Table of Contents

Program Version:EnergyPlus, Version 9.5.0-Unknown, YMD=2021.05.12 10:29

Tabular Output Report in Format: HTML

Building: US+MF+CZ4B+elecres+crawlspace+IECC_2021

Environment: ANNUAL ** Albuquerque Intl Sunport NM USA TMY3 WMO#=723650

Simulation Timestamp: 2021-05-12 10:29:11


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2021-05-12 10:29:11

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [kBtu] Energy Per Total Building Area [kBtu/ft2] Energy Per Conditioned Building Area [kBtu/ft2]
Total Site Energy 629475.19 16.14 29.13
Net Site Energy 629475.19 16.14 29.13
Total Source Energy 1993547.93 51.11 92.25
Net Source Energy 1993547.93 51.11 92.25


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 1.200
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil No 1 1.050
Fuel Oil No 2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [ft2]
Total Building Area 39005.22
Net Conditioned Building Area 21609.96
Unconditioned Building Area 17395.26


End Uses

Electricity [kBtu] Natural Gas [kBtu] Gasoline [kBtu] Diesel [kBtu] Coal [kBtu] Fuel Oil No 1 [kBtu] Fuel Oil No 2 [kBtu] Propane [kBtu] Other Fuel 1 [kBtu] Other Fuel 2 [kBtu] District Cooling [kBtu] District Heating [kBtu] Water [gal]
Heating 136755.90 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 50001.46 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 38708.60 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 18809.03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 299798.81 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 31115.88 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 54285.51 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 330767.30
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 629475.19 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 330767.30
Note: Electricity appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [kBtu] Natural Gas [kBtu] Gasoline [kBtu] Diesel [kBtu] Coal [kBtu] Fuel Oil No 1 [kBtu] Fuel Oil No 2 [kBtu] Propane [kBtu] Other Fuel 1 [kBtu] Other Fuel 2 [kBtu] District Cooling [kBtu] District Heating [kBtu] Water [gal]
Heating General 136755.90 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 50001.46 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting General 38708.60 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Exterior-Lights 18809.03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Garage-Lights 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment dishwasher 9418.03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  refrigerator 41096.32 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  clotheswasher 4809.31 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  electric_dryer 42687.44 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  electric_range 30929.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  television 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  electric_mels 160227.26 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  IECC_adj 10631.34 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans General 22463.25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Ventilation 8652.63 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Domestic Hot Water 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 330767.30
  General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Water Heater 4468.60 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Water Heater Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Other 49816.91 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [kBtu/ft2] Natural Gas Intensity [kBtu/ft2] Gasoline Intensity [kBtu/ft2] Diesel Intensity [kBtu/ft2] Coal Intensity [kBtu/ft2] Fuel Oil No 1 Intensity [kBtu/ft2] Fuel Oil No 2 Intensity [kBtu/ft2] Propane Intensity [kBtu/ft2] Other Fuel 1 Intensity [kBtu/ft2] Other Fuel 2 Intensity [kBtu/ft2] District Cooling Intensity [kBtu/ft2] District Heating Intensity [kBtu/ft2] Water Intensity [gal/ft2]
Lighting 2.66 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 12.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 15.31
Other 13.87 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 29.13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 15.31


Utility Use Per Total Floor Area

Electricity Intensity [kBtu/ft2] Natural Gas Intensity [kBtu/ft2] Gasoline Intensity [kBtu/ft2] Diesel Intensity [kBtu/ft2] Coal Intensity [kBtu/ft2] Fuel Oil No 1 Intensity [kBtu/ft2] Fuel Oil No 2 Intensity [kBtu/ft2] Propane Intensity [kBtu/ft2] Other Fuel 1 Intensity [kBtu/ft2] Other Fuel 2 Intensity [kBtu/ft2] District Cooling Intensity [kBtu/ft2] District Heating Intensity [kBtu/ft2] Water Intensity [gal/ft2]
Lighting 1.47 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 6.98 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 8.48
Other 7.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 16.14 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 8.48


Electric Loads Satisfied

Electricity [kBtu] Percent Electricity [%]
Fuel-Fired Power Generation 0.000 0.00
High Temperature Geothermal* 0.000 0.00
Photovoltaic Power 0.000 0.00
Wind Power 0.000 0.00
Power Conversion 0.000 0.00
Net Decrease in On-Site Storage 0.000 0.00
Total On-Site Electric Sources 0.000 0.00
     
Electricity Coming From Utility 629475.192 100.00
Surplus Electricity Going To Utility 0.000 0.00
Net Electricity From Utility 629475.192 100.00
     
Total On-Site and Utility Electric Sources 629475.192 100.00
Total Electricity End Uses 629475.192 100.00


On-Site Thermal Sources

Heat [kBtu] Percent Heat [%]
Water-Side Heat Recovery 0.00  
Air to Air Heat Recovery for Cooling 0.00  
Air to Air Heat Recovery for Heating 0.00  
High-Temperature Geothermal* 0.00  
Solar Water Thermal 0.00  
Solar Air Thermal 0.00  
Total On-Site Thermal Sources 0.00  


Water Source Summary

Water [gal] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 330767.30 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 330767.30 100.00
Total Water End Uses 330767.30 100.00


Setpoint Not Met Criteria

Degrees [deltaF]
Tolerance for Zone Heating Setpoint Not Met Time 0.36
Tolerance for Zone Cooling Setpoint Not Met Time 0.36


Comfort and Setpoint Not Met Summary

Facility [Hours]
Time Setpoint Not Met During Occupied Heating 954.83
Time Setpoint Not Met During Occupied Cooling 9.00
Time Not Comfortable Based on Simple ASHRAE 55-2004 218.00


Note 1: An asterisk (*) indicates that the feature is not yet implemented.

Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Adaptive Comfort Summary
Initialization Summary
Annual Heat Emissions Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
Coil Sizing Details
System Summary
Outdoor Air Summary
Outdoor Air Details
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary
Annual Thermal Resilience Summary
Annual CO2 Resilience Summary
Annual Visual Resilience Summary

FANSPLIT

| CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR |

COILLOADS

| MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_TOPFLOOR | MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_TOPFLOOR | MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_FRONTROW_BOTTOMFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_FRONTROW_BOTTOMFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_FRONTROW_BOTTOMFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_BACKROW_BOTTOMFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_BACKROW_BOTTOMFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_BACKROW_BOTTOMFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_FRONTROW_MIDDLEFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_FRONTROW_MIDDLEFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_FRONTROW_MIDDLEFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_BACKROW_MIDDLEFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_BACKROW_MIDDLEFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_BACKROW_MIDDLEFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_FRONTROW_TOPFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_FRONTROW_TOPFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_FRONTROW_TOPFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_BACKROW_TOPFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_BACKROW_TOPFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_BACKROW_TOPFLOOR |

WATER HEATER: LOADS

| WATER HEATER_TANK_UNIT1_FRONTROW_BOTTOMFLOOR | WATER HEATER_TANK_UNIT2_FRONTROW_BOTTOMFLOOR | WATER HEATER_TANK_UNIT3_FRONTROW_BOTTOMFLOOR | WATER HEATER_TANK_UNIT1_BACKROW_BOTTOMFLOOR | WATER HEATER_TANK_UNIT2_BACKROW_BOTTOMFLOOR | WATER HEATER_TANK_UNIT3_BACKROW_BOTTOMFLOOR | WATER HEATER_TANK_UNIT1_FRONTROW_MIDDLEFLOOR | WATER HEATER_TANK_UNIT2_FRONTROW_MIDDLEFLOOR | WATER HEATER_TANK_UNIT3_FRONTROW_MIDDLEFLOOR | WATER HEATER_TANK_UNIT1_BACKROW_MIDDLEFLOOR | WATER HEATER_TANK_UNIT2_BACKROW_MIDDLEFLOOR | WATER HEATER_TANK_UNIT3_BACKROW_MIDDLEFLOOR | WATER HEATER_TANK_UNIT1_FRONTROW_TOPFLOOR | WATER HEATER_TANK_UNIT2_FRONTROW_TOPFLOOR | WATER HEATER_TANK_UNIT3_FRONTROW_TOPFLOOR | WATER HEATER_TANK_UNIT1_BACKROW_TOPFLOOR | WATER HEATER_TANK_UNIT2_BACKROW_TOPFLOOR | WATER HEATER_TANK_UNIT3_BACKROW_TOPFLOOR |

HEATING AND COOLING LOADS

| CRAWLSPACE | BREEZEWAY | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | ATTIC | LIVING_UNIT3_BACKROW_TOPFLOOR | LIVING_UNIT3_FRONTROW_TOPFLOOR | LIVING_UNIT1_FRONTROW_TOPFLOOR | LIVING_UNIT2_BACKROW_TOPFLOOR | LIVING_UNIT2_FRONTROW_TOPFLOOR | LIVING_UNIT1_BACKROW_TOPFLOOR |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2021-05-12 10:29:11

General

Value
Program Version and Build EnergyPlus, Version 9.5.0-Unknown, YMD=2021.05.12 10:29
RunPeriod ANNUAL
Weather File Albuquerque Intl Sunport NM USA TMY3 WMO#=723650
Latitude [deg] 35.04
Longitude [deg] -106.6
Elevation [ft] 5311.94
Time Zone -7.0
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [ft2] 17103.09 6415.36 2136.19 6415.36 2136.19
Above Ground Wall Area [ft2] 16363.00 6175.53 2005.97 6175.53 2005.97
Window Opening Area [ft2] 2126.74 531.68 531.68 531.68 531.68
Gross Window-Wall Ratio [%] 12.43 8.29 24.89 8.29 24.89
Above Ground Window-Wall Ratio [%] 13.00 8.61 26.51 8.61 26.51


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [ft2] 15296.60 6115.58 1532.73 6115.58 1532.73
Above Ground Wall Area [ft2] 15296.60 6115.58 1532.73 6115.58 1532.73
Window Opening Area [ft2] 2126.74 531.68 531.68 531.68 531.68
Gross Window-Wall Ratio [%] 13.90 8.69 34.69 8.69 34.69
Above Ground Window-Wall Ratio [%] 13.90 8.69 34.69 8.69 34.69


Skylight-Roof Ratio

Total
Gross Roof Area [ft2] 8451.30
Skylight Area [ft2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [ft2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [ft3] Multipliers Above Ground Gross Wall Area [ft2] Underground Gross Wall Area [ft2] Window Glass Area [ft2] Opening Area [ft2] Lighting [Btu/h-ft2] People [ft2 per person] Plug and Process [Btu/h-ft2]
CRAWLSPACE 7794.39 No Yes 19513.17 1.00 185.02 740.10 0.00 0.00 0.0000   0.0000
BREEZEWAY 1798.16 No Yes 30553.25 1.00 0.00 0.00 0.00 0.00 0.0000   0.0000
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 934.97 0.00 147.69 147.69 0.5831 600.28 2.9092
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 679.51 0.00 59.08 59.08 0.5831 600.28 2.9092
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 934.97 0.00 147.69 147.69 0.5831 600.28 2.9092
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 934.97 0.00 147.69 147.69 0.5831 600.28 2.9092
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 679.51 0.00 59.08 59.08 0.5831 600.28 2.9092
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 934.97 0.00 147.69 147.69 0.5831 600.28 2.9092
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.5831 600.28 2.9092
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 679.51 0.00 59.08 59.08 0.5831 600.28 2.9092
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.5831 600.28 2.9092
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.5831 600.28 2.9092
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 679.51 0.00 59.08 59.08 0.5831 600.28 2.9092
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.5831 600.28 2.9092
ATTIC 7802.71 No Yes 52795.56 1.00 881.37 0.00 0.00 0.00 0.0000   0.0000
LIVING_UNIT3_BACKROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.5831 600.28 2.9092
LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.5831 600.28 2.9092
LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.5831 600.28 2.9092
LIVING_UNIT2_BACKROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 679.51 0.00 59.08 59.08 0.5831 600.28 2.9092
LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 679.51 0.00 59.08 59.08 0.5831 600.28 2.9092
LIVING_UNIT1_BACKROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.5831 600.28 2.9092
Total 39005.22     286601.37   16363.00 740.10 2126.74 2126.74 0.3230 1083.48 1.6118
Conditioned Total 21609.96     183739.38   15296.60 0.00 2126.74 2126.74 0.5831 600.28 2.9092
Unconditioned Total 17395.26     102861.98   1066.39 740.10 0.00 0.00 0.0000   0.0000
Not Part of Total 0.00     0.00   0.00 0.00 0.00 0.00      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2021-05-12 10:29:11

End Uses

Electricity [kBtuh] Natural Gas [kBtuh] Gasoline [kBtuh] Diesel [kBtuh] Coal [kBtuh] Fuel Oil No 1 [kBtuh] Fuel Oil No 2 [kBtuh] Propane [kBtuh] Other Fuel 1 [kBtuh] Other Fuel 2 [kBtuh] District Cooling [kBtuh] Steam [kBtuh] Water [gal/min]
Time of Peak 07-JAN-07:30 - - - - - - - - - - - 01-JAN-08:09
Heating 111.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 5.42 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 34.65 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 9.74 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 28.41 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1.20
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 190.04 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1.20


End Uses By Subcategory

Subcategory Electricity [kBtuh] Natural Gas [kBtuh] Gasoline [kBtuh] Diesel [kBtuh] Coal [kBtuh] Fuel Oil No 1 [kBtuh] Fuel Oil No 2 [kBtuh] Propane [kBtuh] Other Fuel 1 [kBtuh] Other Fuel 2 [kBtuh] District Cooling [kBtuh] Steam [kBtuh] Water [gal/min]
Heating General 111.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting General 5.42 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Exterior-Lights 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Garage-Lights 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment dishwasher 0.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  refrigerator 4.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  clotheswasher 0.74 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  electric_dryer 4.26 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  electric_range 3.60 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  television 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  electric_mels 19.46 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  IECC_adj 1.29 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans General 8.75 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Ventilation 0.99 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Domestic Hot Water 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1.20
  General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Water Heater 0.51 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Water Heater Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2021-05-12 10:29:11

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [kBtu] Source Natural Gas [kBtu] Source Gasoline [kBtu] Source Diesel [kBtu] Source Coal [kBtu] Source Fuel Oil No 1 [kBtu] Source Fuel Oil No 2 [kBtu] Source Propane [kBtu] Source Other Fuel 1 [kBtu] Source Other Fuel 2 [kBtu] Source District Cooling [kBtu] Source District Heating [kBtu]
Heating 433105.93 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 158354.63 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 122590.15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 59568.20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 949462.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 98543.98 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 171922.22 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 1993547.93 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [kBtu/ft2] Source Natural Gas [kBtu/ft2] Source Gasoline [kBtu/ft2] Source Diesel [kBtu/ft2] Source Coal [kBtu/ft2] Source Fuel Oil No 1 [kBtu/ft2] Source Fuel Oil No 2 [kBtu/ft2] Source Propane [kBtu/ft2] Source Other Fuel 1 [kBtu/ft2] Source Other Fuel 2 [kBtu/ft2] Source District Cooling [kBtu/ft2] Source District Heating [kBtu/ft2]
Heating 20.04 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 7.33 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 5.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 2.76 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 43.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 4.56 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 7.96 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 92.25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [kBtu/ft2] Source Natural Gas [kBtu/ft2] Source Gasoline [kBtu/ft2] Source Diesel [kBtu/ft2] Source Coal [kBtu/ft2] Source Fuel Oil No 1 [kBtu/ft2] Source Fuel Oil No 2 [kBtu/ft2] Source Propane [kBtu/ft2] Source Other Fuel 1 [kBtu/ft2] Source Other Fuel 2 [kBtu/ft2] Source District Cooling [kBtu/ft2] Source District Heating [kBtu/ft2]
Heating 11.10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 4.06 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 3.14 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 1.53 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 24.34 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 2.53 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 4.41 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 51.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2021-05-12 10:29:11

ZoneHVAC:EnergyRecoveryVentilator

User-Specified Supply Air Flow Rate [ft3/min] User-Specified Exhaust Air Flow Rate [ft3/min]
ERV_UNIT1_FRONTROW_BOTTOMFLOOR 44.99 44.99
ERV_UNIT2_FRONTROW_BOTTOMFLOOR 44.99 44.99
ERV_UNIT3_FRONTROW_BOTTOMFLOOR 44.99 44.99
ERV_UNIT1_BACKROW_BOTTOMFLOOR 44.99 44.99
ERV_UNIT2_BACKROW_BOTTOMFLOOR 44.99 44.99
ERV_UNIT3_BACKROW_BOTTOMFLOOR 44.99 44.99
ERV_UNIT1_FRONTROW_MIDDLEFLOOR 44.99 44.99
ERV_UNIT2_FRONTROW_MIDDLEFLOOR 44.99 44.99
ERV_UNIT3_FRONTROW_MIDDLEFLOOR 44.99 44.99
ERV_UNIT1_BACKROW_MIDDLEFLOOR 44.99 44.99
ERV_UNIT2_BACKROW_MIDDLEFLOOR 44.99 44.99
ERV_UNIT3_BACKROW_MIDDLEFLOOR 44.99 44.99
ERV_UNIT3_BACKROW_TOPFLOOR 44.99 44.99
ERV_UNIT3_FRONTROW_TOPFLOOR 44.99 44.99
ERV_UNIT1_FRONTROW_TOPFLOOR 44.99 44.99
ERV_UNIT2_BACKROW_TOPFLOOR 44.99 44.99
ERV_UNIT2_FRONTROW_TOPFLOOR 44.99 44.99
ERV_UNIT1_BACKROW_TOPFLOOR 44.99 44.99
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:OnOff

User-Specified Maximum Flow Rate [ft3/min] Design Size Maximum Flow Rate [ft3/min]
OASUPPLYFAN_UNIT1_FRONTROW_BOTTOMFLOOR 44.99  
OAEXHAUSTFAN_UNIT1_FRONTROW_BOTTOMFLOOR 44.99  
OASUPPLYFAN_UNIT2_FRONTROW_BOTTOMFLOOR 44.99  
OAEXHAUSTFAN_UNIT2_FRONTROW_BOTTOMFLOOR 44.99  
OASUPPLYFAN_UNIT3_FRONTROW_BOTTOMFLOOR 44.99  
OAEXHAUSTFAN_UNIT3_FRONTROW_BOTTOMFLOOR 44.99  
OASUPPLYFAN_UNIT1_BACKROW_BOTTOMFLOOR 44.99  
OAEXHAUSTFAN_UNIT1_BACKROW_BOTTOMFLOOR 44.99  
OASUPPLYFAN_UNIT2_BACKROW_BOTTOMFLOOR 44.99  
OAEXHAUSTFAN_UNIT2_BACKROW_BOTTOMFLOOR 44.99  
OASUPPLYFAN_UNIT3_BACKROW_BOTTOMFLOOR 44.99  
OAEXHAUSTFAN_UNIT3_BACKROW_BOTTOMFLOOR 44.99  
OASUPPLYFAN_UNIT1_FRONTROW_MIDDLEFLOOR 44.99  
OAEXHAUSTFAN_UNIT1_FRONTROW_MIDDLEFLOOR 44.99  
OASUPPLYFAN_UNIT2_FRONTROW_MIDDLEFLOOR 44.99  
OAEXHAUSTFAN_UNIT2_FRONTROW_MIDDLEFLOOR 44.99  
OASUPPLYFAN_UNIT3_FRONTROW_MIDDLEFLOOR 44.99  
OAEXHAUSTFAN_UNIT3_FRONTROW_MIDDLEFLOOR 44.99  
OASUPPLYFAN_UNIT1_BACKROW_MIDDLEFLOOR 44.99  
OAEXHAUSTFAN_UNIT1_BACKROW_MIDDLEFLOOR 44.99  
OASUPPLYFAN_UNIT2_BACKROW_MIDDLEFLOOR 44.99  
OAEXHAUSTFAN_UNIT2_BACKROW_MIDDLEFLOOR 44.99  
OASUPPLYFAN_UNIT3_BACKROW_MIDDLEFLOOR 44.99  
OAEXHAUSTFAN_UNIT3_BACKROW_MIDDLEFLOOR 44.99  
OASUPPLYFAN_UNIT3_BACKROW_TOPFLOOR 44.99  
OAEXHAUSTFAN_UNIT3_BACKROW_TOPFLOOR 44.99  
OASUPPLYFAN_UNIT3_FRONTROW_TOPFLOOR 44.99  
OAEXHAUSTFAN_UNIT3_FRONTROW_TOPFLOOR 44.99  
OASUPPLYFAN_UNIT1_FRONTROW_TOPFLOOR 44.99  
OAEXHAUSTFAN_UNIT1_FRONTROW_TOPFLOOR 44.99  
OASUPPLYFAN_UNIT2_BACKROW_TOPFLOOR 44.99  
OAEXHAUSTFAN_UNIT2_BACKROW_TOPFLOOR 44.99  
OASUPPLYFAN_UNIT2_FRONTROW_TOPFLOOR 44.99  
OAEXHAUSTFAN_UNIT2_FRONTROW_TOPFLOOR 44.99  
OASUPPLYFAN_UNIT1_BACKROW_TOPFLOOR 44.99  
OAEXHAUSTFAN_UNIT1_BACKROW_TOPFLOOR 44.99  
SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR   489.58
SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR   222.44
SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR   353.42
SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR   483.44
SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR   226.11
SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR   347.28
SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR   472.24
SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR   215.44
SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR   360.91
SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR   466.39
SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR   217.43
SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR   354.16
SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR   494.89
SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR   242.45
SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR   367.64
SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR   496.07
SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR   249.83
SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR   360.81
HEAT PUMP WATER HEATER FAN_UNIT1_FRONTROW_BOTTOMFLOOR   160.01
HEAT PUMP WATER HEATER FAN_UNIT2_FRONTROW_BOTTOMFLOOR   160.01
HEAT PUMP WATER HEATER FAN_UNIT3_FRONTROW_BOTTOMFLOOR   160.01
HEAT PUMP WATER HEATER FAN_UNIT1_BACKROW_BOTTOMFLOOR   160.01
HEAT PUMP WATER HEATER FAN_UNIT2_BACKROW_BOTTOMFLOOR   160.01
HEAT PUMP WATER HEATER FAN_UNIT3_BACKROW_BOTTOMFLOOR   160.01
HEAT PUMP WATER HEATER FAN_UNIT1_FRONTROW_MIDDLEFLOOR   160.01
HEAT PUMP WATER HEATER FAN_UNIT2_FRONTROW_MIDDLEFLOOR   160.01
HEAT PUMP WATER HEATER FAN_UNIT3_FRONTROW_MIDDLEFLOOR   160.01
HEAT PUMP WATER HEATER FAN_UNIT1_BACKROW_MIDDLEFLOOR   160.01
HEAT PUMP WATER HEATER FAN_UNIT2_BACKROW_MIDDLEFLOOR   160.01
HEAT PUMP WATER HEATER FAN_UNIT3_BACKROW_MIDDLEFLOOR   160.01
HEAT PUMP WATER HEATER FAN_UNIT1_FRONTROW_TOPFLOOR   160.01
HEAT PUMP WATER HEATER FAN_UNIT2_FRONTROW_TOPFLOOR   160.01
HEAT PUMP WATER HEATER FAN_UNIT3_FRONTROW_TOPFLOOR   160.01
HEAT PUMP WATER HEATER FAN_UNIT1_BACKROW_TOPFLOOR   160.01
HEAT PUMP WATER HEATER FAN_UNIT2_BACKROW_TOPFLOOR   160.01
HEAT PUMP WATER HEATER FAN_UNIT3_BACKROW_TOPFLOOR   160.01
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

HeatExchanger:AirToAir:SensibleAndLatent

User-Specified Nominal Supply Air Flow Rate [ft3/min]
OA_HEAT_RECOVERY_UNIT1_FRONTROW_BOTTOMFLOOR 44.99
OA_HEAT_RECOVERY_UNIT2_FRONTROW_BOTTOMFLOOR 44.99
OA_HEAT_RECOVERY_UNIT3_FRONTROW_BOTTOMFLOOR 44.99
OA_HEAT_RECOVERY_UNIT1_BACKROW_BOTTOMFLOOR 44.99
OA_HEAT_RECOVERY_UNIT2_BACKROW_BOTTOMFLOOR 44.99
OA_HEAT_RECOVERY_UNIT3_BACKROW_BOTTOMFLOOR 44.99
OA_HEAT_RECOVERY_UNIT1_FRONTROW_MIDDLEFLOOR 44.99
OA_HEAT_RECOVERY_UNIT2_FRONTROW_MIDDLEFLOOR 44.99
OA_HEAT_RECOVERY_UNIT3_FRONTROW_MIDDLEFLOOR 44.99
OA_HEAT_RECOVERY_UNIT1_BACKROW_MIDDLEFLOOR 44.99
OA_HEAT_RECOVERY_UNIT2_BACKROW_MIDDLEFLOOR 44.99
OA_HEAT_RECOVERY_UNIT3_BACKROW_MIDDLEFLOOR 44.99
OA_HEAT_RECOVERY_UNIT3_BACKROW_TOPFLOOR 44.99
OA_HEAT_RECOVERY_UNIT3_FRONTROW_TOPFLOOR 44.99
OA_HEAT_RECOVERY_UNIT1_FRONTROW_TOPFLOOR 44.99
OA_HEAT_RECOVERY_UNIT2_BACKROW_TOPFLOOR 44.99
OA_HEAT_RECOVERY_UNIT2_FRONTROW_TOPFLOOR 44.99
OA_HEAT_RECOVERY_UNIT1_BACKROW_TOPFLOOR 44.99
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirTerminal:SingleDuct:ConstantVolume:NoReheat

Design Size Maximum Air Flow Rate [ft3/min]
ZONEDIRECTAIR_UNIT1_FRONTROW_BOTTOMFLOOR 489.58
ZONEDIRECTAIR_UNIT2_FRONTROW_BOTTOMFLOOR 222.44
ZONEDIRECTAIR_UNIT3_FRONTROW_BOTTOMFLOOR 353.42
ZONEDIRECTAIR_UNIT1_BACKROW_BOTTOMFLOOR 483.44
ZONEDIRECTAIR_UNIT2_BACKROW_BOTTOMFLOOR 226.11
ZONEDIRECTAIR_UNIT3_BACKROW_BOTTOMFLOOR 347.28
ZONEDIRECTAIR_UNIT1_FRONTROW_MIDDLEFLOOR 472.24
ZONEDIRECTAIR_UNIT2_FRONTROW_MIDDLEFLOOR 215.44
ZONEDIRECTAIR_UNIT3_FRONTROW_MIDDLEFLOOR 360.91
ZONEDIRECTAIR_UNIT1_BACKROW_MIDDLEFLOOR 466.39
ZONEDIRECTAIR_UNIT2_BACKROW_MIDDLEFLOOR 217.43
ZONEDIRECTAIR_UNIT3_BACKROW_MIDDLEFLOOR 354.16
ZONEDIRECTAIR_UNIT3_BACKROW_TOPFLOOR 360.81
ZONEDIRECTAIR_UNIT3_FRONTROW_TOPFLOOR 367.64
ZONEDIRECTAIR_UNIT1_FRONTROW_TOPFLOOR 494.89
ZONEDIRECTAIR_UNIT2_BACKROW_TOPFLOOR 249.83
ZONEDIRECTAIR_UNIT2_FRONTROW_TOPFLOOR 242.45
ZONEDIRECTAIR_UNIT1_BACKROW_TOPFLOOR 496.07
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC

Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] Sum of Air Terminal Maximum Flow Rates [ft3/min] Adjusted Heating Design Air Flow Rate [ft3/min] Adjusted Cooling Design Air Flow Rate [ft3/min] Adjusted Main Design Air Flow Rate [ft3/min] User Heating Air Flow Ratio [] Calculated Heating Air Flow Ratio [] Design Supply Air Flow Rate [ft3/min]
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 489.58 489.58 489.58 489.58 489.58 489.58 1.00 1.00 489.58
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 222.44 222.44 222.44 222.44 222.44 222.44 1.00 1.00 222.44
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 353.42 353.42 353.42 353.42 353.42 353.42 1.00 1.00 353.42
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 483.44 483.44 483.44 483.44 483.44 483.44 1.00 1.00 483.44
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 226.11 226.11 226.11 226.11 226.11 226.11 1.00 1.00 226.11
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 347.28 347.28 347.28 347.28 347.28 347.28 1.00 1.00 347.28
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 472.24 472.24 472.24 472.24 472.24 472.24 1.00 1.00 472.24
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 215.44 215.44 215.44 215.44 215.44 215.44 1.00 1.00 215.44
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 360.91 360.91 360.91 360.91 360.91 360.91 1.00 1.00 360.91
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 466.39 466.39 466.39 466.39 466.39 466.39 1.00 1.00 466.39
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 217.43 217.43 217.43 217.43 217.43 217.43 1.00 1.00 217.43
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 354.16 354.16 354.16 354.16 354.16 354.16 1.00 1.00 354.16
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 494.89 494.89 494.89 494.89 494.89 494.89 1.00 1.00 494.89
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 242.45 242.45 242.45 242.45 242.45 242.45 1.00 1.00 242.45
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 367.64 367.64 367.64 367.64 367.64 367.64 1.00 1.00 367.64
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 496.07 496.07 496.07 496.07 496.07 496.07 1.00 1.00 496.07
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 249.83 249.83 249.83 249.83 249.83 249.83 1.00 1.00 249.83
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 360.81 360.81 360.81 360.81 360.81 360.81 1.00 1.00 360.81
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Cooling:DX:SingleSpeed

Design Size Rated Air Flow Rate [ft3/min] Design Size Gross Rated Total Cooling Capacity [ton] Design Size Gross Rated Sensible Heat Ratio
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR 489.58 1.09 0.800655
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR 222.44 0.494178 0.800655
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR 353.42 0.785153 0.800655
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR 483.44 1.07 0.800655
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR 226.11 0.502320 0.800655
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR 347.28 0.771513 0.800655
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR 472.24 1.05 0.800655
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR 215.44 0.478615 0.800655
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR 360.91 0.801799 0.800655
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR 466.39 1.04 0.800655
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR 217.43 0.483029 0.800655
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR 354.16 0.786799 0.800655
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR 494.89 1.10 0.800655
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR 242.45 0.538630 0.800655
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR 367.64 0.816746 0.800655
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR 496.07 1.10 0.800655
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR 249.83 0.555009 0.800655
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR 360.81 0.801569 0.800655
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC:UnitaryHeatCool

Supply Air Flow Rate [ft3/min] Supply Air Flow Rate During Heating Operation [ft3/min] Supply Air Flow Rate During Cooling Operation [ft3/min] Nominal Heating Capacity [Btu/h] Nominal Cooling Capacity [ton] Fraction of Supply Air Flow That Goes Through the Controlling Zone
ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR 489.58 489.58 489.58 7601.34 1.09 1.00
ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR 222.44 222.44 222.44 5979.68 0.494178 1.00
ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR 353.42 353.42 353.42 7603.87 0.785153 1.00
ACANDF_UNIT1_BACKROW_BOTTOMFLOOR 483.44 483.44 483.44 7604.31 1.07 1.00
ACANDF_UNIT2_BACKROW_BOTTOMFLOOR 226.11 226.11 226.11 5980.09 0.502320 1.00
ACANDF_UNIT3_BACKROW_BOTTOMFLOOR 347.28 347.28 347.28 7601.76 0.771513 1.00
ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR 472.24 472.24 472.24 5784.23 1.05 1.00
ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR 215.44 215.44 215.44 4175.88 0.478615 1.00
ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR 360.91 360.91 360.91 5786.51 0.801799 1.00
ACANDF_UNIT1_BACKROW_MIDDLEFLOOR 466.39 466.39 466.39 5786.94 1.04 1.00
ACANDF_UNIT2_BACKROW_MIDDLEFLOOR 217.43 217.43 217.43 4176.23 0.483029 1.00
ACANDF_UNIT3_BACKROW_MIDDLEFLOOR 354.16 354.16 354.16 5784.59 0.786799 1.00
ACANDF_UNIT1_FRONTROW_TOPFLOOR 494.89 494.89 494.89 7268.08 1.10 1.00
ACANDF_UNIT2_FRONTROW_TOPFLOOR 242.45 242.45 242.45 5646.91 0.538630 1.00
ACANDF_UNIT3_FRONTROW_TOPFLOOR 367.64 367.64 367.64 7269.71 0.816746 1.00
ACANDF_UNIT1_BACKROW_TOPFLOOR 496.07 496.07 496.07 7271.55 1.10 1.00
ACANDF_UNIT2_BACKROW_TOPFLOOR 249.83 249.83 249.83 5648.65 0.555009 1.00
ACANDF_UNIT3_BACKROW_TOPFLOOR 360.81 360.81 360.81 7269.84 0.801569 1.00
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Heating:Electric

Design Size Nominal Capacity [Btu/h]
MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR 7601.34
MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR 5979.68
MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR 7603.87
MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR 7604.31
MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR 5980.09
MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR 7601.76
MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR 5784.23
MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR 4175.88
MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR 5786.51
MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR 5786.94
MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR 4176.23
MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR 5784.59
MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_TOPFLOOR 7268.08
MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_TOPFLOOR 5646.91
MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_TOPFLOOR 7269.71
MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_TOPFLOOR 7271.55
MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_TOPFLOOR 5648.65
MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_TOPFLOOR 7269.84
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

WaterHeater:HeatPump:WrappedCondenser

Evaporator air flow rate [ft3/min]
WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR 160.01
WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR 160.01
WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR 160.01
WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR 160.01
WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR 160.01
WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR 160.01
WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR 160.01
WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR 160.01
WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR 160.01
WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR 160.01
WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR 160.01
WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR 160.01
WATER HEATER_UNIT1_FRONTROW_TOPFLOOR 160.01
WATER HEATER_UNIT2_FRONTROW_TOPFLOOR 160.01
WATER HEATER_UNIT3_FRONTROW_TOPFLOOR 160.01
WATER HEATER_UNIT1_BACKROW_TOPFLOOR 160.01
WATER HEATER_UNIT2_BACKROW_TOPFLOOR 160.01
WATER HEATER_UNIT3_BACKROW_TOPFLOOR 160.01
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

PlantLoop

Maximum Loop Flow Rate [ft3/min] Plant Loop Volume [ft3]
DHW LOOP_UNIT1_FRONTROW_BOTTOMFLOOR 1.04 2.09
DHW LOOP_UNIT2_FRONTROW_BOTTOMFLOOR 1.04 2.09
DHW LOOP_UNIT3_FRONTROW_BOTTOMFLOOR 1.04 2.09
DHW LOOP_UNIT1_BACKROW_BOTTOMFLOOR 1.04 2.09
DHW LOOP_UNIT2_BACKROW_BOTTOMFLOOR 1.04 2.09
DHW LOOP_UNIT3_BACKROW_BOTTOMFLOOR 1.04 2.09
DHW LOOP_UNIT1_FRONTROW_MIDDLEFLOOR 1.04 2.09
DHW LOOP_UNIT2_FRONTROW_MIDDLEFLOOR 1.04 2.09
DHW LOOP_UNIT3_FRONTROW_MIDDLEFLOOR 1.04 2.09
DHW LOOP_UNIT1_BACKROW_MIDDLEFLOOR 1.04 2.09
DHW LOOP_UNIT2_BACKROW_MIDDLEFLOOR 1.04 2.09
DHW LOOP_UNIT3_BACKROW_MIDDLEFLOOR 1.04 2.09
DHW LOOP_UNIT1_FRONTROW_TOPFLOOR 1.04 2.09
DHW LOOP_UNIT2_FRONTROW_TOPFLOOR 1.04 2.09
DHW LOOP_UNIT3_FRONTROW_TOPFLOOR 1.04 2.09
DHW LOOP_UNIT1_BACKROW_TOPFLOOR 1.04 2.09
DHW LOOP_UNIT2_BACKROW_TOPFLOOR 1.04 2.09
DHW LOOP_UNIT3_BACKROW_TOPFLOOR 1.04 2.09
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:VariableSpeed

Design Flow Rate [ft3/min]
MAINS PRESSURE_UNIT1_FRONTROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT2_FRONTROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT3_FRONTROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT1_BACKROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT2_BACKROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT3_BACKROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT1_FRONTROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT2_FRONTROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT3_FRONTROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT1_BACKROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT2_BACKROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT3_BACKROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT1_FRONTROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT2_FRONTROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT3_FRONTROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT1_BACKROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT2_BACKROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT3_BACKROW_TOPFLOOR 1.04
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

WaterHeater:Stratified

Maximum Heater Capacity [Btu/h] Use Side Design Flow Rate [ft3/min]
WATER HEATER_TANK_UNIT1_FRONTROW_BOTTOMFLOOR 15354.00 1.04
WATER HEATER_TANK_UNIT2_FRONTROW_BOTTOMFLOOR 15354.00 1.04
WATER HEATER_TANK_UNIT3_FRONTROW_BOTTOMFLOOR 15354.00 1.04
WATER HEATER_TANK_UNIT1_BACKROW_BOTTOMFLOOR 15354.00 1.04
WATER HEATER_TANK_UNIT2_BACKROW_BOTTOMFLOOR 15354.00 1.04
WATER HEATER_TANK_UNIT3_BACKROW_BOTTOMFLOOR 15354.00 1.04
WATER HEATER_TANK_UNIT1_FRONTROW_MIDDLEFLOOR 15354.00 1.04
WATER HEATER_TANK_UNIT2_FRONTROW_MIDDLEFLOOR 15354.00 1.04
WATER HEATER_TANK_UNIT3_FRONTROW_MIDDLEFLOOR 15354.00 1.04
WATER HEATER_TANK_UNIT1_BACKROW_MIDDLEFLOOR 15354.00 1.04
WATER HEATER_TANK_UNIT2_BACKROW_MIDDLEFLOOR 15354.00 1.04
WATER HEATER_TANK_UNIT3_BACKROW_MIDDLEFLOOR 15354.00 1.04
WATER HEATER_TANK_UNIT1_FRONTROW_TOPFLOOR 15354.00 1.04
WATER HEATER_TANK_UNIT2_FRONTROW_TOPFLOOR 15354.00 1.04
WATER HEATER_TANK_UNIT3_FRONTROW_TOPFLOOR 15354.00 1.04
WATER HEATER_TANK_UNIT1_BACKROW_TOPFLOOR 15354.00 1.04
WATER HEATER_TANK_UNIT2_BACKROW_TOPFLOOR 15354.00 1.04
WATER HEATER_TANK_UNIT3_BACKROW_TOPFLOOR 15354.00 1.04
User-Specified values were used. Design Size values were used if no User-Specified values were provided.


Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2021-05-12 10:29:11

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

Possible Shadow Receivers
OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR |
Mir-OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR |
Mir-OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR |
Mir-OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | ROOF_RIGHT | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR |
Mir-OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | ROOF_LEFT | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR |
Mir-OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR |
Mir-OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR |
Mir-OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR |
Mir-OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | ROOF_RIGHT | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR |
Mir-OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | ROOF_LEFT | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR |
Mir-OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR |
Mir-OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR |
Mir-OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR |
Mir-OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | ROOF_RIGHT | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR |
Mir-OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | ROOF_LEFT | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR |
Mir-OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR |
Mir-OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR |
Mir-OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR |
Mir-OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | ROOF_RIGHT | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR |
Mir-OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | ROOF_LEFT | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR |
Mir-OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
Mir-OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
Mir-OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
Mir-OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR ROOF_RIGHT | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
Mir-OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR ROOF_LEFT | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
Mir-OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR |
Mir-OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR |
Mir-OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
Mir-OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR ROOF_RIGHT | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR |
Mir-OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR ROOF_LEFT | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR |
Mir-OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR |
BGWALL_UPPER_LDF OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR |
BGWALL_UPPER_SDR OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR |
BGWALL_UPPER_LDB OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR |
BGWALL_UPPER_SDL OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR |
BREEZEWAY_MIDDLEFLOOR WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR |
BREEZEWAY_TOPFLOOR WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR |
WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR |
WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR |
WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR |
WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR |
WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR |
WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR |
WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR |
WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR DOOR_LDB_UNIT1_FRONTROW_BOTTOMFLOOR |
WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR DOOR_LDB_UNIT2_FRONTROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR |
WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR DOOR_LDB_UNIT3_FRONTROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR DOOR_LDF_UNIT1_BACKROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR |
WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR DOOR_LDF_UNIT2_BACKROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR DOOR_LDF_UNIT3_BACKROW_BOTTOMFLOOR |
WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR DOOR_LDB_UNIT1_FRONTROW_MIDDLEFLOOR |
WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR DOOR_LDB_UNIT2_FRONTROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR |
WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR DOOR_LDB_UNIT3_FRONTROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR DOOR_LDF_UNIT1_BACKROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR |
WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR DOOR_LDF_UNIT2_BACKROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR DOOR_LDF_UNIT3_BACKROW_MIDDLEFLOOR |
WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR |
WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR DOOR_LDF_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR |
WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR DOOR_LDB_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR |
WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR DOOR_LDB_UNIT1_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR DOOR_LDF_UNIT2_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR DOOR_LDB_UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR |
WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR DOOR_LDF_UNIT1_BACKROW_TOPFLOOR |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2021-05-12 10:29:11

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: Initialization Summary

For: Entire Facility

Timestamp: 2021-05-12 10:29:11

Version

Version ID
1 9.5


Timesteps per Hour

#TimeSteps Minutes per TimeStep {minutes}
1 6 10


System Convergence Limits

Minimum System TimeStep {minutes} Max HVAC Iterations Minimum Plant Iterations Maximum Plant Iterations
1 1 20 2 8


Simulation Control

Do Zone Sizing Do System Sizing Do Plant Sizing Do Design Days Do Weather Simulation Do HVAC Sizing Simulation
1 Yes Yes No Yes Yes No


Performance Precision Tradeoffs

Use Coil Direct Simulation Zone Radiant Exchange Algorithm Override Mode Number of Timestep In Hour Force Euler Method Minimum Number of Warmup Days Force Suppress All Begin Environment Resets Minimum System Timestep MaxZoneTempDiff MaxAllowedDelTemp
1 No ScriptF Normal 6 No 1 No 1.0 0.300 2.0000E-003


Output Reporting Tolerances

Tolerance for Time Heating Setpoint Not Met Tolerance for Zone Cooling Setpoint Not Met Time
1 0.200 0.200


Site:GroundTemperature:BuildingSurface

Jan{F} Feb{F} Mar{F} Apr{F} May{F} Jun{F} Jul{F} Aug{F} Sep{F} Oct{F} Nov{F} Dec{F}
1 64.40 64.40 64.40 64.40 64.40 64.40 64.40 64.40 64.40 64.40 64.40 64.40


Site:GroundTemperature:FCfactorMethod

Jan{F} Feb{F} Mar{F} Apr{F} May{F} Jun{F} Jul{F} Aug{F} Sep{F} Oct{F} Nov{F} Dec{F}
1 37.40 41.00 48.02 54.68 67.24 73.87 75.69 72.34 64.58 54.91 45.39 39.11


Site:GroundTemperature:Shallow

Jan{F} Feb{F} Mar{F} Apr{F} May{F} Jun{F} Jul{F} Aug{F} Sep{F} Oct{F} Nov{F} Dec{F}
1 55.40 55.40 55.40 55.40 55.40 55.40 55.40 55.40 55.40 55.40 55.40 55.40


Site:GroundTemperature:Deep

Jan{F} Feb{F} Mar{F} Apr{F} May{F} Jun{F} Jul{F} Aug{F} Sep{F} Oct{F} Nov{F} Dec{F}
1 60.80 60.80 60.80 60.80 60.80 60.80 60.80 60.80 60.80 60.80 60.80 60.80


Site:GroundReflectance

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:SnowModifier

Normal Daylighting {dimensionless}
1 1.000 1.000


Site:GroundReflectance:Snow

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:Snow:Daylighting

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Environment:Weather Station

Wind Sensor Height Above Ground {ft} Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {ft} Air Temperature Sensor Height Above Ground {ft} Wind Speed Modifier Coefficient-Internal Temperature Modifier Coefficient-Internal
1 32.810 0.140 885.870 4.921 1.586 9.750E-003


Site:Location

Location Name Latitude {N+/S- Deg} Longitude {E+/W- Deg} Time Zone Number {GMT+/-} Elevation {ft} Standard Pressure at Elevation {psi} Standard RhoAir at Elevation
1 Albuquerque Intl Sunport NM USA TMY3 WMO#=723650 35.04 -106.62 -7.00 5311.94 12. 0.9904


Site Water Mains Temperature Information

Calculation Method{} Water Mains Temperature Schedule Name{} Annual Average Outdoor Air Temperature{F} Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaF} Fixed Default Water Mains Temperature{F}
1 Correlation NA 56.53 42.30 NA


Building Information

Building Name North Axis {deg} Terrain Loads Convergence Tolerance Value Temperature Convergence Tolerance Value Solar Distribution Maximum Number of Warmup Days Minimum Number of Warmup Days
1 US+MF+CZ4B+elecres+crawlspace+IECC_2021 0.000 Suburbs 4.00000E-002 0.40000 FullExterior 25 6


Inside Convection Algorithm

Algorithm {Simple
TARP
CeilingDiffuser
AdaptiveConvectionAlgorithm}
1 TARP


Outside Convection Algorithm

Algorithm {SimpleCombined
TARP
MoWitt
DOE-2
AdaptiveConvectionAlgorithm}
1 DOE-2


Sky Radiance Distribution

Value {Anisotropic}
1 Anisotropic


Zone Air Solution Algorithm

Value {ThirdOrderBackwardDifference
AnalyticalSolution
EulerMethod}
1 ThirdOrderBackwardDifference


Zone Air Carbon Dioxide Balance Simulation

Simulation {Yes/No} Carbon Dioxide Concentration
1 No N/A


Zone Air Generic Contaminant Balance Simulation

Simulation {Yes/No} Generic Contaminant Concentration
1 No N/A


Zone Air Mass Flow Balance Simulation

Enforce Mass Balance



Adjust Zone Mixing and Return {AdjustMixingOnly
AdjustReturnOnly
AdjustMixingThenReturn
AdjustReturnThenMixing
None}
Adjust Zone Infiltration {AddInfiltration
AdjustInfiltration
None}

Infiltration Zones {MixingSourceZonesOnly
AllZones}


1 No N/A N/A N/A


HVACSystemRootFindingAlgorithm

Value {RegulaFalsi
Bisection
BisectionThenRegulaFalsi
RegulaFalsiThenBisection}
1 RegulaFalsi


Environment:Site Atmospheric Variation

Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {ft} Air Temperature Gradient Coefficient {F/ft}
1 0.220 1213.970 0.003566


Material Details

Material Name ThermalResistance {m2-K/w} Roughness Thickness {ft} Conductivity {w/m-K} Density {lb/ft3} Specific Heat {Btu/lbm-R} Absorptance:Thermal Absorptance:Solar Absorptance:Visible
1 SHEATHING_CONSOL_LAYER 0.8807 Rough 0.1021 3.533E-002 1.255 0.350 0.9000 0.7000 0.7000
2 CEIL_CONSOL_LAYER 9.1788 Rough 1.8587 6.172E-002 2.618 0.185 0.9000 0.7000 0.7000
3 FLOOR_CONSOL_LAYER 2.8450 Rough 0.4584 4.910E-002 3.438 0.219 0.9000 0.7000 0.7000
4 BSMTWALL_CONSOL_LAYER 2.3423E-005 Rough 0.0008 10.844 7.541 0.248 0.9000 0.7000 0.7000
5 CRAWLWALL_CONSOL_LAYER 2.3423E-005 Rough 0.0008 10.844 7.541 0.248 0.9000 0.7000 0.7000
6 WALL_CONSOL_LAYER 2.4438 Rough 0.4584 5.717E-002 7.541 0.248 0.9000 0.7000 0.7000
7 VERY HIGH REFLECTIVITY SURFACE 2.1097E-006 Smooth 0.0016 237.000 168.680 0.216 0.9000 5.0000E-002 5.0000E-002
8 GYPSUMBOARD-5/16IN 5.0054E-002 Rough 0.0260 0.159 39.954 0.270 0.9000 0.4000 0.1000
9 COPPERPIPE 4.7506E-005 MediumRough 0.0625 401.000 140.026 0.200 0.9000 0.6500 0.6500
10 F08 METAL SURFACE 1.7668E-005 Smooth 0.0026 45.280 488.437 0.119 0.9000 0.7000 0.7000
11 CONCRETE_4IN 7.7356E-002 Rough 0.3330 1.312 140.014 0.111 0.9000 0.7000 0.7000
12 ASPHALT_SHINGLE 7.7448E-002 MediumRough 0.0208 8.186E-002 70.000 0.300 0.9000 0.7500 0.7000
13 WOOD_SHINGLE 0.1115 MediumSmooth 0.0417 0.114 26.600 0.390 0.9000 0.7000 0.7000
14 SLATE_SHINGLE 8.8061E-003 MediumSmooth 0.0417 1.442 100.000 0.300 0.9000 0.7000 0.7000
15 CEMENT_STUCCO 2.6422E-002 MediumSmooth 0.0625 0.721 116.464 0.210 0.9000 0.7000 0.7000
16 SYN_STUCCO 3.5237E-002 MediumSmooth 0.0100 8.650E-002 24.971 0.210 0.9000 0.7000 0.7000
17 DRYWALL_1/2IN 7.9331E-002 MediumSmooth 0.0417 0.160 50.000 0.260 0.9000 0.7000 0.7000
18 OSB_5/8IN 0.1365 MediumSmooth 0.0521 0.116 34.000 0.290 0.9000 0.7000 0.7000
19 OSB_7/16IN 9.5550E-002 MediumSmooth 0.0365 0.116 34.000 0.290 0.9000 0.7000 0.7000
20 BLOWN_R30 5.1614 MediumRough 0.6975 4.119E-002 0.600 0.200 0.9000 0.7000 0.7000
21 BLOWN_R30_TOP 2.8489 MediumRough 0.3849 4.119E-002 0.600 0.200 0.9000 0.7000 0.7000
22 PLYWOOD_3/4IN 0.1650 Rough 0.0625 0.115 34.003 0.161 0.9000 0.7000 0.7000
23 BATT_R19 7.3089 MediumRough 0.0833 3.475E-003 0.600 0.200 0.9000 0.7000 0.7000
24 LUMBER_2X4 0.7709 Rough 0.2920 0.115 32.003 0.183 0.9000 0.7000 0.7000
25 CARPET_N_PAD 0.4224 MediumSmooth 0.0833 6.013E-002 2.000 0.200 0.9000 0.7000 0.7000
26 BATT_R13 2.2936 MediumRough 0.2917 3.876E-002 0.600 0.200 0.9000 0.7000 0.7000
27 OSB_1/2IN 0.1092 MediumSmooth 0.0417 0.116 34.000 0.290 0.9000 0.7000 0.7000
28 SOIL_12IN 0.1761 Rough 1.0000 1.731 115.011 0.056 0.9000 0.7000 0.7000
29 DOOR_CONST 0.5870 Smooth 0.1387 7.201E-002 32.003 0.183 0.9000 0.7000 0.7000
30 GYP_BOARD_1/2IN 8.0130E-002 Rough 0.0417 0.159 39.954 0.270 0.9000 0.4000 0.1000
31 STD WOOD 6INCH 1.2500 MediumSmooth 0.4921 0.120 33.711 0.289 0.9000 0.7000 0.7000
32 PIPE INSULATION 0.3830 VeryRough 0.0417 3.317E-002 5.681 0.200 0.9000 0.5000 0.5000
33 MANF_WALL_AIRGAP 0.1200 Smooth 0.0000 0.000 0.000 0.000 0.9000 0.7000 0.7000
34 BLDG_PAPER_FELT 1.0567E-002 Smooth 0.0000 0.000 0.000 0.000 0.9000 0.7000 0.7000
35 R_HIGH 177.0000 MediumRough 0.0000 0.000 0.000 0.000 0.9000 0.7000 0.7000
36 CLEAR ACRYLIC PLASTIC 3.3333E-003 VerySmooth 0.0098 0.900 0.000 0.000 0.9000 0.0000 0.0000
37 DIFFUSING ACRYLIC PLASTIC 2.4444E-003 VerySmooth 0.0072 0.900 0.000 0.000 0.9000 0.0000 0.0000
38 INT_BLIND 0.0000 Rough 0.0000 0.000 0.000 0.000 0.0000 0.0000 0.0000
39 GLASS 0.4127 VerySmooth 0.1373 0.101 0.000 0.000 0.8400 0.0000 0.0000


Material:Air

Material Name ThermalResistance {m2-K/w}
1 AIR_4_IN_VERT 0.1585
2 3/4IN_AIR_SPACE 8.5130E-002
3 3/4IN_REFLECTIVE_AIR_SPACE 0.2466
4 AIR_4_IN_VERT 0.1585


Surface Geometry

Starting Corner Vertex Input Direction Coordinate System Daylight Reference Point Coordinate System Rectangular (Simple) Surface Coordinate System
1 LowerLeftCorner Counterclockwise RelativeCoordinateSystem RelativeCoordinateSystem RelativeToZoneOrigin


Other Side Coefficients

Name Combined convective/radiative film coefficient {Btu/h-ft2-F} User selected Constant Temperature {F} Coefficient modifying the constant temperature term Coefficient modifying the external dry bulb temperature term Coefficient modifying the ground temperature term Coefficient modifying the wind speed term {s/m} Coefficient modifying the zone air temperature term Constant Temperature Schedule Name Sinusoidal Variation Period of Sinusoidal Variation Previous Other Side Temperature Coefficient Minimum Other Side Temperature {F} Maximum Other Side Temperature {F}
1 SURFPROPOTHSDCOEFSLABAVERAGE N/A N/A 1.000 0.000 0.000 0.000 0.000 SCHEDULEOSCSLABAVERAGESURFACETEMP NO 24.000 0.000 N/A N/A
2 SURFPROPOTHSDCOEFSLABPERIMETER N/A N/A 1.000 0.000 0.000 0.000 0.000 SCHEDULEOSCSLABPERIMETERTEMP NO 24.000 0.000 N/A N/A
3 SURFPROPOTHSDCOEFSLABCORE N/A N/A 1.000 0.000 0.000 0.000 0.000 SCHEDULEOSCSLABCORETEMP NO 24.000 0.000 N/A N/A


Surface Heat Transfer Algorithm

Value {CTF - ConductionTransferFunction
EMPD - MoisturePenetrationDepthConductionTransferFunction
CondFD - ConductionFiniteDifference
HAMT - CombinedHeatAndMoistureFiniteElement} - Description
Inside Surface Max Temperature Limit{F}


Surface Convection Coefficient Lower Limit {Btu/h-ft2-F}


Surface Convection Coefficient Upper Limit {Btu/h-ft2-F}


1 CTF - ConductionTransferFunction 392. 0.02 176.1


Shading Summary

Number of Fixed Detached Shades Number of Building Detached Shades Number of Attached Shades
1 0 0 60


