Program Version:EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:18
Tabular Output Report in Format: HTML
Building: RetailStripmall
Environment: RUNPERIOD 1 ** Great Falls Intl Arpt MT USA TMY3 WMO#=727750
Simulation Timestamp: 2020-06-03 19:18:53
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2020-06-03 19:18:53
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1597.82 | 764.39 | 764.39 |
Net Site Energy | 1597.82 | 764.39 | 764.39 |
Total Source Energy | 3861.91 | 1847.52 | 1847.52 |
Net Source Energy | 3861.91 | 1847.52 | 1847.52 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 2090.32 |
Net Conditioned Building Area | 2090.32 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 575.31 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 50.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 502.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 91.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 128.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 183.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 66.01 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1022.51 | 575.31 | 0.00 | 0.00 | 0.00 | 87.30 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 575.31 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 50.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 502.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 91.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 128.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 183.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 66.01 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 283.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 143.88 | 275.23 | 0.00 | 0.00 | 0.00 | 0.04 |
Other | 61.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 489.16 | 275.23 | 0.00 | 0.00 | 0.00 | 0.04 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 283.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 143.88 | 275.23 | 0.00 | 0.00 | 0.00 | 0.04 |
Other | 61.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 489.16 | 275.23 | 0.00 | 0.00 | 0.00 | 0.04 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1022.506 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1022.506 | 100.00 |
Total On-Site and Utility Electric Sources | 1022.506 | 100.00 |
Total Electricity End Uses | 1022.506 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 87.30 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 87.30 | 100.00 |
Total Water End Uses | 87.30 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 0.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 2329.33 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Meter |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2015
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Meter |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTRIPMALL
| Meter |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 6B
| Meter |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MT_GREATFALLS
| Meter |ZoneCoolingSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ZoneHeatingSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ZoneElectricSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |SpaceGainsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |PeakSpaceGainsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |SpaceGainComponentsAtCoolingPeakMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ComfortReportSimple55Monthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |OccupantComfortDataSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |DXReportMonthly
| PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL |WindowReportMonthly
| LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR |WindowEnergyReportMonthly
| LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR |WindowZoneSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |WindowEnergyZoneSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| GAS TANK1 | GAS TANK2 | GAS TANK3 | GAS TANK4 | GAS TANK5 | GAS TANK6 | GAS TANK7 |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC_1:1_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_2:2_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_3:3_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_4:4_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_5:5_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_6:6_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_7:7_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_8:8_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_9:9_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_10:10_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL |FanReportMonthly
| PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN |ZoneTemperatureOscillationReportMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |MechanicalVentilationLoadsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2020-06-03 19:18:53
GeneralValue | |
Program Version and Build | EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:18 |
RunPeriod | RUNPERIOD 1 |
Weather File | Great Falls Intl Arpt MT USA TMY3 WMO#=727750 |
Latitude [deg] | 47.47 |
Longitude [deg] | -111.4 |
Elevation [m] | 1117.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Above Ground Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Window Opening Area [m2] | 124.29 | 0.00 | 0.00 | 124.29 | 0.00 |
Gross Window-Wall Ratio [%] | 10.50 | 0.00 | 0.00 | 26.24 | 0.00 |
Above Ground Window-Wall Ratio [%] | 10.50 | 0.00 | 0.00 | 26.24 | 0.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Above Ground Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Window Opening Area [m2] | 124.29 | 0.00 | 0.00 | 124.29 | 0.00 |
Gross Window-Wall Ratio [%] | 10.50 | 0.00 | 0.00 | 26.24 | 0.00 |
Above Ground Window-Wall Ratio [%] | 10.50 | 0.00 | 0.00 | 26.24 | 0.00 |
Total | |
Gross Roof Area [m2] | 2090.32 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
LGSTORE1 | 348.39 | Yes | Yes | 1805.20 | 1.00 | 276.30 | 0.00 | 20.75 | 20.75 | 18.3665 | 11.61 | 4.3000 |
SMSTORE1 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.37 | 10.37 | 19.8089 | 11.61 | 4.3000 |
SMSTORE2 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.35 | 10.35 | 17.6561 | 11.61 | 4.3000 |
SMSTORE3 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.35 | 10.35 | 17.6561 | 11.61 | 4.3000 |
SMSTORE4 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.35 | 10.35 | 17.6561 | 11.61 | 4.3000 |
LGSTORE2 | 348.39 | Yes | Yes | 1805.20 | 1.00 | 157.89 | 0.00 | 20.70 | 20.70 | 13.1675 | 11.61 | 4.3000 |
SMSTORE5 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.35 | 10.35 | 13.1675 | 11.61 | 4.3000 |
SMSTORE6 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.35 | 10.35 | 13.1675 | 11.61 | 4.3000 |
SMSTORE7 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.35 | 10.35 | 13.1675 | 11.61 | 4.3000 |
SMSTORE8 | 174.19 | Yes | Yes | 902.60 | 1.00 | 197.36 | 0.00 | 10.35 | 10.35 | 13.1675 | 11.61 | 4.3000 |
Total | 2090.32 | 10831.20 | 1184.15 | 0.00 | 124.29 | 124.29 | 15.7096 | 11.61 | 4.3000 | |||
Conditioned Total | 2090.32 | 10831.20 | 1184.15 | 0.00 | 124.29 | 124.29 | 15.7096 | 11.61 | 4.3000 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:18:53
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 17-JUL-13:30 | 09-JAN-09:09 | - | - | - | 06-JAN-13:09 |
Heating | 0.00 | 312435.37 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 36558.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 31196.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 8089.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 11794.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 6273.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 93911.57 | 312435.37 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 312435.37 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 36558.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 31196.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 8089.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 11794.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 6273.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:18:53
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 623.64 | 0.00 | 0.00 | 0.00 |
Cooling | 160.95 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1589.92 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 288.23 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 407.66 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 582.46 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 209.05 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 3238.28 | 623.64 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 298.35 | 0.00 | 0.00 | 0.00 |
Cooling | 77.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 760.61 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 137.89 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 195.02 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 278.65 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 100.01 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1549.18 | 298.35 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 298.35 | 0.00 | 0.00 | 0.00 |
Cooling | 77.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 760.61 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 137.89 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 195.02 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 278.65 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 100.01 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1549.18 | 298.35 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:18:53
AirTerminal:SingleDuct:UncontrolledDesign Size Maximum Air Flow Rate [m3/s] | |
LGSTORE1 DIRECT AIR | 1.94 |
SMSTORE1 DIRECT AIR | 1.05 |
SMSTORE2 DIRECT AIR | 1.05 |
SMSTORE3 DIRECT AIR | 1.05 |
SMSTORE4 DIRECT AIR | 1.05 |
LGSTORE2 DIRECT AIR | 1.89 |
SMSTORE5 DIRECT AIR | 0.957015 |
SMSTORE6 DIRECT AIR | 0.946665 |
SMSTORE7 DIRECT AIR | 0.959700 |
SMSTORE8 DIRECT AIR | 1.05 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC_1:1 | 1.94 | 1.94 | 1.94 | 1.94 | 1.94 | 1.94 | 1.00 | 1.00 | 1.94 |
PSZ-AC_2:2 | 1.05 | 1.05 | 1.05 | 1.05 | 1.05 | 1.05 | 1.00 | 1.00 | 1.05 |
PSZ-AC_3:3 | 1.05 | 1.05 | 1.05 | 1.05 | 1.05 | 1.05 | 1.00 | 1.00 | 1.05 |
PSZ-AC_4:4 | 1.05 | 1.05 | 1.05 | 1.05 | 1.05 | 1.05 | 1.00 | 1.00 | 1.05 |
PSZ-AC_5:5 | 1.05 | 1.05 | 1.05 | 1.05 | 1.05 | 1.05 | 1.00 | 1.000000 | 1.05 |
PSZ-AC_6:6 | 1.89 | 1.89 | 1.89 | 1.89 | 1.89 | 1.89 | 1.00 | 1.000000 | 1.89 |
PSZ-AC_7:7 | 0.957015 | 0.957015 | 0.957015 | 0.957015 | 0.979412 | 0.979412 | 1.00 | 0.977132 | 0.979412 |
PSZ-AC_8:8 | 0.946665 | 0.946665 | 0.946665 | 0.946665 | 0.970479 | 0.970479 | 1.00 | 0.975462 | 0.970479 |
PSZ-AC_9:9 | 0.959700 | 0.959700 | 0.959700 | 0.959700 | 0.959700 | 0.959700 | 1.00 | 1.00 | 0.959700 |
PSZ-AC_10:10 | 1.05 | 1.05 | 1.05 | 1.05 | 1.05 | 1.05 | 1.00 | 1.00 | 1.05 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC_1:1_OA_CONTROLLER | 1.94 | 0.411453 |
PSZ-AC_2:2_OA_CONTROLLER | 1.05 | 0.205727 |
PSZ-AC_3:3_OA_CONTROLLER | 1.05 | 0.205727 |
PSZ-AC_4:4_OA_CONTROLLER | 1.05 | 0.205727 |
PSZ-AC_5:5_OA_CONTROLLER | 1.05 | 0.205727 |
PSZ-AC_6:6_OA_CONTROLLER | 1.89 | 0.411453 |
PSZ-AC_7:7_OA_CONTROLLER | 0.979412 | 0.205727 |
PSZ-AC_8:8_OA_CONTROLLER | 0.970479 | 0.205727 |
PSZ-AC_9:9_OA_CONTROLLER | 0.959700 | 0.205727 |
PSZ-AC_10:10_OA_CONTROLLER | 1.05 | 0.205727 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC_1:1_UNITARY_PACKAGE_DX | 1.94 | 1.94 | 1.94 | 1.28 | 32497.37 | 60015.82 | 40.00 | 1.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_DX | 1.05 | 1.05 | 1.05 | 1.05 | 17469.21 | 31651.70 | 40.00 | 1.00 |
PSZ-AC_3:3_UNITARY_PACKAGE_DX | 1.05 | 1.05 | 1.05 | 1.05 | 17422.97 | 31588.81 | 40.00 | 1.00 |
PSZ-AC_4:4_UNITARY_PACKAGE_DX | 1.05 | 1.05 | 1.05 | 1.05 | 17482.33 | 31668.80 | 40.00 | 1.00 |
PSZ-AC_5:5_UNITARY_PACKAGE_DX | 1.05 | 1.05 | 1.05 | 1.05 | 17381.70 | 31532.93 | 40.00 | 1.00 |
PSZ-AC_6:6_UNITARY_PACKAGE_DX | 1.89 | 1.89 | 1.89 | 1.25 | 31787.43 | 59057.68 | 40.00 | 1.00 |
PSZ-AC_7:7_UNITARY_PACKAGE_DX | 0.979412 | 0.979412 | 0.979412 | 0.979412 | 16385.04 | 29739.22 | 40.00 | 1.00 |
PSZ-AC_8:8_UNITARY_PACKAGE_DX | 0.970479 | 0.970479 | 0.970479 | 0.970479 | 16252.66 | 29532.26 | 40.00 | 1.00 |
PSZ-AC_9:9_UNITARY_PACKAGE_DX | 0.959700 | 0.959700 | 0.959700 | 0.959700 | 16092.91 | 29792.91 | 40.00 | 1.00 |
PSZ-AC_10:10_UNITARY_PACKAGE_DX | 1.05 | 1.05 | 1.05 | 1.05 | 17551.84 | 31561.97 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | Speed 2 Design Size Rated Total Cooling Capacity [W] | Speed 2 User-Specified Rated Total Cooling Capacity [W] | Speed 1 Design Size Rated Total Cooling Capacity [W] | Speed 1 User-Specified Rated Total Cooling Capacity [W] | Speed 2 Design Size Rated Sensible Heat Ratio | Speed 2 User-Specified Rated Sensible Heat Ratio | Speed 1 Design Size Rated Sensible Heat Ratio | Speed 1 User-Specified Rated Sensible Heat Ratio | |
PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | 1.94 | 0.970460 | 1.29 | 32129.12 | 32497.37 | 16248.68 | 16248.68 | 0.794489 | 0.794490 | 0.794490 | 0.794490 |
PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | 1.05 | 0.526330 | 0.701773 | 17425.26 | 17469.21 | 8734.60 | 8734.60 | 0.797730 | 0.797730 | 0.797730 | 0.797730 |
PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | 1.05 | 0.524760 | 0.699680 | 17373.28 | 17422.97 | 8711.49 | 8711.49 | 0.797607 | 0.797610 | 0.797610 | 0.797610 |
PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | 1.05 | 0.526760 | 0.702347 | 17439.50 | 17482.33 | 8741.17 | 8741.17 | 0.797754 | 0.797750 | 0.797750 | 0.797750 |
PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | 1.05 | 0.523360 | 0.697813 | 17326.93 | 17381.70 | 8690.85 | 8690.85 | 0.797497 | 0.797500 | 0.797500 | 0.797500 |
PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | 1.89 | 0.946505 | 1.26 | 31336.04 | 31787.43 | 15893.72 | 15893.72 | 0.793434 | 0.793430 | 0.793430 | 0.793430 |
PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | 0.979410 | 0.489705 | 0.652940 | 16212.71 | 16385.04 | 8192.52 | 8192.52 | 0.794789 | 0.794790 | 0.794790 | 0.794790 |
PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | 0.970480 | 0.485240 | 0.646987 | 16064.89 | 16252.66 | 8126.33 | 8126.33 | 0.794408 | 0.794410 | 0.794410 | 0.794410 |
PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | 0.959700 | 0.479850 | 0.639800 | 15886.44 | 16092.91 | 8046.45 | 8046.45 | 0.793938 | 0.793940 | 0.793940 | 0.793940 |
PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | 1.05 | 0.524085 | 0.698780 | 17350.94 | 17551.84 | 8775.92 | 8775.92 | 0.794447 | 0.794450 | 0.794450 | 0.794450 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | 1.94 | 2076.88 |
PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | 1.05 | 1165.46 |
PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | 1.05 | 1161.98 |
PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | 1.05 | 1166.41 |
PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | 1.05 | 1158.89 |
PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | 1.89 | 2025.61 |
PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | 0.979412 | 1084.36 |
PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | 0.970479 | 1074.47 |
PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | 0.959700 | 1062.54 |
PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | 1.05 | 1160.49 |
Design Size Nominal Capacity [W] | |
PSZ-AC_1:1_UNITARY_PACKAGE_HEATCOIL | 60015.82 |
PSZ-AC_2:2_UNITARY_PACKAGE_HEATCOIL | 31651.70 |
PSZ-AC_3:3_UNITARY_PACKAGE_HEATCOIL | 31588.81 |
PSZ-AC_4:4_UNITARY_PACKAGE_HEATCOIL | 31668.80 |
PSZ-AC_5:5_UNITARY_PACKAGE_HEATCOIL | 31532.93 |
PSZ-AC_6:6_UNITARY_PACKAGE_HEATCOIL | 59057.68 |
PSZ-AC_7:7_UNITARY_PACKAGE_HEATCOIL | 29739.22 |
PSZ-AC_8:8_UNITARY_PACKAGE_HEATCOIL | 29532.26 |
PSZ-AC_9:9_UNITARY_PACKAGE_HEATCOIL | 29792.91 |
PSZ-AC_10:10_UNITARY_PACKAGE_HEATCOIL | 31561.97 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:18:53
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
LGSTORE1_WALL_3 | LGSTORE1_WALL_3_DOOR_1 | LGSTORE1_WALL_3_DOOR_2 | |
LGSTORE1_WALL_1 | LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | |
SMSTORE1_WALL_1 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | |
SMSTORE1_WALL_3 | SMSTORE1_WALL_3_DOOR | |
SMSTORE2_WALL_1 | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | |
SMSTORE2_WALL_3 | SMSTORE2_WALL_3_DOOR | |
SMSTORE3_WALL_1 | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | |
SMSTORE3_WALL_3 | SMSTORE3_WALL_3_DOOR | |
SMSTORE4_WALL_1 | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | |
SMSTORE4_WALL_3 | SMSTORE4_WALL_3_DOOR | |
LGSTORE2_WALL_3 | LGSTORE2_WALL_3_DOOR_1 | LGSTORE2_WALL_3_DOOR_2 | |
LGSTORE2_WALL_1 | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | |
SMSTORE5_WALL_1 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | |
SMSTORE5_WALL_3 | SMSTORE5_WALL_3_DOOR | |
SMSTORE6_WALL_1 | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | |
SMSTORE6_WALL_3 | SMSTORE6_WALL_3_DOOR | |
SMSTORE7_WALL_1 | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | |
SMSTORE7_WALL_3 | SMSTORE7_WALL_3_DOOR | |
SMSTORE8_WALL_1 | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR | |
SMSTORE8_WALL_3 | SMSTORE8_WALL_3_DOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2020-06-03 19:18:53
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2020-06-03 19:18:53
VersionVersion ID | |
1 | 9.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 8.60 | 2.80 | -4.10 | -8.80 | -2.20 | 0.30 | 6.70 | 10.10 | 16.50 | 20.60 | 19.20 | 14.70 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Great Falls Intl Arpt MT USA TMY3 WMO#=727750 | 47.47 | -111.38 | -7.00 | 1117.00 | 88606 | 1.0531 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 7.03 | 29.40 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RetailStripmall | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 10 | 118 | 48 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | LGSTORE1 | 0.0 | 0.00 | 0.00 | 0.00 | 7.62 | 11.43 | 2.59 | 1 | 1 | 1 | 0.00 | 15.24 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 1805.20 | TARP | TARP | 348.39 | 276.30 | 247.76 | 20.75 | 6 | 8 | 0 | Yes |
2 | SMSTORE1 | 0.0 | 0.00 | 0.00 | 0.00 | 19.05 | 11.43 | 2.59 | 1 | 1 | 1 | 15.24 | 22.86 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.67 | 10.37 | 6 | 4 | 0 | Yes |
3 | SMSTORE2 | 0.0 | 0.00 | 0.00 | 0.00 | 26.67 | 11.43 | 2.59 | 1 | 1 | 1 | 22.86 | 30.48 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.35 | 6 | 4 | 0 | Yes |
4 | SMSTORE3 | 0.0 | 0.00 | 0.00 | 0.00 | 34.29 | 11.43 | 2.59 | 1 | 1 | 1 | 30.48 | 38.10 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.35 | 6 | 4 | 0 | Yes |
5 | SMSTORE4 | 0.0 | 0.00 | 0.00 | 0.00 | 41.91 | 11.43 | 2.59 | 1 | 1 | 1 | 38.10 | 45.72 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.35 | 6 | 4 | 0 | Yes |
6 | LGSTORE2 | 0.0 | 0.00 | 0.00 | 0.00 | 53.34 | 11.43 | 2.59 | 1 | 1 | 1 | 45.72 | 60.96 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 1805.20 | TARP | TARP | 348.39 | 157.89 | 129.43 | 20.70 | 6 | 8 | 0 | Yes |
7 | SMSTORE5 | 0.0 | 0.00 | 0.00 | 0.00 | 64.77 | 11.43 | 2.59 | 1 | 1 | 1 | 60.96 | 68.58 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.35 | 6 | 4 | 0 | Yes |
8 | SMSTORE6 | 0.0 | 0.00 | 0.00 | 0.00 | 72.39 | 11.43 | 2.59 | 1 | 1 | 1 | 68.58 | 76.20 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.35 | 6 | 4 | 0 | Yes |
9 | SMSTORE7 | 0.0 | 0.00 | 0.00 | 0.00 | 80.01 | 11.43 | 2.59 | 1 | 1 | 1 | 76.20 | 83.82 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.35 | 6 | 4 | 0 | Yes |
10 | SMSTORE8 | 0.0 | 0.00 | 0.00 | 0.00 | 87.63 | 11.43 | 2.59 | 1 | 1 | 1 | 83.82 | 91.44 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 197.36 | 183.13 | 10.35 | 6 | 4 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | LGSTORE1 | 348.39 | 30.0 | 11.614 | 8.610E-002 | 18.366 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 22.666 | No |
2 | SMSTORE1 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 19.809 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 24.109 | No |
3 | SMSTORE2 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 17.656 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 21.956 | No |
4 | SMSTORE3 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 17.656 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 21.956 | No |
5 | SMSTORE4 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 17.656 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 21.956 | No |
6 | LGSTORE2 | 348.39 | 30.0 | 11.614 | 8.610E-002 | 13.168 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 17.468 | No |
7 | SMSTORE5 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 13.168 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 17.468 | No |
8 | SMSTORE6 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 13.168 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 17.468 | No |
9 | SMSTORE7 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 13.168 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 17.468 | No |
10 | SMSTORE8 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 13.168 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 17.468 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | |
1 | LGSTORE1 | TYPE1_OCC_SCH | LGSTORE1 | 348.39 | 30.0 | 30.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 30 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
2 | SMSTORE1 | TYPE1_OCC_SCH | SMSTORE1 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
3 | SMSTORE2 | TYPE2_OCC_SCH | SMSTORE2 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
4 | SMSTORE3 | TYPE2_OCC_SCH | SMSTORE3 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
5 | SMSTORE4 | TYPE2_OCC_SCH | SMSTORE4 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
6 | LGSTORE2 | TYPE3_OCC_SCH | LGSTORE2 | 348.39 | 30.0 | 30.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 30 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
7 | SMSTORE5 | TYPE3_OCC_SCH | SMSTORE5 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
8 | SMSTORE6 | TYPE3_OCC_SCH | SMSTORE6 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
9 | SMSTORE7 | TYPE3_OCC_SCH | SMSTORE7 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
10 | SMSTORE8 | TYPE3_OCC_SCH | SMSTORE8 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | LGSTORE1_LIGHTS | TYPE1_LIGHT_SCH | LGSTORE1 | 348.39 | 30.0 | 4587.386 | 13.168 | 152.933 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 4587.386 |
2 | LGSTORE1_LIGHTS_ALLOWANCE | TYPE1_LIGHT_SCH | LGSTORE1 | 348.39 | 30.0 | 1811.251 | 5.199 | 60.383 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1811.251 |
3 | SMSTORE1_LIGHTS | TYPE1_LIGHT_SCH | SMSTORE1 | 174.19 | 15.0 | 2293.693 | 13.168 | 152.933 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2293.693 |
4 | SMSTORE1_LIGHTS_ALLOWANCE | TYPE1_LIGHT_SCH | SMSTORE1 | 174.19 | 15.0 | 1156.875 | 6.641 | 77.135 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1156.875 |
5 | SMSTORE2_LIGHTS | TYPE2_LIGHT_SCH | SMSTORE2 | 174.19 | 15.0 | 2293.693 | 13.168 | 152.933 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2293.693 |
6 | SMSTORE2_LIGHTS_ALLOWANCE | TYPE2_LIGHT_SCH | SMSTORE2 | 174.19 | 15.0 | 781.875 | 4.489 | 52.132 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 781.875 |
7 | SMSTORE3_LIGHTS | TYPE2_LIGHT_SCH | SMSTORE3 | 174.19 | 15.0 | 2293.693 | 13.168 | 152.933 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2293.693 |
8 | SMSTORE3_LIGHTS_ALLOWANCE | TYPE2_LIGHT_SCH | SMSTORE3 | 174.19 | 15.0 | 781.875 | 4.489 | 52.132 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 781.875 |
9 | SMSTORE4_LIGHTS | TYPE2_LIGHT_SCH | SMSTORE4 | 174.19 | 15.0 | 2293.693 | 13.168 | 152.933 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2293.693 |
10 | SMSTORE4_LIGHTS_ALLOWANCE | TYPE2_LIGHT_SCH | SMSTORE4 | 174.19 | 15.0 | 781.875 | 4.489 | 52.132 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 781.875 |
11 | LGSTORE2_LIGHTS | TYPE3_LIGHT_SCH | LGSTORE2 | 348.39 | 30.0 | 4587.386 | 13.168 | 152.933 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 4587.386 |
12 | LGSTORE2_LIGHTS_ALLOWANCE | TYPE3_LIGHT_SCH | LGSTORE2 | 348.39 | 30.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
13 | SMSTORE5_LIGHTS | TYPE3_LIGHT_SCH | SMSTORE5 | 174.19 | 15.0 | 2293.693 | 13.168 | 152.933 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2293.693 |
14 | SMSTORE5_LIGHTS_ALLOWANCE | TYPE3_LIGHT_SCH | SMSTORE5 | 174.19 | 15.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
15 | SMSTORE6_LIGHTS | TYPE3_LIGHT_SCH | SMSTORE6 | 174.19 | 15.0 | 2293.693 | 13.168 | 152.933 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2293.693 |
16 | SMSTORE6_LIGHTS_ALLOWANCE | TYPE3_LIGHT_SCH | SMSTORE6 | 174.19 | 15.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
17 | SMSTORE7_LIGHTS | TYPE3_LIGHT_SCH | SMSTORE7 | 174.19 | 15.0 | 2293.693 | 13.168 | 152.933 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2293.693 |
18 | SMSTORE7_LIGHTS_ALLOWANCE | TYPE3_LIGHT_SCH | SMSTORE7 | 174.19 | 15.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
19 | SMSTORE8_LIGHTS | TYPE3_LIGHT_SCH | SMSTORE8 | 174.19 | 15.0 | 2293.693 | 13.168 | 152.933 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2293.693 |
20 | SMSTORE8_LIGHTS_ALLOWANCE | TYPE3_LIGHT_SCH | SMSTORE8 | 174.19 | 15.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | LGSTORE1_MISCPLUG_EQUIP | TYPE1_EQUIP_SCH | LGSTORE1 | 348.39 | 30.0 | 1498.062 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1498.062 |
2 | SMSTORE1_MISCPLUG_EQUIP | TYPE1_EQUIP_SCH | SMSTORE1 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
3 | SMSTORE2_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE2 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
4 | SMSTORE3_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE3 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
5 | SMSTORE4_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE4 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
6 | LGSTORE2_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | LGSTORE2 | 348.39 | 30.0 | 1498.062 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1498.062 |
7 | SMSTORE5_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE5 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
8 | SMSTORE6_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE6 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
9 | SMSTORE7_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE7 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
10 | SMSTORE8_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE8 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.770 | 0.700 | Rough |
5 | NONRES_EXT_WALL | 20 | 4 | 7 | 0.167 | 0.3843 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
6 | LGSTORE1_FLOOR_FFACTOR | 30 | 2 | 7 | 0.167 | 0.1464 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
7 | SMSTORE1_FLOOR_FFACTOR | 31 | 2 | 7 | 0.167 | 0.8283E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
8 | SMSTORE2_FLOOR_FFACTOR | 32 | 2 | 7 | 0.167 | 0.8283E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | SMSTORE3_FLOOR_FFACTOR | 33 | 2 | 7 | 0.167 | 0.8283E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
10 | SMSTORE4_FLOOR_FFACTOR | 34 | 2 | 7 | 0.167 | 0.8283E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
11 | LGSTORE2_FLOOR_FFACTOR | 35 | 2 | 7 | 0.167 | 0.8283E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | SMSTORE5_FLOOR_FFACTOR | 36 | 2 | 7 | 0.167 | 0.8283E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | SMSTORE6_FLOOR_FFACTOR | 37 | 2 | 7 | 0.167 | 0.8283E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | SMSTORE7_FLOOR_FFACTOR | 38 | 2 | 7 | 0.167 | 0.8283E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | SMSTORE8_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.2111 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
6 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
7 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
8 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
9 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
10 | NONRES_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.368 |
11 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
12 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 6.756 |
13 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
14 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.00 |
15 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
16 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.00 |
17 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
18 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.00 |
19 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
20 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.00 |
21 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
22 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.00 |
23 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
24 | ~FC_Insulation_7 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.00 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_8 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.00 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_9 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.00 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
30 | ~FC_Insulation_10 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.659 |
31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009596 | 2.1009596 | 2.1009596 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
14 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
15 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
16 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
17 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
18 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
19 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
20 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
21 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
22 | 7 | -0.35963630E-12 | 0.61482467E-15 | -0.13288964E-12 | 0.15093609E-15 |
23 | 6 | 0.33258387E-07 | 0.11249777E-09 | 0.75805110E-08 | -0.16019892E-12 |
24 | 5 | -0.21313350E-03 | 0.93714421E-06 | -0.10927814E-03 | 0.74776115E-08 |
25 | 4 | 0.31870195 | 0.44521373E-03 | 0.10925225 | -0.37358013E-04 |
26 | 3 | -7.7913368 | 0.13499397E-01 | -2.4947666 | 0.31584435E-01 |
27 | 2 | 42.601618 | 0.47079245E-01 | 15.902165 | -0.35261900 |
28 | 1 | -81.870774 | 0.20888078E-01 | -29.712230 | 1.1068570 |
29 | 0 | 46.824331 | 0.41326549E-03 | 16.278015 | |
30 | 7 | -0.28997596E-08 | -0.17578320E-14 | 0.22751757E-14 | -0.53829073E-16 |
31 | 6 | 0.41991781E-05 | 0.27986603E-08 | 0.31940183E-02 | -0.26794102E-04 |
32 | 5 | -0.29588474E-03 | 0.16552611E-05 | -0.22396035 | 0.19582313E-02 |
33 | 4 | 0.67666006E-02 | 0.75295852E-04 | 4.8334724 | -0.45302727E-01 |
34 | 3 | -0.59297736E-01 | 0.59838054E-03 | -38.043598 | 0.39889893 |
35 | 2 | 0.21038411 | 0.99492606E-03 | 116.52712 | -1.4185167 |
36 | 1 | -0.30354941 | 0.30287292E-03 | -143.93272 | 2.0494576 |
37 | 0 | 0.14796861 | 0.73483799E-05 | 60.838472 | |
38 | 7 | -0.51571905E-08 | -0.97500959E-14 | 0.15789915E-14 | -0.32998988E-16 |
39 | 6 | 0.26247599E-05 | 0.15902949E-08 | 0.31989528E-02 | -0.26835497E-04 |
40 | 5 | -0.17282397E-03 | 0.93714128E-06 | -0.22424071 | 0.19607060E-02 |
41 | 4 | 0.38696203E-02 | 0.42548205E-04 | 4.8381400 | -0.45347597E-01 |
42 | 3 | -0.33643188E-01 | 0.33758390E-03 | -38.069955 | 0.39919029 |
43 | 2 | 0.11898200 | 0.56044665E-03 | 116.57840 | -1.4192028 |
44 | 1 | -0.17142224 | 0.17027190E-03 | -143.96290 | 2.0499538 |
45 | 0 | 0.83499932E-01 | 0.41268798E-05 | 60.838472 | |
46 | 7 | -0.51571905E-08 | -0.97500958E-14 | 0.15789913E-14 | -0.32998984E-16 |
47 | 6 | 0.26247599E-05 | 0.15902949E-08 | 0.31989528E-02 | -0.26835497E-04 |
48 | 5 | -0.17282397E-03 | 0.93714128E-06 | -0.22424071 | 0.19607060E-02 |
49 | 4 | 0.38696203E-02 | 0.42548205E-04 | 4.8381400 | -0.45347597E-01 |
50 | 3 | -0.33643188E-01 | 0.33758390E-03 | -38.069955 | 0.39919029 |
51 | 2 | 0.11898200 | 0.56044665E-03 | 116.57840 | -1.4192028 |
52 | 1 | -0.17142224 | 0.17027190E-03 | -143.96290 | 2.0499538 |
53 | 0 | 0.83499932E-01 | 0.41268798E-05 | 60.838472 | |
54 | 7 | -0.51571905E-08 | -0.97500959E-14 | 0.15789911E-14 | -0.32998980E-16 |
55 | 6 | 0.26247599E-05 | 0.15902949E-08 | 0.31989528E-02 | -0.26835497E-04 |
56 | 5 | -0.17282397E-03 | 0.93714128E-06 | -0.22424071 | 0.19607060E-02 |
57 | 4 | 0.38696203E-02 | 0.42548205E-04 | 4.8381400 | -0.45347597E-01 |
58 | 3 | -0.33643188E-01 | 0.33758390E-03 | -38.069955 | 0.39919029 |
59 | 2 | 0.11898200 | 0.56044665E-03 | 116.57840 | -1.4192028 |
60 | 1 | -0.17142224 | 0.17027190E-03 | -143.96290 | 2.0499538 |
61 | 0 | 0.83499932E-01 | 0.41268798E-05 | 60.838472 | |
62 | 7 | -0.51571905E-08 | -0.97500959E-14 | 0.15789915E-14 | -0.32998988E-16 |
63 | 6 | 0.26247599E-05 | 0.15902949E-08 | 0.31989528E-02 | -0.26835497E-04 |
64 | 5 | -0.17282397E-03 | 0.93714128E-06 | -0.22424071 | 0.19607060E-02 |
65 | 4 | 0.38696203E-02 | 0.42548205E-04 | 4.8381400 | -0.45347597E-01 |
66 | 3 | -0.33643188E-01 | 0.33758390E-03 | -38.069955 | 0.39919029 |
67 | 2 | 0.11898200 | 0.56044665E-03 | 116.57840 | -1.4192028 |
68 | 1 | -0.17142224 | 0.17027190E-03 | -143.96290 | 2.0499538 |
69 | 0 | 0.83499932E-01 | 0.41268798E-05 | 60.838472 | |
70 | 7 | -0.51571905E-08 | -0.97500958E-14 | 0.15789913E-14 | -0.32998984E-16 |
71 | 6 | 0.26247599E-05 | 0.15902949E-08 | 0.31989528E-02 | -0.26835497E-04 |
72 | 5 | -0.17282397E-03 | 0.93714128E-06 | -0.22424071 | 0.19607060E-02 |
73 | 4 | 0.38696203E-02 | 0.42548205E-04 | 4.8381400 | -0.45347597E-01 |
74 | 3 | -0.33643188E-01 | 0.33758390E-03 | -38.069955 | 0.39919029 |
75 | 2 | 0.11898200 | 0.56044665E-03 | 116.57840 | -1.4192028 |
76 | 1 | -0.17142224 | 0.17027190E-03 | -143.96290 | 2.0499538 |
77 | 0 | 0.83499932E-01 | 0.41268798E-05 | 60.838472 | |
78 | 7 | -0.51571905E-08 | -0.97500957E-14 | 0.15789917E-14 | -0.32998991E-16 |
79 | 6 | 0.26247599E-05 | 0.15902949E-08 | 0.31989528E-02 | -0.26835497E-04 |
80 | 5 | -0.17282397E-03 | 0.93714128E-06 | -0.22424071 | 0.19607060E-02 |
81 | 4 | 0.38696203E-02 | 0.42548205E-04 | 4.8381400 | -0.45347597E-01 |
82 | 3 | -0.33643188E-01 | 0.33758390E-03 | -38.069955 | 0.39919029 |
83 | 2 | 0.11898200 | 0.56044665E-03 | 116.57840 | -1.4192028 |
84 | 1 | -0.17142224 | 0.17027190E-03 | -143.96290 | 2.0499538 |
85 | 0 | 0.83499932E-01 | 0.41268798E-05 | 60.838472 | |
86 | 7 | -0.51571905E-08 | -0.97500959E-14 | 0.15789915E-14 | -0.32998988E-16 |
87 | 6 | 0.26247599E-05 | 0.15902949E-08 | 0.31989528E-02 | -0.26835497E-04 |
88 | 5 | -0.17282397E-03 | 0.93714128E-06 | -0.22424071 | 0.19607060E-02 |
89 | 4 | 0.38696203E-02 | 0.42548205E-04 | 4.8381400 | -0.45347597E-01 |
90 | 3 | -0.33643188E-01 | 0.33758390E-03 | -38.069955 | 0.39919029 |
91 | 2 | 0.11898200 | 0.56044665E-03 | 116.57840 | -1.4192028 |
92 | 1 | -0.17142224 | 0.17027190E-03 | -143.96290 | 2.0499538 |
93 | 0 | 0.83499932E-01 | 0.41268798E-05 | 60.838472 | |
94 | 7 | -0.51571905E-08 | -0.97500958E-14 | 0.15789913E-14 | -0.32998984E-16 |
95 | 6 | 0.26247599E-05 | 0.15902949E-08 | 0.31989528E-02 | -0.26835497E-04 |
96 | 5 | -0.17282397E-03 | 0.93714128E-06 | -0.22424071 | 0.19607060E-02 |
97 | 4 | 0.38696203E-02 | 0.42548205E-04 | 4.8381400 | -0.45347597E-01 |
98 | 3 | -0.33643188E-01 | 0.33758390E-03 | -38.069955 | 0.39919029 |
99 | 2 | 0.11898200 | 0.56044665E-03 | 116.57840 | -1.4192028 |
100 | 1 | -0.17142224 | 0.17027190E-03 | -143.96290 | 2.0499538 |
101 | 0 | 0.83499932E-01 | 0.41268798E-05 | 60.838472 | |
102 | 7 | -0.19967951E-08 | -0.58252365E-15 | 0.72897552E-14 | -0.10630581E-15 |
103 | 6 | 0.59274927E-05 | 0.40433693E-08 | 0.31889525E-02 | -0.26751606E-04 |
104 | 5 | -0.42514865E-03 | 0.23948505E-05 | -0.22367243 | 0.19556901E-02 |
105 | 4 | 0.97725356E-02 | 0.10900143E-03 | 4.8286774 | -0.45256634E-01 |
106 | 3 | -0.85796444E-01 | 0.86675557E-03 | -38.016512 | 0.39859954 |
107 | 2 | 0.30461848 | 0.14417950E-02 | 116.47440 | -1.4178116 |
108 | 1 | -0.43965446 | 0.43929230E-03 | -143.90169 | 2.0489476 |
109 | 0 | 0.21434897 | 0.10616597E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.36_SHGC_0.4 | 29 | 1 | VerySmooth | 2.045 | 0.394 | 0.315 | 0.401 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 3.65598E-002 | 0.31435 | 0.48154 | 0.48154 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11562 | 1.00000 | No |
Calculation Method | Value {days} | Allowable Number Figures in Shadow Overlap {} | Polygon Clipping Algorithm | Sky Diffuse Modeling Algorithm | External Shading Calculation Method | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | AverageOverDaysInFrequency | 30 | 15000 | SutherlandHodgman | SimpleSkyDiffuseModeling | InternalCalculation | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | GAS TANK1 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
2 | WaterHeater:Mixed | GAS TANK2 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
3 | WaterHeater:Mixed | GAS TANK3 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
4 | WaterHeater:Mixed | GAS TANK4 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
5 | WaterHeater:Mixed | GAS TANK5 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
6 | WaterHeater:Mixed | GAS TANK6 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
7 | WaterHeater:Mixed | GAS TANK7 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | LGSTORE1_WALL_2 | 0 | 118.41 | 56.08 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 4 | No | No |
2 | LGSTORE1_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 4 | No | No |
3 | LGSTORE1_WALL_3_DOOR_1 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 0 | No | No |
4 | LGSTORE1_WALL_3_DOOR_2 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 0 | No | No |
5 | LGSTORE1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 0 | No | No |
6 | LGSTORE1_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 4 | No | No |
7 | LGSTORE1_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 1 | No | No |
8 | LGSTORE1_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 1 | No | No |
9 | LGSTORE1_WALL_1_WINDOW_3 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 1 | No | No |
10 | LGSTORE1_WALL_1_WINDOW_4 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 1 | No | No |
11 | LGSTORE1_WALL_1_DOOR_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 1 | No | No |
12 | LGSTORE1_WALL_1_DOOR_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 1 | No | No |
13 | LGSTORE1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 0 | No | No |
14 | LGSTORE1_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 0 | No | No |
15 | LGSTORE1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 0 | No | No |
16 | SMSTORE1_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
17 | SMSTORE1_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
18 | SMSTORE1_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
19 | SMSTORE1_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
20 | SMSTORE1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
21 | SMSTORE1_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
22 | SMSTORE1_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
23 | SMSTORE1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
24 | SMSTORE1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
25 | SMSTORE1_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
26 | SMSTORE1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
27 | SMSTORE2_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
28 | SMSTORE2_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
29 | SMSTORE2_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
30 | SMSTORE2_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
31 | SMSTORE2_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
32 | SMSTORE2_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
33 | SMSTORE2_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
34 | SMSTORE2_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
35 | SMSTORE2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
36 | SMSTORE2_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
37 | SMSTORE2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
38 | SMSTORE3_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
39 | SMSTORE3_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
40 | SMSTORE3_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
41 | SMSTORE3_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
42 | SMSTORE3_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
43 | SMSTORE3_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
44 | SMSTORE3_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
45 | SMSTORE3_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
46 | SMSTORE3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
47 | SMSTORE3_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
48 | SMSTORE3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
49 | SMSTORE4_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
50 | SMSTORE4_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
51 | SMSTORE4_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
52 | SMSTORE4_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
53 | SMSTORE4_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
54 | SMSTORE4_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 3 | No | No |
55 | SMSTORE4_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
56 | SMSTORE4_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
57 | SMSTORE4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
58 | SMSTORE4_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
59 | SMSTORE4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
60 | LGSTORE2_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
61 | LGSTORE2_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 4 | No | No |
62 | LGSTORE2_WALL_3_DOOR_1 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
63 | LGSTORE2_WALL_3_DOOR_2 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
64 | LGSTORE2_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
65 | LGSTORE2_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 4 | No | No |
66 | LGSTORE2_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
67 | LGSTORE2_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
68 | LGSTORE2_WALL_1_WINDOW_3 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
69 | LGSTORE2_WALL_1_WINDOW_4 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
70 | LGSTORE2_WALL_1_DOOR_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
71 | LGSTORE2_WALL_1_DOOR_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
72 | LGSTORE2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
73 | LGSTORE2_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
74 | LGSTORE2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
75 | SMSTORE5_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
76 | SMSTORE5_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
77 | SMSTORE5_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
78 | SMSTORE5_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
79 | SMSTORE5_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
80 | SMSTORE5_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
81 | SMSTORE5_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
82 | SMSTORE5_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
83 | SMSTORE5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
84 | SMSTORE5_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
85 | SMSTORE5_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
86 | SMSTORE6_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
87 | SMSTORE6_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
88 | SMSTORE6_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
89 | SMSTORE6_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
90 | SMSTORE6_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
91 | SMSTORE6_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
92 | SMSTORE6_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
93 | SMSTORE6_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
94 | SMSTORE6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
95 | SMSTORE6_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
96 | SMSTORE6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
97 | SMSTORE7_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
98 | SMSTORE7_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
99 | SMSTORE7_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
100 | SMSTORE7_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
101 | SMSTORE7_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
102 | SMSTORE7_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 3 | No | No |
103 | SMSTORE7_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
104 | SMSTORE7_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
105 | SMSTORE7_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
106 | SMSTORE7_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
107 | SMSTORE7_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
108 | SMSTORE8_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 4 | No | No |
109 | SMSTORE8_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 1 | No | No |
110 | SMSTORE8_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 1 | No | No |
111 | SMSTORE8_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 1 | No | No |
112 | SMSTORE8_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
113 | SMSTORE8_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 3 | No | No |
114 | SMSTORE8_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
115 | SMSTORE8_WALL_4 | 0 | 118.41 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 3 | No | No |
116 | SMSTORE8_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
117 | SMSTORE8_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
118 | SMSTORE8_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | LGSTORE1_INFILTRATION | TYPE1_INFIL_SCH | LGSTORE1 | 348.39 | 30.0 | 0.159 | 4.569E-004 | 2.517E-004 | 0.317 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | LGSTORE1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | LGSTORE1 | 348.39 | 30.0 | 0.241 | 6.922E-004 | 3.813E-004 | 0.481 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | SMSTORE1_INFILTRATION | TYPE1_INFIL_SCH | SMSTORE1 | 174.19 | 15.0 | 4.561E-002 | 2.619E-004 | 1.775E-004 | 0.182 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | SMSTORE1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE1 | 174.19 | 15.0 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
5 | SMSTORE2_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE2 | 174.19 | 15.0 | 4.561E-002 | 2.618E-004 | 1.775E-004 | 0.182 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | SMSTORE2_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE2 | 174.19 | 15.0 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
7 | SMSTORE3_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE3 | 174.19 | 15.0 | 4.561E-002 | 2.618E-004 | 1.775E-004 | 0.182 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | SMSTORE3_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE3 | 174.19 | 15.0 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | SMSTORE4_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE4 | 174.19 | 15.0 | 4.561E-002 | 2.618E-004 | 1.775E-004 | 0.182 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | SMSTORE4_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE4 | 174.19 | 15.0 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
11 | LGSTORE2_INFILTRATION | TYPE3_INFIL_SCH | LGSTORE2 | 348.39 | 30.0 | 9.122E-002 | 2.618E-004 | 1.775E-004 | 0.182 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | LGSTORE2_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | LGSTORE2 | 348.39 | 30.0 | 0.241 | 6.922E-004 | 4.692E-004 | 0.481 | 1.000 | 0.000 | 0.000 | 0.000 |
13 | SMSTORE5_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE5 | 174.19 | 15.0 | 4.561E-002 | 2.618E-004 | 1.775E-004 | 0.182 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | SMSTORE5_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE5 | 174.19 | 15.0 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
15 | SMSTORE6_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE6 | 174.19 | 15.0 | 4.561E-002 | 2.618E-004 | 1.775E-004 | 0.182 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | SMSTORE6_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE6 | 174.19 | 15.0 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
17 | SMSTORE7_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE7 | 174.19 | 15.0 | 4.561E-002 | 2.618E-004 | 1.775E-004 | 0.182 | 0.000 | 0.000 | 0.224 | 0.000 |
18 | SMSTORE7_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE7 | 174.19 | 15.0 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
19 | SMSTORE8_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE8 | 174.19 | 15.0 | 0.113 | 6.514E-004 | 3.022E-004 | 0.453 | 0.000 | 0.000 | 0.224 | 0.000 |
20 | SMSTORE8_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE8 | 174.19 | 15.0 | 0.135 | 7.722E-004 | 3.583E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | LGSTORE1 | Mixing/Well-Stirred |
2 | SMSTORE1 | Mixing/Well-Stirred |
3 | SMSTORE2 | Mixing/Well-Stirred |
4 | SMSTORE3 | Mixing/Well-Stirred |
5 | SMSTORE4 | Mixing/Well-Stirred |
6 | LGSTORE2 | Mixing/Well-Stirred |
7 | SMSTORE5 | Mixing/Well-Stirred |
8 | SMSTORE6 | Mixing/Well-Stirred |
9 | SMSTORE7 | Mixing/Well-Stirred |
10 | SMSTORE8 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone LGSTORE1 | 1.2000 |
3 | Zone SMSTORE1 | 1.2000 |
4 | Zone SMSTORE2 | 1.2000 |
5 | Zone SMSTORE3 | 1.2000 |
6 | Zone SMSTORE4 | 1.2000 |
7 | Zone LGSTORE2 | 1.2000 |
8 | Zone SMSTORE5 | 1.2000 |
9 | Zone SMSTORE6 | 1.2000 |
10 | Zone SMSTORE7 | 1.2000 |
11 | Zone SMSTORE8 | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone LGSTORE1 | 1.2000 |
3 | Zone SMSTORE1 | 1.2000 |
4 | Zone SMSTORE2 | 1.2000 |
5 | Zone SMSTORE3 | 1.2000 |
6 | Zone SMSTORE4 | 1.2000 |
7 | Zone LGSTORE2 | 1.2000 |
8 | Zone SMSTORE5 | 1.2000 |
9 | Zone SMSTORE6 | 1.2000 |
10 | Zone SMSTORE7 | 1.2000 |
11 | Zone SMSTORE8 | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | LGSTORE1 | Cooling | 19226.46585 | 23071.75902 | 1.61744 | 1.94092 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 33.40000 | 6.26594E-003 | 348.38640 | 29.99610 | 0.41145 | 0.00000 |
2 | LGSTORE1 | Heating | 29465.42443 | 35358.50932 | 1.45220 | 1.74264 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -27.60000 | 3.41898E-004 | 348.38640 | 29.99610 | 0.41145 | 0.00000 |
3 | SMSTORE1 | Cooling | 10427.56190 | 12513.07428 | 0.87722 | 1.05266 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 33.40000 | 6.26594E-003 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
4 | SMSTORE1 | Heating | 14628.73554 | 17554.48265 | 0.72097 | 0.86516 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -27.60000 | 3.41898E-004 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
5 | SMSTORE2 | Cooling | 10396.39845 | 12475.67814 | 0.87460 | 1.04952 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 33.26667 | 6.26594E-003 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
6 | SMSTORE2 | Heating | 14795.22113 | 17754.26536 | 0.72917 | 0.87501 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -27.60000 | 3.41898E-004 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
7 | SMSTORE3 | Cooling | 10436.02629 | 12523.23155 | 0.87793 | 1.05352 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 33.26667 | 6.26594E-003 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
8 | SMSTORE3 | Heating | 14867.31912 | 17840.78295 | 0.73273 | 0.87927 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -27.60000 | 3.41898E-004 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
9 | SMSTORE4 | Cooling | 10368.71737 | 12442.46084 | 0.87227 | 1.04672 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 33.26667 | 6.26594E-003 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
10 | SMSTORE4 | Heating | 15007.73665 | 18009.28398 | 0.73965 | 0.88758 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -27.60000 | 3.41898E-004 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
11 | LGSTORE2 | Cooling | 18751.82960 | 22502.19552 | 1.57751 | 1.89301 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 33.26667 | 6.26594E-003 | 348.38640 | 29.99610 | 0.41145 | 0.00000 |
12 | LGSTORE2 | Heating | 28539.27679 | 34247.13215 | 1.40656 | 1.68788 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -27.60000 | 3.41898E-004 | 348.38640 | 29.99610 | 0.41145 | 0.00000 |
13 | SMSTORE5 | Cooling | 9773.24628 | 11727.89553 | 0.79751 | 0.95701 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 27.32000 | 6.26593E-003 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
14 | SMSTORE5 | Heating | 15342.47217 | 18410.96660 | 0.75614 | 0.90737 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -27.60000 | 3.41898E-004 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
15 | SMSTORE6 | Cooling | 9670.44524 | 11604.53429 | 0.78889 | 0.94666 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 27.32000 | 6.26593E-003 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
16 | SMSTORE6 | Heating | 15325.97607 | 18391.17128 | 0.75533 | 0.90640 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -27.60000 | 3.41898E-004 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
17 | SMSTORE7 | Cooling | 9506.68032 | 11408.01638 | 0.79975 | 0.95970 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 33.26667 | 6.26594E-003 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
18 | SMSTORE7 | Heating | 15521.28131 | 18625.53757 | 0.76496 | 0.91795 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -27.60000 | 3.41898E-004 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
19 | SMSTORE8 | Cooling | 9674.06551 | 11608.87861 | 0.81384 | 0.97661 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 32.86667 | 6.26593E-003 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
20 | SMSTORE8 | Heating | 17723.30111 | 21267.96133 | 0.87347 | 1.04817 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -27.60000 | 3.41898E-004 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC_1:1 | Cooling | Sensible | 26918.43 | 1.94092 | 1.94092 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-AC_1:1 | Heating | Sensible | 56051.24 | 1.74264 | 1.74264 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
3 | PSZ-AC_2:2 | Cooling | Sensible | 14423.92 | 1.05266 | 1.05266 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-AC_2:2 | Heating | Sensible | 27902.61 | 0.86516 | 0.86516 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
5 | PSZ-AC_3:3 | Cooling | Sensible | 14384.83 | 1.04952 | 1.04952 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
6 | PSZ-AC_3:3 | Heating | Sensible | 28099.49 | 0.87501 | 0.87501 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
7 | PSZ-AC_4:4 | Cooling | Sensible | 14430.95 | 1.05352 | 1.05352 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
8 | PSZ-AC_4:4 | Heating | Sensible | 28184.75 | 0.87927 | 0.87927 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
9 | PSZ-AC_5:5 | Cooling | Sensible | 14351.32 | 1.04672 | 1.04672 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
10 | PSZ-AC_5:5 | Heating | Sensible | 28350.79 | 0.88758 | 0.88758 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
11 | PSZ-AC_6:6 | Cooling | Sensible | 26348.38 | 1.89301 | 1.89301 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
12 | PSZ-AC_6:6 | Heating | Sensible | 54956.10 | 1.68788 | 1.68788 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
13 | PSZ-AC_7:7 | Cooling | Sensible | 13560.39 | 0.97941 | 0.97941 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
14 | PSZ-AC_7:7 | Heating | Sensible | 28746.63 | 0.90737 | 0.90737 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
15 | PSZ-AC_8:8 | Cooling | Sensible | 13456.01 | 0.97048 | 0.97048 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
16 | PSZ-AC_8:8 | Heating | Sensible | 28727.13 | 0.90640 | 0.90640 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
17 | PSZ-AC_9:9 | Cooling | Sensible | 13330.14 | 0.95970 | 0.95970 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
18 | PSZ-AC_9:9 | Heating | Sensible | 28958.08 | 0.91795 | 0.91795 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
19 | PSZ-AC_10:10 | Cooling | Sensible | 13475.59 | 0.97661 | 0.97661 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
20 | PSZ-AC_10:10 | Heating | Sensible | 31561.97 | 1.04817 | 1.04817 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:Uncontrolled | LGSTORE1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.94092 |
2 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.05266 |
3 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE2 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.04952 |
4 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.05352 |
5 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE4 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.04672 |
6 | AirTerminal:SingleDuct:Uncontrolled | LGSTORE2 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.89301 |
7 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE5 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.95701 |
8 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.94666 |
9 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE7 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.95970 |
10 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE8 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.04817 |
11 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.94092 |
12 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.94092 |
13 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.94092 |
14 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.94092 |
15 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.94092 |
16 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Main Design Air Flow Rate [m3/s] | 1.94092 |
17 | AirLoopHVAC | PSZ-AC_1:1 | User Heating Air Flow Ratio [] | 1.00000 |
18 | AirLoopHVAC | PSZ-AC_1:1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
19 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.05266 |
20 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.05266 |
21 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.05266 |
22 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.05266 |
23 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.05266 |
24 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Main Design Air Flow Rate [m3/s] | 1.05266 |
25 | AirLoopHVAC | PSZ-AC_2:2 | User Heating Air Flow Ratio [] | 1.00000 |
26 | AirLoopHVAC | PSZ-AC_2:2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
27 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.04952 |
28 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.04952 |
29 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.04952 |
30 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.04952 |
31 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.04952 |
32 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Main Design Air Flow Rate [m3/s] | 1.04952 |
33 | AirLoopHVAC | PSZ-AC_3:3 | User Heating Air Flow Ratio [] | 1.00000 |
34 | AirLoopHVAC | PSZ-AC_3:3 | Calculated Heating Air Flow Ratio [] | 1.00000 |
35 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.05352 |
36 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.05352 |
37 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.05352 |
38 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.05352 |
39 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.05352 |
40 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Main Design Air Flow Rate [m3/s] | 1.05352 |
41 | AirLoopHVAC | PSZ-AC_4:4 | User Heating Air Flow Ratio [] | 1.00000 |
42 | AirLoopHVAC | PSZ-AC_4:4 | Calculated Heating Air Flow Ratio [] | 1.00000 |
43 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.04672 |
44 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.04672 |
45 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.04672 |
46 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.04672 |
47 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.04672 |
48 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Main Design Air Flow Rate [m3/s] | 1.04672 |
49 | AirLoopHVAC | PSZ-AC_5:5 | User Heating Air Flow Ratio [] | 1.00000 |
50 | AirLoopHVAC | PSZ-AC_5:5 | Calculated Heating Air Flow Ratio [] | 1.00000 |
51 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.89301 |
52 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.89301 |
53 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.89301 |
54 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.89301 |
55 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.89301 |
56 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Main Design Air Flow Rate [m3/s] | 1.89301 |
57 | AirLoopHVAC | PSZ-AC_6:6 | User Heating Air Flow Ratio [] | 1.00000 |
58 | AirLoopHVAC | PSZ-AC_6:6 | Calculated Heating Air Flow Ratio [] | 1.00000 |
59 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.95701 |
60 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.95701 |
61 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.95701 |
62 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.95701 |
63 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.97941 |
64 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Main Design Air Flow Rate [m3/s] | 0.97941 |
65 | AirLoopHVAC | PSZ-AC_7:7 | User Heating Air Flow Ratio [] | 1.00000 |
66 | AirLoopHVAC | PSZ-AC_7:7 | Calculated Heating Air Flow Ratio [] | 0.97713 |
67 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.94666 |
68 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.94666 |
69 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.94666 |
70 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.94666 |
71 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.97048 |
72 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Main Design Air Flow Rate [m3/s] | 0.97048 |
73 | AirLoopHVAC | PSZ-AC_8:8 | User Heating Air Flow Ratio [] | 1.00000 |
74 | AirLoopHVAC | PSZ-AC_8:8 | Calculated Heating Air Flow Ratio [] | 0.97546 |
75 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.95970 |
76 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.95970 |
77 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.95970 |
78 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.95970 |
79 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.95970 |
80 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Main Design Air Flow Rate [m3/s] | 0.95970 |
81 | AirLoopHVAC | PSZ-AC_9:9 | User Heating Air Flow Ratio [] | 1.00000 |
82 | AirLoopHVAC | PSZ-AC_9:9 | Calculated Heating Air Flow Ratio [] | 1.00000 |
83 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.04817 |
84 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.04817 |
85 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.04817 |
86 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.04817 |
87 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.04817 |
88 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Main Design Air Flow Rate [m3/s] | 1.04817 |
89 | AirLoopHVAC | PSZ-AC_10:10 | User Heating Air Flow Ratio [] | 1.00000 |
90 | AirLoopHVAC | PSZ-AC_10:10 | Calculated Heating Air Flow Ratio [] | 1.00000 |
91 | AirLoopHVAC | PSZ-AC_1:1 | Design Supply Air Flow Rate [m3/s] | 1.94092 |
92 | AirLoopHVAC | PSZ-AC_2:2 | Design Supply Air Flow Rate [m3/s] | 1.05266 |
93 | AirLoopHVAC | PSZ-AC_3:3 | Design Supply Air Flow Rate [m3/s] | 1.04952 |
94 | AirLoopHVAC | PSZ-AC_4:4 | Design Supply Air Flow Rate [m3/s] | 1.05352 |
95 | AirLoopHVAC | PSZ-AC_5:5 | Design Supply Air Flow Rate [m3/s] | 1.04672 |
96 | AirLoopHVAC | PSZ-AC_6:6 | Design Supply Air Flow Rate [m3/s] | 1.89301 |
97 | AirLoopHVAC | PSZ-AC_7:7 | Design Supply Air Flow Rate [m3/s] | 0.97941 |
98 | AirLoopHVAC | PSZ-AC_8:8 | Design Supply Air Flow Rate [m3/s] | 0.97048 |
99 | AirLoopHVAC | PSZ-AC_9:9 | Design Supply Air Flow Rate [m3/s] | 0.95970 |
100 | AirLoopHVAC | PSZ-AC_10:10 | Design Supply Air Flow Rate [m3/s] | 1.04817 |
101 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.94092 |
102 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41145 |
103 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.94092 |
104 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.94092 |
105 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.94092 |
106 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.28101 |
107 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.94092 |
108 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.97046 |
109 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.29395 |
110 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 32129.11770 |
111 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 32497.37000 |
112 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 16248.68500 |
113 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 16248.68500 |
114 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.79449 |
115 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.79449 |
116 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.79449 |
117 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.79449 |
118 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 32497.37000 |
119 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 60015.82197 |
120 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
121 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
122 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.94092 |
123 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 2076.87857 |
124 | Coil:Heating:Fuel | PSZ-AC_1:1_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 60015.82197 |
125 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.05266 |
126 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20573 |
127 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.05266 |
128 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.05266 |
129 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.05266 |
130 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.05266 |
131 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.05266 |
132 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.52633 |
133 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.70177 |
134 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 17425.26072 |
135 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 17469.21000 |
136 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 8734.60500 |
137 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 8734.60500 |
138 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.79773 |
139 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.79773 |
140 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.79773 |
141 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.79773 |
142 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 17469.21000 |
143 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 31651.69858 |
144 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
145 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
146 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.05266 |
147 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1165.46406 |
148 | Coil:Heating:Fuel | PSZ-AC_2:2_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 31651.69858 |
149 | Controller:OutdoorAir | PSZ-AC_3:3_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.04952 |
150 | Controller:OutdoorAir | PSZ-AC_3:3_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20573 |
151 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.04952 |
152 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.04952 |
153 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.04952 |
154 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.04952 |
155 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.04952 |
156 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.52476 |
157 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.69968 |
158 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 17373.28257 |
159 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 17422.97000 |
160 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 8711.48500 |
161 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 8711.48500 |
162 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.79761 |
163 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.79761 |
164 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.79761 |
165 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.79761 |
166 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 17422.97000 |
167 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 31588.80837 |
168 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
169 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
170 | Fan:SystemModel | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.04952 |
171 | Fan:SystemModel | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1161.98186 |
172 | Coil:Heating:Fuel | PSZ-AC_3:3_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 31588.80837 |
173 | Controller:OutdoorAir | PSZ-AC_4:4_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.05352 |
174 | Controller:OutdoorAir | PSZ-AC_4:4_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20573 |
175 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.05352 |
