Program Version:EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:19
Tabular Output Report in Format: HTML
Building: RetailStripmall
Environment: RUNPERIOD 1 ** William R Fairchild WA USA TMY3 WMO#=727885
Simulation Timestamp: 2020-06-03 19:19:13
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2020-06-03 19:19:13
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1294.35 | 619.21 | 619.21 |
Net Site Energy | 1294.35 | 619.21 | 619.21 |
Total Source Energy | 3401.67 | 1627.35 | 1627.35 |
Net Source Energy | 3401.67 | 1627.35 | 1627.35 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 2090.32 |
Net Conditioned Building Area | 2090.32 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 334.88 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 16.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 502.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 91.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 128.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 156.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 65.19 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 959.48 | 334.88 | 0.00 | 0.00 | 0.00 | 87.30 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 334.88 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 16.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 502.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 91.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 128.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 156.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 65.19 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 283.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 113.65 | 160.20 | 0.00 | 0.00 | 0.00 | 0.04 |
Other | 61.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 459.01 | 160.20 | 0.00 | 0.00 | 0.00 | 0.04 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 283.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 113.65 | 160.20 | 0.00 | 0.00 | 0.00 | 0.04 |
Other | 61.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 459.01 | 160.20 | 0.00 | 0.00 | 0.00 | 0.04 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 959.478 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 959.478 | 100.00 |
Total On-Site and Utility Electric Sources | 959.478 | 100.00 |
Total Electricity End Uses | 959.478 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 87.30 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 87.30 | 100.00 |
Total Water End Uses | 87.30 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 0.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 1155.17 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Meter |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2015
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Meter |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTRIPMALL
| Meter |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5C
| Meter |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_PORTANGELES
| Meter |ZoneCoolingSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ZoneHeatingSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ZoneElectricSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |SpaceGainsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |PeakSpaceGainsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |SpaceGainComponentsAtCoolingPeakMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ComfortReportSimple55Monthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |OccupantComfortDataSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |DXReportMonthly
| PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL |WindowReportMonthly
| LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR |WindowEnergyReportMonthly
| LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR |WindowZoneSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |WindowEnergyZoneSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| GAS TANK1 | GAS TANK2 | GAS TANK3 | GAS TANK4 | GAS TANK5 | GAS TANK6 | GAS TANK7 |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC_1:1_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_2:2_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_3:3_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_4:4_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_5:5_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_6:6_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_7:7_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_8:8_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_9:9_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_10:10_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL |FanReportMonthly
| PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN |ZoneTemperatureOscillationReportMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |MechanicalVentilationLoadsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2020-06-03 19:19:13
GeneralValue | |
Program Version and Build | EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:19 |
RunPeriod | RUNPERIOD 1 |
Weather File | William R Fairchild WA USA TMY3 WMO#=727885 |
Latitude [deg] | 48.12 |
Longitude [deg] | -123.5 |
Elevation [m] | 91.00 |
Time Zone | -8.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Above Ground Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Window Opening Area [m2] | 124.29 | 0.00 | 0.00 | 124.29 | 0.00 |
Gross Window-Wall Ratio [%] | 10.50 | 0.00 | 0.00 | 26.24 | 0.00 |
Above Ground Window-Wall Ratio [%] | 10.50 | 0.00 | 0.00 | 26.24 | 0.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Above Ground Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Window Opening Area [m2] | 124.29 | 0.00 | 0.00 | 124.29 | 0.00 |
Gross Window-Wall Ratio [%] | 10.50 | 0.00 | 0.00 | 26.24 | 0.00 |
Above Ground Window-Wall Ratio [%] | 10.50 | 0.00 | 0.00 | 26.24 | 0.00 |
Total | |
Gross Roof Area [m2] | 2090.32 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
LGSTORE1 | 348.39 | Yes | Yes | 1805.20 | 1.00 | 276.30 | 0.00 | 20.75 | 20.75 | 18.3665 | 11.61 | 4.3000 |
SMSTORE1 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.37 | 10.37 | 19.8089 | 11.61 | 4.3000 |
SMSTORE2 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.35 | 10.35 | 17.6561 | 11.61 | 4.3000 |
SMSTORE3 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.35 | 10.35 | 17.6561 | 11.61 | 4.3000 |
SMSTORE4 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.35 | 10.35 | 17.6561 | 11.61 | 4.3000 |
LGSTORE2 | 348.39 | Yes | Yes | 1805.20 | 1.00 | 157.89 | 0.00 | 20.70 | 20.70 | 13.1675 | 11.61 | 4.3000 |
SMSTORE5 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.35 | 10.35 | 13.1675 | 11.61 | 4.3000 |
SMSTORE6 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.35 | 10.35 | 13.1675 | 11.61 | 4.3000 |
SMSTORE7 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.35 | 10.35 | 13.1675 | 11.61 | 4.3000 |
SMSTORE8 | 174.19 | Yes | Yes | 902.60 | 1.00 | 197.36 | 0.00 | 10.35 | 10.35 | 13.1675 | 11.61 | 4.3000 |
Total | 2090.32 | 10831.20 | 1184.15 | 0.00 | 124.29 | 124.29 | 15.7096 | 11.61 | 4.3000 | |||
Conditioned Total | 2090.32 | 10831.20 | 1184.15 | 0.00 | 124.29 | 124.29 | 15.7096 | 11.61 | 4.3000 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:19:13
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 22-JUL-15:00 | 10-JAN-09:09 | - | - | - | 06-JAN-13:09 |
Heating | 0.00 | 164474.68 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 20254.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 31196.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 8089.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 9405.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 7566.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 76510.93 | 164474.68 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 164474.68 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 20254.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 31196.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 8089.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 9405.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 7566.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:19:13
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 363.01 | 0.00 | 0.00 | 0.00 |
Cooling | 51.37 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1589.92 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 288.69 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 407.66 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 494.57 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 206.46 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 3038.67 | 363.01 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 173.66 | 0.00 | 0.00 | 0.00 |
Cooling | 24.57 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 760.61 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 138.11 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 195.02 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 236.60 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 98.77 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1453.69 | 173.66 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 173.66 | 0.00 | 0.00 | 0.00 |
Cooling | 24.57 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 760.61 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 138.11 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 195.02 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 236.60 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 98.77 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1453.69 | 173.66 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:19:13
AirTerminal:SingleDuct:UncontrolledDesign Size Maximum Air Flow Rate [m3/s] | |
LGSTORE1 DIRECT AIR | 1.57 |
SMSTORE1 DIRECT AIR | 0.870692 |
SMSTORE2 DIRECT AIR | 0.973713 |
SMSTORE3 DIRECT AIR | 0.968703 |
SMSTORE4 DIRECT AIR | 0.971209 |
LGSTORE2 DIRECT AIR | 1.52 |
SMSTORE5 DIRECT AIR | 0.824569 |
SMSTORE6 DIRECT AIR | 0.815670 |
SMSTORE7 DIRECT AIR | 0.799031 |
SMSTORE8 DIRECT AIR | 0.787832 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC_1:1 | 1.57 | 1.57 | 1.57 | 1.57 | 1.57 | 1.57 | 1.00 | 1.00 | 1.57 |
PSZ-AC_2:2 | 0.870692 | 0.870692 | 0.870692 | 0.870692 | 0.878558 | 0.878558 | 1.00 | 0.991047 | 0.878558 |
PSZ-AC_3:3 | 0.973713 | 0.973713 | 0.973713 | 0.973713 | 0.973713 | 0.973713 | 1.00 | 1.00 | 0.973713 |
PSZ-AC_4:4 | 0.968703 | 0.968703 | 0.968703 | 0.968703 | 0.968703 | 0.968703 | 1.00 | 1.00 | 0.968703 |
PSZ-AC_5:5 | 0.971209 | 0.971209 | 0.971209 | 0.971209 | 0.971209 | 0.971209 | 1.00 | 1.00 | 0.971209 |
PSZ-AC_6:6 | 1.52 | 1.52 | 1.52 | 1.52 | 1.56 | 1.56 | 1.00 | 0.976161 | 1.56 |
PSZ-AC_7:7 | 0.824569 | 0.824569 | 0.824569 | 0.824569 | 0.830345 | 0.830345 | 1.00 | 0.993044 | 0.830345 |
PSZ-AC_8:8 | 0.815670 | 0.815670 | 0.815670 | 0.815670 | 0.822250 | 0.822250 | 1.00 | 0.991997 | 0.822250 |
PSZ-AC_9:9 | 0.799031 | 0.799031 | 0.799031 | 0.799031 | 0.807831 | 0.807831 | 1.00 | 0.989106 | 0.807831 |
PSZ-AC_10:10 | 0.787832 | 0.787832 | 0.787832 | 0.787832 | 0.806400 | 0.806400 | 1.00 | 0.976975 | 0.806400 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC_1:1_OA_CONTROLLER | 1.57 | 0.411453 |
PSZ-AC_2:2_OA_CONTROLLER | 0.878558 | 0.205727 |
PSZ-AC_3:3_OA_CONTROLLER | 0.973713 | 0.205727 |
PSZ-AC_4:4_OA_CONTROLLER | 0.968703 | 0.205727 |
PSZ-AC_5:5_OA_CONTROLLER | 0.971209 | 0.205727 |
PSZ-AC_6:6_OA_CONTROLLER | 1.56 | 0.411453 |
PSZ-AC_7:7_OA_CONTROLLER | 0.830345 | 0.205727 |
PSZ-AC_8:8_OA_CONTROLLER | 0.822250 | 0.205727 |
PSZ-AC_9:9_OA_CONTROLLER | 0.807831 | 0.205727 |
PSZ-AC_10:10_OA_CONTROLLER | 0.806400 | 0.205727 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC_1:1_UNITARY_PACKAGE_DX | 1.57 | 1.57 | 1.57 | 1.04 | 26003.27 | 48043.16 | 40.00 | 1.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_DX | 0.878558 | 0.878558 | 0.878558 | 0.878558 | 14543.25 | 25950.08 | 40.00 | 1.00 |
PSZ-AC_3:3_UNITARY_PACKAGE_DX | 0.973713 | 0.973713 | 0.973713 | 0.973713 | 16118.40 | 28280.11 | 40.00 | 1.00 |
PSZ-AC_4:4_UNITARY_PACKAGE_DX | 0.968703 | 0.968703 | 0.968703 | 0.968703 | 16035.48 | 28166.81 | 40.00 | 1.00 |
PSZ-AC_5:5_UNITARY_PACKAGE_DX | 0.971209 | 0.971209 | 0.971209 | 0.971209 | 16076.96 | 28223.49 | 40.00 | 1.00 |
PSZ-AC_6:6_UNITARY_PACKAGE_DX | 1.56 | 1.56 | 1.56 | 1.03 | 25845.31 | 46985.52 | 40.00 | 1.00 |
PSZ-AC_7:7_UNITARY_PACKAGE_DX | 0.830345 | 0.830345 | 0.830345 | 0.830345 | 13745.15 | 24906.92 | 40.00 | 1.00 |
PSZ-AC_8:8_UNITARY_PACKAGE_DX | 0.822250 | 0.822250 | 0.822250 | 0.822250 | 13611.16 | 24705.64 | 40.00 | 1.00 |
PSZ-AC_9:9_UNITARY_PACKAGE_DX | 0.807831 | 0.807831 | 0.807831 | 0.807831 | 13372.47 | 24329.32 | 40.00 | 1.00 |
PSZ-AC_10:10_UNITARY_PACKAGE_DX | 0.806400 | 0.806400 | 0.806400 | 0.806400 | 13348.78 | 24076.10 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | Speed 2 Design Size Rated Total Cooling Capacity [W] | Speed 2 User-Specified Rated Total Cooling Capacity [W] | Speed 1 Design Size Rated Total Cooling Capacity [W] | Speed 1 User-Specified Rated Total Cooling Capacity [W] | Speed 2 Design Size Rated Sensible Heat Ratio | Speed 2 User-Specified Rated Sensible Heat Ratio | Speed 1 Design Size Rated Sensible Heat Ratio | Speed 1 User-Specified Rated Sensible Heat Ratio | |
PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | 1.57 | 0.785430 | 1.05 | 26003.31 | 26003.27 | 13001.64 | 13001.64 | 0.798655 | 0.798660 | 0.798660 | 0.798660 |
PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | 0.878560 | 0.439280 | 0.585707 | 14543.29 | 14543.25 | 7271.62 | 7271.62 | 0.798655 | 0.798660 | 0.798660 | 0.798660 |
PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | 0.973710 | 0.486855 | 0.649140 | 16118.36 | 16118.40 | 8059.20 | 8059.20 | 0.798654 | 0.798660 | 0.798660 | 0.798660 |
PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | 0.968700 | 0.484350 | 0.645800 | 16035.42 | 16035.48 | 8017.74 | 8017.74 | 0.798654 | 0.798660 | 0.798660 | 0.798660 |
PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | 0.971210 | 0.485605 | 0.647473 | 16076.97 | 16076.96 | 8038.48 | 8038.48 | 0.798655 | 0.798660 | 0.798660 | 0.798660 |
PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | 1.56 | 0.780660 | 1.04 | 25845.39 | 25845.31 | 12922.66 | 12922.66 | 0.798655 | 0.798660 | 0.798660 | 0.798660 |
PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | 0.830340 | 0.415170 | 0.553560 | 13745.08 | 13745.15 | 6872.57 | 6872.57 | 0.798653 | 0.798660 | 0.798660 | 0.798660 |
PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | 0.822250 | 0.411125 | 0.548167 | 13611.16 | 13611.16 | 6805.58 | 6805.58 | 0.798655 | 0.798660 | 0.798660 | 0.798660 |
PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | 0.807830 | 0.403915 | 0.538553 | 13372.45 | 13372.47 | 6686.23 | 6686.23 | 0.798655 | 0.798660 | 0.798660 | 0.798660 |
PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | 0.806400 | 0.403200 | 0.537600 | 13348.78 | 13348.78 | 6674.39 | 6674.39 | 0.798655 | 0.798660 | 0.798660 | 0.798660 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | 1.57 | 1680.89 |
PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | 0.878558 | 972.70 |
PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | 0.973713 | 1078.05 |
PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | 0.968703 | 1072.51 |
PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | 0.971209 | 1075.28 |
PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | 1.56 | 1670.68 |
PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | 0.830345 | 919.32 |
PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | 0.822250 | 910.36 |
PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | 0.807831 | 894.40 |
PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | 0.806400 | 892.81 |
Design Size Nominal Capacity [W] | |
PSZ-AC_1:1_UNITARY_PACKAGE_HEATCOIL | 48043.16 |
PSZ-AC_2:2_UNITARY_PACKAGE_HEATCOIL | 25950.08 |
PSZ-AC_3:3_UNITARY_PACKAGE_HEATCOIL | 28280.11 |
PSZ-AC_4:4_UNITARY_PACKAGE_HEATCOIL | 28166.81 |
PSZ-AC_5:5_UNITARY_PACKAGE_HEATCOIL | 28223.49 |
PSZ-AC_6:6_UNITARY_PACKAGE_HEATCOIL | 46985.52 |
PSZ-AC_7:7_UNITARY_PACKAGE_HEATCOIL | 24906.92 |
PSZ-AC_8:8_UNITARY_PACKAGE_HEATCOIL | 24705.64 |
PSZ-AC_9:9_UNITARY_PACKAGE_HEATCOIL | 24329.32 |
PSZ-AC_10:10_UNITARY_PACKAGE_HEATCOIL | 24076.10 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:19:13
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
LGSTORE1_WALL_3 | LGSTORE1_WALL_3_DOOR_1 | LGSTORE1_WALL_3_DOOR_2 | |
LGSTORE1_WALL_1 | LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | |
SMSTORE1_WALL_1 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | |
SMSTORE1_WALL_3 | SMSTORE1_WALL_3_DOOR | |
SMSTORE2_WALL_1 | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | |
SMSTORE2_WALL_3 | SMSTORE2_WALL_3_DOOR | |
SMSTORE3_WALL_1 | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | |
SMSTORE3_WALL_3 | SMSTORE3_WALL_3_DOOR | |
SMSTORE4_WALL_1 | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | |
SMSTORE4_WALL_3 | SMSTORE4_WALL_3_DOOR | |
LGSTORE2_WALL_3 | LGSTORE2_WALL_3_DOOR_1 | LGSTORE2_WALL_3_DOOR_2 | |
LGSTORE2_WALL_1 | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | |
SMSTORE5_WALL_1 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | |
SMSTORE5_WALL_3 | SMSTORE5_WALL_3_DOOR | |
SMSTORE6_WALL_1 | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | |
SMSTORE6_WALL_3 | SMSTORE6_WALL_3_DOOR | |
SMSTORE7_WALL_1 | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | |
SMSTORE7_WALL_3 | SMSTORE7_WALL_3_DOOR | |
SMSTORE8_WALL_1 | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR | |
SMSTORE8_WALL_3 | SMSTORE8_WALL_3_DOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2020-06-03 19:19:13
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2020-06-03 19:19:13
VersionVersion ID | |
1 | 9.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 9.30 | 6.70 | 4.10 | 4.20 | 4.20 | 5.90 | 9.00 | 10.00 | 13.30 | 15.00 | 15.70 | 13.40 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | William R Fairchild WA USA TMY3 WMO#=727885 | 48.12 | -123.50 | -8.00 | 91.00 | 100237 | 1.1914 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 9.23 | 11.60 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RetailStripmall | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 10 | 118 | 48 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | LGSTORE1 | 0.0 | 0.00 | 0.00 | 0.00 | 7.62 | 11.43 | 2.59 | 1 | 1 | 1 | 0.00 | 15.24 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 1805.20 | TARP | TARP | 348.39 | 276.30 | 247.76 | 20.75 | 6 | 8 | 0 | Yes |
2 | SMSTORE1 | 0.0 | 0.00 | 0.00 | 0.00 | 19.05 | 11.43 | 2.59 | 1 | 1 | 1 | 15.24 | 22.86 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.67 | 10.37 | 6 | 4 | 0 | Yes |
3 | SMSTORE2 | 0.0 | 0.00 | 0.00 | 0.00 | 26.67 | 11.43 | 2.59 | 1 | 1 | 1 | 22.86 | 30.48 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.35 | 6 | 4 | 0 | Yes |
4 | SMSTORE3 | 0.0 | 0.00 | 0.00 | 0.00 | 34.29 | 11.43 | 2.59 | 1 | 1 | 1 | 30.48 | 38.10 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.35 | 6 | 4 | 0 | Yes |
5 | SMSTORE4 | 0.0 | 0.00 | 0.00 | 0.00 | 41.91 | 11.43 | 2.59 | 1 | 1 | 1 | 38.10 | 45.72 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.35 | 6 | 4 | 0 | Yes |
6 | LGSTORE2 | 0.0 | 0.00 | 0.00 | 0.00 | 53.34 | 11.43 | 2.59 | 1 | 1 | 1 | 45.72 | 60.96 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 1805.20 | TARP | TARP | 348.39 | 157.89 | 129.43 | 20.70 | 6 | 8 | 0 | Yes |
7 | SMSTORE5 | 0.0 | 0.00 | 0.00 | 0.00 | 64.77 | 11.43 | 2.59 | 1 | 1 | 1 | 60.96 | 68.58 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.35 | 6 | 4 | 0 | Yes |
8 | SMSTORE6 | 0.0 | 0.00 | 0.00 | 0.00 | 72.39 | 11.43 | 2.59 | 1 | 1 | 1 | 68.58 | 76.20 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.35 | 6 | 4 | 0 | Yes |
9 | SMSTORE7 | 0.0 | 0.00 | 0.00 | 0.00 | 80.01 | 11.43 | 2.59 | 1 | 1 | 1 | 76.20 | 83.82 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.35 | 6 | 4 | 0 | Yes |
10 | SMSTORE8 | 0.0 | 0.00 | 0.00 | 0.00 | 87.63 | 11.43 | 2.59 | 1 | 1 | 1 | 83.82 | 91.44 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 197.36 | 183.13 | 10.35 | 6 | 4 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | LGSTORE1 | 348.39 | 30.0 | 11.614 | 8.610E-002 | 18.366 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 22.666 | No |
2 | SMSTORE1 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 19.809 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 24.109 | No |
3 | SMSTORE2 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 17.656 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 21.956 | No |
4 | SMSTORE3 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 17.656 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 21.956 | No |
5 | SMSTORE4 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 17.656 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 21.956 | No |
6 | LGSTORE2 | 348.39 | 30.0 | 11.614 | 8.610E-002 | 13.168 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 17.468 | No |
7 | SMSTORE5 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 13.168 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 17.468 | No |
8 | SMSTORE6 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 13.168 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 17.468 | No |
9 | SMSTORE7 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 13.168 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 17.468 | No |
10 | SMSTORE8 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 13.168 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 17.468 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | |
1 | LGSTORE1 | TYPE1_OCC_SCH | LGSTORE1 | 348.39 | 30.0 | 30.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 30 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
2 | SMSTORE1 | TYPE1_OCC_SCH | SMSTORE1 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
3 | SMSTORE2 | TYPE2_OCC_SCH | SMSTORE2 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
4 | SMSTORE3 | TYPE2_OCC_SCH | SMSTORE3 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
5 | SMSTORE4 | TYPE2_OCC_SCH | SMSTORE4 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
6 | LGSTORE2 | TYPE3_OCC_SCH | LGSTORE2 | 348.39 | 30.0 | 30.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 30 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
7 | SMSTORE5 | TYPE3_OCC_SCH | SMSTORE5 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
8 | SMSTORE6 | TYPE3_OCC_SCH | SMSTORE6 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
9 | SMSTORE7 | TYPE3_OCC_SCH | SMSTORE7 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
10 | SMSTORE8 | TYPE3_OCC_SCH | SMSTORE8 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | LGSTORE1_LIGHTS | TYPE1_LIGHT_SCH | LGSTORE1 | 348.39 | 30.0 | 4587.386 | 13.168 | 152.933 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 4587.386 |
2 | LGSTORE1_LIGHTS_ALLOWANCE | TYPE1_LIGHT_SCH | LGSTORE1 | 348.39 | 30.0 | 1811.251 | 5.199 | 60.383 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1811.251 |
3 | SMSTORE1_LIGHTS | TYPE1_LIGHT_SCH | SMSTORE1 | 174.19 | 15.0 | 2293.693 | 13.168 | 152.933 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2293.693 |
4 | SMSTORE1_LIGHTS_ALLOWANCE | TYPE1_LIGHT_SCH | SMSTORE1 | 174.19 | 15.0 | 1156.875 | 6.641 | 77.135 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1156.875 |
5 | SMSTORE2_LIGHTS | TYPE2_LIGHT_SCH | SMSTORE2 | 174.19 | 15.0 | 2293.693 | 13.168 | 152.933 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2293.693 |
6 | SMSTORE2_LIGHTS_ALLOWANCE | TYPE2_LIGHT_SCH | SMSTORE2 | 174.19 | 15.0 | 781.875 | 4.489 | 52.132 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 781.875 |
7 | SMSTORE3_LIGHTS | TYPE2_LIGHT_SCH | SMSTORE3 | 174.19 | 15.0 | 2293.693 | 13.168 | 152.933 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2293.693 |
8 | SMSTORE3_LIGHTS_ALLOWANCE | TYPE2_LIGHT_SCH | SMSTORE3 | 174.19 | 15.0 | 781.875 | 4.489 | 52.132 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 781.875 |
9 | SMSTORE4_LIGHTS | TYPE2_LIGHT_SCH | SMSTORE4 | 174.19 | 15.0 | 2293.693 | 13.168 | 152.933 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2293.693 |
10 | SMSTORE4_LIGHTS_ALLOWANCE | TYPE2_LIGHT_SCH | SMSTORE4 | 174.19 | 15.0 | 781.875 | 4.489 | 52.132 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 781.875 |
11 | LGSTORE2_LIGHTS | TYPE3_LIGHT_SCH | LGSTORE2 | 348.39 | 30.0 | 4587.386 | 13.168 | 152.933 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 4587.386 |
12 | LGSTORE2_LIGHTS_ALLOWANCE | TYPE3_LIGHT_SCH | LGSTORE2 | 348.39 | 30.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
13 | SMSTORE5_LIGHTS | TYPE3_LIGHT_SCH | SMSTORE5 | 174.19 | 15.0 | 2293.693 | 13.168 | 152.933 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2293.693 |
14 | SMSTORE5_LIGHTS_ALLOWANCE | TYPE3_LIGHT_SCH | SMSTORE5 | 174.19 | 15.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
15 | SMSTORE6_LIGHTS | TYPE3_LIGHT_SCH | SMSTORE6 | 174.19 | 15.0 | 2293.693 | 13.168 | 152.933 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2293.693 |
16 | SMSTORE6_LIGHTS_ALLOWANCE | TYPE3_LIGHT_SCH | SMSTORE6 | 174.19 | 15.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
17 | SMSTORE7_LIGHTS | TYPE3_LIGHT_SCH | SMSTORE7 | 174.19 | 15.0 | 2293.693 | 13.168 | 152.933 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2293.693 |
18 | SMSTORE7_LIGHTS_ALLOWANCE | TYPE3_LIGHT_SCH | SMSTORE7 | 174.19 | 15.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
19 | SMSTORE8_LIGHTS | TYPE3_LIGHT_SCH | SMSTORE8 | 174.19 | 15.0 | 2293.693 | 13.168 | 152.933 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2293.693 |
20 | SMSTORE8_LIGHTS_ALLOWANCE | TYPE3_LIGHT_SCH | SMSTORE8 | 174.19 | 15.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | LGSTORE1_MISCPLUG_EQUIP | TYPE1_EQUIP_SCH | LGSTORE1 | 348.39 | 30.0 | 1498.062 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1498.062 |
2 | SMSTORE1_MISCPLUG_EQUIP | TYPE1_EQUIP_SCH | SMSTORE1 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
3 | SMSTORE2_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE2 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
4 | SMSTORE3_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE3 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
5 | SMSTORE4_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE4 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
6 | LGSTORE2_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | LGSTORE2 | 348.39 | 30.0 | 1498.062 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1498.062 |
7 | SMSTORE5_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE5 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
8 | SMSTORE6_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE6 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
9 | SMSTORE7_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE7 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
10 | SMSTORE8_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE8 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.770 | 0.700 | Rough |
5 | NONRES_EXT_WALL | 20 | 4 | 7 | 0.167 | 0.3843 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
6 | LGSTORE1_FLOOR_FFACTOR | 30 | 2 | 7 | 0.167 | 0.1464 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
7 | SMSTORE1_FLOOR_FFACTOR | 31 | 2 | 7 | 0.167 | 0.8283E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
8 | SMSTORE2_FLOOR_FFACTOR | 32 | 2 | 7 | 0.167 | 0.8283E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | SMSTORE3_FLOOR_FFACTOR | 33 | 2 | 7 | 0.167 | 0.8283E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
10 | SMSTORE4_FLOOR_FFACTOR | 34 | 2 | 7 | 0.167 | 0.8283E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
11 | LGSTORE2_FLOOR_FFACTOR | 35 | 2 | 7 | 0.167 | 0.8283E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | SMSTORE5_FLOOR_FFACTOR | 36 | 2 | 7 | 0.167 | 0.8283E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | SMSTORE6_FLOOR_FFACTOR | 37 | 2 | 7 | 0.167 | 0.8283E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | SMSTORE7_FLOOR_FFACTOR | 38 | 2 | 7 | 0.167 | 0.8283E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | SMSTORE8_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.2111 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
6 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
7 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
8 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
9 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
10 | NONRES_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.368 |
11 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
12 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 6.756 |
13 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
14 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.00 |
15 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
16 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.00 |
17 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
18 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.00 |
19 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
20 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.00 |
21 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
22 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.00 |
23 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
24 | ~FC_Insulation_7 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.00 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_8 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.00 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_9 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.00 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
30 | ~FC_Insulation_10 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.659 |
31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009596 | 2.1009596 | 2.1009596 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
14 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
15 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
16 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
17 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
18 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
19 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
20 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
21 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
22 | 7 | -0.35963630E-12 | 0.61482467E-15 | -0.13288964E-12 | 0.15093609E-15 |
23 | 6 | 0.33258387E-07 | 0.11249777E-09 | 0.75805110E-08 | -0.16019892E-12 |
24 | 5 | -0.21313350E-03 | 0.93714421E-06 | -0.10927814E-03 | 0.74776115E-08 |
25 | 4 | 0.31870195 | 0.44521373E-03 | 0.10925225 | -0.37358013E-04 |
26 | 3 | -7.7913368 | 0.13499397E-01 | -2.4947666 | 0.31584435E-01 |
27 | 2 | 42.601618 | 0.47079245E-01 | 15.902165 | -0.35261900 |
28 | 1 | -81.870774 | 0.20888078E-01 | -29.712230 | 1.1068570 |
29 | 0 | 46.824331 | 0.41326549E-03 | 16.278015 | |
30 | 7 | -0.28997596E-08 | -0.17578320E-14 | 0.22751757E-14 | -0.53829073E-16 |
31 | 6 | 0.41991781E-05 | 0.27986603E-08 | 0.31940183E-02 | -0.26794102E-04 |
32 | 5 | -0.29588474E-03 | 0.16552611E-05 | -0.22396035 | 0.19582313E-02 |
33 | 4 | 0.67666006E-02 | 0.75295852E-04 | 4.8334724 | -0.45302727E-01 |
34 | 3 | -0.59297736E-01 | 0.59838054E-03 | -38.043598 | 0.39889893 |
35 | 2 | 0.21038411 | 0.99492606E-03 | 116.52712 | -1.4185167 |
36 | 1 | -0.30354941 | 0.30287292E-03 | -143.93272 | 2.0494576 |
37 | 0 | 0.14796861 | 0.73483799E-05 | 60.838472 | |
38 | 7 | -0.51571905E-08 | -0.97500959E-14 | 0.15789915E-14 | -0.32998988E-16 |
39 | 6 | 0.26247599E-05 | 0.15902949E-08 | 0.31989528E-02 | -0.26835497E-04 |
40 | 5 | -0.17282397E-03 | 0.93714128E-06 | -0.22424071 | 0.19607060E-02 |
41 | 4 | 0.38696203E-02 | 0.42548205E-04 | 4.8381400 | -0.45347597E-01 |
42 | 3 | -0.33643188E-01 | 0.33758390E-03 | -38.069955 | 0.39919029 |
43 | 2 | 0.11898200 | 0.56044665E-03 | 116.57840 | -1.4192028 |
44 | 1 | -0.17142224 | 0.17027190E-03 | -143.96290 | 2.0499538 |
45 | 0 | 0.83499932E-01 | 0.41268798E-05 | 60.838472 | |
46 | 7 | -0.51571905E-08 | -0.97500958E-14 | 0.15789913E-14 | -0.32998984E-16 |
47 | 6 | 0.26247599E-05 | 0.15902949E-08 | 0.31989528E-02 | -0.26835497E-04 |
48 | 5 | -0.17282397E-03 | 0.93714128E-06 | -0.22424071 | 0.19607060E-02 |
49 | 4 | 0.38696203E-02 | 0.42548205E-04 | 4.8381400 | -0.45347597E-01 |
50 | 3 | -0.33643188E-01 | 0.33758390E-03 | -38.069955 | 0.39919029 |
51 | 2 | 0.11898200 | 0.56044665E-03 | 116.57840 | -1.4192028 |
52 | 1 | -0.17142224 | 0.17027190E-03 | -143.96290 | 2.0499538 |
53 | 0 | 0.83499932E-01 | 0.41268798E-05 | 60.838472 | |
54 | 7 | -0.51571905E-08 | -0.97500959E-14 | 0.15789911E-14 | -0.32998980E-16 |
55 | 6 | 0.26247599E-05 | 0.15902949E-08 | 0.31989528E-02 | -0.26835497E-04 |
56 | 5 | -0.17282397E-03 | 0.93714128E-06 | -0.22424071 | 0.19607060E-02 |
57 | 4 | 0.38696203E-02 | 0.42548205E-04 | 4.8381400 | -0.45347597E-01 |
58 | 3 | -0.33643188E-01 | 0.33758390E-03 | -38.069955 | 0.39919029 |
59 | 2 | 0.11898200 | 0.56044665E-03 | 116.57840 | -1.4192028 |
60 | 1 | -0.17142224 | 0.17027190E-03 | -143.96290 | 2.0499538 |
61 | 0 | 0.83499932E-01 | 0.41268798E-05 | 60.838472 | |
62 | 7 | -0.51571905E-08 | -0.97500959E-14 | 0.15789915E-14 | -0.32998988E-16 |
63 | 6 | 0.26247599E-05 | 0.15902949E-08 | 0.31989528E-02 | -0.26835497E-04 |
64 | 5 | -0.17282397E-03 | 0.93714128E-06 | -0.22424071 | 0.19607060E-02 |
65 | 4 | 0.38696203E-02 | 0.42548205E-04 | 4.8381400 | -0.45347597E-01 |
66 | 3 | -0.33643188E-01 | 0.33758390E-03 | -38.069955 | 0.39919029 |
67 | 2 | 0.11898200 | 0.56044665E-03 | 116.57840 | -1.4192028 |
68 | 1 | -0.17142224 | 0.17027190E-03 | -143.96290 | 2.0499538 |
69 | 0 | 0.83499932E-01 | 0.41268798E-05 | 60.838472 | |
70 | 7 | -0.51571905E-08 | -0.97500958E-14 | 0.15789913E-14 | -0.32998984E-16 |
71 | 6 | 0.26247599E-05 | 0.15902949E-08 | 0.31989528E-02 | -0.26835497E-04 |
72 | 5 | -0.17282397E-03 | 0.93714128E-06 | -0.22424071 | 0.19607060E-02 |
73 | 4 | 0.38696203E-02 | 0.42548205E-04 | 4.8381400 | -0.45347597E-01 |
74 | 3 | -0.33643188E-01 | 0.33758390E-03 | -38.069955 | 0.39919029 |
75 | 2 | 0.11898200 | 0.56044665E-03 | 116.57840 | -1.4192028 |
76 | 1 | -0.17142224 | 0.17027190E-03 | -143.96290 | 2.0499538 |
77 | 0 | 0.83499932E-01 | 0.41268798E-05 | 60.838472 | |
78 | 7 | -0.51571905E-08 | -0.97500957E-14 | 0.15789917E-14 | -0.32998991E-16 |
79 | 6 | 0.26247599E-05 | 0.15902949E-08 | 0.31989528E-02 | -0.26835497E-04 |
80 | 5 | -0.17282397E-03 | 0.93714128E-06 | -0.22424071 | 0.19607060E-02 |
81 | 4 | 0.38696203E-02 | 0.42548205E-04 | 4.8381400 | -0.45347597E-01 |
82 | 3 | -0.33643188E-01 | 0.33758390E-03 | -38.069955 | 0.39919029 |
83 | 2 | 0.11898200 | 0.56044665E-03 | 116.57840 | -1.4192028 |
84 | 1 | -0.17142224 | 0.17027190E-03 | -143.96290 | 2.0499538 |
85 | 0 | 0.83499932E-01 | 0.41268798E-05 | 60.838472 | |
86 | 7 | -0.51571905E-08 | -0.97500959E-14 | 0.15789915E-14 | -0.32998988E-16 |
87 | 6 | 0.26247599E-05 | 0.15902949E-08 | 0.31989528E-02 | -0.26835497E-04 |
88 | 5 | -0.17282397E-03 | 0.93714128E-06 | -0.22424071 | 0.19607060E-02 |
89 | 4 | 0.38696203E-02 | 0.42548205E-04 | 4.8381400 | -0.45347597E-01 |
90 | 3 | -0.33643188E-01 | 0.33758390E-03 | -38.069955 | 0.39919029 |
91 | 2 | 0.11898200 | 0.56044665E-03 | 116.57840 | -1.4192028 |
92 | 1 | -0.17142224 | 0.17027190E-03 | -143.96290 | 2.0499538 |
93 | 0 | 0.83499932E-01 | 0.41268798E-05 | 60.838472 | |
94 | 7 | -0.51571905E-08 | -0.97500958E-14 | 0.15789913E-14 | -0.32998984E-16 |
95 | 6 | 0.26247599E-05 | 0.15902949E-08 | 0.31989528E-02 | -0.26835497E-04 |
96 | 5 | -0.17282397E-03 | 0.93714128E-06 | -0.22424071 | 0.19607060E-02 |
97 | 4 | 0.38696203E-02 | 0.42548205E-04 | 4.8381400 | -0.45347597E-01 |
98 | 3 | -0.33643188E-01 | 0.33758390E-03 | -38.069955 | 0.39919029 |
99 | 2 | 0.11898200 | 0.56044665E-03 | 116.57840 | -1.4192028 |
100 | 1 | -0.17142224 | 0.17027190E-03 | -143.96290 | 2.0499538 |
101 | 0 | 0.83499932E-01 | 0.41268798E-05 | 60.838472 | |
102 | 7 | -0.19967951E-08 | -0.58252365E-15 | 0.72897552E-14 | -0.10630581E-15 |
103 | 6 | 0.59274927E-05 | 0.40433693E-08 | 0.31889525E-02 | -0.26751606E-04 |
104 | 5 | -0.42514865E-03 | 0.23948505E-05 | -0.22367243 | 0.19556901E-02 |
105 | 4 | 0.97725356E-02 | 0.10900143E-03 | 4.8286774 | -0.45256634E-01 |
106 | 3 | -0.85796444E-01 | 0.86675557E-03 | -38.016512 | 0.39859954 |
107 | 2 | 0.30461848 | 0.14417950E-02 | 116.47440 | -1.4178116 |
108 | 1 | -0.43965446 | 0.43929230E-03 | -143.90169 | 2.0489476 |
109 | 0 | 0.21434897 | 0.10616597E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.38_SHGC_0.4 | 29 | 1 | VerySmooth | 2.159 | 0.394 | 0.315 | 0.401 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 3.45900E-002 | 0.31435 | 0.47939 | 0.47939 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11893 | 1.00000 | No |
Calculation Method | Value {days} | Allowable Number Figures in Shadow Overlap {} | Polygon Clipping Algorithm | Sky Diffuse Modeling Algorithm | External Shading Calculation Method | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | AverageOverDaysInFrequency | 30 | 15000 | SutherlandHodgman | SimpleSkyDiffuseModeling | InternalCalculation | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | GAS TANK1 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
2 | WaterHeater:Mixed | GAS TANK2 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
3 | WaterHeater:Mixed | GAS TANK3 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
4 | WaterHeater:Mixed | GAS TANK4 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
5 | WaterHeater:Mixed | GAS TANK5 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
6 | WaterHeater:Mixed | GAS TANK6 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
7 | WaterHeater:Mixed | GAS TANK7 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | LGSTORE1_WALL_2 | 0 | 118.41 | 56.08 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 4 | No | No |
2 | LGSTORE1_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 4 | No | No |
3 | LGSTORE1_WALL_3_DOOR_1 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 0 | No | No |
4 | LGSTORE1_WALL_3_DOOR_2 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 0 | No | No |
5 | LGSTORE1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 0 | No | No |
6 | LGSTORE1_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 4 | No | No |
7 | LGSTORE1_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 1 | No | No |
8 | LGSTORE1_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 1 | No | No |
9 | LGSTORE1_WALL_1_WINDOW_3 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 1 | No | No |
10 | LGSTORE1_WALL_1_WINDOW_4 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 1 | No | No |
11 | LGSTORE1_WALL_1_DOOR_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 1 | No | No |
12 | LGSTORE1_WALL_1_DOOR_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 1 | No | No |
13 | LGSTORE1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 0 | No | No |
14 | LGSTORE1_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 0 | No | No |
15 | LGSTORE1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 0 | No | No |
16 | SMSTORE1_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
17 | SMSTORE1_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
18 | SMSTORE1_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
19 | SMSTORE1_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
20 | SMSTORE1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
21 | SMSTORE1_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
22 | SMSTORE1_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
23 | SMSTORE1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
24 | SMSTORE1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
25 | SMSTORE1_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
26 | SMSTORE1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
27 | SMSTORE2_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
28 | SMSTORE2_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
29 | SMSTORE2_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
30 | SMSTORE2_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
31 | SMSTORE2_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
32 | SMSTORE2_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
33 | SMSTORE2_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
34 | SMSTORE2_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
35 | SMSTORE2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
36 | SMSTORE2_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
37 | SMSTORE2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
38 | SMSTORE3_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
39 | SMSTORE3_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
40 | SMSTORE3_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
41 | SMSTORE3_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
42 | SMSTORE3_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
43 | SMSTORE3_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
44 | SMSTORE3_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
45 | SMSTORE3_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
46 | SMSTORE3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
47 | SMSTORE3_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
48 | SMSTORE3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
49 | SMSTORE4_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
50 | SMSTORE4_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
51 | SMSTORE4_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
52 | SMSTORE4_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
53 | SMSTORE4_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
54 | SMSTORE4_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 3 | No | No |
55 | SMSTORE4_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
56 | SMSTORE4_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
57 | SMSTORE4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
58 | SMSTORE4_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
59 | SMSTORE4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
60 | LGSTORE2_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
61 | LGSTORE2_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 4 | No | No |
62 | LGSTORE2_WALL_3_DOOR_1 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
63 | LGSTORE2_WALL_3_DOOR_2 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
64 | LGSTORE2_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
65 | LGSTORE2_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 4 | No | No |
66 | LGSTORE2_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
67 | LGSTORE2_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
68 | LGSTORE2_WALL_1_WINDOW_3 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
69 | LGSTORE2_WALL_1_WINDOW_4 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
70 | LGSTORE2_WALL_1_DOOR_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
71 | LGSTORE2_WALL_1_DOOR_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
72 | LGSTORE2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
73 | LGSTORE2_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
74 | LGSTORE2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
75 | SMSTORE5_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
76 | SMSTORE5_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
77 | SMSTORE5_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
78 | SMSTORE5_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
79 | SMSTORE5_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
80 | SMSTORE5_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
81 | SMSTORE5_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
82 | SMSTORE5_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
83 | SMSTORE5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
84 | SMSTORE5_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
85 | SMSTORE5_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
86 | SMSTORE6_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
87 | SMSTORE6_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
88 | SMSTORE6_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
89 | SMSTORE6_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
90 | SMSTORE6_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
91 | SMSTORE6_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
92 | SMSTORE6_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
93 | SMSTORE6_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
94 | SMSTORE6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
95 | SMSTORE6_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
96 | SMSTORE6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
97 | SMSTORE7_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
98 | SMSTORE7_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
99 | SMSTORE7_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
100 | SMSTORE7_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
101 | SMSTORE7_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
102 | SMSTORE7_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 3 | No | No |
103 | SMSTORE7_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
104 | SMSTORE7_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
105 | SMSTORE7_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
106 | SMSTORE7_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
107 | SMSTORE7_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
108 | SMSTORE8_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 4 | No | No |
109 | SMSTORE8_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 1 | No | No |
110 | SMSTORE8_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 1 | No | No |
111 | SMSTORE8_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 1 | No | No |
112 | SMSTORE8_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
113 | SMSTORE8_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 3 | No | No |
114 | SMSTORE8_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
115 | SMSTORE8_WALL_4 | 0 | 118.41 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 3 | No | No |
116 | SMSTORE8_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
117 | SMSTORE8_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
118 | SMSTORE8_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | LGSTORE1_INFILTRATION | TYPE1_INFIL_SCH | LGSTORE1 | 348.39 | 30.0 | 0.159 | 4.569E-004 | 2.517E-004 | 0.317 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | LGSTORE1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | LGSTORE1 | 348.39 | 30.0 | 0.241 | 6.922E-004 | 3.813E-004 | 0.481 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | SMSTORE1_INFILTRATION | TYPE1_INFIL_SCH | SMSTORE1 | 174.19 | 15.0 | 4.561E-002 | 2.619E-004 | 1.775E-004 | 0.182 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | SMSTORE1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE1 | 174.19 | 15.0 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
5 | SMSTORE2_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE2 | 174.19 | 15.0 | 4.561E-002 | 2.618E-004 | 1.775E-004 | 0.182 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | SMSTORE2_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE2 | 174.19 | 15.0 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
7 | SMSTORE3_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE3 | 174.19 | 15.0 | 4.561E-002 | 2.618E-004 | 1.775E-004 | 0.182 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | SMSTORE3_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE3 | 174.19 | 15.0 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | SMSTORE4_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE4 | 174.19 | 15.0 | 4.561E-002 | 2.618E-004 | 1.775E-004 | 0.182 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | SMSTORE4_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE4 | 174.19 | 15.0 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
11 | LGSTORE2_INFILTRATION | TYPE3_INFIL_SCH | LGSTORE2 | 348.39 | 30.0 | 9.122E-002 | 2.618E-004 | 1.775E-004 | 0.182 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | LGSTORE2_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | LGSTORE2 | 348.39 | 30.0 | 0.241 | 6.922E-004 | 4.692E-004 | 0.481 | 1.000 | 0.000 | 0.000 | 0.000 |
13 | SMSTORE5_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE5 | 174.19 | 15.0 | 4.561E-002 | 2.618E-004 | 1.775E-004 | 0.182 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | SMSTORE5_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE5 | 174.19 | 15.0 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
15 | SMSTORE6_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE6 | 174.19 | 15.0 | 4.561E-002 | 2.618E-004 | 1.775E-004 | 0.182 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | SMSTORE6_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE6 | 174.19 | 15.0 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
17 | SMSTORE7_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE7 | 174.19 | 15.0 | 4.561E-002 | 2.618E-004 | 1.775E-004 | 0.182 | 0.000 | 0.000 | 0.224 | 0.000 |
18 | SMSTORE7_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE7 | 174.19 | 15.0 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
19 | SMSTORE8_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE8 | 174.19 | 15.0 | 0.113 | 6.514E-004 | 3.022E-004 | 0.453 | 0.000 | 0.000 | 0.224 | 0.000 |
20 | SMSTORE8_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE8 | 174.19 | 15.0 | 0.135 | 7.722E-004 | 3.583E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | LGSTORE1 | Mixing/Well-Stirred |
2 | SMSTORE1 | Mixing/Well-Stirred |
3 | SMSTORE2 | Mixing/Well-Stirred |
4 | SMSTORE3 | Mixing/Well-Stirred |
5 | SMSTORE4 | Mixing/Well-Stirred |
6 | LGSTORE2 | Mixing/Well-Stirred |
7 | SMSTORE5 | Mixing/Well-Stirred |
8 | SMSTORE6 | Mixing/Well-Stirred |
9 | SMSTORE7 | Mixing/Well-Stirred |
10 | SMSTORE8 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone LGSTORE1 | 1.2000 |
3 | Zone SMSTORE1 | 1.2000 |
4 | Zone SMSTORE2 | 1.2000 |
5 | Zone SMSTORE3 | 1.2000 |
6 | Zone SMSTORE4 | 1.2000 |
7 | Zone LGSTORE2 | 1.2000 |
8 | Zone SMSTORE5 | 1.2000 |
9 | Zone SMSTORE6 | 1.2000 |
10 | Zone SMSTORE7 | 1.2000 |
11 | Zone SMSTORE8 | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone LGSTORE1 | 1.2000 |
3 | Zone SMSTORE1 | 1.2000 |
4 | Zone SMSTORE2 | 1.2000 |
5 | Zone SMSTORE3 | 1.2000 |
6 | Zone SMSTORE4 | 1.2000 |
7 | Zone LGSTORE2 | 1.2000 |
8 | Zone SMSTORE5 | 1.2000 |
9 | Zone SMSTORE6 | 1.2000 |
10 | Zone SMSTORE7 | 1.2000 |
11 | Zone SMSTORE8 | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | LGSTORE1 | Cooling | 17651.03025 | 21181.23630 | 1.30905 | 1.57086 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 26.32417 | 8.38408E-003 | 348.38640 | 29.99610 | 0.41145 | 0.00000 |
2 | LGSTORE1 | Heating | 16828.68583 | 20194.42300 | 0.73324 | 0.87989 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -4.30000 | 2.65759E-003 | 348.38640 | 29.99610 | 0.41145 | 0.00000 |
3 | SMSTORE1 | Cooling | 10116.08682 | 12139.30418 | 0.72558 | 0.87069 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 22.94200 | 8.38408E-003 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
4 | SMSTORE1 | Heating | 8234.18971 | 9881.02766 | 0.35877 | 0.43052 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -4.30000 | 2.65759E-003 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
5 | SMSTORE2 | Cooling | 11261.84221 | 13514.21065 | 0.81143 | 0.97371 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 21.39500 | 8.38408E-003 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
6 | SMSTORE2 | Heating | 8341.50697 | 10009.80836 | 0.36344 | 0.43613 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -4.30000 | 2.65759E-003 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
7 | SMSTORE3 | Cooling | 11206.15170 | 13447.38203 | 0.80725 | 0.96870 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 21.39500 | 8.38408E-003 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
8 | SMSTORE3 | Heating | 8430.13712 | 10116.16455 | 0.36731 | 0.44077 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -4.30000 | 2.65759E-003 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
9 | SMSTORE4 | Cooling | 11233.58583 | 13480.30300 | 0.80934 | 0.97121 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 21.39500 | 8.38408E-003 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
10 | SMSTORE4 | Heating | 8594.15947 | 10312.99136 | 0.37445 | 0.44934 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -4.30000 | 2.65759E-003 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
11 | LGSTORE2 | Cooling | 17778.84166 | 21334.60999 | 1.27008 | 1.52410 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 22.94200 | 8.38408E-003 | 348.38640 | 29.99610 | 0.41145 | 0.00000 |
12 | LGSTORE2 | Heating | 16557.89783 | 19869.47740 | 0.72144 | 0.86573 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -4.30000 | 2.65759E-003 | 348.38640 | 29.99610 | 0.41145 | 0.00000 |
13 | SMSTORE5 | Cooling | 9597.05264 | 11516.46316 | 0.68714 | 0.82457 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 22.94200 | 8.38408E-003 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
14 | SMSTORE5 | Heating | 8855.46803 | 10626.56164 | 0.38584 | 0.46300 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -4.30000 | 2.65759E-003 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
15 | SMSTORE6 | Cooling | 9496.63197 | 11395.95836 | 0.67972 | 0.81567 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 22.94200 | 8.38408E-003 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
16 | SMSTORE6 | Heating | 8859.04902 | 10630.85883 | 0.38599 | 0.46319 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -4.30000 | 2.65759E-003 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
17 | SMSTORE7 | Cooling | 9307.56604 | 11169.07925 | 0.66586 | 0.79903 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 22.94200 | 8.38408E-003 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
18 | SMSTORE7 | Heating | 9129.81400 | 10955.77681 | 0.39779 | 0.47735 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -4.30000 | 2.65759E-003 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
19 | SMSTORE8 | Cooling | 9179.68380 | 11015.62056 | 0.65653 | 0.78783 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 22.94200 | 8.38408E-003 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
20 | SMSTORE8 | Heating | 10653.94306 | 12784.73167 | 0.46420 | 0.55703 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -4.30000 | 2.65759E-003 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC_1:1 | Cooling | Sensible | 22080.84 | 1.57086 | 1.57086 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
2 | PSZ-AC_1:1 | Heating | Sensible | 32415.61 | 0.87989 | 0.87989 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
3 | PSZ-AC_2:2 | Cooling | Sensible | 11978.51 | 0.87856 | 0.87856 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
4 | PSZ-AC_2:2 | Heating | Sensible | 15994.73 | 0.43052 | 0.43052 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
5 | PSZ-AC_3:3 | Cooling | Sensible | 12335.67 | 0.97371 | 0.97371 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
6 | PSZ-AC_3:3 | Heating | Sensible | 16121.64 | 0.43613 | 0.43613 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
7 | PSZ-AC_4:4 | Cooling | Sensible | 12269.52 | 0.96870 | 0.96870 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
8 | PSZ-AC_4:4 | Heating | Sensible | 16226.44 | 0.44077 | 0.44077 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
9 | PSZ-AC_5:5 | Cooling | Sensible | 12302.27 | 0.97121 | 0.97121 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
10 | PSZ-AC_5:5 | Heating | Sensible | 16420.40 | 0.44934 | 0.44934 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
11 | PSZ-AC_6:6 | Cooling | Sensible | 21603.74 | 1.56132 | 1.56132 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
12 | PSZ-AC_6:6 | Heating | Sensible | 32095.41 | 0.86573 | 0.86573 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
13 | PSZ-AC_7:7 | Cooling | Sensible | 11093.99 | 0.83034 | 0.83034 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
14 | PSZ-AC_7:7 | Heating | Sensible | 16729.41 | 0.46300 | 0.46300 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
15 | PSZ-AC_8:8 | Cooling | Sensible | 10989.71 | 0.82225 | 0.82225 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
16 | PSZ-AC_8:8 | Heating | Sensible | 16733.64 | 0.46319 | 0.46319 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
17 | PSZ-AC_9:9 | Cooling | Sensible | 10852.94 | 0.80783 | 0.80783 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
18 | PSZ-AC_9:9 | Heating | Sensible | 17053.83 | 0.47735 | 0.47735 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
19 | PSZ-AC_10:10 | Cooling | Sensible | 10821.42 | 0.80640 | 0.80640 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
20 | PSZ-AC_10:10 | Heating | Sensible | 18856.12 | 0.55703 | 0.55703 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:Uncontrolled | LGSTORE1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.57086 |
2 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.87069 |
3 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE2 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.97371 |
4 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.96870 |
5 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE4 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.97121 |
6 | AirTerminal:SingleDuct:Uncontrolled | LGSTORE2 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.52410 |
7 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE5 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.82457 |
8 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.81567 |
9 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE7 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.79903 |
10 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE8 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.78783 |
11 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.57086 |
12 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.57086 |
13 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.57086 |
14 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.57086 |
15 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.57086 |
16 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Main Design Air Flow Rate [m3/s] | 1.57086 |
17 | AirLoopHVAC | PSZ-AC_1:1 | User Heating Air Flow Ratio [] | 1.00000 |
18 | AirLoopHVAC | PSZ-AC_1:1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
19 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.87069 |
20 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.87069 |
21 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.87069 |
22 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.87069 |
23 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.87856 |
24 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Main Design Air Flow Rate [m3/s] | 0.87856 |
25 | AirLoopHVAC | PSZ-AC_2:2 | User Heating Air Flow Ratio [] | 1.00000 |
26 | AirLoopHVAC | PSZ-AC_2:2 | Calculated Heating Air Flow Ratio [] | 0.99105 |
27 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.97371 |
28 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.97371 |
29 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.97371 |
30 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.97371 |
31 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.97371 |
32 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Main Design Air Flow Rate [m3/s] | 0.97371 |
33 | AirLoopHVAC | PSZ-AC_3:3 | User Heating Air Flow Ratio [] | 1.00000 |
34 | AirLoopHVAC | PSZ-AC_3:3 | Calculated Heating Air Flow Ratio [] | 1.00000 |
35 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.96870 |
36 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.96870 |
37 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.96870 |
38 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.96870 |
39 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.96870 |
40 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Main Design Air Flow Rate [m3/s] | 0.96870 |
41 | AirLoopHVAC | PSZ-AC_4:4 | User Heating Air Flow Ratio [] | 1.00000 |
42 | AirLoopHVAC | PSZ-AC_4:4 | Calculated Heating Air Flow Ratio [] | 1.00000 |
43 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.97121 |
44 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.97121 |
45 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.97121 |
46 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.97121 |
47 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.97121 |
48 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Main Design Air Flow Rate [m3/s] | 0.97121 |
49 | AirLoopHVAC | PSZ-AC_5:5 | User Heating Air Flow Ratio [] | 1.00000 |
50 | AirLoopHVAC | PSZ-AC_5:5 | Calculated Heating Air Flow Ratio [] | 1.00000 |
51 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.52410 |
52 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.52410 |
53 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.52410 |
54 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.52410 |
55 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.56132 |
56 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Main Design Air Flow Rate [m3/s] | 1.56132 |
57 | AirLoopHVAC | PSZ-AC_6:6 | User Heating Air Flow Ratio [] | 1.00000 |
58 | AirLoopHVAC | PSZ-AC_6:6 | Calculated Heating Air Flow Ratio [] | 0.97616 |
59 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.82457 |
60 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.82457 |
61 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.82457 |
62 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.82457 |
63 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.83034 |
64 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Main Design Air Flow Rate [m3/s] | 0.83034 |
65 | AirLoopHVAC | PSZ-AC_7:7 | User Heating Air Flow Ratio [] | 1.00000 |
66 | AirLoopHVAC | PSZ-AC_7:7 | Calculated Heating Air Flow Ratio [] | 0.99304 |
67 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.81567 |
68 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.81567 |
69 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.81567 |
70 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.81567 |
71 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.82225 |
72 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Main Design Air Flow Rate [m3/s] | 0.82225 |
73 | AirLoopHVAC | PSZ-AC_8:8 | User Heating Air Flow Ratio [] | 1.00000 |
74 | AirLoopHVAC | PSZ-AC_8:8 | Calculated Heating Air Flow Ratio [] | 0.99200 |
75 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.79903 |
76 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.79903 |
77 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.79903 |
78 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.79903 |
79 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.80783 |
80 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Main Design Air Flow Rate [m3/s] | 0.80783 |
81 | AirLoopHVAC | PSZ-AC_9:9 | User Heating Air Flow Ratio [] | 1.00000 |
82 | AirLoopHVAC | PSZ-AC_9:9 | Calculated Heating Air Flow Ratio [] | 0.98911 |
83 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.78783 |
84 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.78783 |
85 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.78783 |
86 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.78783 |
87 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.80640 |
88 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Main Design Air Flow Rate [m3/s] | 0.80640 |
89 | AirLoopHVAC | PSZ-AC_10:10 | User Heating Air Flow Ratio [] | 1.00000 |
90 | AirLoopHVAC | PSZ-AC_10:10 | Calculated Heating Air Flow Ratio [] | 0.97698 |
91 | AirLoopHVAC | PSZ-AC_1:1 | Design Supply Air Flow Rate [m3/s] | 1.57086 |
92 | AirLoopHVAC | PSZ-AC_2:2 | Design Supply Air Flow Rate [m3/s] | 0.87856 |
93 | AirLoopHVAC | PSZ-AC_3:3 | Design Supply Air Flow Rate [m3/s] | 0.97371 |
94 | AirLoopHVAC | PSZ-AC_4:4 | Design Supply Air Flow Rate [m3/s] | 0.96870 |
95 | AirLoopHVAC | PSZ-AC_5:5 | Design Supply Air Flow Rate [m3/s] | 0.97121 |
96 | AirLoopHVAC | PSZ-AC_6:6 | Design Supply Air Flow Rate [m3/s] | 1.56132 |
97 | AirLoopHVAC | PSZ-AC_7:7 | Design Supply Air Flow Rate [m3/s] | 0.83034 |
98 | AirLoopHVAC | PSZ-AC_8:8 | Design Supply Air Flow Rate [m3/s] | 0.82225 |
99 | AirLoopHVAC | PSZ-AC_9:9 | Design Supply Air Flow Rate [m3/s] | 0.80783 |
100 | AirLoopHVAC | PSZ-AC_10:10 | Design Supply Air Flow Rate [m3/s] | 0.80640 |
101 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.57086 |
102 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41145 |
103 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.57086 |
104 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.57086 |
105 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.57086 |
106 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.03677 |
107 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.57086 |
108 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.78543 |
109 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.04724 |
110 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 26003.31071 |
111 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 26003.27000 |
112 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 13001.63500 |
113 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 13001.63500 |
114 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.79866 |
115 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.79866 |
116 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.79866 |
117 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.79866 |
118 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 26003.27000 |
119 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 48043.15718 |
120 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
121 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
122 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.57086 |
123 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1680.89167 |
124 | Coil:Heating:Fuel | PSZ-AC_1:1_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 48043.15718 |
125 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.87856 |
126 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20573 |
127 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.87856 |
128 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.87856 |
129 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.87856 |
130 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.87856 |
131 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.87856 |
132 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.43928 |
133 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.58571 |
134 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 14543.28754 |
135 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 14543.25000 |
136 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 7271.62500 |
137 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 7271.62500 |
138 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.79866 |
139 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.79866 |
140 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.79866 |
141 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.79866 |
142 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 14543.25000 |
143 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 25950.08303 |
144 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
145 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
146 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.87856 |
147 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 972.70290 |
148 | Coil:Heating:Fuel | PSZ-AC_2:2_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 25950.08303 |
149 | Controller:OutdoorAir | PSZ-AC_3:3_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.97371 |
150 | Controller:OutdoorAir | PSZ-AC_3:3_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20573 |
151 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.97371 |
152 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.97371 |
153 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.97371 |
154 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.97371 |
155 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.97371 |
156 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.48686 |