Zone Summary

Number of Zones Number of Zone Surfaces Number of SubSurfaces
1 21 186 48


Zone Information

Zone Name North Axis {deg} Origin X-Coordinate {ft} Origin Y-Coordinate {ft} Origin Z-Coordinate {ft} Centroid X-Coordinate {ft} Centroid Y-Coordinate {ft} Centroid Z-Coordinate {ft} Type Zone Multiplier Zone List Multiplier Minimum X {ft} Maximum X {ft} Minimum Y {ft} Maximum Y {ft} Minimum Z {ft} Maximum Z {ft} Ceiling Height {ft} Volume {ft3} Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} Floor Area {ft2} Exterior Gross Wall Area {ft2} Exterior Net Wall Area {ft2} Exterior Window Area {ft2} Number of Surfaces Number of SubSurfaces Number of Shading SubSurfaces Part of Total Building Area
1 CRAWLSPACE 0.0 0.00 0.00 0.00 59.94 32.51 -0.8 1 1 1 0.00 119.89 0.00 65.10 -2.0 0.49 2.49 19513.15 TARP DOE-2 7794.37 185.05 185.05 0.00 15 0 0 Yes
2 BREEZEWAY 0.0 0.00 0.00 0.00 59.94 32.55 13.26 1 1 1 0.00 119.89 30.05 35.04 0.49 25.99 17.00 30553.07 TARP DOE-2 1798.18 0.00 0.00 0.00 4 0 0 Yes
3 LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.0 0.00 0.00 0.00 19.98 15.03 4.76 1 1 1 0.00 39.96 0.00 30.05 0.49 8.99 8.50 10207.79 TARP DOE-2 1200.51 934.94 766.25 147.70 6 3 4 Yes
4 LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.0 0.00 0.00 0.00 59.94 15.03 4.76 1 1 1 39.96 79.93 0.00 30.05 0.49 8.99 8.50 10207.79 TARP DOE-2 1200.51 679.48 599.39 59.10 6 2 2 Yes
5 LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.0 0.00 0.00 0.00 99.91 15.03 4.76 1 1 1 79.93 119.89 0.00 30.05 0.49 8.99 8.50 10207.79 TARP DOE-2 1200.51 934.94 766.25 147.70 6 3 4 Yes
6 LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.0 0.00 0.00 0.00 19.98 50.07 4.76 1 1 1 0.00 39.96 35.04 65.10 0.49 8.99 8.50 10207.79 TARP DOE-2 1200.51 934.94 766.25 147.70 6 3 4 Yes
7 LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.0 0.00 0.00 0.00 59.94 50.07 4.76 1 1 1 39.96 79.93 35.04 65.10 0.49 8.99 8.50 10207.79 TARP DOE-2 1200.51 679.48 599.39 59.10 6 2 2 Yes
8 LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.0 0.00 0.00 0.00 99.91 50.07 4.76 1 1 1 79.93 119.89 35.04 65.10 0.49 8.99 8.50 10207.79 TARP DOE-2 1200.51 934.94 766.25 147.70 6 3 4 Yes
9 LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.0 0.00 0.00 0.00 19.98 15.03 13.26 1 1 1 0.00 39.96 0.00 30.05 8.99 17.49 8.50 10207.79 TARP DOE-2 1200.51 934.94 766.25 147.70 6 3 4 Yes
10 LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.0 0.00 0.00 0.00 59.94 15.03 13.26 1 1 1 39.96 79.93 0.00 30.05 8.99 17.49 8.50 10207.79 TARP DOE-2 1200.51 679.48 599.39 59.10 6 2 2 Yes
11 LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.0 0.00 0.00 0.00 99.91 15.03 13.26 1 1 1 79.93 119.89 0.00 30.05 8.99 17.49 8.50 10207.79 TARP DOE-2 1200.51 934.94 766.25 147.70 6 3 4 Yes
12 LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.0 0.00 0.00 0.00 19.98 50.07 13.26 1 1 1 0.00 39.96 35.04 65.10 8.99 17.49 8.50 10207.79 TARP DOE-2 1200.51 934.94 766.25 147.70 6 3 4 Yes
13 LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.0 0.00 0.00 0.00 59.94 50.07 13.26 1 1 1 39.96 79.93 35.04 65.10 8.99 17.49 8.50 10207.79 TARP DOE-2 1200.51 679.48 599.39 59.10 6 2 2 Yes
14 LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.0 0.00 0.00 0.00 99.91 50.07 13.26 1 1 1 79.93 119.89 35.04 65.10 8.99 17.49 8.50 10207.79 TARP DOE-2 1200.51 934.94 766.25 147.70 6 3 4 Yes
15 ATTIC 0.0 -134.9 51.61 0.00 59.94 32.55 29.56 1 1 1 0.00 119.89 0.00 65.10 25.99 39.54 6.76 52795.39 TARP DOE-2 7802.66 881.33 881.33 0.00 11 0 0 Yes
16 LIVING_UNIT3_BACKROW_TOPFLOOR 0.0 0.00 0.00 0.00 99.91 50.07 21.75 1 1 1 79.93 119.89 35.04 65.10 17.49 25.99 8.50 10207.79 TARP DOE-2 1200.51 934.94 766.25 147.70 6 3 4 Yes
17 LIVING_UNIT3_FRONTROW_TOPFLOOR 0.0 0.00 0.00 0.00 99.91 15.03 21.75 1 1 1 79.93 119.89 0.00 30.05 17.49 25.99 8.50 10207.79 TARP DOE-2 1200.51 934.94 766.25 147.70 6 3 4 Yes
18 LIVING_UNIT1_FRONTROW_TOPFLOOR 0.0 0.00 0.00 0.00 19.98 15.03 21.75 1 1 1 0.00 39.96 0.00 30.05 17.49 25.99 8.50 10207.79 TARP DOE-2 1200.51 934.94 766.25 147.70 6 3 4 Yes
19 LIVING_UNIT2_BACKROW_TOPFLOOR 0.0 0.00 0.00 0.00 59.94 50.07 21.75 1 1 1 39.96 79.93 35.04 65.10 17.49 25.99 8.50 10207.79 TARP DOE-2 1200.51 679.48 599.39 59.10 6 2 2 Yes
20 LIVING_UNIT2_FRONTROW_TOPFLOOR 0.0 0.00 0.00 0.00 59.94 15.03 21.75 1 1 1 39.96 79.93 0.00 30.05 17.49 25.99 8.50 10207.79 TARP DOE-2 1200.51 679.48 599.39 59.10 6 2 2 Yes
21 LIVING_UNIT1_BACKROW_TOPFLOOR 0.0 0.00 0.00 0.00 19.98 50.07 21.75 1 1 1 0.00 39.96 35.04 65.10 17.49 25.99 8.50 10207.79 TARP DOE-2 1200.51 934.94 766.25 147.70 6 3 4 Yes


Zone Internal Gains Nominal

Zone Name Floor Area {ft2} # Occupants Area per Occupant {ft2/person} Occupant per Area {person/ft2} Interior Lighting {Btu/h-ft2} Electric Load {Btu/h-ft2} Gas Load {Btu/h-ft2} Other Load {Btu/h-ft2} Hot Water Eq {Btu/h-ft2} Steam Equipment {Btu/h-ft2} Sum Loads per Area {Btu/h-ft2} Outdoor Controlled Baseboard Heat
1 CRAWLSPACE 7794.37 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No
2 BREEZEWAY 1798.18 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No
3 LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 600.276 0.002 0.583 2.909 0.000 0.000 0.000 0.000 3.492 No
4 LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 600.276 0.002 0.583 2.909 0.000 0.000 0.000 0.000 3.492 No
5 LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 600.276 0.002 0.583 2.909 0.000 0.000 0.000 0.000 3.492 No
6 LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 600.276 0.002 0.583 2.909 0.000 0.000 0.000 0.000 3.492 No
7 LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 600.276 0.002 0.583 2.909 0.000 0.000 0.000 0.000 3.492 No
8 LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 600.276 0.002 0.583 2.909 0.000 0.000 0.000 0.000 3.492 No
9 LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 600.276 0.002 0.583 2.909 0.000 0.000 0.000 0.000 3.492 No
10 LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 600.276 0.002 0.583 2.909 0.000 0.000 0.000 0.000 3.492 No
11 LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 600.276 0.002 0.583 2.909 0.000 0.000 0.000 0.000 3.492 No
12 LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 600.276 0.002 0.583 2.909 0.000 0.000 0.000 0.000 3.492 No
13 LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 600.276 0.002 0.583 2.909 0.000 0.000 0.000 0.000 3.492 No
14 LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 600.276 0.002 0.583 2.909 0.000 0.000 0.000 0.000 3.492 No
15 ATTIC 7802.66 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No
16 LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 600.276 0.002 0.583 2.909 0.000 0.000 0.000 0.000 3.492 No
17 LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 600.276 0.002 0.583 2.909 0.000 0.000 0.000 0.000 3.492 No
18 LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 600.276 0.002 0.583 2.909 0.000 0.000 0.000 0.000 3.492 No
19 LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 600.276 0.002 0.583 2.909 0.000 0.000 0.000 0.000 3.492 No
20 LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 600.276 0.002 0.583 2.909 0.000 0.000 0.000 0.000 3.492 No
21 LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 600.276 0.002 0.583 2.909 0.000 0.000 0.000 0.000 3.492 No


People Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {ft2} # Zone Occupants Number of People {} People/Floor Area {person/ft2} Floor Area per person {ft2/person} Fraction Radiant Fraction Convected Sensible Fraction Calculation Activity level ASHRAE 55 Warnings Carbon Dioxide Generation Rate Nominal Minimum Number of People Nominal Maximum Number of People
1 PEOPLE_UNIT1_FRONTROW_BOTTOMFLOOR OCCUPANCY LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
2 PEOPLE_UNIT2_FRONTROW_BOTTOMFLOOR OCCUPANCY LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
3 PEOPLE_UNIT3_FRONTROW_BOTTOMFLOOR OCCUPANCY LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
4 PEOPLE_UNIT1_BACKROW_BOTTOMFLOOR OCCUPANCY LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
5 PEOPLE_UNIT2_BACKROW_BOTTOMFLOOR OCCUPANCY LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
6 PEOPLE_UNIT3_BACKROW_BOTTOMFLOOR OCCUPANCY LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
7 PEOPLE_UNIT1_FRONTROW_MIDDLEFLOOR OCCUPANCY LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
8 PEOPLE_UNIT2_FRONTROW_MIDDLEFLOOR OCCUPANCY LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
9 PEOPLE_UNIT3_FRONTROW_MIDDLEFLOOR OCCUPANCY LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
10 PEOPLE_UNIT1_BACKROW_MIDDLEFLOOR OCCUPANCY LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
11 PEOPLE_UNIT2_BACKROW_MIDDLEFLOOR OCCUPANCY LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
12 PEOPLE_UNIT3_BACKROW_MIDDLEFLOOR OCCUPANCY LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
13 PEOPLE_UNIT1_FRONTROW_TOPFLOOR OCCUPANCY LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
14 PEOPLE_UNIT2_FRONTROW_TOPFLOOR OCCUPANCY LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
15 PEOPLE_UNIT3_FRONTROW_TOPFLOOR OCCUPANCY LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
16 PEOPLE_UNIT1_BACKROW_TOPFLOOR OCCUPANCY LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
17 PEOPLE_UNIT2_BACKROW_TOPFLOOR OCCUPANCY LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
18 PEOPLE_UNIT3_BACKROW_TOPFLOOR OCCUPANCY LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2


Lights Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {ft2} # Zone Occupants Lighting Level {Btu/h} Lights/Floor Area {Btu/h-ft2} Lights per person {W/person} Fraction Return Air Fraction Radiant Fraction Short Wave Fraction Convected Fraction Replaceable End-Use Category Nominal Minimum Lighting Level {Btu/h} Nominal Maximum Lighting Level {Btu/h}
1 LIVING HARDWIRED LIGHTING1_FRONTROW_BOTTOMFLOOR INTERIORLIGHTINGHE LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 481.174 0.401 70.512 0.000 0.600 0.200 0.200 0.000 General 33.079 481.174
2 LIVING PLUG-IN LIGHTING1_FRONTROW_BOTTOMFLOOR INTERIORLIGHTINGHE LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
3 LIVING HARDWIRED LIGHTING2_FRONTROW_BOTTOMFLOOR INTERIORLIGHTINGHE LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 481.174 0.401 70.512 0.000 0.600 0.200 0.200 0.000 General 33.079 481.174
4 LIVING PLUG-IN LIGHTING2_FRONTROW_BOTTOMFLOOR INTERIORLIGHTINGHE LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
5 LIVING HARDWIRED LIGHTING3_FRONTROW_BOTTOMFLOOR INTERIORLIGHTINGHE LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 481.174 0.401 70.512 0.000 0.600 0.200 0.200 0.000 General 33.079 481.174
6 LIVING PLUG-IN LIGHTING3_FRONTROW_BOTTOMFLOOR INTERIORLIGHTINGHE LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
7 LIVING HARDWIRED LIGHTING1_BACKROW_BOTTOMFLOOR INTERIORLIGHTINGHE LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 481.174 0.401 70.512 0.000 0.600 0.200 0.200 0.000 General 33.079 481.174
8 LIVING PLUG-IN LIGHTING1_BACKROW_BOTTOMFLOOR INTERIORLIGHTINGHE LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
9 LIVING HARDWIRED LIGHTING2_BACKROW_BOTTOMFLOOR INTERIORLIGHTINGHE LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 481.174 0.401 70.512 0.000 0.600 0.200 0.200 0.000 General 33.079 481.174
10 LIVING PLUG-IN LIGHTING2_BACKROW_BOTTOMFLOOR INTERIORLIGHTINGHE LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
11 LIVING HARDWIRED LIGHTING3_BACKROW_BOTTOMFLOOR INTERIORLIGHTINGHE LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 481.174 0.401 70.512 0.000 0.600 0.200 0.200 0.000 General 33.079 481.174
12 LIVING PLUG-IN LIGHTING3_BACKROW_BOTTOMFLOOR INTERIORLIGHTINGHE LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
13 LIVING HARDWIRED LIGHTING1_FRONTROW_MIDDLEFLOOR INTERIORLIGHTINGHE LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 481.174 0.401 70.512 0.000 0.600 0.200 0.200 0.000 General 33.079 481.174
14 LIVING PLUG-IN LIGHTING1_FRONTROW_MIDDLEFLOOR INTERIORLIGHTINGHE LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
15 LIVING HARDWIRED LIGHTING2_FRONTROW_MIDDLEFLOOR INTERIORLIGHTINGHE LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 481.174 0.401 70.512 0.000 0.600 0.200 0.200 0.000 General 33.079 481.174
16 LIVING PLUG-IN LIGHTING2_FRONTROW_MIDDLEFLOOR INTERIORLIGHTINGHE LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
17 LIVING HARDWIRED LIGHTING3_FRONTROW_MIDDLEFLOOR INTERIORLIGHTINGHE LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 481.174 0.401 70.512 0.000 0.600 0.200 0.200 0.000 General 33.079 481.174
18 LIVING PLUG-IN LIGHTING3_FRONTROW_MIDDLEFLOOR INTERIORLIGHTINGHE LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
19 LIVING HARDWIRED LIGHTING1_BACKROW_MIDDLEFLOOR INTERIORLIGHTINGHE LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 481.174 0.401 70.512 0.000 0.600 0.200 0.200 0.000 General 33.079 481.174
20 LIVING PLUG-IN LIGHTING1_BACKROW_MIDDLEFLOOR INTERIORLIGHTINGHE LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
21 LIVING HARDWIRED LIGHTING2_BACKROW_MIDDLEFLOOR INTERIORLIGHTINGHE LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 481.174 0.401 70.512 0.000 0.600 0.200 0.200 0.000 General 33.079 481.174
22 LIVING PLUG-IN LIGHTING2_BACKROW_MIDDLEFLOOR INTERIORLIGHTINGHE LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
23 LIVING HARDWIRED LIGHTING3_BACKROW_MIDDLEFLOOR INTERIORLIGHTINGHE LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 481.174 0.401 70.512 0.000 0.600 0.200 0.200 0.000 General 33.079 481.174
24 LIVING PLUG-IN LIGHTING3_BACKROW_MIDDLEFLOOR INTERIORLIGHTINGHE LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
25 LIVING HARDWIRED LIGHTING1_FRONTROW_TOPFLOOR INTERIORLIGHTINGHE LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 481.174 0.401 70.512 0.000 0.600 0.200 0.200 0.000 General 33.079 481.174
26 LIVING PLUG-IN LIGHTING1_FRONTROW_TOPFLOOR INTERIORLIGHTINGHE LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
27 LIVING HARDWIRED LIGHTING2_FRONTROW_TOPFLOOR INTERIORLIGHTINGHE LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 481.174 0.401 70.512 0.000 0.600 0.200 0.200 0.000 General 33.079 481.174
28 LIVING PLUG-IN LIGHTING2_FRONTROW_TOPFLOOR INTERIORLIGHTINGHE LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
29 LIVING HARDWIRED LIGHTING3_FRONTROW_TOPFLOOR INTERIORLIGHTINGHE LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 481.174 0.401 70.512 0.000 0.600 0.200 0.200 0.000 General 33.079 481.174
30 LIVING PLUG-IN LIGHTING3_FRONTROW_TOPFLOOR INTERIORLIGHTINGHE LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
31 LIVING HARDWIRED LIGHTING1_BACKROW_TOPFLOOR INTERIORLIGHTINGHE LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 481.174 0.401 70.512 0.000 0.600 0.200 0.200 0.000 General 33.079 481.174
32 LIVING PLUG-IN LIGHTING1_BACKROW_TOPFLOOR INTERIORLIGHTINGHE LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
33 LIVING HARDWIRED LIGHTING2_BACKROW_TOPFLOOR INTERIORLIGHTINGHE LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 481.174 0.401 70.512 0.000 0.600 0.200 0.200 0.000 General 33.079 481.174
34 LIVING PLUG-IN LIGHTING2_BACKROW_TOPFLOOR INTERIORLIGHTINGHE LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
35 LIVING HARDWIRED LIGHTING3_BACKROW_TOPFLOOR INTERIORLIGHTINGHE LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 481.174 0.401 70.512 0.000 0.600 0.200 0.200 0.000 General 33.079 481.174
36 LIVING PLUG-IN LIGHTING3_BACKROW_TOPFLOOR INTERIORLIGHTINGHE LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812


ElectricEquipment Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {ft2} # Zone Occupants Equipment Level {Btu/h} Equipment/Floor Area {Btu/h-ft2} Equipment per person {W/person} Fraction Latent Fraction Radiant Fraction Lost Fraction Convected End-Use SubCategory Nominal Minimum Equipment Level {Btu/h} Nominal Maximum Equipment Level {Btu/h}
1 DISHWASHER1_FRONTROW_BOTTOMFLOOR DISHWASHER LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 166.833
2 REFRIGERATOR1_FRONTROW_BOTTOMFLOOR REFRIGERATOR LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
3 CLOTHESWASHER1_FRONTROW_BOTTOMFLOOR CLOTHESWASHER LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 72.311
4 ELECTRIC_DRYER1_FRONTROW_BOTTOMFLOOR CLOTHESDRYER LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
5 ELECTRIC_RANGE1_FRONTROW_BOTTOMFLOOR COOKINGRANGE LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
6 TELEVISION1_FRONTROW_BOTTOMFLOOR INTERIORLIGHTING LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
7 ELECTRIC_MELS1_FRONTROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
8 IECC_ADJ1_FRONTROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
9 DISHWASHER2_FRONTROW_BOTTOMFLOOR DISHWASHER LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 166.833
10 REFRIGERATOR2_FRONTROW_BOTTOMFLOOR REFRIGERATOR LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
11 CLOTHESWASHER2_FRONTROW_BOTTOMFLOOR CLOTHESWASHER LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 72.311
12 ELECTRIC_DRYER2_FRONTROW_BOTTOMFLOOR CLOTHESDRYER LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
13 ELECTRIC_RANGE2_FRONTROW_BOTTOMFLOOR COOKINGRANGE LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
14 TELEVISION2_FRONTROW_BOTTOMFLOOR INTERIORLIGHTING LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
15 ELECTRIC_MELS2_FRONTROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
16 IECC_ADJ2_FRONTROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
17 DISHWASHER3_FRONTROW_BOTTOMFLOOR DISHWASHER LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 166.833
18 REFRIGERATOR3_FRONTROW_BOTTOMFLOOR REFRIGERATOR LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
19 CLOTHESWASHER3_FRONTROW_BOTTOMFLOOR CLOTHESWASHER LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 72.311
20 ELECTRIC_DRYER3_FRONTROW_BOTTOMFLOOR CLOTHESDRYER LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
21 ELECTRIC_RANGE3_FRONTROW_BOTTOMFLOOR COOKINGRANGE LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
22 TELEVISION3_FRONTROW_BOTTOMFLOOR INTERIORLIGHTING LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
23 ELECTRIC_MELS3_FRONTROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
24 IECC_ADJ3_FRONTROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
25 DISHWASHER1_BACKROW_BOTTOMFLOOR DISHWASHER LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 166.833
26 REFRIGERATOR1_BACKROW_BOTTOMFLOOR REFRIGERATOR LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
27 CLOTHESWASHER1_BACKROW_BOTTOMFLOOR CLOTHESWASHER LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 72.311
28 ELECTRIC_DRYER1_BACKROW_BOTTOMFLOOR CLOTHESDRYER LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
29 ELECTRIC_RANGE1_BACKROW_BOTTOMFLOOR COOKINGRANGE LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
30 TELEVISION1_BACKROW_BOTTOMFLOOR INTERIORLIGHTING LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
31 ELECTRIC_MELS1_BACKROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
32 IECC_ADJ1_BACKROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
33 DISHWASHER2_BACKROW_BOTTOMFLOOR DISHWASHER LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 166.833
34 REFRIGERATOR2_BACKROW_BOTTOMFLOOR REFRIGERATOR LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
35 CLOTHESWASHER2_BACKROW_BOTTOMFLOOR CLOTHESWASHER LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 72.311
36 ELECTRIC_DRYER2_BACKROW_BOTTOMFLOOR CLOTHESDRYER LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
37 ELECTRIC_RANGE2_BACKROW_BOTTOMFLOOR COOKINGRANGE LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
38 TELEVISION2_BACKROW_BOTTOMFLOOR INTERIORLIGHTING LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
39 ELECTRIC_MELS2_BACKROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
40 IECC_ADJ2_BACKROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
41 DISHWASHER3_BACKROW_BOTTOMFLOOR DISHWASHER LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 166.833
42 REFRIGERATOR3_BACKROW_BOTTOMFLOOR REFRIGERATOR LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
43 CLOTHESWASHER3_BACKROW_BOTTOMFLOOR CLOTHESWASHER LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 72.311
44 ELECTRIC_DRYER3_BACKROW_BOTTOMFLOOR CLOTHESDRYER LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
45 ELECTRIC_RANGE3_BACKROW_BOTTOMFLOOR COOKINGRANGE LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
46 TELEVISION3_BACKROW_BOTTOMFLOOR INTERIORLIGHTING LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
47 ELECTRIC_MELS3_BACKROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
48 IECC_ADJ3_BACKROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
49 DISHWASHER1_FRONTROW_MIDDLEFLOOR DISHWASHER LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 166.833
50 REFRIGERATOR1_FRONTROW_MIDDLEFLOOR REFRIGERATOR LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
51 CLOTHESWASHER1_FRONTROW_MIDDLEFLOOR CLOTHESWASHER LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 72.311
52 ELECTRIC_DRYER1_FRONTROW_MIDDLEFLOOR CLOTHESDRYER LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
53 ELECTRIC_RANGE1_FRONTROW_MIDDLEFLOOR COOKINGRANGE LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
54 TELEVISION1_FRONTROW_MIDDLEFLOOR INTERIORLIGHTING LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
55 ELECTRIC_MELS1_FRONTROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
56 IECC_ADJ1_FRONTROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
57 DISHWASHER2_FRONTROW_MIDDLEFLOOR DISHWASHER LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 166.833
58 REFRIGERATOR2_FRONTROW_MIDDLEFLOOR REFRIGERATOR LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
59 CLOTHESWASHER2_FRONTROW_MIDDLEFLOOR CLOTHESWASHER LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 72.311
60 ELECTRIC_DRYER2_FRONTROW_MIDDLEFLOOR CLOTHESDRYER LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
61 ELECTRIC_RANGE2_FRONTROW_MIDDLEFLOOR COOKINGRANGE LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
62 TELEVISION2_FRONTROW_MIDDLEFLOOR INTERIORLIGHTING LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
63 ELECTRIC_MELS2_FRONTROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
64 IECC_ADJ2_FRONTROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
65 DISHWASHER3_FRONTROW_MIDDLEFLOOR DISHWASHER LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 166.833
66 REFRIGERATOR3_FRONTROW_MIDDLEFLOOR REFRIGERATOR LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
67 CLOTHESWASHER3_FRONTROW_MIDDLEFLOOR CLOTHESWASHER LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 72.311
68 ELECTRIC_DRYER3_FRONTROW_MIDDLEFLOOR CLOTHESDRYER LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
69 ELECTRIC_RANGE3_FRONTROW_MIDDLEFLOOR COOKINGRANGE LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
70 TELEVISION3_FRONTROW_MIDDLEFLOOR INTERIORLIGHTING LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
71 ELECTRIC_MELS3_FRONTROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
72 IECC_ADJ3_FRONTROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
73 DISHWASHER1_BACKROW_MIDDLEFLOOR DISHWASHER LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 166.833
74 REFRIGERATOR1_BACKROW_MIDDLEFLOOR REFRIGERATOR LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
75 CLOTHESWASHER1_BACKROW_MIDDLEFLOOR CLOTHESWASHER LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 72.311
76 ELECTRIC_DRYER1_BACKROW_MIDDLEFLOOR CLOTHESDRYER LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
77 ELECTRIC_RANGE1_BACKROW_MIDDLEFLOOR COOKINGRANGE LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
78 TELEVISION1_BACKROW_MIDDLEFLOOR INTERIORLIGHTING LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
79 ELECTRIC_MELS1_BACKROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
80 IECC_ADJ1_BACKROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
81 DISHWASHER2_BACKROW_MIDDLEFLOOR DISHWASHER LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 166.833
82 REFRIGERATOR2_BACKROW_MIDDLEFLOOR REFRIGERATOR LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
83 CLOTHESWASHER2_BACKROW_MIDDLEFLOOR CLOTHESWASHER LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 72.311
84 ELECTRIC_DRYER2_BACKROW_MIDDLEFLOOR CLOTHESDRYER LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
85 ELECTRIC_RANGE2_BACKROW_MIDDLEFLOOR COOKINGRANGE LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
86 TELEVISION2_BACKROW_MIDDLEFLOOR INTERIORLIGHTING LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
87 ELECTRIC_MELS2_BACKROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
88 IECC_ADJ2_BACKROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
89 DISHWASHER3_BACKROW_MIDDLEFLOOR DISHWASHER LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 166.833
90 REFRIGERATOR3_BACKROW_MIDDLEFLOOR REFRIGERATOR LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
91 CLOTHESWASHER3_BACKROW_MIDDLEFLOOR CLOTHESWASHER LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 72.311
92 ELECTRIC_DRYER3_BACKROW_MIDDLEFLOOR CLOTHESDRYER LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
93 ELECTRIC_RANGE3_BACKROW_MIDDLEFLOOR COOKINGRANGE LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
94 TELEVISION3_BACKROW_MIDDLEFLOOR INTERIORLIGHTING LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
95 ELECTRIC_MELS3_BACKROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
96 IECC_ADJ3_BACKROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
97 DISHWASHER1_FRONTROW_TOPFLOOR DISHWASHER LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 166.833
98 REFRIGERATOR1_FRONTROW_TOPFLOOR REFRIGERATOR LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
99 CLOTHESWASHER1_FRONTROW_TOPFLOOR CLOTHESWASHER LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 72.311
100 ELECTRIC_DRYER1_FRONTROW_TOPFLOOR CLOTHESDRYER LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
101 ELECTRIC_RANGE1_FRONTROW_TOPFLOOR COOKINGRANGE LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
102 TELEVISION1_FRONTROW_TOPFLOOR INTERIORLIGHTING LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
103 ELECTRIC_MELS1_FRONTROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
104 IECC_ADJ1_FRONTROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
105 DISHWASHER2_FRONTROW_TOPFLOOR DISHWASHER LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 166.833
106 REFRIGERATOR2_FRONTROW_TOPFLOOR REFRIGERATOR LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
107 CLOTHESWASHER2_FRONTROW_TOPFLOOR CLOTHESWASHER LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 72.311
108 ELECTRIC_DRYER2_FRONTROW_TOPFLOOR CLOTHESDRYER LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
109 ELECTRIC_RANGE2_FRONTROW_TOPFLOOR COOKINGRANGE LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
110 TELEVISION2_FRONTROW_TOPFLOOR INTERIORLIGHTING LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
111 ELECTRIC_MELS2_FRONTROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
112 IECC_ADJ2_FRONTROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
113 DISHWASHER3_FRONTROW_TOPFLOOR DISHWASHER LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 166.833
114 REFRIGERATOR3_FRONTROW_TOPFLOOR REFRIGERATOR LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
115 CLOTHESWASHER3_FRONTROW_TOPFLOOR CLOTHESWASHER LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 72.311
116 ELECTRIC_DRYER3_FRONTROW_TOPFLOOR CLOTHESDRYER LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
117 ELECTRIC_RANGE3_FRONTROW_TOPFLOOR COOKINGRANGE LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
118 TELEVISION3_FRONTROW_TOPFLOOR INTERIORLIGHTING LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
119 ELECTRIC_MELS3_FRONTROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
120 IECC_ADJ3_FRONTROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
121 DISHWASHER1_BACKROW_TOPFLOOR DISHWASHER LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 166.833
122 REFRIGERATOR1_BACKROW_TOPFLOOR REFRIGERATOR LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
123 CLOTHESWASHER1_BACKROW_TOPFLOOR CLOTHESWASHER LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 72.311
124 ELECTRIC_DRYER1_BACKROW_TOPFLOOR CLOTHESDRYER LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
125 ELECTRIC_RANGE1_BACKROW_TOPFLOOR COOKINGRANGE LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
126 TELEVISION1_BACKROW_TOPFLOOR INTERIORLIGHTING LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
127 ELECTRIC_MELS1_BACKROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
128 IECC_ADJ1_BACKROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
129 DISHWASHER2_BACKROW_TOPFLOOR DISHWASHER LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 166.833
130 REFRIGERATOR2_BACKROW_TOPFLOOR REFRIGERATOR LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
131 CLOTHESWASHER2_BACKROW_TOPFLOOR CLOTHESWASHER LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 72.311
132 ELECTRIC_DRYER2_BACKROW_TOPFLOOR CLOTHESDRYER LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
133 ELECTRIC_RANGE2_BACKROW_TOPFLOOR COOKINGRANGE LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
134 TELEVISION2_BACKROW_TOPFLOOR INTERIORLIGHTING LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
135 ELECTRIC_MELS2_BACKROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
136 IECC_ADJ2_BACKROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
137 DISHWASHER3_BACKROW_TOPFLOOR DISHWASHER LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 166.833
138 REFRIGERATOR3_BACKROW_TOPFLOOR REFRIGERATOR LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
139 CLOTHESWASHER3_BACKROW_TOPFLOOR CLOTHESWASHER LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 72.311
140 ELECTRIC_DRYER3_BACKROW_TOPFLOOR CLOTHESDRYER LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
141 ELECTRIC_RANGE3_BACKROW_TOPFLOOR COOKINGRANGE LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
142 TELEVISION3_BACKROW_TOPFLOOR INTERIORLIGHTING LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
143 ELECTRIC_MELS3_BACKROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
144 IECC_ADJ3_BACKROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736


Construction CTF

Construction Name Index #Layers #CTFs Time Step {Hours} ThermalConductance {Btu/h-ft2-F} OuterThermalAbsorptance InnerThermalAbsorptance OuterSolarAbsorptance InnerSolarAbsorptance Roughness
1 EXTERIOR WALL 1 5 10 0.167 0.0498 0.900 0.900 0.700 0.700 MediumSmooth
2 CEILING-FLOOR-LAYER 3 1 5 0.167 0.228 0.900 0.900 0.700 0.700 Rough
3 EXTERIOR FLOOR 4 3 8 0.167 0.0513 0.900 0.900 0.700 0.700 Rough
4 INTERIOR FLOOR 5 2 4 0.167 0.300 0.900 0.900 0.700 0.700 Rough
5 INTERIOR CEILING 6 2 13 0.167 0.0190 0.900 0.900 0.700 0.700 Rough
6 ATTIC FLOOR 7 2 13 0.167 0.0190 0.900 0.900 0.700 0.700 MediumSmooth
7 INTERIORWALL 9 3 5 0.167 0.597 0.900 0.900 0.700 0.700 MediumSmooth
8 EXTERIOR ROOF 11 2 4 0.167 0.943 0.900 0.900 0.750 0.700 MediumRough
9 EXTERIOR DOOR 14 1 5 0.167 0.300 0.900 0.900 0.700 0.700 Smooth
10 GABLE_END 16 5 6 0.167 0.428 0.900 0.900 0.700 0.700 MediumSmooth
11 CRAWL WALL 24 1 5 0.167 2.28 0.900 0.900 0.700 0.700 Rough
12 iz-EXTERIOR FLOOR 25 3 8 0.167 0.0513 0.900 0.900 0.700 0.700 MediumSmooth


Material CTF Summary

Material Name Thickness {ft} Conductivity {w/m-K} Density {lb/ft3} Specific Heat {Btu/lbm-R} ThermalResistance {m2-K/w}
1 SYN_STUCCO 0.0098 0.086 24.971 0.210 0.3524E-01
2 SHEATHING_CONSOL_LAYER 0.1020 0.035 1.255 0.350 0.8807
3 OSB_7/16IN 0.0364 0.116 34.000 0.290 0.9555E-01
4 WALL_CONSOL_LAYER 0.4584 0.057 7.541 0.248 2.444
5 DRYWALL_1/2IN 0.0417 0.160 50.000 0.260 0.7933E-01
6 LUMBER_2X4 0.2920 0.115 32.003 0.183 0.7709
7 FLOOR_CONSOL_LAYER 0.4584 0.049 3.438 0.219 2.845
8 PLYWOOD_3/4IN 0.0627 0.115 34.003 0.161 0.1650
9 CARPET_N_PAD 0.0833 0.060 2.000 0.200 0.4224
10 PLYWOOD_3/4IN 0.0627 0.115 34.003 0.161 0.1650
11 CARPET_N_PAD 0.0833 0.060 2.000 0.200 0.4224
12 CEIL_CONSOL_LAYER 1.8587 0.062 2.618 0.185 9.179
13 DRYWALL_1/2IN 0.0417 0.160 50.000 0.260 0.7933E-01
14 DRYWALL_1/2IN 0.0417 0.160 50.000 0.260 0.7933E-01
15 CEIL_CONSOL_LAYER 1.8587 0.062 2.618 0.185 9.179
16 DRYWALL_1/2IN 0.0417 0.160 50.000 0.260 0.7933E-01
17 OSB_5/8IN 0.0522 0.116 34.000 0.290 0.1365
18 DRYWALL_1/2IN 0.0417 0.160 50.000 0.260 0.7933E-01
19 ASPHALT_SHINGLE 0.0207 0.082 70.000 0.300 0.7745E-01
20 OSB_1/2IN 0.0417 0.116 34.000 0.290 0.1092
21 DOOR_CONST 0.1388 0.072 32.003 0.183 0.5870
22 CEMENT_STUCCO 0.0627 0.721 116.464 0.210 0.2642E-01
23 BLDG_PAPER_FELT 0.0000 0.000 0.000 0.000 0.1057E-01
24 OSB_5/8IN 0.0522 0.116 34.000 0.290 0.1365
25 DRYWALL_1/2IN 0.0417 0.160 50.000 0.260 0.7933E-01
26 CONCRETE_4IN 0.3330 1.312 140.014 0.111 0.7736E-01
27 CARPET_N_PAD 0.0833 0.060 2.000 0.200 0.4224
28 PLYWOOD_3/4IN 0.0627 0.115 34.003 0.161 0.1650
29 FLOOR_CONSOL_LAYER 0.4584 0.049 3.438 0.219 2.845


Material:Air

Material Name ThermalResistance {m2-K/w}
1 AIR_4_IN_VERT 0.1585
2 3/4IN_AIR_SPACE 8.5130E-002
3 3/4IN_REFLECTIVE_AIR_SPACE 0.2466
4 AIR_4_IN_VERT 0.1585


CTF

Time Outside Cross Inside Flux (except final one)
1 10 0.51360630E-08 -0.22035233E-13 0.91774209E-08 -0.50676220E-13
2 9 -0.14060012E-04 0.39159197E-12 -0.22958088E-04 0.29728831E-08
3 8 0.28980689E-02 0.65531654E-09 0.46215968E-02 -0.71708779E-05
4 7 -0.65978682E-01 0.13350779E-06 -0.16306378 0.13238707E-02
5 6 0.64596177 0.50193482E-05 2.1320981 -0.28125917E-01
6 5 -3.4215999 0.48298777E-04 -13.652056 0.25148823
7 4 10.645660 0.13839053E-03 47.881148 -1.1749737
8 3 -19.924231 0.11919231E-03 -96.040791 3.0621859
9 2 21.976583 0.26462555E-04 109.48934 -4.4404618
10 1 -13.118296 0.91387708E-06 -65.855375 3.3273744
11 0 3.2593552 0.33613880E-09 16.204438  
12 5 -0.10726087E-01 0.44268190E-05 -0.10726087E-01 0.97389233E-03
13 4 0.31857203 0.80150166E-03 0.31857203 -0.30727185E-01
14 3 -2.8372473 0.12516450E-01 -2.8372473 0.30041224
15 2 9.6667056 0.33176537E-01 9.6667056 -1.1584571
16 1 -13.322214 0.15207483E-01 -13.322214 1.8397512
17 0 6.2472388 0.62260140E-03 6.2472388  
18 8 0.57415395E-12 0.13118744E-13 0.10972129E-06 -0.16121901E-12
19 7 -0.11209345E-05 0.79302418E-09 -0.25702593E-04 0.31491488E-06
20 6 0.21835020E-03 0.55842834E-06 0.16732899E-02 -0.62999473E-04
21 5 -0.11788181E-01 0.43793696E-04 -0.40973943E-01 0.36016799E-02
22 4 0.21386917 0.66464187E-03 0.43752526 -0.72376639E-01
23 3 -1.3884299 0.23440260E-02 -2.2272953 0.54574706
24 2 3.6315139 0.19014595E-02 5.4333867 -1.6855834
25 1 -4.0346078 0.26548191E-03 -6.0131296 2.1907513
26 0 1.5944472 0.16612988E-05 2.4140608  
27 4 0.50405178E-13 0.16668152E-13 0.29402090E-13 -0.58636069E-16
28 3 -0.78967347E-05 0.18486376E-05 -0.51544008E-05 0.20741056E-12
29 2 0.37655193 0.34407043E-01 0.80677627E-01 -0.16328896E-04
30 1 -8.0349315 0.81344511 -1.1624309 0.21506451
31 0 8.9946927 0.48845120 2.4180636  
32 13 -0.95016766E-17 -0.11776553E-17 -0.33255767E-09 0.99855310E-17
33 12 0.61338794E-09 -0.58488406E-15 0.16056222E-03 -0.43490528E-09
34 11 -0.75116140E-04 -0.12733754E-14 -0.83172474E-02 0.53259175E-04
35 10 0.23489104E-02 0.19285539E-11 0.16199673 -0.16913697E-02
36 9 -0.32325933E-01 0.31831827E-09 -1.7014869 0.23684835E-01
37 8 0.25799047 0.11552332E-07 11.081256 -0.19274894
38 7 -1.3247958 0.13607244E-06 -47.903612 1.0115855
39 6 4.5908388 0.61202310E-06 142.28685 -3.5913725
40 5 -10.947340 0.11168173E-05 -294.46769 8.7955522
41 4 17.960252 0.81578039E-06 423.45640 -14.856181
42 3 -19.872933 0.21758675E-06 -414.30161 16.962607
43 2 14.135270 0.16726228E-07 262.68178 -12.475847
44 1 -5.8235685 0.25078833E-09 -97.209670 5.3243306
45 0 1.0543411 -0.72051379E-11 15.923944  
46 13 -0.33255767E-09 -0.11776553E-17 -0.95016766E-17 0.99855310E-17
47 12 0.16056222E-03 -0.58488406E-15 0.61338794E-09 -0.43490528E-09
48 11 -0.83172474E-02 -0.12733754E-14 -0.75116140E-04 0.53259175E-04
49 10 0.16199673 0.19285539E-11 0.23489104E-02 -0.16913697E-02
50 9 -1.7014869 0.31831827E-09 -0.32325933E-01 0.23684835E-01
51 8 11.081256 0.11552332E-07 0.25799047 -0.19274894
52 7 -47.903612 0.13607244E-06 -1.3247958 1.0115855
53 6 142.28685 0.61202310E-06 4.5908388 -3.5913725
54 5 -294.46769 0.11168173E-05 -10.947340 8.7955522
55 4 423.45640 0.81578039E-06 17.960252 -14.856181
56 3 -414.30161 0.21758675E-06 -19.872933 16.962607
57 2 262.68178 0.16726228E-07 14.135270 -12.475847
58 1 -97.209670 0.25078833E-09 -5.8235685 5.3243306
59 0 15.923944 -0.72051379E-11 1.0543411  
60 5 -0.27590492E-07 0.65241430E-08 -0.27590492E-07 0.17331255E-13
61 4 0.68608714E-03 0.11323974E-03 0.68608714E-03 -0.15705033E-07
62 3 -0.21538511 0.37821720E-01 -0.21538511 0.25667047E-03
63 2 5.0173519 0.62258424 5.0173519 -0.50236511E-01
64 1 -19.904252 0.86481321 -19.904252 0.58144210
65 0 16.688993 0.62060609E-01 16.688993  
66 4 0.75441920E-10 0.23883683E-10 0.47514224E-10 -0.69373194E-20
67 3 -0.33730907E-03 0.89366797E-04 -0.22574866E-03 0.77828620E-10
68 2 0.58624422 0.18542418 0.49024360 -0.17301269E-03
69 1 -11.299243 2.8799011 -8.6239668 0.15905732
70 0 15.219762 1.4410112 12.640375  
71 5 -0.32935335E-06 0.42931990E-07 -0.32935335E-06 0.47097488E-08
72 4 0.68052310E-03 0.12823787E-03 0.68052310E-03 -0.14200104E-04
73 3 -0.11535993 0.17375615E-01 -0.11535993 0.40770076E-02
74 2 2.1922172 0.21284128 2.1922172 -0.13171357
75 1 -7.8704965 0.30308566 -7.8704965 0.79499401
76 0 6.3596665 0.33276539E-01 6.3596665  
77 6 0.97988530E-11 0.43917118E-12 0.24496810E-11 -0.34892153E-15
78 5 -0.75005310E-05 0.16499726E-06 -0.28271466E-05 0.19166609E-11
79 4 0.32354224E-01 0.66949565E-03 0.10283773E-01 -0.11111676E-05
80 3 -1.8201547 0.67148336E-01 -0.62076152 0.38788549E-02
81 2 21.173821 0.53241617 7.5279938 -0.97325542E-01
82 1 -64.420211 0.46601667 -21.697519 0.64629334
83 0 46.121323 0.20873329E-01 15.867130  
84 5 -0.15664505E-06 0.43005807E-07 -0.15664505E-06 0.11899247E-09
85 4 0.10791049E-02 0.34140917E-03 0.10791049E-02 -0.15677434E-05
86 3 -0.39592122 0.90314630E-01 -0.39592122 0.13116776E-02
87 2 11.651569 1.6702487 11.651569 -0.78737360E-01
88 1 -51.506798 3.1050242 -51.506798 0.66829999
89 0 45.538973 0.42297268 45.538973  
90 8 0.10972129E-06 0.13118744E-13 0.57415395E-12 -0.16121901E-12
91 7 -0.25702593E-04 0.79302418E-09 -0.11209345E-05 0.31491488E-06
92 6 0.16732899E-02 0.55842834E-06 0.21835020E-03 -0.62999473E-04
93 5 -0.40973943E-01 0.43793696E-04 -0.11788181E-01 0.36016799E-02
94 4 0.43752526 0.66464187E-03 0.21386917 -0.72376639E-01
95 3 -2.2272953 0.23440260E-02 -1.3884299 0.54574706
96 2 5.4333867 0.19014595E-02 3.6315139 -1.6855834
97 1 -6.0131296 0.26548191E-03 -4.0346078 2.1907513
98 0 2.4140608 0.16612988E-05 1.5944472  


WindowConstruction

Construction Name Index #Layers Roughness Conductance {Btu/h-ft2-F} SHGC Solar Transmittance at Normal Incidence Visible Transmittance at Normal Incidence
1 EXTERIOR WINDOW 12 1 VerySmooth 0.300 0.335 0.248 0.883
2 INTERIOR WINDOW 13 1 VerySmooth 0.300 0.335 0.248 0.883
3 WINDOW_W_BLINDS 18 2 VerySmooth 0.300 0.309 4.646E-002 0.133
4 TDD DOME 22 1 VerySmooth 1.071 0.929 0.920 0.920
5 TDD DIFFUSER 23 1 VerySmooth 1.077 0.906 0.900 0.900


WindowMaterial:Glazing

Material Name Optical Data Type Spectral Data Set Name Thickness {ft} Solar Transmittance Front Solar Reflectance Back Solar Reflectance Visible Transmittance Front Visible Reflectance Back Visible Reflectance Infrared Transmittance Front Thermal Emissivity Back Thermal Emissivity Conductivity {W/m-K} Dirt Factor Solar Diffusing
1 GLASS SpectralAverage   0.13728 0.24698 0.55113 0.55113 0.88000 0.11900 0.11900 0.00000 0.84000 0.84000 0.10138 1.00000 No
2 GLASS SpectralAverage   0.13728 0.24698 0.55113 0.55113 0.88000 0.11900 0.11900 0.00000 0.84000 0.84000 0.10138 1.00000 No
3 GLASS SpectralAverage   0.13728 0.24698 0.55113 0.55113 0.88000 0.11900 0.11900 0.00000 0.84000 0.84000 0.10138 1.00000 No
4 CLEAR ACRYLIC PLASTIC SpectralAverage   0.00984 0.92000 5.00000E-002 5.00000E-002 0.92000 5.00000E-002 5.00000E-002 0.00000 0.90000 0.90000 0.90000 1.00000 No
5 DIFFUSING ACRYLIC PLASTIC SpectralAverage   0.00722 0.90000 8.00000E-002 8.00000E-002 0.90000 8.00000E-002 8.00000E-002 0.00000 0.90000 0.90000 0.90000 1.00000 No


WindowMaterial:Blind

Material Name Slat Width {ft} Slat Separation {ft} Slat Thickness {ft} Slat Angle {deg} Slat Beam Solar Transmittance Slat Beam Solar Front Reflectance Blind To Glass Distance {ft}
1 INT_BLIND 0.0820 0.0615 0.0033 45.000 0.000 0.500 0.164


Shadowing/Sun Position Calculations Annual Simulations

Shading Calculation Method Shading Calculation Update Frequency Method Shading Calculation Update Frequency {days} Maximum Figures in Shadow Overlap Calculations {} Polygon Clipping Algorithm Pixel Counting Resolution Sky Diffuse Modeling Algorithm Output External Shading Calculation Results Disable Self-Shading Within Shading Zone Groups Disable Self-Shading From Shading Zone Groups to Other Zones
1 PolygonClipping Periodic 20 15000. SutherlandHodgman 512 SimpleSkyDiffuseModeling No No No


Heat Pump Water Heater Information

Type Name Volume {ft3} Maximum Capacity {Btu/h} Standard Rated Recovery Efficiency Standard Rated Energy Factor "DX Coil Total Cooling Rate {W HPWH Only}"
1 WaterHeater:HeatPump:WrappedCondenser WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR 6.9509 4165.4 0.000 0.0000 785  
2 WaterHeater:HeatPump:WrappedCondenser WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR 6.9509 4165.4 0.000 0.0000 785  
3 WaterHeater:HeatPump:WrappedCondenser WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR 6.9509 4165.4 0.000 0.0000 785  
4 WaterHeater:HeatPump:WrappedCondenser WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR 6.9509 4165.4 0.000 0.0000 785  
5 WaterHeater:HeatPump:WrappedCondenser WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR 6.9509 4165.4 0.000 0.0000 785  
6 WaterHeater:HeatPump:WrappedCondenser WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR 6.9509 4165.4 0.000 0.0000 785  
7 WaterHeater:HeatPump:WrappedCondenser WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR 6.9509 4165.4 0.000 0.0000 785  
8 WaterHeater:HeatPump:WrappedCondenser WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR 6.9509 4165.4 0.000 0.0000 785  
9 WaterHeater:HeatPump:WrappedCondenser WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR 6.9509 4165.4 0.000 0.0000 785  
10 WaterHeater:HeatPump:WrappedCondenser WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR 6.9509 4165.4 0.000 0.0000 785  
11 WaterHeater:HeatPump:WrappedCondenser WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR 6.9509 4165.4 0.000 0.0000 785  
12 WaterHeater:HeatPump:WrappedCondenser WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR 6.9509 4165.4 0.000 0.0000 785  
13 WaterHeater:HeatPump:WrappedCondenser WATER HEATER_UNIT1_FRONTROW_TOPFLOOR 6.9509 4165.4 0.000 0.0000 785  
14 WaterHeater:HeatPump:WrappedCondenser WATER HEATER_UNIT2_FRONTROW_TOPFLOOR 6.9509 4165.4 0.000 0.0000 785  
15 WaterHeater:HeatPump:WrappedCondenser WATER HEATER_UNIT3_FRONTROW_TOPFLOOR 6.9509 4165.4 0.000 0.0000 785  
16 WaterHeater:HeatPump:WrappedCondenser WATER HEATER_UNIT1_BACKROW_TOPFLOOR 6.9509 4165.4 0.000 0.0000 785  
17 WaterHeater:HeatPump:WrappedCondenser WATER HEATER_UNIT2_BACKROW_TOPFLOOR 6.9509 4165.4 0.000 0.0000 785  
18 WaterHeater:HeatPump:WrappedCondenser WATER HEATER_UNIT3_BACKROW_TOPFLOOR 6.9509 4165.4 0.000 0.0000 785  


Water Heater Stratified Node Information

Node Number Height {ft} Volume {ft3} Maximum Capacity {Btu/h} Off-Cycle UA {Btu/h-F} On-Cycle UA {Btu/h-F} Number Of Inlets Number Of Outlets
1 1 5.2299 6.9509 0.000 2.9246 2.9246 1 1
2 1 5.2299 6.9509 0.000 2.9246 2.9246 1 1
3 1 5.2299 6.9509 0.000 2.9246 2.9246 1 1
4 1 5.2299 6.9509 0.000 2.9246 2.9246 1 1
5 1 5.2299 6.9509 0.000 2.9246 2.9246 1 1
6 1 5.2299 6.9509 0.000 2.9246 2.9246 1 1
7 1 5.2299 6.9509 0.000 2.9246 2.9246 1 1
8 1 5.2299 6.9509 0.000 2.9246 2.9246 1 1
9 1 5.2299 6.9509 0.000 2.9246 2.9246 1 1
10 1 5.2299 6.9509 0.000 2.9246 2.9246 1 1
11 1 5.2299 6.9509 0.000 2.9246 2.9246 1 1
12 1 5.2299 6.9509 0.000 2.9246 2.9246 1 1
13 1 5.2299 6.9509 0.000 2.9246 2.9246 1 1
14 1 5.2299 6.9509 0.000 2.9246 2.9246 1 1
15 1 5.2299 6.9509 0.000 2.9246 2.9246 1 1
16 1 5.2299 6.9509 0.000 2.9246 2.9246 1 1
17 1 5.2299 6.9509 0.000 2.9246 2.9246 1 1
18 1 5.2299 6.9509 0.000 2.9246 2.9246 1 1


ZoneInfiltration Airflow Stats Nominal

Name Schedule Name Zone Name Zone Floor Area {ft2} # Zone Occupants Design Volume Flow Rate {ft3/min} Volume Flow Rate/Floor Area {ft3/min-ft2} Volume Flow Rate/Exterior Surface Area {ft3/min-ft2} ACH - Air Changes per Hour Equation A - Constant Term Coefficient {} Equation B - Temperature Term Coefficient {1/C} Equation C - Velocity Term Coefficient {s/m} Equation D - Velocity Squared Term Coefficient {s2/m2}
1 LIVING_SHERMANGRIMSRUD_UNIT1_FRONTROW_BOTTOMFLOOR ALWAYS_AVAIL LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
2 LIVING_SHERMANGRIMSRUD_UNIT2_FRONTROW_BOTTOMFLOOR ALWAYS_AVAIL LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
3 LIVING_SHERMANGRIMSRUD_UNIT3_FRONTROW_BOTTOMFLOOR ALWAYS_AVAIL LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
4 LIVING_SHERMANGRIMSRUD_UNIT1_BACKROW_BOTTOMFLOOR ALWAYS_AVAIL LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
5 LIVING_SHERMANGRIMSRUD_UNIT2_BACKROW_BOTTOMFLOOR ALWAYS_AVAIL LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
6 LIVING_SHERMANGRIMSRUD_UNIT3_BACKROW_BOTTOMFLOOR ALWAYS_AVAIL LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
7 LIVING_SHERMANGRIMSRUD_UNIT1_FRONTROW_MIDDLEFLOOR ALWAYS_AVAIL LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
8 LIVING_SHERMANGRIMSRUD_UNIT2_FRONTROW_MIDDLEFLOOR ALWAYS_AVAIL LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
9 LIVING_SHERMANGRIMSRUD_UNIT3_FRONTROW_MIDDLEFLOOR ALWAYS_AVAIL LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
10 LIVING_SHERMANGRIMSRUD_UNIT1_BACKROW_MIDDLEFLOOR ALWAYS_AVAIL LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
11 LIVING_SHERMANGRIMSRUD_UNIT2_BACKROW_MIDDLEFLOOR ALWAYS_AVAIL LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
12 LIVING_SHERMANGRIMSRUD_UNIT3_BACKROW_MIDDLEFLOOR ALWAYS_AVAIL LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
13 LIVING_SHERMANGRIMSRUD_UNIT1_FRONTROW_TOPFLOOR ALWAYS_AVAIL LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
14 LIVING_SHERMANGRIMSRUD_UNIT2_FRONTROW_TOPFLOOR ALWAYS_AVAIL LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
15 LIVING_SHERMANGRIMSRUD_UNIT3_FRONTROW_TOPFLOOR ALWAYS_AVAIL LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
16 LIVING_SHERMANGRIMSRUD_UNIT1_BACKROW_TOPFLOOR ALWAYS_AVAIL LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
17 LIVING_SHERMANGRIMSRUD_UNIT2_BACKROW_TOPFLOOR ALWAYS_AVAIL LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
18 LIVING_SHERMANGRIMSRUD_UNIT3_BACKROW_TOPFLOOR ALWAYS_AVAIL LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
19 ATTICVENT ALWAYS_AVAIL ATTIC 7802.66 0.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
20 CRAWLVENT ALWAYS_AVAIL CRAWLSPACE 7794.37 0.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000


