Program Version:EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:19
Tabular Output Report in Format: HTML
Building: RetailStripmall
Environment: RUNPERIOD 1 ** Rochester International Arpt MN USA TMY3 WMO#=726440
Simulation Timestamp: 2020-06-03 19:19:46
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2020-06-03 19:19:46
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1872.51 | 895.80 | 895.80 |
Net Site Energy | 1872.51 | 895.80 | 895.80 |
Total Source Energy | 4037.55 | 1931.55 | 1931.55 |
Net Source Energy | 4037.55 | 1931.55 | 1931.55 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 2090.32 |
Net Conditioned Building Area | 2090.32 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 908.64 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 79.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 502.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 91.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 128.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 96.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 66.31 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 963.87 | 908.64 | 0.00 | 0.00 | 0.00 | 87.30 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 908.64 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 79.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 502.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 91.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 128.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 96.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 66.31 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 283.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 115.77 | 434.69 | 0.00 | 0.00 | 0.00 | 0.04 |
Other | 61.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 461.11 | 434.69 | 0.00 | 0.00 | 0.00 | 0.04 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 283.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 115.77 | 434.69 | 0.00 | 0.00 | 0.00 | 0.04 |
Other | 61.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 461.11 | 434.69 | 0.00 | 0.00 | 0.00 | 0.04 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 963.875 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 963.875 | 100.00 |
Total On-Site and Utility Electric Sources | 963.875 | 100.00 |
Total Electricity End Uses | 963.875 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 87.30 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 87.30 | 100.00 |
Total Water End Uses | 87.30 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.33 |
Time Setpoint Not Met During Occupied Cooling | 0.67 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 2796.17 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Meter |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2015
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Meter |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTRIPMALL
| Meter |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 6A
| Meter |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_ROCHESTER
| Meter |ZoneCoolingSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ZoneHeatingSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ZoneElectricSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |SpaceGainsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |PeakSpaceGainsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |SpaceGainComponentsAtCoolingPeakMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ComfortReportSimple55Monthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |OccupantComfortDataSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |DXReportMonthly
| PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL |WindowReportMonthly
| LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR |WindowEnergyReportMonthly
| LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR |WindowZoneSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |WindowEnergyZoneSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| GAS TANK1 | GAS TANK2 | GAS TANK3 | GAS TANK4 | GAS TANK5 | GAS TANK6 | GAS TANK7 |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC_1:1_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_2:2_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_3:3_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_4:4_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_5:5_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_6:6_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_7:7_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_8:8_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_9:9_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_10:10_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL |FanReportMonthly
| PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN |ZoneTemperatureOscillationReportMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |MechanicalVentilationLoadsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2020-06-03 19:19:46
GeneralValue | |
Program Version and Build | EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:19 |
RunPeriod | RUNPERIOD 1 |
Weather File | Rochester International Arpt MN USA TMY3 WMO#=726440 |
Latitude [deg] | 43.90 |
Longitude [deg] | -92.5 |
Elevation [m] | 398.00 |
Time Zone | -6.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Above Ground Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Window Opening Area [m2] | 124.29 | 0.00 | 0.00 | 124.29 | 0.00 |
Gross Window-Wall Ratio [%] | 10.50 | 0.00 | 0.00 | 26.24 | 0.00 |
Above Ground Window-Wall Ratio [%] | 10.50 | 0.00 | 0.00 | 26.24 | 0.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Above Ground Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Window Opening Area [m2] | 124.29 | 0.00 | 0.00 | 124.29 | 0.00 |
Gross Window-Wall Ratio [%] | 10.50 | 0.00 | 0.00 | 26.24 | 0.00 |
Above Ground Window-Wall Ratio [%] | 10.50 | 0.00 | 0.00 | 26.24 | 0.00 |
Total | |
Gross Roof Area [m2] | 2090.32 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
LGSTORE1 | 348.39 | Yes | Yes | 1805.20 | 1.00 | 276.30 | 0.00 | 20.75 | 20.75 | 18.3665 | 11.61 | 4.3000 |
SMSTORE1 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.37 | 10.37 | 19.8089 | 11.61 | 4.3000 |
SMSTORE2 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.35 | 10.35 | 17.6561 | 11.61 | 4.3000 |
SMSTORE3 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.35 | 10.35 | 17.6561 | 11.61 | 4.3000 |
SMSTORE4 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.35 | 10.35 | 17.6561 | 11.61 | 4.3000 |
LGSTORE2 | 348.39 | Yes | Yes | 1805.20 | 1.00 | 157.89 | 0.00 | 20.70 | 20.70 | 13.1675 | 11.61 | 4.3000 |
SMSTORE5 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.35 | 10.35 | 13.1675 | 11.61 | 4.3000 |
SMSTORE6 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.35 | 10.35 | 13.1675 | 11.61 | 4.3000 |
SMSTORE7 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.35 | 10.35 | 13.1675 | 11.61 | 4.3000 |
SMSTORE8 | 174.19 | Yes | Yes | 902.60 | 1.00 | 197.36 | 0.00 | 10.35 | 10.35 | 13.1675 | 11.61 | 4.3000 |
Total | 2090.32 | 10831.20 | 1184.15 | 0.00 | 124.29 | 124.29 | 15.7096 | 11.61 | 4.3000 | |||
Conditioned Total | 2090.32 | 10831.20 | 1184.15 | 0.00 | 124.29 | 124.29 | 15.7096 | 11.61 | 4.3000 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:19:46
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 04-AUG-13:39 | 02-FEB-09:09 | - | - | - | 06-JAN-13:09 |
Heating | 0.00 | 363273.12 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 51081.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 31196.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 8089.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 8969.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 6503.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 105839.69 | 363273.12 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 363273.12 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 51081.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 31196.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 8089.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 8969.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 6503.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:19:46
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 984.96 | 0.00 | 0.00 | 0.00 |
Cooling | 252.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1589.92 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 288.58 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 407.66 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 304.42 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 210.01 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 3052.59 | 984.96 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 471.20 | 0.00 | 0.00 | 0.00 |
Cooling | 120.55 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 760.61 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 138.06 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 195.02 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 145.63 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 100.47 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1460.35 | 471.20 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 471.20 | 0.00 | 0.00 | 0.00 |
Cooling | 120.55 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 760.61 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 138.06 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 195.02 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 145.63 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 100.47 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1460.35 | 471.20 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:19:46
AirTerminal:SingleDuct:UncontrolledDesign Size Maximum Air Flow Rate [m3/s] | |
LGSTORE1 DIRECT AIR | 1.72 |
SMSTORE1 DIRECT AIR | 0.940466 |
SMSTORE2 DIRECT AIR | 0.951779 |
SMSTORE3 DIRECT AIR | 0.945876 |
SMSTORE4 DIRECT AIR | 0.949680 |
LGSTORE2 DIRECT AIR | 1.66 |
SMSTORE5 DIRECT AIR | 0.896549 |
SMSTORE6 DIRECT AIR | 0.887880 |
SMSTORE7 DIRECT AIR | 0.873030 |
SMSTORE8 DIRECT AIR | 0.997455 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC_1:1 | 1.72 | 1.72 | 1.72 | 1.72 | 1.72 | 1.72 | 1.00 | 1.00 | 1.72 |
PSZ-AC_2:2 | 0.940466 | 0.940466 | 0.940466 | 0.940466 | 0.940466 | 0.940466 | 1.00 | 1.000000 | 0.940466 |
PSZ-AC_3:3 | 0.951779 | 0.951779 | 0.951779 | 0.951779 | 0.951779 | 0.951779 | 1.00 | 1.00 | 0.951779 |
PSZ-AC_4:4 | 0.945876 | 0.945876 | 0.945876 | 0.945876 | 0.945876 | 0.945876 | 1.00 | 1.00 | 0.945876 |
PSZ-AC_5:5 | 0.949680 | 0.949680 | 0.949680 | 0.949680 | 0.949680 | 0.949680 | 1.00 | 1.00 | 0.949680 |
PSZ-AC_6:6 | 1.66 | 1.66 | 1.66 | 1.66 | 1.68 | 1.68 | 1.00 | 0.990917 | 1.68 |
PSZ-AC_7:7 | 0.896549 | 0.896549 | 0.896549 | 0.896549 | 0.896549 | 0.896549 | 1.00 | 1.00 | 0.896549 |
PSZ-AC_8:8 | 0.887880 | 0.887880 | 0.887880 | 0.887880 | 0.887880 | 0.887880 | 1.00 | 1.00 | 0.887880 |
PSZ-AC_9:9 | 0.873030 | 0.873030 | 0.873030 | 0.873030 | 0.873030 | 0.873030 | 1.00 | 1.00 | 0.873030 |
PSZ-AC_10:10 | 0.997455 | 0.997455 | 0.997455 | 0.997455 | 0.997455 | 0.997455 | 1.00 | 1.00 | 0.997455 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC_1:1_OA_CONTROLLER | 1.72 | 0.411453 |
PSZ-AC_2:2_OA_CONTROLLER | 0.940466 | 0.205727 |
PSZ-AC_3:3_OA_CONTROLLER | 0.951779 | 0.205727 |
PSZ-AC_4:4_OA_CONTROLLER | 0.945876 | 0.205727 |
PSZ-AC_5:5_OA_CONTROLLER | 0.949680 | 0.205727 |
PSZ-AC_6:6_OA_CONTROLLER | 1.68 | 0.411453 |
PSZ-AC_7:7_OA_CONTROLLER | 0.896549 | 0.205727 |
PSZ-AC_8:8_OA_CONTROLLER | 0.887880 | 0.205727 |
PSZ-AC_9:9_OA_CONTROLLER | 0.873030 | 0.205727 |
PSZ-AC_10:10_OA_CONTROLLER | 0.997455 | 0.205727 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC_1:1_UNITARY_PACKAGE_DX | 1.72 | 1.72 | 1.72 | 1.13 | 39525.84 | 59908.60 | 40.00 | 1.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_DX | 0.940466 | 0.940466 | 0.940466 | 0.620707 | 21275.44 | 31740.57 | 40.00 | 1.00 |
PSZ-AC_3:3_UNITARY_PACKAGE_DX | 0.951779 | 0.951779 | 0.951779 | 0.628174 | 21560.01 | 31987.27 | 40.00 | 1.00 |
PSZ-AC_4:4_UNITARY_PACKAGE_DX | 0.945876 | 0.945876 | 0.945876 | 0.624278 | 21404.43 | 31858.55 | 40.00 | 1.00 |
PSZ-AC_5:5_UNITARY_PACKAGE_DX | 0.949680 | 0.949680 | 0.949680 | 0.626789 | 21529.80 | 31941.48 | 40.00 | 1.00 |
PSZ-AC_6:6_UNITARY_PACKAGE_DX | 1.68 | 1.68 | 1.68 | 1.11 | 38828.11 | 58675.12 | 40.00 | 1.00 |
PSZ-AC_7:7_UNITARY_PACKAGE_DX | 0.896549 | 0.896549 | 0.896549 | 0.591722 | 20713.52 | 30782.84 | 40.00 | 1.00 |
PSZ-AC_8:8_UNITARY_PACKAGE_DX | 0.887880 | 0.887880 | 0.887880 | 0.586001 | 20565.68 | 30593.81 | 40.00 | 1.00 |
PSZ-AC_9:9_UNITARY_PACKAGE_DX | 0.873030 | 0.873030 | 0.873030 | 0.576200 | 20283.67 | 30269.98 | 40.00 | 1.00 |
PSZ-AC_10:10_UNITARY_PACKAGE_DX | 0.997455 | 0.997455 | 0.997455 | 0.658321 | 22894.64 | 32983.67 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | Speed 2 Design Size Rated Total Cooling Capacity [W] | Speed 2 User-Specified Rated Total Cooling Capacity [W] | Speed 1 Design Size Rated Total Cooling Capacity [W] | Speed 1 User-Specified Rated Total Cooling Capacity [W] | Speed 2 Design Size Rated Sensible Heat Ratio | Speed 2 User-Specified Rated Sensible Heat Ratio | Speed 1 Design Size Rated Sensible Heat Ratio | Speed 1 User-Specified Rated Sensible Heat Ratio | |
PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | 1.72 | 0.858555 | 1.14 | 37437.37 | 39525.84 | 19762.92 | 19762.92 | 0.695392 | 0.695390 | 0.695390 | 0.695390 |
PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | 0.940470 | 0.470235 | 0.626980 | 20125.88 | 21275.44 | 10637.72 | 10637.72 | 0.700029 | 0.700030 | 0.700030 | 0.700030 |
PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | 0.951780 | 0.475890 | 0.634520 | 20397.00 | 21560.01 | 10780.00 | 10780.00 | 0.699670 | 0.699670 | 0.699670 | 0.699670 |
PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | 0.945880 | 0.472940 | 0.630587 | 20248.36 | 21404.43 | 10702.22 | 10702.22 | 0.699946 | 0.699940 | 0.699940 | 0.699940 |
PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | 0.949680 | 0.474840 | 0.633120 | 20369.62 | 21529.80 | 10764.90 | 10764.90 | 0.699454 | 0.699450 | 0.699450 | 0.699450 |
PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | 1.68 | 0.837895 | 1.12 | 36793.97 | 38828.11 | 19414.06 | 19414.06 | 0.693667 | 0.693670 | 0.693670 | 0.693670 |
PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | 0.896550 | 0.448275 | 0.597700 | 19624.29 | 20713.52 | 10356.76 | 10356.76 | 0.694422 | 0.694420 | 0.694420 | 0.694420 |
PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | 0.887880 | 0.443940 | 0.591920 | 19487.75 | 20565.68 | 10282.84 | 10282.84 | 0.693750 | 0.693750 | 0.693750 | 0.693750 |
PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | 0.873030 | 0.436515 | 0.582020 | 19224.72 | 20283.67 | 10141.83 | 10141.83 | 0.692948 | 0.692950 | 0.692950 | 0.692950 |
PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | 0.997460 | 0.498730 | 0.664973 | 21682.54 | 22894.64 | 11447.32 | 11447.32 | 0.696151 | 0.696150 | 0.696150 | 0.696150 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | 1.72 | 1837.39 |
PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | 0.940466 | 1041.24 |
PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | 0.951779 | 1053.77 |
PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | 0.945876 | 1047.24 |
PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | 0.949680 | 1051.45 |
PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | 1.68 | 1793.17 |
PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | 0.896549 | 992.62 |
PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | 0.887880 | 983.02 |
PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | 0.873030 | 966.58 |
PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | 0.997455 | 1104.34 |
Design Size Nominal Capacity [W] | |
PSZ-AC_1:1_UNITARY_PACKAGE_HEATCOIL | 59908.60 |
PSZ-AC_2:2_UNITARY_PACKAGE_HEATCOIL | 31740.57 |
PSZ-AC_3:3_UNITARY_PACKAGE_HEATCOIL | 31987.27 |
PSZ-AC_4:4_UNITARY_PACKAGE_HEATCOIL | 31858.55 |
PSZ-AC_5:5_UNITARY_PACKAGE_HEATCOIL | 31941.48 |
PSZ-AC_6:6_UNITARY_PACKAGE_HEATCOIL | 58675.12 |
PSZ-AC_7:7_UNITARY_PACKAGE_HEATCOIL | 30782.84 |
PSZ-AC_8:8_UNITARY_PACKAGE_HEATCOIL | 30593.81 |
PSZ-AC_9:9_UNITARY_PACKAGE_HEATCOIL | 30269.98 |
PSZ-AC_10:10_UNITARY_PACKAGE_HEATCOIL | 32983.67 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:19:46
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
LGSTORE1_WALL_3 | LGSTORE1_WALL_3_DOOR_1 | LGSTORE1_WALL_3_DOOR_2 | |
LGSTORE1_WALL_1 | LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | |
SMSTORE1_WALL_1 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | |
SMSTORE1_WALL_3 | SMSTORE1_WALL_3_DOOR | |
SMSTORE2_WALL_1 | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | |
SMSTORE2_WALL_3 | SMSTORE2_WALL_3_DOOR | |
SMSTORE3_WALL_1 | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | |
SMSTORE3_WALL_3 | SMSTORE3_WALL_3_DOOR | |
SMSTORE4_WALL_1 | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | |
SMSTORE4_WALL_3 | SMSTORE4_WALL_3_DOOR | |
LGSTORE2_WALL_3 | LGSTORE2_WALL_3_DOOR_1 | LGSTORE2_WALL_3_DOOR_2 | |
LGSTORE2_WALL_1 | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | |
SMSTORE5_WALL_1 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | |
SMSTORE5_WALL_3 | SMSTORE5_WALL_3_DOOR | |
SMSTORE6_WALL_1 | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | |
SMSTORE6_WALL_3 | SMSTORE6_WALL_3_DOOR | |
SMSTORE7_WALL_1 | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | |
SMSTORE7_WALL_3 | SMSTORE7_WALL_3_DOOR | |
SMSTORE8_WALL_1 | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR | |
SMSTORE8_WALL_3 | SMSTORE8_WALL_3_DOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2020-06-03 19:19:46
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2020-06-03 19:19:46
VersionVersion ID | |
1 | 9.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 7.40 | -0.00 | -7.60 | -12.60 | -7.70 | 0.30 | 7.00 | 14.20 | 19.20 | 20.90 | 20.00 | 15.40 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Rochester International Arpt MN USA TMY3 WMO#=726440 | 43.90 | -92.50 | -6.00 | 398.00 | 96634 | 1.1486 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 6.38 | 33.50 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RetailStripmall | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 10 | 118 | 48 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | LGSTORE1 | 0.0 | 0.00 | 0.00 | 0.00 | 7.62 | 11.43 | 2.59 | 1 | 1 | 1 | 0.00 | 15.24 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 1805.20 | TARP | TARP | 348.39 | 276.30 | 247.76 | 20.75 | 6 | 8 | 0 | Yes |
2 | SMSTORE1 | 0.0 | 0.00 | 0.00 | 0.00 | 19.05 | 11.43 | 2.59 | 1 | 1 | 1 | 15.24 | 22.86 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.67 | 10.37 | 6 | 4 | 0 | Yes |
3 | SMSTORE2 | 0.0 | 0.00 | 0.00 | 0.00 | 26.67 | 11.43 | 2.59 | 1 | 1 | 1 | 22.86 | 30.48 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.35 | 6 | 4 | 0 | Yes |
4 | SMSTORE3 | 0.0 | 0.00 | 0.00 | 0.00 | 34.29 | 11.43 | 2.59 | 1 | 1 | 1 | 30.48 | 38.10 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.35 | 6 | 4 | 0 | Yes |
5 | SMSTORE4 | 0.0 | 0.00 | 0.00 | 0.00 | 41.91 | 11.43 | 2.59 | 1 | 1 | 1 | 38.10 | 45.72 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.35 | 6 | 4 | 0 | Yes |
6 | LGSTORE2 | 0.0 | 0.00 | 0.00 | 0.00 | 53.34 | 11.43 | 2.59 | 1 | 1 | 1 | 45.72 | 60.96 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 1805.20 | TARP | TARP | 348.39 | 157.89 | 129.43 | 20.70 | 6 | 8 | 0 | Yes |
7 | SMSTORE5 | 0.0 | 0.00 | 0.00 | 0.00 | 64.77 | 11.43 | 2.59 | 1 | 1 | 1 | 60.96 | 68.58 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.35 | 6 | 4 | 0 | Yes |
8 | SMSTORE6 | 0.0 | 0.00 | 0.00 | 0.00 | 72.39 | 11.43 | 2.59 | 1 | 1 | 1 | 68.58 | 76.20 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.35 | 6 | 4 | 0 | Yes |
9 | SMSTORE7 | 0.0 | 0.00 | 0.00 | 0.00 | 80.01 | 11.43 | 2.59 | 1 | 1 | 1 | 76.20 | 83.82 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.35 | 6 | 4 | 0 | Yes |
10 | SMSTORE8 | 0.0 | 0.00 | 0.00 | 0.00 | 87.63 | 11.43 | 2.59 | 1 | 1 | 1 | 83.82 | 91.44 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 197.36 | 183.13 | 10.35 | 6 | 4 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | LGSTORE1 | 348.39 | 30.0 | 11.614 | 8.610E-002 | 18.366 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 22.666 | No |
2 | SMSTORE1 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 19.809 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 24.109 | No |
3 | SMSTORE2 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 17.656 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 21.956 | No |
4 | SMSTORE3 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 17.656 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 21.956 | No |
5 | SMSTORE4 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 17.656 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 21.956 | No |
6 | LGSTORE2 | 348.39 | 30.0 | 11.614 | 8.610E-002 | 13.168 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 17.468 | No |
7 | SMSTORE5 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 13.168 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 17.468 | No |
8 | SMSTORE6 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 13.168 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 17.468 | No |
9 | SMSTORE7 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 13.168 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 17.468 | No |
10 | SMSTORE8 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 13.168 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 17.468 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | |
1 | LGSTORE1 | TYPE1_OCC_SCH | LGSTORE1 | 348.39 | 30.0 | 30.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 30 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
2 | SMSTORE1 | TYPE1_OCC_SCH | SMSTORE1 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
3 | SMSTORE2 | TYPE2_OCC_SCH | SMSTORE2 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
4 | SMSTORE3 | TYPE2_OCC_SCH | SMSTORE3 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
5 | SMSTORE4 | TYPE2_OCC_SCH | SMSTORE4 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
6 | LGSTORE2 | TYPE3_OCC_SCH | LGSTORE2 | 348.39 | 30.0 | 30.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 30 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
7 | SMSTORE5 | TYPE3_OCC_SCH | SMSTORE5 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
8 | SMSTORE6 | TYPE3_OCC_SCH | SMSTORE6 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
9 | SMSTORE7 | TYPE3_OCC_SCH | SMSTORE7 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
10 | SMSTORE8 | TYPE3_OCC_SCH | SMSTORE8 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | LGSTORE1_LIGHTS | TYPE1_LIGHT_SCH | LGSTORE1 | 348.39 | 30.0 | 4587.386 | 13.168 | 152.933 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 4587.386 |
2 | LGSTORE1_LIGHTS_ALLOWANCE | TYPE1_LIGHT_SCH | LGSTORE1 | 348.39 | 30.0 | 1811.251 | 5.199 | 60.383 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1811.251 |
3 | SMSTORE1_LIGHTS | TYPE1_LIGHT_SCH | SMSTORE1 | 174.19 | 15.0 | 2293.693 | 13.168 | 152.933 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2293.693 |
4 | SMSTORE1_LIGHTS_ALLOWANCE | TYPE1_LIGHT_SCH | SMSTORE1 | 174.19 | 15.0 | 1156.875 | 6.641 | 77.135 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1156.875 |
5 | SMSTORE2_LIGHTS | TYPE2_LIGHT_SCH | SMSTORE2 | 174.19 | 15.0 | 2293.693 | 13.168 | 152.933 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2293.693 |
6 | SMSTORE2_LIGHTS_ALLOWANCE | TYPE2_LIGHT_SCH | SMSTORE2 | 174.19 | 15.0 | 781.875 | 4.489 | 52.132 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 781.875 |
7 | SMSTORE3_LIGHTS | TYPE2_LIGHT_SCH | SMSTORE3 | 174.19 | 15.0 | 2293.693 | 13.168 | 152.933 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2293.693 |
8 | SMSTORE3_LIGHTS_ALLOWANCE | TYPE2_LIGHT_SCH | SMSTORE3 | 174.19 | 15.0 | 781.875 | 4.489 | 52.132 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 781.875 |
9 | SMSTORE4_LIGHTS | TYPE2_LIGHT_SCH | SMSTORE4 | 174.19 | 15.0 | 2293.693 | 13.168 | 152.933 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2293.693 |
10 | SMSTORE4_LIGHTS_ALLOWANCE | TYPE2_LIGHT_SCH | SMSTORE4 | 174.19 | 15.0 | 781.875 | 4.489 | 52.132 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 781.875 |
11 | LGSTORE2_LIGHTS | TYPE3_LIGHT_SCH | LGSTORE2 | 348.39 | 30.0 | 4587.386 | 13.168 | 152.933 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 4587.386 |
12 | LGSTORE2_LIGHTS_ALLOWANCE | TYPE3_LIGHT_SCH | LGSTORE2 | 348.39 | 30.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
13 | SMSTORE5_LIGHTS | TYPE3_LIGHT_SCH | SMSTORE5 | 174.19 | 15.0 | 2293.693 | 13.168 | 152.933 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2293.693 |
14 | SMSTORE5_LIGHTS_ALLOWANCE | TYPE3_LIGHT_SCH | SMSTORE5 | 174.19 | 15.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
15 | SMSTORE6_LIGHTS | TYPE3_LIGHT_SCH | SMSTORE6 | 174.19 | 15.0 | 2293.693 | 13.168 | 152.933 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2293.693 |
16 | SMSTORE6_LIGHTS_ALLOWANCE | TYPE3_LIGHT_SCH | SMSTORE6 | 174.19 | 15.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
17 | SMSTORE7_LIGHTS | TYPE3_LIGHT_SCH | SMSTORE7 | 174.19 | 15.0 | 2293.693 | 13.168 | 152.933 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2293.693 |
18 | SMSTORE7_LIGHTS_ALLOWANCE | TYPE3_LIGHT_SCH | SMSTORE7 | 174.19 | 15.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
19 | SMSTORE8_LIGHTS | TYPE3_LIGHT_SCH | SMSTORE8 | 174.19 | 15.0 | 2293.693 | 13.168 | 152.933 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2293.693 |
20 | SMSTORE8_LIGHTS_ALLOWANCE | TYPE3_LIGHT_SCH | SMSTORE8 | 174.19 | 15.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | LGSTORE1_MISCPLUG_EQUIP | TYPE1_EQUIP_SCH | LGSTORE1 | 348.39 | 30.0 | 1498.062 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1498.062 |
2 | SMSTORE1_MISCPLUG_EQUIP | TYPE1_EQUIP_SCH | SMSTORE1 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
3 | SMSTORE2_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE2 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
4 | SMSTORE3_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE3 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
5 | SMSTORE4_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE4 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
6 | LGSTORE2_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | LGSTORE2 | 348.39 | 30.0 | 1498.062 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1498.062 |
7 | SMSTORE5_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE5 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
8 | SMSTORE6_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE6 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
9 | SMSTORE7_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE7 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
10 | SMSTORE8_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE8 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.770 | 0.700 | Rough |
5 | NONRES_EXT_WALL | 20 | 4 | 7 | 0.167 | 0.3843 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
6 | LGSTORE1_FLOOR_FFACTOR | 30 | 2 | 7 | 0.167 | 0.1464 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
7 | SMSTORE1_FLOOR_FFACTOR | 31 | 2 | 7 | 0.167 | 0.8283E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
8 | SMSTORE2_FLOOR_FFACTOR | 32 | 2 | 7 | 0.167 | 0.8283E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | SMSTORE3_FLOOR_FFACTOR | 33 | 2 | 7 | 0.167 | 0.8283E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
10 | SMSTORE4_FLOOR_FFACTOR | 34 | 2 | 7 | 0.167 | 0.8283E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
11 | LGSTORE2_FLOOR_FFACTOR | 35 | 2 | 7 | 0.167 | 0.8283E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | SMSTORE5_FLOOR_FFACTOR | 36 | 2 | 7 | 0.167 | 0.8283E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | SMSTORE6_FLOOR_FFACTOR | 37 | 2 | 7 | 0.167 | 0.8283E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | SMSTORE7_FLOOR_FFACTOR | 38 | 2 | 7 | 0.167 | 0.8283E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | SMSTORE8_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.2111 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
6 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
7 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
8 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
9 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
10 | NONRES_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.368 |
11 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
12 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 6.756 |
13 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
14 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.00 |
15 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
16 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.00 |
17 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
18 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.00 |
19 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
20 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.00 |
21 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
22 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.00 |
23 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
24 | ~FC_Insulation_7 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.00 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_8 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.00 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_9 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.00 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
30 | ~FC_Insulation_10 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.659 |
31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009596 | 2.1009596 | 2.1009596 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
14 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
15 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
16 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
17 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
18 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
19 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
20 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
21 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
22 | 7 | -0.35963630E-12 | 0.61482467E-15 | -0.13288964E-12 | 0.15093609E-15 |
23 | 6 | 0.33258387E-07 | 0.11249777E-09 | 0.75805110E-08 | -0.16019892E-12 |
24 | 5 | -0.21313350E-03 | 0.93714421E-06 | -0.10927814E-03 | 0.74776115E-08 |
25 | 4 | 0.31870195 | 0.44521373E-03 | 0.10925225 | -0.37358013E-04 |
26 | 3 | -7.7913368 | 0.13499397E-01 | -2.4947666 | 0.31584435E-01 |
27 | 2 | 42.601618 | 0.47079245E-01 | 15.902165 | -0.35261900 |
28 | 1 | -81.870774 | 0.20888078E-01 | -29.712230 | 1.1068570 |
29 | 0 | 46.824331 | 0.41326549E-03 | 16.278015 | |
30 | 7 | -0.28997596E-08 | -0.17578320E-14 | 0.22751757E-14 | -0.53829073E-16 |
31 | 6 | 0.41991781E-05 | 0.27986603E-08 | 0.31940183E-02 | -0.26794102E-04 |
32 | 5 | -0.29588474E-03 | 0.16552611E-05 | -0.22396035 | 0.19582313E-02 |
33 | 4 | 0.67666006E-02 | 0.75295852E-04 | 4.8334724 | -0.45302727E-01 |
34 | 3 | -0.59297736E-01 | 0.59838054E-03 | -38.043598 | 0.39889893 |
35 | 2 | 0.21038411 | 0.99492606E-03 | 116.52712 | -1.4185167 |
36 | 1 | -0.30354941 | 0.30287292E-03 | -143.93272 | 2.0494576 |
37 | 0 | 0.14796861 | 0.73483799E-05 | 60.838472 | |
38 | 7 | -0.51571905E-08 | -0.97500959E-14 | 0.15789915E-14 | -0.32998988E-16 |
39 | 6 | 0.26247599E-05 | 0.15902949E-08 | 0.31989528E-02 | -0.26835497E-04 |
40 | 5 | -0.17282397E-03 | 0.93714128E-06 | -0.22424071 | 0.19607060E-02 |
41 | 4 | 0.38696203E-02 | 0.42548205E-04 | 4.8381400 | -0.45347597E-01 |
42 | 3 | -0.33643188E-01 | 0.33758390E-03 | -38.069955 | 0.39919029 |
43 | 2 | 0.11898200 | 0.56044665E-03 | 116.57840 | -1.4192028 |
44 | 1 | -0.17142224 | 0.17027190E-03 | -143.96290 | 2.0499538 |
45 | 0 | 0.83499932E-01 | 0.41268798E-05 | 60.838472 | |
46 | 7 | -0.51571905E-08 | -0.97500958E-14 | 0.15789913E-14 | -0.32998984E-16 |
47 | 6 | 0.26247599E-05 | 0.15902949E-08 | 0.31989528E-02 | -0.26835497E-04 |
48 | 5 | -0.17282397E-03 | 0.93714128E-06 | -0.22424071 | 0.19607060E-02 |
49 | 4 | 0.38696203E-02 | 0.42548205E-04 | 4.8381400 | -0.45347597E-01 |
50 | 3 | -0.33643188E-01 | 0.33758390E-03 | -38.069955 | 0.39919029 |
51 | 2 | 0.11898200 | 0.56044665E-03 | 116.57840 | -1.4192028 |
52 | 1 | -0.17142224 | 0.17027190E-03 | -143.96290 | 2.0499538 |
53 | 0 | 0.83499932E-01 | 0.41268798E-05 | 60.838472 | |
54 | 7 | -0.51571905E-08 | -0.97500959E-14 | 0.15789911E-14 | -0.32998980E-16 |
55 | 6 | 0.26247599E-05 | 0.15902949E-08 | 0.31989528E-02 | -0.26835497E-04 |
56 | 5 | -0.17282397E-03 | 0.93714128E-06 | -0.22424071 | 0.19607060E-02 |
57 | 4 | 0.38696203E-02 | 0.42548205E-04 | 4.8381400 | -0.45347597E-01 |
58 | 3 | -0.33643188E-01 | 0.33758390E-03 | -38.069955 | 0.39919029 |
59 | 2 | 0.11898200 | 0.56044665E-03 | 116.57840 | -1.4192028 |
60 | 1 | -0.17142224 | 0.17027190E-03 | -143.96290 | 2.0499538 |
61 | 0 | 0.83499932E-01 | 0.41268798E-05 | 60.838472 | |
62 | 7 | -0.51571905E-08 | -0.97500959E-14 | 0.15789915E-14 | -0.32998988E-16 |
63 | 6 | 0.26247599E-05 | 0.15902949E-08 | 0.31989528E-02 | -0.26835497E-04 |
64 | 5 | -0.17282397E-03 | 0.93714128E-06 | -0.22424071 | 0.19607060E-02 |
65 | 4 | 0.38696203E-02 | 0.42548205E-04 | 4.8381400 | -0.45347597E-01 |
66 | 3 | -0.33643188E-01 | 0.33758390E-03 | -38.069955 | 0.39919029 |
67 | 2 | 0.11898200 | 0.56044665E-03 | 116.57840 | -1.4192028 |
68 | 1 | -0.17142224 | 0.17027190E-03 | -143.96290 | 2.0499538 |
69 | 0 | 0.83499932E-01 | 0.41268798E-05 | 60.838472 | |
70 | 7 | -0.51571905E-08 | -0.97500958E-14 | 0.15789913E-14 | -0.32998984E-16 |
71 | 6 | 0.26247599E-05 | 0.15902949E-08 | 0.31989528E-02 | -0.26835497E-04 |
72 | 5 | -0.17282397E-03 | 0.93714128E-06 | -0.22424071 | 0.19607060E-02 |
73 | 4 | 0.38696203E-02 | 0.42548205E-04 | 4.8381400 | -0.45347597E-01 |
74 | 3 | -0.33643188E-01 | 0.33758390E-03 | -38.069955 | 0.39919029 |
75 | 2 | 0.11898200 | 0.56044665E-03 | 116.57840 | -1.4192028 |
76 | 1 | -0.17142224 | 0.17027190E-03 | -143.96290 | 2.0499538 |
77 | 0 | 0.83499932E-01 | 0.41268798E-05 | 60.838472 | |
78 | 7 | -0.51571905E-08 | -0.97500957E-14 | 0.15789917E-14 | -0.32998991E-16 |
79 | 6 | 0.26247599E-05 | 0.15902949E-08 | 0.31989528E-02 | -0.26835497E-04 |
80 | 5 | -0.17282397E-03 | 0.93714128E-06 | -0.22424071 | 0.19607060E-02 |
81 | 4 | 0.38696203E-02 | 0.42548205E-04 | 4.8381400 | -0.45347597E-01 |
82 | 3 | -0.33643188E-01 | 0.33758390E-03 | -38.069955 | 0.39919029 |
83 | 2 | 0.11898200 | 0.56044665E-03 | 116.57840 | -1.4192028 |
84 | 1 | -0.17142224 | 0.17027190E-03 | -143.96290 | 2.0499538 |
85 | 0 | 0.83499932E-01 | 0.41268798E-05 | 60.838472 | |
86 | 7 | -0.51571905E-08 | -0.97500959E-14 | 0.15789915E-14 | -0.32998988E-16 |
87 | 6 | 0.26247599E-05 | 0.15902949E-08 | 0.31989528E-02 | -0.26835497E-04 |
88 | 5 | -0.17282397E-03 | 0.93714128E-06 | -0.22424071 | 0.19607060E-02 |
89 | 4 | 0.38696203E-02 | 0.42548205E-04 | 4.8381400 | -0.45347597E-01 |
90 | 3 | -0.33643188E-01 | 0.33758390E-03 | -38.069955 | 0.39919029 |
91 | 2 | 0.11898200 | 0.56044665E-03 | 116.57840 | -1.4192028 |
92 | 1 | -0.17142224 | 0.17027190E-03 | -143.96290 | 2.0499538 |
93 | 0 | 0.83499932E-01 | 0.41268798E-05 | 60.838472 | |
94 | 7 | -0.51571905E-08 | -0.97500958E-14 | 0.15789913E-14 | -0.32998984E-16 |
95 | 6 | 0.26247599E-05 | 0.15902949E-08 | 0.31989528E-02 | -0.26835497E-04 |
96 | 5 | -0.17282397E-03 | 0.93714128E-06 | -0.22424071 | 0.19607060E-02 |
97 | 4 | 0.38696203E-02 | 0.42548205E-04 | 4.8381400 | -0.45347597E-01 |
98 | 3 | -0.33643188E-01 | 0.33758390E-03 | -38.069955 | 0.39919029 |
99 | 2 | 0.11898200 | 0.56044665E-03 | 116.57840 | -1.4192028 |
100 | 1 | -0.17142224 | 0.17027190E-03 | -143.96290 | 2.0499538 |
101 | 0 | 0.83499932E-01 | 0.41268798E-05 | 60.838472 | |
102 | 7 | -0.19967951E-08 | -0.58252365E-15 | 0.72897552E-14 | -0.10630581E-15 |
103 | 6 | 0.59274927E-05 | 0.40433693E-08 | 0.31889525E-02 | -0.26751606E-04 |
104 | 5 | -0.42514865E-03 | 0.23948505E-05 | -0.22367243 | 0.19556901E-02 |
105 | 4 | 0.97725356E-02 | 0.10900143E-03 | 4.8286774 | -0.45256634E-01 |
106 | 3 | -0.85796444E-01 | 0.86675557E-03 | -38.016512 | 0.39859954 |
107 | 2 | 0.30461848 | 0.14417950E-02 | 116.47440 | -1.4178116 |
108 | 1 | -0.43965446 | 0.43929230E-03 | -143.90169 | 2.0489476 |
109 | 0 | 0.21434897 | 0.10616597E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.36_SHGC_0.4 | 29 | 1 | VerySmooth | 2.045 | 0.394 | 0.315 | 0.401 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 3.65598E-002 | 0.31435 | 0.48154 | 0.48154 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11562 | 1.00000 | No |
Calculation Method | Value {days} | Allowable Number Figures in Shadow Overlap {} | Polygon Clipping Algorithm | Sky Diffuse Modeling Algorithm | External Shading Calculation Method | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | AverageOverDaysInFrequency | 30 | 15000 | SutherlandHodgman | SimpleSkyDiffuseModeling | InternalCalculation | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | GAS TANK1 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
2 | WaterHeater:Mixed | GAS TANK2 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
3 | WaterHeater:Mixed | GAS TANK3 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
4 | WaterHeater:Mixed | GAS TANK4 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
5 | WaterHeater:Mixed | GAS TANK5 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
6 | WaterHeater:Mixed | GAS TANK6 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
7 | WaterHeater:Mixed | GAS TANK7 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | LGSTORE1_WALL_2 | 0 | 118.41 | 56.08 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 4 | No | No |
2 | LGSTORE1_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 4 | No | No |
3 | LGSTORE1_WALL_3_DOOR_1 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 0 | No | No |
4 | LGSTORE1_WALL_3_DOOR_2 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 0 | No | No |
5 | LGSTORE1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 0 | No | No |
6 | LGSTORE1_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 4 | No | No |
7 | LGSTORE1_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 1 | No | No |
8 | LGSTORE1_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 1 | No | No |
9 | LGSTORE1_WALL_1_WINDOW_3 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 1 | No | No |
10 | LGSTORE1_WALL_1_WINDOW_4 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 1 | No | No |
11 | LGSTORE1_WALL_1_DOOR_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 1 | No | No |
12 | LGSTORE1_WALL_1_DOOR_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 1 | No | No |
13 | LGSTORE1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 0 | No | No |
14 | LGSTORE1_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 0 | No | No |
15 | LGSTORE1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 0 | No | No |
16 | SMSTORE1_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
17 | SMSTORE1_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
18 | SMSTORE1_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
19 | SMSTORE1_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
20 | SMSTORE1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
21 | SMSTORE1_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
22 | SMSTORE1_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
23 | SMSTORE1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
24 | SMSTORE1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
25 | SMSTORE1_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
26 | SMSTORE1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
27 | SMSTORE2_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
28 | SMSTORE2_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
29 | SMSTORE2_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
30 | SMSTORE2_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
31 | SMSTORE2_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
32 | SMSTORE2_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
33 | SMSTORE2_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
34 | SMSTORE2_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
35 | SMSTORE2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
36 | SMSTORE2_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
37 | SMSTORE2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
38 | SMSTORE3_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
39 | SMSTORE3_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
40 | SMSTORE3_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
41 | SMSTORE3_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
42 | SMSTORE3_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
43 | SMSTORE3_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
44 | SMSTORE3_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
45 | SMSTORE3_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
46 | SMSTORE3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
47 | SMSTORE3_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
48 | SMSTORE3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
49 | SMSTORE4_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
50 | SMSTORE4_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
51 | SMSTORE4_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
52 | SMSTORE4_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
53 | SMSTORE4_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
54 | SMSTORE4_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 3 | No | No |
55 | SMSTORE4_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
56 | SMSTORE4_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
57 | SMSTORE4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
58 | SMSTORE4_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
59 | SMSTORE4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
60 | LGSTORE2_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
61 | LGSTORE2_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 4 | No | No |
62 | LGSTORE2_WALL_3_DOOR_1 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
63 | LGSTORE2_WALL_3_DOOR_2 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
64 | LGSTORE2_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
65 | LGSTORE2_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 4 | No | No |
66 | LGSTORE2_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
67 | LGSTORE2_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
68 | LGSTORE2_WALL_1_WINDOW_3 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
69 | LGSTORE2_WALL_1_WINDOW_4 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
70 | LGSTORE2_WALL_1_DOOR_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
71 | LGSTORE2_WALL_1_DOOR_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
72 | LGSTORE2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
73 | LGSTORE2_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
74 | LGSTORE2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
75 | SMSTORE5_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
76 | SMSTORE5_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
77 | SMSTORE5_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
78 | SMSTORE5_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
79 | SMSTORE5_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
80 | SMSTORE5_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
81 | SMSTORE5_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
82 | SMSTORE5_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
83 | SMSTORE5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
84 | SMSTORE5_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
85 | SMSTORE5_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
86 | SMSTORE6_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
87 | SMSTORE6_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
88 | SMSTORE6_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
89 | SMSTORE6_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
90 | SMSTORE6_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
91 | SMSTORE6_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
92 | SMSTORE6_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
93 | SMSTORE6_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
94 | SMSTORE6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
95 | SMSTORE6_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
96 | SMSTORE6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
97 | SMSTORE7_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
98 | SMSTORE7_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
99 | SMSTORE7_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
100 | SMSTORE7_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
101 | SMSTORE7_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
102 | SMSTORE7_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 3 | No | No |
103 | SMSTORE7_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
104 | SMSTORE7_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
105 | SMSTORE7_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
106 | SMSTORE7_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
107 | SMSTORE7_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
108 | SMSTORE8_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 4 | No | No |
109 | SMSTORE8_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 1 | No | No |
110 | SMSTORE8_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 1 | No | No |
111 | SMSTORE8_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 1 | No | No |
112 | SMSTORE8_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
113 | SMSTORE8_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 3 | No | No |
114 | SMSTORE8_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
115 | SMSTORE8_WALL_4 | 0 | 118.41 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 3 | No | No |
116 | SMSTORE8_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
117 | SMSTORE8_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
118 | SMSTORE8_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | LGSTORE1_INFILTRATION | TYPE1_INFIL_SCH | LGSTORE1 | 348.39 | 30.0 | 0.159 | 4.569E-004 | 2.517E-004 | 0.317 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | LGSTORE1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | LGSTORE1 | 348.39 | 30.0 | 0.241 | 6.922E-004 | 3.813E-004 | 0.481 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | SMSTORE1_INFILTRATION | TYPE1_INFIL_SCH | SMSTORE1 | 174.19 | 15.0 | 4.561E-002 | 2.619E-004 | 1.775E-004 | 0.182 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | SMSTORE1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE1 | 174.19 | 15.0 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
5 | SMSTORE2_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE2 | 174.19 | 15.0 | 4.561E-002 | 2.618E-004 | 1.775E-004 | 0.182 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | SMSTORE2_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE2 | 174.19 | 15.0 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
7 | SMSTORE3_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE3 | 174.19 | 15.0 | 4.561E-002 | 2.618E-004 | 1.775E-004 | 0.182 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | SMSTORE3_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE3 | 174.19 | 15.0 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | SMSTORE4_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE4 | 174.19 | 15.0 | 4.561E-002 | 2.618E-004 | 1.775E-004 | 0.182 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | SMSTORE4_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE4 | 174.19 | 15.0 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
11 | LGSTORE2_INFILTRATION | TYPE3_INFIL_SCH | LGSTORE2 | 348.39 | 30.0 | 9.122E-002 | 2.618E-004 | 1.775E-004 | 0.182 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | LGSTORE2_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | LGSTORE2 | 348.39 | 30.0 | 0.241 | 6.922E-004 | 4.692E-004 | 0.481 | 1.000 | 0.000 | 0.000 | 0.000 |
13 | SMSTORE5_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE5 | 174.19 | 15.0 | 4.561E-002 | 2.618E-004 | 1.775E-004 | 0.182 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | SMSTORE5_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE5 | 174.19 | 15.0 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
15 | SMSTORE6_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE6 | 174.19 | 15.0 | 4.561E-002 | 2.618E-004 | 1.775E-004 | 0.182 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | SMSTORE6_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE6 | 174.19 | 15.0 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
17 | SMSTORE7_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE7 | 174.19 | 15.0 | 4.561E-002 | 2.618E-004 | 1.775E-004 | 0.182 | 0.000 | 0.000 | 0.224 | 0.000 |
18 | SMSTORE7_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE7 | 174.19 | 15.0 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
19 | SMSTORE8_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE8 | 174.19 | 15.0 | 0.113 | 6.514E-004 | 3.022E-004 | 0.453 | 0.000 | 0.000 | 0.224 | 0.000 |
20 | SMSTORE8_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE8 | 174.19 | 15.0 | 0.135 | 7.722E-004 | 3.583E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | LGSTORE1 | Mixing/Well-Stirred |
2 | SMSTORE1 | Mixing/Well-Stirred |
3 | SMSTORE2 | Mixing/Well-Stirred |
4 | SMSTORE3 | Mixing/Well-Stirred |
5 | SMSTORE4 | Mixing/Well-Stirred |
6 | LGSTORE2 | Mixing/Well-Stirred |
7 | SMSTORE5 | Mixing/Well-Stirred |
8 | SMSTORE6 | Mixing/Well-Stirred |
9 | SMSTORE7 | Mixing/Well-Stirred |
10 | SMSTORE8 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone LGSTORE1 | 1.2000 |
3 | Zone SMSTORE1 | 1.2000 |
4 | Zone SMSTORE2 | 1.2000 |
5 | Zone SMSTORE3 | 1.2000 |
6 | Zone SMSTORE4 | 1.2000 |
7 | Zone LGSTORE2 | 1.2000 |
8 | Zone SMSTORE5 | 1.2000 |
9 | Zone SMSTORE6 | 1.2000 |
10 | Zone SMSTORE7 | 1.2000 |
11 | Zone SMSTORE8 | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone LGSTORE1 | 1.2000 |
3 | Zone SMSTORE1 | 1.2000 |
4 | Zone SMSTORE2 | 1.2000 |
5 | Zone SMSTORE3 | 1.2000 |
6 | Zone SMSTORE4 | 1.2000 |
7 | Zone LGSTORE2 | 1.2000 |
8 | Zone SMSTORE5 | 1.2000 |
9 | Zone SMSTORE6 | 1.2000 |
10 | Zone SMSTORE7 | 1.2000 |
11 | Zone SMSTORE8 | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | LGSTORE1 | Cooling | 18595.35086 | 22314.42104 | 1.43093 | 1.71711 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 31.20000 | 1.53444E-002 | 348.38640 | 29.99610 | 0.41145 | 0.00000 |
2 | LGSTORE1 | Heating | 30553.68245 | 36664.41894 | 1.38071 | 1.65685 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -26.20000 | 3.61342E-004 | 348.38640 | 29.99610 | 0.41145 | 0.00000 |
3 | SMSTORE1 | Cooling | 10508.39106 | 12610.06927 | 0.78372 | 0.94047 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 27.17200 | 1.53444E-002 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
4 | SMSTORE1 | Heating | 15134.55493 | 18161.46591 | 0.68392 | 0.82071 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -26.20000 | 3.61342E-004 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
5 | SMSTORE2 | Cooling | 10631.42495 | 12757.70994 | 0.79315 | 0.95178 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 25.37000 | 1.53444E-002 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
6 | SMSTORE2 | Heating | 15293.03679 | 18351.64415 | 0.69108 | 0.82930 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -26.20000 | 3.61342E-004 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
7 | SMSTORE3 | Cooling | 10567.64667 | 12681.17601 | 0.78823 | 0.94588 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 25.37000 | 1.53444E-002 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
8 | SMSTORE3 | Heating | 15353.91124 | 18424.69349 | 0.69384 | 0.83260 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -26.20000 | 3.61342E-004 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
9 | SMSTORE4 | Cooling | 10608.70435 | 12730.44522 | 0.79140 | 0.94968 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 25.37000 | 1.53444E-002 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
10 | SMSTORE4 | Heating | 15488.49022 | 18586.18827 | 0.69992 | 0.83990 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -26.20000 | 3.61342E-004 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
11 | LGSTORE2 | Cooling | 18627.41339 | 22352.89607 | 1.38380 | 1.66056 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 27.17200 | 1.53444E-002 | 348.38640 | 29.99610 | 0.41145 | 0.00000 |
12 | LGSTORE2 | Heating | 29399.47895 | 35279.37474 | 1.32857 | 1.59429 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -26.20000 | 3.61342E-004 | 348.38640 | 29.99610 | 0.41145 | 0.00000 |
13 | SMSTORE5 | Cooling | 10030.98847 | 12037.18617 | 0.74712 | 0.89655 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 27.17200 | 1.53444E-002 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
14 | SMSTORE5 | Heating | 15820.60100 | 18984.72120 | 0.71493 | 0.85791 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -26.20000 | 3.61342E-004 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
15 | SMSTORE6 | Cooling | 9936.95149 | 11924.34178 | 0.73990 | 0.88788 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 27.17200 | 1.53444E-002 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
16 | SMSTORE6 | Heating | 15805.22504 | 18966.27004 | 0.71423 | 0.85708 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -26.20000 | 3.61342E-004 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
17 | SMSTORE7 | Cooling | 9775.87760 | 11731.05312 | 0.72753 | 0.87303 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 27.17200 | 1.53444E-002 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
18 | SMSTORE7 | Heating | 15997.23141 | 19196.67770 | 0.72291 | 0.86749 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -26.20000 | 3.61342E-004 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
19 | SMSTORE8 | Cooling | 9861.04615 | 11833.25538 | 0.73407 | 0.88088 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 27.17200 | 1.53444E-002 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
20 | SMSTORE8 | Heating | 18394.31982 | 22073.18379 | 0.83121 | 0.99746 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -26.20000 | 3.61342E-004 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC_1:1 | Cooling | Sensible | 25442.75 | 1.71711 | 1.71711 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-AC_1:1 | Heating | Sensible | 58594.59 | 1.65685 | 1.65685 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
3 | PSZ-AC_2:2 | Cooling | Sensible | 13614.54 | 0.94047 | 0.94047 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-AC_2:2 | Heating | Sensible | 29129.01 | 0.82071 | 0.82071 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
5 | PSZ-AC_3:3 | Cooling | Sensible | 13558.30 | 0.95178 | 0.95178 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
6 | PSZ-AC_3:3 | Heating | Sensible | 29316.42 | 0.82930 | 0.82930 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
7 | PSZ-AC_4:4 | Cooling | Sensible | 13601.38 | 0.94588 | 0.94588 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
8 | PSZ-AC_4:4 | Heating | Sensible | 29388.41 | 0.83260 | 0.83260 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
9 | PSZ-AC_5:5 | Cooling | Sensible | 13524.39 | 0.94968 | 0.94968 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
10 | PSZ-AC_5:5 | Heating | Sensible | 29547.55 | 0.83990 | 0.83990 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
11 | PSZ-AC_6:6 | Cooling | Sensible | 24814.16 | 1.67579 | 1.67579 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
12 | PSZ-AC_6:6 | Heating | Sensible | 57229.84 | 1.59429 | 1.59429 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
13 | PSZ-AC_7:7 | Cooling | Sensible | 12764.74 | 0.89655 | 0.89655 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
14 | PSZ-AC_7:7 | Heating | Sensible | 29940.29 | 0.85791 | 0.85791 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
15 | PSZ-AC_8:8 | Cooling | Sensible | 12667.27 | 0.88788 | 0.88788 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
16 | PSZ-AC_8:8 | Heating | Sensible | 29922.11 | 0.85708 | 0.85708 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
17 | PSZ-AC_9:9 | Cooling | Sensible | 12551.95 | 0.87303 | 0.87303 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
18 | PSZ-AC_9:9 | Heating | Sensible | 30149.16 | 0.86749 | 0.86749 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
19 | PSZ-AC_10:10 | Cooling | Sensible | 12725.22 | 0.88635 | 0.88635 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
20 | PSZ-AC_10:10 | Heating | Sensible | 32983.67 | 0.99746 | 0.99746 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:Uncontrolled | LGSTORE1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.71711 |
2 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.94047 |
3 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE2 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.95178 |
4 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.94588 |
5 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE4 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.94968 |
6 | AirTerminal:SingleDuct:Uncontrolled | LGSTORE2 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.66056 |
7 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE5 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.89655 |
8 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.88788 |
9 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE7 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.87303 |
10 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE8 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.99746 |
11 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.71711 |
12 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.71711 |
13 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.71711 |
14 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.71711 |
15 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.71711 |
16 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Main Design Air Flow Rate [m3/s] | 1.71711 |
17 | AirLoopHVAC | PSZ-AC_1:1 | User Heating Air Flow Ratio [] | 1.00000 |
18 | AirLoopHVAC | PSZ-AC_1:1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
19 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.94047 |
20 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.94047 |
21 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.94047 |
22 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.94047 |
23 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.94047 |
24 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Main Design Air Flow Rate [m3/s] | 0.94047 |
25 | AirLoopHVAC | PSZ-AC_2:2 | User Heating Air Flow Ratio [] | 1.00000 |
26 | AirLoopHVAC | PSZ-AC_2:2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
27 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.95178 |
28 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.95178 |
29 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.95178 |
30 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.95178 |
31 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.95178 |
32 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Main Design Air Flow Rate [m3/s] | 0.95178 |
33 | AirLoopHVAC | PSZ-AC_3:3 | User Heating Air Flow Ratio [] | 1.00000 |
34 | AirLoopHVAC | PSZ-AC_3:3 | Calculated Heating Air Flow Ratio [] | 1.00000 |
35 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.94588 |
36 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.94588 |
37 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.94588 |
38 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.94588 |
39 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.94588 |
40 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Main Design Air Flow Rate [m3/s] | 0.94588 |
41 | AirLoopHVAC | PSZ-AC_4:4 | User Heating Air Flow Ratio [] | 1.00000 |
42 | AirLoopHVAC | PSZ-AC_4:4 | Calculated Heating Air Flow Ratio [] | 1.00000 |
43 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.94968 |
44 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.94968 |
45 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.94968 |
46 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.94968 |
47 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.94968 |
48 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Main Design Air Flow Rate [m3/s] | 0.94968 |
49 | AirLoopHVAC | PSZ-AC_5:5 | User Heating Air Flow Ratio [] | 1.00000 |
50 | AirLoopHVAC | PSZ-AC_5:5 | Calculated Heating Air Flow Ratio [] | 1.00000 |
51 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.66056 |
52 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.66056 |
53 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.66056 |
54 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.66056 |
55 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.67579 |
56 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Main Design Air Flow Rate [m3/s] | 1.67579 |
57 | AirLoopHVAC | PSZ-AC_6:6 | User Heating Air Flow Ratio [] | 1.00000 |
58 | AirLoopHVAC | PSZ-AC_6:6 | Calculated Heating Air Flow Ratio [] | 0.99092 |
59 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.89655 |
60 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.89655 |
61 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.89655 |
62 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.89655 |
63 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.89655 |
64 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Main Design Air Flow Rate [m3/s] | 0.89655 |
65 | AirLoopHVAC | PSZ-AC_7:7 | User Heating Air Flow Ratio [] | 1.00000 |
66 | AirLoopHVAC | PSZ-AC_7:7 | Calculated Heating Air Flow Ratio [] | 1.00000 |
67 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.88788 |
68 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.88788 |
69 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.88788 |
70 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.88788 |
71 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.88788 |
72 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Main Design Air Flow Rate [m3/s] | 0.88788 |
73 | AirLoopHVAC | PSZ-AC_8:8 | User Heating Air Flow Ratio [] | 1.00000 |
74 | AirLoopHVAC | PSZ-AC_8:8 | Calculated Heating Air Flow Ratio [] | 1.00000 |
75 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.87303 |
76 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.87303 |
77 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.87303 |
78 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.87303 |
79 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.87303 |
80 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Main Design Air Flow Rate [m3/s] | 0.87303 |
81 | AirLoopHVAC | PSZ-AC_9:9 | User Heating Air Flow Ratio [] | 1.00000 |
82 | AirLoopHVAC | PSZ-AC_9:9 | Calculated Heating Air Flow Ratio [] | 1.00000 |
83 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.99746 |
84 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.99746 |
85 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.99746 |
86 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.99746 |
87 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.99746 |
88 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Main Design Air Flow Rate [m3/s] | 0.99746 |
89 | AirLoopHVAC | PSZ-AC_10:10 | User Heating Air Flow Ratio [] | 1.00000 |
90 | AirLoopHVAC | PSZ-AC_10:10 | Calculated Heating Air Flow Ratio [] | 1.00000 |
91 | AirLoopHVAC | PSZ-AC_1:1 | Design Supply Air Flow Rate [m3/s] | 1.71711 |
92 | AirLoopHVAC | PSZ-AC_2:2 | Design Supply Air Flow Rate [m3/s] | 0.94047 |
93 | AirLoopHVAC | PSZ-AC_3:3 | Design Supply Air Flow Rate [m3/s] | 0.95178 |
94 | AirLoopHVAC | PSZ-AC_4:4 | Design Supply Air Flow Rate [m3/s] | 0.94588 |
95 | AirLoopHVAC | PSZ-AC_5:5 | Design Supply Air Flow Rate [m3/s] | 0.94968 |
96 | AirLoopHVAC | PSZ-AC_6:6 | Design Supply Air Flow Rate [m3/s] | 1.67579 |
97 | AirLoopHVAC | PSZ-AC_7:7 | Design Supply Air Flow Rate [m3/s] | 0.89655 |
98 | AirLoopHVAC | PSZ-AC_8:8 | Design Supply Air Flow Rate [m3/s] | 0.88788 |
99 | AirLoopHVAC | PSZ-AC_9:9 | Design Supply Air Flow Rate [m3/s] | 0.87303 |
100 | AirLoopHVAC | PSZ-AC_10:10 | Design Supply Air Flow Rate [m3/s] | 0.99746 |
101 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.71711 |
102 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41145 |
103 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.71711 |
104 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.71711 |
105 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.71711 |
106 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.13329 |
107 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.71711 |
108 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.85856 |
109 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.14474 |
110 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 37437.36831 |
111 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 39525.84000 |
112 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 19762.92000 |
113 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 19762.92000 |
114 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.69539 |
115 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.69539 |
116 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.69539 |
117 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.69539 |
118 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 39525.84000 |
119 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 59908.60472 |
120 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
121 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
122 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.71711 |
123 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1837.39176 |
124 | Coil:Heating:Fuel | PSZ-AC_1:1_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 59908.60472 |
125 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.94047 |
126 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20573 |
127 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.94047 |
128 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.94047 |
129 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.94047 |
130 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.62071 |
131 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.94047 |
132 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.47024 |
133 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.62698 |
134 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 20125.88414 |
135 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 21275.44000 |
136 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 10637.72000 |
137 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 10637.72000 |
138 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.70003 |
139 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.70003 |
140 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.70003 |
141 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.70003 |
142 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 21275.44000 |
143 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 31740.56551 |
144 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
145 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
146 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.94047 |
147 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1041.24483 |
148 | Coil:Heating:Fuel | PSZ-AC_2:2_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 31740.56551 |
149 | Controller:OutdoorAir | PSZ-AC_3:3_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.95178 |
150 | Controller:OutdoorAir | PSZ-AC_3:3_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20573 |
151 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.95178 |
152 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.95178 |
153 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.95178 |
154 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.62817 |
155 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.95178 |
156 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.47589 |
157 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.63452 |
158 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 20396.99694 |
159 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 21560.01000 |
160 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 10780.00500 |
161 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 10780.00500 |
162 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.69967 |
163 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.69967 |
164 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.69967 |
165 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.69967 |
166 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 21560.01000 |
167 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 31987.26900 |
168 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
169 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