157 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.64914 |
158 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 16118.35789 |
159 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 16118.40000 |
160 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 8059.20000 |
161 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 8059.20000 |
162 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.79865 |
163 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.79866 |
164 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.79866 |
165 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.79866 |
166 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 16118.40000 |
167 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 28280.10715 |
168 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
169 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
170 | Fan:SystemModel | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.97371 |
171 | Fan:SystemModel | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1078.05447 |
172 | Coil:Heating:Fuel | PSZ-AC_3:3_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 28280.10715 |
173 | Controller:OutdoorAir | PSZ-AC_4:4_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.96870 |
174 | Controller:OutdoorAir | PSZ-AC_4:4_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20573 |
175 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.96870 |
176 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.96870 |
177 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.96870 |
178 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.96870 |
179 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.96870 |
180 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.48435 |
181 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.64580 |
182 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 16035.42460 |
183 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 16035.48000 |
184 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 8017.74000 |
185 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 8017.74000 |
186 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.79865 |
187 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.79866 |
188 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.79866 |
189 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.79866 |
190 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 16035.48000 |
191 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 28166.81293 |
192 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
193 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
194 | Fan:SystemModel | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.96870 |
195 | Fan:SystemModel | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1072.50843 |
196 | Coil:Heating:Fuel | PSZ-AC_4:4_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 28166.81293 |
197 | Controller:OutdoorAir | PSZ-AC_5:5_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.97121 |
198 | Controller:OutdoorAir | PSZ-AC_5:5_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20573 |
199 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.97121 |
200 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.97121 |
201 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.97121 |
202 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.97121 |
203 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.97121 |
204 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.48561 |
205 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.64747 |
206 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 16076.97401 |
207 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 16076.96000 |
208 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 8038.48000 |
209 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 8038.48000 |
210 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.79866 |
211 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.79866 |
212 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.79866 |
213 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.79866 |
214 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 16076.96000 |
215 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 28223.48614 |
216 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
217 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
218 | Fan:SystemModel | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.97121 |
219 | Fan:SystemModel | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1075.28298 |
220 | Coil:Heating:Fuel | PSZ-AC_5:5_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 28223.48614 |
221 | Controller:OutdoorAir | PSZ-AC_6:6_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.56132 |
222 | Controller:OutdoorAir | PSZ-AC_6:6_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41145 |
223 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.56132 |
224 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.56132 |
225 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.56132 |
226 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.03047 |
227 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.56132 |
228 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.78066 |
229 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.04088 |
230 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 25845.38984 |
231 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 25845.31000 |
232 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 12922.65500 |
233 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 12922.65500 |
234 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.79866 |
235 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.79866 |
236 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.79866 |
237 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.79866 |
238 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 25845.31000 |
239 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 46985.51623 |
240 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
241 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
242 | Fan:SystemModel | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.56132 |
243 | Fan:SystemModel | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1670.68123 |
244 | Coil:Heating:Fuel | PSZ-AC_6:6_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 46985.51623 |
245 | Controller:OutdoorAir | PSZ-AC_7:7_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.83034 |
246 | Controller:OutdoorAir | PSZ-AC_7:7_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20573 |
247 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.83034 |
248 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.83034 |
249 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.83034 |
250 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.83034 |
251 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.83034 |
252 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.41517 |
253 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.55356 |
254 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 13745.07532 |
255 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 13745.15000 |
256 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 6872.57500 |
257 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 6872.57500 |
258 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.79865 |
259 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.79866 |
260 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.79866 |
261 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.79866 |
262 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 13745.15000 |
263 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 24906.92037 |
264 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
265 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
266 | Fan:SystemModel | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.83034 |
267 | Fan:SystemModel | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 919.32326 |
268 | Coil:Heating:Fuel | PSZ-AC_7:7_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 24906.92037 |
269 | Controller:OutdoorAir | PSZ-AC_8:8_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.82225 |
270 | Controller:OutdoorAir | PSZ-AC_8:8_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20573 |
271 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.82225 |
272 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.82225 |
273 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.82225 |
274 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.82225 |
275 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.82225 |
276 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.41113 |
277 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.54817 |
278 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 13611.15709 |
279 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 13611.16000 |
280 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 6805.58000 |
281 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 6805.58000 |
282 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.79866 |
283 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.79866 |
284 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.79866 |
285 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.79866 |
286 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 13611.16000 |
287 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 24705.64081 |
288 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
289 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
290 | Fan:SystemModel | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.82225 |
291 | Fan:SystemModel | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 910.36127 |
292 | Coil:Heating:Fuel | PSZ-AC_8:8_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 24705.64081 |
293 | Controller:OutdoorAir | PSZ-AC_9:9_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.80783 |
294 | Controller:OutdoorAir | PSZ-AC_9:9_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20573 |
295 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.80783 |
296 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.80783 |
297 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.80783 |
298 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.80783 |
299 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.80783 |
300 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.40392 |
301 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.53855 |
302 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 13372.45489 |
303 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 13372.47000 |
304 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 6686.23500 |
305 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 6686.23500 |
306 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.79865 |
307 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.79866 |
308 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.79866 |
309 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.79866 |
310 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 13372.47000 |
311 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 24329.31582 |
312 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
313 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
314 | Fan:SystemModel | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.80783 |
315 | Fan:SystemModel | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 894.39701 |
316 | Coil:Heating:Fuel | PSZ-AC_9:9_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 24329.31582 |
317 | Controller:OutdoorAir | PSZ-AC_10:10_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.80640 |
318 | Controller:OutdoorAir | PSZ-AC_10:10_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20573 |
319 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.80640 |
320 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.80640 |
321 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.80640 |
322 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.80640 |
323 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.80640 |
324 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.40320 |
325 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.53760 |
326 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 13348.78331 |
327 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 13348.78000 |
328 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 6674.39000 |
329 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 6674.39000 |
330 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.79866 |
331 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.79866 |
332 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.79866 |
333 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.79866 |
334 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 13348.78000 |
335 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 24076.10092 |
336 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
337 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
338 | Fan:SystemModel | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.80640 |
339 | Fan:SystemModel | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 892.81241 |
340 | Coil:Heating:Fuel | PSZ-AC_10:10_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 24076.10092 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | 24772.2 | 11.11 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | 13854.7 | 32.99 | |||
3 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | 15355.3 | 41.60 | |||
4 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | 15276.3 | 53.64 | |||
5 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | 15315.8 | 65.34 | |||
6 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | 24621.7 | 49.25 | |||
7 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | 13094.4 | 110.50 | |||
8 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | 12966.8 | 123.42 | |||
9 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | 12739.4 | 137.46 | |||
10 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | 12716.8 | 149.54 |
Zone Name | # Surfaces | |
1 | LGSTORE1 | 15 |
2 | SMSTORE1 | 11 |
3 | SMSTORE2 | 11 |
4 | SMSTORE3 | 11 |
5 | SMSTORE4 | 11 |
6 | LGSTORE2 | 15 |
7 | SMSTORE5 | 11 |
8 | SMSTORE6 | 11 |
9 | SMSTORE7 | 11 |
10 | SMSTORE8 | 11 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | LGSTORE1_WALL_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | LGSTORE1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 71.15 | 78.94 | 71.15 | 0.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | LGSTORE1_WALL_3_DOOR_1 | Door | LGSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
4 | LGSTORE1_WALL_3_DOOR_2 | Door | LGSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
5 | LGSTORE1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
6 | LGSTORE1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 58.20 | 78.94 | 58.20 | 180.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
7 | LGSTORE1_WALL_1_WINDOW_1 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
8 | LGSTORE1_WALL_1_WINDOW_2 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
9 | LGSTORE1_WALL_1_WINDOW_3 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
10 | LGSTORE1_WALL_1_WINDOW_4 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
11 | LGSTORE1_WALL_1_DOOR_1 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
12 | LGSTORE1_WALL_1_DOOR_2 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
13 | LGSTORE1_FLOOR | Floor | CTF - ConductionTransferFunction | LGSTORE1_FLOOR_FFACTOR | 0.146 | 0.141 | 348.39 | 348.39 | 348.39 | 270.00 | 180.00 | 22.86 | 15.24 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | LGSTORE1_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 348.39 | 348.39 | 348.39 | 270.00 | 0.00 | 22.86 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
15 | LGSTORE1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 696.77 | 696.77 | 696.77 | 0.00 | 90.00 | 696.77 | 1.00 | 0.00 | LGSTORE1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
16 | SMSTORE1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 29.10 | 39.47 | 29.10 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
17 | SMSTORE1_WALL_1_WINDOW_1 | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
18 | SMSTORE1_WALL_1_WINDOW_2 | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
19 | SMSTORE1_WALL_1_DOOR | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
20 | SMSTORE1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | SMSTORE1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 35.57 | 39.47 | 35.57 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | SMSTORE1_WALL_3_DOOR | Door | SMSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
23 | SMSTORE1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE2_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
24 | SMSTORE1_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE1_FLOOR_FFACTOR | 8.283E-002 | 8.119E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | SMSTORE1_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
26 | SMSTORE1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
27 | SMSTORE2_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 29.12 | 39.47 | 29.12 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | SMSTORE2_WALL_1_WINDOW_1 | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
29 | SMSTORE2_WALL_1_WINDOW_2 | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
30 | SMSTORE2_WALL_1_DOOR | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
31 | SMSTORE2_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
32 | SMSTORE2_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | SMSTORE2_WALL_3_DOOR | Door | SMSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
34 | SMSTORE2_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE3_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | SMSTORE2_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE2_FLOOR_FFACTOR | 8.283E-002 | 8.119E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
36 | SMSTORE2_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
37 | SMSTORE2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
38 | SMSTORE3_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 29.12 | 39.47 | 29.12 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
39 | SMSTORE3_WALL_1_WINDOW_1 | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
40 | SMSTORE3_WALL_1_WINDOW_2 | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
41 | SMSTORE3_WALL_1_DOOR | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
42 | SMSTORE3_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE2_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | SMSTORE3_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | SMSTORE3_WALL_3_DOOR | Door | SMSTORE3_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
45 | SMSTORE3_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE4_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | SMSTORE3_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE3_FLOOR_FFACTOR | 8.283E-002 | 8.119E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
47 | SMSTORE3_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
48 | SMSTORE3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
49 | SMSTORE4_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 29.12 | 39.47 | 29.12 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | SMSTORE4_WALL_1_WINDOW_1 | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
51 | SMSTORE4_WALL_1_WINDOW_2 | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
52 | SMSTORE4_WALL_1_DOOR | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | SMSTORE4_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE3_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | SMSTORE4_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | SMSTORE4_WALL_3_DOOR | Door | SMSTORE4_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | SMSTORE4_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE2_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | SMSTORE4_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE4_FLOOR_FFACTOR | 8.283E-002 | 8.119E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | SMSTORE4_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | SMSTORE4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | LGSTORE2_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE4_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | LGSTORE2_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 71.19 | 78.94 | 71.19 | 0.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
62 | LGSTORE2_WALL_3_DOOR_1 | Door | LGSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
63 | LGSTORE2_WALL_3_DOOR_2 | Door | LGSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
64 | LGSTORE2_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE5_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | LGSTORE2_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 58.24 | 78.94 | 58.24 | 180.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
66 | LGSTORE2_WALL_1_WINDOW_1 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | LGSTORE2_WALL_1_WINDOW_2 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | LGSTORE2_WALL_1_WINDOW_3 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | LGSTORE2_WALL_1_WINDOW_4 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | LGSTORE2_WALL_1_DOOR_1 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
71 | LGSTORE2_WALL_1_DOOR_2 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
72 | LGSTORE2_FLOOR | Floor | CTF - ConductionTransferFunction | LGSTORE2_FLOOR_FFACTOR | 8.283E-002 | 8.119E-002 | 348.39 | 348.39 | 348.39 | 270.00 | 180.00 | 22.86 | 15.24 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
73 | LGSTORE2_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 348.39 | 348.39 | 348.39 | 270.00 | 0.00 | 22.86 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
74 | LGSTORE2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 696.77 | 696.77 | 696.77 | 0.00 | 90.00 | 696.77 | 1.00 | 0.00 | LGSTORE2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
75 | SMSTORE5_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 29.12 | 39.47 | 29.12 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | SMSTORE5_WALL_1_WINDOW_1 | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
77 | SMSTORE5_WALL_1_WINDOW_2 | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | SMSTORE5_WALL_1_DOOR | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
79 | SMSTORE5_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE2_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | SMSTORE5_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | SMSTORE5_WALL_3_DOOR | Door | SMSTORE5_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
82 | SMSTORE5_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE6_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
83 | SMSTORE5_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE5_FLOOR_FFACTOR | 8.283E-002 | 8.119E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
84 | SMSTORE5_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
85 | SMSTORE5_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE5_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
86 | SMSTORE6_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 29.12 | 39.47 | 29.12 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | SMSTORE6_WALL_1_WINDOW_1 | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
88 | SMSTORE6_WALL_1_WINDOW_2 | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
89 | SMSTORE6_WALL_1_DOOR | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
90 | SMSTORE6_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE5_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
91 | SMSTORE6_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
92 | SMSTORE6_WALL_3_DOOR | Door | SMSTORE6_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
93 | SMSTORE6_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE7_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | SMSTORE6_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE6_FLOOR_FFACTOR | 8.283E-002 | 8.119E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
95 | SMSTORE6_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
96 | SMSTORE6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
97 | SMSTORE7_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 29.12 | 39.47 | 29.12 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | SMSTORE7_WALL_1_WINDOW_1 | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
99 | SMSTORE7_WALL_1_WINDOW_2 | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
100 | SMSTORE7_WALL_1_DOOR | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
101 | SMSTORE7_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE6_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
102 | SMSTORE7_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 35.59 | 39.47 | 35.59 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | SMSTORE7_WALL_3_DOOR | Door | SMSTORE7_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
104 | SMSTORE7_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE8_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | SMSTORE7_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE7_FLOOR_FFACTOR | 8.283E-002 | 8.119E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
106 | SMSTORE7_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
107 | SMSTORE7_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE7_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
108 | SMSTORE8_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 29.12 | 39.47 | 29.12 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | SMSTORE8_WALL_1_WINDOW_1 | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
110 | SMSTORE8_WALL_1_WINDOW_2 | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
111 | SMSTORE8_WALL_1_DOOR | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
112 | SMSTORE8_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE7_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
113 | SMSTORE8_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | SMSTORE8_WALL_3_DOOR | Door | SMSTORE8_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
115 | SMSTORE8_WALL_4 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | SMSTORE8_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE8_FLOOR_FFACTOR | 0.211 | 0.201 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | SMSTORE8_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | SMSTORE8_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE8_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1 |
2 | VETERANS DAY | Holiday | InputFile | 11/11 | 1 |
3 | CHRISTMAS | Holiday | InputFile | 12/25 | 1 |
4 | INDEPENDENCE DAY | Holiday | InputFile | 07/04 | 1 |
5 | MLK DAY | Holiday | InputFile | 01/16 | 1 |
6 | PRESIDENTS DAY | Holiday | InputFile | 02/20 | 1 |
7 | MEMORIAL DAY | Holiday | InputFile | 05/29 | 1 |
8 | LABOR DAY | Holiday | InputFile | 09/04 | 1 |
9 | COLUMBUS DAY | Holiday | InputFile | 10/09 | 1 |
10 | THANKSGIVING | Holiday | InputFile | 11/23 | 1 |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
NumberofWarmupDays | |
1 | 11 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | LGSTORE1 | RunPeriod: RUNPERIOD 1 | 1.3272326687E-002 | 5.2588420780E-002 | Pass | Pass | 0.7490390440 | 7.3810022010 | Pass | Pass |
2 | SMSTORE1 | RunPeriod: RUNPERIOD 1 | 6.3494604555E-002 | 0.1836515687 | Pass | Pass | 0.4687420176 | 2.9119761035 | Pass | Pass |
3 | SMSTORE2 | RunPeriod: RUNPERIOD 1 | 1.7244063713E-002 | 3.0605348163E-002 | Pass | Pass | 0.1603535464 | 0.8492253764 | Pass | Pass |
4 | SMSTORE3 | RunPeriod: RUNPERIOD 1 | 2.2448916509E-002 | 5.5040266109E-002 | Pass | Pass | 4.6065710844E-002 | 0.1359244544 | Pass | Pass |
5 | SMSTORE4 | RunPeriod: RUNPERIOD 1 | 2.6888516617E-002 | 8.1912333483E-002 | Pass | Pass | 9.4916113450E-002 | 0.5339212056 | Pass | Pass |
6 | LGSTORE2 | RunPeriod: RUNPERIOD 1 | 3.4769549596E-002 | 0.1328814633 | Pass | Pass | 0.1101276266 | 0.6125767004 | Pass | Pass |
7 | SMSTORE5 | RunPeriod: RUNPERIOD 1 | 4.3800000534E-002 | 0.2090422736 | Pass | Pass | 0.1264128328 | 0.4725305394 | Pass | Pass |
8 | SMSTORE6 | RunPeriod: RUNPERIOD 1 | 4.2136231502E-002 | 0.2082423079 | Pass | Pass | 9.1760032117E-002 | 0.3110769098 | Pass | Pass |
9 | SMSTORE7 | RunPeriod: RUNPERIOD 1 | 4.2746296052E-002 | 0.2085487228 | Pass | Pass | 5.6930530955E-002 | 0.1683713064 | Pass | Pass |
10 | SMSTORE8 | RunPeriod: RUNPERIOD 1 | 6.1713806792E-002 | 0.2401663484 | Pass | Pass | 7.4404748681E-002 | 0.3775407507 | Pass | Pass |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2020-06-03 19:19:13
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | -4.30 | 0.00 | -4.30 | Wetbulb [C] | 1.20 | 110.00 |
WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 26.40 | 9.10 | 17.00 | Wetbulb [C] | 2.10 | 90.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2020-06-03 19:19:13
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_2 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE1_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 78.94 | 71.15 | 0.00 | 90.00 | N |
LGSTORE1_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 78.94 | 58.20 | 180.00 | 90.00 | S |
LGSTORE1_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 348.39 | 348.39 | 270.00 | 0.00 | |
SMSTORE1_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 29.10 | 180.00 | 90.00 | S |
SMSTORE1_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 35.57 | 0.00 | 90.00 | N |
SMSTORE1_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE2_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 29.12 | 180.00 | 90.00 | S |
SMSTORE2_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE2_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE3_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 29.12 | 180.00 | 90.00 | S |
SMSTORE3_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE3_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE4_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 29.12 | 180.00 | 90.00 | S |
SMSTORE4_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE4_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
LGSTORE2_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 78.94 | 71.19 | 0.00 | 90.00 | N |
LGSTORE2_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 78.94 | 58.24 | 180.00 | 90.00 | S |
LGSTORE2_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 348.39 | 348.39 | 270.00 | 0.00 | |
SMSTORE5_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 29.12 | 180.00 | 90.00 | S |
SMSTORE5_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE5_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE6_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 29.12 | 180.00 | 90.00 | S |
SMSTORE6_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE6_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE7_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 29.12 | 180.00 | 90.00 | S |
SMSTORE7_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE7_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE8_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 29.12 | 180.00 | 90.00 | S |
SMSTORE8_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE8_WALL_4 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE8_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
LGSTORE1_FLOOR | LGSTORE1_FLOOR_FFACTOR | 1.00 | 0.146 | 348.39 | 348.39 | 270.00 | 180.00 | ||
SMSTORE1_FLOOR | SMSTORE1_FLOOR_FFACTOR | 1.00 | 0.083 | 174.19 | 174.19 | 270.00 | 180.00 | ||
SMSTORE2_FLOOR | SMSTORE2_FLOOR_FFACTOR | 1.00 | 0.083 | 174.19 | 174.19 | 270.00 | 180.00 | ||
SMSTORE3_FLOOR | SMSTORE3_FLOOR_FFACTOR | 1.00 | 0.083 | 174.19 | 174.19 | 270.00 | 180.00 | ||
SMSTORE4_FLOOR | SMSTORE4_FLOOR_FFACTOR | 1.00 | 0.083 | 174.19 | 174.19 | 270.00 | 180.00 | ||
LGSTORE2_FLOOR | LGSTORE2_FLOOR_FFACTOR | 1.00 | 0.083 | 348.39 | 348.39 | 270.00 | 180.00 | ||
SMSTORE5_FLOOR | SMSTORE5_FLOOR_FFACTOR | 1.00 | 0.083 | 174.19 | 174.19 | 270.00 | 180.00 | ||
SMSTORE6_FLOOR | SMSTORE6_FLOOR_FFACTOR | 1.00 | 0.083 | 174.19 | 174.19 | 270.00 | 180.00 | ||
SMSTORE7_FLOOR | SMSTORE7_FLOOR_FFACTOR | 1.00 | 0.083 | 174.19 | 174.19 | 270.00 | 180.00 | ||
SMSTORE8_FLOOR | SMSTORE8_FLOOR_FFACTOR | 1.00 | 0.211 | 174.19 | 174.19 | 270.00 | 180.00 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.38_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.159 | 0.394 | 0.401 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE1_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.38_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.159 | 0.394 | 0.401 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE1_WALL_1_WINDOW_3 | NONRESWINDOW_U_0.38_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.159 | 0.394 | 0.401 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE1_WALL_1_WINDOW_4 | NONRESWINDOW_U_0.38_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.159 | 0.394 | 0.401 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE1_WALL_1_DOOR_1 | NONRESWINDOW_U_0.38_SHGC_0.4 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.159 | 0.394 | 0.401 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE1_WALL_1_DOOR_2 | NONRESWINDOW_U_0.38_SHGC_0.4 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.159 | 0.394 | 0.401 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE1_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.38_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.159 | 0.394 | 0.401 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE1_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.38_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.159 | 0.394 | 0.401 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE1_WALL_1_DOOR | NONRESWINDOW_U_0.38_SHGC_0.4 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.159 | 0.394 | 0.401 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE2_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.38_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.159 | 0.394 | 0.401 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE2_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.38_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.159 | 0.394 | 0.401 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE2_WALL_1_DOOR | NONRESWINDOW_U_0.38_SHGC_0.4 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.159 | 0.394 | 0.401 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE3_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.38_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.159 | 0.394 | 0.401 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE3_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.38_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.159 | 0.394 | 0.401 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE3_WALL_1_DOOR | NONRESWINDOW_U_0.38_SHGC_0.4 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.159 | 0.394 | 0.401 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE4_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.38_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.159 | 0.394 | 0.401 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE4_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.38_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.159 | 0.394 | 0.401 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE4_WALL_1_DOOR | NONRESWINDOW_U_0.38_SHGC_0.4 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.159 | 0.394 | 0.401 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE2_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.38_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.159 | 0.394 | 0.401 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE2_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.38_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.159 | 0.394 | 0.401 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE2_WALL_1_WINDOW_3 | NONRESWINDOW_U_0.38_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.159 | 0.394 | 0.401 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE2_WALL_1_WINDOW_4 | NONRESWINDOW_U_0.38_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.159 | 0.394 | 0.401 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE2_WALL_1_DOOR_1 | NONRESWINDOW_U_0.38_SHGC_0.4 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.159 | 0.394 | 0.401 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE2_WALL_1_DOOR_2 | NONRESWINDOW_U_0.38_SHGC_0.4 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.159 | 0.394 | 0.401 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE5_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.38_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.159 | 0.394 | 0.401 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE5_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.38_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.159 | 0.394 | 0.401 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE5_WALL_1_DOOR | NONRESWINDOW_U_0.38_SHGC_0.4 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.159 | 0.394 | 0.401 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE6_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.38_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.159 | 0.394 | 0.401 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE6_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.38_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.159 | 0.394 | 0.401 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE6_WALL_1_DOOR | NONRESWINDOW_U_0.38_SHGC_0.4 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.159 | 0.394 | 0.401 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE7_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.38_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.159 | 0.394 | 0.401 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE7_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.38_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.159 | 0.394 | 0.401 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE7_WALL_1_DOOR | NONRESWINDOW_U_0.38_SHGC_0.4 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.159 | 0.394 | 0.401 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE8_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.38_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.159 | 0.394 | 0.401 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE8_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.38_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.159 | 0.394 | 0.401 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE8_WALL_1_DOOR | NONRESWINDOW_U_0.38_SHGC_0.4 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.159 | 0.394 | 0.401 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | ||
Total or Average | 124.29 | 2.159 | 0.394 | 0.401 | ||||||||||||
North Total or Average | 0.00 | - | - | - | ||||||||||||
Non-North Total or Average | 124.29 | 2.159 | 0.394 | 0.401 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
LGSTORE1_WALL_3_DOOR_1 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.90 | LGSTORE1_WALL_3 |
LGSTORE1_WALL_3_DOOR_2 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.90 | LGSTORE1_WALL_3 |
SMSTORE1_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.90 | SMSTORE1_WALL_3 |
SMSTORE2_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE2_WALL_3 |
SMSTORE3_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE3_WALL_3 |
SMSTORE4_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE4_WALL_3 |
LGSTORE2_WALL_3_DOOR_1 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | LGSTORE2_WALL_3 |
LGSTORE2_WALL_3_DOOR_2 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | LGSTORE2_WALL_3 |
SMSTORE5_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE5_WALL_3 |
SMSTORE6_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE6_WALL_3 |
SMSTORE7_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE7_WALL_3 |
SMSTORE8_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE8_WALL_3 |
Report: Shading Summary
For: Entire Facility
Timestamp: 2020-06-03 19:19:13
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
LGSTORE1_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_DOOR_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_DOOR_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_DOOR_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_DOOR_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2020-06-03 19:19:13
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
LGSTORE1_LIGHTS | LGSTORE1 | 13.1675 | 348.39 | 4587.39 | LightsWired | TYPE1_LIGHT_SCH | 98.40 | 168.00 | 98.38 | 0.0000 | Y | 84.71 |
LGSTORE1_LIGHTS_ALLOWANCE | LGSTORE1 | 5.1990 | 348.39 | 1811.25 | LightsWired | TYPE1_LIGHT_SCH | 98.40 | 168.00 | 98.38 | 0.0000 | Y | 33.45 |
SMSTORE1_LIGHTS | SMSTORE1 | 13.1675 | 174.19 | 2293.69 | LightsWired | TYPE1_LIGHT_SCH | 98.40 | 168.00 | 98.38 | 0.0000 | Y | 42.36 |
SMSTORE1_LIGHTS_ALLOWANCE | SMSTORE1 | 6.6413 | 174.19 | 1156.88 | LightsWired | TYPE1_LIGHT_SCH | 98.40 | 168.00 | 98.38 | 0.0000 | Y | 21.36 |
SMSTORE2_LIGHTS | SMSTORE2 | 13.1675 | 174.19 | 2293.69 | LightsWired | TYPE2_LIGHT_SCH | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 33.57 |
SMSTORE2_LIGHTS_ALLOWANCE | SMSTORE2 | 4.4886 | 174.19 | 781.88 | LightsWired | TYPE2_LIGHT_SCH | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 11.44 |
SMSTORE3_LIGHTS | SMSTORE3 | 13.1675 | 174.19 | 2293.69 | LightsWired | TYPE2_LIGHT_SCH | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 33.57 |
SMSTORE3_LIGHTS_ALLOWANCE | SMSTORE3 | 4.4886 | 174.19 | 781.88 | LightsWired | TYPE2_LIGHT_SCH | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 11.44 |
SMSTORE4_LIGHTS | SMSTORE4 | 13.1675 | 174.19 | 2293.69 | LightsWired | TYPE2_LIGHT_SCH | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 33.57 |
SMSTORE4_LIGHTS_ALLOWANCE | SMSTORE4 | 4.4886 | 174.19 | 781.88 | LightsWired | TYPE2_LIGHT_SCH | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 11.44 |
LGSTORE2_LIGHTS | LGSTORE2 | 13.1675 | 348.39 | 4587.39 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 168.00 | 71.66 | 0.0000 | Y | 61.71 |
LGSTORE2_LIGHTS_ALLOWANCE | LGSTORE2 | 0.0000 | 348.39 | 0.00 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE5_LIGHTS | SMSTORE5 | 13.1675 | 174.19 | 2293.69 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 168.00 | 71.66 | 0.0000 | Y | 30.85 |
SMSTORE5_LIGHTS_ALLOWANCE | SMSTORE5 | 0.0000 | 174.19 | 0.00 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE6_LIGHTS | SMSTORE6 | 13.1675 | 174.19 | 2293.69 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 168.00 | 71.66 | 0.0000 | Y | 30.85 |
SMSTORE6_LIGHTS_ALLOWANCE | SMSTORE6 | 0.0000 | 174.19 | 0.00 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE7_LIGHTS | SMSTORE7 | 13.1675 | 174.19 | 2293.69 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 168.00 | 71.66 | 0.0000 | Y | 30.85 |
SMSTORE7_LIGHTS_ALLOWANCE | SMSTORE7 | 0.0000 | 174.19 | 0.00 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE8_LIGHTS | SMSTORE8 | 13.1675 | 174.19 | 2293.69 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 168.00 | 71.66 | 0.0000 | Y | 30.85 |
SMSTORE8_LIGHTS_ALLOWANCE | SMSTORE8 | 0.0000 | 174.19 | 0.00 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
Interior Lighting Total | 7.8548 | 4180.64 | 32838.07 | 502.03 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 314.61 | AstronomicalClock | - | 42.50 | 42.50 | 2.51 | |
EXTERIOR_LIGHTS_B | 6630.02 | AstronomicalClock | - | 83.54 | 71.23 | 88.64 | |
Exterior Lighting Total | 6944.63 | 91.15 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2020-06-03 19:19:13
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 26003.27 | 20767.77 | 5235.50 | 0.80 | 3.80 | |||
PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 14543.25 | 11615.11 | 2928.14 | 0.80 | 4.12 | |||
PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 16118.40 | 12873.12 | 3245.28 | 0.80 | 4.12 | |||
PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 16035.48 | 12806.90 | 3228.58 | 0.80 | 4.12 | |||
PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 16076.96 | 12840.02 | 3236.94 | 0.80 | 4.12 | |||
PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 25845.31 | 20641.62 | 5203.69 | 0.80 | 3.80 | |||
PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 13745.15 | 10977.70 | 2767.45 | 0.80 | 4.12 | |||
PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 13611.16 | 10870.69 | 2740.47 | 0.80 | 4.12 | |||
PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 13372.47 | 10680.06 | 2692.41 | 0.80 | 4.12 | |||
PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 13348.78 | 10661.14 | 2687.64 | 0.80 | 4.12 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | 24772.2 | 11.11 | ||||
PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | 13854.7 | 32.99 | ||||
PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | 15355.3 | 41.60 | ||||
PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | 15276.3 | 53.64 | ||||
PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | 15315.8 | 65.34 | ||||
PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | 24621.7 | 49.25 | ||||
PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | 13094.4 | 110.50 | ||||
PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | 12966.8 | 123.42 | ||||
PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | 12739.4 | 137.46 | ||||
PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | 12716.8 | 149.54 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
PSZ-AC_1:1_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 48043.16 | 0.80 | |
PSZ-AC_2:2_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 25950.08 | 0.80 | |
PSZ-AC_3:3_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 28280.11 | 0.80 | |
PSZ-AC_4:4_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 28166.81 | 0.80 | |
PSZ-AC_5:5_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 28223.49 | 0.80 | |
PSZ-AC_6:6_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 46985.52 | 0.80 | |
PSZ-AC_7:7_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 24906.92 | 0.80 | |
PSZ-AC_8:8_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 24705.64 | 0.80 | |
PSZ-AC_9:9_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 24329.32 | 0.80 | |
PSZ-AC_10:10_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 24076.10 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 1.57 | 1680.89 | 1070.05 | 1.00 | 1.35 | General | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 |
PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 0.88 | 972.70 | 1107.16 | 1.00 | 1.44 | General | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 |
PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 0.97 | 1078.05 | 1107.16 | 1.00 | 1.41 | General | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 |
PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 0.97 | 1072.51 | 1107.16 | 1.00 | 1.41 | General | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 |
PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 0.97 | 1075.28 | 1107.16 | 1.00 | 1.41 | General | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 |
PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 1.56 | 1670.68 | 1070.05 | 1.00 | 1.35 | General | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 |
PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 0.83 | 919.32 | 1107.16 | 1.00 | 1.45 | General | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 |
PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 0.82 | 910.36 | 1107.16 | 1.00 | 1.46 | General | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 |
PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 0.81 | 894.40 | 1107.16 | 1.00 | 1.46 | General | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 |
PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 0.81 | 892.81 | 1107.16 | 1.00 | 1.46 | General | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
GAS TANK1 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK2 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK3 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK4 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK5 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK6 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK7 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:19:13
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
LGSTORE1 | 17651.03 | 21181.24 | 60.80 | 1.309 | 1.571 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 23.89 | 23.89 | 0.00880 | 26.32 | 0.00838 | 0.411 | 0.00 |
SMSTORE1 | 10116.09 | 12139.30 | 69.69 | 0.726 | 0.871 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 23.89 | 23.89 | 0.00906 | 22.94 | 0.00838 | 0.206 | 0.00 |
SMSTORE2 | 11261.84 | 13514.21 | 77.58 | 0.811 | 0.974 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 23.89 | 23.89 | 0.00932 | 21.39 | 0.00838 | 0.206 | 0.00 |
SMSTORE3 | 11206.15 | 13447.38 | 77.20 | 0.807 | 0.969 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 23.89 | 23.89 | 0.00928 | 21.39 | 0.00838 | 0.206 | 0.00 |
SMSTORE4 | 11233.59 | 13480.30 | 77.39 | 0.809 | 0.971 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 23.89 | 23.89 | 0.00932 | 21.39 | 0.00838 | 0.206 | 0.00 |
LGSTORE2 | 17778.84 | 21334.61 | 61.24 | 1.270 | 1.524 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 23.89 | 23.89 | 0.00936 | 22.94 | 0.00838 | 0.411 | 0.00 |
SMSTORE5 | 9597.05 | 11516.46 | 66.11 | 0.687 | 0.825 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 23.89 | 23.89 | 0.00926 | 22.94 | 0.00838 | 0.206 | 0.00 |
SMSTORE6 | 9496.63 | 11395.96 | 65.42 | 0.680 | 0.816 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 23.89 | 23.89 | 0.00928 | 22.94 | 0.00838 | 0.206 | 0.00 |
SMSTORE7 | 9307.57 | 11169.08 | 64.12 | 0.666 | 0.799 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 23.89 | 23.89 | 0.00934 | 22.94 | 0.00838 | 0.206 | 0.00 |
SMSTORE8 | 9179.68 | 11015.62 | 63.24 | 0.657 | 0.788 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 23.89 | 23.89 | 0.00930 | 22.94 | 0.00838 | 0.206 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
LGSTORE1 | 16828.69 | 20194.42 | 57.97 | 0.733 | 0.880 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00679 | -4.30 | 0.00266 | 0.411 | 0.00 |
SMSTORE1 | 8234.19 | 9881.03 | 56.72 | 0.359 | 0.431 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00667 | -4.30 | 0.00266 | 0.206 | 0.00 |
SMSTORE2 | 8341.51 | 10009.81 | 57.46 | 0.363 | 0.436 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00668 | -4.30 | 0.00266 | 0.206 | 0.00 |
SMSTORE3 | 8430.14 | 10116.16 | 58.07 | 0.367 | 0.441 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00669 | -4.30 | 0.00266 | 0.206 | 0.00 |
SMSTORE4 | 8594.16 | 10312.99 | 59.20 | 0.374 | 0.449 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00670 | -4.30 | 0.00266 | 0.206 | 0.00 |
LGSTORE2 | 16557.90 | 19869.48 | 57.03 | 0.721 | 0.866 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00679 | -4.30 | 0.00266 | 0.411 | 0.00 |
SMSTORE5 | 8855.47 | 10626.56 | 61.00 | 0.386 | 0.463 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00672 | -4.30 | 0.00266 | 0.206 | 0.00 |
SMSTORE6 | 8859.05 | 10630.86 | 61.03 | 0.386 | 0.463 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00672 | -4.30 | 0.00266 | 0.206 | 0.00 |
SMSTORE7 | 9129.81 | 10955.78 | 62.89 | 0.398 | 0.477 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00675 | -4.30 | 0.00266 | 0.206 | 0.00 |
SMSTORE8 | 10653.94 | 12784.73 | 73.39 | 0.464 | 0.557 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00684 | -4.30 | 0.00266 | 0.206 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC_1:1 | 1.57 | 1.57 | 0.88 | 0.88 | 1.5709 | 1.5709 | 1.5709 | 1.0000 | 1.0000 |
PSZ-AC_2:2 | 0.88 | 0.88 | 0.43 | 0.43 | 0.8786 | 0.8707 | 0.8786 | 0.9910 | 1.0000 |
PSZ-AC_3:3 | 0.97 | 0.97 | 0.44 | 0.44 | 0.9737 | 0.9737 | 0.9737 | 1.0000 | 1.0000 |
PSZ-AC_4:4 | 0.97 | 0.97 | 0.44 | 0.44 | 0.9687 | 0.9687 | 0.9687 | 1.0000 | 1.0000 |
PSZ-AC_5:5 | 0.97 | 0.97 | 0.45 | 0.45 | 0.9712 | 0.9712 | 0.9712 | 1.0000 | 1.0000 |
PSZ-AC_6:6 | 1.56 | 1.56 | 0.87 | 0.87 | 1.5613 | 1.5241 | 1.5613 | 0.9762 | 1.0000 |
PSZ-AC_7:7 | 0.83 | 0.83 | 0.46 | 0.46 | 0.8303 | 0.8246 | 0.8303 | 0.9930 | 1.0000 |
PSZ-AC_8:8 | 0.82 | 0.82 | 0.46 | 0.46 | 0.8222 | 0.8157 | 0.8222 | 0.9920 | 1.0000 |
PSZ-AC_9:9 | 0.81 | 0.81 | 0.48 | 0.48 | 0.8078 | 0.7990 | 0.8078 | 0.9891 | 1.0000 |
PSZ-AC_10:10 | 0.81 | 0.81 | 0.56 | 0.56 | 0.8064 | 0.7878 | 0.8064 | 0.9770 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_1:1 | 13001.635 | 0.000 | 1.570860 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 13001.64 | 12542.33 | 1.570860 | 24.55 | 16.62 | 0.00869242 | 12.80 | 12.00 | 0.00850000 | 26.40 | 0.00838408 | 17.00 | 26.1929 | 23.89 | 0.00880206 | 47.1698 | 17642.82 | 0.00 | -999.00 | -999.00 |
PSZ-AC_1:1_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_1:1 | 48043.157 | 48043.157 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 48043.16 | 48043.16 | 1.570857 | 9.23 | 6.38 | 0.00485894 | 40.00 | 21.02 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 26.1929 | 21.11 | 0.00679251 | 43.2439 | 16828.69 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_2:2 | 7271.625 | 0.000 | 0.878560 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 | 7271.62 | 7028.59 | 0.878560 | 24.47 | 16.58 | 0.00868067 | 12.80 | 12.00 | 0.00850000 | 26.32 | 0.00838408 | 16.97 | 23.4164 | 23.89 | 0.00905855 | 48.5292 | 9631.25 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_2:2 | 25950.083 | 25950.083 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 25950.08 | 25950.08 | 0.878558 | 8.97 | 6.12 | 0.00475191 | 40.00 | 21.02 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 23.4164 | 21.11 | 0.00666857 | 42.4638 | 8234.19 | 0.00 | -999.00 | -999.00 |
PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_3:3 | 8059.200 | 0.000 | 0.973710 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 8059.20 | 7127.96 | 0.973710 | 23.38 | 16.58 | 0.00912600 | 12.80 | 12.00 | 0.00850000 | 21.39 | 0.00838408 | 15.22 | 21.1281 | 23.89 | 0.00932475 | 49.9391 | 11261.84 | 0.00 | -999.00 | -999.00 |
PSZ-AC_3:3_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_3:3 | 28280.107 | 28280.107 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 28280.11 | 28280.11 | 0.973713 | 9.12 | 6.23 | 0.00478107 | 40.00 | 21.02 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 21.1281 | 21.11 | 0.00667711 | 42.5176 | 8341.51 | 0.00 | -999.00 | -999.00 |
PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_4:4 | 8017.740 | 0.000 | 0.968700 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 8017.74 | 7134.23 | 0.968700 | 23.38 | 16.55 | 0.00909328 | 12.80 | 12.00 | 0.00850000 | 21.39 | 0.00838408 | 15.22 | 21.2374 | 23.89 | 0.00928451 | 49.7259 | 11206.15 | 0.00 | -999.00 | -999.00 |
PSZ-AC_4:4_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_4:4 | 28166.813 | 28166.813 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 28166.81 | 28166.81 | 0.968703 | 9.25 | 6.32 | 0.00480530 | 40.00 | 21.02 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 21.2373 | 21.11 | 0.00668516 | 42.5683 | 8430.14 | 0.00 | -999.00 | -999.00 |
PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_5:5 | 8038.480 | 0.000 | 0.971210 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 8038.48 | 7112.87 | 0.971210 | 23.38 | 16.58 | 0.00912346 | 12.80 | 12.00 | 0.00850000 | 21.39 | 0.00838408 | 15.22 | 21.1825 | 23.89 | 0.00932218 | 49.9254 | 11233.59 | 0.00 | -999.00 | -999.00 |
PSZ-AC_5:5_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_5:5 | 28223.486 | 28223.486 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 28223.49 | 28223.49 | 0.971209 | 9.48 | 6.49 | 0.00484951 | 40.00 | 21.02 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 21.1825 | 21.11 | 0.00670053 | 42.6652 | 8594.16 | 0.00 | -999.00 | -999.00 |
PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_6:6 | 12922.655 | 0.000 | 1.561320 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 | 12922.66 | 12460.91 | 1.561320 | 24.54 | 16.62 | 0.00869461 | 12.80 | 12.00 | 0.00850000 | 26.32 | 0.00838408 | 16.97 | 26.3529 | 23.89 | 0.00935872 | 50.1170 | 17778.84 | 0.00 | -999.00 | -999.00 |
PSZ-AC_6:6_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_6:6 | 46985.516 | 46985.516 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 46985.52 | 46985.52 | 1.561315 | 9.03 | 6.24 | 0.00482521 | 40.00 | 21.02 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 26.3530 | 21.11 | 0.00678849 | 43.2185 | 16557.90 | 0.00 | -999.00 | -999.00 |
PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_7:7 | 6872.575 | 0.000 | 0.830340 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 | 6872.57 | 6635.84 | 0.830340 | 24.52 | 16.61 | 0.00868711 | 12.80 | 12.00 | 0.00850000 | 26.32 | 0.00838408 | 16.97 | 24.7762 | 23.89 | 0.00925656 | 49.5771 | 9597.05 | 0.00 | -999.00 | -999.00 |
PSZ-AC_7:7_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_7:7 | 24906.920 | 24906.920 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 24906.92 | 24906.92 | 0.830345 | 9.82 | 6.74 | 0.00491646 | 40.00 | 21.02 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 24.7761 | 21.11 | 0.00672271 | 42.8050 | 8855.47 | 0.00 | -999.00 | -999.00 |
PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_8:8 | 6805.580 | 0.000 | 0.822250 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 | 6805.58 | 6570.34 | 0.822250 | 24.53 | 16.61 | 0.00868787 | 12.80 | 12.00 | 0.00850000 | 26.32 | 0.00838408 | 16.97 | 25.0200 | 23.89 | 0.00928380 | 49.7212 | 9496.63 | 0.00 | -999.00 | -999.00 |
PSZ-AC_8:8_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_8:8 | 24705.641 | 24705.641 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 24705.64 | 24705.64 | 0.822250 | 9.82 | 6.74 | 0.00491741 | 40.00 | 21.02 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 25.0200 | 21.11 | 0.00672312 | 42.8076 | 8859.05 | 0.00 | -999.00 | -999.00 |
PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_9:9 | 6686.235 | 0.000 | 0.807830 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 | 6686.23 | 6454.09 | 0.807830 | 24.54 | 16.61 | 0.00868886 | 12.80 | 12.00 | 0.00850000 | 26.32 | 0.00838408 | 16.97 | 25.4666 | 23.89 | 0.00933790 | 50.0071 | 9307.57 | 0.00 | -999.00 | -999.00 |
PSZ-AC_9:9_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_9:9 | 24329.316 | 24329.316 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 24329.32 | 24329.32 | 0.807831 | 10.16 | 6.98 | 0.00498384 | 40.00 | 21.02 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 25.4666 | 21.11 | 0.00674575 | 42.9502 | 9129.81 | 0.00 | -999.00 | -999.00 |
PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_10:10 | 6674.390 | 0.000 | 0.806400 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:10:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 | 6674.39 | 6440.08 | 0.806400 | 24.45 | 16.58 | 0.00868984 | 12.80 | 12.00 | 0.00850000 | 26.02 | 0.00838408 | 16.87 | 25.5117 | 23.89 | 0.00930399 | 49.8277 | 9179.68 | 0.00 | -999.00 | -999.00 |
PSZ-AC_10:10_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_10:10 | 24076.101 | 24076.101 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 24076.10 | 24076.10 | 0.806400 | 11.72 | 8.09 | 0.00529685 | 40.00 | 21.02 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 25.5118 | 21.11 | 0.00684241 | 43.5594 | 10653.94 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2020-06-03 19:19:13
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | LGSTORE1 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 13001.635 | 0.000 | 1.570860 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9988 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 13001.64 | 12542.33 | 1.0000 | 1.87147864 | 1.570860 | 24.55 | 16.62 | 0.00869242 | 46801.7 | 12.80 | 12.00 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 13001.64 | 26.40 | 0.00838408 | 17.00 | 0.41145340 | 26.1929 | 23.89 | 0.00880191 | 23.89 | 0.00880206 | 47.1698 | 17642.82 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_1:1_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | LGSTORE1 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 48043.157 | 48043.157 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.570857 | 1.87147553 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 48043.16 | 48043.16 | 1.0000 | 1.87147553 | 1.570857 | 9.23 | 6.38 | 0.00485894 | 21506.6 | 40.00 | 21.02 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 48043.16 | -4.30 | 0.00265759 | -4.30 | 0.41145340 | 26.1929 | 21.11 | 0.00679251 | 21.11 | 0.00679251 | 43.2439 | 16828.69 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | SMSTORE1 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 7271.625 | 0.000 | 0.878560 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9769 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 | 7271.62 | 7028.59 | 1.0000 | 1.04669179 | 0.878560 | 24.47 | 16.58 | 0.00868067 | 46696.8 | 12.80 | 12.00 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7271.62 | 26.32 | 0.00838408 | 16.97 | 0.20572670 | 23.4164 | 23.89 | 0.00877434 | 23.89 | 0.00905855 | 48.5292 | 9631.25 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | SMSTORE1 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 25950.083 | 25950.083 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.878558 | 1.04668913 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 25950.08 | 25950.08 | 1.0000 | 1.04668913 | 0.878558 | 8.97 | 6.12 | 0.00475191 | 20973.4 | 40.00 | 21.02 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 25950.08 | -4.30 | 0.00265759 | -4.30 | 0.20572670 | 23.4164 | 21.11 | 0.00666857 | 21.11 | 0.00666857 | 42.4638 | 8234.19 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_3:3 | SMSTORE2 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 8059.200 | 0.000 | 0.973710 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.8048 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 8059.20 | 7127.96 | 1.0000 | 1.16005084 | 0.973710 | 23.38 | 16.58 | 0.00912600 | 46715.7 | 12.80 | 12.00 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8059.20 | 21.39 | 0.00838408 | 15.22 | 0.20572670 | 21.1281 | 23.91 | 0.00932475 | 23.89 | 0.00932475 | 49.9391 | 11261.84 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_3:3_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_3:3 | SMSTORE2 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 28280.107 | 28280.107 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.973713 | 1.16005400 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 28280.11 | 28280.11 | 1.0000 | 1.16005400 | 0.973713 | 9.12 | 6.23 | 0.00478107 | 21205.2 | 40.00 | 21.02 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 28280.11 | -4.30 | 0.00265759 | -4.30 | 0.20572670 | 21.1281 | 21.11 | 0.00667711 | 21.11 | 0.00667711 | 42.5176 | 8341.51 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_4:4 | SMSTORE3 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 8017.740 | 0.000 | 0.968700 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.7440 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 8017.74 | 7134.23 | 1.0000 | 1.15408207 | 0.968700 | 23.38 | 16.55 | 0.00909328 | 46630.1 | 12.80 | 12.00 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8017.74 | 21.39 | 0.00838408 | 15.22 | 0.20572670 | 21.2374 | 23.92 | 0.00928451 | 23.89 | 0.00928451 | 49.7259 | 11206.15 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_4:4_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_4:4 | SMSTORE3 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 28166.813 | 28166.813 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.968703 | 1.15408611 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 28166.81 | 28166.81 | 1.0000 | 1.15408611 | 0.968703 | 9.25 | 6.32 | 0.00480530 | 21393.9 | 40.00 | 21.02 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 28166.81 | -4.30 | 0.00265759 | -4.30 | 0.20572670 | 21.2373 | 21.11 | 0.00668516 | 21.11 | 0.00668516 | 42.5683 | 8430.14 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_5:5 | SMSTORE4 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 8038.480 | 0.000 | 0.971210 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.8001 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 8038.48 | 7112.87 | 1.0000 | 1.15707241 | 0.971210 | 23.38 | 16.58 | 0.00912346 | 46707.8 | 12.80 | 12.00 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8038.48 | 21.39 | 0.00838408 | 15.22 | 0.20572670 | 21.1825 | 23.91 | 0.00932218 | 23.89 | 0.00932218 | 49.9254 | 11233.59 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_5:5_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_5:5 | SMSTORE4 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 28223.486 | 28223.486 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.971209 | 1.15707170 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 28223.49 | 28223.49 | 1.0000 | 1.15707170 | 0.971209 | 9.48 | 6.49 | 0.00484951 | 21734.7 | 40.00 | 21.02 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 28223.49 | -4.30 | 0.00265759 | -4.30 | 0.20572670 | 21.1825 | 21.11 | 0.00670053 | 21.11 | 0.00670053 | 42.6652 | 8594.16 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_6:6 | LGSTORE2 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 12922.655 | 0.000 | 1.561320 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.0028 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 | 12922.66 | 12460.91 | 1.0000 | 1.86011295 | 1.561320 | 24.54 | 16.62 | 0.00869461 | 46801.1 | 12.80 | 12.00 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 12922.66 | 26.32 | 0.00838408 | 16.97 | 0.41145340 | 26.3529 | 23.89 | 0.00880813 | 23.89 | 0.00935872 | 50.1170 | 17778.84 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_6:6_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_6:6 | LGSTORE2 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 46985.516 | 46985.516 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.561315 | 1.86010741 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 46985.52 | 46985.52 | 1.0000 | 1.86010741 | 1.561315 | 9.03 | 6.24 | 0.00482521 | 21224.7 | 40.00 | 21.02 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 46985.52 | -4.30 | 0.00265759 | -4.30 | 0.41145340 | 26.3530 | 21.11 | 0.00678849 | 21.11 | 0.00678849 | 43.2185 | 16557.90 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_7:7 | SMSTORE5 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 6872.575 | 0.000 | 0.830340 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9889 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 | 6872.57 | 6635.84 | 1.0000 | 0.98924384 | 0.830340 | 24.52 | 16.61 | 0.00868711 | 46763.5 | 12.80 | 12.00 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 6872.57 | 26.32 | 0.00838408 | 16.97 | 0.20572670 | 24.7762 | 23.89 | 0.00879372 | 23.89 | 0.00925656 | 49.5771 | 9597.05 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_7:7_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_7:7 | SMSTORE5 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 24906.920 | 24906.920 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.830345 | 0.98924930 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 24906.92 | 24906.92 | 1.0000 | 0.98924930 | 0.830345 | 9.82 | 6.74 | 0.00491646 | 22251.4 | 40.00 | 21.02 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 24906.92 | -4.30 | 0.00265759 | -4.30 | 0.20572670 | 24.7761 | 21.11 | 0.00672271 | 21.11 | 0.00672271 | 42.8050 | 8855.47 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_8:8 | SMSTORE6 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 6805.580 | 0.000 | 0.822250 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9903 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 | 6805.58 | 6570.34 | 1.0000 | 0.97960564 | 0.822250 | 24.53 | 16.61 | 0.00868787 | 46771.9 | 12.80 | 12.00 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 6805.58 | 26.32 | 0.00838408 | 16.97 | 0.20572670 | 25.0200 | 23.89 | 0.00879619 | 23.89 | 0.00928380 | 49.7212 | 9496.63 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_8:8_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_8:8 | SMSTORE6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 24705.641 | 24705.641 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.822250 | 0.97960563 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 24705.64 | 24705.64 | 1.0000 | 0.97960563 | 0.822250 | 9.82 | 6.74 | 0.00491741 | 22258.4 | 40.00 | 21.02 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 24705.64 | -4.30 | 0.00265759 | -4.30 | 0.20572670 | 25.0200 | 21.11 | 0.00672312 | 21.11 | 0.00672312 | 42.8076 | 8859.05 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_9:9 | SMSTORE7 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 6686.235 | 0.000 | 0.807830 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9921 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 | 6686.23 | 6454.09 | 1.0000 | 0.96242605 | 0.807830 | 24.54 | 16.61 | 0.00868886 | 46783.1 | 12.80 | 12.00 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 6686.23 | 26.32 | 0.00838408 | 16.97 | 0.20572670 | 25.4666 | 23.89 | 0.00879951 | 23.89 | 0.00933790 | 50.0071 | 9307.57 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_9:9_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_9:9 | SMSTORE7 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 24329.316 | 24329.316 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.807831 | 0.96242709 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 24329.32 | 24329.32 | 1.0000 | 0.96242709 | 0.807831 | 10.16 | 6.98 | 0.00498384 | 22765.2 | 40.00 | 21.02 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 24329.32 | -4.30 | 0.00265759 | -4.30 | 0.20572670 | 25.4666 | 21.11 | 0.00674575 | 21.11 | 0.00674575 | 42.9502 | 9129.81 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_10:10 | SMSTORE8 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 6674.390 | 0.000 | 0.806400 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9940 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:10:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 | 6674.39 | 6440.08 | 1.0000 | 0.96072239 | 0.806400 | 24.45 | 16.58 | 0.00868984 | 46700.6 | 12.80 | 12.00 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 6674.39 | 26.02 | 0.00838408 | 16.87 | 0.20572670 | 25.5117 | 23.89 | 0.00880021 | 23.89 | 0.00930399 | 49.8277 | 9179.68 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_10:10_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_10:10 | SMSTORE8 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 24076.101 | 24076.101 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.806400 | 0.96072197 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 24076.10 | 24076.10 | 1.0000 | 0.96072197 | 0.806400 | 11.72 | 8.09 | 0.00529685 | 25143.3 | 40.00 | 21.02 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 24076.10 | -4.30 | 0.00265759 | -4.30 | 0.20572670 | 25.5118 | 21.11 | 0.00684241 | 21.11 | 0.00684241 | 43.5594 | 10653.94 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2020-06-03 19:19:13
