Program Version:EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:18
Tabular Output Report in Format: HTML
Building: RetailStripmall
Environment: RUNPERIOD 1 ** New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820
Simulation Timestamp: 2020-06-03 19:18:56
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2020-06-03 19:18:56
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 2223.27 | 1063.61 | 1063.61 |
Net Site Energy | 2223.27 | 1063.61 | 1063.61 |
Total Source Energy | 7034.82 | 3365.43 | 3365.43 |
Net Source Energy | 7034.82 | 3365.43 | 3365.43 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 2090.32 |
Net Conditioned Building Area | 2090.32 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 3.02 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 804.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 708.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 167.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 128.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 352.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 58.79 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 2220.25 | 3.02 | 0.00 | 0.00 | 0.00 | 87.30 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 3.02 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 804.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 708.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 167.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 128.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 352.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 58.79 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 418.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 581.61 | 1.45 | 0.00 | 0.00 | 0.00 | 0.04 |
Other | 61.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 1062.16 | 1.45 | 0.00 | 0.00 | 0.00 | 0.04 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 418.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 581.61 | 1.45 | 0.00 | 0.00 | 0.00 | 0.04 |
Other | 61.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 1062.16 | 1.45 | 0.00 | 0.00 | 0.00 | 0.04 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 2220.253 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 2220.253 | 100.00 |
Total On-Site and Utility Electric Sources | 2220.253 | 100.00 |
Total Electricity End Uses | 2220.253 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 87.30 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 87.30 | 100.00 |
Total Water End Uses | 87.30 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 9.17 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 1197.17 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Meter |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2006
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Meter |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTRIPMALL
| Meter |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 1B
| Meter |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY IND_DELHI_NEWDELHI
| Meter |ZoneCoolingSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ZoneHeatingSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ZoneElectricSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |SpaceGainsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |PeakSpaceGainsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |SpaceGainComponentsAtCoolingPeakMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ComfortReportSimple55Monthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |OccupantComfortDataSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |DXReportMonthly
| PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL |WindowReportMonthly
| LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR |WindowEnergyReportMonthly
| LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR |WindowZoneSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |WindowEnergyZoneSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| GAS TANK1 | GAS TANK2 | GAS TANK3 | GAS TANK4 | GAS TANK5 | GAS TANK6 | GAS TANK7 |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC_1:1_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_2:2_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_3:3_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_4:4_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_5:5_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_6:6_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_7:7_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_8:8_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_9:9_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_10:10_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL |FanReportMonthly
| PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN |ZoneTemperatureOscillationReportMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |MechanicalVentilationLoadsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2020-06-03 19:18:56
GeneralValue | |
Program Version and Build | EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:18 |
RunPeriod | RUNPERIOD 1 |
Weather File | New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820 |
Latitude [deg] | 28.58 |
Longitude [deg] | 77.20 |
Elevation [m] | 216.00 |
Time Zone | 5.50 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Above Ground Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Window Opening Area [m2] | 124.29 | 0.00 | 0.00 | 124.29 | 0.00 |
Gross Window-Wall Ratio [%] | 10.50 | 0.00 | 0.00 | 26.24 | 0.00 |
Above Ground Window-Wall Ratio [%] | 10.50 | 0.00 | 0.00 | 26.24 | 0.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Above Ground Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Window Opening Area [m2] | 124.29 | 0.00 | 0.00 | 124.29 | 0.00 |
Gross Window-Wall Ratio [%] | 10.50 | 0.00 | 0.00 | 26.24 | 0.00 |
Above Ground Window-Wall Ratio [%] | 10.50 | 0.00 | 0.00 | 26.24 | 0.00 |
Total | |
Gross Roof Area [m2] | 2090.32 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
LGSTORE1 | 348.39 | Yes | Yes | 1805.20 | 1.00 | 276.30 | 0.00 | 20.75 | 20.75 | 28.8173 | 11.61 | 4.3000 |
SMSTORE1 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.37 | 10.37 | 28.8173 | 11.61 | 4.3000 |
SMSTORE2 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.35 | 10.35 | 22.6280 | 11.61 | 4.3000 |
SMSTORE3 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.35 | 10.35 | 22.6280 | 11.61 | 4.3000 |
SMSTORE4 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.35 | 10.35 | 22.6280 | 11.61 | 4.3000 |
LGSTORE2 | 348.39 | Yes | Yes | 1805.20 | 1.00 | 157.89 | 0.00 | 20.70 | 20.70 | 18.3225 | 11.61 | 4.3000 |
SMSTORE5 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.35 | 10.35 | 18.3225 | 11.61 | 4.3000 |
SMSTORE6 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.35 | 10.35 | 18.3225 | 11.61 | 4.3000 |
SMSTORE7 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.35 | 10.35 | 18.3225 | 11.61 | 4.3000 |
SMSTORE8 | 174.19 | Yes | Yes | 902.60 | 1.00 | 197.36 | 0.00 | 10.35 | 10.35 | 18.3225 | 11.61 | 4.3000 |
Total | 2090.32 | 10831.20 | 1184.15 | 0.00 | 124.29 | 124.29 | 22.0226 | 11.61 | 4.3000 | |||
Conditioned Total | 2090.32 | 10831.20 | 1184.15 | 0.00 | 124.29 | 124.29 | 22.0226 | 11.61 | 4.3000 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:18:56
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 10-JUN-15:50 | 02-JAN-08:09 | - | - | - | 06-JAN-13:09 |
Heating | 0.00 | 94354.47 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 117828.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 43732.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 8089.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 20381.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 7525.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 197558.14 | 94354.47 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 94354.47 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 117828.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 43732.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 8089.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 20381.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 7525.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:18:56
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 3.28 | 0.00 | 0.00 | 0.00 |
Cooling | 2548.43 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 2244.57 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 529.05 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 407.66 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1115.63 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 186.20 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 7031.54 | 3.28 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 1.57 | 0.00 | 0.00 | 0.00 |
Cooling | 1219.16 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1073.80 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 253.09 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 195.02 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 533.71 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 89.08 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 3363.86 | 1.57 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 1.57 | 0.00 | 0.00 | 0.00 |
Cooling | 1219.16 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1073.80 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 253.09 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 195.02 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 533.71 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 89.08 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 3363.86 | 1.57 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:18:56
AirTerminal:SingleDuct:UncontrolledDesign Size Maximum Air Flow Rate [m3/s] | |
LGSTORE1 DIRECT AIR | 3.22 |
SMSTORE1 DIRECT AIR | 1.63 |
SMSTORE2 DIRECT AIR | 1.56 |
SMSTORE3 DIRECT AIR | 1.56 |
SMSTORE4 DIRECT AIR | 1.56 |
LGSTORE2 DIRECT AIR | 2.87 |
SMSTORE5 DIRECT AIR | 1.51 |
SMSTORE6 DIRECT AIR | 1.51 |
SMSTORE7 DIRECT AIR | 1.51 |
SMSTORE8 DIRECT AIR | 1.68 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC_1:1 | 3.22 | 3.22 | 3.22 | 3.22 | 3.22 | 3.22 | 1.00 | 1.000000 | 3.22 |
PSZ-AC_2:2 | 1.63 | 1.63 | 1.63 | 1.63 | 1.63 | 1.63 | 1.00 | 1.00 | 1.63 |
PSZ-AC_3:3 | 1.56 | 1.56 | 1.56 | 1.56 | 1.56 | 1.56 | 1.00 | 1.00 | 1.56 |
PSZ-AC_4:4 | 1.56 | 1.56 | 1.56 | 1.56 | 1.56 | 1.56 | 1.00 | 1.00 | 1.56 |
PSZ-AC_5:5 | 1.56 | 1.56 | 1.56 | 1.56 | 1.56 | 1.56 | 1.00 | 1.00 | 1.56 |
PSZ-AC_6:6 | 2.87 | 2.87 | 2.87 | 2.87 | 2.87 | 2.87 | 1.00 | 1.00 | 2.87 |
PSZ-AC_7:7 | 1.51 | 1.51 | 1.51 | 1.51 | 1.51 | 1.51 | 1.00 | 1.00 | 1.51 |
PSZ-AC_8:8 | 1.51 | 1.51 | 1.51 | 1.51 | 1.51 | 1.51 | 1.00 | 1.00 | 1.51 |
PSZ-AC_9:9 | 1.51 | 1.51 | 1.51 | 1.51 | 1.51 | 1.51 | 1.00 | 1.00 | 1.51 |
PSZ-AC_10:10 | 1.68 | 1.68 | 1.68 | 1.68 | 1.68 | 1.68 | 1.00 | 1.000000 | 1.68 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC_1:1_OA_CONTROLLER | 3.22 | 0.530908 |
PSZ-AC_2:2_OA_CONTROLLER | 1.63 | 0.265454 |
PSZ-AC_3:3_OA_CONTROLLER | 1.56 | 0.265454 |
PSZ-AC_4:4_OA_CONTROLLER | 1.56 | 0.265454 |
PSZ-AC_5:5_OA_CONTROLLER | 1.56 | 0.265454 |
PSZ-AC_6:6_OA_CONTROLLER | 2.87 | 0.530908 |
PSZ-AC_7:7_OA_CONTROLLER | 1.51 | 0.265454 |
PSZ-AC_8:8_OA_CONTROLLER | 1.51 | 0.265454 |
PSZ-AC_9:9_OA_CONTROLLER | 1.51 | 0.265454 |
PSZ-AC_10:10_OA_CONTROLLER | 1.68 | 0.265454 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC_1:1_UNITARY_PACKAGE_DX | 3.22 | 3.22 | 3.22 | 3.22 | 66560.00 | 81128.24 | 40.00 | 1.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_DX | 1.63 | 1.63 | 1.63 | 1.63 | 33607.54 | 40997.44 | 40.00 | 1.00 |
PSZ-AC_3:3_UNITARY_PACKAGE_DX | 1.56 | 1.56 | 1.56 | 1.56 | 32386.23 | 39471.74 | 40.00 | 1.00 |
PSZ-AC_4:4_UNITARY_PACKAGE_DX | 1.56 | 1.56 | 1.56 | 1.56 | 32328.52 | 39399.56 | 40.00 | 1.00 |
PSZ-AC_5:5_UNITARY_PACKAGE_DX | 1.56 | 1.56 | 1.56 | 1.56 | 32284.42 | 39344.45 | 40.00 | 1.00 |
PSZ-AC_6:6_UNITARY_PACKAGE_DX | 2.87 | 2.87 | 2.87 | 2.87 | 60301.45 | 73310.12 | 40.00 | 1.00 |
PSZ-AC_7:7_UNITARY_PACKAGE_DX | 1.51 | 1.51 | 1.51 | 1.51 | 31517.54 | 38385.92 | 40.00 | 1.00 |
PSZ-AC_8:8_UNITARY_PACKAGE_DX | 1.51 | 1.51 | 1.51 | 1.51 | 31406.18 | 38246.90 | 40.00 | 1.00 |
PSZ-AC_9:9_UNITARY_PACKAGE_DX | 1.51 | 1.51 | 1.51 | 1.51 | 31468.69 | 38324.73 | 40.00 | 1.00 |
PSZ-AC_10:10_UNITARY_PACKAGE_DX | 1.68 | 1.68 | 1.68 | 1.68 | 34189.34 | 41962.10 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | Speed 2 Design Size Rated Total Cooling Capacity [W] | Speed 2 User-Specified Rated Total Cooling Capacity [W] | Speed 1 Design Size Rated Total Cooling Capacity [W] | Speed 1 User-Specified Rated Total Cooling Capacity [W] | Speed 2 Design Size Rated Sensible Heat Ratio | Speed 2 User-Specified Rated Sensible Heat Ratio | Speed 1 Design Size Rated Sensible Heat Ratio | Speed 1 User-Specified Rated Sensible Heat Ratio | |
PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | 3.22 | 1.61 | 3.22 | 53382.39 | 66560.00 | 33280.00 | 66560.00 | 0.725867 | 0.725870 | 0.725870 | 0.725870 |
PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | 1.63 | 0.815930 | 1.63 | 27013.08 | 33607.54 | 16803.77 | 33607.54 | 0.726514 | 0.726510 | 0.726510 | 0.726510 |
PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | 1.56 | 0.781690 | 1.56 | 26167.32 | 32386.23 | 16193.11 | 32386.23 | 0.724789 | 0.724790 | 0.724790 | 0.724790 |
PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | 1.56 | 0.780070 | 1.56 | 26130.07 | 32328.52 | 16164.26 | 32328.52 | 0.724704 | 0.724700 | 0.724700 | 0.724700 |
PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | 1.56 | 0.778835 | 1.56 | 26101.65 | 32284.42 | 16142.21 | 32284.42 | 0.724639 | 0.724640 | 0.724640 | 0.724640 |
PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | 2.87 | 1.44 | 2.87 | 49201.57 | 60301.45 | 30150.72 | 60301.45 | 0.721058 | 0.721060 | 0.721060 | 0.721060 |
PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | 1.51 | 0.757325 | 1.51 | 25605.49 | 31517.54 | 15758.77 | 31517.54 | 0.723477 | 0.723480 | 0.723480 | 0.723480 |
PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | 1.51 | 0.754205 | 1.51 | 25533.16 | 31406.18 | 15703.09 | 31406.18 | 0.723305 | 0.723310 | 0.723310 | 0.723310 |
PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | 1.51 | 0.755950 | 1.51 | 25573.94 | 31468.69 | 15734.34 | 31468.69 | 0.723399 | 0.723400 | 0.723400 | 0.723400 |
PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | 1.68 | 0.837570 | 1.68 | 27729.51 | 34189.34 | 17094.67 | 34189.34 | 0.729189 | 0.729190 | 0.729190 | 0.729190 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | 3.22 | 3529.59 |
PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | 1.63 | 1786.07 |
PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | 1.56 | 1711.13 |
PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | 1.56 | 1707.58 |
PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | 1.56 | 1704.88 |
PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | 2.87 | 3145.56 |
PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | 1.51 | 1657.79 |
PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | 1.51 | 1650.96 |
PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | 1.51 | 1654.79 |
PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | 1.68 | 1833.46 |
Design Size Nominal Capacity [W] | |
PSZ-AC_1:1_UNITARY_PACKAGE_HEATCOIL | 81128.24 |
PSZ-AC_2:2_UNITARY_PACKAGE_HEATCOIL | 40997.44 |
PSZ-AC_3:3_UNITARY_PACKAGE_HEATCOIL | 39471.74 |
PSZ-AC_4:4_UNITARY_PACKAGE_HEATCOIL | 39399.56 |
PSZ-AC_5:5_UNITARY_PACKAGE_HEATCOIL | 39344.45 |
PSZ-AC_6:6_UNITARY_PACKAGE_HEATCOIL | 73310.12 |
PSZ-AC_7:7_UNITARY_PACKAGE_HEATCOIL | 38385.92 |
PSZ-AC_8:8_UNITARY_PACKAGE_HEATCOIL | 38246.90 |
PSZ-AC_9:9_UNITARY_PACKAGE_HEATCOIL | 38324.73 |
PSZ-AC_10:10_UNITARY_PACKAGE_HEATCOIL | 41962.10 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:18:56
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
LGSTORE1_WALL_3 | LGSTORE1_WALL_3_DOOR_1 | LGSTORE1_WALL_3_DOOR_2 | |
LGSTORE1_WALL_1 | LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | |
SMSTORE1_WALL_1 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | |
SMSTORE1_WALL_3 | SMSTORE1_WALL_3_DOOR | |
SMSTORE2_WALL_1 | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | |
SMSTORE2_WALL_3 | SMSTORE2_WALL_3_DOOR | |
SMSTORE3_WALL_1 | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | |
SMSTORE3_WALL_3 | SMSTORE3_WALL_3_DOOR | |
SMSTORE4_WALL_1 | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | |
SMSTORE4_WALL_3 | SMSTORE4_WALL_3_DOOR | |
LGSTORE2_WALL_3 | LGSTORE2_WALL_3_DOOR_1 | LGSTORE2_WALL_3_DOOR_2 | |
LGSTORE2_WALL_1 | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | |
SMSTORE5_WALL_1 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | |
SMSTORE5_WALL_3 | SMSTORE5_WALL_3_DOOR | |
SMSTORE6_WALL_1 | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | |
SMSTORE6_WALL_3 | SMSTORE6_WALL_3_DOOR | |
SMSTORE7_WALL_1 | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | |
SMSTORE7_WALL_3 | SMSTORE7_WALL_3_DOOR | |
SMSTORE8_WALL_1 | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR | |
SMSTORE8_WALL_3 | SMSTORE8_WALL_3_DOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2020-06-03 19:18:56
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2020-06-03 19:18:56
VersionVersion ID | |
1 | 9.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 25.10 | 19.60 | 14.50 | 13.40 | 17.00 | 22.40 | 29.10 | 33.00 | 33.60 | 31.70 | 30.00 | 28.70 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820 | 28.58 | 77.20 | 5.50 | 216.00 | 98757 | 1.1738 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 24.84 | 20.20 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RetailStripmall | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 10 | 118 | 48 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | LGSTORE1 | 0.0 | 0.00 | 0.00 | 0.00 | 7.62 | 11.43 | 2.59 | 1 | 1 | 1 | 0.00 | 15.24 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 1805.20 | TARP | TARP | 348.39 | 276.30 | 247.76 | 20.75 | 6 | 8 | 0 | Yes |
2 | SMSTORE1 | 0.0 | 0.00 | 0.00 | 0.00 | 19.05 | 11.43 | 2.59 | 1 | 1 | 1 | 15.24 | 22.86 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.67 | 10.37 | 6 | 4 | 0 | Yes |
3 | SMSTORE2 | 0.0 | 0.00 | 0.00 | 0.00 | 26.67 | 11.43 | 2.59 | 1 | 1 | 1 | 22.86 | 30.48 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.35 | 6 | 4 | 0 | Yes |
4 | SMSTORE3 | 0.0 | 0.00 | 0.00 | 0.00 | 34.29 | 11.43 | 2.59 | 1 | 1 | 1 | 30.48 | 38.10 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.35 | 6 | 4 | 0 | Yes |
5 | SMSTORE4 | 0.0 | 0.00 | 0.00 | 0.00 | 41.91 | 11.43 | 2.59 | 1 | 1 | 1 | 38.10 | 45.72 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.35 | 6 | 4 | 0 | Yes |
6 | LGSTORE2 | 0.0 | 0.00 | 0.00 | 0.00 | 53.34 | 11.43 | 2.59 | 1 | 1 | 1 | 45.72 | 60.96 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 1805.20 | TARP | TARP | 348.39 | 157.89 | 129.43 | 20.70 | 6 | 8 | 0 | Yes |
7 | SMSTORE5 | 0.0 | 0.00 | 0.00 | 0.00 | 64.77 | 11.43 | 2.59 | 1 | 1 | 1 | 60.96 | 68.58 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.35 | 6 | 4 | 0 | Yes |
8 | SMSTORE6 | 0.0 | 0.00 | 0.00 | 0.00 | 72.39 | 11.43 | 2.59 | 1 | 1 | 1 | 68.58 | 76.20 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.35 | 6 | 4 | 0 | Yes |
9 | SMSTORE7 | 0.0 | 0.00 | 0.00 | 0.00 | 80.01 | 11.43 | 2.59 | 1 | 1 | 1 | 76.20 | 83.82 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.35 | 6 | 4 | 0 | Yes |
10 | SMSTORE8 | 0.0 | 0.00 | 0.00 | 0.00 | 87.63 | 11.43 | 2.59 | 1 | 1 | 1 | 83.82 | 91.44 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 197.36 | 183.13 | 10.35 | 6 | 4 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | LGSTORE1 | 348.39 | 30.0 | 11.614 | 8.610E-002 | 28.817 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 33.117 | No |
2 | SMSTORE1 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 28.817 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 33.117 | No |
3 | SMSTORE2 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 22.628 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 26.928 | No |
4 | SMSTORE3 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 22.628 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 26.928 | No |
5 | SMSTORE4 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 22.628 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 26.928 | No |
6 | LGSTORE2 | 348.39 | 30.0 | 11.614 | 8.610E-002 | 18.322 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 22.622 | No |
7 | SMSTORE5 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 18.322 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 22.622 | No |
8 | SMSTORE6 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 18.322 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 22.622 | No |
9 | SMSTORE7 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 18.322 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 22.622 | No |
10 | SMSTORE8 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 18.322 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 22.622 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | |
1 | LGSTORE1 | TYPE1_OCC_SCH | LGSTORE1 | 348.39 | 30.0 | 30.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 30 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
2 | SMSTORE1 | TYPE1_OCC_SCH | SMSTORE1 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
3 | SMSTORE2 | TYPE2_OCC_SCH | SMSTORE2 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
4 | SMSTORE3 | TYPE2_OCC_SCH | SMSTORE3 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
5 | SMSTORE4 | TYPE2_OCC_SCH | SMSTORE4 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
6 | LGSTORE2 | TYPE3_OCC_SCH | LGSTORE2 | 348.39 | 30.0 | 30.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 30 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
7 | SMSTORE5 | TYPE3_OCC_SCH | SMSTORE5 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
8 | SMSTORE6 | TYPE3_OCC_SCH | SMSTORE6 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
9 | SMSTORE7 | TYPE3_OCC_SCH | SMSTORE7 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
10 | SMSTORE8 | TYPE3_OCC_SCH | SMSTORE8 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | LGSTORE1_LIGHTS | TYPE1_LIGHT_SCH | LGSTORE1 | 348.39 | 30.0 | 6383.296 | 18.322 | 212.804 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 6383.296 |
2 | LGSTORE1_LIGHTS_ALLOWANCE | TYPE1_LIGHT_SCH | LGSTORE1 | 348.39 | 30.0 | 3656.252 | 10.495 | 121.891 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3656.252 |
3 | SMSTORE1_LIGHTS | TYPE1_LIGHT_SCH | SMSTORE1 | 174.19 | 15.0 | 3191.648 | 18.322 | 212.805 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3191.648 |
4 | SMSTORE1_LIGHTS_ALLOWANCE | TYPE1_LIGHT_SCH | SMSTORE1 | 174.19 | 15.0 | 1828.126 | 10.495 | 121.891 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1828.126 |
5 | SMSTORE2_LIGHTS | TYPE2_LIGHT_SCH | SMSTORE2 | 174.19 | 15.0 | 3191.648 | 18.322 | 212.805 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3191.648 |
6 | SMSTORE2_LIGHTS_ALLOWANCE | TYPE2_LIGHT_SCH | SMSTORE2 | 174.19 | 15.0 | 750.000 | 4.306 | 50.007 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 750.000 |
7 | SMSTORE3_LIGHTS | TYPE2_LIGHT_SCH | SMSTORE3 | 174.19 | 15.0 | 3191.648 | 18.322 | 212.805 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3191.648 |
8 | SMSTORE3_LIGHTS_ALLOWANCE | TYPE2_LIGHT_SCH | SMSTORE3 | 174.19 | 15.0 | 750.000 | 4.306 | 50.007 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 750.000 |
9 | SMSTORE4_LIGHTS | TYPE2_LIGHT_SCH | SMSTORE4 | 174.19 | 15.0 | 3191.648 | 18.322 | 212.805 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3191.648 |
10 | SMSTORE4_LIGHTS_ALLOWANCE | TYPE2_LIGHT_SCH | SMSTORE4 | 174.19 | 15.0 | 750.000 | 4.306 | 50.007 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 750.000 |
11 | LGSTORE2_LIGHTS | TYPE3_LIGHT_SCH | LGSTORE2 | 348.39 | 30.0 | 6383.296 | 18.322 | 212.804 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 6383.296 |
12 | LGSTORE2_LIGHTS_ALLOWANCE | TYPE3_LIGHT_SCH | LGSTORE2 | 348.39 | 30.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
13 | SMSTORE5_LIGHTS | TYPE3_LIGHT_SCH | SMSTORE5 | 174.19 | 15.0 | 3191.648 | 18.322 | 212.805 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3191.648 |
14 | SMSTORE5_LIGHTS_ALLOWANCE | TYPE3_LIGHT_SCH | SMSTORE5 | 174.19 | 15.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
15 | SMSTORE6_LIGHTS | TYPE3_LIGHT_SCH | SMSTORE6 | 174.19 | 15.0 | 3191.648 | 18.322 | 212.805 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3191.648 |
16 | SMSTORE6_LIGHTS_ALLOWANCE | TYPE3_LIGHT_SCH | SMSTORE6 | 174.19 | 15.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
17 | SMSTORE7_LIGHTS | TYPE3_LIGHT_SCH | SMSTORE7 | 174.19 | 15.0 | 3191.648 | 18.322 | 212.805 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3191.648 |
18 | SMSTORE7_LIGHTS_ALLOWANCE | TYPE3_LIGHT_SCH | SMSTORE7 | 174.19 | 15.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
19 | SMSTORE8_LIGHTS | TYPE3_LIGHT_SCH | SMSTORE8 | 174.19 | 15.0 | 3191.648 | 18.322 | 212.805 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3191.648 |
20 | SMSTORE8_LIGHTS_ALLOWANCE | TYPE3_LIGHT_SCH | SMSTORE8 | 174.19 | 15.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | LGSTORE1_MISCPLUG_EQUIP | TYPE1_EQUIP_SCH | LGSTORE1 | 348.39 | 30.0 | 1498.062 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1498.062 |
2 | SMSTORE1_MISCPLUG_EQUIP | TYPE1_EQUIP_SCH | SMSTORE1 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
3 | SMSTORE2_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE2 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
4 | SMSTORE3_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE3 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
5 | SMSTORE4_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE4 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
6 | LGSTORE2_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | LGSTORE2 | 348.39 | 30.0 | 1498.062 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1498.062 |
7 | SMSTORE5_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE5 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
8 | SMSTORE6_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE6 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
9 | SMSTORE7_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE7 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
10 | SMSTORE8_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE8 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.975 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.3762 | 0.900 | 0.900 | 0.770 | 0.700 | Rough |
5 | NONRES_EXT_WALL | 20 | 4 | 7 | 0.167 | 0.7871 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
6 | LGSTORE1_FLOOR_FFACTOR | 30 | 2 | 7 | 0.167 | 0.1995 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
7 | SMSTORE1_FLOOR_FFACTOR | 31 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
8 | SMSTORE2_FLOOR_FFACTOR | 32 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | SMSTORE3_FLOOR_FFACTOR | 33 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
10 | SMSTORE4_FLOOR_FFACTOR | 34 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
11 | LGSTORE2_FLOOR_FFACTOR | 35 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | SMSTORE5_FLOOR_FFACTOR | 36 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | SMSTORE6_FLOOR_FFACTOR | 37 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | SMSTORE7_FLOOR_FFACTOR | 38 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | SMSTORE8_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.2888 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2516 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
6 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.599 |
7 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
8 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
9 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
10 | NONRES_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.037 |
11 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
12 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.937 |
13 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
14 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
15 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
16 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
17 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
18 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
19 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
20 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
21 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
22 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
23 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
24 | ~FC_Insulation_7 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_8 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_9 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
30 | ~FC_Insulation_10 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.386 |
31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.9747885 | 3.9747885 | 3.9747885 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
14 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
15 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
16 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
17 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
18 | 3 | -0.61039648E-06 | 0.16815647E-08 | -0.37447326E-05 | 0.10149002E-16 |
19 | 2 | 0.76989337 | 0.22941655E-02 | 1.0458372 | -0.71793422E-06 |
20 | 1 | -21.843031 | 0.15409339 | -6.3407615 | 0.20050303 |
21 | 0 | 21.373924 | 0.14439780 | 5.5957134 | |
22 | 7 | -0.29735092E-12 | 0.24575595E-14 | -0.94456721E-13 | 0.15324278E-15 |
23 | 6 | 0.28546880E-07 | 0.22114619E-09 | 0.65405332E-08 | -0.13451374E-12 |
24 | 5 | -0.18947583E-03 | 0.18937623E-05 | -0.97466953E-04 | 0.64660656E-08 |
25 | 4 | 0.29140875 | 0.92215111E-03 | 0.99417931E-01 | -0.33466744E-04 |
26 | 3 | -7.2517161 | 0.28579858E-01 | -2.3345767 | 0.28937395E-01 |
27 | 2 | 40.822959 | 0.10163225 | 15.247323 | -0.33280368 |
28 | 1 | -80.508872 | 0.45869584E-01 | -29.125752 | 1.0778326 |
29 | 0 | 46.824339 | 0.92288667E-03 | 16.291614 | |
30 | 7 | -0.21163652E-08 | -0.68723841E-15 | 0.43910983E-14 | -0.57684426E-16 |
31 | 6 | 0.56109385E-05 | 0.38186281E-08 | 0.31898696E-02 | -0.26759299E-04 |
32 | 5 | -0.40164657E-03 | 0.22608617E-05 | -0.22372456 | 0.19561502E-02 |
33 | 4 | 0.92272104E-02 | 0.10289840E-03 | 4.8295456 | -0.45264980E-01 |
34 | 3 | -0.80993241E-01 | 0.81813938E-03 | -38.021416 | 0.39865375 |
35 | 2 | 0.28754352 | 0.13608947E-02 | 116.48395 | -1.4179393 |
36 | 1 | -0.41499682 | 0.41453381E-03 | -143.90731 | 2.0490399 |
37 | 0 | 0.20232414 | 0.10048102E-04 | 60.838472 | |
38 | 7 | -0.37862368E-08 | -0.38757603E-14 | 0.11479940E-14 | -0.41635801E-16 |
39 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
40 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
41 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
42 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
43 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
44 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
45 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
46 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479937E-14 | -0.41635796E-16 |
47 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
48 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
49 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
50 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
51 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
52 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
53 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
54 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479940E-14 | -0.41635801E-16 |
55 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
56 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
57 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
58 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
59 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
60 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
61 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
62 | 7 | -0.37862368E-08 | -0.38757603E-14 | 0.11479940E-14 | -0.41635801E-16 |
63 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
64 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
65 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
66 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
67 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
68 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
69 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
70 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479937E-14 | -0.41635796E-16 |
71 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
72 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
73 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
74 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
75 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
76 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
77 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
78 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479937E-14 | -0.41635796E-16 |
79 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
80 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
81 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
82 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
83 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
84 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
85 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
86 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479940E-14 | -0.41635801E-16 |
87 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
88 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
89 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
90 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
91 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
92 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
93 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
94 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479936E-14 | -0.41635794E-16 |
95 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
96 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
97 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
98 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
99 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
100 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
101 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
102 | 7 | -0.14484255E-08 | -0.22640907E-15 | 0.11860658E-13 | -0.17473455E-15 |
103 | 6 | 0.80640390E-05 | 0.55493782E-08 | 0.31828288E-02 | -0.26700235E-04 |
104 | 5 | -0.58275339E-03 | 0.32892043E-05 | -0.22332434 | 0.19526176E-02 |
105 | 4 | 0.13421983E-01 | 0.14977251E-03 | 4.8228790 | -0.45200897E-01 |
106 | 3 | -0.11791368 | 0.11914425E-02 | -37.983753 | 0.39823745 |
107 | 2 | 0.41875064 | 0.19825898E-02 | 116.41064 | -1.4169588 |
108 | 1 | -0.60444169 | 0.60433957E-03 | -143.86415 | 2.0483306 |
109 | 0 | 0.29470347 | 0.14596444E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_1.2_SHGC_0.25 | 29 | 1 | VerySmooth | 5.832 | 0.251 | 0.110 | 0.250 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.10958 | 0.41417 | 0.41417 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.39147 | 1.00000 | No |
Calculation Method | Value {days} | Allowable Number Figures in Shadow Overlap {} | Polygon Clipping Algorithm | Sky Diffuse Modeling Algorithm | External Shading Calculation Method | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | AverageOverDaysInFrequency | 30 | 15000 | SutherlandHodgman | SimpleSkyDiffuseModeling | InternalCalculation | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | GAS TANK1 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
2 | WaterHeater:Mixed | GAS TANK2 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
3 | WaterHeater:Mixed | GAS TANK3 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
4 | WaterHeater:Mixed | GAS TANK4 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
5 | WaterHeater:Mixed | GAS TANK5 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
6 | WaterHeater:Mixed | GAS TANK6 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
7 | WaterHeater:Mixed | GAS TANK7 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | LGSTORE1_WALL_2 | 0 | 118.41 | 56.08 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 4 | No | No |
2 | LGSTORE1_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 4 | No | No |
3 | LGSTORE1_WALL_3_DOOR_1 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 0 | No | No |
4 | LGSTORE1_WALL_3_DOOR_2 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 0 | No | No |
5 | LGSTORE1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 0 | No | No |
6 | LGSTORE1_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 4 | No | No |
7 | LGSTORE1_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 1 | No | No |
8 | LGSTORE1_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 1 | No | No |
9 | LGSTORE1_WALL_1_WINDOW_3 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 1 | No | No |
10 | LGSTORE1_WALL_1_WINDOW_4 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 1 | No | No |
11 | LGSTORE1_WALL_1_DOOR_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 1 | No | No |
12 | LGSTORE1_WALL_1_DOOR_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 1 | No | No |
13 | LGSTORE1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 0 | No | No |
14 | LGSTORE1_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 0 | No | No |
15 | LGSTORE1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 0 | No | No |
16 | SMSTORE1_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
17 | SMSTORE1_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
18 | SMSTORE1_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
19 | SMSTORE1_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
20 | SMSTORE1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
21 | SMSTORE1_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
22 | SMSTORE1_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
23 | SMSTORE1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
24 | SMSTORE1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
25 | SMSTORE1_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
26 | SMSTORE1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
27 | SMSTORE2_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
28 | SMSTORE2_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
29 | SMSTORE2_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
30 | SMSTORE2_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
31 | SMSTORE2_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
32 | SMSTORE2_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
33 | SMSTORE2_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
34 | SMSTORE2_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
35 | SMSTORE2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
36 | SMSTORE2_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
37 | SMSTORE2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
38 | SMSTORE3_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
39 | SMSTORE3_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
40 | SMSTORE3_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
41 | SMSTORE3_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
42 | SMSTORE3_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
43 | SMSTORE3_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
44 | SMSTORE3_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
45 | SMSTORE3_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
46 | SMSTORE3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
47 | SMSTORE3_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
48 | SMSTORE3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
49 | SMSTORE4_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
50 | SMSTORE4_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
51 | SMSTORE4_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
52 | SMSTORE4_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
53 | SMSTORE4_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
54 | SMSTORE4_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 3 | No | No |
55 | SMSTORE4_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
56 | SMSTORE4_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
57 | SMSTORE4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
58 | SMSTORE4_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
59 | SMSTORE4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
60 | LGSTORE2_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
61 | LGSTORE2_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 4 | No | No |
62 | LGSTORE2_WALL_3_DOOR_1 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
63 | LGSTORE2_WALL_3_DOOR_2 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
64 | LGSTORE2_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
65 | LGSTORE2_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 4 | No | No |
66 | LGSTORE2_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
67 | LGSTORE2_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
68 | LGSTORE2_WALL_1_WINDOW_3 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
69 | LGSTORE2_WALL_1_WINDOW_4 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
70 | LGSTORE2_WALL_1_DOOR_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
71 | LGSTORE2_WALL_1_DOOR_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
72 | LGSTORE2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
73 | LGSTORE2_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
74 | LGSTORE2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
75 | SMSTORE5_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
76 | SMSTORE5_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
77 | SMSTORE5_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
78 | SMSTORE5_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
79 | SMSTORE5_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
80 | SMSTORE5_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
81 | SMSTORE5_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
82 | SMSTORE5_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
83 | SMSTORE5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
84 | SMSTORE5_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
85 | SMSTORE5_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
86 | SMSTORE6_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
87 | SMSTORE6_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
88 | SMSTORE6_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
89 | SMSTORE6_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
90 | SMSTORE6_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
91 | SMSTORE6_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
92 | SMSTORE6_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
93 | SMSTORE6_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
94 | SMSTORE6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
95 | SMSTORE6_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
96 | SMSTORE6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
97 | SMSTORE7_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
98 | SMSTORE7_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
99 | SMSTORE7_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
100 | SMSTORE7_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
101 | SMSTORE7_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
102 | SMSTORE7_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 3 | No | No |
103 | SMSTORE7_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
104 | SMSTORE7_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
105 | SMSTORE7_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
106 | SMSTORE7_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
107 | SMSTORE7_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
108 | SMSTORE8_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 4 | No | No |
109 | SMSTORE8_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 1 | No | No |
110 | SMSTORE8_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 1 | No | No |
111 | SMSTORE8_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 1 | No | No |
112 | SMSTORE8_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
113 | SMSTORE8_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 3 | No | No |
114 | SMSTORE8_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
115 | SMSTORE8_WALL_4 | 0 | 118.41 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 3 | No | No |
116 | SMSTORE8_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
117 | SMSTORE8_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
118 | SMSTORE8_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | LGSTORE1_INFILTRATION | TYPE1_INFIL_SCH | LGSTORE1 | 348.39 | 30.0 | 0.286 | 8.224E-004 | 4.530E-004 | 0.571 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | LGSTORE1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | LGSTORE1 | 348.39 | 30.0 | 0.389 | 1.116E-003 | 6.149E-004 | 0.776 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | SMSTORE1_INFILTRATION | TYPE1_INFIL_SCH | SMSTORE1 | 174.19 | 15.0 | 8.210E-002 | 4.713E-004 | 3.194E-004 | 0.327 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | SMSTORE1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE1 | 174.19 | 15.0 | 0.222 | 1.276E-003 | 8.648E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
5 | SMSTORE2_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE2 | 174.19 | 15.0 | 8.210E-002 | 4.713E-004 | 3.194E-004 | 0.327 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | SMSTORE2_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE2 | 174.19 | 15.0 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
7 | SMSTORE3_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE3 | 174.19 | 15.0 | 8.210E-002 | 4.713E-004 | 3.194E-004 | 0.327 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | SMSTORE3_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE3 | 174.19 | 15.0 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | SMSTORE4_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE4 | 174.19 | 15.0 | 8.210E-002 | 4.713E-004 | 3.194E-004 | 0.327 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | SMSTORE4_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE4 | 174.19 | 15.0 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
11 | LGSTORE2_INFILTRATION | TYPE3_INFIL_SCH | LGSTORE2 | 348.39 | 30.0 | 0.164 | 4.713E-004 | 3.194E-004 | 0.327 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | LGSTORE2_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | LGSTORE2 | 348.39 | 30.0 | 0.389 | 1.116E-003 | 7.565E-004 | 0.776 | 1.000 | 0.000 | 0.000 | 0.000 |
13 | SMSTORE5_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE5 | 174.19 | 15.0 | 8.210E-002 | 4.713E-004 | 3.194E-004 | 0.327 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | SMSTORE5_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE5 | 174.19 | 15.0 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
15 | SMSTORE6_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE6 | 174.19 | 15.0 | 8.210E-002 | 4.713E-004 | 3.194E-004 | 0.327 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | SMSTORE6_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE6 | 174.19 | 15.0 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
17 | SMSTORE7_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE7 | 174.19 | 15.0 | 8.210E-002 | 4.713E-004 | 3.194E-004 | 0.327 | 0.000 | 0.000 | 0.224 | 0.000 |
18 | SMSTORE7_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE7 | 174.19 | 15.0 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
19 | SMSTORE8_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE8 | 174.19 | 15.0 | 0.204 | 1.172E-003 | 5.440E-004 | 0.815 | 0.000 | 0.000 | 0.224 | 0.000 |
20 | SMSTORE8_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE8 | 174.19 | 15.0 | 0.222 | 1.276E-003 | 5.921E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | LGSTORE1 | Mixing/Well-Stirred |
2 | SMSTORE1 | Mixing/Well-Stirred |
3 | SMSTORE2 | Mixing/Well-Stirred |
4 | SMSTORE3 | Mixing/Well-Stirred |
5 | SMSTORE4 | Mixing/Well-Stirred |
6 | LGSTORE2 | Mixing/Well-Stirred |
7 | SMSTORE5 | Mixing/Well-Stirred |
8 | SMSTORE6 | Mixing/Well-Stirred |
9 | SMSTORE7 | Mixing/Well-Stirred |
10 | SMSTORE8 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone LGSTORE1 | 1.2000 |
3 | Zone SMSTORE1 | 1.2000 |
4 | Zone SMSTORE2 | 1.2000 |
5 | Zone SMSTORE3 | 1.2000 |
6 | Zone SMSTORE4 | 1.2000 |
7 | Zone LGSTORE2 | 1.2000 |
8 | Zone SMSTORE5 | 1.2000 |
9 | Zone SMSTORE6 | 1.2000 |
10 | Zone SMSTORE7 | 1.2000 |
11 | Zone SMSTORE8 | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone LGSTORE1 | 1.2000 |
3 | Zone SMSTORE1 | 1.2000 |
4 | Zone SMSTORE2 | 1.2000 |
5 | Zone SMSTORE3 | 1.2000 |
6 | Zone SMSTORE4 | 1.2000 |
7 | Zone LGSTORE2 | 1.2000 |
8 | Zone SMSTORE5 | 1.2000 |
9 | Zone SMSTORE6 | 1.2000 |
10 | Zone SMSTORE7 | 1.2000 |
11 | Zone SMSTORE8 | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | LGSTORE1 | Cooling | 35598.57260 | 42718.28712 | 2.68736 | 3.22483 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:30:00 | 42.00000 | 9.11023E-003 | 348.38640 | 29.99610 | 0.53091 | 0.00000 |
2 | LGSTORE1 | Heating | 15883.85648 | 19060.62778 | 0.70248 | 0.84298 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 6.30000 | 6.07234E-003 | 348.38640 | 29.99610 | 0.53091 | 0.00000 |
3 | SMSTORE1 | Cooling | 18013.80768 | 21616.56922 | 1.35988 | 1.63186 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | 42.00000 | 9.11023E-003 | 174.19320 | 14.99800 | 0.26545 | 0.00000 |
4 | SMSTORE1 | Heating | 8009.89197 | 9611.87037 | 0.35424 | 0.42509 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 6.30000 | 6.07234E-003 | 174.19320 | 14.99800 | 0.26545 | 0.00000 |
5 | SMSTORE2 | Cooling | 17257.94770 | 20709.53725 | 1.30282 | 1.56338 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:50:00 | 41.91917 | 9.11022E-003 | 174.19320 | 14.99800 | 0.26545 | 0.00000 |
6 | SMSTORE2 | Heating | 8128.83861 | 9754.60633 | 0.35950 | 0.43141 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 6.30000 | 6.07234E-003 | 174.19320 | 14.99800 | 0.26545 | 0.00000 |
7 | SMSTORE3 | Cooling | 17222.18832 | 20666.62599 | 1.30012 | 1.56014 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:50:00 | 41.91917 | 9.11022E-003 | 174.19320 | 14.99800 | 0.26545 | 0.00000 |
8 | SMSTORE3 | Heating | 8212.32103 | 9854.78524 | 0.36320 | 0.43584 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 6.30000 | 6.07234E-003 | 174.19320 | 14.99800 | 0.26545 | 0.00000 |
9 | SMSTORE4 | Cooling | 17194.88413 | 20633.86096 | 1.29806 | 1.55767 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:50:00 | 41.91917 | 9.11022E-003 | 174.19320 | 14.99800 | 0.26545 | 0.00000 |
10 | SMSTORE4 | Heating | 8369.31319 | 10043.17583 | 0.37014 | 0.44417 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 6.30000 | 6.07234E-003 | 174.19320 | 14.99800 | 0.26545 | 0.00000 |
11 | LGSTORE2 | Cooling | 31725.37916 | 38070.45499 | 2.39496 | 2.87396 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:50:00 | 41.91917 | 9.11022E-003 | 348.38640 | 29.99610 | 0.53091 | 0.00000 |
12 | LGSTORE2 | Heating | 15977.53399 | 19173.04079 | 0.70662 | 0.84795 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 6.30000 | 6.07234E-003 | 348.38640 | 29.99610 | 0.53091 | 0.00000 |
13 | SMSTORE5 | Cooling | 16720.01634 | 20064.01960 | 1.26221 | 1.51465 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:50:00 | 41.91917 | 9.11022E-003 | 174.19320 | 14.99800 | 0.26545 | 0.00000 |
14 | SMSTORE5 | Heating | 8620.11329 | 10344.13595 | 0.38123 | 0.45748 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 6.30000 | 6.07234E-003 | 174.19320 | 14.99800 | 0.26545 | 0.00000 |
15 | SMSTORE6 | Cooling | 16651.14242 | 19981.37090 | 1.25701 | 1.50841 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:50:00 | 41.91917 | 9.11022E-003 | 174.19320 | 14.99800 | 0.26545 | 0.00000 |
16 | SMSTORE6 | Heating | 8612.46269 | 10334.95523 | 0.38089 | 0.45707 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 6.30000 | 6.07234E-003 | 174.19320 | 14.99800 | 0.26545 | 0.00000 |
17 | SMSTORE7 | Cooling | 16689.72423 | 20027.66908 | 1.25992 | 1.51190 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:40:00 | 41.83833 | 9.11022E-003 | 174.19320 | 14.99800 | 0.26545 | 0.00000 |
18 | SMSTORE7 | Heating | 8816.42914 | 10579.71497 | 0.38991 | 0.46790 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 6.30000 | 6.07234E-003 | 174.19320 | 14.99800 | 0.26545 | 0.00000 |
19 | SMSTORE8 | Cooling | 18492.51393 | 22191.01672 | 1.39595 | 1.67514 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:00:00 | 41.51500 | 9.11022E-003 | 174.19320 | 14.99800 | 0.26545 | 0.00000 |
20 | SMSTORE8 | Heating | 9963.24493 | 11955.89391 | 0.44063 | 0.52876 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 6.30000 | 6.07234E-003 | 174.19320 | 14.99800 | 0.26545 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC_1:1 | Cooling | Sensible | 53514.98 | 3.22483 | 3.22483 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
2 | PSZ-AC_1:1 | Heating | Sensible | 28056.36 | 0.84298 | 0.84298 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
3 | PSZ-AC_2:2 | Cooling | Sensible | 27011.65 | 1.63186 | 1.63186 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
4 | PSZ-AC_2:2 | Heating | Sensible | 14108.52 | 0.42509 | 0.42509 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
5 | PSZ-AC_3:3 | Cooling | Sensible | 26114.82 | 1.56338 | 1.56338 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
6 | PSZ-AC_3:3 | Heating | Sensible | 14249.17 | 0.43141 | 0.43141 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
7 | PSZ-AC_4:4 | Cooling | Sensible | 26072.02 | 1.56014 | 1.56014 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
8 | PSZ-AC_4:4 | Heating | Sensible | 14347.89 | 0.43584 | 0.43584 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
9 | PSZ-AC_5:5 | Cooling | Sensible | 26039.45 | 1.55767 | 1.55767 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
10 | PSZ-AC_5:5 | Heating | Sensible | 14533.54 | 0.44417 | 0.44417 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
11 | PSZ-AC_6:6 | Cooling | Sensible | 48916.21 | 2.87396 | 2.87396 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
12 | PSZ-AC_6:6 | Heating | Sensible | 28167.14 | 0.84795 | 0.84795 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
13 | PSZ-AC_7:7 | Cooling | Sensible | 25472.92 | 1.51465 | 1.51465 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
14 | PSZ-AC_7:7 | Heating | Sensible | 14830.12 | 0.45748 | 0.45748 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
15 | PSZ-AC_8:8 | Cooling | Sensible | 25391.26 | 1.50841 | 1.50841 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
16 | PSZ-AC_8:8 | Heating | Sensible | 14821.07 | 0.45707 | 0.45707 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
17 | PSZ-AC_9:9 | Cooling | Sensible | 25436.19 | 1.51190 | 1.51190 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
18 | PSZ-AC_9:9 | Heating | Sensible | 15062.26 | 0.46790 | 0.46790 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
19 | PSZ-AC_10:10 | Cooling | Sensible | 27469.19 | 1.67514 | 1.67514 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
20 | PSZ-AC_10:10 | Heating | Sensible | 16418.39 | 0.52876 | 0.52876 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:Uncontrolled | LGSTORE1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 3.22483 |
2 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.63186 |
3 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE2 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.56338 |
4 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.56014 |
5 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE4 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.55767 |
6 | AirTerminal:SingleDuct:Uncontrolled | LGSTORE2 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.87396 |
7 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE5 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.51465 |
8 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.50841 |
9 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE7 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.51190 |
10 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE8 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.67514 |
11 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 3.22483 |
12 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 3.22483 |
13 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 3.22483 |
14 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 3.22483 |
15 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 3.22483 |
16 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Main Design Air Flow Rate [m3/s] | 3.22483 |
17 | AirLoopHVAC | PSZ-AC_1:1 | User Heating Air Flow Ratio [] | 1.00000 |
18 | AirLoopHVAC | PSZ-AC_1:1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
19 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.63186 |
20 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.63186 |
21 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.63186 |
22 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.63186 |
23 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.63186 |
24 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Main Design Air Flow Rate [m3/s] | 1.63186 |
25 | AirLoopHVAC | PSZ-AC_2:2 | User Heating Air Flow Ratio [] | 1.00000 |
26 | AirLoopHVAC | PSZ-AC_2:2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
27 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.56338 |
28 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.56338 |
29 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.56338 |
30 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.56338 |
31 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.56338 |
32 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Main Design Air Flow Rate [m3/s] | 1.56338 |
33 | AirLoopHVAC | PSZ-AC_3:3 | User Heating Air Flow Ratio [] | 1.00000 |
34 | AirLoopHVAC | PSZ-AC_3:3 | Calculated Heating Air Flow Ratio [] | 1.00000 |
35 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.56014 |
36 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.56014 |
37 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.56014 |
38 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.56014 |
39 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.56014 |
40 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Main Design Air Flow Rate [m3/s] | 1.56014 |
41 | AirLoopHVAC | PSZ-AC_4:4 | User Heating Air Flow Ratio [] | 1.00000 |
42 | AirLoopHVAC | PSZ-AC_4:4 | Calculated Heating Air Flow Ratio [] | 1.00000 |
43 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.55767 |
44 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.55767 |
45 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.55767 |
46 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.55767 |
47 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.55767 |
48 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Main Design Air Flow Rate [m3/s] | 1.55767 |
49 | AirLoopHVAC | PSZ-AC_5:5 | User Heating Air Flow Ratio [] | 1.00000 |
50 | AirLoopHVAC | PSZ-AC_5:5 | Calculated Heating Air Flow Ratio [] | 1.00000 |
51 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.87396 |
52 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.87396 |
53 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.87396 |
54 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Heating Design Air Flow Rate [m3/s] | 2.87396 |
55 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.87396 |
56 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Main Design Air Flow Rate [m3/s] | 2.87396 |
57 | AirLoopHVAC | PSZ-AC_6:6 | User Heating Air Flow Ratio [] | 1.00000 |
58 | AirLoopHVAC | PSZ-AC_6:6 | Calculated Heating Air Flow Ratio [] | 1.00000 |
59 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.51465 |
60 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.51465 |
61 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.51465 |
62 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.51465 |
63 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.51465 |
64 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Main Design Air Flow Rate [m3/s] | 1.51465 |
65 | AirLoopHVAC | PSZ-AC_7:7 | User Heating Air Flow Ratio [] | 1.00000 |
66 | AirLoopHVAC | PSZ-AC_7:7 | Calculated Heating Air Flow Ratio [] | 1.00000 |
67 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.50841 |
68 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.50841 |
69 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.50841 |
70 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.50841 |
71 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.50841 |
72 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Main Design Air Flow Rate [m3/s] | 1.50841 |
73 | AirLoopHVAC | PSZ-AC_8:8 | User Heating Air Flow Ratio [] | 1.00000 |
74 | AirLoopHVAC | PSZ-AC_8:8 | Calculated Heating Air Flow Ratio [] | 1.00000 |
75 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.51190 |
76 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.51190 |
77 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.51190 |
78 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.51190 |
79 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.51190 |
80 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Main Design Air Flow Rate [m3/s] | 1.51190 |
81 | AirLoopHVAC | PSZ-AC_9:9 | User Heating Air Flow Ratio [] | 1.00000 |
82 | AirLoopHVAC | PSZ-AC_9:9 | Calculated Heating Air Flow Ratio [] | 1.00000 |
83 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.67514 |
84 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.67514 |
85 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.67514 |
86 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.67514 |
87 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.67514 |
88 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Main Design Air Flow Rate [m3/s] | 1.67514 |
89 | AirLoopHVAC | PSZ-AC_10:10 | User Heating Air Flow Ratio [] | 1.00000 |
90 | AirLoopHVAC | PSZ-AC_10:10 | Calculated Heating Air Flow Ratio [] | 1.00000 |
91 | AirLoopHVAC | PSZ-AC_1:1 | Design Supply Air Flow Rate [m3/s] | 3.22483 |
92 | AirLoopHVAC | PSZ-AC_2:2 | Design Supply Air Flow Rate [m3/s] | 1.63186 |
93 | AirLoopHVAC | PSZ-AC_3:3 | Design Supply Air Flow Rate [m3/s] | 1.56338 |
94 | AirLoopHVAC | PSZ-AC_4:4 | Design Supply Air Flow Rate [m3/s] | 1.56014 |
95 | AirLoopHVAC | PSZ-AC_5:5 | Design Supply Air Flow Rate [m3/s] | 1.55767 |
96 | AirLoopHVAC | PSZ-AC_6:6 | Design Supply Air Flow Rate [m3/s] | 2.87396 |
97 | AirLoopHVAC | PSZ-AC_7:7 | Design Supply Air Flow Rate [m3/s] | 1.51465 |
98 | AirLoopHVAC | PSZ-AC_8:8 | Design Supply Air Flow Rate [m3/s] | 1.50841 |
99 | AirLoopHVAC | PSZ-AC_9:9 | Design Supply Air Flow Rate [m3/s] | 1.51190 |
100 | AirLoopHVAC | PSZ-AC_10:10 | Design Supply Air Flow Rate [m3/s] | 1.67514 |
101 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 3.22483 |
102 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.53091 |
103 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 3.22483 |
104 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 3.22483 |
105 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 3.22483 |
106 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 3.22483 |
107 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 3.22483 |
108 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.61242 |
109 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 3.22483 |
110 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 53382.38702 |
111 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 66560.00000 |
112 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 33280.00000 |
113 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 66560.00000 |
114 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.72587 |
115 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.72587 |
116 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.72587 |
117 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.72587 |
118 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 66560.00000 |
119 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 81128.24084 |
120 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
121 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
122 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 3.22483 |
123 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 3529.59430 |
124 | Coil:Heating:Fuel | PSZ-AC_1:1_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 81128.24084 |
125 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.63186 |
126 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.26545 |
127 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.63186 |
128 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.63186 |
129 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.63186 |
130 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.63186 |
131 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.63186 |
132 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.81593 |
133 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.63186 |
134 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 27013.07731 |
135 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 33607.54000 |
136 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 16803.77000 |
137 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 33607.54000 |
138 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.72651 |
139 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.72651 |
140 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.72651 |
141 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.72651 |
142 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 33607.54000 |
143 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 40997.43787 |
144 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
145 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
146 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.63186 |
147 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1786.07433 |
148 | Coil:Heating:Fuel | PSZ-AC_2:2_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 40997.43787 |
149 | Controller:OutdoorAir | PSZ-AC_3:3_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.56338 |
150 | Controller:OutdoorAir | PSZ-AC_3:3_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.26545 |
151 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.56338 |
152 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.56338 |
153 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.56338 |
154 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.56338 |
155 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.56338 |
156 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.78169 |
157 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.56338 |
158 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 26167.31778 |
159 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 32386.23000 |
160 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 16193.11500 |
161 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 32386.23000 |
162 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.72479 |
163 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.72479 |
164 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.72479 |
165 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.72479 |
166 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 32386.23000 |
167 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 39471.74027 |
168 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
169 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
170 | Fan:SystemModel | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.56338 |
171 | Fan:SystemModel | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1711.13009 |
172 | Coil:Heating:Fuel | PSZ-AC_3:3_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 39471.74027 |
173 | Controller:OutdoorAir | PSZ-AC_4:4_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.56014 |
174 | Controller:OutdoorAir | PSZ-AC_4:4_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.26545 |
175 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.56014 |
176 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.56014 |
177 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.56014 |
178 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.56014 |
179 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.56014 |
180 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.78007 |
181 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.56014 |
182 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 26130.07037 |
183 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 32328.52000 |
184 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 16164.26000 |
185 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 32328.52000 |
186 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.72470 |
187 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.72470 |
188 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.72470 |
189 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.72470 |
190 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 32328.52000 |
191 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 39399.56286 |
192 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
193 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
194 | Fan:SystemModel | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.56014 |
195 | Fan:SystemModel | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1707.58455 |
196 | Coil:Heating:Fuel | PSZ-AC_4:4_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 39399.56286 |
197 | Controller:OutdoorAir | PSZ-AC_5:5_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.55767 |
198 | Controller:OutdoorAir | PSZ-AC_5:5_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.26545 |
199 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.55767 |
200 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.55767 |
201 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.55767 |
202 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.55767 |
203 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.55767 |