ZoneVentilation Airflow Stats Nominal

Name Schedule Name Zone Name Zone Floor Area {ft2} # Zone Occupants Design Volume Flow Rate {ft3/min} Volume Flow Rate/Floor Area {ft3/min-ft2} Volume Flow Rate/person Area {ft3/min-person} ACH - Air Changes per Hour Fan Type {Exhaust;Intake;Natural} Fan Pressure Rise {psi} Fan Efficiency {} Equation A - Constant Term Coefficient {} Equation B - Temperature Term Coefficient {1/C} Equation C - Velocity Term Coefficient {s/m} Equation D - Velocity Squared Term Coefficient {s2/m2} Minimum Indoor Temperature{F}/Schedule Maximum Indoor Temperature{F}/Schedule Delta Temperature{F}/Schedule Minimum Outdoor Temperature{F}/Schedule Maximum Outdoor Temperature{F}/Schedule Maximum WindSpeed{ft/min}
1 VENTILATION_UNIT1_FRONTROW_BOTTOMFLOOR ALWAYS_AVAIL LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
2 VENTILATION_UNIT2_FRONTROW_BOTTOMFLOOR ALWAYS_AVAIL LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
3 VENTILATION_UNIT3_FRONTROW_BOTTOMFLOOR ALWAYS_AVAIL LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
4 VENTILATION_UNIT1_BACKROW_BOTTOMFLOOR ALWAYS_AVAIL LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
5 VENTILATION_UNIT2_BACKROW_BOTTOMFLOOR ALWAYS_AVAIL LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
6 VENTILATION_UNIT3_BACKROW_BOTTOMFLOOR ALWAYS_AVAIL LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
7 VENTILATION_UNIT1_FRONTROW_MIDDLEFLOOR ALWAYS_AVAIL LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
8 VENTILATION_UNIT2_FRONTROW_MIDDLEFLOOR ALWAYS_AVAIL LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
9 VENTILATION_UNIT3_FRONTROW_MIDDLEFLOOR ALWAYS_AVAIL LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
10 VENTILATION_UNIT1_BACKROW_MIDDLEFLOOR ALWAYS_AVAIL LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
11 VENTILATION_UNIT2_BACKROW_MIDDLEFLOOR ALWAYS_AVAIL LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
12 VENTILATION_UNIT3_BACKROW_MIDDLEFLOOR ALWAYS_AVAIL LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
13 VENTILATION_UNIT1_FRONTROW_TOPFLOOR ALWAYS_AVAIL LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
14 VENTILATION_UNIT2_FRONTROW_TOPFLOOR ALWAYS_AVAIL LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
15 VENTILATION_UNIT3_FRONTROW_TOPFLOOR ALWAYS_AVAIL LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
16 VENTILATION_UNIT1_BACKROW_TOPFLOOR ALWAYS_AVAIL LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
17 VENTILATION_UNIT2_BACKROW_TOPFLOOR ALWAYS_AVAIL LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
18 VENTILATION_UNIT3_BACKROW_TOPFLOOR ALWAYS_AVAIL LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40


AirFlow Model

Simple
1 Simple


RoomAir Model

Zone Name Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined
1 CRAWLSPACE Mixing/Well-Stirred
2 BREEZEWAY Mixing/Well-Stirred
3 LIVING_UNIT1_FRONTROW_BOTTOMFLOOR Mixing/Well-Stirred
4 LIVING_UNIT2_FRONTROW_BOTTOMFLOOR Mixing/Well-Stirred
5 LIVING_UNIT3_FRONTROW_BOTTOMFLOOR Mixing/Well-Stirred
6 LIVING_UNIT1_BACKROW_BOTTOMFLOOR Mixing/Well-Stirred
7 LIVING_UNIT2_BACKROW_BOTTOMFLOOR Mixing/Well-Stirred
8 LIVING_UNIT3_BACKROW_BOTTOMFLOOR Mixing/Well-Stirred
9 LIVING_UNIT1_FRONTROW_MIDDLEFLOOR Mixing/Well-Stirred
10 LIVING_UNIT2_FRONTROW_MIDDLEFLOOR Mixing/Well-Stirred
11 LIVING_UNIT3_FRONTROW_MIDDLEFLOOR Mixing/Well-Stirred
12 LIVING_UNIT1_BACKROW_MIDDLEFLOOR Mixing/Well-Stirred
13 LIVING_UNIT2_BACKROW_MIDDLEFLOOR Mixing/Well-Stirred
14 LIVING_UNIT3_BACKROW_MIDDLEFLOOR Mixing/Well-Stirred
15 ATTIC Mixing/Well-Stirred
16 LIVING_UNIT3_BACKROW_TOPFLOOR Mixing/Well-Stirred
17 LIVING_UNIT3_FRONTROW_TOPFLOOR Mixing/Well-Stirred
18 LIVING_UNIT1_FRONTROW_TOPFLOOR Mixing/Well-Stirred
19 LIVING_UNIT2_BACKROW_TOPFLOOR Mixing/Well-Stirred
20 LIVING_UNIT2_FRONTROW_TOPFLOOR Mixing/Well-Stirred
21 LIVING_UNIT1_BACKROW_TOPFLOOR Mixing/Well-Stirred


AirflowNetwork Model:Control

No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation
1 NoMultizoneOrDistribution


Zone Volume Capacitance Multiplier

Sensible Heat Capacity Multiplier Moisture Capacity Multiplier Carbon Dioxide Capacity Multiplier Generic Contaminant Capacity Multiplier
1 1.000 1.000 1.000 1.000


Load Timesteps in Zone Design Calculation Averaging Window

Value
1 6


Heating Sizing Factor Information

Sizing Factor ID Value
1 Global 1.0000


Cooling Sizing Factor Information

Sizing Factor ID Value
1 Global 1.0000


Zone Sizing Information

Zone Name Load Type Calc Des Load {Btu/h} User Des Load {Btu/h} Calc Des Air Flow Rate {ft3/min} User Des Air Flow Rate {ft3/min} Design Day Name Date/Time of Peak Temperature at Peak {F} Humidity Ratio at Peak {lbWater/lbDryAir} Floor Area {ft2} # Occupants Calc Outdoor Air Flow Rate {ft3/min} Calc DOAS Heat Addition Rate {Btu/h}
1 LIVING_UNIT1_FRONTROW_BOTTOMFLOOR Cooling 9468.46545 9468.46545 489.57621 489.57621 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 90.56300 0.00570 1200.55323 2.00000 44.99491 0.00000
2 LIVING_UNIT1_FRONTROW_BOTTOMFLOOR Heating 5509.37298 5509.37298 121.93854 121.93854 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 17.78000 0.00234 1200.55323 2.00000 44.99491 0.00000
3 LIVING_UNIT2_FRONTROW_BOTTOMFLOOR Cooling 4302.05367 4302.05367 222.43641 222.43641 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 85.70300 0.00569 1200.55323 2.00000 44.99491 0.00000
4 LIVING_UNIT2_FRONTROW_BOTTOMFLOOR Heating 3863.72877 3863.72877 85.51651 85.51651 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 17.78000 0.00234 1200.55323 2.00000 44.99491 0.00000
5 LIVING_UNIT3_FRONTROW_BOTTOMFLOOR Cooling 6835.24182 6835.24182 353.43216 353.43216 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:20:00 87.16100 0.00569 1200.55323 2.00000 44.99491 0.00000
6 LIVING_UNIT3_FRONTROW_BOTTOMFLOOR Heating 5511.94587 5511.94587 121.99554 121.99554 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 17.78000 0.00234 1200.55323 2.00000 44.99491 0.00000
7 LIVING_UNIT1_BACKROW_BOTTOMFLOOR Cooling 9349.75968 9349.75968 483.43214 483.43214 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:40:00 90.15800 0.00570 1200.55323 2.00000 44.99491 0.00000
8 LIVING_UNIT1_BACKROW_BOTTOMFLOOR Heating 5512.38585 5512.38585 122.00528 122.00528 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 17.78000 0.00234 1200.55323 2.00000 44.99491 0.00000
9 LIVING_UNIT2_BACKROW_BOTTOMFLOOR Cooling 4372.93077 4372.93077 226.10167 226.10167 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 85.70300 0.00569 1200.55323 2.00000 44.99491 0.00000
10 LIVING_UNIT2_BACKROW_BOTTOMFLOOR Heating 3864.14473 3864.14473 85.52562 85.52562 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 17.78000 0.00234 1200.55323 2.00000 44.99491 0.00000
11 LIVING_UNIT3_BACKROW_BOTTOMFLOOR Cooling 6716.48106 6716.48106 347.28809 347.28809 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 09:50:00 85.25750 0.00569 1200.55323 2.00000 44.99491 0.00000
12 LIVING_UNIT3_BACKROW_BOTTOMFLOOR Heating 5509.79757 5509.79757 121.94787 121.94787 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 17.78000 0.00234 1200.55323 2.00000 44.99491 0.00000
13 LIVING_UNIT1_FRONTROW_MIDDLEFLOOR Cooling 9133.01119 9133.01119 472.24570 472.24570 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:40:00 90.15800 0.00570 1200.55323 2.00000 44.99491 0.00000
14 LIVING_UNIT1_FRONTROW_MIDDLEFLOOR Heating 3665.32411 3665.32411 81.12774 81.12774 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 17.78000 0.00234 1200.55323 2.00000 44.99491 0.00000
15 LIVING_UNIT2_FRONTROW_MIDDLEFLOOR Cooling 4166.54268 4166.54268 215.44489 215.44489 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 85.70300 0.00569 1200.55323 2.00000 44.99491 0.00000
16 LIVING_UNIT2_FRONTROW_MIDDLEFLOOR Heating 2033.17122 2033.17122 45.00254 45.00254 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 17.78000 0.00234 1200.55323 2.00000 44.99491 0.00000
17 LIVING_UNIT3_FRONTROW_MIDDLEFLOOR Cooling 6980.12142 6980.12142 360.91097 360.91097 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:30:00 87.76850 0.00569 1200.55323 2.00000 44.99491 0.00000
18 LIVING_UNIT3_FRONTROW_MIDDLEFLOOR Heating 3667.63124 3667.63124 81.17880 81.17880 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 17.78000 0.00234 1200.55323 2.00000 44.99491 0.00000
19 LIVING_UNIT1_BACKROW_MIDDLEFLOOR Cooling 9019.94969 9019.94969 466.39825 466.39825 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:50:00 89.75300 0.00569 1200.55323 2.00000 44.99491 0.00000
20 LIVING_UNIT1_BACKROW_MIDDLEFLOOR Heating 3668.06466 3668.06466 81.18855 81.18855 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 17.78000 0.00234 1200.55323 2.00000 44.99491 0.00000
21 LIVING_UNIT2_BACKROW_MIDDLEFLOOR Cooling 4204.95962 4204.95962 217.43641 217.43641 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 85.70300 0.00569 1200.55323 2.00000 44.99491 0.00000
22 LIVING_UNIT2_BACKROW_MIDDLEFLOOR Heating 2033.52228 2033.52228 45.01038 45.01038 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 17.78000 0.00234 1200.55323 2.00000 44.99491 0.00000
23 LIVING_UNIT3_BACKROW_MIDDLEFLOOR Cooling 6849.52422 6849.52422 354.15250 354.15250 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:10:00 86.55350 0.00569 1200.55323 2.00000 44.99491 0.00000
24 LIVING_UNIT3_BACKROW_MIDDLEFLOOR Heating 3665.68162 3665.68162 81.13579 81.13579 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 17.78000 0.00234 1200.55323 2.00000 44.99491 0.00000
25 LIVING_UNIT3_BACKROW_TOPFLOOR Cooling 6978.15361 6978.15361 360.80504 360.80504 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:10:00 86.55350 0.00569 1200.55323 2.00000 44.99491 0.00000
26 LIVING_UNIT3_BACKROW_TOPFLOOR Heating 5172.97643 5172.97643 114.49299 114.49299 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 17.78000 0.00234 1200.55323 2.00000 44.99491 0.00000
27 LIVING_UNIT3_FRONTROW_TOPFLOOR Cooling 7110.28601 7110.28601 367.64826 367.64826 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:30:00 87.76850 0.00569 1200.55323 2.00000 44.99491 0.00000
28 LIVING_UNIT3_FRONTROW_TOPFLOOR Heating 5172.84630 5172.84630 114.49024 114.49024 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 17.78000 0.00234 1200.55323 2.00000 44.99491 0.00000
29 LIVING_UNIT1_FRONTROW_TOPFLOOR Cooling 9571.06664 9571.06664 494.89401 494.89401 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:40:00 90.15800 0.00570 1200.55323 2.00000 44.99491 0.00000
30 LIVING_UNIT1_FRONTROW_TOPFLOOR Heating 5171.19414 5171.19414 114.45359 114.45359 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 17.78000 0.00234 1200.55323 2.00000 44.99491 0.00000
31 LIVING_UNIT2_BACKROW_TOPFLOOR Cooling 4831.61395 4831.61395 249.83048 249.83048 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 85.70300 0.00569 1200.55323 2.00000 44.99491 0.00000
32 LIVING_UNIT2_BACKROW_TOPFLOOR Heating 3527.79990 3527.79990 78.08135 78.08135 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 17.78000 0.00234 1200.55323 2.00000 44.99491 0.00000
33 LIVING_UNIT2_FRONTROW_TOPFLOOR Cooling 4689.02749 4689.02749 242.45760 242.45760 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 85.70300 0.00569 1200.55323 2.00000 44.99491 0.00000
34 LIVING_UNIT2_FRONTROW_TOPFLOOR Heating 3526.03344 3526.03344 78.04215 78.04215 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 17.78000 0.00234 1200.55323 2.00000 44.99491 0.00000
35 LIVING_UNIT1_BACKROW_TOPFLOOR Cooling 9593.92619 9593.92619 496.05926 496.05926 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:50:00 89.75300 0.00569 1200.55323 2.00000 44.99491 0.00000
36 LIVING_UNIT1_BACKROW_TOPFLOOR Heating 5174.71143 5174.71143 114.53155 114.53155 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 17.78000 0.00234 1200.55323 2.00000 44.99491 0.00000


System Sizing Information

System Name Load Type Peak Load Kind User Design Capacity Calc Des Air Flow Rate [ft3/min] User Des Air Flow Rate [ft3/min] Design Day Name Date/Time of Peak
1 CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR Cooling Sensible 2916.88 489.57621 489.57621 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
2 CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR Heating Sensible 2227.82 121.93854 121.93854 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00
3 CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR Cooling Sensible 1367.95 222.43641 222.43641 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
4 CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR Heating Sensible 1752.54 85.51651 85.51651 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00
5 CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR Cooling Sensible 2116.55 353.43216 353.43216 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
6 CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR Heating Sensible 2228.57 121.99554 121.99554 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00
7 CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR Cooling Sensible 2877.85 483.43214 483.43214 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
8 CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR Heating Sensible 2228.69 122.00528 122.00528 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00
9 CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR Cooling Sensible 1388.42 226.10167 226.10167 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
10 CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR Heating Sensible 1752.66 85.52562 85.52562 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00
11 CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR Cooling Sensible 2059.91 347.28809 347.28809 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
12 CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR Heating Sensible 2227.95 121.94787 121.94787 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00
13 CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR Cooling Sensible 2815.26 472.24570 472.24570 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
14 CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR Heating Sensible 1695.26 81.12774 81.12774 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00
15 CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR Cooling Sensible 1328.82 215.44489 215.44489 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
16 CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR Heating Sensible 1223.88 45.00254 45.00254 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00
17 CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR Cooling Sensible 2165.53 360.91097 360.91097 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
18 CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR Heating Sensible 1695.93 81.17880 81.17880 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00
19 CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR Cooling Sensible 2777.86 466.39825 466.39825 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
20 CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR Heating Sensible 1696.05 81.18855 81.18855 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00
21 CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR Cooling Sensible 1339.92 217.43641 217.43641 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
22 CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR Heating Sensible 1223.98 45.01038 45.01038 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00
23 CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR Cooling Sensible 2113.55 354.15250 354.15250 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
24 CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR Heating Sensible 1695.37 81.13579 81.13579 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00
25 CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR Cooling Sensible 2941.75 494.89401 494.89401 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
26 CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR Heating Sensible 2130.15 114.45359 114.45359 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00
27 CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR Cooling Sensible 1479.69 242.45760 242.45760 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
28 CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR Heating Sensible 1655.01 78.04215 78.04215 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00
29 CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR Cooling Sensible 2203.11 367.64826 367.64826 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
30 CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR Heating Sensible 2130.63 114.49024 114.49024 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00
31 CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR Cooling Sensible 2943.60 496.05926 496.05926 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
32 CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR Heating Sensible 2131.17 114.53155 114.53155 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00
33 CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR Cooling Sensible 1520.87 249.83048 249.83048 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
34 CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR Heating Sensible 1655.52 78.08135 78.08135 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00
35 CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR Cooling Sensible 2150.69 360.80504 360.80504 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
36 CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR Heating Sensible 2130.67 114.49299 114.49299 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00


Component Sizing Information

Component Type Component Name Input Field Description Value
1 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT1_FRONTROW_BOTTOMFLOOR User-Specified Supply Air Flow Rate [ft3/min] 44.99491
2 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT1_FRONTROW_BOTTOMFLOOR User-Specified Exhaust Air Flow Rate [ft3/min] 44.99491
3 Fan:OnOff OASUPPLYFAN_UNIT1_FRONTROW_BOTTOMFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
4 Fan:OnOff OAEXHAUSTFAN_UNIT1_FRONTROW_BOTTOMFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
5 HeatExchanger:AirToAir:SensibleAndLatent OA_HEAT_RECOVERY_UNIT1_FRONTROW_BOTTOMFLOOR User-Specified Nominal Supply Air Flow Rate [ft3/min] 44.99491
6 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT1_FRONTROW_BOTTOMFLOOR Design Size Maximum Air Flow Rate [ft3/min] 489.57621
7 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT2_FRONTROW_BOTTOMFLOOR User-Specified Supply Air Flow Rate [ft3/min] 44.99491
8 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT2_FRONTROW_BOTTOMFLOOR User-Specified Exhaust Air Flow Rate [ft3/min] 44.99491
9 Fan:OnOff OASUPPLYFAN_UNIT2_FRONTROW_BOTTOMFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
10 Fan:OnOff OAEXHAUSTFAN_UNIT2_FRONTROW_BOTTOMFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
11 HeatExchanger:AirToAir:SensibleAndLatent OA_HEAT_RECOVERY_UNIT2_FRONTROW_BOTTOMFLOOR User-Specified Nominal Supply Air Flow Rate [ft3/min] 44.99491
12 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT2_FRONTROW_BOTTOMFLOOR Design Size Maximum Air Flow Rate [ft3/min] 222.43641
13 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT3_FRONTROW_BOTTOMFLOOR User-Specified Supply Air Flow Rate [ft3/min] 44.99491
14 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT3_FRONTROW_BOTTOMFLOOR User-Specified Exhaust Air Flow Rate [ft3/min] 44.99491
15 Fan:OnOff OASUPPLYFAN_UNIT3_FRONTROW_BOTTOMFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
16 Fan:OnOff OAEXHAUSTFAN_UNIT3_FRONTROW_BOTTOMFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
17 HeatExchanger:AirToAir:SensibleAndLatent OA_HEAT_RECOVERY_UNIT3_FRONTROW_BOTTOMFLOOR User-Specified Nominal Supply Air Flow Rate [ft3/min] 44.99491
18 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT3_FRONTROW_BOTTOMFLOOR Design Size Maximum Air Flow Rate [ft3/min] 353.43216
19 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT1_BACKROW_BOTTOMFLOOR User-Specified Supply Air Flow Rate [ft3/min] 44.99491
20 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT1_BACKROW_BOTTOMFLOOR User-Specified Exhaust Air Flow Rate [ft3/min] 44.99491
21 Fan:OnOff OASUPPLYFAN_UNIT1_BACKROW_BOTTOMFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
22 Fan:OnOff OAEXHAUSTFAN_UNIT1_BACKROW_BOTTOMFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
23 HeatExchanger:AirToAir:SensibleAndLatent OA_HEAT_RECOVERY_UNIT1_BACKROW_BOTTOMFLOOR User-Specified Nominal Supply Air Flow Rate [ft3/min] 44.99491
24 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT1_BACKROW_BOTTOMFLOOR Design Size Maximum Air Flow Rate [ft3/min] 483.43214
25 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT2_BACKROW_BOTTOMFLOOR User-Specified Supply Air Flow Rate [ft3/min] 44.99491
26 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT2_BACKROW_BOTTOMFLOOR User-Specified Exhaust Air Flow Rate [ft3/min] 44.99491
27 Fan:OnOff OASUPPLYFAN_UNIT2_BACKROW_BOTTOMFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
28 Fan:OnOff OAEXHAUSTFAN_UNIT2_BACKROW_BOTTOMFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
29 HeatExchanger:AirToAir:SensibleAndLatent OA_HEAT_RECOVERY_UNIT2_BACKROW_BOTTOMFLOOR User-Specified Nominal Supply Air Flow Rate [ft3/min] 44.99491
30 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT2_BACKROW_BOTTOMFLOOR Design Size Maximum Air Flow Rate [ft3/min] 226.10167
31 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT3_BACKROW_BOTTOMFLOOR User-Specified Supply Air Flow Rate [ft3/min] 44.99491
32 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT3_BACKROW_BOTTOMFLOOR User-Specified Exhaust Air Flow Rate [ft3/min] 44.99491
33 Fan:OnOff OASUPPLYFAN_UNIT3_BACKROW_BOTTOMFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
34 Fan:OnOff OAEXHAUSTFAN_UNIT3_BACKROW_BOTTOMFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
35 HeatExchanger:AirToAir:SensibleAndLatent OA_HEAT_RECOVERY_UNIT3_BACKROW_BOTTOMFLOOR User-Specified Nominal Supply Air Flow Rate [ft3/min] 44.99491
36 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT3_BACKROW_BOTTOMFLOOR Design Size Maximum Air Flow Rate [ft3/min] 347.28809
37 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT1_FRONTROW_MIDDLEFLOOR User-Specified Supply Air Flow Rate [ft3/min] 44.99491
38 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT1_FRONTROW_MIDDLEFLOOR User-Specified Exhaust Air Flow Rate [ft3/min] 44.99491
39 Fan:OnOff OASUPPLYFAN_UNIT1_FRONTROW_MIDDLEFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
40 Fan:OnOff OAEXHAUSTFAN_UNIT1_FRONTROW_MIDDLEFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
41 HeatExchanger:AirToAir:SensibleAndLatent OA_HEAT_RECOVERY_UNIT1_FRONTROW_MIDDLEFLOOR User-Specified Nominal Supply Air Flow Rate [ft3/min] 44.99491
42 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT1_FRONTROW_MIDDLEFLOOR Design Size Maximum Air Flow Rate [ft3/min] 472.24570
43 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT2_FRONTROW_MIDDLEFLOOR User-Specified Supply Air Flow Rate [ft3/min] 44.99491
44 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT2_FRONTROW_MIDDLEFLOOR User-Specified Exhaust Air Flow Rate [ft3/min] 44.99491
45 Fan:OnOff OASUPPLYFAN_UNIT2_FRONTROW_MIDDLEFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
46 Fan:OnOff OAEXHAUSTFAN_UNIT2_FRONTROW_MIDDLEFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
47 HeatExchanger:AirToAir:SensibleAndLatent OA_HEAT_RECOVERY_UNIT2_FRONTROW_MIDDLEFLOOR User-Specified Nominal Supply Air Flow Rate [ft3/min] 44.99491
48 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT2_FRONTROW_MIDDLEFLOOR Design Size Maximum Air Flow Rate [ft3/min] 215.44489
49 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT3_FRONTROW_MIDDLEFLOOR User-Specified Supply Air Flow Rate [ft3/min] 44.99491
50 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT3_FRONTROW_MIDDLEFLOOR User-Specified Exhaust Air Flow Rate [ft3/min] 44.99491
51 Fan:OnOff OASUPPLYFAN_UNIT3_FRONTROW_MIDDLEFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
52 Fan:OnOff OAEXHAUSTFAN_UNIT3_FRONTROW_MIDDLEFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
53 HeatExchanger:AirToAir:SensibleAndLatent OA_HEAT_RECOVERY_UNIT3_FRONTROW_MIDDLEFLOOR User-Specified Nominal Supply Air Flow Rate [ft3/min] 44.99491
54 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT3_FRONTROW_MIDDLEFLOOR Design Size Maximum Air Flow Rate [ft3/min] 360.91097
55 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT1_BACKROW_MIDDLEFLOOR User-Specified Supply Air Flow Rate [ft3/min] 44.99491
56 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT1_BACKROW_MIDDLEFLOOR User-Specified Exhaust Air Flow Rate [ft3/min] 44.99491
57 Fan:OnOff OASUPPLYFAN_UNIT1_BACKROW_MIDDLEFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
58 Fan:OnOff OAEXHAUSTFAN_UNIT1_BACKROW_MIDDLEFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
59 HeatExchanger:AirToAir:SensibleAndLatent OA_HEAT_RECOVERY_UNIT1_BACKROW_MIDDLEFLOOR User-Specified Nominal Supply Air Flow Rate [ft3/min] 44.99491
60 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT1_BACKROW_MIDDLEFLOOR Design Size Maximum Air Flow Rate [ft3/min] 466.39825
61 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT2_BACKROW_MIDDLEFLOOR User-Specified Supply Air Flow Rate [ft3/min] 44.99491
62 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT2_BACKROW_MIDDLEFLOOR User-Specified Exhaust Air Flow Rate [ft3/min] 44.99491
63 Fan:OnOff OASUPPLYFAN_UNIT2_BACKROW_MIDDLEFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
64 Fan:OnOff OAEXHAUSTFAN_UNIT2_BACKROW_MIDDLEFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
65 HeatExchanger:AirToAir:SensibleAndLatent OA_HEAT_RECOVERY_UNIT2_BACKROW_MIDDLEFLOOR User-Specified Nominal Supply Air Flow Rate [ft3/min] 44.99491
66 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT2_BACKROW_MIDDLEFLOOR Design Size Maximum Air Flow Rate [ft3/min] 217.43641
67 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT3_BACKROW_MIDDLEFLOOR User-Specified Supply Air Flow Rate [ft3/min] 44.99491
68 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT3_BACKROW_MIDDLEFLOOR User-Specified Exhaust Air Flow Rate [ft3/min] 44.99491
69 Fan:OnOff OASUPPLYFAN_UNIT3_BACKROW_MIDDLEFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
70 Fan:OnOff OAEXHAUSTFAN_UNIT3_BACKROW_MIDDLEFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
71 HeatExchanger:AirToAir:SensibleAndLatent OA_HEAT_RECOVERY_UNIT3_BACKROW_MIDDLEFLOOR User-Specified Nominal Supply Air Flow Rate [ft3/min] 44.99491
72 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT3_BACKROW_MIDDLEFLOOR Design Size Maximum Air Flow Rate [ft3/min] 354.15250
73 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT3_BACKROW_TOPFLOOR User-Specified Supply Air Flow Rate [ft3/min] 44.99491
74 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT3_BACKROW_TOPFLOOR User-Specified Exhaust Air Flow Rate [ft3/min] 44.99491
75 Fan:OnOff OASUPPLYFAN_UNIT3_BACKROW_TOPFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
76 Fan:OnOff OAEXHAUSTFAN_UNIT3_BACKROW_TOPFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
77 HeatExchanger:AirToAir:SensibleAndLatent OA_HEAT_RECOVERY_UNIT3_BACKROW_TOPFLOOR User-Specified Nominal Supply Air Flow Rate [ft3/min] 44.99491
78 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT3_BACKROW_TOPFLOOR Design Size Maximum Air Flow Rate [ft3/min] 360.80504
79 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT3_FRONTROW_TOPFLOOR User-Specified Supply Air Flow Rate [ft3/min] 44.99491
80 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT3_FRONTROW_TOPFLOOR User-Specified Exhaust Air Flow Rate [ft3/min] 44.99491
81 Fan:OnOff OASUPPLYFAN_UNIT3_FRONTROW_TOPFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
82 Fan:OnOff OAEXHAUSTFAN_UNIT3_FRONTROW_TOPFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
83 HeatExchanger:AirToAir:SensibleAndLatent OA_HEAT_RECOVERY_UNIT3_FRONTROW_TOPFLOOR User-Specified Nominal Supply Air Flow Rate [ft3/min] 44.99491
84 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT3_FRONTROW_TOPFLOOR Design Size Maximum Air Flow Rate [ft3/min] 367.64826
85 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT1_FRONTROW_TOPFLOOR User-Specified Supply Air Flow Rate [ft3/min] 44.99491
86 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT1_FRONTROW_TOPFLOOR User-Specified Exhaust Air Flow Rate [ft3/min] 44.99491
87 Fan:OnOff OASUPPLYFAN_UNIT1_FRONTROW_TOPFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
88 Fan:OnOff OAEXHAUSTFAN_UNIT1_FRONTROW_TOPFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
89 HeatExchanger:AirToAir:SensibleAndLatent OA_HEAT_RECOVERY_UNIT1_FRONTROW_TOPFLOOR User-Specified Nominal Supply Air Flow Rate [ft3/min] 44.99491
90 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT1_FRONTROW_TOPFLOOR Design Size Maximum Air Flow Rate [ft3/min] 494.89401
91 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT2_BACKROW_TOPFLOOR User-Specified Supply Air Flow Rate [ft3/min] 44.99491
92 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT2_BACKROW_TOPFLOOR User-Specified Exhaust Air Flow Rate [ft3/min] 44.99491
93 Fan:OnOff OASUPPLYFAN_UNIT2_BACKROW_TOPFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
94 Fan:OnOff OAEXHAUSTFAN_UNIT2_BACKROW_TOPFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
95 HeatExchanger:AirToAir:SensibleAndLatent OA_HEAT_RECOVERY_UNIT2_BACKROW_TOPFLOOR User-Specified Nominal Supply Air Flow Rate [ft3/min] 44.99491
96 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT2_BACKROW_TOPFLOOR Design Size Maximum Air Flow Rate [ft3/min] 249.83048
97 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT2_FRONTROW_TOPFLOOR User-Specified Supply Air Flow Rate [ft3/min] 44.99491
98 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT2_FRONTROW_TOPFLOOR User-Specified Exhaust Air Flow Rate [ft3/min] 44.99491
99 Fan:OnOff OASUPPLYFAN_UNIT2_FRONTROW_TOPFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
100 Fan:OnOff OAEXHAUSTFAN_UNIT2_FRONTROW_TOPFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
101 HeatExchanger:AirToAir:SensibleAndLatent OA_HEAT_RECOVERY_UNIT2_FRONTROW_TOPFLOOR User-Specified Nominal Supply Air Flow Rate [ft3/min] 44.99491
102 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT2_FRONTROW_TOPFLOOR Design Size Maximum Air Flow Rate [ft3/min] 242.45760
103 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT1_BACKROW_TOPFLOOR User-Specified Supply Air Flow Rate [ft3/min] 44.99491
104 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT1_BACKROW_TOPFLOOR User-Specified Exhaust Air Flow Rate [ft3/min] 44.99491
105 Fan:OnOff OASUPPLYFAN_UNIT1_BACKROW_TOPFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
106 Fan:OnOff OAEXHAUSTFAN_UNIT1_BACKROW_TOPFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
107 HeatExchanger:AirToAir:SensibleAndLatent OA_HEAT_RECOVERY_UNIT1_BACKROW_TOPFLOOR User-Specified Nominal Supply Air Flow Rate [ft3/min] 44.99491
108 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT1_BACKROW_TOPFLOOR Design Size Maximum Air Flow Rate [ft3/min] 496.05926
109 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 489.57621
110 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 489.57621
111 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 489.57621
112 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 489.57621
113 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 489.57621
114 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 489.57621
115 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR User Heating Air Flow Ratio [] 1.00000
116 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR Calculated Heating Air Flow Ratio [] 1.00000
117 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 222.43641
118 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 222.43641
119 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 222.43641
120 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 222.43641
121 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 222.43641
122 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 222.43641
123 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR User Heating Air Flow Ratio [] 1.00000
124 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR Calculated Heating Air Flow Ratio [] 1.00000
125 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 353.43216
126 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 353.43216
127 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 353.43216
128 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 353.43216
129 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 353.43216
130 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 353.43216
131 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR User Heating Air Flow Ratio [] 1.00000
132 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR Calculated Heating Air Flow Ratio [] 1.00000
133 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 483.43214
134 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 483.43214
135 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 483.43214
136 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 483.43214
137 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 483.43214
138 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 483.43214
139 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR User Heating Air Flow Ratio [] 1.00000
140 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR Calculated Heating Air Flow Ratio [] 1.00000
141 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 226.10167
142 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 226.10167
143 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 226.10167
144 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 226.10167
145 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 226.10167
146 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 226.10167
147 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR User Heating Air Flow Ratio [] 1.00000
148 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR Calculated Heating Air Flow Ratio [] 1.00000
149 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 347.28809
150 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 347.28809
151 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 347.28809
152 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 347.28809
153 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 347.28809
154 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 347.28809
155 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR User Heating Air Flow Ratio [] 1.00000
156 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR Calculated Heating Air Flow Ratio [] 1.00000
157 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 472.24570
158 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 472.24570
159 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 472.24570
160 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 472.24570
161 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 472.24570
162 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 472.24570
163 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR User Heating Air Flow Ratio [] 1.00000
164 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR Calculated Heating Air Flow Ratio [] 1.00000
165 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 215.44489
166 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 215.44489
167 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 215.44489
168 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 215.44489
169 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 215.44489
170 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 215.44489
171 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR User Heating Air Flow Ratio [] 1.00000
172 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR Calculated Heating Air Flow Ratio [] 1.00000
173 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 360.91097
174 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 360.91097
175 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 360.91097
176 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 360.91097
177 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 360.91097
178 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 360.91097
179 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR User Heating Air Flow Ratio [] 1.00000
180 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR Calculated Heating Air Flow Ratio [] 1.00000
181 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 466.39825
182 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 466.39825
183 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 466.39825
184 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 466.39825
185 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 466.39825
186 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 466.39825
187 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR User Heating Air Flow Ratio [] 1.00000
188 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR Calculated Heating Air Flow Ratio [] 1.00000
189 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 217.43641
190 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 217.43641
191 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 217.43641
192 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 217.43641
193 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 217.43641
194 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 217.43641
195 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR User Heating Air Flow Ratio [] 1.00000
196 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR Calculated Heating Air Flow Ratio [] 1.00000
197 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 354.15250
198 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 354.15250
199 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 354.15250
200 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 354.15250
201 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 354.15250
202 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 354.15250
203 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR User Heating Air Flow Ratio [] 1.00000
204 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR Calculated Heating Air Flow Ratio [] 1.00000
205 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 494.89401
206 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 494.89401
207 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 494.89401
208 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 494.89401
209 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 494.89401
210 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 494.89401
211 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR User Heating Air Flow Ratio [] 1.00000
212 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR Calculated Heating Air Flow Ratio [] 1.00000
213 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 242.45760
214 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 242.45760
215 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 242.45760
216 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 242.45760
217 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 242.45760
218 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 242.45760
219 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR User Heating Air Flow Ratio [] 1.00000
220 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR Calculated Heating Air Flow Ratio [] 1.00000
221 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 367.64826
222 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 367.64826
223 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 367.64826
224 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 367.64826
225 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 367.64826
226 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 367.64826
227 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR User Heating Air Flow Ratio [] 1.00000
228 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR Calculated Heating Air Flow Ratio [] 1.00000
229 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 496.05926
230 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 496.05926
231 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 496.05926
232 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 496.05926
233 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 496.05926
234 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 496.05926
235 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR User Heating Air Flow Ratio [] 1.00000
236 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR Calculated Heating Air Flow Ratio [] 1.00000
237 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 249.83048
238 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 249.83048
239 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 249.83048
240 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 249.83048
241 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 249.83048
242 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 249.83048
243 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR User Heating Air Flow Ratio [] 1.00000
244 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR Calculated Heating Air Flow Ratio [] 1.00000
245 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 360.80504
246 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 360.80504
247 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 360.80504
248 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 360.80504
249 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 360.80504
250 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 360.80504
251 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR User Heating Air Flow Ratio [] 1.00000
252 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR Calculated Heating Air Flow Ratio [] 1.00000
253 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR Design Supply Air Flow Rate [ft3/min] 489.57621
254 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR Design Supply Air Flow Rate [ft3/min] 222.43641
255 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR Design Supply Air Flow Rate [ft3/min] 353.43216
256 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR Design Supply Air Flow Rate [ft3/min] 483.43214
257 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR Design Supply Air Flow Rate [ft3/min] 226.10167
258 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR Design Supply Air Flow Rate [ft3/min] 347.28809
259 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR Design Supply Air Flow Rate [ft3/min] 472.24570
260 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR Design Supply Air Flow Rate [ft3/min] 215.44489
261 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR Design Supply Air Flow Rate [ft3/min] 360.91097
262 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR Design Supply Air Flow Rate [ft3/min] 466.39825
263 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR Design Supply Air Flow Rate [ft3/min] 217.43641
264 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR Design Supply Air Flow Rate [ft3/min] 354.15250
265 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR Design Supply Air Flow Rate [ft3/min] 494.89401
266 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR Design Supply Air Flow Rate [ft3/min] 242.45760
267 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR Design Supply Air Flow Rate [ft3/min] 367.64826
268 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR Design Supply Air Flow Rate [ft3/min] 496.05926
269 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR Design Supply Air Flow Rate [ft3/min] 249.83048
270 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR Design Supply Air Flow Rate [ft3/min] 360.80504
271 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Design Size Rated Air Flow Rate [ft3/min] 489.57621
272 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 1.08764
273 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Design Size Gross Rated Sensible Heat Ratio 0.80066
274 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR Supply Air Flow Rate [ft3/min] 489.57621
275 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 489.57621
276 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 489.57621
277 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR Nominal Heating Capacity [Btu/h] 7601.33730
278 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR Nominal Cooling Capacity [ton] 1.08764
279 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
280 Fan:OnOff SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR Design Size Maximum Flow Rate [ft3/min] 489.57621
281 Coil:Heating:Electric MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Design Size Nominal Capacity [Btu/h] 7601.33730
282 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Design Size Rated Air Flow Rate [ft3/min] 222.43641
283 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 0.49418
284 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Design Size Gross Rated Sensible Heat Ratio 0.80066
285 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR Supply Air Flow Rate [ft3/min] 222.43641
286 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 222.43641
287 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 222.43641
288 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR Nominal Heating Capacity [Btu/h] 5979.68303
289 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR Nominal Cooling Capacity [ton] 0.49418
290 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
291 Fan:OnOff SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR Design Size Maximum Flow Rate [ft3/min] 222.43641
292 Coil:Heating:Electric MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Design Size Nominal Capacity [Btu/h] 5979.68303
293 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Design Size Rated Air Flow Rate [ft3/min] 353.43216
294 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 0.78515
295 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Design Size Gross Rated Sensible Heat Ratio 0.80066
296 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR Supply Air Flow Rate [ft3/min] 353.43216
297 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 353.43216
298 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 353.43216
299 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR Nominal Heating Capacity [Btu/h] 7603.87272
300 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR Nominal Cooling Capacity [ton] 0.78515
301 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
302 Fan:OnOff SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR Design Size Maximum Flow Rate [ft3/min] 353.43216
303 Coil:Heating:Electric MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Design Size Nominal Capacity [Btu/h] 7603.87272
304 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR Design Size Rated Air Flow Rate [ft3/min] 483.43214
305 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 1.07400
306 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR Design Size Gross Rated Sensible Heat Ratio 0.80066
307 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_BOTTOMFLOOR Supply Air Flow Rate [ft3/min] 483.43214
308 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_BOTTOMFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 483.43214
309 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_BOTTOMFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 483.43214
310 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_BOTTOMFLOOR Nominal Heating Capacity [Btu/h] 7604.30632
311 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_BOTTOMFLOOR Nominal Cooling Capacity [ton] 1.07400
312 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_BOTTOMFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
313 Fan:OnOff SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR Design Size Maximum Flow Rate [ft3/min] 483.43214
314 Coil:Heating:Electric MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR Design Size Nominal Capacity [Btu/h] 7604.30632
315 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR Design Size Rated Air Flow Rate [ft3/min] 226.10167
316 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 0.50232
317 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR Design Size Gross Rated Sensible Heat Ratio 0.80066
318 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_BOTTOMFLOOR Supply Air Flow Rate [ft3/min] 226.10167
319 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_BOTTOMFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 226.10167
320 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_BOTTOMFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 226.10167
321 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_BOTTOMFLOOR Nominal Heating Capacity [Btu/h] 5980.09295
322 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_BOTTOMFLOOR Nominal Cooling Capacity [ton] 0.50232
323 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_BOTTOMFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
324 Fan:OnOff SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR Design Size Maximum Flow Rate [ft3/min] 226.10167
325 Coil:Heating:Electric MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR Design Size Nominal Capacity [Btu/h] 5980.09295
326 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR Design Size Rated Air Flow Rate [ft3/min] 347.28809
327 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 0.77151
328 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR Design Size Gross Rated Sensible Heat Ratio 0.80066
329 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_BOTTOMFLOOR Supply Air Flow Rate [ft3/min] 347.28809
330 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_BOTTOMFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 347.28809
331 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_BOTTOMFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 347.28809
332 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_BOTTOMFLOOR Nominal Heating Capacity [Btu/h] 7601.75574
333 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_BOTTOMFLOOR Nominal Cooling Capacity [ton] 0.77151
334 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_BOTTOMFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
335 Fan:OnOff SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR Design Size Maximum Flow Rate [ft3/min] 347.28809
336 Coil:Heating:Electric MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR Design Size Nominal Capacity [Btu/h] 7601.75574
337 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Design Size Rated Air Flow Rate [ft3/min] 472.24570
338 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 1.04911
339 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Design Size Gross Rated Sensible Heat Ratio 0.80066
340 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR Supply Air Flow Rate [ft3/min] 472.24570
341 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 472.24570
342 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 472.24570
343 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR Nominal Heating Capacity [Btu/h] 5784.23490
344 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR Nominal Cooling Capacity [ton] 1.04911
345 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
346 Fan:OnOff SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR Design Size Maximum Flow Rate [ft3/min] 472.24570
347 Coil:Heating:Electric MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Design Size Nominal Capacity [Btu/h] 5784.23490
348 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Design Size Rated Air Flow Rate [ft3/min] 215.44489
349 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 0.47862
350 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Design Size Gross Rated Sensible Heat Ratio 0.80066
351 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR Supply Air Flow Rate [ft3/min] 215.44489
352 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 215.44489
353 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 215.44489
354 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR Nominal Heating Capacity [Btu/h] 4175.88259
355 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR Nominal Cooling Capacity [ton] 0.47862
356 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
357 Fan:OnOff SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR Design Size Maximum Flow Rate [ft3/min] 215.44489
358 Coil:Heating:Electric MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Design Size Nominal Capacity [Btu/h] 4175.88259
359 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Design Size Rated Air Flow Rate [ft3/min] 360.91097
360 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 0.80180
361 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Design Size Gross Rated Sensible Heat Ratio 0.80066
362 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR Supply Air Flow Rate [ft3/min] 360.91097
363 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 360.91097
364 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 360.91097
365 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR Nominal Heating Capacity [Btu/h] 5786.50838
366 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR Nominal Cooling Capacity [ton] 0.80180
367 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
368 Fan:OnOff SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR Design Size Maximum Flow Rate [ft3/min] 360.91097
369 Coil:Heating:Electric MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Design Size Nominal Capacity [Btu/h] 5786.50838
370 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR Design Size Rated Air Flow Rate [ft3/min] 466.39825
371 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 1.03613
372 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR Design Size Gross Rated Sensible Heat Ratio 0.80066
373 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_MIDDLEFLOOR Supply Air Flow Rate [ft3/min] 466.39825
374 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_MIDDLEFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 466.39825
375 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_MIDDLEFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 466.39825
376 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_MIDDLEFLOOR Nominal Heating Capacity [Btu/h] 5786.93553
377 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_MIDDLEFLOOR Nominal Cooling Capacity [ton] 1.03613
378 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_MIDDLEFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
379 Fan:OnOff SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR Design Size Maximum Flow Rate [ft3/min] 466.39825
380 Coil:Heating:Electric MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR Design Size Nominal Capacity [Btu/h] 5786.93553
381 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR Design Size Rated Air Flow Rate [ft3/min] 217.43641
382 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 0.48303
383 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR Design Size Gross Rated Sensible Heat Ratio 0.80066
384 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_MIDDLEFLOOR Supply Air Flow Rate [ft3/min] 217.43641
385 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_MIDDLEFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 217.43641
386 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_MIDDLEFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 217.43641
387 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_MIDDLEFLOOR Nominal Heating Capacity [Btu/h] 4176.22853
388 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_MIDDLEFLOOR Nominal Cooling Capacity [ton] 0.48303
389 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_MIDDLEFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
390 Fan:OnOff SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR Design Size Maximum Flow Rate [ft3/min] 217.43641
391 Coil:Heating:Electric MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR Design Size Nominal Capacity [Btu/h] 4176.22853
392 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR Design Size Rated Air Flow Rate [ft3/min] 354.15250
393 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 0.78680
394 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR Design Size Gross Rated Sensible Heat Ratio 0.80066
395 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_MIDDLEFLOOR Supply Air Flow Rate [ft3/min] 354.15250
396 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_MIDDLEFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 354.15250
397 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_MIDDLEFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 354.15250
398 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_MIDDLEFLOOR Nominal Heating Capacity [Btu/h] 5784.58719
399 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_MIDDLEFLOOR Nominal Cooling Capacity [ton] 0.78680
400 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_MIDDLEFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
401 Fan:OnOff SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR Design Size Maximum Flow Rate [ft3/min] 354.15250
402 Coil:Heating:Electric MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR Design Size Nominal Capacity [Btu/h] 5784.58719
403 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR Design Size Rated Air Flow Rate [ft3/min] 494.89401
404 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 1.09942
405 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR Design Size Gross Rated Sensible Heat Ratio 0.80066
406 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_TOPFLOOR Supply Air Flow Rate [ft3/min] 494.89401
407 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_TOPFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 494.89401
408 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_TOPFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 494.89401
409 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_TOPFLOOR Nominal Heating Capacity [Btu/h] 7268.08473
410 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_TOPFLOOR Nominal Cooling Capacity [ton] 1.09942
411 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_TOPFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
412 Fan:OnOff SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR Design Size Maximum Flow Rate [ft3/min] 494.89401
413 Coil:Heating:Electric MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_TOPFLOOR Design Size Nominal Capacity [Btu/h] 7268.08473
414 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR Design Size Rated Air Flow Rate [ft3/min] 242.45760
415 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 0.53863
416 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR Design Size Gross Rated Sensible Heat Ratio 0.80066
417 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_TOPFLOOR Supply Air Flow Rate [ft3/min] 242.45760
418 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_TOPFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 242.45760
419 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_TOPFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 242.45760
420 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_TOPFLOOR Nominal Heating Capacity [Btu/h] 5646.90743
421 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_TOPFLOOR Nominal Cooling Capacity [ton] 0.53863
422 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_TOPFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
423 Fan:OnOff SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR Design Size Maximum Flow Rate [ft3/min] 242.45760
424 Coil:Heating:Electric MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_TOPFLOOR Design Size Nominal Capacity [Btu/h] 5646.90743
425 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR Design Size Rated Air Flow Rate [ft3/min] 367.64826
426 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 0.81675
427 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR Design Size Gross Rated Sensible Heat Ratio 0.80066
428 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_TOPFLOOR Supply Air Flow Rate [ft3/min] 367.64826
429 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_TOPFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 367.64826
430 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_TOPFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 367.64826
431 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_TOPFLOOR Nominal Heating Capacity [Btu/h] 7269.71280
432 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_TOPFLOOR Nominal Cooling Capacity [ton] 0.81675
433 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_TOPFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
434 Fan:OnOff SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR Design Size Maximum Flow Rate [ft3/min] 367.64826
435 Coil:Heating:Electric MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_TOPFLOOR Design Size Nominal Capacity [Btu/h] 7269.71280
436 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR Design Size Rated Air Flow Rate [ft3/min] 496.05926
437 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 1.10205
438 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR Design Size Gross Rated Sensible Heat Ratio 0.80066
439 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_TOPFLOOR Supply Air Flow Rate [ft3/min] 496.05926
440 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_TOPFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 496.05926
441 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_TOPFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 496.05926
442 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_TOPFLOOR Nominal Heating Capacity [Btu/h] 7271.55078
443 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_TOPFLOOR Nominal Cooling Capacity [ton] 1.10205
444 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_TOPFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
445 Fan:OnOff SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR Design Size Maximum Flow Rate [ft3/min] 496.05926
446 Coil:Heating:Electric MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_TOPFLOOR Design Size Nominal Capacity [Btu/h] 7271.55078
447 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR Design Size Rated Air Flow Rate [ft3/min] 249.83048
448 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 0.55501
449 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR Design Size Gross Rated Sensible Heat Ratio 0.80066
450 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_TOPFLOOR Supply Air Flow Rate [ft3/min] 249.83048
451 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_TOPFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 249.83048
452 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_TOPFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 249.83048
453 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_TOPFLOOR Nominal Heating Capacity [Btu/h] 5648.64816
454 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_TOPFLOOR Nominal Cooling Capacity [ton] 0.55501
455 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_TOPFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
456 Fan:OnOff SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR Design Size Maximum Flow Rate [ft3/min] 249.83048
457 Coil:Heating:Electric MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_TOPFLOOR Design Size Nominal Capacity [Btu/h] 5648.64816
458 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR Design Size Rated Air Flow Rate [ft3/min] 360.80504
459 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 0.80157
460 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR Design Size Gross Rated Sensible Heat Ratio 0.80066
461 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_TOPFLOOR Supply Air Flow Rate [ft3/min] 360.80504
462 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_TOPFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 360.80504
463 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_TOPFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 360.80504
464 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_TOPFLOOR Nominal Heating Capacity [Btu/h] 7269.84106
465 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_TOPFLOOR Nominal Cooling Capacity [ton] 0.80157
466 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_TOPFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
467 Fan:OnOff SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR Design Size Maximum Flow Rate [ft3/min] 360.80504
468 Coil:Heating:Electric MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_TOPFLOOR Design Size Nominal Capacity [Btu/h] 7269.84106
469 Fan:OnOff HEAT PUMP WATER HEATER FAN_UNIT1_FRONTROW_BOTTOMFLOOR Design Size Maximum Flow Rate [ft3/min] 160.01057
470 Fan:OnOff HEAT PUMP WATER HEATER FAN_UNIT2_FRONTROW_BOTTOMFLOOR Design Size Maximum Flow Rate [ft3/min] 160.01057
471 Fan:OnOff HEAT PUMP WATER HEATER FAN_UNIT3_FRONTROW_BOTTOMFLOOR Design Size Maximum Flow Rate [ft3/min] 160.01057
472 Fan:OnOff HEAT PUMP WATER HEATER FAN_UNIT1_BACKROW_BOTTOMFLOOR Design Size Maximum Flow Rate [ft3/min] 160.01057
473 Fan:OnOff HEAT PUMP WATER HEATER FAN_UNIT2_BACKROW_BOTTOMFLOOR Design Size Maximum Flow Rate [ft3/min] 160.01057
474 Fan:OnOff HEAT PUMP WATER HEATER FAN_UNIT3_BACKROW_BOTTOMFLOOR Design Size Maximum Flow Rate [ft3/min] 160.01057
475 Fan:OnOff HEAT PUMP WATER HEATER FAN_UNIT1_FRONTROW_MIDDLEFLOOR Design Size Maximum Flow Rate [ft3/min] 160.01057
476 Fan:OnOff HEAT PUMP WATER HEATER FAN_UNIT2_FRONTROW_MIDDLEFLOOR Design Size Maximum Flow Rate [ft3/min] 160.01057
477 Fan:OnOff HEAT PUMP WATER HEATER FAN_UNIT3_FRONTROW_MIDDLEFLOOR Design Size Maximum Flow Rate [ft3/min] 160.01057
478 Fan:OnOff HEAT PUMP WATER HEATER FAN_UNIT1_BACKROW_MIDDLEFLOOR Design Size Maximum Flow Rate [ft3/min] 160.01057
479 Fan:OnOff HEAT PUMP WATER HEATER FAN_UNIT2_BACKROW_MIDDLEFLOOR Design Size Maximum Flow Rate [ft3/min] 160.01057
480 Fan:OnOff HEAT PUMP WATER HEATER FAN_UNIT3_BACKROW_MIDDLEFLOOR Design Size Maximum Flow Rate [ft3/min] 160.01057
481 Fan:OnOff HEAT PUMP WATER HEATER FAN_UNIT1_FRONTROW_TOPFLOOR Design Size Maximum Flow Rate [ft3/min] 160.01057
482 Fan:OnOff HEAT PUMP WATER HEATER FAN_UNIT2_FRONTROW_TOPFLOOR Design Size Maximum Flow Rate [ft3/min] 160.01057
483 Fan:OnOff HEAT PUMP WATER HEATER FAN_UNIT3_FRONTROW_TOPFLOOR Design Size Maximum Flow Rate [ft3/min] 160.01057
484 Fan:OnOff HEAT PUMP WATER HEATER FAN_UNIT1_BACKROW_TOPFLOOR Design Size Maximum Flow Rate [ft3/min] 160.01057
485 Fan:OnOff HEAT PUMP WATER HEATER FAN_UNIT2_BACKROW_TOPFLOOR Design Size Maximum Flow Rate [ft3/min] 160.01057
486 Fan:OnOff HEAT PUMP WATER HEATER FAN_UNIT3_BACKROW_TOPFLOOR Design Size Maximum Flow Rate [ft3/min] 160.01057
487 WaterHeater:HeatPump:WrappedCondenser WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR Evaporator air flow rate [ft3/min] 160.01057
488 WaterHeater:HeatPump:WrappedCondenser WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR Evaporator air flow rate [ft3/min] 160.01057
489 WaterHeater:HeatPump:WrappedCondenser WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR Evaporator air flow rate [ft3/min] 160.01057
490 WaterHeater:HeatPump:WrappedCondenser WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR Evaporator air flow rate [ft3/min] 160.01057
491 WaterHeater:HeatPump:WrappedCondenser WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR Evaporator air flow rate [ft3/min] 160.01057
492 WaterHeater:HeatPump:WrappedCondenser WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR Evaporator air flow rate [ft3/min] 160.01057
493 WaterHeater:HeatPump:WrappedCondenser WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR Evaporator air flow rate [ft3/min] 160.01057
494 WaterHeater:HeatPump:WrappedCondenser WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR Evaporator air flow rate [ft3/min] 160.01057
495 WaterHeater:HeatPump:WrappedCondenser WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR Evaporator air flow rate [ft3/min] 160.01057
496 WaterHeater:HeatPump:WrappedCondenser WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR Evaporator air flow rate [ft3/min] 160.01057
497 WaterHeater:HeatPump:WrappedCondenser WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR Evaporator air flow rate [ft3/min] 160.01057
498 WaterHeater:HeatPump:WrappedCondenser WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR Evaporator air flow rate [ft3/min] 160.01057
499 WaterHeater:HeatPump:WrappedCondenser WATER HEATER_UNIT1_FRONTROW_TOPFLOOR Evaporator air flow rate [ft3/min] 160.01057
500 WaterHeater:HeatPump:WrappedCondenser WATER HEATER_UNIT2_FRONTROW_TOPFLOOR Evaporator air flow rate [ft3/min] 160.01057
501 WaterHeater:HeatPump:WrappedCondenser WATER HEATER_UNIT3_FRONTROW_TOPFLOOR Evaporator air flow rate [ft3/min] 160.01057
502 WaterHeater:HeatPump:WrappedCondenser WATER HEATER_UNIT1_BACKROW_TOPFLOOR Evaporator air flow rate [ft3/min] 160.01057
503 WaterHeater:HeatPump:WrappedCondenser WATER HEATER_UNIT2_BACKROW_TOPFLOOR Evaporator air flow rate [ft3/min] 160.01057
504 WaterHeater:HeatPump:WrappedCondenser WATER HEATER_UNIT3_BACKROW_TOPFLOOR Evaporator air flow rate [ft3/min] 160.01057
505 PlantLoop DHW LOOP_UNIT1_FRONTROW_BOTTOMFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
506 PlantLoop DHW LOOP_UNIT1_FRONTROW_BOTTOMFLOOR Plant Loop Volume [ft3] 2.08975
507 Pump:VariableSpeed MAINS PRESSURE_UNIT1_FRONTROW_BOTTOMFLOOR Design Flow Rate [ft3/min] 1.04461
508 WaterHeater:Stratified WATER HEATER_TANK_UNIT1_FRONTROW_BOTTOMFLOOR Maximum Heater Capacity [Btu/h] 15354.00000
509 WaterHeater:Stratified WATER HEATER_TANK_UNIT1_FRONTROW_BOTTOMFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
510 PlantLoop DHW LOOP_UNIT2_FRONTROW_BOTTOMFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
511 PlantLoop DHW LOOP_UNIT2_FRONTROW_BOTTOMFLOOR Plant Loop Volume [ft3] 2.08975
512 Pump:VariableSpeed MAINS PRESSURE_UNIT2_FRONTROW_BOTTOMFLOOR Design Flow Rate [ft3/min] 1.04461
513 WaterHeater:Stratified WATER HEATER_TANK_UNIT2_FRONTROW_BOTTOMFLOOR Maximum Heater Capacity [Btu/h] 15354.00000
514 WaterHeater:Stratified WATER HEATER_TANK_UNIT2_FRONTROW_BOTTOMFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
515 PlantLoop DHW LOOP_UNIT3_FRONTROW_BOTTOMFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
516 PlantLoop DHW LOOP_UNIT3_FRONTROW_BOTTOMFLOOR Plant Loop Volume [ft3] 2.08975
517 Pump:VariableSpeed MAINS PRESSURE_UNIT3_FRONTROW_BOTTOMFLOOR Design Flow Rate [ft3/min] 1.04461
518 WaterHeater:Stratified WATER HEATER_TANK_UNIT3_FRONTROW_BOTTOMFLOOR Maximum Heater Capacity [Btu/h] 15354.00000
519 WaterHeater:Stratified WATER HEATER_TANK_UNIT3_FRONTROW_BOTTOMFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
520 PlantLoop DHW LOOP_UNIT1_BACKROW_BOTTOMFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
521 PlantLoop DHW LOOP_UNIT1_BACKROW_BOTTOMFLOOR Plant Loop Volume [ft3] 2.08975
522 Pump:VariableSpeed MAINS PRESSURE_UNIT1_BACKROW_BOTTOMFLOOR Design Flow Rate [ft3/min] 1.04461
523 WaterHeater:Stratified WATER HEATER_TANK_UNIT1_BACKROW_BOTTOMFLOOR Maximum Heater Capacity [Btu/h] 15354.00000
524 WaterHeater:Stratified WATER HEATER_TANK_UNIT1_BACKROW_BOTTOMFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
525 PlantLoop DHW LOOP_UNIT2_BACKROW_BOTTOMFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
526 PlantLoop DHW LOOP_UNIT2_BACKROW_BOTTOMFLOOR Plant Loop Volume [ft3] 2.08975
527 Pump:VariableSpeed MAINS PRESSURE_UNIT2_BACKROW_BOTTOMFLOOR Design Flow Rate [ft3/min] 1.04461
528 WaterHeater:Stratified WATER HEATER_TANK_UNIT2_BACKROW_BOTTOMFLOOR Maximum Heater Capacity [Btu/h] 15354.00000
529 WaterHeater:Stratified WATER HEATER_TANK_UNIT2_BACKROW_BOTTOMFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
530 PlantLoop DHW LOOP_UNIT3_BACKROW_BOTTOMFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
531 PlantLoop DHW LOOP_UNIT3_BACKROW_BOTTOMFLOOR Plant Loop Volume [ft3] 2.08975
532 Pump:VariableSpeed MAINS PRESSURE_UNIT3_BACKROW_BOTTOMFLOOR Design Flow Rate [ft3/min] 1.04461
533 WaterHeater:Stratified WATER HEATER_TANK_UNIT3_BACKROW_BOTTOMFLOOR Maximum Heater Capacity [Btu/h] 15354.00000
534 WaterHeater:Stratified WATER HEATER_TANK_UNIT3_BACKROW_BOTTOMFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
535 PlantLoop DHW LOOP_UNIT1_FRONTROW_MIDDLEFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
536 PlantLoop DHW LOOP_UNIT1_FRONTROW_MIDDLEFLOOR Plant Loop Volume [ft3] 2.08975
537 Pump:VariableSpeed MAINS PRESSURE_UNIT1_FRONTROW_MIDDLEFLOOR Design Flow Rate [ft3/min] 1.04461
538 WaterHeater:Stratified WATER HEATER_TANK_UNIT1_FRONTROW_MIDDLEFLOOR Maximum Heater Capacity [Btu/h] 15354.00000
539 WaterHeater:Stratified WATER HEATER_TANK_UNIT1_FRONTROW_MIDDLEFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
540 PlantLoop DHW LOOP_UNIT2_FRONTROW_MIDDLEFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
541 PlantLoop DHW LOOP_UNIT2_FRONTROW_MIDDLEFLOOR Plant Loop Volume [ft3] 2.08975
542 Pump:VariableSpeed MAINS PRESSURE_UNIT2_FRONTROW_MIDDLEFLOOR Design Flow Rate [ft3/min] 1.04461
543 WaterHeater:Stratified WATER HEATER_TANK_UNIT2_FRONTROW_MIDDLEFLOOR Maximum Heater Capacity [Btu/h] 15354.00000
544 WaterHeater:Stratified WATER HEATER_TANK_UNIT2_FRONTROW_MIDDLEFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
545 PlantLoop DHW LOOP_UNIT3_FRONTROW_MIDDLEFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
546 PlantLoop DHW LOOP_UNIT3_FRONTROW_MIDDLEFLOOR Plant Loop Volume [ft3] 2.08975
547 Pump:VariableSpeed MAINS PRESSURE_UNIT3_FRONTROW_MIDDLEFLOOR Design Flow Rate [ft3/min] 1.04461
548 WaterHeater:Stratified WATER HEATER_TANK_UNIT3_FRONTROW_MIDDLEFLOOR Maximum Heater Capacity [Btu/h] 15354.00000
549 WaterHeater:Stratified WATER HEATER_TANK_UNIT3_FRONTROW_MIDDLEFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
550 PlantLoop DHW LOOP_UNIT1_BACKROW_MIDDLEFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
551 PlantLoop DHW LOOP_UNIT1_BACKROW_MIDDLEFLOOR Plant Loop Volume [ft3] 2.08975
552 Pump:VariableSpeed MAINS PRESSURE_UNIT1_BACKROW_MIDDLEFLOOR Design Flow Rate [ft3/min] 1.04461
553 WaterHeater:Stratified WATER HEATER_TANK_UNIT1_BACKROW_MIDDLEFLOOR Maximum Heater Capacity [Btu/h] 15354.00000
554 WaterHeater:Stratified WATER HEATER_TANK_UNIT1_BACKROW_MIDDLEFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
555 PlantLoop DHW LOOP_UNIT2_BACKROW_MIDDLEFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
556 PlantLoop DHW LOOP_UNIT2_BACKROW_MIDDLEFLOOR Plant Loop Volume [ft3] 2.08975
557 Pump:VariableSpeed MAINS PRESSURE_UNIT2_BACKROW_MIDDLEFLOOR Design Flow Rate [ft3/min] 1.04461
558 WaterHeater:Stratified WATER HEATER_TANK_UNIT2_BACKROW_MIDDLEFLOOR Maximum Heater Capacity [Btu/h] 15354.00000
559 WaterHeater:Stratified WATER HEATER_TANK_UNIT2_BACKROW_MIDDLEFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
560 PlantLoop DHW LOOP_UNIT3_BACKROW_MIDDLEFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
561 PlantLoop DHW LOOP_UNIT3_BACKROW_MIDDLEFLOOR Plant Loop Volume [ft3] 2.08975
562 Pump:VariableSpeed MAINS PRESSURE_UNIT3_BACKROW_MIDDLEFLOOR Design Flow Rate [ft3/min] 1.04461
563 WaterHeater:Stratified WATER HEATER_TANK_UNIT3_BACKROW_MIDDLEFLOOR Maximum Heater Capacity [Btu/h] 15354.00000
564 WaterHeater:Stratified WATER HEATER_TANK_UNIT3_BACKROW_MIDDLEFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
565 PlantLoop DHW LOOP_UNIT1_FRONTROW_TOPFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
566 PlantLoop DHW LOOP_UNIT1_FRONTROW_TOPFLOOR Plant Loop Volume [ft3] 2.08975
567 Pump:VariableSpeed MAINS PRESSURE_UNIT1_FRONTROW_TOPFLOOR Design Flow Rate [ft3/min] 1.04461
568 WaterHeater:Stratified WATER HEATER_TANK_UNIT1_FRONTROW_TOPFLOOR Maximum Heater Capacity [Btu/h] 15354.00000
569 WaterHeater:Stratified WATER HEATER_TANK_UNIT1_FRONTROW_TOPFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
570 PlantLoop DHW LOOP_UNIT2_FRONTROW_TOPFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
571 PlantLoop DHW LOOP_UNIT2_FRONTROW_TOPFLOOR Plant Loop Volume [ft3] 2.08975
572 Pump:VariableSpeed MAINS PRESSURE_UNIT2_FRONTROW_TOPFLOOR Design Flow Rate [ft3/min] 1.04461
573 WaterHeater:Stratified WATER HEATER_TANK_UNIT2_FRONTROW_TOPFLOOR Maximum Heater Capacity [Btu/h] 15354.00000
574 WaterHeater:Stratified WATER HEATER_TANK_UNIT2_FRONTROW_TOPFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
575 PlantLoop DHW LOOP_UNIT3_FRONTROW_TOPFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
576 PlantLoop DHW LOOP_UNIT3_FRONTROW_TOPFLOOR Plant Loop Volume [ft3] 2.08975
577 Pump:VariableSpeed MAINS PRESSURE_UNIT3_FRONTROW_TOPFLOOR Design Flow Rate [ft3/min] 1.04461
578 WaterHeater:Stratified WATER HEATER_TANK_UNIT3_FRONTROW_TOPFLOOR Maximum Heater Capacity [Btu/h] 15354.00000
579 WaterHeater:Stratified WATER HEATER_TANK_UNIT3_FRONTROW_TOPFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
580 PlantLoop DHW LOOP_UNIT1_BACKROW_TOPFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
581 PlantLoop DHW LOOP_UNIT1_BACKROW_TOPFLOOR Plant Loop Volume [ft3] 2.08975
582 Pump:VariableSpeed MAINS PRESSURE_UNIT1_BACKROW_TOPFLOOR Design Flow Rate [ft3/min] 1.04461
583 WaterHeater:Stratified WATER HEATER_TANK_UNIT1_BACKROW_TOPFLOOR Maximum Heater Capacity [Btu/h] 15354.00000
584 WaterHeater:Stratified WATER HEATER_TANK_UNIT1_BACKROW_TOPFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
585 PlantLoop DHW LOOP_UNIT2_BACKROW_TOPFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
586 PlantLoop DHW LOOP_UNIT2_BACKROW_TOPFLOOR Plant Loop Volume [ft3] 2.08975
587 Pump:VariableSpeed MAINS PRESSURE_UNIT2_BACKROW_TOPFLOOR Design Flow Rate [ft3/min] 1.04461
588 WaterHeater:Stratified WATER HEATER_TANK_UNIT2_BACKROW_TOPFLOOR Maximum Heater Capacity [Btu/h] 15354.00000
589 WaterHeater:Stratified WATER HEATER_TANK_UNIT2_BACKROW_TOPFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
590 PlantLoop DHW LOOP_UNIT3_BACKROW_TOPFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
591 PlantLoop DHW LOOP_UNIT3_BACKROW_TOPFLOOR Plant Loop Volume [ft3] 2.08975
592 Pump:VariableSpeed MAINS PRESSURE_UNIT3_BACKROW_TOPFLOOR Design Flow Rate [ft3/min] 1.04461
593 WaterHeater:Stratified WATER HEATER_TANK_UNIT3_BACKROW_TOPFLOOR Maximum Heater Capacity [Btu/h] 15354.00000
594 WaterHeater:Stratified WATER HEATER_TANK_UNIT3_BACKROW_TOPFLOOR Use Side Design Flow Rate [ft3/min] 1.04461