176 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.05352 |
177 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.05352 |
178 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.05352 |
179 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.05352 |
180 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.52676 |
181 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.70235 |
182 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 17439.49677 |
183 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 17482.33000 |
184 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 8741.16500 |
185 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 8741.16500 |
186 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.79775 |
187 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.79775 |
188 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.79775 |
189 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.79775 |
190 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 17482.33000 |
191 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 31668.79519 |
192 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
193 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
194 | Fan:SystemModel | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.05352 |
195 | Fan:SystemModel | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1166.41094 |
196 | Coil:Heating:Fuel | PSZ-AC_4:4_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 31668.79519 |
197 | Controller:OutdoorAir | PSZ-AC_5:5_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.04672 |
198 | Controller:OutdoorAir | PSZ-AC_5:5_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20573 |
199 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.04672 |
200 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.04672 |
201 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.04672 |
202 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.04672 |
203 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.04672 |
204 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.52336 |
205 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.69781 |
206 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 17326.93263 |
207 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 17381.70000 |
208 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 8690.85000 |
209 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 8690.85000 |
210 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.79750 |
211 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.79750 |
212 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.79750 |
213 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.79750 |
214 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 17381.70000 |
215 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 31532.92923 |
216 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
217 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
218 | Fan:SystemModel | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.04672 |
219 | Fan:SystemModel | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1158.88797 |
220 | Coil:Heating:Fuel | PSZ-AC_5:5_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 31532.92923 |
221 | Controller:OutdoorAir | PSZ-AC_6:6_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.89301 |
222 | Controller:OutdoorAir | PSZ-AC_6:6_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41145 |
223 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.89301 |
224 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.89301 |
225 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.89301 |
226 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.24939 |
227 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.89301 |
228 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.94651 |
229 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.26201 |
230 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 31336.03708 |
231 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 31787.43000 |
232 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 15893.71500 |
233 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 15893.71500 |
234 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.79343 |
235 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.79343 |
236 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.79343 |
237 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.79343 |
238 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 31787.43000 |
239 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 59057.68157 |
240 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
241 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
242 | Fan:SystemModel | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.89301 |
243 | Fan:SystemModel | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 2025.61232 |
244 | Coil:Heating:Fuel | PSZ-AC_6:6_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 59057.68157 |
245 | Controller:OutdoorAir | PSZ-AC_7:7_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.97941 |
246 | Controller:OutdoorAir | PSZ-AC_7:7_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20573 |
247 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.97941 |
248 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.97941 |
249 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.97941 |
250 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.97941 |
251 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.97941 |
252 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.48971 |
253 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.65294 |
254 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 16212.71313 |
255 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 16385.04000 |
256 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 8192.52000 |
257 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 8192.52000 |
258 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.79479 |
259 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.79479 |
260 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.79479 |
261 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.79479 |
262 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 16385.04000 |
263 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 29739.21704 |
264 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
265 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
266 | Fan:SystemModel | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.97941 |
267 | Fan:SystemModel | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1084.36461 |
268 | Coil:Heating:Fuel | PSZ-AC_7:7_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 29739.21704 |
269 | Controller:OutdoorAir | PSZ-AC_8:8_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.97048 |
270 | Controller:OutdoorAir | PSZ-AC_8:8_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20573 |
271 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.97048 |
272 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.97048 |
273 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.97048 |
274 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.97048 |
275 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.97048 |
276 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.48524 |
277 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.64699 |
278 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 16064.88992 |
279 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 16252.66000 |
280 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 8126.33000 |
281 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 8126.33000 |
282 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.79441 |
283 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.79441 |
284 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.79441 |
285 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.79441 |
286 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 16252.66000 |
287 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 29532.26295 |
288 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
289 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
290 | Fan:SystemModel | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.97048 |
291 | Fan:SystemModel | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1074.47394 |
292 | Coil:Heating:Fuel | PSZ-AC_8:8_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 29532.26295 |
293 | Controller:OutdoorAir | PSZ-AC_9:9_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.95970 |
294 | Controller:OutdoorAir | PSZ-AC_9:9_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20573 |
295 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.95970 |
296 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.95970 |
297 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.95970 |
298 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.95970 |
299 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.95970 |
300 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.47985 |
301 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.63980 |
302 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 15886.44264 |
303 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 16092.91000 |
304 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 8046.45500 |
305 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 8046.45500 |
306 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.79394 |
307 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.79394 |
308 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.79394 |
309 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.79394 |
310 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 16092.91000 |
311 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 29792.90696 |
312 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
313 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
314 | Fan:SystemModel | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.95970 |
315 | Fan:SystemModel | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1062.54048 |
316 | Coil:Heating:Fuel | PSZ-AC_9:9_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 29792.90696 |
317 | Controller:OutdoorAir | PSZ-AC_10:10_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.04817 |
318 | Controller:OutdoorAir | PSZ-AC_10:10_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20573 |
319 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.04817 |
320 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.04817 |
321 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.04817 |
322 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.04817 |
323 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.04817 |
324 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.52409 |
325 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.69878 |
326 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 17350.93528 |
327 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 17551.84000 |
328 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 8775.92000 |
329 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 8775.92000 |
330 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.79445 |
331 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.79445 |
332 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.79445 |
333 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.79445 |
334 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 17551.84000 |
335 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 31561.97237 |
336 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
337 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
338 | Fan:SystemModel | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.04817 |
339 | Fan:SystemModel | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1160.48781 |
340 | Coil:Heating:Fuel | PSZ-AC_10:10_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 31561.97237 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | 30976.0 | 11.13 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | 16644.2 | 33.87 | |||
3 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | 16600.4 | 45.80 | |||
4 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | 16656.7 | 57.49 | |||
5 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | 16561.3 | 69.67 | |||
6 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | 30303.6 | 46.96 | |||
7 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | 15617.4 | 108.88 | |||
8 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | 15492.0 | 121.65 | |||
9 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | 15340.7 | 134.75 | |||
10 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | 16730.3 | 135.39 |
Zone Name | # Surfaces | |
1 | LGSTORE1 | 15 |
2 | SMSTORE1 | 11 |
3 | SMSTORE2 | 11 |
4 | SMSTORE3 | 11 |
5 | SMSTORE4 | 11 |
6 | LGSTORE2 | 15 |
7 | SMSTORE5 | 11 |
8 | SMSTORE6 | 11 |
9 | SMSTORE7 | 11 |
10 | SMSTORE8 | 11 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | LGSTORE1_WALL_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | LGSTORE1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 71.15 | 78.94 | 71.15 | 0.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | LGSTORE1_WALL_3_DOOR_1 | Door | LGSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
4 | LGSTORE1_WALL_3_DOOR_2 | Door | LGSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
5 | LGSTORE1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
6 | LGSTORE1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 58.20 | 78.94 | 58.20 | 180.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
7 | LGSTORE1_WALL_1_WINDOW_1 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
8 | LGSTORE1_WALL_1_WINDOW_2 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
9 | LGSTORE1_WALL_1_WINDOW_3 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
10 | LGSTORE1_WALL_1_WINDOW_4 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
11 | LGSTORE1_WALL_1_DOOR_1 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
12 | LGSTORE1_WALL_1_DOOR_2 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
13 | LGSTORE1_FLOOR | Floor | CTF - ConductionTransferFunction | LGSTORE1_FLOOR_FFACTOR | 0.146 | 0.141 | 348.39 | 348.39 | 348.39 | 270.00 | 180.00 | 22.86 | 15.24 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | LGSTORE1_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 348.39 | 348.39 | 348.39 | 270.00 | 0.00 | 22.86 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
15 | LGSTORE1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 696.77 | 696.77 | 696.77 | 0.00 | 90.00 | 696.77 | 1.00 | 0.00 | LGSTORE1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
16 | SMSTORE1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 29.10 | 39.47 | 29.10 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
17 | SMSTORE1_WALL_1_WINDOW_1 | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
18 | SMSTORE1_WALL_1_WINDOW_2 | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
19 | SMSTORE1_WALL_1_DOOR | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
20 | SMSTORE1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | SMSTORE1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 35.57 | 39.47 | 35.57 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | SMSTORE1_WALL_3_DOOR | Door | SMSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
23 | SMSTORE1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE2_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
24 | SMSTORE1_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE1_FLOOR_FFACTOR | 8.283E-002 | 8.119E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | SMSTORE1_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
26 | SMSTORE1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
27 | SMSTORE2_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 29.12 | 39.47 | 29.12 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | SMSTORE2_WALL_1_WINDOW_1 | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
29 | SMSTORE2_WALL_1_WINDOW_2 | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
30 | SMSTORE2_WALL_1_DOOR | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
31 | SMSTORE2_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
32 | SMSTORE2_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | SMSTORE2_WALL_3_DOOR | Door | SMSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
34 | SMSTORE2_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE3_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | SMSTORE2_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE2_FLOOR_FFACTOR | 8.283E-002 | 8.119E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
36 | SMSTORE2_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
37 | SMSTORE2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
38 | SMSTORE3_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 29.12 | 39.47 | 29.12 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
39 | SMSTORE3_WALL_1_WINDOW_1 | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
40 | SMSTORE3_WALL_1_WINDOW_2 | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
41 | SMSTORE3_WALL_1_DOOR | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
42 | SMSTORE3_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE2_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | SMSTORE3_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | SMSTORE3_WALL_3_DOOR | Door | SMSTORE3_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
45 | SMSTORE3_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE4_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | SMSTORE3_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE3_FLOOR_FFACTOR | 8.283E-002 | 8.119E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
47 | SMSTORE3_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
48 | SMSTORE3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
49 | SMSTORE4_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 29.12 | 39.47 | 29.12 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | SMSTORE4_WALL_1_WINDOW_1 | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
51 | SMSTORE4_WALL_1_WINDOW_2 | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
52 | SMSTORE4_WALL_1_DOOR | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | SMSTORE4_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE3_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | SMSTORE4_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | SMSTORE4_WALL_3_DOOR | Door | SMSTORE4_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | SMSTORE4_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE2_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | SMSTORE4_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE4_FLOOR_FFACTOR | 8.283E-002 | 8.119E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | SMSTORE4_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | SMSTORE4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | LGSTORE2_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE4_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | LGSTORE2_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 71.19 | 78.94 | 71.19 | 0.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
62 | LGSTORE2_WALL_3_DOOR_1 | Door | LGSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
63 | LGSTORE2_WALL_3_DOOR_2 | Door | LGSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
64 | LGSTORE2_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE5_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | LGSTORE2_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 58.24 | 78.94 | 58.24 | 180.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
66 | LGSTORE2_WALL_1_WINDOW_1 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | LGSTORE2_WALL_1_WINDOW_2 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | LGSTORE2_WALL_1_WINDOW_3 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | LGSTORE2_WALL_1_WINDOW_4 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | LGSTORE2_WALL_1_DOOR_1 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
71 | LGSTORE2_WALL_1_DOOR_2 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
72 | LGSTORE2_FLOOR | Floor | CTF - ConductionTransferFunction | LGSTORE2_FLOOR_FFACTOR | 8.283E-002 | 8.119E-002 | 348.39 | 348.39 | 348.39 | 270.00 | 180.00 | 22.86 | 15.24 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
73 | LGSTORE2_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 348.39 | 348.39 | 348.39 | 270.00 | 0.00 | 22.86 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
74 | LGSTORE2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 696.77 | 696.77 | 696.77 | 0.00 | 90.00 | 696.77 | 1.00 | 0.00 | LGSTORE2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
75 | SMSTORE5_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 29.12 | 39.47 | 29.12 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | SMSTORE5_WALL_1_WINDOW_1 | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
77 | SMSTORE5_WALL_1_WINDOW_2 | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | SMSTORE5_WALL_1_DOOR | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
79 | SMSTORE5_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE2_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | SMSTORE5_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | SMSTORE5_WALL_3_DOOR | Door | SMSTORE5_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
82 | SMSTORE5_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE6_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
83 | SMSTORE5_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE5_FLOOR_FFACTOR | 8.283E-002 | 8.119E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
84 | SMSTORE5_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
85 | SMSTORE5_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE5_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
86 | SMSTORE6_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 29.12 | 39.47 | 29.12 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | SMSTORE6_WALL_1_WINDOW_1 | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
88 | SMSTORE6_WALL_1_WINDOW_2 | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
89 | SMSTORE6_WALL_1_DOOR | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
90 | SMSTORE6_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE5_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
91 | SMSTORE6_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
92 | SMSTORE6_WALL_3_DOOR | Door | SMSTORE6_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
93 | SMSTORE6_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE7_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | SMSTORE6_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE6_FLOOR_FFACTOR | 8.283E-002 | 8.119E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
95 | SMSTORE6_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
96 | SMSTORE6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
97 | SMSTORE7_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 29.12 | 39.47 | 29.12 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | SMSTORE7_WALL_1_WINDOW_1 | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
99 | SMSTORE7_WALL_1_WINDOW_2 | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
100 | SMSTORE7_WALL_1_DOOR | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
101 | SMSTORE7_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE6_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
102 | SMSTORE7_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 35.59 | 39.47 | 35.59 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | SMSTORE7_WALL_3_DOOR | Door | SMSTORE7_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
104 | SMSTORE7_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE8_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | SMSTORE7_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE7_FLOOR_FFACTOR | 8.283E-002 | 8.119E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
106 | SMSTORE7_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
107 | SMSTORE7_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE7_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
108 | SMSTORE8_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 29.12 | 39.47 | 29.12 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | SMSTORE8_WALL_1_WINDOW_1 | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
110 | SMSTORE8_WALL_1_WINDOW_2 | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
111 | SMSTORE8_WALL_1_DOOR | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
112 | SMSTORE8_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE7_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
113 | SMSTORE8_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | SMSTORE8_WALL_3_DOOR | Door | SMSTORE8_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
115 | SMSTORE8_WALL_4 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | SMSTORE8_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE8_FLOOR_FFACTOR | 0.211 | 0.201 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | SMSTORE8_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | SMSTORE8_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE8_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1 |
2 | VETERANS DAY | Holiday | InputFile | 11/11 | 1 |
3 | CHRISTMAS | Holiday | InputFile | 12/25 | 1 |
4 | INDEPENDENCE DAY | Holiday | InputFile | 07/04 | 1 |
5 | MLK DAY | Holiday | InputFile | 01/16 | 1 |
6 | PRESIDENTS DAY | Holiday | InputFile | 02/20 | 1 |
7 | MEMORIAL DAY | Holiday | InputFile | 05/29 | 1 |
8 | LABOR DAY | Holiday | InputFile | 09/04 | 1 |
9 | COLUMBUS DAY | Holiday | InputFile | 10/09 | 1 |
10 | THANKSGIVING | Holiday | InputFile | 11/23 | 1 |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
NumberofWarmupDays | |
1 | 13 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | LGSTORE1 | RunPeriod: RUNPERIOD 1 | 2.6470092445E-002 | 0.1217988410 | Pass | Pass | 0.2036282469 | 0.5780990945 | Pass | Pass |
2 | SMSTORE1 | RunPeriod: RUNPERIOD 1 | 5.7464898808E-002 | 9.7155215889E-002 | Pass | Pass | 7.2477853583E-002 | 0.2937081442 | Pass | Pass |
3 | SMSTORE2 | RunPeriod: RUNPERIOD 1 | 2.5159346504E-002 | 6.5732963616E-002 | Pass | Pass | 0.1522345351 | 0.4738364618 | Pass | Pass |
4 | SMSTORE3 | RunPeriod: RUNPERIOD 1 | 2.9883352431E-002 | 0.1005805354 | Pass | Pass | 0.5113665921 | 3.5542936409 | Pass | Pass |
5 | SMSTORE4 | RunPeriod: RUNPERIOD 1 | 3.3566960022E-002 | 0.1243052954 | Pass | Pass | 0.3015477165 | 1.3758417073 | Pass | Pass |
6 | LGSTORE2 | RunPeriod: RUNPERIOD 1 | 4.2877254591E-002 | 0.1692117277 | Pass | Pass | 0.1754251143 | 0.8465188798 | Pass | Pass |
7 | SMSTORE5 | RunPeriod: RUNPERIOD 1 | 4.3413013227E-002 | 0.1412628759 | Pass | Pass | 0.1459813972 | 0.4663391299 | Pass | Pass |
8 | SMSTORE6 | RunPeriod: RUNPERIOD 1 | 4.5249867544E-002 | 0.1536038783 | Pass | Pass | 0.1444004809 | 0.4772746207 | Pass | Pass |
9 | SMSTORE7 | RunPeriod: RUNPERIOD 1 | 5.4848960885E-002 | 0.2051887805 | Pass | Pass | 0.1379035430 | 0.7413490488 | Pass | Pass |
10 | SMSTORE8 | RunPeriod: RUNPERIOD 1 | 7.5063587107E-002 | 0.2980373456 | Pass | Pass | 8.2139347276E-002 | 0.2898651872 | Pass | Pass |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2020-06-03 19:18:53
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | -27.60 | 0.00 | -27.60 | Wetbulb [C] | 2.70 | 230.00 |
GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 33.40 | 16.00 | 16.30 | Wetbulb [C] | 4.90 | 240.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2020-06-03 19:18:53
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_2 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE1_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 78.94 | 71.15 | 0.00 | 90.00 | N |
LGSTORE1_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 78.94 | 58.20 | 180.00 | 90.00 | S |
LGSTORE1_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 348.39 | 348.39 | 270.00 | 0.00 | |
SMSTORE1_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 29.10 | 180.00 | 90.00 | S |
SMSTORE1_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 35.57 | 0.00 | 90.00 | N |
SMSTORE1_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE2_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 29.12 | 180.00 | 90.00 | S |
SMSTORE2_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE2_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE3_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 29.12 | 180.00 | 90.00 | S |
SMSTORE3_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE3_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE4_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 29.12 | 180.00 | 90.00 | S |
SMSTORE4_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE4_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
LGSTORE2_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 78.94 | 71.19 | 0.00 | 90.00 | N |
LGSTORE2_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 78.94 | 58.24 | 180.00 | 90.00 | S |
LGSTORE2_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 348.39 | 348.39 | 270.00 | 0.00 | |
SMSTORE5_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 29.12 | 180.00 | 90.00 | S |
SMSTORE5_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE5_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE6_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 29.12 | 180.00 | 90.00 | S |
SMSTORE6_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE6_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE7_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 29.12 | 180.00 | 90.00 | S |
SMSTORE7_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE7_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE8_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 29.12 | 180.00 | 90.00 | S |
SMSTORE8_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE8_WALL_4 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE8_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
LGSTORE1_FLOOR | LGSTORE1_FLOOR_FFACTOR | 1.00 | 0.146 | 348.39 | 348.39 | 270.00 | 180.00 | ||
SMSTORE1_FLOOR | SMSTORE1_FLOOR_FFACTOR | 1.00 | 0.083 | 174.19 | 174.19 | 270.00 | 180.00 | ||
SMSTORE2_FLOOR | SMSTORE2_FLOOR_FFACTOR | 1.00 | 0.083 | 174.19 | 174.19 | 270.00 | 180.00 | ||
SMSTORE3_FLOOR | SMSTORE3_FLOOR_FFACTOR | 1.00 | 0.083 | 174.19 | 174.19 | 270.00 | 180.00 | ||
SMSTORE4_FLOOR | SMSTORE4_FLOOR_FFACTOR | 1.00 | 0.083 | 174.19 | 174.19 | 270.00 | 180.00 | ||
LGSTORE2_FLOOR | LGSTORE2_FLOOR_FFACTOR | 1.00 | 0.083 | 348.39 | 348.39 | 270.00 | 180.00 | ||
SMSTORE5_FLOOR | SMSTORE5_FLOOR_FFACTOR | 1.00 | 0.083 | 174.19 | 174.19 | 270.00 | 180.00 | ||
SMSTORE6_FLOOR | SMSTORE6_FLOOR_FFACTOR | 1.00 | 0.083 | 174.19 | 174.19 | 270.00 | 180.00 | ||
SMSTORE7_FLOOR | SMSTORE7_FLOOR_FFACTOR | 1.00 | 0.083 | 174.19 | 174.19 | 270.00 | 180.00 | ||
SMSTORE8_FLOOR | SMSTORE8_FLOOR_FFACTOR | 1.00 | 0.211 | 174.19 | 174.19 | 270.00 | 180.00 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.36_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.045 | 0.394 | 0.401 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE1_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.36_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.045 | 0.394 | 0.401 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE1_WALL_1_WINDOW_3 | NONRESWINDOW_U_0.36_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.045 | 0.394 | 0.401 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE1_WALL_1_WINDOW_4 | NONRESWINDOW_U_0.36_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.045 | 0.394 | 0.401 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE1_WALL_1_DOOR_1 | NONRESWINDOW_U_0.36_SHGC_0.4 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.045 | 0.394 | 0.401 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE1_WALL_1_DOOR_2 | NONRESWINDOW_U_0.36_SHGC_0.4 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.045 | 0.394 | 0.401 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE1_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.36_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.045 | 0.394 | 0.401 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE1_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.36_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.045 | 0.394 | 0.401 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE1_WALL_1_DOOR | NONRESWINDOW_U_0.36_SHGC_0.4 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.045 | 0.394 | 0.401 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE2_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.36_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.045 | 0.394 | 0.401 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE2_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.36_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.045 | 0.394 | 0.401 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE2_WALL_1_DOOR | NONRESWINDOW_U_0.36_SHGC_0.4 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.045 | 0.394 | 0.401 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE3_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.36_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.045 | 0.394 | 0.401 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE3_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.36_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.045 | 0.394 | 0.401 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE3_WALL_1_DOOR | NONRESWINDOW_U_0.36_SHGC_0.4 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.045 | 0.394 | 0.401 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE4_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.36_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.045 | 0.394 | 0.401 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE4_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.36_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.045 | 0.394 | 0.401 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE4_WALL_1_DOOR | NONRESWINDOW_U_0.36_SHGC_0.4 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.045 | 0.394 | 0.401 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE2_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.36_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.045 | 0.394 | 0.401 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE2_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.36_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.045 | 0.394 | 0.401 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE2_WALL_1_WINDOW_3 | NONRESWINDOW_U_0.36_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.045 | 0.394 | 0.401 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE2_WALL_1_WINDOW_4 | NONRESWINDOW_U_0.36_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.045 | 0.394 | 0.401 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE2_WALL_1_DOOR_1 | NONRESWINDOW_U_0.36_SHGC_0.4 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.045 | 0.394 | 0.401 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE2_WALL_1_DOOR_2 | NONRESWINDOW_U_0.36_SHGC_0.4 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.045 | 0.394 | 0.401 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE5_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.36_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.045 | 0.394 | 0.401 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE5_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.36_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.045 | 0.394 | 0.401 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE5_WALL_1_DOOR | NONRESWINDOW_U_0.36_SHGC_0.4 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.045 | 0.394 | 0.401 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE6_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.36_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.045 | 0.394 | 0.401 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE6_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.36_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.045 | 0.394 | 0.401 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE6_WALL_1_DOOR | NONRESWINDOW_U_0.36_SHGC_0.4 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.045 | 0.394 | 0.401 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE7_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.36_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.045 | 0.394 | 0.401 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE7_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.36_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.045 | 0.394 | 0.401 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE7_WALL_1_DOOR | NONRESWINDOW_U_0.36_SHGC_0.4 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.045 | 0.394 | 0.401 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE8_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.36_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.045 | 0.394 | 0.401 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE8_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.36_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.045 | 0.394 | 0.401 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE8_WALL_1_DOOR | NONRESWINDOW_U_0.36_SHGC_0.4 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.045 | 0.394 | 0.401 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | ||
Total or Average | 124.29 | 2.045 | 0.394 | 0.401 | ||||||||||||
North Total or Average | 0.00 | - | - | - | ||||||||||||
Non-North Total or Average | 124.29 | 2.045 | 0.394 | 0.401 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
LGSTORE1_WALL_3_DOOR_1 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.90 | LGSTORE1_WALL_3 |
LGSTORE1_WALL_3_DOOR_2 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.90 | LGSTORE1_WALL_3 |
SMSTORE1_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.90 | SMSTORE1_WALL_3 |
SMSTORE2_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE2_WALL_3 |
SMSTORE3_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE3_WALL_3 |
SMSTORE4_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE4_WALL_3 |
LGSTORE2_WALL_3_DOOR_1 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | LGSTORE2_WALL_3 |
LGSTORE2_WALL_3_DOOR_2 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | LGSTORE2_WALL_3 |
SMSTORE5_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE5_WALL_3 |
SMSTORE6_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE6_WALL_3 |
SMSTORE7_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE7_WALL_3 |
SMSTORE8_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE8_WALL_3 |
Report: Shading Summary
For: Entire Facility
Timestamp: 2020-06-03 19:18:53
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
LGSTORE1_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_DOOR_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_DOOR_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_DOOR_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_DOOR_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2020-06-03 19:18:53
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
LGSTORE1_LIGHTS | LGSTORE1 | 13.1675 | 348.39 | 4587.39 | LightsWired | TYPE1_LIGHT_SCH | 98.40 | 168.00 | 98.38 | 0.0000 | Y | 84.71 |
LGSTORE1_LIGHTS_ALLOWANCE | LGSTORE1 | 5.1990 | 348.39 | 1811.25 | LightsWired | TYPE1_LIGHT_SCH | 98.40 | 168.00 | 98.38 | 0.0000 | Y | 33.45 |
SMSTORE1_LIGHTS | SMSTORE1 | 13.1675 | 174.19 | 2293.69 | LightsWired | TYPE1_LIGHT_SCH | 98.40 | 168.00 | 98.38 | 0.0000 | Y | 42.36 |
SMSTORE1_LIGHTS_ALLOWANCE | SMSTORE1 | 6.6413 | 174.19 | 1156.88 | LightsWired | TYPE1_LIGHT_SCH | 98.40 | 168.00 | 98.38 | 0.0000 | Y | 21.36 |
SMSTORE2_LIGHTS | SMSTORE2 | 13.1675 | 174.19 | 2293.69 | LightsWired | TYPE2_LIGHT_SCH | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 33.57 |
SMSTORE2_LIGHTS_ALLOWANCE | SMSTORE2 | 4.4886 | 174.19 | 781.88 | LightsWired | TYPE2_LIGHT_SCH | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 11.44 |
SMSTORE3_LIGHTS | SMSTORE3 | 13.1675 | 174.19 | 2293.69 | LightsWired | TYPE2_LIGHT_SCH | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 33.57 |
SMSTORE3_LIGHTS_ALLOWANCE | SMSTORE3 | 4.4886 | 174.19 | 781.88 | LightsWired | TYPE2_LIGHT_SCH | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 11.44 |
SMSTORE4_LIGHTS | SMSTORE4 | 13.1675 | 174.19 | 2293.69 | LightsWired | TYPE2_LIGHT_SCH | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 33.57 |
SMSTORE4_LIGHTS_ALLOWANCE | SMSTORE4 | 4.4886 | 174.19 | 781.88 | LightsWired | TYPE2_LIGHT_SCH | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 11.44 |
LGSTORE2_LIGHTS | LGSTORE2 | 13.1675 | 348.39 | 4587.39 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 168.00 | 71.66 | 0.0000 | Y | 61.71 |
LGSTORE2_LIGHTS_ALLOWANCE | LGSTORE2 | 0.0000 | 348.39 | 0.00 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE5_LIGHTS | SMSTORE5 | 13.1675 | 174.19 | 2293.69 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 168.00 | 71.66 | 0.0000 | Y | 30.85 |
SMSTORE5_LIGHTS_ALLOWANCE | SMSTORE5 | 0.0000 | 174.19 | 0.00 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE6_LIGHTS | SMSTORE6 | 13.1675 | 174.19 | 2293.69 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 168.00 | 71.66 | 0.0000 | Y | 30.85 |
SMSTORE6_LIGHTS_ALLOWANCE | SMSTORE6 | 0.0000 | 174.19 | 0.00 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE7_LIGHTS | SMSTORE7 | 13.1675 | 174.19 | 2293.69 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 168.00 | 71.66 | 0.0000 | Y | 30.85 |
SMSTORE7_LIGHTS_ALLOWANCE | SMSTORE7 | 0.0000 | 174.19 | 0.00 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE8_LIGHTS | SMSTORE8 | 13.1675 | 174.19 | 2293.69 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 168.00 | 71.66 | 0.0000 | Y | 30.85 |
SMSTORE8_LIGHTS_ALLOWANCE | SMSTORE8 | 0.0000 | 174.19 | 0.00 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
Interior Lighting Total | 7.8548 | 4180.64 | 32838.07 | 502.03 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 314.61 | AstronomicalClock | - | 42.11 | 42.11 | 2.49 | |
EXTERIOR_LIGHTS_B | 6630.02 | AstronomicalClock | - | 83.57 | 71.13 | 88.52 | |
Exterior Lighting Total | 6944.63 | 91.01 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2020-06-03 19:18:53
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 32497.37 | 25818.84 | 6678.53 | 0.79 | 3.80 | |||
PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 17469.21 | 13935.71 | 3533.50 | 0.80 | 4.12 | |||
PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 17422.97 | 13896.74 | 3526.23 | 0.80 | 4.12 | |||
PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 17482.33 | 13946.53 | 3535.80 | 0.80 | 4.12 | |||
PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 17381.70 | 13861.91 | 3519.79 | 0.80 | 4.12 | |||
PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 31787.43 | 25221.10 | 6566.33 | 0.79 | 3.80 | |||
PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 16385.04 | 13022.67 | 3362.37 | 0.79 | 4.12 | |||
PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 16252.66 | 12911.28 | 3341.38 | 0.79 | 4.12 | |||
PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 16092.91 | 12776.80 | 3316.11 | 0.79 | 4.12 | |||
PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 17551.84 | 13944.06 | 3607.78 | 0.79 | 4.12 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | 30976.0 | 11.13 | ||||
PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | 16644.2 | 33.87 | ||||
PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | 16600.4 | 45.80 | ||||
PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | 16656.7 | 57.49 | ||||
PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | 16561.3 | 69.67 | ||||
PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | 30303.6 | 46.96 | ||||
PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | 15617.4 | 108.88 | ||||
PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | 15492.0 | 121.65 | ||||
PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | 15340.7 | 134.75 | ||||
PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | 16730.3 | 135.39 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
PSZ-AC_1:1_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 60015.82 | 0.80 | |
PSZ-AC_2:2_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 31651.70 | 0.80 | |
PSZ-AC_3:3_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 31588.81 | 0.80 | |
PSZ-AC_4:4_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 31668.80 | 0.80 | |
PSZ-AC_5:5_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 31532.93 | 0.80 | |
PSZ-AC_6:6_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 59057.68 | 0.80 | |
PSZ-AC_7:7_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 29739.22 | 0.80 | |
PSZ-AC_8:8_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 29532.26 | 0.80 | |
PSZ-AC_9:9_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 29792.91 | 0.80 | |
PSZ-AC_10:10_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 31561.97 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 1.94 | 2076.88 | 1070.05 | 1.00 | 1.32 | General | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 |
PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.05 | 1165.46 | 1107.16 | 1.00 | 1.39 | General | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 |
PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.05 | 1161.98 | 1107.16 | 1.00 | 1.39 | General | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 |
PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.05 | 1166.41 | 1107.16 | 1.00 | 1.39 | General | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 |
PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.05 | 1158.89 | 1107.16 | 1.00 | 1.39 | General | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 |
PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 1.89 | 2025.61 | 1070.05 | 1.00 | 1.32 | General | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 |
PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 0.98 | 1084.36 | 1107.16 | 1.00 | 1.41 | General | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 |
PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 0.97 | 1074.47 | 1107.16 | 1.00 | 1.41 | General | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 |
PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 0.96 | 1062.54 | 1107.16 | 1.00 | 1.41 | General | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 |
PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.05 | 1160.49 | 1107.16 | 1.00 | 1.39 | General | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
GAS TANK1 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK2 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK3 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK4 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK5 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK6 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK7 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:18:53
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
LGSTORE1 | 19226.47 | 23071.76 | 66.22 | 1.617 | 1.941 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 23.89 | 23.89 | 0.00721 | 33.40 | 0.00627 | 0.411 | 0.00 |
SMSTORE1 | 10427.56 | 12513.07 | 71.83 | 0.877 | 1.053 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 23.89 | 23.89 | 0.00718 | 33.40 | 0.00627 | 0.206 | 0.00 |
SMSTORE2 | 10396.40 | 12475.68 | 71.62 | 0.875 | 1.050 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 23.89 | 23.89 | 0.00718 | 33.27 | 0.00627 | 0.206 | 0.00 |
SMSTORE3 | 10436.03 | 12523.23 | 71.89 | 0.878 | 1.054 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 23.89 | 23.89 | 0.00718 | 33.27 | 0.00627 | 0.206 | 0.00 |
SMSTORE4 | 10368.72 | 12442.46 | 71.43 | 0.872 | 1.047 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 23.89 | 23.89 | 0.00718 | 33.27 | 0.00627 | 0.206 | 0.00 |
LGSTORE2 | 18751.83 | 22502.20 | 64.59 | 1.578 | 1.893 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 23.89 | 23.89 | 0.00721 | 33.27 | 0.00627 | 0.411 | 0.00 |
SMSTORE5 | 9773.25 | 11727.90 | 67.33 | 0.798 | 0.957 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 23.89 | 23.89 | 0.00757 | 27.32 | 0.00627 | 0.206 | 0.00 |
SMSTORE6 | 9670.45 | 11604.53 | 66.62 | 0.789 | 0.947 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 23.89 | 23.89 | 0.00759 | 27.32 | 0.00627 | 0.206 | 0.00 |
SMSTORE7 | 9506.68 | 11408.02 | 65.49 | 0.800 | 0.960 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 23.89 | 23.89 | 0.00720 | 33.27 | 0.00627 | 0.206 | 0.00 |
SMSTORE8 | 9674.07 | 11608.88 | 66.64 | 0.814 | 0.977 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 23.89 | 23.89 | 0.00719 | 32.87 | 0.00627 | 0.206 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
LGSTORE1 | 29465.42 | 35358.51 | 101.49 | 1.452 | 1.743 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00675 | -27.60 | 0.00034 | 0.411 | 0.00 |
SMSTORE1 | 14628.74 | 17554.48 | 100.78 | 0.721 | 0.865 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00664 | -27.60 | 0.00034 | 0.206 | 0.00 |
SMSTORE2 | 14795.22 | 17754.27 | 101.92 | 0.729 | 0.875 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00665 | -27.60 | 0.00034 | 0.206 | 0.00 |
SMSTORE3 | 14867.32 | 17840.78 | 102.42 | 0.733 | 0.879 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00666 | -27.60 | 0.00034 | 0.206 | 0.00 |
SMSTORE4 | 15007.74 | 18009.28 | 103.39 | 0.740 | 0.888 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00666 | -27.60 | 0.00034 | 0.206 | 0.00 |
LGSTORE2 | 28539.28 | 34247.13 | 98.30 | 1.407 | 1.688 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00674 | -27.60 | 0.00034 | 0.411 | 0.00 |
SMSTORE5 | 15342.47 | 18410.97 | 105.69 | 0.756 | 0.907 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00669 | -27.60 | 0.00034 | 0.206 | 0.00 |
SMSTORE6 | 15325.98 | 18391.17 | 105.58 | 0.755 | 0.906 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00668 | -27.60 | 0.00034 | 0.206 | 0.00 |
SMSTORE7 | 15521.28 | 18625.54 | 106.92 | 0.765 | 0.918 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00670 | -27.60 | 0.00034 | 0.206 | 0.00 |
SMSTORE8 | 17723.30 | 21267.96 | 122.09 | 0.873 | 1.048 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00680 | -27.60 | 0.00034 | 0.206 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC_1:1 | 1.94 | 1.94 | 1.74 | 1.74 | 1.9409 | 1.9409 | 1.9409 | 1.0000 | 1.0000 |
PSZ-AC_2:2 | 1.05 | 1.05 | 0.87 | 0.87 | 1.0527 | 1.0527 | 1.0527 | 1.0000 | 1.0000 |
PSZ-AC_3:3 | 1.05 | 1.05 | 0.88 | 0.88 | 1.0495 | 1.0495 | 1.0495 | 1.0000 | 1.0000 |
PSZ-AC_4:4 | 1.05 | 1.05 | 0.88 | 0.88 | 1.0535 | 1.0535 | 1.0535 | 1.0000 | 1.0000 |
PSZ-AC_5:5 | 1.05 | 1.05 | 0.89 | 0.89 | 1.0467 | 1.0467 | 1.0467 | 1.0000 | 1.0000 |
PSZ-AC_6:6 | 1.89 | 1.89 | 1.69 | 1.69 | 1.8930 | 1.8930 | 1.8930 | 1.0000 | 1.0000 |
PSZ-AC_7:7 | 0.98 | 0.98 | 0.91 | 0.91 | 0.9794 | 0.9570 | 0.9794 | 0.9771 | 1.0000 |
PSZ-AC_8:8 | 0.97 | 0.97 | 0.91 | 0.91 | 0.9705 | 0.9467 | 0.9705 | 0.9755 | 1.0000 |
PSZ-AC_9:9 | 0.96 | 0.96 | 0.92 | 0.92 | 0.9597 | 0.9597 | 0.9597 | 1.0000 | 1.0000 |
PSZ-AC_10:10 | 0.98 | 0.98 | 1.05 | 1.05 | 1.0482 | 1.0482 | 1.0482 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_1:1 | 16248.685 | 0.000 | 1.940920 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 16248.68 | 16248.68 | 1.940920 | 25.91 | 14.40 | 0.00700667 | 12.80 | 10.89 | 0.00850000 | 33.40 | 0.00626594 | 16.30 | 21.1989 | 23.89 | 0.00720594 | 34.2219 | 19226.47 | 0.00 | -999.00 | -999.00 |
PSZ-AC_1:1_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_1:1 | 60015.822 | 60015.822 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 60015.82 | 60015.82 | 1.940922 | 9.61 | 6.08 | 0.00523894 | 40.00 | 19.60 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 21.1989 | 21.10 | 0.00675255 | 38.0114 | 29465.42 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_2:2 | 8734.605 | 0.000 | 1.052660 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 8734.60 | 8734.60 | 1.052660 | 25.75 | 14.34 | 0.00700301 | 12.80 | 10.89 | 0.00850000 | 33.40 | 0.00626594 | 16.30 | 19.5435 | 23.89 | 0.00718205 | 34.1096 | 10427.56 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_2:2 | 31651.699 | 31651.699 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 31651.70 | 31651.70 | 1.052662 | 9.52 | 5.93 | 0.00514216 | 40.00 | 19.60 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 19.5435 | 21.10 | 0.00663972 | 37.3838 | 14628.74 | 0.00 | -999.00 | -999.00 |
PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_3:3 | 8711.485 | 0.000 | 1.049520 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 8711.49 | 8711.49 | 1.049520 | 25.75 | 14.34 | 0.00700285 | 12.80 | 10.89 | 0.00850000 | 33.40 | 0.00626594 | 16.30 | 19.6020 | 23.89 | 0.00718267 | 34.1125 | 10394.57 | 0.00 | -999.00 | -999.00 |
PSZ-AC_3:3_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_3:3 | 31588.808 | 31588.808 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 31588.81 | 31588.81 | 1.049517 | 9.65 | 6.02 | 0.00516747 | 40.00 | 19.60 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 19.6020 | 21.10 | 0.00665078 | 37.4455 | 14795.22 | 0.00 | -999.00 | -999.00 |
PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_4:4 | 8741.165 | 0.000 | 1.053520 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 8741.17 | 8741.17 | 1.053520 | 25.75 | 14.34 | 0.00700304 | 12.80 | 10.89 | 0.00850000 | 33.40 | 0.00626594 | 16.30 | 19.5276 | 23.89 | 0.00718206 | 34.1097 | 10433.50 | 0.00 | -999.00 | -999.00 |
PSZ-AC_4:4_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_4:4 | 31668.795 | 31668.795 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 31668.80 | 31668.80 | 1.053517 | 9.71 | 6.06 | 0.00517827 | 40.00 | 19.60 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 19.5276 | 21.10 | 0.00665549 | 37.4717 | 14867.32 | 0.00 | -999.00 | -999.00 |
PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_5:5 | 8690.850 | 0.000 | 1.046720 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 8690.85 | 8690.85 | 1.046720 | 25.76 | 14.34 | 0.00700271 | 12.80 | 10.89 | 0.00850000 | 33.40 | 0.00626594 | 16.30 | 19.6544 | 23.89 | 0.00718310 | 34.1145 | 10366.28 | 0.00 | -999.00 | -999.00 |
PSZ-AC_5:5_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_5:5 | 31532.929 | 31532.929 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 31532.93 | 31532.93 | 1.046723 | 9.82 | 6.13 | 0.00519911 | 40.00 | 19.60 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 19.6544 | 21.10 | 0.00666463 | 37.5226 | 15007.74 | 0.00 | -999.00 | -999.00 |
PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_6:6 | 15893.715 | 0.000 | 1.893010 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 15893.72 | 15893.72 | 1.893010 | 25.96 | 14.42 | 0.00700735 | 12.80 | 10.89 | 0.00850000 | 33.40 | 0.00626594 | 16.30 | 21.7354 | 23.89 | 0.00721352 | 34.2575 | 18745.27 | 0.00 | -999.00 | -999.00 |
PSZ-AC_6:6_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_6:6 | 59057.682 | 59057.682 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 59057.68 | 59057.68 | 1.893012 | 9.23 | 5.83 | 0.00517880 | 40.00 | 19.60 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 21.7354 | 21.10 | 0.00673797 | 37.9299 | 28539.28 | 0.00 | -999.00 | -999.00 |
PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_7:7 | 8192.520 | 0.000 | 0.979410 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 8192.52 | 8192.52 | 0.979410 | 25.89 | 14.38 | 0.00699893 | 12.80 | 10.89 | 0.00850000 | 33.40 | 0.00626594 | 16.30 | 21.0052 | 23.89 | 0.00756967 | 35.9331 | 9698.65 | 0.00 | -999.00 | -999.00 |
PSZ-AC_7:7_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_7:7 | 29739.217 | 29739.217 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 29739.22 | 29739.22 | 0.979412 | 10.06 | 6.30 | 0.00524749 | 40.00 | 19.60 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 21.0051 | 21.10 | 0.00668584 | 37.6408 | 15342.47 | 0.00 | -999.00 | -999.00 |
PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_8:8 | 8126.330 | 0.000 | 0.970480 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 8126.33 | 8126.33 | 0.970480 | 25.91 | 14.39 | 0.00699836 | 12.80 | 10.89 | 0.00850000 | 33.40 | 0.00626594 | 16.30 | 21.1984 | 23.89 | 0.00758901 | 36.0240 | 9610.54 | 0.00 | -999.00 | -999.00 |
PSZ-AC_8:8_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_8:8 | 29532.263 | 29532.263 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 29532.26 | 29532.26 | 0.970479 | 10.05 | 6.29 | 0.00524515 | 40.00 | 19.60 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 21.1985 | 21.10 | 0.00668481 | 37.6350 | 15325.98 | 0.00 | -999.00 | -999.00 |
PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_9:9 | 8046.455 | 0.000 | 0.959700 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 8046.45 | 8046.45 | 0.959700 | 25.93 | 14.40 | 0.00699765 | 12.80 | 10.89 | 0.00850000 | 33.40 | 0.00626594 | 16.30 | 21.4366 | 23.89 | 0.00719755 | 34.1824 | 9504.29 | 0.00 | -999.00 | -999.00 |
PSZ-AC_9:9_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_9:9 | 29792.907 | 29792.907 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 29792.91 | 29792.91 | 0.959700 | 10.19 | 6.39 | 0.00527263 | 40.00 | 19.60 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 21.4366 | 21.10 | 0.00669689 | 37.7023 | 15521.28 | 0.00 | -999.00 | -999.00 |
PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_10:10 | 8775.920 | 0.000 | 1.048170 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 8775.92 | 8775.92 | 1.048170 | 25.90 | 14.39 | 0.00699453 | 12.80 | 10.89 | 0.00850000 | 33.40 | 0.00626594 | 16.30 | 19.6272 | 23.89 | 0.00719115 | 34.1523 | 9627.07 | 0.00 | -999.00 | -999.00 |
PSZ-AC_10:10_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_10:10 | 31561.972 | 31561.972 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 31561.97 | 31561.97 | 1.048168 | 11.55 | 7.29 | 0.00552966 | 40.00 | 19.60 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 19.6273 | 21.10 | 0.00679652 | 38.2578 | 17723.30 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2020-06-03 19:18:53
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | LGSTORE1 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 16248.685 | 0.000 | 1.940920 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.8650 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 16248.68 | 16248.68 | 1.0000 | 2.04406026 | 1.940920 | 25.91 | 14.40 | 0.00700667 | 43891.5 | 12.80 | 10.89 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 16248.68 | 33.40 | 0.00626594 | 16.30 | 0.41145340 | 21.1989 | 23.89 | 0.00720594 | 23.89 | 0.00720594 | 34.2219 | 19226.47 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_1:1_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | LGSTORE1 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 60015.822 | 60015.822 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.940922 | 2.04406264 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 60015.82 | 60015.82 | 1.0000 | 2.04406264 | 1.940922 | 9.61 | 6.08 | 0.00523894 | 22848.4 | 40.00 | 19.60 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 60015.82 | -27.60 | 0.00034190 | -27.60 | 0.41145340 | 21.1989 | 21.11 | 0.00675255 | 21.10 | 0.00675255 | 38.0114 | 29465.42 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | SMSTORE1 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 8734.605 | 0.000 | 1.052660 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.8582 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 8734.60 | 8734.60 | 1.0000 | 1.10859823 | 1.052660 | 25.75 | 14.34 | 0.00700301 | 43721.9 | 12.80 | 10.89 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8734.60 | 33.40 | 0.00626594 | 16.30 | 0.20572670 | 19.5435 | 23.89 | 0.00718205 | 23.89 | 0.00718205 | 34.1096 | 10427.56 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | SMSTORE1 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 31651.699 | 31651.699 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.052662 | 1.10860045 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 31651.70 | 31651.70 | 1.0000 | 1.10860045 | 1.052662 | 9.52 | 5.93 | 0.00514216 | 22521.4 | 40.00 | 19.60 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 31651.70 | -27.60 | 0.00034190 | -27.60 | 0.20572670 | 19.5435 | 21.11 | 0.00663972 | 21.10 | 0.00663972 | 37.3838 | 14628.74 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_3:3 | SMSTORE2 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 8711.485 | 0.000 | 1.049520 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.8579 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 8711.49 | 8711.49 | 1.0000 | 1.10529137 | 1.049520 | 25.75 | 14.34 | 0.00700285 | 43727.5 | 12.80 | 10.89 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8711.49 | 33.40 | 0.00626594 | 16.30 | 0.20572670 | 19.6020 | 23.89 | 0.00718256 | 23.89 | 0.00718267 | 34.1125 | 10394.57 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_3:3_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_3:3 | SMSTORE2 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 31588.808 | 31588.808 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.049517 | 1.10528815 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 31588.81 | 31588.81 | 1.0000 | 1.10528815 | 1.049517 | 9.65 | 6.02 | 0.00516747 | 22717.4 | 40.00 | 19.60 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 31588.81 | -27.60 | 0.00034190 | -27.60 | 0.20572670 | 19.6020 | 21.11 | 0.00665078 | 21.10 | 0.00665078 | 37.4455 | 14795.22 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_4:4 | SMSTORE3 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 8741.165 | 0.000 | 1.053520 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.8583 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 8741.17 | 8741.17 | 1.0000 | 1.10950393 | 1.053520 | 25.75 | 14.34 | 0.00700304 | 43720.9 | 12.80 | 10.89 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8741.17 | 33.40 | 0.00626594 | 16.30 | 0.20572670 | 19.5276 | 23.89 | 0.00718196 | 23.89 | 0.00718206 | 34.1097 | 10433.50 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_4:4_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_4:4 | SMSTORE3 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 31668.795 | 31668.795 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.053517 | 1.10950114 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 31668.80 | 31668.80 | 1.0000 | 1.10950114 | 1.053517 | 9.71 | 6.06 | 0.00517827 | 22800.9 | 40.00 | 19.60 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 31668.80 | -27.60 | 0.00034190 | -27.60 | 0.20572670 | 19.5276 | 21.11 | 0.00665549 | 21.10 | 0.00665549 | 37.4717 | 14867.32 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_5:5 | SMSTORE4 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 8690.850 | 0.000 | 1.046720 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.8577 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 8690.85 | 8690.85 | 1.0000 | 1.10234258 | 1.046720 | 25.76 | 14.34 | 0.00700271 | 43732.4 | 12.80 | 10.89 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8690.85 | 33.40 | 0.00626594 | 16.30 | 0.20572670 | 19.6544 | 23.89 | 0.00718299 | 23.89 | 0.00718310 | 34.1145 | 10366.28 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_5:5_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_5:5 | SMSTORE4 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 31532.929 | 31532.929 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.046723 | 1.10234522 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 31532.93 | 31532.93 | 1.0000 | 1.10234522 | 1.046723 | 9.82 | 6.13 | 0.00519911 | 22961.6 | 40.00 | 19.60 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 31532.93 | -27.60 | 0.00034190 | -27.60 | 0.20572670 | 19.6544 | 21.11 | 0.00666463 | 21.10 | 0.00666463 | 37.5226 | 15007.74 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_6:6 | LGSTORE2 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 15893.715 | 0.000 | 1.893010 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.8663 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 15893.72 | 15893.72 | 1.0000 | 1.99360432 | 1.893010 | 25.96 | 14.42 | 0.00700735 | 43945.9 | 12.80 | 10.89 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 15893.72 | 33.40 | 0.00626594 | 16.30 | 0.41145340 | 21.7354 | 23.89 | 0.00721335 | 23.89 | 0.00721352 | 34.2575 | 18745.27 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_6:6_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_6:6 | LGSTORE2 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 59057.682 | 59057.682 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.893012 | 1.99360642 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 59057.68 | 59057.68 | 1.0000 | 1.99360642 | 1.893012 | 9.23 | 5.83 | 0.00517880 | 22318.5 | 40.00 | 19.60 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 59057.68 | -27.60 | 0.00034190 | -27.60 | 0.41145340 | 21.7354 | 21.11 | 0.00673797 | 21.10 | 0.00673797 | 37.9299 | 28539.28 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_7:7 | SMSTORE5 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 8192.520 | 0.000 | 0.979410 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.8507 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 8192.52 | 8192.52 | 1.0000 | 1.03145573 | 0.979410 | 25.89 | 14.38 | 0.00699893 | 43853.7 | 12.80 | 10.89 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8192.52 | 33.40 | 0.00626594 | 16.30 | 0.20572670 | 21.0052 | 23.89 | 0.00719392 | 23.89 | 0.00756967 | 35.9331 | 9698.65 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_7:7_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_7:7 | SMSTORE5 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 29739.217 | 29739.217 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.979412 | 1.03145789 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 29739.22 | 29739.22 | 1.0000 | 1.03145789 | 0.979412 | 10.06 | 6.30 | 0.00524749 | 23333.4 | 40.00 | 19.60 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 29739.22 | -27.60 | 0.00034190 | -27.60 | 0.20572670 | 21.0051 | 21.11 | 0.00668584 | 21.10 | 0.00668584 | 37.6408 | 15342.47 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_8:8 | SMSTORE6 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 8126.330 | 0.000 | 0.970480 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.8496 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 8126.33 | 8126.33 | 1.0000 | 1.02205119 | 0.970480 | 25.91 | 14.39 | 0.00699836 | 43870.9 | 12.80 | 10.89 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8126.33 | 33.40 | 0.00626594 | 16.30 | 0.20572670 | 21.1984 | 23.89 | 0.00719547 | 23.89 | 0.00758901 | 36.0240 | 9610.54 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_8:8_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_8:8 | SMSTORE6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 29532.263 | 29532.263 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.970479 | 1.02204979 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 29532.26 | 29532.26 | 1.0000 | 1.02204979 | 0.970479 | 10.05 | 6.29 | 0.00524515 | 23315.4 | 40.00 | 19.60 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 29532.26 | -27.60 | 0.00034190 | -27.60 | 0.20572670 | 21.1985 | 21.11 | 0.00668481 | 21.10 | 0.00668481 | 37.6350 | 15325.98 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_9:9 | SMSTORE7 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 8046.455 | 0.000 | 0.959700 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.8483 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 8046.45 | 8046.45 | 1.0000 | 1.01069834 | 0.959700 | 25.93 | 14.40 | 0.00699765 | 43892.1 | 12.80 | 10.89 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8046.45 | 33.40 | 0.00626594 | 16.30 | 0.20572670 | 21.4366 | 23.89 | 0.00719736 | 23.89 | 0.00719755 | 34.1824 | 9504.29 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_9:9_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_9:9 | SMSTORE7 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 29792.907 | 29792.907 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.959700 | 1.01069857 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 29792.91 | 29792.91 | 1.0000 | 1.01069857 | 0.959700 | 10.19 | 6.39 | 0.00527263 | 23525.8 | 40.00 | 19.60 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 29792.91 | -27.60 | 0.00034190 | -27.60 | 0.20572670 | 21.4366 | 21.11 | 0.00669689 | 21.10 | 0.00669689 | 37.7023 | 15521.28 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_10:10 | SMSTORE8 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 8775.920 | 0.000 | 1.048170 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.8425 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 8775.92 | 8775.92 | 1.0000 | 1.10386963 | 1.048170 | 25.90 | 14.39 | 0.00699453 | 43857.7 | 12.80 | 10.89 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8775.92 | 33.40 | 0.00626594 | 16.30 | 0.20572670 | 19.6272 | 23.89 | 0.00719018 | 23.89 | 0.00719115 | 34.1523 | 9627.07 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_10:10_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_10:10 | SMSTORE8 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 31561.972 | 31561.972 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.048168 | 1.10386700 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 31561.97 | 31561.97 | 1.0000 | 1.10386700 | 1.048168 | 11.55 | 7.29 | 0.00552966 | 25550.0 | 40.00 | 19.60 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 31561.97 | -27.60 | 0.00034190 | -27.60 | 0.20572670 | 19.6273 | 21.11 | 0.00679652 | 21.10 | 0.00679652 | 38.2578 | 17723.30 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2020-06-03 19:18:53