170 | Fan:SystemModel | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.95178 |
171 | Fan:SystemModel | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1053.77066 |
172 | Coil:Heating:Fuel | PSZ-AC_3:3_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 31987.26900 |
173 | Controller:OutdoorAir | PSZ-AC_4:4_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.94588 |
174 | Controller:OutdoorAir | PSZ-AC_4:4_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20573 |
175 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.94588 |
176 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.94588 |
177 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.94588 |
178 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.62428 |
179 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.94588 |
180 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.47294 |
181 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.63059 |
182 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 20248.35568 |
183 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 21404.43000 |
184 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 10702.21500 |
185 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 10702.21500 |
186 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.69995 |
187 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.69994 |
188 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.69994 |
189 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.69994 |
190 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 21404.43000 |
191 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 31858.54704 |
192 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
193 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
194 | Fan:SystemModel | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.94588 |
195 | Fan:SystemModel | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1047.23530 |
196 | Coil:Heating:Fuel | PSZ-AC_4:4_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 31858.54704 |
197 | Controller:OutdoorAir | PSZ-AC_5:5_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.94968 |
198 | Controller:OutdoorAir | PSZ-AC_5:5_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20573 |
199 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.94968 |
200 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.94968 |
201 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.94968 |
202 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.62679 |
203 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.94968 |
204 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.47484 |
205 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.63312 |
206 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 20369.61840 |
207 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 21529.80000 |
208 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 10764.90000 |
209 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 10764.90000 |
210 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.69945 |
211 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.69945 |
212 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.69945 |
213 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.69945 |
214 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 21529.80000 |
215 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 31941.47884 |
216 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
217 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
218 | Fan:SystemModel | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.94968 |
219 | Fan:SystemModel | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1051.44614 |
220 | Coil:Heating:Fuel | PSZ-AC_5:5_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 31941.47884 |
221 | Controller:OutdoorAir | PSZ-AC_6:6_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.67579 |
222 | Controller:OutdoorAir | PSZ-AC_6:6_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41145 |
223 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.67579 |
224 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.67579 |
225 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.67579 |
226 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.10602 |
227 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.67579 |
228 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.83790 |
229 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.11719 |
230 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 36793.96875 |
231 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 38828.11000 |
232 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 19414.05500 |
233 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 19414.05500 |
234 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.69367 |
235 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.69367 |
236 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.69367 |
237 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.69367 |
238 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 38828.11000 |
239 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 58675.12224 |
240 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
241 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
242 | Fan:SystemModel | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.67579 |
243 | Fan:SystemModel | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1793.17006 |
244 | Coil:Heating:Fuel | PSZ-AC_6:6_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 58675.12224 |
245 | Controller:OutdoorAir | PSZ-AC_7:7_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.89655 |
246 | Controller:OutdoorAir | PSZ-AC_7:7_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20573 |
247 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.89655 |
248 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.89655 |
249 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.89655 |
250 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.59172 |
251 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.89655 |
252 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.44828 |
253 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.59770 |
254 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 19624.28858 |
255 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 20713.52000 |
256 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 10356.76000 |
257 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 10356.76000 |
258 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.69442 |
259 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.69442 |
260 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.69442 |
261 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.69442 |
262 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 20713.52000 |
263 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 30782.84179 |
264 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
265 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
266 | Fan:SystemModel | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.89655 |
267 | Fan:SystemModel | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 992.62159 |
268 | Coil:Heating:Fuel | PSZ-AC_7:7_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 30782.84179 |
269 | Controller:OutdoorAir | PSZ-AC_8:8_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.88788 |
270 | Controller:OutdoorAir | PSZ-AC_8:8_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20573 |
271 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.88788 |
272 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.88788 |
273 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.88788 |
274 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.58600 |
275 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.88788 |
276 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.44394 |
277 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.59192 |
278 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 19487.75167 |
279 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 20565.68000 |
280 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 10282.84000 |
281 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 10282.84000 |
282 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.69375 |
283 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.69375 |
284 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.69375 |
285 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.69375 |
286 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 20565.68000 |
287 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 30593.81474 |
288 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
289 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
290 | Fan:SystemModel | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.88788 |
291 | Fan:SystemModel | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 983.02440 |
292 | Coil:Heating:Fuel | PSZ-AC_8:8_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 30593.81474 |
293 | Controller:OutdoorAir | PSZ-AC_9:9_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.87303 |
294 | Controller:OutdoorAir | PSZ-AC_9:9_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20573 |
295 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.87303 |
296 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.87303 |
297 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.87303 |
298 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.57620 |
299 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.87303 |
300 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.43652 |
301 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.58202 |
302 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 19224.72349 |
303 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 20283.67000 |
304 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 10141.83500 |
305 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 10141.83500 |
306 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.69295 |
307 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.69295 |
308 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.69295 |
309 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.69295 |
310 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 20283.67000 |
311 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 30269.98081 |
312 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
313 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
314 | Fan:SystemModel | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.87303 |
315 | Fan:SystemModel | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 966.58302 |
316 | Coil:Heating:Fuel | PSZ-AC_9:9_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 30269.98081 |
317 | Controller:OutdoorAir | PSZ-AC_10:10_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.99746 |
318 | Controller:OutdoorAir | PSZ-AC_10:10_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20573 |
319 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.99746 |
320 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.99746 |
321 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.99746 |
322 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.65832 |
323 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.99746 |
324 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.49873 |
325 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.66497 |
326 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 21682.53881 |
327 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 22894.64000 |
328 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 11447.32000 |
329 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 11447.32000 |
330 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.69615 |
331 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.69615 |
332 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.69615 |
333 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.69615 |
334 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 22894.64000 |
335 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 32983.66625 |
336 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
337 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
338 | Fan:SystemModel | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.99746 |
339 | Fan:SystemModel | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1104.34140 |
340 | Coil:Heating:Fuel | PSZ-AC_10:10_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 32983.66625 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | 38173.1 | 11.81 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | 20534.8 | 33.67 | |||
3 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | 20810.4 | 45.01 | |||
4 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | 20659.5 | 57.11 | |||
5 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | 20781.9 | 68.57 | |||
6 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | 37507.8 | 49.95 | |||
7 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | 20007.2 | 105.41 | |||
8 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | 19866.2 | 118.02 | |||
9 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | 19595.8 | 131.53 | |||
10 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | 22108.9 | 128.16 |
Zone Name | # Surfaces | |
1 | LGSTORE1 | 15 |
2 | SMSTORE1 | 11 |
3 | SMSTORE2 | 11 |
4 | SMSTORE3 | 11 |
5 | SMSTORE4 | 11 |
6 | LGSTORE2 | 15 |
7 | SMSTORE5 | 11 |
8 | SMSTORE6 | 11 |
9 | SMSTORE7 | 11 |
10 | SMSTORE8 | 11 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | LGSTORE1_WALL_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | LGSTORE1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 71.15 | 78.94 | 71.15 | 0.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | LGSTORE1_WALL_3_DOOR_1 | Door | LGSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
4 | LGSTORE1_WALL_3_DOOR_2 | Door | LGSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
5 | LGSTORE1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
6 | LGSTORE1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 58.20 | 78.94 | 58.20 | 180.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
7 | LGSTORE1_WALL_1_WINDOW_1 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
8 | LGSTORE1_WALL_1_WINDOW_2 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
9 | LGSTORE1_WALL_1_WINDOW_3 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
10 | LGSTORE1_WALL_1_WINDOW_4 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
11 | LGSTORE1_WALL_1_DOOR_1 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
12 | LGSTORE1_WALL_1_DOOR_2 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
13 | LGSTORE1_FLOOR | Floor | CTF - ConductionTransferFunction | LGSTORE1_FLOOR_FFACTOR | 0.146 | 0.141 | 348.39 | 348.39 | 348.39 | 270.00 | 180.00 | 22.86 | 15.24 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | LGSTORE1_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 348.39 | 348.39 | 348.39 | 270.00 | 0.00 | 22.86 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
15 | LGSTORE1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 696.77 | 696.77 | 696.77 | 0.00 | 90.00 | 696.77 | 1.00 | 0.00 | LGSTORE1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
16 | SMSTORE1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 29.10 | 39.47 | 29.10 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
17 | SMSTORE1_WALL_1_WINDOW_1 | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
18 | SMSTORE1_WALL_1_WINDOW_2 | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
19 | SMSTORE1_WALL_1_DOOR | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
20 | SMSTORE1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | SMSTORE1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 35.57 | 39.47 | 35.57 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | SMSTORE1_WALL_3_DOOR | Door | SMSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
23 | SMSTORE1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE2_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
24 | SMSTORE1_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE1_FLOOR_FFACTOR | 8.283E-002 | 8.119E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | SMSTORE1_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
26 | SMSTORE1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
27 | SMSTORE2_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 29.12 | 39.47 | 29.12 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | SMSTORE2_WALL_1_WINDOW_1 | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
29 | SMSTORE2_WALL_1_WINDOW_2 | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
30 | SMSTORE2_WALL_1_DOOR | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
31 | SMSTORE2_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
32 | SMSTORE2_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | SMSTORE2_WALL_3_DOOR | Door | SMSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
34 | SMSTORE2_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE3_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | SMSTORE2_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE2_FLOOR_FFACTOR | 8.283E-002 | 8.119E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
36 | SMSTORE2_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
37 | SMSTORE2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
38 | SMSTORE3_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 29.12 | 39.47 | 29.12 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
39 | SMSTORE3_WALL_1_WINDOW_1 | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
40 | SMSTORE3_WALL_1_WINDOW_2 | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
41 | SMSTORE3_WALL_1_DOOR | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
42 | SMSTORE3_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE2_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | SMSTORE3_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | SMSTORE3_WALL_3_DOOR | Door | SMSTORE3_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
45 | SMSTORE3_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE4_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | SMSTORE3_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE3_FLOOR_FFACTOR | 8.283E-002 | 8.119E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
47 | SMSTORE3_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
48 | SMSTORE3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
49 | SMSTORE4_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 29.12 | 39.47 | 29.12 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | SMSTORE4_WALL_1_WINDOW_1 | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
51 | SMSTORE4_WALL_1_WINDOW_2 | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
52 | SMSTORE4_WALL_1_DOOR | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | SMSTORE4_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE3_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | SMSTORE4_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | SMSTORE4_WALL_3_DOOR | Door | SMSTORE4_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | SMSTORE4_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE2_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | SMSTORE4_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE4_FLOOR_FFACTOR | 8.283E-002 | 8.119E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | SMSTORE4_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | SMSTORE4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | LGSTORE2_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE4_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | LGSTORE2_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 71.19 | 78.94 | 71.19 | 0.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
62 | LGSTORE2_WALL_3_DOOR_1 | Door | LGSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
63 | LGSTORE2_WALL_3_DOOR_2 | Door | LGSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
64 | LGSTORE2_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE5_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | LGSTORE2_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 58.24 | 78.94 | 58.24 | 180.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
66 | LGSTORE2_WALL_1_WINDOW_1 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | LGSTORE2_WALL_1_WINDOW_2 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | LGSTORE2_WALL_1_WINDOW_3 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | LGSTORE2_WALL_1_WINDOW_4 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | LGSTORE2_WALL_1_DOOR_1 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
71 | LGSTORE2_WALL_1_DOOR_2 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
72 | LGSTORE2_FLOOR | Floor | CTF - ConductionTransferFunction | LGSTORE2_FLOOR_FFACTOR | 8.283E-002 | 8.119E-002 | 348.39 | 348.39 | 348.39 | 270.00 | 180.00 | 22.86 | 15.24 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
73 | LGSTORE2_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 348.39 | 348.39 | 348.39 | 270.00 | 0.00 | 22.86 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
74 | LGSTORE2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 696.77 | 696.77 | 696.77 | 0.00 | 90.00 | 696.77 | 1.00 | 0.00 | LGSTORE2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
75 | SMSTORE5_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 29.12 | 39.47 | 29.12 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | SMSTORE5_WALL_1_WINDOW_1 | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
77 | SMSTORE5_WALL_1_WINDOW_2 | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | SMSTORE5_WALL_1_DOOR | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
79 | SMSTORE5_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE2_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | SMSTORE5_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | SMSTORE5_WALL_3_DOOR | Door | SMSTORE5_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
82 | SMSTORE5_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE6_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
83 | SMSTORE5_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE5_FLOOR_FFACTOR | 8.283E-002 | 8.119E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
84 | SMSTORE5_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
85 | SMSTORE5_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE5_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
86 | SMSTORE6_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 29.12 | 39.47 | 29.12 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | SMSTORE6_WALL_1_WINDOW_1 | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
88 | SMSTORE6_WALL_1_WINDOW_2 | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
89 | SMSTORE6_WALL_1_DOOR | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
90 | SMSTORE6_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE5_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
91 | SMSTORE6_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
92 | SMSTORE6_WALL_3_DOOR | Door | SMSTORE6_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
93 | SMSTORE6_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE7_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | SMSTORE6_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE6_FLOOR_FFACTOR | 8.283E-002 | 8.119E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
95 | SMSTORE6_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
96 | SMSTORE6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
97 | SMSTORE7_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 29.12 | 39.47 | 29.12 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | SMSTORE7_WALL_1_WINDOW_1 | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
99 | SMSTORE7_WALL_1_WINDOW_2 | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
100 | SMSTORE7_WALL_1_DOOR | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
101 | SMSTORE7_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE6_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
102 | SMSTORE7_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 35.59 | 39.47 | 35.59 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | SMSTORE7_WALL_3_DOOR | Door | SMSTORE7_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
104 | SMSTORE7_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE8_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | SMSTORE7_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE7_FLOOR_FFACTOR | 8.283E-002 | 8.119E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
106 | SMSTORE7_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
107 | SMSTORE7_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE7_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
108 | SMSTORE8_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 29.12 | 39.47 | 29.12 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | SMSTORE8_WALL_1_WINDOW_1 | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
110 | SMSTORE8_WALL_1_WINDOW_2 | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
111 | SMSTORE8_WALL_1_DOOR | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
112 | SMSTORE8_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE7_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
113 | SMSTORE8_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | SMSTORE8_WALL_3_DOOR | Door | SMSTORE8_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
115 | SMSTORE8_WALL_4 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | SMSTORE8_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE8_FLOOR_FFACTOR | 0.211 | 0.201 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | SMSTORE8_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | SMSTORE8_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE8_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1 |
2 | VETERANS DAY | Holiday | InputFile | 11/11 | 1 |
3 | CHRISTMAS | Holiday | InputFile | 12/25 | 1 |
4 | INDEPENDENCE DAY | Holiday | InputFile | 07/04 | 1 |
5 | MLK DAY | Holiday | InputFile | 01/16 | 1 |
6 | PRESIDENTS DAY | Holiday | InputFile | 02/20 | 1 |
7 | MEMORIAL DAY | Holiday | InputFile | 05/29 | 1 |
8 | LABOR DAY | Holiday | InputFile | 09/04 | 1 |
9 | COLUMBUS DAY | Holiday | InputFile | 10/09 | 1 |
10 | THANKSGIVING | Holiday | InputFile | 11/23 | 1 |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
NumberofWarmupDays | |
1 | 10 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | LGSTORE1 | RunPeriod: RUNPERIOD 1 | 4.3874680707E-002 | 0.2199721589 | Pass | Pass | 0.6026810424 | 5.9157541661 | Pass | Pass |
2 | SMSTORE1 | RunPeriod: RUNPERIOD 1 | 4.4126868187E-002 | 0.1736646834 | Pass | Pass | 0.1738950647 | 0.7424527458 | Pass | Pass |
3 | SMSTORE2 | RunPeriod: RUNPERIOD 1 | 5.0413371089E-002 | 0.2256139416 | Pass | Pass | 0.1016815874 | 0.5800529162 | Pass | Pass |
4 | SMSTORE3 | RunPeriod: RUNPERIOD 1 | 5.8523517918E-002 | 0.2426957858 | Pass | Pass | 6.9022911691E-002 | 0.2672956769 | Pass | Pass |
5 | SMSTORE4 | RunPeriod: RUNPERIOD 1 | 6.3849684595E-002 | 0.2593497762 | Pass | Pass | 6.1987983609E-002 | 0.2314517787 | Pass | Pass |
6 | LGSTORE2 | RunPeriod: RUNPERIOD 1 | 7.1898272832E-002 | 0.2829438658 | Pass | Pass | 0.1044311843 | 0.5733247077 | Pass | Pass |
7 | SMSTORE5 | RunPeriod: RUNPERIOD 1 | 7.0960597011E-002 | 0.2804096835 | Pass | Pass | 9.8919553730E-002 | 0.5968995527 | Pass | Pass |
8 | SMSTORE6 | RunPeriod: RUNPERIOD 1 | 7.1944682118E-002 | 0.2847541129 | Pass | Pass | 9.5672059318E-002 | 0.5702569216 | Pass | Pass |
9 | SMSTORE7 | RunPeriod: RUNPERIOD 1 | 7.6655437958E-002 | 0.3083119302 | Pass | Pass | 9.7482336220E-002 | 0.6179072813 | Pass | Pass |
10 | SMSTORE8 | RunPeriod: RUNPERIOD 1 | 0.1260683720 | 0.3430217775 | Pass | Pass | 0.3871241300 | 3.2123543424 | Pass | Pass |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2020-06-03 19:19:46
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | -26.20 | 0.00 | -26.20 | Wetbulb [C] | 5.70 | 310.00 |
ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 31.20 | 10.60 | 23.10 | Wetbulb [C] | 6.70 | 200.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2020-06-03 19:19:46
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_2 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE1_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 78.94 | 71.15 | 0.00 | 90.00 | N |
LGSTORE1_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 78.94 | 58.20 | 180.00 | 90.00 | S |
LGSTORE1_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 348.39 | 348.39 | 270.00 | 0.00 | |
SMSTORE1_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 29.10 | 180.00 | 90.00 | S |
SMSTORE1_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 35.57 | 0.00 | 90.00 | N |
SMSTORE1_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE2_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 29.12 | 180.00 | 90.00 | S |
SMSTORE2_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE2_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE3_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 29.12 | 180.00 | 90.00 | S |
SMSTORE3_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE3_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE4_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 29.12 | 180.00 | 90.00 | S |
SMSTORE4_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE4_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
LGSTORE2_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 78.94 | 71.19 | 0.00 | 90.00 | N |
LGSTORE2_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 78.94 | 58.24 | 180.00 | 90.00 | S |
LGSTORE2_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 348.39 | 348.39 | 270.00 | 0.00 | |
SMSTORE5_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 29.12 | 180.00 | 90.00 | S |
SMSTORE5_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE5_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE6_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 29.12 | 180.00 | 90.00 | S |
SMSTORE6_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE6_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE7_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 29.12 | 180.00 | 90.00 | S |
SMSTORE7_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE7_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE8_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 29.12 | 180.00 | 90.00 | S |
SMSTORE8_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE8_WALL_4 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE8_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
LGSTORE1_FLOOR | LGSTORE1_FLOOR_FFACTOR | 1.00 | 0.146 | 348.39 | 348.39 | 270.00 | 180.00 | ||
SMSTORE1_FLOOR | SMSTORE1_FLOOR_FFACTOR | 1.00 | 0.083 | 174.19 | 174.19 | 270.00 | 180.00 | ||
SMSTORE2_FLOOR | SMSTORE2_FLOOR_FFACTOR | 1.00 | 0.083 | 174.19 | 174.19 | 270.00 | 180.00 | ||
SMSTORE3_FLOOR | SMSTORE3_FLOOR_FFACTOR | 1.00 | 0.083 | 174.19 | 174.19 | 270.00 | 180.00 | ||
SMSTORE4_FLOOR | SMSTORE4_FLOOR_FFACTOR | 1.00 | 0.083 | 174.19 | 174.19 | 270.00 | 180.00 | ||
LGSTORE2_FLOOR | LGSTORE2_FLOOR_FFACTOR | 1.00 | 0.083 | 348.39 | 348.39 | 270.00 | 180.00 | ||
SMSTORE5_FLOOR | SMSTORE5_FLOOR_FFACTOR | 1.00 | 0.083 | 174.19 | 174.19 | 270.00 | 180.00 | ||
SMSTORE6_FLOOR | SMSTORE6_FLOOR_FFACTOR | 1.00 | 0.083 | 174.19 | 174.19 | 270.00 | 180.00 | ||
SMSTORE7_FLOOR | SMSTORE7_FLOOR_FFACTOR | 1.00 | 0.083 | 174.19 | 174.19 | 270.00 | 180.00 | ||
SMSTORE8_FLOOR | SMSTORE8_FLOOR_FFACTOR | 1.00 | 0.211 | 174.19 | 174.19 | 270.00 | 180.00 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.36_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.045 | 0.394 | 0.401 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE1_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.36_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.045 | 0.394 | 0.401 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE1_WALL_1_WINDOW_3 | NONRESWINDOW_U_0.36_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.045 | 0.394 | 0.401 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE1_WALL_1_WINDOW_4 | NONRESWINDOW_U_0.36_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.045 | 0.394 | 0.401 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE1_WALL_1_DOOR_1 | NONRESWINDOW_U_0.36_SHGC_0.4 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.045 | 0.394 | 0.401 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE1_WALL_1_DOOR_2 | NONRESWINDOW_U_0.36_SHGC_0.4 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.045 | 0.394 | 0.401 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE1_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.36_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.045 | 0.394 | 0.401 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE1_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.36_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.045 | 0.394 | 0.401 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE1_WALL_1_DOOR | NONRESWINDOW_U_0.36_SHGC_0.4 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.045 | 0.394 | 0.401 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE2_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.36_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.045 | 0.394 | 0.401 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE2_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.36_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.045 | 0.394 | 0.401 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE2_WALL_1_DOOR | NONRESWINDOW_U_0.36_SHGC_0.4 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.045 | 0.394 | 0.401 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE3_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.36_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.045 | 0.394 | 0.401 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE3_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.36_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.045 | 0.394 | 0.401 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE3_WALL_1_DOOR | NONRESWINDOW_U_0.36_SHGC_0.4 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.045 | 0.394 | 0.401 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE4_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.36_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.045 | 0.394 | 0.401 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE4_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.36_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.045 | 0.394 | 0.401 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE4_WALL_1_DOOR | NONRESWINDOW_U_0.36_SHGC_0.4 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.045 | 0.394 | 0.401 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE2_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.36_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.045 | 0.394 | 0.401 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE2_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.36_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.045 | 0.394 | 0.401 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE2_WALL_1_WINDOW_3 | NONRESWINDOW_U_0.36_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.045 | 0.394 | 0.401 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE2_WALL_1_WINDOW_4 | NONRESWINDOW_U_0.36_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.045 | 0.394 | 0.401 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE2_WALL_1_DOOR_1 | NONRESWINDOW_U_0.36_SHGC_0.4 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.045 | 0.394 | 0.401 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE2_WALL_1_DOOR_2 | NONRESWINDOW_U_0.36_SHGC_0.4 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.045 | 0.394 | 0.401 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE5_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.36_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.045 | 0.394 | 0.401 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE5_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.36_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.045 | 0.394 | 0.401 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE5_WALL_1_DOOR | NONRESWINDOW_U_0.36_SHGC_0.4 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.045 | 0.394 | 0.401 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE6_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.36_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.045 | 0.394 | 0.401 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE6_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.36_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.045 | 0.394 | 0.401 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE6_WALL_1_DOOR | NONRESWINDOW_U_0.36_SHGC_0.4 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.045 | 0.394 | 0.401 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE7_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.36_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.045 | 0.394 | 0.401 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE7_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.36_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.045 | 0.394 | 0.401 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE7_WALL_1_DOOR | NONRESWINDOW_U_0.36_SHGC_0.4 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.045 | 0.394 | 0.401 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE8_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.36_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.045 | 0.394 | 0.401 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE8_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.36_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.045 | 0.394 | 0.401 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE8_WALL_1_DOOR | NONRESWINDOW_U_0.36_SHGC_0.4 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.045 | 0.394 | 0.401 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | ||
Total or Average | 124.29 | 2.045 | 0.394 | 0.401 | ||||||||||||
North Total or Average | 0.00 | - | - | - | ||||||||||||
Non-North Total or Average | 124.29 | 2.045 | 0.394 | 0.401 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
LGSTORE1_WALL_3_DOOR_1 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.90 | LGSTORE1_WALL_3 |
LGSTORE1_WALL_3_DOOR_2 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.90 | LGSTORE1_WALL_3 |
SMSTORE1_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.90 | SMSTORE1_WALL_3 |
SMSTORE2_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE2_WALL_3 |
SMSTORE3_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE3_WALL_3 |
SMSTORE4_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE4_WALL_3 |
LGSTORE2_WALL_3_DOOR_1 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | LGSTORE2_WALL_3 |
LGSTORE2_WALL_3_DOOR_2 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | LGSTORE2_WALL_3 |
SMSTORE5_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE5_WALL_3 |
SMSTORE6_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE6_WALL_3 |
SMSTORE7_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE7_WALL_3 |
SMSTORE8_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE8_WALL_3 |
Report: Shading Summary
For: Entire Facility
Timestamp: 2020-06-03 19:19:46
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
LGSTORE1_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_DOOR_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_DOOR_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_DOOR_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_DOOR_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2020-06-03 19:19:46
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
LGSTORE1_LIGHTS | LGSTORE1 | 13.1675 | 348.39 | 4587.39 | LightsWired | TYPE1_LIGHT_SCH | 98.40 | 168.00 | 98.38 | 0.0000 | Y | 84.71 |
LGSTORE1_LIGHTS_ALLOWANCE | LGSTORE1 | 5.1990 | 348.39 | 1811.25 | LightsWired | TYPE1_LIGHT_SCH | 98.40 | 168.00 | 98.38 | 0.0000 | Y | 33.45 |
SMSTORE1_LIGHTS | SMSTORE1 | 13.1675 | 174.19 | 2293.69 | LightsWired | TYPE1_LIGHT_SCH | 98.40 | 168.00 | 98.38 | 0.0000 | Y | 42.36 |
SMSTORE1_LIGHTS_ALLOWANCE | SMSTORE1 | 6.6413 | 174.19 | 1156.88 | LightsWired | TYPE1_LIGHT_SCH | 98.40 | 168.00 | 98.38 | 0.0000 | Y | 21.36 |
SMSTORE2_LIGHTS | SMSTORE2 | 13.1675 | 174.19 | 2293.69 | LightsWired | TYPE2_LIGHT_SCH | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 33.57 |
SMSTORE2_LIGHTS_ALLOWANCE | SMSTORE2 | 4.4886 | 174.19 | 781.88 | LightsWired | TYPE2_LIGHT_SCH | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 11.44 |
SMSTORE3_LIGHTS | SMSTORE3 | 13.1675 | 174.19 | 2293.69 | LightsWired | TYPE2_LIGHT_SCH | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 33.57 |
SMSTORE3_LIGHTS_ALLOWANCE | SMSTORE3 | 4.4886 | 174.19 | 781.88 | LightsWired | TYPE2_LIGHT_SCH | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 11.44 |
SMSTORE4_LIGHTS | SMSTORE4 | 13.1675 | 174.19 | 2293.69 | LightsWired | TYPE2_LIGHT_SCH | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 33.57 |
SMSTORE4_LIGHTS_ALLOWANCE | SMSTORE4 | 4.4886 | 174.19 | 781.88 | LightsWired | TYPE2_LIGHT_SCH | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 11.44 |
LGSTORE2_LIGHTS | LGSTORE2 | 13.1675 | 348.39 | 4587.39 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 168.00 | 71.66 | 0.0000 | Y | 61.71 |
LGSTORE2_LIGHTS_ALLOWANCE | LGSTORE2 | 0.0000 | 348.39 | 0.00 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE5_LIGHTS | SMSTORE5 | 13.1675 | 174.19 | 2293.69 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 168.00 | 71.66 | 0.0000 | Y | 30.85 |
SMSTORE5_LIGHTS_ALLOWANCE | SMSTORE5 | 0.0000 | 174.19 | 0.00 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE6_LIGHTS | SMSTORE6 | 13.1675 | 174.19 | 2293.69 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 168.00 | 71.66 | 0.0000 | Y | 30.85 |
SMSTORE6_LIGHTS_ALLOWANCE | SMSTORE6 | 0.0000 | 174.19 | 0.00 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE7_LIGHTS | SMSTORE7 | 13.1675 | 174.19 | 2293.69 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 168.00 | 71.66 | 0.0000 | Y | 30.85 |
SMSTORE7_LIGHTS_ALLOWANCE | SMSTORE7 | 0.0000 | 174.19 | 0.00 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE8_LIGHTS | SMSTORE8 | 13.1675 | 174.19 | 2293.69 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 168.00 | 71.66 | 0.0000 | Y | 30.85 |
SMSTORE8_LIGHTS_ALLOWANCE | SMSTORE8 | 0.0000 | 174.19 | 0.00 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
Interior Lighting Total | 7.8548 | 4180.64 | 32838.07 | 502.03 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 314.61 | AstronomicalClock | - | 42.24 | 42.24 | 2.49 | |
EXTERIOR_LIGHTS_B | 6630.02 | AstronomicalClock | - | 83.63 | 71.21 | 88.63 | |
Exterior Lighting Total | 6944.63 | 91.12 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2020-06-03 19:19:46
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 39525.84 | 27485.87 | 12039.97 | 0.70 | 3.80 | |||
PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 21275.44 | 14893.45 | 6381.99 | 0.70 | 3.80 | |||
PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 21560.01 | 15084.89 | 6475.12 | 0.70 | 3.80 | |||
PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 21404.43 | 14981.82 | 6422.61 | 0.70 | 3.80 | |||
PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 21529.80 | 15059.02 | 6470.78 | 0.70 | 3.80 | |||
PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 38828.11 | 26933.90 | 11894.21 | 0.69 | 3.80 | |||
PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 20713.52 | 14383.88 | 6329.64 | 0.69 | 3.80 | |||
PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 20565.68 | 14267.44 | 6298.24 | 0.69 | 3.80 | |||
PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 20283.67 | 14055.57 | 6228.10 | 0.69 | 3.80 | |||
PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 22894.64 | 15938.10 | 6956.54 | 0.70 | 3.80 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | 38173.1 | 11.81 | ||||
PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | 20534.8 | 33.67 | ||||
PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | 20810.4 | 45.01 | ||||
PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | 20659.5 | 57.11 | ||||
PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | 20781.9 | 68.57 | ||||
PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | 37507.8 | 49.95 | ||||
PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | 20007.2 | 105.41 | ||||
PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | 19866.2 | 118.02 | ||||
PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | 19595.8 | 131.53 | ||||
PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | 22108.9 | 128.16 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
PSZ-AC_1:1_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 59908.60 | 0.80 | |
PSZ-AC_2:2_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 31740.57 | 0.80 | |
PSZ-AC_3:3_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 31987.27 | 0.80 | |
PSZ-AC_4:4_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 31858.55 | 0.80 | |
PSZ-AC_5:5_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 31941.48 | 0.80 | |
PSZ-AC_6:6_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 58675.12 | 0.80 | |
PSZ-AC_7:7_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 30782.84 | 0.80 | |
PSZ-AC_8:8_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 30593.81 | 0.80 | |
PSZ-AC_9:9_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 30269.98 | 0.80 | |
PSZ-AC_10:10_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 32983.67 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 1.72 | 1837.39 | 1070.05 | 1.00 | 1.34 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 |
PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 0.94 | 1041.24 | 1107.16 | 1.00 | 1.42 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 |
PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 0.95 | 1053.77 | 1107.16 | 1.00 | 1.41 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 |
PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 0.95 | 1047.24 | 1107.16 | 1.00 | 1.42 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 |
PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 0.95 | 1051.45 | 1107.16 | 1.00 | 1.42 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 |
PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 1.68 | 1793.17 | 1070.05 | 1.00 | 1.34 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 |
PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 0.90 | 992.62 | 1107.16 | 1.00 | 1.43 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 |
PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 0.89 | 983.02 | 1107.16 | 1.00 | 1.43 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 |
PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 0.87 | 966.58 | 1107.16 | 1.00 | 1.44 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 |
PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.00 | 1104.34 | 1107.16 | 1.00 | 1.40 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
GAS TANK1 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK2 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK3 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK4 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK5 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK6 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK7 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:19:46
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
LGSTORE1 | 18595.35 | 22314.42 | 64.05 | 1.431 | 1.717 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 23.89 | 23.89 | 0.00980 | 31.20 | 0.01534 | 0.411 | 0.00 |
SMSTORE1 | 10508.39 | 12610.07 | 72.39 | 0.784 | 0.940 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 23.89 | 23.89 | 0.00919 | 27.17 | 0.01534 | 0.206 | 0.00 |
SMSTORE2 | 10631.42 | 12757.71 | 73.24 | 0.793 | 0.952 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 23.89 | 23.89 | 0.00933 | 25.37 | 0.01534 | 0.206 | 0.00 |
SMSTORE3 | 10567.65 | 12681.18 | 72.80 | 0.788 | 0.946 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 23.89 | 23.89 | 0.00931 | 25.37 | 0.01534 | 0.206 | 0.00 |
SMSTORE4 | 10608.70 | 12730.45 | 73.08 | 0.791 | 0.950 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 23.89 | 23.89 | 0.00933 | 25.37 | 0.01534 | 0.206 | 0.00 |
LGSTORE2 | 18627.41 | 22352.90 | 64.16 | 1.384 | 1.661 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 23.89 | 23.89 | 0.00942 | 27.17 | 0.01534 | 0.411 | 0.00 |
SMSTORE5 | 10030.99 | 12037.19 | 69.10 | 0.747 | 0.897 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 23.89 | 23.89 | 0.00934 | 27.17 | 0.01534 | 0.206 | 0.00 |
SMSTORE6 | 9936.95 | 11924.34 | 68.45 | 0.740 | 0.888 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 23.89 | 23.89 | 0.00936 | 27.17 | 0.01534 | 0.206 | 0.00 |
SMSTORE7 | 9775.88 | 11731.05 | 67.35 | 0.728 | 0.873 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 23.89 | 23.89 | 0.00941 | 27.17 | 0.01534 | 0.206 | 0.00 |
SMSTORE8 | 9861.05 | 11833.26 | 67.93 | 0.734 | 0.881 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 23.89 | 23.89 | 0.00943 | 27.17 | 0.01534 | 0.206 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
LGSTORE1 | 30553.68 | 36664.42 | 105.24 | 1.381 | 1.657 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00668 | -26.20 | 0.00036 | 0.411 | 0.00 |
SMSTORE1 | 15134.55 | 18161.47 | 104.26 | 0.684 | 0.821 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00658 | -26.20 | 0.00036 | 0.206 | 0.00 |
SMSTORE2 | 15293.04 | 18351.64 | 105.35 | 0.691 | 0.829 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00659 | -26.20 | 0.00036 | 0.206 | 0.00 |
SMSTORE3 | 15353.91 | 18424.69 | 105.77 | 0.694 | 0.833 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00659 | -26.20 | 0.00036 | 0.206 | 0.00 |
SMSTORE4 | 15488.49 | 18586.19 | 106.70 | 0.700 | 0.840 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00660 | -26.20 | 0.00036 | 0.206 | 0.00 |
LGSTORE2 | 29399.48 | 35279.37 | 101.27 | 1.329 | 1.594 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00667 | -26.20 | 0.00036 | 0.411 | 0.00 |
SMSTORE5 | 15820.60 | 18984.72 | 108.99 | 0.715 | 0.858 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00662 | -26.20 | 0.00036 | 0.206 | 0.00 |
SMSTORE6 | 15805.23 | 18966.27 | 108.88 | 0.714 | 0.857 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00662 | -26.20 | 0.00036 | 0.206 | 0.00 |
SMSTORE7 | 15997.23 | 19196.68 | 110.20 | 0.723 | 0.867 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00663 | -26.20 | 0.00036 | 0.206 | 0.00 |
SMSTORE8 | 18394.32 | 22073.18 | 126.72 | 0.831 | 0.997 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00672 | -26.20 | 0.00036 | 0.206 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC_1:1 | 1.72 | 1.72 | 1.66 | 1.66 | 1.7171 | 1.7171 | 1.7171 | 1.0000 | 1.0000 |
PSZ-AC_2:2 | 0.94 | 0.94 | 0.82 | 0.82 | 0.9405 | 0.9405 | 0.9405 | 1.0000 | 1.0000 |
PSZ-AC_3:3 | 0.95 | 0.95 | 0.83 | 0.83 | 0.9518 | 0.9518 | 0.9518 | 1.0000 | 1.0000 |
PSZ-AC_4:4 | 0.95 | 0.95 | 0.83 | 0.83 | 0.9459 | 0.9459 | 0.9459 | 1.0000 | 1.0000 |
PSZ-AC_5:5 | 0.95 | 0.95 | 0.84 | 0.84 | 0.9497 | 0.9497 | 0.9497 | 1.0000 | 1.0000 |
PSZ-AC_6:6 | 1.68 | 1.68 | 1.59 | 1.59 | 1.6758 | 1.6606 | 1.6758 | 0.9909 | 1.0000 |
PSZ-AC_7:7 | 0.90 | 0.90 | 0.86 | 0.86 | 0.8965 | 0.8965 | 0.8965 | 1.0000 | 1.0000 |
PSZ-AC_8:8 | 0.89 | 0.89 | 0.86 | 0.86 | 0.8879 | 0.8879 | 0.8879 | 1.0000 | 1.0000 |
PSZ-AC_9:9 | 0.87 | 0.87 | 0.87 | 0.87 | 0.8730 | 0.8730 | 0.8730 | 1.0000 | 1.0000 |
PSZ-AC_10:10 | 0.89 | 0.89 | 1.00 | 1.00 | 0.9975 | 0.9975 | 0.9975 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_1:1 | 19762.920 | 0.000 | 1.717110 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 19762.92 | 13679.80 | 1.717110 | 25.64 | 18.55 | 0.01112716 | 12.80 | 11.67 | 0.00850000 | 31.20 | 0.01534436 | 23.10 | 23.9620 | 23.89 | 0.00979819 | 50.5515 | 18595.35 | 0.00 | -999.00 | -999.00 |
PSZ-AC_1:1_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_1:1 | 59908.605 | 59908.605 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 59908.60 | 59908.60 | 1.717113 | 9.36 | 6.47 | 0.00510981 | 40.00 | 20.60 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 23.9619 | 21.10 | 0.00667859 | 41.0068 | 30553.68 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_2:2 | 10637.720 | 0.000 | 0.940470 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 10637.72 | 7447.68 | 0.940470 | 25.51 | 18.42 | 0.01100818 | 12.80 | 11.67 | 0.00850000 | 31.20 | 0.01534436 | 23.10 | 21.8749 | 23.89 | 0.00918929 | 47.4521 | 10053.66 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_2:2 | 31740.566 | 31740.566 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 31740.57 | 31740.57 | 0.940466 | 9.25 | 6.31 | 0.00501891 | 40.00 | 20.60 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 21.8750 | 21.10 | 0.00657699 | 40.3901 | 15134.55 | 0.00 | -999.00 | -999.00 |
PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_3:3 | 10780.005 | 0.000 | 0.951780 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 10780.00 | 7539.60 | 0.951780 | 25.51 | 18.43 | 0.01101803 | 12.80 | 11.67 | 0.00850000 | 31.20 | 0.01534436 | 23.10 | 21.6149 | 23.89 | 0.00933489 | 48.1942 | 10006.06 | 0.00 | -999.00 | -999.00 |
PSZ-AC_3:3_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_3:3 | 31987.269 | 31987.269 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 31987.27 | 31987.27 | 0.951779 | 9.37 | 6.40 | 0.00504307 | 40.00 | 20.60 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 21.6150 | 21.10 | 0.00658765 | 40.4549 | 15293.04 | 0.00 | -999.00 | -999.00 |
PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_4:4 | 10702.215 | 0.000 | 0.945880 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 10702.22 | 7491.07 | 0.945880 | 25.51 | 18.42 | 0.01101046 | 12.80 | 11.67 | 0.00850000 | 31.20 | 0.01534436 | 23.10 | 21.7498 | 23.89 | 0.00931031 | 48.0687 | 10042.53 | 0.00 | -999.00 | -999.00 |
PSZ-AC_4:4_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_4:4 | 31858.547 | 31858.547 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 31858.55 | 31858.55 | 0.945876 | 9.42 | 6.43 | 0.00505220 | 40.00 | 20.60 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 21.7499 | 21.10 | 0.00659163 | 40.4791 | 15353.91 | 0.00 | -999.00 | -999.00 |
PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_5:5 | 10764.900 | 0.000 | 0.949680 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 10764.90 | 7524.38 | 0.949680 | 25.52 | 18.44 | 0.01102401 | 12.80 | 11.67 | 0.00850000 | 31.20 | 0.01534436 | 23.10 | 21.6627 | 23.89 | 0.00933298 | 48.1844 | 9977.36 | 0.00 | -999.00 | -999.00 |
PSZ-AC_5:5_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_5:5 | 31941.479 | 31941.479 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 31941.48 | 31941.48 | 0.949680 | 9.52 | 6.50 | 0.00507225 | 40.00 | 20.60 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 21.6627 | 21.10 | 0.00660047 | 40.5329 | 15488.49 | 0.00 | -999.00 | -999.00 |
PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_6:6 | 19414.055 | 0.000 | 1.675790 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | 19414.06 | 13382.02 | 1.675790 | 25.69 | 18.61 | 0.01117230 | 12.80 | 11.67 | 0.00850000 | 31.20 | 0.01534436 | 23.10 | 24.5528 | 23.89 | 0.00941616 | 48.6088 | 18063.35 | 0.00 | -999.00 | -999.00 |
PSZ-AC_6:6_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_6:6 | 58675.122 | 58675.122 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 58675.12 | 58675.12 | 1.675786 | 8.90 | 6.17 | 0.00504432 | 40.00 | 20.60 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 24.5529 | 21.10 | 0.00667331 | 40.9741 | 29399.48 | 0.00 | -999.00 | -999.00 |
PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_7:7 | 10356.760 | 0.000 | 0.896550 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 10356.76 | 7135.45 | 0.896550 | 25.63 | 18.58 | 0.01116593 | 12.80 | 11.67 | 0.00850000 | 31.20 | 0.01534436 | 23.10 | 22.9465 | 23.89 | 0.00933897 | 48.2156 | 9334.38 | 0.00 | -999.00 | -999.00 |
PSZ-AC_7:7_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_7:7 | 30782.842 | 30782.842 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 30782.84 | 30782.84 | 0.896549 | 9.76 | 6.68 | 0.00512049 | 40.00 | 20.60 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 22.9465 | 21.10 | 0.00662173 | 40.6620 | 15820.60 | 0.00 | -999.00 | -999.00 |
PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_8:8 | 10282.840 | 0.000 | 0.887880 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 10282.84 | 7070.86 | 0.887880 | 25.65 | 18.60 | 0.01118530 | 12.80 | 11.67 | 0.00850000 | 31.20 | 0.01534436 | 23.10 | 23.1706 | 23.89 | 0.00936266 | 48.3363 | 9251.88 | 0.00 | -999.00 | -999.00 |
PSZ-AC_8:8_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_8:8 | 30593.815 | 30593.815 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 30593.81 | 30593.81 | 0.887880 | 9.75 | 6.67 | 0.00511830 | 40.00 | 20.60 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 23.1705 | 21.10 | 0.00662077 | 40.6562 | 15805.23 | 0.00 | -999.00 | -999.00 |
PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_9:9 | 10141.835 | 0.000 | 0.873030 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 10141.83 | 6957.82 | 0.873030 | 25.67 | 18.63 | 0.01120857 | 12.80 | 11.67 | 0.00850000 | 31.20 | 0.01534436 | 23.10 | 23.5647 | 23.89 | 0.00941105 | 48.5830 | 9154.27 | 0.00 | -999.00 | -999.00 |
PSZ-AC_9:9_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_9:9 | 30269.981 | 30269.981 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 30269.98 | 30269.98 | 0.873030 | 9.89 | 6.77 | 0.00514546 | 40.00 | 20.60 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 23.5647 | 21.10 | 0.00663273 | 40.7289 | 15997.23 | 0.00 | -999.00 | -999.00 |
PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_10:10 | 11447.320 | 0.000 | 0.997460 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:10:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | 11447.32 | 7863.29 | 0.997460 | 25.52 | 18.55 | 0.01117094 | 12.80 | 11.67 | 0.00850000 | 30.76 | 0.01534436 | 22.98 | 20.6251 | 23.89 | 0.00942911 | 48.6751 | 9369.45 | 0.00 | -999.00 | -999.00 |
PSZ-AC_10:10_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_10:10 | 32983.666 | 32983.666 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 32983.67 | 32983.67 | 0.997455 | 11.35 | 7.76 | 0.00540573 | 40.00 | 20.60 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 20.6252 | 21.10 | 0.00671649 | 41.2389 | 18394.32 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2020-06-03 19:19:46
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | LGSTORE1 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 19762.920 | 0.000 | 1.717110 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1025.5248 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 19762.92 | 13679.80 | 1.0000 | 1.97219670 | 1.717110 | 25.64 | 18.55 | 0.01112716 | 54121.1 | 12.80 | 11.67 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 19762.92 | 31.20 | 0.01534436 | 23.10 | 0.41145340 | 23.9620 | 23.89 | 0.00979819 | 23.89 | 0.00979819 | 50.5515 | 18595.35 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_1:1_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | LGSTORE1 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 59908.605 | 59908.605 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.717113 | 1.97219980 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 59908.60 | 59908.60 | 1.0000 | 1.97219980 | 1.717113 | 9.36 | 6.47 | 0.00510981 | 22271.6 | 40.00 | 20.60 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 59908.60 | -26.20 | 0.00036134 | -26.20 | 0.41145340 | 23.9619 | 21.11 | 0.00667859 | 21.10 | 0.00667859 | 41.0068 | 30553.68 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | SMSTORE1 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 10637.720 | 0.000 | 0.940470 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1025.3037 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 10637.72 | 7447.68 | 1.0000 | 1.08018230 | 0.940470 | 25.51 | 18.42 | 0.01100818 | 53682.7 | 12.80 | 11.67 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10637.72 | 31.20 | 0.01534436 | 23.10 | 0.20572670 | 21.8749 | 23.89 | 0.00977373 | 23.89 | 0.00918929 | 47.4521 | 10053.66 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | SMSTORE1 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 31740.566 | 31740.566 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.940466 | 1.08017737 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 31740.57 | 31740.57 | 1.0000 | 1.08017737 | 0.940466 | 9.25 | 6.31 | 0.00501891 | 21930.5 | 40.00 | 20.60 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 31740.57 | -26.20 | 0.00036134 | -26.20 | 0.20572670 | 21.8750 | 21.11 | 0.00657699 | 21.10 | 0.00657699 | 40.3901 | 15134.55 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_3:3 | SMSTORE2 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 10780.005 | 0.000 | 0.951780 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1025.3220 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 10780.00 | 7539.60 | 1.0000 | 1.09317247 | 0.951780 | 25.51 | 18.43 | 0.01101803 | 53715.7 | 12.80 | 11.67 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10780.00 | 31.20 | 0.01534436 | 23.10 | 0.20572670 | 21.6149 | 23.89 | 0.00977884 | 23.89 | 0.00933489 | 48.1942 | 10006.06 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_3:3_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_3:3 | SMSTORE2 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 31987.269 | 31987.269 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.951779 | 1.09317155 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 31987.27 | 31987.27 | 1.0000 | 1.09317155 | 0.951779 | 9.37 | 6.40 | 0.00504307 | 22116.0 | 40.00 | 20.60 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 31987.27 | -26.20 | 0.00036134 | -26.20 | 0.20572670 | 21.6150 | 21.11 | 0.00658765 | 21.10 | 0.00658765 | 40.4549 | 15293.04 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_4:4 | SMSTORE3 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 10702.215 | 0.000 | 0.945880 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1025.3079 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 10702.22 | 7491.07 | 1.0000 | 1.08639599 | 0.945880 | 25.51 | 18.42 | 0.01101046 | 53690.4 | 12.80 | 11.67 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10702.22 | 31.20 | 0.01534436 | 23.10 | 0.20572670 | 21.7498 | 23.89 | 0.00977489 | 23.89 | 0.00931031 | 48.0687 | 10042.53 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_4:4_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_4:4 | SMSTORE3 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 31858.547 | 31858.547 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.945876 | 1.08639183 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 31858.55 | 31858.55 | 1.0000 | 1.08639183 | 0.945876 | 9.42 | 6.43 | 0.00505220 | 22186.2 | 40.00 | 20.60 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 31858.55 | -26.20 | 0.00036134 | -26.20 | 0.20572670 | 21.7499 | 21.11 | 0.00659163 | 21.10 | 0.00659163 | 40.4791 | 15353.91 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_5:5 | SMSTORE4 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 10764.900 | 0.000 | 0.949680 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1025.3331 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 10764.90 | 7524.38 | 1.0000 | 1.09076050 | 0.949680 | 25.52 | 18.44 | 0.01102401 | 53735.8 | 12.80 | 11.67 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10764.90 | 31.20 | 0.01534436 | 23.10 | 0.20572670 | 21.6627 | 23.89 | 0.00978195 | 23.89 | 0.00933298 | 48.1844 | 9977.36 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_5:5_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_5:5 | SMSTORE4 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 31941.479 | 31941.479 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.949680 | 1.09076012 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 31941.48 | 31941.48 | 1.0000 | 1.09076012 | 0.949680 | 9.52 | 6.50 | 0.00507225 | 22339.7 | 40.00 | 20.60 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 31941.48 | -26.20 | 0.00036134 | -26.20 | 0.20572670 | 21.6627 | 21.11 | 0.00660047 | 21.10 | 0.00660047 | 40.5329 | 15488.49 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_6:6 | LGSTORE2 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 19414.055 | 0.000 | 1.675790 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1025.6088 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | 19414.06 | 13382.02 | 1.0000 | 1.92473837 | 1.675790 | 25.69 | 18.61 | 0.01117230 | 54289.2 | 12.80 | 11.67 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 19414.06 | 31.20 | 0.01534436 | 23.10 | 0.41145340 | 24.5528 | 23.89 | 0.00980614 | 23.89 | 0.00941616 | 48.6088 | 18063.35 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_6:6_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_6:6 | LGSTORE2 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 58675.122 | 58675.122 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.675786 | 1.92473359 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 58675.12 | 58675.12 | 1.0000 | 1.92473359 | 1.675786 | 8.90 | 6.17 | 0.00504432 | 21639.3 | 40.00 | 20.60 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 58675.12 | -26.20 | 0.00036134 | -26.20 | 0.41145340 | 24.5529 | 21.11 | 0.00667331 | 21.10 | 0.00667331 | 40.9741 | 29399.48 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_7:7 | SMSTORE5 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 10356.760 | 0.000 | 0.896550 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1025.5969 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 10356.76 | 7135.45 | 1.0000 | 1.02973773 | 0.896550 | 25.63 | 18.58 | 0.01116593 | 54212.8 | 12.80 | 11.67 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10356.76 | 31.20 | 0.01534436 | 23.10 | 0.20572670 | 22.9465 | 23.89 | 0.00985598 | 23.89 | 0.00933897 | 48.2156 | 9334.38 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_7:7_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_7:7 | SMSTORE5 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 30782.842 | 30782.842 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.896549 | 1.02973609 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 30782.84 | 30782.84 | 1.0000 | 1.02973609 | 0.896549 | 9.76 | 6.68 | 0.00512049 | 22708.0 | 40.00 | 20.60 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 30782.84 | -26.20 | 0.00036134 | -26.20 | 0.20572670 | 22.9465 | 21.11 | 0.00662173 | 21.10 | 0.00662173 | 40.6620 | 15820.60 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_8:8 | SMSTORE6 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 10282.840 | 0.000 | 0.887880 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1025.6329 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 10282.84 | 7070.86 | 1.0000 | 1.01977975 | 0.887880 | 25.65 | 18.60 | 0.01118530 | 54278.2 | 12.80 | 11.67 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10282.84 | 31.20 | 0.01534436 | 23.10 | 0.20572670 | 23.1706 | 23.89 | 0.00986611 | 23.89 | 0.00936266 | 48.3363 | 9251.88 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_8:8_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_8:8 | SMSTORE6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 30593.815 | 30593.815 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.887880 | 1.01978006 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 30593.81 | 30593.81 | 1.0000 | 1.01978006 | 0.887880 | 9.75 | 6.67 | 0.00511830 | 22691.3 | 40.00 | 20.60 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 30593.81 | -26.20 | 0.00036134 | -26.20 | 0.20572670 | 23.1705 | 21.11 | 0.00662077 | 21.10 | 0.00662077 | 40.6562 | 15805.23 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_9:9 | SMSTORE7 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 10141.835 | 0.000 | 0.873030 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1025.6762 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 10141.83 | 6957.82 | 1.0000 | 1.00272369 | 0.873030 | 25.67 | 18.63 | 0.01120857 | 54356.8 | 12.80 | 11.67 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10141.83 | 31.20 | 0.01534436 | 23.10 | 0.20572670 | 23.5647 | 23.89 | 0.00987828 | 23.89 | 0.00941105 | 48.5830 | 9154.27 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_9:9_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_9:9 | SMSTORE7 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 30269.981 | 30269.981 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.873030 | 1.00272393 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 30269.98 | 30269.98 | 1.0000 | 1.00272393 | 0.873030 | 9.89 | 6.77 | 0.00514546 | 22897.9 | 40.00 | 20.60 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 30269.98 | -26.20 | 0.00036134 | -26.20 | 0.20572670 | 23.5647 | 21.11 | 0.00663273 | 21.10 | 0.00663273 | 40.7289 | 15997.23 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_10:10 | SMSTORE8 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 11447.320 | 0.000 | 0.997460 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1025.6062 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:10:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | 11447.32 | 7863.29 | 1.0000 | 1.14563850 | 0.997460 | 25.52 | 18.55 | 0.01117094 | 54108.4 | 12.80 | 11.67 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11447.32 | 30.76 | 0.01534436 | 22.98 | 0.20572670 | 20.6251 | 23.89 | 0.00987256 | 23.89 | 0.00942911 | 48.6751 | 9369.45 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_10:10_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_10:10 | SMSTORE8 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 32983.666 | 32983.666 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.997455 | 1.14563315 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 32983.67 | 32983.67 | 1.0000 | 1.14563315 | 0.997455 | 11.35 | 7.76 | 0.00540573 | 25036.8 | 40.00 | 20.60 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 32983.67 | -26.20 | 0.00036134 | -26.20 | 0.20572670 | 20.6252 | 21.11 | 0.00671649 | 21.10 | 0.00671649 | 41.2389 | 18394.32 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2020-06-03 19:19:46