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-AC_1:1_OA_CONTROLLER | DifferentialDryBulb | 0.41 | 1.57 | - | |||
PSZ-AC_3:3_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 0.97 | - | |||
PSZ-AC_4:4_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 0.97 | - | |||
PSZ-AC_5:5_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 0.97 | - | |||
PSZ-AC_6:6_OA_CONTROLLER | DifferentialDryBulb | 0.41 | 1.56 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
LGSTORE1 | 1200.50 | 4215.67 | 277.50 |
SMSTORE1 | 1233.50 | 3733.50 | 124.83 |
SMSTORE2 | 967.50 | 2836.17 | 74.50 |
SMSTORE3 | 965.00 | 2868.00 | 106.50 |
SMSTORE4 | 921.17 | 2967.00 | 155.83 |
LGSTORE2 | 804.33 | 3038.00 | 261.83 |
SMSTORE5 | 796.67 | 3014.33 | 324.33 |
SMSTORE6 | 804.17 | 3056.17 | 361.00 |
SMSTORE7 | 849.17 | 3147.67 | 463.17 |
SMSTORE8 | 1216.67 | 3318.67 | 967.00 |
Facility | 2322.17 | 4781.33 | 1155.17 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
LGSTORE1 | 0.67 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 0.00 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 0.67 | 0.00 | 0.00 | 0.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2020-06-03 19:19:13
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
LGSTORE1 | 9.03 | 30.00 | 1805.20 | 0.890 | 0.223 | 0.000 | 0.000 |
SMSTORE1 | 4.51 | 15.00 | 902.60 | 0.653 | 0.242 | 0.000 | 0.000 |
SMSTORE2 | 3.78 | 15.00 | 902.60 | 1.144 | 0.317 | 0.000 | 0.000 |
SMSTORE3 | 3.78 | 15.00 | 902.60 | 1.135 | 0.317 | 0.000 | 0.000 |
SMSTORE4 | 3.78 | 15.00 | 902.60 | 1.112 | 0.317 | 0.000 | 0.000 |
LGSTORE2 | 13.21 | 30.00 | 1805.20 | 0.922 | 0.304 | 0.000 | 0.000 |
SMSTORE5 | 6.60 | 15.00 | 902.60 | 0.831 | 0.339 | 0.000 | 0.000 |
SMSTORE6 | 6.60 | 15.00 | 902.60 | 0.831 | 0.339 | 0.000 | 0.000 |
SMSTORE7 | 6.60 | 15.00 | 902.60 | 0.831 | 0.339 | 0.000 | 0.000 |
SMSTORE8 | 6.60 | 15.00 | 902.60 | 0.830 | 0.350 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
LGSTORE1 | 9.03 | 30.00 | 1805.20 | 0.000 | 0.000 | 0.000 | 0.000 |
SMSTORE1 | 4.51 | 15.00 | 902.60 | 0.000 | 0.000 | 0.000 | 0.000 |
SMSTORE2 | 3.78 | 15.00 | 902.60 | 0.807 | 0.000 | 0.000 | 0.000 |
SMSTORE3 | 3.78 | 15.00 | 902.60 | 0.807 | 0.000 | 0.000 | 0.000 |
SMSTORE4 | 3.78 | 15.00 | 902.60 | 0.807 | 0.000 | 0.000 | 0.000 |
LGSTORE2 | 13.21 | 30.00 | 1805.20 | 0.805 | 0.000 | 0.000 | 0.000 |
SMSTORE5 | 6.60 | 15.00 | 902.60 | 0.802 | 0.000 | 0.000 | 0.000 |
SMSTORE6 | 6.60 | 15.00 | 902.60 | 0.802 | 0.000 | 0.000 | 0.000 |
SMSTORE7 | 6.60 | 15.00 | 902.60 | 0.802 | 0.000 | 0.000 | 0.000 |
SMSTORE8 | 6.60 | 15.00 | 902.60 | 0.801 | 0.000 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2020-06-03 19:19:13
Surfaces by ClassTotal | Outdoors | |
Wall | 40 | 22 |
Floor | 10 | 10 |
Roof | 10 | 10 |
Internal Mass | 10 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 36 | 36 |
Door | 12 | 12 |
Glass Door | 12 | 12 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 10 |
Conditioned Zones | 10 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 0 |
Defaulted Fields | 0 |
Fields with Defaults | 0 |
Autosized Fields | 0 |
Autosizable Fields | 0 |
Autocalculated Fields | 0 |
Autocalculatable Fields | 0 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2020-06-03 19:19:13
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 959.48 | 3309.32 | 29-JAN-08:00 | 76510.93 | 22-JUL-16:00 |
Electricity:Building | 630.75 | 2091.32 | 01-JAN-00:10 | 39285.70 | 01-JAN-11:10 |
Electricity:Zone:LGSTORE1 | 144.52 | 394.83 | 01-JAN-00:10 | 7426.96 | 01-JAN-10:10 |
InteriorLights:Electricity | 502.03 | 1641.90 | 01-JAN-00:10 | 31196.17 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:LGSTORE1 | 118.16 | 319.93 | 01-JAN-00:10 | 6078.71 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity | 502.03 | 1641.90 | 01-JAN-00:10 | 31196.17 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE1 | 76.90 | 209.98 | 01-JAN-00:10 | 3952.17 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE1 | 63.72 | 172.53 | 01-JAN-00:10 | 3278.04 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE2 | 55.48 | 191.23 | 01-JAN-00:10 | 3595.92 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE2 | 45.01 | 153.78 | 01-JAN-00:10 | 2921.79 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE3 | 55.48 | 191.23 | 01-JAN-00:10 | 3595.92 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE3 | 45.01 | 153.78 | 01-JAN-00:10 | 2921.79 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE4 | 55.48 | 191.23 | 01-JAN-00:10 | 3595.92 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE4 | 45.01 | 153.78 | 01-JAN-00:10 | 2921.79 | 01-JAN-10:10 |
Electricity:Zone:LGSTORE2 | 80.97 | 304.27 | 01-JAN-00:10 | 5706.27 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:LGSTORE2 | 61.71 | 229.37 | 01-JAN-00:10 | 4358.02 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE5 | 40.48 | 152.14 | 01-JAN-00:10 | 2853.14 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE5 | 30.85 | 114.68 | 01-JAN-00:10 | 2179.01 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE6 | 40.48 | 152.14 | 01-JAN-00:10 | 2853.14 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE6 | 30.85 | 114.68 | 01-JAN-00:10 | 2179.01 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE7 | 40.48 | 152.14 | 01-JAN-00:10 | 2853.14 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE7 | 30.85 | 114.68 | 01-JAN-00:10 | 2179.01 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE8 | 40.48 | 152.14 | 01-JAN-00:10 | 2853.14 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE8 | 30.85 | 114.68 | 01-JAN-00:10 | 2179.01 | 01-JAN-11:10 |
InteriorEquipment:Electricity | 128.72 | 449.42 | 01-JAN-00:10 | 8089.53 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:LGSTORE1 | 26.36 | 74.90 | 01-JAN-00:10 | 1348.26 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity | 128.72 | 449.42 | 01-JAN-00:10 | 8089.53 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE1 | 13.18 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE2 | 10.47 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE3 | 10.47 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE4 | 10.47 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:LGSTORE2 | 19.26 | 74.90 | 01-JAN-00:10 | 1348.26 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE5 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE6 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE7 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE8 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
Electricity:Plant | 65.19 | 1218.00 | 18-JAN-07:10 | 11862.24 | 04-JAN-14:20 |
WaterSystems:Electricity | 65.19 | 1218.00 | 18-JAN-07:10 | 11862.24 | 04-JAN-14:20 |
Water Heater:WaterSystems:Electricity | 65.19 | 1218.00 | 18-JAN-07:10 | 11862.24 | 04-JAN-14:20 |
ElectricityPurchased:Facility | 959.48 | 3309.32 | 29-JAN-08:00 | 76510.93 | 22-JUL-16:00 |
ElectricityPurchased:Plant | 959.48 | 3309.32 | 29-JAN-08:00 | 76510.93 | 22-JUL-16:00 |
Cogeneration:ElectricityPurchased | 959.48 | 3309.32 | 29-JAN-08:00 | 76510.93 | 22-JUL-16:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 959.48 | 3309.32 | 29-JAN-08:00 | 76510.93 | 22-JUL-16:00 |
ElectricityNet:Plant | 959.48 | 3309.32 | 29-JAN-08:00 | 76510.93 | 22-JUL-16:00 |
Cogeneration:ElectricityNet | 959.48 | 3309.32 | 29-JAN-08:00 | 76510.93 | 22-JUL-16:00 |
Electricity:HVAC | 172.38 | 0.00 | 01-JAN-00:10 | 29748.55 | 22-JUL-15:00 |
Fans:Electricity | 156.16 | 0.00 | 01-JAN-00:10 | 10167.68 | 10-JAN-09:10 |
General:Fans:Electricity | 156.16 | 0.00 | 01-JAN-00:10 | 10167.68 | 10-JAN-09:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 16.22 | 0.00 | 01-JAN-00:10 | 20347.41 | 22-JUL-15:00 |
ExteriorLights:Electricity | 91.15 | 0.00 | 01-JAN-08:20 | 6944.63 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 91.15 | 0.00 | 01-JAN-08:20 | 6944.63 | 01-JAN-06:10 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Gas:Facility | 334.88 | 0.00 | 01-JAN-00:10 | 164474.68 | 10-JAN-09:10 |
Gas:HVAC | 334.88 | 0.00 | 01-JAN-00:10 | 164474.68 | 10-JAN-09:10 |
Heating:Gas | 334.88 | 0.00 | 01-JAN-00:10 | 164474.68 | 10-JAN-09:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water:Plant | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
WaterSystems:Water | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water Heater:WaterSystems:Water | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
MainsWater:Facility | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
MainsWater:Plant | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
WaterSystems:MainsWater | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water Heater:WaterSystems:MainsWater | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:Facility | 667.98 | 0.00 | 01-JAN-00:10 | 207552.58 | 10-JAN-09:10 |
EnergyTransfer:Building | 329.22 | 0.00 | 01-JAN-00:10 | 75972.84 | 10-JAN-09:10 |
EnergyTransfer:Zone:LGSTORE1 | 75.83 | 0.00 | 01-JAN-00:10 | 14333.10 | 12-JAN-09:10 |
Heating:EnergyTransfer | 55.49 | 0.00 | 01-JAN-00:10 | 71226.48 | 10-JAN-09:10 |
Heating:EnergyTransfer:Zone:LGSTORE1 | 5.15 | 0.00 | 01-JAN-00:10 | 12690.93 | 30-DEC-09:10 |
Cooling:EnergyTransfer | 273.73 | 0.00 | 01-JAN-00:10 | 66568.95 | 22-JUL-15:00 |
Cooling:EnergyTransfer:Zone:LGSTORE1 | 70.68 | 0.00 | 01-JAN-00:10 | 11761.39 | 22-JUL-16:20 |
EnergyTransfer:Zone:SMSTORE1 | 39.12 | 0.00 | 01-JAN-00:10 | 8205.14 | 03-NOV-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE1 | 1.53 | 0.00 | 01-JAN-00:10 | 6558.42 | 10-JAN-09:10 |
Cooling:EnergyTransfer:Zone:SMSTORE1 | 37.59 | 0.00 | 01-JAN-00:10 | 6187.65 | 22-JUL-16:10 |
EnergyTransfer:Zone:SMSTORE2 | 28.42 | 0.00 | 01-JAN-00:10 | 6219.68 | 22-JUL-07:10 |
Heating:EnergyTransfer:Zone:SMSTORE2 | 2.94 | 0.00 | 01-JAN-00:10 | 4564.87 | 10-JAN-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE2 | 25.47 | 0.00 | 01-JAN-00:10 | 6182.62 | 23-JUL-08:10 |
EnergyTransfer:Zone:SMSTORE3 | 27.57 | 0.00 | 01-JAN-00:10 | 6547.14 | 10-JAN-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE3 | 3.38 | 0.00 | 01-JAN-00:10 | 5404.83 | 10-JAN-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE3 | 24.20 | 0.00 | 01-JAN-00:10 | 6269.31 | 23-JUL-08:10 |
EnergyTransfer:Zone:SMSTORE4 | 25.83 | 0.00 | 01-JAN-00:10 | 7330.19 | 10-JAN-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE4 | 4.08 | 0.00 | 01-JAN-00:10 | 6176.70 | 10-JAN-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE4 | 21.75 | 0.00 | 01-JAN-00:10 | 5921.84 | 23-JUL-08:10 |
EnergyTransfer:Zone:LGSTORE2 | 43.31 | 0.00 | 01-JAN-00:10 | 16677.53 | 10-JAN-09:10 |
Heating:EnergyTransfer:Zone:LGSTORE2 | 7.97 | 0.00 | 01-JAN-00:10 | 15211.25 | 10-JAN-09:10 |
Cooling:EnergyTransfer:Zone:LGSTORE2 | 35.34 | 0.00 | 01-JAN-00:10 | 10526.75 | 22-JUL-15:00 |
EnergyTransfer:Zone:SMSTORE5 | 22.56 | 0.00 | 01-JAN-00:10 | 8851.57 | 10-JAN-09:10 |
Heating:EnergyTransfer:Zone:SMSTORE5 | 5.37 | 0.00 | 01-JAN-00:10 | 8188.80 | 10-JAN-09:10 |
Cooling:EnergyTransfer:Zone:SMSTORE5 | 17.19 | 0.00 | 01-JAN-00:10 | 5454.84 | 22-JUL-15:00 |
EnergyTransfer:Zone:SMSTORE6 | 22.14 | 0.00 | 01-JAN-00:10 | 9309.05 | 26-DEC-09:10 |
Heating:EnergyTransfer:Zone:SMSTORE6 | 5.75 | 0.00 | 01-JAN-00:10 | 8454.34 | 26-DEC-09:10 |
Cooling:EnergyTransfer:Zone:SMSTORE6 | 16.39 | 0.00 | 01-JAN-00:10 | 5382.41 | 22-JUL-15:00 |
EnergyTransfer:Zone:SMSTORE7 | 21.37 | 0.00 | 01-JAN-00:10 | 9050.00 | 10-JAN-09:10 |
Heating:EnergyTransfer:Zone:SMSTORE7 | 6.98 | 0.00 | 01-JAN-00:10 | 8378.11 | 10-JAN-09:10 |
Cooling:EnergyTransfer:Zone:SMSTORE7 | 14.38 | 0.00 | 01-JAN-00:10 | 5244.26 | 22-JUL-15:00 |
EnergyTransfer:Zone:SMSTORE8 | 23.05 | 0.00 | 01-JAN-00:10 | 10698.77 | 09-JAN-09:10 |
Heating:EnergyTransfer:Zone:SMSTORE8 | 12.32 | 0.00 | 01-JAN-00:10 | 10114.45 | 09-JAN-09:10 |
Cooling:EnergyTransfer:Zone:SMSTORE8 | 10.73 | 0.00 | 01-JAN-00:10 | 5181.10 | 22-JUL-15:00 |
EnergyTransfer:HVAC | 338.77 | 0.00 | 01-JAN-00:10 | 131579.74 | 10-JAN-09:10 |
HeatingCoils:EnergyTransfer | 267.90 | 0.00 | 01-JAN-00:10 | 131579.74 | 10-JAN-09:10 |
CoolingCoils:EnergyTransfer | 70.87 | 0.00 | 01-JAN-00:10 | 91263.26 | 22-JUL-15:00 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2020-06-03 19:19:13
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
LGSTORE1 | 0.000 | 0.000 | 5.150 | -70.682 | 0.000 | 0.000 | 13.719 | 118.163 | 26.357 | 16.804 | 0.000 | 0.065 | 0.002 | 0.000 | -10.903 | 0.000 | -33.358 | -65.315 |
SMSTORE1 | 0.000 | 0.000 | 1.530 | -37.589 | 0.000 | 0.000 | 6.678 | 63.721 | 13.179 | 8.311 | 0.000 | 0.035 | 0.001 | 0.000 | -5.744 | 0.000 | -17.549 | -32.572 |
SMSTORE2 | 0.000 | 0.000 | 2.944 | -25.475 | 0.000 | 0.000 | 4.082 | 45.008 | 10.467 | 8.293 | 0.000 | 0.035 | 0.000 | 0.000 | -5.656 | 0.000 | -17.892 | -21.806 |
SMSTORE3 | 0.000 | 0.000 | 3.380 | -24.195 | 0.000 | 0.000 | 4.089 | 45.008 | 10.467 | 8.309 | 0.000 | 0.035 | 0.001 | 0.000 | -5.590 | 0.000 | -17.826 | -23.677 |
SMSTORE4 | 0.000 | 0.000 | 4.082 | -21.753 | 0.000 | 0.000 | 4.100 | 45.008 | 10.467 | 8.336 | 0.000 | 0.035 | 0.001 | 0.000 | -5.520 | 0.000 | -17.725 | -27.030 |
LGSTORE2 | 0.000 | 0.000 | 7.973 | -35.339 | 0.000 | 0.000 | 14.222 | 61.707 | 19.261 | 16.822 | 0.000 | 0.063 | 0.002 | 0.000 | -10.708 | 0.000 | -31.668 | -42.332 |
SMSTORE5 | 0.000 | 0.000 | 5.370 | -17.192 | 0.000 | 0.000 | 7.089 | 30.853 | 9.631 | 8.415 | 0.000 | 0.035 | 0.002 | 0.000 | -5.343 | 0.000 | -17.480 | -21.378 |
SMSTORE6 | 0.000 | 0.000 | 5.755 | -16.387 | 0.000 | 0.000 | 7.098 | 30.853 | 9.631 | 8.429 | 0.000 | 0.035 | 0.001 | 0.000 | -5.313 | 0.000 | -17.437 | -22.664 |
SMSTORE7 | 0.000 | 0.000 | 6.985 | -14.382 | 0.000 | 0.000 | 7.119 | 30.853 | 9.631 | 8.464 | 0.000 | 0.035 | 0.000 | 0.000 | -5.225 | 0.000 | -17.318 | -26.162 |
SMSTORE8 | 0.000 | 0.000 | 12.320 | -10.734 | 0.000 | 0.000 | 7.154 | 30.853 | 9.631 | 8.553 | 0.000 | 0.036 | 0.000 | 0.000 | -4.934 | 0.000 | -19.718 | -33.162 |
Total Facility | 0.000 | 0.000 | 55.488 | -273.728 | 0.000 | 0.000 | 75.350 | 502.028 | 128.721 | 100.736 | 0.000 | 0.409 | 0.008 | 0.000 | -64.935 | 0.000 | -207.972 | -316.097 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
LGSTORE1 | 24-JUL-08:62 | 0.00 | 0.00 | 0.00 | -24006.33 | 0.00 | 0.00 | 98.44 | 3199.32 | 749.03 | 518.07 | 0.00 | 0.00 | 19871.68 | 0.00 | -0.00 | 0.00 | -430.21 | 0.00 |
SMSTORE1 | 06-AUG-07:02 | 0.00 | 0.00 | 0.00 | -13495.67 | 0.00 | 0.00 | 49.50 | 172.53 | 37.45 | 25.27 | 0.00 | 0.00 | 13451.18 | 0.00 | -0.00 | 0.00 | -240.26 | 0.00 |
SMSTORE2 | 20-JUL-07:02 | 0.00 | 0.00 | 0.00 | -19081.37 | 0.00 | 0.00 | 46.88 | 1537.78 | 374.52 | 37.31 | 0.00 | 0.00 | 17399.08 | 0.00 | -0.00 | 0.00 | -314.20 | 0.00 |
SMSTORE3 | 20-JUL-07:02 | 0.00 | 0.00 | 0.00 | -18952.22 | 0.00 | 0.00 | 47.04 | 1537.78 | 374.52 | 37.99 | 0.00 | 0.00 | 17268.31 | 0.00 | -0.00 | 0.00 | -313.42 | 0.00 |
SMSTORE4 | 20-JUL-07:02 | 0.00 | 0.00 | 0.00 | -18872.66 | 0.00 | 0.00 | 47.53 | 1537.78 | 374.52 | 40.14 | 0.00 | 0.00 | 17182.99 | 0.00 | -0.00 | 0.00 | -310.29 | 0.00 |
LGSTORE2 | 24-JUL-08:62 | 0.00 | 0.00 | 0.00 | -26365.58 | 0.00 | 0.00 | 212.93 | 2293.69 | 749.03 | 504.47 | 0.00 | 0.00 | 23020.29 | 0.00 | -0.00 | 0.00 | -414.83 | 0.00 |
SMSTORE5 | 23-JUL-09:02 | 0.00 | 0.00 | 0.00 | -12117.78 | 0.00 | 0.00 | 107.82 | 1146.85 | 374.52 | 438.33 | 0.00 | 0.00 | 10149.16 | 0.00 | -0.00 | 0.00 | -98.90 | 0.00 |
SMSTORE6 | 23-JUL-09:02 | 0.00 | 0.00 | 0.00 | -11968.54 | 0.00 | 0.00 | 108.31 | 1146.85 | 374.52 | 439.55 | 0.00 | 0.00 | 9996.93 | 0.00 | -0.00 | 0.00 | -97.61 | 0.00 |
SMSTORE7 | 23-JUL-09:02 | 0.00 | 0.00 | 0.00 | -11677.92 | 0.00 | 0.00 | 109.53 | 1146.85 | 374.52 | 442.15 | 0.00 | 0.00 | 9699.22 | 0.00 | -0.00 | 0.00 | -94.34 | 0.00 |
SMSTORE8 | 23-JUL-09:02 | 0.00 | 0.00 | 0.00 | -11537.44 | 0.00 | 0.00 | 110.36 | 1146.85 | 374.52 | 444.33 | 0.00 | 0.00 | 9568.26 | 0.00 | -0.00 | 0.00 | -106.87 | 0.00 |
Total Facility | 22-JUL-08:62 | 0.00 | 0.00 | 0.00 | -114594.01 | 0.00 | 0.00 | 1085.95 | 20571.05 | 5393.02 | 4169.31 | 0.00 | 7.85 | 83535.46 | 0.00 | 0.00 | 0.00 | -168.63 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
LGSTORE1 | 04-DEC-09:01 | 0.00 | 0.00 | 42424.37 | 0.00 | 0.00 | 0.00 | 130.09 | 3199.32 | 749.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -377.65 | 0.00 | -611.39 | -45513.76 |
SMSTORE1 | 09-MAR-09:01 | 0.00 | 0.00 | 23739.63 | 0.00 | 0.00 | 0.00 | 65.19 | 1725.28 | 374.52 | 312.45 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -252.46 | -25964.61 |
SMSTORE2 | 31-DEC-09:01 | 0.00 | 0.00 | 23450.07 | 0.00 | 0.00 | 0.00 | 64.43 | 1537.78 | 374.52 | 324.05 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -496.26 | -25254.58 |
SMSTORE3 | 31-DEC-09:01 | 0.00 | 0.00 | 23403.02 | 0.00 | 0.00 | 0.00 | 65.18 | 1537.78 | 374.52 | 328.89 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -489.95 | -25219.45 |
SMSTORE4 | 25-DEC-09:01 | 0.00 | 0.00 | 24223.93 | 0.00 | 0.00 | 0.00 | 65.03 | 1537.78 | 374.52 | 242.33 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -455.47 | -25988.12 |
LGSTORE2 | 29-JAN-10:01 | 0.00 | 0.00 | 42653.13 | 0.00 | 0.00 | 0.00 | 282.99 | 2293.69 | 749.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -140.08 | 0.00 | -447.20 | -45391.56 |
SMSTORE5 | 29-JAN-10:01 | 0.00 | 0.00 | 23007.79 | 0.00 | 0.00 | 0.00 | 149.45 | 1146.85 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -60.35 | 0.00 | -215.96 | -24402.30 |
SMSTORE6 | 29-JAN-10:01 | 0.00 | 0.00 | 22839.25 | 0.00 | 0.00 | 0.00 | 150.08 | 1146.85 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -58.19 | 0.00 | -213.16 | -24239.33 |
SMSTORE7 | 29-JAN-10:01 | 0.00 | 0.00 | 22546.14 | 0.00 | 0.00 | 0.00 | 151.76 | 1146.85 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -52.78 | 0.00 | -205.68 | -23960.79 |
SMSTORE8 | 29-JAN-10:01 | 0.00 | 0.00 | 22372.02 | 0.00 | 0.00 | 0.00 | 152.96 | 1146.85 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -41.49 | 0.00 | -236.78 | -23768.07 |
Total Facility | 04-DEC-09:01 | 0.00 | 0.00 | 196927.06 | 0.00 | 0.00 | 0.00 | 1476.26 | 20571.05 | 5393.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2150.36 | 0.00 | -3502.17 | -218714.88 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2020-06-03 19:19:13
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 1.5709 | 0.0000 | 29.9961 | 1.0000 | 0.4115 | 1.5709 | 0.2619 | 1.0000 | 0.4115 | 0.2619 | ||
PSZ-AC_2:2 | 0.8707 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 0.8786 | 0.2342 | 1.0000 | 0.2057 | 0.2342 | ||
PSZ-AC_3:3 | 0.9737 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 0.9737 | 0.2113 | 1.0000 | 0.2057 | 0.2113 | ||
PSZ-AC_4:4 | 0.9687 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 0.9687 | 0.2124 | 1.0000 | 0.2057 | 0.2124 | ||
PSZ-AC_5:5 | 0.9712 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 0.9712 | 0.2118 | 1.0000 | 0.2057 | 0.2118 | ||
PSZ-AC_6:6 | 1.5241 | 0.0000 | 29.9961 | 1.0000 | 0.4115 | 1.5613 | 0.2635 | 1.0000 | 0.4115 | 0.2635 | ||
PSZ-AC_7:7 | 0.8246 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 0.8303 | 0.2478 | 1.0000 | 0.2057 | 0.2478 | ||
PSZ-AC_8:8 | 0.8157 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 0.8222 | 0.2502 | 1.0000 | 0.2057 | 0.2502 | ||
PSZ-AC_9:9 | 0.7990 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 0.8078 | 0.2547 | 1.0000 | 0.2057 | 0.2547 | ||
PSZ-AC_10:10 | 0.7878 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 0.8064 | 0.2551 | 1.0000 | 0.2057 | 0.2551 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 1.5709 | 0.0000 | 29.9961 | 1.0000 | 0.4115 | 1.5709 | 1.0000 | 1.0000 | 0.4115 | 0.2619 | ||
PSZ-AC_2:2 | 0.8707 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 0.8707 | 1.0000 | 1.0000 | 0.2057 | 0.2363 | ||
PSZ-AC_3:3 | 0.9737 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 0.9737 | 1.0000 | 1.0000 | 0.2057 | 0.2113 | ||
PSZ-AC_4:4 | 0.9687 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 0.9687 | 1.0000 | 1.0000 | 0.2057 | 0.2124 | ||
PSZ-AC_5:5 | 0.9712 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 0.9712 | 1.0000 | 1.0000 | 0.2057 | 0.2118 | ||
PSZ-AC_6:6 | 1.5241 | 0.0000 | 29.9961 | 1.0000 | 0.4115 | 1.5241 | 1.0000 | 1.0000 | 0.4115 | 0.2700 | ||
PSZ-AC_7:7 | 0.8246 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 0.8246 | 1.0000 | 1.0000 | 0.2057 | 0.2495 | ||
PSZ-AC_8:8 | 0.8157 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 0.8157 | 1.0000 | 1.0000 | 0.2057 | 0.2522 | ||
PSZ-AC_9:9 | 0.7990 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 0.7990 | 1.0000 | 1.0000 | 0.2057 | 0.2575 | ||
PSZ-AC_10:10 | 0.7878 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 0.7878 | 1.0000 | 1.0000 | 0.2057 | 0.2611 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
LGSTORE1 | PSZ-AC_1:1 | 0.000000 | 29.9961 | 0.001181 | 348.39 | 0.4115 | 1.0000 | 0.4115 | 1.000 | 0.4115 |
SMSTORE1 | PSZ-AC_2:2 | 0.000000 | 14.9980 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE2 | PSZ-AC_3:3 | 0.000000 | 14.9980 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE3 | PSZ-AC_4:4 | 0.000000 | 14.9980 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE4 | PSZ-AC_5:5 | 0.000000 | 14.9980 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
LGSTORE2 | PSZ-AC_6:6 | 0.000000 | 29.9961 | 0.001181 | 348.39 | 0.4115 | 1.0000 | 0.4115 | 1.000 | 0.4115 |
SMSTORE5 | PSZ-AC_7:7 | 0.000000 | 14.9980 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE6 | PSZ-AC_8:8 | 0.000000 | 14.9980 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE7 | PSZ-AC_9:9 | 0.000000 | 14.9980 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE8 | PSZ-AC_10:10 | 0.000000 | 14.9980 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC_1:1 | 0.000000 | 30.00 | 0.001181 | 348.3864 | 0.4115 | 0.4115 | 0.4115 |
PSZ-AC_2:2 | 0.000000 | 15.00 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_3:3 | 0.000000 | 15.00 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_4:4 | 0.000000 | 15.00 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_5:5 | 0.000000 | 15.00 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_6:6 | 0.000000 | 30.00 | 0.001181 | 348.3864 | 0.4115 | 0.4115 | 0.4115 |
PSZ-AC_7:7 | 0.000000 | 15.00 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_8:8 | 0.000000 | 15.00 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_9:9 | 0.000000 | 15.00 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_10:10 | 0.000000 | 15.00 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LGSTORE1 | PSZ-AC_1:1 | 1.5709 | 1.5709 | 1.5709 | 0.4115 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE1 | PSZ-AC_2:2 | 0.8707 | 0.8707 | 0.8707 | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE2 | PSZ-AC_3:3 | 0.9737 | 0.9737 | 0.9737 | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE3 | PSZ-AC_4:4 | 0.9687 | 0.9687 | 0.9687 | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE4 | PSZ-AC_5:5 | 0.9712 | 0.9712 | 0.9712 | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
LGSTORE2 | PSZ-AC_6:6 | 1.5241 | 1.5241 | 1.5241 | 0.4115 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE5 | PSZ-AC_7:7 | 0.8246 | 0.8246 | 0.8246 | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE6 | PSZ-AC_8:8 | 0.8157 | 0.8157 | 0.8157 | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE7 | PSZ-AC_9:9 | 0.7990 | 0.7990 | 0.7990 | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE8 | PSZ-AC_10:10 | 0.7878 | 0.7878 | 0.7878 | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 1.5709 | 1.5709 | 1.5709 | 1.5709 | 0.4115 | 1.0000 |
PSZ-AC_2:2 | 0.8707 | 0.8786 | 0.8707 | 0.8707 | 0.2057 | 1.0000 |
PSZ-AC_3:3 | 0.9737 | 0.9737 | 0.9737 | 0.9737 | 0.2057 | 1.0000 |
PSZ-AC_4:4 | 0.9687 | 0.9687 | 0.9687 | 0.9687 | 0.2057 | 1.0000 |
PSZ-AC_5:5 | 0.9712 | 0.9712 | 0.9712 | 0.9712 | 0.2057 | 1.0000 |
PSZ-AC_6:6 | 1.5241 | 1.5613 | 1.5241 | 1.5241 | 0.4115 | 1.0000 |
PSZ-AC_7:7 | 0.8246 | 0.8303 | 0.8246 | 0.8246 | 0.2057 | 1.0000 |
PSZ-AC_8:8 | 0.8157 | 0.8222 | 0.8157 | 0.8157 | 0.2057 | 1.0000 |
PSZ-AC_9:9 | 0.7990 | 0.8078 | 0.7990 | 0.7990 | 0.2057 | 1.0000 |
PSZ-AC_10:10 | 0.7878 | 0.8064 | 0.7878 | 0.7878 | 0.2057 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LGSTORE1 | PSZ-AC_1:1 | 1.5709 | 1.5709 | 1.5709 | 0.4115 | 0.4676 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE1 | PSZ-AC_2:2 | 0.8707 | 0.8707 | 0.8707 | 0.2057 | 0.4779 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE2 | PSZ-AC_3:3 | 0.9737 | 0.9737 | 0.9737 | 0.2057 | 0.4717 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE3 | PSZ-AC_4:4 | 0.9687 | 0.9687 | 0.9687 | 0.2057 | 0.4667 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE4 | PSZ-AC_5:5 | 0.9712 | 0.9712 | 0.9712 | 0.2057 | 0.4578 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
LGSTORE2 | PSZ-AC_6:6 | 1.5241 | 1.5241 | 1.5241 | 0.4115 | 0.4753 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE5 | PSZ-AC_7:7 | 0.8246 | 0.8246 | 0.8246 | 0.2057 | 0.4443 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE6 | PSZ-AC_8:8 | 0.8157 | 0.8157 | 0.8157 | 0.2057 | 0.4442 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE7 | PSZ-AC_9:9 | 0.7990 | 0.7990 | 0.7990 | 0.2057 | 0.4310 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE8 | PSZ-AC_10:10 | 0.7878 | 0.7878 | 0.7878 | 0.2057 | 0.3693 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 1.5709 | 1.5709 | 1.5709 | 1.5709 | 0.4115 | 1.0000 |
PSZ-AC_2:2 | 0.8707 | 0.8707 | 0.8707 | 0.8707 | 0.2057 | 1.0000 |
PSZ-AC_3:3 | 0.9737 | 0.9737 | 0.9737 | 0.9737 | 0.2057 | 1.0000 |
PSZ-AC_4:4 | 0.9687 | 0.9687 | 0.9687 | 0.9687 | 0.2057 | 1.0000 |
PSZ-AC_5:5 | 0.9712 | 0.9712 | 0.9712 | 0.9712 | 0.2057 | 1.0000 |
PSZ-AC_6:6 | 1.5241 | 1.5241 | 1.5241 | 1.5241 | 0.4115 | 1.0000 |
PSZ-AC_7:7 | 0.8246 | 0.8246 | 0.8246 | 0.8246 | 0.2057 | 1.0000 |
PSZ-AC_8:8 | 0.8157 | 0.8157 | 0.8157 | 0.8157 | 0.2057 | 1.0000 |
PSZ-AC_9:9 | 0.7990 | 0.7990 | 0.7990 | 0.7990 | 0.2057 | 1.0000 |
PSZ-AC_10:10 | 0.7878 | 0.7878 | 0.7878 | 0.7878 | 0.2057 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2020-06-03 19:19:13
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** William R Fairchild WA USA TMY3 WMO#=727885 |
Total gross floor area [m2] | 2090.32 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
LGSTORE1 | 348.39 | 348.39 | 0.00 | 112.00 |
SMSTORE1 | 174.19 | 174.19 | 0.00 | 112.00 |
SMSTORE2 | 174.19 | 174.19 | 0.00 | 84.29 |
SMSTORE3 | 174.19 | 174.19 | 0.00 | 84.29 |
SMSTORE4 | 174.19 | 174.19 | 0.00 | 84.29 |
LGSTORE2 | 348.39 | 348.39 | 0.00 | 77.29 |
SMSTORE5 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE6 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE7 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE8 | 174.19 | 174.19 | 0.00 | 77.29 |
Totals | 2090.32 | 2090.32 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 0.00 |
Number of hours not met | 0.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Fuel Use [GJ] | Additional Fuel Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- Not Subdivided | 0.00 | 0.00 | 334.88 | 164474.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- Not Subdivided | 16.22 | 20347.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 502.03 | 31196.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 91.15 | 6944.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 128.72 | 8089.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 156.16 | 10167.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 65.19 | 11862.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 128.72 | 959.48 |
Natural Gas | 0.00 | 334.88 |
Additional | 0.00 | 0.00 |
Total | 128.72 | 1294.35 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 240.17 |
Space Heating | 0.00 |
Space Cooling | 7.76 |
Fans (All) | 74.71 |
Service Water Heating | 31.19 |
Receptacle Equipment | 61.58 |
Miscellaneous (All) | 459.01 |
Subtotal | 459.01 |
Natural Gas [MJ/m2] | |
Space Heating | 160.20 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 160.20 |
Subtotal | 160.20 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 38.79 |
Space Heating | 25.87 |
Space Cooling | 1.25 |
Fans (All) | 12.07 |
Service Water Heating | 5.04 |
Receptacle Equipment | 9.94 |
Miscellaneous | 7.04 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
TYPE1_OCC_SCH | 1630. | 5840. |
TYPE2_OCC_SCH | 995. | 4429. |
TYPE3_OCC_SCH | 1709. | 4064. |
TYPE1_LIGHT_SCH | 5131. | 8760. |
TYPE2_LIGHT_SCH | 4096. | 8760. |
TYPE3_LIGHT_SCH | 3767. | 8760. |
TYPE1_EQUIP_SCH | 4888. | 8760. |
TYPE2_EQUIP_SCH | 3911. | 8760. |
TYPE3_EQUIP_SCH | 3600. | 8760. |
TYPE1_INFIL_SCH | 4302. | 8760. |
TYPE2_INFIL_SCH | 5164. | 8760. |
TYPE3_INFIL_SCH | 5438. | 8760. |
INFIL_DOOR_OPENING_SCH | 2477. | 4380. |
TYPE1_MINOA_MOTORIZEDDAMPER_SCH | 5579. | 5579. |
TYPE2_MINOA_MOTORIZEDDAMPER_SCH | 4429. | 4429. |
TYPE3_MINOA_MOTORIZEDDAMPER_SCH | 4064. | 4064. |
TYPE1_SWH_SCH | 2063. | 6048. |
TYPE2_SWH_SCH | 1831. | 4429. |
TYPE3_SWH_SCH | 1733. | 4064. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 7118. | 8760. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 5839. | 5839. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 7300. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
TYPE1_HTGSETP_SCH_YES_OPTIMUM | LGSTORE1 DUALSPSCHED | January | 21.11 | 365 | 21.11 | 365 |
TYPE1_CLGSETP_SCH_YES_OPTIMUM | LGSTORE1 DUALSPSCHED | July | 23.89 | 365 | 23.89 | 365 |
TYPE2_HTGSETP_SCH_YES_OPTIMUM | SMSTORE2 DUALSPSCHED | January | 21.11 | 365 | 15.56 | 365 |
TYPE2_CLGSETP_SCH_YES_OPTIMUM | SMSTORE2 DUALSPSCHED | July | 23.89 | 365 | 29.44 | 365 |
TYPE3_HTGSETP_SCH_YES_OPTIMUM | LGSTORE2 DUALSPSCHED | January | 21.11 | 365 | 15.56 | 365 |
TYPE3_CLGSETP_SCH_YES_OPTIMUM | LGSTORE2 DUALSPSCHED | July | 23.89 | 365 | 29.44 | 365 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Meter
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.708389E+11 |
February | 0.000 | 0.576057E+11 |
March | 0.000 | 0.522872E+11 |
April | 0.000 | 0.120393E+11 |
May | 0.000 | 0.766304E+10 |
June | 0.000 | 0.316172E+09 |
July | 0.000 | 0.199965E+08 |
August | 0.000 | 0.000 |
September | 0.000 | 0.285710E+08 |
October | 0.000 | 0.129786E+11 |
November | 0.000 | 0.443253E+11 |
December | 0.000 | 0.767731E+11 |
Annual Sum or Average | 0.334876E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.767731E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Meter
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.708389E+11 |
February | 0.000 | 0.576057E+11 |
March | 0.000 | 0.522872E+11 |
April | 0.000 | 0.120393E+11 |
May | 0.000 | 0.766304E+10 |
June | 0.000 | 0.316172E+09 |
July | 0.000 | 0.199965E+08 |
August | 0.000 | 0.000 |
September | 0.000 | 0.285710E+08 |
October | 0.000 | 0.129786E+11 |
November | 0.000 | 0.443253E+11 |
December | 0.000 | 0.767731E+11 |
Annual Sum or Average | 0.334876E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.767731E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2015
For: Meter
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.708389E+11 |
February | 0.000 | 0.576057E+11 |
March | 0.000 | 0.522872E+11 |
April | 0.000 | 0.120393E+11 |
May | 0.000 | 0.766304E+10 |
June | 0.000 | 0.316172E+09 |
July | 0.000 | 0.199965E+08 |
August | 0.000 | 0.000 |
September | 0.000 | 0.285710E+08 |
October | 0.000 | 0.129786E+11 |
November | 0.000 | 0.443253E+11 |
December | 0.000 | 0.767731E+11 |
Annual Sum or Average | 0.334876E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.767731E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Meter
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.708389E+11 |
February | 0.000 | 0.576057E+11 |
March | 0.000 | 0.522872E+11 |
April | 0.000 | 0.120393E+11 |
May | 0.000 | 0.766304E+10 |
June | 0.000 | 0.316172E+09 |
July | 0.000 | 0.199965E+08 |
August | 0.000 | 0.000 |
September | 0.000 | 0.285710E+08 |
October | 0.000 | 0.129786E+11 |
November | 0.000 | 0.443253E+11 |
December | 0.000 | 0.767731E+11 |
Annual Sum or Average | 0.334876E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.767731E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTRIPMALL
For: Meter
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.708389E+11 |
February | 0.000 | 0.576057E+11 |
March | 0.000 | 0.522872E+11 |
April | 0.000 | 0.120393E+11 |
May | 0.000 | 0.766304E+10 |
June | 0.000 | 0.316172E+09 |
July | 0.000 | 0.199965E+08 |
August | 0.000 | 0.000 |
September | 0.000 | 0.285710E+08 |
October | 0.000 | 0.129786E+11 |
November | 0.000 | 0.443253E+11 |
December | 0.000 | 0.767731E+11 |
Annual Sum or Average | 0.334876E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.767731E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.708389E+11 |
February | 0.000 | 0.576057E+11 |
March | 0.000 | 0.522872E+11 |
April | 0.000 | 0.120393E+11 |
May | 0.000 | 0.766304E+10 |
June | 0.000 | 0.316172E+09 |
July | 0.000 | 0.199965E+08 |
August | 0.000 | 0.000 |
September | 0.000 | 0.285710E+08 |
October | 0.000 | 0.129786E+11 |
November | 0.000 | 0.443253E+11 |
December | 0.000 | 0.767731E+11 |
Annual Sum or Average | 0.334876E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.767731E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.708389E+11 |
February | 0.000 | 0.576057E+11 |
March | 0.000 | 0.522872E+11 |
April | 0.000 | 0.120393E+11 |
May | 0.000 | 0.766304E+10 |
June | 0.000 | 0.316172E+09 |
July | 0.000 | 0.199965E+08 |
August | 0.000 | 0.000 |
September | 0.000 | 0.285710E+08 |
October | 0.000 | 0.129786E+11 |
November | 0.000 | 0.443253E+11 |
December | 0.000 | 0.767731E+11 |
Annual Sum or Average | 0.334876E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.767731E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5C
For: Meter
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.708389E+11 |
February | 0.000 | 0.576057E+11 |
March | 0.000 | 0.522872E+11 |
April | 0.000 | 0.120393E+11 |
May | 0.000 | 0.766304E+10 |
June | 0.000 | 0.316172E+09 |
July | 0.000 | 0.199965E+08 |
August | 0.000 | 0.000 |
September | 0.000 | 0.285710E+08 |
October | 0.000 | 0.129786E+11 |
November | 0.000 | 0.443253E+11 |
December | 0.000 | 0.767731E+11 |
Annual Sum or Average | 0.334876E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.767731E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_PORTANGELES
For: Meter
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.708389E+11 |
February | 0.000 | 0.576057E+11 |
March | 0.000 | 0.522872E+11 |
April | 0.000 | 0.120393E+11 |
May | 0.000 | 0.766304E+10 |
June | 0.000 | 0.316172E+09 |
July | 0.000 | 0.199965E+08 |
August | 0.000 | 0.000 |
September | 0.000 | 0.285710E+08 |
October | 0.000 | 0.129786E+11 |
November | 0.000 | 0.443253E+11 |
December | 0.000 | 0.767731E+11 |
Annual Sum or Average | 0.334876E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.767731E+11 |
Report: ZoneCoolingSummaryMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.272207E+10 | 12283.27 | 11-JAN-23:52 | -6.0 | -7.4 | 0.567772E+09 | 680.13 | 13-JAN-13:20 | 7.67 | 6.06 |
February | 0.249475E+10 | 9981.58 | 18-FEB-00:03 | -1.2 | -1.5 | 0.512496E+09 | 680.12 | 04-FEB-13:09 | 9.00 | 6.12 |
March | 0.308889E+10 | 8601.95 | 03-MAR-00:03 | 1.55 | 0.95 | 0.562833E+09 | 688.56 | 19-MAR-17:30 | 11.50 | 10.70 |
April | 0.670758E+10 | 9097.63 | 30-APR-16:25 | 24.00 | 12.83 | 0.595163E+09 | 899.05 | 30-APR-12:09 | 22.00 | 13.84 |
May | 0.718925E+10 | 7260.20 | 23-MAY-17:10 | 18.00 | 13.64 | 0.627420E+09 | 899.03 | 21-MAY-17:19 | 20.00 | 12.91 |
June | 0.814348E+10 | 23537.04 | 13-JUN-08:62 | 21.10 | 15.98 | 0.691321E+09 | 899.24 | 25-JUN-17:00 | 22.00 | 19.93 |
July | 0.953846E+10 | 24012.23 | 24-JUL-08:62 | 14.17 | 13.49 | 0.744477E+09 | 899.03 | 16-JUL-16:00 | 18.00 | 14.97 |
August | 0.981290E+10 | 18479.43 | 06-AUG-07:02 | 13.17 | 12.51 | 0.742503E+09 | 899.04 | 20-AUG-17:00 | 17.00 | 13.48 |
September | 0.869964E+10 | 9294.74 | 13-SEP-14:00 | 23.00 | 16.21 | 0.716210E+09 | 899.04 | 10-SEP-16:10 | 20.67 | 16.44 |
October | 0.653105E+10 | 7777.97 | 05-OCT-20:00 | 5.00 | 4.08 | 0.612219E+09 | 898.77 | 07-OCT-12:00 | 17.00 | 9.19 |
November | 0.362044E+10 | 9329.05 | 29-NOV-09:04 | 1.17 | -0.1 | 0.549707E+09 | 696.97 | 10-NOV-13:00 | 12.00 | 8.90 |
December | 0.213370E+10 | 10710.41 | 30-DEC-00:03 | -2.8 | -4.2 | 0.570474E+09 | 680.13 | 15-DEC-13:09 | 6.00 | 5.05 |
Annual Sum or Average | 0.706822E+11 | 0.749260E+10 | ||||||||
Minimum of Months | 0.213370E+10 | 7260.20 | -6.0 | -7.4 | 0.512496E+09 | 680.12 | 6.00 | 5.05 | ||
Maximum of Months | 0.981290E+10 | 24012.23 | 24.00 | 16.21 | 0.744477E+09 | 899.24 | 22.00 | 19.93 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.152021E+10 | 5013.83 | 10-JAN-08:62 | -5.7 | -6.7 | 0.297797E+09 | 418.43 | 29-JAN-18:00 | 9.00 | 8.43 |
February | 0.146025E+10 | 4232.02 | 17-FEB-08:62 | -2.3 | -2.4 | 0.268375E+09 | 415.94 | 05-FEB-18:00 | 6.00 | 5.04 |
March | 0.175536E+10 | 3947.19 | 14-MAR-08:04 | 3.17 | 2.40 | 0.296374E+09 | 434.27 | 19-MAR-17:00 | 11.00 | 10.48 |
April | 0.307768E+10 | 5083.77 | 30-APR-07:03 | 16.23 | 12.97 | 0.326966E+09 | 449.51 | 16-APR-17:40 | 10.33 | 7.18 |
May | 0.331503E+10 | 4444.41 | 28-MAY-17:10 | 12.00 | 7.58 | 0.342434E+09 | 449.51 | 21-MAY-17:30 | 20.00 | 12.99 |
June | 0.437444E+10 | 12271.17 | 13-JUN-08:62 | 21.10 | 15.98 | 0.358040E+09 | 449.58 | 25-JUN-17:00 | 22.00 | 19.93 |
July | 0.540585E+10 | 12926.26 | 22-JUL-08:62 | 24.00 | 16.55 | 0.376200E+09 | 449.51 | 28-JUL-12:20 | 16.00 | 14.13 |
August | 0.572122E+10 | 13496.54 | 06-AUG-07:02 | 13.17 | 12.51 | 0.371455E+09 | 449.51 | 11-AUG-12:09 | 18.83 | 15.23 |
September | 0.493212E+10 | 5182.12 | 13-SEP-14:00 | 23.00 | 16.21 | 0.363183E+09 | 449.51 | 10-SEP-17:10 | 19.00 | 15.89 |
October | 0.295216E+10 | 3959.37 | 08-OCT-17:10 | 12.83 | 12.28 | 0.336628E+09 | 449.50 | 01-OCT-12:00 | 12.00 | 9.78 |
November | 0.190232E+10 | 4173.73 | 28-NOV-09:04 | 2.17 | 0.48 | 0.291990E+09 | 419.55 | 05-NOV-17:00 | 6.00 | 5.05 |
December | 0.117268E+10 | 4299.06 | 08-DEC-09:04 | 1.50 | 1.37 | 0.297764E+09 | 403.89 | 17-DEC-18:00 | 2.00 | 1.57 |
Annual Sum or Average | 0.375893E+11 | 0.392721E+10 | ||||||||
Minimum of Months | 0.117268E+10 | 3947.19 | -5.7 | -6.7 | 0.268375E+09 | 403.89 | 2.00 | 1.57 | ||
Maximum of Months | 0.572122E+10 | 13496.54 | 24.00 | 16.55 | 0.376200E+09 | 449.58 | 22.00 | 19.93 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.827391E+09 | 5384.39 | 10-JAN-08:04 | -5.7 | -6.7 | 0.169247E+09 | 340.06 | 28-JAN-13:00 | 11.00 | 9.40 |
February | 0.774371E+09 | 3694.37 | 19-FEB-09:03 | 2.33 | 1.83 | 0.153653E+09 | 340.44 | 04-FEB-13:00 | 9.00 | 6.12 |
March | 0.105339E+10 | 3632.83 | 21-MAR-07:02 | 1.33 | 0.85 | 0.174167E+09 | 369.93 | 25-MAR-12:00 | 14.00 | 11.21 |
April | 0.227001E+10 | 17171.93 | 30-APR-08:62 | 17.50 | 12.50 | 0.188526E+09 | 449.50 | 29-APR-12:00 | 19.00 | 12.78 |
May | 0.249896E+10 | 15856.85 | 01-MAY-07:02 | 7.17 | 5.30 | 0.199886E+09 | 449.49 | 27-MAY-12:00 | 15.00 | 10.67 |
June | 0.299399E+10 | 18319.62 | 14-JUN-07:02 | 12.00 | 12.00 | 0.219298E+09 | 449.49 | 24-JUN-12:09 | 16.83 | 12.75 |
July | 0.365542E+10 | 19085.72 | 20-JUL-07:02 | 11.33 | 11.25 | 0.223191E+09 | 449.49 | 29-JUL-12:09 | 17.00 | 13.95 |
August | 0.404002E+10 | 18677.64 | 22-AUG-07:02 | 16.00 | 11.38 | 0.229842E+09 | 449.50 | 05-AUG-12:39 | 19.33 | 14.36 |
September | 0.337966E+10 | 18323.23 | 28-SEP-07:02 | 8.17 | 7.15 | 0.217929E+09 | 449.50 | 23-SEP-12:00 | 19.00 | 14.77 |
October | 0.220269E+10 | 7456.20 | 02-OCT-07:03 | 10.17 | 7.63 | 0.192322E+09 | 449.49 | 07-OCT-12:09 | 16.17 | 10.37 |
November | 0.123252E+10 | 3649.47 | 04-NOV-07:02 | 1.33 | 0.86 | 0.164363E+09 | 347.91 | 25-NOV-13:39 | 10.00 | 5.63 |
December | 0.546522E+09 | 4409.58 | 31-DEC-09:03 | 0.33 | -0.2 | 0.168931E+09 | 340.06 | 16-DEC-13:09 | 8.00 | 7.37 |
Annual Sum or Average | 0.254750E+11 | 0.230136E+10 | ||||||||
Minimum of Months | 0.546522E+09 | 3632.83 | -5.7 | -6.7 | 0.153653E+09 | 340.06 | 8.00 | 5.63 | ||
Maximum of Months | 0.404002E+10 | 19085.72 | 17.50 | 12.50 | 0.229842E+09 | 449.50 | 19.33 | 14.77 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.696407E+09 | 5711.57 | 10-JAN-08:04 | -5.7 | -6.7 | 0.169152E+09 | 340.06 | 28-JAN-13:00 | 11.00 | 9.40 |
February | 0.658246E+09 | 3976.69 | 13-FEB-08:04 | 1.00 | 0.16 | 0.153630E+09 | 340.06 | 04-FEB-13:09 | 9.00 | 6.12 |
March | 0.912271E+09 | 3367.13 | 12-MAR-08:03 | 3.33 | 1.48 | 0.173992E+09 | 366.22 | 25-MAR-12:00 | 14.00 | 11.21 |
April | 0.214397E+10 | 16103.43 | 30-APR-08:62 | 17.50 | 12.50 | 0.186687E+09 | 449.50 | 29-APR-12:00 | 19.00 | 12.78 |
May | 0.239937E+10 | 15092.75 | 01-MAY-07:02 | 7.17 | 5.30 | 0.198014E+09 | 449.49 | 27-MAY-12:00 | 15.00 | 10.67 |
June | 0.290633E+10 | 18183.75 | 14-JUN-07:02 | 12.00 | 12.00 | 0.218747E+09 | 449.49 | 24-JUN-12:09 | 16.83 | 12.75 |
July | 0.358869E+10 | 18956.51 | 20-JUL-07:02 | 11.33 | 11.25 | 0.223042E+09 | 449.49 | 29-JUL-12:09 | 17.00 | 13.95 |
August | 0.398876E+10 | 18553.22 | 22-AUG-07:02 | 16.00 | 11.38 | 0.229828E+09 | 449.50 | 05-AUG-12:39 | 19.33 | 14.36 |
September | 0.330603E+10 | 18135.71 | 14-SEP-07:02 | 13.67 | 12.10 | 0.217827E+09 | 449.50 | 23-SEP-12:00 | 19.00 | 14.77 |
October | 0.206182E+10 | 5583.24 | 02-OCT-07:03 | 10.17 | 7.63 | 0.190744E+09 | 449.49 | 07-OCT-12:09 | 16.17 | 10.37 |
November | 0.107180E+10 | 3613.66 | 04-NOV-07:02 | 1.33 | 0.86 | 0.164070E+09 | 342.26 | 25-NOV-13:39 | 10.00 | 5.63 |
December | 0.461339E+09 | 4094.20 | 18-DEC-08:04 | 1.00 | 0.66 | 0.168918E+09 | 340.06 | 16-DEC-13:09 | 8.00 | 7.37 |
Annual Sum or Average | 0.241950E+11 | 0.229465E+10 | ||||||||
Minimum of Months | 0.461339E+09 | 3367.13 | -5.7 | -6.7 | 0.153630E+09 | 340.06 | 8.00 | 5.63 | ||
Maximum of Months | 0.398876E+10 | 18956.51 | 17.50 | 12.50 | 0.229828E+09 | 449.50 | 19.33 | 14.77 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.540116E+09 | 5767.45 | 10-JAN-08:04 | -5.7 | -6.7 | 0.169117E+09 | 340.06 | 28-JAN-13:00 | 11.00 | 9.40 |
February | 0.509661E+09 | 4732.13 | 17-FEB-08:05 | -2.3 | -2.4 | 0.153619E+09 | 340.06 | 04-FEB-13:09 | 9.00 | 6.12 |
March | 0.727955E+09 | 3583.14 | 27-MAR-07:04 | 2.50 | 1.17 | 0.173834E+09 | 360.98 | 25-MAR-12:00 | 14.00 | 11.21 |
April | 0.192571E+10 | 13114.47 | 30-APR-08:62 | 17.50 | 12.50 | 0.183884E+09 | 449.50 | 29-APR-12:00 | 19.00 | 12.78 |
May | 0.218276E+10 | 11899.09 | 01-MAY-07:02 | 7.17 | 5.30 | 0.195037E+09 | 449.49 | 27-MAY-12:00 | 15.00 | 10.67 |
June | 0.264200E+10 | 18060.24 | 14-JUN-07:02 | 12.00 | 12.00 | 0.216824E+09 | 449.49 | 24-JUN-12:09 | 16.83 | 12.75 |
July | 0.335095E+10 | 18876.96 | 20-JUL-07:02 | 11.33 | 11.25 | 0.222518E+09 | 449.49 | 29-JUL-12:09 | 17.00 | 13.95 |
August | 0.378063E+10 | 18469.61 | 22-AUG-07:02 | 16.00 | 11.38 | 0.229780E+09 | 449.50 | 05-AUG-12:30 | 19.50 | 14.42 |
September | 0.306074E+10 | 18048.41 | 14-SEP-07:02 | 13.67 | 12.10 | 0.217417E+09 | 449.50 | 23-SEP-12:00 | 19.00 | 14.77 |
October | 0.180924E+10 | 3591.60 | 06-OCT-07:02 | 3.83 | 3.69 | 0.188219E+09 | 449.49 | 07-OCT-12:09 | 16.17 | 10.37 |
November | 0.870521E+09 | 3906.06 | 20-NOV-08:04 | 1.33 | 1.20 | 0.163838E+09 | 340.06 | 18-NOV-13:09 | 10.00 | 7.78 |
December | 0.352704E+09 | 4271.45 | 30-DEC-08:05 | 0.00 | -2.1 | 0.168897E+09 | 340.06 | 16-DEC-13:09 | 8.00 | 7.37 |
Annual Sum or Average | 0.217530E+11 | 0.228298E+10 | ||||||||
Minimum of Months | 0.352704E+09 | 3583.14 | -5.7 | -6.7 | 0.153619E+09 | 340.06 | 8.00 | 6.12 | ||
Maximum of Months | 0.378063E+10 | 18876.96 | 17.50 | 12.50 | 0.229780E+09 | 449.50 | 19.50 | 14.77 |
Report: ZoneCoolingSummaryMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.527966E+09 | 11730.19 | 10-JAN-09:05 | -3.8 | -5.3 | 0.577903E+09 | 906.82 | 07-JAN-15:00 | 6.00 | 4.13 |
February | 0.526540E+09 | 9451.28 | 17-FEB-09:04 | 1.33 | 0.85 | 0.526172E+09 | 906.82 | 25-FEB-15:00 | 5.00 | 5.00 |
March | 0.825646E+09 | 9028.65 | 15-MAR-08:04 | 2.00 | 1.57 | 0.596083E+09 | 906.83 | 04-MAR-15:09 | 6.00 | 4.33 |
April | 0.334427E+10 | 7610.23 | 30-APR-15:00 | 24.00 | 13.10 | 0.603381E+09 | 1198.64 | 29-APR-14:00 | 20.00 | 12.74 |
May | 0.392440E+10 | 6708.19 | 01-MAY-08:63 | 8.00 | 6.01 | 0.635339E+09 | 1144.55 | 27-MAY-14:09 | 15.67 | 10.93 |
June | 0.491858E+10 | 19166.51 | 13-JUN-08:62 | 21.10 | 15.98 | 0.705491E+09 | 1198.66 | 24-JUN-14:09 | 18.83 | 13.60 |
July | 0.556656E+10 | 26372.97 | 24-JUL-08:62 | 14.17 | 13.49 | 0.749452E+09 | 1198.64 | 29-JUL-14:09 | 17.00 | 13.95 |
August | 0.605898E+10 | 16326.30 | 18-AUG-08:63 | 19.00 | 15.27 | 0.787499E+09 | 1198.68 | 19-AUG-14:09 | 19.17 | 14.83 |
September | 0.519622E+10 | 8431.00 | 13-SEP-14:10 | 23.00 | 16.21 | 0.730308E+09 | 1198.67 | 23-SEP-14:00 | 19.00 | 14.77 |
October | 0.313274E+10 | 7136.38 | 05-OCT-19:50 | 5.33 | 4.33 | 0.612892E+09 | 1198.64 | 07-OCT-14:09 | 17.33 | 9.91 |
November | 0.101262E+10 | 9574.16 | 29-NOV-09:04 | 1.17 | -0.1 | 0.556795E+09 | 906.82 | 25-NOV-15:00 | 8.00 | 4.80 |
December | 0.304910E+09 | 10160.97 | 26-DEC-20:12 | -1.7 | -2.1 | 0.578828E+09 | 906.82 | 02-DEC-15:20 | 8.67 | 7.77 |
Annual Sum or Average | 0.353394E+11 | 0.766014E+10 | ||||||||
Minimum of Months | 0.304910E+09 | 6708.19 | -3.8 | -5.3 | 0.526172E+09 | 906.82 | 5.00 | 4.13 | ||
Maximum of Months | 0.605898E+10 | 26372.97 | 24.00 | 16.21 | 0.787499E+09 | 1198.68 | 20.00 | 14.83 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.371155E+09 | 5302.16 | 10-JAN-09:05 | -3.8 | -5.3 | 0.288816E+09 | 453.41 | 28-JAN-15:39 | 10.33 | 8.88 |
February | 0.385175E+09 | 4172.49 | 16-FEB-20:43 | -1.0 | -1.0 | 0.262951E+09 | 453.41 | 25-FEB-15:00 | 5.00 | 5.00 |
March | 0.538872E+09 | 3712.47 | 15-MAR-08:05 | 2.00 | 1.57 | 0.297906E+09 | 453.51 | 25-MAR-14:09 | 11.83 | 9.31 |
April | 0.154959E+10 | 3879.01 | 30-APR-15:00 | 24.00 | 13.10 | 0.304599E+09 | 599.32 | 22-APR-14:09 | 17.75 | 9.95 |
May | 0.174887E+10 | 2909.09 | 01-MAY-07:02 | 7.17 | 5.30 | 0.321609E+09 | 589.41 | 27-MAY-14:09 | 15.67 | 10.93 |
June | 0.215270E+10 | 4319.01 | 13-JUN-17:00 | 27.00 | 17.51 | 0.358506E+09 | 599.33 | 24-JUN-14:09 | 18.83 | 13.60 |
July | 0.267059E+10 | 12118.31 | 23-JUL-09:02 | 20.17 | 15.70 | 0.376846E+09 | 599.33 | 29-JUL-14:00 | 17.00 | 13.95 |
August | 0.301662E+10 | 4490.66 | 14-AUG-16:50 | 26.83 | 14.63 | 0.393861E+09 | 599.34 | 26-AUG-14:09 | 17.83 | 14.80 |
September | 0.242769E+10 | 4260.68 | 13-SEP-14:10 | 23.00 | 16.21 | 0.368962E+09 | 599.33 | 23-SEP-14:00 | 19.00 | 14.77 |
October | 0.144505E+10 | 3413.57 | 06-OCT-07:02 | 3.83 | 3.69 | 0.309936E+09 | 599.32 | 07-OCT-14:09 | 17.33 | 9.91 |
November | 0.627330E+09 | 4053.79 | 29-NOV-09:05 | 1.17 | -0.1 | 0.278249E+09 | 453.41 | 25-NOV-15:00 | 8.00 | 4.80 |
December | 0.258403E+09 | 4517.85 | 27-DEC-09:05 | -0.7 | -0.8 | 0.289302E+09 | 453.41 | 23-DEC-15:09 | 9.00 | 6.98 |
Annual Sum or Average | 0.171921E+11 | 0.385154E+10 | ||||||||
Minimum of Months | 0.258403E+09 | 2909.09 | -3.8 | -5.3 | 0.262951E+09 | 453.41 | 5.00 | 4.80 | ||
Maximum of Months | 0.301662E+10 | 12118.31 | 27.00 | 17.51 | 0.393861E+09 | 599.34 | 19.00 | 14.80 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.326175E+09 | 5326.12 | 10-JAN-09:05 | -3.8 | -5.3 | 0.288813E+09 | 453.41 | 28-JAN-15:30 | 10.50 | 8.88 |
February | 0.337306E+09 | 4033.59 | 17-FEB-09:05 | 1.33 | 0.85 | 0.262951E+09 | 453.41 | 25-FEB-15:00 | 5.00 | 5.00 |
March | 0.480211E+09 | 3861.46 | 15-MAR-08:05 | 2.00 | 1.57 | 0.297897E+09 | 453.43 | 25-MAR-14:09 | 11.83 | 9.31 |
April | 0.147392E+10 | 3763.94 | 30-APR-15:00 | 24.00 | 13.10 | 0.303586E+09 | 599.32 | 22-APR-14:20 | 17.80 | 9.90 |
May | 0.166754E+10 | 2894.88 | 01-MAY-07:02 | 7.17 | 5.30 | 0.320163E+09 | 584.27 | 27-MAY-14:09 | 15.67 | 10.93 |
June | 0.208471E+10 | 4214.58 | 13-JUN-17:00 | 27.00 | 17.51 | 0.356310E+09 | 599.33 | 24-JUN-14:09 | 18.83 | 13.60 |
July | 0.257650E+10 | 11969.07 | 23-JUL-09:02 | 20.17 | 15.70 | 0.375983E+09 | 599.33 | 29-JUL-14:00 | 17.00 | 13.95 |
August | 0.291408E+10 | 4405.83 | 14-AUG-16:50 | 26.83 | 14.63 | 0.393761E+09 | 599.34 | 26-AUG-14:09 | 17.83 | 14.80 |
September | 0.234829E+10 | 4168.36 | 13-SEP-14:20 | 23.00 | 16.21 | 0.367935E+09 | 599.33 | 23-SEP-14:00 | 19.00 | 14.77 |
October | 0.138249E+10 | 3389.19 | 06-OCT-07:02 | 3.83 | 3.69 | 0.308465E+09 | 599.32 | 07-OCT-14:09 | 17.33 | 9.91 |
November | 0.572316E+09 | 4077.66 | 29-NOV-09:05 | 1.17 | -0.1 | 0.278237E+09 | 453.41 | 18-NOV-15:00 | 8.00 | 5.66 |
December | 0.223432E+09 | 4541.81 | 27-DEC-09:05 | -0.7 | -0.8 | 0.289299E+09 | 453.41 | 23-DEC-15:09 | 9.00 | 6.98 |
Annual Sum or Average | 0.163870E+11 | 0.384340E+10 | ||||||||
Minimum of Months | 0.223432E+09 | 2894.88 | -3.8 | -5.3 | 0.262951E+09 | 453.41 | 5.00 | 5.00 | ||
Maximum of Months | 0.291408E+10 | 11969.07 | 27.00 | 17.51 | 0.393761E+09 | 599.34 | 19.00 | 14.80 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.214877E+09 | 5375.08 | 10-JAN-09:05 | -3.8 | -5.3 | 0.288812E+09 | 453.41 | 21-JAN-15:00 | 6.10 | 5.14 |
February | 0.214649E+09 | 4128.57 | 23-FEB-20:43 | -0.7 | -0.7 | 0.262949E+09 | 453.41 | 25-FEB-15:00 | 5.00 | 5.00 |
March | 0.336305E+09 | 3910.09 | 15-MAR-08:05 | 2.00 | 1.57 | 0.297848E+09 | 453.41 | 04-MAR-15:09 | 6.00 | 4.33 |
April | 0.127313E+10 | 3505.46 | 30-APR-15:00 | 24.00 | 13.10 | 0.301329E+09 | 599.32 | 22-APR-14:00 | 18.00 | 9.67 |
May | 0.146231E+10 | 2837.87 | 01-MAY-07:02 | 7.17 | 5.30 | 0.316646E+09 | 569.02 | 27-MAY-14:09 | 15.67 | 10.93 |
June | 0.191702E+10 | 3998.79 | 13-JUN-17:00 | 27.00 | 17.51 | 0.350430E+09 | 599.33 | 24-JUN-14:09 | 18.83 | 13.60 |
July | 0.235801E+10 | 11678.46 | 23-JUL-09:02 | 20.17 | 15.70 | 0.373554E+09 | 599.33 | 29-JUL-14:00 | 17.00 | 13.95 |
August | 0.266395E+10 | 4211.40 | 14-AUG-17:00 | 27.00 | 14.36 | 0.393452E+09 | 599.34 | 26-AUG-14:09 | 17.83 | 14.80 |
September | 0.215973E+10 | 3984.05 | 13-SEP-14:20 | 23.00 | 16.21 | 0.364651E+09 | 599.33 | 23-SEP-14:00 | 19.00 | 14.77 |
October | 0.121710E+10 | 3303.97 | 06-OCT-07:02 | 3.83 | 3.69 | 0.305082E+09 | 599.32 | 07-OCT-14:20 | 17.67 | 9.96 |
November | 0.436631E+09 | 4123.64 | 29-NOV-09:05 | 1.17 | -0.1 | 0.278197E+09 | 453.41 | 18-NOV-15:09 | 8.83 | 6.42 |
December | 0.128298E+09 | 4589.89 | 27-DEC-09:05 | -0.7 | -0.8 | 0.289301E+09 | 453.41 | 23-DEC-15:09 | 9.00 | 6.98 |
Annual Sum or Average | 0.143820E+11 | 0.382225E+10 | ||||||||
Minimum of Months | 0.128298E+09 | 2837.87 | -3.8 | -5.3 | 0.262949E+09 | 453.41 | 5.00 | 4.33 | ||
Maximum of Months | 0.266395E+10 | 11678.46 | 27.00 | 17.51 | 0.393452E+09 | 599.34 | 19.00 | 14.80 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 50911026.33 | 4702.30 | 12-JAN-09:05 | -1.0 | -2.7 | 0.288805E+09 | 453.41 | 07-JAN-15:00 | 6.00 | 4.13 |
February | 32085284.33 | 4449.50 | 17-FEB-08:05 | -2.3 | -2.4 | 0.262951E+09 | 453.41 | 25-FEB-15:00 | 5.00 | 5.00 |
March | 62108976.46 | 3958.97 | 15-MAR-08:05 | 2.00 | 1.57 | 0.297870E+09 | 453.41 | 04-MAR-15:09 | 6.00 | 4.33 |
April | 0.845383E+09 | 3127.24 | 30-APR-15:00 | 24.00 | 13.10 | 0.298741E+09 | 599.32 | 29-APR-14:00 | 20.00 | 12.74 |
May | 0.100322E+10 | 2681.96 | 01-MAY-08:07 | 8.00 | 6.01 | 0.311769E+09 | 543.80 | 27-MAY-14:09 | 15.67 | 10.93 |
June | 0.162876E+10 | 3718.47 | 13-JUN-17:00 | 27.00 | 17.51 | 0.339933E+09 | 599.33 | 24-JUN-14:09 | 18.83 | 13.60 |
July | 0.201385E+10 | 11538.03 | 23-JUL-09:02 | 20.17 | 15.70 | 0.368711E+09 | 599.33 | 15-JUL-14:00 | 18.00 | 12.88 |
August | 0.223152E+10 | 3901.31 | 14-AUG-17:00 | 27.00 | 14.36 | 0.392132E+09 | 599.34 | 26-AUG-14:09 | 17.83 | 14.80 |
September | 0.186660E+10 | 3740.82 | 13-SEP-14:10 | 23.00 | 16.21 | 0.357714E+09 | 599.34 | 23-SEP-14:00 | 19.00 | 14.77 |
October | 0.826318E+09 | 3039.80 | 06-OCT-07:02 | 3.83 | 3.69 | 0.300428E+09 | 599.31 | 07-OCT-14:00 | 19.00 | 10.08 |
November | 0.144612E+09 | 4168.09 | 29-NOV-09:05 | 1.17 | -0.1 | 0.278193E+09 | 453.41 | 04-NOV-14:00 | 9.00 | 6.58 |
December | 28167555.45 | 4627.40 | 27-DEC-09:05 | -0.7 | -0.8 | 0.289301E+09 | 453.41 | 23-DEC-15:09 | 9.00 | 6.98 |
Annual Sum or Average | 0.107335E+11 | 0.378655E+10 | ||||||||
Minimum of Months | 28167555.45 | 2681.96 | -2.3 | -2.7 | 0.262951E+09 | 453.41 | 5.00 | 4.13 | ||
Maximum of Months | 0.223152E+10 | 11538.03 | 27.00 | 17.51 | 0.392132E+09 | 599.34 | 20.00 | 14.80 |
Report: ZoneHeatingSummaryMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.125271E+10 | 41032.10 | 14-JAN-09:01 | 5.17 |
February | 0.718357E+09 | 41625.94 | 01-FEB-09:01 | 7.00 |
March | 0.642120E+09 | 42417.22 | 28-MAR-08:61 | 8.38 |
April | 0.109068E+09 | 40914.63 | 01-APR-08:61 | 5.50 |
May | 75768596.74 | 21132.75 | 05-MAY-08:61 | 8.17 |
June | 64079391.36 | 804.14 | 25-JUN-07:04 | 14.50 |
July | 63699908.26 | 1215.77 | 23-JUL-07:05 | 18.17 |
August | 60193418.84 | 983.84 | 06-AUG-07:03 | 13.17 |
September | 66868539.79 | 668.53 | 30-SEP-07:02 | 9.33 |
October | 86371171.06 | 20267.98 | 23-OCT-08:61 | 7.33 |
November | 0.415376E+09 | 40342.02 | 30-NOV-09:01 | 4.00 |
December | 0.159546E+10 | 42425.17 | 04-DEC-09:01 | 8.17 |
Annual Sum or Average | 0.515007E+10 | |||
Minimum of Months | 60193418.84 | 668.53 | 4.00 | |
Maximum of Months | 0.159546E+10 | 42425.17 | 18.17 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.412312E+09 | 23117.64 | 17-JAN-09:01 | 8.25 |
February | 0.205430E+09 | 23045.41 | 22-FEB-09:01 | 8.00 |
March | 0.189857E+09 | 23739.69 | 09-MAR-09:01 | 11.00 |
April | 31281190.14 | 23018.01 | 03-APR-08:61 | 8.17 |
May | 10667288.97 | 23010.02 | 06-MAY-08:61 | 8.17 |
June | 318169.68 | 638.31 | 13-JUN-08:05 | 21.10 |
July | 3065915.36 | 1271.99 | 22-JUL-08:05 | 24.00 |
August | 30981.86 | 154.91 | 14-AUG-08:07 | 20.17 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 |
October | 25586966.31 | 23261.85 | 25-OCT-08:61 | 9.33 |
November | 0.146856E+09 | 23341.38 | 22-NOV-09:01 | 9.33 |
December | 0.504301E+09 | 23249.29 | 04-DEC-09:01 | 8.17 |
Annual Sum or Average | 0.152971E+10 | |||
Minimum of Months | 0.00 | 0.00 | 8.00 | |
Maximum of Months | 0.504301E+09 | 23739.69 | 24.00 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.611846E+09 | 14798.39 | 10-JAN-08:62 | -5.7 |
February | 0.314656E+09 | 12132.93 | 19-FEB-09:01 | 2.33 |
March | 0.269283E+09 | 7394.05 | 05-MAR-09:01 | 5.17 |
April | 0.110275E+09 | 2473.72 | 10-APR-15:20 | 7.33 |
May | 0.104854E+09 | 1064.06 | 28-MAY-08:00 | 9.00 |
June | 0.102505E+09 | 1031.05 | 11-JUN-07:02 | 13.17 |
July | 0.111232E+09 | 2032.46 | 22-JUL-17:12 | 29.33 |
August | 0.106577E+09 | 1031.51 | 06-AUG-07:02 | 13.17 |
September | 0.103625E+09 | 1038.58 | 21-SEP-06:01 | 5.33 |
October | 0.110131E+09 | 1798.62 | 28-OCT-07:08 | 4.67 |
November | 0.243627E+09 | 4823.65 | 29-NOV-09:37 | 1.67 |
December | 0.754905E+09 | 23449.98 | 31-DEC-09:01 | 0.33 |
Annual Sum or Average | 0.294352E+10 | |||
Minimum of Months | 0.102505E+09 | 1031.05 | -5.7 | |
Maximum of Months | 0.754905E+09 | 23449.98 | 29.33 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.711311E+09 | 19019.10 | 10-JAN-08:62 | -5.7 |
February | 0.391853E+09 | 18319.09 | 20-FEB-09:01 | 3.33 |
March | 0.334820E+09 | 13079.08 | 05-MAR-09:01 | 5.17 |
April | 0.113793E+09 | 2312.26 | 08-APR-07:06 | 2.50 |
May | 0.104377E+09 | 1053.34 | 28-MAY-08:00 | 9.00 |
June | 0.102003E+09 | 1025.88 | 11-JUN-07:02 | 13.17 |
July | 0.110676E+09 | 2029.69 | 22-JUL-17:12 | 29.33 |
August | 0.106033E+09 | 1026.50 | 06-AUG-07:02 | 13.17 |
September | 0.103114E+09 | 1033.42 | 21-SEP-06:01 | 5.33 |
October | 0.111661E+09 | 1328.37 | 28-OCT-07:17 | 5.33 |
November | 0.306293E+09 | 8037.25 | 20-NOV-08:62 | 1.33 |
December | 0.883980E+09 | 23402.93 | 31-DEC-09:01 | 0.33 |
Annual Sum or Average | 0.337991E+10 | |||
Minimum of Months | 0.102003E+09 | 1025.88 | -5.7 | |
Maximum of Months | 0.883980E+09 | 23402.93 | 29.33 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.868494E+09 | 23244.56 | 08-JAN-09:01 | 2.17 |
February | 0.516403E+09 | 23984.85 | 20-FEB-09:01 | 3.33 |
March | 0.448474E+09 | 18729.29 | 05-MAR-09:01 | 5.17 |
April | 0.121796E+09 | 1992.75 | 03-APR-07:04 | 4.67 |
May | 0.106362E+09 | 1205.23 | 17-MAY-07:20 | 7.33 |
June | 0.102454E+09 | 1028.29 | 11-JUN-07:02 | 13.17 |
July | 0.111252E+09 | 2037.64 | 22-JUL-17:12 | 29.33 |
August | 0.106483E+09 | 1028.96 | 06-AUG-07:02 | 13.17 |
September | 0.103551E+09 | 1036.05 | 21-SEP-06:01 | 5.33 |
October | 0.119082E+09 | 3266.42 | 24-OCT-08:61 | 7.33 |
November | 0.384455E+09 | 12153.22 | 20-NOV-08:62 | 1.33 |
December | 0.109294E+10 | 24224.18 | 25-DEC-09:01 | 4.17 |
Annual Sum or Average | 0.408175E+10 | |||
Minimum of Months | 0.102454E+09 | 1028.29 | 1.33 | |
Maximum of Months | 0.109294E+10 | 24224.18 | 29.33 |
Report: ZoneHeatingSummaryMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.184445E+10 | 42653.03 | 29-JAN-10:01 | 11.17 |
February | 0.119056E+10 | 41222.79 | 22-FEB-09:01 | 8.00 |
March | 0.105510E+10 | 42645.42 | 09-MAR-09:01 | 11.00 |
April | 0.158491E+09 | 41201.15 | 03-APR-08:61 | 8.17 |
May | 83229126.93 | 20936.33 | 17-MAY-08:61 | 8.17 |
June | 65647575.59 | 662.71 | 06-JUN-07:25 | 11.50 |
July | 75886295.06 | 2873.81 | 22-JUL-17:03 | 29.17 |
August | 67666183.61 | 658.05 | 04-AUG-07:13 | 13.33 |
September | 66127748.28 | 665.09 | 28-SEP-07:02 | 8.17 |
October | 0.158019E+09 | 40867.28 | 23-OCT-08:61 | 7.33 |
November | 0.872830E+09 | 41631.05 | 22-NOV-09:01 | 9.33 |
December | 0.233468E+10 | 41825.19 | 04-DEC-09:01 | 8.17 |
Annual Sum or Average | 0.797269E+10 | |||
Minimum of Months | 65647575.59 | 658.05 | 7.33 | |
Maximum of Months | 0.233468E+10 | 42653.03 | 29.17 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.121419E+10 | 23007.74 | 29-JAN-10:01 | 11.17 |
February | 0.853399E+09 | 22358.43 | 22-FEB-09:01 | 8.00 |
March | 0.785622E+09 | 22992.88 | 09-MAR-09:01 | 11.00 |
April | 0.146845E+09 | 22826.80 | 26-APR-08:61 | 11.83 |
May | 67210672.51 | 22828.71 | 18-MAY-08:61 | 11.03 |
June | 3388631.00 | 15450.71 | 08-JUN-08:62 | 11.00 |
July | 10148430.25 | 1927.85 | 22-JUL-17:12 | 29.33 |
August | 683047.10 | 548.35 | 20-AUG-16:03 | 23.67 |
September | 96060.60 | 176.80 | 24-SEP-16:03 | 21.83 |
October | 0.152217E+09 | 22851.63 | 20-OCT-08:61 | 11.83 |
November | 0.654577E+09 | 22946.94 | 24-NOV-09:01 | 11.17 |
December | 0.148160E+10 | 22472.07 | 04-DEC-09:01 | 8.17 |
Annual Sum or Average | 0.536998E+10 | |||
Minimum of Months | 96060.60 | 176.80 | 8.00 | |
Maximum of Months | 0.148160E+10 | 23007.74 | 29.33 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.128612E+10 | 22839.20 | 29-JAN-10:01 | 11.17 |
February | 0.917120E+09 | 22171.22 | 22-FEB-09:01 | 8.00 |
March | 0.843975E+09 | 22822.49 | 09-MAR-09:01 | 11.00 |
April | 0.167769E+09 | 22662.67 | 26-APR-08:61 | 11.83 |
May | 77874909.15 | 22658.86 | 18-MAY-08:61 | 11.03 |
June | 4543447.00 | 18281.48 | 08-JUN-08:62 | 11.00 |
July | 10203053.78 | 1923.39 | 22-JUL-17:12 | 29.33 |
August | 686291.14 | 548.98 | 20-AUG-16:03 | 23.67 |
September | 98973.97 | 177.86 | 24-SEP-16:03 | 21.83 |
October | 0.180442E+09 | 22681.13 | 20-OCT-08:61 | 11.83 |
November | 0.711357E+09 | 22778.43 | 24-NOV-09:01 | 11.17 |
December | 0.155448E+10 | 22281.95 | 04-DEC-09:01 | 8.17 |
Annual Sum or Average | 0.575466E+10 | |||
Minimum of Months | 98973.97 | 177.86 | 8.00 | |
Maximum of Months | 0.155448E+10 | 22839.20 | 29.33 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.152468E+10 | 22546.09 | 29-JAN-10:01 | 11.17 |
February | 0.112840E+10 | 21820.67 | 22-FEB-09:01 | 8.00 |
March | 0.105242E+10 | 22530.80 | 09-MAR-09:01 | 11.00 |
April | 0.212190E+09 | 22401.25 | 27-APR-08:62 | 13.00 |
May | 0.120233E+09 | 22363.76 | 18-MAY-08:61 | 11.03 |
June | 9402968.91 | 21947.57 | 08-JUN-08:62 | 11.00 |
July | 10830017.18 | 5805.90 | 05-JUL-08:62 | 13.00 |
August | 715877.83 | 553.13 | 20-AUG-16:03 | 23.67 |
September | 117586.07 | 184.33 | 24-SEP-16:03 | 21.83 |
October | 0.250130E+09 | 22383.11 | 20-OCT-08:61 | 11.83 |
November | 0.876887E+09 | 22481.92 | 24-NOV-09:01 | 11.17 |
December | 0.179898E+10 | 21929.15 | 04-DEC-09:01 | 8.17 |
Annual Sum or Average | 0.698499E+10 | |||
Minimum of Months | 117586.07 | 184.33 | 8.00 | |
Maximum of Months | 0.179898E+10 | 22546.09 | 23.67 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.258115E+10 | 22371.98 | 29-JAN-10:01 | 11.17 |
February | 0.205807E+10 | 21606.86 | 22-FEB-09:01 | 8.00 |
March | 0.193651E+10 | 22361.45 | 19-MAR-09:01 | 11.17 |
April | 0.401973E+09 | 22338.41 | 27-APR-08:62 | 13.00 |
May | 0.296080E+09 | 22288.94 | 18-MAY-08:61 | 11.03 |
June | 33960270.87 | 22017.34 | 07-JUN-08:62 | 11.67 |
July | 18160007.62 | 15258.46 | 05-JUL-08:62 | 13.00 |
August | 938201.50 | 577.29 | 20-AUG-16:03 | 23.67 |
September | 8438826.22 | 7544.60 | 20-SEP-08:63 | 11.50 |
October | 0.513851E+09 | 22304.36 | 20-OCT-08:61 | 11.83 |
November | 0.150836E+10 | 22340.70 | 24-NOV-09:01 | 11.17 |
December | 0.296253E+10 | 21727.87 | 04-DEC-09:01 | 8.17 |
Annual Sum or Average | 0.123200E+11 | |||
Minimum of Months | 938201.50 | 577.29 | 8.00 | |
Maximum of Months | 0.296253E+10 | 22371.98 | 23.67 |
Report: ZoneElectricSummaryMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.100203E+11 | 6078.71 | 01-JAN-10:09 | 0.223514E+10 | 1348.26 | 01-JAN-10:09 |
February | 0.906661E+10 | 6078.71 | 01-FEB-10:09 | 0.202238E+10 | 1348.26 | 01-FEB-10:09 |
March | 0.100410E+11 | 6078.71 | 01-MAR-10:09 | 0.223972E+10 | 1348.26 | 01-MAR-10:09 |
April | 0.972311E+10 | 6078.71 | 01-APR-09:09 | 0.216880E+10 | 1348.26 | 01-APR-09:09 |
May | 0.100203E+11 | 6078.71 | 01-MAY-09:09 | 0.223514E+10 | 1348.26 | 01-MAY-09:09 |
June | 0.972311E+10 | 6078.71 | 01-JUN-09:09 | 0.216880E+10 | 1348.26 | 01-JUN-09:09 |
July | 0.100410E+11 | 6078.71 | 01-JUL-09:09 | 0.223972E+10 | 1348.26 | 01-JUL-09:09 |
August | 0.100203E+11 | 6078.71 | 01-AUG-09:09 | 0.223514E+10 | 1348.26 | 01-AUG-09:09 |
September | 0.974384E+10 | 6078.71 | 01-SEP-09:09 | 0.217339E+10 | 1348.26 | 01-SEP-09:09 |
October | 0.100203E+11 | 6078.71 | 01-OCT-09:09 | 0.223514E+10 | 1348.26 | 01-OCT-09:09 |
November | 0.968165E+10 | 6078.71 | 01-NOV-09:09 | 0.215964E+10 | 1348.26 | 01-NOV-09:09 |
December | 0.100617E+11 | 6078.71 | 01-DEC-10:09 | 0.224431E+10 | 1348.26 | 01-DEC-10:09 |
Annual Sum or Average | 0.118163E+12 | 0.263573E+11 | ||||
Minimum of Months | 0.906661E+10 | 6078.71 | 0.202238E+10 | 1348.26 | ||
Maximum of Months | 0.100617E+11 | 6078.71 | 0.224431E+10 | 1348.26 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.540359E+10 | 3278.04 | 01-JAN-10:09 | 0.111757E+10 | 674.13 | 01-JAN-10:09 |
February | 0.488932E+10 | 3278.04 | 01-FEB-10:09 | 0.101119E+10 | 674.13 | 01-FEB-10:09 |
March | 0.541477E+10 | 3278.04 | 01-MAR-10:09 | 0.111986E+10 | 674.13 | 01-MAR-10:09 |
April | 0.524335E+10 | 3278.04 | 01-APR-09:09 | 0.108440E+10 | 674.13 | 01-APR-09:09 |
May | 0.540359E+10 | 3278.04 | 01-MAY-09:09 | 0.111757E+10 | 674.13 | 01-MAY-09:09 |
June | 0.524335E+10 | 3278.04 | 01-JUN-09:09 | 0.108440E+10 | 674.13 | 01-JUN-09:09 |
July | 0.541477E+10 | 3278.04 | 01-JUL-09:09 | 0.111986E+10 | 674.13 | 01-JUL-09:09 |
August | 0.540359E+10 | 3278.04 | 01-AUG-09:09 | 0.111757E+10 | 674.13 | 01-AUG-09:09 |
September | 0.525453E+10 | 3278.04 | 01-SEP-09:09 | 0.108669E+10 | 674.13 | 01-SEP-09:09 |
October | 0.540359E+10 | 3278.04 | 01-OCT-09:09 | 0.111757E+10 | 674.13 | 01-OCT-09:09 |
November | 0.522099E+10 | 3278.04 | 01-NOV-09:09 | 0.107982E+10 | 674.13 | 01-NOV-09:09 |
December | 0.542595E+10 | 3278.04 | 01-DEC-10:09 | 0.112215E+10 | 674.13 | 01-DEC-10:09 |
Annual Sum or Average | 0.637214E+11 | 0.131787E+11 | ||||
Minimum of Months | 0.488932E+10 | 3278.04 | 0.101119E+10 | 674.13 | ||
Maximum of Months | 0.542595E+10 | 3278.04 | 0.112215E+10 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.379993E+10 | 2921.79 | 01-JAN-10:09 | 0.883781E+09 | 674.13 | 01-JAN-10:09 |
February | 0.344119E+10 | 2921.79 | 01-FEB-09:09 | 0.800324E+09 | 674.13 | 01-FEB-09:09 |
March | 0.387965E+10 | 2921.79 | 01-MAR-09:09 | 0.902118E+09 | 674.13 | 01-MAR-09:09 |
April | 0.368699E+10 | 2921.79 | 01-APR-08:09 | 0.857490E+09 | 674.13 | 01-APR-08:09 |
May | 0.383979E+10 | 2921.79 | 01-MAY-08:09 | 0.892950E+09 | 674.13 | 01-MAY-08:09 |
June | 0.374678E+10 | 2921.79 | 01-JUN-08:09 | 0.871243E+09 | 674.13 | 01-JUN-08:09 |
July | 0.378000E+10 | 2921.79 | 01-JUL-08:09 | 0.879197E+09 | 674.13 | 01-JUL-08:09 |
August | 0.387965E+10 | 2921.79 | 01-AUG-08:09 | 0.902118E+09 | 674.13 | 01-AUG-08:09 |
September | 0.368699E+10 | 2921.79 | 01-SEP-08:09 | 0.857490E+09 | 674.13 | 01-SEP-08:09 |
October | 0.379993E+10 | 2921.79 | 01-OCT-09:09 | 0.883781E+09 | 674.13 | 01-OCT-09:09 |
November | 0.368699E+10 | 2921.79 | 01-NOV-08:09 | 0.857490E+09 | 674.13 | 01-NOV-08:09 |
December | 0.378000E+10 | 2921.79 | 01-DEC-09:09 | 0.879197E+09 | 674.13 | 01-DEC-09:09 |
Annual Sum or Average | 0.450079E+11 | 0.104672E+11 | ||||
Minimum of Months | 0.344119E+10 | 2921.79 | 0.800324E+09 | 674.13 | ||
Maximum of Months | 0.387965E+10 | 2921.79 | 0.902118E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.379993E+10 | 2921.79 | 01-JAN-10:09 | 0.883781E+09 | 674.13 | 01-JAN-10:09 |
February | 0.344119E+10 | 2921.79 | 01-FEB-09:09 | 0.800324E+09 | 674.13 | 01-FEB-09:09 |
March | 0.387965E+10 | 2921.79 | 01-MAR-09:09 | 0.902118E+09 | 674.13 | 01-MAR-09:09 |
April | 0.368699E+10 | 2921.79 | 01-APR-08:09 | 0.857490E+09 | 674.13 | 01-APR-08:09 |
May | 0.383979E+10 | 2921.79 | 01-MAY-08:09 | 0.892950E+09 | 674.13 | 01-MAY-08:09 |
June | 0.374678E+10 | 2921.79 | 01-JUN-08:09 | 0.871243E+09 | 674.13 | 01-JUN-08:09 |
July | 0.378000E+10 | 2921.79 | 01-JUL-08:09 | 0.879197E+09 | 674.13 | 01-JUL-08:09 |
August | 0.387965E+10 | 2921.79 | 01-AUG-08:09 | 0.902118E+09 | 674.13 | 01-AUG-08:09 |
September | 0.368699E+10 | 2921.79 | 01-SEP-08:09 | 0.857490E+09 | 674.13 | 01-SEP-08:09 |
October | 0.379993E+10 | 2921.79 | 01-OCT-09:09 | 0.883781E+09 | 674.13 | 01-OCT-09:09 |
November | 0.368699E+10 | 2921.79 | 01-NOV-08:09 | 0.857490E+09 | 674.13 | 01-NOV-08:09 |
December | 0.378000E+10 | 2921.79 | 01-DEC-09:09 | 0.879197E+09 | 674.13 | 01-DEC-09:09 |
Annual Sum or Average | 0.450079E+11 | 0.104672E+11 | ||||
Minimum of Months | 0.344119E+10 | 2921.79 | 0.800324E+09 | 674.13 | ||
Maximum of Months | 0.387965E+10 | 2921.79 | 0.902118E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.379993E+10 | 2921.79 | 01-JAN-10:09 | 0.883781E+09 | 674.13 | 01-JAN-10:09 |