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-AC_1:1_OA_CONTROLLER | DifferentialDryBulb | 0.41 | 1.94 | - | |||
PSZ-AC_2:2_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.05 | - | |||
PSZ-AC_3:3_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.05 | - | |||
PSZ-AC_4:4_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.05 | - | |||
PSZ-AC_5:5_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.05 | - | |||
PSZ-AC_6:6_OA_CONTROLLER | DifferentialDryBulb | 0.41 | 1.89 | - | |||
PSZ-AC_7:7_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 0.98 | - | |||
PSZ-AC_8:8_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 0.97 | - | |||
PSZ-AC_9:9_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 0.96 | - | |||
PSZ-AC_10:10_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.05 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
LGSTORE1 | 2150.50 | 4077.33 | 1410.83 |
SMSTORE1 | 1478.83 | 3818.00 | 764.17 |
SMSTORE2 | 1468.83 | 2876.33 | 825.67 |
SMSTORE3 | 1557.83 | 2913.33 | 918.50 |
SMSTORE4 | 1621.33 | 2980.83 | 1014.67 |
LGSTORE2 | 1630.83 | 2874.83 | 1166.50 |
SMSTORE5 | 1587.33 | 2882.33 | 1191.33 |
SMSTORE6 | 1615.17 | 2908.17 | 1237.00 |
SMSTORE7 | 1737.33 | 2969.17 | 1394.50 |
SMSTORE8 | 2075.83 | 3094.33 | 1774.00 |
Facility | 3205.17 | 4548.00 | 2329.33 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
LGSTORE1 | 5.67 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 2.17 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 0.00 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 0.17 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 27.50 | 0.00 | 0.00 | 0.00 |
Facility | 34.33 | 0.00 | 0.00 | 0.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2020-06-03 19:18:53
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
LGSTORE1 | 9.03 | 30.00 | 1805.20 | 0.952 | 0.241 | 0.000 | 0.000 |
SMSTORE1 | 4.51 | 15.00 | 902.60 | 0.986 | 0.253 | 0.000 | 0.000 |
SMSTORE2 | 3.77 | 15.00 | 902.60 | 1.167 | 0.329 | 0.000 | 0.000 |
SMSTORE3 | 3.77 | 15.00 | 902.60 | 1.163 | 0.329 | 0.000 | 0.000 |
SMSTORE4 | 3.77 | 15.00 | 902.60 | 1.143 | 0.329 | 0.000 | 0.000 |
LGSTORE2 | 13.20 | 30.00 | 1805.20 | 0.960 | 0.316 | 0.000 | 0.000 |
SMSTORE5 | 6.60 | 15.00 | 902.60 | 1.102 | 0.351 | 0.000 | 0.000 |
SMSTORE6 | 6.60 | 15.00 | 902.60 | 1.094 | 0.351 | 0.000 | 0.000 |
SMSTORE7 | 6.60 | 15.00 | 902.60 | 1.074 | 0.351 | 0.000 | 0.000 |
SMSTORE8 | 6.60 | 15.00 | 902.60 | 1.068 | 0.377 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
LGSTORE1 | 9.03 | 30.00 | 1805.20 | 0.000 | 0.000 | 0.000 | 0.000 |
SMSTORE1 | 4.51 | 15.00 | 902.60 | 0.000 | 0.000 | 0.000 | 0.000 |
SMSTORE2 | 3.77 | 15.00 | 902.60 | 0.799 | 0.000 | 0.000 | 0.000 |
SMSTORE3 | 3.77 | 15.00 | 902.60 | 0.799 | 0.000 | 0.000 | 0.000 |
SMSTORE4 | 3.77 | 15.00 | 902.60 | 0.799 | 0.000 | 0.000 | 0.000 |
LGSTORE2 | 13.20 | 30.00 | 1805.20 | 0.799 | 0.000 | 0.000 | 0.000 |
SMSTORE5 | 6.60 | 15.00 | 902.60 | 0.799 | 0.000 | 0.000 | 0.000 |
SMSTORE6 | 6.60 | 15.00 | 902.60 | 0.799 | 0.000 | 0.000 | 0.000 |
SMSTORE7 | 6.60 | 15.00 | 902.60 | 0.799 | 0.000 | 0.000 | 0.000 |
SMSTORE8 | 6.60 | 15.00 | 902.60 | 0.799 | 0.000 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2020-06-03 19:18:53
Surfaces by ClassTotal | Outdoors | |
Wall | 40 | 22 |
Floor | 10 | 10 |
Roof | 10 | 10 |
Internal Mass | 10 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 36 | 36 |
Door | 12 | 12 |
Glass Door | 12 | 12 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 10 |
Conditioned Zones | 10 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 0 |
Defaulted Fields | 0 |
Fields with Defaults | 0 |
Autosized Fields | 0 |
Autosizable Fields | 0 |
Autocalculated Fields | 0 |
Autocalculatable Fields | 0 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2020-06-03 19:18:53
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1022.51 | 3309.32 | 12-FEB-07:50 | 93911.57 | 17-JUL-13:30 |
Electricity:Building | 630.75 | 2091.32 | 01-JAN-00:10 | 39285.70 | 01-JAN-11:10 |
Electricity:Zone:LGSTORE1 | 144.52 | 394.83 | 01-JAN-00:10 | 7426.96 | 01-JAN-10:10 |
InteriorLights:Electricity | 502.03 | 1641.90 | 01-JAN-00:10 | 31196.17 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:LGSTORE1 | 118.16 | 319.93 | 01-JAN-00:10 | 6078.71 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity | 502.03 | 1641.90 | 01-JAN-00:10 | 31196.17 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE1 | 76.90 | 209.98 | 01-JAN-00:10 | 3952.17 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE1 | 63.72 | 172.53 | 01-JAN-00:10 | 3278.04 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE2 | 55.48 | 191.23 | 01-JAN-00:10 | 3595.92 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE2 | 45.01 | 153.78 | 01-JAN-00:10 | 2921.79 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE3 | 55.48 | 191.23 | 01-JAN-00:10 | 3595.92 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE3 | 45.01 | 153.78 | 01-JAN-00:10 | 2921.79 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE4 | 55.48 | 191.23 | 01-JAN-00:10 | 3595.92 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE4 | 45.01 | 153.78 | 01-JAN-00:10 | 2921.79 | 01-JAN-10:10 |
Electricity:Zone:LGSTORE2 | 80.97 | 304.27 | 01-JAN-00:10 | 5706.27 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:LGSTORE2 | 61.71 | 229.37 | 01-JAN-00:10 | 4358.02 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE5 | 40.48 | 152.14 | 01-JAN-00:10 | 2853.14 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE5 | 30.85 | 114.68 | 01-JAN-00:10 | 2179.01 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE6 | 40.48 | 152.14 | 01-JAN-00:10 | 2853.14 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE6 | 30.85 | 114.68 | 01-JAN-00:10 | 2179.01 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE7 | 40.48 | 152.14 | 01-JAN-00:10 | 2853.14 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE7 | 30.85 | 114.68 | 01-JAN-00:10 | 2179.01 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE8 | 40.48 | 152.14 | 01-JAN-00:10 | 2853.14 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE8 | 30.85 | 114.68 | 01-JAN-00:10 | 2179.01 | 01-JAN-11:10 |
InteriorEquipment:Electricity | 128.72 | 449.42 | 01-JAN-00:10 | 8089.53 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:LGSTORE1 | 26.36 | 74.90 | 01-JAN-00:10 | 1348.26 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity | 128.72 | 449.42 | 01-JAN-00:10 | 8089.53 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE1 | 13.18 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE2 | 10.47 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE3 | 10.47 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE4 | 10.47 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:LGSTORE2 | 19.26 | 74.90 | 01-JAN-00:10 | 1348.26 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE5 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE6 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE7 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE8 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
Electricity:Plant | 66.01 | 1218.00 | 01-JAN-09:10 | 13109.68 | 07-JAN-13:10 |
WaterSystems:Electricity | 66.01 | 1218.00 | 01-JAN-09:10 | 13109.68 | 07-JAN-13:10 |
Water Heater:WaterSystems:Electricity | 66.01 | 1218.00 | 01-JAN-09:10 | 13109.68 | 07-JAN-13:10 |
ElectricityPurchased:Facility | 1022.51 | 3309.32 | 12-FEB-07:50 | 93911.57 | 17-JUL-13:30 |
ElectricityPurchased:Plant | 1022.51 | 3309.32 | 12-FEB-07:50 | 93911.57 | 17-JUL-13:30 |
Cogeneration:ElectricityPurchased | 1022.51 | 3309.32 | 12-FEB-07:50 | 93911.57 | 17-JUL-13:30 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1022.51 | 3309.32 | 12-FEB-07:50 | 93911.57 | 17-JUL-13:30 |
ElectricityNet:Plant | 1022.51 | 3309.32 | 12-FEB-07:50 | 93911.57 | 17-JUL-13:30 |
Cogeneration:ElectricityNet | 1022.51 | 3309.32 | 12-FEB-07:50 | 93911.57 | 17-JUL-13:30 |
Electricity:HVAC | 234.74 | 0.00 | 01-JAN-00:10 | 50624.90 | 17-JUL-16:10 |
Fans:Electricity | 183.92 | 0.00 | 01-JAN-00:10 | 12470.16 | 09-JAN-09:10 |
General:Fans:Electricity | 183.92 | 0.00 | 01-JAN-00:10 | 12470.16 | 09-JAN-09:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 50.82 | 0.00 | 01-JAN-00:10 | 38610.04 | 17-JUL-16:10 |
ExteriorLights:Electricity | 91.01 | 0.00 | 01-JAN-08:20 | 6944.63 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 91.01 | 0.00 | 01-JAN-08:20 | 6944.63 | 01-JAN-06:10 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Gas:Facility | 575.31 | 0.00 | 01-JAN-00:10 | 312435.37 | 09-JAN-09:10 |
Gas:HVAC | 575.31 | 0.00 | 01-JAN-00:10 | 312435.37 | 09-JAN-09:10 |
Heating:Gas | 575.31 | 0.00 | 01-JAN-00:10 | 312435.37 | 09-JAN-09:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water:Plant | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
WaterSystems:Water | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water Heater:WaterSystems:Water | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
MainsWater:Facility | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
MainsWater:Plant | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
WaterSystems:MainsWater | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water Heater:WaterSystems:MainsWater | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:Facility | 1148.63 | 0.00 | 01-JAN-00:10 | 387010.47 | 09-JAN-09:10 |
EnergyTransfer:Building | 472.20 | 0.00 | 01-JAN-00:10 | 137062.18 | 09-JAN-09:10 |
EnergyTransfer:Zone:LGSTORE1 | 96.54 | 0.00 | 01-JAN-00:10 | 24091.63 | 09-JAN-09:10 |
Heating:EnergyTransfer | 164.56 | 0.00 | 01-JAN-00:10 | 136549.31 | 09-JAN-09:10 |
Heating:EnergyTransfer:Zone:LGSTORE1 | 23.24 | 0.00 | 01-JAN-00:10 | 23578.76 | 09-JAN-09:10 |
Cooling:EnergyTransfer | 307.64 | 0.00 | 01-JAN-00:10 | 92090.19 | 17-JUL-16:10 |
Cooling:EnergyTransfer:Zone:LGSTORE1 | 73.30 | 0.00 | 01-JAN-00:10 | 19269.65 | 28-JAN-00:10 |
EnergyTransfer:Zone:SMSTORE1 | 48.21 | 0.00 | 01-JAN-00:10 | 11120.90 | 08-JAN-09:10 |
Heating:EnergyTransfer:Zone:SMSTORE1 | 8.60 | 0.00 | 01-JAN-00:10 | 10722.20 | 08-JAN-09:10 |
Cooling:EnergyTransfer:Zone:SMSTORE1 | 39.61 | 0.00 | 01-JAN-00:10 | 10469.66 | 27-JUL-20:20 |
EnergyTransfer:Zone:SMSTORE2 | 38.72 | 0.00 | 01-JAN-00:10 | 12361.76 | 09-JAN-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE2 | 10.68 | 0.00 | 01-JAN-00:10 | 12361.76 | 09-JAN-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE2 | 28.04 | 0.00 | 01-JAN-00:10 | 8010.66 | 17-JUL-16:10 |
EnergyTransfer:Zone:SMSTORE3 | 38.63 | 0.00 | 01-JAN-00:10 | 12854.10 | 09-JAN-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE3 | 11.49 | 0.00 | 01-JAN-00:10 | 12854.10 | 09-JAN-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE3 | 27.14 | 0.00 | 01-JAN-00:10 | 8070.82 | 17-JUL-16:10 |
EnergyTransfer:Zone:SMSTORE4 | 37.92 | 0.00 | 01-JAN-00:10 | 13287.26 | 09-JAN-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE4 | 12.74 | 0.00 | 01-JAN-00:10 | 13287.26 | 09-JAN-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE4 | 25.18 | 0.00 | 01-JAN-00:10 | 7993.50 | 17-JUL-16:10 |
EnergyTransfer:Zone:LGSTORE2 | 66.28 | 0.00 | 01-JAN-00:10 | 24906.44 | 09-JAN-09:10 |
Heating:EnergyTransfer:Zone:LGSTORE2 | 24.17 | 0.00 | 01-JAN-00:10 | 24906.44 | 09-JAN-09:10 |
Cooling:EnergyTransfer:Zone:LGSTORE2 | 42.11 | 0.00 | 01-JAN-00:10 | 14514.96 | 17-JUL-16:10 |
EnergyTransfer:Zone:SMSTORE5 | 34.38 | 0.00 | 01-JAN-00:10 | 13460.75 | 09-JAN-09:10 |
Heating:EnergyTransfer:Zone:SMSTORE5 | 14.30 | 0.00 | 01-JAN-00:10 | 13460.75 | 09-JAN-09:10 |
Cooling:EnergyTransfer:Zone:SMSTORE5 | 20.08 | 0.00 | 01-JAN-00:10 | 7628.36 | 17-JUL-16:10 |
EnergyTransfer:Zone:SMSTORE6 | 34.25 | 0.00 | 01-JAN-00:10 | 13487.69 | 09-JAN-09:10 |
Heating:EnergyTransfer:Zone:SMSTORE6 | 14.72 | 0.00 | 01-JAN-00:10 | 13487.69 | 09-JAN-09:10 |
Cooling:EnergyTransfer:Zone:SMSTORE6 | 19.53 | 0.00 | 01-JAN-00:10 | 7568.87 | 17-JUL-16:10 |
EnergyTransfer:Zone:SMSTORE7 | 34.48 | 0.00 | 01-JAN-00:10 | 13814.53 | 09-JAN-09:10 |
Heating:EnergyTransfer:Zone:SMSTORE7 | 16.69 | 0.00 | 01-JAN-00:10 | 13814.53 | 09-JAN-09:10 |
Cooling:EnergyTransfer:Zone:SMSTORE7 | 17.79 | 0.00 | 01-JAN-00:10 | 7475.43 | 17-JUL-16:10 |
EnergyTransfer:Zone:SMSTORE8 | 42.82 | 0.00 | 01-JAN-00:10 | 16318.97 | 09-JAN-09:10 |
Heating:EnergyTransfer:Zone:SMSTORE8 | 27.95 | 0.00 | 01-JAN-00:10 | 16318.97 | 09-JAN-09:10 |
Cooling:EnergyTransfer:Zone:SMSTORE8 | 14.87 | 0.00 | 01-JAN-00:10 | 7753.28 | 17-JUL-13:00 |
EnergyTransfer:HVAC | 676.42 | 0.00 | 01-JAN-00:10 | 249948.29 | 09-JAN-09:10 |
HeatingCoils:EnergyTransfer | 460.25 | 0.00 | 01-JAN-00:10 | 249948.29 | 09-JAN-09:10 |
CoolingCoils:EnergyTransfer | 216.17 | 0.00 | 01-JAN-00:10 | 138751.27 | 17-JUL-16:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2020-06-03 19:18:53
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
LGSTORE1 | 0.000 | 0.000 | 23.243 | -73.299 | 0.000 | 0.000 | 13.604 | 118.163 | 26.357 | 23.142 | 0.000 | 1.726 | 0.000 | 0.000 | -12.533 | 0.000 | -43.460 | -76.944 |
SMSTORE1 | 0.000 | 0.000 | 8.601 | -39.605 | 0.000 | 0.000 | 6.659 | 63.721 | 13.179 | 11.453 | 0.000 | 0.931 | 0.000 | 0.000 | -6.562 | 0.000 | -21.036 | -37.342 |
SMSTORE2 | 0.000 | 0.000 | 10.675 | -28.041 | 0.000 | 0.000 | 4.054 | 45.008 | 10.467 | 11.436 | 0.000 | 0.912 | 0.001 | 0.000 | -6.480 | 0.000 | -21.670 | -26.361 |
SMSTORE3 | 0.000 | 0.000 | 11.494 | -27.136 | 0.000 | 0.000 | 4.060 | 45.008 | 10.467 | 11.452 | 0.000 | 0.912 | 0.001 | 0.000 | -6.420 | 0.000 | -21.585 | -28.252 |
SMSTORE4 | 0.000 | 0.000 | 12.736 | -25.179 | 0.000 | 0.000 | 4.070 | 45.008 | 10.467 | 11.476 | 0.000 | 0.913 | 0.002 | 0.000 | -6.354 | 0.000 | -21.477 | -31.659 |
LGSTORE2 | 0.000 | 0.000 | 24.165 | -42.112 | 0.000 | 0.000 | 14.078 | 61.707 | 19.261 | 23.102 | 0.000 | 1.646 | 0.004 | 0.000 | -12.363 | 0.000 | -39.331 | -50.154 |
SMSTORE5 | 0.000 | 0.000 | 14.300 | -20.077 | 0.000 | 0.000 | 7.008 | 30.853 | 9.631 | 11.525 | 0.000 | 0.914 | 0.003 | 0.000 | -6.207 | 0.000 | -21.493 | -26.453 |
SMSTORE6 | 0.000 | 0.000 | 14.715 | -19.531 | 0.000 | 0.000 | 7.012 | 30.853 | 9.631 | 11.535 | 0.000 | 0.914 | 0.002 | 0.000 | -6.184 | 0.000 | -21.459 | -27.486 |
SMSTORE7 | 0.000 | 0.000 | 16.686 | -17.789 | 0.000 | 0.000 | 7.029 | 30.853 | 9.631 | 11.569 | 0.000 | 0.914 | 0.002 | 0.000 | -6.095 | 0.000 | -21.322 | -31.475 |
SMSTORE8 | 0.000 | 0.000 | 27.947 | -14.871 | 0.000 | 0.000 | 7.058 | 30.853 | 9.631 | 11.664 | 0.000 | 0.965 | 0.003 | 0.000 | -5.766 | 0.000 | -27.571 | -39.911 |
Total Facility | 0.000 | 0.000 | 164.563 | -307.640 | 0.000 | 0.000 | 74.631 | 502.028 | 128.721 | 138.354 | 0.000 | 10.747 | 0.018 | 0.000 | -74.963 | 0.000 | -260.405 | -376.037 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
LGSTORE1 | 27-JUL-08:62 | 0.00 | 0.00 | 0.00 | -36911.07 | 0.00 | 0.00 | 95.86 | 3199.32 | 749.03 | 400.50 | 0.00 | 0.00 | 32844.02 | 0.00 | -0.00 | 0.00 | -377.66 | 0.00 |
SMSTORE1 | 02-AUG-08:62 | 0.00 | 0.00 | 0.00 | -21670.06 | 0.00 | 0.00 | 46.94 | 1725.28 | 374.52 | 165.47 | 0.00 | 0.00 | 19616.34 | 0.00 | -0.00 | 0.00 | -258.48 | 0.00 |
SMSTORE2 | 28-SEP-07:01 | 0.00 | 0.00 | 0.00 | -26081.45 | 0.00 | 0.00 | 47.74 | 1537.78 | 374.52 | 0.00 | 0.00 | 0.00 | 24683.40 | 0.00 | -185.48 | 0.00 | -376.51 | 0.00 |
SMSTORE3 | 28-SEP-07:01 | 0.00 | 0.00 | 0.00 | -26175.29 | 0.00 | 0.00 | 47.73 | 1537.78 | 374.52 | 0.00 | 0.00 | 0.00 | 24777.29 | 0.00 | -185.54 | 0.00 | -376.49 | 0.00 |
SMSTORE4 | 28-SEP-07:01 | 0.00 | 0.00 | 0.00 | -25889.66 | 0.00 | 0.00 | 48.28 | 1537.78 | 374.52 | 0.00 | 0.00 | 0.00 | 24485.51 | 0.00 | -183.16 | 0.00 | -373.27 | 0.00 |
LGSTORE2 | 26-AUG-08:62 | 0.00 | 0.00 | 0.00 | -37167.08 | 0.00 | 0.00 | 213.80 | 2293.69 | 749.03 | 493.07 | 0.00 | 0.00 | 33711.80 | 0.00 | -0.00 | 0.00 | -294.31 | 0.00 |
SMSTORE5 | 26-AUG-08:62 | 0.00 | 0.00 | 0.00 | -19544.11 | 0.00 | 0.00 | 103.14 | 1146.85 | 374.52 | 243.71 | 0.00 | 0.00 | 17846.80 | 0.00 | -0.00 | 0.00 | -170.89 | 0.00 |
SMSTORE6 | 26-AUG-08:62 | 0.00 | 0.00 | 0.00 | -19332.16 | 0.00 | 0.00 | 103.67 | 1146.85 | 374.52 | 244.76 | 0.00 | 0.00 | 17632.17 | 0.00 | -0.00 | 0.00 | -169.79 | 0.00 |
SMSTORE7 | 26-AUG-08:62 | 0.00 | 0.00 | 0.00 | -18972.47 | 0.00 | 0.00 | 105.36 | 1146.85 | 374.52 | 247.87 | 0.00 | 0.00 | 17263.73 | 0.00 | -0.00 | 0.00 | -165.85 | 0.00 |
SMSTORE8 | 13-AUG-09:01 | 0.00 | 0.00 | 0.00 | -19569.49 | 0.00 | 0.00 | 102.70 | 1146.85 | 374.52 | 351.27 | 0.00 | 0.00 | 17747.92 | 0.00 | -0.00 | 0.00 | -153.76 | 0.00 |
Total Facility | 27-JUL-08:62 | 0.00 | 0.00 | 0.00 | -178730.64 | 0.00 | 0.00 | 1074.83 | 20571.05 | 5393.02 | 2383.22 | 0.00 | 0.00 | 151667.12 | 0.00 | 0.00 | 0.00 | -2358.60 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
LGSTORE1 | 27-JAN-08:61 | 0.00 | 0.00 | 60250.56 | 0.00 | 0.00 | 0.00 | 0.00 | 319.93 | 74.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1450.65 | 0.00 | -2338.96 | -56855.78 |
SMSTORE1 | 27-JAN-08:61 | 0.00 | 0.00 | 31702.31 | 0.00 | 0.00 | 0.00 | 0.00 | 172.53 | 37.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -751.70 | 0.00 | -1172.46 | -29988.13 |
SMSTORE2 | 31-DEC-08:61 | 0.00 | 0.00 | 31635.58 | 0.00 | 0.00 | 0.00 | 0.00 | 153.78 | 37.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -792.04 | 0.00 | -1157.63 | -29877.13 |
SMSTORE3 | 31-DEC-08:61 | 0.00 | 0.00 | 31713.64 | 0.00 | 0.00 | 0.00 | 0.00 | 153.78 | 37.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -786.52 | 0.00 | -1150.33 | -29968.02 |
SMSTORE4 | 31-DEC-08:61 | 0.00 | 0.00 | 31583.03 | 0.00 | 0.00 | 0.00 | 0.00 | 153.78 | 37.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -782.02 | 0.00 | -1143.73 | -29848.51 |
LGSTORE2 | 08-JAN-09:01 | 0.00 | 0.00 | 59291.21 | 0.00 | 0.00 | 0.00 | 0.00 | 229.37 | 74.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -929.30 | 0.00 | -1796.01 | -56870.17 |
SMSTORE5 | 08-JAN-09:01 | 0.00 | 0.00 | 29894.88 | 0.00 | 0.00 | 0.00 | 0.00 | 114.68 | 37.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -465.84 | 0.00 | -999.24 | -28581.94 |
SMSTORE6 | 08-JAN-09:01 | 0.00 | 0.00 | 29671.39 | 0.00 | 0.00 | 0.00 | 0.00 | 114.68 | 37.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -465.55 | 0.00 | -999.25 | -28358.73 |
SMSTORE7 | 09-JAN-08:61 | 0.00 | 0.00 | 29946.64 | 0.00 | 0.00 | 0.00 | 0.00 | 114.68 | 37.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -736.98 | 0.00 | -1011.08 | -28350.72 |
SMSTORE8 | 28-JAN-08:61 | 0.00 | 0.00 | 31701.23 | 0.00 | 0.00 | 0.00 | 0.00 | 114.68 | 37.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -678.96 | 0.00 | -1238.92 | -29935.49 |
Total Facility | 30-JAN-08:61 | 0.00 | 0.00 | 345775.53 | 0.00 | 0.00 | 0.00 | 435.71 | 5793.92 | 1460.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -6265.15 | 0.00 | -10653.64 | -336546.98 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2020-06-03 19:18:53
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 1.9409 | 0.0000 | 29.9961 | 1.0000 | 0.4115 | 1.9409 | 0.2120 | 1.0000 | 0.4115 | 0.2120 | ||
PSZ-AC_2:2 | 1.0527 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.0527 | 0.1954 | 1.0000 | 0.2057 | 0.1954 | ||
PSZ-AC_3:3 | 1.0495 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.0495 | 0.1960 | 1.0000 | 0.2057 | 0.1960 | ||
PSZ-AC_4:4 | 1.0535 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.0535 | 0.1953 | 1.0000 | 0.2057 | 0.1953 | ||
PSZ-AC_5:5 | 1.0467 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.0467 | 0.1965 | 1.0000 | 0.2057 | 0.1965 | ||
PSZ-AC_6:6 | 1.8930 | 0.0000 | 29.9961 | 1.0000 | 0.4115 | 1.8930 | 0.2174 | 1.0000 | 0.4115 | 0.2174 | ||
PSZ-AC_7:7 | 0.9570 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 0.9794 | 0.2101 | 1.0000 | 0.2057 | 0.2101 | ||
PSZ-AC_8:8 | 0.9467 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 0.9705 | 0.2120 | 1.0000 | 0.2057 | 0.2120 | ||
PSZ-AC_9:9 | 0.9597 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 0.9597 | 0.2144 | 1.0000 | 0.2057 | 0.2144 | ||
PSZ-AC_10:10 | 1.0482 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.0482 | 0.2107 | 1.0000 | 0.2057 | 0.1963 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 1.9409 | 0.0000 | 29.9961 | 1.0000 | 0.4115 | 1.9409 | 1.0000 | 1.0000 | 0.4115 | 0.2120 | ||
PSZ-AC_2:2 | 1.0527 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.0527 | 1.0000 | 1.0000 | 0.2057 | 0.1954 | ||
PSZ-AC_3:3 | 1.0495 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.0495 | 1.0000 | 1.0000 | 0.2057 | 0.1960 | ||
PSZ-AC_4:4 | 1.0535 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.0535 | 1.0000 | 1.0000 | 0.2057 | 0.1953 | ||
PSZ-AC_5:5 | 1.0467 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.0467 | 1.0000 | 1.0000 | 0.2057 | 0.1965 | ||
PSZ-AC_6:6 | 1.8930 | 0.0000 | 29.9961 | 1.0000 | 0.4115 | 1.8930 | 1.0000 | 1.0000 | 0.4115 | 0.2174 | ||
PSZ-AC_7:7 | 0.9570 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 0.9570 | 1.0000 | 1.0000 | 0.2057 | 0.2150 | ||
PSZ-AC_8:8 | 0.9467 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 0.9467 | 1.0000 | 1.0000 | 0.2057 | 0.2173 | ||
PSZ-AC_9:9 | 0.9597 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 0.9597 | 1.0000 | 1.0000 | 0.2057 | 0.2144 | ||
PSZ-AC_10:10 | 1.0482 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.0482 | 1.0000 | 1.0000 | 0.2057 | 0.1963 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
LGSTORE1 | PSZ-AC_1:1 | 0.000000 | 29.9961 | 0.001181 | 348.39 | 0.4115 | 1.0000 | 0.4115 | 1.000 | 0.4115 |
SMSTORE1 | PSZ-AC_2:2 | 0.000000 | 14.9980 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE2 | PSZ-AC_3:3 | 0.000000 | 14.9980 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE3 | PSZ-AC_4:4 | 0.000000 | 14.9980 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE4 | PSZ-AC_5:5 | 0.000000 | 14.9980 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
LGSTORE2 | PSZ-AC_6:6 | 0.000000 | 29.9961 | 0.001181 | 348.39 | 0.4115 | 1.0000 | 0.4115 | 1.000 | 0.4115 |
SMSTORE5 | PSZ-AC_7:7 | 0.000000 | 14.9980 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE6 | PSZ-AC_8:8 | 0.000000 | 14.9980 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE7 | PSZ-AC_9:9 | 0.000000 | 14.9980 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE8 | PSZ-AC_10:10 | 0.000000 | 14.9980 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC_1:1 | 0.000000 | 30.00 | 0.001181 | 348.3864 | 0.4115 | 0.4115 | 0.4115 |
PSZ-AC_2:2 | 0.000000 | 15.00 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_3:3 | 0.000000 | 15.00 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_4:4 | 0.000000 | 15.00 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_5:5 | 0.000000 | 15.00 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_6:6 | 0.000000 | 30.00 | 0.001181 | 348.3864 | 0.4115 | 0.4115 | 0.4115 |
PSZ-AC_7:7 | 0.000000 | 15.00 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_8:8 | 0.000000 | 15.00 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_9:9 | 0.000000 | 15.00 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_10:10 | 0.000000 | 15.00 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LGSTORE1 | PSZ-AC_1:1 | 1.9409 | 1.9409 | 1.9409 | 0.4115 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE1 | PSZ-AC_2:2 | 1.0527 | 1.0527 | 1.0527 | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE2 | PSZ-AC_3:3 | 1.0495 | 1.0495 | 1.0495 | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE3 | PSZ-AC_4:4 | 1.0535 | 1.0535 | 1.0535 | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE4 | PSZ-AC_5:5 | 1.0467 | 1.0467 | 1.0467 | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
LGSTORE2 | PSZ-AC_6:6 | 1.8930 | 1.8930 | 1.8930 | 0.4115 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE5 | PSZ-AC_7:7 | 0.9570 | 0.9570 | 0.9570 | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE6 | PSZ-AC_8:8 | 0.9467 | 0.9467 | 0.9467 | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE7 | PSZ-AC_9:9 | 0.9597 | 0.9597 | 0.9597 | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE8 | PSZ-AC_10:10 | 1.0482 | 1.0482 | 1.0482 | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 1.9409 | 1.9409 | 1.9409 | 1.9409 | 0.4115 | 1.0000 |
PSZ-AC_2:2 | 1.0527 | 1.0527 | 1.0527 | 1.0527 | 0.2057 | 1.0000 |
PSZ-AC_3:3 | 1.0495 | 1.0495 | 1.0495 | 1.0495 | 0.2057 | 1.0000 |
PSZ-AC_4:4 | 1.0535 | 1.0535 | 1.0535 | 1.0535 | 0.2057 | 1.0000 |
PSZ-AC_5:5 | 1.0467 | 1.0467 | 1.0467 | 1.0467 | 0.2057 | 1.0000 |
PSZ-AC_6:6 | 1.8930 | 1.8930 | 1.8930 | 1.8930 | 0.4115 | 1.0000 |
PSZ-AC_7:7 | 0.9570 | 0.9794 | 0.9570 | 0.9570 | 0.2057 | 1.0000 |
PSZ-AC_8:8 | 0.9467 | 0.9705 | 0.9467 | 0.9467 | 0.2057 | 1.0000 |
PSZ-AC_9:9 | 0.9597 | 0.9597 | 0.9597 | 0.9597 | 0.2057 | 1.0000 |
PSZ-AC_10:10 | 1.0482 | 1.0482 | 1.0482 | 1.0482 | 0.2057 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LGSTORE1 | PSZ-AC_1:1 | 1.9409 | 1.9409 | 1.9409 | 0.4115 | 0.2361 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE1 | PSZ-AC_2:2 | 1.0527 | 1.0527 | 1.0527 | 0.2057 | 0.2378 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE2 | PSZ-AC_3:3 | 1.0495 | 1.0495 | 1.0495 | 0.2057 | 0.2351 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE3 | PSZ-AC_4:4 | 1.0535 | 1.0535 | 1.0535 | 0.2057 | 0.2340 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE4 | PSZ-AC_5:5 | 1.0467 | 1.0467 | 1.0467 | 0.2057 | 0.2318 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
LGSTORE2 | PSZ-AC_6:6 | 1.8930 | 1.8930 | 1.8930 | 0.4115 | 0.2438 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE5 | PSZ-AC_7:7 | 0.9570 | 0.9570 | 0.9570 | 0.2057 | 0.2267 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE6 | PSZ-AC_8:8 | 0.9467 | 0.9467 | 0.9467 | 0.2057 | 0.2270 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE7 | PSZ-AC_9:9 | 0.9597 | 0.9597 | 0.9597 | 0.2057 | 0.2241 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE8 | PSZ-AC_10:10 | 1.0482 | 1.0482 | 1.0482 | 0.2057 | 0.1963 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 1.9409 | 1.9409 | 1.9409 | 1.9409 | 0.4115 | 1.0000 |
PSZ-AC_2:2 | 1.0527 | 1.0527 | 1.0527 | 1.0527 | 0.2057 | 1.0000 |
PSZ-AC_3:3 | 1.0495 | 1.0495 | 1.0495 | 1.0495 | 0.2057 | 1.0000 |
PSZ-AC_4:4 | 1.0535 | 1.0535 | 1.0535 | 1.0535 | 0.2057 | 1.0000 |
PSZ-AC_5:5 | 1.0467 | 1.0467 | 1.0467 | 1.0467 | 0.2057 | 1.0000 |
PSZ-AC_6:6 | 1.8930 | 1.8930 | 1.8930 | 1.8930 | 0.4115 | 1.0000 |
PSZ-AC_7:7 | 0.9570 | 0.9570 | 0.9570 | 0.9570 | 0.2057 | 1.0000 |
PSZ-AC_8:8 | 0.9467 | 0.9467 | 0.9467 | 0.9467 | 0.2057 | 1.0000 |
PSZ-AC_9:9 | 0.9597 | 0.9597 | 0.9597 | 0.9597 | 0.2057 | 1.0000 |
PSZ-AC_10:10 | 1.0482 | 1.0482 | 1.0482 | 1.0482 | 0.2057 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2020-06-03 19:18:53
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Great Falls Intl Arpt MT USA TMY3 WMO#=727750 |
Total gross floor area [m2] | 2090.32 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
LGSTORE1 | 348.39 | 348.39 | 0.00 | 112.00 |
SMSTORE1 | 174.19 | 174.19 | 0.00 | 112.00 |
SMSTORE2 | 174.19 | 174.19 | 0.00 | 84.29 |
SMSTORE3 | 174.19 | 174.19 | 0.00 | 84.29 |
SMSTORE4 | 174.19 | 174.19 | 0.00 | 84.29 |
LGSTORE2 | 348.39 | 348.39 | 0.00 | 77.29 |
SMSTORE5 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE6 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE7 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE8 | 174.19 | 174.19 | 0.00 | 77.29 |
Totals | 2090.32 | 2090.32 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 0.00 |
Number of hours not met | 0.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Fuel Use [GJ] | Additional Fuel Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- Not Subdivided | 0.00 | 0.00 | 575.31 | 312435.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- Not Subdivided | 50.82 | 38610.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 502.03 | 31196.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 91.01 | 6944.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 128.72 | 8089.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 183.92 | 12470.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 66.01 | 13109.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 128.72 | 1022.51 |
Natural Gas | 0.00 | 575.31 |
Additional | 0.00 | 0.00 |
Total | 128.72 | 1597.82 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 240.17 |
Space Heating | 0.00 |
Space Cooling | 24.31 |
Fans (All) | 87.98 |
Service Water Heating | 31.58 |
Receptacle Equipment | 61.58 |
Miscellaneous (All) | 489.16 |
Subtotal | 489.16 |
Natural Gas [MJ/m2] | |
Space Heating | 275.23 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 275.23 |
Subtotal | 275.23 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 31.42 |
Space Heating | 36.01 |
Space Cooling | 3.18 |
Fans (All) | 11.51 |
Service Water Heating | 4.13 |
Receptacle Equipment | 8.06 |
Miscellaneous | 5.70 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
TYPE1_OCC_SCH | 1630. | 5840. |
TYPE2_OCC_SCH | 995. | 4429. |
TYPE3_OCC_SCH | 1709. | 4064. |
TYPE1_LIGHT_SCH | 5131. | 8760. |
TYPE2_LIGHT_SCH | 4096. | 8760. |
TYPE3_LIGHT_SCH | 3767. | 8760. |
TYPE1_EQUIP_SCH | 4888. | 8760. |
TYPE2_EQUIP_SCH | 3911. | 8760. |
TYPE3_EQUIP_SCH | 3600. | 8760. |
TYPE1_INFIL_SCH | 4302. | 8760. |
TYPE2_INFIL_SCH | 5164. | 8760. |
TYPE3_INFIL_SCH | 5438. | 8760. |
INFIL_DOOR_OPENING_SCH | 2477. | 4380. |
TYPE1_MINOA_MOTORIZEDDAMPER_SCH | 5579. | 5579. |
TYPE2_MINOA_MOTORIZEDDAMPER_SCH | 4429. | 4429. |
TYPE3_MINOA_MOTORIZEDDAMPER_SCH | 4064. | 4064. |
TYPE1_SWH_SCH | 2063. | 6048. |
TYPE2_SWH_SCH | 1831. | 4429. |
TYPE3_SWH_SCH | 1733. | 4064. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 7118. | 8760. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 5839. | 5839. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 7300. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
TYPE1_HTGSETP_SCH_YES_OPTIMUM | LGSTORE1 DUALSPSCHED | January | 21.11 | 365 | 21.11 | 365 |
TYPE1_CLGSETP_SCH_YES_OPTIMUM | LGSTORE1 DUALSPSCHED | July | 23.89 | 365 | 23.89 | 365 |
TYPE2_HTGSETP_SCH_YES_OPTIMUM | SMSTORE2 DUALSPSCHED | January | 21.11 | 365 | 15.56 | 365 |
TYPE2_CLGSETP_SCH_YES_OPTIMUM | SMSTORE2 DUALSPSCHED | July | 23.89 | 365 | 29.44 | 365 |
TYPE3_HTGSETP_SCH_YES_OPTIMUM | LGSTORE2 DUALSPSCHED | January | 21.11 | 365 | 15.56 | 365 |
TYPE3_CLGSETP_SCH_YES_OPTIMUM | LGSTORE2 DUALSPSCHED | July | 23.89 | 365 | 29.44 | 365 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Meter
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.171927E+12 |
February | 0.000 | 0.956365E+11 |
March | 0.000 | 0.752745E+11 |
April | 0.000 | 0.281965E+11 |
May | 0.000 | 0.176056E+11 |
June | 0.000 | 0.396179E+09 |
July | 0.000 | 0.000 |
August | 0.000 | 4614389.479 |
September | 0.000 | 0.223943E+10 |
October | 0.000 | 0.102831E+11 |
November | 0.000 | 0.514079E+11 |
December | 0.000 | 0.122339E+12 |
Annual Sum or Average | 0.575310E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.171927E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Meter
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.171927E+12 |
February | 0.000 | 0.956365E+11 |
March | 0.000 | 0.752745E+11 |
April | 0.000 | 0.281965E+11 |
May | 0.000 | 0.176056E+11 |
June | 0.000 | 0.396179E+09 |
July | 0.000 | 0.000 |
August | 0.000 | 4614389.479 |
September | 0.000 | 0.223943E+10 |
October | 0.000 | 0.102831E+11 |
November | 0.000 | 0.514079E+11 |
December | 0.000 | 0.122339E+12 |
Annual Sum or Average | 0.575310E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.171927E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2015
For: Meter
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.171927E+12 |
February | 0.000 | 0.956365E+11 |
March | 0.000 | 0.752745E+11 |
April | 0.000 | 0.281965E+11 |
May | 0.000 | 0.176056E+11 |
June | 0.000 | 0.396179E+09 |
July | 0.000 | 0.000 |
August | 0.000 | 4614389.479 |
September | 0.000 | 0.223943E+10 |
October | 0.000 | 0.102831E+11 |
November | 0.000 | 0.514079E+11 |
December | 0.000 | 0.122339E+12 |
Annual Sum or Average | 0.575310E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.171927E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Meter
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.171927E+12 |
February | 0.000 | 0.956365E+11 |
March | 0.000 | 0.752745E+11 |
April | 0.000 | 0.281965E+11 |
May | 0.000 | 0.176056E+11 |
June | 0.000 | 0.396179E+09 |
July | 0.000 | 0.000 |
August | 0.000 | 4614389.479 |
September | 0.000 | 0.223943E+10 |
October | 0.000 | 0.102831E+11 |
November | 0.000 | 0.514079E+11 |
December | 0.000 | 0.122339E+12 |
Annual Sum or Average | 0.575310E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.171927E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTRIPMALL
For: Meter
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.171927E+12 |
February | 0.000 | 0.956365E+11 |
March | 0.000 | 0.752745E+11 |
April | 0.000 | 0.281965E+11 |
May | 0.000 | 0.176056E+11 |
June | 0.000 | 0.396179E+09 |
July | 0.000 | 0.000 |
August | 0.000 | 4614389.479 |
September | 0.000 | 0.223943E+10 |
October | 0.000 | 0.102831E+11 |
November | 0.000 | 0.514079E+11 |
December | 0.000 | 0.122339E+12 |
Annual Sum or Average | 0.575310E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.171927E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.171927E+12 |
February | 0.000 | 0.956365E+11 |
March | 0.000 | 0.752745E+11 |
April | 0.000 | 0.281965E+11 |
May | 0.000 | 0.176056E+11 |
June | 0.000 | 0.396179E+09 |
July | 0.000 | 0.000 |
August | 0.000 | 4614389.479 |
September | 0.000 | 0.223943E+10 |
October | 0.000 | 0.102831E+11 |
November | 0.000 | 0.514079E+11 |
December | 0.000 | 0.122339E+12 |
Annual Sum or Average | 0.575310E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.171927E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.171927E+12 |
February | 0.000 | 0.956365E+11 |
March | 0.000 | 0.752745E+11 |
April | 0.000 | 0.281965E+11 |
May | 0.000 | 0.176056E+11 |
June | 0.000 | 0.396179E+09 |
July | 0.000 | 0.000 |
August | 0.000 | 4614389.479 |
September | 0.000 | 0.223943E+10 |
October | 0.000 | 0.102831E+11 |
November | 0.000 | 0.514079E+11 |
December | 0.000 | 0.122339E+12 |
Annual Sum or Average | 0.575310E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.171927E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 6B
For: Meter
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.171927E+12 |
February | 0.000 | 0.956365E+11 |
March | 0.000 | 0.752745E+11 |
April | 0.000 | 0.281965E+11 |
May | 0.000 | 0.176056E+11 |
June | 0.000 | 0.396179E+09 |
July | 0.000 | 0.000 |
August | 0.000 | 4614389.479 |
September | 0.000 | 0.223943E+10 |
October | 0.000 | 0.102831E+11 |
November | 0.000 | 0.514079E+11 |
December | 0.000 | 0.122339E+12 |
Annual Sum or Average | 0.575310E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.171927E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MT_GREATFALLS
For: Meter
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.171927E+12 |
February | 0.000 | 0.956365E+11 |
March | 0.000 | 0.752745E+11 |
April | 0.000 | 0.281965E+11 |
May | 0.000 | 0.176056E+11 |
June | 0.000 | 0.396179E+09 |
July | 0.000 | 0.000 |
August | 0.000 | 4614389.479 |
September | 0.000 | 0.223943E+10 |
October | 0.000 | 0.102831E+11 |
November | 0.000 | 0.514079E+11 |
December | 0.000 | 0.122339E+12 |
Annual Sum or Average | 0.575310E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.171927E+12 |
Report: ZoneCoolingSummaryMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.928864E+09 | 20452.56 | 28-JAN-00:01 | -29.2 | -29.5 | 0.566652E+09 | 680.12 | 13-JAN-13:30 | 5.85 | 2.12 |
February | 0.190879E+10 | 16964.68 | 04-FEB-00:01 | -21.0 | -21.3 | 0.518221E+09 | 827.09 | 26-FEB-17:10 | 14.85 | 5.61 |
March | 0.247386E+10 | 15316.62 | 04-MAR-00:01 | -17.2 | -17.7 | 0.563040E+09 | 680.12 | 10-MAR-13:09 | 8.72 | 4.37 |
April | 0.386677E+10 | 9988.77 | 30-APR-08:04 | -2.8 | -4.0 | 0.591423E+09 | 898.99 | 16-APR-17:19 | 19.80 | 8.87 |
May | 0.570443E+10 | 15616.08 | 20-MAY-08:62 | 20.10 | 12.38 | 0.660504E+09 | 899.01 | 19-MAY-12:09 | 24.27 | 14.49 |
June | 0.960188E+10 | 31202.94 | 26-JUN-08:62 | 20.37 | 13.12 | 0.712204E+09 | 899.02 | 04-JUN-12:09 | 23.12 | 14.05 |
July | 0.134203E+11 | 36912.82 | 27-JUL-08:62 | 14.68 | 10.38 | 0.753628E+09 | 899.02 | 15-JUL-12:00 | 30.60 | 17.64 |
August | 0.127874E+11 | 36231.70 | 26-AUG-08:62 | 16.28 | 9.48 | 0.739068E+09 | 899.07 | 06-AUG-16:10 | 35.50 | 16.21 |
September | 0.101593E+11 | 34550.14 | 05-SEP-08:61 | 19.03 | 12.19 | 0.698029E+09 | 899.07 | 10-SEP-12:00 | 18.30 | 13.27 |
October | 0.725941E+10 | 9447.15 | 18-OCT-14:00 | 25.00 | 11.37 | 0.666022E+09 | 898.99 | 22-OCT-17:19 | 15.57 | 7.64 |
November | 0.375494E+10 | 15528.40 | 26-NOV-09:04 | -15.8 | -16.5 | 0.569291E+09 | 855.78 | 04-NOV-12:00 | 16.70 | 8.09 |
December | 0.143300E+10 | 18019.77 | 29-DEC-00:01 | -23.6 | -23.9 | 0.569732E+09 | 680.12 | 09-DEC-13:09 | 3.95 | 0.92 |
Annual Sum or Average | 0.732990E+11 | 0.760781E+10 | ||||||||
Minimum of Months | 0.928864E+09 | 9447.15 | -29.2 | -29.5 | 0.518221E+09 | 680.12 | 3.95 | 0.92 | ||
Maximum of Months | 0.134203E+11 | 36912.82 | 25.00 | 13.12 | 0.753628E+09 | 899.07 | 35.50 | 17.64 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.402521E+09 | 7466.85 | 19-JAN-09:04 | -17.1 | -17.6 | 0.289978E+09 | 408.18 | 01-JAN-18:00 | 2.80 | -0.1 |
February | 0.758008E+09 | 7611.11 | 09-FEB-09:04 | -18.2 | -18.5 | 0.273877E+09 | 449.50 | 26-FEB-17:19 | 14.10 | 5.33 |
March | 0.121191E+10 | 7899.99 | 04-MAR-09:04 | -19.3 | -20.0 | 0.298257E+09 | 425.13 | 26-MAR-17:00 | 8.90 | 1.04 |
April | 0.175724E+10 | 18271.69 | 25-APR-20:02 | 12.12 | 5.44 | 0.323132E+09 | 449.50 | 16-APR-16:10 | 20.00 | 8.80 |
May | 0.315991E+10 | 19441.29 | 13-MAY-20:14 | 17.80 | 7.43 | 0.346218E+09 | 449.50 | 13-MAY-12:09 | 23.40 | 10.96 |
June | 0.571849E+10 | 20441.82 | 24-JUN-22:02 | 16.60 | 7.89 | 0.357392E+09 | 449.52 | 18-JUN-12:09 | 21.78 | 14.73 |
July | 0.767882E+10 | 20800.08 | 27-JUL-08:62 | 14.68 | 10.38 | 0.375431E+09 | 449.50 | 23-JUL-17:19 | 23.87 | 12.98 |
August | 0.739182E+10 | 21673.39 | 02-AUG-08:62 | 11.88 | 8.37 | 0.368911E+09 | 449.51 | 20-AUG-12:09 | 18.98 | 12.62 |
September | 0.566307E+10 | 20917.30 | 08-SEP-20:30 | 13.60 | 8.06 | 0.355553E+09 | 449.53 | 10-SEP-12:50 | 18.77 | 13.26 |
October | 0.356584E+10 | 19549.27 | 15-OCT-18:08 | 16.93 | 8.37 | 0.354459E+09 | 449.49 | 22-OCT-17:19 | 15.57 | 7.64 |
November | 0.163996E+10 | 18228.12 | 04-NOV-19:22 | 13.70 | 6.55 | 0.309082E+09 | 449.49 | 05-NOV-17:19 | 12.73 | 5.65 |
December | 0.658053E+09 | 6392.28 | 14-DEC-09:03 | -12.3 | -12.4 | 0.294110E+09 | 400.48 | 10-DEC-18:00 | 0.00 | -3.2 |
Annual Sum or Average | 0.396056E+11 | 0.394640E+10 | ||||||||
Minimum of Months | 0.402521E+09 | 6392.28 | -19.3 | -20.0 | 0.273877E+09 | 400.48 | 0.00 | -3.2 | ||
Maximum of Months | 0.767882E+10 | 21673.39 | 17.80 | 10.38 | 0.375431E+09 | 449.53 | 23.87 | 14.73 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.187249E+09 | 7418.42 | 19-JAN-08:04 | -17.3 | -17.7 | 0.169060E+09 | 340.55 | 14-JAN-13:20 | 10.20 | 4.86 |
February | 0.515363E+09 | 7633.95 | 09-FEB-08:03 | -18.3 | -18.6 | 0.158327E+09 | 415.37 | 25-FEB-13:00 | 15.00 | 5.03 |
March | 0.926597E+09 | 7852.28 | 04-MAR-08:04 | -19.9 | -20.6 | 0.176601E+09 | 361.84 | 18-MAR-12:00 | 11.70 | 3.92 |
April | 0.131669E+10 | 4684.79 | 29-APR-07:02 | -4.5 | -6.1 | 0.185436E+09 | 432.53 | 08-APR-12:30 | 12.80 | 6.12 |
May | 0.208598E+10 | 18180.39 | 20-MAY-07:02 | 18.58 | 11.87 | 0.204448E+09 | 449.50 | 13-MAY-12:09 | 23.40 | 10.96 |
June | 0.399110E+10 | 23838.92 | 07-JUN-07:01 | 9.68 | 6.15 | 0.220409E+09 | 449.50 | 03-JUN-12:00 | 23.90 | 14.38 |
July | 0.545732E+10 | 22285.58 | 12-JUL-07:02 | 14.37 | 8.07 | 0.224203E+09 | 449.50 | 01-JUL-12:00 | 26.70 | 16.71 |
August | 0.533212E+10 | 24385.00 | 28-AUG-07:01 | 10.33 | 6.39 | 0.229475E+09 | 449.49 | 12-AUG-12:00 | 30.00 | 14.95 |
September | 0.396684E+10 | 26083.38 | 28-SEP-07:01 | 7.95 | 4.26 | 0.212051E+09 | 449.50 | 23-SEP-12:09 | 21.28 | 11.86 |
October | 0.261264E+10 | 24410.28 | 19-OCT-07:02 | 11.57 | 5.30 | 0.205342E+09 | 449.49 | 28-OCT-12:09 | 18.12 | 9.55 |
November | 0.126032E+10 | 6326.08 | 27-NOV-08:04 | -12.7 | -13.5 | 0.175306E+09 | 449.49 | 04-NOV-12:39 | 16.50 | 8.00 |
December | 0.388572E+09 | 6544.81 | 14-DEC-08:03 | -13.2 | -13.3 | 0.169060E+09 | 340.38 | 02-DEC-13:50 | 9.40 | 4.29 |
Annual Sum or Average | 0.280408E+11 | 0.232972E+10 | ||||||||
Minimum of Months | 0.187249E+09 | 4684.79 | -19.9 | -20.6 | 0.158327E+09 | 340.38 | 9.40 | 3.92 | ||
Maximum of Months | 0.545732E+10 | 26083.38 | 18.58 | 11.87 | 0.229475E+09 | 449.50 | 30.00 | 16.71 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.137097E+09 | 6403.94 | 25-JAN-08:04 | -13.4 | -14.0 | 0.169045E+09 | 340.06 | 14-JAN-13:09 | 10.40 | 5.00 |
February | 0.446254E+09 | 6939.11 | 02-FEB-08:03 | -15.0 | -15.5 | 0.157720E+09 | 410.36 | 25-FEB-13:00 | 15.00 | 5.03 |
March | 0.807920E+09 | 7944.29 | 04-MAR-08:04 | -19.9 | -20.6 | 0.175965E+09 | 358.49 | 18-MAR-12:00 | 11.70 | 3.92 |
April | 0.117234E+10 | 4788.20 | 29-APR-07:02 | -4.5 | -6.1 | 0.183975E+09 | 427.42 | 08-APR-12:30 | 12.80 | 6.12 |
May | 0.195477E+10 | 18187.07 | 20-MAY-07:02 | 18.58 | 11.87 | 0.203608E+09 | 449.50 | 13-MAY-12:09 | 23.40 | 10.96 |
June | 0.395109E+10 | 23896.11 | 07-JUN-07:01 | 9.68 | 6.15 | 0.220333E+09 | 449.50 | 03-JUN-12:00 | 23.90 | 14.38 |
July | 0.547485E+10 | 22352.96 | 12-JUL-07:02 | 14.37 | 8.07 | 0.224203E+09 | 449.50 | 01-JUL-12:00 | 26.70 | 16.71 |
August | 0.534245E+10 | 24505.62 | 28-AUG-07:01 | 10.33 | 6.39 | 0.229454E+09 | 449.49 | 12-AUG-12:00 | 30.00 | 14.95 |
September | 0.392164E+10 | 26177.23 | 28-SEP-07:01 | 7.95 | 4.26 | 0.211750E+09 | 449.50 | 23-SEP-12:09 | 21.28 | 11.86 |
October | 0.247712E+10 | 23388.26 | 19-OCT-07:02 | 11.57 | 5.30 | 0.204376E+09 | 449.49 | 28-OCT-12:09 | 18.12 | 9.55 |
November | 0.113614E+10 | 6481.61 | 27-NOV-08:04 | -12.7 | -13.5 | 0.173881E+09 | 449.49 | 04-NOV-12:00 | 16.70 | 8.09 |
December | 0.314339E+09 | 6201.96 | 12-DEC-08:03 | -11.5 | -12.1 | 0.168976E+09 | 340.06 | 09-DEC-13:09 | 3.95 | 0.92 |
Annual Sum or Average | 0.271360E+11 | 0.232329E+10 | ||||||||
Minimum of Months | 0.137097E+09 | 4788.20 | -19.9 | -20.6 | 0.157720E+09 | 340.06 | 3.95 | 0.92 | ||
Maximum of Months | 0.547485E+10 | 26177.23 | 18.58 | 11.87 | 0.229454E+09 | 449.50 | 30.00 | 16.71 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 90117529.61 | 6550.26 | 25-JAN-08:04 | -13.4 | -14.0 | 0.169031E+09 | 340.06 | 14-JAN-13:09 | 10.40 | 5.00 |
February | 0.357763E+09 | 4464.76 | 22-FEB-08:03 | -3.9 | -5.5 | 0.156985E+09 | 402.50 | 25-FEB-13:00 | 15.00 | 5.03 |
March | 0.664644E+09 | 4746.41 | 07-MAR-08:03 | -4.0 | -5.7 | 0.175268E+09 | 353.66 | 18-MAR-12:00 | 11.70 | 3.92 |
April | 0.968626E+09 | 4766.01 | 29-APR-07:02 | -4.5 | -6.1 | 0.181894E+09 | 416.48 | 08-APR-12:30 | 12.80 | 6.12 |
May | 0.172029E+10 | 17680.90 | 20-MAY-07:02 | 18.58 | 11.87 | 0.202238E+09 | 449.50 | 13-MAY-12:09 | 23.40 | 10.96 |
June | 0.374276E+10 | 23620.79 | 07-JUN-07:01 | 9.68 | 6.15 | 0.220080E+09 | 449.50 | 03-JUN-12:00 | 23.90 | 14.38 |
July | 0.530043E+10 | 21247.45 | 29-JUL-07:02 | 14.60 | 9.34 | 0.224166E+09 | 449.50 | 01-JUL-12:00 | 26.70 | 16.71 |
August | 0.515781E+10 | 24251.79 | 28-AUG-07:01 | 10.33 | 6.39 | 0.229302E+09 | 449.49 | 12-AUG-12:00 | 30.00 | 14.95 |
September | 0.372829E+10 | 25891.58 | 28-SEP-07:01 | 7.95 | 4.26 | 0.211082E+09 | 449.50 | 23-SEP-12:09 | 21.28 | 11.86 |
October | 0.224379E+10 | 20250.56 | 19-OCT-07:02 | 11.57 | 5.30 | 0.202566E+09 | 449.49 | 28-OCT-12:09 | 18.12 | 9.55 |
November | 0.974615E+09 | 7019.62 | 26-NOV-09:04 | -15.8 | -16.5 | 0.171875E+09 | 449.43 | 04-NOV-12:00 | 16.70 | 8.09 |
December | 0.229885E+09 | 5967.87 | 27-DEC-08:04 | -10.7 | -11.2 | 0.168918E+09 | 340.06 | 09-DEC-13:09 | 3.95 | 0.92 |
Annual Sum or Average | 0.251790E+11 | 0.231340E+10 | ||||||||
Minimum of Months | 90117529.61 | 4464.76 | -15.8 | -16.5 | 0.156985E+09 | 340.06 | 3.95 | 0.92 | ||
Maximum of Months | 0.530043E+10 | 25891.58 | 18.58 | 11.87 | 0.229302E+09 | 449.50 | 30.00 | 16.71 |
Report: ZoneCoolingSummaryMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 79812407.01 | 12785.62 | 05-JAN-09:04 | -9.3 | -9.4 | 0.577659E+09 | 906.82 | 14-JAN-15:00 | 10.00 | 4.55 |
February | 0.564385E+09 | 11781.93 | 23-FEB-09:04 | -6.7 | -7.4 | 0.531862E+09 | 1023.43 | 27-FEB-15:00 | 18.90 | 7.03 |
March | 0.919032E+09 | 13295.47 | 03-MAR-09:04 | -13.4 | -14.2 | 0.596411E+09 | 916.20 | 18-MAR-14:00 | 12.20 | 4.15 |
April | 0.174582E+10 | 9917.49 | 30-APR-09:04 | -2.3 | -3.7 | 0.601269E+09 | 1063.81 | 07-APR-16:00 | 21.10 | 9.06 |
May | 0.288950E+10 | 12176.16 | 20-MAY-08:62 | 20.10 | 12.38 | 0.671717E+09 | 1198.63 | 27-MAY-14:00 | 23.30 | 12.28 |
June | 0.619827E+10 | 34259.91 | 25-JUN-09:02 | 17.15 | 11.94 | 0.749207E+09 | 1198.64 | 03-JUN-14:09 | 24.18 | 14.31 |
July | 0.890908E+10 | 36762.14 | 27-JUL-08:62 | 14.68 | 10.38 | 0.766520E+09 | 1198.64 | 08-JUL-14:09 | 19.08 | 9.43 |
August | 0.872139E+10 | 37169.02 | 26-AUG-08:62 | 16.28 | 9.48 | 0.783582E+09 | 1198.72 | 05-AUG-14:20 | 34.40 | 17.09 |
September | 0.629533E+10 | 35574.25 | 08-SEP-08:62 | 14.60 | 9.19 | 0.713724E+09 | 1198.71 | 02-SEP-14:09 | 33.98 | 16.01 |
October | 0.394969E+10 | 10340.02 | 10-OCT-08:04 | -3.7 | -4.5 | 0.666311E+09 | 1198.63 | 21-OCT-14:00 | 16.10 | 8.09 |
November | 0.162421E+10 | 11638.36 | 11-NOV-10:03 | -6.7 | -7.8 | 0.567484E+09 | 1172.20 | 04-NOV-14:50 | 16.78 | 7.98 |
December | 0.215883E+09 | 13017.77 | 12-DEC-09:04 | -9.8 | -10.5 | 0.578682E+09 | 906.82 | 02-DEC-15:00 | 3.90 | 1.29 |
Annual Sum or Average | 0.421124E+11 | 0.780443E+10 | ||||||||
Minimum of Months | 79812407.01 | 9917.49 | -13.4 | -14.2 | 0.531862E+09 | 906.82 | 3.90 | 1.29 | ||
Maximum of Months | 0.890908E+10 | 37169.02 | 20.10 | 12.38 | 0.783582E+09 | 1198.72 | 34.40 | 17.09 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 24202298.38 | 5893.39 | 05-JAN-09:04 | -9.3 | -9.4 | 0.288849E+09 | 453.41 | 14-JAN-15:09 | 10.50 | 5.05 |
February | 0.206156E+09 | 5306.97 | 23-FEB-09:04 | -6.7 | -7.4 | 0.267462E+09 | 532.50 | 25-FEB-15:00 | 15.00 | 5.18 |
March | 0.382136E+09 | 6685.73 | 03-MAR-09:04 | -13.4 | -14.2 | 0.299041E+09 | 476.45 | 18-MAR-14:00 | 12.20 | 4.15 |
April | 0.619478E+09 | 4445.76 | 28-APR-08:02 | -2.7 | -4.0 | 0.306233E+09 | 540.15 | 01-APR-14:00 | 18.30 | 6.98 |
May | 0.121721E+10 | 11898.45 | 20-MAY-08:62 | 20.10 | 12.38 | 0.340948E+09 | 599.32 | 27-MAY-14:00 | 23.30 | 12.28 |
June | 0.307843E+10 | 18021.20 | 25-JUN-09:02 | 17.15 | 11.94 | 0.376744E+09 | 599.32 | 17-JUN-14:09 | 18.98 | 10.18 |
July | 0.460011E+10 | 19308.97 | 27-JUL-08:62 | 14.68 | 10.38 | 0.383621E+09 | 599.32 | 01-JUL-14:00 | 24.40 | 16.22 |
August | 0.446314E+10 | 19544.95 | 26-AUG-08:62 | 16.28 | 9.48 | 0.392614E+09 | 599.32 | 19-AUG-14:09 | 21.28 | 11.33 |
September | 0.307583E+10 | 18976.17 | 09-SEP-08:62 | 17.15 | 9.14 | 0.360241E+09 | 599.33 | 09-SEP-14:09 | 27.70 | 13.65 |
October | 0.168681E+10 | 7836.93 | 19-OCT-08:62 | 14.37 | 6.91 | 0.340458E+09 | 599.32 | 21-OCT-14:00 | 16.10 | 8.09 |
November | 0.635745E+09 | 7053.87 | 26-NOV-10:04 | -15.1 | -15.9 | 0.287617E+09 | 599.32 | 04-NOV-14:00 | 16.70 | 7.95 |
December | 87857072.86 | 6523.84 | 14-DEC-09:04 | -12.3 | -12.4 | 0.289351E+09 | 453.41 | 02-DEC-15:09 | 6.65 | 2.69 |
Annual Sum or Average | 0.200771E+11 | 0.393318E+10 | ||||||||
Minimum of Months | 24202298.38 | 4445.76 | -15.1 | -15.9 | 0.267462E+09 | 453.41 | 6.65 | 2.69 | ||
Maximum of Months | 0.460011E+10 | 19544.95 | 20.10 | 12.38 | 0.392614E+09 | 599.33 | 27.70 | 16.22 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 23613162.29 | 5905.15 | 05-JAN-09:04 | -9.3 | -9.4 | 0.288833E+09 | 453.41 | 14-JAN-15:30 | 10.30 | 4.85 |
February | 0.192680E+09 | 5375.19 | 23-FEB-09:04 | -6.7 | -7.4 | 0.267144E+09 | 528.83 | 25-FEB-15:00 | 15.00 | 5.18 |
March | 0.346436E+09 | 6735.37 | 03-MAR-09:04 | -13.4 | -14.2 | 0.298830E+09 | 473.13 | 18-MAR-14:00 | 12.20 | 4.15 |
April | 0.578889E+09 | 4250.69 | 30-APR-09:04 | -2.3 | -3.7 | 0.305138E+09 | 536.68 | 01-APR-14:00 | 18.30 | 6.98 |
May | 0.115788E+10 | 10404.66 | 20-MAY-08:62 | 20.10 | 12.38 | 0.340155E+09 | 599.32 | 27-MAY-14:00 | 23.30 | 12.28 |
June | 0.299332E+10 | 17816.29 | 25-JUN-09:02 | 17.15 | 11.94 | 0.376527E+09 | 599.32 | 17-JUN-14:09 | 18.98 | 10.18 |
July | 0.451977E+10 | 19100.64 | 27-JUL-08:62 | 14.68 | 10.38 | 0.383588E+09 | 599.32 | 01-JUL-14:00 | 24.40 | 16.22 |
August | 0.438424E+10 | 19333.00 | 26-AUG-08:62 | 16.28 | 9.48 | 0.392543E+09 | 599.32 | 19-AUG-14:09 | 21.28 | 11.33 |
September | 0.301503E+10 | 18705.03 | 09-SEP-08:62 | 17.15 | 9.14 | 0.359922E+09 | 599.33 | 09-SEP-14:09 | 27.70 | 13.65 |
October | 0.164392E+10 | 7050.75 | 19-OCT-08:62 | 14.37 | 6.91 | 0.339705E+09 | 599.32 | 21-OCT-14:00 | 16.10 | 8.09 |
November | 0.603224E+09 | 5505.74 | 26-NOV-10:04 | -15.1 | -15.9 | 0.287039E+09 | 599.33 | 04-NOV-14:00 | 16.70 | 7.95 |
December | 72003693.84 | 6502.91 | 14-DEC-09:04 | -12.3 | -12.4 | 0.289360E+09 | 453.41 | 02-DEC-15:09 | 6.65 | 2.69 |
Annual Sum or Average | 0.195310E+11 | 0.392878E+10 | ||||||||
Minimum of Months | 23613162.29 | 4250.69 | -15.1 | -15.9 | 0.267144E+09 | 453.41 | 6.65 | 2.69 | ||
Maximum of Months | 0.451977E+10 | 19333.00 | 20.10 | 12.38 | 0.392543E+09 | 599.33 | 27.70 | 16.22 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 11954592.03 | 5851.46 | 05-JAN-09:04 | -9.3 | -9.4 | 0.288828E+09 | 453.41 | 14-JAN-15:09 | 10.50 | 5.05 |
February | 0.140506E+09 | 5356.56 | 23-FEB-09:04 | -6.7 | -7.4 | 0.266165E+09 | 515.60 | 25-FEB-15:00 | 15.00 | 5.18 |
March | 0.233057E+09 | 4708.27 | 07-MAR-09:04 | -4.0 | -5.7 | 0.298330E+09 | 462.72 | 18-MAR-14:00 | 12.20 | 4.15 |
April | 0.430179E+09 | 4506.09 | 30-APR-09:04 | -2.3 | -3.7 | 0.301622E+09 | 531.90 | 06-APR-16:10 | 22.02 | 10.90 |
May | 0.950628E+09 | 5253.47 | 20-MAY-08:62 | 20.10 | 12.38 | 0.337147E+09 | 599.32 | 27-MAY-14:00 | 23.30 | 12.28 |
June | 0.272281E+10 | 17445.95 | 25-JUN-09:02 | 17.15 | 11.94 | 0.375416E+09 | 599.32 | 17-JUN-14:09 | 18.98 | 10.18 |
July | 0.432157E+10 | 18760.34 | 27-JUL-08:62 | 14.68 | 10.38 | 0.383445E+09 | 599.32 | 01-JUL-14:00 | 24.40 | 16.22 |
August | 0.418225E+10 | 18973.31 | 26-AUG-08:62 | 16.28 | 9.48 | 0.392195E+09 | 599.32 | 19-AUG-14:09 | 21.28 | 11.33 |
September | 0.281484E+10 | 18131.02 | 08-SEP-08:62 | 14.60 | 9.19 | 0.358479E+09 | 599.33 | 09-SEP-14:09 | 27.70 | 13.65 |
October | 0.145359E+10 | 4642.45 | 10-OCT-08:04 | -3.7 | -4.5 | 0.336155E+09 | 599.32 | 21-OCT-14:00 | 16.10 | 8.09 |
November | 0.483318E+09 | 5264.39 | 11-NOV-10:03 | -6.7 | -7.8 | 0.285120E+09 | 597.95 | 04-NOV-14:00 | 16.70 | 7.95 |
December | 44672924.17 | 5975.56 | 12-DEC-09:04 | -9.8 | -10.5 | 0.289335E+09 | 453.41 | 09-DEC-15:00 | 10.60 | 3.83 |
Annual Sum or Average | 0.177894E+11 | 0.391224E+10 | ||||||||
Minimum of Months | 11954592.03 | 4506.09 | -9.8 | -10.5 | 0.266165E+09 | 453.41 | 10.50 | 3.83 | ||
Maximum of Months | 0.432157E+10 | 18973.31 | 20.10 | 12.38 | 0.392195E+09 | 599.33 | 27.70 | 16.22 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 4971262.17 | 3979.68 | 21-JAN-09:04 | -1.0 | -3.5 | 0.288812E+09 | 453.41 | 14-JAN-15:09 | 10.50 | 5.05 |
February | 43418416.58 | 4634.69 | 22-FEB-09:04 | -4.0 | -5.5 | 0.264782E+09 | 488.82 | 25-FEB-15:00 | 15.00 | 5.18 |
March | 32795088.10 | 4624.54 | 25-MAR-08:04 | -3.8 | -5.0 | 0.297907E+09 | 453.41 | 18-MAR-14:09 | 11.78 | 3.96 |
April | 0.129687E+09 | 4480.15 | 28-APR-08:04 | -2.7 | -4.0 | 0.296238E+09 | 531.91 | 07-APR-16:10 | 21.10 | 8.75 |
May | 0.544047E+09 | 4119.24 | 07-MAY-09:04 | -1.1 | -1.6 | 0.331814E+09 | 599.32 | 27-MAY-14:00 | 23.30 | 12.28 |
June | 0.228219E+10 | 16984.69 | 25-JUN-09:02 | 17.15 | 11.94 | 0.372128E+09 | 599.33 | 17-JUN-14:00 | 19.40 | 10.22 |
July | 0.416625E+10 | 18211.04 | 27-JUL-08:62 | 14.68 | 10.38 | 0.382973E+09 | 599.33 | 01-JUL-14:00 | 24.40 | 16.22 |
August | 0.396436E+10 | 19569.82 | 13-AUG-09:01 | 17.98 | 10.96 | 0.391208E+09 | 599.32 | 19-AUG-14:09 | 21.28 | 11.33 |
September | 0.246498E+10 | 19194.35 | 05-SEP-08:61 | 19.03 | 12.19 | 0.355575E+09 | 599.33 | 09-SEP-14:09 | 27.70 | 13.65 |
October | 0.102120E+10 | 4684.21 | 10-OCT-08:04 | -3.7 | -4.5 | 0.329726E+09 | 599.32 | 28-OCT-14:09 | 19.08 | 9.41 |
November | 0.209047E+09 | 5323.04 | 12-NOV-10:04 | -6.6 | -7.9 | 0.282343E+09 | 577.66 | 04-NOV-14:00 | 16.70 | 7.95 |
December | 8278533.65 | 5244.34 | 22-DEC-09:04 | -6.7 | -7.1 | 0.289305E+09 | 453.41 | 09-DEC-15:09 | 8.27 | 3.16 |
Annual Sum or Average | 0.148712E+11 | 0.388281E+10 | ||||||||
Minimum of Months | 4971262.17 | 3979.68 | -6.7 | -7.9 | 0.264782E+09 | 453.41 | 8.27 | 3.16 | ||
Maximum of Months | 0.416625E+10 | 19569.82 | 19.03 | 12.19 | 0.391208E+09 | 599.33 | 27.70 | 16.22 |
Report: ZoneHeatingSummaryMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.861836E+10 | 60250.56 | 27-JAN-08:61 | -27.2 |
February | 0.401013E+10 | 59946.54 | 10-FEB-08:61 | -18.8 |
March | 0.264808E+10 | 60090.18 | 06-MAR-08:61 | -16.9 |
April | 0.787735E+09 | 55053.85 | 01-APR-08:61 | 8.30 |
May | 0.450146E+09 | 52467.34 | 09-MAY-08:61 | 2.07 |
June | 75148044.53 | 930.27 | 25-JUN-07:03 | 14.18 |
July | 70554689.74 | 2095.21 | 18-JUL-08:05 | 26.57 |
August | 75626335.76 | 1800.51 | 07-AUG-08:05 | 25.97 |
September | 78406167.73 | 13458.89 | 20-SEP-08:62 | 7.07 |
October | 0.153782E+09 | 49802.81 | 10-OCT-08:61 | -3.7 |
November | 0.139424E+10 | 52085.87 | 30-NOV-09:01 | 1.10 |
December | 0.488101E+10 | 60103.60 | 31-DEC-08:61 | -27.6 |
Annual Sum or Average | 0.232432E+11 | |||
Minimum of Months | 70554689.74 | 930.27 | -27.6 | |
Maximum of Months | 0.861836E+10 | 60250.56 | 26.57 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.327102E+10 | 31702.33 | 27-JAN-08:61 | -27.2 |
February | 0.137559E+10 | 31460.64 | 05-FEB-08:61 | -20.1 |
March | 0.802075E+09 | 31674.02 | 06-MAR-08:61 | -16.9 |
April | 0.207778E+09 | 18347.95 | 29-APR-08:61 | -1.8 |
May | 0.157770E+09 | 13023.94 | 08-MAY-08:61 | -1.6 |
June | 0.101199E+09 | 1476.44 | 25-JUN-07:03 | 14.18 |
July | 98247948.73 | 1989.38 | 18-JUL-08:05 | 26.57 |
August | 0.105725E+09 | 1863.53 | 07-AUG-08:05 | 25.97 |
September | 0.100591E+09 | 1780.09 | 04-SEP-07:04 | 20.02 |
October | 0.114166E+09 | 2651.43 | 10-OCT-08:02 | -3.7 |
November | 0.496603E+09 | 26445.00 | 28-NOV-09:01 | -4.2 |
December | 0.177071E+10 | 31689.61 | 31-DEC-08:61 | -27.6 |
Annual Sum or Average | 0.860148E+10 | |||
Minimum of Months | 98247948.73 | 1476.44 | -27.6 | |
Maximum of Months | 0.327102E+10 | 31702.33 | 26.57 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.376835E+10 | 31546.31 | 08-JAN-08:61 | -27.2 |
February | 0.170760E+10 | 31411.26 | 05-FEB-08:61 | -20.1 |
March | 0.104613E+10 | 31336.58 | 06-MAR-07:01 | -19.7 |
April | 0.266982E+09 | 22846.51 | 30-APR-08:61 | -2.8 |
May | 0.237576E+09 | 25325.38 | 08-MAY-07:01 | -2.1 |
June | 0.137983E+09 | 1546.07 | 24-JUN-17:12 | 27.23 |
July | 0.189035E+09 | 2760.51 | 17-JUL-19:02 | 33.48 |
August | 0.171198E+09 | 3142.07 | 06-AUG-16:02 | 35.50 |
September | 0.139155E+09 | 2847.54 | 02-SEP-17:02 | 34.03 |
October | 0.139747E+09 | 3669.26 | 10-OCT-07:02 | -5.7 |
November | 0.679819E+09 | 26849.47 | 29-NOV-08:61 | -1.1 |
December | 0.219176E+10 | 31635.59 | 31-DEC-08:61 | -27.6 |
Annual Sum or Average | 0.106753E+11 | |||
Minimum of Months | 0.137983E+09 | 1546.07 | -27.6 | |
Maximum of Months | 0.376835E+10 | 31635.59 | 35.50 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.399635E+10 | 31623.59 | 08-JAN-08:61 | -27.2 |
February | 0.184912E+10 | 31487.90 | 05-FEB-08:61 | -20.1 |
March | 0.115904E+10 | 31413.72 | 06-MAR-07:01 | -19.7 |
April | 0.299089E+09 | 26682.02 | 30-APR-08:61 | -2.8 |
May | 0.266669E+09 | 26978.16 | 08-MAY-07:01 | -2.1 |
June | 0.138597E+09 | 1550.60 | 24-JUN-17:12 | 27.23 |
July | 0.188225E+09 | 2760.50 | 17-JUL-19:02 | 33.48 |
August | 0.170242E+09 | 3142.39 | 06-AUG-16:02 | 35.50 |
September | 0.138445E+09 | 2849.31 | 02-SEP-17:02 | 34.03 |
October | 0.154142E+09 | 9409.42 | 10-OCT-07:02 | -5.7 |
November | 0.765789E+09 | 26980.51 | 29-NOV-08:61 | -1.1 |
December | 0.236825E+10 | 31713.65 | 31-DEC-08:61 | -27.6 |
Annual Sum or Average | 0.114940E+11 | |||
Minimum of Months | 0.138445E+09 | 1550.60 | -27.6 | |
Maximum of Months | 0.399635E+10 | 31713.65 | 35.50 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.433165E+10 | 31494.06 | 08-JAN-08:61 | -27.2 |
February | 0.205953E+10 | 31359.76 | 05-FEB-08:61 | -20.1 |
March | 0.134457E+10 | 31286.61 | 06-MAR-07:01 | -19.7 |
April | 0.369268E+09 | 26608.79 | 30-APR-08:61 | -2.8 |
May | 0.313246E+09 | 27192.81 | 09-MAY-07:01 | 0.78 |
June | 0.138742E+09 | 1549.30 | 24-JUN-17:12 | 27.23 |
July | 0.189964E+09 | 2761.49 | 17-JUL-19:02 | 33.48 |
August | 0.171454E+09 | 3144.13 | 06-AUG-16:02 | 35.50 |
September | 0.139219E+09 | 2852.03 | 02-SEP-17:02 | 34.03 |
October | 0.169302E+09 | 14145.91 | 10-OCT-07:02 | -5.7 |
November | 0.879199E+09 | 26913.55 | 29-NOV-08:61 | -1.1 |
December | 0.263000E+10 | 31583.04 | 31-DEC-08:61 | -27.6 |
Annual Sum or Average | 0.127361E+11 | |||
Minimum of Months | 0.138742E+09 | 1549.30 | -27.6 | |
Maximum of Months | 0.433165E+10 | 31583.04 | 35.50 |
Report: ZoneHeatingSummaryMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.853302E+10 | 59291.23 | 08-JAN-09:01 | -27.1 |
February | 0.405465E+10 | 59022.88 | 10-FEB-08:61 | -18.8 |
March | 0.263511E+10 | 59174.57 | 06-MAR-08:61 | -16.9 |
April | 0.773940E+09 | 54124.45 | 01-APR-08:61 | 8.30 |
May | 0.520370E+09 | 54185.88 | 02-MAY-08:61 | 12.15 |
June | 85058740.95 | 1946.15 | 24-JUN-17:03 | 27.52 |
July | 0.123779E+09 | 4263.12 | 16-JUL-16:02 | 32.88 |
August | 0.116610E+09 | 5319.79 | 06-AUG-16:02 | 35.50 |
September | 0.120298E+09 | 15089.91 | 20-SEP-08:62 | 7.07 |
October | 0.223413E+09 | 51229.52 | 11-OCT-08:61 | 2.57 |
November | 0.176067E+10 | 58754.64 | 27-NOV-08:61 | -12.7 |
December | 0.521840E+10 | 58949.74 | 18-DEC-08:61 | -3.1 |
Annual Sum or Average | 0.241653E+11 | |||
Minimum of Months | 85058740.95 | 1946.15 | -27.1 | |
Maximum of Months | 0.853302E+10 | 59291.23 | 35.50 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.475291E+10 | 29894.89 | 08-JAN-09:01 | -27.1 |
February | 0.232530E+10 | 29755.07 | 10-FEB-08:61 | -18.8 |
March | 0.157752E+10 | 29834.55 | 06-MAR-08:61 | -16.9 |
April | 0.509999E+09 | 27222.25 | 01-APR-08:61 | 8.30 |
May | 0.372876E+09 | 25996.92 | 09-MAY-08:61 | 2.07 |
June | 0.118692E+09 | 1507.72 | 24-JUN-17:12 | 27.23 |
July | 0.147964E+09 | 2622.30 | 16-JUL-16:02 | 32.88 |
August | 0.135689E+09 | 3131.06 | 06-AUG-16:02 | 35.50 |
September | 0.133928E+09 | 2845.14 | 02-SEP-17:02 | 34.03 |
October | 0.191577E+09 | 24753.24 | 10-OCT-08:61 | -3.7 |
November | 0.105078E+10 | 29616.06 | 27-NOV-08:61 | -12.7 |
December | 0.298260E+10 | 29716.23 | 18-DEC-08:61 | -3.1 |
Annual Sum or Average | 0.142998E+11 | |||
Minimum of Months | 0.118692E+09 | 1507.72 | -27.1 | |
Maximum of Months | 0.475291E+10 | 29894.89 | 35.50 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.483934E+10 | 29671.39 | 08-JAN-09:01 | -27.1 |
February | 0.239346E+10 | 29555.13 | 10-FEB-08:61 | -18.8 |
March | 0.164865E+10 | 29634.39 | 06-MAR-08:61 | -16.9 |
April | 0.551702E+09 | 27049.28 | 01-APR-08:61 | 8.30 |
May | 0.396901E+09 | 25821.33 | 09-MAY-08:61 | 2.07 |
June | 0.117869E+09 | 1501.98 | 24-JUN-17:12 | 27.23 |
July | 0.147353E+09 | 2619.90 | 16-JUL-16:02 | 32.88 |
August | 0.135086E+09 | 3129.06 | 06-AUG-16:02 | 35.50 |
September | 0.132997E+09 | 2843.35 | 02-SEP-17:02 | 34.03 |
October | 0.199567E+09 | 24575.99 | 10-OCT-08:61 | -3.7 |
November | 0.109307E+10 | 29418.20 | 27-NOV-08:61 | -12.7 |
December | 0.305924E+10 | 29516.88 | 18-DEC-08:61 | -3.1 |
Annual Sum or Average | 0.147152E+11 | |||
Minimum of Months | 0.117869E+09 | 1501.98 | -27.1 | |
Maximum of Months | 0.483934E+10 | 29671.39 | 35.50 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.527711E+10 | 29946.64 | 09-JAN-08:61 | -27.1 |
February | 0.271303E+10 | 29807.94 | 10-FEB-08:61 | -18.8 |
March | 0.196743E+10 | 29886.10 | 06-MAR-08:61 | -16.9 |
April | 0.737540E+09 | 27401.89 | 01-APR-08:61 | 8.30 |
May | 0.505628E+09 | 28032.22 | 08-MAY-07:01 | -2.1 |
June | 0.117245E+09 | 1497.30 | 24-JUN-17:12 | 27.23 |
July | 0.146987E+09 | 2618.41 | 16-JUL-16:02 | 32.88 |
August | 0.135074E+09 | 3128.07 | 06-AUG-16:02 | 35.50 |
September | 0.136380E+09 | 7328.05 | 20-SEP-08:62 | 7.07 |
October | 0.231018E+09 | 25930.26 | 11-OCT-08:61 | 2.57 |
November | 0.127927E+10 | 29670.98 | 27-NOV-08:61 | -12.7 |
December | 0.343921E+10 | 29774.15 | 23-DEC-08:61 | -9.2 |
Annual Sum or Average | 0.166859E+11 | |||
Minimum of Months | 0.117245E+09 | 1497.30 | -27.1 | |
Maximum of Months | 0.527711E+10 | 29946.64 | 35.50 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.820816E+10 | 31701.23 | 28-JAN-08:61 | -25.1 |
February | 0.455380E+10 | 31530.54 | 03-FEB-08:61 | -17.1 |
March | 0.375422E+10 | 31609.51 | 06-MAR-08:61 | -16.9 |
April | 0.169310E+10 | 31325.19 | 30-APR-08:61 | -2.8 |
May | 0.102368E+10 | 31464.09 | 08-MAY-07:01 | -2.1 |
June | 0.140132E+09 | 2896.69 | 17-JUN-08:65 | 11.47 |
July | 0.156555E+09 | 2671.69 | 16-JUL-16:02 | 32.88 |
August | 0.143429E+09 | 3166.95 | 06-AUG-16:02 | 35.50 |
September | 0.204652E+09 | 23340.26 | 20-SEP-08:62 | 7.07 |
October | 0.420782E+09 | 27833.46 | 11-OCT-08:61 | 2.57 |
November | 0.219154E+10 | 31415.41 | 27-NOV-08:61 | -12.7 |
December | 0.545636E+10 | 31617.15 | 31-DEC-09:01 | -26.2 |
Annual Sum or Average | 0.279464E+11 | |||
Minimum of Months | 0.140132E+09 | 2671.69 | -26.2 | |
Maximum of Months | 0.820816E+10 | 31701.23 | 35.50 |
Report: ZoneElectricSummaryMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.100203E+11 | 6078.71 | 01-JAN-10:09 | 0.223514E+10 | 1348.26 | 01-JAN-10:09 |
February | 0.906661E+10 | 6078.71 | 01-FEB-10:09 | 0.202238E+10 | 1348.26 | 01-FEB-10:09 |
March | 0.100410E+11 | 6078.71 | 01-MAR-10:09 | 0.223972E+10 | 1348.26 | 01-MAR-10:09 |
April | 0.972311E+10 | 6078.71 | 01-APR-09:09 | 0.216880E+10 | 1348.26 | 01-APR-09:09 |
May | 0.100203E+11 | 6078.71 | 01-MAY-09:09 | 0.223514E+10 | 1348.26 | 01-MAY-09:09 |
June | 0.972311E+10 | 6078.71 | 01-JUN-09:09 | 0.216880E+10 | 1348.26 | 01-JUN-09:09 |
July | 0.100410E+11 | 6078.71 | 01-JUL-09:09 | 0.223972E+10 | 1348.26 | 01-JUL-09:09 |
August | 0.100203E+11 | 6078.71 | 01-AUG-09:09 | 0.223514E+10 | 1348.26 | 01-AUG-09:09 |
September | 0.974384E+10 | 6078.71 | 01-SEP-09:09 | 0.217339E+10 | 1348.26 | 01-SEP-09:09 |
October | 0.100203E+11 | 6078.71 | 01-OCT-09:09 | 0.223514E+10 | 1348.26 | 01-OCT-09:09 |
November | 0.968165E+10 | 6078.71 | 01-NOV-09:09 | 0.215964E+10 | 1348.26 | 01-NOV-09:09 |
December | 0.100617E+11 | 6078.71 | 01-DEC-10:09 | 0.224431E+10 | 1348.26 | 01-DEC-10:09 |
Annual Sum or Average | 0.118163E+12 | 0.263573E+11 | ||||
Minimum of Months | 0.906661E+10 | 6078.71 | 0.202238E+10 | 1348.26 | ||
Maximum of Months | 0.100617E+11 | 6078.71 | 0.224431E+10 | 1348.26 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.540359E+10 | 3278.04 | 01-JAN-10:09 | 0.111757E+10 | 674.13 | 01-JAN-10:09 |
February | 0.488932E+10 | 3278.04 | 01-FEB-10:09 | 0.101119E+10 | 674.13 | 01-FEB-10:09 |
March | 0.541477E+10 | 3278.04 | 01-MAR-10:09 | 0.111986E+10 | 674.13 | 01-MAR-10:09 |
April | 0.524335E+10 | 3278.04 | 01-APR-09:09 | 0.108440E+10 | 674.13 | 01-APR-09:09 |
May | 0.540359E+10 | 3278.04 | 01-MAY-09:09 | 0.111757E+10 | 674.13 | 01-MAY-09:09 |
June | 0.524335E+10 | 3278.04 | 01-JUN-09:09 | 0.108440E+10 | 674.13 | 01-JUN-09:09 |
July | 0.541477E+10 | 3278.04 | 01-JUL-09:09 | 0.111986E+10 | 674.13 | 01-JUL-09:09 |
August | 0.540359E+10 | 3278.04 | 01-AUG-09:09 | 0.111757E+10 | 674.13 | 01-AUG-09:09 |
September | 0.525453E+10 | 3278.04 | 01-SEP-09:09 | 0.108669E+10 | 674.13 | 01-SEP-09:09 |
October | 0.540359E+10 | 3278.04 | 01-OCT-09:09 | 0.111757E+10 | 674.13 | 01-OCT-09:09 |
November | 0.522099E+10 | 3278.04 | 01-NOV-09:09 | 0.107982E+10 | 674.13 | 01-NOV-09:09 |
December | 0.542595E+10 | 3278.04 | 01-DEC-10:09 | 0.112215E+10 | 674.13 | 01-DEC-10:09 |
Annual Sum or Average | 0.637214E+11 | 0.131787E+11 | ||||
Minimum of Months | 0.488932E+10 | 3278.04 | 0.101119E+10 | 674.13 | ||
Maximum of Months | 0.542595E+10 | 3278.04 | 0.112215E+10 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.379993E+10 | 2921.79 | 01-JAN-10:09 | 0.883781E+09 | 674.13 | 01-JAN-10:09 |
February | 0.344119E+10 | 2921.79 | 01-FEB-09:09 | 0.800324E+09 | 674.13 | 01-FEB-09:09 |
March | 0.387965E+10 | 2921.79 | 01-MAR-09:09 | 0.902118E+09 | 674.13 | 01-MAR-09:09 |
April | 0.368699E+10 | 2921.79 | 01-APR-08:09 | 0.857490E+09 | 674.13 | 01-APR-08:09 |
May | 0.383979E+10 | 2921.79 | 01-MAY-08:09 | 0.892950E+09 | 674.13 | 01-MAY-08:09 |
June | 0.374678E+10 | 2921.79 | 01-JUN-08:09 | 0.871243E+09 | 674.13 | 01-JUN-08:09 |
July | 0.378000E+10 | 2921.79 | 01-JUL-08:09 | 0.879197E+09 | 674.13 | 01-JUL-08:09 |
August | 0.387965E+10 | 2921.79 | 01-AUG-08:09 | 0.902118E+09 | 674.13 | 01-AUG-08:09 |
September | 0.368699E+10 | 2921.79 | 01-SEP-08:09 | 0.857490E+09 | 674.13 | 01-SEP-08:09 |
October | 0.379993E+10 | 2921.79 | 01-OCT-09:09 | 0.883781E+09 | 674.13 | 01-OCT-09:09 |
November | 0.368699E+10 | 2921.79 | 01-NOV-08:09 | 0.857490E+09 | 674.13 | 01-NOV-08:09 |
December | 0.378000E+10 | 2921.79 | 01-DEC-09:09 | 0.879197E+09 | 674.13 | 01-DEC-09:09 |
Annual Sum or Average | 0.450079E+11 | 0.104672E+11 | ||||
Minimum of Months | 0.344119E+10 | 2921.79 | 0.800324E+09 | 674.13 | ||
Maximum of Months | 0.387965E+10 | 2921.79 | 0.902118E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.379993E+10 | 2921.79 | 01-JAN-10:09 | 0.883781E+09 | 674.13 | 01-JAN-10:09 |
February | 0.344119E+10 | 2921.79 | 01-FEB-09:09 | 0.800324E+09 | 674.13 | 01-FEB-09:09 |
March | 0.387965E+10 | 2921.79 | 01-MAR-09:09 | 0.902118E+09 | 674.13 | 01-MAR-09:09 |
April | 0.368699E+10 | 2921.79 | 01-APR-08:09 | 0.857490E+09 | 674.13 | 01-APR-08:09 |
May | 0.383979E+10 | 2921.79 | 01-MAY-08:09 | 0.892950E+09 | 674.13 | 01-MAY-08:09 |
June | 0.374678E+10 | 2921.79 | 01-JUN-08:09 | 0.871243E+09 | 674.13 | 01-JUN-08:09 |
July | 0.378000E+10 | 2921.79 | 01-JUL-08:09 | 0.879197E+09 | 674.13 | 01-JUL-08:09 |
August | 0.387965E+10 | 2921.79 | 01-AUG-08:09 | 0.902118E+09 | 674.13 | 01-AUG-08:09 |
September | 0.368699E+10 | 2921.79 | 01-SEP-08:09 | 0.857490E+09 | 674.13 | 01-SEP-08:09 |
October | 0.379993E+10 | 2921.79 | 01-OCT-09:09 | 0.883781E+09 | 674.13 | 01-OCT-09:09 |
November | 0.368699E+10 | 2921.79 | 01-NOV-08:09 | 0.857490E+09 | 674.13 | 01-NOV-08:09 |
December | 0.378000E+10 | 2921.79 | 01-DEC-09:09 | 0.879197E+09 | 674.13 | 01-DEC-09:09 |
Annual Sum or Average | 0.450079E+11 | 0.104672E+11 | ||||
Minimum of Months | 0.344119E+10 | 2921.79 | 0.800324E+09 | 674.13 | ||
Maximum of Months | 0.387965E+10 | 2921.79 | 0.902118E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.379993E+10 | 2921.79 | 01-JAN-10:09 | 0.883781E+09 | 674.13 | 01-JAN-10:09 |
February | 0.344119E+10 | 2921.79 | 01-FEB-09:09 | 0.800324E+09 | 674.13 | 01-FEB-09:09 |
March | 0.387965E+10 | 2921.79 | 01-MAR-09:09 | 0.902118E+09 | 674.13 | 01-MAR-09:09 |
April | 0.368699E+10 | 2921.79 | 01-APR-08:09 | 0.857490E+09 | 674.13 | 01-APR-08:09 |
May | 0.383979E+10 | 2921.79 | 01-MAY-08:09 | 0.892950E+09 | 674.13 | 01-MAY-08:09 |
June | 0.374678E+10 | 2921.79 | 01-JUN-08:09 | 0.871243E+09 | 674.13 | 01-JUN-08:09 |
July | 0.378000E+10 | 2921.79 | 01-JUL-08:09 | 0.879197E+09 | 674.13 | 01-JUL-08:09 |
August | 0.387965E+10 | 2921.79 | 01-AUG-08:09 | 0.902118E+09 | 674.13 | 01-AUG-08:09 |
September | 0.368699E+10 | 2921.79 | 01-SEP-08:09 | 0.857490E+09 | 674.13 | 01-SEP-08:09 |
October | 0.379993E+10 | 2921.79 | 01-OCT-09:09 | 0.883781E+09 | 674.13 | 01-OCT-09:09 |
November | 0.368699E+10 | 2921.79 | 01-NOV-08:09 | 0.857490E+09 | 674.13 | 01-NOV-08:09 |
December | 0.378000E+10 | 2921.79 | 01-DEC-09:09 | 0.879197E+09 | 674.13 | 01-DEC-09:09 |
Annual Sum or Average | 0.450079E+11 | 0.104672E+11 | ||||
Minimum of Months | 0.344119E+10 | 2921.79 | 0.800324E+09 | 674.13 | ||
Maximum of Months | 0.387965E+10 | 2921.79 | 0.902118E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.520705E+10 | 4358.02 | 01-JAN-11:09 | 0.162546E+10 | 1348.26 | 01-JAN-11:09 |
February | 0.471657E+10 | 4358.02 | 01-FEB-10:09 | 0.147229E+10 | 1348.26 | 01-FEB-10:09 |
March | 0.532596E+10 | 4358.02 | 01-MAR-10:09 | 0.166213E+10 | 1348.26 | 01-MAR-10:09 |
April | 0.505346E+10 | 4358.02 | 01-APR-09:09 | 0.157746E+10 | 1348.26 | 01-APR-09:09 |
May | 0.526650E+10 | 4358.02 | 01-MAY-09:09 | 0.164379E+10 | 1348.26 | 01-MAY-09:09 |
June | 0.514264E+10 | 4358.02 | 01-JUN-09:09 | 0.160496E+10 | 1348.26 | 01-JUN-09:09 |
July | 0.517732E+10 | 4358.02 | 01-JUL-09:09 | 0.161629E+10 | 1348.26 | 01-JUL-09:09 |
August | 0.532596E+10 | 4358.02 | 01-AUG-09:09 | 0.166213E+10 | 1348.26 | 01-AUG-09:09 |
September | 0.505346E+10 | 4358.02 | 01-SEP-09:09 | 0.157746E+10 | 1348.26 | 01-SEP-09:09 |
October | 0.520705E+10 | 4358.02 | 01-OCT-10:09 | 0.162546E+10 | 1348.26 | 01-OCT-10:09 |
November | 0.505346E+10 | 4358.02 | 01-NOV-09:09 | 0.157746E+10 | 1348.26 | 01-NOV-09:09 |
December | 0.517732E+10 | 4358.02 | 01-DEC-10:09 | 0.161629E+10 | 1348.26 | 01-DEC-10:09 |
Annual Sum or Average | 0.617068E+11 | 0.192612E+11 | ||||
Minimum of Months | 0.471657E+10 | 4358.02 | 0.147229E+10 | 1348.26 | ||
Maximum of Months | 0.532596E+10 | 4358.02 | 0.166213E+10 | 1348.26 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.260353E+10 | 2179.01 | 01-JAN-11:09 | 0.812728E+09 | 674.13 | 01-JAN-11:09 |
February | 0.235828E+10 | 2179.01 | 01-FEB-10:09 | 0.736147E+09 | 674.13 | 01-FEB-10:09 |
March | 0.266298E+10 | 2179.01 | 01-MAR-10:09 | 0.831065E+09 | 674.13 | 01-MAR-10:09 |
April | 0.252673E+10 | 2179.01 | 01-APR-09:09 | 0.788729E+09 | 674.13 | 01-APR-09:09 |