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-AC_1:1_OA_CONTROLLER | DifferentialDryBulb | 0.41 | 1.72 | - | |||
PSZ-AC_2:2_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 0.94 | - | |||
PSZ-AC_3:3_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 0.95 | - | |||
PSZ-AC_4:4_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 0.95 | - | |||
PSZ-AC_5:5_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 0.95 | - | |||
PSZ-AC_6:6_OA_CONTROLLER | DifferentialDryBulb | 0.41 | 1.68 | - | |||
PSZ-AC_7:7_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 0.90 | - | |||
PSZ-AC_8:8_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 0.89 | - | |||
PSZ-AC_9:9_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 0.87 | - | |||
PSZ-AC_10:10_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.00 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
LGSTORE1 | 3613.50 | 4011.33 | 2100.00 |
SMSTORE1 | 2964.00 | 3721.00 | 1365.33 |
SMSTORE2 | 2587.67 | 2963.50 | 1397.67 |
SMSTORE3 | 2655.83 | 2987.00 | 1474.83 |
SMSTORE4 | 2697.83 | 3041.67 | 1557.17 |
LGSTORE2 | 2546.33 | 2857.17 | 1582.67 |
SMSTORE5 | 2516.00 | 2892.33 | 1609.50 |
SMSTORE6 | 2521.33 | 2922.83 | 1639.50 |
SMSTORE7 | 2562.83 | 2987.50 | 1735.83 |
SMSTORE8 | 2737.17 | 3095.50 | 2014.33 |
Facility | 4286.83 | 4472.00 | 2796.17 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
LGSTORE1 | 8.17 | 0.33 | 0.33 | 0.33 |
SMSTORE1 | 4.33 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 0.00 | 0.17 | 0.00 | 0.17 |
SMSTORE3 | 0.00 | 0.33 | 0.00 | 0.33 |
SMSTORE4 | 0.00 | 0.17 | 0.00 | 0.17 |
LGSTORE2 | 0.33 | 0.17 | 0.33 | 0.17 |
SMSTORE5 | 0.17 | 0.00 | 0.17 | 0.00 |
SMSTORE6 | 0.67 | 0.00 | 0.17 | 0.00 |
SMSTORE7 | 0.83 | 0.00 | 0.33 | 0.00 |
SMSTORE8 | 64.67 | 0.00 | 0.33 | 0.00 |
Facility | 73.67 | 0.67 | 0.33 | 0.67 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2020-06-03 19:19:46
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
LGSTORE1 | 9.03 | 30.00 | 1805.20 | 0.931 | 0.244 | 0.000 | 0.000 |
SMSTORE1 | 4.51 | 15.00 | 902.60 | 0.801 | 0.255 | 0.000 | 0.000 |
SMSTORE2 | 3.78 | 15.00 | 902.60 | 0.981 | 0.332 | 0.000 | 0.000 |
SMSTORE3 | 3.78 | 15.00 | 902.60 | 0.977 | 0.332 | 0.000 | 0.000 |
SMSTORE4 | 3.78 | 15.00 | 902.60 | 0.972 | 0.332 | 0.000 | 0.000 |
LGSTORE2 | 13.22 | 30.00 | 1805.20 | 0.941 | 0.319 | 0.000 | 0.000 |
SMSTORE5 | 6.61 | 15.00 | 902.60 | 0.955 | 0.353 | 0.000 | 0.000 |
SMSTORE6 | 6.61 | 15.00 | 902.60 | 0.950 | 0.353 | 0.000 | 0.000 |
SMSTORE7 | 6.61 | 15.00 | 902.60 | 0.940 | 0.353 | 0.000 | 0.000 |
SMSTORE8 | 6.61 | 15.00 | 902.60 | 0.953 | 0.381 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
LGSTORE1 | 9.03 | 30.00 | 1805.20 | 0.000 | 0.000 | 0.000 | 0.000 |
SMSTORE1 | 4.51 | 15.00 | 902.60 | 0.000 | 0.000 | 0.000 | 0.000 |
SMSTORE2 | 3.78 | 15.00 | 902.60 | 0.800 | 0.000 | 0.000 | 0.000 |
SMSTORE3 | 3.78 | 15.00 | 902.60 | 0.800 | 0.000 | 0.000 | 0.000 |
SMSTORE4 | 3.78 | 15.00 | 902.60 | 0.800 | 0.000 | 0.000 | 0.000 |
LGSTORE2 | 13.22 | 30.00 | 1805.20 | 0.800 | 0.000 | 0.000 | 0.000 |
SMSTORE5 | 6.61 | 15.00 | 902.60 | 0.801 | 0.000 | 0.000 | 0.000 |
SMSTORE6 | 6.61 | 15.00 | 902.60 | 0.800 | 0.000 | 0.000 | 0.000 |
SMSTORE7 | 6.61 | 15.00 | 902.60 | 0.800 | 0.000 | 0.000 | 0.000 |
SMSTORE8 | 6.61 | 15.00 | 902.60 | 0.800 | 0.000 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2020-06-03 19:19:46
Surfaces by ClassTotal | Outdoors | |
Wall | 40 | 22 |
Floor | 10 | 10 |
Roof | 10 | 10 |
Internal Mass | 10 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 36 | 36 |
Door | 12 | 12 |
Glass Door | 12 | 12 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 10 |
Conditioned Zones | 10 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 0 |
Defaulted Fields | 0 |
Fields with Defaults | 0 |
Autosized Fields | 0 |
Autosizable Fields | 0 |
Autocalculated Fields | 0 |
Autocalculatable Fields | 0 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2020-06-03 19:19:46
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 963.87 | 3309.32 | 01-JAN-08:00 | 105839.69 | 04-AUG-13:40 |
Electricity:Building | 630.75 | 2091.32 | 01-JAN-00:10 | 39285.70 | 01-JAN-11:10 |
Electricity:Zone:LGSTORE1 | 144.52 | 394.83 | 01-JAN-00:10 | 7426.96 | 01-JAN-10:10 |
InteriorLights:Electricity | 502.03 | 1641.90 | 01-JAN-00:10 | 31196.17 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:LGSTORE1 | 118.16 | 319.93 | 01-JAN-00:10 | 6078.71 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity | 502.03 | 1641.90 | 01-JAN-00:10 | 31196.17 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE1 | 76.90 | 209.98 | 01-JAN-00:10 | 3952.17 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE1 | 63.72 | 172.53 | 01-JAN-00:10 | 3278.04 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE2 | 55.48 | 191.23 | 01-JAN-00:10 | 3595.92 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE2 | 45.01 | 153.78 | 01-JAN-00:10 | 2921.79 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE3 | 55.48 | 191.23 | 01-JAN-00:10 | 3595.92 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE3 | 45.01 | 153.78 | 01-JAN-00:10 | 2921.79 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE4 | 55.48 | 191.23 | 01-JAN-00:10 | 3595.92 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE4 | 45.01 | 153.78 | 01-JAN-00:10 | 2921.79 | 01-JAN-10:10 |
Electricity:Zone:LGSTORE2 | 80.97 | 304.27 | 01-JAN-00:10 | 5706.27 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:LGSTORE2 | 61.71 | 229.37 | 01-JAN-00:10 | 4358.02 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE5 | 40.48 | 152.14 | 01-JAN-00:10 | 2853.14 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE5 | 30.85 | 114.68 | 01-JAN-00:10 | 2179.01 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE6 | 40.48 | 152.14 | 01-JAN-00:10 | 2853.14 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE6 | 30.85 | 114.68 | 01-JAN-00:10 | 2179.01 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE7 | 40.48 | 152.14 | 01-JAN-00:10 | 2853.14 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE7 | 30.85 | 114.68 | 01-JAN-00:10 | 2179.01 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE8 | 40.48 | 152.14 | 01-JAN-00:10 | 2853.14 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE8 | 30.85 | 114.68 | 01-JAN-00:10 | 2179.01 | 01-JAN-11:10 |
InteriorEquipment:Electricity | 128.72 | 449.42 | 01-JAN-00:10 | 8089.53 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:LGSTORE1 | 26.36 | 74.90 | 01-JAN-00:10 | 1348.26 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity | 128.72 | 449.42 | 01-JAN-00:10 | 8089.53 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE1 | 13.18 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE2 | 10.47 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE3 | 10.47 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE4 | 10.47 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:LGSTORE2 | 19.26 | 74.90 | 01-JAN-00:10 | 1348.26 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE5 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE6 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE7 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE8 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
Electricity:Plant | 66.31 | 1218.00 | 02-JAN-08:10 | 11887.88 | 30-MAR-13:40 |
WaterSystems:Electricity | 66.31 | 1218.00 | 02-JAN-08:10 | 11887.88 | 30-MAR-13:40 |
Water Heater:WaterSystems:Electricity | 66.31 | 1218.00 | 02-JAN-08:10 | 11887.88 | 30-MAR-13:40 |
ElectricityPurchased:Facility | 963.87 | 3309.32 | 08-JAN-08:00 | 105839.69 | 04-AUG-13:40 |
ElectricityPurchased:Plant | 963.87 | 3309.32 | 08-JAN-08:00 | 105839.69 | 04-AUG-13:40 |
Cogeneration:ElectricityPurchased | 963.87 | 3309.32 | 08-JAN-08:00 | 105839.69 | 04-AUG-13:40 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 963.87 | 3309.32 | 08-JAN-08:00 | 105839.69 | 04-AUG-13:40 |
ElectricityNet:Plant | 963.87 | 3309.32 | 08-JAN-08:00 | 105839.69 | 04-AUG-13:40 |
Cogeneration:ElectricityNet | 963.87 | 3309.32 | 08-JAN-08:00 | 105839.69 | 04-AUG-13:40 |
Electricity:HVAC | 175.69 | 0.00 | 01-JAN-00:10 | 60116.40 | 04-AUG-16:00 |
Fans:Electricity | 96.12 | 0.00 | 01-JAN-00:10 | 10318.75 | 02-FEB-09:10 |
General:Fans:Electricity | 96.12 | 0.00 | 01-JAN-00:10 | 10318.75 | 02-FEB-09:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 79.57 | 0.00 | 01-JAN-00:10 | 51271.75 | 04-AUG-16:00 |
ExteriorLights:Electricity | 91.12 | 0.00 | 01-JAN-08:00 | 6944.63 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 91.12 | 0.00 | 01-JAN-08:00 | 6944.63 | 01-JAN-06:10 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Gas:Facility | 908.64 | 0.00 | 01-JAN-00:10 | 363273.12 | 02-FEB-09:10 |
Gas:HVAC | 908.64 | 0.00 | 01-JAN-00:10 | 363273.12 | 02-FEB-09:10 |
Heating:Gas | 908.64 | 0.00 | 01-JAN-00:10 | 363273.12 | 02-FEB-09:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water:Plant | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
WaterSystems:Water | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water Heater:WaterSystems:Water | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
MainsWater:Facility | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
MainsWater:Plant | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
WaterSystems:MainsWater | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water Heater:WaterSystems:MainsWater | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:Facility | 1615.17 | 0.00 | 01-JAN-00:10 | 429927.74 | 02-FEB-09:10 |
EnergyTransfer:Building | 559.54 | 0.00 | 01-JAN-00:10 | 143362.01 | 02-FEB-12:10 |
EnergyTransfer:Zone:LGSTORE1 | 108.84 | 0.00 | 01-JAN-00:10 | 25539.15 | 02-FEB-09:10 |
Heating:EnergyTransfer | 260.25 | 0.00 | 01-JAN-00:10 | 143362.01 | 02-FEB-12:10 |
Heating:EnergyTransfer:Zone:LGSTORE1 | 39.24 | 0.00 | 01-JAN-00:10 | 25539.15 | 02-FEB-09:10 |
Cooling:EnergyTransfer | 299.29 | 0.00 | 01-JAN-00:10 | 84292.05 | 04-AUG-15:00 |
Cooling:EnergyTransfer:Zone:LGSTORE1 | 69.60 | 0.00 | 01-JAN-00:10 | 22803.36 | 03-FEB-00:10 |
EnergyTransfer:Zone:SMSTORE1 | 52.07 | 0.00 | 01-JAN-00:10 | 12045.88 | 04-FEB-09:10 |
Heating:EnergyTransfer:Zone:SMSTORE1 | 14.46 | 0.00 | 01-JAN-00:10 | 11402.80 | 04-FEB-09:10 |
Cooling:EnergyTransfer:Zone:SMSTORE1 | 37.61 | 0.00 | 01-JAN-00:10 | 8421.39 | 22-AUG-21:50 |
EnergyTransfer:Zone:SMSTORE2 | 44.32 | 0.00 | 01-JAN-00:10 | 13075.92 | 02-FEB-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE2 | 17.28 | 0.00 | 01-JAN-00:10 | 13075.92 | 02-FEB-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE2 | 27.04 | 0.00 | 01-JAN-00:10 | 7369.48 | 07-SEP-13:50 |
EnergyTransfer:Zone:SMSTORE3 | 44.73 | 0.00 | 01-JAN-00:10 | 13285.01 | 02-FEB-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE3 | 18.44 | 0.00 | 01-JAN-00:10 | 13285.01 | 02-FEB-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE3 | 26.30 | 0.00 | 01-JAN-00:10 | 7354.25 | 07-SEP-13:50 |
EnergyTransfer:Zone:SMSTORE4 | 44.94 | 0.00 | 01-JAN-00:10 | 13668.81 | 06-FEB-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE4 | 20.10 | 0.00 | 01-JAN-00:10 | 13638.47 | 02-FEB-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE4 | 24.84 | 0.00 | 01-JAN-00:10 | 7238.68 | 07-SEP-13:50 |
EnergyTransfer:Zone:LGSTORE2 | 80.30 | 0.00 | 01-JAN-00:10 | 24882.64 | 06-FEB-09:10 |
Heating:EnergyTransfer:Zone:LGSTORE2 | 39.86 | 0.00 | 01-JAN-00:10 | 24692.63 | 02-FEB-09:10 |
Cooling:EnergyTransfer:Zone:LGSTORE2 | 40.44 | 0.00 | 01-JAN-00:10 | 13255.30 | 04-AUG-15:00 |
EnergyTransfer:Zone:SMSTORE5 | 42.60 | 0.00 | 01-JAN-00:10 | 13384.08 | 02-FEB-09:10 |
Heating:EnergyTransfer:Zone:SMSTORE5 | 22.37 | 0.00 | 01-JAN-00:10 | 13384.08 | 02-FEB-09:10 |
Cooling:EnergyTransfer:Zone:SMSTORE5 | 20.23 | 0.00 | 01-JAN-00:10 | 6911.12 | 04-AUG-15:00 |
EnergyTransfer:Zone:SMSTORE6 | 42.44 | 0.00 | 01-JAN-00:10 | 13407.19 | 02-FEB-09:10 |
Heating:EnergyTransfer:Zone:SMSTORE6 | 22.83 | 0.00 | 01-JAN-00:10 | 13407.19 | 02-FEB-09:10 |
Cooling:EnergyTransfer:Zone:SMSTORE6 | 19.61 | 0.00 | 01-JAN-00:10 | 6849.22 | 04-AUG-15:00 |
EnergyTransfer:Zone:SMSTORE7 | 43.23 | 0.00 | 01-JAN-00:10 | 13717.34 | 02-FEB-09:10 |
Heating:EnergyTransfer:Zone:SMSTORE7 | 25.14 | 0.00 | 01-JAN-00:10 | 13717.34 | 02-FEB-09:10 |
Cooling:EnergyTransfer:Zone:SMSTORE7 | 18.10 | 0.00 | 01-JAN-00:10 | 6777.23 | 04-AUG-15:00 |
EnergyTransfer:Zone:SMSTORE8 | 56.05 | 0.00 | 01-JAN-00:10 | 17018.89 | 02-FEB-09:10 |
Heating:EnergyTransfer:Zone:SMSTORE8 | 40.53 | 0.00 | 01-JAN-00:10 | 17018.89 | 02-FEB-09:10 |
Cooling:EnergyTransfer:Zone:SMSTORE8 | 15.52 | 0.00 | 01-JAN-00:10 | 7067.78 | 04-AUG-15:00 |
EnergyTransfer:HVAC | 1055.64 | 0.00 | 01-JAN-00:10 | 290618.49 | 02-FEB-09:10 |
HeatingCoils:EnergyTransfer | 726.91 | 0.00 | 01-JAN-00:10 | 290618.49 | 02-FEB-09:10 |
CoolingCoils:EnergyTransfer | 328.73 | 0.00 | 01-JAN-00:10 | 215998.78 | 04-AUG-13:00 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2020-06-03 19:19:46
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
LGSTORE1 | 0.000 | 0.000 | 39.244 | -69.596 | 0.000 | 0.000 | 13.637 | 118.163 | 26.357 | 18.688 | 0.000 | 1.562 | 0.005 | 0.000 | -12.688 | 0.000 | -54.458 | -80.910 |
SMSTORE1 | 0.000 | 0.000 | 14.460 | -37.611 | 0.000 | 0.000 | 6.734 | 63.721 | 13.179 | 9.257 | 0.000 | 0.839 | 0.001 | 0.000 | -6.611 | 0.000 | -25.815 | -38.151 |
SMSTORE2 | 0.000 | 0.000 | 17.280 | -27.038 | 0.000 | 0.000 | 4.094 | 45.008 | 10.467 | 9.247 | 0.000 | 0.817 | 0.001 | 0.000 | -6.501 | 0.000 | -26.660 | -26.714 |
SMSTORE3 | 0.000 | 0.000 | 18.438 | -26.297 | 0.000 | 0.000 | 4.099 | 45.008 | 10.467 | 9.262 | 0.000 | 0.817 | 0.001 | 0.000 | -6.437 | 0.000 | -26.566 | -28.792 |
SMSTORE4 | 0.000 | 0.000 | 20.097 | -24.841 | 0.000 | 0.000 | 4.106 | 45.008 | 10.467 | 9.282 | 0.000 | 0.818 | 0.000 | 0.000 | -6.380 | 0.000 | -26.470 | -32.086 |
LGSTORE2 | 0.000 | 0.000 | 39.862 | -40.438 | 0.000 | 0.000 | 14.115 | 61.707 | 19.261 | 18.668 | 0.000 | 1.475 | 0.001 | 0.000 | -12.449 | 0.000 | -48.984 | -53.217 |
SMSTORE5 | 0.000 | 0.000 | 22.371 | -20.231 | 0.000 | 0.000 | 7.061 | 30.853 | 9.631 | 9.325 | 0.000 | 0.819 | 0.000 | 0.000 | -6.241 | 0.000 | -26.565 | -27.024 |
SMSTORE6 | 0.000 | 0.000 | 22.832 | -19.612 | 0.000 | 0.000 | 7.067 | 30.853 | 9.631 | 9.337 | 0.000 | 0.819 | 0.000 | 0.000 | -6.216 | 0.000 | -26.519 | -28.192 |
SMSTORE7 | 0.000 | 0.000 | 25.135 | -18.098 | 0.000 | 0.000 | 7.082 | 30.853 | 9.631 | 9.368 | 0.000 | 0.820 | 0.001 | 0.000 | -6.133 | 0.000 | -26.378 | -32.280 |
SMSTORE8 | 0.000 | 0.000 | 40.533 | -15.517 | 0.000 | 0.000 | 7.106 | 30.853 | 9.631 | 9.456 | 0.000 | 0.875 | 0.002 | 0.000 | -5.816 | 0.000 | -34.824 | -42.295 |
Total Facility | 0.000 | 0.000 | 260.251 | -299.280 | 0.000 | 0.000 | 75.101 | 502.028 | 128.721 | 111.890 | 0.000 | 9.661 | 0.013 | 0.000 | -75.471 | 0.000 | -323.240 | -389.661 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
LGSTORE1 | 18-JUL-08:62 | 0.00 | 0.00 | 0.00 | -31844.36 | 0.00 | 0.00 | 96.53 | 3199.32 | 749.03 | 517.63 | 0.00 | 0.00 | 27570.01 | 0.00 | -0.00 | 0.00 | -288.16 | 0.00 |
SMSTORE1 | 18-JUL-08:62 | 0.00 | 0.00 | 0.00 | -17859.14 | 0.00 | 0.00 | 46.79 | 1725.28 | 374.52 | 252.97 | 0.00 | 0.00 | 15599.30 | 0.00 | -0.00 | 0.00 | -139.72 | 0.00 |
SMSTORE2 | 06-AUG-08:62 | 0.00 | 0.00 | 0.00 | -20542.34 | 0.00 | 0.00 | 47.15 | 1537.78 | 374.52 | 159.04 | 0.00 | 0.00 | 18728.73 | 0.00 | -0.00 | 0.00 | -304.88 | 0.00 |
SMSTORE3 | 06-AUG-08:62 | 0.00 | 0.00 | 0.00 | -20434.95 | 0.00 | 0.00 | 47.05 | 1537.78 | 374.52 | 158.39 | 0.00 | 0.00 | 18622.96 | 0.00 | -0.00 | 0.00 | -305.74 | 0.00 |
SMSTORE4 | 06-AUG-08:62 | 0.00 | 0.00 | 0.00 | -20439.19 | 0.00 | 0.00 | 47.43 | 1537.78 | 374.52 | 159.79 | 0.00 | 0.00 | 18622.68 | 0.00 | -0.00 | 0.00 | -303.01 | 0.00 |
LGSTORE2 | 06-AUG-09:02 | 0.00 | 0.00 | 0.00 | -31762.54 | 0.00 | 0.00 | 211.05 | 2293.69 | 749.03 | 476.84 | 0.00 | 0.00 | 28589.71 | 0.00 | -0.00 | 0.00 | -557.79 | 0.00 |
SMSTORE5 | 18-JUL-08:62 | 0.00 | 0.00 | 0.00 | -16516.86 | 0.00 | 0.00 | 105.63 | 1146.85 | 374.52 | 255.28 | 0.00 | 0.00 | 14767.69 | 0.00 | -0.00 | 0.00 | -133.09 | 0.00 |
SMSTORE6 | 18-JUL-08:62 | 0.00 | 0.00 | 0.00 | -16334.54 | 0.00 | 0.00 | 106.14 | 1146.85 | 374.52 | 256.39 | 0.00 | 0.00 | 14582.36 | 0.00 | -0.00 | 0.00 | -131.72 | 0.00 |
SMSTORE7 | 12-SEP-08:62 | 0.00 | 0.00 | 0.00 | -15696.71 | 0.00 | 0.00 | 105.80 | 1146.85 | 374.52 | 0.00 | 0.00 | 0.00 | 14281.66 | 0.00 | -6.44 | 0.00 | -205.67 | 0.00 |
SMSTORE8 | 08-SEP-08:62 | 0.00 | 0.00 | 0.00 | -15543.39 | 0.00 | 0.00 | 107.17 | 1146.85 | 374.52 | 415.92 | 0.00 | 0.00 | 13539.34 | 0.00 | -0.00 | 0.00 | -40.40 | 0.00 |
Total Facility | 18-SEP-08:62 | 0.00 | 0.00 | 0.00 | -148063.22 | 0.00 | 0.00 | 1079.45 | 20571.05 | 5393.02 | 4255.20 | 0.00 | 0.00 | 117843.96 | 0.00 | 0.00 | 0.00 | -1079.47 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
LGSTORE1 | 19-JAN-00:42 | 0.00 | 0.00 | 60811.36 | 0.00 | 0.00 | 0.00 | 0.00 | 319.93 | 74.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1477.68 | 0.00 | -7493.39 | -52235.12 |
SMSTORE1 | 04-FEB-08:61 | 0.00 | 0.00 | 31801.91 | 0.00 | 0.00 | 0.00 | 0.00 | 172.53 | 37.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -673.26 | 0.00 | -1295.71 | -30042.93 |
SMSTORE2 | 11-DEC-07:01 | 0.00 | 0.00 | 31997.04 | 0.00 | 0.00 | 0.00 | 0.00 | 153.78 | 37.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -661.27 | 0.00 | -175.21 | -31351.79 |
SMSTORE3 | 11-DEC-07:01 | 0.00 | 0.00 | 31876.89 | 0.00 | 0.00 | 0.00 | 0.00 | 153.78 | 37.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -657.70 | 0.00 | -175.17 | -31235.26 |
SMSTORE4 | 11-DEC-07:01 | 0.00 | 0.00 | 31948.91 | 0.00 | 0.00 | 0.00 | 0.00 | 153.78 | 37.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -653.67 | 0.00 | -173.73 | -31312.74 |
LGSTORE2 | 04-FEB-08:61 | 0.00 | 0.00 | 58860.27 | 0.00 | 0.00 | 0.00 | 0.00 | 229.37 | 74.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1297.74 | 0.00 | -2305.38 | -55561.42 |
SMSTORE5 | 04-FEB-08:61 | 0.00 | 0.00 | 30935.27 | 0.00 | 0.00 | 0.00 | 0.00 | 114.68 | 37.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -654.87 | 0.00 | -1281.88 | -29150.65 |
SMSTORE6 | 12-DEC-08:61 | 0.00 | 0.00 | 30723.49 | 0.00 | 0.00 | 0.00 | 0.00 | 114.68 | 37.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -584.82 | 0.00 | -1022.12 | -29268.69 |
SMSTORE7 | 09-DEC-08:61 | 0.00 | 0.00 | 30396.24 | 0.00 | 0.00 | 0.00 | 0.00 | 114.68 | 37.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -665.11 | 0.00 | -1460.03 | -28423.24 |
SMSTORE8 | 09-DEC-06:02 | 0.00 | 0.00 | 33380.86 | 0.00 | 0.00 | 0.00 | 0.00 | 114.68 | 37.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -662.54 | 0.00 | -5258.98 | -27611.47 |
Total Facility | 13-DEC-08:61 | 0.00 | 0.00 | 352369.28 | 0.00 | 0.00 | 0.00 | 435.41 | 5793.92 | 1460.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4245.00 | 0.00 | -10854.28 | -344959.94 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2020-06-03 19:19:46
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 1.7171 | 0.0000 | 29.9961 | 1.0000 | 0.4115 | 1.7171 | 0.2396 | 1.0000 | 0.4115 | 0.2396 | ||
PSZ-AC_2:2 | 0.9405 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 0.9405 | 0.2187 | 1.0000 | 0.2057 | 0.2187 | ||
PSZ-AC_3:3 | 0.9518 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 0.9518 | 0.2161 | 1.0000 | 0.2057 | 0.2161 | ||
PSZ-AC_4:4 | 0.9459 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 0.9459 | 0.2175 | 1.0000 | 0.2057 | 0.2175 | ||
PSZ-AC_5:5 | 0.9497 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 0.9497 | 0.2166 | 1.0000 | 0.2057 | 0.2166 | ||
PSZ-AC_6:6 | 1.6606 | 0.0000 | 29.9961 | 1.0000 | 0.4115 | 1.6758 | 0.2455 | 1.0000 | 0.4115 | 0.2455 | ||
PSZ-AC_7:7 | 0.8965 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 0.8965 | 0.2295 | 1.0000 | 0.2057 | 0.2295 | ||
PSZ-AC_8:8 | 0.8879 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 0.8879 | 0.2317 | 1.0000 | 0.2057 | 0.2317 | ||
PSZ-AC_9:9 | 0.8730 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 0.8730 | 0.2356 | 1.0000 | 0.2057 | 0.2356 | ||
PSZ-AC_10:10 | 0.9975 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 0.9975 | 0.2321 | 1.0000 | 0.2057 | 0.2063 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 1.7171 | 0.0000 | 29.9961 | 1.0000 | 0.4115 | 1.7171 | 1.0000 | 1.0000 | 0.4115 | 0.2396 | ||
PSZ-AC_2:2 | 0.9405 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 0.9405 | 1.0000 | 1.0000 | 0.2057 | 0.2187 | ||
PSZ-AC_3:3 | 0.9518 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 0.9518 | 1.0000 | 1.0000 | 0.2057 | 0.2161 | ||
PSZ-AC_4:4 | 0.9459 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 0.9459 | 1.0000 | 1.0000 | 0.2057 | 0.2175 | ||
PSZ-AC_5:5 | 0.9497 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 0.9497 | 1.0000 | 1.0000 | 0.2057 | 0.2166 | ||
PSZ-AC_6:6 | 1.6606 | 0.0000 | 29.9961 | 1.0000 | 0.4115 | 1.6606 | 1.0000 | 1.0000 | 0.4115 | 0.2478 | ||
PSZ-AC_7:7 | 0.8965 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 0.8965 | 1.0000 | 1.0000 | 0.2057 | 0.2295 | ||
PSZ-AC_8:8 | 0.8879 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 0.8879 | 1.0000 | 1.0000 | 0.2057 | 0.2317 | ||
PSZ-AC_9:9 | 0.8730 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 0.8730 | 1.0000 | 1.0000 | 0.2057 | 0.2356 | ||
PSZ-AC_10:10 | 0.9975 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 0.9975 | 1.0000 | 1.0000 | 0.2057 | 0.2063 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
LGSTORE1 | PSZ-AC_1:1 | 0.000000 | 29.9961 | 0.001181 | 348.39 | 0.4115 | 1.0000 | 0.4115 | 1.000 | 0.4115 |
SMSTORE1 | PSZ-AC_2:2 | 0.000000 | 14.9980 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE2 | PSZ-AC_3:3 | 0.000000 | 14.9980 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE3 | PSZ-AC_4:4 | 0.000000 | 14.9980 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE4 | PSZ-AC_5:5 | 0.000000 | 14.9980 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
LGSTORE2 | PSZ-AC_6:6 | 0.000000 | 29.9961 | 0.001181 | 348.39 | 0.4115 | 1.0000 | 0.4115 | 1.000 | 0.4115 |
SMSTORE5 | PSZ-AC_7:7 | 0.000000 | 14.9980 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE6 | PSZ-AC_8:8 | 0.000000 | 14.9980 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE7 | PSZ-AC_9:9 | 0.000000 | 14.9980 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE8 | PSZ-AC_10:10 | 0.000000 | 14.9980 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC_1:1 | 0.000000 | 30.00 | 0.001181 | 348.3864 | 0.4115 | 0.4115 | 0.4115 |
PSZ-AC_2:2 | 0.000000 | 15.00 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_3:3 | 0.000000 | 15.00 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_4:4 | 0.000000 | 15.00 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_5:5 | 0.000000 | 15.00 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_6:6 | 0.000000 | 30.00 | 0.001181 | 348.3864 | 0.4115 | 0.4115 | 0.4115 |
PSZ-AC_7:7 | 0.000000 | 15.00 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_8:8 | 0.000000 | 15.00 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_9:9 | 0.000000 | 15.00 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_10:10 | 0.000000 | 15.00 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LGSTORE1 | PSZ-AC_1:1 | 1.7171 | 1.7171 | 1.7171 | 0.4115 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE1 | PSZ-AC_2:2 | 0.9405 | 0.9405 | 0.9405 | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE2 | PSZ-AC_3:3 | 0.9518 | 0.9518 | 0.9518 | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE3 | PSZ-AC_4:4 | 0.9459 | 0.9459 | 0.9459 | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE4 | PSZ-AC_5:5 | 0.9497 | 0.9497 | 0.9497 | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
LGSTORE2 | PSZ-AC_6:6 | 1.6606 | 1.6606 | 1.6606 | 0.4115 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE5 | PSZ-AC_7:7 | 0.8965 | 0.8965 | 0.8965 | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE6 | PSZ-AC_8:8 | 0.8879 | 0.8879 | 0.8879 | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE7 | PSZ-AC_9:9 | 0.8730 | 0.8730 | 0.8730 | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE8 | PSZ-AC_10:10 | 0.9975 | 0.9975 | 0.9975 | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 1.7171 | 1.7171 | 1.7171 | 1.7171 | 0.4115 | 1.0000 |
PSZ-AC_2:2 | 0.9405 | 0.9405 | 0.9405 | 0.9405 | 0.2057 | 1.0000 |
PSZ-AC_3:3 | 0.9518 | 0.9518 | 0.9518 | 0.9518 | 0.2057 | 1.0000 |
PSZ-AC_4:4 | 0.9459 | 0.9459 | 0.9459 | 0.9459 | 0.2057 | 1.0000 |
PSZ-AC_5:5 | 0.9497 | 0.9497 | 0.9497 | 0.9497 | 0.2057 | 1.0000 |
PSZ-AC_6:6 | 1.6606 | 1.6758 | 1.6606 | 1.6606 | 0.4115 | 1.0000 |
PSZ-AC_7:7 | 0.8965 | 0.8965 | 0.8965 | 0.8965 | 0.2057 | 1.0000 |
PSZ-AC_8:8 | 0.8879 | 0.8879 | 0.8879 | 0.8879 | 0.2057 | 1.0000 |
PSZ-AC_9:9 | 0.8730 | 0.8730 | 0.8730 | 0.8730 | 0.2057 | 1.0000 |
PSZ-AC_10:10 | 0.9975 | 0.9975 | 0.9975 | 0.9975 | 0.2057 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LGSTORE1 | PSZ-AC_1:1 | 1.7171 | 1.7171 | 1.7171 | 0.4115 | 0.2483 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE1 | PSZ-AC_2:2 | 0.9405 | 0.9405 | 0.9405 | 0.2057 | 0.2507 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE2 | PSZ-AC_3:3 | 0.9518 | 0.9518 | 0.9518 | 0.2057 | 0.2481 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE3 | PSZ-AC_4:4 | 0.9459 | 0.9459 | 0.9459 | 0.2057 | 0.2471 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE4 | PSZ-AC_5:5 | 0.9497 | 0.9497 | 0.9497 | 0.2057 | 0.2449 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
LGSTORE2 | PSZ-AC_6:6 | 1.6606 | 1.6606 | 1.6606 | 0.4115 | 0.2581 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE5 | PSZ-AC_7:7 | 0.8965 | 0.8965 | 0.8965 | 0.2057 | 0.2398 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE6 | PSZ-AC_8:8 | 0.8879 | 0.8879 | 0.8879 | 0.2057 | 0.2400 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE7 | PSZ-AC_9:9 | 0.8730 | 0.8730 | 0.8730 | 0.2057 | 0.2372 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE8 | PSZ-AC_10:10 | 0.9975 | 0.9975 | 0.9975 | 0.2057 | 0.2063 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 1.7171 | 1.7171 | 1.7171 | 1.7171 | 0.4115 | 1.0000 |
PSZ-AC_2:2 | 0.9405 | 0.9405 | 0.9405 | 0.9405 | 0.2057 | 1.0000 |
PSZ-AC_3:3 | 0.9518 | 0.9518 | 0.9518 | 0.9518 | 0.2057 | 1.0000 |
PSZ-AC_4:4 | 0.9459 | 0.9459 | 0.9459 | 0.9459 | 0.2057 | 1.0000 |
PSZ-AC_5:5 | 0.9497 | 0.9497 | 0.9497 | 0.9497 | 0.2057 | 1.0000 |
PSZ-AC_6:6 | 1.6606 | 1.6606 | 1.6606 | 1.6606 | 0.4115 | 1.0000 |
PSZ-AC_7:7 | 0.8965 | 0.8965 | 0.8965 | 0.8965 | 0.2057 | 1.0000 |
PSZ-AC_8:8 | 0.8879 | 0.8879 | 0.8879 | 0.8879 | 0.2057 | 1.0000 |
PSZ-AC_9:9 | 0.8730 | 0.8730 | 0.8730 | 0.8730 | 0.2057 | 1.0000 |
PSZ-AC_10:10 | 0.9975 | 0.9975 | 0.9975 | 0.9975 | 0.2057 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2020-06-03 19:19:46
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Rochester International Arpt MN USA TMY3 WMO#=726440 |
Total gross floor area [m2] | 2090.32 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
LGSTORE1 | 348.39 | 348.39 | 0.00 | 112.00 |
SMSTORE1 | 174.19 | 174.19 | 0.00 | 112.00 |
SMSTORE2 | 174.19 | 174.19 | 0.00 | 84.29 |
SMSTORE3 | 174.19 | 174.19 | 0.00 | 84.29 |
SMSTORE4 | 174.19 | 174.19 | 0.00 | 84.29 |
LGSTORE2 | 348.39 | 348.39 | 0.00 | 77.29 |
SMSTORE5 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE6 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE7 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE8 | 174.19 | 174.19 | 0.00 | 77.29 |
Totals | 2090.32 | 2090.32 | 0.00 |
Data | |
Number of hours heating loads not met | 0.33 |
Number of hours cooling loads not met | 0.67 |
Number of hours not met | 1.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Fuel Use [GJ] | Additional Fuel Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- Not Subdivided | 0.00 | 0.00 | 908.64 | 363273.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- Not Subdivided | 79.57 | 51271.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 502.03 | 31196.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 91.12 | 6944.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 128.72 | 8089.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 96.12 | 10318.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 66.31 | 11887.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 128.72 | 963.87 |
Natural Gas | 0.00 | 908.64 |
Additional | 0.00 | 0.00 |
Total | 128.72 | 1872.51 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 240.17 |
Space Heating | 0.00 |
Space Cooling | 38.07 |
Fans (All) | 45.98 |
Service Water Heating | 31.72 |
Receptacle Equipment | 61.58 |
Miscellaneous (All) | 461.11 |
Subtotal | 461.11 |
Natural Gas [MJ/m2] | |
Space Heating | 434.69 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 434.69 |
Subtotal | 434.69 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 26.81 |
Space Heating | 48.52 |
Space Cooling | 4.25 |
Fans (All) | 5.13 |
Service Water Heating | 3.54 |
Receptacle Equipment | 6.87 |
Miscellaneous | 4.87 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
TYPE1_OCC_SCH | 1630. | 5840. |
TYPE2_OCC_SCH | 995. | 4429. |
TYPE3_OCC_SCH | 1709. | 4064. |
TYPE1_LIGHT_SCH | 5131. | 8760. |
TYPE2_LIGHT_SCH | 4096. | 8760. |
TYPE3_LIGHT_SCH | 3767. | 8760. |
TYPE1_EQUIP_SCH | 4888. | 8760. |
TYPE2_EQUIP_SCH | 3911. | 8760. |
TYPE3_EQUIP_SCH | 3600. | 8760. |
TYPE1_INFIL_SCH | 4302. | 8760. |
TYPE2_INFIL_SCH | 5164. | 8760. |
TYPE3_INFIL_SCH | 5438. | 8760. |
INFIL_DOOR_OPENING_SCH | 2477. | 4380. |
TYPE1_MINOA_MOTORIZEDDAMPER_SCH | 5579. | 5579. |
TYPE2_MINOA_MOTORIZEDDAMPER_SCH | 4429. | 4429. |
TYPE3_MINOA_MOTORIZEDDAMPER_SCH | 4064. | 4064. |
TYPE1_SWH_SCH | 2063. | 6048. |
TYPE2_SWH_SCH | 1831. | 4429. |
TYPE3_SWH_SCH | 1733. | 4064. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 7118. | 8760. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 5839. | 5839. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 7300. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
TYPE1_HTGSETP_SCH_YES_OPTIMUM | LGSTORE1 DUALSPSCHED | January | 21.11 | 365 | 21.11 | 365 |
TYPE1_CLGSETP_SCH_YES_OPTIMUM | LGSTORE1 DUALSPSCHED | July | 23.89 | 365 | 23.89 | 365 |
TYPE2_HTGSETP_SCH_YES_OPTIMUM | SMSTORE2 DUALSPSCHED | January | 21.11 | 365 | 15.56 | 365 |
TYPE2_CLGSETP_SCH_YES_OPTIMUM | SMSTORE2 DUALSPSCHED | July | 23.89 | 365 | 29.44 | 365 |
TYPE3_HTGSETP_SCH_YES_OPTIMUM | LGSTORE2 DUALSPSCHED | January | 21.11 | 365 | 15.56 | 365 |
TYPE3_CLGSETP_SCH_YES_OPTIMUM | LGSTORE2 DUALSPSCHED | July | 23.89 | 365 | 29.44 | 365 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Meter
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.241658E+12 |
February | 0.000 | 0.172382E+12 |
March | 0.000 | 0.112728E+12 |
April | 0.000 | 0.561465E+11 |
May | 0.000 | 0.365939E+10 |
June | 0.000 | 0.584229E+09 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.316111E+10 |
October | 0.000 | 0.252103E+11 |
November | 0.000 | 0.103874E+12 |
December | 0.000 | 0.189231E+12 |
Annual Sum or Average | 0.908635E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.241658E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Meter
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.241658E+12 |
February | 0.000 | 0.172382E+12 |
March | 0.000 | 0.112728E+12 |
April | 0.000 | 0.561465E+11 |
May | 0.000 | 0.365939E+10 |
June | 0.000 | 0.584229E+09 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.316111E+10 |
October | 0.000 | 0.252103E+11 |
November | 0.000 | 0.103874E+12 |
December | 0.000 | 0.189231E+12 |
Annual Sum or Average | 0.908635E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.241658E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2015
For: Meter
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.241658E+12 |
February | 0.000 | 0.172382E+12 |
March | 0.000 | 0.112728E+12 |
April | 0.000 | 0.561465E+11 |
May | 0.000 | 0.365939E+10 |
June | 0.000 | 0.584229E+09 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.316111E+10 |
October | 0.000 | 0.252103E+11 |
November | 0.000 | 0.103874E+12 |
December | 0.000 | 0.189231E+12 |
Annual Sum or Average | 0.908635E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.241658E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Meter
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.241658E+12 |
February | 0.000 | 0.172382E+12 |
March | 0.000 | 0.112728E+12 |
April | 0.000 | 0.561465E+11 |
May | 0.000 | 0.365939E+10 |
June | 0.000 | 0.584229E+09 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.316111E+10 |
October | 0.000 | 0.252103E+11 |
November | 0.000 | 0.103874E+12 |
December | 0.000 | 0.189231E+12 |
Annual Sum or Average | 0.908635E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.241658E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTRIPMALL
For: Meter
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.241658E+12 |
February | 0.000 | 0.172382E+12 |
March | 0.000 | 0.112728E+12 |
April | 0.000 | 0.561465E+11 |
May | 0.000 | 0.365939E+10 |
June | 0.000 | 0.584229E+09 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.316111E+10 |
October | 0.000 | 0.252103E+11 |
November | 0.000 | 0.103874E+12 |
December | 0.000 | 0.189231E+12 |
Annual Sum or Average | 0.908635E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.241658E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.241658E+12 |
February | 0.000 | 0.172382E+12 |
March | 0.000 | 0.112728E+12 |
April | 0.000 | 0.561465E+11 |
May | 0.000 | 0.365939E+10 |
June | 0.000 | 0.584229E+09 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.316111E+10 |
October | 0.000 | 0.252103E+11 |
November | 0.000 | 0.103874E+12 |
December | 0.000 | 0.189231E+12 |
Annual Sum or Average | 0.908635E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.241658E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.241658E+12 |
February | 0.000 | 0.172382E+12 |
March | 0.000 | 0.112728E+12 |
April | 0.000 | 0.561465E+11 |
May | 0.000 | 0.365939E+10 |
June | 0.000 | 0.584229E+09 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.316111E+10 |
October | 0.000 | 0.252103E+11 |
November | 0.000 | 0.103874E+12 |
December | 0.000 | 0.189231E+12 |
Annual Sum or Average | 0.908635E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.241658E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 6A
For: Meter
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.241658E+12 |
February | 0.000 | 0.172382E+12 |
March | 0.000 | 0.112728E+12 |
April | 0.000 | 0.561465E+11 |
May | 0.000 | 0.365939E+10 |
June | 0.000 | 0.584229E+09 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.316111E+10 |
October | 0.000 | 0.252103E+11 |
November | 0.000 | 0.103874E+12 |
December | 0.000 | 0.189231E+12 |
Annual Sum or Average | 0.908635E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.241658E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_ROCHESTER
For: Meter
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.241658E+12 |
February | 0.000 | 0.172382E+12 |
March | 0.000 | 0.112728E+12 |
April | 0.000 | 0.561465E+11 |
May | 0.000 | 0.365939E+10 |
June | 0.000 | 0.584229E+09 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.316111E+10 |
October | 0.000 | 0.252103E+11 |
November | 0.000 | 0.103874E+12 |
December | 0.000 | 0.189231E+12 |
Annual Sum or Average | 0.908635E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.241658E+12 |
Report: ZoneCoolingSummaryMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.423612E+09 | 20677.29 | 06-JAN-00:01 | -25.1 | -25.3 | 0.566349E+09 | 680.12 | 21-JAN-13:09 | -5.9 | -6.6 |
February | 0.633166E+09 | 24267.47 | 03-FEB-00:01 | -32.8 | -32.9 | 0.511446E+09 | 680.12 | 19-FEB-13:09 | 2.30 | 0.38 |
March | 0.162278E+10 | 13976.72 | 07-MAR-21:12 | -10.8 | -11.8 | 0.567936E+09 | 839.68 | 19-MAR-17:40 | 16.83 | 12.88 |
April | 0.356602E+10 | 11449.28 | 01-APR-08:04 | -3.4 | -4.3 | 0.589499E+09 | 898.97 | 16-APR-16:30 | 28.60 | 20.42 |
May | 0.661320E+10 | 23747.95 | 31-MAY-08:62 | 23.77 | 18.95 | 0.703680E+09 | 899.01 | 14-MAY-12:30 | 20.00 | 14.49 |
June | 0.106989E+11 | 28479.68 | 17-JUN-08:62 | 20.97 | 16.70 | 0.703536E+09 | 898.98 | 11-JUN-17:00 | 31.10 | 23.54 |
July | 0.128734E+11 | 31862.24 | 18-JUL-08:62 | 19.18 | 13.66 | 0.753965E+09 | 899.02 | 30-JUL-17:40 | 25.37 | 19.16 |
August | 0.131286E+11 | 30606.04 | 15-AUG-08:62 | 17.48 | 14.95 | 0.743487E+09 | 899.02 | 06-AUG-16:10 | 18.48 | 11.67 |
September | 0.107332E+11 | 30744.09 | 12-SEP-08:62 | 15.50 | 14.84 | 0.693351E+09 | 899.03 | 02-SEP-12:09 | 25.68 | 16.85 |
October | 0.600534E+10 | 9161.78 | 26-OCT-08:02 | 1.28 | -0.1 | 0.611731E+09 | 899.00 | 20-OCT-12:00 | 21.80 | 12.59 |
November | 0.263834E+10 | 15210.67 | 25-NOV-00:01 | -13.4 | -13.7 | 0.559864E+09 | 826.29 | 03-NOV-12:00 | 15.60 | 11.01 |
December | 0.660780E+09 | 19597.23 | 09-DEC-00:01 | -22.8 | -23.0 | 0.569367E+09 | 680.12 | 16-DEC-13:20 | -4.4 | -5.9 |
Annual Sum or Average | 0.695973E+11 | 0.757421E+10 | ||||||||
Minimum of Months | 0.423612E+09 | 9161.78 | -32.8 | -32.9 | 0.511446E+09 | 680.12 | -5.9 | -6.6 | ||
Maximum of Months | 0.131286E+11 | 31862.24 | 23.77 | 18.95 | 0.753965E+09 | 899.03 | 31.10 | 23.54 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 92721944.86 | 8219.06 | 04-JAN-19:42 | -16.4 | -16.7 | 0.285245E+09 | 360.43 | 01-JAN-18:00 | -1.1 | -1.4 |
February | 0.251547E+09 | 6724.08 | 17-FEB-09:04 | -7.8 | -8.7 | 0.260472E+09 | 381.81 | 20-FEB-18:00 | -1.1 | -3.4 |
March | 0.878838E+09 | 6665.41 | 13-MAR-08:04 | -7.7 | -9.1 | 0.294222E+09 | 449.49 | 19-MAR-17:49 | 16.47 | 12.67 |
April | 0.194199E+10 | 11104.83 | 18-APR-20:10 | 18.03 | 14.93 | 0.307830E+09 | 449.51 | 16-APR-17:00 | 26.70 | 19.82 |
May | 0.385644E+10 | 14927.27 | 21-MAY-17:08 | 17.70 | 9.57 | 0.362120E+09 | 449.51 | 14-MAY-12:09 | 19.60 | 14.24 |
June | 0.603846E+10 | 17043.21 | 20-JUN-08:62 | 20.78 | 14.78 | 0.356038E+09 | 449.51 | 23-JUN-12:00 | 23.90 | 14.87 |
July | 0.726097E+10 | 17867.60 | 18-JUL-08:62 | 19.18 | 13.66 | 0.375493E+09 | 449.49 | 01-JUL-12:30 | 25.85 | 17.34 |
August | 0.730038E+10 | 17395.72 | 30-AUG-08:62 | 16.88 | 14.39 | 0.370313E+09 | 449.51 | 06-AUG-16:10 | 18.48 | 11.67 |
September | 0.577333E+10 | 17166.23 | 12-SEP-08:62 | 15.50 | 14.84 | 0.351787E+09 | 449.52 | 03-SEP-12:09 | 17.98 | 13.18 |
October | 0.284689E+10 | 4496.45 | 23-OCT-08:61 | 0.70 | -1.0 | 0.325175E+09 | 449.50 | 21-OCT-12:00 | 19.60 | 13.31 |
November | 0.115346E+10 | 8583.36 | 26-NOV-09:04 | -22.7 | -23.1 | 0.292963E+09 | 449.48 | 05-NOV-17:00 | 8.30 | 6.40 |
December | 0.216662E+09 | 7448.19 | 27-DEC-09:04 | -11.1 | -11.5 | 0.289939E+09 | 391.23 | 03-DEC-18:00 | 0.60 | -0.6 |
Annual Sum or Average | 0.376117E+11 | 0.387160E+10 | ||||||||
Minimum of Months | 92721944.86 | 4496.45 | -22.7 | -23.1 | 0.260472E+09 | 360.43 | -1.1 | -3.4 | ||
Maximum of Months | 0.730038E+10 | 17867.60 | 20.78 | 14.93 | 0.375493E+09 | 449.52 | 26.70 | 19.82 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 34433596.74 | 8567.25 | 25-JAN-08:04 | -16.6 | -16.9 | 0.169002E+09 | 340.06 | 21-JAN-13:09 | -5.9 | -6.6 |
February | 0.116740E+09 | 8429.28 | 28-FEB-08:04 | -16.0 | -16.5 | 0.153526E+09 | 340.06 | 25-FEB-13:00 | 5.00 | 2.56 |
March | 0.578731E+09 | 6800.75 | 16-MAR-07:04 | -8.2 | -9.4 | 0.175314E+09 | 340.06 | 18-MAR-12:00 | 11.10 | 7.72 |
April | 0.136500E+10 | 6385.91 | 03-APR-07:04 | -6.6 | -7.4 | 0.177713E+09 | 449.45 | 15-APR-12:09 | 27.88 | 20.23 |
May | 0.265819E+10 | 14099.39 | 31-MAY-07:03 | 21.05 | 17.89 | 0.215584E+09 | 449.50 | 13-MAY-12:09 | 16.37 | 15.31 |
June | 0.441819E+10 | 18431.00 | 21-JUN-07:02 | 15.37 | 13.88 | 0.217407E+09 | 449.48 | 24-JUN-12:00 | 26.70 | 20.20 |
July | 0.511280E+10 | 17892.71 | 19-JUL-07:02 | 17.07 | 14.57 | 0.223952E+09 | 449.49 | 01-JUL-12:30 | 25.85 | 17.34 |
August | 0.535402E+10 | 20551.77 | 06-AUG-08:62 | 12.80 | 11.04 | 0.230036E+09 | 449.50 | 19-AUG-12:00 | 19.40 | 18.26 |
September | 0.422956E+10 | 18104.77 | 13-SEP-07:02 | 15.10 | 14.34 | 0.208270E+09 | 449.51 | 02-SEP-12:09 | 25.68 | 16.85 |
October | 0.221021E+10 | 4358.24 | 31-OCT-07:02 | 1.28 | 0.03 | 0.182272E+09 | 449.49 | 21-OCT-12:20 | 19.13 | 13.02 |
November | 0.891983E+09 | 7140.41 | 21-NOV-08:04 | -10.0 | -10.7 | 0.167595E+09 | 406.14 | 04-NOV-12:00 | 13.90 | 6.79 |
December | 68853656.00 | 8200.23 | 07-DEC-08:04 | -14.4 | -15.2 | 0.168814E+09 | 340.06 | 16-DEC-13:20 | -4.4 | -5.9 |
Annual Sum or Average | 0.270387E+11 | 0.228949E+10 | ||||||||
Minimum of Months | 34433596.74 | 4358.24 | -16.6 | -16.9 | 0.153526E+09 | 340.06 | -5.9 | -6.6 | ||
Maximum of Months | 0.535402E+10 | 20551.77 | 21.05 | 17.89 | 0.230036E+09 | 449.51 | 27.88 | 20.23 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 27613812.58 | 8412.62 | 25-JAN-08:04 | -16.6 | -16.9 | 0.169001E+09 | 340.06 | 21-JAN-13:09 | -5.9 | -6.6 |
February | 94795621.47 | 8439.49 | 28-FEB-08:04 | -16.0 | -16.5 | 0.153519E+09 | 340.06 | 25-FEB-13:09 | 4.50 | 2.48 |
March | 0.496714E+09 | 6764.90 | 16-MAR-07:04 | -8.2 | -9.4 | 0.175064E+09 | 340.06 | 11-MAR-13:09 | 3.98 | 1.28 |
April | 0.126645E+10 | 6054.16 | 04-APR-07:04 | -4.8 | -5.6 | 0.177258E+09 | 449.45 | 15-APR-12:09 | 27.88 | 20.23 |
May | 0.252731E+10 | 13957.12 | 31-MAY-07:03 | 21.05 | 17.89 | 0.214382E+09 | 449.50 | 13-MAY-12:09 | 16.37 | 15.31 |
June | 0.438031E+10 | 18308.58 | 21-JUN-07:02 | 15.37 | 13.88 | 0.216899E+09 | 449.48 | 24-JUN-12:50 | 26.70 | 20.14 |
July | 0.511040E+10 | 17782.02 | 19-JUL-07:02 | 17.07 | 14.57 | 0.223950E+09 | 449.49 | 01-JUL-12:30 | 25.85 | 17.34 |
August | 0.533915E+10 | 20444.26 | 06-AUG-08:62 | 12.80 | 11.04 | 0.230032E+09 | 449.50 | 19-AUG-12:00 | 19.40 | 18.26 |
September | 0.417668E+10 | 17984.82 | 13-SEP-07:02 | 15.10 | 14.34 | 0.207742E+09 | 449.51 | 02-SEP-12:09 | 25.68 | 16.85 |
October | 0.200914E+10 | 4489.62 | 16-OCT-07:03 | 0.92 | -0.0 | 0.180789E+09 | 449.49 | 21-OCT-12:50 | 19.48 | 13.23 |
November | 0.813168E+09 | 7178.18 | 21-NOV-08:04 | -10.0 | -10.7 | 0.166675E+09 | 399.27 | 04-NOV-12:00 | 13.90 | 6.79 |
December | 55445659.72 | 8157.42 | 07-DEC-08:04 | -14.4 | -15.2 | 0.168806E+09 | 340.06 | 16-DEC-13:20 | -4.4 | -5.9 |
Annual Sum or Average | 0.262972E+11 | 0.228412E+10 | ||||||||
Minimum of Months | 27613812.58 | 4489.62 | -16.6 | -16.9 | 0.153519E+09 | 340.06 | -5.9 | -6.6 | ||
Maximum of Months | 0.533915E+10 | 20444.26 | 21.05 | 17.89 | 0.230032E+09 | 449.51 | 27.88 | 20.23 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 20176347.37 | 7883.88 | 21-JAN-08:04 | -13.7 | -14.0 | 0.168999E+09 | 340.06 | 21-JAN-13:09 | -5.9 | -6.6 |
February | 63624464.06 | 8123.96 | 28-FEB-08:04 | -16.0 | -16.5 | 0.153516E+09 | 340.06 | 25-FEB-13:09 | 4.50 | 2.48 |
March | 0.396526E+09 | 6539.47 | 21-MAR-07:03 | -7.1 | -8.4 | 0.174792E+09 | 340.06 | 11-MAR-13:09 | 3.98 | 1.28 |
April | 0.113142E+10 | 6011.25 | 04-APR-07:04 | -4.8 | -5.6 | 0.176664E+09 | 449.46 | 15-APR-12:09 | 27.88 | 20.23 |
May | 0.232726E+10 | 13571.51 | 31-MAY-07:03 | 21.05 | 17.89 | 0.212290E+09 | 449.50 | 27-MAY-12:09 | 20.28 | 16.28 |
June | 0.421245E+10 | 18277.88 | 21-JUN-07:02 | 15.37 | 13.88 | 0.216257E+09 | 449.46 | 17-JUN-12:09 | 26.02 | 17.80 |
July | 0.495169E+10 | 17748.58 | 19-JUL-07:02 | 17.07 | 14.57 | 0.223922E+09 | 449.49 | 01-JUL-12:30 | 25.85 | 17.34 |
August | 0.517583E+10 | 20448.58 | 06-AUG-08:62 | 12.80 | 11.04 | 0.230000E+09 | 449.50 | 19-AUG-12:00 | 19.40 | 18.26 |
September | 0.401793E+10 | 17971.31 | 13-SEP-07:02 | 15.10 | 14.34 | 0.207029E+09 | 449.51 | 02-SEP-12:09 | 25.68 | 16.85 |
October | 0.179059E+10 | 4666.48 | 28-OCT-07:03 | 0.05 | -1.5 | 0.179470E+09 | 449.49 | 21-OCT-12:00 | 19.60 | 13.31 |
November | 0.722549E+09 | 6542.24 | 22-NOV-08:04 | -7.1 | -8.3 | 0.165880E+09 | 392.09 | 04-NOV-12:00 | 13.90 | 6.79 |
December | 31254732.72 | 6756.07 | 04-DEC-08:04 | -8.0 | -8.3 | 0.168800E+09 | 340.06 | 16-DEC-13:20 | -4.4 | -5.9 |
Annual Sum or Average | 0.248413E+11 | 0.227762E+10 | ||||||||
Minimum of Months | 20176347.37 | 4666.48 | -16.0 | -16.5 | 0.153516E+09 | 340.06 | -5.9 | -6.6 | ||
Maximum of Months | 0.517583E+10 | 20448.58 | 21.05 | 17.89 | 0.230000E+09 | 449.51 | 27.88 | 20.23 |
Report: ZoneCoolingSummaryMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 19000908.44 | 13341.06 | 05-JAN-09:05 | -22.4 | -22.7 | 0.577624E+09 | 906.81 | 21-JAN-15:00 | -4.4 | -5.3 |
February | 55594951.46 | 11436.54 | 09-FEB-09:04 | -3.6 | -3.8 | 0.525915E+09 | 906.82 | 25-FEB-15:00 | 5.60 | 2.86 |
March | 0.499836E+09 | 10630.80 | 11-MAR-09:04 | -1.9 | -3.5 | 0.599220E+09 | 1053.67 | 25-MAR-14:00 | 18.90 | 10.41 |
April | 0.169906E+10 | 11422.86 | 01-APR-08:04 | -3.4 | -4.3 | 0.603160E+09 | 1198.53 | 15-APR-14:09 | 29.50 | 20.38 |
May | 0.370732E+10 | 23318.45 | 31-MAY-08:62 | 23.77 | 18.95 | 0.712594E+09 | 1198.66 | 06-MAY-14:00 | 21.10 | 11.56 |
June | 0.703361E+10 | 28855.21 | 20-JUN-08:62 | 20.78 | 14.78 | 0.737659E+09 | 1198.63 | 17-JUN-14:09 | 24.18 | 18.98 |
July | 0.832528E+10 | 31189.95 | 18-JUL-08:62 | 19.18 | 13.66 | 0.766729E+09 | 1198.65 | 01-JUL-14:00 | 27.20 | 19.05 |
August | 0.872563E+10 | 31776.85 | 06-AUG-09:02 | 12.80 | 10.33 | 0.789052E+09 | 1198.66 | 19-AUG-14:09 | 18.98 | 18.58 |
September | 0.664559E+10 | 31471.38 | 03-SEP-09:02 | 17.38 | 12.75 | 0.706562E+09 | 1198.66 | 23-SEP-14:00 | 20.60 | 11.38 |
October | 0.265192E+10 | 9269.18 | 23-OCT-08:03 | 0.70 | -1.0 | 0.607600E+09 | 1198.68 | 21-OCT-14:50 | 20.98 | 14.32 |
November | 0.105039E+10 | 11516.54 | 12-NOV-10:04 | -3.6 | -5.1 | 0.562240E+09 | 1061.65 | 04-NOV-14:00 | 14.40 | 6.79 |
December | 25742621.61 | 10384.92 | 01-DEC-09:04 | -3.3 | -4.5 | 0.578609E+09 | 906.82 | 02-DEC-15:00 | 5.60 | 3.09 |
Annual Sum or Average | 0.404390E+11 | 0.776696E+10 | ||||||||
Minimum of Months | 19000908.44 | 9269.18 | -22.4 | -22.7 | 0.525915E+09 | 906.81 | -4.4 | -5.3 | ||
Maximum of Months | 0.872563E+10 | 31776.85 | 23.77 | 18.95 | 0.789052E+09 | 1198.68 | 29.50 | 20.38 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 7982657.44 | 5835.95 | 12-JAN-09:04 | -4.1 | -4.6 | 0.288811E+09 | 453.40 | 21-JAN-15:00 | -4.4 | -5.3 |
February | 24463295.82 | 5732.53 | 09-FEB-09:04 | -3.6 | -3.8 | 0.262956E+09 | 453.41 | 25-FEB-15:00 | 5.60 | 2.86 |
March | 0.226698E+09 | 5808.27 | 10-MAR-09:04 | -4.0 | -5.1 | 0.299480E+09 | 522.29 | 25-MAR-14:00 | 18.90 | 10.41 |
April | 0.812721E+09 | 5702.91 | 04-APR-08:04 | -3.7 | -5.0 | 0.301235E+09 | 599.27 | 15-APR-14:09 | 29.50 | 20.38 |
May | 0.177668E+10 | 12300.99 | 31-MAY-08:62 | 23.77 | 18.95 | 0.354306E+09 | 599.33 | 06-MAY-14:00 | 21.10 | 11.56 |
June | 0.356157E+10 | 14810.89 | 17-JUN-08:62 | 20.97 | 16.70 | 0.368467E+09 | 599.31 | 17-JUN-14:09 | 24.18 | 18.98 |
July | 0.425779E+10 | 16527.44 | 18-JUL-08:62 | 19.18 | 13.66 | 0.383350E+09 | 599.33 | 01-JUL-14:00 | 27.20 | 19.05 |
August | 0.446124E+10 | 15766.76 | 15-AUG-08:62 | 17.48 | 14.95 | 0.394521E+09 | 599.33 | 19-AUG-14:09 | 18.98 | 18.58 |
September | 0.335484E+10 | 16235.07 | 12-SEP-08:62 | 15.50 | 14.84 | 0.353018E+09 | 599.33 | 23-SEP-14:00 | 20.60 | 11.38 |
October | 0.124150E+10 | 4619.27 | 23-OCT-08:03 | 0.70 | -1.0 | 0.303341E+09 | 599.33 | 21-OCT-14:00 | 21.10 | 14.39 |
November | 0.495374E+09 | 5728.46 | 12-NOV-10:04 | -3.6 | -5.1 | 0.281000E+09 | 528.21 | 04-NOV-14:00 | 14.40 | 6.79 |
December | 10348714.60 | 5873.47 | 08-DEC-09:04 | -5.0 | -5.6 | 0.289304E+09 | 453.41 | 16-DEC-15:09 | -2.8 | -4.1 |
Annual Sum or Average | 0.202312E+11 | 0.387979E+10 | ||||||||
Minimum of Months | 7982657.44 | 4619.27 | -5.0 | -5.6 | 0.262956E+09 | 453.40 | -4.4 | -5.3 | ||
Maximum of Months | 0.446124E+10 | 16527.44 | 23.77 | 18.95 | 0.394521E+09 | 599.33 | 29.50 | 20.38 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 5972051.25 | 5820.82 | 12-JAN-09:04 | -4.1 | -4.6 | 0.288811E+09 | 453.40 | 21-JAN-15:00 | -4.4 | -5.3 |
February | 20399643.91 | 5719.92 | 09-FEB-09:04 | -3.6 | -3.8 | 0.262955E+09 | 453.41 | 25-FEB-15:00 | 5.60 | 2.86 |
March | 0.204796E+09 | 5799.83 | 10-MAR-09:04 | -4.0 | -5.1 | 0.299304E+09 | 518.83 | 25-MAR-14:00 | 18.90 | 10.41 |
April | 0.760199E+09 | 5724.36 | 01-APR-08:04 | -3.4 | -4.3 | 0.300733E+09 | 599.27 | 15-APR-14:09 | 29.50 | 20.38 |
May | 0.167642E+10 | 11715.31 | 31-MAY-08:62 | 23.77 | 18.95 | 0.351159E+09 | 599.33 | 06-MAY-14:00 | 21.10 | 11.56 |
June | 0.346736E+10 | 14158.02 | 17-JUN-08:62 | 20.97 | 16.70 | 0.367827E+09 | 599.31 | 17-JUN-14:09 | 24.18 | 18.98 |
July | 0.417165E+10 | 16344.96 | 18-JUL-08:62 | 19.18 | 13.66 | 0.383308E+09 | 599.33 | 01-JUL-14:00 | 27.20 | 19.05 |
August | 0.437735E+10 | 15591.99 | 15-AUG-08:62 | 17.48 | 14.95 | 0.394502E+09 | 599.33 | 19-AUG-14:09 | 18.98 | 18.58 |
September | 0.327857E+10 | 16066.17 | 12-SEP-08:62 | 15.50 | 14.84 | 0.352359E+09 | 599.33 | 23-SEP-14:00 | 20.60 | 11.38 |
October | 0.116933E+10 | 4658.21 | 23-OCT-08:03 | 0.70 | -1.0 | 0.302640E+09 | 599.33 | 21-OCT-14:00 | 21.10 | 14.39 |
November | 0.471771E+09 | 5773.36 | 12-NOV-10:04 | -3.6 | -5.1 | 0.280764E+09 | 524.36 | 04-NOV-14:00 | 14.40 | 6.79 |
December | 8941187.49 | 5642.88 | 01-DEC-09:04 | -3.3 | -4.5 | 0.289303E+09 | 453.41 | 16-DEC-15:09 | -2.8 | -4.1 |
Annual Sum or Average | 0.196127E+11 | 0.387366E+10 | ||||||||
Minimum of Months | 5972051.25 | 4658.21 | -4.1 | -5.1 | 0.262955E+09 | 453.40 | -4.4 | -5.3 | ||
Maximum of Months | 0.437735E+10 | 16344.96 | 23.77 | 18.95 | 0.394502E+09 | 599.33 | 29.50 | 20.38 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 4637000.81 | 5180.03 | 14-JAN-09:04 | -3.8 | -4.0 | 0.288811E+09 | 453.40 | 21-JAN-15:00 | -4.4 | -5.3 |
February | 11138816.93 | 5695.65 | 09-FEB-09:04 | -3.6 | -3.8 | 0.262951E+09 | 453.41 | 25-FEB-15:20 | 5.60 | 2.70 |
March | 0.142227E+09 | 5164.00 | 22-MAR-08:04 | -1.4 | -3.1 | 0.298830E+09 | 507.75 | 25-MAR-14:00 | 18.90 | 10.41 |
April | 0.616124E+09 | 5640.69 | 01-APR-08:04 | -3.4 | -4.3 | 0.299367E+09 | 599.27 | 15-APR-14:09 | 29.50 | 20.38 |
May | 0.145323E+10 | 6060.31 | 31-MAY-08:62 | 23.77 | 18.95 | 0.344135E+09 | 599.33 | 27-MAY-14:20 | 21.10 | 16.83 |
June | 0.323543E+10 | 12757.63 | 12-JUN-08:62 | 19.50 | 18.00 | 0.366290E+09 | 599.32 | 17-JUN-14:09 | 24.18 | 18.98 |
July | 0.397099E+10 | 15217.02 | 18-JUL-08:62 | 19.18 | 13.66 | 0.383150E+09 | 599.33 | 01-JUL-14:00 | 27.20 | 19.05 |
August | 0.418965E+10 | 14203.29 | 29-AUG-08:62 | 19.08 | 16.09 | 0.394440E+09 | 599.33 | 19-AUG-14:09 | 18.98 | 18.58 |
September | 0.310164E+10 | 15704.06 | 12-SEP-08:62 | 15.50 | 14.84 | 0.350815E+09 | 599.33 | 23-SEP-14:00 | 20.60 | 11.38 |
October | 0.974477E+09 | 4734.55 | 23-OCT-08:03 | 0.70 | -1.0 | 0.300991E+09 | 599.32 | 21-OCT-14:39 | 20.87 | 14.25 |
November | 0.394096E+09 | 5719.67 | 12-NOV-10:04 | -3.6 | -5.1 | 0.280271E+09 | 515.49 | 04-NOV-14:00 | 14.40 | 6.79 |
December | 5034958.82 | 5608.66 | 01-DEC-09:04 | -3.3 | -4.5 | 0.289301E+09 | 453.41 | 16-DEC-15:09 | -2.8 | -4.1 |
Annual Sum or Average | 0.180987E+11 | 0.385935E+10 | ||||||||
Minimum of Months | 4637000.81 | 4734.55 | -3.8 | -5.1 | 0.262951E+09 | 453.40 | -4.4 | -5.3 | ||
Maximum of Months | 0.418965E+10 | 15704.06 | 23.77 | 18.95 | 0.394440E+09 | 599.33 | 29.50 | 20.38 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 795479.77 | 4937.09 | 13-JAN-09:04 | -0.5 | -1.5 | 0.288812E+09 | 453.40 | 21-JAN-15:00 | -4.4 | -5.3 |
February | 3904136.51 | 4953.38 | 26-FEB-10:04 | -1.0 | -2.4 | 0.262951E+09 | 453.41 | 18-FEB-15:09 | -6.7 | -7.5 |
March | 32921967.89 | 4668.45 | 30-MAR-08:04 | 1.10 | 0.61 | 0.298067E+09 | 475.65 | 25-MAR-14:00 | 18.90 | 10.41 |
April | 0.334118E+09 | 4860.28 | 22-APR-08:04 | 0.00 | -0.5 | 0.296659E+09 | 599.29 | 15-APR-14:09 | 29.50 | 20.38 |
May | 0.963215E+09 | 4279.96 | 31-MAY-15:00 | 30.00 | 19.68 | 0.332711E+09 | 599.33 | 06-MAY-14:00 | 21.10 | 11.56 |
June | 0.283359E+10 | 13802.98 | 28-JUN-08:62 | 24.27 | 19.17 | 0.363473E+09 | 599.32 | 17-JUN-14:09 | 24.18 | 18.98 |
July | 0.369984E+10 | 14406.41 | 01-JUL-08:62 | 23.07 | 18.40 | 0.382585E+09 | 599.31 | 22-JUL-14:00 | 20.60 | 14.31 |
August | 0.398647E+10 | 14633.11 | 23-AUG-08:62 | 18.98 | 17.57 | 0.394237E+09 | 599.33 | 19-AUG-14:20 | 19.07 | 18.58 |
September | 0.286490E+10 | 15545.57 | 08-SEP-08:62 | 22.25 | 17.67 | 0.348130E+09 | 599.33 | 23-SEP-14:00 | 20.60 | 11.38 |
October | 0.565527E+09 | 4602.90 | 26-OCT-08:04 | 1.28 | -0.1 | 0.298714E+09 | 599.32 | 21-OCT-14:00 | 21.10 | 14.39 |
November | 0.230320E+09 | 5675.36 | 12-NOV-10:04 | -3.6 | -5.1 | 0.279544E+09 | 499.24 | 04-NOV-14:00 | 14.40 | 6.79 |
December | 2274844.34 | 4900.48 | 30-DEC-09:04 | -1.1 | -1.8 | 0.289301E+09 | 453.41 | 16-DEC-15:09 | -2.8 | -4.1 |
Annual Sum or Average | 0.155179E+11 | 0.383519E+10 | ||||||||
Minimum of Months | 795479.77 | 4279.96 | -3.6 | -5.1 | 0.262951E+09 | 453.40 | -6.7 | -7.5 | ||
Maximum of Months | 0.398647E+10 | 15545.57 | 30.00 | 19.68 | 0.394237E+09 | 599.33 | 29.50 | 20.38 |
Report: ZoneHeatingSummaryMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.124020E+11 | 60811.26 | 19-JAN-00:42 | -21.5 |
February | 0.808920E+10 | 60063.04 | 04-FEB-08:61 | -30.3 |
March | 0.429844E+10 | 59964.09 | 03-MAR-08:61 | -3.9 |
April | 0.171387E+10 | 59541.01 | 03-APR-07:01 | -6.6 |
May | 97699119.01 | 52326.82 | 02-MAY-08:61 | 4.08 |
June | 67876645.17 | 1676.01 | 26-JUN-08:06 | 25.37 |
July | 62939836.77 | 1298.23 | 30-JUL-07:05 | 20.18 |
August | 66609564.08 | 1834.89 | 03-AUG-08:07 | 25.87 |
September | 76045501.22 | 51836.53 | 30-SEP-08:61 | 3.35 |
October | 0.156691E+09 | 51787.27 | 27-OCT-08:61 | 3.15 |
November | 0.371445E+10 | 59928.14 | 27-NOV-08:61 | -9.4 |
December | 0.849769E+10 | 60002.04 | 12-DEC-08:61 | -19.3 |
Annual Sum or Average | 0.392435E+11 | |||
Minimum of Months | 62939836.77 | 1298.23 | -30.3 | |
Maximum of Months | 0.124020E+11 | 60811.26 | 25.87 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.477073E+10 | 31792.27 | 06-JAN-08:61 | -28.1 |
February | 0.299041E+10 | 31801.94 | 04-FEB-08:61 | -30.3 |
March | 0.139494E+10 | 31633.42 | 06-MAR-08:61 | -11.8 |
April | 0.479093E+09 | 27323.86 | 28-APR-08:61 | 1.78 |
May | 40757078.52 | 5319.37 | 02-MAY-08:61 | 4.08 |
June | 38361109.71 | 940.52 | 26-JUN-08:06 | 25.37 |
July | 36305895.41 | 775.87 | 30-JUL-07:05 | 20.18 |
August | 38199547.00 | 889.77 | 04-AUG-08:07 | 25.78 |
September | 36645594.85 | 1329.19 | 30-SEP-08:61 | 3.35 |
October | 45907668.36 | 9681.83 | 27-OCT-08:61 | 3.15 |
November | 0.134481E+10 | 29740.86 | 28-NOV-08:61 | -16.1 |
December | 0.324346E+10 | 31778.67 | 11-DEC-08:61 | -21.7 |
Annual Sum or Average | 0.144596E+11 | |||
Minimum of Months | 36305895.41 | 775.87 | -30.3 | |
Maximum of Months | 0.477073E+10 | 31801.94 | 25.78 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.549422E+10 | 31888.48 | 08-JAN-08:61 | -11.6 |
February | 0.350751E+10 | 31909.95 | 05-FEB-08:61 | -20.4 |
March | 0.174914E+10 | 31860.45 | 06-MAR-07:01 | -12.7 |
April | 0.643646E+09 | 28270.69 | 23-APR-08:61 | 4.87 |
May | 45771944.50 | 7398.17 | 02-MAY-07:02 | 2.98 |
June | 65625130.89 | 2217.50 | 11-JUN-16:02 | 32.62 |
July | 56174015.08 | 1454.22 | 02-JUL-16:02 | 29.32 |
August | 47783131.80 | 946.66 | 27-AUG-16:03 | 27.20 |
September | 48963856.90 | 4668.47 | 30-SEP-07:02 | 0.97 |
October | 62316780.19 | 7899.99 | 08-OCT-08:62 | 5.03 |
November | 0.172415E+10 | 31780.61 | 26-NOV-08:61 | -25.2 |
December | 0.383419E+10 | 31997.04 | 11-DEC-07:01 | -21.7 |
Annual Sum or Average | 0.172795E+11 | |||
Minimum of Months | 45771944.50 | 946.66 | -25.2 | |
Maximum of Months | 0.549422E+10 | 31997.04 | 32.62 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.578579E+10 | 31810.90 | 30-JAN-07:01 | -29.0 |
February | 0.372335E+10 | 31786.94 | 05-FEB-08:61 | -20.4 |
March | 0.189935E+10 | 31738.55 | 06-MAR-07:01 | -12.7 |
April | 0.725352E+09 | 28205.22 | 23-APR-08:61 | 4.87 |
May | 49564400.35 | 11528.64 | 02-MAY-07:02 | 2.98 |
June | 65329263.24 | 2218.48 | 11-JUN-16:02 | 32.62 |
July | 55816636.14 | 1453.03 | 02-JUL-16:02 | 29.32 |
August | 47484943.56 | 947.19 | 27-AUG-16:03 | 27.20 |
September | 50258523.27 | 8056.19 | 30-SEP-07:02 | 0.97 |
October | 77660123.10 | 13348.51 | 16-OCT-07:02 | 0.92 |
November | 0.187639E+10 | 31658.94 | 26-NOV-08:61 | -25.2 |
December | 0.408135E+10 | 31876.88 | 11-DEC-07:01 | -21.7 |
Annual Sum or Average | 0.184377E+11 | |||
Minimum of Months | 47484943.56 | 947.19 | -29.0 | |
Maximum of Months | 0.578579E+10 | 31876.88 | 32.62 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.619183E+10 | 31909.08 | 30-JAN-07:01 | -29.0 |
February | 0.402768E+10 | 31921.53 | 05-FEB-08:61 | -20.4 |
March | 0.213498E+10 | 31819.38 | 06-MAR-07:01 | -12.7 |
April | 0.851378E+09 | 28350.71 | 29-APR-07:01 | 5.97 |
May | 54945445.08 | 15676.56 | 02-MAY-07:02 | 2.98 |
June | 66193792.99 | 2223.92 | 11-JUN-16:02 | 32.62 |
July | 56506965.05 | 1457.31 | 02-JUL-16:02 | 29.32 |
August | 48058881.23 | 953.07 | 27-AUG-16:03 | 27.20 |
September | 53044515.37 | 11306.36 | 30-SEP-07:02 | 0.97 |
October | 0.100819E+09 | 17821.28 | 16-OCT-07:02 | 0.92 |
November | 0.208485E+10 | 31738.92 | 26-NOV-08:61 | -25.2 |
December | 0.442683E+10 | 31948.91 | 11-DEC-07:01 | -21.7 |
Annual Sum or Average | 0.200971E+11 | |||
Minimum of Months | 48058881.23 | 953.07 | -29.0 | |
Maximum of Months | 0.619183E+10 | 31948.91 | 32.62 |
Report: ZoneHeatingSummaryMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.121509E+11 | 58836.50 | 06-JAN-08:61 | -28.1 |
February | 0.795341E+10 | 58860.28 | 04-FEB-08:61 | -30.3 |
March | 0.429834E+10 | 58767.19 | 03-MAR-08:61 | -3.9 |
April | 0.172644E+10 | 58383.46 | 03-APR-07:01 | -6.6 |
May | 0.103086E+09 | 53293.96 | 03-MAY-08:61 | 9.18 |
June | 0.111241E+09 | 4447.98 | 11-JUN-16:02 | 32.62 |
July | 90893855.93 | 2899.21 | 02-JUL-16:02 | 29.32 |
August | 79729487.28 | 1897.61 | 27-AUG-16:03 | 27.20 |
September | 93205857.18 | 50690.11 | 30-SEP-08:61 | 3.35 |
October | 0.228405E+09 | 51189.40 | 17-OCT-08:61 | 4.35 |
November | 0.415670E+10 | 58767.40 | 26-NOV-09:01 | -22.7 |
December | 0.886984E+10 | 58833.37 | 09-DEC-08:61 | -22.8 |
Annual Sum or Average | 0.398622E+11 | |||
Minimum of Months | 79729487.28 | 1897.61 | -30.3 | |
Maximum of Months | 0.121509E+11 | 58860.28 | 32.62 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.670277E+10 | 30865.31 | 06-JAN-08:61 | -28.1 |
February | 0.443572E+10 | 30935.27 | 04-FEB-08:61 | -30.3 |
March | 0.247567E+10 | 30824.18 | 03-MAR-08:61 | -3.9 |
April | 0.103480E+10 | 30612.72 | 03-APR-07:01 | -6.6 |
May | 66432488.31 | 28081.88 | 03-MAY-08:61 | 9.18 |
June | 60921025.35 | 2237.03 | 11-JUN-16:02 | 32.62 |
July | 50456040.82 | 1466.18 | 02-JUL-16:02 | 29.32 |
August | 44386732.53 | 965.64 | 27-AUG-16:03 | 27.20 |
September | 52494452.10 | 26780.23 | 30-SEP-08:61 | 3.35 |
October | 0.150305E+09 | 27029.44 | 17-OCT-08:61 | 4.35 |
November | 0.236507E+10 | 30825.01 | 26-NOV-09:01 | -22.7 |
December | 0.493143E+10 | 30868.19 | 12-DEC-08:61 | -19.3 |
Annual Sum or Average | 0.223705E+11 | |||
Minimum of Months | 44386732.53 | 965.64 | -30.3 | |
Maximum of Months | 0.670277E+10 | 30935.27 | 32.62 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.677875E+10 | 30681.04 | 06-JAN-08:61 | -28.1 |
February | 0.451364E+10 | 30710.93 | 04-FEB-08:61 | -30.3 |
March | 0.255904E+10 | 30640.26 | 03-MAR-08:61 | -3.9 |
April | 0.109339E+10 | 30432.27 | 03-APR-07:01 | -6.6 |
May | 68397997.30 | 27930.07 | 03-MAY-08:61 | 9.18 |
June | 60319251.03 | 2239.19 | 11-JUN-16:02 | 32.62 |
July | 50223207.94 | 1467.27 | 02-JUL-16:02 | 29.32 |
August | 44106024.25 | 966.98 | 27-AUG-16:03 | 27.20 |
September | 53330064.75 | 26616.30 | 30-SEP-08:61 | 3.35 |
October | 0.166237E+09 | 26867.18 | 17-OCT-08:61 | 4.35 |
November | 0.243046E+10 | 30642.22 | 26-NOV-09:01 | -22.7 |
December | 0.501427E+10 | 30723.49 | 12-DEC-08:61 | -19.3 |
Annual Sum or Average | 0.228322E+11 | |||
Minimum of Months | 44106024.25 | 966.98 | -30.3 | |
Maximum of Months | 0.677875E+10 | 30723.49 | 32.62 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.722739E+10 | 30383.32 | 24-JAN-08:61 | -16.7 |
February | 0.492385E+10 | 30380.26 | 04-FEB-08:61 | -30.3 |
March | 0.294776E+10 | 30327.66 | 03-MAR-08:61 | -3.9 |
April | 0.134472E+10 | 30133.98 | 04-APR-07:01 | -4.8 |
May | 92016488.24 | 27729.23 | 03-MAY-08:61 | 9.18 |
June | 63634669.56 | 5314.24 | 05-JUN-08:62 | 9.90 |
July | 49720184.35 | 1469.51 | 02-JUL-16:02 | 29.32 |
August | 43718849.43 | 970.32 | 27-AUG-16:03 | 27.20 |
September | 58563123.53 | 26545.48 | 29-SEP-08:61 | 5.05 |
October | 0.239463E+09 | 27125.72 | 08-OCT-09:01 | 7.45 |
November | 0.269196E+10 | 30328.21 | 26-NOV-09:01 | -22.7 |
December | 0.545235E+10 | 30396.24 | 09-DEC-08:61 | -22.8 |
Annual Sum or Average | 0.251351E+11 | |||
Minimum of Months | 43718849.43 | 970.32 | -30.3 | |
Maximum of Months | 0.722739E+10 | 30396.24 | 29.32 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.110536E+11 | 33357.82 | 29-JAN-08:22 | -22.8 |
February | 0.789054E+10 | 33225.14 | 02-FEB-01:12 | -34.1 |
March | 0.524634E+10 | 32959.01 | 03-MAR-08:61 | -3.9 |
April | 0.269591E+10 | 32813.49 | 25-APR-07:01 | 1.10 |
May | 0.250811E+09 | 30537.96 | 03-MAY-08:61 | 9.18 |
June | 0.102807E+09 | 26190.98 | 05-JUN-08:62 | 9.90 |
July | 53925445.77 | 1493.33 | 02-JUL-16:02 | 29.32 |
August | 48286216.69 | 1053.28 | 03-AUG-08:06 | 25.87 |
September | 0.103999E+09 | 29344.52 | 29-SEP-08:61 | 5.05 |
October | 0.585514E+09 | 29895.96 | 08-OCT-09:01 | 7.45 |
November | 0.425196E+10 | 33055.34 | 26-NOV-09:01 | -22.7 |
December | 0.824856E+10 | 33380.85 | 09-DEC-06:02 | -22.8 |
Annual Sum or Average | 0.405322E+11 | |||
Minimum of Months | 48286216.69 | 1053.28 | -34.1 | |
Maximum of Months | 0.110536E+11 | 33380.85 | 29.32 |
Report: ZoneElectricSummaryMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.100203E+11 | 6078.71 | 01-JAN-10:09 | 0.223514E+10 | 1348.26 | 01-JAN-10:09 |
February | 0.906661E+10 | 6078.71 | 01-FEB-10:09 | 0.202238E+10 | 1348.26 | 01-FEB-10:09 |
March | 0.100410E+11 | 6078.71 | 01-MAR-10:09 | 0.223972E+10 | 1348.26 | 01-MAR-10:09 |
April | 0.972311E+10 | 6078.71 | 01-APR-09:09 | 0.216880E+10 | 1348.26 | 01-APR-09:09 |
May | 0.100203E+11 | 6078.71 | 01-MAY-09:09 | 0.223514E+10 | 1348.26 | 01-MAY-09:09 |
June | 0.972311E+10 | 6078.71 | 01-JUN-09:09 | 0.216880E+10 | 1348.26 | 01-JUN-09:09 |
July | 0.100410E+11 | 6078.71 | 01-JUL-09:09 | 0.223972E+10 | 1348.26 | 01-JUL-09:09 |
August | 0.100203E+11 | 6078.71 | 01-AUG-09:09 | 0.223514E+10 | 1348.26 | 01-AUG-09:09 |
September | 0.974384E+10 | 6078.71 | 01-SEP-09:09 | 0.217339E+10 | 1348.26 | 01-SEP-09:09 |
October | 0.100203E+11 | 6078.71 | 01-OCT-09:09 | 0.223514E+10 | 1348.26 | 01-OCT-09:09 |
November | 0.968165E+10 | 6078.71 | 01-NOV-09:09 | 0.215964E+10 | 1348.26 | 01-NOV-09:09 |
December | 0.100617E+11 | 6078.71 | 01-DEC-10:09 | 0.224431E+10 | 1348.26 | 01-DEC-10:09 |
Annual Sum or Average | 0.118163E+12 | 0.263573E+11 | ||||
Minimum of Months | 0.906661E+10 | 6078.71 | 0.202238E+10 | 1348.26 | ||
Maximum of Months | 0.100617E+11 | 6078.71 | 0.224431E+10 | 1348.26 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.540359E+10 | 3278.04 | 01-JAN-10:09 | 0.111757E+10 | 674.13 | 01-JAN-10:09 |
February | 0.488932E+10 | 3278.04 | 01-FEB-10:09 | 0.101119E+10 | 674.13 | 01-FEB-10:09 |
March | 0.541477E+10 | 3278.04 | 01-MAR-10:09 | 0.111986E+10 | 674.13 | 01-MAR-10:09 |
April | 0.524335E+10 | 3278.04 | 01-APR-09:09 | 0.108440E+10 | 674.13 | 01-APR-09:09 |
May | 0.540359E+10 | 3278.04 | 01-MAY-09:09 | 0.111757E+10 | 674.13 | 01-MAY-09:09 |
June | 0.524335E+10 | 3278.04 | 01-JUN-09:09 | 0.108440E+10 | 674.13 | 01-JUN-09:09 |
July | 0.541477E+10 | 3278.04 | 01-JUL-09:09 | 0.111986E+10 | 674.13 | 01-JUL-09:09 |
August | 0.540359E+10 | 3278.04 | 01-AUG-09:09 | 0.111757E+10 | 674.13 | 01-AUG-09:09 |
September | 0.525453E+10 | 3278.04 | 01-SEP-09:09 | 0.108669E+10 | 674.13 | 01-SEP-09:09 |
October | 0.540359E+10 | 3278.04 | 01-OCT-09:09 | 0.111757E+10 | 674.13 | 01-OCT-09:09 |
November | 0.522099E+10 | 3278.04 | 01-NOV-09:09 | 0.107982E+10 | 674.13 | 01-NOV-09:09 |
December | 0.542595E+10 | 3278.04 | 01-DEC-10:09 | 0.112215E+10 | 674.13 | 01-DEC-10:09 |
Annual Sum or Average | 0.637214E+11 | 0.131787E+11 | ||||
Minimum of Months | 0.488932E+10 | 3278.04 | 0.101119E+10 | 674.13 | ||
Maximum of Months | 0.542595E+10 | 3278.04 | 0.112215E+10 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.379993E+10 | 2921.79 | 01-JAN-10:09 | 0.883781E+09 | 674.13 | 01-JAN-10:09 |
February | 0.344119E+10 | 2921.79 | 01-FEB-09:09 | 0.800324E+09 | 674.13 | 01-FEB-09:09 |
March | 0.387965E+10 | 2921.79 | 01-MAR-09:09 | 0.902118E+09 | 674.13 | 01-MAR-09:09 |
April | 0.368699E+10 | 2921.79 | 01-APR-08:09 | 0.857490E+09 | 674.13 | 01-APR-08:09 |
May | 0.383979E+10 | 2921.79 | 01-MAY-08:09 | 0.892950E+09 | 674.13 | 01-MAY-08:09 |
June | 0.374678E+10 | 2921.79 | 01-JUN-08:09 | 0.871243E+09 | 674.13 | 01-JUN-08:09 |
July | 0.378000E+10 | 2921.79 | 01-JUL-08:09 | 0.879197E+09 | 674.13 | 01-JUL-08:09 |
August | 0.387965E+10 | 2921.79 | 01-AUG-08:09 | 0.902118E+09 | 674.13 | 01-AUG-08:09 |
September | 0.368699E+10 | 2921.79 | 01-SEP-08:09 | 0.857490E+09 | 674.13 | 01-SEP-08:09 |
October | 0.379993E+10 | 2921.79 | 01-OCT-09:09 | 0.883781E+09 | 674.13 | 01-OCT-09:09 |
November | 0.368699E+10 | 2921.79 | 01-NOV-08:09 | 0.857490E+09 | 674.13 | 01-NOV-08:09 |
December | 0.378000E+10 | 2921.79 | 01-DEC-09:09 | 0.879197E+09 | 674.13 | 01-DEC-09:09 |
Annual Sum or Average | 0.450079E+11 | 0.104672E+11 | ||||
Minimum of Months | 0.344119E+10 | 2921.79 | 0.800324E+09 | 674.13 | ||
Maximum of Months | 0.387965E+10 | 2921.79 | 0.902118E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.379993E+10 | 2921.79 | 01-JAN-10:09 | 0.883781E+09 | 674.13 | 01-JAN-10:09 |
February | 0.344119E+10 | 2921.79 | 01-FEB-09:09 | 0.800324E+09 | 674.13 | 01-FEB-09:09 |
March | 0.387965E+10 | 2921.79 | 01-MAR-09:09 | 0.902118E+09 | 674.13 | 01-MAR-09:09 |
April | 0.368699E+10 | 2921.79 | 01-APR-08:09 | 0.857490E+09 | 674.13 | 01-APR-08:09 |
May | 0.383979E+10 | 2921.79 | 01-MAY-08:09 | 0.892950E+09 | 674.13 | 01-MAY-08:09 |
June | 0.374678E+10 | 2921.79 | 01-JUN-08:09 | 0.871243E+09 | 674.13 | 01-JUN-08:09 |
July | 0.378000E+10 | 2921.79 | 01-JUL-08:09 | 0.879197E+09 | 674.13 | 01-JUL-08:09 |
August | 0.387965E+10 | 2921.79 | 01-AUG-08:09 | 0.902118E+09 | 674.13 | 01-AUG-08:09 |
September | 0.368699E+10 | 2921.79 | 01-SEP-08:09 | 0.857490E+09 | 674.13 | 01-SEP-08:09 |
October | 0.379993E+10 | 2921.79 | 01-OCT-09:09 | 0.883781E+09 | 674.13 | 01-OCT-09:09 |
November | 0.368699E+10 | 2921.79 | 01-NOV-08:09 | 0.857490E+09 | 674.13 | 01-NOV-08:09 |
December | 0.378000E+10 | 2921.79 | 01-DEC-09:09 | 0.879197E+09 | 674.13 | 01-DEC-09:09 |
Annual Sum or Average | 0.450079E+11 | 0.104672E+11 | ||||
Minimum of Months | 0.344119E+10 | 2921.79 | 0.800324E+09 | 674.13 | ||
Maximum of Months | 0.387965E+10 | 2921.79 | 0.902118E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.379993E+10 | 2921.79 | 01-JAN-10:09 | 0.883781E+09 | 674.13 | 01-JAN-10:09 |
February | 0.344119E+10 | 2921.79 | 01-FEB-09:09 | 0.800324E+09 | 674.13 | 01-FEB-09:09 |
March | 0.387965E+10 | 2921.79 | 01-MAR-09:09 | 0.902118E+09 | 674.13 | 01-MAR-09:09 |
April | 0.368699E+10 | 2921.79 | 01-APR-08:09 | 0.857490E+09 | 674.13 | 01-APR-08:09 |
May | 0.383979E+10 | 2921.79 | 01-MAY-08:09 | 0.892950E+09 | 674.13 | 01-MAY-08:09 |
June | 0.374678E+10 | 2921.79 | 01-JUN-08:09 | 0.871243E+09 | 674.13 | 01-JUN-08:09 |
July | 0.378000E+10 | 2921.79 | 01-JUL-08:09 | 0.879197E+09 | 674.13 | 01-JUL-08:09 |
August | 0.387965E+10 | 2921.79 | 01-AUG-08:09 | 0.902118E+09 | 674.13 | 01-AUG-08:09 |
September | 0.368699E+10 | 2921.79 | 01-SEP-08:09 | 0.857490E+09 | 674.13 | 01-SEP-08:09 |
October | 0.379993E+10 | 2921.79 | 01-OCT-09:09 | 0.883781E+09 | 674.13 | 01-OCT-09:09 |
November | 0.368699E+10 | 2921.79 | 01-NOV-08:09 | 0.857490E+09 | 674.13 | 01-NOV-08:09 |
December | 0.378000E+10 | 2921.79 | 01-DEC-09:09 | 0.879197E+09 | 674.13 | 01-DEC-09:09 |
Annual Sum or Average | 0.450079E+11 | 0.104672E+11 | ||||
Minimum of Months | 0.344119E+10 | 2921.79 | 0.800324E+09 | 674.13 | ||
Maximum of Months | 0.387965E+10 | 2921.79 | 0.902118E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.520705E+10 | 4358.02 | 01-JAN-11:09 | 0.162546E+10 | 1348.26 | 01-JAN-11:09 |
February | 0.471657E+10 | 4358.02 | 01-FEB-10:09 | 0.147229E+10 | 1348.26 | 01-FEB-10:09 |
March | 0.532596E+10 | 4358.02 | 01-MAR-10:09 | 0.166213E+10 | 1348.26 | 01-MAR-10:09 |
April | 0.505346E+10 | 4358.02 | 01-APR-09:09 | 0.157746E+10 | 1348.26 | 01-APR-09:09 |
May | 0.526650E+10 | 4358.02 | 01-MAY-09:09 | 0.164379E+10 | 1348.26 | 01-MAY-09:09 |
June | 0.514264E+10 | 4358.02 | 01-JUN-09:09 | 0.160496E+10 | 1348.26 | 01-JUN-09:09 |
July | 0.517732E+10 | 4358.02 | 01-JUL-09:09 | 0.161629E+10 | 1348.26 | 01-JUL-09:09 |
August | 0.532596E+10 | 4358.02 | 01-AUG-09:09 | 0.166213E+10 | 1348.26 | 01-AUG-09:09 |
September | 0.505346E+10 | 4358.02 | 01-SEP-09:09 | 0.157746E+10 | 1348.26 | 01-SEP-09:09 |