204 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.77884 |
205 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.55767 |
206 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 26101.64501 |
207 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 32284.42000 |
208 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 16142.21000 |
209 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 32284.42000 |
210 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.72464 |
211 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.72464 |
212 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.72464 |
213 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.72464 |
214 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 32284.42000 |
215 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 39344.44714 |
216 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
217 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
218 | Fan:SystemModel | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.55767 |
219 | Fan:SystemModel | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1704.87717 |
220 | Coil:Heating:Fuel | PSZ-AC_5:5_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 39344.44714 |
221 | Controller:OutdoorAir | PSZ-AC_6:6_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.87396 |
222 | Controller:OutdoorAir | PSZ-AC_6:6_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.53091 |
223 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.87396 |
224 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.87396 |
225 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.87396 |
226 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 2.87396 |
227 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.87396 |
228 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.43698 |
229 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 2.87396 |
230 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 49201.57363 |
231 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 60301.45000 |
232 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 30150.72500 |
233 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 60301.45000 |
234 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.72106 |
235 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.72106 |
236 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.72106 |
237 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.72106 |
238 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 60301.45000 |
239 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 73310.12283 |
240 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
241 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
242 | Fan:SystemModel | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.87396 |
243 | Fan:SystemModel | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 3145.56003 |
244 | Coil:Heating:Fuel | PSZ-AC_6:6_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 73310.12283 |
245 | Controller:OutdoorAir | PSZ-AC_7:7_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.51465 |
246 | Controller:OutdoorAir | PSZ-AC_7:7_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.26545 |
247 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.51465 |
248 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.51465 |
249 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.51465 |
250 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.51465 |
251 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.51465 |
252 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.75733 |
253 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.51465 |
254 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 25605.48984 |
255 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 31517.54000 |
256 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 15758.77000 |
257 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 31517.54000 |
258 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.72348 |
259 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.72348 |
260 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.72348 |
261 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.72348 |
262 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 31517.54000 |
263 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 38385.92332 |
264 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
265 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
266 | Fan:SystemModel | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.51465 |
267 | Fan:SystemModel | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1657.79369 |
268 | Coil:Heating:Fuel | PSZ-AC_7:7_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 38385.92332 |
269 | Controller:OutdoorAir | PSZ-AC_8:8_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.50841 |
270 | Controller:OutdoorAir | PSZ-AC_8:8_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.26545 |
271 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.50841 |
272 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.50841 |
273 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.50841 |
274 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.50841 |
275 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.50841 |
276 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.75421 |
277 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.50841 |
278 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 25533.16111 |
279 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 31406.18000 |
280 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 15703.09000 |
281 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 31406.18000 |
282 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.72330 |
283 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.72331 |
284 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.72331 |
285 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.72331 |
286 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 31406.18000 |
287 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 38246.90136 |
288 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
289 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
290 | Fan:SystemModel | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.50841 |
291 | Fan:SystemModel | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1650.96484 |
292 | Coil:Heating:Fuel | PSZ-AC_8:8_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 38246.90136 |
293 | Controller:OutdoorAir | PSZ-AC_9:9_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.51190 |
294 | Controller:OutdoorAir | PSZ-AC_9:9_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.26545 |
295 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.51190 |
296 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.51190 |
297 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.51190 |
298 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.51190 |
299 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.51190 |
300 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.75595 |
301 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.51190 |
302 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 25573.94364 |
303 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 31468.69000 |
304 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 15734.34500 |
305 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 31468.69000 |
306 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.72340 |
307 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.72340 |
308 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.72340 |
309 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.72340 |
310 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 31468.69000 |
311 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 38324.72705 |
312 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
313 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
314 | Fan:SystemModel | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.51190 |
315 | Fan:SystemModel | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1654.78750 |
316 | Coil:Heating:Fuel | PSZ-AC_9:9_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 38324.72705 |
317 | Controller:OutdoorAir | PSZ-AC_10:10_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.67514 |
318 | Controller:OutdoorAir | PSZ-AC_10:10_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.26545 |
319 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.67514 |
320 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.67514 |
321 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.67514 |
322 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.67514 |
323 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.67514 |
324 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.83757 |
325 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.67514 |
326 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 27729.51498 |
327 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 34189.34000 |
328 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 17094.67000 |
329 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 34189.34000 |
330 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.72919 |
331 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.72919 |
332 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.72919 |
333 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.72919 |
334 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 34189.34000 |
335 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 41962.09681 |
336 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
337 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
338 | Fan:SystemModel | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.67514 |
339 | Fan:SystemModel | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1833.45541 |
340 | Coil:Heating:Fuel | PSZ-AC_10:10_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 41962.09681 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | 64024.4 | 9.84 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | 32324.5 | 30.88 | |||
3 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | 31156.9 | 42.43 | |||
4 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | 31101.7 | 52.87 | |||
5 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | 31059.6 | 63.31 | |||
6 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | 58041.1 | 42.10 | |||
7 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | 30326.4 | 95.11 | |||
8 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | 30220.0 | 105.82 | |||
9 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | 30279.8 | 115.98 | |||
10 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | 32872.5 | 116.90 |
Zone Name | # Surfaces | |
1 | LGSTORE1 | 15 |
2 | SMSTORE1 | 11 |
3 | SMSTORE2 | 11 |
4 | SMSTORE3 | 11 |
5 | SMSTORE4 | 11 |
6 | LGSTORE2 | 15 |
7 | SMSTORE5 | 11 |
8 | SMSTORE6 | 11 |
9 | SMSTORE7 | 11 |
10 | SMSTORE8 | 11 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | LGSTORE1_WALL_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.787 | 0.704 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | LGSTORE1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.787 | 0.704 | 71.15 | 78.94 | 71.15 | 0.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | LGSTORE1_WALL_3_DOOR_1 | Door | LGSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
4 | LGSTORE1_WALL_3_DOOR_2 | Door | LGSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
5 | LGSTORE1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
6 | LGSTORE1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.787 | 0.704 | 58.20 | 78.94 | 58.20 | 180.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
7 | LGSTORE1_WALL_1_WINDOW_1 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_1.2_SHGC_0.25 | N/A | 5.832 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
8 | LGSTORE1_WALL_1_WINDOW_2 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_1.2_SHGC_0.25 | N/A | 5.832 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
9 | LGSTORE1_WALL_1_WINDOW_3 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_1.2_SHGC_0.25 | N/A | 5.832 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
10 | LGSTORE1_WALL_1_WINDOW_4 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_1.2_SHGC_0.25 | N/A | 5.832 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
11 | LGSTORE1_WALL_1_DOOR_1 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_1.2_SHGC_0.25 | N/A | 5.832 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
12 | LGSTORE1_WALL_1_DOOR_2 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_1.2_SHGC_0.25 | N/A | 5.832 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
13 | LGSTORE1_FLOOR | Floor | CTF - ConductionTransferFunction | LGSTORE1_FLOOR_FFACTOR | 0.199 | 0.190 | 348.39 | 348.39 | 348.39 | 270.00 | 180.00 | 22.86 | 15.24 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | LGSTORE1_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 348.39 | 348.39 | 348.39 | 270.00 | 0.00 | 22.86 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
15 | LGSTORE1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 696.77 | 696.77 | 696.77 | 0.00 | 90.00 | 696.77 | 1.00 | 0.00 | LGSTORE1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
16 | SMSTORE1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.787 | 0.704 | 29.10 | 39.47 | 29.10 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
17 | SMSTORE1_WALL_1_WINDOW_1 | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_1.2_SHGC_0.25 | N/A | 5.832 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
18 | SMSTORE1_WALL_1_WINDOW_2 | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_1.2_SHGC_0.25 | N/A | 5.832 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
19 | SMSTORE1_WALL_1_DOOR | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_1.2_SHGC_0.25 | N/A | 5.832 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
20 | SMSTORE1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | SMSTORE1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.787 | 0.704 | 35.57 | 39.47 | 35.57 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | SMSTORE1_WALL_3_DOOR | Door | SMSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
23 | SMSTORE1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE2_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
24 | SMSTORE1_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE1_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | SMSTORE1_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
26 | SMSTORE1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
27 | SMSTORE2_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.787 | 0.704 | 29.12 | 39.47 | 29.12 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | SMSTORE2_WALL_1_WINDOW_1 | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_1.2_SHGC_0.25 | N/A | 5.832 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
29 | SMSTORE2_WALL_1_WINDOW_2 | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_1.2_SHGC_0.25 | N/A | 5.832 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
30 | SMSTORE2_WALL_1_DOOR | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_1.2_SHGC_0.25 | N/A | 5.832 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
31 | SMSTORE2_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
32 | SMSTORE2_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.787 | 0.704 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | SMSTORE2_WALL_3_DOOR | Door | SMSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
34 | SMSTORE2_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE3_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | SMSTORE2_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE2_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
36 | SMSTORE2_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
37 | SMSTORE2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
38 | SMSTORE3_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.787 | 0.704 | 29.12 | 39.47 | 29.12 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
39 | SMSTORE3_WALL_1_WINDOW_1 | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_1.2_SHGC_0.25 | N/A | 5.832 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
40 | SMSTORE3_WALL_1_WINDOW_2 | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_1.2_SHGC_0.25 | N/A | 5.832 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
41 | SMSTORE3_WALL_1_DOOR | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_1.2_SHGC_0.25 | N/A | 5.832 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
42 | SMSTORE3_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE2_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | SMSTORE3_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.787 | 0.704 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | SMSTORE3_WALL_3_DOOR | Door | SMSTORE3_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
45 | SMSTORE3_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE4_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | SMSTORE3_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE3_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
47 | SMSTORE3_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
48 | SMSTORE3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
49 | SMSTORE4_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.787 | 0.704 | 29.12 | 39.47 | 29.12 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | SMSTORE4_WALL_1_WINDOW_1 | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_1.2_SHGC_0.25 | N/A | 5.832 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
51 | SMSTORE4_WALL_1_WINDOW_2 | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_1.2_SHGC_0.25 | N/A | 5.832 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
52 | SMSTORE4_WALL_1_DOOR | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_1.2_SHGC_0.25 | N/A | 5.832 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | SMSTORE4_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE3_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | SMSTORE4_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.787 | 0.704 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | SMSTORE4_WALL_3_DOOR | Door | SMSTORE4_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | SMSTORE4_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE2_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | SMSTORE4_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE4_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | SMSTORE4_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | SMSTORE4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | LGSTORE2_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE4_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | LGSTORE2_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.787 | 0.704 | 71.19 | 78.94 | 71.19 | 0.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
62 | LGSTORE2_WALL_3_DOOR_1 | Door | LGSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
63 | LGSTORE2_WALL_3_DOOR_2 | Door | LGSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
64 | LGSTORE2_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE5_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | LGSTORE2_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.787 | 0.704 | 58.24 | 78.94 | 58.24 | 180.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
66 | LGSTORE2_WALL_1_WINDOW_1 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_1.2_SHGC_0.25 | N/A | 5.832 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | LGSTORE2_WALL_1_WINDOW_2 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_1.2_SHGC_0.25 | N/A | 5.832 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | LGSTORE2_WALL_1_WINDOW_3 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_1.2_SHGC_0.25 | N/A | 5.832 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | LGSTORE2_WALL_1_WINDOW_4 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_1.2_SHGC_0.25 | N/A | 5.832 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | LGSTORE2_WALL_1_DOOR_1 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_1.2_SHGC_0.25 | N/A | 5.832 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
71 | LGSTORE2_WALL_1_DOOR_2 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_1.2_SHGC_0.25 | N/A | 5.832 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
72 | LGSTORE2_FLOOR | Floor | CTF - ConductionTransferFunction | LGSTORE2_FLOOR_FFACTOR | 0.112 | 0.109 | 348.39 | 348.39 | 348.39 | 270.00 | 180.00 | 22.86 | 15.24 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
73 | LGSTORE2_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 348.39 | 348.39 | 348.39 | 270.00 | 0.00 | 22.86 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
74 | LGSTORE2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 696.77 | 696.77 | 696.77 | 0.00 | 90.00 | 696.77 | 1.00 | 0.00 | LGSTORE2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
75 | SMSTORE5_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.787 | 0.704 | 29.12 | 39.47 | 29.12 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | SMSTORE5_WALL_1_WINDOW_1 | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_1.2_SHGC_0.25 | N/A | 5.832 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
77 | SMSTORE5_WALL_1_WINDOW_2 | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_1.2_SHGC_0.25 | N/A | 5.832 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | SMSTORE5_WALL_1_DOOR | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_1.2_SHGC_0.25 | N/A | 5.832 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
79 | SMSTORE5_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE2_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | SMSTORE5_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.787 | 0.704 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | SMSTORE5_WALL_3_DOOR | Door | SMSTORE5_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
82 | SMSTORE5_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE6_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
83 | SMSTORE5_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE5_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
84 | SMSTORE5_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
85 | SMSTORE5_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE5_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
86 | SMSTORE6_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.787 | 0.704 | 29.12 | 39.47 | 29.12 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | SMSTORE6_WALL_1_WINDOW_1 | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_1.2_SHGC_0.25 | N/A | 5.832 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
88 | SMSTORE6_WALL_1_WINDOW_2 | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_1.2_SHGC_0.25 | N/A | 5.832 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
89 | SMSTORE6_WALL_1_DOOR | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_1.2_SHGC_0.25 | N/A | 5.832 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
90 | SMSTORE6_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE5_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
91 | SMSTORE6_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.787 | 0.704 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
92 | SMSTORE6_WALL_3_DOOR | Door | SMSTORE6_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
93 | SMSTORE6_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE7_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | SMSTORE6_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE6_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
95 | SMSTORE6_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
96 | SMSTORE6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
97 | SMSTORE7_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.787 | 0.704 | 29.12 | 39.47 | 29.12 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | SMSTORE7_WALL_1_WINDOW_1 | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_1.2_SHGC_0.25 | N/A | 5.832 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
99 | SMSTORE7_WALL_1_WINDOW_2 | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_1.2_SHGC_0.25 | N/A | 5.832 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
100 | SMSTORE7_WALL_1_DOOR | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_1.2_SHGC_0.25 | N/A | 5.832 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
101 | SMSTORE7_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE6_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
102 | SMSTORE7_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.787 | 0.704 | 35.59 | 39.47 | 35.59 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | SMSTORE7_WALL_3_DOOR | Door | SMSTORE7_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
104 | SMSTORE7_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE8_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | SMSTORE7_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE7_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
106 | SMSTORE7_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
107 | SMSTORE7_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE7_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
108 | SMSTORE8_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.787 | 0.704 | 29.12 | 39.47 | 29.12 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | SMSTORE8_WALL_1_WINDOW_1 | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_1.2_SHGC_0.25 | N/A | 5.832 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
110 | SMSTORE8_WALL_1_WINDOW_2 | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_1.2_SHGC_0.25 | N/A | 5.832 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
111 | SMSTORE8_WALL_1_DOOR | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_1.2_SHGC_0.25 | N/A | 5.832 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
112 | SMSTORE8_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE7_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
113 | SMSTORE8_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.787 | 0.704 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | SMSTORE8_WALL_3_DOOR | Door | SMSTORE8_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
115 | SMSTORE8_WALL_4 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.787 | 0.704 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | SMSTORE8_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE8_FLOOR_FFACTOR | 0.289 | 0.270 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | SMSTORE8_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | SMSTORE8_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE8_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1 |
2 | VETERANS DAY | Holiday | InputFile | 11/11 | 1 |
3 | CHRISTMAS | Holiday | InputFile | 12/25 | 1 |
4 | INDEPENDENCE DAY | Holiday | InputFile | 07/04 | 1 |
5 | MLK DAY | Holiday | InputFile | 01/16 | 1 |
6 | PRESIDENTS DAY | Holiday | InputFile | 02/20 | 1 |
7 | MEMORIAL DAY | Holiday | InputFile | 05/29 | 1 |
8 | LABOR DAY | Holiday | InputFile | 09/04 | 1 |
9 | COLUMBUS DAY | Holiday | InputFile | 10/09 | 1 |
10 | THANKSGIVING | Holiday | InputFile | 11/23 | 1 |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
NumberofWarmupDays | |
1 | 8 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | LGSTORE1 | RunPeriod: RUNPERIOD 1 | 6.4744762009E-002 | 7.4806123897E-002 | Pass | Pass | 4.1671865131E-002 | 0.1192303433 | Pass | Pass |
2 | SMSTORE1 | RunPeriod: RUNPERIOD 1 | 5.5100926673E-002 | 8.4437807560E-002 | Pass | Pass | 7.6941168295E-002 | 0.2037879779 | Pass | Pass |
3 | SMSTORE2 | RunPeriod: RUNPERIOD 1 | 5.3590333099E-002 | 6.3324922155E-002 | Pass | Pass | 0.1408401657 | 0.6663257707 | Pass | Pass |
4 | SMSTORE3 | RunPeriod: RUNPERIOD 1 | 5.4938088425E-002 | 0.1023592197 | Pass | Pass | 0.2257912256 | 1.1884539089 | Pass | Pass |
5 | SMSTORE4 | RunPeriod: RUNPERIOD 1 | 5.4031300791E-002 | 0.1321983413 | Pass | Pass | 0.2281558819 | 1.4125635039 | Pass | Pass |
6 | LGSTORE2 | RunPeriod: RUNPERIOD 1 | 5.1345763768E-002 | 0.1607155523 | Pass | Pass | 0.1353869017 | 0.4704280195 | Pass | Pass |
7 | SMSTORE5 | RunPeriod: RUNPERIOD 1 | 5.0609869757E-002 | 0.1678332916 | Pass | Pass | 0.3934140630 | 2.6756073453 | Pass | Pass |
8 | SMSTORE6 | RunPeriod: RUNPERIOD 1 | 5.0335828885E-002 | 0.1741573334 | Pass | Pass | 0.1972551483 | 0.9803055330 | Pass | Pass |
9 | SMSTORE7 | RunPeriod: RUNPERIOD 1 | 5.0848962536E-002 | 0.1939435583 | Pass | Pass | 0.1207810956 | 0.3623123320 | Pass | Pass |
10 | SMSTORE8 | RunPeriod: RUNPERIOD 1 | 6.0324100860E-002 | 0.2492337578 | Pass | Pass | 0.2368599313 | 0.7393152316 | Pass | Pass |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2020-06-03 19:18:56
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 6.30 | 0.00 | 6.30 | Wetbulb [C] | 0.50 | 270.00 |
NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 42.00 | 9.70 | 22.20 | Wetbulb [C] | 3.20 | 320.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2020-06-03 19:18:56
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_2 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE1_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 78.94 | 71.15 | 0.00 | 90.00 | N |
LGSTORE1_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 78.94 | 58.20 | 180.00 | 90.00 | S |
LGSTORE1_ROOF | NONRES_ROOF | 0.23 | 0.358 | 0.376 | 348.39 | 348.39 | 270.00 | 0.00 | |
SMSTORE1_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 39.47 | 29.10 | 180.00 | 90.00 | S |
SMSTORE1_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 39.47 | 35.57 | 0.00 | 90.00 | N |
SMSTORE1_ROOF | NONRES_ROOF | 0.23 | 0.358 | 0.376 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE2_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 39.47 | 29.12 | 180.00 | 90.00 | S |
SMSTORE2_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE2_ROOF | NONRES_ROOF | 0.23 | 0.358 | 0.376 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE3_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 39.47 | 29.12 | 180.00 | 90.00 | S |
SMSTORE3_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE3_ROOF | NONRES_ROOF | 0.23 | 0.358 | 0.376 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE4_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 39.47 | 29.12 | 180.00 | 90.00 | S |
SMSTORE4_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE4_ROOF | NONRES_ROOF | 0.23 | 0.358 | 0.376 | 174.19 | 174.19 | 270.00 | 0.00 | |
LGSTORE2_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 78.94 | 71.19 | 0.00 | 90.00 | N |
LGSTORE2_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 78.94 | 58.24 | 180.00 | 90.00 | S |
LGSTORE2_ROOF | NONRES_ROOF | 0.23 | 0.358 | 0.376 | 348.39 | 348.39 | 270.00 | 0.00 | |
SMSTORE5_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 39.47 | 29.12 | 180.00 | 90.00 | S |
SMSTORE5_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE5_ROOF | NONRES_ROOF | 0.23 | 0.358 | 0.376 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE6_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 39.47 | 29.12 | 180.00 | 90.00 | S |
SMSTORE6_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE6_ROOF | NONRES_ROOF | 0.23 | 0.358 | 0.376 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE7_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 39.47 | 29.12 | 180.00 | 90.00 | S |
SMSTORE7_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE7_ROOF | NONRES_ROOF | 0.23 | 0.358 | 0.376 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE8_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 39.47 | 29.12 | 180.00 | 90.00 | S |
SMSTORE8_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE8_WALL_4 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE8_ROOF | NONRES_ROOF | 0.23 | 0.358 | 0.376 | 174.19 | 174.19 | 270.00 | 0.00 | |
LGSTORE1_FLOOR | LGSTORE1_FLOOR_FFACTOR | 1.00 | 0.199 | 348.39 | 348.39 | 270.00 | 180.00 | ||
SMSTORE1_FLOOR | SMSTORE1_FLOOR_FFACTOR | 1.00 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | ||
SMSTORE2_FLOOR | SMSTORE2_FLOOR_FFACTOR | 1.00 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | ||
SMSTORE3_FLOOR | SMSTORE3_FLOOR_FFACTOR | 1.00 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | ||
SMSTORE4_FLOOR | SMSTORE4_FLOOR_FFACTOR | 1.00 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | ||
LGSTORE2_FLOOR | LGSTORE2_FLOOR_FFACTOR | 1.00 | 0.112 | 348.39 | 348.39 | 270.00 | 180.00 | ||
SMSTORE5_FLOOR | SMSTORE5_FLOOR_FFACTOR | 1.00 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | ||
SMSTORE6_FLOOR | SMSTORE6_FLOOR_FFACTOR | 1.00 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | ||
SMSTORE7_FLOOR | SMSTORE7_FLOOR_FFACTOR | 1.00 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | ||
SMSTORE8_FLOOR | SMSTORE8_FLOOR_FFACTOR | 1.00 | 0.289 | 174.19 | 174.19 | 270.00 | 180.00 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_1_WINDOW_1 | NONRESWINDOW_U_1.2_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 5.832 | 0.251 | 0.250 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE1_WALL_1_WINDOW_2 | NONRESWINDOW_U_1.2_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 5.832 | 0.251 | 0.250 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE1_WALL_1_WINDOW_3 | NONRESWINDOW_U_1.2_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 5.832 | 0.251 | 0.250 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE1_WALL_1_WINDOW_4 | NONRESWINDOW_U_1.2_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 5.832 | 0.251 | 0.250 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE1_WALL_1_DOOR_1 | NONRESWINDOW_U_1.2_SHGC_0.25 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 5.832 | 0.251 | 0.250 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE1_WALL_1_DOOR_2 | NONRESWINDOW_U_1.2_SHGC_0.25 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 5.832 | 0.251 | 0.250 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE1_WALL_1_WINDOW_1 | NONRESWINDOW_U_1.2_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 5.832 | 0.251 | 0.250 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE1_WALL_1_WINDOW_2 | NONRESWINDOW_U_1.2_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 5.832 | 0.251 | 0.250 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE1_WALL_1_DOOR | NONRESWINDOW_U_1.2_SHGC_0.25 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 5.832 | 0.251 | 0.250 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE2_WALL_1_WINDOW_1 | NONRESWINDOW_U_1.2_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 5.832 | 0.251 | 0.250 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE2_WALL_1_WINDOW_2 | NONRESWINDOW_U_1.2_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 5.832 | 0.251 | 0.250 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE2_WALL_1_DOOR | NONRESWINDOW_U_1.2_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 5.832 | 0.251 | 0.250 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE3_WALL_1_WINDOW_1 | NONRESWINDOW_U_1.2_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 5.832 | 0.251 | 0.250 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE3_WALL_1_WINDOW_2 | NONRESWINDOW_U_1.2_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 5.832 | 0.251 | 0.250 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE3_WALL_1_DOOR | NONRESWINDOW_U_1.2_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 5.832 | 0.251 | 0.250 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE4_WALL_1_WINDOW_1 | NONRESWINDOW_U_1.2_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 5.832 | 0.251 | 0.250 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE4_WALL_1_WINDOW_2 | NONRESWINDOW_U_1.2_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 5.832 | 0.251 | 0.250 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE4_WALL_1_DOOR | NONRESWINDOW_U_1.2_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 5.832 | 0.251 | 0.250 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE2_WALL_1_WINDOW_1 | NONRESWINDOW_U_1.2_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 5.832 | 0.251 | 0.250 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE2_WALL_1_WINDOW_2 | NONRESWINDOW_U_1.2_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 5.832 | 0.251 | 0.250 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE2_WALL_1_WINDOW_3 | NONRESWINDOW_U_1.2_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 5.832 | 0.251 | 0.250 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE2_WALL_1_WINDOW_4 | NONRESWINDOW_U_1.2_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 5.832 | 0.251 | 0.250 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE2_WALL_1_DOOR_1 | NONRESWINDOW_U_1.2_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 5.832 | 0.251 | 0.250 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE2_WALL_1_DOOR_2 | NONRESWINDOW_U_1.2_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 5.832 | 0.251 | 0.250 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE5_WALL_1_WINDOW_1 | NONRESWINDOW_U_1.2_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 5.832 | 0.251 | 0.250 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE5_WALL_1_WINDOW_2 | NONRESWINDOW_U_1.2_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 5.832 | 0.251 | 0.250 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE5_WALL_1_DOOR | NONRESWINDOW_U_1.2_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 5.832 | 0.251 | 0.250 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE6_WALL_1_WINDOW_1 | NONRESWINDOW_U_1.2_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 5.832 | 0.251 | 0.250 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE6_WALL_1_WINDOW_2 | NONRESWINDOW_U_1.2_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 5.832 | 0.251 | 0.250 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE6_WALL_1_DOOR | NONRESWINDOW_U_1.2_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 5.832 | 0.251 | 0.250 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE7_WALL_1_WINDOW_1 | NONRESWINDOW_U_1.2_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 5.832 | 0.251 | 0.250 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE7_WALL_1_WINDOW_2 | NONRESWINDOW_U_1.2_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 5.832 | 0.251 | 0.250 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE7_WALL_1_DOOR | NONRESWINDOW_U_1.2_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 5.832 | 0.251 | 0.250 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE8_WALL_1_WINDOW_1 | NONRESWINDOW_U_1.2_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 5.832 | 0.251 | 0.250 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE8_WALL_1_WINDOW_2 | NONRESWINDOW_U_1.2_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 5.832 | 0.251 | 0.250 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE8_WALL_1_DOOR | NONRESWINDOW_U_1.2_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 5.832 | 0.251 | 0.250 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | ||
Total or Average | 124.29 | 5.832 | 0.251 | 0.250 | ||||||||||||
North Total or Average | 0.00 | - | - | - | ||||||||||||
Non-North Total or Average | 124.29 | 5.832 | 0.251 | 0.250 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
LGSTORE1_WALL_3_DOOR_1 | SWINGING DOOR_CON | 2.492 | 3.975 | 3.90 | LGSTORE1_WALL_3 |
LGSTORE1_WALL_3_DOOR_2 | SWINGING DOOR_CON | 2.492 | 3.975 | 3.90 | LGSTORE1_WALL_3 |
SMSTORE1_WALL_3_DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 3.90 | SMSTORE1_WALL_3 |
SMSTORE2_WALL_3_DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 3.88 | SMSTORE2_WALL_3 |
SMSTORE3_WALL_3_DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 3.88 | SMSTORE3_WALL_3 |
SMSTORE4_WALL_3_DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 3.88 | SMSTORE4_WALL_3 |
LGSTORE2_WALL_3_DOOR_1 | SWINGING DOOR_CON | 2.492 | 3.975 | 3.88 | LGSTORE2_WALL_3 |
LGSTORE2_WALL_3_DOOR_2 | SWINGING DOOR_CON | 2.492 | 3.975 | 3.88 | LGSTORE2_WALL_3 |
SMSTORE5_WALL_3_DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 3.88 | SMSTORE5_WALL_3 |
SMSTORE6_WALL_3_DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 3.88 | SMSTORE6_WALL_3 |
SMSTORE7_WALL_3_DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 3.88 | SMSTORE7_WALL_3 |
SMSTORE8_WALL_3_DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 3.88 | SMSTORE8_WALL_3 |
Report: Shading Summary
For: Entire Facility
Timestamp: 2020-06-03 19:18:56
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
LGSTORE1_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_4 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_DOOR_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_DOOR_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_4 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_DOOR_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_DOOR_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2020-06-03 19:18:56
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
LGSTORE1_LIGHTS | LGSTORE1 | 18.3225 | 348.39 | 6383.30 | LightsWired | TYPE1_LIGHT_SCH | 98.40 | 168.00 | 98.38 | 0.0000 | Y | 117.88 |
LGSTORE1_LIGHTS_ALLOWANCE | LGSTORE1 | 10.4948 | 348.39 | 3656.25 | LightsWired | TYPE1_LIGHT_SCH | 98.40 | 168.00 | 98.38 | 0.0000 | Y | 67.52 |
SMSTORE1_LIGHTS | SMSTORE1 | 18.3225 | 174.19 | 3191.65 | LightsWired | TYPE1_LIGHT_SCH | 98.40 | 168.00 | 98.38 | 0.0000 | Y | 58.94 |
SMSTORE1_LIGHTS_ALLOWANCE | SMSTORE1 | 10.4948 | 174.19 | 1828.13 | LightsWired | TYPE1_LIGHT_SCH | 98.40 | 168.00 | 98.38 | 0.0000 | Y | 33.76 |
SMSTORE2_LIGHTS | SMSTORE2 | 18.3225 | 174.19 | 3191.65 | LightsWired | TYPE2_LIGHT_SCH | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 46.71 |
SMSTORE2_LIGHTS_ALLOWANCE | SMSTORE2 | 4.3056 | 174.19 | 750.00 | LightsWired | TYPE2_LIGHT_SCH | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 10.98 |
SMSTORE3_LIGHTS | SMSTORE3 | 18.3225 | 174.19 | 3191.65 | LightsWired | TYPE2_LIGHT_SCH | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 46.71 |
SMSTORE3_LIGHTS_ALLOWANCE | SMSTORE3 | 4.3056 | 174.19 | 750.00 | LightsWired | TYPE2_LIGHT_SCH | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 10.98 |
SMSTORE4_LIGHTS | SMSTORE4 | 18.3225 | 174.19 | 3191.65 | LightsWired | TYPE2_LIGHT_SCH | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 46.71 |
SMSTORE4_LIGHTS_ALLOWANCE | SMSTORE4 | 4.3056 | 174.19 | 750.00 | LightsWired | TYPE2_LIGHT_SCH | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 10.98 |
LGSTORE2_LIGHTS | LGSTORE2 | 18.3225 | 348.39 | 6383.30 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 168.00 | 71.66 | 0.0000 | Y | 85.86 |
LGSTORE2_LIGHTS_ALLOWANCE | LGSTORE2 | 0.0000 | 348.39 | 0.00 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE5_LIGHTS | SMSTORE5 | 18.3225 | 174.19 | 3191.65 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 168.00 | 71.66 | 0.0000 | Y | 42.93 |
SMSTORE5_LIGHTS_ALLOWANCE | SMSTORE5 | 0.0000 | 174.19 | 0.00 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE6_LIGHTS | SMSTORE6 | 18.3225 | 174.19 | 3191.65 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 168.00 | 71.66 | 0.0000 | Y | 42.93 |
SMSTORE6_LIGHTS_ALLOWANCE | SMSTORE6 | 0.0000 | 174.19 | 0.00 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE7_LIGHTS | SMSTORE7 | 18.3225 | 174.19 | 3191.65 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 168.00 | 71.66 | 0.0000 | Y | 42.93 |
SMSTORE7_LIGHTS_ALLOWANCE | SMSTORE7 | 0.0000 | 174.19 | 0.00 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE8_LIGHTS | SMSTORE8 | 18.3225 | 174.19 | 3191.65 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 168.00 | 71.66 | 0.0000 | Y | 42.93 |
SMSTORE8_LIGHTS_ALLOWANCE | SMSTORE8 | 0.0000 | 174.19 | 0.00 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
Interior Lighting Total | 11.0113 | 4180.64 | 46034.15 | 708.74 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS | 10625.34 | AstronomicalClock | - | 83.75 | 83.75 | 167.05 | |
Exterior Lighting Total | 10625.34 | 167.05 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2020-06-03 19:18:56
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 66560.00 | 48313.91 | 18246.09 | 0.73 | 3.30 | |||
PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 33607.54 | 24416.21 | 9191.33 | 0.73 | 3.50 | |||
PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 32386.23 | 23473.22 | 8913.01 | 0.72 | 3.50 | |||
PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 32328.52 | 23428.48 | 8900.04 | 0.72 | 3.50 | |||
PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 32284.42 | 23394.58 | 8889.84 | 0.72 | 3.50 | |||
PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 60301.45 | 43480.96 | 16820.49 | 0.72 | 3.30 | |||
PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 31517.54 | 22802.31 | 8715.23 | 0.72 | 3.50 | |||
PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 31406.18 | 22716.40 | 8689.78 | 0.72 | 3.50 | |||
PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 31468.69 | 22764.45 | 8704.24 | 0.72 | 3.50 | |||
PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 34189.34 | 24930.52 | 9258.82 | 0.73 | 3.50 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | 64024.4 | 9.84 | ||||
PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | 32324.5 | 30.88 | ||||
PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | 31156.9 | 42.43 | ||||
PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | 31101.7 | 52.87 | ||||
PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | 31059.6 | 63.31 | ||||
PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | 58041.1 | 42.10 | ||||
PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | 30326.4 | 95.11 | ||||
PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | 30220.0 | 105.82 | ||||
PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | 30279.8 | 115.98 | ||||
PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | 32872.5 | 116.90 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
PSZ-AC_1:1_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 81128.24 | 0.79 | |
PSZ-AC_2:2_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 40997.44 | 0.80 | |
PSZ-AC_3:3_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 39471.74 | 0.80 | |
PSZ-AC_4:4_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 39399.56 | 0.80 | |
PSZ-AC_5:5_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 39344.45 | 0.80 | |
PSZ-AC_6:6_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 73310.12 | 0.79 | |
PSZ-AC_7:7_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 38385.92 | 0.80 | |
PSZ-AC_8:8_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 38246.90 | 0.80 | |
PSZ-AC_9:9_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 38324.73 | 0.80 | |
PSZ-AC_10:10_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 41962.10 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.57 | 622.50 | 3.22 | 3529.59 | 1094.51 | 1.00 | 1.23 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:30:00 |
PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.57 | 622.50 | 1.63 | 1786.07 | 1094.51 | 1.00 | 1.32 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 |
PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.57 | 622.50 | 1.56 | 1711.13 | 1094.51 | 1.00 | 1.32 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:50:00 |
PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.57 | 622.50 | 1.56 | 1707.58 | 1094.51 | 1.00 | 1.32 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:50:00 |
PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.57 | 622.50 | 1.56 | 1704.88 | 1094.51 | 1.00 | 1.32 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:50:00 |
PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.57 | 622.50 | 2.87 | 3145.56 | 1094.51 | 1.00 | 1.24 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:50:00 |
PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.57 | 622.50 | 1.51 | 1657.79 | 1094.51 | 1.00 | 1.33 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:50:00 |
PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.57 | 622.50 | 1.51 | 1650.96 | 1094.51 | 1.00 | 1.33 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:50:00 |
PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.57 | 622.50 | 1.51 | 1654.79 | 1094.51 | 1.00 | 1.33 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:40:00 |
PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.57 | 622.50 | 1.68 | 1833.46 | 1094.51 | 1.00 | 1.31 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
GAS TANK1 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK2 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK3 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK4 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK5 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK6 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK7 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:18:56
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
LGSTORE1 | 35598.57 | 42718.29 | 122.62 | 2.687 | 3.225 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:30:00 | 23.89 | 23.89 | 0.00742 | 42.00 | 0.00911 | 0.531 | 0.00 |
SMSTORE1 | 18013.81 | 21616.57 | 124.10 | 1.360 | 1.632 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | 23.89 | 23.89 | 0.00744 | 42.00 | 0.00911 | 0.265 | 0.00 |
SMSTORE2 | 17257.95 | 20709.54 | 118.89 | 1.303 | 1.563 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:50:00 | 23.89 | 23.89 | 0.00746 | 41.92 | 0.00911 | 0.265 | 0.00 |
SMSTORE3 | 17222.19 | 20666.63 | 118.64 | 1.300 | 1.560 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:50:00 | 23.89 | 23.89 | 0.00746 | 41.92 | 0.00911 | 0.265 | 0.00 |
SMSTORE4 | 17194.88 | 20633.86 | 118.45 | 1.298 | 1.558 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:50:00 | 23.89 | 23.89 | 0.00746 | 41.92 | 0.00911 | 0.265 | 0.00 |
LGSTORE2 | 31725.38 | 38070.45 | 109.28 | 2.395 | 2.874 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:50:00 | 23.89 | 23.89 | 0.00746 | 41.92 | 0.00911 | 0.531 | 0.00 |
SMSTORE5 | 16720.02 | 20064.02 | 115.18 | 1.262 | 1.515 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:50:00 | 23.89 | 23.89 | 0.00747 | 41.92 | 0.00911 | 0.265 | 0.00 |
SMSTORE6 | 16651.14 | 19981.37 | 114.71 | 1.257 | 1.508 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:50:00 | 23.89 | 23.89 | 0.00747 | 41.92 | 0.00911 | 0.265 | 0.00 |
SMSTORE7 | 16689.72 | 20027.67 | 114.97 | 1.260 | 1.512 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:40:00 | 23.89 | 23.89 | 0.00747 | 41.84 | 0.00911 | 0.265 | 0.00 |
SMSTORE8 | 18492.51 | 22191.02 | 127.39 | 1.396 | 1.675 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:00:00 | 23.89 | 23.89 | 0.00744 | 41.52 | 0.00911 | 0.265 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
LGSTORE1 | 15883.86 | 19060.63 | 54.71 | 0.702 | 0.843 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00738 | 6.30 | 0.00607 | 0.531 | 0.00 |
SMSTORE1 | 8009.89 | 9611.87 | 55.18 | 0.354 | 0.425 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00732 | 6.30 | 0.00607 | 0.265 | 0.00 |
SMSTORE2 | 8128.84 | 9754.61 | 56.00 | 0.360 | 0.431 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00732 | 6.30 | 0.00607 | 0.265 | 0.00 |
SMSTORE3 | 8212.32 | 9854.79 | 56.57 | 0.363 | 0.436 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00733 | 6.30 | 0.00607 | 0.265 | 0.00 |
SMSTORE4 | 8369.31 | 10043.18 | 57.66 | 0.370 | 0.444 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00733 | 6.30 | 0.00607 | 0.265 | 0.00 |
LGSTORE2 | 15977.53 | 19173.04 | 55.03 | 0.707 | 0.848 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00738 | 6.30 | 0.00607 | 0.531 | 0.00 |
SMSTORE5 | 8620.11 | 10344.14 | 59.38 | 0.381 | 0.457 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00734 | 6.30 | 0.00607 | 0.265 | 0.00 |
SMSTORE6 | 8612.46 | 10334.96 | 59.33 | 0.381 | 0.457 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00734 | 6.30 | 0.00607 | 0.265 | 0.00 |
SMSTORE7 | 8816.43 | 10579.71 | 60.74 | 0.390 | 0.468 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00735 | 6.30 | 0.00607 | 0.265 | 0.00 |
SMSTORE8 | 9963.24 | 11955.89 | 68.64 | 0.441 | 0.529 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00739 | 6.30 | 0.00607 | 0.265 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC_1:1 | 3.22 | 3.22 | 0.84 | 0.84 | 3.2248 | 3.2248 | 3.2248 | 1.0000 | 1.0000 |
PSZ-AC_2:2 | 1.63 | 1.63 | 0.43 | 0.43 | 1.6319 | 1.6319 | 1.6319 | 1.0000 | 1.0000 |
PSZ-AC_3:3 | 1.56 | 1.56 | 0.43 | 0.43 | 1.5634 | 1.5634 | 1.5634 | 1.0000 | 1.0000 |
PSZ-AC_4:4 | 1.56 | 1.56 | 0.44 | 0.44 | 1.5601 | 1.5601 | 1.5601 | 1.0000 | 1.0000 |
PSZ-AC_5:5 | 1.56 | 1.56 | 0.44 | 0.44 | 1.5577 | 1.5577 | 1.5577 | 1.0000 | 1.0000 |
PSZ-AC_6:6 | 2.87 | 2.87 | 0.85 | 0.85 | 2.8740 | 2.8740 | 2.8740 | 1.0000 | 1.0000 |
PSZ-AC_7:7 | 1.51 | 1.51 | 0.46 | 0.46 | 1.5147 | 1.5147 | 1.5147 | 1.0000 | 1.0000 |
PSZ-AC_8:8 | 1.51 | 1.51 | 0.46 | 0.46 | 1.5084 | 1.5084 | 1.5084 | 1.0000 | 1.0000 |
PSZ-AC_9:9 | 1.51 | 1.51 | 0.47 | 0.47 | 1.5119 | 1.5119 | 1.5119 | 1.0000 | 1.0000 |
PSZ-AC_10:10 | 1.68 | 1.68 | 0.53 | 0.53 | 1.6751 | 1.6751 | 1.6751 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_1:1 | 66560.000 | 0.000 | 3.224830 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:30:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:30:00 | 66560.00 | 66560.00 | 3.224830 | 26.87 | 16.43 | 0.00769764 | 12.80 | 11.87 | 0.00850000 | 42.00 | 0.00911023 | 22.20 | 16.4631 | 23.89 | 0.00741925 | 39.2622 | 35598.57 | 0.00 | -999.00 | -999.00 |
PSZ-AC_1:1_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_1:1 | 81128.241 | 81128.241 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 81128.24 | 81128.24 | 3.224830 | 11.78 | 9.41 | 0.00655568 | 40.00 | 20.85 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 16.4631 | 21.11 | 0.00737797 | 46.2299 | 15883.86 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_2:2 | 33607.540 | 0.000 | 1.631860 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | 33607.54 | 33607.54 | 1.631860 | 26.83 | 16.43 | 0.00771134 | 12.80 | 11.87 | 0.00850000 | 42.00 | 0.00911023 | 22.20 | 16.2670 | 23.89 | 0.00743958 | 39.3686 | 18013.81 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_2:2 | 40997.438 | 40997.438 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 40997.44 | 40997.44 | 1.631855 | 11.86 | 9.43 | 0.00653975 | 40.00 | 20.85 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 16.2670 | 21.11 | 0.00731697 | 45.8525 | 8009.89 | 0.00 | -999.00 | -999.00 |
PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_3:3 | 32386.230 | 0.000 | 1.563380 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:50:00 | 32386.23 | 32386.23 | 1.563380 | 26.96 | 16.49 | 0.00773708 | 12.80 | 11.87 | 0.00850000 | 42.00 | 0.00911023 | 22.20 | 16.9795 | 23.89 | 0.00745618 | 39.4555 | 17256.79 | 0.00 | -999.00 | -999.00 |
PSZ-AC_3:3_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_3:3 | 39471.740 | 39471.740 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 39471.74 | 39471.74 | 1.563382 | 12.00 | 9.50 | 0.00655290 | 40.00 | 20.85 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 16.9795 | 21.11 | 0.00732159 | 45.8812 | 8128.84 | 0.00 | -999.00 | -999.00 |
PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_4:4 | 32328.520 | 0.000 | 1.560140 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:50:00 | 32328.52 | 32328.52 | 1.560140 | 26.97 | 16.50 | 0.00773836 | 12.80 | 11.87 | 0.00850000 | 42.00 | 0.00911023 | 22.20 | 17.0147 | 23.89 | 0.00745700 | 39.4597 | 17220.66 | 0.00 | -999.00 | -999.00 |
PSZ-AC_4:4_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_4:4 | 39399.563 | 39399.563 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 39399.56 | 39399.56 | 1.560143 | 12.09 | 9.55 | 0.00656209 | 40.00 | 20.85 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 17.0147 | 21.11 | 0.00732512 | 45.9031 | 8212.32 | 0.00 | -999.00 | -999.00 |
PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_5:5 | 32284.420 | 0.000 | 1.557670 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:50:00 | 32284.42 | 32284.42 | 1.557670 | 26.97 | 16.50 | 0.00773934 | 12.80 | 11.87 | 0.00850000 | 42.00 | 0.00911023 | 22.20 | 17.0417 | 23.89 | 0.00745763 | 39.4630 | 17193.17 | 0.00 | -999.00 | -999.00 |
PSZ-AC_5:5_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_5:5 | 39344.447 | 39344.447 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 39344.45 | 39344.45 | 1.557669 | 12.26 | 9.65 | 0.00657914 | 40.00 | 20.85 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 17.0417 | 21.11 | 0.00733191 | 45.9451 | 8369.31 | 0.00 | -999.00 | -999.00 |
PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_6:6 | 60301.450 | 0.000 | 2.873960 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:50:00 | 60301.45 | 60301.45 | 2.873960 | 27.23 | 16.61 | 0.00776537 | 12.80 | 11.87 | 0.00850000 | 42.00 | 0.00911023 | 22.20 | 18.4730 | 23.89 | 0.00746038 | 39.4773 | 31716.72 | 0.00 | -999.00 | -999.00 |
PSZ-AC_6:6_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_6:6 | 73310.123 | 73310.123 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 73310.12 | 73310.12 | 2.873955 | 11.84 | 9.44 | 0.00656179 | 40.00 | 20.85 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 18.4731 | 21.11 | 0.00738140 | 46.2511 | 15977.53 | 0.00 | -999.00 | -999.00 |
PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_7:7 | 31517.540 | 0.000 | 1.514650 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:50:00 | 31517.54 | 31517.54 | 1.514650 | 27.06 | 16.55 | 0.00775670 | 12.80 | 11.87 | 0.00850000 | 42.00 | 0.00911023 | 22.20 | 17.5258 | 23.89 | 0.00746882 | 39.5215 | 16714.95 | 0.00 | -999.00 | -999.00 |
PSZ-AC_7:7_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_7:7 | 38385.923 | 38385.923 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 38385.92 | 38385.92 | 1.514651 | 12.52 | 9.79 | 0.00660540 | 40.00 | 20.85 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 17.5257 | 21.11 | 0.00734230 | 46.0095 | 8620.11 | 0.00 | -999.00 | -999.00 |
PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_8:8 | 31406.180 | 0.000 | 1.508410 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:50:00 | 31406.18 | 31406.18 | 1.508410 | 27.08 | 16.55 | 0.00775926 | 12.80 | 11.87 | 0.00850000 | 42.00 | 0.00911023 | 22.20 | 17.5983 | 23.89 | 0.00747049 | 39.5302 | 16646.03 | 0.00 | -999.00 | -999.00 |
PSZ-AC_8:8_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_8:8 | 38246.901 | 38246.901 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 38246.90 | 38246.90 | 1.508412 | 12.51 | 9.78 | 0.00660463 | 40.00 | 20.85 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 17.5982 | 21.11 | 0.00734202 | 46.0077 | 8612.46 | 0.00 | -999.00 | -999.00 |
PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_9:9 | 31468.690 | 0.000 | 1.511900 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:40:00 | 31468.69 | 31468.69 | 1.511900 | 27.07 | 16.55 | 0.00775785 | 12.80 | 11.87 | 0.00850000 | 42.00 | 0.00911023 | 22.20 | 17.5576 | 23.89 | 0.00746932 | 39.5242 | 16683.95 | 0.00 | -999.00 | -999.00 |
PSZ-AC_9:9_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_9:9 | 38324.727 | 38324.727 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 38324.73 | 38324.73 | 1.511904 | 12.71 | 9.89 | 0.00662518 | 40.00 | 20.85 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 17.5576 | 21.11 | 0.00735008 | 46.0577 | 8816.43 | 0.00 | -999.00 | -999.00 |
PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_10:10 | 34189.340 | 0.000 | 1.675140 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:30:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:00:00 | 34189.34 | 34189.34 | 1.675140 | 26.72 | 16.38 | 0.00770174 | 12.80 | 11.87 | 0.00850000 | 41.76 | 0.00911022 | 22.13 | 15.8467 | 23.89 | 0.00743664 | 39.3533 | 18415.18 | 0.00 | -999.00 | -999.00 |
PSZ-AC_10:10_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_10:10 | 41962.097 | 41962.097 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 41962.10 | 41962.10 | 1.675145 | 13.67 | 10.42 | 0.00672764 | 40.00 | 20.85 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 15.8466 | 21.11 | 0.00738829 | 46.2946 | 9963.24 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2020-06-03 19:18:56
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | LGSTORE1 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 66560.000 | 0.000 | 3.224830 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.1495 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:30:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:30:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:30:00 | 66560.00 | 66560.00 | 1.0000 | 3.78525857 | 3.224830 | 26.87 | 16.43 | 0.00769764 | 46635.2 | 12.80 | 11.87 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 66560.00 | 42.00 | 0.00911023 | 22.20 | 0.53090778 | 16.4631 | 23.89 | 0.00741925 | 23.89 | 0.00741925 | 39.2622 | 35598.57 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_1:1_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | LGSTORE1 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 81128.241 | 81128.241 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 3.224830 | 3.78525872 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 81128.24 | 81128.24 | 1.0000 | 3.78525872 | 3.224830 | 11.78 | 9.41 | 0.00655568 | 28378.2 | 40.00 | 20.85 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 81128.24 | 6.30 | 0.00607234 | 6.30 | 0.53090778 | 16.4631 | 21.11 | 0.00737797 | 21.11 | 0.00737797 | 46.2299 | 15883.86 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | SMSTORE1 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 33607.540 | 0.000 | 1.631860 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.1750 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | 33607.54 | 33607.54 | 1.0000 | 1.91545354 | 1.631860 | 26.83 | 16.43 | 0.00771134 | 46634.0 | 12.80 | 11.87 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 33607.54 | 42.00 | 0.00911023 | 22.20 | 0.26545389 | 16.2670 | 23.89 | 0.00743958 | 23.89 | 0.00743958 | 39.3686 | 18013.81 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | SMSTORE1 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 40997.438 | 40997.438 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.631855 | 1.91544775 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 40997.44 | 40997.44 | 1.0000 | 1.91544775 | 1.631855 | 11.86 | 9.43 | 0.00653975 | 28418.4 | 40.00 | 20.85 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 40997.44 | 6.30 | 0.00607234 | 6.30 | 0.26545389 | 16.2670 | 21.11 | 0.00731697 | 21.11 | 0.00731697 | 45.8525 | 8009.89 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_3:3 | SMSTORE2 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 32386.230 | 0.000 | 1.563380 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.2229 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:50:00 | 32386.23 | 32386.23 | 1.0000 | 1.83507271 | 1.563380 | 26.96 | 16.49 | 0.00773708 | 46831.4 | 12.80 | 11.87 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 32386.23 | 42.00 | 0.00911023 | 22.20 | 0.26545389 | 16.9795 | 23.89 | 0.00745622 | 23.89 | 0.00745618 | 39.4555 | 17256.79 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_3:3_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_3:3 | SMSTORE2 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 39471.740 | 39471.740 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.563382 | 1.83507495 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 39471.74 | 39471.74 | 1.0000 | 1.83507495 | 1.563382 | 12.00 | 9.50 | 0.00655290 | 28589.2 | 40.00 | 20.85 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 39471.74 | 6.30 | 0.00607234 | 6.30 | 0.26545389 | 16.9795 | 21.11 | 0.00732159 | 21.11 | 0.00732159 | 45.8812 | 8128.84 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_4:4 | SMSTORE3 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 32328.520 | 0.000 | 1.560140 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.2252 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:50:00 | 32328.52 | 32328.52 | 1.0000 | 1.83126965 | 1.560140 | 26.97 | 16.50 | 0.00773836 | 46841.2 | 12.80 | 11.87 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 32328.52 | 42.00 | 0.00911023 | 22.20 | 0.26545389 | 17.0147 | 23.89 | 0.00745705 | 23.89 | 0.00745700 | 39.4597 | 17220.66 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_4:4_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_4:4 | SMSTORE3 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 39399.563 | 39399.563 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.560143 | 1.83127259 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 39399.56 | 39399.56 | 1.0000 | 1.83127259 | 1.560143 | 12.09 | 9.55 | 0.00656209 | 28706.6 | 40.00 | 20.85 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 39399.56 | 6.30 | 0.00607234 | 6.30 | 0.26545389 | 17.0147 | 21.11 | 0.00732512 | 21.11 | 0.00732512 | 45.9031 | 8212.32 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_5:5 | SMSTORE4 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 32284.420 | 0.000 | 1.557670 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.2270 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:50:00 | 32284.42 | 32284.42 | 1.0000 | 1.82837040 | 1.557670 | 26.97 | 16.50 | 0.00773934 | 46848.7 | 12.80 | 11.87 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 32284.42 | 42.00 | 0.00911023 | 22.20 | 0.26545389 | 17.0417 | 23.89 | 0.00745769 | 23.89 | 0.00745763 | 39.4630 | 17193.17 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_5:5_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_5:5 | SMSTORE4 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 39344.447 | 39344.447 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.557669 | 1.82836910 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 39344.45 | 39344.45 | 1.0000 | 1.82836910 | 1.557669 | 12.26 | 9.65 | 0.00657914 | 28921.7 | 40.00 | 20.85 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 39344.45 | 6.30 | 0.00607234 | 6.30 | 0.26545389 | 17.0417 | 21.11 | 0.00733191 | 21.11 | 0.00733191 | 45.9451 | 8369.31 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_6:6 | LGSTORE2 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 60301.450 | 0.000 | 2.873960 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.2754 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:50:00 | 60301.45 | 60301.45 | 1.0000 | 3.37341246 | 2.873960 | 27.23 | 16.61 | 0.00776537 | 47180.0 | 12.80 | 11.87 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 60301.45 | 42.00 | 0.00911023 | 22.20 | 0.53090778 | 18.4730 | 23.89 | 0.00746053 | 23.89 | 0.00746038 | 39.4773 | 31716.72 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_6:6_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_6:6 | LGSTORE2 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 73310.123 | 73310.123 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.873955 | 3.37340711 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 73310.12 | 73310.12 | 1.0000 | 3.37340711 | 2.873955 | 11.84 | 9.44 | 0.00656179 | 28449.3 | 40.00 | 20.85 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 73310.12 | 6.30 | 0.00607234 | 6.30 | 0.53090778 | 18.4731 | 21.11 | 0.00738140 | 21.11 | 0.00738140 | 46.2511 | 15977.53 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_7:7 | SMSTORE5 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 31517.540 | 0.000 | 1.514650 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.2593 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:50:00 | 31517.54 | 31517.54 | 1.0000 | 1.77787415 | 1.514650 | 27.06 | 16.55 | 0.00775670 | 46983.0 | 12.80 | 11.87 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 31517.54 | 42.00 | 0.00911023 | 22.20 | 0.26545389 | 17.5258 | 23.89 | 0.00746897 | 23.89 | 0.00746882 | 39.5215 | 16714.95 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_7:7_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_7:7 | SMSTORE5 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 38385.923 | 38385.923 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.514651 | 1.77787516 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 38385.92 | 38385.92 | 1.0000 | 1.77787516 | 1.514651 | 12.52 | 9.79 | 0.00660540 | 29249.9 | 40.00 | 20.85 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 38385.92 | 6.30 | 0.00607234 | 6.30 | 0.26545389 | 17.5257 | 21.11 | 0.00734230 | 21.11 | 0.00734230 | 46.0095 | 8620.11 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_8:8 | SMSTORE6 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 31406.180 | 0.000 | 1.508410 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.2641 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:50:00 | 31406.18 | 31406.18 | 1.0000 | 1.77054973 | 1.508410 | 27.08 | 16.55 | 0.00775926 | 47003.0 | 12.80 | 11.87 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 31406.18 | 42.00 | 0.00911023 | 22.20 | 0.26545389 | 17.5983 | 23.89 | 0.00747063 | 23.89 | 0.00747049 | 39.5302 | 16646.03 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_8:8_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_8:8 | SMSTORE6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 38246.901 | 38246.901 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.508412 | 1.77055166 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 38246.90 | 38246.90 | 1.0000 | 1.77055166 | 1.508412 | 12.51 | 9.78 | 0.00660463 | 29240.2 | 40.00 | 20.85 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 38246.90 | 6.30 | 0.00607234 | 6.30 | 0.26545389 | 17.5982 | 21.11 | 0.00734202 | 21.11 | 0.00734202 | 46.0077 | 8612.46 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_9:9 | SMSTORE7 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 31468.690 | 0.000 | 1.511900 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.2615 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:40:00 | 31468.69 | 31468.69 | 1.0000 | 1.77464624 | 1.511900 | 27.07 | 16.55 | 0.00775785 | 46992.0 | 12.80 | 11.87 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 31468.69 | 42.00 | 0.00911023 | 22.20 | 0.26545389 | 17.5576 | 23.89 | 0.00746972 | 23.89 | 0.00746932 | 39.5242 | 16683.95 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_9:9_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_9:9 | SMSTORE7 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 38324.727 | 38324.727 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.511904 | 1.77465122 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 38324.73 | 38324.73 | 1.0000 | 1.77465122 | 1.511904 | 12.71 | 9.89 | 0.00662518 | 29494.4 | 40.00 | 20.85 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 38324.73 | 6.30 | 0.00607234 | 6.30 | 0.26545389 | 17.5576 | 21.11 | 0.00735008 | 21.11 | 0.00735008 | 46.0577 | 8816.43 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_10:10 | SMSTORE8 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 34189.340 | 0.000 | 1.675140 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.1572 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:30:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:50:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:00:00 | 34189.34 | 34189.34 | 1.0000 | 1.96625498 | 1.675140 | 26.72 | 16.38 | 0.00770174 | 46497.1 | 12.80 | 11.87 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 34189.34 | 41.76 | 0.00911022 | 22.13 | 0.26545389 | 15.8467 | 23.89 | 0.00743605 | 23.89 | 0.00743664 | 39.3533 | 18415.18 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_10:10_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_10:10 | SMSTORE8 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 41962.097 | 41962.097 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.675145 | 1.96626084 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 41962.10 | 41962.10 | 1.0000 | 1.96626084 | 1.675145 | 13.67 | 10.42 | 0.00672764 | 30736.9 | 40.00 | 20.85 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 41962.10 | 6.30 | 0.00607234 | 6.30 | 0.26545389 | 15.8466 | 21.11 | 0.00738829 | 21.11 | 0.00738829 | 46.2946 | 9963.24 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2020-06-03 19:18:56