May | 0.263325E+10 | 2179.01 | 01-MAY-09:09 | 0.821897E+09 | 674.13 | 01-MAY-09:09 |
June | 0.257132E+10 | 2179.01 | 01-JUN-09:09 | 0.802482E+09 | 674.13 | 01-JUN-09:09 |
July | 0.258866E+10 | 2179.01 | 01-JUL-09:09 | 0.808144E+09 | 674.13 | 01-JUL-09:09 |
August | 0.266298E+10 | 2179.01 | 01-AUG-09:09 | 0.831065E+09 | 674.13 | 01-AUG-09:09 |
September | 0.252673E+10 | 2179.01 | 01-SEP-09:09 | 0.788729E+09 | 674.13 | 01-SEP-09:09 |
October | 0.260353E+10 | 2179.01 | 01-OCT-10:09 | 0.812728E+09 | 674.13 | 01-OCT-10:09 |
November | 0.252673E+10 | 2179.01 | 01-NOV-09:09 | 0.788729E+09 | 674.13 | 01-NOV-09:09 |
December | 0.258866E+10 | 2179.01 | 01-DEC-10:09 | 0.808144E+09 | 674.13 | 01-DEC-10:09 |
Annual Sum or Average | 0.308534E+11 | 0.963059E+10 | ||||
Minimum of Months | 0.235828E+10 | 2179.01 | 0.736147E+09 | 674.13 | ||
Maximum of Months | 0.266298E+10 | 2179.01 | 0.831065E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.260353E+10 | 2179.01 | 01-JAN-11:09 | 0.812728E+09 | 674.13 | 01-JAN-11:09 |
February | 0.235828E+10 | 2179.01 | 01-FEB-10:09 | 0.736147E+09 | 674.13 | 01-FEB-10:09 |
March | 0.266298E+10 | 2179.01 | 01-MAR-10:09 | 0.831065E+09 | 674.13 | 01-MAR-10:09 |
April | 0.252673E+10 | 2179.01 | 01-APR-09:09 | 0.788729E+09 | 674.13 | 01-APR-09:09 |
May | 0.263325E+10 | 2179.01 | 01-MAY-09:09 | 0.821897E+09 | 674.13 | 01-MAY-09:09 |
June | 0.257132E+10 | 2179.01 | 01-JUN-09:09 | 0.802482E+09 | 674.13 | 01-JUN-09:09 |
July | 0.258866E+10 | 2179.01 | 01-JUL-09:09 | 0.808144E+09 | 674.13 | 01-JUL-09:09 |
August | 0.266298E+10 | 2179.01 | 01-AUG-09:09 | 0.831065E+09 | 674.13 | 01-AUG-09:09 |
September | 0.252673E+10 | 2179.01 | 01-SEP-09:09 | 0.788729E+09 | 674.13 | 01-SEP-09:09 |
October | 0.260353E+10 | 2179.01 | 01-OCT-10:09 | 0.812728E+09 | 674.13 | 01-OCT-10:09 |
November | 0.252673E+10 | 2179.01 | 01-NOV-09:09 | 0.788729E+09 | 674.13 | 01-NOV-09:09 |
December | 0.258866E+10 | 2179.01 | 01-DEC-10:09 | 0.808144E+09 | 674.13 | 01-DEC-10:09 |
Annual Sum or Average | 0.308534E+11 | 0.963059E+10 | ||||
Minimum of Months | 0.235828E+10 | 2179.01 | 0.736147E+09 | 674.13 | ||
Maximum of Months | 0.266298E+10 | 2179.01 | 0.831065E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.260353E+10 | 2179.01 | 01-JAN-11:09 | 0.812728E+09 | 674.13 | 01-JAN-11:09 |
February | 0.235828E+10 | 2179.01 | 01-FEB-10:09 | 0.736147E+09 | 674.13 | 01-FEB-10:09 |
March | 0.266298E+10 | 2179.01 | 01-MAR-10:09 | 0.831065E+09 | 674.13 | 01-MAR-10:09 |
April | 0.252673E+10 | 2179.01 | 01-APR-09:09 | 0.788729E+09 | 674.13 | 01-APR-09:09 |
May | 0.263325E+10 | 2179.01 | 01-MAY-09:09 | 0.821897E+09 | 674.13 | 01-MAY-09:09 |
June | 0.257132E+10 | 2179.01 | 01-JUN-09:09 | 0.802482E+09 | 674.13 | 01-JUN-09:09 |
July | 0.258866E+10 | 2179.01 | 01-JUL-09:09 | 0.808144E+09 | 674.13 | 01-JUL-09:09 |
August | 0.266298E+10 | 2179.01 | 01-AUG-09:09 | 0.831065E+09 | 674.13 | 01-AUG-09:09 |
September | 0.252673E+10 | 2179.01 | 01-SEP-09:09 | 0.788729E+09 | 674.13 | 01-SEP-09:09 |
October | 0.260353E+10 | 2179.01 | 01-OCT-10:09 | 0.812728E+09 | 674.13 | 01-OCT-10:09 |
November | 0.252673E+10 | 2179.01 | 01-NOV-09:09 | 0.788729E+09 | 674.13 | 01-NOV-09:09 |
December | 0.258866E+10 | 2179.01 | 01-DEC-10:09 | 0.808144E+09 | 674.13 | 01-DEC-10:09 |
Annual Sum or Average | 0.308534E+11 | 0.963059E+10 | ||||
Minimum of Months | 0.235828E+10 | 2179.01 | 0.736147E+09 | 674.13 | ||
Maximum of Months | 0.266298E+10 | 2179.01 | 0.831065E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.260353E+10 | 2179.01 | 01-JAN-11:09 | 0.812728E+09 | 674.13 | 01-JAN-11:09 |
February | 0.235828E+10 | 2179.01 | 01-FEB-10:09 | 0.736147E+09 | 674.13 | 01-FEB-10:09 |
March | 0.266298E+10 | 2179.01 | 01-MAR-10:09 | 0.831065E+09 | 674.13 | 01-MAR-10:09 |
April | 0.252673E+10 | 2179.01 | 01-APR-09:09 | 0.788729E+09 | 674.13 | 01-APR-09:09 |
May | 0.263325E+10 | 2179.01 | 01-MAY-09:09 | 0.821897E+09 | 674.13 | 01-MAY-09:09 |
June | 0.257132E+10 | 2179.01 | 01-JUN-09:09 | 0.802482E+09 | 674.13 | 01-JUN-09:09 |
July | 0.258866E+10 | 2179.01 | 01-JUL-09:09 | 0.808144E+09 | 674.13 | 01-JUL-09:09 |
August | 0.266298E+10 | 2179.01 | 01-AUG-09:09 | 0.831065E+09 | 674.13 | 01-AUG-09:09 |
September | 0.252673E+10 | 2179.01 | 01-SEP-09:09 | 0.788729E+09 | 674.13 | 01-SEP-09:09 |
October | 0.260353E+10 | 2179.01 | 01-OCT-10:09 | 0.812728E+09 | 674.13 | 01-OCT-10:09 |
November | 0.252673E+10 | 2179.01 | 01-NOV-09:09 | 0.788729E+09 | 674.13 | 01-NOV-09:09 |
December | 0.258866E+10 | 2179.01 | 01-DEC-10:09 | 0.808144E+09 | 674.13 | 01-DEC-10:09 |
Annual Sum or Average | 0.308534E+11 | 0.963059E+10 | ||||
Minimum of Months | 0.235828E+10 | 2179.01 | 0.736147E+09 | 674.13 | ||
Maximum of Months | 0.266298E+10 | 2179.01 | 0.831065E+09 | 674.13 |
Report: SpaceGainsMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.180574E+10 | 0.100203E+11 | 0.223514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.819380E+10 |
February | 0.163016E+10 | 0.906661E+10 | 0.202238E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.546248E+10 |
March | 0.178954E+10 | 0.100410E+11 | 0.223972E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.501905E+10 |
April | 0.174484E+10 | 0.972311E+10 | 0.216880E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.316031E+10 |
May | 0.179537E+10 | 0.100203E+11 | 0.223514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40074126.67 | 0.276882E+10 |
June | 0.173447E+10 | 0.972311E+10 | 0.216880E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.249767E+09 | 0.126778E+10 |
July | 0.181028E+10 | 0.100410E+11 | 0.223972E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.677131E+09 | 0.612558E+09 |
August | 0.178501E+10 | 0.100203E+11 | 0.223514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.518073E+09 | 0.884646E+09 |
September | 0.174937E+10 | 0.974384E+10 | 0.217339E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.237873E+09 | 0.184037E+10 |
October | 0.180574E+10 | 0.100203E+11 | 0.223514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2821187.57 | 0.307403E+10 |
November | 0.174613E+10 | 0.968165E+10 | 0.215964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.461795E+10 |
December | 0.181481E+10 | 0.100617E+11 | 0.224431E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.655836E+10 |
Annual Sum or Average | 0.212115E+11 | 0.118163E+12 | 0.263573E+11 | 0.172574E+10 | 0.434602E+11 | ||||
Minimum of Months | 0.163016E+10 | 0.906661E+10 | 0.202238E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.612558E+09 |
Maximum of Months | 0.181481E+10 | 0.100617E+11 | 0.224431E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.677131E+09 | 0.819380E+10 |
Report: SpaceGainsMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.902868E+09 | 0.540359E+10 | 0.111757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.400869E+10 |
February | 0.815075E+09 | 0.488932E+10 | 0.101119E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.266166E+10 |
March | 0.894769E+09 | 0.541477E+10 | 0.111986E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.245377E+10 |
April | 0.872416E+09 | 0.524335E+10 | 0.108440E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158394E+10 |
May | 0.897684E+09 | 0.540359E+10 | 0.111757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21453292.24 | 0.132664E+10 |
June | 0.867232E+09 | 0.524335E+10 | 0.108440E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134783E+09 | 0.563660E+09 |
July | 0.905135E+09 | 0.541477E+10 | 0.111986E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.365787E+09 | 0.244257E+09 |
August | 0.892501E+09 | 0.540359E+10 | 0.111757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.279189E+09 | 0.381115E+09 |
September | 0.874683E+09 | 0.525453E+10 | 0.108669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128212E+09 | 0.843836E+09 |
October | 0.902868E+09 | 0.540359E+10 | 0.111757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1515574.52 | 0.149447E+10 |
November | 0.873064E+09 | 0.522099E+10 | 0.107982E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.226014E+10 |
December | 0.907403E+09 | 0.542595E+10 | 0.112215E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.321374E+10 |
Annual Sum or Average | 0.106057E+11 | 0.637214E+11 | 0.131787E+11 | 0.930939E+09 | 0.210359E+11 | ||||
Minimum of Months | 0.815075E+09 | 0.488932E+10 | 0.101119E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.244257E+09 |
Maximum of Months | 0.907403E+09 | 0.542595E+10 | 0.112215E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.365787E+09 | 0.400869E+10 |
Report: SpaceGainsMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.537120E+09 | 0.379993E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.411280E+10 |
February | 0.487879E+09 | 0.344119E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.273910E+10 |
March | 0.551374E+09 | 0.387965E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.251808E+10 |
April | 0.524810E+09 | 0.368699E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162215E+10 |
May | 0.544247E+09 | 0.383979E+10 | 0.892950E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21302708.73 | 0.136555E+10 |
June | 0.532585E+09 | 0.374678E+10 | 0.871243E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133370E+09 | 0.596923E+09 |
July | 0.536472E+09 | 0.378000E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.357781E+09 | 0.273118E+09 |
August | 0.551374E+09 | 0.387965E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.275992E+09 | 0.407030E+09 |
September | 0.524810E+09 | 0.368699E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122466E+09 | 0.881089E+09 |
October | 0.537120E+09 | 0.379993E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1515544.00 | 0.153530E+10 |
November | 0.518979E+09 | 0.368699E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.231167E+10 |
December | 0.536472E+09 | 0.378000E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.330714E+10 |
Annual Sum or Average | 0.638324E+10 | 0.450079E+11 | 0.104672E+11 | 0.912427E+09 | 0.216700E+11 | ||||
Minimum of Months | 0.487879E+09 | 0.344119E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.273118E+09 |
Maximum of Months | 0.551374E+09 | 0.387965E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.357781E+09 | 0.411280E+10 |
Report: SpaceGainsMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.537120E+09 | 0.379993E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.410566E+10 |
February | 0.487879E+09 | 0.344119E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.272847E+10 |
March | 0.551374E+09 | 0.387965E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.250928E+10 |
April | 0.524810E+09 | 0.368699E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160853E+10 |
May | 0.544247E+09 | 0.383979E+10 | 0.892950E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21303236.53 | 0.135713E+10 |
June | 0.532585E+09 | 0.374678E+10 | 0.871243E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133372E+09 | 0.595973E+09 |
July | 0.536472E+09 | 0.378000E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.357701E+09 | 0.273511E+09 |
August | 0.551374E+09 | 0.387965E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.275929E+09 | 0.407029E+09 |
September | 0.524810E+09 | 0.368699E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122379E+09 | 0.878026E+09 |
October | 0.537120E+09 | 0.379993E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1515543.75 | 0.152541E+10 |
November | 0.518979E+09 | 0.368699E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.229620E+10 |
December | 0.536472E+09 | 0.378000E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.329998E+10 |
Annual Sum or Average | 0.638324E+10 | 0.450079E+11 | 0.104672E+11 | 0.912200E+09 | 0.215852E+11 | ||||
Minimum of Months | 0.487879E+09 | 0.344119E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.273511E+09 |
Maximum of Months | 0.551374E+09 | 0.387965E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.357701E+09 | 0.410566E+10 |
Report: SpaceGainsMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.537120E+09 | 0.379993E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.410033E+10 |
February | 0.487879E+09 | 0.344119E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.271835E+10 |
March | 0.551374E+09 | 0.387965E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.250103E+10 |
April | 0.524810E+09 | 0.368699E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159110E+10 |
May | 0.544247E+09 | 0.383979E+10 | 0.892950E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21305240.34 | 0.134483E+10 |
June | 0.532585E+09 | 0.374678E+10 | 0.871243E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133379E+09 | 0.592332E+09 |
July | 0.536472E+09 | 0.378000E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.357877E+09 | 0.271445E+09 |
August | 0.551374E+09 | 0.387965E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.275992E+09 | 0.404296E+09 |
September | 0.524810E+09 | 0.368699E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122450E+09 | 0.871172E+09 |
October | 0.537120E+09 | 0.379993E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1515544.22 | 0.150995E+10 |
November | 0.518979E+09 | 0.368699E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.227805E+10 |
December | 0.536472E+09 | 0.378000E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.329455E+10 |
Annual Sum or Average | 0.638324E+10 | 0.450079E+11 | 0.104672E+11 | 0.912519E+09 | 0.214774E+11 | ||||
Minimum of Months | 0.487879E+09 | 0.344119E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.271445E+09 |
Maximum of Months | 0.551374E+09 | 0.387965E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.357877E+09 | 0.410033E+10 |
Report: SpaceGainsMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.183632E+10 | 0.520705E+10 | 0.162546E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.753683E+10 |
February | 0.167188E+10 | 0.471657E+10 | 0.147229E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.498459E+10 |
March | 0.189386E+10 | 0.532596E+10 | 0.166213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.459251E+10 |
April | 0.180380E+10 | 0.505346E+10 | 0.157746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.285702E+10 |
May | 0.186509E+10 | 0.526650E+10 | 0.164379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38425151.24 | 0.244050E+10 |
June | 0.182945E+10 | 0.514264E+10 | 0.160496E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.240439E+09 | 0.110146E+10 |
July | 0.183943E+10 | 0.517732E+10 | 0.161629E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.645976E+09 | 0.520394E+09 |
August | 0.189386E+10 | 0.532596E+10 | 0.166213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.497702E+09 | 0.761733E+09 |
September | 0.180380E+10 | 0.505346E+10 | 0.157746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.220979E+09 | 0.160491E+10 |
October | 0.183632E+10 | 0.520705E+10 | 0.162546E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2730551.15 | 0.272363E+10 |
November | 0.176881E+10 | 0.505346E+10 | 0.157746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.415183E+10 |
December | 0.183943E+10 | 0.517732E+10 | 0.161629E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.605534E+10 |
Annual Sum or Average | 0.218821E+11 | 0.617068E+11 | 0.192612E+11 | 0.164625E+10 | 0.393307E+11 | ||||
Minimum of Months | 0.167188E+10 | 0.471657E+10 | 0.147229E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.520394E+09 |
Maximum of Months | 0.189386E+10 | 0.532596E+10 | 0.166213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.645976E+09 | 0.753683E+10 |
Report: SpaceGainsMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.918158E+09 | 0.260353E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.411812E+10 |
February | 0.835938E+09 | 0.235828E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.272128E+10 |
March | 0.946926E+09 | 0.266298E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.250575E+10 |
April | 0.901896E+09 | 0.252673E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.157352E+10 |
May | 0.932542E+09 | 0.263325E+10 | 0.821897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21313952.02 | 0.133854E+10 |
June | 0.914724E+09 | 0.257132E+10 | 0.802482E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133501E+09 | 0.596904E+09 |
July | 0.919713E+09 | 0.258866E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.358495E+09 | 0.275302E+09 |
August | 0.946926E+09 | 0.266298E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.276272E+09 | 0.409242E+09 |
September | 0.901896E+09 | 0.252673E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122513E+09 | 0.874614E+09 |
October | 0.918158E+09 | 0.260353E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1515708.53 | 0.150160E+10 |
November | 0.884402E+09 | 0.252673E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.227157E+10 |
December | 0.919713E+09 | 0.258866E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.330695E+10 |
Annual Sum or Average | 0.109410E+11 | 0.308534E+11 | 0.963059E+10 | 0.913610E+09 | 0.214934E+11 | ||||
Minimum of Months | 0.835938E+09 | 0.235828E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.275302E+09 |
Maximum of Months | 0.946926E+09 | 0.266298E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.358495E+09 | 0.411812E+10 |
Report: SpaceGainsMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.918158E+09 | 0.260353E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.411651E+10 |
February | 0.835938E+09 | 0.235828E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.271809E+10 |
March | 0.946926E+09 | 0.266298E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.250313E+10 |
April | 0.901896E+09 | 0.252673E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156761E+10 |
May | 0.932542E+09 | 0.263325E+10 | 0.821897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21315123.54 | 0.133378E+10 |
June | 0.914724E+09 | 0.257132E+10 | 0.802482E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133513E+09 | 0.595063E+09 |
July | 0.919713E+09 | 0.258866E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.358578E+09 | 0.274282E+09 |
August | 0.946926E+09 | 0.266298E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.276308E+09 | 0.408155E+09 |
September | 0.901896E+09 | 0.252673E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122554E+09 | 0.872509E+09 |
October | 0.918158E+09 | 0.260353E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1515708.74 | 0.149760E+10 |
November | 0.884402E+09 | 0.252673E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.226753E+10 |
December | 0.919713E+09 | 0.258866E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.330512E+10 |
Annual Sum or Average | 0.109410E+11 | 0.308534E+11 | 0.963059E+10 | 0.913783E+09 | 0.214594E+11 | ||||
Minimum of Months | 0.835938E+09 | 0.235828E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.274282E+09 |
Maximum of Months | 0.946926E+09 | 0.266298E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.358578E+09 | 0.411651E+10 |
Report: SpaceGainsMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.918158E+09 | 0.260353E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.410906E+10 |
February | 0.835938E+09 | 0.235828E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.270564E+10 |
March | 0.946926E+09 | 0.266298E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.249367E+10 |
April | 0.901896E+09 | 0.252673E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154673E+10 |
May | 0.932542E+09 | 0.263325E+10 | 0.821897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21318331.98 | 0.131497E+10 |
June | 0.914724E+09 | 0.257132E+10 | 0.802482E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133584E+09 | 0.586933E+09 |
July | 0.919713E+09 | 0.258866E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.358795E+09 | 0.270728E+09 |
August | 0.946926E+09 | 0.266298E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.276381E+09 | 0.403944E+09 |
September | 0.901896E+09 | 0.252673E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122633E+09 | 0.862950E+09 |
October | 0.918158E+09 | 0.260353E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1515704.66 | 0.147871E+10 |
November | 0.884402E+09 | 0.252673E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.225224E+10 |
December | 0.919713E+09 | 0.258866E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.329681E+10 |
Annual Sum or Average | 0.109410E+11 | 0.308534E+11 | 0.963059E+10 | 0.914227E+09 | 0.213224E+11 | ||||
Minimum of Months | 0.835938E+09 | 0.235828E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.270728E+09 |
Maximum of Months | 0.946926E+09 | 0.266298E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.358795E+09 | 0.410906E+10 |
Report: SpaceGainsMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.918158E+09 | 0.260353E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.514368E+10 |
February | 0.835938E+09 | 0.235828E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.344728E+10 |
March | 0.946926E+09 | 0.266298E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.317158E+10 |
April | 0.901896E+09 | 0.252673E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.196635E+10 |
May | 0.932542E+09 | 0.263325E+10 | 0.821897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 22697148.53 | 0.173867E+10 |
June | 0.914724E+09 | 0.257132E+10 | 0.802482E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140869E+09 | 0.840937E+09 |
July | 0.919713E+09 | 0.258866E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.378404E+09 | 0.445816E+09 |
August | 0.946926E+09 | 0.266298E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.292363E+09 | 0.607925E+09 |
September | 0.901896E+09 | 0.252673E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129377E+09 | 0.122274E+10 |
October | 0.918158E+09 | 0.260353E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1606595.28 | 0.195030E+10 |
November | 0.884402E+09 | 0.252673E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.291232E+10 |
December | 0.919713E+09 | 0.258866E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.412331E+10 |
Annual Sum or Average | 0.109410E+11 | 0.308534E+11 | 0.963059E+10 | 0.965317E+09 | 0.275709E+11 | ||||
Minimum of Months | 0.835938E+09 | 0.235828E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.445816E+09 |
Maximum of Months | 0.946926E+09 | 0.266298E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.378404E+09 | 0.514368E+10 |
Report: PeakSpaceGainsMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2159.72 | 01-JAN-13:09 | 6078.71 | 01-JAN-10:09 | 1348.26 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 15364.08 | 10-JAN-18:00 |
February | 2159.72 | 03-FEB-13:09 | 6078.71 | 01-FEB-10:09 | 1348.26 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 12414.04 | 09-FEB-18:00 |
March | 2159.72 | 03-MAR-13:09 | 6078.71 | 01-MAR-10:09 | 1348.26 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 11849.64 | 04-MAR-18:00 |
April | 2159.72 | 01-APR-12:09 | 6078.71 | 01-APR-09:09 | 1348.26 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 7152.78 | 27-APR-11:10 |
May | 2159.72 | 05-MAY-12:09 | 6078.71 | 01-MAY-09:09 | 1348.26 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1606.61 | 20-MAY-16:00 | 6558.06 | 22-MAY-16:00 |
June | 2159.72 | 02-JUN-12:09 | 6078.71 | 01-JUN-09:09 | 1348.26 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2254.08 | 29-JUN-15:00 | 4389.35 | 16-JUN-11:05 |
July | 2159.72 | 01-JUL-12:09 | 6078.71 | 01-JUL-09:09 | 1348.26 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3402.03 | 17-JUL-16:00 | 2632.76 | 05-JUL-11:10 |
August | 2159.72 | 04-AUG-12:09 | 6078.71 | 01-AUG-09:09 | 1348.26 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3013.90 | 05-AUG-16:00 | 4164.84 | 17-AUG-11:05 |
September | 2159.72 | 01-SEP-12:09 | 6078.71 | 01-SEP-09:09 | 1348.26 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2770.44 | 02-SEP-15:00 | 5059.85 | 12-SEP-11:10 |
October | 2159.72 | 01-OCT-12:09 | 6078.71 | 01-OCT-09:09 | 1348.26 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 300.32 | 18-OCT-14:00 | 6168.47 | 10-OCT-11:10 |
November | 2159.72 | 03-NOV-12:09 | 6078.71 | 01-NOV-09:09 | 1348.26 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 10834.03 | 26-NOV-18:00 |
December | 2159.72 | 01-DEC-13:09 | 6078.71 | 01-DEC-10:09 | 1348.26 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 13286.18 | 28-DEC-18:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2159.72 | 6078.71 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2632.76 | |||||
Maximum of Months | 2159.72 | 6078.71 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 3402.03 | 15364.08 |
Report: PeakSpaceGainsMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1079.86 | 01-JAN-13:09 | 3278.04 | 01-JAN-10:09 | 674.13 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 8415.71 | 10-JAN-18:00 |
February | 1079.86 | 03-FEB-13:09 | 3278.04 | 01-FEB-10:09 | 674.13 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 6783.34 | 09-FEB-18:00 |
March | 1079.86 | 03-MAR-13:09 | 3278.04 | 01-MAR-10:09 | 674.13 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 6558.56 | 04-MAR-18:00 |
April | 1079.86 | 01-APR-12:09 | 3278.04 | 01-APR-09:09 | 674.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 3838.43 | 27-APR-11:10 |
May | 1079.86 | 05-MAY-12:09 | 3278.04 | 01-MAY-09:09 | 674.13 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 867.12 | 20-MAY-16:00 | 3450.85 | 22-MAY-16:00 |
June | 1079.86 | 02-JUN-12:09 | 3278.04 | 01-JUN-09:09 | 674.13 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1196.97 | 29-JUN-15:00 | 2517.33 | 16-JUN-11:05 |
July | 1079.86 | 01-JUL-12:09 | 3278.04 | 01-JUL-09:09 | 674.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1854.59 | 17-JUL-16:00 | 1485.06 | 05-JUL-11:10 |
August | 1079.86 | 04-AUG-12:09 | 3278.04 | 01-AUG-09:09 | 674.13 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1638.32 | 05-AUG-16:00 | 2367.47 | 17-AUG-11:05 |
September | 1079.86 | 01-SEP-12:09 | 3278.04 | 01-SEP-09:09 | 674.13 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1488.52 | 02-SEP-15:00 | 2803.38 | 12-SEP-11:05 |
October | 1079.86 | 01-OCT-12:09 | 3278.04 | 01-OCT-09:09 | 674.13 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 161.34 | 18-OCT-14:00 | 3337.09 | 10-OCT-11:10 |
November | 1079.86 | 03-NOV-12:09 | 3278.04 | 01-NOV-09:09 | 674.13 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 5891.64 | 26-NOV-18:00 |
December | 1079.86 | 01-DEC-13:09 | 3278.04 | 01-DEC-10:09 | 674.13 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 7350.57 | 31-DEC-12:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1079.86 | 3278.04 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1485.06 | |||||
Maximum of Months | 1079.86 | 3278.04 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1854.59 | 8415.71 |
Report: PeakSpaceGainsMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1079.86 | 07-JAN-13:09 | 2921.79 | 01-JAN-10:09 | 674.13 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 8415.69 | 10-JAN-18:00 |
February | 1079.86 | 04-FEB-13:09 | 2921.79 | 01-FEB-09:09 | 674.13 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 6783.33 | 09-FEB-18:00 |
March | 1079.86 | 04-MAR-13:09 | 2921.79 | 01-MAR-09:09 | 674.13 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 6558.56 | 04-MAR-18:00 |
April | 1079.86 | 01-APR-12:09 | 2921.79 | 01-APR-08:09 | 674.13 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 3838.42 | 27-APR-11:10 |
May | 1079.86 | 06-MAY-12:09 | 2921.79 | 01-MAY-08:09 | 674.13 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 867.12 | 20-MAY-16:00 | 3450.82 | 22-MAY-16:00 |
June | 1079.86 | 03-JUN-12:09 | 2921.79 | 01-JUN-08:09 | 674.13 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1196.97 | 29-JUN-15:00 | 2504.27 | 16-JUN-11:05 |
July | 1079.86 | 01-JUL-12:09 | 2921.79 | 01-JUL-08:09 | 674.13 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1854.58 | 17-JUL-16:00 | 1485.07 | 05-JUL-11:10 |
August | 1079.86 | 05-AUG-12:09 | 2921.79 | 01-AUG-08:09 | 674.13 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1638.32 | 05-AUG-16:00 | 2369.06 | 17-AUG-11:05 |
September | 1079.86 | 02-SEP-12:09 | 2921.79 | 01-SEP-08:09 | 674.13 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1488.52 | 02-SEP-15:00 | 2793.14 | 12-SEP-11:05 |
October | 1079.86 | 07-OCT-12:09 | 2921.79 | 01-OCT-09:09 | 674.13 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 161.34 | 18-OCT-14:00 | 3337.08 | 10-OCT-11:10 |
November | 1079.86 | 04-NOV-12:09 | 2921.79 | 01-NOV-08:09 | 674.13 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 5891.64 | 26-NOV-18:00 |
December | 1079.86 | 02-DEC-13:09 | 2921.79 | 01-DEC-09:09 | 674.13 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 7350.58 | 31-DEC-12:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1079.86 | 2921.79 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1485.07 | |||||
Maximum of Months | 1079.86 | 2921.79 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1854.58 | 8415.69 |
Report: PeakSpaceGainsMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1079.86 | 07-JAN-13:09 | 2921.79 | 01-JAN-10:09 | 674.13 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 8415.70 | 10-JAN-18:00 |
February | 1079.86 | 04-FEB-13:09 | 2921.79 | 01-FEB-09:09 | 674.13 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 6783.33 | 09-FEB-18:00 |
March | 1079.86 | 04-MAR-13:09 | 2921.79 | 01-MAR-09:09 | 674.13 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 6558.56 | 04-MAR-18:00 |
April | 1079.86 | 01-APR-12:09 | 2921.79 | 01-APR-08:09 | 674.13 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 3838.42 | 27-APR-11:10 |
May | 1079.86 | 06-MAY-12:09 | 2921.79 | 01-MAY-08:09 | 674.13 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 867.12 | 20-MAY-16:00 | 3450.83 | 22-MAY-16:00 |
June | 1079.86 | 03-JUN-12:09 | 2921.79 | 01-JUN-08:09 | 674.13 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1196.97 | 29-JUN-15:00 | 2495.15 | 16-JUN-11:05 |
July | 1079.86 | 01-JUL-12:09 | 2921.79 | 01-JUL-08:09 | 674.13 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1854.58 | 17-JUL-16:00 | 1485.07 | 05-JUL-11:10 |
August | 1079.86 | 05-AUG-12:09 | 2921.79 | 01-AUG-08:09 | 674.13 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1638.32 | 05-AUG-16:00 | 2366.45 | 17-AUG-11:05 |
September | 1079.86 | 02-SEP-12:09 | 2921.79 | 01-SEP-08:09 | 674.13 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1488.52 | 02-SEP-15:00 | 2783.39 | 12-SEP-11:05 |
October | 1079.86 | 07-OCT-12:09 | 2921.79 | 01-OCT-09:09 | 674.13 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 161.34 | 18-OCT-14:00 | 3337.08 | 10-OCT-11:10 |
November | 1079.86 | 04-NOV-12:09 | 2921.79 | 01-NOV-08:09 | 674.13 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 5891.64 | 26-NOV-18:00 |
December | 1079.86 | 02-DEC-13:09 | 2921.79 | 01-DEC-09:09 | 674.13 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 7350.58 | 31-DEC-12:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1079.86 | 2921.79 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1485.07 | |||||
Maximum of Months | 1079.86 | 2921.79 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1854.58 | 8415.70 |
Report: PeakSpaceGainsMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1079.86 | 07-JAN-13:09 | 2921.79 | 01-JAN-10:09 | 674.13 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 8415.70 | 10-JAN-18:00 |
February | 1079.86 | 04-FEB-13:09 | 2921.79 | 01-FEB-09:09 | 674.13 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 6783.33 | 09-FEB-18:00 |
March | 1079.86 | 04-MAR-13:09 | 2921.79 | 01-MAR-09:09 | 674.13 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 6558.56 | 04-MAR-18:00 |
April | 1079.86 | 01-APR-12:09 | 2921.79 | 01-APR-08:09 | 674.13 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 3838.42 | 27-APR-11:10 |
May | 1079.86 | 06-MAY-12:09 | 2921.79 | 01-MAY-08:09 | 674.13 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 867.12 | 20-MAY-16:00 | 3450.83 | 22-MAY-16:00 |
June | 1079.86 | 03-JUN-12:09 | 2921.79 | 01-JUN-08:09 | 674.13 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1196.97 | 29-JUN-15:00 | 2468.75 | 16-JUN-11:05 |
July | 1079.86 | 01-JUL-12:09 | 2921.79 | 01-JUL-08:09 | 674.13 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1854.58 | 17-JUL-16:00 | 1485.07 | 05-JUL-11:10 |
August | 1079.86 | 05-AUG-12:09 | 2921.79 | 01-AUG-08:09 | 674.13 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1638.32 | 05-AUG-16:00 | 2342.39 | 17-AUG-11:05 |
September | 1079.86 | 02-SEP-12:09 | 2921.79 | 01-SEP-08:09 | 674.13 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1488.52 | 02-SEP-15:00 | 2750.39 | 12-SEP-11:05 |
October | 1079.86 | 07-OCT-12:09 | 2921.79 | 01-OCT-09:09 | 674.13 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 161.34 | 18-OCT-14:00 | 3337.08 | 10-OCT-11:10 |
November | 1079.86 | 04-NOV-12:09 | 2921.79 | 01-NOV-08:09 | 674.13 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 5891.64 | 26-NOV-18:00 |
December | 1079.86 | 02-DEC-13:09 | 2921.79 | 01-DEC-09:09 | 674.13 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 7350.58 | 31-DEC-12:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1079.86 | 2921.79 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1485.07 | |||||
Maximum of Months | 1079.86 | 2921.79 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1854.58 | 8415.70 |
Report: PeakSpaceGainsMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2879.63 | 07-JAN-15:09 | 4358.02 | 01-JAN-11:09 | 1348.26 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 15122.72 | 10-JAN-18:00 |
February | 2879.63 | 04-FEB-15:09 | 4358.02 | 01-FEB-10:09 | 1348.26 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 12193.07 | 09-FEB-18:00 |
March | 2879.63 | 04-MAR-15:09 | 4358.02 | 01-MAR-10:09 | 1348.26 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 11770.37 | 04-MAR-18:00 |
April | 2879.63 | 01-APR-14:09 | 4358.02 | 01-APR-09:09 | 1348.26 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 6915.20 | 27-APR-11:10 |
May | 2879.63 | 06-MAY-14:09 | 4358.02 | 01-MAY-09:09 | 1348.26 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1561.15 | 20-MAY-16:00 | 6232.53 | 22-MAY-16:00 |
June | 2879.63 | 03-JUN-14:09 | 4358.02 | 01-JUN-09:09 | 1348.26 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2159.34 | 29-JUN-15:00 | 4348.49 | 16-JUN-11:05 |
July | 2879.63 | 01-JUL-14:09 | 4358.02 | 01-JUL-09:09 | 1348.26 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3334.49 | 17-JUL-16:00 | 2588.76 | 05-JUL-11:10 |
August | 2879.63 | 05-AUG-14:09 | 4358.02 | 01-AUG-09:09 | 1348.26 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2946.71 | 05-AUG-16:00 | 3990.36 | 17-AUG-11:05 |
September | 2879.63 | 02-SEP-14:09 | 4358.02 | 01-SEP-09:09 | 1348.26 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2681.19 | 02-SEP-15:00 | 4867.39 | 12-SEP-11:10 |
October | 2879.63 | 07-OCT-14:09 | 4358.02 | 01-OCT-10:09 | 1348.26 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 290.66 | 18-OCT-14:00 | 6005.89 | 10-OCT-11:10 |
November | 2879.63 | 04-NOV-14:09 | 4358.02 | 01-NOV-09:09 | 1348.26 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 10596.59 | 26-NOV-18:00 |
December | 2879.63 | 02-DEC-15:09 | 4358.02 | 01-DEC-10:09 | 1348.26 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 13191.80 | 31-DEC-12:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2879.63 | 4358.02 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2588.76 | |||||
Maximum of Months | 2879.63 | 4358.02 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 3334.49 | 15122.72 |
Report: PeakSpaceGainsMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1439.81 | 07-JAN-15:09 | 2179.01 | 01-JAN-11:09 | 674.13 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 8415.69 | 10-JAN-18:00 |
February | 1439.81 | 04-FEB-15:09 | 2179.01 | 01-FEB-10:09 | 674.13 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 6783.32 | 09-FEB-18:00 |
March | 1439.81 | 04-MAR-15:09 | 2179.01 | 01-MAR-10:09 | 674.13 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 6558.55 | 04-MAR-18:00 |
April | 1439.81 | 01-APR-14:09 | 2179.01 | 01-APR-09:09 | 674.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 3838.41 | 27-APR-11:10 |
May | 1439.81 | 06-MAY-14:09 | 2179.01 | 01-MAY-09:09 | 674.13 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 867.14 | 20-MAY-16:00 | 3450.82 | 22-MAY-16:00 |
June | 1439.81 | 03-JUN-14:09 | 2179.01 | 01-JUN-09:09 | 674.13 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1196.99 | 29-JUN-15:00 | 2426.18 | 16-JUN-11:05 |
July | 1439.81 | 01-JUL-14:09 | 2179.01 | 01-JUL-09:09 | 674.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1854.61 | 17-JUL-16:00 | 1474.24 | 05-JUL-11:10 |
August | 1439.81 | 05-AUG-14:09 | 2179.01 | 01-AUG-09:09 | 674.13 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1638.34 | 05-AUG-16:00 | 2283.21 | 17-AUG-11:05 |
September | 1439.81 | 02-SEP-14:09 | 2179.01 | 01-SEP-09:09 | 674.13 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1488.54 | 02-SEP-15:00 | 2702.78 | 12-SEP-11:05 |
October | 1439.81 | 07-OCT-14:09 | 2179.01 | 01-OCT-10:09 | 674.13 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 161.35 | 18-OCT-14:00 | 3337.07 | 10-OCT-11:10 |
November | 1439.81 | 04-NOV-14:09 | 2179.01 | 01-NOV-09:09 | 674.13 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 5891.63 | 26-NOV-18:00 |
December | 1439.81 | 02-DEC-15:09 | 2179.01 | 01-DEC-10:09 | 674.13 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 7350.58 | 31-DEC-12:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1439.81 | 2179.01 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1474.24 | |||||
Maximum of Months | 1439.81 | 2179.01 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1854.61 | 8415.69 |
Report: PeakSpaceGainsMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1439.81 | 07-JAN-15:09 | 2179.01 | 01-JAN-11:09 | 674.13 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 8415.69 | 10-JAN-18:00 |
February | 1439.81 | 04-FEB-15:09 | 2179.01 | 01-FEB-10:09 | 674.13 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 6783.32 | 09-FEB-18:00 |
March | 1439.81 | 04-MAR-15:09 | 2179.01 | 01-MAR-10:09 | 674.13 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 6558.55 | 04-MAR-18:00 |
April | 1439.81 | 01-APR-14:09 | 2179.01 | 01-APR-09:09 | 674.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 3838.41 | 27-APR-11:10 |
May | 1439.81 | 06-MAY-14:09 | 2179.01 | 01-MAY-09:09 | 674.13 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 867.14 | 20-MAY-16:00 | 3450.82 | 22-MAY-16:00 |
June | 1439.81 | 03-JUN-14:09 | 2179.01 | 01-JUN-09:09 | 674.13 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1196.99 | 29-JUN-15:00 | 2425.04 | 16-JUN-11:05 |
July | 1439.81 | 01-JUL-14:09 | 2179.01 | 01-JUL-09:09 | 674.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1854.61 | 17-JUL-16:00 | 1471.44 | 05-JUL-11:10 |
August | 1439.81 | 05-AUG-14:09 | 2179.01 | 01-AUG-09:09 | 674.13 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1638.34 | 05-AUG-16:00 | 2276.22 | 17-AUG-11:05 |
September | 1439.81 | 02-SEP-14:09 | 2179.01 | 01-SEP-09:09 | 674.13 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1488.54 | 02-SEP-15:00 | 2701.74 | 12-SEP-11:05 |
October | 1439.81 | 07-OCT-14:09 | 2179.01 | 01-OCT-10:09 | 674.13 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 161.35 | 18-OCT-14:00 | 3337.07 | 10-OCT-11:10 |
November | 1439.81 | 04-NOV-14:09 | 2179.01 | 01-NOV-09:09 | 674.13 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 5891.64 | 26-NOV-18:00 |
December | 1439.81 | 02-DEC-15:09 | 2179.01 | 01-DEC-10:09 | 674.13 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 7350.58 | 31-DEC-12:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1439.81 | 2179.01 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1471.44 | |||||
Maximum of Months | 1439.81 | 2179.01 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1854.61 | 8415.69 |
Report: PeakSpaceGainsMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1439.81 | 07-JAN-15:09 | 2179.01 | 01-JAN-11:09 | 674.13 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 8415.69 | 10-JAN-18:00 |
February | 1439.81 | 04-FEB-15:09 | 2179.01 | 01-FEB-10:09 | 674.13 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 6783.32 | 09-FEB-18:00 |
March | 1439.81 | 04-MAR-15:09 | 2179.01 | 01-MAR-10:09 | 674.13 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 6558.55 | 04-MAR-18:00 |
April | 1439.81 | 01-APR-14:09 | 2179.01 | 01-APR-09:09 | 674.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 3838.41 | 27-APR-11:10 |
May | 1439.81 | 06-MAY-14:09 | 2179.01 | 01-MAY-09:09 | 674.13 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 867.14 | 20-MAY-16:00 | 3450.82 | 22-MAY-16:00 |
June | 1439.81 | 03-JUN-14:09 | 2179.01 | 01-JUN-09:09 | 674.13 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1196.98 | 29-JUN-15:00 | 2422.12 | 16-JUN-11:05 |
July | 1439.81 | 01-JUL-14:09 | 2179.01 | 01-JUL-09:09 | 674.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1854.61 | 17-JUL-16:00 | 1460.32 | 05-JUL-11:10 |
August | 1439.81 | 05-AUG-14:09 | 2179.01 | 01-AUG-09:09 | 674.13 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1638.34 | 05-AUG-16:00 | 2241.49 | 17-AUG-11:05 |
September | 1439.81 | 02-SEP-14:09 | 2179.01 | 01-SEP-09:09 | 674.13 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1488.54 | 02-SEP-15:00 | 2699.79 | 12-SEP-11:10 |
October | 1439.81 | 07-OCT-14:09 | 2179.01 | 01-OCT-10:09 | 674.13 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 161.35 | 18-OCT-14:00 | 3337.07 | 10-OCT-11:10 |
November | 1439.81 | 04-NOV-14:09 | 2179.01 | 01-NOV-09:09 | 674.13 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 5891.64 | 26-NOV-18:00 |
December | 1439.81 | 02-DEC-15:09 | 2179.01 | 01-DEC-10:09 | 674.13 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 7350.58 | 31-DEC-12:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1439.81 | 2179.01 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1460.32 | |||||
Maximum of Months | 1439.81 | 2179.01 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1854.61 | 8415.69 |
Report: PeakSpaceGainsMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1439.81 | 07-JAN-15:09 | 2179.01 | 01-JAN-11:09 | 674.13 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 8656.72 | 10-JAN-18:00 |
February | 1439.81 | 04-FEB-15:09 | 2179.01 | 01-FEB-10:09 | 674.13 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 7003.99 | 09-FEB-18:00 |
March | 1439.81 | 04-MAR-15:09 | 2179.01 | 01-MAR-10:09 | 674.13 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 6689.31 | 04-MAR-14:00 |
April | 1439.81 | 01-APR-14:09 | 2179.01 | 01-APR-09:09 | 674.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 4075.67 | 27-APR-11:10 |
May | 1439.81 | 06-MAY-14:09 | 2179.01 | 01-MAY-09:09 | 674.13 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 912.60 | 20-MAY-16:00 | 3775.94 | 22-MAY-16:00 |
June | 1439.81 | 03-JUN-14:09 | 2179.01 | 01-JUN-09:09 | 674.13 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1291.67 | 29-JUN-15:00 | 2462.91 | 16-JUN-11:05 |
July | 1439.81 | 01-JUL-14:09 | 2179.01 | 01-JUL-09:09 | 674.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1922.12 | 17-JUL-16:00 | 1402.67 | 05-JUL-11:10 |
August | 1439.81 | 05-AUG-14:09 | 2179.01 | 01-AUG-09:09 | 674.13 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1705.54 | 05-AUG-16:00 | 2325.43 | 17-AUG-11:05 |
September | 1439.81 | 02-SEP-14:09 | 2179.01 | 01-SEP-09:09 | 674.13 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1577.77 | 02-SEP-15:00 | 2891.97 | 12-SEP-11:10 |
October | 1439.81 | 07-OCT-14:09 | 2179.01 | 01-OCT-10:09 | 674.13 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 171.02 | 18-OCT-14:00 | 3499.42 | 10-OCT-11:10 |
November | 1439.81 | 04-NOV-14:09 | 2179.01 | 01-NOV-09:09 | 674.13 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 6128.78 | 26-NOV-18:00 |
December | 1439.81 | 02-DEC-15:09 | 2179.01 | 01-DEC-10:09 | 674.13 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 7465.45 | 28-DEC-18:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1439.81 | 2179.01 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1402.67 | |||||
Maximum of Months | 1439.81 | 2179.01 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1922.12 | 8656.72 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 20452.56 | 28-JAN-00:01 | 1619.79 | 28793.87 | 6741.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 356.91 |
February | 16964.68 | 04-FEB-00:01 | 1439.81 | 25594.55 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 403.89 |
March | 15316.62 | 04-MAR-00:01 | 1259.84 | 22395.23 | 5243.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 464.20 |
April | 9988.77 | 30-APR-08:04 | 1439.81 | 25594.55 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1080.55 |
May | 15616.08 | 20-MAY-08:62 | 899.88 | 15996.59 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 168.36 |
June | 31202.94 | 26-JUN-08:62 | 1079.86 | 19195.91 | 4494.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 166.69 |
July | 36912.82 | 27-JUL-08:62 | 1079.86 | 19195.91 | 4494.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 377.66 |
August | 36231.70 | 26-AUG-08:62 | 1079.86 | 19195.91 | 4494.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 317.48 |
September | 34550.14 | 05-SEP-08:61 | 1439.81 | 25594.55 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 254.44 |
October | 9447.15 | 18-OCT-14:00 | 1439.81 | 6078.71 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 300.32 | 0.00 |
November | 15528.40 | 26-NOV-09:04 | 1439.81 | 25594.55 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1990.89 |
December | 18019.77 | 29-DEC-00:01 | 1439.81 | 25594.55 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.31 |
Annual Sum or Average | |||||||||||
Minimum of Months | 9447.15 | 899.88 | 6078.71 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 36912.82 | 1619.79 | 28793.87 | 6741.28 | 0.00 | 0.00 | 0.00 | 0.00 | 300.32 | 1990.89 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7466.85 | 19-JAN-09:04 | 719.90 | 13802.27 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 973.72 |
February | 7611.11 | 09-FEB-09:04 | 719.90 | 13802.27 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 948.08 |
March | 7899.99 | 04-MAR-09:04 | 719.90 | 13802.27 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 927.86 |
April | 18271.69 | 25-APR-20:02 | 5399.28 | 32780.40 | 6741.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 19441.29 | 13-MAY-20:14 | 4859.35 | 29502.36 | 6067.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.01 |
June | 20441.82 | 24-JUN-22:02 | 3599.52 | 32780.40 | 6741.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.67 |
July | 20800.08 | 27-JUL-08:62 | 539.93 | 10351.71 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 213.02 |
August | 21673.39 | 02-AUG-08:62 | 449.94 | 8626.42 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 258.48 |
September | 20917.30 | 08-SEP-20:30 | 1619.78 | 9834.12 | 2022.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.38 |
October | 19549.27 | 15-OCT-18:08 | 2879.62 | 13112.16 | 2696.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 144.01 |
November | 18228.12 | 04-NOV-19:22 | 5399.28 | 32780.40 | 6741.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.55 |
December | 6392.28 | 14-DEC-09:03 | 719.90 | 13802.27 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 766.43 |
Annual Sum or Average | |||||||||||
Minimum of Months | 6392.28 | 449.94 | 8626.42 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 21673.39 | 5399.28 | 32780.40 | 6741.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 973.72 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7418.42 | 19-JAN-08:04 | 719.90 | 12302.27 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 921.73 |
February | 7633.95 | 09-FEB-08:03 | 809.89 | 13840.06 | 3370.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 934.36 |
March | 7852.28 | 04-MAR-08:04 | 719.90 | 12302.27 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 902.10 |
April | 4684.79 | 29-APR-07:02 | 719.90 | 12302.27 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 641.45 |
May | 18180.39 | 20-MAY-07:02 | 449.94 | 7688.92 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 120.36 |
June | 23838.92 | 07-JUN-07:01 | 719.90 | 12302.27 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 332.20 |
July | 22285.58 | 12-JUL-07:02 | 449.94 | 7688.92 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 203.79 |
August | 24385.00 | 28-AUG-07:01 | 629.92 | 10764.49 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 296.28 |
September | 26083.38 | 28-SEP-07:01 | 719.90 | 12302.27 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 376.51 |
October | 24410.28 | 19-OCT-07:02 | 539.93 | 9226.71 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 290.90 |
November | 6326.08 | 27-NOV-08:04 | 719.90 | 12302.27 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 846.74 |
December | 6544.81 | 14-DEC-08:03 | 629.92 | 10764.49 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 771.29 |
Annual Sum or Average | |||||||||||
Minimum of Months | 4684.79 | 449.94 | 7688.92 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 120.36 | |
Maximum of Months | 26083.38 | 809.89 | 13840.06 | 3370.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 934.36 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6403.94 | 25-JAN-08:04 | 719.90 | 12302.27 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 953.33 |
February | 6939.11 | 02-FEB-08:03 | 809.89 | 13840.06 | 3370.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 894.66 |
March | 7944.29 | 04-MAR-08:04 | 719.90 | 12302.27 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 903.83 |
April | 4788.20 | 29-APR-07:02 | 719.90 | 12302.27 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 643.65 |
May | 18187.07 | 20-MAY-07:02 | 449.94 | 7688.92 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 119.07 |
June | 23896.11 | 07-JUN-07:01 | 719.90 | 12302.27 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 331.50 |
July | 22352.96 | 12-JUL-07:02 | 449.94 | 7688.92 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 203.53 |
August | 24505.62 | 28-AUG-07:01 | 629.92 | 10764.49 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 297.05 |
September | 26177.23 | 28-SEP-07:01 | 719.90 | 12302.27 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 376.49 |
October | 23388.26 | 19-OCT-07:02 | 539.93 | 9226.71 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 290.83 |
November | 6481.61 | 27-NOV-08:04 | 719.90 | 12302.27 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 849.31 |
December | 6201.96 | 12-DEC-08:03 | 629.92 | 10764.49 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 789.86 |
Annual Sum or Average | |||||||||||
Minimum of Months | 4788.20 | 449.94 | 7688.92 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 119.07 | |
Maximum of Months | 26177.23 | 809.89 | 13840.06 | 3370.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 953.33 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6550.26 | 25-JAN-08:04 | 719.90 | 12302.27 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 956.56 |
February | 4464.76 | 22-FEB-08:03 | 539.93 | 9226.71 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 609.29 |
March | 4746.41 | 07-MAR-08:03 | 809.89 | 13840.06 | 3370.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 559.52 |
April | 4766.01 | 29-APR-07:02 | 719.90 | 12302.27 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 638.60 |
May | 17680.90 | 20-MAY-07:02 | 449.94 | 7688.92 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 114.81 |
June | 23620.79 | 07-JUN-07:01 | 719.90 | 12302.27 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 328.33 |
July | 21247.45 | 29-JUL-07:02 | 539.93 | 9226.71 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 217.93 |
August | 24251.79 | 28-AUG-07:01 | 629.92 | 10764.49 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 294.58 |
September | 25891.58 | 28-SEP-07:01 | 719.90 | 12302.27 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 373.27 |
October | 20250.56 | 19-OCT-07:02 | 539.93 | 9226.71 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 290.57 |
November | 7019.62 | 26-NOV-09:04 | 719.90 | 12302.27 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 959.04 |
December | 5967.87 | 27-DEC-08:04 | 719.90 | 12302.27 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 719.31 |
Annual Sum or Average | |||||||||||
Minimum of Months | 4464.76 | 449.94 | 7688.92 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 114.81 | |
Maximum of Months | 25891.58 | 809.89 | 13840.06 | 3370.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 959.04 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 12785.62 | 05-JAN-09:04 | 3167.59 | 18349.55 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1555.06 |
February | 11781.93 | 23-FEB-09:04 | 3167.59 | 18349.55 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1180.37 |
March | 13295.47 | 03-MAR-09:04 | 3167.59 | 18349.55 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1678.77 |
April | 9917.49 | 30-APR-09:04 | 3167.59 | 18349.55 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1009.01 |
May | 12176.16 | 20-MAY-08:62 | 1979.74 | 11468.47 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 150.78 |
June | 34259.91 | 25-JUN-09:02 | 1979.74 | 11468.47 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 263.40 |
July | 36762.14 | 27-JUL-08:62 | 2375.69 | 13762.16 | 4494.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 361.16 |
August | 37169.02 | 26-AUG-08:62 | 2375.69 | 13762.16 | 4494.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 294.31 |
September | 35574.25 | 08-SEP-08:62 | 2375.69 | 13762.16 | 4494.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 476.78 |
October | 10340.02 | 10-OCT-08:04 | 3167.59 | 18349.55 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1128.61 |
November | 11638.36 | 11-NOV-10:03 | 2375.69 | 13762.16 | 4494.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1126.94 |
December | 13017.77 | 12-DEC-09:04 | 3167.59 | 18349.55 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1349.95 |
Annual Sum or Average | |||||||||||
Minimum of Months | 9917.49 | 1979.74 | 11468.47 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 150.78 | |
Maximum of Months | 37169.02 | 3167.59 | 18349.55 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1678.77 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5893.39 | 05-JAN-09:04 | 1583.79 | 9174.77 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 849.78 |
February | 5306.97 | 23-FEB-09:04 | 1583.79 | 9174.77 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 652.73 |
March | 6685.73 | 03-MAR-09:04 | 1583.79 | 9174.77 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 920.08 |
April | 4445.76 | 28-APR-08:02 | 1583.79 | 9174.77 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 522.42 |
May | 11898.45 | 20-MAY-08:62 | 989.87 | 5734.23 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.54 |
June | 18021.20 | 25-JUN-09:02 | 989.87 | 5734.23 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 154.27 |
July | 19308.97 | 27-JUL-08:62 | 1187.84 | 6881.08 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 207.96 |
August | 19544.95 | 26-AUG-08:62 | 1187.84 | 6881.08 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 170.89 |
September | 18976.17 | 09-SEP-08:62 | 989.87 | 5734.23 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 156.06 |
October | 7836.93 | 19-OCT-08:62 | 791.89 | 4587.39 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 227.72 |
November | 7053.87 | 26-NOV-10:04 | 1583.79 | 9174.77 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 943.33 |
December | 6523.84 | 14-DEC-09:04 | 1583.79 | 9174.77 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 770.14 |
Annual Sum or Average | |||||||||||
Minimum of Months | 4445.76 | 791.89 | 4587.39 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.54 | |
Maximum of Months | 19544.95 | 1583.79 | 9174.77 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 943.33 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5905.15 | 05-JAN-09:04 | 1583.79 | 9174.77 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 848.43 |
February | 5375.19 | 23-FEB-09:04 | 1583.79 | 9174.77 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 654.04 |
March | 6735.37 | 03-MAR-09:04 | 1583.79 | 9174.77 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 920.44 |
April | 4250.69 | 30-APR-09:04 | 1583.79 | 9174.77 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 551.07 |
May | 10404.66 | 20-MAY-08:62 | 989.87 | 5734.23 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.39 |
June | 17816.29 | 25-JUN-09:02 | 989.87 | 5734.23 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 153.02 |
July | 19100.64 | 27-JUL-08:62 | 1187.84 | 6881.08 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 206.92 |
August | 19333.00 | 26-AUG-08:62 | 1187.84 | 6881.08 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 169.79 |
September | 18705.03 | 09-SEP-08:62 | 989.87 | 5734.23 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 155.07 |
October | 7050.75 | 19-OCT-08:62 | 791.89 | 4587.39 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 227.58 |
November | 5505.74 | 26-NOV-10:04 | 1583.79 | 9174.77 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 942.09 |
December | 6502.91 | 14-DEC-09:04 | 1583.79 | 9174.77 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 767.75 |
Annual Sum or Average | |||||||||||
Minimum of Months | 4250.69 | 791.89 | 4587.39 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.39 | |
Maximum of Months | 19333.00 | 1583.79 | 9174.77 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 942.09 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5851.46 | 05-JAN-09:04 | 1583.79 | 9174.77 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 841.64 |
February | 5356.56 | 23-FEB-09:04 | 1583.79 | 9174.77 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 648.92 |
March | 4708.27 | 07-MAR-09:04 | 1583.79 | 9174.77 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 518.83 |
April | 4506.09 | 30-APR-09:04 | 1583.79 | 9174.77 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 556.36 |
May | 5253.47 | 20-MAY-08:62 | 989.87 | 5734.23 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.90 |
June | 17445.95 | 25-JUN-09:02 | 989.87 | 5734.23 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 148.51 |
July | 18760.34 | 27-JUL-08:62 | 1187.84 | 6881.08 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 203.47 |
August | 18973.31 | 26-AUG-08:62 | 1187.84 | 6881.08 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 165.85 |
September | 18131.02 | 08-SEP-08:62 | 1187.84 | 6881.08 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 262.83 |
October | 4642.45 | 10-OCT-08:04 | 1583.79 | 9174.77 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 618.67 |
November | 5264.39 | 11-NOV-10:03 | 1187.84 | 6881.08 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 624.11 |
December | 5975.56 | 12-DEC-09:04 | 1583.79 | 9174.77 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 740.92 |
Annual Sum or Average | |||||||||||
Minimum of Months | 4506.09 | 989.87 | 5734.23 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.90 | |
Maximum of Months | 18973.31 | 1583.79 | 9174.77 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 841.64 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3979.68 | 21-JAN-09:04 | 1583.79 | 9174.77 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 660.10 |
February | 4634.69 | 22-FEB-09:04 | 1583.79 | 9174.77 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 841.90 |
March | 4624.54 | 25-MAR-08:04 | 1583.79 | 9174.77 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 594.01 |
April | 4480.15 | 28-APR-08:04 | 1583.79 | 9174.77 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 579.13 |
May | 4119.24 | 07-MAY-09:04 | 1583.79 | 9174.77 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 894.64 |
June | 16984.69 | 25-JUN-09:02 | 989.87 | 5734.23 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 159.33 |
July | 18211.04 | 27-JUL-08:62 | 1187.84 | 6881.08 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 214.55 |
August | 19569.82 | 13-AUG-09:01 | 1385.82 | 8027.93 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 153.76 |
September | 19194.35 | 05-SEP-08:61 | 1583.79 | 9174.77 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 162.47 |
October | 4684.21 | 10-OCT-08:04 | 1583.79 | 9174.77 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 771.07 |
November | 5323.04 | 12-NOV-10:04 | 1583.79 | 9174.77 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 688.13 |
December | 5244.34 | 22-DEC-09:04 | 1583.79 | 9174.77 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 706.33 |
Annual Sum or Average | |||||||||||
Minimum of Months | 3979.68 | 989.87 | 5734.23 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 153.76 | |
Maximum of Months | 19569.82 | 1583.79 | 9174.77 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 894.64 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | |
January | 0.855380E+11 | 68922.88 | 14-JAN-17:19 | 0.171927E+12 | 312435.37 | 09-JAN-09:09 |
February | 0.761495E+11 | 67289.07 | 02-FEB-18:00 | 0.956365E+11 | 259033.83 | 04-FEB-09:09 |
March | 0.837950E+11 | 64792.29 | 08-MAR-18:40 | 0.752745E+11 | 235834.78 | 04-MAR-09:09 |
April | 0.786789E+11 | 60530.75 | 07-APR-13:39 | 0.281965E+11 | 134192.52 | 29-APR-08:09 |
May | 0.823178E+11 | 74160.56 | 20-MAY-15:30 | 0.176056E+11 | 144372.91 | 08-MAY-08:09 |
June | 0.863402E+11 | 81837.76 | 23-JUN-13:00 | 0.396179E+09 | 21944.28 | 16-JUN-11:20 |
July | 0.967806E+11 | 93911.57 | 17-JUL-13:30 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.958369E+11 | 88979.92 | 10-AUG-14:39 | 4614389.48 | 635.06 | 17-AUG-11:30 |
September | 0.864480E+11 | 88402.48 | 02-SEP-13:00 | 0.223943E+10 | 41937.05 | 20-SEP-08:09 |
October | 0.836454E+11 | 70602.61 | 18-OCT-14:50 | 0.102831E+11 | 124020.67 | 10-OCT-08:09 |
November | 0.816909E+11 | 66467.87 | 15-NOV-18:49 | 0.514079E+11 | 205676.88 | 27-NOV-09:09 |
December | 0.852851E+11 | 66045.66 | 26-DEC-18:00 | 0.122339E+12 | 294093.79 | 29-DEC-09:09 |
Annual Sum or Average | 0.102251E+13 | 0.575310E+12 | ||||
Minimum of Months | 0.761495E+11 | 60530.75 | 0.00 | 0.00 | ||
Maximum of Months | 0.967806E+11 | 93911.57 | 0.171927E+12 | 312435.37 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.424448E+11 | 0.102745E+11 | 0.108804E+11 | 0.00 | 0.161480E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.579026E+10 | 0.00 |
February | 0.384292E+11 | 0.836953E+10 | 0.985143E+10 | 0.00 | 0.142418E+11 | 0.00 | 0.00 | 345754.02 | 0.00 | 0.00 | 0.00 | 0.525719E+10 | 0.00 |
March | 0.430726E+11 | 0.799109E+10 | 0.110523E+11 | 0.00 | 0.158319E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.584711E+10 | 0.00 |
April | 0.411878E+11 | 0.644497E+10 | 0.105581E+11 | 0.00 | 0.148782E+11 | 0.00 | 0.00 | 71733502.67 | 0.00 | 0.00 | 0.00 | 0.553821E+10 | 0.00 |
May | 0.427427E+11 | 0.556163E+10 | 0.109629E+11 | 0.00 | 0.155026E+11 | 0.00 | 0.00 | 0.192264E+10 | 0.00 | 0.00 | 0.00 | 0.562525E+10 | 0.00 |
June | 0.416347E+11 | 0.486515E+10 | 0.106818E+11 | 0.00 | 0.151343E+11 | 0.00 | 0.00 | 0.868968E+10 | 0.00 | 0.00 | 0.00 | 0.533455E+10 | 0.00 |
July | 0.423277E+11 | 0.523654E+10 | 0.108460E+11 | 0.00 | 0.154184E+11 | 0.00 | 0.00 | 0.175710E+11 | 0.00 | 0.00 | 0.00 | 0.538086E+10 | 0.00 |
August | 0.430407E+11 | 0.614521E+10 | 0.110454E+11 | 0.00 | 0.157240E+11 | 0.00 | 0.00 | 0.144819E+11 | 0.00 | 0.00 | 0.00 | 0.539971E+10 | 0.00 |
September | 0.412197E+11 | 0.716999E+10 | 0.105649E+11 | 0.00 | 0.149670E+11 | 0.00 | 0.00 | 0.729760E+10 | 0.00 | 0.00 | 0.00 | 0.522880E+10 | 0.00 |
October | 0.424448E+11 | 0.873277E+10 | 0.108804E+11 | 0.00 | 0.153240E+11 | 0.00 | 0.00 | 0.785410E+09 | 0.00 | 0.00 | 0.00 | 0.547800E+10 | 0.00 |
November | 0.411240E+11 | 0.961589E+10 | 0.105443E+11 | 0.00 | 0.149850E+11 | 0.00 | 0.00 | 1351329.43 | 0.00 | 0.00 | 0.00 | 0.542036E+10 | 0.00 |
December | 0.423596E+11 | 0.106037E+11 | 0.108529E+11 | 0.00 | 0.157602E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.570872E+10 | 0.00 |
Annual Sum or Average | 0.502028E+12 | 0.910109E+11 | 0.128721E+12 | 0.183915E+12 | 0.00 | 0.508217E+11 | 0.660090E+11 | ||||||
Minimum of Months | 0.384292E+11 | 0.486515E+10 | 0.985143E+10 | 0.00 | 0.142418E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.522880E+10 | 0.00 |
Maximum of Months | 0.430726E+11 | 0.106037E+11 | 0.110523E+11 | 0.00 | 0.161480E+11 | 0.00 | 0.00 | 0.175710E+11 | 0.00 | 0.00 | 0.00 | 0.584711E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS [J] | COOLING:GAS [] | WATERSYSTEMS:GAS [] | COGENERATION:GAS [] | HUMIDIFIER:GAS [] | |
January | 0.00 | 0.00 | 0.171927E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.956365E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.752745E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.281965E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.176056E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.396179E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 4614389.48 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.223943E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.102831E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.514079E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.122339E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.575310E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.171927E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum}[W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum}[W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum}[W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum}[W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 31196.17 | 01-JAN-11:09 | 6944.63 | 01-JAN-06:10 | 8089.53 | 01-JAN-11:09 | 0.00 | 12470.16 | 09-JAN-09:09 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 31196.17 | 01-FEB-10:09 | 6944.63 | 01-FEB-06:10 | 8089.53 | 01-FEB-10:09 | 0.00 | 12211.44 | 04-FEB-09:09 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 31196.17 | 01-MAR-10:09 | 6944.63 | 01-MAR-06:10 | 8089.53 | 01-MAR-10:09 | 0.00 | 12087.62 | 04-MAR-09:09 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 31196.17 | 01-APR-09:09 | 6944.63 | 01-APR-05:10 | 8089.53 | 01-APR-09:09 | 0.00 | 11564.13 | 29-APR-08:09 | 0.00 | 0.00 | 01-APR-00:10 |
May | 31196.17 | 01-MAY-09:09 | 6944.63 | 01-MAY-05:10 | 8089.53 | 01-MAY-09:09 | 0.00 | 11593.88 | 08-MAY-08:09 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 31196.17 | 01-JUN-09:09 | 6944.63 | 01-JUN-20:10 | 8089.53 | 01-JUN-09:09 | 0.00 | 11177.06 | 22-JUN-08:09 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 31196.17 | 01-JUL-09:09 | 6944.63 | 01-JUL-20:30 | 8089.53 | 01-JUL-09:09 | 0.00 | 12014.86 | 17-JUL-16:10 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 31196.17 | 01-AUG-09:09 | 6944.63 | 01-AUG-19:00 | 8089.53 | 01-AUG-09:09 | 0.00 | 11641.17 | 06-AUG-15:00 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 31196.17 | 01-SEP-09:09 | 6944.63 | 01-SEP-05:10 | 8089.53 | 01-SEP-09:09 | 0.00 | 11581.73 | 02-SEP-14:00 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 31196.17 | 01-OCT-10:09 | 6944.63 | 01-OCT-05:10 | 8089.53 | 01-OCT-10:09 | 0.00 | 11467.03 | 10-OCT-08:09 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 31196.17 | 01-NOV-09:09 | 6944.63 | 01-NOV-05:10 | 8089.53 | 01-NOV-09:09 | 0.00 | 11899.86 | 27-NOV-09:09 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 31196.17 | 01-DEC-10:09 | 6944.63 | 01-DEC-06:10 | 8089.53 | 01-DEC-10:09 | 0.00 | 12394.85 | 29-DEC-09:09 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 31196.17 | 6944.63 | 8089.53 | 0.00 | 11177.06 | 0.00 | 0.00 | |||||
Maximum of Months | 31196.17 | 6944.63 | 8089.53 | 0.00 | 12470.16 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum}[W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum}[W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 13109.68 | 07-JAN-13:09 | 0.00 |
February | 107.97 | 28-FEB-22:40 | 0.00 | 0.00 | 0.00 | 9962.81 | 04-FEB-13:09 | 0.00 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 10160.51 | 22-MAR-12:09 | 0.00 |
April | 5858.43 | 07-APR-13:00 | 0.00 | 0.00 | 0.00 | 9746.77 | 06-APR-13:00 | 0.00 |
May | 19644.86 | 20-MAY-15:00 | 0.00 | 0.00 | 0.00 | 9740.09 | 11-MAY-12:30 | 0.00 |
June | 24675.18 | 29-JUN-14:00 | 0.00 | 0.00 | 0.00 | 9560.81 | 29-JUN-04:10 | 0.00 |
July | 38610.04 | 17-JUL-16:10 | 0.00 | 0.00 | 0.00 | 7591.07 | 01-JUL-13:39 | 0.00 |
August | 33890.25 | 06-AUG-15:00 | 0.00 | 0.00 | 0.00 | 9690.76 | 28-AUG-11:09 | 0.00 |
September | 32778.36 | 02-SEP-14:00 | 0.00 | 0.00 | 0.00 | 9709.08 | 09-SEP-13:09 | 0.00 |
October | 15408.67 | 18-OCT-14:39 | 0.00 | 0.00 | 0.00 | 11810.98 | 14-OCT-14:50 | 0.00 |
November | 321.15 | 04-NOV-19:30 | 0.00 | 0.00 | 0.00 | 9712.82 | 28-NOV-15:09 | 0.00 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 9749.94 | 26-DEC-13:30 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 7591.07 | 0.00 | ||
Maximum of Months | 38610.04 | 0.00 | 0.00 | 0.00 | 13109.68 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 68922.88 | 14-JAN-17:19 | 31196.17 | 8089.53 | 6944.63 | 0.00 | 10859.69 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 67289.07 | 02-FEB-18:00 | 31196.17 | 8089.53 | 6944.63 | 0.00 | 11349.29 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 64792.29 | 08-MAR-18:40 | 31196.17 | 8089.53 | 6944.63 | 0.00 | 10975.73 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 60530.75 | 07-APR-13:39 | 31196.17 | 8089.53 | 0.00 | 0.00 | 10675.61 | 0.00 | 0.00 | 4880.88 | 0.00 |