DX Cooling Coil Standard Rating Information

Component Type Component Name Standard Rating (Net) Cooling Capacity {ton} Standard Rated Net COP {Btuh/Btuh} EER {Btu/W-h} SEER User {Btu/W-h} SEER Standard {Btu/W-h} IEER {Btu/W-h}
1 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR 1.0 3.26 11.12 11.77 11.32 11.27
2 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR 0.5 3.26 11.12 11.77 11.32 11.27
3 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR 0.7 3.26 11.12 11.77 11.32 11.27
4 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR 1.0 3.26 11.12 11.77 11.32 11.27
5 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR 0.5 3.26 11.12 11.77 11.32 11.27
6 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR 0.7 3.26 11.12 11.77 11.32 11.27
7 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR 1.0 3.26 11.12 11.77 11.32 11.27
8 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR 0.5 3.26 11.12 11.77 11.32 11.27
9 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR 0.8 3.26 11.12 11.77 11.32 11.27
10 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR 1.0 3.26 11.12 11.77 11.32 11.27
11 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR 0.5 3.26 11.12 11.77 11.32 11.27
12 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR 0.7 3.26 11.12 11.77 11.32 11.27
13 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR 1.0 3.26 11.12 11.77 11.32 11.27
14 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR 0.5 3.26 11.12 11.77 11.32 11.27
15 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR 0.8 3.26 11.12 11.77 11.32 11.27
16 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR 1.1 3.26 11.12 11.77 11.32 11.27
17 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR 0.5 3.26 11.12 11.77 11.32 11.27
18 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR 0.8 3.26 11.12 11.77 11.32 11.27


Environment

Environment Name Environment Type Start Date End Date Start DayOfWeek Duration {#days} Source:Start DayOfWeek Use Daylight Saving Use Holidays Apply Weekend Holiday Rule Use Rain Values Use Snow Values Sky Temperature Model
1 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB SizingPeriod:DesignDay 12/21 12/21 WinterDesignDay 1 N/A N/A N/A N/A N/A N/A Clark and Allen
2 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB SizingPeriod:DesignDay 07/21 07/21 SummerDesignDay 1 N/A N/A N/A N/A N/A N/A Clark and Allen
3 ANNUAL WeatherFileRunPeriod 01/01/2017 12/31/2017 Sunday 365 Use RunPeriod Specified Day Yes Yes No Yes Yes Clark and Allen


Environment:Daylight Saving

Daylight Saving Indicator Source Start Date End Date
1 No SizingPeriod:DesignDay    
2 No SizingPeriod:DesignDay    
3 No      


Environment:WarmupDays

NumberofWarmupDays
1 6
2 7
3 25


Environment:Design Day Data

Max Dry-Bulb Temp {F} Temp Range {dC} Temp Range Ind Type Hum Ind Type Hum Ind Value at Max Temp Hum Ind Units Pressure {psi} Wind Direction {deg CW from N} Wind Speed {ft/min} Clearness Rain Snow
1 17.78 0.00 DefaultMultipliers Wetbulb -7.90 {C} 12. 0 630.0 0.00 No No
2 95.18 13.50 DefaultMultipliers Wetbulb 15.70 {C} 12. 220 866.2 0.00 No No


Environment:Design Day Misc

DayOfYear ASHRAE A Coeff ASHRAE B Coeff ASHRAE C Coeff Solar Constant-Annual Variation Eq of Time {minutes} Solar Declination Angle {deg} Solar Model
1 355 1232.8 0.1424 5.7719E-002 1.0 2.45 -24.. ASHRAEClearSky
2 202 1084.4 0.2082 0.1365 1.0 -6.23 20.6 ASHRAETau


Tabular Report

Style Unit Conversion
1 Commaandhtml commaandhtml


Warmup Convergence Information

Zone Name Environment Type/Name Average Warmup Temperature Difference {deltaF} Std Dev Warmup Temperature Difference {deltaF} Max Temperature Pass/Fail Convergence Min Temperature Pass/Fail Convergence Average Warmup Load Difference {Btu/h} Std Dev Warmup Load Difference {Btu/h} Heating Load Pass/Fail Convergence Cooling Load Pass/Fail Convergence
1 CRAWLSPACE SizingPeriod: ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 0.000504401 0.000487053 Pass Pass 0.000000000 0.000000000 Pass Pass
2 BREEZEWAY SizingPeriod: ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 0.000187195 0.000075964 Pass Pass 0.000000000 0.000000000 Pass Pass
3 LIVING_UNIT1_FRONTROW_BOTTOMFLOOR SizingPeriod: ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 0.110080102 0.219347476 Pass Pass 0.106986966 0.322884334 Pass Pass
4 LIVING_UNIT2_FRONTROW_BOTTOMFLOOR SizingPeriod: ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 0.140618396 0.263683290 Pass Pass 0.211885824 0.789379195 Pass Pass
5 LIVING_UNIT3_FRONTROW_BOTTOMFLOOR SizingPeriod: ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 0.122856623 0.231921773 Pass Pass 0.114228885 0.380078024 Pass Pass
6 LIVING_UNIT1_BACKROW_BOTTOMFLOOR SizingPeriod: ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 0.110738868 0.220256601 Pass Pass 0.107635356 0.325511156 Pass Pass
7 LIVING_UNIT2_BACKROW_BOTTOMFLOOR SizingPeriod: ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 0.140356739 0.263197017 Pass Pass 0.211134058 0.785492107 Pass Pass
8 LIVING_UNIT3_BACKROW_BOTTOMFLOOR SizingPeriod: ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 0.123280194 0.232553152 Pass Pass 0.114308929 0.381765048 Pass Pass
9 LIVING_UNIT1_FRONTROW_MIDDLEFLOOR SizingPeriod: ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 0.121767722 0.236738667 Pass Pass 0.211561643 0.686817443 Pass Pass
10 LIVING_UNIT2_FRONTROW_MIDDLEFLOOR SizingPeriod: ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 0.173499673 0.309994359 Pass Pass 1.462857130 7.117726335 Pass Pass
11 LIVING_UNIT3_FRONTROW_MIDDLEFLOOR SizingPeriod: ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 0.132664693 0.250381854 Pass Pass 0.213389912 0.770223466 Pass Pass
12 LIVING_UNIT1_BACKROW_MIDDLEFLOOR SizingPeriod: ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 0.122415843 0.237300224 Pass Pass 0.211642055 0.688835497 Pass Pass
13 LIVING_UNIT2_BACKROW_MIDDLEFLOOR SizingPeriod: ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 0.173325984 0.309745288 Pass Pass 1.474368351 7.303981308 Pass Pass
14 LIVING_UNIT3_BACKROW_MIDDLEFLOOR SizingPeriod: ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 0.133202113 0.251188510 Pass Pass 0.214778432 0.777569129 Pass Pass
15 ATTIC SizingPeriod: ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 0.000077304 0.000041341 Pass Pass 0.000000000 0.000000000 Pass Pass
16 LIVING_UNIT3_BACKROW_TOPFLOOR SizingPeriod: ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 0.117386159 0.229660569 Pass Pass 0.123213010 0.415586607 Pass Pass
17 LIVING_UNIT3_FRONTROW_TOPFLOOR SizingPeriod: ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 0.116942596 0.228892607 Pass Pass 0.123305217 0.413522182 Pass Pass
18 LIVING_UNIT1_FRONTROW_TOPFLOOR SizingPeriod: ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 0.105540967 0.217294252 Pass Pass 0.113233361 0.352563376 Pass Pass
19 LIVING_UNIT2_BACKROW_TOPFLOOR SizingPeriod: ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 0.136923444 0.263687040 Pass Pass 0.247709840 0.946322187 Pass Pass
20 LIVING_UNIT2_FRONTROW_TOPFLOOR SizingPeriod: ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 0.137535928 0.264761893 Pass Pass 0.249891139 0.958100734 Pass Pass
21 LIVING_UNIT1_BACKROW_TOPFLOOR SizingPeriod: ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 0.105433352 0.217131397 Pass Pass 0.112991553 0.351753166 Pass Pass
22 CRAWLSPACE SizingPeriod: ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 0.243316113 0.143409533 Pass Pass 0.000000000 0.000000000 Pass Pass
23 BREEZEWAY SizingPeriod: ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 0.098903674 0.053885522 Pass Pass 0.000000000 0.000000000 Pass Pass
24 LIVING_UNIT1_FRONTROW_BOTTOMFLOOR SizingPeriod: ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 0.014333179 0.083783332 Pass Pass 0.116622693 0.118400870 Pass Pass
25 LIVING_UNIT2_FRONTROW_BOTTOMFLOOR SizingPeriod: ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 0.019843499 0.116989690 Pass Pass 0.125790833 0.364529907 Pass Pass
26 LIVING_UNIT3_FRONTROW_BOTTOMFLOOR SizingPeriod: ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 0.000361074 0.001806787 Pass Pass 0.098172033 0.166406036 Pass Pass
27 LIVING_UNIT1_BACKROW_BOTTOMFLOOR SizingPeriod: ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 0.012813180 0.075836689 Pass Pass 0.122099708 0.127747374 Pass Pass
28 LIVING_UNIT2_BACKROW_BOTTOMFLOOR SizingPeriod: ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 0.018271616 0.108538998 Pass Pass 0.121198802 0.317167251 Pass Pass
29 LIVING_UNIT3_BACKROW_BOTTOMFLOOR SizingPeriod: ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 0.000362443 0.001818958 Pass Pass 0.099172767 0.170812167 Pass Pass
30 LIVING_UNIT1_FRONTROW_MIDDLEFLOOR SizingPeriod: ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 0.009920193 0.054031255 Pass Pass 0.098520221 0.111570340 Pass Pass
31 LIVING_UNIT2_FRONTROW_MIDDLEFLOOR SizingPeriod: ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 0.014538221 0.087864456 Pass Pass 0.069315437 0.132182869 Pass Pass
32 LIVING_UNIT3_FRONTROW_MIDDLEFLOOR SizingPeriod: ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 0.000260846 0.001107925 Pass Pass 0.073317971 0.072504918 Pass Pass
33 LIVING_UNIT1_BACKROW_MIDDLEFLOOR SizingPeriod: ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 0.008454040 0.044608702 Pass Pass 0.098789609 0.103821082 Pass Pass
34 LIVING_UNIT2_BACKROW_MIDDLEFLOOR SizingPeriod: ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 0.012956100 0.079608492 Pass Pass 0.071955121 0.134553853 Pass Pass
35 LIVING_UNIT3_BACKROW_MIDDLEFLOOR SizingPeriod: ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 0.000262282 0.001113478 Pass Pass 0.073778330 0.076460273 Pass Pass
36 ATTIC SizingPeriod: ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 0.591195511 0.434718515 Pass Pass 0.000000000 0.000000000 Pass Pass
37 LIVING_UNIT3_BACKROW_TOPFLOOR SizingPeriod: ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 0.000227502 0.001038442 Pass Pass 0.068249849 0.070599428 Pass Pass
38 LIVING_UNIT3_FRONTROW_TOPFLOOR SizingPeriod: ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 0.000222511 0.001038940 Pass Pass 0.067733504 0.067332577 Pass Pass
39 LIVING_UNIT1_FRONTROW_TOPFLOOR SizingPeriod: ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 0.007888442 0.039535153 Pass Pass 0.091285745 0.079387613 Pass Pass
40 LIVING_UNIT2_BACKROW_TOPFLOOR SizingPeriod: ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 0.010816702 0.067754535 Pass Pass 0.074505992 0.141368619 Pass Pass
41 LIVING_UNIT2_FRONTROW_TOPFLOOR SizingPeriod: ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 0.012104473 0.074293836 Pass Pass 0.068364109 0.128689643 Pass Pass
42 LIVING_UNIT1_BACKROW_TOPFLOOR SizingPeriod: ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 0.006660913 0.032549935 Pass Pass 0.092208541 0.075765861 Pass Pass
43 CRAWLSPACE RunPeriod: ANNUAL 0.343718809 0.253185268 Pass Pass 0.000000000 0.000000000 Pass Pass
44 BREEZEWAY RunPeriod: ANNUAL 0.077469617 0.056710252 Pass Pass 0.000000000 0.000000000 Pass Pass
45 LIVING_UNIT1_FRONTROW_BOTTOMFLOOR RunPeriod: ANNUAL 0.078363494 0.216108082 Pass Pass 0.649183860 1.452933538 Fail Pass
46 LIVING_UNIT2_FRONTROW_BOTTOMFLOOR RunPeriod: ANNUAL 0.117406716 0.242888328 Pass Pass 7.323067135 0.726085E+02 Fail Pass
47 LIVING_UNIT3_FRONTROW_BOTTOMFLOOR RunPeriod: ANNUAL 0.109714513 0.215630742 Pass Pass 0.844269261 2.792388542 Fail Pass
48 LIVING_UNIT1_BACKROW_BOTTOMFLOOR RunPeriod: ANNUAL 0.070998012 0.165952338 Fail Pass 0.831351948 4.018176069 Fail Pass
49 LIVING_UNIT2_BACKROW_BOTTOMFLOOR RunPeriod: ANNUAL 0.031804984 0.084853462 Pass Pass 2.002669614 0.993097E+01 Fail Fail
50 LIVING_UNIT3_BACKROW_BOTTOMFLOOR RunPeriod: ANNUAL 0.029461422 0.053453340 Pass Pass 3.095702290 0.256898E+02 Fail Fail
51 LIVING_UNIT1_FRONTROW_MIDDLEFLOOR RunPeriod: ANNUAL 0.119601329 0.225980349 Pass Pass 0.734301224 1.931307825 Fail Pass
52 LIVING_UNIT2_FRONTROW_MIDDLEFLOOR RunPeriod: ANNUAL 0.160280051 0.234487398 Pass Pass 1.874854206 6.374251029 Fail Pass
53 LIVING_UNIT3_FRONTROW_MIDDLEFLOOR RunPeriod: ANNUAL 0.134082280 0.203729362 Pass Pass 0.645029474 2.037453099 Fail Pass
54 LIVING_UNIT1_BACKROW_MIDDLEFLOOR RunPeriod: ANNUAL 0.085576550 0.186691142 Pass Pass 1.481219012 7.574519995 Fail Pass
55 LIVING_UNIT2_BACKROW_MIDDLEFLOOR RunPeriod: ANNUAL 0.092670948 0.125629580 Pass Pass 3.664135395 0.245629E+02 Fail Fail
56 LIVING_UNIT3_BACKROW_MIDDLEFLOOR RunPeriod: ANNUAL 0.069344297 0.093667967 Pass Pass 1.592628053 3.335022761 Fail Fail
57 ATTIC RunPeriod: ANNUAL 0.612229228 0.567604158 Pass Pass 0.000000000 0.000000000 Pass Pass
58 LIVING_UNIT3_BACKROW_TOPFLOOR RunPeriod: ANNUAL 0.046531707 0.071280658 Pass Pass 6.622207564 0.454772E+02 Pass Pass
59 LIVING_UNIT3_FRONTROW_TOPFLOOR RunPeriod: ANNUAL 0.123763790 0.224097585 Pass Pass 1.526643005 8.328154544 Fail Pass
60 LIVING_UNIT1_FRONTROW_TOPFLOOR RunPeriod: ANNUAL 0.107065581 0.215801125 Pass Pass 0.679541155 1.793714801 Fail Pass
61 LIVING_UNIT2_BACKROW_TOPFLOOR RunPeriod: ANNUAL 0.045371290 0.085934503 Pass Pass 6.359168868 0.484854E+02 Fail Pass
62 LIVING_UNIT2_FRONTROW_TOPFLOOR RunPeriod: ANNUAL 0.132615196 0.243231110 Pass Pass 1.286822464 7.381746164 Fail Pass
63 LIVING_UNIT1_BACKROW_TOPFLOOR RunPeriod: ANNUAL 0.073249939 0.166679006 Fail Pass 0.977083949 2.619215680 Pass Pass



Table of Contents

Report: Annual Heat Emissions Summary

For: Entire Facility

Timestamp: 2021-05-12 10:29:11

Heat Emission by Components

Envelope Convection Zone Exfiltration Zone Exhaust Air HVAC Relief Air HVAC Reject Heat Total
Heat Emissions [kBtu] 2695123.38 347470.78 0.00 0.00 262964.84 3305572.14



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2021-05-12 10:29:11

SizingPeriod:DesignDay

Maximum Dry Bulb [F] Daily Temperature Range [deltaF] Humidity Value Humidity Type Wind Speed [ft/min] Wind Direction
ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 17.78 0.00 17.78 Wetbulb [F] 629.95 0.00
ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 95.18 24.30 60.26 Wetbulb [F] 866.18 220.00


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2021-05-12 10:29:11

Opaque Exterior

Construction Reflectance U-Factor with Film [Btu/h-ft2-F] U-Factor no Film [Btu/h-ft2-F] Gross Area [ft2] Net Area [ft2] Azimuth [deg] Tilt [deg] Cardinal Direction
BGWALL_UPPER_LDF CRAWL WALL 0.30 0.776 2.276 59.96 59.96 180.00 90.00 S
BGWALL_LOWER_LDF CRAWL WALL 0.30 0.893 2.276 239.83 239.83 180.00 90.00 S
BGWALL_UPPER_SDR CRAWL WALL 0.30 0.776 2.276 32.56 32.56 90.00 90.00 E
BGWALL_LOWER_SDR CRAWL WALL 0.30 0.893 2.276 130.22 130.22 90.00 90.00 E
BGWALL_UPPER_LDB CRAWL WALL 0.30 0.776 2.276 59.96 59.96 0.00 90.00 N
BGWALL_LOWER_LDB CRAWL WALL 0.30 0.893 2.276 239.83 239.83 0.00 90.00 N
BGWALL_UPPER_SDL CRAWL WALL 0.30 0.776 2.276 32.56 32.56 270.00 90.00 W
BGWALL_LOWER_SDL CRAWL WALL 0.30 0.893 2.276 130.22 130.22 270.00 90.00 W
BGFLOOR INTERIOR FLOOR 0.30 0.235 0.300 7794.39 7794.39 0.00 180.00  
BREEZEWAY_BOTTOMFLOOR EXTERIOR FLOOR 0.30 0.049 0.051 599.39 599.39 0.00 180.00  
BREEZEWAY_MIDDLEFLOOR EXTERIOR FLOOR 0.30 0.049 0.051 599.39 599.39 0.00 180.00  
BREEZEWAY_TOPFLOOR EXTERIOR FLOOR 0.30 0.049 0.051 599.39 599.39 0.00 180.00  
WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.76 280.68 180.00 90.00 S
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.76 318.74 0.00 90.00 N
WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.048 0.050 255.46 166.84 270.00 90.00 W
WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.76 280.68 180.00 90.00 S
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.76 318.74 0.00 90.00 N
WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.76 280.68 180.00 90.00 S
WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.048 0.050 255.46 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.76 318.74 0.00 90.00 N
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.76 318.74 180.00 90.00 S
WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.76 280.68 0.00 90.00 N
WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.048 0.050 255.46 166.84 270.00 90.00 W
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.76 318.74 180.00 90.00 S
WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.76 280.68 0.00 90.00 N
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.76 318.74 180.00 90.00 S
WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.048 0.050 255.46 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.76 280.68 0.00 90.00 N
WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 280.68 180.00 90.00 S
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 318.74 0.00 90.00 N
WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.048 0.050 255.45 166.84 270.00 90.00 W
WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 280.68 180.00 90.00 S
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 318.74 0.00 90.00 N
WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 280.68 180.00 90.00 S
WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.048 0.050 255.45 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 318.74 0.00 90.00 N
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 318.74 180.00 90.00 S
WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 280.68 0.00 90.00 N
WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.048 0.050 255.45 166.84 270.00 90.00 W
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 318.74 180.00 90.00 S
WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 280.68 0.00 90.00 N
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 318.74 180.00 90.00 S
WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.048 0.050 255.45 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 280.68 0.00 90.00 N
ROOF_RIGHT GABLE_END 0.30 0.314 0.428 440.68 440.68 90.00 90.00 E
ROOF_LEFT GABLE_END 0.30 0.314 0.428 440.68 440.68 270.00 90.00 W
ROOF_BACK EXTERIOR ROOF 0.25 0.543 0.943 4225.65 4225.65 0.00 22.59  
ROOF_FRONT EXTERIOR ROOF 0.25 0.543 0.943 4225.65 4225.65 180.00 22.59  
WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.048 0.050 255.45 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 280.68 0.00 90.00 N
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 318.74 180.00 90.00 S
WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 280.68 180.00 90.00 S
WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.048 0.050 255.45 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 318.74 0.00 90.00 N
WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 280.68 180.00 90.00 S
WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.048 0.050 255.45 166.84 270.00 90.00 W
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 318.74 0.00 90.00 N
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 318.74 180.00 90.00 S
WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 280.68 0.00 90.00 N
WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 280.68 180.00 90.00 S
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 318.74 0.00 90.00 N
WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 280.68 0.00 90.00 N
WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.048 0.050 255.45 166.84 270.00 90.00 W
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 318.74 180.00 90.00 S


Opaque Interior

Construction Reflectance U-Factor with Film [Btu/h-ft2-F] U-Factor no Film [Btu/h-ft2-F] Gross Area [ft2] Net Area [ft2] Azimuth [deg] Tilt [deg] Cardinal Direction
iz-FLOOR_UNIT1_FRONTROW_BOTTOMFLOOR iz-EXTERIOR FLOOR 0.30 0.048 0.051 1200.55 1200.55 180.00 0.00  
iz-FLOOR_UNIT2_FRONTROW_BOTTOMFLOOR iz-EXTERIOR FLOOR 0.30 0.048 0.051 1200.55 1200.55 180.00 0.00  
iz-FLOOR_UNIT3_FRONTROW_BOTTOMFLOOR iz-EXTERIOR FLOOR 0.30 0.048 0.051 1200.55 1200.55 180.00 0.00  
iz-FLOOR_UNIT1_BACKROW_BOTTOMFLOOR iz-EXTERIOR FLOOR 0.30 0.048 0.051 1200.55 1200.55 180.00 0.00  
iz-FLOOR_UNIT2_BACKROW_BOTTOMFLOOR iz-EXTERIOR FLOOR 0.30 0.048 0.051 1200.55 1200.55 180.00 0.00  
iz-FLOOR_UNIT3_BACKROW_BOTTOMFLOOR iz-EXTERIOR FLOOR 0.30 0.048 0.051 1200.55 1200.55 180.00 0.00  
BREEZEWAYROOF INTERIOR CEILING 0.30 0.018 0.019 599.39 599.39 180.00 0.00  
WALL_SDR_1.UNIT1_FRONTROW_BOTTOMFLOOR INTERIORWALL 0.30 0.329 0.597 255.46 255.46 90.00 90.00 E
FLOOR_UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR FLOOR 0.30 0.048 0.051 1200.55 1200.55 0.00 180.00  
CEILING_UNIT1_FRONTROW_BOTTOMFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 180.00 0.00  
WALL_SDR_1.UNIT2_FRONTROW_BOTTOMFLOOR INTERIORWALL 0.30 0.329 0.597 255.46 255.46 90.00 90.00 E
WALL_SDL_1.UNIT2_FRONTROW_BOTTOMFLOOR INTERIORWALL 0.30 0.329 0.597 255.46 255.46 270.00 90.00 W
FLOOR_UNIT2_FRONTROW_BOTTOMFLOOR EXTERIOR FLOOR 0.30 0.048 0.051 1200.55 1200.55 0.00 180.00  
CEILING_UNIT2_FRONTROW_BOTTOMFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 180.00 0.00  
WALL_SDL_1.UNIT3_FRONTROW_BOTTOMFLOOR INTERIORWALL 0.30 0.329 0.597 255.46 255.46 270.00 90.00 W
FLOOR_UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR FLOOR 0.30 0.048 0.051 1200.55 1200.55 0.00 180.00  
CEILING_UNIT3_FRONTROW_BOTTOMFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 180.00 0.00  
WALL_SDR_1.UNIT1_BACKROW_BOTTOMFLOOR INTERIORWALL 0.30 0.329 0.597 255.46 255.46 90.00 90.00 E
FLOOR_UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR FLOOR 0.30 0.048 0.051 1200.55 1200.55 0.00 180.00  
CEILING_UNIT1_BACKROW_BOTTOMFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 180.00 0.00  
WALL_SDL_1.UNIT2_BACKROW_BOTTOMFLOOR INTERIORWALL 0.30 0.329 0.597 255.46 255.46 270.00 90.00 W
WALL_SDR_1.UNIT2_BACKROW_BOTTOMFLOOR INTERIORWALL 0.30 0.329 0.597 255.46 255.46 90.00 90.00 E
FLOOR_UNIT2_BACKROW_BOTTOMFLOOR EXTERIOR FLOOR 0.30 0.048 0.051 1200.55 1200.55 0.00 180.00  
CEILING_UNIT2_BACKROW_BOTTOMFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 180.00 0.00  
WALL_SDL_1.UNIT3_BACKROW_BOTTOMFLOOR INTERIORWALL 0.30 0.329 0.597 255.46 255.46 270.00 90.00 W
FLOOR_UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR FLOOR 0.30 0.048 0.051 1200.55 1200.55 0.00 180.00  
CEILING_UNIT3_BACKROW_BOTTOMFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 180.00 0.00  
WALL_SDR_1.UNIT1_FRONTROW_MIDDLEFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 90.00 90.00 E
FLOOR_UNIT1_FRONTROW_MIDDLEFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 0.00 180.00  
CEILING_UNIT1_FRONTROW_MIDDLEFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 180.00 0.00  
WALL_SDL_1.UNIT2_FRONTROW_MIDDLEFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 270.00 90.00 W
WALL_SDR_1.UNIT2_FRONTROW_MIDDLEFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 90.00 90.00 E
FLOOR_UNIT2_FRONTROW_MIDDLEFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 0.00 180.00  
CEILING_UNIT2_FRONTROW_MIDDLEFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 180.00 0.00  
WALL_SDL_1.UNIT3_FRONTROW_MIDDLEFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 270.00 90.00 W
FLOOR_UNIT3_FRONTROW_MIDDLEFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 0.00 180.00  
CEILING_UNIT3_FRONTROW_MIDDLEFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 180.00 0.00  
WALL_SDR_1.UNIT1_BACKROW_MIDDLEFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 90.00 90.00 E
FLOOR_UNIT1_BACKROW_MIDDLEFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 0.00 180.00  
CEILING_UNIT1_BACKROW_MIDDLEFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 180.00 0.00  
WALL_SDL_1.UNIT2_BACKROW_MIDDLEFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 90.00 90.00 E
WALL_SDR_1.UNIT2_BACKROW_MIDDLEFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 270.00 90.00 W
FLOOR_UNIT2_BACKROW_MIDDLEFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 0.00 180.00  
CEILING_UNIT2_BACKROW_MIDDLEFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 180.00 0.00  
WALL_SDL_1.UNIT3_BACKROW_MIDDLEFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 270.00 90.00 W
FLOOR_UNIT3_BACKROW_MIDDLEFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 0.00 180.00  
CEILING_UNIT3_BACKROW_MIDDLEFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 180.00 0.00  
iz-BREEZEWAYROOF ATTIC FLOOR 0.30 0.018 0.019 599.39 599.39 0.00 180.00  
iz-CEILING_UNIT3_BACKROW_TOPFLOOR ATTIC FLOOR 0.30 0.018 0.019 1200.55 1200.55 0.00 180.00  
iz-CEILING_UNIT3_FRONTROW_TOPFLOOR ATTIC FLOOR 0.30 0.018 0.019 1200.55 1200.55 0.00 180.00  
iz-CEILING_UNIT1_FRONTROW_TOPFLOOR ATTIC FLOOR 0.30 0.018 0.019 1200.55 1200.55 0.00 180.00  
iz-CEILING_UNIT2_BACKROW_TOPFLOOR ATTIC FLOOR 0.30 0.018 0.019 1200.55 1200.55 0.00 180.00  
iz-CEILING_UNIT2_FRONTROW_TOPFLOOR ATTIC FLOOR 0.30 0.018 0.019 1200.55 1200.55 0.00 180.00  
iz-CEILING_UNIT1_BACKROW_TOPFLOOR ATTIC FLOOR 0.30 0.018 0.019 1200.55 1200.55 0.00 180.00  
WALL_SDL_1.UNIT3_BACKROW_TOPFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 270.00 90.00 W
FLOOR_UNIT3_BACKROW_TOPFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 0.00 180.00  
CEILING_UNIT3_BACKROW_TOPFLOOR INTERIOR CEILING 0.30 0.018 0.019 1200.55 1200.55 180.00 0.00  
WALL_SDL_1.UNIT3_FRONTROW_TOPFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 270.00 90.00 W
FLOOR_UNIT3_FRONTROW_TOPFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 0.00 180.00  
CEILING_UNIT3_FRONTROW_TOPFLOOR INTERIOR CEILING 0.30 0.018 0.019 1200.55 1200.55 180.00 0.00  
WALL_SDR_1.UNIT1_FRONTROW_TOPFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 90.00 90.00 E
FLOOR_UNIT1_FRONTROW_TOPFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 0.00 180.00  
CEILING_UNIT1_FRONTROW_TOPFLOOR INTERIOR CEILING 0.30 0.018 0.019 1200.55 1200.55 180.00 0.00  
WALL_SDL_1.UNIT2_BACKROW_TOPFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 270.00 90.00 W
WALL_SDR_1.UNIT2_BACKROW_TOPFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 90.00 90.00 E
FLOOR_UNIT2_BACKROW_TOPFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 0.00 180.00  
CEILING_UNIT2_BACKROW_TOPFLOOR INTERIOR CEILING 0.30 0.018 0.019 1200.55 1200.55 180.00 0.00  
WALL_SDR_1.UNIT2_FRONTROW_TOPFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 90.00 90.00 E
WALL_SDL_1.UNIT2_FRONTROW_TOPFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 270.00 90.00 W
FLOOR_UNIT2_FRONTROW_TOPFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 0.00 180.00  
CEILING_UNIT2_FRONTROW_TOPFLOOR INTERIOR CEILING 0.30 0.018 0.019 1200.55 1200.55 180.00 0.00  
WALL_SDR_1.UNIT1_BACKROW_TOPFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 90.00 90.00 E
FLOOR_UNIT1_BACKROW_TOPFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 0.00 180.00  
CEILING_UNIT1_BACKROW_TOPFLOOR INTERIOR CEILING 0.30 0.018 0.019 1200.55 1200.55 180.00 0.00  


Exterior Fenestration

Construction Glass Area [ft2] Frame Area [ft2] Divider Area [ft2] Area of One Opening [ft2] Area of Multiplied Openings [ft2] Glass U-Factor [Btu/h-ft2-F] Glass SHGC Glass Visible Transmittance Frame Conductance [Btu/h-ft2-F] Divider Conductance [Btu/h-ft2-F] Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.300 0.335 0.883     Yes WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR 180.00 90.00 S
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.300 0.335 0.883     Yes WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR 270.00 90.00 W
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.300 0.335 0.883     Yes WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR 180.00 90.00 S
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.300 0.335 0.883     Yes WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR 180.00 90.00 S
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.300 0.335 0.883     Yes WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.300 0.335 0.883     Yes WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR 0.00 90.00 N
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.300 0.335 0.883     Yes WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR 270.00 90.00 W
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.300 0.335 0.883     Yes WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR 0.00 90.00 N
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.300 0.335 0.883     Yes WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.300 0.335 0.883     Yes WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR 0.00 90.00 N
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.300 0.335 0.883     Yes WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR 180.00 90.00 S
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.300 0.335 0.883     Yes WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR 270.00 90.00 W
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.300 0.335 0.883     Yes WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR 180.00 90.00 S
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.300 0.335 0.883     Yes WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR 180.00 90.00 S
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.300 0.335 0.883     Yes WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.300 0.335 0.883     Yes WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR 0.00 90.00 N
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.300 0.335 0.883     Yes WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR 270.00 90.00 W
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.300 0.335 0.883     Yes WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR 0.00 90.00 N
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.300 0.335 0.883     Yes WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.300 0.335 0.883     Yes WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR 0.00 90.00 N
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.300 0.335 0.883     Yes WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.300 0.335 0.883     Yes WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR 0.00 90.00 N
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.300 0.335 0.883     Yes WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR 180.00 90.00 S
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.300 0.335 0.883     Yes WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR 90.00 90.00 E
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.300 0.335 0.883     Yes WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR 180.00 90.00 S
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.300 0.335 0.883     Yes WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR 270.00 90.00 W
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.300 0.335 0.883     Yes WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR 0.00 90.00 N
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.300 0.335 0.883     Yes WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR 180.00 90.00 S
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.300 0.335 0.883     Yes WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR 0.00 90.00 N
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.300 0.335 0.883     Yes WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR 270.00 90.00 W
Total or Average           2126.74 0.300 0.335 0.883              
North Total or Average           531.68 0.300 0.335 0.883              
Non-North Total or Average           1595.05 0.300 0.335 0.883              


Interior Fenestration

Construction Area of One Opening [ft2] Area of Openings [ft2] Glass U-Factor [Btu/h-ft2-F] Glass SHGC Glass Visible Transmittance Parent Surface
Total or Average     0.00 - - -  


Exterior Door

Construction U-Factor with Film [Btu/h-ft2-F] U-Factor no Film [Btu/h-ft2-F] Gross Area [ft2] Parent Surface
DOOR_LDB_UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR DOOR 0.239 0.300 21.01 WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR
DOOR_LDB_UNIT2_FRONTROW_BOTTOMFLOOR EXTERIOR DOOR 0.239 0.300 21.01 WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR
DOOR_LDB_UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR DOOR 0.239 0.300 21.01 WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR
DOOR_LDF_UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR DOOR 0.239 0.300 21.01 WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR
DOOR_LDF_UNIT2_BACKROW_BOTTOMFLOOR EXTERIOR DOOR 0.239 0.300 21.01 WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR
DOOR_LDF_UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR DOOR 0.239 0.300 21.01 WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR
DOOR_LDB_UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR DOOR 0.239 0.300 21.01 WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR
DOOR_LDB_UNIT2_FRONTROW_MIDDLEFLOOR EXTERIOR DOOR 0.239 0.300 21.01 WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR
DOOR_LDB_UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR DOOR 0.239 0.300 21.01 WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR
DOOR_LDF_UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR DOOR 0.239 0.300 21.01 WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR
DOOR_LDF_UNIT2_BACKROW_MIDDLEFLOOR EXTERIOR DOOR 0.239 0.300 21.01 WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR
DOOR_LDF_UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR DOOR 0.239 0.300 21.01 WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR
DOOR_LDF_UNIT3_BACKROW_TOPFLOOR EXTERIOR DOOR 0.239 0.300 21.01 WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR
DOOR_LDB_UNIT3_FRONTROW_TOPFLOOR EXTERIOR DOOR 0.239 0.300 21.01 WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR
DOOR_LDB_UNIT1_FRONTROW_TOPFLOOR EXTERIOR DOOR 0.239 0.300 21.01 WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR
DOOR_LDF_UNIT2_BACKROW_TOPFLOOR EXTERIOR DOOR 0.239 0.300 21.01 WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR
DOOR_LDB_UNIT2_FRONTROW_TOPFLOOR EXTERIOR DOOR 0.239 0.300 21.01 WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR
DOOR_LDF_UNIT1_BACKROW_TOPFLOOR EXTERIOR DOOR 0.239 0.300 21.01 WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR


Interior Door

Construction U-Factor with Film [Btu/h-ft2-F] U-Factor no Film [Btu/h-ft2-F] Gross Area [ft2] Parent Surface
None          



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2021-05-12 10:29:11

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR 0.99 0.99 0.99 0.14 0.96 0.93 1.00 0.99 1.00
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.99 0.00 0.00 0.99 0.00 0.00 1.00
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR 0.99 0.99 0.99 0.14 0.96 0.93 1.00 0.99 1.00
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR 0.99 0.99 0.99 0.14 0.96 0.93 1.00 0.99 1.00
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR 1.00 0.96 0.00 0.99 0.93 0.00 1.00 0.95 0.00
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 0.99 0.00 0.00 0.99 0.00 0.00 1.00
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR 1.00 0.96 0.00 0.99 0.93 0.00 1.00 0.95 0.00
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR 0.99 0.99 0.99 0.14 0.96 0.93 1.00 0.99 1.00
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 0.00 0.99 0.00 0.00 0.99 0.00 0.00 1.00
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR 0.99 0.99 0.99 0.14 0.96 0.93 1.00 0.99 1.00
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR 0.99 0.99 0.99 0.14 0.96 0.93 1.00 0.99 1.00
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR 1.00 0.96 0.00 0.99 0.93 0.00 1.00 0.95 0.00
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 0.99 0.00 0.00 0.99 0.00 0.00 1.00
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR 1.00 0.96 0.00 0.99 0.93 0.00 1.00 0.95 0.00
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR 1.00 0.96 0.00 0.99 0.93 0.00 1.00 0.95 0.00
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR 0.99 0.99 0.99 0.14 0.96 0.93 1.00 0.99 1.00
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR 1.00 0.96 0.00 0.99 0.93 0.00 1.00 0.95 0.00
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR 0.99 0.99 0.99 0.14 0.96 0.93 1.00 0.99 1.00
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR 0.00 0.00 0.99 0.00 0.00 0.99 0.00 0.00 1.00
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR 0.99 0.99 0.99 0.14 0.96 0.93 1.00 0.99 1.00
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 0.99 0.00 0.00 0.99 0.00 0.00 1.00


Window Control

Name Type Shaded Construction Control Glare Control
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR SHADES-LIVING_UNIT1_FRONTROW_BOTTOMFLOOR Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR SHADES-LIVING_UNIT3_FRONTROW_BOTTOMFLOOR Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR SHADES-LIVING_UNIT2_FRONTROW_BOTTOMFLOOR Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR SHADES-LIVING_UNIT3_FRONTROW_BOTTOMFLOOR Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR SHADES-LIVING_UNIT3_FRONTROW_BOTTOMFLOOR Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR SHADES-LIVING_UNIT1_BACKROW_BOTTOMFLOOR Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR SHADES-LIVING_UNIT3_BACKROW_BOTTOMFLOOR Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR SHADES-LIVING_UNIT2_BACKROW_BOTTOMFLOOR Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR SHADES-LIVING_UNIT3_BACKROW_BOTTOMFLOOR Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR SHADES-LIVING_UNIT3_BACKROW_BOTTOMFLOOR Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR SHADES-LIVING_UNIT1_FRONTROW_MIDDLEFLOOR Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR SHADES-LIVING_UNIT3_FRONTROW_MIDDLEFLOOR Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR SHADES-LIVING_UNIT2_FRONTROW_MIDDLEFLOOR Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR SHADES-LIVING_UNIT3_FRONTROW_MIDDLEFLOOR Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR SHADES-LIVING_UNIT3_FRONTROW_MIDDLEFLOOR Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR SHADES-LIVING_UNIT1_BACKROW_MIDDLEFLOOR Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR SHADES-LIVING_UNIT3_BACKROW_MIDDLEFLOOR Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR SHADES-LIVING_UNIT2_BACKROW_MIDDLEFLOOR Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR SHADES-LIVING_UNIT3_BACKROW_MIDDLEFLOOR Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR SHADES-LIVING_UNIT3_BACKROW_MIDDLEFLOOR Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR SHADES-LIVING_UNIT3_BACKROW_TOPFLOOR Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR SHADES-LIVING_UNIT3_BACKROW_TOPFLOOR Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR SHADES-LIVING_UNIT3_FRONTROW_TOPFLOOR Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR SHADES-LIVING_UNIT3_FRONTROW_TOPFLOOR Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR SHADES-LIVING_UNIT1_FRONTROW_TOPFLOOR Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR SHADES-LIVING_UNIT3_FRONTROW_TOPFLOOR Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR SHADES-LIVING_UNIT2_BACKROW_TOPFLOOR Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR SHADES-LIVING_UNIT2_FRONTROW_TOPFLOOR Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR SHADES-LIVING_UNIT1_BACKROW_TOPFLOOR Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR SHADES-LIVING_UNIT3_BACKROW_TOPFLOOR Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2021-05-12 10:29:11

Interior Lighting

Zone Lighting Power Density [Btu/h-ft2] Zone Area [ft2] Total Power [Btu/h] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [kWh]
LIVING HARDWIRED LIGHTING1_FRONTROW_BOTTOMFLOOR LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.4008 1200.55 481.17 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 432.94
LIVING PLUG-IN LIGHTING1_FRONTROW_BOTTOMFLOOR LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_FRONTROW_BOTTOMFLOOR LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.4008 1200.55 481.17 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 432.94
LIVING PLUG-IN LIGHTING2_FRONTROW_BOTTOMFLOOR LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_FRONTROW_BOTTOMFLOOR LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.4008 1200.55 481.17 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 432.94
LIVING PLUG-IN LIGHTING3_FRONTROW_BOTTOMFLOOR LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_BACKROW_BOTTOMFLOOR LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.4008 1200.55 481.17 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 432.94
LIVING PLUG-IN LIGHTING1_BACKROW_BOTTOMFLOOR LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_BACKROW_BOTTOMFLOOR LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.4008 1200.55 481.17 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 432.94
LIVING PLUG-IN LIGHTING2_BACKROW_BOTTOMFLOOR LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_BACKROW_BOTTOMFLOOR LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.4008 1200.55 481.17 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 432.94
LIVING PLUG-IN LIGHTING3_BACKROW_BOTTOMFLOOR LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_FRONTROW_MIDDLEFLOOR LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.4008 1200.55 481.17 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 432.94
LIVING PLUG-IN LIGHTING1_FRONTROW_MIDDLEFLOOR LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_FRONTROW_MIDDLEFLOOR LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.4008 1200.55 481.17 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 432.94
LIVING PLUG-IN LIGHTING2_FRONTROW_MIDDLEFLOOR LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_FRONTROW_MIDDLEFLOOR LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.4008 1200.55 481.17 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 432.94
LIVING PLUG-IN LIGHTING3_FRONTROW_MIDDLEFLOOR LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_BACKROW_MIDDLEFLOOR LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.4008 1200.55 481.17 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 432.94
LIVING PLUG-IN LIGHTING1_BACKROW_MIDDLEFLOOR LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_BACKROW_MIDDLEFLOOR LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.4008 1200.55 481.17 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 432.94
LIVING PLUG-IN LIGHTING2_BACKROW_MIDDLEFLOOR LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_BACKROW_MIDDLEFLOOR LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.4008 1200.55 481.17 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 432.94
LIVING PLUG-IN LIGHTING3_BACKROW_MIDDLEFLOOR LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_FRONTROW_TOPFLOOR LIVING_UNIT1_FRONTROW_TOPFLOOR 0.4008 1200.55 481.17 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 432.94
LIVING PLUG-IN LIGHTING1_FRONTROW_TOPFLOOR LIVING_UNIT1_FRONTROW_TOPFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_FRONTROW_TOPFLOOR LIVING_UNIT2_FRONTROW_TOPFLOOR 0.4008 1200.55 481.17 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 432.94
LIVING PLUG-IN LIGHTING2_FRONTROW_TOPFLOOR LIVING_UNIT2_FRONTROW_TOPFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_FRONTROW_TOPFLOOR LIVING_UNIT3_FRONTROW_TOPFLOOR 0.4008 1200.55 481.17 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 432.94
LIVING PLUG-IN LIGHTING3_FRONTROW_TOPFLOOR LIVING_UNIT3_FRONTROW_TOPFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_BACKROW_TOPFLOOR LIVING_UNIT1_BACKROW_TOPFLOOR 0.4008 1200.55 481.17 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 432.94
LIVING PLUG-IN LIGHTING1_BACKROW_TOPFLOOR LIVING_UNIT1_BACKROW_TOPFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_BACKROW_TOPFLOOR LIVING_UNIT2_BACKROW_TOPFLOOR 0.4008 1200.55 481.17 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 432.94
LIVING PLUG-IN LIGHTING2_BACKROW_TOPFLOOR LIVING_UNIT2_BACKROW_TOPFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_BACKROW_TOPFLOOR LIVING_UNIT3_BACKROW_TOPFLOOR 0.4008 1200.55 481.17 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 432.94
LIVING PLUG-IN LIGHTING3_BACKROW_TOPFLOOR LIVING_UNIT3_BACKROW_TOPFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
Interior Lighting Total   0.2915 43219.92 12599.76               11336.81


Daylighting

Zone Control Name Daylighting Method Control Type Fraction Controlled Lighting Installed in Zone [Btu/h] Lighting Controlled [Btu/h]
None              


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [kWh]
EXTERIOR-LIGHTS_UNIT1_FRONTROW_BOTTOMFLOOR 69.87 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 306.04
GARAGE-LIGHTS_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT2_FRONTROW_BOTTOMFLOOR 69.87 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 306.04
GARAGE-LIGHTS_UNIT2_FRONTROW_BOTTOMFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT3_FRONTROW_BOTTOMFLOOR 69.87 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 306.04
GARAGE-LIGHTS_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT1_BACKROW_BOTTOMFLOOR 69.87 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 306.04
GARAGE-LIGHTS_UNIT1_BACKROW_BOTTOMFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT2_BACKROW_BOTTOMFLOOR 69.87 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 306.04
GARAGE-LIGHTS_UNIT2_BACKROW_BOTTOMFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT3_BACKROW_BOTTOMFLOOR 69.87 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 306.04
GARAGE-LIGHTS_UNIT3_BACKROW_BOTTOMFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT1_FRONTROW_MIDDLEFLOOR 69.87 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 306.04
GARAGE-LIGHTS_UNIT1_FRONTROW_MIDDLEFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT2_FRONTROW_MIDDLEFLOOR 69.87 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 306.04
GARAGE-LIGHTS_UNIT2_FRONTROW_MIDDLEFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT3_FRONTROW_MIDDLEFLOOR 69.87 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 306.04
GARAGE-LIGHTS_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT1_BACKROW_MIDDLEFLOOR 69.87 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 306.04
GARAGE-LIGHTS_UNIT1_BACKROW_MIDDLEFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT2_BACKROW_MIDDLEFLOOR 69.87 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 306.04
GARAGE-LIGHTS_UNIT2_BACKROW_MIDDLEFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT3_BACKROW_MIDDLEFLOOR 69.87 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 306.04
GARAGE-LIGHTS_UNIT3_BACKROW_MIDDLEFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT1_FRONTROW_TOPFLOOR 69.87 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 306.04
GARAGE-LIGHTS_UNIT1_FRONTROW_TOPFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT2_FRONTROW_TOPFLOOR 69.87 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 306.04
GARAGE-LIGHTS_UNIT2_FRONTROW_TOPFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT3_FRONTROW_TOPFLOOR 69.87 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 306.04
GARAGE-LIGHTS_UNIT3_FRONTROW_TOPFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT1_BACKROW_TOPFLOOR 69.87 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 306.04
GARAGE-LIGHTS_UNIT1_BACKROW_TOPFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT2_BACKROW_TOPFLOOR 69.87 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 306.04
GARAGE-LIGHTS_UNIT2_BACKROW_TOPFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT3_BACKROW_TOPFLOOR 69.87 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 306.04
GARAGE-LIGHTS_UNIT3_BACKROW_TOPFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
Exterior Lighting Total 1257.69           5508.71



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2021-05-12 10:29:11

Central Plant

Type Nominal Capacity [Btu/h] Nominal Efficiency [Btuh/Btuh] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
None          


Cooling Coils

Type Design Coil Load [Btu/h] Nominal Total Capacity [Btu/h] Nominal Sensible Capacity [Btu/h] Nominal Latent Capacity [Btu/h] Nominal Sensible Heat Ratio Nominal Efficiency [Btuh/Btuh] Nominal Coil UA Value [Btu/h-F] Nominal Coil Surface Area [ft2]
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   13051.63 10449.86 2601.77 0.80 4.07    
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   5930.13 4747.99 1182.14 0.80 4.07    
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   9421.83 7543.64 1878.19 0.80 4.07    
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   12888.03 10318.87 2569.16 0.80 4.07    
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   6027.84 4826.22 1201.62 0.80 4.07    
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   9258.15 7412.59 1845.56 0.80 4.07    
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   12589.38 10079.75 2509.63 0.80 4.07    
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   5743.38 4598.47 1144.91 0.80 4.07    
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   9621.59 7703.58 1918.01 0.80 4.07    
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   12433.56 9954.99 2478.56 0.80 4.07    
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   5796.34 4640.87 1155.47 0.80 4.07    
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   9441.58 7559.45 1882.13 0.80 4.07    
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   13193.09 10563.12 2629.97 0.80 4.07    
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   6463.56 5175.08 1288.48 0.80 4.07    
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   9800.95 7847.18 1953.77 0.80 4.07    
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   13224.64 10588.37 2636.26 0.80 4.07    
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   6660.11 5332.45 1327.66 0.80 4.07    
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   9618.83 7701.37 1917.46 0.80 4.07    
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [ton] Standard Rated Net COP [Btuh/Btuh] EER [Btu/W-h] SEER User [Btu/W-h] SEER Standard [Btu/W-h] IEER [Btu/W-h]
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR   1.0 3.26 11.12 11.77 11.32 11.27
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR   0.5 3.26 11.12 11.77 11.32 11.27
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR   0.7 3.26 11.12 11.77 11.32 11.27
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR   1.0 3.26 11.12 11.77 11.32 11.27
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR   0.5 3.26 11.12 11.77 11.32 11.27
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR   0.7 3.26 11.12 11.77 11.32 11.27
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR   1.0 3.26 11.12 11.77 11.32 11.27
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR   0.5 3.26 11.12 11.77 11.32 11.27
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR   0.8 3.26 11.12 11.77 11.32 11.27
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR   1.0 3.26 11.12 11.77 11.32 11.27
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR   0.5 3.26 11.12 11.77 11.32 11.27
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR   0.7 3.26 11.12 11.77 11.32 11.27
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR   1.0 3.26 11.12 11.77 11.32 11.27
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR   0.5 3.26 11.12 11.77 11.32 11.27
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR   0.8 3.26 11.12 11.77 11.32 11.27
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR   1.1 3.26 11.12 11.77 11.32 11.27
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR   0.5 3.26 11.12 11.77 11.32 11.27
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR   0.8 3.26 11.12 11.77 11.32 11.27
ANSI/AHRI ratings account for supply air fan heat and electric power. SEER User is calculated using user-input PLF curve and cooling coefficient of degradation whereas SEER Standard is calculated using AHRI Std 210/240-2008 default PLF curve and cooling coefficient of degradation.