October | 0.520705E+10 | 4358.02 | 01-OCT-10:09 | 0.162546E+10 | 1348.26 | 01-OCT-10:09 |
November | 0.505346E+10 | 4358.02 | 01-NOV-09:09 | 0.157746E+10 | 1348.26 | 01-NOV-09:09 |
December | 0.517732E+10 | 4358.02 | 01-DEC-10:09 | 0.161629E+10 | 1348.26 | 01-DEC-10:09 |
Annual Sum or Average | 0.617068E+11 | 0.192612E+11 | ||||
Minimum of Months | 0.471657E+10 | 4358.02 | 0.147229E+10 | 1348.26 | ||
Maximum of Months | 0.532596E+10 | 4358.02 | 0.166213E+10 | 1348.26 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.260353E+10 | 2179.01 | 01-JAN-11:09 | 0.812728E+09 | 674.13 | 01-JAN-11:09 |
February | 0.235828E+10 | 2179.01 | 01-FEB-10:09 | 0.736147E+09 | 674.13 | 01-FEB-10:09 |
March | 0.266298E+10 | 2179.01 | 01-MAR-10:09 | 0.831065E+09 | 674.13 | 01-MAR-10:09 |
April | 0.252673E+10 | 2179.01 | 01-APR-09:09 | 0.788729E+09 | 674.13 | 01-APR-09:09 |
May | 0.263325E+10 | 2179.01 | 01-MAY-09:09 | 0.821897E+09 | 674.13 | 01-MAY-09:09 |
June | 0.257132E+10 | 2179.01 | 01-JUN-09:09 | 0.802482E+09 | 674.13 | 01-JUN-09:09 |
July | 0.258866E+10 | 2179.01 | 01-JUL-09:09 | 0.808144E+09 | 674.13 | 01-JUL-09:09 |
August | 0.266298E+10 | 2179.01 | 01-AUG-09:09 | 0.831065E+09 | 674.13 | 01-AUG-09:09 |
September | 0.252673E+10 | 2179.01 | 01-SEP-09:09 | 0.788729E+09 | 674.13 | 01-SEP-09:09 |
October | 0.260353E+10 | 2179.01 | 01-OCT-10:09 | 0.812728E+09 | 674.13 | 01-OCT-10:09 |
November | 0.252673E+10 | 2179.01 | 01-NOV-09:09 | 0.788729E+09 | 674.13 | 01-NOV-09:09 |
December | 0.258866E+10 | 2179.01 | 01-DEC-10:09 | 0.808144E+09 | 674.13 | 01-DEC-10:09 |
Annual Sum or Average | 0.308534E+11 | 0.963059E+10 | ||||
Minimum of Months | 0.235828E+10 | 2179.01 | 0.736147E+09 | 674.13 | ||
Maximum of Months | 0.266298E+10 | 2179.01 | 0.831065E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.260353E+10 | 2179.01 | 01-JAN-11:09 | 0.812728E+09 | 674.13 | 01-JAN-11:09 |
February | 0.235828E+10 | 2179.01 | 01-FEB-10:09 | 0.736147E+09 | 674.13 | 01-FEB-10:09 |
March | 0.266298E+10 | 2179.01 | 01-MAR-10:09 | 0.831065E+09 | 674.13 | 01-MAR-10:09 |
April | 0.252673E+10 | 2179.01 | 01-APR-09:09 | 0.788729E+09 | 674.13 | 01-APR-09:09 |
May | 0.263325E+10 | 2179.01 | 01-MAY-09:09 | 0.821897E+09 | 674.13 | 01-MAY-09:09 |
June | 0.257132E+10 | 2179.01 | 01-JUN-09:09 | 0.802482E+09 | 674.13 | 01-JUN-09:09 |
July | 0.258866E+10 | 2179.01 | 01-JUL-09:09 | 0.808144E+09 | 674.13 | 01-JUL-09:09 |
August | 0.266298E+10 | 2179.01 | 01-AUG-09:09 | 0.831065E+09 | 674.13 | 01-AUG-09:09 |
September | 0.252673E+10 | 2179.01 | 01-SEP-09:09 | 0.788729E+09 | 674.13 | 01-SEP-09:09 |
October | 0.260353E+10 | 2179.01 | 01-OCT-10:09 | 0.812728E+09 | 674.13 | 01-OCT-10:09 |
November | 0.252673E+10 | 2179.01 | 01-NOV-09:09 | 0.788729E+09 | 674.13 | 01-NOV-09:09 |
December | 0.258866E+10 | 2179.01 | 01-DEC-10:09 | 0.808144E+09 | 674.13 | 01-DEC-10:09 |
Annual Sum or Average | 0.308534E+11 | 0.963059E+10 | ||||
Minimum of Months | 0.235828E+10 | 2179.01 | 0.736147E+09 | 674.13 | ||
Maximum of Months | 0.266298E+10 | 2179.01 | 0.831065E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.260353E+10 | 2179.01 | 01-JAN-11:09 | 0.812728E+09 | 674.13 | 01-JAN-11:09 |
February | 0.235828E+10 | 2179.01 | 01-FEB-10:09 | 0.736147E+09 | 674.13 | 01-FEB-10:09 |
March | 0.266298E+10 | 2179.01 | 01-MAR-10:09 | 0.831065E+09 | 674.13 | 01-MAR-10:09 |
April | 0.252673E+10 | 2179.01 | 01-APR-09:09 | 0.788729E+09 | 674.13 | 01-APR-09:09 |
May | 0.263325E+10 | 2179.01 | 01-MAY-09:09 | 0.821897E+09 | 674.13 | 01-MAY-09:09 |
June | 0.257132E+10 | 2179.01 | 01-JUN-09:09 | 0.802482E+09 | 674.13 | 01-JUN-09:09 |
July | 0.258866E+10 | 2179.01 | 01-JUL-09:09 | 0.808144E+09 | 674.13 | 01-JUL-09:09 |
August | 0.266298E+10 | 2179.01 | 01-AUG-09:09 | 0.831065E+09 | 674.13 | 01-AUG-09:09 |
September | 0.252673E+10 | 2179.01 | 01-SEP-09:09 | 0.788729E+09 | 674.13 | 01-SEP-09:09 |
October | 0.260353E+10 | 2179.01 | 01-OCT-10:09 | 0.812728E+09 | 674.13 | 01-OCT-10:09 |
November | 0.252673E+10 | 2179.01 | 01-NOV-09:09 | 0.788729E+09 | 674.13 | 01-NOV-09:09 |
December | 0.258866E+10 | 2179.01 | 01-DEC-10:09 | 0.808144E+09 | 674.13 | 01-DEC-10:09 |
Annual Sum or Average | 0.308534E+11 | 0.963059E+10 | ||||
Minimum of Months | 0.235828E+10 | 2179.01 | 0.736147E+09 | 674.13 | ||
Maximum of Months | 0.266298E+10 | 2179.01 | 0.831065E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.260353E+10 | 2179.01 | 01-JAN-11:09 | 0.812728E+09 | 674.13 | 01-JAN-11:09 |
February | 0.235828E+10 | 2179.01 | 01-FEB-10:09 | 0.736147E+09 | 674.13 | 01-FEB-10:09 |
March | 0.266298E+10 | 2179.01 | 01-MAR-10:09 | 0.831065E+09 | 674.13 | 01-MAR-10:09 |
April | 0.252673E+10 | 2179.01 | 01-APR-09:09 | 0.788729E+09 | 674.13 | 01-APR-09:09 |
May | 0.263325E+10 | 2179.01 | 01-MAY-09:09 | 0.821897E+09 | 674.13 | 01-MAY-09:09 |
June | 0.257132E+10 | 2179.01 | 01-JUN-09:09 | 0.802482E+09 | 674.13 | 01-JUN-09:09 |
July | 0.258866E+10 | 2179.01 | 01-JUL-09:09 | 0.808144E+09 | 674.13 | 01-JUL-09:09 |
August | 0.266298E+10 | 2179.01 | 01-AUG-09:09 | 0.831065E+09 | 674.13 | 01-AUG-09:09 |
September | 0.252673E+10 | 2179.01 | 01-SEP-09:09 | 0.788729E+09 | 674.13 | 01-SEP-09:09 |
October | 0.260353E+10 | 2179.01 | 01-OCT-10:09 | 0.812728E+09 | 674.13 | 01-OCT-10:09 |
November | 0.252673E+10 | 2179.01 | 01-NOV-09:09 | 0.788729E+09 | 674.13 | 01-NOV-09:09 |
December | 0.258866E+10 | 2179.01 | 01-DEC-10:09 | 0.808144E+09 | 674.13 | 01-DEC-10:09 |
Annual Sum or Average | 0.308534E+11 | 0.963059E+10 | ||||
Minimum of Months | 0.235828E+10 | 2179.01 | 0.736147E+09 | 674.13 | ||
Maximum of Months | 0.266298E+10 | 2179.01 | 0.831065E+09 | 674.13 |
Report: SpaceGainsMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.180574E+10 | 0.100203E+11 | 0.223514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109129E+11 |
February | 0.163016E+10 | 0.906661E+10 | 0.202238E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.818671E+10 |
March | 0.178954E+10 | 0.100410E+11 | 0.223972E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.624466E+10 |
April | 0.174484E+10 | 0.972311E+10 | 0.216880E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 80548499.36 | 0.396075E+10 |
May | 0.179537E+10 | 0.100203E+11 | 0.223514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 68162157.45 | 0.196918E+10 |
June | 0.173447E+10 | 0.972311E+10 | 0.216880E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.419469E+09 | 0.101398E+10 |
July | 0.181028E+10 | 0.100410E+11 | 0.223972E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.343638E+09 | 0.544657E+09 |
August | 0.178501E+10 | 0.100203E+11 | 0.223514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.370819E+09 | 0.714108E+09 |
September | 0.174937E+10 | 0.974384E+10 | 0.217339E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.279718E+09 | 0.169236E+10 |
October | 0.180574E+10 | 0.100203E+11 | 0.223514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.365573E+10 |
November | 0.174613E+10 | 0.968165E+10 | 0.215964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.639928E+10 |
December | 0.181481E+10 | 0.100617E+11 | 0.224431E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.916356E+10 |
Annual Sum or Average | 0.212115E+11 | 0.118163E+12 | 0.263573E+11 | 0.156236E+10 | 0.544579E+11 | ||||
Minimum of Months | 0.163016E+10 | 0.906661E+10 | 0.202238E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.544657E+09 |
Maximum of Months | 0.181481E+10 | 0.100617E+11 | 0.224431E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.419469E+09 | 0.109129E+11 |
Report: SpaceGainsMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.902868E+09 | 0.540359E+10 | 0.111757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.523055E+10 |
February | 0.815075E+09 | 0.488932E+10 | 0.101119E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.392667E+10 |
March | 0.894769E+09 | 0.541477E+10 | 0.111986E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.294046E+10 |
April | 0.872416E+09 | 0.524335E+10 | 0.108440E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 41899461.83 | 0.189248E+10 |
May | 0.897684E+09 | 0.540359E+10 | 0.111757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36634213.63 | 0.942847E+09 |
June | 0.867232E+09 | 0.524335E+10 | 0.108440E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.223364E+09 | 0.464940E+09 |
July | 0.905135E+09 | 0.541477E+10 | 0.111986E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185876E+09 | 0.220108E+09 |
August | 0.892501E+09 | 0.540359E+10 | 0.111757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.199859E+09 | 0.276515E+09 |
September | 0.874683E+09 | 0.525453E+10 | 0.108669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150885E+09 | 0.772558E+09 |
October | 0.902868E+09 | 0.540359E+10 | 0.111757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174221E+10 |
November | 0.873064E+09 | 0.522099E+10 | 0.107982E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.303477E+10 |
December | 0.907403E+09 | 0.542595E+10 | 0.112215E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.437131E+10 |
Annual Sum or Average | 0.106057E+11 | 0.637214E+11 | 0.131787E+11 | 0.838518E+09 | 0.258154E+11 | ||||
Minimum of Months | 0.815075E+09 | 0.488932E+10 | 0.101119E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.220108E+09 |
Maximum of Months | 0.907403E+09 | 0.542595E+10 | 0.112215E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.223364E+09 | 0.523055E+10 |
Report: SpaceGainsMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.537120E+09 | 0.379993E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.540463E+10 |
February | 0.487879E+09 | 0.344119E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.406515E+10 |
March | 0.551374E+09 | 0.387965E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.302859E+10 |
April | 0.524810E+09 | 0.368699E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 39752084.67 | 0.193774E+10 |
May | 0.544247E+09 | 0.383979E+10 | 0.892950E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 36617024.81 | 0.968179E+09 |
June | 0.532585E+09 | 0.374678E+10 | 0.871243E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.217043E+09 | 0.478437E+09 |
July | 0.536472E+09 | 0.378000E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179078E+09 | 0.243110E+09 |
August | 0.551374E+09 | 0.387965E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.196952E+09 | 0.307760E+09 |
September | 0.524810E+09 | 0.368699E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147770E+09 | 0.806709E+09 |
October | 0.537120E+09 | 0.379993E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.177059E+10 |
November | 0.518979E+09 | 0.368699E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.313020E+10 |
December | 0.536472E+09 | 0.378000E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.451916E+10 |
Annual Sum or Average | 0.638324E+10 | 0.450079E+11 | 0.104672E+11 | 0.817213E+09 | 0.266602E+11 | ||||
Minimum of Months | 0.487879E+09 | 0.344119E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.243110E+09 |
Maximum of Months | 0.551374E+09 | 0.387965E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.217043E+09 | 0.540463E+10 |
Report: SpaceGainsMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.537120E+09 | 0.379993E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.539601E+10 |
February | 0.487879E+09 | 0.344119E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.405778E+10 |
March | 0.551374E+09 | 0.387965E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.301881E+10 |
April | 0.524810E+09 | 0.368699E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 39811278.19 | 0.192813E+10 |
May | 0.544247E+09 | 0.383979E+10 | 0.892950E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 36616856.07 | 0.956924E+09 |
June | 0.532585E+09 | 0.374678E+10 | 0.871243E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.216985E+09 | 0.474259E+09 |
July | 0.536472E+09 | 0.378000E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179049E+09 | 0.243245E+09 |
August | 0.551374E+09 | 0.387965E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.196957E+09 | 0.307694E+09 |
September | 0.524810E+09 | 0.368699E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147773E+09 | 0.801990E+09 |
October | 0.537120E+09 | 0.379993E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175382E+10 |
November | 0.518979E+09 | 0.368699E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.311597E+10 |
December | 0.536472E+09 | 0.378000E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.451097E+10 |
Annual Sum or Average | 0.638324E+10 | 0.450079E+11 | 0.104672E+11 | 0.817192E+09 | 0.265656E+11 | ||||
Minimum of Months | 0.487879E+09 | 0.344119E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.243245E+09 |
Maximum of Months | 0.551374E+09 | 0.387965E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.216985E+09 | 0.539601E+10 |
Report: SpaceGainsMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.537120E+09 | 0.379993E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.539013E+10 |
February | 0.487879E+09 | 0.344119E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.405256E+10 |
March | 0.551374E+09 | 0.387965E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.301066E+10 |
April | 0.524810E+09 | 0.368699E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 39938166.98 | 0.191865E+10 |
May | 0.544247E+09 | 0.383979E+10 | 0.892950E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 36616203.22 | 0.939262E+09 |
June | 0.532585E+09 | 0.374678E+10 | 0.871243E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.217164E+09 | 0.467800E+09 |
July | 0.536472E+09 | 0.378000E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179131E+09 | 0.241130E+09 |
August | 0.551374E+09 | 0.387965E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.196986E+09 | 0.305365E+09 |
September | 0.524810E+09 | 0.368699E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147791E+09 | 0.794846E+09 |
October | 0.537120E+09 | 0.379993E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174031E+10 |
November | 0.518979E+09 | 0.368699E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.310454E+10 |
December | 0.536472E+09 | 0.378000E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.450507E+10 |
Annual Sum or Average | 0.638324E+10 | 0.450079E+11 | 0.104672E+11 | 0.817627E+09 | 0.264703E+11 | ||||
Minimum of Months | 0.487879E+09 | 0.344119E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.241130E+09 |
Maximum of Months | 0.551374E+09 | 0.387965E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.217164E+09 | 0.539013E+10 |
Report: SpaceGainsMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.183632E+10 | 0.520705E+10 | 0.162546E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.996035E+10 |
February | 0.167188E+10 | 0.471657E+10 | 0.147229E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.748175E+10 |
March | 0.189386E+10 | 0.532596E+10 | 0.166213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.557944E+10 |
April | 0.180380E+10 | 0.505346E+10 | 0.157746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 72728584.18 | 0.354280E+10 |
May | 0.186509E+10 | 0.526650E+10 | 0.164379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 65985528.33 | 0.170309E+10 |
June | 0.182945E+10 | 0.514264E+10 | 0.160496E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.392043E+09 | 0.870751E+09 |
July | 0.183943E+10 | 0.517732E+10 | 0.161629E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.322991E+09 | 0.466686E+09 |
August | 0.189386E+10 | 0.532596E+10 | 0.166213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.354634E+09 | 0.596600E+09 |
September | 0.180380E+10 | 0.505346E+10 | 0.157746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.266220E+09 | 0.148418E+10 |
October | 0.183632E+10 | 0.520705E+10 | 0.162546E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.321849E+10 |
November | 0.176881E+10 | 0.505346E+10 | 0.157746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.574476E+10 |
December | 0.183943E+10 | 0.517732E+10 | 0.161629E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.833497E+10 |
Annual Sum or Average | 0.218821E+11 | 0.617068E+11 | 0.192612E+11 | 0.147460E+10 | 0.489839E+11 | ||||
Minimum of Months | 0.167188E+10 | 0.471657E+10 | 0.147229E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.466686E+09 |
Maximum of Months | 0.189386E+10 | 0.532596E+10 | 0.166213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.392043E+09 | 0.996035E+10 |
Report: SpaceGainsMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.918158E+09 | 0.260353E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.542517E+10 |
February | 0.835938E+09 | 0.235828E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.407380E+10 |
March | 0.946926E+09 | 0.266298E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.302610E+10 |
April | 0.901896E+09 | 0.252673E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 40308827.29 | 0.192069E+10 |
May | 0.932542E+09 | 0.263325E+10 | 0.821897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 36635202.60 | 0.910198E+09 |
June | 0.914724E+09 | 0.257132E+10 | 0.802482E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.217554E+09 | 0.464338E+09 |
July | 0.919713E+09 | 0.258866E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179620E+09 | 0.245221E+09 |
August | 0.946926E+09 | 0.266298E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.196977E+09 | 0.311564E+09 |
September | 0.901896E+09 | 0.252673E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147891E+09 | 0.795503E+09 |
October | 0.918158E+09 | 0.260353E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174008E+10 |
November | 0.884402E+09 | 0.252673E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.311710E+10 |
December | 0.919713E+09 | 0.258866E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.453504E+10 |
Annual Sum or Average | 0.109410E+11 | 0.308534E+11 | 0.963059E+10 | 0.818986E+09 | 0.265648E+11 | ||||
Minimum of Months | 0.835938E+09 | 0.235828E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.245221E+09 |
Maximum of Months | 0.946926E+09 | 0.266298E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.217554E+09 | 0.542517E+10 |
Report: SpaceGainsMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.918158E+09 | 0.260353E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.542395E+10 |
February | 0.835938E+09 | 0.235828E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.407236E+10 |
March | 0.946926E+09 | 0.266298E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.302281E+10 |
April | 0.901896E+09 | 0.252673E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 40398521.91 | 0.191565E+10 |
May | 0.932542E+09 | 0.263325E+10 | 0.821897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 36636247.84 | 0.895272E+09 |
June | 0.914724E+09 | 0.257132E+10 | 0.802482E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.217692E+09 | 0.460308E+09 |
July | 0.919713E+09 | 0.258866E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179680E+09 | 0.243982E+09 |
August | 0.946926E+09 | 0.266298E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.196992E+09 | 0.310400E+09 |
September | 0.901896E+09 | 0.252673E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147907E+09 | 0.791441E+09 |
October | 0.918158E+09 | 0.260353E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.173528E+10 |
November | 0.884402E+09 | 0.252673E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.311409E+10 |
December | 0.919713E+09 | 0.258866E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.453348E+10 |
Annual Sum or Average | 0.109410E+11 | 0.308534E+11 | 0.963059E+10 | 0.819306E+09 | 0.265190E+11 | ||||
Minimum of Months | 0.835938E+09 | 0.235828E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.243982E+09 |
Maximum of Months | 0.946926E+09 | 0.266298E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.217692E+09 | 0.542395E+10 |
Report: SpaceGainsMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.918158E+09 | 0.260353E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.541642E+10 |
February | 0.835938E+09 | 0.235828E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.406455E+10 |
March | 0.946926E+09 | 0.266298E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.300985E+10 |
April | 0.901896E+09 | 0.252673E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 40650816.46 | 0.189926E+10 |
May | 0.932542E+09 | 0.263325E+10 | 0.821897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 36633215.23 | 0.860363E+09 |
June | 0.914724E+09 | 0.257132E+10 | 0.802482E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.218033E+09 | 0.449585E+09 |
July | 0.919713E+09 | 0.258866E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179818E+09 | 0.239948E+09 |
August | 0.946926E+09 | 0.266298E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.197030E+09 | 0.306764E+09 |
September | 0.901896E+09 | 0.252673E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147944E+09 | 0.781123E+09 |
October | 0.918158E+09 | 0.260353E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172168E+10 |
November | 0.884402E+09 | 0.252673E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.310354E+10 |
December | 0.919713E+09 | 0.258866E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.452503E+10 |
Annual Sum or Average | 0.109410E+11 | 0.308534E+11 | 0.963059E+10 | 0.820109E+09 | 0.263781E+11 | ||||
Minimum of Months | 0.835938E+09 | 0.235828E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.239948E+09 |
Maximum of Months | 0.946926E+09 | 0.266298E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.218033E+09 | 0.541642E+10 |
Report: SpaceGainsMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.918158E+09 | 0.260353E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.704969E+10 |
February | 0.835938E+09 | 0.235828E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.526752E+10 |
March | 0.946926E+09 | 0.266298E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.398457E+10 |
April | 0.901896E+09 | 0.252673E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 46764965.30 | 0.245156E+10 |
May | 0.932542E+09 | 0.263325E+10 | 0.821897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 38805128.33 | 0.111052E+10 |
June | 0.914724E+09 | 0.257132E+10 | 0.802482E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.236907E+09 | 0.625178E+09 |
July | 0.919713E+09 | 0.258866E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188778E+09 | 0.379920E+09 |
August | 0.946926E+09 | 0.266298E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.207785E+09 | 0.522562E+09 |
September | 0.901896E+09 | 0.252673E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155630E+09 | 0.110517E+10 |
October | 0.918158E+09 | 0.260353E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230065E+10 |
November | 0.884402E+09 | 0.252673E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.411672E+10 |
December | 0.919713E+09 | 0.258866E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.591035E+10 |
Annual Sum or Average | 0.109410E+11 | 0.308534E+11 | 0.963059E+10 | 0.874670E+09 | 0.348244E+11 | ||||
Minimum of Months | 0.835938E+09 | 0.235828E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.379920E+09 |
Maximum of Months | 0.946926E+09 | 0.266298E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.236907E+09 | 0.704969E+10 |
Report: PeakSpaceGainsMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2159.72 | 01-JAN-13:09 | 6078.71 | 01-JAN-10:09 | 1348.26 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 16720.68 | 30-JAN-18:00 |
February | 2159.72 | 03-FEB-13:09 | 6078.71 | 01-FEB-10:09 | 1348.26 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 18849.35 | 02-FEB-12:10 |
March | 2159.72 | 03-MAR-13:09 | 6078.71 | 01-MAR-10:09 | 1348.26 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 11249.61 | 05-MAR-18:00 |
April | 2159.72 | 01-APR-12:09 | 6078.71 | 01-APR-09:09 | 1348.26 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1871.80 | 15-APR-15:00 | 8218.63 | 03-APR-11:10 |
May | 2159.72 | 05-MAY-12:09 | 6078.71 | 01-MAY-09:09 | 1348.26 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1749.41 | 31-MAY-13:00 | 4183.47 | 01-MAY-17:00 |
June | 2159.72 | 02-JUN-12:09 | 6078.71 | 01-JUN-09:09 | 1348.26 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2768.26 | 11-JUN-15:00 | 3414.92 | 01-JUN-14:00 |
July | 2159.72 | 01-JUL-12:09 | 6078.71 | 01-JUL-09:09 | 1348.26 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1762.76 | 26-JUL-16:00 | 2490.87 | 10-JUL-12:00 |
August | 2159.72 | 04-AUG-12:09 | 6078.71 | 01-AUG-09:09 | 1348.26 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2776.56 | 04-AUG-15:00 | 2497.91 | 06-AUG-11:10 |
September | 2159.72 | 01-SEP-12:09 | 6078.71 | 01-SEP-09:09 | 1348.26 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2383.28 | 06-SEP-14:00 | 4175.30 | 29-SEP-17:00 |
October | 2159.72 | 01-OCT-12:09 | 6078.71 | 01-OCT-09:09 | 1348.26 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 | 5384.95 | 31-OCT-17:00 |
November | 2159.72 | 03-NOV-12:09 | 6078.71 | 01-NOV-09:09 | 1348.26 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 14696.92 | 25-NOV-18:00 |
December | 2159.72 | 01-DEC-13:09 | 6078.71 | 01-DEC-10:09 | 1348.26 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 15662.10 | 09-DEC-12:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2159.72 | 6078.71 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2490.87 | |||||
Maximum of Months | 2159.72 | 6078.71 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 2776.56 | 18849.35 |
Report: PeakSpaceGainsMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1079.86 | 01-JAN-13:09 | 3278.04 | 01-JAN-10:09 | 674.13 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 9136.59 | 30-JAN-18:00 |
February | 1079.86 | 03-FEB-13:09 | 3278.04 | 01-FEB-10:09 | 674.13 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 10245.55 | 02-FEB-12:10 |
March | 1079.86 | 03-MAR-13:09 | 3278.04 | 01-MAR-10:09 | 674.13 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 6071.76 | 05-MAR-18:00 |
April | 1079.86 | 01-APR-12:09 | 3278.04 | 01-APR-09:09 | 674.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 978.58 | 15-APR-15:00 | 4439.28 | 03-APR-11:10 |
May | 1079.86 | 05-MAY-12:09 | 3278.04 | 01-MAY-09:09 | 674.13 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 946.45 | 31-MAY-13:00 | 2216.61 | 01-MAY-17:00 |
June | 1079.86 | 02-JUN-12:09 | 3278.04 | 01-JUN-09:09 | 674.13 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1469.98 | 11-JUN-15:00 | 1937.46 | 01-JUN-14:00 |
July | 1079.86 | 01-JUL-12:09 | 3278.04 | 01-JUL-09:09 | 674.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 953.64 | 26-JUL-16:00 | 1364.91 | 10-JUL-12:00 |
August | 1079.86 | 04-AUG-12:09 | 3278.04 | 01-AUG-09:09 | 674.13 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1513.53 | 04-AUG-15:00 | 1349.77 | 06-AUG-11:10 |
September | 1079.86 | 01-SEP-12:09 | 3278.04 | 01-SEP-09:09 | 674.13 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1289.33 | 06-SEP-14:00 | 2253.51 | 29-SEP-17:00 |
October | 1079.86 | 01-OCT-12:09 | 3278.04 | 01-OCT-09:09 | 674.13 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 | 2974.50 | 31-OCT-17:00 |
November | 1079.86 | 03-NOV-12:09 | 3278.04 | 01-NOV-09:09 | 674.13 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 7895.88 | 25-NOV-18:00 |
December | 1079.86 | 01-DEC-13:09 | 3278.04 | 01-DEC-10:09 | 674.13 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 8201.33 | 09-DEC-12:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1079.86 | 3278.04 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1349.77 | |||||
Maximum of Months | 1079.86 | 3278.04 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1513.53 | 10245.55 |
Report: PeakSpaceGainsMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1079.86 | 07-JAN-13:09 | 2921.79 | 01-JAN-10:09 | 674.13 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 9136.57 | 30-JAN-18:00 |
February | 1079.86 | 04-FEB-13:09 | 2921.79 | 01-FEB-09:09 | 674.13 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 10245.53 | 02-FEB-12:10 |
March | 1079.86 | 04-MAR-13:09 | 2921.79 | 01-MAR-09:09 | 674.13 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 6071.76 | 05-MAR-18:00 |
April | 1079.86 | 01-APR-12:09 | 2921.79 | 01-APR-08:09 | 674.13 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 978.71 | 15-APR-15:00 | 4439.27 | 03-APR-11:10 |
May | 1079.86 | 06-MAY-12:09 | 2921.79 | 01-MAY-08:09 | 674.13 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 946.41 | 31-MAY-13:00 | 2216.60 | 01-MAY-17:00 |
June | 1079.86 | 03-JUN-12:09 | 2921.79 | 01-JUN-08:09 | 674.13 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1469.93 | 11-JUN-15:00 | 1925.96 | 01-JUN-14:00 |
July | 1079.86 | 01-JUL-12:09 | 2921.79 | 01-JUL-08:09 | 674.13 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 953.62 | 26-JUL-16:00 | 1364.90 | 10-JUL-12:00 |
August | 1079.86 | 05-AUG-12:09 | 2921.79 | 01-AUG-08:09 | 674.13 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1513.51 | 04-AUG-15:00 | 1349.76 | 06-AUG-11:10 |
September | 1079.86 | 02-SEP-12:09 | 2921.79 | 01-SEP-08:09 | 674.13 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1289.31 | 06-SEP-14:00 | 2253.50 | 29-SEP-17:00 |
October | 1079.86 | 07-OCT-12:09 | 2921.79 | 01-OCT-09:09 | 674.13 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 | 2974.49 | 31-OCT-17:00 |
November | 1079.86 | 04-NOV-12:09 | 2921.79 | 01-NOV-08:09 | 674.13 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 7895.86 | 25-NOV-18:00 |
December | 1079.86 | 02-DEC-13:09 | 2921.79 | 01-DEC-09:09 | 674.13 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 8201.28 | 09-DEC-12:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1079.86 | 2921.79 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1349.76 | |||||
Maximum of Months | 1079.86 | 2921.79 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1513.51 | 10245.53 |
Report: PeakSpaceGainsMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1079.86 | 07-JAN-13:09 | 2921.79 | 01-JAN-10:09 | 674.13 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 9136.57 | 30-JAN-18:00 |
February | 1079.86 | 04-FEB-13:09 | 2921.79 | 01-FEB-09:09 | 674.13 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 10245.53 | 02-FEB-12:10 |
March | 1079.86 | 04-MAR-13:09 | 2921.79 | 01-MAR-09:09 | 674.13 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 6071.76 | 05-MAR-18:00 |
April | 1079.86 | 01-APR-12:09 | 2921.79 | 01-APR-08:09 | 674.13 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 978.70 | 15-APR-15:00 | 4439.27 | 03-APR-11:10 |
May | 1079.86 | 06-MAY-12:09 | 2921.79 | 01-MAY-08:09 | 674.13 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 946.41 | 31-MAY-13:00 | 2216.60 | 01-MAY-17:00 |
June | 1079.86 | 03-JUN-12:09 | 2921.79 | 01-JUN-08:09 | 674.13 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1469.93 | 11-JUN-15:00 | 1922.53 | 01-JUN-14:00 |
July | 1079.86 | 01-JUL-12:09 | 2921.79 | 01-JUL-08:09 | 674.13 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 953.62 | 26-JUL-16:00 | 1364.90 | 10-JUL-12:00 |
August | 1079.86 | 05-AUG-12:09 | 2921.79 | 01-AUG-08:09 | 674.13 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1513.51 | 04-AUG-15:00 | 1349.76 | 06-AUG-11:10 |
September | 1079.86 | 02-SEP-12:09 | 2921.79 | 01-SEP-08:09 | 674.13 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1289.31 | 06-SEP-14:00 | 2253.53 | 29-SEP-17:00 |
October | 1079.86 | 07-OCT-12:09 | 2921.79 | 01-OCT-09:09 | 674.13 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 | 2974.49 | 31-OCT-17:00 |
November | 1079.86 | 04-NOV-12:09 | 2921.79 | 01-NOV-08:09 | 674.13 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 7895.86 | 25-NOV-18:00 |
December | 1079.86 | 02-DEC-13:09 | 2921.79 | 01-DEC-09:09 | 674.13 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 8201.28 | 09-DEC-12:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1079.86 | 2921.79 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1349.76 | |||||
Maximum of Months | 1079.86 | 2921.79 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1513.51 | 10245.53 |
Report: PeakSpaceGainsMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1079.86 | 07-JAN-13:09 | 2921.79 | 01-JAN-10:09 | 674.13 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 9136.57 | 30-JAN-18:00 |
February | 1079.86 | 04-FEB-13:09 | 2921.79 | 01-FEB-09:09 | 674.13 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 10245.53 | 02-FEB-12:10 |
March | 1079.86 | 04-MAR-13:09 | 2921.79 | 01-MAR-09:09 | 674.13 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 6071.76 | 05-MAR-18:00 |
April | 1079.86 | 01-APR-12:09 | 2921.79 | 01-APR-08:09 | 674.13 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 978.69 | 15-APR-15:00 | 4439.27 | 03-APR-11:10 |
May | 1079.86 | 06-MAY-12:09 | 2921.79 | 01-MAY-08:09 | 674.13 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 946.39 | 31-MAY-13:00 | 2216.61 | 01-MAY-17:00 |
June | 1079.86 | 03-JUN-12:09 | 2921.79 | 01-JUN-08:09 | 674.13 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1469.93 | 11-JUN-15:00 | 1907.11 | 01-JUN-14:00 |
July | 1079.86 | 01-JUL-12:09 | 2921.79 | 01-JUL-08:09 | 674.13 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 953.61 | 26-JUL-16:00 | 1357.18 | 10-JUL-12:00 |
August | 1079.86 | 05-AUG-12:09 | 2921.79 | 01-AUG-08:09 | 674.13 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1513.50 | 04-AUG-15:00 | 1349.76 | 06-AUG-11:10 |
September | 1079.86 | 02-SEP-12:09 | 2921.79 | 01-SEP-08:09 | 674.13 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1289.28 | 06-SEP-14:00 | 2253.53 | 29-SEP-17:00 |
October | 1079.86 | 07-OCT-12:09 | 2921.79 | 01-OCT-09:09 | 674.13 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 | 2974.49 | 31-OCT-17:00 |
November | 1079.86 | 04-NOV-12:09 | 2921.79 | 01-NOV-08:09 | 674.13 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 7895.86 | 25-NOV-18:00 |
December | 1079.86 | 02-DEC-13:09 | 2921.79 | 01-DEC-09:09 | 674.13 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 8201.28 | 09-DEC-12:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1079.86 | 2921.79 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1349.76 | |||||
Maximum of Months | 1079.86 | 2921.79 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1513.50 | 10245.53 |
Report: PeakSpaceGainsMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2879.63 | 07-JAN-15:09 | 4358.02 | 01-JAN-11:09 | 1348.26 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 16423.06 | 30-JAN-18:00 |
February | 2879.63 | 04-FEB-15:09 | 4358.02 | 01-FEB-10:09 | 1348.26 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 18428.53 | 02-FEB-12:10 |
March | 2879.63 | 04-MAR-15:09 | 4358.02 | 01-MAR-10:09 | 1348.26 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 10930.85 | 05-MAR-18:00 |
April | 2879.63 | 01-APR-14:09 | 4358.02 | 01-APR-09:09 | 1348.26 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1769.11 | 15-APR-15:00 | 7991.13 | 03-APR-11:10 |
May | 2879.63 | 06-MAY-14:09 | 4358.02 | 01-MAY-09:09 | 1348.26 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1703.32 | 31-MAY-13:00 | 3999.86 | 01-MAY-17:00 |
June | 2879.63 | 03-JUN-14:09 | 4358.02 | 01-JUN-09:09 | 1348.26 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2651.80 | 11-JUN-15:00 | 3322.52 | 01-JUN-14:00 |
July | 2879.63 | 01-JUL-14:09 | 4358.02 | 01-JUL-09:09 | 1348.26 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1716.27 | 26-JUL-16:00 | 2380.32 | 10-JUL-12:00 |
August | 2879.63 | 05-AUG-14:09 | 4358.02 | 01-AUG-09:09 | 1348.26 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2721.42 | 04-AUG-15:00 | 2429.58 | 06-AUG-11:10 |
September | 2879.63 | 02-SEP-14:09 | 4358.02 | 01-SEP-09:09 | 1348.26 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2320.46 | 06-SEP-14:00 | 4056.99 | 29-SEP-17:00 |
October | 2879.63 | 07-OCT-14:09 | 4358.02 | 01-OCT-10:09 | 1348.26 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 | 5339.56 | 31-OCT-17:00 |
November | 2879.63 | 04-NOV-14:09 | 4358.02 | 01-NOV-09:09 | 1348.26 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 14222.97 | 25-NOV-18:00 |
December | 2879.63 | 02-DEC-15:09 | 4358.02 | 01-DEC-10:09 | 1348.26 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 14821.54 | 09-DEC-12:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2879.63 | 4358.02 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2380.32 | |||||
Maximum of Months | 2879.63 | 4358.02 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 2721.42 | 18428.53 |
Report: PeakSpaceGainsMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1439.81 | 07-JAN-15:09 | 2179.01 | 01-JAN-11:09 | 674.13 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 9136.57 | 30-JAN-18:00 |
February | 1439.81 | 04-FEB-15:09 | 2179.01 | 01-FEB-10:09 | 674.13 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 10245.53 | 02-FEB-12:10 |
March | 1439.81 | 04-MAR-15:09 | 2179.01 | 01-MAR-10:09 | 674.13 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 6071.76 | 05-MAR-18:00 |
April | 1439.81 | 01-APR-14:09 | 2179.01 | 01-APR-09:09 | 674.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 978.72 | 15-APR-15:00 | 4439.26 | 03-APR-11:10 |
May | 1439.81 | 06-MAY-14:09 | 2179.01 | 01-MAY-09:09 | 674.13 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 946.39 | 31-MAY-13:00 | 2216.61 | 01-MAY-17:00 |
June | 1439.81 | 03-JUN-14:09 | 2179.01 | 01-JUN-09:09 | 674.13 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1469.98 | 11-JUN-15:00 | 1850.77 | 01-JUN-14:00 |
July | 1439.81 | 01-JUL-14:09 | 2179.01 | 01-JUL-09:09 | 674.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 953.63 | 26-JUL-16:00 | 1320.61 | 10-JUL-12:00 |
August | 1439.81 | 05-AUG-14:09 | 2179.01 | 01-AUG-09:09 | 674.13 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1513.56 | 04-AUG-15:00 | 1349.76 | 06-AUG-11:10 |
September | 1439.81 | 02-SEP-14:09 | 2179.01 | 01-SEP-09:09 | 674.13 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1289.31 | 06-SEP-14:00 | 2253.54 | 29-SEP-17:00 |
October | 1439.81 | 07-OCT-14:09 | 2179.01 | 01-OCT-10:09 | 674.13 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 | 2974.51 | 31-OCT-17:00 |
November | 1439.81 | 04-NOV-14:09 | 2179.01 | 01-NOV-09:09 | 674.13 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 7895.85 | 25-NOV-18:00 |
December | 1439.81 | 02-DEC-15:09 | 2179.01 | 01-DEC-10:09 | 674.13 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 8201.28 | 09-DEC-12:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1439.81 | 2179.01 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1320.61 | |||||
Maximum of Months | 1439.81 | 2179.01 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1513.56 | 10245.53 |
Report: PeakSpaceGainsMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1439.81 | 07-JAN-15:09 | 2179.01 | 01-JAN-11:09 | 674.13 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 9136.57 | 30-JAN-18:00 |
February | 1439.81 | 04-FEB-15:09 | 2179.01 | 01-FEB-10:09 | 674.13 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 10245.53 | 02-FEB-12:10 |
March | 1439.81 | 04-MAR-15:09 | 2179.01 | 01-MAR-10:09 | 674.13 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 6071.76 | 05-MAR-18:00 |
April | 1439.81 | 01-APR-14:09 | 2179.01 | 01-APR-09:09 | 674.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 978.71 | 15-APR-15:00 | 4439.26 | 03-APR-11:10 |
May | 1439.81 | 06-MAY-14:09 | 2179.01 | 01-MAY-09:09 | 674.13 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 946.38 | 31-MAY-13:00 | 2216.61 | 01-MAY-17:00 |
June | 1439.81 | 03-JUN-14:09 | 2179.01 | 01-JUN-09:09 | 674.13 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1469.98 | 11-JUN-15:00 | 1838.56 | 01-JUN-14:00 |
July | 1439.81 | 01-JUL-14:09 | 2179.01 | 01-JUL-09:09 | 674.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 953.63 | 26-JUL-16:00 | 1312.13 | 10-JUL-12:00 |
August | 1439.81 | 05-AUG-14:09 | 2179.01 | 01-AUG-09:09 | 674.13 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1513.56 | 04-AUG-15:00 | 1349.76 | 06-AUG-11:10 |
September | 1439.81 | 02-SEP-14:09 | 2179.01 | 01-SEP-09:09 | 674.13 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1289.31 | 06-SEP-14:00 | 2253.54 | 29-SEP-17:00 |
October | 1439.81 | 07-OCT-14:09 | 2179.01 | 01-OCT-10:09 | 674.13 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 | 2974.51 | 31-OCT-17:00 |
November | 1439.81 | 04-NOV-14:09 | 2179.01 | 01-NOV-09:09 | 674.13 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 7895.85 | 25-NOV-18:00 |
December | 1439.81 | 02-DEC-15:09 | 2179.01 | 01-DEC-10:09 | 674.13 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 8201.28 | 09-DEC-12:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1439.81 | 2179.01 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1312.13 | |||||
Maximum of Months | 1439.81 | 2179.01 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1513.56 | 10245.53 |
Report: PeakSpaceGainsMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1439.81 | 07-JAN-15:09 | 2179.01 | 01-JAN-11:09 | 674.13 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 9136.57 | 30-JAN-18:00 |
February | 1439.81 | 04-FEB-15:09 | 2179.01 | 01-FEB-10:09 | 674.13 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 10245.53 | 02-FEB-12:10 |
March | 1439.81 | 04-MAR-15:09 | 2179.01 | 01-MAR-10:09 | 674.13 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 6071.76 | 05-MAR-18:00 |
April | 1439.81 | 01-APR-14:09 | 2179.01 | 01-APR-09:09 | 674.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 978.69 | 15-APR-15:00 | 4439.27 | 03-APR-11:10 |
May | 1439.81 | 06-MAY-14:09 | 2179.01 | 01-MAY-09:09 | 674.13 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 946.50 | 31-MAY-13:00 | 2216.59 | 01-MAY-17:00 |
June | 1439.81 | 03-JUN-14:09 | 2179.01 | 01-JUN-09:09 | 674.13 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1469.97 | 11-JUN-15:00 | 1806.23 | 01-JUN-14:00 |
July | 1439.81 | 01-JUL-14:09 | 2179.01 | 01-JUL-09:09 | 674.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 953.63 | 26-JUL-16:00 | 1284.72 | 10-JUL-12:00 |
August | 1439.81 | 05-AUG-14:09 | 2179.01 | 01-AUG-09:09 | 674.13 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1513.56 | 04-AUG-15:00 | 1345.41 | 06-AUG-11:10 |
September | 1439.81 | 02-SEP-14:09 | 2179.01 | 01-SEP-09:09 | 674.13 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1289.31 | 06-SEP-14:00 | 2253.54 | 29-SEP-17:00 |
October | 1439.81 | 07-OCT-14:09 | 2179.01 | 01-OCT-10:09 | 674.13 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 | 2974.51 | 31-OCT-17:00 |
November | 1439.81 | 04-NOV-14:09 | 2179.01 | 01-NOV-09:09 | 674.13 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 7895.85 | 25-NOV-18:00 |
December | 1439.81 | 02-DEC-15:09 | 2179.01 | 01-DEC-10:09 | 674.13 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 8201.28 | 09-DEC-12:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1439.81 | 2179.01 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1284.72 | |||||
Maximum of Months | 1439.81 | 2179.01 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1513.56 | 10245.53 |
Report: PeakSpaceGainsMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1439.81 | 07-JAN-15:09 | 2179.01 | 01-JAN-11:09 | 674.13 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 9433.79 | 30-JAN-18:00 |
February | 1439.81 | 04-FEB-15:09 | 2179.01 | 01-FEB-10:09 | 674.13 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 10665.78 | 02-FEB-12:10 |
March | 1439.81 | 04-MAR-15:09 | 2179.01 | 01-MAR-10:09 | 674.13 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 6390.13 | 05-MAR-18:00 |
April | 1439.81 | 01-APR-14:09 | 2179.01 | 01-APR-09:09 | 674.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1081.21 | 15-APR-15:00 | 4666.45 | 03-APR-11:10 |
May | 1439.81 | 06-MAY-14:09 | 2179.01 | 01-MAY-09:09 | 674.13 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 992.52 | 31-MAY-13:00 | 2399.98 | 01-MAY-17:00 |
June | 1439.81 | 03-JUN-14:09 | 2179.01 | 01-JUN-09:09 | 674.13 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1586.24 | 11-JUN-15:00 | 1780.43 | 01-JUN-14:00 |
July | 1439.81 | 01-JUL-14:09 | 2179.01 | 01-JUL-09:09 | 674.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 999.99 | 26-JUL-16:00 | 1277.12 | 10-JUL-12:00 |
August | 1439.81 | 05-AUG-14:09 | 2179.01 | 01-AUG-09:09 | 674.13 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1568.65 | 04-AUG-15:00 | 1370.48 | 06-AUG-11:10 |
September | 1439.81 | 02-SEP-14:09 | 2179.01 | 01-SEP-09:09 | 674.13 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1351.99 | 06-SEP-14:00 | 2371.70 | 29-SEP-17:00 |
October | 1439.81 | 07-OCT-14:09 | 2179.01 | 01-OCT-10:09 | 674.13 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 | 3019.86 | 31-OCT-17:00 |
November | 1439.81 | 04-NOV-14:09 | 2179.01 | 01-NOV-09:09 | 674.13 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 8369.16 | 25-NOV-18:00 |
December | 1439.81 | 02-DEC-15:09 | 2179.01 | 01-DEC-10:09 | 674.13 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 9040.70 | 09-DEC-12:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1439.81 | 2179.01 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1277.12 | |||||
Maximum of Months | 1439.81 | 2179.01 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1586.24 | 10665.78 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 20677.29 | 06-JAN-00:01 | 1619.79 | 28793.87 | 6741.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 668.88 |
February | 24267.47 | 03-FEB-00:01 | 1799.77 | 31993.19 | 7490.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 493.93 |
March | 13976.72 | 07-MAR-21:12 | 6479.16 | 36472.23 | 8089.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 360.59 |
April | 11449.28 | 01-APR-08:04 | 1439.81 | 25594.55 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1407.45 |
May | 23747.95 | 31-MAY-08:62 | 899.88 | 15996.59 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.11 |
June | 28479.68 | 17-JUN-08:62 | 899.88 | 15996.59 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 134.03 |
July | 31862.24 | 18-JUL-08:62 | 899.88 | 15996.59 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 288.16 |
August | 30606.04 | 15-AUG-08:62 | 899.88 | 15996.59 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 330.97 |
September | 30744.09 | 12-SEP-08:62 | 899.88 | 15996.59 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 424.49 |
October | 9161.78 | 26-OCT-08:02 | 1439.81 | 25594.55 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1055.35 |
November | 15210.67 | 25-NOV-00:01 | 1259.84 | 22395.23 | 5243.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 524.21 |
December | 19597.23 | 09-DEC-00:01 | 1619.79 | 28793.87 | 6741.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2026.30 |
Annual Sum or Average | |||||||||||
Minimum of Months | 9161.78 | 899.88 | 15996.59 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.11 | |
Maximum of Months | 31862.24 | 6479.16 | 36472.23 | 8089.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2026.30 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 8219.06 | 04-JAN-19:42 | 5399.28 | 19668.24 | 4044.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 971.75 |
February | 6724.08 | 17-FEB-09:04 | 719.90 | 13802.27 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 943.97 |
March | 6665.41 | 13-MAR-08:04 | 719.90 | 13802.27 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 757.91 |
April | 11104.83 | 18-APR-20:10 | 2159.71 | 13112.16 | 2696.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.40 |
May | 14927.27 | 21-MAY-17:08 | 6479.14 | 19668.24 | 4044.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 138.81 |
June | 17043.21 | 20-JUN-08:62 | 359.95 | 6901.14 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.90 |
July | 17867.60 | 18-JUL-08:62 | 449.94 | 8626.42 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 139.72 |
August | 17395.72 | 30-AUG-08:62 | 359.95 | 6901.14 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 172.01 |
September | 17166.23 | 12-SEP-08:62 | 449.94 | 8626.42 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 213.54 |
October | 4496.45 | 23-OCT-08:61 | 629.92 | 12076.99 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 540.59 |
November | 8583.36 | 26-NOV-09:04 | 899.88 | 17252.84 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1171.63 |
December | 7448.19 | 27-DEC-09:04 | 719.90 | 13802.27 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 831.47 |
Annual Sum or Average | |||||||||||
Minimum of Months | 4496.45 | 359.95 | 6901.14 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.40 | |
Maximum of Months | 17867.60 | 6479.14 | 19668.24 | 4044.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1171.63 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 8567.25 | 25-JAN-08:04 | 899.88 | 15377.84 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1072.12 |
February | 8429.28 | 28-FEB-08:04 | 899.88 | 15377.84 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1221.84 |
March | 6800.75 | 16-MAR-07:04 | 719.90 | 12302.27 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 884.76 |
April | 6385.91 | 03-APR-07:04 | 719.90 | 12302.27 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 816.78 |
May | 14099.39 | 31-MAY-07:03 | 359.95 | 6151.14 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.29 |
June | 18431.00 | 21-JUN-07:02 | 449.94 | 7688.92 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 216.11 |
July | 17892.71 | 19-JUL-07:02 | 449.94 | 7688.92 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 175.37 |
August | 20551.77 | 06-AUG-08:62 | 449.94 | 7688.92 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 304.88 |
September | 18104.77 | 13-SEP-07:02 | 449.94 | 7688.92 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 227.05 |
October | 4358.24 | 31-OCT-07:02 | 539.93 | 9226.71 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 486.18 |
November | 7140.41 | 21-NOV-08:04 | 719.90 | 12302.27 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 983.60 |
December | 8200.23 | 07-DEC-08:04 | 719.90 | 12302.27 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 979.01 |
Annual Sum or Average | |||||||||||
Minimum of Months | 4358.24 | 359.95 | 6151.14 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.29 | |
Maximum of Months | 20551.77 | 899.88 | 15377.84 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1221.84 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 8412.62 | 25-JAN-08:04 | 899.88 | 15377.84 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1071.87 |
February | 8439.49 | 28-FEB-08:04 | 899.88 | 15377.84 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1222.16 |
March | 6764.90 | 16-MAR-07:04 | 719.90 | 12302.27 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 879.73 |
April | 6054.16 | 04-APR-07:04 | 719.90 | 12302.27 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 661.53 |
May | 13957.12 | 31-MAY-07:03 | 359.95 | 6151.14 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.23 |
June | 18308.58 | 21-JUN-07:02 | 449.94 | 7688.92 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 216.15 |
July | 17782.02 | 19-JUL-07:02 | 449.94 | 7688.92 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 175.63 |
August | 20444.26 | 06-AUG-08:62 | 449.94 | 7688.92 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 305.74 |
September | 17984.82 | 13-SEP-07:02 | 449.94 | 7688.92 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 227.09 |
October | 4489.62 | 16-OCT-07:03 | 539.93 | 9226.71 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 500.39 |
November | 7178.18 | 21-NOV-08:04 | 719.90 | 12302.27 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 982.75 |
December | 8157.42 | 07-DEC-08:04 | 719.90 | 12302.27 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 973.79 |
Annual Sum or Average | |||||||||||
Minimum of Months | 4489.62 | 359.95 | 6151.14 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.23 | |
Maximum of Months | 20444.26 | 899.88 | 15377.84 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1222.16 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7883.88 | 21-JAN-08:04 | 899.88 | 15377.84 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 994.08 |
February | 8123.96 | 28-FEB-08:04 | 899.88 | 15377.84 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1221.51 |
March | 6539.47 | 21-MAR-07:03 | 809.89 | 13840.06 | 3370.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 896.23 |
April | 6011.25 | 04-APR-07:04 | 719.90 | 12302.27 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 657.54 |
May | 13571.51 | 31-MAY-07:03 | 359.95 | 6151.14 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.78 |
June | 18277.88 | 21-JUN-07:02 | 449.94 | 7688.92 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 213.04 |
July | 17748.58 | 19-JUL-07:02 | 449.94 | 7688.92 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 172.55 |
August | 20448.58 | 06-AUG-08:62 | 449.94 | 7688.92 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 303.01 |
September | 17971.31 | 13-SEP-07:02 | 449.94 | 7688.92 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 224.46 |
October | 4666.48 | 28-OCT-07:03 | 539.93 | 9226.71 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 509.13 |
November | 6542.24 | 22-NOV-08:04 | 719.90 | 12302.27 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 881.41 |
December | 6756.07 | 04-DEC-08:04 | 719.90 | 12302.27 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 841.99 |
Annual Sum or Average | |||||||||||
Minimum of Months | 4666.48 | 359.95 | 6151.14 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.78 | |
Maximum of Months | 20448.58 | 899.88 | 15377.84 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1221.51 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 13341.06 | 05-JAN-09:05 | 3167.59 | 18349.55 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2173.91 |
February | 11436.54 | 09-FEB-09:04 | 3167.59 | 18349.55 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1147.57 |
March | 10630.80 | 11-MAR-09:04 | 3167.59 | 18349.55 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1209.90 |
April | 11422.86 | 01-APR-08:04 | 3167.59 | 18349.55 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1227.99 |
May | 23318.45 | 31-MAY-08:62 | 1979.74 | 11468.47 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.03 |
June | 28855.21 | 20-JUN-08:62 | 1583.79 | 9174.77 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.40 |
July | 31189.95 | 18-JUL-08:62 | 1979.74 | 11468.47 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 250.11 |
August | 31776.85 | 06-AUG-09:02 | 1583.79 | 9174.77 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 557.79 |
September | 31471.38 | 03-SEP-09:02 | 1583.79 | 9174.77 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 328.99 |
October | 9269.18 | 23-OCT-08:03 | 2771.64 | 16055.85 | 5243.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 968.06 |
November | 11516.54 | 12-NOV-10:04 | 3167.59 | 18349.55 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1206.96 |
December | 10384.92 | 01-DEC-09:04 | 3167.59 | 18349.55 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1375.07 |
Annual Sum or Average | |||||||||||
Minimum of Months | 9269.18 | 1583.79 | 9174.77 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.03 | |
Maximum of Months | 31776.85 | 3167.59 | 18349.55 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2173.91 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5835.95 | 12-JAN-09:04 | 1583.79 | 9174.77 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 618.82 |
February | 5732.53 | 09-FEB-09:04 | 1583.79 | 9174.77 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 633.21 |
March | 5808.27 | 10-MAR-09:04 | 1583.79 | 9174.77 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 691.77 |
April | 5702.91 | 04-APR-08:04 | 1583.79 | 9174.77 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 631.88 |
May | 12300.99 | 31-MAY-08:62 | 989.87 | 5734.23 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.20 |
June | 14810.89 | 17-JUN-08:62 | 989.87 | 5734.23 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.47 |
July | 16527.44 | 18-JUL-08:62 | 989.87 | 5734.23 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 133.09 |
August | 15766.76 | 15-AUG-08:62 | 989.87 | 5734.23 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 160.69 |
September | 16235.07 | 12-SEP-08:62 | 989.87 | 5734.23 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 209.91 |
October | 4619.27 | 23-OCT-08:03 | 1385.82 | 8027.93 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 531.77 |
November | 5728.46 | 12-NOV-10:04 | 1583.79 | 9174.77 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 661.68 |
December | 5873.47 | 08-DEC-09:04 | 1583.79 | 9174.77 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 831.56 |
Annual Sum or Average | |||||||||||
Minimum of Months | 4619.27 | 989.87 | 5734.23 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.20 | |
Maximum of Months | 16527.44 | 1583.79 | 9174.77 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 831.56 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5820.82 | 12-JAN-09:04 | 1583.79 | 9174.77 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 617.79 |
February | 5719.92 | 09-FEB-09:04 | 1583.79 | 9174.77 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 631.85 |
March | 5799.83 | 10-MAR-09:04 | 1583.79 | 9174.77 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 691.00 |
April | 5724.36 | 01-APR-08:04 | 1583.79 | 9174.77 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 672.14 |
May | 11715.31 | 31-MAY-08:62 | 989.87 | 5734.23 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.10 |
June | 14158.02 | 17-JUN-08:62 | 989.87 | 5734.23 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.69 |
July | 16344.96 | 18-JUL-08:62 | 989.87 | 5734.23 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 131.72 |
August | 15591.99 | 15-AUG-08:62 | 989.87 | 5734.23 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 159.46 |
September | 16066.17 | 12-SEP-08:62 | 989.87 | 5734.23 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 208.93 |
October | 4658.21 | 23-OCT-08:03 | 1385.82 | 8027.93 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 533.08 |
November | 5773.36 | 12-NOV-10:04 | 1583.79 | 9174.77 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 663.27 |
December | 5642.88 | 01-DEC-09:04 | 1583.79 | 9174.77 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 746.38 |
Annual Sum or Average | |||||||||||
Minimum of Months | 4658.21 | 989.87 | 5734.23 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.10 | |
Maximum of Months | 16344.96 | 1583.79 | 9174.77 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 746.38 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5180.03 | 14-JAN-09:04 | 1583.79 | 9174.77 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 766.62 |
February | 5695.65 | 09-FEB-09:04 | 1583.79 | 9174.77 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 629.85 |
March | 5164.00 | 22-MAR-08:04 | 1583.79 | 9174.77 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 608.99 |
April | 5640.69 | 01-APR-08:04 | 1583.79 | 9174.77 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 662.71 |
May | 6060.31 | 31-MAY-08:62 | 989.87 | 5734.23 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.46 |
June | 12757.63 | 12-JUN-08:62 | 1187.84 | 6881.08 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 116.17 |
July | 15217.02 | 18-JUL-08:62 | 989.87 | 5734.23 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 127.49 |
August | 14203.29 | 29-AUG-08:62 | 989.87 | 5734.23 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 133.48 |
September | 15704.06 | 12-SEP-08:62 | 989.87 | 5734.23 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 205.67 |
October | 4734.55 | 23-OCT-08:03 | 1385.82 | 8027.93 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 534.27 |
November | 5719.67 | 12-NOV-10:04 | 1583.79 | 9174.77 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 656.09 |
December | 5608.66 | 01-DEC-09:04 | 1583.79 | 9174.77 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 743.51 |
Annual Sum or Average | |||||||||||
Minimum of Months | 4734.55 | 989.87 | 5734.23 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.46 | |
Maximum of Months | 15704.06 | 1583.79 | 9174.77 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 766.62 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4937.09 | 13-JAN-09:04 | 1583.79 | 9174.77 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 703.07 |
February | 4953.38 | 26-FEB-10:04 | 1583.79 | 9174.77 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 728.62 |
March | 4668.45 | 30-MAR-08:04 | 1583.79 | 9174.77 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 913.12 |
April | 4860.28 | 22-APR-08:04 | 1583.79 | 9174.77 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 691.00 |
May | 4279.96 | 31-MAY-15:00 | 1241.83 | 2179.01 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 985.26 | 0.00 |
June | 13802.98 | 28-JUN-08:62 | 1187.84 | 6881.08 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.38 |
July | 14406.41 | 01-JUL-08:62 | 1187.84 | 6881.08 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.36 |
August | 14633.11 | 23-AUG-08:62 | 1187.84 | 6881.08 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 142.61 |
September | 15545.57 | 08-SEP-08:62 | 1187.84 | 6881.08 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.40 |
October | 4602.90 | 26-OCT-08:04 | 1583.79 | 9174.77 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 632.51 |
November | 5675.36 | 12-NOV-10:04 | 1583.79 | 9174.77 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 798.07 |
December | 4900.48 | 30-DEC-09:04 | 1583.79 | 9174.77 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 766.24 |
Annual Sum or Average | |||||||||||
Minimum of Months | 4279.96 | 1187.84 | 2179.01 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15545.57 | 1583.79 | 9174.77 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 985.26 | 913.12 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | |
January | 0.797204E+11 | 63496.71 | 04-JAN-16:49 | 0.241658E+12 | 330841.21 | 30-JAN-09:09 |
February | 0.706587E+11 | 65623.25 | 03-FEB-17:00 | 0.172382E+12 | 363273.12 | 02-FEB-09:09 |
March | 0.766835E+11 | 60436.28 | 14-MAR-18:40 | 0.112728E+12 | 239839.17 | 06-MAR-09:09 |
April | 0.733503E+11 | 76687.37 | 18-APR-13:30 | 0.561465E+11 | 207755.10 | 03-APR-08:09 |
May | 0.758440E+11 | 78503.98 | 31-MAY-12:50 | 0.365939E+10 | 100425.52 | 02-MAY-08:09 |
June | 0.867671E+11 | 93474.67 | 11-JUN-14:00 | 0.584229E+09 | 19295.40 | 05-JUN-08:00 |
July | 0.946069E+11 | 94602.51 | 26-JUL-15:20 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.959141E+11 | 105839.69 | 04-AUG-13:39 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 0.818481E+11 | 88917.79 | 06-SEP-14:09 | 0.316111E+10 | 92017.66 | 30-SEP-08:09 |
October | 0.748098E+11 | 58775.51 | 06-OCT-18:00 | 0.252103E+11 | 100242.54 | 28-OCT-08:09 |
November | 0.747222E+11 | 62815.37 | 29-NOV-17:30 | 0.103874E+12 | 257219.86 | 25-NOV-17:00 |
December | 0.789499E+11 | 63103.12 | 20-DEC-16:49 | 0.189231E+12 | 307384.68 | 09-DEC-09:09 |
Annual Sum or Average | 0.963875E+12 | 0.908635E+12 | ||||
Minimum of Months | 0.706587E+11 | 58775.51 | 0.00 | 0.00 | ||
Maximum of Months | 0.959141E+11 | 105839.69 | 0.241658E+12 | 363273.12 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.424448E+11 | 0.997447E+10 | 0.108804E+11 | 0.00 | 0.105904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.583026E+10 | 0.00 |
February | 0.384292E+11 | 0.820286E+10 | 0.985143E+10 | 0.00 | 0.886645E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.530873E+10 | 0.00 |
March | 0.430726E+11 | 0.796609E+10 | 0.110523E+11 | 0.00 | 0.870243E+10 | 0.00 | 0.00 | 32960.12 | 0.00 | 0.00 | 0.00 | 0.589008E+10 | 0.00 |
April | 0.411878E+11 | 0.656581E+10 | 0.105581E+11 | 0.00 | 0.753141E+10 | 0.00 | 0.00 | 0.192979E+10 | 0.00 | 0.00 | 0.00 | 0.557743E+10 | 0.00 |
May | 0.427427E+11 | 0.585044E+10 | 0.109629E+11 | 0.00 | 0.707934E+10 | 0.00 | 0.00 | 0.357269E+10 | 0.00 | 0.00 | 0.00 | 0.563590E+10 | 0.00 |
June | 0.416347E+11 | 0.522350E+10 | 0.106818E+11 | 0.00 | 0.694987E+10 | 0.00 | 0.00 | 0.169270E+11 | 0.00 | 0.00 | 0.00 | 0.535011E+10 | 0.00 |
July | 0.423277E+11 | 0.555871E+10 | 0.108460E+11 | 0.00 | 0.706266E+10 | 0.00 | 0.00 | 0.234231E+11 | 0.00 | 0.00 | 0.00 | 0.538860E+10 | 0.00 |
August | 0.430407E+11 | 0.634521E+10 | 0.110454E+11 | 0.00 | 0.726113E+10 | 0.00 | 0.00 | 0.228220E+11 | 0.00 | 0.00 | 0.00 | 0.539963E+10 | 0.00 |
September | 0.412197E+11 | 0.719916E+10 | 0.105649E+11 | 0.00 | 0.682566E+10 | 0.00 | 0.00 | 0.108058E+11 | 0.00 | 0.00 | 0.00 | 0.523275E+10 | 0.00 |
October | 0.424448E+11 | 0.862027E+10 | 0.108804E+11 | 0.00 | 0.726741E+10 | 0.00 | 0.00 | 88270078.57 | 0.00 | 0.00 | 0.00 | 0.550865E+10 | 0.00 |
November | 0.411240E+11 | 0.936171E+10 | 0.105443E+11 | 0.00 | 0.824338E+10 | 0.00 | 0.00 | 313029.60 | 0.00 | 0.00 | 0.00 | 0.544852E+10 | 0.00 |
December | 0.423596E+11 | 0.102536E+11 | 0.108529E+11 | 0.00 | 0.974269E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.574098E+10 | 0.00 |
Annual Sum or Average | 0.502028E+12 | 0.911219E+11 | 0.128721E+12 | 0.961229E+11 | 0.00 | 0.795691E+11 | 0.663116E+11 | ||||||
Minimum of Months | 0.384292E+11 | 0.522350E+10 | 0.985143E+10 | 0.00 | 0.682566E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.523275E+10 | 0.00 |
Maximum of Months | 0.430726E+11 | 0.102536E+11 | 0.110523E+11 | 0.00 | 0.105904E+11 | 0.00 | 0.00 | 0.234231E+11 | 0.00 | 0.00 | 0.00 | 0.589008E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS [J] | COOLING:GAS [] | WATERSYSTEMS:GAS [] | COGENERATION:GAS [] | HUMIDIFIER:GAS [] | |
January | 0.00 | 0.00 | 0.241658E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.172382E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.112728E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.561465E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.365939E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.584229E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.316111E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.252103E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.103874E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.189231E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.908635E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.241658E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum}[W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum}[W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum}[W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum}[W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 31196.17 | 01-JAN-11:09 | 6944.63 | 01-JAN-06:10 | 8089.53 | 01-JAN-11:09 | 0.00 | 9821.26 | 30-JAN-09:09 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 31196.17 | 01-FEB-10:09 | 6944.63 | 01-FEB-06:10 | 8089.53 | 01-FEB-10:09 | 0.00 | 10318.75 | 02-FEB-09:09 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 31196.17 | 01-MAR-10:09 | 6944.63 | 01-MAR-06:10 | 8089.53 | 01-MAR-10:09 | 0.00 | 8423.94 | 06-MAR-09:09 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 31196.17 | 01-APR-09:09 | 6944.63 | 01-APR-05:10 | 8089.53 | 01-APR-09:09 | 0.00 | 7932.00 | 03-APR-08:09 | 0.00 | 0.00 | 01-APR-00:10 |
May | 31196.17 | 01-MAY-09:09 | 6944.63 | 01-MAY-19:10 | 8089.53 | 01-MAY-09:09 | 0.00 | 6286.39 | 02-MAY-08:09 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 31196.17 | 01-JUN-09:09 | 6944.63 | 01-JUN-19:40 | 8089.53 | 01-JUN-09:09 | 0.00 | 7253.37 | 11-JUN-14:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 31196.17 | 01-JUL-09:09 | 6944.63 | 01-JUL-19:00 | 8089.53 | 01-JUL-09:09 | 0.00 | 7156.84 | 26-JUL-16:10 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 31196.17 | 01-AUG-09:09 | 6944.63 | 01-AUG-19:40 | 8089.53 | 01-AUG-09:09 | 0.00 | 9058.79 | 04-AUG-12:00 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 31196.17 | 01-SEP-09:09 | 6944.63 | 01-SEP-05:10 | 8089.53 | 01-SEP-09:09 | 0.00 | 6381.57 | 11-SEP-08:09 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 31196.17 | 01-OCT-10:09 | 6944.63 | 01-OCT-05:10 | 8089.53 | 01-OCT-10:09 | 0.00 | 6284.75 | 28-OCT-08:09 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 31196.17 | 01-NOV-09:09 | 6944.63 | 01-NOV-05:10 | 8089.53 | 01-NOV-09:09 | 0.00 | 8699.95 | 25-NOV-17:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 31196.17 | 01-DEC-10:09 | 6944.63 | 01-DEC-06:10 | 8089.53 | 01-DEC-10:09 | 0.00 | 9460.36 | 09-DEC-09:09 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 31196.17 | 6944.63 | 8089.53 | 0.00 | 6284.75 | 0.00 | 0.00 | |||||
Maximum of Months | 31196.17 | 6944.63 | 8089.53 | 0.00 | 10318.75 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum}[W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum}[W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 11776.38 | 15-JAN-12:20 | 0.00 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 10274.55 | 10-FEB-14:30 | 0.00 |
March | 35.57 | 19-MAR-22:10 | 0.00 | 0.00 | 0.00 | 11887.88 | 30-MAR-13:39 | 0.00 |
April | 25970.97 | 18-APR-14:09 | 0.00 | 0.00 | 0.00 | 9618.43 | 03-APR-13:20 | 0.00 |
May | 27137.95 | 31-MAY-14:00 | 0.00 | 0.00 | 0.00 | 9733.64 | 22-MAY-13:30 | 0.00 |
June | 43609.04 | 11-JUN-14:00 | 0.00 | 0.00 | 0.00 | 9658.18 | 15-JUN-10:50 | 0.00 |
July | 41362.49 | 26-JUL-14:00 | 0.00 | 0.00 | 0.00 | 8756.70 | 17-JUL-18:19 | 0.00 |