February | 0.344119E+10 | 2921.79 | 01-FEB-09:09 | 0.800324E+09 | 674.13 | 01-FEB-09:09 |
March | 0.387965E+10 | 2921.79 | 01-MAR-09:09 | 0.902118E+09 | 674.13 | 01-MAR-09:09 |
April | 0.368699E+10 | 2921.79 | 01-APR-08:09 | 0.857490E+09 | 674.13 | 01-APR-08:09 |
May | 0.383979E+10 | 2921.79 | 01-MAY-08:09 | 0.892950E+09 | 674.13 | 01-MAY-08:09 |
June | 0.374678E+10 | 2921.79 | 01-JUN-08:09 | 0.871243E+09 | 674.13 | 01-JUN-08:09 |
July | 0.378000E+10 | 2921.79 | 01-JUL-08:09 | 0.879197E+09 | 674.13 | 01-JUL-08:09 |
August | 0.387965E+10 | 2921.79 | 01-AUG-08:09 | 0.902118E+09 | 674.13 | 01-AUG-08:09 |
September | 0.368699E+10 | 2921.79 | 01-SEP-08:09 | 0.857490E+09 | 674.13 | 01-SEP-08:09 |
October | 0.379993E+10 | 2921.79 | 01-OCT-09:09 | 0.883781E+09 | 674.13 | 01-OCT-09:09 |
November | 0.368699E+10 | 2921.79 | 01-NOV-08:09 | 0.857490E+09 | 674.13 | 01-NOV-08:09 |
December | 0.378000E+10 | 2921.79 | 01-DEC-09:09 | 0.879197E+09 | 674.13 | 01-DEC-09:09 |
Annual Sum or Average | 0.450079E+11 | 0.104672E+11 | ||||
Minimum of Months | 0.344119E+10 | 2921.79 | 0.800324E+09 | 674.13 | ||
Maximum of Months | 0.387965E+10 | 2921.79 | 0.902118E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.520705E+10 | 4358.02 | 01-JAN-11:09 | 0.162546E+10 | 1348.26 | 01-JAN-11:09 |
February | 0.471657E+10 | 4358.02 | 01-FEB-10:09 | 0.147229E+10 | 1348.26 | 01-FEB-10:09 |
March | 0.532596E+10 | 4358.02 | 01-MAR-10:09 | 0.166213E+10 | 1348.26 | 01-MAR-10:09 |
April | 0.505346E+10 | 4358.02 | 01-APR-09:09 | 0.157746E+10 | 1348.26 | 01-APR-09:09 |
May | 0.526650E+10 | 4358.02 | 01-MAY-09:09 | 0.164379E+10 | 1348.26 | 01-MAY-09:09 |
June | 0.514264E+10 | 4358.02 | 01-JUN-09:09 | 0.160496E+10 | 1348.26 | 01-JUN-09:09 |
July | 0.517732E+10 | 4358.02 | 01-JUL-09:09 | 0.161629E+10 | 1348.26 | 01-JUL-09:09 |
August | 0.532596E+10 | 4358.02 | 01-AUG-09:09 | 0.166213E+10 | 1348.26 | 01-AUG-09:09 |
September | 0.505346E+10 | 4358.02 | 01-SEP-09:09 | 0.157746E+10 | 1348.26 | 01-SEP-09:09 |
October | 0.520705E+10 | 4358.02 | 01-OCT-10:09 | 0.162546E+10 | 1348.26 | 01-OCT-10:09 |
November | 0.505346E+10 | 4358.02 | 01-NOV-09:09 | 0.157746E+10 | 1348.26 | 01-NOV-09:09 |
December | 0.517732E+10 | 4358.02 | 01-DEC-10:09 | 0.161629E+10 | 1348.26 | 01-DEC-10:09 |
Annual Sum or Average | 0.617068E+11 | 0.192612E+11 | ||||
Minimum of Months | 0.471657E+10 | 4358.02 | 0.147229E+10 | 1348.26 | ||
Maximum of Months | 0.532596E+10 | 4358.02 | 0.166213E+10 | 1348.26 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.260353E+10 | 2179.01 | 01-JAN-11:09 | 0.812728E+09 | 674.13 | 01-JAN-11:09 |
February | 0.235828E+10 | 2179.01 | 01-FEB-10:09 | 0.736147E+09 | 674.13 | 01-FEB-10:09 |
March | 0.266298E+10 | 2179.01 | 01-MAR-10:09 | 0.831065E+09 | 674.13 | 01-MAR-10:09 |
April | 0.252673E+10 | 2179.01 | 01-APR-09:09 | 0.788729E+09 | 674.13 | 01-APR-09:09 |
May | 0.263325E+10 | 2179.01 | 01-MAY-09:09 | 0.821897E+09 | 674.13 | 01-MAY-09:09 |
June | 0.257132E+10 | 2179.01 | 01-JUN-09:09 | 0.802482E+09 | 674.13 | 01-JUN-09:09 |
July | 0.258866E+10 | 2179.01 | 01-JUL-09:09 | 0.808144E+09 | 674.13 | 01-JUL-09:09 |
August | 0.266298E+10 | 2179.01 | 01-AUG-09:09 | 0.831065E+09 | 674.13 | 01-AUG-09:09 |
September | 0.252673E+10 | 2179.01 | 01-SEP-09:09 | 0.788729E+09 | 674.13 | 01-SEP-09:09 |
October | 0.260353E+10 | 2179.01 | 01-OCT-10:09 | 0.812728E+09 | 674.13 | 01-OCT-10:09 |
November | 0.252673E+10 | 2179.01 | 01-NOV-09:09 | 0.788729E+09 | 674.13 | 01-NOV-09:09 |
December | 0.258866E+10 | 2179.01 | 01-DEC-10:09 | 0.808144E+09 | 674.13 | 01-DEC-10:09 |
Annual Sum or Average | 0.308534E+11 | 0.963059E+10 | ||||
Minimum of Months | 0.235828E+10 | 2179.01 | 0.736147E+09 | 674.13 | ||
Maximum of Months | 0.266298E+10 | 2179.01 | 0.831065E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.260353E+10 | 2179.01 | 01-JAN-11:09 | 0.812728E+09 | 674.13 | 01-JAN-11:09 |
February | 0.235828E+10 | 2179.01 | 01-FEB-10:09 | 0.736147E+09 | 674.13 | 01-FEB-10:09 |
March | 0.266298E+10 | 2179.01 | 01-MAR-10:09 | 0.831065E+09 | 674.13 | 01-MAR-10:09 |
April | 0.252673E+10 | 2179.01 | 01-APR-09:09 | 0.788729E+09 | 674.13 | 01-APR-09:09 |
May | 0.263325E+10 | 2179.01 | 01-MAY-09:09 | 0.821897E+09 | 674.13 | 01-MAY-09:09 |
June | 0.257132E+10 | 2179.01 | 01-JUN-09:09 | 0.802482E+09 | 674.13 | 01-JUN-09:09 |
July | 0.258866E+10 | 2179.01 | 01-JUL-09:09 | 0.808144E+09 | 674.13 | 01-JUL-09:09 |
August | 0.266298E+10 | 2179.01 | 01-AUG-09:09 | 0.831065E+09 | 674.13 | 01-AUG-09:09 |
September | 0.252673E+10 | 2179.01 | 01-SEP-09:09 | 0.788729E+09 | 674.13 | 01-SEP-09:09 |
October | 0.260353E+10 | 2179.01 | 01-OCT-10:09 | 0.812728E+09 | 674.13 | 01-OCT-10:09 |
November | 0.252673E+10 | 2179.01 | 01-NOV-09:09 | 0.788729E+09 | 674.13 | 01-NOV-09:09 |
December | 0.258866E+10 | 2179.01 | 01-DEC-10:09 | 0.808144E+09 | 674.13 | 01-DEC-10:09 |
Annual Sum or Average | 0.308534E+11 | 0.963059E+10 | ||||
Minimum of Months | 0.235828E+10 | 2179.01 | 0.736147E+09 | 674.13 | ||
Maximum of Months | 0.266298E+10 | 2179.01 | 0.831065E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.260353E+10 | 2179.01 | 01-JAN-11:09 | 0.812728E+09 | 674.13 | 01-JAN-11:09 |
February | 0.235828E+10 | 2179.01 | 01-FEB-10:09 | 0.736147E+09 | 674.13 | 01-FEB-10:09 |
March | 0.266298E+10 | 2179.01 | 01-MAR-10:09 | 0.831065E+09 | 674.13 | 01-MAR-10:09 |
April | 0.252673E+10 | 2179.01 | 01-APR-09:09 | 0.788729E+09 | 674.13 | 01-APR-09:09 |
May | 0.263325E+10 | 2179.01 | 01-MAY-09:09 | 0.821897E+09 | 674.13 | 01-MAY-09:09 |
June | 0.257132E+10 | 2179.01 | 01-JUN-09:09 | 0.802482E+09 | 674.13 | 01-JUN-09:09 |
July | 0.258866E+10 | 2179.01 | 01-JUL-09:09 | 0.808144E+09 | 674.13 | 01-JUL-09:09 |
August | 0.266298E+10 | 2179.01 | 01-AUG-09:09 | 0.831065E+09 | 674.13 | 01-AUG-09:09 |
September | 0.252673E+10 | 2179.01 | 01-SEP-09:09 | 0.788729E+09 | 674.13 | 01-SEP-09:09 |
October | 0.260353E+10 | 2179.01 | 01-OCT-10:09 | 0.812728E+09 | 674.13 | 01-OCT-10:09 |
November | 0.252673E+10 | 2179.01 | 01-NOV-09:09 | 0.788729E+09 | 674.13 | 01-NOV-09:09 |
December | 0.258866E+10 | 2179.01 | 01-DEC-10:09 | 0.808144E+09 | 674.13 | 01-DEC-10:09 |
Annual Sum or Average | 0.308534E+11 | 0.963059E+10 | ||||
Minimum of Months | 0.235828E+10 | 2179.01 | 0.736147E+09 | 674.13 | ||
Maximum of Months | 0.266298E+10 | 2179.01 | 0.831065E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.260353E+10 | 2179.01 | 01-JAN-11:09 | 0.812728E+09 | 674.13 | 01-JAN-11:09 |
February | 0.235828E+10 | 2179.01 | 01-FEB-10:09 | 0.736147E+09 | 674.13 | 01-FEB-10:09 |
March | 0.266298E+10 | 2179.01 | 01-MAR-10:09 | 0.831065E+09 | 674.13 | 01-MAR-10:09 |
April | 0.252673E+10 | 2179.01 | 01-APR-09:09 | 0.788729E+09 | 674.13 | 01-APR-09:09 |
May | 0.263325E+10 | 2179.01 | 01-MAY-09:09 | 0.821897E+09 | 674.13 | 01-MAY-09:09 |
June | 0.257132E+10 | 2179.01 | 01-JUN-09:09 | 0.802482E+09 | 674.13 | 01-JUN-09:09 |
July | 0.258866E+10 | 2179.01 | 01-JUL-09:09 | 0.808144E+09 | 674.13 | 01-JUL-09:09 |
August | 0.266298E+10 | 2179.01 | 01-AUG-09:09 | 0.831065E+09 | 674.13 | 01-AUG-09:09 |
September | 0.252673E+10 | 2179.01 | 01-SEP-09:09 | 0.788729E+09 | 674.13 | 01-SEP-09:09 |
October | 0.260353E+10 | 2179.01 | 01-OCT-10:09 | 0.812728E+09 | 674.13 | 01-OCT-10:09 |
November | 0.252673E+10 | 2179.01 | 01-NOV-09:09 | 0.788729E+09 | 674.13 | 01-NOV-09:09 |
December | 0.258866E+10 | 2179.01 | 01-DEC-10:09 | 0.808144E+09 | 674.13 | 01-DEC-10:09 |
Annual Sum or Average | 0.308534E+11 | 0.963059E+10 | ||||
Minimum of Months | 0.235828E+10 | 2179.01 | 0.736147E+09 | 674.13 | ||
Maximum of Months | 0.266298E+10 | 2179.01 | 0.831065E+09 | 674.13 |
Report: SpaceGainsMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.180574E+10 | 0.100203E+11 | 0.223514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.379277E+10 |
February | 0.163016E+10 | 0.906661E+10 | 0.202238E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.342386E+10 |
March | 0.178954E+10 | 0.100410E+11 | 0.223972E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.323760E+10 |
April | 0.174484E+10 | 0.972311E+10 | 0.216880E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 263066.31 | 0.234210E+10 |
May | 0.179537E+10 | 0.100203E+11 | 0.223514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18126.53 | 0.284585E+10 |
June | 0.173447E+10 | 0.972311E+10 | 0.216880E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10790631.20 | 0.214035E+10 |
July | 0.181028E+10 | 0.100410E+11 | 0.223972E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47492243.37 | 0.184465E+10 |
August | 0.178501E+10 | 0.100203E+11 | 0.223514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6342418.50 | 0.150004E+10 |
September | 0.174937E+10 | 0.974384E+10 | 0.217339E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189535E+10 |
October | 0.180574E+10 | 0.100203E+11 | 0.223514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.264433E+10 |
November | 0.174613E+10 | 0.968165E+10 | 0.215964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.342567E+10 |
December | 0.181481E+10 | 0.100617E+11 | 0.224431E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.426579E+10 |
Annual Sum or Average | 0.212115E+11 | 0.118163E+12 | 0.263573E+11 | 64906485.89 | 0.333584E+11 | ||||
Minimum of Months | 0.163016E+10 | 0.906661E+10 | 0.202238E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150004E+10 |
Maximum of Months | 0.181481E+10 | 0.100617E+11 | 0.224431E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47492243.37 | 0.426579E+10 |
Report: SpaceGainsMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.902868E+09 | 0.540359E+10 | 0.111757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.204870E+10 |
February | 0.815075E+09 | 0.488932E+10 | 0.101119E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.180743E+10 |
March | 0.894769E+09 | 0.541477E+10 | 0.111986E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175070E+10 |
April | 0.872416E+09 | 0.524335E+10 | 0.108440E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 145190.54 | 0.131777E+10 |
May | 0.897684E+09 | 0.540359E+10 | 0.111757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9981.46 | 0.149246E+10 |
June | 0.867232E+09 | 0.524335E+10 | 0.108440E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5887992.11 | 0.110502E+10 |
July | 0.905135E+09 | 0.541477E+10 | 0.111986E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25999871.49 | 0.909477E+09 |
August | 0.892501E+09 | 0.540359E+10 | 0.111757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3455136.09 | 0.730617E+09 |
September | 0.874683E+09 | 0.525453E+10 | 0.108669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.959510E+09 |
October | 0.902868E+09 | 0.540359E+10 | 0.111757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.144358E+10 |
November | 0.873064E+09 | 0.522099E+10 | 0.107982E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.178646E+10 |
December | 0.907403E+09 | 0.542595E+10 | 0.112215E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.219772E+10 |
Annual Sum or Average | 0.106057E+11 | 0.637214E+11 | 0.131787E+11 | 35498171.68 | 0.175495E+11 | ||||
Minimum of Months | 0.815075E+09 | 0.488932E+10 | 0.101119E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.730617E+09 |
Maximum of Months | 0.907403E+09 | 0.542595E+10 | 0.112215E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25999871.49 | 0.219772E+10 |
Report: SpaceGainsMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.537120E+09 | 0.379993E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.206158E+10 |
February | 0.487879E+09 | 0.344119E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182969E+10 |
March | 0.551374E+09 | 0.387965E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175968E+10 |
April | 0.524810E+09 | 0.368699E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 69139.97 | 0.132274E+10 |
May | 0.544247E+09 | 0.383979E+10 | 0.892950E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9977.93 | 0.152440E+10 |
June | 0.532585E+09 | 0.374678E+10 | 0.871243E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5846657.01 | 0.115429E+10 |
July | 0.536472E+09 | 0.378000E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 25563358.16 | 0.960649E+09 |
August | 0.551374E+09 | 0.387965E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3454880.03 | 0.771053E+09 |
September | 0.524810E+09 | 0.368699E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.995723E+09 |
October | 0.537120E+09 | 0.379993E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146030E+10 |
November | 0.518979E+09 | 0.368699E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.180936E+10 |
December | 0.536472E+09 | 0.378000E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.224208E+10 |
Annual Sum or Average | 0.638324E+10 | 0.450079E+11 | 0.104672E+11 | 34944013.11 | 0.178915E+11 | ||||
Minimum of Months | 0.487879E+09 | 0.344119E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.771053E+09 |
Maximum of Months | 0.551374E+09 | 0.387965E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 25563358.16 | 0.224208E+10 |
Report: SpaceGainsMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.537120E+09 | 0.379993E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.205982E+10 |
February | 0.487879E+09 | 0.344119E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182786E+10 |
March | 0.551374E+09 | 0.387965E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175789E+10 |
April | 0.524810E+09 | 0.368699E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 69139.75 | 0.130937E+10 |
May | 0.544247E+09 | 0.383979E+10 | 0.892950E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9977.05 | 0.150826E+10 |
June | 0.532585E+09 | 0.374678E+10 | 0.871243E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5846797.81 | 0.114882E+10 |
July | 0.536472E+09 | 0.378000E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 25560909.34 | 0.958257E+09 |
August | 0.551374E+09 | 0.387965E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3454871.60 | 0.770307E+09 |
September | 0.524810E+09 | 0.368699E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.993978E+09 |
October | 0.537120E+09 | 0.379993E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.144808E+10 |
November | 0.518979E+09 | 0.368699E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.180473E+10 |
December | 0.536472E+09 | 0.378000E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.223861E+10 |
Annual Sum or Average | 0.638324E+10 | 0.450079E+11 | 0.104672E+11 | 34941695.55 | 0.178260E+11 | ||||
Minimum of Months | 0.487879E+09 | 0.344119E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.770307E+09 |
Maximum of Months | 0.551374E+09 | 0.387965E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 25560909.34 | 0.223861E+10 |
Report: SpaceGainsMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.537120E+09 | 0.379993E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.205860E+10 |
February | 0.487879E+09 | 0.344119E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182651E+10 |
March | 0.551374E+09 | 0.387965E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175657E+10 |
April | 0.524810E+09 | 0.368699E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 69138.58 | 0.128982E+10 |
May | 0.544247E+09 | 0.383979E+10 | 0.892950E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9975.75 | 0.148392E+10 |
June | 0.532585E+09 | 0.374678E+10 | 0.871243E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5847040.34 | 0.113270E+10 |
July | 0.536472E+09 | 0.378000E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 25573871.29 | 0.951806E+09 |
August | 0.551374E+09 | 0.387965E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3454825.88 | 0.768470E+09 |
September | 0.524810E+09 | 0.368699E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.989335E+09 |
October | 0.537120E+09 | 0.379993E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142985E+10 |
November | 0.518979E+09 | 0.368699E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.180144E+10 |
December | 0.536472E+09 | 0.378000E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.223567E+10 |
Annual Sum or Average | 0.638324E+10 | 0.450079E+11 | 0.104672E+11 | 34954851.84 | 0.177247E+11 | ||||
Minimum of Months | 0.487879E+09 | 0.344119E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.768470E+09 |
Maximum of Months | 0.551374E+09 | 0.387965E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 25573871.29 | 0.223567E+10 |
Report: SpaceGainsMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.183632E+10 | 0.520705E+10 | 0.162546E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.370721E+10 |
February | 0.167188E+10 | 0.471657E+10 | 0.147229E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.330360E+10 |
March | 0.189386E+10 | 0.532596E+10 | 0.166213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.316260E+10 |
April | 0.180380E+10 | 0.505346E+10 | 0.157746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 124251.69 | 0.224108E+10 |
May | 0.186509E+10 | 0.526650E+10 | 0.164379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17915.00 | 0.260705E+10 |
June | 0.182945E+10 | 0.514264E+10 | 0.160496E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10519474.19 | 0.194798E+10 |
July | 0.183943E+10 | 0.517732E+10 | 0.161629E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46063133.31 | 0.170234E+10 |
August | 0.189386E+10 | 0.532596E+10 | 0.166213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6214145.49 | 0.141035E+10 |
September | 0.180380E+10 | 0.505346E+10 | 0.157746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175739E+10 |
October | 0.183632E+10 | 0.520705E+10 | 0.162546E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.249537E+10 |
November | 0.176881E+10 | 0.505346E+10 | 0.157746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.327069E+10 |
December | 0.183943E+10 | 0.517732E+10 | 0.161629E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.406264E+10 |
Annual Sum or Average | 0.218821E+11 | 0.617068E+11 | 0.192612E+11 | 62938919.69 | 0.316683E+11 | ||||
Minimum of Months | 0.167188E+10 | 0.471657E+10 | 0.147229E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141035E+10 |
Maximum of Months | 0.189386E+10 | 0.532596E+10 | 0.166213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46063133.31 | 0.406264E+10 |
Report: SpaceGainsMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.918158E+09 | 0.260353E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.205378E+10 |
February | 0.835938E+09 | 0.235828E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182312E+10 |
March | 0.946926E+09 | 0.266298E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175117E+10 |
April | 0.901896E+09 | 0.252673E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 69256.28 | 0.124689E+10 |
May | 0.932542E+09 | 0.263325E+10 | 0.821897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9979.90 | 0.143643E+10 |
June | 0.914724E+09 | 0.257132E+10 | 0.802482E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5849192.92 | 0.108116E+10 |
July | 0.919713E+09 | 0.258866E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 25621822.43 | 0.932530E+09 |
August | 0.946926E+09 | 0.266298E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3455174.01 | 0.767082E+09 |
September | 0.901896E+09 | 0.252673E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.972687E+09 |
October | 0.918158E+09 | 0.260353E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138361E+10 |
November | 0.884402E+09 | 0.252673E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179830E+10 |
December | 0.919713E+09 | 0.258866E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.223356E+10 |
Annual Sum or Average | 0.109410E+11 | 0.308534E+11 | 0.963059E+10 | 35005425.54 | 0.174803E+11 | ||||
Minimum of Months | 0.835938E+09 | 0.235828E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.767082E+09 |
Maximum of Months | 0.946926E+09 | 0.266298E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 25621822.43 | 0.223356E+10 |
Report: SpaceGainsMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.918158E+09 | 0.260353E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.205324E+10 |
February | 0.835938E+09 | 0.235828E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182237E+10 |
March | 0.946926E+09 | 0.266298E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175072E+10 |
April | 0.901896E+09 | 0.252673E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 69253.97 | 0.124254E+10 |
May | 0.932542E+09 | 0.263325E+10 | 0.821897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9979.58 | 0.142903E+10 |
June | 0.914724E+09 | 0.257132E+10 | 0.802482E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5849392.84 | 0.107141E+10 |
July | 0.919713E+09 | 0.258866E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 25628034.35 | 0.927618E+09 |
August | 0.946926E+09 | 0.266298E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3455157.79 | 0.765788E+09 |
September | 0.901896E+09 | 0.252673E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.968061E+09 |
October | 0.918158E+09 | 0.260353E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137700E+10 |
November | 0.884402E+09 | 0.252673E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179714E+10 |
December | 0.919713E+09 | 0.258866E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.223240E+10 |
Annual Sum or Average | 0.109410E+11 | 0.308534E+11 | 0.963059E+10 | 35011818.53 | 0.174373E+11 | ||||
Minimum of Months | 0.835938E+09 | 0.235828E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.765788E+09 |
Maximum of Months | 0.946926E+09 | 0.266298E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 25628034.35 | 0.223240E+10 |
Report: SpaceGainsMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.918158E+09 | 0.260353E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.205150E+10 |
February | 0.835938E+09 | 0.235828E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181991E+10 |
March | 0.946926E+09 | 0.266298E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174897E+10 |
April | 0.901896E+09 | 0.252673E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 69247.98 | 0.123253E+10 |
May | 0.932542E+09 | 0.263325E+10 | 0.821897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9978.82 | 0.140978E+10 |
June | 0.914724E+09 | 0.257132E+10 | 0.802482E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5849889.02 | 0.104465E+10 |
July | 0.919713E+09 | 0.258866E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 25642599.50 | 0.913462E+09 |
August | 0.946926E+09 | 0.266298E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3455109.16 | 0.761653E+09 |
September | 0.901896E+09 | 0.252673E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.952874E+09 |
October | 0.918158E+09 | 0.260353E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136102E+10 |
November | 0.884402E+09 | 0.252673E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179362E+10 |
December | 0.919713E+09 | 0.258866E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.222842E+10 |
Annual Sum or Average | 0.109410E+11 | 0.308534E+11 | 0.963059E+10 | 35026824.50 | 0.173184E+11 | ||||
Minimum of Months | 0.835938E+09 | 0.235828E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.761653E+09 |
Maximum of Months | 0.946926E+09 | 0.266298E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 25642599.50 | 0.222842E+10 |
Report: SpaceGainsMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.918158E+09 | 0.260353E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.217513E+10 |
February | 0.835938E+09 | 0.235828E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.200463E+10 |
March | 0.946926E+09 | 0.266298E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185648E+10 |
April | 0.901896E+09 | 0.252673E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 69658.86 | 0.134017E+10 |
May | 0.932542E+09 | 0.263325E+10 | 0.821897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10185.16 | 0.171070E+10 |
June | 0.914724E+09 | 0.257132E+10 | 0.802482E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6053578.32 | 0.125826E+10 |
July | 0.919713E+09 | 0.258866E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 26458376.38 | 0.114460E+10 |
August | 0.946926E+09 | 0.266298E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3583151.17 | 0.955810E+09 |
September | 0.901896E+09 | 0.252673E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113266E+10 |
October | 0.918158E+09 | 0.260353E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153713E+10 |
November | 0.884402E+09 | 0.252673E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.204021E+10 |
December | 0.919713E+09 | 0.258866E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.256209E+10 |
Annual Sum or Average | 0.109410E+11 | 0.308534E+11 | 0.963059E+10 | 36174949.90 | 0.197179E+11 | ||||
Minimum of Months | 0.835938E+09 | 0.235828E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.955810E+09 |
Maximum of Months | 0.946926E+09 | 0.266298E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 26458376.38 | 0.256209E+10 |
Report: PeakSpaceGainsMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2159.72 | 01-JAN-13:09 | 6078.71 | 01-JAN-10:09 | 1348.26 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 8008.27 | 11-JAN-18:00 |
February | 2159.72 | 03-FEB-13:09 | 6078.71 | 01-FEB-10:09 | 1348.26 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 6021.79 | 24-FEB-18:00 |
March | 2159.72 | 03-MAR-13:09 | 6078.71 | 01-MAR-10:09 | 1348.26 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 6220.34 | 15-MAR-12:00 |
April | 2159.72 | 01-APR-12:09 | 6078.71 | 01-APR-09:09 | 1348.26 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 30.04 | 30-APR-17:00 | 4389.64 | 10-APR-11:10 |
May | 2159.72 | 05-MAY-12:09 | 6078.71 | 01-MAY-09:09 | 1348.26 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 30.21 | 22-MAY-15:00 | 4525.99 | 01-MAY-15:00 |
June | 2159.72 | 02-JUN-12:09 | 6078.71 | 01-JUN-09:09 | 1348.26 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 906.26 | 13-JUN-17:00 | 3683.14 | 07-JUN-11:10 |
July | 2159.72 | 01-JUL-12:09 | 6078.71 | 01-JUL-09:09 | 1348.26 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1478.38 | 22-JUL-15:00 | 3247.36 | 04-JUL-14:00 |
August | 2159.72 | 04-AUG-12:09 | 6078.71 | 01-AUG-09:09 | 1348.26 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 903.90 | 14-AUG-17:00 | 2485.15 | 30-AUG-17:00 |
September | 2159.72 | 01-SEP-12:09 | 6078.71 | 01-SEP-09:09 | 1348.26 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 3502.52 | 30-SEP-11:10 |
October | 2159.72 | 01-OCT-12:09 | 6078.71 | 01-OCT-09:09 | 1348.26 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 | 3956.19 | 27-OCT-17:00 |
November | 2159.72 | 03-NOV-12:09 | 6078.71 | 01-NOV-09:09 | 1348.26 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 6540.14 | 28-NOV-18:00 |
December | 2159.72 | 01-DEC-13:09 | 6078.71 | 01-DEC-10:09 | 1348.26 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 7439.34 | 29-DEC-18:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2159.72 | 6078.71 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2485.15 | |||||
Maximum of Months | 2159.72 | 6078.71 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 1478.38 | 8008.27 |
Report: PeakSpaceGainsMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1079.86 | 01-JAN-13:09 | 3278.04 | 01-JAN-10:09 | 674.13 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 4432.44 | 11-JAN-18:00 |
February | 1079.86 | 03-FEB-13:09 | 3278.04 | 01-FEB-10:09 | 674.13 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3322.94 | 24-FEB-18:00 |
March | 1079.86 | 03-MAR-13:09 | 3278.04 | 01-MAR-10:09 | 674.13 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 3469.27 | 15-MAR-12:00 |
April | 1079.86 | 01-APR-12:09 | 3278.04 | 01-APR-09:09 | 674.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.60 | 30-APR-17:00 | 2416.48 | 10-APR-11:10 |
May | 1079.86 | 05-MAY-12:09 | 3278.04 | 01-MAY-09:09 | 674.13 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.64 | 22-MAY-15:00 | 2582.35 | 01-MAY-15:00 |
June | 1079.86 | 02-JUN-12:09 | 3278.04 | 01-JUN-09:09 | 674.13 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 497.66 | 13-JUN-17:00 | 2210.81 | 07-JUN-11:10 |
July | 1079.86 | 01-JUL-12:09 | 3278.04 | 01-JUL-09:09 | 674.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 811.85 | 22-JUL-15:00 | 1955.50 | 04-JUL-14:00 |
August | 1079.86 | 04-AUG-12:09 | 3278.04 | 01-AUG-09:09 | 674.13 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 497.47 | 14-AUG-17:00 | 1344.49 | 30-AUG-17:00 |
September | 1079.86 | 01-SEP-12:09 | 3278.04 | 01-SEP-09:09 | 674.13 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 1981.07 | 30-SEP-11:10 |
October | 1079.86 | 01-OCT-12:09 | 3278.04 | 01-OCT-09:09 | 674.13 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 | 2189.68 | 27-OCT-17:00 |
November | 1079.86 | 03-NOV-12:09 | 3278.04 | 01-NOV-09:09 | 674.13 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3591.16 | 28-NOV-18:00 |
December | 1079.86 | 01-DEC-13:09 | 3278.04 | 01-DEC-10:09 | 674.13 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 4094.99 | 29-DEC-18:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1079.86 | 3278.04 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1344.49 | |||||
Maximum of Months | 1079.86 | 3278.04 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 811.85 | 4432.44 |
Report: PeakSpaceGainsMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1079.86 | 07-JAN-13:09 | 2921.79 | 01-JAN-10:09 | 674.13 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 4432.44 | 11-JAN-18:00 |
February | 1079.86 | 04-FEB-13:09 | 2921.79 | 01-FEB-09:09 | 674.13 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3322.92 | 24-FEB-18:00 |
March | 1079.86 | 04-MAR-13:09 | 2921.79 | 01-MAR-09:09 | 674.13 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 3469.28 | 15-MAR-12:00 |
April | 1079.86 | 01-APR-12:09 | 2921.79 | 01-APR-08:09 | 674.13 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.52 | 30-APR-15:00 | 2416.48 | 10-APR-11:10 |
May | 1079.86 | 06-MAY-12:09 | 2921.79 | 01-MAY-08:09 | 674.13 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.63 | 22-MAY-15:00 | 2595.78 | 01-MAY-15:00 |
June | 1079.86 | 03-JUN-12:09 | 2921.79 | 01-JUN-08:09 | 674.13 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 497.64 | 13-JUN-17:00 | 2225.78 | 07-JUN-11:10 |
July | 1079.86 | 01-JUL-12:09 | 2921.79 | 01-JUL-08:09 | 674.13 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 811.85 | 22-JUL-15:00 | 1943.54 | 04-JUL-14:00 |
August | 1079.86 | 05-AUG-12:09 | 2921.79 | 01-AUG-08:09 | 674.13 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 497.46 | 14-AUG-17:00 | 1344.43 | 30-AUG-17:00 |
September | 1079.86 | 02-SEP-12:09 | 2921.79 | 01-SEP-08:09 | 674.13 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 1986.51 | 30-SEP-11:10 |
October | 1079.86 | 07-OCT-12:09 | 2921.79 | 01-OCT-09:09 | 674.13 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 | 2189.67 | 27-OCT-17:00 |
November | 1079.86 | 04-NOV-12:09 | 2921.79 | 01-NOV-08:09 | 674.13 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3591.16 | 28-NOV-18:00 |
December | 1079.86 | 02-DEC-13:09 | 2921.79 | 01-DEC-09:09 | 674.13 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 4094.99 | 29-DEC-18:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1079.86 | 2921.79 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1344.43 | |||||
Maximum of Months | 1079.86 | 2921.79 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 811.85 | 4432.44 |
Report: PeakSpaceGainsMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1079.86 | 07-JAN-13:09 | 2921.79 | 01-JAN-10:09 | 674.13 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 4432.44 | 11-JAN-18:00 |
February | 1079.86 | 04-FEB-13:09 | 2921.79 | 01-FEB-09:09 | 674.13 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3322.92 | 24-FEB-18:00 |
March | 1079.86 | 04-MAR-13:09 | 2921.79 | 01-MAR-09:09 | 674.13 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 3469.28 | 15-MAR-12:00 |
April | 1079.86 | 01-APR-12:09 | 2921.79 | 01-APR-08:09 | 674.13 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.52 | 30-APR-15:00 | 2416.48 | 10-APR-11:10 |
May | 1079.86 | 06-MAY-12:09 | 2921.79 | 01-MAY-08:09 | 674.13 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.63 | 22-MAY-15:00 | 2589.73 | 01-MAY-15:00 |
June | 1079.86 | 03-JUN-12:09 | 2921.79 | 01-JUN-08:09 | 674.13 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 497.64 | 13-JUN-17:00 | 2202.10 | 07-JUN-11:10 |
July | 1079.86 | 01-JUL-12:09 | 2921.79 | 01-JUL-08:09 | 674.13 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 811.85 | 22-JUL-15:00 | 1924.37 | 04-JUL-14:00 |
August | 1079.86 | 05-AUG-12:09 | 2921.79 | 01-AUG-08:09 | 674.13 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 497.46 | 14-AUG-17:00 | 1344.43 | 30-AUG-17:00 |
September | 1079.86 | 02-SEP-12:09 | 2921.79 | 01-SEP-08:09 | 674.13 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 1984.62 | 30-SEP-11:10 |
October | 1079.86 | 07-OCT-12:09 | 2921.79 | 01-OCT-09:09 | 674.13 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 | 2189.67 | 27-OCT-17:00 |
November | 1079.86 | 04-NOV-12:09 | 2921.79 | 01-NOV-08:09 | 674.13 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3591.16 | 28-NOV-18:00 |
December | 1079.86 | 02-DEC-13:09 | 2921.79 | 01-DEC-09:09 | 674.13 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 4094.99 | 29-DEC-18:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1079.86 | 2921.79 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1344.43 | |||||
Maximum of Months | 1079.86 | 2921.79 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 811.85 | 4432.44 |
Report: PeakSpaceGainsMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1079.86 | 07-JAN-13:09 | 2921.79 | 01-JAN-10:09 | 674.13 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 4432.44 | 11-JAN-18:00 |
February | 1079.86 | 04-FEB-13:09 | 2921.79 | 01-FEB-09:09 | 674.13 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3322.92 | 24-FEB-18:00 |
March | 1079.86 | 04-MAR-13:09 | 2921.79 | 01-MAR-09:09 | 674.13 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 3469.28 | 15-MAR-12:00 |
April | 1079.86 | 01-APR-12:09 | 2921.79 | 01-APR-08:09 | 674.13 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.52 | 30-APR-15:00 | 2416.48 | 10-APR-11:10 |
May | 1079.86 | 06-MAY-12:09 | 2921.79 | 01-MAY-08:09 | 674.13 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.63 | 22-MAY-15:00 | 2559.36 | 01-MAY-15:00 |
June | 1079.86 | 03-JUN-12:09 | 2921.79 | 01-JUN-08:09 | 674.13 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 497.64 | 13-JUN-17:00 | 2136.32 | 07-JUN-11:10 |
July | 1079.86 | 01-JUL-12:09 | 2921.79 | 01-JUL-08:09 | 674.13 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 811.85 | 22-JUL-15:00 | 1873.97 | 04-JUL-14:00 |
August | 1079.86 | 05-AUG-12:09 | 2921.79 | 01-AUG-08:09 | 674.13 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 497.45 | 14-AUG-17:00 | 1344.43 | 30-AUG-17:00 |
September | 1079.86 | 02-SEP-12:09 | 2921.79 | 01-SEP-08:09 | 674.13 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 1977.58 | 30-SEP-11:10 |
October | 1079.86 | 07-OCT-12:09 | 2921.79 | 01-OCT-09:09 | 674.13 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 | 2189.67 | 27-OCT-17:00 |
November | 1079.86 | 04-NOV-12:09 | 2921.79 | 01-NOV-08:09 | 674.13 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3591.16 | 28-NOV-18:00 |
December | 1079.86 | 02-DEC-13:09 | 2921.79 | 01-DEC-09:09 | 674.13 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 4094.99 | 29-DEC-18:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1079.86 | 2921.79 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1344.43 | |||||
Maximum of Months | 1079.86 | 2921.79 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 811.85 | 4432.44 |
Report: PeakSpaceGainsMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2879.63 | 07-JAN-15:09 | 4358.02 | 01-JAN-11:09 | 1348.26 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 7954.69 | 11-JAN-18:00 |
February | 2879.63 | 04-FEB-15:09 | 4358.02 | 01-FEB-10:09 | 1348.26 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 5965.75 | 24-FEB-18:00 |
March | 2879.63 | 04-MAR-15:09 | 4358.02 | 01-MAR-10:09 | 1348.26 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 6220.31 | 15-MAR-12:00 |
April | 2879.63 | 01-APR-14:09 | 4358.02 | 01-APR-09:09 | 1348.26 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 29.72 | 30-APR-15:00 | 4339.63 | 10-APR-11:10 |
May | 2879.63 | 06-MAY-14:09 | 4358.02 | 01-MAY-09:09 | 1348.26 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 29.86 | 22-MAY-15:00 | 4380.12 | 01-MAY-15:00 |
June | 2879.63 | 03-JUN-14:09 | 4358.02 | 01-JUN-09:09 | 1348.26 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 894.07 | 13-JUN-17:00 | 3608.61 | 07-JUN-11:10 |
July | 2879.63 | 01-JUL-14:09 | 4358.02 | 01-JUL-09:09 | 1348.26 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1458.65 | 22-JUL-15:00 | 3025.32 | 04-JUL-14:00 |
August | 2879.63 | 05-AUG-14:09 | 4358.02 | 01-AUG-09:09 | 1348.26 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 893.53 | 14-AUG-17:00 | 2419.63 | 30-AUG-17:00 |
September | 2879.63 | 02-SEP-14:09 | 4358.02 | 01-SEP-09:09 | 1348.26 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 3424.49 | 30-SEP-11:10 |
October | 2879.63 | 07-OCT-14:09 | 4358.02 | 01-OCT-10:09 | 1348.26 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 | 3929.71 | 27-OCT-17:00 |
November | 2879.63 | 04-NOV-14:09 | 4358.02 | 01-NOV-09:09 | 1348.26 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 6451.20 | 28-NOV-18:00 |
December | 2879.63 | 02-DEC-15:09 | 4358.02 | 01-DEC-10:09 | 1348.26 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 7354.05 | 29-DEC-18:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2879.63 | 4358.02 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2419.63 | |||||
Maximum of Months | 2879.63 | 4358.02 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 1458.65 | 7954.69 |
Report: PeakSpaceGainsMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1439.81 | 07-JAN-15:09 | 2179.01 | 01-JAN-11:09 | 674.13 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 4432.43 | 11-JAN-18:00 |
February | 1439.81 | 04-FEB-15:09 | 2179.01 | 01-FEB-10:09 | 674.13 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3322.91 | 24-FEB-18:00 |
March | 1439.81 | 04-MAR-15:09 | 2179.01 | 01-MAR-10:09 | 674.13 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 3469.27 | 15-MAR-12:00 |
April | 1439.81 | 01-APR-14:09 | 2179.01 | 01-APR-09:09 | 674.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.56 | 30-APR-15:00 | 2416.47 | 10-APR-11:10 |
May | 1439.81 | 06-MAY-14:09 | 2179.01 | 01-MAY-09:09 | 674.13 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.63 | 22-MAY-15:00 | 2474.43 | 01-MAY-15:00 |
June | 1439.81 | 03-JUN-14:09 | 2179.01 | 01-JUN-09:09 | 674.13 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 497.65 | 13-JUN-17:00 | 2009.11 | 07-JUN-11:10 |
July | 1439.81 | 01-JUL-14:09 | 2179.01 | 01-JUL-09:09 | 674.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 811.87 | 22-JUL-15:00 | 1726.83 | 04-JUL-14:00 |
August | 1439.81 | 05-AUG-14:09 | 2179.01 | 01-AUG-09:09 | 674.13 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 497.47 | 14-AUG-17:00 | 1344.47 | 30-AUG-17:00 |
September | 1439.81 | 02-SEP-14:09 | 2179.01 | 01-SEP-09:09 | 674.13 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 1949.01 | 30-SEP-11:10 |
October | 1439.81 | 07-OCT-14:09 | 2179.01 | 01-OCT-10:09 | 674.13 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 | 2189.67 | 27-OCT-17:00 |
November | 1439.81 | 04-NOV-14:09 | 2179.01 | 01-NOV-09:09 | 674.13 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3591.15 | 28-NOV-18:00 |
December | 1439.81 | 02-DEC-15:09 | 2179.01 | 01-DEC-10:09 | 674.13 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 4094.97 | 29-DEC-18:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1439.81 | 2179.01 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1344.47 | |||||
Maximum of Months | 1439.81 | 2179.01 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 811.87 | 4432.43 |
Report: PeakSpaceGainsMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1439.81 | 07-JAN-15:09 | 2179.01 | 01-JAN-11:09 | 674.13 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 4432.43 | 11-JAN-18:00 |
February | 1439.81 | 04-FEB-15:09 | 2179.01 | 01-FEB-10:09 | 674.13 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3322.90 | 24-FEB-18:00 |
March | 1439.81 | 04-MAR-15:09 | 2179.01 | 01-MAR-10:09 | 674.13 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 3469.27 | 15-MAR-12:00 |
April | 1439.81 | 01-APR-14:09 | 2179.01 | 01-APR-09:09 | 674.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.56 | 30-APR-15:00 | 2416.47 | 10-APR-11:10 |
May | 1439.81 | 06-MAY-14:09 | 2179.01 | 01-MAY-09:09 | 674.13 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.63 | 22-MAY-15:00 | 2458.18 | 01-MAY-15:00 |
June | 1439.81 | 03-JUN-14:09 | 2179.01 | 01-JUN-09:09 | 674.13 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 497.65 | 13-JUN-17:00 | 2007.29 | 07-JUN-11:10 |
July | 1439.81 | 01-JUL-14:09 | 2179.01 | 01-JUL-09:09 | 674.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 811.87 | 22-JUL-15:00 | 1705.52 | 04-JUL-14:00 |
August | 1439.81 | 05-AUG-14:09 | 2179.01 | 01-AUG-09:09 | 674.13 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 497.47 | 14-AUG-17:00 | 1344.47 | 30-AUG-17:00 |
September | 1439.81 | 02-SEP-14:09 | 2179.01 | 01-SEP-09:09 | 674.13 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 1939.18 | 30-SEP-11:10 |
October | 1439.81 | 07-OCT-14:09 | 2179.01 | 01-OCT-10:09 | 674.13 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 | 2189.67 | 27-OCT-17:00 |
November | 1439.81 | 04-NOV-14:09 | 2179.01 | 01-NOV-09:09 | 674.13 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3591.15 | 28-NOV-18:00 |
December | 1439.81 | 02-DEC-15:09 | 2179.01 | 01-DEC-10:09 | 674.13 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 4094.97 | 29-DEC-18:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1439.81 | 2179.01 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1344.47 | |||||
Maximum of Months | 1439.81 | 2179.01 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 811.87 | 4432.43 |
Report: PeakSpaceGainsMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1439.81 | 07-JAN-15:09 | 2179.01 | 01-JAN-11:09 | 674.13 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 4432.43 | 11-JAN-18:00 |
February | 1439.81 | 04-FEB-15:09 | 2179.01 | 01-FEB-10:09 | 674.13 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3322.90 | 24-FEB-18:00 |
March | 1439.81 | 04-MAR-15:09 | 2179.01 | 01-MAR-10:09 | 674.13 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 3469.27 | 15-MAR-12:00 |
April | 1439.81 | 01-APR-14:09 | 2179.01 | 01-APR-09:09 | 674.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.56 | 30-APR-15:00 | 2416.47 | 10-APR-11:10 |
May | 1439.81 | 06-MAY-14:09 | 2179.01 | 01-MAY-09:09 | 674.13 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.63 | 22-MAY-15:00 | 2416.46 | 01-MAY-15:00 |
June | 1439.81 | 03-JUN-14:09 | 2179.01 | 01-JUN-09:09 | 674.13 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 497.65 | 13-JUN-17:00 | 2007.15 | 07-JUN-11:10 |
July | 1439.81 | 01-JUL-14:09 | 2179.01 | 01-JUL-09:09 | 674.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 811.87 | 22-JUL-15:00 | 1655.29 | 04-JUL-14:00 |
August | 1439.81 | 05-AUG-14:09 | 2179.01 | 01-AUG-09:09 | 674.13 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 497.47 | 14-AUG-17:00 | 1344.47 | 30-AUG-17:00 |
September | 1439.81 | 02-SEP-14:09 | 2179.01 | 01-SEP-09:09 | 674.13 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 1896.92 | 30-SEP-11:10 |
October | 1439.81 | 07-OCT-14:09 | 2179.01 | 01-OCT-10:09 | 674.13 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 | 2189.67 | 27-OCT-17:00 |
November | 1439.81 | 04-NOV-14:09 | 2179.01 | 01-NOV-09:09 | 674.13 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3591.15 | 28-NOV-18:00 |
December | 1439.81 | 02-DEC-15:09 | 2179.01 | 01-DEC-10:09 | 674.13 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 4094.97 | 29-DEC-18:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1439.81 | 2179.01 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1344.47 | |||||
Maximum of Months | 1439.81 | 2179.01 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 811.87 | 4432.43 |
Report: PeakSpaceGainsMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1439.81 | 07-JAN-15:09 | 2179.01 | 01-JAN-11:09 | 674.13 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 4485.93 | 11-JAN-18:00 |
February | 1439.81 | 04-FEB-15:09 | 2179.01 | 01-FEB-10:09 | 674.13 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3378.87 | 24-FEB-18:00 |
March | 1439.81 | 04-MAR-15:09 | 2179.01 | 01-MAR-10:09 | 674.13 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 3469.27 | 15-MAR-12:00 |
April | 1439.81 | 01-APR-14:09 | 2179.01 | 01-APR-09:09 | 674.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.75 | 30-APR-15:00 | 2466.41 | 10-APR-11:10 |
May | 1439.81 | 06-MAY-14:09 | 2179.01 | 01-MAY-09:09 | 674.13 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.98 | 22-MAY-15:00 | 2486.03 | 01-MAY-13:00 |
June | 1439.81 | 03-JUN-14:09 | 2179.01 | 01-JUN-09:09 | 674.13 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 509.95 | 13-JUN-17:00 | 2077.88 | 07-JUN-11:10 |
July | 1439.81 | 01-JUL-14:09 | 2179.01 | 01-JUL-09:09 | 674.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 831.95 | 22-JUL-15:00 | 1614.03 | 27-JUL-11:10 |
August | 1439.81 | 05-AUG-14:09 | 2179.01 | 01-AUG-09:09 | 674.13 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 507.81 | 14-AUG-17:00 | 1409.86 | 30-AUG-17:00 |
September | 1439.81 | 02-SEP-14:09 | 2179.01 | 01-SEP-09:09 | 674.13 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 1869.90 | 30-SEP-11:10 |
October | 1439.81 | 07-OCT-14:09 | 2179.01 | 01-OCT-10:09 | 674.13 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 | 2216.10 | 27-OCT-17:00 |
November | 1439.81 | 04-NOV-14:09 | 2179.01 | 01-NOV-09:09 | 674.13 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3679.96 | 28-NOV-18:00 |
December | 1439.81 | 02-DEC-15:09 | 2179.01 | 01-DEC-10:09 | 674.13 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 4180.14 | 29-DEC-18:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1439.81 | 2179.01 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1409.86 | |||||
Maximum of Months | 1439.81 | 2179.01 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 831.95 | 4485.93 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 12283.27 | 11-JAN-23:52 | 899.88 | 15996.59 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 135.11 |
February | 9981.58 | 18-FEB-00:03 | 719.91 | 12797.27 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.84 |
March | 8601.95 | 03-MAR-00:03 | 539.93 | 9597.96 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 9097.63 | 30-APR-16:25 | 4319.44 | 12157.41 | 2696.51 | 0.00 | 0.00 | 0.00 | 0.00 | 29.71 | 0.00 |
May | 7260.20 | 23-MAY-17:10 | 1799.77 | 6078.71 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 285.46 |
June | 23537.04 | 13-JUN-08:62 | 719.91 | 12797.27 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 151.98 |
July | 24012.23 | 24-JUL-08:62 | 719.91 | 12797.27 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 430.21 |
August | 18479.43 | 06-AUG-07:02 | 1079.86 | 1919.59 | 449.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 430.25 |
September | 9294.74 | 13-SEP-14:00 | 1439.81 | 6078.71 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 267.11 |
October | 7777.97 | 05-OCT-20:00 | 1079.86 | 6078.71 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.82 |
November | 9329.05 | 29-NOV-09:04 | 1439.81 | 25594.55 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 851.67 |
December | 10710.41 | 30-DEC-00:03 | 719.91 | 12797.27 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 256.80 |
Annual Sum or Average | |||||||||||
Minimum of Months | 7260.20 | 539.93 | 1919.59 | 449.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 24012.23 | 4319.44 | 25594.55 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 29.71 | 851.67 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5013.83 | 10-JAN-08:62 | 449.94 | 862.64 | 187.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 593.27 |
February | 4232.02 | 17-FEB-08:62 | 0.00 | 690.11 | 149.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 509.77 |
March | 3947.19 | 14-MAR-08:04 | 719.90 | 13802.27 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 418.74 |
April | 5083.77 | 30-APR-07:03 | 359.95 | 690.11 | 149.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 166.32 |
May | 4444.41 | 28-MAY-17:10 | 2159.71 | 6556.08 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 308.82 |
June | 12271.17 | 13-JUN-08:62 | 359.95 | 6901.14 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.94 |
July | 12926.26 | 22-JUL-08:62 | 539.93 | 10351.71 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.40 |
August | 13496.54 | 06-AUG-07:02 | 539.93 | 1035.17 | 224.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 240.26 |
September | 5182.12 | 13-SEP-14:00 | 719.90 | 3278.04 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 146.32 |
October | 3959.37 | 08-OCT-17:10 | 2159.71 | 6556.08 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 244.62 |
November | 4173.73 | 28-NOV-09:04 | 719.90 | 13802.27 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 504.12 |
December | 4299.06 | 08-DEC-09:04 | 719.90 | 13802.27 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 503.34 |
Annual Sum or Average | |||||||||||
Minimum of Months | 3947.19 | 0.00 | 690.11 | 149.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.40 | |
Maximum of Months | 13496.54 | 2159.71 | 13802.27 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 593.27 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5384.39 | 10-JAN-08:04 | 449.94 | 7688.92 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 629.03 |
February | 3694.37 | 19-FEB-09:03 | 719.90 | 12302.27 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 462.94 |
March | 3632.83 | 21-MAR-07:02 | 449.94 | 7688.92 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 455.74 |
April | 17171.93 | 30-APR-08:62 | 359.95 | 6151.14 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 151.76 |
May | 15856.85 | 01-MAY-07:02 | 449.94 | 7688.92 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 452.09 |
June | 18319.62 | 14-JUN-07:02 | 449.94 | 7688.92 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 320.53 |
July | 19085.72 | 20-JUL-07:02 | 449.94 | 7688.92 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 314.20 |
August | 18677.64 | 22-AUG-07:02 | 449.94 | 7688.92 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 231.67 |
September | 18323.23 | 28-SEP-07:02 | 449.94 | 7688.92 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 348.00 |
October | 7456.20 | 02-OCT-07:03 | 359.95 | 6151.14 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 352.62 |
November | 3649.47 | 04-NOV-07:02 | 449.94 | 7688.92 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 493.92 |
December | 4409.58 | 31-DEC-09:03 | 719.90 | 12302.27 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 503.61 |
Annual Sum or Average | |||||||||||
Minimum of Months | 3632.83 | 359.95 | 6151.14 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 151.76 | |
Maximum of Months | 19085.72 | 719.90 | 12302.27 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 629.03 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5711.57 | 10-JAN-08:04 | 449.94 | 7688.92 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 631.20 |
February | 3976.69 | 13-FEB-08:04 | 449.94 | 7688.92 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 489.62 |
March | 3367.13 | 12-MAR-08:03 | 629.92 | 10764.49 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 438.54 |
April | 16103.43 | 30-APR-08:62 | 359.95 | 6151.14 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 151.59 |
May | 15092.75 | 01-MAY-07:02 | 449.94 | 7688.92 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 452.01 |
June | 18183.75 | 14-JUN-07:02 | 449.94 | 7688.92 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 319.43 |
July | 18956.51 | 20-JUL-07:02 | 449.94 | 7688.92 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 313.42 |
August | 18553.22 | 22-AUG-07:02 | 449.94 | 7688.92 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 230.85 |
September | 18135.71 | 14-SEP-07:02 | 449.94 | 7688.92 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 230.55 |
October | 5583.24 | 02-OCT-07:03 | 359.95 | 6151.14 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 352.34 |
November | 3613.66 | 04-NOV-07:02 | 449.94 | 7688.92 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 489.38 |
December | 4094.20 | 18-DEC-08:04 | 449.94 | 7688.92 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 489.71 |
Annual Sum or Average | |||||||||||
Minimum of Months | 3367.13 | 359.95 | 6151.14 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 151.59 | |
Maximum of Months | 18956.51 | 629.92 | 10764.49 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 631.20 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5767.45 | 10-JAN-08:04 | 449.94 | 7688.92 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 630.29 |
February | 4732.13 | 17-FEB-08:05 | 359.95 | 6151.14 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 541.31 |
March | 3583.14 | 27-MAR-07:04 | 449.94 | 7688.92 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 421.98 |
April | 13114.47 | 30-APR-08:62 | 359.95 | 6151.14 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 151.19 |
May | 11899.09 | 01-MAY-07:02 | 449.94 | 7688.92 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 451.69 |
June | 18060.24 | 14-JUN-07:02 | 449.94 | 7688.92 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 315.06 |
July | 18876.96 | 20-JUL-07:02 | 449.94 | 7688.92 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 310.29 |
August | 18469.61 | 22-AUG-07:02 | 449.94 | 7688.92 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 227.20 |
September | 18048.41 | 14-SEP-07:02 | 449.94 | 7688.92 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 227.69 |
October | 3591.60 | 06-OCT-07:02 | 539.93 | 9226.71 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 440.84 |
November | 3906.06 | 20-NOV-08:04 | 449.94 | 7688.92 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 463.05 |
December | 4271.45 | 30-DEC-08:05 | 359.95 | 6151.14 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 523.03 |
Annual Sum or Average | |||||||||||
Minimum of Months | 3583.14 | 359.95 | 6151.14 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 151.19 | |
Maximum of Months | 18876.96 | 539.93 | 9226.71 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 630.29 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 11730.19 | 10-JAN-09:05 | 3167.59 | 18349.55 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1147.29 |
February | 9451.28 | 17-FEB-09:04 | 3167.59 | 18349.55 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 813.43 |
March | 9028.65 | 15-MAR-08:04 | 3167.59 | 18349.55 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 839.85 |
April | 7610.23 | 30-APR-15:00 | 2483.68 | 4358.02 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 29.72 | 0.00 |
May | 6708.19 | 01-MAY-08:63 | 1187.85 | 6881.08 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 724.92 |
June | 19166.51 | 13-JUN-08:62 | 1583.79 | 9174.77 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 128.03 |
July | 26372.97 | 24-JUL-08:62 | 1583.79 | 9174.77 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 414.83 |
August | 16326.30 | 18-AUG-08:63 | 1187.85 | 6881.08 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 210.20 |
September | 8431.00 | 13-SEP-14:10 | 2483.68 | 4358.02 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 262.92 |
October | 7136.38 | 05-OCT-19:50 | 395.95 | 2293.69 | 749.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.05 |
November | 9574.16 | 29-NOV-09:04 | 3167.59 | 18349.55 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 846.61 |
December | 10160.97 | 26-DEC-20:12 | 1583.79 | 9174.77 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.03 |
Annual Sum or Average | |||||||||||
Minimum of Months | 6708.19 | 395.95 | 2293.69 | 749.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 26372.97 | 3167.59 | 18349.55 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 29.72 | 1147.29 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5302.16 | 10-JAN-09:05 | 1583.79 | 9174.77 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 632.91 |
February | 4172.49 | 16-FEB-20:43 | 593.92 | 3440.54 | 1123.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.11 |
March | 3712.47 | 15-MAR-08:05 | 1583.79 | 9174.77 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 461.47 |
April | 3879.01 | 30-APR-15:00 | 1241.83 | 2179.01 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 16.56 | 0.00 |
May | 2909.09 | 01-MAY-07:02 | 0.00 | 573.42 | 187.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 428.97 |
June | 4319.01 | 13-JUN-17:00 | 1277.83 | 2179.01 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 497.65 | 0.00 |
July | 12118.31 | 23-JUL-09:02 | 1187.84 | 6881.08 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.90 |
August | 4490.66 | 14-AUG-16:50 | 1277.83 | 2179.01 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 471.55 | 0.00 |
September | 4260.68 | 13-SEP-14:10 | 1241.83 | 2179.01 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 146.33 |
October | 3413.57 | 06-OCT-07:02 | 0.00 | 688.11 | 224.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 404.87 |
November | 4053.79 | 29-NOV-09:05 | 1583.79 | 9174.77 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 465.51 |
December | 4517.85 | 27-DEC-09:05 | 1583.79 | 9174.77 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 504.58 |
Annual Sum or Average | |||||||||||
Minimum of Months | 2909.09 | 0.00 | 573.42 | 187.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12118.31 | 1583.79 | 9174.77 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 497.65 | 632.91 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5326.12 | 10-JAN-09:05 | 1583.79 | 9174.77 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 633.30 |
February | 4033.59 | 17-FEB-09:05 | 1583.79 | 9174.77 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 451.25 |
March | 3861.46 | 15-MAR-08:05 | 1583.79 | 9174.77 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 461.73 |
April | 3763.94 | 30-APR-15:00 | 1241.83 | 2179.01 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 16.56 | 0.00 |
May | 2894.88 | 01-MAY-07:02 | 0.00 | 573.42 | 187.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 426.22 |
June | 4214.58 | 13-JUN-17:00 | 1277.83 | 2179.01 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 497.65 | 0.00 |
July | 11969.07 | 23-JUL-09:02 | 1187.84 | 6881.08 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.61 |
August | 4405.83 | 14-AUG-16:50 | 1277.83 | 2179.01 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 471.55 | 0.00 |
September | 4168.36 | 13-SEP-14:20 | 1241.83 | 2179.01 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 146.33 |
October | 3389.19 | 06-OCT-07:02 | 0.00 | 688.11 | 224.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 401.60 |
November | 4077.66 | 29-NOV-09:05 | 1583.79 | 9174.77 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 465.86 |
December | 4541.81 | 27-DEC-09:05 | 1583.79 | 9174.77 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 504.93 |
Annual Sum or Average | |||||||||||
Minimum of Months | 2894.88 | 0.00 | 573.42 | 187.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11969.07 | 1583.79 | 9174.77 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 497.65 | 633.30 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5375.08 | 10-JAN-09:05 | 1583.79 | 9174.77 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 634.17 |
February | 4128.57 | 23-FEB-20:43 | 593.92 | 3440.54 | 1123.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.48 |
March | 3910.09 | 15-MAR-08:05 | 1583.79 | 9174.77 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 462.53 |
April | 3505.46 | 30-APR-15:00 | 1241.83 | 2179.01 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 16.56 | 0.00 |
May | 2837.87 | 01-MAY-07:02 | 0.00 | 573.42 | 187.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 417.71 |
June | 3998.79 | 13-JUN-17:00 | 1277.83 | 2179.01 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 497.65 | 0.00 |
July | 11678.46 | 23-JUL-09:02 | 1187.84 | 6881.08 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.34 |
August | 4211.40 | 14-AUG-17:00 | 1277.83 | 2179.01 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 497.47 | 0.00 |
September | 3984.05 | 13-SEP-14:20 | 1241.83 | 2179.01 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 146.33 |
October | 3303.97 | 06-OCT-07:02 | 0.00 | 688.11 | 224.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 391.80 |
November | 4123.64 | 29-NOV-09:05 | 1583.79 | 9174.77 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 466.57 |
December | 4589.89 | 27-DEC-09:05 | 1583.79 | 9174.77 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 505.69 |
Annual Sum or Average | |||||||||||
Minimum of Months | 2837.87 | 0.00 | 573.42 | 187.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11678.46 | 1583.79 | 9174.77 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 497.65 | 634.17 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4702.30 | 12-JAN-09:05 | 1583.79 | 9174.77 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 586.07 |
February | 4449.50 | 17-FEB-08:05 | 0.00 | 458.74 | 149.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 481.22 |
March | 3958.97 | 15-MAR-08:05 | 1583.79 | 9174.77 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 504.13 |
April | 3127.24 | 30-APR-15:00 | 1241.83 | 2179.01 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 16.75 | 0.00 |
May | 2681.96 | 01-MAY-08:07 | 593.92 | 3440.54 | 1123.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 422.12 |
June | 3718.47 | 13-JUN-17:00 | 1277.83 | 2179.01 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 509.95 | 0.00 |
July | 11538.03 | 23-JUL-09:02 | 1187.84 | 6881.08 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.87 |
August | 3901.31 | 14-AUG-17:00 | 1277.83 | 2179.01 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 507.81 | 0.00 |
September | 3740.82 | 13-SEP-14:10 | 1241.83 | 2179.01 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 150.53 |
October | 3039.80 | 06-OCT-07:02 | 0.00 | 688.11 | 224.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 366.73 |
November | 4168.09 | 29-NOV-09:05 | 1583.79 | 9174.77 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 479.84 |
December | 4627.40 | 27-DEC-09:05 | 1583.79 | 9174.77 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 517.18 |
Annual Sum or Average | |||||||||||
Minimum of Months | 2681.96 | 0.00 | 458.74 | 149.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11538.03 | 1583.79 | 9174.77 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 509.95 | 586.07 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | |
January | 0.826753E+11 | 66247.21 | 04-JAN-18:49 | 0.708389E+11 | 164474.68 | 10-JAN-09:09 |
February | 0.738479E+11 | 63224.04 | 09-FEB-19:49 | 0.576057E+11 | 132929.18 | 13-FEB-09:09 |
March | 0.812898E+11 | 63178.45 | 08-MAR-19:00 | 0.522872E+11 | 122375.97 | 15-MAR-08:09 |
April | 0.767785E+11 | 66515.21 | 30-APR-14:39 | 0.120393E+11 | 94217.25 | 01-APR-08:09 |
May | 0.784365E+11 | 63605.37 | 22-MAY-15:20 | 0.766304E+10 | 65990.16 | 06-MAY-08:09 |
June | 0.777727E+11 | 72655.98 | 13-JUN-15:30 | 0.316172E+09 | 22887.94 | 08-JUN-08:09 |
July | 0.813456E+11 | 76510.93 | 22-JUL-15:00 | 19996537.08 | 8143.36 | 05-JUL-08:09 |
August | 0.842914E+11 | 69227.36 | 14-AUG-17:30 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 0.798931E+11 | 69943.67 | 13-SEP-13:00 | 28571029.68 | 4111.94 | 20-SEP-08:09 |
October | 0.807777E+11 | 63035.25 | 26-OCT-17:30 | 0.129786E+11 | 81045.04 | 23-OCT-08:09 |
November | 0.795324E+11 | 65309.90 | 30-NOV-18:19 | 0.443253E+11 | 131436.92 | 29-NOV-09:09 |
December | 0.828369E+11 | 63485.19 | 28-DEC-17:30 | 0.767731E+11 | 148258.40 | 30-DEC-09:09 |
Annual Sum or Average | 0.959478E+12 | 0.334876E+12 | ||||
Minimum of Months | 0.738479E+11 | 63035.25 | 0.00 | 0.00 | ||
Maximum of Months | 0.842914E+11 | 76510.93 | 0.767731E+11 | 164474.68 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.424448E+11 | 0.103620E+11 | 0.108804E+11 | 0.00 | 0.133696E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.561851E+10 | 0.00 |
February | 0.384292E+11 | 0.840287E+10 | 0.985143E+10 | 0.00 | 0.120716E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.509277E+10 | 0.00 |
March | 0.430726E+11 | 0.799109E+10 | 0.110523E+11 | 0.00 | 0.135064E+11 | 0.00 | 0.00 | 1499984.01 | 0.00 | 0.00 | 0.00 | 0.566596E+10 | 0.00 |
April | 0.411878E+11 | 0.640747E+10 | 0.105581E+11 | 0.00 | 0.126926E+11 | 0.00 | 0.00 | 0.529966E+09 | 0.00 | 0.00 | 0.00 | 0.540256E+10 | 0.00 |
May | 0.427427E+11 | 0.555859E+10 | 0.109629E+11 | 0.00 | 0.131820E+11 | 0.00 | 0.00 | 0.445192E+09 | 0.00 | 0.00 | 0.00 | 0.554502E+10 | 0.00 |
June | 0.416347E+11 | 0.484404E+10 | 0.106818E+11 | 0.00 | 0.128902E+11 | 0.00 | 0.00 | 0.240699E+10 | 0.00 | 0.00 | 0.00 | 0.531502E+10 | 0.00 |
July | 0.423277E+11 | 0.521402E+10 | 0.108460E+11 | 0.00 | 0.130935E+11 | 0.00 | 0.00 | 0.445534E+10 | 0.00 | 0.00 | 0.00 | 0.540901E+10 | 0.00 |
August | 0.430407E+11 | 0.611045E+10 | 0.110454E+11 | 0.00 | 0.133740E+11 | 0.00 | 0.00 | 0.527961E+10 | 0.00 | 0.00 | 0.00 | 0.544120E+10 | 0.00 |
September | 0.412197E+11 | 0.715749E+10 | 0.105649E+11 | 0.00 | 0.127291E+11 | 0.00 | 0.00 | 0.296963E+10 | 0.00 | 0.00 | 0.00 | 0.525216E+10 | 0.00 |
October | 0.424448E+11 | 0.875778E+10 | 0.108804E+11 | 0.00 | 0.130768E+11 | 0.00 | 0.00 | 0.129731E+09 | 0.00 | 0.00 | 0.00 | 0.548819E+10 | 0.00 |
November | 0.411240E+11 | 0.966589E+10 | 0.105443E+11 | 0.00 | 0.128291E+11 | 0.00 | 0.00 | 1686690.66 | 0.00 | 0.00 | 0.00 | 0.536743E+10 | 0.00 |
December | 0.423596E+11 | 0.106828E+11 | 0.108529E+11 | 0.00 | 0.133492E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.559232E+10 | 0.00 |
Annual Sum or Average | 0.502028E+12 | 0.911545E+11 | 0.128721E+12 | 0.156164E+12 | 0.00 | 0.162196E+11 | 0.651902E+11 | ||||||
Minimum of Months | 0.384292E+11 | 0.484404E+10 | 0.985143E+10 | 0.00 | 0.120716E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.509277E+10 | 0.00 |
Maximum of Months | 0.430726E+11 | 0.106828E+11 | 0.110523E+11 | 0.00 | 0.135064E+11 | 0.00 | 0.00 | 0.527961E+10 | 0.00 | 0.00 | 0.00 | 0.566596E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS [J] | COOLING:GAS [] | WATERSYSTEMS:GAS [] | COGENERATION:GAS [] | HUMIDIFIER:GAS [] | |
January | 0.00 | 0.00 | 0.708389E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.576057E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.522872E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.120393E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.766304E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.316172E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 19996537.08 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 28571029.68 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.129786E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.443253E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.767731E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.334876E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.767731E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum}[W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum}[W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum}[W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum}[W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 31196.17 | 01-JAN-11:09 | 6944.63 | 01-JAN-06:10 | 8089.53 | 01-JAN-11:09 | 0.00 | 10167.68 | 10-JAN-09:09 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 31196.17 | 01-FEB-10:09 | 6944.63 | 01-FEB-06:10 | 8089.53 | 01-FEB-10:09 | 0.00 | 9954.70 | 17-FEB-09:09 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 31196.17 | 01-MAR-10:09 | 6944.63 | 01-MAR-06:10 | 8089.53 | 01-MAR-10:09 | 0.00 | 9837.35 | 15-MAR-08:09 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 31196.17 | 01-APR-09:09 | 6944.63 | 01-APR-05:10 | 8089.53 | 01-APR-09:09 | 0.00 | 9636.51 | 01-APR-08:09 | 0.00 | 0.00 | 01-APR-00:10 |