DX Cooling Coil ASHRAE 127 Standard Ratings Report

DX Cooling Coil Type Rated Net Cooling Capacity Test A [ton] Rated Electric Power Test A [W] Rated Net Cooling Capacity Test B [ton] Rated Electric Power Test B [W] Rated Net Cooling Capacity Test C [ton] Rated Electric Power Test C [W] Rated Net Cooling Capacity Test D [ton] Rated Electric Power Test D [W]
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                


DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [Btu/h] Low Temperature Heating (net) Rating Capacity [Btu/h] HSPF [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [Btu/h] Nominal Total Capacity [Btu/h] Nominal Efficiency [Btuh/Btuh]
MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Heating:Electric   7601.34 1.00
MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Heating:Electric   5979.68 1.00
MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Heating:Electric   7603.87 1.00
MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Heating:Electric   7604.31 1.00
MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Heating:Electric   5980.09 1.00
MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Heating:Electric   7601.76 1.00
MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Heating:Electric   5784.23 1.00
MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Heating:Electric   4175.88 1.00
MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Heating:Electric   5786.51 1.00
MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Heating:Electric   5786.94 1.00
MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Heating:Electric   4176.23 1.00
MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Heating:Electric   5784.59 1.00
MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Heating:Electric   7268.08 1.00
MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Heating:Electric   5646.91 1.00
MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Heating:Electric   7269.71 1.00
MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Heating:Electric   7271.55 1.00
MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Heating:Electric   5648.65 1.00
MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Heating:Electric   7269.84 1.00
HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_FRONTROW_BOTTOMFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped   3319.56 3.00
HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_FRONTROW_BOTTOMFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped   3319.56 3.00
HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_FRONTROW_BOTTOMFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped   3319.56 3.00
HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_BACKROW_BOTTOMFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped   3319.56 3.00
HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_BACKROW_BOTTOMFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped   3319.56 3.00
HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_BACKROW_BOTTOMFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped   3319.56 3.00
HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_FRONTROW_MIDDLEFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped   3319.56 3.00
HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_FRONTROW_MIDDLEFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped   3319.56 3.00
HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_FRONTROW_MIDDLEFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped   3319.56 3.00
HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_BACKROW_MIDDLEFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped   3319.56 3.00
HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_BACKROW_MIDDLEFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped   3319.56 3.00
HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_BACKROW_MIDDLEFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped   3319.56 3.00
HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_FRONTROW_TOPFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped   3319.56 3.00
HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_FRONTROW_TOPFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped   3319.56 3.00
HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_FRONTROW_TOPFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped   3319.56 3.00
HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_BACKROW_TOPFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped   3319.56 3.00
HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_BACKROW_TOPFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped   3319.56 3.00
HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_BACKROW_TOPFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped   3319.56 3.00
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

Fans

Type Total Efficiency [Btuh/Btuh] Delta Pressure [psi] Max Air Flow Rate [ft3/min] Rated Electricity Rate [W] Rated Power Per Max Air Flow Rate [W-min/ft3] Motor Heat In Air Fraction Fan Energy Index End Use Subcategory Design Day Name for Fan Sizing Peak Date/Time for Fan Sizing Peak
OASUPPLYFAN_UNIT1_FRONTROW_BOTTOMFLOOR Fan:OnOff 0.60 0.03 44.99 8.04 0.18 0.00 17.66 Ventilation    
OAEXHAUSTFAN_UNIT1_FRONTROW_BOTTOMFLOOR Fan:OnOff 0.60 0.03 44.99 8.04 0.18 0.00 17.66 Ventilation    
OASUPPLYFAN_UNIT2_FRONTROW_BOTTOMFLOOR Fan:OnOff 0.60 0.03 44.99 8.04 0.18 0.00 17.66 Ventilation    
OAEXHAUSTFAN_UNIT2_FRONTROW_BOTTOMFLOOR Fan:OnOff 0.60 0.03 44.99 8.04 0.18 0.00 17.66 Ventilation    
OASUPPLYFAN_UNIT3_FRONTROW_BOTTOMFLOOR Fan:OnOff 0.60 0.03 44.99 8.04 0.18 0.00 17.66 Ventilation    
OAEXHAUSTFAN_UNIT3_FRONTROW_BOTTOMFLOOR Fan:OnOff 0.60 0.03 44.99 8.04 0.18 0.00 17.66 Ventilation    
OASUPPLYFAN_UNIT1_BACKROW_BOTTOMFLOOR Fan:OnOff 0.60 0.03 44.99 8.04 0.18 0.00 17.66 Ventilation    
OAEXHAUSTFAN_UNIT1_BACKROW_BOTTOMFLOOR Fan:OnOff 0.60 0.03 44.99 8.04 0.18 0.00 17.66 Ventilation    
OASUPPLYFAN_UNIT2_BACKROW_BOTTOMFLOOR Fan:OnOff 0.60 0.03 44.99 8.04 0.18 0.00 17.66 Ventilation    
OAEXHAUSTFAN_UNIT2_BACKROW_BOTTOMFLOOR Fan:OnOff 0.60 0.03 44.99 8.04 0.18 0.00 17.66 Ventilation    
OASUPPLYFAN_UNIT3_BACKROW_BOTTOMFLOOR Fan:OnOff 0.60 0.03 44.99 8.04 0.18 0.00 17.66 Ventilation    
OAEXHAUSTFAN_UNIT3_BACKROW_BOTTOMFLOOR Fan:OnOff 0.60 0.03 44.99 8.04 0.18 0.00 17.66 Ventilation    
OASUPPLYFAN_UNIT1_FRONTROW_MIDDLEFLOOR Fan:OnOff 0.60 0.03 44.99 8.04 0.18 0.00 17.66 Ventilation    
OAEXHAUSTFAN_UNIT1_FRONTROW_MIDDLEFLOOR Fan:OnOff 0.60 0.03 44.99 8.04 0.18 0.00 17.66 Ventilation    
OASUPPLYFAN_UNIT2_FRONTROW_MIDDLEFLOOR Fan:OnOff 0.60 0.03 44.99 8.04 0.18 0.00 17.66 Ventilation    
OAEXHAUSTFAN_UNIT2_FRONTROW_MIDDLEFLOOR Fan:OnOff 0.60 0.03 44.99 8.04 0.18 0.00 17.66 Ventilation    
OASUPPLYFAN_UNIT3_FRONTROW_MIDDLEFLOOR Fan:OnOff 0.60 0.03 44.99 8.04 0.18 0.00 17.66 Ventilation    
OAEXHAUSTFAN_UNIT3_FRONTROW_MIDDLEFLOOR Fan:OnOff 0.60 0.03 44.99 8.04 0.18 0.00 17.66 Ventilation    
OASUPPLYFAN_UNIT1_BACKROW_MIDDLEFLOOR Fan:OnOff 0.60 0.03 44.99 8.04 0.18 0.00 17.66 Ventilation    
OAEXHAUSTFAN_UNIT1_BACKROW_MIDDLEFLOOR Fan:OnOff 0.60 0.03 44.99 8.04 0.18 0.00 17.66 Ventilation    
OASUPPLYFAN_UNIT2_BACKROW_MIDDLEFLOOR Fan:OnOff 0.60 0.03 44.99 8.04 0.18 0.00 17.66 Ventilation    
OAEXHAUSTFAN_UNIT2_BACKROW_MIDDLEFLOOR Fan:OnOff 0.60 0.03 44.99 8.04 0.18 0.00 17.66 Ventilation    
OASUPPLYFAN_UNIT3_BACKROW_MIDDLEFLOOR Fan:OnOff 0.60 0.03 44.99 8.04 0.18 0.00 17.66 Ventilation    
OAEXHAUSTFAN_UNIT3_BACKROW_MIDDLEFLOOR Fan:OnOff 0.60 0.03 44.99 8.04 0.18 0.00 17.66 Ventilation    
OASUPPLYFAN_UNIT3_BACKROW_TOPFLOOR Fan:OnOff 0.60 0.03 44.99 8.04 0.18 0.00 17.66 Ventilation    
OAEXHAUSTFAN_UNIT3_BACKROW_TOPFLOOR Fan:OnOff 0.60 0.03 44.99 8.04 0.18 0.00 17.66 Ventilation    
OASUPPLYFAN_UNIT3_FRONTROW_TOPFLOOR Fan:OnOff 0.60 0.03 44.99 8.04 0.18 0.00 17.66 Ventilation    
OAEXHAUSTFAN_UNIT3_FRONTROW_TOPFLOOR Fan:OnOff 0.60 0.03 44.99 8.04 0.18 0.00 17.66 Ventilation    
OASUPPLYFAN_UNIT1_FRONTROW_TOPFLOOR Fan:OnOff 0.60 0.03 44.99 8.04 0.18 0.00 17.66 Ventilation    
OAEXHAUSTFAN_UNIT1_FRONTROW_TOPFLOOR Fan:OnOff 0.60 0.03 44.99 8.04 0.18 0.00 17.66 Ventilation    
OASUPPLYFAN_UNIT2_BACKROW_TOPFLOOR Fan:OnOff 0.60 0.03 44.99 8.04 0.18 0.00 17.66 Ventilation    
OAEXHAUSTFAN_UNIT2_BACKROW_TOPFLOOR Fan:OnOff 0.60 0.03 44.99 8.04 0.18 0.00 17.66 Ventilation    
OASUPPLYFAN_UNIT2_FRONTROW_TOPFLOOR Fan:OnOff 0.60 0.03 44.99 8.04 0.18 0.00 17.66 Ventilation    
OAEXHAUSTFAN_UNIT2_FRONTROW_TOPFLOOR Fan:OnOff 0.60 0.03 44.99 8.04 0.18 0.00 17.66 Ventilation    
OASUPPLYFAN_UNIT1_BACKROW_TOPFLOOR Fan:OnOff 0.60 0.03 44.99 8.04 0.18 0.00 17.66 Ventilation    
OAEXHAUSTFAN_UNIT1_BACKROW_TOPFLOOR Fan:OnOff 0.60 0.03 44.99 8.04 0.18 0.00 17.66 Ventilation    
SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 489.58 184.67 0.38 1.00 2.16 General ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00
SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 222.44 83.90 0.38 1.00 3.30 General ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00
SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 353.42 133.31 0.38 1.00 2.53 General ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00
SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 483.44 182.35 0.38 1.00 2.17 General ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00
SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 226.11 85.29 0.38 1.00 3.26 General ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00
SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 347.28 130.99 0.38 1.00 2.55 General ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00
SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 472.24 178.13 0.38 1.00 2.20 General ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00
SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 215.44 81.26 0.38 1.00 3.36 General ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00
SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 360.91 136.13 0.38 1.00 2.50 General ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00
SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 466.39 175.92 0.38 1.00 2.21 General ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00
SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 217.43 82.01 0.38 1.00 3.34 General ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00
SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 354.16 133.59 0.38 1.00 2.53 General ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00
SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR Fan:OnOff 0.50 0.06 494.89 186.67 0.38 1.00 2.15 General ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00
SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR Fan:OnOff 0.50 0.06 242.45 91.45 0.38 1.00 3.13 General ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00
SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR Fan:OnOff 0.50 0.06 367.64 138.67 0.38 1.00 2.48 General ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00
SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR Fan:OnOff 0.50 0.06 496.07 187.11 0.38 1.00 2.15 General ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00
SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR Fan:OnOff 0.50 0.06 249.83 94.23 0.38 1.00 3.07 General ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00
SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR Fan:OnOff 0.50 0.06 360.81 136.10 0.38 1.00 2.50 General ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00
HEAT PUMP WATER HEATER FAN_UNIT1_FRONTROW_BOTTOMFLOOR Fan:OnOff 0.70 0.01 160.01 10.79 0.07 1.00 11.80 General    
HEAT PUMP WATER HEATER FAN_UNIT2_FRONTROW_BOTTOMFLOOR Fan:OnOff 0.70 0.01 160.01 10.79 0.07 1.00 11.80 General    
HEAT PUMP WATER HEATER FAN_UNIT3_FRONTROW_BOTTOMFLOOR Fan:OnOff 0.70 0.01 160.01 10.79 0.07 1.00 11.80 General    
HEAT PUMP WATER HEATER FAN_UNIT1_BACKROW_BOTTOMFLOOR Fan:OnOff 0.70 0.01 160.01 10.79 0.07 1.00 11.80 General    
HEAT PUMP WATER HEATER FAN_UNIT2_BACKROW_BOTTOMFLOOR Fan:OnOff 0.70 0.01 160.01 10.79 0.07 1.00 11.80 General    
HEAT PUMP WATER HEATER FAN_UNIT3_BACKROW_BOTTOMFLOOR Fan:OnOff 0.70 0.01 160.01 10.79 0.07 1.00 11.80 General    
HEAT PUMP WATER HEATER FAN_UNIT1_FRONTROW_MIDDLEFLOOR Fan:OnOff 0.70 0.01 160.01 10.79 0.07 1.00 11.80 General    
HEAT PUMP WATER HEATER FAN_UNIT2_FRONTROW_MIDDLEFLOOR Fan:OnOff 0.70 0.01 160.01 10.79 0.07 1.00 11.80 General    
HEAT PUMP WATER HEATER FAN_UNIT3_FRONTROW_MIDDLEFLOOR Fan:OnOff 0.70 0.01 160.01 10.79 0.07 1.00 11.80 General    
HEAT PUMP WATER HEATER FAN_UNIT1_BACKROW_MIDDLEFLOOR Fan:OnOff 0.70 0.01 160.01 10.79 0.07 1.00 11.80 General    
HEAT PUMP WATER HEATER FAN_UNIT2_BACKROW_MIDDLEFLOOR Fan:OnOff 0.70 0.01 160.01 10.79 0.07 1.00 11.80 General    
HEAT PUMP WATER HEATER FAN_UNIT3_BACKROW_MIDDLEFLOOR Fan:OnOff 0.70 0.01 160.01 10.79 0.07 1.00 11.80 General    
HEAT PUMP WATER HEATER FAN_UNIT1_FRONTROW_TOPFLOOR Fan:OnOff 0.70 0.01 160.01 10.79 0.07 1.00 11.80 General    
HEAT PUMP WATER HEATER FAN_UNIT2_FRONTROW_TOPFLOOR Fan:OnOff 0.70 0.01 160.01 10.79 0.07 1.00 11.80 General    
HEAT PUMP WATER HEATER FAN_UNIT3_FRONTROW_TOPFLOOR Fan:OnOff 0.70 0.01 160.01 10.79 0.07 1.00 11.80 General    
HEAT PUMP WATER HEATER FAN_UNIT1_BACKROW_TOPFLOOR Fan:OnOff 0.70 0.01 160.01 10.79 0.07 1.00 11.80 General    
HEAT PUMP WATER HEATER FAN_UNIT2_BACKROW_TOPFLOOR Fan:OnOff 0.70 0.01 160.01 10.79 0.07 1.00 11.80 General    
HEAT PUMP WATER HEATER FAN_UNIT3_BACKROW_TOPFLOOR Fan:OnOff 0.70 0.01 160.01 10.79 0.07 1.00 11.80 General    


Pumps

Type Control Head [psi] Water Flow [gal/min] Electricity Rate [W] Power Per Water Flow Rate [W-min/gal] Motor Efficiency [Btuh/Btuh] End Use Subcategory
MAINS PRESSURE_UNIT1_FRONTROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT2_FRONTROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT3_FRONTROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT1_BACKROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT2_BACKROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT3_BACKROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT1_FRONTROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT2_FRONTROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT3_FRONTROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT1_BACKROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT2_BACKROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT3_BACKROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT1_FRONTROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT2_FRONTROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT3_FRONTROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT1_BACKROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT2_BACKROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT3_BACKROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General


Service Water Heating

Type Storage Volume [ft3] Input [Btu/h] Thermal Efficiency [Btuh/Btuh] Recovery Efficiency [Btuh/Btuh] Energy Factor
WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR WaterHeater:HeatPump:WrappedCondenser 6.95 4165.60 1.00 0.00 0.00
WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR WaterHeater:HeatPump:WrappedCondenser 6.95 4165.60 1.00 0.00 0.00
WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR WaterHeater:HeatPump:WrappedCondenser 6.95 4165.60 1.00 0.00 0.00
WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR WaterHeater:HeatPump:WrappedCondenser 6.95 4165.60 1.00 0.00 0.00
WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR WaterHeater:HeatPump:WrappedCondenser 6.95 4165.60 1.00 0.00 0.00
WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR WaterHeater:HeatPump:WrappedCondenser 6.95 4165.60 1.00 0.00 0.00
WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR WaterHeater:HeatPump:WrappedCondenser 6.95 4165.60 1.00 0.00 0.00
WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR WaterHeater:HeatPump:WrappedCondenser 6.95 4165.60 1.00 0.00 0.00
WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR WaterHeater:HeatPump:WrappedCondenser 6.95 4165.60 1.00 0.00 0.00
WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR WaterHeater:HeatPump:WrappedCondenser 6.95 4165.60 1.00 0.00 0.00
WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR WaterHeater:HeatPump:WrappedCondenser 6.95 4165.60 1.00 0.00 0.00
WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR WaterHeater:HeatPump:WrappedCondenser 6.95 4165.60 1.00 0.00 0.00
WATER HEATER_UNIT1_FRONTROW_TOPFLOOR WaterHeater:HeatPump:WrappedCondenser 6.95 4165.60 1.00 0.00 0.00
WATER HEATER_UNIT2_FRONTROW_TOPFLOOR WaterHeater:HeatPump:WrappedCondenser 6.95 4165.60 1.00 0.00 0.00
WATER HEATER_UNIT3_FRONTROW_TOPFLOOR WaterHeater:HeatPump:WrappedCondenser 6.95 4165.60 1.00 0.00 0.00
WATER HEATER_UNIT1_BACKROW_TOPFLOOR WaterHeater:HeatPump:WrappedCondenser 6.95 4165.60 1.00 0.00 0.00
WATER HEATER_UNIT2_BACKROW_TOPFLOOR WaterHeater:HeatPump:WrappedCondenser 6.95 4165.60 1.00 0.00 0.00
WATER HEATER_UNIT3_BACKROW_TOPFLOOR WaterHeater:HeatPump:WrappedCondenser 6.95 4165.60 1.00 0.00 0.00



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2021-05-12 10:29:11

Zone Sensible Cooling

Calculated Design Load [Btu/h] User Design Load [Btu/h] User Design Load per Area [Btu/h-ft2] Calculated Design Air Flow [ft3/min] User Design Air Flow [ft3/min] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [F] Indoor Temperature at Peak Load [F] Indoor Humidity Ratio at Peak Load [lbWater/lbDryAir] Outdoor Temperature at Peak Load [F] Outdoor Humidity Ratio at Peak Load [lbWater/lbDryAir] Minimum Outdoor Air Flow Rate [ft3/min] Heat Gain Rate from DOAS [Btu/h]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 9468.47 9468.47 7.89 489.579 489.579 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 75.00 75.00 0.00822 90.56 0.00570 44.995 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 4302.05 4302.05 3.58 222.445 222.445 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 75.00 75.00 0.00851 85.70 0.00569 44.995 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 6835.24 6835.24 5.69 353.422 353.422 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:20:00 75.00 75.00 0.00815 87.16 0.00569 44.995 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 9349.76 9349.76 7.79 483.442 483.442 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:40:00 75.00 75.00 0.00824 90.16 0.00570 44.995 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 4372.93 4372.93 3.64 226.110 226.110 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 75.00 75.00 0.00851 85.70 0.00569 44.995 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 6716.48 6716.48 5.59 347.282 347.282 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 09:50:00 75.00 75.00 0.00816 85.26 0.00569 44.995 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 9133.01 9133.01 7.61 472.239 472.239 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:40:00 75.00 75.00 0.00830 90.16 0.00570 44.995 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 4166.54 4166.54 3.47 215.440 215.440 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 75.00 75.00 0.00865 85.70 0.00569 44.995 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 6980.12 6980.12 5.81 360.915 360.915 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:30:00 75.00 75.00 0.00821 87.77 0.00569 44.995 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 9019.95 9019.95 7.51 466.394 466.394 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:50:00 75.00 75.00 0.00831 89.75 0.00569 44.995 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 4204.96 4204.96 3.50 217.426 217.426 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 75.00 75.00 0.00865 85.70 0.00569 44.995 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 6849.52 6849.52 5.71 354.163 354.163 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:10:00 75.00 75.00 0.00822 86.55 0.00569 44.995 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 6978.15 6978.15 5.81 360.811 360.811 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:10:00 75.00 75.00 0.00815 86.55 0.00569 44.995 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 7110.29 7110.29 5.92 367.643 367.643 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:30:00 75.00 75.00 0.00814 87.77 0.00569 44.995 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 9571.07 9571.07 7.97 494.885 494.885 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:40:00 75.00 75.00 0.00824 90.16 0.00570 44.995 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 4831.61 4831.61 4.02 249.827 249.827 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 75.00 75.00 0.00848 85.70 0.00569 44.995 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 4689.03 4689.03 3.91 242.454 242.454 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 75.00 75.00 0.00848 85.70 0.00569 44.995 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 9593.93 9593.93 7.99 496.068 496.068 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:50:00 75.00 75.00 0.00825 89.75 0.00569 44.995 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

Zone Sensible Heating

Calculated Design Load [Btu/h] User Design Load [Btu/h] User Design Load per Area [Btu/h-ft2] Calculated Design Air Flow [ft3/min] User Design Air Flow [ft3/min] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [F] Indoor Temperature at Peak Load [F] Indoor Humidity Ratio at Peak Load [lbWater/lbDryAir] Outdoor Temperature at Peak Load [F] Outdoor Humidity Ratio at Peak Load [lbWater/lbDryAir] Minimum Outdoor Air Flow Rate [ft3/min] Heat Gain Rate from DOAS [Btu/h]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 5509.37 5509.37 4.59 121.939 121.939 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 72.00 0.00736 17.78 0.00234 44.995 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 3863.73 3863.73 3.22 85.516 85.516 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 72.00 0.00729 17.78 0.00234 44.995 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 5511.95 5511.95 4.59 121.995 121.995 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 72.00 0.00736 17.78 0.00234 44.995 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 5512.39 5512.39 4.59 122.005 122.005 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 72.00 0.00736 17.78 0.00234 44.995 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 3864.14 3864.14 3.22 85.526 85.526 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 72.00 0.00729 17.78 0.00234 44.995 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 5509.80 5509.80 4.59 121.948 121.948 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 72.00 0.00736 17.78 0.00234 44.995 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 3665.32 3665.32 3.05 81.128 81.128 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 72.00 0.00789 17.78 0.00234 44.995 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 2033.17 2033.17 1.69 45.003 45.003 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 72.00 0.00825 17.78 0.00234 44.995 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 3667.63 3667.63 3.05 81.179 81.179 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 72.00 0.00789 17.78 0.00234 44.995 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 3668.06 3668.06 3.06 81.188 81.188 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 72.00 0.00789 17.78 0.00234 44.995 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 2033.52 2033.52 1.69 45.010 45.010 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 72.00 0.00825 17.78 0.00234 44.995 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 3665.68 3665.68 3.05 81.136 81.136 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 72.00 0.00789 17.78 0.00234 44.995 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 5172.98 5172.98 4.31 114.493 114.493 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 72.00 0.00732 17.78 0.00234 44.995 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 5172.85 5172.85 4.31 114.490 114.490 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 72.00 0.00732 17.78 0.00234 44.995 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 5171.19 5171.19 4.31 114.454 114.454 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 72.00 0.00732 17.78 0.00234 44.995 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 3527.80 3527.80 2.94 78.081 78.081 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 72.00 0.00724 17.78 0.00234 44.995 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 3526.03 3526.03 2.94 78.042 78.042 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 72.00 0.00724 17.78 0.00234 44.995 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 5174.71 5174.71 4.31 114.531 114.531 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 72.00 0.00732 17.78 0.00234 44.995 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

System Design Air Flow Rates

Calculated cooling [ft3/min] User cooling [ft3/min] Calculated heating [ft3/min] User heating [ft3/min] Adjusted cooling [ft3/min] Adjusted heating [ft3/min] Adjusted main [ft3/min] Calculated Heating Air Flow Ratio [] User Heating Air Flow Ratio []
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 489.58 489.58 121.94 121.94 489.5787 489.5787 489.5787 1.0000 1.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 222.44 222.44 85.52 85.52 222.4448 222.4448 222.4448 1.0000 1.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 353.42 353.42 122.00 122.00 353.4216 353.4216 353.4216 1.0000 1.0000
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 483.44 483.44 122.01 122.01 483.4420 483.4420 483.4420 1.0000 1.0000
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 226.11 226.11 85.53 85.53 226.1097 226.1097 226.1097 1.0000 1.0000
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 347.28 347.28 121.95 121.95 347.2818 347.2818 347.2818 1.0000 1.0000
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 472.24 472.24 81.13 81.13 472.2391 472.2391 472.2391 1.0000 1.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 215.44 215.44 45.00 45.00 215.4396 215.4396 215.4396 1.0000 1.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 360.91 360.91 81.18 81.18 360.9149 360.9149 360.9149 1.0000 1.0000
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 466.39 466.39 81.19 81.19 466.3943 466.3943 466.3943 1.0000 1.0000
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 217.43 217.43 45.01 45.01 217.4262 217.4262 217.4262 1.0000 1.0000
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 354.16 354.16 81.14 81.14 354.1626 354.1626 354.1626 1.0000 1.0000
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 494.89 494.89 114.45 114.45 494.8850 494.8850 494.8850 1.0000 1.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 242.45 242.45 78.04 78.04 242.4541 242.4541 242.4541 1.0000 1.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 367.64 367.64 114.49 114.49 367.6428 367.6428 367.6428 1.0000 1.0000
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 496.07 496.07 114.53 114.53 496.0683 496.0683 496.0683 1.0000 1.0000
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 249.83 249.83 78.08 78.08 249.8268 249.8268 249.8268 1.0000 1.0000
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 360.81 360.81 114.49 114.49 360.8112 360.8112 360.8112 1.0000 1.0000


Plant Loop Coincident Design Fluid Flow Rate Adjustments

Previous Design Volume Flow Rate [ft3/min] Algorithm Volume Flow Rate [ft3/min] Coincident Design Volume Flow Rate [ft3/min] Coincident Size Adjusted Peak Sizing Period Name Peak Day into Period {TIMESTAMP}[day] Peak Hour Of Day {TIMESTAMP}[hr] Peak Step Start Minute {TIMESTAMP}[min]
None                


Coil Sizing Summary

Coil Type HVAC Type HVAC Name Coil Final Gross Total Capacity [Btu/h] Coil Final Gross Sensible Capacity [Btu/h] Coil Final Reference Air Volume Flow Rate [ft3/min] Coil Final Reference Plant Fluid Volume Flow Rate [ft3/min] Coil U-value Times Area Value [Btu/h-F] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Coil Total Capacity at Ideal Loads Peak [Btu/h] Coil Sensible Capacity at Ideal Loads Peak [Btu/h] Coil Air Volume Flow Rate at Ideal Loads Peak [ft3/min] Coil Entering Air Drybulb at Ideal Loads Peak [F] Coil Entering Air Wetbulb at Ideal Loads Peak [F] Coil Entering Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] Coil Leaving Air Drybulb at Ideal Loads Peak [F] Coil Leaving Air Wetbulb at Ideal Loads Peak [F] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] Outdoor Air Drybulb at Ideal Loads Peak [F] Outdoor Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [F] Outdoor Air Flow Percentage at Ideal Loads Peak [%] Zone Air Drybulb at Ideal Loads Peak [F] Zone Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [Btu/h] Zone Latent Heat Gain at Ideal Loads Peak [Btu/h] Coil Total Capacity at Rating Conditions [Btu/h] Coil Sensible Capacity at Rating Conditions [Btu/h]
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 13051.631 10449.857 489.578731 -999. -999.00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:20:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 14162.40 14162.40 489.578731 77.85 58.04 0.00799103 53.60 49.15 0.00799103 90.56 0.00569540 58.90 9.1906 75.00 0.00819875 36.5611 9465.69 0.00 13057.08 9483.00
MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Heating:Electric AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 7601.337 7601.337 -999. -999. -999.00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 7601.34 7601.34 489.578731 67.01 52.50 0.00689718 122.00 70.83 0.00800000 17.78 0.00234317 17.78 9.1906 72.00 0.00735807 36.3448 5509.37 0.00 -999.0 -999.0
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 5930.134 4747.993 222.444803 -999. -999.00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:20:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 6266.34 6266.34 222.444803 78.59 58.21 0.00793895 53.60 49.06 0.00793895 85.70 0.00569125 57.27 20.2275 75.00 0.00844037 37.6243 4238.39 0.00 5932.61 4308.69
MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Heating:Electric AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 5979.683 5979.683 -999. -999. -999.00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 5979.68 5979.68 222.444803 61.03 49.14 0.00629312 122.00 70.83 0.00800000 17.78 0.00234317 17.78 20.2275 72.00 0.00729468 36.0347 3863.73 0.00 -999.0 -999.0
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 9421.831 7543.639 353.421600 -999. -999.00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:30:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:20:00 10056.01 10056.01 353.421600 77.97 57.85 0.00783677 53.60 48.88 0.00783677 87.16 0.00569249 57.76 12.7312 75.00 0.00814678 36.3321 6825.05 0.00 9425.76 6845.67
MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Heating:Electric AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 7603.873 7603.873 -999. -999. -999.00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 7603.87 7603.87 353.421600 65.10 51.47 0.00671982 122.00 70.83 0.00800000 17.78 0.00234317 17.78 12.7312 72.00 0.00735832 36.3459 5511.95 0.00 -999.0 -999.0
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 12888.033 10318.872 483.442036 -999. -999.00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:40:00 13954.06 13949.00 483.442036 77.83 58.05 0.00800256 53.60 49.17 0.00800000 90.16 0.00569506 58.76 9.3072 75.00 0.00822440 36.6742 9337.44 0.00 12893.41 9364.13
MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Heating:Electric AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 7604.306 7604.306 -999. -999. -999.00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 7604.31 7604.31 483.442036 66.95 52.46 0.00689158 122.00 70.83 0.00800000 17.78 0.00234317 17.78 9.3072 72.00 0.00735836 36.3462 5512.39 0.00 -999.0 -999.0
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 6027.836 4826.219 226.109696 -999. -999.00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:40:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 6369.68 6369.68 226.109696 78.55 58.20 0.00794556 53.60 49.07 0.00794556 85.70 0.00569125 57.27 19.8996 75.00 0.00847906 37.7945 4347.48 0.00 6030.35 4379.68
MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Heating:Electric AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 5980.093 5980.093 -999. -999. -999.00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 5980.09 5980.09 226.109696 61.21 49.24 0.00630940 122.00 70.83 0.00800000 17.78 0.00234317 17.78 19.8996 72.00 0.00729474 36.0350 3864.14 0.00 -999.0 -999.0
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 9258.151 7412.588 347.281814 -999. -999.00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:10:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 09:50:00 9789.73 9789.73 347.281814 77.75 57.79 0.00784231 53.60 48.89 0.00784231 85.26 0.00569088 57.12 12.9563 75.00 0.00815395 36.3636 6698.42 0.00 9262.01 6726.75
MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Heating:Electric AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 7601.756 7601.756 -999. -999. -999.00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 7601.76 7601.76 347.281814 64.97 51.41 0.00670836 122.00 70.83 0.00800000 17.78 0.00234317 17.78 12.9563 72.00 0.00735811 36.3450 5509.80 0.00 -999.0 -999.0
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 12589.377 10079.751 472.239150 -999. -999.00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:40:00 13623.78 13532.92 472.239150 77.87 58.12 0.00804751 53.60 49.17 0.00800000 90.16 0.00569506 58.76 9.5280 75.00 0.00827973 36.9179 9127.51 0.00 12594.63 9147.13
MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Heating:Electric AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 5784.235 5784.235 -999. -999. -999.00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 5784.23 5784.23 472.239150 66.83 53.19 0.00736521 122.00 70.83 0.00800000 17.78 0.00234317 17.78 9.5280 72.00 0.00789411 38.9565 3665.32 0.00 -999.0 -999.0
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 5743.384 4598.470 215.439629 -999. -999.00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:50:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 6062.09 6038.15 215.439629 78.66 58.36 0.00802874 53.60 49.17 0.00800000 85.70 0.00569125 57.27 20.8852 75.00 0.00863347 38.4736 4143.54 0.00 5745.78 4173.00
MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Heating:Electric AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 4175.883 4175.883 -999. -999. -999.00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 4175.88 4175.88 215.439629 60.68 50.26 0.00701565 122.00 70.83 0.00800000 17.78 0.00234317 17.78 20.8852 72.00 0.00824912 40.6846 2033.17 0.00 -999.0 -999.0
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 9621.593 7703.579 360.914858 -999. -999.00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:40:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:30:00 10294.45 10294.45 360.914858 78.02 57.95 0.00789696 53.60 48.99 0.00789696 87.77 0.00569301 57.97 12.4669 75.00 0.00821002 36.6106 6968.20 0.00 9625.61 6990.82
MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Heating:Electric AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 5786.508 5786.508 -999. -999. -999.00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 5786.51 5786.51 360.914858 65.24 52.33 0.00720210 122.00 70.83 0.00800000 17.78 0.00234317 17.78 12.4669 72.00 0.00789414 38.9566 3667.63 0.00 -999.0 -999.0
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 12433.559 9954.994 466.394279 -999. -999.00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:40:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:50:00 13426.08 13322.64 466.394279 77.85 58.13 0.00805491 53.60 49.17 0.00800000 89.75 0.00569471 58.63 9.6474 75.00 0.00829743 36.9958 9003.98 0.00 12438.75 9033.92
MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Heating:Electric AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 5786.936 5786.936 -999. -999. -999.00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 5786.94 5786.94 466.394279 66.77 53.16 0.00735862 122.00 70.83 0.00800000 17.78 0.00234317 17.78 9.6474 72.00 0.00789414 38.9566 3668.06 0.00 -999.0 -999.0
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 5796.343 4640.873 217.426192 -999. -999.00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:50:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 6117.89 6088.60 217.426192 78.64 58.36 0.00803486 53.60 49.17 0.00800000 85.70 0.00569125 57.27 20.6944 75.00 0.00863525 38.4814 4182.11 0.00 5798.76 4211.48
MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Heating:Electric AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 4176.229 4176.229 -999. -999. -999.00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 4176.23 4176.23 217.426192 60.78 50.32 0.00702686 122.00 70.83 0.00800000 17.78 0.00234317 17.78 20.6944 72.00 0.00824904 40.6842 2033.52 0.00 -999.0 -999.0
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 9441.585 7559.455 354.162572 -999. -999.00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:20:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:10:00 10041.40 10041.40 354.162572 77.89 57.91 0.00789756 53.60 48.99 0.00789756 86.55 0.00569198 57.56 12.7046 75.00 0.00821539 36.6342 6839.02 0.00 9445.52 6860.03
MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Heating:Electric AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 5784.587 5784.587 -999. -999. -999.00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 5784.59 5784.59 354.162572 65.11 52.26 0.00718889 122.00 70.83 0.00800000 17.78 0.00234317 17.78 12.7046 72.00 0.00789411 38.9565 3665.68 0.00 -999.0 -999.0
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 13193.091 10563.118 494.885046 -999. -999.00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:40:00 14284.90 14272.90 494.885046 77.80 58.04 0.00800594 53.60 49.17 0.00800000 90.16 0.00569506 58.76 9.0920 75.00 0.00822250 36.6658 9557.08 0.00 13198.60 9585.78
MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Heating:Electric AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 7268.085 7268.085 -999. -999. -999.00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 7268.08 7268.08 494.885046 67.07 52.47 0.00687113 122.00 70.83 0.00800000 17.78 0.00234317 17.78 9.0920 72.00 0.00732399 36.1784 5171.19 0.00 -999.0 -999.0
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 6463.559 5175.083 242.454085 -999. -999.00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 6831.05 6831.05 242.454085 78.41 58.19 0.00796543 53.60 49.11 0.00796543 85.70 0.00569125 57.27 18.5581 75.00 0.00848365 37.8147 4689.03 0.00 6466.26 4696.26
MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Heating:Electric AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 5646.907 5646.907 -999. -999. -999.00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 5646.91 5646.91 242.454085 61.94 49.57 0.00633447 122.00 70.83 0.00800000 17.78 0.00234317 17.78 18.5581 72.00 0.00724397 35.7870 3526.03 0.00 -999.0 -999.0
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 9800.952 7847.184 367.642771 -999. -999.00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:40:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:30:00 10492.40 10492.40 367.642771 77.99 57.87 0.00784463 53.60 48.89 0.00784463 87.77 0.00569301 57.97 12.2388 75.00 0.00814373 36.3187 7099.68 0.00 9805.04 7121.13
MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Heating:Electric AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 7269.713 7269.713 -999. -999. -999.00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 7269.71 7269.71 367.642771 65.36 51.56 0.00671455 122.00 70.83 0.00800000 17.78 0.00234317 17.78 12.2388 72.00 0.00732416 36.1792 5172.85 0.00 -999.0 -999.0
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 13224.635 10588.374 496.068276 -999. -999.00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:50:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:50:00 14288.69 14260.36 496.068276 77.76 58.04 0.00801401 53.60 49.17 0.00800000 89.75 0.00569471 58.63 9.0703 75.00 0.00824536 36.7665 9593.93 0.00 13230.15 9608.70
MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Heating:Electric AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 7271.551 7271.551 -999. -999. -999.00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 7271.55 7271.55 496.068276 67.08 52.48 0.00687255 122.00 70.83 0.00800000 17.78 0.00234317 17.78 9.0703 72.00 0.00732435 36.1801 5174.71 0.00 -999.0 -999.0
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 6660.109 5332.451 249.826843 -999. -999.00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 7039.11 7039.11 249.826843 78.35 58.18 0.00797428 53.60 49.12 0.00797428 85.70 0.00569125 57.27 18.0105 75.00 0.00847579 37.7802 4831.61 0.00 6662.89 4839.07
MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Heating:Electric AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 5648.648 5648.648 -999. -999. -999.00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 5648.65 5648.65 249.826843 62.23 49.74 0.00636154 122.00 70.83 0.00800000 17.78 0.00234317 17.78 18.0105 72.00 0.00724425 35.7884 3527.80 0.00 -999.0 -999.0
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 9618.829 7701.366 360.811155 -999. -999.00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:20:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:10:00 10235.89 10235.89 360.811155 77.87 57.83 0.00784472 53.60 48.89 0.00784472 86.55 0.00569198 57.56 12.4705 75.00 0.00814815 36.3381 6970.72 0.00 9622.84 6988.81
MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Heating:Electric AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 7269.841 7269.841 -999. -999. -999.00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 7269.84 7269.84 360.811155 65.24 51.50 0.00670302 122.00 70.83 0.00800000 17.78 0.00234317 17.78 12.4705 72.00 0.00732417 36.1793 5172.98 0.00 -999.0 -999.0
HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_FRONTROW_BOTTOMFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped unknown unknown 3506.446 3439.823 400.423678 -999. -999.00 unknown unknown unknown unknown 3319.56 -999.0 -999. -999.0 -999.0 -999. -999.0 -999.0 -999. -999.0 -999. -999.0 -999.000 -999.0 -999. -999.000 -999.0 0.00 -999.0 -999.0
HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_FRONTROW_BOTTOMFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped unknown unknown 3518.905 3452.046 400.423678 -999. -999.00 unknown unknown unknown unknown 3319.56 -999.0 -999. -999.0 -999.0 -999. -999.0 -999.0 -999. -999.0 -999. -999.0 -999.000 -999.0 -999. -999.000 -999.0 0.00 -999.0 -999.0
HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_FRONTROW_BOTTOMFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped unknown unknown 3506.968 3440.335 400.423678 -999. -999.00 unknown unknown unknown unknown 3319.56 -999.0 -999. -999.0 -999.0 -999. -999.0 -999.0 -999. -999.0 -999. -999.0 -999.000 -999.0 -999. -999.000 -999.0 0.00 -999.0 -999.0
HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_BACKROW_BOTTOMFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped unknown unknown 3506.489 3439.866 400.423678 -999. -999.00 unknown unknown unknown unknown 3319.56 -999.0 -999. -999.0 -999.0 -999. -999.0 -999.0 -999. -999.0 -999. -999.0 -999.000 -999.0 -999. -999.000 -999.0 0.00 -999.0 -999.0
HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_BACKROW_BOTTOMFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped unknown unknown 3518.888 3452.029 400.423678 -999. -999.00 unknown unknown unknown unknown 3319.56 -999.0 -999. -999.0 -999.0 -999. -999.0 -999.0 -999. -999.0 -999. -999.0 -999.000 -999.0 -999. -999.000 -999.0 0.00 -999.0 -999.0
HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_BACKROW_BOTTOMFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped unknown unknown 3506.987 3440.355 400.423678 -999. -999.00 unknown unknown unknown unknown 3319.56 -999.0 -999. -999.0 -999.0 -999. -999.0 -999.0 -999. -999.0 -999. -999.0 -999.000 -999.0 -999. -999.000 -999.0 0.00 -999.0 -999.0
HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_FRONTROW_MIDDLEFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped unknown unknown 3568.997 3501.186 400.423678 -999. -999.00 unknown unknown unknown unknown 3319.56 -999.0 -999. -999.0 -999.0 -999. -999.0 -999.0 -999. -999.0 -999. -999.0 -999.000 -999.0 -999. -999.000 -999.0 0.00 -999.0 -999.0
HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_FRONTROW_MIDDLEFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped unknown unknown 3587.820 3519.652 400.423678 -999. -999.00 unknown unknown unknown unknown 3319.56 -999.0 -999. -999.0 -999.0 -999. -999.0 -999.0 -999. -999.0 -999. -999.0 -999.000 -999.0 -999. -999.000 -999.0 0.00 -999.0 -999.0
HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_FRONTROW_MIDDLEFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped unknown unknown 3569.618 3501.795 400.423678 -999. -999.00 unknown unknown unknown unknown 3319.56 -999.0 -999. -999.0 -999.0 -999. -999.0 -999.0 -999. -999.0 -999. -999.0 -999.000 -999.0 -999. -999.000 -999.0 0.00 -999.0 -999.0
HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_BACKROW_MIDDLEFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped unknown unknown 3569.012 3501.201 400.423678 -999. -999.00 unknown unknown unknown unknown 3319.56 -999.0 -999. -999.0 -999.0 -999. -999.0 -999.0 -999. -999.0 -999. -999.0 -999.000 -999.0 -999. -999.000 -999.0 0.00 -999.0 -999.0
HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_BACKROW_MIDDLEFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped unknown unknown 3587.813 3519.644 400.423678 -999. -999.00 unknown unknown unknown unknown 3319.56 -999.0 -999. -999.0 -999.0 -999. -999.0 -999.0 -999. -999.0 -999. -999.0 -999.000 -999.0 -999. -999.000 -999.0 0.00 -999.0 -999.0
HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_BACKROW_MIDDLEFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped unknown unknown 3569.663 3501.840 400.423678 -999. -999.00 unknown unknown unknown unknown 3319.56 -999.0 -999. -999.0 -999.0 -999. -999.0 -999.0 -999. -999.0 -999. -999.0 -999.000 -999.0 -999. -999.000 -999.0 0.00 -999.0 -999.0
HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_FRONTROW_TOPFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped unknown unknown 3506.304 3439.684 400.423678 -999. -999.00 unknown unknown unknown unknown 3319.56 -999.0 -999. -999.0 -999.0 -999. -999.0 -999.0 -999. -999.0 -999. -999.0 -999.000 -999.0 -999. -999.000 -999.0 0.00 -999.0 -999.0
HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_FRONTROW_TOPFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped unknown unknown 3518.572 3451.719 400.423678 -999. -999.00 unknown unknown unknown unknown 3319.56 -999.0 -999. -999.0 -999.0 -999. -999.0 -999.0 -999. -999.0 -999. -999.0 -999.000 -999.0 -999. -999.000 -999.0 0.00 -999.0 -999.0
HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_FRONTROW_TOPFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped unknown unknown 3506.750 3440.122 400.423678 -999. -999.00 unknown unknown unknown unknown 3319.56 -999.0 -999. -999.0 -999.0 -999. -999.0 -999.0 -999. -999.0 -999. -999.0 -999.000 -999.0 -999. -999.000 -999.0 0.00 -999.0 -999.0
HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_BACKROW_TOPFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped unknown unknown 3506.309 3439.689 400.423678 -999. -999.00 unknown unknown unknown unknown 3319.56 -999.0 -999. -999.0 -999.0 -999. -999.0 -999.0 -999. -999.0 -999. -999.0 -999.000 -999.0 -999. -999.000 -999.0 0.00 -999.0 -999.0
HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_BACKROW_TOPFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped unknown unknown 3518.541 3451.689 400.423678 -999. -999.00 unknown unknown unknown unknown 3319.56 -999.0 -999. -999.0 -999.0 -999. -999.0 -999.0 -999. -999.0 -999. -999.0 -999.000 -999.0 -999. -999.000 -999.0 0.00 -999.0 -999.0
HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_BACKROW_TOPFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped unknown unknown 3506.774 3440.145 400.423678 -999. -999.00 unknown unknown unknown unknown 3319.56 -999.0 -999. -999.0 -999.0 -999. -999.0 -999.0 -999. -999.0 -999. -999.0 -999.000 -999.0 -999. -999.000 -999.0 0.00 -999.0 -999.0