August | 51271.75 | 04-AUG-15:00 | 0.00 | 0.00 | 0.00 | 9711.18 | 19-AUG-12:09 | 0.00 |
September | 36219.62 | 06-SEP-14:09 | 0.00 | 0.00 | 0.00 | 9693.96 | 22-SEP-11:30 | 0.00 |
October | 7888.89 | 20-OCT-14:00 | 0.00 | 0.00 | 0.00 | 9716.96 | 02-OCT-13:09 | 0.00 |
November | 136.59 | 07-NOV-23:49 | 0.00 | 0.00 | 0.00 | 9701.76 | 29-NOV-17:30 | 0.00 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 9900.72 | 20-DEC-14:09 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 8756.70 | 0.00 | ||
Maximum of Months | 51271.75 | 0.00 | 0.00 | 0.00 | 11887.88 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 63496.71 | 04-JAN-16:49 | 31196.17 | 8089.53 | 6944.63 | 0.00 | 7563.85 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 65623.25 | 03-FEB-17:00 | 31196.17 | 8089.53 | 6944.63 | 0.00 | 9679.08 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 60436.28 | 14-MAR-18:40 | 31196.17 | 8089.53 | 6944.63 | 0.00 | 6001.46 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 76687.37 | 18-APR-13:30 | 31196.17 | 8089.53 | 0.00 | 0.00 | 4748.33 | 0.00 | 0.00 | 25267.98 | 0.00 |
May | 78503.98 | 31-MAY-12:50 | 31196.17 | 8089.53 | 0.00 | 0.00 | 4748.33 | 0.00 | 0.00 | 26865.61 | 0.00 |
June | 93474.67 | 11-JUN-14:00 | 31196.17 | 8089.53 | 0.00 | 0.00 | 7253.37 | 0.00 | 0.00 | 43609.04 | 0.00 |
July | 94602.51 | 26-JUL-15:20 | 31196.17 | 8089.53 | 0.00 | 0.00 | 7110.30 | 0.00 | 0.00 | 41239.28 | 0.00 |
August | 105839.69 | 04-AUG-13:39 | 31196.17 | 8089.53 | 0.00 | 0.00 | 8969.34 | 0.00 | 0.00 | 51081.61 | 0.00 |
September | 88917.79 | 06-SEP-14:09 | 31196.17 | 8089.53 | 0.00 | 0.00 | 5844.99 | 0.00 | 0.00 | 36219.62 | 0.00 |
October | 58775.51 | 06-OCT-18:00 | 31196.17 | 8089.53 | 6944.63 | 0.00 | 5089.21 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 62815.37 | 29-NOV-17:30 | 31196.17 | 8089.53 | 6944.63 | 0.00 | 6883.28 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 63103.12 | 20-DEC-16:49 | 31196.17 | 8089.53 | 6944.63 | 0.00 | 7379.54 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 58775.51 | 31196.17 | 8089.53 | 0.00 | 0.00 | 4748.33 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 105839.69 | 31196.17 | 8089.53 | 6944.63 | 0.00 | 9679.08 | 0.00 | 0.00 | 51081.61 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS {Maximum}[W] | HEATING:GAS {TIMESTAMP} | COOLING:GAS [] | WATERSYSTEMS:GAS [] | COGENERATION:GAS [] | |
January | 0.00 | 0.00 | 330841.21 | 30-JAN-09:09 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 363273.12 | 02-FEB-09:09 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 239839.17 | 06-MAR-09:09 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 207755.10 | 03-APR-08:09 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 100425.52 | 02-MAY-08:09 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 19295.40 | 05-JUN-08:00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 92017.66 | 30-SEP-08:09 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 100242.54 | 28-OCT-08:09 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 257219.86 | 25-NOV-17:00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 307384.68 | 09-DEC-09:09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 363273.12 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.17 | 20.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 2.00 | 20.33 | 0.33 | 20.52 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 1.17 | 20.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.33 | 20.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.17 | 20.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.49 | 0.33 | 24.49 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.83 | 20.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1.50 | 17.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 8.17 | 19.89 | 0.33 | 20.52 | 0.33 | 24.49 | 0.33 | 24.49 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.17 | 20.47 | 0.33 | 20.52 | 0.33 | 24.49 | 0.33 | 24.49 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.17 | 20.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.67 | 20.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 1.00 | 20.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.17 | 20.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.33 | 20.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1.00 | 20.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4.33 | 20.45 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.17 | 20.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.52 | 0.17 | 24.52 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.17 | 24.52 | 0.17 | 24.52 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.52 | 0.17 | 24.52 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.49 | 0.33 | 24.49 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.33 | 24.49 | 0.33 | 24.49 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.49 | 0.33 | 24.49 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.45 | 0.17 | 24.45 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.17 | 24.45 | 0.17 | 24.45 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.45 | 0.17 | 24.45 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.33 | 20.51 | 0.33 | 20.51 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.46 | 0.17 | 24.46 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.33 | 20.51 | 0.33 | 20.51 | 0.17 | 24.46 | 0.17 | 24.46 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.33 | 20.51 | 0.33 | 20.51 | 0.17 | 24.46 | 0.17 | 24.46 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.17 | 20.52 | 0.17 | 20.52 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.17 | 20.52 | 0.17 | 20.52 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 20.52 | 0.17 | 20.52 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.33 | 14.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.33 | 17.75 | 0.17 | 20.51 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.67 | 16.36 | 0.17 | 20.51 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.33 | 17.75 | 0.17 | 20.51 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.50 | 14.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.33 | 20.50 | 0.33 | 20.50 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.83 | 17.19 | 0.33 | 20.50 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.50 | 20.50 | 0.33 | 20.50 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 27.00 | 14.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16.00 | 14.88 | 0.33 | 20.49 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 3.33 | 14.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.83 | 14.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 4.50 | 14.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 13.00 | 14.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 64.67 | 14.80 | 0.33 | 20.49 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 27.00 | 14.99 | 0.33 | 20.49 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: LGSTORE1
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 496.00 | 20.91 | 472.00 | 20.90 | 472.00 | 20.90 |
February | 448.00 | 20.93 | 353.00 | 20.88 | 353.00 | 20.88 |
March | 496.00 | 21.03 | 287.17 | 20.86 | 287.17 | 20.86 |
April | 419.33 | 21.25 | 161.50 | 21.54 | 121.33 | 20.76 |
May | 273.17 | 22.39 | 154.33 | 23.75 | 13.33 | 22.45 |
June | 137.00 | 22.80 | 341.50 | 23.92 | 40.17 | 24.04 |
July | 64.33 | 24.06 | 483.83 | 23.92 | 64.17 | 24.06 |
August | 78.17 | 24.03 | 463.17 | 23.92 | 75.67 | 24.04 |
September | 161.00 | 22.11 | 226.67 | 23.87 | 3.83 | 21.63 |
October | 462.33 | 21.49 | 23.83 | 20.57 | 22.83 | 20.42 |
November | 480.00 | 21.16 | 198.50 | 20.86 | 198.50 | 20.86 |
December | 496.00 | 20.92 | 448.00 | 20.90 | 448.00 | 20.90 |
Annual Sum or Average | 4011.33 | 21.39 | 3613.50 | 22.30 | 2100.00 | 21.16 |
Minimum of Months | 64.33 | 20.91 | 23.83 | 20.57 | 3.83 | 20.42 |
Maximum of Months | 496.00 | 24.06 | 483.83 | 23.92 | 472.00 | 24.06 |
Report: ComfortReportSimple55Monthly
For: SMSTORE1
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 496.00 | 21.04 | 413.17 | 20.96 | 413.17 | 20.96 |
February | 448.00 | 21.17 | 241.83 | 20.93 | 241.83 | 20.93 |
March | 496.00 | 21.45 | 161.00 | 20.91 | 161.00 | 20.91 |
April | 410.83 | 21.82 | 76.33 | 22.31 | 38.00 | 20.74 |
May | 196.00 | 22.91 | 185.50 | 23.85 | 8.67 | 23.35 |
June | 79.67 | 23.02 | 334.33 | 23.92 | 15.00 | 23.89 |
July | 16.00 | 23.88 | 469.67 | 23.89 | 15.67 | 23.89 |
August | 40.33 | 23.97 | 450.67 | 23.90 | 39.33 | 23.98 |
September | 133.17 | 22.63 | 195.83 | 23.91 | 0.00 | 0.00 |
October | 434.83 | 22.16 | 5.33 | 22.59 | 2.33 | 20.94 |
November | 474.17 | 21.65 | 129.50 | 20.92 | 129.50 | 20.92 |
December | 496.00 | 21.18 | 300.83 | 20.96 | 300.83 | 20.96 |
Annual Sum or Average | 3721.00 | 21.66 | 2964.00 | 22.61 | 1365.33 | 21.10 |
Minimum of Months | 16.00 | 21.04 | 5.33 | 20.91 | 0.00 | 0.00 |
Maximum of Months | 496.00 | 23.97 | 469.67 | 23.92 | 413.17 | 23.98 |
Report: ComfortReportSimple55Monthly
For: SMSTORE2
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 371.00 | 21.11 | 348.00 | 21.11 | 348.00 | 21.11 |
February | 336.00 | 21.11 | 231.33 | 21.11 | 231.33 | 21.11 |
March | 379.00 | 21.19 | 174.50 | 21.11 | 174.50 | 21.11 |
April | 313.00 | 21.38 | 89.00 | 22.09 | 59.33 | 21.11 |
May | 181.00 | 22.60 | 128.17 | 23.91 | 7.50 | 23.44 |
June | 93.83 | 22.94 | 270.33 | 24.03 | 27.33 | 24.12 |
July | 43.00 | 24.17 | 365.17 | 24.02 | 42.83 | 24.17 |
August | 58.00 | 24.02 | 359.33 | 24.00 | 56.67 | 24.03 |
September | 113.33 | 22.11 | 172.33 | 24.01 | 0.67 | 21.11 |
October | 346.33 | 21.54 | 5.83 | 21.11 | 5.83 | 21.11 |
November | 360.00 | 21.31 | 130.50 | 21.11 | 130.50 | 21.11 |
December | 369.00 | 21.11 | 313.17 | 21.11 | 313.17 | 21.11 |
Annual Sum or Average | 2963.50 | 21.51 | 2587.67 | 22.59 | 1397.67 | 21.39 |
Minimum of Months | 43.00 | 21.11 | 5.83 | 21.11 | 0.67 | 21.11 |
Maximum of Months | 379.00 | 24.17 | 365.17 | 24.03 | 348.00 | 24.17 |
Report: ComfortReportSimple55Monthly
For: SMSTORE3
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 371.00 | 21.11 | 350.83 | 21.11 | 350.83 | 21.11 |
February | 336.00 | 21.11 | 249.50 | 21.10 | 249.50 | 21.10 |
March | 379.00 | 21.18 | 190.33 | 21.11 | 190.33 | 21.11 |
April | 313.50 | 21.36 | 97.33 | 21.97 | 69.17 | 21.11 |
May | 191.17 | 22.54 | 122.33 | 23.89 | 8.50 | 23.32 |
June | 95.33 | 22.85 | 268.67 | 24.03 | 27.17 | 24.12 |
July | 42.50 | 24.18 | 365.00 | 24.02 | 42.33 | 24.18 |
August | 57.50 | 24.02 | 359.33 | 24.00 | 56.17 | 24.03 |
September | 116.33 | 22.06 | 172.83 | 24.00 | 1.17 | 21.11 |
October | 355.67 | 21.52 | 8.83 | 21.11 | 8.83 | 21.11 |
November | 360.00 | 21.27 | 142.83 | 21.11 | 142.83 | 21.11 |
December | 369.00 | 21.11 | 328.00 | 21.11 | 328.00 | 21.11 |
Annual Sum or Average | 2987.00 | 21.49 | 2655.83 | 22.54 | 1474.83 | 21.37 |
Minimum of Months | 42.50 | 21.11 | 8.83 | 21.10 | 1.17 | 21.10 |
Maximum of Months | 379.00 | 24.18 | 365.00 | 24.03 | 350.83 | 24.18 |
Report: ComfortReportSimple55Monthly
For: SMSTORE4
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 371.00 | 21.11 | 352.00 | 21.10 | 352.00 | 21.10 |
February | 336.00 | 21.11 | 264.50 | 21.11 | 264.50 | 21.11 |
March | 379.00 | 21.16 | 200.17 | 21.11 | 200.17 | 21.11 |
April | 315.17 | 21.34 | 107.00 | 21.86 | 79.67 | 21.11 |
May | 209.67 | 22.45 | 113.50 | 23.85 | 9.67 | 23.10 |
June | 102.50 | 22.79 | 261.83 | 24.03 | 29.83 | 24.10 |
July | 46.50 | 24.15 | 364.17 | 24.02 | 46.33 | 24.15 |
August | 67.33 | 24.00 | 356.00 | 24.00 | 65.83 | 24.01 |
September | 124.67 | 22.06 | 171.33 | 23.99 | 1.83 | 21.31 |
October | 360.83 | 21.49 | 12.67 | 21.11 | 12.67 | 21.11 |
November | 360.00 | 21.22 | 155.17 | 21.11 | 155.17 | 21.11 |
December | 369.00 | 21.11 | 339.50 | 21.11 | 339.50 | 21.11 |
Annual Sum or Average | 3041.67 | 21.50 | 2697.83 | 22.49 | 1557.17 | 21.39 |
Minimum of Months | 46.50 | 21.11 | 12.67 | 21.10 | 1.83 | 21.10 |
Maximum of Months | 379.00 | 24.15 | 364.17 | 24.03 | 352.00 | 24.15 |
Report: ComfortReportSimple55Monthly
For: LGSTORE2
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.10 | 328.17 | 21.10 | 328.17 | 21.10 |
February | 308.00 | 21.10 | 274.83 | 21.10 | 274.83 | 21.10 |
March | 348.00 | 21.15 | 216.50 | 21.10 | 216.50 | 21.10 |
April | 291.50 | 21.31 | 110.17 | 21.75 | 86.00 | 21.11 |
May | 220.00 | 22.33 | 75.17 | 23.75 | 13.50 | 23.03 |
June | 100.50 | 22.67 | 224.67 | 23.95 | 32.50 | 24.06 |
July | 53.17 | 23.97 | 333.33 | 23.94 | 53.00 | 23.97 |
August | 71.00 | 23.92 | 324.67 | 23.92 | 70.17 | 23.93 |
September | 120.50 | 21.95 | 152.17 | 23.94 | 1.33 | 21.12 |
October | 336.50 | 21.45 | 12.00 | 21.12 | 12.00 | 21.12 |
November | 330.00 | 21.17 | 170.00 | 21.11 | 170.00 | 21.11 |
December | 338.00 | 21.10 | 324.67 | 21.10 | 324.67 | 21.10 |
Annual Sum or Average | 2857.17 | 21.49 | 2546.33 | 22.36 | 1582.67 | 21.40 |
Minimum of Months | 53.17 | 21.10 | 12.00 | 21.10 | 1.33 | 21.10 |
Maximum of Months | 348.00 | 23.97 | 333.33 | 23.95 | 328.17 | 24.06 |
Report: ComfortReportSimple55Monthly
For: SMSTORE5
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.10 | 328.17 | 21.10 | 328.17 | 21.10 |
February | 308.00 | 21.11 | 275.17 | 21.10 | 275.17 | 21.10 |
March | 348.00 | 21.14 | 220.17 | 21.11 | 220.17 | 21.11 |
April | 294.33 | 21.33 | 112.33 | 21.71 | 89.67 | 21.12 |
May | 235.33 | 22.34 | 69.83 | 23.70 | 14.67 | 22.92 |
June | 104.17 | 22.67 | 207.17 | 23.95 | 33.83 | 24.01 |
July | 58.00 | 23.95 | 330.17 | 23.94 | 57.67 | 23.95 |
August | 75.67 | 23.92 | 315.00 | 23.92 | 74.50 | 23.92 |
September | 123.67 | 21.99 | 144.00 | 23.93 | 1.67 | 21.12 |
October | 337.17 | 21.44 | 14.83 | 21.12 | 14.83 | 21.12 |
November | 330.00 | 21.17 | 174.33 | 21.11 | 174.33 | 21.11 |
December | 338.00 | 21.11 | 324.83 | 21.10 | 324.83 | 21.10 |
Annual Sum or Average | 2892.33 | 21.50 | 2516.00 | 22.33 | 1609.50 | 21.42 |
Minimum of Months | 58.00 | 21.10 | 14.83 | 21.10 | 1.67 | 21.10 |
Maximum of Months | 348.00 | 23.95 | 330.17 | 23.95 | 328.17 | 24.01 |
Report: ComfortReportSimple55Monthly
For: SMSTORE6
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.10 | 329.33 | 21.10 | 329.33 | 21.10 |
February | 308.00 | 21.11 | 278.00 | 21.10 | 278.00 | 21.10 |
March | 348.00 | 21.14 | 225.00 | 21.11 | 225.00 | 21.11 |
April | 297.00 | 21.33 | 116.67 | 21.67 | 94.67 | 21.12 |
May | 254.00 | 22.31 | 67.17 | 23.66 | 15.00 | 22.81 |
June | 106.50 | 22.63 | 199.33 | 23.96 | 35.17 | 24.01 |
July | 59.50 | 23.95 | 329.00 | 23.94 | 59.17 | 23.95 |
August | 78.17 | 23.92 | 312.33 | 23.92 | 76.67 | 23.92 |
September | 125.83 | 21.96 | 139.83 | 23.93 | 1.83 | 21.12 |
October | 337.83 | 21.43 | 16.33 | 21.11 | 16.33 | 21.11 |
November | 330.00 | 21.17 | 181.83 | 21.11 | 181.83 | 21.11 |
December | 338.00 | 21.10 | 326.50 | 21.10 | 326.50 | 21.10 |
Annual Sum or Average | 2922.83 | 21.51 | 2521.33 | 22.30 | 1639.50 | 21.42 |
Minimum of Months | 59.50 | 21.10 | 16.33 | 21.10 | 1.83 | 21.10 |
Maximum of Months | 348.00 | 23.95 | 329.33 | 23.96 | 329.33 | 24.01 |
Report: ComfortReportSimple55Monthly
For: SMSTORE7
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.10 | 333.17 | 21.10 | 333.17 | 21.10 |
February | 308.00 | 21.10 | 283.67 | 21.10 | 283.67 | 21.10 |
March | 348.00 | 21.13 | 239.17 | 21.10 | 239.17 | 21.10 |
April | 299.83 | 21.31 | 142.17 | 21.52 | 122.83 | 21.12 |
May | 286.83 | 22.22 | 61.00 | 23.48 | 21.00 | 22.67 |
June | 113.17 | 22.57 | 187.17 | 23.96 | 38.17 | 23.99 |
July | 67.00 | 23.93 | 325.50 | 23.94 | 66.50 | 23.93 |
August | 82.67 | 23.91 | 308.00 | 23.92 | 80.50 | 23.92 |
September | 135.00 | 21.96 | 134.83 | 23.91 | 2.67 | 21.11 |
October | 339.00 | 21.39 | 22.67 | 21.11 | 22.67 | 21.11 |
November | 330.00 | 21.15 | 197.00 | 21.11 | 197.00 | 21.11 |
December | 338.00 | 21.10 | 328.50 | 21.10 | 328.50 | 21.10 |
Annual Sum or Average | 2987.50 | 21.51 | 2562.83 | 22.24 | 1735.83 | 21.43 |
Minimum of Months | 67.00 | 21.10 | 22.67 | 21.10 | 2.67 | 21.10 |
Maximum of Months | 348.00 | 23.93 | 333.17 | 23.96 | 333.17 | 23.99 |
Report: ComfortReportSimple55Monthly
For: SMSTORE8
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.10 | 340.00 | 21.10 | 340.00 | 21.10 |
February | 308.00 | 21.10 | 303.17 | 21.10 | 303.17 | 21.10 |
March | 348.00 | 21.11 | 286.67 | 21.11 | 286.67 | 21.11 |
April | 309.00 | 21.30 | 217.50 | 21.32 | 204.33 | 21.14 |
May | 306.67 | 21.95 | 61.17 | 22.87 | 37.17 | 22.20 |
June | 138.83 | 22.58 | 179.17 | 23.95 | 50.00 | 23.93 |
July | 91.33 | 23.83 | 307.00 | 23.94 | 82.33 | 23.90 |
August | 99.83 | 23.87 | 299.50 | 23.92 | 91.17 | 23.91 |
September | 145.83 | 21.89 | 128.50 | 23.86 | 5.00 | 21.11 |
October | 340.00 | 21.34 | 50.33 | 21.11 | 50.33 | 21.11 |
November | 330.00 | 21.13 | 226.17 | 21.11 | 226.17 | 21.11 |
December | 338.00 | 21.10 | 338.00 | 21.10 | 338.00 | 21.10 |
Annual Sum or Average | 3095.50 | 21.51 | 2737.17 | 22.10 | 2014.33 | 21.44 |
Minimum of Months | 91.33 | 21.10 | 50.33 | 21.10 | 5.00 | 21.10 |
Maximum of Months | 348.00 | 23.87 | 340.00 | 23.95 | 340.00 | 23.93 |
Report: OccupantComfortDataSummaryMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 496.00000 | 20.88108 | 10.35117 | -0.7535 | 17.68069 |
February | 448.00000 | 20.90074 | 14.87704 | -0.6835 | 15.63843 |
March | 496.00000 | 21.01095 | 21.58993 | -0.5641 | 12.67179 |
April | 480.00000 | 21.57283 | 29.97996 | -0.3247 | 10.09035 |
May | 496.00000 | 23.04342 | 43.66402 | -0.8050 | 21.48161 |
June | 480.00000 | 23.58780 | 50.04019 | -0.4977 | 12.09561 |
July | 496.00000 | 23.92906 | 54.09586 | -0.3186 | 7.24507 |
August | 496.00000 | 23.93055 | 52.27548 | -0.3256 | 7.39254 |
September | 480.00000 | 23.30259 | 37.60094 | -0.6659 | 17.76068 |
October | 496.00000 | 21.64854 | 29.28415 | -0.2410 | 7.58065 |
November | 480.00000 | 21.14821 | 22.79926 | -0.4852 | 11.32241 |
December | 496.00000 | 20.90187 | 13.11412 | -0.6899 | 15.66196 |
Annual Sum or Average | 5840.00000 | 22.16239 | 31.73913 | -0.5287 | 13.03313 |
Minimum of Months | 448.00000 | 20.88108 | 10.35117 | -0.8050 | 7.24507 |
Maximum of Months | 496.00000 | 23.93055 | 54.09586 | -0.2410 | 21.48161 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 496.00000 | 21.00455 | 11.45276 | -0.6638 | 14.88911 |
February | 448.00000 | 21.14435 | 15.92807 | -0.5739 | 12.71245 |
March | 496.00000 | 21.41758 | 22.25417 | -0.4312 | 10.14359 |
April | 480.00000 | 22.09044 | 30.00673 | -0.1840 | 8.23565 |
May | 496.00000 | 23.47771 | 42.39290 | -0.6548 | 15.84673 |
June | 480.00000 | 23.75301 | 47.99323 | -0.4530 | 10.18660 |
July | 496.00000 | 23.89637 | 51.76391 | -0.3449 | 7.66331 |
August | 496.00000 | 23.90495 | 50.37083 | -0.3506 | 7.77604 |
September | 480.00000 | 23.52748 | 36.66839 | -0.6079 | 14.89288 |
October | 496.00000 | 22.34749 | 29.18389 | -0.0918 | 6.57600 |
November | 480.00000 | 21.65133 | 23.08718 | -0.3521 | 9.42566 |
December | 496.00000 | 21.14631 | 14.22175 | -0.5858 | 12.83582 |
Annual Sum or Average | 5840.00000 | 22.45412 | 31.36849 | -0.4405 | 10.92006 |
Minimum of Months | 448.00000 | 21.00455 | 11.45276 | -0.6638 | 6.57600 |
Maximum of Months | 496.00000 | 23.90495 | 51.76391 | -0.0918 | 15.84673 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 21.06847 | 9.67444 | -0.6922 | 15.36233 |
February | 336.00000 | 21.07476 | 14.34378 | -0.6211 | 13.48935 |
March | 379.00000 | 21.16376 | 20.65026 | -0.5075 | 10.96958 |
April | 360.00000 | 21.71020 | 29.35689 | -0.2729 | 9.08542 |
May | 375.00000 | 23.26656 | 43.02320 | -0.7221 | 18.45865 |
June | 366.00000 | 23.72179 | 49.30869 | -0.4548 | 11.02256 |
July | 369.00000 | 24.01846 | 53.66009 | -0.2953 | 7.08695 |
August | 379.00000 | 23.99488 | 51.84750 | -0.3126 | 7.29945 |
September | 360.00000 | 23.38551 | 37.08587 | -0.6444 | 17.06639 |
October | 371.00000 | 21.69899 | 29.08444 | -0.2260 | 7.23084 |
November | 360.00000 | 21.30065 | 22.85701 | -0.4390 | 10.17476 |
December | 369.00000 | 21.07396 | 12.47218 | -0.6367 | 13.79064 |
Annual Sum or Average | 4395.00000 | 22.30077 | 31.26441 | -0.4845 | 11.73517 |
Minimum of Months | 336.00000 | 21.06847 | 9.67444 | -0.7221 | 7.08695 |
Maximum of Months | 379.00000 | 24.01846 | 53.66009 | -0.2260 | 18.45865 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 21.06777 | 9.67530 | -0.7039 | 15.70774 |
February | 336.00000 | 21.07233 | 14.34721 | -0.6336 | 13.82251 |
March | 379.00000 | 21.15047 | 20.67579 | -0.5213 | 11.24633 |
April | 360.00000 | 21.68385 | 29.43696 | -0.2879 | 9.26038 |
May | 375.00000 | 23.19527 | 43.25362 | -0.7532 | 19.54473 |
June | 366.00000 | 23.69219 | 49.41343 | -0.4666 | 11.47084 |
July | 369.00000 | 24.01812 | 53.63884 | -0.2957 | 7.09489 |
August | 379.00000 | 23.99413 | 51.85143 | -0.3135 | 7.31092 |
September | 360.00000 | 23.35514 | 37.14291 | -0.6573 | 17.61833 |
October | 371.00000 | 21.61987 | 29.25218 | -0.2529 | 7.40485 |
November | 360.00000 | 21.24983 | 22.97801 | -0.4615 | 10.48105 |
December | 369.00000 | 21.07122 | 12.47501 | -0.6490 | 14.13119 |
Annual Sum or Average | 4395.00000 | 22.27502 | 31.32943 | -0.4989 | 12.07324 |
Minimum of Months | 336.00000 | 21.06777 | 9.67530 | -0.7532 | 7.09489 |
Maximum of Months | 379.00000 | 24.01812 | 53.63884 | -0.2529 | 19.54473 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 21.06719 | 9.67608 | -0.7169 | 16.10432 |
February | 336.00000 | 21.07083 | 14.34912 | -0.6472 | 14.19790 |
March | 379.00000 | 21.13662 | 20.70192 | -0.5371 | 11.58494 |
April | 360.00000 | 21.64952 | 29.55153 | -0.3058 | 9.46364 |
May | 375.00000 | 23.07343 | 43.66099 | -0.8016 | 21.26463 |
June | 366.00000 | 23.65217 | 49.71566 | -0.4843 | 12.04882 |
July | 369.00000 | 24.01259 | 53.90951 | -0.3008 | 7.15102 |
August | 379.00000 | 23.98792 | 52.12293 | -0.3188 | 7.37769 |
September | 360.00000 | 23.31018 | 37.30269 | -0.6771 | 18.35709 |
October | 371.00000 | 21.55134 | 29.39744 | -0.2762 | 7.57840 |
November | 360.00000 | 21.20587 | 23.08263 | -0.4829 | 10.82005 |
December | 369.00000 | 21.06929 | 12.47684 | -0.6625 | 14.51423 |
Annual Sum or Average | 4395.00000 | 22.24289 | 31.48142 | -0.5168 | 12.52170 |
Minimum of Months | 336.00000 | 21.06719 | 9.67608 | -0.8016 | 7.15102 |
Maximum of Months | 379.00000 | 24.01259 | 53.90951 | -0.2762 | 21.26463 |
Report: OccupantComfortDataSummaryMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.06165 | 10.44030 | -0.7547 | 17.26324 |
February | 308.00000 | 21.06358 | 15.15268 | -0.6833 | 15.19900 |
March | 348.00000 | 21.11177 | 21.59224 | -0.5719 | 12.38133 |
April | 330.00000 | 21.59634 | 30.50485 | -0.3394 | 9.93650 |
May | 344.00000 | 22.86405 | 45.12570 | -0.8833 | 24.19110 |
June | 336.00000 | 23.54889 | 50.64906 | -0.5218 | 13.08864 |
July | 338.00000 | 23.95066 | 54.59000 | -0.3220 | 7.36627 |
August | 348.00000 | 23.92893 | 52.77745 | -0.3383 | 7.58588 |
September | 330.00000 | 23.21209 | 37.94048 | -0.7132 | 19.65987 |
October | 340.00000 | 21.46227 | 30.42698 | -0.3075 | 7.83212 |
November | 330.00000 | 21.14839 | 23.99458 | -0.5225 | 11.59671 |
December | 338.00000 | 21.06264 | 13.26052 | -0.6999 | 15.58246 |
Annual Sum or Average | 4030.00000 | 22.17811 | 32.36291 | -0.5540 | 13.45712 |
Minimum of Months | 308.00000 | 21.06165 | 10.44030 | -0.8833 | 7.36627 |
Maximum of Months | 348.00000 | 23.95066 | 54.59000 | -0.3075 | 24.19110 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.06193 | 10.38847 | -0.7485 | 17.06509 |
February | 308.00000 | 21.06377 | 15.10149 | -0.6811 | 15.12507 |
March | 348.00000 | 21.10893 | 21.54932 | -0.5758 | 12.44782 |
April | 330.00000 | 21.58752 | 30.49278 | -0.3492 | 10.01749 |
May | 344.00000 | 22.80794 | 45.28359 | -0.9194 | 25.55385 |
June | 336.00000 | 23.53847 | 50.76875 | -0.5455 | 13.64702 |
July | 338.00000 | 23.94925 | 54.78216 | -0.3434 | 7.65271 |
August | 348.00000 | 23.92800 | 52.97312 | -0.3597 | 7.89115 |
September | 330.00000 | 23.20637 | 37.94425 | -0.7355 | 20.27597 |
October | 340.00000 | 21.45246 | 30.39782 | -0.3203 | 7.98078 |
November | 330.00000 | 21.14600 | 23.94632 | -0.5272 | 11.65239 |
December | 338.00000 | 21.06296 | 13.20709 | -0.6965 | 15.47684 |
Annual Sum or Average | 4030.00000 | 22.16986 | 32.39581 | -0.5662 | 13.71909 |
Minimum of Months | 308.00000 | 21.06193 | 10.38847 | -0.9194 | 7.65271 |
Maximum of Months | 348.00000 | 23.94925 | 54.78216 | -0.3203 | 25.55385 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.06184 | 10.38865 | -0.7512 | 17.14961 |
February | 308.00000 | 21.06352 | 15.10215 | -0.6849 | 15.23189 |
March | 348.00000 | 21.10389 | 21.56001 | -0.5822 | 12.59104 |
April | 330.00000 | 21.57030 | 30.55014 | -0.3594 | 10.14064 |
May | 344.00000 | 22.70922 | 45.61622 | -0.9595 | 27.15481 |
June | 336.00000 | 23.51683 | 50.92949 | -0.5577 | 14.06279 |
July | 338.00000 | 23.94687 | 54.91334 | -0.3482 | 7.72072 |
August | 348.00000 | 23.92608 | 53.08314 | -0.3642 | 7.95909 |
September | 330.00000 | 23.18337 | 38.02231 | -0.7476 | 20.73658 |
October | 340.00000 | 21.43223 | 30.44321 | -0.3295 | 8.07717 |
November | 330.00000 | 21.13863 | 23.96176 | -0.5335 | 11.77548 |
December | 338.00000 | 21.06278 | 13.20756 | -0.7001 | 15.58018 |
Annual Sum or Average | 4030.00000 | 22.15318 | 32.47532 | -0.5759 | 14.00432 |
Minimum of Months | 308.00000 | 21.06184 | 10.38865 | -0.9595 | 7.72072 |
Maximum of Months | 348.00000 | 23.94687 | 54.91334 | -0.3295 | 27.15481 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.06151 | 10.38922 | -0.7637 | 17.54913 |
February | 308.00000 | 21.06261 | 15.10398 | -0.7000 | 15.66940 |
March | 348.00000 | 21.08950 | 21.59034 | -0.6034 | 13.09736 |
April | 330.00000 | 21.52174 | 30.72465 | -0.3888 | 10.56005 |
May | 344.00000 | 22.48904 | 46.36553 | -1.0466 | 30.81178 |
June | 336.00000 | 23.46469 | 51.33209 | -0.5845 | 15.03344 |
July | 338.00000 | 23.93757 | 55.25916 | -0.3573 | 7.85948 |
August | 348.00000 | 23.91986 | 53.35239 | -0.3716 | 8.07992 |
September | 330.00000 | 23.12709 | 38.20602 | -0.7738 | 21.78379 |
October | 340.00000 | 21.38369 | 30.55054 | -0.3516 | 8.34334 |
November | 330.00000 | 21.12281 | 23.99347 | -0.5509 | 12.15653 |
December | 338.00000 | 21.06229 | 13.20853 | -0.7144 | 16.00897 |
Annual Sum or Average | 4030.00000 | 22.11337 | 32.66898 | -0.6001 | 14.74006 |
Minimum of Months | 308.00000 | 21.06151 | 10.38922 | -1.0466 | 7.85948 |
Maximum of Months | 348.00000 | 23.93757 | 55.25916 | -0.3516 | 30.81178 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.06161 | 10.22954 | -0.8321 | 19.87679 |
February | 308.00000 | 21.06244 | 14.96354 | -0.7728 | 17.96367 |
March | 348.00000 | 21.06903 | 21.45408 | -0.6824 | 15.23982 |
April | 330.00000 | 21.43140 | 30.90704 | -0.4789 | 12.22806 |
May | 344.00000 | 22.13663 | 47.37538 | -1.2162 | 38.44935 |
June | 336.00000 | 23.36329 | 52.23968 | -0.6469 | 17.40047 |
July | 338.00000 | 23.90939 | 56.33844 | -0.3770 | 8.24056 |
August | 348.00000 | 23.90173 | 54.23651 | -0.3834 | 8.33790 |
September | 330.00000 | 23.02089 | 38.54746 | -0.8249 | 24.04139 |
October | 340.00000 | 21.31178 | 30.55363 | -0.4046 | 9.20422 |
November | 330.00000 | 21.10037 | 23.96074 | -0.6081 | 13.60703 |
December | 338.00000 | 21.06225 | 13.07559 | -0.7813 | 18.14217 |
Annual Sum or Average | 4030.00000 | 22.04513 | 32.99107 | -0.6669 | 16.89209 |
Minimum of Months | 308.00000 | 21.06161 | 10.22954 | -1.2162 | 8.24056 |
Maximum of Months | 348.00000 | 23.90939 | 56.33844 | -0.3770 | 38.44935 |
Report: DXReportMonthly
For: PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 |
April | 0.165800E+10 | 0.415912E+09 | 54.76 | 0.113304E+10 | 0.524959E+09 | 0.00 | 0.92 | 16-APR-16:10 | 0.00 | 01-APR-00:05 | 18182.43 | 16-APR-16:10 | 12703.58 | 16-APR-16:05 | 6042.63 | 18-APR-12:40 | 4402.28 | 16-APR-16:10 | 0.00 | 01-APR-00:05 |
May | 0.290876E+10 | 0.735099E+09 | 146.81 | 0.198435E+10 | 0.924411E+09 | 0.00 | 1.00 | 31-MAY-08:62 | 0.00 | 01-MAY-00:10 | 41774.04 | 31-MAY-08:62 | 25801.94 | 31-MAY-08:62 | 15972.10 | 31-MAY-08:62 | 9056.05 | 31-MAY-08:62 | 0.00 | 01-MAY-00:10 |
June | 0.140781E+11 | 0.342553E+10 | 336.27 | 0.931302E+10 | 0.476504E+10 | 0.00 | 1.00 | 12-JUN-08:62 | 0.00 | 01-JUN-00:10 | 43425.82 | 26-JUN-08:61 | 26752.50 | 17-JUN-08:62 | 21389.32 | 14-JUN-08:62 | 9337.97 | 26-JUN-08:61 | 0.00 | 01-JUN-00:10 |
July | 0.199147E+11 | 0.471600E+10 | 447.03 | 0.122008E+11 | 0.771385E+10 | 0.00 | 1.00 | 01-JUL-08:62 | 0.00 | 01-JUL-00:05 | 43326.15 | 07-JUL-08:62 | 27380.27 | 18-JUL-08:62 | 24600.34 | 20-JUL-08:62 | 9090.12 | 26-JUL-08:62 | 0.00 | 01-JUL-00:05 |
August | 0.184984E+11 | 0.441373E+10 | 436.92 | 0.115910E+11 | 0.690739E+10 | 0.00 | 1.00 | 01-AUG-08:62 | 0.00 | 01-AUG-00:10 | 44564.21 | 04-AUG-08:61 | 25852.13 | 11-AUG-08:62 | 23709.54 | 31-AUG-08:62 | 9423.10 | 03-AUG-08:15 | 0.00 | 01-AUG-00:10 |
September | 0.867632E+10 | 0.215270E+10 | 259.79 | 0.677624E+10 | 0.190008E+10 | 0.00 | 1.00 | 06-SEP-08:62 | 0.00 | 01-SEP-00:10 | 41917.24 | 11-SEP-08:62 | 28635.71 | 18-SEP-08:62 | 19225.53 | 12-SEP-08:62 | 8941.17 | 11-SEP-08:62 | 0.00 | 01-SEP-00:10 |
October | 70410732.95 | 19125593.21 | 18.56 | 63091628.71 | 7319104.24 | 0.00 | 0.35 | 20-OCT-15:00 | 0.00 | 01-OCT-00:05 | 5362.36 | 20-OCT-15:00 | 5025.78 | 20-OCT-15:00 | 589.02 | 21-OCT-15:00 | 1441.85 | 20-OCT-15:00 | 0.00 | 01-OCT-00:05 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.658046E+11 | 0.158781E+11 | 1700.13 | 0.430616E+11 | 0.227431E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.199147E+11 | 0.471600E+10 | 447.03 | 0.122008E+11 | 0.771385E+10 | 0.00 | 1.00 | 0.00 | 44564.21 | 28635.71 | 24600.34 | 9423.10 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 |
March | 108195.99 | 32960.12 | 0.33 | 87338.89 | 20857.10 | 0.00 | 0.02 | 19-MAR-22:10 | 0.00 | 01-MAR-00:03 | 116.75 | 19-MAR-22:10 | 91.34 | 19-MAR-22:10 | 25.41 | 19-MAR-22:10 | 35.57 | 19-MAR-22:10 | 0.00 | 01-MAR-00:03 |
April | 0.110999E+10 | 0.270838E+09 | 54.49 | 0.770634E+09 | 0.339358E+09 | 0.00 | 1.00 | 15-APR-20:02 | 0.00 | 01-APR-00:05 | 22147.74 | 16-APR-19:33 | 15476.62 | 15-APR-20:02 | 8806.22 | 16-APR-21:56 | 4841.66 | 16-APR-19:33 | 0.00 | 01-APR-00:05 |
May | 0.216787E+10 | 0.525804E+09 | 155.57 | 0.148319E+10 | 0.684682E+09 | 0.00 | 1.00 | 06-MAY-18:08 | 0.00 | 01-MAY-00:10 | 22409.93 | 31-MAY-08:62 | 19008.92 | 21-MAY-17:20 | 10214.99 | 29-MAY-19:57 | 4866.40 | 31-MAY-08:62 | 0.00 | 01-MAY-00:10 |
June | 0.848767E+10 | 0.203118E+10 | 311.35 | 0.568852E+10 | 0.279914E+10 | 0.00 | 1.00 | 08-JUN-20:02 | 0.00 | 01-JUN-00:10 | 22954.55 | 26-JUN-08:61 | 16311.72 | 23-JUN-20:08 | 11354.48 | 14-JUN-21:45 | 5005.82 | 26-JUN-08:61 | 0.00 | 01-JUN-00:10 |
July | 0.123227E+11 | 0.284991E+10 | 392.72 | 0.761480E+10 | 0.470787E+10 | 0.00 | 1.00 | 01-JUL-08:62 | 0.00 | 01-JUL-00:05 | 23118.07 | 07-JUL-08:62 | 17275.36 | 23-JUL-18:54 | 12346.54 | 17-JUL-20:03 | 4904.60 | 16-JUL-19:10 | 0.00 | 01-JUL-00:05 |
August | 0.112884E+11 | 0.263621E+10 | 385.33 | 0.709910E+10 | 0.418926E+10 | 0.00 | 1.00 | 01-AUG-08:62 | 0.00 | 01-AUG-00:10 | 23437.29 | 04-AUG-08:61 | 17383.68 | 06-AUG-17:02 | 12587.36 | 28-AUG-20:05 | 5054.36 | 03-AUG-08:61 | 0.00 | 01-AUG-00:10 |
September | 0.544080E+10 | 0.130465E+10 | 233.55 | 0.423181E+10 | 0.120899E+10 | 0.00 | 1.00 | 01-SEP-20:02 | 0.00 | 01-SEP-00:10 | 22442.63 | 11-SEP-08:62 | 17987.32 | 17-SEP-21:32 | 10533.48 | 11-SEP-20:03 | 4798.52 | 11-SEP-08:62 | 0.00 | 01-SEP-00:10 |
October | 58690887.04 | 15841046.29 | 28.70 | 52509572.02 | 6181315.01 | 0.00 | 0.41 | 20-OCT-15:00 | 0.00 | 01-OCT-00:05 | 3409.08 | 20-OCT-15:00 | 3221.81 | 20-OCT-15:00 | 428.98 | 21-OCT-15:00 | 902.40 | 20-OCT-15:00 | 0.00 | 01-OCT-00:05 |
November | 1039923.68 | 313029.60 | 0.83 | 898783.97 | 141139.71 | 0.00 | 0.06 | 07-NOV-23:50 | 0.00 | 01-NOV-00:10 | 453.67 | 07-NOV-23:50 | 363.67 | 03-NOV-23:10 | 111.38 | 07-NOV-23:50 | 136.59 | 07-NOV-23:50 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.408772E+11 | 0.963478E+10 | 1562.88 | 0.269416E+11 | 0.139356E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.123227E+11 | 0.284991E+10 | 392.72 | 0.761480E+10 | 0.470787E+10 | 0.00 | 1.00 | 0.00 | 23437.29 | 19008.92 | 12587.36 | 5054.36 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 |
April | 0.688269E+09 | 0.172440E+09 | 40.76 | 0.473374E+09 | 0.214896E+09 | 0.00 | 0.91 | 18-APR-14:00 | 0.00 | 01-APR-00:05 | 9740.30 | 18-APR-14:00 | 6676.22 | 18-APR-14:00 | 3233.33 | 18-APR-12:40 | 2347.95 | 18-APR-14:00 | 0.00 | 01-APR-00:05 |
May | 0.135769E+10 | 0.344556E+09 | 117.67 | 0.946326E+09 | 0.411365E+09 | 0.00 | 1.00 | 31-MAY-07:03 | 0.00 | 01-MAY-00:10 | 22570.91 | 31-MAY-07:03 | 13269.87 | 31-MAY-07:03 | 9301.05 | 31-MAY-07:03 | 4767.66 | 31-MAY-07:03 | 0.00 | 01-MAY-00:10 |
June | 0.590943E+10 | 0.143810E+10 | 250.88 | 0.396393E+10 | 0.194550E+10 | 0.00 | 1.00 | 10-JUN-07:03 | 0.00 | 01-JUN-00:10 | 23792.46 | 26-JUN-07:01 | 14669.31 | 24-JUN-07:03 | 12352.15 | 13-JUN-07:02 | 5024.74 | 25-JUN-08:62 | 0.00 | 01-JUN-00:10 |
July | 0.819637E+10 | 0.194755E+10 | 321.79 | 0.514633E+10 | 0.305004E+10 | 0.00 | 1.00 | 01-JUL-07:02 | 0.00 | 01-JUL-00:05 | 23507.04 | 27-JUL-07:02 | 13818.34 | 19-JUL-07:02 | 13313.11 | 20-JUL-07:03 | 5011.80 | 02-JUL-08:61 | 0.00 | 01-JUL-00:05 |
August | 0.811151E+10 | 0.194484E+10 | 327.20 | 0.521110E+10 | 0.290041E+10 | 0.00 | 1.00 | 01-AUG-07:02 | 0.00 | 01-AUG-00:10 | 24410.71 | 04-AUG-07:01 | 13522.02 | 19-AUG-07:03 | 13049.33 | 04-AUG-07:06 | 5057.18 | 04-AUG-07:13 | 0.00 | 01-AUG-00:10 |
September | 0.362917E+10 | 0.905606E+09 | 197.58 | 0.290463E+10 | 0.724538E+09 | 0.00 | 1.00 | 06-SEP-07:02 | 0.00 | 01-SEP-00:10 | 22573.25 | 11-SEP-07:01 | 15137.92 | 18-SEP-07:02 | 9669.26 | 12-SEP-07:02 | 4768.00 | 11-SEP-07:01 | 0.00 | 01-SEP-00:10 |
October | 37991504.60 | 10318712.61 | 14.50 | 34318866.97 | 3672637.63 | 0.00 | 0.35 | 20-OCT-15:00 | 0.00 | 01-OCT-00:05 | 2904.04 | 20-OCT-15:00 | 2744.02 | 20-OCT-15:00 | 317.74 | 21-OCT-15:00 | 781.34 | 20-OCT-15:00 | 0.00 | 01-OCT-00:05 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.279304E+11 | 0.676342E+10 | 1270.38 | 0.186800E+11 | 0.925042E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.819637E+10 | 0.194755E+10 | 327.20 | 0.521110E+10 | 0.305004E+10 | 0.00 | 1.00 | 0.00 | 24410.71 | 15137.92 | 13313.11 | 5057.18 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 |
April | 0.664338E+09 | 0.166711E+09 | 40.14 | 0.456058E+09 | 0.208280E+09 | 0.00 | 0.90 | 18-APR-14:00 | 0.00 | 01-APR-00:05 | 9637.15 | 18-APR-14:00 | 6597.73 | 18-APR-14:00 | 3205.07 | 18-APR-12:40 | 2324.47 | 18-APR-14:00 | 0.00 | 01-APR-00:05 |
May | 0.128972E+10 | 0.327856E+09 | 113.17 | 0.899216E+09 | 0.390501E+09 | 0.00 | 1.00 | 31-MAY-07:03 | 0.00 | 01-MAY-00:10 | 22407.20 | 31-MAY-07:03 | 13163.12 | 31-MAY-07:03 | 9244.08 | 31-MAY-07:03 | 4733.13 | 31-MAY-07:03 | 0.00 | 01-MAY-00:10 |
June | 0.587786E+10 | 0.142940E+10 | 249.80 | 0.394231E+10 | 0.193555E+10 | 0.00 | 1.00 | 10-JUN-07:03 | 0.00 | 01-JUN-00:10 | 23625.31 | 26-JUN-07:01 | 14406.28 | 24-JUN-07:03 | 12261.10 | 13-JUN-07:02 | 4988.52 | 25-JUN-08:62 | 0.00 | 01-JUN-00:10 |
July | 0.819866E+10 | 0.194581E+10 | 322.11 | 0.514673E+10 | 0.305193E+10 | 0.00 | 1.00 | 01-JUL-07:02 | 0.00 | 01-JUL-00:05 | 23338.35 | 27-JUL-07:02 | 13722.44 | 19-JUL-07:02 | 13215.23 | 20-JUL-07:03 | 4975.77 | 02-JUL-08:61 | 0.00 | 01-JUL-00:05 |
August | 0.809348E+10 | 0.193926E+10 | 327.50 | 0.519876E+10 | 0.289472E+10 | 0.00 | 1.00 | 01-AUG-07:02 | 0.00 | 01-AUG-00:10 | 24237.87 | 04-AUG-07:01 | 13420.84 | 19-AUG-07:03 | 12958.11 | 04-AUG-07:06 | 5020.77 | 04-AUG-07:13 | 0.00 | 01-AUG-00:10 |
September | 0.361923E+10 | 0.902200E+09 | 195.79 | 0.289510E+10 | 0.724127E+09 | 0.00 | 1.00 | 06-SEP-07:02 | 0.00 | 01-SEP-00:10 | 22413.00 | 11-SEP-07:01 | 15037.75 | 18-SEP-07:02 | 9592.81 | 12-SEP-07:02 | 4733.99 | 11-SEP-07:01 | 0.00 | 01-SEP-00:10 |
October | 32811961.15 | 8947260.64 | 11.33 | 29813136.60 | 2998824.55 | 0.00 | 0.33 | 20-OCT-15:00 | 0.00 | 01-OCT-00:05 | 2723.27 | 20-OCT-15:00 | 2573.55 | 20-OCT-15:00 | 268.73 | 21-OCT-15:00 | 736.24 | 20-OCT-15:00 | 0.00 | 01-OCT-00:05 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.277761E+11 | 0.672018E+10 | 1259.84 | 0.185680E+11 | 0.920810E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.819866E+10 | 0.194581E+10 | 327.50 | 0.519876E+10 | 0.305193E+10 | 0.00 | 1.00 | 0.00 | 24237.87 | 15037.75 | 13215.23 | 5020.77 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 |
April | 0.622663E+09 | 0.157152E+09 | 38.33 | 0.425550E+09 | 0.197113E+09 | 0.00 | 0.88 | 18-APR-14:00 | 0.00 | 01-APR-00:05 | 9419.66 | 18-APR-14:00 | 6427.20 | 18-APR-14:00 | 3145.83 | 18-APR-12:40 | 2286.09 | 18-APR-14:00 | 0.00 | 01-APR-00:05 |
May | 0.117522E+10 | 0.300547E+09 | 102.53 | 0.819749E+09 | 0.355467E+09 | 0.00 | 0.96 | 31-MAY-07:03 | 0.00 | 01-MAY-00:10 | 22001.36 | 31-MAY-07:03 | 12875.80 | 31-MAY-07:03 | 9125.57 | 31-MAY-07:03 | 4647.91 | 31-MAY-07:03 | 0.00 | 01-MAY-00:10 |
June | 0.569176E+10 | 0.138871E+10 | 246.57 | 0.381125E+10 | 0.188051E+10 | 0.00 | 1.00 | 11-JUN-08:62 | 0.00 | 01-JUN-00:10 | 23754.30 | 26-JUN-07:01 | 13153.19 | 28-JUN-07:02 | 12361.41 | 13-JUN-07:02 | 5017.50 | 25-JUN-08:62 | 0.00 | 01-JUN-00:10 |
July | 0.797759E+10 | 0.190026E+10 | 317.94 | 0.499966E+10 | 0.297793E+10 | 0.00 | 1.00 | 01-JUL-07:02 | 0.00 | 01-JUL-00:05 | 23472.46 | 27-JUL-07:02 | 13771.35 | 19-JUL-07:02 | 13321.93 | 20-JUL-07:03 | 5004.67 | 02-JUL-08:61 | 0.00 | 01-JUL-00:05 |
August | 0.786260E+10 | 0.189065E+10 | 326.00 | 0.504429E+10 | 0.281831E+10 | 0.00 | 1.00 | 01-AUG-07:02 | 0.00 | 01-AUG-00:10 | 24372.27 | 04-AUG-07:01 | 13184.25 | 06-AUG-08:62 | 13091.46 | 04-AUG-07:06 | 5050.14 | 04-AUG-07:13 | 0.00 | 01-AUG-00:10 |
September | 0.351384E+10 | 0.879008E+09 | 190.12 | 0.280823E+10 | 0.705606E+09 | 0.00 | 1.00 | 06-SEP-07:02 | 0.00 | 01-SEP-00:10 | 22540.97 | 11-SEP-07:01 | 15098.35 | 18-SEP-07:02 | 9670.35 | 12-SEP-07:02 | 4761.23 | 11-SEP-07:01 | 0.00 | 01-SEP-00:10 |
October | 26593266.70 | 7294169.97 | 7.00 | 24371818.15 | 2221448.55 | 0.00 | 0.30 | 20-OCT-15:00 | 0.00 | 01-OCT-00:05 | 2510.19 | 20-OCT-15:00 | 2370.57 | 20-OCT-15:00 | 198.15 | 21-OCT-15:00 | 683.34 | 20-OCT-15:00 | 0.00 | 01-OCT-00:05 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.268703E+11 | 0.652362E+10 | 1228.48 | 0.179331E+11 | 0.893716E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.797759E+10 | 0.190026E+10 | 326.00 | 0.504429E+10 | 0.297793E+10 | 0.00 | 1.00 | 0.00 | 24372.27 | 15098.35 | 13321.93 | 5050.14 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 |
April | 0.104902E+10 | 0.264416E+09 | 36.17 | 0.702481E+09 | 0.346539E+09 | 0.00 | 0.89 | 18-APR-14:10 | 0.00 | 01-APR-00:05 | 17311.51 | 18-APR-14:10 | 11584.64 | 18-APR-14:10 | 6006.97 | 18-APR-12:40 | 4175.11 | 18-APR-14:10 | 0.00 | 01-APR-00:05 |
May | 0.193078E+10 | 0.495449E+09 | 86.07 | 0.133337E+10 | 0.597409E+09 | 0.00 | 1.00 | 31-MAY-08:62 | 0.00 | 01-MAY-00:10 | 40999.81 | 31-MAY-08:62 | 25369.84 | 31-MAY-08:62 | 15629.97 | 31-MAY-08:62 | 8892.27 | 31-MAY-08:62 | 0.00 | 01-MAY-00:10 |
June | 0.100403E+11 | 0.244742E+10 | 238.30 | 0.664790E+10 | 0.339243E+10 | 0.00 | 1.00 | 11-JUN-09:02 | 0.00 | 01-JUN-00:10 | 42811.87 | 26-JUN-08:61 | 27080.39 | 20-JUN-08:62 | 21515.64 | 13-JUN-08:62 | 9271.75 | 11-JUN-09:02 | 0.00 | 01-JUN-00:10 |
July | 0.142323E+11 | 0.338060E+10 | 307.64 | 0.876154E+10 | 0.547079E+10 | 0.00 | 1.00 | 01-JUL-08:62 | 0.00 | 01-JUL-00:05 | 42469.51 | 07-JUL-08:62 | 26586.69 | 18-JUL-08:62 | 23825.16 | 20-JUL-08:62 | 9198.22 | 02-JUL-09:01 | 0.00 | 01-JUL-00:05 |
August | 0.139878E+11 | 0.335913E+10 | 321.79 | 0.883990E+10 | 0.514785E+10 | 0.00 | 1.00 | 01-AUG-08:62 | 0.00 | 01-AUG-00:10 | 43602.54 | 04-AUG-08:61 | 25393.67 | 11-AUG-08:62 | 23029.04 | 31-AUG-08:62 | 9241.44 | 04-AUG-08:13 | 0.00 | 01-AUG-00:10 |
September | 0.624030E+10 | 0.155765E+10 | 180.64 | 0.493086E+10 | 0.130944E+10 | 0.00 | 1.00 | 06-SEP-08:62 | 0.00 | 01-SEP-00:10 | 41121.93 | 11-SEP-08:62 | 28250.37 | 17-SEP-09:02 | 18312.90 | 12-SEP-08:62 | 8776.93 | 11-SEP-08:62 | 0.00 | 01-SEP-00:10 |
October | 40665888.26 | 11207676.17 | 5.83 | 36898488.13 | 3767400.13 | 0.00 | 0.29 | 20-OCT-15:00 | 0.00 | 01-OCT-00:05 | 4370.68 | 20-OCT-15:00 | 4068.84 | 20-OCT-15:00 | 335.59 | 21-OCT-15:00 | 1193.06 | 20-OCT-15:00 | 0.00 | 01-OCT-00:05 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.475212E+11 | 0.115159E+11 | 1176.45 | 0.312530E+11 | 0.162682E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.142323E+11 | 0.338060E+10 | 321.79 | 0.883990E+10 | 0.547079E+10 | 0.00 | 1.00 | 0.00 | 43602.54 | 28250.37 | 23825.16 | 9271.75 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 |
April | 0.526164E+09 | 0.133509E+09 | 34.33 | 0.352029E+09 | 0.174135E+09 | 0.00 | 0.87 | 18-APR-14:10 | 0.00 | 01-APR-00:05 | 8897.44 | 18-APR-14:10 | 5956.77 | 18-APR-14:10 | 3066.05 | 18-APR-12:40 | 2164.62 | 18-APR-14:10 | 0.00 | 01-APR-00:05 |
May | 0.949479E+09 | 0.245134E+09 | 83.15 | 0.657401E+09 | 0.292078E+09 | 0.00 | 1.00 | 31-MAY-08:62 | 0.00 | 01-MAY-00:10 | 21875.54 | 31-MAY-08:62 | 13538.62 | 31-MAY-08:62 | 8336.92 | 31-MAY-08:62 | 4744.11 | 31-MAY-08:62 | 0.00 | 01-MAY-00:10 |
June | 0.511578E+10 | 0.125360E+10 | 236.35 | 0.339275E+10 | 0.172303E+10 | 0.00 | 1.00 | 11-JUN-09:02 | 0.00 | 01-JUN-00:10 | 22833.85 | 26-JUN-08:61 | 14235.22 | 30-JUN-08:61 | 11481.42 | 13-JUN-08:62 | 4945.25 | 11-JUN-09:02 | 0.00 | 01-JUN-00:10 |
July | 0.727164E+10 | 0.173754E+10 | 307.12 | 0.448837E+10 | 0.278327E+10 | 0.00 | 1.00 | 01-JUL-08:62 | 0.00 | 01-JUL-00:05 | 22662.36 | 07-JUL-08:62 | 14190.49 | 18-JUL-08:62 | 12723.14 | 20-JUL-08:62 | 4907.11 | 02-JUL-09:01 | 0.00 | 01-JUL-00:05 |
August | 0.713056E+10 | 0.172192E+10 | 321.23 | 0.451816E+10 | 0.261240E+10 | 0.00 | 1.00 | 01-AUG-08:62 | 0.00 | 01-AUG-00:10 | 23238.12 | 04-AUG-08:61 | 13555.83 | 11-AUG-08:62 | 12285.74 | 31-AUG-08:62 | 4929.43 | 04-AUG-08:13 | 0.00 | 01-AUG-00:10 |
September | 0.318758E+10 | 0.799676E+09 | 177.93 | 0.252191E+10 | 0.665672E+09 | 0.00 | 1.00 | 06-SEP-08:62 | 0.00 | 01-SEP-00:10 | 21940.96 | 11-SEP-08:62 | 15096.63 | 17-SEP-09:02 | 9778.71 | 12-SEP-08:62 | 4682.64 | 11-SEP-08:62 | 0.00 | 01-SEP-00:10 |
October | 18085711.60 | 5003856.83 | 5.50 | 16528656.35 | 1557055.25 | 0.00 | 0.28 | 20-OCT-15:00 | 0.00 | 01-OCT-00:05 | 2201.17 | 20-OCT-15:00 | 2052.09 | 20-OCT-15:00 | 149.08 | 20-OCT-15:00 | 603.33 | 20-OCT-15:00 | 0.00 | 01-OCT-00:05 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.241993E+11 | 0.589639E+10 | 1165.61 | 0.159472E+11 | 0.825213E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.727164E+10 | 0.173754E+10 | 321.23 | 0.451816E+10 | 0.278327E+10 | 0.00 | 1.00 | 0.00 | 23238.12 | 15096.63 | 12723.14 | 4945.25 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 |
April | 0.505240E+09 | 0.128506E+09 | 33.17 | 0.336883E+09 | 0.168357E+09 | 0.00 | 0.86 | 18-APR-14:10 | 0.00 | 01-APR-00:05 | 8713.47 | 18-APR-14:10 | 5815.91 | 18-APR-14:20 | 3013.02 | 18-APR-12:40 | 2125.46 | 18-APR-14:10 | 0.00 | 01-APR-00:05 |
May | 0.892693E+09 | 0.231165E+09 | 78.65 | 0.618533E+09 | 0.274160E+09 | 0.00 | 0.95 | 31-MAY-08:62 | 0.00 | 01-MAY-00:10 | 20999.88 | 31-MAY-08:62 | 12949.12 | 31-MAY-08:62 | 8050.76 | 31-MAY-08:62 | 4554.85 | 31-MAY-08:62 | 0.00 | 01-MAY-00:10 |
June | 0.501839E+10 | 0.123059E+10 | 234.62 | 0.332257E+10 | 0.169582E+10 | 0.00 | 1.00 | 11-JUN-09:02 | 0.00 | 01-JUN-00:10 | 22665.63 | 26-JUN-08:61 | 14075.82 | 30-JUN-08:61 | 11170.05 | 12-JUN-08:62 | 4909.64 | 11-JUN-09:02 | 0.00 | 01-JUN-00:10 |
July | 0.715354E+10 | 0.171040E+10 | 305.81 | 0.440751E+10 | 0.274602E+10 | 0.00 | 1.00 | 01-JUL-08:62 | 0.00 | 01-JUL-00:05 | 22499.32 | 07-JUL-08:62 | 14064.43 | 18-JUL-08:62 | 12647.31 | 20-JUL-08:62 | 4871.99 | 02-JUL-09:01 | 0.00 | 01-JUL-00:05 |
August | 0.701887E+10 | 0.169586E+10 | 320.12 | 0.444077E+10 | 0.257810E+10 | 0.00 | 1.00 | 01-AUG-08:62 | 0.00 | 01-AUG-00:10 | 23074.31 | 04-AUG-08:61 | 13438.85 | 11-AUG-08:62 | 12211.44 | 31-AUG-08:62 | 4894.42 | 04-AUG-08:13 | 0.00 | 01-AUG-00:10 |
September | 0.313646E+10 | 0.787228E+09 | 176.81 | 0.247887E+10 | 0.657592E+09 | 0.00 | 1.00 | 06-SEP-08:62 | 0.00 | 01-SEP-00:10 | 21782.33 | 11-SEP-08:62 | 14965.55 | 17-SEP-09:02 | 9720.84 | 12-SEP-08:62 | 4648.99 | 11-SEP-08:62 | 0.00 | 01-SEP-00:10 |
October | 16367072.05 | 4537817.49 | 5.33 | 14996571.36 | 1370500.69 | 0.00 | 0.27 | 20-OCT-15:00 | 0.00 | 01-OCT-00:05 | 2104.77 | 20-OCT-15:00 | 1960.63 | 20-OCT-15:00 | 144.14 | 20-OCT-15:00 | 578.40 | 20-OCT-15:00 | 0.00 | 01-OCT-00:05 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.237415E+11 | 0.578828E+10 | 1154.52 | 0.156201E+11 | 0.812142E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.715354E+10 | 0.171040E+10 | 320.12 | 0.444077E+10 | 0.274602E+10 | 0.00 | 1.00 | 0.00 | 23074.31 | 14965.55 | 12647.31 | 4909.64 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 |
April | 0.455772E+09 | 0.116781E+09 | 30.75 | 0.301288E+09 | 0.154484E+09 | 0.00 | 0.83 | 18-APR-14:10 | 0.00 | 01-APR-00:05 | 8242.47 | 18-APR-14:10 | 5460.21 | 18-APR-14:20 | 2869.52 | 18-APR-12:40 | 2026.76 | 18-APR-14:10 | 0.00 | 01-APR-00:05 |
May | 0.773385E+09 | 0.201647E+09 | 70.43 | 0.536585E+09 | 0.236800E+09 | 0.00 | 0.87 | 31-MAY-15:00 | 0.00 | 01-MAY-00:10 | 10970.76 | 31-MAY-08:62 | 6594.47 | 31-MAY-08:62 | 4376.29 | 31-MAY-08:62 | 2385.25 | 31-MAY-08:62 | 0.00 | 01-MAY-00:10 |
June | 0.478290E+10 | 0.117489E+10 | 231.90 | 0.315483E+10 | 0.162807E+10 | 0.00 | 1.00 | 11-JUN-09:02 | 0.00 | 01-JUN-00:10 | 22337.48 | 26-JUN-08:61 | 13748.71 | 30-JUN-08:61 | 11067.22 | 12-JUN-08:62 | 4841.16 | 11-JUN-09:02 | 0.00 | 01-JUN-00:10 |
July | 0.687860E+10 | 0.164727E+10 | 300.01 | 0.422270E+10 | 0.265589E+10 | 0.00 | 1.00 | 01-JUL-08:62 | 0.00 | 01-JUL-00:05 | 22186.24 | 07-JUL-08:62 | 13714.37 | 02-JUL-09:03 | 12516.36 | 20-JUL-08:62 | 4804.89 | 02-JUL-09:01 | 0.00 | 01-JUL-00:05 |
August | 0.676909E+10 | 0.163766E+10 | 317.79 | 0.427043E+10 | 0.249867E+10 | 0.00 | 1.00 | 01-AUG-08:62 | 0.00 | 01-AUG-00:10 | 22756.38 | 04-AUG-08:61 | 12395.31 | 12-AUG-08:62 | 12083.01 | 31-AUG-08:62 | 4827.56 | 04-AUG-08:13 | 0.00 | 01-AUG-00:10 |
September | 0.302727E+10 | 0.760495E+09 | 172.53 | 0.238697E+10 | 0.640303E+09 | 0.00 | 1.00 | 07-SEP-08:62 | 0.00 | 01-SEP-00:10 | 21477.40 | 11-SEP-08:62 | 14702.93 | 17-SEP-09:02 | 9616.18 | 12-SEP-08:62 | 4584.51 | 11-SEP-08:62 | 0.00 | 01-SEP-00:10 |
October | 12670743.19 | 3532053.77 | 4.50 | 11658001.02 | 1012742.17 | 0.00 | 0.24 | 20-OCT-15:00 | 0.00 | 01-OCT-00:05 | 1872.34 | 20-OCT-15:00 | 1740.41 | 20-OCT-15:00 | 131.93 | 20-OCT-15:00 | 517.94 | 20-OCT-15:00 | 0.00 | 01-OCT-00:05 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.226997E+11 | 0.554227E+10 | 1127.92 | 0.148845E+11 | 0.781523E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.687860E+10 | 0.164727E+10 | 317.79 | 0.427043E+10 | 0.265589E+10 | 0.00 | 1.00 | 0.00 | 22756.38 | 14702.93 | 12516.36 | 4841.16 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 |
April | 0.391035E+09 | 0.103526E+09 | 24.08 | 0.256470E+09 | 0.134566E+09 | 0.00 | 0.71 | 18-APR-14:10 | 0.00 | 01-APR-00:05 | 7636.06 | 18-APR-14:10 | 5011.76 | 18-APR-14:10 | 2710.69 | 18-APR-12:30 | 1949.99 | 18-APR-14:10 | 0.00 | 01-APR-00:05 |
May | 0.618910E+09 | 0.165429E+09 | 55.75 | 0.433076E+09 | 0.185834E+09 | 0.00 | 0.77 | 31-MAY-13:00 | 0.00 | 01-MAY-00:10 | 8227.87 | 31-MAY-13:00 | 6265.29 | 31-MAY-15:00 | 2210.12 | 30-MAY-13:00 | 2155.92 | 31-MAY-13:00 | 0.00 | 01-MAY-00:10 |
June | 0.441338E+10 | 0.110762E+10 | 221.07 | 0.291283E+10 | 0.150055E+10 | 0.00 | 1.00 | 11-JUN-09:02 | 0.00 | 01-JUN-00:10 | 25404.08 | 26-JUN-08:61 | 15304.88 | 11-JUN-09:02 | 12383.68 | 26-JUN-08:03 | 5462.67 | 11-JUN-09:02 | 0.00 | 01-JUN-00:10 |
July | 0.648684E+10 | 0.158780E+10 | 291.27 | 0.400087E+10 | 0.248597E+10 | 0.00 | 1.00 | 01-JUL-08:62 | 0.00 | 01-JUL-00:05 | 25106.63 | 07-JUL-08:62 | 15202.29 | 02-JUL-09:01 | 13561.07 | 07-JUL-08:62 | 5408.15 | 02-JUL-09:01 | 0.00 | 01-JUL-00:05 |
August | 0.642914E+10 | 0.158276E+10 | 301.90 | 0.408621E+10 | 0.234293E+10 | 0.00 | 1.00 | 01-AUG-08:62 | 0.00 | 01-AUG-00:10 | 26108.23 | 04-AUG-08:61 | 13045.05 | 05-AUG-08:62 | 14700.94 | 04-AUG-08:03 | 5451.45 | 04-AUG-08:13 | 0.00 | 01-AUG-00:10 |
September | 0.296126E+10 | 0.756604E+09 | 159.91 | 0.234365E+10 | 0.617608E+09 | 0.00 | 1.00 | 08-SEP-08:62 | 0.00 | 01-SEP-00:10 | 24310.19 | 11-SEP-08:62 | 15549.13 | 08-SEP-08:62 | 10229.87 | 11-SEP-08:62 | 5182.48 | 11-SEP-08:62 | 0.00 | 01-SEP-00:10 |
October | 8726361.85 | 2461891.59 | 3.50 | 8100666.21 | 625695.64 | 0.00 | 0.19 | 20-OCT-15:00 | 0.00 | 01-OCT-00:05 | 1606.52 | 20-OCT-15:00 | 1501.58 | 20-OCT-15:00 | 104.94 | 20-OCT-15:00 | 451.00 | 20-OCT-15:00 | 0.00 | 01-OCT-00:05 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.213093E+11 | 0.530620E+10 | 1057.47 | 0.140412E+11 | 0.726809E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.648684E+10 | 0.158780E+10 | 301.90 | 0.408621E+10 | 0.248597E+10 | 0.00 | 1.00 | 0.00 | 26108.23 | 15549.13 | 14700.94 | 5462.67 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 119.63 | 81.86 | 37.77 | 101.56 | 127.61 | 0.00 | 0.00 | 744.00 |
February | 128.24 | 86.65 | 41.59 | 109.16 | 103.09 | 0.00 | 0.00 | 672.00 |
March | 111.62 | 58.80 | 52.82 | 93.45 | 73.23 | 0.00 | 0.00 | 744.00 |
April | 100.51 | 46.99 | 53.52 | 81.37 | 53.27 | 0.00 | 0.00 | 720.00 |
May | 83.26 | 22.56 | 60.70 | 65.52 | 33.09 | 0.00 | 0.00 | 744.00 |
June | 80.83 | 16.45 | 64.39 | 71.65 | 22.88 | 0.00 | 0.00 | 720.00 |
July | 85.57 | 21.55 | 64.02 | 78.43 | 20.01 | 0.00 | 0.00 | 744.00 |
August | 96.41 | 34.57 | 61.84 | 95.21 | 24.28 | 0.00 | 0.00 | 744.00 |
September | 116.87 | 61.59 | 55.28 | 118.85 | 40.17 | 0.00 | 0.00 | 720.00 |
October | 122.06 | 76.59 | 45.47 | 122.03 | 57.90 | 0.00 | 0.00 | 744.00 |
November | 92.05 | 57.62 | 34.43 | 81.58 | 84.17 | 0.00 | 0.00 | 720.00 |
December | 98.13 | 74.32 | 23.81 | 91.70 | 118.34 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 102.78 | 53.11 | 49.68 | 92.45 | 62.98 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 80.83 | 16.45 | 23.81 | 65.52 | 20.01 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 128.24 | 86.65 | 64.39 | 122.03 | 127.61 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 119.63 | 81.86 | 37.77 | 101.56 | 127.61 | 0.00 | 0.00 | 744.00 |
February | 128.24 | 86.65 | 41.59 | 109.16 | 103.09 | 0.00 | 0.00 | 672.00 |
March | 111.62 | 58.80 | 52.82 | 93.45 | 73.23 | 0.00 | 0.00 | 744.00 |
April | 100.51 | 46.99 | 53.52 | 81.37 | 53.27 | 0.00 | 0.00 | 720.00 |
May | 83.26 | 22.56 | 60.70 | 65.52 | 33.09 | 0.00 | 0.00 | 744.00 |
June | 80.83 | 16.45 | 64.39 | 71.65 | 22.88 | 0.00 | 0.00 | 720.00 |
July | 85.57 | 21.55 | 64.02 | 78.43 | 20.01 | 0.00 | 0.00 | 744.00 |
August | 96.41 | 34.57 | 61.84 | 95.21 | 24.28 | 0.00 | 0.00 | 744.00 |
September | 116.87 | 61.59 | 55.28 | 118.85 | 40.17 | 0.00 | 0.00 | 720.00 |
October | 122.06 | 76.59 | 45.47 | 122.03 | 57.90 | 0.00 | 0.00 | 744.00 |
November | 92.05 | 57.62 | 34.43 | 81.58 | 84.17 | 0.00 | 0.00 | 720.00 |
December | 98.13 | 74.32 | 23.81 | 91.70 | 118.34 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 102.78 | 53.11 | 49.68 | 92.45 | 62.98 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 80.83 | 16.45 | 23.81 | 65.52 | 20.01 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 128.24 | 86.65 | 64.39 | 122.03 | 127.61 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_3
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 119.63 | 81.86 | 37.77 | 101.56 | 127.61 | 0.00 | 0.00 | 744.00 |
February | 128.24 | 86.65 | 41.59 | 109.16 | 103.09 | 0.00 | 0.00 | 672.00 |
March | 111.62 | 58.80 | 52.82 | 93.45 | 73.23 | 0.00 | 0.00 | 744.00 |
April | 100.51 | 46.99 | 53.52 | 81.37 | 53.27 | 0.00 | 0.00 | 720.00 |
May | 83.26 | 22.56 | 60.70 | 65.52 | 33.09 | 0.00 | 0.00 | 744.00 |
June | 80.83 | 16.45 | 64.39 | 71.65 | 22.88 | 0.00 | 0.00 | 720.00 |
July | 85.57 | 21.55 | 64.02 | 78.43 | 20.01 | 0.00 | 0.00 | 744.00 |
August | 96.41 | 34.57 | 61.84 | 95.21 | 24.28 | 0.00 | 0.00 | 744.00 |
September | 116.87 | 61.59 | 55.28 | 118.85 | 40.17 | 0.00 | 0.00 | 720.00 |
October | 122.06 | 76.59 | 45.47 | 122.03 | 57.90 | 0.00 | 0.00 | 744.00 |
November | 92.05 | 57.62 | 34.43 | 81.58 | 84.17 | 0.00 | 0.00 | 720.00 |
December | 98.13 | 74.32 | 23.81 | 91.70 | 118.34 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 102.78 | 53.11 | 49.68 | 92.45 | 62.98 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 80.83 | 16.45 | 23.81 | 65.52 | 20.01 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 128.24 | 86.65 | 64.39 | 122.03 | 127.61 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_4
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 119.63 | 81.86 | 37.77 | 101.56 | 127.61 | 0.00 | 0.00 | 744.00 |
February | 128.24 | 86.65 | 41.59 | 109.16 | 103.09 | 0.00 | 0.00 | 672.00 |
March | 111.62 | 58.80 | 52.82 | 93.45 | 73.23 | 0.00 | 0.00 | 744.00 |
April | 100.51 | 46.99 | 53.52 | 81.37 | 53.27 | 0.00 | 0.00 | 720.00 |
May | 83.26 | 22.56 | 60.70 | 65.52 | 33.09 | 0.00 | 0.00 | 744.00 |
June | 80.83 | 16.45 | 64.39 | 71.65 | 22.88 | 0.00 | 0.00 | 720.00 |
July | 85.57 | 21.55 | 64.02 | 78.43 | 20.01 | 0.00 | 0.00 | 744.00 |
August | 96.41 | 34.57 | 61.84 | 95.21 | 24.28 | 0.00 | 0.00 | 744.00 |
September | 116.87 | 61.59 | 55.28 | 118.85 | 40.17 | 0.00 | 0.00 | 720.00 |
October | 122.06 | 76.59 | 45.47 | 122.03 | 57.90 | 0.00 | 0.00 | 744.00 |
November | 92.05 | 57.62 | 34.43 | 81.58 | 84.17 | 0.00 | 0.00 | 720.00 |
December | 98.13 | 74.32 | 23.81 | 91.70 | 118.34 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 102.78 | 53.11 | 49.68 | 92.45 | 62.98 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 80.83 | 16.45 | 23.81 | 65.52 | 20.01 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 128.24 | 86.65 | 64.39 | 122.03 | 127.61 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_DOOR_1
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 144.03 | 98.55 | 45.48 | 122.59 | 152.15 | 0.00 | 0.00 | 744.00 |
February | 154.40 | 104.32 | 50.07 | 131.72 | 122.94 | 0.00 | 0.00 | 672.00 |
March | 134.38 | 70.79 | 63.59 | 112.73 | 87.35 | 0.00 | 0.00 | 744.00 |
April | 121.01 | 56.57 | 64.44 | 98.07 | 63.59 | 0.00 | 0.00 | 720.00 |
May | 100.24 | 27.17 | 73.08 | 78.95 | 39.59 | 0.00 | 0.00 | 744.00 |
June | 97.32 | 19.80 | 77.52 | 86.19 | 27.41 | 0.00 | 0.00 | 720.00 |
July | 103.02 | 25.94 | 77.08 | 94.33 | 24.01 | 0.00 | 0.00 | 744.00 |
August | 116.07 | 41.62 | 74.46 | 114.54 | 29.10 | 0.00 | 0.00 | 744.00 |
September | 140.70 | 74.15 | 66.55 | 143.03 | 48.09 | 0.00 | 0.00 | 720.00 |
October | 146.95 | 92.21 | 54.74 | 146.99 | 69.22 | 0.00 | 0.00 | 744.00 |
November | 110.83 | 69.38 | 41.45 | 98.38 | 100.43 | 0.00 | 0.00 | 720.00 |
December | 118.14 | 89.48 | 28.66 | 110.56 | 141.16 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 123.75 | 63.94 | 59.81 | 111.40 | 75.20 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 97.32 | 19.80 | 28.66 | 78.95 | 24.01 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 154.40 | 104.32 | 77.52 | 146.99 | 152.15 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_DOOR_2
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 144.03 | 98.55 | 45.48 | 122.59 | 152.15 | 0.00 | 0.00 | 744.00 |
February | 154.40 | 104.32 | 50.07 | 131.72 | 122.94 | 0.00 | 0.00 | 672.00 |
March | 134.38 | 70.79 | 63.59 | 112.73 | 87.35 | 0.00 | 0.00 | 744.00 |
April | 121.01 | 56.57 | 64.44 | 98.07 | 63.59 | 0.00 | 0.00 | 720.00 |
May | 100.24 | 27.17 | 73.08 | 78.95 | 39.59 | 0.00 | 0.00 | 744.00 |
June | 97.32 | 19.80 | 77.52 | 86.19 | 27.41 | 0.00 | 0.00 | 720.00 |
July | 103.02 | 25.94 | 77.08 | 94.33 | 24.01 | 0.00 | 0.00 | 744.00 |
August | 116.07 | 41.62 | 74.46 | 114.54 | 29.10 | 0.00 | 0.00 | 744.00 |
September | 140.70 | 74.15 | 66.55 | 143.03 | 48.09 | 0.00 | 0.00 | 720.00 |
October | 146.95 | 92.21 | 54.74 | 146.99 | 69.22 | 0.00 | 0.00 | 744.00 |
November | 110.83 | 69.38 | 41.45 | 98.38 | 100.43 | 0.00 | 0.00 | 720.00 |
December | 118.14 | 89.48 | 28.66 | 110.56 | 141.16 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 123.75 | 63.94 | 59.81 | 111.40 | 75.20 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 97.32 | 19.80 | 28.66 | 78.95 | 24.01 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 154.40 | 104.32 | 77.52 | 146.99 | 152.15 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 119.63 | 81.86 | 37.77 | 100.55 | 131.45 | 0.00 | 0.00 | 744.00 |
February | 128.24 | 86.65 | 41.59 | 108.03 | 107.03 | 0.00 | 0.00 | 672.00 |
March | 111.62 | 58.80 | 52.82 | 92.20 | 77.25 | 0.00 | 0.00 | 744.00 |
April | 100.51 | 46.99 | 53.52 | 80.28 | 57.11 | 0.00 | 0.00 | 720.00 |
May | 83.26 | 22.56 | 60.70 | 64.06 | 35.37 | 0.00 | 0.00 | 744.00 |
June | 80.83 | 16.45 | 64.39 | 70.99 | 23.93 | 0.00 | 0.00 | 720.00 |
July | 85.57 | 21.55 | 64.02 | 78.21 | 20.25 | 0.00 | 0.00 | 744.00 |
August | 96.41 | 34.57 | 61.84 | 95.03 | 24.56 | 0.00 | 0.00 | 744.00 |
September | 116.87 | 61.59 | 55.28 | 118.35 | 41.41 | 0.00 | 0.00 | 720.00 |
October | 122.06 | 76.59 | 45.47 | 120.89 | 61.25 | 0.00 | 0.00 | 744.00 |
November | 92.05 | 57.62 | 34.43 | 80.56 | 87.99 | 0.00 | 0.00 | 720.00 |
December | 98.13 | 74.32 | 23.81 | 90.94 | 122.35 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 102.78 | 53.11 | 49.68 | 91.58 | 65.64 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 80.83 | 16.45 | 23.81 | 64.06 | 20.25 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 128.24 | 86.65 | 64.39 | 120.89 | 131.45 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 119.63 | 81.86 | 37.77 | 100.55 | 131.45 | 0.00 | 0.00 | 744.00 |
February | 128.24 | 86.65 | 41.59 | 108.03 | 107.03 | 0.00 | 0.00 | 672.00 |
March | 111.62 | 58.80 | 52.82 | 92.20 | 77.25 | 0.00 | 0.00 | 744.00 |
April | 100.51 | 46.99 | 53.52 | 80.28 | 57.11 | 0.00 | 0.00 | 720.00 |
May | 83.26 | 22.56 | 60.70 | 64.06 | 35.37 | 0.00 | 0.00 | 744.00 |
June | 80.83 | 16.45 | 64.39 | 70.99 | 23.93 | 0.00 | 0.00 | 720.00 |
July | 85.57 | 21.55 | 64.02 | 78.21 | 20.25 | 0.00 | 0.00 | 744.00 |
August | 96.41 | 34.57 | 61.84 | 95.03 | 24.56 | 0.00 | 0.00 | 744.00 |
September | 116.87 | 61.59 | 55.28 | 118.35 | 41.41 | 0.00 | 0.00 | 720.00 |
October | 122.06 | 76.59 | 45.47 | 120.89 | 61.25 | 0.00 | 0.00 | 744.00 |
November | 92.05 | 57.62 | 34.43 | 80.56 | 87.99 | 0.00 | 0.00 | 720.00 |
December | 98.13 | 74.32 | 23.81 | 90.94 | 122.35 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 102.78 | 53.11 | 49.68 | 91.58 | 65.64 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 80.83 | 16.45 | 23.81 | 64.06 | 20.25 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 128.24 | 86.65 | 64.39 | 120.89 | 131.45 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_DOOR
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 144.03 | 98.55 | 45.48 | 121.37 | 156.73 | 0.00 | 0.00 | 744.00 |
February | 154.40 | 104.32 | 50.07 | 130.36 | 127.63 | 0.00 | 0.00 | 672.00 |
March | 134.38 | 70.79 | 63.59 | 111.23 | 92.13 | 0.00 | 0.00 | 744.00 |
April | 121.01 | 56.57 | 64.44 | 96.75 | 68.16 | 0.00 | 0.00 | 720.00 |
May | 100.24 | 27.17 | 73.08 | 77.19 | 42.30 | 0.00 | 0.00 | 744.00 |
June | 97.32 | 19.80 | 77.52 | 85.40 | 28.65 | 0.00 | 0.00 | 720.00 |
July | 103.02 | 25.94 | 77.08 | 94.07 | 24.29 | 0.00 | 0.00 | 744.00 |
August | 116.07 | 41.62 | 74.46 | 114.33 | 29.42 | 0.00 | 0.00 | 744.00 |
September | 140.70 | 74.15 | 66.55 | 142.43 | 49.57 | 0.00 | 0.00 | 720.00 |
October | 146.95 | 92.21 | 54.74 | 145.62 | 73.18 | 0.00 | 0.00 | 744.00 |
November | 110.83 | 69.38 | 41.45 | 97.16 | 104.95 | 0.00 | 0.00 | 720.00 |
December | 118.14 | 89.48 | 28.66 | 109.64 | 145.94 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 123.75 | 63.94 | 59.81 | 110.35 | 78.35 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 97.32 | 19.80 | 28.66 | 77.19 | 24.29 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 154.40 | 104.32 | 77.52 | 145.62 | 156.73 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 119.63 | 81.86 | 37.77 | 100.62 | 128.68 | 0.00 | 0.00 | 744.00 |
February | 128.24 | 86.65 | 41.59 | 108.13 | 104.48 | 0.00 | 0.00 | 672.00 |
March | 111.62 | 58.80 | 52.82 | 92.38 | 75.27 | 0.00 | 0.00 | 744.00 |
April | 100.51 | 46.99 | 53.52 | 80.45 | 55.60 | 0.00 | 0.00 | 720.00 |
May | 83.26 | 22.56 | 60.70 | 64.31 | 35.16 | 0.00 | 0.00 | 744.00 |
June | 80.83 | 16.45 | 64.39 | 70.83 | 24.71 | 0.00 | 0.00 | 720.00 |
July | 85.57 | 21.55 | 64.02 | 77.85 | 21.69 | 0.00 | 0.00 | 744.00 |
August | 96.41 | 34.57 | 61.84 | 94.92 | 25.93 | 0.00 | 0.00 | 744.00 |
September | 116.87 | 61.59 | 55.28 | 118.38 | 42.03 | 0.00 | 0.00 | 720.00 |
October | 122.06 | 76.59 | 45.47 | 121.43 | 59.32 | 0.00 | 0.00 | 744.00 |
November | 92.05 | 57.62 | 34.43 | 80.88 | 85.66 | 0.00 | 0.00 | 720.00 |
December | 98.13 | 74.32 | 23.81 | 91.06 | 119.86 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 102.78 | 53.11 | 49.68 | 91.68 | 64.68 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 80.83 | 16.45 | 23.81 | 64.31 | 21.69 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 128.24 | 86.65 | 64.39 | 121.43 | 128.68 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 119.63 | 81.86 | 37.77 | 100.62 | 128.68 | 0.00 | 0.00 | 744.00 |
February | 128.24 | 86.65 | 41.59 | 108.13 | 104.48 | 0.00 | 0.00 | 672.00 |
March | 111.62 | 58.80 | 52.82 | 92.38 | 75.27 | 0.00 | 0.00 | 744.00 |
April | 100.51 | 46.99 | 53.52 | 80.45 | 55.60 | 0.00 | 0.00 | 720.00 |
May | 83.26 | 22.56 | 60.70 | 64.31 | 35.16 | 0.00 | 0.00 | 744.00 |
June | 80.83 | 16.45 | 64.39 | 70.83 | 24.71 | 0.00 | 0.00 | 720.00 |
July | 85.57 | 21.55 | 64.02 | 77.85 | 21.69 | 0.00 | 0.00 | 744.00 |
August | 96.41 | 34.57 | 61.84 | 94.92 | 25.93 | 0.00 | 0.00 | 744.00 |
September | 116.87 | 61.59 | 55.28 | 118.38 | 42.03 | 0.00 | 0.00 | 720.00 |
October | 122.06 | 76.59 | 45.47 | 121.43 | 59.32 | 0.00 | 0.00 | 744.00 |
November | 92.05 | 57.62 | 34.43 | 80.88 | 85.66 | 0.00 | 0.00 | 720.00 |
December | 98.13 | 74.32 | 23.81 | 91.06 | 119.86 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 102.78 | 53.11 | 49.68 | 91.68 | 64.68 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 80.83 | 16.45 | 23.81 | 64.31 | 21.69 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 128.24 | 86.65 | 64.39 | 121.43 | 128.68 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_DOOR
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 143.24 | 98.01 | 45.23 | 120.80 | 152.59 | 0.00 | 0.00 | 744.00 |
February | 153.55 | 103.75 | 49.80 | 129.79 | 123.91 | 0.00 | 0.00 | 672.00 |
March | 133.65 | 70.40 | 63.25 | 110.84 | 89.27 | 0.00 | 0.00 | 744.00 |
April | 120.35 | 56.26 | 64.09 | 96.43 | 65.99 | 0.00 | 0.00 | 720.00 |
May | 99.70 | 27.02 | 72.68 | 77.07 | 41.80 | 0.00 | 0.00 | 744.00 |
June | 96.79 | 19.69 | 77.10 | 84.75 | 29.41 | 0.00 | 0.00 | 720.00 |
July | 102.46 | 25.80 | 76.65 | 93.13 | 25.84 | 0.00 | 0.00 | 744.00 |
August | 115.44 | 41.39 | 74.05 | 113.56 | 30.86 | 0.00 | 0.00 | 744.00 |
September | 139.94 | 73.75 | 66.19 | 141.69 | 50.01 | 0.00 | 0.00 | 720.00 |
October | 146.15 | 91.71 | 54.44 | 145.48 | 70.49 | 0.00 | 0.00 | 744.00 |
November | 110.22 | 69.00 | 41.22 | 97.02 | 101.62 | 0.00 | 0.00 | 720.00 |
December | 117.49 | 88.99 | 28.51 | 109.20 | 142.19 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 123.07 | 63.59 | 59.48 | 109.87 | 76.78 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 96.79 | 19.69 | 28.51 | 77.07 | 25.84 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 153.55 | 103.75 | 77.10 | 145.48 | 152.59 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 119.63 | 81.86 | 37.77 | 100.74 | 127.66 | 0.00 | 0.00 | 744.00 |
February | 128.24 | 86.65 | 41.59 | 108.28 | 103.50 | 0.00 | 0.00 | 672.00 |
March | 111.62 | 58.80 | 52.82 | 92.55 | 74.39 | 0.00 | 0.00 | 744.00 |
April | 100.51 | 46.99 | 53.52 | 80.63 | 54.81 | 0.00 | 0.00 | 720.00 |
May | 83.26 | 22.56 | 60.70 | 64.62 | 34.58 | 0.00 | 0.00 | 744.00 |
June | 80.83 | 16.45 | 64.39 | 70.94 | 24.52 | 0.00 | 0.00 | 720.00 |
July | 85.57 | 21.55 | 64.02 | 77.84 | 21.71 | 0.00 | 0.00 | 744.00 |
August | 96.41 | 34.57 | 61.84 | 94.92 | 25.92 | 0.00 | 0.00 | 744.00 |
September | 116.87 | 61.59 | 55.28 | 118.47 | 41.78 | 0.00 | 0.00 | 720.00 |
October | 122.06 | 76.59 | 45.47 | 121.73 | 58.38 | 0.00 | 0.00 | 744.00 |
November | 92.05 | 57.62 | 34.43 | 81.10 | 84.61 | 0.00 | 0.00 | 720.00 |
December | 98.13 | 74.32 | 23.81 | 91.17 | 118.87 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 102.78 | 53.11 | 49.68 | 91.83 | 64.05 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 80.83 | 16.45 | 23.81 | 64.62 | 21.71 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 128.24 | 86.65 | 64.39 | 121.73 | 127.66 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 119.63 | 81.86 | 37.77 | 100.74 | 127.66 | 0.00 | 0.00 | 744.00 |
February | 128.24 | 86.65 | 41.59 | 108.28 | 103.50 | 0.00 | 0.00 | 672.00 |
March | 111.62 | 58.80 | 52.82 | 92.55 | 74.39 | 0.00 | 0.00 | 744.00 |
April | 100.51 | 46.99 | 53.52 | 80.63 | 54.81 | 0.00 | 0.00 | 720.00 |
May | 83.26 | 22.56 | 60.70 | 64.62 | 34.58 | 0.00 | 0.00 | 744.00 |
June | 80.83 | 16.45 | 64.39 | 70.94 | 24.52 | 0.00 | 0.00 | 720.00 |
July | 85.57 | 21.55 | 64.02 | 77.84 | 21.71 | 0.00 | 0.00 | 744.00 |
August | 96.41 | 34.57 | 61.84 | 94.92 | 25.92 | 0.00 | 0.00 | 744.00 |
September | 116.87 | 61.59 | 55.28 | 118.47 | 41.78 | 0.00 | 0.00 | 720.00 |
October | 122.06 | 76.59 | 45.47 | 121.73 | 58.38 | 0.00 | 0.00 | 744.00 |
November | 92.05 | 57.62 | 34.43 | 81.10 | 84.61 | 0.00 | 0.00 | 720.00 |
December | 98.13 | 74.32 | 23.81 | 91.17 | 118.87 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 102.78 | 53.11 | 49.68 | 91.83 | 64.05 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 80.83 | 16.45 | 23.81 | 64.62 | 21.71 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 128.24 | 86.65 | 64.39 | 121.73 | 127.66 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_DOOR
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 143.24 | 98.01 | 45.23 | 120.95 | 151.37 | 0.00 | 0.00 | 744.00 |
February | 153.55 | 103.75 | 49.80 | 129.96 | 122.74 | 0.00 | 0.00 | 672.00 |
March | 133.65 | 70.40 | 63.25 | 111.05 | 88.23 | 0.00 | 0.00 | 744.00 |
April | 120.35 | 56.26 | 64.09 | 96.65 | 65.06 | 0.00 | 0.00 | 720.00 |
May | 99.70 | 27.02 | 72.68 | 77.44 | 41.11 | 0.00 | 0.00 | 744.00 |
June | 96.79 | 19.69 | 77.10 | 84.87 | 29.18 | 0.00 | 0.00 | 720.00 |
July | 102.46 | 25.80 | 76.65 | 93.12 | 25.87 | 0.00 | 0.00 | 744.00 |
August | 115.44 | 41.39 | 74.05 | 113.57 | 30.85 | 0.00 | 0.00 | 744.00 |
September | 139.94 | 73.75 | 66.19 | 141.80 | 49.70 | 0.00 | 0.00 | 720.00 |
October | 146.15 | 91.71 | 54.44 | 145.83 | 69.38 | 0.00 | 0.00 | 744.00 |
November | 110.22 | 69.00 | 41.22 | 97.28 | 100.37 | 0.00 | 0.00 | 720.00 |
December | 117.49 | 88.99 | 28.51 | 109.34 | 141.00 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 123.07 | 63.59 | 59.48 | 110.05 | 76.02 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 96.79 | 19.69 | 28.51 | 77.44 | 25.87 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 153.55 | 103.75 | 77.10 | 145.83 | 151.37 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 119.63 | 81.86 | 37.77 | 100.87 | 126.95 | 0.00 | 0.00 | 744.00 |
February | 128.24 | 86.65 | 41.59 | 108.44 | 102.80 | 0.00 | 0.00 | 672.00 |
March | 111.62 | 58.80 | 52.82 | 92.75 | 73.70 | 0.00 | 0.00 | 744.00 |
April | 100.51 | 46.99 | 53.52 | 80.85 | 54.16 | 0.00 | 0.00 | 720.00 |
May | 83.26 | 22.56 | 60.70 | 65.08 | 33.90 | 0.00 | 0.00 | 744.00 |
June | 80.83 | 16.45 | 64.39 | 71.14 | 24.16 | 0.00 | 0.00 | 720.00 |
July | 85.57 | 21.55 | 64.02 | 77.95 | 21.49 | 0.00 | 0.00 | 744.00 |
August | 96.41 | 34.57 | 61.84 | 95.02 | 25.69 | 0.00 | 0.00 | 744.00 |
September | 116.87 | 61.59 | 55.28 | 118.63 | 41.38 | 0.00 | 0.00 | 720.00 |
October | 122.06 | 76.59 | 45.47 | 121.98 | 57.73 | 0.00 | 0.00 | 744.00 |
November | 92.05 | 57.62 | 34.43 | 81.31 | 83.83 | 0.00 | 0.00 | 720.00 |
December | 98.13 | 74.32 | 23.81 | 91.30 | 118.14 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 102.78 | 53.11 | 49.68 | 92.02 | 63.48 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 80.83 | 16.45 | 23.81 | 65.08 | 21.49 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 128.24 | 86.65 | 64.39 | 121.98 | 126.95 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 119.63 | 81.86 | 37.77 | 100.87 | 126.95 | 0.00 | 0.00 | 744.00 |
February | 128.24 | 86.65 | 41.59 | 108.44 | 102.80 | 0.00 | 0.00 | 672.00 |
March | 111.62 | 58.80 | 52.82 | 92.75 | 73.70 | 0.00 | 0.00 | 744.00 |
April | 100.51 | 46.99 | 53.52 | 80.85 | 54.16 | 0.00 | 0.00 | 720.00 |
May | 83.26 | 22.56 | 60.70 | 65.08 | 33.90 | 0.00 | 0.00 | 744.00 |
June | 80.83 | 16.45 | 64.39 | 71.14 | 24.16 | 0.00 | 0.00 | 720.00 |
July | 85.57 | 21.55 | 64.02 | 77.95 | 21.49 | 0.00 | 0.00 | 744.00 |
August | 96.41 | 34.57 | 61.84 | 95.02 | 25.69 | 0.00 | 0.00 | 744.00 |
September | 116.87 | 61.59 | 55.28 | 118.63 | 41.38 | 0.00 | 0.00 | 720.00 |
October | 122.06 | 76.59 | 45.47 | 121.98 | 57.73 | 0.00 | 0.00 | 744.00 |
November | 92.05 | 57.62 | 34.43 | 81.31 | 83.83 | 0.00 | 0.00 | 720.00 |
December | 98.13 | 74.32 | 23.81 | 91.30 | 118.14 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 102.78 | 53.11 | 49.68 | 92.02 | 63.48 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 80.83 | 16.45 | 23.81 | 65.08 | 21.49 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 128.24 | 86.65 | 64.39 | 121.98 | 126.95 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_DOOR
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 143.24 | 98.01 | 45.23 | 121.11 | 150.52 | 0.00 | 0.00 | 744.00 |
February | 153.55 | 103.75 | 49.80 | 130.15 | 121.91 | 0.00 | 0.00 | 672.00 |