May | 31196.17 | 01-MAY-09:09 | 6944.63 | 01-MAY-19:19 | 8089.53 | 01-MAY-09:09 | 0.00 | 9458.72 | 06-MAY-08:09 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 31196.17 | 01-JUN-09:09 | 6944.63 | 01-JUN-19:00 | 8089.53 | 01-JUN-09:09 | 0.00 | 9580.69 | 13-JUN-08:09 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 31196.17 | 01-JUL-09:09 | 6944.63 | 01-JUL-20:19 | 8089.53 | 01-JUL-09:09 | 0.00 | 9814.29 | 22-JUL-08:09 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 31196.17 | 01-AUG-09:09 | 6944.63 | 01-AUG-19:49 | 8089.53 | 01-AUG-09:09 | 0.00 | 9371.52 | 17-AUG-08:09 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 31196.17 | 01-SEP-09:09 | 6944.63 | 01-SEP-05:10 | 8089.53 | 01-SEP-09:09 | 0.00 | 9156.07 | 01-SEP-10:30 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 31196.17 | 01-OCT-10:09 | 6944.63 | 01-OCT-05:10 | 8089.53 | 01-OCT-10:09 | 0.00 | 9547.83 | 23-OCT-08:09 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 31196.17 | 01-NOV-09:09 | 6944.63 | 01-NOV-05:10 | 8089.53 | 01-NOV-09:09 | 0.00 | 9912.77 | 29-NOV-09:09 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 31196.17 | 01-DEC-10:09 | 6944.63 | 01-DEC-06:10 | 8089.53 | 01-DEC-10:09 | 0.00 | 10066.58 | 30-DEC-09:09 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 31196.17 | 6944.63 | 8089.53 | 0.00 | 9156.07 | 0.00 | 0.00 | |||||
Maximum of Months | 31196.17 | 6944.63 | 8089.53 | 0.00 | 10167.68 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum}[W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum}[W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 11862.24 | 04-JAN-14:20 | 0.00 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 8199.51 | 06-FEB-14:00 | 0.00 |
March | 94.08 | 19-MAR-19:19 | 0.00 | 0.00 | 0.00 | 8333.31 | 31-MAR-17:49 | 0.00 |
April | 13024.76 | 30-APR-14:00 | 0.00 | 0.00 | 0.00 | 11771.84 | 09-APR-13:39 | 0.00 |
May | 10346.19 | 22-MAY-14:00 | 0.00 | 0.00 | 0.00 | 9702.71 | 19-MAY-14:50 | 0.00 |
June | 17459.06 | 13-JUN-16:00 | 0.00 | 0.00 | 0.00 | 9718.72 | 16-JUN-13:09 | 0.00 |
July | 20347.41 | 22-JUL-14:00 | 0.00 | 0.00 | 0.00 | 9890.34 | 10-JUL-17:30 | 0.00 |
August | 16717.44 | 14-AUG-16:00 | 0.00 | 0.00 | 0.00 | 9717.51 | 30-AUG-12:39 | 0.00 |
September | 13973.19 | 13-SEP-14:09 | 0.00 | 0.00 | 0.00 | 11836.32 | 02-SEP-13:50 | 0.00 |
October | 2455.16 | 07-OCT-14:00 | 0.00 | 0.00 | 0.00 | 8248.00 | 15-OCT-12:00 | 0.00 |
November | 94.87 | 08-NOV-22:00 | 0.00 | 0.00 | 0.00 | 9728.95 | 14-NOV-13:50 | 0.00 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 9734.53 | 20-DEC-13:20 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 8199.51 | 0.00 | ||
Maximum of Months | 20347.41 | 0.00 | 0.00 | 0.00 | 11862.24 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 66247.21 | 04-JAN-18:49 | 31196.17 | 8089.53 | 6944.63 | 0.00 | 9454.56 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 63224.04 | 09-FEB-19:49 | 31196.17 | 8089.53 | 6944.63 | 0.00 | 9421.27 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 63178.45 | 08-MAR-19:00 | 31196.17 | 8089.53 | 6944.63 | 0.00 | 9379.56 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 66515.21 | 30-APR-14:39 | 31196.17 | 8089.53 | 0.00 | 0.00 | 9156.07 | 0.00 | 0.00 | 12635.49 | 0.00 |
May | 63605.37 | 22-MAY-15:20 | 31196.17 | 8089.53 | 0.00 | 0.00 | 9156.07 | 0.00 | 0.00 | 9714.58 | 0.00 |
June | 72655.98 | 13-JUN-15:30 | 31196.17 | 8089.53 | 0.00 | 0.00 | 9156.07 | 0.00 | 0.00 | 16651.56 | 0.00 |
July | 76510.93 | 22-JUL-15:00 | 31196.17 | 8089.53 | 0.00 | 0.00 | 9405.07 | 0.00 | 0.00 | 20254.04 | 0.00 |
August | 69227.36 | 14-AUG-17:30 | 31196.17 | 8089.53 | 0.00 | 0.00 | 9156.07 | 0.00 | 0.00 | 15337.18 | 0.00 |
September | 69943.67 | 13-SEP-13:00 | 31196.17 | 8089.53 | 0.00 | 0.00 | 9156.07 | 0.00 | 0.00 | 13910.43 | 0.00 |
October | 63035.25 | 26-OCT-17:30 | 31196.17 | 8089.53 | 6944.63 | 0.00 | 9236.57 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 65309.90 | 30-NOV-18:19 | 31196.17 | 8089.53 | 6944.63 | 0.00 | 9390.77 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 63485.19 | 28-DEC-17:30 | 31196.17 | 8089.53 | 6944.63 | 0.00 | 9679.75 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 63035.25 | 31196.17 | 8089.53 | 0.00 | 0.00 | 9156.07 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 76510.93 | 31196.17 | 8089.53 | 6944.63 | 0.00 | 9679.75 | 0.00 | 0.00 | 20254.04 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS {Maximum}[W] | HEATING:GAS {TIMESTAMP} | COOLING:GAS [] | WATERSYSTEMS:GAS [] | COGENERATION:GAS [] | |
January | 0.00 | 0.00 | 164474.68 | 10-JAN-09:09 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 132929.18 | 13-FEB-09:09 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 122375.97 | 15-MAR-08:09 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 94217.25 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 65990.16 | 06-MAY-08:09 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 22887.94 | 08-JUN-08:09 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 8143.36 | 05-JUL-08:09 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 4111.94 | 20-SEP-08:09 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 81045.04 | 23-OCT-08:09 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 131436.92 | 29-NOV-09:09 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 148258.40 | 30-DEC-09:09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 164474.68 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.50 | 20.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.17 | 20.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.67 | 20.50 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.50 | 20.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: LGSTORE1
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 496.00 | 21.03 | 76.83 | 20.66 | 76.83 | 20.66 |
February | 448.00 | 21.03 | 45.17 | 20.32 | 45.17 | 20.32 |
March | 496.00 | 21.05 | 42.83 | 20.46 | 42.83 | 20.46 |
April | 433.33 | 21.48 | 12.50 | 20.93 | 11.00 | 20.53 |
May | 432.50 | 21.68 | 22.50 | 23.79 | 0.50 | 19.65 |
June | 208.17 | 22.71 | 118.83 | 23.88 | 0.00 | 0.00 |
July | 91.50 | 23.00 | 280.67 | 23.90 | 0.00 | 0.00 |
August | 31.33 | 23.51 | 328.67 | 23.89 | 0.00 | 0.00 |
September | 121.50 | 23.03 | 171.33 | 23.88 | 0.00 | 0.00 |
October | 481.33 | 21.64 | 2.17 | 20.60 | 2.17 | 20.60 |
November | 480.00 | 21.07 | 24.00 | 20.51 | 24.00 | 20.51 |
December | 496.00 | 21.02 | 75.00 | 20.55 | 75.00 | 20.55 |
Annual Sum or Average | 4215.67 | 21.42 | 1200.50 | 23.11 | 277.50 | 20.52 |
Minimum of Months | 31.33 | 21.02 | 2.17 | 20.32 | 0.00 | 0.00 |
Maximum of Months | 496.00 | 23.51 | 328.67 | 23.90 | 76.83 | 20.66 |
Report: ComfortReportSimple55Monthly
For: SMSTORE1
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 496.00 | 21.53 | 29.50 | 19.91 | 29.50 | 19.91 |
February | 448.00 | 21.52 | 22.33 | 19.65 | 22.33 | 19.65 |
March | 496.00 | 21.58 | 22.17 | 19.79 | 22.17 | 19.79 |
April | 397.00 | 22.43 | 9.00 | 22.60 | 3.33 | 20.42 |
May | 381.83 | 22.58 | 37.67 | 23.89 | 0.00 | 0.00 |
June | 73.00 | 23.07 | 202.83 | 23.89 | 0.00 | 0.00 |
July | 25.83 | 23.30 | 307.67 | 23.90 | 0.00 | 0.00 |
August | 13.83 | 23.50 | 343.33 | 23.89 | 0.00 | 0.00 |
September | 45.00 | 23.13 | 211.50 | 23.89 | 0.00 | 0.00 |
October | 381.00 | 22.31 | 0.33 | 21.16 | 0.33 | 21.16 |
November | 480.00 | 21.68 | 13.67 | 19.85 | 13.67 | 19.85 |
December | 496.00 | 21.48 | 33.50 | 19.87 | 33.50 | 19.87 |
Annual Sum or Average | 3733.50 | 21.90 | 1233.50 | 23.48 | 124.83 | 19.84 |
Minimum of Months | 13.83 | 21.48 | 0.33 | 19.65 | 0.00 | 0.00 |
Maximum of Months | 496.00 | 23.50 | 343.33 | 23.90 | 33.50 | 21.16 |
Report: ComfortReportSimple55Monthly
For: SMSTORE2
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 371.00 | 21.12 | 26.67 | 21.11 | 26.67 | 21.11 |
February | 336.00 | 21.11 | 9.17 | 21.11 | 9.17 | 21.11 |
March | 379.00 | 21.13 | 7.33 | 21.11 | 7.33 | 21.11 |
April | 305.00 | 21.95 | 4.67 | 24.56 | 0.00 | 0.00 |
May | 300.50 | 22.20 | 34.33 | 23.91 | 0.00 | 0.00 |
June | 62.00 | 23.18 | 161.17 | 23.94 | 0.00 | 0.00 |
July | 15.17 | 23.50 | 249.00 | 23.98 | 0.00 | 0.00 |
August | 5.17 | 23.76 | 280.33 | 23.98 | 0.00 | 0.00 |
September | 35.50 | 23.34 | 163.50 | 23.94 | 0.00 | 0.00 |
October | 297.83 | 21.83 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 360.00 | 21.16 | 4.33 | 21.11 | 4.33 | 21.11 |
December | 369.00 | 21.11 | 27.00 | 21.11 | 27.00 | 21.11 |
Annual Sum or Average | 2836.17 | 21.49 | 967.50 | 23.74 | 74.50 | 21.11 |
Minimum of Months | 5.17 | 21.11 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 379.00 | 23.76 | 280.33 | 24.56 | 27.00 | 21.11 |
Report: ComfortReportSimple55Monthly
For: SMSTORE3
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 371.00 | 21.11 | 34.83 | 21.11 | 34.83 | 21.11 |
February | 336.00 | 21.11 | 14.83 | 21.11 | 14.83 | 21.11 |
March | 379.00 | 21.12 | 12.33 | 21.11 | 12.33 | 21.11 |
April | 308.83 | 21.86 | 3.83 | 24.57 | 0.17 | 21.11 |
May | 302.00 | 22.08 | 29.33 | 23.91 | 0.00 | 0.00 |
June | 73.00 | 23.14 | 147.33 | 23.94 | 0.00 | 0.00 |
July | 20.50 | 23.43 | 242.50 | 23.97 | 0.00 | 0.00 |
August | 5.33 | 23.75 | 277.83 | 23.97 | 0.00 | 0.00 |
September | 38.00 | 23.32 | 157.83 | 23.94 | 0.00 | 0.00 |
October | 305.33 | 21.78 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 360.00 | 21.14 | 6.67 | 21.11 | 6.67 | 21.11 |
December | 369.00 | 21.11 | 37.67 | 21.11 | 37.67 | 21.11 |
Annual Sum or Average | 2868.00 | 21.47 | 965.00 | 23.65 | 106.50 | 21.11 |
Minimum of Months | 5.33 | 21.11 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 379.00 | 23.75 | 277.83 | 24.57 | 37.67 | 21.11 |
Report: ComfortReportSimple55Monthly
For: SMSTORE4
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 371.00 | 21.11 | 49.33 | 21.11 | 49.33 | 21.11 |
February | 336.00 | 21.11 | 23.17 | 21.11 | 23.17 | 21.11 |
March | 379.00 | 21.12 | 20.50 | 21.11 | 20.50 | 21.11 |
April | 320.17 | 21.76 | 2.67 | 24.23 | 0.67 | 21.11 |
May | 308.50 | 21.92 | 16.00 | 23.92 | 0.00 | 0.00 |
June | 102.50 | 23.01 | 110.17 | 23.96 | 0.00 | 0.00 |
July | 38.50 | 23.33 | 225.50 | 23.97 | 0.00 | 0.00 |
August | 9.33 | 23.69 | 266.00 | 23.97 | 0.00 | 0.00 |
September | 51.17 | 23.27 | 145.67 | 23.93 | 0.00 | 0.00 |
October | 321.83 | 21.73 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 360.00 | 21.13 | 10.67 | 21.11 | 10.67 | 21.11 |
December | 369.00 | 21.11 | 51.50 | 21.11 | 51.50 | 21.11 |
Annual Sum or Average | 2967.00 | 21.47 | 921.17 | 23.48 | 155.83 | 21.11 |
Minimum of Months | 9.33 | 21.11 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 379.00 | 23.69 | 266.00 | 24.23 | 51.50 | 21.11 |
Report: ComfortReportSimple55Monthly
For: LGSTORE2
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.11 | 85.00 | 21.10 | 85.00 | 21.10 |
February | 308.00 | 21.11 | 32.00 | 21.10 | 32.00 | 21.10 |
March | 348.00 | 21.11 | 34.83 | 21.10 | 34.83 | 21.10 |
April | 308.50 | 21.42 | 4.17 | 21.83 | 3.50 | 21.13 |
May | 307.67 | 21.54 | 5.33 | 23.89 | 0.00 | 0.00 |
June | 204.33 | 22.52 | 51.33 | 23.91 | 0.00 | 0.00 |
July | 82.00 | 22.82 | 171.00 | 23.91 | 0.00 | 0.00 |
August | 24.33 | 23.34 | 218.00 | 23.91 | 0.00 | 0.00 |
September | 110.00 | 22.92 | 96.17 | 23.90 | 0.00 | 0.00 |
October | 337.17 | 21.54 | 1.17 | 21.15 | 1.17 | 21.15 |
November | 330.00 | 21.11 | 17.67 | 21.11 | 17.67 | 21.11 |
December | 338.00 | 21.11 | 87.67 | 21.10 | 87.67 | 21.10 |
Annual Sum or Average | 3038.00 | 21.46 | 804.33 | 23.00 | 261.83 | 21.10 |
Minimum of Months | 24.33 | 21.11 | 1.17 | 21.10 | 0.00 | 0.00 |
Maximum of Months | 348.00 | 23.34 | 218.00 | 23.91 | 87.67 | 21.15 |
Report: ComfortReportSimple55Monthly
For: SMSTORE5
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.10 | 96.67 | 21.09 | 96.67 | 21.09 |
February | 308.00 | 21.10 | 40.83 | 21.07 | 40.83 | 21.07 |
March | 348.00 | 21.11 | 46.17 | 21.08 | 46.17 | 21.08 |
April | 308.50 | 21.52 | 10.33 | 21.57 | 9.17 | 21.08 |
May | 303.50 | 21.63 | 7.00 | 22.82 | 2.67 | 21.08 |
June | 191.17 | 22.69 | 40.83 | 23.93 | 0.00 | 0.00 |
July | 83.17 | 23.01 | 149.67 | 23.93 | 0.00 | 0.00 |
August | 28.33 | 23.45 | 192.67 | 23.92 | 0.00 | 0.00 |
September | 98.50 | 23.09 | 83.67 | 23.92 | 0.00 | 0.00 |
October | 337.17 | 21.64 | 3.83 | 21.03 | 3.83 | 21.03 |
November | 330.00 | 21.11 | 25.33 | 21.07 | 25.33 | 21.07 |
December | 338.00 | 21.10 | 99.67 | 21.09 | 99.67 | 21.09 |
Annual Sum or Average | 3014.33 | 21.50 | 796.67 | 22.77 | 324.33 | 21.08 |
Minimum of Months | 28.33 | 21.10 | 3.83 | 21.03 | 0.00 | 0.00 |
Maximum of Months | 348.00 | 23.45 | 192.67 | 23.93 | 99.67 | 21.09 |
Report: ComfortReportSimple55Monthly
For: SMSTORE6
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.10 | 105.17 | 21.09 | 105.17 | 21.09 |
February | 308.00 | 21.10 | 45.50 | 21.07 | 45.50 | 21.07 |
March | 348.00 | 21.11 | 52.83 | 21.08 | 52.83 | 21.08 |
April | 309.17 | 21.49 | 12.33 | 21.48 | 11.17 | 21.07 |
May | 308.17 | 21.62 | 6.50 | 22.66 | 2.83 | 21.07 |
June | 205.33 | 22.65 | 36.50 | 23.92 | 0.17 | 21.36 |
July | 88.50 | 22.94 | 138.33 | 23.93 | 0.00 | 0.00 |
August | 33.17 | 23.42 | 186.17 | 23.92 | 0.00 | 0.00 |
September | 109.17 | 23.06 | 77.50 | 23.92 | 0.00 | 0.00 |
October | 338.67 | 21.61 | 4.50 | 21.03 | 4.50 | 21.03 |
November | 330.00 | 21.11 | 28.67 | 21.07 | 28.67 | 21.07 |
December | 338.00 | 21.10 | 110.17 | 21.09 | 110.17 | 21.09 |
Annual Sum or Average | 3056.17 | 21.50 | 804.17 | 22.65 | 361.00 | 21.09 |
Minimum of Months | 33.17 | 21.10 | 4.50 | 21.03 | 0.00 | 0.00 |
Maximum of Months | 348.00 | 23.42 | 186.17 | 23.93 | 110.17 | 21.36 |
Report: ComfortReportSimple55Monthly
For: SMSTORE7
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.10 | 128.50 | 21.10 | 128.50 | 21.10 |
February | 308.00 | 21.10 | 58.50 | 21.08 | 58.50 | 21.08 |
March | 348.00 | 21.10 | 69.33 | 21.08 | 69.33 | 21.08 |
April | 311.00 | 21.43 | 17.00 | 21.25 | 16.33 | 21.07 |
May | 318.17 | 21.58 | 4.50 | 21.11 | 4.50 | 21.11 |
June | 228.50 | 22.50 | 29.33 | 23.91 | 0.33 | 21.30 |
July | 100.67 | 22.78 | 121.00 | 23.93 | 0.00 | 0.00 |
August | 43.67 | 23.33 | 170.33 | 23.92 | 0.00 | 0.00 |
September | 141.67 | 22.96 | 65.00 | 23.92 | 0.00 | 0.00 |
October | 340.00 | 21.52 | 6.83 | 21.03 | 6.83 | 21.03 |
November | 330.00 | 21.11 | 39.00 | 21.07 | 39.00 | 21.07 |
December | 338.00 | 21.10 | 139.83 | 21.10 | 139.83 | 21.10 |
Annual Sum or Average | 3147.67 | 21.50 | 849.17 | 22.38 | 463.17 | 21.09 |
Minimum of Months | 43.67 | 21.10 | 4.50 | 21.03 | 0.00 | 0.00 |
Maximum of Months | 348.00 | 23.33 | 170.33 | 23.93 | 139.83 | 21.30 |
Report: ComfortReportSimple55Monthly
For: SMSTORE8
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.10 | 199.50 | 21.10 | 199.50 | 21.10 |
February | 308.00 | 21.10 | 160.17 | 21.10 | 160.17 | 21.10 |
March | 348.00 | 21.10 | 175.00 | 21.10 | 175.00 | 21.10 |
April | 316.00 | 21.39 | 35.17 | 21.14 | 34.67 | 21.08 |
May | 330.83 | 21.51 | 14.83 | 21.06 | 14.83 | 21.06 |
June | 262.00 | 22.23 | 17.33 | 23.82 | 0.83 | 21.13 |
July | 139.67 | 22.66 | 86.50 | 23.93 | 0.17 | 21.40 |
August | 68.67 | 23.13 | 103.00 | 23.92 | 0.00 | 0.00 |
September | 197.50 | 22.78 | 43.33 | 23.91 | 0.00 | 0.00 |
October | 340.00 | 21.38 | 18.67 | 21.05 | 18.67 | 21.05 |
November | 330.00 | 21.10 | 99.50 | 21.09 | 99.50 | 21.09 |
December | 338.00 | 21.10 | 263.67 | 21.10 | 263.67 | 21.10 |
Annual Sum or Average | 3318.67 | 21.50 | 1216.67 | 21.68 | 967.00 | 21.10 |
Minimum of Months | 68.67 | 21.10 | 14.83 | 21.05 | 0.00 | 0.00 |
Maximum of Months | 348.00 | 23.13 | 263.67 | 23.93 | 263.67 | 21.40 |
Report: OccupantComfortDataSummaryMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 496.00000 | 21.02876 | 31.26719 | -0.4446 | 9.41767 |
February | 448.00000 | 21.02239 | 32.29158 | -0.4328 | 9.13142 |
March | 496.00000 | 21.04045 | 32.42549 | -0.4243 | 8.94898 |
April | 480.00000 | 21.71445 | 32.35926 | -0.1972 | 7.08274 |
May | 496.00000 | 21.95331 | 38.29475 | -1.1740 | 35.99395 |
June | 480.00000 | 23.31210 | 44.21429 | -0.6568 | 15.30713 |
July | 496.00000 | 23.71527 | 44.73962 | -0.4978 | 10.81613 |
August | 496.00000 | 23.86141 | 44.79919 | -0.4459 | 9.36054 |
September | 480.00000 | 23.61807 | 42.38334 | -0.5573 | 12.21802 |
October | 496.00000 | 21.70074 | 40.97232 | -0.1572 | 6.42500 |
November | 480.00000 | 21.06951 | 36.54151 | -0.3763 | 8.12815 |
December | 496.00000 | 21.01434 | 30.44096 | -0.4697 | 9.82658 |
Annual Sum or Average | 5840.00000 | 22.09258 | 37.58970 | -0.4870 | 11.92388 |
Minimum of Months | 448.00000 | 21.01434 | 30.44096 | -1.1740 | 6.42500 |
Maximum of Months | 496.00000 | 23.86141 | 44.79919 | -0.1572 | 35.99395 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 496.00000 | 21.50006 | 32.22147 | -0.3192 | 7.91217 |
February | 448.00000 | 21.48834 | 33.20820 | -0.3099 | 7.63231 |
March | 496.00000 | 21.55193 | 33.03418 | -0.2942 | 7.54948 |
April | 480.00000 | 22.66537 | 31.98289 | 0.00956 | 6.32847 |
May | 496.00000 | 22.86459 | 37.24373 | -0.8996 | 24.00707 |
June | 480.00000 | 23.74243 | 43.14528 | -0.5212 | 11.17735 |
July | 496.00000 | 23.85611 | 44.02985 | -0.4515 | 9.47954 |
August | 496.00000 | 23.88313 | 44.27018 | -0.4337 | 9.05816 |
September | 480.00000 | 23.81144 | 41.93224 | -0.4908 | 10.39152 |
October | 496.00000 | 22.64714 | 40.11766 | 0.04765 | 6.25987 |
November | 480.00000 | 21.65696 | 36.76509 | -0.2392 | 6.97074 |
December | 496.00000 | 21.44978 | 31.31722 | -0.3504 | 8.20550 |
Annual Sum or Average | 5840.00000 | 22.59807 | 37.46262 | -0.3552 | 9.60650 |
Minimum of Months | 448.00000 | 21.44978 | 31.31722 | -0.8996 | 6.25987 |
Maximum of Months | 496.00000 | 23.88313 | 44.27018 | 0.04765 | 24.00707 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 21.11616 | 31.18867 | -0.4113 | 8.67825 |
February | 336.00000 | 21.11167 | 32.40195 | -0.3955 | 8.33760 |
March | 379.00000 | 21.13148 | 31.75432 | -0.3919 | 8.28961 |
April | 360.00000 | 22.26793 | 30.71984 | -0.0775 | 6.54179 |
May | 375.00000 | 22.54565 | 36.75469 | -0.9900 | 27.81496 |
June | 366.00000 | 23.77651 | 42.84031 | -0.5151 | 11.07257 |
July | 369.00000 | 23.92796 | 44.43818 | -0.4295 | 9.11889 |
August | 379.00000 | 23.95816 | 44.89960 | -0.4090 | 8.65586 |
September | 360.00000 | 23.86431 | 41.88647 | -0.4758 | 10.06821 |
October | 371.00000 | 22.24323 | 39.63499 | -0.0370 | 6.32743 |
November | 360.00000 | 21.16812 | 36.26323 | -0.3461 | 7.63054 |
December | 369.00000 | 21.10771 | 30.19671 | -0.4365 | 9.05687 |
Annual Sum or Average | 4395.00000 | 22.35994 | 36.95343 | -0.4109 | 10.17235 |
Minimum of Months | 336.00000 | 21.10771 | 30.19671 | -0.9900 | 6.32743 |
Maximum of Months | 379.00000 | 23.95816 | 44.89960 | -0.0370 | 27.81496 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 21.10881 | 31.20387 | -0.4238 | 8.89941 |
February | 336.00000 | 21.10778 | 32.40972 | -0.4061 | 8.52055 |
March | 379.00000 | 21.12175 | 31.77391 | -0.4033 | 8.47901 |
April | 360.00000 | 22.16614 | 30.90642 | -0.1064 | 6.65530 |
May | 375.00000 | 22.44272 | 36.98054 | -1.0292 | 29.56399 |
June | 366.00000 | 23.74419 | 42.93545 | -0.5304 | 11.48453 |
July | 369.00000 | 23.91729 | 44.47229 | -0.4364 | 9.27214 |
August | 379.00000 | 23.95539 | 44.91368 | -0.4124 | 8.71113 |
September | 360.00000 | 23.85479 | 41.92219 | -0.4826 | 10.22119 |
October | 371.00000 | 22.15681 | 39.85583 | -0.0624 | 6.41042 |
November | 360.00000 | 21.14862 | 36.30951 | -0.3601 | 7.82771 |
December | 369.00000 | 21.10449 | 30.20278 | -0.4479 | 9.27640 |
Annual Sum or Average | 4395.00000 | 22.32730 | 37.02942 | -0.4264 | 10.48593 |
Minimum of Months | 336.00000 | 21.10449 | 30.20278 | -1.0292 | 6.41042 |
Maximum of Months | 379.00000 | 23.95539 | 44.91368 | -0.0624 | 29.56399 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 21.10398 | 31.21332 | -0.4372 | 9.15481 |
February | 336.00000 | 21.10462 | 32.41584 | -0.4184 | 8.74212 |
March | 379.00000 | 21.11360 | 31.78997 | -0.4163 | 8.70682 |
April | 360.00000 | 22.00763 | 31.20998 | -0.1502 | 6.80422 |
May | 375.00000 | 22.27563 | 37.35080 | -1.0927 | 32.36617 |
June | 366.00000 | 23.63375 | 43.25113 | -0.5781 | 12.85203 |
July | 369.00000 | 23.88118 | 44.59067 | -0.4578 | 9.77533 |
August | 379.00000 | 23.94680 | 44.96251 | -0.4225 | 8.89612 |
September | 360.00000 | 23.82020 | 42.04145 | -0.5040 | 10.74238 |
October | 371.00000 | 22.01636 | 40.21631 | -0.1029 | 6.47067 |
November | 360.00000 | 21.13282 | 36.34770 | -0.3739 | 8.03712 |
December | 369.00000 | 21.10076 | 30.20952 | -0.4620 | 9.55757 |
Annual Sum or Average | 4395.00000 | 22.26944 | 37.17286 | -0.4527 | 11.05599 |
Minimum of Months | 336.00000 | 21.10076 | 30.20952 | -1.0927 | 6.47067 |
Maximum of Months | 379.00000 | 23.94680 | 44.96251 | -0.1029 | 32.36617 |
Report: OccupantComfortDataSummaryMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.08486 | 32.19632 | -0.4706 | 9.82883 |
February | 308.00000 | 21.08655 | 33.32546 | -0.4489 | 9.32029 |
March | 348.00000 | 21.09024 | 32.69109 | -0.4474 | 9.28893 |
April | 330.00000 | 21.58216 | 32.89377 | -0.2458 | 7.35890 |
May | 344.00000 | 21.77739 | 39.32003 | -1.2477 | 39.31603 |
June | 336.00000 | 23.02244 | 45.62129 | -0.7623 | 18.85142 |
July | 338.00000 | 23.61913 | 45.85109 | -0.5430 | 12.12614 |
August | 348.00000 | 23.85317 | 45.59949 | -0.4599 | 9.62224 |
September | 330.00000 | 23.50973 | 43.61718 | -0.5998 | 13.38322 |
October | 340.00000 | 21.55751 | 42.18922 | -0.2088 | 6.65880 |
November | 330.00000 | 21.09572 | 37.36104 | -0.4058 | 8.55678 |
December | 338.00000 | 21.08070 | 31.15948 | -0.5005 | 10.36678 |
Annual Sum or Average | 4030.00000 | 22.03742 | 38.52671 | -0.5300 | 12.94977 |
Minimum of Months | 308.00000 | 21.08070 | 31.15948 | -1.2477 | 6.65880 |
Maximum of Months | 348.00000 | 23.85317 | 45.85109 | -0.2088 | 39.31603 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.06275 | 32.07143 | -0.4845 | 10.15686 |
February | 308.00000 | 21.06214 | 33.29214 | -0.4644 | 9.68225 |
March | 348.00000 | 21.06542 | 32.52478 | -0.4643 | 9.68073 |
April | 330.00000 | 21.64770 | 32.63460 | -0.2531 | 7.58849 |
May | 344.00000 | 21.86899 | 39.04947 | -1.2507 | 39.59275 |
June | 336.00000 | 23.16696 | 45.15603 | -0.7520 | 18.51016 |
July | 338.00000 | 23.66644 | 45.45072 | -0.5569 | 12.38021 |
August | 348.00000 | 23.85604 | 45.37189 | -0.4831 | 10.09839 |
September | 330.00000 | 23.60862 | 43.16484 | -0.5996 | 13.33734 |
October | 340.00000 | 21.63277 | 41.88768 | -0.2123 | 6.87785 |
November | 330.00000 | 21.06952 | 37.25230 | -0.4232 | 8.92416 |
December | 338.00000 | 21.06150 | 31.01981 | -0.5118 | 10.65756 |
Annual Sum or Average | 4030.00000 | 22.07168 | 38.27982 | -0.5397 | 13.18453 |
Minimum of Months | 308.00000 | 21.06150 | 31.01981 | -1.2507 | 6.87785 |
Maximum of Months | 348.00000 | 23.85604 | 45.45072 | -0.2123 | 39.59275 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.06242 | 32.07266 | -0.4911 | 10.29449 |
February | 308.00000 | 21.06230 | 33.29224 | -0.4710 | 9.81536 |
March | 348.00000 | 21.06535 | 32.52538 | -0.4710 | 9.81431 |
April | 330.00000 | 21.61622 | 32.69436 | -0.2653 | 7.70949 |
May | 344.00000 | 21.82553 | 39.15077 | -1.2713 | 40.54320 |
June | 336.00000 | 23.09643 | 45.36375 | -0.7797 | 19.50219 |
July | 338.00000 | 23.63352 | 45.58876 | -0.5732 | 12.88210 |
August | 348.00000 | 23.84581 | 45.45725 | -0.4918 | 10.30310 |
September | 330.00000 | 23.56952 | 43.29557 | -0.6172 | 13.87032 |
October | 340.00000 | 21.58881 | 41.98685 | -0.2271 | 6.95676 |
November | 330.00000 | 21.06797 | 37.25678 | -0.4299 | 9.05021 |
December | 338.00000 | 21.06132 | 31.02069 | -0.5178 | 10.78833 |
Annual Sum or Average | 4030.00000 | 22.04880 | 38.34930 | -0.5522 | 13.52296 |
Minimum of Months | 308.00000 | 21.06132 | 31.02069 | -1.2713 | 6.95676 |
Maximum of Months | 348.00000 | 23.84581 | 45.58876 | -0.2271 | 40.54320 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.06196 | 32.07426 | -0.5069 | 10.63408 |
February | 308.00000 | 21.06179 | 33.29375 | -0.4873 | 10.15014 |
March | 348.00000 | 21.06335 | 32.53075 | -0.4869 | 10.14171 |
April | 330.00000 | 21.54684 | 32.82735 | -0.2915 | 7.98010 |
May | 344.00000 | 21.71929 | 39.39928 | -1.3194 | 42.77937 |
June | 336.00000 | 22.90954 | 45.91036 | -0.8491 | 22.10039 |
July | 338.00000 | 23.54347 | 45.94777 | -0.6123 | 14.16342 |
August | 348.00000 | 23.81518 | 45.68333 | -0.5120 | 10.80958 |
September | 330.00000 | 23.44902 | 43.67154 | -0.6651 | 15.41456 |
October | 340.00000 | 21.48747 | 42.21190 | -0.2602 | 7.15578 |
November | 330.00000 | 21.06452 | 37.26712 | -0.4447 | 9.33301 |
December | 338.00000 | 21.06156 | 31.02121 | -0.5328 | 11.12474 |
Annual Sum or Average | 4030.00000 | 21.98934 | 38.52799 | -0.5824 | 14.38094 |
Minimum of Months | 308.00000 | 21.06156 | 31.02121 | -1.3194 | 7.15578 |
Maximum of Months | 348.00000 | 23.81518 | 45.94777 | -0.2602 | 42.77937 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.06131 | 32.05349 | -0.5650 | 11.98039 |
February | 308.00000 | 21.06184 | 33.23520 | -0.5480 | 11.49458 |
March | 348.00000 | 21.06285 | 32.48160 | -0.5453 | 11.43577 |
April | 330.00000 | 21.46197 | 32.92023 | -0.3448 | 8.70498 |
May | 344.00000 | 21.56218 | 39.67992 | -1.4169 | 47.48683 |
June | 336.00000 | 22.57217 | 46.77552 | -0.9829 | 27.56544 |
July | 338.00000 | 23.35978 | 46.56777 | -0.6948 | 16.97371 |
August | 348.00000 | 23.71972 | 46.12125 | -0.5680 | 12.37928 |
September | 330.00000 | 23.19422 | 44.27848 | -0.7682 | 19.04376 |
October | 340.00000 | 21.34493 | 42.41652 | -0.3283 | 7.87499 |
November | 330.00000 | 21.06227 | 37.17493 | -0.4955 | 10.37024 |
December | 338.00000 | 21.06146 | 30.92702 | -0.5893 | 12.48411 |
Annual Sum or Average | 4030.00000 | 21.88402 | 38.76254 | -0.6557 | 16.55391 |
Minimum of Months | 308.00000 | 21.06131 | 30.92702 | -1.4169 | 7.87499 |
Maximum of Months | 348.00000 | 23.71972 | 46.77552 | -0.3283 | 47.48683 |
Report: DXReportMonthly
For: PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 0.384286E+09 | 95161206.77 | 32.33 | 0.380781E+09 | 3505727.19 | 0.00 | 0.83 | 30-APR-16:40 | 0.00 | 01-APR-00:05 | 9821.08 | 30-APR-16:25 | 9821.08 | 30-APR-16:25 | 320.15 | 30-APR-19:50 | 2320.27 | 30-APR-16:25 | 0.00 | 01-APR-00:05 |
May | 0.227228E+09 | 59133175.77 | 34.50 | 0.192675E+09 | 34553370.23 | 0.00 | 0.67 | 22-MAY-15:00 | 0.00 | 01-MAY-00:10 | 7753.41 | 22-MAY-15:00 | 7088.99 | 22-MAY-15:00 | 812.81 | 23-MAY-17:10 | 1916.45 | 22-MAY-15:00 | 0.00 | 01-MAY-00:10 |
June | 0.163352E+10 | 0.393712E+09 | 109.02 | 0.134857E+10 | 0.284949E+09 | 0.00 | 1.00 | 13-JUN-08:62 | 0.00 | 01-JUN-00:10 | 26165.16 | 13-JUN-08:62 | 21827.20 | 13-JUN-08:62 | 6816.43 | 27-JUN-08:63 | 5568.34 | 13-JUN-08:62 | 0.00 | 01-JUN-00:10 |
July | 0.317575E+10 | 0.785475E+09 | 250.01 | 0.265671E+10 | 0.519044E+09 | 0.00 | 1.00 | 10-JUL-08:62 | 0.00 | 01-JUL-00:05 | 26303.57 | 18-JUL-08:62 | 24286.42 | 22-JUL-08:62 | 8950.50 | 24-JUL-08:62 | 5809.30 | 22-JUL-08:62 | 0.00 | 01-JUL-00:05 |
August | 0.345604E+10 | 0.867275E+09 | 321.38 | 0.279772E+10 | 0.658318E+09 | 0.00 | 1.00 | 14-AUG-17:00 | 0.00 | 01-AUG-00:10 | 17506.04 | 17-AUG-08:63 | 12636.95 | 15-AUG-08:63 | 7280.79 | 17-AUG-08:63 | 3725.61 | 17-AUG-08:63 | 0.00 | 01-AUG-00:10 |
September | 0.181040E+10 | 0.446790E+09 | 173.50 | 0.150176E+10 | 0.308638E+09 | 0.00 | 0.87 | 13-SEP-14:00 | 0.00 | 01-SEP-00:10 | 10867.62 | 13-SEP-14:00 | 9231.77 | 13-SEP-14:00 | 2595.58 | 12-SEP-14:00 | 2480.95 | 13-SEP-14:00 | 0.00 | 01-SEP-00:10 |
October | 2216916.08 | 615169.07 | 3.67 | 2216916.08 | 0.00 | 0.00 | 0.11 | 07-OCT-15:00 | 0.00 | 01-OCT-00:05 | 998.89 | 07-OCT-15:00 | 998.89 | 07-OCT-15:00 | 0.00 | 01-OCT-00:05 | 274.86 | 07-OCT-15:00 | 0.00 | 01-OCT-00:05 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.106894E+11 | 0.264816E+10 | 924.41 | 0.888043E+10 | 0.180901E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.345604E+10 | 0.867275E+09 | 321.38 | 0.279772E+10 | 0.658318E+09 | 0.00 | 1.00 | 0.00 | 26303.57 | 24286.42 | 8950.50 | 5809.30 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 5371755.68 | 1499984.01 | 8.83 | 4918034.27 | 453721.41 | 0.00 | 0.07 | 19-MAR-19:20 | 0.00 | 01-MAR-00:10 | 339.20 | 19-MAR-19:20 | 298.97 | 19-MAR-19:20 | 40.24 | 19-MAR-19:20 | 94.08 | 19-MAR-19:20 | 0.00 | 01-MAR-00:10 |
April | 0.815421E+09 | 0.190036E+09 | 146.25 | 0.815361E+09 | 60352.96 | 0.00 | 0.83 | 30-APR-15:00 | 0.00 | 01-APR-00:05 | 6054.06 | 30-APR-15:00 | 6054.06 | 30-APR-15:00 | 77.17 | 30-APR-07:03 | 1247.99 | 30-APR-15:00 | 0.00 | 01-APR-00:05 |
May | 0.929560E+09 | 0.222994E+09 | 180.22 | 0.891095E+09 | 38464462.50 | 0.00 | 0.71 | 22-MAY-15:00 | 0.00 | 01-MAY-00:10 | 5128.80 | 22-MAY-15:00 | 4918.49 | 22-MAY-15:00 | 481.30 | 23-MAY-14:00 | 1090.32 | 22-MAY-15:00 | 0.00 | 01-MAY-00:10 |
June | 0.286208E+10 | 0.650840E+09 | 352.22 | 0.263512E+10 | 0.226966E+09 | 0.00 | 1.00 | 13-JUN-08:62 | 0.00 | 01-JUN-00:10 | 14794.74 | 13-JUN-08:62 | 13250.97 | 13-JUN-08:62 | 1543.78 | 13-JUN-08:62 | 2901.64 | 13-JUN-08:62 | 0.00 | 01-JUN-00:10 |
July | 0.467754E+10 | 0.104064E+10 | 434.71 | 0.427168E+10 | 0.405861E+09 | 0.00 | 1.00 | 10-JUL-08:62 | 0.00 | 01-JUL-00:05 | 14834.07 | 10-JUL-08:62 | 14144.85 | 22-JUL-08:62 | 1882.02 | 18-JUL-08:62 | 3012.81 | 22-JUL-08:62 | 0.00 | 01-JUL-00:05 |
August | 0.533098E+10 | 0.117569E+10 | 462.40 | 0.484560E+10 | 0.485375E+09 | 0.00 | 1.00 | 06-AUG-07:02 | 0.00 | 01-AUG-00:10 | 14545.64 | 06-AUG-07:02 | 12338.40 | 06-AUG-07:02 | 2207.24 | 06-AUG-07:02 | 2857.35 | 06-AUG-07:02 | 0.00 | 01-AUG-00:10 |
September | 0.364735E+10 | 0.823319E+09 | 416.07 | 0.338121E+10 | 0.266142E+09 | 0.00 | 0.85 | 13-SEP-14:00 | 0.00 | 01-SEP-00:10 | 6508.39 | 13-SEP-14:00 | 5950.82 | 13-SEP-14:00 | 1009.30 | 12-SEP-14:00 | 1301.28 | 13-SEP-14:00 | 0.00 | 01-SEP-00:10 |
October | 0.477876E+09 | 0.120272E+09 | 146.11 | 0.469439E+09 | 8436988.77 | 0.00 | 0.59 | 08-OCT-17:10 | 0.00 | 01-OCT-00:05 | 3597.32 | 08-OCT-17:10 | 3096.47 | 08-OCT-17:10 | 500.85 | 08-OCT-17:10 | 829.09 | 08-OCT-17:10 | 0.00 | 01-OCT-00:05 |
November | 6051278.84 | 1686690.66 | 12.83 | 5796677.22 | 254601.62 | 0.00 | 0.07 | 08-NOV-23:00 | 0.00 | 01-NOV-00:10 | 342.15 | 08-NOV-23:00 | 305.50 | 08-NOV-23:00 | 36.65 | 08-NOV-23:00 | 94.87 | 08-NOV-23:00 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.187522E+11 | 0.422698E+10 | 2159.65 | 0.173202E+11 | 0.143201E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.533098E+10 | 0.117569E+10 | 462.40 | 0.484560E+10 | 0.485375E+09 | 0.00 | 1.00 | 0.00 | 14834.07 | 14144.85 | 2207.24 | 3012.81 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 0.118488E+09 | 26222959.79 | 33.49 | 0.118067E+09 | 421148.49 | 0.00 | 0.91 | 30-APR-08:62 | 0.00 | 01-APR-00:05 | 14607.61 | 30-APR-08:62 | 13364.51 | 30-APR-08:62 | 1243.11 | 30-APR-08:62 | 2851.86 | 30-APR-08:62 | 0.00 | 01-APR-00:05 |
May | 73171871.00 | 16570369.94 | 43.26 | 67307010.65 | 5864860.35 | 0.00 | 0.68 | 26-MAY-07:02 | 0.00 | 01-MAY-00:10 | 5096.84 | 26-MAY-07:02 | 4540.66 | 22-MAY-15:00 | 1469.19 | 26-MAY-07:02 | 1042.19 | 26-MAY-07:02 | 0.00 | 01-MAY-00:10 |
June | 0.713698E+09 | 0.153493E+09 | 149.00 | 0.623233E+09 | 90464739.78 | 0.00 | 1.00 | 13-JUN-07:02 | 0.00 | 01-JUN-00:10 | 16303.21 | 27-JUN-07:02 | 13648.87 | 26-JUN-07:02 | 7201.12 | 27-JUN-07:02 | 3199.75 | 27-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.103898E+10 | 0.227135E+09 | 194.29 | 0.936216E+09 | 0.102766E+09 | 0.00 | 1.00 | 07-JUL-07:02 | 0.00 | 01-JUL-00:05 | 16299.49 | 18-JUL-07:02 | 14710.89 | 22-JUL-07:02 | 6331.42 | 25-JUL-07:02 | 3288.55 | 22-JUL-07:02 | 0.00 | 01-JUL-00:05 |
August | 0.106186E+10 | 0.234322E+09 | 227.44 | 0.918787E+09 | 0.143076E+09 | 0.00 | 1.00 | 01-AUG-07:03 | 0.00 | 01-AUG-00:10 | 16199.51 | 17-AUG-07:02 | 13615.24 | 15-AUG-07:02 | 6595.98 | 17-AUG-07:02 | 3181.26 | 17-AUG-07:02 | 0.00 | 01-AUG-00:10 |
September | 0.689369E+09 | 0.151331E+09 | 161.91 | 0.606827E+09 | 82541707.69 | 0.00 | 1.00 | 01-SEP-07:03 | 0.00 | 01-SEP-00:10 | 15998.96 | 16-SEP-07:02 | 10926.24 | 14-SEP-07:02 | 6323.30 | 16-SEP-07:02 | 3143.59 | 16-SEP-07:02 | 0.00 | 01-SEP-00:10 |
October | 251974.47 | 61579.34 | 29.97 | 251938.98 | 35.49 | 0.00 | 0.05 | 07-OCT-15:00 | 0.00 | 01-OCT-00:05 | 286.67 | 07-OCT-15:00 | 286.67 | 07-OCT-15:00 | 0.10 | 02-OCT-07:03 | 69.85 | 07-OCT-15:00 | 0.00 | 01-OCT-00:05 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.369582E+10 | 0.809136E+09 | 839.36 | 0.327069E+10 | 0.425134E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.106186E+10 | 0.234322E+09 | 227.44 | 0.936216E+09 | 0.143076E+09 | 0.00 | 1.00 | 0.00 | 16303.21 | 14710.89 | 7201.12 | 3288.55 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 0.112864E+09 | 25003272.08 | 31.58 | 0.112526E+09 | 337991.26 | 0.00 | 0.78 | 30-APR-08:62 | 0.00 | 01-APR-00:05 | 13412.22 | 30-APR-08:62 | 12292.71 | 30-APR-08:62 | 1119.51 | 30-APR-08:62 | 2603.51 | 30-APR-08:62 | 0.00 | 01-APR-00:05 |
May | 62704386.47 | 14262840.47 | 41.50 | 58146881.25 | 4557505.23 | 0.00 | 0.58 | 22-MAY-15:00 | 0.00 | 01-MAY-00:10 | 4499.82 | 22-MAY-15:00 | 4293.08 | 22-MAY-15:00 | 898.14 | 26-MAY-07:02 | 992.44 | 22-MAY-15:00 | 0.00 | 01-MAY-00:10 |
June | 0.692182E+09 | 0.149155E+09 | 144.34 | 0.605012E+09 | 87169156.25 | 0.00 | 1.00 | 13-JUN-07:02 | 0.00 | 01-JUN-00:10 | 16218.13 | 27-JUN-07:02 | 13570.07 | 26-JUN-07:02 | 7170.60 | 27-JUN-07:02 | 3183.08 | 27-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.102038E+10 | 0.223093E+09 | 192.68 | 0.919760E+09 | 0.100617E+09 | 0.00 | 1.00 | 07-JUL-07:02 | 0.00 | 01-JUL-00:05 | 16214.05 | 18-JUL-07:02 | 14629.38 | 22-JUL-07:02 | 6300.94 | 25-JUL-07:02 | 3271.48 | 22-JUL-07:02 | 0.00 | 01-JUL-00:05 |
August | 0.104136E+10 | 0.229901E+09 | 226.94 | 0.901339E+09 | 0.140024E+09 | 0.00 | 1.00 | 04-AUG-07:03 | 0.00 | 01-AUG-00:10 | 16115.23 | 17-AUG-07:02 | 13539.79 | 15-AUG-07:02 | 6566.81 | 17-AUG-07:02 | 3164.73 | 17-AUG-07:02 | 0.00 | 01-AUG-00:10 |
September | 0.669324E+09 | 0.147117E+09 | 159.85 | 0.589725E+09 | 79599334.22 | 0.00 | 1.00 | 01-SEP-07:03 | 0.00 | 01-SEP-00:10 | 15914.84 | 16-SEP-07:02 | 10862.92 | 14-SEP-07:02 | 6299.54 | 16-SEP-07:02 | 3127.07 | 16-SEP-07:02 | 0.00 | 01-SEP-00:10 |
October | 142082.01 | 34797.96 | 28.58 | 142075.01 | 7.00 | 0.00 | 0.03 | 07-OCT-15:00 | 0.00 | 01-OCT-00:05 | 195.44 | 07-OCT-15:00 | 195.44 | 07-OCT-15:00 | 0.01 | 02-OCT-07:03 | 47.79 | 07-OCT-15:00 | 0.00 | 01-OCT-00:05 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.359896E+10 | 0.788567E+09 | 825.47 | 0.318665E+10 | 0.412304E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.104136E+10 | 0.229901E+09 | 226.94 | 0.919760E+09 | 0.140024E+09 | 0.00 | 1.00 | 0.00 | 16218.13 | 14629.38 | 7170.60 | 3271.48 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 98303783.01 | 21839370.63 | 28.63 | 98088807.59 | 214975.42 | 0.00 | 0.71 | 30-APR-15:00 | 0.00 | 01-APR-00:05 | 9973.02 | 30-APR-08:62 | 9226.48 | 30-APR-08:62 | 746.54 | 30-APR-08:62 | 1885.71 | 30-APR-08:62 | 0.00 | 01-APR-00:05 |
May | 49236592.07 | 11256331.73 | 37.12 | 46201084.68 | 3035507.39 | 0.00 | 0.54 | 22-MAY-15:00 | 0.00 | 01-MAY-00:10 | 4146.57 | 22-MAY-15:00 | 3953.78 | 22-MAY-15:00 | 224.97 | 22-MAY-14:00 | 925.46 | 22-MAY-15:00 | 0.00 | 01-MAY-00:10 |
June | 0.637387E+09 | 0.138193E+09 | 122.10 | 0.558388E+09 | 78999299.91 | 0.00 | 1.00 | 13-JUN-07:02 | 0.00 | 01-JUN-00:10 | 16255.75 | 27-JUN-07:02 | 13575.94 | 26-JUN-07:02 | 7212.25 | 27-JUN-07:02 | 3190.56 | 27-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.948243E+09 | 0.208004E+09 | 185.69 | 0.858371E+09 | 89872945.02 | 0.00 | 1.00 | 07-JUL-07:02 | 0.00 | 01-JUL-00:05 | 16251.38 | 18-JUL-07:02 | 14640.03 | 22-JUL-07:02 | 6334.91 | 25-JUL-07:02 | 3279.27 | 22-JUL-07:02 | 0.00 | 01-JUL-00:05 |
August | 0.955442E+09 | 0.211432E+09 | 221.16 | 0.829857E+09 | 0.125585E+09 | 0.00 | 1.00 | 06-AUG-08:62 | 0.00 | 01-AUG-00:10 | 16152.67 | 17-AUG-07:02 | 13548.76 | 15-AUG-07:02 | 6605.71 | 17-AUG-07:02 | 3172.14 | 17-AUG-07:02 | 0.00 | 01-AUG-00:10 |
September | 0.605147E+09 | 0.133693E+09 | 150.50 | 0.534861E+09 | 70285759.03 | 0.00 | 1.00 | 02-SEP-07:02 | 0.00 | 01-SEP-00:10 | 15951.58 | 16-SEP-07:02 | 10864.95 | 14-SEP-07:02 | 6337.51 | 16-SEP-07:02 | 3134.30 | 16-SEP-07:02 | 0.00 | 01-SEP-00:10 |
October | 14097.91 | 3477.14 | 17.87 | 14097.91 | 0.00 | 0.00 | 0.00 | 07-OCT-13:00 | 0.00 | 01-OCT-00:05 | 1.75 | 07-OCT-13:00 | 1.75 | 07-OCT-13:00 | 0.00 | 07-OCT-12:40 | 0.43 | 07-OCT-13:00 | 0.00 | 01-OCT-00:05 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.329377E+10 | 0.724421E+09 | 763.08 | 0.292578E+10 | 0.367994E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.955442E+09 | 0.211432E+09 | 221.16 | 0.858371E+09 | 0.125585E+09 | 0.00 | 1.00 | 0.00 | 16255.75 | 14640.03 | 7212.25 | 3279.27 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 0.164890E+09 | 42047632.04 | 17.83 | 0.163420E+09 | 1470043.46 | 0.00 | 0.73 | 30-APR-15:00 | 0.00 | 01-APR-00:05 | 8330.64 | 30-APR-15:00 | 8330.64 | 30-APR-15:00 | 173.55 | 28-APR-15:00 | 2030.93 | 30-APR-15:00 | 0.00 | 01-APR-00:05 |
May | 74397943.22 | 19680130.78 | 14.92 | 65621214.20 | 8776729.02 | 0.00 | 0.53 | 22-MAY-15:00 | 0.00 | 01-MAY-00:10 | 5960.45 | 22-MAY-15:00 | 5382.69 | 22-MAY-15:00 | 577.76 | 22-MAY-15:00 | 1530.58 | 22-MAY-15:00 | 0.00 | 01-MAY-00:10 |
June | 0.105650E+10 | 0.261339E+09 | 71.82 | 0.883711E+09 | 0.172787E+09 | 0.00 | 0.93 | 13-JUN-16:30 | 0.00 | 01-JUN-00:10 | 22055.94 | 13-JUN-08:62 | 17622.18 | 13-JUN-08:62 | 6509.92 | 27-JUN-08:63 | 4692.76 | 13-JUN-08:62 | 0.00 | 01-JUN-00:10 |
July | 0.188379E+10 | 0.471260E+09 | 161.71 | 0.160471E+10 | 0.279073E+09 | 0.00 | 1.00 | 18-JUL-08:62 | 0.00 | 01-JUL-00:05 | 26155.05 | 18-JUL-08:62 | 23974.90 | 22-JUL-08:62 | 9943.98 | 24-JUL-08:62 | 5779.76 | 22-JUL-08:62 | 0.00 | 01-JUL-00:05 |
August | 0.224227E+10 | 0.567431E+09 | 236.33 | 0.183559E+10 | 0.406684E+09 | 0.00 | 1.00 | 26-AUG-08:63 | 0.00 | 01-AUG-00:10 | 17293.74 | 18-AUG-08:63 | 12693.74 | 18-AUG-08:63 | 7105.58 | 17-AUG-08:63 | 3683.53 | 18-AUG-08:63 | 0.00 | 01-AUG-00:10 |
September | 0.120868E+10 | 0.303234E+09 | 108.00 | 0.102048E+10 | 0.188202E+09 | 0.00 | 0.81 | 13-SEP-14:10 | 0.00 | 01-SEP-00:10 | 9880.33 | 13-SEP-14:10 | 8365.22 | 13-SEP-14:10 | 2171.75 | 12-SEP-14:00 | 2298.13 | 13-SEP-14:10 | 0.00 | 01-SEP-00:10 |
October | 640451.31 | 178962.03 | 2.00 | 640451.31 | 0.00 | 0.00 | 0.06 | 07-OCT-15:00 | 0.00 | 01-OCT-00:05 | 581.51 | 07-OCT-15:00 | 581.51 | 07-OCT-15:00 | 0.00 | 01-OCT-00:05 | 161.79 | 07-OCT-15:00 | 0.00 | 01-OCT-00:05 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.663116E+10 | 0.166517E+10 | 612.61 | 0.557417E+10 | 0.105699E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.224227E+10 | 0.567431E+09 | 236.33 | 0.183559E+10 | 0.406684E+09 | 0.00 | 1.00 | 0.00 | 26155.05 | 23974.90 | 9943.98 | 5779.76 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 0.174087E+09 | 38953725.59 | 28.33 | 0.174087E+09 | 0.00 | 0.00 | 0.72 | 30-APR-15:00 | 0.00 | 01-APR-00:05 | 4824.45 | 30-APR-15:00 | 4824.45 | 30-APR-15:00 | 0.00 | 30-APR-13:10 | 1028.08 | 30-APR-15:00 | 0.00 | 01-APR-00:05 |
May | 0.141239E+09 | 32632176.57 | 30.67 | 0.127775E+09 | 13463876.96 | 0.00 | 0.53 | 22-MAY-15:00 | 0.00 | 01-MAY-00:10 | 3475.31 | 22-MAY-15:00 | 3278.01 | 22-MAY-15:00 | 305.55 | 23-MAY-14:10 | 777.51 | 22-MAY-15:00 | 0.00 | 01-MAY-00:10 |
June | 0.878821E+09 | 0.192643E+09 | 103.29 | 0.787228E+09 | 91593082.43 | 0.00 | 0.89 | 13-JUN-17:00 | 0.00 | 01-JUN-00:10 | 6468.12 | 13-JUN-16:30 | 6030.40 | 13-JUN-17:00 | 1166.33 | 26-JUN-17:10 | 1356.02 | 13-JUN-17:00 | 0.00 | 01-JUN-00:10 |
July | 0.197294E+10 | 0.434608E+09 | 233.06 | 0.175725E+10 | 0.215691E+09 | 0.00 | 1.00 | 22-JUL-08:62 | 0.00 | 01-JUL-00:05 | 13932.67 | 23-JUL-09:02 | 13208.37 | 22-JUL-08:62 | 1482.41 | 23-JUL-09:02 | 2841.77 | 22-JUL-08:62 | 0.00 | 01-JUL-00:05 |
August | 0.259996E+10 | 0.573229E+09 | 305.17 | 0.230675E+10 | 0.293209E+09 | 0.00 | 0.88 | 14-AUG-17:00 | 0.00 | 01-AUG-00:10 | 6178.36 | 14-AUG-17:00 | 6178.36 | 14-AUG-17:00 | 936.36 | 17-AUG-13:00 | 1320.99 | 14-AUG-17:00 | 0.00 | 01-AUG-00:10 |
September | 0.130063E+10 | 0.286223E+09 | 178.50 | 0.117568E+10 | 0.124957E+09 | 0.00 | 0.78 | 13-SEP-14:20 | 0.00 | 01-SEP-00:10 | 5508.77 | 13-SEP-14:20 | 4975.30 | 13-SEP-14:10 | 876.52 | 12-SEP-14:10 | 1126.41 | 13-SEP-14:20 | 0.00 | 01-SEP-00:10 |
October | 14844402.34 | 3473817.02 | 5.50 | 14844402.34 | 0.00 | 0.00 | 0.30 | 07-OCT-15:00 | 0.00 | 01-OCT-00:05 | 1762.21 | 07-OCT-15:00 | 1762.21 | 07-OCT-15:00 | 0.00 | 07-OCT-15:40 | 401.62 | 07-OCT-15:00 | 0.00 | 01-OCT-00:05 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.708252E+10 | 0.156176E+10 | 884.51 | 0.634361E+10 | 0.738914E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.259996E+10 | 0.573229E+09 | 305.17 | 0.230675E+10 | 0.293209E+09 | 0.00 | 1.00 | 0.00 | 13932.67 | 13208.37 | 1482.41 | 2841.77 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 0.160966E+09 | 36069892.99 | 27.00 | 0.160966E+09 | 0.00 | 0.00 | 0.71 | 30-APR-15:00 | 0.00 | 01-APR-00:05 | 4700.45 | 30-APR-15:00 | 4700.45 | 30-APR-15:00 | 0.00 | 30-APR-12:40 | 1004.59 | 30-APR-15:00 | 0.00 | 01-APR-00:05 |
May | 0.126422E+09 | 29277893.21 | 27.33 | 0.114298E+09 | 12124059.43 | 0.00 | 0.52 | 22-MAY-15:00 | 0.00 | 01-MAY-00:10 | 3349.05 | 22-MAY-15:00 | 3157.80 | 22-MAY-15:00 | 287.95 | 23-MAY-14:10 | 751.95 | 22-MAY-15:00 | 0.00 | 01-MAY-00:10 |
June | 0.823222E+09 | 0.180730E+09 | 98.17 | 0.736510E+09 | 86712373.98 | 0.00 | 0.88 | 13-JUN-17:00 | 0.00 | 01-JUN-00:10 | 6344.43 | 13-JUN-16:30 | 5916.81 | 13-JUN-17:00 | 1143.45 | 26-JUN-17:10 | 1333.34 | 13-JUN-17:00 | 0.00 | 01-JUN-00:10 |
July | 0.186723E+10 | 0.411849E+09 | 226.31 | 0.166279E+10 | 0.204444E+09 | 0.00 | 1.00 | 22-JUL-08:62 | 0.00 | 01-JUL-00:05 | 13792.48 | 23-JUL-09:02 | 13050.03 | 22-JUL-08:62 | 1497.39 | 23-JUL-09:02 | 2813.51 | 22-JUL-08:62 | 0.00 | 01-JUL-00:05 |
August | 0.247662E+10 | 0.547111E+09 | 301.61 | 0.219575E+10 | 0.280867E+09 | 0.00 | 0.87 | 14-AUG-17:00 | 0.00 | 01-AUG-00:10 | 6085.22 | 14-AUG-17:00 | 6085.22 | 14-AUG-17:00 | 922.02 | 17-AUG-13:00 | 1302.64 | 14-AUG-17:00 | 0.00 | 01-AUG-00:10 |
September | 0.121582E+10 | 0.267871E+09 | 169.83 | 0.109773E+10 | 0.118088E+09 | 0.00 | 0.77 | 13-SEP-14:20 | 0.00 | 01-SEP-00:10 | 5400.47 | 13-SEP-14:20 | 4873.87 | 13-SEP-14:20 | 859.74 | 12-SEP-14:10 | 1106.41 | 13-SEP-14:20 | 0.00 | 01-SEP-00:10 |
October | 11809029.94 | 2769649.29 | 3.83 | 11809029.94 | 0.00 | 0.00 | 0.28 | 07-OCT-15:00 | 0.00 | 01-OCT-00:05 | 1601.35 | 07-OCT-15:00 | 1601.35 | 07-OCT-15:00 | 0.00 | 07-OCT-15:40 | 367.22 | 07-OCT-15:00 | 0.00 | 01-OCT-00:05 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.668209E+10 | 0.147568E+10 | 854.08 | 0.597986E+10 | 0.702235E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.247662E+10 | 0.547111E+09 | 301.61 | 0.219575E+10 | 0.280867E+09 | 0.00 | 1.00 | 0.00 | 13792.48 | 13050.03 | 1497.39 | 2813.51 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 0.133384E+09 | 29980030.44 | 23.33 | 0.133384E+09 | 0.00 | 0.00 | 0.69 | 30-APR-15:00 | 0.00 | 01-APR-00:05 | 4426.07 | 30-APR-15:00 | 4426.07 | 30-APR-15:00 | 0.00 | 30-APR-14:40 | 953.01 | 30-APR-15:00 | 0.00 | 01-APR-00:05 |
May | 96905738.78 | 22570039.06 | 23.00 | 87592061.12 | 9313677.66 | 0.00 | 0.49 | 22-MAY-15:00 | 0.00 | 01-MAY-00:10 | 3063.40 | 22-MAY-15:00 | 2886.15 | 22-MAY-15:00 | 251.51 | 23-MAY-14:10 | 694.03 | 22-MAY-15:00 | 0.00 | 01-MAY-00:10 |
June | 0.706132E+09 | 0.155529E+09 | 88.08 | 0.629821E+09 | 76311092.71 | 0.00 | 0.87 | 13-JUN-17:00 | 0.00 | 01-JUN-00:10 | 6091.37 | 13-JUN-16:30 | 5684.68 | 13-JUN-17:00 | 1088.87 | 26-JUN-17:10 | 1287.65 | 13-JUN-17:00 | 0.00 | 01-JUN-00:10 |
July | 0.163404E+10 | 0.361485E+09 | 207.49 | 0.145580E+10 | 0.178235E+09 | 0.00 | 1.00 | 22-JUL-08:62 | 0.00 | 01-JUL-00:05 | 13540.08 | 23-JUL-09:02 | 12740.53 | 22-JUL-08:62 | 1536.80 | 23-JUL-09:02 | 2762.49 | 22-JUL-08:62 | 0.00 | 01-JUL-00:05 |
August | 0.218565E+10 | 0.485112E+09 | 289.08 | 0.193545E+10 | 0.250200E+09 | 0.00 | 0.86 | 14-AUG-17:00 | 0.00 | 01-AUG-00:10 | 5875.03 | 14-AUG-17:00 | 5875.03 | 14-AUG-17:00 | 891.64 | 17-AUG-13:00 | 1262.47 | 14-AUG-17:00 | 0.00 | 01-AUG-00:10 |
September | 0.103217E+10 | 0.227965E+09 | 145.50 | 0.929695E+09 | 0.102476E+09 | 0.00 | 0.76 | 13-SEP-14:20 | 0.00 | 01-SEP-00:10 | 5185.04 | 13-SEP-14:20 | 4673.16 | 13-SEP-14:20 | 826.37 | 12-SEP-14:10 | 1066.96 | 13-SEP-14:20 | 0.00 | 01-SEP-00:10 |
October | 7135539.41 | 1688677.05 | 2.83 | 7135539.41 | 0.00 | 0.00 | 0.22 | 07-OCT-15:00 | 0.00 | 01-OCT-00:05 | 1252.20 | 07-OCT-15:00 | 1252.20 | 07-OCT-15:00 | 0.00 | 07-OCT-15:20 | 291.27 | 07-OCT-15:00 | 0.00 | 01-OCT-00:05 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.579541E+10 | 0.128433E+10 | 779.32 | 0.517888E+10 | 0.616535E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.218565E+10 | 0.485112E+09 | 289.08 | 0.193545E+10 | 0.250200E+09 | 0.00 | 1.00 | 0.00 | 13540.08 | 12740.53 | 1536.80 | 2762.49 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 0.109004E+09 | 24652216.58 | 18.00 | 0.109004E+09 | 0.00 | 0.00 | 0.64 | 30-APR-15:00 | 0.00 | 01-APR-00:05 | 4046.40 | 30-APR-15:00 | 4046.40 | 30-APR-15:00 | 0.00 | 30-APR-14:10 | 884.08 | 30-APR-15:00 | 0.00 | 01-APR-00:05 |
May | 71647987.07 | 16815486.08 | 17.50 | 64936980.38 | 6711006.69 | 0.00 | 0.44 | 22-MAY-15:00 | 0.00 | 01-MAY-00:10 | 2726.76 | 22-MAY-15:00 | 2566.91 | 22-MAY-15:00 | 205.74 | 23-MAY-14:10 | 626.05 | 22-MAY-15:00 | 0.00 | 01-MAY-00:10 |
June | 0.593577E+09 | 0.131352E+09 | 72.58 | 0.528369E+09 | 65208147.23 | 0.00 | 0.83 | 13-JUN-17:00 | 0.00 | 01-JUN-00:10 | 5798.11 | 13-JUN-16:30 | 5402.49 | 13-JUN-17:00 | 974.13 | 26-JUN-17:10 | 1237.47 | 13-JUN-17:00 | 0.00 | 01-JUN-00:10 |
July | 0.131501E+10 | 0.291793E+09 | 176.86 | 0.117965E+10 | 0.135359E+09 | 0.00 | 1.00 | 22-JUL-08:62 | 0.00 | 01-JUL-00:05 | 13525.15 | 23-JUL-09:02 | 12652.41 | 22-JUL-08:62 | 1645.70 | 23-JUL-09:02 | 2751.91 | 22-JUL-08:62 | 0.00 | 01-JUL-00:05 |
August | 0.173488E+10 | 0.388104E+09 | 258.33 | 0.153743E+10 | 0.197455E+09 | 0.00 | 0.83 | 14-AUG-17:00 | 0.00 | 01-AUG-00:10 | 5563.66 | 14-AUG-17:00 | 5563.66 | 14-AUG-17:00 | 865.77 | 17-AUG-13:00 | 1208.96 | 14-AUG-17:00 | 0.00 | 01-AUG-00:10 |
September | 0.819906E+09 | 0.182081E+09 | 115.00 | 0.737416E+09 | 82489457.12 | 0.00 | 0.73 | 13-SEP-14:10 | 0.00 | 01-SEP-00:10 | 4916.12 | 13-SEP-14:10 | 4427.73 | 13-SEP-14:10 | 784.35 | 12-SEP-14:10 | 1021.34 | 13-SEP-14:10 | 0.00 | 01-SEP-00:10 |
October | 2627227.06 | 632440.35 | 1.67 | 2627227.06 | 0.00 | 0.00 | 0.13 | 07-OCT-15:00 | 0.00 | 01-OCT-00:05 | 723.87 | 07-OCT-15:00 | 723.87 | 07-OCT-15:00 | 0.00 | 07-OCT-14:50 | 172.46 | 07-OCT-15:00 | 0.00 | 01-OCT-00:05 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.464665E+10 | 0.103543E+10 | 659.94 | 0.415943E+10 | 0.487223E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.173488E+10 | 0.388104E+09 | 258.33 | 0.153743E+10 | 0.197455E+09 | 0.00 | 1.00 | 0.00 | 13525.15 | 12652.41 | 1645.70 | 2751.91 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.59 | 50.22 | 27.37 | 74.45 | 71.91 | 0.00 | 0.00 | 744.00 |
February | 94.79 | 57.84 | 36.94 | 89.74 | 69.65 | 0.00 | 0.00 | 672.00 |
March | 58.61 | 17.07 | 41.54 | 41.27 | 58.59 | 0.00 | 0.00 | 744.00 |
April | 121.70 | 55.01 | 66.69 | 110.99 | 49.22 | 0.00 | 0.00 | 720.00 |
May | 100.63 | 32.75 | 67.88 | 74.36 | 43.34 | 0.00 | 0.00 | 744.00 |
June | 92.70 | 22.43 | 70.27 | 67.97 | 35.62 | 0.00 | 0.00 | 720.00 |
July | 100.44 | 31.44 | 69.00 | 79.64 | 33.71 | 0.00 | 0.00 | 744.00 |
August | 117.71 | 52.95 | 64.76 | 108.94 | 36.93 | 0.00 | 0.00 | 744.00 |
September | 139.16 | 81.54 | 57.62 | 141.94 | 46.69 | 0.00 | 0.00 | 720.00 |
October | 95.60 | 55.88 | 39.72 | 95.51 | 56.62 | 0.00 | 0.00 | 744.00 |
November | 67.75 | 41.20 | 26.54 | 64.88 | 66.36 | 0.00 | 0.00 | 720.00 |
December | 53.69 | 34.39 | 19.30 | 50.32 | 81.39 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 93.22 | 44.22 | 49.00 | 83.14 | 54.09 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 53.69 | 17.07 | 19.30 | 41.27 | 33.71 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 139.16 | 81.54 | 70.27 | 141.94 | 81.39 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.59 | 50.22 | 27.37 | 74.45 | 71.91 | 0.00 | 0.00 | 744.00 |
February | 94.79 | 57.84 | 36.94 | 89.74 | 69.65 | 0.00 | 0.00 | 672.00 |
March | 58.61 | 17.07 | 41.54 | 41.27 | 58.59 | 0.00 | 0.00 | 744.00 |
April | 121.70 | 55.01 | 66.69 | 110.99 | 49.22 | 0.00 | 0.00 | 720.00 |
May | 100.63 | 32.75 | 67.88 | 74.36 | 43.34 | 0.00 | 0.00 | 744.00 |
June | 92.70 | 22.43 | 70.27 | 67.97 | 35.62 | 0.00 | 0.00 | 720.00 |
July | 100.44 | 31.44 | 69.00 | 79.64 | 33.71 | 0.00 | 0.00 | 744.00 |
August | 117.71 | 52.95 | 64.76 | 108.94 | 36.93 | 0.00 | 0.00 | 744.00 |
September | 139.16 | 81.54 | 57.62 | 141.94 | 46.69 | 0.00 | 0.00 | 720.00 |
October | 95.60 | 55.88 | 39.72 | 95.51 | 56.62 | 0.00 | 0.00 | 744.00 |
November | 67.75 | 41.20 | 26.54 | 64.88 | 66.36 | 0.00 | 0.00 | 720.00 |
December | 53.69 | 34.39 | 19.30 | 50.32 | 81.39 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 93.22 | 44.22 | 49.00 | 83.14 | 54.09 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 53.69 | 17.07 | 19.30 | 41.27 | 33.71 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 139.16 | 81.54 | 70.27 | 141.94 | 81.39 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_3
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.59 | 50.22 | 27.37 | 74.45 | 71.91 | 0.00 | 0.00 | 744.00 |
February | 94.79 | 57.84 | 36.94 | 89.74 | 69.65 | 0.00 | 0.00 | 672.00 |
March | 58.61 | 17.07 | 41.54 | 41.27 | 58.59 | 0.00 | 0.00 | 744.00 |
April | 121.70 | 55.01 | 66.69 | 110.99 | 49.22 | 0.00 | 0.00 | 720.00 |
May | 100.63 | 32.75 | 67.88 | 74.36 | 43.34 | 0.00 | 0.00 | 744.00 |
June | 92.70 | 22.43 | 70.27 | 67.97 | 35.62 | 0.00 | 0.00 | 720.00 |
July | 100.44 | 31.44 | 69.00 | 79.64 | 33.71 | 0.00 | 0.00 | 744.00 |
August | 117.71 | 52.95 | 64.76 | 108.94 | 36.93 | 0.00 | 0.00 | 744.00 |
September | 139.16 | 81.54 | 57.62 | 141.94 | 46.69 | 0.00 | 0.00 | 720.00 |
October | 95.60 | 55.88 | 39.72 | 95.51 | 56.62 | 0.00 | 0.00 | 744.00 |
November | 67.75 | 41.20 | 26.54 | 64.88 | 66.36 | 0.00 | 0.00 | 720.00 |
December | 53.69 | 34.39 | 19.30 | 50.32 | 81.39 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 93.22 | 44.22 | 49.00 | 83.14 | 54.09 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 53.69 | 17.07 | 19.30 | 41.27 | 33.71 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 139.16 | 81.54 | 70.27 | 141.94 | 81.39 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_4
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.59 | 50.22 | 27.37 | 74.45 | 71.91 | 0.00 | 0.00 | 744.00 |
February | 94.79 | 57.84 | 36.94 | 89.74 | 69.65 | 0.00 | 0.00 | 672.00 |
March | 58.61 | 17.07 | 41.54 | 41.27 | 58.59 | 0.00 | 0.00 | 744.00 |
April | 121.70 | 55.01 | 66.69 | 110.99 | 49.22 | 0.00 | 0.00 | 720.00 |
May | 100.63 | 32.75 | 67.88 | 74.36 | 43.34 | 0.00 | 0.00 | 744.00 |
June | 92.70 | 22.43 | 70.27 | 67.97 | 35.62 | 0.00 | 0.00 | 720.00 |
July | 100.44 | 31.44 | 69.00 | 79.64 | 33.71 | 0.00 | 0.00 | 744.00 |
August | 117.71 | 52.95 | 64.76 | 108.94 | 36.93 | 0.00 | 0.00 | 744.00 |
September | 139.16 | 81.54 | 57.62 | 141.94 | 46.69 | 0.00 | 0.00 | 720.00 |
October | 95.60 | 55.88 | 39.72 | 95.51 | 56.62 | 0.00 | 0.00 | 744.00 |
November | 67.75 | 41.20 | 26.54 | 64.88 | 66.36 | 0.00 | 0.00 | 720.00 |
December | 53.69 | 34.39 | 19.30 | 50.32 | 81.39 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 93.22 | 44.22 | 49.00 | 83.14 | 54.09 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 53.69 | 17.07 | 19.30 | 41.27 | 33.71 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 139.16 | 81.54 | 70.27 | 141.94 | 81.39 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_DOOR_1
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 93.41 | 60.46 | 32.95 | 89.67 | 85.98 | 0.00 | 0.00 | 744.00 |
February | 114.12 | 69.64 | 44.48 | 108.11 | 83.23 | 0.00 | 0.00 | 672.00 |
March | 70.57 | 20.56 | 50.01 | 49.79 | 70.06 | 0.00 | 0.00 | 744.00 |
April | 146.52 | 66.23 | 80.29 | 133.68 | 58.89 | 0.00 | 0.00 | 720.00 |
May | 121.16 | 39.43 | 81.72 | 89.65 | 51.79 | 0.00 | 0.00 | 744.00 |
June | 111.61 | 27.00 | 84.61 | 81.92 | 42.59 | 0.00 | 0.00 | 720.00 |
July | 120.93 | 37.86 | 83.07 | 95.93 | 40.32 | 0.00 | 0.00 | 744.00 |
August | 141.72 | 63.75 | 77.97 | 131.16 | 44.21 | 0.00 | 0.00 | 744.00 |
September | 167.54 | 98.17 | 69.37 | 170.85 | 55.88 | 0.00 | 0.00 | 720.00 |
October | 115.09 | 67.28 | 47.81 | 114.99 | 67.72 | 0.00 | 0.00 | 744.00 |
November | 81.56 | 49.61 | 31.95 | 78.15 | 79.33 | 0.00 | 0.00 | 720.00 |
December | 64.64 | 41.40 | 23.23 | 60.63 | 97.22 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 112.23 | 53.24 | 58.99 | 100.14 | 64.68 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 64.64 | 20.56 | 23.23 | 49.79 | 40.32 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 167.54 | 98.17 | 84.61 | 170.85 | 97.22 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_DOOR_2
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 93.41 | 60.46 | 32.95 | 89.67 | 85.98 | 0.00 | 0.00 | 744.00 |
February | 114.12 | 69.64 | 44.48 | 108.11 | 83.23 | 0.00 | 0.00 | 672.00 |
March | 70.57 | 20.56 | 50.01 | 49.79 | 70.06 | 0.00 | 0.00 | 744.00 |
April | 146.52 | 66.23 | 80.29 | 133.68 | 58.89 | 0.00 | 0.00 | 720.00 |
May | 121.16 | 39.43 | 81.72 | 89.65 | 51.79 | 0.00 | 0.00 | 744.00 |
June | 111.61 | 27.00 | 84.61 | 81.92 | 42.59 | 0.00 | 0.00 | 720.00 |
July | 120.93 | 37.86 | 83.07 | 95.93 | 40.32 | 0.00 | 0.00 | 744.00 |
August | 141.72 | 63.75 | 77.97 | 131.16 | 44.21 | 0.00 | 0.00 | 744.00 |
September | 167.54 | 98.17 | 69.37 | 170.85 | 55.88 | 0.00 | 0.00 | 720.00 |
October | 115.09 | 67.28 | 47.81 | 114.99 | 67.72 | 0.00 | 0.00 | 744.00 |
November | 81.56 | 49.61 | 31.95 | 78.15 | 79.33 | 0.00 | 0.00 | 720.00 |
December | 64.64 | 41.40 | 23.23 | 60.63 | 97.22 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 112.23 | 53.24 | 58.99 | 100.14 | 64.68 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 64.64 | 20.56 | 23.23 | 49.79 | 40.32 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 167.54 | 98.17 | 84.61 | 170.85 | 97.22 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.59 | 50.22 | 27.37 | 73.86 | 75.33 | 0.00 | 0.00 | 744.00 |
February | 94.79 | 57.84 | 36.94 | 89.07 | 73.20 | 0.00 | 0.00 | 672.00 |
March | 58.61 | 17.07 | 41.54 | 40.54 | 61.93 | 0.00 | 0.00 | 744.00 |
April | 121.70 | 55.01 | 66.69 | 109.27 | 53.12 | 0.00 | 0.00 | 720.00 |
May | 100.63 | 32.75 | 67.88 | 72.55 | 47.08 | 0.00 | 0.00 | 744.00 |
June | 92.70 | 22.43 | 70.27 | 66.61 | 37.51 | 0.00 | 0.00 | 720.00 |
July | 100.44 | 31.44 | 69.00 | 78.95 | 34.82 | 0.00 | 0.00 | 744.00 |
August | 117.71 | 52.95 | 64.76 | 108.56 | 37.73 | 0.00 | 0.00 | 744.00 |
September | 139.16 | 81.54 | 57.62 | 141.28 | 48.14 | 0.00 | 0.00 | 720.00 |
October | 95.60 | 55.88 | 39.72 | 94.28 | 60.93 | 0.00 | 0.00 | 744.00 |
November | 67.75 | 41.20 | 26.54 | 64.33 | 70.06 | 0.00 | 0.00 | 720.00 |
December | 53.69 | 34.39 | 19.30 | 49.95 | 85.19 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 93.22 | 44.22 | 49.00 | 82.24 | 57.01 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 53.69 | 17.07 | 19.30 | 40.54 | 34.82 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 139.16 | 81.54 | 70.27 | 141.28 | 85.19 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.59 | 50.22 | 27.37 | 73.86 | 75.33 | 0.00 | 0.00 | 744.00 |
February | 94.79 | 57.84 | 36.94 | 89.07 | 73.20 | 0.00 | 0.00 | 672.00 |
March | 58.61 | 17.07 | 41.54 | 40.54 | 61.93 | 0.00 | 0.00 | 744.00 |
April | 121.70 | 55.01 | 66.69 | 109.27 | 53.12 | 0.00 | 0.00 | 720.00 |
May | 100.63 | 32.75 | 67.88 | 72.55 | 47.08 | 0.00 | 0.00 | 744.00 |
June | 92.70 | 22.43 | 70.27 | 66.61 | 37.51 | 0.00 | 0.00 | 720.00 |
July | 100.44 | 31.44 | 69.00 | 78.95 | 34.82 | 0.00 | 0.00 | 744.00 |
August | 117.71 | 52.95 | 64.76 | 108.56 | 37.73 | 0.00 | 0.00 | 744.00 |
September | 139.16 | 81.54 | 57.62 | 141.28 | 48.14 | 0.00 | 0.00 | 720.00 |
October | 95.60 | 55.88 | 39.72 | 94.28 | 60.93 | 0.00 | 0.00 | 744.00 |
November | 67.75 | 41.20 | 26.54 | 64.33 | 70.06 | 0.00 | 0.00 | 720.00 |
December | 53.69 | 34.39 | 19.30 | 49.95 | 85.19 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 93.22 | 44.22 | 49.00 | 82.24 | 57.01 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 53.69 | 17.07 | 19.30 | 40.54 | 34.82 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 139.16 | 81.54 | 70.27 | 141.28 | 85.19 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_DOOR
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 93.41 | 60.46 | 32.95 | 88.97 | 90.06 | 0.00 | 0.00 | 744.00 |
February | 114.12 | 69.64 | 44.48 | 107.30 | 87.43 | 0.00 | 0.00 | 672.00 |
March | 70.57 | 20.56 | 50.01 | 48.91 | 74.03 | 0.00 | 0.00 | 744.00 |
April | 146.52 | 66.23 | 80.29 | 131.62 | 63.52 | 0.00 | 0.00 | 720.00 |
May | 121.16 | 39.43 | 81.72 | 87.48 | 56.21 | 0.00 | 0.00 | 744.00 |
June | 111.61 | 27.00 | 84.61 | 80.30 | 44.82 | 0.00 | 0.00 | 720.00 |
July | 120.93 | 37.86 | 83.07 | 95.10 | 41.63 | 0.00 | 0.00 | 744.00 |
August | 141.72 | 63.75 | 77.97 | 130.69 | 45.16 | 0.00 | 0.00 | 744.00 |
September | 167.54 | 98.17 | 69.37 | 170.06 | 57.59 | 0.00 | 0.00 | 720.00 |
October | 115.09 | 67.28 | 47.81 | 113.52 | 72.84 | 0.00 | 0.00 | 744.00 |
November | 81.56 | 49.61 | 31.95 | 77.48 | 83.71 | 0.00 | 0.00 | 720.00 |
December | 64.64 | 41.40 | 23.23 | 60.17 | 101.74 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 112.23 | 53.24 | 58.99 | 99.06 | 68.13 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 64.64 | 20.56 | 23.23 | 48.91 | 41.63 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 167.54 | 98.17 | 84.61 | 170.06 | 101.74 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.59 | 50.22 | 27.37 | 73.95 | 73.45 | 0.00 | 0.00 | 744.00 |
February | 94.79 | 57.84 | 36.94 | 89.14 | 71.39 | 0.00 | 0.00 | 672.00 |
March | 58.61 | 17.07 | 41.54 | 40.65 | 60.31 | 0.00 | 0.00 | 744.00 |
April | 121.70 | 55.01 | 66.69 | 109.35 | 52.20 | 0.00 | 0.00 | 720.00 |
May | 100.63 | 32.75 | 67.88 | 72.60 | 46.37 | 0.00 | 0.00 | 744.00 |
June | 92.70 | 22.43 | 70.27 | 66.39 | 38.02 | 0.00 | 0.00 | 720.00 |
July | 100.44 | 31.44 | 69.00 | 78.71 | 35.59 | 0.00 | 0.00 | 744.00 |
August | 117.71 | 52.95 | 64.76 | 108.42 | 38.65 | 0.00 | 0.00 | 744.00 |
September | 139.16 | 81.54 | 57.62 | 141.13 | 48.83 | 0.00 | 0.00 | 720.00 |
October | 95.60 | 55.88 | 39.72 | 94.34 | 59.85 | 0.00 | 0.00 | 744.00 |
November | 67.75 | 41.20 | 26.54 | 64.45 | 68.04 | 0.00 | 0.00 | 720.00 |
December | 53.69 | 34.39 | 19.30 | 49.98 | 83.17 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 93.22 | 44.22 | 49.00 | 82.23 | 56.25 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 53.69 | 17.07 | 19.30 | 40.65 | 35.59 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 139.16 | 81.54 | 70.27 | 141.13 | 83.17 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.59 | 50.22 | 27.37 | 73.95 | 73.45 | 0.00 | 0.00 | 744.00 |
February | 94.79 | 57.84 | 36.94 | 89.14 | 71.39 | 0.00 | 0.00 | 672.00 |
March | 58.61 | 17.07 | 41.54 | 40.65 | 60.31 | 0.00 | 0.00 | 744.00 |
April | 121.70 | 55.01 | 66.69 | 109.35 | 52.20 | 0.00 | 0.00 | 720.00 |
May | 100.63 | 32.75 | 67.88 | 72.60 | 46.37 | 0.00 | 0.00 | 744.00 |
June | 92.70 | 22.43 | 70.27 | 66.39 | 38.02 | 0.00 | 0.00 | 720.00 |
July | 100.44 | 31.44 | 69.00 | 78.71 | 35.59 | 0.00 | 0.00 | 744.00 |
August | 117.71 | 52.95 | 64.76 | 108.42 | 38.65 | 0.00 | 0.00 | 744.00 |
September | 139.16 | 81.54 | 57.62 | 141.13 | 48.83 | 0.00 | 0.00 | 720.00 |
October | 95.60 | 55.88 | 39.72 | 94.34 | 59.85 | 0.00 | 0.00 | 744.00 |
November | 67.75 | 41.20 | 26.54 | 64.45 | 68.04 | 0.00 | 0.00 | 720.00 |
December | 53.69 | 34.39 | 19.30 | 49.98 | 83.17 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 93.22 | 44.22 | 49.00 | 82.23 | 56.25 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 53.69 | 17.07 | 19.30 | 40.65 | 35.59 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 139.16 | 81.54 | 70.27 | 141.13 | 83.17 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_DOOR
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 92.90 | 60.13 | 32.77 | 88.60 | 87.32 | 0.00 | 0.00 | 744.00 |
February | 113.49 | 69.26 | 44.24 | 106.79 | 84.81 | 0.00 | 0.00 | 672.00 |
March | 70.18 | 20.44 | 49.74 | 48.78 | 71.69 | 0.00 | 0.00 | 744.00 |
April | 145.72 | 65.87 | 79.85 | 131.00 | 62.07 | 0.00 | 0.00 | 720.00 |
May | 120.49 | 39.22 | 81.28 | 87.07 | 55.06 | 0.00 | 0.00 | 744.00 |
June | 111.00 | 26.86 | 84.15 | 79.60 | 45.17 | 0.00 | 0.00 | 720.00 |
July | 120.27 | 37.65 | 82.62 | 94.31 | 42.29 | 0.00 | 0.00 | 744.00 |
August | 140.94 | 63.40 | 77.54 | 129.81 | 45.97 | 0.00 | 0.00 | 744.00 |
September | 166.62 | 97.64 | 68.99 | 168.96 | 58.07 | 0.00 | 0.00 | 720.00 |
October | 114.46 | 66.91 | 47.55 | 112.97 | 71.15 | 0.00 | 0.00 | 744.00 |
November | 81.12 | 49.34 | 31.78 | 77.20 | 80.86 | 0.00 | 0.00 | 720.00 |
December | 64.28 | 41.18 | 23.11 | 59.89 | 98.78 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 111.62 | 52.95 | 58.67 | 98.51 | 66.85 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 64.28 | 20.44 | 23.11 | 48.78 | 42.29 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 166.62 | 97.64 | 84.15 | 168.96 | 98.78 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.59 | 50.22 | 27.37 | 74.09 | 72.55 | 0.00 | 0.00 | 744.00 |
February | 94.79 | 57.84 | 36.94 | 89.27 | 70.57 | 0.00 | 0.00 | 672.00 |
March | 58.61 | 17.07 | 41.54 | 40.79 | 59.53 | 0.00 | 0.00 | 744.00 |
April | 121.70 | 55.01 | 66.69 | 109.69 | 51.36 | 0.00 | 0.00 | 720.00 |
May | 100.63 | 32.75 | 67.88 | 72.95 | 45.60 | 0.00 | 0.00 | 744.00 |
June | 92.70 | 22.43 | 70.27 | 66.56 | 37.66 | 0.00 | 0.00 | 720.00 |
July | 100.44 | 31.44 | 69.00 | 78.80 | 35.36 | 0.00 | 0.00 | 744.00 |
August | 117.71 | 52.95 | 64.76 | 108.46 | 38.49 | 0.00 | 0.00 | 744.00 |
September | 139.16 | 81.54 | 57.62 | 141.20 | 48.55 | 0.00 | 0.00 | 720.00 |
October | 95.60 | 55.88 | 39.72 | 94.55 | 58.93 | 0.00 | 0.00 | 744.00 |
November | 67.75 | 41.20 | 26.54 | 64.57 | 67.13 | 0.00 | 0.00 | 720.00 |
December | 53.69 | 34.39 | 19.30 | 50.07 | 82.22 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 93.22 | 44.22 | 49.00 | 82.39 | 55.59 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 53.69 | 17.07 | 19.30 | 40.79 | 35.36 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 139.16 | 81.54 | 70.27 | 141.20 | 82.22 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.59 | 50.22 | 27.37 | 74.09 | 72.55 | 0.00 | 0.00 | 744.00 |
February | 94.79 | 57.84 | 36.94 | 89.27 | 70.57 | 0.00 | 0.00 | 672.00 |
March | 58.61 | 17.07 | 41.54 | 40.79 | 59.53 | 0.00 | 0.00 | 744.00 |
April | 121.70 | 55.01 | 66.69 | 109.69 | 51.36 | 0.00 | 0.00 | 720.00 |
May | 100.63 | 32.75 | 67.88 | 72.95 | 45.60 | 0.00 | 0.00 | 744.00 |
June | 92.70 | 22.43 | 70.27 | 66.56 | 37.66 | 0.00 | 0.00 | 720.00 |
July | 100.44 | 31.44 | 69.00 | 78.80 | 35.36 | 0.00 | 0.00 | 744.00 |
August | 117.71 | 52.95 | 64.76 | 108.46 | 38.49 | 0.00 | 0.00 | 744.00 |
September | 139.16 | 81.54 | 57.62 | 141.20 | 48.55 | 0.00 | 0.00 | 720.00 |
October | 95.60 | 55.88 | 39.72 | 94.55 | 58.93 | 0.00 | 0.00 | 744.00 |
November | 67.75 | 41.20 | 26.54 | 64.57 | 67.13 | 0.00 | 0.00 | 720.00 |
December | 53.69 | 34.39 | 19.30 | 50.07 | 82.22 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 93.22 | 44.22 | 49.00 | 82.39 | 55.59 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 53.69 | 17.07 | 19.30 | 40.79 | 35.36 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 139.16 | 81.54 | 70.27 | 141.20 | 82.22 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_DOOR
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 92.90 | 60.13 | 32.77 | 88.76 | 86.25 | 0.00 | 0.00 | 744.00 |
February | 113.49 | 69.26 | 44.24 | 106.96 | 83.83 | 0.00 | 0.00 | 672.00 |
March | 70.18 | 20.44 | 49.74 | 48.95 | 70.77 | 0.00 | 0.00 | 744.00 |
April | 145.72 | 65.87 | 79.85 | 131.41 | 61.06 | 0.00 | 0.00 | 720.00 |
May | 120.49 | 39.22 | 81.28 | 87.48 | 54.14 | 0.00 | 0.00 | 744.00 |
June | 111.00 | 26.86 | 84.15 | 79.80 | 44.74 | 0.00 | 0.00 | 720.00 |
July | 120.27 | 37.65 | 82.62 | 94.41 | 42.03 | 0.00 | 0.00 | 744.00 |
August | 140.94 | 63.40 | 77.54 | 129.86 | 45.78 | 0.00 | 0.00 | 744.00 |
September | 166.62 | 97.64 | 68.99 | 169.04 | 57.74 | 0.00 | 0.00 | 720.00 |
October | 114.46 | 66.91 | 47.55 | 113.22 | 70.06 | 0.00 | 0.00 | 744.00 |
November | 81.12 | 49.34 | 31.78 | 77.35 | 79.78 | 0.00 | 0.00 | 720.00 |
December | 64.28 | 41.18 | 23.11 | 60.00 | 97.65 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 111.62 | 52.95 | 58.67 | 98.70 | 66.07 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 64.28 | 20.44 | 23.11 | 48.95 | 42.03 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 166.62 | 97.64 | 84.15 | 169.04 | 97.65 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.59 | 50.22 | 27.37 | 74.24 | 71.86 | 0.00 | 0.00 | 744.00 |
February | 94.79 | 57.84 | 36.94 | 89.42 | 69.94 | 0.00 | 0.00 | 672.00 |
March | 58.61 | 17.07 | 41.54 | 40.95 | 58.93 | 0.00 | 0.00 | 744.00 |
April | 121.70 | 55.01 | 66.69 | 110.20 | 50.44 | 0.00 | 0.00 | 720.00 |
May | 100.63 | 32.75 | 67.88 | 73.51 | 44.67 | 0.00 | 0.00 | 744.00 |
June | 92.70 | 22.43 | 70.27 | 67.06 | 36.94 | 0.00 | 0.00 | 720.00 |
July | 100.44 | 31.44 | 69.00 | 79.07 | 34.90 | 0.00 | 0.00 | 744.00 |
August | 117.71 | 52.95 | 64.76 | 108.59 | 38.17 | 0.00 | 0.00 | 744.00 |
September | 139.16 | 81.54 | 57.62 | 141.41 | 48.04 | 0.00 | 0.00 | 720.00 |
October | 95.60 | 55.88 | 39.72 | 94.89 | 57.88 | 0.00 | 0.00 | 744.00 |
November | 67.75 | 41.20 | 26.54 | 64.70 | 66.48 | 0.00 | 0.00 | 720.00 |
December | 53.69 | 34.39 | 19.30 | 50.18 | 81.43 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 93.22 | 44.22 | 49.00 | 82.65 | 54.90 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 53.69 | 17.07 | 19.30 | 40.95 | 34.90 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 139.16 | 81.54 | 70.27 | 141.41 | 81.43 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.59 | 50.22 | 27.37 | 74.24 | 71.86 | 0.00 | 0.00 | 744.00 |
February | 94.79 | 57.84 | 36.94 | 89.42 | 69.94 | 0.00 | 0.00 | 672.00 |
March | 58.61 | 17.07 | 41.54 | 40.95 | 58.93 | 0.00 | 0.00 | 744.00 |
April | 121.70 | 55.01 | 66.69 | 110.20 | 50.44 | 0.00 | 0.00 | 720.00 |
May | 100.63 | 32.75 | 67.88 | 73.51 | 44.67 | 0.00 | 0.00 | 744.00 |
June | 92.70 | 22.43 | 70.27 | 67.06 | 36.94 | 0.00 | 0.00 | 720.00 |
July | 100.44 | 31.44 | 69.00 | 79.07 | 34.90 | 0.00 | 0.00 | 744.00 |
August | 117.71 | 52.95 | 64.76 | 108.59 | 38.17 | 0.00 | 0.00 | 744.00 |
September | 139.16 | 81.54 | 57.62 | 141.41 | 48.04 | 0.00 | 0.00 | 720.00 |
October | 95.60 | 55.88 | 39.72 | 94.89 | 57.88 | 0.00 | 0.00 | 744.00 |
November | 67.75 | 41.20 | 26.54 | 64.70 | 66.48 | 0.00 | 0.00 | 720.00 |
December | 53.69 | 34.39 | 19.30 | 50.18 | 81.43 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 93.22 | 44.22 | 49.00 | 82.65 | 54.90 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 53.69 | 17.07 | 19.30 | 40.95 | 34.90 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 139.16 | 81.54 | 70.27 | 141.41 | 81.43 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_DOOR
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 92.90 | 60.13 | 32.77 | 88.94 | 85.43 | 0.00 | 0.00 | 744.00 |
February | 113.49 | 69.26 | 44.24 | 107.14 | 83.08 | 0.00 | 0.00 | 672.00 |
March | 70.18 | 20.44 | 49.74 | 49.15 | 70.05 | 0.00 | 0.00 | 744.00 |
April | 145.72 | 65.87 | 79.85 | 132.01 | 59.97 | 0.00 | 0.00 | 720.00 |
May | 120.49 | 39.22 | 81.28 | 88.15 | 53.05 | 0.00 | 0.00 | 744.00 |
June | 111.00 | 26.86 | 84.15 | 80.40 | 43.89 | 0.00 | 0.00 | 720.00 |
July | 120.27 | 37.65 | 82.62 | 94.74 | 41.48 | 0.00 | 0.00 | 744.00 |
August | 140.94 | 63.40 | 77.54 | 130.02 | 45.40 | 0.00 | 0.00 | 744.00 |
September | 166.62 | 97.64 | 68.99 | 169.29 | 57.13 | 0.00 | 0.00 | 720.00 |
October | 114.46 | 66.91 | 47.55 | 113.63 | 68.81 | 0.00 | 0.00 | 744.00 |
November | 81.12 | 49.34 | 31.78 | 77.50 | 79.00 | 0.00 | 0.00 | 720.00 |