Table of Contents

Report: Coil Sizing Details

For: Entire Facility

Timestamp: 2021-05-12 10:29:11

Coils

Coil Type Coil Location HVAC Type HVAC Name Zone Name(s) System Sizing Method Concurrence System Sizing Method Capacity System Sizing Method Air Flow Autosized Coil Capacity? Autosized Coil Airflow? Autosized Coil Water Flow? OA Pretreated prior to coil inlet? Coil Final Gross Total Capacity [Btu/h] Coil Final Gross Sensible Capacity [Btu/h] Coil Final Reference Air Volume Flow Rate [ft3/min] Coil Final Reference Plant Fluid Volume Flow Rate [ft3/min] Coil U-value Times Area Value [Btu/h-F] Terminal Unit Reheat Coil Multiplier DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio Moist Air Heat Capacity [Btu/lbm-R] Dry Air Heat Capacity [Btu/lbm-R] Standard Air Density Adjusted for Elevation [lb/ft3] Supply Fan Name for Coil Supply Fan Type for Coil Supply Fan Maximum Air Volume Flow Rate [ft3/min] Supply Fan Maximum Air Mass Flow Rate [lb/s] Plant Name for Coil Plant Fluid Specific Heat Capacity [Btu/lbm-R] Plant Fluid Density [lb/ft3] Plant Maximum Fluid Mass Flow Rate [lb/s] Plant Design Fluid Return Temperature [F] Plant Design Fluid Supply Temperature [F] Plant Design Fluid Temperature Difference [deltaF] Plant Design Capacity [Btu/h] Coil Capacity Percentage of Plant Design Capacity [%] Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Total Ideal Loads Peak Date/Time at Total Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Peak Load Type to Size On Coil Total Capacity at Ideal Loads Peak [Btu/h] Coil Sensible Capacity at Ideal Loads Peak [Btu/h] Coil Off-Rating Capacity Modifier at Ideal Loads Peak [] Coil Air Mass Flow Rate at Ideal Loads Peak [lb/s] Coil Air Volume Flow Rate at Ideal Loads Peak [ft3/min] Coil Entering Air Drybulb at Ideal Loads Peak [F] Coil Entering Air Wetbulb at Ideal Loads Peak [F] Coil Entering Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] Coil Entering Air Enthalpy at Ideal Loads Peak [Btu/lbm-R] Coil Leaving Air Drybulb at Ideal Loads Peak [F] Coil Leaving Air Wetbulb at Ideal Loads Peak [F] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] Coil Leaving Air Enthalpy at Ideal Loads Peak [Btu/lbm-R] Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [lb/s] Coil Entering Plant Fluid Temperature at Ideal Loads Peak [F] Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [F] Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaF] Supply Fan Air Heat Gain at Ideal Loads Peak [Btu/h] Coil and Fan Net Total Capacity at Ideal Loads Peak [Btu/h] Outdoor Air Drybulb at Ideal Loads Peak [F] Outdoor Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [F] Outdoor Air Volume Flow Rate at Ideal Loads Peak [ft3/min] Outdoor Air Flow Percentage at Ideal Loads Peak [%] System Return Air Drybulb at Ideal Loads Peak [F] System Return Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] Zone Air Drybulb at Ideal Loads Peak [F] Zone Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [Btu/h] Zone Latent Heat Gain at Ideal Loads Peak [Btu/h] Coil Total Capacity at Rating Conditions [Btu/h] Coil Sensible Capacity at Rating Conditions [Btu/h] Coil Air Mass Flow Rate at Rating Conditions [lb/s] Coil Entering Air Drybulb at Rating Conditions [F] Coil Entering Air Wetbulb at Rating Conditions [F] Coil Entering Air Humidity Ratio at Rating Conditions [lbWater/lbDryAir] Coil Entering Air Enthalpy at Rating Conditions [Btu/lbm-R] Coil Leaving Air Drybulb at Rating Conditions [F] Coil Leaving Air Wetbulb at Rating Conditions [F] Coil Leaving Air Humidity Ratio at Rating Conditions [lbWater/lbDryAir] Coil Leaving Air Enthalpy at Rating Conditions [Btu/lbm-R]
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR LIVING_UNIT1_FRONTROW_BOTTOMFLOOR Non-Coincident CoolingDesignCapacity N/A Yes Yes unknown No 13051.631 10449.857 489.578731 -999. -999.00 -999.0000 1.15159 1.00000 0.2435 0.2400 0.0618 SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR Fan:OnOff 489.578731 0.50455548   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:20:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 Sensible 14162.40 14162.40 0.9216 0.50455548 489.578731 77.85 58.04 0.00799103 11.0 53.60 49.15 0.00799103 7.7 -999. -999.0 -999.0 -999.0 630.079 13532.32 90.56 0.00569540 58.90 44.99498340 9.1906 75.00 0.00822336 75.00 0.00819875 36.5611 9465.69 0.00 13057.08 9483.00 0.48462936 80.00 67.00 0.01118466 13.2 57.74 56.30 0.00931636 9.1
MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Heating:Electric AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR LIVING_UNIT1_FRONTROW_BOTTOMFLOOR Non-Coincident HeatingDesignCapacity N/A Yes No unknown No 7601.337 7601.337 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0618 SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR Fan:OnOff 489.578731 0.50455548   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 unknown unknown ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 Sensible 7601.34 7601.34 1.0000 0.50455548 489.578731 67.01 52.50 0.00689718 8.8 122.00 70.83 0.00800000 17.0 -999. -999.0 -999.0 -999.0 0.000 7601.34 17.78 0.00234317 17.78 44.99498340 9.1906 72.00 0.00735807 72.00 0.00735807 36.3448 5509.37 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR LIVING_UNIT2_FRONTROW_BOTTOMFLOOR Non-Coincident CoolingDesignCapacity N/A Yes Yes unknown No 5930.134 4747.993 222.444803 -999. -999.00 -999.0000 1.14934 1.00000 0.2435 0.2400 0.0618 SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR Fan:OnOff 222.444803 0.22924963   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:20:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:50:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 Sensible 6266.34 6266.34 0.9463 0.22924963 222.444803 78.59 58.21 0.00793895 11.0 53.60 49.06 0.00793895 7.7 -999. -999.0 -999.0 -999.0 286.282 5980.06 85.70 0.00569125 57.27 44.99498340 20.2275 75.00 0.00850889 75.00 0.00844037 37.6243 4238.39 0.00 5932.61 4308.69 0.22019601 80.00 67.00 0.01118466 13.2 57.74 56.30 0.00931636 9.1
MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Heating:Electric AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR LIVING_UNIT2_FRONTROW_BOTTOMFLOOR Non-Coincident HeatingDesignCapacity N/A Yes No unknown No 5979.683 5979.683 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0618 SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR Fan:OnOff 222.444803 0.22924963   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 unknown unknown ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 Sensible 5979.68 5979.68 1.0000 0.22924963 222.444803 61.03 49.14 0.00629312 7.7 122.00 70.83 0.00800000 17.0 -999. -999.0 -999.0 -999.0 0.000 5979.68 17.78 0.00234317 17.78 44.99498340 20.2275 72.00 0.00729468 72.00 0.00729468 36.0347 3863.73 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR LIVING_UNIT3_FRONTROW_BOTTOMFLOOR Non-Coincident CoolingDesignCapacity N/A Yes Yes unknown No 9421.831 7543.639 353.421600 -999. -999.00 -999.0000 1.16541 1.00000 0.2435 0.2400 0.0618 SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR Fan:OnOff 353.421600 0.36423316   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:30:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:30:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:20:00 Sensible 10056.01 10056.01 0.9369 0.36423316 353.421600 77.97 57.85 0.00783677 10.9 53.60 48.88 0.00783677 7.6 -999. -999.0 -999.0 -999.0 454.847 9601.17 87.16 0.00569249 57.76 44.99498340 12.7312 75.00 0.00814959 75.00 0.00814678 36.3321 6825.05 0.00 9425.76 6845.67 0.34984870 80.00 67.00 0.01118466 13.2 57.74 56.30 0.00931636 9.1
MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Heating:Electric AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR LIVING_UNIT3_FRONTROW_BOTTOMFLOOR Non-Coincident HeatingDesignCapacity N/A Yes No unknown No 7603.873 7603.873 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0618 SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR Fan:OnOff 353.421600 0.36423316   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 unknown unknown ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 Sensible 7603.87 7603.87 1.0000 0.36423316 353.421600 65.10 51.47 0.00671982 8.5 122.00 70.83 0.00800000 17.0 -999. -999.0 -999.0 -999.0 0.000 7603.87 17.78 0.00234317 17.78 44.99498340 12.7312 72.00 0.00735832 72.00 0.00735832 36.3459 5511.95 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR LIVING_UNIT1_BACKROW_BOTTOMFLOOR Non-Coincident CoolingDesignCapacity N/A Yes Yes unknown No 12888.033 10318.872 483.442036 -999. -999.00 -999.0000 1.15448 1.00000 0.2436 0.2400 0.0618 SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR Fan:OnOff 483.442036 0.49823106   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:40:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:40:00 Sensible 13954.06 13949.00 0.9236 0.49823106 483.442036 77.83 58.05 0.00800256 11.0 53.60 49.17 0.00800000 7.7 -999. -999.0 -999.0 -999.0 622.181 13331.88 90.16 0.00569506 58.76 44.99498340 9.3072 75.00 0.00823936 75.00 0.00822440 36.6742 9337.44 0.00 12893.41 9364.13 0.47855470 80.00 67.00 0.01118466 13.2 57.74 56.30 0.00931636 9.1
MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Heating:Electric AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR LIVING_UNIT1_BACKROW_BOTTOMFLOOR Non-Coincident HeatingDesignCapacity N/A Yes No unknown No 7604.306 7604.306 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0618 SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR Fan:OnOff 483.442036 0.49823106   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 unknown unknown ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 Sensible 7604.31 7604.31 1.0000 0.49823106 483.442036 66.95 52.46 0.00689158 8.8 122.00 70.83 0.00800000 17.0 -999. -999.0 -999.0 -999.0 0.000 7604.31 17.78 0.00234317 17.78 44.99498340 9.3072 72.00 0.00735836 72.00 0.00735836 36.3462 5512.39 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR LIVING_UNIT2_BACKROW_BOTTOMFLOOR Non-Coincident CoolingDesignCapacity N/A Yes Yes unknown No 6027.836 4826.219 226.109696 -999. -999.00 -999.0000 1.15087 1.00000 0.2435 0.2400 0.0618 SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR Fan:OnOff 226.109696 0.23302664   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:40:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:50:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 Sensible 6369.68 6369.68 0.9463 0.23302664 226.109696 78.55 58.20 0.00794556 11.0 53.60 49.07 0.00794556 7.7 -999. -999.0 -999.0 -999.0 290.999 6078.68 85.70 0.00569125 57.27 44.99498340 19.8996 75.00 0.00850560 75.00 0.00847906 37.7945 4347.48 0.00 6030.35 4379.68 0.22382385 80.00 67.00 0.01118466 13.2 57.74 56.30 0.00931636 9.1
MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Heating:Electric AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR LIVING_UNIT2_BACKROW_BOTTOMFLOOR Non-Coincident HeatingDesignCapacity N/A Yes No unknown No 5980.093 5980.093 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0618 SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR Fan:OnOff 226.109696 0.23302664   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 unknown unknown ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 Sensible 5980.09 5980.09 1.0000 0.23302664 226.109696 61.21 49.24 0.00630940 7.7 122.00 70.83 0.00800000 17.0 -999. -999.0 -999.0 -999.0 0.000 5980.09 17.78 0.00234317 17.78 44.99498340 19.8996 72.00 0.00729474 72.00 0.00729474 36.0350 3864.14 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR LIVING_UNIT3_BACKROW_BOTTOMFLOOR Non-Coincident CoolingDesignCapacity N/A Yes Yes unknown No 9258.151 7412.588 347.281814 -999. -999.00 -999.0000 1.18652 1.00000 0.2435 0.2400 0.0618 SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR Fan:OnOff 347.281814 0.35790555   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:10:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:10:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 09:50:00 Sensible 9789.73 9789.73 0.9457 0.35790555 347.281814 77.75 57.79 0.00784231 10.9 53.60 48.89 0.00784231 7.6 -999. -999.0 -999.0 -999.0 446.945 9342.78 85.26 0.00569088 57.12 44.99498340 12.9563 75.00 0.00816255 75.00 0.00815395 36.3636 6698.42 0.00 9262.01 6726.75 0.34377098 80.00 67.00 0.01118466 13.2 57.74 56.30 0.00931636 9.1
MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Heating:Electric AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR LIVING_UNIT3_BACKROW_BOTTOMFLOOR Non-Coincident HeatingDesignCapacity N/A Yes No unknown No 7601.756 7601.756 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0618 SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR Fan:OnOff 347.281814 0.35790555   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 unknown unknown ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 Sensible 7601.76 7601.76 1.0000 0.35790555 347.281814 64.97 51.41 0.00670836 8.5 122.00 70.83 0.00800000 17.0 -999. -999.0 -999.0 -999.0 0.000 7601.76 17.78 0.00234317 17.78 44.99498340 12.9563 72.00 0.00735811 72.00 0.00735811 36.3450 5509.80 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR LIVING_UNIT1_FRONTROW_MIDDLEFLOOR Non-Coincident CoolingDesignCapacity N/A Yes Yes unknown No 12589.377 10079.751 472.239150 -999. -999.00 -999.0000 1.14412 1.00000 0.2436 0.2400 0.0618 SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR Fan:OnOff 472.239150 0.48668547   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:40:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:40:00 Sensible 13623.78 13532.92 0.9241 0.48668547 472.239150 77.87 58.12 0.00804751 11.0 53.60 49.17 0.00800000 7.7 -999. -999.0 -999.0 -999.0 607.763 13016.02 90.16 0.00569506 58.76 44.99498340 9.5280 75.00 0.00829526 75.00 0.00827973 36.9179 9127.51 0.00 12594.63 9147.13 0.46746507 80.00 67.00 0.01118466 13.2 57.74 56.30 0.00931636 9.1
MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Heating:Electric AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR LIVING_UNIT1_FRONTROW_MIDDLEFLOOR Non-Coincident HeatingDesignCapacity N/A Yes No unknown No 5784.235 5784.235 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0618 SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR Fan:OnOff 472.239150 0.48668547   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 unknown unknown ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 Sensible 5784.23 5784.23 1.0000 0.48668547 472.239150 66.83 53.19 0.00736521 9.1 122.00 70.83 0.00800000 17.0 -999. -999.0 -999.0 -999.0 0.000 5784.23 17.78 0.00234317 17.78 44.99498340 9.5280 72.00 0.00789411 72.00 0.00789411 38.9565 3665.32 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR LIVING_UNIT2_FRONTROW_MIDDLEFLOOR Non-Coincident CoolingDesignCapacity N/A Yes Yes unknown No 5743.384 4598.470 215.439629 -999. -999.00 -999.0000 1.14173 1.00000 0.2436 0.2400 0.0618 SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR Fan:OnOff 215.439629 0.22203017   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:50:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 Sensible 6062.09 6038.15 0.9474 0.22203017 215.439629 78.66 58.36 0.00802874 11.1 53.60 49.17 0.00800000 7.7 -999. -999.0 -999.0 -999.0 277.267 5784.82 85.70 0.00569125 57.27 44.99498340 20.8852 75.00 0.00864580 75.00 0.00863347 38.4736 4143.54 0.00 5745.78 4173.00 0.21326165 80.00 67.00 0.01118466 13.2 57.74 56.30 0.00931636 9.1
MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Heating:Electric AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR LIVING_UNIT2_FRONTROW_MIDDLEFLOOR Non-Coincident HeatingDesignCapacity N/A Yes No unknown No 4175.883 4175.883 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0618 SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR Fan:OnOff 215.439629 0.22203017   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 unknown unknown ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 Sensible 4175.88 4175.88 1.0000 0.22203017 215.439629 60.68 50.26 0.00701565 8.1 122.00 70.83 0.00800000 17.0 -999. -999.0 -999.0 -999.0 0.000 4175.88 17.78 0.00234317 17.78 44.99498340 20.8852 72.00 0.00824912 72.00 0.00824912 40.6846 2033.17 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR LIVING_UNIT3_FRONTROW_MIDDLEFLOOR Non-Coincident CoolingDesignCapacity N/A Yes Yes unknown No 9621.593 7703.579 360.914858 -999. -999.00 -999.0000 1.16056 1.00000 0.2435 0.2400 0.0618 SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR Fan:OnOff 360.914858 0.37195564   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:40:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:40:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:30:00 Sensible 10294.45 10294.45 0.9346 0.37195564 360.914858 78.02 57.95 0.00789696 10.9 53.60 48.99 0.00789696 7.6 -999. -999.0 -999.0 -999.0 464.491 9829.96 87.77 0.00569301 57.97 44.99498340 12.4669 75.00 0.00821086 75.00 0.00821002 36.6106 6968.20 0.00 9625.61 6990.82 0.35726621 80.00 67.00 0.01118466 13.2 57.74 56.30 0.00931636 9.1
MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Heating:Electric AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR LIVING_UNIT3_FRONTROW_MIDDLEFLOOR Non-Coincident HeatingDesignCapacity N/A Yes No unknown No 5786.508 5786.508 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0618 SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR Fan:OnOff 360.914858 0.37195564   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 unknown unknown ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 Sensible 5786.51 5786.51 1.0000 0.37195564 360.914858 65.24 52.33 0.00720210 8.8 122.00 70.83 0.00800000 17.0 -999. -999.0 -999.0 -999.0 0.000 5786.51 17.78 0.00234317 17.78 44.99498340 12.4669 72.00 0.00789414 72.00 0.00789414 38.9566 3667.63 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR LIVING_UNIT1_BACKROW_MIDDLEFLOOR Non-Coincident CoolingDesignCapacity N/A Yes Yes unknown No 12433.559 9954.994 466.394279 -999. -999.00 -999.0000 1.14600 1.00000 0.2436 0.2400 0.0618 SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR Fan:OnOff 466.394279 0.48066179   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:40:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:50:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:50:00 Sensible 13426.08 13322.64 0.9261 0.48066179 466.394279 77.85 58.13 0.00805491 11.0 53.60 49.17 0.00800000 7.7 -999. -999.0 -999.0 -999.0 600.241 12825.84 89.75 0.00569471 58.63 44.99498340 9.6474 75.00 0.00830692 75.00 0.00829743 36.9958 9003.98 0.00 12438.75 9033.92 0.46167929 80.00 67.00 0.01118466 13.2 57.74 56.30 0.00931636 9.1
MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Heating:Electric AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR LIVING_UNIT1_BACKROW_MIDDLEFLOOR Non-Coincident HeatingDesignCapacity N/A Yes No unknown No 5786.936 5786.936 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0618 SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR Fan:OnOff 466.394279 0.48066179   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 unknown unknown ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 Sensible 5786.94 5786.94 1.0000 0.48066179 466.394279 66.77 53.16 0.00735862 9.1 122.00 70.83 0.00800000 17.0 -999. -999.0 -999.0 -999.0 0.000 5786.94 17.78 0.00234317 17.78 44.99498340 9.6474 72.00 0.00789414 72.00 0.00789414 38.9566 3668.06 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR LIVING_UNIT2_BACKROW_MIDDLEFLOOR Non-Coincident CoolingDesignCapacity N/A Yes Yes unknown No 5796.343 4640.873 217.426192 -999. -999.00 -999.0000 1.14140 1.00000 0.2436 0.2400 0.0618 SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR Fan:OnOff 217.426192 0.22407750   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:50:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 Sensible 6117.89 6088.60 0.9474 0.22407750 217.426192 78.64 58.36 0.00803486 11.1 53.60 49.17 0.00800000 7.7 -999. -999.0 -999.0 -999.0 279.823 5838.07 85.70 0.00569125 57.27 44.99498340 20.6944 75.00 0.00864641 75.00 0.00863525 38.4814 4182.11 0.00 5798.76 4211.48 0.21522813 80.00 67.00 0.01118466 13.2 57.74 56.30 0.00931636 9.1
MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Heating:Electric AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR LIVING_UNIT2_BACKROW_MIDDLEFLOOR Non-Coincident HeatingDesignCapacity N/A Yes No unknown No 4176.229 4176.229 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0618 SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR Fan:OnOff 217.426192 0.22407750   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 unknown unknown ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 Sensible 4176.23 4176.23 1.0000 0.22407750 217.426192 60.78 50.32 0.00702686 8.1 122.00 70.83 0.00800000 17.0 -999. -999.0 -999.0 -999.0 0.000 4176.23 17.78 0.00234317 17.78 44.99498340 20.6944 72.00 0.00824904 72.00 0.00824904 40.6842 2033.52 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR LIVING_UNIT3_BACKROW_MIDDLEFLOOR Non-Coincident CoolingDesignCapacity N/A Yes Yes unknown No 9441.585 7559.455 354.162572 -999. -999.00 -999.0000 1.17324 1.00000 0.2435 0.2400 0.0618 SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR Fan:OnOff 354.162572 0.36499680   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:20:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:20:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:10:00 Sensible 10041.40 10041.40 0.9403 0.36499680 354.162572 77.89 57.91 0.00789756 10.9 53.60 48.99 0.00789756 7.6 -999. -999.0 -999.0 -999.0 455.801 9585.60 86.55 0.00569198 57.56 44.99498340 12.7046 75.00 0.00821855 75.00 0.00821539 36.6342 6839.02 0.00 9445.52 6860.03 0.35058218 80.00 67.00 0.01118466 13.2 57.74 56.30 0.00931636 9.1
MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Heating:Electric AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR LIVING_UNIT3_BACKROW_MIDDLEFLOOR Non-Coincident HeatingDesignCapacity N/A Yes No unknown No 5784.587 5784.587 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0618 SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR Fan:OnOff 354.162572 0.36499680   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 unknown unknown ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 Sensible 5784.59 5784.59 1.0000 0.36499680 354.162572 65.11 52.26 0.00718889 8.8 122.00 70.83 0.00800000 17.0 -999. -999.0 -999.0 -999.0 0.000 5784.59 17.78 0.00234317 17.78 44.99498340 12.7046 72.00 0.00789411 72.00 0.00789411 38.9565 3665.68 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR LIVING_UNIT1_FRONTROW_TOPFLOOR Non-Coincident CoolingDesignCapacity N/A Yes Yes unknown No 13193.091 10563.118 494.885046 -999. -999.00 -999.0000 1.15521 1.00000 0.2436 0.2400 0.0618 SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR Fan:OnOff 494.885046 0.51002412   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:40:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:40:00 Sensible 14284.90 14272.90 0.9236 0.51002412 494.885046 77.80 58.04 0.00800594 11.0 53.60 49.17 0.00800000 7.7 -999. -999.0 -999.0 -999.0 636.908 13648.00 90.16 0.00569506 58.76 44.99498340 9.0920 75.00 0.00823706 75.00 0.00822250 36.6658 9557.08 0.00 13198.60 9585.78 0.48988203 80.00 67.00 0.01118466 13.2 57.74 56.30 0.00931636 9.1
MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Heating:Electric AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR LIVING_UNIT1_FRONTROW_TOPFLOOR Non-Coincident HeatingDesignCapacity N/A Yes No unknown No 7268.085 7268.085 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0618 SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR Fan:OnOff 494.885046 0.51002412   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 unknown unknown ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 Sensible 7268.08 7268.08 1.0000 0.51002412 494.885046 67.07 52.47 0.00687113 8.8 122.00 70.83 0.00800000 17.0 -999. -999.0 -999.0 -999.0 0.000 7268.08 17.78 0.00234317 17.78 44.99498340 9.0920 72.00 0.00732399 72.00 0.00732399 36.1784 5171.19 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR LIVING_UNIT2_FRONTROW_TOPFLOOR Non-Coincident CoolingDesignCapacity N/A Yes Yes unknown No 6463.559 5175.083 242.454085 -999. -999.00 -999.0000 1.15706 1.00000 0.2435 0.2400 0.0618 SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR Fan:OnOff 242.454085 0.24987102   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 Sensible 6831.05 6831.05 0.9462 0.24987102 242.454085 78.41 58.19 0.00796543 11.0 53.60 49.11 0.00796543 7.7 -999. -999.0 -999.0 -999.0 312.034 6519.01 85.70 0.00569125 57.27 44.99498340 18.5581 75.00 0.00848365 75.00 0.00848365 37.8147 4689.03 0.00 6466.26 4696.26 0.24000301 80.00 67.00 0.01118466 13.2 57.74 56.30 0.00931636 9.1
MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Heating:Electric AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR LIVING_UNIT2_FRONTROW_TOPFLOOR Non-Coincident HeatingDesignCapacity N/A Yes No unknown No 5646.907 5646.907 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0618 SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR Fan:OnOff 242.454085 0.24987102   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 unknown unknown ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 Sensible 5646.91 5646.91 1.0000 0.24987102 242.454085 61.94 49.57 0.00633447 7.8 122.00 70.83 0.00800000 17.0 -999. -999.0 -999.0 -999.0 0.000 5646.91 17.78 0.00234317 17.78 44.99498340 18.5581 72.00 0.00724397 72.00 0.00724397 35.7870 3526.03 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR LIVING_UNIT3_FRONTROW_TOPFLOOR Non-Coincident CoolingDesignCapacity N/A Yes Yes unknown No 9800.952 7847.184 367.642771 -999. -999.00 -999.0000 1.16122 1.00000 0.2435 0.2400 0.0618 SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR Fan:OnOff 367.642771 0.37888937   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:40:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:40:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:30:00 Sensible 10492.40 10492.40 0.9341 0.37888937 367.642771 77.99 57.87 0.00784463 10.9 53.60 48.89 0.00784463 7.6 -999. -999.0 -999.0 -999.0 473.149 10019.25 87.77 0.00569301 57.97 44.99498340 12.2388 75.00 0.00814468 75.00 0.00814373 36.3187 7099.68 0.00 9805.04 7121.13 0.36392610 80.00 67.00 0.01118466 13.2 57.74 56.30 0.00931636 9.1
MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Heating:Electric AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR LIVING_UNIT3_FRONTROW_TOPFLOOR Non-Coincident HeatingDesignCapacity N/A Yes No unknown No 7269.713 7269.713 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0618 SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR Fan:OnOff 367.642771 0.37888937   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 unknown unknown ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 Sensible 7269.71 7269.71 1.0000 0.37888937 367.642771 65.36 51.56 0.00671455 8.5 122.00 70.83 0.00800000 17.0 -999. -999.0 -999.0 -999.0 0.000 7269.71 17.78 0.00234317 17.78 44.99498340 12.2388 72.00 0.00732416 72.00 0.00732416 36.1792 5172.85 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR LIVING_UNIT1_BACKROW_TOPFLOOR Non-Coincident CoolingDesignCapacity N/A Yes Yes unknown No 13224.635 10588.374 496.068276 -999. -999.00 -999.0000 1.15777 1.00000 0.2436 0.2400 0.0618 SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR Fan:OnOff 496.068276 0.51124355   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:50:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:50:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:50:00 Sensible 14288.69 14260.36 0.9255 0.51124355 496.068276 77.76 58.04 0.00801401 11.0 53.60 49.17 0.00800000 7.7 -999. -999.0 -999.0 -999.0 638.431 13650.25 89.75 0.00569471 58.63 44.99498340 9.0703 75.00 0.00824536 75.00 0.00824536 36.7665 9593.93 0.00 13230.15 9608.70 0.49105330 80.00 67.00 0.01118466 13.2 57.74 56.30 0.00931636 9.1
MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Heating:Electric AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR LIVING_UNIT1_BACKROW_TOPFLOOR Non-Coincident HeatingDesignCapacity N/A Yes No unknown No 7271.551 7271.551 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0618 SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR Fan:OnOff 496.068276 0.51124355   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 unknown unknown ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 Sensible 7271.55 7271.55 1.0000 0.51124355 496.068276 67.08 52.48 0.00687255 8.8 122.00 70.83 0.00800000 17.0 -999. -999.0 -999.0 -999.0 0.000 7271.55 17.78 0.00234317 17.78 44.99498340 9.0703 72.00 0.00732435 72.00 0.00732435 36.1801 5174.71 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR LIVING_UNIT2_BACKROW_TOPFLOOR Non-Coincident CoolingDesignCapacity N/A Yes Yes unknown No 6660.109 5332.451 249.826843 -999. -999.00 -999.0000 1.15962 1.00000 0.2435 0.2400 0.0618 SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR Fan:OnOff 249.826843 0.25746932   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 Sensible 7039.11 7039.11 0.9462 0.25746932 249.826843 78.35 58.18 0.00797428 11.0 53.60 49.12 0.00797428 7.7 -999. -999.0 -999.0 -999.0 321.523 6717.59 85.70 0.00569125 57.27 44.99498340 18.0105 75.00 0.00847579 75.00 0.00847579 37.7802 4831.61 0.00 6662.89 4839.07 0.24730123 80.00 67.00 0.01118466 13.2 57.74 56.30 0.00931636 9.1
MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Heating:Electric AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR LIVING_UNIT2_BACKROW_TOPFLOOR Non-Coincident HeatingDesignCapacity N/A Yes No unknown No 5648.648 5648.648 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0618 SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR Fan:OnOff 249.826843 0.25746932   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 unknown unknown ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 Sensible 5648.65 5648.65 1.0000 0.25746932 249.826843 62.23 49.74 0.00636154 7.9 122.00 70.83 0.00800000 17.0 -999. -999.0 -999.0 -999.0 0.000 5648.65 17.78 0.00234317 17.78 44.99498340 18.0105 72.00 0.00724425 72.00 0.00724425 35.7884 3527.80 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR LIVING_UNIT3_BACKROW_TOPFLOOR Non-Coincident CoolingDesignCapacity N/A Yes Yes unknown No 9618.829 7701.366 360.811155 -999. -999.00 -999.0000 1.17381 1.00000 0.2435 0.2400 0.0618 SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR Fan:OnOff 360.811155 0.37184877   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:20:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:20:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:10:00 Sensible 10235.89 10235.89 0.9397 0.37184877 360.811155 77.87 57.83 0.00784472 10.9 53.60 48.89 0.00784472 7.6 -999. -999.0 -999.0 -999.0 464.357 9771.53 86.55 0.00569198 57.56 44.99498340 12.4705 75.00 0.00815143 75.00 0.00814815 36.3381 6970.72 0.00 9622.84 6988.81 0.35716355 80.00 67.00 0.01118466 13.2 57.74 56.30 0.00931636 9.1
MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Heating:Electric AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR LIVING_UNIT3_BACKROW_TOPFLOOR Non-Coincident HeatingDesignCapacity N/A Yes No unknown No 7269.841 7269.841 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0618 SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR Fan:OnOff 360.811155 0.37184877   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 unknown unknown ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 Sensible 7269.84 7269.84 1.0000 0.37184877 360.811155 65.24 51.50 0.00670302 8.5 122.00 70.83 0.00800000 17.0 -999. -999.0 -999.0 -999.0 0.000 7269.84 17.78 0.00234317 17.78 44.99498340 12.4705 72.00 0.00732417 72.00 0.00732417 36.1793 5172.98 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_FRONTROW_BOTTOMFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped unknown unknown unknown N/A N/A N/A N/A No No unknown No 3506.446 3439.823 400.423678 -999. -999.00 -999.0000 1.00000 1.00000 0.2400 0.2400 0.0618 HEAT PUMP WATER HEATER FAN_UNIT1_FRONTROW_BOTTOMFLOOR Fan:OnOff 160.010573 0.16490547   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. unknown unknown unknown unknown unknown unknown Sensible 3319.56 -999.0 1.0000 -999. -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999. -999. -999.0 -999.0 -999.0 0.000 3319.56 -999.0 -999. -999.0 -999. -999.000 -999.0 -999. -999.0 -999. -999.000 -999.0 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_FRONTROW_BOTTOMFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped unknown unknown unknown N/A N/A N/A N/A No No unknown No 3518.905 3452.046 400.423678 -999. -999.00 -999.0000 1.00000 1.00000 0.2400 0.2400 0.0618 HEAT PUMP WATER HEATER FAN_UNIT2_FRONTROW_BOTTOMFLOOR Fan:OnOff 160.010573 0.16490547   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. unknown unknown unknown unknown unknown unknown Sensible 3319.56 -999.0 1.0000 -999. -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999. -999. -999.0 -999.0 -999.0 0.000 3319.56 -999.0 -999. -999.0 -999. -999.000 -999.0 -999. -999.0 -999. -999.000 -999.0 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_FRONTROW_BOTTOMFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped unknown unknown unknown N/A N/A N/A N/A No No unknown No 3506.968 3440.335 400.423678 -999. -999.00 -999.0000 1.00000 1.00000 0.2400 0.2400 0.0618 HEAT PUMP WATER HEATER FAN_UNIT3_FRONTROW_BOTTOMFLOOR Fan:OnOff 160.010573 0.16490547   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. unknown unknown unknown unknown unknown unknown Sensible 3319.56 -999.0 1.0000 -999. -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999. -999. -999.0 -999.0 -999.0 0.000 3319.56 -999.0 -999. -999.0 -999. -999.000 -999.0 -999. -999.0 -999. -999.000 -999.0 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_BACKROW_BOTTOMFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped unknown unknown unknown N/A N/A N/A N/A No No unknown No 3506.489 3439.866 400.423678 -999. -999.00 -999.0000 1.00000 1.00000 0.2400 0.2400 0.0618 HEAT PUMP WATER HEATER FAN_UNIT1_BACKROW_BOTTOMFLOOR Fan:OnOff 160.010573 0.16490547   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. unknown unknown unknown unknown unknown unknown Sensible 3319.56 -999.0 1.0000 -999. -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999. -999. -999.0 -999.0 -999.0 0.000 3319.56 -999.0 -999. -999.0 -999. -999.000 -999.0 -999. -999.0 -999. -999.000 -999.0 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_BACKROW_BOTTOMFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped unknown unknown unknown N/A N/A N/A N/A No No unknown No 3518.888 3452.029 400.423678 -999. -999.00 -999.0000 1.00000 1.00000 0.2400 0.2400 0.0618 HEAT PUMP WATER HEATER FAN_UNIT2_BACKROW_BOTTOMFLOOR Fan:OnOff 160.010573 0.16490547   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. unknown unknown unknown unknown unknown unknown Sensible 3319.56 -999.0 1.0000 -999. -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999. -999. -999.0 -999.0 -999.0 0.000 3319.56 -999.0 -999. -999.0 -999. -999.000 -999.0 -999. -999.0 -999. -999.000 -999.0 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_BACKROW_BOTTOMFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped unknown unknown unknown N/A N/A N/A N/A No No unknown No 3506.987 3440.355 400.423678 -999. -999.00 -999.0000 1.00000 1.00000 0.2400 0.2400 0.0618 HEAT PUMP WATER HEATER FAN_UNIT3_BACKROW_BOTTOMFLOOR Fan:OnOff 160.010573 0.16490547   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. unknown unknown unknown unknown unknown unknown Sensible 3319.56 -999.0 1.0000 -999. -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999. -999. -999.0 -999.0 -999.0 0.000 3319.56 -999.0 -999. -999.0 -999. -999.000 -999.0 -999. -999.0 -999. -999.000 -999.0 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_FRONTROW_MIDDLEFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped unknown unknown unknown N/A N/A N/A N/A No No unknown No 3568.997 3501.186 400.423678 -999. -999.00 -999.0000 1.00000 1.00000 0.2400 0.2400 0.0618 HEAT PUMP WATER HEATER FAN_UNIT1_FRONTROW_MIDDLEFLOOR Fan:OnOff 160.010573 0.16490547   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. unknown unknown unknown unknown unknown unknown Sensible 3319.56 -999.0 1.0000 -999. -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999. -999. -999.0 -999.0 -999.0 0.000 3319.56 -999.0 -999. -999.0 -999. -999.000 -999.0 -999. -999.0 -999. -999.000 -999.0 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_FRONTROW_MIDDLEFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped unknown unknown unknown N/A N/A N/A N/A No No unknown No 3587.820 3519.652 400.423678 -999. -999.00 -999.0000 1.00000 1.00000 0.2400 0.2400 0.0618 HEAT PUMP WATER HEATER FAN_UNIT2_FRONTROW_MIDDLEFLOOR Fan:OnOff 160.010573 0.16490547   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. unknown unknown unknown unknown unknown unknown Sensible 3319.56 -999.0 1.0000 -999. -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999. -999. -999.0 -999.0 -999.0 0.000 3319.56 -999.0 -999. -999.0 -999. -999.000 -999.0 -999. -999.0 -999. -999.000 -999.0 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_FRONTROW_MIDDLEFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped unknown unknown unknown N/A N/A N/A N/A No No unknown No 3569.618 3501.795 400.423678 -999. -999.00 -999.0000 1.00000 1.00000 0.2400 0.2400 0.0618 HEAT PUMP WATER HEATER FAN_UNIT3_FRONTROW_MIDDLEFLOOR Fan:OnOff 160.010573 0.16490547   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. unknown unknown unknown unknown unknown unknown Sensible 3319.56 -999.0 1.0000 -999. -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999. -999. -999.0 -999.0 -999.0 0.000 3319.56 -999.0 -999. -999.0 -999. -999.000 -999.0 -999. -999.0 -999. -999.000 -999.0 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_BACKROW_MIDDLEFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped unknown unknown unknown N/A N/A N/A N/A No No unknown No 3569.012 3501.201 400.423678 -999. -999.00 -999.0000 1.00000 1.00000 0.2400 0.2400 0.0618 HEAT PUMP WATER HEATER FAN_UNIT1_BACKROW_MIDDLEFLOOR Fan:OnOff 160.010573 0.16490547   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. unknown unknown unknown unknown unknown unknown Sensible 3319.56 -999.0 1.0000 -999. -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999. -999. -999.0 -999.0 -999.0 0.000 3319.56 -999.0 -999. -999.0 -999. -999.000 -999.0 -999. -999.0 -999. -999.000 -999.0 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_BACKROW_MIDDLEFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped unknown unknown unknown N/A N/A N/A N/A No No unknown No 3587.813 3519.644 400.423678 -999. -999.00 -999.0000 1.00000 1.00000 0.2400 0.2400 0.0618 HEAT PUMP WATER HEATER FAN_UNIT2_BACKROW_MIDDLEFLOOR Fan:OnOff 160.010573 0.16490547   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. unknown unknown unknown unknown unknown unknown Sensible 3319.56 -999.0 1.0000 -999. -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999. -999. -999.0 -999.0 -999.0 0.000 3319.56 -999.0 -999. -999.0 -999. -999.000 -999.0 -999. -999.0 -999. -999.000 -999.0 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_BACKROW_MIDDLEFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped unknown unknown unknown N/A N/A N/A N/A No No unknown No 3569.663 3501.840 400.423678 -999. -999.00 -999.0000 1.00000 1.00000 0.2400 0.2400 0.0618 HEAT PUMP WATER HEATER FAN_UNIT3_BACKROW_MIDDLEFLOOR Fan:OnOff 160.010573 0.16490547   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. unknown unknown unknown unknown unknown unknown Sensible 3319.56 -999.0 1.0000 -999. -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999. -999. -999.0 -999.0 -999.0 0.000 3319.56 -999.0 -999. -999.0 -999. -999.000 -999.0 -999. -999.0 -999. -999.000 -999.0 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_FRONTROW_TOPFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped unknown unknown unknown N/A N/A N/A N/A No No unknown No 3506.304 3439.684 400.423678 -999. -999.00 -999.0000 1.00000 1.00000 0.2400 0.2400 0.0618 HEAT PUMP WATER HEATER FAN_UNIT1_FRONTROW_TOPFLOOR Fan:OnOff 160.010573 0.16490547   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. unknown unknown unknown unknown unknown unknown Sensible 3319.56 -999.0 1.0000 -999. -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999. -999. -999.0 -999.0 -999.0 0.000 3319.56 -999.0 -999. -999.0 -999. -999.000 -999.0 -999. -999.0 -999. -999.000 -999.0 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_FRONTROW_TOPFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped unknown unknown unknown N/A N/A N/A N/A No No unknown No 3518.572 3451.719 400.423678 -999. -999.00 -999.0000 1.00000 1.00000 0.2400 0.2400 0.0618 HEAT PUMP WATER HEATER FAN_UNIT2_FRONTROW_TOPFLOOR Fan:OnOff 160.010573 0.16490547   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. unknown unknown unknown unknown unknown unknown Sensible 3319.56 -999.0 1.0000 -999. -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999. -999. -999.0 -999.0 -999.0 0.000 3319.56 -999.0 -999. -999.0 -999. -999.000 -999.0 -999. -999.0 -999. -999.000 -999.0 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_FRONTROW_TOPFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped unknown unknown unknown N/A N/A N/A N/A No No unknown No 3506.750 3440.122 400.423678 -999. -999.00 -999.0000 1.00000 1.00000 0.2400 0.2400 0.0618 HEAT PUMP WATER HEATER FAN_UNIT3_FRONTROW_TOPFLOOR Fan:OnOff 160.010573 0.16490547   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. unknown unknown unknown unknown unknown unknown Sensible 3319.56 -999.0 1.0000 -999. -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999. -999. -999.0 -999.0 -999.0 0.000 3319.56 -999.0 -999. -999.0 -999. -999.000 -999.0 -999. -999.0 -999. -999.000 -999.0 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_BACKROW_TOPFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped unknown unknown unknown N/A N/A N/A N/A No No unknown No 3506.309 3439.689 400.423678 -999. -999.00 -999.0000 1.00000 1.00000 0.2400 0.2400 0.0618 HEAT PUMP WATER HEATER FAN_UNIT1_BACKROW_TOPFLOOR Fan:OnOff 160.010573 0.16490547   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. unknown unknown unknown unknown unknown unknown Sensible 3319.56 -999.0 1.0000 -999. -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999. -999. -999.0 -999.0 -999.0 0.000 3319.56 -999.0 -999. -999.0 -999. -999.000 -999.0 -999. -999.0 -999. -999.000 -999.0 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_BACKROW_TOPFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped unknown unknown unknown N/A N/A N/A N/A No No unknown No 3518.541 3451.689 400.423678 -999. -999.00 -999.0000 1.00000 1.00000 0.2400 0.2400 0.0618 HEAT PUMP WATER HEATER FAN_UNIT2_BACKROW_TOPFLOOR Fan:OnOff 160.010573 0.16490547   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. unknown unknown unknown unknown unknown unknown Sensible 3319.56 -999.0 1.0000 -999. -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999. -999. -999.0 -999.0 -999.0 0.000 3319.56 -999.0 -999. -999.0 -999. -999.000 -999.0 -999. -999.0 -999. -999.000 -999.0 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_BACKROW_TOPFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped unknown unknown unknown N/A N/A N/A N/A No No unknown No 3506.774 3440.145 400.423678 -999. -999.00 -999.0000 1.00000 1.00000 0.2400 0.2400 0.0618 HEAT PUMP WATER HEATER FAN_UNIT3_BACKROW_TOPFLOOR Fan:OnOff 160.010573 0.16490547   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. unknown unknown unknown unknown unknown unknown Sensible 3319.56 -999.0 1.0000 -999. -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999. -999. -999.0 -999.0 -999.0 0.000 3319.56 -999.0 -999. -999.0 -999. -999.000 -999.0 -999. -999.0 -999. -999.000 -999.0 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2021-05-12 10:29:11

Economizer

High Limit Shutoff Control Minimum Outdoor Air [ft3/min] Maximum Outdoor Air [ft3/min] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [F] Outdoor Air Enthalpy Limit [F]
None              


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [ft3/min-person] Outdoor Air Per Area [ft3/min-ft2] Outdoor Air Per Zone [ft3/min] Outdoor Air ACH [ACH] Outdoor Air Method Outdoor Air Schedule Name Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule Name
None                    


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1949.83 5255.50 137.83
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1470.50 5780.00 115.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 2054.50 5088.50 114.83
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1771.67 5810.83 170.83
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1155.17 6161.17 136.33
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1897.00 5635.17 143.67
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 2177.67 4725.83 53.33
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1672.83 5135.50 37.83
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 2288.83 4515.33 44.33
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1946.50 5376.17 60.17
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1321.33 5664.17 43.83
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 2125.67 5243.17 48.17
LIVING_UNIT3_BACKROW_TOPFLOOR 2249.67 5259.17 55.33
LIVING_UNIT3_FRONTROW_TOPFLOOR 2343.33 4803.00 53.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 2207.33 4935.17 62.17
LIVING_UNIT2_BACKROW_TOPFLOOR 1548.83 5630.17 48.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 1794.50 5335.33 41.33
LIVING_UNIT1_BACKROW_TOPFLOOR 2061.17 5388.33 73.83
CRAWLSPACE 0.00 0.00 0.00
BREEZEWAY 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00
Facility 2833.83 6473.17 218.00
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 25.00 4.33 25.00 4.33
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 74.83 5.50 74.83 5.50
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 30.33 0.00 30.33 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 33.83 4.50 33.83 4.50
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 114.67 2.67 114.67 2.67
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 28.67 0.33 28.67 0.33
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 51.33 2.33 51.33 2.33
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 245.33 1.83 245.33 1.83
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 49.67 0.00 49.67 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 78.00 2.17 78.00 2.17
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 396.33 0.33 396.33 0.33
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 84.00 0.00 84.00 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 25.50 0.00 25.50 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 25.17 0.00 25.17 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 21.83 2.83 21.83 2.83
LIVING_UNIT2_BACKROW_TOPFLOOR 105.33 1.00 105.33 1.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 67.33 2.00 67.33 2.00
LIVING_UNIT1_BACKROW_TOPFLOOR 29.83 2.67 29.83 2.67
CRAWLSPACE 0.00 0.00 0.00 0.00
BREEZEWAY 0.00 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00 0.00
Facility 954.83 9.00 954.83 9.00
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2021-05-12 10:29:11

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [ft3] Mechanical Ventilation [ACH] Infiltration [ACH] AFN Infiltration [ACH] Simple Ventilation [ACH]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.268 0.117 0.000 0.000
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.268 0.103 0.000 0.000
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.268 0.118 0.000 0.000
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.267 0.117 0.000 0.000
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.267 0.103 0.000 0.000
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.267 0.117 0.000 0.000
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.268 0.052 0.000 0.000
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.268 0.038 0.000 0.000
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.268 0.052 0.000 0.000
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.268 0.051 0.000 0.000
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.268 0.037 0.000 0.000
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.268 0.051 0.000 0.000
LIVING_UNIT3_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.268 0.117 0.000 0.000
LIVING_UNIT3_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.268 0.118 0.000 0.000
LIVING_UNIT1_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.268 0.118 0.000 0.000
LIVING_UNIT2_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.268 0.103 0.000 0.000
LIVING_UNIT2_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.268 0.104 0.000 0.000
LIVING_UNIT1_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.268 0.117 0.000 0.000
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [ft3] Mechanical Ventilation [ACH] Infiltration [ACH] AFN Infiltration [ACH] Simple Ventilation [ACH]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.261 0.000 0.000 0.000
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.261 0.000 0.000 0.000
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.261 0.000 0.000 0.000
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.261 0.000 0.000 0.000
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.261 0.000 0.000 0.000
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.261 0.000 0.000 0.000
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.261 0.000 0.000 0.000
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.261 0.000 0.000 0.000
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.261 0.000 0.000 0.000
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.261 0.000 0.000 0.000
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.261 0.000 0.000 0.000
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.261 0.000 0.000 0.000
LIVING_UNIT3_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.261 0.000 0.000 0.000
LIVING_UNIT3_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.261 0.000 0.000 0.000
LIVING_UNIT1_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.261 0.000 0.000 0.000
LIVING_UNIT2_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.261 0.000 0.000 0.000
LIVING_UNIT2_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.261 0.000 0.000 0.000
LIVING_UNIT1_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.261 0.000 0.000 0.000
Values shown for a single zone without multipliers


Table of Contents

Report: Outdoor Air Details

For: Entire Facility

Timestamp: 2021-05-12 10:29:11

Mechanical Ventilation Parameters by Zone

AirLoop Name Average Number of Occupants Nominal Number of Occupants Zone Volume [ft3] Zone Area [ft2] Design Zone Outdoor Airflow - Voz [ft3/min] Minimum Dynamic Target Ventilation - Voz-dyn-min [ft3/min]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 1200.55 0.0000 0.000
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 1200.55 0.0000 0.000
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 1200.55 0.0000 0.000
LIVING_UNIT1_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 1200.55 0.0000 0.000
LIVING_UNIT2_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 1200.55 0.0000 0.000
LIVING_UNIT3_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 1200.55 0.0000 0.000
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 1200.55 0.0000 0.000
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 1200.55 0.0000 0.000
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 1200.55 0.0000 0.000
LIVING_UNIT1_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 1200.55 0.0000 0.000
LIVING_UNIT2_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 1200.55 0.0000 0.000
LIVING_UNIT3_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 1200.55 0.0000 0.000
LIVING_UNIT3_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 1.38 2.00 10207.71 1200.55 0.0000 0.000
LIVING_UNIT3_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 1200.55 0.0000 0.000
LIVING_UNIT1_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 1200.55 0.0000 0.000
LIVING_UNIT2_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 1.38 2.00 10207.71 1200.55 0.0000 0.000
LIVING_UNIT2_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 1200.55 0.0000 0.000
LIVING_UNIT1_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 1.38 2.00 10207.71 1200.55 0.0000 0.000
Total Facility   24.79 36.00 183739.38 21609.96 0.0000 0.000


Total Outdoor Air by Zone

Mechanical Ventilation [ft3] Natural Ventilation [ft3] Total Ventilation [ft3] Infiltration [ft3] Total Ventilation and Infiltration [ft3] Dynamic Target Ventilation - Voz-dyn [ft3] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr] Time Above Zero When Unoccupied [hr]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 23785081.69 0.00 23785081.69 10439691.88 34224773.56 23785081.69 0.00 8808.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 23785081.69 0.00 23785081.69 9193020.30 32978101.99 23785081.69 0.00 8808.00 0.00 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 23785081.69 0.00 23785081.69 10452392.41 34237474.10 23785081.69 0.00 8808.00 0.00 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 23785081.69 0.00 23785081.69 10410529.31 34195611.00 23785081.69 0.00 8808.00 0.00 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 23785081.69 0.00 23785081.69 9158229.22 32943310.91 23785081.69 0.00 8808.00 0.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 23785081.69 0.00 23785081.69 10414733.61 34199815.30 23785081.69 0.00 8808.00 0.00 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 23785081.69 0.00 23785081.69 4584676.50 28369758.18 23785081.69 0.00 8808.00 0.00 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 23785081.69 0.00 23785081.69 3335358.53 27120440.22 23785081.69 0.00 8808.00 0.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 23785081.69 0.00 23785081.69 4590164.28 28375245.97 23785081.69 0.00 8808.00 0.00 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 23785081.69 0.00 23785081.69 4569487.21 28354568.90 23785081.69 0.00 8808.00 0.00 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 23785081.69 0.00 23785081.69 3318349.61 27103431.29 23785081.69 0.00 8808.00 0.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 23785081.69 0.00 23785081.69 4570798.03 28355879.72 23785081.69 0.00 8808.00 0.00 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 23785081.69 0.00 23785081.69 10436903.05 34221984.74 23785081.69 0.00 8808.00 0.00 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 23785081.69 0.00 23785081.69 10471393.74 34256475.43 23785081.69 0.00 8808.00 0.00 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 23785081.69 0.00 23785081.69 10460392.54 34245474.23 23785081.69 0.00 8808.00 0.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 23785081.69 0.00 23785081.69 9177604.31 32962686.00 23785081.69 0.00 8808.00 0.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 23785081.69 0.00 23785081.69 9211819.17 32996900.86 23785081.69 0.00 8808.00 0.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 23785081.69 0.00 23785081.69 10432330.05 34217411.74 23785081.69 0.00 8808.00 0.00 0.00
Total Facility 0.428131E+09 0.00 0.428131E+09 0.145228E+09 0.573359E+09 0.428131E+09 0.00 8808.00 0.00 0.00


Average Outdoor Air During Occupancy by Zone - Flow Rates

Mechanical Ventilation [ft3/min] Natural Ventilation [ft3/min] Total Ventilation [ft3/min] Infiltration [ft3/min] Total Ventilation and Infiltration [ft3/min] Dynamic Target Ventilation - Voz-dyn [ft3/min] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 44.9950 0.0000 44.9950 19.7491 64.7441 44.9950 0.00 8808.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 44.9950 0.0000 44.9950 17.3907 62.3857 44.9950 0.00 8808.00 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 44.9950 0.0000 44.9950 19.7731 64.7681 44.9950 0.00 8808.00 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 44.9950 0.0000 44.9950 19.6939 64.6889 44.9950 0.00 8808.00 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 44.9950 0.0000 44.9950 17.3249 62.3199 44.9950 0.00 8808.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 44.9950 0.0000 44.9950 19.7019 64.6969 44.9950 0.00 8808.00 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 44.9950 0.0000 44.9950 8.6730 53.6680 44.9950 0.00 8808.00 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 44.9950 0.0000 44.9950 6.3096 51.3046 44.9950 0.00 8808.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 44.9950 0.0000 44.9950 8.6834 53.6783 44.9950 0.00 8808.00 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 44.9950 0.0000 44.9950 8.6442 53.6392 44.9950 0.00 8808.00 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 44.9950 0.0000 44.9950 6.2774 51.2724 44.9950 0.00 8808.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 44.9950 0.0000 44.9950 8.6467 53.6417 44.9950 0.00 8808.00 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 44.9950 0.0000 44.9950 19.7438 64.7388 44.9950 0.00 8808.00 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 44.9950 0.0000 44.9950 19.8091 64.8040 44.9950 0.00 8808.00 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 44.9950 0.0000 44.9950 19.7883 64.7832 44.9950 0.00 8808.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 44.9950 0.0000 44.9950 17.3616 62.3565 44.9950 0.00 8808.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 44.9950 0.0000 44.9950 17.4263 62.4213 44.9950 0.00 8808.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 44.9950 0.0000 44.9950 19.7352 64.7301 44.9950 0.00 8808.00 0.00
Total Facility 809.9097 0.0000 809.9097 274.7321 1084.6418 809.9097 0.00 8808.00 0.00


Total Outdoor Air by AirLoop

Mechanical Ventilation [ft3] Natural Ventilation [ft3/min] Total Ventilation [ft3/min] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [ft3] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr] Time Above Zero When Unoccupied [hr]
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.00 23785081.69 8808.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.00 23785081.69 8808.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.00 23785081.69 8808.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 23785081.69 8808.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 23785081.69 8808.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 23785081.69 8808.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 0.00 0.00 0.00 23785081.69 8808.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 0.00 0.00 0.00 23785081.69 8808.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 0.00 0.00 23785081.69 8808.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 23785081.69 8808.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 23785081.69 8808.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 23785081.69 8808.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 0.00 0.00 0.00 23785081.69 8808.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 0.00 0.00 0.00 23785081.69 8808.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 0.00 0.00 0.00 23785081.69 8808.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 0.00 0.00 0.00 23785081.69 8808.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 0.00 0.00 0.00 23785081.69 8808.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 0.00 23785081.69 8808.00 0.00 0.00 0.00


Average Outdoor Air During Occupancy by AirLoop

Mechanical Ventilation [ft3/min] Natural Ventilation [ft3/min] Total Ventilation [ft3/min] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [ft3/min] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr]
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 0.0000 0.0000 0.0000 44.9950 8808.00 0.00 0.00
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 0.0000 0.0000 0.0000 44.9950 8808.00 0.00 0.00
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 0.0000 0.0000 0.0000 44.9950 8808.00 0.00 0.00
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 0.0000 0.0000 0.0000 44.9950 8808.00 0.00 0.00
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 0.0000 0.0000 0.0000 44.9950 8808.00 0.00 0.00
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 0.0000 0.0000 0.0000 44.9950 8808.00 0.00 0.00
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 0.0000 0.0000 0.0000 44.9950 8808.00 0.00 0.00
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 0.0000 0.0000 0.0000 44.9950 8808.00 0.00 0.00
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 0.0000 0.0000 0.0000 44.9950 8808.00 0.00 0.00
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 0.0000 0.0000 0.0000 44.9950 8808.00 0.00 0.00
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 0.0000 0.0000 0.0000 44.9950 8808.00 0.00 0.00
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 0.0000 0.0000 0.0000 44.9950 8808.00 0.00 0.00
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 0.0000 0.0000 0.0000 44.9950 8808.00 0.00 0.00
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 0.0000 0.0000 0.0000 44.9950 8808.00 0.00 0.00
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 0.0000 0.0000 0.0000 44.9950 8808.00 0.00 0.00
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 0.0000 0.0000 0.0000 44.9950 8808.00 0.00 0.00
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 0.0000 0.0000 0.0000 44.9950 8808.00 0.00 0.00
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 0.0000 0.0000 0.0000 44.9950 8808.00 0.00 0.00


Outdoor Air Controller Limiting Factors by AirLoop

No Limiting Factor [hr] Limits and Scheduled Limits [hr] Economizer [hr] Exhaust Flow [hr] Mixed Air Flow [hr] High Humidity [hr] Demand Controlled Ventilation [hr] Night Ventilation [hr] Demand Limiting [hr] Energy Management System [hr]
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Average Outdoor Air for Limiting Factors During Occupancy