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
LGSTORE1 | 5027.67 | 1164.33 | 933.17 |
SMSTORE1 | 4884.83 | 975.67 | 789.33 |
SMSTORE2 | 3600.33 | 1157.33 | 923.17 |
SMSTORE3 | 3547.00 | 1184.50 | 919.17 |
SMSTORE4 | 3509.50 | 1218.00 | 926.17 |
LGSTORE2 | 3176.83 | 1113.83 | 840.33 |
SMSTORE5 | 3078.50 | 1147.17 | 846.83 |
SMSTORE6 | 3054.83 | 1161.50 | 849.00 |
SMSTORE7 | 3021.67 | 1186.17 | 846.83 |
SMSTORE8 | 3028.33 | 1169.17 | 784.00 |
Facility | 5116.33 | 1752.33 | 1197.17 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
LGSTORE1 | 0.00 | 13.17 | 0.00 | 9.17 |
SMSTORE1 | 0.00 | 7.67 | 0.00 | 5.67 |
SMSTORE2 | 0.00 | 17.17 | 0.00 | 0.00 |
SMSTORE3 | 0.00 | 17.83 | 0.00 | 0.00 |
SMSTORE4 | 0.00 | 16.83 | 0.00 | 0.00 |
LGSTORE2 | 0.00 | 15.83 | 0.00 | 0.00 |
SMSTORE5 | 0.00 | 14.00 | 0.00 | 0.00 |
SMSTORE6 | 0.00 | 14.00 | 0.00 | 0.00 |
SMSTORE7 | 0.00 | 13.33 | 0.00 | 0.00 |
SMSTORE8 | 0.00 | 16.67 | 0.00 | 0.00 |
Facility | 0.00 | 36.33 | 0.00 | 9.17 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2020-06-03 19:18:56
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
LGSTORE1 | 9.02 | 30.00 | 1805.20 | 1.094 | 0.340 | 0.000 | 0.000 |
SMSTORE1 | 4.51 | 15.00 | 902.60 | 0.888 | 0.379 | 0.000 | 0.000 |
SMSTORE2 | 3.78 | 15.00 | 902.60 | 1.095 | 0.499 | 0.000 | 0.000 |
SMSTORE3 | 3.78 | 15.00 | 902.60 | 1.095 | 0.499 | 0.000 | 0.000 |
SMSTORE4 | 3.78 | 15.00 | 902.60 | 1.095 | 0.499 | 0.000 | 0.000 |
LGSTORE2 | 13.23 | 30.00 | 1805.20 | 1.094 | 0.466 | 0.000 | 0.000 |
SMSTORE5 | 6.61 | 15.00 | 902.60 | 1.094 | 0.532 | 0.000 | 0.000 |
SMSTORE6 | 6.61 | 15.00 | 902.60 | 1.094 | 0.532 | 0.000 | 0.000 |
SMSTORE7 | 6.61 | 15.00 | 902.60 | 1.094 | 0.532 | 0.000 | 0.000 |
SMSTORE8 | 6.61 | 15.00 | 902.60 | 1.094 | 0.547 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
LGSTORE1 | 9.02 | 30.00 | 1805.20 | 1.009 | 0.000 | 0.000 | 0.000 |
SMSTORE1 | 4.51 | 15.00 | 902.60 | 0.000 | 0.000 | 0.000 | 0.000 |
SMSTORE2 | 3.78 | 15.00 | 902.60 | 1.004 | 0.000 | 0.000 | 0.000 |
SMSTORE3 | 3.78 | 15.00 | 902.60 | 1.004 | 0.000 | 0.000 | 0.000 |
SMSTORE4 | 3.78 | 15.00 | 902.60 | 1.003 | 0.000 | 0.000 | 0.000 |
LGSTORE2 | 13.23 | 30.00 | 1805.20 | 1.007 | 0.000 | 0.000 | 0.000 |
SMSTORE5 | 6.61 | 15.00 | 902.60 | 1.006 | 0.000 | 0.000 | 0.000 |
SMSTORE6 | 6.61 | 15.00 | 902.60 | 1.006 | 0.000 | 0.000 | 0.000 |
SMSTORE7 | 6.61 | 15.00 | 902.60 | 1.006 | 0.000 | 0.000 | 0.000 |
SMSTORE8 | 6.61 | 15.00 | 902.60 | 1.004 | 0.000 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2020-06-03 19:18:56
Surfaces by ClassTotal | Outdoors | |
Wall | 40 | 22 |
Floor | 10 | 10 |
Roof | 10 | 10 |
Internal Mass | 10 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 36 | 36 |
Door | 12 | 12 |
Glass Door | 12 | 12 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 10 |
Conditioned Zones | 10 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 0 |
Defaulted Fields | 0 |
Fields with Defaults | 0 |
Autosized Fields | 0 |
Autosizable Fields | 0 |
Autocalculated Fields | 0 |
Autocalculatable Fields | 0 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2020-06-03 19:18:56
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 2220.25 | 3969.13 | 08-JAN-07:20 | 197558.14 | 10-JUN-15:50 |
Electricity:Building | 837.46 | 2751.13 | 01-JAN-00:10 | 51821.98 | 01-JAN-11:10 |
Electricity:Zone:LGSTORE1 | 211.76 | 576.88 | 01-JAN-00:10 | 10885.83 | 01-JAN-10:10 |
InteriorLights:Electricity | 708.74 | 2301.71 | 01-JAN-00:10 | 43732.45 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:LGSTORE1 | 185.40 | 501.98 | 01-JAN-00:10 | 9537.57 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity | 708.74 | 2301.71 | 01-JAN-00:10 | 43732.45 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE1 | 105.88 | 288.44 | 01-JAN-00:10 | 5442.91 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE1 | 92.70 | 250.99 | 01-JAN-00:10 | 4768.79 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE2 | 68.15 | 234.53 | 01-JAN-00:10 | 4418.69 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE2 | 57.68 | 197.08 | 01-JAN-00:10 | 3744.57 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE3 | 68.15 | 234.53 | 01-JAN-00:10 | 4418.69 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE3 | 57.68 | 197.08 | 01-JAN-00:10 | 3744.57 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE4 | 68.15 | 234.53 | 01-JAN-00:10 | 4418.69 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE4 | 57.68 | 197.08 | 01-JAN-00:10 | 3744.57 | 01-JAN-10:10 |
Electricity:Zone:LGSTORE2 | 105.13 | 394.07 | 01-JAN-00:10 | 7412.39 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:LGSTORE2 | 85.86 | 319.16 | 01-JAN-00:10 | 6064.13 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE5 | 52.56 | 197.03 | 01-JAN-00:10 | 3706.19 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE5 | 42.93 | 159.58 | 01-JAN-00:10 | 3032.07 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE6 | 52.56 | 197.03 | 01-JAN-00:10 | 3706.19 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE6 | 42.93 | 159.58 | 01-JAN-00:10 | 3032.07 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE7 | 52.56 | 197.03 | 01-JAN-00:10 | 3706.19 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE7 | 42.93 | 159.58 | 01-JAN-00:10 | 3032.07 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE8 | 52.56 | 197.03 | 01-JAN-00:10 | 3706.19 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE8 | 42.93 | 159.58 | 01-JAN-00:10 | 3032.07 | 01-JAN-11:10 |
InteriorEquipment:Electricity | 128.72 | 449.42 | 01-JAN-00:10 | 8089.53 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:LGSTORE1 | 26.36 | 74.90 | 01-JAN-00:10 | 1348.26 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity | 128.72 | 449.42 | 01-JAN-00:10 | 8089.53 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE1 | 13.18 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE2 | 10.47 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE3 | 10.47 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE4 | 10.47 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:LGSTORE2 | 19.26 | 74.90 | 01-JAN-00:10 | 1348.26 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE5 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE6 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE7 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE8 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
Electricity:Plant | 58.79 | 1218.00 | 03-JAN-08:10 | 11785.84 | 02-JAN-12:40 |
WaterSystems:Electricity | 58.79 | 1218.00 | 03-JAN-08:10 | 11785.84 | 02-JAN-12:40 |
Water Heater:WaterSystems:Electricity | 58.79 | 1218.00 | 03-JAN-08:10 | 11785.84 | 02-JAN-12:40 |
ElectricityPurchased:Facility | 2220.25 | 3969.13 | 08-JAN-07:20 | 197558.14 | 10-JUN-15:50 |
ElectricityPurchased:Plant | 2220.25 | 3969.13 | 08-JAN-07:20 | 197558.14 | 10-JUN-15:50 |
Cogeneration:ElectricityPurchased | 2220.25 | 3969.13 | 08-JAN-07:20 | 197558.14 | 10-JUN-15:50 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 2220.25 | 3969.13 | 08-JAN-07:20 | 197558.14 | 10-JUN-15:50 |
ElectricityNet:Plant | 2220.25 | 3969.13 | 08-JAN-07:20 | 197558.14 | 10-JUN-15:50 |
Cogeneration:ElectricityNet | 2220.25 | 3969.13 | 08-JAN-07:20 | 197558.14 | 10-JUN-15:50 |
Electricity:HVAC | 1156.95 | 0.00 | 01-JAN-00:10 | 138540.82 | 10-JUN-16:00 |
Fans:Electricity | 352.27 | 0.00 | 01-JAN-00:10 | 20381.82 | 13-JAN-18:00 |
General:Fans:Electricity | 352.27 | 0.00 | 01-JAN-00:10 | 20381.82 | 13-JAN-18:00 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 804.68 | 0.00 | 01-JAN-00:10 | 118159.00 | 10-JUN-16:00 |
ExteriorLights:Electricity | 167.05 | 0.00 | 01-JAN-07:20 | 10625.34 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 167.05 | 0.00 | 01-JAN-07:20 | 10625.34 | 01-JAN-00:10 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Gas:Facility | 3.02 | 0.00 | 01-JAN-00:10 | 94354.47 | 02-JAN-08:10 |
Gas:HVAC | 3.02 | 0.00 | 01-JAN-00:10 | 94354.47 | 02-JAN-08:10 |
Heating:Gas | 3.02 | 0.00 | 01-JAN-00:10 | 94354.47 | 02-JAN-08:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water:Plant | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
WaterSystems:Water | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water Heater:WaterSystems:Water | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
MainsWater:Facility | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
MainsWater:Plant | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
WaterSystems:MainsWater | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water Heater:WaterSystems:MainsWater | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:Facility | 3910.88 | 0.00 | 01-JAN-00:10 | 540895.67 | 01-JUL-14:40 |
EnergyTransfer:Building | 1322.20 | 0.00 | 01-JAN-00:10 | 185766.51 | 12-JUN-14:10 |
EnergyTransfer:Zone:LGSTORE1 | 288.43 | 0.00 | 01-JAN-00:10 | 31795.16 | 08-JUN-16:10 |
Heating:EnergyTransfer | 9.81 | 0.00 | 01-JAN-00:10 | 52672.76 | 10-JUN-17:10 |
Heating:EnergyTransfer:Zone:LGSTORE1 | 0.23 | 0.00 | 01-JAN-00:10 | 3838.64 | 08-APR-07:20 |
Cooling:EnergyTransfer | 1312.39 | 0.00 | 01-JAN-00:10 | 185766.51 | 12-JUN-14:10 |
Cooling:EnergyTransfer:Zone:LGSTORE1 | 288.21 | 0.00 | 01-JAN-00:10 | 31795.16 | 08-JUN-16:10 |
EnergyTransfer:Zone:SMSTORE1 | 144.99 | 0.00 | 01-JAN-00:10 | 15629.59 | 12-JUN-14:00 |
Heating:EnergyTransfer:Zone:SMSTORE1 | 0.11 | 0.00 | 01-JAN-00:10 | 1569.96 | 16-OCT-07:20 |
Cooling:EnergyTransfer:Zone:SMSTORE1 | 144.88 | 0.00 | 01-JAN-00:10 | 15629.59 | 12-JUN-14:00 |
EnergyTransfer:Zone:SMSTORE2 | 107.15 | 0.00 | 01-JAN-00:10 | 15411.18 | 12-JUN-14:00 |
Heating:EnergyTransfer:Zone:SMSTORE2 | 1.78 | 0.00 | 01-JAN-00:10 | 5850.75 | 10-JUN-17:10 |
Cooling:EnergyTransfer:Zone:SMSTORE2 | 105.36 | 0.00 | 01-JAN-00:10 | 15411.18 | 12-JUN-14:00 |
EnergyTransfer:Zone:SMSTORE3 | 106.50 | 0.00 | 01-JAN-00:10 | 15514.80 | 12-JUN-14:00 |
Heating:EnergyTransfer:Zone:SMSTORE3 | 1.79 | 0.00 | 01-JAN-00:10 | 5850.36 | 10-JUN-17:10 |
Cooling:EnergyTransfer:Zone:SMSTORE3 | 104.71 | 0.00 | 01-JAN-00:10 | 15514.80 | 12-JUN-14:00 |
EnergyTransfer:Zone:SMSTORE4 | 104.82 | 0.00 | 01-JAN-00:10 | 15516.81 | 12-JUN-14:00 |
Heating:EnergyTransfer:Zone:SMSTORE4 | 1.84 | 0.00 | 01-JAN-00:10 | 6150.74 | 02-JAN-07:10 |
Cooling:EnergyTransfer:Zone:SMSTORE4 | 102.99 | 0.00 | 01-JAN-00:10 | 15516.81 | 12-JUN-14:00 |
EnergyTransfer:Zone:LGSTORE2 | 183.61 | 0.00 | 01-JAN-00:10 | 29233.45 | 12-JUN-14:10 |
Heating:EnergyTransfer:Zone:LGSTORE2 | 1.26 | 0.00 | 01-JAN-00:10 | 12523.79 | 02-JAN-08:10 |
Cooling:EnergyTransfer:Zone:LGSTORE2 | 182.35 | 0.00 | 01-JAN-00:10 | 29233.45 | 12-JUN-14:10 |
EnergyTransfer:Zone:SMSTORE5 | 95.21 | 0.00 | 01-JAN-00:10 | 15512.51 | 12-JUN-14:10 |
Heating:EnergyTransfer:Zone:SMSTORE5 | 0.66 | 0.00 | 01-JAN-00:10 | 6593.06 | 02-JAN-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE5 | 94.55 | 0.00 | 01-JAN-00:10 | 15512.51 | 12-JUN-14:10 |
EnergyTransfer:Zone:SMSTORE6 | 94.37 | 0.00 | 01-JAN-00:10 | 15458.30 | 12-JUN-14:10 |
Heating:EnergyTransfer:Zone:SMSTORE6 | 0.67 | 0.00 | 01-JAN-00:10 | 6783.74 | 02-JAN-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE6 | 93.70 | 0.00 | 01-JAN-00:10 | 15458.30 | 12-JUN-14:10 |
EnergyTransfer:Zone:SMSTORE7 | 93.74 | 0.00 | 01-JAN-00:10 | 15556.44 | 12-JUN-14:10 |
Heating:EnergyTransfer:Zone:SMSTORE7 | 0.69 | 0.00 | 01-JAN-00:10 | 7728.25 | 02-JAN-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE7 | 93.05 | 0.00 | 01-JAN-00:10 | 15556.44 | 12-JUN-14:10 |
EnergyTransfer:Zone:SMSTORE8 | 103.37 | 0.00 | 01-JAN-00:10 | 17767.26 | 12-JUN-12:40 |
Heating:EnergyTransfer:Zone:SMSTORE8 | 0.77 | 0.00 | 01-JAN-00:10 | 10708.58 | 02-JAN-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE8 | 102.60 | 0.00 | 01-JAN-00:10 | 17767.26 | 12-JUN-12:40 |
EnergyTransfer:HVAC | 2588.68 | 0.00 | 01-JAN-00:10 | 391569.44 | 01-JUL-15:00 |
HeatingCoils:EnergyTransfer | 2.41 | 0.00 | 01-JAN-00:10 | 75282.55 | 02-JAN-08:10 |
CoolingCoils:EnergyTransfer | 2586.27 | 0.00 | 01-JAN-00:10 | 391569.44 | 01-JUL-15:00 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2020-06-03 19:18:56
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
LGSTORE1 | 0.000 | 0.000 | 0.229 | -288.202 | 0.000 | 0.000 | 12.390 | 185.400 | 26.357 | 26.450 | 0.000 | 25.867 | 25.197 | 0.000 | -8.005 | 0.000 | -5.684 | -0.002 |
SMSTORE1 | 0.000 | 0.000 | 0.114 | -144.879 | 0.000 | 0.000 | 6.194 | 92.700 | 13.179 | 13.309 | 0.000 | 14.401 | 11.976 | 0.000 | -4.009 | 0.000 | -2.985 | -0.001 |
SMSTORE2 | 0.000 | 0.000 | 1.783 | -105.361 | 0.000 | 0.000 | 3.721 | 57.682 | 10.467 | 13.107 | 0.000 | 14.172 | 11.529 | 0.000 | -4.055 | 0.000 | -3.045 | -0.002 |
SMSTORE3 | 0.000 | 0.000 | 1.789 | -104.705 | 0.000 | 0.000 | 3.722 | 57.682 | 10.467 | 13.105 | 0.000 | 14.167 | 10.828 | 0.000 | -4.027 | 0.000 | -3.029 | -0.000 |
SMSTORE4 | 0.000 | 0.000 | 1.836 | -102.984 | 0.000 | 0.000 | 3.723 | 57.682 | 10.467 | 13.129 | 0.000 | 14.172 | 8.962 | 0.000 | -3.978 | 0.000 | -3.010 | -0.002 |
LGSTORE2 | 0.000 | 0.000 | 1.264 | -182.347 | 0.000 | 0.000 | 12.785 | 85.864 | 19.261 | 26.412 | 0.000 | 24.916 | 24.867 | 0.000 | -7.701 | 0.000 | -5.323 | -0.003 |
SMSTORE5 | 0.000 | 0.000 | 0.665 | -94.545 | 0.000 | 0.000 | 6.393 | 42.932 | 9.631 | 13.264 | 0.000 | 14.190 | 14.267 | 0.000 | -3.812 | 0.000 | -2.985 | -0.000 |
SMSTORE6 | 0.000 | 0.000 | 0.672 | -93.697 | 0.000 | 0.000 | 6.394 | 42.932 | 9.631 | 13.280 | 0.000 | 14.192 | 13.366 | 0.000 | -3.792 | 0.000 | -2.977 | -0.001 |
SMSTORE7 | 0.000 | 0.000 | 0.688 | -93.049 | 0.000 | 0.000 | 6.396 | 42.932 | 9.631 | 13.284 | 0.000 | 14.192 | 12.640 | 0.000 | -3.758 | 0.000 | -2.956 | -0.001 |
SMSTORE8 | 0.000 | 0.000 | 0.768 | -102.598 | 0.000 | 0.000 | 6.399 | 42.932 | 9.631 | 13.162 | 0.000 | 14.786 | 21.954 | 0.000 | -3.656 | 0.000 | -3.378 | -0.002 |
Total Facility | 0.000 | 0.000 | 9.808 | -1312.366 | 0.000 | 0.000 | 68.118 | 708.738 | 128.721 | 158.503 | 0.000 | 165.056 | 155.585 | 0.000 | -46.793 | 0.000 | -35.370 | -0.013 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
LGSTORE1 | 06-MAY-07:01 | 0.00 | 0.00 | 0.00 | -56099.47 | 0.00 | 0.00 | 0.00 | 501.98 | 74.90 | 378.34 | 0.00 | 257.41 | 54886.84 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 06-MAY-07:01 | 0.00 | 0.00 | 0.00 | -28217.65 | 0.00 | 0.00 | 0.00 | 250.99 | 37.45 | 196.60 | 0.00 | 145.29 | 27587.32 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 06-MAY-06:01 | 0.00 | 0.00 | 0.00 | -27699.35 | 0.00 | 0.00 | 0.00 | 197.08 | 37.45 | 26.14 | 0.00 | 6.31 | 27432.37 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 06-MAY-06:01 | 0.00 | 0.00 | 0.00 | -27702.28 | 0.00 | 0.00 | 0.00 | 197.08 | 37.45 | 23.05 | 0.00 | 6.11 | 27438.58 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 06-MAY-06:01 | 0.00 | 0.00 | 0.00 | -27585.32 | 0.00 | 0.00 | 0.00 | 197.08 | 37.45 | 26.27 | 0.00 | 6.42 | 27318.09 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 30-APR-08:61 | 0.00 | 0.00 | 0.00 | -51233.86 | 0.00 | 0.00 | 0.00 | 319.16 | 74.90 | 408.43 | 0.00 | 42.01 | 50389.35 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 29-MAY-08:61 | 0.00 | 0.00 | 0.00 | -26709.78 | 0.00 | 0.00 | 0.00 | 159.58 | 37.45 | 379.71 | 0.00 | 225.85 | 25907.20 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 29-MAY-08:61 | 0.00 | 0.00 | 0.00 | -26608.59 | 0.00 | 0.00 | 0.00 | 159.58 | 37.45 | 380.58 | 0.00 | 226.62 | 25804.35 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 29-MAY-08:61 | 0.00 | 0.00 | 0.00 | -26649.51 | 0.00 | 0.00 | 0.00 | 159.58 | 37.45 | 380.13 | 0.00 | 227.53 | 25844.81 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 29-MAY-08:61 | 0.00 | 0.00 | 0.00 | -29187.58 | 0.00 | 0.00 | 0.00 | 159.58 | 37.45 | 364.80 | 0.00 | 297.22 | 28328.52 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 06-MAY-07:01 | 0.00 | 0.00 | 0.00 | -259495.21 | 0.00 | 0.00 | 157.59 | 7622.93 | 1460.61 | 2531.10 | 0.00 | 1958.67 | 245764.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
LGSTORE1 | 07-JUN-07:05 | 0.00 | 0.00 | 11285.59 | 0.00 | 0.00 | 0.00 | 69.22 | 501.98 | 74.90 | 757.45 | 0.00 | 942.55 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -13631.69 |
SMSTORE1 | 12-JUN-07:05 | 0.00 | 0.00 | 5908.36 | 0.00 | 0.00 | 0.00 | 35.38 | 250.99 | 37.45 | 439.26 | 0.00 | 492.81 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -7164.26 |
SMSTORE2 | 11-JUN-16:01 | 0.00 | 0.00 | 6778.47 | 0.00 | 0.00 | 0.00 | 52.53 | 1970.82 | 374.52 | 945.82 | 0.00 | 4529.75 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -14651.91 |
SMSTORE3 | 02-JAN-07:03 | 0.00 | 0.00 | 14853.30 | 0.00 | 0.00 | 0.00 | 0.00 | 197.08 | 37.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -549.83 | 0.00 | 0.00 | -14538.00 |
SMSTORE4 | 02-JAN-07:03 | 0.00 | 0.00 | 20063.88 | 0.00 | 0.00 | 0.00 | 0.00 | 197.08 | 37.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -534.62 | 0.00 | 0.00 | -19763.80 |
LGSTORE2 | 01-JAN-09:01 | 0.00 | 0.00 | 66059.87 | 0.00 | 0.00 | 0.00 | 0.00 | 319.16 | 74.90 | 587.82 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -779.07 | -66262.69 |
SMSTORE5 | 01-JAN-09:01 | 0.00 | 0.00 | 34665.73 | 0.00 | 0.00 | 0.00 | 0.00 | 159.58 | 37.45 | 295.58 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -442.84 | -34715.49 |
SMSTORE6 | 01-JAN-09:01 | 0.00 | 0.00 | 34563.64 | 0.00 | 0.00 | 0.00 | 0.00 | 159.58 | 37.45 | 299.04 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -439.20 | -34620.50 |
SMSTORE7 | 01-JAN-09:01 | 0.00 | 0.00 | 34711.63 | 0.00 | 0.00 | 0.00 | 0.00 | 159.58 | 37.45 | 308.50 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -429.03 | -34788.13 |
SMSTORE8 | 01-JAN-09:01 | 0.00 | 0.00 | 38257.24 | 0.00 | 0.00 | 0.00 | 0.00 | 159.58 | 37.45 | 335.72 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -412.23 | -38377.76 |
Total Facility | 01-JAN-09:01 | -3802.09 | 3802.09 | 209864.78 | -3802.09 | 0.00 | 0.00 | 369.90 | 14399.63 | 2471.80 | 3221.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -5254.75 | -221270.74 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2020-06-03 19:18:56
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 3.2248 | 0.0000 | 29.9961 | 1.0000 | 0.5309 | 3.2248 | 0.1646 | 1.0000 | 0.5309 | 0.1646 | ||
PSZ-AC_2:2 | 1.6319 | 0.0000 | 14.9980 | 1.0000 | 0.2655 | 1.6319 | 0.1627 | 1.0000 | 0.2655 | 0.1627 | ||
PSZ-AC_3:3 | 1.5634 | 0.0000 | 14.9980 | 1.0000 | 0.2655 | 1.5634 | 0.1698 | 1.0000 | 0.2655 | 0.1698 | ||
PSZ-AC_4:4 | 1.5601 | 0.0000 | 14.9980 | 1.0000 | 0.2655 | 1.5601 | 0.1701 | 1.0000 | 0.2655 | 0.1701 | ||
PSZ-AC_5:5 | 1.5577 | 0.0000 | 14.9980 | 1.0000 | 0.2655 | 1.5577 | 0.1704 | 1.0000 | 0.2655 | 0.1704 | ||
PSZ-AC_6:6 | 2.8740 | 0.0000 | 29.9961 | 1.0000 | 0.5309 | 2.8740 | 0.1847 | 1.0000 | 0.5309 | 0.1847 | ||
PSZ-AC_7:7 | 1.5147 | 0.0000 | 14.9980 | 1.0000 | 0.2655 | 1.5147 | 0.1753 | 1.0000 | 0.2655 | 0.1753 | ||
PSZ-AC_8:8 | 1.5084 | 0.0000 | 14.9980 | 1.0000 | 0.2655 | 1.5084 | 0.1760 | 1.0000 | 0.2655 | 0.1760 | ||
PSZ-AC_9:9 | 1.5119 | 0.0000 | 14.9980 | 1.0000 | 0.2655 | 1.5119 | 0.1756 | 1.0000 | 0.2655 | 0.1756 | ||
PSZ-AC_10:10 | 1.6751 | 0.0000 | 14.9980 | 1.0000 | 0.2655 | 1.6751 | 0.1585 | 1.0000 | 0.2655 | 0.1585 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 3.2248 | 0.0000 | 29.9961 | 1.0000 | 0.5309 | 3.2248 | 1.0000 | 1.0000 | 0.5309 | 0.1646 | ||
PSZ-AC_2:2 | 1.6319 | 0.0000 | 14.9980 | 1.0000 | 0.2655 | 1.6319 | 1.0000 | 1.0000 | 0.2655 | 0.1627 | ||
PSZ-AC_3:3 | 1.5634 | 0.0000 | 14.9980 | 1.0000 | 0.2655 | 1.5634 | 1.0000 | 1.0000 | 0.2655 | 0.1698 | ||
PSZ-AC_4:4 | 1.5601 | 0.0000 | 14.9980 | 1.0000 | 0.2655 | 1.5601 | 1.0000 | 1.0000 | 0.2655 | 0.1701 | ||
PSZ-AC_5:5 | 1.5577 | 0.0000 | 14.9980 | 1.0000 | 0.2655 | 1.5577 | 1.0000 | 1.0000 | 0.2655 | 0.1704 | ||
PSZ-AC_6:6 | 2.8740 | 0.0000 | 29.9961 | 1.0000 | 0.5309 | 2.8740 | 1.0000 | 1.0000 | 0.5309 | 0.1847 | ||
PSZ-AC_7:7 | 1.5147 | 0.0000 | 14.9980 | 1.0000 | 0.2655 | 1.5147 | 1.0000 | 1.0000 | 0.2655 | 0.1753 | ||
PSZ-AC_8:8 | 1.5084 | 0.0000 | 14.9980 | 1.0000 | 0.2655 | 1.5084 | 1.0000 | 1.0000 | 0.2655 | 0.1760 | ||
PSZ-AC_9:9 | 1.5119 | 0.0000 | 14.9980 | 1.0000 | 0.2655 | 1.5119 | 1.0000 | 1.0000 | 0.2655 | 0.1756 | ||
PSZ-AC_10:10 | 1.6751 | 0.0000 | 14.9980 | 1.0000 | 0.2655 | 1.6751 | 1.0000 | 1.0000 | 0.2655 | 0.1585 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
LGSTORE1 | PSZ-AC_1:1 | 0.000000 | 29.9961 | 0.001524 | 348.39 | 0.5309 | 1.0000 | 0.5309 | 1.000 | 0.5309 |
SMSTORE1 | PSZ-AC_2:2 | 0.000000 | 14.9980 | 0.001524 | 174.19 | 0.2655 | 1.0000 | 0.2655 | 1.000 | 0.2655 |
SMSTORE2 | PSZ-AC_3:3 | 0.000000 | 14.9980 | 0.001524 | 174.19 | 0.2655 | 1.0000 | 0.2655 | 1.000 | 0.2655 |
SMSTORE3 | PSZ-AC_4:4 | 0.000000 | 14.9980 | 0.001524 | 174.19 | 0.2655 | 1.0000 | 0.2655 | 1.000 | 0.2655 |
SMSTORE4 | PSZ-AC_5:5 | 0.000000 | 14.9980 | 0.001524 | 174.19 | 0.2655 | 1.0000 | 0.2655 | 1.000 | 0.2655 |
LGSTORE2 | PSZ-AC_6:6 | 0.000000 | 29.9961 | 0.001524 | 348.39 | 0.5309 | 1.0000 | 0.5309 | 1.000 | 0.5309 |
SMSTORE5 | PSZ-AC_7:7 | 0.000000 | 14.9980 | 0.001524 | 174.19 | 0.2655 | 1.0000 | 0.2655 | 1.000 | 0.2655 |
SMSTORE6 | PSZ-AC_8:8 | 0.000000 | 14.9980 | 0.001524 | 174.19 | 0.2655 | 1.0000 | 0.2655 | 1.000 | 0.2655 |
SMSTORE7 | PSZ-AC_9:9 | 0.000000 | 14.9980 | 0.001524 | 174.19 | 0.2655 | 1.0000 | 0.2655 | 1.000 | 0.2655 |
SMSTORE8 | PSZ-AC_10:10 | 0.000000 | 14.9980 | 0.001524 | 174.19 | 0.2655 | 1.0000 | 0.2655 | 1.000 | 0.2655 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC_1:1 | 0.000000 | 30.00 | 0.001524 | 348.3864 | 0.5309 | 0.5309 | 0.5309 |
PSZ-AC_2:2 | 0.000000 | 15.00 | 0.001524 | 174.1932 | 0.2655 | 0.2655 | 0.2655 |
PSZ-AC_3:3 | 0.000000 | 15.00 | 0.001524 | 174.1932 | 0.2655 | 0.2655 | 0.2655 |
PSZ-AC_4:4 | 0.000000 | 15.00 | 0.001524 | 174.1932 | 0.2655 | 0.2655 | 0.2655 |
PSZ-AC_5:5 | 0.000000 | 15.00 | 0.001524 | 174.1932 | 0.2655 | 0.2655 | 0.2655 |
PSZ-AC_6:6 | 0.000000 | 30.00 | 0.001524 | 348.3864 | 0.5309 | 0.5309 | 0.5309 |
PSZ-AC_7:7 | 0.000000 | 15.00 | 0.001524 | 174.1932 | 0.2655 | 0.2655 | 0.2655 |
PSZ-AC_8:8 | 0.000000 | 15.00 | 0.001524 | 174.1932 | 0.2655 | 0.2655 | 0.2655 |
PSZ-AC_9:9 | 0.000000 | 15.00 | 0.001524 | 174.1932 | 0.2655 | 0.2655 | 0.2655 |
PSZ-AC_10:10 | 0.000000 | 15.00 | 0.001524 | 174.1932 | 0.2655 | 0.2655 | 0.2655 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LGSTORE1 | PSZ-AC_1:1 | 3.2248 | 3.2248 | 3.2248 | 0.5309 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE1 | PSZ-AC_2:2 | 1.6319 | 1.6319 | 1.6319 | 0.2655 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE2 | PSZ-AC_3:3 | 1.5634 | 1.5634 | 1.5634 | 0.2655 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE3 | PSZ-AC_4:4 | 1.5601 | 1.5601 | 1.5601 | 0.2655 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE4 | PSZ-AC_5:5 | 1.5577 | 1.5577 | 1.5577 | 0.2655 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
LGSTORE2 | PSZ-AC_6:6 | 2.8740 | 2.8740 | 2.8740 | 0.5309 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE5 | PSZ-AC_7:7 | 1.5147 | 1.5147 | 1.5147 | 0.2655 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE6 | PSZ-AC_8:8 | 1.5084 | 1.5084 | 1.5084 | 0.2655 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE7 | PSZ-AC_9:9 | 1.5119 | 1.5119 | 1.5119 | 0.2655 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE8 | PSZ-AC_10:10 | 1.6751 | 1.6751 | 1.6751 | 0.2655 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 3.2248 | 3.2248 | 3.2248 | 3.2248 | 0.5309 | 1.0000 |
PSZ-AC_2:2 | 1.6319 | 1.6319 | 1.6319 | 1.6319 | 0.2655 | 1.0000 |
PSZ-AC_3:3 | 1.5634 | 1.5634 | 1.5634 | 1.5634 | 0.2655 | 1.0000 |
PSZ-AC_4:4 | 1.5601 | 1.5601 | 1.5601 | 1.5601 | 0.2655 | 1.0000 |
PSZ-AC_5:5 | 1.5577 | 1.5577 | 1.5577 | 1.5577 | 0.2655 | 1.0000 |
PSZ-AC_6:6 | 2.8740 | 2.8740 | 2.8740 | 2.8740 | 0.5309 | 1.0000 |
PSZ-AC_7:7 | 1.5147 | 1.5147 | 1.5147 | 1.5147 | 0.2655 | 1.0000 |
PSZ-AC_8:8 | 1.5084 | 1.5084 | 1.5084 | 1.5084 | 0.2655 | 1.0000 |
PSZ-AC_9:9 | 1.5119 | 1.5119 | 1.5119 | 1.5119 | 0.2655 | 1.0000 |
PSZ-AC_10:10 | 1.6751 | 1.6751 | 1.6751 | 1.6751 | 0.2655 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LGSTORE1 | PSZ-AC_1:1 | 3.2248 | 3.2248 | 3.2248 | 0.5309 | 0.6298 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE1 | PSZ-AC_2:2 | 1.6319 | 1.6319 | 1.6319 | 0.2655 | 0.6245 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE2 | PSZ-AC_3:3 | 1.5634 | 1.5634 | 1.5634 | 0.2655 | 0.6153 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE3 | PSZ-AC_4:4 | 1.5601 | 1.5601 | 1.5601 | 0.2655 | 0.6091 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE4 | PSZ-AC_5:5 | 1.5577 | 1.5577 | 1.5577 | 0.2655 | 0.5976 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
LGSTORE2 | PSZ-AC_6:6 | 2.8740 | 2.8740 | 2.8740 | 0.5309 | 0.6261 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE5 | PSZ-AC_7:7 | 1.5147 | 1.5147 | 1.5147 | 0.2655 | 0.5803 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE6 | PSZ-AC_8:8 | 1.5084 | 1.5084 | 1.5084 | 0.2655 | 0.5808 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE7 | PSZ-AC_9:9 | 1.5119 | 1.5119 | 1.5119 | 0.2655 | 0.5673 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE8 | PSZ-AC_10:10 | 1.6751 | 1.6751 | 1.6751 | 0.2655 | 0.5020 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 3.2248 | 3.2248 | 3.2248 | 3.2248 | 0.5309 | 1.0000 |
PSZ-AC_2:2 | 1.6319 | 1.6319 | 1.6319 | 1.6319 | 0.2655 | 1.0000 |
PSZ-AC_3:3 | 1.5634 | 1.5634 | 1.5634 | 1.5634 | 0.2655 | 1.0000 |
PSZ-AC_4:4 | 1.5601 | 1.5601 | 1.5601 | 1.5601 | 0.2655 | 1.0000 |
PSZ-AC_5:5 | 1.5577 | 1.5577 | 1.5577 | 1.5577 | 0.2655 | 1.0000 |
PSZ-AC_6:6 | 2.8740 | 2.8740 | 2.8740 | 2.8740 | 0.5309 | 1.0000 |
PSZ-AC_7:7 | 1.5147 | 1.5147 | 1.5147 | 1.5147 | 0.2655 | 1.0000 |
PSZ-AC_8:8 | 1.5084 | 1.5084 | 1.5084 | 1.5084 | 0.2655 | 1.0000 |
PSZ-AC_9:9 | 1.5119 | 1.5119 | 1.5119 | 1.5119 | 0.2655 | 1.0000 |
PSZ-AC_10:10 | 1.6751 | 1.6751 | 1.6751 | 1.6751 | 0.2655 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2020-06-03 19:18:56
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820 |
Total gross floor area [m2] | 2090.32 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
LGSTORE1 | 348.39 | 348.39 | 0.00 | 112.00 |
SMSTORE1 | 174.19 | 174.19 | 0.00 | 112.00 |
SMSTORE2 | 174.19 | 174.19 | 0.00 | 84.29 |
SMSTORE3 | 174.19 | 174.19 | 0.00 | 84.29 |
SMSTORE4 | 174.19 | 174.19 | 0.00 | 84.29 |
LGSTORE2 | 348.39 | 348.39 | 0.00 | 77.29 |
SMSTORE5 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE6 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE7 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE8 | 174.19 | 174.19 | 0.00 | 77.29 |
Totals | 2090.32 | 2090.32 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 9.17 |
Number of hours not met | 9.17 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Fuel Use [GJ] | Additional Fuel Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- Not Subdivided | 0.00 | 0.00 | 3.02 | 94354.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- Not Subdivided | 804.68 | 118159.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 708.74 | 43732.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 167.05 | 10625.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 128.72 | 8089.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 352.27 | 20381.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 58.79 | 11785.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 128.72 | 2220.25 |
Natural Gas | 0.00 | 3.02 |
Additional | 0.00 | 0.00 |
Total | 128.72 | 2223.27 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 339.06 |
Space Heating | 0.00 |
Space Cooling | 384.96 |
Fans (All) | 168.52 |
Service Water Heating | 28.13 |
Receptacle Equipment | 61.58 |
Miscellaneous (All) | 1062.16 |
Subtotal | 1062.16 |
Natural Gas [MJ/m2] | |
Space Heating | 1.45 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 1.45 |
Subtotal | 1.45 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 31.88 |
Space Heating | 0.14 |
Space Cooling | 36.19 |
Fans (All) | 15.84 |
Service Water Heating | 2.64 |
Receptacle Equipment | 5.79 |
Miscellaneous | 7.51 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
TYPE1_OCC_SCH | 1630. | 5840. |
TYPE2_OCC_SCH | 995. | 4429. |
TYPE3_OCC_SCH | 1709. | 4064. |
TYPE1_LIGHT_SCH | 5131. | 8760. |
TYPE2_LIGHT_SCH | 4096. | 8760. |
TYPE3_LIGHT_SCH | 3767. | 8760. |
TYPE1_EQUIP_SCH | 4888. | 8760. |
TYPE2_EQUIP_SCH | 3911. | 8760. |
TYPE3_EQUIP_SCH | 3600. | 8760. |
TYPE1_INFIL_SCH | 4302. | 8760. |
TYPE2_INFIL_SCH | 5164. | 8760. |
TYPE3_INFIL_SCH | 5438. | 8760. |
INFIL_DOOR_OPENING_SCH | 2505. | 4380. |
TYPE1_MINOA_MOTORIZEDDAMPER_SCH | 5579. | 5579. |
TYPE2_MINOA_MOTORIZEDDAMPER_SCH | 4429. | 4429. |
TYPE3_MINOA_MOTORIZEDDAMPER_SCH | 4064. | 4064. |
TYPE1_SWH_SCH | 2063. | 6048. |
TYPE2_SWH_SCH | 1831. | 4429. |
TYPE3_SWH_SCH | 1733. | 4064. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 7118. | 8760. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 5839. | 5839. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 7300. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
TYPE1_HTGSETP_SCH_NO_OPTIMUM | LGSTORE1 DUALSPSCHED | January | 21.11 | 365 | 21.11 | 365 |
TYPE1_CLGSETP_SCH_NO_OPTIMUM | LGSTORE1 DUALSPSCHED | July | 23.89 | 365 | 23.89 | 365 |
TYPE2_HTGSETP_SCH_NO_OPTIMUM | SMSTORE2 DUALSPSCHED | January | 21.11 | 365 | 15.56 | 365 |
TYPE2_CLGSETP_SCH_NO_OPTIMUM | SMSTORE2 DUALSPSCHED | July | 23.89 | 365 | 29.44 | 365 |
TYPE3_HTGSETP_SCH_NO_OPTIMUM | LGSTORE2 DUALSPSCHED | January | 21.11 | 365 | 15.56 | 365 |
TYPE3_CLGSETP_SCH_NO_OPTIMUM | LGSTORE2 DUALSPSCHED | July | 23.89 | 365 | 29.44 | 365 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Meter
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.251344E+10 |
February | 0.000 | 0.171231E+09 |
March | 0.000 | 0.000 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.000 |
December | 0.000 | 0.336949E+09 |
Annual Sum or Average | 0.302162E+10 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.251344E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Meter
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.251344E+10 |
February | 0.000 | 0.171231E+09 |
March | 0.000 | 0.000 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.000 |
December | 0.000 | 0.336949E+09 |
Annual Sum or Average | 0.302162E+10 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.251344E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2006
For: Meter
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.251344E+10 |
February | 0.000 | 0.171231E+09 |
March | 0.000 | 0.000 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.000 |
December | 0.000 | 0.336949E+09 |
Annual Sum or Average | 0.302162E+10 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.251344E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Meter
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.251344E+10 |
February | 0.000 | 0.171231E+09 |
March | 0.000 | 0.000 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.000 |
December | 0.000 | 0.336949E+09 |
Annual Sum or Average | 0.302162E+10 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.251344E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTRIPMALL
For: Meter
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.251344E+10 |
February | 0.000 | 0.171231E+09 |
March | 0.000 | 0.000 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.000 |
December | 0.000 | 0.336949E+09 |
Annual Sum or Average | 0.302162E+10 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.251344E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.251344E+10 |
February | 0.000 | 0.171231E+09 |
March | 0.000 | 0.000 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.000 |
December | 0.000 | 0.336949E+09 |
Annual Sum or Average | 0.302162E+10 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.251344E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.251344E+10 |
February | 0.000 | 0.171231E+09 |
March | 0.000 | 0.000 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.000 |
December | 0.000 | 0.336949E+09 |
Annual Sum or Average | 0.302162E+10 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.251344E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 1B
For: Meter
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.251344E+10 |
February | 0.000 | 0.171231E+09 |
March | 0.000 | 0.000 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.000 |
December | 0.000 | 0.336949E+09 |
Annual Sum or Average | 0.302162E+10 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.251344E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY IND_DELHI_NEWDELHI
For: Meter
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.251344E+10 |
February | 0.000 | 0.171231E+09 |
March | 0.000 | 0.000 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.000 |
December | 0.000 | 0.336949E+09 |
Annual Sum or Average | 0.302162E+10 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.251344E+10 |
Report: ZoneCoolingSummaryMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.104044E+11 | 12067.43 | 12-JAN-15:00 | 23.60 | 14.18 | 0.745859E+09 | 899.04 | 29-JAN-18:00 | 15.00 | 10.77 |
February | 0.129727E+11 | 16321.28 | 22-FEB-15:00 | 27.10 | 16.17 | 0.677214E+09 | 899.08 | 20-FEB-18:40 | 21.40 | 14.04 |
March | 0.206590E+11 | 47516.18 | 30-MAR-07:02 | 21.65 | 17.02 | 0.744897E+09 | 899.10 | 05-MAR-13:50 | 28.68 | 17.15 |
April | 0.277597E+11 | 55661.89 | 08-APR-07:02 | 24.45 | 14.69 | 0.726468E+09 | 899.10 | 14-APR-12:09 | 36.62 | 20.77 |
May | 0.333825E+11 | 56098.66 | 06-MAY-07:01 | 30.00 | 17.73 | 0.747633E+09 | 899.09 | 07-MAY-17:49 | 39.42 | 22.06 |
June | 0.331282E+11 | 53188.15 | 07-JUN-07:01 | 34.92 | 19.60 | 0.722257E+09 | 899.09 | 02-JUN-12:09 | 37.00 | 21.29 |
July | 0.323233E+11 | 45306.05 | 07-JUL-07:01 | 33.33 | 24.38 | 0.753786E+09 | 898.99 | 04-JUL-16:19 | 39.77 | 24.54 |
August | 0.308760E+11 | 40546.01 | 14-AUG-07:01 | 28.90 | 26.43 | 0.743244E+09 | 898.94 | 06-AUG-16:19 | 36.20 | 26.30 |
September | 0.282599E+11 | 45311.66 | 26-SEP-07:01 | 25.87 | 19.86 | 0.728347E+09 | 898.95 | 24-SEP-16:30 | 34.45 | 25.39 |
October | 0.266956E+11 | 51705.63 | 23-OCT-07:02 | 20.23 | 14.64 | 0.751792E+09 | 899.13 | 08-OCT-16:10 | 31.85 | 19.34 |
November | 0.193417E+11 | 33955.27 | 09-NOV-08:62 | 19.90 | 16.69 | 0.726781E+09 | 899.09 | 12-NOV-18:49 | 23.47 | 14.78 |
December | 0.124022E+11 | 14015.50 | 02-DEC-14:00 | 24.10 | 13.12 | 0.752727E+09 | 899.05 | 24-DEC-17:49 | 19.20 | 12.79 |
Annual Sum or Average | 0.288205E+12 | 0.882100E+10 | ||||||||
Minimum of Months | 0.104044E+11 | 12067.43 | 19.90 | 13.12 | 0.677214E+09 | 898.94 | 15.00 | 10.77 | ||
Maximum of Months | 0.333825E+11 | 56098.66 | 34.92 | 26.43 | 0.753786E+09 | 899.13 | 39.77 | 26.30 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.534631E+10 | 6213.79 | 12-JAN-14:50 | 23.55 | 14.14 | 0.373911E+09 | 449.53 | 07-JAN-13:50 | 20.82 | 13.26 |
February | 0.681346E+10 | 8797.79 | 25-FEB-08:63 | 18.73 | 15.94 | 0.338833E+09 | 449.54 | 20-FEB-18:19 | 22.20 | 14.15 |
March | 0.107247E+11 | 24922.11 | 30-MAR-07:02 | 21.65 | 17.02 | 0.372479E+09 | 449.55 | 05-MAR-13:20 | 28.33 | 17.01 |
April | 0.140564E+11 | 28157.58 | 08-APR-07:02 | 24.45 | 14.69 | 0.363240E+09 | 449.56 | 30-APR-17:00 | 35.30 | 17.36 |
May | 0.167256E+11 | 28217.22 | 06-MAY-07:01 | 30.00 | 17.73 | 0.373813E+09 | 449.55 | 29-MAY-17:19 | 40.67 | 21.27 |
June | 0.164519E+11 | 26460.45 | 07-JUN-07:01 | 34.92 | 19.60 | 0.361117E+09 | 449.54 | 02-JUN-12:09 | 37.00 | 21.29 |
July | 0.160118E+11 | 23674.42 | 07-JUL-07:01 | 33.33 | 24.38 | 0.376876E+09 | 449.49 | 04-JUL-16:19 | 39.77 | 24.54 |
August | 0.152241E+11 | 22178.63 | 14-AUG-07:01 | 28.90 | 26.43 | 0.371603E+09 | 449.47 | 06-AUG-16:19 | 36.20 | 26.30 |
September | 0.139775E+11 | 24610.86 | 26-SEP-07:01 | 25.87 | 19.86 | 0.364161E+09 | 449.47 | 24-SEP-16:30 | 34.45 | 25.39 |
October | 0.133582E+11 | 26867.77 | 25-OCT-07:02 | 20.13 | 15.93 | 0.375894E+09 | 449.55 | 01-OCT-17:10 | 34.07 | 20.25 |
November | 0.982352E+10 | 17501.53 | 09-NOV-08:62 | 19.90 | 16.69 | 0.363407E+09 | 449.54 | 03-NOV-12:30 | 27.15 | 16.22 |
December | 0.636698E+10 | 7286.21 | 02-DEC-14:00 | 24.10 | 13.12 | 0.376815E+09 | 449.52 | 24-DEC-17:40 | 19.50 | 12.89 |
Annual Sum or Average | 0.144880E+12 | 0.441215E+10 | ||||||||
Minimum of Months | 0.534631E+10 | 6213.79 | 18.73 | 13.12 | 0.338833E+09 | 449.47 | 19.50 | 12.89 | ||
Maximum of Months | 0.167256E+11 | 28217.22 | 34.92 | 26.43 | 0.376876E+09 | 449.56 | 40.67 | 26.30 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.308977E+10 | 5240.90 | 12-JAN-14:50 | 23.55 | 14.14 | 0.219913E+09 | 449.51 | 28-JAN-13:00 | 18.10 | 11.35 |
February | 0.434834E+10 | 7616.16 | 22-FEB-14:00 | 27.00 | 16.30 | 0.202408E+09 | 449.49 | 04-FEB-13:09 | 22.38 | 12.53 |
March | 0.756290E+10 | 24397.00 | 29-MAR-06:02 | 21.15 | 17.30 | 0.230343E+09 | 449.53 | 04-MAR-13:09 | 26.57 | 15.78 |
April | 0.104484E+11 | 27644.60 | 08-APR-06:02 | 23.28 | 14.20 | 0.219887E+09 | 449.52 | 22-APR-12:00 | 32.80 | 19.08 |
May | 0.128908E+11 | 27698.73 | 06-MAY-06:01 | 29.38 | 17.54 | 0.228247E+09 | 449.48 | 27-MAY-12:09 | 39.90 | 20.27 |
June | 0.127117E+11 | 25437.62 | 12-JUN-06:01 | 34.87 | 19.37 | 0.223358E+09 | 449.51 | 03-JUN-12:39 | 39.43 | 23.02 |
July | 0.119447E+11 | 19907.19 | 05-JUL-06:01 | 33.02 | 24.49 | 0.224867E+09 | 449.39 | 01-JUL-12:09 | 37.90 | 28.06 |
August | 0.115234E+11 | 17359.77 | 03-AUG-06:01 | 28.43 | 23.35 | 0.230921E+09 | 449.35 | 05-AUG-12:09 | 35.03 | 26.47 |
September | 0.103028E+11 | 20956.26 | 27-SEP-06:01 | 23.70 | 20.39 | 0.219742E+09 | 449.42 | 09-SEP-12:09 | 27.27 | 25.68 |
October | 0.976801E+10 | 26298.44 | 23-OCT-06:02 | 19.08 | 14.20 | 0.224718E+09 | 449.48 | 21-OCT-12:09 | 29.33 | 18.35 |
November | 0.686812E+10 | 10718.39 | 09-NOV-07:03 | 18.42 | 16.26 | 0.216505E+09 | 449.53 | 04-NOV-12:30 | 29.55 | 17.19 |
December | 0.390492E+10 | 6442.79 | 02-DEC-14:00 | 24.10 | 13.12 | 0.221596E+09 | 449.50 | 23-DEC-13:00 | 20.00 | 12.28 |
Annual Sum or Average | 0.105364E+12 | 0.266250E+10 | ||||||||
Minimum of Months | 0.308977E+10 | 5240.90 | 18.42 | 13.12 | 0.202408E+09 | 449.35 | 18.10 | 11.35 | ||
Maximum of Months | 0.128908E+11 | 27698.73 | 34.87 | 24.49 | 0.230921E+09 | 449.53 | 39.90 | 28.06 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.283322E+10 | 5052.13 | 12-JAN-14:50 | 23.55 | 14.14 | 0.219202E+09 | 449.51 | 28-JAN-13:00 | 18.10 | 11.35 |
February | 0.418347E+10 | 7491.74 | 22-FEB-14:00 | 27.00 | 16.30 | 0.202247E+09 | 449.49 | 11-FEB-13:09 | 20.65 | 13.77 |
March | 0.747405E+10 | 24347.56 | 29-MAR-06:02 | 21.15 | 17.30 | 0.230328E+09 | 449.53 | 04-MAR-13:09 | 26.57 | 15.78 |
April | 0.104479E+11 | 27608.11 | 08-APR-06:02 | 23.28 | 14.20 | 0.219884E+09 | 449.52 | 22-APR-12:00 | 32.80 | 19.08 |
May | 0.129479E+11 | 27701.66 | 06-MAY-06:01 | 29.38 | 17.54 | 0.228246E+09 | 449.48 | 27-MAY-12:09 | 39.90 | 20.27 |
June | 0.127601E+11 | 25592.05 | 12-JUN-06:01 | 34.87 | 19.37 | 0.223356E+09 | 449.51 | 03-JUN-12:39 | 39.43 | 23.02 |
July | 0.120065E+11 | 20146.81 | 05-JUL-06:01 | 33.02 | 24.49 | 0.224866E+09 | 449.39 | 01-JUL-12:09 | 37.90 | 28.06 |
August | 0.115466E+11 | 17393.86 | 03-AUG-06:01 | 28.43 | 23.35 | 0.230919E+09 | 449.35 | 05-AUG-12:09 | 35.03 | 26.47 |
September | 0.103096E+11 | 20961.86 | 27-SEP-06:01 | 23.70 | 20.39 | 0.219739E+09 | 449.43 | 09-SEP-12:09 | 27.27 | 25.68 |
October | 0.974884E+10 | 26301.63 | 23-OCT-06:02 | 19.08 | 14.20 | 0.224713E+09 | 449.48 | 21-OCT-12:09 | 29.33 | 18.35 |
November | 0.675294E+10 | 10314.40 | 09-NOV-07:03 | 18.42 | 16.26 | 0.216478E+09 | 449.53 | 04-NOV-12:30 | 29.55 | 17.19 |
December | 0.369676E+10 | 6292.49 | 02-DEC-14:00 | 24.10 | 13.12 | 0.221282E+09 | 449.50 | 23-DEC-13:00 | 20.00 | 12.28 |
Annual Sum or Average | 0.104708E+12 | 0.266126E+10 | ||||||||
Minimum of Months | 0.283322E+10 | 5052.13 | 18.42 | 13.12 | 0.202247E+09 | 449.35 | 18.10 | 11.35 | ||
Maximum of Months | 0.129479E+11 | 27701.66 | 34.87 | 24.49 | 0.230919E+09 | 449.53 | 39.90 | 28.06 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.261138E+10 | 4879.52 | 12-JAN-14:50 | 23.55 | 14.14 | 0.218561E+09 | 449.51 | 28-JAN-13:00 | 18.10 | 11.35 |
February | 0.400632E+10 | 7352.67 | 22-FEB-14:00 | 27.00 | 16.30 | 0.202062E+09 | 449.49 | 11-FEB-13:09 | 20.65 | 13.77 |
March | 0.729555E+10 | 24181.08 | 29-MAR-06:02 | 21.15 | 17.30 | 0.230303E+09 | 449.53 | 04-MAR-13:09 | 26.57 | 15.78 |
April | 0.103132E+11 | 27511.41 | 08-APR-06:02 | 23.28 | 14.20 | 0.219872E+09 | 449.50 | 29-APR-12:09 | 37.25 | 19.97 |
May | 0.128470E+11 | 27584.70 | 06-MAY-06:01 | 29.38 | 17.54 | 0.228238E+09 | 449.48 | 27-MAY-12:09 | 39.90 | 20.27 |
June | 0.126601E+11 | 25545.00 | 12-JUN-06:01 | 34.87 | 19.37 | 0.223349E+09 | 449.51 | 03-JUN-12:39 | 39.43 | 23.02 |
July | 0.119178E+11 | 20076.85 | 05-JUL-06:01 | 33.02 | 24.49 | 0.224857E+09 | 449.39 | 01-JUL-12:09 | 37.90 | 28.06 |
August | 0.114364E+11 | 17188.24 | 03-AUG-06:01 | 28.43 | 23.35 | 0.230908E+09 | 449.35 | 05-AUG-12:09 | 35.03 | 26.47 |
September | 0.101978E+11 | 20808.71 | 27-SEP-06:01 | 23.70 | 20.39 | 0.219728E+09 | 449.43 | 09-SEP-12:09 | 27.27 | 25.68 |
October | 0.961523E+10 | 26196.71 | 23-OCT-06:02 | 19.08 | 14.20 | 0.224701E+09 | 449.48 | 21-OCT-12:09 | 29.33 | 18.35 |
November | 0.658543E+10 | 9422.46 | 04-NOV-14:00 | 30.30 | 17.14 | 0.216447E+09 | 449.53 | 04-NOV-12:30 | 29.55 | 17.19 |
December | 0.350014E+10 | 6153.16 | 02-DEC-14:00 | 24.10 | 13.12 | 0.220980E+09 | 449.50 | 23-DEC-13:00 | 20.00 | 12.28 |
Annual Sum or Average | 0.102986E+12 | 0.266001E+10 | ||||||||
Minimum of Months | 0.261138E+10 | 4879.52 | 19.08 | 13.12 | 0.202062E+09 | 449.35 | 18.10 | 11.35 | ||
Maximum of Months | 0.128470E+11 | 27584.70 | 34.87 | 24.49 | 0.230908E+09 | 449.53 | 39.90 | 28.06 |
Report: ZoneCoolingSummaryMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.420509E+10 | 8683.74 | 12-JAN-15:10 | 23.55 | 14.23 | 0.746883E+09 | 1198.69 | 28-JAN-15:09 | 18.37 | 11.44 |
February | 0.679420E+10 | 13346.48 | 22-FEB-14:00 | 27.00 | 16.30 | 0.692376E+09 | 1198.65 | 11-FEB-15:00 | 21.20 | 14.71 |
March | 0.128994E+11 | 43498.74 | 30-MAR-07:02 | 21.65 | 17.02 | 0.789369E+09 | 1198.74 | 04-MAR-15:00 | 26.70 | 15.70 |
April | 0.183668E+11 | 51238.44 | 30-APR-08:61 | 26.15 | 14.11 | 0.753134E+09 | 1198.76 | 29-APR-14:00 | 32.00 | 18.74 |
May | 0.230251E+11 | 51230.06 | 29-MAY-08:61 | 32.12 | 19.76 | 0.778757E+09 | 1198.60 | 06-MAY-14:00 | 41.70 | 19.93 |
June | 0.227348E+11 | 47724.30 | 12-JUN-07:01 | 35.90 | 20.10 | 0.763488E+09 | 1198.67 | 03-JUN-14:09 | 40.38 | 22.59 |
July | 0.212668E+11 | 40214.54 | 07-JUL-07:01 | 33.33 | 24.38 | 0.768333E+09 | 1198.32 | 22-JUL-14:09 | 29.58 | 26.97 |
August | 0.204656E+11 | 35627.88 | 08-AUG-07:01 | 30.50 | 24.41 | 0.789996E+09 | 1198.34 | 19-AUG-14:00 | 27.10 | 25.89 |
September | 0.181196E+11 | 40734.96 | 27-SEP-07:02 | 24.98 | 20.38 | 0.752856E+09 | 1198.46 | 09-SEP-14:09 | 26.78 | 25.72 |
October | 0.171716E+11 | 48379.53 | 23-OCT-07:02 | 20.23 | 14.64 | 0.766452E+09 | 1198.59 | 28-OCT-14:00 | 29.30 | 18.42 |
November | 0.115359E+11 | 24650.57 | 09-NOV-08:62 | 19.90 | 16.69 | 0.737014E+09 | 1198.75 | 04-NOV-14:00 | 30.20 | 17.53 |
December | 0.576544E+10 | 10972.43 | 02-DEC-14:10 | 24.07 | 13.13 | 0.757910E+09 | 1198.69 | 23-DEC-15:39 | 19.57 | 12.18 |
Annual Sum or Average | 0.182350E+12 | 0.909657E+10 | ||||||||
Minimum of Months | 0.420509E+10 | 8683.74 | 19.90 | 13.13 | 0.692376E+09 | 1198.32 | 18.37 | 11.44 | ||
Maximum of Months | 0.230251E+11 | 51238.44 | 35.90 | 24.41 | 0.789996E+09 | 1198.76 | 41.70 | 26.97 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.200293E+10 | 4456.37 | 12-JAN-15:10 | 23.55 | 14.23 | 0.373038E+09 | 599.34 | 28-JAN-15:09 | 18.37 | 11.44 |
February | 0.341724E+10 | 6940.60 | 22-FEB-14:00 | 27.00 | 16.30 | 0.346115E+09 | 599.32 | 11-FEB-15:00 | 21.20 | 14.71 |
March | 0.665470E+10 | 21741.45 | 30-MAR-07:02 | 21.65 | 17.02 | 0.394678E+09 | 599.37 | 04-MAR-15:00 | 26.70 | 15.70 |
April | 0.958056E+10 | 26669.70 | 30-APR-08:61 | 26.15 | 14.11 | 0.376554E+09 | 599.38 | 29-APR-14:00 | 32.00 | 18.74 |
May | 0.120649E+11 | 26708.80 | 29-MAY-08:61 | 32.12 | 19.76 | 0.389370E+09 | 599.30 | 06-MAY-14:00 | 41.70 | 19.93 |
June | 0.119015E+11 | 24888.80 | 12-JUN-07:01 | 35.90 | 20.10 | 0.381734E+09 | 599.33 | 03-JUN-14:09 | 40.38 | 22.59 |
July | 0.111113E+11 | 20967.88 | 07-JUL-07:01 | 33.33 | 24.38 | 0.384148E+09 | 599.15 | 22-JUL-14:09 | 29.58 | 26.97 |
August | 0.106673E+11 | 18568.63 | 08-AUG-07:01 | 30.50 | 24.41 | 0.394980E+09 | 599.16 | 19-AUG-14:00 | 27.10 | 25.89 |
September | 0.944190E+10 | 21193.65 | 27-SEP-07:02 | 24.98 | 20.38 | 0.376408E+09 | 599.22 | 09-SEP-14:09 | 26.78 | 25.72 |
October | 0.892745E+10 | 25175.93 | 23-OCT-07:02 | 20.23 | 14.64 | 0.383215E+09 | 599.29 | 28-OCT-14:00 | 29.30 | 18.42 |
November | 0.593411E+10 | 11317.19 | 09-NOV-08:62 | 19.90 | 16.69 | 0.368504E+09 | 599.37 | 04-NOV-14:00 | 30.20 | 17.53 |
December | 0.284269E+10 | 5654.57 | 02-DEC-14:10 | 24.07 | 13.13 | 0.378807E+09 | 599.34 | 23-DEC-15:39 | 19.57 | 12.18 |
Annual Sum or Average | 0.945467E+11 | 0.454755E+10 | ||||||||
Minimum of Months | 0.200293E+10 | 4456.37 | 19.90 | 13.13 | 0.346115E+09 | 599.15 | 18.37 | 11.44 | ||
Maximum of Months | 0.120649E+11 | 26708.80 | 35.90 | 24.41 | 0.394980E+09 | 599.38 | 41.70 | 26.97 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.193668E+10 | 4383.23 | 12-JAN-15:10 | 23.55 | 14.23 | 0.372577E+09 | 599.34 | 28-JAN-15:09 | 18.37 | 11.44 |
February | 0.334527E+10 | 6866.41 | 22-FEB-14:00 | 27.00 | 16.30 | 0.345980E+09 | 599.32 | 11-FEB-15:00 | 21.20 | 14.71 |
March | 0.657077E+10 | 21074.37 | 30-MAR-07:02 | 21.65 | 17.02 | 0.394666E+09 | 599.37 | 04-MAR-15:00 | 26.70 | 15.70 |
April | 0.950348E+10 | 26540.66 | 30-APR-08:61 | 26.15 | 14.11 | 0.376550E+09 | 599.38 | 29-APR-14:00 | 32.00 | 18.74 |
May | 0.119894E+11 | 26607.60 | 29-MAY-08:61 | 32.12 | 19.76 | 0.389369E+09 | 599.30 | 06-MAY-14:00 | 41.70 | 19.93 |
June | 0.118282E+11 | 24780.40 | 12-JUN-07:01 | 35.90 | 20.10 | 0.381732E+09 | 599.33 | 03-JUN-14:09 | 40.38 | 22.59 |
July | 0.110455E+11 | 20842.48 | 07-JUL-07:01 | 33.33 | 24.38 | 0.384146E+09 | 599.15 | 22-JUL-14:09 | 29.58 | 26.97 |
August | 0.105995E+11 | 18460.50 | 08-AUG-07:01 | 30.50 | 24.41 | 0.394978E+09 | 599.16 | 19-AUG-14:00 | 27.10 | 25.89 |
September | 0.937939E+10 | 21076.53 | 27-SEP-07:02 | 24.98 | 20.38 | 0.376404E+09 | 599.22 | 09-SEP-14:09 | 26.78 | 25.72 |
October | 0.885957E+10 | 25067.23 | 23-OCT-07:02 | 20.23 | 14.64 | 0.383211E+09 | 599.29 | 28-OCT-14:00 | 29.30 | 18.42 |
November | 0.586459E+10 | 10873.83 | 09-NOV-08:62 | 19.90 | 16.69 | 0.368493E+09 | 599.37 | 04-NOV-14:00 | 30.20 | 17.53 |
December | 0.277668E+10 | 5590.38 | 02-DEC-14:10 | 24.07 | 13.13 | 0.378587E+09 | 599.34 | 23-DEC-15:39 | 19.57 | 12.18 |
Annual Sum or Average | 0.936991E+11 | 0.454669E+10 | ||||||||
Minimum of Months | 0.193668E+10 | 4383.23 | 19.90 | 13.13 | 0.345980E+09 | 599.15 | 18.37 | 11.44 | ||
Maximum of Months | 0.119894E+11 | 26607.60 | 35.90 | 24.41 | 0.394978E+09 | 599.38 | 41.70 | 26.97 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.177071E+10 | 4224.42 | 12-JAN-15:10 | 23.55 | 14.23 | 0.371441E+09 | 599.34 | 28-JAN-15:09 | 18.37 | 11.44 |
February | 0.317276E+10 | 6744.44 | 22-FEB-14:00 | 27.00 | 16.30 | 0.345572E+09 | 599.32 | 11-FEB-15:00 | 21.20 | 14.71 |
March | 0.641552E+10 | 20537.53 | 11-MAR-08:62 | 24.43 | 17.40 | 0.394630E+09 | 599.37 | 04-MAR-15:00 | 26.70 | 15.70 |
April | 0.945246E+10 | 26522.56 | 30-APR-08:61 | 26.15 | 14.11 | 0.376548E+09 | 599.38 | 29-APR-14:00 | 32.00 | 18.74 |
May | 0.120051E+11 | 26648.52 | 29-MAY-08:61 | 32.12 | 19.76 | 0.389369E+09 | 599.30 | 06-MAY-14:00 | 41.70 | 19.93 |
June | 0.118631E+11 | 24868.65 | 12-JUN-07:01 | 35.90 | 20.10 | 0.381732E+09 | 599.33 | 03-JUN-14:09 | 40.38 | 22.59 |
July | 0.110975E+11 | 20928.59 | 07-JUL-07:01 | 33.33 | 24.38 | 0.384147E+09 | 599.15 | 22-JUL-14:09 | 29.58 | 26.97 |
August | 0.106511E+11 | 18542.62 | 08-AUG-07:01 | 30.50 | 24.41 | 0.394979E+09 | 599.16 | 19-AUG-14:00 | 27.10 | 25.89 |
September | 0.940980E+10 | 21113.39 | 27-SEP-07:02 | 24.98 | 20.38 | 0.376405E+09 | 599.22 | 09-SEP-14:09 | 26.78 | 25.72 |
October | 0.884166E+10 | 25071.76 | 23-OCT-07:02 | 20.23 | 14.64 | 0.383210E+09 | 599.29 | 28-OCT-14:00 | 29.30 | 18.42 |
November | 0.575757E+10 | 9731.10 | 09-NOV-08:62 | 19.90 | 16.69 | 0.368465E+09 | 599.37 | 04-NOV-14:00 | 30.20 | 17.53 |
December | 0.261375E+10 | 5460.37 | 02-DEC-14:10 | 24.07 | 13.13 | 0.378034E+09 | 599.34 | 23-DEC-15:39 | 19.57 | 12.18 |
Annual Sum or Average | 0.930511E+11 | 0.454453E+10 | ||||||||
Minimum of Months | 0.177071E+10 | 4224.42 | 19.90 | 13.13 | 0.345572E+09 | 599.15 | 18.37 | 11.44 | ||
Maximum of Months | 0.120051E+11 | 26648.52 | 35.90 | 24.41 | 0.394979E+09 | 599.38 | 41.70 | 26.97 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.153540E+10 | 4235.07 | 12-JAN-15:10 | 23.55 | 14.23 | 0.370543E+09 | 599.34 | 28-JAN-15:09 | 18.37 | 11.44 |
February | 0.304377E+10 | 7182.68 | 22-FEB-14:00 | 27.00 | 16.30 | 0.344582E+09 | 599.32 | 11-FEB-15:00 | 21.20 | 14.71 |
March | 0.661936E+10 | 16399.09 | 11-MAR-08:62 | 24.43 | 17.40 | 0.394543E+09 | 599.36 | 04-MAR-15:00 | 26.70 | 15.70 |
April | 0.104129E+11 | 28713.49 | 30-APR-08:61 | 26.15 | 14.11 | 0.376580E+09 | 599.38 | 29-APR-14:00 | 32.00 | 18.74 |
May | 0.135386E+11 | 29187.26 | 29-MAY-08:61 | 32.12 | 19.76 | 0.389387E+09 | 599.30 | 06-MAY-14:00 | 41.70 | 19.93 |
June | 0.134120E+11 | 27947.34 | 12-JUN-07:01 | 35.90 | 20.10 | 0.381750E+09 | 599.32 | 03-JUN-14:09 | 40.38 | 22.59 |
July | 0.126520E+11 | 22764.45 | 07-JUL-07:01 | 33.33 | 24.38 | 0.384190E+09 | 599.16 | 22-JUL-14:09 | 29.58 | 26.97 |
August | 0.122028E+11 | 19751.62 | 15-AUG-07:01 | 27.52 | 25.69 | 0.395019E+09 | 599.15 | 19-AUG-14:00 | 27.10 | 25.89 |
September | 0.107119E+11 | 23112.52 | 27-SEP-07:02 | 24.98 | 20.38 | 0.376465E+09 | 599.23 | 09-SEP-14:09 | 26.78 | 25.72 |
October | 0.988876E+10 | 25687.76 | 02-OCT-07:01 | 24.92 | 18.37 | 0.383273E+09 | 599.29 | 28-OCT-14:00 | 29.30 | 18.42 |
November | 0.611909E+10 | 9631.90 | 04-NOV-13:50 | 30.27 | 17.16 | 0.368446E+09 | 599.37 | 04-NOV-14:00 | 30.20 | 17.53 |
December | 0.246435E+10 | 5671.36 | 01-DEC-14:00 | 23.50 | 13.04 | 0.377443E+09 | 599.34 | 23-DEC-15:50 | 19.33 | 12.10 |
Annual Sum or Average | 0.102601E+12 | 0.454222E+10 | ||||||||
Minimum of Months | 0.153540E+10 | 4235.07 | 23.50 | 13.04 | 0.344582E+09 | 599.15 | 18.37 | 11.44 | ||
Maximum of Months | 0.135386E+11 | 29187.26 | 35.90 | 25.69 | 0.395019E+09 | 599.38 | 41.70 | 26.97 |
Report: ZoneHeatingSummaryMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 1488069.28 | 2709.50 | 02-JAN-08:05 | 7.38 |
February | 554598.78 | 1180.99 | 25-FEB-08:07 | 18.73 |
March | 22517959.19 | 5945.29 | 11-MAR-08:04 | 24.43 |
April | 57734068.27 | 9183.21 | 28-APR-07:04 | 29.48 |
May | 26275420.72 | 10822.97 | 01-MAY-07:04 | 33.43 |
June | 20959888.31 | 11286.46 | 07-JUN-07:05 | 34.92 |
July | 11934561.67 | 8846.74 | 04-JUL-07:06 | 31.77 |
August | 16772905.66 | 7872.50 | 09-AUG-07:06 | 30.30 |
September | 23535071.76 | 7402.29 | 22-SEP-07:05 | 28.37 |
October | 43229774.16 | 6730.51 | 04-OCT-07:04 | 26.28 |
November | 3927533.54 | 2969.97 | 09-NOV-08:05 | 19.90 |
December | 103521.82 | 345.07 | 06-DEC-09:15 | 19.50 |
Annual Sum or Average | 0.229033E+09 | |||
Minimum of Months | 103521.82 | 345.07 | 7.38 | |
Maximum of Months | 57734068.27 | 11286.46 | 34.92 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 53421.79 | 623.25 | 03-JAN-08:09 | 6.40 |
February | 338849.95 | 784.89 | 25-FEB-08:07 | 18.73 |
March | 12404856.61 | 3119.31 | 11-MAR-08:04 | 24.43 |
April | 24977272.94 | 4699.29 | 27-APR-07:04 | 30.20 |
May | 13084113.34 | 5390.05 | 01-MAY-07:04 | 33.43 |
June | 10185995.49 | 5908.92 | 12-JUN-07:05 | 35.90 |
July | 7971441.36 | 5131.39 | 07-JUL-07:05 | 33.33 |
August | 9281143.07 | 4240.25 | 07-AUG-07:05 | 30.33 |
September | 10693068.36 | 3776.35 | 12-SEP-07:04 | 27.77 |
October | 22784173.50 | 3401.46 | 04-OCT-07:04 | 26.28 |
November | 2206754.54 | 1561.93 | 09-NOV-08:05 | 19.90 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 12.50 |
Annual Sum or Average | 0.113981E+09 | |||
Minimum of Months | 0.00 | 0.00 | 6.40 | |
Maximum of Months | 24977272.94 | 5908.92 | 35.90 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 7432373.38 | 6561.66 | 02-JAN-07:03 | 6.78 |
February | 7840092.92 | 1109.32 | 20-FEB-17:25 | 23.80 |
March | 89117162.29 | 3123.45 | 28-MAR-19:12 | 30.40 |
April | 0.261676E+09 | 5522.03 | 16-APR-16:01 | 39.13 |
May | 0.285986E+09 | 6450.03 | 07-MAY-16:01 | 42.17 |
June | 0.282994E+09 | 6778.27 | 11-JUN-16:01 | 43.35 |
July | 0.243597E+09 | 5980.54 | 02-JUL-16:01 | 40.38 |
August | 0.223089E+09 | 4724.18 | 06-AUG-16:01 | 36.25 |
September | 0.213938E+09 | 4193.35 | 24-SEP-16:01 | 34.68 |
October | 0.142792E+09 | 4328.42 | 01-OCT-16:01 | 35.32 |
November | 24175310.71 | 2152.71 | 05-NOV-16:12 | 27.37 |
December | 211236.92 | 108.11 | 24-DEC-17:50 | 19.20 |
Annual Sum or Average | 0.178285E+10 | |||
Minimum of Months | 211236.92 | 108.11 | 6.78 | |
Maximum of Months | 0.285986E+09 | 6778.27 | 43.35 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 20706054.01 | 14854.52 | 02-JAN-07:03 | 6.78 |
February | 8186258.58 | 1116.87 | 20-FEB-17:25 | 23.80 |
March | 89612401.81 | 3121.76 | 28-MAR-19:12 | 30.40 |
April | 0.261098E+09 | 5520.60 | 16-APR-16:01 | 39.13 |
May | 0.284097E+09 | 6447.25 | 07-MAY-16:01 | 42.17 |
June | 0.279138E+09 | 6774.40 | 11-JUN-16:01 | 43.35 |
July | 0.242323E+09 | 5977.56 | 02-JUL-16:01 | 40.38 |
August | 0.222781E+09 | 4721.64 | 06-AUG-16:01 | 36.25 |
September | 0.213659E+09 | 4191.85 | 24-SEP-16:01 | 34.68 |
October | 0.142333E+09 | 4327.48 | 01-OCT-16:01 | 35.32 |
November | 24449846.59 | 2155.18 | 05-NOV-16:12 | 27.37 |
December | 328827.28 | 148.86 | 24-DEC-17:05 | 20.40 |
Annual Sum or Average | 0.178871E+10 | |||
Minimum of Months | 328827.28 | 148.86 | 6.78 | |
Maximum of Months | 0.284097E+09 | 14854.52 | 43.35 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 33708765.78 | 20065.53 | 02-JAN-07:03 | 6.78 |
February | 8605042.09 | 1124.78 | 20-FEB-17:25 | 23.80 |
March | 91508206.23 | 3127.71 | 28-MAR-19:12 | 30.40 |
April | 0.265252E+09 | 5522.79 | 16-APR-16:01 | 39.13 |
May | 0.292252E+09 | 6448.36 | 07-MAY-16:01 | 42.17 |
June | 0.286794E+09 | 6775.13 | 11-JUN-16:01 | 43.35 |
July | 0.246089E+09 | 5978.42 | 02-JUL-16:01 | 40.38 |
August | 0.225537E+09 | 4722.83 | 06-AUG-16:01 | 36.25 |
September | 0.215559E+09 | 4194.14 | 24-SEP-16:01 | 34.68 |
October | 0.145047E+09 | 4330.16 | 01-OCT-16:01 | 35.32 |
November | 24920291.69 | 2158.01 | 05-NOV-16:12 | 27.37 |
December | 461755.96 | 180.94 | 24-DEC-17:05 | 20.40 |
Annual Sum or Average | 0.183573E+10 | |||
Minimum of Months | 461755.96 | 180.94 | 6.78 | |
Maximum of Months | 0.292252E+09 | 20065.53 | 43.35 |
Report: ZoneHeatingSummaryMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 70787164.69 | 66061.67 | 01-JAN-09:01 | 9.20 |
February | 12032784.63 | 2231.56 | 20-FEB-17:03 | 24.33 |
March | 77949787.38 | 6071.90 | 12-MAR-16:02 | 31.18 |
April | 0.188513E+09 | 11052.14 | 16-APR-16:01 | 39.13 |
May | 0.147824E+09 | 12899.86 | 07-MAY-16:01 | 42.17 |
June | 0.124741E+09 | 13564.70 | 11-JUN-16:01 | 43.35 |
July | 0.160194E+09 | 11948.05 | 02-JUL-16:01 | 40.38 |
August | 0.116371E+09 | 9424.18 | 06-AUG-16:01 | 36.25 |
September | 0.157303E+09 | 8378.27 | 24-SEP-16:01 | 34.68 |
October | 0.162498E+09 | 8660.55 | 01-OCT-16:01 | 35.32 |
November | 44380605.21 | 4272.63 | 04-NOV-17:02 | 27.72 |
December | 1499897.16 | 2430.29 | 23-DEC-08:07 | 7.55 |
Annual Sum or Average | 0.126409E+10 | |||
Minimum of Months | 1499897.16 | 2231.56 | 7.55 | |
Maximum of Months | 0.188513E+09 | 66061.67 | 43.35 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 43011767.18 | 34666.63 | 01-JAN-09:01 | 9.20 |
February | 7416502.56 | 1148.38 | 20-FEB-17:03 | 24.33 |
March | 42329706.78 | 3072.73 | 12-MAR-16:11 | 31.07 |
April | 96297418.05 | 5526.20 | 16-APR-16:01 | 39.13 |
May | 75649538.46 | 6448.35 | 07-MAY-16:01 | 42.17 |
June | 65907594.77 | 6775.09 | 11-JUN-16:01 | 43.35 |
July | 84572828.25 | 5976.01 | 02-JUL-16:01 | 40.38 |
August | 60232097.57 | 4720.94 | 06-AUG-16:01 | 36.25 |
September | 79448527.90 | 4196.96 | 24-SEP-16:01 | 34.68 |
October | 84544663.31 | 4335.03 | 01-OCT-16:01 | 35.32 |
November | 24234278.67 | 2168.85 | 04-NOV-17:02 | 27.72 |
December | 1206062.27 | 1219.28 | 23-DEC-08:07 | 7.55 |
Annual Sum or Average | 0.664851E+09 | |||
Minimum of Months | 1206062.27 | 1148.38 | 7.55 | |
Maximum of Months | 96297418.05 | 34666.63 | 43.35 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 46213879.75 | 34564.54 | 01-JAN-09:01 | 9.20 |
February | 7471305.20 | 1151.96 | 20-FEB-17:03 | 24.33 |
March | 42428528.42 | 3069.67 | 12-MAR-16:11 | 31.07 |
April | 96840105.93 | 5526.83 | 16-APR-16:01 | 39.13 |
May | 76203596.13 | 6448.66 | 07-MAY-16:01 | 42.17 |
June | 66461434.91 | 6775.65 | 11-JUN-16:01 | 43.35 |
July | 85213762.21 | 5976.09 | 02-JUL-16:01 | 40.38 |
August | 60508702.47 | 4720.91 | 06-AUG-16:01 | 36.25 |
September | 79720764.98 | 4197.31 | 24-SEP-16:01 | 34.68 |
October | 85019037.15 | 4335.39 | 01-OCT-16:01 | 35.32 |
November | 24237825.86 | 2170.18 | 04-NOV-17:02 | 27.72 |
December | 1324971.37 | 1000.02 | 23-DEC-08:07 | 7.55 |
Annual Sum or Average | 0.671644E+09 | |||
Minimum of Months | 1324971.37 | 1000.02 | 7.55 | |
Maximum of Months | 96840105.93 | 34564.54 | 43.35 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 59946166.09 | 34712.53 | 01-JAN-09:01 | 9.20 |
February | 8262871.87 | 1168.72 | 20-FEB-17:03 | 24.33 |
March | 42523605.49 | 3076.91 | 12-MAR-16:11 | 31.07 |
April | 96098948.58 | 5527.52 | 16-APR-16:01 | 39.13 |
May | 76689099.13 | 6447.83 | 07-MAY-16:01 | 42.17 |
June | 66852123.82 | 6773.40 | 11-JUN-16:01 | 43.35 |
July | 85615920.24 | 5973.67 | 02-JUL-16:01 | 40.38 |
August | 60384998.12 | 4718.55 | 06-AUG-16:01 | 36.25 |
September | 79387427.93 | 4195.83 | 24-SEP-16:01 | 34.68 |
October | 84948843.96 | 4334.45 | 01-OCT-16:01 | 35.32 |
November | 24526171.66 | 2176.34 | 04-NOV-17:02 | 27.72 |
December | 2469761.68 | 1049.70 | 23-DEC-08:63 | 7.55 |
Annual Sum or Average | 0.687706E+09 | |||
Minimum of Months | 2469761.68 | 1049.70 | 7.55 | |
Maximum of Months | 96098948.58 | 34712.53 | 43.35 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.152179E+09 | 38258.21 | 01-JAN-09:01 | 9.20 |
February | 28091964.73 | 5329.30 | 11-FEB-08:65 | 11.12 |
March | 49163983.49 | 3193.98 | 12-MAR-16:11 | 31.07 |
April | 86029309.69 | 5529.47 | 16-APR-16:01 | 39.13 |
May | 69079891.43 | 6438.01 | 07-MAY-16:01 | 42.17 |
June | 57399589.70 | 6746.38 | 11-JUN-16:01 | 43.35 |
July | 73611659.75 | 5951.08 | 02-JUL-16:01 | 40.38 |
August | 51635917.47 | 4697.78 | 06-AUG-16:01 | 36.25 |
September | 72329011.54 | 4178.82 | 24-SEP-16:01 | 34.68 |
October | 82115083.60 | 4320.53 | 01-OCT-16:01 | 35.32 |
November | 26248535.52 | 2257.15 | 05-NOV-16:12 | 27.37 |
December | 19684277.31 | 9540.93 | 23-DEC-08:63 | 7.55 |
Annual Sum or Average | 0.767569E+09 | |||
Minimum of Months | 19684277.31 | 2257.15 | 7.55 | |
Maximum of Months | 0.152179E+09 | 38258.21 | 43.35 |
Report: ZoneElectricSummaryMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.157219E+11 | 9537.57 | 01-JAN-10:09 | 0.223514E+10 | 1348.26 | 01-JAN-10:09 |
February | 0.142256E+11 | 9537.57 | 01-FEB-10:09 | 0.202238E+10 | 1348.26 | 01-FEB-10:09 |
March | 0.157545E+11 | 9537.57 | 01-MAR-10:09 | 0.223972E+10 | 1348.26 | 01-MAR-10:09 |
April | 0.152557E+11 | 9537.57 | 01-APR-09:09 | 0.216880E+10 | 1348.26 | 01-APR-09:09 |
May | 0.157219E+11 | 9537.57 | 01-MAY-09:09 | 0.223514E+10 | 1348.26 | 01-MAY-09:09 |
June | 0.152557E+11 | 9537.57 | 01-JUN-09:09 | 0.216880E+10 | 1348.26 | 01-JUN-09:09 |
July | 0.157545E+11 | 9537.57 | 01-JUL-09:09 | 0.223972E+10 | 1348.26 | 01-JUL-09:09 |
August | 0.157219E+11 | 9537.57 | 01-AUG-09:09 | 0.223514E+10 | 1348.26 | 01-AUG-09:09 |
September | 0.152882E+11 | 9537.57 | 01-SEP-09:09 | 0.217339E+10 | 1348.26 | 01-SEP-09:09 |
October | 0.157219E+11 | 9537.57 | 01-OCT-09:09 | 0.223514E+10 | 1348.26 | 01-OCT-09:09 |
November | 0.151906E+11 | 9537.57 | 01-NOV-09:09 | 0.215964E+10 | 1348.26 | 01-NOV-09:09 |
December | 0.157870E+11 | 9537.57 | 01-DEC-10:09 | 0.224431E+10 | 1348.26 | 01-DEC-10:09 |
Annual Sum or Average | 0.185400E+12 | 0.263573E+11 | ||||
Minimum of Months | 0.142256E+11 | 9537.57 | 0.202238E+10 | 1348.26 | ||
Maximum of Months | 0.157870E+11 | 9537.57 | 0.224431E+10 | 1348.26 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.786097E+10 | 4768.79 | 01-JAN-10:09 | 0.111757E+10 | 674.13 | 01-JAN-10:09 |
February | 0.711282E+10 | 4768.79 | 01-FEB-10:09 | 0.101119E+10 | 674.13 | 01-FEB-10:09 |
March | 0.787723E+10 | 4768.79 | 01-MAR-10:09 | 0.111986E+10 | 674.13 | 01-MAR-10:09 |
April | 0.762785E+10 | 4768.79 | 01-APR-09:09 | 0.108440E+10 | 674.13 | 01-APR-09:09 |
May | 0.786097E+10 | 4768.79 | 01-MAY-09:09 | 0.111757E+10 | 674.13 | 01-MAY-09:09 |
June | 0.762785E+10 | 4768.79 | 01-JUN-09:09 | 0.108440E+10 | 674.13 | 01-JUN-09:09 |
July | 0.787723E+10 | 4768.79 | 01-JUL-09:09 | 0.111986E+10 | 674.13 | 01-JUL-09:09 |
August | 0.786097E+10 | 4768.79 | 01-AUG-09:09 | 0.111757E+10 | 674.13 | 01-AUG-09:09 |
September | 0.764411E+10 | 4768.79 | 01-SEP-09:09 | 0.108669E+10 | 674.13 | 01-SEP-09:09 |
October | 0.786097E+10 | 4768.79 | 01-OCT-09:09 | 0.111757E+10 | 674.13 | 01-OCT-09:09 |
November | 0.759532E+10 | 4768.79 | 01-NOV-09:09 | 0.107982E+10 | 674.13 | 01-NOV-09:09 |
December | 0.789349E+10 | 4768.79 | 01-DEC-10:09 | 0.112215E+10 | 674.13 | 01-DEC-10:09 |
Annual Sum or Average | 0.926998E+11 | 0.131787E+11 | ||||
Minimum of Months | 0.711282E+10 | 4768.79 | 0.101119E+10 | 674.13 | ||
Maximum of Months | 0.789349E+10 | 4768.79 | 0.112215E+10 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.486999E+10 | 3744.57 | 01-JAN-10:09 | 0.883781E+09 | 674.13 | 01-JAN-10:09 |
February | 0.441023E+10 | 3744.57 | 01-FEB-09:09 | 0.800324E+09 | 674.13 | 01-FEB-09:09 |
March | 0.497215E+10 | 3744.57 | 01-MAR-09:09 | 0.902118E+09 | 674.13 | 01-MAR-09:09 |
April | 0.472525E+10 | 3744.57 | 01-APR-08:09 | 0.857490E+09 | 674.13 | 01-APR-08:09 |
May | 0.492107E+10 | 3744.57 | 01-MAY-08:09 | 0.892950E+09 | 674.13 | 01-MAY-08:09 |
June | 0.480187E+10 | 3744.57 | 01-JUN-08:09 | 0.871243E+09 | 674.13 | 01-JUN-08:09 |
July | 0.484444E+10 | 3744.57 | 01-JUL-08:09 | 0.879197E+09 | 674.13 | 01-JUL-08:09 |
August | 0.497215E+10 | 3744.57 | 01-AUG-08:09 | 0.902118E+09 | 674.13 | 01-AUG-08:09 |
September | 0.472525E+10 | 3744.57 | 01-SEP-08:09 | 0.857490E+09 | 674.13 | 01-SEP-08:09 |
October | 0.486999E+10 | 3744.57 | 01-OCT-09:09 | 0.883781E+09 | 674.13 | 01-OCT-09:09 |
November | 0.472525E+10 | 3744.57 | 01-NOV-08:09 | 0.857490E+09 | 674.13 | 01-NOV-08:09 |
December | 0.484444E+10 | 3744.57 | 01-DEC-09:09 | 0.879197E+09 | 674.13 | 01-DEC-09:09 |
Annual Sum or Average | 0.576821E+11 | 0.104672E+11 | ||||
Minimum of Months | 0.441023E+10 | 3744.57 | 0.800324E+09 | 674.13 | ||
Maximum of Months | 0.497215E+10 | 3744.57 | 0.902118E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.486999E+10 | 3744.57 | 01-JAN-10:09 | 0.883781E+09 | 674.13 | 01-JAN-10:09 |
February | 0.441023E+10 | 3744.57 | 01-FEB-09:09 | 0.800324E+09 | 674.13 | 01-FEB-09:09 |
March | 0.497215E+10 | 3744.57 | 01-MAR-09:09 | 0.902118E+09 | 674.13 | 01-MAR-09:09 |
April | 0.472525E+10 | 3744.57 | 01-APR-08:09 | 0.857490E+09 | 674.13 | 01-APR-08:09 |
May | 0.492107E+10 | 3744.57 | 01-MAY-08:09 | 0.892950E+09 | 674.13 | 01-MAY-08:09 |
June | 0.480187E+10 | 3744.57 | 01-JUN-08:09 | 0.871243E+09 | 674.13 | 01-JUN-08:09 |
July | 0.484444E+10 | 3744.57 | 01-JUL-08:09 | 0.879197E+09 | 674.13 | 01-JUL-08:09 |
August | 0.497215E+10 | 3744.57 | 01-AUG-08:09 | 0.902118E+09 | 674.13 | 01-AUG-08:09 |
September | 0.472525E+10 | 3744.57 | 01-SEP-08:09 | 0.857490E+09 | 674.13 | 01-SEP-08:09 |
October | 0.486999E+10 | 3744.57 | 01-OCT-09:09 | 0.883781E+09 | 674.13 | 01-OCT-09:09 |
November | 0.472525E+10 | 3744.57 | 01-NOV-08:09 | 0.857490E+09 | 674.13 | 01-NOV-08:09 |
December | 0.484444E+10 | 3744.57 | 01-DEC-09:09 | 0.879197E+09 | 674.13 | 01-DEC-09:09 |
Annual Sum or Average | 0.576821E+11 | 0.104672E+11 | ||||
Minimum of Months | 0.441023E+10 | 3744.57 | 0.800324E+09 | 674.13 | ||
Maximum of Months | 0.497215E+10 | 3744.57 | 0.902118E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.486999E+10 | 3744.57 | 01-JAN-10:09 | 0.883781E+09 | 674.13 | 01-JAN-10:09 |
February | 0.441023E+10 | 3744.57 | 01-FEB-09:09 | 0.800324E+09 | 674.13 | 01-FEB-09:09 |
March | 0.497215E+10 | 3744.57 | 01-MAR-09:09 | 0.902118E+09 | 674.13 | 01-MAR-09:09 |
April | 0.472525E+10 | 3744.57 | 01-APR-08:09 | 0.857490E+09 | 674.13 | 01-APR-08:09 |
May | 0.492107E+10 | 3744.57 | 01-MAY-08:09 | 0.892950E+09 | 674.13 | 01-MAY-08:09 |
June | 0.480187E+10 | 3744.57 | 01-JUN-08:09 | 0.871243E+09 | 674.13 | 01-JUN-08:09 |
July | 0.484444E+10 | 3744.57 | 01-JUL-08:09 | 0.879197E+09 | 674.13 | 01-JUL-08:09 |
August | 0.497215E+10 | 3744.57 | 01-AUG-08:09 | 0.902118E+09 | 674.13 | 01-AUG-08:09 |
September | 0.472525E+10 | 3744.57 | 01-SEP-08:09 | 0.857490E+09 | 674.13 | 01-SEP-08:09 |
October | 0.486999E+10 | 3744.57 | 01-OCT-09:09 | 0.883781E+09 | 674.13 | 01-OCT-09:09 |
November | 0.472525E+10 | 3744.57 | 01-NOV-08:09 | 0.857490E+09 | 674.13 | 01-NOV-08:09 |
December | 0.484444E+10 | 3744.57 | 01-DEC-09:09 | 0.879197E+09 | 674.13 | 01-DEC-09:09 |
Annual Sum or Average | 0.576821E+11 | 0.104672E+11 | ||||
Minimum of Months | 0.441023E+10 | 3744.57 | 0.800324E+09 | 674.13 | ||
Maximum of Months | 0.497215E+10 | 3744.57 | 0.902118E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.724555E+10 | 6064.13 | 01-JAN-11:09 | 0.162546E+10 | 1348.26 | 01-JAN-11:09 |
February | 0.656305E+10 | 6064.13 | 01-FEB-10:09 | 0.147229E+10 | 1348.26 | 01-FEB-10:09 |
March | 0.741101E+10 | 6064.13 | 01-MAR-10:09 | 0.166213E+10 | 1348.26 | 01-MAR-10:09 |
April | 0.703184E+10 | 6064.13 | 01-APR-09:09 | 0.157746E+10 | 1348.26 | 01-APR-09:09 |
May | 0.732828E+10 | 6064.13 | 01-MAY-09:09 | 0.164379E+10 | 1348.26 | 01-MAY-09:09 |
June | 0.715593E+10 | 6064.13 | 01-JUN-09:09 | 0.160496E+10 | 1348.26 | 01-JUN-09:09 |
July | 0.720419E+10 | 6064.13 | 01-JUL-09:09 | 0.161629E+10 | 1348.26 | 01-JUL-09:09 |
August | 0.741101E+10 | 6064.13 | 01-AUG-09:09 | 0.166213E+10 | 1348.26 | 01-AUG-09:09 |
September | 0.703184E+10 | 6064.13 | 01-SEP-09:09 | 0.157746E+10 | 1348.26 | 01-SEP-09:09 |
October | 0.724555E+10 | 6064.13 | 01-OCT-10:09 | 0.162546E+10 | 1348.26 | 01-OCT-10:09 |
November | 0.703184E+10 | 6064.13 | 01-NOV-09:09 | 0.157746E+10 | 1348.26 | 01-NOV-09:09 |
December | 0.720419E+10 | 6064.13 | 01-DEC-10:09 | 0.161629E+10 | 1348.26 | 01-DEC-10:09 |
Annual Sum or Average | 0.858643E+11 | 0.192612E+11 | ||||
Minimum of Months | 0.656305E+10 | 6064.13 | 0.147229E+10 | 1348.26 | ||
Maximum of Months | 0.741101E+10 | 6064.13 | 0.166213E+10 | 1348.26 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.362278E+10 | 3032.07 | 01-JAN-11:09 | 0.812728E+09 | 674.13 | 01-JAN-11:09 |
February | 0.328152E+10 | 3032.07 | 01-FEB-10:09 | 0.736147E+09 | 674.13 | 01-FEB-10:09 |
March | 0.370550E+10 | 3032.07 | 01-MAR-10:09 | 0.831065E+09 | 674.13 | 01-MAR-10:09 |
April | 0.351592E+10 | 3032.07 | 01-APR-09:09 | 0.788729E+09 | 674.13 | 01-APR-09:09 |
May | 0.366414E+10 | 3032.07 | 01-MAY-09:09 | 0.821897E+09 | 674.13 | 01-MAY-09:09 |
June | 0.357797E+10 | 3032.07 | 01-JUN-09:09 | 0.802482E+09 | 674.13 | 01-JUN-09:09 |
July | 0.360209E+10 | 3032.07 | 01-JUL-09:09 | 0.808144E+09 | 674.13 | 01-JUL-09:09 |
August | 0.370550E+10 | 3032.07 | 01-AUG-09:09 | 0.831065E+09 | 674.13 | 01-AUG-09:09 |
September | 0.351592E+10 | 3032.07 | 01-SEP-09:09 | 0.788729E+09 | 674.13 | 01-SEP-09:09 |
October | 0.362278E+10 | 3032.07 | 01-OCT-10:09 | 0.812728E+09 | 674.13 | 01-OCT-10:09 |
November | 0.351592E+10 | 3032.07 | 01-NOV-09:09 | 0.788729E+09 | 674.13 | 01-NOV-09:09 |
December | 0.360209E+10 | 3032.07 | 01-DEC-10:09 | 0.808144E+09 | 674.13 | 01-DEC-10:09 |
Annual Sum or Average | 0.429321E+11 | 0.963059E+10 | ||||
Minimum of Months | 0.328152E+10 | 3032.07 | 0.736147E+09 | 674.13 | ||
Maximum of Months | 0.370550E+10 | 3032.07 | 0.831065E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.362278E+10 | 3032.07 | 01-JAN-11:09 | 0.812728E+09 | 674.13 | 01-JAN-11:09 |
February | 0.328152E+10 | 3032.07 | 01-FEB-10:09 | 0.736147E+09 | 674.13 | 01-FEB-10:09 |
March | 0.370550E+10 | 3032.07 | 01-MAR-10:09 | 0.831065E+09 | 674.13 | 01-MAR-10:09 |
April | 0.351592E+10 | 3032.07 | 01-APR-09:09 | 0.788729E+09 | 674.13 | 01-APR-09:09 |
May | 0.366414E+10 | 3032.07 | 01-MAY-09:09 | 0.821897E+09 | 674.13 | 01-MAY-09:09 |
June | 0.357797E+10 | 3032.07 | 01-JUN-09:09 | 0.802482E+09 | 674.13 | 01-JUN-09:09 |
July | 0.360209E+10 | 3032.07 | 01-JUL-09:09 | 0.808144E+09 | 674.13 | 01-JUL-09:09 |
August | 0.370550E+10 | 3032.07 | 01-AUG-09:09 | 0.831065E+09 | 674.13 | 01-AUG-09:09 |
September | 0.351592E+10 | 3032.07 | 01-SEP-09:09 | 0.788729E+09 | 674.13 | 01-SEP-09:09 |
October | 0.362278E+10 | 3032.07 | 01-OCT-10:09 | 0.812728E+09 | 674.13 | 01-OCT-10:09 |
November | 0.351592E+10 | 3032.07 | 01-NOV-09:09 | 0.788729E+09 | 674.13 | 01-NOV-09:09 |
December | 0.360209E+10 | 3032.07 | 01-DEC-10:09 | 0.808144E+09 | 674.13 | 01-DEC-10:09 |
Annual Sum or Average | 0.429321E+11 | 0.963059E+10 | ||||