December | 64.28 | 41.18 | 23.11 | 60.14 | 96.71 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 111.62 | 52.95 | 58.67 | 99.02 | 65.25 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 64.28 | 20.44 | 23.11 | 49.15 | 41.48 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 166.62 | 97.64 | 84.15 | 169.29 | 96.71 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.59 | 50.22 | 27.37 | 74.76 | 70.20 | 0.00 | 0.00 | 744.00 |
February | 94.79 | 57.84 | 36.94 | 90.00 | 68.33 | 0.00 | 0.00 | 672.00 |
March | 58.61 | 17.07 | 41.54 | 41.49 | 57.49 | 0.00 | 0.00 | 744.00 |
April | 121.70 | 55.01 | 66.69 | 111.31 | 48.59 | 0.00 | 0.00 | 720.00 |
May | 100.63 | 32.75 | 67.88 | 74.75 | 42.76 | 0.00 | 0.00 | 744.00 |
June | 92.70 | 22.43 | 70.27 | 68.52 | 35.08 | 0.00 | 0.00 | 720.00 |
July | 100.44 | 31.44 | 69.00 | 79.81 | 33.69 | 0.00 | 0.00 | 744.00 |
August | 117.71 | 52.95 | 64.76 | 108.87 | 37.27 | 0.00 | 0.00 | 744.00 |
September | 139.16 | 81.54 | 57.62 | 142.12 | 46.57 | 0.00 | 0.00 | 720.00 |
October | 95.60 | 55.88 | 39.72 | 95.84 | 55.62 | 0.00 | 0.00 | 744.00 |
November | 67.75 | 41.20 | 26.54 | 65.10 | 64.94 | 0.00 | 0.00 | 720.00 |
December | 53.69 | 34.39 | 19.30 | 50.60 | 79.27 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 93.22 | 44.22 | 49.00 | 83.40 | 53.24 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 53.69 | 17.07 | 19.30 | 41.49 | 33.69 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 139.16 | 81.54 | 70.27 | 142.12 | 79.27 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.59 | 50.22 | 27.37 | 74.76 | 70.20 | 0.00 | 0.00 | 744.00 |
February | 94.79 | 57.84 | 36.94 | 90.00 | 68.33 | 0.00 | 0.00 | 672.00 |
March | 58.61 | 17.07 | 41.54 | 41.49 | 57.49 | 0.00 | 0.00 | 744.00 |
April | 121.70 | 55.01 | 66.69 | 111.31 | 48.59 | 0.00 | 0.00 | 720.00 |
May | 100.63 | 32.75 | 67.88 | 74.75 | 42.76 | 0.00 | 0.00 | 744.00 |
June | 92.70 | 22.43 | 70.27 | 68.52 | 35.08 | 0.00 | 0.00 | 720.00 |
July | 100.44 | 31.44 | 69.00 | 79.81 | 33.69 | 0.00 | 0.00 | 744.00 |
August | 117.71 | 52.95 | 64.76 | 108.87 | 37.27 | 0.00 | 0.00 | 744.00 |
September | 139.16 | 81.54 | 57.62 | 142.12 | 46.57 | 0.00 | 0.00 | 720.00 |
October | 95.60 | 55.88 | 39.72 | 95.84 | 55.62 | 0.00 | 0.00 | 744.00 |
November | 67.75 | 41.20 | 26.54 | 65.10 | 64.94 | 0.00 | 0.00 | 720.00 |
December | 53.69 | 34.39 | 19.30 | 50.60 | 79.27 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 93.22 | 44.22 | 49.00 | 83.40 | 53.24 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 53.69 | 17.07 | 19.30 | 41.49 | 33.69 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 139.16 | 81.54 | 70.27 | 142.12 | 79.27 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_3
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.59 | 50.22 | 27.37 | 74.76 | 70.20 | 0.00 | 0.00 | 744.00 |
February | 94.79 | 57.84 | 36.94 | 90.00 | 68.33 | 0.00 | 0.00 | 672.00 |
March | 58.61 | 17.07 | 41.54 | 41.49 | 57.49 | 0.00 | 0.00 | 744.00 |
April | 121.70 | 55.01 | 66.69 | 111.31 | 48.59 | 0.00 | 0.00 | 720.00 |
May | 100.63 | 32.75 | 67.88 | 74.75 | 42.76 | 0.00 | 0.00 | 744.00 |
June | 92.70 | 22.43 | 70.27 | 68.52 | 35.08 | 0.00 | 0.00 | 720.00 |
July | 100.44 | 31.44 | 69.00 | 79.81 | 33.69 | 0.00 | 0.00 | 744.00 |
August | 117.71 | 52.95 | 64.76 | 108.87 | 37.27 | 0.00 | 0.00 | 744.00 |
September | 139.16 | 81.54 | 57.62 | 142.12 | 46.57 | 0.00 | 0.00 | 720.00 |
October | 95.60 | 55.88 | 39.72 | 95.84 | 55.62 | 0.00 | 0.00 | 744.00 |
November | 67.75 | 41.20 | 26.54 | 65.10 | 64.94 | 0.00 | 0.00 | 720.00 |
December | 53.69 | 34.39 | 19.30 | 50.60 | 79.27 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 93.22 | 44.22 | 49.00 | 83.40 | 53.24 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 53.69 | 17.07 | 19.30 | 41.49 | 33.69 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 139.16 | 81.54 | 70.27 | 142.12 | 79.27 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_4
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.59 | 50.22 | 27.37 | 74.76 | 70.20 | 0.00 | 0.00 | 744.00 |
February | 94.79 | 57.84 | 36.94 | 90.00 | 68.33 | 0.00 | 0.00 | 672.00 |
March | 58.61 | 17.07 | 41.54 | 41.49 | 57.49 | 0.00 | 0.00 | 744.00 |
April | 121.70 | 55.01 | 66.69 | 111.31 | 48.59 | 0.00 | 0.00 | 720.00 |
May | 100.63 | 32.75 | 67.88 | 74.75 | 42.76 | 0.00 | 0.00 | 744.00 |
June | 92.70 | 22.43 | 70.27 | 68.52 | 35.08 | 0.00 | 0.00 | 720.00 |
July | 100.44 | 31.44 | 69.00 | 79.81 | 33.69 | 0.00 | 0.00 | 744.00 |
August | 117.71 | 52.95 | 64.76 | 108.87 | 37.27 | 0.00 | 0.00 | 744.00 |
September | 139.16 | 81.54 | 57.62 | 142.12 | 46.57 | 0.00 | 0.00 | 720.00 |
October | 95.60 | 55.88 | 39.72 | 95.84 | 55.62 | 0.00 | 0.00 | 744.00 |
November | 67.75 | 41.20 | 26.54 | 65.10 | 64.94 | 0.00 | 0.00 | 720.00 |
December | 53.69 | 34.39 | 19.30 | 50.60 | 79.27 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 93.22 | 44.22 | 49.00 | 83.40 | 53.24 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 53.69 | 17.07 | 19.30 | 41.49 | 33.69 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 139.16 | 81.54 | 70.27 | 142.12 | 79.27 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_DOOR_1
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 92.90 | 60.13 | 32.77 | 89.57 | 83.46 | 0.00 | 0.00 | 744.00 |
February | 113.49 | 69.26 | 44.24 | 107.83 | 81.17 | 0.00 | 0.00 | 672.00 |
March | 70.18 | 20.44 | 49.74 | 49.80 | 68.35 | 0.00 | 0.00 | 744.00 |
April | 145.72 | 65.87 | 79.85 | 133.34 | 57.79 | 0.00 | 0.00 | 720.00 |
May | 120.49 | 39.22 | 81.28 | 89.63 | 50.80 | 0.00 | 0.00 | 744.00 |
June | 111.00 | 26.86 | 84.15 | 82.14 | 41.69 | 0.00 | 0.00 | 720.00 |
July | 120.27 | 37.65 | 82.62 | 95.62 | 40.05 | 0.00 | 0.00 | 744.00 |
August | 140.94 | 63.40 | 77.54 | 130.36 | 44.34 | 0.00 | 0.00 | 744.00 |
September | 166.62 | 97.64 | 68.99 | 170.14 | 55.40 | 0.00 | 0.00 | 720.00 |
October | 114.46 | 66.91 | 47.55 | 114.76 | 66.13 | 0.00 | 0.00 | 744.00 |
November | 81.12 | 49.34 | 31.78 | 77.99 | 77.17 | 0.00 | 0.00 | 720.00 |
December | 64.28 | 41.18 | 23.11 | 60.64 | 94.14 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 111.62 | 52.95 | 58.67 | 99.92 | 63.28 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 64.28 | 20.44 | 23.11 | 49.80 | 40.05 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 166.62 | 97.64 | 84.15 | 170.14 | 94.14 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_DOOR_2
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 92.90 | 60.13 | 32.77 | 89.57 | 83.46 | 0.00 | 0.00 | 744.00 |
February | 113.49 | 69.26 | 44.24 | 107.83 | 81.17 | 0.00 | 0.00 | 672.00 |
March | 70.18 | 20.44 | 49.74 | 49.80 | 68.35 | 0.00 | 0.00 | 744.00 |
April | 145.72 | 65.87 | 79.85 | 133.34 | 57.79 | 0.00 | 0.00 | 720.00 |
May | 120.49 | 39.22 | 81.28 | 89.63 | 50.80 | 0.00 | 0.00 | 744.00 |
June | 111.00 | 26.86 | 84.15 | 82.14 | 41.69 | 0.00 | 0.00 | 720.00 |
July | 120.27 | 37.65 | 82.62 | 95.62 | 40.05 | 0.00 | 0.00 | 744.00 |
August | 140.94 | 63.40 | 77.54 | 130.36 | 44.34 | 0.00 | 0.00 | 744.00 |
September | 166.62 | 97.64 | 68.99 | 170.14 | 55.40 | 0.00 | 0.00 | 720.00 |
October | 114.46 | 66.91 | 47.55 | 114.76 | 66.13 | 0.00 | 0.00 | 744.00 |
November | 81.12 | 49.34 | 31.78 | 77.99 | 77.17 | 0.00 | 0.00 | 720.00 |
December | 64.28 | 41.18 | 23.11 | 60.64 | 94.14 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 111.62 | 52.95 | 58.67 | 99.92 | 63.28 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 64.28 | 20.44 | 23.11 | 49.80 | 40.05 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 166.62 | 97.64 | 84.15 | 170.14 | 94.14 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.59 | 50.22 | 27.37 | 74.75 | 70.06 | 0.00 | 0.00 | 744.00 |
February | 94.79 | 57.84 | 36.94 | 90.00 | 68.21 | 0.00 | 0.00 | 672.00 |
March | 58.61 | 17.07 | 41.54 | 41.51 | 57.25 | 0.00 | 0.00 | 744.00 |
April | 121.70 | 55.01 | 66.69 | 111.38 | 48.43 | 0.00 | 0.00 | 720.00 |
May | 100.63 | 32.75 | 67.88 | 74.81 | 42.70 | 0.00 | 0.00 | 744.00 |
June | 92.70 | 22.43 | 70.27 | 68.53 | 35.09 | 0.00 | 0.00 | 720.00 |
July | 100.44 | 31.44 | 69.00 | 79.92 | 33.58 | 0.00 | 0.00 | 744.00 |
August | 117.71 | 52.95 | 64.76 | 108.99 | 37.11 | 0.00 | 0.00 | 744.00 |
September | 139.16 | 81.54 | 57.62 | 142.10 | 46.59 | 0.00 | 0.00 | 720.00 |
October | 95.60 | 55.88 | 39.72 | 95.82 | 55.47 | 0.00 | 0.00 | 744.00 |
November | 67.75 | 41.20 | 26.54 | 65.14 | 64.75 | 0.00 | 0.00 | 720.00 |
December | 53.69 | 34.39 | 19.30 | 50.59 | 79.32 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 93.22 | 44.22 | 49.00 | 83.43 | 53.14 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 53.69 | 17.07 | 19.30 | 41.51 | 33.58 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 139.16 | 81.54 | 70.27 | 142.10 | 79.32 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.59 | 50.22 | 27.37 | 74.75 | 70.06 | 0.00 | 0.00 | 744.00 |
February | 94.79 | 57.84 | 36.94 | 90.00 | 68.21 | 0.00 | 0.00 | 672.00 |
March | 58.61 | 17.07 | 41.54 | 41.51 | 57.25 | 0.00 | 0.00 | 744.00 |
April | 121.70 | 55.01 | 66.69 | 111.38 | 48.43 | 0.00 | 0.00 | 720.00 |
May | 100.63 | 32.75 | 67.88 | 74.81 | 42.70 | 0.00 | 0.00 | 744.00 |
June | 92.70 | 22.43 | 70.27 | 68.53 | 35.09 | 0.00 | 0.00 | 720.00 |
July | 100.44 | 31.44 | 69.00 | 79.92 | 33.58 | 0.00 | 0.00 | 744.00 |
August | 117.71 | 52.95 | 64.76 | 108.99 | 37.11 | 0.00 | 0.00 | 744.00 |
September | 139.16 | 81.54 | 57.62 | 142.10 | 46.59 | 0.00 | 0.00 | 720.00 |
October | 95.60 | 55.88 | 39.72 | 95.82 | 55.47 | 0.00 | 0.00 | 744.00 |
November | 67.75 | 41.20 | 26.54 | 65.14 | 64.75 | 0.00 | 0.00 | 720.00 |
December | 53.69 | 34.39 | 19.30 | 50.59 | 79.32 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 93.22 | 44.22 | 49.00 | 83.43 | 53.14 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 53.69 | 17.07 | 19.30 | 41.51 | 33.58 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 139.16 | 81.54 | 70.27 | 142.10 | 79.32 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_DOOR
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 92.90 | 60.13 | 32.77 | 89.56 | 83.28 | 0.00 | 0.00 | 744.00 |
February | 113.49 | 69.26 | 44.24 | 107.85 | 81.02 | 0.00 | 0.00 | 672.00 |
March | 70.18 | 20.44 | 49.74 | 49.83 | 68.05 | 0.00 | 0.00 | 744.00 |
April | 145.72 | 65.87 | 79.85 | 133.44 | 57.58 | 0.00 | 0.00 | 720.00 |
May | 120.49 | 39.22 | 81.28 | 89.72 | 50.71 | 0.00 | 0.00 | 744.00 |
June | 111.00 | 26.86 | 84.15 | 82.16 | 41.70 | 0.00 | 0.00 | 720.00 |
July | 120.27 | 37.65 | 82.62 | 95.77 | 39.91 | 0.00 | 0.00 | 744.00 |
August | 140.94 | 63.40 | 77.54 | 130.51 | 44.14 | 0.00 | 0.00 | 744.00 |
September | 166.62 | 97.64 | 68.99 | 170.13 | 55.41 | 0.00 | 0.00 | 720.00 |
October | 114.46 | 66.91 | 47.55 | 114.74 | 65.94 | 0.00 | 0.00 | 744.00 |
November | 81.12 | 49.34 | 31.78 | 78.03 | 76.94 | 0.00 | 0.00 | 720.00 |
December | 64.28 | 41.18 | 23.11 | 60.63 | 94.19 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 111.62 | 52.95 | 58.67 | 99.96 | 63.15 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 64.28 | 20.44 | 23.11 | 49.83 | 39.91 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 166.62 | 97.64 | 84.15 | 170.13 | 94.19 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.59 | 50.22 | 27.37 | 74.83 | 69.74 | 0.00 | 0.00 | 744.00 |
February | 94.79 | 57.84 | 36.94 | 90.09 | 67.89 | 0.00 | 0.00 | 672.00 |
March | 58.61 | 17.07 | 41.54 | 41.61 | 56.95 | 0.00 | 0.00 | 744.00 |
April | 121.70 | 55.01 | 66.69 | 111.56 | 48.13 | 0.00 | 0.00 | 720.00 |
May | 100.63 | 32.75 | 67.88 | 75.04 | 42.38 | 0.00 | 0.00 | 744.00 |
June | 92.70 | 22.43 | 70.27 | 68.82 | 34.76 | 0.00 | 0.00 | 720.00 |
July | 100.44 | 31.44 | 69.00 | 80.13 | 33.33 | 0.00 | 0.00 | 744.00 |
August | 117.71 | 52.95 | 64.76 | 109.11 | 36.92 | 0.00 | 0.00 | 744.00 |
September | 139.16 | 81.54 | 57.62 | 142.27 | 46.31 | 0.00 | 0.00 | 720.00 |
October | 95.60 | 55.88 | 39.72 | 95.97 | 55.08 | 0.00 | 0.00 | 744.00 |
November | 67.75 | 41.20 | 26.54 | 65.21 | 64.42 | 0.00 | 0.00 | 720.00 |
December | 53.69 | 34.39 | 19.30 | 50.64 | 79.00 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 93.22 | 44.22 | 49.00 | 83.58 | 52.84 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 53.69 | 17.07 | 19.30 | 41.61 | 33.33 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 139.16 | 81.54 | 70.27 | 142.27 | 79.00 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.59 | 50.22 | 27.37 | 74.83 | 69.74 | 0.00 | 0.00 | 744.00 |
February | 94.79 | 57.84 | 36.94 | 90.09 | 67.89 | 0.00 | 0.00 | 672.00 |
March | 58.61 | 17.07 | 41.54 | 41.61 | 56.95 | 0.00 | 0.00 | 744.00 |
April | 121.70 | 55.01 | 66.69 | 111.56 | 48.13 | 0.00 | 0.00 | 720.00 |
May | 100.63 | 32.75 | 67.88 | 75.04 | 42.38 | 0.00 | 0.00 | 744.00 |
June | 92.70 | 22.43 | 70.27 | 68.82 | 34.76 | 0.00 | 0.00 | 720.00 |
July | 100.44 | 31.44 | 69.00 | 80.13 | 33.33 | 0.00 | 0.00 | 744.00 |
August | 117.71 | 52.95 | 64.76 | 109.11 | 36.92 | 0.00 | 0.00 | 744.00 |
September | 139.16 | 81.54 | 57.62 | 142.27 | 46.31 | 0.00 | 0.00 | 720.00 |
October | 95.60 | 55.88 | 39.72 | 95.97 | 55.08 | 0.00 | 0.00 | 744.00 |
November | 67.75 | 41.20 | 26.54 | 65.21 | 64.42 | 0.00 | 0.00 | 720.00 |
December | 53.69 | 34.39 | 19.30 | 50.64 | 79.00 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 93.22 | 44.22 | 49.00 | 83.58 | 52.84 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 53.69 | 17.07 | 19.30 | 41.61 | 33.33 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 139.16 | 81.54 | 70.27 | 142.27 | 79.00 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_DOOR
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 92.90 | 60.13 | 32.77 | 89.66 | 82.89 | 0.00 | 0.00 | 744.00 |
February | 113.49 | 69.26 | 44.24 | 107.96 | 80.63 | 0.00 | 0.00 | 672.00 |
March | 70.18 | 20.44 | 49.74 | 49.94 | 67.69 | 0.00 | 0.00 | 744.00 |
April | 145.72 | 65.87 | 79.85 | 133.65 | 57.22 | 0.00 | 0.00 | 720.00 |
May | 120.49 | 39.22 | 81.28 | 89.99 | 50.33 | 0.00 | 0.00 | 744.00 |
June | 111.00 | 26.86 | 84.15 | 82.51 | 41.30 | 0.00 | 0.00 | 720.00 |
July | 120.27 | 37.65 | 82.62 | 96.01 | 39.62 | 0.00 | 0.00 | 744.00 |
August | 140.94 | 63.40 | 77.54 | 130.65 | 43.92 | 0.00 | 0.00 | 744.00 |
September | 166.62 | 97.64 | 68.99 | 170.33 | 55.08 | 0.00 | 0.00 | 720.00 |
October | 114.46 | 66.91 | 47.55 | 114.92 | 65.48 | 0.00 | 0.00 | 744.00 |
November | 81.12 | 49.34 | 31.78 | 78.12 | 76.55 | 0.00 | 0.00 | 720.00 |
December | 64.28 | 41.18 | 23.11 | 60.69 | 93.80 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 111.62 | 52.95 | 58.67 | 100.13 | 62.79 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 64.28 | 20.44 | 23.11 | 49.94 | 39.62 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 166.62 | 97.64 | 84.15 | 170.33 | 93.80 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.59 | 50.22 | 27.37 | 75.02 | 68.78 | 0.00 | 0.00 | 744.00 |
February | 94.79 | 57.84 | 36.94 | 90.32 | 66.90 | 0.00 | 0.00 | 672.00 |
March | 58.61 | 17.07 | 41.54 | 41.83 | 56.05 | 0.00 | 0.00 | 744.00 |
April | 121.70 | 55.01 | 66.69 | 111.95 | 47.30 | 0.00 | 0.00 | 720.00 |
May | 100.63 | 32.75 | 67.88 | 75.57 | 41.47 | 0.00 | 0.00 | 744.00 |
June | 92.70 | 22.43 | 70.27 | 69.54 | 33.83 | 0.00 | 0.00 | 720.00 |
July | 100.44 | 31.44 | 69.00 | 80.62 | 32.66 | 0.00 | 0.00 | 744.00 |
August | 117.71 | 52.95 | 64.76 | 109.39 | 36.40 | 0.00 | 0.00 | 744.00 |
September | 139.16 | 81.54 | 57.62 | 142.70 | 45.48 | 0.00 | 0.00 | 720.00 |
October | 95.60 | 55.88 | 39.72 | 96.32 | 54.06 | 0.00 | 0.00 | 744.00 |
November | 67.75 | 41.20 | 26.54 | 65.37 | 63.53 | 0.00 | 0.00 | 720.00 |
December | 53.69 | 34.39 | 19.30 | 50.77 | 77.99 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 93.22 | 44.22 | 49.00 | 83.92 | 51.96 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 53.69 | 17.07 | 19.30 | 41.83 | 32.66 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 139.16 | 81.54 | 70.27 | 142.70 | 77.99 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.59 | 50.22 | 27.37 | 75.02 | 68.78 | 0.00 | 0.00 | 744.00 |
February | 94.79 | 57.84 | 36.94 | 90.32 | 66.90 | 0.00 | 0.00 | 672.00 |
March | 58.61 | 17.07 | 41.54 | 41.83 | 56.05 | 0.00 | 0.00 | 744.00 |
April | 121.70 | 55.01 | 66.69 | 111.95 | 47.30 | 0.00 | 0.00 | 720.00 |
May | 100.63 | 32.75 | 67.88 | 75.57 | 41.47 | 0.00 | 0.00 | 744.00 |
June | 92.70 | 22.43 | 70.27 | 69.54 | 33.83 | 0.00 | 0.00 | 720.00 |
July | 100.44 | 31.44 | 69.00 | 80.62 | 32.66 | 0.00 | 0.00 | 744.00 |
August | 117.71 | 52.95 | 64.76 | 109.39 | 36.40 | 0.00 | 0.00 | 744.00 |
September | 139.16 | 81.54 | 57.62 | 142.70 | 45.48 | 0.00 | 0.00 | 720.00 |
October | 95.60 | 55.88 | 39.72 | 96.32 | 54.06 | 0.00 | 0.00 | 744.00 |
November | 67.75 | 41.20 | 26.54 | 65.37 | 63.53 | 0.00 | 0.00 | 720.00 |
December | 53.69 | 34.39 | 19.30 | 50.77 | 77.99 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 93.22 | 44.22 | 49.00 | 83.92 | 51.96 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 53.69 | 17.07 | 19.30 | 41.83 | 32.66 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 139.16 | 81.54 | 70.27 | 142.70 | 77.99 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_DOOR
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 92.90 | 60.13 | 32.77 | 89.89 | 81.74 | 0.00 | 0.00 | 744.00 |
February | 113.49 | 69.26 | 44.24 | 108.23 | 79.45 | 0.00 | 0.00 | 672.00 |
March | 70.18 | 20.44 | 49.74 | 50.22 | 66.62 | 0.00 | 0.00 | 744.00 |
April | 145.72 | 65.87 | 79.85 | 134.12 | 56.24 | 0.00 | 0.00 | 720.00 |
May | 120.49 | 39.22 | 81.28 | 90.62 | 49.24 | 0.00 | 0.00 | 744.00 |
June | 111.00 | 26.86 | 84.15 | 83.37 | 40.20 | 0.00 | 0.00 | 720.00 |
July | 120.27 | 37.65 | 82.62 | 96.61 | 38.81 | 0.00 | 0.00 | 744.00 |
August | 140.94 | 63.40 | 77.54 | 131.00 | 43.30 | 0.00 | 0.00 | 744.00 |
September | 166.62 | 97.64 | 68.99 | 170.85 | 54.09 | 0.00 | 0.00 | 720.00 |
October | 114.46 | 66.91 | 47.55 | 115.35 | 64.26 | 0.00 | 0.00 | 744.00 |
November | 81.12 | 49.34 | 31.78 | 78.32 | 75.48 | 0.00 | 0.00 | 720.00 |
December | 64.28 | 41.18 | 23.11 | 60.85 | 92.59 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 111.62 | 52.95 | 58.67 | 100.55 | 61.75 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 64.28 | 20.44 | 23.11 | 50.22 | 38.81 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 166.62 | 97.64 | 84.15 | 170.85 | 92.59 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.59 | 50.22 | 27.37 | 75.68 | 65.39 | 0.00 | 0.00 | 744.00 |
February | 94.79 | 57.84 | 36.94 | 91.13 | 63.26 | 0.00 | 0.00 | 672.00 |
March | 58.61 | 17.07 | 41.54 | 42.63 | 52.83 | 0.00 | 0.00 | 744.00 |
April | 121.70 | 55.01 | 66.69 | 112.86 | 44.65 | 0.00 | 0.00 | 720.00 |
May | 100.63 | 32.75 | 67.88 | 76.81 | 38.56 | 0.00 | 0.00 | 744.00 |
June | 92.70 | 22.43 | 70.27 | 71.07 | 31.25 | 0.00 | 0.00 | 720.00 |
July | 100.44 | 31.44 | 69.00 | 81.74 | 30.54 | 0.00 | 0.00 | 744.00 |
August | 117.71 | 52.95 | 64.76 | 110.17 | 34.43 | 0.00 | 0.00 | 744.00 |
September | 139.16 | 81.54 | 57.62 | 143.65 | 42.96 | 0.00 | 0.00 | 720.00 |
October | 95.60 | 55.88 | 39.72 | 97.09 | 51.13 | 0.00 | 0.00 | 744.00 |
November | 67.75 | 41.20 | 26.54 | 65.90 | 60.41 | 0.00 | 0.00 | 720.00 |
December | 53.69 | 34.39 | 19.30 | 51.23 | 74.26 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 93.22 | 44.22 | 49.00 | 84.80 | 49.07 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 53.69 | 17.07 | 19.30 | 42.63 | 30.54 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 139.16 | 81.54 | 70.27 | 143.65 | 74.26 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.59 | 50.22 | 27.37 | 75.68 | 65.39 | 0.00 | 0.00 | 744.00 |
February | 94.79 | 57.84 | 36.94 | 91.13 | 63.26 | 0.00 | 0.00 | 672.00 |
March | 58.61 | 17.07 | 41.54 | 42.63 | 52.83 | 0.00 | 0.00 | 744.00 |
April | 121.70 | 55.01 | 66.69 | 112.86 | 44.65 | 0.00 | 0.00 | 720.00 |
May | 100.63 | 32.75 | 67.88 | 76.81 | 38.56 | 0.00 | 0.00 | 744.00 |
June | 92.70 | 22.43 | 70.27 | 71.07 | 31.25 | 0.00 | 0.00 | 720.00 |
July | 100.44 | 31.44 | 69.00 | 81.74 | 30.54 | 0.00 | 0.00 | 744.00 |
August | 117.71 | 52.95 | 64.76 | 110.17 | 34.43 | 0.00 | 0.00 | 744.00 |
September | 139.16 | 81.54 | 57.62 | 143.65 | 42.96 | 0.00 | 0.00 | 720.00 |
October | 95.60 | 55.88 | 39.72 | 97.09 | 51.13 | 0.00 | 0.00 | 744.00 |
November | 67.75 | 41.20 | 26.54 | 65.90 | 60.41 | 0.00 | 0.00 | 720.00 |
December | 53.69 | 34.39 | 19.30 | 51.23 | 74.26 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 93.22 | 44.22 | 49.00 | 84.80 | 49.07 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 53.69 | 17.07 | 19.30 | 42.63 | 30.54 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 139.16 | 81.54 | 70.27 | 143.65 | 74.26 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_DOOR
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 92.90 | 60.13 | 32.77 | 90.69 | 77.69 | 0.00 | 0.00 | 744.00 |
February | 113.49 | 69.26 | 44.24 | 109.22 | 75.12 | 0.00 | 0.00 | 672.00 |
March | 70.18 | 20.44 | 49.74 | 51.19 | 62.78 | 0.00 | 0.00 | 744.00 |
April | 145.72 | 65.87 | 79.85 | 135.22 | 53.09 | 0.00 | 0.00 | 720.00 |
May | 120.49 | 39.22 | 81.28 | 92.11 | 45.80 | 0.00 | 0.00 | 744.00 |
June | 111.00 | 26.86 | 84.15 | 85.20 | 37.14 | 0.00 | 0.00 | 720.00 |
July | 120.27 | 37.65 | 82.62 | 97.95 | 36.31 | 0.00 | 0.00 | 744.00 |
August | 140.94 | 63.40 | 77.54 | 131.93 | 40.97 | 0.00 | 0.00 | 744.00 |
September | 166.62 | 97.64 | 68.99 | 171.99 | 51.11 | 0.00 | 0.00 | 720.00 |
October | 114.46 | 66.91 | 47.55 | 116.27 | 60.78 | 0.00 | 0.00 | 744.00 |
November | 81.12 | 49.34 | 31.78 | 78.97 | 71.76 | 0.00 | 0.00 | 720.00 |
December | 64.28 | 41.18 | 23.11 | 61.41 | 88.16 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 111.62 | 52.95 | 58.67 | 101.61 | 58.31 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 64.28 | 20.44 | 23.11 | 51.19 | 36.31 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 166.62 | 97.64 | 84.15 | 171.99 | 88.16 | 0.00 | 0.00 | 744.00 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.207804E+09 | 0.134500E+09 | 73304068.41 | 0.199400E+09 | 0.192597E+09 |
February | 0.229307E+09 | 0.139931E+09 | 89376690.89 | 0.217106E+09 | 0.168507E+09 |
March | 0.156988E+09 | 45730722.64 | 0.111257E+09 | 0.110532E+09 | 0.156933E+09 |
April | 0.315448E+09 | 0.142596E+09 | 0.172852E+09 | 0.287687E+09 | 0.127587E+09 |
May | 0.269535E+09 | 87724495.05 | 0.181810E+09 | 0.199173E+09 | 0.116073E+09 |
June | 0.240291E+09 | 58138134.90 | 0.182153E+09 | 0.176167E+09 | 92336600.27 |
July | 0.269027E+09 | 84220443.19 | 0.184806E+09 | 0.213305E+09 | 90290783.12 |
August | 0.315280E+09 | 0.141820E+09 | 0.173460E+09 | 0.291798E+09 | 98908215.04 |
September | 0.360699E+09 | 0.211357E+09 | 0.149342E+09 | 0.367919E+09 | 0.121019E+09 |
October | 0.256042E+09 | 0.149669E+09 | 0.106373E+09 | 0.255826E+09 | 0.151638E+09 |
November | 0.175596E+09 | 0.106803E+09 | 68792821.08 | 0.168176E+09 | 0.172008E+09 |
December | 0.143797E+09 | 92112206.48 | 51684381.78 | 0.134787E+09 | 0.217987E+09 |
Annual Sum or Average | 0.293981E+10 | 0.139460E+10 | 0.154521E+10 | 0.262188E+10 | 0.170588E+10 |
Minimum of Months | 0.143797E+09 | 45730722.64 | 51684381.78 | 0.110532E+09 | 90290783.12 |
Maximum of Months | 0.360699E+09 | 0.211357E+09 | 0.184806E+09 | 0.367919E+09 | 0.217987E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.207804E+09 | 0.134500E+09 | 73304068.41 | 0.199400E+09 | 0.192597E+09 |
February | 0.229307E+09 | 0.139931E+09 | 89376690.89 | 0.217106E+09 | 0.168507E+09 |
March | 0.156988E+09 | 45730722.64 | 0.111257E+09 | 0.110532E+09 | 0.156933E+09 |
April | 0.315448E+09 | 0.142596E+09 | 0.172852E+09 | 0.287687E+09 | 0.127587E+09 |
May | 0.269535E+09 | 87724495.05 | 0.181810E+09 | 0.199173E+09 | 0.116073E+09 |
June | 0.240291E+09 | 58138134.90 | 0.182153E+09 | 0.176167E+09 | 92336600.27 |
July | 0.269027E+09 | 84220443.19 | 0.184806E+09 | 0.213305E+09 | 90290783.12 |
August | 0.315280E+09 | 0.141820E+09 | 0.173460E+09 | 0.291798E+09 | 98908215.04 |
September | 0.360699E+09 | 0.211357E+09 | 0.149342E+09 | 0.367919E+09 | 0.121019E+09 |
October | 0.256042E+09 | 0.149669E+09 | 0.106373E+09 | 0.255826E+09 | 0.151638E+09 |
November | 0.175596E+09 | 0.106803E+09 | 68792821.08 | 0.168176E+09 | 0.172008E+09 |
December | 0.143797E+09 | 92112206.48 | 51684381.78 | 0.134787E+09 | 0.217987E+09 |
Annual Sum or Average | 0.293981E+10 | 0.139460E+10 | 0.154521E+10 | 0.262188E+10 | 0.170588E+10 |
Minimum of Months | 0.143797E+09 | 45730722.64 | 51684381.78 | 0.110532E+09 | 90290783.12 |
Maximum of Months | 0.360699E+09 | 0.211357E+09 | 0.184806E+09 | 0.367919E+09 | 0.217987E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_3
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.207804E+09 | 0.134500E+09 | 73304068.41 | 0.199400E+09 | 0.192597E+09 |
February | 0.229307E+09 | 0.139931E+09 | 89376690.89 | 0.217106E+09 | 0.168507E+09 |
March | 0.156988E+09 | 45730722.64 | 0.111257E+09 | 0.110532E+09 | 0.156933E+09 |
April | 0.315448E+09 | 0.142596E+09 | 0.172852E+09 | 0.287687E+09 | 0.127587E+09 |
May | 0.269535E+09 | 87724495.05 | 0.181810E+09 | 0.199173E+09 | 0.116073E+09 |
June | 0.240291E+09 | 58138134.90 | 0.182153E+09 | 0.176167E+09 | 92336600.27 |
July | 0.269027E+09 | 84220443.19 | 0.184806E+09 | 0.213305E+09 | 90290783.12 |
August | 0.315280E+09 | 0.141820E+09 | 0.173460E+09 | 0.291798E+09 | 98908215.04 |
September | 0.360699E+09 | 0.211357E+09 | 0.149342E+09 | 0.367919E+09 | 0.121019E+09 |
October | 0.256042E+09 | 0.149669E+09 | 0.106373E+09 | 0.255826E+09 | 0.151638E+09 |
November | 0.175596E+09 | 0.106803E+09 | 68792821.08 | 0.168176E+09 | 0.172008E+09 |
December | 0.143797E+09 | 92112206.48 | 51684381.78 | 0.134787E+09 | 0.217987E+09 |
Annual Sum or Average | 0.293981E+10 | 0.139460E+10 | 0.154521E+10 | 0.262188E+10 | 0.170588E+10 |
Minimum of Months | 0.143797E+09 | 45730722.64 | 51684381.78 | 0.110532E+09 | 90290783.12 |
Maximum of Months | 0.360699E+09 | 0.211357E+09 | 0.184806E+09 | 0.367919E+09 | 0.217987E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_4
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.207804E+09 | 0.134500E+09 | 73304068.41 | 0.199400E+09 | 0.192597E+09 |
February | 0.229307E+09 | 0.139931E+09 | 89376690.89 | 0.217106E+09 | 0.168507E+09 |
March | 0.156988E+09 | 45730722.64 | 0.111257E+09 | 0.110532E+09 | 0.156933E+09 |
April | 0.315448E+09 | 0.142596E+09 | 0.172852E+09 | 0.287687E+09 | 0.127587E+09 |
May | 0.269535E+09 | 87724495.05 | 0.181810E+09 | 0.199173E+09 | 0.116073E+09 |
June | 0.240291E+09 | 58138134.90 | 0.182153E+09 | 0.176167E+09 | 92336600.27 |
July | 0.269027E+09 | 84220443.19 | 0.184806E+09 | 0.213305E+09 | 90290783.12 |
August | 0.315280E+09 | 0.141820E+09 | 0.173460E+09 | 0.291798E+09 | 98908215.04 |
September | 0.360699E+09 | 0.211357E+09 | 0.149342E+09 | 0.367919E+09 | 0.121019E+09 |
October | 0.256042E+09 | 0.149669E+09 | 0.106373E+09 | 0.255826E+09 | 0.151638E+09 |
November | 0.175596E+09 | 0.106803E+09 | 68792821.08 | 0.168176E+09 | 0.172008E+09 |
December | 0.143797E+09 | 92112206.48 | 51684381.78 | 0.134787E+09 | 0.217987E+09 |
Annual Sum or Average | 0.293981E+10 | 0.139460E+10 | 0.154521E+10 | 0.262188E+10 | 0.170588E+10 |
Minimum of Months | 0.143797E+09 | 45730722.64 | 51684381.78 | 0.110532E+09 | 90290783.12 |
Maximum of Months | 0.360699E+09 | 0.211357E+09 | 0.184806E+09 | 0.367919E+09 | 0.217987E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_DOOR_1
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.250185E+09 | 0.161931E+09 | 88254240.26 | 0.240184E+09 | 0.230292E+09 |
February | 0.276074E+09 | 0.168469E+09 | 0.107605E+09 | 0.261529E+09 | 0.201353E+09 |
March | 0.189005E+09 | 55057383.18 | 0.133948E+09 | 0.133354E+09 | 0.187648E+09 |
April | 0.379783E+09 | 0.171678E+09 | 0.208105E+09 | 0.346494E+09 | 0.152635E+09 |
May | 0.324506E+09 | 0.105616E+09 | 0.218890E+09 | 0.240120E+09 | 0.138704E+09 |
June | 0.289298E+09 | 69995254.52 | 0.219302E+09 | 0.212342E+09 | 0.110403E+09 |
July | 0.323894E+09 | 0.101397E+09 | 0.222497E+09 | 0.256947E+09 | 0.107999E+09 |
August | 0.379581E+09 | 0.170744E+09 | 0.208837E+09 | 0.351290E+09 | 0.118401E+09 |
September | 0.434262E+09 | 0.254462E+09 | 0.179800E+09 | 0.442855E+09 | 0.144828E+09 |
October | 0.308261E+09 | 0.180194E+09 | 0.128067E+09 | 0.307989E+09 | 0.181372E+09 |
November | 0.211408E+09 | 0.128585E+09 | 82822935.91 | 0.202553E+09 | 0.205631E+09 |
December | 0.173124E+09 | 0.110898E+09 | 62225275.44 | 0.162391E+09 | 0.260399E+09 |
Annual Sum or Average | 0.353938E+10 | 0.167903E+10 | 0.186035E+10 | 0.315805E+10 | 0.203967E+10 |
Minimum of Months | 0.173124E+09 | 55057383.18 | 62225275.44 | 0.133354E+09 | 0.107999E+09 |
Maximum of Months | 0.434262E+09 | 0.254462E+09 | 0.222497E+09 | 0.442855E+09 | 0.260399E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_DOOR_2
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.250185E+09 | 0.161931E+09 | 88254240.26 | 0.240184E+09 | 0.230292E+09 |
February | 0.276074E+09 | 0.168469E+09 | 0.107605E+09 | 0.261529E+09 | 0.201353E+09 |
March | 0.189005E+09 | 55057383.18 | 0.133948E+09 | 0.133354E+09 | 0.187648E+09 |
April | 0.379783E+09 | 0.171678E+09 | 0.208105E+09 | 0.346494E+09 | 0.152635E+09 |
May | 0.324506E+09 | 0.105616E+09 | 0.218890E+09 | 0.240120E+09 | 0.138704E+09 |
June | 0.289298E+09 | 69995254.52 | 0.219302E+09 | 0.212342E+09 | 0.110403E+09 |
July | 0.323894E+09 | 0.101397E+09 | 0.222497E+09 | 0.256947E+09 | 0.107999E+09 |
August | 0.379581E+09 | 0.170744E+09 | 0.208837E+09 | 0.351290E+09 | 0.118401E+09 |
September | 0.434262E+09 | 0.254462E+09 | 0.179800E+09 | 0.442855E+09 | 0.144828E+09 |
October | 0.308261E+09 | 0.180194E+09 | 0.128067E+09 | 0.307989E+09 | 0.181372E+09 |
November | 0.211408E+09 | 0.128585E+09 | 82822935.91 | 0.202553E+09 | 0.205631E+09 |
December | 0.173124E+09 | 0.110898E+09 | 62225275.44 | 0.162391E+09 | 0.260399E+09 |
Annual Sum or Average | 0.353938E+10 | 0.167903E+10 | 0.186035E+10 | 0.315805E+10 | 0.203967E+10 |
Minimum of Months | 0.173124E+09 | 55057383.18 | 62225275.44 | 0.133354E+09 | 0.107999E+09 |
Maximum of Months | 0.434262E+09 | 0.254462E+09 | 0.222497E+09 | 0.442855E+09 | 0.260399E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.207804E+09 | 0.134500E+09 | 73304068.41 | 0.197831E+09 | 0.201774E+09 |
February | 0.229307E+09 | 0.139931E+09 | 89376690.89 | 0.215489E+09 | 0.177074E+09 |
March | 0.156988E+09 | 45730722.64 | 0.111257E+09 | 0.108580E+09 | 0.165873E+09 |
April | 0.315448E+09 | 0.142596E+09 | 0.172852E+09 | 0.283226E+09 | 0.137695E+09 |
May | 0.269535E+09 | 87724495.05 | 0.181810E+09 | 0.194318E+09 | 0.126097E+09 |
June | 0.240291E+09 | 58138134.90 | 0.182153E+09 | 0.172662E+09 | 97217535.12 |
July | 0.269027E+09 | 84220443.19 | 0.184806E+09 | 0.211456E+09 | 93249304.61 |
August | 0.315280E+09 | 0.141820E+09 | 0.173460E+09 | 0.290754E+09 | 0.101058E+09 |
September | 0.360699E+09 | 0.211357E+09 | 0.149342E+09 | 0.366205E+09 | 0.124773E+09 |
October | 0.256042E+09 | 0.149669E+09 | 0.106373E+09 | 0.252528E+09 | 0.163201E+09 |
November | 0.175596E+09 | 0.106803E+09 | 68792821.08 | 0.166750E+09 | 0.181586E+09 |
December | 0.143797E+09 | 92112206.48 | 51684381.78 | 0.133777E+09 | 0.228177E+09 |
Annual Sum or Average | 0.293981E+10 | 0.139460E+10 | 0.154521E+10 | 0.259357E+10 | 0.179778E+10 |
Minimum of Months | 0.143797E+09 | 45730722.64 | 51684381.78 | 0.108580E+09 | 93249304.61 |
Maximum of Months | 0.360699E+09 | 0.211357E+09 | 0.184806E+09 | 0.366205E+09 | 0.228177E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.207804E+09 | 0.134500E+09 | 73304068.41 | 0.197831E+09 | 0.201774E+09 |
February | 0.229307E+09 | 0.139931E+09 | 89376690.89 | 0.215489E+09 | 0.177074E+09 |
March | 0.156988E+09 | 45730722.64 | 0.111257E+09 | 0.108580E+09 | 0.165873E+09 |
April | 0.315448E+09 | 0.142596E+09 | 0.172852E+09 | 0.283226E+09 | 0.137695E+09 |
May | 0.269535E+09 | 87724495.05 | 0.181810E+09 | 0.194318E+09 | 0.126097E+09 |
June | 0.240291E+09 | 58138134.90 | 0.182153E+09 | 0.172662E+09 | 97217535.12 |
July | 0.269027E+09 | 84220443.19 | 0.184806E+09 | 0.211456E+09 | 93249304.61 |
August | 0.315280E+09 | 0.141820E+09 | 0.173460E+09 | 0.290754E+09 | 0.101058E+09 |
September | 0.360699E+09 | 0.211357E+09 | 0.149342E+09 | 0.366205E+09 | 0.124773E+09 |
October | 0.256042E+09 | 0.149669E+09 | 0.106373E+09 | 0.252528E+09 | 0.163201E+09 |
November | 0.175596E+09 | 0.106803E+09 | 68792821.08 | 0.166750E+09 | 0.181586E+09 |
December | 0.143797E+09 | 92112206.48 | 51684381.78 | 0.133777E+09 | 0.228177E+09 |
Annual Sum or Average | 0.293981E+10 | 0.139460E+10 | 0.154521E+10 | 0.259357E+10 | 0.179778E+10 |
Minimum of Months | 0.143797E+09 | 45730722.64 | 51684381.78 | 0.108580E+09 | 93249304.61 |
Maximum of Months | 0.360699E+09 | 0.211357E+09 | 0.184806E+09 | 0.366205E+09 | 0.228177E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_DOOR
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.250185E+09 | 0.161931E+09 | 88254240.26 | 0.238287E+09 | 0.241206E+09 |
February | 0.276074E+09 | 0.168469E+09 | 0.107605E+09 | 0.259572E+09 | 0.211513E+09 |
March | 0.189005E+09 | 55057383.18 | 0.133948E+09 | 0.130991E+09 | 0.198274E+09 |
April | 0.379783E+09 | 0.171678E+09 | 0.208105E+09 | 0.341151E+09 | 0.164632E+09 |
May | 0.324506E+09 | 0.105616E+09 | 0.218890E+09 | 0.234301E+09 | 0.150562E+09 |
June | 0.289298E+09 | 69995254.52 | 0.219302E+09 | 0.208144E+09 | 0.116183E+09 |
July | 0.323894E+09 | 0.101397E+09 | 0.222497E+09 | 0.254727E+09 | 0.111496E+09 |
August | 0.379581E+09 | 0.170744E+09 | 0.208837E+09 | 0.350031E+09 | 0.120948E+09 |
September | 0.434262E+09 | 0.254462E+09 | 0.179800E+09 | 0.440804E+09 | 0.149280E+09 |
October | 0.308261E+09 | 0.180194E+09 | 0.128067E+09 | 0.304051E+09 | 0.195095E+09 |
November | 0.211408E+09 | 0.128585E+09 | 82822935.91 | 0.200836E+09 | 0.216982E+09 |
December | 0.173124E+09 | 0.110898E+09 | 62225275.44 | 0.161169E+09 | 0.272498E+09 |
Annual Sum or Average | 0.353938E+10 | 0.167903E+10 | 0.186035E+10 | 0.312406E+10 | 0.214867E+10 |
Minimum of Months | 0.173124E+09 | 55057383.18 | 62225275.44 | 0.130991E+09 | 0.111496E+09 |
Maximum of Months | 0.434262E+09 | 0.254462E+09 | 0.222497E+09 | 0.440804E+09 | 0.272498E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.207804E+09 | 0.134500E+09 | 73304068.41 | 0.198075E+09 | 0.196715E+09 |
February | 0.229307E+09 | 0.139931E+09 | 89376690.89 | 0.215638E+09 | 0.172701E+09 |
March | 0.156988E+09 | 45730722.64 | 0.111257E+09 | 0.108884E+09 | 0.161526E+09 |
April | 0.315448E+09 | 0.142596E+09 | 0.172852E+09 | 0.283442E+09 | 0.135302E+09 |
May | 0.269535E+09 | 87724495.05 | 0.181810E+09 | 0.194456E+09 | 0.124194E+09 |
June | 0.240291E+09 | 58138134.90 | 0.182153E+09 | 0.172076E+09 | 98557191.04 |
July | 0.269027E+09 | 84220443.19 | 0.184806E+09 | 0.210818E+09 | 95328185.35 |
August | 0.315280E+09 | 0.141820E+09 | 0.173460E+09 | 0.290385E+09 | 0.103512E+09 |
September | 0.360699E+09 | 0.211357E+09 | 0.149342E+09 | 0.365816E+09 | 0.126570E+09 |
October | 0.256042E+09 | 0.149669E+09 | 0.106373E+09 | 0.252679E+09 | 0.160297E+09 |
November | 0.175596E+09 | 0.106803E+09 | 68792821.08 | 0.167051E+09 | 0.176348E+09 |
December | 0.143797E+09 | 92112206.48 | 51684381.78 | 0.133855E+09 | 0.222757E+09 |
Annual Sum or Average | 0.293981E+10 | 0.139460E+10 | 0.154521E+10 | 0.259317E+10 | 0.177381E+10 |
Minimum of Months | 0.143797E+09 | 45730722.64 | 51684381.78 | 0.108884E+09 | 95328185.35 |
Maximum of Months | 0.360699E+09 | 0.211357E+09 | 0.184806E+09 | 0.365816E+09 | 0.222757E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.207804E+09 | 0.134500E+09 | 73304068.41 | 0.198075E+09 | 0.196715E+09 |
February | 0.229307E+09 | 0.139931E+09 | 89376690.89 | 0.215638E+09 | 0.172701E+09 |
March | 0.156988E+09 | 45730722.64 | 0.111257E+09 | 0.108884E+09 | 0.161526E+09 |
April | 0.315448E+09 | 0.142596E+09 | 0.172852E+09 | 0.283442E+09 | 0.135302E+09 |
May | 0.269535E+09 | 87724495.05 | 0.181810E+09 | 0.194456E+09 | 0.124194E+09 |
June | 0.240291E+09 | 58138134.90 | 0.182153E+09 | 0.172076E+09 | 98557191.04 |
July | 0.269027E+09 | 84220443.19 | 0.184806E+09 | 0.210818E+09 | 95328185.35 |
August | 0.315280E+09 | 0.141820E+09 | 0.173460E+09 | 0.290385E+09 | 0.103512E+09 |
September | 0.360699E+09 | 0.211357E+09 | 0.149342E+09 | 0.365816E+09 | 0.126570E+09 |
October | 0.256042E+09 | 0.149669E+09 | 0.106373E+09 | 0.252679E+09 | 0.160297E+09 |
November | 0.175596E+09 | 0.106803E+09 | 68792821.08 | 0.167051E+09 | 0.176348E+09 |
December | 0.143797E+09 | 92112206.48 | 51684381.78 | 0.133855E+09 | 0.222757E+09 |
Annual Sum or Average | 0.293981E+10 | 0.139460E+10 | 0.154521E+10 | 0.259317E+10 | 0.177381E+10 |
Minimum of Months | 0.143797E+09 | 45730722.64 | 51684381.78 | 0.108884E+09 | 95328185.35 |
Maximum of Months | 0.360699E+09 | 0.211357E+09 | 0.184806E+09 | 0.365816E+09 | 0.222757E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_DOOR
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.248818E+09 | 0.161046E+09 | 87771976.65 | 0.237297E+09 | 0.233872E+09 |
February | 0.274565E+09 | 0.167549E+09 | 0.107017E+09 | 0.258355E+09 | 0.205169E+09 |
March | 0.187972E+09 | 54756523.16 | 0.133216E+09 | 0.130654E+09 | 0.192023E+09 |
April | 0.377707E+09 | 0.170740E+09 | 0.206968E+09 | 0.339560E+09 | 0.160874E+09 |
May | 0.322732E+09 | 0.105039E+09 | 0.217694E+09 | 0.233197E+09 | 0.147465E+09 |
June | 0.287717E+09 | 69612766.79 | 0.218104E+09 | 0.206321E+09 | 0.117079E+09 |
July | 0.322124E+09 | 0.100843E+09 | 0.221281E+09 | 0.252589E+09 | 0.113282E+09 |
August | 0.377507E+09 | 0.169811E+09 | 0.207695E+09 | 0.347686E+09 | 0.123121E+09 |
September | 0.431889E+09 | 0.253072E+09 | 0.178817E+09 | 0.437941E+09 | 0.150524E+09 |
October | 0.306576E+09 | 0.179209E+09 | 0.127367E+09 | 0.302578E+09 | 0.190566E+09 |
November | 0.210253E+09 | 0.127882E+09 | 82370351.56 | 0.200114E+09 | 0.209584E+09 |
December | 0.172177E+09 | 0.110292E+09 | 61885246.61 | 0.160402E+09 | 0.264576E+09 |
Annual Sum or Average | 0.352004E+10 | 0.166985E+10 | 0.185019E+10 | 0.310669E+10 | 0.210814E+10 |
Minimum of Months | 0.172177E+09 | 54756523.16 | 61885246.61 | 0.130654E+09 | 0.113282E+09 |
Maximum of Months | 0.431889E+09 | 0.253072E+09 | 0.221281E+09 | 0.437941E+09 | 0.264576E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.207804E+09 | 0.134500E+09 | 73304068.41 | 0.198441E+09 | 0.194311E+09 |
February | 0.229307E+09 | 0.139931E+09 | 89376690.89 | 0.215963E+09 | 0.170714E+09 |
March | 0.156988E+09 | 45730722.64 | 0.111257E+09 | 0.109254E+09 | 0.159445E+09 |
April | 0.315448E+09 | 0.142596E+09 | 0.172852E+09 | 0.284311E+09 | 0.133121E+09 |
May | 0.269535E+09 | 87724495.05 | 0.181810E+09 | 0.195385E+09 | 0.122124E+09 |
June | 0.240291E+09 | 58138134.90 | 0.182153E+09 | 0.172518E+09 | 97617558.53 |
July | 0.269027E+09 | 84220443.19 | 0.184806E+09 | 0.211059E+09 | 94719609.07 |
August | 0.315280E+09 | 0.141820E+09 | 0.173460E+09 | 0.290495E+09 | 0.103091E+09 |
September | 0.360699E+09 | 0.211357E+09 | 0.149342E+09 | 0.365993E+09 | 0.125841E+09 |
October | 0.256042E+09 | 0.149669E+09 | 0.106373E+09 | 0.253233E+09 | 0.157843E+09 |
November | 0.175596E+09 | 0.106803E+09 | 68792821.08 | 0.167368E+09 | 0.174003E+09 |
December | 0.143797E+09 | 92112206.48 | 51684381.78 | 0.134104E+09 | 0.220224E+09 |
Annual Sum or Average | 0.293981E+10 | 0.139460E+10 | 0.154521E+10 | 0.259812E+10 | 0.175305E+10 |
Minimum of Months | 0.143797E+09 | 45730722.64 | 51684381.78 | 0.109254E+09 | 94719609.07 |
Maximum of Months | 0.360699E+09 | 0.211357E+09 | 0.184806E+09 | 0.365993E+09 | 0.220224E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.207804E+09 | 0.134500E+09 | 73304068.41 | 0.198441E+09 | 0.194311E+09 |
February | 0.229307E+09 | 0.139931E+09 | 89376690.89 | 0.215963E+09 | 0.170714E+09 |
March | 0.156988E+09 | 45730722.64 | 0.111257E+09 | 0.109254E+09 | 0.159445E+09 |
April | 0.315448E+09 | 0.142596E+09 | 0.172852E+09 | 0.284311E+09 | 0.133121E+09 |
May | 0.269535E+09 | 87724495.05 | 0.181810E+09 | 0.195385E+09 | 0.122124E+09 |
June | 0.240291E+09 | 58138134.90 | 0.182153E+09 | 0.172518E+09 | 97617558.53 |
July | 0.269027E+09 | 84220443.19 | 0.184806E+09 | 0.211059E+09 | 94719609.07 |
August | 0.315280E+09 | 0.141820E+09 | 0.173460E+09 | 0.290495E+09 | 0.103091E+09 |
September | 0.360699E+09 | 0.211357E+09 | 0.149342E+09 | 0.365993E+09 | 0.125841E+09 |
October | 0.256042E+09 | 0.149669E+09 | 0.106373E+09 | 0.253233E+09 | 0.157843E+09 |
November | 0.175596E+09 | 0.106803E+09 | 68792821.08 | 0.167368E+09 | 0.174003E+09 |
December | 0.143797E+09 | 92112206.48 | 51684381.78 | 0.134104E+09 | 0.220224E+09 |
Annual Sum or Average | 0.293981E+10 | 0.139460E+10 | 0.154521E+10 | 0.259812E+10 | 0.175305E+10 |
Minimum of Months | 0.143797E+09 | 45730722.64 | 51684381.78 | 0.109254E+09 | 94719609.07 |
Maximum of Months | 0.360699E+09 | 0.211357E+09 | 0.184806E+09 | 0.365993E+09 | 0.220224E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_DOOR
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.248818E+09 | 0.161046E+09 | 87771976.65 | 0.237742E+09 | 0.231003E+09 |
February | 0.274565E+09 | 0.167549E+09 | 0.107017E+09 | 0.258750E+09 | 0.202801E+09 |
March | 0.187972E+09 | 54756523.16 | 0.133216E+09 | 0.131104E+09 | 0.189542E+09 |
April | 0.377707E+09 | 0.170740E+09 | 0.206968E+09 | 0.340602E+09 | 0.158278E+09 |
May | 0.322732E+09 | 0.105039E+09 | 0.217694E+09 | 0.234311E+09 | 0.145008E+09 |
June | 0.287717E+09 | 69612766.79 | 0.218104E+09 | 0.206852E+09 | 0.115964E+09 |
July | 0.322124E+09 | 0.100843E+09 | 0.221281E+09 | 0.252880E+09 | 0.112560E+09 |
August | 0.377507E+09 | 0.169811E+09 | 0.207695E+09 | 0.347818E+09 | 0.122622E+09 |
September | 0.431889E+09 | 0.253072E+09 | 0.178817E+09 | 0.438155E+09 | 0.149658E+09 |
October | 0.306576E+09 | 0.179209E+09 | 0.127367E+09 | 0.303241E+09 | 0.187646E+09 |
November | 0.210253E+09 | 0.127882E+09 | 82370351.56 | 0.200497E+09 | 0.206788E+09 |
December | 0.172177E+09 | 0.110292E+09 | 61885246.61 | 0.160704E+09 | 0.261556E+09 |
Annual Sum or Average | 0.352004E+10 | 0.166985E+10 | 0.185019E+10 | 0.311266E+10 | 0.208343E+10 |
Minimum of Months | 0.172177E+09 | 54756523.16 | 61885246.61 | 0.131104E+09 | 0.112560E+09 |
Maximum of Months | 0.431889E+09 | 0.253072E+09 | 0.221281E+09 | 0.438155E+09 | 0.261556E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.207804E+09 | 0.134500E+09 | 73304068.41 | 0.198834E+09 | 0.192474E+09 |
February | 0.229307E+09 | 0.139931E+09 | 89376690.89 | 0.216335E+09 | 0.169195E+09 |
March | 0.156988E+09 | 45730722.64 | 0.111257E+09 | 0.109688E+09 | 0.157839E+09 |
April | 0.315448E+09 | 0.142596E+09 | 0.172852E+09 | 0.285631E+09 | 0.130729E+09 |
May | 0.269535E+09 | 87724495.05 | 0.181810E+09 | 0.196877E+09 | 0.119649E+09 |
June | 0.240291E+09 | 58138134.90 | 0.182153E+09 | 0.173814E+09 | 95752734.04 |
July | 0.269027E+09 | 84220443.19 | 0.184806E+09 | 0.211783E+09 | 93488929.47 |
August | 0.315280E+09 | 0.141820E+09 | 0.173460E+09 | 0.290842E+09 | 0.102233E+09 |
September | 0.360699E+09 | 0.211357E+09 | 0.149342E+09 | 0.366532E+09 | 0.124516E+09 |
October | 0.256042E+09 | 0.149669E+09 | 0.106373E+09 | 0.254157E+09 | 0.155017E+09 |
November | 0.175596E+09 | 0.106803E+09 | 68792821.08 | 0.167691E+09 | 0.172306E+09 |
December | 0.143797E+09 | 92112206.48 | 51684381.78 | 0.134405E+09 | 0.218115E+09 |
Annual Sum or Average | 0.293981E+10 | 0.139460E+10 | 0.154521E+10 | 0.260659E+10 | 0.173131E+10 |
Minimum of Months | 0.143797E+09 | 45730722.64 | 51684381.78 | 0.109688E+09 | 93488929.47 |
Maximum of Months | 0.360699E+09 | 0.211357E+09 | 0.184806E+09 | 0.366532E+09 | 0.218115E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.207804E+09 | 0.134500E+09 | 73304068.41 | 0.198834E+09 | 0.192474E+09 |
February | 0.229307E+09 | 0.139931E+09 | 89376690.89 | 0.216335E+09 | 0.169195E+09 |
March | 0.156988E+09 | 45730722.64 | 0.111257E+09 | 0.109688E+09 | 0.157839E+09 |
April | 0.315448E+09 | 0.142596E+09 | 0.172852E+09 | 0.285631E+09 | 0.130729E+09 |
May | 0.269535E+09 | 87724495.05 | 0.181810E+09 | 0.196877E+09 | 0.119649E+09 |
June | 0.240291E+09 | 58138134.90 | 0.182153E+09 | 0.173814E+09 | 95752734.04 |
July | 0.269027E+09 | 84220443.19 | 0.184806E+09 | 0.211783E+09 | 93488929.47 |
August | 0.315280E+09 | 0.141820E+09 | 0.173460E+09 | 0.290842E+09 | 0.102233E+09 |
September | 0.360699E+09 | 0.211357E+09 | 0.149342E+09 | 0.366532E+09 | 0.124516E+09 |
October | 0.256042E+09 | 0.149669E+09 | 0.106373E+09 | 0.254157E+09 | 0.155017E+09 |
November | 0.175596E+09 | 0.106803E+09 | 68792821.08 | 0.167691E+09 | 0.172306E+09 |
December | 0.143797E+09 | 92112206.48 | 51684381.78 | 0.134405E+09 | 0.218115E+09 |
Annual Sum or Average | 0.293981E+10 | 0.139460E+10 | 0.154521E+10 | 0.260659E+10 | 0.173131E+10 |
Minimum of Months | 0.143797E+09 | 45730722.64 | 51684381.78 | 0.109688E+09 | 93488929.47 |
Maximum of Months | 0.360699E+09 | 0.211357E+09 | 0.184806E+09 | 0.366532E+09 | 0.218115E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_DOOR
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.248818E+09 | 0.161046E+09 | 87771976.65 | 0.238220E+09 | 0.228814E+09 |
February | 0.274565E+09 | 0.167549E+09 | 0.107017E+09 | 0.259203E+09 | 0.200994E+09 |
March | 0.187972E+09 | 54756523.16 | 0.133216E+09 | 0.131631E+09 | 0.187629E+09 |
April | 0.377707E+09 | 0.170740E+09 | 0.206968E+09 | 0.342183E+09 | 0.155439E+09 |
May | 0.322732E+09 | 0.105039E+09 | 0.217694E+09 | 0.236099E+09 | 0.142079E+09 |
June | 0.287717E+09 | 69612766.79 | 0.218104E+09 | 0.208409E+09 | 0.113757E+09 |
July | 0.322124E+09 | 0.100843E+09 | 0.221281E+09 | 0.253752E+09 | 0.111105E+09 |
August | 0.377507E+09 | 0.169811E+09 | 0.207695E+09 | 0.348238E+09 | 0.121607E+09 |
September | 0.431889E+09 | 0.253072E+09 | 0.178817E+09 | 0.438806E+09 | 0.148088E+09 |
October | 0.306576E+09 | 0.179209E+09 | 0.127367E+09 | 0.304350E+09 | 0.184288E+09 |
November | 0.210253E+09 | 0.127882E+09 | 82370351.56 | 0.200890E+09 | 0.204768E+09 |
December | 0.172177E+09 | 0.110292E+09 | 61885246.61 | 0.161069E+09 | 0.259040E+09 |
Annual Sum or Average | 0.352004E+10 | 0.166985E+10 | 0.185019E+10 | 0.312285E+10 | 0.205761E+10 |
Minimum of Months | 0.172177E+09 | 54756523.16 | 61885246.61 | 0.131631E+09 | 0.111105E+09 |
Maximum of Months | 0.431889E+09 | 0.253072E+09 | 0.221281E+09 | 0.438806E+09 | 0.259040E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.207804E+09 | 0.134500E+09 | 73304068.41 | 0.200243E+09 | 0.188033E+09 |
February | 0.229307E+09 | 0.139931E+09 | 89376690.89 | 0.217723E+09 | 0.165302E+09 |
March | 0.156988E+09 | 45730722.64 | 0.111257E+09 | 0.111130E+09 | 0.153992E+09 |
April | 0.315448E+09 | 0.142596E+09 | 0.172852E+09 | 0.288521E+09 | 0.125957E+09 |
May | 0.269535E+09 | 87724495.05 | 0.181810E+09 | 0.200208E+09 | 0.114542E+09 |
June | 0.240291E+09 | 58138134.90 | 0.182153E+09 | 0.177601E+09 | 90932730.17 |
July | 0.269027E+09 | 84220443.19 | 0.184806E+09 | 0.213750E+09 | 90227830.29 |
August | 0.315280E+09 | 0.141820E+09 | 0.173460E+09 | 0.291599E+09 | 99814309.34 |
September | 0.360699E+09 | 0.211357E+09 | 0.149342E+09 | 0.368366E+09 | 0.120717E+09 |
October | 0.256042E+09 | 0.149669E+09 | 0.106373E+09 | 0.256698E+09 | 0.148968E+09 |
November | 0.175596E+09 | 0.106803E+09 | 68792821.08 | 0.168740E+09 | 0.168318E+09 |
December | 0.143797E+09 | 92112206.48 | 51684381.78 | 0.135538E+09 | 0.212305E+09 |
Annual Sum or Average | 0.293981E+10 | 0.139460E+10 | 0.154521E+10 | 0.263012E+10 | 0.167911E+10 |
Minimum of Months | 0.143797E+09 | 45730722.64 | 51684381.78 | 0.111130E+09 | 90227830.29 |
Maximum of Months | 0.360699E+09 | 0.211357E+09 | 0.184806E+09 | 0.368366E+09 | 0.212305E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.207804E+09 | 0.134500E+09 | 73304068.41 | 0.200243E+09 | 0.188033E+09 |
February | 0.229307E+09 | 0.139931E+09 | 89376690.89 | 0.217723E+09 | 0.165302E+09 |
March | 0.156988E+09 | 45730722.64 | 0.111257E+09 | 0.111130E+09 | 0.153992E+09 |
April | 0.315448E+09 | 0.142596E+09 | 0.172852E+09 | 0.288521E+09 | 0.125957E+09 |
May | 0.269535E+09 | 87724495.05 | 0.181810E+09 | 0.200208E+09 | 0.114542E+09 |
June | 0.240291E+09 | 58138134.90 | 0.182153E+09 | 0.177601E+09 | 90932730.17 |
July | 0.269027E+09 | 84220443.19 | 0.184806E+09 | 0.213750E+09 | 90227830.29 |
August | 0.315280E+09 | 0.141820E+09 | 0.173460E+09 | 0.291599E+09 | 99814309.34 |
September | 0.360699E+09 | 0.211357E+09 | 0.149342E+09 | 0.368366E+09 | 0.120717E+09 |
October | 0.256042E+09 | 0.149669E+09 | 0.106373E+09 | 0.256698E+09 | 0.148968E+09 |
November | 0.175596E+09 | 0.106803E+09 | 68792821.08 | 0.168740E+09 | 0.168318E+09 |
December | 0.143797E+09 | 92112206.48 | 51684381.78 | 0.135538E+09 | 0.212305E+09 |
Annual Sum or Average | 0.293981E+10 | 0.139460E+10 | 0.154521E+10 | 0.263012E+10 | 0.167911E+10 |
Minimum of Months | 0.143797E+09 | 45730722.64 | 51684381.78 | 0.111130E+09 | 90227830.29 |
Maximum of Months | 0.360699E+09 | 0.211357E+09 | 0.184806E+09 | 0.368366E+09 | 0.212305E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_3
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.207804E+09 | 0.134500E+09 | 73304068.41 | 0.200243E+09 | 0.188033E+09 |
February | 0.229307E+09 | 0.139931E+09 | 89376690.89 | 0.217723E+09 | 0.165302E+09 |
March | 0.156988E+09 | 45730722.64 | 0.111257E+09 | 0.111130E+09 | 0.153992E+09 |
April | 0.315448E+09 | 0.142596E+09 | 0.172852E+09 | 0.288521E+09 | 0.125957E+09 |
May | 0.269535E+09 | 87724495.05 | 0.181810E+09 | 0.200208E+09 | 0.114542E+09 |
June | 0.240291E+09 | 58138134.90 | 0.182153E+09 | 0.177601E+09 | 90932730.17 |
July | 0.269027E+09 | 84220443.19 | 0.184806E+09 | 0.213750E+09 | 90227830.29 |
August | 0.315280E+09 | 0.141820E+09 | 0.173460E+09 | 0.291599E+09 | 99814309.34 |
September | 0.360699E+09 | 0.211357E+09 | 0.149342E+09 | 0.368366E+09 | 0.120717E+09 |
October | 0.256042E+09 | 0.149669E+09 | 0.106373E+09 | 0.256698E+09 | 0.148968E+09 |
November | 0.175596E+09 | 0.106803E+09 | 68792821.08 | 0.168740E+09 | 0.168318E+09 |
December | 0.143797E+09 | 92112206.48 | 51684381.78 | 0.135538E+09 | 0.212305E+09 |
Annual Sum or Average | 0.293981E+10 | 0.139460E+10 | 0.154521E+10 | 0.263012E+10 | 0.167911E+10 |
Minimum of Months | 0.143797E+09 | 45730722.64 | 51684381.78 | 0.111130E+09 | 90227830.29 |
Maximum of Months | 0.360699E+09 | 0.211357E+09 | 0.184806E+09 | 0.368366E+09 | 0.212305E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_4
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.207804E+09 | 0.134500E+09 | 73304068.41 | 0.200243E+09 | 0.188033E+09 |
February | 0.229307E+09 | 0.139931E+09 | 89376690.89 | 0.217723E+09 | 0.165302E+09 |
March | 0.156988E+09 | 45730722.64 | 0.111257E+09 | 0.111130E+09 | 0.153992E+09 |
April | 0.315448E+09 | 0.142596E+09 | 0.172852E+09 | 0.288521E+09 | 0.125957E+09 |
May | 0.269535E+09 | 87724495.05 | 0.181810E+09 | 0.200208E+09 | 0.114542E+09 |
June | 0.240291E+09 | 58138134.90 | 0.182153E+09 | 0.177601E+09 | 90932730.17 |
July | 0.269027E+09 | 84220443.19 | 0.184806E+09 | 0.213750E+09 | 90227830.29 |
August | 0.315280E+09 | 0.141820E+09 | 0.173460E+09 | 0.291599E+09 | 99814309.34 |
September | 0.360699E+09 | 0.211357E+09 | 0.149342E+09 | 0.368366E+09 | 0.120717E+09 |
October | 0.256042E+09 | 0.149669E+09 | 0.106373E+09 | 0.256698E+09 | 0.148968E+09 |
November | 0.175596E+09 | 0.106803E+09 | 68792821.08 | 0.168740E+09 | 0.168318E+09 |
December | 0.143797E+09 | 92112206.48 | 51684381.78 | 0.135538E+09 | 0.212305E+09 |
Annual Sum or Average | 0.293981E+10 | 0.139460E+10 | 0.154521E+10 | 0.263012E+10 | 0.167911E+10 |
Minimum of Months | 0.143797E+09 | 45730722.64 | 51684381.78 | 0.111130E+09 | 90227830.29 |
Maximum of Months | 0.360699E+09 | 0.211357E+09 | 0.184806E+09 | 0.368366E+09 | 0.212305E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_DOOR_1
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.248818E+09 | 0.161046E+09 | 87771976.65 | 0.239907E+09 | 0.223527E+09 |
February | 0.274565E+09 | 0.167549E+09 | 0.107017E+09 | 0.260860E+09 | 0.196374E+09 |
March | 0.187972E+09 | 54756523.16 | 0.133216E+09 | 0.133373E+09 | 0.183055E+09 |
April | 0.377707E+09 | 0.170740E+09 | 0.206968E+09 | 0.345626E+09 | 0.149783E+09 |
May | 0.322732E+09 | 0.105039E+09 | 0.217694E+09 | 0.240068E+09 | 0.136052E+09 |
June | 0.287717E+09 | 69612766.79 | 0.218104E+09 | 0.212916E+09 | 0.108065E+09 |
July | 0.322124E+09 | 0.100843E+09 | 0.221281E+09 | 0.256106E+09 | 0.107258E+09 |
August | 0.377507E+09 | 0.169811E+09 | 0.207695E+09 | 0.349160E+09 | 0.118755E+09 |
September | 0.431889E+09 | 0.253072E+09 | 0.178817E+09 | 0.440993E+09 | 0.143601E+09 |
October | 0.306576E+09 | 0.179209E+09 | 0.127367E+09 | 0.307367E+09 | 0.177116E+09 |
November | 0.210253E+09 | 0.127882E+09 | 82370351.56 | 0.202142E+09 | 0.200028E+09 |
December | 0.172177E+09 | 0.110292E+09 | 61885246.61 | 0.162420E+09 | 0.252138E+09 |
Annual Sum or Average | 0.352004E+10 | 0.166985E+10 | 0.185019E+10 | 0.315094E+10 | 0.199575E+10 |
Minimum of Months | 0.172177E+09 | 54756523.16 | 61885246.61 | 0.133373E+09 | 0.107258E+09 |
Maximum of Months | 0.431889E+09 | 0.253072E+09 | 0.221281E+09 | 0.440993E+09 | 0.252138E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_DOOR_2
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.248818E+09 | 0.161046E+09 | 87771976.65 | 0.239907E+09 | 0.223527E+09 |
February | 0.274565E+09 | 0.167549E+09 | 0.107017E+09 | 0.260860E+09 | 0.196374E+09 |
March | 0.187972E+09 | 54756523.16 | 0.133216E+09 | 0.133373E+09 | 0.183055E+09 |
April | 0.377707E+09 | 0.170740E+09 | 0.206968E+09 | 0.345626E+09 | 0.149783E+09 |
May | 0.322732E+09 | 0.105039E+09 | 0.217694E+09 | 0.240068E+09 | 0.136052E+09 |
June | 0.287717E+09 | 69612766.79 | 0.218104E+09 | 0.212916E+09 | 0.108065E+09 |
July | 0.322124E+09 | 0.100843E+09 | 0.221281E+09 | 0.256106E+09 | 0.107258E+09 |
August | 0.377507E+09 | 0.169811E+09 | 0.207695E+09 | 0.349160E+09 | 0.118755E+09 |
September | 0.431889E+09 | 0.253072E+09 | 0.178817E+09 | 0.440993E+09 | 0.143601E+09 |
October | 0.306576E+09 | 0.179209E+09 | 0.127367E+09 | 0.307367E+09 | 0.177116E+09 |
November | 0.210253E+09 | 0.127882E+09 | 82370351.56 | 0.202142E+09 | 0.200028E+09 |
December | 0.172177E+09 | 0.110292E+09 | 61885246.61 | 0.162420E+09 | 0.252138E+09 |
Annual Sum or Average | 0.352004E+10 | 0.166985E+10 | 0.185019E+10 | 0.315094E+10 | 0.199575E+10 |
Minimum of Months | 0.172177E+09 | 54756523.16 | 61885246.61 | 0.133373E+09 | 0.107258E+09 |
Maximum of Months | 0.431889E+09 | 0.253072E+09 | 0.221281E+09 | 0.440993E+09 | 0.252138E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.207804E+09 | 0.134500E+09 | 73304068.41 | 0.200211E+09 | 0.187661E+09 |
February | 0.229307E+09 | 0.139931E+09 | 89376690.89 | 0.217739E+09 | 0.165019E+09 |
March | 0.156988E+09 | 45730722.64 | 0.111257E+09 | 0.111184E+09 | 0.153351E+09 |
April | 0.315448E+09 | 0.142596E+09 | 0.172852E+09 | 0.288703E+09 | 0.125522E+09 |
May | 0.269535E+09 | 87724495.05 | 0.181810E+09 | 0.200383E+09 | 0.114370E+09 |
June | 0.240291E+09 | 58138134.90 | 0.182153E+09 | 0.177624E+09 | 90960868.24 |
July | 0.269027E+09 | 84220443.19 | 0.184806E+09 | 0.214065E+09 | 89935705.04 |
August | 0.315280E+09 | 0.141820E+09 | 0.173460E+09 | 0.291913E+09 | 99387118.33 |
September | 0.360699E+09 | 0.211357E+09 | 0.149342E+09 | 0.368330E+09 | 0.120754E+09 |
October | 0.256042E+09 | 0.149669E+09 | 0.106373E+09 | 0.256631E+09 | 0.148570E+09 |
November | 0.175596E+09 | 0.106803E+09 | 68792821.08 | 0.168830E+09 | 0.167831E+09 |
December | 0.143797E+09 | 92112206.48 | 51684381.78 | 0.135509E+09 | 0.212458E+09 |
Annual Sum or Average | 0.293981E+10 | 0.139460E+10 | 0.154521E+10 | 0.263112E+10 | 0.167582E+10 |
Minimum of Months | 0.143797E+09 | 45730722.64 | 51684381.78 | 0.111184E+09 | 89935705.04 |
Maximum of Months | 0.360699E+09 | 0.211357E+09 | 0.184806E+09 | 0.368330E+09 | 0.212458E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.207804E+09 | 0.134500E+09 | 73304068.41 | 0.200211E+09 | 0.187661E+09 |
February | 0.229307E+09 | 0.139931E+09 | 89376690.89 | 0.217739E+09 | 0.165019E+09 |
March | 0.156988E+09 | 45730722.64 | 0.111257E+09 | 0.111184E+09 | 0.153351E+09 |
April | 0.315448E+09 | 0.142596E+09 | 0.172852E+09 | 0.288703E+09 | 0.125522E+09 |
May | 0.269535E+09 | 87724495.05 | 0.181810E+09 | 0.200383E+09 | 0.114370E+09 |
June | 0.240291E+09 | 58138134.90 | 0.182153E+09 | 0.177624E+09 | 90960868.24 |
July | 0.269027E+09 | 84220443.19 | 0.184806E+09 | 0.214065E+09 | 89935705.04 |
August | 0.315280E+09 | 0.141820E+09 | 0.173460E+09 | 0.291913E+09 | 99387118.33 |
September | 0.360699E+09 | 0.211357E+09 | 0.149342E+09 | 0.368330E+09 | 0.120754E+09 |
October | 0.256042E+09 | 0.149669E+09 | 0.106373E+09 | 0.256631E+09 | 0.148570E+09 |
November | 0.175596E+09 | 0.106803E+09 | 68792821.08 | 0.168830E+09 | 0.167831E+09 |
December | 0.143797E+09 | 92112206.48 | 51684381.78 | 0.135509E+09 | 0.212458E+09 |
Annual Sum or Average | 0.293981E+10 | 0.139460E+10 | 0.154521E+10 | 0.263112E+10 | 0.167582E+10 |
Minimum of Months | 0.143797E+09 | 45730722.64 | 51684381.78 | 0.111184E+09 | 89935705.04 |
Maximum of Months | 0.360699E+09 | 0.211357E+09 | 0.184806E+09 | 0.368330E+09 | 0.212458E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_DOOR
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.248818E+09 | 0.161046E+09 | 87771976.65 | 0.239888E+09 | 0.223058E+09 |
February | 0.274565E+09 | 0.167549E+09 | 0.107017E+09 | 0.260901E+09 | 0.196006E+09 |
March | 0.187972E+09 | 54756523.16 | 0.133216E+09 | 0.133457E+09 | 0.182277E+09 |
April | 0.377707E+09 | 0.170740E+09 | 0.206968E+09 | 0.345873E+09 | 0.149247E+09 |
May | 0.322732E+09 | 0.105039E+09 | 0.217694E+09 | 0.240307E+09 | 0.135818E+09 |
June | 0.287717E+09 | 69612766.79 | 0.218104E+09 | 0.212971E+09 | 0.108074E+09 |
July | 0.322124E+09 | 0.100843E+09 | 0.221281E+09 | 0.256502E+09 | 0.106891E+09 |
August | 0.377507E+09 | 0.169811E+09 | 0.207695E+09 | 0.349554E+09 | 0.118232E+09 |
September | 0.431889E+09 | 0.253072E+09 | 0.178817E+09 | 0.440978E+09 | 0.143618E+09 |
October | 0.306576E+09 | 0.179209E+09 | 0.127367E+09 | 0.307316E+09 | 0.176616E+09 |
November | 0.210253E+09 | 0.127882E+09 | 82370351.56 | 0.202266E+09 | 0.199418E+09 |
December | 0.172177E+09 | 0.110292E+09 | 61885246.61 | 0.162400E+09 | 0.252275E+09 |
Annual Sum or Average | 0.352004E+10 | 0.166985E+10 | 0.185019E+10 | 0.315241E+10 | 0.199153E+10 |
Minimum of Months | 0.172177E+09 | 54756523.16 | 61885246.61 | 0.133457E+09 | 0.106891E+09 |
Maximum of Months | 0.431889E+09 | 0.253072E+09 | 0.221281E+09 | 0.440978E+09 | 0.252275E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.207804E+09 | 0.134500E+09 | 73304068.41 | 0.200417E+09 | 0.186788E+09 |
February | 0.229307E+09 | 0.139931E+09 | 89376690.89 | 0.217957E+09 | 0.164231E+09 |
March | 0.156988E+09 | 45730722.64 | 0.111257E+09 | 0.111436E+09 | 0.152535E+09 |
April | 0.315448E+09 | 0.142596E+09 | 0.172852E+09 | 0.289162E+09 | 0.124743E+09 |
May | 0.269535E+09 | 87724495.05 | 0.181810E+09 | 0.200974E+09 | 0.113509E+09 |
June | 0.240291E+09 | 58138134.90 | 0.182153E+09 | 0.178378E+09 | 90107702.26 |
July | 0.269027E+09 | 84220443.19 | 0.184806E+09 | 0.214616E+09 | 89279848.82 |
August | 0.315280E+09 | 0.141820E+09 | 0.173460E+09 | 0.292237E+09 | 98896532.03 |
September | 0.360699E+09 | 0.211357E+09 | 0.149342E+09 | 0.368760E+09 | 0.120047E+09 |
October | 0.256042E+09 | 0.149669E+09 | 0.106373E+09 | 0.257046E+09 | 0.147524E+09 |
November | 0.175596E+09 | 0.106803E+09 | 68792821.08 | 0.169013E+09 | 0.166984E+09 |
December | 0.143797E+09 | 92112206.48 | 51684381.78 | 0.135640E+09 | 0.211584E+09 |
Annual Sum or Average | 0.293981E+10 | 0.139460E+10 | 0.154521E+10 | 0.263564E+10 | 0.166623E+10 |
Minimum of Months | 0.143797E+09 | 45730722.64 | 51684381.78 | 0.111436E+09 | 89279848.82 |
Maximum of Months | 0.360699E+09 | 0.211357E+09 | 0.184806E+09 | 0.368760E+09 | 0.211584E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.207804E+09 | 0.134500E+09 | 73304068.41 | 0.200417E+09 | 0.186788E+09 |
February | 0.229307E+09 | 0.139931E+09 | 89376690.89 | 0.217957E+09 | 0.164231E+09 |
March | 0.156988E+09 | 45730722.64 | 0.111257E+09 | 0.111436E+09 | 0.152535E+09 |
April | 0.315448E+09 | 0.142596E+09 | 0.172852E+09 | 0.289162E+09 | 0.124743E+09 |
May | 0.269535E+09 | 87724495.05 | 0.181810E+09 | 0.200974E+09 | 0.113509E+09 |
June | 0.240291E+09 | 58138134.90 | 0.182153E+09 | 0.178378E+09 | 90107702.26 |
July | 0.269027E+09 | 84220443.19 | 0.184806E+09 | 0.214616E+09 | 89279848.82 |
August | 0.315280E+09 | 0.141820E+09 | 0.173460E+09 | 0.292237E+09 | 98896532.03 |
September | 0.360699E+09 | 0.211357E+09 | 0.149342E+09 | 0.368760E+09 | 0.120047E+09 |
October | 0.256042E+09 | 0.149669E+09 | 0.106373E+09 | 0.257046E+09 | 0.147524E+09 |
November | 0.175596E+09 | 0.106803E+09 | 68792821.08 | 0.169013E+09 | 0.166984E+09 |
December | 0.143797E+09 | 92112206.48 | 51684381.78 | 0.135640E+09 | 0.211584E+09 |
Annual Sum or Average | 0.293981E+10 | 0.139460E+10 | 0.154521E+10 | 0.263564E+10 | 0.166623E+10 |
Minimum of Months | 0.143797E+09 | 45730722.64 | 51684381.78 | 0.111436E+09 | 89279848.82 |
Maximum of Months | 0.360699E+09 | 0.211357E+09 | 0.184806E+09 | 0.368760E+09 | 0.211584E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_DOOR
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.248818E+09 | 0.161046E+09 | 87771976.65 | 0.240139E+09 | 0.222014E+09 |
February | 0.274565E+09 | 0.167549E+09 | 0.107017E+09 | 0.261166E+09 | 0.195064E+09 |
March | 0.187972E+09 | 54756523.16 | 0.133216E+09 | 0.133764E+09 | 0.181302E+09 |
April | 0.377707E+09 | 0.170740E+09 | 0.206968E+09 | 0.346424E+09 | 0.148319E+09 |
May | 0.322732E+09 | 0.105039E+09 | 0.217694E+09 | 0.241017E+09 | 0.134796E+09 |
June | 0.287717E+09 | 69612766.79 | 0.218104E+09 | 0.213873E+09 | 0.107061E+09 |
July | 0.322124E+09 | 0.100843E+09 | 0.221281E+09 | 0.257162E+09 | 0.106112E+09 |
August | 0.377507E+09 | 0.169811E+09 | 0.207695E+09 | 0.349943E+09 | 0.117649E+09 |
September | 0.431889E+09 | 0.253072E+09 | 0.178817E+09 | 0.441494E+09 | 0.142778E+09 |
October | 0.306576E+09 | 0.179209E+09 | 0.127367E+09 | 0.307814E+09 | 0.175370E+09 |
November | 0.210253E+09 | 0.127882E+09 | 82370351.56 | 0.202489E+09 | 0.198406E+09 |
December | 0.172177E+09 | 0.110292E+09 | 61885246.61 | 0.162560E+09 | 0.251230E+09 |
Annual Sum or Average | 0.352004E+10 | 0.166985E+10 | 0.185019E+10 | 0.315785E+10 | 0.198010E+10 |
Minimum of Months | 0.172177E+09 | 54756523.16 | 61885246.61 | 0.133764E+09 | 0.106112E+09 |
Maximum of Months | 0.431889E+09 | 0.253072E+09 | 0.221281E+09 | 0.441494E+09 | 0.251230E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.207804E+09 | 0.134500E+09 | 73304068.41 | 0.200925E+09 | 0.184214E+09 |
February | 0.229307E+09 | 0.139931E+09 | 89376690.89 | 0.218512E+09 | 0.161841E+09 |
March | 0.156988E+09 | 45730722.64 | 0.111257E+09 | 0.112039E+09 | 0.150121E+09 |
April | 0.315448E+09 | 0.142596E+09 | 0.172852E+09 | 0.290180E+09 | 0.122605E+09 |
May | 0.269535E+09 | 87724495.05 | 0.181810E+09 | 0.202394E+09 | 0.111062E+09 |
June | 0.240291E+09 | 58138134.90 | 0.182153E+09 | 0.180248E+09 | 87690202.04 |
July | 0.269027E+09 | 84220443.19 | 0.184806E+09 | 0.215945E+09 | 87463332.31 |
August | 0.315280E+09 | 0.141820E+09 | 0.173460E+09 | 0.293002E+09 | 97481431.08 |
September | 0.360699E+09 | 0.211357E+09 | 0.149342E+09 | 0.369879E+09 | 0.117876E+09 |
October | 0.256042E+09 | 0.149669E+09 | 0.106373E+09 | 0.257986E+09 | 0.144784E+09 |
November | 0.175596E+09 | 0.106803E+09 | 68792821.08 | 0.169431E+09 | 0.164663E+09 |
December | 0.143797E+09 | 92112206.48 | 51684381.78 | 0.135990E+09 | 0.208876E+09 |
Annual Sum or Average | 0.293981E+10 | 0.139460E+10 | 0.154521E+10 | 0.264653E+10 | 0.163868E+10 |
Minimum of Months | 0.143797E+09 | 45730722.64 | 51684381.78 | 0.112039E+09 | 87463332.31 |
Maximum of Months | 0.360699E+09 | 0.211357E+09 | 0.184806E+09 | 0.369879E+09 | 0.208876E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.207804E+09 | 0.134500E+09 | 73304068.41 | 0.200925E+09 | 0.184214E+09 |
February | 0.229307E+09 | 0.139931E+09 | 89376690.89 | 0.218512E+09 | 0.161841E+09 |
March | 0.156988E+09 | 45730722.64 | 0.111257E+09 | 0.112039E+09 | 0.150121E+09 |
April | 0.315448E+09 | 0.142596E+09 | 0.172852E+09 | 0.290180E+09 | 0.122605E+09 |
May | 0.269535E+09 | 87724495.05 | 0.181810E+09 | 0.202394E+09 | 0.111062E+09 |
June | 0.240291E+09 | 58138134.90 | 0.182153E+09 | 0.180248E+09 | 87690202.04 |
July | 0.269027E+09 | 84220443.19 | 0.184806E+09 | 0.215945E+09 | 87463332.31 |
August | 0.315280E+09 | 0.141820E+09 | 0.173460E+09 | 0.293002E+09 | 97481431.08 |
September | 0.360699E+09 | 0.211357E+09 | 0.149342E+09 | 0.369879E+09 | 0.117876E+09 |
October | 0.256042E+09 | 0.149669E+09 | 0.106373E+09 | 0.257986E+09 | 0.144784E+09 |
November | 0.175596E+09 | 0.106803E+09 | 68792821.08 | 0.169431E+09 | 0.164663E+09 |
December | 0.143797E+09 | 92112206.48 | 51684381.78 | 0.135990E+09 | 0.208876E+09 |
Annual Sum or Average | 0.293981E+10 | 0.139460E+10 | 0.154521E+10 | 0.264653E+10 | 0.163868E+10 |
Minimum of Months | 0.143797E+09 | 45730722.64 | 51684381.78 | 0.112039E+09 | 87463332.31 |
Maximum of Months | 0.360699E+09 | 0.211357E+09 | 0.184806E+09 | 0.369879E+09 | 0.208876E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_DOOR
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.248818E+09 | 0.161046E+09 | 87771976.65 | 0.240757E+09 | 0.218942E+09 |
February | 0.274565E+09 | 0.167549E+09 | 0.107017E+09 | 0.261841E+09 | 0.192216E+09 |
March | 0.187972E+09 | 54756523.16 | 0.133216E+09 | 0.134500E+09 | 0.178427E+09 |
April | 0.377707E+09 | 0.170740E+09 | 0.206968E+09 | 0.347649E+09 | 0.145780E+09 |
May | 0.322732E+09 | 0.105039E+09 | 0.217694E+09 | 0.242720E+09 | 0.131896E+09 |
June | 0.287717E+09 | 69612766.79 | 0.218104E+09 | 0.216108E+09 | 0.104195E+09 |
July | 0.322124E+09 | 0.100843E+09 | 0.221281E+09 | 0.258751E+09 | 0.103960E+09 |
August | 0.377507E+09 | 0.169811E+09 | 0.207695E+09 | 0.350863E+09 | 0.115973E+09 |
September | 0.431889E+09 | 0.253072E+09 | 0.178817E+09 | 0.442834E+09 | 0.140204E+09 |
October | 0.306576E+09 | 0.179209E+09 | 0.127367E+09 | 0.308940E+09 | 0.172112E+09 |
November | 0.210253E+09 | 0.127882E+09 | 82370351.56 | 0.202997E+09 | 0.195640E+09 |
December | 0.172177E+09 | 0.110292E+09 | 61885246.61 | 0.162986E+09 | 0.248002E+09 |
Annual Sum or Average | 0.352004E+10 | 0.166985E+10 | 0.185019E+10 | 0.317095E+10 | 0.194734E+10 |
Minimum of Months | 0.172177E+09 | 54756523.16 | 61885246.61 | 0.134500E+09 | 0.103960E+09 |
Maximum of Months | 0.431889E+09 | 0.253072E+09 | 0.221281E+09 | 0.442834E+09 | 0.248002E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.207804E+09 | 0.134500E+09 | 73304068.41 | 0.202691E+09 | 0.175130E+09 |
February | 0.229307E+09 | 0.139931E+09 | 89376690.89 | 0.220464E+09 | 0.153038E+09 |
March | 0.156988E+09 | 45730722.64 | 0.111257E+09 | 0.114173E+09 | 0.141494E+09 |
April | 0.315448E+09 | 0.142596E+09 | 0.172852E+09 | 0.292538E+09 | 0.115730E+09 |
May | 0.269535E+09 | 87724495.05 | 0.181810E+09 | 0.205715E+09 | 0.103269E+09 |
June | 0.240291E+09 | 58138134.90 | 0.182153E+09 | 0.184201E+09 | 80997219.56 |
July | 0.269027E+09 | 84220443.19 | 0.184806E+09 | 0.218939E+09 | 81792244.81 |
August | 0.315280E+09 | 0.141820E+09 | 0.173460E+09 | 0.295071E+09 | 92225774.47 |
September | 0.360699E+09 | 0.211357E+09 | 0.149342E+09 | 0.372344E+09 | 0.111354E+09 |
October | 0.256042E+09 | 0.149669E+09 | 0.106373E+09 | 0.260046E+09 | 0.136954E+09 |
November | 0.175596E+09 | 0.106803E+09 | 68792821.08 | 0.170817E+09 | 0.156573E+09 |
December | 0.143797E+09 | 92112206.48 | 51684381.78 | 0.137212E+09 | 0.198909E+09 |
Annual Sum or Average | 0.293981E+10 | 0.139460E+10 | 0.154521E+10 | 0.267421E+10 | 0.154747E+10 |
Minimum of Months | 0.143797E+09 | 45730722.64 | 51684381.78 | 0.114173E+09 | 80997219.56 |
Maximum of Months | 0.360699E+09 | 0.211357E+09 | 0.184806E+09 | 0.372344E+09 | 0.198909E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.207804E+09 | 0.134500E+09 | 73304068.41 | 0.202691E+09 | 0.175130E+09 |
February | 0.229307E+09 | 0.139931E+09 | 89376690.89 | 0.220464E+09 | 0.153038E+09 |
March | 0.156988E+09 | 45730722.64 | 0.111257E+09 | 0.114173E+09 | 0.141494E+09 |
April | 0.315448E+09 | 0.142596E+09 | 0.172852E+09 | 0.292538E+09 | 0.115730E+09 |
May | 0.269535E+09 | 87724495.05 | 0.181810E+09 | 0.205715E+09 | 0.103269E+09 |
June | 0.240291E+09 | 58138134.90 | 0.182153E+09 | 0.184201E+09 | 80997219.56 |
July | 0.269027E+09 | 84220443.19 | 0.184806E+09 | 0.218939E+09 | 81792244.81 |
August | 0.315280E+09 | 0.141820E+09 | 0.173460E+09 | 0.295071E+09 | 92225774.47 |
September | 0.360699E+09 | 0.211357E+09 | 0.149342E+09 | 0.372344E+09 | 0.111354E+09 |
October | 0.256042E+09 | 0.149669E+09 | 0.106373E+09 | 0.260046E+09 | 0.136954E+09 |
November | 0.175596E+09 | 0.106803E+09 | 68792821.08 | 0.170817E+09 | 0.156573E+09 |
December | 0.143797E+09 | 92112206.48 | 51684381.78 | 0.137212E+09 | 0.198909E+09 |
Annual Sum or Average | 0.293981E+10 | 0.139460E+10 | 0.154521E+10 | 0.267421E+10 | 0.154747E+10 |
Minimum of Months | 0.143797E+09 | 45730722.64 | 51684381.78 | 0.114173E+09 | 80997219.56 |