No Limiting Factor [ft3/min] Limits and Scheduled Limits [ft3/min] Economizer [ft3/min] Exhaust Flow [ft3/min] Mixed Air Flow [ft3/min] High Humidity [ft3/min] Demand Controlled Ventilation [ft3/min] Night Ventilation [ft3/min] Demand Limiting [ft3/min] Energy Management System [ft3/min]
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000



Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2021-05-12 10:29:11

Surfaces by Class

Total Outdoors
Wall 82 58
Floor 29 4
Roof 27 2
Internal Mass 0 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 30 30
Door 18 18
Glass Door 0 0
Shading 60 60
Overhang 30 30
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 18
Conditioned Zones 18
Unconditioned Zones 3
Supply Plenums 0
Return Plenums 0


Input Fields

Count
IDF Objects 2040
Defaulted Fields 1700
Fields with Defaults 7086
Autosized Fields 360
Autosizable Fields 612
Autocalculated Fields 197
Autocalculatable Fields 421



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2021-05-12 10:29:11

Annual and Peak Values - Electricity

Electricity Annual Value [kWh] Electricity Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Electricity Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
Electricity:Facility 184358.02 7967.15 17-APR-03:20 55659.08 07-JAN-07:30
Electricity:Building 99140.61 6270.77 02-JAN-03:10 18720.91 01-JAN-18:10
Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 5507.81 348.38 02-JAN-03:10 1040.05 01-JAN-18:10
InteriorLights:Electricity 11336.81 253.88 01-JAN-00:10 3692.78 01-JAN-19:10
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 629.82 14.10 01-JAN-00:10 205.15 01-JAN-19:10
General:InteriorLights:Electricity 11336.81 253.88 01-JAN-00:10 3692.78 01-JAN-19:10
Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 5507.81 348.38 02-JAN-03:10 1040.05 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 629.82 14.10 01-JAN-00:10 205.15 01-JAN-19:10
Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 5507.81 348.38 02-JAN-03:10 1040.05 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 629.82 14.10 01-JAN-00:10 205.15 01-JAN-19:10
Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 5507.81 348.38 02-JAN-03:10 1040.05 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 629.82 14.10 01-JAN-00:10 205.15 01-JAN-19:10
Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 5507.81 348.38 02-JAN-03:10 1040.05 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 629.82 14.10 01-JAN-00:10 205.15 01-JAN-19:10
Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 5507.81 348.38 02-JAN-03:10 1040.05 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 629.82 14.10 01-JAN-00:10 205.15 01-JAN-19:10
Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 5507.81 348.38 02-JAN-03:10 1040.05 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 629.82 14.10 01-JAN-00:10 205.15 01-JAN-19:10
Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 5507.81 348.38 02-JAN-03:10 1040.05 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 629.82 14.10 01-JAN-00:10 205.15 01-JAN-19:10
Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 5507.81 348.38 02-JAN-03:10 1040.05 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 629.82 14.10 01-JAN-00:10 205.15 01-JAN-19:10
Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 5507.81 348.38 02-JAN-03:10 1040.05 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 629.82 14.10 01-JAN-00:10 205.15 01-JAN-19:10
Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 5507.81 348.38 02-JAN-03:10 1040.05 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 629.82 14.10 01-JAN-00:10 205.15 01-JAN-19:10
Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 5507.81 348.38 02-JAN-03:10 1040.05 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 629.82 14.10 01-JAN-00:10 205.15 01-JAN-19:10
Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 5507.81 348.38 02-JAN-03:10 1040.05 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 629.82 14.10 01-JAN-00:10 205.15 01-JAN-19:10
Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 5507.81 348.38 02-JAN-03:10 1040.05 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 629.82 14.10 01-JAN-00:10 205.15 01-JAN-19:10
Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 5507.81 348.38 02-JAN-03:10 1040.05 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 629.82 14.10 01-JAN-00:10 205.15 01-JAN-19:10
Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 5507.81 348.38 02-JAN-03:10 1040.05 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 629.82 14.10 01-JAN-00:10 205.15 01-JAN-19:10
Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 5507.81 348.38 02-JAN-03:10 1040.05 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 629.82 14.10 01-JAN-00:10 205.15 01-JAN-19:10
Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 5507.81 348.38 02-JAN-03:10 1040.05 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 629.82 14.10 01-JAN-00:10 205.15 01-JAN-19:10
InteriorEquipment:Electricity 87803.80 5989.14 02-JAN-04:10 15388.75 01-JAN-18:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 4877.99 332.73 02-JAN-04:10 854.93 01-JAN-18:10
dishwasher:InteriorEquipment:Electricity 2758.31 25.25 02-JAN-03:10 880.12 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity 12036.11 1198.77 01-JAN-04:10 1639.04 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity 1408.53 13.53 02-JAN-02:10 381.47 01-JAN-09:10
electric_dryer:InteriorEquipment:Electricity 12502.11 63.73 02-JAN-03:10 3196.73 01-JAN-11:10
electric_range:InteriorEquipment:Electricity 9058.39 87.62 01-JAN-02:10 3721.08 01-JAN-17:10
television:InteriorEquipment:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
electric_mels:InteriorEquipment:Electricity 46926.68 4099.97 01-JAN-09:10 7929.96 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity 3113.66 272.04 01-JAN-09:10 526.17 01-JAN-20:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 4877.99 332.73 02-JAN-04:10 854.93 01-JAN-18:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 4877.99 332.73 02-JAN-04:10 854.93 01-JAN-18:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 4877.99 332.73 02-JAN-04:10 854.93 01-JAN-18:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 4877.99 332.73 02-JAN-04:10 854.93 01-JAN-18:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 4877.99 332.73 02-JAN-04:10 854.93 01-JAN-18:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 4877.99 332.73 02-JAN-04:10 854.93 01-JAN-18:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 4877.99 332.73 02-JAN-04:10 854.93 01-JAN-18:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 4877.99 332.73 02-JAN-04:10 854.93 01-JAN-18:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 4877.99 332.73 02-JAN-04:10 854.93 01-JAN-18:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 4877.99 332.73 02-JAN-04:10 854.93 01-JAN-18:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 4877.99 332.73 02-JAN-04:10 854.93 01-JAN-18:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 4877.99 332.73 02-JAN-04:10 854.93 01-JAN-18:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 4877.99 332.73 02-JAN-04:10 854.93 01-JAN-18:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 4877.99 332.73 02-JAN-04:10 854.93 01-JAN-18:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 4877.99 332.73 02-JAN-04:10 854.93 01-JAN-18:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 4877.99 332.73 02-JAN-04:10 854.93 01-JAN-18:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 4877.99 332.73 02-JAN-04:10 854.93 01-JAN-18:10
Electricity:HVAC 63809.79 289.29 15-FEB-00:50 36091.37 05-FEB-08:10
Cooling:Electricity 14644.22 0.00 01-JAN-00:10 11827.37 28-JUN-16:10
General:Cooling:Electricity 14644.22 0.00 01-JAN-00:10 11827.37 28-JUN-16:10
Electricity:Plant 15898.91 149.40 01-JAN-00:10 9078.75 01-JUL-10:30
WaterSystems:Electricity 15898.91 149.40 01-JAN-00:10 9078.75 01-JUL-10:30
Fans:Electricity 9113.09 289.29 15-FEB-00:50 2874.41 05-FEB-08:10
General:Fans:Electricity 6578.94 0.00 15-FEB-00:50 2585.12 05-FEB-08:10
Ventilation:Fans:Electricity 2534.14 289.29 01-JAN-00:10 289.29 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricityPurchased:Facility 184358.02 7967.15 17-APR-03:20 55659.08 07-JAN-07:30
ElectricityPurchased:Plant 184358.02 7967.15 17-APR-03:20 55659.08 07-JAN-07:30
Cogeneration:ElectricityPurchased 184358.02 7967.15 17-APR-03:20 55659.08 07-JAN-07:30
General:Cogeneration:ElectricityPurchased 184358.02 7967.15 17-APR-03:20 55659.08 07-JAN-07:30
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricityNet:Facility 184358.02 7967.15 17-APR-03:20 55659.08 07-JAN-07:30
ElectricityNet:Plant 184358.02 7967.15 17-APR-03:20 55659.08 07-JAN-07:30
Cogeneration:ElectricityNet 184358.02 7967.15 17-APR-03:20 55659.08 07-JAN-07:30
General:Cogeneration:ElectricityNet 184358.02 7967.15 17-APR-03:20 55659.08 07-JAN-07:30
HeatRecovery:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:HeatRecovery:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ExteriorLights:Electricity 5508.71 0.00 01-JAN-06:10 1257.69 01-JAN-00:10
Exterior-Lights:ExteriorLights:Electricity 5508.71 0.00 01-JAN-06:10 1257.69 01-JAN-00:10
Garage-Lights:ExteriorLights:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Heating:Electricity 40052.49 0.00 05-JAN-15:40 33216.96 05-FEB-08:10
General:Heating:Electricity 40052.49 0.00 05-JAN-15:40 33216.96 05-FEB-08:10
Pumps:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Pumps:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Water Heater:WaterSystems:Electricity 1308.75 149.40 01-JAN-00:10 149.40 01-JAN-08:10
Water Heater Parasitic:WaterSystems:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10


Annual and Peak Values - Natural Gas

Natural Gas Annual Value [therm] Natural Gas Minimum Value [Btu/h] Timestamp of Minimum {TIMESTAMP} Natural Gas Maximum Value [Btu/h] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Cooling

Cooling Annual Value [ton-hrs] Cooling Minimum Value [ton] Timestamp of Minimum {TIMESTAMP} Cooling Maximum Value [ton] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Water

Annual Value [ft3] Minimum Value [ft3/min] Timestamp of Minimum {TIMESTAMP} Maximum Value [ft3/min] Timestamp of Maximum {TIMESTAMP}
Water:Facility 44223.64 0.01 02-JAN-02:10 0.16 01-JAN-08:10
Water:Plant 44223.64 0.01 02-JAN-02:10 0.16 01-JAN-08:10
WaterSystems:Water 44223.64 0.01 02-JAN-02:10 0.16 01-JAN-08:10
Domestic Hot Water:WaterSystems:Water 44223.64 0.01 02-JAN-02:10 0.16 01-JAN-08:10
MainsWater:Facility 44223.64 0.01 02-JAN-02:10 0.16 01-JAN-08:10
MainsWater:Plant 44223.64 0.01 02-JAN-02:10 0.16 01-JAN-08:10
WaterSystems:MainsWater 44223.64 0.01 02-JAN-02:10 0.16 01-JAN-08:10
Domestic Hot Water:WaterSystems:MainsWater 44223.64 0.01 02-JAN-02:10 0.16 01-JAN-08:10
Water Heater:WaterSystems:Water 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Water Heater:WaterSystems:MainsWater 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10


Annual and Peak Values - Other by Weight/Mass

Annual Value [lb] Minimum Value [lb/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [lb/s] Timestamp of Maximum {TIMESTAMP}
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10


Annual and Peak Values - Other Volumetric

Annual Value [ft3] Minimum Value [ft3/min] Timestamp of Minimum {TIMESTAMP} Maximum Value [ft3/min] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [gal] Minimum Value [gal] Timestamp of Minimum {TIMESTAMP} Maximum Value [gal] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other

Annual Value [kBtu] Minimum Value [Btu/h] Timestamp of Minimum {TIMESTAMP} Maximum Value [Btu/h] Timestamp of Maximum {TIMESTAMP}
EnergyTransfer:Facility 912898.31 12319.20 08-SEP-04:00 288661.91 20-JUL-18:20
EnergyTransfer:HVAC 445704.07 0.00 15-FEB-00:50 163781.38 04-JAN-07:20
CoolingCoils:EnergyTransfer 308948.17 0.00 01-JAN-00:10 147466.50 20-JUL-18:20
EnergyTransfer:Building 341605.01 4797.11 28-MAR-10:10 125827.29 20-JUL-18:20
EnergyTransfer:Zone:CRAWLSPACE 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Heating:EnergyTransfer 53761.88 0.00 05-JAN-15:40 61306.12 17-JAN-05:10
Heating:EnergyTransfer:Zone:CRAWLSPACE 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer 53761.88 0.00 05-JAN-15:40 61306.12 17-JAN-05:10
Cooling:EnergyTransfer 287843.13 0.00 01-JAN-04:30 125827.29 20-JUL-18:20
Cooling:EnergyTransfer:Zone:CRAWLSPACE 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cooling:EnergyTransfer 287843.13 0.00 01-JAN-04:30 125827.29 20-JUL-18:20
EnergyTransfer:Zone:BREEZEWAY 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Heating:EnergyTransfer:Zone:BREEZEWAY 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:BREEZEWAY 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 21728.92 0.59 31-JAN-13:20 11286.47 20-JUL-17:50
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 3956.25 0.00 01-JAN-10:40 5041.79 17-JAN-09:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 17772.67 0.00 01-JAN-00:10 11286.47 20-JUL-17:50
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 15510.39 0.11 02-JAN-01:40 5490.23 21-JUL-19:20
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 2290.35 0.00 01-JAN-10:10 4040.16 06-FEB-06:30
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 13220.04 0.00 01-JAN-00:10 5490.23 21-JUL-19:20
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 21893.66 0.29 30-NOV-22:30 7560.78 29-JUN-09:00
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 3712.96 0.00 01-JAN-08:50 5441.18 15-DEC-06:40
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 18180.70 0.00 01-JAN-00:10 7560.78 29-JUN-09:00
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 19139.19 0.25 20-OCT-05:50 11185.94 20-JUL-17:50
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 5625.85 0.00 01-JAN-13:40 5415.13 06-FEB-04:40
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 13513.34 0.00 01-JAN-00:10 11185.94 20-JUL-17:50
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 12863.66 0.86 08-OCT-05:50 5168.96 21-JUL-19:20
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 3886.04 0.00 01-JAN-18:20 4335.82 17-JAN-05:10
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 8977.62 0.00 01-JAN-00:10 5168.96 21-JUL-19:20
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 18762.44 0.61 09-JUN-03:40 7948.40 29-JUN-09:10
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 5076.25 0.00 01-JAN-13:20 5457.08 17-JAN-05:10
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 13686.19 0.00 01-JAN-00:10 7948.40 29-JUN-09:10
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 22488.93 0.77 23-FEB-22:40 10661.05 20-JUL-17:50
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1702.86 0.00 01-JAN-00:10 3263.69 22-DEC-06:50
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 20786.06 0.00 01-JAN-01:40 10661.05 20-JUL-17:50
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 17235.15 0.04 06-DEC-07:30 5077.63 20-SEP-14:10
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 592.34 0.00 01-JAN-00:10 2601.61 19-JAN-09:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 16642.81 0.00 01-JAN-04:30 5077.63 20-SEP-14:10
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 23039.01 0.27 12-OCT-05:00 7609.94 17-AUG-10:00
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1592.64 0.00 01-JAN-00:10 3404.33 06-FEB-04:40
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 21446.38 0.00 01-JAN-01:40 7609.94 17-AUG-10:00
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 18584.31 0.23 14-MAR-23:20 10503.91 20-JUL-17:50
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 2711.94 0.00 01-JAN-13:20 3730.18 15-DEC-09:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 15872.36 0.00 01-JAN-00:10 10503.91 20-JUL-17:50
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 12882.78 0.13 08-JAN-22:40 4886.24 21-JUL-18:40
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1246.61 0.00 01-JAN-00:10 2628.53 05-FEB-10:20
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 11636.17 0.00 01-JAN-01:40 4886.24 21-JUL-18:40
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 18930.72 0.41 23-DEC-10:10 7700.34 29-JUN-08:50
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 2471.27 0.00 01-JAN-09:40 3627.42 17-JAN-08:10
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 16459.45 0.00 01-JAN-00:10 7700.34 29-JUN-08:50
EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Heating:EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 20388.39 0.37 23-JAN-14:40 7995.89 29-JUN-09:00
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 4025.53 0.00 01-JAN-12:50 4662.57 15-DEC-07:40
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 16362.86 0.00 01-JAN-00:10 7995.89 29-JUN-09:00
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 23165.90 0.67 21-FEB-14:50 7695.78 21-JUL-09:40
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 2884.37 0.00 01-JAN-08:50 4390.32 17-JAN-09:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 20281.53 0.00 01-JAN-00:10 7695.78 21-JUL-09:40
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 22804.26 0.31 09-JUN-02:40 11184.72 20-JUL-18:20
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 3078.74 0.00 01-JAN-00:10 4397.40 15-DEC-07:20
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 19725.53 0.00 01-JAN-01:30 11184.72 20-JUL-18:20
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 14546.22 0.27 10-FEB-00:20 5640.23 21-JUL-19:20
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 2844.98 0.00 01-JAN-17:10 3890.82 04-FEB-08:30
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 11701.24 0.00 01-JAN-00:10 5640.23 21-JUL-19:20
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 17161.48 1.30 27-FEB-10:20 5694.55 21-JUL-19:20
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 1611.81 0.00 01-JAN-00:10 3980.57 17-JAN-09:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 15549.68 0.00 01-JAN-01:40 5694.55 21-JUL-19:20
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 20479.59 0.72 29-MAR-12:30 11439.22 20-JUL-18:20
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 4451.09 0.00 01-JAN-13:40 4616.84 15-DEC-07:40
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 16028.50 0.00 01-JAN-00:10 11439.22 20-JUL-18:20
HeatRecoveryForHeating:EnergyTransfer 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
HeatRecoveryForCooling:EnergyTransfer 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
HeatingCoils:EnergyTransfer 136755.90 0.00 05-JAN-15:40 113336.27 05-FEB-08:10
EnergyTransfer:Plant 125589.23 1019.42 10-AUG-03:00 33910.27 04-FEB-09:00
WaterSystems:EnergyTransfer 125589.23 1019.42 10-AUG-03:00 33910.27 04-FEB-09:00
Domestic Hot Water:WaterSystems:EnergyTransfer 125589.23 1019.42 10-AUG-03:00 33910.27 04-FEB-09:00
PlantLoopHeatingDemand:Facility 125589.23 1019.42 10-AUG-03:00 33910.27 04-FEB-09:00
PlantLoopHeatingDemand:Plant 125589.23 1019.42 10-AUG-03:00 33910.27 04-FEB-09:00
WaterSystems:PlantLoopHeatingDemand 125589.23 1019.42 10-AUG-03:00 33910.27 04-FEB-09:00
General:WaterSystems:PlantLoopHeatingDemand 125589.23 1019.42 10-AUG-03:00 33910.27 04-FEB-09:00
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2021-05-12 10:29:11

Annual Building Sensible Heat Gain Components

HVAC Zone Eq & Other Sensible Air Heating [kBtu] HVAC Zone Eq & Other Sensible Air Cooling [ton-hrs] HVAC Terminal Unit Sensible Air Heating [kBtu] HVAC Terminal Unit Sensible Air Cooling [ton-hrs] HVAC Input Heated Surface Heating [kBtu] HVAC Input Cooled Surface Cooling [ton-hrs] People Sensible Heat Addition [kBtu] Lights Sensible Heat Addition [kBtu] Equipment Sensible Heat Addition [kBtu] Window Heat Addition [kBtu] Interzone Air Transfer Heat Addition [kBtu] Infiltration Heat Addition [kBtu] Opaque Surface Conduction and Other Heat Addition [kBtu] Equipment Sensible Heat Removal [kBtu] Window Heat Removal [kBtu] Interzone Air Transfer Heat Removal [kBtu] Infiltration Heat Removal [kBtu] Opaque Surface Conduction and Other Heat Removal [kBtu]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 441.185 -929.56 9137.426 -1018.71 0.000 0.000 3026.350 2150.478 10401.374 15204.995 0.000 197.438 0.027 0.000 -4717.69 0.000 -3163.26 -9283.33
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 441.965 -927.74 7020.827 -603.94 0.000 0.000 3025.510 2150.478 10401.374 7151.814 0.000 174.333 0.043 0.000 -1886.97 0.000 -2779.16 -7307.70
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 442.011 -934.66 8302.140 -998.37 0.000 0.000 3025.445 2150.478 10401.374 15885.453 0.000 196.816 0.009 0.000 -4565.47 0.000 -3175.81 -9450.58
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 441.906 -921.99 12193.053 -787.06 0.000 0.000 3042.107 2150.478 10401.374 10025.509 0.000 197.974 0.000 0.000 -4820.77 0.000 -3118.16 -9991.07
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 442.944 -917.72 10833.922 -445.41 0.000 0.000 3047.140 2150.478 10401.374 1822.211 0.000 175.853 0.000 0.000 -1972.84 0.000 -2728.37 -7804.25
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 442.299 -925.70 11533.574 -788.64 0.000 0.000 3042.612 2150.478 10401.374 10624.943 0.000 196.945 0.000 0.000 -4566.61 0.000 -3120.20 -10119.62
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 442.011 -938.46 5680.003 -1160.57 0.000 0.000 3001.988 2150.478 10401.374 15101.313 0.000 86.005 0.270 0.000 -4876.07 0.000 -1406.35 -5375.58
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 441.758 -937.72 3668.353 -741.21 0.000 0.000 2998.292 2150.478 10401.374 7102.507 0.000 62.662 0.119 0.000 -1949.94 0.000 -1023.16 -3691.76
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 441.872 -943.53 5093.704 -1170.83 0.000 0.000 3002.129 2150.478 10401.374 15774.941 0.000 85.839 0.053 0.000 -4712.52 0.000 -1413.23 -5435.29
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 442.352 -929.51 8217.175 -887.61 0.000 0.000 3022.880 2150.478 10401.374 9944.420 0.000 86.139 0.010 0.000 -4973.29 0.000 -1381.33 -6090.26
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 442.512 -923.65 6702.495 -536.59 0.000 0.000 3032.496 2150.478 10401.374 1795.859 0.000 63.077 0.143 0.000 -2031.55 0.000 -995.12 -4027.03
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 443.384 -932.61 7705.948 -910.94 0.000 0.000 3026.622 2150.478 10401.374 10532.259 0.000 85.869 0.000 0.000 -4700.06 0.000 -1381.41 -6126.96
LIVING_UNIT3_BACKROW_TOPFLOOR 441.125 -930.59 9951.004 -962.26 0.000 0.000 3028.473 2150.478 10401.374 10532.500 0.000 195.252 0.000 0.000 -4708.89 0.000 -3151.79 -6110.06
LIVING_UNIT3_FRONTROW_TOPFLOOR 441.195 -938.81 7099.881 -1137.98 0.000 0.000 3011.585 2150.478 10401.374 15786.903 0.000 195.208 0.025 0.000 -4696.81 0.000 -3205.51 -6246.08
LIVING_UNIT1_FRONTROW_TOPFLOOR 441.406 -934.47 7783.702 -1136.80 0.000 0.000 3011.264 2150.478 10401.374 15102.273 0.000 195.539 0.051 0.000 -4856.02 0.000 -3194.51 -6163.65
LIVING_UNIT2_BACKROW_TOPFLOOR 442.213 -923.80 9048.624 -604.11 0.000 0.000 3032.057 2150.478 10401.374 1793.909 0.000 173.258 0.000 0.000 -2035.24 0.000 -2756.94 -3902.60
LIVING_UNIT2_FRONTROW_TOPFLOOR 441.570 -933.34 5696.245 -738.52 0.000 0.000 3009.200 2150.478 10401.374 7102.635 0.000 172.503 0.085 0.000 -1941.48 0.000 -2809.42 -4147.42
LIVING_UNIT1_BACKROW_TOPFLOOR 441.777 -927.51 10490.921 -947.08 0.000 0.000 3026.631 2150.478 10401.374 9934.175 0.000 195.776 0.004 0.000 -4971.93 0.000 -3149.62 -6009.49
CRAWLSPACE 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 39278.157 119647.019 0.000 0.000 0.000 -158925.18 0.000
BREEZEWAY 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
ATTIC 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 22724.326 177571.517 0.000 0.000 0.000 -200295.84 -1.98
Total Facility 7955.486 -16751.37 146158.998 -15576.63 0.000 0.000 54412.780 38708.604 187224.736 181218.620 0.000 64738.968 297219.374 0.000 -68984.15 0.000 -403174.39 -117284.72


Peak Cooling Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [Btu/h] HVAC Zone Eq & Other Sensible Air Cooling [ton] HVAC Terminal Unit Sensible Air Heating [Btu/h] HVAC Terminal Unit Sensible Air Cooling [ton] HVAC Input Heated Surface Heating [Btu/h] HVAC Input Cooled Surface Cooling [ton] People Sensible Heat Addition [Btu/h] Lights Sensible Heat Addition [Btu/h] Equipment Sensible Heat Addition [Btu/h] Window Heat Addition [Btu/h] Interzone Air Transfer Heat Addition [Btu/h] Infiltration Heat Addition [Btu/h] Opaque Surface Conduction and Other Heat Addition [Btu/h] Equipment Sensible Heat Removal [Btu/h] Window Heat Removal [Btu/h] Interzone Air Transfer Heat Removal [Btu/h] Infiltration Heat Removal [Btu/h] Opaque Surface Conduction and Other Heat Removal [Btu/h]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 20-JUL-17:50 0.00 -0.2 0.00 -0.8 0.00 0.00 256.43 469.21 1655.83 7241.34 0.00 322.28 2640.96 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 21-JUL-19:13 0.00 -0.2 0.00 -0.4 0.00 0.00 415.55 699.99 1650.38 157.30 0.00 211.41 4451.84 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 29-JUN-09:00 0.00 -0.2 0.00 -0.5 0.00 0.00 193.52 132.34 1145.20 7370.57 0.00 104.10 0.00 0.00 0.00 0.00 0.00 -569.7
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 20-JUL-17:50 0.00 -0.2 0.00 -0.8 0.00 0.00 256.77 469.21 1655.83 7752.99 0.00 322.35 2051.03 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 21-JUL-19:13 0.00 -0.2 0.00 -0.4 0.00 0.00 418.78 699.99 1650.38 157.41 0.00 213.41 3837.29 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 29-JUN-09:00 0.00 -0.2 0.00 -0.6 0.00 0.00 191.45 132.34 1145.20 7330.10 0.00 102.59 1266.55 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 20-JUL-17:50 0.00 -0.2 0.00 -0.8 0.00 0.00 257.89 469.21 1655.83 7245.71 0.00 141.29 1942.66 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 21-JUL-18:57 0.00 -0.2 0.00 -0.4 0.00 0.00 418.13 631.63 1713.00 260.94 0.00 90.03 3947.01 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 17-AUG-10:00 0.00 -0.2 0.00 -0.4 0.00 0.00 115.09 90.23 1083.81 7304.26 0.00 40.91 0.00 0.00 0.00 0.00 0.00 -1024.3
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 20-JUL-17:50 0.00 -0.2 0.00 -0.8 0.00 0.00 258.47 469.21 1655.83 7753.74 0.00 141.41 1241.06 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 21-JUL-18:33 0.00 -0.2 0.00 -0.3 0.00 0.00 420.00 631.63 1713.00 928.58 0.00 89.93 2734.98 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 29-JUN-08:40 0.00 -0.2 0.00 -0.5 0.00 0.00 193.62 132.34 1145.20 7666.05 0.00 46.10 0.00 0.00 0.00 0.00 0.00 -689.5
LIVING_UNIT3_BACKROW_TOPFLOOR 29-JUN-08:50 0.00 -0.2 0.00 -0.5 0.00 0.00 192.90 132.34 1145.20 7498.70 0.00 103.61 0.00 0.00 0.00 0.00 0.00 -206.6
LIVING_UNIT3_FRONTROW_TOPFLOOR 21-JUL-09:35 0.00 0.04 0.00 -0.7 0.00 0.00 115.09 90.23 1083.81 7189.33 0.00 148.45 0.00 0.00 0.00 0.00 0.00 -930.9
LIVING_UNIT1_FRONTROW_TOPFLOOR 20-JUL-18:13 0.00 -0.2 0.00 -0.9 0.00 0.00 418.56 631.63 1713.00 6124.68 0.00 301.34 3861.73 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 21-JUL-19:13 0.00 -0.2 0.00 -0.4 0.00 0.00 420.06 699.99 1650.38 160.57 0.00 212.78 4025.55 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 21-JUL-19:13 0.00 -0.2 0.00 -0.4 0.00 0.00 418.68 699.99 1650.38 167.45 0.00 212.44 4426.15 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 20-JUL-18:13 0.00 -0.2 0.00 -0.9 0.00 0.00 417.32 631.63 1713.00 6813.35 0.00 300.31 3505.77 0.00 0.00 0.00 0.00 0.00
CRAWLSPACE - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
BREEZEWAY - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ATTIC - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 20-JUL-18:13 0.00 -3.4 0.00 -7.4 0.00 0.00 7660.40 11369.32 30834.00 51400.91 0.00 40462.49 13978.68 0.00 0.00 0.00 -26052.4 0.00


Peak Heating Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [Btu/h] HVAC Zone Eq & Other Sensible Air Cooling [ton] HVAC Terminal Unit Sensible Air Heating [Btu/h] HVAC Terminal Unit Sensible Air Cooling [ton] HVAC Input Heated Surface Heating [Btu/h] HVAC Input Cooled Surface Cooling [ton] People Sensible Heat Addition [Btu/h] Lights Sensible Heat Addition [Btu/h] Equipment Sensible Heat Addition [Btu/h] Window Heat Addition [Btu/h] Interzone Air Transfer Heat Addition [Btu/h] Infiltration Heat Addition [Btu/h] Opaque Surface Conduction and Other Heat Addition [Btu/h] Equipment Sensible Heat Removal [Btu/h] Window Heat Removal [Btu/h] Interzone Air Transfer Heat Removal [Btu/h] Infiltration Heat Removal [Btu/h] Opaque Surface Conduction and Other Heat Removal [Btu/h]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 17-JAN-08:55 -1782.1 0.00 8029.00 0.00 0.00 0.00 219.04 132.34 1145.20 0.00 0.00 0.00 0.00 0.00 -680.3 0.00 -1511.8 -5551.4
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 03-NOV-22:50 -1224.4 0.00 6155.22 0.00 0.00 0.00 527.86 294.76 1333.61 0.00 0.00 0.00 0.00 0.00 -536.5 0.00 -1221.1 -5329.5
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 06-FEB-06:05 -1903.0 0.00 7906.39 0.00 0.00 0.00 539.47 336.87 1074.44 0.00 0.00 0.00 0.00 0.00 -1885.5 0.00 -1293.5 -4775.1
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 17-JAN-05:05 -1815.8 0.00 8003.55 0.00 0.00 0.00 538.02 300.78 914.52 0.00 0.00 0.00 0.00 0.00 -1777.3 0.00 -1479.8 -4684.0
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 07-FEB-21:10 -1431.1 0.00 6171.55 0.00 0.00 0.00 528.39 529.36 1545.38 0.00 0.00 0.00 0.00 0.00 -608.5 0.00 -747.1 -5988.0
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 17-JAN-09:35 -1703.6 0.00 7833.84 0.00 0.00 0.00 129.87 90.23 1083.81 0.00 0.00 0.00 0.00 0.00 -53.2 0.00 -1349.9 -6031.0
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 24-OCT-23:57 -1540.2 0.00 6267.17 0.00 0.00 0.00 532.86 120.31 1146.27 0.00 0.00 0.00 0.00 0.00 -1564.8 0.00 -322.8 -4638.8
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 23-MAR-08:12 -1048.9 0.00 4415.97 0.00 0.00 0.00 216.67 132.34 1145.20 813.28 0.00 0.00 0.00 0.00 0.00 0.00 -137.9 -5536.7
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 13-JAN-23:50 -1532.7 0.00 6087.29 0.00 0.00 0.00 534.62 120.31 1146.27 0.00 0.00 0.00 0.00 0.00 -1628.1 0.00 -320.1 -4407.6
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 04-NOV-23:20 -1178.1 0.00 6167.88 0.00 0.00 0.00 526.51 120.31 1155.04 0.00 0.00 0.00 0.00 0.00 -1179.9 0.00 -200.6 -5411.1
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 09-MAR-08:13 -925.6 0.00 4432.75 0.00 0.00 0.00 218.47 132.34 1145.20 26.06 0.00 0.00 0.00 0.00 0.00 0.00 -138.6 -4890.7
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 24-NOV-23:50 -1296.1 0.00 6077.27 0.00 0.00 0.00 527.88 120.31 1146.27 0.00 0.00 0.00 0.00 0.00 -1426.5 0.00 -514.8 -4634.3
LIVING_UNIT3_BACKROW_TOPFLOOR 17-JAN-05:05 -1822.3 0.00 7563.69 0.00 0.00 0.00 535.66 300.78 914.52 0.00 0.00 0.00 0.00 0.00 -1852.0 0.00 -1488.4 -4152.0
LIVING_UNIT3_FRONTROW_TOPFLOOR 17-JAN-08:55 -1782.9 0.00 7555.04 0.00 0.00 0.00 219.60 132.34 1145.20 0.00 0.00 0.00 0.00 0.00 -526.1 0.00 -1514.6 -5228.5
LIVING_UNIT1_FRONTROW_TOPFLOOR 17-JAN-08:55 -1787.1 0.00 6948.46 0.00 0.00 0.00 217.02 132.34 1145.20 0.00 0.00 0.00 0.00 0.00 -736.5 0.00 -1520.2 -4399.2
LIVING_UNIT2_BACKROW_TOPFLOOR 06-NOV-13:07 -1345.4 0.00 5849.61 0.00 0.00 0.00 127.29 90.23 1076.04 276.21 0.00 0.00 0.00 0.00 0.00 0.00 -189.9 -5884.1
LIVING_UNIT2_FRONTROW_TOPFLOOR 21-MAR-13:05 -1178.2 0.00 5866.78 0.00 0.00 0.00 127.29 90.23 1076.04 417.62 0.00 0.00 0.00 0.00 0.00 0.00 -612.8 -5787.0
LIVING_UNIT1_BACKROW_TOPFLOOR 27-DEC-22:15 -1640.4 0.00 7447.93 0.00 0.00 0.00 541.70 294.76 1333.61 0.00 0.00 0.00 0.00 0.00 -1657.1 0.00 -746.5 -5573.9
CRAWLSPACE - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
BREEZEWAY - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ATTIC - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 17-JAN-05:05 -32771.6 0.00 98761.76 0.00 0.00 0.00 9553.68 5413.96 16461.32 0.00 0.00 803.89 16899.78 0.00 -26369.5 0.00 -88753.3 0.00



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2021-05-12 10:29:11

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [ft3/min] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Uncorrected Outdoor Air Intake Airflow - Vou [ft3/min] System Primary Airflow - Vps [ft3/min] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Outdoor Air Intake Flow - Vot [ft3/min] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 489.5787 0.0000 2.0000 1.0000 0.0000 489.5787 0.0000 1.0000 0.0000 0.0000    
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 222.4448 0.0000 2.0000 1.0000 0.0000 222.4448 0.0000 1.0000 0.0000 0.0000    
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 353.4216 0.0000 2.0000 1.0000 0.0000 353.4216 0.0000 1.0000 0.0000 0.0000    
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 483.4420 0.0000 2.0000 1.0000 0.0000 483.4420 0.0000 1.0000 0.0000 0.0000    
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 226.1097 0.0000 2.0000 1.0000 0.0000 226.1097 0.0000 1.0000 0.0000 0.0000    
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 347.2818 0.0000 2.0000 1.0000 0.0000 347.2818 0.0000 1.0000 0.0000 0.0000    
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 472.2391 0.0000 2.0000 1.0000 0.0000 472.2391 0.0000 1.0000 0.0000 0.0000    
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 215.4396 0.0000 2.0000 1.0000 0.0000 215.4396 0.0000 1.0000 0.0000 0.0000    
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 360.9149 0.0000 2.0000 1.0000 0.0000 360.9149 0.0000 1.0000 0.0000 0.0000    
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 466.3943 0.0000 2.0000 1.0000 0.0000 466.3943 0.0000 1.0000 0.0000 0.0000    
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 217.4262 0.0000 2.0000 1.0000 0.0000 217.4262 0.0000 1.0000 0.0000 0.0000    
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 354.1626 0.0000 2.0000 1.0000 0.0000 354.1626 0.0000 1.0000 0.0000 0.0000    
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 494.8850 0.0000 2.0000 1.0000 0.0000 494.8850 0.0000 1.0000 0.0000 0.0000    
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 242.4541 0.0000 2.0000 1.0000 0.0000 242.4541 0.0000 1.0000 0.0000 0.0000    
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 367.6428 0.0000 2.0000 1.0000 0.0000 367.6428 0.0000 1.0000 0.0000 0.0000    
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 496.0683 0.0000 2.0000 1.0000 0.0000 496.0683 0.0000 1.0000 0.0000 0.0000    
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 249.8268 0.0000 2.0000 1.0000 0.0000 249.8268 0.0000 1.0000 0.0000 0.0000    
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 360.8112 0.0000 2.0000 1.0000 0.0000 360.8112 0.0000 1.0000 0.0000 0.0000    


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [ft3/min] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Uncorrected Outdoor Air Intake Airflow - Vou [ft3/min] System Primary Airflow - Vps [ft3/min] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Outdoor Air Intake Flow Vot [ft3/min] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 489.5787 0.0000 2.0000 1.0000 0.0000 489.5787 0.0000 1.0000 0.0000 0.0000    
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 222.4448 0.0000 2.0000 1.0000 0.0000 222.4448 0.0000 1.0000 0.0000 0.0000    
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 353.4216 0.0000 2.0000 1.0000 0.0000 353.4216 0.0000 1.0000 0.0000 0.0000    
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 483.4420 0.0000 2.0000 1.0000 0.0000 483.4420 0.0000 1.0000 0.0000 0.0000    
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 226.1097 0.0000 2.0000 1.0000 0.0000 226.1097 0.0000 1.0000 0.0000 0.0000    
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 347.2818 0.0000 2.0000 1.0000 0.0000 347.2818 0.0000 1.0000 0.0000 0.0000    
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 472.2391 0.0000 2.0000 1.0000 0.0000 472.2391 0.0000 1.0000 0.0000 0.0000    
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 215.4396 0.0000 2.0000 1.0000 0.0000 215.4396 0.0000 1.0000 0.0000 0.0000    
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 360.9149 0.0000 2.0000 1.0000 0.0000 360.9149 0.0000 1.0000 0.0000 0.0000    
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 466.3943 0.0000 2.0000 1.0000 0.0000 466.3943 0.0000 1.0000 0.0000 0.0000    
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 217.4262 0.0000 2.0000 1.0000 0.0000 217.4262 0.0000 1.0000 0.0000 0.0000    
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 354.1626 0.0000 2.0000 1.0000 0.0000 354.1626 0.0000 1.0000 0.0000 0.0000    
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 494.8850 0.0000 2.0000 1.0000 0.0000 494.8850 0.0000 1.0000 0.0000 0.0000    
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 242.4541 0.0000 2.0000 1.0000 0.0000 242.4541 0.0000 1.0000 0.0000 0.0000    
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 367.6428 0.0000 2.0000 1.0000 0.0000 367.6428 0.0000 1.0000 0.0000 0.0000    
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 496.0683 0.0000 2.0000 1.0000 0.0000 496.0683 0.0000 1.0000 0.0000 0.0000    
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 249.8268 0.0000 2.0000 1.0000 0.0000 249.8268 0.0000 1.0000 0.0000 0.0000    
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 360.8112 0.0000 2.0000 1.0000 0.0000 360.8112 0.0000 1.0000 0.0000 0.0000    


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [ft3/min-person] Zone Population - Pz Area Outdoor Air Rate - Ra [ft3/min-ft2] Zone Floor Area - Az [ft2] Breathing Zone Outdoor Airflow - Vbz [ft3/min] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [ft3/min] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [ft3/min]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT1_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT2_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT3_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT1_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT2_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT3_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT3_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT3_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT1_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT2_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT2_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT1_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000


System Ventilation Parameters

People Outdoor Air Rate - Rp [ft3/min-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [ft3/min-ft2] Sum of Zone Floor Area - Az-sum [ft2] Breathing Zone Outdoor Airflow - Vbz [ft3/min] Cooling Zone Outdoor Airflow - Voz-clg [ft3/min] Heating Zone Outdoor Airflow - Voz-htg [ft3/min]
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [ft3/min] Zone Discharge Airflow - Vdz [ft3/min] Minimum Zone Primary Airflow - Vpz-min [ft3/min] Zone Outdoor Airflow Cooling - Voz-clg [ft3/min] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 489.5787 489.5787 489.5787 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 222.4448 222.4448 222.4448 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 353.4216 353.4216 353.4216 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT1_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 483.4420 483.4420 483.4420 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT2_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 226.1097 226.1097 226.1097 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT3_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 347.2818 347.2818 347.2818 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 472.2391 472.2391 472.2391 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 215.4396 215.4396 215.4396 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 360.9149 360.9149 360.9149 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT1_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 466.3943 466.3943 466.3943 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT2_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 217.4262 217.4262 217.4262 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT3_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 354.1626 354.1626 354.1626 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT3_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 360.8112 360.8112 360.8112 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT3_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 367.6428 367.6428 367.6428 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT1_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 494.8850 494.8850 494.8850 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT2_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 249.8268 249.8268 249.8268 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT2_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 242.4541 242.4541 242.4541 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT1_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 496.0683 496.0683 496.0683 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [ft3/min] System Primary Airflow - Vps [ft3/min] Sum of Zone Discharge Airflow - Vdz-sum [ft3/min] Sum of Min Zone Primary Airflow - Vpz-min [ft3/min] Zone Outdoor Airflow Cooling - Voz-clg [ft3/min] Zone Ventilation Efficiency - Evz-min
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 489.5787 489.5787 489.5787 489.5787 0.0000 1.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 222.4448 222.4448 222.4448 222.4448 0.0000 1.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 353.4216 353.4216 353.4216 353.4216 0.0000 1.0000
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 483.4420 483.4420 483.4420 483.4420 0.0000 1.0000
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 226.1097 226.1097 226.1097 226.1097 0.0000 1.0000
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 347.2818 347.2818 347.2818 347.2818 0.0000 1.0000
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 472.2391 472.2391 472.2391 472.2391 0.0000 1.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 215.4396 215.4396 215.4396 215.4396 0.0000 1.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 360.9149 360.9149 360.9149 360.9149 0.0000 1.0000
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 466.3943 466.3943 466.3943 466.3943 0.0000 1.0000
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 217.4262 217.4262 217.4262 217.4262 0.0000 1.0000
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 354.1626 354.1626 354.1626 354.1626 0.0000 1.0000
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 494.8850 494.8850 494.8850 494.8850 0.0000 1.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 242.4541 242.4541 242.4541 242.4541 0.0000 1.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 367.6428 367.6428 367.6428 367.6428 0.0000 1.0000
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 496.0683 496.0683 496.0683 496.0683 0.0000 1.0000
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 249.8268 249.8268 249.8268 249.8268 0.0000 1.0000
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 360.8112 360.8112 360.8112 360.8112 0.0000 1.0000


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [ft3/min] Zone Discharge Airflow - Vdz [ft3/min] Minimum Zone Primary Airflow - Vpz-min [ft3/min] Zone Outdoor Airflow Heating - Voz-htg [ft3/min] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 489.5787 489.5787 489.5787 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 222.4448 222.4448 222.4448 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 353.4216 353.4216 353.4216 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT1_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 483.4420 483.4420 483.4420 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT2_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 226.1097 226.1097 226.1097 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT3_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 347.2818 347.2818 347.2818 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 472.2391 472.2391 472.2391 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 215.4396 215.4396 215.4396 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 360.9149 360.9149 360.9149 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT1_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 466.3943 466.3943 466.3943 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT2_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 217.4262 217.4262 217.4262 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT3_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 354.1626 354.1626 354.1626 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT3_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 360.8112 360.8112 360.8112 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT3_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 367.6428 367.6428 367.6428 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT1_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 494.8850 494.8850 494.8850 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT2_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 249.8268 249.8268 249.8268 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT2_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 242.4541 242.4541 242.4541 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT1_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 496.0683 496.0683 496.0683 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [ft3/min] System Primary Airflow - Vps [ft3/min] Sum of Zone Discharge Airflow - Vdz-sum [ft3/min] Sum of Min Zone Primary Airflow - Vpz-min [ft3/min] Zone Outdoor Airflow Heating - Voz-htg [ft3/min] Zone Ventilation Efficiency - Evz-min
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 489.5787 489.5787 489.5787 489.5787 0.0000 1.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 222.4448 222.4448 222.4448 222.4448 0.0000 1.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 353.4216 353.4216 353.4216 353.4216 0.0000 1.0000
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 483.4420 483.4420 483.4420 483.4420 0.0000 1.0000
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 226.1097 226.1097 226.1097 226.1097 0.0000 1.0000
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 347.2818 347.2818 347.2818 347.2818 0.0000 1.0000
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 472.2391 472.2391 472.2391 472.2391 0.0000 1.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 215.4396 215.4396 215.4396 215.4396 0.0000 1.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 360.9149 360.9149 360.9149 360.9149 0.0000 1.0000
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 466.3943 466.3943 466.3943 466.3943 0.0000 1.0000
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 217.4262 217.4262 217.4262 217.4262 0.0000 1.0000
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 354.1626 354.1626 354.1626 354.1626 0.0000 1.0000
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 494.8850 494.8850 494.8850 494.8850 0.0000 1.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 242.4541 242.4541 242.4541 242.4541 0.0000 1.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 367.6428 367.6428 367.6428 367.6428 0.0000 1.0000
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 496.0683 496.0683 496.0683 496.0683 0.0000 1.0000
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 249.8268 249.8268 249.8268 249.8268 0.0000 1.0000
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 360.8112 360.8112 360.8112 360.8112 0.0000 1.0000



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2021-05-12 10:29:11

Sec1.1A-General Information

Data
Weather File ANNUAL ** Albuquerque Intl Sunport NM USA TMY3 WMO#=723650
Total gross floor area [ft2] 39005.22
Principal Heating Source Electricity


EAp2-1. Space Usage Type

Space Area [ft2] Regularly Occupied Area [ft2] Unconditioned Area [ft2] Typical Hours/Week in Operation [hr/wk]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_BACKROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_BACKROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_BACKROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
CRAWLSPACE 7794.39 0.00 7794.39 0.00
BREEZEWAY 1798.16 0.00 1798.16 0.00
ATTIC 7802.71 0.00 7802.71 0.00
Totals 39005.22 21609.96 17395.26  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 954.83
Number of hours cooling loads not met 9.00
Number of hours not met 963.83


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electricity Energy Use [kWh] Electricity Demand [W] Natural Gas Energy Use [therm] Natural Gas Demand [Btu/h] Gasoline Use [therm] Gasoline Demand [Btu/h] Diesel Use [kBtu] Diesel Demand [Btu/h] Coal Use [kBtu] Coal Demand [Btu/h] Fuel Oil No 1 Use [kBtu] Fuel Oil No 1 Demand [Btu/h] Fuel Oil No 2 Use [kBtu] Fuel Oil No 2 Demand [Btu/h] Propane Use [kBtu] Propane Demand [Btu/h] Other Fuel 1 Use [kBtu] Other Fuel 1 Demand [Btu/h] Other Fuel 2 Use [kBtu] Other Fuel 2 Demand [Btu/h] District Cooling Use [ton-hrs] District Cooling Demand [ton] District Heating Use [kBtu] District Heating Demand [Btu/h]
Heating -- General 40052.49 33216.96 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling -- General 14644.22 11827.37 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting -- General 11336.81 3692.78 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting -- Exterior-Lights 5508.71 1257.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting -- Garage-Lights 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- dishwasher 2758.31 880.12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- refrigerator 12036.11 1639.04 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- clotheswasher 1408.53 381.47 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- electric_dryer 12502.11 3196.73 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- electric_range 9058.39 3721.08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- television 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- electric_mels 46926.68 7929.96 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- IECC_adj 3113.66 526.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- General 6578.94 2585.12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- Ventilation 2534.14 289.29 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- Domestic Hot Water 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- Water Heater 1308.75 149.40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- Water Heater Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- Other 14590.16 8929.35 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


EAp2-6. Energy Use Summary

Process Subtotal [kBtu] Total Energy Use [kBtu]
Electricity 299798.81 629475.19
Natural Gas 0.00 0.00
Additional 0.00 0.00
Total 299798.81 629475.19


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [kBtu]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [kWh/ft2]
Interior Lighting (All) 0.29
Space Heating 1.03
Space Cooling 0.38
Fans (All) 0.23
Service Water Heating 0.41
Receptacle Equipment 2.25
Miscellaneous (All) 4.73
Subtotal 4.73


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [kWh/ft2]
Space Heating 0.00
Service Water Heating 0.00
Miscellaneous (All) 0.00
Subtotal 0.00


EAp2-17c. Energy Use Intensity - Additional

Additional [kBtu/ft2]
Subtotal 0.00
Miscellaneous 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting (All) 6.15
Space Heating 21.73
Space Cooling 7.94
Fans (All) 4.94
Service Water Heating 8.62
Receptacle Equipment 47.63
Miscellaneous 2.99


Schedules-Equivalent Full Load Hours (Schedule Type=Fraction)

Equivalent Full Load Hours of Operation Per Year [hr] Hours > 1% [hr]
OCCUPANCY 6031. 8760.
INTERIORLIGHTING 2852. 8760.
INTERIORLIGHTINGHE 3070. 8760.
INTERIORLIGHTINGHE_OS 2910. 8760.
INTERIORLIGHTINGHE_VS 2149. 8760.
EXTERIORLIGHTING 4380. 4380.
REFRIGERATOR 7343. 8760.
MISCPLUGLOAD 5918. 8760.
COOKINGRANGE 2434. 8760.
DHW_SCH 365. 8760.
DISHWASHER 2799. 8760.
CLOTHESWASHER 3297. 8760.
CLOTHESDRYER 3911. 8760.
SINKS 4179. 8760.
SHOWERS 2640. 8760.
BATHS 2586. 8760.
DHWDIST 4662. 8760.
SHADING_2012IECC 0. 0.
SINKSENSSCHEDULE 6025. 8760.
SINKLATSCHEDULE 2735. 8760.
SHOWERSENSSCHEDULE 4492. 8760.
SHOWERLATSCHEDULE 4268. 8760.
BATHSENSSCHEDULE 8760. 8760.
BATHLATSCHEDULE 0. 0.