May | 74160.56 | 20-MAY-15:30 | 31196.17 | 8089.53 | 0.00 | 0.00 | 10675.61 | 0.00 | 0.00 | 18742.80 | 0.00 |
June | 81837.76 | 23-JUN-13:00 | 31196.17 | 8089.53 | 0.00 | 0.00 | 10795.66 | 0.00 | 0.00 | 24330.56 | 0.00 |
July | 93911.57 | 17-JUL-13:30 | 31196.17 | 8089.53 | 0.00 | 0.00 | 11794.77 | 0.00 | 0.00 | 36558.06 | 0.00 |
August | 88979.92 | 10-AUG-14:39 | 31196.17 | 8089.53 | 0.00 | 0.00 | 11456.90 | 0.00 | 0.00 | 30936.98 | 0.00 |
September | 88402.48 | 02-SEP-13:00 | 31196.17 | 8089.53 | 0.00 | 0.00 | 11533.08 | 0.00 | 0.00 | 32120.46 | 0.00 |
October | 70602.61 | 18-OCT-14:50 | 31196.17 | 8089.53 | 0.00 | 0.00 | 10675.61 | 0.00 | 0.00 | 15391.16 | 0.00 |
November | 66467.87 | 15-NOV-18:49 | 31196.17 | 8089.53 | 6944.63 | 0.00 | 10836.88 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 66045.66 | 26-DEC-18:00 | 31196.17 | 8089.53 | 6944.63 | 0.00 | 11151.83 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 60530.75 | 31196.17 | 8089.53 | 0.00 | 0.00 | 10675.61 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 93911.57 | 31196.17 | 8089.53 | 6944.63 | 0.00 | 11794.77 | 0.00 | 0.00 | 36558.06 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS {Maximum}[W] | HEATING:GAS {TIMESTAMP} | COOLING:GAS [] | WATERSYSTEMS:GAS [] | COGENERATION:GAS [] | |
January | 0.00 | 0.00 | 312435.37 | 09-JAN-09:09 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 259033.83 | 04-FEB-09:09 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 235834.78 | 04-MAR-09:09 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 134192.52 | 29-APR-08:09 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 144372.91 | 08-MAY-08:09 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 21944.28 | 16-JUN-11:20 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 635.06 | 17-AUG-11:30 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 41937.05 | 20-SEP-08:09 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 124020.67 | 10-OCT-08:09 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 205676.88 | 27-NOV-09:09 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 294093.79 | 29-DEC-09:09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 312435.37 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.83 | 20.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 1.00 | 20.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.50 | 20.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.17 | 20.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1.00 | 20.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1.17 | 20.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 5.67 | 20.40 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.83 | 20.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.17 | 20.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.17 | 20.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.33 | 20.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.33 | 20.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.17 | 20.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2.17 | 20.43 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.17 | 20.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 14.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.17 | 14.98 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 14.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 18.83 | 14.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 2.67 | 14.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 3.33 | 14.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.17 | 14.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 2.50 | 14.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 27.50 | 14.84 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 18.83 | 14.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: LGSTORE1
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 496.00 | 20.94 | 386.33 | 20.89 | 386.33 | 20.89 |
February | 448.00 | 21.04 | 238.17 | 20.83 | 238.17 | 20.83 |
March | 496.00 | 20.99 | 204.83 | 20.79 | 204.83 | 20.79 |
April | 480.00 | 21.57 | 77.67 | 20.72 | 77.67 | 20.72 |
May | 383.50 | 21.94 | 48.83 | 21.47 | 35.67 | 20.58 |
June | 130.17 | 23.08 | 131.67 | 23.91 | 0.00 | 0.00 |
July | 21.33 | 23.59 | 280.67 | 23.93 | 0.67 | 23.89 |
August | 48.67 | 23.12 | 175.33 | 23.93 | 0.00 | 0.00 |
September | 193.33 | 22.44 | 146.33 | 23.88 | 6.83 | 23.17 |
October | 404.33 | 22.12 | 10.50 | 20.58 | 10.50 | 20.58 |
November | 480.00 | 21.31 | 122.67 | 20.86 | 122.67 | 20.86 |
December | 496.00 | 20.95 | 327.50 | 20.87 | 327.50 | 20.87 |
Annual Sum or Average | 4077.33 | 21.47 | 2150.50 | 21.91 | 1410.83 | 20.85 |
Minimum of Months | 21.33 | 20.94 | 10.50 | 20.58 | 0.00 | 0.00 |
Maximum of Months | 496.00 | 23.59 | 386.33 | 23.93 | 386.33 | 23.89 |
Report: ComfortReportSimple55Monthly
For: SMSTORE1
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 496.00 | 21.23 | 286.00 | 20.97 | 286.00 | 20.97 |
February | 448.00 | 21.63 | 147.33 | 20.98 | 147.33 | 20.98 |
March | 496.00 | 21.62 | 93.50 | 20.96 | 93.50 | 20.96 |
April | 470.33 | 22.54 | 9.33 | 21.03 | 9.33 | 21.03 |
May | 338.67 | 22.61 | 22.17 | 22.90 | 7.17 | 20.83 |
June | 75.50 | 23.42 | 135.67 | 23.94 | 0.00 | 0.00 |
July | 15.17 | 23.53 | 263.67 | 23.97 | 0.00 | 0.00 |
August | 44.17 | 23.38 | 164.33 | 23.99 | 0.00 | 0.00 |
September | 141.00 | 22.98 | 141.67 | 23.93 | 5.67 | 23.89 |
October | 321.33 | 22.87 | 0.83 | 20.95 | 0.83 | 20.95 |
November | 475.83 | 22.16 | 47.17 | 20.92 | 47.17 | 20.92 |
December | 496.00 | 21.37 | 167.17 | 20.97 | 167.17 | 20.97 |
Annual Sum or Average | 3818.00 | 22.02 | 1478.83 | 22.42 | 764.17 | 20.99 |
Minimum of Months | 15.17 | 21.23 | 0.83 | 20.92 | 0.00 | 0.00 |
Maximum of Months | 496.00 | 23.53 | 286.00 | 23.99 | 286.00 | 23.89 |
Report: ComfortReportSimple55Monthly
For: SMSTORE2
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 371.00 | 21.11 | 264.50 | 21.11 | 264.50 | 21.11 |
February | 336.00 | 21.34 | 143.17 | 21.11 | 143.17 | 21.11 |
March | 379.00 | 21.22 | 109.83 | 21.11 | 109.83 | 21.11 |
April | 357.17 | 22.04 | 18.67 | 21.11 | 18.67 | 21.11 |
May | 266.17 | 22.18 | 30.50 | 23.13 | 12.00 | 21.11 |
June | 52.50 | 23.10 | 127.50 | 24.16 | 0.00 | 0.00 |
July | 6.67 | 24.32 | 226.67 | 24.17 | 0.83 | 28.51 |
August | 24.17 | 23.47 | 159.50 | 24.21 | 0.83 | 28.86 |
September | 109.17 | 22.62 | 118.67 | 24.13 | 6.67 | 24.59 |
October | 248.33 | 22.35 | 3.17 | 22.03 | 2.50 | 21.11 |
November | 357.17 | 21.66 | 68.33 | 21.11 | 68.33 | 21.11 |
December | 369.00 | 21.12 | 198.33 | 21.11 | 198.33 | 21.11 |
Annual Sum or Average | 2876.33 | 21.66 | 1468.83 | 22.47 | 825.67 | 21.15 |
Minimum of Months | 6.67 | 21.11 | 3.17 | 21.11 | 0.00 | 0.00 |
Maximum of Months | 379.00 | 24.32 | 264.50 | 24.21 | 264.50 | 28.86 |
Report: ComfortReportSimple55Monthly
For: SMSTORE3
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 371.00 | 21.11 | 286.00 | 21.11 | 286.00 | 21.11 |
February | 336.00 | 21.31 | 157.67 | 21.11 | 157.67 | 21.11 |
March | 379.00 | 21.20 | 121.67 | 21.11 | 121.67 | 21.11 |
April | 360.00 | 21.98 | 30.00 | 21.11 | 30.00 | 21.11 |
May | 275.00 | 22.18 | 31.17 | 22.76 | 16.00 | 21.11 |
June | 54.50 | 23.10 | 125.83 | 24.16 | 0.00 | 0.00 |
July | 6.83 | 24.30 | 227.33 | 24.17 | 0.83 | 28.53 |
August | 24.83 | 23.46 | 161.33 | 24.21 | 0.83 | 28.87 |
September | 117.50 | 22.65 | 117.33 | 24.13 | 6.67 | 24.59 |
October | 261.17 | 22.35 | 3.67 | 21.89 | 3.00 | 21.11 |
November | 358.50 | 21.60 | 81.67 | 21.11 | 81.67 | 21.11 |
December | 369.00 | 21.11 | 214.17 | 21.11 | 214.17 | 21.11 |
Annual Sum or Average | 2913.33 | 21.65 | 1557.83 | 22.38 | 918.50 | 21.15 |
Minimum of Months | 6.83 | 21.11 | 3.67 | 21.11 | 0.00 | 0.00 |
Maximum of Months | 379.00 | 24.30 | 286.00 | 24.21 | 286.00 | 28.87 |
Report: ComfortReportSimple55Monthly
For: SMSTORE4
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 371.00 | 21.11 | 301.67 | 21.11 | 301.67 | 21.11 |
February | 336.00 | 21.27 | 176.17 | 21.11 | 176.17 | 21.11 |
March | 379.00 | 21.17 | 138.83 | 21.11 | 138.83 | 21.11 |
April | 360.00 | 21.87 | 39.83 | 21.11 | 39.83 | 21.11 |
May | 285.83 | 22.14 | 34.67 | 22.35 | 22.17 | 21.11 |
June | 68.50 | 23.17 | 118.50 | 24.16 | 0.00 | 0.00 |
July | 8.17 | 24.17 | 218.67 | 24.17 | 0.83 | 28.49 |
August | 28.00 | 23.38 | 151.17 | 24.22 | 0.67 | 29.01 |
September | 132.50 | 22.67 | 114.00 | 24.13 | 6.83 | 24.57 |
October | 282.83 | 22.34 | 5.00 | 21.25 | 4.83 | 21.11 |
November | 360.00 | 21.50 | 92.00 | 21.11 | 92.00 | 21.11 |
December | 369.00 | 21.11 | 230.83 | 21.11 | 230.83 | 21.11 |
Annual Sum or Average | 2980.83 | 21.64 | 1621.33 | 22.27 | 1014.67 | 21.14 |
Minimum of Months | 8.17 | 21.11 | 5.00 | 21.11 | 0.00 | 0.00 |
Maximum of Months | 379.00 | 24.17 | 301.67 | 24.22 | 301.67 | 29.01 |
Report: ComfortReportSimple55Monthly
For: LGSTORE2
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.11 | 309.50 | 21.11 | 309.50 | 21.11 |
February | 308.00 | 21.18 | 217.83 | 21.11 | 217.83 | 21.11 |
March | 348.00 | 21.11 | 166.00 | 21.11 | 166.00 | 21.11 |
April | 330.00 | 21.56 | 52.33 | 21.11 | 52.33 | 21.11 |
May | 284.50 | 21.93 | 39.50 | 21.45 | 35.33 | 21.11 |
June | 98.17 | 23.12 | 81.17 | 23.97 | 0.00 | 0.00 |
July | 11.67 | 23.79 | 175.17 | 24.00 | 0.67 | 28.25 |
August | 33.50 | 22.99 | 116.83 | 24.00 | 0.33 | 29.11 |
September | 149.67 | 22.46 | 94.33 | 24.02 | 6.33 | 24.17 |
October | 303.33 | 22.13 | 6.67 | 21.11 | 6.67 | 21.11 |
November | 330.00 | 21.24 | 114.00 | 21.11 | 114.00 | 21.11 |
December | 338.00 | 21.11 | 257.50 | 21.11 | 257.50 | 21.11 |
Annual Sum or Average | 2874.83 | 21.54 | 1630.83 | 21.94 | 1166.50 | 21.13 |
Minimum of Months | 11.67 | 21.11 | 6.67 | 21.11 | 0.00 | 0.00 |
Maximum of Months | 348.00 | 23.79 | 309.50 | 24.02 | 309.50 | 29.11 |
Report: ComfortReportSimple55Monthly
For: SMSTORE5
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.11 | 311.00 | 21.11 | 311.00 | 21.11 |
February | 308.00 | 21.22 | 221.67 | 21.11 | 221.67 | 21.11 |
March | 348.00 | 21.13 | 172.33 | 21.11 | 172.33 | 21.11 |
April | 330.00 | 21.72 | 55.67 | 21.11 | 55.67 | 21.11 |
May | 290.50 | 22.17 | 40.17 | 21.37 | 37.33 | 21.11 |
June | 97.33 | 23.36 | 71.33 | 24.02 | 0.00 | 0.00 |
July | 12.33 | 23.98 | 152.00 | 24.04 | 0.67 | 28.42 |
August | 33.50 | 23.29 | 92.50 | 24.05 | 0.33 | 29.21 |
September | 147.50 | 22.71 | 85.33 | 24.06 | 7.00 | 24.22 |
October | 307.17 | 22.41 | 7.00 | 21.11 | 7.00 | 21.11 |
November | 330.00 | 21.35 | 117.00 | 21.11 | 117.00 | 21.11 |
December | 338.00 | 21.11 | 261.33 | 21.11 | 261.33 | 21.11 |
Annual Sum or Average | 2882.33 | 21.66 | 1587.33 | 21.86 | 1191.33 | 21.13 |
Minimum of Months | 12.33 | 21.11 | 7.00 | 21.11 | 0.00 | 0.00 |
Maximum of Months | 348.00 | 23.98 | 311.00 | 24.06 | 311.00 | 29.21 |
Report: ComfortReportSimple55Monthly
For: SMSTORE6
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.11 | 313.00 | 21.11 | 313.00 | 21.11 |
February | 308.00 | 21.21 | 229.33 | 21.11 | 229.33 | 21.11 |
March | 348.00 | 21.13 | 183.83 | 21.11 | 183.83 | 21.11 |
April | 330.00 | 21.69 | 62.67 | 21.11 | 62.67 | 21.11 |
May | 297.50 | 22.18 | 42.00 | 21.23 | 41.00 | 21.11 |
June | 106.83 | 23.38 | 66.50 | 24.02 | 0.00 | 0.00 |
July | 13.50 | 23.96 | 146.00 | 24.04 | 0.67 | 28.40 |
August | 35.50 | 23.30 | 88.67 | 24.05 | 0.33 | 29.18 |
September | 149.17 | 22.70 | 84.17 | 24.06 | 7.17 | 24.15 |
October | 311.67 | 22.41 | 7.83 | 21.11 | 7.83 | 21.11 |
November | 330.00 | 21.34 | 122.67 | 21.11 | 122.67 | 21.11 |
December | 338.00 | 21.11 | 268.50 | 21.11 | 268.50 | 21.11 |
Annual Sum or Average | 2908.17 | 21.67 | 1615.17 | 21.81 | 1237.00 | 21.13 |
Minimum of Months | 13.50 | 21.11 | 7.83 | 21.11 | 0.00 | 0.00 |
Maximum of Months | 348.00 | 23.96 | 313.00 | 24.06 | 313.00 | 29.18 |
Report: ComfortReportSimple55Monthly
For: SMSTORE7
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.11 | 319.17 | 21.11 | 319.17 | 21.11 |
February | 308.00 | 21.18 | 253.83 | 21.11 | 253.83 | 21.11 |
March | 348.00 | 21.12 | 224.33 | 21.11 | 224.33 | 21.11 |
April | 330.00 | 21.60 | 93.50 | 21.11 | 93.50 | 21.11 |
May | 309.83 | 22.14 | 53.17 | 21.19 | 52.33 | 21.11 |
June | 122.33 | 23.34 | 56.67 | 24.03 | 0.00 | 0.00 |
July | 18.17 | 23.84 | 134.50 | 24.05 | 0.50 | 28.49 |
August | 42.50 | 23.29 | 78.83 | 24.06 | 0.33 | 29.13 |
September | 157.50 | 22.65 | 80.67 | 24.04 | 7.83 | 23.95 |
October | 324.83 | 22.35 | 12.00 | 21.11 | 12.00 | 21.11 |
November | 330.00 | 21.28 | 143.00 | 21.11 | 143.00 | 21.11 |
December | 338.00 | 21.11 | 287.67 | 21.11 | 287.67 | 21.11 |
Annual Sum or Average | 2969.17 | 21.66 | 1737.33 | 21.70 | 1394.50 | 21.13 |
Minimum of Months | 18.17 | 21.11 | 12.00 | 21.11 | 0.00 | 0.00 |
Maximum of Months | 348.00 | 23.84 | 319.17 | 24.06 | 319.17 | 29.13 |
Report: ComfortReportSimple55Monthly
For: SMSTORE8
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.11 | 335.00 | 21.11 | 335.00 | 21.11 |
February | 308.00 | 21.15 | 279.33 | 21.11 | 279.33 | 21.11 |
March | 348.00 | 21.11 | 306.50 | 21.11 | 306.50 | 21.11 |
April | 330.00 | 21.45 | 191.00 | 21.11 | 191.00 | 21.11 |
May | 328.00 | 22.06 | 99.50 | 21.14 | 98.83 | 21.11 |
June | 161.17 | 23.21 | 47.17 | 24.01 | 0.17 | 21.08 |
July | 35.17 | 23.69 | 113.83 | 24.07 | 0.67 | 28.40 |
August | 66.00 | 23.29 | 74.17 | 24.07 | 0.33 | 29.25 |
September | 175.17 | 22.58 | 78.33 | 23.93 | 11.17 | 23.21 |
October | 334.83 | 22.18 | 30.00 | 21.11 | 30.00 | 21.11 |
November | 330.00 | 21.21 | 195.17 | 21.11 | 195.17 | 21.11 |
December | 338.00 | 21.11 | 325.83 | 21.11 | 325.83 | 21.11 |
Annual Sum or Average | 3094.33 | 21.64 | 2075.83 | 21.55 | 1774.00 | 21.12 |
Minimum of Months | 35.17 | 21.11 | 30.00 | 21.11 | 0.17 | 21.08 |
Maximum of Months | 348.00 | 23.69 | 335.00 | 24.07 | 335.00 | 29.25 |
Report: OccupantComfortDataSummaryMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 496.00000 | 20.91265 | 10.70470 | -0.7026 | 16.22126 |
February | 448.00000 | 21.02780 | 13.96534 | -0.5966 | 13.42543 |
March | 496.00000 | 20.97248 | 15.69581 | -0.5739 | 12.48838 |
April | 480.00000 | 21.56620 | 20.83896 | -0.3663 | 9.07760 |
May | 496.00000 | 22.36987 | 24.34748 | -1.1755 | 37.05745 |
June | 480.00000 | 23.67338 | 31.09239 | -0.6152 | 14.10148 |
July | 496.00000 | 23.91033 | 33.66241 | -0.4617 | 9.68907 |
August | 496.00000 | 23.83943 | 30.28584 | -0.5157 | 11.11042 |
September | 480.00000 | 23.31647 | 31.41708 | -0.7141 | 18.57625 |
October | 496.00000 | 22.44577 | 22.99992 | -0.0775 | 6.78189 |
November | 480.00000 | 21.30110 | 17.18385 | -0.4411 | 10.03816 |
December | 496.00000 | 20.93880 | 13.01019 | -0.6339 | 14.07564 |
Annual Sum or Average | 5840.00000 | 22.19606 | 22.13396 | -0.5731 | 14.41059 |
Minimum of Months | 448.00000 | 20.91265 | 10.70470 | -1.1755 | 6.78189 |
Maximum of Months | 496.00000 | 23.91033 | 33.66241 | -0.0775 | 37.05745 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 496.00000 | 21.20208 | 11.78884 | -0.5867 | 13.15711 |
February | 448.00000 | 21.60923 | 14.60655 | -0.4357 | 10.37401 |
March | 496.00000 | 21.59455 | 16.53945 | -0.4041 | 9.21780 |
April | 480.00000 | 22.54631 | 20.57709 | -0.1382 | 6.71572 |
May | 496.00000 | 22.99416 | 23.96142 | -0.9700 | 27.60598 |
June | 480.00000 | 23.81966 | 30.82409 | -0.5600 | 12.12238 |
July | 496.00000 | 23.90451 | 33.71535 | -0.4628 | 9.72591 |
August | 496.00000 | 23.87087 | 30.22633 | -0.5055 | 10.66421 |
September | 480.00000 | 23.62478 | 31.02802 | -0.6207 | 14.61671 |
October | 496.00000 | 23.22069 | 22.37798 | 0.08678 | 6.26747 |
November | 480.00000 | 22.15601 | 17.38123 | -0.2456 | 7.77923 |
December | 496.00000 | 21.34297 | 14.02033 | -0.5073 | 11.06223 |
Annual Sum or Average | 5840.00000 | 22.66161 | 22.28717 | -0.4465 | 11.63347 |
Minimum of Months | 448.00000 | 21.20208 | 11.78884 | -0.9700 | 6.26747 |
Maximum of Months | 496.00000 | 23.90451 | 33.71535 | 0.08678 | 27.60598 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 21.08383 | 10.32328 | -0.6420 | 14.04967 |
February | 336.00000 | 21.32315 | 13.18717 | -0.5147 | 11.43348 |
March | 379.00000 | 21.21457 | 15.36748 | -0.4917 | 10.43203 |
April | 360.00000 | 22.04984 | 19.84886 | -0.2434 | 7.59418 |
May | 375.00000 | 22.71137 | 23.23760 | -1.0649 | 32.29101 |
June | 366.00000 | 23.88311 | 30.49201 | -0.5454 | 12.14741 |
July | 369.00000 | 24.05746 | 33.21573 | -0.4191 | 9.11204 |
August | 379.00000 | 23.99284 | 29.86897 | -0.4689 | 10.11365 |
September | 360.00000 | 23.57758 | 30.99765 | -0.6345 | 15.89945 |
October | 371.00000 | 22.88246 | 22.11994 | 0.01853 | 6.56937 |
November | 360.00000 | 21.67802 | 16.66010 | -0.3503 | 8.75987 |
December | 369.00000 | 21.10112 | 12.79857 | -0.5775 | 12.29546 |
Annual Sum or Average | 4395.00000 | 22.47125 | 21.56263 | -0.4954 | 12.59245 |
Minimum of Months | 336.00000 | 21.08383 | 10.32328 | -1.0649 | 6.56937 |
Maximum of Months | 379.00000 | 24.05746 | 33.21573 | 0.01853 | 32.29101 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 21.08095 | 10.32603 | -0.6550 | 14.40058 |
February | 336.00000 | 21.28970 | 13.21559 | -0.5335 | 11.77805 |
March | 379.00000 | 21.18702 | 15.39300 | -0.5087 | 10.76679 |
April | 360.00000 | 21.97344 | 19.94444 | -0.2698 | 7.82725 |
May | 375.00000 | 22.66352 | 23.30506 | -1.0907 | 33.43651 |
June | 366.00000 | 23.87711 | 30.50646 | -0.5496 | 12.27843 |
July | 369.00000 | 24.05746 | 33.21703 | -0.4183 | 9.10415 |
August | 379.00000 | 23.99168 | 29.87338 | -0.4688 | 10.12552 |
September | 360.00000 | 23.55661 | 31.03320 | -0.6440 | 16.30381 |
October | 371.00000 | 22.82694 | 22.19411 | -0.0002 | 6.62298 |
November | 360.00000 | 21.60196 | 16.74829 | -0.3775 | 9.07673 |
December | 369.00000 | 21.09461 | 12.80546 | -0.5908 | 12.62684 |
Annual Sum or Average | 4395.00000 | 22.44195 | 21.59949 | -0.5097 | 12.89681 |
Minimum of Months | 336.00000 | 21.08095 | 10.32603 | -1.0907 | 6.62298 |
Maximum of Months | 379.00000 | 24.05746 | 33.21703 | -0.0002 | 33.43651 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 21.07807 | 10.32886 | -0.6694 | 14.80740 |
February | 336.00000 | 21.24986 | 13.25076 | -0.5554 | 12.19775 |
March | 379.00000 | 21.15672 | 15.42199 | -0.5282 | 11.17158 |
April | 360.00000 | 21.86557 | 20.08160 | -0.3057 | 8.17270 |
May | 375.00000 | 22.58174 | 23.42968 | -1.1315 | 35.19359 |
June | 366.00000 | 23.85360 | 30.55308 | -0.5655 | 12.72967 |
July | 369.00000 | 24.05091 | 33.23055 | -0.4263 | 9.24348 |
August | 379.00000 | 23.97843 | 29.89492 | -0.4794 | 10.37391 |
September | 360.00000 | 23.50577 | 31.13324 | -0.6682 | 17.17486 |
October | 371.00000 | 22.72266 | 22.33949 | -0.0320 | 6.67991 |
November | 360.00000 | 21.49625 | 16.87610 | -0.4121 | 9.48360 |
December | 369.00000 | 21.08890 | 12.81174 | -0.6055 | 13.00533 |
Annual Sum or Average | 4395.00000 | 22.39448 | 21.66512 | -0.5323 | 13.38832 |
Minimum of Months | 336.00000 | 21.07807 | 10.32886 | -1.1315 | 6.67991 |
Maximum of Months | 379.00000 | 24.05091 | 33.23055 | -0.0320 | 35.19359 |
Report: OccupantComfortDataSummaryMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.06597 | 11.10949 | -0.7082 | 15.93728 |
February | 308.00000 | 21.14403 | 14.09585 | -0.6069 | 13.27637 |
March | 348.00000 | 21.08179 | 16.33042 | -0.5694 | 12.08664 |
April | 330.00000 | 21.54165 | 21.24275 | -0.3902 | 9.08979 |
May | 344.00000 | 22.26833 | 24.57198 | -1.2443 | 40.12692 |
June | 336.00000 | 23.68236 | 31.32101 | -0.6242 | 14.33445 |
July | 338.00000 | 23.93923 | 33.70673 | -0.4612 | 9.77224 |
August | 348.00000 | 23.84221 | 30.70431 | -0.5204 | 11.33322 |
September | 330.00000 | 23.27606 | 32.16914 | -0.7404 | 19.76305 |
October | 340.00000 | 22.31692 | 23.68907 | -0.1215 | 6.88068 |
November | 330.00000 | 21.22421 | 18.01575 | -0.4883 | 10.55054 |
December | 338.00000 | 21.06981 | 13.62644 | -0.6431 | 14.01703 |
Annual Sum or Average | 4030.00000 | 22.21354 | 22.60235 | -0.5939 | 14.80428 |
Minimum of Months | 308.00000 | 21.06597 | 11.10949 | -1.2443 | 6.88068 |
Maximum of Months | 348.00000 | 23.93923 | 33.70673 | -0.1215 | 40.12692 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.06906 | 11.04492 | -0.7044 | 15.80364 |
February | 308.00000 | 21.18867 | 13.99473 | -0.6013 | 13.19012 |
March | 348.00000 | 21.10601 | 16.23984 | -0.5706 | 12.11092 |
April | 330.00000 | 21.70733 | 20.95406 | -0.3705 | 8.93370 |
May | 344.00000 | 22.44094 | 24.18604 | -1.2162 | 38.80663 |
June | 336.00000 | 23.77246 | 31.14263 | -0.6200 | 14.02759 |
July | 338.00000 | 23.96588 | 33.75581 | -0.4762 | 10.06729 |
August | 348.00000 | 23.88496 | 30.52503 | -0.5319 | 11.45447 |
September | 330.00000 | 23.40907 | 31.94610 | -0.7250 | 18.98404 |
October | 340.00000 | 22.55701 | 23.22879 | -0.0888 | 6.81057 |
November | 330.00000 | 21.33868 | 17.80934 | -0.4745 | 10.41484 |
December | 338.00000 | 21.07409 | 13.55870 | -0.6424 | 13.97697 |
Annual Sum or Average | 4030.00000 | 22.30192 | 22.41885 | -0.5860 | 14.58849 |
Minimum of Months | 308.00000 | 21.06906 | 11.04492 | -1.2162 | 6.81057 |
Maximum of Months | 348.00000 | 23.96588 | 33.75581 | -0.0888 | 38.80663 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.06787 | 11.04637 | -0.7086 | 15.92328 |
February | 308.00000 | 21.17870 | 14.00429 | -0.6082 | 13.34566 |
March | 348.00000 | 21.09970 | 16.24637 | -0.5776 | 12.27936 |
April | 330.00000 | 21.67552 | 20.99542 | -0.3830 | 9.11061 |
May | 344.00000 | 22.41470 | 24.23213 | -1.2311 | 39.47097 |
June | 336.00000 | 23.76263 | 31.17098 | -0.6284 | 14.27157 |
July | 338.00000 | 23.96323 | 33.76422 | -0.4815 | 10.17422 |
August | 348.00000 | 23.88128 | 30.53400 | -0.5374 | 11.58667 |
September | 330.00000 | 23.39647 | 31.97444 | -0.7328 | 19.25444 |
October | 340.00000 | 22.53231 | 23.26684 | -0.0970 | 6.84688 |
November | 330.00000 | 21.32131 | 17.83106 | -0.4826 | 10.56236 |
December | 338.00000 | 21.07333 | 13.55964 | -0.6476 | 14.11738 |
Annual Sum or Average | 4030.00000 | 22.28971 | 22.43882 | -0.5938 | 14.78599 |
Minimum of Months | 308.00000 | 21.06787 | 11.04637 | -1.2311 | 6.84688 |
Maximum of Months | 348.00000 | 23.96323 | 33.76422 | -0.0970 | 39.47097 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.06566 | 11.04908 | -0.7236 | 16.37775 |
February | 308.00000 | 21.14900 | 14.03166 | -0.6320 | 13.90999 |
March | 348.00000 | 21.08324 | 16.26348 | -0.6001 | 12.84646 |
April | 330.00000 | 21.57213 | 21.13054 | -0.4243 | 9.73833 |
May | 344.00000 | 22.31358 | 24.39805 | -1.2843 | 41.88426 |
June | 336.00000 | 23.71607 | 31.28676 | -0.6575 | 15.20990 |
July | 338.00000 | 23.95316 | 33.79642 | -0.4929 | 10.42439 |
August | 348.00000 | 23.86436 | 30.56865 | -0.5512 | 11.98332 |
September | 330.00000 | 23.34029 | 32.09434 | -0.7607 | 20.31929 |
October | 340.00000 | 22.41610 | 23.44016 | -0.1322 | 7.00751 |
November | 330.00000 | 21.26319 | 17.90406 | -0.5097 | 11.06532 |
December | 338.00000 | 21.06916 | 13.56402 | -0.6653 | 14.61711 |
Annual Sum or Average | 4030.00000 | 22.24303 | 22.51398 | -0.6203 | 15.49115 |
Minimum of Months | 308.00000 | 21.06566 | 11.04908 | -1.2843 | 7.00751 |
Maximum of Months | 348.00000 | 23.95316 | 33.79642 | -0.1322 | 41.88426 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.06296 | 10.93742 | -0.7928 | 18.63465 |
February | 308.00000 | 21.10987 | 13.96977 | -0.7100 | 16.10252 |
March | 348.00000 | 21.06639 | 16.13149 | -0.6766 | 14.97489 |
April | 330.00000 | 21.40818 | 21.20356 | -0.5259 | 11.72470 |
May | 344.00000 | 22.12529 | 24.68410 | -1.4123 | 47.81796 |
June | 336.00000 | 23.58057 | 31.54664 | -0.7383 | 18.10216 |
July | 338.00000 | 23.92584 | 33.88747 | -0.5139 | 10.99919 |
August | 348.00000 | 23.81577 | 30.61410 | -0.5814 | 13.04779 |
September | 330.00000 | 23.22152 | 32.19712 | -0.8258 | 23.00982 |
October | 340.00000 | 22.19788 | 23.62706 | -0.2110 | 7.65522 |
November | 330.00000 | 21.17851 | 17.91779 | -0.5802 | 12.65956 |
December | 338.00000 | 21.06397 | 13.48162 | -0.7329 | 16.66617 |
Annual Sum or Average | 4030.00000 | 22.15557 | 22.57045 | -0.6925 | 17.66071 |
Minimum of Months | 308.00000 | 21.06296 | 10.93742 | -1.4123 | 7.65522 |
Maximum of Months | 348.00000 | 23.92584 | 33.88747 | -0.2110 | 47.81796 |
Report: DXReportMonthly
For: PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 652.35 | 184.40 | 1.67 | 652.35 | 0.00 | 0.00 | 0.00 | 27-FEB-15:30 | 0.00 | 01-FEB-00:03 | 0.17 | 27-FEB-15:30 | 0.17 | 27-FEB-15:30 | 0.00 | 01-FEB-00:03 | 0.05 | 27-FEB-15:30 | 0.00 | 01-FEB-00:03 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 44930229.26 | 12386932.73 | 17.66 | 44930229.26 | 0.00 | 0.00 | 0.30 | 07-APR-14:00 | 0.00 | 01-APR-00:05 | 3626.24 | 07-APR-14:00 | 3626.24 | 07-APR-14:00 | 0.00 | 07-APR-17:10 | 988.02 | 07-APR-14:00 | 0.00 | 01-APR-00:05 |
May | 0.160071E+10 | 0.415679E+09 | 121.06 | 0.158855E+10 | 12156042.53 | 0.00 | 0.93 | 20-MAY-08:62 | 0.00 | 01-MAY-00:10 | 13882.30 | 20-MAY-08:62 | 13015.18 | 20-MAY-08:62 | 867.12 | 20-MAY-08:62 | 3391.82 | 20-MAY-16:10 | 0.00 | 01-MAY-00:10 |
June | 0.685468E+10 | 0.174186E+10 | 301.46 | 0.650213E+10 | 0.352550E+09 | 0.00 | 1.00 | 21-JUN-08:61 | 0.00 | 01-JUN-00:10 | 32407.66 | 22-JUN-08:61 | 30586.74 | 23-JUN-08:61 | 5930.37 | 24-JUN-08:62 | 6994.37 | 22-JUN-08:61 | 0.00 | 01-JUN-00:10 |
July | 0.138966E+11 | 0.357110E+10 | 424.60 | 0.134715E+11 | 0.425065E+09 | 0.00 | 1.00 | 01-JUL-08:62 | 0.00 | 01-JUL-00:05 | 33530.85 | 19-JUL-08:61 | 31589.07 | 17-JUL-08:02 | 8993.95 | 19-JUL-08:03 | 7370.23 | 18-JUL-08:61 | 0.00 | 01-JUL-00:05 |
August | 0.113311E+11 | 0.291636E+10 | 396.40 | 0.112351E+11 | 96001766.35 | 0.00 | 1.00 | 01-AUG-08:62 | 0.00 | 01-AUG-00:10 | 31717.55 | 09-AUG-08:61 | 31717.55 | 09-AUG-08:61 | 5036.83 | 01-AUG-08:62 | 7227.99 | 09-AUG-08:61 | 0.00 | 01-AUG-00:10 |
September | 0.623327E+10 | 0.157370E+10 | 245.23 | 0.585621E+10 | 0.377061E+09 | 0.00 | 1.00 | 01-SEP-08:62 | 0.00 | 01-SEP-00:10 | 31834.48 | 07-SEP-08:62 | 30970.34 | 02-SEP-08:62 | 11642.90 | 07-SEP-08:62 | 6777.51 | 07-SEP-08:62 | 0.00 | 01-SEP-00:10 |
October | 0.654754E+09 | 0.168048E+09 | 77.39 | 0.654754E+09 | 8.96 | 0.00 | 0.77 | 18-OCT-14:00 | 0.00 | 01-OCT-00:10 | 10764.98 | 18-OCT-14:00 | 10764.98 | 18-OCT-14:00 | 0.01 | 13-OCT-17:20 | 2643.32 | 18-OCT-14:00 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.406160E+11 | 0.103991E+11 | 1585.46 | 0.393532E+11 | 0.126283E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.138966E+11 | 0.357110E+10 | 424.60 | 0.134715E+11 | 0.425065E+09 | 0.00 | 1.00 | 0.00 | 33530.85 | 31717.55 | 11642.90 | 7370.23 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 1241973.82 | 342949.51 | 7.83 | 1241973.82 | 0.00 | 0.00 | 0.07 | 28-FEB-22:40 | 0.00 | 01-FEB-00:03 | 391.63 | 28-FEB-22:40 | 391.63 | 28-FEB-22:40 | 0.00 | 01-FEB-00:03 | 107.97 | 28-FEB-22:40 | 0.00 | 01-FEB-00:03 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 82914028.55 | 18609847.12 | 40.39 | 82914028.55 | 0.00 | 0.00 | 1.00 | 06-APR-20:02 | 0.00 | 01-APR-00:05 | 16439.98 | 16-APR-17:08 | 16439.98 | 16-APR-17:08 | 0.00 | 07-APR-14:10 | 3211.49 | 06-APR-20:02 | 0.00 | 01-APR-00:05 |
May | 0.128623E+10 | 0.277439E+09 | 129.47 | 0.127826E+10 | 7974018.07 | 0.00 | 1.00 | 02-MAY-20:31 | 0.00 | 01-MAY-00:10 | 16753.69 | 20-MAY-18:17 | 16753.69 | 20-MAY-18:17 | 3085.33 | 20-MAY-21:35 | 3445.54 | 20-MAY-18:17 | 0.00 | 01-MAY-00:10 |
June | 0.458622E+10 | 0.993894E+09 | 285.24 | 0.441008E+10 | 0.176148E+09 | 0.00 | 1.00 | 03-JUN-18:01 | 0.00 | 01-JUN-00:10 | 17543.43 | 21-JUN-20:02 | 16760.92 | 25-JUN-17:47 | 5295.79 | 21-JUN-22:39 | 3541.53 | 18-JUN-19:11 | 0.00 | 01-JUN-00:10 |
July | 0.855892E+10 | 0.189983E+10 | 368.06 | 0.835146E+10 | 0.207463E+09 | 0.00 | 1.00 | 01-JUL-08:62 | 0.00 | 01-JUL-00:05 | 18075.45 | 18-JUL-22:00 | 17103.70 | 18-JUL-08:61 | 7768.09 | 18-JUL-22:00 | 3681.39 | 18-JUL-08:61 | 0.00 | 01-JUL-00:05 |
August | 0.710181E+10 | 0.157426E+10 | 342.24 | 0.706241E+10 | 39405466.10 | 0.00 | 1.00 | 01-AUG-08:62 | 0.00 | 01-AUG-00:10 | 17107.52 | 09-AUG-08:61 | 17107.52 | 09-AUG-08:61 | 3567.65 | 15-AUG-20:30 | 3608.08 | 07-AUG-08:61 | 0.00 | 01-AUG-00:10 |
September | 0.387189E+10 | 0.843218E+09 | 230.46 | 0.369029E+10 | 0.181598E+09 | 0.00 | 1.00 | 01-SEP-08:62 | 0.00 | 01-SEP-00:10 | 17825.06 | 06-SEP-20:02 | 16733.08 | 24-SEP-17:11 | 6319.15 | 06-SEP-23:00 | 3507.65 | 06-SEP-20:02 | 0.00 | 01-SEP-00:10 |
October | 0.459964E+09 | 0.100631E+09 | 101.53 | 0.459916E+09 | 47965.89 | 0.00 | 1.00 | 02-OCT-20:02 | 0.00 | 01-OCT-00:10 | 16439.98 | 15-OCT-17:50 | 16439.98 | 15-OCT-17:50 | 239.83 | 25-OCT-08:63 | 3211.49 | 02-OCT-20:02 | 0.00 | 01-OCT-00:10 |
November | 5739374.68 | 1338097.35 | 14.05 | 5739374.68 | 0.00 | 0.00 | 1.00 | 04-NOV-19:22 | 0.00 | 01-NOV-00:10 | 16439.98 | 04-NOV-19:22 | 16439.98 | 04-NOV-19:22 | 0.00 | 06-NOV-23:10 | 3211.49 | 04-NOV-19:22 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.259549E+11 | 0.570956E+10 | 1519.28 | 0.253423E+11 | 0.612636E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.855892E+10 | 0.189983E+10 | 368.06 | 0.835146E+10 | 0.207463E+09 | 0.00 | 1.00 | 0.00 | 18075.45 | 17107.52 | 7768.09 | 3681.39 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 1234.25 | 304.19 | 5.50 | 1234.25 | 0.00 | 0.00 | 0.00 | 27-FEB-15:30 | 0.00 | 01-FEB-00:03 | 0.14 | 27-FEB-15:30 | 0.14 | 27-FEB-15:30 | 0.00 | 01-FEB-00:03 | 0.03 | 27-FEB-15:30 | 0.00 | 01-FEB-00:03 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 44272571.47 | 10427759.82 | 30.67 | 44272571.47 | 0.00 | 0.00 | 0.41 | 07-APR-14:00 | 0.00 | 01-APR-00:05 | 3069.45 | 07-APR-14:00 | 3069.45 | 07-APR-14:00 | 0.00 | 07-APR-13:30 | 705.96 | 07-APR-14:00 | 0.00 | 01-APR-00:05 |
May | 0.776409E+09 | 0.173812E+09 | 108.54 | 0.774422E+09 | 1987612.62 | 0.00 | 1.00 | 20-MAY-07:02 | 0.00 | 01-MAY-00:10 | 16463.83 | 20-MAY-07:02 | 15318.82 | 20-MAY-07:02 | 2669.81 | 30-MAY-07:02 | 3219.00 | 20-MAY-07:02 | 0.00 | 01-MAY-00:10 |
June | 0.330800E+10 | 0.732282E+09 | 248.93 | 0.320456E+10 | 0.103442E+09 | 0.00 | 1.00 | 01-JUN-07:02 | 0.00 | 01-JUN-00:10 | 17325.27 | 22-JUN-07:01 | 16396.45 | 29-JUN-07:02 | 4610.70 | 04-JUN-08:62 | 3404.09 | 22-JUN-07:01 | 0.00 | 01-JUN-00:10 |
July | 0.639486E+10 | 0.143916E+10 | 305.78 | 0.627977E+10 | 0.115095E+09 | 0.00 | 1.00 | 01-JUL-07:02 | 0.00 | 01-JUL-00:05 | 17922.16 | 19-JUL-07:01 | 16946.45 | 18-JUL-07:01 | 6079.06 | 04-JUL-08:62 | 3519.73 | 19-JUL-07:01 | 0.00 | 01-JUL-00:05 |
August | 0.529548E+10 | 0.119204E+10 | 287.58 | 0.527357E+10 | 21908365.07 | 0.00 | 1.00 | 01-AUG-07:01 | 0.00 | 01-AUG-00:10 | 16896.06 | 09-AUG-07:01 | 16865.95 | 06-AUG-08:61 | 3884.09 | 14-AUG-07:02 | 3472.66 | 06-AUG-08:61 | 0.00 | 01-AUG-00:10 |
September | 0.269996E+10 | 0.595704E+09 | 190.70 | 0.257269E+10 | 0.127268E+09 | 0.00 | 1.00 | 01-SEP-07:02 | 0.00 | 01-SEP-00:10 | 17093.35 | 07-SEP-07:01 | 16922.55 | 04-SEP-08:61 | 6126.23 | 07-SEP-07:03 | 3601.46 | 04-SEP-08:61 | 0.00 | 01-SEP-00:10 |
October | 0.355620E+09 | 78871148.27 | 88.26 | 0.355249E+09 | 371012.28 | 0.00 | 0.99 | 19-OCT-07:02 | 0.00 | 01-OCT-00:10 | 16315.41 | 19-OCT-07:02 | 16315.41 | 19-OCT-07:02 | 1336.37 | 01-OCT-08:61 | 3186.14 | 19-OCT-07:02 | 0.00 | 01-OCT-00:10 |
November | 1474.50 | 363.40 | 6.50 | 1474.50 | 0.00 | 0.00 | 0.00 | 04-NOV-14:00 | 0.00 | 01-NOV-00:10 | 0.19 | 04-NOV-14:00 | 0.19 | 04-NOV-14:00 | 0.00 | 01-NOV-00:10 | 0.05 | 04-NOV-14:00 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.188746E+11 | 0.422229E+10 | 1272.45 | 0.185045E+11 | 0.370071E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.639486E+10 | 0.143916E+10 | 305.78 | 0.627977E+10 | 0.127268E+09 | 0.00 | 1.00 | 0.00 | 17922.16 | 16946.45 | 6126.23 | 3601.46 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 731.04 | 180.17 | 3.17 | 731.04 | 0.00 | 0.00 | 0.00 | 27-FEB-15:30 | 0.00 | 01-FEB-00:03 | 0.13 | 27-FEB-15:30 | 0.13 | 27-FEB-15:30 | 0.00 | 27-FEB-15:30 | 0.03 | 27-FEB-15:30 | 0.00 | 01-FEB-00:03 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 37874608.75 | 8962830.16 | 28.67 | 37874608.75 | 0.00 | 0.00 | 0.39 | 07-APR-14:00 | 0.00 | 01-APR-00:05 | 2904.47 | 07-APR-14:00 | 2904.47 | 07-APR-14:00 | 0.00 | 06-APR-16:00 | 671.98 | 07-APR-14:00 | 0.00 | 01-APR-00:05 |
May | 0.750487E+09 | 0.168542E+09 | 106.75 | 0.748711E+09 | 1776137.82 | 0.00 | 1.00 | 20-MAY-07:02 | 0.00 | 01-MAY-00:10 | 16517.64 | 20-MAY-07:02 | 15362.64 | 20-MAY-07:02 | 2446.41 | 30-MAY-07:02 | 3229.43 | 20-MAY-07:02 | 0.00 | 01-MAY-00:10 |
June | 0.328687E+10 | 0.728502E+09 | 248.10 | 0.318445E+10 | 0.102416E+09 | 0.00 | 1.00 | 01-JUN-07:02 | 0.00 | 01-JUN-00:10 | 17384.49 | 22-JUN-07:01 | 16452.32 | 29-JUN-07:02 | 4507.23 | 04-JUN-08:62 | 3415.73 | 22-JUN-07:01 | 0.00 | 01-JUN-00:10 |
July | 0.641595E+10 | 0.144400E+10 | 305.84 | 0.629994E+10 | 0.116007E+09 | 0.00 | 1.00 | 01-JUL-07:02 | 0.00 | 01-JUL-00:05 | 17984.36 | 19-JUL-07:01 | 17007.59 | 18-JUL-07:01 | 6096.52 | 04-JUL-08:62 | 3531.90 | 19-JUL-07:01 | 0.00 | 01-JUL-00:05 |
August | 0.530665E+10 | 0.119478E+10 | 287.70 | 0.528476E+10 | 21890133.54 | 0.00 | 1.00 | 01-AUG-07:01 | 0.00 | 01-AUG-00:10 | 16955.25 | 09-AUG-07:01 | 16925.42 | 06-AUG-08:61 | 3889.95 | 14-AUG-07:02 | 3484.87 | 06-AUG-08:61 | 0.00 | 01-AUG-00:10 |
September | 0.269735E+10 | 0.595321E+09 | 188.90 | 0.256945E+10 | 0.127904E+09 | 0.00 | 1.00 | 01-SEP-07:02 | 0.00 | 01-SEP-00:10 | 17153.19 | 07-SEP-07:01 | 16983.95 | 04-SEP-08:61 | 6139.48 | 07-SEP-07:03 | 3614.28 | 04-SEP-08:61 | 0.00 | 01-SEP-00:10 |
October | 0.332248E+09 | 73922097.01 | 83.82 | 0.331973E+09 | 274749.09 | 0.00 | 0.99 | 20-OCT-07:01 | 0.00 | 01-OCT-00:10 | 15246.29 | 19-OCT-07:02 | 15246.29 | 19-OCT-07:02 | 995.55 | 01-OCT-08:61 | 2963.11 | 19-OCT-07:02 | 0.00 | 01-OCT-00:10 |
November | 1255.29 | 309.38 | 5.00 | 1255.29 | 0.00 | 0.00 | 0.00 | 04-NOV-14:00 | 0.00 | 01-NOV-00:10 | 0.18 | 04-NOV-14:00 | 0.18 | 04-NOV-14:00 | 0.00 | 01-NOV-00:10 | 0.04 | 04-NOV-14:00 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.188274E+11 | 0.421403E+10 | 1257.94 | 0.184572E+11 | 0.370268E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.641595E+10 | 0.144400E+10 | 305.84 | 0.629994E+10 | 0.127904E+09 | 0.00 | 1.00 | 0.00 | 17984.36 | 17007.59 | 6139.48 | 3614.28 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 533.88 | 131.58 | 2.33 | 533.88 | 0.00 | 0.00 | 0.00 | 27-FEB-15:30 | 0.00 | 01-FEB-00:03 | 0.11 | 27-FEB-15:30 | 0.11 | 27-FEB-15:30 | 0.00 | 01-FEB-00:03 | 0.03 | 27-FEB-15:30 | 0.00 | 01-FEB-00:03 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 28271230.13 | 6743219.33 | 26.33 | 28271230.13 | 0.00 | 0.00 | 0.36 | 07-APR-14:00 | 0.00 | 01-APR-00:05 | 2589.09 | 07-APR-14:00 | 2589.09 | 07-APR-14:00 | 0.00 | 07-APR-14:00 | 605.17 | 07-APR-14:00 | 0.00 | 01-APR-00:05 |
May | 0.691132E+09 | 0.156134E+09 | 101.97 | 0.689838E+09 | 1294316.30 | 0.00 | 0.98 | 20-MAY-07:02 | 0.00 | 01-MAY-00:10 | 16182.86 | 20-MAY-07:02 | 15021.62 | 20-MAY-07:02 | 1702.92 | 30-MAY-07:02 | 3160.71 | 20-MAY-07:02 | 0.00 | 01-MAY-00:10 |
June | 0.316758E+10 | 0.704473E+09 | 242.74 | 0.306957E+10 | 98006683.12 | 0.00 | 1.00 | 01-JUN-07:02 | 0.00 | 01-JUN-00:10 | 17279.57 | 22-JUN-07:01 | 16357.63 | 29-JUN-07:02 | 4419.77 | 13-JUN-07:02 | 3395.13 | 22-JUN-07:01 | 0.00 | 01-JUN-00:10 |
July | 0.626908E+10 | 0.141400E+10 | 303.58 | 0.615674E+10 | 0.112341E+09 | 0.00 | 1.00 | 01-JUL-07:02 | 0.00 | 01-JUL-00:05 | 17877.95 | 19-JUL-07:01 | 16905.00 | 18-JUL-07:01 | 6079.83 | 04-JUL-08:62 | 3511.12 | 19-JUL-07:01 | 0.00 | 01-JUL-00:05 |
August | 0.517134E+10 | 0.116666E+10 | 285.93 | 0.515061E+10 | 20726877.52 | 0.00 | 1.00 | 01-AUG-07:01 | 0.00 | 01-AUG-00:10 | 16853.87 | 09-AUG-07:01 | 16825.32 | 06-AUG-08:61 | 3887.69 | 14-AUG-07:02 | 3464.30 | 06-AUG-08:61 | 0.00 | 01-AUG-00:10 |
September | 0.261453E+10 | 0.578111E+09 | 181.31 | 0.248958E+10 | 0.124949E+09 | 0.00 | 1.00 | 01-SEP-07:02 | 0.00 | 01-SEP-00:10 | 17051.09 | 07-SEP-07:01 | 16883.90 | 04-SEP-08:61 | 6123.30 | 07-SEP-07:03 | 3593.11 | 04-SEP-08:61 | 0.00 | 01-SEP-00:10 |
October | 0.294658E+09 | 65902276.21 | 76.00 | 0.294571E+09 | 86788.20 | 0.00 | 0.76 | 18-OCT-14:00 | 0.00 | 01-OCT-00:10 | 12113.10 | 19-OCT-07:02 | 12113.10 | 19-OCT-07:02 | 516.16 | 25-OCT-07:02 | 2312.76 | 19-OCT-07:02 | 0.00 | 01-OCT-00:10 |
November | 1029.31 | 253.68 | 4.17 | 1029.31 | 0.00 | 0.00 | 0.00 | 04-NOV-14:00 | 0.00 | 01-NOV-00:10 | 0.15 | 04-NOV-14:00 | 0.15 | 04-NOV-14:00 | 0.00 | 04-NOV-13:50 | 0.04 | 04-NOV-14:00 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.182366E+11 | 0.409202E+10 | 1224.37 | 0.178792E+11 | 0.357404E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.626908E+10 | 0.141400E+10 | 303.58 | 0.615674E+10 | 0.124949E+09 | 0.00 | 1.00 | 0.00 | 17877.95 | 16905.00 | 6123.30 | 3593.11 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 21871252.20 | 6101979.30 | 8.83 | 21871252.20 | 0.00 | 0.00 | 0.23 | 07-APR-14:10 | 0.00 | 01-APR-00:05 | 2660.77 | 07-APR-14:10 | 2660.77 | 07-APR-14:10 | 0.00 | 01-APR-00:05 | 736.49 | 07-APR-14:00 | 0.00 | 01-APR-00:05 |
May | 0.988411E+09 | 0.260881E+09 | 74.45 | 0.982366E+09 | 6045533.46 | 0.00 | 0.85 | 20-MAY-16:00 | 0.00 | 01-MAY-00:10 | 12014.41 | 20-MAY-16:00 | 12014.41 | 20-MAY-16:00 | 705.63 | 20-MAY-08:62 | 3182.08 | 20-MAY-16:00 | 0.00 | 01-MAY-00:10 |
June | 0.513484E+10 | 0.132109E+10 | 222.17 | 0.488344E+10 | 0.251401E+09 | 0.00 | 1.00 | 21-JUN-08:61 | 0.00 | 01-JUN-00:10 | 31634.01 | 22-JUN-08:61 | 29606.93 | 23-JUN-08:61 | 6220.56 | 21-JUN-08:61 | 6839.19 | 23-JUN-08:61 | 0.00 | 01-JUN-00:10 |
July | 0.102999E+11 | 0.267235E+10 | 296.93 | 0.100260E+11 | 0.273895E+09 | 0.00 | 1.00 | 01-JUL-08:62 | 0.00 | 01-JUL-00:05 | 32649.68 | 19-JUL-08:61 | 30805.58 | 18-JUL-08:61 | 8146.88 | 19-JUL-08:03 | 7211.34 | 18-JUL-08:61 | 0.00 | 01-JUL-00:05 |
August | 0.857517E+10 | 0.222393E+10 | 290.20 | 0.850554E+10 | 69627990.69 | 0.00 | 1.00 | 01-AUG-08:62 | 0.00 | 01-AUG-00:10 | 31025.35 | 09-AUG-08:61 | 31025.35 | 09-AUG-08:61 | 4645.32 | 14-AUG-08:62 | 7335.44 | 06-AUG-09:01 | 0.00 | 01-AUG-00:10 |
September | 0.437374E+10 | 0.110631E+10 | 161.63 | 0.407027E+10 | 0.303466E+09 | 0.00 | 1.00 | 01-SEP-08:62 | 0.00 | 01-SEP-00:10 | 31099.66 | 07-SEP-08:62 | 30802.98 | 04-SEP-09:01 | 11170.88 | 07-SEP-08:62 | 7258.49 | 04-SEP-09:01 | 0.00 | 01-SEP-00:10 |
October | 0.438425E+09 | 0.113910E+09 | 50.17 | 0.438425E+09 | 0.00 | 0.00 | 0.72 | 18-OCT-14:30 | 0.00 | 01-OCT-00:10 | 9739.84 | 18-OCT-14:30 | 9739.84 | 18-OCT-14:30 | 0.00 | 18-OCT-12:30 | 2427.88 | 18-OCT-14:30 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.298324E+11 | 0.770458E+10 | 1104.37 | 0.289280E+11 | 0.904435E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.102999E+11 | 0.267235E+10 | 296.93 | 0.100260E+11 | 0.303466E+09 | 0.00 | 1.00 | 0.00 | 32649.68 | 31025.35 | 11170.88 | 7335.44 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 7916.53 | 1950.17 | 1.67 | 7916.53 | 0.00 | 0.00 | 0.00 | 27-FEB-14:30 | 0.00 | 01-FEB-00:03 | 12.67 | 27-FEB-14:30 | 12.67 | 27-FEB-14:30 | 0.00 | 01-FEB-00:03 | 3.12 | 27-FEB-14:30 | 0.00 | 01-FEB-00:03 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 13980721.75 | 3376391.56 | 15.50 | 13980721.75 | 0.00 | 0.00 | 0.28 | 07-APR-14:00 | 0.00 | 01-APR-00:05 | 1864.49 | 07-APR-14:00 | 1864.49 | 07-APR-14:00 | 0.00 | 07-APR-14:30 | 445.16 | 07-APR-14:00 | 0.00 | 01-APR-00:05 |
May | 0.571380E+09 | 0.130464E+09 | 83.21 | 0.570864E+09 | 516751.78 | 0.00 | 0.86 | 20-MAY-16:00 | 0.00 | 01-MAY-00:10 | 10743.53 | 20-MAY-08:62 | 10417.63 | 20-MAY-08:62 | 325.90 | 20-MAY-08:62 | 2041.89 | 20-MAY-08:62 | 0.00 | 01-MAY-00:10 |
June | 0.289003E+10 | 0.647030E+09 | 233.10 | 0.279119E+10 | 98834619.36 | 0.00 | 1.00 | 21-JUN-08:61 | 0.00 | 01-JUN-00:10 | 16335.69 | 22-JUN-08:61 | 15419.69 | 28-JUN-08:62 | 3290.08 | 13-JUN-08:62 | 3258.33 | 23-JUN-08:61 | 0.00 | 01-JUN-00:10 |
July | 0.577434E+10 | 0.131056E+10 | 295.14 | 0.567237E+10 | 0.101970E+09 | 0.00 | 1.00 | 01-JUL-08:62 | 0.00 | 01-JUL-00:05 | 16872.90 | 19-JUL-08:61 | 16007.59 | 18-JUL-08:61 | 4791.48 | 04-JUL-09:02 | 3448.03 | 18-JUL-08:61 | 0.00 | 01-JUL-00:05 |
August | 0.475913E+10 | 0.108028E+10 | 289.47 | 0.474171E+10 | 17412663.73 | 0.00 | 1.00 | 01-AUG-08:62 | 0.00 | 01-AUG-00:10 | 16016.37 | 09-AUG-08:61 | 16016.37 | 09-AUG-08:61 | 3010.66 | 14-AUG-08:62 | 3499.58 | 06-AUG-09:01 | 0.00 | 01-AUG-00:10 |
September | 0.234164E+10 | 0.519265E+09 | 166.01 | 0.221829E+10 | 0.123349E+09 | 0.00 | 1.00 | 01-SEP-08:62 | 0.00 | 01-SEP-00:10 | 16070.75 | 07-SEP-08:62 | 15941.28 | 04-SEP-09:01 | 5761.60 | 07-SEP-08:62 | 3460.65 | 04-SEP-09:01 | 0.00 | 01-SEP-00:10 |
October | 0.233224E+09 | 52510055.86 | 62.37 | 0.233224E+09 | 0.00 | 0.00 | 0.75 | 18-OCT-14:30 | 0.00 | 01-OCT-00:10 | 5789.52 | 18-OCT-14:40 | 5789.52 | 18-OCT-14:40 | 0.00 | 18-OCT-15:20 | 1247.85 | 18-OCT-14:40 | 0.00 | 01-OCT-00:10 |
November | 24841.71 | 6112.72 | 2.33 | 24841.71 | 0.00 | 0.00 | 0.01 | 04-NOV-15:50 | 0.00 | 01-NOV-00:10 | 40.90 | 04-NOV-15:50 | 40.90 | 04-NOV-15:50 | 0.00 | 01-NOV-00:10 | 10.06 | 04-NOV-15:50 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.165838E+11 | 0.374349E+10 | 1148.81 | 0.162417E+11 | 0.342082E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.577434E+10 | 0.131056E+10 | 295.14 | 0.567237E+10 | 0.123349E+09 | 0.00 | 1.00 | 0.00 | 16872.90 | 16016.37 | 5761.60 | 3499.58 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 219.05 | 53.99 | 1.17 | 219.05 | 0.00 | 0.00 | 0.00 | 27-FEB-15:10 | 0.00 | 01-FEB-00:03 | 0.08 | 27-FEB-15:10 | 0.08 | 27-FEB-15:10 | 0.00 | 01-FEB-00:03 | 0.02 | 27-FEB-15:10 | 0.00 | 01-FEB-00:03 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 12107782.95 | 2930201.31 | 14.33 | 12107782.95 | 0.00 | 0.00 | 0.27 | 07-APR-14:00 | 0.00 | 01-APR-00:05 | 1762.21 | 07-APR-14:00 | 1762.21 | 07-APR-14:00 | 0.00 | 06-APR-16:20 | 422.12 | 07-APR-14:00 | 0.00 | 01-APR-00:05 |
May | 0.552021E+09 | 0.126285E+09 | 79.42 | 0.551551E+09 | 469619.89 | 0.00 | 0.85 | 20-MAY-16:00 | 0.00 | 01-MAY-00:10 | 9129.45 | 20-MAY-08:62 | 8910.19 | 20-MAY-08:62 | 219.27 | 20-MAY-08:62 | 1707.15 | 20-MAY-08:62 | 0.00 | 01-MAY-00:10 |
June | 0.283271E+10 | 0.634979E+09 | 232.19 | 0.273566E+10 | 97052310.53 | 0.00 | 1.00 | 21-JUN-08:61 | 0.00 | 01-JUN-00:10 | 16201.57 | 22-JUN-08:61 | 15295.10 | 29-JUN-08:62 | 3119.41 | 21-JUN-08:61 | 3231.60 | 23-JUN-08:61 | 0.00 | 01-JUN-00:10 |
July | 0.569710E+10 | 0.129402E+10 | 294.14 | 0.559663E+10 | 0.100468E+09 | 0.00 | 1.00 | 01-JUL-08:62 | 0.00 | 01-JUL-00:05 | 16734.63 | 19-JUL-08:61 | 15804.76 | 18-JUL-08:61 | 4251.80 | 04-JUL-09:02 | 3411.81 | 18-JUL-08:61 | 0.00 | 01-JUL-00:05 |
August | 0.469306E+10 | 0.106604E+10 | 289.02 | 0.467608E+10 | 16971587.38 | 0.00 | 1.00 | 01-AUG-08:62 | 0.00 | 01-AUG-00:10 | 15883.76 | 09-AUG-08:61 | 15883.76 | 09-AUG-08:61 | 2998.95 | 14-AUG-08:62 | 3470.86 | 06-AUG-09:01 | 0.00 | 01-AUG-00:10 |
September | 0.230733E+10 | 0.511938E+09 | 164.62 | 0.218561E+10 | 0.121720E+09 | 0.00 | 1.00 | 01-SEP-08:62 | 0.00 | 01-SEP-00:10 | 15939.30 | 07-SEP-08:62 | 15803.81 | 04-SEP-09:01 | 5726.67 | 07-SEP-08:62 | 3431.57 | 04-SEP-09:01 | 0.00 | 01-SEP-00:10 |
October | 0.225221E+09 | 50763375.44 | 60.04 | 0.225221E+09 | 0.00 | 0.00 | 0.75 | 18-OCT-14:30 | 0.00 | 01-OCT-00:10 | 5703.87 | 18-OCT-14:40 | 5703.87 | 18-OCT-14:40 | 0.00 | 18-OCT-15:40 | 1230.95 | 18-OCT-14:40 | 0.00 | 01-OCT-00:10 |
November | 25168.32 | 6192.89 | 2.00 | 25168.32 | 0.00 | 0.00 | 0.01 | 04-NOV-15:40 | 0.00 | 01-NOV-00:10 | 41.42 | 04-NOV-15:40 | 41.42 | 04-NOV-15:40 | 0.00 | 01-NOV-00:10 | 10.19 | 04-NOV-15:40 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.163196E+11 | 0.368696E+10 | 1136.93 | 0.159829E+11 | 0.336681E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.569710E+10 | 0.129402E+10 | 294.14 | 0.559663E+10 | 0.121720E+09 | 0.00 | 1.00 | 0.00 | 16734.63 | 15883.76 | 5726.67 | 3470.86 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 7527645.09 | 1837287.17 | 8.67 | 7527645.09 | 0.00 | 0.00 | 0.22 | 07-APR-14:00 | 0.00 | 01-APR-00:05 | 1440.84 | 07-APR-14:00 | 1440.84 | 07-APR-14:00 | 0.00 | 07-APR-13:40 | 349.18 | 07-APR-14:00 | 0.00 | 01-APR-00:05 |
May | 0.494256E+09 | 0.113957E+09 | 70.95 | 0.493890E+09 | 365352.86 | 0.00 | 0.83 | 20-MAY-16:00 | 0.00 | 01-MAY-00:10 | 6518.34 | 20-MAY-16:00 | 6518.34 | 20-MAY-16:00 | 89.29 | 20-MAY-08:62 | 1512.61 | 20-MAY-16:00 | 0.00 | 01-MAY-00:10 |
June | 0.267878E+10 | 0.603260E+09 | 221.13 | 0.258632E+10 | 92459623.08 | 0.00 | 1.00 | 21-JUN-08:61 | 0.00 | 01-JUN-00:10 | 16035.94 | 22-JUN-08:61 | 15004.60 | 23-JUN-08:61 | 3134.96 | 21-JUN-08:61 | 3198.68 | 23-JUN-08:61 | 0.00 | 01-JUN-00:10 |
July | 0.552458E+10 | 0.125816E+10 | 292.11 | 0.542791E+10 | 96672167.31 | 0.00 | 1.00 | 01-JUL-08:62 | 0.00 | 01-JUL-00:05 | 16565.06 | 19-JUL-08:61 | 15627.50 | 18-JUL-08:61 | 4187.12 | 19-JUL-08:03 | 3374.27 | 18-JUL-08:61 | 0.00 | 01-JUL-00:05 |
August | 0.454145E+10 | 0.103419E+10 | 284.74 | 0.452584E+10 | 15612133.04 | 0.00 | 1.00 | 01-AUG-08:62 | 0.00 | 01-AUG-00:10 | 15720.04 | 09-AUG-08:61 | 15720.04 | 09-AUG-08:61 | 2612.03 | 14-AUG-08:62 | 3433.20 | 06-AUG-09:01 | 0.00 | 01-AUG-00:10 |
September | 0.221912E+10 | 0.493397E+09 | 155.63 | 0.210124E+10 | 0.117875E+09 | 0.00 | 1.00 | 01-SEP-08:62 | 0.00 | 01-SEP-00:10 | 15777.72 | 07-SEP-08:62 | 15647.19 | 04-SEP-09:01 | 5700.63 | 07-SEP-08:62 | 3397.59 | 04-SEP-09:01 | 0.00 | 01-SEP-00:10 |
October | 0.196796E+09 | 44578733.95 | 51.58 | 0.196796E+09 | 0.00 | 0.00 | 0.72 | 18-OCT-14:40 | 0.00 | 01-OCT-00:10 | 5438.97 | 18-OCT-14:40 | 5438.97 | 18-OCT-14:40 | 0.00 | 18-OCT-15:30 | 1181.94 | 18-OCT-14:40 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.156625E+11 | 0.354938E+10 | 1084.82 | 0.153395E+11 | 0.322984E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.552458E+10 | 0.125816E+10 | 292.11 | 0.542791E+10 | 0.117875E+09 | 0.00 | 1.00 | 0.00 | 16565.06 | 15720.04 | 5700.63 | 3433.20 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 1423322.56 | 357054.17 | 1.33 | 1423322.56 | 0.00 | 0.00 | 0.09 | 07-APR-14:00 | 0.00 | 01-APR-00:05 | 645.44 | 07-APR-14:00 | 645.44 | 07-APR-14:00 | 0.00 | 01-APR-00:05 | 161.71 | 07-APR-14:00 | 0.00 | 01-APR-00:05 |
May | 0.421943E+09 | 99444175.13 | 56.83 | 0.421725E+09 | 218466.82 | 0.00 | 0.75 | 20-MAY-16:00 | 0.00 | 01-MAY-00:10 | 6253.00 | 20-MAY-16:00 | 6253.00 | 20-MAY-16:00 | 35.85 | 19-MAY-11:20 | 1488.37 | 20-MAY-16:00 | 0.00 | 01-MAY-00:10 |
June | 0.253964E+10 | 0.582303E+09 | 199.97 | 0.245254E+10 | 87105717.44 | 0.00 | 1.00 | 21-JUN-08:61 | 0.00 | 01-JUN-00:10 | 17471.30 | 22-JUN-08:61 | 16527.53 | 23-JUN-08:61 | 3201.01 | 21-JUN-08:61 | 3479.85 | 22-JUN-08:61 | 0.00 | 01-JUN-00:10 |
July | 0.551283E+10 | 0.126788E+10 | 283.85 | 0.542035E+10 | 92476037.19 | 0.00 | 1.00 | 02-JUL-09:02 | 0.00 | 01-JUL-00:05 | 18082.45 | 19-JUL-08:61 | 17029.51 | 17-JUL-08:61 | 4756.73 | 19-JUL-08:03 | 3672.39 | 18-JUL-08:61 | 0.00 | 01-JUL-00:05 |
August | 0.449384E+10 | 0.103334E+10 | 274.70 | 0.448079E+10 | 13047949.89 | 0.00 | 1.00 | 01-AUG-08:62 | 0.00 | 01-AUG-00:10 | 17132.18 | 09-AUG-08:61 | 17132.18 | 09-AUG-08:61 | 2448.27 | 01-AUG-08:62 | 3739.66 | 06-AUG-09:01 | 0.00 | 01-AUG-00:10 |
September | 0.213916E+10 | 0.480638E+09 | 143.55 | 0.203121E+10 | 0.107951E+09 | 0.00 | 1.00 | 01-SEP-08:62 | 0.00 | 01-SEP-00:10 | 17192.46 | 07-SEP-08:62 | 17039.16 | 04-SEP-09:01 | 6284.30 | 07-SEP-08:62 | 3702.40 | 04-SEP-09:01 | 0.00 | 01-SEP-00:10 |
October | 0.157970E+09 | 36272491.08 | 44.08 | 0.157970E+09 | 0.00 | 0.00 | 0.65 | 18-OCT-14:30 | 0.00 | 01-OCT-00:10 | 5191.56 | 18-OCT-14:40 | 5191.56 | 18-OCT-14:40 | 0.00 | 18-OCT-14:40 | 1154.25 | 18-OCT-14:40 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.152668E+11 | 0.350024E+10 | 1004.32 | 0.149660E+11 | 0.300799E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.551283E+10 | 0.126788E+10 | 283.85 | 0.542035E+10 | 0.107951E+09 | 0.00 | 1.00 | 0.00 | 18082.45 | 17132.18 | 6284.30 | 3739.66 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.98 | 84.25 | 33.73 | 109.27 | 118.28 | 0.00 | 0.00 | 744.00 |
February | 150.30 | 108.10 | 42.20 | 148.38 | 87.87 | 0.00 | 0.00 | 672.00 |
March | 134.40 | 75.50 | 58.90 | 124.17 | 77.16 | 0.00 | 0.00 | 744.00 |
April | 108.00 | 51.66 | 56.34 | 91.63 | 56.25 | 0.00 | 0.00 | 720.00 |
May | 95.93 | 31.85 | 64.08 | 73.94 | 45.17 | 0.00 | 0.00 | 744.00 |
June | 95.32 | 27.79 | 67.53 | 79.50 | 32.10 | 0.00 | 0.00 | 720.00 |
July | 102.76 | 37.95 | 64.81 | 96.85 | 25.36 | 0.00 | 0.00 | 744.00 |
August | 122.14 | 61.58 | 60.56 | 123.38 | 28.87 | 0.00 | 0.00 | 744.00 |
September | 135.53 | 83.06 | 52.47 | 142.99 | 41.30 | 0.00 | 0.00 | 720.00 |
October | 141.68 | 97.98 | 43.70 | 148.44 | 59.20 | 0.00 | 0.00 | 744.00 |
November | 129.10 | 93.51 | 35.59 | 131.01 | 74.54 | 0.00 | 0.00 | 720.00 |
December | 112.19 | 81.00 | 31.19 | 107.32 | 101.33 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 120.24 | 69.26 | 50.97 | 114.50 | 62.20 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 95.32 | 27.79 | 31.19 | 73.94 | 25.36 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 150.30 | 108.10 | 67.53 | 148.44 | 118.28 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.98 | 84.25 | 33.73 | 109.27 | 118.28 | 0.00 | 0.00 | 744.00 |
February | 150.30 | 108.10 | 42.20 | 148.38 | 87.87 | 0.00 | 0.00 | 672.00 |
March | 134.40 | 75.50 | 58.90 | 124.17 | 77.16 | 0.00 | 0.00 | 744.00 |
April | 108.00 | 51.66 | 56.34 | 91.63 | 56.25 | 0.00 | 0.00 | 720.00 |
May | 95.93 | 31.85 | 64.08 | 73.94 | 45.17 | 0.00 | 0.00 | 744.00 |
June | 95.32 | 27.79 | 67.53 | 79.50 | 32.10 | 0.00 | 0.00 | 720.00 |
July | 102.76 | 37.95 | 64.81 | 96.85 | 25.36 | 0.00 | 0.00 | 744.00 |
August | 122.14 | 61.58 | 60.56 | 123.38 | 28.87 | 0.00 | 0.00 | 744.00 |
September | 135.53 | 83.06 | 52.47 | 142.99 | 41.30 | 0.00 | 0.00 | 720.00 |
October | 141.68 | 97.98 | 43.70 | 148.44 | 59.20 | 0.00 | 0.00 | 744.00 |
November | 129.10 | 93.51 | 35.59 | 131.01 | 74.54 | 0.00 | 0.00 | 720.00 |
December | 112.19 | 81.00 | 31.19 | 107.32 | 101.33 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 120.24 | 69.26 | 50.97 | 114.50 | 62.20 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 95.32 | 27.79 | 31.19 | 73.94 | 25.36 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 150.30 | 108.10 | 67.53 | 148.44 | 118.28 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_3
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.98 | 84.25 | 33.73 | 109.27 | 118.28 | 0.00 | 0.00 | 744.00 |
February | 150.30 | 108.10 | 42.20 | 148.38 | 87.87 | 0.00 | 0.00 | 672.00 |
March | 134.40 | 75.50 | 58.90 | 124.17 | 77.16 | 0.00 | 0.00 | 744.00 |
April | 108.00 | 51.66 | 56.34 | 91.63 | 56.25 | 0.00 | 0.00 | 720.00 |
May | 95.93 | 31.85 | 64.08 | 73.94 | 45.17 | 0.00 | 0.00 | 744.00 |
June | 95.32 | 27.79 | 67.53 | 79.50 | 32.10 | 0.00 | 0.00 | 720.00 |
July | 102.76 | 37.95 | 64.81 | 96.85 | 25.36 | 0.00 | 0.00 | 744.00 |
August | 122.14 | 61.58 | 60.56 | 123.38 | 28.87 | 0.00 | 0.00 | 744.00 |
September | 135.53 | 83.06 | 52.47 | 142.99 | 41.30 | 0.00 | 0.00 | 720.00 |
October | 141.68 | 97.98 | 43.70 | 148.44 | 59.20 | 0.00 | 0.00 | 744.00 |
November | 129.10 | 93.51 | 35.59 | 131.01 | 74.54 | 0.00 | 0.00 | 720.00 |
December | 112.19 | 81.00 | 31.19 | 107.32 | 101.33 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 120.24 | 69.26 | 50.97 | 114.50 | 62.20 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 95.32 | 27.79 | 31.19 | 73.94 | 25.36 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 150.30 | 108.10 | 67.53 | 148.44 | 118.28 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_4
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.98 | 84.25 | 33.73 | 109.27 | 118.28 | 0.00 | 0.00 | 744.00 |
February | 150.30 | 108.10 | 42.20 | 148.38 | 87.87 | 0.00 | 0.00 | 672.00 |
March | 134.40 | 75.50 | 58.90 | 124.17 | 77.16 | 0.00 | 0.00 | 744.00 |
April | 108.00 | 51.66 | 56.34 | 91.63 | 56.25 | 0.00 | 0.00 | 720.00 |
May | 95.93 | 31.85 | 64.08 | 73.94 | 45.17 | 0.00 | 0.00 | 744.00 |
June | 95.32 | 27.79 | 67.53 | 79.50 | 32.10 | 0.00 | 0.00 | 720.00 |
July | 102.76 | 37.95 | 64.81 | 96.85 | 25.36 | 0.00 | 0.00 | 744.00 |
August | 122.14 | 61.58 | 60.56 | 123.38 | 28.87 | 0.00 | 0.00 | 744.00 |
September | 135.53 | 83.06 | 52.47 | 142.99 | 41.30 | 0.00 | 0.00 | 720.00 |
October | 141.68 | 97.98 | 43.70 | 148.44 | 59.20 | 0.00 | 0.00 | 744.00 |
November | 129.10 | 93.51 | 35.59 | 131.01 | 74.54 | 0.00 | 0.00 | 720.00 |
December | 112.19 | 81.00 | 31.19 | 107.32 | 101.33 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 120.24 | 69.26 | 50.97 | 114.50 | 62.20 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 95.32 | 27.79 | 31.19 | 73.94 | 25.36 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 150.30 | 108.10 | 67.53 | 148.44 | 118.28 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_DOOR_1
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 142.04 | 101.44 | 40.61 | 131.78 | 141.11 | 0.00 | 0.00 | 744.00 |
February | 180.96 | 130.15 | 50.80 | 178.84 | 104.89 | 0.00 | 0.00 | 672.00 |
March | 161.82 | 90.90 | 70.92 | 149.67 | 92.12 | 0.00 | 0.00 | 744.00 |
April | 130.03 | 62.20 | 67.83 | 110.42 | 67.21 | 0.00 | 0.00 | 720.00 |
May | 115.50 | 38.35 | 77.15 | 89.11 | 53.99 | 0.00 | 0.00 | 744.00 |
June | 114.76 | 33.45 | 81.30 | 95.69 | 38.40 | 0.00 | 0.00 | 720.00 |
July | 123.72 | 45.68 | 78.03 | 116.48 | 30.40 | 0.00 | 0.00 | 744.00 |
August | 147.05 | 74.14 | 72.92 | 148.42 | 34.59 | 0.00 | 0.00 | 744.00 |
September | 163.17 | 100.00 | 63.17 | 172.10 | 49.42 | 0.00 | 0.00 | 720.00 |
October | 170.57 | 117.96 | 52.61 | 178.74 | 70.80 | 0.00 | 0.00 | 744.00 |
November | 155.43 | 112.58 | 42.85 | 157.84 | 89.05 | 0.00 | 0.00 | 720.00 |
December | 135.07 | 97.52 | 37.55 | 129.41 | 120.97 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 144.76 | 83.39 | 61.37 | 137.92 | 74.31 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 114.76 | 33.45 | 37.55 | 89.11 | 30.40 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 180.96 | 130.15 | 81.30 | 178.84 | 141.11 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_DOOR_2
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 142.04 | 101.44 | 40.61 | 131.78 | 141.11 | 0.00 | 0.00 | 744.00 |
February | 180.96 | 130.15 | 50.80 | 178.84 | 104.89 | 0.00 | 0.00 | 672.00 |
March | 161.82 | 90.90 | 70.92 | 149.67 | 92.12 | 0.00 | 0.00 | 744.00 |
April | 130.03 | 62.20 | 67.83 | 110.42 | 67.21 | 0.00 | 0.00 | 720.00 |
May | 115.50 | 38.35 | 77.15 | 89.11 | 53.99 | 0.00 | 0.00 | 744.00 |
June | 114.76 | 33.45 | 81.30 | 95.69 | 38.40 | 0.00 | 0.00 | 720.00 |
July | 123.72 | 45.68 | 78.03 | 116.48 | 30.40 | 0.00 | 0.00 | 744.00 |
August | 147.05 | 74.14 | 72.92 | 148.42 | 34.59 | 0.00 | 0.00 | 744.00 |
September | 163.17 | 100.00 | 63.17 | 172.10 | 49.42 | 0.00 | 0.00 | 720.00 |
October | 170.57 | 117.96 | 52.61 | 178.74 | 70.80 | 0.00 | 0.00 | 744.00 |
November | 155.43 | 112.58 | 42.85 | 157.84 | 89.05 | 0.00 | 0.00 | 720.00 |
December | 135.07 | 97.52 | 37.55 | 129.41 | 120.97 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 144.76 | 83.39 | 61.37 | 137.92 | 74.31 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 114.76 | 33.45 | 37.55 | 89.11 | 30.40 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 180.96 | 130.15 | 81.30 | 178.84 | 141.11 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.98 | 84.25 | 33.73 | 108.21 | 122.40 | 0.00 | 0.00 | 744.00 |
February | 150.30 | 108.10 | 42.20 | 146.76 | 92.03 | 0.00 | 0.00 | 672.00 |
March | 134.40 | 75.50 | 58.90 | 122.70 | 81.60 | 0.00 | 0.00 | 744.00 |
April | 108.00 | 51.66 | 56.34 | 89.77 | 61.01 | 0.00 | 0.00 | 720.00 |
May | 95.93 | 31.85 | 64.08 | 72.43 | 48.30 | 0.00 | 0.00 | 744.00 |
June | 95.32 | 27.79 | 67.53 | 78.69 | 33.21 | 0.00 | 0.00 | 720.00 |
July | 102.76 | 37.95 | 64.81 | 96.61 | 25.71 | 0.00 | 0.00 | 744.00 |
August | 122.14 | 61.58 | 60.56 | 123.02 | 29.36 | 0.00 | 0.00 | 744.00 |
September | 135.53 | 83.06 | 52.47 | 142.14 | 42.89 | 0.00 | 0.00 | 720.00 |
October | 141.68 | 97.98 | 43.70 | 146.93 | 62.46 | 0.00 | 0.00 | 744.00 |
November | 129.10 | 93.51 | 35.59 | 129.34 | 78.68 | 0.00 | 0.00 | 720.00 |
December | 112.19 | 81.00 | 31.19 | 106.19 | 105.20 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 120.24 | 69.26 | 50.97 | 113.33 | 65.14 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 95.32 | 27.79 | 31.19 | 72.43 | 25.71 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 150.30 | 108.10 | 67.53 | 146.93 | 122.40 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.98 | 84.25 | 33.73 | 108.21 | 122.40 | 0.00 | 0.00 | 744.00 |
February | 150.30 | 108.10 | 42.20 | 146.76 | 92.03 | 0.00 | 0.00 | 672.00 |
March | 134.40 | 75.50 | 58.90 | 122.70 | 81.60 | 0.00 | 0.00 | 744.00 |
April | 108.00 | 51.66 | 56.34 | 89.77 | 61.01 | 0.00 | 0.00 | 720.00 |
May | 95.93 | 31.85 | 64.08 | 72.43 | 48.30 | 0.00 | 0.00 | 744.00 |
June | 95.32 | 27.79 | 67.53 | 78.69 | 33.21 | 0.00 | 0.00 | 720.00 |
July | 102.76 | 37.95 | 64.81 | 96.61 | 25.71 | 0.00 | 0.00 | 744.00 |
August | 122.14 | 61.58 | 60.56 | 123.02 | 29.36 | 0.00 | 0.00 | 744.00 |
September | 135.53 | 83.06 | 52.47 | 142.14 | 42.89 | 0.00 | 0.00 | 720.00 |
October | 141.68 | 97.98 | 43.70 | 146.93 | 62.46 | 0.00 | 0.00 | 744.00 |
November | 129.10 | 93.51 | 35.59 | 129.34 | 78.68 | 0.00 | 0.00 | 720.00 |
December | 112.19 | 81.00 | 31.19 | 106.19 | 105.20 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 120.24 | 69.26 | 50.97 | 113.33 | 65.14 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 95.32 | 27.79 | 31.19 | 72.43 | 25.71 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 150.30 | 108.10 | 67.53 | 146.93 | 122.40 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_DOOR
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 142.04 | 101.44 | 40.61 | 130.52 | 145.99 | 0.00 | 0.00 | 744.00 |
February | 180.96 | 130.15 | 50.80 | 176.90 | 109.82 | 0.00 | 0.00 | 672.00 |
March | 161.82 | 90.90 | 70.92 | 147.91 | 97.39 | 0.00 | 0.00 | 744.00 |
April | 130.03 | 62.20 | 67.83 | 108.18 | 72.87 | 0.00 | 0.00 | 720.00 |
May | 115.50 | 38.35 | 77.15 | 87.30 | 57.69 | 0.00 | 0.00 | 744.00 |
June | 114.76 | 33.45 | 81.30 | 94.72 | 39.72 | 0.00 | 0.00 | 720.00 |
July | 123.72 | 45.68 | 78.03 | 116.17 | 30.81 | 0.00 | 0.00 | 744.00 |
August | 147.05 | 74.14 | 72.92 | 147.99 | 35.17 | 0.00 | 0.00 | 744.00 |
September | 163.17 | 100.00 | 63.17 | 171.08 | 51.31 | 0.00 | 0.00 | 720.00 |
October | 170.57 | 117.96 | 52.61 | 176.95 | 74.66 | 0.00 | 0.00 | 744.00 |
November | 155.43 | 112.58 | 42.85 | 155.85 | 93.95 | 0.00 | 0.00 | 720.00 |
December | 135.07 | 97.52 | 37.55 | 128.05 | 125.55 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 144.76 | 83.39 | 61.37 | 136.52 | 77.80 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 114.76 | 33.45 | 37.55 | 87.30 | 30.81 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 180.96 | 130.15 | 81.30 | 176.95 | 145.99 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.98 | 84.25 | 33.73 | 108.37 | 119.86 | 0.00 | 0.00 | 744.00 |
February | 150.30 | 108.10 | 42.20 | 147.07 | 89.91 | 0.00 | 0.00 | 672.00 |
March | 134.40 | 75.50 | 58.90 | 122.95 | 79.61 | 0.00 | 0.00 | 744.00 |
April | 108.00 | 51.66 | 56.34 | 90.06 | 59.51 | 0.00 | 0.00 | 720.00 |
May | 95.93 | 31.85 | 64.08 | 72.54 | 47.70 | 0.00 | 0.00 | 744.00 |
June | 95.32 | 27.79 | 67.53 | 78.45 | 34.21 | 0.00 | 0.00 | 720.00 |
July | 102.76 | 37.95 | 64.81 | 96.09 | 27.39 | 0.00 | 0.00 | 744.00 |
August | 122.14 | 61.58 | 60.56 | 122.68 | 30.97 | 0.00 | 0.00 | 744.00 |
September | 135.53 | 83.06 | 52.47 | 141.97 | 43.79 | 0.00 | 0.00 | 720.00 |
October | 141.68 | 97.98 | 43.70 | 147.15 | 61.86 | 0.00 | 0.00 | 744.00 |
November | 129.10 | 93.51 | 35.59 | 129.76 | 76.84 | 0.00 | 0.00 | 720.00 |
December | 112.19 | 81.00 | 31.19 | 106.42 | 102.97 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 120.24 | 69.26 | 50.97 | 113.39 | 64.46 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 95.32 | 27.79 | 31.19 | 72.54 | 27.39 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 150.30 | 108.10 | 67.53 | 147.15 | 119.86 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.98 | 84.25 | 33.73 | 108.37 | 119.86 | 0.00 | 0.00 | 744.00 |
February | 150.30 | 108.10 | 42.20 | 147.07 | 89.91 | 0.00 | 0.00 | 672.00 |
March | 134.40 | 75.50 | 58.90 | 122.95 | 79.61 | 0.00 | 0.00 | 744.00 |
April | 108.00 | 51.66 | 56.34 | 90.06 | 59.51 | 0.00 | 0.00 | 720.00 |
May | 95.93 | 31.85 | 64.08 | 72.54 | 47.70 | 0.00 | 0.00 | 744.00 |
June | 95.32 | 27.79 | 67.53 | 78.45 | 34.21 | 0.00 | 0.00 | 720.00 |
July | 102.76 | 37.95 | 64.81 | 96.09 | 27.39 | 0.00 | 0.00 | 744.00 |
August | 122.14 | 61.58 | 60.56 | 122.68 | 30.97 | 0.00 | 0.00 | 744.00 |
September | 135.53 | 83.06 | 52.47 | 141.97 | 43.79 | 0.00 | 0.00 | 720.00 |
October | 141.68 | 97.98 | 43.70 | 147.15 | 61.86 | 0.00 | 0.00 | 744.00 |
November | 129.10 | 93.51 | 35.59 | 129.76 | 76.84 | 0.00 | 0.00 | 720.00 |
December | 112.19 | 81.00 | 31.19 | 106.42 | 102.97 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 120.24 | 69.26 | 50.97 | 113.39 | 64.46 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 95.32 | 27.79 | 31.19 | 72.54 | 27.39 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 150.30 | 108.10 | 67.53 | 147.15 | 119.86 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_DOOR
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 141.27 | 100.88 | 40.39 | 130.00 | 142.19 | 0.00 | 0.00 | 744.00 |
February | 179.97 | 129.44 | 50.53 | 176.32 | 106.72 | 0.00 | 0.00 | 672.00 |
March | 160.93 | 90.40 | 70.53 | 147.41 | 94.51 | 0.00 | 0.00 | 744.00 |
April | 129.32 | 61.86 | 67.46 | 107.95 | 70.70 | 0.00 | 0.00 | 720.00 |
May | 114.87 | 38.14 | 76.73 | 86.96 | 56.65 | 0.00 | 0.00 | 744.00 |
June | 114.13 | 33.27 | 80.86 | 93.92 | 40.67 | 0.00 | 0.00 | 720.00 |
July | 123.04 | 45.43 | 77.61 | 114.93 | 32.60 | 0.00 | 0.00 | 744.00 |
August | 146.25 | 73.73 | 72.52 | 146.78 | 36.86 | 0.00 | 0.00 | 744.00 |
September | 162.28 | 99.46 | 62.82 | 169.95 | 52.07 | 0.00 | 0.00 | 720.00 |
October | 169.64 | 117.32 | 52.32 | 176.25 | 73.54 | 0.00 | 0.00 | 744.00 |
November | 154.58 | 111.96 | 42.62 | 155.50 | 91.27 | 0.00 | 0.00 | 720.00 |
December | 134.33 | 96.99 | 37.35 | 127.64 | 122.22 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 143.97 | 82.93 | 61.04 | 135.85 | 76.56 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 114.13 | 33.27 | 37.35 | 86.96 | 32.60 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 179.97 | 129.44 | 80.86 | 176.32 | 142.19 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.98 | 84.25 | 33.73 | 108.51 | 118.84 | 0.00 | 0.00 | 744.00 |
February | 150.30 | 108.10 | 42.20 | 147.32 | 88.95 | 0.00 | 0.00 | 672.00 |
March | 134.40 | 75.50 | 58.90 | 123.16 | 78.71 | 0.00 | 0.00 | 744.00 |
April | 108.00 | 51.66 | 56.34 | 90.36 | 58.58 | 0.00 | 0.00 | 720.00 |
May | 95.93 | 31.85 | 64.08 | 72.77 | 47.05 | 0.00 | 0.00 | 744.00 |
June | 95.32 | 27.79 | 67.53 | 78.50 | 34.10 | 0.00 | 0.00 | 720.00 |
July | 102.76 | 37.95 | 64.81 | 96.07 | 27.45 | 0.00 | 0.00 | 744.00 |
August | 122.14 | 61.58 | 60.56 | 122.67 | 31.01 | 0.00 | 0.00 | 744.00 |
September | 135.53 | 83.06 | 52.47 | 142.03 | 43.60 | 0.00 | 0.00 | 720.00 |
October | 141.68 | 97.98 | 43.70 | 147.36 | 61.20 | 0.00 | 0.00 | 744.00 |
November | 129.10 | 93.51 | 35.59 | 130.05 | 75.83 | 0.00 | 0.00 | 720.00 |
December | 112.19 | 81.00 | 31.19 | 106.59 | 102.03 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 120.24 | 69.26 | 50.97 | 113.55 | 63.86 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 95.32 | 27.79 | 31.19 | 72.77 | 27.45 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 150.30 | 108.10 | 67.53 | 147.36 | 118.84 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.98 | 84.25 | 33.73 | 108.51 | 118.84 | 0.00 | 0.00 | 744.00 |
February | 150.30 | 108.10 | 42.20 | 147.32 | 88.95 | 0.00 | 0.00 | 672.00 |
March | 134.40 | 75.50 | 58.90 | 123.16 | 78.71 | 0.00 | 0.00 | 744.00 |
April | 108.00 | 51.66 | 56.34 | 90.36 | 58.58 | 0.00 | 0.00 | 720.00 |
May | 95.93 | 31.85 | 64.08 | 72.77 | 47.05 | 0.00 | 0.00 | 744.00 |
June | 95.32 | 27.79 | 67.53 | 78.50 | 34.10 | 0.00 | 0.00 | 720.00 |
July | 102.76 | 37.95 | 64.81 | 96.07 | 27.45 | 0.00 | 0.00 | 744.00 |
August | 122.14 | 61.58 | 60.56 | 122.67 | 31.01 | 0.00 | 0.00 | 744.00 |
September | 135.53 | 83.06 | 52.47 | 142.03 | 43.60 | 0.00 | 0.00 | 720.00 |
October | 141.68 | 97.98 | 43.70 | 147.36 | 61.20 | 0.00 | 0.00 | 744.00 |
November | 129.10 | 93.51 | 35.59 | 130.05 | 75.83 | 0.00 | 0.00 | 720.00 |
December | 112.19 | 81.00 | 31.19 | 106.59 | 102.03 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 120.24 | 69.26 | 50.97 | 113.55 | 63.86 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 95.32 | 27.79 | 31.19 | 72.77 | 27.45 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 150.30 | 108.10 | 67.53 | 147.36 | 118.84 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_DOOR
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 141.27 | 100.88 | 40.39 | 130.17 | 140.97 | 0.00 | 0.00 | 744.00 |
February | 179.97 | 129.44 | 50.53 | 176.61 | 105.58 | 0.00 | 0.00 | 672.00 |
March | 160.93 | 90.40 | 70.53 | 147.66 | 93.43 | 0.00 | 0.00 | 744.00 |
April | 129.32 | 61.86 | 67.46 | 108.31 | 69.59 | 0.00 | 0.00 | 720.00 |
May | 114.87 | 38.14 | 76.73 | 87.24 | 55.89 | 0.00 | 0.00 | 744.00 |
June | 114.13 | 33.27 | 80.86 | 93.98 | 40.53 | 0.00 | 0.00 | 720.00 |
July | 123.04 | 45.43 | 77.61 | 114.90 | 32.69 | 0.00 | 0.00 | 744.00 |
August | 146.25 | 73.73 | 72.52 | 146.76 | 36.91 | 0.00 | 0.00 | 744.00 |
September | 162.28 | 99.46 | 62.82 | 170.02 | 51.84 | 0.00 | 0.00 | 720.00 |
October | 169.64 | 117.32 | 52.32 | 176.50 | 72.75 | 0.00 | 0.00 | 744.00 |
November | 154.58 | 111.96 | 42.62 | 155.85 | 90.06 | 0.00 | 0.00 | 720.00 |
December | 134.33 | 96.99 | 37.35 | 127.84 | 121.11 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 143.97 | 82.93 | 61.04 | 136.04 | 75.84 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 114.13 | 33.27 | 37.35 | 87.24 | 32.69 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 179.97 | 129.44 | 80.86 | 176.61 | 140.97 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.98 | 84.25 | 33.73 | 108.67 | 118.09 | 0.00 | 0.00 | 744.00 |
February | 150.30 | 108.10 | 42.20 | 147.59 | 88.18 | 0.00 | 0.00 | 672.00 |
March | 134.40 | 75.50 | 58.90 | 123.39 | 77.97 | 0.00 | 0.00 | 744.00 |
April | 108.00 | 51.66 | 56.34 | 90.75 | 57.65 | 0.00 | 0.00 | 720.00 |
May | 95.93 | 31.85 | 64.08 | 73.15 | 46.31 | 0.00 | 0.00 | 744.00 |
June | 95.32 | 27.79 | 67.53 | 78.70 | 33.73 | 0.00 | 0.00 | 720.00 |
July | 102.76 | 37.95 | 64.81 | 96.19 | 27.19 | 0.00 | 0.00 | 744.00 |
August | 122.14 | 61.58 | 60.56 | 122.79 | 30.71 | 0.00 | 0.00 | 744.00 |
September | 135.53 | 83.06 | 52.47 | 142.22 | 43.12 | 0.00 | 0.00 | 720.00 |
October | 141.68 | 97.98 | 43.70 | 147.69 | 60.41 | 0.00 | 0.00 | 744.00 |
November | 129.10 | 93.51 | 35.59 | 130.41 | 74.90 | 0.00 | 0.00 | 720.00 |
December | 112.19 | 81.00 | 31.19 | 106.77 | 101.31 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 120.24 | 69.26 | 50.97 | 113.79 | 63.21 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 95.32 | 27.79 | 31.19 | 73.15 | 27.19 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 150.30 | 108.10 | 67.53 | 147.69 | 118.09 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.98 | 84.25 | 33.73 | 108.67 | 118.09 | 0.00 | 0.00 | 744.00 |
February | 150.30 | 108.10 | 42.20 | 147.59 | 88.18 | 0.00 | 0.00 | 672.00 |
March | 134.40 | 75.50 | 58.90 | 123.39 | 77.97 | 0.00 | 0.00 | 744.00 |
April | 108.00 | 51.66 | 56.34 | 90.75 | 57.65 | 0.00 | 0.00 | 720.00 |
May | 95.93 | 31.85 | 64.08 | 73.15 | 46.31 | 0.00 | 0.00 | 744.00 |
June | 95.32 | 27.79 | 67.53 | 78.70 | 33.73 | 0.00 | 0.00 | 720.00 |
July | 102.76 | 37.95 | 64.81 | 96.19 | 27.19 | 0.00 | 0.00 | 744.00 |
August | 122.14 | 61.58 | 60.56 | 122.79 | 30.71 | 0.00 | 0.00 | 744.00 |
September | 135.53 | 83.06 | 52.47 | 142.22 | 43.12 | 0.00 | 0.00 | 720.00 |
October | 141.68 | 97.98 | 43.70 | 147.69 | 60.41 | 0.00 | 0.00 | 744.00 |
November | 129.10 | 93.51 | 35.59 | 130.41 | 74.90 | 0.00 | 0.00 | 720.00 |
December | 112.19 | 81.00 | 31.19 | 106.77 | 101.31 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 120.24 | 69.26 | 50.97 | 113.79 | 63.21 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 95.32 | 27.79 | 31.19 | 73.15 | 27.19 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 150.30 | 108.10 | 67.53 | 147.69 | 118.09 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_DOOR
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 141.27 | 100.88 | 40.39 | 130.36 | 140.08 | 0.00 | 0.00 | 744.00 |
February | 179.97 | 129.44 | 50.53 | 176.94 | 104.66 | 0.00 | 0.00 | 672.00 |
March | 160.93 | 90.40 | 70.53 | 147.94 | 92.55 | 0.00 | 0.00 | 744.00 |
April | 129.32 | 61.86 | 67.46 | 108.78 | 68.48 | 0.00 | 0.00 | 720.00 |
May | 114.87 | 38.14 | 76.73 | 87.69 | 55.00 | 0.00 | 0.00 | 744.00 |
June | 114.13 | 33.27 | 80.86 | 94.22 | 40.10 | 0.00 | 0.00 | 720.00 |
July | 123.04 | 45.43 | 77.61 | 115.05 | 32.38 | 0.00 | 0.00 | 744.00 |
August | 146.25 | 73.73 | 72.52 | 146.91 | 36.55 | 0.00 | 0.00 | 744.00 |
September | 162.28 | 99.46 | 62.82 | 170.26 | 51.28 | 0.00 | 0.00 | 720.00 |
October | 169.64 | 117.32 | 52.32 | 176.90 | 71.81 | 0.00 | 0.00 | 744.00 |
November | 154.58 | 111.96 | 42.62 | 156.28 | 88.95 | 0.00 | 0.00 | 720.00 |
December | 134.33 | 96.99 | 37.35 | 128.06 | 120.25 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 143.97 | 82.93 | 61.04 | 136.33 | 75.07 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 114.13 | 33.27 | 37.35 | 87.69 | 32.38 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 179.97 | 129.44 | 80.86 | 176.94 | 140.08 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.98 | 84.25 | 33.73 | 109.51 | 115.63 | 0.00 | 0.00 | 744.00 |