Maximum of Months | 0.360699E+09 | 0.211357E+09 | 0.184806E+09 | 0.372344E+09 | 0.198909E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_DOOR
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.248818E+09 | 0.161046E+09 | 87771976.65 | 0.242908E+09 | 0.208098E+09 |
February | 0.274565E+09 | 0.167549E+09 | 0.107017E+09 | 0.264215E+09 | 0.181725E+09 |
March | 0.187972E+09 | 54756523.16 | 0.133216E+09 | 0.137105E+09 | 0.168137E+09 |
April | 0.377707E+09 | 0.170740E+09 | 0.206968E+09 | 0.350500E+09 | 0.137605E+09 |
May | 0.322732E+09 | 0.105039E+09 | 0.217694E+09 | 0.246720E+09 | 0.122671E+09 |
June | 0.287717E+09 | 69612766.79 | 0.218104E+09 | 0.220836E+09 | 96271219.89 |
July | 0.322124E+09 | 0.100843E+09 | 0.221281E+09 | 0.262337E+09 | 97249186.29 |
August | 0.377507E+09 | 0.169811E+09 | 0.207695E+09 | 0.353350E+09 | 0.109744E+09 |
September | 0.431889E+09 | 0.253072E+09 | 0.178817E+09 | 0.445786E+09 | 0.132474E+09 |
October | 0.306576E+09 | 0.179209E+09 | 0.127367E+09 | 0.311421E+09 | 0.162799E+09 |
November | 0.210253E+09 | 0.127882E+09 | 82370351.56 | 0.204678E+09 | 0.185997E+09 |
December | 0.172177E+09 | 0.110292E+09 | 61885246.61 | 0.164469E+09 | 0.236119E+09 |
Annual Sum or Average | 0.352004E+10 | 0.166985E+10 | 0.185019E+10 | 0.320433E+10 | 0.183889E+10 |
Minimum of Months | 0.172177E+09 | 54756523.16 | 61885246.61 | 0.137105E+09 | 96271219.89 |
Maximum of Months | 0.431889E+09 | 0.253072E+09 | 0.221281E+09 | 0.445786E+09 | 0.236119E+09 |
Report: WindowZoneSummaryMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 477.14 | 459.59 | 497.16 | 321.78 | 175.38 | 0.00 | 0.00 |
February | 575.18 | 445.08 | 607.38 | 370.64 | 236.74 | 0.00 | 0.00 |
March | 264.65 | 374.49 | 375.58 | 109.41 | 266.18 | 0.00 | 0.00 |
April | 711.32 | 314.67 | 779.84 | 352.52 | 427.32 | 0.00 | 0.00 |
May | 476.75 | 276.92 | 644.84 | 209.88 | 434.97 | 0.00 | 0.00 |
June | 435.71 | 227.68 | 594.04 | 143.73 | 450.31 | 0.00 | 0.00 |
July | 510.42 | 215.49 | 643.63 | 201.49 | 442.14 | 0.00 | 0.00 |
August | 698.09 | 236.12 | 754.29 | 339.30 | 414.99 | 0.00 | 0.00 |
September | 909.49 | 298.51 | 891.71 | 522.51 | 369.20 | 0.00 | 0.00 |
October | 612.04 | 361.89 | 612.56 | 358.07 | 254.49 | 0.00 | 0.00 |
November | 415.82 | 424.11 | 434.10 | 264.04 | 170.07 | 0.00 | 0.00 |
December | 322.55 | 519.99 | 344.02 | 220.37 | 123.65 | 0.00 | 0.00 |
Annual Sum or Average | 532.84 | 345.73 | 597.35 | 283.37 | 313.98 | 0.00 | 0.00 |
Minimum of Months | 264.65 | 215.49 | 344.02 | 109.41 | 123.65 | 0.00 | 0.00 |
Maximum of Months | 909.49 | 519.99 | 891.71 | 522.51 | 450.31 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 236.69 | 240.72 | 248.58 | 160.89 | 87.69 | 0.00 | 0.00 |
February | 285.45 | 233.82 | 303.69 | 185.32 | 118.37 | 0.00 | 0.00 |
March | 129.98 | 197.89 | 187.79 | 54.70 | 133.09 | 0.00 | 0.00 |
April | 350.16 | 169.76 | 389.92 | 176.26 | 213.66 | 0.00 | 0.00 |
May | 232.58 | 150.37 | 322.42 | 104.94 | 217.48 | 0.00 | 0.00 |
June | 213.53 | 119.84 | 297.02 | 71.86 | 225.16 | 0.00 | 0.00 |
July | 253.00 | 111.26 | 321.81 | 100.75 | 221.07 | 0.00 | 0.00 |
August | 347.80 | 120.62 | 377.14 | 169.65 | 207.50 | 0.00 | 0.00 |
September | 452.63 | 153.87 | 445.86 | 261.26 | 184.60 | 0.00 | 0.00 |
October | 302.09 | 194.70 | 306.28 | 179.04 | 127.24 | 0.00 | 0.00 |
November | 206.15 | 223.83 | 217.05 | 132.02 | 85.03 | 0.00 | 0.00 |
December | 160.07 | 272.12 | 172.01 | 110.19 | 61.83 | 0.00 | 0.00 |
Annual Sum or Average | 263.55 | 182.15 | 298.67 | 141.69 | 156.99 | 0.00 | 0.00 |
Minimum of Months | 129.98 | 111.26 | 172.01 | 54.70 | 61.83 | 0.00 | 0.00 |
Maximum of Months | 452.63 | 272.12 | 445.86 | 261.26 | 225.16 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 236.50 | 234.21 | 248.07 | 160.56 | 87.51 | 0.00 | 0.00 |
February | 285.07 | 227.58 | 303.07 | 184.94 | 118.13 | 0.00 | 0.00 |
March | 130.09 | 192.31 | 187.41 | 54.59 | 132.81 | 0.00 | 0.00 |
April | 349.71 | 166.47 | 389.12 | 175.90 | 213.22 | 0.00 | 0.00 |
May | 232.27 | 147.79 | 321.76 | 104.72 | 217.04 | 0.00 | 0.00 |
June | 212.37 | 121.22 | 296.41 | 71.72 | 224.69 | 0.00 | 0.00 |
July | 251.73 | 113.48 | 321.15 | 100.54 | 220.61 | 0.00 | 0.00 |
August | 346.65 | 123.26 | 376.37 | 169.30 | 207.07 | 0.00 | 0.00 |
September | 451.22 | 155.73 | 444.94 | 260.72 | 184.22 | 0.00 | 0.00 |
October | 301.65 | 190.85 | 305.65 | 178.67 | 126.98 | 0.00 | 0.00 |
November | 206.10 | 216.93 | 216.61 | 131.75 | 84.86 | 0.00 | 0.00 |
December | 159.84 | 265.12 | 171.66 | 109.96 | 61.70 | 0.00 | 0.00 |
Annual Sum or Average | 262.97 | 179.34 | 298.06 | 141.40 | 156.67 | 0.00 | 0.00 |
Minimum of Months | 130.09 | 113.48 | 171.66 | 54.59 | 61.70 | 0.00 | 0.00 |
Maximum of Months | 451.22 | 265.12 | 444.94 | 260.72 | 224.69 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 236.94 | 231.34 | 248.07 | 160.56 | 87.51 | 0.00 | 0.00 |
February | 285.50 | 224.96 | 303.07 | 184.94 | 118.13 | 0.00 | 0.00 |
March | 130.53 | 189.83 | 187.41 | 54.59 | 132.81 | 0.00 | 0.00 |
April | 350.78 | 163.78 | 389.12 | 175.90 | 213.22 | 0.00 | 0.00 |
May | 233.38 | 145.33 | 321.76 | 104.72 | 217.04 | 0.00 | 0.00 |
June | 212.92 | 120.06 | 296.41 | 71.72 | 224.69 | 0.00 | 0.00 |
July | 252.02 | 112.75 | 321.15 | 100.54 | 220.61 | 0.00 | 0.00 |
August | 346.78 | 122.76 | 376.37 | 169.30 | 207.07 | 0.00 | 0.00 |
September | 451.44 | 154.84 | 444.94 | 260.72 | 184.22 | 0.00 | 0.00 |
October | 302.31 | 187.92 | 305.65 | 178.67 | 126.98 | 0.00 | 0.00 |
November | 206.49 | 214.04 | 216.61 | 131.75 | 84.86 | 0.00 | 0.00 |
December | 160.14 | 262.10 | 171.66 | 109.96 | 61.70 | 0.00 | 0.00 |
Annual Sum or Average | 263.47 | 177.24 | 298.06 | 141.40 | 156.67 | 0.00 | 0.00 |
Minimum of Months | 130.53 | 112.75 | 171.66 | 54.59 | 61.70 | 0.00 | 0.00 |
Maximum of Months | 451.44 | 262.10 | 444.94 | 260.72 | 224.69 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 237.41 | 229.15 | 248.07 | 160.56 | 87.51 | 0.00 | 0.00 |
February | 285.99 | 222.96 | 303.07 | 184.94 | 118.13 | 0.00 | 0.00 |
March | 131.05 | 187.91 | 187.41 | 54.59 | 132.81 | 0.00 | 0.00 |
April | 352.41 | 160.84 | 389.12 | 175.90 | 213.22 | 0.00 | 0.00 |
May | 235.16 | 142.39 | 321.76 | 104.72 | 217.04 | 0.00 | 0.00 |
June | 214.52 | 117.77 | 296.41 | 71.72 | 224.69 | 0.00 | 0.00 |
July | 252.88 | 111.29 | 321.15 | 100.54 | 220.61 | 0.00 | 0.00 |
August | 347.19 | 121.74 | 376.37 | 169.30 | 207.07 | 0.00 | 0.00 |
September | 452.11 | 153.21 | 444.94 | 260.72 | 184.22 | 0.00 | 0.00 |
October | 303.41 | 184.56 | 305.65 | 178.67 | 126.98 | 0.00 | 0.00 |
November | 206.90 | 211.95 | 216.61 | 131.75 | 84.86 | 0.00 | 0.00 |
December | 160.50 | 259.58 | 171.66 | 109.96 | 61.70 | 0.00 | 0.00 |
Annual Sum or Average | 264.33 | 175.05 | 298.06 | 141.40 | 156.67 | 0.00 | 0.00 |
Minimum of Months | 131.05 | 111.29 | 171.66 | 54.59 | 61.70 | 0.00 | 0.00 |
Maximum of Months | 452.11 | 259.58 | 444.94 | 260.72 | 224.69 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 478.19 | 447.73 | 496.14 | 321.12 | 175.02 | 0.00 | 0.00 |
February | 575.65 | 435.66 | 606.13 | 369.88 | 236.25 | 0.00 | 0.00 |
March | 265.56 | 366.67 | 374.81 | 109.18 | 265.63 | 0.00 | 0.00 |
April | 711.94 | 309.95 | 778.24 | 351.80 | 426.44 | 0.00 | 0.00 |
May | 478.26 | 272.65 | 643.52 | 209.44 | 434.08 | 0.00 | 0.00 |
June | 438.36 | 223.71 | 592.82 | 143.43 | 449.39 | 0.00 | 0.00 |
July | 510.46 | 214.84 | 642.31 | 201.08 | 441.23 | 0.00 | 0.00 |
August | 696.21 | 237.74 | 752.74 | 338.60 | 414.14 | 0.00 | 0.00 |
September | 908.74 | 297.09 | 889.88 | 521.44 | 368.44 | 0.00 | 0.00 |
October | 612.88 | 354.73 | 611.31 | 357.34 | 253.97 | 0.00 | 0.00 |
November | 416.38 | 414.09 | 433.21 | 263.49 | 169.72 | 0.00 | 0.00 |
December | 323.70 | 505.34 | 343.32 | 219.92 | 123.40 | 0.00 | 0.00 |
Annual Sum or Average | 533.43 | 339.55 | 596.12 | 282.79 | 313.33 | 0.00 | 0.00 |
Minimum of Months | 265.56 | 214.84 | 343.32 | 109.18 | 123.40 | 0.00 | 0.00 |
Maximum of Months | 908.74 | 505.34 | 889.88 | 521.44 | 449.39 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 239.06 | 223.41 | 248.07 | 160.56 | 87.51 | 0.00 | 0.00 |
February | 287.86 | 217.44 | 303.07 | 184.94 | 118.13 | 0.00 | 0.00 |
March | 132.85 | 182.56 | 187.41 | 54.59 | 132.81 | 0.00 | 0.00 |
April | 356.20 | 154.43 | 389.12 | 175.90 | 213.22 | 0.00 | 0.00 |
May | 239.35 | 136.11 | 321.76 | 104.72 | 217.04 | 0.00 | 0.00 |
June | 219.22 | 111.88 | 296.41 | 71.72 | 224.69 | 0.00 | 0.00 |
July | 255.61 | 107.06 | 321.15 | 100.54 | 220.61 | 0.00 | 0.00 |
August | 348.48 | 118.36 | 376.37 | 169.30 | 207.07 | 0.00 | 0.00 |
September | 454.34 | 148.58 | 444.94 | 260.72 | 184.22 | 0.00 | 0.00 |
October | 306.37 | 176.88 | 305.65 | 178.67 | 126.98 | 0.00 | 0.00 |
November | 208.30 | 206.44 | 216.61 | 131.75 | 84.86 | 0.00 | 0.00 |
December | 161.82 | 252.83 | 171.66 | 109.96 | 61.70 | 0.00 | 0.00 |
Annual Sum or Average | 266.83 | 169.43 | 298.06 | 141.40 | 156.67 | 0.00 | 0.00 |
Minimum of Months | 132.85 | 107.06 | 171.66 | 54.59 | 61.70 | 0.00 | 0.00 |
Maximum of Months | 454.34 | 252.83 | 444.94 | 260.72 | 224.69 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 239.31 | 222.37 | 248.07 | 160.56 | 87.51 | 0.00 | 0.00 |
February | 288.14 | 216.40 | 303.07 | 184.94 | 118.13 | 0.00 | 0.00 |
March | 133.15 | 181.59 | 187.41 | 54.59 | 132.81 | 0.00 | 0.00 |
April | 356.77 | 153.47 | 389.12 | 175.90 | 213.22 | 0.00 | 0.00 |
May | 240.06 | 135.09 | 321.76 | 104.72 | 217.04 | 0.00 | 0.00 |
June | 220.15 | 110.83 | 296.41 | 71.72 | 224.69 | 0.00 | 0.00 |
July | 256.27 | 106.28 | 321.15 | 100.54 | 220.61 | 0.00 | 0.00 |
August | 348.87 | 117.77 | 376.37 | 169.30 | 207.07 | 0.00 | 0.00 |
September | 454.87 | 147.71 | 444.94 | 260.72 | 184.22 | 0.00 | 0.00 |
October | 306.86 | 175.63 | 305.65 | 178.67 | 126.98 | 0.00 | 0.00 |
November | 208.53 | 205.39 | 216.61 | 131.75 | 84.86 | 0.00 | 0.00 |
December | 161.98 | 251.79 | 171.66 | 109.96 | 61.70 | 0.00 | 0.00 |
Annual Sum or Average | 267.29 | 168.46 | 298.06 | 141.40 | 156.67 | 0.00 | 0.00 |
Minimum of Months | 133.15 | 106.28 | 171.66 | 54.59 | 61.70 | 0.00 | 0.00 |
Maximum of Months | 454.87 | 251.79 | 444.94 | 260.72 | 224.69 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 239.92 | 219.30 | 248.07 | 160.56 | 87.51 | 0.00 | 0.00 |
February | 288.88 | 213.25 | 303.07 | 184.94 | 118.13 | 0.00 | 0.00 |
March | 133.88 | 178.71 | 187.41 | 54.59 | 132.81 | 0.00 | 0.00 |
April | 358.03 | 150.84 | 389.12 | 175.90 | 213.22 | 0.00 | 0.00 |
May | 241.75 | 132.18 | 321.76 | 104.72 | 217.04 | 0.00 | 0.00 |
June | 222.46 | 107.86 | 296.41 | 71.72 | 224.69 | 0.00 | 0.00 |
July | 257.86 | 104.12 | 321.15 | 100.54 | 220.61 | 0.00 | 0.00 |
August | 349.79 | 116.09 | 376.37 | 169.30 | 207.07 | 0.00 | 0.00 |
September | 456.25 | 145.04 | 444.94 | 260.72 | 184.22 | 0.00 | 0.00 |
October | 307.99 | 172.37 | 305.65 | 178.67 | 126.98 | 0.00 | 0.00 |
November | 209.05 | 202.53 | 216.61 | 131.75 | 84.86 | 0.00 | 0.00 |
December | 162.40 | 248.56 | 171.66 | 109.96 | 61.70 | 0.00 | 0.00 |
Annual Sum or Average | 268.39 | 165.67 | 298.06 | 141.40 | 156.67 | 0.00 | 0.00 |
Minimum of Months | 133.88 | 104.12 | 171.66 | 54.59 | 61.70 | 0.00 | 0.00 |
Maximum of Months | 456.25 | 248.56 | 444.94 | 260.72 | 224.69 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 242.04 | 208.47 | 248.07 | 160.56 | 87.51 | 0.00 | 0.00 |
February | 291.48 | 201.64 | 303.07 | 184.94 | 118.13 | 0.00 | 0.00 |
March | 136.44 | 168.43 | 187.41 | 54.59 | 132.81 | 0.00 | 0.00 |
April | 360.95 | 142.39 | 389.12 | 175.90 | 213.22 | 0.00 | 0.00 |
May | 245.73 | 122.91 | 321.76 | 104.72 | 217.04 | 0.00 | 0.00 |
June | 227.33 | 99.64 | 296.41 | 71.72 | 224.69 | 0.00 | 0.00 |
July | 261.43 | 97.38 | 321.15 | 100.54 | 220.61 | 0.00 | 0.00 |
August | 352.26 | 109.84 | 376.37 | 169.30 | 207.07 | 0.00 | 0.00 |
September | 459.29 | 137.03 | 444.94 | 260.72 | 184.22 | 0.00 | 0.00 |
October | 310.45 | 163.05 | 305.65 | 178.67 | 126.98 | 0.00 | 0.00 |
November | 210.77 | 192.57 | 216.61 | 131.75 | 84.86 | 0.00 | 0.00 |
December | 163.86 | 236.69 | 171.66 | 109.96 | 61.70 | 0.00 | 0.00 |
Annual Sum or Average | 271.21 | 156.45 | 298.06 | 141.40 | 156.67 | 0.00 | 0.00 |
Minimum of Months | 136.44 | 97.38 | 171.66 | 54.59 | 61.70 | 0.00 | 0.00 |
Maximum of Months | 459.29 | 236.69 | 444.94 | 260.72 | 224.69 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.127797E+10 | 0.123097E+10 | 0.133159E+10 | 0.861863E+09 | 0.469725E+09 | 0.00 | 0.00 |
February | 0.139148E+10 | 0.107673E+10 | 0.146938E+10 | 0.896661E+09 | 0.572716E+09 | 0.00 | 0.00 |
March | 0.708835E+09 | 0.100303E+10 | 0.100596E+10 | 0.293038E+09 | 0.712924E+09 | 0.00 | 0.00 |
April | 0.184374E+10 | 0.815616E+09 | 0.202136E+10 | 0.913739E+09 | 0.110762E+10 | 0.00 | 0.00 |
May | 0.127693E+10 | 0.741699E+09 | 0.172715E+10 | 0.562129E+09 | 0.116502E+10 | 0.00 | 0.00 |
June | 0.112935E+10 | 0.590153E+09 | 0.153976E+10 | 0.372543E+09 | 0.116722E+10 | 0.00 | 0.00 |
July | 0.136711E+10 | 0.577160E+09 | 0.172389E+10 | 0.539676E+09 | 0.118422E+10 | 0.00 | 0.00 |
August | 0.186977E+10 | 0.632434E+09 | 0.202028E+10 | 0.908771E+09 | 0.111151E+10 | 0.00 | 0.00 |
September | 0.235739E+10 | 0.773734E+09 | 0.231132E+10 | 0.135435E+10 | 0.956967E+09 | 0.00 | 0.00 |
October | 0.163928E+10 | 0.969295E+09 | 0.164069E+10 | 0.959064E+09 | 0.681625E+09 | 0.00 | 0.00 |
November | 0.107781E+10 | 0.109929E+10 | 0.112520E+10 | 0.684381E+09 | 0.440817E+09 | 0.00 | 0.00 |
December | 0.863928E+09 | 0.139275E+10 | 0.921433E+09 | 0.590245E+09 | 0.331188E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.168036E+11 | 0.109029E+11 | 0.188380E+11 | 0.893646E+10 | 0.990155E+10 | 0.00 | 0.00 |
Minimum of Months | 0.708835E+09 | 0.577160E+09 | 0.921433E+09 | 0.293038E+09 | 0.331188E+09 | 0.00 | 0.00 |
Maximum of Months | 0.235739E+10 | 0.139275E+10 | 0.231132E+10 | 0.135435E+10 | 0.118422E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.633948E+09 | 0.644754E+09 | 0.665794E+09 | 0.430932E+09 | 0.234862E+09 | 0.00 | 0.00 |
February | 0.690549E+09 | 0.565661E+09 | 0.734689E+09 | 0.448330E+09 | 0.286358E+09 | 0.00 | 0.00 |
March | 0.348151E+09 | 0.530019E+09 | 0.502981E+09 | 0.146519E+09 | 0.356462E+09 | 0.00 | 0.00 |
April | 0.907602E+09 | 0.440021E+09 | 0.101068E+10 | 0.456869E+09 | 0.553810E+09 | 0.00 | 0.00 |
May | 0.622937E+09 | 0.402756E+09 | 0.863575E+09 | 0.281065E+09 | 0.582511E+09 | 0.00 | 0.00 |
June | 0.553467E+09 | 0.310618E+09 | 0.769879E+09 | 0.186272E+09 | 0.583608E+09 | 0.00 | 0.00 |
July | 0.677639E+09 | 0.297995E+09 | 0.861947E+09 | 0.269838E+09 | 0.592109E+09 | 0.00 | 0.00 |
August | 0.931538E+09 | 0.323065E+09 | 0.101014E+10 | 0.454385E+09 | 0.555756E+09 | 0.00 | 0.00 |
September | 0.117321E+10 | 0.398826E+09 | 0.115566E+10 | 0.677176E+09 | 0.478483E+09 | 0.00 | 0.00 |
October | 0.809107E+09 | 0.521497E+09 | 0.820345E+09 | 0.479532E+09 | 0.340813E+09 | 0.00 | 0.00 |
November | 0.534336E+09 | 0.580155E+09 | 0.562599E+09 | 0.342191E+09 | 0.220409E+09 | 0.00 | 0.00 |
December | 0.428723E+09 | 0.728852E+09 | 0.460717E+09 | 0.295123E+09 | 0.165594E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.831121E+10 | 0.574422E+10 | 0.941900E+10 | 0.446823E+10 | 0.495077E+10 | 0.00 | 0.00 |
Minimum of Months | 0.348151E+09 | 0.297995E+09 | 0.460717E+09 | 0.146519E+09 | 0.165594E+09 | 0.00 | 0.00 |
Maximum of Months | 0.117321E+10 | 0.728852E+09 | 0.115566E+10 | 0.677176E+09 | 0.592109E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.633446E+09 | 0.627302E+09 | 0.664427E+09 | 0.430047E+09 | 0.234380E+09 | 0.00 | 0.00 |
February | 0.689630E+09 | 0.550571E+09 | 0.733180E+09 | 0.447410E+09 | 0.285770E+09 | 0.00 | 0.00 |
March | 0.348421E+09 | 0.515075E+09 | 0.501948E+09 | 0.146218E+09 | 0.355730E+09 | 0.00 | 0.00 |
April | 0.906442E+09 | 0.431478E+09 | 0.100860E+10 | 0.455931E+09 | 0.552672E+09 | 0.00 | 0.00 |
May | 0.622107E+09 | 0.395852E+09 | 0.861802E+09 | 0.280488E+09 | 0.581314E+09 | 0.00 | 0.00 |
June | 0.550473E+09 | 0.314193E+09 | 0.768298E+09 | 0.185889E+09 | 0.582409E+09 | 0.00 | 0.00 |
July | 0.674223E+09 | 0.303938E+09 | 0.860177E+09 | 0.269284E+09 | 0.590893E+09 | 0.00 | 0.00 |
August | 0.928456E+09 | 0.330144E+09 | 0.100807E+10 | 0.453452E+09 | 0.554615E+09 | 0.00 | 0.00 |
September | 0.116957E+10 | 0.403663E+09 | 0.115329E+10 | 0.675785E+09 | 0.477501E+09 | 0.00 | 0.00 |
October | 0.807936E+09 | 0.511160E+09 | 0.818660E+09 | 0.478547E+09 | 0.340113E+09 | 0.00 | 0.00 |
November | 0.534216E+09 | 0.562279E+09 | 0.561444E+09 | 0.341488E+09 | 0.219956E+09 | 0.00 | 0.00 |
December | 0.428113E+09 | 0.710090E+09 | 0.459771E+09 | 0.294517E+09 | 0.165254E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.829304E+10 | 0.565575E+10 | 0.939966E+10 | 0.445906E+10 | 0.494061E+10 | 0.00 | 0.00 |
Minimum of Months | 0.348421E+09 | 0.303938E+09 | 0.459771E+09 | 0.146218E+09 | 0.165254E+09 | 0.00 | 0.00 |
Maximum of Months | 0.116957E+10 | 0.710090E+09 | 0.115329E+10 | 0.675785E+09 | 0.590893E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.634623E+09 | 0.619625E+09 | 0.664427E+09 | 0.430047E+09 | 0.234380E+09 | 0.00 | 0.00 |
February | 0.690675E+09 | 0.544228E+09 | 0.733180E+09 | 0.447410E+09 | 0.285770E+09 | 0.00 | 0.00 |
March | 0.349611E+09 | 0.508432E+09 | 0.501948E+09 | 0.146218E+09 | 0.355730E+09 | 0.00 | 0.00 |
April | 0.909224E+09 | 0.424519E+09 | 0.100860E+10 | 0.455931E+09 | 0.552672E+09 | 0.00 | 0.00 |
May | 0.625079E+09 | 0.389255E+09 | 0.861802E+09 | 0.280488E+09 | 0.581314E+09 | 0.00 | 0.00 |
June | 0.551887E+09 | 0.311199E+09 | 0.768298E+09 | 0.185889E+09 | 0.582409E+09 | 0.00 | 0.00 |
July | 0.674998E+09 | 0.301999E+09 | 0.860177E+09 | 0.269284E+09 | 0.590893E+09 | 0.00 | 0.00 |
August | 0.928808E+09 | 0.328805E+09 | 0.100807E+10 | 0.453452E+09 | 0.554615E+09 | 0.00 | 0.00 |
September | 0.117014E+10 | 0.401339E+09 | 0.115329E+10 | 0.675785E+09 | 0.477501E+09 | 0.00 | 0.00 |
October | 0.809706E+09 | 0.503332E+09 | 0.818660E+09 | 0.478547E+09 | 0.340113E+09 | 0.00 | 0.00 |
November | 0.535232E+09 | 0.554793E+09 | 0.561444E+09 | 0.341488E+09 | 0.219956E+09 | 0.00 | 0.00 |
December | 0.428912E+09 | 0.702005E+09 | 0.459771E+09 | 0.294517E+09 | 0.165254E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.830890E+10 | 0.558953E+10 | 0.939966E+10 | 0.445906E+10 | 0.494061E+10 | 0.00 | 0.00 |
Minimum of Months | 0.349611E+09 | 0.301999E+09 | 0.459771E+09 | 0.146218E+09 | 0.165254E+09 | 0.00 | 0.00 |
Maximum of Months | 0.117014E+10 | 0.702005E+09 | 0.115329E+10 | 0.675785E+09 | 0.590893E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.635888E+09 | 0.613762E+09 | 0.664427E+09 | 0.430047E+09 | 0.234380E+09 | 0.00 | 0.00 |
February | 0.691872E+09 | 0.539383E+09 | 0.733180E+09 | 0.447410E+09 | 0.285770E+09 | 0.00 | 0.00 |
March | 0.351007E+09 | 0.503306E+09 | 0.501948E+09 | 0.146218E+09 | 0.355730E+09 | 0.00 | 0.00 |
April | 0.913445E+09 | 0.416897E+09 | 0.100860E+10 | 0.455931E+09 | 0.552672E+09 | 0.00 | 0.00 |
May | 0.629852E+09 | 0.381377E+09 | 0.861802E+09 | 0.280488E+09 | 0.581314E+09 | 0.00 | 0.00 |
June | 0.556037E+09 | 0.305262E+09 | 0.768298E+09 | 0.185889E+09 | 0.582409E+09 | 0.00 | 0.00 |
July | 0.677318E+09 | 0.298082E+09 | 0.860177E+09 | 0.269284E+09 | 0.590893E+09 | 0.00 | 0.00 |
August | 0.929922E+09 | 0.326072E+09 | 0.100807E+10 | 0.453452E+09 | 0.554615E+09 | 0.00 | 0.00 |
September | 0.117187E+10 | 0.397119E+09 | 0.115329E+10 | 0.675785E+09 | 0.477501E+09 | 0.00 | 0.00 |
October | 0.812663E+09 | 0.494321E+09 | 0.818660E+09 | 0.478547E+09 | 0.340113E+09 | 0.00 | 0.00 |
November | 0.536272E+09 | 0.549379E+09 | 0.561444E+09 | 0.341488E+09 | 0.219956E+09 | 0.00 | 0.00 |
December | 0.429879E+09 | 0.695269E+09 | 0.459771E+09 | 0.294517E+09 | 0.165254E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.833603E+10 | 0.552023E+10 | 0.939966E+10 | 0.445906E+10 | 0.494061E+10 | 0.00 | 0.00 |
Minimum of Months | 0.351007E+09 | 0.298082E+09 | 0.459771E+09 | 0.146218E+09 | 0.165254E+09 | 0.00 | 0.00 |
Maximum of Months | 0.117187E+10 | 0.695269E+09 | 0.115329E+10 | 0.675785E+09 | 0.590893E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.128078E+10 | 0.119919E+10 | 0.132885E+10 | 0.860093E+09 | 0.468760E+09 | 0.00 | 0.00 |
February | 0.139261E+10 | 0.105395E+10 | 0.146636E+10 | 0.894820E+09 | 0.571540E+09 | 0.00 | 0.00 |
March | 0.711266E+09 | 0.982079E+09 | 0.100390E+10 | 0.292436E+09 | 0.711460E+09 | 0.00 | 0.00 |
April | 0.184534E+10 | 0.803392E+09 | 0.201721E+10 | 0.911862E+09 | 0.110534E+10 | 0.00 | 0.00 |
May | 0.128097E+10 | 0.730268E+09 | 0.172360E+10 | 0.560975E+09 | 0.116263E+10 | 0.00 | 0.00 |
June | 0.113623E+10 | 0.579861E+09 | 0.153660E+10 | 0.371778E+09 | 0.116482E+10 | 0.00 | 0.00 |
July | 0.136721E+10 | 0.575427E+09 | 0.172035E+10 | 0.538568E+09 | 0.118179E+10 | 0.00 | 0.00 |
August | 0.186472E+10 | 0.636766E+09 | 0.201614E+10 | 0.906905E+09 | 0.110923E+10 | 0.00 | 0.00 |
September | 0.235545E+10 | 0.770069E+09 | 0.230657E+10 | 0.135157E+10 | 0.955002E+09 | 0.00 | 0.00 |
October | 0.164153E+10 | 0.950105E+09 | 0.163732E+10 | 0.957094E+09 | 0.680226E+09 | 0.00 | 0.00 |
November | 0.107924E+10 | 0.107333E+10 | 0.112289E+10 | 0.682976E+09 | 0.439912E+09 | 0.00 | 0.00 |
December | 0.866992E+09 | 0.135349E+10 | 0.919541E+09 | 0.589033E+09 | 0.330508E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.168223E+11 | 0.107079E+11 | 0.187993E+11 | 0.891811E+10 | 0.988122E+10 | 0.00 | 0.00 |
Minimum of Months | 0.711266E+09 | 0.575427E+09 | 0.919541E+09 | 0.292436E+09 | 0.330508E+09 | 0.00 | 0.00 |
Maximum of Months | 0.235545E+10 | 0.135349E+10 | 0.230657E+10 | 0.135157E+10 | 0.118179E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.640310E+09 | 0.598380E+09 | 0.664427E+09 | 0.430047E+09 | 0.234380E+09 | 0.00 | 0.00 |
February | 0.696379E+09 | 0.526043E+09 | 0.733180E+09 | 0.447410E+09 | 0.285770E+09 | 0.00 | 0.00 |
March | 0.355824E+09 | 0.488978E+09 | 0.501948E+09 | 0.146218E+09 | 0.355730E+09 | 0.00 | 0.00 |
April | 0.923278E+09 | 0.400290E+09 | 0.100860E+10 | 0.455931E+09 | 0.552672E+09 | 0.00 | 0.00 |
May | 0.641073E+09 | 0.364558E+09 | 0.861802E+09 | 0.280488E+09 | 0.581314E+09 | 0.00 | 0.00 |
June | 0.568218E+09 | 0.289995E+09 | 0.768298E+09 | 0.185889E+09 | 0.582409E+09 | 0.00 | 0.00 |
July | 0.684632E+09 | 0.286762E+09 | 0.860177E+09 | 0.269284E+09 | 0.590893E+09 | 0.00 | 0.00 |
August | 0.933380E+09 | 0.317006E+09 | 0.100807E+10 | 0.453452E+09 | 0.554615E+09 | 0.00 | 0.00 |
September | 0.117764E+10 | 0.385126E+09 | 0.115329E+10 | 0.675785E+09 | 0.477501E+09 | 0.00 | 0.00 |
October | 0.820578E+09 | 0.473757E+09 | 0.818660E+09 | 0.478547E+09 | 0.340113E+09 | 0.00 | 0.00 |
November | 0.539926E+09 | 0.535080E+09 | 0.561444E+09 | 0.341488E+09 | 0.219956E+09 | 0.00 | 0.00 |
December | 0.433418E+09 | 0.677190E+09 | 0.459771E+09 | 0.294517E+09 | 0.165254E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.841465E+10 | 0.534316E+10 | 0.939966E+10 | 0.445906E+10 | 0.494061E+10 | 0.00 | 0.00 |
Minimum of Months | 0.355824E+09 | 0.286762E+09 | 0.459771E+09 | 0.146218E+09 | 0.165254E+09 | 0.00 | 0.00 |
Maximum of Months | 0.117764E+10 | 0.677190E+09 | 0.115329E+10 | 0.675785E+09 | 0.590893E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.640973E+09 | 0.595589E+09 | 0.664427E+09 | 0.430047E+09 | 0.234380E+09 | 0.00 | 0.00 |
February | 0.697079E+09 | 0.523525E+09 | 0.733180E+09 | 0.447410E+09 | 0.285770E+09 | 0.00 | 0.00 |
March | 0.356637E+09 | 0.486371E+09 | 0.501948E+09 | 0.146218E+09 | 0.355730E+09 | 0.00 | 0.00 |
April | 0.924748E+09 | 0.397805E+09 | 0.100860E+10 | 0.455931E+09 | 0.552672E+09 | 0.00 | 0.00 |
May | 0.642966E+09 | 0.361815E+09 | 0.861802E+09 | 0.280488E+09 | 0.581314E+09 | 0.00 | 0.00 |
June | 0.570628E+09 | 0.287276E+09 | 0.768298E+09 | 0.185889E+09 | 0.582409E+09 | 0.00 | 0.00 |
July | 0.686394E+09 | 0.284672E+09 | 0.860177E+09 | 0.269284E+09 | 0.590893E+09 | 0.00 | 0.00 |
August | 0.934417E+09 | 0.315442E+09 | 0.100807E+10 | 0.453452E+09 | 0.554615E+09 | 0.00 | 0.00 |
September | 0.117901E+10 | 0.382872E+09 | 0.115329E+10 | 0.675785E+09 | 0.477501E+09 | 0.00 | 0.00 |
October | 0.821907E+09 | 0.470418E+09 | 0.818660E+09 | 0.478547E+09 | 0.340113E+09 | 0.00 | 0.00 |
November | 0.540516E+09 | 0.532374E+09 | 0.561444E+09 | 0.341488E+09 | 0.219956E+09 | 0.00 | 0.00 |
December | 0.433839E+09 | 0.674398E+09 | 0.459771E+09 | 0.294517E+09 | 0.165254E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.842912E+10 | 0.531256E+10 | 0.939966E+10 | 0.445906E+10 | 0.494061E+10 | 0.00 | 0.00 |
Minimum of Months | 0.356637E+09 | 0.284672E+09 | 0.459771E+09 | 0.146218E+09 | 0.165254E+09 | 0.00 | 0.00 |
Maximum of Months | 0.117901E+10 | 0.674398E+09 | 0.115329E+10 | 0.675785E+09 | 0.590893E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.642607E+09 | 0.587369E+09 | 0.664427E+09 | 0.430047E+09 | 0.234380E+09 | 0.00 | 0.00 |
February | 0.698865E+09 | 0.515898E+09 | 0.733180E+09 | 0.447410E+09 | 0.285770E+09 | 0.00 | 0.00 |
March | 0.358578E+09 | 0.478669E+09 | 0.501948E+09 | 0.146218E+09 | 0.355730E+09 | 0.00 | 0.00 |
April | 0.928009E+09 | 0.390990E+09 | 0.100860E+10 | 0.455931E+09 | 0.552672E+09 | 0.00 | 0.00 |
May | 0.647507E+09 | 0.354018E+09 | 0.861802E+09 | 0.280488E+09 | 0.581314E+09 | 0.00 | 0.00 |
June | 0.576604E+09 | 0.279575E+09 | 0.768298E+09 | 0.185889E+09 | 0.582409E+09 | 0.00 | 0.00 |
July | 0.690642E+09 | 0.278886E+09 | 0.860177E+09 | 0.269284E+09 | 0.590893E+09 | 0.00 | 0.00 |
August | 0.936866E+09 | 0.310935E+09 | 0.100807E+10 | 0.453452E+09 | 0.554615E+09 | 0.00 | 0.00 |
September | 0.118259E+10 | 0.375955E+09 | 0.115329E+10 | 0.675785E+09 | 0.477501E+09 | 0.00 | 0.00 |
October | 0.824912E+09 | 0.461679E+09 | 0.818660E+09 | 0.478547E+09 | 0.340113E+09 | 0.00 | 0.00 |
November | 0.541859E+09 | 0.524965E+09 | 0.561444E+09 | 0.341488E+09 | 0.219956E+09 | 0.00 | 0.00 |
December | 0.434965E+09 | 0.665755E+09 | 0.459771E+09 | 0.294517E+09 | 0.165254E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.846401E+10 | 0.522469E+10 | 0.939966E+10 | 0.445906E+10 | 0.494061E+10 | 0.00 | 0.00 |
Minimum of Months | 0.358578E+09 | 0.278886E+09 | 0.459771E+09 | 0.146218E+09 | 0.165254E+09 | 0.00 | 0.00 |
Maximum of Months | 0.118259E+10 | 0.665755E+09 | 0.115329E+10 | 0.675785E+09 | 0.590893E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.648289E+09 | 0.558358E+09 | 0.664427E+09 | 0.430047E+09 | 0.234380E+09 | 0.00 | 0.00 |
February | 0.705142E+09 | 0.487801E+09 | 0.733180E+09 | 0.447410E+09 | 0.285770E+09 | 0.00 | 0.00 |
March | 0.365451E+09 | 0.451124E+09 | 0.501948E+09 | 0.146218E+09 | 0.355730E+09 | 0.00 | 0.00 |
April | 0.935577E+09 | 0.369065E+09 | 0.100860E+10 | 0.455931E+09 | 0.552672E+09 | 0.00 | 0.00 |
May | 0.658150E+09 | 0.329209E+09 | 0.861802E+09 | 0.280488E+09 | 0.581314E+09 | 0.00 | 0.00 |
June | 0.589237E+09 | 0.258265E+09 | 0.768298E+09 | 0.185889E+09 | 0.582409E+09 | 0.00 | 0.00 |
July | 0.700214E+09 | 0.260833E+09 | 0.860177E+09 | 0.269284E+09 | 0.590893E+09 | 0.00 | 0.00 |
August | 0.943492E+09 | 0.294195E+09 | 0.100807E+10 | 0.453452E+09 | 0.554615E+09 | 0.00 | 0.00 |
September | 0.119048E+10 | 0.355182E+09 | 0.115329E+10 | 0.675785E+09 | 0.477501E+09 | 0.00 | 0.00 |
October | 0.831514E+09 | 0.436707E+09 | 0.818660E+09 | 0.478547E+09 | 0.340113E+09 | 0.00 | 0.00 |
November | 0.546312E+09 | 0.499142E+09 | 0.561444E+09 | 0.341488E+09 | 0.219956E+09 | 0.00 | 0.00 |
December | 0.438893E+09 | 0.633938E+09 | 0.459771E+09 | 0.294517E+09 | 0.165254E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.855275E+10 | 0.493382E+10 | 0.939966E+10 | 0.445906E+10 | 0.494061E+10 | 0.00 | 0.00 |
Minimum of Months | 0.365451E+09 | 0.258265E+09 | 0.459771E+09 | 0.146218E+09 | 0.165254E+09 | 0.00 | 0.00 |
Maximum of Months | 0.119048E+10 | 0.633938E+09 | 0.115329E+10 | 0.675785E+09 | 0.590893E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 4.18 | 3.24 | 2.03 | 1.05 | -4.0 | 28.28 | 62.93 | 0.00 |
February | 4.25 | 3.55 | 2.74 | 1.60 | -5.0 | 43.80 | 86.73 | 0.02 |
March | 5.90 | 4.45 | 2.76 | 1.18 | -2.0 | 68.95 | 35.00 | 0.00 |
April | 8.96 | 6.23 | 3.38 | 1.56 | -0.7 | 96.13 | 186.12 | 0.00 |
May | 9.99 | 8.06 | 6.28 | 3.35 | -0.9 | 110.92 | 199.68 | 0.02 |
June | 13.31 | 11.26 | 9.70 | 3.33 | 3.35 | 121.69 | 199.28 | 0.00 |
July | 15.02 | 12.39 | 10.49 | 3.21 | 4.48 | 111.91 | 220.83 | 0.00 |
August | 15.65 | 12.74 | 10.65 | 2.92 | 3.94 | 91.47 | 211.91 | 0.00 |
September | 13.43 | 11.01 | 9.10 | 2.64 | 1.42 | 68.72 | 198.32 | 0.01 |
October | 9.33 | 8.03 | 6.81 | 1.97 | -1.0 | 48.92 | 91.86 | 0.04 |
November | 6.66 | 5.65 | 4.54 | 2.05 | -2.3 | 30.27 | 53.24 | 0.04 |
December | 4.10 | 3.14 | 1.95 | 2.36 | -5.1 | 20.52 | 40.74 | 0.04 |
Annual Sum or Average | 9.26 | 7.50 | 5.89 | 2.27 | -0.6 | 70.25 | 132.30 | 0.02 |
Minimum of Months | 4.10 | 3.14 | 1.95 | 1.05 | -5.1 | 20.52 | 35.00 | 0.00 |
Maximum of Months | 15.65 | 12.74 | 10.65 | 3.35 | 4.48 | 121.69 | 220.83 | 0.04 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 14.00 | 29-JAN-05:00 | 9.36 | 5.00 | 3.60 | 8.35 | 0.00 | 0.00 |
February | 11.00 | 07-FEB-14:00 | 9.86 | 9.00 | 2.10 | 6.35 | 138.00 | 225.00 |
March | 14.00 | 25-MAR-12:00 | 11.21 | 9.00 | 2.60 | 7.35 | 287.00 | 93.00 |
April | 24.00 | 30-APR-14:00 | 13.10 | 4.00 | 1.50 | 7.75 | 167.50 | 716.00 |
May | 24.00 | 22-MAY-14:00 | 16.06 | 11.00 | 2.60 | 9.33 | 159.00 | 769.00 |
June | 27.00 | 13-JUN-16:00 | 17.51 | 12.00 | 3.10 | 12.41 | 141.50 | 652.50 |
July | 30.00 | 22-JUL-17:00 | 16.77 | 8.00 | 0.00 | 14.28 | 122.00 | 407.00 |
August | 27.00 | 14-AUG-17:19 | 14.15 | 3.33 | 2.60 | 10.37 | 133.00 | 358.83 |
September | 23.00 | 11-SEP-16:00 | 16.21 | 12.00 | 2.60 | 8.74 | 108.00 | 325.50 |
October | 19.00 | 07-OCT-14:00 | 10.08 | 1.00 | 1.50 | 2.22 | 131.00 | 540.50 |
November | 16.00 | 24-NOV-11:00 | 12.00 | 9.00 | 4.10 | 9.33 | 61.50 | 0.00 |
December | 13.00 | 23-DEC-10:00 | 7.62 | 2.00 | 7.70 | 6.75 | 70.50 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 11.00 | 7.62 | 1.00 | 0.00 | 2.22 | 0.00 | 0.00 | |
Maximum of Months | 30.00 | 17.51 | 12.00 | 7.70 | 14.28 | 287.00 | 769.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -6.0 | 10-JAN-07:00 | -6.9 | -9.0 | 0.00 | -20.0 | 0.00 | 0.00 |
February | -4.0 | 17-FEB-06:00 | -4.0 | -4.0 | 0.00 | -20.5 | 0.00 | 0.00 |
March | -1.0 | 08-MAR-06:00 | -1.4 | -2.0 | 0.00 | -14.4 | 17.50 | 184.50 |
April | 0.00 | 08-APR-04:00 | -0.8 | -2.0 | 0.00 | -12.7 | 0.00 | 0.00 |
May | 2.00 | 06-MAY-04:00 | 1.57 | 1.00 | 3.60 | -13.7 | 12.50 | 117.00 |
June | 6.00 | 01-JUN-03:00 | 5.04 | 4.00 | 0.00 | -9.2 | 0.00 | 0.00 |
July | 7.00 | 05-JUL-04:00 | 6.47 | 6.00 | 3.10 | -7.8 | 28.00 | 155.00 |
August | 8.00 | 20-AUG-04:00 | 7.45 | 7.00 | 0.00 | -6.6 | 0.00 | 0.00 |
September | 5.00 | 20-SEP-03:00 | 5.00 | 5.00 | 2.60 | -10.0 | 0.00 | 0.00 |
October | 2.00 | 07-OCT-03:00 | 2.00 | 2.00 | 0.00 | -13.4 | 0.00 | 0.00 |
November | -2.0 | 29-NOV-01:00 | -2.0 | -2.0 | 3.10 | -10.7 | 0.00 | 0.00 |
December | -3.0 | 29-DEC-20:00 | -4.4 | -7.0 | 3.60 | -20.2 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -6.0 | -6.9 | -9.0 | 0.00 | -20.5 | 0.00 | 0.00 | |
Maximum of Months | 8.00 | 7.45 | 7.00 | 3.60 | -6.6 | 28.00 | 184.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 12.44 | 29-JAN-04:00 | 13.00 | 12.00 | 0.00 | 9.13 | 0.00 | 0.00 |
February | 9.86 | 07-FEB-14:00 | 11.00 | 9.00 | 2.10 | 6.35 | 138.00 | 225.00 |
March | 12.00 | 19-MAR-11:00 | 12.00 | 12.00 | 2.60 | 8.15 | 131.00 | 0.00 |
April | 15.39 | 28-APR-07:00 | 16.00 | 15.00 | 0.00 | 5.54 | 119.50 | 626.00 |
May | 16.06 | 22-MAY-14:00 | 24.00 | 11.00 | 2.60 | 9.33 | 159.00 | 769.00 |
June | 19.93 | 25-JUN-17:00 | 22.00 | 19.00 | 0.00 | 15.94 | 136.50 | 360.50 |
July | 17.29 | 22-JUL-09:00 | 26.00 | 12.00 | 4.60 | 11.46 | 224.50 | 619.50 |
August | 17.04 | 14-AUG-12:00 | 24.00 | 13.00 | 2.60 | 9.91 | 205.50 | 669.50 |
September | 16.53 | 10-SEP-15:00 | 21.00 | 14.00 | 3.60 | 8.54 | 160.50 | 483.00 |
October | 13.58 | 17-OCT-14:00 | 16.00 | 12.00 | 0.00 | 12.03 | 144.00 | 44.50 |
November | 12.00 | 24-NOV-11:00 | 16.00 | 9.00 | 4.10 | 9.33 | 61.50 | 0.00 |
December | 7.93 | 02-DEC-12:00 | 9.00 | 7.00 | 0.00 | 2.01 | 135.50 | 84.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 7.93 | 9.00 | 7.00 | 0.00 | 2.01 | 0.00 | 0.00 | |
Maximum of Months | 19.93 | 26.00 | 19.00 | 4.60 | 15.94 | 224.50 | 769.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 12.00 | 29-JAN-04:00 | 13.00 | 12.44 | 0.00 | 9.13 | 0.00 | 0.00 |
February | 9.00 | 07-FEB-14:00 | 11.00 | 9.86 | 2.10 | 6.35 | 138.00 | 225.00 |
March | 12.00 | 19-MAR-11:00 | 12.00 | 12.00 | 2.60 | 8.15 | 131.00 | 0.00 |
April | 15.00 | 28-APR-07:00 | 16.00 | 15.39 | 0.00 | 5.54 | 119.50 | 626.00 |
May | 12.00 | 23-MAY-07:00 | 17.00 | 13.94 | 3.10 | 5.13 | 112.00 | 719.50 |
June | 19.00 | 25-JUN-17:00 | 22.00 | 19.93 | 0.00 | 15.94 | 136.50 | 360.50 |
July | 14.00 | 17-JUL-17:00 | 18.00 | 15.44 | 3.60 | 9.91 | 120.00 | 0.00 |
August | 16.00 | 08-AUG-12:00 | 18.00 | 16.70 | 1.50 | 11.46 | 154.00 | 0.00 |
September | 14.00 | 10-SEP-15:00 | 21.00 | 16.53 | 3.60 | 8.54 | 160.50 | 483.00 |
October | 13.00 | 17-OCT-18:00 | 13.00 | 13.00 | 2.60 | 9.33 | 0.00 | 0.00 |
November | 12.00 | 08-NOV-14:00 | 12.00 | 12.00 | 0.00 | 8.15 | 93.00 | 106.00 |
December | 7.00 | 02-DEC-11:00 | 8.00 | 7.45 | 3.10 | 1.16 | 144.50 | 146.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 7.00 | 8.00 | 7.45 | 0.00 | 1.16 | 0.00 | 0.00 | |
Maximum of Months | 19.00 | 22.00 | 19.93 | 3.60 | 15.94 | 160.50 | 719.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 10.33 | 8.85 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 10.00 | 14.79 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 10.33 | 17.09 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 11.26 | 40.86 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 12.54 | 47.73 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 13.82 | 50.98 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 14.77 | 51.67 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 15.12 | 44.67 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 14.78 | 34.25 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 13.84 | 17.71 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 12.55 | 9.34 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 11.27 | 6.14 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 12.57 | 28.73 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 10.00 | 6.14 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 15.12 | 51.67 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK1
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.362153E+09 | -238918783.8 | 0.00 | 0.00 | 744.00 | 0.00 | -123233936.9 | 58.99 | 0.00 | 0.00 |
February | 0.329901E+09 | -218405119.4 | 0.00 | 0.00 | 672.00 | 0.00 | -111496238.5 | 58.99 | 0.00 | 0.00 |
March | 0.367071E+09 | -243940278.1 | 0.00 | 0.00 | 744.00 | 0.00 | -123130260.3 | 58.99 | 0.00 | 0.00 |
April | 0.345671E+09 | -228938879.2 | 0.00 | 0.00 | 720.00 | 0.00 | -116731639.8 | 58.99 | 0.00 | 0.00 |
May | 0.350191E+09 | -230429440.5 | 0.00 | 0.00 | 744.00 | 0.00 | -119761517.1 | 58.99 | 0.00 | 0.00 |
June | 0.330335E+09 | -218893949.2 | 0.00 | 0.00 | 720.00 | 0.00 | -111441429.0 | 58.99 | 0.00 | 0.00 |
July | 0.330949E+09 | -217252266.6 | 0.00 | 0.00 | 744.00 | 0.00 | -113696621.2 | 58.99 | 0.00 | 0.00 |
August | 0.332910E+09 | -219768178.0 | 0.00 | 0.00 | 744.00 | 0.00 | -113142256.2 | 58.99 | 0.00 | 0.00 |
September | 0.322626E+09 | -212230192.4 | 0.00 | 0.00 | 720.00 | 0.00 | -110395455.9 | 58.99 | 0.00 | 0.00 |
October | 0.342047E+09 | -221704726.9 | 0.00 | 0.00 | 744.00 | 0.00 | -120342391.2 | 58.99 | 0.00 | 0.00 |
November | 0.338857E+09 | -220046087.6 | 0.00 | 0.00 | 720.00 | 0.00 | -118811159.2 | 58.99 | 0.00 | 0.00 |
December | 0.358188E+09 | -234598248.2 | 0.00 | 0.00 | 744.00 | 0.00 | -123589971.2 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.411090E+10 | -.270513E+10 | 8760.00 | -.140577E+10 | 58.99 | |||||
Minimum of Months | 0.322626E+09 | -243940278.1 | 0.00 | 0.00 | 672.00 | 0.00 | -123589971.2 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.367071E+09 | -212230192.4 | 0.00 | 0.00 | 744.00 | 0.00 | -110395455.9 | 58.99 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK2
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.360175E+09 | -238919280.7 | 0.00 | 0.00 | 744.00 | 0.00 | -121255739.5 | 58.99 | 0.00 | 0.00 |
February | 0.328040E+09 | -218404472.8 | 0.00 | 0.00 | 672.00 | 0.00 | -109635895.6 | 58.99 | 0.00 | 0.00 |
March | 0.364970E+09 | -243937221.4 | 0.00 | 0.00 | 744.00 | 0.00 | -121032452.6 | 58.99 | 0.00 | 0.00 |
April | 0.342482E+09 | -228941264.4 | 0.00 | 0.00 | 720.00 | 0.00 | -113540742.6 | 58.99 | 0.00 | 0.00 |
May | 0.347000E+09 | -230443583.5 | 0.00 | 0.00 | 744.00 | 0.00 | -116556335.5 | 58.99 | 0.00 | 0.00 |
June | 0.328688E+09 | -218893149.3 | 0.00 | 0.00 | 720.00 | 0.00 | -109794452.6 | 58.99 | 0.00 | 0.00 |
July | 0.330116E+09 | -217250226.7 | 0.00 | 0.00 | 744.00 | 0.00 | -112865947.4 | 58.99 | 0.00 | 0.00 |
August | 0.332454E+09 | -219767443.8 | 0.00 | 0.00 | 744.00 | 0.00 | -112686403.8 | 58.99 | 0.00 | 0.00 |
September | 0.321690E+09 | -212235375.1 | 0.00 | 0.00 | 720.00 | 0.00 | -109454799.5 | 58.99 | 0.00 | 0.00 |
October | 0.338844E+09 | -221712952.2 | 0.00 | 0.00 | 744.00 | 0.00 | -117131296.1 | 58.99 | 0.00 | 0.00 |
November | 0.336652E+09 | -220053210.5 | 0.00 | 0.00 | 720.00 | 0.00 | -116598800.9 | 58.99 | 0.00 | 0.00 |
December | 0.356245E+09 | -234597051.8 | 0.00 | 0.00 | 744.00 | 0.00 | -121648257.9 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.408736E+10 | -.270516E+10 | 8760.00 | -.138220E+10 | 58.99 | |||||
Minimum of Months | 0.321690E+09 | -243937221.4 | 0.00 | 0.00 | 672.00 | 0.00 | -121648257.9 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.364970E+09 | -212235375.1 | 0.00 | 0.00 | 744.00 | 0.00 | -109454799.5 | 58.99 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK3
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.332860E+09 | -210101805.0 | 0.00 | 0.00 | 744.00 | 0.00 | -122758501.4 | 58.99 | 0.00 | 0.00 |
February | 0.303144E+09 | -192218031.5 | 0.00 | 0.00 | 672.00 | 0.00 | -110926017.8 | 58.99 | 0.00 | 0.00 |
March | 0.340311E+09 | -217866043.4 | 0.00 | 0.00 | 744.00 | 0.00 | -122444610.1 | 59.00 | 0.00 | 0.00 |
April | 0.315562E+09 | -201198826.3 | 0.00 | 0.00 | 720.00 | 0.00 | -114363157.2 | 58.99 | 0.00 | 0.00 |
May | 0.321573E+09 | -204357770.8 | 0.00 | 0.00 | 744.00 | 0.00 | -117215272.1 | 58.99 | 0.00 | 0.00 |
June | 0.304422E+09 | -195102383.8 | 0.00 | 0.00 | 720.00 | 0.00 | -109319160.2 | 58.99 | 0.00 | 0.00 |
July | 0.301895E+09 | -189792624.9 | 0.00 | 0.00 | 744.00 | 0.00 | -112102783.1 | 58.99 | 0.00 | 0.00 |
August | 0.308328E+09 | -196433655.7 | 0.00 | 0.00 | 744.00 | 0.00 | -111894166.6 | 58.99 | 0.00 | 0.00 |
September | 0.295261E+09 | -186375654.0 | 0.00 | 0.00 | 720.00 | 0.00 | -108884947.0 | 58.99 | 0.00 | 0.00 |
October | 0.313073E+09 | -194981922.1 | 0.00 | 0.00 | 744.00 | 0.00 | -118091047.2 | 58.99 | 0.00 | 0.00 |
November | 0.312430E+09 | -194311516.7 | 0.00 | 0.00 | 720.00 | 0.00 | -118118514.5 | 58.98 | 0.00 | 0.00 |
December | 0.327960E+09 | -204786941.4 | 0.00 | 0.00 | 744.00 | 0.00 | -123173097.4 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.377682E+10 | -.238753E+10 | 8760.00 | -.138929E+10 | 58.99 | |||||
Minimum of Months | 0.295261E+09 | -217866043.4 | 0.00 | 0.00 | 672.00 | 0.00 | -123173097.4 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.340311E+09 | -186375654.0 | 0.00 | 0.00 | 744.00 | 0.00 | -108884947.0 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK4
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.333294E+09 | -210100454.2 | 0.00 | 0.00 | 744.00 | 0.00 | -123193606.5 | 58.99 | 0.00 | 0.00 |
February | 0.303504E+09 | -192210182.2 | 0.00 | 0.00 | 672.00 | 0.00 | -111293752.4 | 58.99 | 0.00 | 0.00 |
March | 0.340699E+09 | -217869187.8 | 0.00 | 0.00 | 744.00 | 0.00 | -122829501.9 | 59.00 | 0.00 | 0.00 |
April | 0.316125E+09 | -201210358.1 | 0.00 | 0.00 | 720.00 | 0.00 | -114914273.0 | 58.99 | 0.00 | 0.00 |
May | 0.322115E+09 | -204351800.4 | 0.00 | 0.00 | 744.00 | 0.00 | -117762985.7 | 58.99 | 0.00 | 0.00 |
June | 0.304657E+09 | -195099358.6 | 0.00 | 0.00 | 720.00 | 0.00 | -109558089.7 | 58.99 | 0.00 | 0.00 |
July | 0.302036E+09 | -189793658.3 | 0.00 | 0.00 | 744.00 | 0.00 | -112241911.2 | 58.99 | 0.00 | 0.00 |
August | 0.308413E+09 | -196441023.7 | 0.00 | 0.00 | 744.00 | 0.00 | -111971935.6 | 58.99 | 0.00 | 0.00 |
September | 0.295404E+09 | -186377018.9 | 0.00 | 0.00 | 720.00 | 0.00 | -109026648.3 | 58.99 | 0.00 | 0.00 |
October | 0.313615E+09 | -194983757.5 | 0.00 | 0.00 | 744.00 | 0.00 | -118631602.0 | 58.99 | 0.00 | 0.00 |
November | 0.312845E+09 | -194320338.2 | 0.00 | 0.00 | 720.00 | 0.00 | -118524254.8 | 58.98 | 0.00 | 0.00 |
December | 0.328378E+09 | -204803512.1 | 0.00 | 0.00 | 744.00 | 0.00 | -123574632.6 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.378108E+10 | -.238756E+10 | 8760.00 | -.139352E+10 | 58.99 | |||||
Minimum of Months | 0.295404E+09 | -217869187.8 | 0.00 | 0.00 | 672.00 | 0.00 | -123574632.6 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.340699E+09 | -186377018.9 | 0.00 | 0.00 | 744.00 | 0.00 | -109026648.3 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK5
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.322983E+09 | -198568585.9 | 0.00 | 0.00 | 744.00 | 0.00 | -124414219.7 | 59.00 | 0.00 | 0.00 |
February | 0.294112E+09 | -181760805.7 | 0.00 | 0.00 | 672.00 | 0.00 | -112351094.8 | 59.00 | 0.00 | 0.00 |
March | 0.330090E+09 | -206164865.5 | 0.00 | 0.00 | 744.00 | 0.00 | -123925337.1 | 58.99 | 0.00 | 0.00 |
April | 0.307609E+09 | -190388298.4 | 0.00 | 0.00 | 720.00 | 0.00 | -117221080.7 | 58.99 | 0.00 | 0.00 |
May | 0.313518E+09 | -193260637.6 | 0.00 | 0.00 | 744.00 | 0.00 | -120257565.7 | 58.99 | 0.00 | 0.00 |
June | 0.296602E+09 | -184615251.2 | 0.00 | 0.00 | 720.00 | 0.00 | -111986784.7 | 58.99 | 0.00 | 0.00 |
July | 0.293165E+09 | -179502574.8 | 0.00 | 0.00 | 744.00 | 0.00 | -113662518.9 | 58.99 | 0.00 | 0.00 |
August | 0.298676E+09 | -185907482.0 | 0.00 | 0.00 | 744.00 | 0.00 | -112768185.3 | 58.98 | 0.00 | 0.00 |
September | 0.286892E+09 | -176382146.0 | 0.00 | 0.00 | 720.00 | 0.00 | -110510193.7 | 58.99 | 0.00 | 0.00 |
October | 0.305294E+09 | -184274484.4 | 0.00 | 0.00 | 744.00 | 0.00 | -121019556.8 | 58.99 | 0.00 | 0.00 |
November | 0.303123E+09 | -183503531.4 | 0.00 | 0.00 | 720.00 | 0.00 | -119619939.7 | 58.99 | 0.00 | 0.00 |
December | 0.318609E+09 | -193672163.1 | 0.00 | 0.00 | 744.00 | 0.00 | -124936826.4 | 59.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.367067E+10 | -.225800E+10 | 8760.00 | -.141267E+10 | 58.99 | |||||
Minimum of Months | 0.286892E+09 | -206164865.5 | 0.00 | 0.00 | 672.00 | 0.00 | -124936826.4 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.330090E+09 | -176382146.0 | 0.00 | 0.00 | 744.00 | 0.00 | -110510193.7 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK6
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.323217E+09 | -198568134.1 | 0.00 | 0.00 | 744.00 | 0.00 | -124648653.2 | 59.00 | 0.00 | 0.00 |
February | 0.294324E+09 | -181790339.9 | 0.00 | 0.00 | 672.00 | 0.00 | -112533858.5 | 58.98 | 0.00 | 0.00 |
March | 0.330353E+09 | -206146561.1 | 0.00 | 0.00 | 744.00 | 0.00 | -124206481.1 | 59.00 | 0.00 | 0.00 |
April | 0.307718E+09 | -190395053.2 | 0.00 | 0.00 | 720.00 | 0.00 | -117322877.4 | 58.99 | 0.00 | 0.00 |
May | 0.313545E+09 | -193267176.6 | 0.00 | 0.00 | 744.00 | 0.00 | -120277752.8 | 58.99 | 0.00 | 0.00 |
June | 0.296526E+09 | -184610293.7 | 0.00 | 0.00 | 720.00 | 0.00 | -111915830.6 | 58.99 | 0.00 | 0.00 |
July | 0.293250E+09 | -179486122.3 | 0.00 | 0.00 | 744.00 | 0.00 | -113764245.6 | 59.00 | 0.00 | 0.00 |
August | 0.298855E+09 | -185821473.8 | 0.00 | 0.00 | 744.00 | 0.00 | -113033084.7 | 59.01 | 0.00 | 0.00 |
September | 0.286874E+09 | -176371278.0 | 0.00 | 0.00 | 720.00 | 0.00 | -110502933.7 | 58.99 | 0.00 | 0.00 |
October | 0.305387E+09 | -184277363.6 | 0.00 | 0.00 | 744.00 | 0.00 | -121109883.6 | 58.99 | 0.00 | 0.00 |
November | 0.303379E+09 | -183502689.2 | 0.00 | 0.00 | 720.00 | 0.00 | -119876402.3 | 58.99 | 0.00 | 0.00 |
December | 0.318787E+09 | -193677959.8 | 0.00 | 0.00 | 744.00 | 0.00 | -125108696.0 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.367222E+10 | -.225791E+10 | 8760.00 | -.141430E+10 | 58.99 | |||||
Minimum of Months | 0.286874E+09 | -206146561.1 | 0.00 | 0.00 | 672.00 | 0.00 | -125108696.0 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.330353E+09 | -176371278.0 | 0.00 | 0.00 | 744.00 | 0.00 | -110502933.7 | 59.01 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK7
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.323358E+09 | -198568204.7 | 0.00 | 0.00 | 744.00 | 0.00 | -124790019.7 | 59.00 | 0.00 | 0.00 |
February | 0.294447E+09 | -181777724.3 | 0.00 | 0.00 | 672.00 | 0.00 | -112669038.3 | 58.99 | 0.00 | 0.00 |
March | 0.330485E+09 | -206170577.9 | 0.00 | 0.00 | 744.00 | 0.00 | -124314646.4 | 58.99 | 0.00 | 0.00 |
April | 0.307911E+09 | -190391435.1 | 0.00 | 0.00 | 720.00 | 0.00 | -117519823.9 | 58.99 | 0.00 | 0.00 |
May | 0.313788E+09 | -193258018.2 | 0.00 | 0.00 | 744.00 | 0.00 | -120530414.6 | 58.99 | 0.00 | 0.00 |
June | 0.296813E+09 | -184610964.5 | 0.00 | 0.00 | 720.00 | 0.00 | -112202000.9 | 58.99 | 0.00 | 0.00 |
July | 0.293447E+09 | -179481688.5 | 0.00 | 0.00 | 744.00 | 0.00 | -113965661.8 | 59.00 | 0.00 | 0.00 |
August | 0.298962E+09 | -185850600.7 | 0.00 | 0.00 | 744.00 | 0.00 | -113111884.8 | 59.00 | 0.00 | 0.00 |
September | 0.287061E+09 | -176380669.0 | 0.00 | 0.00 | 720.00 | 0.00 | -110680578.7 | 58.99 | 0.00 | 0.00 |
October | 0.305629E+09 | -184291972.0 | 0.00 | 0.00 | 744.00 | 0.00 | -121337464.8 | 58.99 | 0.00 | 0.00 |
November | 0.303503E+09 | -183504098.7 | 0.00 | 0.00 | 720.00 | 0.00 | -119999208.1 | 58.99 | 0.00 | 0.00 |
December | 0.318910E+09 | -193682393.1 | 0.00 | 0.00 | 744.00 | 0.00 | -125228087.5 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.367432E+10 | -.225797E+10 | 8760.00 | -.141635E+10 | 58.99 | |||||
Minimum of Months | 0.287061E+09 | -206170577.9 | 0.00 | 0.00 | 672.00 | 0.00 | -125228087.5 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.330485E+09 | -176380669.0 | 0.00 | 0.00 | 744.00 | 0.00 | -110680578.7 | 59.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 195.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 217.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 215.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 359.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 417.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 410.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 429.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 396.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 337.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 234.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 171.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 131.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3515.67 | ||||||||||
Minimum of Months | 131.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 429.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.108710E+11 | 48043.16 | 02-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.913340E+10 | 48043.16 | 01-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.815840E+10 | 48043.16 | 01-MAR-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.182140E+10 | 48043.16 | 01-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.111799E+10 | 26755.90 | 05-MAY-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 9478823.64 | 1929.91 | 07-JUN-11:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.181199E+10 | 26314.96 | 23-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.675364E+10 | 48043.16 | 03-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.119089E+11 | 48043.16 | 01-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.515862E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.119089E+11 | 48043.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.290151E+10 | 25950.08 | 01-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.218904E+10 | 25950.08 | 01-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.178094E+10 | 25950.08 | 01-MAR-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.158866E+09 | 25950.08 | 01-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 37001487.38 | 25950.08 | 05-MAY-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.135913E+09 | 25950.08 | 19-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.138197E+10 | 25950.08 | 01-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.331628E+10 | 25950.08 | 01-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.119015E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.331628E+10 | 25950.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_3:3_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.353423E+10 | 21034.99 | 10-JAN-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.275348E+10 | 16100.48 | 19-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.230920E+10 | 10527.70 | 05-MAR-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.242161E+09 | 5025.29 | 10-APR-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 39070328.48 | 2980.30 | 06-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.228820E+09 | 4790.80 | 28-OCT-07:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.185495E+10 | 8816.56 | 29-NOV-09:37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.394084E+10 | 28280.11 | 31-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.149028E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.394084E+10 | 28280.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_4:4_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.377227E+10 | 25470.39 | 10-JAN-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.295457E+10 | 22348.48 | 19-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.252262E+10 | 16430.33 | 05-MAR-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.318811E+09 | 5835.00 | 08-APR-07:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 72084816.61 | 2958.41 | 06-MAY-07:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.323890E+09 | 4319.02 | 23-OCT-07:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.208228E+10 | 12229.86 | 20-NOV-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.416397E+10 | 28166.81 | 31-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.162105E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.416397E+10 | 28166.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_5:5_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.408218E+10 | 28223.49 | 10-JAN-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.322458E+10 | 28223.49 | 19-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.281558E+10 | 22290.31 | 05-MAR-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.430065E+09 | 4993.20 | 03-APR-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.152408E+09 | 3554.84 | 06-MAY-07:17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.466506E+09 | 5763.36 | 24-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.235455E+10 | 16550.17 | 20-NOV-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.447819E+10 | 28223.49 | 17-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.180041E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.447819E+10 | 28223.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_6:6_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.981835E+10 | 46985.52 | 01-JAN-10:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.804127E+10 | 46985.52 | 01-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.761673E+10 | 46985.52 | 01-MAR-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.204423E+10 | 46985.52 | 01-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.139643E+10 | 26561.37 | 17-MAY-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 37378757.88 | 3377.67 | 08-JUN-08:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.232026E+10 | 46985.52 | 23-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.670180E+10 | 46985.52 | 03-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.104784E+11 | 46985.52 | 01-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.484549E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.104784E+11 | 46985.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_7:7_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.483444E+10 | 24906.92 | 01-JAN-10:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.389882E+10 | 24906.92 | 01-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.358246E+10 | 24906.92 | 01-MAR-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.844891E+09 | 24906.92 | 01-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.534573E+09 | 24906.92 | 03-MAY-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 11385856.93 | 17655.89 | 08-JUN-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.955016E+09 | 24906.92 | 11-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.310039E+10 | 24906.92 | 01-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.519482E+10 | 24906.92 | 01-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.229568E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.519482E+10 | 24906.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_8:8_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.496301E+10 | 24705.64 | 01-JAN-10:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.402146E+10 | 24705.64 | 01-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.371137E+10 | 24705.64 | 01-MAR-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.928565E+09 | 24705.64 | 01-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.608968E+09 | 24705.64 | 03-MAY-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 17847195.42 | 20584.52 | 08-JUN-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 236191.24 | 1574.61 | 05-JUL-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.103861E+10 | 24705.64 | 11-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.322245E+10 | 24705.64 | 01-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.531472E+10 | 24705.64 | 01-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.238272E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.531472E+10 | 24705.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_9:9_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.533435E+10 | 24329.32 | 01-JAN-10:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.437527E+10 | 24329.32 | 01-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.408471E+10 | 24329.32 | 01-MAR-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.114070E+10 | 24329.32 | 01-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.810874E+09 | 24329.32 | 03-MAY-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 40929539.95 | 24329.32 | 08-JUN-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 2044803.65 | 7288.21 | 05-JUL-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 486968.50 | 902.72 | 09-SEP-08:63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.125237E+10 | 24329.32 | 05-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.354156E+10 | 24329.32 | 01-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.567648E+10 | 24329.32 | 01-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.262598E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.567648E+10 | 24329.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_10:10_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.655977E+10 | 24076.10 | 01-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.549264E+10 | 24076.10 | 01-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.524779E+10 | 24076.10 | 01-MAR-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.170177E+10 | 24076.10 | 01-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.136104E+10 | 24076.10 | 02-MAY-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.135918E+09 | 24076.10 | 06-JUN-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 13716234.77 | 17195.92 | 05-JUL-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 22369855.24 | 9637.21 | 20-SEP-08:63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.184954E+10 | 24076.10 | 03-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.446671E+10 | 24076.10 | 01-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.694584E+10 | 24076.10 | 01-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.337971E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.694584E+10 | 24076.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.384286E+09 | 0.380781E+09 | 9821.08 | 30-APR-16:25 | 9821.08 | 0.00 |
May | 0.00 | 0.00 | 0.227228E+09 | 0.192675E+09 | 7753.41 | 22-MAY-15:00 | 7088.99 | 0.00 |
June | 0.00 | 0.00 | 0.163352E+10 | 0.134857E+10 | 26165.16 | 13-JUN-08:62 | 21827.20 | 0.00 |
July | 0.00 | 0.00 | 0.317575E+10 | 0.265671E+10 | 26303.57 | 18-JUL-08:62 | 17764.59 | 0.00 |
August | 0.00 | 0.00 | 0.345604E+10 | 0.279772E+10 | 17506.04 | 17-AUG-08:63 | 10225.25 | 0.00 |
September | 0.00 | 0.00 | 0.181040E+10 | 0.150176E+10 | 10867.62 | 13-SEP-14:00 | 9231.77 | 0.00 |
October | 0.00 | 0.00 | 2216916.08 | 2216916.08 | 998.89 | 07-OCT-15:00 | 998.89 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.106894E+11 | 0.888043E+10 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.345604E+10 | 0.279772E+10 | 26303.57 | 21827.20 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 5371755.68 | 4918034.27 | 339.20 | 19-MAR-19:20 | 298.97 | 0.00 |
April | 0.00 | 0.00 | 0.815421E+09 | 0.815361E+09 | 6054.06 | 30-APR-15:00 | 6054.06 | 0.00 |
May | 0.00 | 0.00 | 0.929560E+09 | 0.891095E+09 | 5128.80 | 22-MAY-15:00 | 4918.49 | 0.00 |
June | 0.00 | 0.00 | 0.286208E+10 | 0.263512E+10 | 14794.74 | 13-JUN-08:62 | 13250.97 | 0.00 |
July | 0.00 | 0.00 | 0.467754E+10 | 0.427168E+10 | 14834.07 | 10-JUL-08:62 | 13457.85 | 0.00 |
August | 0.00 | 0.00 | 0.533098E+10 | 0.484560E+10 | 14545.64 | 06-AUG-07:02 | 12338.40 | 0.00 |
September | 0.00 | 0.00 | 0.364735E+10 | 0.338121E+10 | 6508.39 | 13-SEP-14:00 | 5950.82 | 0.00 |
October | 0.00 | 0.00 | 0.477876E+09 | 0.469439E+09 | 3597.32 | 08-OCT-17:10 | 3096.47 | 0.00 |
November | 0.00 | 0.00 | 6051278.84 | 5796677.22 | 342.15 | 08-NOV-23:00 | 305.50 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.187522E+11 | 0.173202E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.533098E+10 | 0.484560E+10 | 14834.07 | 13457.85 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.118488E+09 | 0.118067E+09 | 14607.61 | 30-APR-08:62 | 13364.51 | 0.00 |
May | 0.00 | 0.00 | 73171871.00 | 67307010.65 | 5096.84 | 26-MAY-07:02 | 3627.64 | 0.00 |
June | 0.00 | 0.00 | 0.713698E+09 | 0.623233E+09 | 16303.21 | 27-JUN-07:02 | 9102.09 | 0.00 |
July | 0.00 | 0.00 | 0.103898E+10 | 0.936216E+09 | 16299.49 | 18-JUL-07:02 | 10705.75 | 0.00 |
August | 0.00 | 0.00 | 0.106186E+10 | 0.918787E+09 | 16199.51 | 17-AUG-07:02 | 9603.52 | 0.00 |
September | 0.00 | 0.00 | 0.689369E+09 | 0.606827E+09 | 15998.96 | 16-SEP-07:02 | 9675.66 | 0.00 |
October | 0.00 | 0.00 | 251974.47 | 251938.98 | 286.67 | 07-OCT-15:00 | 286.67 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.369582E+10 | 0.327069E+10 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.106186E+10 | 0.936216E+09 | 16303.21 | 13364.51 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.112864E+09 | 0.112526E+09 | 13412.22 | 30-APR-08:62 | 12292.71 | 0.00 |
May | 0.00 | 0.00 | 62704386.47 | 58146881.25 | 4499.82 | 22-MAY-15:00 | 4293.08 | 0.00 |
June | 0.00 | 0.00 | 0.692182E+09 | 0.605012E+09 | 16218.13 | 27-JUN-07:02 | 9047.52 | 0.00 |
July | 0.00 | 0.00 | 0.102038E+10 | 0.919760E+09 | 16214.05 | 18-JUL-07:02 | 10640.89 | 0.00 |
August | 0.00 | 0.00 | 0.104136E+10 | 0.901339E+09 | 16115.23 | 17-AUG-07:02 | 9548.43 | 0.00 |
September | 0.00 | 0.00 | 0.669324E+09 | 0.589725E+09 | 15914.84 | 16-SEP-07:02 | 9615.30 | 0.00 |
October | 0.00 | 0.00 | 142082.01 | 142075.01 | 195.44 | 07-OCT-15:00 | 195.44 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.359896E+10 | 0.318665E+10 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.104136E+10 | 0.919760E+09 | 16218.13 | 12292.71 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 98303783.01 | 98088807.59 | 9973.02 | 30-APR-08:62 | 9226.48 | 0.00 |
May | 0.00 | 0.00 | 49236592.07 | 46201084.68 | 4146.57 | 22-MAY-15:00 | 3953.78 | 0.00 |
June | 0.00 | 0.00 | 0.637387E+09 | 0.558388E+09 | 16255.75 | 27-JUN-07:02 | 9043.51 | 0.00 |
July | 0.00 | 0.00 | 0.948243E+09 | 0.858371E+09 | 16251.38 | 18-JUL-07:02 | 10640.82 | 0.00 |
August | 0.00 | 0.00 | 0.955442E+09 | 0.829857E+09 | 16152.67 | 17-AUG-07:02 | 9546.96 | 0.00 |
September | 0.00 | 0.00 | 0.605147E+09 | 0.534861E+09 | 15951.58 | 16-SEP-07:02 | 9614.07 | 0.00 |
October | 0.00 | 0.00 | 14097.91 | 14097.91 | 1.75 | 07-OCT-13:00 | 1.75 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.329377E+10 | 0.292578E+10 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.955442E+09 | 0.858371E+09 | 16255.75 | 10640.82 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.164890E+09 | 0.163420E+09 | 8330.64 | 30-APR-15:00 | 8330.64 | 0.00 |
May | 0.00 | 0.00 | 74397943.22 | 65621214.20 | 5960.45 | 22-MAY-15:00 | 5382.69 | 0.00 |
June | 0.00 | 0.00 | 0.105650E+10 | 0.883711E+09 | 22055.94 | 13-JUN-08:62 | 17622.18 | 0.00 |
July | 0.00 | 0.00 | 0.188379E+10 | 0.160471E+10 | 26155.05 | 18-JUL-08:62 | 17533.60 | 0.00 |
August | 0.00 | 0.00 | 0.224227E+10 | 0.183559E+10 | 17293.74 | 18-AUG-08:63 | 12693.74 | 0.00 |
September | 0.00 | 0.00 | 0.120868E+10 | 0.102048E+10 | 9880.33 | 13-SEP-14:10 | 8365.22 | 0.00 |
October | 0.00 | 0.00 | 640451.31 | 640451.31 | 581.51 | 07-OCT-15:00 | 581.51 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.663116E+10 | 0.557417E+10 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.224227E+10 | 0.183559E+10 | 26155.05 | 17622.18 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.174087E+09 | 0.174087E+09 | 4824.45 | 30-APR-15:00 | 4824.45 | 0.00 |
May | 0.00 | 0.00 | 0.141239E+09 | 0.127775E+09 | 3475.31 | 22-MAY-15:00 | 3278.01 | 0.00 |
June | 0.00 | 0.00 | 0.878821E+09 | 0.787228E+09 | 6468.12 | 13-JUN-16:30 | 5970.11 | 0.00 |
July | 0.00 | 0.00 | 0.197294E+10 | 0.175725E+10 | 13932.67 | 23-JUL-09:02 | 12450.26 | 0.00 |
August | 0.00 | 0.00 | 0.259996E+10 | 0.230675E+10 | 6178.36 | 14-AUG-17:00 | 6178.36 | 0.00 |
September | 0.00 | 0.00 | 0.130063E+10 | 0.117568E+10 | 5508.77 | 13-SEP-14:20 | 4975.02 | 0.00 |
October | 0.00 | 0.00 | 14844402.34 | 14844402.34 | 1762.21 | 07-OCT-15:00 | 1762.21 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.708252E+10 | 0.634361E+10 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.259996E+10 | 0.230675E+10 | 13932.67 | 12450.26 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.160966E+09 | 0.160966E+09 | 4700.45 | 30-APR-15:00 | 4700.45 | 0.00 |
May | 0.00 | 0.00 | 0.126422E+09 | 0.114298E+09 | 3349.05 | 22-MAY-15:00 | 3157.80 | 0.00 |
June | 0.00 | 0.00 | 0.823222E+09 | 0.736510E+09 | 6344.43 | 13-JUN-16:30 | 5854.20 | 0.00 |
July | 0.00 | 0.00 | 0.186723E+10 | 0.166279E+10 | 13792.48 | 23-JUL-09:02 | 12295.09 | 0.00 |
August | 0.00 | 0.00 | 0.247662E+10 | 0.219575E+10 | 6085.22 | 14-AUG-17:00 | 6085.22 | 0.00 |
September | 0.00 | 0.00 | 0.121582E+10 | 0.109773E+10 | 5400.47 | 13-SEP-14:20 | 4873.87 | 0.00 |
October | 0.00 | 0.00 | 11809029.94 | 11809029.94 | 1601.35 | 07-OCT-15:00 | 1601.35 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.668209E+10 | 0.597986E+10 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.247662E+10 | 0.219575E+10 | 13792.48 | 12295.09 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.133384E+09 | 0.133384E+09 | 4426.07 | 30-APR-15:00 | 4426.07 | 0.00 |
May | 0.00 | 0.00 | 96905738.78 | 87592061.12 | 3063.40 | 22-MAY-15:00 | 2886.15 | 0.00 |
June | 0.00 | 0.00 | 0.706132E+09 | 0.629821E+09 | 6091.37 | 13-JUN-16:30 | 5617.00 | 0.00 |
July | 0.00 | 0.00 | 0.163404E+10 | 0.145580E+10 | 13540.08 | 23-JUL-09:02 | 12003.29 | 0.00 |
August | 0.00 | 0.00 | 0.218565E+10 | 0.193545E+10 | 5875.03 | 14-AUG-17:00 | 5875.03 | 0.00 |
September | 0.00 | 0.00 | 0.103217E+10 | 0.929695E+09 | 5185.04 | 13-SEP-14:20 | 4673.16 | 0.00 |
October | 0.00 | 0.00 | 7135539.41 | 7135539.41 | 1252.20 | 07-OCT-15:00 | 1252.20 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.579541E+10 | 0.517888E+10 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.218565E+10 | 0.193545E+10 | 13540.08 | 12003.29 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.109004E+09 | 0.109004E+09 | 4046.40 | 30-APR-15:00 | 4046.40 | 0.00 |
May | 0.00 | 0.00 | 71647987.07 | 64936980.38 | 2726.76 | 22-MAY-15:00 | 2566.91 | 0.00 |
June | 0.00 | 0.00 | 0.593577E+09 | 0.528369E+09 | 5798.11 | 13-JUN-16:30 | 5340.43 | 0.00 |
July | 0.00 | 0.00 | 0.131501E+10 | 0.117965E+10 | 13525.15 | 23-JUL-09:02 | 11879.46 | 0.00 |
August | 0.00 | 0.00 | 0.173488E+10 | 0.153743E+10 | 5563.66 | 14-AUG-17:00 | 5563.66 | 0.00 |
September | 0.00 | 0.00 | 0.819906E+09 | 0.737416E+09 | 4916.12 | 13-SEP-14:10 | 4427.73 | 0.00 |
October | 0.00 | 0.00 | 2627227.06 | 2627227.06 | 723.87 | 07-OCT-15:00 | 723.87 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.464665E+10 | 0.415943E+10 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.173488E+10 | 0.153743E+10 | 13525.15 | 11879.46 | 0.00 |
Report: FanReportMonthly
For: PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.144831E+10 | 0.41 | 1680.89 | 02-JAN-09:01 | 0.89 |
February | 0.129547E+10 | 0.40 | 1680.89 | 01-FEB-09:01 | 0.88 |
March | 0.139361E+10 | 0.40 | 1680.89 | 01-MAR-09:01 | 0.89 |
April | 0.122185E+10 | 0.37 | 1680.89 | 01-APR-08:61 | 0.89 |
May | 0.124339E+10 | 0.37 | 1234.02 | 05-MAY-08:61 | 0.77 |
June | 0.118428E+10 | 0.36 | 1680.89 | 13-JUN-08:62 | 0.88 |
July | 0.122664E+10 | 0.36 | 1680.89 | 10-JUL-08:62 | 0.88 |
August | 0.122015E+10 | 0.36 | 1005.76 | 17-AUG-08:63 | 0.68 |
September | 0.118604E+10 | 0.36 | 672.36 | 14-SEP-16:40 | 0.53 |
October | 0.125796E+10 | 0.37 | 1224.77 | 23-OCT-08:61 | 0.76 |
November | 0.132058E+10 | 0.39 | 1680.89 | 03-NOV-08:61 | 0.89 |
December | 0.147487E+10 | 0.41 | 1680.89 | 01-DEC-09:01 | 0.89 |
Annual Sum or Average | 0.154731E+11 | 0.38 | |||
Minimum of Months | 0.118428E+10 | 0.36 | 672.36 | 0.53 | |
Maximum of Months | 0.147487E+10 | 0.41 | 1680.89 | 0.89 |
Report: FanReportMonthly
For: PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.132015E+10 | 0.46 | 972.70 | 01-JAN-17:20 | 0.92 |
February | 0.119409E+10 | 0.46 | 972.70 | 01-FEB-11:50 | 0.91 |
March | 0.134223E+10 | 0.49 | 972.70 | 01-MAR-19:10 | 0.92 |
April | 0.134448E+10 | 0.62 | 972.70 | 06-APR-09:20 | 0.92 |
May | 0.140897E+10 | 0.63 | 972.70 | 22-MAY-17:00 | 0.91 |
June | 0.145997E+10 | 0.65 | 972.70 | 08-JUN-16:20 | 0.91 |
July | 0.152746E+10 | 0.65 | 972.70 | 06-JUL-19:30 | 0.91 |
August | 0.154568E+10 | 0.64 | 972.70 | 01-AUG-15:40 | 0.91 |
September | 0.146044E+10 | 0.65 | 972.70 | 05-SEP-10:40 | 0.91 |
October | 0.137758E+10 | 0.60 | 972.70 | 05-OCT-13:20 | 0.92 |
November | 0.128286E+10 | 0.49 | 972.70 | 02-NOV-08:08 | 0.91 |
December | 0.131315E+10 | 0.46 | 972.70 | 02-DEC-16:40 | 0.91 |
Annual Sum or Average | 0.165771E+11 | 0.57 | |||
Minimum of Months | 0.119409E+10 | 0.46 | 972.70 | 0.91 | |
Maximum of Months | 0.154568E+10 | 0.65 | 972.70 | 0.92 |
Report: FanReportMonthly
For: PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.156016E+10 | 0.50 | 1078.05 | 15-JAN-12:20 | 0.92 |
February | 0.141268E+10 | 0.50 | 1078.05 | 03-FEB-11:10 | 0.92 |
March | 0.159121E+10 | 0.51 | 1078.05 | 01-MAR-18:10 | 0.92 |
April | 0.151359E+10 | 0.50 | 1078.05 | 08-APR-15:40 | 0.92 |
May | 0.157568E+10 | 0.50 | 1078.05 | 11-MAY-17:50 | 0.92 |
June | 0.153687E+10 | 0.50 | 1078.05 | 03-JUN-15:20 | 0.91 |
July | 0.155240E+10 | 0.49 | 1078.05 | 03-JUL-18:40 | 0.91 |
August | 0.159121E+10 | 0.50 | 1078.05 | 01-AUG-12:10 | 0.91 |
September | 0.151359E+10 | 0.49 | 1078.05 | 01-SEP-10:30 | 0.91 |
October | 0.156016E+10 | 0.49 | 1078.05 | 05-OCT-13:10 | 0.92 |
November | 0.151359E+10 | 0.50 | 1078.05 | 01-NOV-20:00 | 0.91 |
December | 0.155240E+10 | 0.49 | 1078.05 | 08-DEC-20:47 | 0.92 |
Annual Sum or Average | 0.184735E+11 | 0.50 | |||
Minimum of Months | 0.141268E+10 | 0.49 | 1078.05 | 0.91 | |
Maximum of Months | 0.159121E+10 | 0.51 | 1078.05 | 0.92 |
Report: FanReportMonthly
For: PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.155213E+10 | 0.50 | 1072.51 | 02-JAN-10:30 | 0.92 |
February | 0.140542E+10 | 0.50 | 1072.51 | 03-FEB-13:00 | 0.92 |
March | 0.158302E+10 | 0.51 | 1072.51 | 02-MAR-12:50 | 0.92 |
April | 0.150580E+10 | 0.50 | 1072.51 | 01-APR-11:30 | 0.92 |
May | 0.156758E+10 | 0.50 | 1072.51 | 04-MAY-14:00 | 0.91 |
June | 0.152897E+10 | 0.50 | 1072.51 | 03-JUN-15:20 | 0.91 |