Minimum of Months | 0.328152E+10 | 3032.07 | 0.736147E+09 | 674.13 | ||
Maximum of Months | 0.370550E+10 | 3032.07 | 0.831065E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.362278E+10 | 3032.07 | 01-JAN-11:09 | 0.812728E+09 | 674.13 | 01-JAN-11:09 |
February | 0.328152E+10 | 3032.07 | 01-FEB-10:09 | 0.736147E+09 | 674.13 | 01-FEB-10:09 |
March | 0.370550E+10 | 3032.07 | 01-MAR-10:09 | 0.831065E+09 | 674.13 | 01-MAR-10:09 |
April | 0.351592E+10 | 3032.07 | 01-APR-09:09 | 0.788729E+09 | 674.13 | 01-APR-09:09 |
May | 0.366414E+10 | 3032.07 | 01-MAY-09:09 | 0.821897E+09 | 674.13 | 01-MAY-09:09 |
June | 0.357797E+10 | 3032.07 | 01-JUN-09:09 | 0.802482E+09 | 674.13 | 01-JUN-09:09 |
July | 0.360209E+10 | 3032.07 | 01-JUL-09:09 | 0.808144E+09 | 674.13 | 01-JUL-09:09 |
August | 0.370550E+10 | 3032.07 | 01-AUG-09:09 | 0.831065E+09 | 674.13 | 01-AUG-09:09 |
September | 0.351592E+10 | 3032.07 | 01-SEP-09:09 | 0.788729E+09 | 674.13 | 01-SEP-09:09 |
October | 0.362278E+10 | 3032.07 | 01-OCT-10:09 | 0.812728E+09 | 674.13 | 01-OCT-10:09 |
November | 0.351592E+10 | 3032.07 | 01-NOV-09:09 | 0.788729E+09 | 674.13 | 01-NOV-09:09 |
December | 0.360209E+10 | 3032.07 | 01-DEC-10:09 | 0.808144E+09 | 674.13 | 01-DEC-10:09 |
Annual Sum or Average | 0.429321E+11 | 0.963059E+10 | ||||
Minimum of Months | 0.328152E+10 | 3032.07 | 0.736147E+09 | 674.13 | ||
Maximum of Months | 0.370550E+10 | 3032.07 | 0.831065E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.362278E+10 | 3032.07 | 01-JAN-11:09 | 0.812728E+09 | 674.13 | 01-JAN-11:09 |
February | 0.328152E+10 | 3032.07 | 01-FEB-10:09 | 0.736147E+09 | 674.13 | 01-FEB-10:09 |
March | 0.370550E+10 | 3032.07 | 01-MAR-10:09 | 0.831065E+09 | 674.13 | 01-MAR-10:09 |
April | 0.351592E+10 | 3032.07 | 01-APR-09:09 | 0.788729E+09 | 674.13 | 01-APR-09:09 |
May | 0.366414E+10 | 3032.07 | 01-MAY-09:09 | 0.821897E+09 | 674.13 | 01-MAY-09:09 |
June | 0.357797E+10 | 3032.07 | 01-JUN-09:09 | 0.802482E+09 | 674.13 | 01-JUN-09:09 |
July | 0.360209E+10 | 3032.07 | 01-JUL-09:09 | 0.808144E+09 | 674.13 | 01-JUL-09:09 |
August | 0.370550E+10 | 3032.07 | 01-AUG-09:09 | 0.831065E+09 | 674.13 | 01-AUG-09:09 |
September | 0.351592E+10 | 3032.07 | 01-SEP-09:09 | 0.788729E+09 | 674.13 | 01-SEP-09:09 |
October | 0.362278E+10 | 3032.07 | 01-OCT-10:09 | 0.812728E+09 | 674.13 | 01-OCT-10:09 |
November | 0.351592E+10 | 3032.07 | 01-NOV-09:09 | 0.788729E+09 | 674.13 | 01-NOV-09:09 |
December | 0.360209E+10 | 3032.07 | 01-DEC-10:09 | 0.808144E+09 | 674.13 | 01-DEC-10:09 |
Annual Sum or Average | 0.429321E+11 | 0.963059E+10 | ||||
Minimum of Months | 0.328152E+10 | 3032.07 | 0.736147E+09 | 674.13 | ||
Maximum of Months | 0.370550E+10 | 3032.07 | 0.831065E+09 | 674.13 |
Report: SpaceGainsMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.180574E+10 | 0.157219E+11 | 0.223514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.218542E+10 |
February | 0.163016E+10 | 0.142256E+11 | 0.202238E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122261E+09 | 0.977346E+09 |
March | 0.178954E+10 | 0.157545E+11 | 0.223972E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124877E+10 | 0.285928E+09 |
April | 0.174484E+10 | 0.152557E+11 | 0.216880E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.336888E+10 | 21332404.81 |
May | 0.179537E+10 | 0.157219E+11 | 0.223514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.479624E+10 | 9295764.63 |
June | 0.173447E+10 | 0.152557E+11 | 0.216880E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.432832E+10 | 4186095.10 |
July | 0.181028E+10 | 0.157545E+11 | 0.223972E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.351762E+10 | 3326368.02 |
August | 0.178501E+10 | 0.157219E+11 | 0.223514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.295602E+10 | 4312809.62 |
September | 0.174937E+10 | 0.152882E+11 | 0.217339E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.256918E+10 | 10312851.08 |
October | 0.180574E+10 | 0.157219E+11 | 0.223514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.220557E+10 | 47699844.75 |
November | 0.174613E+10 | 0.151906E+11 | 0.215964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.749162E+09 | 0.288926E+09 |
December | 0.181481E+10 | 0.157870E+11 | 0.224431E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5269695.46 | 0.184550E+10 |
Annual Sum or Average | 0.212115E+11 | 0.185400E+12 | 0.263573E+11 | 0.258673E+11 | 0.568359E+10 | ||||
Minimum of Months | 0.163016E+10 | 0.142256E+11 | 0.202238E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3326368.02 |
Maximum of Months | 0.181481E+10 | 0.157870E+11 | 0.224431E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.479624E+10 | 0.218542E+10 |
Report: SpaceGainsMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.902868E+09 | 0.786097E+10 | 0.111757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119012E+10 |
February | 0.815075E+09 | 0.711282E+10 | 0.101119E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 68875079.52 | 0.493124E+09 |
March | 0.894769E+09 | 0.787723E+10 | 0.111986E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.701114E+09 | 0.118526E+09 |
April | 0.872416E+09 | 0.762785E+10 | 0.108440E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.187836E+10 | 7334701.57 |
May | 0.897684E+09 | 0.786097E+10 | 0.111757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.265047E+10 | 2702161.63 |
June | 0.867232E+09 | 0.762785E+10 | 0.108440E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.240822E+10 | 1176951.67 |
July | 0.905135E+09 | 0.787723E+10 | 0.111986E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.193626E+10 | 853808.33 |
August | 0.892501E+09 | 0.786097E+10 | 0.111757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.164457E+10 | 1080364.51 |
September | 0.874683E+09 | 0.764411E+10 | 0.108669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143978E+10 | 2600664.41 |
October | 0.902868E+09 | 0.786097E+10 | 0.111757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124598E+10 | 21779590.22 |
November | 0.873064E+09 | 0.759532E+10 | 0.107982E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.424653E+09 | 0.146928E+09 |
December | 0.907403E+09 | 0.789349E+10 | 0.112215E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2977839.87 | 0.998392E+09 |
Annual Sum or Average | 0.106057E+11 | 0.926998E+11 | 0.131787E+11 | 0.144013E+11 | 0.298462E+10 | ||||
Minimum of Months | 0.815075E+09 | 0.711282E+10 | 0.101119E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 853808.33 |
Maximum of Months | 0.907403E+09 | 0.789349E+10 | 0.112215E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.265047E+10 | 0.119012E+10 |
Report: SpaceGainsMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.537120E+09 | 0.486999E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118182E+10 |
February | 0.487879E+09 | 0.441023E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 68783647.67 | 0.515071E+09 |
March | 0.551374E+09 | 0.497215E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.686485E+09 | 0.137335E+09 |
April | 0.524810E+09 | 0.472525E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.184908E+10 | 9955237.60 |
May | 0.544247E+09 | 0.492107E+10 | 0.892950E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.261885E+10 | 3324009.27 |
June | 0.532585E+09 | 0.480187E+10 | 0.871243E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.238525E+10 | 1514257.28 |
July | 0.536472E+09 | 0.484444E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189894E+10 | 1058560.38 |
August | 0.551374E+09 | 0.497215E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161903E+10 | 3008644.67 |
September | 0.524810E+09 | 0.472525E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141061E+10 | 4780515.00 |
October | 0.537120E+09 | 0.486999E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121266E+10 | 23424911.07 |
November | 0.518979E+09 | 0.472525E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.419480E+09 | 0.159363E+09 |
December | 0.536472E+09 | 0.484444E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2978461.83 | 0.100453E+10 |
Annual Sum or Average | 0.638324E+10 | 0.576821E+11 | 0.104672E+11 | 0.141722E+11 | 0.304519E+10 | ||||
Minimum of Months | 0.487879E+09 | 0.441023E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1058560.38 |
Maximum of Months | 0.551374E+09 | 0.497215E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.261885E+10 | 0.118182E+10 |
Report: SpaceGainsMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.537120E+09 | 0.486999E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117248E+10 |
February | 0.487879E+09 | 0.441023E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 68784167.94 | 0.512202E+09 |
March | 0.551374E+09 | 0.497215E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.686495E+09 | 0.136868E+09 |
April | 0.524810E+09 | 0.472525E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.184877E+10 | 10068883.40 |
May | 0.544247E+09 | 0.492107E+10 | 0.892950E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.261745E+10 | 3574202.26 |
June | 0.532585E+09 | 0.480187E+10 | 0.871243E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.238441E+10 | 1624256.95 |
July | 0.536472E+09 | 0.484444E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189749E+10 | 1156932.52 |
August | 0.551374E+09 | 0.497215E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161830E+10 | 3129253.17 |
September | 0.524810E+09 | 0.472525E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141035E+10 | 4991164.35 |
October | 0.537120E+09 | 0.486999E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121256E+10 | 23479749.73 |
November | 0.518979E+09 | 0.472525E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.419493E+09 | 0.158822E+09 |
December | 0.536472E+09 | 0.484444E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2978610.39 | 0.100016E+10 |
Annual Sum or Average | 0.638324E+10 | 0.576821E+11 | 0.104672E+11 | 0.141671E+11 | 0.302855E+10 | ||||
Minimum of Months | 0.487879E+09 | 0.441023E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1156932.52 |
Maximum of Months | 0.551374E+09 | 0.497215E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.261745E+10 | 0.117248E+10 |
Report: SpaceGainsMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.537120E+09 | 0.486999E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116462E+10 |
February | 0.487879E+09 | 0.441023E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 68784670.17 | 0.509225E+09 |
March | 0.551374E+09 | 0.497215E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.686606E+09 | 0.135389E+09 |
April | 0.524810E+09 | 0.472525E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.184911E+10 | 9711519.56 |
May | 0.544247E+09 | 0.492107E+10 | 0.892950E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.261847E+10 | 3323903.83 |
June | 0.532585E+09 | 0.480187E+10 | 0.871243E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.238519E+10 | 1550467.52 |
July | 0.536472E+09 | 0.484444E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189869E+10 | 1024194.40 |
August | 0.551374E+09 | 0.497215E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161908E+10 | 2855217.88 |
September | 0.524810E+09 | 0.472525E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141066E+10 | 4590982.69 |
October | 0.537120E+09 | 0.486999E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121275E+10 | 23270947.64 |
November | 0.518979E+09 | 0.472525E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.419509E+09 | 0.158094E+09 |
December | 0.536472E+09 | 0.484444E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2978768.19 | 0.996289E+09 |
Annual Sum or Average | 0.638324E+10 | 0.576821E+11 | 0.104672E+11 | 0.141718E+11 | 0.300994E+10 | ||||
Minimum of Months | 0.487879E+09 | 0.441023E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1024194.40 |
Maximum of Months | 0.551374E+09 | 0.497215E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.261847E+10 | 0.116462E+10 |
Report: SpaceGainsMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.183632E+10 | 0.724555E+10 | 0.162546E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.203463E+10 |
February | 0.167188E+10 | 0.656305E+10 | 0.147229E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120606E+09 | 0.910480E+09 |
March | 0.189386E+10 | 0.741101E+10 | 0.166213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120538E+10 | 0.251704E+09 |
April | 0.180380E+10 | 0.703184E+10 | 0.157746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.324860E+10 | 19627612.09 |
May | 0.186509E+10 | 0.732828E+10 | 0.164379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.461131E+10 | 6658272.75 |
June | 0.182945E+10 | 0.715593E+10 | 0.160496E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.419636E+10 | 3600046.91 |
July | 0.183943E+10 | 0.720419E+10 | 0.161629E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.334626E+10 | 1798934.38 |
August | 0.189386E+10 | 0.741101E+10 | 0.166213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.284668E+10 | 4824773.50 |
September | 0.180380E+10 | 0.703184E+10 | 0.157746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.247395E+10 | 9478484.02 |
October | 0.183632E+10 | 0.724555E+10 | 0.162546E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.212632E+10 | 45244581.93 |
November | 0.176881E+10 | 0.703184E+10 | 0.157746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.734978E+09 | 0.283194E+09 |
December | 0.183943E+10 | 0.720419E+10 | 0.161629E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5221179.61 | 0.175152E+10 |
Annual Sum or Average | 0.218821E+11 | 0.858643E+11 | 0.192612E+11 | 0.249157E+11 | 0.532276E+10 | ||||
Minimum of Months | 0.167188E+10 | 0.656305E+10 | 0.147229E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1798934.38 |
Maximum of Months | 0.189386E+10 | 0.741101E+10 | 0.166213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.461131E+10 | 0.203463E+10 |
Report: SpaceGainsMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.918158E+09 | 0.362278E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114922E+10 |
February | 0.835938E+09 | 0.328152E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 68791726.35 | 0.506897E+09 |
March | 0.946926E+09 | 0.370550E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.687474E+09 | 0.134310E+09 |
April | 0.901896E+09 | 0.351592E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185044E+10 | 9892632.53 |
May | 0.932542E+09 | 0.366414E+10 | 0.821897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.262313E+10 | 3105902.90 |
June | 0.914724E+09 | 0.357797E+10 | 0.802482E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.238914E+10 | 1708431.66 |
July | 0.919713E+09 | 0.360209E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.190268E+10 | 778350.76 |
August | 0.946926E+09 | 0.370550E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162155E+10 | 2279453.37 |
September | 0.901896E+09 | 0.351592E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141061E+10 | 4402594.63 |
October | 0.918158E+09 | 0.362278E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121366E+10 | 24630557.59 |
November | 0.884402E+09 | 0.351592E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.419590E+09 | 0.158466E+09 |
December | 0.919713E+09 | 0.360209E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2979590.09 | 0.989451E+09 |
Annual Sum or Average | 0.109410E+11 | 0.429321E+11 | 0.963059E+10 | 0.141900E+11 | 0.298515E+10 | ||||
Minimum of Months | 0.835938E+09 | 0.328152E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 778350.76 |
Maximum of Months | 0.946926E+09 | 0.370550E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.262313E+10 | 0.114922E+10 |
Report: SpaceGainsMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.918158E+09 | 0.362278E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114598E+10 |
February | 0.835938E+09 | 0.328152E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 68792196.71 | 0.505431E+09 |
March | 0.946926E+09 | 0.370550E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.687549E+09 | 0.133683E+09 |
April | 0.901896E+09 | 0.351592E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185062E+10 | 9748531.62 |
May | 0.932542E+09 | 0.366414E+10 | 0.821897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.262354E+10 | 3035302.65 |
June | 0.914724E+09 | 0.357797E+10 | 0.802482E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.238945E+10 | 1676476.06 |
July | 0.919713E+09 | 0.360209E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.190313E+10 | 750190.38 |
August | 0.946926E+09 | 0.370550E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162183E+10 | 2225030.74 |
September | 0.901896E+09 | 0.351592E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141076E+10 | 4289379.94 |
October | 0.918158E+09 | 0.362278E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121377E+10 | 24539516.38 |
November | 0.884402E+09 | 0.351592E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.419600E+09 | 0.158110E+09 |
December | 0.919713E+09 | 0.360209E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2979576.47 | 0.987531E+09 |
Annual Sum or Average | 0.109410E+11 | 0.429321E+11 | 0.963059E+10 | 0.141920E+11 | 0.297700E+10 | ||||
Minimum of Months | 0.835938E+09 | 0.328152E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 750190.38 |
Maximum of Months | 0.946926E+09 | 0.370550E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.262354E+10 | 0.114598E+10 |
Report: SpaceGainsMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.918158E+09 | 0.362278E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113775E+10 |
February | 0.835938E+09 | 0.328152E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 68792809.39 | 0.500904E+09 |
March | 0.946926E+09 | 0.370550E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.687659E+09 | 0.131851E+09 |
April | 0.901896E+09 | 0.351592E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185083E+10 | 9455432.73 |
May | 0.932542E+09 | 0.366414E+10 | 0.821897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.262373E+10 | 2912386.53 |
June | 0.914724E+09 | 0.357797E+10 | 0.802482E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.238952E+10 | 1650542.23 |
July | 0.919713E+09 | 0.360209E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.190299E+10 | 722254.67 |
August | 0.946926E+09 | 0.370550E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162177E+10 | 2204092.95 |
September | 0.901896E+09 | 0.351592E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141075E+10 | 4183999.59 |
October | 0.918158E+09 | 0.362278E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121379E+10 | 24425456.89 |
November | 0.884402E+09 | 0.351592E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.419610E+09 | 0.157247E+09 |
December | 0.919713E+09 | 0.360209E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2979557.96 | 0.982444E+09 |
Annual Sum or Average | 0.109410E+11 | 0.429321E+11 | 0.963059E+10 | 0.141924E+11 | 0.295575E+10 | ||||
Minimum of Months | 0.835938E+09 | 0.328152E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 722254.67 |
Maximum of Months | 0.946926E+09 | 0.370550E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.262373E+10 | 0.113775E+10 |
Report: SpaceGainsMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.918158E+09 | 0.362278E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122850E+10 |
February | 0.835938E+09 | 0.328152E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 70299980.55 | 0.606983E+09 |
March | 0.946926E+09 | 0.370550E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.705361E+09 | 0.203530E+09 |
April | 0.901896E+09 | 0.351592E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192361E+10 | 16713724.46 |
May | 0.932542E+09 | 0.366414E+10 | 0.821897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.276826E+10 | 7141349.10 |
June | 0.914724E+09 | 0.357797E+10 | 0.802482E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.249801E+10 | 3941748.75 |
July | 0.919713E+09 | 0.360209E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.201900E+10 | 2180542.27 |
August | 0.946926E+09 | 0.370550E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168845E+10 | 5054917.23 |
September | 0.901896E+09 | 0.351592E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.145144E+10 | 10999277.93 |
October | 0.918158E+09 | 0.362278E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123361E+10 | 34039156.19 |
November | 0.884402E+09 | 0.351592E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.424830E+09 | 0.185244E+09 |
December | 0.919713E+09 | 0.360209E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3030970.06 | 0.107334E+10 |
Annual Sum or Average | 0.109410E+11 | 0.429321E+11 | 0.963059E+10 | 0.147859E+11 | 0.337767E+10 | ||||
Minimum of Months | 0.835938E+09 | 0.328152E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2180542.27 |
Maximum of Months | 0.946926E+09 | 0.370550E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.276826E+10 | 0.122850E+10 |
Report: PeakSpaceGainsMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2159.72 | 01-JAN-13:09 | 9537.57 | 01-JAN-10:09 | 1348.26 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 4825.01 | 01-JAN-18:00 |
February | 2159.72 | 03-FEB-13:09 | 9537.57 | 01-FEB-10:09 | 1348.26 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1458.22 | 22-FEB-15:00 | 4418.18 | 10-FEB-18:00 |
March | 2159.72 | 03-MAR-13:09 | 9537.57 | 01-MAR-10:09 | 1348.26 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5081.46 | 28-MAR-15:00 | 1750.83 | 25-MAR-00:10 |
April | 2159.72 | 01-APR-12:09 | 9537.57 | 01-APR-09:09 | 1348.26 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 7535.38 | 15-APR-15:00 | 321.53 | 10-APR-07:03 |
May | 2159.72 | 05-MAY-12:09 | 9537.57 | 01-MAY-09:09 | 1348.26 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8909.04 | 03-MAY-15:00 | 154.70 | 15-MAY-03:00 |
June | 2159.72 | 02-JUN-12:09 | 9537.57 | 01-JUN-09:09 | 1348.26 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 9076.67 | 06-JUN-15:00 | 180.96 | 18-JUN-05:00 |
July | 2159.72 | 01-JUL-12:09 | 9537.57 | 01-JUL-09:09 | 1348.26 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 7163.31 | 07-JUL-15:00 | 158.69 | 19-JUL-03:00 |
August | 2159.72 | 04-AUG-12:09 | 9537.57 | 01-AUG-09:09 | 1348.26 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5962.39 | 07-AUG-15:00 | 161.30 | 15-AUG-24:00 |
September | 2159.72 | 01-SEP-12:09 | 9537.57 | 01-SEP-09:09 | 1348.26 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5499.29 | 29-SEP-13:00 | 113.31 | 07-SEP-07:01 |
October | 2159.72 | 01-OCT-12:09 | 9537.57 | 01-OCT-09:09 | 1348.26 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5550.65 | 02-OCT-14:00 | 512.30 | 11-OCT-17:00 |
November | 2159.72 | 03-NOV-12:09 | 9537.57 | 01-NOV-09:09 | 1348.26 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2874.43 | 04-NOV-14:00 | 2243.97 | 30-NOV-18:00 |
December | 2159.72 | 01-DEC-13:09 | 9537.57 | 01-DEC-10:09 | 1348.26 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 328.18 | 28-DEC-14:00 | 5560.60 | 31-DEC-18:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2159.72 | 9537.57 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 113.31 | |||||
Maximum of Months | 2159.72 | 9537.57 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 9076.67 | 5560.60 |
Report: PeakSpaceGainsMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1079.86 | 01-JAN-13:09 | 4768.79 | 01-JAN-10:09 | 674.13 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2719.77 | 01-JAN-18:00 |
February | 1079.86 | 03-FEB-13:09 | 4768.79 | 01-FEB-10:09 | 674.13 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 826.28 | 22-FEB-15:00 | 2523.37 | 10-FEB-18:00 |
March | 1079.86 | 03-MAR-13:09 | 4768.79 | 01-MAR-10:09 | 674.13 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2904.57 | 28-MAR-15:00 | 900.27 | 18-MAR-17:00 |
April | 1079.86 | 01-APR-12:09 | 4768.79 | 01-APR-09:09 | 674.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4149.31 | 15-APR-15:00 | 172.54 | 10-APR-07:03 |
May | 1079.86 | 05-MAY-12:09 | 4768.79 | 01-MAY-09:09 | 674.13 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5010.90 | 03-MAY-15:00 | 45.48 | 15-MAY-03:00 |
June | 1079.86 | 02-JUN-12:09 | 4768.79 | 01-JUN-09:09 | 674.13 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5023.33 | 07-JUN-16:00 | 52.94 | 18-JUN-05:00 |
July | 1079.86 | 01-JUL-12:09 | 4768.79 | 01-JUL-09:09 | 674.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4042.70 | 07-JUL-15:00 | 44.81 | 19-JUL-03:00 |
August | 1079.86 | 04-AUG-12:09 | 4768.79 | 01-AUG-09:09 | 674.13 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3349.82 | 07-AUG-15:00 | 61.86 | 16-AUG-07:01 |
September | 1079.86 | 01-SEP-12:09 | 4768.79 | 01-SEP-09:09 | 674.13 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3084.45 | 29-SEP-13:00 | 53.26 | 07-SEP-07:01 |
October | 1079.86 | 01-OCT-12:09 | 4768.79 | 01-OCT-09:09 | 674.13 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3139.75 | 02-OCT-14:00 | 288.47 | 11-OCT-16:00 |
November | 1079.86 | 03-NOV-12:09 | 4768.79 | 01-NOV-09:09 | 674.13 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1632.50 | 04-NOV-14:00 | 1275.90 | 30-NOV-18:00 |
December | 1079.86 | 01-DEC-13:09 | 4768.79 | 01-DEC-10:09 | 674.13 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 184.59 | 28-DEC-14:00 | 3118.97 | 21-DEC-12:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1079.86 | 4768.79 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.81 | |||||
Maximum of Months | 1079.86 | 4768.79 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 5023.33 | 3118.97 |
Report: PeakSpaceGainsMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1079.86 | 07-JAN-13:09 | 3744.57 | 01-JAN-10:09 | 674.13 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2521.69 | 15-JAN-17:00 |
February | 1079.86 | 04-FEB-13:09 | 3744.57 | 01-FEB-09:09 | 674.13 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 826.27 | 22-FEB-15:00 | 2398.93 | 10-FEB-18:00 |
March | 1079.86 | 04-MAR-13:09 | 3744.57 | 01-MAR-09:09 | 674.13 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2904.56 | 28-MAR-15:00 | 900.30 | 18-MAR-17:00 |
April | 1079.86 | 01-APR-12:09 | 3744.57 | 01-APR-08:09 | 674.13 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4149.31 | 15-APR-15:00 | 274.36 | 22-APR-18:10 |
May | 1079.86 | 06-MAY-12:09 | 3744.57 | 01-MAY-08:09 | 674.13 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5010.88 | 03-MAY-15:00 | 55.81 | 15-MAY-03:00 |
June | 1079.86 | 03-JUN-12:09 | 3744.57 | 01-JUN-08:09 | 674.13 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5023.32 | 07-JUN-16:00 | 60.28 | 18-JUN-04:00 |
July | 1079.86 | 01-JUL-12:09 | 3744.57 | 01-JUL-08:09 | 674.13 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4042.71 | 07-JUL-15:00 | 46.78 | 19-JUL-03:00 |
August | 1079.86 | 05-AUG-12:09 | 3744.57 | 01-AUG-08:09 | 674.13 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3349.81 | 07-AUG-15:00 | 386.24 | 20-AUG-17:00 |
September | 1079.86 | 02-SEP-12:09 | 3744.57 | 01-SEP-08:09 | 674.13 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3084.41 | 29-SEP-13:00 | 294.34 | 03-SEP-17:00 |
October | 1079.86 | 07-OCT-12:09 | 3744.57 | 01-OCT-09:09 | 674.13 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3139.76 | 02-OCT-14:00 | 288.49 | 11-OCT-16:00 |
November | 1079.86 | 04-NOV-12:09 | 3744.57 | 01-NOV-08:09 | 674.13 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1632.49 | 04-NOV-14:00 | 1275.90 | 30-NOV-18:00 |
December | 1079.86 | 02-DEC-13:09 | 3744.57 | 01-DEC-09:09 | 674.13 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 184.82 | 28-DEC-14:00 | 2995.82 | 21-DEC-12:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1079.86 | 3744.57 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.78 | |||||
Maximum of Months | 1079.86 | 3744.57 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 5023.32 | 2995.82 |
Report: PeakSpaceGainsMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1079.86 | 07-JAN-13:09 | 3744.57 | 01-JAN-10:09 | 674.13 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2488.74 | 15-JAN-17:00 |
February | 1079.86 | 04-FEB-13:09 | 3744.57 | 01-FEB-09:09 | 674.13 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 826.27 | 22-FEB-15:00 | 2368.86 | 10-FEB-18:00 |
March | 1079.86 | 04-MAR-13:09 | 3744.57 | 01-MAR-09:09 | 674.13 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2904.56 | 28-MAR-15:00 | 900.30 | 18-MAR-17:00 |
April | 1079.86 | 01-APR-12:09 | 3744.57 | 01-APR-08:09 | 674.13 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4149.31 | 15-APR-15:00 | 273.45 | 22-APR-18:10 |
May | 1079.86 | 06-MAY-12:09 | 3744.57 | 01-MAY-08:09 | 674.13 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5010.88 | 03-MAY-15:00 | 58.69 | 15-MAY-03:00 |
June | 1079.86 | 03-JUN-12:09 | 3744.57 | 01-JUN-08:09 | 674.13 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5023.32 | 07-JUN-16:00 | 62.43 | 18-JUN-04:00 |
July | 1079.86 | 01-JUL-12:09 | 3744.57 | 01-JUL-08:09 | 674.13 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4042.71 | 07-JUL-15:00 | 47.38 | 19-JUL-03:00 |
August | 1079.86 | 05-AUG-12:09 | 3744.57 | 01-AUG-08:09 | 674.13 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3349.82 | 07-AUG-15:00 | 387.88 | 20-AUG-17:00 |
September | 1079.86 | 02-SEP-12:09 | 3744.57 | 01-SEP-08:09 | 674.13 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3084.41 | 29-SEP-13:00 | 298.07 | 03-SEP-17:00 |
October | 1079.86 | 07-OCT-12:09 | 3744.57 | 01-OCT-09:09 | 674.13 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3139.76 | 02-OCT-14:00 | 288.49 | 11-OCT-16:00 |
November | 1079.86 | 04-NOV-12:09 | 3744.57 | 01-NOV-08:09 | 674.13 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1632.49 | 04-NOV-14:00 | 1275.90 | 30-NOV-18:00 |
December | 1079.86 | 02-DEC-13:09 | 3744.57 | 01-DEC-09:09 | 674.13 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 184.88 | 28-DEC-14:00 | 2966.15 | 21-DEC-12:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1079.86 | 3744.57 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.38 | |||||
Maximum of Months | 1079.86 | 3744.57 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 5023.32 | 2966.15 |
Report: PeakSpaceGainsMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1079.86 | 07-JAN-13:09 | 3744.57 | 01-JAN-10:09 | 674.13 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2458.76 | 15-JAN-17:00 |
February | 1079.86 | 04-FEB-13:09 | 3744.57 | 01-FEB-09:09 | 674.13 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 826.27 | 22-FEB-15:00 | 2338.13 | 10-FEB-18:00 |
March | 1079.86 | 04-MAR-13:09 | 3744.57 | 01-MAR-09:09 | 674.13 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2904.56 | 28-MAR-15:00 | 900.31 | 18-MAR-17:00 |
April | 1079.86 | 01-APR-12:09 | 3744.57 | 01-APR-08:09 | 674.13 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4149.31 | 15-APR-15:00 | 269.48 | 22-APR-18:10 |
May | 1079.86 | 06-MAY-12:09 | 3744.57 | 01-MAY-08:09 | 674.13 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5010.88 | 03-MAY-15:00 | 57.56 | 15-MAY-03:00 |
June | 1079.86 | 03-JUN-12:09 | 3744.57 | 01-JUN-08:09 | 674.13 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5023.32 | 07-JUN-16:00 | 61.52 | 18-JUN-04:00 |
July | 1079.86 | 01-JUL-12:09 | 3744.57 | 01-JUL-08:09 | 674.13 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4042.71 | 07-JUL-15:00 | 46.01 | 19-JUL-03:00 |
August | 1079.86 | 05-AUG-12:09 | 3744.57 | 01-AUG-08:09 | 674.13 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3349.82 | 07-AUG-15:00 | 380.59 | 20-AUG-17:00 |
September | 1079.86 | 02-SEP-12:09 | 3744.57 | 01-SEP-08:09 | 674.13 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3084.41 | 29-SEP-13:00 | 291.49 | 03-SEP-17:00 |
October | 1079.86 | 07-OCT-12:09 | 3744.57 | 01-OCT-09:09 | 674.13 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3139.76 | 02-OCT-14:00 | 288.49 | 11-OCT-16:00 |
November | 1079.86 | 04-NOV-12:09 | 3744.57 | 01-NOV-08:09 | 674.13 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1632.49 | 04-NOV-14:00 | 1275.90 | 30-NOV-18:00 |
December | 1079.86 | 02-DEC-13:09 | 3744.57 | 01-DEC-09:09 | 674.13 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 184.89 | 28-DEC-14:00 | 2935.07 | 21-DEC-12:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1079.86 | 3744.57 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.01 | |||||
Maximum of Months | 1079.86 | 3744.57 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 5023.32 | 2935.07 |
Report: PeakSpaceGainsMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2879.63 | 07-JAN-15:09 | 6064.13 | 01-JAN-11:09 | 1348.26 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 4187.79 | 15-JAN-17:00 |
February | 2879.63 | 04-FEB-15:09 | 6064.13 | 01-FEB-10:09 | 1348.26 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1447.93 | 22-FEB-15:00 | 3968.84 | 10-FEB-18:00 |
March | 2879.63 | 04-MAR-15:09 | 6064.13 | 01-MAR-10:09 | 1348.26 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5081.51 | 28-MAR-15:00 | 1578.49 | 18-MAR-17:00 |
April | 2879.63 | 01-APR-14:09 | 6064.13 | 01-APR-09:09 | 1348.26 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 7298.96 | 15-APR-15:00 | 487.47 | 22-APR-18:10 |
May | 2879.63 | 06-MAY-14:09 | 6064.13 | 01-MAY-09:09 | 1348.26 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8787.01 | 03-MAY-15:00 | 111.99 | 15-MAY-03:00 |
June | 2879.63 | 03-JUN-14:09 | 6064.13 | 01-JUN-09:09 | 1348.26 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8819.62 | 06-JUN-15:00 | 181.56 | 18-JUN-07:01 |
July | 2879.63 | 01-JUL-14:09 | 6064.13 | 01-JUL-09:09 | 1348.26 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 7085.77 | 07-JUL-15:00 | 86.17 | 19-JUL-03:00 |
August | 2879.63 | 05-AUG-14:09 | 6064.13 | 01-AUG-09:09 | 1348.26 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5874.14 | 07-AUG-15:00 | 657.78 | 20-AUG-17:00 |
September | 2879.63 | 02-SEP-14:09 | 6064.13 | 01-SEP-09:09 | 1348.26 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5410.96 | 29-SEP-13:00 | 502.86 | 03-SEP-17:00 |
October | 2879.63 | 07-OCT-14:09 | 6064.13 | 01-OCT-10:09 | 1348.26 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5501.24 | 02-OCT-14:00 | 537.88 | 29-OCT-07:03 |
November | 2879.63 | 04-NOV-14:09 | 6064.13 | 01-NOV-09:09 | 1348.26 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2858.62 | 04-NOV-14:00 | 2233.88 | 30-NOV-18:00 |
December | 2879.63 | 02-DEC-15:09 | 6064.13 | 01-DEC-10:09 | 1348.26 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 324.26 | 28-DEC-14:00 | 5040.52 | 21-DEC-12:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2879.63 | 6064.13 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.17 | |||||
Maximum of Months | 2879.63 | 6064.13 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 8819.62 | 5040.52 |
Report: PeakSpaceGainsMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1439.81 | 07-JAN-15:09 | 3032.07 | 01-JAN-11:09 | 674.13 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2377.39 | 15-JAN-17:00 |
February | 1439.81 | 04-FEB-15:09 | 3032.07 | 01-FEB-10:09 | 674.13 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 826.34 | 22-FEB-15:00 | 2250.99 | 10-FEB-18:00 |
March | 1439.81 | 04-MAR-15:09 | 3032.07 | 01-MAR-10:09 | 674.13 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2904.59 | 28-MAR-15:00 | 900.31 | 18-MAR-17:00 |
April | 1439.81 | 01-APR-14:09 | 3032.07 | 01-APR-09:09 | 674.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4149.36 | 15-APR-15:00 | 254.70 | 22-APR-18:10 |
May | 1439.81 | 06-MAY-14:09 | 3032.07 | 01-MAY-09:09 | 674.13 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5010.93 | 03-MAY-15:00 | 55.15 | 15-MAY-03:00 |
June | 1439.81 | 03-JUN-14:09 | 3032.07 | 01-JUN-09:09 | 674.13 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5023.36 | 07-JUN-16:00 | 95.29 | 18-JUN-07:01 |
July | 1439.81 | 01-JUL-14:09 | 3032.07 | 01-JUL-09:09 | 674.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4042.81 | 07-JUL-15:00 | 41.65 | 19-JUL-03:00 |
August | 1439.81 | 05-AUG-14:09 | 3032.07 | 01-AUG-09:09 | 674.13 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3349.35 | 07-AUG-15:00 | 348.03 | 20-AUG-17:00 |
September | 1439.81 | 02-SEP-14:09 | 3032.07 | 01-SEP-09:09 | 674.13 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3084.45 | 29-SEP-13:00 | 260.96 | 03-SEP-17:00 |
October | 1439.81 | 07-OCT-14:09 | 3032.07 | 01-OCT-10:09 | 674.13 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3139.78 | 02-OCT-14:00 | 301.40 | 29-OCT-07:03 |
November | 1439.81 | 04-NOV-14:09 | 3032.07 | 01-NOV-09:09 | 674.13 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1632.48 | 04-NOV-14:00 | 1275.91 | 30-NOV-18:00 |
December | 1439.81 | 02-DEC-15:09 | 3032.07 | 01-DEC-10:09 | 674.13 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 184.91 | 28-DEC-14:00 | 2863.25 | 21-DEC-12:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1439.81 | 3032.07 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.65 | |||||
Maximum of Months | 1439.81 | 3032.07 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 5023.36 | 2863.25 |
Report: PeakSpaceGainsMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1439.81 | 07-JAN-15:09 | 3032.07 | 01-JAN-11:09 | 674.13 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2363.22 | 15-JAN-17:00 |
February | 1439.81 | 04-FEB-15:09 | 3032.07 | 01-FEB-10:09 | 674.13 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 826.59 | 22-FEB-15:00 | 2235.09 | 10-FEB-18:00 |
March | 1439.81 | 04-MAR-15:09 | 3032.07 | 01-MAR-10:09 | 674.13 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2904.59 | 28-MAR-15:00 | 900.31 | 18-MAR-17:00 |
April | 1439.81 | 01-APR-14:09 | 3032.07 | 01-APR-09:09 | 674.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4149.36 | 15-APR-15:00 | 252.92 | 22-APR-18:10 |
May | 1439.81 | 06-MAY-14:09 | 3032.07 | 01-MAY-09:09 | 674.13 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5010.93 | 03-MAY-15:00 | 54.56 | 15-MAY-03:00 |
June | 1439.81 | 03-JUN-14:09 | 3032.07 | 01-JUN-09:09 | 674.13 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5023.36 | 07-JUN-16:00 | 93.93 | 18-JUN-07:01 |
July | 1439.81 | 01-JUL-14:09 | 3032.07 | 01-JUL-09:09 | 674.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4042.81 | 07-JUL-15:00 | 41.26 | 19-JUL-03:00 |
August | 1439.81 | 05-AUG-14:09 | 3032.07 | 01-AUG-09:09 | 674.13 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3349.36 | 07-AUG-15:00 | 342.84 | 20-AUG-17:00 |
September | 1439.81 | 02-SEP-14:09 | 3032.07 | 01-SEP-09:09 | 674.13 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3084.45 | 29-SEP-13:00 | 256.02 | 03-SEP-17:00 |
October | 1439.81 | 07-OCT-14:09 | 3032.07 | 01-OCT-10:09 | 674.13 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3139.78 | 02-OCT-14:00 | 300.07 | 29-OCT-07:03 |
November | 1439.81 | 04-NOV-14:09 | 3032.07 | 01-NOV-09:09 | 674.13 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1632.48 | 04-NOV-14:00 | 1275.91 | 30-NOV-18:00 |
December | 1439.81 | 02-DEC-15:09 | 3032.07 | 01-DEC-10:09 | 674.13 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 184.91 | 28-DEC-14:00 | 2850.75 | 21-DEC-12:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1439.81 | 3032.07 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.26 | |||||
Maximum of Months | 1439.81 | 3032.07 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 5023.36 | 2850.75 |
Report: PeakSpaceGainsMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1439.81 | 07-JAN-15:09 | 3032.07 | 01-JAN-11:09 | 674.13 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2330.43 | 15-JAN-17:00 |
February | 1439.81 | 04-FEB-15:09 | 3032.07 | 01-FEB-10:09 | 674.13 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 826.59 | 22-FEB-15:00 | 2194.85 | 10-FEB-18:00 |
March | 1439.81 | 04-MAR-15:09 | 3032.07 | 01-MAR-10:09 | 674.13 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2904.59 | 28-MAR-15:00 | 900.31 | 18-MAR-17:00 |
April | 1439.81 | 01-APR-14:09 | 3032.07 | 01-APR-09:09 | 674.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4149.36 | 15-APR-15:00 | 249.53 | 22-APR-18:10 |
May | 1439.81 | 06-MAY-14:09 | 3032.07 | 01-MAY-09:09 | 674.13 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5010.93 | 03-MAY-15:00 | 53.56 | 15-MAY-03:00 |
June | 1439.81 | 03-JUN-14:09 | 3032.07 | 01-JUN-09:09 | 674.13 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5023.36 | 07-JUN-16:00 | 92.06 | 18-JUN-07:01 |
July | 1439.81 | 01-JUL-14:09 | 3032.07 | 01-JUL-09:09 | 674.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4042.82 | 07-JUL-15:00 | 40.78 | 19-JUL-03:00 |
August | 1439.81 | 05-AUG-14:09 | 3032.07 | 01-AUG-09:09 | 674.13 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3349.37 | 07-AUG-15:00 | 344.47 | 20-AUG-17:00 |
September | 1439.81 | 02-SEP-14:09 | 3032.07 | 01-SEP-09:09 | 674.13 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3084.45 | 29-SEP-13:00 | 258.20 | 03-SEP-17:00 |
October | 1439.81 | 07-OCT-14:09 | 3032.07 | 01-OCT-10:09 | 674.13 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3139.79 | 02-OCT-14:00 | 296.67 | 29-OCT-07:03 |
November | 1439.81 | 04-NOV-14:09 | 3032.07 | 01-NOV-09:09 | 674.13 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1632.48 | 04-NOV-14:00 | 1275.91 | 30-NOV-18:00 |
December | 1439.81 | 02-DEC-15:09 | 3032.07 | 01-DEC-10:09 | 674.13 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 184.91 | 28-DEC-14:00 | 2818.52 | 21-DEC-12:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1439.81 | 3032.07 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.78 | |||||
Maximum of Months | 1439.81 | 3032.07 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 5023.36 | 2818.52 |
Report: PeakSpaceGainsMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1439.81 | 07-JAN-15:09 | 3032.07 | 01-JAN-11:09 | 674.13 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2317.83 | 15-JAN-17:00 |
February | 1439.81 | 04-FEB-15:09 | 3032.07 | 01-FEB-10:09 | 674.13 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 837.12 | 22-FEB-15:00 | 2129.85 | 10-FEB-18:00 |
March | 1439.81 | 04-MAR-15:09 | 3032.07 | 01-MAR-10:09 | 674.13 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2904.59 | 28-MAR-15:00 | 1098.95 | 24-MAR-24:00 |
April | 1439.81 | 01-APR-14:09 | 3032.07 | 01-APR-09:09 | 674.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4385.57 | 15-APR-15:00 | 400.26 | 22-APR-18:10 |
May | 1439.81 | 06-MAY-14:09 | 3032.07 | 01-MAY-09:09 | 674.13 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5132.86 | 03-MAY-15:00 | 126.47 | 15-MAY-03:00 |
June | 1439.81 | 03-JUN-14:09 | 3032.07 | 01-JUN-09:09 | 674.13 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5273.36 | 06-JUN-15:00 | 140.49 | 18-JUN-04:00 |
July | 1439.81 | 01-JUL-14:09 | 3032.07 | 01-JUL-09:09 | 674.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4120.44 | 07-JUL-15:00 | 101.93 | 19-JUL-03:00 |
August | 1439.81 | 05-AUG-14:09 | 3032.07 | 01-AUG-09:09 | 674.13 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3436.66 | 07-AUG-15:00 | 443.69 | 20-AUG-17:00 |
September | 1439.81 | 02-SEP-14:09 | 3032.07 | 01-SEP-09:09 | 674.13 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3172.67 | 29-SEP-13:00 | 344.86 | 03-SEP-17:00 |
October | 1439.81 | 07-OCT-14:09 | 3032.07 | 01-OCT-10:09 | 674.13 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3189.20 | 02-OCT-14:00 | 320.14 | 29-OCT-07:03 |
November | 1439.81 | 04-NOV-14:09 | 3032.07 | 01-NOV-09:09 | 674.13 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1648.25 | 04-NOV-14:00 | 1285.99 | 30-NOV-18:00 |
December | 1439.81 | 02-DEC-15:09 | 3032.07 | 01-DEC-10:09 | 674.13 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 189.40 | 28-DEC-14:00 | 2822.41 | 21-DEC-12:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1439.81 | 3032.07 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.93 | |||||
Maximum of Months | 1439.81 | 3032.07 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 5273.36 | 2822.41 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 12067.43 | 12-JAN-15:00 | 1439.81 | 9537.57 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 141.18 |
February | 16321.28 | 22-FEB-15:00 | 1439.81 | 9537.57 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 1458.22 | 0.00 |
March | 47516.18 | 30-MAR-07:02 | 899.88 | 2509.89 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 171.95 |
April | 55661.89 | 08-APR-07:02 | 0.00 | 2509.89 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 20.34 | 0.00 |
May | 56098.66 | 06-MAY-07:01 | 0.00 | 4015.82 | 599.22 | 0.00 | 0.00 | 0.00 | 0.00 | 257.41 | 0.00 |
June | 53188.15 | 07-JUN-07:01 | 1799.77 | 5019.77 | 749.03 | 0.00 | 0.00 | 0.00 | 0.00 | 611.19 | 0.00 |
July | 45306.05 | 07-JUL-07:01 | 0.00 | 5019.77 | 749.03 | 0.00 | 0.00 | 0.00 | 0.00 | 444.49 | 0.00 |
August | 40546.01 | 14-AUG-07:01 | 1619.79 | 4517.80 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 136.94 | 0.00 |
September | 45311.66 | 26-SEP-07:01 | 1259.84 | 3513.84 | 524.32 | 0.00 | 0.00 | 0.00 | 0.00 | 7.48 | 0.00 |
October | 51705.63 | 23-OCT-07:02 | 899.88 | 2509.89 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 289.08 |
November | 33955.27 | 09-NOV-08:62 | 719.91 | 2007.91 | 299.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 285.56 |
December | 14015.50 | 02-DEC-14:00 | 2159.72 | 9537.57 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 93.30 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 12067.43 | 0.00 | 2007.91 | 299.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 56098.66 | 2159.72 | 9537.57 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 1458.22 | 289.08 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6213.79 | 12-JAN-14:50 | 719.90 | 4768.79 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.26 |
February | 8797.79 | 25-FEB-08:63 | 0.00 | 752.97 | 112.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 218.81 |
March | 24922.11 | 30-MAR-07:02 | 449.94 | 1254.94 | 187.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.04 |
April | 28157.58 | 08-APR-07:02 | 0.00 | 1254.94 | 187.26 | 0.00 | 0.00 | 0.00 | 0.00 | 7.88 | 0.00 |
May | 28217.22 | 06-MAY-07:01 | 0.00 | 2007.91 | 299.61 | 0.00 | 0.00 | 0.00 | 0.00 | 145.29 | 0.00 |
June | 26460.45 | 07-JUN-07:01 | 899.88 | 2509.89 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 320.39 | 0.00 |
July | 23674.42 | 07-JUL-07:01 | 0.00 | 2509.89 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 243.72 | 0.00 |
August | 22178.63 | 14-AUG-07:01 | 809.89 | 2258.90 | 337.06 | 0.00 | 0.00 | 0.00 | 0.00 | 85.19 | 0.00 |
September | 24610.86 | 26-SEP-07:01 | 629.92 | 1756.92 | 262.16 | 0.00 | 0.00 | 0.00 | 0.00 | 12.98 | 0.00 |
October | 26867.77 | 25-OCT-07:02 | 449.94 | 1254.94 | 187.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 151.17 |
November | 17501.53 | 09-NOV-08:62 | 359.95 | 1003.95 | 149.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 160.97 |
December | 7286.21 | 02-DEC-14:00 | 1079.86 | 4768.79 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 53.07 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 6213.79 | 0.00 | 752.97 | 112.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 28217.22 | 1079.86 | 4768.79 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 320.39 | 218.81 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5240.90 | 12-JAN-14:50 | 539.93 | 3744.57 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.26 |
February | 7616.16 | 22-FEB-14:00 | 719.90 | 3744.57 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 799.67 | 0.00 |
March | 24397.00 | 29-MAR-06:02 | 0.00 | 985.41 | 187.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.20 |
April | 27644.60 | 08-APR-06:02 | 0.00 | 985.41 | 187.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.03 |
May | 27698.73 | 06-MAY-06:01 | 0.00 | 1773.74 | 337.06 | 0.00 | 0.00 | 0.00 | 0.00 | 6.31 | 0.00 |
June | 25437.62 | 12-JUN-06:01 | 0.00 | 1970.82 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 27.82 | 0.00 |
July | 19907.19 | 05-JUL-06:01 | 0.00 | 1970.82 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 18.11 | 0.00 |
August | 17359.77 | 03-AUG-06:01 | 0.00 | 1773.74 | 337.06 | 0.00 | 0.00 | 0.00 | 0.00 | 4.11 | 0.00 |
September | 20956.26 | 27-SEP-06:01 | 0.00 | 1379.58 | 262.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 |
October | 26298.44 | 23-OCT-06:02 | 0.00 | 985.41 | 187.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.68 |
November | 10718.39 | 09-NOV-07:03 | 0.00 | 591.25 | 112.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.81 |
December | 6442.79 | 02-DEC-14:00 | 1079.86 | 3744.57 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 53.08 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 5240.90 | 0.00 | 591.25 | 112.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 27698.73 | 1079.86 | 3744.57 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 799.67 | 92.26 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5052.13 | 12-JAN-14:50 | 539.93 | 3744.57 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.27 |
February | 7491.74 | 22-FEB-14:00 | 719.90 | 3744.57 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 799.66 | 0.00 |
March | 24347.56 | 29-MAR-06:02 | 0.00 | 985.41 | 187.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.21 |
April | 27608.11 | 08-APR-06:02 | 0.00 | 985.41 | 187.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.08 |
May | 27701.66 | 06-MAY-06:01 | 0.00 | 1773.74 | 337.06 | 0.00 | 0.00 | 0.00 | 0.00 | 6.11 | 0.00 |
June | 25592.05 | 12-JUN-06:01 | 0.00 | 1970.82 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 26.97 | 0.00 |
July | 20146.81 | 05-JUL-06:01 | 0.00 | 1970.82 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 17.34 | 0.00 |
August | 17393.86 | 03-AUG-06:01 | 0.00 | 1773.74 | 337.06 | 0.00 | 0.00 | 0.00 | 0.00 | 3.94 | 0.00 |
September | 20961.86 | 27-SEP-06:01 | 0.00 | 1379.58 | 262.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.04 |
October | 26301.63 | 23-OCT-06:02 | 0.00 | 985.41 | 187.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.75 |
November | 10314.40 | 09-NOV-07:03 | 0.00 | 591.25 | 112.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.81 |
December | 6292.49 | 02-DEC-14:00 | 1079.86 | 3744.57 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 53.07 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 5052.13 | 0.00 | 591.25 | 112.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 27701.66 | 1079.86 | 3744.57 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 799.66 | 92.27 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4879.52 | 12-JAN-14:50 | 539.93 | 3744.57 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.27 |
February | 7352.67 | 22-FEB-14:00 | 719.90 | 3744.57 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 799.66 | 0.00 |
March | 24181.08 | 29-MAR-06:02 | 0.00 | 985.41 | 187.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.16 |
April | 27511.41 | 08-APR-06:02 | 0.00 | 985.41 | 187.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.74 |
May | 27584.70 | 06-MAY-06:01 | 0.00 | 1773.74 | 337.06 | 0.00 | 0.00 | 0.00 | 0.00 | 6.42 | 0.00 |
June | 25545.00 | 12-JUN-06:01 | 0.00 | 1970.82 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 27.01 | 0.00 |
July | 20076.85 | 05-JUL-06:01 | 0.00 | 1970.82 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 17.41 | 0.00 |
August | 17188.24 | 03-AUG-06:01 | 0.00 | 1773.74 | 337.06 | 0.00 | 0.00 | 0.00 | 0.00 | 4.32 | 0.00 |
September | 20808.71 | 27-SEP-06:01 | 0.00 | 1379.58 | 262.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.94 |
October | 26196.71 | 23-OCT-06:02 | 0.00 | 985.41 | 187.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.66 |
November | 9422.46 | 04-NOV-14:00 | 719.90 | 3744.57 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1632.49 | 0.00 |
December | 6153.16 | 02-DEC-14:00 | 1079.86 | 3744.57 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 53.07 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 4879.52 | 0.00 | 985.41 | 187.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 27584.70 | 1079.86 | 3744.57 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1632.49 | 92.27 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 8683.74 | 12-JAN-15:10 | 2483.68 | 6064.13 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 161.83 |
February | 13346.48 | 22-FEB-14:00 | 2555.67 | 6064.13 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 1400.83 | 0.00 |
March | 43498.74 | 30-MAR-07:02 | 0.00 | 1595.82 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 164.23 |
April | 51238.44 | 30-APR-08:61 | 0.00 | 2234.15 | 524.32 | 0.00 | 0.00 | 0.00 | 0.00 | 42.01 | 0.00 |
May | 51230.06 | 29-MAY-08:61 | 0.00 | 3191.65 | 749.03 | 0.00 | 0.00 | 0.00 | 0.00 | 402.22 | 0.00 |
June | 47724.30 | 12-JUN-07:01 | 0.00 | 3191.65 | 749.03 | 0.00 | 0.00 | 0.00 | 0.00 | 537.22 | 0.00 |
July | 40214.54 | 07-JUL-07:01 | 0.00 | 3191.65 | 749.03 | 0.00 | 0.00 | 0.00 | 0.00 | 418.80 | 0.00 |
August | 35627.88 | 08-AUG-07:01 | 0.00 | 3191.65 | 749.03 | 0.00 | 0.00 | 0.00 | 0.00 | 220.70 | 0.00 |
September | 40734.96 | 27-SEP-07:02 | 0.00 | 1914.99 | 449.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.33 |
October | 48379.53 | 23-OCT-07:02 | 0.00 | 1595.82 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 288.21 |
November | 24650.57 | 09-NOV-08:62 | 0.00 | 1276.66 | 299.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 277.52 |
December | 10972.43 | 02-DEC-14:10 | 2771.64 | 6064.13 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 77.69 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 8683.74 | 0.00 | 1276.66 | 299.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 51238.44 | 2771.64 | 6064.13 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 1400.83 | 288.21 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4456.37 | 12-JAN-15:10 | 1241.83 | 3032.07 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.21 |
February | 6940.60 | 22-FEB-14:00 | 1277.83 | 3032.07 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 799.91 | 0.00 |
March | 21741.45 | 30-MAR-07:02 | 0.00 | 797.91 | 187.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.49 |
April | 26669.70 | 30-APR-08:61 | 0.00 | 1117.08 | 262.16 | 0.00 | 0.00 | 0.00 | 0.00 | 29.01 | 0.00 |
May | 26708.80 | 29-MAY-08:61 | 0.00 | 1595.82 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 225.85 | 0.00 |
June | 24888.80 | 12-JUN-07:01 | 0.00 | 1595.82 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 304.99 | 0.00 |
July | 20967.88 | 07-JUL-07:01 | 0.00 | 1595.82 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 242.10 | 0.00 |
August | 18568.63 | 08-AUG-07:01 | 0.00 | 1595.82 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 129.49 | 0.00 |
September | 21193.65 | 27-SEP-07:02 | 0.00 | 957.49 | 224.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.43 |
October | 25175.93 | 23-OCT-07:02 | 0.00 | 797.91 | 187.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 159.99 |
November | 11317.19 | 09-NOV-08:62 | 0.00 | 638.33 | 149.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 158.10 |
December | 5654.57 | 02-DEC-14:10 | 1385.82 | 3032.07 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 44.37 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 4456.37 | 0.00 | 638.33 | 149.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 26708.80 | 1385.82 | 3032.07 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 799.91 | 159.99 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4383.23 | 12-JAN-15:10 | 1241.83 | 3032.07 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.21 |
February | 6866.41 | 22-FEB-14:00 | 1277.83 | 3032.07 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 799.91 | 0.00 |
March | 21074.37 | 30-MAR-07:02 | 0.00 | 797.91 | 187.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.33 |
April | 26540.66 | 30-APR-08:61 | 0.00 | 1117.08 | 262.16 | 0.00 | 0.00 | 0.00 | 0.00 | 30.14 | 0.00 |
May | 26607.60 | 29-MAY-08:61 | 0.00 | 1595.82 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 226.62 | 0.00 |
June | 24780.40 | 12-JUN-07:01 | 0.00 | 1595.82 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 305.48 | 0.00 |
July | 20842.48 | 07-JUL-07:01 | 0.00 | 1595.82 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 243.18 | 0.00 |
August | 18460.50 | 08-AUG-07:01 | 0.00 | 1595.82 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 130.36 | 0.00 |
September | 21076.53 | 27-SEP-07:02 | 0.00 | 957.49 | 224.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.48 |
October | 25067.23 | 23-OCT-07:02 | 0.00 | 797.91 | 187.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 159.24 |
November | 10873.83 | 09-NOV-08:62 | 0.00 | 638.33 | 149.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 157.92 |
December | 5590.38 | 02-DEC-14:10 | 1385.82 | 3032.07 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 44.37 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 4383.23 | 0.00 | 638.33 | 149.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 26607.60 | 1385.82 | 3032.07 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 799.91 | 159.24 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4224.42 | 12-JAN-15:10 | 1241.83 | 3032.07 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.21 |
February | 6744.44 | 22-FEB-14:00 | 1277.83 | 3032.07 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 799.91 | 0.00 |
March | 20537.53 | 11-MAR-08:62 | 0.00 | 797.91 | 187.26 | 0.00 | 0.00 | 0.00 | 0.00 | 14.96 | 0.00 |
April | 26522.56 | 30-APR-08:61 | 0.00 | 1117.08 | 262.16 | 0.00 | 0.00 | 0.00 | 0.00 | 32.63 | 0.00 |
May | 26648.52 | 29-MAY-08:61 | 0.00 | 1595.82 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 227.53 | 0.00 |
June | 24868.65 | 12-JUN-07:01 | 0.00 | 1595.82 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 304.24 | 0.00 |
July | 20928.59 | 07-JUL-07:01 | 0.00 | 1595.82 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 242.21 | 0.00 |
August | 18542.62 | 08-AUG-07:01 | 0.00 | 1595.82 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 129.42 | 0.00 |
September | 21113.39 | 27-SEP-07:02 | 0.00 | 957.49 | 224.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.92 |
October | 25071.76 | 23-OCT-07:02 | 0.00 | 797.91 | 187.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 157.55 |
November | 9731.10 | 09-NOV-08:62 | 0.00 | 638.33 | 149.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 157.48 |
December | 5460.37 | 02-DEC-14:10 | 1385.82 | 3032.07 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 44.37 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 4224.42 | 0.00 | 638.33 | 149.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 26648.52 | 1385.82 | 3032.07 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 799.91 | 157.55 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4235.07 | 12-JAN-15:10 | 1241.83 | 3032.07 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.12 |
February | 7182.68 | 22-FEB-14:00 | 1277.83 | 3032.07 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 807.39 | 0.00 |
March | 16399.09 | 11-MAR-08:62 | 0.00 | 797.91 | 187.26 | 0.00 | 0.00 | 0.00 | 0.00 | 17.00 | 0.00 |
April | 28713.49 | 30-APR-08:61 | 0.00 | 1117.08 | 262.16 | 0.00 | 0.00 | 0.00 | 0.00 | 40.76 | 0.00 |
May | 29187.26 | 29-MAY-08:61 | 0.00 | 1595.82 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 297.22 | 0.00 |
June | 27947.34 | 12-JUN-07:01 | 0.00 | 1595.82 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 343.77 | 0.00 |
July | 22764.45 | 07-JUL-07:01 | 0.00 | 1595.82 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 261.03 | 0.00 |
August | 19751.62 | 15-AUG-07:01 | 0.00 | 1276.66 | 299.61 | 0.00 | 0.00 | 0.00 | 0.00 | 38.69 | 0.00 |
September | 23112.52 | 27-SEP-07:02 | 0.00 | 957.49 | 224.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.09 |
October | 25687.76 | 02-OCT-07:01 | 0.00 | 1117.08 | 262.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.21 |
November | 9631.90 | 04-NOV-13:50 | 1385.82 | 3032.07 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1640.65 | 0.00 |
December | 5671.36 | 01-DEC-14:00 | 1277.83 | 3032.07 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.43 |
Annual Sum or Average | |||||||||||
Minimum of Months | 4235.07 | 0.00 | 797.91 | 187.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 29187.26 | 1385.82 | 3032.07 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1640.65 | 104.43 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | |
January | 0.130600E+12 | 106169.08 | 12-JAN-17:49 | 0.251344E+10 | 94354.47 | 02-JAN-08:09 |
February | 0.129663E+12 | 118557.28 | 22-FEB-14:50 | 0.171231E+09 | 18079.02 | 02-FEB-08:30 |
March | 0.166871E+12 | 146685.11 | 28-MAR-14:50 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 0.189466E+12 | 168874.14 | 16-APR-14:00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 0.225146E+12 | 186789.69 | 03-MAY-14:50 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 0.228208E+12 | 197558.14 | 10-JUN-15:50 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 0.231943E+12 | 192208.00 | 01-JUL-13:50 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.231294E+12 | 184916.50 | 27-AUG-14:20 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 0.209126E+12 | 174988.18 | 14-SEP-14:00 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 0.187146E+12 | 162125.35 | 04-OCT-12:20 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 0.154951E+12 | 131471.26 | 06-NOV-13:39 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 0.135839E+12 | 109894.40 | 28-DEC-13:00 | 0.336949E+09 | 28912.24 | 21-DEC-08:30 |
Annual Sum or Average | 0.222025E+13 | 0.302162E+10 | ||||
Minimum of Months | 0.129663E+12 | 106169.08 | 0.00 | 0.00 | ||
Maximum of Months | 0.231943E+12 | 197558.14 | 0.251344E+10 | 94354.47 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.599295E+11 | 0.160528E+11 | 0.108804E+11 | 0.00 | 0.296236E+11 | 0.00 | 0.00 | 0.887735E+10 | 0.00 | 0.00 | 0.00 | 0.523606E+10 | 0.00 |
February | 0.542583E+11 | 0.138916E+11 | 0.985143E+10 | 0.00 | 0.268513E+11 | 0.00 | 0.00 | 0.201041E+11 | 0.00 | 0.00 | 0.00 | 0.470657E+10 | 0.00 |
March | 0.607812E+11 | 0.143952E+11 | 0.110523E+11 | 0.00 | 0.301894E+11 | 0.00 | 0.00 | 0.453042E+11 | 0.00 | 0.00 | 0.00 | 0.514886E+10 | 0.00 |
April | 0.581548E+11 | 0.129672E+11 | 0.105581E+11 | 0.00 | 0.288941E+11 | 0.00 | 0.00 | 0.740569E+11 | 0.00 | 0.00 | 0.00 | 0.483493E+10 | 0.00 |
May | 0.603309E+11 | 0.125528E+11 | 0.109629E+11 | 0.00 | 0.300839E+11 | 0.00 | 0.00 | 0.106335E+12 | 0.00 | 0.00 | 0.00 | 0.488058E+10 | 0.00 |
June | 0.587570E+11 | 0.116921E+11 | 0.106818E+11 | 0.00 | 0.293526E+11 | 0.00 | 0.00 | 0.113078E+12 | 0.00 | 0.00 | 0.00 | 0.464703E+10 | 0.00 |
July | 0.597776E+11 | 0.123296E+11 | 0.108460E+11 | 0.00 | 0.298325E+11 | 0.00 | 0.00 | 0.114419E+12 | 0.00 | 0.00 | 0.00 | 0.473780E+10 | 0.00 |
August | 0.607324E+11 | 0.130118E+11 | 0.110454E+11 | 0.00 | 0.303585E+11 | 0.00 | 0.00 | 0.111352E+12 | 0.00 | 0.00 | 0.00 | 0.479372E+10 | 0.00 |
September | 0.582036E+11 | 0.135154E+11 | 0.105649E+11 | 0.00 | 0.289867E+11 | 0.00 | 0.00 | 0.931480E+11 | 0.00 | 0.00 | 0.00 | 0.470700E+10 | 0.00 |
October | 0.599295E+11 | 0.149690E+11 | 0.108804E+11 | 0.00 | 0.297668E+11 | 0.00 | 0.00 | 0.666278E+11 | 0.00 | 0.00 | 0.00 | 0.497249E+10 | 0.00 |
November | 0.580572E+11 | 0.153196E+11 | 0.105443E+11 | 0.00 | 0.287818E+11 | 0.00 | 0.00 | 0.373147E+11 | 0.00 | 0.00 | 0.00 | 0.493319E+10 | 0.00 |
December | 0.598264E+11 | 0.163524E+11 | 0.108529E+11 | 0.00 | 0.295457E+11 | 0.00 | 0.00 | 0.140655E+11 | 0.00 | 0.00 | 0.00 | 0.519631E+10 | 0.00 |
Annual Sum or Average | 0.708738E+12 | 0.167050E+12 | 0.128721E+12 | 0.352267E+12 | 0.00 | 0.804683E+12 | 0.587945E+11 | ||||||
Minimum of Months | 0.542583E+11 | 0.116921E+11 | 0.985143E+10 | 0.00 | 0.268513E+11 | 0.00 | 0.00 | 0.887735E+10 | 0.00 | 0.00 | 0.00 | 0.464703E+10 | 0.00 |
Maximum of Months | 0.607812E+11 | 0.163524E+11 | 0.110523E+11 | 0.00 | 0.303585E+11 | 0.00 | 0.00 | 0.114419E+12 | 0.00 | 0.00 | 0.00 | 0.523606E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS [J] | COOLING:GAS [] | WATERSYSTEMS:GAS [] | COGENERATION:GAS [] | HUMIDIFIER:GAS [] | |
January | 0.00 | 0.00 | 0.251344E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.171231E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.336949E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.302162E+10 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.251344E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum}[W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum}[W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum}[W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum}[W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 43732.45 | 01-JAN-11:09 | 10625.34 | 01-JAN-00:10 | 8089.53 | 01-JAN-11:09 | 0.00 | 20381.82 | 13-JAN-17:00 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 43732.45 | 01-FEB-10:09 | 10625.34 | 01-FEB-00:10 | 8089.53 | 01-FEB-10:09 | 0.00 | 20381.82 | 01-FEB-11:30 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 43732.45 | 01-MAR-10:09 | 10625.34 | 01-MAR-00:10 | 8089.53 | 01-MAR-10:09 | 0.00 | 20381.82 | 06-MAR-15:50 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 43732.45 | 01-APR-09:09 | 10625.34 | 01-APR-00:10 | 8089.53 | 01-APR-09:09 | 0.00 | 20381.82 | 03-APR-11:39 | 0.00 | 0.00 | 01-APR-00:10 |
May | 43732.45 | 01-MAY-09:09 | 10625.34 | 01-MAY-00:10 | 8089.53 | 01-MAY-09:09 | 0.00 | 20381.82 | 01-MAY-12:20 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 43732.45 | 01-JUN-09:09 | 10625.34 | 01-JUN-00:10 | 8089.53 | 01-JUN-09:09 | 0.00 | 20381.82 | 02-JUN-09:30 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 43732.45 | 01-JUL-09:09 | 10625.34 | 01-JUL-00:10 | 8089.53 | 01-JUL-09:09 | 0.00 | 20381.82 | 01-JUL-15:39 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 43732.45 | 01-AUG-09:09 | 10625.34 | 01-AUG-00:10 | 8089.53 | 01-AUG-09:09 | 0.00 | 20381.82 | 16-AUG-15:50 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 43732.45 | 01-SEP-09:09 | 10625.34 | 01-SEP-00:10 | 8089.53 | 01-SEP-09:09 | 0.00 | 20381.82 | 06-SEP-07:40 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 43732.45 | 01-OCT-10:09 | 10625.34 | 01-OCT-00:10 | 8089.53 | 01-OCT-10:09 | 0.00 | 20381.82 | 03-OCT-13:09 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 43732.45 | 01-NOV-09:09 | 10625.34 | 01-NOV-00:10 | 8089.53 | 01-NOV-09:09 | 0.00 | 20381.82 | 01-NOV-11:39 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 43732.45 | 01-DEC-10:09 | 10625.34 | 01-DEC-00:10 | 8089.53 | 01-DEC-10:09 | 0.00 | 20381.82 | 07-DEC-18:40 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 43732.45 | 10625.34 | 8089.53 | 0.00 | 20381.82 | 0.00 | 0.00 | |||||
Maximum of Months | 43732.45 | 10625.34 | 8089.53 | 0.00 | 20381.82 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum}[W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum}[W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 24697.86 | 12-JAN-14:00 | 0.00 | 0.00 | 0.00 | 11785.84 | 02-JAN-12:39 | 0.00 |
February | 39881.64 | 22-FEB-13:00 | 0.00 | 0.00 | 0.00 | 9675.43 | 10-FEB-12:50 | 0.00 |
March | 69586.86 | 28-MAR-14:00 | 0.00 | 0.00 | 0.00 | 9184.67 | 03-MAR-18:40 | 0.00 |
April | 93351.57 | 16-APR-14:00 | 0.00 | 0.00 | 0.00 | 7559.37 | 12-APR-12:30 | 0.00 |
May | 109785.24 | 03-MAY-14:00 | 0.00 | 0.00 | 0.00 | 7530.47 | 05-MAY-15:30 | 0.00 |
June | 118159.00 | 10-JUN-15:00 | 0.00 | 0.00 | 0.00 | 7529.00 | 20-JUN-14:20 | 0.00 |
July | 114811.66 | 01-JUL-14:30 | 0.00 | 0.00 | 0.00 | 9596.09 | 17-JUL-09:09 | 0.00 |
August | 109474.04 | 27-AUG-14:09 | 0.00 | 0.00 | 0.00 | 7541.13 | 18-AUG-12:50 | 0.00 |
September | 97356.72 | 14-SEP-14:00 | 0.00 | 0.00 | 0.00 | 9213.92 | 07-SEP-13:50 | 0.00 |
October | 84514.58 | 03-OCT-13:00 | 0.00 | 0.00 | 0.00 | 7625.89 | 04-OCT-12:20 | 0.00 |
November | 53147.07 | 09-NOV-13:30 | 0.00 | 0.00 | 0.00 | 9682.58 | 22-NOV-14:39 | 0.00 |
December | 30114.89 | 28-DEC-13:00 | 0.00 | 0.00 | 0.00 | 9634.89 | 03-DEC-17:40 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 24697.86 | 0.00 | 0.00 | 0.00 | 7529.00 | 0.00 | ||
Maximum of Months | 118159.00 | 0.00 | 0.00 | 0.00 | 11785.84 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 106169.08 | 12-JAN-17:49 | 43732.45 | 8089.53 | 10625.34 | 0.00 | 20381.82 | 0.00 | 0.00 | 15789.54 | 0.00 |
February | 118557.28 | 22-FEB-14:50 | 43732.45 | 8089.53 | 0.00 | 0.00 | 20381.82 | 0.00 | 0.00 | 39807.58 | 0.00 |
March | 146685.11 | 28-MAR-14:50 | 43732.45 | 8089.53 | 0.00 | 0.00 | 20381.82 | 0.00 | 0.00 | 69281.81 | 0.00 |
April | 168874.14 | 16-APR-14:00 | 43732.45 | 8089.53 | 0.00 | 0.00 | 20381.82 | 0.00 | 0.00 | 93351.57 | 0.00 |
May | 186789.69 | 03-MAY-14:50 | 43732.45 | 8089.53 | 0.00 | 0.00 | 20381.82 | 0.00 | 0.00 | 109155.05 | 0.00 |
June | 197558.14 | 10-JUN-15:50 | 43732.45 | 8089.53 | 0.00 | 0.00 | 20381.82 | 0.00 | 0.00 | 117828.68 | 0.00 |
July | 192208.00 | 01-JUL-13:50 | 43732.45 | 8089.53 | 0.00 | 0.00 | 20381.82 | 0.00 | 0.00 | 114573.92 | 0.00 |
August | 184916.50 | 27-AUG-14:20 | 43732.45 | 8089.53 | 0.00 | 0.00 | 20381.82 | 0.00 | 0.00 | 109396.44 | 0.00 |
September | 174988.18 | 14-SEP-14:00 | 43732.45 | 8089.53 | 0.00 | 0.00 | 20381.82 | 0.00 | 0.00 | 97356.72 | 0.00 |
October | 162125.35 | 04-OCT-12:20 | 43732.45 | 8089.53 | 0.00 | 0.00 | 20381.82 | 0.00 | 0.00 | 82295.66 | 0.00 |
November | 131471.26 | 06-NOV-13:39 | 43732.45 | 8089.53 | 0.00 | 0.00 | 20381.82 | 0.00 | 0.00 | 52332.41 | 0.00 |
December | 109894.40 | 28-DEC-13:00 | 43732.45 | 8089.53 | 0.00 | 0.00 | 20381.82 | 0.00 | 0.00 | 30114.89 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 106169.08 | 43732.45 | 8089.53 | 0.00 | 0.00 | 20381.82 | 0.00 | 0.00 | 15789.54 | 0.00 | |
Maximum of Months | 197558.14 | 43732.45 | 8089.53 | 10625.34 | 0.00 | 20381.82 | 0.00 | 0.00 | 117828.68 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS {Maximum}[W] | HEATING:GAS {TIMESTAMP} | COOLING:GAS [] | WATERSYSTEMS:GAS [] | COGENERATION:GAS [] | |