February | 150.30 | 108.10 | 42.20 | 148.73 | 86.03 | 0.00 | 0.00 | 672.00 |
March | 134.40 | 75.50 | 58.90 | 124.27 | 76.00 | 0.00 | 0.00 | 744.00 |
April | 108.00 | 51.66 | 56.34 | 91.80 | 55.56 | 0.00 | 0.00 | 720.00 |
May | 95.93 | 31.85 | 64.08 | 74.13 | 44.53 | 0.00 | 0.00 | 744.00 |
June | 95.32 | 27.79 | 67.53 | 79.13 | 32.66 | 0.00 | 0.00 | 720.00 |
July | 102.76 | 37.95 | 64.81 | 96.22 | 26.34 | 0.00 | 0.00 | 744.00 |
August | 122.14 | 61.58 | 60.56 | 122.93 | 29.72 | 0.00 | 0.00 | 744.00 |
September | 135.53 | 83.06 | 52.47 | 142.73 | 41.87 | 0.00 | 0.00 | 720.00 |
October | 141.68 | 97.98 | 43.70 | 148.75 | 58.54 | 0.00 | 0.00 | 744.00 |
November | 129.10 | 93.51 | 35.59 | 131.45 | 72.79 | 0.00 | 0.00 | 720.00 |
December | 112.19 | 81.00 | 31.19 | 107.65 | 99.16 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 120.24 | 69.26 | 50.97 | 114.53 | 61.49 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 95.32 | 27.79 | 31.19 | 74.13 | 26.34 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 150.30 | 108.10 | 67.53 | 148.75 | 115.63 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.98 | 84.25 | 33.73 | 109.51 | 115.63 | 0.00 | 0.00 | 744.00 |
February | 150.30 | 108.10 | 42.20 | 148.73 | 86.03 | 0.00 | 0.00 | 672.00 |
March | 134.40 | 75.50 | 58.90 | 124.27 | 76.00 | 0.00 | 0.00 | 744.00 |
April | 108.00 | 51.66 | 56.34 | 91.80 | 55.56 | 0.00 | 0.00 | 720.00 |
May | 95.93 | 31.85 | 64.08 | 74.13 | 44.53 | 0.00 | 0.00 | 744.00 |
June | 95.32 | 27.79 | 67.53 | 79.13 | 32.66 | 0.00 | 0.00 | 720.00 |
July | 102.76 | 37.95 | 64.81 | 96.22 | 26.34 | 0.00 | 0.00 | 744.00 |
August | 122.14 | 61.58 | 60.56 | 122.93 | 29.72 | 0.00 | 0.00 | 744.00 |
September | 135.53 | 83.06 | 52.47 | 142.73 | 41.87 | 0.00 | 0.00 | 720.00 |
October | 141.68 | 97.98 | 43.70 | 148.75 | 58.54 | 0.00 | 0.00 | 744.00 |
November | 129.10 | 93.51 | 35.59 | 131.45 | 72.79 | 0.00 | 0.00 | 720.00 |
December | 112.19 | 81.00 | 31.19 | 107.65 | 99.16 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 120.24 | 69.26 | 50.97 | 114.53 | 61.49 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 95.32 | 27.79 | 31.19 | 74.13 | 26.34 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 150.30 | 108.10 | 67.53 | 148.75 | 115.63 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_3
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.98 | 84.25 | 33.73 | 109.51 | 115.63 | 0.00 | 0.00 | 744.00 |
February | 150.30 | 108.10 | 42.20 | 148.73 | 86.03 | 0.00 | 0.00 | 672.00 |
March | 134.40 | 75.50 | 58.90 | 124.27 | 76.00 | 0.00 | 0.00 | 744.00 |
April | 108.00 | 51.66 | 56.34 | 91.80 | 55.56 | 0.00 | 0.00 | 720.00 |
May | 95.93 | 31.85 | 64.08 | 74.13 | 44.53 | 0.00 | 0.00 | 744.00 |
June | 95.32 | 27.79 | 67.53 | 79.13 | 32.66 | 0.00 | 0.00 | 720.00 |
July | 102.76 | 37.95 | 64.81 | 96.22 | 26.34 | 0.00 | 0.00 | 744.00 |
August | 122.14 | 61.58 | 60.56 | 122.93 | 29.72 | 0.00 | 0.00 | 744.00 |
September | 135.53 | 83.06 | 52.47 | 142.73 | 41.87 | 0.00 | 0.00 | 720.00 |
October | 141.68 | 97.98 | 43.70 | 148.75 | 58.54 | 0.00 | 0.00 | 744.00 |
November | 129.10 | 93.51 | 35.59 | 131.45 | 72.79 | 0.00 | 0.00 | 720.00 |
December | 112.19 | 81.00 | 31.19 | 107.65 | 99.16 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 120.24 | 69.26 | 50.97 | 114.53 | 61.49 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 95.32 | 27.79 | 31.19 | 74.13 | 26.34 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 150.30 | 108.10 | 67.53 | 148.75 | 115.63 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_4
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.98 | 84.25 | 33.73 | 109.51 | 115.63 | 0.00 | 0.00 | 744.00 |
February | 150.30 | 108.10 | 42.20 | 148.73 | 86.03 | 0.00 | 0.00 | 672.00 |
March | 134.40 | 75.50 | 58.90 | 124.27 | 76.00 | 0.00 | 0.00 | 744.00 |
April | 108.00 | 51.66 | 56.34 | 91.80 | 55.56 | 0.00 | 0.00 | 720.00 |
May | 95.93 | 31.85 | 64.08 | 74.13 | 44.53 | 0.00 | 0.00 | 744.00 |
June | 95.32 | 27.79 | 67.53 | 79.13 | 32.66 | 0.00 | 0.00 | 720.00 |
July | 102.76 | 37.95 | 64.81 | 96.22 | 26.34 | 0.00 | 0.00 | 744.00 |
August | 122.14 | 61.58 | 60.56 | 122.93 | 29.72 | 0.00 | 0.00 | 744.00 |
September | 135.53 | 83.06 | 52.47 | 142.73 | 41.87 | 0.00 | 0.00 | 720.00 |
October | 141.68 | 97.98 | 43.70 | 148.75 | 58.54 | 0.00 | 0.00 | 744.00 |
November | 129.10 | 93.51 | 35.59 | 131.45 | 72.79 | 0.00 | 0.00 | 720.00 |
December | 112.19 | 81.00 | 31.19 | 107.65 | 99.16 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 120.24 | 69.26 | 50.97 | 114.53 | 61.49 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 95.32 | 27.79 | 31.19 | 74.13 | 26.34 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 150.30 | 108.10 | 67.53 | 148.75 | 115.63 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_DOOR_1
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 141.27 | 100.88 | 40.39 | 131.36 | 137.18 | 0.00 | 0.00 | 744.00 |
February | 179.97 | 129.44 | 50.53 | 178.29 | 102.13 | 0.00 | 0.00 | 672.00 |
March | 160.93 | 90.40 | 70.53 | 148.99 | 90.23 | 0.00 | 0.00 | 744.00 |
April | 129.32 | 61.86 | 67.46 | 110.02 | 66.01 | 0.00 | 0.00 | 720.00 |
May | 114.87 | 38.14 | 76.73 | 88.87 | 52.91 | 0.00 | 0.00 | 744.00 |
June | 114.13 | 33.27 | 80.86 | 94.74 | 38.83 | 0.00 | 0.00 | 720.00 |
July | 123.04 | 45.43 | 77.61 | 115.10 | 31.37 | 0.00 | 0.00 | 744.00 |
August | 146.25 | 73.73 | 72.52 | 147.09 | 35.39 | 0.00 | 0.00 | 744.00 |
September | 162.28 | 99.46 | 62.82 | 170.87 | 49.81 | 0.00 | 0.00 | 720.00 |
October | 169.64 | 117.32 | 52.32 | 178.15 | 69.60 | 0.00 | 0.00 | 744.00 |
November | 154.58 | 111.96 | 42.62 | 157.52 | 86.47 | 0.00 | 0.00 | 720.00 |
December | 134.33 | 96.99 | 37.35 | 129.10 | 117.71 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 143.97 | 82.93 | 61.04 | 137.22 | 73.04 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 114.13 | 33.27 | 37.35 | 88.87 | 31.37 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 179.97 | 129.44 | 80.86 | 178.29 | 137.18 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_DOOR_2
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 141.27 | 100.88 | 40.39 | 131.36 | 137.18 | 0.00 | 0.00 | 744.00 |
February | 179.97 | 129.44 | 50.53 | 178.29 | 102.13 | 0.00 | 0.00 | 672.00 |
March | 160.93 | 90.40 | 70.53 | 148.99 | 90.23 | 0.00 | 0.00 | 744.00 |
April | 129.32 | 61.86 | 67.46 | 110.02 | 66.01 | 0.00 | 0.00 | 720.00 |
May | 114.87 | 38.14 | 76.73 | 88.87 | 52.91 | 0.00 | 0.00 | 744.00 |
June | 114.13 | 33.27 | 80.86 | 94.74 | 38.83 | 0.00 | 0.00 | 720.00 |
July | 123.04 | 45.43 | 77.61 | 115.10 | 31.37 | 0.00 | 0.00 | 744.00 |
August | 146.25 | 73.73 | 72.52 | 147.09 | 35.39 | 0.00 | 0.00 | 744.00 |
September | 162.28 | 99.46 | 62.82 | 170.87 | 49.81 | 0.00 | 0.00 | 720.00 |
October | 169.64 | 117.32 | 52.32 | 178.15 | 69.60 | 0.00 | 0.00 | 744.00 |
November | 154.58 | 111.96 | 42.62 | 157.52 | 86.47 | 0.00 | 0.00 | 720.00 |
December | 134.33 | 96.99 | 37.35 | 129.10 | 117.71 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 143.97 | 82.93 | 61.04 | 137.22 | 73.04 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 114.13 | 33.27 | 37.35 | 88.87 | 31.37 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 179.97 | 129.44 | 80.86 | 178.29 | 137.18 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.98 | 84.25 | 33.73 | 109.13 | 116.31 | 0.00 | 0.00 | 744.00 |
February | 150.30 | 108.10 | 42.20 | 148.29 | 86.47 | 0.00 | 0.00 | 672.00 |
March | 134.40 | 75.50 | 58.90 | 123.94 | 76.30 | 0.00 | 0.00 | 744.00 |
April | 108.00 | 51.66 | 56.34 | 91.48 | 55.84 | 0.00 | 0.00 | 720.00 |
May | 95.93 | 31.85 | 64.08 | 73.85 | 44.76 | 0.00 | 0.00 | 744.00 |
June | 95.32 | 27.79 | 67.53 | 79.06 | 32.67 | 0.00 | 0.00 | 720.00 |
July | 102.76 | 37.95 | 64.81 | 96.34 | 26.16 | 0.00 | 0.00 | 744.00 |
August | 122.14 | 61.58 | 60.56 | 122.94 | 29.59 | 0.00 | 0.00 | 744.00 |
September | 135.53 | 83.06 | 52.47 | 142.47 | 42.01 | 0.00 | 0.00 | 720.00 |
October | 141.68 | 97.98 | 43.70 | 148.22 | 58.96 | 0.00 | 0.00 | 744.00 |
November | 129.10 | 93.51 | 35.59 | 131.05 | 73.17 | 0.00 | 0.00 | 720.00 |
December | 112.19 | 81.00 | 31.19 | 107.29 | 99.65 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 120.24 | 69.26 | 50.97 | 114.27 | 61.74 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 95.32 | 27.79 | 31.19 | 73.85 | 26.16 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 150.30 | 108.10 | 67.53 | 148.29 | 116.31 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.98 | 84.25 | 33.73 | 109.13 | 116.31 | 0.00 | 0.00 | 744.00 |
February | 150.30 | 108.10 | 42.20 | 148.29 | 86.47 | 0.00 | 0.00 | 672.00 |
March | 134.40 | 75.50 | 58.90 | 123.94 | 76.30 | 0.00 | 0.00 | 744.00 |
April | 108.00 | 51.66 | 56.34 | 91.48 | 55.84 | 0.00 | 0.00 | 720.00 |
May | 95.93 | 31.85 | 64.08 | 73.85 | 44.76 | 0.00 | 0.00 | 744.00 |
June | 95.32 | 27.79 | 67.53 | 79.06 | 32.67 | 0.00 | 0.00 | 720.00 |
July | 102.76 | 37.95 | 64.81 | 96.34 | 26.16 | 0.00 | 0.00 | 744.00 |
August | 122.14 | 61.58 | 60.56 | 122.94 | 29.59 | 0.00 | 0.00 | 744.00 |
September | 135.53 | 83.06 | 52.47 | 142.47 | 42.01 | 0.00 | 0.00 | 720.00 |
October | 141.68 | 97.98 | 43.70 | 148.22 | 58.96 | 0.00 | 0.00 | 744.00 |
November | 129.10 | 93.51 | 35.59 | 131.05 | 73.17 | 0.00 | 0.00 | 720.00 |
December | 112.19 | 81.00 | 31.19 | 107.29 | 99.65 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 120.24 | 69.26 | 50.97 | 114.27 | 61.74 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 95.32 | 27.79 | 31.19 | 73.85 | 26.16 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 150.30 | 108.10 | 67.53 | 148.29 | 116.31 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_DOOR
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 141.27 | 100.88 | 40.39 | 130.93 | 137.96 | 0.00 | 0.00 | 744.00 |
February | 179.97 | 129.44 | 50.53 | 177.78 | 102.62 | 0.00 | 0.00 | 672.00 |
March | 160.93 | 90.40 | 70.53 | 148.62 | 90.57 | 0.00 | 0.00 | 744.00 |
April | 129.32 | 61.86 | 67.46 | 109.66 | 66.32 | 0.00 | 0.00 | 720.00 |
May | 114.87 | 38.14 | 76.73 | 88.54 | 53.17 | 0.00 | 0.00 | 744.00 |
June | 114.13 | 33.27 | 80.86 | 94.66 | 38.84 | 0.00 | 0.00 | 720.00 |
July | 123.04 | 45.43 | 77.61 | 115.25 | 31.15 | 0.00 | 0.00 | 744.00 |
August | 146.25 | 73.73 | 72.52 | 147.10 | 35.22 | 0.00 | 0.00 | 744.00 |
September | 162.28 | 99.46 | 62.82 | 170.56 | 49.95 | 0.00 | 0.00 | 720.00 |
October | 169.64 | 117.32 | 52.32 | 177.54 | 70.09 | 0.00 | 0.00 | 744.00 |
November | 154.58 | 111.96 | 42.62 | 157.05 | 86.90 | 0.00 | 0.00 | 720.00 |
December | 134.33 | 96.99 | 37.35 | 128.69 | 118.27 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 143.97 | 82.93 | 61.04 | 136.91 | 73.33 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 114.13 | 33.27 | 37.35 | 88.54 | 31.15 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 179.97 | 129.44 | 80.86 | 177.78 | 137.96 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.98 | 84.25 | 33.73 | 109.18 | 116.10 | 0.00 | 0.00 | 744.00 |
February | 150.30 | 108.10 | 42.20 | 148.39 | 86.21 | 0.00 | 0.00 | 672.00 |
March | 134.40 | 75.50 | 58.90 | 124.04 | 76.01 | 0.00 | 0.00 | 744.00 |
April | 108.00 | 51.66 | 56.34 | 91.64 | 55.48 | 0.00 | 0.00 | 720.00 |
May | 95.93 | 31.85 | 64.08 | 74.01 | 44.49 | 0.00 | 0.00 | 744.00 |
June | 95.32 | 27.79 | 67.53 | 79.18 | 32.50 | 0.00 | 0.00 | 720.00 |
July | 102.76 | 37.95 | 64.81 | 96.43 | 26.03 | 0.00 | 0.00 | 744.00 |
August | 122.14 | 61.58 | 60.56 | 123.02 | 29.46 | 0.00 | 0.00 | 744.00 |
September | 135.53 | 83.06 | 52.47 | 142.55 | 41.85 | 0.00 | 0.00 | 720.00 |
October | 141.68 | 97.98 | 43.70 | 148.31 | 58.75 | 0.00 | 0.00 | 744.00 |
November | 129.10 | 93.51 | 35.59 | 131.15 | 72.91 | 0.00 | 0.00 | 720.00 |
December | 112.19 | 81.00 | 31.19 | 107.36 | 99.39 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 120.24 | 69.26 | 50.97 | 114.37 | 61.52 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 95.32 | 27.79 | 31.19 | 74.01 | 26.03 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 150.30 | 108.10 | 67.53 | 148.39 | 116.10 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.98 | 84.25 | 33.73 | 109.18 | 116.10 | 0.00 | 0.00 | 744.00 |
February | 150.30 | 108.10 | 42.20 | 148.39 | 86.21 | 0.00 | 0.00 | 672.00 |
March | 134.40 | 75.50 | 58.90 | 124.04 | 76.01 | 0.00 | 0.00 | 744.00 |
April | 108.00 | 51.66 | 56.34 | 91.64 | 55.48 | 0.00 | 0.00 | 720.00 |
May | 95.93 | 31.85 | 64.08 | 74.01 | 44.49 | 0.00 | 0.00 | 744.00 |
June | 95.32 | 27.79 | 67.53 | 79.18 | 32.50 | 0.00 | 0.00 | 720.00 |
July | 102.76 | 37.95 | 64.81 | 96.43 | 26.03 | 0.00 | 0.00 | 744.00 |
August | 122.14 | 61.58 | 60.56 | 123.02 | 29.46 | 0.00 | 0.00 | 744.00 |
September | 135.53 | 83.06 | 52.47 | 142.55 | 41.85 | 0.00 | 0.00 | 720.00 |
October | 141.68 | 97.98 | 43.70 | 148.31 | 58.75 | 0.00 | 0.00 | 744.00 |
November | 129.10 | 93.51 | 35.59 | 131.15 | 72.91 | 0.00 | 0.00 | 720.00 |
December | 112.19 | 81.00 | 31.19 | 107.36 | 99.39 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 120.24 | 69.26 | 50.97 | 114.37 | 61.52 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 95.32 | 27.79 | 31.19 | 74.01 | 26.03 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 150.30 | 108.10 | 67.53 | 148.39 | 116.10 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_DOOR
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 141.27 | 100.88 | 40.39 | 130.98 | 137.71 | 0.00 | 0.00 | 744.00 |
February | 179.97 | 129.44 | 50.53 | 177.90 | 102.32 | 0.00 | 0.00 | 672.00 |
March | 160.93 | 90.40 | 70.53 | 148.73 | 90.22 | 0.00 | 0.00 | 744.00 |
April | 129.32 | 61.86 | 67.46 | 109.85 | 65.90 | 0.00 | 0.00 | 720.00 |
May | 114.87 | 38.14 | 76.73 | 88.73 | 52.84 | 0.00 | 0.00 | 744.00 |
June | 114.13 | 33.27 | 80.86 | 94.81 | 38.64 | 0.00 | 0.00 | 720.00 |
July | 123.04 | 45.43 | 77.61 | 115.36 | 31.00 | 0.00 | 0.00 | 744.00 |
August | 146.25 | 73.73 | 72.52 | 147.19 | 35.07 | 0.00 | 0.00 | 744.00 |
September | 162.28 | 99.46 | 62.82 | 170.66 | 49.77 | 0.00 | 0.00 | 720.00 |
October | 169.64 | 117.32 | 52.32 | 177.65 | 69.84 | 0.00 | 0.00 | 744.00 |
November | 154.58 | 111.96 | 42.62 | 157.18 | 86.59 | 0.00 | 0.00 | 720.00 |
December | 134.33 | 96.99 | 37.35 | 128.78 | 117.97 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 143.97 | 82.93 | 61.04 | 137.03 | 73.06 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 114.13 | 33.27 | 37.35 | 88.73 | 31.00 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 179.97 | 129.44 | 80.86 | 177.90 | 137.71 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.98 | 84.25 | 33.73 | 109.37 | 115.13 | 0.00 | 0.00 | 744.00 |
February | 150.30 | 108.10 | 42.20 | 148.75 | 85.10 | 0.00 | 0.00 | 672.00 |
March | 134.40 | 75.50 | 58.90 | 124.36 | 74.85 | 0.00 | 0.00 | 744.00 |
April | 108.00 | 51.66 | 56.34 | 92.15 | 54.13 | 0.00 | 0.00 | 720.00 |
May | 95.93 | 31.85 | 64.08 | 74.56 | 43.40 | 0.00 | 0.00 | 744.00 |
June | 95.32 | 27.79 | 67.53 | 79.59 | 31.86 | 0.00 | 0.00 | 720.00 |
July | 102.76 | 37.95 | 64.81 | 96.65 | 25.68 | 0.00 | 0.00 | 744.00 |
August | 122.14 | 61.58 | 60.56 | 123.21 | 29.07 | 0.00 | 0.00 | 744.00 |
September | 135.53 | 83.06 | 52.47 | 142.81 | 41.24 | 0.00 | 0.00 | 720.00 |
October | 141.68 | 97.98 | 43.70 | 148.71 | 57.82 | 0.00 | 0.00 | 744.00 |
November | 129.10 | 93.51 | 35.59 | 131.52 | 71.91 | 0.00 | 0.00 | 720.00 |
December | 112.19 | 81.00 | 31.19 | 107.61 | 98.33 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 120.24 | 69.26 | 50.97 | 114.70 | 60.63 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 95.32 | 27.79 | 31.19 | 74.56 | 25.68 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 150.30 | 108.10 | 67.53 | 148.75 | 115.13 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.98 | 84.25 | 33.73 | 109.37 | 115.13 | 0.00 | 0.00 | 744.00 |
February | 150.30 | 108.10 | 42.20 | 148.75 | 85.10 | 0.00 | 0.00 | 672.00 |
March | 134.40 | 75.50 | 58.90 | 124.36 | 74.85 | 0.00 | 0.00 | 744.00 |
April | 108.00 | 51.66 | 56.34 | 92.15 | 54.13 | 0.00 | 0.00 | 720.00 |
May | 95.93 | 31.85 | 64.08 | 74.56 | 43.40 | 0.00 | 0.00 | 744.00 |
June | 95.32 | 27.79 | 67.53 | 79.59 | 31.86 | 0.00 | 0.00 | 720.00 |
July | 102.76 | 37.95 | 64.81 | 96.65 | 25.68 | 0.00 | 0.00 | 744.00 |
August | 122.14 | 61.58 | 60.56 | 123.21 | 29.07 | 0.00 | 0.00 | 744.00 |
September | 135.53 | 83.06 | 52.47 | 142.81 | 41.24 | 0.00 | 0.00 | 720.00 |
October | 141.68 | 97.98 | 43.70 | 148.71 | 57.82 | 0.00 | 0.00 | 744.00 |
November | 129.10 | 93.51 | 35.59 | 131.52 | 71.91 | 0.00 | 0.00 | 720.00 |
December | 112.19 | 81.00 | 31.19 | 107.61 | 98.33 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 120.24 | 69.26 | 50.97 | 114.70 | 60.63 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 95.32 | 27.79 | 31.19 | 74.56 | 25.68 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 150.30 | 108.10 | 67.53 | 148.75 | 115.13 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_DOOR
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 141.27 | 100.88 | 40.39 | 131.21 | 136.55 | 0.00 | 0.00 | 744.00 |
February | 179.97 | 129.44 | 50.53 | 178.34 | 100.99 | 0.00 | 0.00 | 672.00 |
March | 160.93 | 90.40 | 70.53 | 149.12 | 88.85 | 0.00 | 0.00 | 744.00 |
April | 129.32 | 61.86 | 67.46 | 110.47 | 64.30 | 0.00 | 0.00 | 720.00 |
May | 114.87 | 38.14 | 76.73 | 89.40 | 51.56 | 0.00 | 0.00 | 744.00 |
June | 114.13 | 33.27 | 80.86 | 95.31 | 37.88 | 0.00 | 0.00 | 720.00 |
July | 123.04 | 45.43 | 77.61 | 115.61 | 30.58 | 0.00 | 0.00 | 744.00 |
August | 146.25 | 73.73 | 72.52 | 147.43 | 34.60 | 0.00 | 0.00 | 744.00 |
September | 162.28 | 99.46 | 62.82 | 170.98 | 49.04 | 0.00 | 0.00 | 720.00 |
October | 169.64 | 117.32 | 52.32 | 178.13 | 68.74 | 0.00 | 0.00 | 744.00 |
November | 154.58 | 111.96 | 42.62 | 157.63 | 85.40 | 0.00 | 0.00 | 720.00 |
December | 134.33 | 96.99 | 37.35 | 129.08 | 116.71 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 143.97 | 82.93 | 61.04 | 137.44 | 72.00 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 114.13 | 33.27 | 37.35 | 89.40 | 30.58 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 179.97 | 129.44 | 80.86 | 178.34 | 136.55 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.98 | 84.25 | 33.73 | 110.12 | 110.93 | 0.00 | 0.00 | 744.00 |
February | 150.30 | 108.10 | 42.20 | 149.91 | 80.67 | 0.00 | 0.00 | 672.00 |
March | 134.40 | 75.50 | 58.90 | 125.42 | 70.30 | 0.00 | 0.00 | 744.00 |
April | 108.00 | 51.66 | 56.34 | 93.52 | 49.59 | 0.00 | 0.00 | 720.00 |
May | 95.93 | 31.85 | 64.08 | 76.02 | 39.79 | 0.00 | 0.00 | 744.00 |
June | 95.32 | 27.79 | 67.53 | 80.75 | 29.48 | 0.00 | 0.00 | 720.00 |
July | 102.76 | 37.95 | 64.81 | 97.13 | 24.32 | 0.00 | 0.00 | 744.00 |
August | 122.14 | 61.58 | 60.56 | 123.66 | 27.59 | 0.00 | 0.00 | 744.00 |
September | 135.53 | 83.06 | 52.47 | 143.44 | 39.11 | 0.00 | 0.00 | 720.00 |
October | 141.68 | 97.98 | 43.70 | 149.67 | 54.86 | 0.00 | 0.00 | 744.00 |
November | 129.10 | 93.51 | 35.59 | 132.57 | 68.38 | 0.00 | 0.00 | 720.00 |
December | 112.19 | 81.00 | 31.19 | 108.47 | 94.10 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 120.24 | 69.26 | 50.97 | 115.65 | 57.35 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 95.32 | 27.79 | 31.19 | 76.02 | 24.32 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 150.30 | 108.10 | 67.53 | 149.91 | 110.93 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.98 | 84.25 | 33.73 | 110.12 | 110.93 | 0.00 | 0.00 | 744.00 |
February | 150.30 | 108.10 | 42.20 | 149.91 | 80.67 | 0.00 | 0.00 | 672.00 |
March | 134.40 | 75.50 | 58.90 | 125.42 | 70.30 | 0.00 | 0.00 | 744.00 |
April | 108.00 | 51.66 | 56.34 | 93.52 | 49.59 | 0.00 | 0.00 | 720.00 |
May | 95.93 | 31.85 | 64.08 | 76.02 | 39.79 | 0.00 | 0.00 | 744.00 |
June | 95.32 | 27.79 | 67.53 | 80.75 | 29.48 | 0.00 | 0.00 | 720.00 |
July | 102.76 | 37.95 | 64.81 | 97.13 | 24.32 | 0.00 | 0.00 | 744.00 |
August | 122.14 | 61.58 | 60.56 | 123.66 | 27.59 | 0.00 | 0.00 | 744.00 |
September | 135.53 | 83.06 | 52.47 | 143.44 | 39.11 | 0.00 | 0.00 | 720.00 |
October | 141.68 | 97.98 | 43.70 | 149.67 | 54.86 | 0.00 | 0.00 | 744.00 |
November | 129.10 | 93.51 | 35.59 | 132.57 | 68.38 | 0.00 | 0.00 | 720.00 |
December | 112.19 | 81.00 | 31.19 | 108.47 | 94.10 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 120.24 | 69.26 | 50.97 | 115.65 | 57.35 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 95.32 | 27.79 | 31.19 | 76.02 | 24.32 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 150.30 | 108.10 | 67.53 | 149.91 | 110.93 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_DOOR
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 141.27 | 100.88 | 40.39 | 132.13 | 131.54 | 0.00 | 0.00 | 744.00 |
February | 179.97 | 129.44 | 50.53 | 179.74 | 95.73 | 0.00 | 0.00 | 672.00 |
March | 160.93 | 90.40 | 70.53 | 150.42 | 83.44 | 0.00 | 0.00 | 744.00 |
April | 129.32 | 61.86 | 67.46 | 112.12 | 58.91 | 0.00 | 0.00 | 720.00 |
May | 114.87 | 38.14 | 76.73 | 91.15 | 47.27 | 0.00 | 0.00 | 744.00 |
June | 114.13 | 33.27 | 80.86 | 96.70 | 35.06 | 0.00 | 0.00 | 720.00 |
July | 123.04 | 45.43 | 77.61 | 116.19 | 28.98 | 0.00 | 0.00 | 744.00 |
August | 146.25 | 73.73 | 72.52 | 147.97 | 32.85 | 0.00 | 0.00 | 744.00 |
September | 162.28 | 99.46 | 62.82 | 171.73 | 46.53 | 0.00 | 0.00 | 720.00 |
October | 169.64 | 117.32 | 52.32 | 179.28 | 65.22 | 0.00 | 0.00 | 744.00 |
November | 154.58 | 111.96 | 42.62 | 158.89 | 81.21 | 0.00 | 0.00 | 720.00 |
December | 134.33 | 96.99 | 37.35 | 130.12 | 111.68 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 143.97 | 82.93 | 61.04 | 138.58 | 68.12 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 114.13 | 33.27 | 37.35 | 91.15 | 28.98 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 179.97 | 129.44 | 80.86 | 179.74 | 131.54 | 0.00 | 0.00 | 744.00 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.316004E+09 | 0.225666E+09 | 90338001.12 | 0.292657E+09 | 0.316813E+09 |
February | 0.363612E+09 | 0.261526E+09 | 0.102086E+09 | 0.358953E+09 | 0.212582E+09 |
March | 0.359988E+09 | 0.202219E+09 | 0.157769E+09 | 0.332566E+09 | 0.206655E+09 |
April | 0.279938E+09 | 0.133906E+09 | 0.146032E+09 | 0.237498E+09 | 0.145788E+09 |
May | 0.256951E+09 | 85313868.24 | 0.171637E+09 | 0.198034E+09 | 0.120984E+09 |
June | 0.247064E+09 | 72023907.49 | 0.175040E+09 | 0.206060E+09 | 83200836.73 |
July | 0.275231E+09 | 0.101633E+09 | 0.173598E+09 | 0.259415E+09 | 67925285.93 |
August | 0.327145E+09 | 0.164932E+09 | 0.162213E+09 | 0.330450E+09 | 77327043.17 |
September | 0.351293E+09 | 0.215301E+09 | 0.135992E+09 | 0.370634E+09 | 0.107041E+09 |
October | 0.379464E+09 | 0.262428E+09 | 0.117035E+09 | 0.397570E+09 | 0.158557E+09 |
November | 0.334629E+09 | 0.242372E+09 | 92257076.27 | 0.339579E+09 | 0.193214E+09 |
December | 0.300488E+09 | 0.216951E+09 | 83537300.00 | 0.287444E+09 | 0.271409E+09 |
Annual Sum or Average | 0.379181E+10 | 0.218427E+10 | 0.160754E+10 | 0.361086E+10 | 0.196150E+10 |
Minimum of Months | 0.247064E+09 | 72023907.49 | 83537300.00 | 0.198034E+09 | 67925285.93 |
Maximum of Months | 0.379464E+09 | 0.262428E+09 | 0.175040E+09 | 0.397570E+09 | 0.316813E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.316004E+09 | 0.225666E+09 | 90338001.12 | 0.292657E+09 | 0.316813E+09 |
February | 0.363612E+09 | 0.261526E+09 | 0.102086E+09 | 0.358953E+09 | 0.212582E+09 |
March | 0.359988E+09 | 0.202219E+09 | 0.157769E+09 | 0.332566E+09 | 0.206655E+09 |
April | 0.279938E+09 | 0.133906E+09 | 0.146032E+09 | 0.237498E+09 | 0.145788E+09 |
May | 0.256951E+09 | 85313868.24 | 0.171637E+09 | 0.198034E+09 | 0.120984E+09 |
June | 0.247064E+09 | 72023907.49 | 0.175040E+09 | 0.206060E+09 | 83200836.73 |
July | 0.275231E+09 | 0.101633E+09 | 0.173598E+09 | 0.259415E+09 | 67925285.93 |
August | 0.327145E+09 | 0.164932E+09 | 0.162213E+09 | 0.330450E+09 | 77327043.17 |
September | 0.351293E+09 | 0.215301E+09 | 0.135992E+09 | 0.370634E+09 | 0.107041E+09 |
October | 0.379464E+09 | 0.262428E+09 | 0.117035E+09 | 0.397570E+09 | 0.158557E+09 |
November | 0.334629E+09 | 0.242372E+09 | 92257076.27 | 0.339579E+09 | 0.193214E+09 |
December | 0.300488E+09 | 0.216951E+09 | 83537300.00 | 0.287444E+09 | 0.271409E+09 |
Annual Sum or Average | 0.379181E+10 | 0.218427E+10 | 0.160754E+10 | 0.361086E+10 | 0.196150E+10 |
Minimum of Months | 0.247064E+09 | 72023907.49 | 83537300.00 | 0.198034E+09 | 67925285.93 |
Maximum of Months | 0.379464E+09 | 0.262428E+09 | 0.175040E+09 | 0.397570E+09 | 0.316813E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_3
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.316004E+09 | 0.225666E+09 | 90338001.12 | 0.292657E+09 | 0.316813E+09 |
February | 0.363612E+09 | 0.261526E+09 | 0.102086E+09 | 0.358953E+09 | 0.212582E+09 |
March | 0.359988E+09 | 0.202219E+09 | 0.157769E+09 | 0.332566E+09 | 0.206655E+09 |
April | 0.279938E+09 | 0.133906E+09 | 0.146032E+09 | 0.237498E+09 | 0.145788E+09 |
May | 0.256951E+09 | 85313868.24 | 0.171637E+09 | 0.198034E+09 | 0.120984E+09 |
June | 0.247064E+09 | 72023907.49 | 0.175040E+09 | 0.206060E+09 | 83200836.73 |
July | 0.275231E+09 | 0.101633E+09 | 0.173598E+09 | 0.259415E+09 | 67925285.93 |
August | 0.327145E+09 | 0.164932E+09 | 0.162213E+09 | 0.330450E+09 | 77327043.17 |
September | 0.351293E+09 | 0.215301E+09 | 0.135992E+09 | 0.370634E+09 | 0.107041E+09 |
October | 0.379464E+09 | 0.262428E+09 | 0.117035E+09 | 0.397570E+09 | 0.158557E+09 |
November | 0.334629E+09 | 0.242372E+09 | 92257076.27 | 0.339579E+09 | 0.193214E+09 |
December | 0.300488E+09 | 0.216951E+09 | 83537300.00 | 0.287444E+09 | 0.271409E+09 |
Annual Sum or Average | 0.379181E+10 | 0.218427E+10 | 0.160754E+10 | 0.361086E+10 | 0.196150E+10 |
Minimum of Months | 0.247064E+09 | 72023907.49 | 83537300.00 | 0.198034E+09 | 67925285.93 |
Maximum of Months | 0.379464E+09 | 0.262428E+09 | 0.175040E+09 | 0.397570E+09 | 0.316813E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_4
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.316004E+09 | 0.225666E+09 | 90338001.12 | 0.292657E+09 | 0.316813E+09 |
February | 0.363612E+09 | 0.261526E+09 | 0.102086E+09 | 0.358953E+09 | 0.212582E+09 |
March | 0.359988E+09 | 0.202219E+09 | 0.157769E+09 | 0.332566E+09 | 0.206655E+09 |
April | 0.279938E+09 | 0.133906E+09 | 0.146032E+09 | 0.237498E+09 | 0.145788E+09 |
May | 0.256951E+09 | 85313868.24 | 0.171637E+09 | 0.198034E+09 | 0.120984E+09 |
June | 0.247064E+09 | 72023907.49 | 0.175040E+09 | 0.206060E+09 | 83200836.73 |
July | 0.275231E+09 | 0.101633E+09 | 0.173598E+09 | 0.259415E+09 | 67925285.93 |
August | 0.327145E+09 | 0.164932E+09 | 0.162213E+09 | 0.330450E+09 | 77327043.17 |
September | 0.351293E+09 | 0.215301E+09 | 0.135992E+09 | 0.370634E+09 | 0.107041E+09 |
October | 0.379464E+09 | 0.262428E+09 | 0.117035E+09 | 0.397570E+09 | 0.158557E+09 |
November | 0.334629E+09 | 0.242372E+09 | 92257076.27 | 0.339579E+09 | 0.193214E+09 |
December | 0.300488E+09 | 0.216951E+09 | 83537300.00 | 0.287444E+09 | 0.271409E+09 |
Annual Sum or Average | 0.379181E+10 | 0.218427E+10 | 0.160754E+10 | 0.361086E+10 | 0.196150E+10 |
Minimum of Months | 0.247064E+09 | 72023907.49 | 83537300.00 | 0.198034E+09 | 67925285.93 |
Maximum of Months | 0.379464E+09 | 0.262428E+09 | 0.175040E+09 | 0.397570E+09 | 0.316813E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_DOOR_1
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.380453E+09 | 0.271690E+09 | 0.108762E+09 | 0.352960E+09 | 0.377938E+09 |
February | 0.437770E+09 | 0.314863E+09 | 0.122907E+09 | 0.432639E+09 | 0.253757E+09 |
March | 0.433407E+09 | 0.243461E+09 | 0.189946E+09 | 0.400889E+09 | 0.246730E+09 |
April | 0.337031E+09 | 0.161216E+09 | 0.175815E+09 | 0.286203E+09 | 0.174216E+09 |
May | 0.309355E+09 | 0.102713E+09 | 0.206642E+09 | 0.238679E+09 | 0.144594E+09 |
June | 0.297452E+09 | 86712993.89 | 0.210739E+09 | 0.248041E+09 | 99537962.07 |
July | 0.331364E+09 | 0.122361E+09 | 0.209003E+09 | 0.311968E+09 | 81415936.59 |
August | 0.393866E+09 | 0.198570E+09 | 0.195296E+09 | 0.397518E+09 | 92643417.55 |
September | 0.422938E+09 | 0.259211E+09 | 0.163727E+09 | 0.446086E+09 | 0.128100E+09 |
October | 0.456854E+09 | 0.315950E+09 | 0.140904E+09 | 0.478749E+09 | 0.189633E+09 |
November | 0.402876E+09 | 0.291803E+09 | 0.111073E+09 | 0.409134E+09 | 0.230827E+09 |
December | 0.361772E+09 | 0.261197E+09 | 0.100575E+09 | 0.346599E+09 | 0.323998E+09 |
Annual Sum or Average | 0.456514E+10 | 0.262975E+10 | 0.193539E+10 | 0.434947E+10 | 0.234339E+10 |
Minimum of Months | 0.297452E+09 | 86712993.89 | 0.100575E+09 | 0.238679E+09 | 81415936.59 |
Maximum of Months | 0.456854E+09 | 0.315950E+09 | 0.210739E+09 | 0.478749E+09 | 0.377938E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_DOOR_2
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.380453E+09 | 0.271690E+09 | 0.108762E+09 | 0.352960E+09 | 0.377938E+09 |
February | 0.437770E+09 | 0.314863E+09 | 0.122907E+09 | 0.432639E+09 | 0.253757E+09 |
March | 0.433407E+09 | 0.243461E+09 | 0.189946E+09 | 0.400889E+09 | 0.246730E+09 |
April | 0.337031E+09 | 0.161216E+09 | 0.175815E+09 | 0.286203E+09 | 0.174216E+09 |
May | 0.309355E+09 | 0.102713E+09 | 0.206642E+09 | 0.238679E+09 | 0.144594E+09 |
June | 0.297452E+09 | 86712993.89 | 0.210739E+09 | 0.248041E+09 | 99537962.07 |
July | 0.331364E+09 | 0.122361E+09 | 0.209003E+09 | 0.311968E+09 | 81415936.59 |
August | 0.393866E+09 | 0.198570E+09 | 0.195296E+09 | 0.397518E+09 | 92643417.55 |
September | 0.422938E+09 | 0.259211E+09 | 0.163727E+09 | 0.446086E+09 | 0.128100E+09 |
October | 0.456854E+09 | 0.315950E+09 | 0.140904E+09 | 0.478749E+09 | 0.189633E+09 |
November | 0.402876E+09 | 0.291803E+09 | 0.111073E+09 | 0.409134E+09 | 0.230827E+09 |
December | 0.361772E+09 | 0.261197E+09 | 0.100575E+09 | 0.346599E+09 | 0.323998E+09 |
Annual Sum or Average | 0.456514E+10 | 0.262975E+10 | 0.193539E+10 | 0.434947E+10 | 0.234339E+10 |
Minimum of Months | 0.297452E+09 | 86712993.89 | 0.100575E+09 | 0.238679E+09 | 81415936.59 |
Maximum of Months | 0.456854E+09 | 0.315950E+09 | 0.210739E+09 | 0.478749E+09 | 0.377938E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.316004E+09 | 0.225666E+09 | 90338001.12 | 0.289841E+09 | 0.327824E+09 |
February | 0.363612E+09 | 0.261526E+09 | 0.102086E+09 | 0.355034E+09 | 0.222635E+09 |
March | 0.359988E+09 | 0.202219E+09 | 0.157769E+09 | 0.328634E+09 | 0.218551E+09 |
April | 0.279938E+09 | 0.133906E+09 | 0.146032E+09 | 0.232671E+09 | 0.158141E+09 |
May | 0.256951E+09 | 85313868.24 | 0.171637E+09 | 0.193991E+09 | 0.129369E+09 |
June | 0.247064E+09 | 72023907.49 | 0.175040E+09 | 0.203953E+09 | 86079280.07 |
July | 0.275231E+09 | 0.101633E+09 | 0.173598E+09 | 0.258750E+09 | 68857405.37 |
August | 0.327145E+09 | 0.164932E+09 | 0.162213E+09 | 0.329493E+09 | 78639863.73 |
September | 0.351293E+09 | 0.215301E+09 | 0.135992E+09 | 0.368420E+09 | 0.111176E+09 |
October | 0.379464E+09 | 0.262428E+09 | 0.117035E+09 | 0.393528E+09 | 0.167290E+09 |
November | 0.334629E+09 | 0.242372E+09 | 92257076.27 | 0.335241E+09 | 0.203932E+09 |
December | 0.300488E+09 | 0.216951E+09 | 83537300.00 | 0.284415E+09 | 0.281757E+09 |
Annual Sum or Average | 0.379181E+10 | 0.218427E+10 | 0.160754E+10 | 0.357397E+10 | 0.205425E+10 |
Minimum of Months | 0.247064E+09 | 72023907.49 | 83537300.00 | 0.193991E+09 | 68857405.37 |
Maximum of Months | 0.379464E+09 | 0.262428E+09 | 0.175040E+09 | 0.393528E+09 | 0.327824E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.316004E+09 | 0.225666E+09 | 90338001.12 | 0.289841E+09 | 0.327824E+09 |
February | 0.363612E+09 | 0.261526E+09 | 0.102086E+09 | 0.355034E+09 | 0.222635E+09 |
March | 0.359988E+09 | 0.202219E+09 | 0.157769E+09 | 0.328634E+09 | 0.218551E+09 |
April | 0.279938E+09 | 0.133906E+09 | 0.146032E+09 | 0.232671E+09 | 0.158141E+09 |
May | 0.256951E+09 | 85313868.24 | 0.171637E+09 | 0.193991E+09 | 0.129369E+09 |
June | 0.247064E+09 | 72023907.49 | 0.175040E+09 | 0.203953E+09 | 86079280.07 |
July | 0.275231E+09 | 0.101633E+09 | 0.173598E+09 | 0.258750E+09 | 68857405.37 |
August | 0.327145E+09 | 0.164932E+09 | 0.162213E+09 | 0.329493E+09 | 78639863.73 |
September | 0.351293E+09 | 0.215301E+09 | 0.135992E+09 | 0.368420E+09 | 0.111176E+09 |
October | 0.379464E+09 | 0.262428E+09 | 0.117035E+09 | 0.393528E+09 | 0.167290E+09 |
November | 0.334629E+09 | 0.242372E+09 | 92257076.27 | 0.335241E+09 | 0.203932E+09 |
December | 0.300488E+09 | 0.216951E+09 | 83537300.00 | 0.284415E+09 | 0.281757E+09 |
Annual Sum or Average | 0.379181E+10 | 0.218427E+10 | 0.160754E+10 | 0.357397E+10 | 0.205425E+10 |
Minimum of Months | 0.247064E+09 | 72023907.49 | 83537300.00 | 0.193991E+09 | 68857405.37 |
Maximum of Months | 0.379464E+09 | 0.262428E+09 | 0.175040E+09 | 0.393528E+09 | 0.327824E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_DOOR
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.380453E+09 | 0.271690E+09 | 0.108762E+09 | 0.349582E+09 | 0.391024E+09 |
February | 0.437770E+09 | 0.314863E+09 | 0.122907E+09 | 0.427955E+09 | 0.265682E+09 |
March | 0.433407E+09 | 0.243461E+09 | 0.189946E+09 | 0.396168E+09 | 0.260843E+09 |
April | 0.337031E+09 | 0.161216E+09 | 0.175815E+09 | 0.280405E+09 | 0.188870E+09 |
May | 0.309355E+09 | 0.102713E+09 | 0.206642E+09 | 0.233812E+09 | 0.154520E+09 |
June | 0.297452E+09 | 86712993.89 | 0.210739E+09 | 0.245510E+09 | 0.102951E+09 |
July | 0.331364E+09 | 0.122361E+09 | 0.209003E+09 | 0.311161E+09 | 82521225.46 |
August | 0.393866E+09 | 0.198570E+09 | 0.195296E+09 | 0.396367E+09 | 94194394.59 |
September | 0.422938E+09 | 0.259211E+09 | 0.163727E+09 | 0.443447E+09 | 0.132988E+09 |
October | 0.456854E+09 | 0.315950E+09 | 0.140904E+09 | 0.473940E+09 | 0.199970E+09 |
November | 0.402876E+09 | 0.291803E+09 | 0.111073E+09 | 0.403961E+09 | 0.243518E+09 |
December | 0.361772E+09 | 0.261197E+09 | 0.100575E+09 | 0.342973E+09 | 0.336274E+09 |
Annual Sum or Average | 0.456514E+10 | 0.262975E+10 | 0.193539E+10 | 0.430528E+10 | 0.245335E+10 |
Minimum of Months | 0.297452E+09 | 86712993.89 | 0.100575E+09 | 0.233812E+09 | 82521225.46 |
Maximum of Months | 0.456854E+09 | 0.315950E+09 | 0.210739E+09 | 0.473940E+09 | 0.391024E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.316004E+09 | 0.225666E+09 | 90338001.12 | 0.290256E+09 | 0.321039E+09 |
February | 0.363612E+09 | 0.261526E+09 | 0.102086E+09 | 0.355804E+09 | 0.217521E+09 |
March | 0.359988E+09 | 0.202219E+09 | 0.157769E+09 | 0.329310E+09 | 0.213232E+09 |
April | 0.279938E+09 | 0.133906E+09 | 0.146032E+09 | 0.233445E+09 | 0.154255E+09 |
May | 0.256951E+09 | 85313868.24 | 0.171637E+09 | 0.194300E+09 | 0.127751E+09 |
June | 0.247064E+09 | 72023907.49 | 0.175040E+09 | 0.203339E+09 | 88677003.52 |
July | 0.275231E+09 | 0.101633E+09 | 0.173598E+09 | 0.257371E+09 | 73348510.65 |
August | 0.327145E+09 | 0.164932E+09 | 0.162213E+09 | 0.328591E+09 | 82954526.02 |
September | 0.351293E+09 | 0.215301E+09 | 0.135992E+09 | 0.367974E+09 | 0.113510E+09 |
October | 0.379464E+09 | 0.262428E+09 | 0.117035E+09 | 0.394138E+09 | 0.165695E+09 |
November | 0.334629E+09 | 0.242372E+09 | 92257076.27 | 0.336329E+09 | 0.199178E+09 |
December | 0.300488E+09 | 0.216951E+09 | 83537300.00 | 0.285047E+09 | 0.275784E+09 |
Annual Sum or Average | 0.379181E+10 | 0.218427E+10 | 0.160754E+10 | 0.357590E+10 | 0.203295E+10 |
Minimum of Months | 0.247064E+09 | 72023907.49 | 83537300.00 | 0.194300E+09 | 73348510.65 |
Maximum of Months | 0.379464E+09 | 0.262428E+09 | 0.175040E+09 | 0.394138E+09 | 0.321039E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.316004E+09 | 0.225666E+09 | 90338001.12 | 0.290256E+09 | 0.321039E+09 |
February | 0.363612E+09 | 0.261526E+09 | 0.102086E+09 | 0.355804E+09 | 0.217521E+09 |
March | 0.359988E+09 | 0.202219E+09 | 0.157769E+09 | 0.329310E+09 | 0.213232E+09 |
April | 0.279938E+09 | 0.133906E+09 | 0.146032E+09 | 0.233445E+09 | 0.154255E+09 |
May | 0.256951E+09 | 85313868.24 | 0.171637E+09 | 0.194300E+09 | 0.127751E+09 |
June | 0.247064E+09 | 72023907.49 | 0.175040E+09 | 0.203339E+09 | 88677003.52 |
July | 0.275231E+09 | 0.101633E+09 | 0.173598E+09 | 0.257371E+09 | 73348510.65 |
August | 0.327145E+09 | 0.164932E+09 | 0.162213E+09 | 0.328591E+09 | 82954526.02 |
September | 0.351293E+09 | 0.215301E+09 | 0.135992E+09 | 0.367974E+09 | 0.113510E+09 |
October | 0.379464E+09 | 0.262428E+09 | 0.117035E+09 | 0.394138E+09 | 0.165695E+09 |
November | 0.334629E+09 | 0.242372E+09 | 92257076.27 | 0.336329E+09 | 0.199178E+09 |
December | 0.300488E+09 | 0.216951E+09 | 83537300.00 | 0.285047E+09 | 0.275784E+09 |
Annual Sum or Average | 0.379181E+10 | 0.218427E+10 | 0.160754E+10 | 0.357590E+10 | 0.203295E+10 |
Minimum of Months | 0.247064E+09 | 72023907.49 | 83537300.00 | 0.194300E+09 | 73348510.65 |
Maximum of Months | 0.379464E+09 | 0.262428E+09 | 0.175040E+09 | 0.394138E+09 | 0.321039E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_DOOR
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.378374E+09 | 0.270206E+09 | 0.108168E+09 | 0.348185E+09 | 0.380846E+09 |
February | 0.435378E+09 | 0.313143E+09 | 0.122235E+09 | 0.426549E+09 | 0.258184E+09 |
March | 0.431038E+09 | 0.242130E+09 | 0.188908E+09 | 0.394823E+09 | 0.253130E+09 |
April | 0.335189E+09 | 0.160335E+09 | 0.174854E+09 | 0.279803E+09 | 0.183242E+09 |
May | 0.307665E+09 | 0.102152E+09 | 0.205513E+09 | 0.232913E+09 | 0.151737E+09 |
June | 0.295827E+09 | 86239152.39 | 0.209588E+09 | 0.243442E+09 | 0.105411E+09 |
July | 0.329553E+09 | 0.121693E+09 | 0.207861E+09 | 0.307836E+09 | 87325404.26 |
August | 0.391714E+09 | 0.197485E+09 | 0.194229E+09 | 0.393132E+09 | 98726467.59 |
September | 0.420627E+09 | 0.257795E+09 | 0.162832E+09 | 0.440501E+09 | 0.134978E+09 |
October | 0.454358E+09 | 0.314223E+09 | 0.140134E+09 | 0.472079E+09 | 0.196961E+09 |
November | 0.400674E+09 | 0.290209E+09 | 0.110466E+09 | 0.403057E+09 | 0.236560E+09 |
December | 0.359795E+09 | 0.259770E+09 | 0.100025E+09 | 0.341869E+09 | 0.327366E+09 |
Annual Sum or Average | 0.454019E+10 | 0.261538E+10 | 0.192481E+10 | 0.428419E+10 | 0.241447E+10 |
Minimum of Months | 0.295827E+09 | 86239152.39 | 0.100025E+09 | 0.232913E+09 | 87325404.26 |
Maximum of Months | 0.454358E+09 | 0.314223E+09 | 0.209588E+09 | 0.472079E+09 | 0.380846E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.316004E+09 | 0.225666E+09 | 90338001.12 | 0.290637E+09 | 0.318303E+09 |
February | 0.363612E+09 | 0.261526E+09 | 0.102086E+09 | 0.356396E+09 | 0.215196E+09 |
March | 0.359988E+09 | 0.202219E+09 | 0.157769E+09 | 0.329861E+09 | 0.210805E+09 |
April | 0.279938E+09 | 0.133906E+09 | 0.146032E+09 | 0.234216E+09 | 0.151847E+09 |
May | 0.256951E+09 | 85313868.24 | 0.171637E+09 | 0.194917E+09 | 0.126030E+09 |
June | 0.247064E+09 | 72023907.49 | 0.175040E+09 | 0.203471E+09 | 88386122.52 |
July | 0.275231E+09 | 0.101633E+09 | 0.173598E+09 | 0.257308E+09 | 73534229.38 |
August | 0.327145E+09 | 0.164932E+09 | 0.162213E+09 | 0.328556E+09 | 83056560.08 |
September | 0.351293E+09 | 0.215301E+09 | 0.135992E+09 | 0.368142E+09 | 0.113002E+09 |
October | 0.379464E+09 | 0.262428E+09 | 0.117035E+09 | 0.394688E+09 | 0.163923E+09 |
November | 0.334629E+09 | 0.242372E+09 | 92257076.27 | 0.337088E+09 | 0.196555E+09 |
December | 0.300488E+09 | 0.216951E+09 | 83537300.00 | 0.285490E+09 | 0.273269E+09 |
Annual Sum or Average | 0.379181E+10 | 0.218427E+10 | 0.160754E+10 | 0.358077E+10 | 0.201391E+10 |
Minimum of Months | 0.247064E+09 | 72023907.49 | 83537300.00 | 0.194917E+09 | 73534229.38 |
Maximum of Months | 0.379464E+09 | 0.262428E+09 | 0.175040E+09 | 0.394688E+09 | 0.318303E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.316004E+09 | 0.225666E+09 | 90338001.12 | 0.290637E+09 | 0.318303E+09 |
February | 0.363612E+09 | 0.261526E+09 | 0.102086E+09 | 0.356396E+09 | 0.215196E+09 |
March | 0.359988E+09 | 0.202219E+09 | 0.157769E+09 | 0.329861E+09 | 0.210805E+09 |
April | 0.279938E+09 | 0.133906E+09 | 0.146032E+09 | 0.234216E+09 | 0.151847E+09 |
May | 0.256951E+09 | 85313868.24 | 0.171637E+09 | 0.194917E+09 | 0.126030E+09 |
June | 0.247064E+09 | 72023907.49 | 0.175040E+09 | 0.203471E+09 | 88386122.52 |
July | 0.275231E+09 | 0.101633E+09 | 0.173598E+09 | 0.257308E+09 | 73534229.38 |
August | 0.327145E+09 | 0.164932E+09 | 0.162213E+09 | 0.328556E+09 | 83056560.08 |
September | 0.351293E+09 | 0.215301E+09 | 0.135992E+09 | 0.368142E+09 | 0.113002E+09 |
October | 0.379464E+09 | 0.262428E+09 | 0.117035E+09 | 0.394688E+09 | 0.163923E+09 |
November | 0.334629E+09 | 0.242372E+09 | 92257076.27 | 0.337088E+09 | 0.196555E+09 |
December | 0.300488E+09 | 0.216951E+09 | 83537300.00 | 0.285490E+09 | 0.273269E+09 |
Annual Sum or Average | 0.379181E+10 | 0.218427E+10 | 0.160754E+10 | 0.358077E+10 | 0.201391E+10 |
Minimum of Months | 0.247064E+09 | 72023907.49 | 83537300.00 | 0.194917E+09 | 73534229.38 |
Maximum of Months | 0.379464E+09 | 0.262428E+09 | 0.175040E+09 | 0.394688E+09 | 0.318303E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_DOOR
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.378374E+09 | 0.270206E+09 | 0.108168E+09 | 0.348649E+09 | 0.377585E+09 |
February | 0.435378E+09 | 0.313143E+09 | 0.122235E+09 | 0.427263E+09 | 0.255416E+09 |
March | 0.431038E+09 | 0.242130E+09 | 0.188908E+09 | 0.395490E+09 | 0.250241E+09 |
April | 0.335189E+09 | 0.160335E+09 | 0.174854E+09 | 0.280730E+09 | 0.180380E+09 |
May | 0.307665E+09 | 0.102152E+09 | 0.205513E+09 | 0.233657E+09 | 0.149692E+09 |
June | 0.295827E+09 | 86239152.39 | 0.209588E+09 | 0.243601E+09 | 0.105065E+09 |
July | 0.329553E+09 | 0.121693E+09 | 0.207861E+09 | 0.307760E+09 | 87545843.72 |
August | 0.391714E+09 | 0.197485E+09 | 0.194229E+09 | 0.393090E+09 | 98847071.03 |
September | 0.420627E+09 | 0.257795E+09 | 0.162832E+09 | 0.440703E+09 | 0.134374E+09 |
October | 0.454358E+09 | 0.314223E+09 | 0.140134E+09 | 0.472741E+09 | 0.194856E+09 |
November | 0.400674E+09 | 0.290209E+09 | 0.110466E+09 | 0.403967E+09 | 0.233438E+09 |
December | 0.359795E+09 | 0.259770E+09 | 0.100025E+09 | 0.342408E+09 | 0.324372E+09 |
Annual Sum or Average | 0.454019E+10 | 0.261538E+10 | 0.192481E+10 | 0.429006E+10 | 0.239181E+10 |
Minimum of Months | 0.295827E+09 | 86239152.39 | 0.100025E+09 | 0.233657E+09 | 87545843.72 |
Maximum of Months | 0.454358E+09 | 0.314223E+09 | 0.209588E+09 | 0.472741E+09 | 0.377585E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.316004E+09 | 0.225666E+09 | 90338001.12 | 0.291054E+09 | 0.316290E+09 |
February | 0.363612E+09 | 0.261526E+09 | 0.102086E+09 | 0.357060E+09 | 0.213323E+09 |
March | 0.359988E+09 | 0.202219E+09 | 0.157769E+09 | 0.330488E+09 | 0.208830E+09 |
April | 0.279938E+09 | 0.133906E+09 | 0.146032E+09 | 0.235233E+09 | 0.149418E+09 |
May | 0.256951E+09 | 85313868.24 | 0.171637E+09 | 0.195914E+09 | 0.124031E+09 |
June | 0.247064E+09 | 72023907.49 | 0.175040E+09 | 0.203985E+09 | 87432962.02 |
July | 0.275231E+09 | 0.101633E+09 | 0.173598E+09 | 0.257623E+09 | 72835863.66 |
August | 0.327145E+09 | 0.164932E+09 | 0.162213E+09 | 0.328876E+09 | 82241159.16 |
September | 0.351293E+09 | 0.215301E+09 | 0.135992E+09 | 0.368645E+09 | 0.111772E+09 |
October | 0.379464E+09 | 0.262428E+09 | 0.117035E+09 | 0.395585E+09 | 0.161799E+09 |
November | 0.334629E+09 | 0.242372E+09 | 92257076.27 | 0.338010E+09 | 0.194139E+09 |
December | 0.300488E+09 | 0.216951E+09 | 83537300.00 | 0.285975E+09 | 0.271354E+09 |
Annual Sum or Average | 0.379181E+10 | 0.218427E+10 | 0.160754E+10 | 0.358845E+10 | 0.199346E+10 |
Minimum of Months | 0.247064E+09 | 72023907.49 | 83537300.00 | 0.195914E+09 | 72835863.66 |
Maximum of Months | 0.379464E+09 | 0.262428E+09 | 0.175040E+09 | 0.395585E+09 | 0.316290E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.316004E+09 | 0.225666E+09 | 90338001.12 | 0.291054E+09 | 0.316290E+09 |
February | 0.363612E+09 | 0.261526E+09 | 0.102086E+09 | 0.357060E+09 | 0.213323E+09 |
March | 0.359988E+09 | 0.202219E+09 | 0.157769E+09 | 0.330488E+09 | 0.208830E+09 |
April | 0.279938E+09 | 0.133906E+09 | 0.146032E+09 | 0.235233E+09 | 0.149418E+09 |
May | 0.256951E+09 | 85313868.24 | 0.171637E+09 | 0.195914E+09 | 0.124031E+09 |
June | 0.247064E+09 | 72023907.49 | 0.175040E+09 | 0.203985E+09 | 87432962.02 |
July | 0.275231E+09 | 0.101633E+09 | 0.173598E+09 | 0.257623E+09 | 72835863.66 |
August | 0.327145E+09 | 0.164932E+09 | 0.162213E+09 | 0.328876E+09 | 82241159.16 |
September | 0.351293E+09 | 0.215301E+09 | 0.135992E+09 | 0.368645E+09 | 0.111772E+09 |
October | 0.379464E+09 | 0.262428E+09 | 0.117035E+09 | 0.395585E+09 | 0.161799E+09 |
November | 0.334629E+09 | 0.242372E+09 | 92257076.27 | 0.338010E+09 | 0.194139E+09 |
December | 0.300488E+09 | 0.216951E+09 | 83537300.00 | 0.285975E+09 | 0.271354E+09 |
Annual Sum or Average | 0.379181E+10 | 0.218427E+10 | 0.160754E+10 | 0.358845E+10 | 0.199346E+10 |
Minimum of Months | 0.247064E+09 | 72023907.49 | 83537300.00 | 0.195914E+09 | 72835863.66 |
Maximum of Months | 0.379464E+09 | 0.262428E+09 | 0.175040E+09 | 0.395585E+09 | 0.316290E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_DOOR
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.378374E+09 | 0.270206E+09 | 0.108168E+09 | 0.349156E+09 | 0.375184E+09 |
February | 0.435378E+09 | 0.313143E+09 | 0.122235E+09 | 0.428064E+09 | 0.253188E+09 |
March | 0.431038E+09 | 0.242130E+09 | 0.188908E+09 | 0.396249E+09 | 0.247892E+09 |
April | 0.335189E+09 | 0.160335E+09 | 0.174854E+09 | 0.281951E+09 | 0.177495E+09 |
May | 0.307665E+09 | 0.102152E+09 | 0.205513E+09 | 0.234858E+09 | 0.147322E+09 |
June | 0.295827E+09 | 86239152.39 | 0.209588E+09 | 0.244221E+09 | 0.103938E+09 |
July | 0.329553E+09 | 0.121693E+09 | 0.207861E+09 | 0.308141E+09 | 86721208.85 |
August | 0.391714E+09 | 0.197485E+09 | 0.194229E+09 | 0.393477E+09 | 97883758.01 |
September | 0.420627E+09 | 0.257795E+09 | 0.162832E+09 | 0.441308E+09 | 0.132918E+09 |
October | 0.454358E+09 | 0.314223E+09 | 0.140134E+09 | 0.473816E+09 | 0.192336E+09 |
November | 0.400674E+09 | 0.290209E+09 | 0.110466E+09 | 0.405074E+09 | 0.230571E+09 |
December | 0.359795E+09 | 0.259770E+09 | 0.100025E+09 | 0.342995E+09 | 0.322091E+09 |
Annual Sum or Average | 0.454019E+10 | 0.261538E+10 | 0.192481E+10 | 0.429931E+10 | 0.236754E+10 |
Minimum of Months | 0.295827E+09 | 86239152.39 | 0.100025E+09 | 0.234858E+09 | 86721208.85 |
Maximum of Months | 0.454358E+09 | 0.314223E+09 | 0.209588E+09 | 0.473816E+09 | 0.375184E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.316004E+09 | 0.225666E+09 | 90338001.12 | 0.293307E+09 | 0.309696E+09 |
February | 0.363612E+09 | 0.261526E+09 | 0.102086E+09 | 0.359805E+09 | 0.208127E+09 |
March | 0.359988E+09 | 0.202219E+09 | 0.157769E+09 | 0.332840E+09 | 0.203558E+09 |
April | 0.279938E+09 | 0.133906E+09 | 0.146032E+09 | 0.237934E+09 | 0.144010E+09 |
May | 0.256951E+09 | 85313868.24 | 0.171637E+09 | 0.198550E+09 | 0.119280E+09 |
June | 0.247064E+09 | 72023907.49 | 0.175040E+09 | 0.205108E+09 | 84650436.14 |
July | 0.275231E+09 | 0.101633E+09 | 0.173598E+09 | 0.257719E+09 | 70547097.73 |
August | 0.327145E+09 | 0.164932E+09 | 0.162213E+09 | 0.329255E+09 | 79613983.92 |
September | 0.351293E+09 | 0.215301E+09 | 0.135992E+09 | 0.369968E+09 | 0.108532E+09 |
October | 0.379464E+09 | 0.262428E+09 | 0.117035E+09 | 0.398401E+09 | 0.156787E+09 |
November | 0.334629E+09 | 0.242372E+09 | 92257076.27 | 0.340714E+09 | 0.188673E+09 |
December | 0.300488E+09 | 0.216951E+09 | 83537300.00 | 0.288325E+09 | 0.265582E+09 |
Annual Sum or Average | 0.379181E+10 | 0.218427E+10 | 0.160754E+10 | 0.361193E+10 | 0.193906E+10 |
Minimum of Months | 0.247064E+09 | 72023907.49 | 83537300.00 | 0.198550E+09 | 70547097.73 |
Maximum of Months | 0.379464E+09 | 0.262428E+09 | 0.175040E+09 | 0.398401E+09 | 0.309696E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.316004E+09 | 0.225666E+09 | 90338001.12 | 0.293307E+09 | 0.309696E+09 |
February | 0.363612E+09 | 0.261526E+09 | 0.102086E+09 | 0.359805E+09 | 0.208127E+09 |
March | 0.359988E+09 | 0.202219E+09 | 0.157769E+09 | 0.332840E+09 | 0.203558E+09 |
April | 0.279938E+09 | 0.133906E+09 | 0.146032E+09 | 0.237934E+09 | 0.144010E+09 |
May | 0.256951E+09 | 85313868.24 | 0.171637E+09 | 0.198550E+09 | 0.119280E+09 |
June | 0.247064E+09 | 72023907.49 | 0.175040E+09 | 0.205108E+09 | 84650436.14 |
July | 0.275231E+09 | 0.101633E+09 | 0.173598E+09 | 0.257719E+09 | 70547097.73 |
August | 0.327145E+09 | 0.164932E+09 | 0.162213E+09 | 0.329255E+09 | 79613983.92 |
September | 0.351293E+09 | 0.215301E+09 | 0.135992E+09 | 0.369968E+09 | 0.108532E+09 |
October | 0.379464E+09 | 0.262428E+09 | 0.117035E+09 | 0.398401E+09 | 0.156787E+09 |
November | 0.334629E+09 | 0.242372E+09 | 92257076.27 | 0.340714E+09 | 0.188673E+09 |
December | 0.300488E+09 | 0.216951E+09 | 83537300.00 | 0.288325E+09 | 0.265582E+09 |
Annual Sum or Average | 0.379181E+10 | 0.218427E+10 | 0.160754E+10 | 0.361193E+10 | 0.193906E+10 |
Minimum of Months | 0.247064E+09 | 72023907.49 | 83537300.00 | 0.198550E+09 | 70547097.73 |
Maximum of Months | 0.379464E+09 | 0.262428E+09 | 0.175040E+09 | 0.398401E+09 | 0.309696E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_3
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.316004E+09 | 0.225666E+09 | 90338001.12 | 0.293307E+09 | 0.309696E+09 |
February | 0.363612E+09 | 0.261526E+09 | 0.102086E+09 | 0.359805E+09 | 0.208127E+09 |
March | 0.359988E+09 | 0.202219E+09 | 0.157769E+09 | 0.332840E+09 | 0.203558E+09 |
April | 0.279938E+09 | 0.133906E+09 | 0.146032E+09 | 0.237934E+09 | 0.144010E+09 |
May | 0.256951E+09 | 85313868.24 | 0.171637E+09 | 0.198550E+09 | 0.119280E+09 |
June | 0.247064E+09 | 72023907.49 | 0.175040E+09 | 0.205108E+09 | 84650436.14 |
July | 0.275231E+09 | 0.101633E+09 | 0.173598E+09 | 0.257719E+09 | 70547097.73 |
August | 0.327145E+09 | 0.164932E+09 | 0.162213E+09 | 0.329255E+09 | 79613983.92 |
September | 0.351293E+09 | 0.215301E+09 | 0.135992E+09 | 0.369968E+09 | 0.108532E+09 |
October | 0.379464E+09 | 0.262428E+09 | 0.117035E+09 | 0.398401E+09 | 0.156787E+09 |
November | 0.334629E+09 | 0.242372E+09 | 92257076.27 | 0.340714E+09 | 0.188673E+09 |
December | 0.300488E+09 | 0.216951E+09 | 83537300.00 | 0.288325E+09 | 0.265582E+09 |
Annual Sum or Average | 0.379181E+10 | 0.218427E+10 | 0.160754E+10 | 0.361193E+10 | 0.193906E+10 |
Minimum of Months | 0.247064E+09 | 72023907.49 | 83537300.00 | 0.198550E+09 | 70547097.73 |
Maximum of Months | 0.379464E+09 | 0.262428E+09 | 0.175040E+09 | 0.398401E+09 | 0.309696E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_4
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.316004E+09 | 0.225666E+09 | 90338001.12 | 0.293307E+09 | 0.309696E+09 |
February | 0.363612E+09 | 0.261526E+09 | 0.102086E+09 | 0.359805E+09 | 0.208127E+09 |
March | 0.359988E+09 | 0.202219E+09 | 0.157769E+09 | 0.332840E+09 | 0.203558E+09 |
April | 0.279938E+09 | 0.133906E+09 | 0.146032E+09 | 0.237934E+09 | 0.144010E+09 |
May | 0.256951E+09 | 85313868.24 | 0.171637E+09 | 0.198550E+09 | 0.119280E+09 |
June | 0.247064E+09 | 72023907.49 | 0.175040E+09 | 0.205108E+09 | 84650436.14 |
July | 0.275231E+09 | 0.101633E+09 | 0.173598E+09 | 0.257719E+09 | 70547097.73 |
August | 0.327145E+09 | 0.164932E+09 | 0.162213E+09 | 0.329255E+09 | 79613983.92 |
September | 0.351293E+09 | 0.215301E+09 | 0.135992E+09 | 0.369968E+09 | 0.108532E+09 |
October | 0.379464E+09 | 0.262428E+09 | 0.117035E+09 | 0.398401E+09 | 0.156787E+09 |
November | 0.334629E+09 | 0.242372E+09 | 92257076.27 | 0.340714E+09 | 0.188673E+09 |
December | 0.300488E+09 | 0.216951E+09 | 83537300.00 | 0.288325E+09 | 0.265582E+09 |
Annual Sum or Average | 0.379181E+10 | 0.218427E+10 | 0.160754E+10 | 0.361193E+10 | 0.193906E+10 |
Minimum of Months | 0.247064E+09 | 72023907.49 | 83537300.00 | 0.198550E+09 | 70547097.73 |
Maximum of Months | 0.379464E+09 | 0.262428E+09 | 0.175040E+09 | 0.398401E+09 | 0.309696E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_DOOR_1
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.378374E+09 | 0.270206E+09 | 0.108168E+09 | 0.351830E+09 | 0.367416E+09 |
February | 0.435378E+09 | 0.313143E+09 | 0.122235E+09 | 0.431312E+09 | 0.247061E+09 |
March | 0.431038E+09 | 0.242130E+09 | 0.188908E+09 | 0.399053E+09 | 0.241682E+09 |
April | 0.335189E+09 | 0.160335E+09 | 0.174854E+09 | 0.285174E+09 | 0.171104E+09 |
May | 0.307665E+09 | 0.102152E+09 | 0.205513E+09 | 0.238017E+09 | 0.141722E+09 |
June | 0.295827E+09 | 86239152.39 | 0.209588E+09 | 0.245577E+09 | 0.100656E+09 |
July | 0.329553E+09 | 0.121693E+09 | 0.207861E+09 | 0.308289E+09 | 84018748.22 |
August | 0.391714E+09 | 0.197485E+09 | 0.194229E+09 | 0.393955E+09 | 94785489.91 |
September | 0.420627E+09 | 0.257795E+09 | 0.162832E+09 | 0.442884E+09 | 0.129097E+09 |
October | 0.454358E+09 | 0.314223E+09 | 0.140134E+09 | 0.477144E+09 | 0.186418E+09 |
November | 0.400674E+09 | 0.290209E+09 | 0.110466E+09 | 0.408279E+09 | 0.224125E+09 |
December | 0.359795E+09 | 0.259770E+09 | 0.100025E+09 | 0.345785E+09 | 0.315283E+09 |
Annual Sum or Average | 0.454019E+10 | 0.261538E+10 | 0.192481E+10 | 0.432730E+10 | 0.230337E+10 |
Minimum of Months | 0.295827E+09 | 86239152.39 | 0.100025E+09 | 0.238017E+09 | 84018748.22 |
Maximum of Months | 0.454358E+09 | 0.314223E+09 | 0.209588E+09 | 0.477144E+09 | 0.367416E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_DOOR_2
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.378374E+09 | 0.270206E+09 | 0.108168E+09 | 0.351830E+09 | 0.367416E+09 |
February | 0.435378E+09 | 0.313143E+09 | 0.122235E+09 | 0.431312E+09 | 0.247061E+09 |
March | 0.431038E+09 | 0.242130E+09 | 0.188908E+09 | 0.399053E+09 | 0.241682E+09 |
April | 0.335189E+09 | 0.160335E+09 | 0.174854E+09 | 0.285174E+09 | 0.171104E+09 |
May | 0.307665E+09 | 0.102152E+09 | 0.205513E+09 | 0.238017E+09 | 0.141722E+09 |
June | 0.295827E+09 | 86239152.39 | 0.209588E+09 | 0.245577E+09 | 0.100656E+09 |
July | 0.329553E+09 | 0.121693E+09 | 0.207861E+09 | 0.308289E+09 | 84018748.22 |
August | 0.391714E+09 | 0.197485E+09 | 0.194229E+09 | 0.393955E+09 | 94785489.91 |
September | 0.420627E+09 | 0.257795E+09 | 0.162832E+09 | 0.442884E+09 | 0.129097E+09 |
October | 0.454358E+09 | 0.314223E+09 | 0.140134E+09 | 0.477144E+09 | 0.186418E+09 |
November | 0.400674E+09 | 0.290209E+09 | 0.110466E+09 | 0.408279E+09 | 0.224125E+09 |
December | 0.359795E+09 | 0.259770E+09 | 0.100025E+09 | 0.345785E+09 | 0.315283E+09 |
Annual Sum or Average | 0.454019E+10 | 0.261538E+10 | 0.192481E+10 | 0.432730E+10 | 0.230337E+10 |
Minimum of Months | 0.295827E+09 | 86239152.39 | 0.100025E+09 | 0.238017E+09 | 84018748.22 |
Maximum of Months | 0.454358E+09 | 0.314223E+09 | 0.209588E+09 | 0.477144E+09 | 0.367416E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.316004E+09 | 0.225666E+09 | 90338001.12 | 0.292301E+09 | 0.311533E+09 |
February | 0.363612E+09 | 0.261526E+09 | 0.102086E+09 | 0.358731E+09 | 0.209189E+09 |
March | 0.359988E+09 | 0.202219E+09 | 0.157769E+09 | 0.331966E+09 | 0.204370E+09 |
April | 0.279938E+09 | 0.133906E+09 | 0.146032E+09 | 0.237126E+09 | 0.144725E+09 |
May | 0.256951E+09 | 85313868.24 | 0.171637E+09 | 0.197804E+09 | 0.119895E+09 |
June | 0.247064E+09 | 72023907.49 | 0.175040E+09 | 0.204916E+09 | 84684876.22 |
July | 0.275231E+09 | 0.101633E+09 | 0.173598E+09 | 0.258048E+09 | 70064850.43 |
August | 0.327145E+09 | 0.164932E+09 | 0.162213E+09 | 0.329272E+09 | 79251979.35 |
September | 0.351293E+09 | 0.215301E+09 | 0.135992E+09 | 0.369284E+09 | 0.108879E+09 |
October | 0.379464E+09 | 0.262428E+09 | 0.117035E+09 | 0.396989E+09 | 0.157918E+09 |
November | 0.334629E+09 | 0.242372E+09 | 92257076.27 | 0.339670E+09 | 0.189660E+09 |
December | 0.300488E+09 | 0.216951E+09 | 83537300.00 | 0.287365E+09 | 0.266893E+09 |
Annual Sum or Average | 0.379181E+10 | 0.218427E+10 | 0.160754E+10 | 0.360347E+10 | 0.194706E+10 |
Minimum of Months | 0.247064E+09 | 72023907.49 | 83537300.00 | 0.197804E+09 | 70064850.43 |
Maximum of Months | 0.379464E+09 | 0.262428E+09 | 0.175040E+09 | 0.396989E+09 | 0.311533E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.316004E+09 | 0.225666E+09 | 90338001.12 | 0.292301E+09 | 0.311533E+09 |
February | 0.363612E+09 | 0.261526E+09 | 0.102086E+09 | 0.358731E+09 | 0.209189E+09 |
March | 0.359988E+09 | 0.202219E+09 | 0.157769E+09 | 0.331966E+09 | 0.204370E+09 |
April | 0.279938E+09 | 0.133906E+09 | 0.146032E+09 | 0.237126E+09 | 0.144725E+09 |
May | 0.256951E+09 | 85313868.24 | 0.171637E+09 | 0.197804E+09 | 0.119895E+09 |
June | 0.247064E+09 | 72023907.49 | 0.175040E+09 | 0.204916E+09 | 84684876.22 |
July | 0.275231E+09 | 0.101633E+09 | 0.173598E+09 | 0.258048E+09 | 70064850.43 |
August | 0.327145E+09 | 0.164932E+09 | 0.162213E+09 | 0.329272E+09 | 79251979.35 |
September | 0.351293E+09 | 0.215301E+09 | 0.135992E+09 | 0.369284E+09 | 0.108879E+09 |
October | 0.379464E+09 | 0.262428E+09 | 0.117035E+09 | 0.396989E+09 | 0.157918E+09 |
November | 0.334629E+09 | 0.242372E+09 | 92257076.27 | 0.339670E+09 | 0.189660E+09 |
December | 0.300488E+09 | 0.216951E+09 | 83537300.00 | 0.287365E+09 | 0.266893E+09 |
Annual Sum or Average | 0.379181E+10 | 0.218427E+10 | 0.160754E+10 | 0.360347E+10 | 0.194706E+10 |
Minimum of Months | 0.247064E+09 | 72023907.49 | 83537300.00 | 0.197804E+09 | 70064850.43 |
Maximum of Months | 0.379464E+09 | 0.262428E+09 | 0.175040E+09 | 0.396989E+09 | 0.311533E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_DOOR
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.378374E+09 | 0.270206E+09 | 0.108168E+09 | 0.350671E+09 | 0.369518E+09 |
February | 0.435378E+09 | 0.313143E+09 | 0.122235E+09 | 0.430082E+09 | 0.248269E+09 |
March | 0.431038E+09 | 0.242130E+09 | 0.188908E+09 | 0.398053E+09 | 0.242591E+09 |
April | 0.335189E+09 | 0.160335E+09 | 0.174854E+09 | 0.284243E+09 | 0.171914E+09 |
May | 0.307665E+09 | 0.102152E+09 | 0.205513E+09 | 0.237155E+09 | 0.142417E+09 |
June | 0.295827E+09 | 86239152.39 | 0.209588E+09 | 0.245366E+09 | 0.100678E+09 |
July | 0.329553E+09 | 0.121693E+09 | 0.207861E+09 | 0.308687E+09 | 83437648.32 |
August | 0.391714E+09 | 0.197485E+09 | 0.194229E+09 | 0.393991E+09 | 94342531.66 |
September | 0.420627E+09 | 0.257795E+09 | 0.162832E+09 | 0.442103E+09 | 0.129481E+09 |
October | 0.454358E+09 | 0.314223E+09 | 0.140134E+09 | 0.475516E+09 | 0.187721E+09 |
November | 0.400674E+09 | 0.290209E+09 | 0.110466E+09 | 0.407081E+09 | 0.225244E+09 |
December | 0.359795E+09 | 0.259770E+09 | 0.100025E+09 | 0.344682E+09 | 0.316779E+09 |
Annual Sum or Average | 0.454019E+10 | 0.261538E+10 | 0.192481E+10 | 0.431763E+10 | 0.231239E+10 |
Minimum of Months | 0.295827E+09 | 86239152.39 | 0.100025E+09 | 0.237155E+09 | 83437648.32 |
Maximum of Months | 0.454358E+09 | 0.314223E+09 | 0.209588E+09 | 0.475516E+09 | 0.369518E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.316004E+09 | 0.225666E+09 | 90338001.12 | 0.292431E+09 | 0.310957E+09 |
February | 0.363612E+09 | 0.261526E+09 | 0.102086E+09 | 0.358978E+09 | 0.208561E+09 |
March | 0.359988E+09 | 0.202219E+09 | 0.157769E+09 | 0.332223E+09 | 0.203580E+09 |
April | 0.279938E+09 | 0.133906E+09 | 0.146032E+09 | 0.237526E+09 | 0.143808E+09 |
May | 0.256951E+09 | 85313868.24 | 0.171637E+09 | 0.198226E+09 | 0.119151E+09 |
June | 0.247064E+09 | 72023907.49 | 0.175040E+09 | 0.205238E+09 | 84240408.54 |
July | 0.275231E+09 | 0.101633E+09 | 0.173598E+09 | 0.258289E+09 | 69727400.97 |
August | 0.327145E+09 | 0.164932E+09 | 0.162213E+09 | 0.329483E+09 | 78900178.29 |
September | 0.351293E+09 | 0.215301E+09 | 0.135992E+09 | 0.369489E+09 | 0.108468E+09 |
October | 0.379464E+09 | 0.262428E+09 | 0.117035E+09 | 0.397246E+09 | 0.157368E+09 |
November | 0.334629E+09 | 0.242372E+09 | 92257076.27 | 0.339947E+09 | 0.188987E+09 |
December | 0.300488E+09 | 0.216951E+09 | 83537300.00 | 0.287557E+09 | 0.266214E+09 |
Annual Sum or Average | 0.379181E+10 | 0.218427E+10 | 0.160754E+10 | 0.360663E+10 | 0.193996E+10 |
Minimum of Months | 0.247064E+09 | 72023907.49 | 83537300.00 | 0.198226E+09 | 69727400.97 |
Maximum of Months | 0.379464E+09 | 0.262428E+09 | 0.175040E+09 | 0.397246E+09 | 0.310957E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.316004E+09 | 0.225666E+09 | 90338001.12 | 0.292431E+09 | 0.310957E+09 |
February | 0.363612E+09 | 0.261526E+09 | 0.102086E+09 | 0.358978E+09 | 0.208561E+09 |
March | 0.359988E+09 | 0.202219E+09 | 0.157769E+09 | 0.332223E+09 | 0.203580E+09 |
April | 0.279938E+09 | 0.133906E+09 | 0.146032E+09 | 0.237526E+09 | 0.143808E+09 |
May | 0.256951E+09 | 85313868.24 | 0.171637E+09 | 0.198226E+09 | 0.119151E+09 |
June | 0.247064E+09 | 72023907.49 | 0.175040E+09 | 0.205238E+09 | 84240408.54 |
July | 0.275231E+09 | 0.101633E+09 | 0.173598E+09 | 0.258289E+09 | 69727400.97 |
August | 0.327145E+09 | 0.164932E+09 | 0.162213E+09 | 0.329483E+09 | 78900178.29 |
September | 0.351293E+09 | 0.215301E+09 | 0.135992E+09 | 0.369489E+09 | 0.108468E+09 |
October | 0.379464E+09 | 0.262428E+09 | 0.117035E+09 | 0.397246E+09 | 0.157368E+09 |
November | 0.334629E+09 | 0.242372E+09 | 92257076.27 | 0.339947E+09 | 0.188987E+09 |
December | 0.300488E+09 | 0.216951E+09 | 83537300.00 | 0.287557E+09 | 0.266214E+09 |
Annual Sum or Average | 0.379181E+10 | 0.218427E+10 | 0.160754E+10 | 0.360663E+10 | 0.193996E+10 |
Minimum of Months | 0.247064E+09 | 72023907.49 | 83537300.00 | 0.198226E+09 | 69727400.97 |
Maximum of Months | 0.379464E+09 | 0.262428E+09 | 0.175040E+09 | 0.397246E+09 | 0.310957E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_DOOR
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.378374E+09 | 0.270206E+09 | 0.108168E+09 | 0.350830E+09 | 0.368831E+09 |
February | 0.435378E+09 | 0.313143E+09 | 0.122235E+09 | 0.430378E+09 | 0.247521E+09 |
March | 0.431038E+09 | 0.242130E+09 | 0.188908E+09 | 0.398366E+09 | 0.241651E+09 |
April | 0.335189E+09 | 0.160335E+09 | 0.174854E+09 | 0.284725E+09 | 0.170823E+09 |
May | 0.307665E+09 | 0.102152E+09 | 0.205513E+09 | 0.237663E+09 | 0.141532E+09 |
June | 0.295827E+09 | 86239152.39 | 0.209588E+09 | 0.245752E+09 | 0.100150E+09 |
July | 0.329553E+09 | 0.121693E+09 | 0.207861E+09 | 0.308977E+09 | 83037396.85 |
August | 0.391714E+09 | 0.197485E+09 | 0.194229E+09 | 0.394246E+09 | 93924078.50 |
September | 0.420627E+09 | 0.257795E+09 | 0.162832E+09 | 0.442350E+09 | 0.128993E+09 |
October | 0.454358E+09 | 0.314223E+09 | 0.140134E+09 | 0.475824E+09 | 0.187067E+09 |
November | 0.400674E+09 | 0.290209E+09 | 0.110466E+09 | 0.407414E+09 | 0.224443E+09 |
December | 0.359795E+09 | 0.259770E+09 | 0.100025E+09 | 0.344915E+09 | 0.315968E+09 |
Annual Sum or Average | 0.454019E+10 | 0.261538E+10 | 0.192481E+10 | 0.432144E+10 | 0.230394E+10 |
Minimum of Months | 0.295827E+09 | 86239152.39 | 0.100025E+09 | 0.237663E+09 | 83037396.85 |
Maximum of Months | 0.454358E+09 | 0.314223E+09 | 0.209588E+09 | 0.475824E+09 | 0.368831E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.316004E+09 | 0.225666E+09 | 90338001.12 | 0.292929E+09 | 0.308360E+09 |
February | 0.363612E+09 | 0.261526E+09 | 0.102086E+09 | 0.359850E+09 | 0.205876E+09 |
March | 0.359988E+09 | 0.202219E+09 | 0.157769E+09 | 0.333074E+09 | 0.200485E+09 |
April | 0.279938E+09 | 0.133906E+09 | 0.146032E+09 | 0.238866E+09 | 0.140318E+09 |
May | 0.256951E+09 | 85313868.24 | 0.171637E+09 | 0.199710E+09 | 0.116255E+09 |
June | 0.247064E+09 | 72023907.49 | 0.175040E+09 | 0.206310E+09 | 82581714.80 |
July | 0.275231E+09 | 0.101633E+09 | 0.173598E+09 | 0.258857E+09 | 68779739.57 |
August | 0.327145E+09 | 0.164932E+09 | 0.162213E+09 | 0.330008E+09 | 77847912.92 |
September | 0.351293E+09 | 0.215301E+09 | 0.135992E+09 | 0.370174E+09 | 0.106889E+09 |
October | 0.379464E+09 | 0.262428E+09 | 0.117035E+09 | 0.398316E+09 | 0.154871E+09 |
November | 0.334629E+09 | 0.242372E+09 | 92257076.27 | 0.340905E+09 | 0.186385E+09 |
December | 0.300488E+09 | 0.216951E+09 | 83537300.00 | 0.288229E+09 | 0.263378E+09 |
Annual Sum or Average | 0.379181E+10 | 0.218427E+10 | 0.160754E+10 | 0.361723E+10 | 0.191203E+10 |
Minimum of Months | 0.247064E+09 | 72023907.49 | 83537300.00 | 0.199710E+09 | 68779739.57 |
Maximum of Months | 0.379464E+09 | 0.262428E+09 | 0.175040E+09 | 0.398316E+09 | 0.308360E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.316004E+09 | 0.225666E+09 | 90338001.12 | 0.292929E+09 | 0.308360E+09 |
February | 0.363612E+09 | 0.261526E+09 | 0.102086E+09 | 0.359850E+09 | 0.205876E+09 |
March | 0.359988E+09 | 0.202219E+09 | 0.157769E+09 | 0.333074E+09 | 0.200485E+09 |
April | 0.279938E+09 | 0.133906E+09 | 0.146032E+09 | 0.238866E+09 | 0.140318E+09 |
May | 0.256951E+09 | 85313868.24 | 0.171637E+09 | 0.199710E+09 | 0.116255E+09 |
June | 0.247064E+09 | 72023907.49 | 0.175040E+09 | 0.206310E+09 | 82581714.80 |
July | 0.275231E+09 | 0.101633E+09 | 0.173598E+09 | 0.258857E+09 | 68779739.57 |
August | 0.327145E+09 | 0.164932E+09 | 0.162213E+09 | 0.330008E+09 | 77847912.92 |
September | 0.351293E+09 | 0.215301E+09 | 0.135992E+09 | 0.370174E+09 | 0.106889E+09 |
October | 0.379464E+09 | 0.262428E+09 | 0.117035E+09 | 0.398316E+09 | 0.154871E+09 |
November | 0.334629E+09 | 0.242372E+09 | 92257076.27 | 0.340905E+09 | 0.186385E+09 |
December | 0.300488E+09 | 0.216951E+09 | 83537300.00 | 0.288229E+09 | 0.263378E+09 |
Annual Sum or Average | 0.379181E+10 | 0.218427E+10 | 0.160754E+10 | 0.361723E+10 | 0.191203E+10 |
Minimum of Months | 0.247064E+09 | 72023907.49 | 83537300.00 | 0.199710E+09 | 68779739.57 |
Maximum of Months | 0.379464E+09 | 0.262428E+09 | 0.175040E+09 | 0.398316E+09 | 0.308360E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_DOOR
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.378374E+09 | 0.270206E+09 | 0.108168E+09 | 0.351435E+09 | 0.365734E+09 |
February | 0.435378E+09 | 0.313143E+09 | 0.122235E+09 | 0.431430E+09 | 0.244326E+09 |
March | 0.431038E+09 | 0.242130E+09 | 0.188908E+09 | 0.399398E+09 | 0.237966E+09 |
April | 0.335189E+09 | 0.160335E+09 | 0.174854E+09 | 0.286337E+09 | 0.166675E+09 |
May | 0.307665E+09 | 0.102152E+09 | 0.205513E+09 | 0.239450E+09 | 0.138099E+09 |
June | 0.295827E+09 | 86239152.39 | 0.209588E+09 | 0.247037E+09 | 98182787.89 |
July | 0.329553E+09 | 0.121693E+09 | 0.207861E+09 | 0.309660E+09 | 81916757.63 |
August | 0.391714E+09 | 0.197485E+09 | 0.194229E+09 | 0.394877E+09 | 92678916.44 |
September | 0.420627E+09 | 0.257795E+09 | 0.162832E+09 | 0.443172E+09 | 0.127121E+09 |
October | 0.454358E+09 | 0.314223E+09 | 0.140134E+09 | 0.477104E+09 | 0.184103E+09 |
November | 0.400674E+09 | 0.290209E+09 | 0.110466E+09 | 0.408568E+09 | 0.221353E+09 |
December | 0.359795E+09 | 0.259770E+09 | 0.100025E+09 | 0.345729E+09 | 0.312592E+09 |
Annual Sum or Average | 0.454019E+10 | 0.261538E+10 | 0.192481E+10 | 0.433420E+10 | 0.227075E+10 |
Minimum of Months | 0.295827E+09 | 86239152.39 | 0.100025E+09 | 0.239450E+09 | 81916757.63 |
Maximum of Months | 0.454358E+09 | 0.314223E+09 | 0.209588E+09 | 0.477104E+09 | 0.365734E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.316004E+09 | 0.225666E+09 | 90338001.12 | 0.294951E+09 | 0.297128E+09 |
February | 0.363612E+09 | 0.261526E+09 | 0.102086E+09 | 0.362652E+09 | 0.195157E+09 |
March | 0.359988E+09 | 0.202219E+09 | 0.157769E+09 | 0.335936E+09 | 0.188298E+09 |
April | 0.279938E+09 | 0.133906E+09 | 0.146032E+09 | 0.242395E+09 | 0.128541E+09 |
May | 0.256951E+09 | 85313868.24 | 0.171637E+09 | 0.203603E+09 | 0.106560E+09 |
June | 0.247064E+09 | 72023907.49 | 0.175040E+09 | 0.209316E+09 | 76420105.67 |
July | 0.275231E+09 | 0.101633E+09 | 0.173598E+09 | 0.260142E+09 | 65144594.77 |
August | 0.327145E+09 | 0.164932E+09 | 0.162213E+09 | 0.331218E+09 | 73886473.05 |
September | 0.351293E+09 | 0.215301E+09 | 0.135992E+09 | 0.371792E+09 | 0.101374E+09 |
October | 0.379464E+09 | 0.262428E+09 | 0.117035E+09 | 0.400877E+09 | 0.146927E+09 |
November | 0.334629E+09 | 0.242372E+09 | 92257076.27 | 0.343622E+09 | 0.177237E+09 |
December | 0.300488E+09 | 0.216951E+09 | 83537300.00 | 0.290525E+09 | 0.252049E+09 |
Annual Sum or Average | 0.379181E+10 | 0.218427E+10 | 0.160754E+10 | 0.364703E+10 | 0.180872E+10 |
Minimum of Months | 0.247064E+09 | 72023907.49 | 83537300.00 | 0.203603E+09 | 65144594.77 |
Maximum of Months | 0.379464E+09 | 0.262428E+09 | 0.175040E+09 | 0.400877E+09 | 0.297128E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.316004E+09 | 0.225666E+09 | 90338001.12 | 0.294951E+09 | 0.297128E+09 |
February | 0.363612E+09 | 0.261526E+09 | 0.102086E+09 | 0.362652E+09 | 0.195157E+09 |
March | 0.359988E+09 | 0.202219E+09 | 0.157769E+09 | 0.335936E+09 | 0.188298E+09 |
April | 0.279938E+09 | 0.133906E+09 | 0.146032E+09 | 0.242395E+09 | 0.128541E+09 |
May | 0.256951E+09 | 85313868.24 | 0.171637E+09 | 0.203603E+09 | 0.106560E+09 |
June | 0.247064E+09 | 72023907.49 | 0.175040E+09 | 0.209316E+09 | 76420105.67 |
July | 0.275231E+09 | 0.101633E+09 | 0.173598E+09 | 0.260142E+09 | 65144594.77 |
August | 0.327145E+09 | 0.164932E+09 | 0.162213E+09 | 0.331218E+09 | 73886473.05 |
September | 0.351293E+09 | 0.215301E+09 | 0.135992E+09 | 0.371792E+09 | 0.101374E+09 |
October | 0.379464E+09 | 0.262428E+09 | 0.117035E+09 | 0.400877E+09 | 0.146927E+09 |
November | 0.334629E+09 | 0.242372E+09 | 92257076.27 | 0.343622E+09 | 0.177237E+09 |
December | 0.300488E+09 | 0.216951E+09 | 83537300.00 | 0.290525E+09 | 0.252049E+09 |
Annual Sum or Average | 0.379181E+10 | 0.218427E+10 | 0.160754E+10 | 0.364703E+10 | 0.180872E+10 |
Minimum of Months | 0.247064E+09 | 72023907.49 | 83537300.00 | 0.203603E+09 | 65144594.77 |
Maximum of Months | 0.379464E+09 | 0.262428E+09 | 0.175040E+09 | 0.400877E+09 | 0.297128E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_DOOR
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.378374E+09 | 0.270206E+09 | 0.108168E+09 | 0.353891E+09 | 0.352324E+09 |
February | 0.435378E+09 | 0.313143E+09 | 0.122235E+09 | 0.434821E+09 | 0.231584E+09 |
March | 0.431038E+09 | 0.242130E+09 | 0.188908E+09 | 0.402882E+09 | 0.223481E+09 |
April | 0.335189E+09 | 0.160335E+09 | 0.174854E+09 | 0.290603E+09 | 0.152693E+09 |
May | 0.307665E+09 | 0.102152E+09 | 0.205513E+09 | 0.244137E+09 | 0.126610E+09 |
June | 0.295827E+09 | 86239152.39 | 0.209588E+09 | 0.250642E+09 | 90884916.82 |