Schedules-SetPoints (Schedule Type=Temperature)

First Object Used Month Assumed 11am First Wednesday [F] Days with Same 11am Value 11pm First Wednesday [F] Days with Same 11pm Value
HEATING_SCH THERMOSTAT_LIVING DUAL SP CONTROL January 72.00 365 72.00 365
COOLING_SCH THERMOSTAT_LIVING DUAL SP CONTROL July 75.00 365 75.00 365



Table of Contents

Report: Annual Thermal Resilience Summary

For: Entire Facility

Timestamp: 2021-05-12 10:29:11

Heat Index Hours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 8760.00 0.00 0.00 0.00 0.00
CRAWLSPACE 8392.83 367.17 0.00 0.00 0.00
BREEZEWAY 7715.83 1044.17 0.00 0.00 0.00
ATTIC 7250.50 778.33 546.17 185.00 0.00
Min 7250.50 0.00 0.00 0.00 0.00
Max 8760.00 1044.17 546.17 185.00 0.00
Average 8620.91 104.27 26.01 8.81 0.00
Sum 181039.17 2189.67 546.17 185.00 0.00


Heat Index OccupantHours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 9125.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 9125.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 9125.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 9125.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 9125.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 9125.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 9125.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 9125.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 9125.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 9125.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 9125.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 9125.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 9125.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 9125.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 9125.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 9125.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 9125.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 9125.00 0.00 0.00 0.00 0.00
CRAWLSPACE 0.00 0.00 0.00 0.00 0.00
BREEZEWAY 0.00 0.00 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 9125.00 0.00 0.00 0.00 0.00
Average 7821.43 0.00 0.00 0.00 0.00
Sum 164250.00 0.00 0.00 0.00 0.00


Humidex Hours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 8760.00 0.00 0.00 0.00 0.00
CRAWLSPACE 8583.50 176.50 0.00 0.00 0.00
BREEZEWAY 8616.83 143.17 0.00 0.00 0.00
ATTIC 7456.83 981.33 273.00 48.83 0.00
Min 7456.83 0.00 0.00 0.00 0.00
Max 8760.00 981.33 273.00 48.83 0.00
Average 8682.72 61.95 13.00 2.33 0.00
Sum 182337.17 1301.00 273.00 48.83 0.00


Humidex OccupantHours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 9125.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 9125.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 9125.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 9125.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 9125.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 9125.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 9125.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 9125.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 9125.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 9125.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 9125.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 9125.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 9125.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 9125.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 9125.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 9125.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 9125.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 9125.00 0.00 0.00 0.00 0.00
CRAWLSPACE 0.00 0.00 0.00 0.00 0.00
BREEZEWAY 0.00 0.00 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 9125.00 0.00 0.00 0.00 0.00
Average 7821.43 0.00 0.00 0.00 0.00
Sum 164250.00 0.00 0.00 0.00 0.00


Heating SET Hours

SET ≤ 12.2°C Hours (F) SET ≤ 12.2°C OccupantHours (F) Longest SET ≤ 12.2°C Duration [hr] Start Time of the Longest SET ≤ 12.2°C Duration
None        


Cooling SET Hours

SET > 30°C Hours (F) SET > 30°C OccupantHours (F) Longest SET > 30°C Duration [hr] Start Time of the Longest SET > 30°C Duration
None        



Table of Contents

Report: Annual CO2 Resilience Summary

For: Entire Facility

Timestamp: 2021-05-12 10:29:11

CO2 Level Hours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      


CO2 Level OccupantHours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      



Table of Contents

Report: Annual Visual Resilience Summary

For: Entire Facility

Timestamp: 2021-05-12 10:29:11

Illuminance Level Hours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
None        


Illuminance Level OccupantHours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
None        



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR

Timestamp: 2021-05-12 10:29:11

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 75.778 2.967 485.697 47.483 50.450
February 92.778 4.189 390.108 36.090 40.279
March 134.328 6.237 360.461 25.574 31.811
April 258.292 12.934 152.194 9.907 22.841
May 357.611 18.277 65.884 4.052 22.329
June 534.233 33.991 12.258 0.653 34.644
July 683.278 45.856 0.000 0.000 45.856
August 662.219 42.481 0.111 0.009 42.489
September 502.881 29.906 4.078 0.334 30.240
October 307.100 17.261 158.044 10.567 27.828
November 109.056 4.660 343.453 24.848 29.508
December 67.250 2.170 480.267 45.846 48.016
           
Annual Sum or Average 3784.804 220.930 2452.556 205.362 426.291
Minimum of Months 67.250 2.170 0.000 0.000 22.329
Maximum of Months 683.278 45.856 485.697 47.483 50.450



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR

Timestamp: 2021-05-12 10:29:11

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 55.972 1.084 449.956 22.070 23.154
February 55.592 1.330 364.278 17.011 18.342
March 89.717 1.810 311.465 11.968 13.778
April 210.192 5.152 122.664 4.644 9.796
May 328.688 9.080 51.652 1.955 11.035
June 530.049 20.243 5.881 0.230 20.474
July 681.456 30.801 0.000 0.000 30.801
August 660.678 28.341 0.000 0.000 28.341
September 517.008 19.656 1.867 0.097 19.753
October 304.411 10.317 113.447 4.405 14.722
November 95.500 1.812 277.906 10.829 12.641
December 34.722 0.446 442.894 20.946 21.392
           
Annual Sum or Average 3563.984 130.072 2142.009 94.156 224.228
Minimum of Months 34.722 0.446 0.000 0.000 9.796
Maximum of Months 681.456 30.801 449.956 22.070 30.801



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR

Timestamp: 2021-05-12 10:29:11

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 70.389 1.675 471.239 33.824 35.499
February 72.969 2.221 370.686 25.372 27.593
March 140.206 4.303 304.771 16.159 20.463
April 312.253 11.960 102.858 4.712 16.672
May 426.909 18.338 39.611 1.548 19.886
June 580.689 35.210 5.861 0.197 35.407
July 710.972 47.727 0.000 0.000 47.727
August 686.569 43.740 0.000 0.000 43.740
September 538.833 29.524 2.278 0.151 29.675
October 343.356 15.605 132.683 6.505 22.111
November 117.400 3.037 317.922 16.849 19.886
December 35.833 0.578 453.206 32.207 32.786
           
Annual Sum or Average 4036.378 213.919 2201.116 137.525 351.444
Minimum of Months 35.833 0.578 0.000 0.000 16.672
Maximum of Months 710.972 47.727 471.239 33.824 47.727



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR

Timestamp: 2021-05-12 10:29:11

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 1.417 0.011 628.983 61.313 61.324
February 20.997 0.509 506.625 46.689 47.198
March 68.389 2.064 442.558 30.991 33.056
April 206.833 8.853 187.403 11.581 20.435
May 341.343 16.430 68.437 4.098 20.528
June 540.847 33.910 11.422 0.602 34.512
July 682.472 44.463 0.000 0.000 44.463
August 653.633 38.188 0.167 0.013 38.201
September 461.156 21.749 6.033 0.526 22.274
October 209.850 8.237 238.900 14.888 23.125
November 15.806 0.274 499.931 36.723 36.997
December 0.000 0.000 656.222 63.122 63.122
           
Annual Sum or Average 3202.744 174.689 3246.681 270.545 445.235
Minimum of Months 0.000 0.000 0.000 0.000 20.435
Maximum of Months 682.472 44.463 656.222 63.122 63.122



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR

Timestamp: 2021-05-12 10:29:11

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 0.000 0.000 698.361 33.044 33.044
February 0.000 0.000 574.886 26.024 26.024
March 2.361 0.011 465.578 17.167 17.178
April 131.511 2.430 182.633 6.493 8.923
May 311.185 7.587 59.558 2.167 9.753
June 530.054 20.339 5.208 0.204 20.543
July 674.925 29.626 0.000 0.000 29.626
August 643.417 24.331 0.000 0.000 24.331
September 447.208 11.863 3.336 0.188 12.051
October 155.292 2.855 213.089 7.700 10.555
November 0.000 0.000 556.014 20.421 20.421
December 0.000 0.000 719.486 34.001 34.001
           
Annual Sum or Average 2895.953 99.042 3478.150 147.409 246.451
Minimum of Months 0.000 0.000 0.000 0.000 8.923
Maximum of Months 674.925 29.626 719.486 34.001 34.001



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR

Timestamp: 2021-05-12 10:29:11

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 0.000 0.000 702.629 44.900 44.900
February 0.847 0.001 538.781 34.220 34.222
March 29.000 0.235 373.425 19.723 19.957
April 231.672 7.446 122.542 5.540 12.986
May 402.945 16.442 41.097 1.656 18.098
June 588.506 35.203 6.306 0.208 35.411
July 711.500 46.304 0.000 0.000 46.304
August 682.111 39.593 0.000 0.000 39.593
September 503.647 21.458 2.111 0.121 21.579
October 201.239 5.867 188.347 8.760 14.627
November 0.889 0.007 519.575 26.185 26.191
December 0.000 0.000 734.944 46.511 46.511
           
Annual Sum or Average 3352.356 172.557 3229.757 187.822 360.379
Minimum of Months 0.000 0.000 0.000 0.000 12.986
Maximum of Months 711.500 46.304 734.944 46.511 46.511



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR

Timestamp: 2021-05-12 10:29:11

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 111.556 4.060 396.142 38.845 42.905
February 124.417 5.392 304.419 29.089 34.481
March 166.411 7.675 231.274 18.956 26.631
April 325.075 15.565 75.119 6.301 21.867
May 451.306 21.499 26.805 2.209 23.707
June 590.319 36.782 3.514 0.262 37.044
July 698.747 48.872 0.000 0.000 48.872
August 696.272 46.418 0.000 0.000 46.418
September 579.569 33.925 0.611 0.058 33.983
October 374.572 20.203 88.147 7.393 27.596
November 162.667 6.371 230.919 18.380 24.751
December 104.556 3.252 387.336 37.467 40.719
           
Annual Sum or Average 4385.467 250.015 1744.288 158.959 408.974
Minimum of Months 104.556 3.252 0.000 0.000 21.867
Maximum of Months 698.747 48.872 396.142 38.845 48.872



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR

Timestamp: 2021-05-12 10:29:11

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 95.992 2.042 301.889 17.156 19.198
February 99.358 2.262 224.794 12.646 14.908
March 139.736 2.992 136.519 7.928 10.920
April 290.633 7.436 45.222 2.683 10.120
May 444.427 12.184 16.614 0.961 13.145
June 591.912 22.970 0.917 0.068 23.038
July 689.389 33.409 0.000 0.000 33.409
August 688.456 31.866 0.000 0.000 31.866
September 619.742 23.895 0.000 0.000 23.895
October 397.683 13.460 53.958 2.873 16.333
November 152.375 3.507 129.953 7.094 10.601
December 86.167 1.361 291.081 15.876 17.238
           
Annual Sum or Average 4295.870 157.384 1200.947 67.285 224.669
Minimum of Months 86.167 1.361 0.000 0.000 10.120
Maximum of Months 689.389 33.409 301.889 17.156 33.409



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR

Timestamp: 2021-05-12 10:29:11

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 97.056 2.841 377.150 29.298 32.139
February 116.544 3.573 282.611 21.118 24.691
March 189.481 6.479 195.002 12.271 18.750
April 377.561 15.724 46.156 2.685 18.409
May 524.018 22.657 14.750 0.810 23.467
June 632.681 38.736 1.194 0.041 38.776
July 722.125 50.928 0.000 0.000 50.928
August 716.639 47.873 0.000 0.000 47.873
September 616.606 34.088 0.167 0.013 34.100
October 404.328 19.265 75.572 4.632 23.897
November 168.794 5.056 208.611 12.716 17.773
December 84.208 1.643 368.981 27.719 29.362
           
Annual Sum or Average 4650.040 248.862 1570.193 111.303 360.166
Minimum of Months 84.208 1.643 0.000 0.000 17.773
Maximum of Months 722.125 50.928 377.150 29.298 50.928



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR

Timestamp: 2021-05-12 10:29:11

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 3.333 0.023 558.358 54.100 54.123
February 31.575 0.632 430.039 40.008 40.640
March 93.167 2.652 318.533 24.484 27.136
April 270.917 10.771 98.892 7.955 18.726
May 442.505 19.604 29.433 2.413 22.017
June 593.806 36.787 3.056 0.243 37.029
July 698.556 47.534 0.000 0.000 47.534
August 687.369 42.219 0.000 0.000 42.219
September 547.578 25.595 1.533 0.143 25.738
October 266.989 10.083 143.472 11.221 21.305
November 23.111 0.316 384.361 30.203 30.519
December 0.000 0.000 580.083 56.237 56.237
           
Annual Sum or Average 3658.905 196.217 2547.760 227.006 423.223
Minimum of Months 0.000 0.000 0.000 0.000 18.726
Maximum of Months 698.556 47.534 580.083 56.237 56.237



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR

Timestamp: 2021-05-12 10:29:11

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 0.000 0.000 575.928 29.292 29.292
February 0.000 0.000 439.856 22.485 22.485
March 15.056 0.071 248.709 13.292 13.363
April 203.664 3.777 72.356 4.143 7.920
May 424.243 10.578 19.683 1.182 11.760
June 594.210 23.147 0.806 0.060 23.208
July 684.106 32.235 0.000 0.000 32.235
August 667.997 27.958 0.000 0.000 27.958
September 557.567 15.945 0.139 0.009 15.954
October 219.769 4.401 109.967 5.677 10.078
November 0.667 0.001 349.656 16.915 16.915
December 0.000 0.000 603.897 30.642 30.642
           
Annual Sum or Average 3367.278 118.113 2420.994 123.695 241.809
Minimum of Months 0.000 0.000 0.000 0.000 7.920
Maximum of Months 684.106 32.235 603.897 30.642 32.235



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR

Timestamp: 2021-05-12 10:29:11

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 0.000 0.000 566.756 41.938 41.938
February 6.111 0.039 429.044 30.910 30.950
March 78.411 0.903 248.972 15.511 16.414
April 319.944 10.456 61.558 3.288 13.744
May 504.494 20.661 14.014 0.793 21.454
June 636.317 38.591 1.083 0.051 38.642
July 722.014 49.542 0.000 0.000 49.542
August 715.889 43.772 0.000 0.000 43.772
September 589.908 26.004 0.528 0.041 26.045
October 284.617 8.206 108.681 6.480 14.686
November 3.000 0.026 367.364 22.426 22.452
December 0.000 0.000 639.761 43.966 43.966
           
Annual Sum or Average 3860.706 198.201 2437.762 165.405 363.606
Minimum of Months 0.000 0.000 0.000 0.000 13.744
Maximum of Months 722.014 49.542 639.761 43.966 49.542



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR

Timestamp: 2021-05-12 10:29:11

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 73.194 2.435 462.678 44.565 47.000
February 93.069 3.828 361.500 33.135 36.962
March 141.639 6.073 306.630 21.861 27.934
April 304.661 14.354 111.136 7.495 21.848
May 432.400 21.392 41.237 2.725 24.117
June 587.061 38.840 4.500 0.311 39.151
July 704.314 52.279 0.000 0.000 52.279
August 695.783 48.789 0.000 0.000 48.789
September 564.293 34.023 0.819 0.071 34.093
October 342.656 18.646 119.056 8.683 27.329
November 114.889 4.410 297.731 21.970 26.380
December 64.889 1.704 457.531 43.399 45.103
           
Annual Sum or Average 4118.848 246.772 2162.817 184.214 430.985
Minimum of Months 64.889 1.704 0.000 0.000 21.848
Maximum of Months 704.314 52.279 462.678 44.565 52.279



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR

Timestamp: 2021-05-12 10:29:11

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 51.056 0.827 416.047 21.829 22.656
February 56.056 1.283 319.936 16.360 17.643
March 97.542 1.912 230.509 10.406 12.318
April 262.817 6.765 74.289 3.366 10.131
May 416.035 12.346 28.852 1.305 13.651
June 587.622 25.224 2.014 0.101 25.326
July 694.678 37.038 0.000 0.000 37.038
August 691.222 34.528 0.000 0.000 34.528
September 602.154 24.286 0.000 0.000 24.286
October 353.164 12.188 76.614 3.658 15.846
November 104.292 1.883 215.967 9.817 11.700
December 30.389 0.361 403.553 20.779 21.140
           
Annual Sum or Average 3947.024 158.643 1767.781 87.621 246.264
Minimum of Months 30.389 0.361 0.000 0.000 10.131
Maximum of Months 694.678 37.038 416.047 21.829 37.038



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR

Timestamp: 2021-05-12 10:29:11

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 65.722 1.412 448.025 32.719 34.131
February 74.733 2.213 344.403 24.007 26.220
March 150.478 4.528 254.681 13.970 18.498
April 350.308 13.962 72.194 3.425 17.387
May 490.600 22.046 22.236 0.930 22.976
June 629.197 40.287 1.972 0.082 40.369
July 725.236 53.994 0.000 0.000 53.994
August 717.333 49.947 0.000 0.000 49.947
September 603.569 34.019 0.556 0.034 34.053
October 382.317 17.416 99.703 5.593 23.009
November 117.494 2.987 272.225 15.083 18.069
December 32.375 0.464 436.911 31.542 32.006
           
Annual Sum or Average 4339.364 243.274 1952.906 127.384 370.659
Minimum of Months 32.375 0.464 0.000 0.000 17.387
Maximum of Months 725.236 53.994 448.025 32.719 53.994



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR

Timestamp: 2021-05-12 10:29:11

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 1.000 0.003 610.694 58.928 58.931
February 24.444 0.560 474.125 43.507 44.067
March 87.444 2.476 379.833 26.750 29.226
April 265.083 11.028 136.886 8.887 19.915
May 427.732 20.185 44.304 2.881 23.066
June 591.959 39.154 4.375 0.299 39.453
July 704.867 51.552 0.000 0.000 51.552
August 690.336 45.854 0.000 0.000 45.854
September 538.523 27.601 1.611 0.139 27.740
October 262.058 10.474 178.903 12.368 22.842
November 18.361 0.283 450.917 33.547 33.830
December 0.000 0.000 631.847 61.230 61.230
           
Annual Sum or Average 3611.808 209.168 2913.495 248.537 457.705
Minimum of Months 0.000 0.000 0.000 0.000 19.915
Maximum of Months 704.867 51.552 631.847 61.230 61.230



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR

Timestamp: 2021-05-12 10:29:11

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 0.000 0.000 662.842 33.946 33.946
February 0.000 0.000 525.328 25.826 25.826
March 11.778 0.077 355.255 15.327 15.404
April 195.458 4.259 105.558 4.823 9.082
May 411.200 11.356 32.669 1.493 12.849
June 591.019 25.647 1.514 0.095 25.741
July 693.211 36.483 0.000 0.000 36.483
August 681.269 31.829 0.000 0.000 31.829
September 556.822 18.040 0.333 0.017 18.057
October 215.517 5.005 146.333 6.526 11.531
November 0.167 0.000 468.528 19.739 19.739
December 0.000 0.000 684.806 35.194 35.194
           
Annual Sum or Average 3356.442 132.696 2983.165 142.985 275.681
Minimum of Months 0.000 0.000 0.000 0.000 9.082
Maximum of Months 693.211 36.483 684.806 35.194 36.483



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR

Timestamp: 2021-05-12 10:29:11

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 0.000 0.000 660.215 43.862 43.862
February 5.467 0.031 493.661 32.343 32.374
March 55.075 0.649 310.270 16.853 17.502
April 302.336 10.196 80.956 3.887 14.083
May 484.981 20.742 21.389 0.922 21.664
June 632.261 40.499 1.972 0.079 40.579
July 726.014 53.168 0.000 0.000 53.168
August 716.944 47.098 0.000 0.000 47.098
September 589.583 27.715 0.611 0.041 27.756
October 278.700 8.538 135.833 7.170 15.708
November 0.056 0.000 451.394 24.219 24.219
December 0.000 0.000 720.767 45.918 45.918
           
Annual Sum or Average 3791.417 208.636 2877.068 175.293 383.930
Minimum of Months 0.000 0.000 0.000 0.000 14.083
Maximum of Months 726.014 53.168 720.767 45.918 53.168



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR

Timestamp: 2021-05-12 10:29:11

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 2627.04 0.00 0.00
February 2210.65 0.00 0.00
March 1414.92 0.00 0.00
April 566.38 0.00 0.00
May 224.18 0.00 0.00
June 37.31 0.00 0.00
July 0.00 0.00 0.00
August 0.47 0.00 0.00
September 19.11 0.00 0.00
October 584.64 0.00 0.00
November 1420.55 0.00 0.00
December 2536.48 0.00 0.00
       
Annual Sum or Average 964.98 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 2627.04 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR

Timestamp: 2021-05-12 10:29:11

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 2114.08 0.00 0.00
February 1804.12 0.00 0.00
March 1146.39 0.00 0.00
April 459.67 0.00 0.00
May 187.29 0.00 0.00
June 22.81 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 9.60 0.00 0.00
October 421.94 0.00 0.00
November 1071.86 0.00 0.00
December 2006.42 0.00 0.00
       
Annual Sum or Average 766.01 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 2114.08 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR

Timestamp: 2021-05-12 10:29:11

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 2593.14 0.00 0.00
February 2153.59 0.00 0.00
March 1238.86 0.00 0.00
April 373.30 0.00 0.00
May 118.68 0.00 0.00
June 15.62 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 11.96 0.00 0.00
October 498.72 0.00 0.00
November 1334.84 0.00 0.00
December 2469.22 0.00 0.00
       
Annual Sum or Average 895.48 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 2593.14 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR

Timestamp: 2021-05-12 10:29:11

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 3436.62 0.00 0.00
February 2897.30 0.00 0.00
March 1737.06 0.00 0.00
April 670.77 0.00 0.00
May 229.67 0.00 0.00
June 34.86 0.00 0.00
July 0.00 0.00 0.00
August 0.73 0.00 0.00
September 30.44 0.00 0.00
October 834.48 0.00 0.00
November 2126.95 0.00 0.00
December 3538.02 0.00 0.00
       
Annual Sum or Average 1287.92 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 3538.02 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR

Timestamp: 2021-05-12 10:29:11

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 3114.16 0.00 0.00
February 2715.42 0.00 0.00
March 1617.90 0.00 0.00
April 632.36 0.00 0.00
May 204.20 0.00 0.00
June 19.82 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 18.33 0.00 0.00
October 725.66 0.00 0.00
November 1988.73 0.00 0.00
December 3204.37 0.00 0.00
       
Annual Sum or Average 1179.90 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 3204.37 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR

Timestamp: 2021-05-12 10:29:11

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 3502.18 0.00 0.00
February 2955.17 0.00 0.00
March 1538.36 0.00 0.00
April 446.55 0.00 0.00
May 129.13 0.00 0.00
June 16.75 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 9.75 0.00 0.00
October 683.27 0.00 0.00
November 2110.48 0.00 0.00
December 3627.87 0.00 0.00
       
Annual Sum or Average 1244.26 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 3627.87 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR

Timestamp: 2021-05-12 10:29:11

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 1695.42 0.00 0.00
February 1405.67 0.00 0.00
March 827.35 0.00 0.00
April 284.20 0.00 0.00
May 96.39 0.00 0.00
June 11.83 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 2.60 0.00 0.00
October 322.68 0.00 0.00
November 828.94 0.00 0.00
December 1635.30 0.00 0.00
       
Annual Sum or Average 589.25 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 1695.42 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR

Timestamp: 2021-05-12 10:29:11

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 1184.94 0.00 0.00
February 967.01 0.00 0.00
March 547.61 0.00 0.00
April 191.50 0.00 0.00
May 66.40 0.00 0.00
June 4.88 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 198.42 0.00 0.00
November 506.30 0.00 0.00
December 1096.56 0.00 0.00
       
Annual Sum or Average 394.71 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 1184.94 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR

Timestamp: 2021-05-12 10:29:11

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 1673.86 0.00 0.00
February 1335.76 0.00 0.00
March 701.08 0.00 0.00
April 158.52 0.00 0.00
May 46.26 0.00 0.00
June 2.40 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.75 0.00 0.00
October 264.65 0.00 0.00
November 750.73 0.00 0.00
December 1583.62 0.00 0.00
       
Annual Sum or Average 540.07 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 1673.86 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR

Timestamp: 2021-05-12 10:29:11

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 2391.98 0.00 0.00
February 1958.45 0.00 0.00
March 1082.52 0.00 0.00
April 363.44 0.00 0.00
May 106.68 0.00 0.00
June 11.08 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 6.51 0.00 0.00
October 496.13 0.00 0.00
November 1379.91 0.00 0.00
December 2486.46 0.00 0.00
       
Annual Sum or Average 852.44 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 2486.46 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR

Timestamp: 2021-05-12 10:29:11

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 2004.83 0.00 0.00
February 1703.83 0.00 0.00
March 909.78 0.00 0.00
April 292.99 0.00 0.00
May 80.87 0.00 0.00
June 4.26 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.63 0.00 0.00
October 388.58 0.00 0.00
November 1196.29 0.00 0.00
December 2097.24 0.00 0.00
       
Annual Sum or Average 719.05 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 2097.24 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR

Timestamp: 2021-05-12 10:29:11

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 2440.83 0.00 0.00
February 1991.78 0.00 0.00
March 902.76 0.00 0.00
April 197.77 0.00 0.00
May 46.13 0.00 0.00
June 3.10 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 2.45 0.00 0.00
October 377.16 0.00 0.00
November 1348.73 0.00 0.00
December 2558.89 0.00 0.00
       
Annual Sum or Average 817.62 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 2558.89 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_TOPFLOOR

Timestamp: 2021-05-12 10:29:11

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 2332.23 0.00 0.00
February 1919.83 0.00 0.00
March 1144.06 0.00 0.00
April 405.31 0.00 0.00
May 142.60 0.00 0.00
June 16.83 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 3.82 0.00 0.00
October 454.40 0.00 0.00
November 1188.10 0.00 0.00
December 2271.21 0.00 0.00
       
Annual Sum or Average 818.78 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 2332.23 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_TOPFLOOR

Timestamp: 2021-05-12 10:29:11

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 1811.63 0.00 0.00
February 1503.22 0.00 0.00
March 863.65 0.00 0.00
April 288.63 0.00 0.00
May 108.29 0.00 0.00
June 8.68 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 303.62 0.00 0.00
November 841.95 0.00 0.00
December 1724.52 0.00 0.00
       
Annual Sum or Average 617.62 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 1811.63 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_TOPFLOOR

Timestamp: 2021-05-12 10:29:11

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 2305.42 0.00 0.00
February 1872.80 0.00 0.00
March 984.35 0.00 0.00
April 249.40 0.00 0.00
May 65.56 0.00 0.00
June 5.99 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 2.47 0.00 0.00
October 394.06 0.00 0.00
November 1098.18 0.00 0.00
December 2222.50 0.00 0.00
       
Annual Sum or Average 762.32 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 2305.42 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_TOPFLOOR

Timestamp: 2021-05-12 10:29:11

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 3078.03 0.00 0.00
February 2516.03 0.00 0.00
March 1397.23 0.00 0.00
April 479.65 0.00 0.00
May 150.48 0.00 0.00
June 16.16 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 7.52 0.00 0.00
October 646.03 0.00 0.00
November 1810.68 0.00 0.00
December 3198.27 0.00 0.00
       
Annual Sum or Average 1102.58 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 3198.27 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_TOPFLOOR

Timestamp: 2021-05-12 10:29:11

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 2734.98 0.00 0.00
February 2303.70 0.00 0.00
March 1234.86 0.00 0.00
April 401.54 0.00 0.00
May 120.31 0.00 0.00
June 7.87 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 1.40 0.00 0.00
October 525.78 0.00 0.00
November 1643.38 0.00 0.00
December 2835.59 0.00 0.00
       
Annual Sum or Average 978.43 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 2835.59 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_TOPFLOOR

Timestamp: 2021-05-12 10:29:11

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 3149.14 0.00 0.00
February 2570.94 0.00 0.00
March 1210.04 0.00 0.00
April 288.35 0.00 0.00
May 66.19 0.00 0.00
June 5.88 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 3.03 0.00 0.00
October 514.80 0.00 0.00
November 1796.81 0.00 0.00
December 3296.78 0.00 0.00
       
Annual Sum or Average 1068.91 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 3296.78 0.00 0.00



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR

Timestamp: 2021-05-12 10:29:11

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.02
February 0.00 0.00 0.03
March 0.00 0.00 0.04
April 0.00 0.00 0.09
May 0.00 0.00 0.13
June 0.00 0.00 0.24
July 0.00 0.00 0.32
August 0.00 0.00 0.30
September 0.00 0.00 0.22
October 0.00 0.00 0.12
November 0.00 0.00 0.03
December 0.00 0.00 0.02
       
Annual Sum or Average 0.00 0.00 0.13
Minimum of Months 0.00 0.00 0.02
Maximum of Months 0.00 0.00 0.32



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR

Timestamp: 2021-05-12 10:29:11

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.01
February 0.00 0.00 0.01
March 0.00 0.00 0.01
April 0.00 0.00 0.04
May 0.00 0.00 0.06
June 0.00 0.00 0.15
July 0.00 0.00 0.22
August 0.00 0.00 0.21
September 0.00 0.00 0.15
October 0.00 0.00 0.08
November 0.00 0.00 0.01
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.08
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.22



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR

Timestamp: 2021-05-12 10:29:11

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.01
February 0.00 0.00 0.02
March 0.00 0.00 0.03
April 0.00 0.00 0.09
May 0.00 0.00 0.13
June 0.00 0.00 0.25
July 0.00 0.00 0.34
August 0.00 0.00 0.31
September 0.00 0.00 0.22
October 0.00 0.00 0.11
November 0.00 0.00 0.02
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.13
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.34



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR

Timestamp: 2021-05-12 10:29:11

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.01
April 0.00 0.00 0.06
May 0.00 0.00 0.11
June 0.00 0.00 0.24
July 0.00 0.00 0.31
August 0.00 0.00 0.26
September 0.00 0.00 0.16
October 0.00 0.00 0.06
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.10
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.31



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR

Timestamp: 2021-05-12 10:29:11

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.02
May 0.00 0.00 0.05
June 0.00 0.00 0.15
July 0.00 0.00 0.21
August 0.00 0.00 0.17
September 0.00 0.00 0.09
October 0.00 0.00 0.02
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.06
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.21



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR

Timestamp: 2021-05-12 10:29:11

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.05
May 0.00 0.00 0.11
June 0.00 0.00 0.25
July 0.00 0.00 0.33
August 0.00 0.00 0.28
September 0.00 0.00 0.16
October 0.00 0.00 0.04
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.10
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.33



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR

Timestamp: 2021-05-12 10:29:11

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.03
February 0.00 0.00 0.04
March 0.00 0.00 0.05
April 0.00 0.00 0.11
May 0.00 0.00 0.15
June 0.00 0.00 0.26
July 0.00 0.00 0.34
August 0.00 0.00 0.32
September 0.00 0.00 0.25
October 0.00 0.00 0.14
November 0.00 0.00 0.05
December 0.00 0.00 0.02
       
Annual Sum or Average 0.00 0.00 0.15
Minimum of Months 0.00 0.00 0.02
Maximum of Months 0.00 0.00 0.34



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR

Timestamp: 2021-05-12 10:29:11

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.01
February 0.00 0.00 0.02
March 0.00 0.00 0.02
April 0.00 0.00 0.05
May 0.00 0.00 0.09
June 0.00 0.00 0.17
July 0.00 0.00 0.24
August 0.00 0.00 0.23
September 0.00 0.00 0.18
October 0.00 0.00 0.10
November 0.00 0.00 0.03
December 0.00 0.00 0.01
       
Annual Sum or Average 0.00 0.00 0.10
Minimum of Months 0.00 0.00 0.01
Maximum of Months 0.00 0.00 0.24



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR

Timestamp: 2021-05-12 10:29:11

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.02
February 0.00 0.00 0.03
March 0.00 0.00 0.05
April 0.00 0.00 0.11
May 0.00 0.00 0.16
June 0.00 0.00 0.28
July 0.00 0.00 0.36
August 0.00 0.00 0.34
September 0.00 0.00 0.25
October 0.00 0.00 0.14
November 0.00 0.00 0.04
December 0.00 0.00 0.01
       
Annual Sum or Average 0.00 0.00 0.15
Minimum of Months 0.00 0.00 0.01
Maximum of Months 0.00 0.00 0.36



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR

Timestamp: 2021-05-12 10:29:11

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.02
April 0.00 0.00 0.08
May 0.00 0.00 0.13
June 0.00 0.00 0.26
July 0.00 0.00 0.33
August 0.00 0.00 0.29
September 0.00 0.00 0.18
October 0.00 0.00 0.07
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.12
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.33



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR

Timestamp: 2021-05-12 10:29:11

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.03
May 0.00 0.00 0.07
June 0.00 0.00 0.17
July 0.00 0.00 0.23
August 0.00 0.00 0.20
September 0.00 0.00 0.12
October 0.00 0.00 0.03
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.07
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.23



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR

Timestamp: 2021-05-12 10:29:11

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.01
April 0.00 0.00 0.07
May 0.00 0.00 0.14
June 0.00 0.00 0.28
July 0.00 0.00 0.35
August 0.00 0.00 0.31
September 0.00 0.00 0.19
October 0.00 0.00 0.06
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.12
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.35



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR

Timestamp: 2021-05-12 10:29:11

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.02
February 0.00 0.00 0.03
March 0.00 0.00 0.04
April 0.00 0.00 0.10
May 0.00 0.00 0.15
June 0.00 0.00 0.27
July 0.00 0.00 0.36
August 0.00 0.00 0.34
September 0.00 0.00 0.25
October 0.00 0.00 0.13
November 0.00 0.00 0.03
December 0.00 0.00 0.01
       
Annual Sum or Average 0.00 0.00 0.15
Minimum of Months 0.00 0.00 0.01
Maximum of Months 0.00 0.00 0.36



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR

Timestamp: 2021-05-12 10:29:11

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.01
February 0.00 0.00 0.01
March 0.00 0.00 0.01
April 0.00 0.00 0.05
May 0.00 0.00 0.09
June 0.00 0.00 0.18
July 0.00 0.00 0.27
August 0.00 0.00 0.25
September 0.00 0.00 0.18
October 0.00 0.00 0.09
November 0.00 0.00 0.01
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.10
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.27



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR

Timestamp: 2021-05-12 10:29:11

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.01
February 0.00 0.00 0.02
March 0.00 0.00 0.03
April 0.00 0.00 0.10
May 0.00 0.00 0.15
June 0.00 0.00 0.29
July 0.00 0.00 0.39
August 0.00 0.00 0.36
September 0.00 0.00 0.25
October 0.00 0.00 0.12
November 0.00 0.00 0.02
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.15
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.39



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR

Timestamp: 2021-05-12 10:29:11

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.02
April 0.00 0.00 0.08
May 0.00 0.00 0.14
June 0.00 0.00 0.28
July 0.00 0.00 0.36
August 0.00 0.00 0.32
September 0.00 0.00 0.20
October 0.00 0.00 0.07
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.12
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.36



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR

Timestamp: 2021-05-12 10:29:11

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.03
May 0.00 0.00 0.08
June 0.00 0.00 0.19
July 0.00 0.00 0.26
August 0.00 0.00 0.23
September 0.00 0.00 0.13
October 0.00 0.00 0.04
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.08
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.26



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR

Timestamp: 2021-05-12 10:29:11

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.07
May 0.00 0.00 0.14
June 0.00 0.00 0.29
July 0.00 0.00 0.38
August 0.00 0.00 0.34
September 0.00 0.00 0.20
October 0.00 0.00 0.06
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.13
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.38



Table of Contents

Report: COILLOADS

For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_FRONTROW_BOTTOMFLOOR

Timestamp: 2021-05-12 10:29:11

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.06
February 0.00 0.00 0.06
March 0.00 0.00 0.06
April 0.00 0.00 0.05
May 0.00 0.00 0.05
June 0.00 0.00 0.05
July 0.00 0.00 0.04
August 0.00 0.00 0.04
September 0.00 0.00 0.04
October 0.00 0.00 0.05
November 0.00 0.00 0.05
December 0.00 0.00 0.06
       
Annual Sum or Average 0.00 0.00 0.05
Minimum of Months 0.00 0.00 0.04
Maximum of Months 0.00 0.00 0.06



Table of Contents

Report: COILLOADS

For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_FRONTROW_BOTTOMFLOOR

Timestamp: 2021-05-12 10:29:11

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.06
February 0.00 0.00 0.06
March 0.00 0.00 0.06
April 0.00 0.00 0.05
May 0.00 0.00 0.05
June 0.00 0.00 0.05
July 0.00 0.00 0.04
August 0.00 0.00 0.04
September 0.00 0.00 0.04
October 0.00 0.00 0.05
November 0.00 0.00 0.05
December 0.00 0.00 0.06
       
Annual Sum or Average 0.00 0.00 0.05
Minimum of Months 0.00 0.00 0.04
Maximum of Months 0.00 0.00 0.06



Table of Contents

Report: COILLOADS

For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_FRONTROW_BOTTOMFLOOR

Timestamp: 2021-05-12 10:29:11

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.06
February 0.00 0.00 0.06
March 0.00 0.00 0.06
April 0.00 0.00 0.05
May 0.00 0.00 0.05
June 0.00 0.00 0.05
July 0.00 0.00 0.04
August 0.00 0.00 0.04
September 0.00 0.00 0.04
October 0.00 0.00 0.05
November 0.00 0.00 0.05
December 0.00 0.00 0.06
       
Annual Sum or Average 0.00 0.00 0.05
Minimum of Months 0.00 0.00 0.04
Maximum of Months 0.00 0.00 0.06



Table of Contents

Report: COILLOADS

For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_BACKROW_BOTTOMFLOOR

Timestamp: 2021-05-12 10:29:11

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.06
February 0.00 0.00 0.06
March 0.00 0.00 0.06
April 0.00 0.00 0.05
May 0.00 0.00 0.05
June 0.00 0.00 0.05
July 0.00 0.00 0.04
August 0.00 0.00 0.04
September 0.00 0.00 0.04
October 0.00 0.00 0.05
November 0.00 0.00 0.05
December 0.00 0.00 0.06
       
Annual Sum or Average 0.00 0.00 0.05
Minimum of Months 0.00 0.00 0.04
Maximum of Months 0.00 0.00 0.06



Table of Contents

Report: COILLOADS

For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_BACKROW_BOTTOMFLOOR

Timestamp: 2021-05-12 10:29:11

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.06
February 0.00 0.00 0.06
March 0.00 0.00 0.06
April 0.00 0.00 0.05
May 0.00 0.00 0.05
June 0.00 0.00 0.05
July 0.00 0.00 0.04
August 0.00 0.00 0.04
September 0.00 0.00 0.04
October 0.00 0.00 0.05
November 0.00 0.00 0.05
December 0.00 0.00 0.06
       
Annual Sum or Average 0.00 0.00 0.05
Minimum of Months 0.00 0.00 0.04
Maximum of Months 0.00 0.00 0.06



Table of Contents

Report: COILLOADS

For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_BACKROW_BOTTOMFLOOR

Timestamp: 2021-05-12 10:29:11

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.06
February 0.00 0.00 0.06
March 0.00 0.00 0.06
April 0.00 0.00 0.05
May 0.00 0.00 0.05
June 0.00 0.00 0.05
July 0.00 0.00 0.04
August 0.00 0.00 0.04
September 0.00 0.00 0.04
October 0.00 0.00 0.05
November 0.00 0.00 0.05
December 0.00 0.00 0.06
       
Annual Sum or Average 0.00 0.00 0.05
Minimum of Months 0.00 0.00 0.04
Maximum of Months 0.00 0.00 0.06



Table of Contents

Report: COILLOADS

For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_FRONTROW_MIDDLEFLOOR

Timestamp: 2021-05-12 10:29:11

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.06
February 0.00 0.00 0.06
March 0.00 0.00 0.06
April 0.00 0.00 0.05
May 0.00 0.00 0.05
June 0.00 0.00 0.05
July 0.00 0.00 0.04
August 0.00 0.00 0.04
September 0.00 0.00 0.04
October 0.00 0.00 0.05
November 0.00 0.00 0.05
December 0.00 0.00 0.06
       
Annual Sum or Average 0.00 0.00 0.05
Minimum of Months 0.00 0.00 0.04
Maximum of Months 0.00 0.00 0.06



Table of Contents

Report: COILLOADS

For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_FRONTROW_MIDDLEFLOOR

Timestamp: 2021-05-12 10:29:11

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.06
February 0.00 0.00 0.06
March 0.00 0.00 0.06
April 0.00 0.00 0.05
May 0.00 0.00 0.05
June 0.00 0.00 0.05
July 0.00 0.00 0.04
August 0.00 0.00 0.04
September 0.00 0.00 0.04
October 0.00 0.00 0.05
November 0.00 0.00 0.05
December 0.00 0.00 0.06
       
Annual Sum or Average 0.00 0.00 0.05
Minimum of Months 0.00 0.00 0.04
Maximum of Months 0.00 0.00 0.06



Table of Contents

Report: COILLOADS

For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_FRONTROW_MIDDLEFLOOR

Timestamp: 2021-05-12 10:29:11

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.06
February 0.00 0.00 0.06
March 0.00 0.00 0.06
April 0.00 0.00 0.05
May 0.00 0.00 0.05
June 0.00 0.00 0.05
July 0.00 0.00 0.04
August 0.00 0.00 0.04
September 0.00 0.00 0.04
October 0.00 0.00 0.05
November 0.00 0.00 0.05
December 0.00 0.00 0.06
       
Annual Sum or Average 0.00 0.00 0.05
Minimum of Months 0.00 0.00 0.04
Maximum of Months 0.00 0.00 0.06



Table of Contents

Report: COILLOADS

For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_BACKROW_MIDDLEFLOOR

Timestamp: 2021-05-12 10:29:11

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.06
February 0.00 0.00 0.06
March 0.00 0.00 0.06
April 0.00 0.00 0.05
May 0.00 0.00 0.05
June 0.00 0.00 0.05
July 0.00 0.00 0.04
August 0.00 0.00 0.04
September 0.00 0.00 0.04
October 0.00 0.00 0.05
November 0.00 0.00 0.05
December 0.00 0.00 0.06
       
Annual Sum or Average 0.00 0.00 0.05
Minimum of Months 0.00 0.00 0.04
Maximum of Months 0.00 0.00 0.06



Table of Contents

Report: COILLOADS

For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_BACKROW_MIDDLEFLOOR

Timestamp: 2021-05-12 10:29:11

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.06
February 0.00 0.00 0.06
March 0.00 0.00 0.06
April 0.00 0.00 0.05
May 0.00 0.00 0.05
June 0.00 0.00 0.05
July 0.00 0.00 0.04
August 0.00 0.00 0.04
September 0.00 0.00 0.04
October 0.00 0.00 0.05
November 0.00 0.00 0.05
December 0.00 0.00 0.06
       
Annual Sum or Average 0.00 0.00 0.05
Minimum of Months 0.00 0.00 0.04
Maximum of Months 0.00 0.00 0.06



Table of Contents

Report: COILLOADS

For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_BACKROW_MIDDLEFLOOR

Timestamp: 2021-05-12 10:29:11

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.06
February 0.00 0.00 0.06
March 0.00 0.00 0.06
April 0.00 0.00 0.05
May 0.00 0.00 0.05
June 0.00 0.00 0.05
July 0.00 0.00 0.04
August 0.00 0.00 0.04
September 0.00 0.00 0.04
October 0.00 0.00 0.05
November 0.00 0.00 0.05
December 0.00 0.00 0.06
       
Annual Sum or Average 0.00 0.00 0.05
Minimum of Months 0.00 0.00 0.04
Maximum of Months 0.00 0.00 0.06



Table of Contents

Report: COILLOADS

For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_FRONTROW_TOPFLOOR

Timestamp: 2021-05-12 10:29:11

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.06
February 0.00 0.00 0.06
March 0.00 0.00 0.06
April 0.00 0.00 0.05
May 0.00 0.00 0.05
June 0.00 0.00 0.05
July 0.00 0.00 0.04
August 0.00 0.00 0.04
September 0.00 0.00 0.04
October 0.00 0.00 0.05
November 0.00 0.00 0.05
December 0.00 0.00 0.06
       
Annual Sum or Average 0.00 0.00 0.05
Minimum of Months 0.00 0.00 0.04
Maximum of Months 0.00 0.00 0.06



Table of Contents

Report: COILLOADS

For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_FRONTROW_TOPFLOOR

Timestamp: 2021-05-12 10:29:11

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.06
February 0.00 0.00 0.06
March 0.00 0.00 0.06
April 0.00 0.00 0.05
May 0.00 0.00 0.05
June 0.00 0.00 0.05
July 0.00 0.00 0.04
August 0.00 0.00 0.04
September 0.00 0.00 0.04
October 0.00 0.00 0.05
November 0.00 0.00 0.05
December 0.00 0.00 0.06
       
Annual Sum or Average 0.00 0.00 0.05
Minimum of Months 0.00 0.00 0.04
Maximum of Months 0.00 0.00 0.06



Table of Contents

Report: COILLOADS

For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_FRONTROW_TOPFLOOR

Timestamp: 2021-05-12 10:29:11

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.06
February 0.00 0.00 0.06
March 0.00 0.00 0.06
April 0.00 0.00 0.05
May 0.00 0.00 0.05
June 0.00 0.00 0.05
July 0.00 0.00 0.04
August 0.00 0.00 0.04
September 0.00 0.00 0.04
October 0.00 0.00 0.05
November 0.00 0.00 0.05
December 0.00 0.00 0.06
       
Annual Sum or Average 0.00 0.00 0.05
Minimum of Months 0.00 0.00 0.04
Maximum of Months 0.00 0.00 0.06



Table of Contents

Report: COILLOADS

For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_BACKROW_TOPFLOOR

Timestamp: 2021-05-12 10:29:11

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.06
February 0.00 0.00 0.06
March 0.00 0.00 0.06
April 0.00 0.00 0.05
May 0.00 0.00 0.05
June 0.00 0.00 0.05
July 0.00 0.00 0.04
August 0.00 0.00 0.04
September 0.00 0.00 0.04
October 0.00 0.00 0.05
November 0.00 0.00 0.05
December 0.00 0.00 0.06
       
Annual Sum or Average 0.00 0.00 0.05
Minimum of Months 0.00 0.00 0.04
Maximum of Months 0.00 0.00 0.06



Table of Contents

Report: COILLOADS

For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_BACKROW_TOPFLOOR

Timestamp: 2021-05-12 10:29:11

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.06
February 0.00 0.00 0.06
March 0.00 0.00 0.06
April 0.00 0.00 0.05
May 0.00 0.00 0.05
June 0.00 0.00 0.05
July 0.00 0.00 0.04
August 0.00 0.00 0.04
September 0.00 0.00 0.04
October 0.00 0.00 0.05
November 0.00 0.00 0.05
December 0.00 0.00 0.06
       
Annual Sum or Average 0.00 0.00 0.05
Minimum of Months 0.00 0.00 0.04
Maximum of Months 0.00 0.00 0.06



Table of Contents

Report: COILLOADS

For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_BACKROW_TOPFLOOR

Timestamp: 2021-05-12 10:29:11

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.06
February 0.00 0.00 0.06
March 0.00 0.00 0.06
April 0.00 0.00 0.05
May 0.00 0.00 0.05
June 0.00 0.00 0.05
July 0.00 0.00 0.04
August 0.00 0.00 0.04
September 0.00 0.00 0.04
October 0.00 0.00 0.05
November 0.00 0.00 0.05
December 0.00 0.00 0.06
       
Annual Sum or Average 0.00 0.00 0.05
Minimum of Months 0.00 0.00 0.04
Maximum of Months 0.00 0.00 0.06



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_TANK_UNIT1_FRONTROW_BOTTOMFLOOR

Timestamp: 2021-05-12 10:29:11

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00
         
Annual Sum or Average 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_TANK_UNIT2_FRONTROW_BOTTOMFLOOR

Timestamp: 2021-05-12 10:29:11

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00
         
Annual Sum or Average 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_TANK_UNIT3_FRONTROW_BOTTOMFLOOR

Timestamp: 2021-05-12 10:29:11

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00
         
Annual Sum or Average 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_TANK_UNIT1_BACKROW_BOTTOMFLOOR

Timestamp: 2021-05-12 10:29:11

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00
         
Annual Sum or Average 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_TANK_UNIT2_BACKROW_BOTTOMFLOOR

Timestamp: 2021-05-12 10:29:11

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00
         
Annual Sum or Average 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_TANK_UNIT3_BACKROW_BOTTOMFLOOR

Timestamp: 2021-05-12 10:29:11

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00
         
Annual Sum or Average 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_TANK_UNIT1_FRONTROW_MIDDLEFLOOR

Timestamp: 2021-05-12 10:29:11

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00
         
Annual Sum or Average 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_TANK_UNIT2_FRONTROW_MIDDLEFLOOR

Timestamp: 2021-05-12 10:29:11

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00
         
Annual Sum or Average 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_TANK_UNIT3_FRONTROW_MIDDLEFLOOR

Timestamp: 2021-05-12 10:29:11

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00
         
Annual Sum or Average 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_TANK_UNIT1_BACKROW_MIDDLEFLOOR

Timestamp: 2021-05-12 10:29:11

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00
         
Annual Sum or Average 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_TANK_UNIT2_BACKROW_MIDDLEFLOOR

Timestamp: 2021-05-12 10:29:11

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00
         
Annual Sum or Average 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_TANK_UNIT3_BACKROW_MIDDLEFLOOR

Timestamp: 2021-05-12 10:29:11

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00
         
Annual Sum or Average 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_TANK_UNIT1_FRONTROW_TOPFLOOR

Timestamp: 2021-05-12 10:29:11

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00
         
Annual Sum or Average 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_TANK_UNIT2_FRONTROW_TOPFLOOR

Timestamp: 2021-05-12 10:29:11

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00
         
Annual Sum or Average 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_TANK_UNIT3_FRONTROW_TOPFLOOR

Timestamp: 2021-05-12 10:29:11

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00
         
Annual Sum or Average 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_TANK_UNIT1_BACKROW_TOPFLOOR

Timestamp: 2021-05-12 10:29:11

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00
         
Annual Sum or Average 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_TANK_UNIT2_BACKROW_TOPFLOOR

Timestamp: 2021-05-12 10:29:11

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00
         
Annual Sum or Average 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_TANK_UNIT3_BACKROW_TOPFLOOR

Timestamp: 2021-05-12 10:29:11

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00
         
Annual Sum or Average 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00



Table of Contents

Report: HEATING AND COOLING LOADS

For: CRAWLSPACE

Timestamp: 2021-05-12 10:29:11

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: HEATING AND COOLING LOADS

For: BREEZEWAY

Timestamp: 2021-05-12 10:29:11

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT1_FRONTROW_BOTTOMFLOOR

Timestamp: 2021-05-12 10:29:11

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 53.14 999.03
February 60.38 725.67
March 75.84 433.82
April 115.02 147.19
May 134.26 56.82
June 185.17 8.06
July 214.69 0.12
August 209.33 0.12
September 175.46 3.14
October 133.47 179.20
November 71.24 440.07
December 52.05 963.02
     
Annual Sum or Average 1480.07 3956.25
Minimum of Months 52.05 0.12
Maximum of Months 214.69 999.03



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT2_FRONTROW_BOTTOMFLOOR

Timestamp: 2021-05-12 10:29:11

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 48.48 592.61
February 48.94 428.22
March 58.22 246.88
April 80.32 93.42
May 91.90 38.34
June 123.98 5.92
July 151.37 0.29
August 148.74 0.18
September 130.65 1.31
October 105.61 100.52
November 64.56 236.59
December 48.17 546.08
     
Annual Sum or Average 1100.93 2290.35
Minimum of Months 48.17 0.18
Maximum of Months 151.37 592.61



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT3_FRONTROW_BOTTOMFLOOR

Timestamp: 2021-05-12 10:29:11

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 49.41 963.70
February 54.35 700.64
March 76.25 391.01
April 120.91 106.61
May 140.78 30.71
June 196.25 4.12
July 229.59 0.00
August 220.45 0.00
September 177.39 1.95
October 131.08 163.29
November 69.13 425.28
December 48.46 925.67
     
Annual Sum or Average 1514.05 3712.96
Minimum of Months 48.46 0.00
Maximum of Months 229.59 963.70



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT1_BACKROW_BOTTOMFLOOR

Timestamp: 2021-05-12 10:29:11

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 15.28 1385.31
February 23.59 1017.84
March 43.18 562.73
April 89.51 173.62
May 124.41 55.84
June 185.32 8.92
July 207.92 0.12
August 188.19 0.25
September 134.15 6.44
October 76.42 257.47
November 25.48 723.64
December 11.89 1433.69
     
Annual Sum or Average 1125.36 5625.85
Minimum of Months 11.89 0.12
Maximum of Months 207.92 1433.69



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT2_BACKROW_BOTTOMFLOOR

Timestamp: 2021-05-12 10:29:11

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 6.97 954.34
February 11.44 714.88
March 28.31 376.86
April 57.32 123.60
May 83.42 43.38
June 124.37 4.76
July 144.77 0.42
August 127.68 0.45
September 89.69 4.65
October 52.48 179.34
November 17.54 495.92
December 3.65 987.43
     
Annual Sum or Average 747.64 3886.04
Minimum of Months 3.65 0.42
Maximum of Months 144.77 987.43



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT3_BACKROW_BOTTOMFLOOR

Timestamp: 2021-05-12 10:29:11

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 5.58 1267.93
February 16.10 955.71
March 43.69 492.05
April 94.51 126.11
May 130.76 33.13
June 196.35 3.57
July 222.46 0.00
August 198.86 0.00
September 134.94 1.67
October 72.51 214.55
November 22.66 662.30
December 1.34 1319.23
     
Annual Sum or Average 1139.75 5076.25
Minimum of Months 1.34 0.00
Maximum of Months 222.46 1319.23



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT1_FRONTROW_MIDDLEFLOOR

Timestamp: 2021-05-12 10:29:11

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 73.69 448.30
February 81.07 320.23
March 100.61 169.22
April 139.70 56.65
May 155.97 18.95
June 199.99 2.62
July 229.07 0.01
August 228.17 0.05
September 196.06 0.09
October 157.54 75.89
November 96.07 173.20
December 73.08 437.64
     
Annual Sum or Average 1731.01 1702.86
Minimum of Months 73.08 0.01
Maximum of Months 229.07 448.30



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT2_FRONTROW_MIDDLEFLOOR

Timestamp: 2021-05-12 10:29:11

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 77.12 157.26
February 76.15 108.51
March 88.69 65.44
April 103.98 21.37
May 113.27 8.09
June 138.40 0.99
July 164.66 0.11
August 166.60 0.08
September 152.63 0.01
October 130.83 23.17
November 95.39 63.24
December 78.26 144.07
     
Annual Sum or Average 1385.97 592.34
Minimum of Months 76.15 0.01
Maximum of Months 166.60 157.26



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT3_FRONTROW_MIDDLEFLOOR

Timestamp: 2021-05-12 10:29:11

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 71.23 442.52
February 76.44 309.86
March 102.73 147.46
April 148.79 35.29
May 166.04 10.27
June 213.80 0.39
July 245.00 0.00
August 240.48 0.00
September 200.38 0.09
October 157.17 61.84
November 94.77 161.73
December 69.19 423.18
     
Annual Sum or Average 1786.00 1592.64
Minimum of Months 69.19 0.00
Maximum of Months 245.00 442.52



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT1_BACKROW_MIDDLEFLOOR

Timestamp: 2021-05-12 10:29:11

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 25.54 702.15
February 34.74 482.91
March 61.68 228.23
April 111.17 72.74
May 146.08 22.96
June 200.39 2.56
July 222.51 0.01
August 207.06 0.06
September 153.52 0.78
October 96.40 119.04
November 39.88 328.57
December 22.84 751.92
     
Annual Sum or Average 1321.81 2711.94
Minimum of Months 22.84 0.01
Maximum of Months 222.51 751.92



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT2_BACKROW_MIDDLEFLOOR

Timestamp: 2021-05-12 10:29:11

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 22.41 302.34
February 27.61 212.74
March 53.37 124.40
April 79.36 40.65
May 103.95 10.01
June 139.21 0.76
July 158.14 0.17
August 145.51 0.12
September 110.01 0.57
October 71.72 55.71
November 38.93 163.64
December 18.82 335.50
     
Annual Sum or Average 969.03 1246.61
Minimum of Months 18.82 0.12
Maximum of Months 158.14 335.50



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT3_BACKROW_MIDDLEFLOOR

Timestamp: 2021-05-12 10:29:11

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 23.48 677.21
February 30.82 466.26
March 64.03 197.85
April 118.91 38.74
May 155.78 10.84
June 213.72 0.67
July 238.07 0.00
August 218.94 0.00
September 157.12 0.30
October 93.69 91.77
November 40.89 311.47
December 15.25 676.16
     
Annual Sum or Average 1370.70 2471.27
Minimum of Months 15.25 0.00
Maximum of Months 238.07 677.21



Table of Contents

Report: HEATING AND COOLING LOADS

For: ATTIC

Timestamp: 2021-05-12 10:29:11

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT3_BACKROW_TOPFLOOR

Timestamp: 2021-05-12 10:29:11

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 11.34 1069.65
February 21.61 754.15
March 54.30 336.79
April 114.48 73.64
May 155.15 16.89
June 223.44 1.55
July 255.58 0.00
August 235.12 0.00
September 165.84 0.32
October 91.80 154.88
November 30.52 521.86
December 3.46 1095.81
     
Annual Sum or Average 1362.66 4025.53
Minimum of Months 3.46 0.00
Maximum of Months 255.58 1095.81



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT3_FRONTROW_TOPFLOOR

Timestamp: 2021-05-12 10:29:11

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 51.70 789.33
February 58.17 552.95
March 83.43 265.59
April 135.45 60.84
May 161.80 16.03
June 221.81 1.63
July 259.49 0.00
August 250.15 0.00
September 199.29 0.31
October 143.17 117.15
November 74.01 309.48
December 50.53 771.05
     
Annual Sum or Average 1689.00 2884.37
Minimum of Months 50.53 0.00
Maximum of Months 259.49 789.33



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT1_FRONTROW_TOPFLOOR

Timestamp: 2021-05-12 10:29:11

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 54.24 816.21
February 62.85 571.29
March 81.53 296.23
April 128.08 90.25
May 153.22 32.91
June 209.81 5.21
July 244.35 0.03
August 238.70 0.04
September 195.81 0.26
October 144.92 131.43
November 76.06 335.04
December 53.13 799.84
     
Annual Sum or Average 1642.70 3078.74
Minimum of Months 53.13 0.03
Maximum of Months 244.35 816.21



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT2_BACKROW_TOPFLOOR

Timestamp: 2021-05-12 10:29:11

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 12.11 735.82
February 17.54 509.12
March 42.38 245.77
April 77.57 75.83
May 106.29 25.10
June 151.04 1.90
July 177.27 0.04
August 163.37 0.13
September 120.25 0.31
October 70.93 116.40
November 26.83 354.01
December 8.86 780.53
     
Annual Sum or Average 974.45 2844.98
Minimum of Months 8.86 0.04
Maximum of Months 177.27 780.53



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT2_FRONTROW_TOPFLOOR

Timestamp: 2021-05-12 10:29:11

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 52.55 430.20
February 55.46 302.97
March 70.11 162.76
April 96.01 52.70
May 112.15 21.39
June 149.19 2.05
July 180.97 0.05
August 178.20 0.05
September 153.21 0.02
October 119.97 67.31
November 73.45 166.67
December 53.69 405.63
     
Annual Sum or Average 1294.94 1611.81
Minimum of Months 52.55 0.02
Maximum of Months 180.97 430.20



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT1_BACKROW_TOPFLOOR

Timestamp: 2021-05-12 10:29:11

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 18.04 1143.20
February 28.68 808.19
March 52.91 384.31
April 107.16 102.37
May 146.81 35.78
June 211.44 4.55
July 240.60 0.02
August 223.88 0.03
September 163.07 1.10
October 94.36 189.34
November 32.12 562.54
December 15.75 1219.65
     
Annual Sum or Average 1334.82 4451.09
Minimum of Months 15.75 0.02
Maximum of Months 240.60 1219.65