March | 133.65 | 70.40 | 63.25 | 111.30 | 87.42 | 0.00 | 0.00 | 744.00 |
April | 120.35 | 56.26 | 64.09 | 96.91 | 64.28 | 0.00 | 0.00 | 720.00 |
May | 99.70 | 27.02 | 72.68 | 77.99 | 40.30 | 0.00 | 0.00 | 744.00 |
June | 96.79 | 19.69 | 77.10 | 85.13 | 28.75 | 0.00 | 0.00 | 720.00 |
July | 102.46 | 25.80 | 76.65 | 93.25 | 25.61 | 0.00 | 0.00 | 744.00 |
August | 115.44 | 41.39 | 74.05 | 113.68 | 30.57 | 0.00 | 0.00 | 744.00 |
September | 139.94 | 73.75 | 66.19 | 141.99 | 49.24 | 0.00 | 0.00 | 720.00 |
October | 146.15 | 91.71 | 54.44 | 146.14 | 68.61 | 0.00 | 0.00 | 744.00 |
November | 110.22 | 69.00 | 41.22 | 97.54 | 99.44 | 0.00 | 0.00 | 720.00 |
December | 117.49 | 88.99 | 28.51 | 109.48 | 140.13 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 123.07 | 63.59 | 59.48 | 110.28 | 75.35 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 96.79 | 19.69 | 28.51 | 77.99 | 25.61 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 153.55 | 103.75 | 77.10 | 146.14 | 150.52 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 119.63 | 81.86 | 37.77 | 101.77 | 124.33 | 0.00 | 0.00 | 744.00 |
February | 128.24 | 86.65 | 41.59 | 109.38 | 100.54 | 0.00 | 0.00 | 672.00 |
March | 111.62 | 58.80 | 52.82 | 93.57 | 71.69 | 0.00 | 0.00 | 744.00 |
April | 100.51 | 46.99 | 53.52 | 81.42 | 52.53 | 0.00 | 0.00 | 720.00 |
May | 83.26 | 22.56 | 60.70 | 65.84 | 32.54 | 0.00 | 0.00 | 744.00 |
June | 80.83 | 16.45 | 64.39 | 71.31 | 23.32 | 0.00 | 0.00 | 720.00 |
July | 85.57 | 21.55 | 64.02 | 77.92 | 20.88 | 0.00 | 0.00 | 744.00 |
August | 96.41 | 34.57 | 61.84 | 94.98 | 25.00 | 0.00 | 0.00 | 744.00 |
September | 116.87 | 61.59 | 55.28 | 118.81 | 40.51 | 0.00 | 0.00 | 720.00 |
October | 122.06 | 76.59 | 45.47 | 122.61 | 56.50 | 0.00 | 0.00 | 744.00 |
November | 92.05 | 57.62 | 34.43 | 82.01 | 81.80 | 0.00 | 0.00 | 720.00 |
December | 98.13 | 74.32 | 23.81 | 91.95 | 115.63 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 102.78 | 53.11 | 49.68 | 92.54 | 61.93 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 80.83 | 16.45 | 23.81 | 65.84 | 20.88 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 128.24 | 86.65 | 64.39 | 122.61 | 124.33 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 119.63 | 81.86 | 37.77 | 101.77 | 124.33 | 0.00 | 0.00 | 744.00 |
February | 128.24 | 86.65 | 41.59 | 109.38 | 100.54 | 0.00 | 0.00 | 672.00 |
March | 111.62 | 58.80 | 52.82 | 93.57 | 71.69 | 0.00 | 0.00 | 744.00 |
April | 100.51 | 46.99 | 53.52 | 81.42 | 52.53 | 0.00 | 0.00 | 720.00 |
May | 83.26 | 22.56 | 60.70 | 65.84 | 32.54 | 0.00 | 0.00 | 744.00 |
June | 80.83 | 16.45 | 64.39 | 71.31 | 23.32 | 0.00 | 0.00 | 720.00 |
July | 85.57 | 21.55 | 64.02 | 77.92 | 20.88 | 0.00 | 0.00 | 744.00 |
August | 96.41 | 34.57 | 61.84 | 94.98 | 25.00 | 0.00 | 0.00 | 744.00 |
September | 116.87 | 61.59 | 55.28 | 118.81 | 40.51 | 0.00 | 0.00 | 720.00 |
October | 122.06 | 76.59 | 45.47 | 122.61 | 56.50 | 0.00 | 0.00 | 744.00 |
November | 92.05 | 57.62 | 34.43 | 82.01 | 81.80 | 0.00 | 0.00 | 720.00 |
December | 98.13 | 74.32 | 23.81 | 91.95 | 115.63 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 102.78 | 53.11 | 49.68 | 92.54 | 61.93 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 80.83 | 16.45 | 23.81 | 65.84 | 20.88 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 128.24 | 86.65 | 64.39 | 122.61 | 124.33 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_3
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 119.63 | 81.86 | 37.77 | 101.77 | 124.33 | 0.00 | 0.00 | 744.00 |
February | 128.24 | 86.65 | 41.59 | 109.38 | 100.54 | 0.00 | 0.00 | 672.00 |
March | 111.62 | 58.80 | 52.82 | 93.57 | 71.69 | 0.00 | 0.00 | 744.00 |
April | 100.51 | 46.99 | 53.52 | 81.42 | 52.53 | 0.00 | 0.00 | 720.00 |
May | 83.26 | 22.56 | 60.70 | 65.84 | 32.54 | 0.00 | 0.00 | 744.00 |
June | 80.83 | 16.45 | 64.39 | 71.31 | 23.32 | 0.00 | 0.00 | 720.00 |
July | 85.57 | 21.55 | 64.02 | 77.92 | 20.88 | 0.00 | 0.00 | 744.00 |
August | 96.41 | 34.57 | 61.84 | 94.98 | 25.00 | 0.00 | 0.00 | 744.00 |
September | 116.87 | 61.59 | 55.28 | 118.81 | 40.51 | 0.00 | 0.00 | 720.00 |
October | 122.06 | 76.59 | 45.47 | 122.61 | 56.50 | 0.00 | 0.00 | 744.00 |
November | 92.05 | 57.62 | 34.43 | 82.01 | 81.80 | 0.00 | 0.00 | 720.00 |
December | 98.13 | 74.32 | 23.81 | 91.95 | 115.63 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 102.78 | 53.11 | 49.68 | 92.54 | 61.93 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 80.83 | 16.45 | 23.81 | 65.84 | 20.88 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 128.24 | 86.65 | 64.39 | 122.61 | 124.33 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_4
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 119.63 | 81.86 | 37.77 | 101.77 | 124.33 | 0.00 | 0.00 | 744.00 |
February | 128.24 | 86.65 | 41.59 | 109.38 | 100.54 | 0.00 | 0.00 | 672.00 |
March | 111.62 | 58.80 | 52.82 | 93.57 | 71.69 | 0.00 | 0.00 | 744.00 |
April | 100.51 | 46.99 | 53.52 | 81.42 | 52.53 | 0.00 | 0.00 | 720.00 |
May | 83.26 | 22.56 | 60.70 | 65.84 | 32.54 | 0.00 | 0.00 | 744.00 |
June | 80.83 | 16.45 | 64.39 | 71.31 | 23.32 | 0.00 | 0.00 | 720.00 |
July | 85.57 | 21.55 | 64.02 | 77.92 | 20.88 | 0.00 | 0.00 | 744.00 |
August | 96.41 | 34.57 | 61.84 | 94.98 | 25.00 | 0.00 | 0.00 | 744.00 |
September | 116.87 | 61.59 | 55.28 | 118.81 | 40.51 | 0.00 | 0.00 | 720.00 |
October | 122.06 | 76.59 | 45.47 | 122.61 | 56.50 | 0.00 | 0.00 | 744.00 |
November | 92.05 | 57.62 | 34.43 | 82.01 | 81.80 | 0.00 | 0.00 | 720.00 |
December | 98.13 | 74.32 | 23.81 | 91.95 | 115.63 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 102.78 | 53.11 | 49.68 | 92.54 | 61.93 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 80.83 | 16.45 | 23.81 | 65.84 | 20.88 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 128.24 | 86.65 | 64.39 | 122.61 | 124.33 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_DOOR_1
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 143.24 | 98.01 | 45.23 | 122.17 | 147.44 | 0.00 | 0.00 | 744.00 |
February | 153.55 | 103.75 | 49.80 | 131.27 | 119.25 | 0.00 | 0.00 | 672.00 |
March | 133.65 | 70.40 | 63.25 | 112.27 | 85.04 | 0.00 | 0.00 | 744.00 |
April | 120.35 | 56.26 | 64.09 | 97.60 | 62.36 | 0.00 | 0.00 | 720.00 |
May | 99.70 | 27.02 | 72.68 | 78.91 | 38.69 | 0.00 | 0.00 | 744.00 |
June | 96.79 | 19.69 | 77.10 | 85.33 | 27.77 | 0.00 | 0.00 | 720.00 |
July | 102.46 | 25.80 | 76.65 | 93.23 | 24.88 | 0.00 | 0.00 | 744.00 |
August | 115.44 | 41.39 | 74.05 | 113.65 | 29.77 | 0.00 | 0.00 | 744.00 |
September | 139.94 | 73.75 | 66.19 | 142.20 | 48.21 | 0.00 | 0.00 | 720.00 |
October | 146.15 | 91.71 | 54.44 | 146.88 | 67.15 | 0.00 | 0.00 | 744.00 |
November | 110.22 | 69.00 | 41.22 | 98.37 | 97.05 | 0.00 | 0.00 | 720.00 |
December | 117.49 | 88.99 | 28.51 | 110.26 | 137.17 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 123.07 | 63.59 | 59.48 | 110.90 | 73.52 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 96.79 | 19.69 | 28.51 | 78.91 | 24.88 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 153.55 | 103.75 | 77.10 | 146.88 | 147.44 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_DOOR_2
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 143.24 | 98.01 | 45.23 | 122.17 | 147.44 | 0.00 | 0.00 | 744.00 |
February | 153.55 | 103.75 | 49.80 | 131.27 | 119.25 | 0.00 | 0.00 | 672.00 |
March | 133.65 | 70.40 | 63.25 | 112.27 | 85.04 | 0.00 | 0.00 | 744.00 |
April | 120.35 | 56.26 | 64.09 | 97.60 | 62.36 | 0.00 | 0.00 | 720.00 |
May | 99.70 | 27.02 | 72.68 | 78.91 | 38.69 | 0.00 | 0.00 | 744.00 |
June | 96.79 | 19.69 | 77.10 | 85.33 | 27.77 | 0.00 | 0.00 | 720.00 |
July | 102.46 | 25.80 | 76.65 | 93.23 | 24.88 | 0.00 | 0.00 | 744.00 |
August | 115.44 | 41.39 | 74.05 | 113.65 | 29.77 | 0.00 | 0.00 | 744.00 |
September | 139.94 | 73.75 | 66.19 | 142.20 | 48.21 | 0.00 | 0.00 | 720.00 |
October | 146.15 | 91.71 | 54.44 | 146.88 | 67.15 | 0.00 | 0.00 | 744.00 |
November | 110.22 | 69.00 | 41.22 | 98.37 | 97.05 | 0.00 | 0.00 | 720.00 |
December | 117.49 | 88.99 | 28.51 | 110.26 | 137.17 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 123.07 | 63.59 | 59.48 | 110.90 | 73.52 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 96.79 | 19.69 | 28.51 | 78.91 | 24.88 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 153.55 | 103.75 | 77.10 | 146.88 | 147.44 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 119.63 | 81.86 | 37.77 | 101.37 | 125.19 | 0.00 | 0.00 | 744.00 |
February | 128.24 | 86.65 | 41.59 | 109.00 | 101.17 | 0.00 | 0.00 | 672.00 |
March | 111.62 | 58.80 | 52.82 | 93.29 | 72.05 | 0.00 | 0.00 | 744.00 |
April | 100.51 | 46.99 | 53.52 | 81.36 | 52.62 | 0.00 | 0.00 | 720.00 |
May | 83.26 | 22.56 | 60.70 | 66.04 | 32.26 | 0.00 | 0.00 | 744.00 |
June | 80.83 | 16.45 | 64.39 | 71.49 | 23.10 | 0.00 | 0.00 | 720.00 |
July | 85.57 | 21.55 | 64.02 | 78.08 | 20.66 | 0.00 | 0.00 | 744.00 |
August | 96.41 | 34.57 | 61.84 | 95.08 | 24.80 | 0.00 | 0.00 | 744.00 |
September | 116.87 | 61.59 | 55.28 | 118.82 | 40.35 | 0.00 | 0.00 | 720.00 |
October | 122.06 | 76.59 | 45.47 | 122.44 | 56.49 | 0.00 | 0.00 | 744.00 |
November | 92.05 | 57.62 | 34.43 | 81.79 | 82.20 | 0.00 | 0.00 | 720.00 |
December | 98.13 | 74.32 | 23.81 | 91.68 | 116.39 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 102.78 | 53.11 | 49.68 | 92.45 | 62.09 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 80.83 | 16.45 | 23.81 | 66.04 | 20.66 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 128.24 | 86.65 | 64.39 | 122.44 | 125.19 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 119.63 | 81.86 | 37.77 | 101.37 | 125.19 | 0.00 | 0.00 | 744.00 |
February | 128.24 | 86.65 | 41.59 | 109.00 | 101.17 | 0.00 | 0.00 | 672.00 |
March | 111.62 | 58.80 | 52.82 | 93.29 | 72.05 | 0.00 | 0.00 | 744.00 |
April | 100.51 | 46.99 | 53.52 | 81.36 | 52.62 | 0.00 | 0.00 | 720.00 |
May | 83.26 | 22.56 | 60.70 | 66.04 | 32.26 | 0.00 | 0.00 | 744.00 |
June | 80.83 | 16.45 | 64.39 | 71.49 | 23.10 | 0.00 | 0.00 | 720.00 |
July | 85.57 | 21.55 | 64.02 | 78.08 | 20.66 | 0.00 | 0.00 | 744.00 |
August | 96.41 | 34.57 | 61.84 | 95.08 | 24.80 | 0.00 | 0.00 | 744.00 |
September | 116.87 | 61.59 | 55.28 | 118.82 | 40.35 | 0.00 | 0.00 | 720.00 |
October | 122.06 | 76.59 | 45.47 | 122.44 | 56.49 | 0.00 | 0.00 | 744.00 |
November | 92.05 | 57.62 | 34.43 | 81.79 | 82.20 | 0.00 | 0.00 | 720.00 |
December | 98.13 | 74.32 | 23.81 | 91.68 | 116.39 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 102.78 | 53.11 | 49.68 | 92.45 | 62.09 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 80.83 | 16.45 | 23.81 | 66.04 | 20.66 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 128.24 | 86.65 | 64.39 | 122.44 | 125.19 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_DOOR
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 143.24 | 98.01 | 45.23 | 121.72 | 148.43 | 0.00 | 0.00 | 744.00 |
February | 153.55 | 103.75 | 49.80 | 130.83 | 119.96 | 0.00 | 0.00 | 672.00 |
March | 133.65 | 70.40 | 63.25 | 111.96 | 85.45 | 0.00 | 0.00 | 744.00 |
April | 120.35 | 56.26 | 64.09 | 97.54 | 62.45 | 0.00 | 0.00 | 720.00 |
May | 99.70 | 27.02 | 72.68 | 79.15 | 38.36 | 0.00 | 0.00 | 744.00 |
June | 96.79 | 19.69 | 77.10 | 85.55 | 27.50 | 0.00 | 0.00 | 720.00 |
July | 102.46 | 25.80 | 76.65 | 93.43 | 24.62 | 0.00 | 0.00 | 744.00 |
August | 115.44 | 41.39 | 74.05 | 113.77 | 29.52 | 0.00 | 0.00 | 744.00 |
September | 139.94 | 73.75 | 66.19 | 142.23 | 48.01 | 0.00 | 0.00 | 720.00 |
October | 146.15 | 91.71 | 54.44 | 146.70 | 67.13 | 0.00 | 0.00 | 744.00 |
November | 110.22 | 69.00 | 41.22 | 98.12 | 97.50 | 0.00 | 0.00 | 720.00 |
December | 117.49 | 88.99 | 28.51 | 109.95 | 138.04 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 123.07 | 63.59 | 59.48 | 110.80 | 73.70 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 96.79 | 19.69 | 28.51 | 79.15 | 24.62 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 153.55 | 103.75 | 77.10 | 146.70 | 148.43 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 119.63 | 81.86 | 37.77 | 101.41 | 125.04 | 0.00 | 0.00 | 744.00 |
February | 128.24 | 86.65 | 41.59 | 109.04 | 100.96 | 0.00 | 0.00 | 672.00 |
March | 111.62 | 58.80 | 52.82 | 93.38 | 71.78 | 0.00 | 0.00 | 744.00 |
April | 100.51 | 46.99 | 53.52 | 81.50 | 52.26 | 0.00 | 0.00 | 720.00 |
May | 83.26 | 22.56 | 60.70 | 66.43 | 31.74 | 0.00 | 0.00 | 744.00 |
June | 80.83 | 16.45 | 64.39 | 71.65 | 22.88 | 0.00 | 0.00 | 720.00 |
July | 85.57 | 21.55 | 64.02 | 78.18 | 20.53 | 0.00 | 0.00 | 744.00 |
August | 96.41 | 34.57 | 61.84 | 95.16 | 24.67 | 0.00 | 0.00 | 744.00 |
September | 116.87 | 61.59 | 55.28 | 118.94 | 40.12 | 0.00 | 0.00 | 720.00 |
October | 122.06 | 76.59 | 45.47 | 122.56 | 56.22 | 0.00 | 0.00 | 744.00 |
November | 92.05 | 57.62 | 34.43 | 81.87 | 81.94 | 0.00 | 0.00 | 720.00 |
December | 98.13 | 74.32 | 23.81 | 91.72 | 116.20 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 102.78 | 53.11 | 49.68 | 92.56 | 61.85 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 80.83 | 16.45 | 23.81 | 66.43 | 20.53 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 128.24 | 86.65 | 64.39 | 122.56 | 125.04 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 119.63 | 81.86 | 37.77 | 101.41 | 125.04 | 0.00 | 0.00 | 744.00 |
February | 128.24 | 86.65 | 41.59 | 109.04 | 100.96 | 0.00 | 0.00 | 672.00 |
March | 111.62 | 58.80 | 52.82 | 93.38 | 71.78 | 0.00 | 0.00 | 744.00 |
April | 100.51 | 46.99 | 53.52 | 81.50 | 52.26 | 0.00 | 0.00 | 720.00 |
May | 83.26 | 22.56 | 60.70 | 66.43 | 31.74 | 0.00 | 0.00 | 744.00 |
June | 80.83 | 16.45 | 64.39 | 71.65 | 22.88 | 0.00 | 0.00 | 720.00 |
July | 85.57 | 21.55 | 64.02 | 78.18 | 20.53 | 0.00 | 0.00 | 744.00 |
August | 96.41 | 34.57 | 61.84 | 95.16 | 24.67 | 0.00 | 0.00 | 744.00 |
September | 116.87 | 61.59 | 55.28 | 118.94 | 40.12 | 0.00 | 0.00 | 720.00 |
October | 122.06 | 76.59 | 45.47 | 122.56 | 56.22 | 0.00 | 0.00 | 744.00 |
November | 92.05 | 57.62 | 34.43 | 81.87 | 81.94 | 0.00 | 0.00 | 720.00 |
December | 98.13 | 74.32 | 23.81 | 91.72 | 116.20 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 102.78 | 53.11 | 49.68 | 92.56 | 61.85 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 80.83 | 16.45 | 23.81 | 66.43 | 20.53 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 128.24 | 86.65 | 64.39 | 122.56 | 125.04 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_DOOR
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 143.24 | 98.01 | 45.23 | 121.75 | 148.25 | 0.00 | 0.00 | 744.00 |
February | 153.55 | 103.75 | 49.80 | 130.89 | 119.72 | 0.00 | 0.00 | 672.00 |
March | 133.65 | 70.40 | 63.25 | 112.07 | 85.13 | 0.00 | 0.00 | 744.00 |
April | 120.35 | 56.26 | 64.09 | 97.70 | 62.02 | 0.00 | 0.00 | 720.00 |
May | 99.70 | 27.02 | 72.68 | 79.62 | 37.74 | 0.00 | 0.00 | 744.00 |
June | 96.79 | 19.69 | 77.10 | 85.75 | 27.24 | 0.00 | 0.00 | 720.00 |
July | 102.46 | 25.80 | 76.65 | 93.55 | 24.47 | 0.00 | 0.00 | 744.00 |
August | 115.44 | 41.39 | 74.05 | 113.87 | 29.37 | 0.00 | 0.00 | 744.00 |
September | 139.94 | 73.75 | 66.19 | 142.37 | 47.74 | 0.00 | 0.00 | 720.00 |
October | 146.15 | 91.71 | 54.44 | 146.84 | 66.81 | 0.00 | 0.00 | 744.00 |
November | 110.22 | 69.00 | 41.22 | 98.21 | 97.19 | 0.00 | 0.00 | 720.00 |
December | 117.49 | 88.99 | 28.51 | 110.00 | 137.81 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 123.07 | 63.59 | 59.48 | 110.94 | 73.41 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 96.79 | 19.69 | 28.51 | 79.62 | 24.47 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 153.55 | 103.75 | 77.10 | 146.84 | 148.25 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 119.63 | 81.86 | 37.77 | 101.55 | 124.14 | 0.00 | 0.00 | 744.00 |
February | 128.24 | 86.65 | 41.59 | 109.24 | 99.98 | 0.00 | 0.00 | 672.00 |
March | 111.62 | 58.80 | 52.82 | 93.69 | 70.65 | 0.00 | 0.00 | 744.00 |
April | 100.51 | 46.99 | 53.52 | 81.89 | 51.02 | 0.00 | 0.00 | 720.00 |
May | 83.26 | 22.56 | 60.70 | 67.31 | 30.51 | 0.00 | 0.00 | 744.00 |
June | 80.83 | 16.45 | 64.39 | 72.04 | 22.31 | 0.00 | 0.00 | 720.00 |
July | 85.57 | 21.55 | 64.02 | 78.41 | 20.21 | 0.00 | 0.00 | 744.00 |
August | 96.41 | 34.57 | 61.84 | 95.33 | 24.36 | 0.00 | 0.00 | 744.00 |
September | 116.87 | 61.59 | 55.28 | 119.19 | 39.57 | 0.00 | 0.00 | 720.00 |
October | 122.06 | 76.59 | 45.47 | 122.86 | 55.43 | 0.00 | 0.00 | 744.00 |
November | 92.05 | 57.62 | 34.43 | 82.10 | 81.01 | 0.00 | 0.00 | 720.00 |
December | 98.13 | 74.32 | 23.81 | 91.87 | 115.22 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 102.78 | 53.11 | 49.68 | 92.87 | 61.02 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 80.83 | 16.45 | 23.81 | 67.31 | 20.21 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 128.24 | 86.65 | 64.39 | 122.86 | 124.14 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 119.63 | 81.86 | 37.77 | 101.55 | 124.14 | 0.00 | 0.00 | 744.00 |
February | 128.24 | 86.65 | 41.59 | 109.24 | 99.98 | 0.00 | 0.00 | 672.00 |
March | 111.62 | 58.80 | 52.82 | 93.69 | 70.65 | 0.00 | 0.00 | 744.00 |
April | 100.51 | 46.99 | 53.52 | 81.89 | 51.02 | 0.00 | 0.00 | 720.00 |
May | 83.26 | 22.56 | 60.70 | 67.31 | 30.51 | 0.00 | 0.00 | 744.00 |
June | 80.83 | 16.45 | 64.39 | 72.04 | 22.31 | 0.00 | 0.00 | 720.00 |
July | 85.57 | 21.55 | 64.02 | 78.41 | 20.21 | 0.00 | 0.00 | 744.00 |
August | 96.41 | 34.57 | 61.84 | 95.33 | 24.36 | 0.00 | 0.00 | 744.00 |
September | 116.87 | 61.59 | 55.28 | 119.19 | 39.57 | 0.00 | 0.00 | 720.00 |
October | 122.06 | 76.59 | 45.47 | 122.86 | 55.43 | 0.00 | 0.00 | 744.00 |
November | 92.05 | 57.62 | 34.43 | 82.10 | 81.01 | 0.00 | 0.00 | 720.00 |
December | 98.13 | 74.32 | 23.81 | 91.87 | 115.22 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 102.78 | 53.11 | 49.68 | 92.87 | 61.02 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 80.83 | 16.45 | 23.81 | 67.31 | 20.21 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 128.24 | 86.65 | 64.39 | 122.86 | 124.14 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_DOOR
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 143.24 | 98.01 | 45.23 | 121.93 | 147.17 | 0.00 | 0.00 | 744.00 |
February | 153.55 | 103.75 | 49.80 | 131.12 | 118.55 | 0.00 | 0.00 | 672.00 |
March | 133.65 | 70.40 | 63.25 | 112.44 | 83.78 | 0.00 | 0.00 | 744.00 |
April | 120.35 | 56.26 | 64.09 | 98.18 | 60.55 | 0.00 | 0.00 | 720.00 |
May | 99.70 | 27.02 | 72.68 | 80.67 | 36.28 | 0.00 | 0.00 | 744.00 |
June | 96.79 | 19.69 | 77.10 | 86.21 | 26.56 | 0.00 | 0.00 | 720.00 |
July | 102.46 | 25.80 | 76.65 | 93.82 | 24.08 | 0.00 | 0.00 | 744.00 |
August | 115.44 | 41.39 | 74.05 | 114.07 | 29.01 | 0.00 | 0.00 | 744.00 |
September | 139.94 | 73.75 | 66.19 | 142.67 | 47.08 | 0.00 | 0.00 | 720.00 |
October | 146.15 | 91.71 | 54.44 | 147.20 | 65.86 | 0.00 | 0.00 | 744.00 |
November | 110.22 | 69.00 | 41.22 | 98.49 | 96.08 | 0.00 | 0.00 | 720.00 |
December | 117.49 | 88.99 | 28.51 | 110.18 | 136.64 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 123.07 | 63.59 | 59.48 | 111.31 | 72.42 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 96.79 | 19.69 | 28.51 | 80.67 | 24.08 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 153.55 | 103.75 | 77.10 | 147.20 | 147.17 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 119.63 | 81.86 | 37.77 | 102.23 | 120.09 | 0.00 | 0.00 | 744.00 |
February | 128.24 | 86.65 | 41.59 | 110.09 | 95.56 | 0.00 | 0.00 | 672.00 |
March | 111.62 | 58.80 | 52.82 | 94.76 | 65.99 | 0.00 | 0.00 | 744.00 |
April | 100.51 | 46.99 | 53.52 | 83.11 | 46.44 | 0.00 | 0.00 | 720.00 |
May | 83.26 | 22.56 | 60.70 | 69.28 | 27.18 | 0.00 | 0.00 | 744.00 |
June | 80.83 | 16.45 | 64.39 | 73.08 | 20.39 | 0.00 | 0.00 | 720.00 |
July | 85.57 | 21.55 | 64.02 | 79.01 | 18.99 | 0.00 | 0.00 | 744.00 |
August | 96.41 | 34.57 | 61.84 | 95.73 | 23.20 | 0.00 | 0.00 | 744.00 |
September | 116.87 | 61.59 | 55.28 | 119.74 | 37.76 | 0.00 | 0.00 | 720.00 |
October | 122.06 | 76.59 | 45.47 | 123.66 | 52.68 | 0.00 | 0.00 | 744.00 |
November | 92.05 | 57.62 | 34.43 | 82.83 | 77.44 | 0.00 | 0.00 | 720.00 |
December | 98.13 | 74.32 | 23.81 | 92.47 | 110.79 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 102.78 | 53.11 | 49.68 | 93.74 | 57.87 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 80.83 | 16.45 | 23.81 | 69.28 | 18.99 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 128.24 | 86.65 | 64.39 | 123.66 | 120.09 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 119.63 | 81.86 | 37.77 | 102.23 | 120.09 | 0.00 | 0.00 | 744.00 |
February | 128.24 | 86.65 | 41.59 | 110.09 | 95.56 | 0.00 | 0.00 | 672.00 |
March | 111.62 | 58.80 | 52.82 | 94.76 | 65.99 | 0.00 | 0.00 | 744.00 |
April | 100.51 | 46.99 | 53.52 | 83.11 | 46.44 | 0.00 | 0.00 | 720.00 |
May | 83.26 | 22.56 | 60.70 | 69.28 | 27.18 | 0.00 | 0.00 | 744.00 |
June | 80.83 | 16.45 | 64.39 | 73.08 | 20.39 | 0.00 | 0.00 | 720.00 |
July | 85.57 | 21.55 | 64.02 | 79.01 | 18.99 | 0.00 | 0.00 | 744.00 |
August | 96.41 | 34.57 | 61.84 | 95.73 | 23.20 | 0.00 | 0.00 | 744.00 |
September | 116.87 | 61.59 | 55.28 | 119.74 | 37.76 | 0.00 | 0.00 | 720.00 |
October | 122.06 | 76.59 | 45.47 | 123.66 | 52.68 | 0.00 | 0.00 | 744.00 |
November | 92.05 | 57.62 | 34.43 | 82.83 | 77.44 | 0.00 | 0.00 | 720.00 |
December | 98.13 | 74.32 | 23.81 | 92.47 | 110.79 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 102.78 | 53.11 | 49.68 | 93.74 | 57.87 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 80.83 | 16.45 | 23.81 | 69.28 | 18.99 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 128.24 | 86.65 | 64.39 | 123.66 | 120.09 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_DOOR
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 143.24 | 98.01 | 45.23 | 122.77 | 142.33 | 0.00 | 0.00 | 744.00 |
February | 153.55 | 103.75 | 49.80 | 132.17 | 113.28 | 0.00 | 0.00 | 672.00 |
March | 133.65 | 70.40 | 63.25 | 113.74 | 78.25 | 0.00 | 0.00 | 744.00 |
April | 120.35 | 56.26 | 64.09 | 99.65 | 55.11 | 0.00 | 0.00 | 720.00 |
May | 99.70 | 27.02 | 72.68 | 83.03 | 32.34 | 0.00 | 0.00 | 744.00 |
June | 96.79 | 19.69 | 77.10 | 87.46 | 24.28 | 0.00 | 0.00 | 720.00 |
July | 102.46 | 25.80 | 76.65 | 94.54 | 22.64 | 0.00 | 0.00 | 744.00 |
August | 115.44 | 41.39 | 74.05 | 114.55 | 27.63 | 0.00 | 0.00 | 744.00 |
September | 139.94 | 73.75 | 66.19 | 143.33 | 44.95 | 0.00 | 0.00 | 720.00 |
October | 146.15 | 91.71 | 54.44 | 148.17 | 62.61 | 0.00 | 0.00 | 744.00 |
November | 110.22 | 69.00 | 41.22 | 99.38 | 91.84 | 0.00 | 0.00 | 720.00 |
December | 117.49 | 88.99 | 28.51 | 110.91 | 131.36 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 123.07 | 63.59 | 59.48 | 112.37 | 68.68 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 96.79 | 19.69 | 28.51 | 83.03 | 22.64 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 153.55 | 103.75 | 77.10 | 148.17 | 142.33 | 0.00 | 0.00 | 744.00 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.320420E+09 | 0.219248E+09 | 0.101171E+09 | 0.272023E+09 | 0.341778E+09 |
February | 0.310244E+09 | 0.209629E+09 | 0.100615E+09 | 0.264073E+09 | 0.249401E+09 |
March | 0.298959E+09 | 0.157481E+09 | 0.141478E+09 | 0.250285E+09 | 0.196127E+09 |
April | 0.260528E+09 | 0.121793E+09 | 0.138735E+09 | 0.210914E+09 | 0.138068E+09 |
May | 0.223012E+09 | 60435776.82 | 0.162576E+09 | 0.175498E+09 | 88634794.96 |
June | 0.209524E+09 | 42632042.87 | 0.166892E+09 | 0.185713E+09 | 59309746.37 |
July | 0.229186E+09 | 57717198.46 | 0.171469E+09 | 0.210056E+09 | 53601610.85 |
August | 0.258228E+09 | 92583616.90 | 0.165644E+09 | 0.255012E+09 | 65029678.54 |
September | 0.302924E+09 | 0.159644E+09 | 0.143280E+09 | 0.308069E+09 | 0.104111E+09 |
October | 0.326917E+09 | 0.205140E+09 | 0.121778E+09 | 0.326843E+09 | 0.155072E+09 |
November | 0.238598E+09 | 0.149360E+09 | 89237204.53 | 0.211444E+09 | 0.218169E+09 |
December | 0.262824E+09 | 0.199060E+09 | 63763438.80 | 0.245616E+09 | 0.316952E+09 |
Annual Sum or Average | 0.324136E+10 | 0.167472E+10 | 0.156664E+10 | 0.291555E+10 | 0.198625E+10 |
Minimum of Months | 0.209524E+09 | 42632042.87 | 63763438.80 | 0.175498E+09 | 53601610.85 |
Maximum of Months | 0.326917E+09 | 0.219248E+09 | 0.171469E+09 | 0.326843E+09 | 0.341778E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.320420E+09 | 0.219248E+09 | 0.101171E+09 | 0.272023E+09 | 0.341778E+09 |
February | 0.310244E+09 | 0.209629E+09 | 0.100615E+09 | 0.264073E+09 | 0.249401E+09 |
March | 0.298959E+09 | 0.157481E+09 | 0.141478E+09 | 0.250285E+09 | 0.196127E+09 |
April | 0.260528E+09 | 0.121793E+09 | 0.138735E+09 | 0.210914E+09 | 0.138068E+09 |
May | 0.223012E+09 | 60435776.82 | 0.162576E+09 | 0.175498E+09 | 88634794.96 |
June | 0.209524E+09 | 42632042.87 | 0.166892E+09 | 0.185713E+09 | 59309746.37 |
July | 0.229186E+09 | 57717198.46 | 0.171469E+09 | 0.210056E+09 | 53601610.85 |
August | 0.258228E+09 | 92583616.90 | 0.165644E+09 | 0.255012E+09 | 65029678.54 |
September | 0.302924E+09 | 0.159644E+09 | 0.143280E+09 | 0.308069E+09 | 0.104111E+09 |
October | 0.326917E+09 | 0.205140E+09 | 0.121778E+09 | 0.326843E+09 | 0.155072E+09 |
November | 0.238598E+09 | 0.149360E+09 | 89237204.53 | 0.211444E+09 | 0.218169E+09 |
December | 0.262824E+09 | 0.199060E+09 | 63763438.80 | 0.245616E+09 | 0.316952E+09 |
Annual Sum or Average | 0.324136E+10 | 0.167472E+10 | 0.156664E+10 | 0.291555E+10 | 0.198625E+10 |
Minimum of Months | 0.209524E+09 | 42632042.87 | 63763438.80 | 0.175498E+09 | 53601610.85 |
Maximum of Months | 0.326917E+09 | 0.219248E+09 | 0.171469E+09 | 0.326843E+09 | 0.341778E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_3
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.320420E+09 | 0.219248E+09 | 0.101171E+09 | 0.272023E+09 | 0.341778E+09 |
February | 0.310244E+09 | 0.209629E+09 | 0.100615E+09 | 0.264073E+09 | 0.249401E+09 |
March | 0.298959E+09 | 0.157481E+09 | 0.141478E+09 | 0.250285E+09 | 0.196127E+09 |
April | 0.260528E+09 | 0.121793E+09 | 0.138735E+09 | 0.210914E+09 | 0.138068E+09 |
May | 0.223012E+09 | 60435776.82 | 0.162576E+09 | 0.175498E+09 | 88634794.96 |
June | 0.209524E+09 | 42632042.87 | 0.166892E+09 | 0.185713E+09 | 59309746.37 |
July | 0.229186E+09 | 57717198.46 | 0.171469E+09 | 0.210056E+09 | 53601610.85 |
August | 0.258228E+09 | 92583616.90 | 0.165644E+09 | 0.255012E+09 | 65029678.54 |
September | 0.302924E+09 | 0.159644E+09 | 0.143280E+09 | 0.308069E+09 | 0.104111E+09 |
October | 0.326917E+09 | 0.205140E+09 | 0.121778E+09 | 0.326843E+09 | 0.155072E+09 |
November | 0.238598E+09 | 0.149360E+09 | 89237204.53 | 0.211444E+09 | 0.218169E+09 |
December | 0.262824E+09 | 0.199060E+09 | 63763438.80 | 0.245616E+09 | 0.316952E+09 |
Annual Sum or Average | 0.324136E+10 | 0.167472E+10 | 0.156664E+10 | 0.291555E+10 | 0.198625E+10 |
Minimum of Months | 0.209524E+09 | 42632042.87 | 63763438.80 | 0.175498E+09 | 53601610.85 |
Maximum of Months | 0.326917E+09 | 0.219248E+09 | 0.171469E+09 | 0.326843E+09 | 0.341778E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_4
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.320420E+09 | 0.219248E+09 | 0.101171E+09 | 0.272023E+09 | 0.341778E+09 |
February | 0.310244E+09 | 0.209629E+09 | 0.100615E+09 | 0.264073E+09 | 0.249401E+09 |
March | 0.298959E+09 | 0.157481E+09 | 0.141478E+09 | 0.250285E+09 | 0.196127E+09 |
April | 0.260528E+09 | 0.121793E+09 | 0.138735E+09 | 0.210914E+09 | 0.138068E+09 |
May | 0.223012E+09 | 60435776.82 | 0.162576E+09 | 0.175498E+09 | 88634794.96 |
June | 0.209524E+09 | 42632042.87 | 0.166892E+09 | 0.185713E+09 | 59309746.37 |
July | 0.229186E+09 | 57717198.46 | 0.171469E+09 | 0.210056E+09 | 53601610.85 |
August | 0.258228E+09 | 92583616.90 | 0.165644E+09 | 0.255012E+09 | 65029678.54 |
September | 0.302924E+09 | 0.159644E+09 | 0.143280E+09 | 0.308069E+09 | 0.104111E+09 |
October | 0.326917E+09 | 0.205140E+09 | 0.121778E+09 | 0.326843E+09 | 0.155072E+09 |
November | 0.238598E+09 | 0.149360E+09 | 89237204.53 | 0.211444E+09 | 0.218169E+09 |
December | 0.262824E+09 | 0.199060E+09 | 63763438.80 | 0.245616E+09 | 0.316952E+09 |
Annual Sum or Average | 0.324136E+10 | 0.167472E+10 | 0.156664E+10 | 0.291555E+10 | 0.198625E+10 |
Minimum of Months | 0.209524E+09 | 42632042.87 | 63763438.80 | 0.175498E+09 | 53601610.85 |
Maximum of Months | 0.326917E+09 | 0.219248E+09 | 0.171469E+09 | 0.326843E+09 | 0.341778E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_DOOR_1
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.385768E+09 | 0.263963E+09 | 0.121805E+09 | 0.328333E+09 | 0.407530E+09 |
February | 0.373517E+09 | 0.252382E+09 | 0.121136E+09 | 0.318649E+09 | 0.297427E+09 |
March | 0.359930E+09 | 0.189599E+09 | 0.170332E+09 | 0.301944E+09 | 0.233959E+09 |
April | 0.313661E+09 | 0.146632E+09 | 0.167029E+09 | 0.254201E+09 | 0.164837E+09 |
May | 0.268494E+09 | 72761494.47 | 0.195733E+09 | 0.211453E+09 | 0.106036E+09 |
June | 0.252256E+09 | 51326735.82 | 0.200929E+09 | 0.223411E+09 | 71052838.66 |
July | 0.275928E+09 | 69488469.20 | 0.206439E+09 | 0.252664E+09 | 64301775.38 |
August | 0.310893E+09 | 0.111466E+09 | 0.199427E+09 | 0.306777E+09 | 77933980.58 |
September | 0.364704E+09 | 0.192202E+09 | 0.172502E+09 | 0.370734E+09 | 0.124656E+09 |
October | 0.393591E+09 | 0.246977E+09 | 0.146614E+09 | 0.393691E+09 | 0.185395E+09 |
November | 0.287259E+09 | 0.179822E+09 | 0.107437E+09 | 0.254990E+09 | 0.260303E+09 |
December | 0.316426E+09 | 0.239658E+09 | 76767824.34 | 0.296126E+09 | 0.378087E+09 |
Annual Sum or Average | 0.390243E+10 | 0.201628E+10 | 0.188615E+10 | 0.351297E+10 | 0.237152E+10 |
Minimum of Months | 0.252256E+09 | 51326735.82 | 76767824.34 | 0.211453E+09 | 64301775.38 |
Maximum of Months | 0.393591E+09 | 0.263963E+09 | 0.206439E+09 | 0.393691E+09 | 0.407530E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_DOOR_2
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.385768E+09 | 0.263963E+09 | 0.121805E+09 | 0.328333E+09 | 0.407530E+09 |
February | 0.373517E+09 | 0.252382E+09 | 0.121136E+09 | 0.318649E+09 | 0.297427E+09 |
March | 0.359930E+09 | 0.189599E+09 | 0.170332E+09 | 0.301944E+09 | 0.233959E+09 |
April | 0.313661E+09 | 0.146632E+09 | 0.167029E+09 | 0.254201E+09 | 0.164837E+09 |
May | 0.268494E+09 | 72761494.47 | 0.195733E+09 | 0.211453E+09 | 0.106036E+09 |
June | 0.252256E+09 | 51326735.82 | 0.200929E+09 | 0.223411E+09 | 71052838.66 |
July | 0.275928E+09 | 69488469.20 | 0.206439E+09 | 0.252664E+09 | 64301775.38 |
August | 0.310893E+09 | 0.111466E+09 | 0.199427E+09 | 0.306777E+09 | 77933980.58 |
September | 0.364704E+09 | 0.192202E+09 | 0.172502E+09 | 0.370734E+09 | 0.124656E+09 |
October | 0.393591E+09 | 0.246977E+09 | 0.146614E+09 | 0.393691E+09 | 0.185395E+09 |
November | 0.287259E+09 | 0.179822E+09 | 0.107437E+09 | 0.254990E+09 | 0.260303E+09 |
December | 0.316426E+09 | 0.239658E+09 | 76767824.34 | 0.296126E+09 | 0.378087E+09 |
Annual Sum or Average | 0.390243E+10 | 0.201628E+10 | 0.188615E+10 | 0.351297E+10 | 0.237152E+10 |
Minimum of Months | 0.252256E+09 | 51326735.82 | 76767824.34 | 0.211453E+09 | 64301775.38 |
Maximum of Months | 0.393591E+09 | 0.263963E+09 | 0.206439E+09 | 0.393691E+09 | 0.407530E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.320420E+09 | 0.219248E+09 | 0.101171E+09 | 0.269320E+09 | 0.352076E+09 |
February | 0.310244E+09 | 0.209629E+09 | 0.100615E+09 | 0.261334E+09 | 0.258928E+09 |
March | 0.298959E+09 | 0.157481E+09 | 0.141478E+09 | 0.246938E+09 | 0.206913E+09 |
April | 0.260528E+09 | 0.121793E+09 | 0.138735E+09 | 0.208080E+09 | 0.148035E+09 |
May | 0.223012E+09 | 60435776.82 | 0.162576E+09 | 0.171584E+09 | 94743689.12 |
June | 0.209524E+09 | 42632042.87 | 0.166892E+09 | 0.183999E+09 | 62014834.92 |
July | 0.229186E+09 | 57717198.46 | 0.171469E+09 | 0.209479E+09 | 54232364.05 |
August | 0.258228E+09 | 92583616.90 | 0.165644E+09 | 0.254540E+09 | 65773733.35 |
September | 0.302924E+09 | 0.159644E+09 | 0.143280E+09 | 0.306759E+09 | 0.107345E+09 |
October | 0.326917E+09 | 0.205140E+09 | 0.121778E+09 | 0.323779E+09 | 0.164056E+09 |
November | 0.238598E+09 | 0.149360E+09 | 89237204.53 | 0.208822E+09 | 0.228075E+09 |
December | 0.262824E+09 | 0.199060E+09 | 63763438.80 | 0.243569E+09 | 0.327711E+09 |
Annual Sum or Average | 0.324136E+10 | 0.167472E+10 | 0.156664E+10 | 0.288820E+10 | 0.206990E+10 |
Minimum of Months | 0.209524E+09 | 42632042.87 | 63763438.80 | 0.171584E+09 | 54232364.05 |
Maximum of Months | 0.326917E+09 | 0.219248E+09 | 0.171469E+09 | 0.323779E+09 | 0.352076E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.320420E+09 | 0.219248E+09 | 0.101171E+09 | 0.269320E+09 | 0.352076E+09 |
February | 0.310244E+09 | 0.209629E+09 | 0.100615E+09 | 0.261334E+09 | 0.258928E+09 |
March | 0.298959E+09 | 0.157481E+09 | 0.141478E+09 | 0.246938E+09 | 0.206913E+09 |
April | 0.260528E+09 | 0.121793E+09 | 0.138735E+09 | 0.208080E+09 | 0.148035E+09 |
May | 0.223012E+09 | 60435776.82 | 0.162576E+09 | 0.171584E+09 | 94743689.12 |
June | 0.209524E+09 | 42632042.87 | 0.166892E+09 | 0.183999E+09 | 62014834.92 |
July | 0.229186E+09 | 57717198.46 | 0.171469E+09 | 0.209479E+09 | 54232364.05 |
August | 0.258228E+09 | 92583616.90 | 0.165644E+09 | 0.254540E+09 | 65773733.35 |
September | 0.302924E+09 | 0.159644E+09 | 0.143280E+09 | 0.306759E+09 | 0.107345E+09 |
October | 0.326917E+09 | 0.205140E+09 | 0.121778E+09 | 0.323779E+09 | 0.164056E+09 |
November | 0.238598E+09 | 0.149360E+09 | 89237204.53 | 0.208822E+09 | 0.228075E+09 |
December | 0.262824E+09 | 0.199060E+09 | 63763438.80 | 0.243569E+09 | 0.327711E+09 |
Annual Sum or Average | 0.324136E+10 | 0.167472E+10 | 0.156664E+10 | 0.288820E+10 | 0.206990E+10 |
Minimum of Months | 0.209524E+09 | 42632042.87 | 63763438.80 | 0.171584E+09 | 54232364.05 |
Maximum of Months | 0.326917E+09 | 0.219248E+09 | 0.171469E+09 | 0.323779E+09 | 0.352076E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_DOOR
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.385768E+09 | 0.263963E+09 | 0.121805E+09 | 0.325089E+09 | 0.419781E+09 |
February | 0.373517E+09 | 0.252382E+09 | 0.121136E+09 | 0.315361E+09 | 0.308756E+09 |
March | 0.359930E+09 | 0.189599E+09 | 0.170332E+09 | 0.297910E+09 | 0.246756E+09 |
April | 0.313661E+09 | 0.146632E+09 | 0.167029E+09 | 0.250779E+09 | 0.176667E+09 |
May | 0.268494E+09 | 72761494.47 | 0.195733E+09 | 0.206752E+09 | 0.113287E+09 |
June | 0.252256E+09 | 51326735.82 | 0.200929E+09 | 0.221346E+09 | 74264389.30 |
July | 0.275928E+09 | 69488469.20 | 0.206439E+09 | 0.251966E+09 | 65050048.93 |
August | 0.310893E+09 | 0.111466E+09 | 0.199427E+09 | 0.306212E+09 | 78807210.78 |
September | 0.364704E+09 | 0.192202E+09 | 0.172502E+09 | 0.369170E+09 | 0.128475E+09 |
October | 0.393591E+09 | 0.246977E+09 | 0.146614E+09 | 0.390036E+09 | 0.196001E+09 |
November | 0.287259E+09 | 0.179822E+09 | 0.107437E+09 | 0.251850E+09 | 0.272031E+09 |
December | 0.316426E+09 | 0.239658E+09 | 76767824.34 | 0.293670E+09 | 0.390876E+09 |
Annual Sum or Average | 0.390243E+10 | 0.201628E+10 | 0.188615E+10 | 0.348014E+10 | 0.247075E+10 |
Minimum of Months | 0.252256E+09 | 51326735.82 | 76767824.34 | 0.206752E+09 | 65050048.93 |
Maximum of Months | 0.393591E+09 | 0.263963E+09 | 0.206439E+09 | 0.390036E+09 | 0.419781E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.320420E+09 | 0.219248E+09 | 0.101171E+09 | 0.269505E+09 | 0.344658E+09 |
February | 0.310244E+09 | 0.209629E+09 | 0.100615E+09 | 0.261597E+09 | 0.252760E+09 |
March | 0.298959E+09 | 0.157481E+09 | 0.141478E+09 | 0.247432E+09 | 0.201590E+09 |
April | 0.260528E+09 | 0.121793E+09 | 0.138735E+09 | 0.208521E+09 | 0.144110E+09 |
May | 0.223012E+09 | 60435776.82 | 0.162576E+09 | 0.172257E+09 | 94182018.75 |
June | 0.209524E+09 | 42632042.87 | 0.166892E+09 | 0.183596E+09 | 64051854.67 |
July | 0.229186E+09 | 57717198.46 | 0.171469E+09 | 0.208500E+09 | 58101132.46 |
August | 0.258228E+09 | 92583616.90 | 0.165644E+09 | 0.254221E+09 | 69448295.74 |
September | 0.302924E+09 | 0.159644E+09 | 0.143280E+09 | 0.306852E+09 | 0.108953E+09 |
October | 0.326917E+09 | 0.205140E+09 | 0.121778E+09 | 0.325229E+09 | 0.158876E+09 |
November | 0.238598E+09 | 0.149360E+09 | 89237204.53 | 0.209640E+09 | 0.222030E+09 |
December | 0.262824E+09 | 0.199060E+09 | 63763438.80 | 0.243906E+09 | 0.321043E+09 |
Annual Sum or Average | 0.324136E+10 | 0.167472E+10 | 0.156664E+10 | 0.289126E+10 | 0.203980E+10 |
Minimum of Months | 0.209524E+09 | 42632042.87 | 63763438.80 | 0.172257E+09 | 58101132.46 |
Maximum of Months | 0.326917E+09 | 0.219248E+09 | 0.171469E+09 | 0.325229E+09 | 0.344658E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.320420E+09 | 0.219248E+09 | 0.101171E+09 | 0.269505E+09 | 0.344658E+09 |
February | 0.310244E+09 | 0.209629E+09 | 0.100615E+09 | 0.261597E+09 | 0.252760E+09 |
March | 0.298959E+09 | 0.157481E+09 | 0.141478E+09 | 0.247432E+09 | 0.201590E+09 |
April | 0.260528E+09 | 0.121793E+09 | 0.138735E+09 | 0.208521E+09 | 0.144110E+09 |
May | 0.223012E+09 | 60435776.82 | 0.162576E+09 | 0.172257E+09 | 94182018.75 |
June | 0.209524E+09 | 42632042.87 | 0.166892E+09 | 0.183596E+09 | 64051854.67 |
July | 0.229186E+09 | 57717198.46 | 0.171469E+09 | 0.208500E+09 | 58101132.46 |
August | 0.258228E+09 | 92583616.90 | 0.165644E+09 | 0.254221E+09 | 69448295.74 |
September | 0.302924E+09 | 0.159644E+09 | 0.143280E+09 | 0.306852E+09 | 0.108953E+09 |
October | 0.326917E+09 | 0.205140E+09 | 0.121778E+09 | 0.325229E+09 | 0.158876E+09 |
November | 0.238598E+09 | 0.149360E+09 | 89237204.53 | 0.209640E+09 | 0.222030E+09 |
December | 0.262824E+09 | 0.199060E+09 | 63763438.80 | 0.243906E+09 | 0.321043E+09 |
Annual Sum or Average | 0.324136E+10 | 0.167472E+10 | 0.156664E+10 | 0.289126E+10 | 0.203980E+10 |
Minimum of Months | 0.209524E+09 | 42632042.87 | 63763438.80 | 0.172257E+09 | 58101132.46 |
Maximum of Months | 0.326917E+09 | 0.219248E+09 | 0.171469E+09 | 0.325229E+09 | 0.344658E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_DOOR
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.383660E+09 | 0.262521E+09 | 0.121139E+09 | 0.323556E+09 | 0.408691E+09 |
February | 0.371476E+09 | 0.251003E+09 | 0.120474E+09 | 0.313976E+09 | 0.299766E+09 |
March | 0.357964E+09 | 0.188563E+09 | 0.169401E+09 | 0.296886E+09 | 0.239106E+09 |
April | 0.311947E+09 | 0.145831E+09 | 0.166116E+09 | 0.249949E+09 | 0.171054E+09 |
May | 0.267027E+09 | 72363890.67 | 0.194663E+09 | 0.206431E+09 | 0.111966E+09 |
June | 0.250877E+09 | 51046261.85 | 0.199831E+09 | 0.219674E+09 | 76224898.92 |
July | 0.274420E+09 | 69108750.79 | 0.205311E+09 | 0.249440E+09 | 69215752.39 |
August | 0.309194E+09 | 0.110857E+09 | 0.198337E+09 | 0.304160E+09 | 82661649.25 |
September | 0.362712E+09 | 0.191152E+09 | 0.171559E+09 | 0.367266E+09 | 0.129628E+09 |
October | 0.391441E+09 | 0.245628E+09 | 0.145813E+09 | 0.389641E+09 | 0.188799E+09 |
November | 0.285689E+09 | 0.178839E+09 | 0.106850E+09 | 0.251468E+09 | 0.263387E+09 |
December | 0.314697E+09 | 0.238348E+09 | 76348328.03 | 0.292486E+09 | 0.380830E+09 |
Annual Sum or Average | 0.388110E+10 | 0.200526E+10 | 0.187584E+10 | 0.346493E+10 | 0.242133E+10 |
Minimum of Months | 0.250877E+09 | 51046261.85 | 76348328.03 | 0.206431E+09 | 69215752.39 |
Maximum of Months | 0.391441E+09 | 0.262521E+09 | 0.205311E+09 | 0.389641E+09 | 0.408691E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.320420E+09 | 0.219248E+09 | 0.101171E+09 | 0.269818E+09 | 0.341926E+09 |
February | 0.310244E+09 | 0.209629E+09 | 0.100615E+09 | 0.261945E+09 | 0.250390E+09 |
March | 0.298959E+09 | 0.157481E+09 | 0.141478E+09 | 0.247893E+09 | 0.199250E+09 |
April | 0.260528E+09 | 0.121793E+09 | 0.138735E+09 | 0.208994E+09 | 0.142079E+09 |
May | 0.223012E+09 | 60435776.82 | 0.162576E+09 | 0.173083E+09 | 92627684.73 |
June | 0.209524E+09 | 42632042.87 | 0.166892E+09 | 0.183864E+09 | 63557393.48 |
July | 0.229186E+09 | 57717198.46 | 0.171469E+09 | 0.208488E+09 | 58156638.87 |
August | 0.258228E+09 | 92583616.90 | 0.165644E+09 | 0.254245E+09 | 69417745.19 |
September | 0.302924E+09 | 0.159644E+09 | 0.143280E+09 | 0.307075E+09 | 0.108282E+09 |
October | 0.326917E+09 | 0.205140E+09 | 0.121778E+09 | 0.326030E+09 | 0.156373E+09 |
November | 0.238598E+09 | 0.149360E+09 | 89237204.53 | 0.210208E+09 | 0.219317E+09 |
December | 0.262824E+09 | 0.199060E+09 | 63763438.80 | 0.244202E+09 | 0.318377E+09 |
Annual Sum or Average | 0.324136E+10 | 0.167472E+10 | 0.156664E+10 | 0.289585E+10 | 0.201975E+10 |
Minimum of Months | 0.209524E+09 | 42632042.87 | 63763438.80 | 0.173083E+09 | 58156638.87 |
Maximum of Months | 0.326917E+09 | 0.219248E+09 | 0.171469E+09 | 0.326030E+09 | 0.341926E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.320420E+09 | 0.219248E+09 | 0.101171E+09 | 0.269818E+09 | 0.341926E+09 |
February | 0.310244E+09 | 0.209629E+09 | 0.100615E+09 | 0.261945E+09 | 0.250390E+09 |
March | 0.298959E+09 | 0.157481E+09 | 0.141478E+09 | 0.247893E+09 | 0.199250E+09 |
April | 0.260528E+09 | 0.121793E+09 | 0.138735E+09 | 0.208994E+09 | 0.142079E+09 |
May | 0.223012E+09 | 60435776.82 | 0.162576E+09 | 0.173083E+09 | 92627684.73 |
June | 0.209524E+09 | 42632042.87 | 0.166892E+09 | 0.183864E+09 | 63557393.48 |
July | 0.229186E+09 | 57717198.46 | 0.171469E+09 | 0.208488E+09 | 58156638.87 |
August | 0.258228E+09 | 92583616.90 | 0.165644E+09 | 0.254245E+09 | 69417745.19 |
September | 0.302924E+09 | 0.159644E+09 | 0.143280E+09 | 0.307075E+09 | 0.108282E+09 |
October | 0.326917E+09 | 0.205140E+09 | 0.121778E+09 | 0.326030E+09 | 0.156373E+09 |
November | 0.238598E+09 | 0.149360E+09 | 89237204.53 | 0.210208E+09 | 0.219317E+09 |
December | 0.262824E+09 | 0.199060E+09 | 63763438.80 | 0.244202E+09 | 0.318377E+09 |
Annual Sum or Average | 0.324136E+10 | 0.167472E+10 | 0.156664E+10 | 0.289585E+10 | 0.201975E+10 |
Minimum of Months | 0.209524E+09 | 42632042.87 | 63763438.80 | 0.173083E+09 | 58156638.87 |
Maximum of Months | 0.326917E+09 | 0.219248E+09 | 0.171469E+09 | 0.326030E+09 | 0.341926E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_DOOR
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.383660E+09 | 0.262521E+09 | 0.121139E+09 | 0.323939E+09 | 0.405430E+09 |
February | 0.371476E+09 | 0.251003E+09 | 0.120474E+09 | 0.314399E+09 | 0.296940E+09 |
March | 0.357964E+09 | 0.188563E+09 | 0.169401E+09 | 0.297446E+09 | 0.236320E+09 |
April | 0.311947E+09 | 0.145831E+09 | 0.166116E+09 | 0.250520E+09 | 0.168637E+09 |
May | 0.267027E+09 | 72363890.67 | 0.194663E+09 | 0.207421E+09 | 0.110120E+09 |
June | 0.250877E+09 | 51046261.85 | 0.199831E+09 | 0.219995E+09 | 75637900.64 |
July | 0.274420E+09 | 69108750.79 | 0.205311E+09 | 0.249425E+09 | 69282013.78 |
August | 0.309194E+09 | 0.110857E+09 | 0.198337E+09 | 0.304189E+09 | 82625231.10 |
September | 0.362712E+09 | 0.191152E+09 | 0.171559E+09 | 0.367535E+09 | 0.128831E+09 |
October | 0.391441E+09 | 0.245628E+09 | 0.145813E+09 | 0.390602E+09 | 0.185823E+09 |
November | 0.285689E+09 | 0.178839E+09 | 0.106850E+09 | 0.252152E+09 | 0.260157E+09 |
December | 0.314697E+09 | 0.238348E+09 | 76348328.03 | 0.292845E+09 | 0.377649E+09 |
Annual Sum or Average | 0.388110E+10 | 0.200526E+10 | 0.187584E+10 | 0.347047E+10 | 0.239745E+10 |
Minimum of Months | 0.250877E+09 | 51046261.85 | 76348328.03 | 0.207421E+09 | 69282013.78 |
Maximum of Months | 0.391441E+09 | 0.262521E+09 | 0.205311E+09 | 0.390602E+09 | 0.405430E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.320420E+09 | 0.219248E+09 | 0.101171E+09 | 0.270182E+09 | 0.340011E+09 |
February | 0.310244E+09 | 0.209629E+09 | 0.100615E+09 | 0.262329E+09 | 0.248695E+09 |
March | 0.298959E+09 | 0.157481E+09 | 0.141478E+09 | 0.248424E+09 | 0.197410E+09 |
April | 0.260528E+09 | 0.121793E+09 | 0.138735E+09 | 0.209551E+09 | 0.140371E+09 |
May | 0.223012E+09 | 60435776.82 | 0.162576E+09 | 0.174304E+09 | 90794721.15 |
June | 0.209524E+09 | 42632042.87 | 0.166892E+09 | 0.184406E+09 | 62620546.01 |
July | 0.229186E+09 | 57717198.46 | 0.171469E+09 | 0.208778E+09 | 57569668.21 |
August | 0.258228E+09 | 92583616.90 | 0.165644E+09 | 0.254498E+09 | 68795679.57 |
September | 0.302924E+09 | 0.159644E+09 | 0.143280E+09 | 0.307485E+09 | 0.107257E+09 |
October | 0.326917E+09 | 0.205140E+09 | 0.121778E+09 | 0.326713E+09 | 0.154628E+09 |
November | 0.238598E+09 | 0.149360E+09 | 89237204.53 | 0.210755E+09 | 0.217289E+09 |
December | 0.262824E+09 | 0.199060E+09 | 63763438.80 | 0.244525E+09 | 0.316421E+09 |
Annual Sum or Average | 0.324136E+10 | 0.167472E+10 | 0.156664E+10 | 0.290195E+10 | 0.200186E+10 |
Minimum of Months | 0.209524E+09 | 42632042.87 | 63763438.80 | 0.174304E+09 | 57569668.21 |
Maximum of Months | 0.326917E+09 | 0.219248E+09 | 0.171469E+09 | 0.326713E+09 | 0.340011E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.320420E+09 | 0.219248E+09 | 0.101171E+09 | 0.270182E+09 | 0.340011E+09 |
February | 0.310244E+09 | 0.209629E+09 | 0.100615E+09 | 0.262329E+09 | 0.248695E+09 |
March | 0.298959E+09 | 0.157481E+09 | 0.141478E+09 | 0.248424E+09 | 0.197410E+09 |
April | 0.260528E+09 | 0.121793E+09 | 0.138735E+09 | 0.209551E+09 | 0.140371E+09 |
May | 0.223012E+09 | 60435776.82 | 0.162576E+09 | 0.174304E+09 | 90794721.15 |
June | 0.209524E+09 | 42632042.87 | 0.166892E+09 | 0.184406E+09 | 62620546.01 |
July | 0.229186E+09 | 57717198.46 | 0.171469E+09 | 0.208778E+09 | 57569668.21 |
August | 0.258228E+09 | 92583616.90 | 0.165644E+09 | 0.254498E+09 | 68795679.57 |
September | 0.302924E+09 | 0.159644E+09 | 0.143280E+09 | 0.307485E+09 | 0.107257E+09 |
October | 0.326917E+09 | 0.205140E+09 | 0.121778E+09 | 0.326713E+09 | 0.154628E+09 |
November | 0.238598E+09 | 0.149360E+09 | 89237204.53 | 0.210755E+09 | 0.217289E+09 |
December | 0.262824E+09 | 0.199060E+09 | 63763438.80 | 0.244525E+09 | 0.316421E+09 |
Annual Sum or Average | 0.324136E+10 | 0.167472E+10 | 0.156664E+10 | 0.290195E+10 | 0.200186E+10 |
Minimum of Months | 0.209524E+09 | 42632042.87 | 63763438.80 | 0.174304E+09 | 57569668.21 |
Maximum of Months | 0.326917E+09 | 0.219248E+09 | 0.171469E+09 | 0.326713E+09 | 0.340011E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_DOOR
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.383660E+09 | 0.262521E+09 | 0.121139E+09 | 0.324383E+09 | 0.403144E+09 |
February | 0.371476E+09 | 0.251003E+09 | 0.120474E+09 | 0.314867E+09 | 0.294918E+09 |
March | 0.357964E+09 | 0.188563E+09 | 0.169401E+09 | 0.298093E+09 | 0.234134E+09 |
April | 0.311947E+09 | 0.145831E+09 | 0.166116E+09 | 0.251192E+09 | 0.166608E+09 |
May | 0.267027E+09 | 72363890.67 | 0.194663E+09 | 0.208883E+09 | 0.107949E+09 |
June | 0.250877E+09 | 51046261.85 | 0.199831E+09 | 0.220645E+09 | 74530336.69 |
July | 0.274420E+09 | 69108750.79 | 0.205311E+09 | 0.249774E+09 | 68589372.28 |
August | 0.309194E+09 | 0.110857E+09 | 0.198337E+09 | 0.304493E+09 | 81891504.98 |
September | 0.362712E+09 | 0.191152E+09 | 0.171559E+09 | 0.368027E+09 | 0.127619E+09 |
October | 0.391441E+09 | 0.245628E+09 | 0.145813E+09 | 0.391424E+09 | 0.183753E+09 |
November | 0.285689E+09 | 0.178839E+09 | 0.106850E+09 | 0.252813E+09 | 0.257745E+09 |
December | 0.314697E+09 | 0.238348E+09 | 76348328.03 | 0.293240E+09 | 0.375314E+09 |
Annual Sum or Average | 0.388110E+10 | 0.200526E+10 | 0.187584E+10 | 0.347783E+10 | 0.237620E+10 |
Minimum of Months | 0.250877E+09 | 51046261.85 | 76348328.03 | 0.208883E+09 | 68589372.28 |
Maximum of Months | 0.391441E+09 | 0.262521E+09 | 0.205311E+09 | 0.391424E+09 | 0.403144E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.320420E+09 | 0.219248E+09 | 0.101171E+09 | 0.272584E+09 | 0.333012E+09 |
February | 0.310244E+09 | 0.209629E+09 | 0.100615E+09 | 0.264602E+09 | 0.243236E+09 |
March | 0.298959E+09 | 0.157481E+09 | 0.141478E+09 | 0.250605E+09 | 0.192015E+09 |
April | 0.260528E+09 | 0.121793E+09 | 0.138735E+09 | 0.211035E+09 | 0.136170E+09 |
May | 0.223012E+09 | 60435776.82 | 0.162576E+09 | 0.176358E+09 | 87145043.97 |
June | 0.209524E+09 | 42632042.87 | 0.166892E+09 | 0.184837E+09 | 60457873.83 |
July | 0.229186E+09 | 57717198.46 | 0.171469E+09 | 0.208689E+09 | 55931672.23 |
August | 0.258228E+09 | 92583616.90 | 0.165644E+09 | 0.254394E+09 | 66958981.86 |
September | 0.302924E+09 | 0.159644E+09 | 0.143280E+09 | 0.307945E+09 | 0.105015E+09 |
October | 0.326917E+09 | 0.205140E+09 | 0.121778E+09 | 0.328388E+09 | 0.151319E+09 |
November | 0.238598E+09 | 0.149360E+09 | 89237204.53 | 0.212581E+09 | 0.212029E+09 |
December | 0.262824E+09 | 0.199060E+09 | 63763438.80 | 0.246276E+09 | 0.309717E+09 |
Annual Sum or Average | 0.324136E+10 | 0.167472E+10 | 0.156664E+10 | 0.291829E+10 | 0.195301E+10 |
Minimum of Months | 0.209524E+09 | 42632042.87 | 63763438.80 | 0.176358E+09 | 55931672.23 |
Maximum of Months | 0.326917E+09 | 0.219248E+09 | 0.171469E+09 | 0.328388E+09 | 0.333012E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.320420E+09 | 0.219248E+09 | 0.101171E+09 | 0.272584E+09 | 0.333012E+09 |
February | 0.310244E+09 | 0.209629E+09 | 0.100615E+09 | 0.264602E+09 | 0.243236E+09 |
March | 0.298959E+09 | 0.157481E+09 | 0.141478E+09 | 0.250605E+09 | 0.192015E+09 |
April | 0.260528E+09 | 0.121793E+09 | 0.138735E+09 | 0.211035E+09 | 0.136170E+09 |
May | 0.223012E+09 | 60435776.82 | 0.162576E+09 | 0.176358E+09 | 87145043.97 |
June | 0.209524E+09 | 42632042.87 | 0.166892E+09 | 0.184837E+09 | 60457873.83 |
July | 0.229186E+09 | 57717198.46 | 0.171469E+09 | 0.208689E+09 | 55931672.23 |
August | 0.258228E+09 | 92583616.90 | 0.165644E+09 | 0.254394E+09 | 66958981.86 |
September | 0.302924E+09 | 0.159644E+09 | 0.143280E+09 | 0.307945E+09 | 0.105015E+09 |
October | 0.326917E+09 | 0.205140E+09 | 0.121778E+09 | 0.328388E+09 | 0.151319E+09 |
November | 0.238598E+09 | 0.149360E+09 | 89237204.53 | 0.212581E+09 | 0.212029E+09 |
December | 0.262824E+09 | 0.199060E+09 | 63763438.80 | 0.246276E+09 | 0.309717E+09 |
Annual Sum or Average | 0.324136E+10 | 0.167472E+10 | 0.156664E+10 | 0.291829E+10 | 0.195301E+10 |
Minimum of Months | 0.209524E+09 | 42632042.87 | 63763438.80 | 0.176358E+09 | 55931672.23 |
Maximum of Months | 0.326917E+09 | 0.219248E+09 | 0.171469E+09 | 0.328388E+09 | 0.333012E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_3
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.320420E+09 | 0.219248E+09 | 0.101171E+09 | 0.272584E+09 | 0.333012E+09 |
February | 0.310244E+09 | 0.209629E+09 | 0.100615E+09 | 0.264602E+09 | 0.243236E+09 |
March | 0.298959E+09 | 0.157481E+09 | 0.141478E+09 | 0.250605E+09 | 0.192015E+09 |
April | 0.260528E+09 | 0.121793E+09 | 0.138735E+09 | 0.211035E+09 | 0.136170E+09 |
May | 0.223012E+09 | 60435776.82 | 0.162576E+09 | 0.176358E+09 | 87145043.97 |
June | 0.209524E+09 | 42632042.87 | 0.166892E+09 | 0.184837E+09 | 60457873.83 |
July | 0.229186E+09 | 57717198.46 | 0.171469E+09 | 0.208689E+09 | 55931672.23 |
August | 0.258228E+09 | 92583616.90 | 0.165644E+09 | 0.254394E+09 | 66958981.86 |
September | 0.302924E+09 | 0.159644E+09 | 0.143280E+09 | 0.307945E+09 | 0.105015E+09 |
October | 0.326917E+09 | 0.205140E+09 | 0.121778E+09 | 0.328388E+09 | 0.151319E+09 |
November | 0.238598E+09 | 0.149360E+09 | 89237204.53 | 0.212581E+09 | 0.212029E+09 |
December | 0.262824E+09 | 0.199060E+09 | 63763438.80 | 0.246276E+09 | 0.309717E+09 |
Annual Sum or Average | 0.324136E+10 | 0.167472E+10 | 0.156664E+10 | 0.291829E+10 | 0.195301E+10 |
Minimum of Months | 0.209524E+09 | 42632042.87 | 63763438.80 | 0.176358E+09 | 55931672.23 |
Maximum of Months | 0.326917E+09 | 0.219248E+09 | 0.171469E+09 | 0.328388E+09 | 0.333012E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_4
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.320420E+09 | 0.219248E+09 | 0.101171E+09 | 0.272584E+09 | 0.333012E+09 |
February | 0.310244E+09 | 0.209629E+09 | 0.100615E+09 | 0.264602E+09 | 0.243236E+09 |
March | 0.298959E+09 | 0.157481E+09 | 0.141478E+09 | 0.250605E+09 | 0.192015E+09 |
April | 0.260528E+09 | 0.121793E+09 | 0.138735E+09 | 0.211035E+09 | 0.136170E+09 |
May | 0.223012E+09 | 60435776.82 | 0.162576E+09 | 0.176358E+09 | 87145043.97 |
June | 0.209524E+09 | 42632042.87 | 0.166892E+09 | 0.184837E+09 | 60457873.83 |
July | 0.229186E+09 | 57717198.46 | 0.171469E+09 | 0.208689E+09 | 55931672.23 |
August | 0.258228E+09 | 92583616.90 | 0.165644E+09 | 0.254394E+09 | 66958981.86 |
September | 0.302924E+09 | 0.159644E+09 | 0.143280E+09 | 0.307945E+09 | 0.105015E+09 |
October | 0.326917E+09 | 0.205140E+09 | 0.121778E+09 | 0.328388E+09 | 0.151319E+09 |
November | 0.238598E+09 | 0.149360E+09 | 89237204.53 | 0.212581E+09 | 0.212029E+09 |
December | 0.262824E+09 | 0.199060E+09 | 63763438.80 | 0.246276E+09 | 0.309717E+09 |
Annual Sum or Average | 0.324136E+10 | 0.167472E+10 | 0.156664E+10 | 0.291829E+10 | 0.195301E+10 |
Minimum of Months | 0.209524E+09 | 42632042.87 | 63763438.80 | 0.176358E+09 | 55931672.23 |
Maximum of Months | 0.326917E+09 | 0.219248E+09 | 0.171469E+09 | 0.328388E+09 | 0.333012E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_DOOR_1
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.383660E+09 | 0.262521E+09 | 0.121139E+09 | 0.327230E+09 | 0.394909E+09 |
February | 0.371476E+09 | 0.251003E+09 | 0.120474E+09 | 0.317559E+09 | 0.288486E+09 |
March | 0.357964E+09 | 0.188563E+09 | 0.169401E+09 | 0.300701E+09 | 0.227784E+09 |
April | 0.311947E+09 | 0.145831E+09 | 0.166116E+09 | 0.252975E+09 | 0.161644E+09 |
May | 0.267027E+09 | 72363890.67 | 0.194663E+09 | 0.211347E+09 | 0.103633E+09 |
June | 0.250877E+09 | 51046261.85 | 0.199831E+09 | 0.221187E+09 | 71970423.47 |
July | 0.274420E+09 | 69108750.79 | 0.205311E+09 | 0.249696E+09 | 66648826.72 |
August | 0.309194E+09 | 0.110857E+09 | 0.198337E+09 | 0.304397E+09 | 79726976.75 |
September | 0.362712E+09 | 0.191152E+09 | 0.171559E+09 | 0.368588E+09 | 0.124968E+09 |
October | 0.391441E+09 | 0.245628E+09 | 0.145813E+09 | 0.393410E+09 | 0.179850E+09 |
November | 0.285689E+09 | 0.178839E+09 | 0.106850E+09 | 0.254981E+09 | 0.251545E+09 |
December | 0.314697E+09 | 0.238348E+09 | 76348328.03 | 0.295314E+09 | 0.367405E+09 |
Annual Sum or Average | 0.388110E+10 | 0.200526E+10 | 0.187584E+10 | 0.349739E+10 | 0.231857E+10 |
Minimum of Months | 0.250877E+09 | 51046261.85 | 76348328.03 | 0.211347E+09 | 66648826.72 |
Maximum of Months | 0.391441E+09 | 0.262521E+09 | 0.205311E+09 | 0.393410E+09 | 0.394909E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_DOOR_2
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.383660E+09 | 0.262521E+09 | 0.121139E+09 | 0.327230E+09 | 0.394909E+09 |
February | 0.371476E+09 | 0.251003E+09 | 0.120474E+09 | 0.317559E+09 | 0.288486E+09 |
March | 0.357964E+09 | 0.188563E+09 | 0.169401E+09 | 0.300701E+09 | 0.227784E+09 |
April | 0.311947E+09 | 0.145831E+09 | 0.166116E+09 | 0.252975E+09 | 0.161644E+09 |
May | 0.267027E+09 | 72363890.67 | 0.194663E+09 | 0.211347E+09 | 0.103633E+09 |
June | 0.250877E+09 | 51046261.85 | 0.199831E+09 | 0.221187E+09 | 71970423.47 |
July | 0.274420E+09 | 69108750.79 | 0.205311E+09 | 0.249696E+09 | 66648826.72 |
August | 0.309194E+09 | 0.110857E+09 | 0.198337E+09 | 0.304397E+09 | 79726976.75 |
September | 0.362712E+09 | 0.191152E+09 | 0.171559E+09 | 0.368588E+09 | 0.124968E+09 |
October | 0.391441E+09 | 0.245628E+09 | 0.145813E+09 | 0.393410E+09 | 0.179850E+09 |
November | 0.285689E+09 | 0.178839E+09 | 0.106850E+09 | 0.254981E+09 | 0.251545E+09 |
December | 0.314697E+09 | 0.238348E+09 | 76348328.03 | 0.295314E+09 | 0.367405E+09 |
Annual Sum or Average | 0.388110E+10 | 0.200526E+10 | 0.187584E+10 | 0.349739E+10 | 0.231857E+10 |
Minimum of Months | 0.250877E+09 | 51046261.85 | 76348328.03 | 0.211347E+09 | 66648826.72 |
Maximum of Months | 0.391441E+09 | 0.262521E+09 | 0.205311E+09 | 0.393410E+09 | 0.394909E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.320420E+09 | 0.219248E+09 | 0.101171E+09 | 0.271522E+09 | 0.335320E+09 |
February | 0.310244E+09 | 0.209629E+09 | 0.100615E+09 | 0.263690E+09 | 0.244739E+09 |
March | 0.298959E+09 | 0.157481E+09 | 0.141478E+09 | 0.249874E+09 | 0.192987E+09 |
April | 0.260528E+09 | 0.121793E+09 | 0.138735E+09 | 0.210886E+09 | 0.136400E+09 |
May | 0.223012E+09 | 60435776.82 | 0.162576E+09 | 0.176887E+09 | 86403860.17 |
June | 0.209524E+09 | 42632042.87 | 0.166892E+09 | 0.185296E+09 | 59878870.80 |
July | 0.229186E+09 | 57717198.46 | 0.171469E+09 | 0.209134E+09 | 55331226.66 |
August | 0.258228E+09 | 92583616.90 | 0.165644E+09 | 0.254658E+09 | 66416083.32 |
September | 0.302924E+09 | 0.159644E+09 | 0.143280E+09 | 0.307989E+09 | 0.104578E+09 |
October | 0.326917E+09 | 0.205140E+09 | 0.121778E+09 | 0.327946E+09 | 0.151308E+09 |
November | 0.238598E+09 | 0.149360E+09 | 89237204.53 | 0.212003E+09 | 0.213069E+09 |
December | 0.262824E+09 | 0.199060E+09 | 63763438.80 | 0.245564E+09 | 0.311746E+09 |
Annual Sum or Average | 0.324136E+10 | 0.167472E+10 | 0.156664E+10 | 0.291545E+10 | 0.195818E+10 |
Minimum of Months | 0.209524E+09 | 42632042.87 | 63763438.80 | 0.176887E+09 | 55331226.66 |
Maximum of Months | 0.326917E+09 | 0.219248E+09 | 0.171469E+09 | 0.327946E+09 | 0.335320E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.320420E+09 | 0.219248E+09 | 0.101171E+09 | 0.271522E+09 | 0.335320E+09 |
February | 0.310244E+09 | 0.209629E+09 | 0.100615E+09 | 0.263690E+09 | 0.244739E+09 |
March | 0.298959E+09 | 0.157481E+09 | 0.141478E+09 | 0.249874E+09 | 0.192987E+09 |
April | 0.260528E+09 | 0.121793E+09 | 0.138735E+09 | 0.210886E+09 | 0.136400E+09 |
May | 0.223012E+09 | 60435776.82 | 0.162576E+09 | 0.176887E+09 | 86403860.17 |
June | 0.209524E+09 | 42632042.87 | 0.166892E+09 | 0.185296E+09 | 59878870.80 |
July | 0.229186E+09 | 57717198.46 | 0.171469E+09 | 0.209134E+09 | 55331226.66 |
August | 0.258228E+09 | 92583616.90 | 0.165644E+09 | 0.254658E+09 | 66416083.32 |
September | 0.302924E+09 | 0.159644E+09 | 0.143280E+09 | 0.307989E+09 | 0.104578E+09 |
October | 0.326917E+09 | 0.205140E+09 | 0.121778E+09 | 0.327946E+09 | 0.151308E+09 |
November | 0.238598E+09 | 0.149360E+09 | 89237204.53 | 0.212003E+09 | 0.213069E+09 |
December | 0.262824E+09 | 0.199060E+09 | 63763438.80 | 0.245564E+09 | 0.311746E+09 |
Annual Sum or Average | 0.324136E+10 | 0.167472E+10 | 0.156664E+10 | 0.291545E+10 | 0.195818E+10 |
Minimum of Months | 0.209524E+09 | 42632042.87 | 63763438.80 | 0.176887E+09 | 55331226.66 |
Maximum of Months | 0.326917E+09 | 0.219248E+09 | 0.171469E+09 | 0.327946E+09 | 0.335320E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_DOOR
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.383660E+09 | 0.262521E+09 | 0.121139E+09 | 0.326008E+09 | 0.397560E+09 |
February | 0.371476E+09 | 0.251003E+09 | 0.120474E+09 | 0.316512E+09 | 0.290203E+09 |
March | 0.357964E+09 | 0.188563E+09 | 0.169401E+09 | 0.299865E+09 | 0.228878E+09 |
April | 0.311947E+09 | 0.145831E+09 | 0.166116E+09 | 0.252815E+09 | 0.161880E+09 |
May | 0.267027E+09 | 72363890.67 | 0.194663E+09 | 0.211994E+09 | 0.102733E+09 |
June | 0.250877E+09 | 51046261.85 | 0.199831E+09 | 0.221740E+09 | 71275304.75 |
July | 0.274420E+09 | 69108750.79 | 0.205311E+09 | 0.250232E+09 | 65931320.86 |
August | 0.309194E+09 | 0.110857E+09 | 0.198337E+09 | 0.304725E+09 | 79072612.27 |
September | 0.362712E+09 | 0.191152E+09 | 0.171559E+09 | 0.368660E+09 | 0.124431E+09 |
October | 0.391441E+09 | 0.245628E+09 | 0.145813E+09 | 0.392920E+09 | 0.179800E+09 |
November | 0.285689E+09 | 0.178839E+09 | 0.106850E+09 | 0.254324E+09 | 0.252714E+09 |
December | 0.314697E+09 | 0.238348E+09 | 76348328.03 | 0.294499E+09 | 0.369734E+09 |
Annual Sum or Average | 0.388110E+10 | 0.200526E+10 | 0.187584E+10 | 0.349430E+10 | 0.232421E+10 |
Minimum of Months | 0.250877E+09 | 51046261.85 | 76348328.03 | 0.211994E+09 | 65931320.86 |
Maximum of Months | 0.391441E+09 | 0.262521E+09 | 0.205311E+09 | 0.392920E+09 | 0.397560E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.320420E+09 | 0.219248E+09 | 0.101171E+09 | 0.271603E+09 | 0.334905E+09 |
February | 0.310244E+09 | 0.209629E+09 | 0.100615E+09 | 0.263802E+09 | 0.244254E+09 |
March | 0.298959E+09 | 0.157481E+09 | 0.141478E+09 | 0.250118E+09 | 0.192253E+09 |
April | 0.260528E+09 | 0.121793E+09 | 0.138735E+09 | 0.211239E+09 | 0.135466E+09 |
May | 0.223012E+09 | 60435776.82 | 0.162576E+09 | 0.177938E+09 | 85021403.64 |
June | 0.209524E+09 | 42632042.87 | 0.166892E+09 | 0.185725E+09 | 59309489.23 |
July | 0.229186E+09 | 57717198.46 | 0.171469E+09 | 0.209406E+09 | 54991813.14 |
August | 0.258228E+09 | 92583616.90 | 0.165644E+09 | 0.254879E+09 | 66081822.69 |
September | 0.302924E+09 | 0.159644E+09 | 0.143280E+09 | 0.308281E+09 | 0.104000E+09 |
October | 0.326917E+09 | 0.205140E+09 | 0.121778E+09 | 0.328260E+09 | 0.150583E+09 |
November | 0.238598E+09 | 0.149360E+09 | 89237204.53 | 0.212206E+09 | 0.212400E+09 |
December | 0.262824E+09 | 0.199060E+09 | 63763438.80 | 0.245662E+09 | 0.311228E+09 |
Annual Sum or Average | 0.324136E+10 | 0.167472E+10 | 0.156664E+10 | 0.291912E+10 | 0.195049E+10 |
Minimum of Months | 0.209524E+09 | 42632042.87 | 63763438.80 | 0.177938E+09 | 54991813.14 |
Maximum of Months | 0.326917E+09 | 0.219248E+09 | 0.171469E+09 | 0.328260E+09 | 0.334905E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.320420E+09 | 0.219248E+09 | 0.101171E+09 | 0.271603E+09 | 0.334905E+09 |
February | 0.310244E+09 | 0.209629E+09 | 0.100615E+09 | 0.263802E+09 | 0.244254E+09 |
March | 0.298959E+09 | 0.157481E+09 | 0.141478E+09 | 0.250118E+09 | 0.192253E+09 |
April | 0.260528E+09 | 0.121793E+09 | 0.138735E+09 | 0.211239E+09 | 0.135466E+09 |
May | 0.223012E+09 | 60435776.82 | 0.162576E+09 | 0.177938E+09 | 85021403.64 |
June | 0.209524E+09 | 42632042.87 | 0.166892E+09 | 0.185725E+09 | 59309489.23 |
July | 0.229186E+09 | 57717198.46 | 0.171469E+09 | 0.209406E+09 | 54991813.14 |
August | 0.258228E+09 | 92583616.90 | 0.165644E+09 | 0.254879E+09 | 66081822.69 |
September | 0.302924E+09 | 0.159644E+09 | 0.143280E+09 | 0.308281E+09 | 0.104000E+09 |
October | 0.326917E+09 | 0.205140E+09 | 0.121778E+09 | 0.328260E+09 | 0.150583E+09 |
November | 0.238598E+09 | 0.149360E+09 | 89237204.53 | 0.212206E+09 | 0.212400E+09 |
December | 0.262824E+09 | 0.199060E+09 | 63763438.80 | 0.245662E+09 | 0.311228E+09 |
Annual Sum or Average | 0.324136E+10 | 0.167472E+10 | 0.156664E+10 | 0.291912E+10 | 0.195049E+10 |
Minimum of Months | 0.209524E+09 | 42632042.87 | 63763438.80 | 0.177938E+09 | 54991813.14 |
Maximum of Months | 0.326917E+09 | 0.219248E+09 | 0.171469E+09 | 0.328260E+09 | 0.334905E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_DOOR
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.383660E+09 | 0.262521E+09 | 0.121139E+09 | 0.326107E+09 | 0.397063E+09 |
February | 0.371476E+09 | 0.251003E+09 | 0.120474E+09 | 0.316648E+09 | 0.289624E+09 |
March | 0.357964E+09 | 0.188563E+09 | 0.169401E+09 | 0.300161E+09 | 0.228004E+09 |
April | 0.311947E+09 | 0.145831E+09 | 0.166116E+09 | 0.253241E+09 | 0.160767E+09 |
May | 0.267027E+09 | 72363890.67 | 0.194663E+09 | 0.213252E+09 | 0.101091E+09 |
June | 0.250877E+09 | 51046261.85 | 0.199831E+09 | 0.222255E+09 | 70597950.82 |
July | 0.274420E+09 | 69108750.79 | 0.205311E+09 | 0.250560E+09 | 65528319.59 |
August | 0.309194E+09 | 0.110857E+09 | 0.198337E+09 | 0.304991E+09 | 78675336.10 |
September | 0.362712E+09 | 0.191152E+09 | 0.171559E+09 | 0.369012E+09 | 0.123745E+09 |
October | 0.391441E+09 | 0.245628E+09 | 0.145813E+09 | 0.393298E+09 | 0.178938E+09 |
November | 0.285689E+09 | 0.178839E+09 | 0.106850E+09 | 0.254571E+09 | 0.251916E+09 |
December | 0.314697E+09 | 0.238348E+09 | 76348328.03 | 0.294618E+09 | 0.369114E+09 |
Annual Sum or Average | 0.388110E+10 | 0.200526E+10 | 0.187584E+10 | 0.349871E+10 | 0.231506E+10 |
Minimum of Months | 0.250877E+09 | 51046261.85 | 76348328.03 | 0.213252E+09 | 65528319.59 |
Maximum of Months | 0.391441E+09 | 0.262521E+09 | 0.205311E+09 | 0.393298E+09 | 0.397063E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.320420E+09 | 0.219248E+09 | 0.101171E+09 | 0.271979E+09 | 0.332489E+09 |
February | 0.310244E+09 | 0.209629E+09 | 0.100615E+09 | 0.264266E+09 | 0.241873E+09 |
March | 0.298959E+09 | 0.157481E+09 | 0.141478E+09 | 0.250929E+09 | 0.189216E+09 |
April | 0.260528E+09 | 0.121793E+09 | 0.138735E+09 | 0.212266E+09 | 0.132242E+09 |
May | 0.223012E+09 | 60435776.82 | 0.162576E+09 | 0.180291E+09 | 81727223.43 |
June | 0.209524E+09 | 42632042.87 | 0.166892E+09 | 0.186732E+09 | 57824014.48 |
July | 0.229186E+09 | 57717198.46 | 0.171469E+09 | 0.210005E+09 | 54119018.20 |
August | 0.258228E+09 | 92583616.90 | 0.165644E+09 | 0.255327E+09 | 65257912.94 |
September | 0.302924E+09 | 0.159644E+09 | 0.143280E+09 | 0.308934E+09 | 0.102558E+09 |
October | 0.326917E+09 | 0.205140E+09 | 0.121778E+09 | 0.329070E+09 | 0.148453E+09 |
November | 0.238598E+09 | 0.149360E+09 | 89237204.53 | 0.212804E+09 | 0.209978E+09 |
December | 0.262824E+09 | 0.199060E+09 | 63763438.80 | 0.246063E+09 | 0.308597E+09 |
Annual Sum or Average | 0.324136E+10 | 0.167472E+10 | 0.156664E+10 | 0.292866E+10 | 0.192433E+10 |
Minimum of Months | 0.209524E+09 | 42632042.87 | 63763438.80 | 0.180291E+09 | 54119018.20 |
Maximum of Months | 0.326917E+09 | 0.219248E+09 | 0.171469E+09 | 0.329070E+09 | 0.332489E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.320420E+09 | 0.219248E+09 | 0.101171E+09 | 0.271979E+09 | 0.332489E+09 |
February | 0.310244E+09 | 0.209629E+09 | 0.100615E+09 | 0.264266E+09 | 0.241873E+09 |
March | 0.298959E+09 | 0.157481E+09 | 0.141478E+09 | 0.250929E+09 | 0.189216E+09 |
April | 0.260528E+09 | 0.121793E+09 | 0.138735E+09 | 0.212266E+09 | 0.132242E+09 |
May | 0.223012E+09 | 60435776.82 | 0.162576E+09 | 0.180291E+09 | 81727223.43 |
June | 0.209524E+09 | 42632042.87 | 0.166892E+09 | 0.186732E+09 | 57824014.48 |
July | 0.229186E+09 | 57717198.46 | 0.171469E+09 | 0.210005E+09 | 54119018.20 |
August | 0.258228E+09 | 92583616.90 | 0.165644E+09 | 0.255327E+09 | 65257912.94 |
September | 0.302924E+09 | 0.159644E+09 | 0.143280E+09 | 0.308934E+09 | 0.102558E+09 |
October | 0.326917E+09 | 0.205140E+09 | 0.121778E+09 | 0.329070E+09 | 0.148453E+09 |
November | 0.238598E+09 | 0.149360E+09 | 89237204.53 | 0.212804E+09 | 0.209978E+09 |
December | 0.262824E+09 | 0.199060E+09 | 63763438.80 | 0.246063E+09 | 0.308597E+09 |
Annual Sum or Average | 0.324136E+10 | 0.167472E+10 | 0.156664E+10 | 0.292866E+10 | 0.192433E+10 |
Minimum of Months | 0.209524E+09 | 42632042.87 | 63763438.80 | 0.180291E+09 | 54119018.20 |
Maximum of Months | 0.326917E+09 | 0.219248E+09 | 0.171469E+09 | 0.329070E+09 | 0.332489E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_DOOR
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.383660E+09 | 0.262521E+09 | 0.121139E+09 | 0.326565E+09 | 0.394180E+09 |
February | 0.371476E+09 | 0.251003E+09 | 0.120474E+09 | 0.317215E+09 | 0.286784E+09 |
March | 0.357964E+09 | 0.188563E+09 | 0.169401E+09 | 0.301147E+09 | 0.224393E+09 |
April | 0.311947E+09 | 0.145831E+09 | 0.166116E+09 | 0.254482E+09 | 0.156933E+09 |
May | 0.267027E+09 | 72363890.67 | 0.194663E+09 | 0.216065E+09 | 97184239.92 |
June | 0.250877E+09 | 51046261.85 | 0.199831E+09 | 0.223464E+09 | 68839261.21 |
July | 0.274420E+09 | 69108750.79 | 0.205311E+09 | 0.251279E+09 | 64495402.73 |
August | 0.309194E+09 | 0.110857E+09 | 0.198337E+09 | 0.305530E+09 | 77701077.99 |
September | 0.362712E+09 | 0.191152E+09 | 0.171559E+09 | 0.369796E+09 | 0.122038E+09 |
October | 0.391441E+09 | 0.245628E+09 | 0.145813E+09 | 0.394272E+09 | 0.176408E+09 |
November | 0.285689E+09 | 0.178839E+09 | 0.106850E+09 | 0.255295E+09 | 0.249037E+09 |
December | 0.314697E+09 | 0.238348E+09 | 76348328.03 | 0.295105E+09 | 0.365972E+09 |
Annual Sum or Average | 0.388110E+10 | 0.200526E+10 | 0.187584E+10 | 0.351022E+10 | 0.228397E+10 |
Minimum of Months | 0.250877E+09 | 51046261.85 | 76348328.03 | 0.216065E+09 | 64495402.73 |
Maximum of Months | 0.391441E+09 | 0.262521E+09 | 0.205311E+09 | 0.394272E+09 | 0.394180E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.320420E+09 | 0.219248E+09 | 0.101171E+09 | 0.273826E+09 | 0.321657E+09 |
February | 0.310244E+09 | 0.209629E+09 | 0.100615E+09 | 0.266331E+09 | 0.231186E+09 |
March | 0.298959E+09 | 0.157481E+09 | 0.141478E+09 | 0.253800E+09 | 0.176754E+09 |
April | 0.260528E+09 | 0.121793E+09 | 0.138735E+09 | 0.215409E+09 | 0.120376E+09 |
May | 0.223012E+09 | 60435776.82 | 0.162576E+09 | 0.185568E+09 | 72805237.68 |
June | 0.209524E+09 | 42632042.87 | 0.166892E+09 | 0.189435E+09 | 52840880.36 |
July | 0.229186E+09 | 57717198.46 | 0.171469E+09 | 0.211617E+09 | 50853499.01 |
August | 0.258228E+09 | 92583616.90 | 0.165644E+09 | 0.256397E+09 | 62136009.68 |
September | 0.302924E+09 | 0.159644E+09 | 0.143280E+09 | 0.310353E+09 | 97878277.90 |
October | 0.326917E+09 | 0.205140E+09 | 0.121778E+09 | 0.331217E+09 | 0.141101E+09 |
November | 0.238598E+09 | 0.149360E+09 | 89237204.53 | 0.214704E+09 | 0.200721E+09 |
December | 0.262824E+09 | 0.199060E+09 | 63763438.80 | 0.247662E+09 | 0.296731E+09 |
Annual Sum or Average | 0.324136E+10 | 0.167472E+10 | 0.156664E+10 | 0.295632E+10 | 0.182504E+10 |
Minimum of Months | 0.209524E+09 | 42632042.87 | 63763438.80 | 0.185568E+09 | 50853499.01 |
Maximum of Months | 0.326917E+09 | 0.219248E+09 | 0.171469E+09 | 0.331217E+09 | 0.321657E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.320420E+09 | 0.219248E+09 | 0.101171E+09 | 0.273826E+09 | 0.321657E+09 |
February | 0.310244E+09 | 0.209629E+09 | 0.100615E+09 | 0.266331E+09 | 0.231186E+09 |
March | 0.298959E+09 | 0.157481E+09 | 0.141478E+09 | 0.253800E+09 | 0.176754E+09 |
April | 0.260528E+09 | 0.121793E+09 | 0.138735E+09 | 0.215409E+09 | 0.120376E+09 |
May | 0.223012E+09 | 60435776.82 | 0.162576E+09 | 0.185568E+09 | 72805237.68 |
June | 0.209524E+09 | 42632042.87 | 0.166892E+09 | 0.189435E+09 | 52840880.36 |
July | 0.229186E+09 | 57717198.46 | 0.171469E+09 | 0.211617E+09 | 50853499.01 |
August | 0.258228E+09 | 92583616.90 | 0.165644E+09 | 0.256397E+09 | 62136009.68 |
September | 0.302924E+09 | 0.159644E+09 | 0.143280E+09 | 0.310353E+09 | 97878277.90 |
October | 0.326917E+09 | 0.205140E+09 | 0.121778E+09 | 0.331217E+09 | 0.141101E+09 |
November | 0.238598E+09 | 0.149360E+09 | 89237204.53 | 0.214704E+09 | 0.200721E+09 |
December | 0.262824E+09 | 0.199060E+09 | 63763438.80 | 0.247662E+09 | 0.296731E+09 |
Annual Sum or Average | 0.324136E+10 | 0.167472E+10 | 0.156664E+10 | 0.295632E+10 | 0.182504E+10 |