July | 0.329553E+09 | 0.121693E+09 | 0.207861E+09 | 0.311200E+09 | 77612077.94 |
August | 0.391714E+09 | 0.197485E+09 | 0.194229E+09 | 0.396331E+09 | 87990191.93 |
September | 0.420627E+09 | 0.257795E+09 | 0.162832E+09 | 0.445118E+09 | 0.120595E+09 |
October | 0.454358E+09 | 0.314223E+09 | 0.140134E+09 | 0.480179E+09 | 0.174694E+09 |
November | 0.400674E+09 | 0.290209E+09 | 0.110466E+09 | 0.411849E+09 | 0.210506E+09 |
December | 0.359795E+09 | 0.259770E+09 | 0.100025E+09 | 0.348514E+09 | 0.299114E+09 |
Annual Sum or Average | 0.454019E+10 | 0.261538E+10 | 0.192481E+10 | 0.437017E+10 | 0.214809E+10 |
Minimum of Months | 0.295827E+09 | 86239152.39 | 0.100025E+09 | 0.244137E+09 | 77612077.94 |
Maximum of Months | 0.454358E+09 | 0.314223E+09 | 0.209588E+09 | 0.480179E+09 | 0.352324E+09 |
Report: WindowZoneSummaryMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 700.62 | 755.35 | 756.02 | 539.89 | 216.13 | 0.00 | 0.00 |
February | 951.18 | 561.28 | 963.12 | 692.72 | 270.40 | 0.00 | 0.00 |
March | 796.01 | 492.86 | 861.25 | 483.79 | 377.45 | 0.00 | 0.00 |
April | 587.35 | 359.41 | 692.06 | 331.04 | 361.02 | 0.00 | 0.00 |
May | 473.97 | 288.65 | 614.74 | 204.11 | 410.63 | 0.00 | 0.00 |
June | 509.38 | 205.20 | 610.79 | 178.06 | 432.73 | 0.00 | 0.00 |
July | 620.37 | 162.24 | 658.47 | 243.15 | 415.32 | 0.00 | 0.00 |
August | 790.34 | 184.66 | 782.67 | 394.59 | 388.08 | 0.00 | 0.00 |
September | 916.17 | 264.03 | 868.46 | 532.26 | 336.20 | 0.00 | 0.00 |
October | 951.23 | 378.39 | 907.84 | 627.84 | 280.00 | 0.00 | 0.00 |
November | 839.73 | 476.28 | 827.26 | 599.19 | 228.08 | 0.00 | 0.00 |
December | 688.09 | 647.26 | 718.90 | 519.04 | 199.86 | 0.00 | 0.00 |
Annual Sum or Average | 733.84 | 397.41 | 770.47 | 443.83 | 326.64 | 0.00 | 0.00 |
Minimum of Months | 473.97 | 162.24 | 610.79 | 178.06 | 199.86 | 0.00 | 0.00 |
Maximum of Months | 951.23 | 755.35 | 963.12 | 692.72 | 432.73 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 346.95 | 390.78 | 378.01 | 269.95 | 108.06 | 0.00 | 0.00 |
February | 470.41 | 293.88 | 481.56 | 346.36 | 135.20 | 0.00 | 0.00 |
March | 393.31 | 260.58 | 430.62 | 241.90 | 188.73 | 0.00 | 0.00 |
April | 287.71 | 194.89 | 346.03 | 165.52 | 180.51 | 0.00 | 0.00 |
May | 232.15 | 154.29 | 307.37 | 102.05 | 205.32 | 0.00 | 0.00 |
June | 252.09 | 106.14 | 305.39 | 89.03 | 216.37 | 0.00 | 0.00 |
July | 309.39 | 82.23 | 329.24 | 121.58 | 207.66 | 0.00 | 0.00 |
August | 394.02 | 93.89 | 391.34 | 197.29 | 194.04 | 0.00 | 0.00 |
September | 455.36 | 137.09 | 434.23 | 266.13 | 168.10 | 0.00 | 0.00 |
October | 470.80 | 199.58 | 453.92 | 313.92 | 140.00 | 0.00 | 0.00 |
November | 414.52 | 251.30 | 413.63 | 299.59 | 114.04 | 0.00 | 0.00 |
December | 340.43 | 335.94 | 359.45 | 259.52 | 99.93 | 0.00 | 0.00 |
Annual Sum or Average | 363.18 | 208.08 | 385.23 | 221.91 | 163.32 | 0.00 | 0.00 |
Minimum of Months | 232.15 | 82.23 | 305.39 | 89.03 | 99.93 | 0.00 | 0.00 |
Maximum of Months | 470.80 | 390.78 | 481.56 | 346.36 | 216.37 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 346.74 | 381.92 | 377.23 | 269.39 | 107.84 | 0.00 | 0.00 |
February | 470.47 | 286.55 | 480.57 | 345.65 | 134.92 | 0.00 | 0.00 |
March | 393.31 | 253.73 | 429.74 | 241.40 | 188.34 | 0.00 | 0.00 |
April | 288.08 | 189.72 | 345.32 | 165.18 | 180.14 | 0.00 | 0.00 |
May | 232.05 | 152.05 | 306.74 | 101.84 | 204.89 | 0.00 | 0.00 |
June | 250.82 | 109.09 | 304.77 | 88.85 | 215.92 | 0.00 | 0.00 |
July | 307.12 | 87.37 | 328.56 | 121.33 | 207.23 | 0.00 | 0.00 |
August | 392.14 | 98.80 | 390.53 | 196.89 | 193.64 | 0.00 | 0.00 |
September | 453.88 | 139.66 | 433.34 | 265.59 | 167.75 | 0.00 | 0.00 |
October | 470.56 | 197.26 | 452.99 | 313.28 | 139.71 | 0.00 | 0.00 |
November | 415.01 | 244.95 | 412.78 | 298.98 | 113.80 | 0.00 | 0.00 |
December | 340.49 | 328.16 | 358.71 | 258.99 | 99.72 | 0.00 | 0.00 |
Annual Sum or Average | 362.63 | 205.49 | 384.44 | 221.46 | 162.98 | 0.00 | 0.00 |
Minimum of Months | 232.05 | 87.37 | 304.77 | 88.85 | 99.72 | 0.00 | 0.00 |
Maximum of Months | 470.56 | 381.92 | 480.57 | 345.65 | 215.92 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 347.19 | 378.66 | 377.23 | 269.39 | 107.84 | 0.00 | 0.00 |
February | 471.25 | 283.49 | 480.57 | 345.65 | 134.92 | 0.00 | 0.00 |
March | 393.97 | 250.84 | 429.74 | 241.40 | 188.34 | 0.00 | 0.00 |
April | 289.03 | 186.76 | 345.32 | 165.18 | 180.14 | 0.00 | 0.00 |
May | 232.78 | 150.00 | 306.74 | 101.84 | 204.89 | 0.00 | 0.00 |
June | 250.98 | 108.73 | 304.77 | 88.85 | 215.92 | 0.00 | 0.00 |
July | 307.04 | 87.59 | 328.56 | 121.33 | 207.23 | 0.00 | 0.00 |
August | 392.10 | 98.92 | 390.53 | 196.89 | 193.64 | 0.00 | 0.00 |
September | 454.08 | 139.03 | 433.34 | 265.59 | 167.75 | 0.00 | 0.00 |
October | 471.22 | 195.15 | 452.99 | 313.28 | 139.71 | 0.00 | 0.00 |
November | 415.95 | 241.72 | 412.78 | 298.98 | 113.80 | 0.00 | 0.00 |
December | 341.02 | 325.16 | 358.71 | 258.99 | 99.72 | 0.00 | 0.00 |
Annual Sum or Average | 363.13 | 203.56 | 384.44 | 221.46 | 162.98 | 0.00 | 0.00 |
Minimum of Months | 232.78 | 87.59 | 304.77 | 88.85 | 99.72 | 0.00 | 0.00 |
Maximum of Months | 471.25 | 378.66 | 480.57 | 345.65 | 215.92 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 347.69 | 376.26 | 377.23 | 269.39 | 107.84 | 0.00 | 0.00 |
February | 472.13 | 281.02 | 480.57 | 345.65 | 134.92 | 0.00 | 0.00 |
March | 394.72 | 248.49 | 429.74 | 241.40 | 188.34 | 0.00 | 0.00 |
April | 290.28 | 183.77 | 345.32 | 165.18 | 180.14 | 0.00 | 0.00 |
May | 233.98 | 147.62 | 306.74 | 101.84 | 204.89 | 0.00 | 0.00 |
June | 251.62 | 107.56 | 304.77 | 88.85 | 215.92 | 0.00 | 0.00 |
July | 307.42 | 86.77 | 328.56 | 121.33 | 207.23 | 0.00 | 0.00 |
August | 392.48 | 97.96 | 390.53 | 196.89 | 193.64 | 0.00 | 0.00 |
September | 454.71 | 137.52 | 433.34 | 265.59 | 167.75 | 0.00 | 0.00 |
October | 472.29 | 192.63 | 452.99 | 313.28 | 139.71 | 0.00 | 0.00 |
November | 417.09 | 238.75 | 412.78 | 298.98 | 113.80 | 0.00 | 0.00 |
December | 341.60 | 322.88 | 358.71 | 258.99 | 99.72 | 0.00 | 0.00 |
Annual Sum or Average | 363.91 | 201.50 | 384.44 | 221.46 | 162.98 | 0.00 | 0.00 |
Minimum of Months | 233.98 | 86.77 | 304.77 | 88.85 | 99.72 | 0.00 | 0.00 |
Maximum of Months | 472.29 | 376.26 | 480.57 | 345.65 | 215.92 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 700.75 | 736.86 | 754.47 | 538.78 | 215.68 | 0.00 | 0.00 |
February | 951.49 | 548.38 | 961.15 | 691.30 | 269.85 | 0.00 | 0.00 |
March | 795.05 | 484.47 | 859.48 | 482.80 | 376.68 | 0.00 | 0.00 |
April | 587.22 | 354.26 | 690.64 | 330.36 | 360.28 | 0.00 | 0.00 |
May | 474.25 | 283.96 | 613.48 | 203.69 | 409.79 | 0.00 | 0.00 |
June | 506.01 | 208.30 | 609.53 | 177.69 | 431.84 | 0.00 | 0.00 |
July | 615.09 | 168.10 | 657.12 | 242.65 | 414.47 | 0.00 | 0.00 |
August | 785.89 | 189.68 | 781.07 | 393.78 | 387.29 | 0.00 | 0.00 |
September | 912.67 | 267.10 | 866.68 | 531.17 | 335.51 | 0.00 | 0.00 |
October | 951.27 | 373.35 | 905.98 | 626.55 | 279.42 | 0.00 | 0.00 |
November | 840.82 | 464.10 | 825.57 | 597.96 | 227.61 | 0.00 | 0.00 |
December | 688.80 | 632.05 | 717.42 | 517.97 | 199.45 | 0.00 | 0.00 |
Annual Sum or Average | 732.57 | 392.03 | 768.89 | 442.92 | 325.97 | 0.00 | 0.00 |
Minimum of Months | 474.25 | 168.10 | 609.53 | 177.69 | 199.45 | 0.00 | 0.00 |
Maximum of Months | 951.49 | 736.86 | 961.15 | 691.30 | 431.84 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 349.19 | 370.59 | 377.23 | 269.39 | 107.84 | 0.00 | 0.00 |
February | 474.35 | 275.57 | 480.57 | 345.65 | 134.92 | 0.00 | 0.00 |
March | 396.50 | 243.18 | 429.74 | 241.40 | 188.34 | 0.00 | 0.00 |
April | 292.63 | 178.00 | 345.32 | 165.18 | 180.14 | 0.00 | 0.00 |
May | 236.25 | 142.70 | 306.74 | 101.84 | 204.89 | 0.00 | 0.00 |
June | 252.78 | 104.19 | 304.77 | 88.85 | 215.92 | 0.00 | 0.00 |
July | 307.94 | 83.47 | 328.56 | 121.33 | 207.23 | 0.00 | 0.00 |
August | 392.97 | 94.40 | 390.53 | 196.89 | 193.64 | 0.00 | 0.00 |
September | 455.51 | 133.97 | 433.34 | 265.59 | 167.75 | 0.00 | 0.00 |
October | 473.98 | 188.01 | 452.99 | 313.28 | 139.71 | 0.00 | 0.00 |
November | 419.14 | 233.24 | 412.78 | 298.98 | 113.80 | 0.00 | 0.00 |
December | 343.27 | 317.56 | 358.71 | 258.99 | 99.72 | 0.00 | 0.00 |
Annual Sum or Average | 365.44 | 196.81 | 384.44 | 221.46 | 162.98 | 0.00 | 0.00 |
Minimum of Months | 236.25 | 83.47 | 304.77 | 88.85 | 99.72 | 0.00 | 0.00 |
Maximum of Months | 474.35 | 370.59 | 480.57 | 345.65 | 215.92 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 349.35 | 369.90 | 377.23 | 269.39 | 107.84 | 0.00 | 0.00 |
February | 474.67 | 274.74 | 480.57 | 345.65 | 134.92 | 0.00 | 0.00 |
March | 396.81 | 242.24 | 429.74 | 241.40 | 188.34 | 0.00 | 0.00 |
April | 293.12 | 176.87 | 345.32 | 165.18 | 180.14 | 0.00 | 0.00 |
May | 236.75 | 141.81 | 306.74 | 101.84 | 204.89 | 0.00 | 0.00 |
June | 253.17 | 103.64 | 304.77 | 88.85 | 215.92 | 0.00 | 0.00 |
July | 308.23 | 83.07 | 328.56 | 121.33 | 207.23 | 0.00 | 0.00 |
August | 393.22 | 93.98 | 390.53 | 196.89 | 193.64 | 0.00 | 0.00 |
September | 455.76 | 133.46 | 433.34 | 265.59 | 167.75 | 0.00 | 0.00 |
October | 474.28 | 187.35 | 452.99 | 313.28 | 139.71 | 0.00 | 0.00 |
November | 419.49 | 232.41 | 412.78 | 298.98 | 113.80 | 0.00 | 0.00 |
December | 343.50 | 316.75 | 358.71 | 258.99 | 99.72 | 0.00 | 0.00 |
Annual Sum or Average | 365.76 | 196.09 | 384.44 | 221.46 | 162.98 | 0.00 | 0.00 |
Minimum of Months | 236.75 | 83.07 | 304.77 | 88.85 | 99.72 | 0.00 | 0.00 |
Maximum of Months | 474.67 | 369.90 | 480.57 | 345.65 | 215.92 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 349.95 | 366.81 | 377.23 | 269.39 | 107.84 | 0.00 | 0.00 |
February | 475.83 | 271.20 | 480.57 | 345.65 | 134.92 | 0.00 | 0.00 |
March | 397.83 | 238.55 | 429.74 | 241.40 | 188.34 | 0.00 | 0.00 |
April | 294.78 | 172.57 | 345.32 | 165.18 | 180.14 | 0.00 | 0.00 |
May | 238.53 | 138.37 | 306.74 | 101.84 | 204.89 | 0.00 | 0.00 |
June | 254.50 | 101.60 | 304.77 | 88.85 | 215.92 | 0.00 | 0.00 |
July | 308.91 | 81.94 | 328.56 | 121.33 | 207.23 | 0.00 | 0.00 |
August | 393.85 | 92.73 | 390.53 | 196.89 | 193.64 | 0.00 | 0.00 |
September | 456.60 | 131.52 | 433.34 | 265.59 | 167.75 | 0.00 | 0.00 |
October | 475.56 | 184.38 | 452.99 | 313.28 | 139.71 | 0.00 | 0.00 |
November | 420.67 | 229.21 | 412.78 | 298.98 | 113.80 | 0.00 | 0.00 |
December | 344.31 | 313.38 | 358.71 | 258.99 | 99.72 | 0.00 | 0.00 |
Annual Sum or Average | 366.84 | 193.26 | 384.44 | 221.46 | 162.98 | 0.00 | 0.00 |
Minimum of Months | 238.53 | 81.94 | 304.77 | 88.85 | 99.72 | 0.00 | 0.00 |
Maximum of Months | 475.83 | 366.81 | 480.57 | 345.65 | 215.92 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 352.37 | 353.41 | 377.23 | 269.39 | 107.84 | 0.00 | 0.00 |
February | 479.55 | 257.07 | 480.57 | 345.65 | 134.92 | 0.00 | 0.00 |
March | 401.27 | 224.04 | 429.74 | 241.40 | 188.34 | 0.00 | 0.00 |
April | 299.15 | 158.09 | 345.32 | 165.18 | 180.14 | 0.00 | 0.00 |
May | 243.18 | 126.84 | 306.74 | 101.84 | 204.89 | 0.00 | 0.00 |
June | 258.21 | 94.03 | 304.77 | 88.85 | 215.92 | 0.00 | 0.00 |
July | 310.44 | 77.62 | 328.56 | 121.33 | 207.23 | 0.00 | 0.00 |
August | 395.30 | 88.02 | 390.53 | 196.89 | 193.64 | 0.00 | 0.00 |
September | 458.60 | 124.75 | 433.34 | 265.59 | 167.75 | 0.00 | 0.00 |
October | 478.62 | 174.94 | 452.99 | 313.28 | 139.71 | 0.00 | 0.00 |
November | 424.03 | 217.97 | 412.78 | 298.98 | 113.80 | 0.00 | 0.00 |
December | 347.06 | 299.89 | 358.71 | 258.99 | 99.72 | 0.00 | 0.00 |
Annual Sum or Average | 369.87 | 182.82 | 384.44 | 221.46 | 162.98 | 0.00 | 0.00 |
Minimum of Months | 243.18 | 77.62 | 304.77 | 88.85 | 99.72 | 0.00 | 0.00 |
Maximum of Months | 479.55 | 353.41 | 480.57 | 345.65 | 215.92 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.187655E+10 | 0.202312E+10 | 0.202492E+10 | 0.144605E+10 | 0.578876E+09 | 0.00 | 0.00 |
February | 0.230109E+10 | 0.135784E+10 | 0.232999E+10 | 0.167583E+10 | 0.654159E+09 | 0.00 | 0.00 |
March | 0.213204E+10 | 0.132008E+10 | 0.230677E+10 | 0.129580E+10 | 0.101097E+10 | 0.00 | 0.00 |
April | 0.152240E+10 | 0.931585E+09 | 0.179381E+10 | 0.858059E+09 | 0.935756E+09 | 0.00 | 0.00 |
May | 0.126949E+10 | 0.773118E+09 | 0.164651E+10 | 0.546682E+09 | 0.109983E+10 | 0.00 | 0.00 |
June | 0.132032E+10 | 0.531879E+09 | 0.158316E+10 | 0.461522E+09 | 0.112164E+10 | 0.00 | 0.00 |
July | 0.166159E+10 | 0.434533E+09 | 0.176365E+10 | 0.651256E+09 | 0.111240E+10 | 0.00 | 0.00 |
August | 0.211684E+10 | 0.494595E+09 | 0.209631E+10 | 0.105687E+10 | 0.103944E+10 | 0.00 | 0.00 |
September | 0.237471E+10 | 0.684363E+09 | 0.225105E+10 | 0.137963E+10 | 0.871421E+09 | 0.00 | 0.00 |
October | 0.254778E+10 | 0.101349E+10 | 0.243156E+10 | 0.168161E+10 | 0.749950E+09 | 0.00 | 0.00 |
November | 0.217658E+10 | 0.123451E+10 | 0.214427E+10 | 0.155309E+10 | 0.591174E+09 | 0.00 | 0.00 |
December | 0.184297E+10 | 0.173363E+10 | 0.192550E+10 | 0.139020E+10 | 0.535298E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.231424E+11 | 0.125327E+11 | 0.242975E+11 | 0.139966E+11 | 0.103009E+11 | 0.00 | 0.00 |
Minimum of Months | 0.126949E+10 | 0.434533E+09 | 0.158316E+10 | 0.461522E+09 | 0.535298E+09 | 0.00 | 0.00 |
Maximum of Months | 0.254778E+10 | 0.202312E+10 | 0.243156E+10 | 0.168161E+10 | 0.112164E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.929264E+09 | 0.104667E+10 | 0.101246E+10 | 0.723023E+09 | 0.289438E+09 | 0.00 | 0.00 |
February | 0.113802E+10 | 0.710952E+09 | 0.116499E+10 | 0.837915E+09 | 0.327080E+09 | 0.00 | 0.00 |
March | 0.105343E+10 | 0.697943E+09 | 0.115338E+10 | 0.647898E+09 | 0.505485E+09 | 0.00 | 0.00 |
April | 0.745747E+09 | 0.505152E+09 | 0.896907E+09 | 0.429029E+09 | 0.467878E+09 | 0.00 | 0.00 |
May | 0.621794E+09 | 0.413257E+09 | 0.823257E+09 | 0.273341E+09 | 0.549916E+09 | 0.00 | 0.00 |
June | 0.653415E+09 | 0.275109E+09 | 0.791580E+09 | 0.230761E+09 | 0.560820E+09 | 0.00 | 0.00 |
July | 0.828660E+09 | 0.220236E+09 | 0.881826E+09 | 0.325628E+09 | 0.556198E+09 | 0.00 | 0.00 |
August | 0.105535E+10 | 0.251474E+09 | 0.104816E+10 | 0.528435E+09 | 0.519722E+09 | 0.00 | 0.00 |
September | 0.118029E+10 | 0.355339E+09 | 0.112552E+10 | 0.689814E+09 | 0.435711E+09 | 0.00 | 0.00 |
October | 0.126100E+10 | 0.534550E+09 | 0.121578E+10 | 0.840807E+09 | 0.374975E+09 | 0.00 | 0.00 |
November | 0.107444E+10 | 0.651382E+09 | 0.107213E+10 | 0.776547E+09 | 0.295587E+09 | 0.00 | 0.00 |
December | 0.911803E+09 | 0.899788E+09 | 0.962748E+09 | 0.695099E+09 | 0.267649E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.114532E+11 | 0.656185E+10 | 0.121488E+11 | 0.699830E+10 | 0.515046E+10 | 0.00 | 0.00 |
Minimum of Months | 0.621794E+09 | 0.220236E+09 | 0.791580E+09 | 0.230761E+09 | 0.267649E+09 | 0.00 | 0.00 |
Maximum of Months | 0.126100E+10 | 0.104667E+10 | 0.121578E+10 | 0.840807E+09 | 0.560820E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.928695E+09 | 0.102292E+10 | 0.101038E+10 | 0.721538E+09 | 0.288844E+09 | 0.00 | 0.00 |
February | 0.113816E+10 | 0.693226E+09 | 0.116260E+10 | 0.836194E+09 | 0.326408E+09 | 0.00 | 0.00 |
March | 0.105344E+10 | 0.679594E+09 | 0.115101E+10 | 0.646568E+09 | 0.504447E+09 | 0.00 | 0.00 |
April | 0.746693E+09 | 0.491751E+09 | 0.895066E+09 | 0.428148E+09 | 0.466917E+09 | 0.00 | 0.00 |
May | 0.621512E+09 | 0.407239E+09 | 0.821566E+09 | 0.272780E+09 | 0.548787E+09 | 0.00 | 0.00 |
June | 0.650119E+09 | 0.282764E+09 | 0.789955E+09 | 0.230287E+09 | 0.559668E+09 | 0.00 | 0.00 |
July | 0.822577E+09 | 0.234022E+09 | 0.880015E+09 | 0.324959E+09 | 0.555056E+09 | 0.00 | 0.00 |
August | 0.105031E+10 | 0.264635E+09 | 0.104600E+10 | 0.527350E+09 | 0.518655E+09 | 0.00 | 0.00 |
September | 0.117645E+10 | 0.361997E+09 | 0.112321E+10 | 0.688398E+09 | 0.434816E+09 | 0.00 | 0.00 |
October | 0.126036E+10 | 0.528352E+09 | 0.121329E+10 | 0.839080E+09 | 0.374205E+09 | 0.00 | 0.00 |
November | 0.107572E+10 | 0.634916E+09 | 0.106993E+10 | 0.774952E+09 | 0.294980E+09 | 0.00 | 0.00 |
December | 0.911962E+09 | 0.878933E+09 | 0.960771E+09 | 0.693672E+09 | 0.267100E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.114360E+11 | 0.648035E+10 | 0.121238E+11 | 0.698393E+10 | 0.513988E+10 | 0.00 | 0.00 |
Minimum of Months | 0.621512E+09 | 0.234022E+09 | 0.789955E+09 | 0.230287E+09 | 0.267100E+09 | 0.00 | 0.00 |
Maximum of Months | 0.126036E+10 | 0.102292E+10 | 0.121329E+10 | 0.839080E+09 | 0.559668E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.929922E+09 | 0.101419E+10 | 0.101038E+10 | 0.721538E+09 | 0.288844E+09 | 0.00 | 0.00 |
February | 0.114005E+10 | 0.685808E+09 | 0.116260E+10 | 0.836194E+09 | 0.326408E+09 | 0.00 | 0.00 |
March | 0.105521E+10 | 0.671851E+09 | 0.115101E+10 | 0.646568E+09 | 0.504447E+09 | 0.00 | 0.00 |
April | 0.749160E+09 | 0.484074E+09 | 0.895066E+09 | 0.428148E+09 | 0.466917E+09 | 0.00 | 0.00 |
May | 0.623489E+09 | 0.401752E+09 | 0.821566E+09 | 0.272780E+09 | 0.548787E+09 | 0.00 | 0.00 |
June | 0.650542E+09 | 0.281837E+09 | 0.789955E+09 | 0.230287E+09 | 0.559668E+09 | 0.00 | 0.00 |
July | 0.822376E+09 | 0.234614E+09 | 0.880015E+09 | 0.324959E+09 | 0.555056E+09 | 0.00 | 0.00 |
August | 0.105020E+10 | 0.264960E+09 | 0.104600E+10 | 0.527350E+09 | 0.518655E+09 | 0.00 | 0.00 |
September | 0.117699E+10 | 0.360378E+09 | 0.112321E+10 | 0.688398E+09 | 0.434816E+09 | 0.00 | 0.00 |
October | 0.126212E+10 | 0.522701E+09 | 0.121329E+10 | 0.839080E+09 | 0.374205E+09 | 0.00 | 0.00 |
November | 0.107814E+10 | 0.626548E+09 | 0.106993E+10 | 0.774952E+09 | 0.294980E+09 | 0.00 | 0.00 |
December | 0.913387E+09 | 0.870911E+09 | 0.960771E+09 | 0.693672E+09 | 0.267100E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.114516E+11 | 0.641962E+10 | 0.121238E+11 | 0.698393E+10 | 0.513988E+10 | 0.00 | 0.00 |
Minimum of Months | 0.623489E+09 | 0.234614E+09 | 0.789955E+09 | 0.230287E+09 | 0.267100E+09 | 0.00 | 0.00 |
Maximum of Months | 0.126212E+10 | 0.101419E+10 | 0.121329E+10 | 0.839080E+09 | 0.559668E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.931263E+09 | 0.100776E+10 | 0.101038E+10 | 0.721538E+09 | 0.288844E+09 | 0.00 | 0.00 |
February | 0.114218E+10 | 0.679833E+09 | 0.116260E+10 | 0.836194E+09 | 0.326408E+09 | 0.00 | 0.00 |
March | 0.105722E+10 | 0.665550E+09 | 0.115101E+10 | 0.646568E+09 | 0.504447E+09 | 0.00 | 0.00 |
April | 0.752416E+09 | 0.476331E+09 | 0.895066E+09 | 0.428148E+09 | 0.466917E+09 | 0.00 | 0.00 |
May | 0.626685E+09 | 0.395383E+09 | 0.821566E+09 | 0.272780E+09 | 0.548787E+09 | 0.00 | 0.00 |
June | 0.652191E+09 | 0.278804E+09 | 0.789955E+09 | 0.230287E+09 | 0.559668E+09 | 0.00 | 0.00 |
July | 0.823387E+09 | 0.232393E+09 | 0.880015E+09 | 0.324959E+09 | 0.555056E+09 | 0.00 | 0.00 |
August | 0.105123E+10 | 0.262366E+09 | 0.104600E+10 | 0.527350E+09 | 0.518655E+09 | 0.00 | 0.00 |
September | 0.117860E+10 | 0.356462E+09 | 0.112321E+10 | 0.688398E+09 | 0.434816E+09 | 0.00 | 0.00 |
October | 0.126499E+10 | 0.515933E+09 | 0.121329E+10 | 0.839080E+09 | 0.374205E+09 | 0.00 | 0.00 |
November | 0.108109E+10 | 0.618846E+09 | 0.106993E+10 | 0.774952E+09 | 0.294980E+09 | 0.00 | 0.00 |
December | 0.914945E+09 | 0.864798E+09 | 0.960771E+09 | 0.693672E+09 | 0.267100E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.114762E+11 | 0.635446E+10 | 0.121238E+11 | 0.698393E+10 | 0.513988E+10 | 0.00 | 0.00 |
Minimum of Months | 0.626685E+09 | 0.232393E+09 | 0.789955E+09 | 0.230287E+09 | 0.267100E+09 | 0.00 | 0.00 |
Maximum of Months | 0.126499E+10 | 0.100776E+10 | 0.121329E+10 | 0.839080E+09 | 0.559668E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.187688E+10 | 0.197361E+10 | 0.202076E+10 | 0.144308E+10 | 0.577688E+09 | 0.00 | 0.00 |
February | 0.230184E+10 | 0.132663E+10 | 0.232520E+10 | 0.167239E+10 | 0.652816E+09 | 0.00 | 0.00 |
March | 0.212946E+10 | 0.129759E+10 | 0.230203E+10 | 0.129314E+10 | 0.100889E+10 | 0.00 | 0.00 |
April | 0.152208E+10 | 0.918245E+09 | 0.179013E+10 | 0.856297E+09 | 0.933834E+09 | 0.00 | 0.00 |
May | 0.127023E+10 | 0.760560E+09 | 0.164313E+10 | 0.545560E+09 | 0.109757E+10 | 0.00 | 0.00 |
June | 0.131158E+10 | 0.539913E+09 | 0.157991E+10 | 0.460574E+09 | 0.111934E+10 | 0.00 | 0.00 |
July | 0.164745E+10 | 0.450226E+09 | 0.176003E+10 | 0.649918E+09 | 0.111011E+10 | 0.00 | 0.00 |
August | 0.210493E+10 | 0.508026E+09 | 0.209201E+10 | 0.105470E+10 | 0.103731E+10 | 0.00 | 0.00 |
September | 0.236564E+10 | 0.692319E+09 | 0.224643E+10 | 0.137680E+10 | 0.869632E+09 | 0.00 | 0.00 |
October | 0.254789E+10 | 0.999984E+09 | 0.242657E+10 | 0.167816E+10 | 0.748410E+09 | 0.00 | 0.00 |
November | 0.217941E+10 | 0.120294E+10 | 0.213986E+10 | 0.154990E+10 | 0.589960E+09 | 0.00 | 0.00 |
December | 0.184487E+10 | 0.169289E+10 | 0.192154E+10 | 0.138734E+10 | 0.534199E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.231023E+11 | 0.123629E+11 | 0.242476E+11 | 0.139679E+11 | 0.102798E+11 | 0.00 | 0.00 |
Minimum of Months | 0.127023E+10 | 0.450226E+09 | 0.157991E+10 | 0.460574E+09 | 0.534199E+09 | 0.00 | 0.00 |
Maximum of Months | 0.254789E+10 | 0.197361E+10 | 0.242657E+10 | 0.167816E+10 | 0.111934E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.935271E+09 | 0.992582E+09 | 0.101038E+10 | 0.721538E+09 | 0.288844E+09 | 0.00 | 0.00 |
February | 0.114754E+10 | 0.666648E+09 | 0.116260E+10 | 0.836194E+09 | 0.326408E+09 | 0.00 | 0.00 |
March | 0.106198E+10 | 0.651330E+09 | 0.115101E+10 | 0.646568E+09 | 0.504447E+09 | 0.00 | 0.00 |
April | 0.758495E+09 | 0.461363E+09 | 0.895066E+09 | 0.428148E+09 | 0.466917E+09 | 0.00 | 0.00 |
May | 0.632762E+09 | 0.382207E+09 | 0.821566E+09 | 0.272780E+09 | 0.548787E+09 | 0.00 | 0.00 |
June | 0.655199E+09 | 0.270048E+09 | 0.789955E+09 | 0.230287E+09 | 0.559668E+09 | 0.00 | 0.00 |
July | 0.824782E+09 | 0.223567E+09 | 0.880015E+09 | 0.324959E+09 | 0.555056E+09 | 0.00 | 0.00 |
August | 0.105254E+10 | 0.252846E+09 | 0.104600E+10 | 0.527350E+09 | 0.518655E+09 | 0.00 | 0.00 |
September | 0.118067E+10 | 0.347240E+09 | 0.112321E+10 | 0.688398E+09 | 0.434816E+09 | 0.00 | 0.00 |
October | 0.126949E+10 | 0.503558E+09 | 0.121329E+10 | 0.839080E+09 | 0.374205E+09 | 0.00 | 0.00 |
November | 0.108642E+10 | 0.604563E+09 | 0.106993E+10 | 0.774952E+09 | 0.294980E+09 | 0.00 | 0.00 |
December | 0.919411E+09 | 0.850565E+09 | 0.960771E+09 | 0.693672E+09 | 0.267100E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.115246E+11 | 0.620652E+10 | 0.121238E+11 | 0.698393E+10 | 0.513988E+10 | 0.00 | 0.00 |
Minimum of Months | 0.632762E+09 | 0.223567E+09 | 0.789955E+09 | 0.230287E+09 | 0.267100E+09 | 0.00 | 0.00 |
Maximum of Months | 0.126949E+10 | 0.992582E+09 | 0.121329E+10 | 0.839080E+09 | 0.559668E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.935691E+09 | 0.990744E+09 | 0.101038E+10 | 0.721538E+09 | 0.288844E+09 | 0.00 | 0.00 |
February | 0.114833E+10 | 0.664642E+09 | 0.116260E+10 | 0.836194E+09 | 0.326408E+09 | 0.00 | 0.00 |
March | 0.106281E+10 | 0.648811E+09 | 0.115101E+10 | 0.646568E+09 | 0.504447E+09 | 0.00 | 0.00 |
April | 0.759776E+09 | 0.458439E+09 | 0.895066E+09 | 0.428148E+09 | 0.466917E+09 | 0.00 | 0.00 |
May | 0.634114E+09 | 0.379833E+09 | 0.821566E+09 | 0.272780E+09 | 0.548787E+09 | 0.00 | 0.00 |
June | 0.656227E+09 | 0.268630E+09 | 0.789955E+09 | 0.230287E+09 | 0.559668E+09 | 0.00 | 0.00 |
July | 0.825555E+09 | 0.222492E+09 | 0.880015E+09 | 0.324959E+09 | 0.555056E+09 | 0.00 | 0.00 |
August | 0.105321E+10 | 0.251724E+09 | 0.104600E+10 | 0.527350E+09 | 0.518655E+09 | 0.00 | 0.00 |
September | 0.118133E+10 | 0.345929E+09 | 0.112321E+10 | 0.688398E+09 | 0.434816E+09 | 0.00 | 0.00 |
October | 0.127032E+10 | 0.501803E+09 | 0.121329E+10 | 0.839080E+09 | 0.374205E+09 | 0.00 | 0.00 |
November | 0.108731E+10 | 0.602416E+09 | 0.106993E+10 | 0.774952E+09 | 0.294980E+09 | 0.00 | 0.00 |
December | 0.920028E+09 | 0.848394E+09 | 0.960771E+09 | 0.693672E+09 | 0.267100E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.115347E+11 | 0.618386E+10 | 0.121238E+11 | 0.698393E+10 | 0.513988E+10 | 0.00 | 0.00 |
Minimum of Months | 0.634114E+09 | 0.222492E+09 | 0.789955E+09 | 0.230287E+09 | 0.267100E+09 | 0.00 | 0.00 |
Maximum of Months | 0.127032E+10 | 0.990744E+09 | 0.121329E+10 | 0.839080E+09 | 0.559668E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.937293E+09 | 0.982453E+09 | 0.101038E+10 | 0.721538E+09 | 0.288844E+09 | 0.00 | 0.00 |
February | 0.115113E+10 | 0.656077E+09 | 0.116260E+10 | 0.836194E+09 | 0.326408E+09 | 0.00 | 0.00 |
March | 0.106555E+10 | 0.638935E+09 | 0.115101E+10 | 0.646568E+09 | 0.504447E+09 | 0.00 | 0.00 |
April | 0.764068E+09 | 0.447309E+09 | 0.895066E+09 | 0.428148E+09 | 0.466917E+09 | 0.00 | 0.00 |
May | 0.638870E+09 | 0.370609E+09 | 0.821566E+09 | 0.272780E+09 | 0.548787E+09 | 0.00 | 0.00 |
June | 0.659657E+09 | 0.263346E+09 | 0.789955E+09 | 0.230287E+09 | 0.559668E+09 | 0.00 | 0.00 |
July | 0.827373E+09 | 0.219476E+09 | 0.880015E+09 | 0.324959E+09 | 0.555056E+09 | 0.00 | 0.00 |
August | 0.105489E+10 | 0.248375E+09 | 0.104600E+10 | 0.527350E+09 | 0.518655E+09 | 0.00 | 0.00 |
September | 0.118352E+10 | 0.340899E+09 | 0.112321E+10 | 0.688398E+09 | 0.434816E+09 | 0.00 | 0.00 |
October | 0.127374E+10 | 0.493845E+09 | 0.121329E+10 | 0.839080E+09 | 0.374205E+09 | 0.00 | 0.00 |
November | 0.109038E+10 | 0.594122E+09 | 0.106993E+10 | 0.774952E+09 | 0.294980E+09 | 0.00 | 0.00 |
December | 0.922187E+09 | 0.839348E+09 | 0.960771E+09 | 0.693672E+09 | 0.267100E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.115686E+11 | 0.609479E+10 | 0.121238E+11 | 0.698393E+10 | 0.513988E+10 | 0.00 | 0.00 |
Minimum of Months | 0.638870E+09 | 0.219476E+09 | 0.789955E+09 | 0.230287E+09 | 0.267100E+09 | 0.00 | 0.00 |
Maximum of Months | 0.127374E+10 | 0.982453E+09 | 0.121329E+10 | 0.839080E+09 | 0.559668E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.943792E+09 | 0.946579E+09 | 0.101038E+10 | 0.721538E+09 | 0.288844E+09 | 0.00 | 0.00 |
February | 0.116012E+10 | 0.621898E+09 | 0.116260E+10 | 0.836194E+09 | 0.326408E+09 | 0.00 | 0.00 |
March | 0.107475E+10 | 0.600074E+09 | 0.115101E+10 | 0.646568E+09 | 0.504447E+09 | 0.00 | 0.00 |
April | 0.775393E+09 | 0.409774E+09 | 0.895066E+09 | 0.428148E+09 | 0.466917E+09 | 0.00 | 0.00 |
May | 0.651342E+09 | 0.339730E+09 | 0.821566E+09 | 0.272780E+09 | 0.548787E+09 | 0.00 | 0.00 |
June | 0.669273E+09 | 0.243725E+09 | 0.789955E+09 | 0.230287E+09 | 0.559668E+09 | 0.00 | 0.00 |
July | 0.831485E+09 | 0.207901E+09 | 0.880015E+09 | 0.324959E+09 | 0.555056E+09 | 0.00 | 0.00 |
August | 0.105877E+10 | 0.235763E+09 | 0.104600E+10 | 0.527350E+09 | 0.518655E+09 | 0.00 | 0.00 |
September | 0.118870E+10 | 0.323342E+09 | 0.112321E+10 | 0.688398E+09 | 0.434816E+09 | 0.00 | 0.00 |
October | 0.128193E+10 | 0.468549E+09 | 0.121329E+10 | 0.839080E+09 | 0.374205E+09 | 0.00 | 0.00 |
November | 0.109909E+10 | 0.564977E+09 | 0.106993E+10 | 0.774952E+09 | 0.294980E+09 | 0.00 | 0.00 |
December | 0.929564E+09 | 0.803212E+09 | 0.960771E+09 | 0.693672E+09 | 0.267100E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.116642E+11 | 0.576552E+10 | 0.121238E+11 | 0.698393E+10 | 0.513988E+10 | 0.00 | 0.00 |
Minimum of Months | 0.651342E+09 | 0.207901E+09 | 0.789955E+09 | 0.230287E+09 | 0.267100E+09 | 0.00 | 0.00 |
Maximum of Months | 0.128193E+10 | 0.946579E+09 | 0.121329E+10 | 0.839080E+09 | 0.559668E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -8.8 | -10.8 | -16.1 | 5.70 | -23.3 | 32.48 | 106.19 | 0.00 |
February | -2.2 | -4.9 | -9.9 | 6.21 | -16.1 | 41.31 | 158.25 | 0.00 |
March | 0.30 | -2.8 | -8.4 | 5.38 | -12.8 | 78.62 | 145.02 | 0.00 |
April | 6.67 | 2.37 | -2.9 | 4.89 | -6.2 | 82.10 | 182.32 | 0.01 |
May | 10.10 | 5.18 | 0.22 | 5.28 | -1.1 | 102.67 | 205.47 | 0.01 |
June | 16.46 | 10.04 | 4.91 | 4.56 | 5.04 | 103.05 | 264.47 | 0.02 |
July | 20.57 | 12.44 | 6.56 | 4.24 | 8.00 | 89.47 | 301.47 | 0.00 |
August | 19.17 | 11.02 | 4.61 | 4.29 | 7.18 | 78.96 | 261.05 | 0.00 |
September | 14.69 | 9.07 | 4.37 | 5.43 | 3.41 | 63.03 | 204.21 | 0.00 |
October | 8.64 | 4.13 | -1.0 | 5.38 | -4.2 | 47.64 | 162.42 | 0.00 |
November | 2.84 | -0.8 | -6.9 | 5.91 | -11.0 | 33.00 | 125.52 | 0.00 |
December | -4.1 | -6.4 | -11.1 | 5.64 | -18.2 | 26.54 | 97.81 | 0.00 |
Annual Sum or Average | 7.07 | 2.40 | -2.9 | 5.23 | -5.7 | 65.04 | 184.63 | 0.00 |
Minimum of Months | -8.8 | -10.8 | -16.1 | 4.24 | -23.3 | 26.54 | 97.81 | 0.00 |
Maximum of Months | 20.57 | 12.44 | 6.56 | 6.21 | 8.00 | 103.05 | 301.47 | 0.02 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.60 | 14-JAN-12:00 | 5.15 | -1.1 | 8.20 | -2.3 | 105.00 | 464.50 |
February | 18.90 | 27-FEB-14:00 | 7.20 | -7.8 | 5.20 | 1.37 | 76.00 | 634.50 |
March | 15.00 | 14-MAR-13:20 | 6.65 | -2.4 | 9.30 | 1.23 | 201.67 | 711.67 |
April | 23.30 | 07-APR-13:00 | 9.64 | -4.4 | 9.30 | 4.92 | 314.50 | 110.00 |
May | 30.00 | 20-MAY-15:00 | 15.19 | 5.60 | 6.70 | 20.57 | 215.50 | 18.50 |
June | 32.20 | 29-JUN-12:00 | 14.36 | 0.60 | 9.30 | 17.03 | 187.00 | 729.00 |
July | 37.20 | 17-JUL-15:00 | 17.25 | 4.40 | 4.60 | 20.22 | 119.50 | 797.00 |
August | 35.60 | 05-AUG-15:00 | 17.61 | 6.70 | 5.20 | 22.47 | 136.50 | 625.50 |
September | 34.40 | 02-SEP-14:00 | 16.25 | 4.40 | 7.70 | 20.75 | 95.50 | 789.50 |
October | 25.00 | 18-OCT-13:00 | 11.37 | -1.1 | 7.70 | 7.35 | 48.00 | 913.00 |
November | 17.20 | 04-NOV-13:00 | 8.15 | -1.1 | 11.30 | 2.22 | 81.00 | 689.50 |
December | 13.90 | 10-DEC-01:00 | 5.47 | -5.0 | 13.90 | 5.74 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 10.60 | 5.15 | -7.8 | 4.60 | -2.3 | 0.00 | 0.00 | |
Maximum of Months | 37.20 | 17.61 | 6.70 | 13.90 | 22.47 | 314.50 | 913.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -33.9 | 10-JAN-21:00 | -34.0 | -37.8 | 3.10 | -54.3 | 0.00 | 0.00 |
February | -25.0 | 01-FEB-03:00 | -25.2 | -27.8 | 2.10 | -45.6 | 0.00 | 0.00 |
March | -23.3 | 04-MAR-23:00 | -23.8 | -28.9 | 3.60 | -44.5 | 0.00 | 0.00 |
April | -7.8 | 29-APR-03:00 | -8.6 | -10.6 | 4.10 | -25.6 | 0.00 | 0.00 |
May | -2.8 | 08-MAY-00:10 | -3.3 | -3.9 | 6.18 | -10.2 | 0.00 | 0.00 |
June | 0.60 | 15-JUN-03:00 | -0.4 | -1.7 | 2.60 | -15.7 | 0.00 | 0.00 |
July | 5.60 | 08-JUL-03:00 | 2.98 | 0.00 | 4.10 | -9.2 | 0.00 | 0.00 |
August | 6.70 | 17-AUG-00:00 | 4.32 | 1.70 | 2.60 | -7.1 | 0.00 | 0.00 |
September | 0.00 | 17-SEP-02:00 | -1.5 | -3.9 | 4.10 | -16.8 | 0.00 | 0.00 |
October | -6.1 | 10-OCT-05:19 | -6.6 | -7.8 | 3.77 | -20.6 | 0.00 | 0.00 |
November | -16.7 | 26-NOV-07:00 | -17.3 | -20.6 | 4.60 | -33.8 | 19.50 | 94.00 |
December | -28.3 | 29-DEC-08:00 | -28.5 | -32.2 | 2.10 | -48.7 | 69.50 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -33.9 | -34.0 | -37.8 | 2.10 | -54.3 | 0.00 | 0.00 | |
Maximum of Months | 6.70 | 4.32 | 1.70 | 6.18 | -7.1 | 69.50 | 94.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 5.17 | 13-JAN-14:00 | 10.00 | 0.00 | 8.80 | -3.0 | 40.00 | 694.00 |
February | 7.20 | 27-FEB-14:00 | 18.90 | -7.8 | 5.20 | 1.37 | 76.00 | 634.50 |
March | 6.92 | 14-MAR-13:00 | 15.00 | -1.7 | 10.30 | 1.80 | 241.00 | 538.00 |
April | 11.00 | 06-APR-15:00 | 22.20 | 1.10 | 3.60 | 5.33 | 110.00 | 779.00 |
May | 15.19 | 20-MAY-15:00 | 30.00 | 5.60 | 6.70 | 20.57 | 215.50 | 18.50 |
June | 19.18 | 20-JUN-14:00 | 29.40 | 14.40 | 2.60 | 18.28 | 204.00 | 614.00 |
July | 19.19 | 19-JUL-11:00 | 29.40 | 14.40 | 8.80 | 19.52 | 306.50 | 563.50 |
August | 17.61 | 05-AUG-15:00 | 35.60 | 6.70 | 5.20 | 22.47 | 136.50 | 625.50 |
September | 20.11 | 07-SEP-15:20 | 25.17 | 17.93 | 4.10 | 15.88 | 127.67 | 652.00 |
October | 11.58 | 18-OCT-14:00 | 25.00 | -0.6 | 7.70 | 7.55 | 40.50 | 852.00 |
November | 8.87 | 17-NOV-16:00 | 17.20 | 1.10 | 11.30 | 4.10 | 0.00 | 0.00 |
December | 7.61 | 19-DEC-14:00 | 12.80 | 2.80 | 8.20 | 1.37 | 74.00 | 138.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 5.17 | 10.00 | -7.8 | 2.60 | -3.0 | 0.00 | 0.00 | |
Maximum of Months | 20.11 | 35.60 | 17.93 | 11.30 | 22.47 | 306.50 | 852.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 1.70 | 12-JAN-14:00 | 7.20 | 4.47 | 5.20 | -1.0 | 107.00 | 61.00 |
February | -0.6 | 11-FEB-08:00 | 4.40 | 2.15 | 10.80 | -5.7 | 69.50 | 50.50 |
March | -0.6 | 10-MAR-12:00 | 8.90 | 4.49 | 10.30 | -2.3 | 253.00 | 140.50 |
April | 6.10 | 17-APR-16:19 | 7.97 | 6.96 | 4.50 | 0.84 | 201.50 | 117.50 |
May | 12.20 | 02-MAY-12:00 | 18.90 | 14.60 | 12.90 | 14.84 | 108.50 | 934.50 |
June | 15.60 | 20-JUN-19:00 | 25.60 | 18.75 | 3.60 | 20.22 | 17.50 | 17.00 |
July | 16.70 | 18-JUL-21:00 | 19.40 | 17.51 | 4.10 | 16.49 | 0.00 | 0.00 |
August | 11.10 | 08-AUG-11:00 | 26.70 | 16.73 | 2.60 | 12.03 | 134.50 | 869.00 |
September | 18.30 | 07-SEP-14:00 | 24.40 | 20.09 | 4.10 | 15.57 | 111.00 | 720.00 |
October | 6.70 | 01-OCT-14:09 | 9.08 | 7.77 | 2.10 | 4.06 | 260.33 | 0.33 |
November | 3.30 | 16-NOV-19:00 | 10.60 | 6.87 | 9.80 | -1.7 | 0.00 | 0.00 |
December | 2.80 | 19-DEC-14:09 | 10.97 | 6.80 | 10.78 | -1.0 | 95.00 | 292.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -0.6 | 4.40 | 2.15 | 2.10 | -5.7 | 0.00 | 0.00 | |
Maximum of Months | 18.30 | 26.70 | 20.09 | 12.90 | 20.22 | 260.33 | 934.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 5.41 | 12.59 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 4.46 | 20.37 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 5.03 | 30.19 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 7.01 | 37.07 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 9.90 | 46.35 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 12.91 | 55.45 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 15.24 | 57.38 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 16.26 | 48.01 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 15.67 | 34.51 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 13.64 | 22.84 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 10.74 | 14.52 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 7.74 | 10.24 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 10.37 | 32.53 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 4.46 | 10.24 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 16.26 | 57.38 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK1
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.388959E+09 | -263101045.8 | 0.00 | 0.00 | 744.00 | 0.00 | -125857912.4 | 59.00 | 0.00 | 0.00 |
February | 0.355903E+09 | -243119076.8 | 0.00 | 0.00 | 672.00 | 0.00 | -112783839.9 | 58.99 | 0.00 | 0.00 |
March | 0.395122E+09 | -270544099.7 | 0.00 | 0.00 | 744.00 | 0.00 | -124578389.7 | 58.99 | 0.00 | 0.00 |
April | 0.367507E+09 | -249345153.9 | 0.00 | 0.00 | 720.00 | 0.00 | -118161674.5 | 58.99 | 0.00 | 0.00 |
May | 0.362800E+09 | -243590061.4 | 0.00 | 0.00 | 744.00 | 0.00 | -119209978.0 | 58.99 | 0.00 | 0.00 |
June | 0.333682E+09 | -223303609.0 | 0.00 | 0.00 | 720.00 | 0.00 | -110378856.3 | 58.99 | 0.00 | 0.00 |
July | 0.327576E+09 | -214926265.2 | 0.00 | 0.00 | 744.00 | 0.00 | -112649246.2 | 58.99 | 0.00 | 0.00 |
August | 0.326975E+09 | -214080444.3 | 0.00 | 0.00 | 744.00 | 0.00 | -112894840.9 | 58.99 | 0.00 | 0.00 |
September | 0.319249E+09 | -207990825.3 | 0.00 | 0.00 | 720.00 | 0.00 | -111257786.5 | 58.99 | 0.00 | 0.00 |
October | 0.340901E+09 | -222693419.7 | 0.00 | 0.00 | 744.00 | 0.00 | -118207191.9 | 58.99 | 0.00 | 0.00 |
November | 0.347343E+09 | -228638980.6 | 0.00 | 0.00 | 720.00 | 0.00 | -118703861.6 | 58.99 | 0.00 | 0.00 |
December | 0.376948E+09 | -251969403.8 | 0.00 | 0.00 | 744.00 | 0.00 | -124978493.4 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.424296E+10 | -.283330E+10 | 8760.00 | -.140966E+10 | 58.99 | |||||
Minimum of Months | 0.319249E+09 | -270544099.7 | 0.00 | 0.00 | 672.00 | 0.00 | -125857912.4 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.395122E+09 | -207990825.3 | 0.00 | 0.00 | 744.00 | 0.00 | -110378856.3 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK2
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.387111E+09 | -263100867.6 | 0.00 | 0.00 | 744.00 | 0.00 | -124009683.8 | 59.00 | 0.00 | 0.00 |
February | 0.353574E+09 | -243118351.6 | 0.00 | 0.00 | 672.00 | 0.00 | -110455336.3 | 58.99 | 0.00 | 0.00 |
March | 0.392383E+09 | -270549915.8 | 0.00 | 0.00 | 744.00 | 0.00 | -121832687.4 | 58.99 | 0.00 | 0.00 |
April | 0.363958E+09 | -249343576.2 | 0.00 | 0.00 | 720.00 | 0.00 | -114613995.4 | 58.99 | 0.00 | 0.00 |
May | 0.360268E+09 | -243587525.8 | 0.00 | 0.00 | 744.00 | 0.00 | -116680805.1 | 58.99 | 0.00 | 0.00 |
June | 0.332805E+09 | -223290787.2 | 0.00 | 0.00 | 720.00 | 0.00 | -109513764.8 | 58.99 | 0.00 | 0.00 |
July | 0.327307E+09 | -214918412.4 | 0.00 | 0.00 | 744.00 | 0.00 | -112388139.4 | 58.99 | 0.00 | 0.00 |
August | 0.326598E+09 | -214081146.9 | 0.00 | 0.00 | 744.00 | 0.00 | -112517141.6 | 58.99 | 0.00 | 0.00 |
September | 0.317959E+09 | -207991889.2 | 0.00 | 0.00 | 720.00 | 0.00 | -109966672.7 | 58.99 | 0.00 | 0.00 |
October | 0.338177E+09 | -222692891.0 | 0.00 | 0.00 | 744.00 | 0.00 | -115484032.5 | 58.99 | 0.00 | 0.00 |
November | 0.344325E+09 | -228636444.9 | 0.00 | 0.00 | 720.00 | 0.00 | -115688128.3 | 58.99 | 0.00 | 0.00 |
December | 0.374888E+09 | -251969342.6 | 0.00 | 0.00 | 744.00 | 0.00 | -122918401.4 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.421935E+10 | -.283328E+10 | 8760.00 | -.138607E+10 | 58.99 | |||||
Minimum of Months | 0.317959E+09 | -270549915.8 | 0.00 | 0.00 | 672.00 | 0.00 | -124009683.8 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.392383E+09 | -207991889.2 | 0.00 | 0.00 | 744.00 | 0.00 | -109513764.8 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK3
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.357318E+09 | -231349625.5 | 0.00 | 0.00 | 744.00 | 0.00 | -125968193.5 | 59.00 | 0.00 | 0.00 |
February | 0.326081E+09 | -213946669.6 | 0.00 | 0.00 | 672.00 | 0.00 | -112134696.3 | 59.00 | 0.00 | 0.00 |
March | 0.365243E+09 | -241644843.7 | 0.00 | 0.00 | 744.00 | 0.00 | -123598628.4 | 58.99 | 0.00 | 0.00 |
April | 0.335254E+09 | -219131154.4 | 0.00 | 0.00 | 720.00 | 0.00 | -116122854.5 | 58.99 | 0.00 | 0.00 |
May | 0.333301E+09 | -216078099.4 | 0.00 | 0.00 | 744.00 | 0.00 | -117222514.4 | 58.99 | 0.00 | 0.00 |
June | 0.307581E+09 | -199013509.2 | 0.00 | 0.00 | 720.00 | 0.00 | -108567813.7 | 58.99 | 0.00 | 0.00 |
July | 0.298341E+09 | -187736379.5 | 0.00 | 0.00 | 744.00 | 0.00 | -110604140.5 | 58.99 | 0.00 | 0.00 |
August | 0.302359E+09 | -191351836.7 | 0.00 | 0.00 | 744.00 | 0.00 | -111007195.1 | 58.99 | 0.00 | 0.00 |
September | 0.291898E+09 | -182660511.8 | 0.00 | 0.00 | 720.00 | 0.00 | -109237614.1 | 58.99 | 0.00 | 0.00 |
October | 0.312072E+09 | -195864071.5 | 0.00 | 0.00 | 744.00 | 0.00 | -116207599.9 | 58.99 | 0.00 | 0.00 |
November | 0.319255E+09 | -201875693.9 | 0.00 | 0.00 | 720.00 | 0.00 | -117379484.2 | 58.99 | 0.00 | 0.00 |
December | 0.344708E+09 | -219920599.6 | 0.00 | 0.00 | 744.00 | 0.00 | -124787721.7 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.389341E+10 | -.250057E+10 | 8760.00 | -.139284E+10 | 58.99 | |||||
Minimum of Months | 0.291898E+09 | -241644843.7 | 0.00 | 0.00 | 672.00 | 0.00 | -125968193.5 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.365243E+09 | -182660511.8 | 0.00 | 0.00 | 744.00 | 0.00 | -108567813.7 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK4
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.357790E+09 | -231348261.0 | 0.00 | 0.00 | 744.00 | 0.00 | -126441656.0 | 59.00 | 0.00 | 0.00 |
February | 0.326547E+09 | -213976678.0 | 0.00 | 0.00 | 672.00 | 0.00 | -112570532.2 | 58.99 | 0.00 | 0.00 |
March | 0.365720E+09 | -241629107.6 | 0.00 | 0.00 | 744.00 | 0.00 | -124091133.2 | 59.00 | 0.00 | 0.00 |
April | 0.335821E+09 | -219118079.4 | 0.00 | 0.00 | 720.00 | 0.00 | -116703366.1 | 59.00 | 0.00 | 0.00 |
May | 0.333697E+09 | -216063622.6 | 0.00 | 0.00 | 744.00 | 0.00 | -117633533.7 | 58.99 | 0.00 | 0.00 |
June | 0.307650E+09 | -199016983.2 | 0.00 | 0.00 | 720.00 | 0.00 | -108633223.0 | 58.99 | 0.00 | 0.00 |
July | 0.298290E+09 | -187745845.9 | 0.00 | 0.00 | 744.00 | 0.00 | -110544474.5 | 58.99 | 0.00 | 0.00 |
August | 0.302332E+09 | -191364282.3 | 0.00 | 0.00 | 744.00 | 0.00 | -110967588.7 | 58.99 | 0.00 | 0.00 |
September | 0.292013E+09 | -182665205.6 | 0.00 | 0.00 | 720.00 | 0.00 | -109347936.1 | 58.99 | 0.00 | 0.00 |
October | 0.312489E+09 | -195857328.4 | 0.00 | 0.00 | 744.00 | 0.00 | -116631428.7 | 58.99 | 0.00 | 0.00 |
November | 0.319838E+09 | -201854699.9 | 0.00 | 0.00 | 720.00 | 0.00 | -117983331.9 | 59.00 | 0.00 | 0.00 |
December | 0.345158E+09 | -219925928.6 | 0.00 | 0.00 | 744.00 | 0.00 | -125232395.6 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.389735E+10 | -.250057E+10 | 8760.00 | -.139678E+10 | 58.99 | |||||
Minimum of Months | 0.292013E+09 | -241629107.6 | 0.00 | 0.00 | 672.00 | 0.00 | -126441656.0 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.365720E+09 | -182665205.6 | 0.00 | 0.00 | 744.00 | 0.00 | -108633223.0 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK5
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.346703E+09 | -218677170.9 | 0.00 | 0.00 | 744.00 | 0.00 | -128026019.4 | 58.99 | 0.00 | 0.00 |
February | 0.316560E+09 | -202327344.3 | 0.00 | 0.00 | 672.00 | 0.00 | -114232871.0 | 58.99 | 0.00 | 0.00 |
March | 0.354328E+09 | -228639277.5 | 0.00 | 0.00 | 744.00 | 0.00 | -125688378.4 | 59.00 | 0.00 | 0.00 |
April | 0.326287E+09 | -207356531.7 | 0.00 | 0.00 | 720.00 | 0.00 | -118930168.8 | 58.99 | 0.00 | 0.00 |
May | 0.324035E+09 | -204330626.3 | 0.00 | 0.00 | 744.00 | 0.00 | -119704055.5 | 58.99 | 0.00 | 0.00 |
June | 0.298103E+09 | -188308575.0 | 0.00 | 0.00 | 720.00 | 0.00 | -109793942.3 | 58.99 | 0.00 | 0.00 |
July | 0.288980E+09 | -177541503.1 | 0.00 | 0.00 | 744.00 | 0.00 | -111438760.6 | 59.00 | 0.00 | 0.00 |
August | 0.293026E+09 | -181012527.3 | 0.00 | 0.00 | 744.00 | 0.00 | -112013591.4 | 59.01 | 0.00 | 0.00 |
September | 0.283483E+09 | -172848265.8 | 0.00 | 0.00 | 720.00 | 0.00 | -110634812.0 | 59.00 | 0.00 | 0.00 |
October | 0.303875E+09 | -185115368.1 | 0.00 | 0.00 | 744.00 | 0.00 | -118759986.3 | 58.99 | 0.00 | 0.00 |
November | 0.310658E+09 | -190656277.2 | 0.00 | 0.00 | 720.00 | 0.00 | -120001448.2 | 58.99 | 0.00 | 0.00 |
December | 0.334748E+09 | -208003186.4 | 0.00 | 0.00 | 744.00 | 0.00 | -126745033.6 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.378079E+10 | -.236482E+10 | 8760.00 | -.141597E+10 | 58.99 | |||||
Minimum of Months | 0.283483E+09 | -228639277.5 | 0.00 | 0.00 | 672.00 | 0.00 | -128026019.4 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.354328E+09 | -172848265.8 | 0.00 | 0.00 | 744.00 | 0.00 | -109793942.3 | 59.01 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK6
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.346594E+09 | -218678942.6 | 0.00 | 0.00 | 744.00 | 0.00 | -127915400.2 | 58.99 | 0.00 | 0.00 |
February | 0.316425E+09 | -202329959.3 | 0.00 | 0.00 | 672.00 | 0.00 | -114095271.0 | 58.99 | 0.00 | 0.00 |
March | 0.354229E+09 | -228640586.2 | 0.00 | 0.00 | 744.00 | 0.00 | -125588167.5 | 58.99 | 0.00 | 0.00 |
April | 0.325956E+09 | -207353678.1 | 0.00 | 0.00 | 720.00 | 0.00 | -118602241.0 | 59.00 | 0.00 | 0.00 |
May | 0.323675E+09 | -204313366.8 | 0.00 | 0.00 | 744.00 | 0.00 | -119361204.6 | 59.00 | 0.00 | 0.00 |
June | 0.297943E+09 | -188316312.1 | 0.00 | 0.00 | 720.00 | 0.00 | -109627044.9 | 58.99 | 0.00 | 0.00 |
July | 0.288985E+09 | -177536960.3 | 0.00 | 0.00 | 744.00 | 0.00 | -111447796.1 | 59.00 | 0.00 | 0.00 |
August | 0.293001E+09 | -181001337.8 | 0.00 | 0.00 | 744.00 | 0.00 | -111999369.3 | 59.02 | 0.00 | 0.00 |
September | 0.283231E+09 | -172855089.9 | 0.00 | 0.00 | 720.00 | 0.00 | -110375645.0 | 58.99 | 0.00 | 0.00 |
October | 0.303368E+09 | -185103143.4 | 0.00 | 0.00 | 744.00 | 0.00 | -118264888.7 | 58.99 | 0.00 | 0.00 |
November | 0.310418E+09 | -190649862.1 | 0.00 | 0.00 | 720.00 | 0.00 | -119767833.8 | 59.00 | 0.00 | 0.00 |
December | 0.334668E+09 | -207985645.6 | 0.00 | 0.00 | 744.00 | 0.00 | -126682087.5 | 59.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.377849E+10 | -.236476E+10 | 8760.00 | -.141373E+10 | 59.00 | |||||
Minimum of Months | 0.283231E+09 | -228640586.2 | 0.00 | 0.00 | 672.00 | 0.00 | -127915400.2 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.354229E+09 | -172855089.9 | 0.00 | 0.00 | 744.00 | 0.00 | -109627044.9 | 59.02 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK7
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.346691E+09 | -218676599.3 | 0.00 | 0.00 | 744.00 | 0.00 | -128014133.2 | 58.99 | 0.00 | 0.00 |
February | 0.316549E+09 | -202326660.0 | 0.00 | 0.00 | 672.00 | 0.00 | -114222009.9 | 58.99 | 0.00 | 0.00 |
March | 0.354385E+09 | -228638336.7 | 0.00 | 0.00 | 744.00 | 0.00 | -125746976.3 | 59.00 | 0.00 | 0.00 |
April | 0.326166E+09 | -207357089.8 | 0.00 | 0.00 | 720.00 | 0.00 | -118808615.9 | 58.99 | 0.00 | 0.00 |
May | 0.323854E+09 | -204338464.6 | 0.00 | 0.00 | 744.00 | 0.00 | -119515524.3 | 58.99 | 0.00 | 0.00 |
June | 0.298060E+09 | -188304158.8 | 0.00 | 0.00 | 720.00 | 0.00 | -109756166.3 | 58.99 | 0.00 | 0.00 |
July | 0.289071E+09 | -177549891.1 | 0.00 | 0.00 | 744.00 | 0.00 | -111520995.1 | 58.99 | 0.00 | 0.00 |
August | 0.293071E+09 | -181040462.3 | 0.00 | 0.00 | 744.00 | 0.00 | -112030237.3 | 59.00 | 0.00 | 0.00 |
September | 0.283330E+09 | -172855687.2 | 0.00 | 0.00 | 720.00 | 0.00 | -110474677.7 | 58.99 | 0.00 | 0.00 |
October | 0.303508E+09 | -185102356.8 | 0.00 | 0.00 | 744.00 | 0.00 | -118405281.9 | 59.00 | 0.00 | 0.00 |
November | 0.310563E+09 | -190655600.0 | 0.00 | 0.00 | 720.00 | 0.00 | -119907291.7 | 58.99 | 0.00 | 0.00 |
December | 0.334783E+09 | -207978971.2 | 0.00 | 0.00 | 744.00 | 0.00 | -126803964.4 | 59.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.378003E+10 | -.236482E+10 | 8760.00 | -.141521E+10 | 58.99 | |||||
Minimum of Months | 0.283330E+09 | -228638336.7 | 0.00 | 0.00 | 672.00 | 0.00 | -128014133.2 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.354385E+09 | -172855687.2 | 0.00 | 0.00 | 744.00 | 0.00 | -109756166.3 | 59.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 226.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 275.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 304.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 325.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 385.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 434.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 417.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 421.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 352.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 317.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 269.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 236.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3965.83 | ||||||||||
Minimum of Months | 226.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 434.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.272189E+11 | 60015.82 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.153052E+11 | 60015.82 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.126462E+11 | 60015.82 | 01-MAR-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.485721E+10 | 60015.82 | 01-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.290385E+10 | 60015.82 | 01-MAY-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 85400526.07 | 5074.73 | 16-JUN-08:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.419334E+09 | 18889.84 | 20-SEP-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.167627E+10 | 60015.82 | 10-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.836867E+10 | 60015.82 | 12-NOV-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.197024E+11 | 60015.82 | 01-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.931835E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.272189E+11 | 60015.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.907488E+10 | 31651.70 | 05-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.460551E+10 | 31651.70 | 01-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.305384E+10 | 31651.70 | 04-MAR-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.848772E+09 | 22838.95 | 29-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.520532E+09 | 17275.85 | 08-MAY-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 7013642.49 | 817.64 | 19-SEP-08:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.214302E+09 | 6902.48 | 10-OCT-08:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.202352E+10 | 31651.70 | 27-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.596662E+10 | 31651.70 | 14-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.263150E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.907488E+10 | 31651.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_3:3_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.102425E+11 | 31588.81 | 06-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.547398E+10 | 31588.81 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.393098E+10 | 31588.81 | 04-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.119577E+10 | 27717.60 | 30-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.760951E+09 | 30033.74 | 08-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 8040.33 | 13.40 | 16-JUN-11:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 29846278.56 | 3643.29 | 19-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.391846E+09 | 8513.24 | 10-OCT-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.262761E+10 | 31588.81 | 26-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.707384E+10 | 31588.81 | 03-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.317274E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.102425E+11 | 31588.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_4:4_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.105148E+11 | 31668.80 | 06-JAN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.566483E+10 | 31668.80 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.414942E+10 | 31668.80 | 03-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.131200E+10 | 31668.80 | 30-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.839119E+09 | 31668.80 | 08-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 175956.36 | 293.26 | 16-JUN-11:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 42316564.06 | 3761.91 | 19-SEP-07:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.448443E+09 | 14566.06 | 10-OCT-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.280492E+10 | 31668.80 | 26-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.731789E+10 | 31668.80 | 03-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.330940E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.105148E+11 | 31668.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_5:5_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.109080E+11 | 31532.93 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.595859E+10 | 31532.93 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.448147E+10 | 31532.93 | 03-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.151857E+10 | 31532.93 | 29-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.962412E+09 | 31532.93 | 01-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 1723785.78 | 714.74 | 16-JUN-11:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 68686737.24 | 4556.58 | 20-SEP-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.534693E+09 | 19564.24 | 10-OCT-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.305321E+10 | 31532.93 | 13-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.767444E+10 | 31532.93 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.351618E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.109080E+11 | 31532.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_6:6_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.220903E+11 | 59057.68 | 01-JAN-10:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.126245E+11 | 59057.68 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.102530E+11 | 59057.68 | 01-MAR-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.412863E+10 | 59057.68 | 01-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.264072E+10 | 59057.68 | 01-MAY-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 76762979.44 | 6465.62 | 16-JUN-08:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.438667E+09 | 20566.39 | 20-SEP-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.173346E+10 | 59057.68 | 10-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.734180E+10 | 59057.68 | 12-NOV-10:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.161366E+11 | 59057.68 | 01-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.774645E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.220903E+11 | 59057.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_7:7_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.108692E+11 | 29739.22 | 01-JAN-10:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.601133E+10 | 29739.22 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.465333E+10 | 29739.22 | 03-MAR-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.169894E+10 | 29739.22 | 01-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.107960E+10 | 29739.22 | 01-MAY-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 13555016.24 | 1997.58 | 16-JUN-11:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.121864E+09 | 3778.16 | 20-SEP-08:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.631372E+09 | 29739.22 | 10-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.325114E+10 | 29739.22 | 12-NOV-10:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.772929E+10 | 29739.22 | 01-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.360597E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.108692E+11 | 29739.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_8:8_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.109690E+11 | 29532.26 | 01-JAN-10:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.610154E+10 | 29532.26 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.477199E+10 | 29532.26 | 03-MAR-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.177782E+10 | 29532.26 | 01-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.112984E+10 | 29532.26 | 01-MAY-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16744278.04 | 1950.68 | 16-JUN-11:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.133474E+09 | 4088.30 | 20-SEP-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.663191E+09 | 29532.26 | 10-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.333381E+10 | 29532.26 | 12-NOV-10:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.783474E+10 | 29532.26 | 01-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.367321E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.109690E+11 | 29532.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_9:9_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.114322E+11 | 29792.91 | 01-JAN-10:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.647810E+10 | 29792.91 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.521568E+10 | 29792.91 | 01-MAR-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.207957E+10 | 29792.91 | 01-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.131887E+10 | 29792.91 | 01-MAY-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 32627205.26 | 2453.24 | 16-JUN-08:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.186441E+09 | 9690.27 | 20-SEP-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.786805E+09 | 29792.91 | 10-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.363961E+10 | 29792.91 | 12-NOV-10:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.825714E+10 | 29792.91 | 01-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.394270E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.114322E+11 | 29792.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_10:10_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.142219E+11 | 31561.97 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.828557E+10 | 31561.97 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.706374E+10 | 31561.97 | 01-MAR-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.313995E+10 | 31561.97 | 01-APR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.192857E+10 | 31561.97 | 01-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 89945236.27 | 4167.64 | 17-JUN-08:65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 3691511.58 | 508.05 | 17-AUG-11:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.343903E+09 | 26542.18 | 20-SEP-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.114607E+10 | 31561.97 | 05-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.468205E+10 | 31561.97 | 02-NOV-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.101779E+11 | 31561.97 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.510833E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.142219E+11 | 31561.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 652.35 | 652.35 | 0.17 | 27-FEB-15:30 | 0.17 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 44930229.26 | 44930229.26 | 3626.24 | 07-APR-14:00 | 3626.24 | 0.00 |
May | 0.00 | 0.00 | 0.160071E+10 | 0.158855E+10 | 13882.30 | 20-MAY-08:62 | 13015.18 | 0.00 |
June | 0.00 | 0.00 | 0.685468E+10 | 0.650213E+10 | 32407.66 | 22-JUN-08:61 | 27086.34 | 0.00 |
July | 0.00 | 0.00 | 0.138966E+11 | 0.134715E+11 | 33530.85 | 19-JUL-08:61 | 24647.15 | 0.00 |
August | 0.00 | 0.00 | 0.113311E+11 | 0.112351E+11 | 31717.55 | 09-AUG-08:61 | 31717.55 | 0.00 |
September | 0.00 | 0.00 | 0.623327E+10 | 0.585621E+10 | 31834.48 | 07-SEP-08:62 | 20191.57 | 0.00 |
October | 0.00 | 0.00 | 0.654754E+09 | 0.654754E+09 | 10764.98 | 18-OCT-14:00 | 10764.98 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.406160E+11 | 0.393532E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.138966E+11 | 0.134715E+11 | 33530.85 | 31717.55 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 1241973.82 | 1241973.82 | 391.63 | 28-FEB-22:40 | 391.63 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 82914028.55 | 82914028.55 | 16439.98 | 16-APR-17:08 | 16439.98 | 0.00 |
May | 0.00 | 0.00 | 0.128623E+10 | 0.127826E+10 | 16753.69 | 20-MAY-18:17 | 16753.69 | 0.00 |
June | 0.00 | 0.00 | 0.458622E+10 | 0.441008E+10 | 17543.43 | 21-JUN-20:02 | 14173.53 | 0.00 |
July | 0.00 | 0.00 | 0.855892E+10 | 0.835146E+10 | 18075.45 | 18-JUL-22:00 | 10307.36 | 0.00 |
August | 0.00 | 0.00 | 0.710181E+10 | 0.706241E+10 | 17107.52 | 09-AUG-08:61 | 17107.52 | 0.00 |
September | 0.00 | 0.00 | 0.387189E+10 | 0.369029E+10 | 17825.06 | 06-SEP-20:02 | 12485.96 | 0.00 |
October | 0.00 | 0.00 | 0.459964E+09 | 0.459916E+09 | 16439.98 | 15-OCT-17:50 | 16439.98 | 0.00 |
November | 0.00 | 0.00 | 5739374.68 | 5739374.68 | 16439.98 | 04-NOV-19:22 | 16439.98 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.259549E+11 | 0.253423E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.855892E+10 | 0.835146E+10 | 18075.45 | 17107.52 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 1234.25 | 1234.25 | 0.14 | 27-FEB-15:30 | 0.14 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 44272571.47 | 44272571.47 | 3069.45 | 07-APR-14:00 | 3069.45 | 0.00 |
May | 0.00 | 0.00 | 0.776409E+09 | 0.774422E+09 | 16463.83 | 20-MAY-07:02 | 15318.82 | 0.00 |
June | 0.00 | 0.00 | 0.330800E+10 | 0.320456E+10 | 17325.27 | 22-JUN-07:01 | 13321.84 | 0.00 |
July | 0.00 | 0.00 | 0.639486E+10 | 0.627977E+10 | 17922.16 | 19-JUL-07:01 | 12809.35 | 0.00 |
August | 0.00 | 0.00 | 0.529548E+10 | 0.527357E+10 | 16896.06 | 09-AUG-07:01 | 15868.91 | 0.00 |
September | 0.00 | 0.00 | 0.269996E+10 | 0.257269E+10 | 17093.35 | 07-SEP-07:01 | 11038.98 | 0.00 |
October | 0.00 | 0.00 | 0.355620E+09 | 0.355249E+09 | 16315.41 | 19-OCT-07:02 | 16315.41 | 0.00 |
November | 0.00 | 0.00 | 1474.50 | 1474.50 | 0.19 | 04-NOV-14:00 | 0.19 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.188746E+11 | 0.185045E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.639486E+10 | 0.627977E+10 | 17922.16 | 16315.41 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 731.04 | 731.04 | 0.13 | 27-FEB-15:30 | 0.13 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 37874608.75 | 37874608.75 | 2904.47 | 07-APR-14:00 | 2904.47 | 0.00 |
May | 0.00 | 0.00 | 0.750487E+09 | 0.748711E+09 | 16517.64 | 20-MAY-07:02 | 15362.64 | 0.00 |
June | 0.00 | 0.00 | 0.328687E+10 | 0.318445E+10 | 17384.49 | 22-JUN-07:01 | 13368.66 | 0.00 |
July | 0.00 | 0.00 | 0.641595E+10 | 0.629994E+10 | 17984.36 | 19-JUL-07:01 | 12854.32 | 0.00 |
August | 0.00 | 0.00 | 0.530665E+10 | 0.528476E+10 | 16955.25 | 09-AUG-07:01 | 15932.28 | 0.00 |
September | 0.00 | 0.00 | 0.269735E+10 | 0.256945E+10 | 17153.19 | 07-SEP-07:01 | 11086.49 | 0.00 |
October | 0.00 | 0.00 | 0.332248E+09 | 0.331973E+09 | 15246.29 | 19-OCT-07:02 | 15246.29 | 0.00 |
November | 0.00 | 0.00 | 1255.29 | 1255.29 | 0.18 | 04-NOV-14:00 | 0.18 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.188274E+11 | 0.184572E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.641595E+10 | 0.629994E+10 | 17984.36 | 15932.28 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 533.88 | 533.88 | 0.11 | 27-FEB-15:30 | 0.11 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 28271230.13 | 28271230.13 | 2589.09 | 07-APR-14:00 | 2589.09 | 0.00 |
May | 0.00 | 0.00 | 0.691132E+09 | 0.689838E+09 | 16182.86 | 20-MAY-07:02 | 15021.62 | 0.00 |
June | 0.00 | 0.00 | 0.316758E+10 | 0.306957E+10 | 17279.57 | 22-JUN-07:01 | 13258.50 | 0.00 |
July | 0.00 | 0.00 | 0.626908E+10 | 0.615674E+10 | 17877.95 | 19-JUL-07:01 | 12768.62 | 0.00 |
August | 0.00 | 0.00 | 0.517134E+10 | 0.515061E+10 | 16853.87 | 09-AUG-07:01 | 15818.50 | 0.00 |
September | 0.00 | 0.00 | 0.261453E+10 | 0.248958E+10 | 17051.09 | 07-SEP-07:01 | 10998.70 | 0.00 |
October | 0.00 | 0.00 | 0.294658E+09 | 0.294571E+09 | 12113.10 | 19-OCT-07:02 | 12113.10 | 0.00 |
November | 0.00 | 0.00 | 1029.31 | 1029.31 | 0.15 | 04-NOV-14:00 | 0.15 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.182366E+11 | 0.178792E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.626908E+10 | 0.615674E+10 | 17877.95 | 15818.50 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 21871252.20 | 21871252.20 | 2660.77 | 07-APR-14:10 | 2660.77 | 0.00 |
May | 0.00 | 0.00 | 0.988411E+09 | 0.982366E+09 | 12014.41 | 20-MAY-16:00 | 12014.41 | 0.00 |
June | 0.00 | 0.00 | 0.513484E+10 | 0.488344E+10 | 31634.01 | 22-JUN-08:61 | 26689.54 | 0.00 |
July | 0.00 | 0.00 | 0.102999E+11 | 0.100260E+11 | 32649.68 | 19-JUL-08:61 | 24638.53 | 0.00 |
August | 0.00 | 0.00 | 0.857517E+10 | 0.850554E+10 | 31025.35 | 09-AUG-08:61 | 31025.35 | 0.00 |
September | 0.00 | 0.00 | 0.437374E+10 | 0.407027E+10 | 31099.66 | 07-SEP-08:62 | 19928.79 | 0.00 |
October | 0.00 | 0.00 | 0.438425E+09 | 0.438425E+09 | 9739.84 | 18-OCT-14:30 | 9739.84 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.298324E+11 | 0.289280E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.102999E+11 | 0.100260E+11 | 32649.68 | 31025.35 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 7916.53 | 7916.53 | 12.67 | 27-FEB-14:30 | 12.67 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 13980721.75 | 13980721.75 | 1864.49 | 07-APR-14:00 | 1864.49 | 0.00 |
May | 0.00 | 0.00 | 0.571380E+09 | 0.570864E+09 | 10743.53 | 20-MAY-08:62 | 10417.63 | 0.00 |
June | 0.00 | 0.00 | 0.289003E+10 | 0.279119E+10 | 16335.69 | 22-JUN-08:61 | 13830.63 | 0.00 |
July | 0.00 | 0.00 | 0.577434E+10 | 0.567237E+10 | 16872.90 | 19-JUL-08:61 | 12724.90 | 0.00 |
August | 0.00 | 0.00 | 0.475913E+10 | 0.474171E+10 | 16016.37 | 09-AUG-08:61 | 16016.37 | 0.00 |
September | 0.00 | 0.00 | 0.234164E+10 | 0.221829E+10 | 16070.75 | 07-SEP-08:62 | 10309.15 | 0.00 |
October | 0.00 | 0.00 | 0.233224E+09 | 0.233224E+09 | 5789.52 | 18-OCT-14:40 | 5789.52 | 0.00 |
November | 0.00 | 0.00 | 24841.71 | 24841.71 | 40.90 | 04-NOV-15:50 | 40.90 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.165838E+11 | 0.162417E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.577434E+10 | 0.567237E+10 | 16872.90 | 16016.37 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 219.05 | 219.05 | 0.08 | 27-FEB-15:10 | 0.08 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 12107782.95 | 12107782.95 | 1762.21 | 07-APR-14:00 | 1762.21 | 0.00 |
May | 0.00 | 0.00 | 0.552021E+09 | 0.551551E+09 | 9129.45 | 20-MAY-08:62 | 8910.19 | 0.00 |
June | 0.00 | 0.00 | 0.283271E+10 | 0.273566E+10 | 16201.57 | 22-JUN-08:61 | 13699.96 | 0.00 |
July | 0.00 | 0.00 | 0.569710E+10 | 0.559663E+10 | 16734.63 | 19-JUL-08:61 | 12606.69 | 0.00 |
August | 0.00 | 0.00 | 0.469306E+10 | 0.467608E+10 | 15883.76 | 09-AUG-08:61 | 15883.76 | 0.00 |
September | 0.00 | 0.00 | 0.230733E+10 | 0.218561E+10 | 15939.30 | 07-SEP-08:62 | 10212.63 | 0.00 |
October | 0.00 | 0.00 | 0.225221E+09 | 0.225221E+09 | 5703.87 | 18-OCT-14:40 | 5703.87 | 0.00 |
November | 0.00 | 0.00 | 25168.32 | 25168.32 | 41.42 | 04-NOV-15:40 | 41.42 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.163196E+11 | 0.159829E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.569710E+10 | 0.559663E+10 | 16734.63 | 15883.76 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 7527645.09 | 7527645.09 | 1440.84 | 07-APR-14:00 | 1440.84 | 0.00 |
May | 0.00 | 0.00 | 0.494256E+09 | 0.493890E+09 | 6518.34 | 20-MAY-16:00 | 6518.34 | 0.00 |
June | 0.00 | 0.00 | 0.267878E+10 | 0.258632E+10 | 16035.94 | 22-JUN-08:61 | 13518.79 | 0.00 |
July | 0.00 | 0.00 | 0.552458E+10 | 0.542791E+10 | 16565.06 | 19-JUL-08:61 | 12446.46 | 0.00 |
August | 0.00 | 0.00 | 0.454145E+10 | 0.452584E+10 | 15720.04 | 09-AUG-08:61 | 15720.04 | 0.00 |
September | 0.00 | 0.00 | 0.221912E+10 | 0.210124E+10 | 15777.72 | 07-SEP-08:62 | 10077.09 | 0.00 |
October | 0.00 | 0.00 | 0.196796E+09 | 0.196796E+09 | 5438.97 | 18-OCT-14:40 | 5438.97 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.156625E+11 | 0.153395E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.552458E+10 | 0.542791E+10 | 16565.06 | 15720.04 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 1423322.56 | 1423322.56 | 645.44 | 07-APR-14:00 | 645.44 | 0.00 |
May | 0.00 | 0.00 | 0.421943E+09 | 0.421725E+09 | 6253.00 | 20-MAY-16:00 | 6253.00 | 0.00 |
June | 0.00 | 0.00 | 0.253964E+10 | 0.245254E+10 | 17471.30 | 22-JUN-08:61 | 14685.41 | 0.00 |
July | 0.00 | 0.00 | 0.551283E+10 | 0.542035E+10 | 18082.45 | 19-JUL-08:61 | 13397.22 | 0.00 |
August | 0.00 | 0.00 | 0.449384E+10 | 0.448079E+10 | 17132.18 | 09-AUG-08:61 | 17132.18 | 0.00 |
September | 0.00 | 0.00 | 0.213916E+10 | 0.203121E+10 | 17192.46 | 07-SEP-08:62 | 10908.15 | 0.00 |
October | 0.00 | 0.00 | 0.157970E+09 | 0.157970E+09 | 5191.56 | 18-OCT-14:40 | 5191.56 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.152668E+11 | 0.149660E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.551283E+10 | 0.542035E+10 | 18082.45 | 17132.18 | 0.00 |
Report: FanReportMonthly
For: PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.207644E+10 | 0.51 | 2076.88 | 01-JAN-09:01 | 1.01 |
February | 0.168331E+10 | 0.48 | 2076.88 | 01-FEB-08:61 | 1.01 |
March | 0.177404E+10 | 0.46 | 2076.88 | 01-MAR-09:01 | 1.01 |
April | 0.156339E+10 | 0.43 | 2076.88 | 01-APR-08:61 | 1.01 |
May | 0.156774E+10 | 0.42 | 2076.88 | 01-MAY-08:61 | 1.01 |
June | 0.146609E+10 | 0.41 | 2076.88 | 21-JUN-08:61 | 0.99 |
July | 0.155617E+10 | 0.42 | 2076.88 | 01-JUL-08:62 | 0.99 |
August | 0.155059E+10 | 0.42 | 2076.88 | 01-AUG-08:62 | 1.00 |
September | 0.149565E+10 | 0.42 | 2076.88 | 01-SEP-08:62 | 1.00 |
October | 0.154212E+10 | 0.42 | 2076.88 | 10-OCT-08:61 | 1.01 |
November | 0.163108E+10 | 0.45 | 2076.88 | 12-NOV-09:02 | 1.01 |
December | 0.192367E+10 | 0.49 | 2076.88 | 01-DEC-09:01 | 1.01 |
Annual Sum or Average | 0.198303E+11 | 0.44 | |||
Minimum of Months | 0.146609E+10 | 0.41 | 2076.88 | 0.99 | |
Maximum of Months | 0.207644E+10 | 0.51 | 2076.88 | 1.01 |
Report: FanReportMonthly
For: PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.159169E+10 | 0.59 | 1165.46 | 02-JAN-19:40 | 1.04 |
February | 0.143963E+10 | 0.58 | 1165.46 | 13-FEB-16:00 | 1.04 |
March | 0.160821E+10 | 0.55 | 1165.46 | 01-MAR-09:09 | 1.04 |
April | 0.160468E+10 | 0.62 | 1165.46 | 18-APR-15:40 | 1.04 |
May | 0.177420E+10 | 0.64 | 1165.46 | 22-MAY-15:15 | 1.04 |
June | 0.185265E+10 | 0.66 | 1165.46 | 08-JUN-10:20 | 1.04 |
July | 0.190609E+10 | 0.65 | 1165.46 | 01-JUL-08:10 | 1.03 |
August | 0.190852E+10 | 0.65 | 1165.46 | 22-AUG-10:20 | 1.03 |
September | 0.181998E+10 | 0.67 | 1165.46 | 01-SEP-08:30 | 1.03 |
October | 0.176488E+10 | 0.67 | 1165.46 | 23-OCT-17:00 | 1.04 |
November | 0.157594E+10 | 0.60 | 1165.46 | 02-NOV-08:20 | 1.04 |
December | 0.157621E+10 | 0.55 | 1165.46 | 01-DEC-10:00 | 1.04 |
Annual Sum or Average | 0.204227E+11 | 0.62 | |||
Minimum of Months | 0.143963E+10 | 0.55 | 1165.46 | 1.03 | |
Maximum of Months | 0.190852E+10 | 0.67 | 1165.46 | 1.04 |
Report: FanReportMonthly
For: PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.168162E+10 | 0.56 | 1161.98 | 01-JAN-09:30 | 1.04 |
February | 0.152266E+10 | 0.56 | 1161.98 | 01-FEB-08:08 | 1.04 |
March | 0.171509E+10 | 0.57 | 1161.98 | 01-MAR-08:07 | 1.04 |
April | 0.163142E+10 | 0.56 | 1161.98 | 01-APR-10:00 | 1.04 |
May | 0.169835E+10 | 0.57 | 1161.98 | 01-MAY-08:09 | 1.04 |
June | 0.165652E+10 | 0.57 | 1161.98 | 01-JUN-13:40 | 1.03 |
July | 0.167325E+10 | 0.56 | 1161.98 | 02-JUL-12:50 | 1.03 |
August | 0.171509E+10 | 0.57 | 1161.98 | 01-AUG-11:10 | 1.03 |
September | 0.163142E+10 | 0.56 | 1161.98 | 01-SEP-08:05 | 1.03 |
October | 0.168162E+10 | 0.56 | 1161.98 | 02-OCT-14:00 | 1.04 |
November | 0.163142E+10 | 0.56 | 1161.98 | 02-NOV-08:06 | 1.04 |
December | 0.167325E+10 | 0.56 | 1161.98 | 01-DEC-08:06 | 1.04 |
Annual Sum or Average | 0.199117E+11 | 0.56 | |||
Minimum of Months | 0.152266E+10 | 0.56 | 1161.98 | 1.03 | |
Maximum of Months | 0.171509E+10 | 0.57 | 1161.98 | 1.04 |
Report: FanReportMonthly
For: PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.168818E+10 | 0.56 | 1166.41 | 01-JAN-09:09 | 1.04 |
February | 0.152846E+10 | 0.56 | 1166.41 | 01-FEB-08:00 | 1.04 |
March | 0.172162E+10 | 0.57 | 1166.41 | 01-MAR-08:07 | 1.04 |
April | 0.163764E+10 | 0.56 | 1166.41 | 15-APR-08:05 | 1.04 |
May | 0.170483E+10 | 0.57 | 1166.41 | 01-MAY-07:06 | 1.04 |
June | 0.166284E+10 | 0.57 | 1166.41 | 01-JUN-13:20 | 1.03 |