January | 0.00 | 0.00 | 94354.47 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 18079.02 | 02-FEB-08:30 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 28912.24 | 21-DEC-08:30 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 94354.47 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 24.54 | 0.50 | 24.57 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 24.62 | 2.00 | 24.62 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 24.72 | 3.67 | 24.70 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 24.62 | 2.83 | 24.65 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.55 | 0.17 | 24.55 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 13.17 | 24.65 | 9.17 | 24.66 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 24.72 | 3.67 | 24.70 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.50 | 0.33 | 24.50 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 24.52 | 1.50 | 24.53 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 24.59 | 2.33 | 24.60 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 24.52 | 1.50 | 24.52 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 7.67 | 24.55 | 5.67 | 24.55 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 24.59 | 2.33 | 24.60 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 24.52 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 24.66 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 24.87 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 24.75 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 24.58 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 17.17 | 24.73 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 24.87 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 24.54 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 24.91 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 24.92 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 24.78 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 24.61 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 17.83 | 24.81 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 24.92 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 24.53 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 24.89 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 24.88 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 24.73 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 24.61 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 16.83 | 24.78 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 24.89 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 24.60 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 24.66 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 25.13 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 24.74 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 24.67 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 15.83 | 24.81 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 25.13 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 24.57 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 24.61 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 24.92 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 24.72 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 24.65 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 14.00 | 24.73 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 24.92 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 24.57 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 24.60 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 24.91 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 24.71 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 24.65 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 14.00 | 24.72 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 24.91 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 24.57 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 24.60 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 24.90 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 24.72 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 24.67 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 13.33 | 24.73 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 24.90 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 25.47 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 24.94 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 25.53 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 24.98 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 24.69 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 16.67 | 25.18 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 25.53 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: LGSTORE1
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 104.17 | 22.52 | 184.50 | 23.89 | 0.00 | 0.00 |
February | 42.33 | 22.85 | 306.33 | 23.89 | 0.00 | 0.00 |
March | 8.00 | 23.63 | 441.00 | 23.89 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 469.50 | 23.89 | 0.00 | 0.00 |
May | 16.50 | 23.97 | 496.00 | 23.89 | 16.50 | 23.97 |
June | 101.83 | 23.91 | 480.00 | 23.89 | 101.83 | 23.91 |
July | 288.83 | 23.90 | 496.00 | 23.90 | 288.83 | 23.90 |
August | 325.67 | 23.90 | 496.00 | 23.89 | 325.67 | 23.90 |
September | 197.17 | 23.90 | 480.00 | 23.89 | 197.17 | 23.90 |
October | 3.17 | 23.90 | 491.33 | 23.89 | 3.17 | 23.90 |
November | 6.67 | 23.47 | 422.50 | 23.89 | 0.00 | 0.00 |
December | 70.00 | 22.90 | 264.50 | 23.89 | 0.00 | 0.00 |
Annual Sum or Average | 1164.33 | 23.67 | 5027.67 | 23.89 | 933.17 | 23.90 |
Minimum of Months | 0.00 | 0.00 | 184.50 | 23.89 | 0.00 | 0.00 |
Maximum of Months | 325.67 | 23.97 | 496.00 | 23.90 | 325.67 | 23.97 |
Report: ComfortReportSimple55Monthly
For: SMSTORE1
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 81.17 | 22.62 | 149.17 | 23.89 | 0.00 | 0.00 |
February | 34.50 | 23.02 | 276.33 | 23.89 | 0.00 | 0.00 |
March | 4.33 | 23.75 | 430.17 | 23.89 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 468.67 | 23.89 | 0.00 | 0.00 |
May | 9.83 | 23.97 | 496.00 | 23.89 | 9.83 | 23.97 |
June | 87.33 | 23.90 | 480.00 | 23.89 | 87.33 | 23.90 |
July | 254.17 | 23.90 | 496.00 | 23.89 | 254.17 | 23.90 |
August | 268.83 | 23.89 | 496.00 | 23.89 | 268.83 | 23.89 |
September | 169.17 | 23.89 | 480.00 | 23.89 | 169.17 | 23.89 |
October | 0.00 | 0.00 | 486.00 | 23.89 | 0.00 | 0.00 |
November | 5.33 | 23.54 | 396.67 | 23.89 | 0.00 | 0.00 |
December | 61.00 | 23.11 | 229.83 | 23.89 | 0.00 | 0.00 |
Annual Sum or Average | 975.67 | 23.71 | 4884.83 | 23.89 | 789.33 | 23.90 |
Minimum of Months | 0.00 | 0.00 | 149.17 | 23.89 | 0.00 | 0.00 |
Maximum of Months | 268.83 | 23.97 | 496.00 | 23.89 | 268.83 | 23.97 |
Report: ComfortReportSimple55Monthly
For: SMSTORE2
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 107.00 | 22.50 | 59.83 | 23.93 | 0.00 | 0.00 |
February | 38.83 | 22.76 | 198.17 | 24.03 | 0.00 | 0.00 |
March | 9.00 | 24.96 | 324.33 | 24.11 | 2.50 | 28.28 |
April | 12.33 | 28.89 | 350.00 | 24.21 | 12.33 | 28.89 |
May | 30.67 | 27.35 | 375.00 | 24.25 | 30.67 | 27.35 |
June | 112.33 | 24.92 | 366.00 | 24.25 | 112.33 | 24.92 |
July | 270.50 | 24.34 | 369.00 | 24.23 | 270.50 | 24.34 |
August | 288.17 | 24.28 | 379.00 | 24.20 | 288.17 | 24.28 |
September | 193.33 | 24.37 | 360.00 | 24.18 | 193.33 | 24.37 |
October | 12.83 | 27.12 | 367.67 | 24.14 | 12.83 | 27.12 |
November | 7.00 | 23.60 | 315.00 | 24.04 | 0.50 | 27.93 |
December | 75.33 | 22.91 | 136.33 | 23.95 | 0.00 | 0.00 |
Annual Sum or Average | 1157.33 | 24.23 | 3600.33 | 24.16 | 923.17 | 24.61 |
Minimum of Months | 7.00 | 22.50 | 59.83 | 23.93 | 0.00 | 0.00 |
Maximum of Months | 288.17 | 28.89 | 379.00 | 24.25 | 288.17 | 28.89 |
Report: ComfortReportSimple55Monthly
For: SMSTORE3
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 125.50 | 22.53 | 49.50 | 23.93 | 0.00 | 0.00 |
February | 42.33 | 22.73 | 185.00 | 24.03 | 0.00 | 0.00 |
March | 9.50 | 24.87 | 322.00 | 24.11 | 2.50 | 28.26 |
April | 12.33 | 28.89 | 350.00 | 24.21 | 12.33 | 28.89 |
May | 30.50 | 27.37 | 375.00 | 24.25 | 30.50 | 27.37 |
June | 112.17 | 24.92 | 366.00 | 24.25 | 112.17 | 24.92 |
July | 268.17 | 24.34 | 369.00 | 24.23 | 268.17 | 24.34 |
August | 287.50 | 24.28 | 379.00 | 24.20 | 287.50 | 24.28 |
September | 192.83 | 24.37 | 360.00 | 24.18 | 192.83 | 24.37 |
October | 12.67 | 27.11 | 367.33 | 24.14 | 12.67 | 27.11 |
November | 8.33 | 23.54 | 311.00 | 24.04 | 0.50 | 27.92 |
December | 82.67 | 22.88 | 113.17 | 23.95 | 0.00 | 0.00 |
Annual Sum or Average | 1184.50 | 24.19 | 3547.00 | 24.16 | 919.17 | 24.61 |
Minimum of Months | 8.33 | 22.53 | 49.50 | 23.93 | 0.00 | 0.00 |
Maximum of Months | 287.50 | 28.89 | 379.00 | 24.25 | 287.50 | 28.89 |
Report: ComfortReportSimple55Monthly
For: SMSTORE4
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 137.83 | 22.52 | 43.00 | 23.92 | 0.00 | 0.00 |
February | 47.67 | 22.72 | 176.33 | 24.03 | 0.00 | 0.00 |
March | 10.33 | 24.60 | 316.67 | 24.11 | 2.17 | 28.32 |
April | 12.00 | 28.88 | 349.17 | 24.21 | 12.00 | 28.88 |
May | 30.67 | 27.33 | 375.00 | 24.24 | 30.67 | 27.33 |
June | 113.17 | 24.90 | 366.00 | 24.25 | 113.17 | 24.90 |
July | 270.50 | 24.33 | 369.00 | 24.23 | 270.50 | 24.33 |
August | 289.67 | 24.28 | 379.00 | 24.19 | 289.67 | 24.28 |
September | 194.67 | 24.36 | 360.00 | 24.18 | 194.67 | 24.36 |
October | 12.83 | 26.99 | 367.33 | 24.14 | 12.83 | 26.99 |
November | 10.00 | 23.50 | 306.17 | 24.04 | 0.50 | 27.87 |
December | 88.67 | 22.84 | 101.83 | 23.95 | 0.00 | 0.00 |
Annual Sum or Average | 1218.00 | 24.14 | 3509.50 | 24.16 | 926.17 | 24.60 |
Minimum of Months | 10.00 | 22.52 | 43.00 | 23.92 | 0.00 | 0.00 |
Maximum of Months | 289.67 | 28.88 | 379.00 | 24.25 | 289.67 | 28.88 |
Report: ComfortReportSimple55Monthly
For: LGSTORE2
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 144.50 | 22.73 | 29.67 | 23.92 | 0.00 | 0.00 |
February | 42.17 | 22.91 | 144.50 | 23.95 | 0.00 | 0.00 |
March | 6.00 | 24.73 | 285.33 | 23.97 | 1.33 | 28.56 |
April | 5.83 | 29.03 | 320.00 | 24.02 | 5.83 | 29.03 |
May | 18.17 | 25.97 | 344.00 | 24.02 | 18.17 | 25.97 |
June | 100.67 | 24.22 | 336.00 | 24.00 | 100.67 | 24.22 |
July | 254.83 | 24.08 | 338.00 | 24.04 | 254.83 | 24.08 |
August | 272.00 | 24.01 | 348.00 | 23.98 | 272.00 | 24.01 |
September | 179.17 | 24.09 | 330.00 | 24.01 | 179.17 | 24.09 |
October | 8.17 | 26.89 | 338.50 | 24.00 | 8.17 | 26.89 |
November | 3.67 | 23.57 | 277.67 | 23.95 | 0.17 | 27.96 |
December | 78.67 | 22.95 | 85.17 | 23.91 | 0.00 | 0.00 |
Annual Sum or Average | 1113.83 | 23.86 | 3176.83 | 23.99 | 840.33 | 24.19 |
Minimum of Months | 3.67 | 22.73 | 29.67 | 23.91 | 0.00 | 0.00 |
Maximum of Months | 272.00 | 29.03 | 348.00 | 24.04 | 272.00 | 29.03 |
Report: ComfortReportSimple55Monthly
For: SMSTORE5
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 157.67 | 22.81 | 17.83 | 23.94 | 0.00 | 0.00 |
February | 47.67 | 22.99 | 117.17 | 23.96 | 0.00 | 0.00 |
March | 7.50 | 24.45 | 271.17 | 23.97 | 1.17 | 28.57 |
April | 5.50 | 29.01 | 313.67 | 24.02 | 5.50 | 29.01 |
May | 18.33 | 25.90 | 344.00 | 24.02 | 18.33 | 25.90 |
June | 101.00 | 24.21 | 336.00 | 24.00 | 101.00 | 24.21 |
July | 255.00 | 24.08 | 338.00 | 24.04 | 255.00 | 24.08 |
August | 277.83 | 24.00 | 348.00 | 23.98 | 277.83 | 24.00 |
September | 180.00 | 24.09 | 330.00 | 24.00 | 180.00 | 24.09 |
October | 7.83 | 26.83 | 337.00 | 24.00 | 7.83 | 26.83 |
November | 4.50 | 23.61 | 259.00 | 23.96 | 0.17 | 27.86 |
December | 84.33 | 23.00 | 66.67 | 23.92 | 0.00 | 0.00 |
Annual Sum or Average | 1147.17 | 23.85 | 3078.50 | 24.00 | 846.83 | 24.18 |
Minimum of Months | 4.50 | 22.81 | 17.83 | 23.92 | 0.00 | 0.00 |
Maximum of Months | 277.83 | 29.01 | 348.00 | 24.04 | 277.83 | 29.01 |
Report: ComfortReportSimple55Monthly
For: SMSTORE6
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 163.83 | 22.81 | 15.50 | 23.95 | 0.00 | 0.00 |
February | 48.83 | 22.97 | 109.00 | 23.96 | 0.00 | 0.00 |
March | 7.67 | 24.41 | 268.00 | 23.97 | 1.17 | 28.55 |
April | 5.50 | 29.00 | 313.17 | 24.02 | 5.50 | 29.00 |
May | 18.33 | 25.90 | 344.00 | 24.01 | 18.33 | 25.90 |
June | 101.33 | 24.21 | 336.00 | 24.00 | 101.33 | 24.21 |
July | 256.17 | 24.08 | 338.00 | 24.03 | 256.17 | 24.08 |
August | 278.50 | 24.00 | 348.00 | 23.98 | 278.50 | 24.00 |
September | 180.00 | 24.09 | 330.00 | 24.00 | 180.00 | 24.09 |
October | 7.83 | 26.74 | 336.67 | 24.00 | 7.83 | 26.74 |
November | 5.00 | 23.60 | 255.67 | 23.96 | 0.17 | 27.84 |
December | 88.50 | 23.01 | 60.83 | 23.92 | 0.00 | 0.00 |
Annual Sum or Average | 1161.50 | 23.84 | 3054.83 | 24.00 | 849.00 | 24.17 |
Minimum of Months | 5.00 | 22.81 | 15.50 | 23.92 | 0.00 | 0.00 |
Maximum of Months | 278.50 | 29.00 | 348.00 | 24.03 | 278.50 | 29.00 |
Report: ComfortReportSimple55Monthly
For: SMSTORE7
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 176.17 | 22.78 | 12.00 | 23.96 | 0.00 | 0.00 |
February | 54.33 | 22.93 | 97.50 | 23.96 | 0.00 | 0.00 |
March | 9.33 | 24.23 | 263.67 | 23.97 | 1.17 | 28.53 |
April | 5.33 | 29.03 | 312.33 | 24.02 | 5.33 | 29.03 |
May | 18.50 | 25.88 | 344.00 | 24.01 | 18.50 | 25.88 |
June | 101.33 | 24.21 | 336.00 | 24.00 | 101.33 | 24.21 |
July | 254.83 | 24.08 | 338.00 | 24.03 | 254.83 | 24.08 |
August | 277.50 | 24.00 | 348.00 | 23.98 | 277.50 | 24.00 |
September | 179.83 | 24.09 | 330.00 | 24.00 | 179.83 | 24.09 |
October | 8.17 | 26.70 | 336.83 | 24.00 | 8.17 | 26.70 |
November | 6.00 | 23.55 | 252.50 | 23.96 | 0.17 | 27.82 |
December | 94.83 | 22.97 | 50.83 | 23.92 | 0.00 | 0.00 |
Annual Sum or Average | 1186.17 | 23.81 | 3021.67 | 24.00 | 846.83 | 24.18 |
Minimum of Months | 5.33 | 22.78 | 12.00 | 23.92 | 0.00 | 0.00 |
Maximum of Months | 277.50 | 29.03 | 348.00 | 24.03 | 277.50 | 29.03 |
Report: ComfortReportSimple55Monthly
For: SMSTORE8
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 192.67 | 22.78 | 10.00 | 23.82 | 0.50 | 21.11 |
February | 67.00 | 22.87 | 92.67 | 23.96 | 0.00 | 0.00 |
March | 14.17 | 23.91 | 263.17 | 23.97 | 1.17 | 28.66 |
April | 6.00 | 29.05 | 316.17 | 24.02 | 6.00 | 29.05 |
May | 18.83 | 25.95 | 344.00 | 24.02 | 18.83 | 25.95 |
June | 92.17 | 24.25 | 336.00 | 24.00 | 92.17 | 24.25 |
July | 240.17 | 24.10 | 338.00 | 24.04 | 240.17 | 24.10 |
August | 251.17 | 24.02 | 348.00 | 23.99 | 251.17 | 24.02 |
September | 164.33 | 24.12 | 330.00 | 24.01 | 164.33 | 24.12 |
October | 9.17 | 26.87 | 336.17 | 24.01 | 9.17 | 26.87 |
November | 9.17 | 23.67 | 260.83 | 23.96 | 0.50 | 27.89 |
December | 104.33 | 22.92 | 53.33 | 23.92 | 0.00 | 0.00 |
Annual Sum or Average | 1169.17 | 23.78 | 3028.33 | 24.00 | 784.00 | 24.22 |
Minimum of Months | 6.00 | 22.78 | 10.00 | 23.82 | 0.00 | 0.00 |
Maximum of Months | 251.17 | 29.05 | 348.00 | 24.04 | 251.17 | 29.05 |
Report: OccupantComfortDataSummaryMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 496.00000 | 23.58502 | 37.73003 | 0.33326 | 8.10106 |
February | 448.00000 | 23.78274 | 39.63438 | 0.43561 | 9.33975 |
March | 496.00000 | 23.88921 | 40.68701 | 0.53231 | 11.11498 |
April | 480.00000 | 23.90428 | 41.04543 | 0.61276 | 13.05536 |
May | 496.00000 | 23.91798 | 49.77014 | -0.0653 | 5.33085 |
June | 480.00000 | 23.92011 | 55.90190 | -0.0056 | 5.26028 |
July | 496.00000 | 23.92340 | 62.50504 | 0.02241 | 5.24753 |
August | 496.00000 | 23.92173 | 64.01991 | 0.01694 | 5.23062 |
September | 480.00000 | 23.91254 | 60.85070 | -0.0336 | 5.22169 |
October | 496.00000 | 23.90268 | 46.90156 | 0.64058 | 13.76555 |
November | 480.00000 | 23.88568 | 40.48493 | 0.52497 | 10.92531 |
December | 496.00000 | 23.73973 | 37.00104 | 0.39011 | 8.63931 |
Annual Sum or Average | 5840.00000 | 23.85717 | 48.09673 | 0.28255 | 8.42663 |
Minimum of Months | 448.00000 | 23.58502 | 37.00104 | -0.0653 | 5.22169 |
Maximum of Months | 496.00000 | 23.92340 | 64.01991 | 0.64058 | 13.76555 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 496.00000 | 23.66515 | 37.45473 | 0.34090 | 8.00139 |
February | 448.00000 | 23.81720 | 38.92324 | 0.42767 | 9.08172 |
March | 496.00000 | 23.89453 | 40.08466 | 0.50953 | 10.56805 |
April | 480.00000 | 23.90512 | 40.83858 | 0.57664 | 12.10679 |
May | 496.00000 | 23.91706 | 49.27272 | -0.1313 | 5.54790 |
June | 480.00000 | 23.91797 | 55.26041 | -0.0788 | 5.33717 |
July | 496.00000 | 23.91989 | 61.44014 | -0.0513 | 5.25732 |
August | 496.00000 | 23.91834 | 62.75956 | -0.0579 | 5.27746 |
September | 480.00000 | 23.91059 | 59.30077 | -0.1053 | 5.41932 |
October | 496.00000 | 23.90244 | 45.83760 | 0.59706 | 12.61186 |
November | 480.00000 | 23.88919 | 39.64069 | 0.49597 | 10.26923 |
December | 496.00000 | 23.78525 | 36.57240 | 0.38549 | 8.42565 |
Annual Sum or Average | 5840.00000 | 23.87028 | 47.33463 | 0.24109 | 8.14970 |
Minimum of Months | 448.00000 | 23.66515 | 36.57240 | -0.1313 | 5.25732 |
Maximum of Months | 496.00000 | 23.91989 | 62.75956 | 0.59706 | 12.61186 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 23.46083 | 37.56644 | 0.27226 | 7.50137 |
February | 336.00000 | 23.80378 | 39.22136 | 0.40727 | 8.95477 |
March | 379.00000 | 24.03382 | 40.06484 | 0.52588 | 11.07766 |
April | 360.00000 | 24.13624 | 40.36239 | 0.61374 | 13.40255 |
May | 375.00000 | 24.17250 | 49.57748 | -0.0636 | 6.21806 |
June | 366.00000 | 24.17484 | 56.00863 | -0.0086 | 6.20223 |
July | 369.00000 | 24.15748 | 63.33658 | 0.01915 | 6.16285 |
August | 379.00000 | 24.12835 | 65.29318 | 0.00735 | 5.96464 |
September | 360.00000 | 24.11799 | 61.81793 | -0.0412 | 5.88286 |
October | 371.00000 | 24.08643 | 46.74313 | 0.63649 | 13.84480 |
November | 360.00000 | 23.98106 | 39.79873 | 0.50770 | 10.58992 |
December | 369.00000 | 23.69334 | 36.38013 | 0.34573 | 8.05008 |
Annual Sum or Average | 4395.00000 | 23.99679 | 48.09706 | 0.26681 | 8.64363 |
Minimum of Months | 336.00000 | 23.46083 | 36.38013 | -0.0636 | 5.88286 |
Maximum of Months | 379.00000 | 24.17484 | 65.29318 | 0.63649 | 13.84480 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 23.40674 | 37.76332 | 0.25009 | 7.34439 |
February | 336.00000 | 23.78232 | 39.33089 | 0.39629 | 8.81363 |
March | 379.00000 | 24.03104 | 40.08817 | 0.52257 | 11.00624 |
April | 360.00000 | 24.13571 | 40.34791 | 0.61339 | 13.39389 |
May | 375.00000 | 24.17234 | 49.54317 | -0.0620 | 6.21834 |
June | 366.00000 | 24.17461 | 55.96848 | -0.0074 | 6.20647 |
July | 369.00000 | 24.15734 | 63.27900 | 0.02039 | 6.17065 |
August | 379.00000 | 24.12802 | 65.26272 | 0.00753 | 5.96732 |
September | 360.00000 | 24.11756 | 61.80196 | -0.0414 | 5.88406 |
October | 371.00000 | 24.08564 | 46.74101 | 0.63562 | 13.82037 |
November | 360.00000 | 23.97590 | 39.84065 | 0.50291 | 10.49450 |
December | 369.00000 | 23.66168 | 36.50114 | 0.33131 | 7.90350 |
Annual Sum or Average | 4395.00000 | 23.98705 | 48.12125 | 0.26243 | 8.59189 |
Minimum of Months | 336.00000 | 23.40674 | 36.50114 | -0.0620 | 5.88406 |
Maximum of Months | 379.00000 | 24.17461 | 65.26272 | 0.63562 | 13.82037 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 23.35741 | 37.94312 | 0.23233 | 7.23475 |
February | 336.00000 | 23.75937 | 39.46048 | 0.38656 | 8.69440 |
March | 379.00000 | 24.02654 | 40.16366 | 0.51821 | 10.91380 |
April | 360.00000 | 24.13381 | 40.38298 | 0.61077 | 13.32057 |
May | 375.00000 | 24.17097 | 49.59244 | -0.0639 | 6.20465 |
June | 366.00000 | 24.17335 | 56.04024 | -0.0091 | 6.18706 |
July | 369.00000 | 24.15588 | 63.36415 | 0.01946 | 6.15263 |
August | 379.00000 | 24.12625 | 65.37899 | 0.00596 | 5.94779 |
September | 360.00000 | 24.11567 | 61.92663 | -0.0436 | 5.87089 |
October | 371.00000 | 24.08369 | 46.82259 | 0.63343 | 13.75731 |
November | 360.00000 | 23.96977 | 39.92042 | 0.49826 | 10.40315 |
December | 369.00000 | 23.63256 | 36.61730 | 0.31983 | 7.79784 |
Annual Sum or Average | 4395.00000 | 23.97682 | 48.21646 | 0.25739 | 8.53081 |
Minimum of Months | 336.00000 | 23.35741 | 36.61730 | -0.0639 | 5.87089 |
Maximum of Months | 379.00000 | 24.17335 | 65.37899 | 0.63343 | 13.75731 |
Report: OccupantComfortDataSummaryMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 23.36333 | 38.65678 | 0.22726 | 7.01113 |
February | 308.00000 | 23.75705 | 39.84467 | 0.38622 | 8.52832 |
March | 348.00000 | 23.93304 | 40.53659 | 0.50859 | 10.63299 |
April | 330.00000 | 23.98816 | 40.86090 | 0.60036 | 12.89737 |
May | 344.00000 | 23.99125 | 50.36194 | -0.0817 | 5.72344 |
June | 336.00000 | 23.97684 | 56.87455 | -0.0309 | 5.54886 |
July | 338.00000 | 24.00613 | 64.12901 | 0.00585 | 5.73025 |
August | 348.00000 | 23.96349 | 66.23776 | -0.0130 | 5.48319 |
September | 330.00000 | 23.98016 | 62.61031 | -0.0584 | 5.58358 |
October | 340.00000 | 23.97667 | 47.17931 | 0.62858 | 13.53862 |
November | 330.00000 | 23.92225 | 40.11154 | 0.49540 | 10.28399 |
December | 338.00000 | 23.65397 | 37.28052 | 0.32299 | 7.71031 |
Annual Sum or Average | 4030.00000 | 23.87667 | 48.81067 | 0.24749 | 8.21109 |
Minimum of Months | 308.00000 | 23.36333 | 37.28052 | -0.0817 | 5.48319 |
Maximum of Months | 348.00000 | 24.00613 | 66.23776 | 0.62858 | 13.53862 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 23.35658 | 38.65327 | 0.21332 | 6.88728 |
February | 308.00000 | 23.75543 | 39.86283 | 0.37015 | 8.26697 |
March | 348.00000 | 23.93275 | 40.57297 | 0.48791 | 10.18626 |
April | 330.00000 | 23.98746 | 40.86155 | 0.57323 | 12.21327 |
May | 344.00000 | 23.99098 | 50.38465 | -0.1241 | 5.88850 |
June | 336.00000 | 23.97650 | 56.95225 | -0.0736 | 5.62829 |
July | 338.00000 | 24.00541 | 64.30708 | -0.0337 | 5.73527 |
August | 348.00000 | 23.96282 | 66.46760 | -0.0508 | 5.52202 |
September | 330.00000 | 23.97934 | 62.78245 | -0.0944 | 5.68177 |
October | 340.00000 | 23.97634 | 47.25179 | 0.60390 | 12.88644 |
November | 330.00000 | 23.92216 | 40.15346 | 0.47609 | 9.87914 |
December | 338.00000 | 23.65310 | 37.28141 | 0.30948 | 7.53099 |
Annual Sum or Average | 4030.00000 | 23.87555 | 48.88187 | 0.21958 | 8.01538 |
Minimum of Months | 308.00000 | 23.35658 | 37.28141 | -0.1241 | 5.52202 |
Maximum of Months | 348.00000 | 24.00541 | 66.46760 | 0.60390 | 12.88644 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 23.33745 | 38.72036 | 0.20582 | 6.83972 |
February | 308.00000 | 23.74691 | 39.91592 | 0.36511 | 8.20381 |
March | 348.00000 | 23.93161 | 40.60315 | 0.48491 | 10.12629 |
April | 330.00000 | 23.98714 | 40.87779 | 0.57075 | 12.15273 |
May | 344.00000 | 23.99084 | 50.41744 | -0.1271 | 5.90268 |
June | 336.00000 | 23.97636 | 57.00101 | -0.0765 | 5.63563 |
July | 338.00000 | 24.00517 | 64.37201 | -0.0362 | 5.73613 |
August | 348.00000 | 23.96262 | 66.54001 | -0.0532 | 5.52492 |
September | 330.00000 | 23.97902 | 62.84986 | -0.0969 | 5.68857 |
October | 340.00000 | 23.97603 | 47.28768 | 0.60188 | 12.83386 |
November | 330.00000 | 23.92104 | 40.18139 | 0.47343 | 9.82701 |
December | 338.00000 | 23.64220 | 37.32715 | 0.30424 | 7.48217 |
Annual Sum or Average | 4030.00000 | 23.87204 | 48.92876 | 0.21614 | 7.98631 |
Minimum of Months | 308.00000 | 23.33745 | 37.32715 | -0.1271 | 5.52492 |
Maximum of Months | 348.00000 | 24.00517 | 66.54001 | 0.60188 | 12.83386 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 23.28875 | 38.88184 | 0.18939 | 6.75984 |
February | 308.00000 | 23.72049 | 40.05983 | 0.35387 | 8.09090 |
March | 348.00000 | 23.92798 | 40.67575 | 0.48114 | 10.06141 |
April | 330.00000 | 23.98692 | 40.89638 | 0.57118 | 12.16578 |
May | 344.00000 | 23.99085 | 50.42189 | -0.1236 | 5.88747 |
June | 336.00000 | 23.97636 | 56.99023 | -0.0724 | 5.62583 |
July | 338.00000 | 24.00527 | 64.32768 | -0.0317 | 5.73528 |
August | 348.00000 | 23.96271 | 66.48566 | -0.0488 | 5.51882 |
September | 330.00000 | 23.97907 | 62.82724 | -0.0931 | 5.67693 |
October | 340.00000 | 23.97591 | 47.30810 | 0.60335 | 12.87337 |
November | 330.00000 | 23.91800 | 40.23753 | 0.47121 | 9.79105 |
December | 338.00000 | 23.61178 | 37.44567 | 0.29292 | 7.40071 |
Annual Sum or Average | 4030.00000 | 23.86279 | 48.96665 | 0.21432 | 7.95630 |
Minimum of Months | 308.00000 | 23.28875 | 37.44567 | -0.1236 | 5.51882 |
Maximum of Months | 348.00000 | 24.00527 | 66.48566 | 0.60335 | 12.87337 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 23.23797 | 39.04918 | 0.16546 | 6.71121 |
February | 308.00000 | 23.66327 | 40.31652 | 0.33454 | 7.99931 |
March | 348.00000 | 23.91814 | 40.86755 | 0.48588 | 10.23982 |
April | 330.00000 | 23.98984 | 40.91363 | 0.60238 | 12.98319 |
May | 344.00000 | 23.99308 | 50.22225 | -0.0630 | 5.71655 |
June | 336.00000 | 23.97844 | 56.51316 | -0.0112 | 5.58311 |
July | 338.00000 | 24.00976 | 63.47621 | 0.02640 | 5.83031 |
August | 348.00000 | 23.96664 | 65.39556 | 0.00811 | 5.54564 |
September | 330.00000 | 23.98446 | 61.96502 | -0.0400 | 5.62003 |
October | 340.00000 | 23.98104 | 47.07894 | 0.63658 | 13.79248 |
November | 330.00000 | 23.91509 | 40.28370 | 0.48436 | 10.11072 |
December | 338.00000 | 23.56964 | 37.53199 | 0.27727 | 7.36837 |
Annual Sum or Average | 4030.00000 | 23.85170 | 48.71708 | 0.24076 | 8.11602 |
Minimum of Months | 308.00000 | 23.23797 | 37.53199 | -0.0630 | 5.54564 |
Maximum of Months | 348.00000 | 24.00976 | 65.39556 | 0.63658 | 13.79248 |
Report: DXReportMonthly
For: PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.807262E+10 | 0.253375E+10 | 360.83 | 0.737426E+10 | 0.698366E+09 | 0.00 | 0.30 | 12-JAN-15:00 | 0.00 | 01-JAN-00:05 | 15902.62 | 12-JAN-15:00 | 15429.81 | 12-JAN-15:00 | 2317.48 | 13-JAN-14:00 | 5000.75 | 12-JAN-15:00 | 0.00 | 01-JAN-00:05 |
February | 0.155245E+11 | 0.486213E+10 | 397.06 | 0.138937E+11 | 0.163078E+10 | 0.00 | 0.43 | 22-FEB-15:00 | 0.00 | 01-FEB-00:05 | 23218.58 | 22-FEB-15:00 | 21931.86 | 22-FEB-15:00 | 5395.47 | 25-FEB-18:03 | 7499.10 | 22-FEB-15:00 | 0.00 | 01-FEB-00:05 |
March | 0.312202E+11 | 0.100806E+11 | 490.18 | 0.277869E+11 | 0.343332E+10 | 0.00 | 1.00 | 11-MAR-08:62 | 0.00 | 01-MAR-00:05 | 68949.96 | 11-MAR-08:62 | 54789.56 | 11-MAR-08:62 | 14524.61 | 30-MAR-07:02 | 17519.51 | 11-MAR-08:62 | 0.00 | 01-MAR-00:05 |
April | 0.463633E+11 | 0.161691E+11 | 486.80 | 0.423636E+11 | 0.399961E+10 | 0.00 | 1.00 | 02-APR-07:02 | 0.00 | 01-APR-00:03 | 69415.09 | 26-APR-07:02 | 64753.39 | 08-APR-07:02 | 15756.75 | 03-APR-07:02 | 18968.54 | 27-APR-07:01 | 0.00 | 01-APR-00:03 |
May | 0.645267E+11 | 0.227125E+11 | 503.38 | 0.530268E+11 | 0.115000E+11 | 0.00 | 1.00 | 01-MAY-07:01 | 0.00 | 01-MAY-00:10 | 74598.86 | 24-MAY-07:02 | 65445.46 | 06-MAY-07:01 | 34919.36 | 24-MAY-07:03 | 20014.55 | 04-MAY-07:01 | 0.00 | 01-MAY-00:10 |
June | 0.719015E+11 | 0.243175E+11 | 488.58 | 0.527668E+11 | 0.191346E+11 | 0.00 | 1.00 | 01-JUN-07:01 | 0.00 | 01-JUN-00:10 | 76215.72 | 26-JUN-07:01 | 64029.88 | 07-JUN-07:01 | 39750.40 | 26-JUN-07:12 | 21223.30 | 10-JUN-16:10 | 0.00 | 01-JUN-00:10 |
July | 0.808897E+11 | 0.251681E+11 | 504.82 | 0.501368E+11 | 0.307529E+11 | 0.00 | 1.00 | 01-JUL-07:01 | 0.00 | 01-JUL-00:03 | 76403.94 | 26-JUL-07:01 | 55236.86 | 07-JUL-07:01 | 42406.18 | 25-JUL-07:05 | 20498.42 | 01-JUL-16:10 | 0.00 | 01-JUL-00:03 |
August | 0.798542E+11 | 0.240174E+11 | 503.69 | 0.467962E+11 | 0.330580E+11 | 0.00 | 1.00 | 01-AUG-07:01 | 0.00 | 01-AUG-00:10 | 76372.66 | 10-AUG-07:01 | 48415.31 | 14-AUG-07:01 | 40345.25 | 10-AUG-07:06 | 19362.28 | 27-AUG-14:50 | 0.00 | 01-AUG-00:10 |
September | 0.671213E+11 | 0.205633E+11 | 489.34 | 0.422705E+11 | 0.248508E+11 | 0.00 | 1.00 | 01-SEP-07:01 | 0.00 | 01-SEP-00:10 | 75835.78 | 03-SEP-07:01 | 52562.33 | 26-SEP-07:01 | 38268.49 | 03-SEP-07:12 | 18724.27 | 22-SEP-07:01 | 0.00 | 01-SEP-00:10 |
October | 0.454035E+11 | 0.146154E+11 | 498.98 | 0.371437E+11 | 0.825976E+10 | 0.00 | 1.00 | 01-OCT-07:01 | 0.00 | 01-OCT-00:03 | 72347.39 | 12-OCT-07:02 | 57896.88 | 23-OCT-07:02 | 27913.94 | 12-OCT-07:02 | 18144.90 | 04-OCT-07:01 | 0.00 | 01-OCT-00:03 |
November | 0.264202E+11 | 0.835688E+10 | 470.38 | 0.234646E+11 | 0.295558E+10 | 0.00 | 0.80 | 09-NOV-08:62 | 0.00 | 01-NOV-00:10 | 51426.37 | 09-NOV-08:62 | 39175.65 | 09-NOV-08:62 | 12250.72 | 09-NOV-08:62 | 13394.13 | 09-NOV-08:62 | 0.00 | 01-NOV-00:10 |
December | 0.115365E+11 | 0.360886E+10 | 410.00 | 0.103943E+11 | 0.114228E+10 | 0.00 | 0.35 | 28-DEC-15:00 | 0.00 | 01-DEC-01:05 | 18772.77 | 28-DEC-15:00 | 17850.35 | 03-DEC-14:00 | 2492.28 | 10-DEC-18:10 | 5910.99 | 28-DEC-15:00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.548834E+12 | 0.177006E+12 | 5604.04 | 0.407418E+12 | 0.141416E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.807262E+10 | 0.253375E+10 | 360.83 | 0.737426E+10 | 0.698366E+09 | 0.00 | 0.30 | 0.00 | 15902.62 | 15429.81 | 2317.48 | 5000.75 | 0.00 | |||||||
Maximum of Months | 0.808897E+11 | 0.251681E+11 | 504.82 | 0.530268E+11 | 0.330580E+11 | 0.00 | 1.00 | 0.00 | 76403.94 | 65445.46 | 42406.18 | 21223.30 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.502962E+10 | 0.151769E+10 | 416.31 | 0.463707E+10 | 0.392544E+09 | 0.00 | 0.31 | 12-JAN-15:00 | 0.00 | 01-JAN-00:05 | 8145.40 | 12-JAN-15:00 | 7911.65 | 12-JAN-15:00 | 1238.44 | 15-JAN-18:10 | 2412.53 | 12-JAN-15:00 | 0.00 | 01-JAN-00:05 |
February | 0.837796E+10 | 0.250705E+10 | 412.22 | 0.759645E+10 | 0.781512E+09 | 0.00 | 0.44 | 25-FEB-08:63 | 0.00 | 01-FEB-00:05 | 12476.89 | 25-FEB-08:63 | 11193.56 | 22-FEB-14:30 | 2732.51 | 25-FEB-18:03 | 3603.99 | 22-FEB-14:40 | 0.00 | 01-FEB-00:05 |
March | 0.154796E+11 | 0.477171E+10 | 493.74 | 0.139876E+11 | 0.149195E+10 | 0.00 | 1.00 | 11-MAR-08:62 | 0.00 | 01-MAR-00:05 | 34503.65 | 30-MAR-07:02 | 28997.79 | 11-MAR-08:62 | 6043.52 | 30-MAR-07:02 | 8283.54 | 11-MAR-08:62 | 0.00 | 01-MAR-00:05 |
April | 0.220269E+11 | 0.736477E+10 | 486.68 | 0.203569E+11 | 0.167002E+10 | 0.00 | 1.00 | 02-APR-07:02 | 0.00 | 01-APR-00:03 | 34605.50 | 03-APR-07:02 | 32776.45 | 08-APR-07:02 | 6222.58 | 03-APR-07:02 | 8982.72 | 27-APR-07:01 | 0.00 | 01-APR-00:03 |
May | 0.303539E+11 | 0.102653E+11 | 503.23 | 0.252917E+11 | 0.506225E+10 | 0.00 | 1.00 | 01-MAY-07:01 | 0.00 | 01-MAY-00:10 | 36842.34 | 24-MAY-07:02 | 32989.39 | 06-MAY-07:01 | 14504.83 | 24-MAY-07:03 | 9526.57 | 04-MAY-07:01 | 0.00 | 01-MAY-00:10 |
June | 0.335792E+11 | 0.109174E+11 | 488.54 | 0.250132E+11 | 0.856590E+10 | 0.00 | 1.00 | 01-JUN-07:01 | 0.00 | 01-JUN-00:10 | 37290.90 | 26-JUN-07:01 | 32044.14 | 07-JUN-07:01 | 16267.68 | 26-JUN-07:12 | 9970.90 | 10-JUN-16:10 | 0.00 | 01-JUN-00:10 |
July | 0.375878E+11 | 0.112593E+11 | 504.67 | 0.237211E+11 | 0.138667E+11 | 0.00 | 1.00 | 01-JUL-07:01 | 0.00 | 01-JUL-00:03 | 37778.70 | 25-JUL-07:01 | 28808.97 | 07-JUL-07:01 | 18036.25 | 25-JUL-07:13 | 9681.77 | 01-JUL-16:10 | 0.00 | 01-JUL-00:03 |
August | 0.372318E+11 | 0.107635E+11 | 503.63 | 0.222069E+11 | 0.150250E+11 | 0.00 | 1.00 | 01-AUG-07:01 | 0.00 | 01-AUG-00:10 | 37699.38 | 10-AUG-07:01 | 26266.29 | 14-AUG-07:01 | 17287.11 | 10-AUG-07:12 | 9232.36 | 27-AUG-14:00 | 0.00 | 01-AUG-00:10 |
September | 0.311053E+11 | 0.917249E+10 | 489.17 | 0.200289E+11 | 0.110764E+11 | 0.00 | 1.00 | 01-SEP-07:01 | 0.00 | 01-SEP-00:10 | 37129.58 | 03-SEP-07:01 | 28431.16 | 26-SEP-07:01 | 15386.93 | 03-SEP-07:04 | 8878.32 | 22-SEP-07:01 | 0.00 | 01-SEP-00:10 |
October | 0.216139E+11 | 0.667077E+10 | 498.31 | 0.180245E+11 | 0.358936E+10 | 0.00 | 1.00 | 01-OCT-07:01 | 0.00 | 01-OCT-00:03 | 35659.06 | 12-OCT-07:02 | 30295.08 | 16-OCT-07:02 | 10463.03 | 12-OCT-07:02 | 8562.56 | 04-OCT-07:01 | 0.00 | 01-OCT-00:03 |
November | 0.133519E+11 | 0.403072E+10 | 472.54 | 0.120491E+11 | 0.130278E+10 | 0.00 | 0.76 | 09-NOV-08:62 | 0.00 | 01-NOV-00:10 | 23863.87 | 09-NOV-08:62 | 20169.78 | 09-NOV-08:62 | 3694.09 | 09-NOV-08:62 | 5955.68 | 09-NOV-08:62 | 0.00 | 01-NOV-00:10 |
December | 0.676263E+10 | 0.202774E+10 | 444.42 | 0.616780E+10 | 0.594831E+09 | 0.00 | 0.35 | 28-DEC-14:20 | 0.00 | 01-DEC-01:05 | 9509.12 | 28-DEC-14:40 | 9209.50 | 03-DEC-14:00 | 1276.81 | 29-DEC-20:10 | 2824.89 | 28-DEC-14:30 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.262501E+12 | 0.812683E+11 | 5713.45 | 0.199081E+12 | 0.634192E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.502962E+10 | 0.151769E+10 | 412.22 | 0.463707E+10 | 0.392544E+09 | 0.00 | 0.31 | 0.00 | 8145.40 | 7911.65 | 1238.44 | 2412.53 | 0.00 | |||||||
Maximum of Months | 0.375878E+11 | 0.112593E+11 | 504.67 | 0.252917E+11 | 0.150250E+11 | 0.00 | 1.00 | 0.00 | 37778.70 | 32989.39 | 18036.25 | 9970.90 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.243803E+10 | 0.724152E+09 | 232.83 | 0.226616E+10 | 0.171874E+09 | 0.00 | 0.28 | 12-JAN-15:00 | 0.00 | 01-JAN-00:05 | 7076.08 | 12-JAN-15:00 | 6861.86 | 12-JAN-15:00 | 1027.62 | 13-JAN-14:00 | 2111.86 | 12-JAN-15:00 | 0.00 | 01-JAN-00:05 |
February | 0.536805E+10 | 0.159488E+10 | 264.58 | 0.486070E+10 | 0.507352E+09 | 0.00 | 0.42 | 22-FEB-14:00 | 0.00 | 01-FEB-00:05 | 10943.42 | 22-FEB-14:00 | 10335.78 | 22-FEB-14:00 | 2379.73 | 25-FEB-16:30 | 3338.63 | 22-FEB-14:30 | 0.00 | 01-FEB-00:05 |
March | 0.115536E+11 | 0.354710E+10 | 360.82 | 0.103645E+11 | 0.118910E+10 | 0.00 | 1.00 | 11-MAR-07:02 | 0.00 | 01-MAR-00:05 | 34152.15 | 11-MAR-07:02 | 27506.57 | 29-MAR-06:02 | 9393.13 | 11-MAR-07:02 | 8056.41 | 11-MAR-07:02 | 0.00 | 01-MAR-00:05 |
April | 0.173988E+11 | 0.574037E+10 | 361.53 | 0.159386E+11 | 0.146015E+10 | 0.00 | 1.00 | 02-APR-07:02 | 0.00 | 01-APR-00:03 | 34409.27 | 17-APR-06:01 | 31589.27 | 08-APR-06:02 | 9318.50 | 17-APR-06:02 | 8733.64 | 27-APR-06:01 | 0.00 | 01-APR-00:03 |
May | 0.249063E+11 | 0.826492E+10 | 384.43 | 0.204399E+11 | 0.446635E+10 | 0.00 | 1.00 | 01-MAY-06:01 | 0.00 | 01-MAY-00:10 | 36399.23 | 23-MAY-06:01 | 31806.06 | 06-MAY-06:01 | 17091.11 | 23-MAY-06:04 | 9023.24 | 03-MAY-15:00 | 0.00 | 01-MAY-00:10 |
June | 0.277439E+11 | 0.877815E+10 | 376.75 | 0.201652E+11 | 0.757873E+10 | 0.00 | 1.00 | 01-JUN-06:01 | 0.00 | 01-JUN-00:10 | 37239.42 | 25-JUN-07:02 | 30620.58 | 12-JUN-06:01 | 22155.78 | 26-JUN-06:05 | 9681.96 | 10-JUN-16:00 | 0.00 | 01-JUN-00:10 |
July | 0.305442E+11 | 0.884164E+10 | 375.69 | 0.184727E+11 | 0.120715E+11 | 0.00 | 1.00 | 01-JUL-06:01 | 0.00 | 01-JUL-00:03 | 37272.94 | 19-JUL-06:01 | 24468.61 | 05-JUL-06:01 | 22360.30 | 24-JUL-06:06 | 9428.65 | 01-JUL-14:00 | 0.00 | 01-JUL-00:03 |
August | 0.308340E+11 | 0.866107E+10 | 382.47 | 0.175928E+11 | 0.132412E+11 | 0.00 | 1.00 | 01-AUG-06:01 | 0.00 | 01-AUG-00:10 | 37353.00 | 21-AUG-06:01 | 20923.48 | 03-AUG-06:01 | 23001.14 | 28-AUG-06:07 | 8980.01 | 27-AUG-14:00 | 0.00 | 01-AUG-00:10 |
September | 0.251238E+11 | 0.721233E+10 | 360.92 | 0.155123E+11 | 0.961148E+10 | 0.00 | 1.00 | 01-SEP-06:01 | 0.00 | 01-SEP-00:10 | 37362.26 | 10-SEP-07:02 | 23769.12 | 27-SEP-06:01 | 22854.66 | 11-SEP-06:05 | 8512.10 | 22-SEP-06:01 | 0.00 | 01-SEP-00:10 |
October | 0.168869E+11 | 0.516227E+10 | 368.08 | 0.138578E+11 | 0.302906E+10 | 0.00 | 1.00 | 01-OCT-07:01 | 0.00 | 01-OCT-00:03 | 35426.93 | 12-OCT-06:02 | 28819.47 | 23-OCT-06:02 | 14688.02 | 12-OCT-06:02 | 8278.37 | 04-OCT-06:01 | 0.00 | 01-OCT-00:03 |
November | 0.973250E+10 | 0.293013E+10 | 331.50 | 0.877635E+10 | 0.956153E+09 | 0.00 | 0.59 | 09-NOV-07:03 | 0.00 | 01-NOV-00:10 | 17365.36 | 09-NOV-07:03 | 13386.82 | 04-NOV-14:00 | 5005.31 | 09-NOV-07:03 | 4538.28 | 09-NOV-07:03 | 0.00 | 01-NOV-00:10 |
December | 0.385582E+10 | 0.114195E+10 | 269.83 | 0.352241E+10 | 0.333419E+09 | 0.00 | 0.33 | 28-DEC-14:00 | 0.00 | 01-DEC-00:10 | 8505.03 | 28-DEC-14:00 | 8219.43 | 02-DEC-14:00 | 1087.38 | 16-DEC-14:00 | 2545.33 | 28-DEC-14:00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.206386E+12 | 0.625990E+11 | 4069.44 | 0.151769E+12 | 0.546164E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.243803E+10 | 0.724152E+09 | 232.83 | 0.226616E+10 | 0.171874E+09 | 0.00 | 0.28 | 0.00 | 7076.08 | 6861.86 | 1027.62 | 2111.86 | 0.00 | |||||||
Maximum of Months | 0.308340E+11 | 0.884164E+10 | 384.43 | 0.204399E+11 | 0.132412E+11 | 0.00 | 1.00 | 0.00 | 37362.26 | 31806.06 | 23001.14 | 9681.96 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.222506E+10 | 0.661899E+09 | 223.67 | 0.207021E+10 | 0.154847E+09 | 0.00 | 0.27 | 12-JAN-15:00 | 0.00 | 01-JAN-00:05 | 6882.94 | 12-JAN-15:00 | 6670.60 | 12-JAN-15:00 | 1000.66 | 13-JAN-14:00 | 2057.90 | 12-JAN-15:00 | 0.00 | 01-JAN-00:05 |
February | 0.519634E+10 | 0.154617E+10 | 261.42 | 0.470362E+10 | 0.492727E+09 | 0.00 | 0.41 | 22-FEB-14:00 | 0.00 | 01-FEB-00:05 | 10813.69 | 22-FEB-14:00 | 10207.80 | 22-FEB-14:00 | 2349.16 | 25-FEB-16:30 | 3302.68 | 22-FEB-14:30 | 0.00 | 01-FEB-00:05 |
March | 0.114554E+11 | 0.351902E+10 | 359.28 | 0.102712E+11 | 0.118420E+10 | 0.00 | 1.00 | 11-MAR-07:02 | 0.00 | 01-MAR-00:05 | 34089.04 | 11-MAR-07:02 | 27442.86 | 29-MAR-06:02 | 9411.48 | 11-MAR-07:02 | 8041.79 | 11-MAR-07:02 | 0.00 | 01-MAR-00:05 |
April | 0.173984E+11 | 0.573861E+10 | 361.60 | 0.159343E+11 | 0.146414E+10 | 0.00 | 1.00 | 02-APR-07:02 | 0.00 | 01-APR-00:03 | 34372.91 | 17-APR-06:01 | 31534.81 | 08-APR-06:02 | 9210.15 | 17-APR-06:02 | 8718.68 | 27-APR-06:01 | 0.00 | 01-APR-00:03 |
May | 0.249703E+11 | 0.828026E+10 | 384.43 | 0.204943E+11 | 0.447598E+10 | 0.00 | 1.00 | 01-MAY-06:01 | 0.00 | 01-MAY-00:10 | 36341.87 | 23-MAY-06:01 | 31793.51 | 29-MAY-07:01 | 17021.37 | 23-MAY-06:04 | 9017.04 | 03-MAY-15:00 | 0.00 | 01-MAY-00:10 |
June | 0.278043E+11 | 0.879220E+10 | 377.10 | 0.202134E+11 | 0.759084E+10 | 0.00 | 1.00 | 01-JUN-06:01 | 0.00 | 01-JUN-00:10 | 37180.13 | 25-JUN-07:02 | 30708.16 | 12-JUN-06:01 | 22036.66 | 26-JUN-06:05 | 9678.61 | 10-JUN-16:00 | 0.00 | 01-JUN-00:10 |
July | 0.306231E+11 | 0.885956E+10 | 377.03 | 0.185330E+11 | 0.120902E+11 | 0.00 | 1.00 | 01-JUL-06:01 | 0.00 | 01-JUL-00:03 | 37206.70 | 26-JUL-06:01 | 24644.93 | 05-JUL-06:01 | 22248.90 | 24-JUL-06:06 | 9424.22 | 01-JUL-14:00 | 0.00 | 01-JUL-00:03 |
August | 0.308625E+11 | 0.866522E+10 | 382.51 | 0.176115E+11 | 0.132510E+11 | 0.00 | 1.00 | 01-AUG-06:01 | 0.00 | 01-AUG-00:10 | 37286.45 | 21-AUG-06:01 | 20934.02 | 03-AUG-06:01 | 22856.16 | 28-AUG-06:07 | 8979.86 | 27-AUG-14:00 | 0.00 | 01-AUG-00:10 |
September | 0.251303E+11 | 0.721182E+10 | 360.93 | 0.155148E+11 | 0.961545E+10 | 0.00 | 1.00 | 01-SEP-06:01 | 0.00 | 01-SEP-00:10 | 37295.69 | 10-SEP-07:02 | 23752.31 | 27-SEP-06:01 | 22811.68 | 11-SEP-06:05 | 8496.92 | 22-SEP-06:01 | 0.00 | 01-SEP-00:10 |
October | 0.168644E+11 | 0.515511E+10 | 368.03 | 0.138346E+11 | 0.302984E+10 | 0.00 | 1.00 | 01-OCT-07:01 | 0.00 | 01-OCT-00:03 | 35365.28 | 12-OCT-06:02 | 28795.86 | 23-OCT-06:02 | 14684.70 | 13-OCT-06:02 | 8264.09 | 04-OCT-06:01 | 0.00 | 01-OCT-00:03 |
November | 0.960719E+10 | 0.289485E+10 | 329.83 | 0.865851E+10 | 0.948685E+09 | 0.00 | 0.57 | 09-NOV-07:03 | 0.00 | 01-NOV-00:10 | 16746.78 | 09-NOV-07:03 | 13298.53 | 04-NOV-14:00 | 4857.25 | 09-NOV-07:03 | 4398.51 | 09-NOV-07:03 | 0.00 | 01-NOV-00:10 |
December | 0.364906E+10 | 0.108256E+10 | 265.08 | 0.333097E+10 | 0.318089E+09 | 0.00 | 0.32 | 28-DEC-14:00 | 0.00 | 01-DEC-00:10 | 8308.09 | 28-DEC-14:00 | 8065.61 | 02-DEC-14:00 | 1067.75 | 16-DEC-14:00 | 2490.78 | 28-DEC-14:00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.205786E+12 | 0.624073E+11 | 4050.90 | 0.151170E+12 | 0.546160E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.222506E+10 | 0.661899E+09 | 223.67 | 0.207021E+10 | 0.154847E+09 | 0.00 | 0.27 | 0.00 | 6882.94 | 6670.60 | 1000.66 | 2057.90 | 0.00 | |||||||
Maximum of Months | 0.308625E+11 | 0.885956E+10 | 384.43 | 0.204943E+11 | 0.132510E+11 | 0.00 | 1.00 | 0.00 | 37295.69 | 31793.51 | 22856.16 | 9678.61 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.203927E+10 | 0.607440E+09 | 215.83 | 0.190001E+10 | 0.139268E+09 | 0.00 | 0.27 | 12-JAN-15:00 | 0.00 | 01-JAN-00:05 | 6705.57 | 12-JAN-15:00 | 6496.75 | 12-JAN-15:00 | 973.67 | 13-JAN-14:00 | 2008.23 | 12-JAN-15:00 | 0.00 | 01-JAN-00:05 |
February | 0.501048E+10 | 0.149328E+10 | 257.67 | 0.453613E+10 | 0.474354E+09 | 0.00 | 0.41 | 22-FEB-14:00 | 0.00 | 01-FEB-00:05 | 10666.87 | 22-FEB-14:00 | 10065.90 | 22-FEB-14:00 | 2312.15 | 25-FEB-16:30 | 3262.95 | 22-FEB-14:30 | 0.00 | 01-FEB-00:05 |
March | 0.112551E+11 | 0.346241E+10 | 357.44 | 0.100887E+11 | 0.116638E+10 | 0.00 | 1.00 | 11-MAR-07:02 | 0.00 | 01-MAR-00:05 | 34022.41 | 11-MAR-07:02 | 27290.14 | 29-MAR-06:02 | 9510.45 | 11-MAR-07:02 | 8028.46 | 11-MAR-07:02 | 0.00 | 01-MAR-00:05 |
April | 0.172481E+11 | 0.569453E+10 | 361.36 | 0.157922E+11 | 0.145588E+10 | 0.00 | 1.00 | 02-APR-07:02 | 0.00 | 01-APR-00:03 | 34318.91 | 17-APR-06:01 | 31456.55 | 08-APR-06:02 | 9228.99 | 17-APR-06:02 | 8704.92 | 27-APR-06:01 | 0.00 | 01-APR-00:03 |
May | 0.248432E+11 | 0.824228E+10 | 384.06 | 0.203814E+11 | 0.446180E+10 | 0.00 | 1.00 | 01-MAY-06:01 | 0.00 | 01-MAY-00:10 | 36279.38 | 23-MAY-06:01 | 31736.99 | 29-MAY-07:01 | 16933.80 | 23-MAY-06:03 | 8988.79 | 03-MAY-15:00 | 0.00 | 01-MAY-00:10 |
June | 0.276696E+11 | 0.875357E+10 | 376.95 | 0.201015E+11 | 0.756810E+10 | 0.00 | 1.00 | 01-JUN-06:01 | 0.00 | 01-JUN-00:10 | 37122.25 | 26-JUN-06:01 | 30658.17 | 12-JUN-06:01 | 22078.45 | 26-JUN-06:05 | 9652.64 | 10-JUN-16:00 | 0.00 | 01-JUN-00:10 |
July | 0.304965E+11 | 0.882514E+10 | 375.97 | 0.184359E+11 | 0.120606E+11 | 0.00 | 1.00 | 01-JUL-06:01 | 0.00 | 01-JUL-00:03 | 37155.75 | 19-JUL-06:01 | 24574.93 | 05-JUL-06:01 | 22301.20 | 24-JUL-06:06 | 9393.81 | 01-JUL-14:00 | 0.00 | 01-JUL-00:03 |
August | 0.307067E+11 | 0.862474E+10 | 382.32 | 0.174948E+11 | 0.132119E+11 | 0.00 | 1.00 | 01-AUG-06:01 | 0.00 | 01-AUG-00:10 | 37235.57 | 21-AUG-06:01 | 20794.06 | 08-AUG-06:01 | 22900.94 | 28-AUG-06:07 | 8958.59 | 27-AUG-14:00 | 0.00 | 01-AUG-00:10 |
September | 0.249802E+11 | 0.717257E+10 | 360.92 | 0.153979E+11 | 0.958228E+10 | 0.00 | 1.00 | 01-SEP-06:01 | 0.00 | 01-SEP-00:10 | 37244.80 | 10-SEP-07:02 | 23613.96 | 27-SEP-06:01 | 22847.64 | 11-SEP-06:05 | 8485.35 | 22-SEP-06:01 | 0.00 | 01-SEP-00:10 |
October | 0.167044E+11 | 0.511087E+10 | 367.49 | 0.136952E+11 | 0.300918E+10 | 0.00 | 1.00 | 01-OCT-07:01 | 0.00 | 01-OCT-00:03 | 35305.32 | 12-OCT-06:02 | 28690.94 | 23-OCT-06:02 | 14779.35 | 13-OCT-06:02 | 8251.78 | 04-OCT-06:01 | 0.00 | 01-OCT-00:03 |
November | 0.942220E+10 | 0.284296E+10 | 327.53 | 0.848966E+10 | 0.932540E+09 | 0.00 | 0.52 | 09-NOV-07:03 | 0.00 | 01-NOV-00:10 | 15182.22 | 09-NOV-07:03 | 13176.12 | 04-NOV-14:00 | 4453.40 | 09-NOV-07:03 | 4347.78 | 09-NOV-13:30 | 0.00 | 01-NOV-00:10 |
December | 0.345394E+10 | 0.102628E+10 | 260.33 | 0.315148E+10 | 0.302463E+09 | 0.00 | 0.32 | 28-DEC-14:00 | 0.00 | 01-DEC-00:10 | 8127.42 | 28-DEC-14:00 | 7923.58 | 02-DEC-14:00 | 1047.77 | 16-DEC-14:00 | 2440.62 | 28-DEC-14:00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.203830E+12 | 0.618561E+11 | 4027.87 | 0.149465E+12 | 0.543647E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.203927E+10 | 0.607440E+09 | 215.83 | 0.190001E+10 | 0.139268E+09 | 0.00 | 0.27 | 0.00 | 6705.57 | 6496.75 | 973.67 | 2008.23 | 0.00 | |||||||
Maximum of Months | 0.307067E+11 | 0.882514E+10 | 384.06 | 0.203814E+11 | 0.132119E+11 | 0.00 | 1.00 | 0.00 | 37244.80 | 31736.99 | 22900.94 | 9652.64 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.322584E+10 | 0.102070E+10 | 194.08 | 0.298759E+10 | 0.238244E+09 | 0.00 | 0.26 | 12-JAN-15:10 | 0.00 | 01-JAN-00:05 | 12165.39 | 12-JAN-15:10 | 11632.82 | 12-JAN-15:10 | 1890.48 | 13-JAN-14:00 | 3868.02 | 12-JAN-15:10 | 0.00 | 01-JAN-00:05 |
February | 0.884571E+10 | 0.280384E+10 | 255.97 | 0.794564E+10 | 0.900077E+09 | 0.00 | 0.41 | 22-FEB-14:00 | 0.00 | 01-FEB-00:05 | 19838.12 | 22-FEB-14:00 | 18514.12 | 22-FEB-14:00 | 4554.57 | 25-FEB-16:00 | 6432.47 | 22-FEB-14:00 | 0.00 | 01-FEB-00:05 |
March | 0.206934E+11 | 0.676950E+10 | 352.71 | 0.184246E+11 | 0.226871E+10 | 0.00 | 1.00 | 11-MAR-08:62 | 0.00 | 01-MAR-00:05 | 62956.49 | 11-MAR-08:62 | 49031.51 | 30-MAR-07:02 | 16005.24 | 11-MAR-08:62 | 15939.40 | 11-MAR-08:62 | 0.00 | 01-MAR-00:05 |
April | 0.318256E+11 | 0.111887E+11 | 350.12 | 0.291395E+11 | 0.268610E+10 | 0.00 | 1.00 | 02-APR-08:62 | 0.00 | 01-APR-00:03 | 63965.78 | 17-APR-07:01 | 58439.28 | 08-APR-07:02 | 16953.38 | 17-APR-07:02 | 17228.09 | 16-APR-08:61 | 0.00 | 01-APR-00:03 |
May | 0.460631E+11 | 0.162283E+11 | 371.44 | 0.376853E+11 | 0.837772E+10 | 0.00 | 1.00 | 01-MAY-07:01 | 0.00 | 01-MAY-00:10 | 67206.05 | 21-MAY-08:61 | 59500.90 | 29-MAY-08:61 | 29955.35 | 24-MAY-07:03 | 18154.25 | 04-MAY-07:01 | 0.00 | 01-MAY-00:10 |
June | 0.512657E+11 | 0.172149E+11 | 362.20 | 0.371610E+11 | 0.141047E+11 | 0.00 | 1.00 | 01-JUN-07:01 | 0.00 | 01-JUN-00:10 | 69312.70 | 25-JUN-08:61 | 57726.53 | 12-JUN-07:01 | 40973.96 | 26-JUN-07:05 | 19340.32 | 10-JUN-16:00 | 0.00 | 01-JUN-00:10 |
July | 0.561280E+11 | 0.171800E+11 | 363.09 | 0.336787E+11 | 0.224493E+11 | 0.00 | 1.00 | 01-JUL-07:01 | 0.00 | 01-JUL-00:03 | 69298.65 | 23-JUL-08:61 | 49333.74 | 07-JUL-07:01 | 41546.50 | 23-JUL-08:06 | 18836.31 | 01-JUL-14:30 | 0.00 | 01-JUL-00:03 |
August | 0.569051E+11 | 0.169048E+11 | 373.09 | 0.320959E+11 | 0.248092E+11 | 0.00 | 1.00 | 01-AUG-07:01 | 0.00 | 01-AUG-00:10 | 69516.66 | 21-AUG-07:01 | 43052.48 | 08-AUG-07:01 | 42334.15 | 28-AUG-07:07 | 17974.42 | 27-AUG-14:10 | 0.00 | 01-AUG-00:10 |
September | 0.458909E+11 | 0.139711E+11 | 350.84 | 0.281038E+11 | 0.177871E+11 | 0.00 | 1.00 | 01-SEP-07:01 | 0.00 | 01-SEP-00:10 | 69548.19 | 04-SEP-08:61 | 47053.64 | 27-SEP-07:02 | 42455.64 | 11-SEP-07:05 | 17026.07 | 24-SEP-08:13 | 0.00 | 01-SEP-00:10 |
October | 0.308172E+11 | 0.100126E+11 | 356.85 | 0.251082E+11 | 0.570895E+10 | 0.00 | 1.00 | 01-OCT-08:61 | 0.00 | 01-OCT-00:03 | 65381.04 | 12-OCT-07:02 | 53138.05 | 23-OCT-07:02 | 25831.70 | 12-OCT-07:02 | 16404.30 | 04-OCT-07:01 | 0.00 | 01-OCT-00:03 |
November | 0.171407E+11 | 0.549649E+10 | 329.71 | 0.152944E+11 | 0.184634E+10 | 0.00 | 0.68 | 09-NOV-08:62 | 0.00 | 01-NOV-00:10 | 38042.59 | 09-NOV-08:62 | 28034.33 | 09-NOV-08:62 | 10008.26 | 09-NOV-08:62 | 10284.43 | 09-NOV-08:62 | 0.00 | 01-NOV-00:10 |
December | 0.572691E+10 | 0.180908E+10 | 249.67 | 0.516937E+10 | 0.557536E+09 | 0.00 | 0.31 | 28-DEC-14:00 | 0.00 | 01-DEC-00:10 | 14944.95 | 28-DEC-14:00 | 14227.76 | 02-DEC-14:10 | 2032.29 | 16-DEC-14:30 | 4764.58 | 28-DEC-14:00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.374528E+12 | 0.120600E+12 | 3909.77 | 0.272794E+12 | 0.101734E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.322584E+10 | 0.102070E+10 | 194.08 | 0.298759E+10 | 0.238244E+09 | 0.00 | 0.26 | 0.00 | 12165.39 | 11632.82 | 1890.48 | 3868.02 | 0.00 | |||||||
Maximum of Months | 0.569051E+11 | 0.172149E+11 | 373.09 | 0.376853E+11 | 0.248092E+11 | 0.00 | 1.00 | 0.00 | 69548.19 | 59500.90 | 42455.64 | 19340.32 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.161549E+10 | 0.482395E+09 | 192.08 | 0.150096E+10 | 0.114532E+09 | 0.00 | 0.26 | 12-JAN-15:10 | 0.00 | 01-JAN-00:05 | 6269.76 | 12-JAN-15:10 | 6015.52 | 12-JAN-15:10 | 948.05 | 13-JAN-14:00 | 1881.38 | 12-JAN-15:10 | 0.00 | 01-JAN-00:05 |
February | 0.454123E+10 | 0.135859E+10 | 256.06 | 0.409048E+10 | 0.450752E+09 | 0.00 | 0.40 | 22-FEB-14:00 | 0.00 | 01-FEB-00:05 | 10273.72 | 22-FEB-14:00 | 9610.48 | 22-FEB-14:00 | 2320.92 | 25-FEB-16:00 | 3144.05 | 22-FEB-14:00 | 0.00 | 01-FEB-00:05 |
March | 0.106785E+11 | 0.329820E+10 | 353.25 | 0.952977E+10 | 0.114873E+10 | 0.00 | 1.00 | 11-MAR-08:62 | 0.00 | 01-MAR-00:05 | 32893.71 | 11-MAR-08:62 | 24740.32 | 30-MAR-07:02 | 8332.96 | 11-MAR-08:62 | 7853.93 | 11-MAR-08:62 | 0.00 | 01-MAR-00:05 |
April | 0.164477E+11 | 0.546239E+10 | 350.06 | 0.150759E+11 | 0.137176E+10 | 0.00 | 1.00 | 02-APR-08:62 | 0.00 | 01-APR-00:03 | 33439.34 | 17-APR-07:01 | 30404.54 | 09-APR-08:62 | 8879.61 | 17-APR-07:02 | 8488.78 | 16-APR-08:61 | 0.00 | 01-APR-00:03 |
May | 0.238237E+11 | 0.793208E+10 | 370.63 | 0.195112E+11 | 0.431245E+10 | 0.00 | 1.00 | 01-MAY-07:01 | 0.00 | 01-MAY-00:10 | 35124.06 | 21-MAY-08:61 | 31080.17 | 29-MAY-08:61 | 15606.96 | 24-MAY-07:03 | 8942.27 | 04-MAY-07:01 | 0.00 | 01-MAY-00:10 |
June | 0.264974E+11 | 0.841265E+10 | 362.49 | 0.192304E+11 | 0.726697E+10 | 0.00 | 1.00 | 01-JUN-07:01 | 0.00 | 01-JUN-00:10 | 36227.43 | 25-JUN-08:61 | 30119.29 | 12-JUN-07:01 | 21496.29 | 26-JUN-07:05 | 9528.31 | 10-JUN-16:00 | 0.00 | 01-JUN-00:10 |
July | 0.290129E+11 | 0.839454E+10 | 362.20 | 0.174363E+11 | 0.115766E+11 | 0.00 | 1.00 | 01-JUL-07:01 | 0.00 | 01-JUL-00:03 | 36220.09 | 23-JUL-08:61 | 25766.48 | 07-JUL-07:01 | 21761.82 | 23-JUL-08:05 | 9269.48 | 10-JUL-13:00 | 0.00 | 01-JUL-00:03 |
August | 0.294002E+11 | 0.825641E+10 | 372.70 | 0.166098E+11 | 0.127904E+11 | 0.00 | 1.00 | 01-AUG-07:01 | 0.00 | 01-AUG-00:10 | 36334.04 | 21-AUG-07:01 | 22505.20 | 08-AUG-07:01 | 22306.93 | 28-AUG-07:06 | 8859.11 | 27-AUG-14:10 | 0.00 | 01-AUG-00:10 |
September | 0.237249E+11 | 0.682515E+10 | 350.70 | 0.145532E+11 | 0.917169E+10 | 0.00 | 1.00 | 01-SEP-07:01 | 0.00 | 01-SEP-00:10 | 36350.52 | 04-SEP-08:61 | 24649.94 | 27-SEP-07:02 | 22324.78 | 11-SEP-07:05 | 8390.90 | 24-SEP-08:13 | 0.00 | 01-SEP-00:10 |
October | 0.159328E+11 | 0.488883E+10 | 356.96 | 0.130085E+11 | 0.292431E+10 | 0.00 | 1.00 | 01-OCT-08:61 | 0.00 | 01-OCT-00:03 | 34146.73 | 12-OCT-07:02 | 27877.60 | 23-OCT-07:02 | 13386.53 | 12-OCT-07:02 | 8080.68 | 04-OCT-07:01 | 0.00 | 01-OCT-00:03 |
November | 0.885389E+10 | 0.267988E+10 | 329.57 | 0.792078E+10 | 0.933103E+09 | 0.00 | 0.61 | 09-NOV-08:62 | 0.00 | 01-NOV-00:10 | 17643.70 | 09-NOV-08:62 | 13061.63 | 09-NOV-08:62 | 4582.07 | 09-NOV-08:62 | 4584.90 | 09-NOV-08:62 | 0.00 | 01-NOV-00:10 |
December | 0.292910E+10 | 0.873199E+09 | 249.75 | 0.265119E+10 | 0.277910E+09 | 0.00 | 0.31 | 28-DEC-14:00 | 0.00 | 01-DEC-00:10 | 7703.43 | 28-DEC-14:00 | 7367.30 | 02-DEC-14:10 | 1030.62 | 16-DEC-14:30 | 2318.20 | 28-DEC-14:00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.193458E+12 | 0.588643E+11 | 3906.44 | 0.141119E+12 | 0.523392E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.161549E+10 | 0.482395E+09 | 192.08 | 0.150096E+10 | 0.114532E+09 | 0.00 | 0.26 | 0.00 | 6269.76 | 6015.52 | 948.05 | 1881.38 | 0.00 | |||||||
Maximum of Months | 0.294002E+11 | 0.841265E+10 | 372.70 | 0.195112E+11 | 0.127904E+11 | 0.00 | 1.00 | 0.00 | 36350.52 | 31080.17 | 22324.78 | 9528.31 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.155248E+10 | 0.463788E+09 | 186.83 | 0.144291E+10 | 0.109564E+09 | 0.00 | 0.25 | 12-JAN-15:10 | 0.00 | 01-JAN-00:05 | 6188.39 | 12-JAN-15:10 | 5935.51 | 12-JAN-15:10 | 934.88 | 13-JAN-14:00 | 1858.09 | 12-JAN-15:10 | 0.00 | 01-JAN-00:05 |
February | 0.445819E+10 | 0.133462E+10 | 254.89 | 0.401528E+10 | 0.442910E+09 | 0.00 | 0.40 | 22-FEB-14:00 | 0.00 | 01-FEB-00:05 | 10190.37 | 22-FEB-14:00 | 9529.41 | 22-FEB-14:00 | 2299.21 | 25-FEB-16:00 | 3119.96 | 22-FEB-14:00 | 0.00 | 01-FEB-00:05 |
March | 0.105776E+11 | 0.326866E+10 | 352.25 | 0.943647E+10 | 0.114116E+10 | 0.00 | 1.00 | 11-MAR-08:62 | 0.00 | 01-MAR-00:05 | 32773.05 | 11-MAR-08:62 | 24422.53 | 11-MAR-08:62 | 8350.51 | 11-MAR-08:62 | 7825.63 | 11-MAR-08:62 | 0.00 | 01-MAR-00:05 |
April | 0.163569E+11 | 0.543340E+10 | 350.06 | 0.149893E+11 | 0.136755E+10 | 0.00 | 1.00 | 02-APR-08:62 | 0.00 | 01-APR-00:03 | 33317.21 | 17-APR-07:01 | 30285.74 | 09-APR-08:62 | 8874.28 | 17-APR-07:02 | 8458.39 | 16-APR-08:61 | 0.00 | 01-APR-00:03 |
May | 0.237284E+11 | 0.790005E+10 | 370.52 | 0.194256E+11 | 0.430284E+10 | 0.00 | 1.00 | 01-MAY-07:01 | 0.00 | 01-MAY-00:10 | 34996.89 | 21-MAY-08:61 | 30966.07 | 29-MAY-08:61 | 15589.79 | 24-MAY-07:03 | 8910.29 | 04-MAY-07:01 | 0.00 | 01-MAY-00:10 |
June | 0.263999E+11 | 0.838035E+10 | 362.42 | 0.191470E+11 | 0.725290E+10 | 0.00 | 1.00 | 01-JUN-07:01 | 0.00 | 01-JUN-00:10 | 36099.44 | 25-JUN-08:61 | 29997.04 | 12-JUN-07:01 | 21444.94 | 26-JUN-07:05 | 9499.12 | 10-JUN-16:00 | 0.00 | 01-JUN-00:10 |
July | 0.289169E+11 | 0.836446E+10 | 362.18 | 0.173601E+11 | 0.115568E+11 | 0.00 | 1.00 | 01-JUL-07:01 | 0.00 | 01-JUL-00:03 | 36092.12 | 23-JUL-08:61 | 25632.11 | 07-JUL-07:01 | 21706.80 | 23-JUL-08:05 | 9244.18 | 10-JUL-13:00 | 0.00 | 01-JUL-00:03 |
August | 0.292997E+11 | 0.822598E+10 | 372.72 | 0.165318E+11 | 0.127679E+11 | 0.00 | 1.00 | 01-AUG-07:01 | 0.00 | 01-AUG-00:10 | 36205.66 | 21-AUG-07:01 | 22387.41 | 08-AUG-07:01 | 22248.54 | 28-AUG-07:06 | 8834.40 | 27-AUG-14:10 | 0.00 | 01-AUG-00:10 |
September | 0.236340E+11 | 0.679790E+10 | 350.70 | 0.144811E+11 | 0.915293E+10 | 0.00 | 1.00 | 01-SEP-07:01 | 0.00 | 01-SEP-00:10 | 36222.08 | 04-SEP-08:61 | 24515.87 | 27-SEP-07:02 | 22271.95 | 11-SEP-07:05 | 8361.27 | 24-SEP-08:13 | 0.00 | 01-SEP-00:10 |
October | 0.158454E+11 | 0.486279E+10 | 356.79 | 0.129308E+11 | 0.291463E+10 | 0.00 | 1.00 | 01-OCT-08:61 | 0.00 | 01-OCT-00:03 | 34026.02 | 12-OCT-07:02 | 27747.54 | 23-OCT-07:02 | 13390.71 | 12-OCT-07:02 | 8052.15 | 04-OCT-07:01 | 0.00 | 01-OCT-00:03 |
November | 0.876935E+10 | 0.265540E+10 | 329.07 | 0.784264E+10 | 0.926710E+09 | 0.00 | 0.59 | 09-NOV-08:62 | 0.00 | 01-NOV-00:10 | 17001.21 | 09-NOV-08:62 | 12657.88 | 04-NOV-14:10 | 4445.45 | 09-NOV-08:62 | 4440.35 | 09-NOV-08:62 | 0.00 | 01-NOV-00:10 |
December | 0.285488E+10 | 0.851537E+09 | 248.17 | 0.258351E+10 | 0.271365E+09 | 0.00 | 0.31 | 28-DEC-14:00 | 0.00 | 01-DEC-00:10 | 7621.03 | 28-DEC-14:00 | 7296.29 | 02-DEC-14:10 | 1021.70 | 16-DEC-14:30 | 2294.66 | 28-DEC-14:00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.192394E+12 | 0.585389E+11 | 3896.59 | 0.140186E+12 | 0.522073E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.155248E+10 | 0.463788E+09 | 186.83 | 0.144291E+10 | 0.109564E+09 | 0.00 | 0.25 | 0.00 | 6188.39 | 5935.51 | 934.88 | 1858.09 | 0.00 | |||||||
Maximum of Months | 0.292997E+11 | 0.838035E+10 | 372.72 | 0.194256E+11 | 0.127679E+11 | 0.00 | 1.00 | 0.00 | 36222.08 | 30966.07 | 22271.95 | 9499.12 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.142967E+10 | 0.427611E+09 | 177.25 | 0.133017E+10 | 99503103.80 | 0.00 | 0.25 | 12-JAN-15:10 | 0.00 | 01-JAN-00:05 | 6027.52 | 12-JAN-15:10 | 5780.35 | 12-JAN-15:10 | 904.12 | 13-JAN-14:00 | 1813.00 | 12-JAN-15:10 | 0.00 | 01-JAN-00:05 |
February | 0.428823E+10 | 0.128603E+10 | 250.14 | 0.386389E+10 | 0.424346E+09 | 0.00 | 0.40 | 22-FEB-14:00 | 0.00 | 01-FEB-00:05 | 10065.83 | 22-FEB-14:00 | 9411.10 | 22-FEB-14:00 | 2261.55 | 25-FEB-16:00 | 3086.19 | 22-FEB-14:00 | 0.00 | 01-FEB-00:05 |
March | 0.104108E+11 | 0.322205E+10 | 350.73 | 0.928623E+10 | 0.112454E+10 | 0.00 | 1.00 | 11-MAR-08:62 | 0.00 | 01-MAR-00:05 | 32820.01 | 11-MAR-08:62 | 24348.36 | 11-MAR-08:62 | 8471.65 | 11-MAR-08:62 | 7838.91 | 11-MAR-08:62 | 0.00 | 01-MAR-00:05 |
April | 0.163069E+11 | 0.542084E+10 | 350.41 | 0.149435E+11 | 0.136344E+10 | 0.00 | 1.00 | 02-APR-08:62 | 0.00 | 01-APR-00:03 | 33373.41 | 17-APR-07:01 | 30313.43 | 09-APR-08:62 | 8924.32 | 17-APR-07:02 | 8473.96 | 16-APR-08:61 | 0.00 | 01-APR-00:03 |
May | 0.237467E+11 | 0.790864E+10 | 370.44 | 0.194457E+11 | 0.430105E+10 | 0.00 | 1.00 | 01-MAY-07:01 | 0.00 | 01-MAY-00:10 | 35057.83 | 21-MAY-08:61 | 31022.88 | 29-MAY-08:61 | 15675.81 | 24-MAY-07:03 | 8927.98 | 04-MAY-07:01 | 0.00 | 01-MAY-00:10 |
June | 0.264410E+11 | 0.839539E+10 | 362.39 | 0.191866E+11 | 0.725447E+10 | 0.00 | 1.00 | 01-JUN-07:01 | 0.00 | 01-JUN-00:10 | 36171.30 | 25-JUN-08:61 | 30087.45 | 12-JUN-07:01 | 21551.18 | 26-JUN-07:05 | 9522.32 | 10-JUN-16:00 | 0.00 | 01-JUN-00:10 |
July | 0.289842E+11 | 0.838473E+10 | 362.17 | 0.174169E+11 | 0.115673E+11 | 0.00 | 1.00 | 01-JUL-07:01 | 0.00 | 01-JUL-00:03 | 36163.97 | 23-JUL-08:61 | 25722.39 | 07-JUL-07:01 | 21786.30 | 23-JUL-08:05 | 9278.46 | 10-JUL-13:00 | 0.00 | 01-JUL-00:03 |
August | 0.293707E+11 | 0.824673E+10 | 372.81 | 0.165889E+11 | 0.127818E+11 | 0.00 | 1.00 | 01-AUG-07:01 | 0.00 | 01-AUG-00:10 | 36277.74 | 21-AUG-07:01 | 22475.72 | 08-AUG-07:01 | 22283.31 | 28-AUG-07:07 | 8858.49 | 27-AUG-14:10 | 0.00 | 01-AUG-00:10 |
September | 0.236756E+11 | 0.681102E+10 | 350.65 | 0.145168E+11 | 0.915885E+10 | 0.00 | 1.00 | 01-SEP-07:01 | 0.00 | 01-SEP-00:10 | 36294.19 | 04-SEP-08:61 | 24563.11 | 27-SEP-07:02 | 22357.68 | 11-SEP-07:05 | 8377.94 | 24-SEP-08:13 | 0.00 | 01-SEP-00:10 |
October | 0.158278E+11 | 0.485922E+10 | 356.79 | 0.129176E+11 | 0.291013E+10 | 0.00 | 1.00 | 01-OCT-08:61 | 0.00 | 01-OCT-00:03 | 34085.64 | 12-OCT-07:02 | 27773.32 | 23-OCT-07:02 | 13470.66 | 12-OCT-07:02 | 8067.48 | 04-OCT-07:01 | 0.00 | 01-OCT-00:03 |
November | 0.865557E+10 | 0.262371E+10 | 327.01 | 0.774058E+10 | 0.914993E+09 | 0.00 | 0.54 | 09-NOV-08:62 | 0.00 | 01-NOV-00:10 | 15337.05 | 09-NOV-08:62 | 12611.35 | 04-NOV-14:10 | 4051.75 | 09-NOV-08:62 | 4190.49 | 09-NOV-13:30 | 0.00 | 01-NOV-00:10 |
December | 0.270313E+10 | 0.807419E+09 | 242.17 | 0.244691E+10 | 0.256218E+09 | 0.00 | 0.30 | 28-DEC-14:00 | 0.00 | 01-DEC-00:10 | 7481.34 | 28-DEC-14:00 | 7170.13 | 02-DEC-14:10 | 1002.83 | 16-DEC-14:30 | 2256.08 | 28-DEC-14:00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.191840E+12 | 0.583934E+11 | 3872.95 | 0.139684E+12 | 0.521567E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.142967E+10 | 0.427611E+09 | 177.25 | 0.133017E+10 | 99503103.80 | 0.00 | 0.25 | 0.00 | 6027.52 | 5780.35 | 904.12 | 1813.00 | 0.00 | |||||||
Maximum of Months | 0.293707E+11 | 0.839539E+10 | 372.81 | 0.194457E+11 | 0.127818E+11 | 0.00 | 1.00 | 0.00 | 36294.19 | 31022.88 | 22357.68 | 9522.32 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.146200E+10 | 0.437930E+09 | 173.17 | 0.137118E+10 | 90819714.12 | 0.00 | 0.23 | 12-JAN-15:10 | 0.00 | 01-JAN-00:05 | 6176.59 | 12-JAN-15:10 | 5968.32 | 12-JAN-15:10 | 878.72 | 13-JAN-14:00 | 1864.37 | 12-JAN-15:10 | 0.00 | 01-JAN-00:05 |
February | 0.438037E+10 | 0.131746E+10 | 242.33 | 0.397913E+10 | 0.401237E+09 | 0.00 | 0.39 | 22-FEB-14:00 | 0.00 | 01-FEB-00:05 | 10647.27 | 22-FEB-14:00 | 10025.19 | 22-FEB-14:00 | 2226.64 | 25-FEB-16:00 | 3273.22 | 22-FEB-14:00 | 0.00 | 01-FEB-00:05 |
March | 0.108272E+11 | 0.336491E+10 | 344.30 | 0.972139E+10 | 0.110576E+10 | 0.00 | 0.82 | 11-MAR-08:62 | 0.00 | 01-MAR-00:05 | 27387.36 | 11-MAR-08:62 | 20224.19 | 11-MAR-08:62 | 7163.18 | 11-MAR-08:62 | 6945.11 | 11-MAR-08:62 | 0.00 | 01-MAR-00:05 |
April | 0.175379E+11 | 0.584426E+10 | 352.21 | 0.161432E+11 | 0.139469E+10 | 0.00 | 1.00 | 02-APR-08:62 | 0.00 | 01-APR-00:03 | 36336.25 | 17-APR-07:01 | 33050.60 | 09-APR-08:62 | 10160.48 | 03-APR-07:02 | 9207.86 | 16-APR-08:61 | 0.00 | 01-APR-00:03 |
May | 0.257401E+11 | 0.860050E+10 | 372.88 | 0.212393E+11 | 0.450079E+10 | 0.00 | 1.00 | 01-MAY-07:01 | 0.00 | 01-MAY-00:10 | 38738.32 | 24-MAY-07:02 | 33922.23 | 29-MAY-08:61 | 20005.20 | 24-MAY-07:03 | 9714.71 | 04-MAY-07:01 | 0.00 | 01-MAY-00:10 |
June | 0.285667E+11 | 0.911582E+10 | 364.09 | 0.209952E+11 | 0.757148E+10 | 0.00 | 1.00 | 01-JUN-07:01 | 0.00 | 01-JUN-00:10 | 39298.52 | 25-JUN-08:61 | 33513.19 | 12-JUN-07:01 | 24323.68 | 26-JUN-07:05 | 10212.62 | 10-JUN-16:00 | 0.00 | 01-JUN-00:10 |
July | 0.314494E+11 | 0.914184E+10 | 366.79 | 0.192488E+11 | 0.122005E+11 | 0.00 | 1.00 | 01-JUL-07:01 | 0.00 | 01-JUL-00:03 | 39406.39 | 26-JUL-07:01 | 27843.38 | 07-JUL-07:01 | 24217.22 | 23-JUL-08:05 | 10101.26 | 10-JUL-13:00 | 0.00 | 01-JUL-00:03 |
August | 0.318465E+11 | 0.898650E+10 | 374.01 | 0.184148E+11 | 0.134318E+11 | 0.00 | 1.00 | 01-AUG-07:01 | 0.00 | 01-AUG-00:10 | 39414.16 | 21-AUG-07:01 | 23812.56 | 09-AUG-07:01 | 24185.84 | 28-AUG-07:07 | 9572.99 | 27-AUG-14:10 | 0.00 | 01-AUG-00:10 |
September | 0.256530E+11 | 0.741030E+10 | 351.91 | 0.160701E+11 | 0.958292E+10 | 0.00 | 1.00 | 01-SEP-07:01 | 0.00 | 01-SEP-00:10 | 39432.04 | 04-SEP-08:61 | 27113.85 | 27-SEP-07:02 | 24580.73 | 10-SEP-08:05 | 9102.43 | 24-SEP-08:13 | 0.00 | 01-SEP-00:10 |
October | 0.172141E+11 | 0.528992E+10 | 357.89 | 0.142052E+11 | 0.300888E+10 | 0.00 | 1.00 | 01-OCT-08:61 | 0.00 | 01-OCT-00:03 | 37489.73 | 12-OCT-07:02 | 29386.04 | 03-OCT-07:02 | 16465.91 | 12-OCT-07:02 | 8769.19 | 04-OCT-07:01 | 0.00 | 01-OCT-00:03 |
November | 0.923628E+10 | 0.280367E+10 | 324.83 | 0.832552E+10 | 0.910765E+09 | 0.00 | 0.51 | 09-NOV-13:10 | 0.00 | 01-NOV-00:10 | 14689.64 | 09-NOV-13:10 | 13509.37 | 04-NOV-14:00 | 2805.18 | 09-NOV-08:62 | 4524.22 | 09-NOV-13:10 | 0.00 | 01-NOV-00:10 |
December | 0.279841E+10 | 0.836918E+09 | 237.67 | 0.255791E+10 | 0.240500E+09 | 0.00 | 0.29 | 28-DEC-14:00 | 0.00 | 01-DEC-00:10 | 7809.68 | 28-DEC-14:00 | 7493.66 | 02-DEC-14:00 | 1001.16 | 16-DEC-14:30 | 2362.02 | 28-DEC-14:00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.206712E+12 | 0.631500E+11 | 3862.07 | 0.152272E+12 | 0.544401E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.146200E+10 | 0.437930E+09 | 173.17 | 0.137118E+10 | 90819714.12 | 0.00 | 0.23 | 0.00 | 6176.59 | 5968.32 | 878.72 | 1864.37 | 0.00 | |||||||
Maximum of Months | 0.318465E+11 | 0.914184E+10 | 374.01 | 0.212393E+11 | 0.134318E+11 | 0.00 | 1.00 | 0.00 | 39432.04 | 33922.23 | 24580.73 | 10212.62 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 54.66 | 32.93 | 21.73 | 118.24 | 101.89 | 0.00 | 0.00 | 744.00 |
February | 52.73 | 29.32 | 23.41 | 126.64 | 80.99 | 0.00 | 0.00 | 672.00 |
March | 46.63 | 21.50 | 25.14 | 132.88 | 47.98 | 0.00 | 0.00 | 744.00 |
April | 34.08 | 11.38 | 22.70 | 132.12 | 17.87 | 0.00 | 0.00 | 720.00 |
May | 23.73 | 2.67 | 21.06 | 124.59 | 4.02 | 0.00 | 0.00 | 744.00 |
June | 21.10 | 0.65 | 20.45 | 123.49 | 3.72 | 0.00 | 0.00 | 720.00 |
July | 21.90 | 0.50 | 21.40 | 112.94 | 1.20 | 0.00 | 0.00 | 744.00 |
August | 23.45 | 1.66 | 21.79 | 104.87 | 3.21 | 0.00 | 0.00 | 744.00 |
September | 31.86 | 9.01 | 22.85 | 114.91 | 10.35 | 0.00 | 0.00 | 720.00 |
October | 53.73 | 30.28 | 23.45 | 172.69 | 37.88 | 0.00 | 0.00 | 744.00 |
November | 65.48 | 43.00 | 22.48 | 180.37 | 70.96 | 0.00 | 0.00 | 720.00 |
December | 58.16 | 36.06 | 22.10 | 133.44 | 99.50 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 40.55 | 18.18 | 22.37 | 131.40 | 39.78 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 21.10 | 0.50 | 20.45 | 104.87 | 1.20 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 65.48 | 43.00 | 25.14 | 180.37 | 101.89 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 54.66 | 32.93 | 21.73 | 118.24 | 101.89 | 0.00 | 0.00 | 744.00 |
February | 52.73 | 29.32 | 23.41 | 126.64 | 80.99 | 0.00 | 0.00 | 672.00 |
March | 46.63 | 21.50 | 25.14 | 132.88 | 47.98 | 0.00 | 0.00 | 744.00 |
April | 34.08 | 11.38 | 22.70 | 132.12 | 17.87 | 0.00 | 0.00 | 720.00 |
May | 23.73 | 2.67 | 21.06 | 124.59 | 4.02 | 0.00 | 0.00 | 744.00 |
June | 21.10 | 0.65 | 20.45 | 123.49 | 3.72 | 0.00 | 0.00 | 720.00 |
July | 21.90 | 0.50 | 21.40 | 112.94 | 1.20 | 0.00 | 0.00 | 744.00 |
August | 23.45 | 1.66 | 21.79 | 104.87 | 3.21 | 0.00 | 0.00 | 744.00 |
September | 31.86 | 9.01 | 22.85 | 114.91 | 10.35 | 0.00 | 0.00 | 720.00 |
October | 53.73 | 30.28 | 23.45 | 172.69 | 37.88 | 0.00 | 0.00 | 744.00 |
November | 65.48 | 43.00 | 22.48 | 180.37 | 70.96 | 0.00 | 0.00 | 720.00 |
December | 58.16 | 36.06 | 22.10 | 133.44 | 99.50 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 40.55 | 18.18 | 22.37 | 131.40 | 39.78 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 21.10 | 0.50 | 20.45 | 104.87 | 1.20 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 65.48 | 43.00 | 25.14 | 180.37 | 101.89 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_3
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 54.66 | 32.93 | 21.73 | 118.24 | 101.89 | 0.00 | 0.00 | 744.00 |
February | 52.73 | 29.32 | 23.41 | 126.64 | 80.99 | 0.00 | 0.00 | 672.00 |
March | 46.63 | 21.50 | 25.14 | 132.88 | 47.98 | 0.00 | 0.00 | 744.00 |
April | 34.08 | 11.38 | 22.70 | 132.12 | 17.87 | 0.00 | 0.00 | 720.00 |
May | 23.73 | 2.67 | 21.06 | 124.59 | 4.02 | 0.00 | 0.00 | 744.00 |
June | 21.10 | 0.65 | 20.45 | 123.49 | 3.72 | 0.00 | 0.00 | 720.00 |
July | 21.90 | 0.50 | 21.40 | 112.94 | 1.20 | 0.00 | 0.00 | 744.00 |
August | 23.45 | 1.66 | 21.79 | 104.87 | 3.21 | 0.00 | 0.00 | 744.00 |
September | 31.86 | 9.01 | 22.85 | 114.91 | 10.35 | 0.00 | 0.00 | 720.00 |
October | 53.73 | 30.28 | 23.45 | 172.69 | 37.88 | 0.00 | 0.00 | 744.00 |
November | 65.48 | 43.00 | 22.48 | 180.37 | 70.96 | 0.00 | 0.00 | 720.00 |
December | 58.16 | 36.06 | 22.10 | 133.44 | 99.50 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 40.55 | 18.18 | 22.37 | 131.40 | 39.78 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 21.10 | 0.50 | 20.45 | 104.87 | 1.20 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 65.48 | 43.00 | 25.14 | 180.37 | 101.89 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_4
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 54.66 | 32.93 | 21.73 | 118.24 | 101.89 | 0.00 | 0.00 | 744.00 |
February | 52.73 | 29.32 | 23.41 | 126.64 | 80.99 | 0.00 | 0.00 | 672.00 |
March | 46.63 | 21.50 | 25.14 | 132.88 | 47.98 | 0.00 | 0.00 | 744.00 |
April | 34.08 | 11.38 | 22.70 | 132.12 | 17.87 | 0.00 | 0.00 | 720.00 |
May | 23.73 | 2.67 | 21.06 | 124.59 | 4.02 | 0.00 | 0.00 | 744.00 |
June | 21.10 | 0.65 | 20.45 | 123.49 | 3.72 | 0.00 | 0.00 | 720.00 |
July | 21.90 | 0.50 | 21.40 | 112.94 | 1.20 | 0.00 | 0.00 | 744.00 |
August | 23.45 | 1.66 | 21.79 | 104.87 | 3.21 | 0.00 | 0.00 | 744.00 |
September | 31.86 | 9.01 | 22.85 | 114.91 | 10.35 | 0.00 | 0.00 | 720.00 |
October | 53.73 | 30.28 | 23.45 | 172.69 | 37.88 | 0.00 | 0.00 | 744.00 |
November | 65.48 | 43.00 | 22.48 | 180.37 | 70.96 | 0.00 | 0.00 | 720.00 |
December | 58.16 | 36.06 | 22.10 | 133.44 | 99.50 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 40.55 | 18.18 | 22.37 | 131.40 | 39.78 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 21.10 | 0.50 | 20.45 | 104.87 | 1.20 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 65.48 | 43.00 | 25.14 | 180.37 | 101.89 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_DOOR_1
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 65.80 | 39.64 | 26.16 | 141.57 | 121.06 | 0.00 | 0.00 | 744.00 |
February | 63.49 | 35.30 | 28.19 | 151.52 | 96.21 | 0.00 | 0.00 | 672.00 |
March | 56.15 | 25.88 | 30.27 | 158.63 | 57.18 | 0.00 | 0.00 | 744.00 |
April | 41.03 | 13.70 | 27.33 | 157.19 | 21.35 | 0.00 | 0.00 | 720.00 |
May | 28.57 | 3.21 | 25.36 | 147.73 | 4.82 | 0.00 | 0.00 | 744.00 |
June | 25.40 | 0.78 | 24.62 | 146.39 | 4.44 | 0.00 | 0.00 | 720.00 |
July | 26.37 | 0.60 | 25.77 | 133.96 | 1.45 | 0.00 | 0.00 | 744.00 |
August | 28.23 | 2.00 | 26.24 | 124.57 | 3.87 | 0.00 | 0.00 | 744.00 |
September | 38.36 | 10.85 | 27.51 | 136.71 | 12.40 | 0.00 | 0.00 | 720.00 |
October | 64.68 | 36.45 | 28.23 | 205.86 | 45.24 | 0.00 | 0.00 | 744.00 |
November | 78.83 | 51.76 | 27.07 | 215.38 | 84.53 | 0.00 | 0.00 | 720.00 |
December | 70.02 | 43.42 | 26.61 | 159.63 | 118.25 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 48.82 | 21.89 | 26.94 | 156.56 | 47.35 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 25.40 | 0.60 | 24.62 | 124.57 | 1.45 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 78.83 | 51.76 | 30.27 | 215.38 | 121.06 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_DOOR_2
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 65.80 | 39.64 | 26.16 | 141.57 | 121.06 | 0.00 | 0.00 | 744.00 |
February | 63.49 | 35.30 | 28.19 | 151.52 | 96.21 | 0.00 | 0.00 | 672.00 |
March | 56.15 | 25.88 | 30.27 | 158.63 | 57.18 | 0.00 | 0.00 | 744.00 |
April | 41.03 | 13.70 | 27.33 | 157.19 | 21.35 | 0.00 | 0.00 | 720.00 |
May | 28.57 | 3.21 | 25.36 | 147.73 | 4.82 | 0.00 | 0.00 | 744.00 |
June | 25.40 | 0.78 | 24.62 | 146.39 | 4.44 | 0.00 | 0.00 | 720.00 |
July | 26.37 | 0.60 | 25.77 | 133.96 | 1.45 | 0.00 | 0.00 | 744.00 |
August | 28.23 | 2.00 | 26.24 | 124.57 | 3.87 | 0.00 | 0.00 | 744.00 |
September | 38.36 | 10.85 | 27.51 | 136.71 | 12.40 | 0.00 | 0.00 | 720.00 |
October | 64.68 | 36.45 | 28.23 | 205.86 | 45.24 | 0.00 | 0.00 | 744.00 |
November | 78.83 | 51.76 | 27.07 | 215.38 | 84.53 | 0.00 | 0.00 | 720.00 |
December | 70.02 | 43.42 | 26.61 | 159.63 | 118.25 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 48.82 | 21.89 | 26.94 | 156.56 | 47.35 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 25.40 | 0.60 | 24.62 | 124.57 | 1.45 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 78.83 | 51.76 | 30.27 | 215.38 | 121.06 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 54.66 | 32.93 | 21.73 | 117.15 | 103.38 | 0.00 | 0.00 | 744.00 |
February | 52.73 | 29.32 | 23.41 | 125.73 | 82.12 | 0.00 | 0.00 | 672.00 |
March | 46.63 | 21.50 | 25.14 | 132.64 | 48.39 | 0.00 | 0.00 | 744.00 |
April | 34.08 | 11.38 | 22.70 | 133.15 | 17.74 | 0.00 | 0.00 | 720.00 |
May | 23.73 | 2.67 | 21.06 | 126.87 | 3.74 | 0.00 | 0.00 | 744.00 |
June | 21.10 | 0.65 | 20.45 | 126.30 | 3.45 | 0.00 | 0.00 | 720.00 |
July | 21.90 | 0.50 | 21.40 | 115.70 | 1.00 | 0.00 | 0.00 | 744.00 |
August | 23.45 | 1.66 | 21.79 | 107.06 | 2.74 | 0.00 | 0.00 | 744.00 |
September | 31.86 | 9.01 | 22.85 | 116.41 | 9.45 | 0.00 | 0.00 | 720.00 |
October | 53.73 | 30.28 | 23.45 | 173.25 | 37.21 | 0.00 | 0.00 | 744.00 |
November | 65.48 | 43.00 | 22.48 | 180.11 | 70.89 | 0.00 | 0.00 | 720.00 |
December | 58.16 | 36.06 | 22.10 | 132.59 | 100.40 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 40.55 | 18.18 | 22.37 | 132.23 | 39.86 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 21.10 | 0.50 | 20.45 | 107.06 | 1.00 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 65.48 | 43.00 | 25.14 | 180.11 | 103.38 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 54.66 | 32.93 | 21.73 | 117.15 | 103.38 | 0.00 | 0.00 | 744.00 |
February | 52.73 | 29.32 | 23.41 | 125.73 | 82.12 | 0.00 | 0.00 | 672.00 |
March | 46.63 | 21.50 | 25.14 | 132.64 | 48.39 | 0.00 | 0.00 | 744.00 |
April | 34.08 | 11.38 | 22.70 | 133.15 | 17.74 | 0.00 | 0.00 | 720.00 |
May | 23.73 | 2.67 | 21.06 | 126.87 | 3.74 | 0.00 | 0.00 | 744.00 |
June | 21.10 | 0.65 | 20.45 | 126.30 | 3.45 | 0.00 | 0.00 | 720.00 |
July | 21.90 | 0.50 | 21.40 | 115.70 | 1.00 | 0.00 | 0.00 | 744.00 |
August | 23.45 | 1.66 | 21.79 | 107.06 | 2.74 | 0.00 | 0.00 | 744.00 |
September | 31.86 | 9.01 | 22.85 | 116.41 | 9.45 | 0.00 | 0.00 | 720.00 |
October | 53.73 | 30.28 | 23.45 | 173.25 | 37.21 | 0.00 | 0.00 | 744.00 |
November | 65.48 | 43.00 | 22.48 | 180.11 | 70.89 | 0.00 | 0.00 | 720.00 |
December | 58.16 | 36.06 | 22.10 | 132.59 | 100.40 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 40.55 | 18.18 | 22.37 | 132.23 | 39.86 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 21.10 | 0.50 | 20.45 | 107.06 | 1.00 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 65.48 | 43.00 | 25.14 | 180.11 | 103.38 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_DOOR
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 65.80 | 39.64 | 26.16 | 140.33 | 122.78 | 0.00 | 0.00 | 744.00 |
February | 63.49 | 35.30 | 28.19 | 150.49 | 97.52 | 0.00 | 0.00 | 672.00 |
March | 56.15 | 25.88 | 30.27 | 158.40 | 57.64 | 0.00 | 0.00 | 744.00 |
April | 41.03 | 13.70 | 27.33 | 158.46 | 21.18 | 0.00 | 0.00 | 720.00 |
May | 28.57 | 3.21 | 25.36 | 150.45 | 4.49 | 0.00 | 0.00 | 744.00 |
June | 25.40 | 0.78 | 24.62 | 149.76 | 4.11 | 0.00 | 0.00 | 720.00 |
July | 26.37 | 0.60 | 25.77 | 137.26 | 1.20 | 0.00 | 0.00 | 744.00 |
August | 28.23 | 2.00 | 26.24 | 127.22 | 3.29 | 0.00 | 0.00 | 744.00 |
September | 38.36 | 10.85 | 27.51 | 138.54 | 11.31 | 0.00 | 0.00 | 720.00 |
October | 64.68 | 36.45 | 28.23 | 206.58 | 44.43 | 0.00 | 0.00 | 744.00 |
November | 78.83 | 51.76 | 27.07 | 215.13 | 84.41 | 0.00 | 0.00 | 720.00 |
December | 70.02 | 43.42 | 26.61 | 158.67 | 119.28 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 48.82 | 21.89 | 26.94 | 157.58 | 47.42 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 25.40 | 0.60 | 24.62 | 127.22 | 1.20 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 78.83 | 51.76 | 30.27 | 215.13 | 122.78 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 54.66 | 32.93 | 21.73 | 118.59 | 99.07 | 0.00 | 0.00 | 744.00 |
February | 52.73 | 29.32 | 23.41 | 126.54 | 80.72 | 0.00 | 0.00 | 672.00 |
March | 46.63 | 21.50 | 25.14 | 132.75 | 49.87 | 0.00 | 0.00 | 744.00 |
April | 34.08 | 11.38 | 22.70 | 130.79 | 20.01 | 0.00 | 0.00 | 720.00 |
May | 23.73 | 2.67 | 21.06 | 121.73 | 5.10 | 0.00 | 0.00 | 744.00 |