Minimum of Months | 0.209524E+09 | 42632042.87 | 63763438.80 | 0.185568E+09 | 50853499.01 |
Maximum of Months | 0.326917E+09 | 0.219248E+09 | 0.171469E+09 | 0.331217E+09 | 0.321657E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_DOOR
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.383660E+09 | 0.262521E+09 | 0.121139E+09 | 0.328820E+09 | 0.381220E+09 |
February | 0.371476E+09 | 0.251003E+09 | 0.120474E+09 | 0.319740E+09 | 0.274045E+09 |
March | 0.357964E+09 | 0.188563E+09 | 0.169401E+09 | 0.304647E+09 | 0.209581E+09 |
April | 0.311947E+09 | 0.145831E+09 | 0.166116E+09 | 0.258294E+09 | 0.142840E+09 |
May | 0.267027E+09 | 72363890.67 | 0.194663E+09 | 0.222390E+09 | 86608653.71 |
June | 0.250877E+09 | 51046261.85 | 0.199831E+09 | 0.226708E+09 | 62935872.99 |
July | 0.274420E+09 | 69108750.79 | 0.205311E+09 | 0.253211E+09 | 60628013.10 |
August | 0.309194E+09 | 0.110857E+09 | 0.198337E+09 | 0.306812E+09 | 74010524.63 |
September | 0.362712E+09 | 0.191152E+09 | 0.171559E+09 | 0.371498E+09 | 0.116501E+09 |
October | 0.391441E+09 | 0.245628E+09 | 0.145813E+09 | 0.396866E+09 | 0.167705E+09 |
November | 0.285689E+09 | 0.178839E+09 | 0.106850E+09 | 0.257602E+09 | 0.238040E+09 |
December | 0.314697E+09 | 0.238348E+09 | 76348328.03 | 0.297050E+09 | 0.351826E+09 |
Annual Sum or Average | 0.388110E+10 | 0.200526E+10 | 0.187584E+10 | 0.354364E+10 | 0.216594E+10 |
Minimum of Months | 0.250877E+09 | 51046261.85 | 76348328.03 | 0.222390E+09 | 60628013.10 |
Maximum of Months | 0.391441E+09 | 0.262521E+09 | 0.205311E+09 | 0.396866E+09 | 0.381220E+09 |
Report: WindowZoneSummaryMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 651.42 | 814.73 | 766.58 | 524.54 | 242.05 | 0.00 | 0.00 |
February | 700.06 | 658.26 | 821.76 | 555.26 | 266.51 | 0.00 | 0.00 |
March | 599.25 | 467.60 | 715.24 | 376.76 | 338.48 | 0.00 | 0.00 |
April | 521.63 | 340.26 | 644.07 | 301.09 | 342.98 | 0.00 | 0.00 |
May | 419.99 | 211.55 | 533.54 | 144.59 | 388.95 | 0.00 | 0.00 |
June | 458.98 | 146.35 | 517.98 | 105.39 | 412.59 | 0.00 | 0.00 |
July | 502.37 | 128.07 | 548.31 | 138.08 | 410.23 | 0.00 | 0.00 |
August | 609.92 | 155.31 | 617.79 | 221.50 | 396.29 | 0.00 | 0.00 |
September | 761.48 | 256.85 | 748.88 | 394.67 | 354.21 | 0.00 | 0.00 |
October | 782.09 | 370.03 | 782.13 | 490.78 | 291.35 | 0.00 | 0.00 |
November | 523.05 | 537.53 | 589.86 | 369.25 | 220.61 | 0.00 | 0.00 |
December | 587.93 | 755.67 | 628.79 | 476.24 | 152.55 | 0.00 | 0.00 |
Annual Sum or Average | 592.60 | 402.34 | 658.62 | 340.29 | 318.33 | 0.00 | 0.00 |
Minimum of Months | 419.99 | 128.07 | 517.98 | 105.39 | 152.55 | 0.00 | 0.00 |
Maximum of Months | 782.09 | 814.73 | 821.76 | 555.26 | 412.59 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 322.48 | 419.63 | 383.29 | 262.27 | 121.02 | 0.00 | 0.00 |
February | 346.41 | 341.69 | 410.88 | 277.63 | 133.25 | 0.00 | 0.00 |
March | 295.62 | 246.63 | 357.62 | 188.38 | 169.24 | 0.00 | 0.00 |
April | 257.31 | 182.38 | 322.04 | 150.55 | 171.49 | 0.00 | 0.00 |
May | 205.32 | 113.04 | 266.77 | 72.29 | 194.48 | 0.00 | 0.00 |
June | 227.37 | 76.50 | 258.99 | 52.70 | 206.29 | 0.00 | 0.00 |
July | 250.49 | 64.78 | 274.16 | 69.04 | 205.11 | 0.00 | 0.00 |
August | 304.40 | 78.54 | 308.90 | 110.75 | 198.15 | 0.00 | 0.00 |
September | 379.12 | 132.39 | 374.44 | 197.33 | 177.11 | 0.00 | 0.00 |
October | 387.39 | 195.68 | 391.06 | 245.39 | 145.67 | 0.00 | 0.00 |
November | 258.29 | 280.93 | 294.93 | 184.62 | 110.31 | 0.00 | 0.00 |
December | 291.52 | 390.64 | 314.39 | 238.12 | 76.27 | 0.00 | 0.00 |
Annual Sum or Average | 293.52 | 209.62 | 329.31 | 170.15 | 159.16 | 0.00 | 0.00 |
Minimum of Months | 205.32 | 64.78 | 258.99 | 52.70 | 76.27 | 0.00 | 0.00 |
Maximum of Months | 387.39 | 419.63 | 410.88 | 277.63 | 206.29 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 322.04 | 409.95 | 382.50 | 261.73 | 120.77 | 0.00 | 0.00 |
February | 346.05 | 332.87 | 410.04 | 277.06 | 132.98 | 0.00 | 0.00 |
March | 295.61 | 239.80 | 356.89 | 187.99 | 168.89 | 0.00 | 0.00 |
April | 257.33 | 177.19 | 321.37 | 150.24 | 171.14 | 0.00 | 0.00 |
May | 205.70 | 112.13 | 266.22 | 72.15 | 194.08 | 0.00 | 0.00 |
June | 226.41 | 78.83 | 258.46 | 52.59 | 205.87 | 0.00 | 0.00 |
July | 248.82 | 69.23 | 273.59 | 68.90 | 204.69 | 0.00 | 0.00 |
August | 303.39 | 82.72 | 308.26 | 110.52 | 197.74 | 0.00 | 0.00 |
September | 378.46 | 134.08 | 373.67 | 196.93 | 176.74 | 0.00 | 0.00 |
October | 388.33 | 189.12 | 390.26 | 244.89 | 145.37 | 0.00 | 0.00 |
November | 258.78 | 272.93 | 294.32 | 184.24 | 110.08 | 0.00 | 0.00 |
December | 291.33 | 381.91 | 313.75 | 237.63 | 76.12 | 0.00 | 0.00 |
Annual Sum or Average | 293.23 | 206.14 | 328.63 | 169.80 | 158.84 | 0.00 | 0.00 |
Minimum of Months | 205.70 | 69.23 | 258.46 | 52.59 | 76.12 | 0.00 | 0.00 |
Maximum of Months | 388.33 | 409.95 | 410.04 | 277.06 | 205.87 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 322.42 | 406.69 | 382.50 | 261.73 | 120.77 | 0.00 | 0.00 |
February | 346.51 | 329.75 | 410.04 | 277.06 | 132.98 | 0.00 | 0.00 |
March | 296.16 | 237.01 | 356.89 | 187.99 | 168.89 | 0.00 | 0.00 |
April | 257.91 | 174.69 | 321.37 | 150.24 | 171.14 | 0.00 | 0.00 |
May | 206.69 | 110.28 | 266.22 | 72.15 | 194.08 | 0.00 | 0.00 |
June | 226.75 | 78.22 | 258.46 | 52.59 | 205.87 | 0.00 | 0.00 |
July | 248.81 | 69.29 | 273.59 | 68.90 | 204.69 | 0.00 | 0.00 |
August | 303.42 | 82.68 | 308.26 | 110.52 | 197.74 | 0.00 | 0.00 |
September | 378.74 | 133.25 | 373.67 | 196.93 | 176.74 | 0.00 | 0.00 |
October | 389.29 | 186.14 | 390.26 | 244.89 | 145.37 | 0.00 | 0.00 |
November | 259.48 | 269.60 | 294.32 | 184.24 | 110.08 | 0.00 | 0.00 |
December | 291.68 | 378.73 | 313.75 | 237.63 | 76.12 | 0.00 | 0.00 |
Annual Sum or Average | 293.70 | 204.11 | 328.63 | 169.80 | 158.84 | 0.00 | 0.00 |
Minimum of Months | 206.69 | 69.29 | 258.46 | 52.59 | 76.12 | 0.00 | 0.00 |
Maximum of Months | 389.29 | 406.69 | 410.04 | 277.06 | 205.87 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 322.86 | 404.41 | 382.50 | 261.73 | 120.77 | 0.00 | 0.00 |
February | 347.03 | 327.51 | 410.04 | 277.06 | 132.98 | 0.00 | 0.00 |
March | 296.80 | 234.82 | 356.89 | 187.99 | 168.89 | 0.00 | 0.00 |
April | 258.60 | 172.59 | 321.37 | 150.24 | 171.14 | 0.00 | 0.00 |
May | 208.14 | 108.10 | 266.22 | 72.15 | 194.08 | 0.00 | 0.00 |
June | 227.41 | 77.07 | 258.46 | 52.59 | 205.87 | 0.00 | 0.00 |
July | 249.15 | 68.60 | 273.59 | 68.90 | 204.69 | 0.00 | 0.00 |
August | 303.72 | 81.95 | 308.26 | 110.52 | 197.74 | 0.00 | 0.00 |
September | 379.24 | 132.00 | 373.67 | 196.93 | 176.74 | 0.00 | 0.00 |
October | 390.10 | 184.07 | 390.26 | 244.89 | 145.37 | 0.00 | 0.00 |
November | 260.15 | 267.10 | 294.32 | 184.24 | 110.08 | 0.00 | 0.00 |
December | 292.07 | 376.40 | 313.75 | 237.63 | 76.12 | 0.00 | 0.00 |
Annual Sum or Average | 294.32 | 202.31 | 328.63 | 169.80 | 158.84 | 0.00 | 0.00 |
Minimum of Months | 208.14 | 68.60 | 258.46 | 52.59 | 76.12 | 0.00 | 0.00 |
Maximum of Months | 390.10 | 404.41 | 410.04 | 277.06 | 205.87 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 651.43 | 792.21 | 765.01 | 523.46 | 241.55 | 0.00 | 0.00 |
February | 700.03 | 640.67 | 820.08 | 554.12 | 265.96 | 0.00 | 0.00 |
March | 598.80 | 456.85 | 713.77 | 375.99 | 337.78 | 0.00 | 0.00 |
April | 520.87 | 334.86 | 642.75 | 300.48 | 342.27 | 0.00 | 0.00 |
May | 421.19 | 207.53 | 532.45 | 144.29 | 388.15 | 0.00 | 0.00 |
June | 455.91 | 148.83 | 516.92 | 105.18 | 411.74 | 0.00 | 0.00 |
July | 498.11 | 133.30 | 547.19 | 137.80 | 409.38 | 0.00 | 0.00 |
August | 607.22 | 159.53 | 616.52 | 221.05 | 395.48 | 0.00 | 0.00 |
September | 759.63 | 258.49 | 747.35 | 393.86 | 353.49 | 0.00 | 0.00 |
October | 784.19 | 360.28 | 780.52 | 489.77 | 290.75 | 0.00 | 0.00 |
November | 524.80 | 521.30 | 588.65 | 368.49 | 220.16 | 0.00 | 0.00 |
December | 588.31 | 736.89 | 627.50 | 475.26 | 152.24 | 0.00 | 0.00 |
Annual Sum or Average | 591.96 | 394.76 | 657.27 | 339.59 | 317.68 | 0.00 | 0.00 |
Minimum of Months | 421.19 | 133.30 | 516.92 | 105.18 | 152.24 | 0.00 | 0.00 |
Maximum of Months | 784.19 | 792.21 | 820.08 | 554.12 | 411.74 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 324.47 | 398.82 | 382.50 | 261.73 | 120.77 | 0.00 | 0.00 |
February | 348.83 | 322.29 | 410.04 | 277.06 | 132.98 | 0.00 | 0.00 |
March | 298.54 | 229.56 | 356.89 | 187.99 | 168.89 | 0.00 | 0.00 |
April | 260.26 | 167.70 | 321.37 | 150.24 | 171.14 | 0.00 | 0.00 |
May | 211.23 | 102.87 | 266.22 | 72.15 | 194.08 | 0.00 | 0.00 |
June | 228.52 | 73.70 | 258.46 | 52.59 | 205.87 | 0.00 | 0.00 |
July | 249.59 | 65.93 | 273.59 | 68.90 | 204.69 | 0.00 | 0.00 |
August | 303.93 | 79.12 | 308.26 | 110.52 | 197.74 | 0.00 | 0.00 |
September | 379.88 | 128.70 | 373.67 | 196.93 | 176.74 | 0.00 | 0.00 |
October | 391.58 | 180.11 | 390.26 | 244.89 | 145.37 | 0.00 | 0.00 |
November | 261.70 | 261.90 | 294.32 | 184.24 | 110.08 | 0.00 | 0.00 |
December | 293.32 | 370.83 | 313.75 | 237.63 | 76.12 | 0.00 | 0.00 |
Annual Sum or Average | 295.70 | 197.89 | 328.63 | 169.80 | 158.84 | 0.00 | 0.00 |
Minimum of Months | 211.23 | 65.93 | 258.46 | 52.59 | 76.12 | 0.00 | 0.00 |
Maximum of Months | 391.58 | 398.82 | 410.04 | 277.06 | 205.87 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 324.56 | 398.32 | 382.50 | 261.73 | 120.77 | 0.00 | 0.00 |
February | 348.98 | 321.65 | 410.04 | 277.06 | 132.98 | 0.00 | 0.00 |
March | 298.83 | 228.68 | 356.89 | 187.99 | 168.89 | 0.00 | 0.00 |
April | 260.69 | 166.55 | 321.37 | 150.24 | 171.14 | 0.00 | 0.00 |
May | 212.49 | 101.23 | 266.22 | 72.15 | 194.08 | 0.00 | 0.00 |
June | 229.05 | 73.00 | 258.46 | 52.59 | 205.87 | 0.00 | 0.00 |
July | 249.91 | 65.53 | 273.59 | 68.90 | 204.69 | 0.00 | 0.00 |
August | 304.19 | 78.72 | 308.26 | 110.52 | 197.74 | 0.00 | 0.00 |
September | 380.24 | 127.99 | 373.67 | 196.93 | 176.74 | 0.00 | 0.00 |
October | 391.96 | 179.25 | 390.26 | 244.89 | 145.37 | 0.00 | 0.00 |
November | 261.95 | 261.08 | 294.32 | 184.24 | 110.08 | 0.00 | 0.00 |
December | 293.44 | 370.21 | 313.75 | 237.63 | 76.12 | 0.00 | 0.00 |
Annual Sum or Average | 296.07 | 197.11 | 328.63 | 169.80 | 158.84 | 0.00 | 0.00 |
Minimum of Months | 212.49 | 65.53 | 258.46 | 52.59 | 76.12 | 0.00 | 0.00 |
Maximum of Months | 391.96 | 398.32 | 410.04 | 277.06 | 205.87 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 325.02 | 395.44 | 382.50 | 261.73 | 120.77 | 0.00 | 0.00 |
February | 349.60 | 318.51 | 410.04 | 277.06 | 132.98 | 0.00 | 0.00 |
March | 299.81 | 225.07 | 356.89 | 187.99 | 168.89 | 0.00 | 0.00 |
April | 261.96 | 162.58 | 321.37 | 150.24 | 171.14 | 0.00 | 0.00 |
May | 215.30 | 97.31 | 266.22 | 72.15 | 194.08 | 0.00 | 0.00 |
June | 230.30 | 71.18 | 258.46 | 52.59 | 205.87 | 0.00 | 0.00 |
July | 250.63 | 64.49 | 273.59 | 68.90 | 204.69 | 0.00 | 0.00 |
August | 304.73 | 77.74 | 308.26 | 110.52 | 197.74 | 0.00 | 0.00 |
September | 381.04 | 126.22 | 373.67 | 196.93 | 176.74 | 0.00 | 0.00 |
October | 392.93 | 176.71 | 390.26 | 244.89 | 145.37 | 0.00 | 0.00 |
November | 262.69 | 258.10 | 294.32 | 184.24 | 110.08 | 0.00 | 0.00 |
December | 293.92 | 367.07 | 313.75 | 237.63 | 76.12 | 0.00 | 0.00 |
Annual Sum or Average | 297.04 | 194.46 | 328.63 | 169.80 | 158.84 | 0.00 | 0.00 |
Minimum of Months | 215.30 | 64.49 | 258.46 | 52.59 | 76.12 | 0.00 | 0.00 |
Maximum of Months | 392.93 | 395.44 | 410.04 | 277.06 | 205.87 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 327.24 | 382.52 | 382.50 | 261.73 | 120.77 | 0.00 | 0.00 |
February | 352.35 | 304.40 | 410.04 | 277.06 | 132.98 | 0.00 | 0.00 |
March | 303.26 | 210.23 | 356.89 | 187.99 | 168.89 | 0.00 | 0.00 |
April | 265.86 | 147.99 | 321.37 | 150.24 | 171.14 | 0.00 | 0.00 |
May | 221.60 | 86.70 | 266.22 | 72.15 | 194.08 | 0.00 | 0.00 |
June | 233.63 | 65.05 | 258.46 | 52.59 | 205.87 | 0.00 | 0.00 |
July | 252.56 | 60.61 | 273.59 | 68.90 | 204.69 | 0.00 | 0.00 |
August | 306.01 | 74.03 | 308.26 | 110.52 | 197.74 | 0.00 | 0.00 |
September | 382.80 | 120.47 | 373.67 | 196.93 | 176.74 | 0.00 | 0.00 |
October | 395.50 | 167.98 | 390.26 | 244.89 | 145.37 | 0.00 | 0.00 |
November | 265.05 | 246.71 | 294.32 | 184.24 | 110.08 | 0.00 | 0.00 |
December | 295.84 | 352.93 | 313.75 | 237.63 | 76.12 | 0.00 | 0.00 |
Annual Sum or Average | 299.86 | 184.42 | 328.63 | 169.80 | 158.84 | 0.00 | 0.00 |
Minimum of Months | 221.60 | 60.61 | 258.46 | 52.59 | 76.12 | 0.00 | 0.00 |
Maximum of Months | 395.50 | 382.52 | 410.04 | 277.06 | 205.87 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.174476E+10 | 0.218217E+10 | 0.205322E+10 | 0.140492E+10 | 0.648296E+09 | 0.00 | 0.00 |
February | 0.169359E+10 | 0.159246E+10 | 0.198801E+10 | 0.134328E+10 | 0.644733E+09 | 0.00 | 0.00 |
March | 0.160502E+10 | 0.125242E+10 | 0.191570E+10 | 0.100912E+10 | 0.906573E+09 | 0.00 | 0.00 |
April | 0.135206E+10 | 0.881945E+09 | 0.166943E+10 | 0.780436E+09 | 0.888997E+09 | 0.00 | 0.00 |
May | 0.112490E+10 | 0.566611E+09 | 0.142904E+10 | 0.387266E+09 | 0.104177E+10 | 0.00 | 0.00 |
June | 0.118967E+10 | 0.379344E+09 | 0.134261E+10 | 0.273182E+09 | 0.106943E+10 | 0.00 | 0.00 |
July | 0.134555E+10 | 0.343010E+09 | 0.146860E+10 | 0.369846E+09 | 0.109875E+10 | 0.00 | 0.00 |
August | 0.163360E+10 | 0.415986E+09 | 0.165470E+10 | 0.593266E+09 | 0.106143E+10 | 0.00 | 0.00 |
September | 0.197375E+10 | 0.665755E+09 | 0.194110E+10 | 0.102298E+10 | 0.918125E+09 | 0.00 | 0.00 |
October | 0.209475E+10 | 0.991078E+09 | 0.209485E+10 | 0.131451E+10 | 0.780340E+09 | 0.00 | 0.00 |
November | 0.135575E+10 | 0.139328E+10 | 0.152891E+10 | 0.957086E+09 | 0.571823E+09 | 0.00 | 0.00 |
December | 0.157472E+10 | 0.202398E+10 | 0.168415E+10 | 0.127556E+10 | 0.408589E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.186881E+11 | 0.126880E+11 | 0.207703E+11 | 0.107314E+11 | 0.100389E+11 | 0.00 | 0.00 |
Minimum of Months | 0.112490E+10 | 0.343010E+09 | 0.134261E+10 | 0.273182E+09 | 0.408589E+09 | 0.00 | 0.00 |
Maximum of Months | 0.209475E+10 | 0.218217E+10 | 0.209485E+10 | 0.140492E+10 | 0.109875E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.863727E+09 | 0.112393E+10 | 0.102661E+10 | 0.702460E+09 | 0.324148E+09 | 0.00 | 0.00 |
February | 0.838029E+09 | 0.826611E+09 | 0.994005E+09 | 0.671639E+09 | 0.322366E+09 | 0.00 | 0.00 |
March | 0.791784E+09 | 0.660580E+09 | 0.957848E+09 | 0.504561E+09 | 0.453287E+09 | 0.00 | 0.00 |
April | 0.666939E+09 | 0.472737E+09 | 0.834717E+09 | 0.390218E+09 | 0.444498E+09 | 0.00 | 0.00 |
May | 0.549920E+09 | 0.302774E+09 | 0.714518E+09 | 0.193633E+09 | 0.520885E+09 | 0.00 | 0.00 |
June | 0.589344E+09 | 0.198294E+09 | 0.671304E+09 | 0.136591E+09 | 0.534713E+09 | 0.00 | 0.00 |
July | 0.670925E+09 | 0.173515E+09 | 0.734299E+09 | 0.184923E+09 | 0.549376E+09 | 0.00 | 0.00 |
August | 0.815293E+09 | 0.210355E+09 | 0.827348E+09 | 0.296633E+09 | 0.530715E+09 | 0.00 | 0.00 |
September | 0.982688E+09 | 0.343165E+09 | 0.970552E+09 | 0.511490E+09 | 0.459063E+09 | 0.00 | 0.00 |
October | 0.103759E+10 | 0.524112E+09 | 0.104743E+10 | 0.657256E+09 | 0.390170E+09 | 0.00 | 0.00 |
November | 0.669492E+09 | 0.728180E+09 | 0.764454E+09 | 0.478543E+09 | 0.285911E+09 | 0.00 | 0.00 |
December | 0.780808E+09 | 0.104630E+10 | 0.842073E+09 | 0.637778E+09 | 0.204295E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.925654E+10 | 0.661055E+10 | 0.103852E+11 | 0.536572E+10 | 0.501943E+10 | 0.00 | 0.00 |
Minimum of Months | 0.549920E+09 | 0.173515E+09 | 0.671304E+09 | 0.136591E+09 | 0.204295E+09 | 0.00 | 0.00 |
Maximum of Months | 0.103759E+10 | 0.112393E+10 | 0.104743E+10 | 0.702460E+09 | 0.549376E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.862563E+09 | 0.109800E+10 | 0.102450E+10 | 0.701017E+09 | 0.323482E+09 | 0.00 | 0.00 |
February | 0.837169E+09 | 0.805286E+09 | 0.991964E+09 | 0.670260E+09 | 0.321704E+09 | 0.00 | 0.00 |
March | 0.791749E+09 | 0.642286E+09 | 0.955881E+09 | 0.503525E+09 | 0.452356E+09 | 0.00 | 0.00 |
April | 0.666992E+09 | 0.459273E+09 | 0.833003E+09 | 0.389417E+09 | 0.443586E+09 | 0.00 | 0.00 |
May | 0.550945E+09 | 0.300330E+09 | 0.713051E+09 | 0.193235E+09 | 0.519815E+09 | 0.00 | 0.00 |
June | 0.586866E+09 | 0.204328E+09 | 0.669925E+09 | 0.136310E+09 | 0.533615E+09 | 0.00 | 0.00 |
July | 0.666440E+09 | 0.185418E+09 | 0.732791E+09 | 0.184543E+09 | 0.548248E+09 | 0.00 | 0.00 |
August | 0.812602E+09 | 0.221558E+09 | 0.825649E+09 | 0.296024E+09 | 0.529625E+09 | 0.00 | 0.00 |
September | 0.980970E+09 | 0.347535E+09 | 0.968559E+09 | 0.510439E+09 | 0.458120E+09 | 0.00 | 0.00 |
October | 0.104010E+10 | 0.506551E+09 | 0.104528E+10 | 0.655907E+09 | 0.389369E+09 | 0.00 | 0.00 |
November | 0.670748E+09 | 0.707446E+09 | 0.762885E+09 | 0.477560E+09 | 0.285324E+09 | 0.00 | 0.00 |
December | 0.780297E+09 | 0.102291E+10 | 0.840344E+09 | 0.636469E+09 | 0.203875E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.924744E+10 | 0.650093E+10 | 0.103638E+11 | 0.535471E+10 | 0.500912E+10 | 0.00 | 0.00 |
Minimum of Months | 0.550945E+09 | 0.185418E+09 | 0.669925E+09 | 0.136310E+09 | 0.203875E+09 | 0.00 | 0.00 |
Maximum of Months | 0.104010E+10 | 0.109800E+10 | 0.104528E+10 | 0.701017E+09 | 0.548248E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.863575E+09 | 0.108928E+10 | 0.102450E+10 | 0.701017E+09 | 0.323482E+09 | 0.00 | 0.00 |
February | 0.838289E+09 | 0.797719E+09 | 0.991964E+09 | 0.670260E+09 | 0.321704E+09 | 0.00 | 0.00 |
March | 0.793231E+09 | 0.634818E+09 | 0.955881E+09 | 0.503525E+09 | 0.452356E+09 | 0.00 | 0.00 |
April | 0.668507E+09 | 0.452793E+09 | 0.833003E+09 | 0.389417E+09 | 0.443586E+09 | 0.00 | 0.00 |
May | 0.553587E+09 | 0.295376E+09 | 0.713051E+09 | 0.193235E+09 | 0.519815E+09 | 0.00 | 0.00 |
June | 0.587723E+09 | 0.202753E+09 | 0.669925E+09 | 0.136310E+09 | 0.533615E+09 | 0.00 | 0.00 |
July | 0.666400E+09 | 0.185595E+09 | 0.732791E+09 | 0.184543E+09 | 0.548248E+09 | 0.00 | 0.00 |
August | 0.812679E+09 | 0.221461E+09 | 0.825649E+09 | 0.296024E+09 | 0.529625E+09 | 0.00 | 0.00 |
September | 0.981685E+09 | 0.345395E+09 | 0.968559E+09 | 0.510439E+09 | 0.458120E+09 | 0.00 | 0.00 |
October | 0.104266E+10 | 0.498569E+09 | 0.104528E+10 | 0.655907E+09 | 0.389369E+09 | 0.00 | 0.00 |
November | 0.672568E+09 | 0.698791E+09 | 0.762885E+09 | 0.477560E+09 | 0.285324E+09 | 0.00 | 0.00 |
December | 0.781248E+09 | 0.101440E+10 | 0.840344E+09 | 0.636469E+09 | 0.203875E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.926216E+10 | 0.643695E+10 | 0.103638E+11 | 0.535471E+10 | 0.500912E+10 | 0.00 | 0.00 |
Minimum of Months | 0.553587E+09 | 0.185595E+09 | 0.669925E+09 | 0.136310E+09 | 0.203875E+09 | 0.00 | 0.00 |
Maximum of Months | 0.104266E+10 | 0.108928E+10 | 0.104528E+10 | 0.701017E+09 | 0.548248E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.864746E+09 | 0.108317E+10 | 0.102450E+10 | 0.701017E+09 | 0.323482E+09 | 0.00 | 0.00 |
February | 0.839525E+09 | 0.792308E+09 | 0.991964E+09 | 0.670260E+09 | 0.321704E+09 | 0.00 | 0.00 |
March | 0.794939E+09 | 0.628953E+09 | 0.955881E+09 | 0.503525E+09 | 0.452356E+09 | 0.00 | 0.00 |
April | 0.670294E+09 | 0.447350E+09 | 0.833003E+09 | 0.389417E+09 | 0.443586E+09 | 0.00 | 0.00 |
May | 0.557491E+09 | 0.289539E+09 | 0.713051E+09 | 0.193235E+09 | 0.519815E+09 | 0.00 | 0.00 |
June | 0.589456E+09 | 0.199771E+09 | 0.669925E+09 | 0.136310E+09 | 0.533615E+09 | 0.00 | 0.00 |
July | 0.667329E+09 | 0.183729E+09 | 0.732791E+09 | 0.184543E+09 | 0.548248E+09 | 0.00 | 0.00 |
August | 0.813489E+09 | 0.219483E+09 | 0.825649E+09 | 0.296024E+09 | 0.529625E+09 | 0.00 | 0.00 |
September | 0.982997E+09 | 0.342132E+09 | 0.968559E+09 | 0.510439E+09 | 0.458120E+09 | 0.00 | 0.00 |
October | 0.104485E+10 | 0.493008E+09 | 0.104528E+10 | 0.655907E+09 | 0.389369E+09 | 0.00 | 0.00 |
November | 0.674321E+09 | 0.692324E+09 | 0.762885E+09 | 0.477560E+09 | 0.285324E+09 | 0.00 | 0.00 |
December | 0.782288E+09 | 0.100815E+10 | 0.840344E+09 | 0.636469E+09 | 0.203875E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.928172E+10 | 0.637992E+10 | 0.103638E+11 | 0.535471E+10 | 0.500912E+10 | 0.00 | 0.00 |
Minimum of Months | 0.557491E+09 | 0.183729E+09 | 0.669925E+09 | 0.136310E+09 | 0.203875E+09 | 0.00 | 0.00 |
Maximum of Months | 0.104485E+10 | 0.108317E+10 | 0.104528E+10 | 0.701017E+09 | 0.548248E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.174479E+10 | 0.212187E+10 | 0.204900E+10 | 0.140203E+10 | 0.646964E+09 | 0.00 | 0.00 |
February | 0.169352E+10 | 0.154992E+10 | 0.198393E+10 | 0.134052E+10 | 0.643409E+09 | 0.00 | 0.00 |
March | 0.160382E+10 | 0.122363E+10 | 0.191176E+10 | 0.100705E+10 | 0.904712E+09 | 0.00 | 0.00 |
April | 0.135009E+10 | 0.867969E+09 | 0.166601E+10 | 0.778834E+09 | 0.887171E+09 | 0.00 | 0.00 |
May | 0.112812E+10 | 0.555845E+09 | 0.142610E+10 | 0.386471E+09 | 0.103963E+10 | 0.00 | 0.00 |
June | 0.118172E+10 | 0.385772E+09 | 0.133985E+10 | 0.272621E+09 | 0.106723E+10 | 0.00 | 0.00 |
July | 0.133415E+10 | 0.357024E+09 | 0.146558E+10 | 0.369086E+09 | 0.109650E+10 | 0.00 | 0.00 |
August | 0.162637E+10 | 0.427290E+09 | 0.165130E+10 | 0.592048E+09 | 0.105925E+10 | 0.00 | 0.00 |
September | 0.196895E+10 | 0.669995E+09 | 0.193712E+10 | 0.102088E+10 | 0.916240E+09 | 0.00 | 0.00 |
October | 0.210037E+10 | 0.964977E+09 | 0.209055E+10 | 0.131181E+10 | 0.778738E+09 | 0.00 | 0.00 |
November | 0.136028E+10 | 0.135120E+10 | 0.152577E+10 | 0.955121E+09 | 0.570648E+09 | 0.00 | 0.00 |
December | 0.157573E+10 | 0.197368E+10 | 0.168069E+10 | 0.127294E+10 | 0.407750E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.186679E+11 | 0.124492E+11 | 0.207277E+11 | 0.107094E+11 | 0.100182E+11 | 0.00 | 0.00 |
Minimum of Months | 0.112812E+10 | 0.357024E+09 | 0.133985E+10 | 0.272621E+09 | 0.407750E+09 | 0.00 | 0.00 |
Maximum of Months | 0.210037E+10 | 0.212187E+10 | 0.209055E+10 | 0.140203E+10 | 0.109650E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.869051E+09 | 0.106820E+10 | 0.102450E+10 | 0.701017E+09 | 0.323482E+09 | 0.00 | 0.00 |
February | 0.843892E+09 | 0.779680E+09 | 0.991964E+09 | 0.670260E+09 | 0.321704E+09 | 0.00 | 0.00 |
March | 0.799611E+09 | 0.614850E+09 | 0.955881E+09 | 0.503525E+09 | 0.452356E+09 | 0.00 | 0.00 |
April | 0.674586E+09 | 0.434680E+09 | 0.833003E+09 | 0.389417E+09 | 0.443586E+09 | 0.00 | 0.00 |
May | 0.565767E+09 | 0.275540E+09 | 0.713051E+09 | 0.193235E+09 | 0.519815E+09 | 0.00 | 0.00 |
June | 0.592332E+09 | 0.191033E+09 | 0.669925E+09 | 0.136310E+09 | 0.533615E+09 | 0.00 | 0.00 |
July | 0.668500E+09 | 0.176594E+09 | 0.732791E+09 | 0.184543E+09 | 0.548248E+09 | 0.00 | 0.00 |
August | 0.814040E+09 | 0.211905E+09 | 0.825649E+09 | 0.296024E+09 | 0.529625E+09 | 0.00 | 0.00 |
September | 0.984638E+09 | 0.333587E+09 | 0.968559E+09 | 0.510439E+09 | 0.458120E+09 | 0.00 | 0.00 |
October | 0.104881E+10 | 0.482415E+09 | 0.104528E+10 | 0.655907E+09 | 0.389369E+09 | 0.00 | 0.00 |
November | 0.678330E+09 | 0.678851E+09 | 0.762885E+09 | 0.477560E+09 | 0.285324E+09 | 0.00 | 0.00 |
December | 0.785626E+09 | 0.993227E+09 | 0.840344E+09 | 0.636469E+09 | 0.203875E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.932519E+10 | 0.624056E+10 | 0.103638E+11 | 0.535471E+10 | 0.500912E+10 | 0.00 | 0.00 |
Minimum of Months | 0.565767E+09 | 0.176594E+09 | 0.669925E+09 | 0.136310E+09 | 0.203875E+09 | 0.00 | 0.00 |
Maximum of Months | 0.104881E+10 | 0.106820E+10 | 0.104528E+10 | 0.701017E+09 | 0.548248E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.869312E+09 | 0.106687E+10 | 0.102450E+10 | 0.701017E+09 | 0.323482E+09 | 0.00 | 0.00 |
February | 0.844251E+09 | 0.778132E+09 | 0.991964E+09 | 0.670260E+09 | 0.321704E+09 | 0.00 | 0.00 |
March | 0.800394E+09 | 0.612508E+09 | 0.955881E+09 | 0.503525E+09 | 0.452356E+09 | 0.00 | 0.00 |
April | 0.675720E+09 | 0.431699E+09 | 0.833003E+09 | 0.389417E+09 | 0.443586E+09 | 0.00 | 0.00 |
May | 0.569128E+09 | 0.271134E+09 | 0.713051E+09 | 0.193235E+09 | 0.519815E+09 | 0.00 | 0.00 |
June | 0.593704E+09 | 0.189217E+09 | 0.669925E+09 | 0.136310E+09 | 0.533615E+09 | 0.00 | 0.00 |
July | 0.669371E+09 | 0.175512E+09 | 0.732791E+09 | 0.184543E+09 | 0.548248E+09 | 0.00 | 0.00 |
August | 0.814749E+09 | 0.210839E+09 | 0.825649E+09 | 0.296024E+09 | 0.529625E+09 | 0.00 | 0.00 |
September | 0.985573E+09 | 0.331744E+09 | 0.968559E+09 | 0.510439E+09 | 0.458120E+09 | 0.00 | 0.00 |
October | 0.104982E+10 | 0.480104E+09 | 0.104528E+10 | 0.655907E+09 | 0.389369E+09 | 0.00 | 0.00 |
November | 0.678982E+09 | 0.676714E+09 | 0.762885E+09 | 0.477560E+09 | 0.285324E+09 | 0.00 | 0.00 |
December | 0.785942E+09 | 0.991570E+09 | 0.840344E+09 | 0.636469E+09 | 0.203875E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.933694E+10 | 0.621605E+10 | 0.103638E+11 | 0.535471E+10 | 0.500912E+10 | 0.00 | 0.00 |
Minimum of Months | 0.569128E+09 | 0.175512E+09 | 0.669925E+09 | 0.136310E+09 | 0.203875E+09 | 0.00 | 0.00 |
Maximum of Months | 0.104982E+10 | 0.106687E+10 | 0.104528E+10 | 0.701017E+09 | 0.548248E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.870521E+09 | 0.105916E+10 | 0.102450E+10 | 0.701017E+09 | 0.323482E+09 | 0.00 | 0.00 |
February | 0.845746E+09 | 0.770528E+09 | 0.991964E+09 | 0.670260E+09 | 0.321704E+09 | 0.00 | 0.00 |
March | 0.803002E+09 | 0.602822E+09 | 0.955881E+09 | 0.503525E+09 | 0.452356E+09 | 0.00 | 0.00 |
April | 0.679011E+09 | 0.421416E+09 | 0.833003E+09 | 0.389417E+09 | 0.443586E+09 | 0.00 | 0.00 |
May | 0.576647E+09 | 0.260638E+09 | 0.713051E+09 | 0.193235E+09 | 0.519815E+09 | 0.00 | 0.00 |
June | 0.596927E+09 | 0.184487E+09 | 0.669925E+09 | 0.136310E+09 | 0.533615E+09 | 0.00 | 0.00 |
July | 0.671289E+09 | 0.172733E+09 | 0.732791E+09 | 0.184543E+09 | 0.548248E+09 | 0.00 | 0.00 |
August | 0.816184E+09 | 0.208217E+09 | 0.825649E+09 | 0.296024E+09 | 0.529625E+09 | 0.00 | 0.00 |
September | 0.987663E+09 | 0.327155E+09 | 0.968559E+09 | 0.510439E+09 | 0.458120E+09 | 0.00 | 0.00 |
October | 0.105241E+10 | 0.473313E+09 | 0.104528E+10 | 0.655907E+09 | 0.389369E+09 | 0.00 | 0.00 |
November | 0.680901E+09 | 0.668992E+09 | 0.762885E+09 | 0.477560E+09 | 0.285324E+09 | 0.00 | 0.00 |
December | 0.787231E+09 | 0.983166E+09 | 0.840344E+09 | 0.636469E+09 | 0.203875E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.936753E+10 | 0.613262E+10 | 0.103638E+11 | 0.535471E+10 | 0.500912E+10 | 0.00 | 0.00 |
Minimum of Months | 0.576647E+09 | 0.172733E+09 | 0.669925E+09 | 0.136310E+09 | 0.203875E+09 | 0.00 | 0.00 |
Maximum of Months | 0.105241E+10 | 0.105916E+10 | 0.104528E+10 | 0.701017E+09 | 0.548248E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.876471E+09 | 0.102453E+10 | 0.102450E+10 | 0.701017E+09 | 0.323482E+09 | 0.00 | 0.00 |
February | 0.852398E+09 | 0.736413E+09 | 0.991964E+09 | 0.670260E+09 | 0.321704E+09 | 0.00 | 0.00 |
March | 0.812246E+09 | 0.563088E+09 | 0.955881E+09 | 0.503525E+09 | 0.452356E+09 | 0.00 | 0.00 |
April | 0.689111E+09 | 0.383592E+09 | 0.833003E+09 | 0.389417E+09 | 0.443586E+09 | 0.00 | 0.00 |
May | 0.593526E+09 | 0.232219E+09 | 0.713051E+09 | 0.193235E+09 | 0.519815E+09 | 0.00 | 0.00 |
June | 0.605578E+09 | 0.168617E+09 | 0.669925E+09 | 0.136310E+09 | 0.533615E+09 | 0.00 | 0.00 |
July | 0.676444E+09 | 0.162335E+09 | 0.732791E+09 | 0.184543E+09 | 0.548248E+09 | 0.00 | 0.00 |
August | 0.819605E+09 | 0.198283E+09 | 0.825649E+09 | 0.296024E+09 | 0.529625E+09 | 0.00 | 0.00 |
September | 0.992205E+09 | 0.312257E+09 | 0.968559E+09 | 0.510439E+09 | 0.458120E+09 | 0.00 | 0.00 |
October | 0.105930E+10 | 0.449905E+09 | 0.104528E+10 | 0.655907E+09 | 0.389369E+09 | 0.00 | 0.00 |
November | 0.687009E+09 | 0.639480E+09 | 0.762885E+09 | 0.477560E+09 | 0.285324E+09 | 0.00 | 0.00 |
December | 0.792373E+09 | 0.945288E+09 | 0.840344E+09 | 0.636469E+09 | 0.203875E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.945626E+10 | 0.581601E+10 | 0.103638E+11 | 0.535471E+10 | 0.500912E+10 | 0.00 | 0.00 |
Minimum of Months | 0.593526E+09 | 0.162335E+09 | 0.669925E+09 | 0.136310E+09 | 0.203875E+09 | 0.00 | 0.00 |
Maximum of Months | 0.105930E+10 | 0.102453E+10 | 0.104528E+10 | 0.701017E+09 | 0.548248E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -12.6 | -13.1 | -15.2 | 6.10 | -26.1 | 37.55 | 107.22 | 0.02 |
February | -7.7 | -8.6 | -10.9 | 6.39 | -21.3 | 45.57 | 135.04 | 0.00 |
March | 0.33 | -1.3 | -4.2 | 6.99 | -10.6 | 74.69 | 127.11 | 0.00 |
April | 7.02 | 4.42 | 1.63 | 6.38 | -3.6 | 77.59 | 184.47 | 0.02 |
May | 14.19 | 11.29 | 8.94 | 5.14 | 4.69 | 102.33 | 182.89 | 0.00 |
June | 19.16 | 15.70 | 13.79 | 4.87 | 8.84 | 110.26 | 213.51 | 0.04 |
July | 20.92 | 17.86 | 16.31 | 4.22 | 9.95 | 102.99 | 231.93 | 0.03 |
August | 20.05 | 16.99 | 15.28 | 4.97 | 11.01 | 95.97 | 190.14 | 0.00 |
September | 15.39 | 11.23 | 8.10 | 4.97 | 3.17 | 72.67 | 177.74 | 0.01 |
October | 7.43 | 4.70 | 1.56 | 5.55 | -3.9 | 55.50 | 131.91 | 0.00 |
November | -0.0 | -1.4 | -3.9 | 6.30 | -10.9 | 41.35 | 79.05 | 0.00 |
December | -7.6 | -8.4 | -10.6 | 6.09 | -20.0 | 22.97 | 92.59 | 0.00 |
Annual Sum or Average | 6.46 | 4.18 | 1.81 | 5.66 | -4.8 | 70.09 | 154.52 | 0.01 |
Minimum of Months | -12.6 | -13.1 | -15.2 | 4.22 | -26.1 | 22.97 | 79.05 | 0.00 |
Maximum of Months | 20.92 | 17.86 | 16.31 | 6.99 | 11.01 | 110.26 | 231.93 | 0.04 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 6.10 | 17-JAN-23:19 | 3.74 | 0.93 | 10.63 | -0.4 | 0.00 | 0.00 |
February | 8.30 | 24-FEB-14:00 | 5.61 | 2.80 | 5.20 | -7.3 | 71.00 | 794.50 |
March | 18.90 | 19-MAR-15:00 | 13.92 | 10.60 | 8.80 | 7.95 | 139.50 | 237.50 |
April | 30.00 | 15-APR-15:20 | 19.10 | 13.53 | 12.70 | 15.70 | 115.83 | 790.83 |
May | 30.00 | 31-MAY-12:00 | 19.68 | 14.40 | 6.20 | 19.52 | 251.00 | 580.50 |
June | 33.30 | 11-JUN-14:00 | 24.80 | 21.70 | 10.30 | 24.50 | 281.00 | 458.50 |
July | 30.00 | 26-JUL-15:20 | 25.66 | 24.23 | 5.13 | 20.98 | 260.33 | 436.00 |
August | 33.90 | 04-AUG-14:00 | 25.30 | 22.20 | 4.60 | 23.82 | 194.50 | 612.00 |
September | 32.20 | 06-SEP-13:00 | 21.17 | 16.10 | 6.20 | 18.28 | 135.00 | 769.00 |
October | 23.30 | 20-OCT-14:00 | 13.34 | 5.60 | 7.20 | 7.35 | 55.00 | 745.50 |
November | 16.10 | 03-NOV-13:00 | 10.46 | 5.60 | 6.70 | 0.51 | 82.00 | 691.00 |
December | 7.20 | 02-DEC-13:00 | 3.93 | 0.00 | 7.70 | -3.9 | 75.00 | 301.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.10 | 3.74 | 0.00 | 4.60 | -7.3 | 0.00 | 0.00 | |
Maximum of Months | 33.90 | 25.66 | 24.23 | 12.70 | 24.50 | 281.00 | 794.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -31.1 | 31-JAN-03:00 | -31.3 | -34.4 | 4.60 | -46.7 | 0.00 | 0.00 |
February | -36.7 | 02-FEB-05:00 | -36.8 | -40.2 | 3.10 | -59.6 | 0.00 | 0.00 |
March | -17.2 | 06-MAR-00:00 | -17.6 | -20.0 | 5.20 | -36.8 | 0.00 | 0.00 |
April | -7.2 | 03-APR-05:19 | -8.0 | -9.8 | 7.37 | -15.9 | 0.00 | 0.00 |
May | 0.60 | 03-MAY-02:00 | -0.0 | -1.1 | 1.50 | -15.5 | 0.00 | 0.00 |
June | 5.00 | 01-JUN-04:00 | 5.00 | 5.00 | 3.10 | -7.8 | 30.50 | 132.50 |
July | 10.00 | 23-JUL-03:00 | 9.66 | 9.40 | 2.60 | -4.3 | 0.00 | 0.00 |
August | 8.30 | 07-AUG-03:00 | 7.41 | 6.70 | 3.10 | -3.2 | 0.00 | 0.00 |
September | -1.1 | 30-SEP-00:00 | -2.4 | -4.4 | 4.10 | -17.8 | 0.00 | 0.00 |
October | -3.3 | 23-OCT-05:00 | -4.2 | -6.1 | 3.60 | -19.1 | 0.00 | 0.00 |
November | -28.9 | 26-NOV-06:00 | -29.0 | -30.6 | 1.50 | -50.2 | 0.00 | 0.00 |
December | -22.8 | 09-DEC-00:20 | -23.0 | -25.0 | 13.40 | -37.7 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -36.7 | -36.8 | -40.2 | 1.50 | -59.6 | 0.00 | 0.00 | |
Maximum of Months | 10.00 | 9.66 | 9.40 | 13.40 | -3.2 | 30.50 | 132.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 5.60 | 18-JAN-00:00 | 5.60 | 5.60 | 7.70 | 0.30 | 0.00 | 0.00 |
February | 5.87 | 24-FEB-15:00 | 8.30 | 3.30 | 5.70 | -7.3 | 54.50 | 665.50 |
March | 13.92 | 19-MAR-15:00 | 18.90 | 10.60 | 8.80 | 7.95 | 139.50 | 237.50 |
April | 20.93 | 18-APR-11:00 | 27.80 | 17.80 | 13.90 | 17.57 | 334.00 | 447.00 |
May | 19.92 | 29-MAY-13:00 | 23.30 | 18.30 | 6.20 | 20.75 | 379.00 | 52.00 |
June | 24.80 | 11-JUN-14:00 | 33.30 | 21.70 | 10.30 | 24.50 | 281.00 | 458.50 |
July | 26.15 | 26-JUL-18:00 | 27.80 | 25.60 | 3.10 | 19.35 | 33.50 | 51.00 |
August | 26.63 | 04-AUG-12:00 | 31.70 | 25.00 | 4.60 | 25.66 | 235.00 | 593.50 |
September | 21.17 | 06-SEP-13:00 | 32.20 | 16.10 | 6.20 | 18.28 | 135.00 | 769.00 |
October | 14.83 | 02-OCT-14:00 | 18.30 | 12.80 | 3.60 | 12.41 | 202.00 | 164.00 |
November | 13.03 | 09-NOV-04:00 | 15.00 | 11.70 | 10.30 | 10.88 | 0.00 | 0.00 |
December | 3.93 | 02-DEC-13:00 | 7.20 | 0.00 | 7.70 | -3.9 | 75.00 | 301.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 3.93 | 5.60 | 0.00 | 3.10 | -7.3 | 0.00 | 0.00 | |
Maximum of Months | 26.63 | 33.30 | 25.60 | 13.90 | 25.66 | 379.00 | 769.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 5.60 | 18-JAN-00:00 | 5.60 | 5.60 | 7.70 | 0.30 | 0.00 | 0.00 |
February | 3.30 | 24-FEB-15:00 | 8.30 | 5.87 | 5.70 | -7.3 | 54.50 | 665.50 |
March | 11.10 | 26-MAR-05:00 | 13.30 | 12.04 | 8.20 | 9.13 | 0.00 | 0.00 |
April | 18.30 | 18-APR-09:00 | 25.60 | 20.52 | 14.40 | 15.57 | 196.00 | 741.50 |
May | 18.30 | 29-MAY-13:00 | 23.30 | 19.92 | 6.20 | 20.75 | 379.00 | 52.00 |
June | 22.20 | 13-JUN-11:00 | 26.70 | 23.34 | 8.80 | 16.85 | 273.50 | 600.50 |
July | 25.60 | 26-JUL-18:00 | 27.80 | 26.15 | 3.10 | 19.35 | 33.50 | 51.00 |
August | 25.00 | 04-AUG-12:00 | 31.70 | 26.63 | 4.60 | 25.66 | 235.00 | 593.50 |
September | 18.30 | 12-SEP-02:00 | 18.90 | 18.46 | 5.70 | 14.28 | 0.00 | 0.00 |
October | 12.80 | 02-OCT-13:00 | 17.40 | 14.50 | 3.40 | 11.65 | 249.50 | 141.50 |
November | 11.70 | 08-NOV-10:00 | 13.90 | 12.62 | 7.20 | 9.91 | 158.00 | 0.50 |
December | 0.00 | 02-DEC-11:00 | 5.00 | 2.78 | 7.20 | -8.3 | 115.50 | 562.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 0.00 | 5.00 | 2.78 | 3.10 | -8.3 | 0.00 | 0.00 | |
Maximum of Months | 25.60 | 31.70 | 26.63 | 14.40 | 25.66 | 379.00 | 741.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 4.29 | 14.52 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 3.18 | 19.75 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 3.75 | 28.43 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 5.88 | 38.20 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 9.06 | 44.89 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 12.40 | 51.07 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 15.02 | 51.61 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 16.22 | 43.31 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 15.63 | 34.41 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 13.44 | 22.83 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 10.25 | 13.98 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 6.92 | 10.24 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 9.71 | 31.16 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 3.18 | 10.24 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 16.22 | 51.61 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK1
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.395223E+09 | -268565639.6 | 0.00 | 0.00 | 744.00 | 0.00 | -126657771.8 | 58.99 | 0.00 | 0.00 |
February | 0.362669E+09 | -248806559.4 | 0.00 | 0.00 | 672.00 | 0.00 | -113862183.3 | 58.99 | 0.00 | 0.00 |
March | 0.401937E+09 | -276979484.2 | 0.00 | 0.00 | 744.00 | 0.00 | -124957419.2 | 58.99 | 0.00 | 0.00 |
April | 0.373129E+09 | -254736142.8 | 0.00 | 0.00 | 720.00 | 0.00 | -118392468.3 | 58.99 | 0.00 | 0.00 |
May | 0.364434E+09 | -247766407.7 | 0.00 | 0.00 | 744.00 | 0.00 | -116667281.8 | 58.99 | 0.00 | 0.00 |
June | 0.336019E+09 | -225765964.9 | 0.00 | 0.00 | 720.00 | 0.00 | -110252810.6 | 58.99 | 0.00 | 0.00 |
July | 0.328397E+09 | -215983985.9 | 0.00 | 0.00 | 744.00 | 0.00 | -112412958.6 | 58.99 | 0.00 | 0.00 |
August | 0.326712E+09 | -214290147.0 | 0.00 | 0.00 | 744.00 | 0.00 | -112422054.9 | 58.99 | 0.00 | 0.00 |
September | 0.319299E+09 | -208168683.4 | 0.00 | 0.00 | 720.00 | 0.00 | -111129981.4 | 58.99 | 0.00 | 0.00 |
October | 0.344744E+09 | -223672278.7 | 0.00 | 0.00 | 744.00 | 0.00 | -121071551.0 | 58.99 | 0.00 | 0.00 |
November | 0.350726E+09 | -230932097.1 | 0.00 | 0.00 | 720.00 | 0.00 | -119794040.1 | 58.99 | 0.00 | 0.00 |
December | 0.381912E+09 | -255968015.1 | 0.00 | 0.00 | 744.00 | 0.00 | -125944167.0 | 59.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.428520E+10 | -.287164E+10 | 8760.00 | -.141356E+10 | 58.99 | |||||
Minimum of Months | 0.319299E+09 | -276979484.2 | 0.00 | 0.00 | 672.00 | 0.00 | -126657771.8 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.401937E+09 | -208168683.4 | 0.00 | 0.00 | 744.00 | 0.00 | -110252810.6 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK2
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.393781E+09 | -268563068.5 | 0.00 | 0.00 | 744.00 | 0.00 | -125217680.3 | 59.00 | 0.00 | 0.00 |
February | 0.361086E+09 | -248802453.7 | 0.00 | 0.00 | 672.00 | 0.00 | -112283311.3 | 58.99 | 0.00 | 0.00 |
March | 0.399746E+09 | -276975831.2 | 0.00 | 0.00 | 744.00 | 0.00 | -122770631.9 | 58.99 | 0.00 | 0.00 |
April | 0.370787E+09 | -254751173.6 | 0.00 | 0.00 | 720.00 | 0.00 | -116036253.8 | 58.99 | 0.00 | 0.00 |
May | 0.362487E+09 | -247770111.4 | 0.00 | 0.00 | 744.00 | 0.00 | -114717246.7 | 58.99 | 0.00 | 0.00 |
June | 0.335184E+09 | -225765835.9 | 0.00 | 0.00 | 720.00 | 0.00 | -109418426.1 | 58.99 | 0.00 | 0.00 |
July | 0.328259E+09 | -215984827.2 | 0.00 | 0.00 | 744.00 | 0.00 | -112273796.0 | 58.99 | 0.00 | 0.00 |
August | 0.326544E+09 | -214293228.0 | 0.00 | 0.00 | 744.00 | 0.00 | -112251073.3 | 58.99 | 0.00 | 0.00 |
September | 0.318350E+09 | -208168803.5 | 0.00 | 0.00 | 720.00 | 0.00 | -110181051.0 | 58.99 | 0.00 | 0.00 |
October | 0.342094E+09 | -223679889.5 | 0.00 | 0.00 | 744.00 | 0.00 | -118413649.6 | 58.99 | 0.00 | 0.00 |
November | 0.348534E+09 | -230932748.1 | 0.00 | 0.00 | 720.00 | 0.00 | -117601673.7 | 58.99 | 0.00 | 0.00 |
December | 0.380194E+09 | -255978400.9 | 0.00 | 0.00 | 744.00 | 0.00 | -124215513.5 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.426705E+10 | -.287167E+10 | 8760.00 | -.139538E+10 | 58.99 | |||||
Minimum of Months | 0.318350E+09 | -276975831.2 | 0.00 | 0.00 | 672.00 | 0.00 | -125217680.3 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.399746E+09 | -208168803.5 | 0.00 | 0.00 | 744.00 | 0.00 | -109418426.1 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK3
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.363383E+09 | -236173752.5 | 0.00 | 0.00 | 744.00 | 0.00 | -127208975.4 | 58.99 | 0.00 | 0.00 |
February | 0.332985E+09 | -218966382.1 | 0.00 | 0.00 | 672.00 | 0.00 | -114019010.3 | 58.99 | 0.00 | 0.00 |
March | 0.371812E+09 | -247376457.1 | 0.00 | 0.00 | 744.00 | 0.00 | -124435245.6 | 58.99 | 0.00 | 0.00 |
April | 0.341236E+09 | -223864060.9 | 0.00 | 0.00 | 720.00 | 0.00 | -117372006.4 | 58.99 | 0.00 | 0.00 |
May | 0.334813E+09 | -219773086.0 | 0.00 | 0.00 | 744.00 | 0.00 | -115039754.1 | 58.99 | 0.00 | 0.00 |
June | 0.309836E+09 | -201208660.8 | 0.00 | 0.00 | 720.00 | 0.00 | -108627707.2 | 58.99 | 0.00 | 0.00 |
July | 0.299403E+09 | -188655863.9 | 0.00 | 0.00 | 744.00 | 0.00 | -110747279.5 | 58.99 | 0.00 | 0.00 |
August | 0.302565E+09 | -191547680.0 | 0.00 | 0.00 | 744.00 | 0.00 | -111016948.0 | 58.99 | 0.00 | 0.00 |
September | 0.292562E+09 | -182827316.9 | 0.00 | 0.00 | 720.00 | 0.00 | -109734633.7 | 58.99 | 0.00 | 0.00 |
October | 0.317023E+09 | -196730371.8 | 0.00 | 0.00 | 744.00 | 0.00 | -120292960.0 | 58.99 | 0.00 | 0.00 |
November | 0.323367E+09 | -203892729.7 | 0.00 | 0.00 | 720.00 | 0.00 | -119474580.6 | 58.99 | 0.00 | 0.00 |
December | 0.349552E+09 | -223431070.5 | 0.00 | 0.00 | 744.00 | 0.00 | -126120879.2 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.393854E+10 | -.253445E+10 | 8760.00 | -.140409E+10 | 58.99 | |||||
Minimum of Months | 0.292562E+09 | -247376457.1 | 0.00 | 0.00 | 672.00 | 0.00 | -127208975.4 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.371812E+09 | -182827316.9 | 0.00 | 0.00 | 744.00 | 0.00 | -108627707.2 | 58.99 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK4
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.363837E+09 | -236165240.2 | 0.00 | 0.00 | 744.00 | 0.00 | -127671802.6 | 59.00 | 0.00 | 0.00 |
February | 0.333407E+09 | -218952551.6 | 0.00 | 0.00 | 672.00 | 0.00 | -114454931.7 | 59.00 | 0.00 | 0.00 |
March | 0.372237E+09 | -247390046.5 | 0.00 | 0.00 | 744.00 | 0.00 | -124847108.5 | 58.98 | 0.00 | 0.00 |
April | 0.341649E+09 | -223876657.1 | 0.00 | 0.00 | 720.00 | 0.00 | -117772245.2 | 58.99 | 0.00 | 0.00 |
May | 0.335239E+09 | -219777267.2 | 0.00 | 0.00 | 744.00 | 0.00 | -115461380.5 | 58.99 | 0.00 | 0.00 |
June | 0.309985E+09 | -201198817.7 | 0.00 | 0.00 | 720.00 | 0.00 | -108786148.3 | 58.99 | 0.00 | 0.00 |
July | 0.299391E+09 | -188646295.7 | 0.00 | 0.00 | 744.00 | 0.00 | -110744454.4 | 59.00 | 0.00 | 0.00 |
August | 0.302573E+09 | -191549153.9 | 0.00 | 0.00 | 744.00 | 0.00 | -111024193.1 | 58.99 | 0.00 | 0.00 |
September | 0.292722E+09 | -182821774.4 | 0.00 | 0.00 | 720.00 | 0.00 | -109900131.6 | 58.99 | 0.00 | 0.00 |
October | 0.317610E+09 | -196714474.2 | 0.00 | 0.00 | 744.00 | 0.00 | -120895403.4 | 59.00 | 0.00 | 0.00 |
November | 0.323899E+09 | -203892791.1 | 0.00 | 0.00 | 720.00 | 0.00 | -120006395.7 | 58.99 | 0.00 | 0.00 |
December | 0.350010E+09 | -223429485.5 | 0.00 | 0.00 | 744.00 | 0.00 | -126580326.9 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.394256E+10 | -.253441E+10 | 8760.00 | -.140814E+10 | 58.99 | |||||
Minimum of Months | 0.292722E+09 | -247390046.5 | 0.00 | 0.00 | 672.00 | 0.00 | -127671802.6 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.372237E+09 | -182821774.4 | 0.00 | 0.00 | 744.00 | 0.00 | -108786148.3 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK5
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.352560E+09 | -223215357.3 | 0.00 | 0.00 | 744.00 | 0.00 | -129345006.3 | 58.99 | 0.00 | 0.00 |
February | 0.322911E+09 | -207065321.4 | 0.00 | 0.00 | 672.00 | 0.00 | -115845678.4 | 58.99 | 0.00 | 0.00 |
March | 0.360433E+09 | -234071231.2 | 0.00 | 0.00 | 744.00 | 0.00 | -126361812.4 | 58.99 | 0.00 | 0.00 |
April | 0.330965E+09 | -211850189.8 | 0.00 | 0.00 | 720.00 | 0.00 | -119114577.0 | 58.99 | 0.00 | 0.00 |
May | 0.325043E+09 | -207860003.1 | 0.00 | 0.00 | 744.00 | 0.00 | -117183234.6 | 58.98 | 0.00 | 0.00 |
June | 0.300045E+09 | -190377843.5 | 0.00 | 0.00 | 720.00 | 0.00 | -109667656.4 | 58.99 | 0.00 | 0.00 |
July | 0.289726E+09 | -178417055.4 | 0.00 | 0.00 | 744.00 | 0.00 | -111309043.2 | 58.99 | 0.00 | 0.00 |
August | 0.292831E+09 | -181314942.4 | 0.00 | 0.00 | 744.00 | 0.00 | -111516256.7 | 58.96 | 0.00 | 0.00 |
September | 0.283723E+09 | -173004029.1 | 0.00 | 0.00 | 720.00 | 0.00 | -110718987.0 | 58.99 | 0.00 | 0.00 |
October | 0.308073E+09 | -185939155.9 | 0.00 | 0.00 | 744.00 | 0.00 | -122134318.2 | 58.99 | 0.00 | 0.00 |
November | 0.314046E+09 | -192568818.3 | 0.00 | 0.00 | 720.00 | 0.00 | -121477026.4 | 58.99 | 0.00 | 0.00 |
December | 0.339429E+09 | -211307585.0 | 0.00 | 0.00 | 744.00 | 0.00 | -128121204.2 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.381979E+10 | -.239699E+10 | 8760.00 | -.142279E+10 | 58.99 | |||||
Minimum of Months | 0.283723E+09 | -234071231.2 | 0.00 | 0.00 | 672.00 | 0.00 | -129345006.3 | 58.96 | 0.00 | 0.00 |
Maximum of Months | 0.360433E+09 | -173004029.1 | 0.00 | 0.00 | 744.00 | 0.00 | -109667656.4 | 58.99 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK6
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.352417E+09 | -223218414.4 | 0.00 | 0.00 | 744.00 | 0.00 | -129198529.4 | 58.99 | 0.00 | 0.00 |
February | 0.322825E+09 | -207057124.7 | 0.00 | 0.00 | 672.00 | 0.00 | -115768168.2 | 59.00 | 0.00 | 0.00 |
March | 0.360392E+09 | -234070756.9 | 0.00 | 0.00 | 744.00 | 0.00 | -126321309.4 | 58.99 | 0.00 | 0.00 |
April | 0.331008E+09 | -211835429.1 | 0.00 | 0.00 | 720.00 | 0.00 | -119172517.9 | 59.00 | 0.00 | 0.00 |
May | 0.325305E+09 | -207851706.0 | 0.00 | 0.00 | 744.00 | 0.00 | -117453534.4 | 58.99 | 0.00 | 0.00 |
June | 0.300178E+09 | -190381564.1 | 0.00 | 0.00 | 720.00 | 0.00 | -109796621.6 | 58.99 | 0.00 | 0.00 |
July | 0.289842E+09 | -178411596.0 | 0.00 | 0.00 | 744.00 | 0.00 | -111430852.4 | 59.00 | 0.00 | 0.00 |
August | 0.292951E+09 | -181239029.7 | 0.00 | 0.00 | 744.00 | 0.00 | -111712413.2 | 58.99 | 0.00 | 0.00 |
September | 0.283833E+09 | -173002891.0 | 0.00 | 0.00 | 720.00 | 0.00 | -110829699.1 | 59.00 | 0.00 | 0.00 |
October | 0.308142E+09 | -185931828.0 | 0.00 | 0.00 | 744.00 | 0.00 | -122209764.2 | 58.99 | 0.00 | 0.00 |
November | 0.314034E+09 | -192581421.9 | 0.00 | 0.00 | 720.00 | 0.00 | -121452488.9 | 58.99 | 0.00 | 0.00 |
December | 0.339323E+09 | -211294490.5 | 0.00 | 0.00 | 744.00 | 0.00 | -128028713.4 | 59.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.382025E+10 | -.239688E+10 | 8760.00 | -.142337E+10 | 58.99 | |||||
Minimum of Months | 0.283833E+09 | -234070756.9 | 0.00 | 0.00 | 672.00 | 0.00 | -129198529.4 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.360392E+09 | -173002891.0 | 0.00 | 0.00 | 744.00 | 0.00 | -109796621.6 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK7
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.352484E+09 | -223215605.3 | 0.00 | 0.00 | 744.00 | 0.00 | -129268025.5 | 58.99 | 0.00 | 0.00 |
February | 0.322903E+09 | -207058435.0 | 0.00 | 0.00 | 672.00 | 0.00 | -115844870.0 | 59.00 | 0.00 | 0.00 |
March | 0.360527E+09 | -234070817.1 | 0.00 | 0.00 | 744.00 | 0.00 | -126456139.4 | 58.99 | 0.00 | 0.00 |
April | 0.331195E+09 | -211852784.6 | 0.00 | 0.00 | 720.00 | 0.00 | -119341917.5 | 58.99 | 0.00 | 0.00 |
May | 0.325759E+09 | -207841570.6 | 0.00 | 0.00 | 744.00 | 0.00 | -117917790.1 | 58.99 | 0.00 | 0.00 |
June | 0.300329E+09 | -190379032.2 | 0.00 | 0.00 | 720.00 | 0.00 | -109949509.9 | 58.99 | 0.00 | 0.00 |
July | 0.289936E+09 | -178413461.6 | 0.00 | 0.00 | 744.00 | 0.00 | -111522044.3 | 59.00 | 0.00 | 0.00 |
August | 0.293030E+09 | -181245785.4 | 0.00 | 0.00 | 744.00 | 0.00 | -111784015.3 | 58.99 | 0.00 | 0.00 |
September | 0.283974E+09 | -173006905.7 | 0.00 | 0.00 | 720.00 | 0.00 | -110967338.0 | 58.99 | 0.00 | 0.00 |
October | 0.308308E+09 | -185942693.1 | 0.00 | 0.00 | 744.00 | 0.00 | -122365702.4 | 58.99 | 0.00 | 0.00 |
November | 0.314158E+09 | -192578165.6 | 0.00 | 0.00 | 720.00 | 0.00 | -121580125.3 | 58.99 | 0.00 | 0.00 |
December | 0.339402E+09 | -211296264.1 | 0.00 | 0.00 | 744.00 | 0.00 | -128106128.5 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.382201E+10 | -.239690E+10 | 8760.00 | -.142510E+10 | 58.99 | |||||
Minimum of Months | 0.283974E+09 | -234070817.1 | 0.00 | 0.00 | 672.00 | 0.00 | -129268025.5 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.360527E+09 | -173006905.7 | 0.00 | 0.00 | 744.00 | 0.00 | -109949509.9 | 59.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 214.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 226.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 334.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 285.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 428.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 400.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 414.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 410.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 326.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 325.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 254.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 186.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3807.33 | ||||||||||
Minimum of Months | 186.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 428.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.366642E+11 | 59908.60 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.262274E+11 | 59908.60 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.169903E+11 | 59908.60 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.834904E+10 | 59908.60 | 01-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.437102E+09 | 59908.60 | 02-MAY-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 25321365.14 | 2182.86 | 02-JUN-08:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.415793E+09 | 59908.60 | 30-SEP-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.333886E+10 | 59908.60 | 27-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.155879E+11 | 59908.60 | 10-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.287170E+11 | 59908.60 | 01-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.136753E+12 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.366642E+11 | 59908.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.136805E+11 | 31740.57 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.951623E+10 | 31740.57 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.565282E+10 | 31740.57 | 01-MAR-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.257268E+10 | 31740.57 | 01-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 66261559.89 | 8909.01 | 02-MAY-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 33997497.10 | 5085.12 | 30-SEP-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.632386E+09 | 13523.83 | 27-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.537293E+10 | 31740.57 | 14-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.104611E+11 | 31740.57 | 01-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.479889E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.136805E+11 | 31740.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_3:3_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.151183E+11 | 31987.27 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.106749E+11 | 31987.27 | 01-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.673346E+10 | 31987.27 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.321870E+10 | 31987.27 | 02-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.143911E+09 | 11335.32 | 02-MAY-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.105904E+09 | 9025.45 | 30-SEP-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120010E+10 | 11869.70 | 27-OCT-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.626669E+10 | 31987.27 | 11-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.117502E+11 | 31987.27 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.552121E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.151183E+11 | 31987.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_4:4_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.154159E+11 | 31858.55 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109124E+11 | 31858.55 | 01-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.696210E+10 | 31858.55 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.337070E+10 | 31858.55 | 02-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.168830E+09 | 15562.19 | 02-MAY-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 1489816.56 | 403.68 | 05-JUN-07:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.133060E+09 | 12479.95 | 30-SEP-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.137842E+10 | 17838.54 | 16-OCT-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.648269E+10 | 31858.55 | 11-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.120103E+11 | 31858.55 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.568358E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.154159E+11 | 31858.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_5:5_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.158191E+11 | 31941.48 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.112394E+11 | 31941.48 | 01-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.728556E+10 | 31941.48 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.357966E+10 | 31941.48 | 01-APR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.199876E+09 | 19830.95 | 02-MAY-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 12083530.52 | 981.03 | 05-JUN-11:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.170999E+09 | 15806.71 | 30-SEP-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.158064E+10 | 22417.55 | 16-OCT-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.676133E+10 | 31941.48 | 11-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.123705E+11 | 31941.48 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.590192E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.158191E+11 | 31941.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_6:6_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.298654E+11 | 58675.12 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.212677E+11 | 58675.12 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.139740E+11 | 58675.12 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.693808E+10 | 58675.12 | 01-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.425340E+09 | 58675.12 | 01-MAY-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 67322011.42 | 5822.90 | 05-JUN-08:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.437173E+09 | 58675.12 | 30-SEP-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.346136E+10 | 58675.12 | 16-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.130156E+11 | 58675.12 | 10-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.235146E+11 | 58675.12 | 01-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.112967E+12 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.298654E+11 | 58675.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_7:7_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.154855E+11 | 30782.84 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.110319E+11 | 30782.84 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.727143E+10 | 30782.84 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.362219E+10 | 30782.84 | 01-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.227584E+09 | 30782.84 | 01-MAY-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 38076607.48 | 2486.74 | 05-JUN-08:17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.228011E+09 | 30782.84 | 30-SEP-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.179335E+10 | 30782.84 | 16-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.676281E+10 | 30782.84 | 10-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.121859E+11 | 30782.84 | 01-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.586468E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.154855E+11 | 30782.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_8:8_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.155681E+11 | 30593.81 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.111175E+11 | 30593.81 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.737902E+10 | 30593.81 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.371295E+10 | 30593.81 | 01-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.249872E+09 | 30593.81 | 01-MAY-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 48541820.67 | 2253.97 | 05-JUN-08:17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.248040E+09 | 30593.81 | 30-SEP-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.187652E+10 | 30593.81 | 16-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.685365E+10 | 30593.81 | 10-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.122743E+11 | 30593.81 | 01-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.593285E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.155681E+11 | 30593.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_9:9_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.160202E+11 | 30269.98 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.115383E+11 | 30269.98 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.782809E+10 | 30269.98 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.405197E+10 | 30269.98 | 01-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.331082E+09 | 30269.98 | 01-MAY-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 82729198.97 | 7642.02 | 05-JUN-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.303091E+09 | 30269.98 | 29-SEP-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.212943E+10 | 30269.98 | 08-OCT-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.719218E+10 | 30269.98 | 10-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.127183E+11 | 30269.98 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.621954E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.160202E+11 | 30269.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_10:10_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.196889E+11 | 32983.67 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.143800E+11 | 32983.67 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.101059E+11 | 32983.67 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.550127E+10 | 32983.67 | 01-APR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.677651E+09 | 32983.67 | 01-MAY-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.191819E+09 | 29203.79 | 05-JUN-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.452817E+09 | 32983.67 | 29-SEP-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.277718E+10 | 32983.67 | 06-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.880367E+10 | 32983.67 | 10-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.153827E+11 | 32983.67 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.779619E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.196889E+11 | 32983.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.165800E+10 | 0.113304E+10 | 18182.43 | 16-APR-16:10 | 12701.29 | 0.00 |
May | 0.00 | 0.00 | 0.290876E+10 | 0.198435E+10 | 41774.04 | 31-MAY-08:62 | 25801.94 | 0.00 |
June | 0.00 | 0.00 | 0.140781E+11 | 0.931302E+10 | 43425.82 | 26-JUN-08:61 | 24147.92 | 0.00 |
July | 0.00 | 0.00 | 0.199147E+11 | 0.122008E+11 | 43326.15 | 07-JUL-08:62 | 20310.92 | 0.00 |
August | 0.00 | 0.00 | 0.184984E+11 | 0.115910E+11 | 44564.21 | 04-AUG-08:61 | 21620.64 | 0.00 |
September | 0.00 | 0.00 | 0.867632E+10 | 0.677624E+10 | 41917.24 | 11-SEP-08:62 | 24577.12 | 0.00 |
October | 0.00 | 0.00 | 70410732.95 | 63091628.71 | 5362.36 | 20-OCT-15:00 | 5025.78 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.658046E+11 | 0.430616E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.199147E+11 | 0.122008E+11 | 44564.21 | 25801.94 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 108195.99 | 87338.89 | 116.75 | 19-MAR-22:10 | 91.34 | 0.00 |
April | 0.00 | 0.00 | 0.110999E+10 | 0.770634E+09 | 22147.74 | 16-APR-19:33 | 14237.14 | 0.00 |
May | 0.00 | 0.00 | 0.216787E+10 | 0.148319E+10 | 22409.93 | 31-MAY-08:62 | 14334.14 | 0.00 |
June | 0.00 | 0.00 | 0.848767E+10 | 0.568852E+10 | 22954.55 | 26-JUN-08:61 | 14451.99 | 0.00 |
July | 0.00 | 0.00 | 0.123227E+11 | 0.761480E+10 | 23118.07 | 07-JUL-08:62 | 11649.26 | 0.00 |
August | 0.00 | 0.00 | 0.112884E+11 | 0.709910E+10 | 23437.29 | 04-AUG-08:61 | 13310.56 | 0.00 |
September | 0.00 | 0.00 | 0.544080E+10 | 0.423181E+10 | 22442.63 | 11-SEP-08:62 | 13710.85 | 0.00 |
October | 0.00 | 0.00 | 58690887.04 | 52509572.02 | 3409.08 | 20-OCT-15:00 | 3221.81 | 0.00 |
November | 0.00 | 0.00 | 1039923.68 | 898783.97 | 453.67 | 07-NOV-23:50 | 342.30 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.408772E+11 | 0.269416E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.123227E+11 | 0.761480E+10 | 23437.29 | 14451.99 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.688269E+09 | 0.473374E+09 | 9740.30 | 18-APR-14:00 | 6676.22 | 0.00 |
May | 0.00 | 0.00 | 0.135769E+10 | 0.946326E+09 | 22570.91 | 31-MAY-07:03 | 13269.87 | 0.00 |
June | 0.00 | 0.00 | 0.590943E+10 | 0.396393E+10 | 23792.46 | 26-JUN-07:01 | 12955.73 | 0.00 |
July | 0.00 | 0.00 | 0.819637E+10 | 0.514633E+10 | 23507.04 | 27-JUL-07:02 | 11029.40 | 0.00 |
August | 0.00 | 0.00 | 0.811151E+10 | 0.521110E+10 | 24410.71 | 04-AUG-07:01 | 11485.87 | 0.00 |
September | 0.00 | 0.00 | 0.362917E+10 | 0.290463E+10 | 22573.25 | 11-SEP-07:01 | 13061.41 | 0.00 |
October | 0.00 | 0.00 | 37991504.60 | 34318866.97 | 2904.04 | 20-OCT-15:00 | 2744.02 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.279304E+11 | 0.186800E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.819637E+10 | 0.521110E+10 | 24410.71 | 13269.87 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.664338E+09 | 0.456058E+09 | 9637.15 | 18-APR-14:00 | 6597.73 | 0.00 |
May | 0.00 | 0.00 | 0.128972E+10 | 0.899216E+09 | 22407.20 | 31-MAY-07:03 | 13163.12 | 0.00 |
June | 0.00 | 0.00 | 0.587786E+10 | 0.394231E+10 | 23625.31 | 26-JUN-07:01 | 12885.03 | 0.00 |
July | 0.00 | 0.00 | 0.819866E+10 | 0.514673E+10 | 23338.35 | 27-JUL-07:02 | 10951.63 | 0.00 |
August | 0.00 | 0.00 | 0.809348E+10 | 0.519876E+10 | 24237.87 | 04-AUG-07:01 | 11404.91 | 0.00 |
September | 0.00 | 0.00 | 0.361923E+10 | 0.289510E+10 | 22413.00 | 11-SEP-07:01 | 12982.82 | 0.00 |
October | 0.00 | 0.00 | 32811961.15 | 29813136.60 | 2723.27 | 20-OCT-15:00 | 2573.55 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.277761E+11 | 0.185680E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.819866E+10 | 0.519876E+10 | 24237.87 | 13163.12 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.622663E+09 | 0.425550E+09 | 9419.66 | 18-APR-14:00 | 6427.20 | 0.00 |
May | 0.00 | 0.00 | 0.117522E+10 | 0.819749E+09 | 22001.36 | 31-MAY-07:03 | 12875.80 | 0.00 |
June | 0.00 | 0.00 | 0.569176E+10 | 0.381125E+10 | 23754.30 | 26-JUN-07:01 | 12900.33 | 0.00 |
July | 0.00 | 0.00 | 0.797759E+10 | 0.499966E+10 | 23472.46 | 27-JUL-07:02 | 10979.91 | 0.00 |
August | 0.00 | 0.00 | 0.786260E+10 | 0.504429E+10 | 24372.27 | 04-AUG-07:01 | 11392.98 | 0.00 |
September | 0.00 | 0.00 | 0.351384E+10 | 0.280823E+10 | 22540.97 | 11-SEP-07:01 | 13036.36 | 0.00 |
October | 0.00 | 0.00 | 26593266.70 | 24371818.15 | 2510.19 | 20-OCT-15:00 | 2370.57 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.268703E+11 | 0.179331E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.797759E+10 | 0.504429E+10 | 24372.27 | 13036.36 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.104902E+10 | 0.702481E+09 | 17311.51 | 18-APR-14:10 | 11584.64 | 0.00 |
May | 0.00 | 0.00 | 0.193078E+10 | 0.133337E+10 | 40999.81 | 31-MAY-08:62 | 25369.84 | 0.00 |
June | 0.00 | 0.00 | 0.100403E+11 | 0.664790E+10 | 42811.87 | 26-JUN-08:61 | 23670.79 | 0.00 |
July | 0.00 | 0.00 | 0.142323E+11 | 0.876154E+10 | 42469.51 | 07-JUL-08:62 | 20219.47 | 0.00 |
August | 0.00 | 0.00 | 0.139878E+11 | 0.883990E+10 | 43602.54 | 04-AUG-08:61 | 21572.68 | 0.00 |
September | 0.00 | 0.00 | 0.624030E+10 | 0.493086E+10 | 41121.93 | 11-SEP-08:62 | 24379.51 | 0.00 |
October | 0.00 | 0.00 | 40665888.26 | 36898488.13 | 4370.68 | 20-OCT-15:00 | 4068.84 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.475212E+11 | 0.312530E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.142323E+11 | 0.883990E+10 | 43602.54 | 25369.84 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.526164E+09 | 0.352029E+09 | 8897.44 | 18-APR-14:10 | 5956.77 | 0.00 |
May | 0.00 | 0.00 | 0.949479E+09 | 0.657401E+09 | 21875.54 | 31-MAY-08:62 | 13538.62 | 0.00 |
June | 0.00 | 0.00 | 0.511578E+10 | 0.339275E+10 | 22833.85 | 26-JUN-08:61 | 12649.00 | 0.00 |
July | 0.00 | 0.00 | 0.727164E+10 | 0.448837E+10 | 22662.36 | 07-JUL-08:62 | 10780.60 | 0.00 |
August | 0.00 | 0.00 | 0.713056E+10 | 0.451816E+10 | 23238.12 | 04-AUG-08:61 | 11543.57 | 0.00 |
September | 0.00 | 0.00 | 0.318758E+10 | 0.252191E+10 | 21940.96 | 11-SEP-08:62 | 13022.89 | 0.00 |
October | 0.00 | 0.00 | 18085711.60 | 16528656.35 | 2201.17 | 20-OCT-15:00 | 2052.09 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.241993E+11 | 0.159472E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.727164E+10 | 0.451816E+10 | 23238.12 | 13538.62 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.505240E+09 | 0.336883E+09 | 8713.47 | 18-APR-14:10 | 5815.82 | 0.00 |
May | 0.00 | 0.00 | 0.892693E+09 | 0.618533E+09 | 20999.88 | 31-MAY-08:62 | 12949.12 | 0.00 |
June | 0.00 | 0.00 | 0.501839E+10 | 0.332257E+10 | 22665.63 | 26-JUN-08:61 | 12507.08 | 0.00 |
July | 0.00 | 0.00 | 0.715354E+10 | 0.440751E+10 | 22499.32 | 07-JUL-08:62 | 10685.09 | 0.00 |
August | 0.00 | 0.00 | 0.701887E+10 | 0.444077E+10 | 23074.31 | 04-AUG-08:61 | 11408.11 | 0.00 |
September | 0.00 | 0.00 | 0.313646E+10 | 0.247887E+10 | 21782.33 | 11-SEP-08:62 | 12910.52 | 0.00 |
October | 0.00 | 0.00 | 16367072.05 | 14996571.36 | 2104.77 | 20-OCT-15:00 | 1960.63 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.237415E+11 | 0.156201E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.715354E+10 | 0.444077E+10 | 23074.31 | 12949.12 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.455772E+09 | 0.301288E+09 | 8242.47 | 18-APR-14:10 | 5457.71 | 0.00 |
May | 0.00 | 0.00 | 0.773385E+09 | 0.536585E+09 | 10970.76 | 31-MAY-08:62 | 6594.47 | 0.00 |
June | 0.00 | 0.00 | 0.478290E+10 | 0.315483E+10 | 22337.48 | 26-JUN-08:61 | 12203.01 | 0.00 |
July | 0.00 | 0.00 | 0.687860E+10 | 0.422270E+10 | 22186.24 | 07-JUL-08:62 | 10488.28 | 0.00 |
August | 0.00 | 0.00 | 0.676909E+10 | 0.427043E+10 | 22756.38 | 04-AUG-08:61 | 11146.84 | 0.00 |
September | 0.00 | 0.00 | 0.302727E+10 | 0.238697E+10 | 21477.40 | 11-SEP-08:62 | 12687.61 | 0.00 |
October | 0.00 | 0.00 | 12670743.19 | 11658001.02 | 1872.34 | 20-OCT-15:00 | 1740.41 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.226997E+11 | 0.148845E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.687860E+10 | 0.427043E+10 | 22756.38 | 12687.61 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.391035E+09 | 0.256470E+09 | 7636.06 | 18-APR-14:10 | 5011.76 | 0.00 |
May | 0.00 | 0.00 | 0.618910E+09 | 0.433076E+09 | 8227.87 | 31-MAY-13:00 | 6230.04 | 0.00 |
June | 0.00 | 0.00 | 0.441338E+10 | 0.291283E+10 | 25404.08 | 26-JUN-08:61 | 13047.59 | 0.00 |
July | 0.00 | 0.00 | 0.648684E+10 | 0.400087E+10 | 25106.63 | 07-JUL-08:62 | 11545.56 | 0.00 |
August | 0.00 | 0.00 | 0.642914E+10 | 0.408621E+10 | 26108.23 | 04-AUG-08:61 | 11408.06 | 0.00 |
September | 0.00 | 0.00 | 0.296126E+10 | 0.234365E+10 | 24310.19 | 11-SEP-08:62 | 14080.32 | 0.00 |
October | 0.00 | 0.00 | 8726361.85 | 8100666.21 | 1606.52 | 20-OCT-15:00 | 1501.58 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.213093E+11 | 0.140412E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.648684E+10 | 0.408621E+10 | 26108.23 | 14080.32 | 0.00 |
Report: FanReportMonthly
For: PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.201461E+10 | 0.51 | 1837.39 | 01-JAN-09:01 | 0.92 |
February | 0.169359E+10 | 0.48 | 1837.39 | 01-FEB-08:61 | 0.93 |
March | 0.165120E+10 | 0.44 | 1837.39 | 01-MAR-08:61 | 0.92 |
April | 0.144800E+10 | 0.41 | 1837.39 | 01-APR-08:61 | 0.92 |
May | 0.134171E+10 | 0.38 | 1837.39 | 02-MAY-08:61 | 0.92 |
June | 0.132061E+10 | 0.38 | 1837.39 | 12-JUN-08:62 | 0.91 |
July | 0.136171E+10 | 0.38 | 1837.39 | 01-JUL-08:62 | 0.91 |
August | 0.137148E+10 | 0.38 | 1837.39 | 01-AUG-08:62 | 0.90 |
September | 0.131126E+10 | 0.38 | 1837.39 | 06-SEP-08:62 | 0.91 |
October | 0.139495E+10 | 0.39 | 1837.39 | 27-OCT-08:61 | 0.92 |
November | 0.157699E+10 | 0.43 | 1837.39 | 10-NOV-09:01 | 0.92 |
December | 0.187077E+10 | 0.48 | 1837.39 | 01-DEC-09:01 | 0.92 |
Annual Sum or Average | 0.183569E+11 | 0.42 | |||
Minimum of Months | 0.131126E+10 | 0.38 | 1837.39 | 0.90 | |
Maximum of Months | 0.201461E+10 | 0.51 | 1837.39 | 0.93 |
Report: FanReportMonthly
For: PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.838489E+09 | 0.46 | 1041.24 | 01-JAN-09:01 | 0.95 |
February | 0.701222E+09 | 0.40 | 1041.24 | 01-FEB-08:61 | 0.96 |
March | 0.691450E+09 | 0.35 | 1041.24 | 01-MAR-09:01 | 0.96 |
April | 0.627038E+09 | 0.34 | 1041.24 | 01-APR-08:61 | 0.95 |
May | 0.693385E+09 | 0.38 | 1041.24 | 31-MAY-08:62 | 0.94 |
June | 0.677012E+09 | 0.38 | 1041.24 | 09-JUN-08:62 | 0.94 |
July | 0.700933E+09 | 0.36 | 1041.24 | 01-JUL-08:62 | 0.94 |
August | 0.718189E+09 | 0.37 | 1041.24 | 01-AUG-08:62 | 0.93 |
September | 0.659771E+09 | 0.37 | 1041.24 | 06-SEP-08:62 | 0.94 |
October | 0.614694E+09 | 0.35 | 682.69 | 27-OCT-08:61 | 0.78 |
November | 0.663027E+09 | 0.37 | 1041.24 | 14-NOV-09:01 | 0.95 |
December | 0.770264E+09 | 0.39 | 1041.24 | 01-DEC-09:01 | 0.95 |
Annual Sum or Average | 0.835547E+10 | 0.38 | |||
Minimum of Months | 0.614694E+09 | 0.34 | 682.69 | 0.78 | |
Maximum of Months | 0.838489E+09 | 0.46 | 1041.24 | 0.96 |
Report: FanReportMonthly
For: PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.908858E+09 | 0.40 | 1053.77 | 01-JAN-09:01 | 0.95 |
February | 0.763345E+09 | 0.38 | 1053.77 | 01-FEB-07:01 | 0.96 |
March | 0.755240E+09 | 0.36 | 1053.77 | 01-MAR-08:61 | 0.96 |
April | 0.655419E+09 | 0.33 | 1053.77 | 02-APR-08:61 | 0.95 |
May | 0.619068E+09 | 0.31 | 1053.77 | 31-MAY-07:03 | 0.94 |
June | 0.610392E+09 | 0.32 | 1053.77 | 10-JUN-07:03 | 0.94 |
July | 0.617665E+09 | 0.31 | 1053.77 | 01-JUL-07:02 | 0.94 |
August | 0.637730E+09 | 0.32 | 1053.77 | 01-AUG-07:02 | 0.94 |
September | 0.596134E+09 | 0.31 | 1053.77 | 06-SEP-07:02 | 0.94 |
October | 0.633728E+09 | 0.32 | 656.13 | 27-OCT-07:02 | 0.75 |
November | 0.715665E+09 | 0.35 | 1053.77 | 11-NOV-09:01 | 0.96 |
December | 0.839228E+09 | 0.38 | 1053.77 | 01-DEC-08:61 | 0.95 |
Annual Sum or Average | 0.835247E+10 | 0.34 | |||
Minimum of Months | 0.596134E+09 | 0.31 | 656.13 | 0.75 | |
Maximum of Months | 0.908858E+09 | 0.40 | 1053.77 | 0.96 |
Report: FanReportMonthly
For: PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.910459E+09 | 0.40 | 1047.24 | 01-JAN-09:01 | 0.95 |
February | 0.764207E+09 | 0.38 | 1047.24 | 01-FEB-07:01 | 0.96 |
March | 0.755600E+09 | 0.36 | 1047.24 | 01-MAR-08:61 | 0.96 |
April | 0.654607E+09 | 0.33 | 1047.24 | 02-APR-08:61 | 0.95 |
May | 0.615712E+09 | 0.31 | 1047.24 | 31-MAY-07:03 | 0.94 |
June | 0.607165E+09 | 0.32 | 1047.24 | 10-JUN-07:03 | 0.94 |
July | 0.614439E+09 | 0.31 | 1047.24 | 01-JUL-07:02 | 0.94 |
August | 0.634315E+09 | 0.32 | 1047.24 | 01-AUG-07:02 | 0.94 |
September | 0.593127E+09 | 0.31 | 1047.24 | 06-SEP-07:02 | 0.94 |
October | 0.633410E+09 | 0.32 | 770.72 | 16-OCT-07:02 | 0.82 |
November | 0.715984E+09 | 0.35 | 1047.24 | 11-NOV-09:01 | 0.96 |
December | 0.840145E+09 | 0.38 | 1047.24 | 01-DEC-08:61 | 0.95 |
Annual Sum or Average | 0.833917E+10 | 0.34 | |||
