 | 0.596284E+09 | 0.00 | 0.55 |
September | 0.220032E+10 | 40803683.00 | 0.00 | 1666851.64 | 0.00 | 0.349083E+09 | 0.845023E+09 | 0.00 | 0.54 |
October | 0.225356E+10 | 0.00 | 0.00 | 208978.81 | 0.00 | 0.363352E+10 | 0.147736E+09 | 0.00 | 0.53 |
November | 0.597553E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.813087E+10 | 0.00 | 26464.75 | 0.54 |
December | 20605465.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.145301E+11 | 0.00 | 0.00 | 0.53 |
Annual Sum or Average | 0.971682E+10 | 0.395112E+10 | 0.00 | 8462450.71 | 79328443.10 | 0.700346E+11 | 0.272278E+10 | 26464.75 | 0.54 |
Minimum of Months | 20588462.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.53 |
Maximum of Months | 0.225356E+10 | 0.169960E+10 | 0.00 | 2467949.95 | 53345598.86 | 0.156016E+11 | 0.845023E+09 | 26464.75 | 0.55 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:20:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 7945557.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162489E+11 | 0.00 | 0.00 | 0.56 |
February | 7137602.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119626E+11 | 0.00 | 0.00 | 0.55 |
March | 11960318.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109736E+11 | 0.00 | 0.00 | 0.55 |
April | 0.425087E+09 | 4681971.26 | 0.00 | 0.00 | 2715681.75 | 0.557389E+10 | 0.00 | 9594.56 | 0.54 |
May | 0.112769E+10 | 0.214611E+09 | 0.00 | 233531.03 | 1381788.43 | 0.133738E+10 | 0.128171E+09 | 0.00 | 0.54 |
June | 0.813648E+09 | 0.101578E+10 | 10587.87 | 1011145.61 | 20506894.03 | 0.118746E+09 | 0.308534E+09 | 77.71 | 0.55 |
July | 0.308170E+09 | 0.161746E+10 | 0.00 | 1555230.85 | 46009802.22 | 6197935.81 | 0.356492E+09 | 0.00 | 0.54 |
August | 0.693947E+09 | 0.848794E+09 | 0.00 | 1933445.68 | 3190737.37 | 10208551.69 | 0.499814E+09 | 0.00 | 0.55 |
September | 0.185750E+10 | 40528985.24 | 0.00 | 1237866.62 | 0.00 | 0.724163E+09 | 0.740213E+09 | 0.00 | 0.54 |
October | 0.137924E+10 | 0.00 | 0.00 | 147834.29 | 0.00 | 0.448681E+10 | 0.134398E+09 | 0.00 | 0.53 |
November | 0.116237E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.867602E+10 | 0.00 | 0.00 | 0.54 |
December | 5780938.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150770E+11 | 0.00 | 0.00 | 0.55 |
Annual Sum or Average | 0.675435E+10 | 0.374186E+10 | 10587.87 | 6119054.08 | 73804903.79 | 0.751956E+11 | 0.216762E+10 | 9672.27 | 0.55 |
Minimum of Months | 5780938.02 | 0.00 | 0.00 | 0.00 | 0.00 | 6197935.81 | 0.00 | 0.00 | 0.53 |
Maximum of Months | 0.185750E+10 | 0.161746E+10 | 10587.87 | 1933445.68 | 46009802.22 | 0.162489E+11 | 0.740213E+09 | 9594.56 | 0.56 |