July | 0.167963E+10 | 0.56 | 1166.41 | 01-JUL-07:03 | 1.03 |
August | 0.172162E+10 | 0.57 | 1166.41 | 01-AUG-08:15 | 1.03 |
September | 0.163764E+10 | 0.56 | 1166.41 | 01-SEP-07:03 | 1.03 |
October | 0.168803E+10 | 0.56 | 1166.41 | 02-OCT-13:00 | 1.04 |
November | 0.163764E+10 | 0.56 | 1166.41 | 22-NOV-12:20 | 1.04 |
December | 0.167963E+10 | 0.56 | 1166.41 | 01-DEC-09:08 | 1.04 |
Annual Sum or Average | 0.199878E+11 | 0.56 | |||
Minimum of Months | 0.152846E+10 | 0.56 | 1166.41 | 1.03 | |
Maximum of Months | 0.172162E+10 | 0.57 | 1166.41 | 1.04 |
Report: FanReportMonthly
For: PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.167756E+10 | 0.57 | 1158.89 | 04-JAN-18:20 | 1.04 |
February | 0.151861E+10 | 0.56 | 1158.89 | 03-FEB-08:00 | 1.04 |
March | 0.171052E+10 | 0.57 | 1158.89 | 01-MAR-20:30 | 1.04 |
April | 0.162708E+10 | 0.56 | 1158.89 | 12-APR-08:30 | 1.04 |
May | 0.169383E+10 | 0.57 | 1158.89 | 02-MAY-08:20 | 1.04 |
June | 0.165211E+10 | 0.57 | 1158.89 | 15-JUN-14:10 | 1.04 |
July | 0.166880E+10 | 0.56 | 1158.89 | 20-JUL-08:15 | 1.03 |
August | 0.171052E+10 | 0.57 | 1158.89 | 09-AUG-18:10 | 1.03 |
September | 0.162708E+10 | 0.56 | 1158.89 | 01-SEP-08:62 | 1.03 |
October | 0.167714E+10 | 0.56 | 1158.89 | 02-OCT-18:20 | 1.04 |
November | 0.162708E+10 | 0.56 | 1158.89 | 03-NOV-07:50 | 1.04 |
December | 0.166880E+10 | 0.56 | 1158.89 | 01-DEC-12:00 | 1.04 |
Annual Sum or Average | 0.198591E+11 | 0.56 | |||
Minimum of Months | 0.151861E+10 | 0.56 | 1158.89 | 1.03 | |
Maximum of Months | 0.171052E+10 | 0.57 | 1158.89 | 1.04 |
Report: FanReportMonthly
For: PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.153885E+10 | 0.39 | 2025.61 | 01-JAN-10:01 | 1.01 |
February | 0.124000E+10 | 0.35 | 2025.61 | 01-FEB-08:61 | 1.01 |
March | 0.131656E+10 | 0.35 | 2025.61 | 01-MAR-09:01 | 1.00 |
April | 0.113504E+10 | 0.32 | 2025.61 | 01-APR-08:61 | 1.01 |
May | 0.114817E+10 | 0.32 | 2025.61 | 01-MAY-08:61 | 1.01 |
June | 0.107056E+10 | 0.31 | 2025.61 | 21-JUN-08:61 | 0.99 |
July | 0.111360E+10 | 0.31 | 2025.61 | 01-JUL-08:62 | 0.99 |
August | 0.113904E+10 | 0.31 | 2025.61 | 01-AUG-08:62 | 1.00 |
September | 0.107628E+10 | 0.31 | 2025.61 | 01-SEP-08:62 | 1.00 |
October | 0.111784E+10 | 0.31 | 2025.61 | 10-OCT-08:61 | 1.00 |
November | 0.120117E+10 | 0.33 | 2025.61 | 12-NOV-10:01 | 1.01 |
December | 0.140865E+10 | 0.36 | 2025.61 | 01-DEC-09:01 | 1.01 |
Annual Sum or Average | 0.145058E+11 | 0.33 | |||
Minimum of Months | 0.107056E+10 | 0.31 | 2025.61 | 0.99 | |
Maximum of Months | 0.153885E+10 | 0.39 | 2025.61 | 1.01 |
Report: FanReportMonthly
For: PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.145066E+10 | 0.53 | 1084.36 | 01-JAN-10:03 | 1.04 |
February | 0.131174E+10 | 0.52 | 1084.36 | 01-FEB-10:40 | 1.04 |
March | 0.147957E+10 | 0.53 | 1084.36 | 01-MAR-12:10 | 1.04 |
April | 0.140534E+10 | 0.52 | 1084.36 | 01-APR-10:30 | 1.04 |
May | 0.146389E+10 | 0.52 | 1084.36 | 01-MAY-08:06 | 1.04 |
June | 0.142876E+10 | 0.53 | 1084.36 | 01-JUN-13:50 | 1.03 |
July | 0.144047E+10 | 0.51 | 1084.36 | 01-JUL-10:00 | 1.03 |
August | 0.147951E+10 | 0.53 | 1084.36 | 01-AUG-08:03 | 1.03 |
September | 0.140534E+10 | 0.52 | 1084.36 | 01-SEP-19:07 | 1.04 |
October | 0.144828E+10 | 0.52 | 1084.36 | 03-OCT-10:30 | 1.04 |
November | 0.140534E+10 | 0.52 | 1084.36 | 02-NOV-11:50 | 1.04 |
December | 0.144073E+10 | 0.52 | 1084.36 | 01-DEC-11:40 | 1.04 |
Annual Sum or Average | 0.171596E+11 | 0.52 | |||
Minimum of Months | 0.131174E+10 | 0.51 | 1084.36 | 1.03 | |
Maximum of Months | 0.147957E+10 | 0.53 | 1084.36 | 1.04 |
Report: FanReportMonthly
For: PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.143758E+10 | 0.53 | 1074.47 | 20-JAN-08:50 | 1.04 |
February | 0.129985E+10 | 0.52 | 1074.47 | 06-FEB-11:10 | 1.04 |
March | 0.146608E+10 | 0.53 | 1074.47 | 01-MAR-14:40 | 1.04 |
April | 0.139252E+10 | 0.52 | 1074.47 | 02-APR-09:07 | 1.04 |
May | 0.145054E+10 | 0.52 | 1074.47 | 01-MAY-18:10 | 1.04 |
June | 0.141573E+10 | 0.53 | 1074.47 | 01-JUN-18:30 | 1.03 |
July | 0.142733E+10 | 0.51 | 1074.47 | 01-JUL-08:30 | 1.03 |
August | 0.146601E+10 | 0.53 | 1074.47 | 01-AUG-17:30 | 1.03 |
September | 0.139252E+10 | 0.52 | 1074.47 | 05-SEP-18:00 | 1.03 |
October | 0.143507E+10 | 0.52 | 1074.47 | 05-OCT-17:10 | 1.04 |
November | 0.139252E+10 | 0.52 | 1074.47 | 03-NOV-09:30 | 1.04 |
December | 0.142759E+10 | 0.52 | 1074.47 | 14-DEC-18:10 | 1.04 |
Annual Sum or Average | 0.170033E+11 | 0.52 | |||
Minimum of Months | 0.129985E+10 | 0.51 | 1074.47 | 1.03 | |
Maximum of Months | 0.146608E+10 | 0.53 | 1074.47 | 1.04 |
Report: FanReportMonthly
For: PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.142327E+10 | 0.54 | 1062.54 | 02-JAN-14:20 | 1.04 |
February | 0.128545E+10 | 0.52 | 1062.54 | 02-FEB-09:40 | 1.04 |
March | 0.145021E+10 | 0.53 | 1062.54 | 08-MAR-09:20 | 1.04 |
April | 0.137705E+10 | 0.52 | 1062.54 | 06-APR-16:00 | 1.04 |
May | 0.143443E+10 | 0.52 | 1062.54 | 01-MAY-12:00 | 1.04 |
June | 0.140000E+10 | 0.53 | 1062.54 | 05-JUN-08:62 | 1.03 |
July | 0.141148E+10 | 0.51 | 1062.54 | 03-JUL-19:10 | 1.03 |
August | 0.144973E+10 | 0.53 | 1062.54 | 02-AUG-09:40 | 1.03 |
September | 0.137705E+10 | 0.52 | 1062.54 | 02-SEP-11:20 | 1.03 |
October | 0.141913E+10 | 0.52 | 1062.54 | 02-OCT-08:15 | 1.04 |
November | 0.137705E+10 | 0.52 | 1062.54 | 01-NOV-08:07 | 1.04 |
December | 0.141190E+10 | 0.52 | 1062.54 | 06-DEC-14:20 | 1.04 |
Annual Sum or Average | 0.168168E+11 | 0.52 | |||
Minimum of Months | 0.128545E+10 | 0.51 | 1062.54 | 1.03 | |
Maximum of Months | 0.145021E+10 | 0.54 | 1062.54 | 1.04 |
Report: FanReportMonthly
For: PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.158217E+10 | 0.62 | 1160.49 | 10-JAN-18:40 | 1.05 |
February | 0.141207E+10 | 0.56 | 1160.49 | 21-FEB-08:30 | 1.04 |
March | 0.159000E+10 | 0.55 | 1160.49 | 01-MAR-10:10 | 1.04 |
April | 0.150399E+10 | 0.52 | 1160.49 | 02-APR-13:30 | 1.04 |
May | 0.156666E+10 | 0.52 | 1160.49 | 10-MAY-08:05 | 1.04 |
June | 0.152906E+10 | 0.53 | 1160.49 | 01-JUN-15:10 | 1.03 |
July | 0.154159E+10 | 0.51 | 1160.49 | 12-JUL-19:00 | 1.04 |
August | 0.158337E+10 | 0.53 | 1160.49 | 01-AUG-17:50 | 1.03 |
September | 0.150399E+10 | 0.52 | 1160.49 | 13-SEP-08:50 | 1.03 |
October | 0.154995E+10 | 0.52 | 1160.49 | 05-OCT-18:30 | 1.04 |
November | 0.150571E+10 | 0.53 | 1160.49 | 04-NOV-09:10 | 1.04 |
December | 0.154977E+10 | 0.55 | 1160.49 | 02-DEC-13:30 | 1.04 |
Annual Sum or Average | 0.184183E+11 | 0.54 | |||
Minimum of Months | 0.141207E+10 | 0.51 | 1160.49 | 1.03 | |
Maximum of Months | 0.159000E+10 | 0.62 | 1160.49 | 1.05 |
Report: ZoneTemperatureOscillationReportMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 1.97 | 0.31 |
February | 1.24 | 0.78 |
March | 1.40 | 0.57 |
April | 0.26 | 1.50 |
May | 0.14 | 1.50 |
June | 0.25 | 1.50 |
July | 0.39 | 0.00 |
August | 0.25 | 0.50 |
September | 0.28 | 1.50 |
October | 0.39 | 1.29 |
November | 0.50 | 0.42 |
December | 1.10 | 0.38 |
Annual Sum or Average | 8.15 | 0.61 |
Minimum of Months | 0.14 | 0.00 |
Maximum of Months | 1.97 | 1.50 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.19 | 0.00 |
February | 0.71 | 5.21 |
March | 1.18 | 4.45 |
April | 1.75 | 4.48 |
May | 4.02 | 4.03 |
June | 5.57 | 3.24 |
July | 5.17 | 2.53 |
August | 7.65 | 2.84 |
September | 6.08 | 3.09 |
October | 1.56 | 3.25 |
November | 1.60 | 3.47 |
December | 0.46 | 3.95 |
Annual Sum or Average | 35.93 | 3.26 |
Minimum of Months | 0.19 | 0.00 |
Maximum of Months | 7.65 | 5.21 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.27 | 0.00 |
February | 0.17 | 0.00 |
March | 0.03 | 0.00 |
April | 0.64 | 0.75 |
May | 0.86 | 0.75 |
June | 1.52 | 0.75 |
July | 3.27 | 0.73 |
August | 2.73 | 0.75 |
September | 2.18 | 0.75 |
October | 1.39 | 0.58 |
November | 0.53 | 0.75 |
December | 0.14 | 0.00 |
Annual Sum or Average | 13.74 | 0.70 |
Minimum of Months | 0.03 | 0.00 |
Maximum of Months | 3.27 | 0.75 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.26 | 0.00 |
February | 0.17 | 0.00 |
March | 0.03 | 0.00 |
April | 0.56 | 0.75 |
May | 0.78 | 0.75 |
June | 1.44 | 0.75 |
July | 3.19 | 0.73 |
August | 2.73 | 0.75 |
September | 2.01 | 0.75 |
October | 1.25 | 0.65 |
November | 0.08 | 0.75 |
December | 0.14 | 0.00 |
Annual Sum or Average | 12.64 | 0.70 |
Minimum of Months | 0.03 | 0.00 |
Maximum of Months | 3.19 | 0.75 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.48 | 0.00 |
February | 0.20 | 0.00 |
March | 0.09 | 0.00 |
April | 0.25 | 0.75 |
May | 0.47 | 0.75 |
June | 1.44 | 0.75 |
July | 3.36 | 0.73 |
August | 2.98 | 0.75 |
September | 1.76 | 0.75 |
October | 1.08 | 0.63 |
November | 0.00 | 0.00 |
December | 0.29 | 0.00 |
Annual Sum or Average | 12.40 | 0.67 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 3.36 | 0.75 |
Report: ZoneTemperatureOscillationReportMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 1.25 | 0.00 |
February | 0.52 | 0.00 |
March | 0.16 | 0.00 |
April | 0.08 | 3.30 |
May | 0.06 | 3.30 |
June | 0.55 | 3.30 |
July | 1.52 | 3.00 |
August | 0.94 | 2.32 |
September | 1.36 | 3.30 |
October | 0.39 | 2.12 |
November | 0.04 | 0.00 |
December | 0.46 | 0.00 |
Annual Sum or Average | 7.32 | 1.95 |
Minimum of Months | 0.04 | 0.00 |
Maximum of Months | 1.52 | 3.30 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.73 | 0.00 |
February | 0.31 | 0.00 |
March | 0.12 | 0.00 |
April | 0.00 | 0.00 |
May | 0.22 | 1.65 |
June | 0.63 | 1.65 |
July | 1.46 | 1.49 |
August | 0.85 | 1.27 |
September | 1.08 | 1.65 |
October | 0.17 | 0.82 |
November | 0.04 | 0.00 |
December | 0.42 | 0.00 |
Annual Sum or Average | 6.04 | 1.09 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 1.46 | 1.65 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 1.08 | 0.00 |
February | 0.43 | 0.00 |
March | 0.12 | 0.00 |
April | 0.00 | 0.00 |
May | 0.14 | 1.65 |
June | 0.55 | 1.65 |
July | 1.40 | 1.49 |
August | 0.85 | 1.44 |
September | 1.08 | 1.65 |
October | 0.08 | 0.00 |
November | 0.04 | 0.00 |
December | 0.50 | 0.00 |
Annual Sum or Average | 6.29 | 0.99 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 1.40 | 1.65 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 1.54 | 0.00 |
February | 0.70 | 0.00 |
March | 0.21 | 0.00 |
April | 0.00 | 0.00 |
May | 0.10 | 0.94 |
June | 0.63 | 1.65 |
July | 1.32 | 1.58 |
August | 1.19 | 1.50 |
September | 1.11 | 1.65 |
October | 0.08 | 0.00 |
November | 0.18 | 0.00 |
December | 0.90 | 0.00 |
Annual Sum or Average | 7.95 | 0.86 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 1.54 | 1.65 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 4.24 | 0.00 |
February | 2.43 | 0.11 |
March | 1.26 | 0.00 |
April | 0.78 | 0.00 |
May | 0.21 | 0.00 |
June | 0.30 | 1.65 |
July | 1.15 | 1.45 |
August | 0.60 | 1.35 |
September | 1.03 | 1.65 |
October | 0.00 | 0.00 |
November | 1.17 | 0.00 |
December | 3.33 | 0.00 |
Annual Sum or Average | 16.50 | 0.30 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 4.24 | 1.65 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_1:1
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.207644E+10 | 0.340236E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.168331E+10 | 0.191316E+11 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.177404E+10 | 0.158078E+11 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.157578E+10 | 0.607151E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.198342E+10 | 0.362982E+10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.320795E+10 | 0.106751E+09 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.512727E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.446695E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.306935E+10 | 0.524168E+09 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.171017E+10 | 0.209534E+10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.163108E+10 | 0.104608E+11 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.192367E+10 | 0.246280E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.302294E+11 | 0.116479E+12 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.157578E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.512727E+10 | 0.340236E+11 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_2:2
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.159169E+10 | 0.113436E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.143997E+10 | 0.575689E+10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.160821E+10 | 0.381730E+10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.162329E+10 | 0.106096E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.205163E+10 | 0.650666E+09 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.284654E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.380592E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.348278E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.266320E+10 | 8767053.11 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.186551E+10 | 0.267877E+09 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.157728E+10 | 0.252940E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.157621E+10 | 0.745827E+10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.261322E+11 | 0.328937E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.143997E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.380592E+10 | 0.113436E+11 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_3:3
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.168162E+10 | 0.128032E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.152266E+10 | 0.684247E+10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.171509E+10 | 0.491373E+10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.164185E+10 | 0.149471E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.187216E+10 | 0.951189E+09 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.238880E+10 | 10050.41 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.311241E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.290712E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.222713E+10 | 37307848.20 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.176049E+10 | 0.489808E+09 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.163142E+10 | 0.328451E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.167325E+10 | 0.884230E+10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.241340E+11 | 0.396592E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.152266E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.311241E+10 | 0.128032E+11 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_4:4
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.168818E+10 | 0.131436E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.152847E+10 | 0.708104E+10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.172162E+10 | 0.518678E+10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.164660E+10 | 0.164000E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.187337E+10 | 0.104890E+10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.239134E+10 | 219945.45 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.312363E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.291641E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.223296E+10 | 52895705.08 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.176195E+10 | 0.560554E+09 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.163764E+10 | 0.350615E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.167963E+10 | 0.914736E+10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.242018E+11 | 0.413675E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.152847E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.312363E+10 | 0.131436E+11 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_5:5
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.167756E+10 | 0.136350E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.151861E+10 | 0.744824E+10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.171052E+10 | 0.560183E+10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.163382E+10 | 0.189821E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.184996E+10 | 0.120302E+10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.235658E+10 | 2154732.22 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.308280E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.287718E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.220519E+10 | 85858421.55 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.174304E+10 | 0.668366E+09 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.162708E+10 | 0.381651E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.166880E+10 | 0.959305E+10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.239511E+11 | 0.439523E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.151861E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.308280E+10 | 0.136350E+11 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_6:6
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.153885E+10 | 0.276128E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.124000E+10 | 0.157807E+11 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.131656E+10 | 0.128162E+11 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.114114E+10 | 0.516079E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.140906E+10 | 0.330090E+10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.239165E+10 | 95953724.30 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.378595E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.336297E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.218259E+10 | 0.548334E+09 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.123175E+10 | 0.216682E+10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.120117E+10 | 0.917725E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.140865E+10 | 0.201708E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.222103E+11 | 0.968306E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.114114E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.378595E+10 | 0.276128E+11 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_7:7
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.145066E+10 | 0.135865E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.131174E+10 | 0.751417E+10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.147957E+10 | 0.581666E+10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.140871E+10 | 0.212368E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.159436E+10 | 0.134950E+10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.207579E+10 | 16943770.30 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.275103E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.255979E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.192460E+10 | 0.152330E+09 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.150079E+10 | 0.789215E+09 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.140534E+10 | 0.406392E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.144073E+10 | 0.966161E+10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.209031E+11 | 0.450746E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.131174E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.275103E+10 | 0.135865E+11 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_8:8
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.143758E+10 | 0.137113E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.129985E+10 | 0.762692E+10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.146608E+10 | 0.596499E+10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.139545E+10 | 0.222227E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.157682E+10 | 0.141230E+10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.205071E+10 | 20930347.55 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.272135E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.253205E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.190446E+10 | 0.166842E+09 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.148583E+10 | 0.828988E+09 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.139252E+10 | 0.416726E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.142759E+10 | 0.979343E+10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.206903E+11 | 0.459152E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.129985E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.272135E+10 | 0.137113E+11 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_9:9
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.142327E+10 | 0.142903E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.128545E+10 | 0.809762E+10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.145021E+10 | 0.651960E+10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.137889E+10 | 0.259946E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.154839E+10 | 0.164858E+10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.200326E+10 | 40784006.57 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.266964E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.248392E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.187045E+10 | 0.233051E+09 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.146371E+10 | 0.983506E+09 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.137705E+10 | 0.454951E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.141190E+10 | 0.103214E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.203661E+11 | 0.492838E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.128545E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.266964E+10 | 0.142903E+11 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_10:10
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.158217E+10 | 0.177774E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.141207E+10 | 0.103570E+11 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.159000E+10 | 0.882968E+10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.150435E+10 | 0.392494E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.166610E+10 | 0.241071E+10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.211136E+10 | 0.112432E+09 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.280947E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.261671E+10 | 4614389.48 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.198463E+10 | 0.429879E+09 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.158622E+10 | 0.143259E+10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.150571E+10 | 0.585256E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.154977E+10 | 0.127224E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.219186E+11 | 0.638541E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.141207E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.280947E+10 | 0.177774E+11 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_1:1
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.207644E+10 | 0.00 | 0.272189E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.168331E+10 | 652.35 | 0.153052E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.177404E+10 | 0.00 | 0.126462E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.156339E+10 | 44930229.26 | 0.485721E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.156774E+10 | 0.160071E+10 | 0.290385E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.146609E+10 | 0.685468E+10 | 85400526.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.155617E+10 | 0.138966E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.155059E+10 | 0.113311E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.149565E+10 | 0.623327E+10 | 0.419334E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.154212E+10 | 0.654754E+09 | 0.167627E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.163108E+10 | 0.00 | 0.836867E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.192367E+10 | 0.00 | 0.197024E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.198303E+11 | 0.406160E+11 | 0.931835E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.146609E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.207644E+10 | 0.138966E+11 | 0.272189E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_2:2
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.159169E+10 | 0.00 | 0.907488E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.143963E+10 | 1241973.82 | 0.460551E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.160821E+10 | 0.00 | 0.305384E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.160468E+10 | 82914028.55 | 0.848772E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.177420E+10 | 0.128623E+10 | 0.520532E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.185265E+10 | 0.458622E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.190609E+10 | 0.855892E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.190852E+10 | 0.710181E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.181998E+10 | 0.387189E+10 | 7013642.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.176488E+10 | 0.459964E+09 | 0.214302E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.157594E+10 | 5739374.68 | 0.202352E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.157621E+10 | 0.00 | 0.596662E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.204227E+11 | 0.259549E+11 | 0.263150E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.143963E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.190852E+10 | 0.855892E+10 | 0.907488E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_3:3
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.168162E+10 | 0.00 | 0.102425E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.152266E+10 | 1234.25 | 0.547398E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.171509E+10 | 0.00 | 0.393098E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.163142E+10 | 44272571.47 | 0.119577E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.169835E+10 | 0.776409E+09 | 0.760951E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.165652E+10 | 0.330800E+10 | 8040.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.167325E+10 | 0.639486E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.171509E+10 | 0.529548E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.163142E+10 | 0.269996E+10 | 29846278.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.168162E+10 | 0.355620E+09 | 0.391846E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.163142E+10 | 1474.50 | 0.262761E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.167325E+10 | 0.00 | 0.707384E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.199117E+11 | 0.188746E+11 | 0.317274E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.152266E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.171509E+10 | 0.639486E+10 | 0.102425E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_4:4
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.168818E+10 | 0.00 | 0.105148E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.152846E+10 | 731.04 | 0.566483E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.172162E+10 | 0.00 | 0.414942E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.163764E+10 | 37874608.75 | 0.131200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.170483E+10 | 0.750487E+09 | 0.839119E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.166284E+10 | 0.328687E+10 | 175956.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.167963E+10 | 0.641595E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.172162E+10 | 0.530665E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.163764E+10 | 0.269735E+10 | 42316564.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.168803E+10 | 0.332248E+09 | 0.448443E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.163764E+10 | 1255.29 | 0.280492E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.167963E+10 | 0.00 | 0.731789E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.199878E+11 | 0.188274E+11 | 0.330940E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.152846E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.172162E+10 | 0.641595E+10 | 0.105148E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_5:5
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.167756E+10 | 0.00 | 0.109080E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.151861E+10 | 533.88 | 0.595859E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.171052E+10 | 0.00 | 0.448147E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.162708E+10 | 28271230.13 | 0.151857E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.169383E+10 | 0.691132E+09 | 0.962412E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.165211E+10 | 0.316758E+10 | 1723785.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.166880E+10 | 0.626908E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.171052E+10 | 0.517134E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.162708E+10 | 0.261453E+10 | 68686737.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.167714E+10 | 0.294658E+09 | 0.534693E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.162708E+10 | 1029.31 | 0.305321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.166880E+10 | 0.00 | 0.767444E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.198591E+11 | 0.182366E+11 | 0.351618E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.151861E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.171052E+10 | 0.626908E+10 | 0.109080E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_6:6
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.153885E+10 | 0.00 | 0.220903E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.124000E+10 | 0.00 | 0.126245E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.131656E+10 | 0.00 | 0.102530E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.113504E+10 | 21871252.20 | 0.412863E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.114817E+10 | 0.988411E+09 | 0.264072E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.107056E+10 | 0.513484E+10 | 76762979.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.111360E+10 | 0.102999E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.113904E+10 | 0.857517E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.107628E+10 | 0.437374E+10 | 0.438667E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.111784E+10 | 0.438425E+09 | 0.173346E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.120117E+10 | 0.00 | 0.734180E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.140865E+10 | 0.00 | 0.161366E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.145058E+11 | 0.298324E+11 | 0.774645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.107056E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.153885E+10 | 0.102999E+11 | 0.220903E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_7:7
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.145066E+10 | 0.00 | 0.108692E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.131174E+10 | 7916.53 | 0.601133E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.147957E+10 | 0.00 | 0.465333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.140534E+10 | 13980721.75 | 0.169894E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.146389E+10 | 0.571380E+09 | 0.107960E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.142876E+10 | 0.289003E+10 | 13555016.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.144047E+10 | 0.577434E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.147951E+10 | 0.475913E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.140534E+10 | 0.234164E+10 | 0.121864E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.144828E+10 | 0.233224E+09 | 0.631372E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.140534E+10 | 24841.71 | 0.325114E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.144073E+10 | 0.00 | 0.772929E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.171596E+11 | 0.165838E+11 | 0.360597E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.131174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.147957E+10 | 0.577434E+10 | 0.108692E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_8:8
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.143758E+10 | 0.00 | 0.109690E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.129985E+10 | 219.05 | 0.610154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.146608E+10 | 0.00 | 0.477199E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.139252E+10 | 12107782.95 | 0.177782E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.145054E+10 | 0.552021E+09 | 0.112984E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.141573E+10 | 0.283271E+10 | 16744278.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.142733E+10 | 0.569710E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.146601E+10 | 0.469306E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.139252E+10 | 0.230733E+10 | 0.133474E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.143507E+10 | 0.225221E+09 | 0.663191E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.139252E+10 | 25168.32 | 0.333381E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.142759E+10 | 0.00 | 0.783474E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.170033E+11 | 0.163196E+11 | 0.367321E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.129985E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.146608E+10 | 0.569710E+10 | 0.109690E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_9:9
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.142327E+10 | 0.00 | 0.114322E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.128545E+10 | 0.00 | 0.647810E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145021E+10 | 0.00 | 0.521568E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.137705E+10 | 7527645.09 | 0.207957E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.143443E+10 | 0.494256E+09 | 0.131887E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.140000E+10 | 0.267878E+10 | 32627205.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.141148E+10 | 0.552458E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.144973E+10 | 0.454145E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.137705E+10 | 0.221912E+10 | 0.186441E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.141913E+10 | 0.196796E+09 | 0.786805E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.137705E+10 | 0.00 | 0.363961E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.141190E+10 | 0.00 | 0.825714E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.168168E+11 | 0.156625E+11 | 0.394270E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.128545E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.145021E+10 | 0.552458E+10 | 0.114322E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_10:10
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.158217E+10 | 0.00 | 0.142219E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.141207E+10 | 0.00 | 0.828557E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.159000E+10 | 0.00 | 0.706374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.150399E+10 | 1423322.56 | 0.313995E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.156666E+10 | 0.421943E+09 | 0.192857E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.152906E+10 | 0.253964E+10 | 89945236.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.154159E+10 | 0.551283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.158337E+10 | 0.449384E+10 | 3691511.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.150399E+10 | 0.213916E+10 | 0.343903E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.154995E+10 | 0.157970E+09 | 0.114607E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.150571E+10 | 0.00 | 0.468205E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.154977E+10 | 0.00 | 0.101779E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.184183E+11 | 0.152668E+11 | 0.510833E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.141207E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.159000E+10 | 0.551283E+10 | 0.142219E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_1:1
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.207644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.340236E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.168331E+10 | 0.00 | 0.00 | 0.00 | 184.40 | 0.00 | 0.191316E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.177404E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158078E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.156339E+10 | 0.00 | 0.00 | 0.00 | 12386932.73 | 0.00 | 0.607151E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.156774E+10 | 0.00 | 0.00 | 0.00 | 0.415679E+09 | 0.00 | 0.362982E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.146609E+10 | 0.00 | 0.00 | 0.00 | 0.174186E+10 | 0.00 | 0.106751E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.155617E+10 | 0.00 | 0.00 | 0.00 | 0.357110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.155059E+10 | 0.00 | 0.00 | 0.00 | 0.291636E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.149565E+10 | 0.00 | 0.00 | 0.00 | 0.157370E+10 | 0.00 | 0.524168E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.154212E+10 | 0.00 | 0.00 | 0.00 | 0.168048E+09 | 0.00 | 0.209534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.163108E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104608E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.192367E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.246280E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.198303E+11 | 0.00 | 0.00 | 0.00 | 0.103991E+11 | 0.00 | 0.116479E+12 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.146609E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.207644E+10 | 0.00 | 0.00 | 0.00 | 0.357110E+10 | 0.00 | 0.340236E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_2:2
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.159169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113436E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.143963E+10 | 0.00 | 0.00 | 0.00 | 342949.51 | 0.00 | 0.575689E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.160821E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.381730E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.160468E+10 | 0.00 | 0.00 | 0.00 | 18609847.12 | 0.00 | 0.106096E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.177420E+10 | 0.00 | 0.00 | 0.00 | 0.277439E+09 | 0.00 | 0.650666E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.185265E+10 | 0.00 | 0.00 | 0.00 | 0.993894E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.190609E+10 | 0.00 | 0.00 | 0.00 | 0.189983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.190852E+10 | 0.00 | 0.00 | 0.00 | 0.157426E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.181998E+10 | 0.00 | 0.00 | 0.00 | 0.843218E+09 | 0.00 | 8767053.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.176488E+10 | 0.00 | 0.00 | 0.00 | 0.100631E+09 | 0.00 | 0.267877E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.157594E+10 | 0.00 | 0.00 | 0.00 | 1338097.35 | 0.00 | 0.252940E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.157621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.745827E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.204227E+11 | 0.00 | 0.00 | 0.00 | 0.570956E+10 | 0.00 | 0.328937E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.143963E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.190852E+10 | 0.00 | 0.00 | 0.00 | 0.189983E+10 | 0.00 | 0.113436E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_3:3
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.168162E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128032E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.152266E+10 | 0.00 | 0.00 | 0.00 | 304.19 | 0.00 | 0.684247E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.171509E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.491373E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.163142E+10 | 0.00 | 0.00 | 0.00 | 10427759.82 | 0.00 | 0.149471E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.169835E+10 | 0.00 | 0.00 | 0.00 | 0.173812E+09 | 0.00 | 0.951189E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.165652E+10 | 0.00 | 0.00 | 0.00 | 0.732282E+09 | 0.00 | 10050.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.167325E+10 | 0.00 | 0.00 | 0.00 | 0.143916E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.171509E+10 | 0.00 | 0.00 | 0.00 | 0.119204E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.163142E+10 | 0.00 | 0.00 | 0.00 | 0.595704E+09 | 0.00 | 37307848.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.168162E+10 | 0.00 | 0.00 | 0.00 | 78871148.27 | 0.00 | 0.489808E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.163142E+10 | 0.00 | 0.00 | 0.00 | 363.40 | 0.00 | 0.328451E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.167325E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.884230E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.199117E+11 | 0.00 | 0.00 | 0.00 | 0.422229E+10 | 0.00 | 0.396592E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.152266E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.171509E+10 | 0.00 | 0.00 | 0.00 | 0.143916E+10 | 0.00 | 0.128032E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_4:4
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.168818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131436E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.152846E+10 | 0.00 | 0.00 | 0.00 | 180.17 | 0.00 | 0.708104E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.172162E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.518678E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.163764E+10 | 0.00 | 0.00 | 0.00 | 8962830.16 | 0.00 | 0.164000E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.170483E+10 | 0.00 | 0.00 | 0.00 | 0.168542E+09 | 0.00 | 0.104890E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.166284E+10 | 0.00 | 0.00 | 0.00 | 0.728502E+09 | 0.00 | 219945.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.167963E+10 | 0.00 | 0.00 | 0.00 | 0.144400E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.172162E+10 | 0.00 | 0.00 | 0.00 | 0.119478E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.163764E+10 | 0.00 | 0.00 | 0.00 | 0.595321E+09 | 0.00 | 52895705.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.168803E+10 | 0.00 | 0.00 | 0.00 | 73922097.01 | 0.00 | 0.560554E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.163764E+10 | 0.00 | 0.00 | 0.00 | 309.38 | 0.00 | 0.350615E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.167963E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.914736E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.199878E+11 | 0.00 | 0.00 | 0.00 | 0.421403E+10 | 0.00 | 0.413675E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.152846E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.172162E+10 | 0.00 | 0.00 | 0.00 | 0.144400E+10 | 0.00 | 0.131436E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_5:5
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.167756E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136350E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.151861E+10 | 0.00 | 0.00 | 0.00 | 131.58 | 0.00 | 0.744824E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.171052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.560183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.162708E+10 | 0.00 | 0.00 | 0.00 | 6743219.33 | 0.00 | 0.189821E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.169383E+10 | 0.00 | 0.00 | 0.00 | 0.156134E+09 | 0.00 | 0.120302E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.165211E+10 | 0.00 | 0.00 | 0.00 | 0.704473E+09 | 0.00 | 2154732.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.166880E+10 | 0.00 | 0.00 | 0.00 | 0.141400E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.171052E+10 | 0.00 | 0.00 | 0.00 | 0.116666E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.162708E+10 | 0.00 | 0.00 | 0.00 | 0.578111E+09 | 0.00 | 85858421.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.167714E+10 | 0.00 | 0.00 | 0.00 | 65902276.21 | 0.00 | 0.668366E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.162708E+10 | 0.00 | 0.00 | 0.00 | 253.68 | 0.00 | 0.381651E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.166880E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.959305E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.198591E+11 | 0.00 | 0.00 | 0.00 | 0.409202E+10 | 0.00 | 0.439523E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.151861E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.171052E+10 | 0.00 | 0.00 | 0.00 | 0.141400E+10 | 0.00 | 0.136350E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_6:6
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.153885E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.276128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.124000E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.157807E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.131656E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128162E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.113504E+10 | 0.00 | 0.00 | 0.00 | 6101979.30 | 0.00 | 0.516079E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.114817E+10 | 0.00 | 0.00 | 0.00 | 0.260881E+09 | 0.00 | 0.330090E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.107056E+10 | 0.00 | 0.00 | 0.00 | 0.132109E+10 | 0.00 | 95953724.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.111360E+10 | 0.00 | 0.00 | 0.00 | 0.267235E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.113904E+10 | 0.00 | 0.00 | 0.00 | 0.222393E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.107628E+10 | 0.00 | 0.00 | 0.00 | 0.110631E+10 | 0.00 | 0.548334E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.111784E+10 | 0.00 | 0.00 | 0.00 | 0.113910E+09 | 0.00 | 0.216682E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.120117E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.917725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.140865E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.201708E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.145058E+11 | 0.00 | 0.00 | 0.00 | 0.770458E+10 | 0.00 | 0.968306E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.107056E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.153885E+10 | 0.00 | 0.00 | 0.00 | 0.267235E+10 | 0.00 | 0.276128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_7:7
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.145066E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135865E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.131174E+10 | 0.00 | 0.00 | 0.00 | 1950.17 | 0.00 | 0.751417E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.147957E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.581666E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.140534E+10 | 0.00 | 0.00 | 0.00 | 3376391.56 | 0.00 | 0.212368E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.146389E+10 | 0.00 | 0.00 | 0.00 | 0.130464E+09 | 0.00 | 0.134950E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.142876E+10 | 0.00 | 0.00 | 0.00 | 0.647030E+09 | 0.00 | 16943770.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.144047E+10 | 0.00 | 0.00 | 0.00 | 0.131056E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.147951E+10 | 0.00 | 0.00 | 0.00 | 0.108028E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.140534E+10 | 0.00 | 0.00 | 0.00 | 0.519265E+09 | 0.00 | 0.152330E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.144828E+10 | 0.00 | 0.00 | 0.00 | 52510055.86 | 0.00 | 0.789215E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.140534E+10 | 0.00 | 0.00 | 0.00 | 6112.72 | 0.00 | 0.406392E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.144073E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.966161E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.171596E+11 | 0.00 | 0.00 | 0.00 | 0.374349E+10 | 0.00 | 0.450746E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.131174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.147957E+10 | 0.00 | 0.00 | 0.00 | 0.131056E+10 | 0.00 | 0.135865E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_8:8
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.143758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137113E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.129985E+10 | 0.00 | 0.00 | 0.00 | 53.99 | 0.00 | 0.762692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.146608E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.596499E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.139252E+10 | 0.00 | 0.00 | 0.00 | 2930201.31 | 0.00 | 0.222227E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.145054E+10 | 0.00 | 0.00 | 0.00 | 0.126285E+09 | 0.00 | 0.141230E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.141573E+10 | 0.00 | 0.00 | 0.00 | 0.634979E+09 | 0.00 | 20930347.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.142733E+10 | 0.00 | 0.00 | 0.00 | 0.129402E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.146601E+10 | 0.00 | 0.00 | 0.00 | 0.106604E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.139252E+10 | 0.00 | 0.00 | 0.00 | 0.511938E+09 | 0.00 | 0.166842E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.143507E+10 | 0.00 | 0.00 | 0.00 | 50763375.44 | 0.00 | 0.828988E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.139252E+10 | 0.00 | 0.00 | 0.00 | 6192.89 | 0.00 | 0.416726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.142759E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.979343E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.170033E+11 | 0.00 | 0.00 | 0.00 | 0.368696E+10 | 0.00 | 0.459152E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.129985E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.146608E+10 | 0.00 | 0.00 | 0.00 | 0.129402E+10 | 0.00 | 0.137113E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_9:9
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.142327E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142903E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.128545E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.809762E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145021E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.651960E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.137705E+10 | 0.00 | 0.00 | 0.00 | 1837287.17 | 0.00 | 0.259946E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.143443E+10 | 0.00 | 0.00 | 0.00 | 0.113957E+09 | 0.00 | 0.164858E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.140000E+10 | 0.00 | 0.00 | 0.00 | 0.603260E+09 | 0.00 | 40784006.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.141148E+10 | 0.00 | 0.00 | 0.00 | 0.125816E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.144973E+10 | 0.00 | 0.00 | 0.00 | 0.103419E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.137705E+10 | 0.00 | 0.00 | 0.00 | 0.493397E+09 | 0.00 | 0.233051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.141913E+10 | 0.00 | 0.00 | 0.00 | 44578733.95 | 0.00 | 0.983506E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.137705E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.454951E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.141190E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103214E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.168168E+11 | 0.00 | 0.00 | 0.00 | 0.354938E+10 | 0.00 | 0.492838E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.128545E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.145021E+10 | 0.00 | 0.00 | 0.00 | 0.125816E+10 | 0.00 | 0.142903E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_10:10
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.158217E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.177774E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.141207E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103570E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.159000E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.882968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.150399E+10 | 0.00 | 0.00 | 0.00 | 357054.17 | 0.00 | 0.392494E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.156666E+10 | 0.00 | 0.00 | 0.00 | 99444175.13 | 0.00 | 0.241071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.152906E+10 | 0.00 | 0.00 | 0.00 | 0.582303E+09 | 0.00 | 0.112432E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.154159E+10 | 0.00 | 0.00 | 0.00 | 0.126788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.158337E+10 | 0.00 | 0.00 | 0.00 | 0.103334E+10 | 0.00 | 4614389.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.150399E+10 | 0.00 | 0.00 | 0.00 | 0.480638E+09 | 0.00 | 0.429879E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.154995E+10 | 0.00 | 0.00 | 0.00 | 36272491.08 | 0.00 | 0.143259E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.150571E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.585256E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.154977E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127224E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.184183E+11 | 0.00 | 0.00 | 0.00 | 0.350024E+10 | 0.00 | 0.638541E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.141207E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.159000E+10 | 0.00 | 0.00 | 0.00 | 0.126788E+10 | 0.00 | 0.177774E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.436091E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.176674E+11 | 0.00 | 0.00 | 0.52 |
February | 0.561528E+10 | 0.00 | 0.00 | 26429.48 | 0.00 | 0.961633E+10 | 28171705.48 | 0.00 | 0.52 |
March | 0.799350E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.666278E+10 | 0.00 | 0.00 | 0.53 |
April | 0.706203E+10 | 0.00 | 0.00 | 612420.49 | 0.00 | 0.231004E+10 | 0.514088E+09 | 0.00 | 0.55 |
May | 0.529980E+10 | 44976645.61 | 0.00 | 7938030.17 | 4388204.76 | 0.130747E+10 | 0.201888E+10 | 0.00 | 0.65 |
June | 0.132255E+10 | 0.576588E+09 | 0.00 | 18509347.41 | 0.00 | 0.00 | 0.404117E+10 | 0.00 | 0.79 |
July | 0.178993E+09 | 0.147809E+10 | 0.00 | 23940039.64 | 2453321.20 | 0.00 | 0.292181E+10 | 0.00 | 0.78 |
August | 0.491286E+09 | 0.103972E+10 | 0.00 | 24393598.19 | 1586576.58 | 0.00 | 0.405558E+10 | 0.00 | 0.83 |
September | 0.297003E+10 | 0.547279E+09 | 0.00 | 15096302.10 | 588046.86 | 11484720.71 | 0.392524E+10 | 0.00 | 0.76 |
October | 0.709547E+10 | 3858383.72 | 0.00 | 4305204.65 | 0.00 | 0.448085E+09 | 0.264731E+10 | 0.00 | 0.62 |
November | 0.867532E+10 | 0.00 | 0.00 | 74139.29 | 0.00 | 0.398633E+10 | 0.128231E+09 | 0.00 | 0.52 |
December | 0.679856E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118079E+11 | 0.00 | 0.00 | 0.53 |
Annual Sum or Average | 0.578637E+11 | 0.369052E+10 | 0.00 | 94895511.43 | 9016149.39 | 0.538178E+11 | 0.202805E+11 | 0.00 | 0.63 |
Minimum of Months | 0.178993E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.52 |
Maximum of Months | 0.867532E+10 | 0.147809E+10 | 0.00 | 24393598.19 | 4388204.76 | 0.176674E+11 | 0.405558E+10 | 0.00 | 0.83 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.172112E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.626142E+10 | 0.00 | 0.00 | 0.39 |
February | 0.215985E+10 | 0.00 | 0.00 | 154229.12 | 0.00 | 0.327039E+10 | 0.162276E+09 | 0.00 | 0.40 |
March | 0.313947E+10 | 0.00 | 0.00 | 2174.07 | 0.00 | 0.211586E+10 | 1475561.95 | 0.00 | 0.39 |
April | 0.257795E+10 | 0.00 | 0.00 | 1060088.56 | 0.00 | 0.573589E+09 | 0.974517E+09 | 0.00 | 0.51 |
May | 0.185047E+10 | 22474747.53 | 0.00 | 4009869.91 | 755523.36 | 0.301385E+09 | 0.213247E+10 | 0.00 | 0.76 |
June | 0.238655E+09 | 0.270803E+09 | 0.00 | 8266580.61 | 0.00 | 0.00 | 0.322321E+10 | 0.00 | 1.02 |
July | 24182982.46 | 0.716178E+09 | 0.00 | 8523698.71 | 2187887.16 | 0.00 | 0.195110E+10 | 0.00 | 0.91 |
August | 0.133975E+09 | 0.513262E+09 | 0.00 | 9569073.00 | 886653.10 | 0.00 | 0.279894E+10 | 0.00 | 1.04 |
September | 0.764078E+09 | 0.266104E+09 | 0.00 | 7241305.45 | 487040.39 | 0.00 | 0.334315E+10 | 0.00 | 0.94 |
October | 0.209039E+10 | 2190595.06 | 0.00 | 4261660.12 | 0.00 | 18052506.23 | 0.312499E+10 | 0.00 | 0.71 |
November | 0.323263E+10 | 0.00 | 0.00 | 509938.16 | 0.00 | 0.123369E+10 | 0.470223E+09 | 0.00 | 0.42 |
December | 0.244781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.416517E+10 | 0.00 | 0.00 | 0.38 |
Annual Sum or Average | 0.203806E+11 | 0.179101E+10 | 0.00 | 43598617.72 | 4317104.02 | 0.179396E+11 | 0.181824E+11 | 0.00 | 0.66 |
Minimum of Months | 24182982.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.323263E+10 | 0.716178E+09 | 0.00 | 9569073.00 | 2187887.16 | 0.626142E+10 | 0.334315E+10 | 0.00 | 1.04 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.116544E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.727406E+10 | 0.00 | 0.00 | 0.41 |
February | 0.174483E+10 | 0.00 | 0.00 | 46000.62 | 0.00 | 0.408086E+10 | 67110320.13 | 0.00 | 0.42 |
March | 0.285234E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.276585E+10 | 0.00 | 0.00 | 0.42 |
April | 0.280767E+10 | 0.00 | 0.00 | 383357.02 | 0.00 | 0.706565E+09 | 0.415238E+09 | 0.00 | 0.48 |
May | 0.205870E+10 | 20538262.43 | 0.00 | 1738205.89 | 2301492.08 | 0.428346E+09 | 0.117469E+10 | 0.00 | 0.64 |
June | 0.454097E+09 | 0.250973E+09 | 0.00 | 4742732.24 | 5114277.33 | 0.00 | 0.213572E+10 | 0.00 | 0.84 |
July | 99032621.84 | 0.618228E+09 | 0.00 | 5268292.34 | 30132278.20 | 0.00 | 0.122858E+10 | 0.00 | 0.74 |
August | 0.272858E+09 | 0.457794E+09 | 0.00 | 6028827.89 | 18303697.00 | 0.00 | 0.190164E+10 | 0.00 | 0.86 |
September | 0.108778E+10 | 0.219833E+09 | 0.00 | 4358443.46 | 14317342.47 | 1657336.04 | 0.207813E+10 | 0.00 | 0.78 |
October | 0.243566E+10 | 2376748.03 | 0.00 | 2224134.91 | 0.00 | 0.196813E+09 | 0.168911E+10 | 0.00 | 0.61 |
November | 0.301577E+10 | 0.00 | 0.00 | 83008.40 | 0.00 | 0.179828E+10 | 0.127125E+09 | 0.00 | 0.42 |
December | 0.202895E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.500846E+10 | 0.00 | 0.00 | 0.41 |
Annual Sum or Average | 0.200231E+11 | 0.156974E+10 | 0.00 | 24873002.77 | 70169087.08 | 0.222609E+11 | 0.108173E+11 | 0.00 | 0.59 |
Minimum of Months | 99032621.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.301577E+10 | 0.618228E+09 | 0.00 | 6028827.89 | 30132278.20 | 0.727406E+10 | 0.213572E+10 | 0.00 | 0.86 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.941007E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.749824E+10 | 0.00 | 0.00 | 0.41 |
February | 0.161140E+10 | 0.00 | 0.00 | 28888.09 | 0.00 | 0.422132E+10 | 45119456.05 | 0.00 | 0.42 |
March | 0.268293E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.292734E+10 | 0.00 | 0.00 | 0.42 |
April | 0.271060E+10 | 0.00 | 0.00 | 315142.00 | 0.00 | 0.806730E+09 | 0.362492E+09 | 0.00 | 0.47 |
May | 0.198474E+10 | 20435314.79 | 0.00 | 1612794.42 | 2639608.40 | 0.509594E+09 | 0.111594E+10 | 0.00 | 0.63 |
June | 0.456344E+09 | 0.250740E+09 | 0.00 | 4678118.79 | 5111943.44 | 0.00 | 0.211959E+10 | 0.00 | 0.84 |
July | 99988182.40 | 0.618467E+09 | 0.00 | 5302632.59 | 29897272.64 | 0.00 | 0.123112E+10 | 0.00 | 0.74 |
August | 0.284424E+09 | 0.457797E+09 | 0.00 | 6052876.25 | 18042634.20 | 0.00 | 0.189638E+10 | 0.00 | 0.86 |
September | 0.111575E+10 | 0.219687E+09 | 0.00 | 4282498.33 | 14289049.57 | 3166932.48 | 0.202481E+10 | 0.00 | 0.77 |
October | 0.246739E+10 | 2378863.34 | 0.00 | 2022972.79 | 0.00 | 0.223618E+09 | 0.156566E+10 | 0.00 | 0.60 |
November | 0.288462E+10 | 0.00 | 0.00 | 56932.10 | 0.00 | 0.194066E+10 | 87486507.22 | 0.00 | 0.42 |
December | 0.181478E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.522141E+10 | 0.00 | 0.00 | 0.41 |
Annual Sum or Average | 0.190540E+11 | 0.156950E+10 | 0.00 | 24352855.37 | 69980508.25 | 0.233521E+11 | 0.104486E+11 | 0.00 | 0.58 |
Minimum of Months | 99988182.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.288462E+10 | 0.618467E+09 | 0.00 | 6052876.25 | 29897272.64 | 0.749824E+10 | 0.211959E+10 | 0.00 | 0.86 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.723189E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.771573E+10 | 0.00 | 0.00 | 0.41 |
February | 0.142740E+10 | 0.00 | 0.00 | 15424.02 | 0.00 | 0.440949E+10 | 25323649.03 | 0.00 | 0.41 |
March | 0.237107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.323051E+10 | 0.00 | 0.00 | 0.42 |
April | 0.247408E+10 | 0.00 | 0.00 | 230460.42 | 0.00 | 0.104718E+10 | 0.288527E+09 | 0.00 | 0.46 |
May | 0.188307E+10 | 20437391.11 | 0.00 | 1331747.22 | 2963808.81 | 0.654348E+09 | 0.960892E+09 | 0.00 | 0.61 |
June | 0.484531E+09 | 0.249827E+09 | 0.00 | 4265746.58 | 5135023.42 | 0.00 | 0.199114E+10 | 0.00 | 0.82 |
July | 0.108679E+09 | 0.617738E+09 | 0.00 | 4993183.15 | 30401872.05 | 0.00 | 0.118224E+10 | 0.00 | 0.73 |
August | 0.304206E+09 | 0.457764E+09 | 0.00 | 5691952.16 | 18430830.31 | 0.00 | 0.181562E+10 | 0.00 | 0.85 |
September | 0.116098E+10 | 0.219095E+09 | 0.00 | 3902987.30 | 14416145.72 | 3700591.90 | 0.188224E+10 | 0.00 | 0.76 |
October | 0.252165E+10 | 2375270.31 | 0.00 | 1647026.54 | 0.00 | 0.257426E+09 | 0.134025E+10 | 0.00 | 0.58 |
November | 0.267361E+10 | 0.00 | 0.00 | 30524.08 | 0.00 | 0.215151E+10 | 48644740.43 | 0.00 | 0.41 |
December | 0.150897E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.552626E+10 | 0.00 | 0.00 | 0.41 |
Annual Sum or Average | 0.176414E+11 | 0.156724E+10 | 0.00 | 22109051.48 | 71347680.31 | 0.249962E+11 | 0.953488E+10 | 0.00 | 0.57 |
Minimum of Months | 0.108679E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.267361E+10 | 0.617738E+09 | 0.00 | 5691952.16 | 30401872.05 | 0.771573E+10 | 0.199114E+10 | 0.00 | 0.85 |
Report: MechanicalVentilationLoadsMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.612726E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149217E+11 | 0.00 | 0.00 | 0.38 |
February | 0.182708E+10 | 0.00 | 0.00 | 1727.99 | 0.00 | 0.887412E+10 | 6665470.48 | 0.00 | 0.38 |
March | 0.381079E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.640899E+10 | 0.00 | 0.00 | 0.39 |
April | 0.400973E+10 | 0.00 | 0.00 | 156797.01 | 0.00 | 0.241067E+10 | 0.174563E+09 | 0.00 | 0.39 |
May | 0.343475E+10 | 28776989.82 | 0.00 | 1688248.71 | 5328962.39 | 0.140472E+10 | 0.795081E+09 | 0.00 | 0.45 |
June | 0.986989E+09 | 0.486945E+09 | 0.00 | 5477914.12 | 333335.85 | 0.00 | 0.218236E+10 | 0.00 | 0.54 |
July | 0.166589E+09 | 0.122514E+10 | 0.00 | 6098642.49 | 27451310.94 | 0.00 | 0.126822E+10 | 0.00 | 0.50 |
August | 0.420187E+09 | 0.859276E+09 | 0.00 | 7457422.44 | 28156652.39 | 0.00 | 0.219002E+10 | 0.00 | 0.57 |
September | 0.227143E+10 | 0.407759E+09 | 0.00 | 4867417.79 | 28304157.34 | 16612514.16 | 0.201374E+10 | 0.00 | 0.52 |
October | 0.489227E+10 | 1834412.97 | 0.00 | 1695470.64 | 0.00 | 0.570159E+09 | 0.112763E+10 | 0.00 | 0.44 |
November | 0.425847E+10 | 0.00 | 0.00 | 1175.27 | 0.00 | 0.450114E+10 | 11078232.16 | 0.00 | 0.38 |
December | 0.169032E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112155E+11 | 0.00 | 0.00 | 0.38 |
Annual Sum or Average | 0.283813E+11 | 0.300973E+10 | 0.00 | 27444816.46 | 89574418.91 | 0.503236E+11 | 0.976936E+10 | 0.00 | 0.44 |
Minimum of Months | 0.166589E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.489227E+10 | 0.122514E+10 | 0.00 | 7457422.44 | 28304157.34 | 0.149217E+11 | 0.219002E+10 | 0.00 | 0.57 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.227484E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.753258E+10 | 0.00 | 0.00 | 0.38 |
February | 0.847117E+09 | 0.00 | 0.00 | 4231.55 | 0.00 | 0.450143E+10 | 12008141.45 | 0.00 | 0.38 |
March | 0.173116E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.337630E+10 | 0.00 | 0.00 | 0.39 |
April | 0.190552E+10 | 0.00 | 0.00 | 106602.27 | 0.00 | 0.129712E+10 | 0.173235E+09 | 0.00 | 0.41 |
May | 0.160333E+10 | 14226992.86 | 0.00 | 927720.44 | 2687121.68 | 0.775664E+09 | 0.660639E+09 | 0.00 | 0.52 |
June | 0.378348E+09 | 0.231917E+09 | 0.00 | 3236030.61 | 92359.37 | 0.00 | 0.162886E+10 | 0.00 | 0.70 |
July | 60571065.18 | 0.598520E+09 | 0.00 | 3641742.44 | 12406614.09 | 0.00 | 0.935644E+09 | 0.00 | 0.63 |
August | 0.190217E+09 | 0.429370E+09 | 0.00 | 4204198.20 | 13911889.03 | 0.00 | 0.156329E+10 | 0.00 | 0.75 |
September | 0.103831E+10 | 0.197814E+09 | 0.00 | 2847004.65 | 14660224.28 | 11606717.09 | 0.154840E+10 | 0.00 | 0.66 |
October | 0.221753E+10 | 1215078.23 | 0.00 | 1056514.16 | 0.00 | 0.338023E+09 | 0.100668E+10 | 0.00 | 0.51 |
November | 0.206067E+10 | 0.00 | 0.00 | 11471.31 | 0.00 | 0.232722E+10 | 23525692.31 | 0.00 | 0.38 |
December | 0.706013E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.573946E+10 | 0.00 | 0.00 | 0.38 |
Annual Sum or Average | 0.129663E+11 | 0.147306E+10 | 0.00 | 16035515.63 | 43758208.45 | 0.258994E+11 | 0.755228E+10 | 0.00 | 0.51 |
Minimum of Months | 60571065.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.221753E+10 | 0.598520E+09 | 0.00 | 4204198.20 | 14660224.28 | 0.753258E+10 | 0.162886E+10 | 0.00 | 0.75 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.181017E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.757890E+10 | 0.00 | 0.00 | 0.38 |
February | 0.783345E+09 | 0.00 | 0.00 | 2809.58 | 0.00 | 0.456462E+10 | 9433625.62 | 0.00 | 0.38 |
March | 0.161798E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.348801E+10 | 0.00 | 0.00 | 0.39 |
April | 0.182235E+10 | 0.00 | 0.00 | 92021.07 | 0.00 | 0.137762E+10 | 0.161012E+09 | 0.00 | 0.41 |
May | 0.157215E+10 | 14229157.64 | 0.00 | 863803.63 | 2799177.49 | 0.824445E+09 | 0.614631E+09 | 0.00 | 0.52 |
June | 0.393430E+09 | 0.231421E+09 | 0.00 | 3084454.15 | 95810.79 | 0.00 | 0.157542E+10 | 0.00 | 0.69 |
July | 65523167.78 | 0.598151E+09 | 0.00 | 3519635.30 | 12440980.21 | 0.00 | 0.914399E+09 | 0.00 | 0.62 |
August | 0.192467E+09 | 0.429582E+09 | 0.00 | 4076052.58 | 13925214.23 | 0.00 | 0.153527E+10 | 0.00 | 0.74 |
September | 0.105585E+10 | 0.197541E+09 | 0.00 | 2760234.15 | 14588071.43 | 9863583.63 | 0.150478E+10 | 0.00 | 0.65 |
October | 0.223093E+10 | 1208809.16 | 0.00 | 998643.36 | 0.00 | 0.361309E+09 | 0.944621E+09 | 0.00 | 0.50 |
November | 0.200942E+10 | 0.00 | 0.00 | 9865.25 | 0.00 | 0.237625E+10 | 20422188.49 | 0.00 | 0.38 |
December | 0.651498E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.579403E+10 | 0.00 | 0.00 | 0.38 |
Annual Sum or Average | 0.125760E+11 | 0.147213E+10 | 0.00 | 15407519.07 | 43849254.15 | 0.263750E+11 | 0.727999E+10 | 0.00 | 0.50 |
Minimum of Months | 65523167.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.223093E+10 | 0.598151E+09 | 0.00 | 4076052.58 | 14588071.43 | 0.757890E+10 | 0.157542E+10 | 0.00 | 0.74 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.101454E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.765842E+10 | 0.00 | 0.00 | 0.38 |
February | 0.550717E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.479812E+10 | 0.00 | 0.00 | 0.38 |
March | 0.121369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.388886E+10 | 0.00 | 0.00 | 0.39 |
April | 0.159891E+10 | 0.00 | 0.00 | 47652.77 | 0.00 | 0.161393E+10 | 0.102539E+09 | 0.00 | 0.40 |
May | 0.143258E+10 | 14229895.88 | 0.00 | 668025.98 | 3177235.24 | 0.987911E+09 | 0.501434E+09 | 0.00 | 0.50 |
June | 0.492251E+09 | 0.230071E+09 | 0.00 | 2570158.14 | 109417.51 | 0.00 | 0.135498E+10 | 0.00 | 0.66 |
July | 83251616.53 | 0.597164E+09 | 0.00 | 3140001.61 | 12623363.87 | 0.00 | 0.853629E+09 | 0.00 | 0.61 |
August | 0.204172E+09 | 0.430181E+09 | 0.00 | 3689121.81 | 13779963.31 | 0.00 | 0.145633E+10 | 0.00 | 0.73 |
September | 0.108641E+10 | 0.196491E+09 | 0.00 | 2469205.29 | 14698121.49 | 36528631.28 | 0.136554E+10 | 0.00 | 0.64 |
October | 0.221959E+10 | 1201162.03 | 0.00 | 787348.54 | 0.00 | 0.461838E+09 | 0.764603E+09 | 0.00 | 0.49 |
November | 0.175301E+10 | 0.00 | 0.00 | 2532.49 | 0.00 | 0.262461E+10 | 11529088.67 | 0.00 | 0.38 |
December | 0.394446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.605075E+10 | 0.00 | 0.00 | 0.38 |
Annual Sum or Average | 0.111305E+11 | 0.146934E+10 | 0.00 | 13374046.62 | 44388101.42 | 0.281210E+11 | 0.641058E+10 | 0.00 | 0.49 |
Minimum of Months | 83251616.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.221959E+10 | 0.597164E+09 | 0.00 | 3689121.81 | 14698121.49 | 0.765842E+10 | 0.145633E+10 | 0.00 | 0.73 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:18:53
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 10363618.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.773601E+10 | 0.00 | 0.00 | 0.38 |
February | 0.240482E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.508935E+10 | 0.00 | 0.00 | 0.38 |
March | 0.274095E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.480754E+10 | 0.00 | 0.00 | 0.39 |
April | 0.822683E+09 | 0.00 | 0.00 | 296.54 | 0.00 | 0.240419E+10 | 4957156.18 | 0.00 | 0.39 |
May | 0.100935E+10 | 14495617.73 | 0.00 | 387566.71 | 3724820.73 | 0.146511E+10 | 0.316813E+09 | 0.00 | 0.48 |
June | 0.611571E+09 | 0.231384E+09 | 0.00 | 1773690.84 | 117466.93 | 82768095.32 | 0.996180E+09 | 0.00 | 0.65 |
July | 0.117869E+09 | 0.594553E+09 | 0.00 | 2620680.64 | 12673751.15 | 0.00 | 0.795161E+09 | 0.00 | 0.62 |
August | 0.238460E+09 | 0.431758E+09 | 0.00 | 3018000.52 | 13771766.62 | 0.00 | 0.136889E+10 | 0.00 | 0.74 |
September | 0.932725E+09 | 0.196132E+09 | 0.00 | 1958045.21 | 13346607.44 | 0.276972E+09 | 0.119041E+10 | 0.00 | 0.64 |
October | 0.187970E+10 | 1275566.16 | 0.00 | 529231.25 | 0.00 | 0.879055E+09 | 0.562220E+09 | 0.00 | 0.48 |
November | 0.100079E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.335651E+10 | 0.00 | 0.00 | 0.38 |
December | 23769791.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.641089E+10 | 0.00 | 0.00 | 0.38 |
Annual Sum or Average | 0.716187E+10 | 0.146960E+10 | 0.00 | 10287511.71 | 43634412.88 | 0.325084E+11 | 0.523463E+10 | 0.00 | 0.49 |
Minimum of Months | 10363618.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.187970E+10 | 0.594553E+09 | 0.00 | 3018000.52 | 13771766.62 | 0.773601E+10 | 0.136889E+10 | 0.00 | 0.74 |