Minimum of Months | 0.593127E+09 | 0.31 | 770.72 | 0.82 | |
Maximum of Months | 0.910459E+09 | 0.40 | 1047.24 | 0.96 |
Report: FanReportMonthly
For: PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.921476E+09 | 0.41 | 1051.45 | 01-JAN-09:01 | 0.95 |
February | 0.773298E+09 | 0.39 | 1051.45 | 01-FEB-07:01 | 0.96 |
March | 0.764669E+09 | 0.36 | 1051.45 | 01-MAR-08:61 | 0.96 |
April | 0.661193E+09 | 0.33 | 1051.45 | 01-APR-07:02 | 0.95 |
May | 0.618755E+09 | 0.31 | 1021.75 | 31-MAY-07:03 | 0.93 |
June | 0.607996E+09 | 0.32 | 1051.45 | 11-JUN-08:62 | 0.94 |
July | 0.615384E+09 | 0.31 | 1051.45 | 01-JUL-07:02 | 0.94 |
August | 0.635131E+09 | 0.32 | 1051.45 | 01-AUG-07:02 | 0.94 |
September | 0.595709E+09 | 0.31 | 1051.45 | 06-SEP-07:02 | 0.94 |
October | 0.639880E+09 | 0.32 | 863.34 | 16-OCT-07:02 | 0.87 |
November | 0.724033E+09 | 0.35 | 1051.45 | 11-NOV-09:01 | 0.96 |
December | 0.850166E+09 | 0.39 | 1051.45 | 01-DEC-08:61 | 0.95 |
Annual Sum or Average | 0.840769E+10 | 0.34 | |||
Minimum of Months | 0.595709E+09 | 0.31 | 863.34 | 0.87 | |
Maximum of Months | 0.921476E+09 | 0.41 | 1051.45 | 0.96 |
Report: FanReportMonthly
For: PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.150803E+10 | 0.38 | 1793.17 | 01-JAN-09:01 | 0.92 |
February | 0.125963E+10 | 0.36 | 1793.17 | 01-FEB-08:61 | 0.93 |
March | 0.123504E+10 | 0.33 | 1793.17 | 01-MAR-08:61 | 0.93 |
April | 0.105680E+10 | 0.30 | 1793.17 | 01-APR-08:61 | 0.92 |
May | 0.976240E+09 | 0.28 | 1793.17 | 01-MAY-08:61 | 0.92 |
June | 0.964644E+09 | 0.28 | 1793.17 | 11-JUN-09:02 | 0.91 |
July | 0.973726E+09 | 0.28 | 1793.17 | 01-JUL-08:62 | 0.91 |
August | 0.100833E+10 | 0.29 | 1793.17 | 01-AUG-08:62 | 0.90 |
September | 0.942233E+09 | 0.28 | 1793.17 | 06-SEP-08:62 | 0.91 |
October | 0.102145E+10 | 0.29 | 1793.17 | 16-OCT-08:61 | 0.92 |
November | 0.116831E+10 | 0.32 | 1793.17 | 10-NOV-09:01 | 0.92 |
December | 0.138553E+10 | 0.36 | 1793.17 | 01-DEC-09:01 | 0.92 |
Annual Sum or Average | 0.135000E+11 | 0.31 | |||
Minimum of Months | 0.942233E+09 | 0.28 | 1793.17 | 0.90 | |
Maximum of Months | 0.150803E+10 | 0.38 | 1793.17 | 0.93 |
Report: FanReportMonthly
For: PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.831054E+09 | 0.39 | 992.62 | 01-JAN-09:01 | 0.95 |
February | 0.694556E+09 | 0.37 | 992.62 | 01-FEB-08:61 | 0.96 |
March | 0.682483E+09 | 0.34 | 992.62 | 01-MAR-08:61 | 0.96 |
April | 0.584656E+09 | 0.31 | 992.62 | 01-APR-08:61 | 0.95 |
May | 0.540490E+09 | 0.29 | 992.62 | 01-MAY-08:61 | 0.95 |
June | 0.531408E+09 | 0.29 | 992.62 | 11-JUN-09:02 | 0.94 |
July | 0.536386E+09 | 0.28 | 992.62 | 01-JUL-08:62 | 0.94 |
August | 0.555103E+09 | 0.29 | 992.62 | 01-AUG-08:62 | 0.93 |
September | 0.520752E+09 | 0.29 | 992.62 | 06-SEP-08:62 | 0.94 |
October | 0.564995E+09 | 0.30 | 992.62 | 16-OCT-08:61 | 0.95 |
November | 0.645449E+09 | 0.33 | 992.62 | 10-NOV-09:01 | 0.95 |
December | 0.763870E+09 | 0.37 | 992.62 | 01-DEC-09:01 | 0.95 |
Annual Sum or Average | 0.745120E+10 | 0.32 | |||
Minimum of Months | 0.520752E+09 | 0.28 | 992.62 | 0.93 | |
Maximum of Months | 0.831054E+09 | 0.39 | 992.62 | 0.96 |
Report: FanReportMonthly
For: PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.826544E+09 | 0.39 | 983.02 | 01-JAN-09:01 | 0.95 |
February | 0.690893E+09 | 0.38 | 983.02 | 01-FEB-08:61 | 0.96 |
March | 0.678838E+09 | 0.34 | 983.02 | 01-MAR-08:61 | 0.96 |
April | 0.581181E+09 | 0.31 | 983.02 | 01-APR-08:61 | 0.95 |
May | 0.535717E+09 | 0.29 | 983.02 | 01-MAY-08:61 | 0.95 |
June | 0.526189E+09 | 0.29 | 983.02 | 11-JUN-09:02 | 0.94 |
July | 0.530935E+09 | 0.28 | 983.02 | 01-JUL-08:62 | 0.94 |
August | 0.549598E+09 | 0.29 | 983.02 | 01-AUG-08:62 | 0.93 |
September | 0.516081E+09 | 0.29 | 983.02 | 06-SEP-08:62 | 0.94 |
October | 0.561348E+09 | 0.30 | 983.02 | 16-OCT-08:61 | 0.95 |
November | 0.641768E+09 | 0.33 | 983.02 | 10-NOV-09:01 | 0.95 |
December | 0.759684E+09 | 0.37 | 983.02 | 01-DEC-09:01 | 0.95 |
Annual Sum or Average | 0.739878E+10 | 0.32 | |||
Minimum of Months | 0.516081E+09 | 0.28 | 983.02 | 0.93 | |
Maximum of Months | 0.826544E+09 | 0.39 | 983.02 | 0.96 |
Report: FanReportMonthly
For: PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.825091E+09 | 0.40 | 966.58 | 01-JAN-09:01 | 0.95 |
February | 0.690044E+09 | 0.38 | 966.58 | 01-FEB-08:61 | 0.96 |
March | 0.677636E+09 | 0.34 | 966.58 | 01-MAR-08:61 | 0.96 |
April | 0.578709E+09 | 0.31 | 966.58 | 01-APR-08:61 | 0.95 |
May | 0.528300E+09 | 0.29 | 966.58 | 01-MAY-08:61 | 0.95 |
June | 0.517255E+09 | 0.29 | 966.58 | 11-JUN-09:02 | 0.94 |
July | 0.521404E+09 | 0.28 | 966.58 | 01-JUL-08:62 | 0.94 |
August | 0.540181E+09 | 0.29 | 966.58 | 01-AUG-08:62 | 0.93 |
September | 0.508506E+09 | 0.29 | 966.58 | 07-SEP-08:62 | 0.94 |
October | 0.557186E+09 | 0.30 | 966.58 | 08-OCT-09:01 | 0.95 |
November | 0.638970E+09 | 0.34 | 966.58 | 10-NOV-09:01 | 0.95 |
December | 0.758309E+09 | 0.38 | 966.58 | 01-DEC-08:61 | 0.95 |
Annual Sum or Average | 0.734159E+10 | 0.33 | |||
Minimum of Months | 0.508506E+09 | 0.28 | 966.58 | 0.93 | |
Maximum of Months | 0.825091E+09 | 0.40 | 966.58 | 0.96 |
Report: FanReportMonthly
For: PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.100582E+10 | 0.54 | 1104.34 | 01-JAN-09:01 | 0.95 |
February | 0.835671E+09 | 0.47 | 1104.34 | 01-FEB-08:61 | 0.96 |
March | 0.810282E+09 | 0.39 | 1104.34 | 01-MAR-08:61 | 0.96 |
April | 0.683816E+09 | 0.33 | 1104.34 | 01-APR-07:02 | 0.95 |
May | 0.609958E+09 | 0.29 | 1104.34 | 01-MAY-08:61 | 0.95 |
June | 0.587199E+09 | 0.29 | 1104.34 | 11-JUN-09:02 | 0.94 |
July | 0.590082E+09 | 0.28 | 1104.34 | 01-JUL-08:62 | 0.94 |
August | 0.611072E+09 | 0.29 | 1104.34 | 01-AUG-08:62 | 0.93 |
September | 0.582088E+09 | 0.29 | 1104.34 | 08-SEP-08:62 | 0.94 |
October | 0.645774E+09 | 0.30 | 1104.34 | 06-OCT-08:62 | 0.95 |
November | 0.753191E+09 | 0.38 | 1104.34 | 10-NOV-09:01 | 0.95 |
December | 0.904722E+09 | 0.43 | 1104.34 | 01-DEC-08:61 | 0.95 |
Annual Sum or Average | 0.861967E+10 | 0.36 | |||
Minimum of Months | 0.582088E+09 | 0.28 | 1104.34 | 0.93 | |
Maximum of Months | 0.100582E+10 | 0.54 | 1104.34 | 0.96 |
Report: ZoneTemperatureOscillationReportMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 2.43 | 0.37 |
February | 1.94 | 0.33 |
March | 1.91 | 0.43 |
April | 0.85 | 0.91 |
May | 0.39 | 1.50 |
June | 0.81 | 1.19 |
July | 0.08 | 0.00 |
August | 0.22 | 0.56 |
September | 0.47 | 1.06 |
October | 0.61 | 0.68 |
November | 1.22 | 0.10 |
December | 3.74 | 0.52 |
Annual Sum or Average | 14.67 | 0.53 |
Minimum of Months | 0.08 | 0.00 |
Maximum of Months | 3.74 | 1.50 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.65 | 0.00 |
February | 0.40 | 0.00 |
March | 0.53 | 3.32 |
April | 1.50 | 3.93 |
May | 6.39 | 6.19 |
June | 16.10 | 3.75 |
July | 30.14 | 4.05 |
August | 21.78 | 4.29 |
September | 13.96 | 5.02 |
October | 2.47 | 3.75 |
November | 0.56 | 4.27 |
December | 0.65 | 0.58 |
Annual Sum or Average | 95.11 | 4.26 |
Minimum of Months | 0.40 | 0.00 |
Maximum of Months | 30.14 | 6.19 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 1.02 | 0.00 |
February | 0.43 | 0.00 |
March | 0.03 | 0.00 |
April | 0.53 | 0.63 |
May | 2.36 | 0.75 |
June | 2.40 | 0.72 |
July | 0.71 | 0.75 |
August | 1.01 | 0.75 |
September | 1.74 | 0.75 |
October | 1.03 | 0.75 |
November | 0.67 | 0.56 |
December | 0.31 | 0.00 |
Annual Sum or Average | 12.23 | 0.62 |
Minimum of Months | 0.03 | 0.00 |
Maximum of Months | 2.40 | 0.75 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 1.26 | 0.00 |
February | 0.53 | 0.00 |
March | 0.03 | 0.00 |
April | 0.53 | 0.63 |
May | 2.19 | 0.75 |
June | 2.32 | 0.72 |
July | 0.88 | 0.75 |
August | 0.93 | 0.75 |
September | 1.51 | 0.75 |
October | 0.78 | 0.75 |
November | 0.66 | 0.47 |
December | 0.44 | 0.00 |
Annual Sum or Average | 12.06 | 0.58 |
Minimum of Months | 0.03 | 0.00 |
Maximum of Months | 2.32 | 0.75 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 1.49 | 0.00 |
February | 0.56 | 0.00 |
March | 0.09 | 0.00 |
April | 0.53 | 0.63 |
May | 1.97 | 0.75 |
June | 2.29 | 0.75 |
July | 0.57 | 0.75 |
August | 0.76 | 0.75 |
September | 1.68 | 0.75 |
October | 0.42 | 0.75 |
November | 0.51 | 0.29 |
December | 0.60 | 0.00 |
Annual Sum or Average | 11.48 | 0.54 |
Minimum of Months | 0.09 | 0.00 |
Maximum of Months | 2.29 | 0.75 |
Report: ZoneTemperatureOscillationReportMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 2.42 | 0.00 |
February | 1.09 | 0.00 |
March | 0.26 | 0.00 |
April | 0.26 | 2.26 |
May | 0.25 | 3.30 |
June | 1.64 | 3.30 |
July | 0.28 | 3.30 |
August | 0.44 | 2.27 |
September | 0.37 | 3.30 |
October | 0.08 | 3.30 |
November | 0.63 | 0.00 |
December | 1.77 | 0.00 |
Annual Sum or Average | 9.50 | 1.08 |
Minimum of Months | 0.08 | 0.00 |
Maximum of Months | 2.42 | 3.30 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 1.69 | 0.00 |
February | 0.99 | 0.00 |
March | 0.22 | 0.00 |
April | 0.26 | 1.13 |
May | 0.25 | 1.65 |
June | 1.17 | 1.65 |
July | 0.28 | 1.65 |
August | 0.19 | 1.18 |
September | 0.21 | 1.65 |
October | 0.08 | 1.65 |
November | 0.35 | 0.00 |
December | 1.13 | 0.00 |
Annual Sum or Average | 6.83 | 0.56 |
Minimum of Months | 0.08 | 0.00 |
Maximum of Months | 1.69 | 1.65 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 1.80 | 0.00 |
February | 0.99 | 0.00 |
March | 0.26 | 0.00 |
April | 0.18 | 1.65 |
May | 0.08 | 1.65 |
June | 1.08 | 1.65 |
July | 0.28 | 1.65 |
August | 0.14 | 1.65 |
September | 0.21 | 1.65 |
October | 0.08 | 1.65 |
November | 0.35 | 0.00 |
December | 1.17 | 0.00 |
Annual Sum or Average | 6.64 | 0.51 |
Minimum of Months | 0.08 | 0.00 |
Maximum of Months | 1.80 | 1.65 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 2.01 | 0.00 |
February | 1.24 | 0.00 |
March | 0.44 | 0.00 |
April | 0.12 | 1.65 |
May | 0.00 | 0.00 |
June | 1.00 | 1.65 |
July | 0.23 | 1.65 |
August | 0.17 | 1.65 |
September | 0.21 | 1.65 |
October | 0.00 | 0.00 |
November | 0.59 | 0.00 |
December | 1.89 | 0.00 |
Annual Sum or Average | 7.90 | 0.36 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 2.01 | 1.65 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 4.34 | 0.00 |
February | 2.89 | 0.00 |
March | 2.29 | 0.00 |
April | 0.85 | 0.08 |
May | 0.22 | 0.62 |
June | 1.00 | 1.65 |
July | 0.28 | 1.65 |
August | 0.11 | 1.65 |
September | 0.21 | 1.65 |
October | 0.08 | 1.65 |
November | 2.24 | 0.00 |
December | 3.89 | 0.00 |
Annual Sum or Average | 18.40 | 0.16 |
Minimum of Months | 0.08 | 0.00 |
Maximum of Months | 4.34 | 1.65 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_1:1
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.201461E+10 | 0.458303E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.169359E+10 | 0.327843E+11 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.165120E+10 | 0.212378E+11 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.186391E+10 | 0.104363E+11 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.207681E+10 | 0.546377E+09 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.474614E+10 | 31651706.42 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.607772E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.578522E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.346396E+10 | 0.519742E+09 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.141407E+10 | 0.417358E+10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.157699E+10 | 0.194849E+11 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.187077E+10 | 0.358962E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.342350E+11 | 0.170941E+12 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.141407E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.607772E+10 | 0.458303E+11 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_2:2
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.838489E+09 | 0.171006E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.701222E+09 | 0.118953E+11 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.691483E+09 | 0.706603E+10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.897876E+09 | 0.321585E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.121919E+10 | 82826949.87 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.270819E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.355084E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.335440E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.196443E+10 | 42496871.37 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.630535E+09 | 0.790483E+09 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.663340E+09 | 0.671616E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.770264E+09 | 0.130764E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.179903E+11 | 0.599861E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.630535E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.355084E+10 | 0.171006E+11 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_3:3
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.908858E+09 | 0.188978E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.763345E+09 | 0.133436E+11 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.755240E+09 | 0.841683E+10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.827859E+09 | 0.402337E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.963624E+09 | 0.179888E+09 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.204850E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.256522E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.258257E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.150174E+10 | 0.132380E+09 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.644047E+09 | 0.150012E+10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.715665E+09 | 0.783336E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.839228E+09 | 0.146878E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.151159E+11 | 0.690152E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.644047E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.258257E+10 | 0.188978E+11 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_4:4
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.910459E+09 | 0.192699E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.764207E+09 | 0.136405E+11 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.755600E+09 | 0.870262E+10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.821318E+09 | 0.421337E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.943568E+09 | 0.211038E+09 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.203657E+10 | 1862270.70 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.256025E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.257357E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.149533E+10 | 0.166325E+09 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.642357E+09 | 0.172302E+10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.715984E+09 | 0.810337E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.840145E+09 | 0.150128E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.150594E+11 | 0.710448E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.642357E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.257357E+10 | 0.192699E+11 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_5:5
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.921476E+09 | 0.197739E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.773298E+09 | 0.140493E+11 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.764669E+09 | 0.910695E+10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.818345E+09 | 0.447457E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.919303E+09 | 0.249845E+09 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.199670E+10 | 15104413.14 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.251564E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.252578E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.147472E+10 | 0.213749E+09 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.647174E+09 | 0.197580E+10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.724033E+09 | 0.845166E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.850166E+09 | 0.154631E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.149313E+11 | 0.737740E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.647174E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.252578E+10 | 0.197739E+11 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_6:6
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.150803E+10 | 0.373318E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.125963E+10 | 0.265846E+11 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.123504E+10 | 0.174675E+11 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.132122E+10 | 0.867259E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.147169E+10 | 0.531675E+09 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.341207E+10 | 84152514.28 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.435433E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.436745E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.249988E+10 | 0.546466E+09 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.103266E+10 | 0.432670E+10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.116831E+10 | 0.162696E+11 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.138553E+10 | 0.293933E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.250158E+11 | 0.141208E+12 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.103266E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.436745E+10 | 0.373318E+11 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_7:7
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.831054E+09 | 0.193569E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.694556E+09 | 0.137899E+11 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.682483E+09 | 0.908929E+10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.718165E+09 | 0.452774E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.785624E+09 | 0.284479E+09 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.178501E+10 | 47595759.34 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.227393E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.227702E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.132043E+10 | 0.285014E+09 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.569999E+09 | 0.224169E+10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.645449E+09 | 0.845351E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.763870E+09 | 0.152324E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.133476E+11 | 0.733085E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.569999E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.227702E+10 | 0.193569E+11 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_8:8
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.826544E+09 | 0.194602E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.690893E+09 | 0.138968E+11 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.678838E+09 | 0.922377E+10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.709688E+09 | 0.464119E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.766882E+09 | 0.312340E+09 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.175678E+10 | 60677275.84 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.224134E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.224546E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.130331E+10 | 0.310049E+09 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.565886E+09 | 0.234565E+10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.641768E+09 | 0.856707E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.759684E+09 | 0.153429E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.131871E+11 | 0.741606E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.565886E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.224546E+10 | 0.194602E+11 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_9:9
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.825091E+09 | 0.200253E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.690044E+09 | 0.144229E+11 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.677636E+09 | 0.978511E+10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.695490E+09 | 0.506496E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.729947E+09 | 0.413853E+09 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.169214E+10 | 0.103411E+09 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.216867E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.217784E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.126900E+10 | 0.378864E+09 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.560718E+09 | 0.266178E+10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.638970E+09 | 0.899022E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.758309E+09 | 0.158979E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.128839E+11 | 0.777443E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.560718E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.217784E+10 | 0.200253E+11 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_10:10
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.100582E+10 | 0.246112E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.835671E+09 | 0.179750E+11 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.810282E+09 | 0.126324E+11 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.787342E+09 | 0.687659E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.775386E+09 | 0.847064E+09 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.169482E+10 | 0.239773E+09 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.217788E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.219383E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.133869E+10 | 0.566021E+09 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.648236E+09 | 0.347148E+10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.753191E+09 | 0.110046E+11 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.904722E+09 | 0.192284E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.139259E+11 | 0.974524E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.648236E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.219383E+10 | 0.246112E+11 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_1:1
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.201461E+10 | 0.00 | 0.366642E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.169359E+10 | 0.00 | 0.262274E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.165120E+10 | 0.00 | 0.169903E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.144800E+10 | 0.165800E+10 | 0.834904E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.134171E+10 | 0.290876E+10 | 0.437102E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.132061E+10 | 0.140781E+11 | 25321365.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.136171E+10 | 0.199147E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.137148E+10 | 0.184984E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.131126E+10 | 0.867632E+10 | 0.415793E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.139495E+10 | 70410732.95 | 0.333886E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.157699E+10 | 0.00 | 0.155879E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.187077E+10 | 0.00 | 0.287170E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.183569E+11 | 0.658046E+11 | 0.136753E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.131126E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.201461E+10 | 0.199147E+11 | 0.366642E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_2:2
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.838489E+09 | 0.00 | 0.136805E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.701222E+09 | 0.00 | 0.951623E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.691450E+09 | 108195.99 | 0.565282E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.627038E+09 | 0.104081E+10 | 0.257268E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.693385E+09 | 0.201069E+10 | 66261559.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.677012E+09 | 0.803559E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.700933E+09 | 0.113639E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.718189E+09 | 0.105832E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.659771E+09 | 0.498064E+10 | 33997497.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.614694E+09 | 58690887.04 | 0.632386E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.663027E+09 | 1039923.68 | 0.537293E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.770264E+09 | 0.00 | 0.104611E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.835547E+10 | 0.380747E+11 | 0.479889E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.614694E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.838489E+09 | 0.113639E+11 | 0.136805E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_3:3
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.908858E+09 | 0.00 | 0.151183E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.763345E+09 | 0.00 | 0.106749E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.755240E+09 | 0.00 | 0.673346E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.655419E+09 | 0.688269E+09 | 0.321870E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.619068E+09 | 0.135769E+10 | 0.143911E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.610392E+09 | 0.590943E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.617665E+09 | 0.819637E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.637730E+09 | 0.811151E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.596134E+09 | 0.362917E+10 | 0.105904E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.633728E+09 | 37991504.60 | 0.120010E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.715665E+09 | 0.00 | 0.626669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.839228E+09 | 0.00 | 0.117502E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.835247E+10 | 0.279304E+11 | 0.552121E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.596134E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.908858E+09 | 0.819637E+10 | 0.151183E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_4:4
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.910459E+09 | 0.00 | 0.154159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.764207E+09 | 0.00 | 0.109124E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.755600E+09 | 0.00 | 0.696210E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.654607E+09 | 0.664338E+09 | 0.337070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.615712E+09 | 0.128972E+10 | 0.168830E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.607165E+09 | 0.587786E+10 | 1489816.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.614439E+09 | 0.819866E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.634315E+09 | 0.809348E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.593127E+09 | 0.361923E+10 | 0.133060E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.633410E+09 | 32811961.15 | 0.137842E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.715984E+09 | 0.00 | 0.648269E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.840145E+09 | 0.00 | 0.120103E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.833917E+10 | 0.277761E+11 | 0.568358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.593127E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.910459E+09 | 0.819866E+10 | 0.154159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_5:5
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.921476E+09 | 0.00 | 0.158191E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.773298E+09 | 0.00 | 0.112394E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.764669E+09 | 0.00 | 0.728556E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.661193E+09 | 0.622663E+09 | 0.357966E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.618755E+09 | 0.117522E+10 | 0.199876E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.607996E+09 | 0.569176E+10 | 12083530.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.615384E+09 | 0.797759E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.635131E+09 | 0.786260E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.595709E+09 | 0.351384E+10 | 0.170999E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.639880E+09 | 26593266.70 | 0.158064E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.724033E+09 | 0.00 | 0.676133E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.850166E+09 | 0.00 | 0.123705E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.840769E+10 | 0.268703E+11 | 0.590192E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.595709E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.921476E+09 | 0.797759E+10 | 0.158191E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_6:6
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.150803E+10 | 0.00 | 0.298654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.125963E+10 | 0.00 | 0.212677E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.123504E+10 | 0.00 | 0.139740E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.105680E+10 | 0.104902E+10 | 0.693808E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.976240E+09 | 0.193078E+10 | 0.425340E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.964644E+09 | 0.100403E+11 | 67322011.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.973726E+09 | 0.142323E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.100833E+10 | 0.139878E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.942233E+09 | 0.624030E+10 | 0.437173E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.102145E+10 | 40665888.26 | 0.346136E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.116831E+10 | 0.00 | 0.130156E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.138553E+10 | 0.00 | 0.235146E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.135000E+11 | 0.475212E+11 | 0.112967E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.942233E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.150803E+10 | 0.142323E+11 | 0.298654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_7:7
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.831054E+09 | 0.00 | 0.154855E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.694556E+09 | 0.00 | 0.110319E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.682483E+09 | 0.00 | 0.727143E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.584656E+09 | 0.526164E+09 | 0.362219E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.540490E+09 | 0.949479E+09 | 0.227584E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.531408E+09 | 0.511578E+10 | 38076607.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.536386E+09 | 0.727164E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.555103E+09 | 0.713056E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.520752E+09 | 0.318758E+10 | 0.228011E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.564995E+09 | 18085711.60 | 0.179335E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.645449E+09 | 0.00 | 0.676281E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.763870E+09 | 0.00 | 0.121859E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.745120E+10 | 0.241993E+11 | 0.586468E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.520752E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.831054E+09 | 0.727164E+10 | 0.154855E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_8:8
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.826544E+09 | 0.00 | 0.155681E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.690893E+09 | 0.00 | 0.111175E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.678838E+09 | 0.00 | 0.737902E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.581181E+09 | 0.505240E+09 | 0.371295E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.535717E+09 | 0.892693E+09 | 0.249872E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.526189E+09 | 0.501839E+10 | 48541820.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.530935E+09 | 0.715354E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.549598E+09 | 0.701887E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.516081E+09 | 0.313646E+10 | 0.248040E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.561348E+09 | 16367072.05 | 0.187652E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.641768E+09 | 0.00 | 0.685365E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.759684E+09 | 0.00 | 0.122743E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.739878E+10 | 0.237415E+11 | 0.593285E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.516081E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.826544E+09 | 0.715354E+10 | 0.155681E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_9:9
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.825091E+09 | 0.00 | 0.160202E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.690044E+09 | 0.00 | 0.115383E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.677636E+09 | 0.00 | 0.782809E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.578709E+09 | 0.455772E+09 | 0.405197E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.528300E+09 | 0.773385E+09 | 0.331082E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.517255E+09 | 0.478290E+10 | 82729198.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.521404E+09 | 0.687860E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.540181E+09 | 0.676909E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.508506E+09 | 0.302727E+10 | 0.303091E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.557186E+09 | 12670743.19 | 0.212943E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.638970E+09 | 0.00 | 0.719218E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.758309E+09 | 0.00 | 0.127183E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.734159E+10 | 0.226997E+11 | 0.621954E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.508506E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.825091E+09 | 0.687860E+10 | 0.160202E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_10:10
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.100582E+10 | 0.00 | 0.196889E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.835671E+09 | 0.00 | 0.143800E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.810282E+09 | 0.00 | 0.101059E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.683816E+09 | 0.391035E+09 | 0.550127E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.609958E+09 | 0.618910E+09 | 0.677651E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.587199E+09 | 0.441338E+10 | 0.191819E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.590082E+09 | 0.648684E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.611072E+09 | 0.642914E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.582088E+09 | 0.296126E+10 | 0.452817E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.645774E+09 | 8726361.85 | 0.277718E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.753191E+09 | 0.00 | 0.880367E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.904722E+09 | 0.00 | 0.153827E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.861967E+10 | 0.213093E+11 | 0.779619E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.582088E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.100582E+10 | 0.648684E+10 | 0.196889E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_1:1
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.458303E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.169359E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.327843E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.165120E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.212378E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.144800E+10 | 0.00 | 0.00 | 0.00 | 0.415912E+09 | 0.00 | 0.104363E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.134171E+10 | 0.00 | 0.00 | 0.00 | 0.735099E+09 | 0.00 | 0.546377E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.132061E+10 | 0.00 | 0.00 | 0.00 | 0.342553E+10 | 0.00 | 31651706.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.136171E+10 | 0.00 | 0.00 | 0.00 | 0.471600E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.137148E+10 | 0.00 | 0.00 | 0.00 | 0.441373E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.131126E+10 | 0.00 | 0.00 | 0.00 | 0.215270E+10 | 0.00 | 0.519742E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.139495E+10 | 0.00 | 0.00 | 0.00 | 19125593.21 | 0.00 | 0.417358E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.157699E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.194849E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.187077E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.358962E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.183569E+11 | 0.00 | 0.00 | 0.00 | 0.158781E+11 | 0.00 | 0.170941E+12 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.131126E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.471600E+10 | 0.00 | 0.458303E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_2:2
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.838489E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171006E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.701222E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118953E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.691450E+09 | 0.00 | 0.00 | 0.00 | 32960.12 | 0.00 | 0.706603E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.627038E+09 | 0.00 | 0.00 | 0.00 | 0.270838E+09 | 0.00 | 0.321585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.693385E+09 | 0.00 | 0.00 | 0.00 | 0.525804E+09 | 0.00 | 82826949.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.677012E+09 | 0.00 | 0.00 | 0.00 | 0.203118E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.700933E+09 | 0.00 | 0.00 | 0.00 | 0.284991E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.718189E+09 | 0.00 | 0.00 | 0.00 | 0.263621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.659771E+09 | 0.00 | 0.00 | 0.00 | 0.130465E+10 | 0.00 | 42496871.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.614694E+09 | 0.00 | 0.00 | 0.00 | 15841046.29 | 0.00 | 0.790483E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.663027E+09 | 0.00 | 0.00 | 0.00 | 313029.60 | 0.00 | 0.671616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.770264E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130764E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.835547E+10 | 0.00 | 0.00 | 0.00 | 0.963478E+10 | 0.00 | 0.599861E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.614694E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.838489E+09 | 0.00 | 0.00 | 0.00 | 0.284991E+10 | 0.00 | 0.171006E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_3:3
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.908858E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188978E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.763345E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133436E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.755240E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.841683E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.655419E+09 | 0.00 | 0.00 | 0.00 | 0.172440E+09 | 0.00 | 0.402337E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.619068E+09 | 0.00 | 0.00 | 0.00 | 0.344556E+09 | 0.00 | 0.179888E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.610392E+09 | 0.00 | 0.00 | 0.00 | 0.143810E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.617665E+09 | 0.00 | 0.00 | 0.00 | 0.194755E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.637730E+09 | 0.00 | 0.00 | 0.00 | 0.194484E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.596134E+09 | 0.00 | 0.00 | 0.00 | 0.905606E+09 | 0.00 | 0.132380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.633728E+09 | 0.00 | 0.00 | 0.00 | 10318712.61 | 0.00 | 0.150012E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.715665E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.783336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.839228E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146878E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.835247E+10 | 0.00 | 0.00 | 0.00 | 0.676342E+10 | 0.00 | 0.690152E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.596134E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.908858E+09 | 0.00 | 0.00 | 0.00 | 0.194755E+10 | 0.00 | 0.188978E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_4:4
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.910459E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192699E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.764207E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136405E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.755600E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.870262E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.654607E+09 | 0.00 | 0.00 | 0.00 | 0.166711E+09 | 0.00 | 0.421337E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.615712E+09 | 0.00 | 0.00 | 0.00 | 0.327856E+09 | 0.00 | 0.211038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.607165E+09 | 0.00 | 0.00 | 0.00 | 0.142940E+10 | 0.00 | 1862270.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.614439E+09 | 0.00 | 0.00 | 0.00 | 0.194581E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.634315E+09 | 0.00 | 0.00 | 0.00 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.593127E+09 | 0.00 | 0.00 | 0.00 | 0.902200E+09 | 0.00 | 0.166325E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.633410E+09 | 0.00 | 0.00 | 0.00 | 8947260.64 | 0.00 | 0.172302E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.715984E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.810337E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.840145E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.833917E+10 | 0.00 | 0.00 | 0.00 | 0.672018E+10 | 0.00 | 0.710448E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.593127E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.910459E+09 | 0.00 | 0.00 | 0.00 | 0.194581E+10 | 0.00 | 0.192699E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_5:5
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.921476E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.197739E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.773298E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140493E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.764669E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.910695E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.661193E+09 | 0.00 | 0.00 | 0.00 | 0.157152E+09 | 0.00 | 0.447457E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.618755E+09 | 0.00 | 0.00 | 0.00 | 0.300547E+09 | 0.00 | 0.249845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.607996E+09 | 0.00 | 0.00 | 0.00 | 0.138871E+10 | 0.00 | 15104413.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.615384E+09 | 0.00 | 0.00 | 0.00 | 0.190026E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.635131E+09 | 0.00 | 0.00 | 0.00 | 0.189065E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.595709E+09 | 0.00 | 0.00 | 0.00 | 0.879008E+09 | 0.00 | 0.213749E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.639880E+09 | 0.00 | 0.00 | 0.00 | 7294169.97 | 0.00 | 0.197580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.724033E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.845166E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.850166E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154631E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.840769E+10 | 0.00 | 0.00 | 0.00 | 0.652362E+10 | 0.00 | 0.737740E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.595709E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.921476E+09 | 0.00 | 0.00 | 0.00 | 0.190026E+10 | 0.00 | 0.197739E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_6:6
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.150803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.373318E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.125963E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.265846E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.123504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174675E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.105680E+10 | 0.00 | 0.00 | 0.00 | 0.264416E+09 | 0.00 | 0.867259E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.976240E+09 | 0.00 | 0.00 | 0.00 | 0.495449E+09 | 0.00 | 0.531675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.964644E+09 | 0.00 | 0.00 | 0.00 | 0.244742E+10 | 0.00 | 84152514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.973726E+09 | 0.00 | 0.00 | 0.00 | 0.338060E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.100833E+10 | 0.00 | 0.00 | 0.00 | 0.335913E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.942233E+09 | 0.00 | 0.00 | 0.00 | 0.155765E+10 | 0.00 | 0.546466E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.102145E+10 | 0.00 | 0.00 | 0.00 | 11207676.17 | 0.00 | 0.432670E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.116831E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162696E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.138553E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.293933E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.135000E+11 | 0.00 | 0.00 | 0.00 | 0.115159E+11 | 0.00 | 0.141208E+12 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.942233E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.150803E+10 | 0.00 | 0.00 | 0.00 | 0.338060E+10 | 0.00 | 0.373318E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_7:7
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.831054E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.193569E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.694556E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137899E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.682483E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.908929E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.584656E+09 | 0.00 | 0.00 | 0.00 | 0.133509E+09 | 0.00 | 0.452774E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.540490E+09 | 0.00 | 0.00 | 0.00 | 0.245134E+09 | 0.00 | 0.284479E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.531408E+09 | 0.00 | 0.00 | 0.00 | 0.125360E+10 | 0.00 | 47595759.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.536386E+09 | 0.00 | 0.00 | 0.00 | 0.173754E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.555103E+09 | 0.00 | 0.00 | 0.00 | 0.172192E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.520752E+09 | 0.00 | 0.00 | 0.00 | 0.799676E+09 | 0.00 | 0.285014E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.564995E+09 | 0.00 | 0.00 | 0.00 | 5003856.83 | 0.00 | 0.224169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.645449E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.845351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.763870E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.152324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.745120E+10 | 0.00 | 0.00 | 0.00 | 0.589639E+10 | 0.00 | 0.733085E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.520752E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.831054E+09 | 0.00 | 0.00 | 0.00 | 0.173754E+10 | 0.00 | 0.193569E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_8:8
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.826544E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.194602E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.690893E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138968E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.678838E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.922377E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.581181E+09 | 0.00 | 0.00 | 0.00 | 0.128506E+09 | 0.00 | 0.464119E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.535717E+09 | 0.00 | 0.00 | 0.00 | 0.231165E+09 | 0.00 | 0.312340E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.526189E+09 | 0.00 | 0.00 | 0.00 | 0.123059E+10 | 0.00 | 60677275.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.530935E+09 | 0.00 | 0.00 | 0.00 | 0.171040E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.549598E+09 | 0.00 | 0.00 | 0.00 | 0.169586E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.516081E+09 | 0.00 | 0.00 | 0.00 | 0.787228E+09 | 0.00 | 0.310049E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.561348E+09 | 0.00 | 0.00 | 0.00 | 4537817.49 | 0.00 | 0.234565E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.641768E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.856707E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.759684E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153429E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.739878E+10 | 0.00 | 0.00 | 0.00 | 0.578828E+10 | 0.00 | 0.741606E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.516081E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.826544E+09 | 0.00 | 0.00 | 0.00 | 0.171040E+10 | 0.00 | 0.194602E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_9:9
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.825091E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.200253E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.690044E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.144229E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.677636E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.978511E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.578709E+09 | 0.00 | 0.00 | 0.00 | 0.116781E+09 | 0.00 | 0.506496E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.528300E+09 | 0.00 | 0.00 | 0.00 | 0.201647E+09 | 0.00 | 0.413853E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.517255E+09 | 0.00 | 0.00 | 0.00 | 0.117489E+10 | 0.00 | 0.103411E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.521404E+09 | 0.00 | 0.00 | 0.00 | 0.164727E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.540181E+09 | 0.00 | 0.00 | 0.00 | 0.163766E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.508506E+09 | 0.00 | 0.00 | 0.00 | 0.760495E+09 | 0.00 | 0.378864E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.557186E+09 | 0.00 | 0.00 | 0.00 | 3532053.77 | 0.00 | 0.266178E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.638970E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.899022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.758309E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158979E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.734159E+10 | 0.00 | 0.00 | 0.00 | 0.554227E+10 | 0.00 | 0.777443E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.508506E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.825091E+09 | 0.00 | 0.00 | 0.00 | 0.164727E+10 | 0.00 | 0.200253E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_10:10
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.100582E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.246112E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.835671E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179750E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.810282E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.683816E+09 | 0.00 | 0.00 | 0.00 | 0.103526E+09 | 0.00 | 0.687659E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.609958E+09 | 0.00 | 0.00 | 0.00 | 0.165429E+09 | 0.00 | 0.847064E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.587199E+09 | 0.00 | 0.00 | 0.00 | 0.110762E+10 | 0.00 | 0.239773E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.590082E+09 | 0.00 | 0.00 | 0.00 | 0.158780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.611072E+09 | 0.00 | 0.00 | 0.00 | 0.158276E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.582088E+09 | 0.00 | 0.00 | 0.00 | 0.756604E+09 | 0.00 | 0.566021E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.645774E+09 | 0.00 | 0.00 | 0.00 | 2461891.59 | 0.00 | 0.347148E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.753191E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110046E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.904722E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192284E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.861967E+10 | 0.00 | 0.00 | 0.00 | 0.530620E+10 | 0.00 | 0.974524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.582088E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.100582E+10 | 0.00 | 0.00 | 0.00 | 0.158780E+10 | 0.00 | 0.246112E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.147335E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.256321E+11 | 0.00 | 0.00 | 0.52 |
February | 0.353770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172917E+11 | 0.00 | 0.00 | 0.53 |
March | 0.607646E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102967E+11 | 0.00 | 0.00 | 0.53 |
April | 0.615278E+10 | 0.447512E+09 | 0.00 | 1000935.05 | 9745543.80 | 0.443070E+10 | 0.421822E+09 | 0.00 | 0.56 |
May | 0.396932E+10 | 0.486733E+09 | 0.00 | 5052924.74 | 1654229.62 | 97718781.12 | 0.249394E+10 | 0.00 | 0.65 |
June | 0.163736E+10 | 0.379978E+10 | 0.00 | 7394144.80 | 12433490.73 | 0.00 | 0.163103E+10 | 0.00 | 0.73 |
July | 17048793.01 | 0.537861E+10 | 0.00 | 10932389.46 | 14010414.05 | 0.00 | 0.168559E+10 | 0.00 | 0.81 |
August | 48403763.06 | 0.443420E+10 | 0.00 | 13535587.17 | 17729559.64 | 0.00 | 0.230822E+10 | 0.00 | 0.82 |
September | 0.307195E+10 | 0.138623E+10 | 0.00 | 11762244.59 | 3736297.30 | 28236972.04 | 0.294412E+10 | 0.00 | 0.71 |
October | 0.994065E+10 | 0.00 | 0.00 | 757369.12 | 0.00 | 0.358750E+09 | 0.674260E+09 | 0.00 | 0.54 |
November | 0.694890E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.954723E+10 | 0.00 | 0.00 | 0.53 |
December | 0.459283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185711E+11 | 0.00 | 0.00 | 0.52 |
Annual Sum or Average | 0.474667E+11 | 0.159331E+11 | 0.00 | 50435594.92 | 59309535.15 | 0.862543E+11 | 0.121590E+11 | 0.00 | 0.62 |
Minimum of Months | 17048793.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.52 |
Maximum of Months | 0.994065E+10 | 0.537861E+10 | 0.00 | 13535587.17 | 17729559.64 | 0.256321E+11 | 0.294412E+10 | 0.00 | 0.82 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.824527E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.919771E+10 | 0.00 | 0.00 | 0.39 |
February | 0.151416E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.612212E+10 | 0.00 | 0.00 | 0.39 |
March | 0.264019E+10 | 0.00 | 0.00 | 43175.62 | 0.00 | 0.331701E+10 | 35996912.38 | 0.00 | 0.40 |
April | 0.232044E+10 | 0.235474E+09 | 0.00 | 598673.75 | 3471961.77 | 0.147603E+10 | 0.345521E+09 | 0.00 | 0.45 |
May | 0.110514E+10 | 0.292706E+09 | 0.00 | 3717235.84 | 1083632.91 | 2848390.62 | 0.211947E+10 | 0.00 | 0.67 |
June | 0.475865E+09 | 0.194433E+10 | 0.00 | 3053924.51 | 7849621.14 | 0.00 | 0.982700E+09 | 0.00 | 0.68 |
July | 3360734.74 | 0.288914E+10 | 0.00 | 2867987.23 | 16731530.16 | 0.00 | 0.606840E+09 | 0.00 | 0.75 |
August | 6884277.37 | 0.237124E+10 | 0.00 | 4336059.16 | 11225239.19 | 0.00 | 0.845604E+09 | 0.00 | 0.79 |
September | 0.905059E+09 | 0.753062E+09 | 0.00 | 4643951.56 | 4158354.53 | 1058644.09 | 0.180765E+10 | 0.00 | 0.67 |
October | 0.348187E+10 | 0.00 | 0.00 | 971002.55 | 0.00 | 16262934.00 | 0.708512E+09 | 0.00 | 0.44 |
November | 0.260449E+10 | 0.00 | 0.00 | 156370.21 | 0.00 | 0.329603E+10 | 0.125013E+09 | 0.00 | 0.40 |
December | 0.188472E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.649279E+10 | 0.00 | 0.00 | 0.38 |
Annual Sum or Average | 0.177667E+11 | 0.848596E+10 | 0.00 | 20388380.43 | 44520339.69 | 0.299219E+11 | 0.757730E+10 | 0.00 | 0.53 |
Minimum of Months | 3360734.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.348187E+10 | 0.288914E+10 | 0.00 | 4643951.56 | 16731530.16 | 0.919771E+10 | 0.211947E+10 | 0.00 | 0.79 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.212561E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104657E+11 | 0.00 | 0.00 | 0.41 |
February | 0.943812E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.719249E+10 | 0.00 | 0.00 | 0.41 |
March | 0.213346E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.427638E+10 | 0.00 | 0.00 | 0.42 |
April | 0.227432E+10 | 0.174009E+09 | 0.00 | 244915.77 | 13131679.30 | 0.184028E+10 | 0.142575E+09 | 0.00 | 0.44 |
May | 0.151648E+10 | 0.231579E+09 | 0.00 | 1500762.92 | 7030455.95 | 22001653.73 | 0.923399E+09 | 0.00 | 0.54 |
June | 0.626868E+09 | 0.147867E+10 | 0.00 | 2121816.71 | 90201325.89 | 0.00 | 0.651162E+09 | 0.00 | 0.59 |
July | 40521789.88 | 0.204358E+10 | 0.00 | 2774377.63 | 0.119682E+09 | 0.00 | 0.498591E+09 | 0.00 | 0.62 |
August | 92246211.61 | 0.188531E+10 | 0.00 | 3122731.20 | 75826022.01 | 0.00 | 0.558784E+09 | 0.00 | 0.65 |
September | 0.119052E+10 | 0.606520E+09 | 0.00 | 2714692.26 | 20780117.29 | 21944946.18 | 0.102784E+10 | 0.00 | 0.56 |
October | 0.372287E+10 | 0.00 | 0.00 | 224890.36 | 0.00 | 0.163934E+09 | 0.165595E+09 | 0.00 | 0.43 |
November | 0.217448E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.407576E+10 | 0.00 | 0.00 | 0.41 |
December | 0.958456E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.796328E+10 | 0.00 | 0.00 | 0.41 |
Annual Sum or Average | 0.158866E+11 | 0.641967E+10 | 0.00 | 12704186.86 | 0.326651E+09 | 0.360218E+11 | 0.396795E+10 | 0.00 | 0.49 |
Minimum of Months | 40521789.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.372287E+10 | 0.204358E+10 | 0.00 | 3122731.20 | 0.119682E+09 | 0.104657E+11 | 0.102784E+10 | 0.00 | 0.65 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.199270E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104789E+11 | 0.00 | 0.00 | 0.41 |
February | 0.740018E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.739598E+10 | 0.00 | 0.00 | 0.41 |
March | 0.188768E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.451845E+10 | 0.00 | 0.00 | 0.42 |
April | 0.208782E+10 | 0.171119E+09 | 0.00 | 225655.01 | 13152445.85 | 0.202407E+10 | 0.135245E+09 | 0.00 | 0.44 |
May | 0.155803E+10 | 0.224529E+09 | 0.00 | 1285290.14 | 6889673.73 | 32349298.85 | 0.813563E+09 | 0.00 | 0.53 |
June | 0.622015E+09 | 0.147625E+10 | 0.00 | 2086679.60 | 89769898.23 | 0.00 | 0.642836E+09 | 0.00 | 0.59 |
July | 40503228.60 | 0.204674E+10 | 0.00 | 2793049.46 | 0.119335E+09 | 0.00 | 0.493913E+09 | 0.00 | 0.62 |
August | 89838785.13 | 0.188321E+10 | 0.00 | 3116972.33 | 75237659.15 | 0.00 | 0.557366E+09 | 0.00 | 0.65 |
September | 0.119645E+10 | 0.607058E+09 | 0.00 | 2661079.67 | 20766762.74 | 29413783.53 | 0.993947E+09 | 0.00 | 0.56 |
October | 0.364464E+10 | 0.00 | 0.00 | 176987.95 | 0.00 | 0.242036E+09 | 0.130518E+09 | 0.00 | 0.43 |
November | 0.197546E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.425898E+10 | 0.00 | 0.00 | 0.41 |
December | 0.685974E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.823545E+10 | 0.00 | 0.00 | 0.41 |
Annual Sum or Average | 0.147277E+11 | 0.640890E+10 | 0.00 | 12345714.15 | 0.325151E+09 | 0.372156E+11 | 0.376739E+10 | 0.00 | 0.49 |
Minimum of Months | 40503228.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.364464E+10 | 0.204674E+10 | 0.00 | 3116972.33 | 0.119335E+09 | 0.104789E+11 | 0.993947E+09 | 0.00 | 0.65 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.158718E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105194E+11 | 0.00 | 0.00 | 0.41 |
February | 0.547854E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.758808E+10 | 0.00 | 0.00 | 0.41 |
March | 0.152706E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.487502E+10 | 0.00 | 0.00 | 0.42 |
April | 0.185036E+10 | 0.164791E+09 | 0.00 | 196107.24 | 14691059.35 | 0.226209E+10 | 0.122782E+09 | 0.00 | 0.44 |
May | 0.163558E+10 | 0.211795E+09 | 0.00 | 979372.95 | 6838700.46 | 54244495.89 | 0.634117E+09 | 0.00 | 0.51 |
June | 0.659343E+09 | 0.145098E+10 | 0.00 | 1921019.77 | 89690700.74 | 0.00 | 0.597176E+09 | 0.00 | 0.59 |
July | 41258019.07 | 0.200552E+10 | 0.00 | 2620200.35 | 0.118838E+09 | 0.00 | 0.500440E+09 | 0.00 | 0.62 |
August | 98018876.53 | 0.184316E+10 | 0.00 | 2965715.89 | 75017613.48 | 0.00 | 0.562899E+09 | 0.00 | 0.65 |
September | 0.124531E+10 | 0.600372E+09 | 0.00 | 2449794.39 | 20733742.35 | 28931291.21 | 0.919134E+09 | 0.00 | 0.55 |
October | 0.353696E+10 | 0.00 | 0.00 | 128416.24 | 0.00 | 0.351857E+09 | 99890669.07 | 0.00 | 0.42 |
November | 0.170157E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.451915E+10 | 0.00 | 0.00 | 0.41 |
December | 0.415047E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.850617E+10 | 0.00 | 0.00 | 0.41 |
Annual Sum or Average | 0.134171E+11 | 0.627662E+10 | 0.00 | 11260626.84 | 0.325810E+09 | 0.387049E+11 | 0.343644E+10 | 0.00 | 0.49 |
Minimum of Months | 41258019.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.353696E+10 | 0.200552E+10 | 0.00 | 2965715.89 | 0.118838E+09 | 0.105194E+11 | 0.919134E+09 | 0.00 | 0.65 |
Report: MechanicalVentilationLoadsMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.179437E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.194209E+11 | 0.00 | 0.00 | 0.38 |
February | 0.484792E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.144561E+11 | 0.00 | 0.00 | 0.38 |
March | 0.202691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.972167E+10 | 0.00 | 0.00 | 0.39 |
April | 0.294008E+10 | 0.304545E+09 | 0.00 | 312272.06 | 33681903.68 | 0.453608E+10 | 0.243382E+09 | 0.00 | 0.40 |
May | 0.311151E+10 | 0.368187E+09 | 0.00 | 1135237.52 | 2082329.00 | 0.144571E+09 | 0.754289E+09 | 0.00 | 0.44 |
June | 0.112250E+10 | 0.268674E+10 | 0.00 | 2833479.08 | 0.103274E+09 | 2328162.76 | 0.100896E+10 | 0.00 | 0.51 |
July | 35256571.62 | 0.384697E+10 | 0.00 | 3202628.82 | 88607860.42 | 0.00 | 0.780827E+09 | 0.00 | 0.52 |
August | 55722759.53 | 0.344288E+10 | 0.00 | 4369308.92 | 55803014.13 | 0.00 | 0.942284E+09 | 0.00 | 0.56 |
September | 0.227278E+10 | 0.114545E+10 | 0.00 | 3469927.11 | 26722857.93 | 31513709.79 | 0.144803E+10 | 0.00 | 0.48 |
October | 0.633359E+10 | 0.00 | 30090.46 | 155227.81 | 16543.83 | 0.797457E+09 | 0.112114E+09 | 8925.46 | 0.39 |
November | 0.255351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.887520E+10 | 0.00 | 54418.72 | 0.38 |
December | 0.213651E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161865E+11 | 0.00 | 0.00 | 0.37 |
Annual Sum or Average | 0.213297E+11 | 0.117948E+11 | 30090.46 | 15478081.33 | 0.310188E+09 | 0.741724E+11 | 0.528988E+10 | 63344.18 | 0.43 |
Minimum of Months | 35256571.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.37 |
Maximum of Months | 0.633359E+10 | 0.384697E+10 | 30090.46 | 4369308.92 | 0.103274E+09 | 0.194209E+11 | 0.144803E+10 | 54418.72 | 0.56 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 72276024.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.972188E+10 | 0.00 | 0.00 | 0.38 |
February | 0.203260E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.726176E+10 | 0.00 | 0.00 | 0.38 |
March | 0.908989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.495848E+10 | 0.00 | 0.00 | 0.39 |
April | 0.137684E+10 | 0.150509E+09 | 0.00 | 147664.59 | 17704119.14 | 0.236091E+10 | 0.117809E+09 | 0.00 | 0.40 |
May | 0.156552E+10 | 0.180454E+09 | 0.00 | 501433.57 | 1144845.91 | 0.101348E+09 | 0.319702E+09 | 0.00 | 0.44 |
June | 0.562679E+09 | 0.133740E+10 | 0.00 | 1413207.44 | 53585213.24 | 1800817.15 | 0.527978E+09 | 0.00 | 0.52 |
July | 17548432.05 | 0.191956E+10 | 0.00 | 1599252.01 | 43709024.16 | 0.00 | 0.420865E+09 | 0.00 | 0.54 |
August | 27731726.10 | 0.171440E+10 | 0.00 | 2223515.45 | 27322188.66 | 0.00 | 0.515887E+09 | 0.00 | 0.58 |
September | 0.113855E+10 | 0.573457E+09 | 0.00 | 1737985.31 | 14264499.22 | 22869604.20 | 0.742374E+09 | 0.00 | 0.49 |
October | 0.301041E+10 | 0.00 | 14101.13 | 71644.56 | 6882.16 | 0.550147E+09 | 52610700.57 | 5328.93 | 0.39 |
November | 0.120070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.450683E+10 | 0.00 | 26777.00 | 0.38 |
December | 57132597.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.813683E+10 | 0.00 | 0.00 | 0.37 |
Annual Sum or Average | 0.101416E+11 | 0.587579E+10 | 14101.13 | 7694702.91 | 0.157737E+09 | 0.376229E+11 | 0.269723E+10 | 32105.93 | 0.44 |
Minimum of Months | 17548432.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.37 |
Maximum of Months | 0.301041E+10 | 0.191956E+10 | 14101.13 | 2223515.45 | 53585213.24 | 0.972188E+10 | 0.742374E+09 | 26777.00 | 0.58 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 51397277.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.974275E+10 | 0.00 | 0.00 | 0.38 |
February | 0.171972E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.729306E+10 | 0.00 | 0.00 | 0.38 |
March | 0.829439E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.503667E+10 | 0.00 | 0.00 | 0.39 |
April | 0.127247E+10 | 0.146660E+09 | 0.00 | 131877.37 | 19297563.04 | 0.246798E+10 | 0.107896E+09 | 0.00 | 0.39 |
May | 0.156166E+10 | 0.173668E+09 | 0.00 | 423587.80 | 1123262.83 | 0.126691E+09 | 0.256139E+09 | 0.00 | 0.44 |
June | 0.572855E+09 | 0.132232E+10 | 0.00 | 1344520.73 | 54884313.54 | 959417.06 | 0.507456E+09 | 0.00 | 0.52 |
July | 18089617.24 | 0.189765E+10 | 0.00 | 1544896.75 | 43687737.07 | 0.00 | 0.418199E+09 | 0.00 | 0.54 |
August | 28326176.65 | 0.169684E+10 | 0.00 | 2165367.63 | 26944840.90 | 0.00 | 0.513746E+09 | 0.00 | 0.58 |
September | 0.113673E+10 | 0.570280E+09 | 0.00 | 1677510.88 | 14022601.04 | 27892615.41 | 0.722605E+09 | 0.00 | 0.49 |
October | 0.293814E+10 | 0.00 | 15110.27 | 64636.59 | 6996.70 | 0.618306E+09 | 49196743.74 | 6727.18 | 0.39 |
November | 0.114382E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.456166E+10 | 0.00 | 30746.96 | 0.38 |
December | 50443148.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.814351E+10 | 0.00 | 0.00 | 0.37 |
Annual Sum or Average | 0.977534E+10 | 0.580742E+10 | 15110.27 | 7352397.75 | 0.159967E+09 | 0.380195E+11 | 0.257524E+10 | 37474.14 | 0.44 |
Minimum of Months | 18089617.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.37 |
Maximum of Months | 0.293814E+10 | 0.189765E+10 | 15110.27 | 2165367.63 | 54884313.54 | 0.974275E+10 | 0.722605E+09 | 30746.96 | 0.58 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 26142936.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.976792E+10 | 0.00 | 0.00 | 0.38 |
February | 89326265.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.737562E+10 | 0.00 | 0.00 | 0.38 |
March | 0.628122E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.523411E+10 | 0.00 | 0.00 | 0.39 |
April | 0.101019E+10 | 0.134503E+09 | 0.00 | 95989.33 | 25585139.19 | 0.273133E+10 | 85445302.39 | 0.00 | 0.39 |
May | 0.152353E+10 | 0.159991E+09 | 0.00 | 289849.41 | 1535446.52 | 0.162363E+09 | 0.175382E+09 | 0.00 | 0.43 |
June | 0.570815E+09 | 0.128872E+10 | 0.00 | 1171742.59 | 54516964.25 | 17556337.43 | 0.467726E+09 | 0.00 | 0.51 |
July | 47453438.27 | 0.184785E+10 | 0.00 | 1371090.61 | 43522679.05 | 0.00 | 0.387065E+09 | 0.00 | 0.53 |
August | 36869521.85 | 0.165612E+10 | 0.00 | 1997152.76 | 26722028.92 | 0.00 | 0.502902E+09 | 0.00 | 0.57 |
September | 0.113408E+10 | 0.564497E+09 | 0.00 | 1491882.13 | 13928585.14 | 48793734.59 | 0.667128E+09 | 0.00 | 0.48 |
October | 0.266204E+10 | 0.00 | 18961.62 | 48772.55 | 7503.88 | 0.886329E+09 | 39847890.54 | 12122.76 | 0.38 |
November | 0.100267E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.469863E+10 | 0.00 | 45359.93 | 0.38 |
December | 24194480.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.816970E+10 | 0.00 | 0.00 | 0.37 |
Annual Sum or Average | 0.875544E+10 | 0.565168E+10 | 18961.62 | 6466479.38 | 0.165818E+09 | 0.390923E+11 | 0.232550E+10 | 57482.69 | 0.43 |
Minimum of Months | 24194480.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.37 |
Maximum of Months | 0.266204E+10 | 0.184785E+10 | 18961.62 | 1997152.76 | 54516964.25 | 0.976792E+10 | 0.667128E+09 | 45359.93 | 0.57 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:19:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 2831796.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.977275E+10 | 0.00 | 0.00 | 0.38 |
February | 5459650.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.744462E+10 | 0.00 | 0.00 | 0.38 |
March | 0.131741E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.570294E+10 | 0.00 | 0.00 | 0.39 |
April | 0.429488E+09 | 0.114587E+09 | 232562.81 | 43491.28 | 30704368.83 | 0.329721E+10 | 41430787.29 | 4587.68 | 0.38 |
May | 0.125757E+10 | 0.143236E+09 | 0.00 | 151595.80 | 2761286.34 | 0.360791E+09 | 0.102996E+09 | 0.00 | 0.42 |
June | 0.491409E+09 | 0.120486E+10 | 0.00 | 931951.74 | 50362347.16 | 0.115049E+09 | 0.450327E+09 | 0.00 | 0.52 |
July | 88985487.12 | 0.173638E+10 | 0.00 | 1212613.84 | 37737118.32 | 0.00 | 0.396342E+09 | 0.00 | 0.56 |
August | 65233551.81 | 0.157118E+10 | 0.00 | 1721768.66 | 24239114.02 | 0.00 | 0.578222E+09 | 0.00 | 0.60 |
September | 0.994524E+09 | 0.551124E+09 | 0.00 | 1228080.81 | 12719959.04 | 0.222179E+09 | 0.616544E+09 | 0.00 | 0.49 |
October | 0.182803E+10 | 0.00 | 0.00 | 30070.18 | 0.00 | 0.169147E+10 | 29565481.83 | 7974.92 | 0.38 |
November | 0.641728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.504492E+10 | 0.00 | 0.00 | 0.38 |
December | 3172340.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.817546E+10 | 0.00 | 0.00 | 0.37 |
Annual Sum or Average | 0.594017E+10 | 0.532137E+10 | 232562.81 | 5319572.31 | 0.158524E+09 | 0.418274E+11 | 0.221543E+10 | 12562.60 | 0.44 |
Minimum of Months | 2831796.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.37 |
Maximum of Months | 0.182803E+10 | 0.173638E+10 | 232562.81 | 1721768.66 | 50362347.16 | 0.977275E+10 | 0.616544E+09 | 7974.92 | 0.60 |