June | 21.10 | 0.65 | 20.45 | 120.76 | 4.69 | 0.00 | 0.00 | 720.00 |
July | 21.90 | 0.50 | 21.40 | 109.49 | 1.60 | 0.00 | 0.00 | 744.00 |
August | 23.45 | 1.66 | 21.79 | 103.36 | 4.10 | 0.00 | 0.00 | 744.00 |
September | 31.86 | 9.01 | 22.85 | 114.69 | 12.20 | 0.00 | 0.00 | 720.00 |
October | 53.73 | 30.28 | 23.45 | 172.89 | 40.35 | 0.00 | 0.00 | 744.00 |
November | 65.48 | 43.00 | 22.48 | 180.56 | 71.66 | 0.00 | 0.00 | 720.00 |
December | 58.16 | 36.06 | 22.10 | 133.75 | 97.74 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 40.55 | 18.18 | 22.37 | 130.46 | 40.41 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 21.10 | 0.50 | 20.45 | 103.36 | 1.60 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 65.48 | 43.00 | 25.14 | 180.56 | 99.07 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 54.66 | 32.93 | 21.73 | 118.59 | 99.07 | 0.00 | 0.00 | 744.00 |
February | 52.73 | 29.32 | 23.41 | 126.54 | 80.72 | 0.00 | 0.00 | 672.00 |
March | 46.63 | 21.50 | 25.14 | 132.75 | 49.87 | 0.00 | 0.00 | 744.00 |
April | 34.08 | 11.38 | 22.70 | 130.79 | 20.01 | 0.00 | 0.00 | 720.00 |
May | 23.73 | 2.67 | 21.06 | 121.73 | 5.10 | 0.00 | 0.00 | 744.00 |
June | 21.10 | 0.65 | 20.45 | 120.76 | 4.69 | 0.00 | 0.00 | 720.00 |
July | 21.90 | 0.50 | 21.40 | 109.49 | 1.60 | 0.00 | 0.00 | 744.00 |
August | 23.45 | 1.66 | 21.79 | 103.36 | 4.10 | 0.00 | 0.00 | 744.00 |
September | 31.86 | 9.01 | 22.85 | 114.69 | 12.20 | 0.00 | 0.00 | 720.00 |
October | 53.73 | 30.28 | 23.45 | 172.89 | 40.35 | 0.00 | 0.00 | 744.00 |
November | 65.48 | 43.00 | 22.48 | 180.56 | 71.66 | 0.00 | 0.00 | 720.00 |
December | 58.16 | 36.06 | 22.10 | 133.75 | 97.74 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 40.55 | 18.18 | 22.37 | 130.46 | 40.41 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 21.10 | 0.50 | 20.45 | 103.36 | 1.60 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 65.48 | 43.00 | 25.14 | 180.56 | 99.07 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_DOOR
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 65.44 | 39.42 | 26.02 | 141.29 | 116.97 | 0.00 | 0.00 | 744.00 |
February | 63.14 | 35.11 | 28.03 | 150.65 | 95.26 | 0.00 | 0.00 | 672.00 |
March | 55.84 | 25.74 | 30.10 | 157.68 | 58.98 | 0.00 | 0.00 | 744.00 |
April | 40.81 | 13.63 | 27.18 | 154.91 | 23.71 | 0.00 | 0.00 | 720.00 |
May | 28.41 | 3.19 | 25.22 | 143.74 | 6.07 | 0.00 | 0.00 | 744.00 |
June | 25.26 | 0.77 | 24.49 | 142.56 | 5.53 | 0.00 | 0.00 | 720.00 |
July | 26.22 | 0.59 | 25.63 | 129.38 | 1.91 | 0.00 | 0.00 | 744.00 |
August | 28.08 | 1.99 | 26.09 | 122.29 | 4.87 | 0.00 | 0.00 | 744.00 |
September | 38.15 | 10.79 | 27.36 | 135.86 | 14.46 | 0.00 | 0.00 | 720.00 |
October | 64.33 | 36.26 | 28.07 | 205.06 | 47.81 | 0.00 | 0.00 | 744.00 |
November | 78.40 | 51.48 | 26.92 | 214.51 | 84.76 | 0.00 | 0.00 | 720.00 |
December | 69.64 | 43.18 | 26.46 | 159.20 | 115.42 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 48.56 | 21.77 | 26.79 | 154.71 | 47.77 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 25.26 | 0.59 | 24.49 | 122.29 | 1.91 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 78.40 | 51.48 | 30.10 | 214.51 | 116.97 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 54.66 | 32.93 | 21.73 | 119.19 | 97.18 | 0.00 | 0.00 | 744.00 |
February | 52.73 | 29.32 | 23.41 | 126.87 | 79.69 | 0.00 | 0.00 | 672.00 |
March | 46.63 | 21.50 | 25.14 | 132.86 | 49.61 | 0.00 | 0.00 | 744.00 |
April | 34.08 | 11.38 | 22.70 | 130.73 | 20.25 | 0.00 | 0.00 | 720.00 |
May | 23.73 | 2.67 | 21.06 | 121.33 | 5.41 | 0.00 | 0.00 | 744.00 |
June | 21.10 | 0.65 | 20.45 | 120.26 | 4.91 | 0.00 | 0.00 | 720.00 |
July | 21.90 | 0.50 | 21.40 | 108.89 | 1.73 | 0.00 | 0.00 | 744.00 |
August | 23.45 | 1.66 | 21.79 | 103.08 | 4.30 | 0.00 | 0.00 | 744.00 |
September | 31.86 | 9.01 | 22.85 | 114.65 | 12.54 | 0.00 | 0.00 | 720.00 |
October | 53.73 | 30.28 | 23.45 | 172.90 | 40.50 | 0.00 | 0.00 | 744.00 |
November | 65.48 | 43.00 | 22.48 | 180.73 | 71.18 | 0.00 | 0.00 | 720.00 |
December | 58.16 | 36.06 | 22.10 | 134.21 | 96.44 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 40.55 | 18.18 | 22.37 | 130.44 | 40.13 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 21.10 | 0.50 | 20.45 | 103.08 | 1.73 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 65.48 | 43.00 | 25.14 | 180.73 | 97.18 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 54.66 | 32.93 | 21.73 | 119.19 | 97.18 | 0.00 | 0.00 | 744.00 |
February | 52.73 | 29.32 | 23.41 | 126.87 | 79.69 | 0.00 | 0.00 | 672.00 |
March | 46.63 | 21.50 | 25.14 | 132.86 | 49.61 | 0.00 | 0.00 | 744.00 |
April | 34.08 | 11.38 | 22.70 | 130.73 | 20.25 | 0.00 | 0.00 | 720.00 |
May | 23.73 | 2.67 | 21.06 | 121.33 | 5.41 | 0.00 | 0.00 | 744.00 |
June | 21.10 | 0.65 | 20.45 | 120.26 | 4.91 | 0.00 | 0.00 | 720.00 |
July | 21.90 | 0.50 | 21.40 | 108.89 | 1.73 | 0.00 | 0.00 | 744.00 |
August | 23.45 | 1.66 | 21.79 | 103.08 | 4.30 | 0.00 | 0.00 | 744.00 |
September | 31.86 | 9.01 | 22.85 | 114.65 | 12.54 | 0.00 | 0.00 | 720.00 |
October | 53.73 | 30.28 | 23.45 | 172.90 | 40.50 | 0.00 | 0.00 | 744.00 |
November | 65.48 | 43.00 | 22.48 | 180.73 | 71.18 | 0.00 | 0.00 | 720.00 |
December | 58.16 | 36.06 | 22.10 | 134.21 | 96.44 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 40.55 | 18.18 | 22.37 | 130.44 | 40.13 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 21.10 | 0.50 | 20.45 | 103.08 | 1.73 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 65.48 | 43.00 | 25.14 | 180.73 | 97.18 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_DOOR
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 65.44 | 39.42 | 26.02 | 142.01 | 114.73 | 0.00 | 0.00 | 744.00 |
February | 63.14 | 35.11 | 28.03 | 151.06 | 94.05 | 0.00 | 0.00 | 672.00 |
March | 55.84 | 25.74 | 30.10 | 157.82 | 58.67 | 0.00 | 0.00 | 744.00 |
April | 40.81 | 13.63 | 27.18 | 154.83 | 23.99 | 0.00 | 0.00 | 720.00 |
May | 28.41 | 3.19 | 25.22 | 143.27 | 6.44 | 0.00 | 0.00 | 744.00 |
June | 25.26 | 0.77 | 24.49 | 141.97 | 5.78 | 0.00 | 0.00 | 720.00 |
July | 26.22 | 0.59 | 25.63 | 128.67 | 2.06 | 0.00 | 0.00 | 744.00 |
August | 28.08 | 1.99 | 26.09 | 121.96 | 5.11 | 0.00 | 0.00 | 744.00 |
September | 38.15 | 10.79 | 27.36 | 135.81 | 14.87 | 0.00 | 0.00 | 720.00 |
October | 64.33 | 36.26 | 28.07 | 205.07 | 47.99 | 0.00 | 0.00 | 744.00 |
November | 78.40 | 51.48 | 26.92 | 214.70 | 84.20 | 0.00 | 0.00 | 720.00 |
December | 69.64 | 43.18 | 26.46 | 159.75 | 113.88 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 48.56 | 21.77 | 26.79 | 154.69 | 47.44 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 25.26 | 0.59 | 24.49 | 121.96 | 2.06 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 78.40 | 51.48 | 30.10 | 214.70 | 114.73 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 54.66 | 32.93 | 21.73 | 119.67 | 95.94 | 0.00 | 0.00 | 744.00 |
February | 52.73 | 29.32 | 23.41 | 127.17 | 78.87 | 0.00 | 0.00 | 672.00 |
March | 46.63 | 21.50 | 25.14 | 133.03 | 49.04 | 0.00 | 0.00 | 744.00 |
April | 34.08 | 11.38 | 22.70 | 130.90 | 19.86 | 0.00 | 0.00 | 720.00 |
May | 23.73 | 2.67 | 21.06 | 121.56 | 5.20 | 0.00 | 0.00 | 744.00 |
June | 21.10 | 0.65 | 20.45 | 120.59 | 4.77 | 0.00 | 0.00 | 720.00 |
July | 21.90 | 0.50 | 21.40 | 109.12 | 1.60 | 0.00 | 0.00 | 744.00 |
August | 23.45 | 1.66 | 21.79 | 103.30 | 4.09 | 0.00 | 0.00 | 744.00 |
September | 31.86 | 9.01 | 22.85 | 114.75 | 12.15 | 0.00 | 0.00 | 720.00 |
October | 53.73 | 30.28 | 23.45 | 172.99 | 40.09 | 0.00 | 0.00 | 744.00 |
November | 65.48 | 43.00 | 22.48 | 180.91 | 70.63 | 0.00 | 0.00 | 720.00 |
December | 58.16 | 36.06 | 22.10 | 134.57 | 95.59 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 40.55 | 18.18 | 22.37 | 130.67 | 39.64 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 21.10 | 0.50 | 20.45 | 103.30 | 1.60 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 65.48 | 43.00 | 25.14 | 180.91 | 95.94 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 54.66 | 32.93 | 21.73 | 119.67 | 95.94 | 0.00 | 0.00 | 744.00 |
February | 52.73 | 29.32 | 23.41 | 127.17 | 78.87 | 0.00 | 0.00 | 672.00 |
March | 46.63 | 21.50 | 25.14 | 133.03 | 49.04 | 0.00 | 0.00 | 744.00 |
April | 34.08 | 11.38 | 22.70 | 130.90 | 19.86 | 0.00 | 0.00 | 720.00 |
May | 23.73 | 2.67 | 21.06 | 121.56 | 5.20 | 0.00 | 0.00 | 744.00 |
June | 21.10 | 0.65 | 20.45 | 120.59 | 4.77 | 0.00 | 0.00 | 720.00 |
July | 21.90 | 0.50 | 21.40 | 109.12 | 1.60 | 0.00 | 0.00 | 744.00 |
August | 23.45 | 1.66 | 21.79 | 103.30 | 4.09 | 0.00 | 0.00 | 744.00 |
September | 31.86 | 9.01 | 22.85 | 114.75 | 12.15 | 0.00 | 0.00 | 720.00 |
October | 53.73 | 30.28 | 23.45 | 172.99 | 40.09 | 0.00 | 0.00 | 744.00 |
November | 65.48 | 43.00 | 22.48 | 180.91 | 70.63 | 0.00 | 0.00 | 720.00 |
December | 58.16 | 36.06 | 22.10 | 134.57 | 95.59 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 40.55 | 18.18 | 22.37 | 130.67 | 39.64 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 21.10 | 0.50 | 20.45 | 103.30 | 1.60 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 65.48 | 43.00 | 25.14 | 180.91 | 95.94 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_DOOR
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 65.44 | 39.42 | 26.02 | 142.58 | 113.28 | 0.00 | 0.00 | 744.00 |
February | 63.14 | 35.11 | 28.03 | 151.41 | 93.09 | 0.00 | 0.00 | 672.00 |
March | 55.84 | 25.74 | 30.10 | 158.02 | 58.00 | 0.00 | 0.00 | 744.00 |
April | 40.81 | 13.63 | 27.18 | 155.03 | 23.54 | 0.00 | 0.00 | 720.00 |
May | 28.41 | 3.19 | 25.22 | 143.53 | 6.21 | 0.00 | 0.00 | 744.00 |
June | 25.26 | 0.77 | 24.49 | 142.36 | 5.63 | 0.00 | 0.00 | 720.00 |
July | 26.22 | 0.59 | 25.63 | 128.94 | 1.92 | 0.00 | 0.00 | 744.00 |
August | 28.08 | 1.99 | 26.09 | 122.21 | 4.86 | 0.00 | 0.00 | 744.00 |
September | 38.15 | 10.79 | 27.36 | 135.93 | 14.41 | 0.00 | 0.00 | 720.00 |
October | 64.33 | 36.26 | 28.07 | 205.18 | 47.50 | 0.00 | 0.00 | 744.00 |
November | 78.40 | 51.48 | 26.92 | 214.92 | 83.55 | 0.00 | 0.00 | 720.00 |
December | 69.64 | 43.18 | 26.46 | 160.18 | 112.88 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 48.56 | 21.77 | 26.79 | 154.98 | 46.86 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 25.26 | 0.59 | 24.49 | 122.21 | 1.92 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 78.40 | 51.48 | 30.10 | 214.92 | 113.28 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 54.66 | 32.93 | 21.73 | 121.40 | 93.41 | 0.00 | 0.00 | 744.00 |
February | 52.73 | 29.32 | 23.41 | 128.55 | 76.82 | 0.17 | 0.00 | 672.00 |
March | 46.63 | 21.50 | 25.14 | 133.91 | 47.21 | 0.00 | 0.00 | 744.00 |
April | 34.08 | 11.38 | 22.70 | 131.54 | 18.64 | 0.00 | 0.00 | 720.00 |
May | 23.73 | 2.67 | 21.06 | 121.95 | 4.64 | 0.00 | 0.00 | 744.00 |
June | 21.10 | 0.65 | 20.45 | 121.34 | 4.45 | 0.00 | 0.00 | 720.00 |
July | 21.90 | 0.50 | 21.40 | 109.29 | 1.26 | 0.00 | 0.00 | 744.00 |
August | 23.45 | 1.66 | 21.79 | 103.72 | 3.45 | 0.00 | 0.00 | 744.00 |
September | 31.86 | 9.01 | 22.85 | 114.99 | 11.05 | 0.00 | 0.00 | 720.00 |
October | 53.73 | 30.28 | 23.45 | 173.35 | 38.74 | 0.00 | 0.00 | 744.00 |
November | 65.48 | 43.00 | 22.48 | 181.80 | 69.11 | 0.00 | 0.00 | 720.00 |
December | 58.16 | 36.06 | 22.10 | 136.00 | 93.74 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 40.55 | 18.18 | 22.37 | 131.45 | 38.37 | 0.17 | 0.00 | 8760.00 |
Minimum of Months | 21.10 | 0.50 | 20.45 | 103.72 | 1.26 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 65.48 | 43.00 | 25.14 | 181.80 | 93.74 | 0.17 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 54.66 | 32.93 | 21.73 | 121.40 | 93.41 | 0.00 | 0.00 | 744.00 |
February | 52.73 | 29.32 | 23.41 | 128.55 | 76.82 | 0.17 | 0.00 | 672.00 |
March | 46.63 | 21.50 | 25.14 | 133.91 | 47.21 | 0.00 | 0.00 | 744.00 |
April | 34.08 | 11.38 | 22.70 | 131.54 | 18.64 | 0.00 | 0.00 | 720.00 |
May | 23.73 | 2.67 | 21.06 | 121.95 | 4.64 | 0.00 | 0.00 | 744.00 |
June | 21.10 | 0.65 | 20.45 | 121.34 | 4.45 | 0.00 | 0.00 | 720.00 |
July | 21.90 | 0.50 | 21.40 | 109.29 | 1.26 | 0.00 | 0.00 | 744.00 |
August | 23.45 | 1.66 | 21.79 | 103.72 | 3.45 | 0.00 | 0.00 | 744.00 |
September | 31.86 | 9.01 | 22.85 | 114.99 | 11.05 | 0.00 | 0.00 | 720.00 |
October | 53.73 | 30.28 | 23.45 | 173.35 | 38.74 | 0.00 | 0.00 | 744.00 |
November | 65.48 | 43.00 | 22.48 | 181.80 | 69.11 | 0.00 | 0.00 | 720.00 |
December | 58.16 | 36.06 | 22.10 | 136.00 | 93.74 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 40.55 | 18.18 | 22.37 | 131.45 | 38.37 | 0.17 | 0.00 | 8760.00 |
Minimum of Months | 21.10 | 0.50 | 20.45 | 103.72 | 1.26 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 65.48 | 43.00 | 25.14 | 181.80 | 93.74 | 0.17 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_3
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 54.66 | 32.93 | 21.73 | 121.40 | 93.41 | 0.00 | 0.00 | 744.00 |
February | 52.73 | 29.32 | 23.41 | 128.55 | 76.82 | 0.17 | 0.00 | 672.00 |
March | 46.63 | 21.50 | 25.14 | 133.91 | 47.21 | 0.00 | 0.00 | 744.00 |
April | 34.08 | 11.38 | 22.70 | 131.54 | 18.64 | 0.00 | 0.00 | 720.00 |
May | 23.73 | 2.67 | 21.06 | 121.95 | 4.64 | 0.00 | 0.00 | 744.00 |
June | 21.10 | 0.65 | 20.45 | 121.34 | 4.45 | 0.00 | 0.00 | 720.00 |
July | 21.90 | 0.50 | 21.40 | 109.29 | 1.26 | 0.00 | 0.00 | 744.00 |
August | 23.45 | 1.66 | 21.79 | 103.72 | 3.45 | 0.00 | 0.00 | 744.00 |
September | 31.86 | 9.01 | 22.85 | 114.99 | 11.05 | 0.00 | 0.00 | 720.00 |
October | 53.73 | 30.28 | 23.45 | 173.35 | 38.74 | 0.00 | 0.00 | 744.00 |
November | 65.48 | 43.00 | 22.48 | 181.80 | 69.11 | 0.00 | 0.00 | 720.00 |
December | 58.16 | 36.06 | 22.10 | 136.00 | 93.74 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 40.55 | 18.18 | 22.37 | 131.45 | 38.37 | 0.17 | 0.00 | 8760.00 |
Minimum of Months | 21.10 | 0.50 | 20.45 | 103.72 | 1.26 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 65.48 | 43.00 | 25.14 | 181.80 | 93.74 | 0.17 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_4
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 54.66 | 32.93 | 21.73 | 121.40 | 93.41 | 0.00 | 0.00 | 744.00 |
February | 52.73 | 29.32 | 23.41 | 128.55 | 76.82 | 0.17 | 0.00 | 672.00 |
March | 46.63 | 21.50 | 25.14 | 133.91 | 47.21 | 0.00 | 0.00 | 744.00 |
April | 34.08 | 11.38 | 22.70 | 131.54 | 18.64 | 0.00 | 0.00 | 720.00 |
May | 23.73 | 2.67 | 21.06 | 121.95 | 4.64 | 0.00 | 0.00 | 744.00 |
June | 21.10 | 0.65 | 20.45 | 121.34 | 4.45 | 0.00 | 0.00 | 720.00 |
July | 21.90 | 0.50 | 21.40 | 109.29 | 1.26 | 0.00 | 0.00 | 744.00 |
August | 23.45 | 1.66 | 21.79 | 103.72 | 3.45 | 0.00 | 0.00 | 744.00 |
September | 31.86 | 9.01 | 22.85 | 114.99 | 11.05 | 0.00 | 0.00 | 720.00 |
October | 53.73 | 30.28 | 23.45 | 173.35 | 38.74 | 0.00 | 0.00 | 744.00 |
November | 65.48 | 43.00 | 22.48 | 181.80 | 69.11 | 0.00 | 0.00 | 720.00 |
December | 58.16 | 36.06 | 22.10 | 136.00 | 93.74 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 40.55 | 18.18 | 22.37 | 131.45 | 38.37 | 0.17 | 0.00 | 8760.00 |
Minimum of Months | 21.10 | 0.50 | 20.45 | 103.72 | 1.26 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 65.48 | 43.00 | 25.14 | 181.80 | 93.74 | 0.17 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_DOOR_1
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 65.44 | 39.42 | 26.02 | 144.59 | 110.31 | 0.00 | 0.00 | 744.00 |
February | 63.14 | 35.11 | 28.03 | 153.00 | 90.69 | 0.17 | 0.00 | 672.00 |
March | 55.84 | 25.74 | 30.10 | 159.05 | 55.86 | 0.00 | 0.00 | 744.00 |
April | 40.81 | 13.63 | 27.18 | 155.79 | 22.09 | 0.00 | 0.00 | 720.00 |
May | 28.41 | 3.19 | 25.22 | 144.02 | 5.53 | 0.00 | 0.00 | 744.00 |
June | 25.26 | 0.77 | 24.49 | 143.26 | 5.24 | 0.00 | 0.00 | 720.00 |
July | 26.22 | 0.59 | 25.63 | 129.15 | 1.50 | 0.00 | 0.00 | 744.00 |
August | 28.08 | 1.99 | 26.09 | 122.71 | 4.11 | 0.00 | 0.00 | 744.00 |
September | 38.15 | 10.79 | 27.36 | 136.20 | 13.10 | 0.00 | 0.00 | 720.00 |
October | 64.33 | 36.26 | 28.07 | 205.59 | 45.91 | 0.00 | 0.00 | 744.00 |
November | 78.40 | 51.48 | 26.92 | 215.95 | 81.77 | 0.00 | 0.00 | 720.00 |
December | 69.64 | 43.18 | 26.46 | 161.84 | 110.71 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 48.56 | 21.77 | 26.79 | 155.88 | 45.36 | 0.17 | 0.00 | 8760.00 |
Minimum of Months | 25.26 | 0.59 | 24.49 | 122.71 | 1.50 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 78.40 | 51.48 | 30.10 | 215.95 | 110.71 | 0.17 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_DOOR_2
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 65.44 | 39.42 | 26.02 | 144.59 | 110.31 | 0.00 | 0.00 | 744.00 |
February | 63.14 | 35.11 | 28.03 | 153.00 | 90.69 | 0.17 | 0.00 | 672.00 |
March | 55.84 | 25.74 | 30.10 | 159.05 | 55.86 | 0.00 | 0.00 | 744.00 |
April | 40.81 | 13.63 | 27.18 | 155.79 | 22.09 | 0.00 | 0.00 | 720.00 |
May | 28.41 | 3.19 | 25.22 | 144.02 | 5.53 | 0.00 | 0.00 | 744.00 |
June | 25.26 | 0.77 | 24.49 | 143.26 | 5.24 | 0.00 | 0.00 | 720.00 |
July | 26.22 | 0.59 | 25.63 | 129.15 | 1.50 | 0.00 | 0.00 | 744.00 |
August | 28.08 | 1.99 | 26.09 | 122.71 | 4.11 | 0.00 | 0.00 | 744.00 |
September | 38.15 | 10.79 | 27.36 | 136.20 | 13.10 | 0.00 | 0.00 | 720.00 |
October | 64.33 | 36.26 | 28.07 | 205.59 | 45.91 | 0.00 | 0.00 | 744.00 |
November | 78.40 | 51.48 | 26.92 | 215.95 | 81.77 | 0.00 | 0.00 | 720.00 |
December | 69.64 | 43.18 | 26.46 | 161.84 | 110.71 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 48.56 | 21.77 | 26.79 | 155.88 | 45.36 | 0.17 | 0.00 | 8760.00 |
Minimum of Months | 25.26 | 0.59 | 24.49 | 122.71 | 1.50 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 78.40 | 51.48 | 30.10 | 215.95 | 110.71 | 0.17 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 54.66 | 32.93 | 21.73 | 121.04 | 93.32 | 0.00 | 0.00 | 744.00 |
February | 52.73 | 29.32 | 23.41 | 128.17 | 76.67 | 0.17 | 0.00 | 672.00 |
March | 46.63 | 21.50 | 25.14 | 133.91 | 46.71 | 0.00 | 0.00 | 744.00 |
April | 34.08 | 11.38 | 22.70 | 132.28 | 18.05 | 0.00 | 0.00 | 720.00 |
May | 23.73 | 2.67 | 21.06 | 123.57 | 4.24 | 0.00 | 0.00 | 744.00 |
June | 21.10 | 0.65 | 20.45 | 123.23 | 4.17 | 0.00 | 0.00 | 720.00 |
July | 21.90 | 0.50 | 21.40 | 110.93 | 1.05 | 0.00 | 0.00 | 744.00 |
August | 23.45 | 1.66 | 21.79 | 104.91 | 3.07 | 0.00 | 0.00 | 744.00 |
September | 31.86 | 9.01 | 22.85 | 115.64 | 10.32 | 0.00 | 0.00 | 720.00 |
October | 53.73 | 30.28 | 23.45 | 173.54 | 38.04 | 0.00 | 0.00 | 744.00 |
November | 65.48 | 43.00 | 22.48 | 181.61 | 68.65 | 0.00 | 0.00 | 720.00 |
December | 58.16 | 36.06 | 22.10 | 135.68 | 93.64 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 40.55 | 18.18 | 22.37 | 132.01 | 37.99 | 0.17 | 0.00 | 8760.00 |
Minimum of Months | 21.10 | 0.50 | 20.45 | 104.91 | 1.05 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 65.48 | 43.00 | 25.14 | 181.61 | 93.64 | 0.17 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 54.66 | 32.93 | 21.73 | 121.04 | 93.32 | 0.00 | 0.00 | 744.00 |
February | 52.73 | 29.32 | 23.41 | 128.17 | 76.67 | 0.17 | 0.00 | 672.00 |
March | 46.63 | 21.50 | 25.14 | 133.91 | 46.71 | 0.00 | 0.00 | 744.00 |
April | 34.08 | 11.38 | 22.70 | 132.28 | 18.05 | 0.00 | 0.00 | 720.00 |
May | 23.73 | 2.67 | 21.06 | 123.57 | 4.24 | 0.00 | 0.00 | 744.00 |
June | 21.10 | 0.65 | 20.45 | 123.23 | 4.17 | 0.00 | 0.00 | 720.00 |
July | 21.90 | 0.50 | 21.40 | 110.93 | 1.05 | 0.00 | 0.00 | 744.00 |
August | 23.45 | 1.66 | 21.79 | 104.91 | 3.07 | 0.00 | 0.00 | 744.00 |
September | 31.86 | 9.01 | 22.85 | 115.64 | 10.32 | 0.00 | 0.00 | 720.00 |
October | 53.73 | 30.28 | 23.45 | 173.54 | 38.04 | 0.00 | 0.00 | 744.00 |
November | 65.48 | 43.00 | 22.48 | 181.61 | 68.65 | 0.00 | 0.00 | 720.00 |
December | 58.16 | 36.06 | 22.10 | 135.68 | 93.64 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 40.55 | 18.18 | 22.37 | 132.01 | 37.99 | 0.17 | 0.00 | 8760.00 |
Minimum of Months | 21.10 | 0.50 | 20.45 | 104.91 | 1.05 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 65.48 | 43.00 | 25.14 | 181.61 | 93.64 | 0.17 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_DOOR
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 65.44 | 39.42 | 26.02 | 144.23 | 110.18 | 0.00 | 0.00 | 744.00 |
February | 63.14 | 35.11 | 28.03 | 152.62 | 90.48 | 0.17 | 0.00 | 672.00 |
March | 55.84 | 25.74 | 30.10 | 159.09 | 55.26 | 0.00 | 0.00 | 744.00 |
April | 40.81 | 13.63 | 27.18 | 156.69 | 21.39 | 0.00 | 0.00 | 720.00 |
May | 28.41 | 3.19 | 25.22 | 145.92 | 5.06 | 0.00 | 0.00 | 744.00 |
June | 25.26 | 0.77 | 24.49 | 145.49 | 4.91 | 0.00 | 0.00 | 720.00 |
July | 26.22 | 0.59 | 25.63 | 131.09 | 1.26 | 0.00 | 0.00 | 744.00 |
August | 28.08 | 1.99 | 26.09 | 124.14 | 3.65 | 0.00 | 0.00 | 744.00 |
September | 38.15 | 10.79 | 27.36 | 137.01 | 12.24 | 0.00 | 0.00 | 720.00 |
October | 64.33 | 36.26 | 28.07 | 205.87 | 45.08 | 0.00 | 0.00 | 744.00 |
November | 78.40 | 51.48 | 26.92 | 215.78 | 81.22 | 0.00 | 0.00 | 720.00 |
December | 69.64 | 43.18 | 26.46 | 161.52 | 110.58 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 48.56 | 21.77 | 26.79 | 156.58 | 44.90 | 0.17 | 0.00 | 8760.00 |
Minimum of Months | 25.26 | 0.59 | 24.49 | 124.14 | 1.26 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 78.40 | 51.48 | 30.10 | 215.78 | 110.58 | 0.17 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 54.66 | 32.93 | 21.73 | 121.24 | 92.87 | 0.00 | 0.00 | 744.00 |
February | 52.73 | 29.32 | 23.41 | 128.34 | 76.31 | 0.17 | 0.00 | 672.00 |
March | 46.63 | 21.50 | 25.14 | 134.03 | 46.45 | 0.00 | 0.00 | 744.00 |
April | 34.08 | 11.38 | 22.70 | 132.42 | 17.89 | 0.00 | 0.00 | 720.00 |
May | 23.73 | 2.67 | 21.06 | 123.77 | 4.16 | 0.00 | 0.00 | 744.00 |
June | 21.10 | 0.65 | 20.45 | 123.46 | 4.11 | 0.00 | 0.00 | 720.00 |
July | 21.90 | 0.50 | 21.40 | 111.14 | 1.02 | 0.00 | 0.00 | 744.00 |
August | 23.45 | 1.66 | 21.79 | 105.08 | 3.00 | 0.00 | 0.00 | 744.00 |
September | 31.86 | 9.01 | 22.85 | 115.76 | 10.18 | 0.00 | 0.00 | 720.00 |
October | 53.73 | 30.28 | 23.45 | 173.63 | 37.87 | 0.00 | 0.00 | 744.00 |
November | 65.48 | 43.00 | 22.48 | 181.72 | 68.43 | 0.00 | 0.00 | 720.00 |
December | 58.16 | 36.06 | 22.10 | 135.86 | 93.31 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 40.55 | 18.18 | 22.37 | 132.17 | 37.79 | 0.17 | 0.00 | 8760.00 |
Minimum of Months | 21.10 | 0.50 | 20.45 | 105.08 | 1.02 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 65.48 | 43.00 | 25.14 | 181.72 | 93.31 | 0.17 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 54.66 | 32.93 | 21.73 | 121.24 | 92.87 | 0.00 | 0.00 | 744.00 |
February | 52.73 | 29.32 | 23.41 | 128.34 | 76.31 | 0.17 | 0.00 | 672.00 |
March | 46.63 | 21.50 | 25.14 | 134.03 | 46.45 | 0.00 | 0.00 | 744.00 |
April | 34.08 | 11.38 | 22.70 | 132.42 | 17.89 | 0.00 | 0.00 | 720.00 |
May | 23.73 | 2.67 | 21.06 | 123.77 | 4.16 | 0.00 | 0.00 | 744.00 |
June | 21.10 | 0.65 | 20.45 | 123.46 | 4.11 | 0.00 | 0.00 | 720.00 |
July | 21.90 | 0.50 | 21.40 | 111.14 | 1.02 | 0.00 | 0.00 | 744.00 |
August | 23.45 | 1.66 | 21.79 | 105.08 | 3.00 | 0.00 | 0.00 | 744.00 |
September | 31.86 | 9.01 | 22.85 | 115.76 | 10.18 | 0.00 | 0.00 | 720.00 |
October | 53.73 | 30.28 | 23.45 | 173.63 | 37.87 | 0.00 | 0.00 | 744.00 |
November | 65.48 | 43.00 | 22.48 | 181.72 | 68.43 | 0.00 | 0.00 | 720.00 |
December | 58.16 | 36.06 | 22.10 | 135.86 | 93.31 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 40.55 | 18.18 | 22.37 | 132.17 | 37.79 | 0.17 | 0.00 | 8760.00 |
Minimum of Months | 21.10 | 0.50 | 20.45 | 105.08 | 1.02 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 65.48 | 43.00 | 25.14 | 181.72 | 93.31 | 0.17 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_DOOR
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 65.44 | 39.42 | 26.02 | 144.47 | 109.64 | 0.00 | 0.00 | 744.00 |
February | 63.14 | 35.11 | 28.03 | 152.83 | 90.06 | 0.17 | 0.00 | 672.00 |
March | 55.84 | 25.74 | 30.10 | 159.24 | 54.95 | 0.00 | 0.00 | 744.00 |
April | 40.81 | 13.63 | 27.18 | 156.86 | 21.20 | 0.00 | 0.00 | 720.00 |
May | 28.41 | 3.19 | 25.22 | 146.16 | 4.96 | 0.00 | 0.00 | 744.00 |
June | 25.26 | 0.77 | 24.49 | 145.76 | 4.84 | 0.00 | 0.00 | 720.00 |
July | 26.22 | 0.59 | 25.63 | 131.34 | 1.22 | 0.00 | 0.00 | 744.00 |
August | 28.08 | 1.99 | 26.09 | 124.34 | 3.57 | 0.00 | 0.00 | 744.00 |
September | 38.15 | 10.79 | 27.36 | 137.14 | 12.07 | 0.00 | 0.00 | 720.00 |
October | 64.33 | 36.26 | 28.07 | 205.97 | 44.87 | 0.00 | 0.00 | 744.00 |
November | 78.40 | 51.48 | 26.92 | 215.92 | 80.95 | 0.00 | 0.00 | 720.00 |
December | 69.64 | 43.18 | 26.46 | 161.74 | 110.19 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 48.56 | 21.77 | 26.79 | 156.77 | 44.67 | 0.17 | 0.00 | 8760.00 |
Minimum of Months | 25.26 | 0.59 | 24.49 | 124.34 | 1.22 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 78.40 | 51.48 | 30.10 | 215.92 | 110.19 | 0.17 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 54.66 | 32.93 | 21.73 | 121.72 | 91.62 | 0.00 | 0.00 | 744.00 |
February | 52.73 | 29.32 | 23.41 | 128.76 | 75.26 | 0.33 | 0.00 | 672.00 |
March | 46.63 | 21.50 | 25.14 | 134.23 | 45.87 | 0.00 | 0.00 | 744.00 |
April | 34.08 | 11.38 | 22.70 | 132.44 | 17.71 | 0.00 | 0.00 | 720.00 |
May | 23.73 | 2.67 | 21.06 | 123.61 | 4.17 | 0.00 | 0.00 | 744.00 |
June | 21.10 | 0.65 | 20.45 | 123.20 | 4.12 | 0.00 | 0.00 | 720.00 |
July | 21.90 | 0.50 | 21.40 | 110.77 | 1.04 | 0.00 | 0.00 | 744.00 |
August | 23.45 | 1.66 | 21.79 | 104.79 | 3.08 | 0.00 | 0.00 | 744.00 |
September | 31.86 | 9.01 | 22.85 | 115.61 | 10.30 | 0.00 | 0.00 | 720.00 |
October | 53.73 | 30.28 | 23.45 | 173.60 | 37.83 | 0.00 | 0.00 | 744.00 |
November | 65.48 | 43.00 | 22.48 | 181.88 | 68.02 | 0.00 | 0.00 | 720.00 |
December | 58.16 | 36.06 | 22.10 | 136.30 | 92.38 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 40.55 | 18.18 | 22.37 | 132.20 | 37.44 | 0.33 | 0.00 | 8760.00 |
Minimum of Months | 21.10 | 0.50 | 20.45 | 104.79 | 1.04 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 65.48 | 43.00 | 25.14 | 181.88 | 92.38 | 0.33 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 54.66 | 32.93 | 21.73 | 121.72 | 91.62 | 0.00 | 0.00 | 744.00 |
February | 52.73 | 29.32 | 23.41 | 128.76 | 75.26 | 0.33 | 0.00 | 672.00 |
March | 46.63 | 21.50 | 25.14 | 134.23 | 45.87 | 0.00 | 0.00 | 744.00 |
April | 34.08 | 11.38 | 22.70 | 132.44 | 17.71 | 0.00 | 0.00 | 720.00 |
May | 23.73 | 2.67 | 21.06 | 123.61 | 4.17 | 0.00 | 0.00 | 744.00 |
June | 21.10 | 0.65 | 20.45 | 123.20 | 4.12 | 0.00 | 0.00 | 720.00 |
July | 21.90 | 0.50 | 21.40 | 110.77 | 1.04 | 0.00 | 0.00 | 744.00 |
August | 23.45 | 1.66 | 21.79 | 104.79 | 3.08 | 0.00 | 0.00 | 744.00 |
September | 31.86 | 9.01 | 22.85 | 115.61 | 10.30 | 0.00 | 0.00 | 720.00 |
October | 53.73 | 30.28 | 23.45 | 173.60 | 37.83 | 0.00 | 0.00 | 744.00 |
November | 65.48 | 43.00 | 22.48 | 181.88 | 68.02 | 0.00 | 0.00 | 720.00 |
December | 58.16 | 36.06 | 22.10 | 136.30 | 92.38 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 40.55 | 18.18 | 22.37 | 132.20 | 37.44 | 0.33 | 0.00 | 8760.00 |
Minimum of Months | 21.10 | 0.50 | 20.45 | 104.79 | 1.04 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 65.48 | 43.00 | 25.14 | 181.88 | 92.38 | 0.33 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_DOOR
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 65.44 | 39.42 | 26.02 | 145.04 | 108.17 | 0.00 | 0.00 | 744.00 |
February | 63.14 | 35.11 | 28.03 | 153.33 | 88.83 | 0.33 | 0.00 | 672.00 |
March | 55.84 | 25.74 | 30.10 | 159.49 | 54.27 | 0.00 | 0.00 | 744.00 |
April | 40.81 | 13.63 | 27.18 | 156.88 | 20.99 | 0.00 | 0.00 | 720.00 |
May | 28.41 | 3.19 | 25.22 | 145.97 | 4.97 | 0.00 | 0.00 | 744.00 |
June | 25.26 | 0.77 | 24.49 | 145.44 | 4.85 | 0.00 | 0.00 | 720.00 |
July | 26.22 | 0.59 | 25.63 | 130.90 | 1.25 | 0.00 | 0.00 | 744.00 |
August | 28.08 | 1.99 | 26.09 | 123.99 | 3.66 | 0.00 | 0.00 | 744.00 |
September | 38.15 | 10.79 | 27.36 | 136.96 | 12.21 | 0.00 | 0.00 | 720.00 |
October | 64.33 | 36.26 | 28.07 | 205.93 | 44.83 | 0.00 | 0.00 | 744.00 |
November | 78.40 | 51.48 | 26.92 | 216.10 | 80.47 | 0.00 | 0.00 | 720.00 |
December | 69.64 | 43.18 | 26.46 | 162.26 | 109.08 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 48.56 | 21.77 | 26.79 | 156.81 | 44.27 | 0.33 | 0.00 | 8760.00 |
Minimum of Months | 25.26 | 0.59 | 24.49 | 123.99 | 1.25 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 78.40 | 51.48 | 30.10 | 216.10 | 109.08 | 0.33 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 54.66 | 32.93 | 21.73 | 122.58 | 87.42 | 0.00 | 0.00 | 744.00 |
February | 52.73 | 29.32 | 23.41 | 129.57 | 71.24 | 0.50 | 0.00 | 672.00 |
March | 46.63 | 21.50 | 25.14 | 134.31 | 43.47 | 0.00 | 0.00 | 744.00 |
April | 34.08 | 11.38 | 22.70 | 131.20 | 17.22 | 0.00 | 0.00 | 720.00 |
May | 23.73 | 2.67 | 21.06 | 121.11 | 4.44 | 0.00 | 0.00 | 744.00 |
June | 21.10 | 0.65 | 20.45 | 119.93 | 4.37 | 3.50 | 0.00 | 720.00 |
July | 21.90 | 0.50 | 21.40 | 107.09 | 1.37 | 0.00 | 0.00 | 744.00 |
August | 23.45 | 1.66 | 21.79 | 101.78 | 3.88 | 0.00 | 0.00 | 744.00 |
September | 31.86 | 9.01 | 22.85 | 113.69 | 11.69 | 0.00 | 0.00 | 720.00 |
October | 53.73 | 30.28 | 23.45 | 172.45 | 38.34 | 0.00 | 0.00 | 744.00 |
November | 65.48 | 43.00 | 22.48 | 181.76 | 66.63 | 0.00 | 0.00 | 720.00 |
December | 58.16 | 36.06 | 22.10 | 137.13 | 88.95 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 40.55 | 18.18 | 22.37 | 131.00 | 36.43 | 4.00 | 0.00 | 8760.00 |
Minimum of Months | 21.10 | 0.50 | 20.45 | 101.78 | 1.37 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 65.48 | 43.00 | 25.14 | 181.76 | 88.95 | 3.50 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 54.66 | 32.93 | 21.73 | 122.58 | 87.42 | 0.00 | 0.00 | 744.00 |
February | 52.73 | 29.32 | 23.41 | 129.57 | 71.24 | 0.50 | 0.00 | 672.00 |
March | 46.63 | 21.50 | 25.14 | 134.31 | 43.47 | 0.00 | 0.00 | 744.00 |
April | 34.08 | 11.38 | 22.70 | 131.20 | 17.22 | 0.00 | 0.00 | 720.00 |
May | 23.73 | 2.67 | 21.06 | 121.11 | 4.44 | 0.00 | 0.00 | 744.00 |
June | 21.10 | 0.65 | 20.45 | 119.93 | 4.37 | 3.50 | 0.00 | 720.00 |
July | 21.90 | 0.50 | 21.40 | 107.09 | 1.37 | 0.00 | 0.00 | 744.00 |
August | 23.45 | 1.66 | 21.79 | 101.78 | 3.88 | 0.00 | 0.00 | 744.00 |
September | 31.86 | 9.01 | 22.85 | 113.69 | 11.69 | 0.00 | 0.00 | 720.00 |
October | 53.73 | 30.28 | 23.45 | 172.45 | 38.34 | 0.00 | 0.00 | 744.00 |
November | 65.48 | 43.00 | 22.48 | 181.76 | 66.63 | 0.00 | 0.00 | 720.00 |
December | 58.16 | 36.06 | 22.10 | 137.13 | 88.95 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 40.55 | 18.18 | 22.37 | 131.00 | 36.43 | 4.00 | 0.00 | 8760.00 |
Minimum of Months | 21.10 | 0.50 | 20.45 | 101.78 | 1.37 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 65.48 | 43.00 | 25.14 | 181.76 | 88.95 | 3.50 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_DOOR
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 65.44 | 39.42 | 26.02 | 146.07 | 103.22 | 0.00 | 0.00 | 744.00 |
February | 63.14 | 35.11 | 28.03 | 154.29 | 84.10 | 0.50 | 0.00 | 672.00 |
March | 55.84 | 25.74 | 30.10 | 159.58 | 51.45 | 0.00 | 0.00 | 744.00 |
April | 40.81 | 13.63 | 27.18 | 155.39 | 20.41 | 0.00 | 0.00 | 720.00 |
May | 28.41 | 3.19 | 25.22 | 142.98 | 5.30 | 0.00 | 0.00 | 744.00 |
June | 25.26 | 0.77 | 24.49 | 141.54 | 5.14 | 3.50 | 0.00 | 720.00 |
July | 26.22 | 0.59 | 25.63 | 126.52 | 1.65 | 0.00 | 0.00 | 744.00 |
August | 28.08 | 1.99 | 26.09 | 120.38 | 4.62 | 0.00 | 0.00 | 744.00 |
September | 38.15 | 10.79 | 27.36 | 134.66 | 13.86 | 0.00 | 0.00 | 720.00 |
October | 64.33 | 36.26 | 28.07 | 204.54 | 45.44 | 0.00 | 0.00 | 744.00 |
November | 78.40 | 51.48 | 26.92 | 215.95 | 78.83 | 0.00 | 0.00 | 720.00 |
December | 69.64 | 43.18 | 26.46 | 163.25 | 105.05 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 48.56 | 21.77 | 26.79 | 155.37 | 43.07 | 4.00 | 0.00 | 8760.00 |
Minimum of Months | 25.26 | 0.59 | 24.49 | 120.38 | 1.65 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 78.40 | 51.48 | 30.10 | 215.95 | 105.05 | 3.50 | 0.00 | 744.00 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.146391E+09 | 88187280.52 | 58204094.77 | 0.316684E+09 | 0.272915E+09 |
February | 0.127569E+09 | 70931396.48 | 56637649.59 | 0.306374E+09 | 0.195920E+09 |
March | 0.124907E+09 | 57575446.50 | 67331707.46 | 0.355900E+09 | 0.128521E+09 |
April | 88344968.40 | 29504458.70 | 58840509.70 | 0.342464E+09 | 46331771.37 |
May | 63549535.86 | 7141765.29 | 56407770.57 | 0.333706E+09 | 10757956.95 |
June | 54679175.71 | 1673297.37 | 53005878.34 | 0.320094E+09 | 9631093.51 |
July | 58654436.73 | 1328821.70 | 57325615.03 | 0.302507E+09 | 3221337.18 |
August | 62810368.98 | 4444991.25 | 58365377.73 | 0.280890E+09 | 8598421.40 |
September | 82592210.82 | 23362549.71 | 59229661.11 | 0.297845E+09 | 26831312.08 |
October | 0.143898E+09 | 81099637.29 | 62798147.36 | 0.462531E+09 | 0.101457E+09 |
November | 0.169719E+09 | 0.111444E+09 | 58274818.43 | 0.467529E+09 | 0.183941E+09 |
December | 0.155781E+09 | 96593536.03 | 59187848.61 | 0.357409E+09 | 0.266511E+09 |
Annual Sum or Average | 0.127890E+10 | 0.573287E+09 | 0.705609E+09 | 0.414393E+10 | 0.125464E+10 |
Minimum of Months | 54679175.71 | 1328821.70 | 53005878.34 | 0.280890E+09 | 3221337.18 |
Maximum of Months | 0.169719E+09 | 0.111444E+09 | 67331707.46 | 0.467529E+09 | 0.272915E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.146391E+09 | 88187280.52 | 58204094.77 | 0.316684E+09 | 0.272915E+09 |
February | 0.127569E+09 | 70931396.48 | 56637649.59 | 0.306374E+09 | 0.195920E+09 |
March | 0.124907E+09 | 57575446.50 | 67331707.46 | 0.355900E+09 | 0.128521E+09 |
April | 88344968.40 | 29504458.70 | 58840509.70 | 0.342464E+09 | 46331771.37 |
May | 63549535.86 | 7141765.29 | 56407770.57 | 0.333706E+09 | 10757956.95 |
June | 54679175.71 | 1673297.37 | 53005878.34 | 0.320094E+09 | 9631093.51 |
July | 58654436.73 | 1328821.70 | 57325615.03 | 0.302507E+09 | 3221337.18 |
August | 62810368.98 | 4444991.25 | 58365377.73 | 0.280890E+09 | 8598421.40 |
September | 82592210.82 | 23362549.71 | 59229661.11 | 0.297845E+09 | 26831312.08 |
October | 0.143898E+09 | 81099637.29 | 62798147.36 | 0.462531E+09 | 0.101457E+09 |
November | 0.169719E+09 | 0.111444E+09 | 58274818.43 | 0.467529E+09 | 0.183941E+09 |
December | 0.155781E+09 | 96593536.03 | 59187848.61 | 0.357409E+09 | 0.266511E+09 |
Annual Sum or Average | 0.127890E+10 | 0.573287E+09 | 0.705609E+09 | 0.414393E+10 | 0.125464E+10 |
Minimum of Months | 54679175.71 | 1328821.70 | 53005878.34 | 0.280890E+09 | 3221337.18 |
Maximum of Months | 0.169719E+09 | 0.111444E+09 | 67331707.46 | 0.467529E+09 | 0.272915E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_3
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.146391E+09 | 88187280.52 | 58204094.77 | 0.316684E+09 | 0.272915E+09 |
February | 0.127569E+09 | 70931396.48 | 56637649.59 | 0.306374E+09 | 0.195920E+09 |
March | 0.124907E+09 | 57575446.50 | 67331707.46 | 0.355900E+09 | 0.128521E+09 |
April | 88344968.40 | 29504458.70 | 58840509.70 | 0.342464E+09 | 46331771.37 |
May | 63549535.86 | 7141765.29 | 56407770.57 | 0.333706E+09 | 10757956.95 |
June | 54679175.71 | 1673297.37 | 53005878.34 | 0.320094E+09 | 9631093.51 |
July | 58654436.73 | 1328821.70 | 57325615.03 | 0.302507E+09 | 3221337.18 |
August | 62810368.98 | 4444991.25 | 58365377.73 | 0.280890E+09 | 8598421.40 |
September | 82592210.82 | 23362549.71 | 59229661.11 | 0.297845E+09 | 26831312.08 |
October | 0.143898E+09 | 81099637.29 | 62798147.36 | 0.462531E+09 | 0.101457E+09 |
November | 0.169719E+09 | 0.111444E+09 | 58274818.43 | 0.467529E+09 | 0.183941E+09 |
December | 0.155781E+09 | 96593536.03 | 59187848.61 | 0.357409E+09 | 0.266511E+09 |
Annual Sum or Average | 0.127890E+10 | 0.573287E+09 | 0.705609E+09 | 0.414393E+10 | 0.125464E+10 |
Minimum of Months | 54679175.71 | 1328821.70 | 53005878.34 | 0.280890E+09 | 3221337.18 |
Maximum of Months | 0.169719E+09 | 0.111444E+09 | 67331707.46 | 0.467529E+09 | 0.272915E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_4
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.146391E+09 | 88187280.52 | 58204094.77 | 0.316684E+09 | 0.272915E+09 |
February | 0.127569E+09 | 70931396.48 | 56637649.59 | 0.306374E+09 | 0.195920E+09 |
March | 0.124907E+09 | 57575446.50 | 67331707.46 | 0.355900E+09 | 0.128521E+09 |
April | 88344968.40 | 29504458.70 | 58840509.70 | 0.342464E+09 | 46331771.37 |
May | 63549535.86 | 7141765.29 | 56407770.57 | 0.333706E+09 | 10757956.95 |
June | 54679175.71 | 1673297.37 | 53005878.34 | 0.320094E+09 | 9631093.51 |
July | 58654436.73 | 1328821.70 | 57325615.03 | 0.302507E+09 | 3221337.18 |
August | 62810368.98 | 4444991.25 | 58365377.73 | 0.280890E+09 | 8598421.40 |
September | 82592210.82 | 23362549.71 | 59229661.11 | 0.297845E+09 | 26831312.08 |
October | 0.143898E+09 | 81099637.29 | 62798147.36 | 0.462531E+09 | 0.101457E+09 |
November | 0.169719E+09 | 0.111444E+09 | 58274818.43 | 0.467529E+09 | 0.183941E+09 |
December | 0.155781E+09 | 96593536.03 | 59187848.61 | 0.357409E+09 | 0.266511E+09 |
Annual Sum or Average | 0.127890E+10 | 0.573287E+09 | 0.705609E+09 | 0.414393E+10 | 0.125464E+10 |
Minimum of Months | 54679175.71 | 1328821.70 | 53005878.34 | 0.280890E+09 | 3221337.18 |
Maximum of Months | 0.169719E+09 | 0.111444E+09 | 67331707.46 | 0.467529E+09 | 0.272915E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_DOOR_1
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.176248E+09 | 0.106173E+09 | 70074666.73 | 0.379175E+09 | 0.324237E+09 |
February | 0.153586E+09 | 85397668.13 | 68188749.18 | 0.366563E+09 | 0.232763E+09 |
March | 0.150382E+09 | 69317807.30 | 81063832.00 | 0.424884E+09 | 0.153148E+09 |
April | 0.106363E+09 | 35521815.41 | 70840876.81 | 0.407443E+09 | 55350059.95 |
May | 76510296.46 | 8598309.52 | 67911986.94 | 0.395674E+09 | 12920586.32 |
June | 65830849.70 | 2014561.96 | 63816287.74 | 0.379442E+09 | 11499628.79 |
July | 70616854.75 | 1599831.39 | 69017023.36 | 0.358796E+09 | 3885061.77 |
August | 75620378.44 | 5351535.52 | 70268842.93 | 0.333637E+09 | 10353020.57 |
September | 99436674.87 | 28127280.24 | 71309394.63 | 0.354342E+09 | 32139389.83 |
October | 0.173245E+09 | 97639694.90 | 75605664.26 | 0.551372E+09 | 0.121182E+09 |
November | 0.204332E+09 | 0.134172E+09 | 70159814.30 | 0.558266E+09 | 0.219107E+09 |
December | 0.187553E+09 | 0.116294E+09 | 71259054.58 | 0.427555E+09 | 0.316716E+09 |
Annual Sum or Average | 0.153972E+10 | 0.690207E+09 | 0.849516E+09 | 0.493715E+10 | 0.149330E+10 |
Minimum of Months | 65830849.70 | 1599831.39 | 63816287.74 | 0.333637E+09 | 3885061.77 |
Maximum of Months | 0.204332E+09 | 0.134172E+09 | 81063832.00 | 0.558266E+09 | 0.324237E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_DOOR_2
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.176248E+09 | 0.106173E+09 | 70074666.73 | 0.379175E+09 | 0.324237E+09 |
February | 0.153586E+09 | 85397668.13 | 68188749.18 | 0.366563E+09 | 0.232763E+09 |
March | 0.150382E+09 | 69317807.30 | 81063832.00 | 0.424884E+09 | 0.153148E+09 |
April | 0.106363E+09 | 35521815.41 | 70840876.81 | 0.407443E+09 | 55350059.95 |
May | 76510296.46 | 8598309.52 | 67911986.94 | 0.395674E+09 | 12920586.32 |
June | 65830849.70 | 2014561.96 | 63816287.74 | 0.379442E+09 | 11499628.79 |
July | 70616854.75 | 1599831.39 | 69017023.36 | 0.358796E+09 | 3885061.77 |
August | 75620378.44 | 5351535.52 | 70268842.93 | 0.333637E+09 | 10353020.57 |
September | 99436674.87 | 28127280.24 | 71309394.63 | 0.354342E+09 | 32139389.83 |
October | 0.173245E+09 | 97639694.90 | 75605664.26 | 0.551372E+09 | 0.121182E+09 |
November | 0.204332E+09 | 0.134172E+09 | 70159814.30 | 0.558266E+09 | 0.219107E+09 |
December | 0.187553E+09 | 0.116294E+09 | 71259054.58 | 0.427555E+09 | 0.316716E+09 |
Annual Sum or Average | 0.153972E+10 | 0.690207E+09 | 0.849516E+09 | 0.493715E+10 | 0.149330E+10 |
Minimum of Months | 65830849.70 | 1599831.39 | 63816287.74 | 0.333637E+09 | 3885061.77 |
Maximum of Months | 0.204332E+09 | 0.134172E+09 | 81063832.00 | 0.558266E+09 | 0.324237E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.146391E+09 | 88187280.52 | 58204094.77 | 0.313772E+09 | 0.276895E+09 |
February | 0.127569E+09 | 70931396.48 | 56637649.59 | 0.304160E+09 | 0.198665E+09 |
March | 0.124907E+09 | 57575446.50 | 67331707.46 | 0.355262E+09 | 0.129621E+09 |
April | 88344968.40 | 29504458.70 | 58840509.70 | 0.345131E+09 | 45980297.83 |
May | 63549535.86 | 7141765.29 | 56407770.57 | 0.339798E+09 | 10009806.49 |
June | 54679175.71 | 1673297.37 | 53005878.34 | 0.327374E+09 | 8936055.38 |
July | 58654436.73 | 1328821.70 | 57325615.03 | 0.309884E+09 | 2668514.94 |
August | 62810368.98 | 4444991.25 | 58365377.73 | 0.286753E+09 | 7327424.95 |
September | 82592210.82 | 23362549.71 | 59229661.11 | 0.301730E+09 | 24487334.79 |
October | 0.143898E+09 | 81099637.29 | 62798147.36 | 0.464039E+09 | 99673700.55 |
November | 0.169719E+09 | 0.111444E+09 | 58274818.43 | 0.466853E+09 | 0.183740E+09 |
December | 0.155781E+09 | 96593536.03 | 59187848.61 | 0.355135E+09 | 0.268910E+09 |
Annual Sum or Average | 0.127890E+10 | 0.573287E+09 | 0.705609E+09 | 0.416989E+10 | 0.125691E+10 |
Minimum of Months | 54679175.71 | 1328821.70 | 53005878.34 | 0.286753E+09 | 2668514.94 |
Maximum of Months | 0.169719E+09 | 0.111444E+09 | 67331707.46 | 0.466853E+09 | 0.276895E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.146391E+09 | 88187280.52 | 58204094.77 | 0.313772E+09 | 0.276895E+09 |
February | 0.127569E+09 | 70931396.48 | 56637649.59 | 0.304160E+09 | 0.198665E+09 |
March | 0.124907E+09 | 57575446.50 | 67331707.46 | 0.355262E+09 | 0.129621E+09 |
April | 88344968.40 | 29504458.70 | 58840509.70 | 0.345131E+09 | 45980297.83 |
May | 63549535.86 | 7141765.29 | 56407770.57 | 0.339798E+09 | 10009806.49 |
June | 54679175.71 | 1673297.37 | 53005878.34 | 0.327374E+09 | 8936055.38 |
July | 58654436.73 | 1328821.70 | 57325615.03 | 0.309884E+09 | 2668514.94 |
August | 62810368.98 | 4444991.25 | 58365377.73 | 0.286753E+09 | 7327424.95 |
September | 82592210.82 | 23362549.71 | 59229661.11 | 0.301730E+09 | 24487334.79 |
October | 0.143898E+09 | 81099637.29 | 62798147.36 | 0.464039E+09 | 99673700.55 |
November | 0.169719E+09 | 0.111444E+09 | 58274818.43 | 0.466853E+09 | 0.183740E+09 |
December | 0.155781E+09 | 96593536.03 | 59187848.61 | 0.355135E+09 | 0.268910E+09 |
Annual Sum or Average | 0.127890E+10 | 0.573287E+09 | 0.705609E+09 | 0.416989E+10 | 0.125691E+10 |
Minimum of Months | 54679175.71 | 1328821.70 | 53005878.34 | 0.286753E+09 | 2668514.94 |
Maximum of Months | 0.169719E+09 | 0.111444E+09 | 67331707.46 | 0.466853E+09 | 0.276895E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_DOOR
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.176248E+09 | 0.106173E+09 | 70074666.73 | 0.375849E+09 | 0.328852E+09 |
February | 0.153586E+09 | 85397668.13 | 68188749.18 | 0.364060E+09 | 0.235921E+09 |
March | 0.150382E+09 | 69317807.30 | 81063832.00 | 0.424252E+09 | 0.154389E+09 |
April | 0.106363E+09 | 35521815.41 | 70840876.81 | 0.410724E+09 | 54906645.67 |
May | 76510296.46 | 8598309.52 | 67911986.94 | 0.402962E+09 | 12022975.80 |
June | 65830849.70 | 2014561.96 | 63816287.74 | 0.388169E+09 | 10665532.70 |
July | 70616854.75 | 1599831.39 | 69017023.36 | 0.367641E+09 | 3219922.56 |
August | 75620378.44 | 5351535.52 | 70268842.93 | 0.340740E+09 | 8820369.03 |
September | 99436674.87 | 28127280.24 | 71309394.63 | 0.359101E+09 | 29315017.76 |
October | 0.173245E+09 | 97639694.90 | 75605664.26 | 0.553317E+09 | 0.119008E+09 |
November | 0.204332E+09 | 0.134172E+09 | 70159814.30 | 0.557619E+09 | 0.218800E+09 |
December | 0.187553E+09 | 0.116294E+09 | 71259054.58 | 0.424989E+09 | 0.319467E+09 |
Annual Sum or Average | 0.153972E+10 | 0.690207E+09 | 0.849516E+09 | 0.496942E+10 | 0.149539E+10 |
Minimum of Months | 65830849.70 | 1599831.39 | 63816287.74 | 0.340740E+09 | 3219922.56 |
Maximum of Months | 0.204332E+09 | 0.134172E+09 | 81063832.00 | 0.557619E+09 | 0.328852E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.146391E+09 | 88187280.52 | 58204094.77 | 0.317632E+09 | 0.265349E+09 |
February | 0.127569E+09 | 70931396.48 | 56637649.59 | 0.306117E+09 | 0.195267E+09 |
March | 0.124907E+09 | 57575446.50 | 67331707.46 | 0.355551E+09 | 0.133577E+09 |
April | 88344968.40 | 29504458.70 | 58840509.70 | 0.339015E+09 | 51853919.25 |
May | 63549535.86 | 7141765.29 | 56407770.57 | 0.326039E+09 | 13649765.81 |
June | 54679175.71 | 1673297.37 | 53005878.34 | 0.313013E+09 | 12159258.47 |
July | 58654436.73 | 1328821.70 | 57325615.03 | 0.293248E+09 | 4279087.68 |
August | 62810368.98 | 4444991.25 | 58365377.73 | 0.276845E+09 | 10973379.79 |
September | 82592210.82 | 23362549.71 | 59229661.11 | 0.297287E+09 | 31618209.24 |
October | 0.143898E+09 | 81099637.29 | 62798147.36 | 0.463062E+09 | 0.108074E+09 |
November | 0.169719E+09 | 0.111444E+09 | 58274818.43 | 0.468021E+09 | 0.185736E+09 |
December | 0.155781E+09 | 96593536.03 | 59187848.61 | 0.358234E+09 | 0.261791E+09 |
Annual Sum or Average | 0.127890E+10 | 0.573287E+09 | 0.705609E+09 | 0.411406E+10 | 0.127433E+10 |
Minimum of Months | 54679175.71 | 1328821.70 | 53005878.34 | 0.276845E+09 | 4279087.68 |
Maximum of Months | 0.169719E+09 | 0.111444E+09 | 67331707.46 | 0.468021E+09 | 0.265349E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.146391E+09 | 88187280.52 | 58204094.77 | 0.317632E+09 | 0.265349E+09 |
February | 0.127569E+09 | 70931396.48 | 56637649.59 | 0.306117E+09 | 0.195267E+09 |
March | 0.124907E+09 | 57575446.50 | 67331707.46 | 0.355551E+09 | 0.133577E+09 |
April | 88344968.40 | 29504458.70 | 58840509.70 | 0.339015E+09 | 51853919.25 |
May | 63549535.86 | 7141765.29 | 56407770.57 | 0.326039E+09 | 13649765.81 |
June | 54679175.71 | 1673297.37 | 53005878.34 | 0.313013E+09 | 12159258.47 |
July | 58654436.73 | 1328821.70 | 57325615.03 | 0.293248E+09 | 4279087.68 |
August | 62810368.98 | 4444991.25 | 58365377.73 | 0.276845E+09 | 10973379.79 |
September | 82592210.82 | 23362549.71 | 59229661.11 | 0.297287E+09 | 31618209.24 |
October | 0.143898E+09 | 81099637.29 | 62798147.36 | 0.463062E+09 | 0.108074E+09 |
November | 0.169719E+09 | 0.111444E+09 | 58274818.43 | 0.468021E+09 | 0.185736E+09 |
December | 0.155781E+09 | 96593536.03 | 59187848.61 | 0.358234E+09 | 0.261791E+09 |
Annual Sum or Average | 0.127890E+10 | 0.573287E+09 | 0.705609E+09 | 0.411406E+10 | 0.127433E+10 |
Minimum of Months | 54679175.71 | 1328821.70 | 53005878.34 | 0.276845E+09 | 4279087.68 |
Maximum of Months | 0.169719E+09 | 0.111444E+09 | 67331707.46 | 0.468021E+09 | 0.265349E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_DOOR
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.175284E+09 | 0.105593E+09 | 69691745.05 | 0.378436E+09 | 0.313286E+09 |
February | 0.152747E+09 | 84931014.20 | 67816133.06 | 0.364452E+09 | 0.230448E+09 |
March | 0.149560E+09 | 68939021.47 | 80620860.24 | 0.422341E+09 | 0.157979E+09 |
April | 0.105781E+09 | 35327707.12 | 70453768.20 | 0.401522E+09 | 61450669.22 |
May | 76092207.41 | 8551324.22 | 67540883.19 | 0.384995E+09 | 16270445.73 |
June | 65471118.28 | 2003553.42 | 63467564.85 | 0.369519E+09 | 14334072.59 |
July | 70230970.30 | 1591089.14 | 68639881.16 | 0.346519E+09 | 5117952.13 |
August | 75207152.33 | 5322292.15 | 69884860.18 | 0.327532E+09 | 13049895.51 |
September | 98893305.07 | 27973579.26 | 70919725.81 | 0.352154E+09 | 37490202.50 |
October | 0.172299E+09 | 97106144.65 | 75192518.55 | 0.549229E+09 | 0.128052E+09 |
November | 0.203216E+09 | 0.133439E+09 | 69776427.34 | 0.555997E+09 | 0.219711E+09 |
December | 0.186528E+09 | 0.115658E+09 | 70869660.83 | 0.426397E+09 | 0.309134E+09 |
Annual Sum or Average | 0.153131E+10 | 0.686436E+09 | 0.844874E+09 | 0.487909E+10 | 0.150632E+10 |
Minimum of Months | 65471118.28 | 1591089.14 | 63467564.85 | 0.327532E+09 | 5117952.13 |
Maximum of Months | 0.203216E+09 | 0.133439E+09 | 80620860.24 | 0.555997E+09 | 0.313286E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.146391E+09 | 88187280.52 | 58204094.77 | 0.319245E+09 | 0.260274E+09 |
February | 0.127569E+09 | 70931396.48 | 56637649.59 | 0.306933E+09 | 0.192784E+09 |
March | 0.124907E+09 | 57575446.50 | 67331707.46 | 0.355848E+09 | 0.132862E+09 |
April | 88344968.40 | 29504458.70 | 58840509.70 | 0.338843E+09 | 52479220.85 |
May | 63549535.86 | 7141765.29 | 56407770.57 | 0.324965E+09 | 14486045.09 |
June | 54679175.71 | 1673297.37 | 53005878.34 | 0.311710E+09 | 12715585.81 |
July | 58654436.73 | 1328821.70 | 57325615.03 | 0.291652E+09 | 4620393.53 |
August | 62810368.98 | 4444991.25 | 58365377.73 | 0.276098E+09 | 11518260.83 |
September | 82592210.82 | 23362549.71 | 59229661.11 | 0.297170E+09 | 32499593.39 |
October | 0.143898E+09 | 81099637.29 | 62798147.36 | 0.463094E+09 | 0.108485E+09 |
November | 0.169719E+09 | 0.111444E+09 | 58274818.43 | 0.468443E+09 | 0.184500E+09 |
December | 0.155781E+09 | 96593536.03 | 59187848.61 | 0.359458E+09 | 0.258311E+09 |
Annual Sum or Average | 0.127890E+10 | 0.573287E+09 | 0.705609E+09 | 0.411346E+10 | 0.126554E+10 |
Minimum of Months | 54679175.71 | 1328821.70 | 53005878.34 | 0.276098E+09 | 4620393.53 |
Maximum of Months | 0.169719E+09 | 0.111444E+09 | 67331707.46 | 0.468443E+09 | 0.260274E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.146391E+09 | 88187280.52 | 58204094.77 | 0.319245E+09 | 0.260274E+09 |
February | 0.127569E+09 | 70931396.48 | 56637649.59 | 0.306933E+09 | 0.192784E+09 |
March | 0.124907E+09 | 57575446.50 | 67331707.46 | 0.355848E+09 | 0.132862E+09 |
April | 88344968.40 | 29504458.70 | 58840509.70 | 0.338843E+09 | 52479220.85 |
May | 63549535.86 | 7141765.29 | 56407770.57 | 0.324965E+09 | 14486045.09 |
June | 54679175.71 | 1673297.37 | 53005878.34 | 0.311710E+09 | 12715585.81 |
July | 58654436.73 | 1328821.70 | 57325615.03 | 0.291652E+09 | 4620393.53 |
August | 62810368.98 | 4444991.25 | 58365377.73 | 0.276098E+09 | 11518260.83 |
September | 82592210.82 | 23362549.71 | 59229661.11 | 0.297170E+09 | 32499593.39 |
October | 0.143898E+09 | 81099637.29 | 62798147.36 | 0.463094E+09 | 0.108485E+09 |
November | 0.169719E+09 | 0.111444E+09 | 58274818.43 | 0.468443E+09 | 0.184500E+09 |
December | 0.155781E+09 | 96593536.03 | 59187848.61 | 0.359458E+09 | 0.258311E+09 |
Annual Sum or Average | 0.127890E+10 | 0.573287E+09 | 0.705609E+09 | 0.411346E+10 | 0.126554E+10 |
Minimum of Months | 54679175.71 | 1328821.70 | 53005878.34 | 0.276098E+09 | 4620393.53 |
Maximum of Months | 0.169719E+09 | 0.111444E+09 | 67331707.46 | 0.468443E+09 | 0.260274E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_DOOR
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.175284E+09 | 0.105593E+09 | 69691745.05 | 0.380367E+09 | 0.307293E+09 |
February | 0.152747E+09 | 84931014.20 | 67816133.06 | 0.365433E+09 | 0.227521E+09 |
March | 0.149560E+09 | 68939021.47 | 80620860.24 | 0.422699E+09 | 0.157135E+09 |
April | 0.105781E+09 | 35327707.12 | 70453768.20 | 0.401318E+09 | 62191057.99 |
May | 76092207.41 | 8551324.22 | 67540883.19 | 0.383725E+09 | 17261964.82 |
June | 65471118.28 | 2003553.42 | 63467564.85 | 0.367976E+09 | 14991260.44 |
July | 70230970.30 | 1591089.14 | 68639881.16 | 0.344631E+09 | 5523606.74 |
August | 75207152.33 | 5322292.15 | 69884860.18 | 0.326649E+09 | 13698215.25 |
September | 98893305.07 | 27973579.26 | 70919725.81 | 0.352015E+09 | 38531401.43 |
October | 0.172299E+09 | 97106144.65 | 75192518.55 | 0.549267E+09 | 0.128540E+09 |
November | 0.203216E+09 | 0.133439E+09 | 69776427.34 | 0.556505E+09 | 0.218247E+09 |
December | 0.186528E+09 | 0.115658E+09 | 70869660.83 | 0.427864E+09 | 0.305027E+09 |
Annual Sum or Average | 0.153131E+10 | 0.686436E+09 | 0.844874E+09 | 0.487845E+10 | 0.149596E+10 |
Minimum of Months | 65471118.28 | 1591089.14 | 63467564.85 | 0.326649E+09 | 5523606.74 |
Maximum of Months | 0.203216E+09 | 0.133439E+09 | 80620860.24 | 0.556505E+09 | 0.307293E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.146391E+09 | 88187280.52 | 58204094.77 | 0.320511E+09 | 0.256969E+09 |
February | 0.127569E+09 | 70931396.48 | 56637649.59 | 0.307651E+09 | 0.190803E+09 |
March | 0.124907E+09 | 57575446.50 | 67331707.46 | 0.356298E+09 | 0.131339E+09 |
April | 88344968.40 | 29504458.70 | 58840509.70 | 0.339285E+09 | 51468576.32 |
May | 63549535.86 | 7141765.29 | 56407770.57 | 0.325575E+09 | 13939283.27 |
June | 54679175.71 | 1673297.37 | 53005878.34 | 0.312567E+09 | 12368309.13 |
July | 58654436.73 | 1328821.70 | 57325615.03 | 0.292269E+09 | 4296487.61 |
August | 62810368.98 | 4444991.25 | 58365377.73 | 0.276674E+09 | 10942599.66 |
September | 82592210.82 | 23362549.71 | 59229661.11 | 0.297430E+09 | 31493114.07 |
October | 0.143898E+09 | 81099637.29 | 62798147.36 | 0.463342E+09 | 0.107378E+09 |
November | 0.169719E+09 | 0.111444E+09 | 58274818.43 | 0.468907E+09 | 0.183069E+09 |
December | 0.155781E+09 | 96593536.03 | 59187848.61 | 0.360435E+09 | 0.256021E+09 |
Annual Sum or Average | 0.127890E+10 | 0.573287E+09 | 0.705609E+09 | 0.412094E+10 | 0.125009E+10 |
Minimum of Months | 54679175.71 | 1328821.70 | 53005878.34 | 0.276674E+09 | 4296487.61 |
Maximum of Months | 0.169719E+09 | 0.111444E+09 | 67331707.46 | 0.468907E+09 | 0.256969E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.146391E+09 | 88187280.52 | 58204094.77 | 0.320511E+09 | 0.256969E+09 |
February | 0.127569E+09 | 70931396.48 | 56637649.59 | 0.307651E+09 | 0.190803E+09 |
March | 0.124907E+09 | 57575446.50 | 67331707.46 | 0.356298E+09 | 0.131339E+09 |
April | 88344968.40 | 29504458.70 | 58840509.70 | 0.339285E+09 | 51468576.32 |
May | 63549535.86 | 7141765.29 | 56407770.57 | 0.325575E+09 | 13939283.27 |
June | 54679175.71 | 1673297.37 | 53005878.34 | 0.312567E+09 | 12368309.13 |
July | 58654436.73 | 1328821.70 | 57325615.03 | 0.292269E+09 | 4296487.61 |
August | 62810368.98 | 4444991.25 | 58365377.73 | 0.276674E+09 | 10942599.66 |
September | 82592210.82 | 23362549.71 | 59229661.11 | 0.297430E+09 | 31493114.07 |
October | 0.143898E+09 | 81099637.29 | 62798147.36 | 0.463342E+09 | 0.107378E+09 |
November | 0.169719E+09 | 0.111444E+09 | 58274818.43 | 0.468907E+09 | 0.183069E+09 |
December | 0.155781E+09 | 96593536.03 | 59187848.61 | 0.360435E+09 | 0.256021E+09 |
Annual Sum or Average | 0.127890E+10 | 0.573287E+09 | 0.705609E+09 | 0.412094E+10 | 0.125009E+10 |
Minimum of Months | 54679175.71 | 1328821.70 | 53005878.34 | 0.276674E+09 | 4296487.61 |
Maximum of Months | 0.169719E+09 | 0.111444E+09 | 67331707.46 | 0.468907E+09 | 0.256969E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_DOOR
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.175284E+09 | 0.105593E+09 | 69691745.05 | 0.381881E+09 | 0.303399E+09 |
February | 0.152747E+09 | 84931014.20 | 67816133.06 | 0.366294E+09 | 0.225194E+09 |
March | 0.149560E+09 | 68939021.47 | 80620860.24 | 0.423242E+09 | 0.155346E+09 |
April | 0.105781E+09 | 35327707.12 | 70453768.20 | 0.401848E+09 | 61002925.02 |
May | 76092207.41 | 8551324.22 | 67540883.19 | 0.384443E+09 | 16619724.09 |
June | 65471118.28 | 2003553.42 | 63467564.85 | 0.368985E+09 | 14584213.75 |
July | 70230970.30 | 1591089.14 | 68639881.16 | 0.345354E+09 | 5142244.46 |
August | 75207152.33 | 5322292.15 | 69884860.18 | 0.327328E+09 | 13021450.03 |
September | 98893305.07 | 27973579.26 | 70919725.81 | 0.352327E+09 | 37352625.13 |
October | 0.172299E+09 | 97106144.65 | 75192518.55 | 0.549567E+09 | 0.127237E+09 |
November | 0.203216E+09 | 0.133439E+09 | 69776427.34 | 0.557064E+09 | 0.216565E+09 |
December | 0.186528E+09 | 0.115658E+09 | 70869660.83 | 0.429034E+09 | 0.302336E+09 |
Annual Sum or Average | 0.153131E+10 | 0.686436E+09 | 0.844874E+09 | 0.488737E+10 | 0.147780E+10 |
Minimum of Months | 65471118.28 | 1591089.14 | 63467564.85 | 0.327328E+09 | 5142244.46 |
Maximum of Months | 0.203216E+09 | 0.133439E+09 | 80620860.24 | 0.557064E+09 | 0.303399E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.146391E+09 | 88187280.52 | 58204094.77 | 0.325147E+09 | 0.250198E+09 |
February | 0.127569E+09 | 70931396.48 | 56637649.59 | 0.310977E+09 | 0.185837E+09 |
March | 0.124907E+09 | 57575446.50 | 67331707.46 | 0.358674E+09 | 0.126439E+09 |
April | 88344968.40 | 29504458.70 | 58840509.70 | 0.340952E+09 | 48313534.75 |
May | 63549535.86 | 7141765.29 | 56407770.57 | 0.326644E+09 | 12427841.53 |
June | 54679175.71 | 1673297.37 | 53005878.34 | 0.314524E+09 | 11529257.82 |
July | 58654436.73 | 1328821.70 | 57325615.03 | 0.292715E+09 | 3361826.09 |
August | 62810368.98 | 4444991.25 | 58365377.73 | 0.277804E+09 | 9250189.78 |
September | 82592210.82 | 23362549.71 | 59229661.11 | 0.298044E+09 | 28639218.32 |
October | 0.143898E+09 | 81099637.29 | 62798147.36 | 0.464289E+09 | 0.103750E+09 |
November | 0.169719E+09 | 0.111444E+09 | 58274818.43 | 0.471218E+09 | 0.179139E+09 |
December | 0.155781E+09 | 96593536.03 | 59187848.61 | 0.364264E+09 | 0.251081E+09 |
Annual Sum or Average | 0.127890E+10 | 0.573287E+09 | 0.705609E+09 | 0.414525E+10 | 0.120997E+10 |
Minimum of Months | 54679175.71 | 1328821.70 | 53005878.34 | 0.277804E+09 | 3361826.09 |
Maximum of Months | 0.169719E+09 | 0.111444E+09 | 67331707.46 | 0.471218E+09 | 0.251081E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.146391E+09 | 88187280.52 | 58204094.77 | 0.325147E+09 | 0.250198E+09 |
February | 0.127569E+09 | 70931396.48 | 56637649.59 | 0.310977E+09 | 0.185837E+09 |
March | 0.124907E+09 | 57575446.50 | 67331707.46 | 0.358674E+09 | 0.126439E+09 |
April | 88344968.40 | 29504458.70 | 58840509.70 | 0.340952E+09 | 48313534.75 |
May | 63549535.86 | 7141765.29 | 56407770.57 | 0.326644E+09 | 12427841.53 |
June | 54679175.71 | 1673297.37 | 53005878.34 | 0.314524E+09 | 11529257.82 |
July | 58654436.73 | 1328821.70 | 57325615.03 | 0.292715E+09 | 3361826.09 |
August | 62810368.98 | 4444991.25 | 58365377.73 | 0.277804E+09 | 9250189.78 |
September | 82592210.82 | 23362549.71 | 59229661.11 | 0.298044E+09 | 28639218.32 |
October | 0.143898E+09 | 81099637.29 | 62798147.36 | 0.464289E+09 | 0.103750E+09 |
November | 0.169719E+09 | 0.111444E+09 | 58274818.43 | 0.471218E+09 | 0.179139E+09 |
December | 0.155781E+09 | 96593536.03 | 59187848.61 | 0.364264E+09 | 0.251081E+09 |
Annual Sum or Average | 0.127890E+10 | 0.573287E+09 | 0.705609E+09 | 0.414525E+10 | 0.120997E+10 |
Minimum of Months | 54679175.71 | 1328821.70 | 53005878.34 | 0.277804E+09 | 3361826.09 |
Maximum of Months | 0.169719E+09 | 0.111444E+09 | 67331707.46 | 0.471218E+09 | 0.251081E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_3
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.146391E+09 | 88187280.52 | 58204094.77 | 0.325147E+09 | 0.250198E+09 |
February | 0.127569E+09 | 70931396.48 | 56637649.59 | 0.310977E+09 | 0.185837E+09 |
March | 0.124907E+09 | 57575446.50 | 67331707.46 | 0.358674E+09 | 0.126439E+09 |
April | 88344968.40 | 29504458.70 | 58840509.70 | 0.340952E+09 | 48313534.75 |
May | 63549535.86 | 7141765.29 | 56407770.57 | 0.326644E+09 | 12427841.53 |
June | 54679175.71 | 1673297.37 | 53005878.34 | 0.314524E+09 | 11529257.82 |
July | 58654436.73 | 1328821.70 | 57325615.03 | 0.292715E+09 | 3361826.09 |
August | 62810368.98 | 4444991.25 | 58365377.73 | 0.277804E+09 | 9250189.78 |
September | 82592210.82 | 23362549.71 | 59229661.11 | 0.298044E+09 | 28639218.32 |
October | 0.143898E+09 | 81099637.29 | 62798147.36 | 0.464289E+09 | 0.103750E+09 |
November | 0.169719E+09 | 0.111444E+09 | 58274818.43 | 0.471218E+09 | 0.179139E+09 |
December | 0.155781E+09 | 96593536.03 | 59187848.61 | 0.364264E+09 | 0.251081E+09 |
Annual Sum or Average | 0.127890E+10 | 0.573287E+09 | 0.705609E+09 | 0.414525E+10 | 0.120997E+10 |
Minimum of Months | 54679175.71 | 1328821.70 | 53005878.34 | 0.277804E+09 | 3361826.09 |
Maximum of Months | 0.169719E+09 | 0.111444E+09 | 67331707.46 | 0.471218E+09 | 0.251081E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_4
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.146391E+09 | 88187280.52 | 58204094.77 | 0.325147E+09 | 0.250198E+09 |
February | 0.127569E+09 | 70931396.48 | 56637649.59 | 0.310977E+09 | 0.185837E+09 |
March | 0.124907E+09 | 57575446.50 | 67331707.46 | 0.358674E+09 | 0.126439E+09 |
April | 88344968.40 | 29504458.70 | 58840509.70 | 0.340952E+09 | 48313534.75 |
May | 63549535.86 | 7141765.29 | 56407770.57 | 0.326644E+09 | 12427841.53 |
June | 54679175.71 | 1673297.37 | 53005878.34 | 0.314524E+09 | 11529257.82 |
July | 58654436.73 | 1328821.70 | 57325615.03 | 0.292715E+09 | 3361826.09 |
August | 62810368.98 | 4444991.25 | 58365377.73 | 0.277804E+09 | 9250189.78 |
September | 82592210.82 | 23362549.71 | 59229661.11 | 0.298044E+09 | 28639218.32 |
October | 0.143898E+09 | 81099637.29 | 62798147.36 | 0.464289E+09 | 0.103750E+09 |
November | 0.169719E+09 | 0.111444E+09 | 58274818.43 | 0.471218E+09 | 0.179139E+09 |
December | 0.155781E+09 | 96593536.03 | 59187848.61 | 0.364264E+09 | 0.251081E+09 |
Annual Sum or Average | 0.127890E+10 | 0.573287E+09 | 0.705609E+09 | 0.414525E+10 | 0.120997E+10 |
Minimum of Months | 54679175.71 | 1328821.70 | 53005878.34 | 0.277804E+09 | 3361826.09 |
Maximum of Months | 0.169719E+09 | 0.111444E+09 | 67331707.46 | 0.471218E+09 | 0.251081E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_DOOR_1
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.175284E+09 | 0.105593E+09 | 69691745.05 | 0.387279E+09 | 0.295445E+09 |
February | 0.152747E+09 | 84931014.20 | 67816133.06 | 0.370143E+09 | 0.219391E+09 |
March | 0.149560E+09 | 68939021.47 | 80620860.24 | 0.426001E+09 | 0.149606E+09 |
April | 0.105781E+09 | 35327707.12 | 70453768.20 | 0.403799E+09 | 57261599.60 |
May | 76092207.41 | 8551324.22 | 67540883.19 | 0.385742E+09 | 14811642.77 |
June | 65471118.28 | 2003553.42 | 63467564.85 | 0.371332E+09 | 13578793.99 |
July | 70230970.30 | 1591089.14 | 68639881.16 | 0.345919E+09 | 4025865.77 |
August | 75207152.33 | 5322292.15 | 69884860.18 | 0.328658E+09 | 11006279.59 |
September | 98893305.07 | 27973579.26 | 70919725.81 | 0.353019E+09 | 33953114.07 |
October | 0.172299E+09 | 97106144.65 | 75192518.55 | 0.550642E+09 | 0.122961E+09 |
November | 0.203216E+09 | 0.133439E+09 | 69776427.34 | 0.559730E+09 | 0.211948E+09 |
December | 0.186528E+09 | 0.115658E+09 | 70869660.83 | 0.433482E+09 | 0.296535E+09 |
Annual Sum or Average | 0.153131E+10 | 0.686436E+09 | 0.844874E+09 | 0.491575E+10 | 0.143052E+10 |
Minimum of Months | 65471118.28 | 1591089.14 | 63467564.85 | 0.328658E+09 | 4025865.77 |
Maximum of Months | 0.203216E+09 | 0.133439E+09 | 80620860.24 | 0.559730E+09 | 0.296535E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_DOOR_2
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.175284E+09 | 0.105593E+09 | 69691745.05 | 0.387279E+09 | 0.295445E+09 |
February | 0.152747E+09 | 84931014.20 | 67816133.06 | 0.370143E+09 | 0.219391E+09 |
March | 0.149560E+09 | 68939021.47 | 80620860.24 | 0.426001E+09 | 0.149606E+09 |
April | 0.105781E+09 | 35327707.12 | 70453768.20 | 0.403799E+09 | 57261599.60 |
May | 76092207.41 | 8551324.22 | 67540883.19 | 0.385742E+09 | 14811642.77 |
June | 65471118.28 | 2003553.42 | 63467564.85 | 0.371332E+09 | 13578793.99 |
July | 70230970.30 | 1591089.14 | 68639881.16 | 0.345919E+09 | 4025865.77 |
August | 75207152.33 | 5322292.15 | 69884860.18 | 0.328658E+09 | 11006279.59 |
September | 98893305.07 | 27973579.26 | 70919725.81 | 0.353019E+09 | 33953114.07 |
October | 0.172299E+09 | 97106144.65 | 75192518.55 | 0.550642E+09 | 0.122961E+09 |
November | 0.203216E+09 | 0.133439E+09 | 69776427.34 | 0.559730E+09 | 0.211948E+09 |
December | 0.186528E+09 | 0.115658E+09 | 70869660.83 | 0.433482E+09 | 0.296535E+09 |
Annual Sum or Average | 0.153131E+10 | 0.686436E+09 | 0.844874E+09 | 0.491575E+10 | 0.143052E+10 |
Minimum of Months | 65471118.28 | 1591089.14 | 63467564.85 | 0.328658E+09 | 4025865.77 |
Maximum of Months | 0.203216E+09 | 0.133439E+09 | 80620860.24 | 0.559730E+09 | 0.296535E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.146391E+09 | 88187280.52 | 58204094.77 | 0.324200E+09 | 0.249952E+09 |
February | 0.127569E+09 | 70931396.48 | 56637649.59 | 0.310076E+09 | 0.185470E+09 |
March | 0.124907E+09 | 57575446.50 | 67331707.46 | 0.358653E+09 | 0.125103E+09 |
April | 88344968.40 | 29504458.70 | 58840509.70 | 0.342867E+09 | 46789933.31 |
May | 63549535.86 | 7141765.29 | 56407770.57 | 0.330977E+09 | 11358890.59 |
June | 54679175.71 | 1673297.37 | 53005878.34 | 0.319412E+09 | 10803307.83 |
July | 58654436.73 | 1328821.70 | 57325615.03 | 0.297107E+09 | 2820985.51 |
August | 62810368.98 | 4444991.25 | 58365377.73 | 0.281000E+09 | 8224696.86 |
September | 82592210.82 | 23362549.71 | 59229661.11 | 0.299750E+09 | 26759789.89 |
October | 0.143898E+09 | 81099637.29 | 62798147.36 | 0.464822E+09 | 0.101883E+09 |
November | 0.169719E+09 | 0.111444E+09 | 58274818.43 | 0.470740E+09 | 0.177950E+09 |
December | 0.155781E+09 | 96593536.03 | 59187848.61 | 0.363415E+09 | 0.250815E+09 |
Annual Sum or Average | 0.127890E+10 | 0.573287E+09 | 0.705609E+09 | 0.416302E+10 | 0.119793E+10 |
Minimum of Months | 54679175.71 | 1328821.70 | 53005878.34 | 0.281000E+09 | 2820985.51 |
Maximum of Months | 0.169719E+09 | 0.111444E+09 | 67331707.46 | 0.470740E+09 | 0.250815E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.146391E+09 | 88187280.52 | 58204094.77 | 0.324200E+09 | 0.249952E+09 |
February | 0.127569E+09 | 70931396.48 | 56637649.59 | 0.310076E+09 | 0.185470E+09 |
March | 0.124907E+09 | 57575446.50 | 67331707.46 | 0.358653E+09 | 0.125103E+09 |
April | 88344968.40 | 29504458.70 | 58840509.70 | 0.342867E+09 | 46789933.31 |
May | 63549535.86 | 7141765.29 | 56407770.57 | 0.330977E+09 | 11358890.59 |
June | 54679175.71 | 1673297.37 | 53005878.34 | 0.319412E+09 | 10803307.83 |
July | 58654436.73 | 1328821.70 | 57325615.03 | 0.297107E+09 | 2820985.51 |
August | 62810368.98 | 4444991.25 | 58365377.73 | 0.281000E+09 | 8224696.86 |
September | 82592210.82 | 23362549.71 | 59229661.11 | 0.299750E+09 | 26759789.89 |
October | 0.143898E+09 | 81099637.29 | 62798147.36 | 0.464822E+09 | 0.101883E+09 |
November | 0.169719E+09 | 0.111444E+09 | 58274818.43 | 0.470740E+09 | 0.177950E+09 |
December | 0.155781E+09 | 96593536.03 | 59187848.61 | 0.363415E+09 | 0.250815E+09 |
Annual Sum or Average | 0.127890E+10 | 0.573287E+09 | 0.705609E+09 | 0.416302E+10 | 0.119793E+10 |
Minimum of Months | 54679175.71 | 1328821.70 | 53005878.34 | 0.281000E+09 | 2820985.51 |
Maximum of Months | 0.169719E+09 | 0.111444E+09 | 67331707.46 | 0.470740E+09 | 0.250815E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_DOOR
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.175284E+09 | 0.105593E+09 | 69691745.05 | 0.386306E+09 | 0.295093E+09 |
February | 0.152747E+09 | 84931014.20 | 67816133.06 | 0.369224E+09 | 0.218896E+09 |
March | 0.149560E+09 | 68939021.47 | 80620860.24 | 0.426110E+09 | 0.147997E+09 |
April | 0.105781E+09 | 35327707.12 | 70453768.20 | 0.406134E+09 | 55452146.17 |
May | 76092207.41 | 8551324.22 | 67540883.19 | 0.390842E+09 | 13542992.78 |
June | 65471118.28 | 2003553.42 | 63467564.85 | 0.377097E+09 | 12719138.43 |
July | 70230970.30 | 1591089.14 | 68639881.16 | 0.351111E+09 | 3381004.47 |
August | 75207152.33 | 5322292.15 | 69884860.18 | 0.332490E+09 | 9787440.67 |
September | 98893305.07 | 27973579.26 | 70919725.81 | 0.355119E+09 | 31724618.69 |
October | 0.172299E+09 | 97106144.65 | 75192518.55 | 0.551393E+09 | 0.120735E+09 |
November | 0.203216E+09 | 0.133439E+09 | 69776427.34 | 0.559313E+09 | 0.210513E+09 |
December | 0.186528E+09 | 0.115658E+09 | 70869660.83 | 0.432621E+09 | 0.296165E+09 |
Annual Sum or Average | 0.153131E+10 | 0.686436E+09 | 0.844874E+09 | 0.493776E+10 | 0.141601E+10 |
Minimum of Months | 65471118.28 | 1591089.14 | 63467564.85 | 0.332490E+09 | 3381004.47 |
Maximum of Months | 0.203216E+09 | 0.133439E+09 | 80620860.24 | 0.559313E+09 | 0.296165E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.146391E+09 | 88187280.52 | 58204094.77 | 0.324742E+09 | 0.248744E+09 |
February | 0.127569E+09 | 70931396.48 | 56637649.59 | 0.310490E+09 | 0.184598E+09 |
March | 0.124907E+09 | 57575446.50 | 67331707.46 | 0.358992E+09 | 0.124421E+09 |
April | 88344968.40 | 29504458.70 | 58840509.70 | 0.343242E+09 | 46358025.07 |
May | 63549535.86 | 7141765.29 | 56407770.57 | 0.331508E+09 | 11142580.59 |
June | 54679175.71 | 1673297.37 | 53005878.34 | 0.320007E+09 | 10649267.68 |
July | 58654436.73 | 1328821.70 | 57325615.03 | 0.297672E+09 | 2728869.58 |
August | 62810368.98 | 4444991.25 | 58365377.73 | 0.281449E+09 | 8044373.18 |
September | 82592210.82 | 23362549.71 | 59229661.11 | 0.300037E+09 | 26397180.81 |
October | 0.143898E+09 | 81099637.29 | 62798147.36 | 0.465054E+09 | 0.101421E+09 |
November | 0.169719E+09 | 0.111444E+09 | 58274818.43 | 0.471024E+09 | 0.177371E+09 |
December | 0.155781E+09 | 96593536.03 | 59187848.61 | 0.363892E+09 | 0.249933E+09 |
Annual Sum or Average | 0.127890E+10 | 0.573287E+09 | 0.705609E+09 | 0.416811E+10 | 0.119181E+10 |
Minimum of Months | 54679175.71 | 1328821.70 | 53005878.34 | 0.281449E+09 | 2728869.58 |
Maximum of Months | 0.169719E+09 | 0.111444E+09 | 67331707.46 | 0.471024E+09 | 0.249933E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.146391E+09 | 88187280.52 | 58204094.77 | 0.324742E+09 | 0.248744E+09 |
February | 0.127569E+09 | 70931396.48 | 56637649.59 | 0.310490E+09 | 0.184598E+09 |
March | 0.124907E+09 | 57575446.50 | 67331707.46 | 0.358992E+09 | 0.124421E+09 |
April | 88344968.40 | 29504458.70 | 58840509.70 | 0.343242E+09 | 46358025.07 |
May | 63549535.86 | 7141765.29 | 56407770.57 | 0.331508E+09 | 11142580.59 |
June | 54679175.71 | 1673297.37 | 53005878.34 | 0.320007E+09 | 10649267.68 |
July | 58654436.73 | 1328821.70 | 57325615.03 | 0.297672E+09 | 2728869.58 |
August | 62810368.98 | 4444991.25 | 58365377.73 | 0.281449E+09 | 8044373.18 |
September | 82592210.82 | 23362549.71 | 59229661.11 | 0.300037E+09 | 26397180.81 |
October | 0.143898E+09 | 81099637.29 | 62798147.36 | 0.465054E+09 | 0.101421E+09 |
November | 0.169719E+09 | 0.111444E+09 | 58274818.43 | 0.471024E+09 | 0.177371E+09 |
December | 0.155781E+09 | 96593536.03 | 59187848.61 | 0.363892E+09 | 0.249933E+09 |
Annual Sum or Average | 0.127890E+10 | 0.573287E+09 | 0.705609E+09 | 0.416811E+10 | 0.119181E+10 |
Minimum of Months | 54679175.71 | 1328821.70 | 53005878.34 | 0.281449E+09 | 2728869.58 |
Maximum of Months | 0.169719E+09 | 0.111444E+09 | 67331707.46 | 0.471024E+09 | 0.249933E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_DOOR
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.175284E+09 | 0.105593E+09 | 69691745.05 | 0.386957E+09 | 0.293668E+09 |
February | 0.152747E+09 | 84931014.20 | 67816133.06 | 0.369723E+09 | 0.217868E+09 |
March | 0.149560E+09 | 68939021.47 | 80620860.24 | 0.426518E+09 | 0.147191E+09 |
April | 0.105781E+09 | 35327707.12 | 70453768.20 | 0.406585E+09 | 54941086.93 |
May | 76092207.41 | 8551324.22 | 67540883.19 | 0.391474E+09 | 13284571.03 |
June | 65471118.28 | 2003553.42 | 63467564.85 | 0.377806E+09 | 12536880.36 |
July | 70230970.30 | 1591089.14 | 68639881.16 | 0.351783E+09 | 3271010.83 |
August | 75207152.33 | 5322292.15 | 69884860.18 | 0.333026E+09 | 9573081.18 |
September | 98893305.07 | 27973579.26 | 70919725.81 | 0.355464E+09 | 31294371.47 |
October | 0.172299E+09 | 97106144.65 | 75192518.55 | 0.551673E+09 | 0.120188E+09 |
November | 0.203216E+09 | 0.133439E+09 | 69776427.34 | 0.559655E+09 | 0.209828E+09 |