July | 0.154441E+10 | 0.49 | 1072.51 | 01-JUL-13:20 | 0.91 |
August | 0.158302E+10 | 0.50 | 1072.51 | 01-AUG-08:65 | 0.91 |
September | 0.150580E+10 | 0.49 | 1072.51 | 01-SEP-13:50 | 0.91 |
October | 0.155213E+10 | 0.49 | 1072.51 | 07-OCT-15:30 | 0.92 |
November | 0.150580E+10 | 0.50 | 1072.51 | 01-NOV-09:50 | 0.92 |
December | 0.154441E+10 | 0.49 | 1072.51 | 01-DEC-19:00 | 0.92 |
Annual Sum or Average | 0.183785E+11 | 0.50 | |||
Minimum of Months | 0.140542E+10 | 0.49 | 1072.51 | 0.91 | |
Maximum of Months | 0.158302E+10 | 0.51 | 1072.51 | 0.92 |
Report: FanReportMonthly
For: PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.155615E+10 | 0.50 | 1075.28 | 01-JAN-09:30 | 0.92 |
February | 0.140905E+10 | 0.50 | 1075.28 | 01-FEB-14:10 | 0.91 |
March | 0.158712E+10 | 0.51 | 1075.28 | 01-MAR-13:00 | 0.92 |
April | 0.150970E+10 | 0.50 | 1075.28 | 01-APR-07:10 | 0.92 |
May | 0.157163E+10 | 0.50 | 1075.28 | 04-MAY-08:20 | 0.91 |
June | 0.153292E+10 | 0.50 | 1075.28 | 01-JUN-13:20 | 0.91 |
July | 0.154841E+10 | 0.49 | 1075.28 | 01-JUL-07:03 | 0.91 |
August | 0.158712E+10 | 0.50 | 1075.28 | 01-AUG-07:03 | 0.91 |
September | 0.150970E+10 | 0.49 | 1075.28 | 01-SEP-12:50 | 0.91 |
October | 0.155615E+10 | 0.49 | 1075.28 | 02-OCT-07:03 | 0.92 |
November | 0.150970E+10 | 0.50 | 1075.28 | 01-NOV-07:13 | 0.92 |
December | 0.154841E+10 | 0.49 | 1075.28 | 01-DEC-09:01 | 0.92 |
Annual Sum or Average | 0.184260E+11 | 0.50 | |||
Minimum of Months | 0.140905E+10 | 0.49 | 1075.28 | 0.91 | |
Maximum of Months | 0.158712E+10 | 0.51 | 1075.28 | 0.92 |
Report: FanReportMonthly
For: PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.110201E+10 | 0.31 | 1670.68 | 01-JAN-10:01 | 0.89 |
February | 0.979898E+09 | 0.30 | 1670.68 | 01-FEB-09:01 | 0.88 |
March | 0.107429E+10 | 0.30 | 1670.68 | 01-MAR-09:01 | 0.89 |
April | 0.909694E+09 | 0.28 | 1670.68 | 01-APR-08:61 | 0.89 |
May | 0.931960E+09 | 0.28 | 1234.94 | 17-MAY-08:61 | 0.77 |
June | 0.881518E+09 | 0.27 | 1358.23 | 13-JUN-08:62 | 0.80 |
July | 0.889464E+09 | 0.26 | 1670.68 | 18-JUL-08:62 | 0.88 |
August | 0.911939E+09 | 0.27 | 1003.80 | 18-AUG-08:63 | 0.68 |
September | 0.866081E+09 | 0.27 | 668.27 | 09-SEP-13:00 | 0.53 |
October | 0.942046E+09 | 0.28 | 1670.68 | 23-OCT-08:61 | 0.88 |
November | 0.100906E+10 | 0.30 | 1670.68 | 03-NOV-08:61 | 0.89 |
December | 0.111128E+10 | 0.31 | 1670.68 | 01-DEC-09:01 | 0.89 |
Annual Sum or Average | 0.116092E+11 | 0.28 | |||
Minimum of Months | 0.866081E+09 | 0.26 | 668.27 | 0.53 | |
Maximum of Months | 0.111128E+10 | 0.31 | 1670.68 | 0.89 |
Report: FanReportMonthly
For: PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.122785E+10 | 0.46 | 919.32 | 01-JAN-11:20 | 0.92 |
February | 0.111201E+10 | 0.46 | 919.32 | 01-FEB-10:10 | 0.91 |
March | 0.125432E+10 | 0.47 | 919.32 | 01-MAR-13:00 | 0.92 |
April | 0.119144E+10 | 0.46 | 919.32 | 01-APR-10:40 | 0.92 |
May | 0.124109E+10 | 0.46 | 919.32 | 03-MAY-11:20 | 0.91 |
June | 0.121130E+10 | 0.46 | 919.32 | 09-JUN-13:50 | 0.91 |
July | 0.122123E+10 | 0.45 | 919.32 | 07-JUL-17:40 | 0.91 |
August | 0.125432E+10 | 0.46 | 919.32 | 11-AUG-13:30 | 0.91 |
September | 0.119144E+10 | 0.46 | 919.32 | 09-SEP-11:00 | 0.91 |
October | 0.122785E+10 | 0.46 | 919.32 | 07-OCT-12:40 | 0.92 |
November | 0.119144E+10 | 0.46 | 919.32 | 01-NOV-08:10 | 0.92 |
December | 0.122123E+10 | 0.45 | 919.32 | 01-DEC-19:20 | 0.92 |
Annual Sum or Average | 0.145455E+11 | 0.46 | |||
Minimum of Months | 0.111201E+10 | 0.45 | 919.32 | 0.91 | |
Maximum of Months | 0.125432E+10 | 0.47 | 919.32 | 0.92 |
Report: FanReportMonthly
For: PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.121588E+10 | 0.46 | 910.36 | 02-JAN-11:40 | 0.92 |
February | 0.110117E+10 | 0.46 | 910.36 | 01-FEB-09:15 | 0.92 |
March | 0.124210E+10 | 0.47 | 910.36 | 01-MAR-20:30 | 0.92 |
April | 0.117983E+10 | 0.46 | 910.36 | 02-APR-14:00 | 0.92 |
May | 0.122899E+10 | 0.46 | 910.36 | 03-MAY-11:10 | 0.91 |
June | 0.119949E+10 | 0.46 | 910.36 | 08-JUN-08:30 | 0.92 |
July | 0.120932E+10 | 0.45 | 910.36 | 06-JUL-15:40 | 0.91 |
August | 0.124210E+10 | 0.46 | 910.36 | 01-AUG-10:40 | 0.91 |
September | 0.117983E+10 | 0.46 | 910.36 | 01-SEP-11:10 | 0.91 |
October | 0.121588E+10 | 0.46 | 910.36 | 04-OCT-08:30 | 0.92 |
November | 0.117983E+10 | 0.46 | 910.36 | 01-NOV-14:25 | 0.91 |
December | 0.120932E+10 | 0.45 | 910.36 | 04-DEC-19:10 | 0.92 |
Annual Sum or Average | 0.144037E+11 | 0.46 | |||
Minimum of Months | 0.110117E+10 | 0.45 | 910.36 | 0.91 | |
Maximum of Months | 0.124210E+10 | 0.47 | 910.36 | 0.92 |
Report: FanReportMonthly
For: PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.119456E+10 | 0.46 | 894.40 | 04-JAN-12:20 | 0.92 |
February | 0.108186E+10 | 0.46 | 894.40 | 01-FEB-11:20 | 0.91 |
March | 0.122032E+10 | 0.47 | 894.40 | 02-MAR-12:50 | 0.92 |
April | 0.115914E+10 | 0.46 | 894.40 | 08-APR-10:30 | 0.92 |
May | 0.120744E+10 | 0.46 | 894.40 | 02-MAY-08:62 | 0.92 |
June | 0.117846E+10 | 0.46 | 894.40 | 12-JUN-12:30 | 0.91 |
July | 0.118812E+10 | 0.45 | 894.40 | 09-JUL-14:20 | 0.91 |
August | 0.122032E+10 | 0.46 | 894.40 | 03-AUG-16:30 | 0.91 |
September | 0.115914E+10 | 0.46 | 894.40 | 12-SEP-16:30 | 0.91 |
October | 0.119456E+10 | 0.46 | 894.40 | 14-OCT-08:09 | 0.91 |
November | 0.115914E+10 | 0.46 | 894.40 | 03-NOV-08:30 | 0.92 |
December | 0.118812E+10 | 0.45 | 894.40 | 02-DEC-12:10 | 0.91 |
Annual Sum or Average | 0.141511E+11 | 0.46 | |||
Minimum of Months | 0.108186E+10 | 0.45 | 894.40 | 0.91 | |
Maximum of Months | 0.122032E+10 | 0.47 | 894.40 | 0.92 |
Report: FanReportMonthly
For: PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.119244E+10 | 0.46 | 892.81 | 01-JAN-12:40 | 0.92 |
February | 0.107995E+10 | 0.46 | 892.81 | 01-FEB-09:20 | 0.91 |
March | 0.121815E+10 | 0.47 | 892.81 | 02-MAR-09:04 | 0.92 |
April | 0.115708E+10 | 0.46 | 892.81 | 02-APR-08:05 | 0.92 |
May | 0.120530E+10 | 0.46 | 892.81 | 01-MAY-19:20 | 0.92 |
June | 0.117637E+10 | 0.46 | 892.81 | 06-JUN-09:00 | 0.91 |
July | 0.118601E+10 | 0.45 | 892.81 | 06-JUL-16:30 | 0.91 |
August | 0.121815E+10 | 0.46 | 892.81 | 05-AUG-13:10 | 0.91 |
September | 0.115708E+10 | 0.46 | 892.81 | 01-SEP-17:40 | 0.91 |
October | 0.119244E+10 | 0.46 | 892.81 | 02-OCT-09:00 | 0.91 |
November | 0.115708E+10 | 0.46 | 892.81 | 02-NOV-13:30 | 0.92 |
December | 0.118601E+10 | 0.45 | 892.81 | 01-DEC-12:40 | 0.92 |
Annual Sum or Average | 0.141261E+11 | 0.46 | |||
Minimum of Months | 0.107995E+10 | 0.45 | 892.81 | 0.91 | |
Maximum of Months | 0.121815E+10 | 0.47 | 892.81 | 0.92 |
Report: ZoneTemperatureOscillationReportMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.50 | 0.25 |
February | 1.00 | 0.71 |
March | 0.44 | 0.56 |
April | 0.42 | 0.50 |
May | 0.36 | 1.27 |
June | 1.22 | 1.50 |
July | 0.42 | 1.50 |
August | 0.00 | 0.00 |
September | 0.81 | 1.24 |
October | 0.64 | 0.85 |
November | 0.19 | 0.43 |
December | 0.78 | 1.23 |
Annual Sum or Average | 6.78 | 1.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 1.22 | 1.50 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 3.62 | 2.06 |
February | 3.72 | 2.59 |
March | 5.00 | 2.26 |
April | 4.00 | 1.86 |
May | 2.42 | 2.13 |
June | 0.83 | 0.40 |
July | 0.44 | 0.37 |
August | 0.50 | 0.67 |
September | 1.11 | 0.52 |
October | 3.50 | 1.78 |
November | 5.03 | 2.68 |
December | 3.33 | 0.55 |
Annual Sum or Average | 33.51 | 1.91 |
Minimum of Months | 0.44 | 0.37 |
Maximum of Months | 5.03 | 2.68 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 2.39 | 0.75 |
May | 2.64 | 0.73 |
June | 0.94 | 0.75 |
July | 0.84 | 0.75 |
August | 0.67 | 0.75 |
September | 0.94 | 0.75 |
October | 2.67 | 0.71 |
November | 0.69 | 0.75 |
December | 0.00 | 0.00 |
Annual Sum or Average | 11.78 | 0.74 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 2.67 | 0.75 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 2.03 | 0.75 |
May | 2.39 | 0.72 |
June | 1.36 | 0.75 |
July | 0.76 | 0.75 |
August | 0.83 | 0.75 |
September | 1.06 | 0.75 |
October | 2.08 | 0.72 |
November | 0.14 | 0.75 |
December | 0.06 | 0.75 |
Annual Sum or Average | 10.70 | 0.74 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 2.39 | 0.75 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 1.28 | 0.75 |
May | 1.75 | 0.71 |
June | 1.17 | 0.75 |
July | 0.59 | 0.75 |
August | 1.25 | 0.75 |
September | 1.56 | 0.75 |
October | 1.72 | 0.71 |
November | 0.06 | 0.75 |
December | 0.03 | 0.75 |
Annual Sum or Average | 9.40 | 0.74 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 1.75 | 0.75 |
Report: ZoneTemperatureOscillationReportMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.17 | 3.30 |
May | 0.28 | 2.31 |
June | 0.81 | 3.30 |
July | 0.67 | 3.30 |
August | 0.00 | 0.00 |
September | 0.42 | 3.30 |
October | 0.47 | 2.33 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 2.81 | 3.04 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.81 | 3.30 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 1.08 | 0.00 |
February | 0.78 | 0.00 |
March | 1.86 | 0.00 |
April | 2.06 | 0.07 |
May | 1.50 | 0.00 |
June | 0.83 | 0.00 |
July | 0.67 | 0.42 |
August | 0.33 | 0.00 |
September | 1.06 | 0.00 |
October | 2.44 | 0.00 |
November | 1.75 | 0.00 |
December | 0.69 | 0.00 |
Annual Sum or Average | 15.06 | 0.03 |
Minimum of Months | 0.33 | 0.00 |
Maximum of Months | 2.44 | 0.42 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 1.00 | 0.00 |
February | 0.50 | 0.00 |
March | 1.64 | 0.00 |
April | 1.97 | 0.00 |
May | 1.50 | 0.00 |
June | 0.72 | 0.00 |
July | 0.67 | 0.42 |
August | 0.33 | 0.00 |
September | 1.06 | 0.00 |
October | 2.44 | 0.00 |
November | 1.61 | 0.00 |
December | 0.53 | 0.00 |
Annual Sum or Average | 13.98 | 0.02 |
Minimum of Months | 0.33 | 0.00 |
Maximum of Months | 2.44 | 0.42 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.42 | 0.00 |
February | 0.25 | 0.00 |
March | 0.75 | 0.00 |
April | 1.81 | 0.00 |
May | 1.17 | 0.00 |
June | 0.61 | 0.00 |
July | 0.56 | 0.51 |
August | 0.33 | 0.00 |
September | 0.94 | 0.00 |
October | 2.14 | 0.00 |
November | 1.44 | 0.00 |
December | 0.06 | 0.00 |
Annual Sum or Average | 10.48 | 0.03 |
Minimum of Months | 0.06 | 0.00 |
Maximum of Months | 2.14 | 0.51 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.36 | 0.00 |
February | 0.08 | 0.00 |
March | 0.00 | 0.00 |
April | 0.11 | 0.00 |
May | 0.22 | 0.00 |
June | 0.17 | 0.00 |
July | 0.23 | 1.25 |
August | 0.00 | 0.00 |
September | 0.28 | 0.00 |
October | 0.64 | 0.00 |
November | 0.31 | 0.00 |
December | 0.33 | 0.00 |
Annual Sum or Average | 2.73 | 0.10 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.64 | 1.25 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_1:1
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.144831E+10 | 0.135888E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.129547E+10 | 0.114168E+11 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.139361E+10 | 0.101980E+11 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.131701E+10 | 0.227675E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.130253E+10 | 0.139749E+10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.157799E+10 | 11848529.55 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.201211E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.208742E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.163283E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.125858E+10 | 0.226498E+10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.132058E+10 | 0.844205E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.147487E+10 | 0.148862E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.181213E+11 | 0.644828E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.125858E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.208742E+10 | 0.148862E+11 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_2:2
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.132015E+10 | 0.362688E+10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.119409E+10 | 0.273631E+10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.134373E+10 | 0.222618E+10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.153452E+10 | 0.198582E+09 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.163196E+10 | 46251859.22 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.211081E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.256810E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.272137E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.228376E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.149786E+10 | 0.169891E+09 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.128455E+10 | 0.172746E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.131315E+10 | 0.414535E+10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.208041E+11 | 0.148769E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.119409E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.272137E+10 | 0.414535E+10 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_3:3
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.156016E+10 | 0.441779E+10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.141268E+10 | 0.344185E+10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.159121E+10 | 0.288651E+10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.153981E+10 | 0.302701E+09 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.159225E+10 | 48837910.60 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.169037E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.177953E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.182553E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.166492E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.156022E+10 | 0.286025E+09 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.151359E+10 | 0.231868E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.155240E+10 | 0.492605E+10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.192827E+11 | 0.186284E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.141268E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.182553E+10 | 0.492605E+10 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_4:4
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.155213E+10 | 0.471534E+10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.140542E+10 | 0.369321E+10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.158302E+10 | 0.315327E+10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.153081E+10 | 0.398514E+09 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.158184E+10 | 90106020.76 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.167812E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.176751E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.181292E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.165292E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.155217E+10 | 0.404862E+09 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.150580E+10 | 0.260285E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.154441E+10 | 0.520496E+10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.191671E+11 | 0.202631E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.140542E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.181292E+10 | 0.520496E+10 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_5:5
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.155615E+10 | 0.510272E+10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.140905E+10 | 0.403072E+10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.158712E+10 | 0.351947E+10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.153154E+10 | 0.537581E+09 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.158289E+10 | 0.190511E+09 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.167112E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.175641E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.179855E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.164339E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.155615E+10 | 0.583132E+09 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.150970E+10 | 0.294318E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.154841E+10 | 0.559774E+10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.191505E+11 | 0.225051E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.140905E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.179855E+10 | 0.559774E+10 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_6:6
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.110201E+10 | 0.122729E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.979898E+09 | 0.100516E+11 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.107429E+10 | 0.952091E+10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.951741E+09 | 0.255529E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.951640E+09 | 0.174553E+10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.114286E+10 | 46723447.35 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.136072E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.147937E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.116932E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.942225E+09 | 0.290033E+10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.100906E+10 | 0.837725E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.111128E+10 | 0.130980E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.132744E+11 | 0.605686E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.942225E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.147937E+10 | 0.130980E+11 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_7:7
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.122785E+10 | 0.604305E+10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.111201E+10 | 0.487353E+10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.125432E+10 | 0.447808E+10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.123040E+10 | 0.105611E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.127372E+10 | 0.668216E+09 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.140394E+10 | 14232321.16 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.165584E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.182755E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.147767E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.123132E+10 | 0.119377E+10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.119144E+10 | 0.387548E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.122123E+10 | 0.649352E+10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.161073E+11 | 0.286960E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.111201E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.182755E+10 | 0.649352E+10 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_8:8
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.121588E+10 | 0.620376E+10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.110117E+10 | 0.502682E+10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.124210E+10 | 0.463921E+10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.121590E+10 | 0.116071E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.125827E+10 | 0.761210E+09 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.138022E+10 | 22308994.28 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.162117E+10 | 295239.05 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.178921E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.144770E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.121865E+10 | 0.129826E+10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.117983E+10 | 0.402806E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.120932E+10 | 0.664341E+10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.158794E+11 | 0.297840E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.110117E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.178921E+10 | 0.664341E+10 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_9:9
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.119456E+10 | 0.666794E+10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.108186E+10 | 0.546909E+10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.122032E+10 | 0.510588E+10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.118912E+10 | 0.142587E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.123001E+10 | 0.101359E+10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.133399E+10 | 51161924.94 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.154960E+10 | 2556004.56 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.170543E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.138710E+10 | 608710.63 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.119625E+10 | 0.156546E+10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.115914E+10 | 0.442695E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.118812E+10 | 0.709560E+10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.154355E+11 | 0.328247E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.108186E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.170543E+10 | 0.709560E+10 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_10:10
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.119244E+10 | 0.819971E+10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.107995E+10 | 0.686580E+10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.121815E+10 | 0.655973E+10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.118174E+10 | 0.212722E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.122211E+10 | 0.170129E+10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.130772E+10 | 0.169897E+09 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.147780E+10 | 17145293.46 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.160626E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.133917E+10 | 27962319.05 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.119307E+10 | 0.231193E+10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.115708E+10 | 0.558338E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.118601E+10 | 0.868230E+10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.151615E+11 | 0.422464E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.107995E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.160626E+10 | 0.868230E+10 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_1:1
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.144831E+10 | 0.00 | 0.108710E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.129547E+10 | 0.00 | 0.913340E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.139361E+10 | 0.00 | 0.815840E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.122185E+10 | 0.384286E+09 | 0.182140E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.124339E+10 | 0.227228E+09 | 0.111799E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.118428E+10 | 0.163352E+10 | 9478823.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.122664E+10 | 0.317575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.122015E+10 | 0.345604E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.118604E+10 | 0.181040E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.125796E+10 | 2216916.08 | 0.181199E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132058E+10 | 0.00 | 0.675364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.147487E+10 | 0.00 | 0.119089E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.154731E+11 | 0.106894E+11 | 0.515862E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.118428E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.147487E+10 | 0.345604E+10 | 0.119089E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_2:2
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.132015E+10 | 0.00 | 0.290151E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.119409E+10 | 0.00 | 0.218904E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.134223E+10 | 5371755.68 | 0.178094E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.134448E+10 | 0.815421E+09 | 0.158866E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.140897E+10 | 0.929560E+09 | 37001487.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.145997E+10 | 0.286208E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.152746E+10 | 0.467754E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.154568E+10 | 0.533098E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.146044E+10 | 0.364735E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.137758E+10 | 0.477876E+09 | 0.135913E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.128286E+10 | 6051278.84 | 0.138197E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.131315E+10 | 0.00 | 0.331628E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.165771E+11 | 0.187522E+11 | 0.119015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.119409E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.154568E+10 | 0.533098E+10 | 0.331628E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_3:3
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.156016E+10 | 0.00 | 0.353423E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.141268E+10 | 0.00 | 0.275348E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.159121E+10 | 0.00 | 0.230920E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.151359E+10 | 0.118488E+09 | 0.242161E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.157568E+10 | 73171871.00 | 39070328.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.153687E+10 | 0.713698E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.155240E+10 | 0.103898E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.159121E+10 | 0.106186E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.151359E+10 | 0.689369E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.156016E+10 | 251974.47 | 0.228820E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.151359E+10 | 0.00 | 0.185495E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.155240E+10 | 0.00 | 0.394084E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.184735E+11 | 0.369582E+10 | 0.149028E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.141268E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.159121E+10 | 0.106186E+10 | 0.394084E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_4:4
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.155213E+10 | 0.00 | 0.377227E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.140542E+10 | 0.00 | 0.295457E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.158302E+10 | 0.00 | 0.252262E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.150580E+10 | 0.112864E+09 | 0.318811E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.156758E+10 | 62704386.47 | 72084816.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.152897E+10 | 0.692182E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.154441E+10 | 0.102038E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.158302E+10 | 0.104136E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.150580E+10 | 0.669324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.155213E+10 | 142082.01 | 0.323890E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.150580E+10 | 0.00 | 0.208228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.154441E+10 | 0.00 | 0.416397E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.183785E+11 | 0.359896E+10 | 0.162105E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.140542E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.158302E+10 | 0.104136E+10 | 0.416397E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_5:5
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.155615E+10 | 0.00 | 0.408218E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.140905E+10 | 0.00 | 0.322458E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.158712E+10 | 0.00 | 0.281558E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.150970E+10 | 98303783.01 | 0.430065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.157163E+10 | 49236592.07 | 0.152408E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.153292E+10 | 0.637387E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.154841E+10 | 0.948243E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.158712E+10 | 0.955442E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.150970E+10 | 0.605147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.155615E+10 | 14097.91 | 0.466506E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.150970E+10 | 0.00 | 0.235455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.154841E+10 | 0.00 | 0.447819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.184260E+11 | 0.329377E+10 | 0.180041E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.140905E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.158712E+10 | 0.955442E+09 | 0.447819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_6:6
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.110201E+10 | 0.00 | 0.981835E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.979898E+09 | 0.00 | 0.804127E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.107429E+10 | 0.00 | 0.761673E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.909694E+09 | 0.164890E+09 | 0.204423E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.931960E+09 | 74397943.22 | 0.139643E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.881518E+09 | 0.105650E+10 | 37378757.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.889464E+09 | 0.188379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.911939E+09 | 0.224227E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.866081E+09 | 0.120868E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.942046E+09 | 640451.31 | 0.232026E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.100906E+10 | 0.00 | 0.670180E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.111128E+10 | 0.00 | 0.104784E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.116092E+11 | 0.663116E+10 | 0.484549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.866081E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.111128E+10 | 0.224227E+10 | 0.104784E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_7:7
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.122785E+10 | 0.00 | 0.483444E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.111201E+10 | 0.00 | 0.389882E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.125432E+10 | 0.00 | 0.358246E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.119144E+10 | 0.174087E+09 | 0.844891E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.124109E+10 | 0.141239E+09 | 0.534573E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.121130E+10 | 0.878821E+09 | 11385856.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.122123E+10 | 0.197294E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.125432E+10 | 0.259996E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.119144E+10 | 0.130063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.122785E+10 | 14844402.34 | 0.955016E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119144E+10 | 0.00 | 0.310039E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.122123E+10 | 0.00 | 0.519482E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.145455E+11 | 0.708252E+10 | 0.229568E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.111201E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.125432E+10 | 0.259996E+10 | 0.519482E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_8:8
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.121588E+10 | 0.00 | 0.496301E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.110117E+10 | 0.00 | 0.402146E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.124210E+10 | 0.00 | 0.371137E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.117983E+10 | 0.160966E+09 | 0.928565E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.122899E+10 | 0.126422E+09 | 0.608968E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.119949E+10 | 0.823222E+09 | 17847195.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.120932E+10 | 0.186723E+10 | 236191.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.124210E+10 | 0.247662E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.117983E+10 | 0.121582E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.121588E+10 | 11809029.94 | 0.103861E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.117983E+10 | 0.00 | 0.322245E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.120932E+10 | 0.00 | 0.531472E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144037E+11 | 0.668209E+10 | 0.238272E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.110117E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.124210E+10 | 0.247662E+10 | 0.531472E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_9:9
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.119456E+10 | 0.00 | 0.533435E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.108186E+10 | 0.00 | 0.437527E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.122032E+10 | 0.00 | 0.408471E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115914E+10 | 0.133384E+09 | 0.114070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.120744E+10 | 96905738.78 | 0.810874E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.117846E+10 | 0.706132E+09 | 40929539.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.118812E+10 | 0.163404E+10 | 2044803.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.122032E+10 | 0.218565E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115914E+10 | 0.103217E+10 | 486968.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.119456E+10 | 7135539.41 | 0.125237E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.115914E+10 | 0.00 | 0.354156E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.118812E+10 | 0.00 | 0.567648E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.141511E+11 | 0.579541E+10 | 0.262598E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.108186E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.122032E+10 | 0.218565E+10 | 0.567648E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_10:10
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.119244E+10 | 0.00 | 0.655977E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.107995E+10 | 0.00 | 0.549264E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.121815E+10 | 0.00 | 0.524779E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115708E+10 | 0.109004E+09 | 0.170177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.120530E+10 | 71647987.07 | 0.136104E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.117637E+10 | 0.593577E+09 | 0.135918E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.118601E+10 | 0.131501E+10 | 13716234.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.121815E+10 | 0.173488E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115708E+10 | 0.819906E+09 | 22369855.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.119244E+10 | 2627227.06 | 0.184954E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.115708E+10 | 0.00 | 0.446671E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.118601E+10 | 0.00 | 0.694584E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.141261E+11 | 0.464665E+10 | 0.337971E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.107995E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.121815E+10 | 0.173488E+10 | 0.694584E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_1:1
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.144831E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135888E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.129547E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114168E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.139361E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101980E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.122185E+10 | 0.00 | 0.00 | 0.00 | 95161206.77 | 0.00 | 0.227675E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.124339E+10 | 0.00 | 0.00 | 0.00 | 59133175.77 | 0.00 | 0.139749E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.118428E+10 | 0.00 | 0.00 | 0.00 | 0.393712E+09 | 0.00 | 11848529.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.122664E+10 | 0.00 | 0.00 | 0.00 | 0.785475E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.122015E+10 | 0.00 | 0.00 | 0.00 | 0.867275E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.118604E+10 | 0.00 | 0.00 | 0.00 | 0.446790E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.125796E+10 | 0.00 | 0.00 | 0.00 | 615169.07 | 0.00 | 0.226498E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132058E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.844205E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.147487E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148862E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.154731E+11 | 0.00 | 0.00 | 0.00 | 0.264816E+10 | 0.00 | 0.644828E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.118428E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.147487E+10 | 0.00 | 0.00 | 0.00 | 0.867275E+09 | 0.00 | 0.148862E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_2:2
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.132015E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.362688E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.119409E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.273631E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.134223E+10 | 0.00 | 0.00 | 0.00 | 1499984.01 | 0.00 | 0.222618E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.134448E+10 | 0.00 | 0.00 | 0.00 | 0.190036E+09 | 0.00 | 0.198582E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.140897E+10 | 0.00 | 0.00 | 0.00 | 0.222994E+09 | 0.00 | 46251859.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.145997E+10 | 0.00 | 0.00 | 0.00 | 0.650840E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.152746E+10 | 0.00 | 0.00 | 0.00 | 0.104064E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.154568E+10 | 0.00 | 0.00 | 0.00 | 0.117569E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.146044E+10 | 0.00 | 0.00 | 0.00 | 0.823319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.137758E+10 | 0.00 | 0.00 | 0.00 | 0.120272E+09 | 0.00 | 0.169891E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.128286E+10 | 0.00 | 0.00 | 0.00 | 1686690.66 | 0.00 | 0.172746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.131315E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.414535E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.165771E+11 | 0.00 | 0.00 | 0.00 | 0.422698E+10 | 0.00 | 0.148769E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.119409E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.154568E+10 | 0.00 | 0.00 | 0.00 | 0.117569E+10 | 0.00 | 0.414535E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_3:3
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.156016E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.441779E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.141268E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.344185E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.159121E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.288651E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.151359E+10 | 0.00 | 0.00 | 0.00 | 26222959.79 | 0.00 | 0.302701E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.157568E+10 | 0.00 | 0.00 | 0.00 | 16570369.94 | 0.00 | 48837910.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.153687E+10 | 0.00 | 0.00 | 0.00 | 0.153493E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.155240E+10 | 0.00 | 0.00 | 0.00 | 0.227135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.159121E+10 | 0.00 | 0.00 | 0.00 | 0.234322E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.151359E+10 | 0.00 | 0.00 | 0.00 | 0.151331E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.156016E+10 | 0.00 | 0.00 | 0.00 | 61579.34 | 0.00 | 0.286025E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.151359E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.231868E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.155240E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.492605E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.184735E+11 | 0.00 | 0.00 | 0.00 | 0.809136E+09 | 0.00 | 0.186284E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.141268E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.159121E+10 | 0.00 | 0.00 | 0.00 | 0.234322E+09 | 0.00 | 0.492605E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_4:4
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.155213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.471534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.140542E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.369321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.158302E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.315327E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.150580E+10 | 0.00 | 0.00 | 0.00 | 25003272.08 | 0.00 | 0.398514E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.156758E+10 | 0.00 | 0.00 | 0.00 | 14262840.47 | 0.00 | 90106020.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.152897E+10 | 0.00 | 0.00 | 0.00 | 0.149155E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.154441E+10 | 0.00 | 0.00 | 0.00 | 0.223093E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.158302E+10 | 0.00 | 0.00 | 0.00 | 0.229901E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.150580E+10 | 0.00 | 0.00 | 0.00 | 0.147117E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.155213E+10 | 0.00 | 0.00 | 0.00 | 34797.96 | 0.00 | 0.404862E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.150580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.260285E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.154441E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.520496E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.183785E+11 | 0.00 | 0.00 | 0.00 | 0.788567E+09 | 0.00 | 0.202631E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.140542E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.158302E+10 | 0.00 | 0.00 | 0.00 | 0.229901E+09 | 0.00 | 0.520496E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_5:5
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.155615E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.510272E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.140905E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.403072E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.158712E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.351947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.150970E+10 | 0.00 | 0.00 | 0.00 | 21839370.63 | 0.00 | 0.537581E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.157163E+10 | 0.00 | 0.00 | 0.00 | 11256331.73 | 0.00 | 0.190511E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.153292E+10 | 0.00 | 0.00 | 0.00 | 0.138193E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.154841E+10 | 0.00 | 0.00 | 0.00 | 0.208004E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.158712E+10 | 0.00 | 0.00 | 0.00 | 0.211432E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.150970E+10 | 0.00 | 0.00 | 0.00 | 0.133693E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.155615E+10 | 0.00 | 0.00 | 0.00 | 3477.14 | 0.00 | 0.583132E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.150970E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.294318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.154841E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.559774E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.184260E+11 | 0.00 | 0.00 | 0.00 | 0.724421E+09 | 0.00 | 0.225051E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.140905E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.158712E+10 | 0.00 | 0.00 | 0.00 | 0.211432E+09 | 0.00 | 0.559774E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_6:6
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.110201E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122729E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.979898E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100516E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.107429E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.952091E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.909694E+09 | 0.00 | 0.00 | 0.00 | 42047632.04 | 0.00 | 0.255529E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.931960E+09 | 0.00 | 0.00 | 0.00 | 19680130.78 | 0.00 | 0.174553E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.881518E+09 | 0.00 | 0.00 | 0.00 | 0.261339E+09 | 0.00 | 46723447.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.889464E+09 | 0.00 | 0.00 | 0.00 | 0.471260E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.911939E+09 | 0.00 | 0.00 | 0.00 | 0.567431E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.866081E+09 | 0.00 | 0.00 | 0.00 | 0.303234E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.942046E+09 | 0.00 | 0.00 | 0.00 | 178962.03 | 0.00 | 0.290033E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.100906E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.837725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.111128E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130980E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.116092E+11 | 0.00 | 0.00 | 0.00 | 0.166517E+10 | 0.00 | 0.605686E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.866081E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.111128E+10 | 0.00 | 0.00 | 0.00 | 0.567431E+09 | 0.00 | 0.130980E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_7:7
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.122785E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.604305E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.111201E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.487353E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.125432E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.447808E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.119144E+10 | 0.00 | 0.00 | 0.00 | 38953725.59 | 0.00 | 0.105611E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.124109E+10 | 0.00 | 0.00 | 0.00 | 32632176.57 | 0.00 | 0.668216E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.121130E+10 | 0.00 | 0.00 | 0.00 | 0.192643E+09 | 0.00 | 14232321.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.122123E+10 | 0.00 | 0.00 | 0.00 | 0.434608E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.125432E+10 | 0.00 | 0.00 | 0.00 | 0.573229E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.119144E+10 | 0.00 | 0.00 | 0.00 | 0.286223E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.122785E+10 | 0.00 | 0.00 | 0.00 | 3473817.02 | 0.00 | 0.119377E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119144E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.387548E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.122123E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.649352E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.145455E+11 | 0.00 | 0.00 | 0.00 | 0.156176E+10 | 0.00 | 0.286960E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.111201E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.125432E+10 | 0.00 | 0.00 | 0.00 | 0.573229E+09 | 0.00 | 0.649352E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_8:8
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.121588E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.620376E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.110117E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.502682E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.124210E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.463921E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.117983E+10 | 0.00 | 0.00 | 0.00 | 36069892.99 | 0.00 | 0.116071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.122899E+10 | 0.00 | 0.00 | 0.00 | 29277893.21 | 0.00 | 0.761210E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.119949E+10 | 0.00 | 0.00 | 0.00 | 0.180730E+09 | 0.00 | 22308994.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.120932E+10 | 0.00 | 0.00 | 0.00 | 0.411849E+09 | 0.00 | 295239.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.124210E+10 | 0.00 | 0.00 | 0.00 | 0.547111E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.117983E+10 | 0.00 | 0.00 | 0.00 | 0.267871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.121588E+10 | 0.00 | 0.00 | 0.00 | 2769649.29 | 0.00 | 0.129826E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.117983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.402806E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.120932E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.664341E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144037E+11 | 0.00 | 0.00 | 0.00 | 0.147568E+10 | 0.00 | 0.297840E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.110117E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.124210E+10 | 0.00 | 0.00 | 0.00 | 0.547111E+09 | 0.00 | 0.664341E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_9:9
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.119456E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.666794E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.108186E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.546909E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.122032E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.510588E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115914E+10 | 0.00 | 0.00 | 0.00 | 29980030.44 | 0.00 | 0.142587E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.120744E+10 | 0.00 | 0.00 | 0.00 | 22570039.06 | 0.00 | 0.101359E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.117846E+10 | 0.00 | 0.00 | 0.00 | 0.155529E+09 | 0.00 | 51161924.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.118812E+10 | 0.00 | 0.00 | 0.00 | 0.361485E+09 | 0.00 | 2556004.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.122032E+10 | 0.00 | 0.00 | 0.00 | 0.485112E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115914E+10 | 0.00 | 0.00 | 0.00 | 0.227965E+09 | 0.00 | 608710.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.119456E+10 | 0.00 | 0.00 | 0.00 | 1688677.05 | 0.00 | 0.156546E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.115914E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.442695E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.118812E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.709560E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.141511E+11 | 0.00 | 0.00 | 0.00 | 0.128433E+10 | 0.00 | 0.328247E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.108186E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.122032E+10 | 0.00 | 0.00 | 0.00 | 0.485112E+09 | 0.00 | 0.709560E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_10:10
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.119244E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.819971E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.107995E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.686580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.121815E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.655973E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115708E+10 | 0.00 | 0.00 | 0.00 | 24652216.58 | 0.00 | 0.212722E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.120530E+10 | 0.00 | 0.00 | 0.00 | 16815486.08 | 0.00 | 0.170129E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.117637E+10 | 0.00 | 0.00 | 0.00 | 0.131352E+09 | 0.00 | 0.169897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.118601E+10 | 0.00 | 0.00 | 0.00 | 0.291793E+09 | 0.00 | 17145293.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.121815E+10 | 0.00 | 0.00 | 0.00 | 0.388104E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115708E+10 | 0.00 | 0.00 | 0.00 | 0.182081E+09 | 0.00 | 27962319.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.119244E+10 | 0.00 | 0.00 | 0.00 | 632440.35 | 0.00 | 0.231193E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.115708E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.558338E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.118601E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.868230E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.141261E+11 | 0.00 | 0.00 | 0.00 | 0.103543E+10 | 0.00 | 0.422464E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.107995E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.121815E+10 | 0.00 | 0.00 | 0.00 | 0.388104E+09 | 0.00 | 0.868230E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.959052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.465170E+10 | 0.00 | 0.00 | 0.52 |
February | 0.917909E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.343200E+10 | 0.00 | 0.00 | 0.53 |
March | 0.933427E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.313448E+10 | 0.00 | 0.00 | 0.53 |
April | 0.861682E+10 | 0.00 | 0.00 | 1649417.97 | 1513068.39 | 0.249645E+09 | 0.862694E+09 | 0.00 | 0.55 |
May | 0.839949E+10 | 608111.59 | 0.00 | 1615537.06 | 0.00 | 28225890.91 | 0.129371E+10 | 0.00 | 0.55 |
June | 0.424040E+10 | 81410377.12 | 0.00 | 5928705.42 | 1199371.07 | 0.00 | 0.407265E+10 | 0.00 | 0.62 |
July | 0.162497E+10 | 0.112516E+09 | 0.00 | 12371002.71 | 1268240.68 | 0.00 | 0.668432E+10 | 0.00 | 0.73 |
August | 0.401589E+09 | 3584360.37 | 0.00 | 15811641.11 | 0.00 | 0.00 | 0.783787E+10 | 0.00 | 0.81 |
September | 0.213782E+10 | 921418.91 | 0.00 | 10346054.37 | 0.00 | 0.00 | 0.651492E+10 | 0.00 | 0.68 |
October | 0.949613E+10 | 0.00 | 0.00 | 291817.80 | 0.00 | 68811094.46 | 0.428444E+09 | 0.00 | 0.53 |
November | 0.956199E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.212857E+10 | 0.00 | 0.00 | 0.52 |
December | 0.841959E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.595237E+10 | 0.00 | 0.00 | 0.53 |
Annual Sum or Average | 0.810027E+11 | 0.199041E+09 | 0.00 | 48014176.44 | 3980680.14 | 0.196458E+11 | 0.276946E+11 | 0.00 | 0.59 |
Minimum of Months | 0.401589E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.52 |
Maximum of Months | 0.959052E+10 | 0.112516E+09 | 0.00 | 15811641.11 | 1513068.39 | 0.595237E+10 | 0.783787E+10 | 0.00 | 0.81 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.402712E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158742E+10 | 0.00 | 0.00 | 0.42 |
February | 0.403582E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.843679E+09 | 0.00 | 0.00 | 0.42 |
March | 0.434550E+10 | 0.00 | 0.00 | 11529.18 | 0.00 | 0.623971E+09 | 4152834.38 | 0.00 | 0.43 |
April | 0.330198E+10 | 0.00 | 0.00 | 1855135.29 | 375143.26 | 25623459.78 | 0.674838E+09 | 0.00 | 0.44 |
May | 0.317295E+10 | 147563.52 | 0.00 | 2172853.88 | 0.00 | 3423834.86 | 0.896844E+09 | 0.00 | 0.44 |
June | 0.868348E+09 | 29073049.67 | 0.00 | 5871368.12 | 0.00 | 0.00 | 0.243808E+10 | 0.00 | 0.48 |
July | 0.392519E+09 | 49747592.30 | 0.00 | 8191221.62 | 42915.48 | 0.00 | 0.228095E+10 | 0.00 | 0.48 |
August | 0.252080E+09 | 1213406.15 | 0.00 | 9565612.76 | 0.00 | 0.00 | 0.207721E+10 | 0.00 | 0.49 |
September | 0.524871E+09 | 0.00 | 0.00 | 7862508.01 | 0.00 | 0.00 | 0.254591E+10 | 0.00 | 0.48 |
October | 0.314730E+10 | 0.00 | 0.00 | 1738233.10 | 0.00 | 13906149.37 | 0.106551E+10 | 0.00 | 0.44 |
November | 0.424092E+10 | 0.00 | 0.00 | 13827.84 | 0.00 | 0.416030E+09 | 4426445.90 | 0.00 | 0.42 |
December | 0.341114E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.214001E+10 | 0.00 | 0.00 | 0.42 |
Annual Sum or Average | 0.317205E+11 | 80181611.64 | 0.00 | 37282289.80 | 418058.74 | 0.565407E+10 | 0.119879E+11 | 0.00 | 0.45 |
Minimum of Months | 0.252080E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.42 |
Maximum of Months | 0.434550E+10 | 49747592.30 | 0.00 | 9565612.76 | 375143.26 | 0.214001E+10 | 0.254591E+10 | 0.00 | 0.49 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.316683E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.224623E+10 | 0.00 | 0.00 | 0.41 |
February | 0.313793E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.157463E+10 | 0.00 | 0.00 | 0.41 |
March | 0.347799E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132325E+10 | 0.00 | 0.00 | 0.42 |
April | 0.316609E+10 | 0.00 | 0.00 | 875914.90 | 513304.67 | 73323315.62 | 0.681112E+09 | 0.00 | 0.49 |
May | 0.311030E+10 | 66073.15 | 0.00 | 1070682.88 | 0.00 | 479831.17 | 0.938712E+09 | 0.00 | 0.50 |
June | 0.943514E+09 | 19987562.60 | 0.00 | 3908420.99 | 10583.89 | 0.00 | 0.293672E+10 | 0.00 | 0.66 |
July | 0.428380E+09 | 38950398.46 | 0.00 | 5875087.33 | 2619701.18 | 0.00 | 0.382406E+10 | 0.00 | 0.85 |
August | 0.286742E+09 | 561448.88 | 0.00 | 7109779.25 | 0.00 | 0.00 | 0.434353E+10 | 0.00 | 1.05 |
September | 0.627581E+09 | 0.00 | 0.00 | 5344161.46 | 0.00 | 0.00 | 0.362458E+10 | 0.00 | 0.81 |
October | 0.309739E+10 | 0.00 | 0.00 | 881784.70 | 0.00 | 15203898.25 | 0.895439E+09 | 0.00 | 0.44 |
November | 0.348983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.962279E+09 | 0.00 | 0.00 | 0.41 |
December | 0.248074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.289754E+10 | 0.00 | 0.00 | 0.41 |
Annual Sum or Average | 0.274133E+11 | 59565483.09 | 0.00 | 25065831.51 | 3143589.74 | 0.909294E+10 | 0.172442E+11 | 0.00 | 0.57 |
Minimum of Months | 0.286742E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.348983E+10 | 38950398.46 | 0.00 | 7109779.25 | 2619701.18 | 0.289754E+10 | 0.434353E+10 | 0.00 | 1.05 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.299104E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.242041E+10 | 0.00 | 0.00 | 0.41 |
February | 0.285974E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185238E+10 | 0.00 | 0.00 | 0.41 |
March | 0.319649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160208E+10 | 0.00 | 0.00 | 0.42 |
April | 0.314284E+10 | 0.00 | 0.00 | 779212.55 | 562052.45 | 0.104954E+09 | 0.615327E+09 | 0.00 | 0.48 |
May | 0.311296E+10 | 56008.19 | 0.00 | 975386.49 | 0.00 | 1260873.64 | 0.868599E+09 | 0.00 | 0.49 |
June | 0.102144E+10 | 19710225.78 | 0.00 | 3649690.93 | 9204.43 | 0.00 | 0.278406E+10 | 0.00 | 0.65 |
July | 0.474430E+09 | 38944858.52 | 0.00 | 5707372.47 | 2579659.53 | 0.00 | 0.372200E+10 | 0.00 | 0.84 |
August | 0.288507E+09 | 538623.46 | 0.00 | 6994128.12 | 0.00 | 0.00 | 0.430307E+10 | 0.00 | 1.04 |
September | 0.670099E+09 | 0.00 | 0.00 | 5171935.55 | 0.00 | 0.00 | 0.352077E+10 | 0.00 | 0.80 |
October | 0.308996E+10 | 0.00 | 0.00 | 777385.96 | 0.00 | 30769480.91 | 0.829258E+09 | 0.00 | 0.44 |
November | 0.327477E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117149E+10 | 0.00 | 0.00 | 0.41 |
December | 0.229839E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.307971E+10 | 0.00 | 0.00 | 0.41 |
Annual Sum or Average | 0.264207E+11 | 59249715.95 | 0.00 | 24055112.06 | 3150916.41 | 0.102631E+11 | 0.166431E+11 | 0.00 | 0.57 |
Minimum of Months | 0.288507E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.327477E+10 | 38944858.52 | 0.00 | 6994128.12 | 2579659.53 | 0.307971E+10 | 0.430307E+10 | 0.00 | 1.04 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.264752E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.276315E+10 | 0.00 | 0.00 | 0.41 |
February | 0.250611E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.220584E+10 | 0.00 | 0.00 | 0.41 |
March | 0.284280E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.195367E+10 | 0.00 | 0.00 | 0.42 |
April | 0.311762E+10 | 0.00 | 0.00 | 615256.30 | 692869.74 | 0.163111E+09 | 0.482048E+09 | 0.00 | 0.47 |
May | 0.312723E+10 | 41363.29 | 0.00 | 772816.42 | 0.00 | 13109461.70 | 0.717519E+09 | 0.00 | 0.48 |
June | 0.134276E+10 | 19000624.44 | 0.00 | 2905718.46 | 6334.40 | 0.00 | 0.225236E+10 | 0.00 | 0.62 |
July | 0.579968E+09 | 39072726.30 | 0.00 | 5113944.13 | 2366321.53 | 0.00 | 0.345172E+10 | 0.00 | 0.81 |
August | 0.308163E+09 | 484768.37 | 0.00 | 6543305.69 | 0.00 | 0.00 | 0.416269E+10 | 0.00 | 1.02 |
September | 0.729656E+09 | 0.00 | 0.00 | 4614463.07 | 0.00 | 0.00 | 0.328138E+10 | 0.00 | 0.77 |
October | 0.311090E+10 | 0.00 | 0.00 | 500001.83 | 0.00 | 82982425.24 | 0.638275E+09 | 0.00 | 0.43 |
November | 0.293989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150181E+10 | 0.00 | 0.00 | 0.41 |
December | 0.201959E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.335819E+10 | 0.00 | 0.00 | 0.41 |
Annual Sum or Average | 0.252722E+11 | 58599482.40 | 0.00 | 21065505.89 | 3065525.67 | 0.120419E+11 | 0.149860E+11 | 0.00 | 0.56 |
Minimum of Months | 0.308163E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.312723E+10 | 39072726.30 | 0.00 | 6543305.69 | 2366321.53 | 0.335819E+10 | 0.416269E+10 | 0.00 | 1.02 |
Report: MechanicalVentilationLoadsMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.378251E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.620411E+10 | 0.00 | 0.00 | 0.38 |
February | 0.362415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.507415E+10 | 0.00 | 0.00 | 0.38 |
March | 0.442962E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.444336E+10 | 0.00 | 0.00 | 0.39 |
April | 0.557419E+10 | 0.00 | 0.00 | 664778.21 | 1392514.53 | 0.400020E+09 | 0.404588E+09 | 0.00 | 0.39 |
May | 0.590120E+10 | 0.00 | 0.00 | 567137.89 | 0.00 | 73146809.69 | 0.523353E+09 | 0.00 | 0.40 |
June | 0.389087E+10 | 34678982.06 | 0.00 | 2399682.79 | 0.00 | 0.00 | 0.136845E+10 | 0.00 | 0.44 |
July | 0.142558E+10 | 66917301.61 | 0.00 | 6441279.71 | 5311319.55 | 0.00 | 0.372460E+10 | 0.00 | 0.50 |
August | 0.425793E+09 | 900018.12 | 0.00 | 9477412.03 | 77901.93 | 0.00 | 0.489501E+10 | 0.00 | 0.59 |
September | 0.217875E+10 | 0.00 | 0.00 | 5174144.61 | 0.00 | 0.00 | 0.314917E+10 | 0.00 | 0.48 |
October | 0.594560E+10 | 0.00 | 0.00 | 83559.91 | 0.00 | 0.581558E+09 | 0.108578E+09 | 0.00 | 0.38 |
November | 0.462243E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.357605E+10 | 0.00 | 0.00 | 0.38 |
December | 0.276346E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.716205E+10 | 0.00 | 0.00 | 0.38 |
Annual Sum or Average | 0.445642E+11 | 0.102496E+09 | 0.00 | 24807995.15 | 6781736.00 | 0.275144E+11 | 0.141738E+11 | 0.00 | 0.42 |
Minimum of Months | 0.425793E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.594560E+10 | 66917301.61 | 0.00 | 9477412.03 | 5311319.55 | 0.716205E+10 | 0.489501E+10 | 0.00 | 0.59 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.193400E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.347874E+10 | 0.00 | 0.00 | 0.41 |
February | 0.196380E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.274861E+10 | 0.00 | 0.00 | 0.41 |
March | 0.226164E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.254106E+10 | 0.00 | 0.00 | 0.42 |
April | 0.297628E+10 | 0.00 | 0.00 | 343681.52 | 1206865.13 | 0.317444E+09 | 0.175737E+09 | 0.00 | 0.41 |
May | 0.314070E+10 | 0.00 | 0.00 | 342297.14 | 0.00 | 98015964.19 | 0.277335E+09 | 0.00 | 0.42 |
June | 0.201452E+10 | 14717827.44 | 0.00 | 1330240.74 | 0.00 | 2081291.85 | 0.738486E+09 | 0.00 | 0.42 |
July | 0.882424E+09 | 29019515.20 | 0.00 | 3234571.98 | 2534568.42 | 0.00 | 0.135322E+10 | 0.00 | 0.41 |
August | 0.403282E+09 | 209292.60 | 0.00 | 4686035.21 | 0.00 | 0.00 | 0.159856E+10 | 0.00 | 0.43 |
September | 0.114833E+10 | 0.00 | 0.00 | 2784545.74 | 0.00 | 0.00 | 0.143251E+10 | 0.00 | 0.42 |
October | 0.307495E+10 | 0.00 | 0.00 | 58886.45 | 0.00 | 0.522773E+09 | 69620002.67 | 0.00 | 0.41 |
November | 0.231992E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.212608E+10 | 0.00 | 0.00 | 0.41 |
December | 0.160969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.376500E+10 | 0.00 | 0.00 | 0.41 |
Annual Sum or Average | 0.237295E+11 | 43946635.24 | 0.00 | 12780258.79 | 3741433.55 | 0.155998E+11 | 0.564547E+10 | 0.00 | 0.42 |
Minimum of Months | 0.403282E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.314070E+10 | 29019515.20 | 0.00 | 4686035.21 | 2534568.42 | 0.376500E+10 | 0.159856E+10 | 0.00 | 0.43 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.177135E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.364024E+10 | 0.00 | 0.00 | 0.41 |
February | 0.188474E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.282675E+10 | 0.00 | 0.00 | 0.41 |
March | 0.216345E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.263774E+10 | 0.00 | 0.00 | 0.42 |
April | 0.292162E+10 | 0.00 | 0.00 | 317208.78 | 1268245.50 | 0.366900E+09 | 0.168577E+09 | 0.00 | 0.41 |
May | 0.311953E+10 | 0.00 | 0.00 | 298904.20 | 0.00 | 0.132003E+09 | 0.248519E+09 | 0.00 | 0.42 |
June | 0.208697E+10 | 14338017.45 | 0.00 | 1194372.10 | 0.00 | 2068931.27 | 0.643457E+09 | 0.00 | 0.42 |
July | 0.914478E+09 | 28881261.47 | 0.00 | 3052978.89 | 2600464.59 | 331659.76 | 0.131588E+10 | 0.00 | 0.41 |
August | 0.423825E+09 | 182386.66 | 0.00 | 4494952.64 | 0.00 | 0.00 | 0.158181E+10 | 0.00 | 0.43 |
September | 0.123289E+10 | 0.00 | 0.00 | 2581202.30 | 0.00 | 0.00 | 0.133848E+10 | 0.00 | 0.42 |
October | 0.299617E+10 | 0.00 | 0.00 | 45719.41 | 0.00 | 0.595181E+09 | 58952113.29 | 0.00 | 0.41 |
November | 0.221902E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.222482E+10 | 0.00 | 0.00 | 0.41 |
December | 0.142575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.394828E+10 | 0.00 | 0.00 | 0.41 |
Annual Sum or Average | 0.231598E+11 | 43401665.58 | 0.00 | 11985338.32 | 3868710.08 | 0.163743E+11 | 0.535567E+10 | 0.00 | 0.42 |
Minimum of Months | 0.423825E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.311953E+10 | 28881261.47 | 0.00 | 4494952.64 | 2600464.59 | 0.394828E+10 | 0.158181E+10 | 0.00 | 0.43 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.126239E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.414632E+10 | 0.00 | 0.00 | 0.41 |
February | 0.155639E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.315274E+10 | 0.00 | 0.00 | 0.41 |
March | 0.183191E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.296473E+10 | 0.00 | 0.00 | 0.42 |
April | 0.279483E+10 | 0.00 | 0.00 | 259155.44 | 1450576.91 | 0.492869E+09 | 0.140334E+09 | 0.00 | 0.41 |
May | 0.299275E+10 | 0.00 | 0.00 | 206715.18 | 0.00 | 0.294787E+09 | 0.171310E+09 | 0.00 | 0.42 |
June | 0.221488E+10 | 13543458.20 | 0.00 | 927155.01 | 0.00 | 8021481.21 | 0.447125E+09 | 0.00 | 0.42 |
July | 0.995677E+09 | 28572801.63 | 0.00 | 2618158.34 | 2797940.97 | 794989.81 | 0.121663E+10 | 0.00 | 0.41 |
August | 0.467202E+09 | 134540.58 | 0.00 | 4033967.59 | 0.00 | 0.00 | 0.154456E+10 | 0.00 | 0.43 |
September | 0.144295E+10 | 0.00 | 0.00 | 2105926.85 | 0.00 | 0.00 | 0.109454E+10 | 0.00 | 0.42 |
October | 0.284495E+10 | 0.00 | 0.00 | 24759.43 | 0.00 | 0.736103E+09 | 28384368.54 | 0.00 | 0.41 |
November | 0.192728E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.251087E+10 | 0.00 | 0.00 | 0.41 |
December | 0.103103E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.434164E+10 | 0.00 | 0.00 | 0.41 |
Annual Sum or Average | 0.213622E+11 | 42250800.40 | 0.00 | 10175837.85 | 4248517.87 | 0.186489E+11 | 0.464288E+10 | 0.00 | 0.42 |
Minimum of Months | 0.467202E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.299275E+10 | 28572801.63 | 0.00 | 4033967.59 | 2797940.97 | 0.434164E+10 | 0.154456E+10 | 0.00 | 0.43 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:19:13
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.346203E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.505440E+10 | 0.00 | 0.00 | 0.41 |
February | 0.195781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.450053E+10 | 0.00 | 0.00 | 0.41 |
March | 0.471895E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.430988E+10 | 0.00 | 0.00 | 0.42 |
April | 0.222681E+10 | 0.00 | 167537.11 | 195049.81 | 1756729.88 | 0.104320E+10 | 0.100545E+09 | 3814.84 | 0.41 |
May | 0.243129E+10 | 0.00 | 0.00 | 123241.23 | 0.00 | 0.850860E+09 | 86086086.49 | 0.00 | 0.42 |
June | 0.218632E+10 | 12772490.14 | 0.00 | 685569.88 | 148177.75 | 48558498.87 | 0.287103E+09 | 0.00 | 0.42 |
July | 0.117390E+10 | 28928733.84 | 0.00 | 1932756.59 | 3589112.86 | 4656232.81 | 0.968873E+09 | 0.00 | 0.41 |
August | 0.588087E+09 | 109609.55 | 0.00 | 3200320.71 | 0.00 | 0.00 | 0.139444E+10 | 0.00 | 0.43 |
September | 0.171397E+10 | 0.00 | 0.00 | 1497002.13 | 0.00 | 4178617.36 | 0.702210E+09 | 0.00 | 0.42 |
October | 0.217633E+10 | 0.00 | 0.00 | 10145.36 | 0.00 | 0.132858E+10 | 17121287.66 | 0.00 | 0.41 |
November | 0.877657E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.353229E+10 | 0.00 | 0.00 | 0.41 |
December | 84130576.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.526783E+10 | 0.00 | 0.00 | 0.41 |
Annual Sum or Average | 0.144724E+11 | 41810833.53 | 167537.11 | 7644085.72 | 5494020.48 | 0.259450E+11 | 0.355638E+10 | 3814.84 | 0.42 |
Minimum of Months | 84130576.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.243129E+10 | 28928733.84 | 167537.11 | 3200320.71 | 3589112.86 | 0.526783E+10 | 0.139444E+10 | 3814.84 | 0.43 |