December | 0.186528E+09 | 0.115658E+09 | 70869660.83 | 0.433191E+09 | 0.295123E+09 |
Annual Sum or Average | 0.153131E+10 | 0.686436E+09 | 0.844874E+09 | 0.494385E+10 | 0.140877E+10 |
Minimum of Months | 65471118.28 | 1591089.14 | 63467564.85 | 0.333026E+09 | 3271010.83 |
Maximum of Months | 0.203216E+09 | 0.133439E+09 | 80620860.24 | 0.559655E+09 | 0.295123E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.146391E+09 | 88187280.52 | 58204094.77 | 0.326009E+09 | 0.245402E+09 |
February | 0.127569E+09 | 70931396.48 | 56637649.59 | 0.311501E+09 | 0.182075E+09 |
March | 0.124907E+09 | 57575446.50 | 67331707.46 | 0.359531E+09 | 0.122857E+09 |
April | 88344968.40 | 29504458.70 | 58840509.70 | 0.343278E+09 | 45901619.56 |
May | 63549535.86 | 7141765.29 | 56407770.57 | 0.331088E+09 | 11165407.47 |
June | 54679175.71 | 1673297.37 | 53005878.34 | 0.319322E+09 | 10681543.65 |
July | 58654436.73 | 1328821.70 | 57325615.03 | 0.296680E+09 | 2797207.15 |
August | 62810368.98 | 4444991.25 | 58365377.73 | 0.280679E+09 | 8240306.88 |
September | 82592210.82 | 23362549.71 | 59229661.11 | 0.299661E+09 | 26692279.75 |
October | 0.143898E+09 | 81099637.29 | 62798147.36 | 0.464957E+09 | 0.101319E+09 |
November | 0.169719E+09 | 0.111444E+09 | 58274818.43 | 0.471431E+09 | 0.176301E+09 |
December | 0.155781E+09 | 96593536.03 | 59187848.61 | 0.365072E+09 | 0.247423E+09 |
Annual Sum or Average | 0.127890E+10 | 0.573287E+09 | 0.705609E+09 | 0.416921E+10 | 0.118086E+10 |
Minimum of Months | 54679175.71 | 1328821.70 | 53005878.34 | 0.280679E+09 | 2797207.15 |
Maximum of Months | 0.169719E+09 | 0.111444E+09 | 67331707.46 | 0.471431E+09 | 0.247423E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.146391E+09 | 88187280.52 | 58204094.77 | 0.326009E+09 | 0.245402E+09 |
February | 0.127569E+09 | 70931396.48 | 56637649.59 | 0.311501E+09 | 0.182075E+09 |
March | 0.124907E+09 | 57575446.50 | 67331707.46 | 0.359531E+09 | 0.122857E+09 |
April | 88344968.40 | 29504458.70 | 58840509.70 | 0.343278E+09 | 45901619.56 |
May | 63549535.86 | 7141765.29 | 56407770.57 | 0.331088E+09 | 11165407.47 |
June | 54679175.71 | 1673297.37 | 53005878.34 | 0.319322E+09 | 10681543.65 |
July | 58654436.73 | 1328821.70 | 57325615.03 | 0.296680E+09 | 2797207.15 |
August | 62810368.98 | 4444991.25 | 58365377.73 | 0.280679E+09 | 8240306.88 |
September | 82592210.82 | 23362549.71 | 59229661.11 | 0.299661E+09 | 26692279.75 |
October | 0.143898E+09 | 81099637.29 | 62798147.36 | 0.464957E+09 | 0.101319E+09 |
November | 0.169719E+09 | 0.111444E+09 | 58274818.43 | 0.471431E+09 | 0.176301E+09 |
December | 0.155781E+09 | 96593536.03 | 59187848.61 | 0.365072E+09 | 0.247423E+09 |
Annual Sum or Average | 0.127890E+10 | 0.573287E+09 | 0.705609E+09 | 0.416921E+10 | 0.118086E+10 |
Minimum of Months | 54679175.71 | 1328821.70 | 53005878.34 | 0.280679E+09 | 2797207.15 |
Maximum of Months | 0.169719E+09 | 0.111444E+09 | 67331707.46 | 0.471431E+09 | 0.247423E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_DOOR
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.175284E+09 | 0.105593E+09 | 69691745.05 | 0.388470E+09 | 0.289734E+09 |
February | 0.152747E+09 | 84931014.20 | 67816133.06 | 0.370932E+09 | 0.214903E+09 |
March | 0.149560E+09 | 68939021.47 | 80620860.24 | 0.427167E+09 | 0.145355E+09 |
April | 0.105781E+09 | 35327707.12 | 70453768.20 | 0.406626E+09 | 54409563.30 |
May | 76092207.41 | 8551324.22 | 67540883.19 | 0.390967E+09 | 13317702.41 |
June | 65471118.28 | 2003553.42 | 63467564.85 | 0.376981E+09 | 12578805.33 |
July | 70230970.30 | 1591089.14 | 68639881.16 | 0.350594E+09 | 3355792.69 |
August | 75207152.33 | 5322292.15 | 69884860.18 | 0.332100E+09 | 9812398.03 |
September | 98893305.07 | 27973579.26 | 70919725.81 | 0.355010E+09 | 31656610.34 |
October | 0.172299E+09 | 97106144.65 | 75192518.55 | 0.551556E+09 | 0.120078E+09 |
November | 0.203216E+09 | 0.133439E+09 | 69776427.34 | 0.560141E+09 | 0.208573E+09 |
December | 0.186528E+09 | 0.115658E+09 | 70869660.83 | 0.434599E+09 | 0.292172E+09 |
Annual Sum or Average | 0.153131E+10 | 0.686436E+09 | 0.844874E+09 | 0.494514E+10 | 0.139595E+10 |
Minimum of Months | 65471118.28 | 1591089.14 | 63467564.85 | 0.332100E+09 | 3355792.69 |
Maximum of Months | 0.203216E+09 | 0.133439E+09 | 80620860.24 | 0.560141E+09 | 0.292172E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.146391E+09 | 88187280.52 | 58204094.77 | 0.328320E+09 | 0.234137E+09 |
February | 0.127569E+09 | 70931396.48 | 56637649.59 | 0.313455E+09 | 0.172351E+09 |
March | 0.124907E+09 | 57575446.50 | 67331707.46 | 0.359741E+09 | 0.116439E+09 |
April | 88344968.40 | 29504458.70 | 58840509.70 | 0.340081E+09 | 44634783.75 |
May | 63549535.86 | 7141765.29 | 56407770.57 | 0.324387E+09 | 11899091.49 |
June | 54679175.71 | 1673297.37 | 53005878.34 | 0.310847E+09 | 11317702.57 |
July | 58654436.73 | 1328821.70 | 57325615.03 | 0.286825E+09 | 3673943.87 |
August | 62810368.98 | 4444991.25 | 58365377.73 | 0.272598E+09 | 10382220.57 |
September | 82592210.82 | 23362549.71 | 59229661.11 | 0.294693E+09 | 30297642.43 |
October | 0.143898E+09 | 81099637.29 | 62798147.36 | 0.461889E+09 | 0.102686E+09 |
November | 0.169719E+09 | 0.111444E+09 | 58274818.43 | 0.471116E+09 | 0.172705E+09 |
December | 0.155781E+09 | 96593536.03 | 59187848.61 | 0.367292E+09 | 0.238253E+09 |
Annual Sum or Average | 0.127890E+10 | 0.573287E+09 | 0.705609E+09 | 0.413124E+10 | 0.114878E+10 |
Minimum of Months | 54679175.71 | 1328821.70 | 53005878.34 | 0.272598E+09 | 3673943.87 |
Maximum of Months | 0.169719E+09 | 0.111444E+09 | 67331707.46 | 0.471116E+09 | 0.238253E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.146391E+09 | 88187280.52 | 58204094.77 | 0.328320E+09 | 0.234137E+09 |
February | 0.127569E+09 | 70931396.48 | 56637649.59 | 0.313455E+09 | 0.172351E+09 |
March | 0.124907E+09 | 57575446.50 | 67331707.46 | 0.359741E+09 | 0.116439E+09 |
April | 88344968.40 | 29504458.70 | 58840509.70 | 0.340081E+09 | 44634783.75 |
May | 63549535.86 | 7141765.29 | 56407770.57 | 0.324387E+09 | 11899091.49 |
June | 54679175.71 | 1673297.37 | 53005878.34 | 0.310847E+09 | 11317702.57 |
July | 58654436.73 | 1328821.70 | 57325615.03 | 0.286825E+09 | 3673943.87 |
August | 62810368.98 | 4444991.25 | 58365377.73 | 0.272598E+09 | 10382220.57 |
September | 82592210.82 | 23362549.71 | 59229661.11 | 0.294693E+09 | 30297642.43 |
October | 0.143898E+09 | 81099637.29 | 62798147.36 | 0.461889E+09 | 0.102686E+09 |
November | 0.169719E+09 | 0.111444E+09 | 58274818.43 | 0.471116E+09 | 0.172705E+09 |
December | 0.155781E+09 | 96593536.03 | 59187848.61 | 0.367292E+09 | 0.238253E+09 |
Annual Sum or Average | 0.127890E+10 | 0.573287E+09 | 0.705609E+09 | 0.413124E+10 | 0.114878E+10 |
Minimum of Months | 54679175.71 | 1328821.70 | 53005878.34 | 0.272598E+09 | 3673943.87 |
Maximum of Months | 0.169719E+09 | 0.111444E+09 | 67331707.46 | 0.471116E+09 | 0.238253E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_DOOR
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.175284E+09 | 0.105593E+09 | 69691745.05 | 0.391245E+09 | 0.276453E+09 |
February | 0.152747E+09 | 84931014.20 | 67816133.06 | 0.373262E+09 | 0.203460E+09 |
March | 0.149560E+09 | 68939021.47 | 80620860.24 | 0.427408E+09 | 0.137802E+09 |
April | 0.105781E+09 | 35327707.12 | 70453768.20 | 0.402773E+09 | 52914083.17 |
May | 76092207.41 | 8551324.22 | 67540883.19 | 0.382956E+09 | 14194688.08 |
June | 65471118.28 | 2003553.42 | 63467564.85 | 0.366864E+09 | 13330683.32 |
July | 70230970.30 | 1591089.14 | 68639881.16 | 0.338859E+09 | 4405996.44 |
August | 75207152.33 | 5322292.15 | 69884860.18 | 0.322435E+09 | 12363385.46 |
September | 98893305.07 | 27973579.26 | 70919725.81 | 0.349032E+09 | 35927425.80 |
October | 0.172299E+09 | 97106144.65 | 75192518.55 | 0.547847E+09 | 0.121704E+09 |
November | 0.203216E+09 | 0.133439E+09 | 69776427.34 | 0.559741E+09 | 0.204333E+09 |
December | 0.186528E+09 | 0.115658E+09 | 70869660.83 | 0.437240E+09 | 0.281362E+09 |
Annual Sum or Average | 0.153131E+10 | 0.686436E+09 | 0.844874E+09 | 0.489966E+10 | 0.135825E+10 |
Minimum of Months | 65471118.28 | 1591089.14 | 63467564.85 | 0.322435E+09 | 4405996.44 |
Maximum of Months | 0.203216E+09 | 0.133439E+09 | 80620860.24 | 0.559741E+09 | 0.281362E+09 |
Report: WindowZoneSummaryMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 756.08 | 649.69 | 350.23 | 210.98 | 139.25 | 0.00 | 0.00 |
February | 809.61 | 516.37 | 337.90 | 187.88 | 150.02 | 0.00 | 0.00 |
March | 848.78 | 306.29 | 298.83 | 137.75 | 161.09 | 0.00 | 0.00 |
April | 842.88 | 114.21 | 218.40 | 72.94 | 145.46 | 0.00 | 0.00 |
May | 793.82 | 25.71 | 152.04 | 17.09 | 134.95 | 0.00 | 0.00 |
June | 786.75 | 23.74 | 135.18 | 4.14 | 131.04 | 0.00 | 0.00 |
July | 719.69 | 7.71 | 140.33 | 3.18 | 137.15 | 0.00 | 0.00 |
August | 668.62 | 20.57 | 150.27 | 10.63 | 139.64 | 0.00 | 0.00 |
September | 733.05 | 66.20 | 204.18 | 57.76 | 146.43 | 0.00 | 0.00 |
October | 1102.47 | 242.01 | 344.27 | 194.03 | 150.24 | 0.00 | 0.00 |
November | 1152.26 | 452.92 | 419.58 | 275.51 | 144.07 | 0.00 | 0.00 |
December | 853.03 | 634.51 | 372.70 | 231.09 | 141.60 | 0.00 | 0.00 |
Annual Sum or Average | 838.72 | 253.84 | 259.86 | 116.49 | 143.37 | 0.00 | 0.00 |
Minimum of Months | 668.62 | 7.71 | 135.18 | 3.18 | 131.04 | 0.00 | 0.00 |
Maximum of Months | 1152.26 | 649.69 | 419.58 | 275.51 | 161.09 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 374.62 | 329.54 | 175.12 | 105.49 | 69.62 | 0.00 | 0.00 |
February | 401.94 | 261.76 | 168.95 | 93.94 | 75.01 | 0.00 | 0.00 |
March | 423.68 | 154.43 | 149.42 | 68.87 | 80.54 | 0.00 | 0.00 |
April | 424.76 | 56.66 | 109.20 | 36.47 | 72.73 | 0.00 | 0.00 |
May | 404.18 | 11.96 | 76.02 | 8.54 | 67.48 | 0.00 | 0.00 |
June | 402.36 | 11.01 | 67.59 | 2.07 | 65.52 | 0.00 | 0.00 |
July | 368.66 | 3.19 | 70.16 | 1.59 | 68.57 | 0.00 | 0.00 |
August | 341.34 | 8.76 | 75.13 | 5.32 | 69.82 | 0.00 | 0.00 |
September | 371.36 | 30.20 | 102.09 | 28.88 | 73.21 | 0.00 | 0.00 |
October | 553.09 | 118.86 | 172.13 | 97.01 | 75.12 | 0.00 | 0.00 |
November | 575.36 | 226.19 | 209.79 | 137.75 | 72.03 | 0.00 | 0.00 |
December | 423.86 | 320.07 | 186.35 | 115.55 | 70.80 | 0.00 | 0.00 |
Annual Sum or Average | 422.03 | 127.13 | 129.93 | 58.24 | 71.69 | 0.00 | 0.00 |
Minimum of Months | 341.34 | 3.19 | 67.59 | 1.59 | 65.52 | 0.00 | 0.00 |
Maximum of Months | 575.36 | 329.54 | 209.79 | 137.75 | 80.54 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 378.47 | 315.11 | 174.76 | 105.27 | 69.48 | 0.00 | 0.00 |
February | 403.72 | 256.69 | 168.60 | 93.75 | 74.86 | 0.00 | 0.00 |
March | 423.18 | 158.73 | 149.11 | 68.73 | 80.38 | 0.00 | 0.00 |
April | 416.49 | 63.72 | 108.98 | 36.40 | 72.58 | 0.00 | 0.00 |
May | 387.20 | 16.27 | 75.86 | 8.53 | 67.34 | 0.00 | 0.00 |
June | 384.08 | 14.91 | 67.45 | 2.06 | 65.39 | 0.00 | 0.00 |
July | 348.35 | 5.11 | 70.02 | 1.59 | 68.43 | 0.00 | 0.00 |
August | 329.01 | 13.07 | 74.98 | 5.31 | 69.67 | 0.00 | 0.00 |
September | 365.25 | 38.86 | 101.88 | 28.82 | 73.06 | 0.00 | 0.00 |
October | 550.83 | 128.51 | 171.78 | 96.81 | 74.97 | 0.00 | 0.00 |
November | 575.63 | 228.08 | 209.36 | 137.47 | 71.89 | 0.00 | 0.00 |
December | 426.70 | 310.90 | 185.97 | 115.31 | 70.66 | 0.00 | 0.00 |
Annual Sum or Average | 415.63 | 128.58 | 129.66 | 58.12 | 71.54 | 0.00 | 0.00 |
Minimum of Months | 329.01 | 5.11 | 67.45 | 1.59 | 65.39 | 0.00 | 0.00 |
Maximum of Months | 575.63 | 315.11 | 209.36 | 137.47 | 80.38 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 380.40 | 309.08 | 174.76 | 105.27 | 69.48 | 0.00 | 0.00 |
February | 404.80 | 253.43 | 168.60 | 93.75 | 74.86 | 0.00 | 0.00 |
March | 423.53 | 157.88 | 149.11 | 68.73 | 80.38 | 0.00 | 0.00 |
April | 416.28 | 64.49 | 108.98 | 36.40 | 72.58 | 0.00 | 0.00 |
May | 385.92 | 17.26 | 75.86 | 8.53 | 67.34 | 0.00 | 0.00 |
June | 382.48 | 15.60 | 67.45 | 2.06 | 65.39 | 0.00 | 0.00 |
July | 346.45 | 5.51 | 70.02 | 1.59 | 68.43 | 0.00 | 0.00 |
August | 328.12 | 13.72 | 74.98 | 5.31 | 69.67 | 0.00 | 0.00 |
September | 365.11 | 39.94 | 101.88 | 28.82 | 73.06 | 0.00 | 0.00 |
October | 550.87 | 129.00 | 171.78 | 96.81 | 74.97 | 0.00 | 0.00 |
November | 576.15 | 226.56 | 209.36 | 137.47 | 71.89 | 0.00 | 0.00 |
December | 428.16 | 306.77 | 185.97 | 115.31 | 70.66 | 0.00 | 0.00 |
Annual Sum or Average | 415.57 | 127.70 | 129.66 | 58.12 | 71.54 | 0.00 | 0.00 |
Minimum of Months | 328.12 | 5.51 | 67.45 | 1.59 | 65.39 | 0.00 | 0.00 |
Maximum of Months | 576.15 | 309.08 | 209.36 | 137.47 | 80.38 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 381.91 | 305.16 | 174.76 | 105.27 | 69.48 | 0.00 | 0.00 |
February | 405.75 | 250.83 | 168.60 | 93.75 | 74.86 | 0.00 | 0.00 |
March | 424.07 | 156.07 | 149.11 | 68.73 | 80.38 | 0.00 | 0.00 |
April | 416.83 | 63.25 | 108.98 | 36.40 | 72.58 | 0.00 | 0.00 |
May | 386.65 | 16.61 | 75.86 | 8.53 | 67.34 | 0.00 | 0.00 |
June | 383.53 | 15.17 | 67.45 | 2.06 | 65.39 | 0.00 | 0.00 |
July | 347.18 | 5.13 | 70.02 | 1.59 | 68.43 | 0.00 | 0.00 |
August | 328.81 | 13.03 | 74.98 | 5.31 | 69.67 | 0.00 | 0.00 |
September | 365.43 | 38.71 | 101.88 | 28.82 | 73.06 | 0.00 | 0.00 |
October | 551.17 | 127.69 | 171.78 | 96.81 | 74.97 | 0.00 | 0.00 |
November | 576.73 | 224.81 | 209.36 | 137.47 | 71.89 | 0.00 | 0.00 |
December | 429.32 | 304.05 | 185.97 | 115.31 | 70.66 | 0.00 | 0.00 |
Annual Sum or Average | 416.33 | 126.14 | 129.66 | 58.12 | 71.54 | 0.00 | 0.00 |
Minimum of Months | 328.81 | 5.13 | 67.45 | 1.59 | 65.39 | 0.00 | 0.00 |
Maximum of Months | 576.73 | 305.16 | 209.36 | 137.47 | 80.38 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 774.77 | 594.27 | 349.51 | 210.55 | 138.96 | 0.00 | 0.00 |
February | 820.19 | 488.64 | 337.21 | 187.49 | 149.71 | 0.00 | 0.00 |
March | 853.75 | 300.54 | 298.22 | 137.46 | 160.76 | 0.00 | 0.00 |
April | 837.73 | 118.74 | 217.96 | 72.79 | 145.17 | 0.00 | 0.00 |
May | 775.86 | 29.62 | 151.73 | 17.05 | 134.67 | 0.00 | 0.00 |
June | 771.90 | 28.27 | 134.90 | 4.13 | 130.77 | 0.00 | 0.00 |
July | 695.45 | 8.03 | 140.04 | 3.17 | 136.87 | 0.00 | 0.00 |
August | 660.29 | 22.03 | 149.96 | 10.61 | 139.35 | 0.00 | 0.00 |
September | 732.34 | 70.39 | 203.76 | 57.64 | 146.13 | 0.00 | 0.00 |
October | 1104.56 | 246.76 | 343.56 | 193.63 | 149.93 | 0.00 | 0.00 |
November | 1159.08 | 439.99 | 418.71 | 274.94 | 143.77 | 0.00 | 0.00 |
December | 867.69 | 596.40 | 371.93 | 230.62 | 141.31 | 0.00 | 0.00 |
Annual Sum or Average | 837.53 | 244.19 | 259.33 | 116.25 | 143.08 | 0.00 | 0.00 |
Minimum of Months | 660.29 | 8.03 | 134.90 | 3.17 | 130.77 | 0.00 | 0.00 |
Maximum of Months | 1159.08 | 596.40 | 418.71 | 274.94 | 160.76 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 386.31 | 296.82 | 174.76 | 105.27 | 69.48 | 0.00 | 0.00 |
February | 408.97 | 243.81 | 168.60 | 93.75 | 74.86 | 0.00 | 0.00 |
March | 426.90 | 148.67 | 149.11 | 68.73 | 80.38 | 0.00 | 0.00 |
April | 421.25 | 57.50 | 108.98 | 36.40 | 72.58 | 0.00 | 0.00 |
May | 393.07 | 13.54 | 75.86 | 8.53 | 67.34 | 0.00 | 0.00 |
June | 391.95 | 13.24 | 67.45 | 2.06 | 65.39 | 0.00 | 0.00 |
July | 352.94 | 3.37 | 70.02 | 1.59 | 68.43 | 0.00 | 0.00 |
August | 333.96 | 9.80 | 74.98 | 5.31 | 69.67 | 0.00 | 0.00 |
September | 368.29 | 32.89 | 101.88 | 28.82 | 73.06 | 0.00 | 0.00 |
October | 552.96 | 121.15 | 171.78 | 96.81 | 74.97 | 0.00 | 0.00 |
November | 579.01 | 218.52 | 209.36 | 137.47 | 71.89 | 0.00 | 0.00 |
December | 432.89 | 297.86 | 185.97 | 115.31 | 70.66 | 0.00 | 0.00 |
Annual Sum or Average | 420.59 | 120.87 | 129.66 | 58.12 | 71.54 | 0.00 | 0.00 |
Minimum of Months | 333.96 | 3.37 | 67.45 | 1.59 | 65.39 | 0.00 | 0.00 |
Maximum of Months | 579.01 | 297.86 | 209.36 | 137.47 | 80.38 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 386.96 | 295.38 | 174.76 | 105.27 | 69.48 | 0.00 | 0.00 |
February | 409.52 | 242.67 | 168.60 | 93.75 | 74.86 | 0.00 | 0.00 |
March | 427.31 | 147.86 | 149.11 | 68.73 | 80.38 | 0.00 | 0.00 |
April | 421.71 | 56.97 | 108.98 | 36.40 | 72.58 | 0.00 | 0.00 |
May | 393.70 | 13.28 | 75.86 | 8.53 | 67.34 | 0.00 | 0.00 |
June | 392.68 | 13.05 | 67.45 | 2.06 | 65.39 | 0.00 | 0.00 |
July | 353.62 | 3.26 | 70.02 | 1.59 | 68.43 | 0.00 | 0.00 |
August | 334.50 | 9.58 | 74.98 | 5.31 | 69.67 | 0.00 | 0.00 |
September | 368.65 | 32.44 | 101.88 | 28.82 | 73.06 | 0.00 | 0.00 |
October | 553.23 | 120.61 | 171.78 | 96.81 | 74.97 | 0.00 | 0.00 |
November | 579.36 | 217.81 | 209.36 | 137.47 | 71.89 | 0.00 | 0.00 |
December | 433.46 | 296.82 | 185.97 | 115.31 | 70.66 | 0.00 | 0.00 |
Annual Sum or Average | 421.11 | 120.26 | 129.66 | 58.12 | 71.54 | 0.00 | 0.00 |
Minimum of Months | 334.50 | 3.26 | 67.45 | 1.59 | 65.39 | 0.00 | 0.00 |
Maximum of Months | 579.36 | 296.82 | 209.36 | 137.47 | 80.38 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 388.47 | 291.42 | 174.76 | 105.27 | 69.48 | 0.00 | 0.00 |
February | 410.85 | 239.36 | 168.60 | 93.75 | 74.86 | 0.00 | 0.00 |
March | 427.95 | 146.01 | 149.11 | 68.73 | 80.38 | 0.00 | 0.00 |
April | 421.75 | 56.41 | 108.98 | 36.40 | 72.58 | 0.00 | 0.00 |
May | 393.20 | 13.31 | 75.86 | 8.53 | 67.34 | 0.00 | 0.00 |
June | 391.83 | 13.09 | 67.45 | 2.06 | 65.39 | 0.00 | 0.00 |
July | 352.43 | 3.34 | 70.02 | 1.59 | 68.43 | 0.00 | 0.00 |
August | 333.58 | 9.82 | 74.98 | 5.31 | 69.67 | 0.00 | 0.00 |
September | 368.18 | 32.81 | 101.88 | 28.82 | 73.06 | 0.00 | 0.00 |
October | 553.12 | 120.49 | 171.78 | 96.81 | 74.97 | 0.00 | 0.00 |
November | 579.86 | 216.50 | 209.36 | 137.47 | 71.89 | 0.00 | 0.00 |
December | 434.86 | 293.84 | 185.97 | 115.31 | 70.66 | 0.00 | 0.00 |
Annual Sum or Average | 421.22 | 119.15 | 129.66 | 58.12 | 71.54 | 0.00 | 0.00 |
Minimum of Months | 333.58 | 3.34 | 67.45 | 1.59 | 65.39 | 0.00 | 0.00 |
Maximum of Months | 579.86 | 293.84 | 209.36 | 137.47 | 80.38 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 391.24 | 278.05 | 174.76 | 105.27 | 69.48 | 0.00 | 0.00 |
February | 413.43 | 226.59 | 168.60 | 93.75 | 74.86 | 0.00 | 0.00 |
March | 428.20 | 138.40 | 149.11 | 68.73 | 80.38 | 0.00 | 0.00 |
April | 417.80 | 54.85 | 108.98 | 36.40 | 72.58 | 0.00 | 0.00 |
May | 385.20 | 14.18 | 75.86 | 8.53 | 67.34 | 0.00 | 0.00 |
June | 381.39 | 13.88 | 67.45 | 2.06 | 65.39 | 0.00 | 0.00 |
July | 340.69 | 4.39 | 70.02 | 1.59 | 68.43 | 0.00 | 0.00 |
August | 323.94 | 12.37 | 74.98 | 5.31 | 69.67 | 0.00 | 0.00 |
September | 362.04 | 37.24 | 101.88 | 28.82 | 73.06 | 0.00 | 0.00 |
October | 549.44 | 122.12 | 171.78 | 96.81 | 74.97 | 0.00 | 0.00 |
November | 579.46 | 212.09 | 209.36 | 137.47 | 71.89 | 0.00 | 0.00 |
December | 437.51 | 282.96 | 185.97 | 115.31 | 70.66 | 0.00 | 0.00 |
Annual Sum or Average | 417.37 | 115.92 | 129.66 | 58.12 | 71.54 | 0.00 | 0.00 |
Minimum of Months | 323.94 | 4.39 | 67.45 | 1.59 | 65.39 | 0.00 | 0.00 |
Maximum of Months | 579.46 | 282.96 | 209.36 | 137.47 | 80.38 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.202509E+10 | 0.174013E+10 | 0.938061E+09 | 0.565095E+09 | 0.372966E+09 | 0.00 | 0.00 |
February | 0.195862E+10 | 0.124921E+10 | 0.817449E+09 | 0.454521E+09 | 0.362928E+09 | 0.00 | 0.00 |
March | 0.227337E+10 | 0.820380E+09 | 0.800392E+09 | 0.368937E+09 | 0.431454E+09 | 0.00 | 0.00 |
April | 0.218474E+10 | 0.296024E+09 | 0.566105E+09 | 0.189061E+09 | 0.377044E+09 | 0.00 | 0.00 |
May | 0.212617E+10 | 68871306.57 | 0.407219E+09 | 45763680.18 | 0.361455E+09 | 0.00 | 0.00 |
June | 0.203926E+10 | 61523373.63 | 0.350378E+09 | 10722313.38 | 0.339656E+09 | 0.00 | 0.00 |
July | 0.192762E+10 | 20654573.51 | 0.375851E+09 | 8514949.57 | 0.367337E+09 | 0.00 | 0.00 |
August | 0.179083E+10 | 55097959.48 | 0.402482E+09 | 28483036.03 | 0.373999E+09 | 0.00 | 0.00 |
September | 0.190006E+10 | 0.171601E+09 | 0.529242E+09 | 0.149705E+09 | 0.379537E+09 | 0.00 | 0.00 |
October | 0.295287E+10 | 0.648189E+09 | 0.922082E+09 | 0.519678E+09 | 0.402404E+09 | 0.00 | 0.00 |
November | 0.298665E+10 | 0.117398E+10 | 0.108754E+10 | 0.714120E+09 | 0.373419E+09 | 0.00 | 0.00 |
December | 0.228474E+10 | 0.169947E+10 | 0.998231E+09 | 0.618961E+09 | 0.379270E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.264500E+11 | 0.800513E+10 | 0.819503E+10 | 0.367356E+10 | 0.452147E+10 | 0.00 | 0.00 |
Minimum of Months | 0.179083E+10 | 20654573.51 | 0.350378E+09 | 8514949.57 | 0.339656E+09 | 0.00 | 0.00 |
Maximum of Months | 0.298665E+10 | 0.174013E+10 | 0.108754E+10 | 0.714120E+09 | 0.431454E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.100339E+10 | 0.882641E+09 | 0.469030E+09 | 0.282547E+09 | 0.186483E+09 | 0.00 | 0.00 |
February | 0.972379E+09 | 0.633250E+09 | 0.408725E+09 | 0.227260E+09 | 0.181464E+09 | 0.00 | 0.00 |
March | 0.113478E+10 | 0.413631E+09 | 0.400196E+09 | 0.184469E+09 | 0.215727E+09 | 0.00 | 0.00 |
April | 0.110099E+10 | 0.146867E+09 | 0.283053E+09 | 94530732.80 | 0.188522E+09 | 0.00 | 0.00 |
May | 0.108256E+10 | 32042123.79 | 0.203609E+09 | 22881840.09 | 0.180728E+09 | 0.00 | 0.00 |
June | 0.104292E+10 | 28537604.40 | 0.175189E+09 | 5361156.69 | 0.169828E+09 | 0.00 | 0.00 |
July | 0.987407E+09 | 8556464.99 | 0.187926E+09 | 4257474.78 | 0.183668E+09 | 0.00 | 0.00 |
August | 0.914246E+09 | 23474702.87 | 0.201241E+09 | 14241518.01 | 0.187000E+09 | 0.00 | 0.00 |
September | 0.962558E+09 | 78286564.17 | 0.264621E+09 | 74852379.67 | 0.189769E+09 | 0.00 | 0.00 |
October | 0.148139E+10 | 0.318355E+09 | 0.461041E+09 | 0.259839E+09 | 0.201202E+09 | 0.00 | 0.00 |
November | 0.149132E+10 | 0.586281E+09 | 0.543769E+09 | 0.357060E+09 | 0.186709E+09 | 0.00 | 0.00 |
December | 0.113526E+10 | 0.857287E+09 | 0.499115E+09 | 0.309481E+09 | 0.189635E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.133092E+11 | 0.400921E+10 | 0.409752E+10 | 0.183678E+10 | 0.226073E+10 | 0.00 | 0.00 |
Minimum of Months | 0.914246E+09 | 8556464.99 | 0.175189E+09 | 4257474.78 | 0.169828E+09 | 0.00 | 0.00 |
Maximum of Months | 0.149132E+10 | 0.882641E+09 | 0.543769E+09 | 0.357060E+09 | 0.215727E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.101370E+10 | 0.843983E+09 | 0.468067E+09 | 0.281967E+09 | 0.186100E+09 | 0.00 | 0.00 |
February | 0.976686E+09 | 0.620980E+09 | 0.407885E+09 | 0.226794E+09 | 0.181091E+09 | 0.00 | 0.00 |
March | 0.113344E+10 | 0.425133E+09 | 0.399374E+09 | 0.184090E+09 | 0.215284E+09 | 0.00 | 0.00 |
April | 0.107955E+10 | 0.165158E+09 | 0.282471E+09 | 94336624.52 | 0.188135E+09 | 0.00 | 0.00 |
May | 0.103707E+10 | 43569662.02 | 0.203191E+09 | 22834854.79 | 0.180356E+09 | 0.00 | 0.00 |
June | 0.995545E+09 | 38652545.92 | 0.174829E+09 | 5350148.16 | 0.169479E+09 | 0.00 | 0.00 |
July | 0.933014E+09 | 13675966.16 | 0.187540E+09 | 4248732.54 | 0.183291E+09 | 0.00 | 0.00 |
August | 0.881220E+09 | 34996036.34 | 0.200828E+09 | 14212274.65 | 0.186616E+09 | 0.00 | 0.00 |
September | 0.946728E+09 | 0.100726E+09 | 0.264078E+09 | 74698678.68 | 0.189379E+09 | 0.00 | 0.00 |
October | 0.147535E+10 | 0.344200E+09 | 0.460094E+09 | 0.259305E+09 | 0.200789E+09 | 0.00 | 0.00 |
November | 0.149204E+10 | 0.591184E+09 | 0.542653E+09 | 0.356327E+09 | 0.186326E+09 | 0.00 | 0.00 |
December | 0.114286E+10 | 0.832716E+09 | 0.498090E+09 | 0.308845E+09 | 0.189245E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.131072E+11 | 0.405497E+10 | 0.408910E+10 | 0.183301E+10 | 0.225609E+10 | 0.00 | 0.00 |
Minimum of Months | 0.881220E+09 | 13675966.16 | 0.174829E+09 | 4248732.54 | 0.169479E+09 | 0.00 | 0.00 |
Maximum of Months | 0.149204E+10 | 0.843983E+09 | 0.542653E+09 | 0.356327E+09 | 0.215284E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.101886E+10 | 0.827840E+09 | 0.468067E+09 | 0.281967E+09 | 0.186100E+09 | 0.00 | 0.00 |
February | 0.979298E+09 | 0.613089E+09 | 0.407885E+09 | 0.226794E+09 | 0.181091E+09 | 0.00 | 0.00 |
March | 0.113439E+10 | 0.422859E+09 | 0.399374E+09 | 0.184090E+09 | 0.215284E+09 | 0.00 | 0.00 |
April | 0.107900E+10 | 0.167149E+09 | 0.282471E+09 | 94336624.52 | 0.188135E+09 | 0.00 | 0.00 |
May | 0.103366E+10 | 46233728.41 | 0.203191E+09 | 22834854.79 | 0.180356E+09 | 0.00 | 0.00 |
June | 0.991396E+09 | 40422409.95 | 0.174829E+09 | 5350148.16 | 0.169479E+09 | 0.00 | 0.00 |
July | 0.927934E+09 | 14764379.98 | 0.187540E+09 | 4248732.54 | 0.183291E+09 | 0.00 | 0.00 |
August | 0.878844E+09 | 36734616.59 | 0.200828E+09 | 14212274.65 | 0.186616E+09 | 0.00 | 0.00 |
September | 0.946356E+09 | 0.103531E+09 | 0.264078E+09 | 74698678.68 | 0.189379E+09 | 0.00 | 0.00 |
October | 0.147546E+10 | 0.345510E+09 | 0.460094E+09 | 0.259305E+09 | 0.200789E+09 | 0.00 | 0.00 |
November | 0.149339E+10 | 0.587247E+09 | 0.542653E+09 | 0.356327E+09 | 0.186326E+09 | 0.00 | 0.00 |
December | 0.114678E+10 | 0.821649E+09 | 0.498090E+09 | 0.308845E+09 | 0.189245E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.131054E+11 | 0.402703E+10 | 0.408910E+10 | 0.183301E+10 | 0.225609E+10 | 0.00 | 0.00 |
Minimum of Months | 0.878844E+09 | 14764379.98 | 0.174829E+09 | 4248732.54 | 0.169479E+09 | 0.00 | 0.00 |
Maximum of Months | 0.149339E+10 | 0.827840E+09 | 0.542653E+09 | 0.356327E+09 | 0.215284E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.102290E+10 | 0.817335E+09 | 0.468067E+09 | 0.281967E+09 | 0.186100E+09 | 0.00 | 0.00 |
February | 0.981595E+09 | 0.606800E+09 | 0.407885E+09 | 0.226794E+09 | 0.181091E+09 | 0.00 | 0.00 |
March | 0.113584E+10 | 0.418023E+09 | 0.399374E+09 | 0.184090E+09 | 0.215284E+09 | 0.00 | 0.00 |
April | 0.108042E+10 | 0.163940E+09 | 0.282471E+09 | 94336624.52 | 0.188135E+09 | 0.00 | 0.00 |
May | 0.103559E+10 | 44498113.19 | 0.203191E+09 | 22834854.79 | 0.180356E+09 | 0.00 | 0.00 |
June | 0.994120E+09 | 39320792.46 | 0.174829E+09 | 5350148.16 | 0.169479E+09 | 0.00 | 0.00 |
July | 0.929893E+09 | 13735112.13 | 0.187540E+09 | 4248732.54 | 0.183291E+09 | 0.00 | 0.00 |
August | 0.880676E+09 | 34906560.87 | 0.200828E+09 | 14212274.65 | 0.186616E+09 | 0.00 | 0.00 |
September | 0.947188E+09 | 0.100339E+09 | 0.264078E+09 | 74698678.68 | 0.189379E+09 | 0.00 | 0.00 |
October | 0.147625E+10 | 0.341993E+09 | 0.460094E+09 | 0.259305E+09 | 0.200789E+09 | 0.00 | 0.00 |
November | 0.149488E+10 | 0.582703E+09 | 0.542653E+09 | 0.356327E+09 | 0.186326E+09 | 0.00 | 0.00 |
December | 0.114990E+10 | 0.814378E+09 | 0.498090E+09 | 0.308845E+09 | 0.189245E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.131293E+11 | 0.397797E+10 | 0.408910E+10 | 0.183301E+10 | 0.225609E+10 | 0.00 | 0.00 |
Minimum of Months | 0.880676E+09 | 13735112.13 | 0.174829E+09 | 4248732.54 | 0.169479E+09 | 0.00 | 0.00 |
Maximum of Months | 0.149488E+10 | 0.817335E+09 | 0.542653E+09 | 0.356327E+09 | 0.215284E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.207514E+10 | 0.159168E+10 | 0.936134E+09 | 0.563934E+09 | 0.372200E+09 | 0.00 | 0.00 |
February | 0.198419E+10 | 0.118213E+10 | 0.815770E+09 | 0.453588E+09 | 0.362183E+09 | 0.00 | 0.00 |
March | 0.228670E+10 | 0.804965E+09 | 0.798748E+09 | 0.368180E+09 | 0.430569E+09 | 0.00 | 0.00 |
April | 0.217140E+10 | 0.307777E+09 | 0.564943E+09 | 0.188673E+09 | 0.376270E+09 | 0.00 | 0.00 |
May | 0.207806E+10 | 79333701.24 | 0.406383E+09 | 45669709.59 | 0.360713E+09 | 0.00 | 0.00 |
June | 0.200076E+10 | 73274158.35 | 0.349659E+09 | 10700296.31 | 0.338959E+09 | 0.00 | 0.00 |
July | 0.186270E+10 | 21498668.61 | 0.375080E+09 | 8497465.07 | 0.366582E+09 | 0.00 | 0.00 |
August | 0.176853E+10 | 59012975.64 | 0.401656E+09 | 28424549.30 | 0.373231E+09 | 0.00 | 0.00 |
September | 0.189821E+10 | 0.182462E+09 | 0.528155E+09 | 0.149397E+09 | 0.378758E+09 | 0.00 | 0.00 |
October | 0.295844E+10 | 0.660921E+09 | 0.920188E+09 | 0.518611E+09 | 0.401578E+09 | 0.00 | 0.00 |
November | 0.300433E+10 | 0.114045E+10 | 0.108531E+10 | 0.712653E+09 | 0.372652E+09 | 0.00 | 0.00 |
December | 0.232402E+10 | 0.159739E+10 | 0.996181E+09 | 0.617690E+09 | 0.378491E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.264125E+11 | 0.770090E+10 | 0.817820E+10 | 0.366602E+10 | 0.451218E+10 | 0.00 | 0.00 |
Minimum of Months | 0.176853E+10 | 21498668.61 | 0.349659E+09 | 8497465.07 | 0.338959E+09 | 0.00 | 0.00 |
Maximum of Months | 0.300433E+10 | 0.159739E+10 | 0.108531E+10 | 0.712653E+09 | 0.430569E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.103470E+10 | 0.794995E+09 | 0.468067E+09 | 0.281967E+09 | 0.186100E+09 | 0.00 | 0.00 |
February | 0.989375E+09 | 0.589835E+09 | 0.407885E+09 | 0.226794E+09 | 0.181091E+09 | 0.00 | 0.00 |
March | 0.114342E+10 | 0.398203E+09 | 0.399374E+09 | 0.184090E+09 | 0.215284E+09 | 0.00 | 0.00 |
April | 0.109187E+10 | 0.149032E+09 | 0.282471E+09 | 94336624.52 | 0.188135E+09 | 0.00 | 0.00 |
May | 0.105279E+10 | 36260343.49 | 0.203191E+09 | 22834854.79 | 0.180356E+09 | 0.00 | 0.00 |
June | 0.101592E+10 | 34325691.21 | 0.174829E+09 | 5350148.16 | 0.169479E+09 | 0.00 | 0.00 |
July | 0.945325E+09 | 9022796.85 | 0.187540E+09 | 4248732.54 | 0.183291E+09 | 0.00 | 0.00 |
August | 0.894489E+09 | 26236366.13 | 0.200828E+09 | 14212274.65 | 0.186616E+09 | 0.00 | 0.00 |
September | 0.954620E+09 | 85244034.50 | 0.264078E+09 | 74698678.68 | 0.189379E+09 | 0.00 | 0.00 |
October | 0.148104E+10 | 0.324501E+09 | 0.460094E+09 | 0.259305E+09 | 0.200789E+09 | 0.00 | 0.00 |
November | 0.150079E+10 | 0.566413E+09 | 0.542653E+09 | 0.356327E+09 | 0.186326E+09 | 0.00 | 0.00 |
December | 0.115945E+10 | 0.797796E+09 | 0.498090E+09 | 0.308845E+09 | 0.189245E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.132638E+11 | 0.381187E+10 | 0.408910E+10 | 0.183301E+10 | 0.225609E+10 | 0.00 | 0.00 |
Minimum of Months | 0.894489E+09 | 9022796.85 | 0.174829E+09 | 4248732.54 | 0.169479E+09 | 0.00 | 0.00 |
Maximum of Months | 0.150079E+10 | 0.797796E+09 | 0.542653E+09 | 0.356327E+09 | 0.215284E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.103644E+10 | 0.791155E+09 | 0.468067E+09 | 0.281967E+09 | 0.186100E+09 | 0.00 | 0.00 |
February | 0.990702E+09 | 0.587063E+09 | 0.407885E+09 | 0.226794E+09 | 0.181091E+09 | 0.00 | 0.00 |
March | 0.114450E+10 | 0.396032E+09 | 0.399374E+09 | 0.184090E+09 | 0.215284E+09 | 0.00 | 0.00 |
April | 0.109307E+10 | 0.147657E+09 | 0.282471E+09 | 94336624.52 | 0.188135E+09 | 0.00 | 0.00 |
May | 0.105449E+10 | 35569071.97 | 0.203191E+09 | 22834854.79 | 0.180356E+09 | 0.00 | 0.00 |
June | 0.101782E+10 | 33835191.92 | 0.174829E+09 | 5350148.16 | 0.169479E+09 | 0.00 | 0.00 |
July | 0.947127E+09 | 8728590.56 | 0.187540E+09 | 4248732.54 | 0.183291E+09 | 0.00 | 0.00 |
August | 0.895923E+09 | 25661808.56 | 0.200828E+09 | 14212274.65 | 0.186616E+09 | 0.00 | 0.00 |
September | 0.955539E+09 | 84088703.61 | 0.264078E+09 | 74698678.68 | 0.189379E+09 | 0.00 | 0.00 |
October | 0.148178E+10 | 0.323031E+09 | 0.460094E+09 | 0.259305E+09 | 0.200789E+09 | 0.00 | 0.00 |
November | 0.150170E+10 | 0.564569E+09 | 0.542653E+09 | 0.356327E+09 | 0.186326E+09 | 0.00 | 0.00 |
December | 0.116098E+10 | 0.794990E+09 | 0.498090E+09 | 0.308845E+09 | 0.189245E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.132801E+11 | 0.379238E+10 | 0.408910E+10 | 0.183301E+10 | 0.225609E+10 | 0.00 | 0.00 |
Minimum of Months | 0.895923E+09 | 8728590.56 | 0.174829E+09 | 4248732.54 | 0.169479E+09 | 0.00 | 0.00 |
Maximum of Months | 0.150170E+10 | 0.794990E+09 | 0.542653E+09 | 0.356327E+09 | 0.215284E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.104049E+10 | 0.780537E+09 | 0.468067E+09 | 0.281967E+09 | 0.186100E+09 | 0.00 | 0.00 |
February | 0.993935E+09 | 0.579054E+09 | 0.407885E+09 | 0.226794E+09 | 0.181091E+09 | 0.00 | 0.00 |
March | 0.114623E+10 | 0.391068E+09 | 0.399374E+09 | 0.184090E+09 | 0.215284E+09 | 0.00 | 0.00 |
April | 0.109318E+10 | 0.146213E+09 | 0.282471E+09 | 94336624.52 | 0.188135E+09 | 0.00 | 0.00 |
May | 0.105314E+10 | 35648018.18 | 0.203191E+09 | 22834854.79 | 0.180356E+09 | 0.00 | 0.00 |
June | 0.101562E+10 | 33941863.40 | 0.174829E+09 | 5350148.16 | 0.169479E+09 | 0.00 | 0.00 |
July | 0.943954E+09 | 8949911.85 | 0.187540E+09 | 4248732.54 | 0.183291E+09 | 0.00 | 0.00 |
August | 0.893458E+09 | 26292483.32 | 0.200828E+09 | 14212274.65 | 0.186616E+09 | 0.00 | 0.00 |
September | 0.954332E+09 | 85041063.84 | 0.264078E+09 | 74698678.68 | 0.189379E+09 | 0.00 | 0.00 |
October | 0.148147E+10 | 0.322716E+09 | 0.460094E+09 | 0.259305E+09 | 0.200789E+09 | 0.00 | 0.00 |
November | 0.150300E+10 | 0.561175E+09 | 0.542653E+09 | 0.356327E+09 | 0.186326E+09 | 0.00 | 0.00 |
December | 0.116474E+10 | 0.787018E+09 | 0.498090E+09 | 0.308845E+09 | 0.189245E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.132836E+11 | 0.375765E+10 | 0.408910E+10 | 0.183301E+10 | 0.225609E+10 | 0.00 | 0.00 |
Minimum of Months | 0.893458E+09 | 8949911.85 | 0.174829E+09 | 4248732.54 | 0.169479E+09 | 0.00 | 0.00 |
Maximum of Months | 0.150300E+10 | 0.787018E+09 | 0.542653E+09 | 0.356327E+09 | 0.215284E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.104788E+10 | 0.744726E+09 | 0.468067E+09 | 0.281967E+09 | 0.186100E+09 | 0.00 | 0.00 |
February | 0.100017E+10 | 0.548162E+09 | 0.407885E+09 | 0.226794E+09 | 0.181091E+09 | 0.00 | 0.00 |
March | 0.114689E+10 | 0.370680E+09 | 0.399374E+09 | 0.184090E+09 | 0.215284E+09 | 0.00 | 0.00 |
April | 0.108293E+10 | 0.142183E+09 | 0.282471E+09 | 94336624.52 | 0.188135E+09 | 0.00 | 0.00 |
May | 0.103173E+10 | 37992613.08 | 0.203191E+09 | 22834854.79 | 0.180356E+09 | 0.00 | 0.00 |
June | 0.988556E+09 | 35966009.15 | 0.174829E+09 | 5350148.16 | 0.169479E+09 | 0.00 | 0.00 |
July | 0.912508E+09 | 11753651.81 | 0.187540E+09 | 4248732.54 | 0.183291E+09 | 0.00 | 0.00 |
August | 0.867630E+09 | 33127574.08 | 0.200828E+09 | 14212274.65 | 0.186616E+09 | 0.00 | 0.00 |
September | 0.938417E+09 | 96522710.66 | 0.264078E+09 | 74698678.68 | 0.189379E+09 | 0.00 | 0.00 |
October | 0.147162E+10 | 0.327075E+09 | 0.460094E+09 | 0.259305E+09 | 0.200789E+09 | 0.00 | 0.00 |
November | 0.150197E+10 | 0.549744E+09 | 0.542653E+09 | 0.356327E+09 | 0.186326E+09 | 0.00 | 0.00 |
December | 0.117182E+10 | 0.757868E+09 | 0.498090E+09 | 0.308845E+09 | 0.189245E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.131621E+11 | 0.365580E+10 | 0.408910E+10 | 0.183301E+10 | 0.225609E+10 | 0.00 | 0.00 |
Minimum of Months | 0.867630E+09 | 11753651.81 | 0.174829E+09 | 4248732.54 | 0.169479E+09 | 0.00 | 0.00 |
Maximum of Months | 0.150197E+10 | 0.757868E+09 | 0.542653E+09 | 0.356327E+09 | 0.215284E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 13.39 | 10.37 | 7.87 | 1.20 | 0.37 | 63.33 | 149.51 | 0.00 |
February | 16.97 | 12.77 | 9.69 | 1.81 | 4.63 | 75.94 | 163.32 | 0.01 |
March | 22.37 | 15.59 | 11.23 | 1.86 | 10.07 | 92.70 | 193.23 | 0.00 |
April | 29.13 | 18.31 | 11.93 | 1.64 | 16.17 | 89.20 | 259.84 | 0.01 |
May | 32.98 | 21.95 | 16.72 | 2.17 | 21.14 | 97.31 | 248.85 | 0.02 |
June | 33.59 | 24.37 | 20.62 | 1.55 | 23.45 | 107.22 | 203.36 | 0.06 |
July | 31.67 | 26.28 | 24.51 | 2.27 | 24.88 | 132.35 | 83.14 | 0.02 |
August | 30.03 | 26.31 | 25.11 | 1.75 | 23.81 | 127.44 | 60.46 | 0.00 |
September | 28.75 | 24.69 | 23.21 | 1.33 | 20.22 | 105.62 | 105.60 | 0.08 |
October | 25.09 | 18.73 | 15.36 | 0.77 | 12.83 | 75.09 | 190.08 | 0.00 |
November | 19.63 | 14.45 | 10.99 | 0.66 | 5.78 | 58.54 | 201.10 | 0.00 |
December | 14.52 | 10.87 | 7.89 | 0.97 | 0.94 | 60.91 | 153.60 | 0.01 |
Annual Sum or Average | 24.88 | 18.75 | 15.46 | 1.50 | 13.74 | 90.59 | 167.44 | 0.02 |
Minimum of Months | 13.39 | 10.37 | 7.87 | 0.66 | 0.37 | 58.54 | 60.46 | 0.00 |
Maximum of Months | 33.59 | 26.31 | 25.11 | 2.27 | 24.88 | 132.35 | 259.84 | 0.08 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 23.60 | 12-JAN-14:00 | 14.18 | 7.40 | 3.80 | 8.15 | 163.00 | 476.00 |
February | 27.10 | 22-FEB-14:00 | 16.17 | 9.10 | 1.50 | 15.39 | 225.00 | 451.00 |
March | 35.60 | 28-MAR-14:00 | 18.47 | 7.70 | 0.00 | 19.52 | 182.00 | 699.00 |
April | 40.30 | 15-APR-14:00 | 20.63 | 10.00 | 6.70 | 28.43 | 201.00 | 649.50 |
May | 44.50 | 03-MAY-14:00 | 20.60 | 5.30 | 2.80 | 28.91 | 150.00 | 809.00 |
June | 44.60 | 07-JUN-15:00 | 21.49 | 9.10 | 3.10 | 28.43 | 167.00 | 640.50 |
July | 40.40 | 02-JUL-15:00 | 26.34 | 21.60 | 2.10 | 29.87 | 200.00 | 545.50 |
August | 37.30 | 07-AUG-14:00 | 26.56 | 22.90 | 3.00 | 29.87 | 311.00 | 370.00 |
September | 37.50 | 17-SEP-19:00 | 27.67 | 24.60 | 0.20 | 28.59 | 0.00 | 0.00 |
October | 36.40 | 02-OCT-14:20 | 21.02 | 13.00 | 1.80 | 21.61 | 187.33 | 678.83 |
November | 30.30 | 04-NOV-13:00 | 17.14 | 8.90 | 1.10 | 14.84 | 155.00 | 710.00 |
December | 24.60 | 28-DEC-13:00 | 15.28 | 8.90 | 2.80 | 10.88 | 181.50 | 535.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 23.60 | 14.18 | 5.30 | 0.00 | 8.15 | 0.00 | 0.00 | |
Maximum of Months | 44.60 | 27.67 | 24.60 | 6.70 | 29.87 | 311.00 | 809.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 4.80 | 05-JAN-06:00 | 4.73 | 4.60 | 0.00 | -10.2 | 0.00 | 0.00 |
February | 6.90 | 02-FEB-05:00 | 6.67 | 6.50 | 0.00 | -7.8 | 0.00 | 0.00 |
March | 13.30 | 01-MAR-03:00 | 10.55 | 8.30 | 0.80 | -1.4 | 0.00 | 0.00 |
April | 17.40 | 11-APR-04:00 | 13.57 | 10.90 | 0.00 | 3.06 | 0.00 | 0.00 |
May | 22.70 | 13-MAY-04:00 | 20.32 | 19.30 | 2.10 | 20.40 | 0.00 | 0.00 |
June | 23.30 | 18-JUN-04:00 | 21.80 | 21.20 | 2.70 | 17.75 | 0.00 | 0.00 |
July | 23.20 | 19-JUL-02:00 | 23.20 | 23.20 | 2.30 | 15.39 | 0.00 | 0.00 |
August | 23.40 | 15-AUG-23:00 | 22.91 | 22.80 | 2.40 | 21.78 | 0.00 | 0.00 |
September | 23.00 | 27-SEP-04:00 | 20.73 | 19.70 | 0.00 | 10.30 | 0.00 | 0.00 |
October | 15.50 | 31-OCT-04:00 | 14.07 | 13.20 | 0.00 | 1.80 | 0.00 | 0.00 |
November | 9.50 | 27-NOV-05:00 | 8.75 | 8.10 | 0.00 | -5.0 | 0.00 | 0.00 |
December | 5.00 | 21-DEC-04:00 | 4.08 | 3.00 | 0.00 | -10.5 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 4.80 | 4.08 | 3.00 | 0.00 | -10.5 | 0.00 | 0.00 | |
Maximum of Months | 23.40 | 23.20 | 23.20 | 2.70 | 21.78 | 0.00 | 0.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 15.61 | 17-JAN-14:00 | 18.20 | 14.10 | 1.00 | 11.07 | 198.00 | 56.50 |
February | 18.14 | 25-FEB-16:00 | 21.20 | 16.60 | 5.90 | 10.88 | 107.50 | 156.50 |
March | 21.36 | 10-MAR-18:49 | 29.25 | 17.73 | 2.10 | 21.44 | 0.00 | 0.00 |
April | 23.40 | 18-APR-13:00 | 37.10 | 17.80 | 5.70 | 23.49 | 233.50 | 671.50 |
May | 27.40 | 22-MAY-22:00 | 29.40 | 26.80 | 0.00 | 20.40 | 0.00 | 0.00 |
June | 28.92 | 28-JUN-12:00 | 34.40 | 27.50 | 1.00 | 25.49 | 332.50 | 501.50 |
July | 29.17 | 01-JUL-16:00 | 37.20 | 26.80 | 2.30 | 25.66 | 196.00 | 196.00 |
August | 29.16 | 27-AUG-15:00 | 35.10 | 27.40 | 1.30 | 29.55 | 256.00 | 129.00 |
September | 28.10 | 14-SEP-16:00 | 33.70 | 26.40 | 1.40 | 26.48 | 122.50 | 108.50 |
October | 23.05 | 06-OCT-10:00 | 28.60 | 20.80 | 1.30 | 20.22 | 327.00 | 348.50 |
November | 18.91 | 08-NOV-17:10 | 27.55 | 14.47 | 0.17 | 16.67 | 28.00 | 65.33 |
December | 15.64 | 29-DEC-19:00 | 16.80 | 14.90 | 4.80 | 13.54 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 15.61 | 16.80 | 14.10 | 0.00 | 10.88 | 0.00 | 0.00 | |
Maximum of Months | 29.17 | 37.20 | 27.50 | 5.90 | 29.55 | 332.50 | 671.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 14.10 | 17-JAN-13:00 | 17.80 | 15.47 | 0.90 | 9.72 | 260.50 | 81.50 |
February | 16.60 | 25-FEB-16:00 | 21.20 | 18.14 | 5.90 | 10.88 | 107.50 | 156.50 |
March | 18.30 | 10-MAR-19:00 | 27.70 | 21.24 | 2.10 | 21.44 | 0.00 | 0.00 |
April | 19.30 | 26-APR-23:10 | 28.53 | 22.03 | 0.00 | 15.60 | 0.00 | 0.00 |
May | 26.80 | 22-MAY-22:00 | 29.40 | 27.40 | 0.00 | 20.40 | 0.00 | 0.00 |
June | 27.50 | 28-JUN-12:00 | 34.40 | 28.92 | 1.00 | 25.49 | 332.50 | 501.50 |
July | 27.30 | 18-JUL-06:19 | 29.10 | 27.69 | 1.17 | 26.48 | 20.00 | 0.00 |
August | 28.80 | 12-AUG-07:00 | 29.10 | 28.83 | 2.90 | 26.81 | 113.00 | 6.50 |
September | 26.50 | 12-SEP-14:00 | 30.50 | 27.38 | 0.90 | 25.99 | 260.00 | 20.00 |
October | 21.10 | 06-OCT-08:00 | 25.50 | 22.40 | 0.30 | 17.21 | 239.00 | 159.00 |
November | 16.30 | 08-NOV-21:19 | 20.10 | 17.58 | 0.00 | 10.95 | 0.00 | 0.00 |
December | 14.90 | 29-DEC-20:10 | 16.72 | 15.59 | 4.73 | 13.13 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 14.10 | 16.72 | 15.47 | 0.00 | 9.72 | 0.00 | 0.00 | |
Maximum of Months | 28.80 | 34.40 | 28.92 | 5.90 | 26.81 | 332.50 | 501.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 20.92 | 27.26 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 21.74 | 33.91 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 24.21 | 44.04 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 27.79 | 55.91 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 31.48 | 58.43 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 34.27 | 54.82 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 35.42 | 39.75 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 34.60 | 34.68 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 32.04 | 35.55 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 28.44 | 39.44 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 24.77 | 33.85 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 22.02 | 26.79 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 28.18 | 40.37 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 20.92 | 26.79 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 35.42 | 58.43 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK1
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.301637E+09 | -186908991.3 | 0.00 | 0.00 | 744.00 | 0.00 | -114727814.8 | 58.99 | 0.00 | 0.00 |
February | 0.268689E+09 | -166088780.4 | 0.00 | 0.00 | 672.00 | 0.00 | -102600249.1 | 58.99 | 0.00 | 0.00 |
March | 0.286687E+09 | -174347985.7 | 0.00 | 0.00 | 744.00 | 0.00 | -112339240.7 | 58.99 | 0.00 | 0.00 |
April | 0.257261E+09 | -149644869.1 | 0.00 | 0.00 | 720.00 | 0.00 | -107615761.6 | 58.99 | 0.00 | 0.00 |
May | 0.246810E+09 | -136557879.1 | 0.00 | 0.00 | 744.00 | 0.00 | -110252546.2 | 58.99 | 0.00 | 0.00 |
June | 0.226147E+09 | -119767321.5 | 0.00 | 0.00 | 720.00 | 0.00 | -106379361.9 | 58.99 | 0.00 | 0.00 |
July | 0.225583E+09 | -115766279.4 | 0.00 | 0.00 | 744.00 | 0.00 | -109817037.5 | 58.99 | 0.00 | 0.00 |
August | 0.232180E+09 | -122191748.6 | 0.00 | 0.00 | 744.00 | 0.00 | -109988268.7 | 58.98 | 0.00 | 0.00 |
September | 0.236327E+09 | -129450323.3 | 0.00 | 0.00 | 720.00 | 0.00 | -106876953.5 | 58.99 | 0.00 | 0.00 |
October | 0.261400E+09 | -150073453.1 | 0.00 | 0.00 | 744.00 | 0.00 | -111326081.2 | 58.99 | 0.00 | 0.00 |
November | 0.270999E+09 | -162151991.5 | 0.00 | 0.00 | 720.00 | 0.00 | -108846710.0 | 58.99 | 0.00 | 0.00 |
December | 0.295679E+09 | -181762396.5 | 0.00 | 0.00 | 744.00 | 0.00 | -113916645.5 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.310940E+10 | -.179471E+10 | 8760.00 | -.131469E+10 | 58.99 | |||||
Minimum of Months | 0.225583E+09 | -186908991.3 | 0.00 | 0.00 | 672.00 | 0.00 | -114727814.8 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.301637E+09 | -115766279.4 | 0.00 | 0.00 | 744.00 | 0.00 | -102600249.1 | 58.99 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK2
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.301145E+09 | -186920923.8 | 0.00 | 0.00 | 744.00 | 0.00 | -114224224.6 | 58.99 | 0.00 | 0.00 |
February | 0.268366E+09 | -166092334.5 | 0.00 | 0.00 | 672.00 | 0.00 | -102273640.0 | 58.99 | 0.00 | 0.00 |
March | 0.286500E+09 | -174342677.9 | 0.00 | 0.00 | 744.00 | 0.00 | -112156868.2 | 58.99 | 0.00 | 0.00 |
April | 0.257241E+09 | -149646399.2 | 0.00 | 0.00 | 720.00 | 0.00 | -107594281.8 | 58.99 | 0.00 | 0.00 |
May | 0.246917E+09 | -136560467.6 | 0.00 | 0.00 | 744.00 | 0.00 | -110356420.9 | 58.99 | 0.00 | 0.00 |
June | 0.226319E+09 | -119755676.9 | 0.00 | 0.00 | 720.00 | 0.00 | -106562873.1 | 58.99 | 0.00 | 0.00 |
July | 0.225772E+09 | -115752665.2 | 0.00 | 0.00 | 744.00 | 0.00 | -110019794.4 | 58.99 | 0.00 | 0.00 |
August | 0.232402E+09 | -122181492.5 | 0.00 | 0.00 | 744.00 | 0.00 | -110220861.7 | 58.99 | 0.00 | 0.00 |
September | 0.236495E+09 | -129448795.2 | 0.00 | 0.00 | 720.00 | 0.00 | -107046498.9 | 58.99 | 0.00 | 0.00 |
October | 0.261456E+09 | -150069698.7 | 0.00 | 0.00 | 744.00 | 0.00 | -111386621.0 | 58.99 | 0.00 | 0.00 |
November | 0.270914E+09 | -162151104.8 | 0.00 | 0.00 | 720.00 | 0.00 | -108763176.5 | 58.99 | 0.00 | 0.00 |
December | 0.295340E+09 | -181755571.2 | 0.00 | 0.00 | 744.00 | 0.00 | -113583976.1 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.310887E+10 | -.179468E+10 | 8760.00 | -.131419E+10 | 58.99 | |||||
Minimum of Months | 0.225772E+09 | -186920923.8 | 0.00 | 0.00 | 672.00 | 0.00 | -114224224.6 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.301145E+09 | -115752665.2 | 0.00 | 0.00 | 744.00 | 0.00 | -102273640.0 | 58.99 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK3
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.279589E+09 | -164388762.8 | 0.00 | 0.00 | 744.00 | 0.00 | -115199846.5 | 58.99 | 0.00 | 0.00 |
February | 0.248369E+09 | -146176004.6 | 0.00 | 0.00 | 672.00 | 0.00 | -102193436.8 | 59.00 | 0.00 | 0.00 |
March | 0.266529E+09 | -155689830.1 | 0.00 | 0.00 | 744.00 | 0.00 | -110838959.3 | 58.99 | 0.00 | 0.00 |
April | 0.236603E+09 | -131502652.8 | 0.00 | 0.00 | 720.00 | 0.00 | -105100446.3 | 58.99 | 0.00 | 0.00 |
May | 0.228470E+09 | -121163289.0 | 0.00 | 0.00 | 744.00 | 0.00 | -107307099.7 | 58.99 | 0.00 | 0.00 |
June | 0.210336E+09 | -106729770.0 | 0.00 | 0.00 | 720.00 | 0.00 | -103606451.4 | 58.98 | 0.00 | 0.00 |
July | 0.207973E+09 | -101128492.7 | 0.00 | 0.00 | 744.00 | 0.00 | -106844016.8 | 58.99 | 0.00 | 0.00 |
August | 0.216765E+09 | -109182693.1 | 0.00 | 0.00 | 744.00 | 0.00 | -107581962.1 | 59.00 | 0.00 | 0.00 |
September | 0.218266E+09 | -113736060.2 | 0.00 | 0.00 | 720.00 | 0.00 | -104529682.5 | 58.99 | 0.00 | 0.00 |
October | 0.241260E+09 | -131984658.2 | 0.00 | 0.00 | 744.00 | 0.00 | -109275440.1 | 59.00 | 0.00 | 0.00 |
November | 0.251092E+09 | -143136098.6 | 0.00 | 0.00 | 720.00 | 0.00 | -107955889.5 | 59.00 | 0.00 | 0.00 |
December | 0.272685E+09 | -158642350.7 | 0.00 | 0.00 | 744.00 | 0.00 | -114042181.2 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.287794E+10 | -.158346E+10 | 8760.00 | -.129448E+10 | 58.99 | |||||
Minimum of Months | 0.207973E+09 | -164388762.8 | 0.00 | 0.00 | 672.00 | 0.00 | -115199846.5 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.279589E+09 | -101128492.7 | 0.00 | 0.00 | 744.00 | 0.00 | -102193436.8 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK4
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.280085E+09 | -164362509.2 | 0.00 | 0.00 | 744.00 | 0.00 | -115722483.0 | 58.99 | 0.00 | 0.00 |
February | 0.248609E+09 | -146214819.2 | 0.00 | 0.00 | 672.00 | 0.00 | -102394508.0 | 58.98 | 0.00 | 0.00 |
March | 0.266591E+09 | -155705254.1 | 0.00 | 0.00 | 744.00 | 0.00 | -110885744.6 | 58.99 | 0.00 | 0.00 |
April | 0.236518E+09 | -131514240.4 | 0.00 | 0.00 | 720.00 | 0.00 | -105003984.1 | 58.99 | 0.00 | 0.00 |
May | 0.228297E+09 | -121171552.9 | 0.00 | 0.00 | 744.00 | 0.00 | -107125578.8 | 58.99 | 0.00 | 0.00 |
June | 0.210185E+09 | -106721359.9 | 0.00 | 0.00 | 720.00 | 0.00 | -103463891.7 | 58.99 | 0.00 | 0.00 |
July | 0.207779E+09 | -101066534.4 | 0.00 | 0.00 | 744.00 | 0.00 | -106712541.7 | 59.00 | 0.00 | 0.00 |
August | 0.216633E+09 | -109194671.0 | 0.00 | 0.00 | 744.00 | 0.00 | -107438371.5 | 59.00 | 0.00 | 0.00 |
September | 0.218162E+09 | -113738698.6 | 0.00 | 0.00 | 720.00 | 0.00 | -104423114.9 | 58.99 | 0.00 | 0.00 |
October | 0.241216E+09 | -131984304.8 | 0.00 | 0.00 | 744.00 | 0.00 | -109231825.7 | 59.00 | 0.00 | 0.00 |
November | 0.251206E+09 | -143139704.5 | 0.00 | 0.00 | 720.00 | 0.00 | -108066571.7 | 59.00 | 0.00 | 0.00 |
December | 0.273030E+09 | -158653889.1 | 0.00 | 0.00 | 744.00 | 0.00 | -114376475.2 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.287831E+10 | -.158347E+10 | 8760.00 | -.129485E+10 | 58.99 | |||||
Minimum of Months | 0.207779E+09 | -164362509.2 | 0.00 | 0.00 | 672.00 | 0.00 | -115722483.0 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.280085E+09 | -101066534.4 | 0.00 | 0.00 | 744.00 | 0.00 | -102394508.0 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK5
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.272128E+09 | -155350116.6 | 0.00 | 0.00 | 744.00 | 0.00 | -116777492.6 | 58.99 | 0.00 | 0.00 |
February | 0.241358E+09 | -138249360.9 | 0.00 | 0.00 | 672.00 | 0.00 | -103108349.5 | 58.99 | 0.00 | 0.00 |
March | 0.258989E+09 | -147297548.9 | 0.00 | 0.00 | 744.00 | 0.00 | -111691351.5 | 59.00 | 0.00 | 0.00 |
April | 0.230195E+09 | -124440968.8 | 0.00 | 0.00 | 720.00 | 0.00 | -105753658.8 | 58.99 | 0.00 | 0.00 |
May | 0.222349E+09 | -114573102.0 | 0.00 | 0.00 | 744.00 | 0.00 | -107776046.1 | 59.00 | 0.00 | 0.00 |
June | 0.205064E+09 | -100961447.6 | 0.00 | 0.00 | 720.00 | 0.00 | -104102921.1 | 59.00 | 0.00 | 0.00 |
July | 0.202688E+09 | -95655249.0 | 0.00 | 0.00 | 744.00 | 0.00 | -107032862.7 | 58.99 | 0.00 | 0.00 |
August | 0.211314E+09 | -103348902.9 | 0.00 | 0.00 | 744.00 | 0.00 | -107964719.2 | 58.99 | 0.00 | 0.00 |
September | 0.212586E+09 | -107638272.9 | 0.00 | 0.00 | 720.00 | 0.00 | -104947316.5 | 58.99 | 0.00 | 0.00 |
October | 0.234547E+09 | -124759292.7 | 0.00 | 0.00 | 744.00 | 0.00 | -109787895.1 | 58.99 | 0.00 | 0.00 |
November | 0.243823E+09 | -135180506.6 | 0.00 | 0.00 | 720.00 | 0.00 | -108642666.8 | 59.00 | 0.00 | 0.00 |
December | 0.265178E+09 | -150031127.4 | 0.00 | 0.00 | 744.00 | 0.00 | -115146615.7 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.280022E+10 | -.149749E+10 | 8760.00 | -.130273E+10 | 58.99 | |||||
Minimum of Months | 0.202688E+09 | -155350116.6 | 0.00 | 0.00 | 672.00 | 0.00 | -116777492.6 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.272128E+09 | -95655249.0 | 0.00 | 0.00 | 744.00 | 0.00 | -103108349.5 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK6
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.272173E+09 | -155347622.9 | 0.00 | 0.00 | 744.00 | 0.00 | -116824987.0 | 58.99 | 0.00 | 0.00 |
February | 0.241404E+09 | -138247430.1 | 0.00 | 0.00 | 672.00 | 0.00 | -103156439.9 | 58.99 | 0.00 | 0.00 |
March | 0.259103E+09 | -147275929.2 | 0.00 | 0.00 | 744.00 | 0.00 | -111827118.1 | 59.01 | 0.00 | 0.00 |
April | 0.230368E+09 | -124451380.1 | 0.00 | 0.00 | 720.00 | 0.00 | -105916243.3 | 58.99 | 0.00 | 0.00 |
May | 0.222553E+09 | -114591632.5 | 0.00 | 0.00 | 744.00 | 0.00 | -107961704.0 | 58.99 | 0.00 | 0.00 |
June | 0.205301E+09 | -101008547.6 | 0.00 | 0.00 | 720.00 | 0.00 | -104292524.8 | 58.98 | 0.00 | 0.00 |
July | 0.202901E+09 | -95605008.0 | 0.00 | 0.00 | 744.00 | 0.00 | -107295786.8 | 59.00 | 0.00 | 0.00 |
August | 0.211537E+09 | -103374114.2 | 0.00 | 0.00 | 744.00 | 0.00 | -108162644.8 | 58.98 | 0.00 | 0.00 |
September | 0.212771E+09 | -107630496.5 | 0.00 | 0.00 | 720.00 | 0.00 | -105140333.0 | 58.99 | 0.00 | 0.00 |
October | 0.234705E+09 | -124753898.0 | 0.00 | 0.00 | 744.00 | 0.00 | -109951345.3 | 58.99 | 0.00 | 0.00 |
November | 0.243928E+09 | -135186064.2 | 0.00 | 0.00 | 720.00 | 0.00 | -108742331.1 | 59.00 | 0.00 | 0.00 |
December | 0.265205E+09 | -150038970.8 | 0.00 | 0.00 | 744.00 | 0.00 | -115166068.4 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.280195E+10 | -.149751E+10 | 8760.00 | -.130444E+10 | 58.99 | |||||
Minimum of Months | 0.202901E+09 | -155347622.9 | 0.00 | 0.00 | 672.00 | 0.00 | -116824987.0 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.272173E+09 | -95605008.0 | 0.00 | 0.00 | 744.00 | 0.00 | -103156439.9 | 59.01 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK7
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.272298E+09 | -155345811.9 | 0.00 | 0.00 | 744.00 | 0.00 | -116951906.0 | 59.00 | 0.00 | 0.00 |
February | 0.241489E+09 | -138246784.3 | 0.00 | 0.00 | 672.00 | 0.00 | -103242317.9 | 58.99 | 0.00 | 0.00 |
March | 0.259173E+09 | -147278058.4 | 0.00 | 0.00 | 744.00 | 0.00 | -111894876.8 | 59.01 | 0.00 | 0.00 |
April | 0.230424E+09 | -124461377.2 | 0.00 | 0.00 | 720.00 | 0.00 | -105962799.7 | 58.99 | 0.00 | 0.00 |
May | 0.222599E+09 | -114609278.5 | 0.00 | 0.00 | 744.00 | 0.00 | -107990149.1 | 58.98 | 0.00 | 0.00 |
June | 0.205350E+09 | -101004825.0 | 0.00 | 0.00 | 720.00 | 0.00 | -104345568.5 | 58.99 | 0.00 | 0.00 |
July | 0.202947E+09 | -95658672.8 | 0.00 | 0.00 | 744.00 | 0.00 | -107288127.4 | 58.98 | 0.00 | 0.00 |
August | 0.211562E+09 | -103316651.3 | 0.00 | 0.00 | 744.00 | 0.00 | -108245749.6 | 58.99 | 0.00 | 0.00 |
September | 0.212811E+09 | -107624933.7 | 0.00 | 0.00 | 720.00 | 0.00 | -105186056.9 | 58.99 | 0.00 | 0.00 |
October | 0.234764E+09 | -124765170.1 | 0.00 | 0.00 | 744.00 | 0.00 | -109998646.7 | 58.99 | 0.00 | 0.00 |
November | 0.243968E+09 | -135245081.4 | 0.00 | 0.00 | 720.00 | 0.00 | -108723396.1 | 58.98 | 0.00 | 0.00 |
December | 0.265303E+09 | -150042223.7 | 0.00 | 0.00 | 744.00 | 0.00 | -115260923.5 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.280269E+10 | -.149760E+10 | 8760.00 | -.130509E+10 | 58.99 | |||||
Minimum of Months | 0.202947E+09 | -155345811.9 | 0.00 | 0.00 | 672.00 | 0.00 | -116951906.0 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.272298E+09 | -95658672.8 | 0.00 | 0.00 | 744.00 | 0.00 | -103242317.9 | 59.01 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 319.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 303.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 364.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 379.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 406.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 386.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 379.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 372.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 344.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 347.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 317.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 315.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4237.50 | ||||||||||
Minimum of Months | 303.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 406.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 84037705.96 | 7811.15 | 02-JAN-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 2117101.17 | 1957.99 | 02-FEB-08:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 11954943.64 | 3957.83 | 21-DEC-08:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 98109750.76 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 84037705.96 | 7811.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 18527877.56 | 3469.92 | 03-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1272012.35 | 852.10 | 21-DEC-08:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 19799889.91 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18527877.56 | 3469.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_3:3_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.125564E+09 | 10072.72 | 02-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 2540061.43 | 1115.91 | 02-FEB-07:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 12867546.33 | 1644.35 | 21-DEC-07:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.140971E+09 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.125564E+09 | 10072.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_4:4_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.179235E+09 | 19237.84 | 02-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5965407.47 | 1540.73 | 02-FEB-07:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 19025651.47 | 2289.92 | 23-DEC-07:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.204226E+09 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.179235E+09 | 19237.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_5:5_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.225323E+09 | 24990.76 | 02-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 9791336.47 | 1587.71 | 02-FEB-07:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 26111954.10 | 2529.04 | 23-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.261226E+09 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.225323E+09 | 24990.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_6:6_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.372970E+09 | 73310.12 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 21180591.90 | 4525.54 | 02-FEB-08:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 48259919.21 | 7763.42 | 21-DEC-08:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.442410E+09 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.372970E+09 | 73310.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_7:7_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.189449E+09 | 38385.92 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 8761415.65 | 2138.54 | 02-FEB-08:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 22192490.20 | 3803.02 | 23-DEC-08:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.220403E+09 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.189449E+09 | 38385.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_8:8_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.201905E+09 | 38246.90 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 10438175.55 | 2109.44 | 02-FEB-08:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 24667856.38 | 3944.98 | 21-DEC-08:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.237011E+09 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.201905E+09 | 38246.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_9:9_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.244419E+09 | 38324.73 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 18276680.89 | 3062.97 | 02-FEB-08:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 34282291.24 | 3756.27 | 23-DEC-08:63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.296978E+09 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.244419E+09 | 38324.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_10:10_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.364993E+09 | 41962.10 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 57693482.72 | 7726.88 | 11-FEB-08:65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 68354855.75 | 13311.91 | 23-DEC-08:63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.491041E+09 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.364993E+09 | 41962.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.807262E+10 | 0.737426E+10 | 15902.62 | 12-JAN-15:00 | 15429.81 | 0.00 |
February | 0.00 | 0.00 | 0.155245E+11 | 0.138937E+11 | 23218.58 | 22-FEB-15:00 | 21931.86 | 0.00 |
March | 0.00 | 0.00 | 0.312202E+11 | 0.277869E+11 | 68949.96 | 11-MAR-08:62 | 54789.56 | 0.00 |
April | 0.00 | 0.00 | 0.463633E+11 | 0.423636E+11 | 69415.09 | 26-APR-07:02 | 53836.20 | 0.00 |
May | 0.00 | 0.00 | 0.645267E+11 | 0.530268E+11 | 74598.86 | 24-MAY-07:02 | 40188.15 | 0.00 |
June | 0.00 | 0.00 | 0.719015E+11 | 0.527668E+11 | 76215.72 | 26-JUN-07:01 | 37306.61 | 0.00 |
July | 0.00 | 0.00 | 0.808897E+11 | 0.501368E+11 | 76403.94 | 26-JUL-07:01 | 36571.45 | 0.00 |
August | 0.00 | 0.00 | 0.798542E+11 | 0.467962E+11 | 76372.66 | 10-AUG-07:01 | 37624.28 | 0.00 |
September | 0.00 | 0.00 | 0.671213E+11 | 0.422705E+11 | 75835.78 | 03-SEP-07:01 | 38856.17 | 0.00 |
October | 0.00 | 0.00 | 0.454035E+11 | 0.371437E+11 | 72347.39 | 12-OCT-07:02 | 44433.45 | 0.00 |
November | 0.00 | 0.00 | 0.264202E+11 | 0.234646E+11 | 51426.37 | 09-NOV-08:62 | 39175.65 | 0.00 |
December | 0.00 | 0.00 | 0.115365E+11 | 0.103943E+11 | 18772.77 | 28-DEC-15:00 | 17448.08 | 0.00 |
Annual Sum or Average | 0.548834E+12 | 0.407418E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.807262E+10 | 0.737426E+10 | 15902.62 | 15429.81 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.808897E+11 | 0.530268E+11 | 76403.94 | 54789.56 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.502962E+10 | 0.463707E+10 | 8145.40 | 12-JAN-15:00 | 7911.65 | 0.00 |
February | 0.00 | 0.00 | 0.837796E+10 | 0.759645E+10 | 12476.89 | 25-FEB-08:63 | 10358.30 | 0.00 |
March | 0.00 | 0.00 | 0.154796E+11 | 0.139876E+11 | 34503.65 | 30-MAR-07:02 | 28460.13 | 0.00 |
April | 0.00 | 0.00 | 0.220269E+11 | 0.203569E+11 | 34605.50 | 03-APR-07:02 | 28382.92 | 0.00 |
May | 0.00 | 0.00 | 0.303539E+11 | 0.252917E+11 | 36842.34 | 24-MAY-07:02 | 22819.65 | 0.00 |
June | 0.00 | 0.00 | 0.335792E+11 | 0.250132E+11 | 37290.90 | 26-JUN-07:01 | 22020.56 | 0.00 |
July | 0.00 | 0.00 | 0.375878E+11 | 0.237211E+11 | 37778.70 | 25-JUL-07:01 | 20905.94 | 0.00 |
August | 0.00 | 0.00 | 0.372318E+11 | 0.222069E+11 | 37699.38 | 10-AUG-07:01 | 21791.66 | 0.00 |
September | 0.00 | 0.00 | 0.311053E+11 | 0.200289E+11 | 37129.58 | 03-SEP-07:01 | 22767.01 | 0.00 |
October | 0.00 | 0.00 | 0.216139E+11 | 0.180245E+11 | 35659.06 | 12-OCT-07:02 | 25196.03 | 0.00 |
November | 0.00 | 0.00 | 0.133519E+11 | 0.120491E+11 | 23863.87 | 09-NOV-08:62 | 20169.78 | 0.00 |
December | 0.00 | 0.00 | 0.676263E+10 | 0.616780E+10 | 9509.12 | 28-DEC-14:40 | 8873.40 | 0.00 |
Annual Sum or Average | 0.262501E+12 | 0.199081E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.502962E+10 | 0.463707E+10 | 8145.40 | 7911.65 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.375878E+11 | 0.252917E+11 | 37778.70 | 28460.13 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.243803E+10 | 0.226616E+10 | 7076.08 | 12-JAN-15:00 | 6861.86 | 0.00 |
February | 0.00 | 0.00 | 0.536805E+10 | 0.486070E+10 | 10943.42 | 22-FEB-14:00 | 10335.78 | 0.00 |
March | 0.00 | 0.00 | 0.115536E+11 | 0.103645E+11 | 34152.15 | 11-MAR-07:02 | 24759.02 | 0.00 |
April | 0.00 | 0.00 | 0.173988E+11 | 0.159386E+11 | 34409.27 | 17-APR-06:01 | 25524.87 | 0.00 |
May | 0.00 | 0.00 | 0.249063E+11 | 0.204399E+11 | 36399.23 | 23-MAY-06:01 | 19598.57 | 0.00 |
June | 0.00 | 0.00 | 0.277439E+11 | 0.201652E+11 | 37239.42 | 25-JUN-07:02 | 16925.29 | 0.00 |
July | 0.00 | 0.00 | 0.305442E+11 | 0.184727E+11 | 37272.94 | 19-JUL-06:01 | 16271.59 | 0.00 |
August | 0.00 | 0.00 | 0.308340E+11 | 0.175928E+11 | 37353.00 | 21-AUG-06:01 | 14788.88 | 0.00 |
September | 0.00 | 0.00 | 0.251238E+11 | 0.155123E+11 | 37362.26 | 10-SEP-07:02 | 15353.97 | 0.00 |
October | 0.00 | 0.00 | 0.168869E+11 | 0.138578E+11 | 35426.93 | 12-OCT-06:02 | 20738.91 | 0.00 |
November | 0.00 | 0.00 | 0.973250E+10 | 0.877635E+10 | 17365.36 | 09-NOV-07:03 | 12360.05 | 0.00 |
December | 0.00 | 0.00 | 0.385582E+10 | 0.352241E+10 | 8505.03 | 28-DEC-14:00 | 7974.23 | 0.00 |
Annual Sum or Average | 0.206386E+12 | 0.151769E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.243803E+10 | 0.226616E+10 | 7076.08 | 6861.86 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.308340E+11 | 0.204399E+11 | 37362.26 | 25524.87 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.222506E+10 | 0.207021E+10 | 6882.94 | 12-JAN-15:00 | 6670.60 | 0.00 |
February | 0.00 | 0.00 | 0.519634E+10 | 0.470362E+10 | 10813.69 | 22-FEB-14:00 | 10207.80 | 0.00 |
March | 0.00 | 0.00 | 0.114554E+11 | 0.102712E+11 | 34089.04 | 11-MAR-07:02 | 24677.56 | 0.00 |
April | 0.00 | 0.00 | 0.173984E+11 | 0.159343E+11 | 34372.91 | 17-APR-06:01 | 25604.68 | 0.00 |
May | 0.00 | 0.00 | 0.249703E+11 | 0.204943E+11 | 36341.87 | 23-MAY-06:01 | 19618.94 | 0.00 |
June | 0.00 | 0.00 | 0.278043E+11 | 0.202134E+11 | 37180.13 | 25-JUN-07:02 | 16927.76 | 0.00 |
July | 0.00 | 0.00 | 0.306231E+11 | 0.185330E+11 | 37206.70 | 26-JUL-06:01 | 17469.00 | 0.00 |
August | 0.00 | 0.00 | 0.308625E+11 | 0.176115E+11 | 37286.45 | 21-AUG-06:01 | 14821.07 | 0.00 |
September | 0.00 | 0.00 | 0.251303E+11 | 0.155148E+11 | 37295.69 | 10-SEP-07:02 | 15306.54 | 0.00 |
October | 0.00 | 0.00 | 0.168644E+11 | 0.138346E+11 | 35365.28 | 12-OCT-06:02 | 20685.44 | 0.00 |
November | 0.00 | 0.00 | 0.960719E+10 | 0.865851E+10 | 16746.78 | 09-NOV-07:03 | 11889.54 | 0.00 |
December | 0.00 | 0.00 | 0.364906E+10 | 0.333097E+10 | 8308.09 | 28-DEC-14:00 | 7783.50 | 0.00 |
Annual Sum or Average | 0.205786E+12 | 0.151170E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.222506E+10 | 0.207021E+10 | 6882.94 | 6670.60 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.308625E+11 | 0.204943E+11 | 37295.69 | 25604.68 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.203927E+10 | 0.190001E+10 | 6705.57 | 12-JAN-15:00 | 6496.75 | 0.00 |
February | 0.00 | 0.00 | 0.501048E+10 | 0.453613E+10 | 10666.87 | 22-FEB-14:00 | 10065.90 | 0.00 |
March | 0.00 | 0.00 | 0.112551E+11 | 0.100887E+11 | 34022.41 | 11-MAR-07:02 | 24511.97 | 0.00 |
April | 0.00 | 0.00 | 0.172481E+11 | 0.157922E+11 | 34318.91 | 17-APR-06:01 | 25525.86 | 0.00 |
May | 0.00 | 0.00 | 0.248432E+11 | 0.203814E+11 | 36279.38 | 23-MAY-06:01 | 19478.46 | 0.00 |
June | 0.00 | 0.00 | 0.276696E+11 | 0.201015E+11 | 37122.25 | 26-JUN-06:01 | 15442.14 | 0.00 |
July | 0.00 | 0.00 | 0.304965E+11 | 0.184359E+11 | 37155.75 | 19-JUL-06:01 | 16128.35 | 0.00 |
August | 0.00 | 0.00 | 0.307067E+11 | 0.174948E+11 | 37235.57 | 21-AUG-06:01 | 14724.86 | 0.00 |
September | 0.00 | 0.00 | 0.249802E+11 | 0.153979E+11 | 37244.80 | 10-SEP-07:02 | 15158.14 | 0.00 |
October | 0.00 | 0.00 | 0.167044E+11 | 0.136952E+11 | 35305.32 | 12-OCT-06:02 | 20545.30 | 0.00 |
November | 0.00 | 0.00 | 0.942220E+10 | 0.848966E+10 | 15182.22 | 09-NOV-07:03 | 10728.82 | 0.00 |
December | 0.00 | 0.00 | 0.345394E+10 | 0.315148E+10 | 8127.42 | 28-DEC-14:00 | 7610.49 | 0.00 |
Annual Sum or Average | 0.203830E+12 | 0.149465E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.203927E+10 | 0.190001E+10 | 6705.57 | 6496.75 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.307067E+11 | 0.203814E+11 | 37244.80 | 25525.86 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.322584E+10 | 0.298759E+10 | 12165.39 | 12-JAN-15:10 | 11632.82 | 0.00 |
February | 0.00 | 0.00 | 0.884571E+10 | 0.794564E+10 | 19838.12 | 22-FEB-14:00 | 18514.12 | 0.00 |
March | 0.00 | 0.00 | 0.206934E+11 | 0.184246E+11 | 62956.49 | 11-MAR-08:62 | 46951.25 | 0.00 |
April | 0.00 | 0.00 | 0.318256E+11 | 0.291395E+11 | 63965.78 | 17-APR-07:01 | 47755.88 | 0.00 |
May | 0.00 | 0.00 | 0.460631E+11 | 0.376853E+11 | 67206.05 | 21-MAY-08:61 | 40486.75 | 0.00 |
June | 0.00 | 0.00 | 0.512657E+11 | 0.371610E+11 | 69312.70 | 25-JUN-08:61 | 31063.88 | 0.00 |
July | 0.00 | 0.00 | 0.561280E+11 | 0.336787E+11 | 69298.65 | 23-JUL-08:61 | 28292.12 | 0.00 |
August | 0.00 | 0.00 | 0.569051E+11 | 0.320959E+11 | 69516.66 | 21-AUG-07:01 | 27648.76 | 0.00 |
September | 0.00 | 0.00 | 0.458909E+11 | 0.281038E+11 | 69548.19 | 04-SEP-08:61 | 29461.28 | 0.00 |
October | 0.00 | 0.00 | 0.308172E+11 | 0.251082E+11 | 65381.04 | 12-OCT-07:02 | 39549.35 | 0.00 |
November | 0.00 | 0.00 | 0.171407E+11 | 0.152944E+11 | 38042.59 | 09-NOV-08:62 | 28034.33 | 0.00 |
December | 0.00 | 0.00 | 0.572691E+10 | 0.516937E+10 | 14944.95 | 28-DEC-14:00 | 13817.56 | 0.00 |
Annual Sum or Average | 0.374528E+12 | 0.272794E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.322584E+10 | 0.298759E+10 | 12165.39 | 11632.82 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.569051E+11 | 0.376853E+11 | 69548.19 | 47755.88 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.161549E+10 | 0.150096E+10 | 6269.76 | 12-JAN-15:10 | 6015.52 | 0.00 |
February | 0.00 | 0.00 | 0.454123E+10 | 0.409048E+10 | 10273.72 | 22-FEB-14:00 | 9610.48 | 0.00 |
March | 0.00 | 0.00 | 0.106785E+11 | 0.952977E+10 | 32893.71 | 11-MAR-08:62 | 24560.76 | 0.00 |
April | 0.00 | 0.00 | 0.164477E+11 | 0.150759E+11 | 33439.34 | 17-APR-07:01 | 24972.07 | 0.00 |
May | 0.00 | 0.00 | 0.238237E+11 | 0.195112E+11 | 35124.06 | 21-MAY-08:61 | 21113.38 | 0.00 |
June | 0.00 | 0.00 | 0.264974E+11 | 0.192304E+11 | 36227.43 | 25-JUN-08:61 | 16116.56 | 0.00 |
July | 0.00 | 0.00 | 0.290129E+11 | 0.174363E+11 | 36220.09 | 23-JUL-08:61 | 14704.15 | 0.00 |
August | 0.00 | 0.00 | 0.294002E+11 | 0.166098E+11 | 36334.04 | 21-AUG-07:01 | 14274.85 | 0.00 |
September | 0.00 | 0.00 | 0.237249E+11 | 0.145532E+11 | 36350.52 | 04-SEP-08:61 | 15266.28 | 0.00 |
October | 0.00 | 0.00 | 0.159328E+11 | 0.130085E+11 | 34146.73 | 12-OCT-07:02 | 20760.19 | 0.00 |
November | 0.00 | 0.00 | 0.885389E+10 | 0.792078E+10 | 17643.70 | 09-NOV-08:62 | 13061.63 | 0.00 |
December | 0.00 | 0.00 | 0.292910E+10 | 0.265119E+10 | 7703.43 | 28-DEC-14:00 | 7142.17 | 0.00 |
Annual Sum or Average | 0.193458E+12 | 0.141119E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.161549E+10 | 0.150096E+10 | 6269.76 | 6015.52 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.294002E+11 | 0.195112E+11 | 36350.52 | 24972.07 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.155248E+10 | 0.144291E+10 | 6188.39 | 12-JAN-15:10 | 5935.51 | 0.00 |
February | 0.00 | 0.00 | 0.445819E+10 | 0.401528E+10 | 10190.37 | 22-FEB-14:00 | 9529.41 | 0.00 |
March | 0.00 | 0.00 | 0.105776E+11 | 0.943647E+10 | 32773.05 | 11-MAR-08:62 | 24422.53 | 0.00 |
April | 0.00 | 0.00 | 0.163569E+11 | 0.149893E+11 | 33317.21 | 17-APR-07:01 | 24850.17 | 0.00 |
May | 0.00 | 0.00 | 0.237284E+11 | 0.194256E+11 | 34996.89 | 21-MAY-08:61 | 21003.92 | 0.00 |
June | 0.00 | 0.00 | 0.263999E+11 | 0.191470E+11 | 36099.44 | 25-JUN-08:61 | 16013.52 | 0.00 |
July | 0.00 | 0.00 | 0.289169E+11 | 0.173601E+11 | 36092.12 | 23-JUL-08:61 | 14621.05 | 0.00 |
August | 0.00 | 0.00 | 0.292997E+11 | 0.165318E+11 | 36205.66 | 21-AUG-07:01 | 14193.17 | 0.00 |
September | 0.00 | 0.00 | 0.236340E+11 | 0.144811E+11 | 36222.08 | 04-SEP-08:61 | 15186.90 | 0.00 |
October | 0.00 | 0.00 | 0.158454E+11 | 0.129308E+11 | 34026.02 | 12-OCT-07:02 | 20635.31 | 0.00 |
November | 0.00 | 0.00 | 0.876935E+10 | 0.784264E+10 | 17001.21 | 09-NOV-08:62 | 12555.76 | 0.00 |
December | 0.00 | 0.00 | 0.285488E+10 | 0.258351E+10 | 7621.03 | 28-DEC-14:00 | 7062.91 | 0.00 |
Annual Sum or Average | 0.192394E+12 | 0.140186E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.155248E+10 | 0.144291E+10 | 6188.39 | 5935.51 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.292997E+11 | 0.194256E+11 | 36222.08 | 24850.17 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.142967E+10 | 0.133017E+10 | 6027.52 | 12-JAN-15:10 | 5780.35 | 0.00 |
February | 0.00 | 0.00 | 0.428823E+10 | 0.386389E+10 | 10065.83 | 22-FEB-14:00 | 9411.10 | 0.00 |
March | 0.00 | 0.00 | 0.104108E+11 | 0.928623E+10 | 32820.01 | 11-MAR-08:62 | 24348.36 | 0.00 |
April | 0.00 | 0.00 | 0.163069E+11 | 0.149435E+11 | 33373.41 | 17-APR-07:01 | 24853.72 | 0.00 |
May | 0.00 | 0.00 | 0.237467E+11 | 0.194457E+11 | 35057.83 | 21-MAY-08:61 | 21003.64 | 0.00 |
June | 0.00 | 0.00 | 0.264410E+11 | 0.191866E+11 | 36171.30 | 25-JUN-08:61 | 15962.10 | 0.00 |
July | 0.00 | 0.00 | 0.289842E+11 | 0.174169E+11 | 36163.97 | 23-JUL-08:61 | 14618.87 | 0.00 |
August | 0.00 | 0.00 | 0.293707E+11 | 0.165889E+11 | 36277.74 | 21-AUG-07:01 | 14206.20 | 0.00 |
September | 0.00 | 0.00 | 0.236756E+11 | 0.145168E+11 | 36294.19 | 04-SEP-08:61 | 15206.22 | 0.00 |
October | 0.00 | 0.00 | 0.158278E+11 | 0.129176E+11 | 34085.64 | 12-OCT-07:02 | 20614.98 | 0.00 |
November | 0.00 | 0.00 | 0.865557E+10 | 0.774058E+10 | 15337.05 | 09-NOV-08:62 | 11285.29 | 0.00 |
December | 0.00 | 0.00 | 0.270313E+10 | 0.244691E+10 | 7481.34 | 28-DEC-14:00 | 6931.46 | 0.00 |
Annual Sum or Average | 0.191840E+12 | 0.139684E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.142967E+10 | 0.133017E+10 | 6027.52 | 5780.35 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.293707E+11 | 0.194457E+11 | 36294.19 | 24853.72 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.146200E+10 | 0.137118E+10 | 6176.59 | 12-JAN-15:10 | 5968.32 | 0.00 |
February | 0.00 | 0.00 | 0.438037E+10 | 0.397913E+10 | 10647.27 | 22-FEB-14:00 | 10025.19 | 0.00 |
March | 0.00 | 0.00 | 0.108272E+11 | 0.972139E+10 | 27387.36 | 11-MAR-08:62 | 20224.19 | 0.00 |
April | 0.00 | 0.00 | 0.175379E+11 | 0.161432E+11 | 36336.25 | 17-APR-07:01 | 26745.19 | 0.00 |
May | 0.00 | 0.00 | 0.257401E+11 | 0.212393E+11 | 38738.32 | 24-MAY-07:02 | 18844.44 | 0.00 |
June | 0.00 | 0.00 | 0.285667E+11 | 0.209952E+11 | 39298.52 | 25-JUN-08:61 | 16765.10 | 0.00 |
July | 0.00 | 0.00 | 0.314494E+11 | 0.192488E+11 | 39406.39 | 26-JUL-07:01 | 16654.22 | 0.00 |
August | 0.00 | 0.00 | 0.318465E+11 | 0.184148E+11 | 39414.16 | 21-AUG-07:01 | 15554.36 | 0.00 |
September | 0.00 | 0.00 | 0.256530E+11 | 0.160701E+11 | 39432.04 | 04-SEP-08:61 | 16259.34 | 0.00 |
October | 0.00 | 0.00 | 0.172141E+11 | 0.142052E+11 | 37489.73 | 12-OCT-07:02 | 21023.82 | 0.00 |
November | 0.00 | 0.00 | 0.923628E+10 | 0.832552E+10 | 14689.64 | 09-NOV-13:10 | 13036.97 | 0.00 |
December | 0.00 | 0.00 | 0.279841E+10 | 0.255791E+10 | 7809.68 | 28-DEC-14:00 | 7291.73 | 0.00 |
Annual Sum or Average | 0.206712E+12 | 0.152272E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.146200E+10 | 0.137118E+10 | 6176.59 | 5968.32 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.318465E+11 | 0.212393E+11 | 39432.04 | 26745.19 | 0.00 |
Report: FanReportMonthly
For: PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.640410E+10 | 0.62 | 3529.59 | 01-JAN-09:01 | 0.92 |
February | 0.579418E+10 | 0.62 | 3529.59 | 01-FEB-11:05 | 0.92 |
March | 0.641680E+10 | 0.62 | 3529.59 | 01-MAR-10:30 | 0.92 |
April | 0.621350E+10 | 0.62 | 3529.59 | 01-APR-07:40 | 0.91 |
May | 0.640410E+10 | 0.62 | 3529.59 | 01-MAY-07:40 | 0.91 |
June | 0.621350E+10 | 0.62 | 3529.59 | 01-JUN-07:40 | 0.91 |
July | 0.641680E+10 | 0.61 | 3529.59 | 01-JUL-09:10 | 0.91 |
August | 0.640410E+10 | 0.61 | 3529.59 | 01-AUG-07:08 | 0.90 |
September | 0.622620E+10 | 0.62 | 3529.59 | 01-SEP-07:06 | 0.90 |
October | 0.640410E+10 | 0.62 | 3529.59 | 01-OCT-08:06 | 0.91 |
November | 0.618808E+10 | 0.62 | 3529.59 | 01-NOV-11:40 | 0.92 |
December | 0.642951E+10 | 0.62 | 3529.59 | 01-DEC-00:10 | 0.92 |
Annual Sum or Average | 0.755150E+11 | 0.62 | |||
Minimum of Months | 0.579418E+10 | 0.61 | 3529.59 | 0.90 | |
Maximum of Months | 0.642951E+10 | 0.62 | 3529.59 | 0.92 |
Report: FanReportMonthly
For: PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.252535E+10 | 0.67 | 1786.07 | 05-JAN-17:50 | 0.92 |
February | 0.231664E+10 | 0.66 | 1786.07 | 02-FEB-12:00 | 0.92 |
March | 0.264458E+10 | 0.66 | 1786.07 | 01-MAR-16:10 | 0.92 |
April | 0.260147E+10 | 0.66 | 1786.07 | 04-APR-19:18 | 0.92 |
May | 0.276658E+10 | 0.65 | 1786.07 | 09-MAY-08:20 | 0.91 |
June | 0.273026E+10 | 0.64 | 1786.07 | 01-JUN-08:30 | 0.91 |
July | 0.282541E+10 | 0.64 | 1786.07 | 07-JUL-19:06 | 0.91 |
August | 0.282602E+10 | 0.64 | 1786.07 | 05-AUG-07:08 | 0.91 |
September | 0.268143E+10 | 0.65 | 1786.07 | 02-SEP-07:30 | 0.91 |
October | 0.266851E+10 | 0.65 | 1786.07 | 03-OCT-09:10 | 0.91 |
November | 0.251468E+10 | 0.66 | 1786.07 | 01-NOV-11:50 | 0.92 |
December | 0.253054E+10 | 0.67 | 1786.07 | 03-DEC-17:50 | 0.92 |
Annual Sum or Average | 0.316315E+11 | 0.65 | |||
Minimum of Months | 0.231664E+10 | 0.64 | 1786.07 | 0.91 | |
Maximum of Months | 0.282602E+10 | 0.67 | 1786.07 | 0.92 |
Report: FanReportMonthly
For: PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.247635E+10 | 0.50 | 1711.13 | 01-JAN-08:50 | 0.92 |
February | 0.224226E+10 | 0.50 | 1711.13 | 01-FEB-16:20 | 0.92 |
March | 0.252563E+10 | 0.50 | 1711.13 | 01-MAR-19:50 | 0.92 |
April | 0.240243E+10 | 0.50 | 1711.13 | 01-APR-07:20 | 0.91 |
May | 0.250099E+10 | 0.50 | 1711.13 | 01-MAY-06:20 | 0.92 |
June | 0.243961E+10 | 0.50 | 1711.13 | 01-JUN-07:07 | 0.91 |
July | 0.246403E+10 | 0.49 | 1711.13 | 01-JUL-09:30 | 0.91 |
August | 0.252563E+10 | 0.50 | 1711.13 | 01-AUG-07:13 | 0.91 |
September | 0.240243E+10 | 0.49 | 1711.13 | 01-SEP-07:01 | 0.90 |
October | 0.247635E+10 | 0.49 | 1711.13 | 01-OCT-08:07 | 0.91 |
November | 0.240243E+10 | 0.50 | 1711.13 | 01-NOV-15:10 | 0.92 |
December | 0.246403E+10 | 0.49 | 1711.13 | 01-DEC-12:20 | 0.92 |
Annual Sum or Average | 0.293222E+11 | 0.50 | |||
Minimum of Months | 0.224226E+10 | 0.49 | 1711.13 | 0.90 | |
Maximum of Months | 0.252563E+10 | 0.50 | 1711.13 | 0.92 |
Report: FanReportMonthly
For: PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.247122E+10 | 0.50 | 1707.58 | 03-JAN-13:50 | 0.92 |
February | 0.223762E+10 | 0.50 | 1707.58 | 07-FEB-11:30 | 0.92 |
March | 0.252039E+10 | 0.50 | 1707.58 | 02-MAR-09:20 | 0.91 |
April | 0.239745E+10 | 0.50 | 1707.58 | 03-APR-08:20 | 0.91 |
May | 0.249581E+10 | 0.50 | 1707.58 | 13-MAY-17:50 | 0.91 |
June | 0.243470E+10 | 0.50 | 1707.58 | 02-JUN-19:40 | 0.91 |
July | 0.245952E+10 | 0.49 | 1707.58 | 01-JUL-06:07 | 0.91 |
August | 0.252039E+10 | 0.50 | 1707.58 | 27-AUG-15:30 | 0.90 |
September | 0.239745E+10 | 0.49 | 1707.58 | 08-SEP-07:00 | 0.90 |
October | 0.247122E+10 | 0.49 | 1707.58 | 22-OCT-10:40 | 0.91 |
November | 0.239745E+10 | 0.50 | 1707.58 | 05-NOV-08:00 | 0.91 |
December | 0.245892E+10 | 0.49 | 1707.58 | 04-DEC-19:50 | 0.91 |
Annual Sum or Average | 0.292621E+11 | 0.50 | |||
Minimum of Months | 0.223762E+10 | 0.49 | 1707.58 | 0.90 | |
Maximum of Months | 0.252039E+10 | 0.50 | 1707.58 | 0.92 |
Report: FanReportMonthly
For: PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.246730E+10 | 0.50 | 1704.88 | 03-JAN-16:00 | 0.92 |
February | 0.223407E+10 | 0.50 | 1704.88 | 02-FEB-20:00 | 0.92 |
March | 0.251640E+10 | 0.50 | 1704.88 | 02-MAR-14:30 | 0.92 |
April | 0.239365E+10 | 0.50 | 1704.88 | 14-APR-07:06 | 0.91 |
May | 0.249185E+10 | 0.50 | 1704.88 | 06-MAY-17:35 | 0.92 |
June | 0.243083E+10 | 0.50 | 1704.88 | 26-JUN-06:09 | 0.90 |
July | 0.245535E+10 | 0.49 | 1704.88 | 01-JUL-06:04 | 0.91 |
August | 0.251640E+10 | 0.50 | 1704.88 | 01-AUG-06:10 | 0.90 |
September | 0.239365E+10 | 0.49 | 1704.88 | 30-SEP-06:03 | 0.91 |
October | 0.246730E+10 | 0.49 | 1704.88 | 11-OCT-06:20 | 0.91 |
November | 0.239365E+10 | 0.50 | 1704.88 | 01-NOV-07:50 | 0.91 |
December | 0.245502E+10 | 0.49 | 1704.88 | 01-DEC-16:10 | 0.92 |
Annual Sum or Average | 0.292155E+11 | 0.50 | |||
Minimum of Months | 0.223407E+10 | 0.49 | 1704.88 | 0.90 | |
Maximum of Months | 0.251640E+10 | 0.50 | 1704.88 | 0.92 |
Report: FanReportMonthly
For: PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.420121E+10 | 0.46 | 3145.56 | 07-JAN-12:50 | 0.92 |
February | 0.380487E+10 | 0.46 | 3145.56 | 15-FEB-12:50 | 0.91 |
March | 0.429180E+10 | 0.47 | 3145.56 | 03-MAR-09:30 | 0.92 |
April | 0.407665E+10 | 0.46 | 3145.56 | 03-APR-19:25 | 0.92 |
May | 0.424709E+10 | 0.46 | 3145.56 | 07-MAY-16:17 | 0.91 |
June | 0.414519E+10 | 0.46 | 3145.56 | 03-JUN-07:08 | 0.91 |
July | 0.417952E+10 | 0.45 | 3145.56 | 04-JUL-16:40 | 0.91 |
August | 0.429180E+10 | 0.46 | 3145.56 | 23-AUG-13:30 | 0.90 |
September | 0.407665E+10 | 0.45 | 3145.56 | 01-SEP-07:05 | 0.90 |
October | 0.420121E+10 | 0.45 | 3145.56 | 02-OCT-19:33 | 0.91 |
November | 0.407665E+10 | 0.46 | 3145.56 | 01-NOV-15:10 | 0.92 |
December | 0.417856E+10 | 0.45 | 3145.56 | 06-DEC-14:50 | 0.92 |
Annual Sum or Average | 0.497712E+11 | 0.46 | |||
Minimum of Months | 0.380487E+10 | 0.45 | 3145.56 | 0.90 | |
Maximum of Months | 0.429180E+10 | 0.47 | 3145.56 | 0.92 |
Report: FanReportMonthly
For: PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.221415E+10 | 0.46 | 1657.79 | 03-JAN-13:10 | 0.92 |
February | 0.200527E+10 | 0.46 | 1657.79 | 01-FEB-14:20 | 0.92 |
March | 0.226189E+10 | 0.47 | 1657.79 | 01-MAR-10:20 | 0.92 |
April | 0.214850E+10 | 0.46 | 1657.79 | 02-APR-10:20 | 0.91 |
May | 0.223802E+10 | 0.46 | 1657.79 | 03-MAY-20:00 | 0.91 |
June | 0.218471E+10 | 0.46 | 1657.79 | 01-JUN-07:50 | 0.91 |
July | 0.220221E+10 | 0.45 | 1657.79 | 01-JUL-13:30 | 0.90 |
August | 0.226189E+10 | 0.46 | 1657.79 | 01-AUG-12:50 | 0.91 |
September | 0.214850E+10 | 0.45 | 1657.79 | 03-SEP-12:00 | 0.91 |
October | 0.221415E+10 | 0.45 | 1657.79 | 02-OCT-07:30 | 0.91 |
November | 0.214850E+10 | 0.46 | 1657.79 | 01-NOV-15:10 | 0.92 |
December | 0.220221E+10 | 0.45 | 1657.79 | 01-DEC-19:30 | 0.91 |
Annual Sum or Average | 0.262300E+11 | 0.46 | |||
Minimum of Months | 0.200527E+10 | 0.45 | 1657.79 | 0.90 | |
Maximum of Months | 0.226189E+10 | 0.47 | 1657.79 | 0.92 |
Report: FanReportMonthly
For: PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.220503E+10 | 0.46 | 1650.96 | 03-JAN-10:00 | 0.92 |
February | 0.199701E+10 | 0.46 | 1650.96 | 01-FEB-08:40 | 0.92 |
March | 0.225258E+10 | 0.47 | 1650.96 | 03-MAR-12:40 | 0.92 |
April | 0.213965E+10 | 0.46 | 1650.96 | 03-APR-16:30 | 0.92 |
May | 0.222880E+10 | 0.46 | 1650.96 | 06-MAY-08:70 | 0.92 |
June | 0.217570E+10 | 0.46 | 1650.96 | 14-JUN-07:09 | 0.91 |
July | 0.219314E+10 | 0.45 | 1650.96 | 01-JUL-07:09 | 0.91 |
August | 0.225258E+10 | 0.46 | 1650.96 | 01-AUG-07:09 | 0.90 |
September | 0.213965E+10 | 0.45 | 1650.96 | 06-SEP-08:30 | 0.90 |
October | 0.220503E+10 | 0.45 | 1650.96 | 05-OCT-20:00 | 0.91 |
November | 0.213965E+10 | 0.46 | 1650.96 | 01-NOV-10:50 | 0.92 |
December | 0.219314E+10 | 0.45 | 1650.96 | 09-DEC-15:30 | 0.92 |
Annual Sum or Average | 0.261220E+11 | 0.46 | |||
Minimum of Months | 0.199701E+10 | 0.45 | 1650.96 | 0.90 | |
Maximum of Months | 0.225258E+10 | 0.47 | 1650.96 | 0.92 |
Report: FanReportMonthly
For: PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.221013E+10 | 0.46 | 1654.79 | 02-JAN-10:30 | 0.92 |
February | 0.200163E+10 | 0.46 | 1654.79 | 01-FEB-11:40 | 0.92 |
March | 0.225779E+10 | 0.47 | 1654.79 | 01-MAR-10:40 | 0.92 |
April | 0.214460E+10 | 0.46 | 1654.79 | 01-APR-07:08 | 0.91 |
May | 0.223396E+10 | 0.46 | 1654.79 | 01-MAY-07:08 | 0.92 |
June | 0.218076E+10 | 0.46 | 1654.79 | 01-JUN-08:20 | 0.91 |
July | 0.219822E+10 | 0.45 | 1654.79 | 01-JUL-07:07 | 0.91 |
August | 0.225779E+10 | 0.46 | 1654.79 | 01-AUG-08:70 | 0.91 |
September | 0.214460E+10 | 0.45 | 1654.79 | 01-SEP-08:30 | 0.90 |
October | 0.221013E+10 | 0.45 | 1654.79 | 01-OCT-10:00 | 0.91 |
November | 0.214460E+10 | 0.46 | 1654.79 | 01-NOV-07:40 | 0.91 |
December | 0.219822E+10 | 0.45 | 1654.79 | 01-DEC-12:50 | 0.92 |
Annual Sum or Average | 0.261825E+11 | 0.46 | |||
Minimum of Months | 0.200163E+10 | 0.45 | 1654.79 | 0.90 | |
Maximum of Months | 0.225779E+10 | 0.47 | 1654.79 | 0.92 |
Report: FanReportMonthly
For: PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.244876E+10 | 0.46 | 1833.46 | 01-JAN-09:09 | 0.91 |
February | 0.221775E+10 | 0.46 | 1833.46 | 02-FEB-08:20 | 0.92 |
March | 0.250157E+10 | 0.47 | 1833.46 | 14-MAR-19:45 | 0.91 |
April | 0.237616E+10 | 0.46 | 1833.46 | 01-APR-07:30 | 0.91 |
May | 0.247669E+10 | 0.46 | 1833.46 | 21-MAY-16:20 | 0.91 |
June | 0.241736E+10 | 0.46 | 1833.46 | 01-JUN-07:09 | 0.91 |
July | 0.243829E+10 | 0.45 | 1833.46 | 01-JUL-07:07 | 0.90 |
August | 0.250187E+10 | 0.46 | 1833.46 | 01-AUG-07:08 | 0.90 |
September | 0.237616E+10 | 0.45 | 1833.46 | 01-SEP-07:05 | 0.90 |
October | 0.244876E+10 | 0.45 | 1833.46 | 09-OCT-16:38 | 0.91 |
November | 0.237616E+10 | 0.46 | 1833.46 | 04-NOV-09:00 | 0.91 |
December | 0.243556E+10 | 0.45 | 1833.46 | 01-DEC-19:50 | 0.91 |
Annual Sum or Average | 0.290151E+11 | 0.46 | |||
Minimum of Months | 0.221775E+10 | 0.45 | 1833.46 | 0.90 | |
Maximum of Months | 0.250187E+10 | 0.47 | 1833.46 | 0.92 |
Report: ZoneTemperatureOscillationReportMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.50 | 1.25 |
February | 0.00 | 0.00 |
March | 0.06 | 0.00 |
April | 1.21 | 0.00 |
May | 1.01 | 0.00 |
June | 0.81 | 0.00 |
July | 0.96 | 0.00 |
August | 0.88 | 0.00 |
September | 1.62 | 0.00 |
October | 2.01 | 0.37 |
November | 0.14 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 9.19 | 0.15 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 2.01 | 1.25 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.75 | 0.61 |
February | 0.00 | 0.00 |
March | 0.06 | 0.00 |
April | 0.62 | 0.00 |
May | 0.67 | 0.00 |
June | 0.64 | 0.00 |
July | 0.80 | 0.00 |
August | 0.38 | 0.00 |
September | 1.12 | 0.00 |
October | 1.01 | 0.25 |
November | 0.14 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 6.19 | 0.11 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 1.12 | 0.61 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.19 | 0.00 |
February | 0.37 | 0.75 |
March | 3.36 | 0.75 |
April | 5.14 | 0.69 |
May | 3.67 | 0.72 |
June | 3.35 | 0.73 |
July | 4.53 | 0.71 |
August | 5.54 | 0.67 |
September | 5.75 | 0.70 |
October | 5.04 | 0.69 |
November | 1.40 | 0.75 |
December | 0.00 | 0.00 |
Annual Sum or Average | 38.37 | 0.70 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 5.75 | 0.75 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.06 | 0.00 |
February | 0.37 | 0.75 |
March | 3.36 | 0.75 |
April | 5.14 | 0.69 |
May | 3.67 | 0.72 |
June | 3.27 | 0.73 |
July | 4.53 | 0.71 |
August | 5.54 | 0.67 |
September | 5.75 | 0.70 |
October | 5.04 | 0.69 |
November | 1.32 | 0.75 |
December | 0.00 | 0.00 |
Annual Sum or Average | 38.06 | 0.70 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 5.75 | 0.75 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.21 | 0.75 |
March | 3.36 | 0.75 |
April | 5.48 | 0.68 |
May | 3.81 | 0.73 |
June | 3.49 | 0.73 |
July | 4.53 | 0.71 |
August | 5.54 | 0.67 |
September | 5.75 | 0.70 |
October | 4.88 | 0.72 |
November | 1.32 | 0.75 |
December | 0.00 | 0.00 |
Annual Sum or Average | 38.37 | 0.71 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 5.75 | 0.75 |
Report: ZoneTemperatureOscillationReportMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.12 | 3.30 |
March | 0.96 | 2.82 |
April | 2.17 | 1.91 |
May | 0.67 | 2.47 |
June | 0.70 | 2.52 |
July | 1.43 | 2.24 |
August | 1.63 | 1.90 |
September | 2.55 | 2.11 |
October | 3.21 | 1.85 |
November | 0.86 | 3.30 |
December | 0.00 | 0.00 |
Annual Sum or Average | 14.32 | 2.18 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 3.21 | 3.30 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.12 | 1.65 |
March | 0.96 | 1.41 |
April | 1.89 | 1.14 |
May | 0.50 | 1.65 |
June | 0.54 | 1.65 |
July | 1.18 | 1.47 |
August | 1.38 | 1.22 |
September | 2.30 | 1.23 |
October | 3.05 | 0.97 |
November | 0.86 | 1.65 |
December | 0.00 | 0.00 |
Annual Sum or Average | 12.79 | 1.26 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 3.05 | 1.65 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.12 | 1.65 |
March | 0.96 | 1.41 |
April | 1.73 | 1.17 |
May | 0.50 | 1.65 |
June | 0.54 | 1.65 |
July | 1.18 | 1.47 |
August | 1.38 | 1.22 |
September | 2.30 | 1.23 |
October | 2.88 | 1.03 |
November | 0.86 | 1.65 |
December | 0.00 | 0.00 |
Annual Sum or Average | 12.46 | 1.28 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 2.88 | 1.65 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.12 | 1.65 |
March | 0.88 | 1.55 |
April | 1.73 | 1.17 |
May | 0.50 | 1.65 |
June | 0.54 | 1.65 |
July | 1.18 | 1.47 |
August | 1.36 | 1.25 |
September | 2.30 | 1.23 |
October | 2.88 | 1.03 |
November | 0.86 | 1.65 |
December | 0.00 | 0.00 |
Annual Sum or Average | 12.35 | 1.29 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 2.88 | 1.65 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.08 | 0.00 |
February | 0.12 | 1.65 |
March | 0.88 | 1.55 |
April | 1.62 | 1.05 |
May | 0.28 | 1.65 |
June | 0.37 | 1.65 |
July | 0.99 | 1.26 |
August | 0.88 | 1.49 |
September | 1.40 | 1.55 |
October | 2.76 | 1.00 |
November | 0.86 | 1.65 |
December | 0.00 | 0.00 |
Annual Sum or Average | 10.24 | 1.29 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 2.76 | 1.65 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_1:1
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.893785E+10 | 0.106041E+09 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.106563E+11 | 2671421.03 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.164974E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.223826E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.291166E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.305310E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.315849E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.304215E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.267895E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.210195E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.145450E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.100384E+11 | 15085102.38 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.252520E+12 | 0.123798E+09 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.893785E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.315849E+11 | 0.106041E+09 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_2:2
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.404304E+10 | 23159846.95 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.482369E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.741629E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.996624E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.130319E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.136476E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.140847E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.135895E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.118539E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.933928E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.654540E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.455828E+10 | 1590015.44 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.112900E+12 | 24749862.38 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.404304E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.140847E+11 | 23159846.95 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_3:3
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.320050E+10 | 0.156955E+09 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.383714E+10 | 3175076.79 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.607273E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.814280E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.107659E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.112178E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.113057E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.111867E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.961475E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.763862E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.533255E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.360598E+10 | 16084432.92 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.919211E+11 | 0.176214E+09 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.320050E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.113057E+11 | 0.156955E+09 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_4:4
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.313311E+10 | 0.224044E+09 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.378379E+10 | 7456759.33 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.603941E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.813606E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.107761E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.112269E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.113191E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.111856E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.960927E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.762632E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.529230E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.354148E+10 | 23782064.33 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.916694E+11 | 0.255283E+09 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.313311E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.113191E+11 | 0.224044E+09 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_5:5
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.307474E+10 | 0.281653E+09 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.372735E+10 | 12239170.59 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.597881E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.808818E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.107341E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.111844E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.112805E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.111411E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.956622E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.757816E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.523661E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.348131E+10 | 32639942.62 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.910715E+11 | 0.326532E+09 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.307474E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.112805E+11 | 0.281653E+09 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_6:6
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.522191E+10 | 0.470625E+09 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.660871E+10 | 26726298.93 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.110613E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.152653E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.204753E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.213601E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.213596E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.211966E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.180477E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.142139E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.957313E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.598765E+10 | 60895797.11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.170371E+12 | 0.558247E+09 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.522191E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.213601E+11 | 0.470625E+09 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_7:7
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.269654E+10 | 0.236811E+09 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.336386E+10 | 10951769.56 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.556010E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.761089E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.101701E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.105974E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.105968E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.105183E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.897365E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.710298E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.482838E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.307541E+10 | 27740612.75 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.850943E+11 | 0.275504E+09 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.269654E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.105974E+11 | 0.236811E+09 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_8:8
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.266882E+10 | 0.252381E+09 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.333163E+10 | 13047719.43 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.552123E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.757306E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.101288E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.105560E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.105576E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.104786E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.893755E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.706782E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.479505E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.304468E+10 | 30834820.48 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.846609E+11 | 0.296264E+09 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.266882E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.105576E+11 | 0.252381E+09 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_9:9
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.263775E+10 | 0.305524E+09 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.328766E+10 | 22845851.11 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.547984E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.756544E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.101426E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.105761E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.105830E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.105045E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.895563E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.706935E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.476832E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.300564E+10 | 42852864.05 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.845758E+11 | 0.371222E+09 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.263775E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.105830E+11 | 0.305524E+09 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_10:10
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.288669E+10 | 0.456241E+09 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.353521E+10 | 72116853.40 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.586647E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.822042E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.110772E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.115332E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.115801E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.114884E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.978646E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.773868E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.517983E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.327248E+10 | 85443569.68 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.921651E+11 | 0.613802E+09 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.288669E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.115801E+11 | 0.456241E+09 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_1:1
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.640410E+10 | 0.807262E+10 | 84037705.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.579418E+10 | 0.155245E+11 | 2117101.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.641680E+10 | 0.312202E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.621350E+10 | 0.463633E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.640410E+10 | 0.645267E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.621350E+10 | 0.719015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.641680E+10 | 0.808897E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.640410E+10 | 0.798542E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.622620E+10 | 0.671213E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.640410E+10 | 0.454035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.618808E+10 | 0.264202E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.642951E+10 | 0.115365E+11 | 11954943.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.755150E+11 | 0.548834E+12 | 98109750.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.579418E+10 | 0.807262E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.642951E+10 | 0.808897E+11 | 84037705.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_2:2
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.252535E+10 | 0.502962E+10 | 18527877.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.231664E+10 | 0.837796E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.264458E+10 | 0.154796E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.260147E+10 | 0.220269E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.276658E+10 | 0.303539E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.273026E+10 | 0.335792E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.282541E+10 | 0.375878E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.282602E+10 | 0.372318E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.268143E+10 | 0.311053E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.266851E+10 | 0.216139E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.251468E+10 | 0.133519E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.253054E+10 | 0.676263E+10 | 1272012.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.316315E+11 | 0.262501E+12 | 19799889.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.231664E+10 | 0.502962E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.282602E+10 | 0.375878E+11 | 18527877.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_3:3
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.247635E+10 | 0.243803E+10 | 0.125564E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.224226E+10 | 0.536805E+10 | 2540061.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.252563E+10 | 0.115536E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.240243E+10 | 0.173988E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.250099E+10 | 0.249063E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.243961E+10 | 0.277439E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.246403E+10 | 0.305442E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.252563E+10 | 0.308340E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.240243E+10 | 0.251238E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.247635E+10 | 0.168869E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.240243E+10 | 0.973250E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.246403E+10 | 0.385582E+10 | 12867546.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.293222E+11 | 0.206386E+12 | 0.140971E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.224226E+10 | 0.243803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.252563E+10 | 0.308340E+11 | 0.125564E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_4:4
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.247122E+10 | 0.222506E+10 | 0.179235E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.223762E+10 | 0.519634E+10 | 5965407.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.252039E+10 | 0.114554E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.239745E+10 | 0.173984E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.249581E+10 | 0.249703E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.243470E+10 | 0.278043E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.245952E+10 | 0.306231E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.252039E+10 | 0.308625E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.239745E+10 | 0.251303E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.247122E+10 | 0.168644E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.239745E+10 | 0.960719E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.245892E+10 | 0.364906E+10 | 19025651.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.292621E+11 | 0.205786E+12 | 0.204226E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.223762E+10 | 0.222506E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.252039E+10 | 0.308625E+11 | 0.179235E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_5:5
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.246730E+10 | 0.203927E+10 | 0.225323E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.223407E+10 | 0.501048E+10 | 9791336.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.251640E+10 | 0.112551E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.239365E+10 | 0.172481E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.249185E+10 | 0.248432E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.243083E+10 | 0.276696E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.245535E+10 | 0.304965E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.251640E+10 | 0.307067E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.239365E+10 | 0.249802E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.246730E+10 | 0.167044E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.239365E+10 | 0.942220E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.245502E+10 | 0.345394E+10 | 26111954.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.292155E+11 | 0.203830E+12 | 0.261226E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.223407E+10 | 0.203927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.251640E+10 | 0.307067E+11 | 0.225323E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_6:6
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.420121E+10 | 0.322584E+10 | 0.372970E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.380487E+10 | 0.884571E+10 | 21180591.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.429180E+10 | 0.206934E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.407665E+10 | 0.318256E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.424709E+10 | 0.460631E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.414519E+10 | 0.512657E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.417952E+10 | 0.561280E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.429180E+10 | 0.569051E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.407665E+10 | 0.458909E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.420121E+10 | 0.308172E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.407665E+10 | 0.171407E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.417856E+10 | 0.572691E+10 | 48259919.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.497712E+11 | 0.374528E+12 | 0.442410E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.380487E+10 | 0.322584E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.429180E+10 | 0.569051E+11 | 0.372970E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_7:7
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.221415E+10 | 0.161549E+10 | 0.189449E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.200527E+10 | 0.454123E+10 | 8761415.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.226189E+10 | 0.106785E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.214850E+10 | 0.164477E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.223802E+10 | 0.238237E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.218471E+10 | 0.264974E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.220221E+10 | 0.290129E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.226189E+10 | 0.294002E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.214850E+10 | 0.237249E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.221415E+10 | 0.159328E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.214850E+10 | 0.885389E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.220221E+10 | 0.292910E+10 | 22192490.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.262300E+11 | 0.193458E+12 | 0.220403E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.200527E+10 | 0.161549E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.226189E+10 | 0.294002E+11 | 0.189449E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_8:8
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.220503E+10 | 0.155248E+10 | 0.201905E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.199701E+10 | 0.445819E+10 | 10438175.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.225258E+10 | 0.105776E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.213965E+10 | 0.163569E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.222880E+10 | 0.237284E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.217570E+10 | 0.263999E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.219314E+10 | 0.289169E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.225258E+10 | 0.292997E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.213965E+10 | 0.236340E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.220503E+10 | 0.158454E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.213965E+10 | 0.876935E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.219314E+10 | 0.285488E+10 | 24667856.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.261220E+11 | 0.192394E+12 | 0.237011E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.199701E+10 | 0.155248E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.225258E+10 | 0.292997E+11 | 0.201905E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_9:9
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.221013E+10 | 0.142967E+10 | 0.244419E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.200163E+10 | 0.428823E+10 | 18276680.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.225779E+10 | 0.104108E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.214460E+10 | 0.163069E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.223396E+10 | 0.237467E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.218076E+10 | 0.264410E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.219822E+10 | 0.289842E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.225779E+10 | 0.293707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.214460E+10 | 0.236756E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.221013E+10 | 0.158278E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.214460E+10 | 0.865557E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.219822E+10 | 0.270313E+10 | 34282291.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.261825E+11 | 0.191840E+12 | 0.296978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.200163E+10 | 0.142967E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.225779E+10 | 0.293707E+11 | 0.244419E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_10:10
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.244876E+10 | 0.146200E+10 | 0.364993E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.221775E+10 | 0.438037E+10 | 57693482.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.250157E+10 | 0.108272E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.237616E+10 | 0.175379E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.247669E+10 | 0.257401E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.241736E+10 | 0.285667E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.243829E+10 | 0.314494E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.250187E+10 | 0.318465E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.237616E+10 | 0.256530E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.244876E+10 | 0.172141E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.237616E+10 | 0.923628E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.243556E+10 | 0.279841E+10 | 68354855.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.290151E+11 | 0.206712E+12 | 0.491041E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.221775E+10 | 0.146200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.250187E+10 | 0.318465E+11 | 0.364993E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_1:1
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.640410E+10 | 0.00 | 0.00 | 0.00 | 0.253375E+10 | 0.00 | 0.106041E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.579418E+10 | 0.00 | 0.00 | 0.00 | 0.486213E+10 | 0.00 | 2671421.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.641680E+10 | 0.00 | 0.00 | 0.00 | 0.100806E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.621350E+10 | 0.00 | 0.00 | 0.00 | 0.161691E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.640410E+10 | 0.00 | 0.00 | 0.00 | 0.227125E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.621350E+10 | 0.00 | 0.00 | 0.00 | 0.243175E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.641680E+10 | 0.00 | 0.00 | 0.00 | 0.251681E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.640410E+10 | 0.00 | 0.00 | 0.00 | 0.240174E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.622620E+10 | 0.00 | 0.00 | 0.00 | 0.205633E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.640410E+10 | 0.00 | 0.00 | 0.00 | 0.146154E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.618808E+10 | 0.00 | 0.00 | 0.00 | 0.835688E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.642951E+10 | 0.00 | 0.00 | 0.00 | 0.360886E+10 | 0.00 | 15085102.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.755150E+11 | 0.00 | 0.00 | 0.00 | 0.177006E+12 | 0.00 | 0.123798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.579418E+10 | 0.00 | 0.00 | 0.00 | 0.253375E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.642951E+10 | 0.00 | 0.00 | 0.00 | 0.251681E+11 | 0.00 | 0.106041E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_2:2
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.252535E+10 | 0.00 | 0.00 | 0.00 | 0.151769E+10 | 0.00 | 23159846.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.231664E+10 | 0.00 | 0.00 | 0.00 | 0.250705E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.264458E+10 | 0.00 | 0.00 | 0.00 | 0.477171E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.260147E+10 | 0.00 | 0.00 | 0.00 | 0.736477E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.276658E+10 | 0.00 | 0.00 | 0.00 | 0.102653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.273026E+10 | 0.00 | 0.00 | 0.00 | 0.109174E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.282541E+10 | 0.00 | 0.00 | 0.00 | 0.112593E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.282602E+10 | 0.00 | 0.00 | 0.00 | 0.107635E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.268143E+10 | 0.00 | 0.00 | 0.00 | 0.917249E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.266851E+10 | 0.00 | 0.00 | 0.00 | 0.667077E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.251468E+10 | 0.00 | 0.00 | 0.00 | 0.403072E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.253054E+10 | 0.00 | 0.00 | 0.00 | 0.202774E+10 | 0.00 | 1590015.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.316315E+11 | 0.00 | 0.00 | 0.00 | 0.812683E+11 | 0.00 | 24749862.38 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.231664E+10 | 0.00 | 0.00 | 0.00 | 0.151769E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.282602E+10 | 0.00 | 0.00 | 0.00 | 0.112593E+11 | 0.00 | 23159846.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_3:3
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.247635E+10 | 0.00 | 0.00 | 0.00 | 0.724152E+09 | 0.00 | 0.156955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.224226E+10 | 0.00 | 0.00 | 0.00 | 0.159488E+10 | 0.00 | 3175076.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.252563E+10 | 0.00 | 0.00 | 0.00 | 0.354710E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.240243E+10 | 0.00 | 0.00 | 0.00 | 0.574037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.250099E+10 | 0.00 | 0.00 | 0.00 | 0.826492E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.243961E+10 | 0.00 | 0.00 | 0.00 | 0.877815E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.246403E+10 | 0.00 | 0.00 | 0.00 | 0.884164E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.252563E+10 | 0.00 | 0.00 | 0.00 | 0.866107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.240243E+10 | 0.00 | 0.00 | 0.00 | 0.721233E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.247635E+10 | 0.00 | 0.00 | 0.00 | 0.516227E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.240243E+10 | 0.00 | 0.00 | 0.00 | 0.293013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.246403E+10 | 0.00 | 0.00 | 0.00 | 0.114195E+10 | 0.00 | 16084432.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.293222E+11 | 0.00 | 0.00 | 0.00 | 0.625990E+11 | 0.00 | 0.176214E+09 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.224226E+10 | 0.00 | 0.00 | 0.00 | 0.724152E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.252563E+10 | 0.00 | 0.00 | 0.00 | 0.884164E+10 | 0.00 | 0.156955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_4:4
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.247122E+10 | 0.00 | 0.00 | 0.00 | 0.661899E+09 | 0.00 | 0.224044E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.223762E+10 | 0.00 | 0.00 | 0.00 | 0.154617E+10 | 0.00 | 7456759.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.252039E+10 | 0.00 | 0.00 | 0.00 | 0.351902E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.239745E+10 | 0.00 | 0.00 | 0.00 | 0.573861E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.249581E+10 | 0.00 | 0.00 | 0.00 | 0.828026E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.243470E+10 | 0.00 | 0.00 | 0.00 | 0.879220E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.245952E+10 | 0.00 | 0.00 | 0.00 | 0.885956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.252039E+10 | 0.00 | 0.00 | 0.00 | 0.866522E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.239745E+10 | 0.00 | 0.00 | 0.00 | 0.721182E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.247122E+10 | 0.00 | 0.00 | 0.00 | 0.515511E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.239745E+10 | 0.00 | 0.00 | 0.00 | 0.289485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.245892E+10 | 0.00 | 0.00 | 0.00 | 0.108256E+10 | 0.00 | 23782064.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.292621E+11 | 0.00 | 0.00 | 0.00 | 0.624073E+11 | 0.00 | 0.255283E+09 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.223762E+10 | 0.00 | 0.00 | 0.00 | 0.661899E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.252039E+10 | 0.00 | 0.00 | 0.00 | 0.885956E+10 | 0.00 | 0.224044E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_5:5
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.246730E+10 | 0.00 | 0.00 | 0.00 | 0.607440E+09 | 0.00 | 0.281653E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.223407E+10 | 0.00 | 0.00 | 0.00 | 0.149328E+10 | 0.00 | 12239170.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.251640E+10 | 0.00 | 0.00 | 0.00 | 0.346241E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.239365E+10 | 0.00 | 0.00 | 0.00 | 0.569453E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.249185E+10 | 0.00 | 0.00 | 0.00 | 0.824228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.243083E+10 | 0.00 | 0.00 | 0.00 | 0.875357E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.245535E+10 | 0.00 | 0.00 | 0.00 | 0.882514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.251640E+10 | 0.00 | 0.00 | 0.00 | 0.862474E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.239365E+10 | 0.00 | 0.00 | 0.00 | 0.717257E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.246730E+10 | 0.00 | 0.00 | 0.00 | 0.511087E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.239365E+10 | 0.00 | 0.00 | 0.00 | 0.284296E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.245502E+10 | 0.00 | 0.00 | 0.00 | 0.102628E+10 | 0.00 | 32639942.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.292155E+11 | 0.00 | 0.00 | 0.00 | 0.618561E+11 | 0.00 | 0.326532E+09 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.223407E+10 | 0.00 | 0.00 | 0.00 | 0.607440E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.251640E+10 | 0.00 | 0.00 | 0.00 | 0.882514E+10 | 0.00 | 0.281653E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_6:6
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.420121E+10 | 0.00 | 0.00 | 0.00 | 0.102070E+10 | 0.00 | 0.470625E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.380487E+10 | 0.00 | 0.00 | 0.00 | 0.280384E+10 | 0.00 | 26726298.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.429180E+10 | 0.00 | 0.00 | 0.00 | 0.676950E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.407665E+10 | 0.00 | 0.00 | 0.00 | 0.111887E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.424709E+10 | 0.00 | 0.00 | 0.00 | 0.162283E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.414519E+10 | 0.00 | 0.00 | 0.00 | 0.172149E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.417952E+10 | 0.00 | 0.00 | 0.00 | 0.171800E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.429180E+10 | 0.00 | 0.00 | 0.00 | 0.169048E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.407665E+10 | 0.00 | 0.00 | 0.00 | 0.139711E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.420121E+10 | 0.00 | 0.00 | 0.00 | 0.100126E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.407665E+10 | 0.00 | 0.00 | 0.00 | 0.549649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.417856E+10 | 0.00 | 0.00 | 0.00 | 0.180908E+10 | 0.00 | 60895797.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.497712E+11 | 0.00 | 0.00 | 0.00 | 0.120600E+12 | 0.00 | 0.558247E+09 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.380487E+10 | 0.00 | 0.00 | 0.00 | 0.102070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.429180E+10 | 0.00 | 0.00 | 0.00 | 0.172149E+11 | 0.00 | 0.470625E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_7:7
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.221415E+10 | 0.00 | 0.00 | 0.00 | 0.482395E+09 | 0.00 | 0.236811E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.200527E+10 | 0.00 | 0.00 | 0.00 | 0.135859E+10 | 0.00 | 10951769.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.226189E+10 | 0.00 | 0.00 | 0.00 | 0.329820E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.214850E+10 | 0.00 | 0.00 | 0.00 | 0.546239E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.223802E+10 | 0.00 | 0.00 | 0.00 | 0.793208E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.218471E+10 | 0.00 | 0.00 | 0.00 | 0.841265E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.220221E+10 | 0.00 | 0.00 | 0.00 | 0.839454E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.226189E+10 | 0.00 | 0.00 | 0.00 | 0.825641E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.214850E+10 | 0.00 | 0.00 | 0.00 | 0.682515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.221415E+10 | 0.00 | 0.00 | 0.00 | 0.488883E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.214850E+10 | 0.00 | 0.00 | 0.00 | 0.267988E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.220221E+10 | 0.00 | 0.00 | 0.00 | 0.873199E+09 | 0.00 | 27740612.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.262300E+11 | 0.00 | 0.00 | 0.00 | 0.588643E+11 | 0.00 | 0.275504E+09 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.200527E+10 | 0.00 | 0.00 | 0.00 | 0.482395E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.226189E+10 | 0.00 | 0.00 | 0.00 | 0.841265E+10 | 0.00 | 0.236811E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_8:8
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.220503E+10 | 0.00 | 0.00 | 0.00 | 0.463788E+09 | 0.00 | 0.252381E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.199701E+10 | 0.00 | 0.00 | 0.00 | 0.133462E+10 | 0.00 | 13047719.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.225258E+10 | 0.00 | 0.00 | 0.00 | 0.326866E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.213965E+10 | 0.00 | 0.00 | 0.00 | 0.543340E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.222880E+10 | 0.00 | 0.00 | 0.00 | 0.790005E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.217570E+10 | 0.00 | 0.00 | 0.00 | 0.838035E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.219314E+10 | 0.00 | 0.00 | 0.00 | 0.836446E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.225258E+10 | 0.00 | 0.00 | 0.00 | 0.822598E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.213965E+10 | 0.00 | 0.00 | 0.00 | 0.679790E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.220503E+10 | 0.00 | 0.00 | 0.00 | 0.486279E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.213965E+10 | 0.00 | 0.00 | 0.00 | 0.265540E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.219314E+10 | 0.00 | 0.00 | 0.00 | 0.851537E+09 | 0.00 | 30834820.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.261220E+11 | 0.00 | 0.00 | 0.00 | 0.585389E+11 | 0.00 | 0.296264E+09 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.199701E+10 | 0.00 | 0.00 | 0.00 | 0.463788E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.225258E+10 | 0.00 | 0.00 | 0.00 | 0.838035E+10 | 0.00 | 0.252381E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_9:9
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.221013E+10 | 0.00 | 0.00 | 0.00 | 0.427611E+09 | 0.00 | 0.305524E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.200163E+10 | 0.00 | 0.00 | 0.00 | 0.128603E+10 | 0.00 | 22845851.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.225779E+10 | 0.00 | 0.00 | 0.00 | 0.322205E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.214460E+10 | 0.00 | 0.00 | 0.00 | 0.542084E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.223396E+10 | 0.00 | 0.00 | 0.00 | 0.790864E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.218076E+10 | 0.00 | 0.00 | 0.00 | 0.839539E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.219822E+10 | 0.00 | 0.00 | 0.00 | 0.838473E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.225779E+10 | 0.00 | 0.00 | 0.00 | 0.824673E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.214460E+10 | 0.00 | 0.00 | 0.00 | 0.681102E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.221013E+10 | 0.00 | 0.00 | 0.00 | 0.485922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.214460E+10 | 0.00 | 0.00 | 0.00 | 0.262371E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.219822E+10 | 0.00 | 0.00 | 0.00 | 0.807419E+09 | 0.00 | 42852864.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.261825E+11 | 0.00 | 0.00 | 0.00 | 0.583934E+11 | 0.00 | 0.371222E+09 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.200163E+10 | 0.00 | 0.00 | 0.00 | 0.427611E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.225779E+10 | 0.00 | 0.00 | 0.00 | 0.839539E+10 | 0.00 | 0.305524E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_10:10
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.244876E+10 | 0.00 | 0.00 | 0.00 | 0.437930E+09 | 0.00 | 0.456241E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.221775E+10 | 0.00 | 0.00 | 0.00 | 0.131746E+10 | 0.00 | 72116853.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.250157E+10 | 0.00 | 0.00 | 0.00 | 0.336491E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.237616E+10 | 0.00 | 0.00 | 0.00 | 0.584426E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.247669E+10 | 0.00 | 0.00 | 0.00 | 0.860050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.241736E+10 | 0.00 | 0.00 | 0.00 | 0.911582E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.243829E+10 | 0.00 | 0.00 | 0.00 | 0.914184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.250187E+10 | 0.00 | 0.00 | 0.00 | 0.898650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.237616E+10 | 0.00 | 0.00 | 0.00 | 0.741030E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.244876E+10 | 0.00 | 0.00 | 0.00 | 0.528992E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.237616E+10 | 0.00 | 0.00 | 0.00 | 0.280367E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.243556E+10 | 0.00 | 0.00 | 0.00 | 0.836918E+09 | 0.00 | 85443569.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.290151E+11 | 0.00 | 0.00 | 0.00 | 0.631500E+11 | 0.00 | 0.613802E+09 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.221775E+10 | 0.00 | 0.00 | 0.00 | 0.437930E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.250187E+10 | 0.00 | 0.00 | 0.00 | 0.914184E+10 | 0.00 | 0.456241E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.261261E+10 | 640951.77 | 0.00 | 15022490.40 | 0.00 | 19428109.96 | 0.690305E+10 | 0.00 | 0.73 |
February | 0.100628E+10 | 0.320296E+09 | 0.00 | 15249997.91 | 0.00 | 0.00 | 0.338321E+10 | 0.00 | 0.74 |
March | 0.180240E+09 | 0.387705E+10 | 0.00 | 7690876.97 | 5370137.21 | 0.00 | 0.813180E+09 | 0.00 | 0.74 |
April | 3853669.09 | 0.111018E+11 | 0.00 | 852591.01 | 72818291.77 | 0.00 | 21784293.46 | 0.00 | 0.74 |
May | 0.00 | 0.214909E+11 | 0.00 | 169145.89 | 69553918.53 | 0.00 | 0.00 | 0.00 | 0.75 |
June | 0.00 | 0.275568E+11 | 0.00 | 0.00 | 79933645.43 | 0.00 | 0.00 | 0.00 | 0.75 |
July | 0.00 | 0.338191E+11 | 0.00 | 0.00 | 51125537.66 | 0.00 | 0.00 | 0.00 | 0.75 |
August | 0.00 | 0.337917E+11 | 0.00 | 0.00 | 76832789.64 | 0.00 | 0.00 | 0.00 | 0.75 |
September | 0.00 | 0.260958E+11 | 0.00 | 0.00 | 0.130301E+09 | 0.00 | 0.00 | 0.00 | 0.75 |
October | 22093308.16 | 0.101203E+11 | 0.00 | 1336486.67 | 57871218.77 | 0.00 | 79505522.85 | 0.00 | 0.74 |
November | 0.246591E+09 | 0.199256E+10 | 0.00 | 12044529.97 | 0.00 | 0.00 | 0.200959E+10 | 0.00 | 0.73 |
December | 0.160853E+10 | 18354807.18 | 0.00 | 18322990.51 | 0.00 | 0.00 | 0.654746E+10 | 0.00 | 0.73 |
Annual Sum or Average | 0.568020E+10 | 0.170185E+12 | 0.00 | 70689109.32 | 0.543807E+09 | 19428109.96 | 0.197578E+11 | 0.00 | 0.74 |
Minimum of Months | 0.00 | 640951.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.73 |
Maximum of Months | 0.261261E+10 | 0.338191E+11 | 0.00 | 18322990.51 | 0.130301E+09 | 19428109.96 | 0.690305E+10 | 0.00 | 0.75 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.966596E+09 | 294322.31 | 0.00 | 8210401.24 | 0.00 | 518299.91 | 0.223409E+10 | 0.00 | 0.56 |
February | 0.374715E+09 | 0.160595E+09 | 0.00 | 8133699.95 | 182471.82 | 0.00 | 0.976027E+09 | 0.00 | 0.57 |
March | 39060621.58 | 0.173813E+10 | 0.00 | 3763692.18 | 7532651.94 | 0.00 | 0.254090E+09 | 0.00 | 0.59 |
April | 1774993.61 | 0.467690E+10 | 0.00 | 430664.54 | 40051749.31 | 0.00 | 7703023.80 | 0.00 | 0.60 |
May | 0.00 | 0.918617E+10 | 0.00 | 42202.24 | 29343195.20 | 0.00 | 0.00 | 0.00 | 0.63 |
June | 0.00 | 0.117792E+11 | 0.00 | 0.00 | 39827652.74 | 0.00 | 0.00 | 0.00 | 0.64 |
July | 0.00 | 0.144338E+11 | 0.00 | 0.00 | 33836359.03 | 0.00 | 0.00 | 0.00 | 0.64 |
August | 0.00 | 0.145555E+11 | 0.00 | 0.00 | 56715536.43 | 0.00 | 0.00 | 0.00 | 0.64 |
September | 0.00 | 0.110325E+11 | 0.00 | 0.00 | 38454674.56 | 0.00 | 0.00 | 0.00 | 0.63 |
October | 3333405.33 | 0.437452E+10 | 0.00 | 309209.26 | 46530494.06 | 0.00 | 9951741.83 | 0.00 | 0.60 |
November | 79477918.21 | 0.981787E+09 | 0.00 | 5678966.30 | 1561080.97 | 0.00 | 0.462173E+09 | 0.00 | 0.58 |
December | 0.658631E+09 | 9377920.38 | 0.00 | 9653257.85 | 0.00 | 0.00 | 0.190278E+10 | 0.00 | 0.56 |
Annual Sum or Average | 0.212359E+10 | 0.729288E+11 | 0.00 | 36222093.56 | 0.294036E+09 | 518299.91 | 0.584682E+10 | 0.00 | 0.60 |
Minimum of Months | 0.00 | 294322.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.56 |
Maximum of Months | 0.966596E+09 | 0.145555E+11 | 0.00 | 9653257.85 | 56715536.43 | 518299.91 | 0.223409E+10 | 0.00 | 0.64 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.182290E+10 | 349040.83 | 0.00 | 3807529.77 | 0.00 | 57287231.27 | 0.154878E+10 | 0.00 | 0.58 |
February | 0.870084E+09 | 0.150512E+09 | 0.00 | 3993581.74 | 525318.31 | 0.00 | 0.752196E+09 | 0.00 | 0.59 |
March | 0.156907E+09 | 0.150589E+10 | 0.00 | 2213710.95 | 66392574.23 | 0.00 | 0.323052E+09 | 0.00 | 0.60 |
April | 2112025.67 | 0.409848E+10 | 0.00 | 405403.08 | 0.246073E+09 | 0.00 | 8272353.71 | 0.00 | 0.59 |
May | 11008.79 | 0.797575E+10 | 0.00 | 270644.96 | 0.460597E+09 | 0.00 | 74324.29 | 0.00 | 0.60 |
June | 0.00 | 0.997053E+10 | 0.00 | 81921.49 | 0.608041E+09 | 0.00 | 0.00 | 0.00 | 0.61 |
July | 0.00 | 0.118443E+11 | 0.00 | 0.00 | 0.701215E+09 | 0.00 | 0.00 | 0.00 | 0.60 |
August | 0.00 | 0.121184E+11 | 0.00 | 0.00 | 0.718696E+09 | 0.00 | 0.00 | 0.00 | 0.61 |
September | 0.00 | 0.903438E+10 | 0.00 | 47774.43 | 0.572775E+09 | 0.00 | 0.00 | 0.00 | 0.60 |
October | 18828688.53 | 0.371852E+10 | 0.00 | 971081.51 | 0.200313E+09 | 0.00 | 80385438.23 | 0.00 | 0.59 |
November | 0.318085E+09 | 0.903411E+09 | 0.00 | 2705765.19 | 13441620.45 | 0.00 | 0.534458E+09 | 0.00 | 0.59 |
December | 0.142069E+10 | 9083559.28 | 0.00 | 5034172.23 | 0.00 | 0.00 | 0.137335E+10 | 0.00 | 0.58 |
Annual Sum or Average | 0.460962E+10 | 0.613295E+11 | 0.00 | 19531585.35 | 0.358807E+10 | 57287231.27 | 0.462057E+10 | 0.00 | 0.59 |
Minimum of Months | 0.00 | 349040.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 |
Maximum of Months | 0.182290E+10 | 0.121184E+11 | 0.00 | 5034172.23 | 0.718696E+09 | 57287231.27 | 0.154878E+10 | 0.00 | 0.61 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.184826E+10 | 339097.85 | 0.00 | 3432541.07 | 0.00 | 93262045.65 | 0.147225E+10 | 0.00 | 0.58 |
February | 0.890083E+09 | 0.148830E+09 | 0.00 | 3794157.70 | 515652.28 | 0.00 | 0.729138E+09 | 0.00 | 0.59 |
March | 0.160854E+09 | 0.150426E+10 | 0.00 | 2168148.22 | 66506790.99 | 0.00 | 0.319814E+09 | 0.00 | 0.60 |
April | 2099825.19 | 0.410140E+10 | 0.00 | 418877.21 | 0.246644E+09 | 0.00 | 8212766.54 | 0.00 | 0.59 |
May | 12419.42 | 0.798822E+10 | 0.00 | 280644.07 | 0.456313E+09 | 0.00 | 74625.69 | 0.00 | 0.60 |
June | 0.00 | 0.998955E+10 | 0.00 | 87246.16 | 0.599344E+09 | 0.00 | 0.00 | 0.00 | 0.61 |
July | 0.00 | 0.118599E+11 | 0.00 | 0.00 | 0.701137E+09 | 0.00 | 0.00 | 0.00 | 0.60 |
August | 0.00 | 0.121260E+11 | 0.00 | 0.00 | 0.719344E+09 | 0.00 | 0.00 | 0.00 | 0.61 |
September | 0.00 | 0.903984E+10 | 0.00 | 52353.12 | 0.571976E+09 | 0.00 | 0.00 | 0.00 | 0.60 |
October | 18762334.28 | 0.372011E+10 | 0.00 | 978342.47 | 0.200246E+09 | 0.00 | 80800962.01 | 0.00 | 0.59 |
November | 0.345363E+09 | 0.901352E+09 | 0.00 | 2628768.13 | 13465391.98 | 0.00 | 0.508138E+09 | 0.00 | 0.59 |
December | 0.149247E+10 | 8839106.52 | 0.00 | 4706994.17 | 0.00 | 0.00 | 0.129391E+10 | 0.00 | 0.58 |
Annual Sum or Average | 0.475791E+10 | 0.613886E+11 | 0.00 | 18548072.32 | 0.357549E+10 | 93262045.65 | 0.441234E+10 | 0.00 | 0.59 |
Minimum of Months | 0.00 | 339097.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 |
Maximum of Months | 0.184826E+10 | 0.121260E+11 | 0.00 | 4706994.17 | 0.719344E+09 | 93262045.65 | 0.147225E+10 | 0.00 | 0.61 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.185811E+10 | 324138.77 | 0.00 | 3108525.35 | 0.00 | 0.135940E+09 | 0.140655E+10 | 0.00 | 0.58 |
February | 0.917941E+09 | 0.146518E+09 | 0.00 | 3573592.66 | 508475.30 | 0.00 | 0.700132E+09 | 0.00 | 0.59 |
March | 0.183135E+09 | 0.149592E+10 | 0.00 | 2063472.68 | 66695300.72 | 0.00 | 0.301214E+09 | 0.00 | 0.60 |
April | 2083323.39 | 0.409581E+10 | 0.00 | 380318.00 | 0.246537E+09 | 0.00 | 8278739.15 | 0.00 | 0.59 |
May | 9847.84 | 0.797417E+10 | 0.00 | 262997.57 | 0.459799E+09 | 0.00 | 75690.43 | 0.00 | 0.60 |
June | 0.00 | 0.996886E+10 | 0.00 | 84984.22 | 0.604528E+09 | 0.00 | 0.00 | 0.00 | 0.61 |
July | 0.00 | 0.118402E+11 | 0.00 | 0.00 | 0.701628E+09 | 0.00 | 0.00 | 0.00 | 0.60 |
August | 0.00 | 0.121019E+11 | 0.00 | 0.00 | 0.717572E+09 | 0.00 | 0.00 | 0.00 | 0.61 |
September | 0.00 | 0.901581E+10 | 0.00 | 49460.24 | 0.570356E+09 | 0.00 | 0.00 | 0.00 | 0.60 |
October | 19205529.99 | 0.370525E+10 | 0.00 | 935625.84 | 0.200881E+09 | 0.00 | 82445807.73 | 0.00 | 0.59 |
November | 0.375372E+09 | 0.895336E+09 | 0.00 | 2511439.23 | 13483205.58 | 0.00 | 0.481861E+09 | 0.00 | 0.59 |
December | 0.153328E+10 | 8571458.96 | 0.00 | 4404311.22 | 0.00 | 0.00 | 0.124760E+10 | 0.00 | 0.58 |
Annual Sum or Average | 0.488913E+10 | 0.612487E+11 | 0.00 | 17374727.01 | 0.358199E+10 | 0.135940E+09 | 0.422816E+10 | 0.00 | 0.59 |
Minimum of Months | 0.00 | 324138.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 |
Maximum of Months | 0.185811E+10 | 0.121019E+11 | 0.00 | 4404311.22 | 0.717572E+09 | 0.135940E+09 | 0.140655E+10 | 0.00 | 0.61 |
Report: MechanicalVentilationLoadsMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.298048E+10 | 0.00 | 0.00 | 5072976.32 | 0.00 | 0.249256E+09 | 0.278479E+10 | 0.00 | 0.54 |
February | 0.126346E+10 | 0.238837E+09 | 0.00 | 6638940.19 | 394079.68 | 0.00 | 0.140467E+10 | 0.00 | 0.54 |
March | 0.220725E+09 | 0.298816E+10 | 0.00 | 3730283.46 | 45869482.88 | 0.00 | 0.406135E+09 | 0.00 | 0.55 |
April | 3316071.44 | 0.816299E+10 | 0.00 | 298941.18 | 0.213262E+09 | 0.00 | 6144558.44 | 0.00 | 0.55 |
May | 0.00 | 0.157916E+11 | 0.00 | 148315.68 | 0.239483E+09 | 0.00 | 0.00 | 0.00 | 0.56 |
June | 0.00 | 0.196972E+11 | 0.00 | 98968.50 | 0.258249E+09 | 0.00 | 0.00 | 0.00 | 0.56 |
July | 0.00 | 0.229701E+11 | 0.00 | 0.00 | 0.432841E+09 | 0.00 | 0.00 | 0.00 | 0.55 |
August | 0.00 | 0.239047E+11 | 0.00 | 0.00 | 0.356025E+09 | 0.00 | 0.00 | 0.00 | 0.56 |
September | 0.00 | 0.176505E+11 | 0.00 | 88525.59 | 0.436860E+09 | 0.00 | 0.00 | 0.00 | 0.55 |
October | 23029043.46 | 0.740360E+10 | 0.00 | 941897.69 | 0.187187E+09 | 0.00 | 57689299.56 | 0.00 | 0.54 |
November | 0.337506E+09 | 0.167788E+10 | 0.00 | 4789908.70 | 21445769.77 | 0.00 | 0.811447E+09 | 0.00 | 0.54 |
December | 0.221321E+10 | 11292383.47 | 0.00 | 7758739.70 | 0.00 | 3876152.11 | 0.271847E+10 | 0.00 | 0.53 |
Annual Sum or Average | 0.704173E+10 | 0.120497E+12 | 0.00 | 29567497.00 | 0.219161E+10 | 0.253132E+09 | 0.818935E+10 | 0.00 | 0.55 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.53 |
Maximum of Months | 0.298048E+10 | 0.239047E+11 | 0.00 | 7758739.70 | 0.436860E+09 | 0.249256E+09 | 0.278479E+10 | 0.00 | 0.56 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.150492E+10 | 0.00 | 0.00 | 2436520.87 | 0.00 | 0.138451E+09 | 0.135672E+10 | 0.00 | 0.54 |
February | 0.641565E+09 | 0.117722E+09 | 0.00 | 3327182.90 | 193058.38 | 0.00 | 0.692697E+09 | 0.00 | 0.54 |
March | 0.112571E+09 | 0.148748E+10 | 0.00 | 1880079.83 | 23266167.80 | 0.00 | 0.201817E+09 | 0.00 | 0.55 |
April | 1105880.81 | 0.408292E+10 | 0.00 | 145776.67 | 0.105162E+09 | 0.00 | 3625116.70 | 0.00 | 0.55 |
May | 0.00 | 0.789988E+10 | 0.00 | 67415.22 | 0.112422E+09 | 0.00 | 0.00 | 0.00 | 0.56 |
June | 0.00 | 0.983476E+10 | 0.00 | 48215.39 | 0.131545E+09 | 0.00 | 0.00 | 0.00 | 0.56 |
July | 0.00 | 0.114496E+11 | 0.00 | 0.00 | 0.221509E+09 | 0.00 | 0.00 | 0.00 | 0.55 |
August | 0.00 | 0.119190E+11 | 0.00 | 0.00 | 0.170244E+09 | 0.00 | 0.00 | 0.00 | 0.56 |
September | 0.00 | 0.881799E+10 | 0.00 | 60216.12 | 0.196474E+09 | 0.00 | 0.00 | 0.00 | 0.55 |
October | 10485407.82 | 0.369202E+10 | 0.00 | 459961.11 | 89689626.53 | 0.00 | 30585021.28 | 0.00 | 0.54 |
November | 0.174365E+09 | 0.832727E+09 | 0.00 | 2411817.19 | 10503235.28 | 0.00 | 0.401580E+09 | 0.00 | 0.54 |
December | 0.112742E+10 | 5561347.81 | 0.00 | 3861497.93 | 0.00 | 1937465.31 | 0.133854E+10 | 0.00 | 0.53 |
Annual Sum or Average | 0.357243E+10 | 0.601396E+11 | 0.00 | 14698683.23 | 0.106101E+10 | 0.140388E+09 | 0.402557E+10 | 0.00 | 0.55 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.53 |
Maximum of Months | 0.150492E+10 | 0.119190E+11 | 0.00 | 3861497.93 | 0.221509E+09 | 0.138451E+09 | 0.135672E+10 | 0.00 | 0.56 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.152329E+10 | 0.00 | 0.00 | 2326175.42 | 0.00 | 0.147729E+09 | 0.132385E+10 | 0.00 | 0.54 |
February | 0.653480E+09 | 0.116736E+09 | 0.00 | 3243908.86 | 194452.56 | 0.00 | 0.680870E+09 | 0.00 | 0.54 |
March | 0.117817E+09 | 0.148361E+10 | 0.00 | 1842872.71 | 23289066.93 | 0.00 | 0.197568E+09 | 0.00 | 0.55 |
April | 1093910.78 | 0.408036E+10 | 0.00 | 142864.67 | 0.104738E+09 | 0.00 | 3648071.77 | 0.00 | 0.55 |
May | 0.00 | 0.789377E+10 | 0.00 | 66360.85 | 0.111736E+09 | 0.00 | 0.00 | 0.00 | 0.56 |
June | 0.00 | 0.982136E+10 | 0.00 | 47411.42 | 0.134894E+09 | 0.00 | 0.00 | 0.00 | 0.56 |
July | 0.00 | 0.114350E+11 | 0.00 | 0.00 | 0.222717E+09 | 0.00 | 0.00 | 0.00 | 0.55 |
August | 0.00 | 0.119037E+11 | 0.00 | 0.00 | 0.170084E+09 | 0.00 | 0.00 | 0.00 | 0.56 |
September | 0.00 | 0.880426E+10 | 0.00 | 60385.75 | 0.196738E+09 | 0.00 | 0.00 | 0.00 | 0.55 |
October | 10861697.14 | 0.368490E+10 | 0.00 | 451728.69 | 89974694.19 | 0.00 | 30737953.47 | 0.00 | 0.54 |
November | 0.177753E+09 | 0.830234E+09 | 0.00 | 2373463.01 | 10535193.57 | 0.00 | 0.399977E+09 | 0.00 | 0.54 |
December | 0.113037E+10 | 5527719.48 | 0.00 | 3750206.93 | 0.00 | 5667907.28 | 0.133068E+10 | 0.00 | 0.53 |
Annual Sum or Average | 0.361467E+10 | 0.600594E+11 | 0.00 | 14305378.31 | 0.106490E+10 | 0.153397E+09 | 0.396733E+10 | 0.00 | 0.55 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.53 |
Maximum of Months | 0.152329E+10 | 0.119037E+11 | 0.00 | 3750206.93 | 0.222717E+09 | 0.147729E+09 | 0.133068E+10 | 0.00 | 0.56 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.155379E+10 | 0.00 | 0.00 | 2085457.51 | 0.00 | 0.192173E+09 | 0.123333E+10 | 0.00 | 0.54 |
February | 0.669974E+09 | 0.114612E+09 | 0.00 | 3045769.94 | 198325.70 | 1230692.45 | 0.659926E+09 | 0.00 | 0.54 |
March | 0.128091E+09 | 0.147561E+10 | 0.00 | 1745107.95 | 23014752.85 | 0.00 | 0.189222E+09 | 0.00 | 0.55 |
April | 1086180.74 | 0.407743E+10 | 0.00 | 137896.73 | 0.104154E+09 | 0.00 | 3719037.32 | 0.00 | 0.55 |
May | 0.00 | 0.789231E+10 | 0.00 | 65271.36 | 0.111816E+09 | 0.00 | 0.00 | 0.00 | 0.56 |
June | 0.00 | 0.982379E+10 | 0.00 | 45128.56 | 0.134186E+09 | 0.00 | 0.00 | 0.00 | 0.56 |
July | 0.00 | 0.114438E+11 | 0.00 | 0.00 | 0.222495E+09 | 0.00 | 0.00 | 0.00 | 0.55 |
August | 0.00 | 0.119125E+11 | 0.00 | 0.00 | 0.172456E+09 | 0.00 | 0.00 | 0.00 | 0.56 |
September | 0.00 | 0.881336E+10 | 0.00 | 60382.15 | 0.191876E+09 | 0.00 | 0.00 | 0.00 | 0.55 |
October | 11000761.33 | 0.368165E+10 | 0.00 | 439251.02 | 89755262.63 | 0.00 | 31435811.64 | 0.00 | 0.54 |
November | 0.191659E+09 | 0.825824E+09 | 0.00 | 2301922.84 | 10568535.83 | 0.00 | 0.388624E+09 | 0.00 | 0.54 |
December | 0.115092E+10 | 5448775.14 | 0.00 | 3495804.97 | 0.00 | 14074873.25 | 0.129526E+10 | 0.00 | 0.53 |
Annual Sum or Average | 0.370652E+10 | 0.600663E+11 | 0.00 | 13421993.03 | 0.106052E+10 | 0.207478E+09 | 0.380152E+10 | 0.00 | 0.55 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.53 |
Maximum of Months | 0.155379E+10 | 0.119125E+11 | 0.00 | 3495804.97 | 0.222495E+09 | 0.192173E+09 | 0.129526E+10 | 0.00 | 0.56 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:18:56
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.144829E+10 | 0.00 | 0.00 | 1919864.36 | 0.00 | 0.359586E+09 | 0.114981E+10 | 0.00 | 0.54 |
February | 0.639169E+09 | 0.111834E+09 | 0.00 | 2906051.56 | 206829.04 | 76009031.66 | 0.596111E+09 | 0.00 | 0.54 |
March | 0.157480E+09 | 0.145718E+10 | 0.00 | 1687077.80 | 20242211.08 | 0.00 | 0.169396E+09 | 0.00 | 0.55 |
April | 1214776.72 | 0.407114E+10 | 0.00 | 140891.39 | 92046749.96 | 0.00 | 4545598.27 | 0.00 | 0.55 |
May | 0.00 | 0.791218E+10 | 0.00 | 107276.79 | 90723316.31 | 0.00 | 14463.71 | 0.00 | 0.56 |
June | 0.00 | 0.990533E+10 | 0.00 | 83397.33 | 0.102847E+09 | 0.00 | 0.00 | 0.00 | 0.56 |
July | 0.00 | 0.115736E+11 | 0.00 | 2210.71 | 0.193380E+09 | 0.00 | 0.00 | 0.00 | 0.55 |
August | 0.00 | 0.121017E+11 | 0.00 | 0.00 | 0.143612E+09 | 0.00 | 0.00 | 0.00 | 0.56 |
September | 0.00 | 0.895939E+10 | 0.00 | 137773.56 | 0.173404E+09 | 0.00 | 0.00 | 0.00 | 0.55 |
October | 11080267.58 | 0.371772E+10 | 0.00 | 413180.62 | 87249675.27 | 0.00 | 32472465.27 | 0.00 | 0.54 |
November | 0.214946E+09 | 0.824113E+09 | 0.00 | 2315812.62 | 10061946.04 | 0.00 | 0.363649E+09 | 0.00 | 0.54 |
December | 0.114551E+10 | 5336513.78 | 0.00 | 3379489.81 | 0.00 | 56484633.00 | 0.121846E+10 | 0.00 | 0.53 |
Annual Sum or Average | 0.361769E+10 | 0.606395E+11 | 0.00 | 13093026.54 | 0.913774E+09 | 0.492080E+09 | 0.353446E+10 | 0.00 | 0.55 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.53 |
Maximum of Months | 0.144829E+10 | 0.121017E+11 | 0.00 | 3379489.81 | 0.193380E+09 | 0.359586E+09 | 0.121846E+10 | 0.00 | 0.56 |